Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2024-07-03 12:26:21
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31562.50 | 681.40 | 681.40 |
Net Site Energy | 31562.50 | 681.40 | 681.40 |
Total Source Energy | 98579.08 | 2128.20 | 2128.20 |
Net Source Energy | 98579.08 | 2128.20 | 2128.20 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 662.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2284.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1007.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2821.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 970.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 162.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7179.70 |
Humidification | 351.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.73 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 392.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 30900.30 | 662.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9590.60 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 662.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2284.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 1007.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 56.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2821.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 970.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 162.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7179.70 |
Humidification | General | 351.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.73 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 392.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 662.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2284.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 1007.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2821.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 970.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 162.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7179.70 |
Humidification | Unassigned | 351.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.73 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 392.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 150.74 | 14.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 667.10 | 14.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 150.74 | 14.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 667.10 | 14.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 30900.303 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 30900.303 | 100.00 |
Total On-Site and Utility Electric Sources | 30900.303 | 100.00 |
Total Electricity End Uses | 30900.303 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9590.60 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9590.60 | 100.00 |
Total Water End Uses | 9590.60 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.67 |
Time Setpoint Not Met During Occupied Cooling | 216.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5143.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS SZVAV FAN | AIRLOOP DATACENTER BASEMENT SYS11 FAN | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 11.6510 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 11.6510 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 11.6510 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.6510 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 11.6510 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.6510 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 11.6510 | 18.58 | 484.4232 | |
Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.6100 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-AUG-15:00 | 03-JAN-05:19 | - | - | - | - | - | - | - | - | - | - | 29-SEP-09:00 |
Heating | 0.00 | 858886.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 412099.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235096.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 241099.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 84272.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 48088.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31552.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2320480.48 | 858886.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 858886.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 412099.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 241099.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 84272.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 48088.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 31552.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 717.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7233.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17769.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3190.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8307.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8934.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3072.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 516.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1112.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1244.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 97861.26 | 717.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 15.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 156.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 192.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 66.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 11.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 24.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2112.70 | 15.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 15.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 156.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 192.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 66.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 11.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 24.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2112.70 | 15.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 7.25 | 0.292179 | 0.300000 | 2.17 |
DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | 32.02 | 0.018652 | 0.500000 | 16.01 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 7.49 | 0.254031 | 0.300000 | 2.25 | 0.677415 | 0.500000 | 0.001500 | 0.000192 | 2.25 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 70.74 | 0.268867 | 0.300000 | 21.22 | 0.716980 | 0.500000 | 0.001417 | 0.003847 | 21.22 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 7.93 | 0.239861 | 0.300000 | 2.38 | 0.639629 | 0.500000 | 0.001588 | 0.001007 | 4.92 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.32 | 0.180414 | 0.300000 | 0.397121 | 0.481104 | 0.500000 | 0.002112 | 0.000141 | 0.688876 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.82 | 0.084608 | 0.300000 | 0.545714 | 0.300000 | 0.500000 | 0.004503 | 0.000106 | 0.545714 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 2.09 | 0.114349 | 0.300000 | 0.626570 | 0.304931 | 0.500000 | 0.003332 | 0.000178 | 0.871377 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 2.23 | 0.068941 | 0.300000 | 0.669723 | 0.300000 | 0.500000 | 0.005526 | 0.000099 | 0.669723 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 12.95 | 0.184373 | 0.300000 | 3.89 | 0.491661 | 0.500000 | 0.002066 | 0.002640 | 12.95 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 18.48 | 0.300000 | 0.500000 | 0.004576 | 0.001801 | 8.84 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 20.31 | 0.117592 | 0.300000 | 6.09 | 0.313578 | 0.500000 | 0.003240 | 0.002710 | 13.30 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 20.16 | 0.076359 | 0.300000 | 6.05 | 0.300000 | 0.500000 | 0.004990 | 0.001659 | 8.14 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.66 | 0.144167 | 0.300000 | 0.496966 | 0.384446 | 0.500000 | 0.002643 | 0.000337 | 1.66 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.85 | 0.083091 | 0.300000 | 0.555675 | 0.300000 | 0.500000 | 0.004585 | 0.000228 | 1.12 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 2.27 | 0.105203 | 0.300000 | 0.681040 | 0.300000 | 0.500000 | 0.003622 | 0.000345 | 1.69 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 2.16 | 0.071103 | 0.300000 | 0.649361 | 0.300000 | 0.500000 | 0.005358 | 0.000215 | 1.05 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 21955.78 | 0.000192 | 442.94 | |
CORE_MID VAV BOX REHEAT COIL | 439702.27 | 0.003847 | 9968.10 | |
CORE_TOP VAV BOX REHEAT COIL | 115085.39 | 0.001007 | 2691.21 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 16088.60 | 0.000141 | 376.12 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12164.46 | 0.000106 | 280.82 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 20329.75 | 0.000178 | 475.14 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11317.23 | 0.000099 | 245.84 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 301748.55 | 0.002640 | 7049.35 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 205894.73 | 0.001801 | 4809.82 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 309748.23 | 0.002710 | 7236.08 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 189623.11 | 0.001659 | 4429.99 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 38566.05 | 0.000337 | 900.81 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 26010.55 | 0.000228 | 607.53 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 39397.37 | 0.000345 | 920.22 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 24553.21 | 0.000215 | 573.51 | |
VAV_BOT WITH REHEAT HEATING COIL | 25920.05 | 0.000227 | 456.48 | |
VAV_MID WITH REHEAT HEATING COIL | 117161.03 | 0.001025 | 2108.55 | |
VAV_TOP WITH REHEAT HEATING COIL | 6623.66 | 0.000058 | 120.66 | |
CAV_BAS HEATING COIL | 77504.93 | 0.000875 | 2622.54 | 100000.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 551845.01 | 0.000875 | 2622.54 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.749591 |
DATACENTER_MID_ZN_6 DIRECT AIR | 7.17 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.740962 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 7.48 | 4.49 | 14.95 | 4.49 | 12.68 | 12.68 | 0.300000 | 0.353782 | 12.68 |
VAV_MID WITH REHEAT | 71.32 | 42.79 | 142.64 | 59.95 | 116.07 | 116.07 | 0.300000 | 0.516480 | 116.07 |
VAV_TOP WITH REHEAT | 7.94 | 4.76 | 15.87 | 10.44 | 14.46 | 14.46 | 0.300000 | 0.722152 | 14.46 |
CAV_BAS | 2.17 | 2.17 | 7.25 | 2.17 | 7.25 | 7.25 | 1.00 | 0.300000 | 7.25 |
AIRLOOP DATACENTER BASEMENT | 16.01 | 16.01 | 32.02 | 16.01 | 32.02 | 32.02 | 1.00 | 0.499997 | 32.02 |
AIRLOOP DATACENTER BOT | 0.749591 | 0.749591 | 0.749591 | 0.749591 | 0.749591 | 0.749591 | 1.00 | 1.00 | 0.749591 |
AIRLOOP DATACENTER MID | 7.17 | 7.17 | 7.17 | 7.17 | 7.17 | 7.17 | 1.00 | 1.00 | 7.17 |
AIRLOOP DATACENTER TOP | 0.740962 | 0.740962 | 0.740962 | 0.740962 | 0.740962 | 0.740962 | 1.00 | 1.00 | 0.740962 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 12.68 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 116.07 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 14.46 | |
CAV_BAS_OA_CONTROLLER | 7.25 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 32.02 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.749591 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 7.17 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.740962 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.17 | 6.67 | 11.08 | 0.008697 | 0.008500 | 223005.39 | 0.007965 | 12.68 |
VAV_MID WITH REHEAT COOLING COIL | 25.28 | 6.67 | 11.08 | 0.008707 | 0.008500 | 2060171.37 | 0.073585 | 116.07 |
VAV_TOP WITH REHEAT COOLING COIL | 25.02 | 6.67 | 11.08 | 0.008674 | 0.008500 | 250714.82 | 0.008955 | 14.46 |
CAV_BAS COOLING COIL | 24.17 | 6.67 | 11.07 | 0.008792 | 0.008500 | 118017.07 | 0.004215 | 7.25 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 27.04 | 6.67 | 15.03 | 0.008530 | 0.008500 | 450969.37 | 0.016108 | 32.02 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 12.68 |
VAV_MID WITH REHEAT FAN | 116.07 |
VAV_TOP WITH REHEAT FAN | 14.46 |
CAV_BAS SZVAV FAN | 7.25 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | 32.02 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007965 | 0.000060 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000227 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.073585 | 0.000006 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.001025 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.008955 | 0.000053 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000058 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | Design Size Minimum Supply Air Temperature [C] | User-Specified Minimum Supply Air Temperature [C] | User-Specified Maximum Supply Air Temperature [C] | User-Specified Nominal Cooling Capacity [W] | Design Size Maximum Supply Air Temperature [C] | |
CAV_BAS_UNITARY_PACKAGE_DX | 7.25 | 7.25 | 7.25 | 2.17 | 118017.07 | 100000.00 | 1.00 | 5.33 | 12.89 | 32.11 | ||
AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | 32.02 | 32.02 | 32.02 | 16.01 | 450969.37 | 100000.00 | 1.00 | 15.89 | 29.11 | |||
AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | 0.749591 | 0.749591 | 0.749591 | 0.749591 | 25841.84 | 1.00 | 12408.39 | 29.11 | ||||
AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | 7.17 | 7.17 | 7.17 | 7.17 | 247091.87 | 1.00 | 118660.02 | 29.11 | ||||
AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | 0.740962 | 0.740962 | 0.740962 | 0.740962 | 25543.57 | 1.00 | 12265.55 | 29.11 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000125 | 0.000037 | 96450.70 | 100000.00 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | 0.749591 | 1289.03 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | 7.17 | 12326.81 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | 0.740962 | 1274.19 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
AIRLOOP DATACENTER BOT COOLING COIL | 0.749590 | 0.374795 | 0.499727 | 12408.39 | 6204.19 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER MID COOLING COIL | 7.17 | 3.58 | 4.78 | 118660.02 | 59330.01 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.740960 | 0.370481 | 0.493973 | 12265.55 | 6132.77 | 0.800660 | 0.800660 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BOT HEATING COIL | 25841.84 |
AIRLOOP DATACENTER MID HEATING COIL | 247091.87 |
AIRLOOP DATACENTER TOP HEATING COIL | 25543.57 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.110828 | 22837.48 | |
HEATSYS1 PUMP | 0.018563 | 5590.43 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.110828 | 13.30 |
HEATSYS1 | 0.018563 | 2.23 |
COOLSYS1_SUPPLY | 0.110828 | 13.30 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.110828 | 0.110828 | 465199.11 | 6.67 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2121890.02 | 2121890.02 | 0.018563 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.055414 | 10540.55 |
COOLSYS1 CHILLER2 PUMP | 0.055414 | 10540.55 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.110828 | 0.055955 | 1566591.00 | 1566628.98 | 0.078514 |
COOLSYS1 CHILLER2 | 0.110828 | 0.055955 | 1566591.00 | 1566628.98 | 0.078514 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.157028 | 18.84 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.157028 | 54755.79 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 64.48 | 1876977.00 | 12.90 | 234622.12 |
TOWERWATERSYS COOLTOWER 2 | 64.48 | 1876977.00 | 12.90 | 234622.12 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 11.651 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 16.493 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 11.651 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 496.074 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 32383.100 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 32383.100 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 9130.649 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 9130.649 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
26 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
27 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
35 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
47 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
48 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
49 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
50 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
51 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
52 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
53 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
54 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
55 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
56 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
57 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
58 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
59 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
60 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
61 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
62 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
63 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
64 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
65 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
66 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
67 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
68 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
69 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
70 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
71 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
72 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
73 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
74 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
75 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
76 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
77 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
78 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
79 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
80 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
81 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
82 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
83 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
84 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
85 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
86 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
87 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
88 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
89 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
90 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
91 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
92 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
93 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
94 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
95 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
96 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
97 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
98 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
99 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
100 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
101 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
102 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
103 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
104 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
105 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
106 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
107 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
108 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
109 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
110 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
111 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
112 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
113 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
114 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
115 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
116 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
117 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
118 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
119 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
120 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
121 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_1.22_SHGC_EAST_0.34 | 35 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.341 | ||
2 | WINDOW_U_1.22_SHGC_SOUTH_0.34 | 36 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.341 | ||
3 | WINDOW_U_1.22_SHGC_WEST_0.34 | 37 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.341 | ||
4 | WINDOW_U_1.22_SHGC_NORTH_0.34 | 38 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.341 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.17779 | 0.27613 | 0.27613 | 0.37400 | 0.14055 | 0.18699 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.17779 | 0.27613 | 0.27613 | 0.37400 | 0.14055 | 0.18699 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.17779 | 0.27613 | 0.27613 | 0.37400 | 0.14055 | 0.18699 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.17779 | 0.27613 | 0.27613 | 0.37400 | 0.14055 | 0.18699 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone BASEMENT | 1.2500 |
3 | Zone CORE_BOTTOM | 1.2500 |
4 | Zone CORE_MID | 1.2500 |
5 | Zone CORE_TOP | 1.2500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.2500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.2500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.2500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone BASEMENT | 1.1500 |
3 | Zone CORE_BOTTOM | 1.1500 |
4 | Zone CORE_MID | 1.1500 |
5 | Zone CORE_TOP | 1.1500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.1500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.1500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.1500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 85212.82115 | 97994.74432 | 6.30322 | 7.24871 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 3.80000 | 5.05843E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 88029.89623 | 101234.38066 | 6.51083 | 7.48746 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 831908.28718 | 956694.53026 | 61.51551 | 70.74284 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 185808.08445 | 232260.10557 | 13.37620 | 16.72025 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 92401.87764 | 106262.15928 | 6.89546 | 7.92977 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30000 | 8.23349E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 53572.49705 | 66965.62131 | 3.93840 | 4.92300 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 15425.13994 | 17738.91093 | 1.15108 | 1.32374 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 31.30000 | 8.23349E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 7486.30350 | 9357.87937 | 0.55110 | 0.68888 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 21197.07779 | 24376.63946 | 1.58178 | 1.81905 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 25.84133 | 8.22486E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 5465.64512 | 6832.05640 | 0.40283 | 0.50354 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 24337.58694 | 27988.22498 | 1.81614 | 2.08857 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 30.85500 | 8.23278E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 9451.66100 | 11814.57625 | 0.69710 | 0.87138 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 26013.92620 | 29916.01513 | 1.94123 | 2.23241 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 30.52867 | 8.23226E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 3820.34835 | 4775.43543 | 0.28042 | 0.35053 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 145142.63563 | 166914.03097 | 10.83098 | 12.45562 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30000 | 8.23349E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 140140.73106 | 175175.91382 | 10.36250 | 12.95313 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 215384.98853 | 247692.73681 | 16.07254 | 18.48342 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 26.40500 | 8.22575E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 95611.29528 | 119514.11909 | 7.07193 | 8.83992 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 236665.76167 | 272165.62592 | 17.66064 | 20.30973 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.92917 | 8.23290E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 143846.99705 | 179808.74631 | 10.63807 | 13.29758 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 234868.84108 | 270099.16724 | 17.52647 | 20.15545 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 88071.54283 | 110089.42854 | 6.51154 | 8.13942 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 17506.28704 | 20132.23009 | 1.30637 | 1.50232 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30000 | 8.23349E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 17903.07255 | 22378.84069 | 1.32524 | 1.65655 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 21584.05433 | 24821.66248 | 1.61065 | 1.85225 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 26.65717 | 8.22614E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 12073.63560 | 15092.04450 | 0.89389 | 1.11737 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 26453.55104 | 30421.58370 | 1.97403 | 2.27013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00333 | 8.23302E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 18288.24855 | 22860.31069 | 1.35388 | 1.69235 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 25223.15688 | 29006.63041 | 1.88221 | 2.16454 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 11398.26891 | 14247.83614 | 0.84371 | 1.05464 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8734.66227 | 10044.86161 | 0.65182 | 0.74959 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 29.16400 | 8.23009E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 3.80000 | 5.05843E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 83528.25277 | 96057.49069 | 6.23326 | 7.16825 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 28.94150 | 8.22975E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 3.80000 | 5.05843E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8634.11501 | 9929.23226 | 0.64431 | 0.74096 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 29.16400 | 8.23009E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 3.80000 | 5.05843E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 373073.67190 | 429034.72268 | 27.83980 | 32.01577 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 23.20100 | 8.22076E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 3.80000 | 5.05843E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 184874.10 | 12.67833 | 12.67833 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 22926.80 | 3.49214 | 3.49214 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1707468.94 | 116.07470 | 116.07470 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 215800.32 | 59.95030 | 59.95030 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 208409.69 | 14.46219 | 14.46219 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 21900.48 | 10.44391 | 10.44391 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 |
7 | CAV_BAS | Cooling | Sensible | 97102.72 | 7.24871 | 7.24871 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 40347.70 | 1.20016 | 1.20016 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 423735.55 | 32.01597 | 32.01597 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 10170.78 | 0.33839 | 0.33839 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 9929.73 | 0.74959 | 0.74959 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 469.85 | 1.56323E-002 | 1.56323E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 94945.95 | 7.16825 | 7.16825 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 4698.48 | 0.15632 | 0.15632 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 9815.89 | 0.74096 | 0.74096 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 469.85 | 1.56323E-002 | 1.56323E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 7.24871 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.29218 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 2.17461 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.48746 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25403 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.24624 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67742 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49982E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.92079E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.24624 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21955.78038 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.92079E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 442.93681 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 70.74284 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26887 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 21.22285 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71698 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.41706E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.84671E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 21.22285 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 439702.26939 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.84671E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 9968.10029 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.92977 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23986 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.37893 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63963 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.58842E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00682E-003 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.92300 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 115085.38958 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00682E-003 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2691.20719 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.32374 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18041 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.39712 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48110 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.11181E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.40750E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.68888 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16088.60064 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.40750E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 376.12317 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.81905 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.46075E-002 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.54571 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.50315E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.06420E-004 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54571 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12164.45655 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.06420E-004 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 280.82456 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.08857 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11435 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.62657 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30493 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.33190E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.77854E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.87138 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20329.75486 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.77854E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 475.13646 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.23241 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.89412E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.66972 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.52645E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.90080E-005 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.66972 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11317.22611 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.90080E-005 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 245.83560 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.95313 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18437 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.88594 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49166 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06646E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.63983E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 12.95313 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 301748.55024 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.63983E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7049.35217 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.48342 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.57567E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.80126E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.83992 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 205894.73095 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.80126E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4809.81979 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 20.30973 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11759 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.09292 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31358 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.24002E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.70981E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 13.29758 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 309748.23012 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.70981E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7236.07830 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 20.15545 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.63590E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.04663 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.98959E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.65891E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.13942 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 189623.11421 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.65891E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4429.99075 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.65655 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14417 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.49697 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38445 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.64276E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.37393E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.65655 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 38566.04586 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.37393E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 900.81174 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.85225 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.30909E-002 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.55567 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.58534E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.27552E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.11737 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26010.55045 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.27552E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 607.52704 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.27013 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10520 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.68104 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.62156E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.44665E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.69235 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 39397.36832 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.44665E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 920.21645 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.16454 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.11030E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.64936 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.35843E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.14802E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.05464 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24553.21264 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.14802E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 573.50715 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.74959 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.16825 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.74096 |
215 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 32.01577 |
216 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 1.86522E-002 |
217 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
218 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 16.00788 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.47561 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.48537 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 14.95122 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.48537 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 12.67833 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 12.67833 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.35378 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 71.32228 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 42.79337 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 142.64456 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 59.95030 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 116.07470 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 116.07470 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.51648 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.93662 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.76197 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 15.87325 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 10.44391 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 14.46219 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 14.46219 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.72215 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.17461 |
244 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.17461 |
245 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.24871 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.17461 |
247 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.24871 |
248 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 7.24871 |
249 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.30000 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 16.00788 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 16.00788 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 32.01577 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 16.00788 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 32.01597 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 32.01597 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.50000 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.74959 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.74959 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.74959 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.74959 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.74959 |
264 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.74959 |
265 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.16825 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.16825 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.16825 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 7.16825 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.16825 |
272 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 7.16825 |
273 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
274 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.74096 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.74096 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.74096 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.74096 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.74096 |
280 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.74096 |
281 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
282 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
283 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 12.67833 |
284 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 116.07470 |
285 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 14.46219 |
286 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 7.24871 |
287 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 32.01597 |
288 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.74959 |
289 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 7.16825 |
290 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.74096 |
291 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 12.67833 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.16818 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.07712 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.69704E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 223005.39338 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.96524E-003 |
299 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 12.67833 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 25920.05195 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.26760E-004 |
302 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 456.48107 |
303 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 12.67833 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.96524E-003 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.97836E-005 |
306 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.26760E-004 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 116.07470 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.27613 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.07715 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.70666E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2060171.37268 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.35845E-002 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 116.07470 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 117161.02728 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02498E-003 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2108.54943 |
319 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 116.07470 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.35845E-002 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.47134E-006 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.02498E-003 |
323 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 14.46219 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.02398 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.08471 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.67363E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 250714.82364 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.95495E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 14.46219 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 6623.65742 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.79466E-005 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 120.66496 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 14.46219 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.95495E-003 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.31762E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.79466E-005 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.24871 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.24871 |
342 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.24871 |
343 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.24871 |
344 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.17461 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.16944 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.06776 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.79218E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 118017.07229 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.21530E-003 |
352 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.24871 |
353 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 118017.07229 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 77504.93288 |
355 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
356 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
357 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.54389 |
358 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
359 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
360 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Minimum Supply Air Temperature [C] | 5.33223 |
361 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 12.88890 |
362 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 32.11110 |
363 | Fan:VariableVolume | CAV_BAS SZVAV FAN | Design Size Maximum Flow Rate [m3/s] | 7.24871 |
364 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 32.01597 |
365 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
366 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 32.01597 |
367 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 32.01597 |
368 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 32.01597 |
369 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 16.00798 |
370 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.04347 |
371 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
372 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 15.02824 |
373 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.52978E-003 |
374 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
375 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Coil Load [W] | 450969.36886 |
376 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.61076E-002 |
377 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 32.01597 |
378 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 450969.36886 |
379 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Capacity [W] | 551845.01379 |
380 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
381 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
382 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.54389 |
383 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
384 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
385 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 15.88890 |
386 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 29.11110 |
387 | Fan:VariableVolume | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Design Size Maximum Flow Rate [m3/s] | 32.01597 |
388 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.25440E-004 |
389 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
390 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
391 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.74959 |
393 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
394 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.74959 |
395 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1289.02515 |
396 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.74959 |
397 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.74959 |
398 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.74959 |
399 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.74959 |
400 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.74959 |
401 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.37480 |
402 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.49973 |
403 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 12408.39000 |
404 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6204.19500 |
405 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
406 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
407 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 12408.39000 |
408 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25841.84456 |
409 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
410 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
411 | Coil:Heating:Fuel | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Nominal Capacity [W] | 25841.84456 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.16825 |
413 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
414 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.16825 |
415 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 12326.80511 |
416 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.16825 |
417 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.16825 |
418 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.16825 |
419 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 7.16825 |
420 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.16825 |
421 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.58413 |
422 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.77883 |
423 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 118660.02000 |
424 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 59330.01000 |
425 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
426 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
427 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 118660.02000 |
428 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 247091.87013 |
429 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
430 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
431 | Coil:Heating:Fuel | AIRLOOP DATACENTER MID HEATING COIL | Design Size Nominal Capacity [W] | 247091.87013 |
432 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.74096 |
433 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
434 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.74096 |
435 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1274.18734 |
436 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.74096 |
437 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.74096 |
438 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.74096 |
439 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.74096 |
440 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.74096 |
441 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.37048 |
442 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.49397 |
443 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 12265.55000 |
444 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6132.77500 |
445 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
446 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
447 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 12265.55000 |
448 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25543.57028 |
449 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
450 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
451 | Coil:Heating:Fuel | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Nominal Capacity [W] | 25543.57028 |
452 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.11083 |
453 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 22837.48220 |
454 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.11083 |
455 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 13.29931 |
456 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.11083 |
457 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.11083 |
458 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 465199.10507 |
459 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 6.67000 |
460 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.85632E-002 |
461 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.22759 |
462 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.85632E-002 |
463 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 5590.42652 |
464 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
465 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2121890.01697 |
466 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2121890.02000 |
467 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.85632E-002 |
468 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.11083 |
469 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 13.29931 |
470 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 5.54138E-002 |
471 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 10540.54531 |
472 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 5.54138E-002 |
473 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 10540.54531 |
474 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.11083 |
475 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.59550E-002 |
476 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1566590.99633 |
477 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1566628.97500 |
478 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 7.85139E-002 |
479 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.11083 |
480 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.59550E-002 |
481 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1566590.99633 |
482 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1566628.97500 |
483 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 7.85139E-002 |
484 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
485 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
486 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
487 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
488 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
489 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.15703 |
490 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 18.84334 |
491 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.15703 |
492 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 54755.79386 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 64.48011 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1876976.99718 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 12.89602 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 234622.12465 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 64.48011 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1876976.99718 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 12.89602 |
500 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 234622.12465 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 20845.57 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 417220.08 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 109178.92 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 15262.91 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11540.82 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 19286.43 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10740.57 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 286263.31 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 195328.59 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 293852.49 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 179891.95 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 36586.93 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 24675.75 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 37375.59 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 23293.20 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 22728.69 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 106895.81 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 6176.63 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94837.96 |
20 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | 94837.96 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 288275.22 | 207095.81 | 81179.41 | 0.72 | 35252.29 | 357.55 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2649949.66 | 1900700.64 | 749249.01 | 0.72 | 323701.90 | 3283.16 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 326547.99 | 235220.29 | 91327.70 | 0.72 | 39970.64 | 405.40 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 161137.92 | 117084.20 | 44053.73 | 0.73 | 20511.69 | 208.04 |
5 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | 566788.97 | 433225.10 | 133563.87 | 0.76 | 55277.73 | 560.66 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | 11820.9 | 9.16 | 9.16 | |||
2 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | 113042.2 | 10.40 | 10.40 | |||
3 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | 11684.9 | 9.16 | 9.16 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 6.37 | 21.74 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 6.37 | 21.74 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.34 | N/A | 6.926 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.34 | N/A | 6.926 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.34 | N/A | 6.926 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.34 | N/A | 6.926 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.34 | N/A | 6.926 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.34 | N/A | 6.926 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.34 | N/A | 6.926 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.34 | N/A | 6.926 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.34 | N/A | 6.926 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.34 | N/A | 6.926 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.34 | N/A | 6.926 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.34 | N/A | 6.926 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.34 | N/A | 6.926 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.34 | N/A | 6.926 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.34 | N/A | 6.926 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.34 | N/A | 6.926 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.34 | N/A | 6.926 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.34 | N/A | 6.926 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.34 | N/A | 6.926 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.34 | N/A | 6.926 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.34 | N/A | 6.926 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.34 | N/A | 6.926 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.34 | N/A | 6.926 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.34 | N/A | 6.926 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2088978068 | 0.1821657195 | Pass | Pass | 0.4664402119 | 2.1857397423 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.4591151713E-002 | 0.1113243617 | Pass | Pass | 2.1474237017E-002 | 0.1450778739 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 7.0793123154E-003 | 5.9757678918E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.6237591423E-002 | 5.8201159490E-002 | Pass | Pass | 2.3240678445E-002 | 0.1510147910 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.8417036871E-002 | 0.1184243891 | Pass | Pass | 2.0734412506E-002 | 0.1405468399 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1494276251 | 0.2915552137 | Pass | Pass | 2.2911234253E-002 | 0.1499980641 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1550233870 | 0.2173794944 | Pass | Pass | 2.0694798232E-002 | 0.1409037619 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1148584559 | 0.2131961023 | Pass | Pass | 2.2616602624E-002 | 0.1489881105 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.0153223353E-002 | 6.1464743341E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1087125676 | 0.1847493647 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1390329309 | 0.1581921922 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 7.2793458898E-002 | 8.6720618492E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.5105156331E-002 | 8.7791765000E-002 | Pass | Pass | 1.4610032262E-002 | 0.1067996394 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1092775376 | 0.1807209022 | Pass | Pass | 1.3269439323E-002 | 7.1786304281E-002 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1389866630 | 0.1542111613 | Pass | Pass | 3.7030798837E-002 | 0.2275318015 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.4448024259E-002 | 8.3455288455E-002 | Pass | Pass | 2.6657585652E-002 | 0.1606773893 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.2585592615E-002 | 2.3984365414E-002 | Pass | Pass | 2.4211690065E-002 | 0.1465239825 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.7777159782E-003 | 7.9425715365E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.6139666180E-002 | 7.2866710849E-002 | Pass | Pass | 3.3414851655E-002 | 0.1900027547 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.5276634433E-006 | 1.8348013578E-006 | Pass | Pass | 6.6021321602E-003 | 4.9985748613E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.7209137183E-006 | 2.4030758373E-006 | Pass | Pass | 0.1943250597 | 0.9356087305 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.1957630774E-002 | 1.9679820692E-002 | Pass | Pass | 2.6713454358E-002 | 3.4560969906E-002 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.7895725387E-003 | 3.7685077048E-003 | Pass | Pass | 3.1308229764E-004 | 4.2886978634E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 9498.63 | 70.86 | 0.00 | 31829.94 | 16077.88 | 57477.34 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_1.22_SHGC_NORTH_0.34 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_1.22_SHGC_NORTH_0.34 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_1.22_SHGC_NORTH_0.34 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_1.22_SHGC_NORTH_0.34 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_1.22_SHGC_NORTH_0.34 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_1.22_SHGC_EAST_0.34 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_1.22_SHGC_EAST_0.34 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_1.22_SHGC_EAST_0.34 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_1.22_SHGC_SOUTH_0.34 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_1.22_SHGC_SOUTH_0.34 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_1.22_SHGC_SOUTH_0.34 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_1.22_SHGC_SOUTH_0.34 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_1.22_SHGC_SOUTH_0.34 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_1.22_SHGC_WEST_0.34 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_1.22_SHGC_WEST_0.34 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_1.22_SHGC_WEST_0.34 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_1.22_SHGC_NORTH_0.34 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 6.926 | 0.341 | 0.376 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_1.22_SHGC_EAST_0.34 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 6.926 | 0.341 | 0.376 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_1.22_SHGC_SOUTH_0.34 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 6.926 | 0.341 | 0.376 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_1.22_SHGC_WEST_0.34 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 6.926 | 0.341 | 0.376 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_1.22_SHGC_NORTH_0.34 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 6.926 | 0.341 | 0.376 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_1.22_SHGC_EAST_0.34 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 6.926 | 0.341 | 0.376 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_1.22_SHGC_SOUTH_0.34 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 6.926 | 0.341 | 0.376 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_1.22_SHGC_WEST_0.34 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 6.926 | 0.341 | 0.376 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 6.926 | 0.341 | 0.376 | |||||||||||||||||
North Total or Average | 1390.74 | 6.926 | 0.341 | 0.376 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 6.926 | 0.341 | 0.376 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 11.6510 | 2779.43 | 32383.10 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 333.79 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.6510 | 24961.20 | 290822.99 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 2997.66 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.6510 | 3134.13 | 36515.73 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.6510 | 3134.20 | 36516.53 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 11.6510 | 783.68 | 9130.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 94.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 22.3674 | 362.03 | 8097.60 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 83.47 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
Interior Lighting Total | 11.7515 | 46320.38 | 544334.28 | 1723.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 64082.80 | AstronomicalClock | - | 83.75 | 83.75 | 1007.50 | |
Exterior Lighting Total | 64082.80 | 1007.50 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3094793.27 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2121890.02 | 0.79 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1566628.98 | 6.11 | 1558984.68 | 6.08 | 6.37 | 21.74 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1566628.98 | 6.11 | 1558984.68 | 6.08 | 6.37 | 21.74 |
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1876977.00 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1876977.00 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 223005.39 | 288275.22 | 207095.81 | 81179.41 | 0.72 | - | 35252.29 | 357.55 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2060171.37 | 2649949.66 | 1900700.64 | 749249.01 | 0.72 | - | 323701.90 | 3283.16 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 250714.82 | 326547.99 | 235220.29 | 91327.70 | 0.72 | - | 39970.64 | 405.40 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 118017.07 | 161137.92 | 117084.20 | 44053.73 | 0.73 | - | 20511.69 | 208.04 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | 450969.37 | 566788.97 | 433225.10 | 133563.87 | 0.76 | - | 55277.73 | 560.66 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | 12408.39 | 9934.90 | 2473.49 | 0.80 | 3.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | 118660.02 | 95006.33 | 23653.69 | 0.80 | 3.50 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 12265.55 | 9820.54 | 2445.01 | 0.80 | 3.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
AIRLOOP DATACENTER BOT COOLING COIL | 11820.9 | 9.16 | 9.16 | ||||
AIRLOOP DATACENTER MID COOLING COIL | 113042.2 | 10.40 | 10.40 | ||||
AIRLOOP DATACENTER TOP COOLING COIL | 11684.9 | 9.16 | 9.16 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 21955.78 | 20845.57 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 439702.27 | 417220.08 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 115085.39 | 109178.92 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 16088.60 | 15262.91 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12164.46 | 11540.82 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 20329.75 | 19286.43 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11317.23 | 10740.57 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 301748.55 | 286263.31 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 205894.73 | 195328.59 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 309748.23 | 293852.49 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 189623.11 | 179891.95 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 38566.05 | 36586.93 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 26010.55 | 24675.75 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 39397.37 | 37375.59 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 24553.21 | 23293.20 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 25920.05 | 22728.69 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 117161.03 | 106895.81 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 6623.66 | 6176.63 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94837.96 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | 100000.00 | 94837.96 | - |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | 25841.84 | 0.80 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | 247091.87 | 0.79 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | 25543.57 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 12.68 | 27716.15 | 2186.10 | 1.00 | 1.11 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 116.07 | 253751.27 | 2186.10 | 1.00 | 1.08 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 14.46 | 31482.02 | 2176.85 | 1.00 | 1.12 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
CAV_BAS SZVAV FAN | Fan:VariableVolume | 0.61 | 1337.13 | 7.25 | 15931.07 | 2197.78 | 1.00 | 1.13 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 0.61 | 637.69 | 32.02 | 33237.65 | 1038.16 | 1.00 | 1.19 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.75 | 1289.03 | 1719.64 | 1.00 | 1.36 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 7.17 | 12326.81 | 1719.64 | 1.00 | 1.09 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.74 | 1274.19 | 1719.64 | 1.00 | 1.36 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.83 | 0.110828 | 22837.48 | 206063.11 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.018563 | 5590.43 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.055414 | 10540.55 | 190215.15 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.055414 | 10540.55 | 190215.15 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 209234.68 | 0.157028 | 54755.79 | 348701.22 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 85212.82 | 97994.74 | 35.26 | 6.303 | 7.249 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 24.71 | 0.00822 | 1.200 | 0.00 |
CORE_BOTTOM | 88029.90 | 101234.38 | 40.56 | 6.511 | 7.487 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00885 | 24.71 | 0.00822 | 1.078 | 0.00 |
CORE_MID | 831908.29 | 956694.53 | 383.27 | 61.516 | 70.743 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00887 | 24.71 | 0.00822 | 10.778 | 0.00 |
CORE_TOP | 92401.88 | 106262.16 | 42.57 | 6.895 | 7.930 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00883 | 31.30 | 0.00823 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 15425.14 | 17738.91 | 56.60 | 1.151 | 1.324 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00874 | 31.30 | 0.00823 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 21197.08 | 24376.64 | 120.69 | 1.582 | 1.819 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 24.00 | 24.00 | 0.00861 | 25.84 | 0.00822 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 24337.59 | 27988.22 | 89.30 | 1.816 | 2.089 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 24.00 | 24.00 | 0.00865 | 30.86 | 0.00823 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 26013.93 | 29916.02 | 148.12 | 1.941 | 2.232 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00859 | 30.53 | 0.00823 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 145142.64 | 166914.03 | 532.57 | 10.831 | 12.456 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00874 | 31.30 | 0.00823 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 215384.99 | 247692.74 | 1226.35 | 16.073 | 18.483 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00860 | 26.41 | 0.00823 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 236665.76 | 272165.63 | 868.37 | 17.661 | 20.310 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00865 | 30.93 | 0.00823 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 234868.84 | 270099.17 | 1337.29 | 17.526 | 20.155 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00860 | 30.41 | 0.00823 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 17506.29 | 20132.23 | 64.24 | 1.306 | 1.502 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00869 | 31.30 | 0.00823 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 21584.05 | 24821.66 | 122.89 | 1.611 | 1.852 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00860 | 26.66 | 0.00823 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 26453.55 | 30421.58 | 97.06 | 1.974 | 2.270 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00863 | 31.00 | 0.00823 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 25223.16 | 29006.63 | 143.61 | 1.882 | 2.165 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00859 | 30.41 | 0.00823 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8734.66 | 10044.86 | 277.46 | 0.652 | 0.750 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 27.00 | 27.00 | 0.00856 | 29.16 | 0.00823 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 83528.25 | 96057.49 | 2653.32 | 6.233 | 7.168 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 27.00 | 27.00 | 0.00857 | 28.94 | 0.00823 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8634.12 | 9929.23 | 274.27 | 0.644 | 0.741 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 27.00 | 27.00 | 0.00857 | 29.16 | 0.00823 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 373073.67 | 429034.72 | 547.46 | 27.840 | 32.016 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00853 | 23.20 | 0.00822 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 24.41 | 0.00506 | 3.80 | 0.00506 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 22.36 | 0.00506 | 3.80 | 0.00506 | 1.078 | 0.00 | |
CORE_MID | 185808.08 | 232260.11 | 93.05 | 13.376 | 16.720 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 10.778 | 0.00 |
CORE_TOP | 53572.50 | 66965.62 | 26.83 | 3.938 | 4.923 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 7486.30 | 9357.88 | 29.86 | 0.551 | 0.689 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 5465.65 | 6832.06 | 33.83 | 0.403 | 0.504 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00786 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 9451.66 | 11814.58 | 37.70 | 0.697 | 0.871 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00789 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 3820.35 | 4775.44 | 23.64 | 0.280 | 0.351 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00768 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 140140.73 | 175175.91 | 558.93 | 10.363 | 12.953 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00787 | 3.80 | 0.00506 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 95611.30 | 119514.12 | 591.73 | 7.072 | 8.840 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 3.80 | 0.00506 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 143847.00 | 179808.75 | 573.70 | 10.638 | 13.298 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 3.80 | 0.00506 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 88071.54 | 110089.43 | 545.06 | 6.512 | 8.139 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00786 | 3.80 | 0.00506 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 17903.07 | 22378.84 | 71.40 | 1.325 | 1.657 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 12073.64 | 15092.04 | 74.72 | 0.894 | 1.117 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 18288.25 | 22860.31 | 72.94 | 1.354 | 1.692 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 11398.27 | 14247.84 | 70.54 | 0.844 | 1.055 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00787 | 3.80 | 0.00506 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 26.82 | 0.00850 | 3.80 | 0.00506 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 24.54 | 0.00593 | 3.80 | 0.00506 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 23.28 | 0.00537 | 3.80 | 0.00506 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 3.80 | 0.00506 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 12.68 | 12.68 | 3.49 | 3.49 | 12.6783 | 4.4854 | 12.6783 | 0.3538 | 0.3000 |
VAV_MID WITH REHEAT | 116.07 | 116.07 | 59.95 | 59.95 | 116.0747 | 59.9503 | 116.0747 | 0.5165 | 0.3000 |
VAV_TOP WITH REHEAT | 14.46 | 14.46 | 10.44 | 10.44 | 14.4622 | 10.4439 | 14.4622 | 0.7222 | 0.3000 |
CAV_BAS | 7.25 | 7.25 | 1.20 | 1.20 | 7.2487 | 2.1746 | 7.2487 | 0.3000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 32.02 | 32.02 | 0.34 | 0.34 | 32.0160 | 16.0079 | 32.0160 | 0.5000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.75 | 0.75 | 0.02 | 0.02 | 0.7496 | 0.7496 | 0.7496 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 7.17 | 7.17 | 0.16 | 0.16 | 7.1683 | 7.1683 | 7.1683 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.74 | 0.74 | 0.02 | 0.02 | 0.7410 | 0.7410 | 0.7410 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 21955.780 | 21955.780 | 2.246237 | 0.00019208 | 442.937 | 12/21 00:10:00 | 12/21 00:10:00 | 21955.78 | 21955.78 | 2.246237 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 22065.18 | 22065.18 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 439702.269 | 439702.269 | 21.222853 | 0.00384671 | 9968.100 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 439702.27 | 439702.27 | 21.222853 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 232260.11 | 0.00 | 441770.46 | 441770.46 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 115085.390 | 115085.390 | 4.923005 | 0.00100682 | 2691.207 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 115085.39 | 115085.39 | 4.923005 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 66965.62 | 0.00 | 115612.79 | 115612.79 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 16088.601 | 16088.601 | 0.688876 | 0.00014075 | 376.123 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16088.60 | 16088.60 | 0.688876 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00781543 | 49.6009 | 9357.88 | 0.00 | 16162.34 | 16162.34 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 12164.457 | 12164.457 | 0.545714 | 0.00010642 | 280.825 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12164.46 | 12164.46 | 0.545714 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00785714 | 49.8621 | 6832.06 | 0.00 | 12220.50 | 12220.50 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 20329.755 | 20329.755 | 0.871377 | 0.00017785 | 475.136 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20329.75 | 20329.75 | 0.871377 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00788997 | 50.0675 | 11814.58 | 0.00 | 20422.94 | 20422.94 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 11317.226 | 11317.226 | 0.669723 | 0.00009901 | 245.836 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11317.23 | 11317.23 | 0.669723 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00767832 | 48.7419 | 4775.44 | 0.00 | 11371.27 | 11371.27 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 301748.550 | 301748.550 | 12.953126 | 0.00263983 | 7049.352 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 301748.55 | 300048.30 | 12.953126 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00787198 | 49.9553 | 175175.91 | 0.00 | 303131.91 | 303131.91 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 205894.731 | 205894.731 | 8.839918 | 0.00180126 | 4809.820 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 205894.73 | 205894.73 | 8.839918 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00787585 | 49.9795 | 119514.12 | 0.00 | 206838.67 | 206838.67 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 309748.230 | 309748.230 | 13.297584 | 0.00270981 | 7236.078 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 309748.23 | 309748.23 | 13.297584 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00787569 | 49.9785 | 179808.75 | 0.00 | 311168.27 | 311168.27 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 189623.114 | 189623.114 | 8.139422 | 0.00165891 | 4429.991 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 189623.11 | 189623.11 | 8.139422 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00786382 | 49.9042 | 110089.43 | 0.00 | 190492.43 | 190492.43 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 38566.046 | 38566.046 | 1.656552 | 0.00033739 | 900.812 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 38566.05 | 38372.63 | 1.656552 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00787852 | 49.9965 | 22378.84 | 0.00 | 38742.86 | 38742.86 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 26010.550 | 26010.550 | 1.117367 | 0.00022755 | 607.527 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 26010.55 | 26010.55 | 1.117367 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00788009 | 50.0063 | 15092.04 | 0.00 | 26129.80 | 26129.80 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 39397.368 | 39397.368 | 1.692346 | 0.00034467 | 920.216 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 39397.37 | 39397.37 | 1.692346 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00788112 | 50.0128 | 22860.31 | 0.00 | 39578.00 | 39578.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 24553.213 | 24553.213 | 1.054636 | 0.00021480 | 573.507 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24553.21 | 24553.21 | 1.054636 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00787297 | 49.9618 | 14247.84 | 0.00 | 24665.78 | 24665.78 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 223005.393 | -999.000 | 12.678334 | 0.00796524 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 223005.39 | 215359.20 | 12.678334 | 25.17 | 16.77 | 0.00869704 | 11.08 | 11.08 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 16.0155 | 24.00 | 0.00878543 | 46.3956 | 147735.93 | 0.00 | 226333.94 | 206384.92 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 25920.052 | 25920.052 | 3.803500 | 0.00022676 | 456.481 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25920.05 | 25920.05 | 3.803500 | 7.15 | 6.36 | 0.00572952 | 12.89 | 11.47 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 53.3850 | 20.77 | 0.00647323 | 41.7540 | 17370.95 | 0.00 | 27516.44 | 27516.44 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2060171.373 | -999.000 | 116.074701 | 0.07358455 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 2060171.37 | 1986755.48 | 116.074701 | 25.28 | 16.82 | 0.00870666 | 11.08 | 11.08 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 17.4939 | 24.00 | 0.00880698 | 46.5078 | 1352577.23 | 0.00 | 2090733.79 | 1904822.15 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 117161.027 | 117161.027 | 34.822410 | 0.00102498 | 2108.549 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 117161.03 | 117161.03 | 34.822410 | 10.06 | 8.24 | 0.00615481 | 12.89 | 11.47 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 58.3130 | 18.66 | 0.00774092 | 56.8049 | 149456.96 | 0.00 | 129416.72 | 129416.72 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 250714.824 | -999.000 | 14.462190 | 0.00895495 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 250714.82 | 243031.93 | 14.462190 | 25.02 | 16.70 | 0.00867363 | 11.08 | 11.08 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 14.0401 | 24.00 | 0.00874552 | 46.1876 | 168523.19 | 0.00 | 254491.44 | 232765.00 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 6623.657 | 6623.657 | 4.338657 | 0.00005795 | 120.665 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6623.66 | 6623.66 | 4.338657 | 11.60 | 9.30 | 0.00647350 | 12.89 | 11.47 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 46.8002 | 16.69 | 0.00783956 | 65.1400 | 15142.84 | 0.00 | 7477.94 | 7477.94 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 118017.072 | -999.000 | 7.248706 | 0.00421530 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 118017.07 | 111684.91 | 7.248706 | 24.17 | 16.51 | 0.00879218 | 11.07 | 11.07 | 0.00850000 | 24.71 | 0.00822310 | 16.21 | 16.5568 | 24.00 | 0.00890509 | 47.0192 | 85212.82 | 0.00 | 122792.80 | 109749.96 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.095922 | 0.00087484 | 2622.544 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 100000.00 | 100000.00 | 3.095922 | 0.63 | 0.63 | 0.00505843 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 38.7657 | 24.41 | 0.00505843 | 26.2219 | 0.00 | 0.00 | 100077.82 | 100077.82 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 450969.369 | -999.000 | 32.015966 | 0.01610758 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 450969.37 | 448845.03 | 32.015966 | 27.04 | 17.28 | 0.00852978 | 15.03 | 12.83 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 1.0570 | 27.00 | 0.00853295 | 37.7252 | 372726.00 | 0.00 | 473757.70 | 473757.70 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 100000.000 | 100000.000 | 3.095922 | 0.00087484 | 2622.544 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 100000.00 | 100000.00 | 3.095922 | 0.04 | 0.04 | 0.00846362 | 29.11 | 17.54 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 10.9303 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | 100077.82 | 100077.82 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER BOT | 12408.390 | 9934.902 | 0.749590 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 6204.19 | 6147.75 | 0.499727 | 27.04 | 17.30 | 0.00855777 | 14.46 | 12.61 | 0.00850000 | 29.16 | 0.00823009 | 17.74 | 3.1282 | 27.00 | 0.00856475 | 37.8619 | 8734.66 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER BOT | 25841.845 | 25841.845 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 25841.84 | 25841.84 | 0.749591 | 0.08 | 0.08 | 0.00842823 | 29.11 | 17.54 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 2.0855 | 26.82 | 0.00850000 | 37.9670 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER MID | 118660.020 | 95006.332 | 7.168250 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 59330.01 | 58766.78 | 4.778833 | 27.05 | 17.30 | 0.00856032 | 14.46 | 12.61 | 0.00850000 | 29.16 | 0.00823009 | 17.74 | 3.2712 | 27.00 | 0.00856768 | 37.8748 | 83503.41 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER MID | 247091.870 | 247091.870 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 247091.87 | 247091.87 | 7.168252 | 0.08 | 0.08 | 0.00590650 | 29.11 | 17.54 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 2.1808 | 24.54 | 0.00592541 | 30.4351 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER TOP | 12265.550 | 9820.535 | 0.740960 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 6132.77 | 6076.27 | 0.493973 | 27.04 | 17.30 | 0.00855852 | 14.46 | 12.61 | 0.00850000 | 29.16 | 0.00823009 | 17.74 | 3.1646 | 27.00 | 0.00856560 | 37.8656 | 8634.12 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER TOP | 25543.570 | 25543.570 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 25543.57 | 25543.57 | 0.740962 | 0.08 | 0.08 | 0.00536485 | 29.11 | 17.54 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 2.1097 | 23.28 | 0.00537146 | 29.7861 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 21955.780 | 21955.780 | 2.246237 | 0.00019208 | 442.937 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.56132588 | 54.44 | 82.22 | 27.78 | 2164593.90 | 1.0143 | 1.034728 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 21955.78 | 21955.78 | 1.0000 | 2.65455521 | 2.246237 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.19205915 | 60.00 | 32.22 | 27.78 | 0.000 | 21955.78 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 22065.18 | 22065.18 | 2.65455521 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 20.95 | 14.83 | 0.00800000 | 41372.0 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 439702.269 | 439702.269 | 21.222853 | 0.00384671 | 9968.100 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.56132588 | 54.44 | 82.22 | 27.78 | 2164593.90 | 20.3134 | 20.722199 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 439702.27 | 439702.27 | 1.0000 | 25.08071433 | 21.222853 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 3.84631486 | 60.00 | 32.22 | 27.78 | 0.000 | 439702.27 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.56 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 232260.11 | 0.00 | 441770.46 | 441770.46 | 25.08071433 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 30.07 | 18.06 | 0.00800000 | 50673.8 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 115085.390 | 115085.390 | 4.923005 | 0.00100682 | 2691.207 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.56132588 | 54.44 | 82.22 | 27.78 | 2164593.90 | 5.3167 | 5.423721 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 115085.39 | 115085.39 | 1.0000 | 5.81790214 | 4.923005 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 1.00671449 | 60.00 | 32.22 | 27.78 | 0.000 | 115085.39 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 66965.62 | 0.00 | 115612.79 | 115612.79 | 5.81790214 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.29 | 18.79 | 0.00800000 | 52931.7 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16088.601 | 16088.601 | 0.688876 | 0.00014075 | 376.123 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.56132588 | 54.44 | 82.22 | 27.78 | 2164593.90 | 0.7433 | 0.758220 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16088.60 | 16088.60 | 1.0000 | 0.81409923 | 0.688876 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.14073574 | 60.00 | 32.22 | 27.78 | 0.000 | 16088.60 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00781543 | 21.00 | 0.00781543 | 49.6009 | 9357.88 | 0.00 | 16162.34 | 16162.34 | 0.81409923 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.27 | 18.78 | 0.00800000 | 52912.9 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12164.457 | 12164.457 | 0.545714 | 0.00010642 | 280.825 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.56132588 | 54.44 | 82.22 | 27.78 | 2164593.90 | 0.5620 | 0.573284 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12164.46 | 12164.46 | 1.0000 | 0.64491345 | 0.545714 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.10640912 | 60.00 | 32.22 | 27.78 | 0.000 | 12164.46 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00785714 | 21.00 | 0.00785714 | 49.8621 | 6832.06 | 0.00 | 12220.50 | 12220.50 | 0.64491345 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.38 | 18.50 | 0.00800000 | 52008.9 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20329.755 | 20329.755 | 0.871377 | 0.00017785 | 475.136 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.56132588 | 54.44 | 82.22 | 27.78 | 2164593.90 | 0.9392 | 0.958097 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 20329.75 | 20329.75 | 1.0000 | 1.02977478 | 0.871377 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.17783542 | 60.00 | 32.22 | 27.78 | 0.000 | 20329.75 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00788997 | 21.00 | 0.00788997 | 50.0675 | 11814.58 | 0.00 | 20422.94 | 20422.94 | 1.02977478 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.25 | 18.78 | 0.00800000 | 52892.3 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11317.226 | 11317.226 | 0.669723 | 0.00009901 | 245.836 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.56132588 | 54.44 | 82.22 | 27.78 | 2164593.90 | 0.5228 | 0.533356 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11317.23 | 11317.23 | 1.0000 | 0.79146450 | 0.669723 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.09899793 | 60.00 | 32.22 | 27.78 | 0.000 | 11317.23 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00767832 | 21.00 | 0.00767832 | 48.7419 | 4775.44 | 0.00 | 11371.27 | 11371.27 | 0.79146450 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 26.89 | 16.98 | 0.00800000 | 47427.2 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 301748.550 | 301748.550 | 12.953126 | 0.00263983 | 7049.352 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.56132588 | 54.44 | 82.22 | 27.78 | 2164593.90 | 13.9402 | 14.220744 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 301748.55 | 300048.30 | 1.0000 | 15.30772751 | 12.953126 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 2.63955866 | 60.00 | 32.22 | 27.78 | 0.000 | 301748.55 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00787198 | 21.00 | 0.00787198 | 49.9553 | 175175.91 | 0.00 | 303131.91 | 303131.91 | 15.30772751 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52862.4 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 205894.731 | 205894.731 | 8.839918 | 0.00180126 | 4809.820 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.56132588 | 54.44 | 82.22 | 27.78 | 2164593.90 | 9.5119 | 9.703365 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 205894.73 | 205894.73 | 1.0000 | 10.44682655 | 8.839918 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 1.80107318 | 60.00 | 32.22 | 27.78 | 0.000 | 205894.73 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00787585 | 21.00 | 0.00787585 | 49.9795 | 119514.12 | 0.00 | 206838.67 | 206838.67 | 10.44682655 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52859.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 309748.230 | 309748.230 | 13.297584 | 0.00270981 | 7236.078 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.56132588 | 54.44 | 82.22 | 27.78 | 2164593.90 | 14.3098 | 14.597751 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 309748.23 | 309748.23 | 1.0000 | 15.71480160 | 13.297584 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 2.70953621 | 60.00 | 32.22 | 27.78 | 0.000 | 309748.23 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00787569 | 21.00 | 0.00787569 | 49.9785 | 179808.75 | 0.00 | 311168.27 | 311168.27 | 15.71480160 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52860.8 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 189623.114 | 189623.114 | 8.139422 | 0.00165891 | 4429.991 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.56132588 | 54.44 | 82.22 | 27.78 | 2164593.90 | 8.7602 | 8.936519 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 189623.11 | 189623.11 | 1.0000 | 9.61899490 | 8.139422 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 1.65873650 | 60.00 | 32.22 | 27.78 | 0.000 | 189623.11 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00786382 | 21.00 | 0.00786382 | 49.9042 | 110089.43 | 0.00 | 190492.43 | 190492.43 | 9.61899490 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52863.6 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 38566.046 | 38566.046 | 1.656552 | 0.00033739 | 900.812 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.56132588 | 54.44 | 82.22 | 27.78 | 2164593.90 | 1.7817 | 1.817533 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 38566.05 | 38372.63 | 1.0000 | 1.95767749 | 1.656552 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.33735818 | 60.00 | 32.22 | 27.78 | 0.000 | 38566.05 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00787852 | 21.00 | 0.00787852 | 49.9965 | 22378.84 | 0.00 | 38742.86 | 38742.86 | 1.95767749 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.76 | 0.00800000 | 52850.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26010.550 | 26010.550 | 1.117367 | 0.00022755 | 607.527 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.56132588 | 54.44 | 82.22 | 27.78 | 2164593.90 | 1.2016 | 1.225820 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 26010.55 | 26010.55 | 1.0000 | 1.32048026 | 1.117367 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.22752843 | 60.00 | 32.22 | 27.78 | 0.000 | 26010.55 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00788009 | 21.00 | 0.00788009 | 50.0063 | 15092.04 | 0.00 | 26129.80 | 26129.80 | 1.32048026 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.76 | 0.00800000 | 52847.9 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 39397.368 | 39397.368 | 1.692346 | 0.00034467 | 920.216 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.56132588 | 54.44 | 82.22 | 27.78 | 2164593.90 | 1.8201 | 1.856711 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 39397.37 | 39397.37 | 1.0000 | 1.99997884 | 1.692346 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.34463021 | 60.00 | 32.22 | 27.78 | 0.000 | 39397.37 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00788112 | 21.00 | 0.00788112 | 50.0128 | 22860.31 | 0.00 | 39578.00 | 39578.00 | 1.99997884 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.76 | 0.00800000 | 52849.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24553.213 | 24553.213 | 1.054636 | 0.00021480 | 573.507 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.56132588 | 54.44 | 82.22 | 27.78 | 2164593.90 | 1.1343 | 1.157139 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 24553.21 | 24553.21 | 1.0000 | 1.24634601 | 1.054636 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.21478030 | 60.00 | 32.22 | 27.78 | 0.000 | 24553.21 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00787297 | 21.00 | 0.00787297 | 49.9618 | 14247.84 | 0.00 | 24665.78 | 24665.78 | 1.24634601 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.76 | 0.00800000 | 52850.3 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 223005.393 | -999.000 | 12.678334 | 0.00796524 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0074 | 1004.8586 | 1.1818 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 12.678334 | 14.98298420 | 4197.9300 | 999.8980 | 110.81630829 | 13.34 | 6.67 | 6.67 | 3102878.03 | 7.1870 | 7.187050 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 223005.39 | 215359.20 | 1.0000 | 14.98298420 | 12.678334 | 25.17 | 16.77 | 0.00869704 | 47447.7 | 11.08 | 11.08 | 0.00850000 | 32563.8 | 7.96442341 | 6.67 | 13.34 | 6.67 | 27716.145 | 195289.25 | 31.30 | 0.00823349 | 18.45 | 2.03050000 | 16.0155 | 24.00 | 0.00878543 | 24.00 | 0.00878543 | 46.3956 | 147735.93 | 0.00 | 226333.94 | 206384.92 | 14.98298420 | 25.17 | 16.97 | 0.00869704 | 47447.7 | 11.68 | 11.29 | 0.00816924 | 32341.6 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 25920.052 | 25920.052 | 3.803500 | 0.00022676 | 456.481 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 12.678334 | 14.98298420 | 4197.9300 | 999.8980 | 18.56132588 | 54.44 | 82.22 | 27.78 | 2164593.90 | 1.1975 | 1.221555 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25920.05 | 25920.05 | 1.0000 | 4.49489526 | 3.803500 | 7.15 | 6.36 | 0.00572952 | 21590.2 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 0.22673679 | 60.00 | 32.22 | 27.78 | 0.000 | 25920.05 | 3.80 | 0.00505843 | 3.80 | 2.03050000 | 53.3850 | 10.99 | 0.00649807 | 20.77 | 0.00647323 | 41.7540 | 17370.95 | 0.00 | 27516.44 | 27516.44 | 4.49489526 | 2.80 | 2.80 | 0.00572952 | 17172.6 | 8.83 | 7.32 | 0.00572952 | 23294.3 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2060171.373 | -999.000 | 116.074701 | 0.07358455 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0252 | 1004.8586 | 1.1818 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 116.074701 | 137.17460514 | 4197.9300 | 999.8980 | 110.81630829 | 13.34 | 6.67 | 6.67 | 3102878.03 | 66.3955 | 66.395500 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 2060171.37 | 1986755.48 | 1.0000 | 137.17460514 | 116.074701 | 25.28 | 16.82 | 0.00870666 | 47582.4 | 11.08 | 11.08 | 0.00850000 | 32563.8 | 73.57704161 | 6.67 | 13.34 | 6.67 | 253751.271 | 1806420.10 | 31.30 | 0.00823349 | 18.45 | 20.30600000 | 17.4939 | 24.00 | 0.00880698 | 24.00 | 0.00880698 | 46.5078 | 1352577.23 | 0.00 | 2090733.79 | 1904822.15 | 137.17460514 | 25.28 | 17.01 | 0.00870666 | 47582.4 | 11.68 | 11.29 | 0.00816941 | 32341.0 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 117161.027 | 117161.027 | 34.822410 | 0.00102498 | 2108.549 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 116.074701 | 137.17460514 | 4197.9300 | 999.8980 | 18.56132588 | 54.44 | 82.22 | 27.78 | 2164593.90 | 5.4126 | 5.521541 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 117161.03 | 117161.03 | 1.0000 | 41.15238154 | 34.822410 | 10.06 | 8.24 | 0.00615481 | 25612.2 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 1.02487122 | 60.00 | 32.22 | 27.78 | 0.000 | 117161.03 | 3.80 | 0.00505843 | 3.80 | 20.30600000 | 58.3130 | 18.81 | 0.00768845 | 18.66 | 0.00774092 | 56.8049 | 149456.96 | 0.00 | 129416.72 | 129416.72 | 41.15238154 | 2.80 | 2.80 | 0.00615481 | 18238.4 | 5.89 | 5.89 | 0.00615481 | 21383.2 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 250714.824 | -999.000 | 14.462190 | 0.00895495 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9638 | 1004.8586 | 1.1818 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 14.462190 | 17.09110766 | 4197.9300 | 999.8980 | 110.81630829 | 13.34 | 6.67 | 6.67 | 3102878.03 | 8.0801 | 8.080073 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 250714.82 | 243031.93 | 1.0000 | 17.09110766 | 14.462190 | 25.02 | 16.70 | 0.00867363 | 47240.8 | 11.08 | 11.08 | 0.00850000 | 32571.5 | 8.95403909 | 6.67 | 13.34 | 6.67 | 31482.016 | 219232.81 | 31.30 | 0.00823349 | 18.45 | 2.03050000 | 14.0401 | 24.00 | 0.00874552 | 24.00 | 0.00874552 | 46.1876 | 168523.19 | 0.00 | 254491.44 | 232765.00 | 17.09110766 | 25.02 | 16.90 | 0.00867363 | 47240.8 | 11.68 | 11.30 | 0.00816971 | 32350.5 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 6623.657 | 6623.657 | 4.338657 | 0.00005795 | 120.665 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 14.462190 | 17.09110766 | 4197.9300 | 999.8980 | 18.56132588 | 54.44 | 82.22 | 27.78 | 2164593.90 | 0.3060 | 0.312158 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6623.66 | 6623.66 | 1.0000 | 5.12733230 | 4.338657 | 11.60 | 9.30 | 0.00647350 | 27988.9 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 0.05794073 | 60.00 | 32.22 | 27.78 | 0.000 | 6623.66 | 3.80 | 0.00505843 | 3.80 | 2.03050000 | 46.8002 | 18.47 | 0.00771834 | 16.69 | 0.00783956 | 65.1400 | 15142.84 | 0.00 | 7477.94 | 7477.94 | 5.12733230 | 2.80 | 2.80 | 0.00647350 | 19037.1 | 4.23 | 4.23 | 0.00647350 | 20495.5 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 118017.072 | -999.000 | 7.248706 | 0.00421530 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1842 | 1004.8586 | 1.1818 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 7.248706 | 8.56636583 | 4197.9300 | 999.8980 | 110.81630829 | 13.34 | 6.67 | 6.67 | 3102878.03 | 3.8035 | 3.803471 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 118017.07 | 111684.91 | 1.0000 | 8.56636583 | 7.248706 | 24.17 | 16.51 | 0.00879218 | 46670.2 | 11.07 | 11.07 | 0.00850000 | 32554.2 | 4.21486637 | 6.67 | 13.34 | 6.67 | 15931.068 | 102086.00 | 24.71 | 0.00822310 | 16.21 | 1.20015641 | 16.5568 | 24.06 | 0.00890509 | 24.00 | 0.00890509 | 47.0192 | 85212.82 | 0.00 | 122792.80 | 109749.96 | 8.56636583 | 24.17 | 16.70 | 0.00879218 | 46670.2 | 11.62 | 11.29 | 0.00818859 | 32335.9 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.095922 | 0.00087484 | 2622.544 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 7.248706 | 8.56636583 | 4197.9300 | 999.8980 | 18.56132588 | 54.44 | 82.22 | 27.78 | 2164593.90 | 4.6198 | 4.712780 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.095922 | 0.63 | 0.63 | 0.00505843 | 13289.0 | 32.11 | 18.53 | 0.00800000 | 52750.5 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | 3.80 | 0.00505843 | 3.80 | 1.20015641 | 38.7657 | 0.00 | 0.00505843 | 24.41 | 0.00505843 | 26.2219 | 0.00 | 0.00 | 100077.82 | 100077.82 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40240.6 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 450969.369 | -999.000 | 32.015966 | 0.01610758 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6964 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 32.015966 | 37.83578562 | 4197.9300 | 999.8980 | 110.81630829 | 13.34 | 6.67 | 6.67 | 3102878.03 | 14.5339 | 14.533906 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 450969.37 | 448845.03 | 1.0000 | 37.83578562 | 32.015966 | 27.04 | 17.28 | 0.00852978 | 48935.6 | 15.03 | 12.83 | 0.00850000 | 36596.4 | 16.10593781 | 6.67 | 13.34 | 6.67 | 33237.655 | 417731.71 | 31.30 | 0.00823349 | 18.45 | 0.33839277 | 1.0570 | 27.00 | 0.00853295 | 27.00 | 0.00853295 | 37.7252 | 372726.00 | 0.00 | 473757.70 | 473757.70 | 37.83578562 | 27.04 | 17.47 | 0.00852978 | 48935.6 | 14.78 | 12.93 | 0.00852978 | 36414.2 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.095922 | 0.00087484 | 2622.544 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 32.015966 | 37.83578562 | 4197.9300 | 999.8980 | 18.56132588 | 54.44 | 82.22 | 27.78 | 2164593.90 | 4.6198 | 4.712780 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.095922 | 0.04 | 0.04 | 0.00846362 | 21208.0 | 29.11 | 17.54 | 0.00800000 | 49691.3 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | 3.80 | 0.00505843 | 3.80 | 0.33839277 | 10.9303 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | 100077.82 | 100077.82 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40240.6 | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12408.390 | 9934.902 | 0.749590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7485 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.749591 | 0.88585015 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | Sensible | 6204.19 | 6147.75 | 1.0000 | 0.59056631 | 0.499727 | 27.04 | 17.30 | 0.00855777 | 49007.6 | 14.46 | 12.61 | 0.00850000 | 36019.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6204.19 | 29.16 | 0.00823009 | 17.74 | 0.01563234 | 3.1282 | 27.00 | 0.00856475 | 27.00 | 0.00856475 | 37.8619 | 8734.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25841.845 | 25841.845 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.749591 | 0.88585015 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 25841.84 | 25841.84 | 1.0000 | 0.88585015 | 0.749591 | 0.08 | 0.08 | 0.00842823 | 21159.4 | 29.11 | 17.54 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25841.84 | 3.80 | 0.00505843 | 3.80 | 0.01563234 | 2.0855 | 0.00 | 0.00850000 | 26.82 | 0.00850000 | 37.9670 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 118660.020 | 95006.332 | 7.168250 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7532 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.168252 | 8.47128711 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | Sensible | 59330.01 | 58766.78 | 1.0000 | 5.64752327 | 4.778833 | 27.05 | 17.30 | 0.00856032 | 49016.1 | 14.46 | 12.61 | 0.00850000 | 36019.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59330.01 | 29.16 | 0.00823009 | 17.74 | 0.15632344 | 3.2712 | 27.00 | 0.00856768 | 27.00 | 0.00856768 | 37.8748 | 83503.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 247091.870 | 247091.870 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.168252 | 8.47128711 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 247091.87 | 247091.87 | 1.0000 | 8.47128711 | 7.168252 | 0.08 | 0.08 | 0.00590650 | 14856.0 | 29.11 | 17.54 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 247091.87 | 3.80 | 0.00505843 | 3.80 | 0.15632344 | 2.1808 | 0.00 | 0.00592541 | 24.54 | 0.00592541 | 30.4351 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12265.550 | 9820.535 | 0.740960 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7499 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.740962 | 0.87565324 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | Sensible | 6132.77 | 6076.27 | 1.0000 | 0.58376715 | 0.493973 | 27.04 | 17.30 | 0.00855852 | 49010.0 | 14.46 | 12.61 | 0.00850000 | 36019.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6132.77 | 29.16 | 0.00823009 | 17.74 | 0.01563234 | 3.1646 | 27.00 | 0.00856560 | 27.00 | 0.00856560 | 37.8656 | 8634.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25543.570 | 25543.570 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.740962 | 0.87565324 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 25543.57 | 25543.57 | 1.0000 | 0.87565324 | 0.740962 | 0.08 | 0.08 | 0.00536485 | 13498.5 | 29.11 | 17.54 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25543.57 | 3.80 | 0.00505843 | 3.80 | 0.01563234 | 2.1097 | 0.00 | 0.00537146 | 23.28 | 0.00537146 | 29.7861 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 12.68 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 116.07 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 14.46 | - | |||
CAV_BAS_OA_CONTROLLER | FixedDryBulb | 1.20 | 7.25 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 32.02 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 3925.17 | 245.33 | 2.67 |
CORE_BOTTOM | 4139.50 | 239.50 | 0.00 |
CORE_MID | 2812.33 | 1490.17 | 12.83 |
CORE_TOP | 2224.67 | 2873.17 | 79.00 |
PERIMETER_BOT_ZN_3 | 2153.50 | 2930.33 | 15.33 |
PERIMETER_BOT_ZN_2 | 2105.67 | 3314.17 | 118.33 |
PERIMETER_BOT_ZN_1 | 2853.50 | 2755.83 | 221.50 |
PERIMETER_BOT_ZN_4 | 2743.83 | 2894.67 | 330.83 |
PERIMETER_MID_ZN_3 | 1635.33 | 4098.33 | 321.33 |
PERIMETER_MID_ZN_2 | 1456.50 | 3433.00 | 233.00 |
PERIMETER_MID_ZN_1 | 2539.33 | 3236.50 | 291.17 |
PERIMETER_MID_ZN_4 | 1756.67 | 4137.00 | 347.17 |
PERIMETER_TOP_ZN_3 | 1911.33 | 4403.17 | 735.17 |
PERIMETER_TOP_ZN_2 | 2152.67 | 3916.33 | 495.67 |
PERIMETER_TOP_ZN_1 | 2648.33 | 3450.67 | 514.17 |
PERIMETER_TOP_ZN_4 | 1998.00 | 4279.33 | 673.17 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1495.67 | 1495.67 |
DATACENTER_MID_ZN_6 | 5943.00 | 527.17 | 527.17 |
DATACENTER_TOP_ZN_6 | 5863.33 | 845.00 | 836.83 |
DATACENTER_BASEMENT_ZN_6 | 5931.50 | 4682.67 | 4682.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5933.00 | 5143.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 15.83 | 0.00 | 0.33 |
CORE_BOTTOM | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 22.67 | 0.00 | 22.67 |
PERIMETER_BOT_ZN_1 | 0.00 | 52.17 | 0.00 | 52.17 |
PERIMETER_BOT_ZN_4 | 0.00 | 44.00 | 0.00 | 36.33 |
PERIMETER_MID_ZN_3 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6.17 | 18.00 | 0.00 | 18.00 |
PERIMETER_MID_ZN_1 | 2.33 | 59.17 | 0.00 | 59.17 |
PERIMETER_MID_ZN_4 | 2.17 | 28.17 | 0.00 | 22.33 |
PERIMETER_TOP_ZN_3 | 21.33 | 0.00 | 0.67 | 0.00 |
PERIMETER_TOP_ZN_2 | 19.33 | 16.17 | 0.33 | 16.17 |
PERIMETER_TOP_ZN_1 | 15.17 | 37.33 | 0.00 | 37.33 |
PERIMETER_TOP_ZN_4 | 12.17 | 28.83 | 0.00 | 22.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 10.17 | 0.00 | 8.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 22.50 | 249.67 | 0.67 | 216.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 1.457 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 1.436 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 1.135 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 1.166 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 1.568 | 0.030 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 3.155 | 0.031 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 2.959 | 0.030 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 4.048 | 0.031 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 1.347 | 0.069 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 2.910 | 0.074 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 2.732 | 0.069 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 3.402 | 0.072 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 1.641 | 0.086 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 3.009 | 0.089 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 2.902 | 0.086 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 3.599 | 0.089 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 32.824 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.22 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.95 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.54 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1031.21 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 58633452.89 | 0.00 | 58633452.89 | 0.00 | 58633452.89 | 37848132.68 | 4151.80 | 1214.27 | 3393.93 | 184.67 |
CORE_BOTTOM | 58903971.83 | 0.00 | 58903971.83 | 0.00 | 58903971.83 | 33990283.35 | 3881.45 | 3.82 | 4874.73 | 207.23 |
CORE_MID | 0.46E+09 | 0.00 | 0.46E+09 | 0.00 | 0.46E+09 | 0.34E+09 | 4076.73 | 16.09 | 4667.17 | 125.91 |
CORE_TOP | 47153160.92 | 0.00 | 47153160.92 | 0.00 | 47153160.92 | 33990283.35 | 4159.96 | 8.67 | 4591.37 | 128.40 |
PERIMETER_BOT_ZN_3 | 8114660.47 | 0.00 | 8114660.47 | 258141.27 | 8372801.74 | 4267819.30 | 3646.99 | 6.11 | 5106.90 | 207.23 |
PERIMETER_BOT_ZN_2 | 10568101.00 | 0.00 | 10568101.00 | 172094.06 | 10740195.07 | 2750345.05 | 3571.43 | 0.00 | 5188.57 | 207.23 |
PERIMETER_BOT_ZN_1 | 15253265.26 | 0.00 | 15253265.26 | 258141.27 | 15511406.53 | 4267912.63 | 3572.43 | 0.17 | 5187.41 | 207.23 |
PERIMETER_BOT_ZN_4 | 13534891.92 | 0.00 | 13534891.92 | 172094.06 | 13706985.98 | 2750345.05 | 3571.26 | 0.00 | 5188.74 | 207.23 |
PERIMETER_MID_ZN_3 | 69119049.61 | 0.00 | 69119049.61 | 605406.74 | 69724456.34 | 42678193.03 | 3797.29 | 8.18 | 4954.53 | 125.91 |
PERIMETER_MID_ZN_2 | 92504704.20 | 0.00 | 92504704.20 | 403604.22 | 92908308.42 | 27503450.52 | 3947.34 | 1.73 | 4810.93 | 887.32 |
PERIMETER_MID_ZN_1 | 0.14E+09 | 0.00 | 0.14E+09 | 605406.74 | 0.14E+09 | 42679126.28 | 3699.01 | 0.58 | 5060.41 | 125.91 |
PERIMETER_MID_ZN_4 | 0.11E+09 | 0.00 | 0.11E+09 | 403604.22 | 0.11E+09 | 27503450.52 | 3698.09 | 0.00 | 5061.91 | 125.91 |
PERIMETER_TOP_ZN_3 | 8392886.41 | 0.00 | 8392886.41 | 751668.47 | 9144554.88 | 4267819.30 | 3789.01 | 9.25 | 4961.74 | 128.40 |
PERIMETER_TOP_ZN_2 | 9901401.15 | 0.00 | 9901401.15 | 501111.97 | 10402513.12 | 2750345.05 | 3727.68 | 0.13 | 5032.19 | 128.40 |
PERIMETER_TOP_ZN_1 | 14761469.03 | 0.00 | 14761469.03 | 751668.47 | 15513137.50 | 4267912.63 | 3731.45 | 0.20 | 5028.35 | 128.40 |
PERIMETER_TOP_ZN_4 | 11847535.80 | 0.00 | 11847535.80 | 501111.97 | 12348647.77 | 2750345.05 | 3726.21 | 0.06 | 5033.73 | 128.40 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.51E+09 | 0.00 | 0.51E+09 | 0.00 | 0.51E+09 | 10671554.30 | 344.99 | 481.11 | 7933.90 | 2623.09 |
Total Facility | 0.95E+10 | 0.00 | 0.95E+10 | 23546250.62 | 0.96E+10 | 0.50E+10 | 4998.00 | 4356.19 | 8469.21 | 3403.98 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.6876 | 0.0000 | 2.6876 | 0.0000 | 2.6876 | 1.2002 | 1425.24 | 1212.54 | 3305.22 |
CORE_BOTTOM | 2.6742 | 0.0000 | 2.6742 | 0.0000 | 2.6742 | 1.0778 | 1269.83 | 3.34 | 4669.83 |
CORE_MID | 21.1264 | 0.0000 | 21.1264 | 0.0000 | 21.1264 | 10.7782 | 1373.91 | 13.07 | 4556.02 |
CORE_TOP | 2.1729 | 0.0000 | 2.1729 | 0.0000 | 2.1729 | 1.0778 | 1426.25 | 6.67 | 4510.08 |
PERIMETER_BOT_ZN_3 | 0.3671 | 0.0000 | 0.3671 | 0.0069 | 0.3740 | 0.1353 | 1037.22 | 6.11 | 4899.67 |
PERIMETER_BOT_ZN_2 | 0.4772 | 0.0000 | 0.4772 | 0.0046 | 0.4818 | 0.0872 | 961.65 | 0.00 | 4981.35 |
PERIMETER_BOT_ZN_1 | 0.6936 | 0.0000 | 0.6936 | 0.0069 | 0.7006 | 0.1353 | 962.65 | 0.17 | 4980.18 |
PERIMETER_BOT_ZN_4 | 0.6116 | 0.0000 | 0.6116 | 0.0046 | 0.6162 | 0.0872 | 961.49 | 0.00 | 4981.51 |
PERIMETER_MID_ZN_3 | 3.1607 | 0.0000 | 3.1607 | 0.0163 | 3.1769 | 1.3533 | 1106.21 | 8.18 | 4828.61 |
PERIMETER_MID_ZN_2 | 4.4070 | 0.0000 | 4.4070 | 0.0112 | 4.4182 | 0.8721 | 1007.00 | 0.00 | 4027.00 |
PERIMETER_MID_ZN_1 | 6.4069 | 0.0000 | 6.4069 | 0.0163 | 6.4232 | 1.3533 | 1007.92 | 0.58 | 4934.50 |
PERIMETER_MID_ZN_4 | 5.1501 | 0.0000 | 5.1501 | 0.0109 | 5.1610 | 0.8721 | 1007.00 | 0.00 | 4936.00 |
PERIMETER_TOP_ZN_3 | 0.3855 | 0.0000 | 0.3855 | 0.0202 | 0.4058 | 0.1353 | 1089.70 | 8.73 | 4844.57 |
PERIMETER_TOP_ZN_2 | 0.4554 | 0.0000 | 0.4554 | 0.0135 | 0.4688 | 0.0872 | 1033.82 | 0.04 | 4909.14 |
PERIMETER_TOP_ZN_1 | 0.6809 | 0.0000 | 0.6809 | 0.0202 | 0.7011 | 0.1353 | 1035.70 | 0.17 | 4907.13 |
PERIMETER_TOP_ZN_4 | 0.5450 | 0.0000 | 0.5450 | 0.0135 | 0.5585 | 0.0872 | 1033.54 | 0.00 | 4909.46 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 16.9421 | 0.0000 | 16.9421 | 0.0000 | 16.9421 | 0.3384 | 150.49 | 481.11 | 5311.39 |
Total Facility | 432.3682 | 0.0000 | 432.3682 | 0.6373 | 433.0056 | 158.4706 | 2181.00 | 4348.28 | 5830.71 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 0.15E+09 | 0.00 | 0.15E+09 | 48026705.38 | 3571.26 | 0.00 | 5188.74 | 207.23 |
VAV_MID WITH REHEAT | 0.12E+10 | 0.00 | 0.12E+10 | 0.48E+09 | 3698.09 | 0.00 | 5061.91 | 125.91 |
VAV_TOP WITH REHEAT | 0.13E+09 | 0.00 | 0.13E+09 | 48026705.38 | 3733.27 | 0.79 | 5025.94 | 128.40 |
CAV_BAS | 81889857.24 | 0.00 | 81889857.24 | 37848132.68 | 4111.86 | 2.55 | 4645.59 | 184.67 |
AIRLOOP DATACENTER BASEMENT | 0.71E+09 | 0.00 | 0.71E+09 | 10671554.30 | 344.62 | 0.02 | 8415.36 | 2623.09 |
AIRLOOP DATACENTER BOT | 341184.02 | 0.00 | 341184.02 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3411840.17 | 0.00 | 3411840.17 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 341184.02 | 0.00 | 341184.02 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 6.7367 | 0.0000 | 6.7367 | 1.5229 | 961.49 | 0.00 | 4981.51 |
VAV_MID WITH REHEAT | 55.9594 | 0.0000 | 55.9594 | 15.2292 | 1007.00 | 0.00 | 4936.00 |
VAV_TOP WITH REHEAT | 5.9211 | 0.0000 | 5.9211 | 1.5229 | 1036.63 | 0.26 | 4906.11 |
CAV_BAS | 3.7535 | 0.0000 | 3.7535 | 1.2002 | 1413.81 | 0.53 | 4528.66 |
AIRLOOP DATACENTER BASEMENT | 23.6614 | 0.0000 | 23.6614 | 0.3384 | 150.39 | 0.00 | 5792.61 |
AIRLOOP DATACENTER BOT | 0.0159 | 0.0000 | 0.0159 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1595 | 0.0000 | 0.1595 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0159 | 0.0000 | 0.0159 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 27.03 | 4879.09 | 0.00 | 0.00 | 0.00 | 282.62 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 139.31 | 4654.87 | 0.00 | 0.00 | 0.00 | 267.73 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 21.14 | 4720.12 | 0.00 | 0.00 | 0.00 | 298.15 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1488.53 | 3268.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 481.16 | 7934.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.7734 | 8.4135 | 0.0000 | 0.0000 | 0.0000 | 2.3460 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 28.8090 | 71.1279 | 0.0000 | 0.0000 | 0.0000 | 24.0612 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.8796 | 7.4951 | 0.0000 | 0.0000 | 0.0000 | 2.3952 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 3.2088 | 5.6797 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4728 | 26.4343 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0218 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2183 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0218 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1343 |
Defaulted Fields | 1287 |
Fields with Defaults | 3878 |
Autosized Fields | 320 |
Autosizable Fields | 465 |
Autocalculated Fields | 223 |
Autocalculatable Fields | 468 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 30900.30 | 287579.37 | 28-MAY-05:00 | 2320480.48 | 15-AUG-16:00 |
Electricity:Building | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 758.19 | 15076.70 | 01-JAN-00:10 | 42602.33 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 589.38 | 5907.35 | 01-JAN-00:10 | 43380.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5893.79 | 59073.32 | 01-JAN-00:10 | 433806.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 589.38 | 5907.33 | 01-JAN-00:10 | 43380.63 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 740.04 | 7417.49 | 01-JAN-00:10 | 54469.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 476.91 | 4780.12 | 01-JAN-00:10 | 35102.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 740.05 | 7417.62 | 01-JAN-00:10 | 54470.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 476.91 | 4780.09 | 01-JAN-00:10 | 35102.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7588.97 | 95364.66 | 01-JAN-00:10 | 387850.11 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1622.27 | 19890.94 | 01-JAN-00:10 | 85232.07 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:HVAC | 3690.82 | 29526.93 | 01-JAN-05:30 | 356919.78 | 05-DEC-15:40 |
ExteriorEquipment:Electricity | 2623.11 | 22123.82 | 01-JAN-00:10 | 235096.12 | 03-APR-07:20 |
Transformer:ExteriorEquipment:Electricity | 56.04 | 979.82 | 01-JAN-00:10 | 3543.78 | 03-APR-07:20 |
ElectricityPurchased:Facility | 30900.30 | 287579.37 | 28-MAY-05:00 | 2320480.48 | 15-AUG-16:00 |
ElectricityPurchased:Plant | 30900.30 | 287579.37 | 28-MAY-05:00 | 2320480.48 | 15-AUG-16:00 |
Cogeneration:ElectricityPurchased | 30900.30 | 287579.37 | 28-MAY-05:00 | 2320480.48 | 15-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 30900.30 | 287579.37 | 28-MAY-05:00 | 2320480.48 | 15-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 30900.30 | 287579.37 | 28-MAY-05:00 | 2320480.48 | 15-AUG-16:00 |
ElectricityNet:Plant | 30900.30 | 287579.37 | 28-MAY-05:00 | 2320480.48 | 15-AUG-16:00 |
Cogeneration:ElectricityNet | 30900.30 | 287579.37 | 28-MAY-05:00 | 2320480.48 | 15-AUG-16:00 |
General:Cogeneration:ElectricityNet | 30900.30 | 287579.37 | 28-MAY-05:00 | 2320480.48 | 15-AUG-16:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 2284.00 | 2947.93 | 09-JAN-07:20 | 412099.16 | 15-AUG-16:00 |
General:Cooling:Electricity | 2284.00 | 2947.93 | 09-JAN-07:20 | 412099.16 | 15-AUG-16:00 |
Fans:Electricity | 2821.10 | 24860.48 | 03-JAN-05:50 | 280698.21 | 29-SEP-16:00 |
General:Fans:Electricity | 2821.10 | 24860.48 | 03-JAN-05:50 | 280698.21 | 29-SEP-16:00 |
ExteriorLights:Electricity | 1007.50 | 0.00 | 01-JAN-07:00 | 64082.80 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 1007.50 | 0.00 | 01-JAN-07:00 | 64082.80 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.31 | 1944.00 | 01-JAN-00:10 | 1944.00 | 01-JAN-00:10 |
Humidifier:Electricity | 351.41 | 0.00 | 01-JAN-00:30 | 100000.00 | 03-JAN-13:10 |
General:Humidifier:Electricity | 351.41 | 0.00 | 01-JAN-00:30 | 100000.00 | 03-JAN-13:10 |
Electricity:Plant | 3347.78 | 0.00 | 01-JAN-00:20 | 549882.50 | 15-AUG-16:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 392.84 | 0.00 | 01-JAN-00:10 | 45273.79 | 02-FEB-12:20 |
Water Heater:WaterSystems:Electricity | 392.84 | 0.00 | 01-JAN-00:10 | 45273.79 | 02-FEB-12:20 |
HeatRejection:Electricity | 162.97 | 0.00 | 01-JAN-00:10 | 48088.10 | 22-MAR-12:50 |
General:HeatRejection:Electricity | 162.97 | 0.00 | 01-JAN-00:10 | 48088.10 | 22-MAR-12:50 |
Pumps:Electricity | 970.24 | 0.00 | 01-JAN-00:20 | 94584.55 | 16-OCT-14:40 |
General:Pumps:Electricity | 970.24 | 0.00 | 01-JAN-00:20 | 94584.55 | 16-OCT-14:40 |
WIRED_LTG_ELECTRICITY | 157.66 | 0.00 | 01-JAN-00:10 | 13766.21 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 662.20 | 0.00 | 01-JAN-00:10 | 858886.85 | 03-JAN-05:20 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 662.20 | 0.00 | 01-JAN-00:10 | 858886.85 | 03-JAN-05:20 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 662.20 | 0.00 | 01-JAN-00:10 | 858886.85 | 03-JAN-05:20 |
Boiler:Heating:NaturalGas | 662.20 | 0.00 | 01-JAN-00:10 | 858886.85 | 03-JAN-05:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 10433.02 | 0.00 | 01-JAN-00:20 | 2619065.92 | 15-AUG-16:00 |
PlantLoopCoolingDemand:HVAC | 10433.02 | 0.00 | 01-JAN-00:20 | 2619065.92 | 15-AUG-16:00 |
CoolingCoils:PlantLoopCoolingDemand | 10433.02 | 0.00 | 01-JAN-00:20 | 2619065.92 | 15-AUG-16:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9590.60 | 0.00 | 01-JAN-00:30 | 0.00 | 29-SEP-10:00 |
Water:HVAC | 130.73 | 0.00 | 01-JAN-00:30 | 0.00 | 15-JAN-10:40 |
Humidifier:Water | 130.73 | 0.00 | 01-JAN-00:30 | 0.00 | 15-JAN-10:40 |
General:Humidifier:Water | 130.73 | 0.00 | 01-JAN-00:30 | 0.00 | 15-JAN-10:40 |
MainsWater:Facility | 9590.60 | 0.00 | 01-JAN-00:30 | 0.00 | 29-SEP-10:00 |
MainsWater:HVAC | 130.73 | 0.00 | 01-JAN-00:30 | 0.00 | 15-JAN-10:40 |
Humidifier:MainsWater | 130.73 | 0.00 | 01-JAN-00:30 | 0.00 | 15-JAN-10:40 |
General:Humidifier:MainsWater | 130.73 | 0.00 | 01-JAN-00:30 | 0.00 | 15-JAN-10:40 |
Water:Plant | 9459.87 | 0.00 | 01-JAN-00:10 | 0.00 | 29-SEP-10:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 12-DEC-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 12-DEC-12:10 |
MainsWater:Plant | 9459.87 | 0.00 | 01-JAN-00:10 | 0.00 | 29-SEP-10:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 12-DEC-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 12-DEC-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 7179.70 | 0.00 | 01-JAN-00:10 | 0.00 | 29-SEP-10:00 |
General:HeatRejection:Water | 7179.70 | 0.00 | 01-JAN-00:10 | 0.00 | 29-SEP-10:00 |
HeatRejection:MainsWater | 7179.70 | 0.00 | 01-JAN-00:10 | 0.00 | 29-SEP-10:00 |
General:HeatRejection:MainsWater | 7179.70 | 0.00 | 01-JAN-00:10 | 0.00 | 29-SEP-10:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 69385.51 | 103618.25 | 09-JAN-04:40 | 12641506.37 | 15-AUG-16:00 |
EnergyTransfer:Building | 21798.32 | 88846.23 | 08-JAN-09:20 | 1786157.19 | 16-OCT-14:10 |
EnergyTransfer:Zone:BASEMENT | 745.07 | 0.00 | 01-JAN-00:10 | 81258.55 | 01-MAY-07:50 |
Heating:EnergyTransfer | 109.81 | 0.00 | 02-JAN-17:10 | 431799.87 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.58 | 0.00 | 01-JAN-00:10 | 10499.96 | 14-OCT-16:10 |
General:Heating:EnergyTransfer | 109.81 | 0.00 | 02-JAN-17:10 | 431799.87 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.58 | 0.00 | 01-JAN-00:10 | 10499.96 | 14-OCT-16:10 |
Cooling:EnergyTransfer | 21688.51 | 87601.78 | 08-JAN-09:20 | 1786157.19 | 16-OCT-14:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 744.49 | 0.00 | 01-JAN-00:10 | 81258.55 | 01-MAY-07:50 |
General:Cooling:EnergyTransfer | 21688.51 | 87601.78 | 08-JAN-09:20 | 1786157.19 | 16-OCT-14:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 744.49 | 0.00 | 01-JAN-00:10 | 81258.55 | 01-MAY-07:50 |
EnergyTransfer:Zone:CORE_BOTTOM | 674.76 | 0.00 | 01-JAN-00:10 | 58201.87 | 07-AUG-13:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 674.76 | 0.00 | 01-JAN-00:10 | 58201.87 | 07-AUG-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 674.76 | 0.00 | 01-JAN-00:10 | 58201.87 | 07-AUG-13:10 |
EnergyTransfer:Zone:CORE_MID | 5253.24 | 0.00 | 01-JAN-00:10 | 482818.76 | 17-OCT-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5253.24 | 0.00 | 01-JAN-00:10 | 482818.76 | 17-OCT-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5253.24 | 0.00 | 01-JAN-00:10 | 482818.76 | 17-OCT-16:00 |
EnergyTransfer:Zone:CORE_TOP | 510.67 | 0.00 | 01-JAN-00:10 | 59506.64 | 16-OCT-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.76 | 0.00 | 01-JAN-00:10 | 34957.31 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.76 | 0.00 | 01-JAN-00:10 | 34957.31 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 509.92 | 0.00 | 01-JAN-00:10 | 59506.64 | 16-OCT-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 509.92 | 0.00 | 01-JAN-00:10 | 59506.64 | 16-OCT-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.84 | 0.00 | 01-JAN-00:10 | 13084.81 | 29-SEP-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.11 | 0.00 | 01-JAN-00:10 | 4797.35 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.11 | 0.00 | 01-JAN-00:10 | 4797.35 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.73 | 0.00 | 01-JAN-00:10 | 13084.81 | 29-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.73 | 0.00 | 01-JAN-00:10 | 13084.81 | 29-SEP-13:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 102.13 | 0.00 | 01-JAN-00:10 | 17597.69 | 29-SEP-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.14 | 0.00 | 01-JAN-00:10 | 3700.84 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.14 | 0.00 | 01-JAN-00:10 | 3700.84 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 101.98 | 0.00 | 01-JAN-00:10 | 17597.69 | 29-SEP-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 101.98 | 0.00 | 01-JAN-00:10 | 17597.69 | 29-SEP-08:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 166.49 | 0.00 | 01-JAN-00:10 | 30263.31 | 31-OCT-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.26 | 0.00 | 01-JAN-00:10 | 6255.34 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.26 | 0.00 | 01-JAN-00:10 | 6255.34 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 166.24 | 0.00 | 01-JAN-00:10 | 30263.31 | 31-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 166.24 | 0.00 | 01-JAN-00:10 | 30263.31 | 31-OCT-12:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 138.51 | 0.00 | 01-JAN-00:10 | 21672.73 | 18-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1645.68 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1645.68 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 138.50 | 0.00 | 01-JAN-00:10 | 21672.73 | 18-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 138.50 | 0.00 | 01-JAN-00:10 | 21672.73 | 18-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 676.58 | 0.00 | 01-JAN-00:10 | 124792.43 | 29-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 23.53 | 0.00 | 01-JAN-00:10 | 104728.90 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 23.53 | 0.00 | 01-JAN-00:10 | 104728.90 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 653.04 | 0.00 | 01-JAN-00:10 | 124792.43 | 29-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 653.04 | 0.00 | 01-JAN-00:10 | 124792.43 | 29-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 846.88 | 0.00 | 01-JAN-00:10 | 174984.82 | 29-SEP-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 11.79 | 0.00 | 01-JAN-00:10 | 72934.73 | 03-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 11.79 | 0.00 | 01-JAN-00:10 | 72934.73 | 03-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 835.09 | 0.00 | 01-JAN-00:10 | 174984.82 | 29-SEP-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 835.09 | 0.00 | 01-JAN-00:10 | 174984.82 | 29-SEP-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1508.68 | 0.00 | 01-JAN-00:10 | 303691.63 | 31-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 13.87 | 0.00 | 01-JAN-00:10 | 93684.97 | 30-MAR-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 13.87 | 0.00 | 01-JAN-00:10 | 93684.97 | 30-MAR-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1494.81 | 0.00 | 01-JAN-00:10 | 303691.63 | 31-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1494.81 | 0.00 | 01-JAN-00:10 | 303691.63 | 31-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 996.76 | 0.00 | 01-JAN-00:10 | 204155.74 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 10.81 | 0.00 | 01-JAN-00:10 | 61232.07 | 03-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 10.81 | 0.00 | 01-JAN-00:10 | 61232.07 | 03-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 985.95 | 0.00 | 01-JAN-00:10 | 204155.74 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 985.95 | 0.00 | 01-JAN-00:10 | 204155.74 | 29-SEP-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 76.80 | 0.00 | 01-JAN-00:10 | 17624.54 | 09-JAN-05:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 7.95 | 0.00 | 01-JAN-00:10 | 17624.54 | 09-JAN-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 7.95 | 0.00 | 01-JAN-00:10 | 17624.54 | 09-JAN-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 68.85 | 0.00 | 01-JAN-00:10 | 13870.26 | 29-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 68.85 | 0.00 | 01-JAN-00:10 | 13870.26 | 29-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 88.39 | 0.00 | 01-JAN-00:10 | 17081.00 | 29-SEP-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 3.82 | 0.00 | 01-JAN-00:10 | 12571.37 | 09-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 3.82 | 0.00 | 01-JAN-00:10 | 12571.37 | 09-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 84.57 | 0.00 | 01-JAN-00:10 | 17081.00 | 29-SEP-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 84.57 | 0.00 | 01-JAN-00:10 | 17081.00 | 29-SEP-09:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 150.77 | 0.00 | 01-JAN-00:10 | 32345.19 | 31-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.24 | 0.00 | 01-JAN-00:10 | 17063.49 | 09-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.24 | 0.00 | 01-JAN-00:10 | 17063.49 | 09-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 145.53 | 0.00 | 01-JAN-00:10 | 32345.19 | 31-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 145.53 | 0.00 | 01-JAN-00:10 | 32345.19 | 31-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 100.10 | 0.00 | 01-JAN-00:10 | 21264.18 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 3.49 | 0.00 | 01-JAN-00:10 | 11083.13 | 09-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 3.49 | 0.00 | 01-JAN-00:10 | 11083.13 | 09-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 96.61 | 0.00 | 01-JAN-00:10 | 21264.18 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 96.61 | 0.00 | 01-JAN-00:10 | 21264.18 | 29-SEP-15:30 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 102.29 | 0.00 | 01-JAN-00:10 | 11188.51 | 16-OCT-15:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.76 | 0.00 | 01-JAN-00:10 | 3423.19 | 21-MAY-12:50 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.76 | 0.00 | 01-JAN-00:10 | 3423.19 | 21-MAY-12:50 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 101.53 | 0.00 | 01-JAN-00:10 | 11188.51 | 16-OCT-15:30 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 101.53 | 0.00 | 01-JAN-00:10 | 11188.51 | 16-OCT-15:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 702.15 | 0.00 | 01-JAN-00:10 | 88618.39 | 25-MAR-17:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.10 | 0.00 | 01-JAN-00:10 | 39166.79 | 15-OCT-14:50 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.10 | 0.00 | 01-JAN-00:10 | 39166.79 | 15-OCT-14:50 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 695.05 | 0.00 | 01-JAN-00:10 | 88618.39 | 25-MAR-17:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 695.05 | 0.00 | 01-JAN-00:10 | 88618.39 | 25-MAR-17:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 176.81 | 0.00 | 01-JAN-00:10 | 33206.24 | 19-JUL-13:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 17.53 | 0.00 | 01-JAN-00:10 | 23958.98 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 17.53 | 0.00 | 01-JAN-00:10 | 23958.98 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 159.28 | 0.00 | 01-JAN-00:10 | 33206.24 | 19-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 159.28 | 0.00 | 01-JAN-00:10 | 33206.24 | 19-JUL-13:10 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.89 | 696.58 | 08-JAN-07:30 | 8245.00 | 18-DEC-16:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.89 | 696.58 | 08-JAN-07:30 | 8245.00 | 18-DEC-16:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.89 | 696.58 | 08-JAN-07:30 | 8245.00 | 18-DEC-16:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1234.63 | 8.79 | 09-JAN-03:20 | 77284.90 | 18-DEC-16:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.09 | 0.00 | 01-JAN-00:10 | 3437.73 | 02-JAN-00:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.09 | 0.00 | 01-JAN-00:10 | 3437.73 | 02-JAN-00:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1234.54 | 0.00 | 01-JAN-00:40 | 77284.90 | 18-DEC-16:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1234.54 | 0.00 | 01-JAN-00:40 | 77284.90 | 18-DEC-16:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 115.79 | 5.06 | 13-JAN-00:20 | 7861.25 | 17-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.54 | 0.00 | 02-JAN-09:20 | 1310.48 | 09-JAN-03:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.54 | 0.00 | 02-JAN-09:20 | 1310.48 | 09-JAN-03:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 115.25 | 0.00 | 01-JAN-00:10 | 7861.25 | 17-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 115.25 | 0.00 | 01-JAN-00:10 | 7861.25 | 17-AUG-16:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7206.09 | 86390.05 | 08-JAN-11:50 | 394290.35 | 28-DEC-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 1.44 | 0.00 | 01-JAN-00:10 | 5169.73 | 23-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 1.44 | 0.00 | 01-JAN-00:10 | 5169.73 | 23-FEB-05:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7204.65 | 86390.05 | 08-JAN-11:50 | 394290.35 | 28-DEC-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7204.65 | 86390.05 | 08-JAN-11:50 | 394290.35 | 28-DEC-18:00 |
PlantLoopHeatingDemand:Facility | 818.03 | 0.00 | 01-JAN-00:10 | 615242.84 | 09-JAN-06:10 |
PlantLoopHeatingDemand:Plant | 387.53 | 0.00 | 01-JAN-00:10 | 44746.54 | 02-FEB-12:40 |
WaterSystems:PlantLoopHeatingDemand | 387.53 | 0.00 | 01-JAN-00:10 | 44746.54 | 02-FEB-12:40 |
General:WaterSystems:PlantLoopHeatingDemand | 387.53 | 0.00 | 01-JAN-00:10 | 44746.54 | 02-FEB-12:40 |
EnergyTransfer:HVAC | 12803.50 | 12738.67 | 08-JAN-07:50 | 2729224.00 | 15-AUG-16:00 |
HeatingCoils:EnergyTransfer | 430.50 | 0.00 | 01-JAN-00:10 | 609769.84 | 09-JAN-06:10 |
PlantLoopHeatingDemand:HVAC | 430.50 | 0.00 | 01-JAN-00:10 | 609769.84 | 09-JAN-06:10 |
HeatingCoils:PlantLoopHeatingDemand | 430.50 | 0.00 | 01-JAN-00:10 | 609769.84 | 09-JAN-06:10 |
CoolingCoils:EnergyTransfer | 12373.00 | 10356.82 | 09-JAN-07:20 | 2729224.00 | 15-AUG-16:00 |
EnergyTransfer:Plant | 34783.70 | 0.00 | 01-JAN-00:20 | 8216970.73 | 15-AUG-16:00 |
LoopToLoop:EnergyTransfer | 10615.38 | 0.00 | 01-JAN-00:20 | 2619864.50 | 15-AUG-16:00 |
WaterSystems:EnergyTransfer | 387.53 | 0.00 | 01-JAN-00:10 | 44746.54 | 02-FEB-12:40 |
WaterUse:WaterSystems:EnergyTransfer | 387.53 | 0.00 | 01-JAN-00:10 | 44746.54 | 02-FEB-12:40 |
Boilers:EnergyTransfer | 428.93 | 0.00 | 01-JAN-00:10 | 660674.55 | 03-JAN-05:20 |
Chillers:EnergyTransfer | 10765.06 | 0.00 | 01-JAN-00:20 | 2589914.45 | 15-AUG-16:00 |
HeatRejection:EnergyTransfer | 12586.80 | 0.00 | 01-JAN-00:20 | 2975883.66 | 15-AUG-16:00 |
General:HeatRejection:EnergyTransfer | 12586.80 | 0.00 | 01-JAN-00:20 | 2975883.66 | 15-AUG-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.577 | -744.488 | 0.000 | 0.000 | 93.196 | 333.789 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -107.472 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -674.760 | 0.000 | 0.000 | 83.474 | 299.766 | 289.614 | 0.000 | 0.000 | 0.000 | 1.906 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5253.255 | 0.000 | 0.000 | 839.451 | 2997.664 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1479.988 |
CORE_TOP | 0.000 | 0.000 | 0.758 | -509.916 | 0.000 | 0.000 | 85.924 | 299.766 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -166.145 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.112 | -86.729 | 0.000 | 0.000 | 10.771 | 37.639 | 36.365 | 29.349 | 0.000 | 0.021 | 65.942 | 0.000 | -91.135 | 0.000 | -2.336 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.143 | -101.985 | 0.000 | 0.000 | 7.072 | 24.256 | 23.435 | 76.367 | 0.000 | 0.016 | 27.282 | 0.000 | -55.092 | 0.000 | -1.494 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.257 | -166.238 | 0.000 | 0.000 | 10.781 | 37.639 | 36.366 | 152.240 | 0.000 | 0.018 | 18.255 | 0.000 | -86.942 | 0.000 | -2.376 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.007 | -138.505 | 0.000 | 0.000 | 7.113 | 24.256 | 23.435 | 83.308 | 0.000 | 0.016 | 67.877 | 0.000 | -65.796 | 0.000 | -1.710 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 23.534 | -653.046 | 0.000 | 0.000 | 111.341 | 376.387 | 363.654 | 312.662 | 0.000 | 0.615 | 328.104 | 0.000 | -816.271 | 0.000 | -46.981 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 11.790 | -835.097 | 0.000 | 0.000 | 52.727 | 242.558 | 234.352 | 748.136 | 0.000 | 0.335 | 93.823 | 0.000 | -516.327 | 0.000 | -32.299 | -0.008 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 13.874 | -1494.832 | 0.000 | 0.000 | 109.142 | 376.395 | 363.660 | 1490.407 | 0.000 | 0.415 | 27.785 | 0.000 | -834.562 | 0.000 | -52.283 | -0.001 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 10.808 | -985.961 | 0.000 | 0.000 | 74.182 | 242.558 | 234.351 | 839.704 | 0.000 | 0.561 | 184.289 | 0.000 | -566.906 | 0.000 | -33.584 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 7.948 | -68.848 | 0.000 | 0.000 | 11.401 | 37.639 | 36.365 | 31.965 | 0.000 | 0.088 | 23.370 | 0.000 | -74.671 | 0.000 | -5.257 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 3.816 | -84.575 | 0.000 | 0.000 | 7.227 | 24.256 | 23.435 | 75.546 | 0.000 | 0.044 | 1.816 | 0.000 | -47.896 | 0.000 | -3.668 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 5.243 | -145.532 | 0.000 | 0.000 | 11.057 | 37.639 | 36.366 | 148.615 | 0.000 | 0.052 | 0.003 | 0.000 | -77.458 | 0.000 | -6.008 | -9.974 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 3.488 | -96.615 | 0.000 | 0.000 | 7.464 | 24.256 | 23.435 | 82.562 | 0.000 | 0.069 | 12.406 | 0.000 | -53.150 | 0.000 | -3.915 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -137.895 | 0.000 | 0.000 | 0.950 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -25.283 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.092 | -1234.542 | 0.000 | 0.000 | 9.502 | 83.466 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -397.323 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.536 | -115.250 | 0.000 | 0.000 | 0.950 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -48.464 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 1.435 | -7204.590 | 0.000 | 0.000 | 21.963 | 94.114 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -407.780 |
GROUNDFLOOR_PLENUM | 0.762 | -101.532 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.034 | 106.292 | 0.000 | 0.000 | 0.000 | -5.555 | 0.000 |
MIDFLOOR_PLENUM | 7.098 | -695.050 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.677 | 780.899 | 0.000 | 0.000 | 0.000 | -93.624 | 0.000 |
TOPFLOOR_PLENUM | 17.530 | -159.282 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.048 | 151.270 | 0.000 | 0.000 | 0.000 | -9.567 | -0.000 |
Total Facility | 25.390 | -955.864 | 84.420 | -20732.657 | 0.000 | 0.000 | 1555.689 | 5610.736 | 14676.396 | 4070.860 | 0.000 | 3.007 | 1891.319 | 0.000 | -3286.208 | 0.000 | -300.656 | -2642.440 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 30-OCT-04:11 | 0.00 | 0.00 | 0.00 | -145162.83 | 0.00 | 0.00 | 0.00 | 3238.31 | 13457.54 | 0.00 | 0.00 | 0.00 | 128466.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 28-AUG-04:11 | 0.00 | 0.00 | 0.00 | -119570.00 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.65 | 0.00 | 0.00 | 0.00 | 110724.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 17-OCT-04:11 | 0.00 | 0.00 | 0.00 | -1034148.78 | 0.00 | 0.00 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 945690.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 28-JUN-05:01 | 0.00 | 0.00 | 0.00 | -107314.59 | 0.00 | 0.00 | 876.26 | 2908.23 | 7647.36 | 0.00 | 0.00 | 0.00 | 95882.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 29-SEP-13:00 | 0.00 | 0.00 | 0.00 | -13085.87 | 0.00 | 0.00 | 1114.37 | 3286.42 | 2160.55 | 10210.87 | 0.00 | 82.55 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3768.88 |
PERIMETER_BOT_ZN_2 | 23-JUL-08:21 | 0.00 | 0.00 | 0.00 | -36379.60 | 0.00 | 0.00 | 16.81 | 117.66 | 464.11 | 20259.99 | 0.00 | 0.00 | 15560.41 | 0.00 | -0.00 | 0.00 | -39.37 | 0.00 |
PERIMETER_BOT_ZN_1 | 29-OCT-12:21 | 0.00 | 0.00 | 0.00 | -43933.50 | 0.00 | 0.00 | 24.31 | 182.58 | 720.19 | 32650.15 | 0.00 | 0.00 | 10568.11 | 0.00 | -0.00 | 0.00 | -211.84 | 0.00 |
PERIMETER_BOT_ZN_4 | 23-JUL-16:21 | 0.00 | 0.00 | 0.00 | -46154.57 | 0.00 | 0.00 | 13.86 | 117.66 | 464.11 | 18819.46 | 0.00 | 0.00 | 26826.59 | 0.00 | -0.00 | 0.00 | -87.10 | 0.00 |
PERIMETER_MID_ZN_3 | 29-SEP-13:10 | 0.00 | 0.00 | 0.00 | -124804.62 | 0.00 | 0.00 | 11651.77 | 32864.16 | 21605.52 | 100803.77 | 0.00 | 1942.18 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -44062.78 |
PERIMETER_MID_ZN_2 | 15-OCT-09:21 | 0.00 | 0.00 | 0.00 | -362855.73 | 0.00 | 0.00 | 170.00 | 1176.61 | 4641.14 | 164790.24 | 0.00 | 1044.84 | 191032.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 15-OCT-12:41 | 0.00 | 0.00 | 0.00 | -447352.55 | 0.00 | 0.00 | 186.50 | 1825.83 | 7201.95 | 309008.20 | 0.00 | 476.29 | 128653.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 15-OCT-15:21 | 0.00 | 0.00 | 0.00 | -415029.62 | 0.00 | 0.00 | 141.70 | 1176.61 | 4641.11 | 211184.85 | 0.00 | 101.81 | 197783.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 29-SEP-13:10 | 0.00 | 0.00 | 0.00 | -13871.61 | 0.00 | 0.00 | 1165.18 | 3286.42 | 2160.55 | 9925.97 | 0.00 | 238.86 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2905.36 |
PERIMETER_TOP_ZN_2 | 23-JUL-08:51 | 0.00 | 0.00 | 0.00 | -36592.23 | 0.00 | 0.00 | 17.47 | 117.66 | 464.11 | 18039.08 | 0.00 | 0.00 | 18140.51 | 0.00 | -0.00 | 0.00 | -186.61 | 0.00 |
PERIMETER_TOP_ZN_1 | 15-OCT-12:11 | 0.00 | 0.00 | 0.00 | -50122.46 | 0.00 | 0.00 | 17.90 | 182.58 | 720.19 | 31980.26 | 0.00 | 45.15 | 17176.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 15-OCT-15:31 | 0.00 | 0.00 | 0.00 | -44920.19 | 0.00 | 0.00 | 12.97 | 117.66 | 464.11 | 19807.58 | 0.00 | 0.00 | 24526.00 | 0.00 | -0.00 | 0.00 | -8.14 | 0.00 |
DATACENTER_BOT_ZN_6 | 18-DEC-16:10 | 0.00 | 0.00 | 0.00 | -8244.76 | 0.00 | 0.00 | 100.85 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -379.30 |
DATACENTER_MID_ZN_6 | 18-DEC-16:20 | 0.00 | 0.00 | 0.00 | -77282.69 | 0.00 | 0.00 | 1008.50 | 7287.84 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8957.87 |
DATACENTER_TOP_ZN_6 | 17-AUG-16:00 | 0.00 | 0.00 | 0.00 | -7861.09 | 0.00 | 0.00 | 100.84 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -762.96 |
DATACENTER_BASEMENT_ZN_6 | 22-NOV-14:52 | 0.00 | 0.00 | 0.00 | -519745.20 | 0.00 | 0.00 | 2794.44 | 8217.58 | 284724.39 | 0.00 | 0.00 | 0.00 | 224008.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 29-MAR-04:12 | 0.00 | -13402.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14442.99 | 0.00 | -0.00 | 0.00 | -1040.47 | 0.00 |
MIDFLOOR_PLENUM | 29-MAR-04:11 | 0.00 | -190649.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208319.64 | 0.00 | -0.00 | 0.00 | -17670.54 | 0.00 |
TOPFLOOR_PLENUM | 19-JUL-13:05 | 0.00 | -33288.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.66 | 33287.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-OCT-05:01 | 0.00 | 5020.71 | 0.00 | -2008403.57 | 0.00 | 0.00 | 16782.22 | 54433.43 | 379706.36 | 0.00 | 0.00 | 0.00 | 1714847.46 | 0.00 | -157715.23 | 0.00 | -4671.38 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 14-OCT-16:03 | 0.00 | 0.00 | 11455.14 | 0.00 | 0.00 | 0.00 | 520.14 | 1619.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -27051.98 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 09-JAN-05:21 | 0.00 | 0.00 | 67224.69 | 0.00 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -76070.55 |
PERIMETER_BOT_ZN_3 | 09-JAN-06:01 | 0.00 | 0.00 | 9081.92 | 0.00 | 0.00 | 0.00 | 148.27 | 365.16 | 960.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9111.46 | 0.00 | -102.63 | -1341.51 |
PERIMETER_BOT_ZN_2 | 09-JAN-06:01 | 0.00 | 0.00 | 7175.92 | 0.00 | 0.00 | 0.00 | 96.45 | 235.32 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6279.59 | 0.00 | -68.14 | -1778.78 |
PERIMETER_BOT_ZN_1 | 09-JAN-05:25 | 0.00 | 0.00 | 13814.15 | 0.00 | 0.00 | 0.00 | 0.00 | 365.17 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8529.42 | 0.00 | -341.17 | -6054.30 |
PERIMETER_BOT_ZN_4 | 30-MAR-05:01 | 0.00 | 0.00 | 4717.65 | 0.00 | 0.00 | 0.00 | 94.15 | 235.32 | 618.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5442.28 | 0.00 | -79.35 | -144.31 |
PERIMETER_MID_ZN_3 | 03-JAN-05:11 | 0.00 | 0.00 | 144376.06 | 0.00 | 0.00 | 0.00 | 0.00 | 3651.57 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -76827.13 | 0.00 | -5264.85 | -73391.27 |
PERIMETER_MID_ZN_2 | 03-JAN-05:11 | 0.00 | 0.00 | 140290.04 | 0.00 | 0.00 | 0.00 | 0.00 | 2353.21 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -50571.69 | 0.00 | -3513.11 | -93363.13 |
PERIMETER_MID_ZN_1 | 30-MAR-04:11 | 0.00 | 0.00 | 178260.17 | 0.00 | 0.00 | 0.00 | 0.00 | 3651.65 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -74914.31 | 0.00 | -9831.58 | -104621.67 |
PERIMETER_MID_ZN_4 | 03-JAN-05:11 | 0.00 | 0.00 | 130850.42 | 0.00 | 0.00 | 0.00 | 0.00 | 2353.21 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -50374.93 | 0.00 | -3660.71 | -83972.63 |
PERIMETER_TOP_ZN_3 | 09-JAN-05:21 | 0.00 | 0.00 | 21090.37 | 0.00 | 0.00 | 0.00 | 0.00 | 365.16 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5940.28 | 0.00 | -738.70 | -15522.10 |
PERIMETER_TOP_ZN_2 | 09-JAN-05:21 | 0.00 | 0.00 | 18584.59 | 0.00 | 0.00 | 0.00 | 0.00 | 235.32 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4180.27 | 0.00 | -500.82 | -14619.30 |
PERIMETER_TOP_ZN_1 | 09-JAN-05:21 | 0.00 | 0.00 | 24625.04 | 0.00 | 0.00 | 0.00 | 0.00 | 365.17 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6703.82 | 0.00 | -771.01 | -18260.95 |
PERIMETER_TOP_ZN_4 | 09-JAN-05:21 | 0.00 | 0.00 | 18988.07 | 0.00 | 0.00 | 0.00 | 0.00 | 235.32 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4248.69 | 0.00 | -521.26 | -14933.90 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 02-JAN-00:23 | 0.00 | 0.00 | 8025.95 | 0.00 | 0.00 | 0.00 | 0.00 | 404.88 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -27916.88 |
DATACENTER_TOP_ZN_6 | 09-JAN-03:25 | 0.00 | 0.00 | 1311.64 | 0.00 | 0.00 | 0.00 | 0.00 | 40.49 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3300.73 |
DATACENTER_BASEMENT_ZN_6 | 23-FEB-05:11 | 0.00 | 0.00 | 50818.63 | 0.00 | 0.00 | 0.00 | 0.00 | 913.06 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -241547.95 |
GROUNDFLOOR_PLENUM | 15-OCT-14:21 | 17450.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.85 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17743.41 |
MIDFLOOR_PLENUM | 15-OCT-14:42 | 178627.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5237.95 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -183865.78 |
TOPFLOOR_PLENUM | 09-JAN-06:13 | 31026.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -367.84 | -30658.27 |
Total Facility | 09-JAN-06:01 | -502340.68 | 454223.62 | 724044.39 | -454223.62 | 0.00 | 0.00 | 19740.92 | 54433.43 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -358727.17 | 0.00 | -14047.97 | -184517.89 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 14.9512 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 12.6783 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 142.6446 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 116.0747 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 15.8732 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 14.4622 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 7.2487 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 7.2487 | 0.1656 | 1.0000 | Not calculated | 1.2002 | 0.1656 | ||
AIRLOOP DATACENTER BASEMENT | 32.0158 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 32.0160 | 0.0106 | 1.0000 | Not calculated | 0.3384 | 0.0106 | ||
AIRLOOP DATACENTER BOT | 0.7496 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7496 | 0.0209 | 1.0000 | Not calculated | 0.0156 | 0.0209 | ||
AIRLOOP DATACENTER MID | 7.1683 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 7.1683 | 0.0218 | 1.0000 | Not calculated | 0.1563 | 0.0218 | ||
AIRLOOP DATACENTER TOP | 0.7410 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7410 | 0.0211 | 1.0000 | Not calculated | 0.0156 | 0.0211 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 7.4756 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.4854 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 71.3223 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 42.7934 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 7.9366 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7620 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 2.1746 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 2.1746 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.5519 | ||
AIRLOOP DATACENTER BASEMENT | 16.0079 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 16.0079 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0211 | ||
AIRLOOP DATACENTER BOT | 0.7496 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7496 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0209 | ||
AIRLOOP DATACENTER MID | 7.1683 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 7.1683 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0218 | ||
AIRLOOP DATACENTER TOP | 0.7410 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7410 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0211 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 7.2487 | 7.2487 | 2.1746 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.4875 | 7.4875 | 2.2462 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 70.7428 | 70.7428 | 21.2229 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.9298 | 7.9298 | 2.3789 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3237 | 1.3237 | 0.3971 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8190 | 1.8190 | 0.5457 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0886 | 2.0886 | 0.6266 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2324 | 2.2324 | 0.6697 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.9531 | 12.9531 | 3.8859 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.4834 | 18.4834 | 5.5450 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 20.3097 | 20.3097 | 6.0929 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 20.1554 | 20.1554 | 6.0466 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6566 | 1.6566 | 0.4970 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8522 | 1.8522 | 0.5557 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2701 | 2.2701 | 0.6810 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1645 | 2.1645 | 0.6494 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7496 | 0.7496 | 0.7496 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.1683 | 7.1683 | 7.1683 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7410 | 0.7410 | 0.7410 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 32.0158 | 32.0158 | 16.0079 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 14.9512 | 12.6783 | 14.9512 | 4.4854 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 142.6446 | 116.0747 | 142.6446 | 42.7934 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 15.8732 | 14.4622 | 15.8732 | 4.7620 | 0.0000 | 1.0000 |
CAV_BAS | 7.2487 | 7.2487 | 7.2487 | 2.1746 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 32.0158 | 32.0160 | 32.0158 | 16.0079 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.7496 | 0.7496 | 0.7496 | 0.7496 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 7.1683 | 7.1683 | 7.1683 | 7.1683 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.7410 | 0.7410 | 0.7410 | 0.7410 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 2.1746 | 2.1746 | 2.1746 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7437 | 3.7437 | 2.2462 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 35.3714 | 35.3714 | 21.2229 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.9649 | 3.9649 | 2.3789 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6619 | 0.6619 | 0.3971 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9095 | 0.9095 | 0.5457 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0443 | 1.0443 | 0.6266 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1162 | 1.1162 | 0.6697 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.4766 | 6.4766 | 3.8859 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.2417 | 9.2417 | 5.5450 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.1549 | 10.1549 | 6.0929 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.0777 | 10.0777 | 6.0466 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8283 | 0.8283 | 0.4970 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9261 | 0.9261 | 0.5557 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1351 | 1.1351 | 0.6810 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0823 | 1.0823 | 0.6494 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7496 | 0.7496 | 0.7496 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.1683 | 7.1683 | 7.1683 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7410 | 0.7410 | 0.7410 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 16.0079 | 16.0079 | 16.0079 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 7.4756 | 4.4854 | 4.4854 | 4.4854 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 71.3223 | 42.7934 | 42.7934 | 42.7934 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 7.9366 | 4.7620 | 4.7620 | 4.7620 | 0.0000 | 1.0000 |
CAV_BAS | 2.1746 | 2.1746 | 2.1746 | 2.1746 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 16.0079 | 16.0079 | 16.0079 | 16.0079 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.7496 | 0.7496 | 0.7496 | 0.7496 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 7.1683 | 7.1683 | 7.1683 | 7.1683 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.7410 | 0.7410 | 0.7410 | 0.7410 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.67 |
Number of hours cooling loads not met | 216.67 |
Number of hours not met | 217.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 662.20 | 858886.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2284.00 | 412099.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 5610.74 | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 1007.50 | 64082.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 56.04 | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.31 | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2821.10 | 280698.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 970.24 | 94584.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 162.97 | 48088.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 351.41 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 392.84 | 45273.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 30900.30 |
Natural Gas | 0.00 | 662.20 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 31562.50 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 121.13 |
Space Heating | 0.00 |
Space Cooling | 49.31 |
Fans (All) | 60.90 |
Service Water Heating | 8.48 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 667.10 |
Subtotal | 667.10 |
Natural Gas [MJ/m2] | |
Space Heating | 14.30 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 14.30 |
Subtotal | 14.30 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 17.78 |
Space Heating | 2.10 |
Space Cooling | 7.24 |
Fans (All) | 8.94 |
Service Water Heating | 1.24 |
Receptacle Equipment | 46.50 |
Miscellaneous | 16.21 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
LTG_SCH_DATACENTER | 2939. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8279.17 | 480.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8682.50 | 77.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8710.67 | 49.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8695.50 | 64.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8562.67 | 197.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8716.00 | 44.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8701.17 | 58.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8704.00 | 56.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8721.50 | 38.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8710.83 | 49.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8703.50 | 56.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 3416.33 | 5343.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 3372.33 | 5387.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 3179.33 | 5580.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5913.83 | 2846.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8567.00 | 193.00 | 0.00 | 0.00 | 0.00 |
Min | 3179.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 5580.67 | 0.00 | 0.00 | 0.00 |
Average | 7867.67 | 892.33 | 0.00 | 0.00 | 0.00 |
Sum | 180956.33 | 20523.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367454.00 | 1162.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330780.00 | 33.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 538.83 | 1729.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 534.17 | 1733.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 529.83 | 1738.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 58907.67 | 44487.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367454.00 | 44487.33 | 0.00 | 0.00 | 0.00 |
Average | 78122.59 | 2212.33 | 0.00 | 0.00 | 0.00 |
Sum | 1796819.50 | 50883.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 7847.17 | 912.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 7638.33 | 1121.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8058.83 | 701.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8566.33 | 193.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8704.50 | 55.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8664.33 | 95.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8632.67 | 127.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8010.33 | 749.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8672.50 | 87.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8643.50 | 116.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8589.67 | 170.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8755.83 | 4.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8673.17 | 86.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8656.17 | 103.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8601.33 | 158.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 5368.50 | 3391.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 5274.67 | 3485.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 5169.83 | 3590.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6036.67 | 2723.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8259.83 | 500.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8739.00 | 21.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7766.33 | 993.67 | 0.00 | 0.00 | 0.00 |
Min | 5169.83 | 4.17 | 0.00 | 0.00 | 0.00 |
Max | 8755.83 | 3590.17 | 0.00 | 0.00 | 0.00 |
Average | 7916.67 | 843.33 | 0.00 | 0.00 | 0.00 |
Sum | 182083.33 | 19396.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 366088.83 | 2527.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 329329.00 | 1484.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 329886.00 | 927.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330524.00 | 289.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 869.67 | 1398.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 842.67 | 1425.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 806.83 | 1461.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 62000.33 | 41394.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 366088.83 | 41394.67 | 0.00 | 0.00 | 0.00 |
Average | 78121.58 | 2213.33 | 0.00 | 0.00 | 0.00 |
Sum | 1796796.33 | 50906.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:21
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.614044E+11 | 139719.73 | 02-JAN-05:11 | 11.00 | 9.07 | 0.556858E+10 | 7499.33 | 03-JAN-14:30 | 17.50 | 9.79 |
February | 0.525175E+11 | 140761.62 | 21-FEB-05:11 | 8.00 | 6.97 | 0.506298E+10 | 7499.34 | 17-FEB-14:50 | 8.00 | 6.97 |
March | 0.622620E+11 | 123871.24 | 20-MAR-04:11 | 11.00 | 10.65 | 0.606387E+10 | 7499.34 | 24-MAR-09:00 | 17.00 | 14.51 |
April | 0.594993E+11 | 122577.89 | 10-APR-04:12 | 12.00 | 10.34 | 0.539773E+10 | 7499.34 | 18-APR-13:20 | 17.00 | 12.41 |
May | 0.605901E+11 | 131054.77 | 27-MAY-04:12 | 8.67 | 7.61 | 0.584352E+10 | 7499.33 | 11-MAY-13:00 | 8.67 | 7.61 |
June | 0.614316E+11 | 134764.14 | 05-JUN-04:11 | 12.00 | 10.91 | 0.586967E+10 | 7502.70 | 27-JUN-09:00 | 23.00 | 18.43 |
July | 0.639259E+11 | 115242.64 | 10-JUL-04:11 | 17.00 | 13.94 | 0.547140E+10 | 7500.41 | 27-JUL-09:50 | 22.00 | 18.09 |
August | 0.712429E+11 | 112389.59 | 22-AUG-04:11 | 15.67 | 13.45 | 0.613361E+10 | 7513.87 | 07-AUG-09:00 | 15.67 | 13.45 |
September | 0.610963E+11 | 121176.15 | 20-SEP-04:12 | 11.33 | 10.20 | 0.543867E+10 | 7507.33 | 22-SEP-13:00 | 22.00 | 18.63 |
October | 0.651793E+11 | 145198.22 | 30-OCT-04:11 | 9.67 | 6.78 | 0.566516E+10 | 7557.43 | 30-OCT-13:09 | 26.17 | 16.67 |
November | 0.629382E+11 | 125929.85 | 24-NOV-05:11 | 8.33 | 1.20 | 0.558443E+10 | 7499.34 | 21-NOV-14:50 | 8.33 | 1.20 |
December | 0.624031E+11 | 127134.71 | 11-DEC-05:11 | 7.67 | 7.12 | 0.539162E+10 | 7499.33 | 21-DEC-14:20 | 16.67 | 12.47 |
Annual Sum or Average | 0.744491E+12 | 0.674913E+11 | ||||||||
Minimum of Months | 0.525175E+11 | 112389.59 | 7.67 | 1.20 | 0.506298E+10 | 7499.33 | 8.00 | 1.20 | ||
Maximum of Months | 0.712429E+11 | 145198.22 | 17.00 | 13.94 | 0.613361E+10 | 7557.43 | 26.17 | 18.63 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.496273E+11 | 115035.92 | 02-JAN-05:11 | 11.00 | 9.07 | 0.506430E+10 | 6734.97 | 10-JAN-14:09 | 16.83 | 11.85 |
February | 0.450999E+11 | 109173.78 | 02-FEB-05:11 | 12.67 | 10.97 | 0.459059E+10 | 6735.00 | 01-FEB-14:09 | 12.67 | 10.97 |
March | 0.550219E+11 | 113351.03 | 24-MAR-04:11 | 12.13 | 12.13 | 0.549207E+10 | 6734.93 | 01-MAR-14:09 | 12.13 | 12.13 |
April | 0.568145E+11 | 114296.79 | 28-APR-04:11 | 14.00 | 12.23 | 0.487679E+10 | 6735.19 | 13-APR-09:00 | 14.00 | 12.23 |
May | 0.550998E+11 | 114614.34 | 01-MAY-04:12 | 13.00 | 11.87 | 0.527667E+10 | 6735.18 | 05-MAY-13:50 | 18.50 | 16.08 |
June | 0.576047E+11 | 116606.46 | 12-JUN-04:11 | 13.07 | 11.97 | 0.526865E+10 | 6734.89 | 08-JUN-09:00 | 13.07 | 11.97 |
July | 0.631730E+11 | 119244.47 | 05-JUL-04:11 | 17.00 | 14.51 | 0.489682E+10 | 6734.88 | 12-JUL-09:20 | 19.00 | 16.05 |
August | 0.706206E+11 | 119590.29 | 28-AUG-04:11 | 14.00 | 14.00 | 0.549932E+10 | 6734.71 | 01-AUG-09:20 | 14.00 | 14.00 |
September | 0.549429E+11 | 114683.71 | 05-SEP-04:12 | 16.00 | 14.34 | 0.487822E+10 | 6734.82 | 21-SEP-09:30 | 20.00 | 18.03 |
October | 0.581486E+11 | 119193.88 | 16-OCT-04:11 | 19.67 | 9.61 | 0.507301E+10 | 6735.07 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.540884E+11 | 118399.74 | 13-NOV-05:11 | 11.00 | 10.06 | 0.502549E+10 | 6735.51 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.545154E+11 | 114570.71 | 11-DEC-05:11 | 7.67 | 7.12 | 0.489287E+10 | 6736.03 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.674757E+12 | 0.608348E+11 | ||||||||
Minimum of Months | 0.450999E+11 | 109173.78 | 7.67 | 7.12 | 0.459059E+10 | 6734.71 | 12.13 | 10.97 | ||
Maximum of Months | 0.706206E+11 | 119590.29 | 19.67 | 14.51 | 0.549932E+10 | 6736.03 | 22.00 | 18.03 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388639E+11 | 98110.51 | 25-JAN-06:01 | 16.00 | 11.06 | 0.499817E+10 | 6734.96 | 10-JAN-14:09 | 16.00 | 11.06 |
February | 0.357299E+11 | 98722.92 | 02-FEB-06:01 | 12.00 | 10.34 | 0.454004E+10 | 6734.99 | 01-FEB-14:09 | 12.00 | 10.34 |
March | 0.420523E+11 | 102152.64 | 24-MAR-05:01 | 12.00 | 12.00 | 0.543799E+10 | 6734.93 | 01-MAR-14:09 | 12.00 | 12.00 |
April | 0.425343E+11 | 100087.48 | 12-APR-05:01 | 13.00 | 13.00 | 0.483406E+10 | 6735.13 | 13-APR-13:00 | 20.00 | 15.65 |
May | 0.449005E+11 | 99904.06 | 19-MAY-05:01 | 8.67 | 8.59 | 0.524568E+10 | 6735.16 | 05-MAY-13:50 | 8.67 | 8.59 |
June | 0.474939E+11 | 102927.42 | 06-JUN-05:01 | 16.00 | 13.67 | 0.524522E+10 | 6734.90 | 08-JUN-09:50 | 16.00 | 14.66 |
July | 0.484574E+11 | 101833.15 | 14-JUL-04:11 | 16.00 | 14.77 | 0.487364E+10 | 6734.88 | 12-JUL-09:20 | 16.00 | 14.77 |
August | 0.526277E+11 | 99391.92 | 23-AUG-04:11 | 15.80 | 14.08 | 0.547824E+10 | 6734.77 | 22-AUG-13:09 | 15.80 | 14.08 |
September | 0.453201E+11 | 101202.73 | 02-SEP-05:01 | 14.33 | 11.88 | 0.485422E+10 | 6734.83 | 21-SEP-09:30 | 20.00 | 18.03 |
October | 0.468709E+11 | 103369.82 | 17-OCT-04:11 | 16.33 | 8.45 | 0.504671E+10 | 6735.02 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.406615E+11 | 102717.13 | 01-NOV-05:01 | 12.83 | 9.89 | 0.497898E+10 | 6735.38 | 29-NOV-14:50 | 18.67 | 10.63 |
December | 0.398110E+11 | 99283.67 | 08-DEC-06:01 | 11.95 | 11.53 | 0.483039E+10 | 6735.93 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.525324E+12 | 0.603633E+11 | ||||||||
Minimum of Months | 0.357299E+11 | 98110.51 | 8.67 | 8.45 | 0.454004E+10 | 6734.77 | 8.67 | 8.59 | ||
Maximum of Months | 0.526277E+11 | 103369.82 | 16.33 | 14.77 | 0.547824E+10 | 6735.93 | 22.00 | 18.03 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.323917E+11 | 43981.25 | 18-JAN-15:00 | 23.00 | 14.79 | 0.467025E+10 | 6734.93 | 10-JAN-14:30 | 23.00 | 14.79 |
February | 0.310080E+11 | 45300.05 | 16-FEB-15:32 | 16.83 | 13.56 | 0.428390E+10 | 6735.00 | 01-FEB-14:09 | 16.83 | 13.56 |
March | 0.380061E+11 | 50401.70 | 23-MAR-15:40 | 21.33 | 17.27 | 0.515914E+10 | 6734.92 | 01-MAR-14:09 | 21.33 | 17.27 |
April | 0.433490E+11 | 55697.85 | 27-APR-14:50 | 19.37 | 15.15 | 0.470844E+10 | 6735.17 | 13-APR-13:00 | 19.37 | 15.15 |
May | 0.461812E+11 | 93656.01 | 03-MAY-05:01 | 14.17 | 14.07 | 0.513359E+10 | 6735.18 | 05-MAY-13:50 | 18.50 | 16.08 |
June | 0.509449E+11 | 107338.09 | 28-JUN-05:01 | 16.17 | 15.98 | 0.518983E+10 | 6734.88 | 08-JUN-09:00 | 16.17 | 15.98 |
July | 0.538184E+11 | 105526.96 | 07-JUL-05:01 | 17.00 | 14.51 | 0.484012E+10 | 6734.87 | 12-JUL-09:20 | 19.00 | 16.05 |
August | 0.569842E+11 | 102311.56 | 22-AUG-05:01 | 15.00 | 13.18 | 0.543714E+10 | 6734.75 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.458167E+11 | 102215.72 | 30-SEP-05:02 | 23.80 | 13.84 | 0.477337E+10 | 6734.81 | 27-SEP-09:20 | 23.80 | 13.84 |
October | 0.445242E+11 | 106383.27 | 06-OCT-05:01 | 19.00 | 17.08 | 0.492058E+10 | 6734.96 | 18-OCT-13:09 | 22.83 | 18.37 |
November | 0.343981E+11 | 45256.40 | 10-NOV-14:52 | 19.00 | 15.88 | 0.473656E+10 | 6735.29 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.324928E+11 | 43486.55 | 05-DEC-16:00 | 23.00 | 12.42 | 0.453127E+10 | 6735.74 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.509915E+12 | 0.583842E+11 | ||||||||
Minimum of Months | 0.310080E+11 | 43486.55 | 14.17 | 12.42 | 0.428390E+10 | 6734.75 | 16.17 | 12.37 | ||
Maximum of Months | 0.569842E+11 | 107338.09 | 23.80 | 17.27 | 0.543714E+10 | 6735.74 | 23.80 | 18.37 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.505578E+10 | 7569.36 | 24-JAN-14:30 | 24.50 | 15.08 | 0.582802E+09 | 845.64 | 13-JAN-14:20 | 24.50 | 15.08 |
February | 0.473224E+10 | 6959.94 | 01-FEB-12:00 | 26.00 | 14.67 | 0.538195E+09 | 845.65 | 01-FEB-14:09 | 19.00 | 15.70 |
March | 0.586740E+10 | 7532.41 | 23-MAR-14:00 | 23.00 | 17.27 | 0.645249E+09 | 845.64 | 01-MAR-14:09 | 23.00 | 17.27 |
April | 0.716450E+10 | 10038.82 | 26-APR-13:30 | 26.50 | 16.94 | 0.593405E+09 | 845.68 | 13-APR-13:00 | 26.50 | 16.94 |
May | 0.767356E+10 | 9942.64 | 04-MAY-13:30 | 23.00 | 16.67 | 0.646602E+09 | 845.68 | 05-MAY-13:50 | 18.50 | 16.08 |
June | 0.891510E+10 | 9276.99 | 29-JUN-16:00 | 23.00 | 18.43 | 0.654063E+09 | 845.64 | 21-JUN-13:09 | 23.00 | 18.43 |
July | 0.101296E+11 | 11211.35 | 31-JUL-13:00 | 28.00 | 21.19 | 0.610971E+09 | 845.63 | 07-JUL-13:09 | 28.00 | 21.19 |
August | 0.104500E+11 | 11128.66 | 17-AUG-14:00 | 28.00 | 21.19 | 0.684671E+09 | 845.62 | 22-AUG-13:20 | 22.33 | 16.84 |
September | 0.772162E+10 | 13084.81 | 29-SEP-13:00 | 36.00 | 18.20 | 0.599711E+09 | 845.63 | 01-SEP-13:09 | 36.00 | 18.20 |
October | 0.785161E+10 | 13070.09 | 16-OCT-12:10 | 35.68 | 17.48 | 0.620419E+09 | 845.66 | 03-OCT-13:00 | 35.68 | 17.48 |
November | 0.567761E+10 | 7349.79 | 28-NOV-14:00 | 25.00 | 11.02 | 0.600413E+09 | 845.71 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.548935E+10 | 7898.21 | 05-DEC-14:25 | 24.50 | 12.89 | 0.571416E+09 | 845.76 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.867284E+11 | 0.734792E+10 | ||||||||
Minimum of Months | 0.473224E+10 | 6959.94 | 23.00 | 11.02 | 0.538195E+09 | 845.62 | 18.50 | 12.37 | ||
Maximum of Months | 0.104500E+11 | 13084.81 | 36.00 | 21.19 | 0.684671E+09 | 845.76 | 36.00 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.631446E+10 | 10816.46 | 20-JAN-08:55 | 17.00 | 13.94 | 0.367738E+09 | 544.97 | 05-JAN-10:00 | 17.00 | 13.94 |
February | 0.568392E+10 | 29824.51 | 20-FEB-09:51 | 14.00 | 8.11 | 0.332333E+09 | 544.99 | 01-FEB-10:50 | 14.00 | 8.11 |
March | 0.710985E+10 | 33290.72 | 19-MAR-09:11 | 16.67 | 14.09 | 0.401254E+09 | 544.97 | 23-MAR-09:00 | 22.00 | 16.42 |
April | 0.910565E+10 | 31819.90 | 09-APR-09:22 | 17.50 | 13.44 | 0.378261E+09 | 545.03 | 13-APR-09:00 | 23.00 | 15.74 |
May | 0.900331E+10 | 32466.76 | 21-MAY-08:31 | 17.33 | 12.11 | 0.405167E+09 | 544.99 | 03-MAY-13:00 | 17.33 | 12.11 |
June | 0.987367E+10 | 35053.19 | 18-JUN-07:41 | 18.83 | 15.22 | 0.410317E+09 | 544.97 | 22-JUN-09:50 | 22.67 | 17.06 |
July | 0.115678E+11 | 36397.73 | 23-JUL-08:21 | 24.00 | 19.32 | 0.389520E+09 | 544.96 | 07-JUL-13:09 | 24.00 | 19.32 |
August | 0.121230E+11 | 31509.97 | 06-AUG-08:32 | 23.33 | 18.92 | 0.436549E+09 | 544.95 | 30-AUG-09:39 | 22.67 | 17.13 |
September | 0.905045E+10 | 35102.55 | 10-SEP-08:11 | 20.00 | 16.84 | 0.377172E+09 | 544.97 | 12-SEP-09:50 | 22.67 | 17.05 |
October | 0.888972E+10 | 33091.34 | 09-OCT-08:11 | 19.33 | 14.92 | 0.387802E+09 | 545.00 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.674043E+10 | 15106.03 | 19-NOV-09:22 | 25.00 | 13.23 | 0.367028E+09 | 545.01 | 10-NOV-10:00 | 25.00 | 13.23 |
December | 0.652155E+10 | 11124.57 | 05-DEC-09:00 | 24.00 | 11.80 | 0.352076E+09 | 544.97 | 19-DEC-10:09 | 23.33 | 10.05 |
Annual Sum or Average | 0.101984E+12 | 0.460522E+10 | ||||||||
Minimum of Months | 0.568392E+10 | 10816.46 | 14.00 | 8.11 | 0.332333E+09 | 544.95 | 14.00 | 8.11 | ||
Maximum of Months | 0.121230E+11 | 36397.73 | 25.00 | 19.32 | 0.436549E+09 | 545.03 | 25.00 | 19.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161266E+11 | 41992.55 | 22-JAN-11:41 | 16.83 | 11.85 | 0.614494E+09 | 880.00 | 18-JAN-14:09 | 16.83 | 11.85 |
February | 0.116548E+11 | 41525.42 | 20-FEB-12:31 | 17.00 | 10.11 | 0.546406E+09 | 846.41 | 03-FEB-14:00 | 17.00 | 10.11 |
March | 0.119832E+11 | 37493.70 | 12-MAR-11:32 | 19.67 | 15.22 | 0.642328E+09 | 846.28 | 10-MAR-14:09 | 19.67 | 15.22 |
April | 0.123826E+11 | 36551.44 | 30-APR-13:01 | 24.00 | 16.95 | 0.583854E+09 | 845.73 | 13-APR-13:50 | 24.00 | 16.95 |
May | 0.989790E+10 | 13613.15 | 04-MAY-12:30 | 23.50 | 16.62 | 0.622121E+09 | 845.72 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.103451E+11 | 11959.98 | 30-JUN-12:20 | 23.67 | 18.03 | 0.632776E+09 | 845.66 | 21-JUN-13:09 | 23.67 | 18.03 |
July | 0.122406E+11 | 22856.02 | 30-JUL-13:01 | 24.00 | 19.79 | 0.597810E+09 | 845.66 | 07-JUL-13:09 | 24.00 | 19.79 |
August | 0.154489E+11 | 20756.78 | 30-AUG-12:40 | 23.67 | 17.83 | 0.674487E+09 | 845.64 | 22-AUG-13:09 | 23.67 | 17.83 |
September | 0.151378E+11 | 37744.96 | 04-SEP-12:12 | 22.00 | 16.84 | 0.593151E+09 | 890.37 | 29-SEP-13:09 | 35.67 | 18.16 |
October | 0.175681E+11 | 43947.15 | 29-OCT-12:21 | 22.50 | 15.57 | 0.621907E+09 | 933.22 | 30-OCT-13:30 | 26.50 | 16.48 |
November | 0.160786E+11 | 41829.56 | 05-NOV-12:01 | 18.00 | 12.13 | 0.613185E+09 | 847.08 | 28-NOV-14:50 | 23.33 | 10.84 |
December | 0.173715E+11 | 42110.89 | 24-DEC-12:31 | 16.67 | 11.09 | 0.596137E+09 | 866.41 | 19-DEC-14:09 | 16.67 | 11.09 |
Annual Sum or Average | 0.166236E+12 | 0.733866E+10 | ||||||||
Minimum of Months | 0.989790E+10 | 11959.98 | 16.67 | 10.11 | 0.546406E+09 | 845.64 | 16.67 | 10.11 | ||
Maximum of Months | 0.175681E+11 | 43947.15 | 24.00 | 19.79 | 0.674487E+09 | 933.22 | 35.67 | 19.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.815729E+10 | 14311.61 | 18-JAN-14:45 | 23.27 | 14.80 | 0.357823E+09 | 544.98 | 04-JAN-14:00 | 23.27 | 14.80 |
February | 0.789164E+10 | 34938.44 | 26-FEB-15:41 | 12.67 | 8.89 | 0.328361E+09 | 544.96 | 01-FEB-14:09 | 12.67 | 8.89 |
March | 0.101654E+11 | 40564.31 | 19-MAR-17:11 | 16.00 | 13.98 | 0.398544E+09 | 544.97 | 10-MAR-14:00 | 16.00 | 13.98 |
April | 0.127972E+11 | 41316.06 | 09-APR-14:41 | 18.17 | 13.86 | 0.374173E+09 | 545.02 | 13-APR-13:50 | 20.17 | 15.46 |
May | 0.115444E+11 | 41120.55 | 21-MAY-15:21 | 19.00 | 13.99 | 0.392877E+09 | 545.02 | 03-MAY-13:00 | 19.00 | 13.99 |
June | 0.129737E+11 | 41915.33 | 25-JUN-17:21 | 20.00 | 16.22 | 0.403959E+09 | 544.97 | 21-JUN-13:09 | 20.00 | 16.22 |
July | 0.153353E+11 | 46175.61 | 23-JUL-16:21 | 24.00 | 19.02 | 0.388494E+09 | 544.96 | 07-JUL-13:09 | 24.00 | 19.02 |
August | 0.167347E+11 | 40384.03 | 13-AUG-16:01 | 23.83 | 19.84 | 0.438725E+09 | 544.95 | 21-AUG-09:09 | 19.50 | 16.16 |
September | 0.118481E+11 | 41028.45 | 04-SEP-14:51 | 21.00 | 15.97 | 0.368678E+09 | 544.96 | 01-SEP-13:09 | 21.00 | 15.97 |
October | 0.114532E+11 | 40074.06 | 15-OCT-15:01 | 30.83 | 15.40 | 0.381808E+09 | 545.01 | 03-OCT-13:00 | 30.83 | 15.40 |
November | 0.976128E+10 | 38220.92 | 12-NOV-15:41 | 17.00 | 13.94 | 0.371493E+09 | 545.09 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.984163E+10 | 32000.19 | 24-DEC-14:31 | 16.33 | 11.98 | 0.359351E+09 | 545.12 | 20-DEC-14:00 | 16.33 | 11.98 |
Annual Sum or Average | 0.138504E+12 | 0.456429E+10 | ||||||||
Minimum of Months | 0.789164E+10 | 14311.61 | 12.67 | 8.89 | 0.328361E+09 | 544.95 | 12.67 | 8.89 | ||
Maximum of Months | 0.167347E+11 | 46175.61 | 30.83 | 19.84 | 0.438725E+09 | 545.12 | 30.83 | 19.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.357682E+10 | 6151.75 | 24-JAN-14:50 | 24.83 | 15.33 | 0.534472E+09 | 845.63 | 18-JAN-14:20 | 24.83 | 15.33 |
February | 0.329352E+10 | 5143.51 | 01-FEB-13:07 | 23.17 | 14.41 | 0.497255E+09 | 845.65 | 01-FEB-14:09 | 19.00 | 15.70 |
March | 0.399600E+10 | 5837.37 | 23-MAR-14:30 | 22.50 | 17.35 | 0.598085E+09 | 845.63 | 24-MAR-13:09 | 19.00 | 15.88 |
April | 0.506000E+10 | 8430.32 | 26-APR-14:00 | 26.00 | 16.74 | 0.565643E+09 | 845.67 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.597909E+10 | 8950.49 | 04-MAY-13:40 | 23.00 | 16.67 | 0.625168E+09 | 845.68 | 05-MAY-13:50 | 18.50 | 16.08 |
June | 0.726104E+10 | 8309.89 | 29-JUN-16:00 | 23.00 | 18.43 | 0.641992E+09 | 845.63 | 21-JUN-13:09 | 23.00 | 18.43 |
July | 0.800133E+10 | 9605.95 | 19-JUL-14:30 | 27.00 | 20.51 | 0.601645E+09 | 845.63 | 07-JUL-13:09 | 27.00 | 20.51 |
August | 0.801541E+10 | 9641.21 | 17-AUG-14:00 | 28.00 | 21.19 | 0.670346E+09 | 845.63 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.628244E+10 | 12479.68 | 29-SEP-13:10 | 35.67 | 18.16 | 0.582009E+09 | 845.63 | 01-SEP-13:09 | 35.67 | 18.16 |
October | 0.622034E+10 | 11769.76 | 16-OCT-12:20 | 35.37 | 17.35 | 0.599819E+09 | 845.65 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.396170E+10 | 5119.46 | 28-NOV-13:50 | 24.83 | 10.89 | 0.552016E+09 | 845.64 | 10-NOV-14:50 | 24.83 | 10.89 |
December | 0.365645E+10 | 5664.88 | 05-DEC-15:00 | 25.00 | 13.22 | 0.516794E+09 | 845.63 | 05-DEC-14:20 | 25.00 | 13.22 |
Annual Sum or Average | 0.653041E+11 | 0.698524E+10 | ||||||||
Minimum of Months | 0.329352E+10 | 5119.46 | 22.50 | 10.89 | 0.497255E+09 | 845.63 | 18.50 | 10.89 | ||
Maximum of Months | 0.801541E+10 | 12479.68 | 35.67 | 21.19 | 0.670346E+09 | 845.68 | 35.67 | 20.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.442861E+10 | 9760.10 | 20-JAN-09:30 | 18.00 | 14.38 | 0.261095E+09 | 548.52 | 05-JAN-11:09 | 18.00 | 14.38 |
February | 0.393597E+10 | 16717.68 | 21-FEB-11:01 | 19.00 | 12.18 | 0.238122E+09 | 548.52 | 01-FEB-11:09 | 19.00 | 12.18 |
March | 0.517310E+10 | 32248.90 | 19-MAR-09:01 | 16.33 | 14.11 | 0.285817E+09 | 548.51 | 23-MAR-10:09 | 22.00 | 16.49 |
April | 0.756894E+10 | 30654.86 | 30-APR-09:22 | 23.50 | 15.91 | 0.272448E+09 | 548.57 | 13-APR-10:09 | 23.50 | 15.91 |
May | 0.746831E+10 | 33614.28 | 28-MAY-08:31 | 18.67 | 14.13 | 0.291805E+09 | 548.54 | 03-MAY-14:09 | 18.67 | 14.13 |
June | 0.876897E+10 | 35305.35 | 18-JUN-08:61 | 19.50 | 15.55 | 0.296254E+09 | 548.51 | 22-JUN-10:09 | 23.00 | 17.27 |
July | 0.105658E+11 | 35222.55 | 02-JUL-08:51 | 22.00 | 16.84 | 0.284193E+09 | 548.49 | 07-JUL-10:09 | 22.00 | 16.41 |
August | 0.110341E+11 | 35405.82 | 06-AUG-08:11 | 22.67 | 18.51 | 0.316886E+09 | 548.50 | 29-AUG-12:09 | 24.33 | 17.16 |
September | 0.785682E+10 | 33228.51 | 03-SEP-09:01 | 20.33 | 15.24 | 0.271543E+09 | 548.51 | 12-SEP-10:09 | 22.83 | 17.20 |
October | 0.751424E+10 | 36286.60 | 15-OCT-09:21 | 32.00 | 16.25 | 0.278272E+09 | 548.56 | 27-OCT-10:09 | 22.00 | 12.16 |
November | 0.474792E+10 | 15468.26 | 04-NOV-10:01 | 15.83 | 11.40 | 0.261528E+09 | 548.54 | 30-NOV-15:09 | 20.50 | 12.92 |
December | 0.444609E+10 | 11648.90 | 23-DEC-11:01 | 16.83 | 8.97 | 0.251002E+09 | 548.55 | 20-DEC-15:09 | 16.83 | 8.97 |
Annual Sum or Average | 0.835088E+11 | 0.330896E+10 | ||||||||
Minimum of Months | 0.393597E+10 | 9760.10 | 15.83 | 8.97 | 0.238122E+09 | 548.49 | 16.83 | 8.97 | ||
Maximum of Months | 0.110341E+11 | 36286.60 | 32.00 | 18.51 | 0.316886E+09 | 548.57 | 24.33 | 17.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154413E+11 | 40071.66 | 08-JAN-13:21 | 17.00 | 10.26 | 0.609018E+09 | 901.27 | 18-JAN-14:09 | 24.33 | 14.82 |
February | 0.105334E+11 | 40457.83 | 20-FEB-12:41 | 17.00 | 10.17 | 0.537099E+09 | 846.40 | 03-FEB-14:30 | 17.00 | 10.17 |
March | 0.103612E+11 | 38113.76 | 19-MAR-13:01 | 19.83 | 15.06 | 0.625292E+09 | 846.57 | 10-MAR-14:30 | 19.83 | 15.06 |
April | 0.103575E+11 | 28175.96 | 09-APR-13:21 | 19.50 | 14.15 | 0.571192E+09 | 845.73 | 13-APR-13:50 | 20.17 | 15.46 |
May | 0.818717E+10 | 12520.37 | 04-MAY-12:30 | 23.50 | 16.62 | 0.605396E+09 | 845.71 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.894733E+10 | 10907.72 | 30-JUN-12:30 | 23.50 | 17.99 | 0.616515E+09 | 845.66 | 21-JUN-13:09 | 23.50 | 17.99 |
July | 0.104606E+11 | 31091.77 | 30-JUL-13:11 | 24.00 | 19.70 | 0.583505E+09 | 845.65 | 07-JUL-13:09 | 24.00 | 19.70 |
August | 0.134151E+11 | 26364.32 | 06-AUG-12:52 | 26.00 | 20.47 | 0.660964E+09 | 845.66 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.141000E+11 | 35847.45 | 04-SEP-12:02 | 22.00 | 16.84 | 0.585254E+09 | 922.57 | 29-SEP-13:09 | 35.67 | 18.16 |
October | 0.166741E+11 | 44734.79 | 15-OCT-12:41 | 32.00 | 16.02 | 0.615387E+09 | 985.94 | 30-OCT-13:39 | 26.67 | 16.38 |
November | 0.148349E+11 | 40854.89 | 05-NOV-12:31 | 18.00 | 12.58 | 0.606815E+09 | 862.60 | 30-NOV-14:09 | 22.67 | 10.93 |
December | 0.161680E+11 | 42760.12 | 25-DEC-13:01 | 22.00 | 9.19 | 0.589101E+09 | 890.24 | 19-DEC-14:09 | 22.00 | 9.19 |
Annual Sum or Average | 0.149481E+12 | 0.720554E+10 | ||||||||
Minimum of Months | 0.818717E+10 | 10907.72 | 17.00 | 9.19 | 0.537099E+09 | 845.65 | 17.00 | 9.19 | ||
Maximum of Months | 0.166741E+11 | 44734.79 | 32.00 | 20.47 | 0.660964E+09 | 985.94 | 35.67 | 19.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.536825E+10 | 12031.89 | 18-JAN-15:00 | 23.00 | 14.79 | 0.338129E+09 | 544.96 | 26-JAN-14:39 | 16.33 | 11.99 |
February | 0.507429E+10 | 13514.32 | 26-FEB-16:29 | 12.30 | 8.60 | 0.307856E+09 | 544.97 | 14-FEB-14:30 | 12.30 | 8.60 |
March | 0.641966E+10 | 33823.80 | 19-MAR-16:21 | 17.50 | 14.74 | 0.367440E+09 | 544.97 | 10-MAR-14:00 | 17.50 | 14.74 |
April | 0.869045E+10 | 35262.25 | 02-APR-16:01 | 18.83 | 14.19 | 0.342908E+09 | 545.01 | 13-APR-13:00 | 20.00 | 15.65 |
May | 0.877263E+10 | 37361.19 | 28-MAY-16:51 | 19.00 | 14.25 | 0.371631E+09 | 545.01 | 03-MAY-13:00 | 19.00 | 14.25 |
June | 0.104003E+11 | 36223.69 | 25-JUN-16:31 | 21.00 | 16.52 | 0.382140E+09 | 544.96 | 12-JUN-13:39 | 21.00 | 16.52 |
July | 0.117130E+11 | 40600.92 | 09-JUL-15:41 | 21.17 | 16.05 | 0.363700E+09 | 544.94 | 11-JUL-13:50 | 22.00 | 16.94 |
August | 0.121078E+11 | 38983.67 | 06-AUG-16:51 | 23.00 | 18.99 | 0.406906E+09 | 544.95 | 29-AUG-13:20 | 25.33 | 17.78 |
September | 0.948671E+10 | 35331.06 | 04-SEP-16:01 | 19.67 | 15.96 | 0.350689E+09 | 544.95 | 27-SEP-13:20 | 20.67 | 16.40 |
October | 0.872138E+10 | 41503.40 | 15-OCT-15:21 | 30.50 | 15.19 | 0.358631E+09 | 544.99 | 03-OCT-13:00 | 30.50 | 15.19 |
November | 0.616281E+10 | 12933.67 | 07-NOV-15:23 | 19.00 | 14.51 | 0.343275E+09 | 545.07 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.567787E+10 | 20142.28 | 25-DEC-15:41 | 21.17 | 9.64 | 0.325327E+09 | 545.13 | 20-DEC-14:00 | 21.17 | 9.64 |
Annual Sum or Average | 0.985952E+11 | 0.425863E+10 | ||||||||
Minimum of Months | 0.507429E+10 | 12031.89 | 12.30 | 8.60 | 0.307856E+09 | 544.94 | 12.30 | 8.60 | ||
Maximum of Months | 0.121078E+11 | 41503.40 | 30.50 | 18.99 | 0.406906E+09 | 545.13 | 30.50 | 17.78 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.331366E+10 | 6444.25 | 18-JAN-14:02 | 24.33 | 14.82 | 0.509204E+09 | 845.63 | 24-JAN-14:20 | 24.33 | 14.96 |
February | 0.314904E+10 | 5259.94 | 01-FEB-13:10 | 23.17 | 14.41 | 0.472338E+09 | 843.49 | 01-FEB-14:30 | 19.00 | 15.33 |
March | 0.408398E+10 | 6570.98 | 23-MAR-14:40 | 22.33 | 17.37 | 0.570509E+09 | 845.63 | 24-MAR-13:50 | 19.00 | 15.88 |
April | 0.548808E+10 | 9761.74 | 26-APR-14:00 | 26.00 | 16.74 | 0.546356E+09 | 845.68 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.645121E+10 | 10221.39 | 04-MAY-13:40 | 23.00 | 16.67 | 0.603420E+09 | 845.68 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.807280E+10 | 9527.66 | 29-JUN-16:00 | 23.00 | 18.43 | 0.624236E+09 | 845.64 | 21-JUN-13:09 | 23.00 | 18.43 |
July | 0.906995E+10 | 11137.67 | 19-JUL-14:30 | 27.00 | 20.51 | 0.588897E+09 | 845.63 | 07-JUL-13:09 | 27.00 | 20.51 |
August | 0.896353E+10 | 10964.73 | 17-AUG-14:00 | 28.00 | 21.19 | 0.654617E+09 | 845.63 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.672893E+10 | 13870.70 | 29-SEP-13:10 | 35.67 | 18.16 | 0.562122E+09 | 845.63 | 01-SEP-13:09 | 35.67 | 18.16 |
October | 0.647240E+10 | 13178.13 | 16-OCT-12:30 | 35.05 | 17.21 | 0.576923E+09 | 845.65 | 18-OCT-13:09 | 22.83 | 18.37 |
November | 0.376746E+10 | 6037.77 | 19-NOV-14:02 | 24.33 | 15.36 | 0.519650E+09 | 838.99 | 28-NOV-14:00 | 23.00 | 10.79 |
December | 0.328635E+10 | 6190.88 | 19-DEC-13:40 | 24.00 | 10.42 | 0.489632E+09 | 845.61 | 05-DEC-14:00 | 24.00 | 10.42 |
Annual Sum or Average | 0.688474E+11 | 0.671790E+10 | ||||||||
Minimum of Months | 0.314904E+10 | 5259.94 | 22.33 | 10.42 | 0.472338E+09 | 838.99 | 19.00 | 10.42 | ||
Maximum of Months | 0.906995E+10 | 13870.70 | 35.67 | 21.19 | 0.654617E+09 | 845.68 | 35.67 | 20.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.439012E+10 | 8211.15 | 20-JAN-09:50 | 18.67 | 14.64 | 0.342232E+09 | 544.96 | 19-JAN-10:00 | 18.67 | 14.64 |
February | 0.383757E+10 | 8316.98 | 01-FEB-10:05 | 23.83 | 12.71 | 0.315435E+09 | 544.98 | 01-FEB-10:50 | 23.17 | 13.31 |
March | 0.520790E+10 | 27630.34 | 19-MAR-09:01 | 16.33 | 14.11 | 0.382096E+09 | 544.97 | 23-MAR-09:00 | 22.00 | 16.42 |
April | 0.764247E+10 | 33587.31 | 30-APR-09:51 | 25.00 | 16.34 | 0.372278E+09 | 545.03 | 13-APR-09:00 | 25.00 | 16.34 |
May | 0.765055E+10 | 32156.13 | 28-MAY-09:01 | 19.33 | 14.45 | 0.396420E+09 | 545.00 | 03-MAY-13:00 | 19.33 | 14.45 |
June | 0.916288E+10 | 33354.19 | 25-JUN-07:51 | 19.00 | 15.26 | 0.403175E+09 | 544.97 | 22-JUN-09:00 | 19.00 | 15.26 |
July | 0.110051E+11 | 36610.49 | 23-JUL-08:51 | 25.00 | 19.60 | 0.387303E+09 | 544.96 | 12-JUL-09:39 | 25.00 | 19.60 |
August | 0.113790E+11 | 34743.82 | 06-AUG-09:41 | 23.17 | 19.52 | 0.433491E+09 | 544.96 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.795614E+10 | 33686.75 | 10-SEP-08:61 | 19.50 | 16.67 | 0.369913E+09 | 544.97 | 12-SEP-09:00 | 23.00 | 17.26 |
October | 0.741271E+10 | 35764.32 | 15-OCT-09:31 | 31.67 | 16.34 | 0.376973E+09 | 544.99 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.461464E+10 | 8523.97 | 19-NOV-10:02 | 26.00 | 14.09 | 0.343692E+09 | 544.96 | 20-NOV-10:09 | 16.33 | 14.28 |
December | 0.431558E+10 | 8608.70 | 05-DEC-09:50 | 25.67 | 12.88 | 0.326539E+09 | 544.96 | 05-DEC-10:39 | 24.67 | 13.14 |
Annual Sum or Average | 0.845746E+11 | 0.444955E+10 | ||||||||
Minimum of Months | 0.383757E+10 | 8211.15 | 16.33 | 12.71 | 0.315435E+09 | 544.96 | 16.33 | 11.71 | ||
Maximum of Months | 0.113790E+11 | 36610.49 | 31.67 | 19.60 | 0.433491E+09 | 545.03 | 25.00 | 19.60 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141595E+11 | 42509.81 | 08-JAN-13:21 | 17.00 | 10.26 | 0.596479E+09 | 853.88 | 18-JAN-14:39 | 23.53 | 14.82 |
February | 0.963360E+10 | 43701.05 | 20-FEB-12:41 | 17.00 | 10.17 | 0.524499E+09 | 846.09 | 03-FEB-14:39 | 17.00 | 10.17 |
March | 0.988561E+10 | 41768.57 | 19-MAR-13:01 | 19.83 | 15.06 | 0.608692E+09 | 846.30 | 22-MAR-13:00 | 21.00 | 16.53 |
April | 0.104090E+11 | 38165.53 | 30-APR-13:11 | 24.00 | 16.87 | 0.560980E+09 | 845.73 | 13-APR-13:50 | 24.00 | 16.87 |
May | 0.830446E+10 | 13809.11 | 04-MAY-12:30 | 23.50 | 16.62 | 0.592548E+09 | 845.72 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.938433E+10 | 12265.77 | 30-JUN-13:10 | 23.00 | 17.85 | 0.605432E+09 | 845.66 | 21-JUN-13:09 | 23.00 | 17.85 |
July | 0.112001E+11 | 17545.80 | 31-JUL-12:40 | 28.00 | 21.19 | 0.575454E+09 | 845.65 | 07-JUL-13:09 | 28.00 | 21.19 |
August | 0.139928E+11 | 20823.66 | 30-AUG-12:50 | 23.83 | 17.97 | 0.651962E+09 | 845.66 | 22-AUG-13:09 | 23.83 | 17.97 |
September | 0.140916E+11 | 41118.64 | 10-SEP-14:01 | 22.83 | 18.25 | 0.574907E+09 | 889.56 | 29-SEP-13:09 | 35.67 | 18.16 |
October | 0.162430E+11 | 50121.53 | 15-OCT-12:11 | 32.00 | 16.54 | 0.602099E+09 | 904.84 | 30-OCT-13:39 | 26.67 | 16.38 |
November | 0.135949E+11 | 45165.53 | 23-NOV-13:01 | 19.33 | 7.28 | 0.594499E+09 | 846.68 | 10-NOV-14:09 | 19.33 | 7.28 |
December | 0.146306E+11 | 43099.49 | 24-DEC-14:21 | 16.50 | 11.96 | 0.575020E+09 | 847.15 | 19-DEC-14:09 | 16.50 | 11.96 |
Annual Sum or Average | 0.145529E+12 | 0.706257E+10 | ||||||||
Minimum of Months | 0.830446E+10 | 12265.77 | 16.50 | 7.28 | 0.524499E+09 | 845.65 | 16.50 | 7.28 | ||
Maximum of Months | 0.162430E+11 | 50121.53 | 32.00 | 21.19 | 0.651962E+09 | 904.84 | 35.67 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.481802E+10 | 12342.75 | 18-JAN-15:00 | 23.00 | 14.79 | 0.335503E+09 | 544.96 | 13-JAN-14:20 | 23.00 | 14.79 |
February | 0.462939E+10 | 13587.98 | 22-FEB-15:36 | 16.60 | 12.17 | 0.304481E+09 | 544.97 | 01-FEB-14:09 | 16.60 | 12.17 |
March | 0.609894E+10 | 31871.29 | 19-MAR-16:21 | 17.50 | 14.74 | 0.363335E+09 | 544.97 | 10-MAR-14:00 | 17.50 | 14.74 |
April | 0.865206E+10 | 39451.34 | 30-APR-15:11 | 22.67 | 16.39 | 0.339443E+09 | 545.01 | 13-APR-13:00 | 22.67 | 16.39 |
May | 0.876767E+10 | 40436.68 | 28-MAY-16:41 | 19.17 | 14.31 | 0.367329E+09 | 545.02 | 03-MAY-13:00 | 19.17 | 14.31 |
June | 0.106162E+11 | 40378.22 | 25-JUN-17:21 | 20.00 | 16.22 | 0.378115E+09 | 544.96 | 12-JUN-13:39 | 20.00 | 16.22 |
July | 0.121134E+11 | 44268.50 | 09-JUL-15:41 | 21.17 | 16.05 | 0.360645E+09 | 544.95 | 07-JUL-13:20 | 21.17 | 16.05 |
August | 0.123834E+11 | 43021.81 | 06-AUG-16:21 | 23.50 | 19.44 | 0.403046E+09 | 544.94 | 29-AUG-13:20 | 25.33 | 17.78 |
September | 0.944776E+10 | 38942.47 | 03-SEP-15:31 | 19.67 | 16.11 | 0.346064E+09 | 544.95 | 29-SEP-13:20 | 35.33 | 18.10 |
October | 0.845199E+10 | 44920.87 | 15-OCT-15:31 | 30.33 | 15.09 | 0.353842E+09 | 544.99 | 03-OCT-13:00 | 30.33 | 15.09 |
November | 0.560608E+10 | 13027.17 | 07-NOV-15:23 | 19.00 | 14.51 | 0.339196E+09 | 545.07 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.502910E+10 | 13252.38 | 18-DEC-15:30 | 22.00 | 8.99 | 0.322143E+09 | 545.10 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.966140E+11 | 0.421314E+10 | ||||||||
Minimum of Months | 0.462939E+10 | 12342.75 | 16.60 | 8.99 | 0.304481E+09 | 544.94 | 16.60 | 12.17 | ||
Maximum of Months | 0.123834E+11 | 44920.87 | 30.33 | 19.44 | 0.403046E+09 | 545.10 | 35.33 | 18.10 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.700140E+10 | 11571.45 | 09-JAN-06:02 | 2.17 | -0.2 | 0.00 | 0.00 | 01-JAN-00:10 | 2.17 | -0.2 |
February | 0.623000E+10 | 9253.80 | 22-FEB-05:17 | 7.67 | 6.49 | 0.00 | 0.00 | 01-FEB-00:10 | 7.67 | 6.49 |
March | 0.735512E+10 | 13402.23 | 29-MAR-04:12 | 7.67 | 5.89 | 0.00 | 0.00 | 01-MAR-00:10 | 7.67 | 5.89 |
April | 0.829504E+10 | 9855.15 | 14-APR-05:12 | 13.67 | 12.51 | 0.00 | 0.00 | 01-APR-00:10 | 13.67 | 12.51 |
May | 0.801612E+10 | 10271.06 | 02-MAY-05:13 | 13.33 | 11.44 | 0.00 | 0.00 | 01-MAY-00:10 | 13.33 | 11.44 |
June | 0.883377E+10 | 9688.50 | 12-JUN-05:04 | 13.33 | 12.27 | 0.00 | 0.00 | 01-JUN-00:10 | 13.33 | 12.27 |
July | 0.103508E+11 | 10336.51 | 24-JUL-05:02 | 16.83 | 16.83 | 0.00 | 0.00 | 01-JUL-00:10 | 16.83 | 16.83 |
August | 0.117006E+11 | 11094.44 | 21-AUG-05:13 | 16.83 | 15.53 | 0.00 | 0.00 | 01-AUG-00:10 | 16.83 | 15.53 |
September | 0.889684E+10 | 10490.89 | 11-SEP-05:13 | 15.00 | 14.20 | 0.00 | 0.00 | 01-SEP-00:10 | 15.00 | 14.20 |
October | 0.933795E+10 | 11627.16 | 16-OCT-14:25 | 31.00 | 15.99 | 0.00 | 0.00 | 01-OCT-00:10 | 31.00 | 15.99 |
November | 0.779777E+10 | 12669.19 | 13-NOV-06:02 | 11.17 | 10.55 | 0.00 | 0.00 | 01-NOV-00:10 | 11.17 | 10.55 |
December | 0.771670E+10 | 9923.08 | 20-DEC-05:16 | 7.67 | 0.70 | 0.00 | 0.00 | 01-DEC-00:10 | 7.67 | 0.70 |
Annual Sum or Average | 0.101532E+12 | 0.00 | ||||||||
Minimum of Months | 0.623000E+10 | 9253.80 | 2.17 | -0.2 | 0.00 | 0.00 | 2.17 | -0.2 | ||
Maximum of Months | 0.117006E+11 | 13402.23 | 31.00 | 16.83 | 0.00 | 0.00 | 31.00 | 16.83 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.419797E+10 | 16396.70 | 27-JAN-05:11 | 4.67 | 4.04 | 0.00 | 0.00 | 01-JAN-00:10 | 4.67 | 4.04 |
February | 0.402969E+10 | 14631.58 | 04-FEB-05:51 | 5.00 | 0.22 | 0.00 | 0.00 | 01-FEB-00:10 | 5.00 | 0.22 |
March | 0.459429E+10 | 19065.64 | 29-MAR-04:11 | 7.67 | 5.89 | 0.00 | 0.00 | 01-MAR-00:10 | 7.67 | 5.89 |
April | 0.541457E+10 | 14475.05 | 01-APR-04:11 | 8.00 | 5.22 | 0.00 | 0.00 | 01-APR-00:10 | 8.00 | 5.22 |
May | 0.570148E+10 | 9918.63 | 13-MAY-05:02 | 10.33 | 9.66 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.66 |
June | 0.666113E+10 | 8948.25 | 22-JUN-04:20 | 13.33 | 12.58 | 0.00 | 0.00 | 01-JUN-00:10 | 13.33 | 12.58 |
July | 0.740576E+10 | 8790.20 | 06-JUL-05:05 | 14.33 | 13.55 | 0.00 | 0.00 | 01-JUL-00:10 | 14.33 | 13.55 |
August | 0.815364E+10 | 8792.66 | 22-AUG-05:05 | 15.00 | 13.18 | 0.00 | 0.00 | 01-AUG-00:10 | 15.00 | 13.18 |
September | 0.675548E+10 | 9499.81 | 16-SEP-05:06 | 14.00 | 12.83 | 0.00 | 0.00 | 01-SEP-00:10 | 14.00 | 12.83 |
October | 0.694699E+10 | 9671.89 | 18-OCT-04:20 | 14.33 | 8.50 | 0.00 | 0.00 | 01-OCT-00:10 | 14.33 | 8.50 |
November | 0.495113E+10 | 14551.18 | 30-NOV-05:11 | 7.33 | 1.99 | 0.00 | 0.00 | 01-NOV-00:10 | 7.33 | 1.99 |
December | 0.469280E+10 | 16565.11 | 13-DEC-05:11 | 6.67 | 5.69 | 0.00 | 0.00 | 01-DEC-00:10 | 6.67 | 5.69 |
Annual Sum or Average | 0.695049E+11 | 0.00 | ||||||||
Minimum of Months | 0.402969E+10 | 8790.20 | 4.67 | 0.22 | 0.00 | 0.00 | 4.67 | 0.22 | ||
Maximum of Months | 0.815364E+10 | 19065.64 | 15.00 | 13.55 | 0.00 | 0.00 | 15.00 | 13.55 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.670227E+10 | 19080.75 | 18-JAN-14:30 | 23.80 | 14.82 | 0.00 | 0.00 | 01-JAN-00:10 | 23.80 | 14.82 |
February | 0.649365E+10 | 19555.09 | 01-FEB-13:03 | 23.17 | 14.41 | 0.00 | 0.00 | 01-FEB-00:10 | 23.17 | 14.41 |
March | 0.960770E+10 | 26159.50 | 23-MAR-14:20 | 22.67 | 17.32 | 0.00 | 0.00 | 01-MAR-00:10 | 22.67 | 17.32 |
April | 0.154141E+11 | 32883.87 | 26-APR-13:05 | 26.83 | 17.07 | 0.00 | 0.00 | 01-APR-00:10 | 26.83 | 17.07 |
May | 0.153442E+11 | 30786.37 | 03-MAY-13:05 | 23.83 | 15.35 | 0.00 | 0.00 | 01-MAY-00:10 | 23.83 | 15.35 |
June | 0.187352E+11 | 30382.17 | 21-JUN-13:05 | 23.83 | 16.97 | 0.00 | 0.00 | 01-JUN-00:10 | 23.83 | 16.97 |
July | 0.221264E+11 | 33288.90 | 19-JUL-13:05 | 27.00 | 20.29 | 0.00 | 0.00 | 01-JUL-00:10 | 27.00 | 20.29 |
August | 0.222657E+11 | 32153.17 | 14-AUG-13:05 | 25.83 | 20.42 | 0.00 | 0.00 | 01-AUG-00:10 | 25.83 | 20.42 |
September | 0.157015E+11 | 32416.58 | 29-SEP-13:05 | 35.67 | 18.16 | 0.00 | 0.00 | 01-SEP-00:10 | 35.67 | 18.16 |
October | 0.130525E+11 | 32541.90 | 16-OCT-13:05 | 33.75 | 16.65 | 0.00 | 0.00 | 01-OCT-00:10 | 33.75 | 16.65 |
November | 0.738033E+10 | 18728.19 | 10-NOV-14:02 | 19.83 | 15.69 | 0.00 | 0.00 | 01-NOV-00:10 | 19.83 | 15.69 |
December | 0.645712E+10 | 17428.53 | 19-DEC-14:04 | 22.83 | 9.79 | 0.00 | 0.00 | 01-DEC-00:10 | 22.83 | 9.79 |
Annual Sum or Average | 0.159281E+12 | 0.00 | ||||||||
Minimum of Months | 0.645712E+10 | 17428.53 | 19.83 | 9.79 | 0.00 | 0.00 | 19.83 | 9.79 | ||
Maximum of Months | 0.222657E+11 | 33288.90 | 35.67 | 20.42 | 0.00 | 0.00 | 35.67 | 20.42 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362324E+10 | 2381.79 | 30-JAN-16:43 | 14.00 | 11.30 | 95230514.09 | 126.83 | 20-JAN-14:00 | 14.00 | 11.30 |
February | 0.775667E+10 | 4363.76 | 22-FEB-16:57 | 14.00 | 12.23 | 86396700.71 | 126.82 | 16-FEB-10:50 | 14.00 | 12.23 |
March | 0.138350E+11 | 6525.44 | 31-MAR-23:22 | 9.90 | 9.31 | 0.103236E+09 | 126.82 | 23-MAR-13:00 | 9.90 | 9.31 |
April | 0.186706E+11 | 8029.40 | 26-APR-16:00 | 22.00 | 16.41 | 91607087.51 | 126.83 | 25-APR-09:09 | 22.00 | 16.41 |
May | 0.413468E+10 | 3113.55 | 31-MAY-23:52 | 13.10 | 11.97 | 99234983.75 | 126.83 | 05-MAY-13:00 | 13.10 | 11.97 |
June | 0.909093E+10 | 5244.78 | 30-JUN-23:52 | 16.40 | 15.78 | 98958840.25 | 126.83 | 29-JUN-09:00 | 16.40 | 15.78 |
July | 0.148216E+11 | 7212.46 | 31-JUL-24:00 | 18.10 | 17.45 | 91881596.87 | 126.82 | 31-JUL-13:00 | 18.10 | 17.45 |
August | 0.199290E+11 | 8155.18 | 06-AUG-17:40 | 21.67 | 19.02 | 0.103240E+09 | 126.83 | 18-AUG-09:09 | 23.33 | 19.67 |
September | 0.425202E+10 | 3401.62 | 30-SEP-23:51 | 18.40 | 17.30 | 91608833.14 | 126.84 | 22-SEP-13:09 | 18.40 | 17.30 |
October | 0.929071E+10 | 5139.60 | 31-OCT-23:52 | 14.90 | 11.04 | 95230949.18 | 126.83 | 04-OCT-09:00 | 14.90 | 11.04 |
November | 0.135546E+11 | 6227.69 | 07-NOV-16:17 | 18.33 | 14.34 | 94300329.83 | 126.82 | 10-NOV-14:00 | 19.00 | 15.88 |
December | 0.189356E+11 | 8245.00 | 18-DEC-16:10 | 20.67 | 8.15 | 91881126.70 | 126.82 | 07-DEC-14:00 | 20.67 | 8.15 |
Annual Sum or Average | 0.137895E+12 | 0.114281E+10 | ||||||||
Minimum of Months | 0.362324E+10 | 2381.79 | 9.90 | 8.15 | 86396700.71 | 126.82 | 9.90 | 8.15 | ||
Maximum of Months | 0.199290E+11 | 8245.00 | 22.00 | 19.02 | 0.103240E+09 | 126.84 | 23.33 | 19.67 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233573E+10 | 2173.12 | 30-JAN-16:43 | 14.00 | 11.30 | 95230509.32 | 126.83 | 20-JAN-14:00 | 14.00 | 11.30 |
February | 0.664787E+10 | 4159.82 | 22-FEB-16:57 | 14.00 | 12.23 | 86396710.58 | 126.82 | 16-FEB-10:50 | 14.00 | 12.23 |
March | 0.124331E+11 | 5988.26 | 10-MAR-17:00 | 20.00 | 12.31 | 0.103236E+09 | 126.82 | 23-MAR-09:00 | 22.00 | 16.42 |
April | 0.172707E+11 | 7645.18 | 26-APR-16:00 | 22.00 | 16.41 | 91607157.49 | 126.83 | 27-APR-13:09 | 20.87 | 15.91 |
May | 0.325789E+10 | 2671.51 | 31-MAY-23:52 | 13.10 | 11.97 | 99234959.16 | 126.83 | 05-MAY-13:00 | 13.10 | 11.97 |
June | 0.827221E+10 | 4902.61 | 30-JUN-23:52 | 16.40 | 15.78 | 98958889.76 | 126.83 | 28-JUN-13:00 | 16.40 | 15.78 |
July | 0.136554E+11 | 6752.43 | 31-JUL-24:00 | 18.10 | 17.45 | 91881504.39 | 126.82 | 31-JUL-13:00 | 18.10 | 17.45 |
August | 0.185035E+11 | 7686.71 | 31-AUG-17:00 | 20.00 | 17.42 | 0.103241E+09 | 126.83 | 24-AUG-13:09 | 20.00 | 17.42 |
September | 0.344818E+10 | 3174.36 | 30-SEP-23:42 | 18.37 | 17.42 | 91608820.32 | 126.83 | 22-SEP-13:09 | 18.37 | 17.42 |
October | 0.830903E+10 | 4684.23 | 31-OCT-23:42 | 15.02 | 11.31 | 95230997.90 | 126.83 | 05-OCT-13:00 | 15.02 | 11.31 |
November | 0.121624E+11 | 5924.36 | 07-NOV-16:17 | 18.33 | 14.34 | 94300329.96 | 126.82 | 10-NOV-10:09 | 20.00 | 14.05 |
December | 0.171582E+11 | 7728.49 | 18-DEC-16:20 | 20.33 | 7.98 | 91881121.06 | 126.83 | 07-DEC-14:00 | 20.33 | 7.98 |
Annual Sum or Average | 0.123454E+12 | 0.114281E+10 | ||||||||
Minimum of Months | 0.233573E+10 | 2173.12 | 13.10 | 7.98 | 86396710.58 | 126.82 | 13.10 | 7.98 | ||
Maximum of Months | 0.185035E+11 | 7728.49 | 22.00 | 17.45 | 0.103241E+09 | 126.83 | 22.00 | 17.45 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147194E+10 | 2162.05 | 30-JAN-16:43 | 14.00 | 11.30 | 95215002.59 | 126.83 | 20-JAN-14:00 | 14.00 | 11.30 |
February | 0.556991E+10 | 4236.28 | 22-FEB-16:57 | 14.00 | 12.23 | 86396727.67 | 126.82 | 16-FEB-10:50 | 14.00 | 12.23 |
March | 0.114377E+11 | 6119.35 | 10-MAR-17:00 | 20.00 | 12.31 | 0.103236E+09 | 126.82 | 23-MAR-09:00 | 22.00 | 16.42 |
April | 0.167136E+11 | 7843.35 | 26-APR-16:00 | 22.00 | 16.41 | 91607033.49 | 126.83 | 04-APR-13:09 | 22.00 | 16.41 |
May | 0.274388E+10 | 2318.16 | 31-MAY-23:12 | 13.30 | 12.55 | 99235549.86 | 126.83 | 05-MAY-13:00 | 13.30 | 12.55 |
June | 0.799003E+10 | 4668.13 | 30-JUN-23:22 | 16.35 | 15.73 | 98958906.34 | 126.83 | 28-JUN-13:09 | 16.35 | 15.73 |
July | 0.135153E+11 | 6563.12 | 31-JUL-23:30 | 18.25 | 17.27 | 91881536.11 | 126.82 | 31-JUL-13:00 | 18.25 | 17.27 |
August | 0.183135E+11 | 7861.25 | 17-AUG-16:00 | 25.00 | 20.20 | 0.103240E+09 | 126.83 | 07-AUG-09:00 | 25.00 | 20.20 |
September | 0.301235E+10 | 2968.47 | 30-SEP-23:12 | 18.27 | 17.76 | 91608891.69 | 126.84 | 22-SEP-13:09 | 18.27 | 17.76 |
October | 0.764456E+10 | 4417.81 | 15-OCT-16:32 | 28.00 | 14.56 | 95231056.89 | 126.83 | 04-OCT-13:09 | 28.00 | 14.56 |
November | 0.110458E+11 | 5966.20 | 07-NOV-16:17 | 18.33 | 14.34 | 94300343.03 | 126.82 | 10-NOV-10:09 | 20.00 | 14.05 |
December | 0.157914E+11 | 7779.90 | 19-DEC-16:10 | 20.67 | 8.11 | 91881085.50 | 126.82 | 07-DEC-14:00 | 20.67 | 8.11 |
Annual Sum or Average | 0.115250E+12 | 0.114279E+10 | ||||||||
Minimum of Months | 0.147194E+10 | 2162.05 | 13.30 | 8.11 | 86396727.67 | 126.82 | 13.30 | 8.11 | ||
Maximum of Months | 0.183135E+11 | 7861.25 | 28.00 | 20.20 | 0.103240E+09 | 126.84 | 28.00 | 20.20 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239836E+12 | 105776.61 | 07-JAN-05:11 | 7.00 | 1.01 | 0.207195E+10 | 2856.21 | 04-JAN-10:00 | 7.00 | 1.01 |
February | 0.439460E+12 | 483878.72 | 05-FEB-23:32 | 7.67 | 5.21 | 0.167924E+10 | 2854.61 | 03-FEB-10:00 | 7.67 | 5.21 |
March | 0.732717E+12 | 516273.68 | 07-MAR-15:12 | 14.00 | 8.62 | 0.193481E+10 | 2842.95 | 10-MAR-14:09 | 22.00 | 12.50 |
April | 0.947737E+12 | 491372.52 | 05-APR-15:43 | 16.33 | 13.18 | 0.181806E+10 | 2796.38 | 03-APR-09:20 | 16.33 | 13.18 |
May | 0.240535E+12 | 465758.60 | 31-MAY-23:52 | 13.10 | 11.97 | 0.214977E+10 | 2850.85 | 24-MAY-09:09 | 13.10 | 11.97 |
June | 0.473266E+12 | 478072.56 | 13-JUN-03:22 | 11.50 | 10.38 | 0.198199E+10 | 2746.94 | 12-JUN-09:20 | 11.50 | 10.38 |
July | 0.732959E+12 | 473527.88 | 06-JUL-05:12 | 14.67 | 13.68 | 0.196114E+10 | 2763.13 | 28-JUL-09:39 | 23.33 | 19.48 |
August | 0.978525E+12 | 473561.30 | 22-AUG-05:16 | 15.00 | 13.18 | 0.222119E+10 | 2758.50 | 18-AUG-09:50 | 15.00 | 13.18 |
September | 0.234954E+12 | 390047.07 | 30-SEP-23:56 | 18.40 | 17.30 | 0.198286E+10 | 2745.28 | 01-SEP-13:20 | 18.40 | 17.30 |
October | 0.491615E+12 | 508668.25 | 31-OCT-23:23 | 15.25 | 11.85 | 0.195245E+10 | 2853.47 | 25-OCT-09:00 | 15.25 | 11.85 |
November | 0.710472E+12 | 519798.86 | 22-NOV-14:52 | 16.00 | 9.08 | 0.183462E+10 | 2846.92 | 27-NOV-10:00 | 22.00 | 8.90 |
December | 0.982577E+12 | 512920.97 | 22-DEC-14:44 | 16.33 | 12.43 | 0.175625E+10 | 3012.76 | 05-DEC-14:00 | 16.33 | 12.43 |
Annual Sum or Average | 0.720465E+13 | 0.233443E+11 | ||||||||
Minimum of Months | 0.234954E+12 | 105776.61 | 7.00 | 1.01 | 0.167924E+10 | 2745.28 | 7.00 | 1.01 | ||
Maximum of Months | 0.982577E+12 | 519798.86 | 18.40 | 17.30 | 0.222119E+10 | 3012.76 | 23.33 | 19.48 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50980405.36 | 2810.46 | 06-JAN-06:45 | 9.00 |
February | 78094857.30 | 2872.48 | 11-FEB-06:55 | 7.80 |
March | 72626581.16 | 2666.94 | 30-MAR-05:04 | 4.97 |
April | 47859588.23 | 3112.02 | 19-APR-05:12 | 10.00 |
May | 50962305.25 | 2823.96 | 27-MAY-05:55 | 11.00 |
June | 48071572.99 | 2446.63 | 01-JUN-05:03 | 12.17 |
July | 24972295.91 | 2369.91 | 14-JUL-05:11 | 16.33 |
August | 13318532.39 | 2851.88 | 19-AUG-16:01 | 24.83 |
September | 35887906.32 | 7868.91 | 30-SEP-16:02 | 28.50 |
October | 57119000.18 | 11455.11 | 14-OCT-16:03 | 31.17 |
November | 50909172.03 | 2630.89 | 28-NOV-06:11 | 15.33 |
December | 46334300.94 | 2530.72 | 20-DEC-06:11 | 8.33 |
Annual Sum or Average | 0.577137E+09 | |||
Minimum of Months | 13318532.39 | 2369.91 | 4.97 | |
Maximum of Months | 78094857.30 | 11455.11 | 31.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:03 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:03 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.436706E+09 | 67225.25 | 09-JAN-05:21 | 4.00 |
February | 74498743.26 | 54246.63 | 21-FEB-06:01 | 8.00 |
March | 26964547.04 | 57069.66 | 30-MAR-05:01 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:03 | 9.63 |
May | 221853.57 | 1479.02 | 15-MAY-05:03 | 8.50 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 5049118.03 | 49705.03 | 30-OCT-05:01 | 10.83 |
November | 71339316.60 | 53583.55 | 24-NOV-06:01 | 8.92 |
December | 0.142977E+09 | 55445.65 | 26-DEC-06:02 | 7.00 |
Annual Sum or Average | 0.757756E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.00 | |
Maximum of Months | 0.436706E+09 | 67225.25 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 63410156.31 | 9082.29 | 09-JAN-06:01 | 2.17 |
February | 9813029.61 | 6807.81 | 04-FEB-06:01 | 5.67 |
March | 28635220.47 | 8755.30 | 30-MAR-05:01 | 4.97 |
April | 236211.99 | 2555.17 | 01-APR-05:01 | 7.83 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 18.42 |
November | 686514.84 | 5462.36 | 24-NOV-06:01 | 8.92 |
December | 9706998.14 | 7038.11 | 23-DEC-06:01 | 5.17 |
Annual Sum or Average | 0.112488E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.17 | |
Maximum of Months | 63410156.31 | 9082.29 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52512065.92 | 7176.47 | 09-JAN-06:01 | 2.17 |
February | 20998780.80 | 5332.09 | 10-FEB-06:02 | 7.03 |
March | 35377765.52 | 6974.74 | 30-MAR-05:01 | 4.97 |
April | 2503330.92 | 3690.21 | 01-APR-05:01 | 7.83 |
May | 408003.92 | 2371.09 | 15-MAY-05:03 | 8.50 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 125997.71 | 2099.96 | 06-JUL-05:01 | 14.33 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 86469.79 | 576.47 | 20-SEP-05:05 | 12.00 |
October | 807251.15 | 3805.21 | 12-OCT-05:01 | 9.00 |
November | 5770922.87 | 5355.75 | 24-NOV-06:02 | 8.92 |
December | 24580039.64 | 5677.93 | 23-DEC-06:02 | 5.17 |
Annual Sum or Average | 0.143171E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.17 | |
Maximum of Months | 52512065.92 | 7176.47 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 89105802.95 | 13815.32 | 09-JAN-05:25 | 4.00 |
February | 36066679.44 | 9544.49 | 10-FEB-06:02 | 7.03 |
March | 82913798.96 | 11670.69 | 30-MAR-05:01 | 4.97 |
April | 7436453.94 | 7878.17 | 01-APR-05:01 | 7.83 |
May | 3807125.60 | 9814.38 | 15-MAY-05:03 | 8.50 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 519887.48 | 5963.54 | 12-OCT-05:01 | 9.00 |
November | 7575500.78 | 9286.87 | 24-NOV-06:02 | 8.92 |
December | 29958008.88 | 10059.50 | 13-DEC-06:02 | 6.17 |
Annual Sum or Average | 0.257383E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.00 | |
Maximum of Months | 89105802.95 | 13815.32 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5401445.14 | 4374.43 | 12-JAN-06:01 | 7.83 |
February | 299373.32 | 1482.61 | 04-FEB-06:02 | 5.67 |
March | 1144327.30 | 4717.68 | 30-MAR-05:01 | 4.97 |
April | 52646.94 | 701.96 | 01-APR-05:04 | 7.83 |
May | 357458.35 | 2383.06 | 15-MAY-05:03 | 8.50 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 18.42 |
November | 17012.16 | 283.54 | 13-NOV-06:01 | 11.17 |
December | 94152.26 | 1050.26 | 15-DEC-06:02 | 6.00 |
Annual Sum or Average | 7366415.47 | |||
Minimum of Months | 0.00 | 0.00 | 4.97 | |
Maximum of Months | 5401445.14 | 4717.68 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.663719E+09 | 14437.64 | 03-JAN-05:11 | 3.67 |
February | 0.366938E+09 | 12930.36 | 04-FEB-05:51 | 5.00 |
March | 0.506329E+09 | 14237.73 | 30-MAR-04:11 | 4.57 |
April | 77292145.03 | 12206.84 | 01-APR-04:11 | 8.00 |
May | 14886546.38 | 11528.71 | 15-MAY-04:11 | 8.67 |
June | 27797.77 | 463.30 | 01-JUN-05:03 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 254778.06 | 1594.42 | 20-SEP-05:03 | 12.00 |
October | 40377000.15 | 10372.93 | 30-OCT-05:03 | 10.83 |
November | 0.213711E+09 | 12561.85 | 24-NOV-05:11 | 8.33 |
December | 0.469946E+09 | 13814.25 | 13-DEC-05:11 | 6.67 |
Annual Sum or Average | 0.235348E+10 | |||
Minimum of Months | 0.00 | 0.00 | 3.67 | |
Maximum of Months | 0.663719E+09 | 14437.64 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.311694E+09 | 14029.01 | 03-JAN-05:11 | 3.67 |
February | 0.201296E+09 | 12050.45 | 04-FEB-05:51 | 5.00 |
March | 0.259008E+09 | 13926.17 | 30-MAR-04:11 | 4.57 |
April | 43520082.47 | 11323.49 | 01-APR-04:11 | 8.00 |
May | 9198429.53 | 9404.31 | 15-MAY-04:11 | 8.67 |
June | 54453.87 | 486.09 | 09-JUN-05:04 | 15.17 |
July | 30703.89 | 511.73 | 06-JUL-05:03 | 14.33 |
August | 175687.29 | 763.36 | 28-AUG-05:06 | 14.00 |
September | 1093183.70 | 2167.57 | 20-SEP-05:03 | 12.00 |
October | 28728770.71 | 8461.09 | 28-OCT-05:02 | 9.33 |
November | 0.100637E+09 | 11665.98 | 24-NOV-05:11 | 8.33 |
December | 0.223619E+09 | 13284.56 | 13-DEC-05:11 | 6.67 |
Annual Sum or Average | 0.117905E+10 | |||
Minimum of Months | 30703.89 | 486.09 | 3.67 | |
Maximum of Months | 0.311694E+09 | 14029.01 | 15.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324710E+09 | 17558.97 | 03-JAN-05:11 | 3.67 |
February | 0.226351E+09 | 15622.61 | 04-FEB-05:51 | 5.00 |
March | 0.399095E+09 | 17826.08 | 30-MAR-04:11 | 4.57 |
April | 75370558.95 | 14913.74 | 01-APR-04:11 | 8.00 |
May | 41088049.94 | 13331.03 | 15-MAY-05:03 | 8.50 |
June | 308928.87 | 2204.43 | 05-JUN-05:01 | 12.17 |
July | 307.79 | 5.13 | 06-JUL-05:04 | 14.33 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 17135.61 | 182.44 | 16-SEP-05:06 | 14.00 |
October | 18556368.30 | 11234.14 | 28-OCT-05:01 | 9.33 |
November | 86767928.64 | 14916.21 | 30-NOV-05:51 | 8.00 |
December | 0.215170E+09 | 17137.15 | 13-DEC-05:11 | 6.67 |
Annual Sum or Average | 0.138744E+10 | |||
Minimum of Months | 0.00 | 0.00 | 3.67 | |
Maximum of Months | 0.399095E+09 | 17826.08 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324213E+09 | 13085.05 | 03-JAN-05:11 | 3.67 |
February | 0.167659E+09 | 11166.12 | 04-FEB-05:51 | 5.00 |
March | 0.237397E+09 | 12904.94 | 29-MAR-04:11 | 7.67 |
April | 32008876.68 | 10588.09 | 01-APR-04:11 | 8.00 |
May | 9851418.95 | 8957.27 | 13-MAY-05:02 | 10.33 |
June | 239479.27 | 1783.48 | 01-JUN-05:02 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 118502.78 | 510.38 | 16-SEP-05:04 | 14.00 |
October | 14452922.16 | 7037.06 | 28-OCT-05:01 | 9.33 |
November | 85980042.53 | 10658.64 | 30-NOV-05:51 | 8.00 |
December | 0.208855E+09 | 12492.32 | 13-DEC-05:11 | 6.67 |
Annual Sum or Average | 0.108078E+10 | |||
Minimum of Months | 0.00 | 0.00 | 3.67 | |
Maximum of Months | 0.324213E+09 | 13085.05 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186718E+10 | 21090.30 | 09-JAN-05:21 | 4.00 |
February | 0.120888E+10 | 18553.15 | 06-FEB-05:11 | 8.33 |
March | 0.143732E+10 | 19967.65 | 30-MAR-04:11 | 4.57 |
April | 0.389913E+09 | 16994.51 | 01-APR-04:11 | 8.00 |
May | 0.186095E+09 | 16172.55 | 15-MAY-04:11 | 8.67 |
June | 8554660.07 | 14243.78 | 01-JUN-05:01 | 12.17 |
July | 492437.87 | 7246.51 | 06-JUL-05:01 | 14.33 |
August | 122528.88 | 497.16 | 24-AUG-05:08 | 16.92 |
September | 30550081.06 | 13746.93 | 20-SEP-05:03 | 12.00 |
October | 0.303176E+09 | 16691.36 | 30-OCT-04:11 | 9.67 |
November | 0.975683E+09 | 18512.80 | 24-NOV-05:11 | 8.33 |
December | 0.153974E+10 | 19479.52 | 13-DEC-05:11 | 6.67 |
Annual Sum or Average | 0.794770E+10 | |||
Minimum of Months | 122528.88 | 497.16 | 4.00 | |
Maximum of Months | 0.186718E+10 | 21090.30 | 16.92 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.887907E+09 | 18584.51 | 09-JAN-05:21 | 4.00 |
February | 0.625850E+09 | 16059.39 | 06-FEB-05:11 | 8.33 |
March | 0.709878E+09 | 17790.09 | 30-MAR-04:11 | 4.57 |
April | 0.187384E+09 | 14653.36 | 01-APR-04:11 | 8.00 |
May | 0.100223E+09 | 13515.62 | 15-MAY-04:11 | 8.67 |
June | 5874166.88 | 11547.02 | 01-JUN-05:01 | 12.17 |
July | 786308.59 | 8216.33 | 06-JUL-05:01 | 14.33 |
August | 546933.65 | 1087.83 | 26-AUG-05:05 | 15.92 |
September | 19370214.01 | 10909.86 | 16-SEP-05:01 | 14.00 |
October | 0.148998E+09 | 14009.63 | 30-OCT-04:11 | 9.67 |
November | 0.422038E+09 | 16068.50 | 24-NOV-05:11 | 8.33 |
December | 0.706705E+09 | 17188.29 | 13-DEC-05:11 | 6.67 |
Annual Sum or Average | 0.381556E+10 | |||
Minimum of Months | 546933.65 | 1087.83 | 4.00 | |
Maximum of Months | 0.887907E+09 | 18584.51 | 15.92 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104076E+10 | 24624.94 | 09-JAN-05:21 | 4.00 |
February | 0.839636E+09 | 20486.14 | 06-FEB-05:11 | 8.33 |
March | 0.115688E+10 | 23699.87 | 30-MAR-04:11 | 4.57 |
April | 0.353561E+09 | 19828.86 | 01-APR-04:11 | 8.00 |
May | 0.288001E+09 | 18731.60 | 15-MAY-04:11 | 8.67 |
June | 24234601.16 | 16421.48 | 13-JUN-05:01 | 11.33 |
July | 963700.31 | 10671.03 | 06-JUL-05:01 | 14.33 |
August | 515768.89 | 1619.80 | 22-AUG-05:03 | 15.00 |
September | 19347753.64 | 14633.44 | 20-SEP-05:03 | 12.00 |
October | 0.180439E+09 | 17811.17 | 30-OCT-04:11 | 9.67 |
November | 0.525789E+09 | 20428.78 | 24-NOV-05:11 | 8.33 |
December | 0.813214E+09 | 22984.01 | 13-DEC-05:11 | 6.67 |
Annual Sum or Average | 0.524335E+10 | |||
Minimum of Months | 515768.89 | 1619.80 | 4.00 | |
Maximum of Months | 0.115688E+10 | 24624.94 | 15.00 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.840065E+09 | 18987.97 | 09-JAN-05:21 | 4.00 |
February | 0.543026E+09 | 15235.31 | 06-FEB-05:11 | 8.33 |
March | 0.652134E+09 | 17321.96 | 30-MAR-04:11 | 4.57 |
April | 0.136273E+09 | 14496.67 | 01-APR-04:11 | 8.00 |
May | 95749104.18 | 12785.38 | 13-MAY-04:12 | 10.00 |
June | 4710605.12 | 11244.96 | 01-JUN-05:01 | 12.17 |
July | 63682.31 | 713.05 | 06-JUL-05:03 | 14.33 |
August | 140763.59 | 1075.96 | 22-AUG-05:04 | 15.00 |
September | 6215059.75 | 8392.66 | 20-SEP-05:03 | 12.00 |
October | 0.123595E+09 | 13138.43 | 30-OCT-04:11 | 9.67 |
November | 0.420256E+09 | 15303.19 | 24-NOV-05:11 | 8.33 |
December | 0.666299E+09 | 17056.63 | 13-DEC-05:11 | 6.67 |
Annual Sum or Average | 0.348853E+10 | |||
Minimum of Months | 63682.31 | 713.05 | 4.00 | |
Maximum of Months | 0.840065E+09 | 18987.97 | 15.00 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50747923.53 | 9756.03 | 08-JAN-13:32 | 17.00 |
February | 44552976.03 | 12095.80 | 20-FEB-15:51 | 17.00 |
March | 39823374.63 | 12626.57 | 19-MAR-14:31 | 18.33 |
April | 73487014.45 | 12132.21 | 30-APR-14:21 | 23.50 |
May | 63530037.77 | 10708.54 | 28-MAY-16:22 | 19.50 |
June | 44365465.72 | 9940.12 | 18-JUN-16:12 | 21.67 |
July | 82684708.63 | 10846.71 | 09-JUL-15:51 | 21.00 |
August | 70465129.42 | 11364.81 | 07-AUG-04:11 | 18.00 |
September | 62897643.10 | 12363.41 | 10-SEP-14:51 | 22.00 |
October | 87346785.71 | 17450.54 | 15-OCT-14:21 | 31.00 |
November | 66012143.18 | 13364.30 | 23-NOV-14:51 | 21.00 |
December | 75745666.25 | 13007.19 | 25-DEC-14:32 | 22.00 |
Annual Sum or Average | 0.761659E+09 | |||
Minimum of Months | 39823374.63 | 9756.03 | 17.00 | |
Maximum of Months | 87346785.71 | 17450.54 | 31.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172601E+09 | 10157.81 | 08-JAN-13:23 | 17.00 |
February | 50236986.50 | 10783.97 | 20-FEB-12:42 | 17.00 |
March | 29028315.49 | 14019.31 | 19-MAR-15:41 | 18.00 |
April | 43123518.31 | 10784.50 | 02-APR-16:01 | 18.83 |
May | 41046067.27 | 10337.65 | 28-MAY-16:11 | 19.67 |
June | 30019757.75 | 9432.59 | 25-JUN-16:31 | 21.00 |
July | 56877438.73 | 9753.91 | 09-JUL-15:42 | 21.17 |
August | 38663608.21 | 8986.53 | 06-AUG-16:11 | 23.67 |
September | 43947762.58 | 10607.54 | 04-SEP-15:21 | 20.50 |
October | 81581348.72 | 17862.77 | 15-OCT-14:42 | 31.00 |
November | 50305155.12 | 11890.19 | 19-NOV-13:21 | 26.00 |
December | 72380769.88 | 14094.82 | 25-DEC-13:42 | 22.00 |
Annual Sum or Average | 0.709812E+09 | |||
Minimum of Months | 29028315.49 | 8986.53 | 17.00 | |
Maximum of Months | 0.172601E+09 | 17862.77 | 31.00 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363591E+10 | 31026.57 | 09-JAN-06:13 | 2.33 |
February | 0.230312E+10 | 22552.32 | 06-FEB-06:02 | 9.00 |
March | 0.261185E+10 | 21903.76 | 08-MAR-06:01 | 5.17 |
April | 0.103392E+10 | 13446.51 | 01-APR-04:21 | 8.00 |
May | 0.817088E+09 | 26527.33 | 04-MAY-05:01 | 14.33 |
June | 0.204438E+09 | 22770.66 | 29-JUN-05:01 | 15.00 |
July | 83413275.97 | 22647.97 | 19-JUL-05:01 | 16.20 |
August | 0.109377E+09 | 22641.34 | 18-AUG-05:02 | 17.92 |
September | 0.336724E+09 | 17776.01 | 30-SEP-05:02 | 23.80 |
October | 0.103534E+10 | 28073.45 | 17-OCT-05:01 | 17.00 |
November | 0.218516E+10 | 21537.60 | 24-NOV-06:02 | 8.92 |
December | 0.317424E+10 | 21657.21 | 26-DEC-06:02 | 7.00 |
Annual Sum or Average | 0.175306E+11 | |||
Minimum of Months | 83413275.97 | 13446.51 | 2.33 | |
Maximum of Months | 0.363591E+10 | 31026.57 | 23.80 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:03 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9177438.17 | 802.59 | 02-JAN-00:23 | 9.50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:03 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 10.63 |
Annual Sum or Average | 9177438.17 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 9177438.17 | 802.59 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.512937E+09 | 1311.64 | 09-JAN-03:25 | 4.50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:03 | 9.63 |
May | 22805874.43 | 1028.09 | 17-MAY-05:01 | 9.50 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 413023.07 | 818.87 | 03-SEP-05:13 | 13.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 10.63 |
Annual Sum or Average | 0.536156E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.50 | |
Maximum of Months | 0.512937E+09 | 1311.64 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.534144E+09 | 50815.56 | 23-FEB-05:11 | 11.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:03 | 9.63 |
May | 961657.32 | 15939.63 | 31-MAY-23:21 | 13.25 |
June | 0.551680E+09 | 24820.16 | 13-JUN-03:11 | 11.67 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 579780.46 | 6157.52 | 30-SEP-23:41 | 18.37 |
October | 0.347709E+09 | 24510.36 | 25-OCT-02:11 | 12.67 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 10.63 |
Annual Sum or Average | 0.143507E+10 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.551680E+09 | 50815.56 | 18.37 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.278508E+11 | 29144.79 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.252627E+11 | 29144.79 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.300191E+11 | 29144.79 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.268132E+11 | 29144.79 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.289349E+11 | 29144.79 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.287951E+11 | 29144.79 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.269531E+11 | 29144.79 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.300191E+11 | 29144.79 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.268132E+11 | 29144.79 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.278508E+11 | 29144.79 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.275243E+11 | 29144.79 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.269531E+11 | 29144.79 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.333789E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.252627E+11 | 29144.79 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.300191E+11 | 29144.79 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.785272E+10 | 8217.58 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.712300E+10 | 8217.58 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.846411E+10 | 8217.58 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.756018E+10 | 8217.58 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.815842E+10 | 8217.58 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.811897E+10 | 8217.58 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.759962E+10 | 8217.58 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.846411E+10 | 8217.58 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.756018E+10 | 8217.58 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.785272E+10 | 8217.58 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.776069E+10 | 8217.58 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.759962E+10 | 8217.58 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.941143E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.712300E+10 | 8217.58 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.846411E+10 | 8217.58 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.289349E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.287951E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.275243E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.333789E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 357986.64 | 0.252442E+09 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45297.18 | 0.292171E+09 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24574.72 | 0.316551E+09 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 468514.46 | 0.184880E+09 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.30 | 0.220232E+09 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28185.53 | 0.119910E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1960379.43 | 86028008.95 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2067903.20 | 0.107989E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3212656.03 | 0.100976E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11946375.18 | 0.158909E+09 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 980605.17 | 0.238050E+09 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 245520.97 | 0.257941E+09 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21338030.80 | 0.233608E+10 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.30 | 86028008.95 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11946375.18 | 0.316551E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 512496.70 | 0.165571E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39148.39 | 0.190157E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39127.78 | 0.205822E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 233775.06 | 0.118284E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 | 0.141070E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18903.74 | 74192271.31 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1402872.21 | 52031549.00 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1718095.55 | 65541304.28 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2203072.05 | 63700968.54 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8234224.27 | 99890642.05 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 706591.57 | 0.152525E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 533698.47 | 0.164765E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15642025.29 | 0.149355E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 | 52031549.00 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8234224.27 | 0.205822E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 216696.22 | 0.265031E+09 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45262.74 | 0.302498E+09 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.00 | 0.316548E+09 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 210867.27 | 0.186508E+09 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.14 | 0.208354E+09 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28307.91 | 0.109128E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2125569.71 | 78396136.56 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1996426.48 | 0.105248E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3176725.77 | 0.109341E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9942169.22 | 0.170199E+09 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98452.78 | 0.250816E+09 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 152298.02 | 0.274124E+09 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17992873.28 | 0.237619E+10 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.14 | 78396136.56 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9942169.22 | 0.316548E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 346661.67 | 0.177192E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69738.80 | 0.208510E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36981.93 | 0.226127E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 494652.73 | 0.141167E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 773.78 | 0.156769E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99088.15 | 85227004.46 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1686324.46 | 67239157.50 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1576162.85 | 88869850.26 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2299369.59 | 75159513.47 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8298593.06 | 0.116967E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 677845.22 | 0.173678E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 325402.62 | 0.193039E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15911594.85 | 0.170995E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 773.78 | 67239157.50 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8298593.06 | 0.226127E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1708373.22 | 0.499040E+09 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 112502.87 | 0.581049E+09 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 307368.49 | 0.647542E+09 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3063185.36 | 0.374660E+09 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464733E+09 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84102.98 | 0.255143E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5222870.06 | 0.175930E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6546019.44 | 0.211780E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7422878.71 | 0.203118E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29636518.40 | 0.314847E+09 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4075307.46 | 0.469867E+09 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3311200.16 | 0.500415E+09 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61490327.14 | 0.469812E+10 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175930E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29636518.40 | 0.647542E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1123387.67 | 0.347244E+09 |
February | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46860.60 | 0.402670E+09 |
March | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40245.61 | 0.447514E+09 |
April | 0.688021E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 351483.65 | 0.262991E+09 |
May | 0.744847E+09 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317598E+09 |
June | 0.742030E+09 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21076.17 | 0.167367E+09 |
July | 0.690839E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2773283.96 | 0.118979E+09 |
August | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3254812.48 | 0.143106E+09 |
September | 0.688021E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4877989.10 | 0.138983E+09 |
October | 0.715730E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18244485.61 | 0.211715E+09 |
November | 0.708685E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1520557.71 | 0.324587E+09 |
December | 0.690839E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1221801.96 | 0.347118E+09 |
Annual Sum or Average | 0.858171E+10 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33475984.52 | 0.322987E+10 |
Minimum of Months | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118979E+09 |
Maximum of Months | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18244485.61 | 0.447514E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 425043.64 | 0.589739E+09 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95307.93 | 0.668374E+09 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695767E+09 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 564154.51 | 0.410388E+09 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458212E+09 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 200751.84 | 0.234557E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5528464.11 | 0.163558E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4665503.86 | 0.218530E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7206492.35 | 0.246914E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22280284.36 | 0.379666E+09 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 195922.71 | 0.557562E+09 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 292819.02 | 0.604999E+09 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41454744.35 | 0.522827E+10 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163558E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22280284.36 | 0.695767E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1438209.68 | 0.350727E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 337102.08 | 0.411100E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 375602.24 | 0.448201E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3057712.81 | 0.278825E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55032.39 | 0.331995E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1316934.25 | 0.175559E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6573367.81 | 0.130517E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8191687.46 | 0.159228E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6167083.87 | 0.153227E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22125227.97 | 0.226398E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3187735.41 | 0.335214E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3229920.51 | 0.357414E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56055616.48 | 0.335840E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55032.39 | 0.130517E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22125227.97 | 0.448201E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3480673.68 | 0.536471E+09 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 250747.10 | 0.629977E+09 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 733607.43 | 0.730282E+09 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4424394.83 | 0.434671E+09 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542047E+09 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109600.49 | 0.302114E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6495768.00 | 0.212532E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8547924.96 | 0.248704E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9516027.78 | 0.232631E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39367733.04 | 0.342246E+09 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6658507.85 | 0.508944E+09 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8445445.42 | 0.536243E+09 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88030430.59 | 0.525686E+10 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212532E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39367733.04 | 0.730282E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2124878.29 | 0.373979E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81059.40 | 0.441345E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90353.66 | 0.507183E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 436676.58 | 0.311957E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377116E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33817.94 | 0.202375E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3312067.14 | 0.150390E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3655693.38 | 0.175544E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6173859.70 | 0.165284E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22211931.68 | 0.236207E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2468505.05 | 0.354010E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3019362.09 | 0.372433E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43608204.92 | 0.366782E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150390E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22211931.68 | 0.507183E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 686922.94 | 0.657472E+09 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 105138.19 | 0.750434E+09 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.796562E+09 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 855872.89 | 0.483637E+09 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542512E+09 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 305894.89 | 0.283420E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6499512.84 | 0.202586E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5799431.51 | 0.262595E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8940201.51 | 0.291763E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27929028.14 | 0.431248E+09 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 218665.75 | 0.629813E+09 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 389997.82 | 0.676436E+09 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51730666.48 | 0.600848E+10 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202586E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27929028.14 | 0.796562E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1924575.53 | 0.395918E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 414862.37 | 0.469129E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 527128.49 | 0.522477E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3648143.67 | 0.333287E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73246.63 | 0.398162E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1413463.02 | 0.212775E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7693933.74 | 0.160521E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9601367.24 | 0.192905E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7755666.84 | 0.183756E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27120525.80 | 0.260510E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4009012.65 | 0.382363E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4542680.57 | 0.403080E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68724606.54 | 0.391488E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73246.63 | 0.160521E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27120525.80 | 0.522477E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.785272E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.712300E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.846411E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.756018E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.815842E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.811897E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.759962E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.846411E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.756018E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.785272E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.776069E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.759962E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.941143E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.712300E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.846411E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364214.75 | 0.610951E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57515.80 | 0.702450E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742704E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459700.10 | 0.436064E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503405E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8240.23 | 0.268242E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2586929.00 | 0.198823E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2382768.28 | 0.256126E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5671068.16 | 0.242162E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21138402.52 | 0.387458E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 910024.67 | 0.576380E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199854.63 | 0.630064E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33778718.14 | 0.555483E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198823E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21138402.52 | 0.742704E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1160408.59 | 0.101886E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121091.92 | 0.118734E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29739.72 | 0.126393E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1760161.12 | 0.733562E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864873E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19267.47 | 0.457657E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5841531.20 | 0.327141E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5410043.06 | 0.420064E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10256017.31 | 0.408444E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39630892.84 | 0.654977E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2860237.86 | 0.974635E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 636663.96 | 0.105093E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67726055.07 | 0.936242E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327141E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39630892.84 | 0.126393E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1894164.02 | 0.919894E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111089E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126427E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1587.17 | 0.830216E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994798E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578692E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 679446.94 | 0.458458E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470985.96 | 0.495110E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9424204.15 | 0.482790E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33058478.76 | 0.620344E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1819081.56 | 0.891957E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563311.98 | 0.919137E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47911260.54 | 0.956656E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458458E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33058478.76 | 0.126427E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 29144.79 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 29144.79 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 29144.79 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 29144.79 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 29144.79 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 29144.79 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 29144.79 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 29144.79 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 29144.79 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 29144.79 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 29144.79 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 29144.79 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.42 | 15-JAN-14:10 | 617.47 | 02-JAN-03:00 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 01-FEB-12:00 | 534.73 | 25-FEB-02:41 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 | 11-MAR-13:03 | 592.58 | 28-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.13 | 30-APR-11:10 | 372.33 | 21-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:50 | 340.31 | 20-MAY-18:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.04 | 29-JUN-11:00 | 254.65 | 11-JUN-11:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.41 | 23-JUL-11:10 | 220.70 | 16-JUL-18:00 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.58 | 06-AUG-13:00 | 183.99 | 21-AUG-23:52 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.05 | 29-SEP-14:00 | 208.01 | 24-SEP-15:30 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.00 | 15-OCT-08:51 | 395.89 | 30-OCT-02:51 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.23 | 19-NOV-12:50 | 513.22 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.22 | 16-DEC-12:55 | 486.54 | 23-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 183.99 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 259.00 | 617.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.09 | 15-JAN-14:40 | 413.79 | 02-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 01-FEB-12:00 | 380.81 | 26-FEB-09:55 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.24 | 11-MAR-14:00 | 451.78 | 26-MAR-09:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.53 | 30-APR-11:50 | 239.13 | 02-APR-06:50 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-13:00 | 236.74 | 29-MAY-13:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.36 | 29-JUN-11:00 | 168.90 | 11-JUN-12:00 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.47 | 23-JUL-11:10 | 157.84 | 16-JUL-09:40 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.52 | 13-AUG-14:50 | 131.38 | 20-AUG-08:20 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.37 | 29-SEP-14:00 | 184.96 | 03-SEP-06:35 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.83 | 15-OCT-13:10 | 259.78 | 30-OCT-02:51 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.92 | 19-NOV-12:50 | 375.35 | 23-NOV-07:00 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.82 | 25-DEC-12:00 | 312.94 | 23-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 131.38 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 192.83 | 451.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 | 14-JAN-11:00 | 558.27 | 29-JAN-13:00 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 01-FEB-12:00 | 641.33 | 26-FEB-11:59 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 11-MAR-14:00 | 613.60 | 26-MAR-11:51 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.32 | 26-APR-13:00 | 404.83 | 16-APR-12:10 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:50 | 380.21 | 29-MAY-13:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.04 | 29-JUN-11:00 | 244.76 | 11-JUN-12:00 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.01 | 23-JUL-10:50 | 203.91 | 09-JUL-12:30 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.36 | 17-AUG-14:00 | 184.36 | 27-AUG-12:20 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.70 | 29-SEP-14:00 | 304.61 | 04-SEP-14:10 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.41 | 15-OCT-12:44 | 398.60 | 30-OCT-02:51 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | 18-NOV-13:00 | 507.98 | 23-NOV-07:00 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.58 | 05-DEC-10:00 | 508.11 | 03-DEC-11:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 184.36 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 202.41 | 641.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.66 | 14-JAN-12:25 | 424.81 | 02-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.13 | 01-FEB-12:00 | 387.25 | 25-FEB-02:41 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 11-MAR-12:20 | 442.52 | 26-MAR-14:00 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.20 | 30-APR-11:10 | 348.73 | 16-APR-17:30 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 | 03-MAY-12:00 | 352.34 | 07-MAY-15:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.91 | 25-JUN-11:20 | 249.20 | 04-JUN-16:30 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.32 | 23-JUL-11:10 | 253.18 | 09-JUL-17:10 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.72 | 06-AUG-12:00 | 179.67 | 27-AUG-15:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.37 | 29-SEP-14:00 | 264.14 | 03-SEP-16:30 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.71 | 15-OCT-08:51 | 293.82 | 11-OCT-01:51 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.54 | 19-NOV-12:10 | 382.54 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.48 | 25-DEC-12:00 | 355.32 | 23-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 | 179.67 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 194.71 | 442.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 96.20 | 15-JAN-14:40 | 1073.33 | 27-JAN-05:14 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.71 | 01-FEB-12:00 | 1093.45 | 04-FEB-05:53 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.97 | 12-MAR-09:53 | 1366.86 | 28-MAR-21:02 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.88 | 30-APR-11:10 | 762.22 | 21-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 740.35 | 20-MAY-17:53 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 25-JUN-12:00 | 522.02 | 06-JUN-21:10 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.03 | 23-JUL-11:00 | 453.24 | 09-JUL-17:00 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.55 | 06-AUG-13:00 | 362.58 | 21-AUG-23:52 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.60 | 29-SEP-14:00 | 414.33 | 24-SEP-15:30 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 639.36 | 15-OCT-09:00 | 778.00 | 30-OCT-02:51 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.95 | 19-NOV-13:00 | 977.50 | 23-NOV-03:51 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 227.79 | 25-DEC-11:52 | 997.30 | 23-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.58 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 639.36 | 1366.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 133.33 | 15-JAN-14:40 | 714.70 | 27-JAN-05:18 |
February | 1239.33 | 01-FEB-08:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.68 | 01-FEB-12:00 | 763.32 | 26-FEB-09:55 |
March | 1239.33 | 01-MAR-08:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.08 | 11-MAR-14:00 | 910.03 | 28-MAR-21:02 |
April | 1239.33 | 03-APR-07:10 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.29 | 02-APR-12:50 | 582.80 | 16-APR-11:53 |
May | 1239.33 | 01-MAY-07:10 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 567.14 | 29-MAY-12:53 |
June | 1239.33 | 01-JUN-07:10 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.20 | 29-JUN-11:00 | 383.32 | 04-JUN-13:27 |
July | 1239.33 | 03-JUL-07:10 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.54 | 31-JUL-13:00 | 383.29 | 16-JUL-09:50 |
August | 1239.33 | 01-AUG-07:10 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.11 | 13-AUG-15:10 | 303.15 | 06-AUG-10:10 |
September | 1239.33 | 01-SEP-07:10 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.63 | 29-SEP-14:10 | 424.62 | 03-SEP-07:00 |
October | 1239.33 | 02-OCT-07:10 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.13 | 15-OCT-12:51 | 523.66 | 30-OCT-02:51 |
November | 1239.33 | 01-NOV-07:10 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.85 | 19-NOV-12:50 | 730.32 | 23-NOV-07:00 |
December | 1239.33 | 01-DEC-08:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 111.32 | 17-DEC-13:00 | 659.47 | 23-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.15 | |||||
Maximum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 452.13 | 910.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 | 14-JAN-11:00 | 1287.66 | 29-JAN-12:50 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.63 | 01-FEB-12:00 | 1472.88 | 20-FEB-14:40 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1367.55 | 28-MAR-21:02 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.18 | 26-APR-13:00 | 972.31 | 16-APR-11:57 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 870.35 | 07-MAY-13:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.22 | 25-JUN-09:40 | 524.11 | 04-JUN-13:27 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.77 | 23-JUL-10:53 | 446.56 | 09-JUL-12:10 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.15 | 13-AUG-09:10 | 372.85 | 27-AUG-12:40 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.36 | 29-SEP-14:00 | 740.59 | 04-SEP-14:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 473.13 | 15-OCT-12:56 | 874.27 | 30-OCT-02:51 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.16 | 18-NOV-13:00 | 1078.16 | 05-NOV-14:00 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.90 | 05-DEC-10:00 | 1179.20 | 03-DEC-11:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.85 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 473.13 | 1472.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.10 | 15-JAN-14:10 | 737.80 | 06-JAN-22:55 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.90 | 01-FEB-12:00 | 790.15 | 26-FEB-16:28 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.27 | 12-MAR-10:30 | 912.62 | 28-MAR-21:02 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.54 | 30-APR-11:30 | 750.70 | 16-APR-17:30 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.16 | 28-MAY-11:50 | 784.57 | 29-MAY-16:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.47 | 25-JUN-11:40 | 551.02 | 04-JUN-16:40 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.80 | 23-JUL-11:20 | 588.52 | 09-JUL-17:00 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.93 | 06-AUG-12:20 | 395.95 | 27-AUG-18:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.07 | 29-SEP-14:00 | 585.90 | 03-SEP-16:20 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 495.18 | 15-OCT-09:00 | 561.56 | 30-OCT-02:51 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.04 | 19-NOV-12:10 | 678.19 | 23-NOV-03:51 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.57 | 25-DEC-11:52 | 686.01 | 23-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 28.16 | 395.95 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 495.18 | 912.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 222.68 | 15-JAN-09:55 | 1340.42 | 27-JAN-05:20 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.20 | 01-FEB-12:00 | 1371.48 | 08-FEB-06:00 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 96.57 | 12-MAR-10:12 | 1699.89 | 28-MAR-21:02 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 247.77 | 30-APR-11:00 | 880.24 | 21-APR-21:53 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 914.34 | 07-MAY-17:55 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.53 | 25-JUN-12:00 | 663.71 | 04-JUN-17:20 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.23 | 23-JUL-11:00 | 621.36 | 09-JUL-17:00 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.06 | 06-AUG-13:10 | 452.02 | 27-AUG-18:00 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.09 | 29-SEP-14:00 | 554.12 | 24-SEP-15:10 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 862.05 | 15-OCT-09:00 | 866.33 | 28-OCT-04:55 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.50 | 19-NOV-13:00 | 1141.32 | 30-NOV-05:20 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 457.83 | 25-DEC-11:55 | 1206.92 | 13-DEC-05:18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.02 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 862.05 | 1699.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 142.76 | 15-JAN-14:50 | 893.63 | 27-JAN-05:19 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.03 | 01-FEB-12:00 | 914.35 | 08-FEB-05:57 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.37 | 11-MAR-14:00 | 1131.43 | 28-MAR-21:02 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.31 | 30-APR-11:20 | 714.35 | 16-APR-11:53 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 752.16 | 29-MAY-12:53 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.21 | 29-JUN-11:00 | 495.57 | 04-JUN-14:00 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.62 | 31-JUL-13:00 | 487.89 | 16-JUL-10:00 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.96 | 06-AUG-13:10 | 359.14 | 20-AUG-08:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.39 | 29-SEP-14:00 | 453.34 | 03-SEP-07:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 551.88 | 15-OCT-13:00 | 577.59 | 28-OCT-04:57 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.37 | 19-NOV-12:50 | 760.90 | 30-NOV-05:16 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 202.63 | 25-DEC-12:00 | 804.63 | 13-DEC-05:19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.14 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 551.88 | 1131.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.76 | 15-JAN-09:55 | 1549.84 | 29-JAN-12:50 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.99 | 01-FEB-12:00 | 1803.63 | 20-FEB-14:40 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1701.87 | 28-MAR-21:02 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.32 | 30-APR-10:00 | 1186.62 | 16-APR-12:00 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1115.92 | 29-MAY-12:53 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.47 | 25-JUN-10:00 | 678.44 | 04-JUN-14:00 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.76 | 23-JUL-11:00 | 592.32 | 09-JUL-12:20 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.19 | 13-AUG-08:51 | 503.23 | 20-AUG-14:00 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.53 | 29-SEP-14:00 | 885.67 | 04-SEP-13:40 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 597.76 | 15-OCT-08:53 | 1077.63 | 29-OCT-13:50 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.59 | 18-NOV-13:00 | 1271.62 | 23-NOV-16:31 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.65 | 05-DEC-10:00 | 1370.84 | 03-DEC-10:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.23 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 597.76 | 1803.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 112.77 | 15-JAN-09:55 | 893.64 | 27-JAN-05:19 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.88 | 01-FEB-12:00 | 969.64 | 26-FEB-16:08 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 68.38 | 12-MAR-10:12 | 1136.36 | 28-MAR-21:02 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.25 | 30-APR-11:20 | 976.93 | 16-APR-17:50 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.39 | 28-MAY-09:52 | 961.21 | 29-MAY-15:50 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.09 | 25-JUN-12:00 | 702.34 | 04-JUN-16:40 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 291.61 | 23-JUL-11:00 | 753.62 | 09-JUL-17:00 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.73 | 06-AUG-12:30 | 505.33 | 27-AUG-18:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.39 | 29-SEP-14:00 | 723.62 | 03-SEP-16:10 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 661.27 | 15-OCT-09:00 | 608.30 | 30-OCT-02:51 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.50 | 19-NOV-12:10 | 796.12 | 23-NOV-16:31 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 282.25 | 25-DEC-12:00 | 804.62 | 13-DEC-05:19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 36.39 | 505.33 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 661.27 | 1136.36 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 8217.58 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 8217.58 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 8217.58 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 8217.58 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 8217.58 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 8217.58 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 8217.58 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 8217.58 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 8217.58 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 8217.58 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 8217.58 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 8217.58 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 8217.58 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 8217.58 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.37 | 15-JAN-09:55 | 1548.76 | 02-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.69 | 01-FEB-12:00 | 1358.47 | 25-FEB-02:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1438.27 | 28-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.40 | 30-APR-10:52 | 875.26 | 17-APR-02:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 797.73 | 27-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.06 | 29-JUN-11:00 | 565.14 | 07-JUN-00:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.94 | 31-JUL-13:00 | 423.31 | 13-JUL-02:51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.23 | 17-AUG-14:00 | 418.27 | 21-AUG-23:52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.85 | 29-SEP-13:50 | 478.77 | 04-SEP-18:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.76 | 15-OCT-12:51 | 948.04 | 30-OCT-02:51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.17 | 19-NOV-13:00 | 1308.80 | 23-NOV-03:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.94 | 05-DEC-10:00 | 1178.05 | 23-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.27 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.76 | 1548.76 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.90 | 15-JAN-09:55 | 2181.16 | 02-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.68 | 01-FEB-12:00 | 2323.88 | 25-FEB-02:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.39 | 11-MAR-12:50 | 2463.73 | 28-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.20 | 30-APR-11:00 | 1470.77 | 21-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1430.31 | 27-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.58 | 29-JUN-11:00 | 978.46 | 07-JUN-00:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.36 | 23-JUL-11:00 | 718.11 | 13-JUL-02:51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.34 | 06-AUG-13:00 | 696.50 | 21-AUG-23:52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.88 | 29-SEP-13:50 | 799.97 | 02-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 914.75 | 15-OCT-13:00 | 1603.13 | 30-OCT-02:51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.30 | 19-NOV-13:00 | 2235.56 | 23-NOV-03:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.46 | 04-DEC-10:00 | 2044.31 | 23-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 696.50 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 914.75 | 2463.73 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.33 | 15-JAN-09:55 | 1979.58 | 06-JAN-22:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2058.73 | 25-FEB-02:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2576.74 | 28-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.65 | 26-APR-13:00 | 1953.97 | 16-APR-12:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2173.82 | 29-MAY-13:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 1563.76 | 04-JUN-14:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.21 | 31-JUL-13:00 | 1360.31 | 09-JUL-12:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.48 | 17-AUG-14:00 | 944.09 | 20-AUG-14:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.00 | 29-SEP-13:20 | 1168.63 | 24-SEP-15:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.99 | 15-OCT-08:51 | 1379.60 | 11-OCT-01:51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.62 | 19-NOV-09:51 | 1601.14 | 23-NOV-03:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.45 | 18-DEC-03:00 | 1867.79 | 23-DEC-03:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 944.09 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.99 | 2576.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 139719.73 | 02-JAN-05:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 140761.62 | 21-FEB-05:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 123871.24 | 20-MAR-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 122577.89 | 10-APR-04:12 | 0.00 | 19429.86 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 131054.77 | 27-MAY-04:12 | 0.00 | 9714.93 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 134764.14 | 05-JUN-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 115242.64 | 10-JUL-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 112389.59 | 22-AUG-04:11 | 0.00 | 22668.17 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 121176.15 | 20-SEP-04:12 | 0.00 | 16191.55 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 145198.22 | 30-OCT-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 125929.85 | 24-NOV-05:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 127134.71 | 11-DEC-05:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 112389.59 | 0.00 | 9714.93 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 145198.22 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 115035.92 | 02-JAN-05:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 109173.78 | 02-FEB-05:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 113351.03 | 24-MAR-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 114296.79 | 28-APR-04:11 | 0.00 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 114614.34 | 01-MAY-04:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 116606.46 | 12-JUN-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 119244.47 | 05-JUL-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 119590.29 | 28-AUG-04:11 | 0.00 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 114683.71 | 05-SEP-04:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 119193.88 | 16-OCT-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 118399.74 | 13-NOV-05:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 114570.71 | 11-DEC-05:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 109173.78 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 119590.29 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 98110.51 | 25-JAN-06:01 | 12897.91 | 23265.84 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 98722.92 | 02-FEB-06:01 | 14510.15 | 26174.07 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 102152.64 | 24-MAR-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 100087.48 | 12-APR-05:01 | 11285.67 | 20357.61 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 99904.06 | 19-MAY-05:01 | 12897.91 | 23265.84 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 102927.42 | 06-JUN-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 101833.15 | 14-JUL-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 99391.92 | 23-AUG-04:11 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 101202.73 | 02-SEP-05:01 | 12897.91 | 23265.84 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 103369.82 | 17-OCT-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 102717.13 | 01-NOV-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 99283.67 | 08-DEC-06:01 | 11285.67 | 20357.61 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 98110.51 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 103369.82 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 43981.25 | 18-JAN-15:00 | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 45300.05 | 16-FEB-15:32 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 50401.70 | 23-MAR-15:40 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 55697.85 | 27-APR-14:50 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 93656.01 | 03-MAY-05:01 | 11285.67 | 20357.61 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 107338.09 | 28-JUN-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 105526.96 | 07-JUL-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 102311.56 | 22-AUG-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 102215.72 | 30-SEP-05:02 | 9673.43 | 17449.38 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 106383.27 | 06-OCT-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 45256.40 | 10-NOV-14:52 | 160145.81 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 43486.55 | 05-DEC-16:00 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 43486.55 | 9673.43 | 17449.38 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 107338.09 | 160145.81 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7569.36 | 24-JAN-14:30 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 |
February | 6959.94 | 01-FEB-12:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 0.00 |
March | 7532.41 | 23-MAR-14:00 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.20 |
April | 10038.82 | 26-APR-13:30 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 0.00 |
May | 9942.64 | 04-MAY-13:30 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.78 |
June | 9276.99 | 29-JUN-16:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.32 |
July | 11211.35 | 31-JUL-13:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 35.21 | 0.00 |
August | 11128.66 | 17-AUG-14:00 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 28.36 | 0.00 |
September | 13084.81 | 29-SEP-13:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 82.55 | 0.00 |
October | 13070.09 | 16-OCT-12:10 | 3846.22 | 6572.83 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.20 | 0.00 |
November | 7349.79 | 28-NOV-14:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 | 0.00 |
December | 7898.21 | 05-DEC-14:25 | 4021.58 | 6572.83 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6959.94 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13084.81 | 4021.58 | 6572.83 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.20 | 11.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10816.46 | 20-JAN-08:55 | 2478.65 | 4235.78 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 29824.51 | 20-FEB-09:51 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.10 |
March | 33290.72 | 19-MAR-09:11 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.43 |
April | 31819.90 | 09-APR-09:22 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.74 |
May | 32466.76 | 21-MAY-08:31 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.37 |
June | 35053.19 | 18-JUN-07:41 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.40 |
July | 36397.73 | 23-JUL-08:21 | 587.05 | 1058.95 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.37 |
August | 31509.97 | 06-AUG-08:32 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.61 |
September | 35102.55 | 10-SEP-08:11 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.18 |
October | 33091.34 | 09-OCT-08:11 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.69 |
November | 15106.03 | 19-NOV-09:22 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.92 |
December | 11124.57 | 05-DEC-09:00 | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10816.46 | 326.14 | 588.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36397.73 | 2478.65 | 4235.78 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 41992.55 | 22-JAN-11:41 | 910.97 | 1643.24 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.11 |
February | 41525.42 | 20-FEB-12:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.52 |
March | 37493.70 | 12-MAR-11:32 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.84 |
April | 36551.44 | 30-APR-13:01 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.93 |
May | 13613.15 | 04-MAY-12:30 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 |
June | 11959.98 | 30-JUN-12:20 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 |
July | 22856.02 | 30-JUL-13:01 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.45 |
August | 20756.78 | 30-AUG-12:40 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 |
September | 37744.96 | 04-SEP-12:12 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.28 |
October | 43947.15 | 29-OCT-12:21 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.84 |
November | 41829.56 | 05-NOV-12:01 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.51 |
December | 42110.89 | 24-DEC-12:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11959.98 | 607.31 | 1095.50 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 | |
Maximum of Months | 43947.15 | 1923.15 | 3286.49 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14311.61 | 18-JAN-14:45 | 2591.66 | 4235.78 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 |
February | 34938.44 | 26-FEB-15:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.40 |
March | 40564.31 | 19-MAR-17:11 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.83 |
April | 41316.06 | 09-APR-14:41 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.14 |
May | 41120.55 | 21-MAY-15:21 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.11 |
June | 41915.33 | 25-JUN-17:21 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.63 |
July | 46175.61 | 23-JUL-16:21 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.10 |
August | 40384.03 | 13-AUG-16:01 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.35 |
September | 41028.45 | 04-SEP-14:51 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.07 |
October | 40074.06 | 15-OCT-15:01 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 51.81 | 0.00 |
November | 38220.92 | 12-NOV-15:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.23 |
December | 32000.19 | 24-DEC-14:31 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14311.61 | 0.00 | 823.62 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46175.61 | 2591.66 | 4235.78 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 51.81 | 314.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6151.75 | 24-JAN-14:50 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 5.21 | 0.00 |
February | 5143.51 | 01-FEB-13:07 | 5769.33 | 9859.25 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.05 |
March | 5837.37 | 23-MAR-14:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.22 |
April | 8430.32 | 26-APR-14:00 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 27.77 | 0.00 |
May | 8950.49 | 04-MAY-13:40 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.63 |
June | 8309.89 | 29-JUN-16:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 |
July | 9605.95 | 19-JUL-14:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 54.08 | 0.00 |
August | 9641.21 | 17-AUG-14:00 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 64.70 | 0.00 |
September | 12479.68 | 29-SEP-13:10 | 4021.58 | 6572.83 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.22 | 0.00 |
October | 11769.76 | 16-OCT-12:20 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 244.82 | 0.00 |
November | 5119.46 | 28-NOV-13:50 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 10.46 | 0.00 |
December | 5664.88 | 05-DEC-15:00 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 15.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5119.46 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12479.68 | 5769.33 | 9859.25 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 244.82 | 30.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9760.10 | 20-JAN-09:30 | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.88 |
February | 16717.68 | 21-FEB-11:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.66 |
March | 32248.90 | 19-MAR-09:01 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.53 |
April | 30654.86 | 30-APR-09:22 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.22 |
May | 33614.28 | 28-MAY-08:31 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.05 |
June | 35305.35 | 18-JUN-08:61 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.53 |
July | 35222.55 | 02-JUL-08:51 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.60 |
August | 35405.82 | 06-AUG-08:11 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.03 |
September | 33228.51 | 03-SEP-09:01 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.75 |
October | 36286.60 | 15-OCT-09:21 | 587.05 | 1058.95 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 104.48 | 0.00 |
November | 15468.26 | 04-NOV-10:01 | 3913.66 | 7059.64 | 7735.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.93 |
December | 11648.90 | 23-DEC-11:01 | 3913.66 | 7059.64 | 7735.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9760.10 | 391.37 | 705.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36286.60 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 104.48 | 310.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 40071.66 | 08-JAN-13:21 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 702.81 |
February | 40457.83 | 20-FEB-12:41 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1147.39 |
March | 38113.76 | 19-MAR-13:01 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 754.88 |
April | 28175.96 | 09-APR-13:21 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.48 |
May | 12520.37 | 04-MAY-12:30 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.53 |
June | 10907.72 | 30-JUN-12:30 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.12 |
July | 31091.77 | 30-JUL-13:11 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.50 |
August | 26364.32 | 06-AUG-12:52 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.73 |
September | 35847.45 | 04-SEP-12:02 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.22 |
October | 44734.79 | 15-OCT-12:41 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 47.63 | 0.00 |
November | 40854.89 | 05-NOV-12:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 936.99 |
December | 42760.12 | 25-DEC-13:01 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10907.72 | 607.31 | 1095.50 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44734.79 | 1923.15 | 3286.49 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 47.63 | 1147.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12031.89 | 18-JAN-15:00 | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.53 |
February | 13514.32 | 26-FEB-16:29 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 761.61 |
March | 33823.80 | 19-MAR-16:21 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.19 |
April | 35262.25 | 02-APR-16:01 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.62 |
May | 37361.19 | 28-MAY-16:51 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.96 |
June | 36223.69 | 25-JUN-16:31 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.46 |
July | 40600.92 | 09-JUL-15:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 38983.67 | 06-AUG-16:51 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.36 |
September | 35331.06 | 04-SEP-16:01 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.57 |
October | 41503.40 | 15-OCT-15:21 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 10.18 | 0.00 |
November | 12933.67 | 07-NOV-15:23 | 7435.95 | 12707.35 | 8354.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.77 |
December | 20142.28 | 25-DEC-15:41 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12031.89 | 456.59 | 823.62 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41503.40 | 7435.95 | 12707.35 | 8354.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.18 | 761.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6444.25 | 18-JAN-14:02 | 10053.95 | 16432.08 | 10802.76 | 0.00 | 0.00 | 0.00 | 0.00 | 10.23 | 0.00 |
February | 5259.94 | 01-FEB-13:10 | 5769.33 | 9859.25 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 |
March | 6570.98 | 23-MAR-14:40 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.60 |
April | 9761.74 | 26-APR-14:00 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 32.49 | 0.00 |
May | 10221.39 | 04-MAY-13:40 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.78 |
June | 9527.66 | 29-JUN-16:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.41 |
July | 11137.67 | 19-JUL-14:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 64.62 | 0.00 |
August | 10964.73 | 17-AUG-14:00 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 78.08 | 0.00 |
September | 13870.70 | 29-SEP-13:10 | 4021.58 | 6572.83 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.86 | 0.00 |
October | 13178.13 | 16-OCT-12:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 287.45 | 0.00 |
November | 6037.77 | 19-NOV-14:02 | 607.30 | 1095.47 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.89 | 0.00 |
December | 6190.88 | 19-DEC-13:40 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5259.94 | 607.30 | 1095.47 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13870.70 | 10053.95 | 16432.08 | 10802.76 | 0.00 | 0.00 | 0.00 | 0.00 | 287.45 | 41.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8211.15 | 20-JAN-09:50 | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 |
February | 8316.98 | 01-FEB-10:05 | 2591.66 | 4235.78 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.96 |
March | 27630.34 | 19-MAR-09:01 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.19 |
April | 33587.31 | 30-APR-09:51 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.54 |
May | 32156.13 | 28-MAY-09:01 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.26 |
June | 33354.19 | 25-JUN-07:51 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.28 |
July | 36610.49 | 23-JUL-08:51 | 587.05 | 1058.95 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.61 |
August | 34743.82 | 06-AUG-09:41 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.19 |
September | 33686.75 | 10-SEP-08:61 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
October | 35764.32 | 15-OCT-09:31 | 587.05 | 1058.95 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 113.19 | 0.00 |
November | 8523.97 | 19-NOV-10:02 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 0.00 |
December | 8608.70 | 05-DEC-09:50 | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 19.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8211.15 | 391.37 | 705.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36610.49 | 2591.66 | 4235.78 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 113.19 | 387.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 42509.81 | 08-JAN-13:21 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 824.61 |
February | 43701.05 | 20-FEB-12:41 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1377.28 |
March | 41768.57 | 19-MAR-13:01 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 917.79 |
April | 38165.53 | 30-APR-13:11 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.81 |
May | 13809.11 | 04-MAY-12:30 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.81 |
June | 12265.77 | 30-JUN-13:10 | 4021.67 | 6572.98 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.63 |
July | 17545.80 | 31-JUL-12:40 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 87.42 | 0.00 |
August | 20823.66 | 30-AUG-12:50 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 |
September | 41118.64 | 10-SEP-14:01 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.86 |
October | 50121.53 | 15-OCT-12:11 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 45.15 | 0.00 |
November | 45165.53 | 23-NOV-13:01 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.14 |
December | 43099.49 | 24-DEC-14:21 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 868.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12265.77 | 708.53 | 1278.08 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50121.53 | 4021.67 | 6572.98 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 87.42 | 1377.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12342.75 | 18-JAN-15:00 | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.09 |
February | 13587.98 | 22-FEB-15:36 | 6196.63 | 10589.46 | 6961.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.66 |
March | 31871.29 | 19-MAR-16:21 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.86 |
April | 39451.34 | 30-APR-15:11 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.33 |
May | 40436.68 | 28-MAY-16:41 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.54 |
June | 40378.22 | 25-JUN-17:21 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.06 |
July | 44268.50 | 09-JUL-15:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43021.81 | 06-AUG-16:21 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.40 |
September | 38942.47 | 03-SEP-15:31 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.25 |
October | 44920.87 | 15-OCT-15:31 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.14 |
November | 13027.17 | 07-NOV-15:23 | 7435.95 | 12707.35 | 8354.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.57 |
December | 13252.38 | 18-DEC-15:30 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12342.75 | 0.00 | 941.28 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44920.87 | 7435.95 | 12707.35 | 8354.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11571.45 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.78 |
February | 9253.80 | 22-FEB-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.00 |
March | 13402.23 | 29-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1040.47 |
April | 9855.15 | 14-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.06 |
May | 10271.06 | 02-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.09 |
June | 9688.50 | 12-JUN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.33 |
July | 10336.51 | 24-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11094.44 | 21-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.84 |
September | 10490.89 | 11-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11627.16 | 16-OCT-14:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.63 | 0.00 |
November | 12669.19 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.61 |
December | 9923.08 | 20-DEC-05:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 889.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9253.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13402.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.63 | 1040.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16396.70 | 27-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1994.69 |
February | 14631.58 | 04-FEB-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2019.23 |
March | 19065.64 | 29-MAR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1767.05 |
April | 14475.05 | 01-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1109.17 |
May | 9918.63 | 13-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.45 |
June | 8948.25 | 22-JUN-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.44 |
July | 8790.20 | 06-JUL-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.73 |
August | 8792.66 | 22-AUG-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.23 |
September | 9499.81 | 16-SEP-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.31 |
October | 9671.89 | 18-OCT-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 753.59 |
November | 14551.18 | 30-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1772.99 |
December | 16565.11 | 13-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1785.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8790.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.31 | |
Maximum of Months | 19065.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2019.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19080.75 | 18-JAN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.91 |
February | 19555.09 | 01-FEB-13:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.06 |
March | 26159.50 | 23-MAR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.39 |
April | 32883.87 | 26-APR-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.20 |
May | 30786.37 | 03-MAY-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.63 |
June | 30382.17 | 21-JUN-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.46 |
July | 33288.90 | 19-JUL-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.66 | 0.00 |
August | 32153.17 | 14-AUG-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.94 |
September | 32416.58 | 29-SEP-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.42 | 0.00 |
October | 32541.90 | 16-OCT-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.37 | 0.00 |
November | 18728.19 | 10-NOV-14:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.35 |
December | 17428.53 | 19-DEC-14:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 17428.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33288.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.42 | 243.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2381.79 | 30-JAN-16:43 | 666.42 | 2186.35 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4363.76 | 22-FEB-16:57 | 666.42 | 2186.35 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6525.44 | 31-MAR-23:22 | 0.00 | 404.88 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8029.40 | 26-APR-16:00 | 222.14 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3113.55 | 31-MAY-23:52 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5244.78 | 30-JUN-23:52 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7212.46 | 31-JUL-24:00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8155.18 | 06-AUG-17:40 | 0.00 | 283.42 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3401.62 | 30-SEP-23:51 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5139.60 | 31-OCT-23:52 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6227.69 | 07-NOV-16:17 | 888.56 | 2915.14 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8245.00 | 18-DEC-16:10 | 222.14 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2381.79 | 0.00 | 40.49 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8245.00 | 888.56 | 2915.14 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2173.12 | 30-JAN-16:43 | 666.42 | 2186.35 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4159.82 | 22-FEB-16:57 | 666.42 | 2186.35 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5988.26 | 10-MAR-17:00 | 222.14 | 728.78 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7645.18 | 26-APR-16:00 | 222.14 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2671.51 | 31-MAY-23:52 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4902.61 | 30-JUN-23:52 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6752.43 | 31-JUL-24:00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7686.71 | 31-AUG-17:00 | 70.15 | 404.88 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3174.36 | 30-SEP-23:42 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4684.23 | 31-OCT-23:42 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5924.36 | 07-NOV-16:17 | 888.56 | 2915.14 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7728.49 | 18-DEC-16:20 | 222.14 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2173.12 | 0.00 | 40.49 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7728.49 | 888.56 | 2915.14 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2162.05 | 30-JAN-16:43 | 666.42 | 2186.35 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4236.28 | 22-FEB-16:57 | 666.42 | 2186.35 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6119.35 | 10-MAR-17:00 | 222.14 | 728.78 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7843.35 | 26-APR-16:00 | 222.14 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2318.16 | 31-MAY-23:12 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4668.13 | 30-JUN-23:22 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6563.12 | 31-JUL-23:30 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7861.25 | 17-AUG-16:00 | 222.14 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2968.47 | 30-SEP-23:12 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4417.81 | 15-OCT-16:32 | 105.22 | 364.39 | 35074.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5966.20 | 07-NOV-16:17 | 888.56 | 2915.14 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7779.90 | 19-DEC-16:10 | 222.14 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2162.05 | 0.00 | 40.49 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7861.25 | 888.56 | 2915.14 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 105776.61 | 07-JAN-05:11 | 0.00 | 4565.32 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 483878.72 | 05-FEB-23:32 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 516273.68 | 07-MAR-15:12 | 48086.79 | 82175.84 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 491372.52 | 05-APR-15:43 | 48086.79 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 465758.60 | 31-MAY-23:52 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 478072.56 | 13-JUN-03:22 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 473527.88 | 06-JUL-05:12 | 5061.77 | 9130.65 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 473561.30 | 22-AUG-05:16 | 5061.77 | 9130.65 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 390047.07 | 30-SEP-23:56 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 508668.25 | 31-OCT-23:23 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 519798.86 | 22-NOV-14:52 | 50279.21 | 82175.84 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 512920.97 | 22-DEC-14:44 | 50279.21 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 105776.61 | 0.00 | 4565.32 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 519798.86 | 50279.21 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.195286E+13 | 1663487.72 | 18-JAN-11:50 | 0.120033E+12 | 858886.85 | 03-JAN-05:19 |
February | 0.208093E+13 | 1852530.44 | 01-FEB-11:50 | 0.102750E+12 | 637026.81 | 06-FEB-05:19 |
March | 0.276949E+13 | 2070919.31 | 23-MAR-15:20 | 0.118465E+12 | 815148.22 | 30-MAR-04:19 |
April | 0.299889E+13 | 2219265.76 | 26-APR-14:09 | 0.478208E+11 | 588916.30 | 01-APR-04:19 |
May | 0.196143E+13 | 1608939.98 | 03-MAY-14:09 | 0.376930E+11 | 452123.46 | 27-MAY-05:10 |
June | 0.240120E+13 | 1921300.42 | 29-JUN-15:00 | 0.105980E+11 | 277992.93 | 01-JUN-05:10 |
July | 0.289826E+13 | 2125484.63 | 25-JUL-15:39 | 0.291996E+10 | 144129.03 | 06-JUL-05:10 |
August | 0.343182E+13 | 2320480.48 | 15-AUG-15:00 | 0.422521E+10 | 103846.26 | 31-AUG-05:10 |
September | 0.200211E+13 | 1896693.16 | 29-SEP-15:00 | 0.140698E+11 | 300567.59 | 20-SEP-05:10 |
October | 0.252402E+13 | 2007063.34 | 16-OCT-15:50 | 0.270338E+11 | 535294.64 | 12-OCT-05:10 |
November | 0.270681E+13 | 2027260.22 | 29-NOV-11:50 | 0.721398E+11 | 599262.02 | 24-NOV-05:19 |
December | 0.317247E+13 | 2193211.31 | 05-DEC-11:39 | 0.104449E+12 | 710154.69 | 13-DEC-05:19 |
Annual Sum or Average | 0.309003E+14 | 0.662197E+12 | ||||
Minimum of Months | 0.195286E+13 | 1608939.98 | 0.291996E+10 | 103846.26 | ||
Maximum of Months | 0.343182E+13 | 2320480.48 | 0.120033E+12 | 858886.85 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.468149E+12 | 0.992771E+11 | 0.766053E+12 | 0.218140E+12 | 0.191564E+12 | 0.391952E+11 | 0.00 | 0.817304E+11 | 0.262077E+10 | 0.518149E+11 | 0.00 | 0.343178E+11 | 0.00 |
February | 0.424646E+12 | 0.848584E+11 | 0.978954E+12 | 0.199667E+12 | 0.187861E+12 | 0.412070E+11 | 0.00 | 0.952312E+11 | 0.153352E+10 | 0.357514E+11 | 0.00 | 0.312184E+11 | 0.00 |
March | 0.504598E+12 | 0.869732E+11 | 0.141687E+13 | 0.230864E+12 | 0.235889E+12 | 0.969112E+11 | 0.00 | 0.134594E+12 | 0.276371E+10 | 0.237162E+11 | 0.00 | 0.363113E+11 | 0.00 |
April | 0.450709E+12 | 0.773223E+11 | 0.165903E+13 | 0.216144E+12 | 0.263755E+12 | 0.933917E+11 | 0.00 | 0.186464E+12 | 0.705572E+10 | 0.127354E+11 | 0.00 | 0.322871E+11 | 0.00 |
May | 0.486374E+12 | 0.738234E+11 | 0.774844E+12 | 0.224502E+12 | 0.202421E+12 | 0.527388E+11 | 0.00 | 0.104952E+12 | 0.428117E+10 | 0.388413E+10 | 0.00 | 0.336151E+11 | 0.00 |
June | 0.484022E+12 | 0.684404E+11 | 0.106252E+13 | 0.222585E+12 | 0.228513E+12 | 0.744650E+11 | 0.00 | 0.212006E+12 | 0.159823E+11 | 88818619.60 | 0.00 | 0.325801E+11 | 0.00 |
July | 0.453060E+12 | 0.720547E+11 | 0.139340E+13 | 0.218061E+12 | 0.269601E+12 | 0.107908E+12 | 0.00 | 0.316575E+12 | 0.365965E+11 | 0.437649E+09 | 0.00 | 0.305653E+11 | 0.00 |
August | 0.504598E+12 | 0.771685E+11 | 0.173200E+13 | 0.230864E+12 | 0.307119E+12 | 0.120561E+12 | 0.00 | 0.379625E+12 | 0.459080E+11 | 0.598528E+09 | 0.00 | 0.333775E+11 | 0.00 |
September | 0.450709E+12 | 0.812442E+11 | 0.740713E+12 | 0.216143E+12 | 0.214170E+12 | 0.689471E+11 | 0.00 | 0.180254E+12 | 0.183721E+11 | 0.902113E+09 | 0.00 | 0.306597E+11 | 0.00 |
October | 0.468149E+12 | 0.910488E+11 | 0.108340E+13 | 0.218140E+12 | 0.231314E+12 | 0.848735E+11 | 0.00 | 0.255446E+12 | 0.219168E+11 | 0.374082E+11 | 0.00 | 0.323199E+11 | 0.00 |
November | 0.462662E+12 | 0.943171E+11 | 0.135889E+13 | 0.209941E+12 | 0.232902E+12 | 0.950689E+11 | 0.00 | 0.156413E+12 | 0.317567E+10 | 0.609313E+11 | 0.00 | 0.325092E+11 | 0.00 |
December | 0.453060E+12 | 0.100969E+12 | 0.170972E+13 | 0.218060E+12 | 0.255995E+12 | 0.949721E+11 | 0.00 | 0.180706E+12 | 0.276212E+10 | 0.123144E+12 | 0.00 | 0.330802E+11 | 0.00 |
Annual Sum or Average | 0.561074E+13 | 0.100750E+13 | 0.146764E+14 | 0.262311E+13 | 0.282110E+13 | 0.970239E+12 | 0.00 | 0.228400E+13 | 0.162968E+12 | 0.351413E+12 | 0.00 | 0.392842E+12 | 0.00 |
Minimum of Months | 0.424646E+12 | 0.684404E+11 | 0.740713E+12 | 0.199667E+12 | 0.187861E+12 | 0.391952E+11 | 0.00 | 0.817304E+11 | 0.153352E+10 | 88818619.60 | 0.00 | 0.305653E+11 | 0.00 |
Maximum of Months | 0.504598E+12 | 0.100969E+12 | 0.173200E+13 | 0.230864E+12 | 0.307119E+12 | 0.120561E+12 | 0.00 | 0.379625E+12 | 0.459080E+11 | 0.123144E+12 | 0.00 | 0.363113E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.120033E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.102750E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.118465E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.478208E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.376930E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.105980E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.291996E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.422521E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.140698E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.270338E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.721398E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.104449E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.662197E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.291996E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.120033E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 489900.85 | 02-JAN-08:09 | 64082.80 | 01-JAN-00:10 | 423497.50 | 02-JAN-08:09 | 235096.12 | 02-JAN-08:20 | 201634.48 | 18-JAN-15:39 | 81424.69 | 24-JAN-15:30 | 0.00 | 01-JAN-00:10 |
February | 489900.85 | 01-FEB-08:09 | 64082.80 | 01-FEB-00:10 | 541788.89 | 01-FEB-08:09 | 235096.12 | 01-FEB-08:20 | 210670.46 | 22-FEB-15:20 | 81109.39 | 01-FEB-13:20 | 0.00 | 01-FEB-00:10 |
March | 489900.85 | 01-MAR-08:09 | 64082.80 | 01-MAR-00:10 | 660080.29 | 01-MAR-08:09 | 235096.12 | 01-MAR-08:20 | 246027.34 | 23-MAR-14:50 | 80974.60 | 23-MAR-13:30 | 0.00 | 01-MAR-00:10 |
April | 489900.85 | 03-APR-07:10 | 64082.80 | 01-APR-00:10 | 778371.69 | 03-APR-07:10 | 235096.12 | 03-APR-07:19 | 249628.62 | 26-APR-14:50 | 83512.08 | 12-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 489900.85 | 01-MAY-07:10 | 64082.80 | 01-MAY-00:10 | 423497.50 | 01-MAY-07:10 | 235096.12 | 01-MAY-07:19 | 198068.66 | 03-MAY-15:20 | 81351.35 | 03-MAY-12:00 | 0.00 | 01-MAY-00:10 |
June | 489900.85 | 01-JUN-07:10 | 64082.80 | 01-JUN-00:10 | 541788.89 | 01-JUN-07:10 | 235096.12 | 01-JUN-07:19 | 208406.48 | 30-JUN-15:00 | 81125.11 | 27-JUN-09:50 | 0.00 | 01-JUN-00:10 |
July | 489900.85 | 03-JUL-07:10 | 64082.80 | 01-JUL-00:10 | 660080.29 | 03-JUL-07:10 | 235096.12 | 03-JUL-07:19 | 235374.26 | 26-JUL-15:30 | 82990.69 | 25-JUL-15:30 | 0.00 | 01-JUL-00:10 |
August | 489900.85 | 01-AUG-07:10 | 64082.80 | 01-AUG-00:10 | 778371.69 | 01-AUG-07:10 | 235096.12 | 01-AUG-07:19 | 257985.45 | 18-AUG-14:00 | 84272.41 | 15-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 489900.85 | 01-SEP-07:10 | 64082.80 | 01-SEP-00:10 | 423497.50 | 01-SEP-07:10 | 235096.12 | 01-SEP-07:19 | 280698.21 | 29-SEP-15:00 | 92751.74 | 29-SEP-10:50 | 0.00 | 01-SEP-00:10 |
October | 489900.85 | 02-OCT-07:10 | 64082.80 | 01-OCT-00:10 | 541788.89 | 02-OCT-07:10 | 235096.12 | 02-OCT-07:19 | 274235.36 | 16-OCT-15:50 | 94584.55 | 16-OCT-14:39 | 0.00 | 01-OCT-00:10 |
November | 489900.85 | 01-NOV-07:10 | 64082.80 | 01-NOV-00:10 | 660080.29 | 01-NOV-07:10 | 235096.12 | 01-NOV-07:19 | 220272.99 | 29-NOV-15:09 | 82069.43 | 28-NOV-13:50 | 0.00 | 01-NOV-00:10 |
December | 489900.85 | 01-DEC-08:09 | 64082.80 | 01-DEC-00:10 | 778371.69 | 01-DEC-08:09 | 235096.12 | 01-DEC-08:20 | 231955.23 | 07-DEC-15:39 | 81948.45 | 19-DEC-13:09 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 489900.85 | 64082.80 | 423497.50 | 235096.12 | 198068.66 | 80974.60 | 0.00 | |||||||
Maximum of Months | 489900.85 | 64082.80 | 778371.69 | 235096.12 | 280698.21 | 94584.55 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 274071.83 | 18-JAN-13:09 | 24626.43 | 18-JAN-14:50 | 100000.00 | 03-JAN-13:09 | 0.00 | 45273.70 | 31-JAN-12:50 | 0.00 |
February | 287864.04 | 01-FEB-11:50 | 32678.36 | 01-FEB-11:50 | 100000.00 | 01-FEB-08:39 | 0.00 | 45273.79 | 02-FEB-12:20 | 0.00 |
March | 278160.16 | 23-MAR-15:20 | 48088.10 | 22-MAR-12:50 | 100000.00 | 10-MAR-09:30 | 0.00 | 45062.96 | 01-MAR-12:50 | 0.00 |
April | 318192.26 | 26-APR-14:09 | 48088.10 | 12-APR-13:30 | 100000.00 | 01-APR-04:40 | 0.00 | 44278.45 | 03-APR-11:00 | 0.00 |
May | 259158.73 | 03-MAY-12:39 | 32206.71 | 03-MAY-12:39 | 100000.00 | 24-MAY-07:40 | 0.00 | 43298.28 | 01-MAY-11:50 | 0.00 |
June | 307585.97 | 27-JUN-12:09 | 48088.10 | 19-JUN-11:09 | 31018.06 | 12-JUN-09:00 | 0.00 | 42135.04 | 01-JUN-11:00 | 0.00 |
July | 362218.13 | 25-JUL-15:39 | 48088.10 | 03-JUL-11:00 | 64833.92 | 29-JUL-11:00 | 0.00 | 41194.80 | 03-JUL-11:20 | 0.00 |
August | 412099.16 | 15-AUG-15:00 | 48088.10 | 02-AUG-09:39 | 66938.14 | 19-AUG-08:00 | 0.00 | 41103.33 | 31-AUG-11:00 | 0.00 |
September | 322067.32 | 29-SEP-12:00 | 48088.10 | 05-SEP-12:00 | 46048.35 | 29-SEP-05:00 | 0.00 | 41876.78 | 29-SEP-11:00 | 0.00 |
October | 367767.71 | 04-OCT-10:50 | 48088.10 | 02-OCT-09:50 | 100000.00 | 12-OCT-09:50 | 0.00 | 43051.18 | 31-OCT-11:30 | 0.00 |
November | 299441.06 | 28-NOV-13:30 | 24044.05 | 10-NOV-12:39 | 100000.00 | 08-NOV-09:20 | 0.00 | 44135.05 | 30-NOV-12:20 | 0.00 |
December | 304137.31 | 18-DEC-14:50 | 21487.99 | 05-DEC-09:00 | 100000.00 | 03-DEC-23:40 | 0.00 | 44910.87 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 259158.73 | 21487.99 | 31018.06 | 0.00 | 41103.33 | 0.00 | ||||
Maximum of Months | 412099.16 | 48088.10 | 100000.00 | 0.00 | 45273.79 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1663487.72 | 18-JAN-11:50 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 146026.09 | 41795.42 | 0.00 | 206704.22 | 13608.14 |
February | 1852530.44 | 01-FEB-11:50 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 147926.98 | 80027.69 | 0.00 | 287864.04 | 32678.36 |
March | 2070919.31 | 23-MAR-15:20 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 245722.16 | 80015.16 | 0.00 | 278160.16 | 48088.10 |
April | 2219265.76 | 26-APR-14:09 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 246889.65 | 81528.87 | 0.00 | 318192.26 | 44208.69 |
May | 1608939.98 | 03-MAY-14:09 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 194664.72 | 41197.78 | 0.00 | 175522.80 | 24044.05 |
June | 1921300.42 | 29-JUN-15:00 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 206704.50 | 80677.62 | 0.00 | 287159.88 | 48088.10 |
July | 2125484.63 | 25-JUL-15:39 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 215680.94 | 82872.04 | 0.00 | 362218.13 | 48088.10 |
August | 2320480.48 | 15-AUG-15:00 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 241099.37 | 84272.41 | 0.00 | 412099.16 | 48088.10 |
September | 1896693.16 | 29-SEP-15:00 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 280698.21 | 84787.59 | 0.00 | 307757.93 | 42547.65 |
October | 2007063.34 | 16-OCT-15:50 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 274235.36 | 87542.11 | 0.00 | 316524.28 | 28939.10 |
November | 2027260.22 | 29-NOV-11:50 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 144377.46 | 80164.50 | 0.00 | 270847.23 | 10828.19 |
December | 2193211.31 | 05-DEC-11:39 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 162410.01 | 80346.62 | 0.00 | 291824.57 | 18700.74 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1608939.98 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 144377.46 | 41197.78 | 0.00 | 175522.80 | 10828.19 | |
Maximum of Months | 2320480.48 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 280698.21 | 87542.11 | 0.00 | 412099.16 | 48088.10 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 858886.85 | 03-JAN-05:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 637026.81 | 06-FEB-05:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 815148.22 | 30-MAR-04:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 588916.30 | 01-APR-04:19 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 452123.46 | 27-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 277992.93 | 01-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 144129.03 | 06-JUL-05:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 103846.26 | 31-AUG-05:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 300567.59 | 20-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 535294.64 | 12-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 599262.02 | 24-NOV-05:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 710154.69 | 13-DEC-05:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 103846.26 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 858886.85 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.89 | 0.33 | 26.93 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.74 | 0.00 | 25.74 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.62 | 0.00 | 25.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.64 | 0.00 | 25.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.68 | 0.00 | 25.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.67 | 0.00 | 25.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.75 | 0.00 | 25.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 26.21 | 0.00 | 26.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.20 | 0.00 | 26.20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.73 | 0.00 | 25.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.72 | 0.00 | 25.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.71 | 0.00 | 25.71 |
Annual Sum or Average | 0.00 | 0.00 | 15.83 | 26.08 | 0.33 | 26.11 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.62 | 0.00 | 25.62 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 26.89 | 0.33 | 26.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.89 | 1.17 | 27.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.34 | 2.67 | 28.34 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.19 | 2.17 | 28.19 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.51 | 2.50 | 28.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.68 | 5.50 | 28.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.60 | 4.33 | 28.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.49 | 2.00 | 28.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.59 | 1.67 | 28.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.81 | 0.50 | 27.81 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 22.67 | 28.47 | 22.67 | 28.47 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.68 | 5.50 | 28.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.56 | 5.00 | 28.56 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.61 | 4.00 | 28.61 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.29 | 2.50 | 28.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.70 | 2.17 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.50 | 0.50 | 27.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.48 | 2.50 | 27.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.74 | 5.33 | 27.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.34 | 14.33 | 27.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.93 | 5.83 | 28.93 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.98 | 10.00 | 27.98 |
Annual Sum or Average | 0.00 | 0.00 | 52.17 | 27.96 | 52.17 | 27.96 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 28.93 | 14.33 | 28.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.51 | 0.33 | 27.51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.97 | 0.67 | 27.97 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.56 | 1.00 | 28.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 29.02 | 4.67 | 29.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.41 | 4.17 | 28.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.60 | 2.83 | 28.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 29.00 | 6.33 | 29.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 29.14 | 4.50 | 29.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.84 | 3.17 | 28.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.62 | 4.83 | 28.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.79 | 2.17 | 27.79 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.84 | 1.67 | 27.84 |
Annual Sum or Average | 0.00 | 0.00 | 44.00 | 28.72 | 36.33 | 28.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.51 | 0.33 | 27.51 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 29.14 | 6.33 | 29.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
February | 0.50 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
March | 1.33 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
April | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
December | 0.67 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Annual Sum or Average | 5.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
February | 1.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
March | 1.50 | 19.22 | 0.00 | 19.22 | 0.50 | 21.29 | 0.50 | 22.54 |
April | 0.33 | 19.38 | 0.00 | 19.38 | 1.67 | 26.87 | 1.67 | 27.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.25 | 1.50 | 28.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.44 | 2.33 | 28.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.66 | 5.00 | 28.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.54 | 3.83 | 28.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.50 | 1.67 | 28.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.60 | 1.33 | 28.60 |
November | 0.50 | 19.37 | 0.00 | 19.37 | 0.17 | 21.36 | 0.17 | 22.56 |
December | 1.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Annual Sum or Average | 6.17 | 19.26 | 0.00 | 19.26 | 18.00 | 26.13 | 18.00 | 27.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.18 | 0.00 | 19.18 |
Maximum of Months | 1.83 | 19.38 | 0.00 | 19.38 | 5.00 | 28.66 | 5.00 | 28.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 19.24 | 0.00 | 19.24 | 6.17 | 26.78 | 6.17 | 27.25 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.53 | 4.17 | 28.53 |
March | 1.00 | 19.26 | 0.00 | 19.26 | 2.33 | 25.52 | 2.33 | 26.63 |
April | 0.17 | 19.43 | 0.00 | 19.43 | 0.67 | 25.94 | 0.67 | 26.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 26.60 | 7.83 | 26.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 26.83 | 20.67 | 26.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.90 | 6.00 | 28.90 |
December | 0.33 | 19.32 | 0.00 | 19.32 | 11.33 | 27.38 | 11.33 | 27.50 |
Annual Sum or Average | 2.33 | 19.27 | 0.00 | 19.27 | 59.17 | 27.13 | 59.17 | 27.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.43 | 0.00 | 19.43 | 20.67 | 28.90 | 20.67 | 28.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.50 | 19.19 | 0.00 | 19.19 | 0.50 | 23.75 | 0.50 | 25.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.39 | 3.00 | 28.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.25 | 2.83 | 28.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.24 | 2.33 | 28.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.55 | 5.00 | 28.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.68 | 3.17 | 28.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.40 | 2.83 | 28.40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.49 | 2.67 | 28.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Annual Sum or Average | 2.17 | 19.26 | 0.00 | 19.26 | 28.17 | 27.79 | 22.33 | 28.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 19.34 | 0.00 | 19.34 | 7.50 | 28.68 | 5.00 | 28.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.83 | 18.44 | 0.67 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 |
February | 2.67 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
March | 3.83 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
April | 0.50 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
May | 0.50 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.67 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
November | 2.83 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
December | 4.50 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
Annual Sum or Average | 21.33 | 18.85 | 0.67 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.83 | 19.26 | 0.67 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.17 | 18.24 | 0.33 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
February | 2.83 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
March | 3.50 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
April | 0.50 | 18.96 | 0.00 | 18.96 | 1.50 | 25.69 | 1.50 | 26.65 |
May | 0.67 | 19.20 | 0.00 | 19.20 | 1.17 | 24.64 | 1.17 | 25.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.36 | 2.00 | 28.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.57 | 5.00 | 28.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.40 | 3.67 | 28.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.21 | 1.33 | 28.21 |
October | 0.67 | 19.21 | 0.00 | 19.21 | 1.50 | 25.55 | 1.50 | 26.70 |
November | 3.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
December | 3.00 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
Annual Sum or Average | 19.33 | 18.77 | 0.33 | 18.75 | 16.17 | 23.08 | 16.17 | 24.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.20 | 0.00 | 18.20 |
Maximum of Months | 5.17 | 19.21 | 0.33 | 19.21 | 5.00 | 28.57 | 5.00 | 28.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 18.71 | 0.00 | 18.71 | 3.83 | 23.80 | 3.83 | 25.40 |
February | 2.33 | 19.08 | 0.00 | 19.08 | 3.17 | 24.40 | 3.17 | 25.83 |
March | 3.17 | 18.96 | 0.00 | 18.96 | 2.00 | 22.48 | 2.00 | 24.03 |
April | 0.50 | 19.05 | 0.00 | 19.05 | 0.50 | 23.28 | 0.50 | 24.69 |
May | 0.50 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.48 | 0.17 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.82 | 4.17 | 27.82 |
October | 0.50 | 19.35 | 0.00 | 19.35 | 12.00 | 27.51 | 12.00 | 27.68 |
November | 2.00 | 19.15 | 0.00 | 19.15 | 5.00 | 26.02 | 5.00 | 27.16 |
December | 2.67 | 19.01 | 0.00 | 19.01 | 6.50 | 25.80 | 6.50 | 26.96 |
Annual Sum or Average | 15.17 | 18.98 | 0.00 | 18.98 | 37.33 | 25.54 | 37.33 | 26.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 19.35 | 0.00 | 19.35 | 12.00 | 27.82 | 12.00 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
February | 2.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
March | 2.17 | 18.98 | 0.00 | 18.98 | 0.50 | 20.70 | 0.50 | 21.89 |
April | 0.33 | 19.07 | 0.00 | 19.07 | 3.83 | 27.66 | 3.17 | 28.02 |
May | 0.17 | 19.34 | 0.00 | 19.34 | 4.00 | 27.86 | 3.00 | 28.04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.35 | 2.50 | 28.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.69 | 5.33 | 28.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.81 | 3.17 | 28.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.47 | 2.50 | 28.49 |
October | 0.33 | 19.40 | 0.00 | 19.40 | 2.33 | 27.62 | 2.33 | 28.16 |
November | 1.50 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
December | 2.50 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
Annual Sum or Average | 12.17 | 18.98 | 0.00 | 18.98 | 28.83 | 25.71 | 22.50 | 26.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.70 | 0.00 | 18.70 |
Maximum of Months | 3.17 | 19.40 | 0.00 | 19.40 | 7.83 | 28.81 | 5.33 | 28.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.57 | 1.00 | 27.56 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.68 | 0.83 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.85 | 6.33 | 27.85 |
Annual Sum or Average | 0.00 | 0.00 | 10.17 | 27.75 | 8.17 | 27.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.85 | 6.33 | 27.85 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 80.67 | 23.56 | 189.50 | 24.78 | 0.00 | 24.78 |
February | 41.83 | 23.78 | 182.33 | 24.80 | 0.00 | 24.80 |
March | 18.00 | 23.56 | 255.17 | 24.61 | 0.00 | 24.61 |
April | 6.67 | 23.87 | 313.17 | 24.64 | 0.00 | 24.64 |
May | 16.83 | 23.28 | 322.33 | 24.57 | 0.00 | 24.57 |
June | 0.17 | 24.00 | 455.67 | 24.43 | 0.17 | 24.43 |
July | 1.00 | 24.00 | 497.00 | 24.58 | 1.00 | 24.58 |
August | 1.50 | 24.00 | 512.67 | 24.46 | 1.50 | 24.45 |
September | 0.00 | 0.00 | 434.67 | 24.55 | 0.00 | 24.55 |
October | 2.50 | 23.72 | 343.67 | 24.83 | 0.00 | 24.83 |
November | 23.00 | 23.88 | 268.67 | 24.87 | 0.00 | 24.87 |
December | 53.17 | 23.74 | 150.33 | 25.10 | 0.00 | 25.10 |
Annual Sum or Average | 245.33 | 23.66 | 3925.17 | 24.64 | 2.67 | 24.64 |
Minimum of Months | 0.00 | 0.00 | 150.33 | 24.43 | 0.00 | 24.43 |
Maximum of Months | 80.67 | 24.00 | 512.67 | 25.10 | 1.50 | 25.10 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 68.17 | 23.67 | 217.17 | 24.37 | 0.00 | 24.37 |
February | 51.67 | 23.72 | 201.67 | 24.30 | 0.00 | 24.30 |
March | 19.67 | 23.70 | 296.33 | 24.34 | 0.00 | 24.34 |
April | 9.50 | 23.75 | 398.50 | 24.26 | 0.00 | 24.26 |
May | 10.67 | 23.46 | 345.17 | 24.26 | 0.00 | 24.26 |
June | 0.00 | 0.00 | 472.67 | 24.25 | 0.00 | 24.25 |
July | 0.00 | 0.00 | 497.00 | 24.30 | 0.00 | 24.30 |
August | 0.00 | 0.00 | 514.00 | 24.28 | 0.00 | 24.28 |
September | 0.00 | 0.00 | 448.33 | 24.27 | 0.00 | 24.27 |
October | 12.50 | 23.85 | 331.33 | 24.40 | 0.00 | 24.40 |
November | 25.17 | 23.99 | 251.33 | 24.49 | 0.00 | 24.49 |
December | 42.17 | 23.91 | 166.00 | 24.55 | 0.00 | 24.55 |
Annual Sum or Average | 239.50 | 23.76 | 4139.50 | 24.32 | 0.00 | 24.32 |
Minimum of Months | 0.00 | 0.00 | 166.00 | 24.25 | 0.00 | 24.25 |
Maximum of Months | 68.17 | 23.99 | 514.00 | 24.55 | 0.00 | 24.55 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 240.33 | 23.37 | 103.00 | 23.58 | 12.83 | 23.56 |
February | 202.33 | 23.31 | 94.67 | 23.59 | 0.00 | 23.59 |
March | 179.33 | 23.31 | 146.33 | 23.70 | 0.00 | 23.70 |
April | 121.83 | 23.18 | 221.67 | 23.83 | 0.00 | 23.83 |
May | 108.17 | 23.28 | 231.17 | 23.91 | 0.00 | 23.91 |
June | 41.67 | 23.24 | 347.50 | 24.10 | 0.00 | 24.10 |
July | 4.67 | 23.24 | 405.17 | 24.13 | 0.00 | 24.13 |
August | 2.33 | 23.19 | 453.00 | 24.11 | 0.00 | 24.11 |
September | 36.00 | 23.28 | 356.33 | 24.08 | 0.00 | 24.08 |
October | 104.33 | 23.45 | 235.50 | 24.03 | 0.00 | 24.03 |
November | 182.33 | 23.47 | 154.83 | 23.86 | 0.00 | 23.86 |
December | 266.83 | 23.39 | 63.17 | 23.55 | 0.00 | 23.55 |
Annual Sum or Average | 1490.17 | 23.35 | 2812.33 | 23.89 | 12.83 | 23.89 |
Minimum of Months | 2.33 | 23.18 | 63.17 | 23.55 | 0.00 | 23.55 |
Maximum of Months | 266.83 | 23.47 | 453.00 | 24.13 | 12.83 | 24.13 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 393.50 | 22.23 | 73.00 | 22.25 | 30.50 | 22.11 |
February | 337.67 | 22.31 | 56.67 | 22.47 | 9.83 | 22.42 |
March | 343.83 | 22.50 | 85.33 | 22.80 | 0.00 | 22.80 |
April | 224.83 | 22.64 | 172.50 | 23.24 | 0.00 | 23.24 |
May | 207.50 | 22.72 | 192.50 | 23.36 | 0.00 | 23.36 |
June | 108.83 | 22.89 | 312.83 | 23.79 | 0.00 | 23.79 |
July | 67.00 | 22.97 | 386.17 | 23.94 | 0.00 | 23.94 |
August | 65.17 | 22.95 | 401.67 | 23.91 | 0.00 | 23.91 |
September | 137.67 | 22.87 | 253.00 | 23.64 | 0.00 | 23.64 |
October | 231.17 | 22.79 | 173.00 | 23.35 | 0.00 | 23.35 |
November | 348.17 | 22.56 | 71.50 | 22.75 | 7.83 | 22.71 |
December | 407.83 | 22.27 | 46.50 | 22.20 | 30.83 | 22.08 |
Annual Sum or Average | 2873.17 | 22.52 | 2224.67 | 23.14 | 79.00 | 23.09 |
Minimum of Months | 65.17 | 22.23 | 46.50 | 22.20 | 0.00 | 22.08 |
Maximum of Months | 407.83 | 22.97 | 401.67 | 23.94 | 30.83 | 23.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 416.50 | 22.22 | 36.17 | 22.31 | 7.67 | 22.28 |
February | 356.67 | 22.21 | 38.67 | 22.35 | 4.33 | 22.33 |
March | 348.00 | 22.22 | 85.50 | 22.58 | 0.83 | 22.57 |
April | 243.00 | 22.60 | 163.17 | 23.17 | 0.00 | 23.17 |
May | 219.83 | 22.66 | 187.00 | 23.31 | 0.00 | 23.31 |
June | 110.17 | 22.90 | 334.17 | 23.80 | 0.00 | 23.80 |
July | 40.50 | 22.92 | 414.67 | 24.07 | 0.00 | 24.07 |
August | 56.83 | 22.92 | 394.33 | 23.96 | 0.00 | 23.96 |
September | 161.00 | 22.75 | 257.17 | 23.55 | 0.00 | 23.55 |
October | 209.67 | 22.73 | 177.50 | 23.40 | 0.00 | 23.40 |
November | 346.33 | 22.47 | 53.50 | 22.68 | 1.17 | 22.67 |
December | 421.83 | 22.40 | 11.67 | 22.44 | 1.33 | 22.44 |
Annual Sum or Average | 2930.33 | 22.45 | 2153.50 | 23.14 | 15.33 | 23.14 |
Minimum of Months | 40.50 | 22.21 | 11.67 | 22.31 | 0.00 | 22.28 |
Maximum of Months | 421.83 | 22.92 | 414.67 | 24.07 | 7.67 | 24.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 377.00 | 21.79 | 71.50 | 22.13 | 7.83 | 22.10 |
February | 359.00 | 21.78 | 55.83 | 22.09 | 3.67 | 22.07 |
March | 339.33 | 21.70 | 121.83 | 22.34 | 7.67 | 22.35 |
April | 241.50 | 22.04 | 210.17 | 23.04 | 10.00 | 23.13 |
May | 262.17 | 22.10 | 195.33 | 23.05 | 8.83 | 23.12 |
June | 199.17 | 22.33 | 251.33 | 23.36 | 11.67 | 23.45 |
July | 143.50 | 22.93 | 336.83 | 23.83 | 24.50 | 23.99 |
August | 163.33 | 22.63 | 333.67 | 23.64 | 18.33 | 23.75 |
September | 216.17 | 22.17 | 235.83 | 23.17 | 9.00 | 23.24 |
October | 247.00 | 22.14 | 188.83 | 23.03 | 7.00 | 23.09 |
November | 360.50 | 21.96 | 63.33 | 22.29 | 3.50 | 22.29 |
December | 405.50 | 21.83 | 41.17 | 22.03 | 6.33 | 22.01 |
Annual Sum or Average | 3314.17 | 22.02 | 2105.67 | 22.85 | 118.33 | 22.91 |
Minimum of Months | 143.50 | 21.70 | 41.17 | 22.03 | 3.50 | 22.01 |
Maximum of Months | 405.50 | 22.93 | 336.83 | 23.83 | 24.50 | 23.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 256.00 | 22.26 | 234.00 | 23.24 | 26.17 | 23.33 |
February | 267.00 | 22.08 | 173.00 | 22.96 | 20.67 | 23.07 |
March | 308.33 | 21.97 | 176.83 | 22.78 | 13.83 | 22.85 |
April | 239.67 | 22.21 | 213.83 | 23.17 | 7.33 | 23.23 |
May | 288.50 | 22.05 | 156.67 | 22.79 | 0.00 | 22.79 |
June | 212.83 | 22.31 | 222.83 | 23.18 | 0.00 | 23.18 |
July | 132.33 | 22.48 | 313.17 | 23.61 | 3.17 | 23.63 |
August | 138.00 | 22.78 | 340.50 | 23.75 | 13.83 | 23.83 |
September | 189.33 | 22.85 | 278.33 | 23.72 | 25.33 | 23.86 |
October | 220.33 | 23.27 | 281.17 | 23.99 | 46.83 | 24.21 |
November | 242.33 | 22.63 | 230.00 | 23.52 | 26.67 | 23.67 |
December | 261.17 | 22.64 | 233.17 | 23.52 | 37.67 | 23.69 |
Annual Sum or Average | 2755.83 | 22.41 | 2853.50 | 23.36 | 221.50 | 23.46 |
Minimum of Months | 132.33 | 21.97 | 156.67 | 22.78 | 0.00 | 22.79 |
Maximum of Months | 308.33 | 23.27 | 340.50 | 23.99 | 46.83 | 24.21 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.67 | 21.77 | 94.83 | 22.25 | 1.83 | 22.25 |
February | 331.67 | 21.91 | 88.33 | 22.39 | 3.17 | 22.42 |
March | 317.67 | 22.00 | 143.33 | 22.68 | 8.17 | 22.74 |
April | 199.33 | 22.83 | 265.83 | 23.70 | 42.67 | 23.86 |
May | 254.00 | 22.37 | 199.33 | 23.22 | 18.17 | 23.36 |
June | 160.83 | 22.75 | 309.33 | 23.72 | 35.00 | 23.83 |
July | 113.83 | 24.39 | 421.00 | 24.36 | 78.33 | 24.48 |
August | 105.33 | 24.42 | 457.50 | 24.29 | 88.67 | 24.36 |
September | 184.17 | 22.52 | 273.67 | 23.52 | 25.00 | 23.64 |
October | 233.67 | 22.52 | 228.33 | 23.42 | 20.17 | 23.56 |
November | 299.50 | 22.17 | 141.50 | 22.87 | 5.33 | 22.91 |
December | 323.00 | 22.19 | 120.83 | 22.80 | 4.33 | 22.84 |
Annual Sum or Average | 2894.67 | 22.39 | 2743.83 | 23.31 | 330.83 | 23.43 |
Minimum of Months | 105.33 | 21.77 | 88.33 | 22.25 | 1.83 | 22.25 |
Maximum of Months | 371.67 | 24.42 | 457.50 | 24.36 | 88.67 | 24.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 473.33 | 21.44 | 101.50 | 21.28 | 92.17 | 21.14 |
February | 431.33 | 21.59 | 50.67 | 21.49 | 45.83 | 21.38 |
March | 456.67 | 21.68 | 69.33 | 21.69 | 40.83 | 21.58 |
April | 348.83 | 21.96 | 84.33 | 22.30 | 6.50 | 22.27 |
May | 319.33 | 22.22 | 111.33 | 22.68 | 0.67 | 22.68 |
June | 196.50 | 22.58 | 229.00 | 23.35 | 0.00 | 23.35 |
July | 137.83 | 22.72 | 298.00 | 23.62 | 0.00 | 23.62 |
August | 192.67 | 22.57 | 273.00 | 23.39 | 0.00 | 23.39 |
September | 270.50 | 22.35 | 166.17 | 22.97 | 0.00 | 22.97 |
October | 315.50 | 22.25 | 115.17 | 22.71 | 4.50 | 22.69 |
November | 463.50 | 21.81 | 44.83 | 21.73 | 38.83 | 21.63 |
December | 492.33 | 21.50 | 92.00 | 21.30 | 92.00 | 21.16 |
Annual Sum or Average | 4098.33 | 21.91 | 1635.33 | 22.30 | 321.33 | 22.19 |
Minimum of Months | 137.83 | 21.44 | 44.83 | 21.28 | 0.00 | 21.14 |
Maximum of Months | 492.33 | 22.72 | 298.00 | 23.62 | 92.17 | 23.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 378.33 | 21.50 | 61.67 | 21.50 | 40.67 | 21.39 |
February | 333.00 | 21.39 | 52.33 | 21.53 | 24.33 | 21.45 |
March | 337.17 | 21.41 | 84.33 | 21.72 | 25.83 | 21.65 |
April | 250.83 | 21.72 | 135.83 | 22.60 | 8.67 | 22.66 |
May | 268.17 | 21.80 | 130.00 | 22.69 | 6.50 | 22.75 |
June | 225.33 | 22.08 | 168.83 | 23.01 | 10.67 | 23.11 |
July | 181.83 | 22.67 | 239.00 | 23.61 | 24.17 | 23.79 |
August | 200.33 | 22.36 | 230.17 | 23.33 | 17.17 | 23.47 |
September | 239.33 | 21.91 | 149.17 | 22.76 | 7.83 | 22.84 |
October | 269.83 | 21.83 | 113.00 | 22.52 | 7.67 | 22.55 |
November | 359.33 | 21.59 | 44.67 | 21.73 | 17.83 | 21.68 |
December | 389.50 | 21.49 | 47.50 | 21.41 | 41.67 | 21.32 |
Annual Sum or Average | 3433.00 | 21.73 | 1456.50 | 22.36 | 233.00 | 22.37 |
Minimum of Months | 181.83 | 21.39 | 44.67 | 21.41 | 6.50 | 21.32 |
Maximum of Months | 389.50 | 22.67 | 239.00 | 23.61 | 41.67 | 23.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 271.67 | 22.04 | 241.50 | 22.97 | 46.67 | 22.98 |
February | 282.83 | 21.78 | 168.00 | 22.64 | 32.17 | 22.70 |
March | 343.00 | 21.67 | 172.67 | 22.32 | 36.83 | 22.29 |
April | 269.50 | 21.78 | 189.17 | 22.76 | 8.00 | 22.76 |
May | 337.00 | 21.82 | 123.83 | 22.43 | 2.00 | 22.42 |
June | 278.83 | 22.05 | 160.83 | 22.75 | 0.00 | 22.75 |
July | 220.50 | 22.26 | 234.67 | 23.17 | 1.17 | 23.18 |
August | 214.17 | 22.28 | 272.33 | 23.29 | 3.50 | 23.31 |
September | 231.50 | 22.59 | 256.17 | 23.51 | 25.33 | 23.65 |
October | 253.33 | 23.01 | 257.50 | 23.81 | 50.83 | 24.05 |
November | 255.50 | 22.21 | 225.50 | 23.23 | 30.17 | 23.34 |
December | 278.67 | 22.28 | 237.17 | 23.19 | 54.50 | 23.28 |
Annual Sum or Average | 3236.50 | 22.12 | 2539.33 | 23.01 | 291.17 | 23.08 |
Minimum of Months | 214.17 | 21.67 | 123.83 | 22.32 | 0.00 | 22.29 |
Maximum of Months | 343.00 | 23.01 | 272.33 | 23.81 | 54.50 | 24.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 429.83 | 21.25 | 108.83 | 21.39 | 61.50 | 21.28 |
February | 380.17 | 21.25 | 89.33 | 21.54 | 31.67 | 21.46 |
March | 424.50 | 21.34 | 105.33 | 21.69 | 31.17 | 21.63 |
April | 348.00 | 21.89 | 139.00 | 22.56 | 21.67 | 22.67 |
May | 353.17 | 21.92 | 137.67 | 22.61 | 14.17 | 22.71 |
June | 269.33 | 22.14 | 185.33 | 22.96 | 13.83 | 23.06 |
July | 222.67 | 22.57 | 242.83 | 23.46 | 33.67 | 23.65 |
August | 242.83 | 22.33 | 235.83 | 23.19 | 24.00 | 23.33 |
September | 306.00 | 22.12 | 163.67 | 22.86 | 13.50 | 22.96 |
October | 343.50 | 21.92 | 135.50 | 22.58 | 12.67 | 22.68 |
November | 390.83 | 21.39 | 103.67 | 21.75 | 27.83 | 21.67 |
December | 426.17 | 21.26 | 109.67 | 21.41 | 61.50 | 21.30 |
Annual Sum or Average | 4137.00 | 21.70 | 1756.67 | 22.30 | 347.17 | 22.32 |
Minimum of Months | 222.67 | 21.25 | 89.33 | 21.39 | 12.67 | 21.28 |
Maximum of Months | 429.83 | 22.57 | 242.83 | 23.46 | 61.50 | 23.65 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.83 | 20.94 | 162.17 | 20.65 | 159.83 | 20.47 |
February | 444.17 | 21.11 | 115.50 | 20.86 | 112.83 | 20.69 |
March | 473.67 | 21.25 | 114.83 | 21.12 | 98.00 | 20.96 |
April | 365.83 | 21.60 | 104.50 | 21.90 | 25.67 | 21.79 |
May | 344.50 | 21.80 | 116.83 | 22.28 | 8.83 | 22.23 |
June | 238.17 | 22.12 | 207.00 | 22.98 | 0.00 | 22.98 |
July | 194.00 | 22.34 | 270.00 | 23.32 | 0.00 | 23.32 |
August | 229.50 | 22.11 | 254.17 | 23.07 | 0.33 | 23.07 |
September | 301.67 | 21.89 | 146.17 | 22.53 | 2.50 | 22.52 |
October | 348.33 | 21.74 | 123.67 | 22.08 | 33.50 | 21.95 |
November | 481.17 | 21.30 | 117.33 | 21.07 | 114.50 | 20.90 |
December | 494.33 | 20.92 | 179.17 | 20.62 | 179.17 | 20.46 |
Annual Sum or Average | 4403.17 | 21.46 | 1911.33 | 21.75 | 735.17 | 21.55 |
Minimum of Months | 194.00 | 20.92 | 104.50 | 20.62 | 0.00 | 20.46 |
Maximum of Months | 494.33 | 22.34 | 270.00 | 23.32 | 179.17 | 23.32 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 465.83 | 21.26 | 111.83 | 21.10 | 95.00 | 20.93 |
February | 399.50 | 21.22 | 93.50 | 21.19 | 66.33 | 21.03 |
March | 406.67 | 21.28 | 136.17 | 21.48 | 66.17 | 21.32 |
April | 256.83 | 21.52 | 202.83 | 22.58 | 17.17 | 22.55 |
May | 289.17 | 21.61 | 181.67 | 22.63 | 7.67 | 22.66 |
June | 240.67 | 21.98 | 230.00 | 23.03 | 10.00 | 23.11 |
July | 177.67 | 22.61 | 327.17 | 23.67 | 25.50 | 23.82 |
August | 195.17 | 22.25 | 320.33 | 23.42 | 18.17 | 23.53 |
September | 251.17 | 21.73 | 213.17 | 22.78 | 6.83 | 22.83 |
October | 306.17 | 21.69 | 156.67 | 22.40 | 19.17 | 22.37 |
November | 446.00 | 21.46 | 71.67 | 21.38 | 59.50 | 21.25 |
December | 481.50 | 21.23 | 107.67 | 21.03 | 104.17 | 20.87 |
Annual Sum or Average | 3916.33 | 21.54 | 2152.67 | 22.18 | 495.67 | 22.09 |
Minimum of Months | 177.67 | 21.22 | 71.67 | 21.03 | 6.83 | 20.87 |
Maximum of Months | 481.50 | 22.61 | 327.17 | 23.67 | 104.17 | 23.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 296.67 | 21.56 | 251.83 | 22.36 | 76.83 | 22.22 |
February | 305.50 | 21.41 | 195.67 | 22.05 | 73.83 | 21.93 |
March | 370.50 | 21.39 | 199.50 | 21.86 | 78.50 | 21.73 |
April | 277.83 | 21.48 | 199.67 | 22.44 | 23.17 | 22.36 |
May | 345.00 | 21.54 | 140.83 | 22.14 | 17.33 | 22.06 |
June | 284.17 | 21.79 | 164.50 | 22.57 | 0.17 | 22.57 |
July | 229.17 | 22.00 | 245.17 | 23.04 | 3.00 | 23.06 |
August | 233.67 | 22.05 | 269.33 | 23.14 | 8.17 | 23.18 |
September | 247.50 | 22.21 | 244.67 | 23.23 | 26.17 | 23.36 |
October | 280.67 | 22.57 | 253.50 | 23.36 | 64.50 | 23.50 |
November | 280.17 | 21.78 | 232.33 | 22.69 | 56.67 | 22.67 |
December | 299.83 | 21.77 | 251.33 | 22.54 | 85.83 | 22.46 |
Annual Sum or Average | 3450.67 | 21.77 | 2648.33 | 22.61 | 514.17 | 22.57 |
Minimum of Months | 229.17 | 21.39 | 140.83 | 21.86 | 0.17 | 21.73 |
Maximum of Months | 370.50 | 22.57 | 269.33 | 23.36 | 85.83 | 23.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 434.67 | 20.99 | 160.00 | 21.02 | 113.50 | 20.85 |
February | 383.17 | 21.00 | 131.00 | 21.19 | 75.67 | 21.04 |
March | 428.83 | 21.13 | 146.00 | 21.40 | 73.00 | 21.28 |
April | 348.50 | 21.71 | 151.33 | 22.38 | 34.17 | 22.46 |
May | 355.67 | 21.73 | 146.67 | 22.44 | 21.17 | 22.52 |
June | 294.17 | 22.08 | 181.83 | 22.85 | 24.00 | 22.98 |
July | 262.00 | 22.59 | 235.33 | 23.36 | 49.33 | 23.57 |
August | 282.50 | 22.34 | 229.50 | 23.10 | 44.33 | 23.26 |
September | 308.83 | 21.89 | 162.00 | 22.68 | 16.67 | 22.79 |
October | 354.83 | 21.73 | 155.67 | 22.30 | 37.83 | 22.31 |
November | 394.83 | 21.15 | 140.50 | 21.42 | 67.50 | 21.28 |
December | 431.33 | 21.00 | 158.17 | 21.03 | 116.00 | 20.86 |
Annual Sum or Average | 4279.33 | 21.53 | 1998.00 | 22.05 | 673.17 | 22.01 |
Minimum of Months | 262.00 | 20.99 | 131.00 | 21.02 | 16.67 | 20.85 |
Maximum of Months | 434.67 | 22.59 | 235.33 | 23.36 | 116.00 | 23.57 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.17 | 27.00 | 502.00 | 27.00 | 22.17 | 27.00 |
February | 36.17 | 27.00 | 454.00 | 27.00 | 36.17 | 27.00 |
March | 89.17 | 27.00 | 514.00 | 27.00 | 89.17 | 27.00 |
April | 198.50 | 27.00 | 485.00 | 27.00 | 198.50 | 27.00 |
May | 64.50 | 27.00 | 508.00 | 27.00 | 64.50 | 27.00 |
June | 140.67 | 27.00 | 496.00 | 27.00 | 140.67 | 27.00 |
July | 262.67 | 27.00 | 497.00 | 27.00 | 262.67 | 27.00 |
August | 342.17 | 27.00 | 514.00 | 27.00 | 342.17 | 27.00 |
September | 95.33 | 27.00 | 485.00 | 27.00 | 95.33 | 27.00 |
October | 89.50 | 27.00 | 502.00 | 27.00 | 89.50 | 27.00 |
November | 81.33 | 27.00 | 489.00 | 27.00 | 81.33 | 27.00 |
December | 73.50 | 27.00 | 497.00 | 27.00 | 73.50 | 27.00 |
Annual Sum or Average | 1495.67 | 27.00 | 5943.00 | 27.00 | 1495.67 | 27.00 |
Minimum of Months | 22.17 | 27.00 | 454.00 | 27.00 | 22.17 | 27.00 |
Maximum of Months | 342.17 | 27.00 | 514.00 | 27.00 | 342.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 27.00 | 502.00 | 27.00 | 2.83 | 27.00 |
February | 12.17 | 27.00 | 454.00 | 27.00 | 12.17 | 27.00 |
March | 25.83 | 27.00 | 514.00 | 27.00 | 25.83 | 27.00 |
April | 63.00 | 27.00 | 485.00 | 27.00 | 63.00 | 27.00 |
May | 19.50 | 27.00 | 508.00 | 27.00 | 19.50 | 27.00 |
June | 65.83 | 27.00 | 496.00 | 27.00 | 65.83 | 27.00 |
July | 105.83 | 27.00 | 497.00 | 27.00 | 105.83 | 27.00 |
August | 125.83 | 27.00 | 514.00 | 27.00 | 125.83 | 27.00 |
September | 47.33 | 27.00 | 485.00 | 27.00 | 47.33 | 27.00 |
October | 23.83 | 27.00 | 502.00 | 27.00 | 23.83 | 27.00 |
November | 24.33 | 27.00 | 489.00 | 27.00 | 24.33 | 27.00 |
December | 10.83 | 27.00 | 497.00 | 27.00 | 10.83 | 27.00 |
Annual Sum or Average | 527.17 | 27.00 | 5943.00 | 27.00 | 527.17 | 27.00 |
Minimum of Months | 2.83 | 27.00 | 454.00 | 27.00 | 2.83 | 27.00 |
Maximum of Months | 125.83 | 27.00 | 514.00 | 27.00 | 125.83 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.17 | 26.60 | 469.33 | 26.99 | 6.00 | 26.99 |
February | 17.67 | 27.00 | 441.33 | 27.00 | 17.67 | 27.00 |
March | 42.33 | 27.00 | 512.17 | 27.00 | 42.33 | 27.00 |
April | 91.50 | 27.00 | 485.00 | 27.00 | 91.50 | 27.00 |
May | 62.83 | 27.00 | 508.00 | 27.00 | 62.83 | 27.00 |
June | 113.67 | 27.00 | 496.00 | 27.00 | 113.67 | 27.00 |
July | 164.83 | 27.00 | 497.00 | 27.00 | 164.83 | 27.00 |
August | 180.33 | 27.00 | 514.00 | 27.00 | 180.33 | 27.00 |
September | 77.00 | 27.00 | 485.00 | 27.00 | 77.00 | 27.00 |
October | 41.83 | 27.00 | 502.00 | 27.00 | 41.83 | 27.00 |
November | 27.00 | 27.00 | 474.83 | 27.00 | 27.00 | 27.00 |
December | 11.83 | 27.00 | 478.67 | 27.00 | 11.83 | 27.00 |
Annual Sum or Average | 845.00 | 26.99 | 5863.33 | 27.00 | 836.83 | 27.00 |
Minimum of Months | 11.83 | 26.60 | 441.33 | 26.99 | 6.00 | 26.99 |
Maximum of Months | 180.33 | 27.00 | 514.00 | 27.00 | 180.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 472.00 | 27.06 | 502.00 | 27.06 | 472.00 | 27.06 |
February | 114.50 | 26.93 | 451.50 | 25.65 | 114.50 | 25.86 |
March | 420.17 | 25.99 | 507.50 | 25.77 | 420.17 | 25.84 |
April | 388.67 | 26.34 | 485.00 | 25.98 | 388.67 | 26.09 |
May | 484.67 | 27.01 | 508.00 | 27.01 | 484.67 | 27.01 |
June | 242.67 | 26.47 | 495.50 | 25.94 | 242.67 | 26.07 |
July | 496.17 | 26.74 | 497.00 | 26.73 | 496.17 | 26.73 |
August | 514.00 | 26.84 | 514.00 | 26.84 | 514.00 | 26.84 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 306.83 | 26.61 | 501.83 | 26.17 | 306.83 | 26.29 |
November | 429.00 | 26.09 | 487.17 | 25.95 | 429.00 | 25.99 |
December | 329.00 | 26.29 | 497.00 | 25.69 | 329.00 | 25.86 |
Annual Sum or Average | 4682.67 | 26.63 | 5931.50 | 26.37 | 4682.67 | 26.45 |
Minimum of Months | 114.50 | 25.99 | 451.50 | 25.65 | 114.50 | 25.84 |
Maximum of Months | 514.00 | 27.06 | 514.00 | 27.06 | 514.00 | 27.06 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00004 | 33.29354 | 0.87901 | 21.47046 |
February | 454.00000 | 27.00002 | 34.46611 | 0.90903 | 22.61334 |
March | 514.00000 | 27.00000 | 35.86556 | 0.95901 | 24.56657 |
April | 485.00000 | 27.00016 | 36.25225 | 1.02109 | 27.13218 |
May | 508.00000 | 27.00014 | 37.99274 | 0.27610 | 6.80508 |
June | 496.00000 | 27.00011 | 38.74090 | 0.34501 | 7.66983 |
July | 497.00000 | 27.00006 | 38.85109 | 0.42787 | 8.97292 |
August | 514.00000 | 27.00038 | 37.79092 | 0.46801 | 9.72531 |
September | 485.00000 | 27.00033 | 39.22542 | 0.31099 | 7.21795 |
October | 502.00000 | 27.00007 | 34.97816 | 0.95901 | 24.54772 |
November | 489.00000 | 27.00000 | 32.90756 | 0.94670 | 24.11219 |
December | 497.00000 | 27.00002 | 30.17420 | 0.94136 | 23.85227 |
Annual Sum or Average | 5943.00000 | 27.00011 | 35.89084 | 0.70163 | 17.33461 |
Minimum of Months | 454.00000 | 27.00000 | 30.17420 | 0.27610 | 6.80508 |
Maximum of Months | 514.00000 | 27.00038 | 39.22542 | 1.02109 | 27.13218 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00004 | 33.31378 | 0.80351 | 18.82952 |
February | 454.00000 | 27.00002 | 34.48312 | 0.83334 | 19.85973 |
March | 514.00000 | 27.00001 | 35.87012 | 0.86790 | 21.08467 |
April | 485.00000 | 27.00016 | 36.31650 | 0.91931 | 23.02345 |
May | 508.00000 | 27.00014 | 38.05286 | 0.19079 | 6.04083 |
June | 496.00000 | 27.00011 | 38.78989 | 0.25573 | 6.61682 |
July | 497.00000 | 27.00005 | 38.93106 | 0.29748 | 7.08877 |
August | 514.00000 | 27.00039 | 37.88773 | 0.31279 | 7.30922 |
September | 485.00000 | 27.00033 | 39.36046 | 0.22704 | 6.34314 |
October | 502.00000 | 27.00008 | 35.01651 | 0.88956 | 21.86189 |
November | 489.00000 | 27.00000 | 32.90674 | 0.85204 | 20.55450 |
December | 497.00000 | 27.00002 | 30.19104 | 0.82515 | 19.54816 |
Annual Sum or Average | 5943.00000 | 27.00011 | 35.93938 | 0.60398 | 14.79405 |
Minimum of Months | 454.00000 | 27.00000 | 30.19104 | 0.19079 | 6.04083 |
Maximum of Months | 514.00000 | 27.00039 | 39.36046 | 0.91931 | 23.02345 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.98780 | 33.38330 | 0.74990 | 17.28401 |
February | 454.00000 | 27.00002 | 34.50493 | 0.78809 | 18.47114 |
March | 514.00000 | 27.00001 | 35.89040 | 0.83176 | 19.95765 |
April | 485.00000 | 27.00015 | 36.47342 | 0.90659 | 22.70413 |
May | 508.00000 | 27.00052 | 38.06286 | 0.17608 | 6.25830 |
June | 496.00000 | 27.00011 | 38.79131 | 0.25775 | 6.90836 |
July | 497.00000 | 27.00006 | 38.93129 | 0.31217 | 7.51706 |
August | 514.00000 | 27.00036 | 37.97361 | 0.32055 | 7.66252 |
September | 485.00000 | 27.00044 | 39.37413 | 0.21364 | 6.48995 |
October | 502.00000 | 27.00008 | 35.02390 | 0.86661 | 21.15071 |
November | 489.00000 | 27.00001 | 32.92868 | 0.80641 | 19.11046 |
December | 497.00000 | 27.00002 | 30.32971 | 0.77050 | 17.85662 |
Annual Sum or Average | 5943.00000 | 26.99912 | 35.98504 | 0.58129 | 14.23482 |
Minimum of Months | 454.00000 | 26.98780 | 30.32971 | 0.17608 | 6.25830 |
Maximum of Months | 514.00000 | 27.00052 | 39.37413 | 0.90659 | 22.70413 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.05766 | 32.54478 | 1.10493 | 30.78283 |
February | 454.00000 | 25.30170 | 35.22900 | 0.89168 | 22.49044 |
March | 514.00000 | 25.53862 | 37.00645 | 1.06267 | 29.73594 |
April | 485.00000 | 25.70006 | 39.95266 | 1.24793 | 38.63402 |
May | 508.00000 | 27.00562 | 36.82294 | 0.53537 | 11.10965 |
June | 496.00000 | 25.67332 | 44.19876 | 0.40928 | 9.96150 |
July | 497.00000 | 26.73036 | 47.02922 | 0.96334 | 24.98221 |
August | 514.00000 | 26.84352 | 48.27450 | 1.21116 | 36.15439 |
September | 485.00000 | 27.00037 | 44.91640 | 0.64032 | 13.72276 |
October | 502.00000 | 25.89207 | 39.63922 | 1.07704 | 30.24902 |
November | 489.00000 | 25.81071 | 33.36644 | 1.11186 | 31.65027 |
December | 497.00000 | 25.28301 | 30.57956 | 1.11470 | 32.49901 |
Annual Sum or Average | 5943.00000 | 26.16133 | 39.16248 | 0.94837 | 26.03720 |
Minimum of Months | 454.00000 | 25.28301 | 30.57956 | 0.40928 | 9.96150 |
Maximum of Months | 514.00000 | 27.05766 | 48.27450 | 1.24793 | 38.63402 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.33387 | 35.24243 | 0.43226 | 9.59892 |
February | 454.00000 | 24.29081 | 37.93982 | 0.43367 | 9.46107 |
March | 514.00000 | 24.25736 | 40.44948 | 0.44913 | 9.60262 |
April | 485.00000 | 24.34763 | 43.48226 | 0.49352 | 10.52194 |
May | 508.00000 | 24.29974 | 43.48527 | -0.3874 | 8.94141 |
June | 496.00000 | 24.38641 | 47.11077 | -0.3262 | 7.91675 |
July | 497.00000 | 24.58558 | 47.89249 | -0.2472 | 7.43616 |
August | 514.00000 | 24.45477 | 48.10722 | -0.2736 | 7.51079 |
September | 485.00000 | 24.47214 | 47.18533 | -0.2917 | 7.84823 |
October | 502.00000 | 24.55816 | 39.15363 | 0.52107 | 11.40373 |
November | 489.00000 | 24.49623 | 35.55702 | 0.47880 | 10.53613 |
December | 497.00000 | 24.37392 | 31.91817 | 0.42157 | 9.46555 |
Annual Sum or Average | 5943.00000 | 24.40500 | 41.48985 | 0.13895 | 9.18151 |
Minimum of Months | 454.00000 | 24.25736 | 31.91817 | -0.3874 | 7.43616 |
Maximum of Months | 514.00000 | 24.58558 | 48.10722 | 0.52107 | 11.40373 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.21475 | 36.80995 | 0.41399 | 8.99618 |
February | 454.00000 | 24.14491 | 39.00577 | 0.41294 | 8.84596 |
March | 514.00000 | 24.20100 | 41.88235 | 0.45439 | 9.56276 |
April | 485.00000 | 24.21706 | 45.39462 | 0.49827 | 10.43092 |
May | 508.00000 | 24.15665 | 45.19210 | -0.4047 | 8.77424 |
June | 496.00000 | 24.23128 | 51.07308 | -0.3246 | 7.60126 |
July | 497.00000 | 24.29954 | 54.09234 | -0.2588 | 6.78835 |
August | 514.00000 | 24.28343 | 54.69101 | -0.2448 | 6.64886 |
September | 485.00000 | 24.24290 | 52.12596 | -0.3149 | 7.46756 |
October | 502.00000 | 24.27132 | 42.28653 | 0.48963 | 10.38903 |
November | 489.00000 | 24.30777 | 36.91225 | 0.45199 | 9.76015 |
December | 497.00000 | 24.24553 | 31.89846 | 0.40175 | 8.70214 |
Annual Sum or Average | 5943.00000 | 24.23516 | 44.32586 | 0.12844 | 8.65893 |
Minimum of Months | 454.00000 | 24.14491 | 31.89846 | -0.4047 | 6.64886 |
Maximum of Months | 514.00000 | 24.30777 | 54.69101 | 0.49827 | 10.43092 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.73986 | 39.65955 | 0.28717 | 7.22362 |
February | 454.00000 | 23.73560 | 40.67661 | 0.29584 | 7.28501 |
March | 514.00000 | 23.81616 | 43.56430 | 0.33811 | 7.73816 |
April | 485.00000 | 23.84181 | 46.88217 | 0.38041 | 8.45152 |
May | 508.00000 | 23.91494 | 46.29169 | -0.5160 | 11.10223 |
June | 496.00000 | 24.01799 | 52.08568 | -0.4267 | 9.22954 |
July | 497.00000 | 24.03007 | 55.52252 | -0.3928 | 8.57019 |
August | 514.00000 | 24.04337 | 56.19648 | -0.3758 | 8.24291 |
September | 485.00000 | 24.00570 | 53.20040 | -0.4243 | 9.15893 |
October | 502.00000 | 24.00954 | 43.53484 | 0.40598 | 8.82620 |
November | 489.00000 | 23.90018 | 38.65440 | 0.32957 | 7.79576 |
December | 497.00000 | 23.72373 | 33.72230 | 0.24935 | 6.80019 |
Annual Sum or Average | 5943.00000 | 23.89947 | 45.87838 | 0.00970 | 8.37771 |
Minimum of Months | 454.00000 | 23.72373 | 33.72230 | -0.5160 | 6.80019 |
Maximum of Months | 514.00000 | 24.04337 | 56.19648 | 0.40598 | 11.10223 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.60160 | 40.76865 | -0.0046 | 7.24577 |
February | 454.00000 | 22.73034 | 43.30925 | 0.04996 | 6.85039 |
March | 514.00000 | 22.98580 | 45.77879 | 0.13684 | 6.91391 |
April | 485.00000 | 23.35242 | 48.23117 | 0.27298 | 7.78534 |
May | 508.00000 | 23.48500 | 47.46250 | -0.6468 | 15.69378 |
June | 496.00000 | 23.78370 | 52.81108 | -0.4828 | 10.89086 |
July | 497.00000 | 23.90097 | 56.02019 | -0.4041 | 9.08014 |
August | 514.00000 | 23.87116 | 56.98070 | -0.4064 | 9.08543 |
September | 485.00000 | 23.64391 | 54.58310 | -0.5329 | 12.12911 |
October | 502.00000 | 23.46120 | 45.17391 | 0.27709 | 7.80119 |
November | 489.00000 | 22.96617 | 41.01913 | 0.09726 | 6.85808 |
December | 497.00000 | 22.57507 | 36.43283 | -0.0352 | 6.99096 |
Annual Sum or Average | 5943.00000 | 23.28402 | 47.41740 | -0.1420 | 8.96198 |
Minimum of Months | 454.00000 | 22.57507 | 36.43283 | -0.6468 | 6.85039 |
Maximum of Months | 514.00000 | 23.90097 | 56.98070 | 0.27709 | 15.69378 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.52722 | 39.03672 | -0.0089 | 6.61928 |
February | 454.00000 | 22.58116 | 41.72721 | 0.02555 | 6.46073 |
March | 514.00000 | 22.77899 | 44.50255 | 0.09918 | 6.97611 |
April | 485.00000 | 23.27434 | 47.30073 | 0.26521 | 7.57984 |
May | 508.00000 | 23.41583 | 46.34064 | -0.6494 | 15.69420 |
June | 496.00000 | 23.79402 | 51.52999 | -0.4547 | 10.40095 |
July | 497.00000 | 24.02185 | 54.33365 | -0.3312 | 8.03119 |
August | 514.00000 | 23.89796 | 55.44427 | -0.3697 | 8.64728 |
September | 485.00000 | 23.56933 | 53.48066 | -0.5415 | 12.55824 |
October | 502.00000 | 23.49530 | 43.48035 | 0.29917 | 8.08734 |
November | 489.00000 | 22.91389 | 39.26786 | 0.09925 | 6.60372 |
December | 497.00000 | 22.63997 | 34.24751 | -0.0043 | 6.24771 |
Annual Sum or Average | 5943.00000 | 23.24738 | 45.92733 | -0.1328 | 8.67754 |
Minimum of Months | 454.00000 | 22.52722 | 34.24751 | -0.6494 | 6.24771 |
Maximum of Months | 514.00000 | 24.02185 | 55.44427 | 0.29917 | 15.69420 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.35241 | 38.92392 | 0.01782 | 7.14526 |
February | 454.00000 | 22.24030 | 42.05839 | 0.01055 | 7.04693 |
March | 514.00000 | 22.43812 | 44.81726 | 0.09079 | 8.02536 |
April | 485.00000 | 22.98943 | 47.77195 | 0.29553 | 9.72879 |
May | 508.00000 | 23.01862 | 47.09865 | -0.6603 | 19.17359 |
June | 496.00000 | 23.26214 | 52.90885 | -0.5093 | 15.06254 |
July | 497.00000 | 23.63337 | 55.34227 | -0.3173 | 11.73426 |
August | 514.00000 | 23.49374 | 56.45178 | -0.3545 | 12.21298 |
September | 485.00000 | 23.10238 | 54.59770 | -0.5690 | 16.38061 |
October | 502.00000 | 23.02838 | 44.44426 | 0.27176 | 8.70052 |
November | 489.00000 | 22.45867 | 39.73112 | 0.06359 | 7.01094 |
December | 497.00000 | 22.24439 | 34.38692 | -0.0286 | 6.79024 |
Annual Sum or Average | 5943.00000 | 22.85996 | 46.58249 | -0.1425 | 10.78002 |
Minimum of Months | 454.00000 | 22.24030 | 34.38692 | -0.6603 | 6.79024 |
Maximum of Months | 514.00000 | 23.63337 | 56.45178 | 0.29553 | 19.17359 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.20818 | 37.04782 | 0.28748 | 11.03398 |
February | 454.00000 | 22.91436 | 40.55120 | 0.20137 | 9.88665 |
March | 514.00000 | 22.78925 | 43.91078 | 0.17897 | 9.45733 |
April | 485.00000 | 23.15055 | 47.30984 | 0.30745 | 9.75854 |
May | 508.00000 | 22.88385 | 47.55521 | -0.7789 | 21.44476 |
June | 496.00000 | 23.20992 | 53.21994 | -0.6164 | 15.47921 |
July | 497.00000 | 23.57456 | 55.68143 | -0.4380 | 11.18173 |
August | 514.00000 | 23.64311 | 56.03183 | -0.3649 | 10.59960 |
September | 485.00000 | 23.55785 | 53.08934 | -0.4047 | 13.40758 |
October | 502.00000 | 23.71142 | 42.55189 | 0.47018 | 13.13940 |
November | 489.00000 | 23.38995 | 37.64840 | 0.34429 | 11.36009 |
December | 497.00000 | 23.37233 | 32.21216 | 0.31497 | 11.56556 |
Annual Sum or Average | 5943.00000 | 23.28520 | 45.61362 | -0.0446 | 12.38440 |
Minimum of Months | 454.00000 | 22.78925 | 32.21216 | -0.7789 | 9.45733 |
Maximum of Months | 514.00000 | 23.71142 | 56.03183 | 0.47018 | 21.44476 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.35870 | 38.64415 | 0.05659 | 7.48970 |
February | 454.00000 | 22.44582 | 41.19740 | 0.10665 | 7.69505 |
March | 514.00000 | 22.71764 | 43.85690 | 0.21190 | 8.71830 |
April | 485.00000 | 23.47300 | 46.16352 | 0.47417 | 12.60724 |
May | 508.00000 | 23.10627 | 46.62964 | -0.5656 | 17.27203 |
June | 496.00000 | 23.53086 | 51.91877 | -0.3406 | 11.87628 |
July | 497.00000 | 24.07038 | 53.84261 | -0.0828 | 9.15201 |
August | 514.00000 | 24.07896 | 54.37737 | -0.0565 | 8.37610 |
September | 485.00000 | 23.35127 | 53.62436 | -0.4120 | 13.38547 |
October | 502.00000 | 23.28316 | 43.38961 | 0.37809 | 10.77806 |
November | 489.00000 | 22.89768 | 38.39056 | 0.22321 | 8.60359 |
December | 497.00000 | 22.85956 | 32.83892 | 0.17544 | 7.99528 |
Annual Sum or Average | 5943.00000 | 23.18632 | 45.44294 | 0.01271 | 10.34009 |
Minimum of Months | 454.00000 | 22.35870 | 32.83892 | -0.5656 | 7.48970 |
Maximum of Months | 514.00000 | 24.07896 | 54.37737 | 0.47417 | 17.27203 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.57838 | 40.96701 | -0.2610 | 8.51067 |
February | 454.00000 | 21.69807 | 44.03952 | -0.2064 | 7.67357 |
March | 514.00000 | 21.91997 | 46.93971 | -0.1314 | 7.42439 |
April | 485.00000 | 22.50525 | 49.72777 | 0.05797 | 6.92407 |
May | 508.00000 | 22.86318 | 48.08922 | -0.8608 | 23.42369 |
June | 496.00000 | 23.39188 | 53.02850 | -0.6170 | 14.83934 |
July | 497.00000 | 23.60402 | 56.28293 | -0.5067 | 11.74852 |
August | 514.00000 | 23.39679 | 57.99226 | -0.5738 | 13.61605 |
September | 485.00000 | 23.03651 | 55.49979 | -0.7430 | 18.98468 |
October | 502.00000 | 22.91166 | 45.32230 | 0.14205 | 7.31976 |
November | 489.00000 | 21.91740 | 41.75297 | -0.1578 | 7.33797 |
December | 497.00000 | 21.52010 | 36.42553 | -0.2974 | 8.44908 |
Annual Sum or Average | 5943.00000 | 22.53519 | 48.04078 | -0.3480 | 11.39109 |
Minimum of Months | 454.00000 | 21.52010 | 36.42553 | -0.8608 | 6.92407 |
Maximum of Months | 514.00000 | 23.60402 | 57.99226 | 0.14205 | 23.42369 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.76362 | 40.27115 | -0.1614 | 7.76771 |
February | 385.00000 | 21.74288 | 43.46836 | -0.1447 | 7.67156 |
March | 433.00000 | 21.95025 | 45.89691 | -0.0647 | 8.16964 |
April | 410.00000 | 22.60687 | 48.87464 | 0.16934 | 9.03095 |
May | 430.00000 | 22.68681 | 48.11202 | -0.8123 | 24.88962 |
June | 418.00000 | 22.91773 | 54.05140 | -0.6575 | 19.83475 |
July | 422.00000 | 23.38129 | 56.58461 | -0.4384 | 15.20105 |
August | 433.00000 | 23.16439 | 58.21086 | -0.4997 | 16.22643 |
September | 410.00000 | 22.70896 | 56.04125 | -0.7372 | 21.81446 |
October | 427.00000 | 22.60419 | 46.21596 | 0.14732 | 8.02853 |
November | 417.00000 | 21.91884 | 41.34132 | -0.0975 | 7.28618 |
December | 422.00000 | 21.67316 | 35.51000 | -0.2046 | 7.73915 |
Annual Sum or Average | 5034.00000 | 22.43112 | 47.90314 | -0.2930 | 12.83695 |
Minimum of Months | 385.00000 | 21.67316 | 35.51000 | -0.8123 | 7.28618 |
Maximum of Months | 433.00000 | 23.38129 | 58.21086 | 0.16934 | 24.88962 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.02251 | 37.33578 | 0.23213 | 11.45936 |
February | 454.00000 | 22.66797 | 41.36112 | 0.12817 | 10.31102 |
March | 514.00000 | 22.45366 | 44.91286 | 0.07860 | 9.65194 |
April | 485.00000 | 22.81864 | 48.36385 | 0.20495 | 9.29584 |
May | 508.00000 | 22.54676 | 48.60941 | -0.9191 | 26.85557 |
June | 496.00000 | 22.82218 | 54.59357 | -0.7665 | 20.42351 |
July | 497.00000 | 23.16956 | 57.48805 | -0.5992 | 15.55983 |
August | 514.00000 | 23.26223 | 57.93878 | -0.5177 | 14.51557 |
September | 485.00000 | 23.34492 | 53.92370 | -0.4912 | 16.25336 |
October | 502.00000 | 23.52399 | 43.26127 | 0.41711 | 13.00459 |
November | 489.00000 | 23.15396 | 38.41873 | 0.27620 | 11.50556 |
December | 497.00000 | 23.13506 | 32.66214 | 0.24311 | 11.98548 |
Annual Sum or Average | 5943.00000 | 22.99413 | 46.62229 | -0.1463 | 14.27974 |
Minimum of Months | 454.00000 | 22.45366 | 32.66214 | -0.9191 | 9.29584 |
Maximum of Months | 514.00000 | 23.52399 | 57.93878 | 0.41711 | 26.85557 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.62040 | 40.22864 | -0.1796 | 8.39996 |
February | 454.00000 | 21.69617 | 43.26701 | -0.1318 | 8.18036 |
March | 514.00000 | 21.79748 | 46.51976 | -0.0751 | 8.30312 |
April | 485.00000 | 22.47045 | 49.11665 | 0.16694 | 9.60505 |
May | 508.00000 | 22.54403 | 48.32837 | -0.8208 | 25.83114 |
June | 496.00000 | 22.89290 | 54.05775 | -0.6140 | 18.80883 |
July | 497.00000 | 23.23266 | 57.04689 | -0.4444 | 15.43261 |
August | 514.00000 | 23.05152 | 58.47549 | -0.4959 | 16.01996 |
September | 485.00000 | 22.76396 | 55.71178 | -0.6659 | 20.43900 |
October | 502.00000 | 22.54099 | 45.60921 | 0.15650 | 8.90197 |
November | 489.00000 | 21.91369 | 40.91192 | -0.0750 | 8.11819 |
December | 497.00000 | 21.64105 | 35.27865 | -0.1924 | 8.42669 |
Annual Sum or Average | 5943.00000 | 22.35158 | 47.92165 | -0.2830 | 13.08298 |
Minimum of Months | 454.00000 | 21.62040 | 35.27865 | -0.8208 | 8.11819 |
Maximum of Months | 514.00000 | 23.23266 | 58.47549 | 0.16694 | 25.83114 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.02150 | 42.19465 | -0.4157 | 11.55381 |
February | 454.00000 | 21.16502 | 45.21064 | -0.3509 | 10.08146 |
March | 514.00000 | 21.44634 | 48.00379 | -0.2560 | 9.07615 |
April | 485.00000 | 22.14921 | 50.54322 | -0.0232 | 7.72530 |
May | 508.00000 | 22.47643 | 48.96130 | -0.9788 | 29.06953 |
June | 496.00000 | 23.03490 | 54.07601 | -0.7095 | 18.93684 |
July | 497.00000 | 23.31955 | 57.35050 | -0.5663 | 14.49479 |
August | 514.00000 | 23.08269 | 59.27621 | -0.6471 | 16.97506 |
September | 485.00000 | 22.62222 | 56.92002 | -0.8640 | 24.35345 |
October | 502.00000 | 22.41710 | 46.62497 | 0.02816 | 7.94547 |
November | 489.00000 | 21.33443 | 42.87947 | -0.3123 | 9.45483 |
December | 497.00000 | 20.93150 | 37.61766 | -0.4608 | 11.92419 |
Annual Sum or Average | 5943.00000 | 22.09083 | 49.17314 | -0.4645 | 14.34087 |
Minimum of Months | 454.00000 | 20.93150 | 37.61766 | -0.9788 | 7.72530 |
Maximum of Months | 514.00000 | 23.31955 | 59.27621 | 0.02816 | 29.06953 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.42769 | 40.88504 | -0.2599 | 9.17633 |
February | 454.00000 | 21.51982 | 44.08650 | -0.2178 | 8.78995 |
March | 514.00000 | 21.80439 | 46.61699 | -0.1109 | 8.94188 |
April | 485.00000 | 22.67013 | 48.75974 | 0.18718 | 9.79043 |
May | 508.00000 | 22.67703 | 48.12458 | -0.8100 | 25.37519 |
June | 496.00000 | 22.97064 | 53.93545 | -0.6178 | 19.29445 |
July | 497.00000 | 23.47874 | 56.43194 | -0.3708 | 14.09674 |
August | 514.00000 | 23.28299 | 58.01635 | -0.4286 | 15.10787 |
September | 485.00000 | 22.74993 | 56.08571 | -0.7124 | 21.78964 |
October | 502.00000 | 22.55028 | 46.16547 | 0.13001 | 8.45570 |
November | 489.00000 | 21.65382 | 41.83432 | -0.1801 | 8.01282 |
December | 497.00000 | 21.31137 | 36.42610 | -0.3120 | 9.23451 |
Annual Sum or Average | 5943.00000 | 22.34786 | 48.14957 | -0.3099 | 13.20787 |
Minimum of Months | 454.00000 | 21.31137 | 36.42610 | -0.8100 | 8.01282 |
Maximum of Months | 514.00000 | 23.47874 | 58.01635 | 0.18718 | 25.37519 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.61609 | 38.33948 | 0.10676 | 12.06717 |
February | 454.00000 | 22.30653 | 42.30935 | 0.01603 | 11.17431 |
March | 514.00000 | 22.10913 | 45.82153 | -0.0217 | 10.65588 |
April | 485.00000 | 22.59120 | 48.98805 | 0.14784 | 10.02442 |
May | 508.00000 | 22.32492 | 49.17009 | -0.9941 | 30.85668 |
June | 496.00000 | 22.64107 | 55.16315 | -0.8120 | 23.11033 |
July | 497.00000 | 23.02193 | 58.18254 | -0.6218 | 17.50845 |
August | 514.00000 | 23.08493 | 58.87937 | -0.5548 | 16.93564 |
September | 485.00000 | 23.09043 | 54.95342 | -0.5706 | 19.77802 |
October | 502.00000 | 23.20703 | 44.24777 | 0.33614 | 12.94359 |
November | 489.00000 | 22.79588 | 39.26613 | 0.16529 | 11.80854 |
December | 497.00000 | 22.72987 | 33.62424 | 0.11526 | 12.35524 |
Annual Sum or Average | 5943.00000 | 22.71118 | 47.46147 | -0.2272 | 15.82018 |
Minimum of Months | 454.00000 | 22.10913 | 33.62424 | -0.9941 | 10.02442 |
Maximum of Months | 514.00000 | 23.20703 | 58.87937 | 0.33614 | 30.85668 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.37321 | 40.92452 | -0.2654 | 10.25186 |
February | 454.00000 | 21.46965 | 43.92705 | -0.2096 | 9.63355 |
March | 514.00000 | 21.59674 | 47.07839 | -0.1411 | 9.47926 |
April | 485.00000 | 22.32806 | 49.53401 | 0.12946 | 10.33427 |
May | 508.00000 | 22.39139 | 48.74196 | -0.8728 | 28.99036 |
June | 496.00000 | 22.75277 | 54.54563 | -0.6479 | 21.02856 |
July | 497.00000 | 23.11394 | 57.67039 | -0.4598 | 17.09093 |
August | 514.00000 | 22.92666 | 59.24606 | -0.5185 | 17.83739 |
September | 485.00000 | 22.58440 | 56.51507 | -0.7208 | 23.33465 |
October | 502.00000 | 22.34391 | 46.30765 | 0.10308 | 9.39346 |
November | 489.00000 | 21.68546 | 41.47585 | -0.1535 | 9.36362 |
December | 497.00000 | 21.37607 | 36.03515 | -0.2840 | 10.30130 |
Annual Sum or Average | 5943.00000 | 22.16670 | 48.54230 | -0.3386 | 14.79990 |
Minimum of Months | 454.00000 | 21.37321 | 36.03515 | -0.8728 | 9.36362 |
Maximum of Months | 514.00000 | 23.11394 | 59.24606 | 0.12946 | 28.99036 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.638945E+11 | 228746.31 | 24-JAN-15:00 | 274.36 | 0.363038E+12 | 0.00 | 0.426932E+12 | 1.89 | 7.09 | 24-JAN-15:50 | 0.00 | 0.00 |
February | 0.667474E+11 | 217573.22 | 01-FEB-13:07 | 286.08 | 0.341818E+12 | 0.00 | 0.408565E+12 | 2.07 | 7.01 | 03-FEB-15:03 | 0.00 | 0.00 |
March | 0.905104E+11 | 223841.35 | 22-MAR-12:30 | 685.15 | 0.474882E+12 | 0.00 | 0.565392E+12 | 4.50 | 7.01 | 10-MAR-11:30 | 0.00 | 0.00 |
April | 0.126793E+12 | 230611.52 | 12-APR-13:00 | 649.34 | 0.701834E+12 | 0.00 | 0.828627E+12 | 4.55 | 7.02 | 30-APR-09:22 | 0.00 | 0.00 |
May | 0.842821E+11 | 222725.76 | 03-MAY-12:20 | 372.51 | 0.454470E+12 | 0.00 | 0.538752E+12 | 2.52 | 7.08 | 03-MAY-13:05 | 0.00 | 0.00 |
June | 0.166755E+12 | 220815.45 | 30-JUN-11:30 | 491.10 | 0.962690E+12 | 0.00 | 0.112945E+13 | 3.70 | 7.03 | 18-JUN-17:12 | 0.00 | 0.00 |
July | 0.217738E+12 | 220919.51 | 25-JUL-08:00 | 647.48 | 0.133567E+13 | 0.00 | 0.155341E+13 | 4.90 | 7.09 | 28-JUL-04:12 | 0.00 | 0.00 |
August | 0.235842E+12 | 231674.86 | 07-AUG-07:15 | 678.70 | 0.148407E+13 | 0.00 | 0.171992E+13 | 5.22 | 7.16 | 09-AUG-04:13 | 0.00 | 0.00 |
September | 0.140138E+12 | 228786.17 | 30-SEP-15:10 | 439.25 | 0.839391E+12 | 0.00 | 0.979529E+12 | 3.35 | 7.17 | 30-SEP-04:02 | 0.00 | 0.00 |
October | 0.184634E+12 | 232353.77 | 05-OCT-08:45 | 508.61 | 0.112207E+13 | 0.00 | 0.130671E+13 | 3.86 | 7.15 | 04-OCT-04:13 | 0.00 | 0.00 |
November | 0.112981E+12 | 222440.39 | 28-NOV-14:08 | 667.85 | 0.620128E+12 | 0.00 | 0.733109E+12 | 4.63 | 7.09 | 08-NOV-11:40 | 0.00 | 0.00 |
December | 0.118708E+12 | 218279.26 | 19-DEC-12:07 | 654.48 | 0.668481E+12 | 0.00 | 0.787189E+12 | 4.45 | 7.06 | 25-DEC-11:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.160902E+13 | 6354.91 | 0.936855E+13 | 0.00 | 0.109776E+14 | 3.82 | 0.00 | 0.00 | ||||
Minimum of Months | 0.638945E+11 | 217573.22 | 274.36 | 0.341818E+12 | 0.00 | 0.408565E+12 | 1.89 | 7.01 | 0.00 | 0.00 | ||
Maximum of Months | 0.235842E+12 | 232353.77 | 685.15 | 0.148407E+13 | 0.00 | 0.171992E+13 | 5.22 | 7.17 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.323962E+09 | 169327.40 | 18-JAN-14:02 | 0.89 | 0.213633E+10 | 0.00 | 0.246030E+10 | 0.01 | 7.00 | 18-JAN-14:02 | 0.00 | 0.00 |
February | 0.253354E+09 | 136755.20 | 01-FEB-11:50 | 0.83 | 0.158779E+10 | 0.00 | 0.184115E+10 | 0.01 | 6.72 | 01-FEB-11:50 | 0.00 | 0.00 |
March | 0.906626E+09 | 139310.74 | 23-MAR-14:05 | 1.97 | 0.585699E+10 | 0.00 | 0.676362E+10 | 0.02 | 6.73 | 23-MAR-14:05 | 0.00 | 0.00 |
April | 0.351396E+10 | 154105.49 | 12-APR-14:05 | 7.25 | 0.230473E+11 | 0.00 | 0.265613E+11 | 0.07 | 6.92 | 12-APR-14:05 | 0.00 | 0.00 |
May | 93800193.40 | 124640.92 | 03-MAY-12:40 | 0.50 | 0.574102E+09 | 0.00 | 0.667902E+09 | 0.00 | 6.41 | 03-MAY-12:40 | 0.00 | 0.00 |
June | 0.114232E+11 | 162219.08 | 27-JUN-12:05 | 24.50 | 0.737095E+11 | 0.00 | 0.851327E+11 | 0.22 | 6.81 | 27-JUN-12:05 | 0.00 | 0.00 |
July | 0.515747E+11 | 170974.35 | 25-JUL-15:40 | 102.68 | 0.336943E+12 | 0.00 | 0.388517E+12 | 0.90 | 6.88 | 23-JUL-07:55 | 0.00 | 0.00 |
August | 0.822800E+11 | 192984.61 | 15-AUG-16:00 | 156.90 | 0.543994E+12 | 0.00 | 0.626274E+12 | 1.39 | 6.93 | 29-AUG-12:05 | 0.00 | 0.00 |
September | 0.187029E+11 | 160839.75 | 05-SEP-13:10 | 39.29 | 0.121583E+12 | 0.00 | 0.140285E+12 | 0.35 | 6.91 | 29-SEP-10:05 | 0.00 | 0.00 |
October | 0.360396E+11 | 203442.39 | 30-OCT-13:02 | 73.12 | 0.237528E+12 | 0.00 | 0.273567E+12 | 0.64 | 6.96 | 30-OCT-12:35 | 0.00 | 0.00 |
November | 0.126696E+10 | 179253.76 | 28-NOV-12:02 | 2.70 | 0.820401E+10 | 0.00 | 0.947097E+10 | 0.02 | 7.01 | 28-NOV-12:02 | 0.00 | 0.00 |
December | 0.633010E+10 | 174694.62 | 19-DEC-14:04 | 13.56 | 0.413483E+11 | 0.00 | 0.476784E+11 | 0.12 | 7.01 | 19-DEC-14:04 | 0.00 | 0.00 |
Annual Sum or Average | 0.212709E+12 | 424.19 | 0.139651E+13 | 0.00 | 0.160922E+13 | 0.32 | 0.00 | 0.00 | ||||
Minimum of Months | 93800193.40 | 124640.92 | 0.50 | 0.574102E+09 | 0.00 | 0.667902E+09 | 0.00 | 6.41 | 0.00 | 0.00 | ||
Maximum of Months | 0.822800E+11 | 203442.39 | 156.90 | 0.543994E+12 | 0.00 | 0.626274E+12 | 1.39 | 7.01 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.258593E+10 | 195.78 | 24044.05 | 17-JAN-12:00 | 1781416.41 | 24-JAN-15:00 | 21.68 | 21.17 | 25.26 |
February | 0.150490E+10 | 265.58 | 20436.06 | 01-FEB-13:10 | 1728972.25 | 01-FEB-13:10 | 22.23 | 21.68 | 33.10 |
March | 0.263628E+10 | 282.75 | 24044.05 | 22-MAR-12:05 | 1668229.95 | 23-MAR-13:00 | 21.73 | 21.02 | 66.42 |
April | 0.657739E+10 | 465.82 | 24044.05 | 04-APR-11:40 | 1784265.35 | 12-APR-13:00 | 22.18 | 21.13 | 68.99 |
May | 0.427151E+10 | 303.65 | 24044.05 | 03-MAY-12:20 | 1735994.38 | 03-MAY-12:20 | 21.87 | 21.21 | 36.58 |
June | 0.140569E+11 | 486.98 | 24044.05 | 14-JUN-09:50 | 1650660.74 | 15-JUN-15:10 | 22.98 | 21.60 | 53.32 |
July | 0.275091E+11 | 641.93 | 24044.05 | 01-JUL-10:20 | 1638272.32 | 14-JUL-09:10 | 23.41 | 21.58 | 67.86 |
August | 0.323305E+11 | 614.83 | 24044.05 | 01-AUG-10:05 | 1715339.45 | 29-AUG-11:50 | 23.76 | 21.73 | 69.34 |
September | 0.152875E+11 | 392.79 | 24044.05 | 05-SEP-12:15 | 1730575.11 | 30-SEP-15:10 | 22.53 | 21.32 | 46.00 |
October | 0.169988E+11 | 492.06 | 24044.05 | 01-OCT-07:02 | 1777847.37 | 19-OCT-12:00 | 23.22 | 21.63 | 53.32 |
November | 0.314407E+10 | 361.85 | 24044.05 | 10-NOV-12:40 | 1719718.09 | 30-NOV-14:00 | 21.97 | 21.04 | 67.09 |
December | 0.244868E+10 | 350.66 | 21042.21 | 07-DEC-14:20 | 1723162.31 | 27-DEC-14:40 | 22.02 | 21.03 | 62.85 |
Annual Sum or Average | 0.129352E+12 | 4854.68 | 22.47 | 21.34 | 54.30 | ||||
Minimum of Months | 0.150490E+10 | 195.78 | 20436.06 | 1638272.32 | 21.68 | 21.02 | 25.26 | ||
Maximum of Months | 0.323305E+11 | 641.93 | 24044.05 | 1784265.35 | 23.76 | 21.73 | 69.34 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 34845840.66 | 0.64 | 18339.50 | 13-JAN-13:30 | 1533140.99 | 18-JAN-14:02 | 21.68 | 21.68 | 0.07 |
February | 28619433.61 | 0.58 | 16339.18 | 01-FEB-11:50 | 1514973.15 | 01-FEB-11:50 | 22.23 | 22.22 | 0.07 |
March | 0.127433E+09 | 1.47 | 24044.05 | 22-MAR-12:50 | 1378380.39 | 23-MAR-13:30 | 21.73 | 21.72 | 0.15 |
April | 0.478330E+09 | 5.67 | 24044.05 | 04-APR-14:10 | 1446260.01 | 26-APR-14:50 | 22.18 | 22.15 | 0.62 |
May | 9662011.66 | 0.17 | 16103.35 | 03-MAY-12:40 | 1385816.91 | 03-MAY-12:40 | 21.87 | 21.87 | 0.02 |
June | 0.192538E+10 | 22.25 | 24044.05 | 19-JUN-11:05 | 1384001.96 | 21-JUN-13:00 | 22.98 | 22.88 | 2.42 |
July | 0.908735E+10 | 104.98 | 24044.05 | 03-JUL-12:00 | 1351643.46 | 25-JUL-15:40 | 23.41 | 22.93 | 10.85 |
August | 0.135775E+11 | 156.86 | 24044.05 | 02-AUG-09:40 | 1465045.45 | 15-AUG-16:00 | 23.76 | 23.00 | 16.28 |
September | 0.308464E+10 | 35.98 | 24044.05 | 05-SEP-13:00 | 1483055.88 | 29-SEP-09:00 | 22.53 | 22.35 | 3.83 |
October | 0.491794E+10 | 64.85 | 24044.05 | 01-OCT-10:41 | 1610781.28 | 17-OCT-15:00 | 23.22 | 22.88 | 6.80 |
November | 31603896.94 | 1.53 | 6612.91 | 28-NOV-14:00 | 1475292.25 | 28-NOV-12:40 | 21.97 | 21.97 | 0.17 |
December | 0.313440E+09 | 11.61 | 11319.81 | 16-DEC-13:35 | 1540848.78 | 29-DEC-11:50 | 22.02 | 21.95 | 1.22 |
Annual Sum or Average | 0.336167E+11 | 406.60 | 22.47 | 22.30 | 3.59 | ||||
Minimum of Months | 9662011.66 | 0.17 | 6612.91 | 1351643.46 | 21.68 | 21.68 | 0.02 | ||
Maximum of Months | 0.135775E+11 | 156.86 | 24044.05 | 1610781.28 | 23.76 | 23.00 | 16.28 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.794557E+11 | 0.00 | 281.24 | 1655040.24 | 27-JAN-05:11 | 0.00 | 26.02 | 41.02 | 0.21 | 0.00 | 0.01 | 0.78 | 27-JAN-05:11 |
February | 0.669343E+11 | 0.00 | 234.99 | 1584082.91 | 06-FEB-05:11 | 0.00 | 24.66 | 38.61 | 0.19 | 0.00 | 0.01 | 0.75 | 06-FEB-05:11 |
March | 0.787227E+11 | 0.00 | 262.16 | 1641901.99 | 10-MAR-05:11 | 0.00 | 25.10 | 39.14 | 0.20 | 0.00 | 0.01 | 0.77 | 10-MAR-05:11 |
April | 0.302373E+11 | 0.00 | 156.61 | 1519124.99 | 01-APR-04:11 | 0.00 | 22.97 | 31.97 | 0.07 | 0.00 | 0.01 | 0.72 | 01-APR-04:11 |
May | 0.230591E+11 | 0.00 | 147.09 | 1346205.63 | 27-MAY-05:01 | 0.00 | 22.64 | 30.93 | 0.05 | 0.00 | 0.00 | 0.63 | 27-MAY-05:01 |
June | 0.633148E+10 | 0.00 | 93.15 | 417998.66 | 01-JUN-05:02 | 0.00 | 20.75 | 26.50 | 0.01 | 0.00 | 0.00 | 0.20 | 01-JUN-05:02 |
July | 0.173839E+10 | 0.00 | 60.28 | 128476.78 | 06-JUL-05:04 | 0.00 | 19.91 | 23.60 | 0.00 | 0.00 | 0.00 | 0.06 | 06-JUL-05:04 |
August | 0.251452E+10 | 0.00 | 71.12 | 92877.24 | 23-AUG-05:10 | 0.00 | 19.87 | 24.23 | 0.00 | 0.00 | 0.00 | 0.04 | 23-AUG-05:10 |
September | 0.841678E+10 | 0.00 | 110.08 | 398653.13 | 20-SEP-05:03 | 0.00 | 21.19 | 27.92 | 0.02 | 0.00 | 0.00 | 0.19 | 20-SEP-05:03 |
October | 0.169521E+11 | 0.00 | 141.67 | 1441463.59 | 12-OCT-05:01 | 0.00 | 22.23 | 30.26 | 0.04 | 0.00 | 0.00 | 0.68 | 12-OCT-05:01 |
November | 0.460912E+11 | 0.00 | 229.66 | 1606219.36 | 30-NOV-05:11 | 0.00 | 24.07 | 36.89 | 0.12 | 0.00 | 0.01 | 0.76 | 30-NOV-05:11 |
December | 0.684801E+11 | 0.00 | 273.94 | 1624019.90 | 21-DEC-05:11 | 0.00 | 24.59 | 39.28 | 0.17 | 0.00 | 0.01 | 0.77 | 21-DEC-05:11 |
Annual Sum or Average | 0.428934E+12 | 0.00 | 2062.00 | 0.00 | 22.83 | 32.50 | 0.09 | 0.00 | 0.01 | ||||
Minimum of Months | 0.173839E+10 | 0.00 | 60.28 | 92877.24 | 0.00 | 19.87 | 23.60 | 0.00 | 0.00 | 0.00 | 0.04 | ||
Maximum of Months | 0.794557E+11 | 0.00 | 281.24 | 1655040.24 | 0.00 | 26.02 | 41.02 | 0.21 | 0.00 | 0.01 | 0.78 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.287911E+11 | 0.00 | 233.50 | 0.287100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122821.80 | 18-JAN-14:04 | 122821.80 | 18-JAN-14:04 | 0.00 | 0.00 | 0.00 |
February | 0.158245E+11 | 0.00 | 180.33 | 0.156789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110011.21 | 01-FEB-12:00 | 110011.21 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.190220E+11 | 0.00 | 183.54 | 0.185873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122476.07 | 23-MAR-14:00 | 107176.12 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.410494E+11 | 0.00 | 296.03 | 0.409590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 139966.80 | 26-APR-13:40 | 137101.68 | 26-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.389289E+11 | 0.00 | 345.75 | 0.387976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108259.49 | 03-MAY-13:10 | 108259.49 | 03-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.677300E+11 | 0.00 | 417.70 | 0.613844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 157448.77 | 30-JUN-04:12 | 108900.66 | 27-JUN-13:10 | 0.00 | 0.00 | 0.00 |
July | 0.120491E+12 | 0.00 | 458.37 | 0.923189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 188688.24 | 28-JUL-14:00 | 141229.73 | 31-JUL-13:50 | 0.00 | 0.00 | 0.00 |
August | 0.147759E+12 | 0.00 | 475.52 | 0.106322E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 213677.67 | 07-AUG-09:50 | 145699.41 | 17-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.809651E+11 | 0.00 | 411.76 | 0.668366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 177760.39 | 22-SEP-04:12 | 163039.96 | 29-SEP-13:30 | 0.00 | 0.00 | 0.00 |
October | 0.942051E+11 | 0.00 | 407.03 | 0.807613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 196250.41 | 01-OCT-14:42 | 168525.76 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 0.317781E+11 | 0.00 | 260.48 | 0.314674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123517.44 | 28-NOV-14:00 | 123517.44 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.371607E+11 | 0.00 | 239.89 | 0.370368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131168.61 | 05-DEC-15:00 | 131168.61 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.723705E+12 | 0.00 | 3909.91 | 0.618861E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.158245E+11 | 0.00 | 180.33 | 0.156789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108259.49 | 107176.12 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.147759E+12 | 0.00 | 475.52 | 0.106322E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 213677.67 | 168525.76 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.267453E+12 | 0.00 | 260.87 | 0.266327E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1049544.64 | 18-JAN-13:02 | 1049544.64 | 18-JAN-13:02 | 0.00 | 0.00 | 0.00 |
February | 0.143037E+12 | 0.00 | 193.37 | 0.141786E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 963855.53 | 01-FEB-12:00 | 963855.53 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.169330E+12 | 0.00 | 195.28 | 0.165423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1105854.55 | 23-MAR-14:05 | 928888.79 | 23-MAR-14:05 | 0.00 | 0.00 | 0.00 |
April | 0.329174E+12 | 0.00 | 299.74 | 0.328688E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1205468.18 | 26-APR-14:05 | 1176903.40 | 26-APR-14:05 | 0.00 | 0.00 | 0.00 |
May | 0.333053E+12 | 0.00 | 344.12 | 0.331933E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 937654.85 | 03-MAY-13:00 | 937654.85 | 03-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.580395E+12 | 0.00 | 412.83 | 0.526863E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1337926.90 | 30-JUN-04:11 | 925242.39 | 29-JUN-13:00 | 0.00 | 0.00 | 0.00 |
July | 0.978665E+12 | 0.00 | 447.73 | 0.748591E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1636156.25 | 28-JUL-14:05 | 1182413.29 | 19-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.116753E+13 | 0.00 | 464.54 | 0.842098E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1702477.91 | 15-AUG-16:00 | 1259251.90 | 17-AUG-14:05 | 0.00 | 0.00 | 0.00 |
September | 0.704780E+12 | 0.00 | 405.90 | 0.584982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1567097.19 | 29-SEP-14:05 | 1567097.19 | 29-SEP-14:05 | 0.00 | 0.00 | 0.00 |
October | 0.816216E+12 | 0.00 | 406.86 | 0.700794E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1805123.01 | 01-OCT-14:31 | 1503306.14 | 16-OCT-14:05 | 0.00 | 0.00 | 0.00 |
November | 0.282721E+12 | 0.00 | 268.95 | 0.280024E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1001205.74 | 28-NOV-14:00 | 1001205.74 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.312154E+12 | 0.00 | 257.24 | 0.311055E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1061754.18 | 05-DEC-15:03 | 1061754.18 | 05-DEC-15:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.608451E+13 | 0.00 | 3957.44 | 0.522856E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.143037E+12 | 0.00 | 193.37 | 0.141786E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 937654.85 | 925242.39 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.116753E+13 | 0.00 | 464.54 | 0.842098E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1805123.01 | 1567097.19 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.223541E+11 | 0.00 | 221.29 | 0.223511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121320.77 | 18-JAN-14:15 | 121320.77 | 18-JAN-14:15 | 0.00 | 0.00 | 0.00 |
February | 0.123609E+11 | 0.00 | 172.90 | 0.122243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102006.95 | 01-FEB-13:03 | 102006.95 | 01-FEB-13:03 | 0.00 | 0.00 | 0.00 |
March | 0.154281E+11 | 0.00 | 174.02 | 0.152193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109915.60 | 23-MAR-15:00 | 100062.98 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.356551E+11 | 0.00 | 286.60 | 0.356002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159997.67 | 26-APR-13:50 | 157244.42 | 26-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.355569E+11 | 0.00 | 333.80 | 0.354629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135455.28 | 03-MAY-13:00 | 135455.28 | 03-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.644178E+11 | 0.00 | 406.22 | 0.587060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159187.38 | 29-JUN-13:20 | 133658.18 | 21-JUN-13:00 | 0.00 | 0.00 | 0.00 |
July | 0.112069E+12 | 0.00 | 438.13 | 0.881779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 188504.39 | 28-JUL-14:00 | 160741.61 | 31-JUL-14:00 | 0.00 | 0.00 | 0.00 |
August | 0.130403E+12 | 0.00 | 452.13 | 0.970570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 194820.11 | 15-AUG-16:00 | 163238.08 | 17-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.738802E+11 | 0.00 | 396.07 | 0.620055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 193856.32 | 29-SEP-13:40 | 193856.32 | 29-SEP-13:40 | 0.00 | 0.00 | 0.00 |
October | 0.837121E+11 | 0.00 | 390.35 | 0.727229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 199615.18 | 01-OCT-14:42 | 193194.13 | 15-OCT-13:31 | 0.00 | 0.00 | 0.00 |
November | 0.233191E+11 | 0.00 | 248.85 | 0.232584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110787.54 | 19-NOV-13:21 | 110787.54 | 19-NOV-13:21 | 0.00 | 0.00 | 0.00 |
December | 0.272896E+11 | 0.00 | 226.63 | 0.272531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118086.13 | 05-DEC-15:00 | 118086.13 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.636445E+12 | 0.00 | 3746.98 | 0.550039E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.123609E+11 | 0.00 | 172.90 | 0.122243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102006.95 | 100062.98 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.130403E+12 | 0.00 | 452.13 | 0.970570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 199615.18 | 193856.32 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.259487E+11 | 0.00 | 277.85 | 0.240253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78679.08 | 17-JAN-11:50 | 67967.97 | 09-JAN-10:18 | 0.00 | 0.00 | 0.00 |
February | 0.185073E+11 | 0.00 | 203.94 | 0.164333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82927.80 | 13-FEB-05:11 | 64551.79 | 07-FEB-08:31 | 0.00 | 0.00 | 0.00 |
March | 0.196006E+11 | 0.00 | 230.93 | 0.171767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 107442.65 | 01-MAR-05:57 | 107442.65 | 01-MAR-05:57 | 0.00 | 0.00 | 0.00 |
April | 0.293326E+11 | 0.00 | 293.78 | 0.250607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84515.96 | 11-APR-17:50 | 58955.98 | 26-APR-13:10 | 0.00 | 0.00 | 0.00 |
May | 0.315251E+11 | 0.00 | 327.32 | 0.282689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74539.14 | 09-MAY-14:18 | 62808.43 | 12-MAY-10:04 | 0.00 | 0.00 | 0.00 |
June | 0.511059E+11 | 0.00 | 361.31 | 0.379354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110267.79 | 29-JUN-07:58 | 60990.46 | 26-JUN-10:00 | 0.00 | 0.00 | 0.00 |
July | 0.779213E+11 | 0.00 | 384.00 | 0.496418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 128896.46 | 31-JUL-00:44 | 114589.58 | 05-JUL-01:03 | 0.00 | 0.00 | 0.00 |
August | 0.926240E+11 | 0.00 | 423.75 | 0.560020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131700.38 | 07-AUG-09:50 | 76720.42 | 28-AUG-01:30 | 0.00 | 0.00 | 0.00 |
September | 0.583201E+11 | 0.00 | 370.08 | 0.398350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124251.78 | 22-SEP-04:12 | 113951.79 | 30-SEP-03:01 | 0.00 | 0.00 | 0.00 |
October | 0.608769E+11 | 0.00 | 374.64 | 0.469322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140056.26 | 05-OCT-04:21 | 131737.50 | 16-OCT-02:44 | 0.00 | 0.00 | 0.00 |
November | 0.236249E+11 | 0.00 | 281.32 | 0.218982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122179.52 | 12-NOV-12:55 | 116488.59 | 12-NOV-15:53 | 0.00 | 0.00 | 0.00 |
December | 0.268539E+11 | 0.00 | 270.46 | 0.260055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91275.56 | 08-DEC-15:13 | 69870.13 | 21-DEC-12:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.516241E+12 | 0.00 | 3799.39 | 0.389215E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.185073E+11 | 0.00 | 203.94 | 0.164333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74539.14 | 58955.98 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.926240E+11 | 0.00 | 423.75 | 0.560020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140056.26 | 131737.50 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.789937E+10 | 0.00 | 293.15 | 0.789937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109880.99 | 13-JAN-12:02 | 109880.99 | 13-JAN-12:02 | 0.00 | 0.00 | 0.00 |
February | 0.141882E+12 | 0.00 | 310.61 | 0.129130E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 397159.30 | 12-FEB-13:41 | 345046.62 | 03-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.228041E+12 | 0.00 | 739.69 | 0.220489E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 372434.01 | 22-MAR-15:57 | 288968.82 | 11-MAR-16:42 | 0.00 | 0.00 | 0.00 |
April | 0.259022E+12 | 0.00 | 719.46 | 0.252115E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 413658.97 | 02-APR-12:36 | 413658.97 | 02-APR-12:36 | 0.00 | 0.00 | 0.00 |
May | 0.192307E+10 | 0.00 | 256.01 | 0.185671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 266666.75 | 31-MAY-23:11 | 235789.63 | 31-MAY-23:11 | 0.00 | 0.00 | 0.00 |
June | 0.246577E+12 | 0.00 | 448.45 | 0.190581E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 474602.51 | 29-JUN-18:22 | 317925.36 | 06-JUN-12:22 | 0.00 | 0.00 | 0.00 |
July | 0.337351E+12 | 0.00 | 743.85 | 0.267087E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 492530.95 | 19-JUL-19:51 | 292283.25 | 19-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.440714E+12 | 0.00 | 743.61 | 0.365729E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 522967.36 | 18-AUG-09:30 | 398025.54 | 06-AUG-08:55 | 0.00 | 0.00 | 0.00 |
September | 0.190487E+11 | 0.00 | 318.75 | 0.186724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 443969.41 | 30-SEP-23:40 | 222323.53 | 30-SEP-23:51 | 0.00 | 0.00 | 0.00 |
October | 0.278204E+12 | 0.00 | 516.82 | 0.229863E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 521538.62 | 01-OCT-07:02 | 335844.07 | 25-OCT-16:41 | 0.00 | 0.00 | 0.00 |
November | 0.236804E+12 | 0.00 | 709.81 | 0.223142E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 392580.82 | 20-NOV-13:11 | 303525.50 | 28-NOV-12:02 | 0.00 | 0.00 | 0.00 |
December | 0.274652E+12 | 0.00 | 744.00 | 0.273055E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 432557.28 | 19-DEC-13:02 | 432557.28 | 19-DEC-13:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247212E+13 | 0.00 | 6544.22 | 0.217962E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.192307E+10 | 0.00 | 256.01 | 0.185671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109880.99 | 109880.99 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.440714E+12 | 0.00 | 744.00 | 0.365729E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 522967.36 | 432557.28 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.682114E+10 | 0.206322E+10 | 744.00 | 0.679489E+10 | 26247221.10 | 0.00 | 0.57 | 18-JAN-16:10 | 0.30 | 09-JAN-07:02 | 3497.98 | 18-JAN-16:10 | 3443.34 | 18-JAN-16:00 | 149.57 | 20-JAN-17:00 | 1027.20 | 24-JAN-16:00 | 0.00 | 01-JAN-00:10 |
February | 0.106436E+11 | 0.297768E+10 | 672.00 | 0.106029E+11 | 40672922.08 | 0.00 | 0.84 | 03-FEB-16:41 | 0.59 | 25-FEB-17:51 | 5498.08 | 22-FEB-17:00 | 5407.38 | 22-FEB-16:57 | 183.76 | 13-FEB-16:51 | 1475.27 | 22-FEB-17:00 | 0.00 | 01-FEB-00:01 |
March | 0.170152E+11 | 0.442490E+10 | 744.00 | 0.169520E+11 | 63154995.47 | 0.00 | 1.00 | 01-MAR-15:01 | 0.84 | 30-MAR-06:10 | 7814.46 | 31-MAR-23:22 | 7814.46 | 31-MAR-23:22 | 228.65 | 23-MAR-16:00 | 2021.02 | 31-MAR-23:22 | 0.00 | 01-MAR-00:01 |
April | 0.218718E+11 | 0.570525E+10 | 720.00 | 0.217716E+11 | 0.100277E+09 | 0.00 | 1.00 | 01-APR-00:03 | 0.53 | 30-APR-24:00 | 9396.66 | 26-APR-16:00 | 9231.37 | 30-APR-17:20 | 196.56 | 25-APR-10:00 | 2592.49 | 26-APR-13:00 | 0.00 | 01-APR-00:03 |
May | 0.741515E+10 | 0.221808E+10 | 744.00 | 0.734271E+10 | 72445837.64 | 0.00 | 0.70 | 31-MAY-23:51 | 0.35 | 13-MAY-06:50 | 4408.63 | 31-MAY-23:51 | 4402.56 | 31-MAY-23:52 | 186.02 | 05-MAY-15:30 | 1233.86 | 31-MAY-23:51 | 0.00 | 01-MAY-00:10 |
June | 0.123878E+11 | 0.342609E+10 | 720.00 | 0.122354E+11 | 0.152329E+09 | 0.00 | 0.95 | 30-JUN-23:51 | 0.65 | 01-JUN-06:01 | 6534.33 | 30-JUN-23:51 | 6533.80 | 30-JUN-23:52 | 267.28 | 29-JUN-13:40 | 1687.09 | 30-JUN-23:51 | 0.00 | 01-JUN-00:01 |
July | 0.183774E+11 | 0.475502E+10 | 744.00 | 0.181336E+11 | 0.243877E+09 | 0.00 | 1.00 | 01-JUL-17:01 | 0.92 | 08-JUL-06:51 | 8566.75 | 31-JUL-23:05 | 8501.15 | 31-JUL-24:00 | 344.84 | 31-JUL-16:00 | 2229.18 | 31-JUL-24:00 | 0.00 | 01-JUL-00:01 |
August | 0.235309E+11 | 0.621168E+10 | 744.00 | 0.232276E+11 | 0.303251E+09 | 0.00 | 1.00 | 01-AUG-00:10 | 0.53 | 31-AUG-24:00 | 9691.95 | 17-AUG-16:00 | 9444.16 | 06-AUG-17:40 | 365.06 | 18-AUG-16:00 | 2763.09 | 17-AUG-14:00 | 0.00 | 01-AUG-00:10 |
September | 0.758617E+10 | 0.227422E+10 | 720.00 | 0.742430E+10 | 0.161867E+09 | 0.00 | 0.74 | 30-SEP-23:51 | 0.38 | 20-SEP-06:10 | 4690.65 | 30-SEP-23:51 | 4690.65 | 30-SEP-23:51 | 329.24 | 22-SEP-10:50 | 1345.77 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 0.126884E+11 | 0.356275E+10 | 744.00 | 0.125900E+11 | 98385501.08 | 0.00 | 0.94 | 31-OCT-23:51 | 0.63 | 28-OCT-06:21 | 6429.10 | 31-OCT-23:51 | 6428.62 | 31-OCT-23:52 | 314.68 | 05-OCT-16:00 | 1962.08 | 16-OCT-11:00 | 0.00 | 01-OCT-00:01 |
November | 0.166857E+11 | 0.432740E+10 | 720.00 | 0.166400E+11 | 45716780.61 | 0.00 | 1.00 | 01-NOV-15:21 | 0.86 | 18-NOV-07:06 | 7489.70 | 07-NOV-16:12 | 7352.59 | 07-NOV-16:20 | 206.07 | 10-NOV-16:50 | 1935.24 | 28-NOV-14:00 | 0.00 | 01-NOV-00:01 |
December | 0.221426E+11 | 0.577648E+10 | 744.00 | 0.221206E+11 | 21976378.46 | 0.00 | 1.00 | 01-DEC-00:01 | 1.00 | 01-DEC-00:01 | 9436.41 | 07-DEC-16:10 | 9414.99 | 18-DEC-16:10 | 175.37 | 07-DEC-16:20 | 2548.23 | 19-DEC-13:00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.177166E+12 | 0.477228E+11 | 8760.00 | 0.175836E+12 | 0.133020E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.682114E+10 | 0.206322E+10 | 672.00 | 0.679489E+10 | 21976378.46 | 0.00 | 0.57 | 0.30 | 3497.98 | 3443.34 | 149.57 | 1027.20 | 0.00 | |||||||
Maximum of Months | 0.235309E+11 | 0.621168E+10 | 744.00 | 0.232276E+11 | 0.303251E+09 | 0.00 | 1.00 | 1.00 | 9691.95 | 9444.16 | 365.06 | 2763.09 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.537322E+11 | 0.141679E+11 | 743.94 | 0.534732E+11 | 0.258972E+09 | 0.00 | 0.56 | 18-JAN-16:10 | 0.00 | 02-JAN-00:23 | 32654.38 | 18-JAN-16:10 | 32108.43 | 18-JAN-16:10 | 1502.30 | 20-JAN-17:00 | 8230.72 | 24-JAN-16:00 | 0.00 | 01-JAN-00:10 |
February | 0.939827E+11 | 0.228228E+11 | 672.00 | 0.935783E+11 | 0.404452E+09 | 0.00 | 0.83 | 03-FEB-16:41 | 0.53 | 26-FEB-04:54 | 52375.27 | 22-FEB-17:00 | 51470.95 | 22-FEB-16:57 | 1826.11 | 13-FEB-16:51 | 12055.59 | 22-FEB-17:00 | 0.00 | 01-FEB-00:01 |
March | 0.154622E+12 | 0.348496E+11 | 744.00 | 0.153992E+12 | 0.629836E+09 | 0.00 | 1.00 | 01-MAR-15:32 | 0.78 | 30-MAR-06:10 | 71817.74 | 31-MAR-23:03 | 71817.74 | 31-MAR-23:03 | 2290.02 | 23-MAR-16:00 | 15850.22 | 31-MAR-23:01 | 0.00 | 01-MAR-00:01 |
April | 0.203251E+12 | 0.453099E+11 | 720.00 | 0.202257E+12 | 0.994242E+09 | 0.00 | 1.00 | 01-APR-00:03 | 0.43 | 30-APR-24:00 | 89565.62 | 26-APR-16:00 | 87825.80 | 26-APR-16:00 | 1962.30 | 25-APR-10:00 | 21034.94 | 26-APR-14:00 | 0.00 | 01-APR-00:03 |
May | 0.638645E+11 | 0.165458E+11 | 744.00 | 0.631502E+11 | 0.714279E+09 | 0.00 | 0.65 | 31-MAY-23:41 | 0.27 | 15-MAY-06:10 | 39129.18 | 31-MAY-23:11 | 39041.77 | 31-MAY-23:52 | 1829.34 | 05-MAY-15:30 | 9505.37 | 31-MAY-23:11 | 0.00 | 01-MAY-00:10 |
June | 0.114223E+12 | 0.272482E+11 | 720.00 | 0.112707E+12 | 0.151651E+10 | 0.00 | 0.94 | 30-JUN-23:51 | 0.61 | 01-JUN-06:01 | 61359.02 | 30-JUN-23:51 | 61352.85 | 30-JUN-23:52 | 2655.72 | 29-JUN-13:40 | 13637.68 | 30-JUN-23:41 | 0.00 | 01-JUN-00:01 |
July | 0.170589E+12 | 0.380422E+11 | 744.00 | 0.168164E+12 | 0.242508E+10 | 0.00 | 1.00 | 01-JUL-17:20 | 0.88 | 08-JUL-06:51 | 80591.12 | 31-JUL-23:05 | 79847.98 | 31-JUL-24:00 | 3438.33 | 31-JUL-16:00 | 17938.22 | 31-JUL-23:05 | 0.00 | 01-JUL-00:01 |
August | 0.219531E+12 | 0.495514E+11 | 744.00 | 0.216512E+12 | 0.301894E+10 | 0.00 | 1.00 | 01-AUG-00:10 | 0.44 | 31-AUG-24:00 | 92097.72 | 17-AUG-16:00 | 88549.11 | 17-AUG-16:00 | 3637.52 | 18-AUG-16:00 | 22368.17 | 17-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.663423E+11 | 0.172169E+11 | 720.00 | 0.647443E+11 | 0.159800E+10 | 0.00 | 0.73 | 30-SEP-23:42 | 0.32 | 20-SEP-06:10 | 44070.40 | 30-SEP-23:42 | 44070.40 | 30-SEP-23:42 | 3257.52 | 22-SEP-11:00 | 10884.97 | 29-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 0.115554E+12 | 0.280525E+11 | 744.00 | 0.114575E+12 | 0.979522E+09 | 0.00 | 0.91 | 31-OCT-23:41 | 0.58 | 30-OCT-06:01 | 59179.94 | 31-OCT-23:31 | 59169.12 | 31-OCT-23:42 | 3135.35 | 05-OCT-16:00 | 15860.08 | 16-OCT-11:00 | 0.00 | 01-OCT-00:01 |
November | 0.151473E+12 | 0.340536E+11 | 720.00 | 0.151018E+12 | 0.455701E+09 | 0.00 | 1.00 | 01-NOV-15:21 | 0.81 | 27-NOV-07:02 | 71306.60 | 07-NOV-16:12 | 69929.22 | 07-NOV-16:20 | 2058.54 | 10-NOV-16:50 | 15660.15 | 07-NOV-16:12 | 0.00 | 01-NOV-00:01 |
December | 0.202142E+12 | 0.449832E+11 | 744.00 | 0.201924E+12 | 0.217764E+09 | 0.00 | 1.00 | 01-DEC-00:01 | 1.00 | 01-DEC-00:01 | 89232.37 | 07-DEC-16:10 | 88363.61 | 18-DEC-16:10 | 1779.50 | 07-DEC-16:10 | 20429.57 | 05-DEC-15:00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.160931E+13 | 0.372844E+12 | 8759.94 | 0.159609E+13 | 0.132133E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.537322E+11 | 0.141679E+11 | 672.00 | 0.534732E+11 | 0.217764E+09 | 0.00 | 0.56 | 0.00 | 32654.38 | 32108.43 | 1502.30 | 8230.72 | 0.00 | |||||||
Maximum of Months | 0.219531E+12 | 0.495514E+11 | 744.00 | 0.216512E+12 | 0.301894E+10 | 0.00 | 1.00 | 1.00 | 92097.72 | 88549.11 | 3637.52 | 22368.17 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.411734E+10 | 0.128089E+10 | 715.39 | 0.409175E+10 | 25594440.99 | 0.00 | 0.56 | 18-JAN-16:10 | 0.00 | 01-JAN-00:50 | 3375.52 | 18-JAN-16:10 | 3320.18 | 18-JAN-16:10 | 149.35 | 20-JAN-17:00 | 991.86 | 18-JAN-16:00 | 0.00 | 01-JAN-00:10 |
February | 0.842043E+10 | 0.242997E+10 | 672.00 | 0.838030E+10 | 40130712.96 | 0.00 | 0.82 | 03-FEB-16:41 | 0.35 | 26-FEB-06:50 | 5355.37 | 22-FEB-17:00 | 5265.07 | 22-FEB-16:57 | 183.33 | 13-FEB-16:41 | 1441.37 | 22-FEB-17:00 | 0.00 | 01-FEB-00:01 |
March | 0.145777E+11 | 0.390255E+10 | 744.00 | 0.145150E+11 | 62728947.39 | 0.00 | 1.00 | 01-MAR-15:51 | 0.64 | 05-MAR-07:00 | 7299.12 | 23-MAR-16:00 | 7261.71 | 10-MAR-17:00 | 229.09 | 23-MAR-16:00 | 1865.99 | 23-MAR-16:00 | 0.00 | 01-MAR-00:01 |
April | 0.198740E+11 | 0.514192E+10 | 720.00 | 0.197761E+11 | 97844191.40 | 0.00 | 1.00 | 01-APR-08:35 | 0.38 | 30-APR-24:00 | 9195.65 | 26-APR-16:00 | 9022.27 | 26-APR-16:00 | 201.21 | 25-APR-09:50 | 2526.20 | 26-APR-14:00 | 0.00 | 01-APR-00:03 |
May | 0.596094E+10 | 0.181192E+10 | 743.49 | 0.588944E+10 | 71503866.28 | 0.00 | 0.60 | 31-MAY-23:11 | 0.00 | 13-MAY-01:33 | 3615.98 | 31-MAY-23:11 | 3592.33 | 31-MAY-23:12 | 181.19 | 05-MAY-15:30 | 1042.87 | 31-MAY-23:11 | 0.00 | 01-MAY-00:10 |
June | 0.112482E+11 | 0.315376E+10 | 720.00 | 0.110961E+11 | 0.152125E+09 | 0.00 | 0.89 | 30-JUN-23:21 | 0.52 | 01-JUN-06:01 | 5946.50 | 30-JUN-23:11 | 5942.31 | 30-JUN-23:22 | 268.74 | 29-JUN-13:40 | 1564.91 | 30-JUN-23:11 | 0.00 | 01-JUN-00:01 |
July | 0.170302E+11 | 0.446446E+10 | 744.00 | 0.167874E+11 | 0.242710E+09 | 0.00 | 1.00 | 01-JUL-17:01 | 0.81 | 06-JUL-06:01 | 7906.91 | 31-JUL-23:05 | 7836.97 | 31-JUL-23:30 | 343.94 | 31-JUL-15:50 | 2097.17 | 19-JUL-15:00 | 0.00 | 01-JUL-00:01 |
August | 0.218736E+11 | 0.573987E+10 | 744.00 | 0.215724E+11 | 0.301213E+09 | 0.00 | 1.00 | 01-AUG-00:10 | 0.38 | 31-AUG-24:00 | 9451.32 | 17-AUG-16:00 | 9096.44 | 17-AUG-16:00 | 363.93 | 18-AUG-16:00 | 2680.77 | 17-AUG-14:20 | 0.00 | 01-AUG-00:10 |
September | 0.630596E+10 | 0.192230E+10 | 719.94 | 0.614580E+10 | 0.160163E+09 | 0.00 | 0.69 | 30-SEP-23:11 | 0.00 | 03-SEP-05:13 | 4242.65 | 30-SEP-23:12 | 4242.65 | 30-SEP-23:12 | 328.11 | 22-SEP-11:00 | 1340.97 | 29-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 0.110020E+11 | 0.315676E+10 | 744.00 | 0.109042E+11 | 97841282.38 | 0.00 | 0.90 | 15-OCT-16:31 | 0.43 | 30-OCT-06:01 | 5691.99 | 15-OCT-16:32 | 5691.99 | 15-OCT-16:32 | 313.23 | 05-OCT-16:00 | 1897.35 | 16-OCT-11:00 | 0.00 | 01-OCT-00:01 |
November | 0.141380E+11 | 0.378385E+10 | 720.00 | 0.140927E+11 | 45302984.98 | 0.00 | 1.00 | 06-NOV-15:41 | 0.64 | 05-NOV-07:10 | 7223.94 | 10-NOV-16:01 | 7076.29 | 07-NOV-16:20 | 204.04 | 10-NOV-16:50 | 1845.49 | 10-NOV-16:01 | 0.00 | 01-NOV-00:01 |
December | 0.189569E+11 | 0.490806E+10 | 744.00 | 0.189367E+11 | 20209624.32 | 0.00 | 1.00 | 01-DEC-00:01 | 0.84 | 25-DEC-07:30 | 9011.16 | 07-DEC-16:10 | 8935.37 | 19-DEC-16:10 | 175.34 | 07-DEC-16:10 | 2416.75 | 05-DEC-15:00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.153505E+12 | 0.416963E+11 | 8730.82 | 0.152188E+12 | 0.131737E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.411734E+10 | 0.128089E+10 | 672.00 | 0.409175E+10 | 20209624.32 | 0.00 | 0.56 | 0.00 | 3375.52 | 3320.18 | 149.35 | 991.86 | 0.00 | |||||||
Maximum of Months | 0.218736E+11 | 0.573987E+10 | 744.00 | 0.215724E+11 | 0.301213E+09 | 0.00 | 1.00 | 0.84 | 9451.32 | 9096.44 | 363.93 | 2680.77 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.82 | 0.00 | 121.82 | 64.68 | 795.92 | 0.00 | 0.00 | 0.00 |
February | 152.91 | 0.00 | 152.91 | 73.83 | 743.95 | 0.17 | 0.00 | 0.00 |
March | 187.38 | 0.00 | 187.38 | 114.61 | 760.82 | 4.83 | 0.00 | 0.00 |
April | 216.43 | 1.38 | 215.06 | 182.27 | 586.53 | 2.33 | 0.00 | 0.00 |
May | 263.66 | 16.31 | 247.35 | 243.68 | 495.35 | 0.00 | 0.00 | 0.00 |
June | 283.65 | 34.24 | 249.41 | 335.15 | 384.04 | 0.00 | 0.00 | 0.00 |
July | 268.51 | 28.71 | 239.80 | 368.78 | 346.53 | 0.00 | 0.00 | 0.00 |
August | 219.46 | 6.44 | 213.01 | 289.23 | 371.89 | 0.00 | 0.00 | 0.00 |
September | 184.01 | 0.06 | 183.95 | 221.75 | 432.26 | 0.00 | 0.00 | 0.00 |
October | 145.94 | 0.00 | 145.94 | 201.26 | 488.77 | 0.00 | 0.00 | 0.00 |
November | 132.14 | 0.00 | 132.14 | 74.55 | 728.68 | 2.17 | 0.00 | 0.00 |
December | 113.40 | 0.00 | 113.40 | 55.12 | 811.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.94 | 7.30 | 183.64 | 186.13 | 577.98 | 9.50 | 0.00 | 0.00 |
Minimum of Months | 113.40 | 0.00 | 113.40 | 55.12 | 346.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 283.65 | 34.24 | 249.41 | 368.78 | 811.30 | 4.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.82 | 0.00 | 121.82 | 64.68 | 795.92 | 0.00 | 0.00 | 0.00 |
February | 152.91 | 0.00 | 152.91 | 73.83 | 743.95 | 0.17 | 0.00 | 0.00 |
March | 187.38 | 0.00 | 187.38 | 114.61 | 760.82 | 4.83 | 0.00 | 0.00 |
April | 216.43 | 1.38 | 215.06 | 182.27 | 586.53 | 2.33 | 0.00 | 0.00 |
May | 263.66 | 16.31 | 247.35 | 243.68 | 495.35 | 0.00 | 0.00 | 0.00 |
June | 283.65 | 34.24 | 249.41 | 335.15 | 384.04 | 0.00 | 0.00 | 0.00 |
July | 268.51 | 28.71 | 239.80 | 368.78 | 346.53 | 0.00 | 0.00 | 0.00 |
August | 219.46 | 6.44 | 213.01 | 289.23 | 371.89 | 0.00 | 0.00 | 0.00 |
September | 184.01 | 0.06 | 183.95 | 221.75 | 432.26 | 0.00 | 0.00 | 0.00 |
October | 145.94 | 0.00 | 145.94 | 201.26 | 488.77 | 0.00 | 0.00 | 0.00 |
November | 132.14 | 0.00 | 132.14 | 74.55 | 728.68 | 2.17 | 0.00 | 0.00 |
December | 113.40 | 0.00 | 113.40 | 55.12 | 811.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.94 | 7.30 | 183.64 | 186.13 | 577.98 | 9.50 | 0.00 | 0.00 |
Minimum of Months | 113.40 | 0.00 | 113.40 | 55.12 | 346.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 283.65 | 34.24 | 249.41 | 368.78 | 811.30 | 4.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.82 | 0.00 | 121.82 | 64.68 | 795.92 | 0.00 | 0.00 | 0.00 |
February | 152.91 | 0.00 | 152.91 | 73.83 | 743.95 | 0.17 | 0.00 | 0.00 |
March | 187.38 | 0.00 | 187.38 | 114.61 | 760.82 | 4.83 | 0.00 | 0.00 |
April | 216.43 | 1.38 | 215.06 | 182.27 | 586.53 | 2.33 | 0.00 | 0.00 |
May | 263.66 | 16.31 | 247.35 | 243.68 | 495.35 | 0.00 | 0.00 | 0.00 |
June | 283.65 | 34.24 | 249.41 | 335.15 | 384.04 | 0.00 | 0.00 | 0.00 |
July | 268.51 | 28.71 | 239.80 | 368.78 | 346.53 | 0.00 | 0.00 | 0.00 |
August | 219.46 | 6.44 | 213.01 | 289.23 | 371.89 | 0.00 | 0.00 | 0.00 |
September | 184.01 | 0.06 | 183.95 | 221.75 | 432.26 | 0.00 | 0.00 | 0.00 |
October | 145.94 | 0.00 | 145.94 | 201.26 | 488.77 | 0.00 | 0.00 | 0.00 |
November | 132.14 | 0.00 | 132.14 | 74.55 | 728.68 | 2.17 | 0.00 | 0.00 |
December | 113.40 | 0.00 | 113.40 | 55.12 | 811.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.94 | 7.30 | 183.64 | 186.13 | 577.98 | 9.50 | 0.00 | 0.00 |
Minimum of Months | 113.40 | 0.00 | 113.40 | 55.12 | 346.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 283.65 | 34.24 | 249.41 | 368.78 | 811.30 | 4.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.82 | 0.00 | 121.82 | 64.68 | 795.92 | 0.00 | 0.00 | 0.00 |
February | 152.91 | 0.00 | 152.91 | 73.83 | 743.95 | 0.17 | 0.00 | 0.00 |
March | 187.38 | 0.00 | 187.38 | 114.61 | 760.82 | 4.83 | 0.00 | 0.00 |
April | 216.43 | 1.38 | 215.06 | 182.27 | 586.53 | 2.33 | 0.00 | 0.00 |
May | 263.66 | 16.31 | 247.35 | 243.68 | 495.35 | 0.00 | 0.00 | 0.00 |
June | 283.65 | 34.24 | 249.41 | 335.15 | 384.04 | 0.00 | 0.00 | 0.00 |
July | 268.51 | 28.71 | 239.80 | 368.78 | 346.53 | 0.00 | 0.00 | 0.00 |
August | 219.46 | 6.44 | 213.01 | 289.23 | 371.89 | 0.00 | 0.00 | 0.00 |
September | 184.01 | 0.06 | 183.95 | 221.75 | 432.26 | 0.00 | 0.00 | 0.00 |
October | 145.94 | 0.00 | 145.94 | 201.26 | 488.77 | 0.00 | 0.00 | 0.00 |
November | 132.14 | 0.00 | 132.14 | 74.55 | 728.68 | 2.17 | 0.00 | 0.00 |
December | 113.40 | 0.00 | 113.40 | 55.12 | 811.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.94 | 7.30 | 183.64 | 186.13 | 577.98 | 9.50 | 0.00 | 0.00 |
Minimum of Months | 113.40 | 0.00 | 113.40 | 55.12 | 346.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 283.65 | 34.24 | 249.41 | 368.78 | 811.30 | 4.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.81 | 0.00 | 121.81 | 64.67 | 795.88 | 0.00 | 0.00 | 0.00 |
February | 152.91 | 0.00 | 152.91 | 73.82 | 743.92 | 0.17 | 0.00 | 0.00 |
March | 187.38 | 0.00 | 187.38 | 114.60 | 760.79 | 4.83 | 0.00 | 0.00 |
April | 216.42 | 1.38 | 215.05 | 182.27 | 586.51 | 2.33 | 0.00 | 0.00 |
May | 263.64 | 16.31 | 247.34 | 243.67 | 495.33 | 0.00 | 0.00 | 0.00 |
June | 283.64 | 34.24 | 249.40 | 335.14 | 384.02 | 0.00 | 0.00 | 0.00 |
July | 268.50 | 28.70 | 239.79 | 368.76 | 346.52 | 0.00 | 0.00 | 0.00 |
August | 219.45 | 6.44 | 213.00 | 289.22 | 371.87 | 0.00 | 0.00 | 0.00 |
September | 184.00 | 0.06 | 183.94 | 221.74 | 432.24 | 0.00 | 0.00 | 0.00 |
October | 145.93 | 0.00 | 145.93 | 201.25 | 488.75 | 0.00 | 0.00 | 0.00 |
November | 132.13 | 0.00 | 132.13 | 74.55 | 728.65 | 2.17 | 0.00 | 0.00 |
December | 113.40 | 0.00 | 113.40 | 55.12 | 811.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.93 | 7.30 | 183.63 | 186.12 | 577.96 | 9.50 | 0.00 | 0.00 |
Minimum of Months | 113.40 | 0.00 | 113.40 | 55.12 | 346.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 283.64 | 34.24 | 249.40 | 368.76 | 811.26 | 4.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 366.95 | 197.11 | 169.84 | 523.76 | 793.37 | 0.00 | 0.00 | 0.00 |
February | 385.26 | 176.55 | 208.71 | 500.91 | 747.80 | 0.00 | 0.00 | 0.00 |
March | 465.39 | 206.00 | 259.39 | 646.20 | 759.37 | 2.83 | 0.00 | 0.00 |
April | 596.08 | 297.93 | 298.15 | 1000.13 | 587.68 | 1.67 | 0.00 | 0.00 |
May | 562.95 | 234.05 | 328.90 | 892.64 | 529.47 | 0.00 | 0.00 | 0.00 |
June | 560.76 | 243.20 | 317.56 | 988.61 | 410.72 | 0.00 | 0.00 | 0.00 |
July | 634.56 | 314.81 | 319.75 | 1235.62 | 365.21 | 0.00 | 0.00 | 0.00 |
August | 625.66 | 331.37 | 294.29 | 1236.44 | 374.55 | 0.00 | 0.00 | 0.00 |
September | 457.30 | 209.71 | 247.59 | 843.95 | 434.45 | 0.00 | 0.00 | 0.00 |
October | 404.23 | 207.61 | 196.62 | 760.47 | 485.55 | 0.00 | 0.00 | 0.00 |
November | 369.91 | 188.49 | 181.43 | 528.35 | 719.70 | 1.83 | 0.00 | 0.00 |
December | 354.49 | 198.15 | 156.34 | 503.89 | 790.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 482.60 | 234.21 | 248.40 | 807.19 | 582.32 | 6.33 | 0.00 | 0.00 |
Minimum of Months | 354.49 | 176.55 | 156.34 | 500.91 | 365.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 634.56 | 331.37 | 328.90 | 1236.44 | 793.37 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 366.95 | 197.11 | 169.84 | 523.76 | 793.37 | 0.00 | 0.00 | 0.00 |
February | 385.26 | 176.55 | 208.71 | 500.91 | 747.80 | 0.00 | 0.00 | 0.00 |
March | 465.39 | 206.00 | 259.39 | 646.20 | 759.37 | 2.83 | 0.00 | 0.00 |
April | 596.08 | 297.93 | 298.15 | 1000.13 | 587.68 | 1.67 | 0.00 | 0.00 |
May | 562.95 | 234.05 | 328.90 | 892.64 | 529.47 | 0.00 | 0.00 | 0.00 |
June | 560.76 | 243.20 | 317.56 | 988.61 | 410.72 | 0.00 | 0.00 | 0.00 |
July | 634.56 | 314.81 | 319.75 | 1235.62 | 365.21 | 0.00 | 0.00 | 0.00 |
August | 625.66 | 331.37 | 294.29 | 1236.44 | 374.55 | 0.00 | 0.00 | 0.00 |
September | 457.30 | 209.71 | 247.59 | 843.95 | 434.45 | 0.00 | 0.00 | 0.00 |
October | 404.23 | 207.61 | 196.62 | 760.47 | 485.55 | 0.00 | 0.00 | 0.00 |
November | 369.91 | 188.49 | 181.43 | 528.35 | 719.70 | 1.83 | 0.00 | 0.00 |
December | 354.49 | 198.15 | 156.34 | 503.89 | 790.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 482.60 | 234.21 | 248.40 | 807.19 | 582.32 | 6.33 | 0.00 | 0.00 |
Minimum of Months | 354.49 | 176.55 | 156.34 | 500.91 | 365.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 634.56 | 331.37 | 328.90 | 1236.44 | 793.37 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 366.94 | 197.11 | 169.83 | 523.75 | 793.36 | 0.00 | 0.00 | 0.00 |
February | 385.25 | 176.55 | 208.70 | 500.90 | 747.79 | 0.00 | 0.00 | 0.00 |
March | 465.38 | 205.99 | 259.39 | 646.19 | 759.36 | 2.83 | 0.00 | 0.00 |
April | 596.07 | 297.92 | 298.15 | 1000.11 | 587.67 | 1.67 | 0.00 | 0.00 |
May | 562.94 | 234.05 | 328.89 | 892.62 | 529.46 | 0.00 | 0.00 | 0.00 |
June | 560.75 | 243.19 | 317.55 | 988.59 | 410.71 | 0.00 | 0.00 | 0.00 |
July | 634.55 | 314.81 | 319.74 | 1235.60 | 365.20 | 0.00 | 0.00 | 0.00 |
August | 625.65 | 331.37 | 294.28 | 1236.42 | 374.54 | 0.00 | 0.00 | 0.00 |
September | 457.29 | 209.71 | 247.59 | 843.93 | 434.44 | 0.00 | 0.00 | 0.00 |
October | 404.22 | 207.61 | 196.61 | 760.45 | 485.54 | 0.00 | 0.00 | 0.00 |
November | 369.91 | 188.48 | 181.42 | 528.34 | 719.69 | 1.83 | 0.00 | 0.00 |
December | 354.49 | 198.15 | 156.34 | 503.88 | 790.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 482.59 | 234.20 | 248.39 | 807.18 | 582.31 | 6.33 | 0.00 | 0.00 |
Minimum of Months | 354.49 | 176.55 | 156.34 | 500.90 | 365.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 634.55 | 331.37 | 328.89 | 1236.42 | 793.36 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 787.14 | 572.93 | 214.21 | 1472.72 | 721.40 | 0.00 | 0.00 | 0.00 |
February | 629.08 | 386.43 | 242.66 | 1051.30 | 683.86 | 0.00 | 0.00 | 0.00 |
March | 516.07 | 255.68 | 260.40 | 840.94 | 720.07 | 3.83 | 0.00 | 0.00 |
April | 451.14 | 190.75 | 260.39 | 789.75 | 580.20 | 2.17 | 0.00 | 0.00 |
May | 314.86 | 52.05 | 262.81 | 428.97 | 515.53 | 0.00 | 0.00 | 0.00 |
June | 272.28 | 25.25 | 247.03 | 386.87 | 392.55 | 0.00 | 0.00 | 0.00 |
July | 293.63 | 46.49 | 247.14 | 505.21 | 349.45 | 0.00 | 0.00 | 0.00 |
August | 385.95 | 141.03 | 244.92 | 766.35 | 373.32 | 0.00 | 0.00 | 0.00 |
September | 520.45 | 274.88 | 245.57 | 1052.14 | 422.97 | 0.00 | 0.00 | 0.00 |
October | 635.89 | 426.02 | 209.87 | 1322.05 | 467.23 | 0.00 | 0.00 | 0.00 |
November | 757.42 | 531.17 | 226.25 | 1395.33 | 666.97 | 1.83 | 0.00 | 0.00 |
December | 838.78 | 633.63 | 205.15 | 1575.10 | 731.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 533.14 | 294.37 | 238.77 | 965.51 | 551.39 | 7.83 | 0.00 | 0.00 |
Minimum of Months | 272.28 | 25.25 | 205.15 | 386.87 | 349.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 838.78 | 633.63 | 262.81 | 1575.10 | 731.33 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 787.14 | 572.93 | 214.21 | 1472.72 | 721.40 | 0.00 | 0.00 | 0.00 |
February | 629.08 | 386.43 | 242.66 | 1051.30 | 683.86 | 0.00 | 0.00 | 0.00 |
March | 516.07 | 255.68 | 260.40 | 840.94 | 720.07 | 3.83 | 0.00 | 0.00 |
April | 451.14 | 190.75 | 260.39 | 789.75 | 580.20 | 2.17 | 0.00 | 0.00 |
May | 314.86 | 52.05 | 262.81 | 428.97 | 515.53 | 0.00 | 0.00 | 0.00 |
June | 272.28 | 25.25 | 247.03 | 386.87 | 392.55 | 0.00 | 0.00 | 0.00 |
July | 293.63 | 46.49 | 247.14 | 505.21 | 349.45 | 0.00 | 0.00 | 0.00 |
August | 385.95 | 141.03 | 244.92 | 766.35 | 373.32 | 0.00 | 0.00 | 0.00 |
September | 520.45 | 274.88 | 245.57 | 1052.14 | 422.97 | 0.00 | 0.00 | 0.00 |
October | 635.89 | 426.02 | 209.87 | 1322.05 | 467.23 | 0.00 | 0.00 | 0.00 |
November | 757.42 | 531.16 | 226.25 | 1395.33 | 666.97 | 1.83 | 0.00 | 0.00 |
December | 838.78 | 633.63 | 205.15 | 1575.10 | 731.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 533.14 | 294.37 | 238.77 | 965.51 | 551.39 | 7.83 | 0.00 | 0.00 |
Minimum of Months | 272.28 | 25.25 | 205.15 | 386.87 | 349.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 838.78 | 633.63 | 262.81 | 1575.10 | 731.33 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 787.14 | 572.93 | 214.21 | 1472.72 | 721.40 | 0.00 | 0.00 | 0.00 |
February | 629.08 | 386.43 | 242.66 | 1051.30 | 683.86 | 0.00 | 0.00 | 0.00 |
March | 516.07 | 255.68 | 260.40 | 840.94 | 720.07 | 3.83 | 0.00 | 0.00 |
April | 451.14 | 190.75 | 260.39 | 789.75 | 580.20 | 2.17 | 0.00 | 0.00 |
May | 314.86 | 52.05 | 262.81 | 428.97 | 515.53 | 0.00 | 0.00 | 0.00 |
June | 272.28 | 25.25 | 247.03 | 386.87 | 392.55 | 0.00 | 0.00 | 0.00 |
July | 293.63 | 46.49 | 247.14 | 505.21 | 349.45 | 0.00 | 0.00 | 0.00 |
August | 385.95 | 141.03 | 244.92 | 766.35 | 373.32 | 0.00 | 0.00 | 0.00 |
September | 520.45 | 274.88 | 245.57 | 1052.14 | 422.97 | 0.00 | 0.00 | 0.00 |
October | 635.89 | 426.02 | 209.87 | 1322.05 | 467.23 | 0.00 | 0.00 | 0.00 |
November | 757.42 | 531.17 | 226.25 | 1395.33 | 666.97 | 1.83 | 0.00 | 0.00 |
December | 838.78 | 633.63 | 205.15 | 1575.10 | 731.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 533.14 | 294.37 | 238.77 | 965.51 | 551.39 | 7.83 | 0.00 | 0.00 |
Minimum of Months | 272.28 | 25.25 | 205.15 | 386.87 | 349.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 838.78 | 633.63 | 262.81 | 1575.10 | 731.33 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 787.14 | 572.93 | 214.21 | 1472.72 | 721.40 | 0.00 | 0.00 | 0.00 |
February | 629.08 | 386.43 | 242.66 | 1051.30 | 683.86 | 0.00 | 0.00 | 0.00 |
March | 516.07 | 255.68 | 260.40 | 840.94 | 720.07 | 3.83 | 0.00 | 0.00 |
April | 451.14 | 190.75 | 260.39 | 789.75 | 580.20 | 2.17 | 0.00 | 0.00 |
May | 314.86 | 52.05 | 262.81 | 428.97 | 515.53 | 0.00 | 0.00 | 0.00 |
June | 272.28 | 25.25 | 247.03 | 386.87 | 392.55 | 0.00 | 0.00 | 0.00 |
July | 293.63 | 46.49 | 247.14 | 505.21 | 349.45 | 0.00 | 0.00 | 0.00 |
August | 385.95 | 141.03 | 244.92 | 766.35 | 373.32 | 0.00 | 0.00 | 0.00 |
September | 520.45 | 274.88 | 245.57 | 1052.14 | 422.97 | 0.00 | 0.00 | 0.00 |
October | 635.89 | 426.02 | 209.87 | 1322.05 | 467.23 | 0.00 | 0.00 | 0.00 |
November | 757.42 | 531.16 | 226.25 | 1395.33 | 666.97 | 1.83 | 0.00 | 0.00 |
December | 838.78 | 633.63 | 205.15 | 1575.10 | 731.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 533.14 | 294.37 | 238.77 | 965.51 | 551.39 | 7.83 | 0.00 | 0.00 |
Minimum of Months | 272.28 | 25.25 | 205.15 | 386.87 | 349.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 838.78 | 633.63 | 262.81 | 1575.10 | 731.33 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 787.11 | 572.91 | 214.20 | 1472.66 | 721.37 | 0.00 | 0.00 | 0.00 |
February | 629.06 | 386.41 | 242.65 | 1051.25 | 683.83 | 0.00 | 0.00 | 0.00 |
March | 516.05 | 255.67 | 260.39 | 840.91 | 720.04 | 3.83 | 0.00 | 0.00 |
April | 451.12 | 190.75 | 260.38 | 789.72 | 580.18 | 2.17 | 0.00 | 0.00 |
May | 314.85 | 52.05 | 262.80 | 428.96 | 515.51 | 0.00 | 0.00 | 0.00 |
June | 272.27 | 25.25 | 247.02 | 386.86 | 392.53 | 0.00 | 0.00 | 0.00 |
July | 293.62 | 46.49 | 247.13 | 505.19 | 349.44 | 0.00 | 0.00 | 0.00 |
August | 385.93 | 141.02 | 244.91 | 766.32 | 373.31 | 0.00 | 0.00 | 0.00 |
September | 520.43 | 274.87 | 245.56 | 1052.10 | 422.95 | 0.00 | 0.00 | 0.00 |
October | 635.87 | 426.01 | 209.86 | 1321.99 | 467.21 | 0.00 | 0.00 | 0.00 |
November | 757.39 | 531.14 | 226.24 | 1395.28 | 666.94 | 1.83 | 0.00 | 0.00 |
December | 838.75 | 633.60 | 205.14 | 1575.04 | 731.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 533.12 | 294.36 | 238.76 | 965.47 | 551.37 | 7.83 | 0.00 | 0.00 |
Minimum of Months | 272.27 | 25.25 | 205.14 | 386.86 | 349.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 838.75 | 633.60 | 262.80 | 1575.04 | 731.31 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 349.77 | 177.52 | 172.24 | 513.82 | 891.61 | 0.00 | 0.00 | 0.00 |
February | 413.55 | 190.36 | 223.19 | 561.97 | 851.80 | 0.00 | 0.00 | 0.00 |
March | 473.10 | 208.12 | 264.98 | 646.83 | 884.42 | 2.00 | 0.00 | 0.00 |
April | 651.86 | 337.86 | 314.00 | 1057.56 | 735.70 | 1.33 | 0.00 | 0.00 |
May | 640.59 | 294.30 | 346.29 | 1013.65 | 614.06 | 0.00 | 0.00 | 0.00 |
June | 678.06 | 337.17 | 340.89 | 1166.96 | 490.06 | 0.00 | 0.00 | 0.00 |
July | 717.95 | 382.43 | 335.52 | 1323.40 | 472.48 | 0.00 | 0.00 | 0.00 |
August | 673.43 | 363.30 | 310.13 | 1252.11 | 514.67 | 0.00 | 0.00 | 0.00 |
September | 576.69 | 307.18 | 269.52 | 1051.97 | 511.95 | 0.00 | 0.00 | 0.00 |
October | 442.40 | 241.19 | 201.21 | 833.74 | 579.32 | 0.00 | 0.00 | 0.00 |
November | 401.28 | 210.36 | 190.92 | 601.86 | 847.61 | 1.83 | 0.00 | 0.00 |
December | 355.93 | 192.01 | 163.92 | 523.52 | 960.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 531.68 | 270.50 | 261.18 | 880.56 | 695.47 | 5.17 | 0.00 | 0.00 |
Minimum of Months | 349.77 | 177.52 | 163.92 | 513.82 | 472.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 717.95 | 382.43 | 346.29 | 1323.40 | 960.73 | 2.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 349.77 | 177.52 | 172.24 | 513.82 | 891.61 | 0.00 | 0.00 | 0.00 |
February | 413.55 | 190.36 | 223.19 | 561.97 | 851.80 | 0.00 | 0.00 | 0.00 |
March | 473.10 | 208.12 | 264.98 | 646.83 | 884.42 | 2.00 | 0.00 | 0.00 |
April | 651.86 | 337.86 | 314.00 | 1057.56 | 735.70 | 1.33 | 0.00 | 0.00 |
May | 640.59 | 294.30 | 346.29 | 1013.65 | 614.06 | 0.00 | 0.00 | 0.00 |
June | 678.06 | 337.17 | 340.89 | 1166.96 | 490.06 | 0.00 | 0.00 | 0.00 |
July | 717.95 | 382.43 | 335.52 | 1323.40 | 472.48 | 0.00 | 0.00 | 0.00 |
August | 673.43 | 363.30 | 310.13 | 1252.11 | 514.67 | 0.00 | 0.00 | 0.00 |
September | 576.69 | 307.18 | 269.52 | 1051.97 | 511.95 | 0.00 | 0.00 | 0.00 |
October | 442.40 | 241.19 | 201.21 | 833.74 | 579.32 | 0.00 | 0.00 | 0.00 |
November | 401.28 | 210.36 | 190.92 | 601.86 | 847.61 | 1.83 | 0.00 | 0.00 |
December | 355.93 | 192.01 | 163.92 | 523.52 | 960.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 531.68 | 270.50 | 261.18 | 880.56 | 695.47 | 5.17 | 0.00 | 0.00 |
Minimum of Months | 349.77 | 177.52 | 163.92 | 513.82 | 472.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 717.95 | 382.43 | 346.29 | 1323.40 | 960.73 | 2.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 349.76 | 177.52 | 172.24 | 513.81 | 891.60 | 0.00 | 0.00 | 0.00 |
February | 413.54 | 190.36 | 223.19 | 561.96 | 851.78 | 0.00 | 0.00 | 0.00 |
March | 473.09 | 208.12 | 264.97 | 646.81 | 884.40 | 2.00 | 0.00 | 0.00 |
April | 651.85 | 337.86 | 313.99 | 1057.54 | 735.69 | 1.33 | 0.00 | 0.00 |
May | 640.58 | 294.30 | 346.28 | 1013.63 | 614.05 | 0.00 | 0.00 | 0.00 |
June | 678.05 | 337.16 | 340.88 | 1166.94 | 490.05 | 0.00 | 0.00 | 0.00 |
July | 717.93 | 382.42 | 335.51 | 1323.37 | 472.48 | 0.00 | 0.00 | 0.00 |
August | 673.42 | 363.29 | 310.13 | 1252.09 | 514.66 | 0.00 | 0.00 | 0.00 |
September | 576.68 | 307.17 | 269.51 | 1051.96 | 511.94 | 0.00 | 0.00 | 0.00 |
October | 442.39 | 241.18 | 201.21 | 833.72 | 579.31 | 0.00 | 0.00 | 0.00 |
November | 401.27 | 210.35 | 190.92 | 601.85 | 847.59 | 1.83 | 0.00 | 0.00 |
December | 355.92 | 192.01 | 163.92 | 523.51 | 960.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 531.67 | 270.49 | 261.18 | 880.54 | 695.46 | 5.17 | 0.00 | 0.00 |
Minimum of Months | 349.76 | 177.52 | 163.92 | 513.81 | 472.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 717.93 | 382.42 | 346.28 | 1323.37 | 960.71 | 2.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 609.08 | 0.00 | 609.08 | 406.61 | 3545.67 | 0.00 | 0.00 | 0.00 |
February | 764.56 | 0.00 | 764.56 | 446.43 | 3322.54 | 4.50 | 0.00 | 0.00 |
March | 936.91 | 0.00 | 936.91 | 654.34 | 3439.84 | 5.83 | 0.00 | 0.00 |
April | 1082.15 | 6.88 | 1075.27 | 989.09 | 2616.17 | 2.83 | 0.00 | 0.00 |
May | 1318.26 | 81.54 | 1236.72 | 1257.79 | 2293.07 | 0.00 | 0.00 | 0.00 |
June | 1418.23 | 171.20 | 1247.02 | 1660.49 | 1776.92 | 0.00 | 0.00 | 0.00 |
July | 1342.52 | 143.53 | 1198.99 | 1873.19 | 1559.83 | 0.00 | 0.00 | 0.00 |
August | 1097.27 | 32.21 | 1065.05 | 1496.46 | 1642.05 | 0.00 | 0.00 | 0.00 |
September | 920.02 | 0.28 | 919.73 | 1141.44 | 1952.94 | 0.00 | 0.00 | 0.00 |
October | 729.68 | 0.00 | 729.68 | 1067.76 | 2195.15 | 0.00 | 0.00 | 0.00 |
November | 660.67 | 0.00 | 660.67 | 471.19 | 3211.78 | 2.33 | 0.00 | 0.00 |
December | 567.00 | 0.00 | 567.00 | 389.38 | 3549.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 954.69 | 36.51 | 918.18 | 991.44 | 2588.38 | 15.50 | 0.00 | 0.00 |
Minimum of Months | 567.00 | 0.00 | 567.00 | 389.38 | 1559.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1418.23 | 171.20 | 1247.02 | 1873.19 | 3549.96 | 5.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1100.83 | 591.33 | 509.50 | 1564.34 | 2222.69 | 0.00 | 0.00 | 0.00 |
February | 1155.76 | 529.65 | 626.11 | 1461.41 | 2095.80 | 3.83 | 0.00 | 0.00 |
March | 1396.15 | 617.98 | 778.17 | 1893.81 | 2158.45 | 3.83 | 0.00 | 0.00 |
April | 1788.21 | 893.77 | 894.45 | 2931.27 | 1659.95 | 1.67 | 0.00 | 0.00 |
May | 1688.83 | 702.16 | 986.68 | 2598.49 | 1511.42 | 0.00 | 0.00 | 0.00 |
June | 1682.25 | 729.58 | 952.67 | 2891.44 | 1159.41 | 0.00 | 0.00 | 0.00 |
July | 1903.67 | 944.43 | 959.24 | 3633.88 | 1016.61 | 0.00 | 0.00 | 0.00 |
August | 1876.96 | 994.11 | 882.85 | 3634.15 | 1046.87 | 0.00 | 0.00 | 0.00 |
September | 1371.89 | 629.12 | 742.77 | 2483.55 | 1213.02 | 0.00 | 0.00 | 0.00 |
October | 1212.68 | 622.83 | 589.84 | 2234.62 | 1357.43 | 0.00 | 0.00 | 0.00 |
November | 1109.73 | 565.45 | 544.28 | 1560.71 | 2016.05 | 2.00 | 0.00 | 0.00 |
December | 1063.47 | 594.44 | 469.02 | 1504.25 | 2217.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1447.79 | 702.61 | 745.18 | 2372.32 | 1637.26 | 11.33 | 0.00 | 0.00 |
Minimum of Months | 1063.47 | 529.65 | 469.02 | 1461.41 | 1016.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1903.67 | 994.11 | 986.68 | 3634.15 | 2222.69 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3935.64 | 2864.63 | 1071.01 | 7211.31 | 3538.46 | 0.00 | 0.00 | 0.00 |
February | 3145.38 | 1932.11 | 1213.27 | 5066.89 | 3323.54 | 3.17 | 0.00 | 0.00 |
March | 2580.34 | 1278.37 | 1301.97 | 4100.49 | 3481.26 | 4.17 | 0.00 | 0.00 |
April | 2255.68 | 953.76 | 1301.92 | 3872.13 | 2749.78 | 2.17 | 0.00 | 0.00 |
May | 1574.29 | 260.26 | 1314.03 | 2093.44 | 2472.19 | 0.00 | 0.00 | 0.00 |
June | 1361.41 | 126.25 | 1235.16 | 1929.29 | 1838.96 | 0.00 | 0.00 | 0.00 |
July | 1468.15 | 232.46 | 1235.69 | 2543.83 | 1590.19 | 0.00 | 0.00 | 0.00 |
August | 1929.72 | 705.12 | 1224.60 | 3803.90 | 1712.18 | 0.00 | 0.00 | 0.00 |
September | 2602.21 | 1374.37 | 1227.84 | 5143.80 | 2034.23 | 0.00 | 0.00 | 0.00 |
October | 3179.43 | 2130.09 | 1049.34 | 6453.74 | 2274.64 | 0.00 | 0.00 | 0.00 |
November | 3787.04 | 2655.79 | 1131.25 | 6792.15 | 3237.69 | 2.33 | 0.00 | 0.00 |
December | 4193.85 | 3168.11 | 1025.73 | 7696.97 | 3545.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2665.66 | 1471.82 | 1193.84 | 4726.05 | 2646.38 | 11.83 | 0.00 | 0.00 |
Minimum of Months | 1361.41 | 126.25 | 1025.73 | 1929.29 | 1590.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4193.85 | 3168.11 | 1314.03 | 7696.97 | 3545.58 | 4.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1049.29 | 532.57 | 516.72 | 1571.23 | 2370.01 | 0.00 | 0.00 | 0.00 |
February | 1240.64 | 571.07 | 669.57 | 1701.49 | 2244.50 | 2.83 | 0.00 | 0.00 |
March | 1419.29 | 624.37 | 794.92 | 1981.21 | 2306.68 | 3.33 | 0.00 | 0.00 |
April | 1955.57 | 1013.58 | 941.99 | 3203.42 | 1869.10 | 1.50 | 0.00 | 0.00 |
May | 1921.74 | 882.89 | 1038.85 | 2994.43 | 1681.26 | 0.00 | 0.00 | 0.00 |
June | 2034.15 | 1011.49 | 1022.66 | 3459.85 | 1299.19 | 0.00 | 0.00 | 0.00 |
July | 2153.82 | 1147.27 | 1006.55 | 3995.40 | 1178.66 | 0.00 | 0.00 | 0.00 |
August | 2020.28 | 1089.88 | 930.39 | 3813.18 | 1223.88 | 0.00 | 0.00 | 0.00 |
September | 1730.06 | 921.52 | 808.54 | 3125.75 | 1361.80 | 0.00 | 0.00 | 0.00 |
October | 1327.19 | 723.55 | 603.64 | 2526.63 | 1504.60 | 0.00 | 0.00 | 0.00 |
November | 1203.82 | 631.07 | 572.75 | 1859.82 | 2163.71 | 2.33 | 0.00 | 0.00 |
December | 1067.77 | 576.02 | 491.75 | 1658.97 | 2395.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1595.03 | 811.49 | 783.54 | 2662.68 | 1797.65 | 10.00 | 0.00 | 0.00 |
Minimum of Months | 1049.29 | 532.57 | 491.75 | 1571.23 | 1178.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2153.82 | 1147.27 | 1038.85 | 3995.40 | 2395.60 | 3.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 609.08 | 0.00 | 609.08 | 472.50 | 3177.15 | 0.17 | 0.00 | 0.00 |
February | 764.56 | 0.00 | 764.56 | 506.21 | 2985.29 | 5.50 | 0.00 | 0.00 |
March | 936.91 | 0.00 | 936.91 | 702.15 | 3168.20 | 8.33 | 0.00 | 0.00 |
April | 1082.15 | 6.88 | 1075.27 | 992.26 | 2443.96 | 3.67 | 0.00 | 0.00 |
May | 1318.26 | 81.54 | 1236.72 | 1267.25 | 2139.87 | 0.00 | 0.00 | 0.00 |
June | 1418.23 | 171.20 | 1247.02 | 1635.76 | 1670.51 | 0.00 | 0.00 | 0.00 |
July | 1342.52 | 143.53 | 1198.99 | 1824.16 | 1485.03 | 0.00 | 0.00 | 0.00 |
August | 1097.27 | 32.21 | 1065.05 | 1464.12 | 1550.75 | 0.00 | 0.00 | 0.00 |
September | 920.02 | 0.28 | 919.73 | 1148.59 | 1803.19 | 0.00 | 0.00 | 0.00 |
October | 729.68 | 0.00 | 729.68 | 1107.48 | 1986.50 | 0.00 | 0.00 | 0.00 |
November | 660.67 | 0.00 | 660.67 | 539.70 | 2875.00 | 2.67 | 0.00 | 0.00 |
December | 567.00 | 0.00 | 567.00 | 462.27 | 3166.15 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 954.69 | 36.51 | 918.18 | 1013.59 | 2367.81 | 23.67 | 0.00 | 0.00 |
Minimum of Months | 567.00 | 0.00 | 567.00 | 462.27 | 1485.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1418.23 | 171.20 | 1247.02 | 1824.16 | 3177.15 | 8.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1100.83 | 591.33 | 509.50 | 1648.98 | 1998.36 | 0.17 | 0.00 | 0.00 |
February | 1155.76 | 529.65 | 626.11 | 1520.32 | 1897.23 | 5.00 | 0.00 | 0.00 |
March | 1396.15 | 617.98 | 778.17 | 1943.96 | 2002.58 | 5.67 | 0.00 | 0.00 |
April | 1788.21 | 893.77 | 894.45 | 2929.50 | 1574.22 | 2.67 | 0.00 | 0.00 |
May | 1688.83 | 702.16 | 986.68 | 2605.41 | 1439.25 | 0.00 | 0.00 | 0.00 |
June | 1682.25 | 729.58 | 952.67 | 2874.66 | 1117.52 | 0.00 | 0.00 | 0.00 |
July | 1903.67 | 944.43 | 959.24 | 3587.99 | 993.91 | 0.00 | 0.00 | 0.00 |
August | 1876.96 | 994.11 | 882.85 | 3595.06 | 1015.87 | 0.00 | 0.00 | 0.00 |
September | 1371.89 | 629.12 | 742.77 | 2482.45 | 1145.26 | 0.00 | 0.00 | 0.00 |
October | 1212.68 | 622.83 | 589.84 | 2258.94 | 1257.40 | 0.00 | 0.00 | 0.00 |
November | 1109.73 | 565.45 | 544.28 | 1632.88 | 1820.73 | 2.50 | 0.00 | 0.00 |
December | 1063.47 | 594.44 | 469.02 | 1592.65 | 1986.21 | 3.00 | 0.00 | 0.00 |
Annual Sum or Average | 1447.79 | 702.61 | 745.18 | 2395.55 | 1518.78 | 19.00 | 0.00 | 0.00 |
Minimum of Months | 1063.47 | 529.65 | 469.02 | 1520.32 | 993.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1903.67 | 994.11 | 986.68 | 3595.06 | 2002.58 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3935.64 | 2864.63 | 1071.01 | 7253.38 | 3218.72 | 0.00 | 0.00 | 0.00 |
February | 3145.38 | 1932.11 | 1213.27 | 5076.03 | 3023.59 | 5.00 | 0.00 | 0.00 |
March | 2580.34 | 1278.37 | 1301.97 | 4113.59 | 3231.15 | 6.33 | 0.00 | 0.00 |
April | 2255.68 | 953.76 | 1301.92 | 3839.14 | 2590.71 | 3.17 | 0.00 | 0.00 |
May | 1574.29 | 260.26 | 1314.03 | 2066.88 | 2337.87 | 0.00 | 0.00 | 0.00 |
June | 1361.41 | 126.25 | 1235.16 | 1888.67 | 1755.11 | 0.00 | 0.00 | 0.00 |
July | 1468.15 | 232.46 | 1235.69 | 2483.55 | 1535.23 | 0.00 | 0.00 | 0.00 |
August | 1929.72 | 705.12 | 1224.60 | 3743.77 | 1638.29 | 0.00 | 0.00 | 0.00 |
September | 2602.21 | 1374.37 | 1227.84 | 5104.37 | 1904.79 | 0.00 | 0.00 | 0.00 |
October | 3179.43 | 2130.09 | 1049.34 | 6438.67 | 2097.78 | 0.00 | 0.00 | 0.00 |
November | 3787.04 | 2655.79 | 1131.25 | 6804.28 | 2951.81 | 2.50 | 0.00 | 0.00 |
December | 4193.85 | 3168.11 | 1025.73 | 7734.14 | 3223.84 | 0.17 | 0.00 | 0.00 |
Annual Sum or Average | 2665.66 | 1471.82 | 1193.84 | 4712.54 | 2456.17 | 17.17 | 0.00 | 0.00 |
Minimum of Months | 1361.41 | 126.25 | 1025.73 | 1888.67 | 1535.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4193.85 | 3168.11 | 1314.03 | 7734.14 | 3231.15 | 6.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1049.29 | 532.57 | 516.72 | 1564.22 | 2185.53 | 0.00 | 0.00 | 0.00 |
February | 1240.64 | 571.07 | 669.57 | 1684.64 | 2076.07 | 4.50 | 0.00 | 0.00 |
March | 1419.29 | 624.37 | 794.92 | 1953.66 | 2166.39 | 5.33 | 0.00 | 0.00 |
April | 1955.57 | 1013.58 | 941.99 | 3136.98 | 1772.02 | 2.00 | 0.00 | 0.00 |
May | 1921.74 | 882.89 | 1038.85 | 2928.73 | 1597.06 | 0.00 | 0.00 | 0.00 |
June | 2034.15 | 1011.49 | 1022.66 | 3379.93 | 1241.42 | 0.00 | 0.00 | 0.00 |
July | 2153.82 | 1147.27 | 1006.55 | 3906.62 | 1136.48 | 0.00 | 0.00 | 0.00 |
August | 2020.28 | 1089.88 | 930.39 | 3731.51 | 1176.89 | 0.00 | 0.00 | 0.00 |
September | 1730.06 | 921.52 | 808.54 | 3070.50 | 1288.07 | 0.00 | 0.00 | 0.00 |
October | 1327.19 | 723.55 | 603.64 | 2497.44 | 1406.27 | 0.00 | 0.00 | 0.00 |
November | 1203.82 | 631.07 | 572.75 | 1846.01 | 1997.43 | 2.50 | 0.00 | 0.00 |
December | 1067.77 | 576.02 | 491.75 | 1656.91 | 2204.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1595.03 | 811.49 | 783.54 | 2618.04 | 1685.38 | 14.33 | 0.00 | 0.00 |
Minimum of Months | 1049.29 | 532.57 | 491.75 | 1564.22 | 1136.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2153.82 | 1147.27 | 1038.85 | 3906.62 | 2204.44 | 5.33 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.326276E+09 | 0.00 | 0.326276E+09 | 0.173228E+09 | 0.213178E+10 |
February | 0.369928E+09 | 0.00 | 0.369928E+09 | 0.178602E+09 | 0.179977E+10 |
March | 0.501888E+09 | 0.00 | 0.501888E+09 | 0.306959E+09 | 0.203777E+10 |
April | 0.560995E+09 | 3567786.23 | 0.557427E+09 | 0.472450E+09 | 0.152029E+10 |
May | 0.706175E+09 | 43678737.01 | 0.662496E+09 | 0.652681E+09 | 0.132675E+10 |
June | 0.735218E+09 | 88752565.40 | 0.646465E+09 | 0.868712E+09 | 0.995425E+09 |
July | 0.719168E+09 | 76884605.93 | 0.642284E+09 | 0.987740E+09 | 0.928149E+09 |
August | 0.587790E+09 | 17255955.08 | 0.570534E+09 | 0.774686E+09 | 0.996061E+09 |
September | 0.476943E+09 | 147381.93 | 0.476796E+09 | 0.574779E+09 | 0.112042E+10 |
October | 0.390878E+09 | 0.00 | 0.390878E+09 | 0.539049E+09 | 0.130912E+10 |
November | 0.342496E+09 | 0.00 | 0.342496E+09 | 0.193240E+09 | 0.188873E+10 |
December | 0.303735E+09 | 0.00 | 0.303735E+09 | 0.147645E+09 | 0.217297E+10 |
Annual Sum or Average | 0.602149E+10 | 0.230287E+09 | 0.579120E+10 | 0.586977E+10 | 0.182272E+11 |
Minimum of Months | 0.303735E+09 | 0.00 | 0.303735E+09 | 0.147645E+09 | 0.928149E+09 |
Maximum of Months | 0.735218E+09 | 88752565.40 | 0.662496E+09 | 0.987740E+09 | 0.217297E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.326275E+09 | 0.00 | 0.326275E+09 | 0.173228E+09 | 0.213178E+10 |
February | 0.369928E+09 | 0.00 | 0.369928E+09 | 0.178602E+09 | 0.179977E+10 |
March | 0.501887E+09 | 0.00 | 0.501887E+09 | 0.306958E+09 | 0.203777E+10 |
April | 0.560995E+09 | 3567781.95 | 0.557427E+09 | 0.472450E+09 | 0.152029E+10 |
May | 0.706174E+09 | 43678684.60 | 0.662496E+09 | 0.652681E+09 | 0.132675E+10 |
June | 0.735217E+09 | 88752458.91 | 0.646465E+09 | 0.868712E+09 | 0.995425E+09 |
July | 0.719168E+09 | 76884513.68 | 0.642283E+09 | 0.987739E+09 | 0.928148E+09 |
August | 0.587790E+09 | 17255934.37 | 0.570534E+09 | 0.774685E+09 | 0.996061E+09 |
September | 0.476943E+09 | 147381.76 | 0.476795E+09 | 0.574779E+09 | 0.112042E+10 |
October | 0.390878E+09 | 0.00 | 0.390878E+09 | 0.539049E+09 | 0.130912E+10 |
November | 0.342495E+09 | 0.00 | 0.342495E+09 | 0.193240E+09 | 0.188873E+10 |
December | 0.303735E+09 | 0.00 | 0.303735E+09 | 0.147645E+09 | 0.217297E+10 |
Annual Sum or Average | 0.602149E+10 | 0.230287E+09 | 0.579120E+10 | 0.586977E+10 | 0.182272E+11 |
Minimum of Months | 0.303735E+09 | 0.00 | 0.303735E+09 | 0.147645E+09 | 0.928148E+09 |
Maximum of Months | 0.735217E+09 | 88752458.91 | 0.662496E+09 | 0.987739E+09 | 0.217297E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.326276E+09 | 0.00 | 0.326276E+09 | 0.173228E+09 | 0.213178E+10 |
February | 0.369928E+09 | 0.00 | 0.369928E+09 | 0.178602E+09 | 0.179977E+10 |
March | 0.501888E+09 | 0.00 | 0.501888E+09 | 0.306959E+09 | 0.203777E+10 |
April | 0.560995E+09 | 3567786.23 | 0.557427E+09 | 0.472450E+09 | 0.152029E+10 |
May | 0.706175E+09 | 43678737.01 | 0.662496E+09 | 0.652681E+09 | 0.132675E+10 |
June | 0.735218E+09 | 88752565.40 | 0.646465E+09 | 0.868712E+09 | 0.995425E+09 |
July | 0.719168E+09 | 76884605.93 | 0.642284E+09 | 0.987740E+09 | 0.928149E+09 |
August | 0.587790E+09 | 17255955.08 | 0.570534E+09 | 0.774686E+09 | 0.996061E+09 |
September | 0.476943E+09 | 147381.93 | 0.476796E+09 | 0.574779E+09 | 0.112042E+10 |
October | 0.390878E+09 | 0.00 | 0.390878E+09 | 0.539049E+09 | 0.130912E+10 |
November | 0.342496E+09 | 0.00 | 0.342496E+09 | 0.193240E+09 | 0.188873E+10 |
December | 0.303735E+09 | 0.00 | 0.303735E+09 | 0.147645E+09 | 0.217297E+10 |
Annual Sum or Average | 0.602149E+10 | 0.230287E+09 | 0.579120E+10 | 0.586977E+10 | 0.182272E+11 |
Minimum of Months | 0.303735E+09 | 0.00 | 0.303735E+09 | 0.147645E+09 | 0.928149E+09 |
Maximum of Months | 0.735218E+09 | 88752565.40 | 0.662496E+09 | 0.987740E+09 | 0.217297E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.326275E+09 | 0.00 | 0.326275E+09 | 0.173228E+09 | 0.213178E+10 |
February | 0.369928E+09 | 0.00 | 0.369928E+09 | 0.178602E+09 | 0.179977E+10 |
March | 0.501887E+09 | 0.00 | 0.501887E+09 | 0.306958E+09 | 0.203777E+10 |
April | 0.560995E+09 | 3567781.95 | 0.557427E+09 | 0.472450E+09 | 0.152029E+10 |
May | 0.706174E+09 | 43678684.60 | 0.662496E+09 | 0.652681E+09 | 0.132675E+10 |
June | 0.735217E+09 | 88752458.91 | 0.646465E+09 | 0.868712E+09 | 0.995425E+09 |
July | 0.719168E+09 | 76884513.68 | 0.642283E+09 | 0.987739E+09 | 0.928148E+09 |
August | 0.587790E+09 | 17255934.37 | 0.570534E+09 | 0.774685E+09 | 0.996061E+09 |
September | 0.476943E+09 | 147381.76 | 0.476795E+09 | 0.574779E+09 | 0.112042E+10 |
October | 0.390878E+09 | 0.00 | 0.390878E+09 | 0.539049E+09 | 0.130912E+10 |
November | 0.342495E+09 | 0.00 | 0.342495E+09 | 0.193240E+09 | 0.188873E+10 |
December | 0.303735E+09 | 0.00 | 0.303735E+09 | 0.147645E+09 | 0.217297E+10 |
Annual Sum or Average | 0.602149E+10 | 0.230287E+09 | 0.579120E+10 | 0.586977E+10 | 0.182272E+11 |
Minimum of Months | 0.303735E+09 | 0.00 | 0.303735E+09 | 0.147645E+09 | 0.928148E+09 |
Maximum of Months | 0.735217E+09 | 88752458.91 | 0.662496E+09 | 0.987739E+09 | 0.217297E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.326263E+09 | 0.00 | 0.326263E+09 | 0.173221E+09 | 0.213170E+10 |
February | 0.369913E+09 | 0.00 | 0.369913E+09 | 0.178595E+09 | 0.179970E+10 |
March | 0.501868E+09 | 0.00 | 0.501868E+09 | 0.306947E+09 | 0.203769E+10 |
April | 0.560973E+09 | 3567642.43 | 0.557405E+09 | 0.472431E+09 | 0.152023E+10 |
May | 0.706146E+09 | 43676976.57 | 0.662469E+09 | 0.652655E+09 | 0.132669E+10 |
June | 0.735188E+09 | 88748988.28 | 0.646439E+09 | 0.868677E+09 | 0.995385E+09 |
July | 0.719139E+09 | 76881507.14 | 0.642258E+09 | 0.987700E+09 | 0.928111E+09 |
August | 0.587767E+09 | 17255259.59 | 0.570511E+09 | 0.774655E+09 | 0.996021E+09 |
September | 0.476924E+09 | 147375.99 | 0.476776E+09 | 0.574756E+09 | 0.112037E+10 |
October | 0.390862E+09 | 0.00 | 0.390862E+09 | 0.539027E+09 | 0.130907E+10 |
November | 0.342482E+09 | 0.00 | 0.342482E+09 | 0.193233E+09 | 0.188865E+10 |
December | 0.303723E+09 | 0.00 | 0.303723E+09 | 0.147639E+09 | 0.217289E+10 |
Annual Sum or Average | 0.602125E+10 | 0.230278E+09 | 0.579097E+10 | 0.586954E+10 | 0.182265E+11 |
Minimum of Months | 0.303723E+09 | 0.00 | 0.303723E+09 | 0.147639E+09 | 0.928111E+09 |
Maximum of Months | 0.735188E+09 | 88748988.28 | 0.662469E+09 | 0.987700E+09 | 0.217289E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.982832E+09 | 0.527944E+09 | 0.454888E+09 | 0.140284E+10 | 0.212496E+10 |
February | 0.932013E+09 | 0.427112E+09 | 0.504901E+09 | 0.121179E+10 | 0.180908E+10 |
March | 0.124650E+10 | 0.551738E+09 | 0.694760E+09 | 0.173078E+10 | 0.203390E+10 |
April | 0.154503E+10 | 0.772222E+09 | 0.772810E+09 | 0.259233E+10 | 0.152327E+10 |
May | 0.150781E+10 | 0.626892E+09 | 0.880915E+09 | 0.239085E+10 | 0.141814E+10 |
June | 0.145348E+10 | 0.630366E+09 | 0.823113E+09 | 0.256247E+10 | 0.106459E+10 |
July | 0.169961E+10 | 0.843200E+09 | 0.856414E+09 | 0.330949E+10 | 0.978173E+09 |
August | 0.167576E+10 | 0.887550E+09 | 0.788214E+09 | 0.331168E+10 | 0.100320E+10 |
September | 0.118533E+10 | 0.543568E+09 | 0.641759E+09 | 0.218751E+10 | 0.112609E+10 |
October | 0.108269E+10 | 0.556070E+09 | 0.526619E+09 | 0.203684E+10 | 0.130050E+10 |
November | 0.958814E+09 | 0.488554E+09 | 0.470260E+09 | 0.136947E+10 | 0.186548E+10 |
December | 0.949471E+09 | 0.530723E+09 | 0.418749E+09 | 0.134961E+10 | 0.211657E+10 |
Annual Sum or Average | 0.152193E+11 | 0.738594E+10 | 0.783340E+10 | 0.254557E+11 | 0.183640E+11 |
Minimum of Months | 0.932013E+09 | 0.427112E+09 | 0.418749E+09 | 0.121179E+10 | 0.978173E+09 |
Maximum of Months | 0.169961E+10 | 0.887550E+09 | 0.880915E+09 | 0.331168E+10 | 0.212496E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.982832E+09 | 0.527944E+09 | 0.454888E+09 | 0.140284E+10 | 0.212496E+10 |
February | 0.932013E+09 | 0.427112E+09 | 0.504901E+09 | 0.121179E+10 | 0.180908E+10 |
March | 0.124650E+10 | 0.551738E+09 | 0.694760E+09 | 0.173078E+10 | 0.203390E+10 |
April | 0.154503E+10 | 0.772222E+09 | 0.772810E+09 | 0.259233E+10 | 0.152327E+10 |
May | 0.150781E+10 | 0.626892E+09 | 0.880915E+09 | 0.239085E+10 | 0.141814E+10 |
June | 0.145348E+10 | 0.630366E+09 | 0.823113E+09 | 0.256247E+10 | 0.106459E+10 |
July | 0.169961E+10 | 0.843200E+09 | 0.856414E+09 | 0.330949E+10 | 0.978173E+09 |
August | 0.167576E+10 | 0.887550E+09 | 0.788214E+09 | 0.331168E+10 | 0.100320E+10 |
September | 0.118533E+10 | 0.543568E+09 | 0.641759E+09 | 0.218751E+10 | 0.112609E+10 |
October | 0.108269E+10 | 0.556070E+09 | 0.526619E+09 | 0.203684E+10 | 0.130050E+10 |
November | 0.958814E+09 | 0.488554E+09 | 0.470260E+09 | 0.136947E+10 | 0.186548E+10 |
December | 0.949471E+09 | 0.530723E+09 | 0.418749E+09 | 0.134961E+10 | 0.211657E+10 |
Annual Sum or Average | 0.152193E+11 | 0.738594E+10 | 0.783340E+10 | 0.254557E+11 | 0.183640E+11 |
Minimum of Months | 0.932013E+09 | 0.427112E+09 | 0.418749E+09 | 0.121179E+10 | 0.978173E+09 |
Maximum of Months | 0.169961E+10 | 0.887550E+09 | 0.880915E+09 | 0.331168E+10 | 0.212496E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.982815E+09 | 0.527934E+09 | 0.454880E+09 | 0.140282E+10 | 0.212492E+10 |
February | 0.931996E+09 | 0.427104E+09 | 0.504892E+09 | 0.121177E+10 | 0.180904E+10 |
March | 0.124648E+10 | 0.551728E+09 | 0.694747E+09 | 0.173075E+10 | 0.203387E+10 |
April | 0.154500E+10 | 0.772208E+09 | 0.772796E+09 | 0.259228E+10 | 0.152325E+10 |
May | 0.150778E+10 | 0.626880E+09 | 0.880899E+09 | 0.239081E+10 | 0.141811E+10 |
June | 0.145345E+10 | 0.630354E+09 | 0.823098E+09 | 0.256242E+10 | 0.106457E+10 |
July | 0.169958E+10 | 0.843184E+09 | 0.856398E+09 | 0.330943E+10 | 0.978155E+09 |
August | 0.167573E+10 | 0.887533E+09 | 0.788199E+09 | 0.331162E+10 | 0.100318E+10 |
September | 0.118531E+10 | 0.543558E+09 | 0.641748E+09 | 0.218747E+10 | 0.112607E+10 |
October | 0.108267E+10 | 0.556060E+09 | 0.526609E+09 | 0.203680E+10 | 0.130048E+10 |
November | 0.958796E+09 | 0.488545E+09 | 0.470251E+09 | 0.136945E+10 | 0.186544E+10 |
December | 0.949454E+09 | 0.530713E+09 | 0.418741E+09 | 0.134958E+10 | 0.211653E+10 |
Annual Sum or Average | 0.152191E+11 | 0.738580E+10 | 0.783326E+10 | 0.254552E+11 | 0.183636E+11 |
Minimum of Months | 0.931996E+09 | 0.427104E+09 | 0.418741E+09 | 0.121177E+10 | 0.978155E+09 |
Maximum of Months | 0.169958E+10 | 0.887533E+09 | 0.880899E+09 | 0.331162E+10 | 0.212492E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.210827E+10 | 0.153454E+10 | 0.573728E+09 | 0.394454E+10 | 0.193219E+10 |
February | 0.152188E+10 | 0.934844E+09 | 0.587034E+09 | 0.254330E+10 | 0.165439E+10 |
March | 0.138225E+10 | 0.684805E+09 | 0.697449E+09 | 0.225238E+10 | 0.192863E+10 |
April | 0.116936E+10 | 0.494437E+09 | 0.674922E+09 | 0.204703E+10 | 0.150388E+10 |
May | 0.843328E+09 | 0.139420E+09 | 0.703908E+09 | 0.114896E+10 | 0.138080E+10 |
June | 0.705761E+09 | 65448260.00 | 0.640313E+09 | 0.100278E+10 | 0.101748E+10 |
July | 0.786468E+09 | 0.124524E+09 | 0.661943E+09 | 0.135314E+10 | 0.935968E+09 |
August | 0.103373E+10 | 0.377723E+09 | 0.656004E+09 | 0.205258E+10 | 0.999913E+09 |
September | 0.134900E+10 | 0.712484E+09 | 0.636521E+09 | 0.272716E+10 | 0.109634E+10 |
October | 0.170318E+10 | 0.114106E+10 | 0.562117E+09 | 0.354097E+10 | 0.125142E+10 |
November | 0.196323E+10 | 0.137678E+10 | 0.586446E+09 | 0.361670E+10 | 0.172877E+10 |
December | 0.224659E+10 | 0.169712E+10 | 0.549472E+09 | 0.421876E+10 | 0.195881E+10 |
Annual Sum or Average | 0.168130E+11 | 0.928319E+10 | 0.752986E+10 | 0.304483E+11 | 0.173886E+11 |
Minimum of Months | 0.705761E+09 | 65448260.00 | 0.549472E+09 | 0.100278E+10 | 0.935968E+09 |
Maximum of Months | 0.224659E+10 | 0.169712E+10 | 0.703908E+09 | 0.421876E+10 | 0.195881E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.210827E+10 | 0.153454E+10 | 0.573727E+09 | 0.394454E+10 | 0.193219E+10 |
February | 0.152188E+10 | 0.934843E+09 | 0.587034E+09 | 0.254329E+10 | 0.165439E+10 |
March | 0.138225E+10 | 0.684804E+09 | 0.697448E+09 | 0.225237E+10 | 0.192863E+10 |
April | 0.116936E+10 | 0.494436E+09 | 0.674922E+09 | 0.204703E+10 | 0.150388E+10 |
May | 0.843327E+09 | 0.139420E+09 | 0.703907E+09 | 0.114896E+10 | 0.138080E+10 |
June | 0.705761E+09 | 65448181.46 | 0.640313E+09 | 0.100278E+10 | 0.101748E+10 |
July | 0.786467E+09 | 0.124524E+09 | 0.661943E+09 | 0.135314E+10 | 0.935968E+09 |
August | 0.103373E+10 | 0.377722E+09 | 0.656003E+09 | 0.205258E+10 | 0.999913E+09 |
September | 0.134900E+10 | 0.712483E+09 | 0.636520E+09 | 0.272715E+10 | 0.109634E+10 |
October | 0.170318E+10 | 0.114106E+10 | 0.562117E+09 | 0.354097E+10 | 0.125142E+10 |
November | 0.196322E+10 | 0.137678E+10 | 0.586446E+09 | 0.361670E+10 | 0.172877E+10 |
December | 0.224659E+10 | 0.169711E+10 | 0.549472E+09 | 0.421875E+10 | 0.195881E+10 |
Annual Sum or Average | 0.168130E+11 | 0.928318E+10 | 0.752985E+10 | 0.304483E+11 | 0.173886E+11 |
Minimum of Months | 0.705761E+09 | 65448181.46 | 0.549472E+09 | 0.100278E+10 | 0.935968E+09 |
Maximum of Months | 0.224659E+10 | 0.169711E+10 | 0.703907E+09 | 0.421875E+10 | 0.195881E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.210827E+10 | 0.153454E+10 | 0.573728E+09 | 0.394454E+10 | 0.193219E+10 |
February | 0.152188E+10 | 0.934844E+09 | 0.587034E+09 | 0.254330E+10 | 0.165439E+10 |
March | 0.138225E+10 | 0.684805E+09 | 0.697449E+09 | 0.225238E+10 | 0.192863E+10 |
April | 0.116936E+10 | 0.494437E+09 | 0.674922E+09 | 0.204703E+10 | 0.150388E+10 |
May | 0.843328E+09 | 0.139420E+09 | 0.703908E+09 | 0.114896E+10 | 0.138080E+10 |
June | 0.705761E+09 | 65448260.00 | 0.640313E+09 | 0.100278E+10 | 0.101748E+10 |
July | 0.786468E+09 | 0.124524E+09 | 0.661943E+09 | 0.135314E+10 | 0.935968E+09 |
August | 0.103373E+10 | 0.377723E+09 | 0.656004E+09 | 0.205258E+10 | 0.999913E+09 |
September | 0.134900E+10 | 0.712484E+09 | 0.636521E+09 | 0.272716E+10 | 0.109634E+10 |
October | 0.170318E+10 | 0.114106E+10 | 0.562117E+09 | 0.354097E+10 | 0.125142E+10 |
November | 0.196323E+10 | 0.137678E+10 | 0.586446E+09 | 0.361670E+10 | 0.172877E+10 |
December | 0.224659E+10 | 0.169712E+10 | 0.549472E+09 | 0.421876E+10 | 0.195881E+10 |
Annual Sum or Average | 0.168130E+11 | 0.928319E+10 | 0.752986E+10 | 0.304483E+11 | 0.173886E+11 |
Minimum of Months | 0.705761E+09 | 65448260.00 | 0.549472E+09 | 0.100278E+10 | 0.935968E+09 |
Maximum of Months | 0.224659E+10 | 0.169712E+10 | 0.703908E+09 | 0.421876E+10 | 0.195881E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.210827E+10 | 0.153454E+10 | 0.573727E+09 | 0.394454E+10 | 0.193219E+10 |
February | 0.152188E+10 | 0.934843E+09 | 0.587034E+09 | 0.254329E+10 | 0.165439E+10 |
March | 0.138225E+10 | 0.684804E+09 | 0.697448E+09 | 0.225237E+10 | 0.192863E+10 |
April | 0.116936E+10 | 0.494436E+09 | 0.674922E+09 | 0.204703E+10 | 0.150388E+10 |
May | 0.843327E+09 | 0.139420E+09 | 0.703907E+09 | 0.114896E+10 | 0.138080E+10 |
June | 0.705761E+09 | 65448181.46 | 0.640313E+09 | 0.100278E+10 | 0.101748E+10 |
July | 0.786467E+09 | 0.124524E+09 | 0.661943E+09 | 0.135314E+10 | 0.935968E+09 |
August | 0.103373E+10 | 0.377722E+09 | 0.656003E+09 | 0.205258E+10 | 0.999913E+09 |
September | 0.134900E+10 | 0.712483E+09 | 0.636520E+09 | 0.272715E+10 | 0.109634E+10 |
October | 0.170318E+10 | 0.114106E+10 | 0.562117E+09 | 0.354097E+10 | 0.125142E+10 |
November | 0.196322E+10 | 0.137678E+10 | 0.586446E+09 | 0.361670E+10 | 0.172877E+10 |
December | 0.224659E+10 | 0.169711E+10 | 0.549472E+09 | 0.421875E+10 | 0.195881E+10 |
Annual Sum or Average | 0.168130E+11 | 0.928318E+10 | 0.752985E+10 | 0.304483E+11 | 0.173886E+11 |
Minimum of Months | 0.705761E+09 | 65448181.46 | 0.549472E+09 | 0.100278E+10 | 0.935968E+09 |
Maximum of Months | 0.224659E+10 | 0.169711E+10 | 0.703907E+09 | 0.421875E+10 | 0.195881E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.210819E+10 | 0.153448E+10 | 0.573704E+09 | 0.394438E+10 | 0.193211E+10 |
February | 0.152182E+10 | 0.934807E+09 | 0.587010E+09 | 0.254319E+10 | 0.165433E+10 |
March | 0.138220E+10 | 0.684777E+09 | 0.697421E+09 | 0.225229E+10 | 0.192855E+10 |
April | 0.116931E+10 | 0.494417E+09 | 0.674895E+09 | 0.204695E+10 | 0.150382E+10 |
May | 0.843294E+09 | 0.139414E+09 | 0.703879E+09 | 0.114891E+10 | 0.138074E+10 |
June | 0.705733E+09 | 65445622.14 | 0.640287E+09 | 0.100274E+10 | 0.101744E+10 |
July | 0.786436E+09 | 0.124519E+09 | 0.661917E+09 | 0.135309E+10 | 0.935931E+09 |
August | 0.103368E+10 | 0.377707E+09 | 0.655977E+09 | 0.205250E+10 | 0.999873E+09 |
September | 0.134895E+10 | 0.712455E+09 | 0.636495E+09 | 0.272705E+10 | 0.109629E+10 |
October | 0.170311E+10 | 0.114102E+10 | 0.562094E+09 | 0.354083E+10 | 0.125137E+10 |
November | 0.196315E+10 | 0.137672E+10 | 0.586422E+09 | 0.361656E+10 | 0.172870E+10 |
December | 0.224650E+10 | 0.169705E+10 | 0.549450E+09 | 0.421859E+10 | 0.195873E+10 |
Annual Sum or Average | 0.168124E+11 | 0.928281E+10 | 0.752955E+10 | 0.304471E+11 | 0.173879E+11 |
Minimum of Months | 0.705733E+09 | 65445622.14 | 0.549450E+09 | 0.100274E+10 | 0.935931E+09 |
Maximum of Months | 0.224650E+10 | 0.169705E+10 | 0.703879E+09 | 0.421859E+10 | 0.195873E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.936816E+09 | 0.475482E+09 | 0.461334E+09 | 0.137621E+10 | 0.238810E+10 |
February | 0.100046E+10 | 0.460519E+09 | 0.539946E+09 | 0.135951E+10 | 0.206067E+10 |
March | 0.126715E+10 | 0.557439E+09 | 0.709713E+09 | 0.173246E+10 | 0.236883E+10 |
April | 0.168963E+10 | 0.875741E+09 | 0.813888E+09 | 0.274119E+10 | 0.190695E+10 |
May | 0.171575E+10 | 0.788254E+09 | 0.927494E+09 | 0.271496E+10 | 0.164471E+10 |
June | 0.175753E+10 | 0.873939E+09 | 0.883586E+09 | 0.302476E+10 | 0.127023E+10 |
July | 0.192295E+10 | 0.102429E+10 | 0.898657E+09 | 0.354459E+10 | 0.126550E+10 |
August | 0.180372E+10 | 0.973059E+09 | 0.830662E+09 | 0.335365E+10 | 0.137848E+10 |
September | 0.149479E+10 | 0.796201E+09 | 0.698586E+09 | 0.272672E+10 | 0.132698E+10 |
October | 0.118493E+10 | 0.645993E+09 | 0.538933E+09 | 0.223309E+10 | 0.155164E+10 |
November | 0.104011E+10 | 0.545249E+09 | 0.494862E+09 | 0.156001E+10 | 0.219699E+10 |
December | 0.953318E+09 | 0.514280E+09 | 0.439039E+09 | 0.140219E+10 | 0.257321E+10 |
Annual Sum or Average | 0.167671E+11 | 0.853045E+10 | 0.823670E+10 | 0.277693E+11 | 0.219323E+11 |
Minimum of Months | 0.936816E+09 | 0.460519E+09 | 0.439039E+09 | 0.135951E+10 | 0.126550E+10 |
Maximum of Months | 0.192295E+10 | 0.102429E+10 | 0.927494E+09 | 0.354459E+10 | 0.257321E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.936816E+09 | 0.475482E+09 | 0.461334E+09 | 0.137621E+10 | 0.238810E+10 |
February | 0.100046E+10 | 0.460519E+09 | 0.539946E+09 | 0.135951E+10 | 0.206067E+10 |
March | 0.126715E+10 | 0.557439E+09 | 0.709713E+09 | 0.173246E+10 | 0.236883E+10 |
April | 0.168963E+10 | 0.875741E+09 | 0.813888E+09 | 0.274119E+10 | 0.190695E+10 |
May | 0.171575E+10 | 0.788254E+09 | 0.927494E+09 | 0.271496E+10 | 0.164471E+10 |
June | 0.175753E+10 | 0.873939E+09 | 0.883586E+09 | 0.302476E+10 | 0.127023E+10 |
July | 0.192295E+10 | 0.102429E+10 | 0.898657E+09 | 0.354459E+10 | 0.126550E+10 |
August | 0.180372E+10 | 0.973059E+09 | 0.830662E+09 | 0.335365E+10 | 0.137848E+10 |
September | 0.149479E+10 | 0.796201E+09 | 0.698586E+09 | 0.272672E+10 | 0.132698E+10 |
October | 0.118493E+10 | 0.645993E+09 | 0.538933E+09 | 0.223309E+10 | 0.155164E+10 |
November | 0.104011E+10 | 0.545249E+09 | 0.494862E+09 | 0.156001E+10 | 0.219699E+10 |
December | 0.953318E+09 | 0.514280E+09 | 0.439039E+09 | 0.140219E+10 | 0.257321E+10 |
Annual Sum or Average | 0.167671E+11 | 0.853045E+10 | 0.823670E+10 | 0.277693E+11 | 0.219323E+11 |
Minimum of Months | 0.936816E+09 | 0.460519E+09 | 0.439039E+09 | 0.135951E+10 | 0.126550E+10 |
Maximum of Months | 0.192295E+10 | 0.102429E+10 | 0.927494E+09 | 0.354459E+10 | 0.257321E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.936799E+09 | 0.475474E+09 | 0.461325E+09 | 0.137618E+10 | 0.238806E+10 |
February | 0.100045E+10 | 0.460510E+09 | 0.539936E+09 | 0.135949E+10 | 0.206063E+10 |
March | 0.126713E+10 | 0.557429E+09 | 0.709700E+09 | 0.173243E+10 | 0.236879E+10 |
April | 0.168960E+10 | 0.875725E+09 | 0.813873E+09 | 0.274114E+10 | 0.190691E+10 |
May | 0.171572E+10 | 0.788240E+09 | 0.927477E+09 | 0.271491E+10 | 0.164468E+10 |
June | 0.175749E+10 | 0.873923E+09 | 0.883570E+09 | 0.302471E+10 | 0.127021E+10 |
July | 0.192291E+10 | 0.102427E+10 | 0.898641E+09 | 0.354453E+10 | 0.126548E+10 |
August | 0.180369E+10 | 0.973041E+09 | 0.830647E+09 | 0.335359E+10 | 0.137846E+10 |
September | 0.149476E+10 | 0.796186E+09 | 0.698573E+09 | 0.272667E+10 | 0.132695E+10 |
October | 0.118490E+10 | 0.645981E+09 | 0.538923E+09 | 0.223304E+10 | 0.155162E+10 |
November | 0.104009E+10 | 0.545239E+09 | 0.494853E+09 | 0.155999E+10 | 0.219695E+10 |
December | 0.953301E+09 | 0.514270E+09 | 0.439031E+09 | 0.140216E+10 | 0.257316E+10 |
Annual Sum or Average | 0.167668E+11 | 0.853029E+10 | 0.823655E+10 | 0.277688E+11 | 0.219319E+11 |
Minimum of Months | 0.936799E+09 | 0.460510E+09 | 0.439031E+09 | 0.135949E+10 | 0.126548E+10 |
Maximum of Months | 0.192291E+10 | 0.102427E+10 | 0.927477E+09 | 0.354453E+10 | 0.257316E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163136E+10 | 0.00 | 0.163136E+10 | 0.108906E+10 | 0.949673E+10 |
February | 0.184962E+10 | 0.00 | 0.184962E+10 | 0.108001E+10 | 0.803790E+10 |
March | 0.250941E+10 | 0.00 | 0.250941E+10 | 0.175258E+10 | 0.921325E+10 |
April | 0.280494E+10 | 17838715.43 | 0.278710E+10 | 0.256371E+10 | 0.678111E+10 |
May | 0.353083E+10 | 0.218391E+09 | 0.331244E+10 | 0.336887E+10 | 0.614176E+10 |
June | 0.367604E+10 | 0.443757E+09 | 0.323229E+10 | 0.430400E+10 | 0.460579E+10 |
July | 0.359580E+10 | 0.384418E+09 | 0.321138E+10 | 0.501714E+10 | 0.417785E+10 |
August | 0.293892E+10 | 86278732.10 | 0.285264E+10 | 0.400812E+10 | 0.439806E+10 |
September | 0.238469E+10 | 736900.75 | 0.238395E+10 | 0.295861E+10 | 0.506203E+10 |
October | 0.195437E+10 | 0.00 | 0.195437E+10 | 0.285988E+10 | 0.587948E+10 |
November | 0.171246E+10 | 0.00 | 0.171246E+10 | 0.122132E+10 | 0.832493E+10 |
December | 0.151866E+10 | 0.00 | 0.151866E+10 | 0.104290E+10 | 0.950820E+10 |
Annual Sum or Average | 0.301071E+11 | 0.115142E+10 | 0.289557E+11 | 0.312662E+11 | 0.816271E+11 |
Minimum of Months | 0.151866E+10 | 0.00 | 0.151866E+10 | 0.104290E+10 | 0.417785E+10 |
Maximum of Months | 0.367604E+10 | 0.443757E+09 | 0.331244E+10 | 0.501714E+10 | 0.950820E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294847E+10 | 0.158382E+10 | 0.136465E+10 | 0.418993E+10 | 0.595325E+10 |
February | 0.279601E+10 | 0.128132E+10 | 0.151469E+10 | 0.353545E+10 | 0.507015E+10 |
March | 0.373946E+10 | 0.165520E+10 | 0.208426E+10 | 0.507237E+10 | 0.578119E+10 |
April | 0.463505E+10 | 0.231664E+10 | 0.231841E+10 | 0.759785E+10 | 0.430258E+10 |
May | 0.452337E+10 | 0.188066E+10 | 0.264272E+10 | 0.695978E+10 | 0.404818E+10 |
June | 0.436039E+10 | 0.189108E+10 | 0.246931E+10 | 0.749462E+10 | 0.300519E+10 |
July | 0.509879E+10 | 0.252957E+10 | 0.256922E+10 | 0.973298E+10 | 0.272289E+10 |
August | 0.502724E+10 | 0.266262E+10 | 0.236462E+10 | 0.973371E+10 | 0.280393E+10 |
September | 0.355595E+10 | 0.163069E+10 | 0.192526E+10 | 0.643737E+10 | 0.314415E+10 |
October | 0.324803E+10 | 0.166819E+10 | 0.157984E+10 | 0.598521E+10 | 0.363574E+10 |
November | 0.287641E+10 | 0.146565E+10 | 0.141076E+10 | 0.404536E+10 | 0.522561E+10 |
December | 0.284839E+10 | 0.159215E+10 | 0.125623E+10 | 0.402899E+10 | 0.593986E+10 |
Annual Sum or Average | 0.456576E+11 | 0.221576E+11 | 0.235000E+11 | 0.748136E+11 | 0.516327E+11 |
Minimum of Months | 0.279601E+10 | 0.128132E+10 | 0.125623E+10 | 0.353545E+10 | 0.272289E+10 |
Maximum of Months | 0.509879E+10 | 0.266262E+10 | 0.264272E+10 | 0.973371E+10 | 0.595325E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.105412E+11 | 0.767263E+10 | 0.286860E+10 | 0.193148E+11 | 0.947740E+10 |
February | 0.760930E+10 | 0.467417E+10 | 0.293514E+10 | 0.122578E+11 | 0.804032E+10 |
March | 0.691119E+10 | 0.342398E+10 | 0.348720E+10 | 0.109828E+11 | 0.932420E+10 |
April | 0.584672E+10 | 0.247215E+10 | 0.337457E+10 | 0.100365E+11 | 0.712744E+10 |
May | 0.421659E+10 | 0.697091E+09 | 0.351950E+10 | 0.560708E+10 | 0.662152E+10 |
June | 0.352876E+10 | 0.327237E+09 | 0.320153E+10 | 0.500073E+10 | 0.476658E+10 |
July | 0.393229E+10 | 0.622615E+09 | 0.330968E+10 | 0.681340E+10 | 0.425916E+10 |
August | 0.516857E+10 | 0.188859E+10 | 0.327998E+10 | 0.101884E+11 | 0.458589E+10 |
September | 0.674494E+10 | 0.356237E+10 | 0.318257E+10 | 0.133327E+11 | 0.527272E+10 |
October | 0.851579E+10 | 0.570524E+10 | 0.281055E+10 | 0.172857E+11 | 0.609239E+10 |
November | 0.981601E+10 | 0.688382E+10 | 0.293219E+10 | 0.176052E+11 | 0.839210E+10 |
December | 0.112328E+11 | 0.848548E+10 | 0.274733E+10 | 0.206156E+11 | 0.949648E+10 |
Annual Sum or Average | 0.840642E+11 | 0.464154E+11 | 0.376488E+11 | 0.149041E+12 | 0.834562E+11 |
Minimum of Months | 0.352876E+10 | 0.327237E+09 | 0.274733E+10 | 0.500073E+10 | 0.425916E+10 |
Maximum of Months | 0.112328E+11 | 0.848548E+10 | 0.351950E+10 | 0.206156E+11 | 0.949648E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.281042E+10 | 0.142643E+10 | 0.138399E+10 | 0.420839E+10 | 0.634785E+10 |
February | 0.300136E+10 | 0.138154E+10 | 0.161982E+10 | 0.411624E+10 | 0.542989E+10 |
March | 0.380142E+10 | 0.167230E+10 | 0.212912E+10 | 0.530648E+10 | 0.617822E+10 |
April | 0.506883E+10 | 0.262719E+10 | 0.244164E+10 | 0.830326E+10 | 0.484470E+10 |
May | 0.514719E+10 | 0.236474E+10 | 0.278245E+10 | 0.802027E+10 | 0.450309E+10 |
June | 0.527252E+10 | 0.262179E+10 | 0.265073E+10 | 0.896792E+10 | 0.336751E+10 |
July | 0.576878E+10 | 0.307284E+10 | 0.269594E+10 | 0.107013E+11 | 0.315693E+10 |
August | 0.541111E+10 | 0.291915E+10 | 0.249196E+10 | 0.102132E+11 | 0.327805E+10 |
September | 0.448431E+10 | 0.238858E+10 | 0.209574E+10 | 0.810195E+10 | 0.352979E+10 |
October | 0.355474E+10 | 0.193796E+10 | 0.161678E+10 | 0.676733E+10 | 0.402991E+10 |
November | 0.312030E+10 | 0.163573E+10 | 0.148457E+10 | 0.482064E+10 | 0.560833E+10 |
December | 0.285993E+10 | 0.154282E+10 | 0.131710E+10 | 0.444340E+10 | 0.641638E+10 |
Annual Sum or Average | 0.503009E+11 | 0.255911E+11 | 0.247098E+11 | 0.839704E+11 | 0.566906E+11 |
Minimum of Months | 0.281042E+10 | 0.138154E+10 | 0.131710E+10 | 0.411624E+10 | 0.315693E+10 |
Maximum of Months | 0.576878E+10 | 0.307284E+10 | 0.278245E+10 | 0.107013E+11 | 0.641638E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163136E+10 | 0.00 | 0.163136E+10 | 0.126555E+10 | 0.850968E+10 |
February | 0.184962E+10 | 0.00 | 0.184962E+10 | 0.122462E+10 | 0.722200E+10 |
March | 0.250941E+10 | 0.00 | 0.250941E+10 | 0.188064E+10 | 0.848570E+10 |
April | 0.280494E+10 | 17838715.43 | 0.278710E+10 | 0.257195E+10 | 0.633473E+10 |
May | 0.353083E+10 | 0.218391E+09 | 0.331244E+10 | 0.339420E+10 | 0.573143E+10 |
June | 0.367604E+10 | 0.443757E+09 | 0.323229E+10 | 0.423988E+10 | 0.432997E+10 |
July | 0.359580E+10 | 0.384418E+09 | 0.321138E+10 | 0.488583E+10 | 0.397752E+10 |
August | 0.293892E+10 | 86278732.10 | 0.285264E+10 | 0.392150E+10 | 0.415354E+10 |
September | 0.238469E+10 | 736900.75 | 0.238395E+10 | 0.297715E+10 | 0.467387E+10 |
October | 0.195437E+10 | 0.00 | 0.195437E+10 | 0.296628E+10 | 0.532064E+10 |
November | 0.171246E+10 | 0.00 | 0.171246E+10 | 0.139889E+10 | 0.745200E+10 |
December | 0.151866E+10 | 0.00 | 0.151866E+10 | 0.123814E+10 | 0.848022E+10 |
Annual Sum or Average | 0.301071E+11 | 0.115142E+10 | 0.289557E+11 | 0.319646E+11 | 0.746713E+11 |
Minimum of Months | 0.151866E+10 | 0.00 | 0.151866E+10 | 0.122462E+10 | 0.397752E+10 |
Maximum of Months | 0.367604E+10 | 0.443757E+09 | 0.331244E+10 | 0.488583E+10 | 0.850968E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294847E+10 | 0.158382E+10 | 0.136465E+10 | 0.441664E+10 | 0.535241E+10 |
February | 0.279601E+10 | 0.128132E+10 | 0.151469E+10 | 0.367795E+10 | 0.458979E+10 |
March | 0.373946E+10 | 0.165520E+10 | 0.208426E+10 | 0.520670E+10 | 0.536371E+10 |
April | 0.463505E+10 | 0.231664E+10 | 0.231841E+10 | 0.759325E+10 | 0.408038E+10 |
May | 0.452337E+10 | 0.188066E+10 | 0.264272E+10 | 0.697832E+10 | 0.385489E+10 |
June | 0.436039E+10 | 0.189108E+10 | 0.246931E+10 | 0.745111E+10 | 0.289662E+10 |
July | 0.509879E+10 | 0.252957E+10 | 0.256922E+10 | 0.961006E+10 | 0.266209E+10 |
August | 0.502724E+10 | 0.266262E+10 | 0.236462E+10 | 0.962902E+10 | 0.272091E+10 |
September | 0.355595E+10 | 0.163069E+10 | 0.192526E+10 | 0.643451E+10 | 0.296851E+10 |
October | 0.324803E+10 | 0.166819E+10 | 0.157984E+10 | 0.605034E+10 | 0.336782E+10 |
November | 0.287641E+10 | 0.146565E+10 | 0.141076E+10 | 0.423242E+10 | 0.471933E+10 |
December | 0.284839E+10 | 0.159215E+10 | 0.125623E+10 | 0.426575E+10 | 0.531987E+10 |
Annual Sum or Average | 0.456576E+11 | 0.221576E+11 | 0.235000E+11 | 0.755461E+11 | 0.478963E+11 |
Minimum of Months | 0.279601E+10 | 0.128132E+10 | 0.125623E+10 | 0.367795E+10 | 0.266209E+10 |
Maximum of Months | 0.509879E+10 | 0.266262E+10 | 0.264272E+10 | 0.962902E+10 | 0.536371E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.105412E+11 | 0.767263E+10 | 0.286860E+10 | 0.194275E+11 | 0.862101E+10 |
February | 0.760930E+10 | 0.467417E+10 | 0.293514E+10 | 0.122799E+11 | 0.731467E+10 |
March | 0.691119E+10 | 0.342398E+10 | 0.348720E+10 | 0.110178E+11 | 0.865431E+10 |
April | 0.584672E+10 | 0.247215E+10 | 0.337457E+10 | 0.995106E+10 | 0.671513E+10 |
May | 0.421659E+10 | 0.697091E+09 | 0.351950E+10 | 0.553594E+10 | 0.626176E+10 |
June | 0.352876E+10 | 0.327237E+09 | 0.320153E+10 | 0.489542E+10 | 0.454925E+10 |
July | 0.393229E+10 | 0.622615E+09 | 0.330968E+10 | 0.665193E+10 | 0.411197E+10 |
August | 0.516857E+10 | 0.188859E+10 | 0.327998E+10 | 0.100273E+11 | 0.438800E+10 |
September | 0.674494E+10 | 0.356237E+10 | 0.318257E+10 | 0.132305E+11 | 0.493722E+10 |
October | 0.851579E+10 | 0.570524E+10 | 0.281055E+10 | 0.172453E+11 | 0.561868E+10 |
November | 0.981601E+10 | 0.688382E+10 | 0.293219E+10 | 0.176367E+11 | 0.765110E+10 |
December | 0.112328E+11 | 0.848548E+10 | 0.274733E+10 | 0.207151E+11 | 0.863473E+10 |
Annual Sum or Average | 0.840642E+11 | 0.464154E+11 | 0.376488E+11 | 0.148615E+12 | 0.774578E+11 |
Minimum of Months | 0.352876E+10 | 0.327237E+09 | 0.274733E+10 | 0.489542E+10 | 0.411197E+10 |
Maximum of Months | 0.112328E+11 | 0.848548E+10 | 0.351950E+10 | 0.207151E+11 | 0.865431E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.281042E+10 | 0.142643E+10 | 0.138399E+10 | 0.418962E+10 | 0.585373E+10 |
February | 0.300136E+10 | 0.138154E+10 | 0.161982E+10 | 0.407549E+10 | 0.502243E+10 |
March | 0.380142E+10 | 0.167230E+10 | 0.212912E+10 | 0.523268E+10 | 0.580245E+10 |
April | 0.506883E+10 | 0.262719E+10 | 0.244164E+10 | 0.813105E+10 | 0.459307E+10 |
May | 0.514719E+10 | 0.236474E+10 | 0.278245E+10 | 0.784430E+10 | 0.427756E+10 |
June | 0.527252E+10 | 0.262179E+10 | 0.265073E+10 | 0.876079E+10 | 0.321775E+10 |
July | 0.576878E+10 | 0.307284E+10 | 0.269594E+10 | 0.104635E+11 | 0.304395E+10 |
August | 0.541111E+10 | 0.291915E+10 | 0.249196E+10 | 0.999448E+10 | 0.315219E+10 |
September | 0.448431E+10 | 0.238858E+10 | 0.209574E+10 | 0.795873E+10 | 0.333868E+10 |
October | 0.355474E+10 | 0.193796E+10 | 0.161678E+10 | 0.668915E+10 | 0.376655E+10 |
November | 0.312030E+10 | 0.163573E+10 | 0.148457E+10 | 0.478485E+10 | 0.517733E+10 |
December | 0.285993E+10 | 0.154282E+10 | 0.131710E+10 | 0.443787E+10 | 0.590438E+10 |
Annual Sum or Average | 0.503009E+11 | 0.255911E+11 | 0.247098E+11 | 0.825625E+11 | 0.531501E+11 |
Minimum of Months | 0.281042E+10 | 0.138154E+10 | 0.131710E+10 | 0.407549E+10 | 0.304395E+10 |
Maximum of Months | 0.576878E+10 | 0.307284E+10 | 0.278245E+10 | 0.104635E+11 | 0.590438E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 323.38 | 3979.55 | 609.08 | 0.00 | 609.08 | 0.00 | 0.00 |
February | 369.13 | 3719.74 | 764.56 | 0.00 | 764.56 | 0.00 | 0.00 |
March | 573.02 | 3804.05 | 936.91 | 0.00 | 936.91 | 0.00 | 0.00 |
April | 911.35 | 2932.63 | 1082.16 | 6.88 | 1075.28 | 0.00 | 0.00 |
May | 1218.41 | 2476.73 | 1318.27 | 81.54 | 1236.73 | 0.00 | 0.00 |
June | 1675.74 | 1920.17 | 1418.23 | 171.20 | 1247.03 | 0.00 | 0.00 |
July | 1843.88 | 1732.64 | 1342.52 | 143.53 | 1199.00 | 0.00 | 0.00 |
August | 1446.16 | 1859.42 | 1097.27 | 32.21 | 1065.06 | 0.00 | 0.00 |
September | 1108.75 | 2161.29 | 920.02 | 0.28 | 919.74 | 0.00 | 0.00 |
October | 1006.28 | 2443.82 | 729.68 | 0.00 | 729.68 | 0.00 | 0.00 |
November | 372.76 | 3643.35 | 660.67 | 0.00 | 660.67 | 0.00 | 0.00 |
December | 275.62 | 4056.44 | 567.00 | 0.00 | 567.00 | 0.00 | 0.00 |
Annual Sum or Average | 930.64 | 2889.89 | 954.69 | 36.51 | 918.18 | 0.00 | 0.00 |
Minimum of Months | 275.62 | 1732.64 | 567.00 | 0.00 | 567.00 | 0.00 | 0.00 |
Maximum of Months | 1843.88 | 4056.44 | 1418.23 | 171.20 | 1247.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1571.28 | 2380.10 | 1100.84 | 591.33 | 509.50 | 0.00 | 0.00 |
February | 1502.71 | 2243.38 | 1155.76 | 529.65 | 626.11 | 0.00 | 0.00 |
March | 1938.59 | 2278.10 | 1396.16 | 617.98 | 778.18 | 0.00 | 0.00 |
April | 3000.36 | 1763.04 | 1788.22 | 893.77 | 894.45 | 0.00 | 0.00 |
May | 2677.91 | 1588.41 | 1688.84 | 702.16 | 986.68 | 0.00 | 0.00 |
June | 2965.80 | 1232.15 | 1682.26 | 729.59 | 952.67 | 0.00 | 0.00 |
July | 3706.85 | 1095.62 | 1903.68 | 944.44 | 959.24 | 0.00 | 0.00 |
August | 3709.30 | 1123.65 | 1876.96 | 994.11 | 882.85 | 0.00 | 0.00 |
September | 2531.82 | 1303.34 | 1371.90 | 629.13 | 742.77 | 0.00 | 0.00 |
October | 2281.39 | 1456.65 | 1212.68 | 622.83 | 589.85 | 0.00 | 0.00 |
November | 1585.03 | 2159.10 | 1109.73 | 565.45 | 544.28 | 0.00 | 0.00 |
December | 1511.65 | 2370.70 | 1063.47 | 594.44 | 469.03 | 0.00 | 0.00 |
Annual Sum or Average | 2421.57 | 1746.94 | 1447.80 | 702.62 | 745.18 | 0.00 | 0.00 |
Minimum of Months | 1502.71 | 1095.62 | 1063.47 | 529.65 | 469.03 | 0.00 | 0.00 |
Maximum of Months | 3709.30 | 2380.10 | 1903.68 | 994.11 | 986.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7363.55 | 3606.96 | 3935.66 | 2864.64 | 1071.02 | 0.00 | 0.00 |
February | 5256.44 | 3419.27 | 3145.39 | 1932.12 | 1213.27 | 0.00 | 0.00 |
March | 4204.67 | 3600.31 | 2580.35 | 1278.37 | 1301.98 | 0.00 | 0.00 |
April | 3948.72 | 2900.97 | 2255.69 | 953.77 | 1301.92 | 0.00 | 0.00 |
May | 2144.84 | 2577.63 | 1574.30 | 260.26 | 1314.03 | 0.00 | 0.00 |
June | 1934.35 | 1962.72 | 1361.41 | 126.25 | 1235.16 | 0.00 | 0.00 |
July | 2526.01 | 1747.24 | 1468.16 | 232.46 | 1235.70 | 0.00 | 0.00 |
August | 3831.70 | 1866.61 | 1929.73 | 705.12 | 1224.61 | 0.00 | 0.00 |
September | 5260.67 | 2114.83 | 2602.22 | 1374.38 | 1227.85 | 0.00 | 0.00 |
October | 6610.18 | 2336.12 | 3179.44 | 2130.10 | 1049.34 | 0.00 | 0.00 |
November | 6976.60 | 3334.80 | 3787.05 | 2655.80 | 1131.25 | 0.00 | 0.00 |
December | 7875.45 | 3656.64 | 4193.86 | 3168.13 | 1025.74 | 0.00 | 0.00 |
Annual Sum or Average | 4827.50 | 2756.92 | 2665.67 | 1471.83 | 1193.84 | 0.00 | 0.00 |
Minimum of Months | 1934.35 | 1747.24 | 1361.41 | 126.25 | 1025.74 | 0.00 | 0.00 |
Maximum of Months | 7875.45 | 3656.64 | 4193.86 | 3168.13 | 1314.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1541.44 | 2674.83 | 1049.29 | 532.57 | 516.72 | 0.00 | 0.00 |
February | 1685.89 | 2555.38 | 1240.65 | 571.08 | 669.57 | 0.00 | 0.00 |
March | 1940.47 | 2653.24 | 1419.29 | 624.37 | 794.92 | 0.00 | 0.00 |
April | 3172.66 | 2207.10 | 1955.58 | 1013.58 | 941.99 | 0.00 | 0.00 |
May | 3040.93 | 1842.18 | 1921.75 | 882.90 | 1038.85 | 0.00 | 0.00 |
June | 3500.86 | 1470.17 | 2034.16 | 1011.50 | 1022.66 | 0.00 | 0.00 |
July | 3970.17 | 1417.44 | 2153.82 | 1147.27 | 1006.55 | 0.00 | 0.00 |
August | 3756.31 | 1543.99 | 2020.28 | 1089.89 | 930.40 | 0.00 | 0.00 |
September | 3155.90 | 1535.84 | 1730.07 | 921.52 | 808.54 | 0.00 | 0.00 |
October | 2501.20 | 1737.94 | 1327.19 | 723.55 | 603.64 | 0.00 | 0.00 |
November | 1805.56 | 2542.80 | 1203.83 | 631.07 | 572.75 | 0.00 | 0.00 |
December | 1570.54 | 2882.16 | 1067.78 | 576.03 | 491.75 | 0.00 | 0.00 |
Annual Sum or Average | 2641.66 | 2086.39 | 1595.04 | 811.49 | 783.55 | 0.00 | 0.00 |
Minimum of Months | 1541.44 | 1417.44 | 1049.29 | 532.57 | 491.75 | 0.00 | 0.00 |
Maximum of Months | 3970.17 | 2882.16 | 2153.82 | 1147.27 | 1038.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 406.61 | 3545.67 | 609.08 | 0.00 | 609.08 | 0.00 | 0.00 |
February | 446.43 | 3322.54 | 764.56 | 0.00 | 764.56 | 0.00 | 0.00 |
March | 654.34 | 3439.84 | 936.91 | 0.00 | 936.91 | 0.00 | 0.00 |
April | 989.09 | 2616.17 | 1082.15 | 6.88 | 1075.27 | 0.00 | 0.00 |
May | 1257.79 | 2293.07 | 1318.26 | 81.54 | 1236.72 | 0.00 | 0.00 |
June | 1660.49 | 1776.92 | 1418.23 | 171.20 | 1247.02 | 0.00 | 0.00 |
July | 1873.19 | 1559.83 | 1342.52 | 143.53 | 1198.99 | 0.00 | 0.00 |
August | 1496.46 | 1642.05 | 1097.27 | 32.21 | 1065.05 | 0.00 | 0.00 |
September | 1141.44 | 1952.94 | 920.02 | 0.28 | 919.73 | 0.00 | 0.00 |
October | 1067.76 | 2195.15 | 729.68 | 0.00 | 729.68 | 0.00 | 0.00 |
November | 471.19 | 3211.78 | 660.67 | 0.00 | 660.67 | 0.00 | 0.00 |
December | 389.38 | 3549.96 | 567.00 | 0.00 | 567.00 | 0.00 | 0.00 |
Annual Sum or Average | 991.44 | 2588.38 | 954.69 | 36.51 | 918.18 | 0.00 | 0.00 |
Minimum of Months | 389.38 | 1559.83 | 567.00 | 0.00 | 567.00 | 0.00 | 0.00 |
Maximum of Months | 1873.19 | 3549.96 | 1418.23 | 171.20 | 1247.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1564.34 | 2222.69 | 1100.83 | 591.33 | 509.50 | 0.00 | 0.00 |
February | 1461.41 | 2095.80 | 1155.76 | 529.65 | 626.11 | 0.00 | 0.00 |
March | 1893.81 | 2158.45 | 1396.15 | 617.98 | 778.17 | 0.00 | 0.00 |
April | 2931.27 | 1659.95 | 1788.21 | 893.77 | 894.45 | 0.00 | 0.00 |
May | 2598.49 | 1511.42 | 1688.83 | 702.16 | 986.68 | 0.00 | 0.00 |
June | 2891.44 | 1159.41 | 1682.25 | 729.58 | 952.67 | 0.00 | 0.00 |
July | 3633.88 | 1016.61 | 1903.67 | 944.43 | 959.24 | 0.00 | 0.00 |
August | 3634.15 | 1046.87 | 1876.96 | 994.11 | 882.85 | 0.00 | 0.00 |
September | 2483.55 | 1213.02 | 1371.89 | 629.12 | 742.77 | 0.00 | 0.00 |
October | 2234.62 | 1357.43 | 1212.68 | 622.83 | 589.84 | 0.00 | 0.00 |
November | 1560.71 | 2016.05 | 1109.73 | 565.45 | 544.28 | 0.00 | 0.00 |
December | 1504.25 | 2217.69 | 1063.47 | 594.44 | 469.02 | 0.00 | 0.00 |
Annual Sum or Average | 2372.32 | 1637.26 | 1447.79 | 702.61 | 745.18 | 0.00 | 0.00 |
Minimum of Months | 1461.41 | 1016.61 | 1063.47 | 529.65 | 469.02 | 0.00 | 0.00 |
Maximum of Months | 3634.15 | 2222.69 | 1903.67 | 994.11 | 986.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7211.31 | 3538.46 | 3935.64 | 2864.63 | 1071.01 | 0.00 | 0.00 |
February | 5066.89 | 3323.54 | 3145.38 | 1932.11 | 1213.27 | 0.00 | 0.00 |
March | 4100.49 | 3481.26 | 2580.34 | 1278.37 | 1301.97 | 0.00 | 0.00 |
April | 3872.13 | 2749.78 | 2255.68 | 953.76 | 1301.92 | 0.00 | 0.00 |
May | 2093.44 | 2472.19 | 1574.29 | 260.26 | 1314.03 | 0.00 | 0.00 |
June | 1929.29 | 1838.96 | 1361.41 | 126.25 | 1235.16 | 0.00 | 0.00 |
July | 2543.83 | 1590.19 | 1468.15 | 232.46 | 1235.69 | 0.00 | 0.00 |
August | 3803.90 | 1712.18 | 1929.72 | 705.12 | 1224.60 | 0.00 | 0.00 |
September | 5143.80 | 2034.23 | 2602.21 | 1374.37 | 1227.84 | 0.00 | 0.00 |
October | 6453.74 | 2274.64 | 3179.43 | 2130.09 | 1049.34 | 0.00 | 0.00 |
November | 6792.15 | 3237.69 | 3787.04 | 2655.79 | 1131.25 | 0.00 | 0.00 |
December | 7696.97 | 3545.58 | 4193.85 | 3168.11 | 1025.73 | 0.00 | 0.00 |
Annual Sum or Average | 4726.05 | 2646.38 | 2665.66 | 1471.82 | 1193.84 | 0.00 | 0.00 |
Minimum of Months | 1929.29 | 1590.19 | 1361.41 | 126.25 | 1025.73 | 0.00 | 0.00 |
Maximum of Months | 7696.97 | 3545.58 | 4193.85 | 3168.11 | 1314.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1571.23 | 2370.01 | 1049.29 | 532.57 | 516.72 | 0.00 | 0.00 |
February | 1701.49 | 2244.50 | 1240.64 | 571.07 | 669.57 | 0.00 | 0.00 |
March | 1981.21 | 2306.68 | 1419.29 | 624.37 | 794.92 | 0.00 | 0.00 |
April | 3203.42 | 1869.10 | 1955.57 | 1013.58 | 941.99 | 0.00 | 0.00 |
May | 2994.43 | 1681.26 | 1921.74 | 882.89 | 1038.85 | 0.00 | 0.00 |
June | 3459.85 | 1299.19 | 2034.15 | 1011.49 | 1022.66 | 0.00 | 0.00 |
July | 3995.40 | 1178.66 | 2153.82 | 1147.27 | 1006.55 | 0.00 | 0.00 |
August | 3813.18 | 1223.88 | 2020.28 | 1089.88 | 930.39 | 0.00 | 0.00 |
September | 3125.75 | 1361.80 | 1730.06 | 921.52 | 808.54 | 0.00 | 0.00 |
October | 2526.63 | 1504.60 | 1327.19 | 723.55 | 603.64 | 0.00 | 0.00 |
November | 1859.82 | 2163.71 | 1203.82 | 631.07 | 572.75 | 0.00 | 0.00 |
December | 1658.97 | 2395.60 | 1067.77 | 576.02 | 491.75 | 0.00 | 0.00 |
Annual Sum or Average | 2662.68 | 1797.65 | 1595.03 | 811.49 | 783.54 | 0.00 | 0.00 |
Minimum of Months | 1571.23 | 1178.66 | 1049.29 | 532.57 | 491.75 | 0.00 | 0.00 |
Maximum of Months | 3995.40 | 2395.60 | 2153.82 | 1147.27 | 1038.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 472.50 | 3177.15 | 609.08 | 0.00 | 609.08 | 0.00 | 0.00 |
February | 506.21 | 2985.29 | 764.56 | 0.00 | 764.56 | 0.00 | 0.00 |
March | 702.15 | 3168.20 | 936.91 | 0.00 | 936.91 | 0.00 | 0.00 |
April | 992.26 | 2443.96 | 1082.15 | 6.88 | 1075.27 | 0.00 | 0.00 |
May | 1267.25 | 2139.87 | 1318.26 | 81.54 | 1236.72 | 0.00 | 0.00 |
June | 1635.76 | 1670.51 | 1418.23 | 171.20 | 1247.02 | 0.00 | 0.00 |
July | 1824.16 | 1485.03 | 1342.52 | 143.53 | 1198.99 | 0.00 | 0.00 |
August | 1464.12 | 1550.75 | 1097.27 | 32.21 | 1065.05 | 0.00 | 0.00 |
September | 1148.59 | 1803.19 | 920.02 | 0.28 | 919.73 | 0.00 | 0.00 |
October | 1107.48 | 1986.50 | 729.68 | 0.00 | 729.68 | 0.00 | 0.00 |
November | 539.70 | 2875.00 | 660.67 | 0.00 | 660.67 | 0.00 | 0.00 |
December | 462.27 | 3166.15 | 567.00 | 0.00 | 567.00 | 0.00 | 0.00 |
Annual Sum or Average | 1013.59 | 2367.81 | 954.69 | 36.51 | 918.18 | 0.00 | 0.00 |
Minimum of Months | 462.27 | 1485.03 | 567.00 | 0.00 | 567.00 | 0.00 | 0.00 |
Maximum of Months | 1824.16 | 3177.15 | 1418.23 | 171.20 | 1247.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1648.98 | 1998.36 | 1100.83 | 591.33 | 509.50 | 0.00 | 0.00 |
February | 1520.32 | 1897.23 | 1155.76 | 529.65 | 626.11 | 0.00 | 0.00 |
March | 1943.96 | 2002.58 | 1396.15 | 617.98 | 778.17 | 0.00 | 0.00 |
April | 2929.50 | 1574.22 | 1788.21 | 893.77 | 894.45 | 0.00 | 0.00 |
May | 2605.41 | 1439.25 | 1688.83 | 702.16 | 986.68 | 0.00 | 0.00 |
June | 2874.66 | 1117.52 | 1682.25 | 729.58 | 952.67 | 0.00 | 0.00 |
July | 3587.99 | 993.91 | 1903.67 | 944.43 | 959.24 | 0.00 | 0.00 |
August | 3595.06 | 1015.87 | 1876.96 | 994.11 | 882.85 | 0.00 | 0.00 |
September | 2482.45 | 1145.26 | 1371.89 | 629.12 | 742.77 | 0.00 | 0.00 |
October | 2258.94 | 1257.40 | 1212.68 | 622.83 | 589.84 | 0.00 | 0.00 |
November | 1632.88 | 1820.73 | 1109.73 | 565.45 | 544.28 | 0.00 | 0.00 |
December | 1592.65 | 1986.21 | 1063.47 | 594.44 | 469.02 | 0.00 | 0.00 |
Annual Sum or Average | 2395.55 | 1518.78 | 1447.79 | 702.61 | 745.18 | 0.00 | 0.00 |
Minimum of Months | 1520.32 | 993.91 | 1063.47 | 529.65 | 469.02 | 0.00 | 0.00 |
Maximum of Months | 3595.06 | 2002.58 | 1903.67 | 994.11 | 986.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7253.38 | 3218.72 | 3935.64 | 2864.63 | 1071.01 | 0.00 | 0.00 |
February | 5076.03 | 3023.59 | 3145.38 | 1932.11 | 1213.27 | 0.00 | 0.00 |
March | 4113.59 | 3231.15 | 2580.34 | 1278.37 | 1301.97 | 0.00 | 0.00 |
April | 3839.14 | 2590.71 | 2255.68 | 953.76 | 1301.92 | 0.00 | 0.00 |
May | 2066.88 | 2337.87 | 1574.29 | 260.26 | 1314.03 | 0.00 | 0.00 |
June | 1888.67 | 1755.11 | 1361.41 | 126.25 | 1235.16 | 0.00 | 0.00 |
July | 2483.55 | 1535.23 | 1468.15 | 232.46 | 1235.69 | 0.00 | 0.00 |
August | 3743.77 | 1638.29 | 1929.72 | 705.12 | 1224.60 | 0.00 | 0.00 |
September | 5104.37 | 1904.79 | 2602.21 | 1374.37 | 1227.84 | 0.00 | 0.00 |
October | 6438.67 | 2097.78 | 3179.43 | 2130.09 | 1049.34 | 0.00 | 0.00 |
November | 6804.28 | 2951.81 | 3787.04 | 2655.79 | 1131.25 | 0.00 | 0.00 |
December | 7734.14 | 3223.84 | 4193.85 | 3168.11 | 1025.73 | 0.00 | 0.00 |
Annual Sum or Average | 4712.54 | 2456.17 | 2665.66 | 1471.82 | 1193.84 | 0.00 | 0.00 |
Minimum of Months | 1888.67 | 1535.23 | 1361.41 | 126.25 | 1025.73 | 0.00 | 0.00 |
Maximum of Months | 7734.14 | 3231.15 | 4193.85 | 3168.11 | 1314.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1564.22 | 2185.53 | 1049.29 | 532.57 | 516.72 | 0.00 | 0.00 |
February | 1684.64 | 2076.07 | 1240.64 | 571.07 | 669.57 | 0.00 | 0.00 |
March | 1953.66 | 2166.39 | 1419.29 | 624.37 | 794.92 | 0.00 | 0.00 |
April | 3136.98 | 1772.02 | 1955.57 | 1013.58 | 941.99 | 0.00 | 0.00 |
May | 2928.73 | 1597.06 | 1921.74 | 882.89 | 1038.85 | 0.00 | 0.00 |
June | 3379.93 | 1241.42 | 2034.15 | 1011.49 | 1022.66 | 0.00 | 0.00 |
July | 3906.62 | 1136.48 | 2153.82 | 1147.27 | 1006.55 | 0.00 | 0.00 |
August | 3731.51 | 1176.89 | 2020.28 | 1089.88 | 930.39 | 0.00 | 0.00 |
September | 3070.50 | 1288.07 | 1730.06 | 921.52 | 808.54 | 0.00 | 0.00 |
October | 2497.44 | 1406.27 | 1327.19 | 723.55 | 603.64 | 0.00 | 0.00 |
November | 1846.01 | 1997.43 | 1203.82 | 631.07 | 572.75 | 0.00 | 0.00 |
December | 1656.91 | 2204.44 | 1067.77 | 576.02 | 491.75 | 0.00 | 0.00 |
Annual Sum or Average | 2618.04 | 1685.38 | 1595.03 | 811.49 | 783.54 | 0.00 | 0.00 |
Minimum of Months | 1564.22 | 1136.48 | 1049.29 | 532.57 | 491.75 | 0.00 | 0.00 |
Maximum of Months | 3906.62 | 2204.44 | 2153.82 | 1147.27 | 1038.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.866133E+09 | 0.106588E+11 | 0.163136E+10 | 0.00 | 0.163136E+10 | 0.00 | 0.00 |
February | 0.893004E+09 | 0.899880E+10 | 0.184963E+10 | 0.00 | 0.184963E+10 | 0.00 | 0.00 |
March | 0.153478E+10 | 0.101888E+11 | 0.250942E+10 | 0.00 | 0.250942E+10 | 0.00 | 0.00 |
April | 0.236223E+10 | 0.760138E+10 | 0.280495E+10 | 17838778.78 | 0.278711E+10 | 0.00 | 0.00 |
May | 0.326338E+10 | 0.663368E+10 | 0.353084E+10 | 0.218392E+09 | 0.331245E+10 | 0.00 | 0.00 |
June | 0.434353E+10 | 0.497709E+10 | 0.367606E+10 | 0.443759E+09 | 0.323230E+10 | 0.00 | 0.00 |
July | 0.493866E+10 | 0.464070E+10 | 0.359581E+10 | 0.384420E+09 | 0.321139E+10 | 0.00 | 0.00 |
August | 0.387340E+10 | 0.498026E+10 | 0.293893E+10 | 86279038.48 | 0.285265E+10 | 0.00 | 0.00 |
September | 0.287387E+10 | 0.560205E+10 | 0.238469E+10 | 736903.37 | 0.238396E+10 | 0.00 | 0.00 |
October | 0.269522E+10 | 0.654554E+10 | 0.195437E+10 | 0.00 | 0.195437E+10 | 0.00 | 0.00 |
November | 0.966194E+09 | 0.944357E+10 | 0.171246E+10 | 0.00 | 0.171246E+10 | 0.00 | 0.00 |
December | 0.738218E+09 | 0.108648E+11 | 0.151866E+10 | 0.00 | 0.151866E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.293486E+11 | 0.911355E+11 | 0.301072E+11 | 0.115143E+10 | 0.289558E+11 | 0.00 | 0.00 |
Minimum of Months | 0.738218E+09 | 0.464070E+10 | 0.151866E+10 | 0.00 | 0.151866E+10 | 0.00 | 0.00 |
Maximum of Months | 0.493866E+10 | 0.108648E+11 | 0.367606E+10 | 0.443759E+09 | 0.331245E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.420851E+10 | 0.637485E+10 | 0.294848E+10 | 0.158382E+10 | 0.136466E+10 | 0.00 | 0.00 |
February | 0.363535E+10 | 0.542719E+10 | 0.279602E+10 | 0.128133E+10 | 0.151469E+10 | 0.00 | 0.00 |
March | 0.519231E+10 | 0.610167E+10 | 0.373947E+10 | 0.165520E+10 | 0.208427E+10 | 0.00 | 0.00 |
April | 0.777693E+10 | 0.456979E+10 | 0.463507E+10 | 0.231665E+10 | 0.231842E+10 | 0.00 | 0.00 |
May | 0.717251E+10 | 0.425439E+10 | 0.452339E+10 | 0.188066E+10 | 0.264273E+10 | 0.00 | 0.00 |
June | 0.768736E+10 | 0.319374E+10 | 0.436041E+10 | 0.189109E+10 | 0.246932E+10 | 0.00 | 0.00 |
July | 0.992842E+10 | 0.293450E+10 | 0.509881E+10 | 0.252958E+10 | 0.256923E+10 | 0.00 | 0.00 |
August | 0.993499E+10 | 0.300957E+10 | 0.502726E+10 | 0.266263E+10 | 0.236463E+10 | 0.00 | 0.00 |
September | 0.656248E+10 | 0.337826E+10 | 0.355596E+10 | 0.163070E+10 | 0.192527E+10 | 0.00 | 0.00 |
October | 0.611048E+10 | 0.390149E+10 | 0.324805E+10 | 0.166820E+10 | 0.157985E+10 | 0.00 | 0.00 |
November | 0.410840E+10 | 0.559639E+10 | 0.287642E+10 | 0.146565E+10 | 0.141077E+10 | 0.00 | 0.00 |
December | 0.404879E+10 | 0.634968E+10 | 0.284840E+10 | 0.159216E+10 | 0.125624E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.763665E+11 | 0.550915E+11 | 0.456577E+11 | 0.221577E+11 | 0.235001E+11 | 0.00 | 0.00 |
Minimum of Months | 0.363535E+10 | 0.293450E+10 | 0.279602E+10 | 0.128133E+10 | 0.125624E+10 | 0.00 | 0.00 |
Maximum of Months | 0.993499E+10 | 0.637485E+10 | 0.509881E+10 | 0.266263E+10 | 0.264273E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.197225E+11 | 0.966087E+10 | 0.105413E+11 | 0.767265E+10 | 0.286861E+10 | 0.00 | 0.00 |
February | 0.127164E+11 | 0.827190E+10 | 0.760933E+10 | 0.467418E+10 | 0.293515E+10 | 0.00 | 0.00 |
March | 0.112618E+11 | 0.964308E+10 | 0.691121E+10 | 0.342400E+10 | 0.348722E+10 | 0.00 | 0.00 |
April | 0.102351E+11 | 0.751932E+10 | 0.584675E+10 | 0.247216E+10 | 0.337458E+10 | 0.00 | 0.00 |
May | 0.574475E+10 | 0.690393E+10 | 0.421660E+10 | 0.697093E+09 | 0.351951E+10 | 0.00 | 0.00 |
June | 0.501385E+10 | 0.508736E+10 | 0.352878E+10 | 0.327239E+09 | 0.320154E+10 | 0.00 | 0.00 |
July | 0.676566E+10 | 0.467980E+10 | 0.393231E+10 | 0.622617E+09 | 0.330969E+10 | 0.00 | 0.00 |
August | 0.102628E+11 | 0.499952E+10 | 0.516859E+10 | 0.188860E+10 | 0.327999E+10 | 0.00 | 0.00 |
September | 0.136357E+11 | 0.548164E+10 | 0.674496E+10 | 0.356239E+10 | 0.318258E+10 | 0.00 | 0.00 |
October | 0.177047E+11 | 0.625706E+10 | 0.851582E+10 | 0.570526E+10 | 0.281056E+10 | 0.00 | 0.00 |
November | 0.180834E+11 | 0.864380E+10 | 0.981605E+10 | 0.688384E+10 | 0.293221E+10 | 0.00 | 0.00 |
December | 0.210936E+11 | 0.979395E+10 | 0.112328E+11 | 0.848551E+10 | 0.274734E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.152240E+12 | 0.869423E+11 | 0.840645E+11 | 0.464155E+11 | 0.376490E+11 | 0.00 | 0.00 |
Minimum of Months | 0.501385E+10 | 0.467980E+10 | 0.352878E+10 | 0.327239E+09 | 0.274734E+10 | 0.00 | 0.00 |
Maximum of Months | 0.210936E+11 | 0.979395E+10 | 0.112328E+11 | 0.848551E+10 | 0.351951E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.412859E+10 | 0.716425E+10 | 0.281043E+10 | 0.142644E+10 | 0.138399E+10 | 0.00 | 0.00 |
February | 0.407852E+10 | 0.618197E+10 | 0.300137E+10 | 0.138155E+10 | 0.161983E+10 | 0.00 | 0.00 |
March | 0.519735E+10 | 0.710645E+10 | 0.380143E+10 | 0.167231E+10 | 0.212913E+10 | 0.00 | 0.00 |
April | 0.822352E+10 | 0.572081E+10 | 0.506886E+10 | 0.262721E+10 | 0.244165E+10 | 0.00 | 0.00 |
May | 0.814483E+10 | 0.493409E+10 | 0.514721E+10 | 0.236475E+10 | 0.278246E+10 | 0.00 | 0.00 |
June | 0.907423E+10 | 0.381068E+10 | 0.527254E+10 | 0.262180E+10 | 0.265074E+10 | 0.00 | 0.00 |
July | 0.106337E+11 | 0.379648E+10 | 0.576880E+10 | 0.307285E+10 | 0.269595E+10 | 0.00 | 0.00 |
August | 0.100609E+11 | 0.413543E+10 | 0.541113E+10 | 0.291916E+10 | 0.249197E+10 | 0.00 | 0.00 |
September | 0.818010E+10 | 0.398090E+10 | 0.448433E+10 | 0.238859E+10 | 0.209574E+10 | 0.00 | 0.00 |
October | 0.669922E+10 | 0.465490E+10 | 0.355476E+10 | 0.193797E+10 | 0.161679E+10 | 0.00 | 0.00 |
November | 0.468002E+10 | 0.659094E+10 | 0.312031E+10 | 0.163574E+10 | 0.148458E+10 | 0.00 | 0.00 |
December | 0.420654E+10 | 0.771959E+10 | 0.285994E+10 | 0.154283E+10 | 0.131711E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.833075E+11 | 0.657965E+11 | 0.503011E+11 | 0.255912E+11 | 0.247099E+11 | 0.00 | 0.00 |
Minimum of Months | 0.407852E+10 | 0.379648E+10 | 0.281043E+10 | 0.138155E+10 | 0.131711E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106337E+11 | 0.771959E+10 | 0.576880E+10 | 0.307285E+10 | 0.278246E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.108906E+10 | 0.949673E+10 | 0.163136E+10 | 0.00 | 0.163136E+10 | 0.00 | 0.00 |
February | 0.108001E+10 | 0.803790E+10 | 0.184962E+10 | 0.00 | 0.184962E+10 | 0.00 | 0.00 |
March | 0.175258E+10 | 0.921325E+10 | 0.250941E+10 | 0.00 | 0.250941E+10 | 0.00 | 0.00 |
April | 0.256371E+10 | 0.678111E+10 | 0.280494E+10 | 17838715.43 | 0.278710E+10 | 0.00 | 0.00 |
May | 0.336887E+10 | 0.614176E+10 | 0.353083E+10 | 0.218391E+09 | 0.331244E+10 | 0.00 | 0.00 |
June | 0.430400E+10 | 0.460579E+10 | 0.367604E+10 | 0.443757E+09 | 0.323229E+10 | 0.00 | 0.00 |
July | 0.501714E+10 | 0.417785E+10 | 0.359580E+10 | 0.384418E+09 | 0.321138E+10 | 0.00 | 0.00 |
August | 0.400812E+10 | 0.439806E+10 | 0.293892E+10 | 86278732.10 | 0.285264E+10 | 0.00 | 0.00 |
September | 0.295861E+10 | 0.506203E+10 | 0.238469E+10 | 736900.75 | 0.238395E+10 | 0.00 | 0.00 |
October | 0.285988E+10 | 0.587948E+10 | 0.195437E+10 | 0.00 | 0.195437E+10 | 0.00 | 0.00 |
November | 0.122132E+10 | 0.832493E+10 | 0.171246E+10 | 0.00 | 0.171246E+10 | 0.00 | 0.00 |
December | 0.104290E+10 | 0.950820E+10 | 0.151866E+10 | 0.00 | 0.151866E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.312662E+11 | 0.816271E+11 | 0.301071E+11 | 0.115142E+10 | 0.289557E+11 | 0.00 | 0.00 |
Minimum of Months | 0.104290E+10 | 0.417785E+10 | 0.151866E+10 | 0.00 | 0.151866E+10 | 0.00 | 0.00 |
Maximum of Months | 0.501714E+10 | 0.950820E+10 | 0.367604E+10 | 0.443757E+09 | 0.331244E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.418993E+10 | 0.595325E+10 | 0.294847E+10 | 0.158382E+10 | 0.136465E+10 | 0.00 | 0.00 |
February | 0.353545E+10 | 0.507015E+10 | 0.279601E+10 | 0.128132E+10 | 0.151469E+10 | 0.00 | 0.00 |
March | 0.507237E+10 | 0.578119E+10 | 0.373946E+10 | 0.165520E+10 | 0.208426E+10 | 0.00 | 0.00 |
April | 0.759785E+10 | 0.430258E+10 | 0.463505E+10 | 0.231664E+10 | 0.231841E+10 | 0.00 | 0.00 |
May | 0.695978E+10 | 0.404818E+10 | 0.452337E+10 | 0.188066E+10 | 0.264272E+10 | 0.00 | 0.00 |
June | 0.749462E+10 | 0.300519E+10 | 0.436039E+10 | 0.189108E+10 | 0.246931E+10 | 0.00 | 0.00 |
July | 0.973298E+10 | 0.272289E+10 | 0.509879E+10 | 0.252957E+10 | 0.256922E+10 | 0.00 | 0.00 |
August | 0.973371E+10 | 0.280393E+10 | 0.502724E+10 | 0.266262E+10 | 0.236462E+10 | 0.00 | 0.00 |
September | 0.643737E+10 | 0.314415E+10 | 0.355595E+10 | 0.163069E+10 | 0.192526E+10 | 0.00 | 0.00 |
October | 0.598521E+10 | 0.363574E+10 | 0.324803E+10 | 0.166819E+10 | 0.157984E+10 | 0.00 | 0.00 |
November | 0.404536E+10 | 0.522561E+10 | 0.287641E+10 | 0.146565E+10 | 0.141076E+10 | 0.00 | 0.00 |
December | 0.402899E+10 | 0.593986E+10 | 0.284839E+10 | 0.159215E+10 | 0.125623E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.748136E+11 | 0.516327E+11 | 0.456576E+11 | 0.221576E+11 | 0.235000E+11 | 0.00 | 0.00 |
Minimum of Months | 0.353545E+10 | 0.272289E+10 | 0.279601E+10 | 0.128132E+10 | 0.125623E+10 | 0.00 | 0.00 |
Maximum of Months | 0.973371E+10 | 0.595325E+10 | 0.509879E+10 | 0.266262E+10 | 0.264272E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.193148E+11 | 0.947740E+10 | 0.105412E+11 | 0.767263E+10 | 0.286860E+10 | 0.00 | 0.00 |
February | 0.122578E+11 | 0.804032E+10 | 0.760930E+10 | 0.467417E+10 | 0.293514E+10 | 0.00 | 0.00 |
March | 0.109828E+11 | 0.932420E+10 | 0.691119E+10 | 0.342398E+10 | 0.348720E+10 | 0.00 | 0.00 |
April | 0.100365E+11 | 0.712744E+10 | 0.584672E+10 | 0.247215E+10 | 0.337457E+10 | 0.00 | 0.00 |
May | 0.560708E+10 | 0.662152E+10 | 0.421659E+10 | 0.697091E+09 | 0.351950E+10 | 0.00 | 0.00 |
June | 0.500073E+10 | 0.476658E+10 | 0.352876E+10 | 0.327237E+09 | 0.320153E+10 | 0.00 | 0.00 |
July | 0.681340E+10 | 0.425916E+10 | 0.393229E+10 | 0.622615E+09 | 0.330968E+10 | 0.00 | 0.00 |
August | 0.101884E+11 | 0.458589E+10 | 0.516857E+10 | 0.188859E+10 | 0.327998E+10 | 0.00 | 0.00 |
September | 0.133327E+11 | 0.527272E+10 | 0.674494E+10 | 0.356237E+10 | 0.318257E+10 | 0.00 | 0.00 |
October | 0.172857E+11 | 0.609239E+10 | 0.851579E+10 | 0.570524E+10 | 0.281055E+10 | 0.00 | 0.00 |
November | 0.176052E+11 | 0.839210E+10 | 0.981601E+10 | 0.688382E+10 | 0.293219E+10 | 0.00 | 0.00 |
December | 0.206156E+11 | 0.949648E+10 | 0.112328E+11 | 0.848548E+10 | 0.274733E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.149041E+12 | 0.834562E+11 | 0.840642E+11 | 0.464154E+11 | 0.376488E+11 | 0.00 | 0.00 |
Minimum of Months | 0.500073E+10 | 0.425916E+10 | 0.352876E+10 | 0.327237E+09 | 0.274733E+10 | 0.00 | 0.00 |
Maximum of Months | 0.206156E+11 | 0.949648E+10 | 0.112328E+11 | 0.848548E+10 | 0.351950E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.420839E+10 | 0.634785E+10 | 0.281042E+10 | 0.142643E+10 | 0.138399E+10 | 0.00 | 0.00 |
February | 0.411624E+10 | 0.542989E+10 | 0.300136E+10 | 0.138154E+10 | 0.161982E+10 | 0.00 | 0.00 |
March | 0.530648E+10 | 0.617822E+10 | 0.380142E+10 | 0.167230E+10 | 0.212912E+10 | 0.00 | 0.00 |
April | 0.830326E+10 | 0.484470E+10 | 0.506883E+10 | 0.262719E+10 | 0.244164E+10 | 0.00 | 0.00 |
May | 0.802027E+10 | 0.450309E+10 | 0.514719E+10 | 0.236474E+10 | 0.278245E+10 | 0.00 | 0.00 |
June | 0.896792E+10 | 0.336751E+10 | 0.527252E+10 | 0.262179E+10 | 0.265073E+10 | 0.00 | 0.00 |
July | 0.107013E+11 | 0.315693E+10 | 0.576878E+10 | 0.307284E+10 | 0.269594E+10 | 0.00 | 0.00 |
August | 0.102132E+11 | 0.327805E+10 | 0.541111E+10 | 0.291915E+10 | 0.249196E+10 | 0.00 | 0.00 |
September | 0.810195E+10 | 0.352979E+10 | 0.448431E+10 | 0.238858E+10 | 0.209574E+10 | 0.00 | 0.00 |
October | 0.676733E+10 | 0.402991E+10 | 0.355474E+10 | 0.193796E+10 | 0.161678E+10 | 0.00 | 0.00 |
November | 0.482064E+10 | 0.560833E+10 | 0.312030E+10 | 0.163573E+10 | 0.148457E+10 | 0.00 | 0.00 |
December | 0.444340E+10 | 0.641638E+10 | 0.285993E+10 | 0.154282E+10 | 0.131710E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.839704E+11 | 0.566906E+11 | 0.503009E+11 | 0.255911E+11 | 0.247098E+11 | 0.00 | 0.00 |
Minimum of Months | 0.411624E+10 | 0.315693E+10 | 0.281042E+10 | 0.138154E+10 | 0.131710E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107013E+11 | 0.641638E+10 | 0.576878E+10 | 0.307284E+10 | 0.278245E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.126555E+10 | 0.850968E+10 | 0.163136E+10 | 0.00 | 0.163136E+10 | 0.00 | 0.00 |
February | 0.122462E+10 | 0.722200E+10 | 0.184962E+10 | 0.00 | 0.184962E+10 | 0.00 | 0.00 |
March | 0.188064E+10 | 0.848570E+10 | 0.250941E+10 | 0.00 | 0.250941E+10 | 0.00 | 0.00 |
April | 0.257195E+10 | 0.633473E+10 | 0.280494E+10 | 17838715.43 | 0.278710E+10 | 0.00 | 0.00 |
May | 0.339420E+10 | 0.573143E+10 | 0.353083E+10 | 0.218391E+09 | 0.331244E+10 | 0.00 | 0.00 |
June | 0.423988E+10 | 0.432997E+10 | 0.367604E+10 | 0.443757E+09 | 0.323229E+10 | 0.00 | 0.00 |
July | 0.488583E+10 | 0.397752E+10 | 0.359580E+10 | 0.384418E+09 | 0.321138E+10 | 0.00 | 0.00 |
August | 0.392150E+10 | 0.415354E+10 | 0.293892E+10 | 86278732.10 | 0.285264E+10 | 0.00 | 0.00 |
September | 0.297715E+10 | 0.467387E+10 | 0.238469E+10 | 736900.75 | 0.238395E+10 | 0.00 | 0.00 |
October | 0.296628E+10 | 0.532064E+10 | 0.195437E+10 | 0.00 | 0.195437E+10 | 0.00 | 0.00 |
November | 0.139889E+10 | 0.745200E+10 | 0.171246E+10 | 0.00 | 0.171246E+10 | 0.00 | 0.00 |
December | 0.123814E+10 | 0.848022E+10 | 0.151866E+10 | 0.00 | 0.151866E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.319646E+11 | 0.746713E+11 | 0.301071E+11 | 0.115142E+10 | 0.289557E+11 | 0.00 | 0.00 |
Minimum of Months | 0.122462E+10 | 0.397752E+10 | 0.151866E+10 | 0.00 | 0.151866E+10 | 0.00 | 0.00 |
Maximum of Months | 0.488583E+10 | 0.850968E+10 | 0.367604E+10 | 0.443757E+09 | 0.331244E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.441664E+10 | 0.535241E+10 | 0.294847E+10 | 0.158382E+10 | 0.136465E+10 | 0.00 | 0.00 |
February | 0.367795E+10 | 0.458979E+10 | 0.279601E+10 | 0.128132E+10 | 0.151469E+10 | 0.00 | 0.00 |
March | 0.520670E+10 | 0.536371E+10 | 0.373946E+10 | 0.165520E+10 | 0.208426E+10 | 0.00 | 0.00 |
April | 0.759325E+10 | 0.408038E+10 | 0.463505E+10 | 0.231664E+10 | 0.231841E+10 | 0.00 | 0.00 |
May | 0.697832E+10 | 0.385489E+10 | 0.452337E+10 | 0.188066E+10 | 0.264272E+10 | 0.00 | 0.00 |
June | 0.745111E+10 | 0.289662E+10 | 0.436039E+10 | 0.189108E+10 | 0.246931E+10 | 0.00 | 0.00 |
July | 0.961006E+10 | 0.266209E+10 | 0.509879E+10 | 0.252957E+10 | 0.256922E+10 | 0.00 | 0.00 |
August | 0.962902E+10 | 0.272091E+10 | 0.502724E+10 | 0.266262E+10 | 0.236462E+10 | 0.00 | 0.00 |
September | 0.643451E+10 | 0.296851E+10 | 0.355595E+10 | 0.163069E+10 | 0.192526E+10 | 0.00 | 0.00 |
October | 0.605034E+10 | 0.336782E+10 | 0.324803E+10 | 0.166819E+10 | 0.157984E+10 | 0.00 | 0.00 |
November | 0.423242E+10 | 0.471933E+10 | 0.287641E+10 | 0.146565E+10 | 0.141076E+10 | 0.00 | 0.00 |
December | 0.426575E+10 | 0.531987E+10 | 0.284839E+10 | 0.159215E+10 | 0.125623E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.755461E+11 | 0.478963E+11 | 0.456576E+11 | 0.221576E+11 | 0.235000E+11 | 0.00 | 0.00 |
Minimum of Months | 0.367795E+10 | 0.266209E+10 | 0.279601E+10 | 0.128132E+10 | 0.125623E+10 | 0.00 | 0.00 |
Maximum of Months | 0.962902E+10 | 0.536371E+10 | 0.509879E+10 | 0.266262E+10 | 0.264272E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.194275E+11 | 0.862101E+10 | 0.105412E+11 | 0.767263E+10 | 0.286860E+10 | 0.00 | 0.00 |
February | 0.122799E+11 | 0.731467E+10 | 0.760930E+10 | 0.467417E+10 | 0.293514E+10 | 0.00 | 0.00 |
March | 0.110178E+11 | 0.865431E+10 | 0.691119E+10 | 0.342398E+10 | 0.348720E+10 | 0.00 | 0.00 |
April | 0.995106E+10 | 0.671513E+10 | 0.584672E+10 | 0.247215E+10 | 0.337457E+10 | 0.00 | 0.00 |
May | 0.553594E+10 | 0.626176E+10 | 0.421659E+10 | 0.697091E+09 | 0.351950E+10 | 0.00 | 0.00 |
June | 0.489542E+10 | 0.454925E+10 | 0.352876E+10 | 0.327237E+09 | 0.320153E+10 | 0.00 | 0.00 |
July | 0.665193E+10 | 0.411197E+10 | 0.393229E+10 | 0.622615E+09 | 0.330968E+10 | 0.00 | 0.00 |
August | 0.100273E+11 | 0.438800E+10 | 0.516857E+10 | 0.188859E+10 | 0.327998E+10 | 0.00 | 0.00 |
September | 0.132305E+11 | 0.493722E+10 | 0.674494E+10 | 0.356237E+10 | 0.318257E+10 | 0.00 | 0.00 |
October | 0.172453E+11 | 0.561868E+10 | 0.851579E+10 | 0.570524E+10 | 0.281055E+10 | 0.00 | 0.00 |
November | 0.176367E+11 | 0.765110E+10 | 0.981601E+10 | 0.688382E+10 | 0.293219E+10 | 0.00 | 0.00 |
December | 0.207151E+11 | 0.863473E+10 | 0.112328E+11 | 0.848548E+10 | 0.274733E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.148615E+12 | 0.774578E+11 | 0.840642E+11 | 0.464154E+11 | 0.376488E+11 | 0.00 | 0.00 |
Minimum of Months | 0.489542E+10 | 0.411197E+10 | 0.352876E+10 | 0.327237E+09 | 0.274733E+10 | 0.00 | 0.00 |
Maximum of Months | 0.207151E+11 | 0.865431E+10 | 0.112328E+11 | 0.848548E+10 | 0.351950E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.418962E+10 | 0.585373E+10 | 0.281042E+10 | 0.142643E+10 | 0.138399E+10 | 0.00 | 0.00 |
February | 0.407549E+10 | 0.502243E+10 | 0.300136E+10 | 0.138154E+10 | 0.161982E+10 | 0.00 | 0.00 |
March | 0.523268E+10 | 0.580245E+10 | 0.380142E+10 | 0.167230E+10 | 0.212912E+10 | 0.00 | 0.00 |
April | 0.813105E+10 | 0.459307E+10 | 0.506883E+10 | 0.262719E+10 | 0.244164E+10 | 0.00 | 0.00 |
May | 0.784430E+10 | 0.427756E+10 | 0.514719E+10 | 0.236474E+10 | 0.278245E+10 | 0.00 | 0.00 |
June | 0.876079E+10 | 0.321775E+10 | 0.527252E+10 | 0.262179E+10 | 0.265073E+10 | 0.00 | 0.00 |
July | 0.104635E+11 | 0.304395E+10 | 0.576878E+10 | 0.307284E+10 | 0.269594E+10 | 0.00 | 0.00 |
August | 0.999448E+10 | 0.315219E+10 | 0.541111E+10 | 0.291915E+10 | 0.249196E+10 | 0.00 | 0.00 |
September | 0.795873E+10 | 0.333868E+10 | 0.448431E+10 | 0.238858E+10 | 0.209574E+10 | 0.00 | 0.00 |
October | 0.668915E+10 | 0.376655E+10 | 0.355474E+10 | 0.193796E+10 | 0.161678E+10 | 0.00 | 0.00 |
November | 0.478485E+10 | 0.517733E+10 | 0.312030E+10 | 0.163573E+10 | 0.148457E+10 | 0.00 | 0.00 |
December | 0.443787E+10 | 0.590438E+10 | 0.285993E+10 | 0.154282E+10 | 0.131710E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.825625E+11 | 0.531501E+11 | 0.503009E+11 | 0.255911E+11 | 0.247098E+11 | 0.00 | 0.00 |
Minimum of Months | 0.407549E+10 | 0.304395E+10 | 0.281042E+10 | 0.138154E+10 | 0.131710E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104635E+11 | 0.590438E+10 | 0.576878E+10 | 0.307284E+10 | 0.278245E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.343181E+11 | -0.338717E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -446405160.3 | 60.05 | 0.00 | 0.00 |
February | 0.312183E+11 | -0.308141E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -404149684.0 | 60.05 | 0.00 | 0.00 |
March | 0.363111E+11 | -0.358631E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -448044908.0 | 60.05 | 0.00 | 0.00 |
April | 0.322873E+11 | -0.318553E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -431978187.1 | 60.05 | 0.00 | 0.00 |
May | 0.336152E+11 | -0.331681E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -447152462.5 | 60.05 | 0.00 | 0.00 |
June | 0.325797E+11 | -0.321480E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -431718327.5 | 60.05 | 0.00 | 0.00 |
July | 0.305654E+11 | -0.301227E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442671865.3 | 60.05 | 0.00 | 0.00 |
August | 0.333776E+11 | -0.329331E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444470904.9 | 60.05 | 0.00 | 0.00 |
September | 0.306596E+11 | -0.302295E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -430067685.4 | 60.05 | 0.00 | 0.00 |
October | 0.323196E+11 | -0.318763E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443255060.3 | 60.05 | 0.00 | 0.00 |
November | 0.325094E+11 | -0.320795E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -429930556.4 | 60.05 | 0.00 | 0.00 |
December | 0.330801E+11 | -0.326345E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -445598023.1 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.392841E+12 | -0.387596E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.524544E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.305654E+11 | -0.358631E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -448044908.0 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.363111E+11 | -0.301227E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -404149684.0 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 293.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 338.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 393.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 381.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 390.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 328.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 300.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 297.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4065.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.342726E+09 | 13221.11 | 09-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162878E+09 | 12715.01 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.232135E+09 | 12808.17 | 08-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15121856.47 | 6265.51 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 819530.62 | 2068.31 | 15-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7689516.01 | 1743.73 | 28-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33556821.87 | 9831.96 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161839E+09 | 12776.41 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.956765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.342726E+09 | 13221.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.739313E+09 | 12793.84 | 09-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.691712E+09 | 12379.08 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.742517E+09 | 12385.10 | 08-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.213000E+09 | 11826.90 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128376E+09 | 5845.79 | 15-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17467112.24 | 2659.60 | 01-JUN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 884770.56 | 7235.50 | 06-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 677391.38 | 3445.52 | 22-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34301848.16 | 4541.20 | 20-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109325E+09 | 8915.85 | 12-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.384525E+09 | 11884.20 | 08-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.640509E+09 | 12354.08 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 677391.38 | 2659.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.742517E+09 | 12793.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.490672E+09 | 18619.92 | 09-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.509905E+09 | 18020.35 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.691500E+09 | 18033.01 | 08-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164847E+09 | 17088.01 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169841E+09 | 16553.15 | 27-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9114142.07 | 3598.01 | 13-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7893998.72 | 3293.68 | 20-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 78520941.32 | 11830.27 | 12-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166438E+09 | 17313.99 | 08-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.324788E+09 | 17988.11 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.691500E+09 | 18619.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.583195E+09 | 11771.68 | 09-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.370571E+09 | 8056.55 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.292750E+09 | 10990.94 | 30-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21518292.30 | 5582.16 | 01-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73255206.03 | 6659.69 | 15-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2224750.02 | 1668.60 | 01-JUN-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3262830.94 | 2223.61 | 20-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 56369514.98 | 3217.23 | 30-OCT-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 83894105.12 | 10310.91 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154682E+09 | 5816.99 | 15-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.583195E+09 | 11771.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 61618567.74 | 105189.33 | 12-JAN-10:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15852787.46 | 47211.29 | 10-FEB-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31993754.42 | 95860.11 | 31-MAR-09:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27311305.32 | 85099.49 | 01-DEC-10:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 61618567.74 | 105189.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.161028E+11 | 172010.40 | 09-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113245E+11 | 161296.23 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137473E+11 | 163813.98 | 30-MAR-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.387430E+10 | 155059.34 | 20-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136467E+10 | 154680.72 | 27-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 54473106.57 | 32981.96 | 01-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1940566.79 | 1847.65 | 28-AUG-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252163E+09 | 52730.55 | 20-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205627E+10 | 156670.71 | 12-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.779334E+10 | 155339.49 | 08-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134963E+11 | 162675.29 | 23-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.700680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161028E+11 | 172010.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160558E+11 | 174670.60 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145607E+11 | 163088.13 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161141E+11 | 165626.56 | 30-MAR-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.652643E+10 | 157202.29 | 20-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.466334E+10 | 156812.82 | 27-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.179806E+10 | 59046.82 | 01-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.652520E+09 | 45619.04 | 06-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.853213E+09 | 43880.83 | 28-AUG-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.292568E+10 | 74075.41 | 20-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.383954E+10 | 158887.14 | 12-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104846E+11 | 157514.44 | 08-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144599E+11 | 164178.43 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.929338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.652520E+09 | 43880.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161141E+11 | 174670.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108158E+11 | 222233.72 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114592E+11 | 207640.69 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162660E+11 | 211102.14 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.684074E+10 | 198043.00 | 22-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.610544E+10 | 201191.67 | 19-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.116117E+10 | 78510.46 | 05-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119701E+09 | 39811.56 | 06-JUL-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.197889E+09 | 23542.57 | 22-AUG-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.762288E+09 | 44465.70 | 20-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.222332E+10 | 199554.83 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.544339E+10 | 200691.97 | 08-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.879715E+10 | 209059.60 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.701921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.119701E+09 | 23542.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.162660E+11 | 222233.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.208313E+11 | 173764.69 | 09-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167121E+11 | 162735.49 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183842E+11 | 164757.34 | 30-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.735851E+10 | 154764.32 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.618480E+10 | 156416.14 | 27-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.179666E+10 | 77612.92 | 01-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.361724E+09 | 36720.17 | 06-JUL-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.659298E+09 | 34161.75 | 31-AUG-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.238471E+10 | 49232.42 | 16-SEP-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.495547E+10 | 156217.69 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128248E+11 | 157115.14 | 08-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184787E+11 | 163812.21 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110932E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.361724E+09 | 34161.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.208313E+11 | 173764.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 69439582.92 | 5892.63 | 09-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 103818.86 | 324.24 | 09-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12622088.30 | 4707.17 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10301389.21 | 3502.17 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92466879.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 69439582.92 | 5892.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.156880E+10 | 85046.96 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.668435E+09 | 76009.59 | 21-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.492246E+09 | 80288.68 | 30-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37281474.29 | 4302.18 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17792157.78 | 16694.02 | 15-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 63412362.90 | 72374.79 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.532523E+09 | 74498.05 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.927073E+09 | 78417.82 | 13-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.430757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.156880E+10 | 85046.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.381634E+10 | 22015.29 | 09-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.290366E+10 | 20593.49 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.320798E+10 | 20937.62 | 30-MAR-04:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127942E+10 | 19684.16 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.828238E+09 | 19459.11 | 15-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151004E+09 | 18886.78 | 01-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 42431401.78 | 10486.76 | 06-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82715520.25 | 3747.65 | 24-AUG-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.389208E+09 | 18815.50 | 16-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.874761E+09 | 19115.76 | 12-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.249837E+10 | 19897.96 | 08-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.349911E+10 | 20781.70 | 23-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 42431401.78 | 3747.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.381634E+10 | 22015.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.264011E+10 | 19532.39 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244119E+10 | 18261.05 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.257173E+10 | 18591.26 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107171E+10 | 17385.71 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.865880E+09 | 17241.80 | 15-MAY-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.357151E+09 | 16673.55 | 01-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151688E+09 | 11834.00 | 06-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.194353E+09 | 4723.25 | 26-AUG-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.569930E+09 | 16701.34 | 16-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.815518E+09 | 16831.32 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191853E+10 | 17648.57 | 08-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.248461E+10 | 18388.09 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.151688E+09 | 4723.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.264011E+10 | 19532.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.245084E+10 | 26412.32 | 09-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.253862E+10 | 24692.02 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.320960E+10 | 25066.58 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156872E+10 | 23451.29 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150632E+10 | 23310.03 | 15-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.534703E+09 | 22599.32 | 13-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.208391E+09 | 15107.96 | 06-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.244995E+09 | 6057.95 | 22-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.506465E+09 | 20752.59 | 20-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.801926E+09 | 22707.10 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168493E+10 | 23800.17 | 08-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.218305E+10 | 24792.63 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.208391E+09 | 6057.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.320960E+10 | 26412.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.331962E+10 | 20629.57 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.276746E+10 | 19277.94 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.300961E+10 | 19568.33 | 30-MAR-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137479E+10 | 18343.48 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122331E+10 | 17839.78 | 19-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.476402E+09 | 17583.06 | 01-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.206714E+09 | 4950.60 | 06-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.278652E+09 | 5307.88 | 22-AUG-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.605382E+09 | 12483.50 | 20-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111076E+10 | 17753.25 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.238436E+10 | 18621.81 | 08-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.307479E+10 | 19409.71 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.206714E+09 | 4950.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.331962E+10 | 20629.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.287911E+11 | 0.287100E+11 | 122821.80 | 18-JAN-14:04 | 122821.80 | 0.15 |
February | 0.00 | 0.00 | 0.158245E+11 | 0.156789E+11 | 110011.21 | 01-FEB-12:00 | 110011.21 | 0.15 |
March | 0.00 | 0.00 | 0.190220E+11 | 0.185873E+11 | 122476.07 | 23-MAR-14:00 | 107176.12 | 0.18 |
April | 0.00 | 0.00 | 0.410494E+11 | 0.409590E+11 | 139966.80 | 26-APR-13:40 | 136773.36 | 0.34 |
May | 0.00 | 0.00 | 0.389289E+11 | 0.387976E+11 | 108259.49 | 03-MAY-13:10 | 108259.49 | 0.38 |
June | 0.00 | 0.00 | 0.677300E+11 | 0.613844E+11 | 157448.77 | 30-JUN-04:12 | 67131.14 | 0.57 |
July | 0.00 | 0.00 | 0.120491E+12 | 0.923189E+11 | 188688.24 | 28-JUL-14:00 | 103374.86 | 0.62 |
August | 0.00 | 0.00 | 0.147759E+12 | 0.106322E+12 | 213677.67 | 07-AUG-09:50 | 120156.64 | 0.64 |
September | 0.00 | 0.00 | 0.809651E+11 | 0.668366E+11 | 177760.39 | 22-SEP-04:12 | 73255.34 | 0.56 |
October | 0.00 | 0.00 | 0.942051E+11 | 0.807613E+11 | 196250.41 | 01-OCT-14:42 | 100430.82 | 0.37 |
November | 0.00 | 0.00 | 0.317781E+11 | 0.314674E+11 | 123517.44 | 28-NOV-14:00 | 123517.44 | 0.18 |
December | 0.00 | 0.00 | 0.371607E+11 | 0.370368E+11 | 131168.61 | 05-DEC-15:00 | 131168.61 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.723705E+12 | 0.618861E+12 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 0.158245E+11 | 0.156789E+11 | 108259.49 | 67131.14 | 0.07 | |
Maximum of Months | 0.00 | 0.00 | 0.147759E+12 | 0.106322E+12 | 213677.67 | 136773.36 | 0.64 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.267453E+12 | 0.266327E+12 | 1049544.64 | 18-JAN-13:02 | 1049544.64 | 0.16 |
February | 0.00 | 0.00 | 0.143037E+12 | 0.141786E+12 | 963855.53 | 01-FEB-12:00 | 963855.53 | 0.16 |
March | 0.00 | 0.00 | 0.169330E+12 | 0.165423E+12 | 1105854.55 | 23-MAR-14:05 | 928888.79 | 0.18 |
April | 0.00 | 0.00 | 0.329174E+12 | 0.328688E+12 | 1205468.18 | 26-APR-14:05 | 1176903.40 | 0.34 |
May | 0.00 | 0.00 | 0.333053E+12 | 0.331933E+12 | 937654.85 | 03-MAY-13:00 | 937654.85 | 0.38 |
June | 0.00 | 0.00 | 0.580395E+12 | 0.526863E+12 | 1337926.90 | 30-JUN-04:11 | 571923.35 | 0.57 |
July | 0.00 | 0.00 | 0.978665E+12 | 0.748591E+12 | 1636156.25 | 28-JUL-14:05 | 889792.77 | 0.60 |
August | 0.00 | 0.00 | 0.116753E+13 | 0.842098E+12 | 1702477.91 | 15-AUG-16:00 | 932154.58 | 0.62 |
September | 0.00 | 0.00 | 0.704780E+12 | 0.584982E+12 | 1567097.19 | 29-SEP-14:05 | 1567097.19 | 0.55 |
October | 0.00 | 0.00 | 0.816216E+12 | 0.700794E+12 | 1805123.01 | 01-OCT-14:31 | 942045.34 | 0.36 |
November | 0.00 | 0.00 | 0.282721E+12 | 0.280024E+12 | 1001205.74 | 28-NOV-14:00 | 1001205.74 | 0.19 |
December | 0.00 | 0.00 | 0.312154E+12 | 0.311055E+12 | 1061754.18 | 05-DEC-15:03 | 1061754.18 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.608451E+13 | 0.522856E+13 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 0.143037E+12 | 0.141786E+12 | 937654.85 | 571923.35 | 0.07 | |
Maximum of Months | 0.00 | 0.00 | 0.116753E+13 | 0.842098E+12 | 1805123.01 | 1567097.19 | 0.62 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.223541E+11 | 0.223511E+11 | 121320.77 | 18-JAN-14:15 | 121320.77 | 0.15 |
February | 0.00 | 0.00 | 0.123609E+11 | 0.122243E+11 | 102006.95 | 01-FEB-13:03 | 102006.95 | 0.14 |
March | 0.00 | 0.00 | 0.154281E+11 | 0.152193E+11 | 109915.60 | 23-MAR-15:00 | 91477.58 | 0.17 |
April | 0.00 | 0.00 | 0.356551E+11 | 0.356002E+11 | 159997.67 | 26-APR-13:50 | 156936.89 | 0.33 |
May | 0.00 | 0.00 | 0.355569E+11 | 0.354629E+11 | 135455.28 | 03-MAY-13:00 | 135455.28 | 0.37 |
June | 0.00 | 0.00 | 0.644178E+11 | 0.587060E+11 | 159187.38 | 29-JUN-13:20 | 105528.39 | 0.56 |
July | 0.00 | 0.00 | 0.112069E+12 | 0.881779E+11 | 188504.39 | 28-JUL-14:00 | 104022.14 | 0.59 |
August | 0.00 | 0.00 | 0.130403E+12 | 0.970570E+11 | 194820.11 | 15-AUG-16:00 | 107133.47 | 0.61 |
September | 0.00 | 0.00 | 0.738802E+11 | 0.620055E+11 | 193856.32 | 29-SEP-13:40 | 193856.32 | 0.54 |
October | 0.00 | 0.00 | 0.837121E+11 | 0.727229E+11 | 199615.18 | 01-OCT-14:42 | 102316.43 | 0.35 |
November | 0.00 | 0.00 | 0.233191E+11 | 0.232584E+11 | 110787.54 | 19-NOV-13:21 | 110787.54 | 0.18 |
December | 0.00 | 0.00 | 0.272896E+11 | 0.272531E+11 | 118086.13 | 05-DEC-15:00 | 118086.13 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.636445E+12 | 0.550039E+12 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 0.123609E+11 | 0.122243E+11 | 102006.95 | 91477.58 | 0.06 | |
Maximum of Months | 0.00 | 0.00 | 0.130403E+12 | 0.970570E+11 | 199615.18 | 193856.32 | 0.61 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.259487E+11 | 0.240253E+11 | 78679.08 | 17-JAN-11:50 | 66282.49 | 0.20 |
February | 0.00 | 0.00 | 0.185073E+11 | 0.164333E+11 | 82927.80 | 13-FEB-05:11 | 34959.20 | 0.19 |
March | 0.00 | 0.00 | 0.196006E+11 | 0.171767E+11 | 107442.65 | 01-MAR-05:57 | 107442.65 | 0.19 |
April | 0.00 | 0.00 | 0.293326E+11 | 0.250607E+11 | 84515.96 | 11-APR-17:50 | 45849.42 | 0.34 |
May | 0.00 | 0.00 | 0.315251E+11 | 0.282689E+11 | 74539.14 | 09-MAY-14:18 | 57057.47 | 0.37 |
June | 0.00 | 0.00 | 0.511059E+11 | 0.379354E+11 | 110267.79 | 29-JUN-07:58 | 47080.40 | 0.49 |
July | 0.00 | 0.00 | 0.779213E+11 | 0.496418E+11 | 128896.46 | 31-JUL-00:44 | 110502.60 | 0.52 |
August | 0.00 | 0.00 | 0.926240E+11 | 0.560020E+11 | 131700.38 | 07-AUG-09:50 | 68893.72 | 0.57 |
September | 0.00 | 0.00 | 0.583201E+11 | 0.398350E+11 | 124251.78 | 22-SEP-04:12 | 51206.08 | 0.50 |
October | 0.00 | 0.00 | 0.608769E+11 | 0.469322E+11 | 140056.26 | 05-OCT-04:21 | 63555.78 | 0.33 |
November | 0.00 | 0.00 | 0.236249E+11 | 0.218982E+11 | 122179.52 | 12-NOV-12:55 | 116399.89 | 0.21 |
December | 0.00 | 0.00 | 0.268539E+11 | 0.260055E+11 | 91275.56 | 08-DEC-15:13 | 59243.99 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.516241E+12 | 0.389215E+12 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 0.185073E+11 | 0.164333E+11 | 74539.14 | 34959.20 | 0.08 | |
Maximum of Months | 0.00 | 0.00 | 0.926240E+11 | 0.560020E+11 | 140056.26 | 116399.89 | 0.57 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.789937E+10 | 0.789937E+10 | 109880.99 | 13-JAN-12:02 | 109880.99 | 0.19 |
February | 0.00 | 0.00 | 0.141882E+12 | 0.129130E+12 | 397159.30 | 12-FEB-13:41 | 229063.95 | 0.27 |
March | 0.00 | 0.00 | 0.228041E+12 | 0.220489E+12 | 372434.01 | 22-MAR-15:57 | 245311.97 | 0.50 |
April | 0.00 | 0.00 | 0.259022E+12 | 0.252115E+12 | 413658.97 | 02-APR-12:36 | 413658.97 | 0.77 |
May | 0.00 | 0.00 | 0.192307E+10 | 0.185671E+10 | 266666.75 | 31-MAY-23:11 | 235789.63 | 0.29 |
June | 0.00 | 0.00 | 0.246577E+12 | 0.190581E+12 | 474602.51 | 29-JUN-18:22 | 256330.24 | 0.62 |
July | 0.00 | 0.00 | 0.337351E+12 | 0.267087E+12 | 492530.95 | 19-JUL-19:51 | 198359.89 | 1.00 |
August | 0.00 | 0.00 | 0.440714E+12 | 0.365729E+12 | 522967.36 | 18-AUG-09:30 | 392184.92 | 1.00 |
September | 0.00 | 0.00 | 0.190487E+11 | 0.186724E+11 | 443969.41 | 30-SEP-23:40 | 190461.07 | 0.43 |
October | 0.00 | 0.00 | 0.278204E+12 | 0.229863E+12 | 521538.62 | 01-OCT-07:02 | 184365.39 | 0.51 |
November | 0.00 | 0.00 | 0.236804E+12 | 0.223142E+12 | 392580.82 | 20-NOV-13:11 | 284205.90 | 0.42 |
December | 0.00 | 0.00 | 0.274652E+12 | 0.273055E+12 | 432557.28 | 19-DEC-13:02 | 432557.28 | 0.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.247212E+13 | 0.217962E+13 | 0.52 | |||
Minimum of Months | 0.00 | 0.00 | 0.192307E+10 | 0.185671E+10 | 109880.99 | 109880.99 | 0.19 | |
Maximum of Months | 0.00 | 0.00 | 0.440714E+12 | 0.365729E+12 | 522967.36 | 432557.28 | 1.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.682114E+10 | 0.679489E+10 | 3497.98 | 18-JAN-16:10 | 3442.24 | 0.00 |
February | 0.00 | 0.00 | 0.106436E+11 | 0.106029E+11 | 5498.08 | 22-FEB-17:00 | 5407.37 | 0.00 |
March | 0.00 | 0.00 | 0.170152E+11 | 0.169520E+11 | 7814.46 | 31-MAR-23:22 | 7814.46 | 0.00 |
April | 0.00 | 0.00 | 0.218718E+11 | 0.217716E+11 | 9396.66 | 26-APR-16:00 | 9223.15 | 0.00 |
May | 0.00 | 0.00 | 0.741515E+10 | 0.734271E+10 | 4408.63 | 31-MAY-23:51 | 4402.52 | 0.00 |
June | 0.00 | 0.00 | 0.123878E+11 | 0.122354E+11 | 6534.33 | 30-JUN-23:51 | 6533.80 | 0.00 |
July | 0.00 | 0.00 | 0.183774E+11 | 0.181336E+11 | 8566.75 | 31-JUL-23:05 | 8452.13 | 0.00 |
August | 0.00 | 0.00 | 0.235309E+11 | 0.232276E+11 | 9691.95 | 17-AUG-16:00 | 9336.29 | 0.00 |
September | 0.00 | 0.00 | 0.758617E+10 | 0.742430E+10 | 4690.65 | 30-SEP-23:51 | 4690.65 | 0.00 |
October | 0.00 | 0.00 | 0.126884E+11 | 0.125900E+11 | 6429.10 | 31-OCT-23:51 | 6428.62 | 0.00 |
November | 0.00 | 0.00 | 0.166857E+11 | 0.166400E+11 | 7489.70 | 07-NOV-16:12 | 7352.53 | 0.00 |
December | 0.00 | 0.00 | 0.221426E+11 | 0.221206E+11 | 9436.41 | 07-DEC-16:10 | 9261.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.177166E+12 | 0.175836E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.682114E+10 | 0.679489E+10 | 3497.98 | 3442.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.235309E+11 | 0.232276E+11 | 9691.95 | 9336.29 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.537322E+11 | 0.534732E+11 | 32654.38 | 18-JAN-16:10 | 32108.43 | 0.00 |
February | 0.00 | 0.00 | 0.939827E+11 | 0.935783E+11 | 52375.27 | 22-FEB-17:00 | 51470.85 | 0.00 |
March | 0.00 | 0.00 | 0.154622E+12 | 0.153992E+12 | 71817.74 | 31-MAR-23:03 | 71817.74 | 0.00 |
April | 0.00 | 0.00 | 0.203251E+12 | 0.202257E+12 | 89565.62 | 26-APR-16:00 | 87825.80 | 0.00 |
May | 0.00 | 0.00 | 0.638645E+11 | 0.631502E+11 | 39129.18 | 31-MAY-23:11 | 38905.95 | 0.00 |
June | 0.00 | 0.00 | 0.114223E+12 | 0.112707E+12 | 61359.02 | 30-JUN-23:51 | 61352.78 | 0.00 |
July | 0.00 | 0.00 | 0.170589E+12 | 0.168164E+12 | 80591.12 | 31-JUL-23:05 | 79563.89 | 0.00 |
August | 0.00 | 0.00 | 0.219531E+12 | 0.216512E+12 | 92097.72 | 17-AUG-16:00 | 88549.11 | 0.00 |
September | 0.00 | 0.00 | 0.663423E+11 | 0.647443E+11 | 44070.40 | 30-SEP-23:42 | 44070.40 | 0.00 |
October | 0.00 | 0.00 | 0.115554E+12 | 0.114575E+12 | 59179.94 | 31-OCT-23:31 | 59161.01 | 0.00 |
November | 0.00 | 0.00 | 0.151473E+12 | 0.151018E+12 | 71306.60 | 07-NOV-16:12 | 69928.58 | 0.00 |
December | 0.00 | 0.00 | 0.202142E+12 | 0.201924E+12 | 89232.37 | 07-DEC-16:10 | 87452.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.160931E+13 | 0.159609E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.537322E+11 | 0.534732E+11 | 32654.38 | 32108.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.219531E+12 | 0.216512E+12 | 92097.72 | 88549.11 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.411734E+10 | 0.409175E+10 | 3375.52 | 18-JAN-16:10 | 3320.18 | 0.00 |
February | 0.00 | 0.00 | 0.842043E+10 | 0.838030E+10 | 5355.37 | 22-FEB-17:00 | 5265.06 | 0.00 |
March | 0.00 | 0.00 | 0.145777E+11 | 0.145150E+11 | 7299.12 | 23-MAR-16:00 | 7070.04 | 0.00 |
April | 0.00 | 0.00 | 0.198740E+11 | 0.197761E+11 | 9195.65 | 26-APR-16:00 | 9022.27 | 0.00 |
May | 0.00 | 0.00 | 0.596094E+10 | 0.588944E+10 | 3615.98 | 31-MAY-23:11 | 3592.20 | 0.00 |
June | 0.00 | 0.00 | 0.112482E+11 | 0.110961E+11 | 5946.50 | 30-JUN-23:11 | 5939.57 | 0.00 |
July | 0.00 | 0.00 | 0.170302E+11 | 0.167874E+11 | 7906.91 | 31-JUL-23:05 | 7827.61 | 0.00 |
August | 0.00 | 0.00 | 0.218736E+11 | 0.215724E+11 | 9451.32 | 17-AUG-16:00 | 9096.44 | 0.00 |
September | 0.00 | 0.00 | 0.630596E+10 | 0.614580E+10 | 4242.65 | 30-SEP-23:12 | 4242.65 | 0.00 |
October | 0.00 | 0.00 | 0.110020E+11 | 0.109042E+11 | 5691.99 | 15-OCT-16:32 | 5691.99 | 0.00 |
November | 0.00 | 0.00 | 0.141380E+11 | 0.140927E+11 | 7223.94 | 10-NOV-16:01 | 7027.68 | 0.00 |
December | 0.00 | 0.00 | 0.189569E+11 | 0.189367E+11 | 9011.16 | 07-DEC-16:10 | 8835.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.153505E+12 | 0.152188E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.411734E+10 | 0.409175E+10 | 3375.52 | 3320.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.218736E+11 | 0.215724E+11 | 9451.32 | 9096.44 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 29665.37 | 1655040.24 | 27-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 27667.96 | 1584082.91 | 06-FEB-05:11 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 29391.67 | 1641901.99 | 10-MAR-05:11 |
April | 0.00 | 0.00 | 01-APR-00:03 | 11665.64 | 1519124.99 | 01-APR-04:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8609.27 | 1346205.63 | 27-MAY-05:01 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 2442.70 | 417998.66 | 01-JUN-05:02 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 649.04 | 128476.78 | 06-JUL-05:04 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 938.81 | 92877.24 | 23-AUG-05:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 3247.22 | 398653.13 | 20-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 6329.18 | 1441463.59 | 12-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17782.09 | 1606219.36 | 30-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 25567.54 | 1624019.90 | 21-DEC-05:11 |
Annual Sum or Average | 0.00 | 13601.40 | ||||
Minimum of Months | 0.00 | 0.00 | 649.04 | 92877.24 | ||
Maximum of Months | 0.00 | 0.00 | 29665.37 | 1655040.24 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 136810.79 | 2369124.03 | 18-JAN-14:02 | 226800.41 | 809024.49 | 08-JAN-09:20 |
February | 142817.52 | 1837124.24 | 01-FEB-11:50 | 86653.05 | 785206.79 | 01-FEB-00:01 |
March | 179738.93 | 1874227.82 | 23-MAR-14:05 | 4837.79 | 678912.64 | 01-MAR-00:01 |
April | 281710.52 | 2134033.73 | 12-APR-14:05 | 6373.95 | 549567.54 | 26-APR-21:06 |
May | 170444.29 | 1650599.85 | 03-MAY-13:00 | 134210.41 | 808999.33 | 28-MAY-05:10 |
June | 403969.79 | 2208601.13 | 27-JUN-12:05 | 25426.95 | 658138.67 | 12-JUN-04:11 |
July | 630327.30 | 2309420.90 | 25-JUL-15:40 | 15620.74 | 511766.17 | 27-JUL-21:09 |
August | 768711.61 | 2589914.45 | 15-AUG-16:00 | 10891.25 | 518341.48 | 31-AUG-23:40 |
September | 377818.05 | 2217124.09 | 05-SEP-13:10 | 91071.37 | 809034.67 | 17-SEP-09:50 |
October | 516725.39 | 2828431.93 | 30-OCT-13:02 | 37617.85 | 763568.99 | 16-OCT-03:31 |
November | 243152.29 | 2512485.74 | 28-NOV-12:02 | 5598.66 | 524413.48 | 01-NOV-00:03 |
December | 267274.12 | 2447513.09 | 19-DEC-14:04 | 6619.54 | 357921.66 | 17-DEC-16:45 |
Annual Sum or Average | 345121.69 | 54287.54 | ||||
Minimum of Months | 136810.79 | 1650599.85 | 4837.79 | 357921.66 | ||
Maximum of Months | 768711.61 | 2828431.93 | 226800.41 | 809034.67 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 157870.79 | 2758502.24 | 18-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 175784.47 | 1773913.06 | 01-FEB-11:40 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 287986.98 | 1760208.77 | 12-MAR-13:41 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 382328.46 | 2153824.83 | 12-APR-14:00 | 0.00 | 0.00 | 01-APR-00:03 |
May | 203626.76 | 1632649.82 | 03-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 447106.75 | 3241736.78 | 30-JUN-05:01 | 0.00 | 0.00 | 01-JUN-00:01 |
July | 677913.38 | 3836882.75 | 25-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:01 |
August | 793836.89 | 3585333.35 | 07-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 403385.66 | 4181332.79 | 30-SEP-04:02 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 552457.88 | 3886695.77 | 05-OCT-04:11 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 345322.13 | 2286886.34 | 10-NOV-06:02 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 367285.17 | 1984986.71 | 17-DEC-12:52 | 0.00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 401470.05 | 0.00 | ||||
Minimum of Months | 157870.79 | 1632649.82 | 0.00 | 0.00 | ||
Maximum of Months | 793836.89 | 4181332.79 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 12564.79 | 44637.39 | 31-JAN-12:23 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 12655.77 | 44639.26 | 02-FEB-12:38 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 13307.34 | 44418.31 | 01-MAR-12:45 |
April | 0.00 | 0.00 | 01-APR-00:03 | 12208.92 | 43614.13 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 12302.43 | 42650.75 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12321.69 | 41560.07 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 11166.97 | 40717.84 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 12214.87 | 40638.33 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 11582.51 | 41325.57 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11820.77 | 42413.99 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 12295.21 | 43470.46 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 12103.52 | 44259.75 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 12209.62 | ||||
Minimum of Months | 0.00 | 0.00 | 11166.97 | 40638.33 | ||
Maximum of Months | 0.00 | 0.00 | 13307.34 | 44639.26 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 164071.33 | 3066281.97 | 18-JAN-14:02 | 1224.64 | 131229.59 | 06-JAN-05:10 |
February | 179287.44 | 3029946.31 | 01-FEB-11:50 | 39.22 | 52582.09 | 28-FEB-17:55 |
March | 197743.35 | 3132649.74 | 23-MAR-13:30 | 1276.18 | 91516.20 | 30-MAR-06:10 |
April | 346909.73 | 3206960.84 | 26-APR-12:30 | 245.65 | 62036.22 | 01-APR-18:50 |
May | 210121.03 | 2771633.81 | 03-MAY-12:40 | 820.31 | 87430.41 | 02-MAY-02:20 |
June | 522882.02 | 3604535.10 | 29-JUN-10:05 | 1.39 | 10386.32 | 06-JUN-20:44 |
July | 944919.17 | 4827597.68 | 31-JUL-13:00 | 0.19 | 4266.83 | 02-JUL-18:56 |
August | 1190229.04 | 5274223.79 | 17-AUG-14:05 | 124.78 | 19456.56 | 30-AUG-22:00 |
September | 506816.79 | 4267576.57 | 22-SEP-12:00 | 337.29 | 82374.42 | 03-SEP-02:40 |
October | 711238.95 | 4559544.57 | 04-OCT-10:50 | 37.11 | 50429.77 | 27-OCT-05:50 |
November | 276244.64 | 2950584.51 | 28-NOV-12:40 | 1130.93 | 106572.86 | 03-NOV-01:35 |
December | 310404.54 | 3081697.55 | 29-DEC-11:50 | 1700.43 | 126373.12 | 22-DEC-07:10 |
Annual Sum or Average | 466290.94 | 584.24 | ||||
Minimum of Months | 164071.33 | 2771633.81 | 0.19 | 4266.83 | ||
Maximum of Months | 1190229.04 | 5274223.79 | 1700.43 | 131229.59 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.117239E+11 | 0.58 | 22356.61 | 03-JAN-06:01 | 1.66 |
February | 0.104724E+11 | 0.59 | 20823.53 | 04-FEB-06:01 | 1.62 |
March | 0.126982E+11 | 0.63 | 20823.53 | 01-MAR-06:01 | 1.61 |
April | 0.140200E+11 | 0.66 | 19937.03 | 01-APR-05:01 | 1.58 |
May | 0.126704E+11 | 0.63 | 18746.55 | 27-MAY-05:01 | 1.54 |
June | 0.138187E+11 | 0.67 | 18216.42 | 26-JUN-04:11 | 1.51 |
July | 0.161315E+11 | 0.70 | 22601.03 | 28-JUL-04:11 | 1.66 |
August | 0.189453E+11 | 0.76 | 22172.98 | 07-AUG-04:11 | 1.64 |
September | 0.138654E+11 | 0.65 | 21892.54 | 29-SEP-15:50 | 1.64 |
October | 0.141712E+11 | 0.65 | 22606.56 | 16-OCT-15:40 | 1.67 |
November | 0.128043E+11 | 0.62 | 21441.82 | 13-NOV-06:01 | 1.62 |
December | 0.127541E+11 | 0.61 | 20823.53 | 13-DEC-06:01 | 1.61 |
Annual Sum or Average | 0.164075E+12 | 0.65 | |||
Minimum of Months | 0.104724E+11 | 0.58 | 18216.42 | 1.51 | |
Maximum of Months | 0.189453E+11 | 0.76 | 22606.56 | 1.67 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.951085E+11 | 0.56 | 201779.14 | 14-JAN-06:03 | 1.66 |
February | 0.855185E+11 | 0.56 | 218751.47 | 03-FEB-06:01 | 1.72 |
March | 0.991458E+11 | 0.59 | 218751.47 | 22-MAR-05:01 | 1.70 |
April | 0.105481E+12 | 0.60 | 192161.60 | 04-APR-05:01 | 1.61 |
May | 0.103944E+12 | 0.59 | 218751.47 | 27-MAY-05:01 | 1.71 |
June | 0.114059E+12 | 0.63 | 169823.68 | 01-JUN-05:01 | 1.52 |
July | 0.123061E+12 | 0.64 | 169823.68 | 01-JUL-04:11 | 1.52 |
August | 0.139297E+12 | 0.69 | 174182.87 | 17-AUG-14:05 | 1.54 |
September | 0.116618E+12 | 0.62 | 207885.79 | 29-SEP-16:00 | 1.67 |
October | 0.116216E+12 | 0.61 | 218751.47 | 12-OCT-05:01 | 1.71 |
November | 0.984604E+11 | 0.57 | 218751.47 | 03-NOV-05:01 | 1.71 |
December | 0.967090E+11 | 0.57 | 218751.47 | 12-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.129362E+13 | 0.60 | |||
Minimum of Months | 0.855185E+11 | 0.56 | 169823.68 | 1.52 | |
Maximum of Months | 0.139297E+12 | 0.69 | 218751.47 | 1.72 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.884466E+10 | 0.50 | 13214.69 | 18-JAN-15:20 | 1.25 |
February | 0.785835E+10 | 0.50 | 13184.87 | 02-FEB-14:52 | 1.25 |
March | 0.927330E+10 | 0.52 | 15823.22 | 23-MAR-15:00 | 1.34 |
April | 0.103534E+11 | 0.54 | 18196.14 | 26-APR-14:00 | 1.42 |
May | 0.103298E+11 | 0.54 | 17419.36 | 03-MAY-05:01 | 1.40 |
June | 0.115541E+11 | 0.57 | 17419.36 | 06-JUN-05:01 | 1.40 |
July | 0.127242E+11 | 0.58 | 18585.46 | 31-JUL-14:30 | 1.44 |
August | 0.140216E+11 | 0.62 | 18991.12 | 17-AUG-14:50 | 1.45 |
September | 0.111338E+11 | 0.55 | 22624.11 | 29-SEP-15:50 | 1.57 |
October | 0.107646E+11 | 0.54 | 21399.05 | 16-OCT-15:40 | 1.53 |
November | 0.874607E+10 | 0.50 | 13455.16 | 10-NOV-14:30 | 1.25 |
December | 0.875790E+10 | 0.50 | 13368.83 | 05-DEC-15:15 | 1.26 |
Annual Sum or Average | 0.124362E+12 | 0.54 | |||
Minimum of Months | 0.785835E+10 | 0.50 | 13184.87 | 1.25 | |
Maximum of Months | 0.140216E+11 | 0.62 | 22624.11 | 1.57 |
Report: FanReportMonthly
For: CAV_BAS SZVAV FAN
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.930038E+10 | 0.62 | 15916.73 | 02-JAN-05:11 | 1.83 |
February | 0.852110E+10 | 0.61 | 15916.73 | 01-FEB-05:11 | 1.83 |
March | 0.993821E+10 | 0.65 | 15916.73 | 01-MAR-05:11 | 1.83 |
April | 0.972524E+10 | 0.64 | 15916.73 | 01-APR-04:11 | 1.83 |
May | 0.886102E+10 | 0.61 | 15916.73 | 01-MAY-04:12 | 1.82 |
June | 0.822012E+10 | 0.63 | 15916.73 | 01-JUN-04:11 | 1.82 |
July | 0.791045E+10 | 0.59 | 15916.73 | 01-JUL-04:11 | 1.82 |
August | 0.866153E+10 | 0.65 | 15916.73 | 01-AUG-04:11 | 1.82 |
September | 0.807979E+10 | 0.61 | 15916.73 | 01-SEP-04:12 | 1.82 |
October | 0.846760E+10 | 0.62 | 15916.73 | 01-OCT-20:28 | 1.82 |
November | 0.114054E+11 | 0.69 | 15916.73 | 01-NOV-04:12 | 1.83 |
December | 0.950312E+10 | 0.62 | 15916.73 | 01-DEC-05:12 | 1.83 |
Annual Sum or Average | 0.108594E+12 | 0.63 | |||
Minimum of Months | 0.791045E+10 | 0.59 | 15916.73 | 1.82 | |
Maximum of Months | 0.114054E+11 | 0.69 | 15916.73 | 1.83 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SYS11 FAN
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.267049E+11 | 0.52 | 9970.47 | 01-JAN-00:10 | 0.52 |
February | 0.394684E+11 | 0.61 | 33207.74 | 01-FEB-00:26 | 0.86 |
March | 0.649524E+11 | 0.73 | 33207.74 | 01-MAR-00:02 | 0.86 |
April | 0.855806E+11 | 0.86 | 33207.74 | 01-APR-00:03 | 0.86 |
May | 0.267342E+11 | 0.52 | 33207.74 | 31-MAY-23:02 | 0.86 |
June | 0.422657E+11 | 0.61 | 33207.74 | 01-JUN-00:01 | 0.86 |
July | 0.698920E+11 | 0.76 | 33207.74 | 01-JUL-00:02 | 0.86 |
August | 0.863130E+11 | 0.84 | 33207.74 | 01-AUG-00:10 | 0.85 |
September | 0.258783E+11 | 0.52 | 33207.74 | 30-SEP-23:02 | 0.86 |
October | 0.418130E+11 | 0.60 | 33207.74 | 01-OCT-00:02 | 0.86 |
November | 0.628908E+11 | 0.73 | 33207.74 | 01-NOV-00:01 | 0.86 |
December | 0.883893E+11 | 0.86 | 33207.74 | 01-DEC-00:02 | 0.87 |
Annual Sum or Average | 0.660883E+12 | 0.68 | |||
Minimum of Months | 0.258783E+11 | 0.52 | 9970.47 | 0.52 | |
Maximum of Months | 0.883893E+11 | 0.86 | 33207.74 | 0.87 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.345252E+10 | 1.43 | 1289.03 | 01-JAN-05:20 | 1.43 |
February | 0.311841E+10 | 1.43 | 1289.03 | 01-FEB-00:48 | 1.43 |
March | 0.345252E+10 | 1.43 | 1289.03 | 01-MAR-01:01 | 1.43 |
April | 0.334115E+10 | 1.43 | 1289.03 | 01-APR-00:34 | 1.43 |
May | 0.345252E+10 | 1.43 | 1289.03 | 01-MAY-05:38 | 1.43 |
June | 0.334115E+10 | 1.43 | 1289.03 | 01-JUN-00:40 | 1.43 |
July | 0.345252E+10 | 1.43 | 1289.03 | 01-JUL-01:02 | 1.43 |
August | 0.345252E+10 | 1.43 | 1289.03 | 01-AUG-02:70 | 1.43 |
September | 0.334115E+10 | 1.42 | 1289.03 | 01-SEP-07:23 | 1.43 |
October | 0.345252E+10 | 1.43 | 1289.03 | 01-OCT-03:11 | 1.43 |
November | 0.334115E+10 | 1.43 | 1289.03 | 01-NOV-02:51 | 1.43 |
December | 0.345252E+10 | 1.43 | 1289.03 | 01-DEC-00:41 | 1.44 |
Annual Sum or Average | 0.406507E+11 | 1.43 | |||
Minimum of Months | 0.311841E+10 | 1.42 | 1289.03 | 1.43 | |
Maximum of Months | 0.345252E+10 | 1.43 | 1289.03 | 1.44 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.330161E+11 | 1.43 | 12326.81 | 02-JAN-20:00 | 1.43 |
February | 0.298210E+11 | 1.43 | 12326.81 | 01-FEB-00:01 | 1.43 |
March | 0.330161E+11 | 1.43 | 12326.81 | 01-MAR-13:53 | 1.43 |
April | 0.319511E+11 | 1.43 | 12326.81 | 02-APR-04:53 | 1.43 |
May | 0.330161E+11 | 1.43 | 12326.81 | 06-MAY-13:35 | 1.43 |
June | 0.319511E+11 | 1.43 | 12326.81 | 01-JUN-00:01 | 1.43 |
July | 0.330161E+11 | 1.43 | 12326.81 | 01-JUL-17:40 | 1.43 |
August | 0.330161E+11 | 1.43 | 12326.81 | 05-AUG-04:57 | 1.43 |
September | 0.319511E+11 | 1.42 | 12326.81 | 03-SEP-12:38 | 1.43 |
October | 0.330161E+11 | 1.43 | 12326.81 | 01-OCT-00:11 | 1.43 |
November | 0.319511E+11 | 1.43 | 12326.81 | 01-NOV-12:57 | 1.43 |
December | 0.330161E+11 | 1.43 | 12326.81 | 01-DEC-05:57 | 1.44 |
Annual Sum or Average | 0.388738E+12 | 1.43 | |||
Minimum of Months | 0.298210E+11 | 1.42 | 12326.81 | 1.43 | |
Maximum of Months | 0.330161E+11 | 1.43 | 12326.81 | 1.44 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.341278E+10 | 1.43 | 1274.19 | 01-JAN-00:20 | 1.43 |
February | 0.308251E+10 | 1.43 | 1274.19 | 01-FEB-00:03 | 1.43 |
March | 0.341278E+10 | 1.43 | 1274.19 | 01-MAR-00:07 | 1.43 |
April | 0.330269E+10 | 1.43 | 1274.19 | 01-APR-00:07 | 1.43 |
May | 0.341278E+10 | 1.43 | 1274.19 | 01-MAY-01:20 | 1.43 |
June | 0.330269E+10 | 1.43 | 1274.19 | 01-JUN-00:04 | 1.43 |
July | 0.341278E+10 | 1.43 | 1274.19 | 01-JUL-00:29 | 1.43 |
August | 0.341278E+10 | 1.43 | 1274.19 | 01-AUG-00:40 | 1.43 |
September | 0.330269E+10 | 1.42 | 1274.19 | 01-SEP-01:30 | 1.43 |
October | 0.341278E+10 | 1.43 | 1274.19 | 01-OCT-00:23 | 1.43 |
November | 0.330269E+10 | 1.43 | 1274.19 | 01-NOV-00:08 | 1.43 |
December | 0.341278E+10 | 1.43 | 1274.19 | 01-DEC-00:03 | 1.44 |
Annual Sum or Average | 0.401828E+11 | 1.43 | |||
Minimum of Months | 0.308251E+10 | 1.42 | 1274.19 | 1.43 | |
Maximum of Months | 0.341278E+10 | 1.43 | 1274.19 | 1.44 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 95613071.86 | 86051764.67 | 2347.38 | 09-JAN-06:02 | 2112.64 | 2112.64 | 50.52 | 11.46 |
February | 76222791.17 | 68600512.05 | 2300.89 | 06-FEB-06:01 | 2070.80 | 2070.80 | 41.00 | 11.36 |
March | 91571899.76 | 82414709.78 | 2338.52 | 30-MAR-05:01 | 2104.67 | 2104.67 | 45.15 | 11.46 |
April | 32667796.03 | 29401016.43 | 1974.49 | 01-APR-05:01 | 1777.04 | 1777.04 | 40.57 | 10.27 |
May | 23845677.56 | 21461109.80 | 1924.10 | 27-MAY-05:01 | 1731.69 | 1731.69 | 34.41 | 10.11 |
June | 5964965.72 | 5368469.15 | 397.46 | 01-JUN-05:02 | 357.71 | 357.71 | 24.12 | 2.41 |
July | 1580989.31 | 1422890.37 | 116.28 | 06-JUL-05:04 | 104.65 | 104.65 | 20.74 | 0.69 |
August | 2285288.40 | 2056759.56 | 83.55 | 23-AUG-05:10 | 75.19 | 75.19 | 20.26 | 0.49 |
September | 7980297.30 | 7182267.57 | 403.25 | 20-SEP-05:03 | 362.92 | 362.92 | 26.59 | 2.45 |
October | 18051618.83 | 16246456.95 | 1941.52 | 12-OCT-05:01 | 1747.37 | 1747.37 | 32.72 | 10.18 |
November | 52261443.43 | 47035299.09 | 2301.31 | 24-NOV-06:01 | 2071.18 | 2071.18 | 41.29 | 11.36 |
December | 78937413.04 | 71043671.74 | 2308.59 | 13-DEC-06:01 | 2077.73 | 2077.73 | 43.10 | 11.38 |
Annual Sum or Average | 0.486983E+09 | 0.438285E+09 | ||||||
Minimum of Months | 1580989.31 | 1422890.37 | 83.55 | 75.19 | 75.19 | 20.26 | 0.49 | |
Maximum of Months | 95613071.86 | 86051764.67 | 2347.38 | 2112.64 | 2112.64 | 50.52 | 11.46 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.158312E+10 | 0.142481E+10 | 17185.98 | 18-JAN-14:00 | 15467.39 | 15467.39 | 9.81 | 96.29 |
February | 0.203584E+10 | 0.183225E+10 | 6912.17 | 22-FEB-13:48 | 6220.95 | 6220.95 | 7.58 | 55.37 |
March | 0.340183E+10 | 0.306165E+10 | 6379.93 | 12-MAR-13:41 | 5741.93 | 5741.93 | 9.07 | 52.14 |
April | 0.394398E+10 | 0.354958E+10 | 11698.54 | 27-APR-05:03 | 10528.68 | 10528.68 | 10.36 | 78.17 |
May | 0.192460E+10 | 0.173214E+10 | 5769.82 | 03-MAY-13:00 | 5192.84 | 5192.84 | 6.75 | 48.21 |
June | 0.405444E+10 | 0.364899E+10 | 22981.36 | 30-JUN-05:01 | 20683.22 | 20683.22 | 9.26 | 110.82 |
July | 0.549295E+10 | 0.494366E+10 | 22981.36 | 15-JUL-05:01 | 20683.22 | 20683.22 | 10.05 | 110.82 |
August | 0.623668E+10 | 0.561302E+10 | 19850.73 | 26-AUG-05:02 | 17865.65 | 17865.65 | 10.01 | 103.39 |
September | 0.340324E+10 | 0.306291E+10 | 17139.90 | 29-SEP-10:50 | 15425.91 | 15425.91 | 6.74 | 96.17 |
October | 0.516200E+10 | 0.464580E+10 | 22981.36 | 02-OCT-05:02 | 20683.22 | 20683.22 | 10.79 | 110.82 |
November | 0.377823E+10 | 0.340041E+10 | 16773.13 | 10-NOV-06:02 | 15095.82 | 15095.82 | 10.30 | 95.10 |
December | 0.388799E+10 | 0.349919E+10 | 10232.83 | 21-DEC-14:27 | 9209.55 | 9209.55 | 8.76 | 72.15 |
Annual Sum or Average | 0.449049E+11 | 0.404144E+11 | ||||||
Minimum of Months | 0.158312E+10 | 0.142481E+10 | 5769.82 | 5192.84 | 5192.84 | 6.74 | 48.21 | |
Maximum of Months | 0.623668E+10 | 0.561302E+10 | 22981.36 | 20683.22 | 20683.22 | 10.79 | 110.82 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.104107E+11 | 0.936960E+10 | 10540.55 | 01-JAN-00:10 | 9486.49 | 9486.49 | 6.78 | 55.41 |
February | 0.108555E+11 | 0.976997E+10 | 10540.55 | 01-FEB-00:26 | 9486.49 | 9486.49 | 7.18 | 55.41 |
March | 0.259999E+11 | 0.233999E+11 | 10540.55 | 01-MAR-00:04 | 9486.49 | 9486.49 | 7.63 | 55.41 |
April | 0.246501E+11 | 0.221851E+11 | 10540.55 | 01-APR-00:07 | 9486.49 | 9486.49 | 10.35 | 55.41 |
May | 0.141354E+11 | 0.127219E+11 | 10540.55 | 01-MAY-00:10 | 9486.49 | 9486.49 | 6.79 | 55.41 |
June | 0.186354E+11 | 0.167718E+11 | 10540.55 | 01-JUN-00:04 | 9486.49 | 9486.49 | 8.34 | 55.41 |
July | 0.245693E+11 | 0.221124E+11 | 10540.55 | 01-JUL-00:01 | 9486.49 | 9486.49 | 10.24 | 55.41 |
August | 0.257540E+11 | 0.231786E+11 | 10540.55 | 01-AUG-00:10 | 9486.49 | 9486.49 | 10.13 | 55.41 |
September | 0.166697E+11 | 0.150028E+11 | 10540.55 | 01-SEP-03:10 | 9486.49 | 9486.49 | 6.84 | 55.41 |
October | 0.193139E+11 | 0.173825E+11 | 10540.55 | 01-OCT-00:01 | 9486.49 | 9486.49 | 8.57 | 55.41 |
November | 0.253484E+11 | 0.228136E+11 | 10540.55 | 01-NOV-00:28 | 9486.49 | 9486.49 | 9.21 | 55.41 |
December | 0.248498E+11 | 0.223648E+11 | 10540.55 | 01-DEC-00:01 | 9486.49 | 9486.49 | 10.23 | 55.41 |
Annual Sum or Average | 0.241192E+12 | 0.217073E+12 | ||||||
Minimum of Months | 0.104107E+11 | 0.936960E+10 | 10540.55 | 9486.49 | 9486.49 | 6.78 | 55.41 | |
Maximum of Months | 0.259999E+11 | 0.233999E+11 | 10540.55 | 9486.49 | 9486.49 | 10.35 | 55.41 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 52808131.98 | 47527318.78 | 10540.55 | 13-JAN-13:25 | 9486.49 | 9486.49 | 13.68 | 27.70 |
February | 56918944.65 | 51227050.18 | 10540.55 | 01-FEB-11:20 | 9486.49 | 9486.49 | 13.35 | 27.70 |
March | 87486526.04 | 78737873.43 | 10540.55 | 22-MAR-12:40 | 9486.49 | 9486.49 | 13.61 | 27.70 |
April | 0.373135E+09 | 0.335822E+09 | 10540.55 | 04-APR-13:50 | 9486.49 | 9486.49 | 13.43 | 27.70 |
May | 34783799.51 | 31305419.56 | 10540.55 | 03-MAY-12:30 | 9486.49 | 9486.49 | 13.77 | 27.70 |
June | 0.111308E+10 | 0.100177E+10 | 10540.55 | 19-JUN-11:00 | 9486.49 | 9486.49 | 13.33 | 27.70 |
July | 0.415867E+10 | 0.374280E+10 | 10540.55 | 03-JUL-12:00 | 9486.49 | 9486.49 | 13.72 | 27.70 |
August | 0.645334E+10 | 0.580801E+10 | 10540.55 | 02-AUG-09:20 | 9486.49 | 9486.49 | 13.32 | 27.70 |
September | 0.179822E+10 | 0.161840E+10 | 10540.55 | 05-SEP-13:00 | 9486.49 | 9486.49 | 13.46 | 27.70 |
October | 0.318288E+10 | 0.286459E+10 | 10540.55 | 01-OCT-10:40 | 9486.49 | 9486.49 | 13.52 | 27.70 |
November | 0.138503E+09 | 0.124652E+09 | 10540.55 | 08-NOV-11:00 | 9486.49 | 9486.49 | 13.06 | 27.70 |
December | 0.626229E+09 | 0.563606E+09 | 10540.55 | 04-DEC-09:50 | 9486.49 | 9486.49 | 13.24 | 27.70 |
Annual Sum or Average | 0.180761E+11 | 0.162684E+11 | ||||||
Minimum of Months | 34783799.51 | 31305419.56 | 10540.55 | 9486.49 | 9486.49 | 13.06 | 27.70 | |
Maximum of Months | 0.645334E+10 | 0.580801E+10 | 10540.55 | 9486.49 | 9486.49 | 13.77 | 27.70 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:10 | 16.86 | 16.86 | 57.22 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 57.59 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 57.57 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:01 | 16.86 | 16.86 | 57.61 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:01 | 16.86 | 16.86 | 57.86 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:01 | 16.86 | 16.86 | 57.78 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:01 | 16.86 | 16.86 | 57.82 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 57.73 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:01 | 16.86 | 16.86 | 57.75 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:01 | 16.86 | 16.86 | 57.79 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 57.73 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 57.46 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 57.22 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.86 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.269401E+11 | 0.242461E+11 | 54511.80 | 18-JAN-14:02 | 49060.62 | 49060.62 | 25.79 | 156.36 |
February | 0.280805E+11 | 0.252725E+11 | 54509.26 | 01-FEB-11:50 | 49058.34 | 49058.34 | 25.74 | 156.36 |
March | 0.672175E+11 | 0.604957E+11 | 54516.44 | 23-MAR-13:30 | 49064.80 | 49064.80 | 25.89 | 156.36 |
April | 0.642826E+11 | 0.578543E+11 | 54521.63 | 26-APR-12:30 | 49069.47 | 49069.47 | 26.01 | 156.36 |
May | 0.365073E+11 | 0.328565E+11 | 54491.22 | 03-MAY-12:40 | 49042.09 | 49042.09 | 25.34 | 156.36 |
June | 0.505469E+11 | 0.454922E+11 | 54549.44 | 29-JUN-10:05 | 49094.50 | 49094.50 | 26.62 | 156.36 |
July | 0.735721E+11 | 0.662149E+11 | 54635.16 | 31-JUL-13:00 | 49171.64 | 49171.64 | 28.49 | 156.36 |
August | 0.820014E+11 | 0.738012E+11 | 54666.52 | 17-AUG-14:05 | 49199.87 | 49199.87 | 29.17 | 156.36 |
September | 0.469586E+11 | 0.422628E+11 | 54595.88 | 22-SEP-12:00 | 49136.29 | 49136.29 | 27.63 | 156.36 |
October | 0.570838E+11 | 0.513754E+11 | 54616.35 | 04-OCT-10:50 | 49154.72 | 49154.72 | 28.08 | 156.36 |
November | 0.656422E+11 | 0.590780E+11 | 54503.72 | 28-NOV-12:40 | 49053.34 | 49053.34 | 25.62 | 156.36 |
December | 0.654162E+11 | 0.588746E+11 | 54512.88 | 29-DEC-11:50 | 49061.59 | 49061.59 | 25.82 | 156.36 |
Annual Sum or Average | 0.664249E+12 | 0.597824E+12 | ||||||
Minimum of Months | 0.269401E+11 | 0.242461E+11 | 54491.22 | 49042.09 | 49042.09 | 25.34 | 156.36 | |
Maximum of Months | 0.820014E+11 | 0.738012E+11 | 54666.52 | 49199.87 | 49199.87 | 29.17 | 156.36 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 54.90 | 54.90 | 29665.37 | 1655040.24 | 27-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 24.01 | 24.01 | 27667.96 | 1584082.91 | 06-FEB-05:11 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 27.67 | 27.67 | 29391.67 | 1641901.99 | 10-MAR-05:11 |
April | 0.00 | 0.00 | 01-APR-00:03 | 25.15 | 25.15 | 11665.64 | 1519124.99 | 01-APR-04:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.08 | 22.08 | 8609.27 | 1346205.63 | 27-MAY-05:01 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 21.57 | 21.57 | 2442.70 | 417998.66 | 01-JUN-05:02 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.63 | 19.63 | 649.04 | 128476.78 | 06-JUL-05:04 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 19.40 | 19.40 | 938.81 | 92877.24 | 23-AUG-05:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 20.98 | 20.98 | 3247.22 | 398653.13 | 20-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 20.86 | 20.86 | 6329.18 | 1441463.59 | 12-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 23.21 | 23.21 | 17782.09 | 1606219.36 | 30-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 24.06 | 24.06 | 25567.54 | 1624019.90 | 21-DEC-05:11 |
Annual Sum or Average | 0.00 | 13601.40 | ||||||
Minimum of Months | 0.00 | 0.00 | 19.40 | 19.40 | 649.04 | 92877.24 | ||
Maximum of Months | 0.00 | 0.00 | 54.90 | 54.90 | 29665.37 | 1655040.24 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 136810.79 | 2369124.03 | 18-JAN-14:02 | 11.80 | 6.70 | 226800.41 | 809024.49 | 08-JAN-09:20 |
February | 142817.52 | 1837124.24 | 01-FEB-11:50 | 10.66 | 6.70 | 86653.05 | 785206.79 | 01-FEB-00:01 |
March | 179738.93 | 1874227.82 | 23-MAR-14:05 | 10.74 | 6.70 | 4837.79 | 678912.64 | 01-MAR-00:01 |
April | 281710.52 | 2134033.73 | 12-APR-14:05 | 11.30 | 6.70 | 6373.95 | 549567.54 | 26-APR-21:06 |
May | 170444.29 | 1650599.85 | 03-MAY-13:00 | 13.82 | 9.05 | 134210.41 | 808999.33 | 28-MAY-05:10 |
June | 403969.79 | 2208601.13 | 27-JUN-12:05 | 11.46 | 6.70 | 25426.95 | 658138.67 | 12-JUN-04:11 |
July | 630327.30 | 2309420.90 | 25-JUL-15:40 | 11.67 | 6.70 | 15620.74 | 511766.17 | 27-JUL-21:09 |
August | 768711.61 | 2589914.45 | 15-AUG-16:00 | 12.28 | 6.70 | 10891.25 | 518341.48 | 31-AUG-23:40 |
September | 377818.05 | 2217124.09 | 05-SEP-13:10 | 11.48 | 6.70 | 91071.37 | 809034.67 | 17-SEP-09:50 |
October | 516725.39 | 2828431.93 | 30-OCT-13:02 | 12.79 | 6.70 | 37617.85 | 763568.99 | 16-OCT-03:31 |
November | 243152.29 | 2512485.74 | 28-NOV-12:02 | 12.11 | 6.70 | 5598.66 | 524413.48 | 01-NOV-00:03 |
December | 267274.12 | 2447513.09 | 19-DEC-14:04 | 11.97 | 6.70 | 6619.54 | 357921.66 | 17-DEC-16:45 |
Annual Sum or Average | 345121.69 | 54287.54 | ||||||
Minimum of Months | 136810.79 | 1650599.85 | 10.66 | 6.70 | 4837.79 | 357921.66 | ||
Maximum of Months | 768711.61 | 2828431.93 | 13.82 | 9.05 | 226800.41 | 809034.67 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 157870.79 | 2758502.24 | 18-JAN-14:00 | 13.54 | 9.83 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 175784.47 | 1773913.06 | 01-FEB-11:40 | 16.60 | 9.21 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 287986.98 | 1760208.77 | 12-MAR-13:41 | 14.77 | 9.49 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 382328.46 | 2153824.83 | 12-APR-14:00 | 15.14 | 7.90 | 0.00 | 0.00 | 01-APR-00:03 |
May | 203626.76 | 1632649.82 | 03-MAY-13:00 | 14.79 | 6.71 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 447106.75 | 3241736.78 | 30-JUN-05:01 | 13.69 | 11.22 | 0.00 | 0.00 | 01-JUN-00:01 |
July | 677913.38 | 3836882.75 | 25-JUL-05:02 | 14.97 | 12.17 | 0.00 | 0.00 | 01-JUL-00:01 |
August | 793836.89 | 3585333.35 | 07-AUG-05:02 | 15.72 | 11.15 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 403385.66 | 4181332.79 | 30-SEP-04:02 | 18.62 | 12.37 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 552457.88 | 3886695.77 | 05-OCT-04:11 | 17.10 | 12.02 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 345322.13 | 2286886.34 | 10-NOV-06:02 | 12.44 | 10.68 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 367285.17 | 1984986.71 | 17-DEC-12:52 | 17.82 | 8.56 | 0.00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 401470.05 | 0.00 | ||||||
Minimum of Months | 157870.79 | 1632649.82 | 12.44 | 6.71 | 0.00 | 0.00 | ||
Maximum of Months | 793836.89 | 4181332.79 | 18.62 | 12.37 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.36 | 58.36 | 12564.79 | 44637.39 | 31-JAN-12:23 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 57.92 | 57.92 | 12655.77 | 44639.26 | 02-FEB-12:38 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 57.94 | 57.94 | 13307.34 | 44418.31 | 01-MAR-12:45 |
April | 0.00 | 0.00 | 01-APR-00:03 | 57.97 | 57.97 | 12208.92 | 43614.13 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.43 | 58.43 | 12302.43 | 42650.75 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 58.07 | 58.07 | 12321.69 | 41560.07 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 58.11 | 58.11 | 11166.97 | 40717.84 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.13 | 58.13 | 12214.87 | 40638.33 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.12 | 58.12 | 11582.51 | 41325.57 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 58.08 | 58.08 | 11820.77 | 42413.99 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 58.03 | 58.03 | 12295.21 | 43470.46 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 57.98 | 57.98 | 12103.52 | 44259.75 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 12209.62 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.92 | 57.92 | 11166.97 | 40638.33 | ||
Maximum of Months | 0.00 | 0.00 | 58.43 | 58.43 | 13307.34 | 44639.26 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 164071.33 | 3066281.97 | 18-JAN-14:02 | 25.79 | 21.10 | 1224.64 | 131229.59 | 06-JAN-05:10 |
February | 179287.44 | 3029946.31 | 01-FEB-11:50 | 25.74 | 21.10 | 39.22 | 52582.09 | 28-FEB-17:55 |
March | 197743.35 | 3132649.74 | 23-MAR-13:30 | 25.89 | 21.68 | 1276.18 | 91516.20 | 30-MAR-06:10 |
April | 346909.73 | 3206960.84 | 26-APR-12:30 | 26.01 | 21.79 | 245.65 | 62036.22 | 01-APR-18:50 |
May | 210121.03 | 2771633.81 | 03-MAY-12:40 | 25.34 | 21.10 | 820.31 | 87430.41 | 02-MAY-02:20 |
June | 522882.02 | 3604535.10 | 29-JUN-10:05 | 26.62 | 22.76 | 1.39 | 10386.32 | 06-JUN-20:44 |
July | 944919.17 | 4827597.68 | 31-JUL-13:00 | 28.49 | 24.62 | 0.19 | 4266.83 | 02-JUL-18:56 |
August | 1190229.04 | 5274223.79 | 17-AUG-14:05 | 29.17 | 24.90 | 124.78 | 19456.56 | 30-AUG-22:00 |
September | 506816.79 | 4267576.57 | 22-SEP-12:00 | 27.63 | 24.53 | 337.29 | 82374.42 | 03-SEP-02:40 |
October | 711238.95 | 4559544.57 | 04-OCT-10:50 | 28.08 | 23.85 | 37.11 | 50429.77 | 27-OCT-05:50 |
November | 276244.64 | 2950584.51 | 28-NOV-12:40 | 25.62 | 21.10 | 1130.93 | 106572.86 | 03-NOV-01:35 |
December | 310404.54 | 3081697.55 | 29-DEC-11:50 | 25.82 | 21.10 | 1700.43 | 126373.12 | 22-DEC-07:10 |
Annual Sum or Average | 466290.94 | 584.24 | ||||||
Minimum of Months | 164071.33 | 2771633.81 | 25.34 | 21.10 | 0.19 | 4266.83 | ||
Maximum of Months | 1190229.04 | 5274223.79 | 29.17 | 24.90 | 1700.43 | 131229.59 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.215591E+10 | 0.00 | 0.287911E+11 | 0.117239E+11 | 0.00 | 0.00 |
February | 0.173507E+10 | 0.00 | 0.158245E+11 | 0.104724E+11 | 0.00 | 0.00 |
March | 0.195890E+10 | 0.00 | 0.190220E+11 | 0.126982E+11 | 0.00 | 0.00 |
April | 0.414487E+09 | 0.00 | 0.410494E+11 | 0.140200E+11 | 0.00 | 0.00 |
May | 0.372291E+09 | 0.00 | 0.389289E+11 | 0.126704E+11 | 0.00 | 0.00 |
June | 28806004.33 | 0.00 | 0.677300E+11 | 0.138187E+11 | 0.00 | 0.00 |
July | 884770.56 | 0.00 | 0.120491E+12 | 0.161315E+11 | 0.00 | 0.00 |
August | 677391.38 | 0.00 | 0.147759E+12 | 0.189453E+11 | 0.00 | 0.00 |
September | 45458677.81 | 0.00 | 0.809651E+11 | 0.138654E+11 | 0.00 | 0.00 |
October | 0.251904E+09 | 0.00 | 0.942051E+11 | 0.141712E+11 | 0.00 | 0.00 |
November | 0.668414E+09 | 0.00 | 0.317781E+11 | 0.128043E+11 | 0.00 | 0.00 |
December | 0.128182E+10 | 0.00 | 0.371607E+11 | 0.127541E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.891461E+10 | 0.00 | 0.723705E+12 | 0.164075E+12 | 0.00 | 0.00 |
Minimum of Months | 677391.38 | 0.00 | 0.158245E+11 | 0.104724E+11 | 0.00 | 0.00 |
Maximum of Months | 0.215591E+10 | 0.00 | 0.147759E+12 | 0.189453E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.638674E+11 | 0.00 | 0.267453E+12 | 0.951085E+11 | 0.00 | 0.00 |
February | 0.540723E+11 | 0.00 | 0.143037E+12 | 0.855185E+11 | 0.00 | 0.00 |
March | 0.645435E+11 | 0.00 | 0.169330E+12 | 0.991458E+11 | 0.00 | 0.00 |
April | 0.246000E+11 | 0.00 | 0.329174E+12 | 0.105481E+12 | 0.00 | 0.00 |
May | 0.183183E+11 | 0.00 | 0.333053E+12 | 0.103944E+12 | 0.00 | 0.00 |
June | 0.481037E+10 | 0.00 | 0.580395E+12 | 0.114059E+12 | 0.00 | 0.00 |
July | 0.113395E+10 | 0.00 | 0.978665E+12 | 0.123061E+12 | 0.00 | 0.00 |
August | 0.171234E+10 | 0.00 | 0.116753E+13 | 0.139297E+12 | 0.00 | 0.00 |
September | 0.632484E+10 | 0.00 | 0.704780E+12 | 0.116618E+12 | 0.00 | 0.00 |
October | 0.130746E+11 | 0.00 | 0.816216E+12 | 0.116216E+12 | 0.00 | 0.00 |
November | 0.365461E+11 | 0.00 | 0.282721E+12 | 0.984604E+11 | 0.00 | 0.00 |
December | 0.552594E+11 | 0.00 | 0.312154E+12 | 0.967090E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.344263E+12 | 0.00 | 0.608451E+13 | 0.129362E+13 | 0.00 | 0.00 |
Minimum of Months | 0.113395E+10 | 0.00 | 0.143037E+12 | 0.855185E+11 | 0.00 | 0.00 |
Maximum of Months | 0.645435E+11 | 0.00 | 0.116753E+13 | 0.139297E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.138651E+11 | 0.00 | 0.223541E+11 | 0.884466E+10 | 0.00 | 0.00 |
February | 0.113195E+11 | 0.00 | 0.123609E+11 | 0.785835E+10 | 0.00 | 0.00 |
March | 0.125038E+11 | 0.00 | 0.154281E+11 | 0.927330E+10 | 0.00 | 0.00 |
April | 0.533192E+10 | 0.00 | 0.356551E+11 | 0.103534E+11 | 0.00 | 0.00 |
May | 0.444154E+10 | 0.00 | 0.355569E+11 | 0.103298E+11 | 0.00 | 0.00 |
June | 0.151926E+10 | 0.00 | 0.644178E+11 | 0.115541E+11 | 0.00 | 0.00 |
July | 0.609224E+09 | 0.00 | 0.112069E+12 | 0.127242E+11 | 0.00 | 0.00 |
August | 0.800715E+09 | 0.00 | 0.130403E+12 | 0.140216E+11 | 0.00 | 0.00 |
September | 0.207099E+10 | 0.00 | 0.738802E+11 | 0.111338E+11 | 0.00 | 0.00 |
October | 0.366637E+10 | 0.00 | 0.837121E+11 | 0.107646E+11 | 0.00 | 0.00 |
November | 0.901870E+10 | 0.00 | 0.233191E+11 | 0.874607E+10 | 0.00 | 0.00 |
December | 0.121789E+11 | 0.00 | 0.272896E+11 | 0.875790E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.773261E+11 | 0.00 | 0.636445E+12 | 0.124362E+12 | 0.00 | 0.00 |
Minimum of Months | 0.609224E+09 | 0.00 | 0.123609E+11 | 0.785835E+10 | 0.00 | 0.00 |
Maximum of Months | 0.138651E+11 | 0.00 | 0.130403E+12 | 0.140216E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.259487E+11 | 0.930038E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.185073E+11 | 0.852110E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.196006E+11 | 0.993821E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.293326E+11 | 0.972524E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.315251E+11 | 0.886102E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.511059E+11 | 0.822012E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.779213E+11 | 0.791045E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.926240E+11 | 0.866153E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.583201E+11 | 0.807979E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.608769E+11 | 0.846760E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.236249E+11 | 0.114054E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.268539E+11 | 0.950312E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.516241E+12 | 0.108594E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.185073E+11 | 0.791045E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.926240E+11 | 0.114054E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.789937E+10 | 0.785198E+11 | 0.00 | 19.28 |
February | 0.00 | 0.00 | 0.141882E+12 | 0.752199E+11 | 0.00 | 13.30 |
March | 0.00 | 0.00 | 0.228041E+12 | 0.886686E+11 | 0.00 | 8.82 |
April | 0.00 | 0.00 | 0.259022E+12 | 0.983160E+11 | 0.00 | 4.74 |
May | 0.00 | 0.00 | 0.192307E+10 | 0.306183E+11 | 0.00 | 1.44 |
June | 0.00 | 0.00 | 0.246577E+12 | 0.423545E+11 | 0.00 | 0.03 |
July | 0.00 | 0.00 | 0.337351E+12 | 0.703296E+11 | 0.00 | 0.16 |
August | 0.00 | 0.00 | 0.440714E+12 | 0.869116E+11 | 0.00 | 0.22 |
September | 0.00 | 0.00 | 0.190487E+11 | 0.267804E+11 | 0.00 | 0.34 |
October | 0.00 | 0.00 | 0.278204E+12 | 0.792213E+11 | 0.00 | 13.92 |
November | 0.00 | 0.00 | 0.236804E+12 | 0.123822E+12 | 0.00 | 22.67 |
December | 0.00 | 0.00 | 0.274652E+12 | 0.211534E+12 | 0.00 | 45.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.247212E+13 | 0.101230E+13 | 0.00 | 130.73 |
Minimum of Months | 0.00 | 0.00 | 0.192307E+10 | 0.267804E+11 | 0.00 | 0.03 |
Maximum of Months | 0.00 | 0.00 | 0.440714E+12 | 0.211534E+12 | 0.00 | 45.81 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.551575E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.609609E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.787743E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.904640E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.567061E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.676724E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.820755E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.966420E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.561537E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.701527E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.766855E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.922901E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.883735E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.551575E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.966420E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.471840E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.526438E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.678657E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.772610E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.495619E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.591993E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.710583E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.825675E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.491680E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.610686E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.660047E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.779993E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.761582E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.471840E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.825675E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.469368E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.551248E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.731534E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.844461E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.522471E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.645646E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.787724E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.915265E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.522499E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.656955E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.708654E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.832084E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.818791E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.469368E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.915265E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.117239E+11 | 0.287911E+11 | 0.215591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104724E+11 | 0.158245E+11 | 0.173507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126982E+11 | 0.190220E+11 | 0.195890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140200E+11 | 0.410494E+11 | 0.414487E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126704E+11 | 0.389289E+11 | 0.372291E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138187E+11 | 0.677300E+11 | 28806004.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161315E+11 | 0.120491E+12 | 884770.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189453E+11 | 0.147759E+12 | 677391.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138654E+11 | 0.809651E+11 | 45458677.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141712E+11 | 0.942051E+11 | 0.251904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128043E+11 | 0.317781E+11 | 0.668414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127541E+11 | 0.371607E+11 | 0.128182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164075E+12 | 0.723705E+12 | 0.891461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104724E+11 | 0.158245E+11 | 677391.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189453E+11 | 0.147759E+12 | 0.215591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.951085E+11 | 0.267453E+12 | 0.638674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.855185E+11 | 0.143037E+12 | 0.540723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.991458E+11 | 0.169330E+12 | 0.645435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105481E+12 | 0.329174E+12 | 0.246000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103944E+12 | 0.333053E+12 | 0.183183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114059E+12 | 0.580395E+12 | 0.481037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123061E+12 | 0.978665E+12 | 0.113395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139297E+12 | 0.116753E+13 | 0.171234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116618E+12 | 0.704780E+12 | 0.632484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116216E+12 | 0.816216E+12 | 0.130746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.984604E+11 | 0.282721E+12 | 0.365461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.967090E+11 | 0.312154E+12 | 0.552594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129362E+13 | 0.608451E+13 | 0.344263E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.855185E+11 | 0.143037E+12 | 0.113395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139297E+12 | 0.116753E+13 | 0.645435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.884466E+10 | 0.223541E+11 | 0.138651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.785835E+10 | 0.123609E+11 | 0.113195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.927330E+10 | 0.154281E+11 | 0.125038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103534E+11 | 0.356551E+11 | 0.533192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103298E+11 | 0.355569E+11 | 0.444154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.115541E+11 | 0.644178E+11 | 0.151926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.127242E+11 | 0.112069E+12 | 0.609224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140216E+11 | 0.130403E+12 | 0.800715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111338E+11 | 0.738802E+11 | 0.207099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107646E+11 | 0.837121E+11 | 0.366637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.874607E+10 | 0.233191E+11 | 0.901870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.875790E+10 | 0.272896E+11 | 0.121789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124362E+12 | 0.636445E+12 | 0.773261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.785835E+10 | 0.123609E+11 | 0.609224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140216E+11 | 0.130403E+12 | 0.138651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.930038E+10 | 0.259487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.852110E+10 | 0.185073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.993821E+10 | 0.196006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.972524E+10 | 0.293326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.886102E+10 | 0.315251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.822012E+10 | 0.511059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.791045E+10 | 0.779213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.866153E+10 | 0.926240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.807979E+10 | 0.583201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.846760E+10 | 0.608769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114054E+11 | 0.236249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.950312E+10 | 0.268539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108594E+12 | 0.516241E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.791045E+10 | 0.185073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114054E+11 | 0.926240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.267049E+11 | 0.789937E+10 | 0.00 | 0.00 | 0.00 | 0.515827E+11 | 0.00 | 0.00 |
February | 0.394684E+11 | 0.141882E+12 | 0.00 | 0.00 | 0.00 | 0.355912E+11 | 0.00 | 0.00 |
March | 0.649524E+11 | 0.228041E+12 | 0.00 | 0.00 | 0.00 | 0.236099E+11 | 0.00 | 0.00 |
April | 0.855806E+11 | 0.259022E+12 | 0.00 | 0.00 | 0.00 | 0.126784E+11 | 0.00 | 0.00 |
May | 0.267342E+11 | 0.192307E+10 | 0.00 | 0.00 | 0.00 | 0.386672E+10 | 0.00 | 0.00 |
June | 0.422657E+11 | 0.246577E+12 | 0.00 | 0.00 | 0.00 | 88420602.63 | 0.00 | 0.00 |
July | 0.698920E+11 | 0.337351E+12 | 0.00 | 0.00 | 0.00 | 0.435687E+09 | 0.00 | 0.00 |
August | 0.863130E+11 | 0.440714E+12 | 0.00 | 0.00 | 0.00 | 0.595846E+09 | 0.00 | 0.00 |
September | 0.258783E+11 | 0.190487E+11 | 0.00 | 0.00 | 0.00 | 0.898071E+09 | 0.00 | 0.00 |
October | 0.418130E+11 | 0.278204E+12 | 0.00 | 0.00 | 0.00 | 0.372406E+11 | 0.00 | 0.00 |
November | 0.628908E+11 | 0.236804E+12 | 0.00 | 0.00 | 0.00 | 0.606583E+11 | 0.00 | 0.00 |
December | 0.883893E+11 | 0.274652E+12 | 0.00 | 0.00 | 0.00 | 0.122592E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.660883E+12 | 0.247212E+13 | 0.00 | 0.00 | 0.00 | 0.349838E+12 | 0.00 | 0.00 |
Minimum of Months | 0.258783E+11 | 0.192307E+10 | 0.00 | 0.00 | 0.00 | 88420602.63 | 0.00 | 0.00 |
Maximum of Months | 0.883893E+11 | 0.440714E+12 | 0.00 | 0.00 | 0.00 | 0.122592E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.345252E+10 | 0.682114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311841E+10 | 0.106436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.345252E+10 | 0.170152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.334115E+10 | 0.218718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.345252E+10 | 0.741515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.334115E+10 | 0.123878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.345252E+10 | 0.183774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.345252E+10 | 0.235309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.334115E+10 | 0.758617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.345252E+10 | 0.126884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.334115E+10 | 0.166857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.345252E+10 | 0.221426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.406507E+11 | 0.177166E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.311841E+10 | 0.682114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.345252E+10 | 0.235309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.330161E+11 | 0.537322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.298210E+11 | 0.939827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.330161E+11 | 0.154622E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.319511E+11 | 0.203251E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.330161E+11 | 0.638645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.319511E+11 | 0.114223E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.330161E+11 | 0.170589E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.330161E+11 | 0.219531E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.319511E+11 | 0.663423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.330161E+11 | 0.115554E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.319511E+11 | 0.151473E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.330161E+11 | 0.202142E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.388738E+12 | 0.160931E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.298210E+11 | 0.537322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.330161E+11 | 0.219531E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.341278E+10 | 0.411734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308251E+10 | 0.842043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.341278E+10 | 0.145777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.330269E+10 | 0.198740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.341278E+10 | 0.596094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.330269E+10 | 0.112482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.341278E+10 | 0.170302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.341278E+10 | 0.218736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.330269E+10 | 0.630596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.341278E+10 | 0.110020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.330269E+10 | 0.141380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.341278E+10 | 0.189569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.401828E+11 | 0.153505E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.308251E+10 | 0.411734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.341278E+10 | 0.218736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.117239E+11 | 0.215591E+10 | 0.287911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104724E+11 | 0.173507E+10 | 0.158245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126982E+11 | 0.195890E+10 | 0.190220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140200E+11 | 0.414487E+09 | 0.410494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126704E+11 | 0.372291E+09 | 0.389289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138187E+11 | 28806004.33 | 0.677300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161315E+11 | 884770.56 | 0.120491E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189453E+11 | 677391.38 | 0.147759E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138654E+11 | 45458677.81 | 0.809651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141712E+11 | 0.251904E+09 | 0.942051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128043E+11 | 0.668414E+09 | 0.317781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127541E+11 | 0.128182E+10 | 0.371607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164075E+12 | 0.891461E+10 | 0.723705E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104724E+11 | 677391.38 | 0.158245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189453E+11 | 0.215591E+10 | 0.147759E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.951085E+11 | 0.638674E+11 | 0.267453E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.855185E+11 | 0.540723E+11 | 0.143037E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.991458E+11 | 0.645435E+11 | 0.169330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105481E+12 | 0.246000E+11 | 0.329174E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103944E+12 | 0.183183E+11 | 0.333053E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114059E+12 | 0.481037E+10 | 0.580395E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123061E+12 | 0.113395E+10 | 0.978665E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139297E+12 | 0.171234E+10 | 0.116753E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116618E+12 | 0.632484E+10 | 0.704780E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116216E+12 | 0.130746E+11 | 0.816216E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.984604E+11 | 0.365461E+11 | 0.282721E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.967090E+11 | 0.552594E+11 | 0.312154E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129362E+13 | 0.344263E+12 | 0.608451E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.855185E+11 | 0.113395E+10 | 0.143037E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139297E+12 | 0.645435E+11 | 0.116753E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.884466E+10 | 0.138651E+11 | 0.223541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.785835E+10 | 0.113195E+11 | 0.123609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.927330E+10 | 0.125038E+11 | 0.154281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103534E+11 | 0.533192E+10 | 0.356551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103298E+11 | 0.444154E+10 | 0.355569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.115541E+11 | 0.151926E+10 | 0.644178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.127242E+11 | 0.609224E+09 | 0.112069E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140216E+11 | 0.800715E+09 | 0.130403E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111338E+11 | 0.207099E+10 | 0.738802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107646E+11 | 0.366637E+10 | 0.837121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.874607E+10 | 0.901870E+10 | 0.233191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.875790E+10 | 0.121789E+11 | 0.272896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124362E+12 | 0.773261E+11 | 0.636445E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.785835E+10 | 0.609224E+09 | 0.123609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140216E+11 | 0.138651E+11 | 0.130403E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.930038E+10 | 0.00 | 0.259487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.852110E+10 | 0.00 | 0.185073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.993821E+10 | 0.00 | 0.196006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.972524E+10 | 0.00 | 0.293326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.886102E+10 | 0.00 | 0.315251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.822012E+10 | 0.00 | 0.511059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.791045E+10 | 0.00 | 0.779213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.866153E+10 | 0.00 | 0.926240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.807979E+10 | 0.00 | 0.583201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.846760E+10 | 0.00 | 0.608769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114054E+11 | 0.00 | 0.236249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.950312E+10 | 0.00 | 0.268539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108594E+12 | 0.00 | 0.516241E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.791045E+10 | 0.00 | 0.185073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114054E+11 | 0.00 | 0.926240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.267049E+11 | 0.00 | 0.789937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518149E+11 | 0.00 | 0.00 | 0.00 |
February | 0.394684E+11 | 0.00 | 0.141882E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357514E+11 | 0.00 | 0.00 | 0.00 |
March | 0.649524E+11 | 0.00 | 0.228041E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237162E+11 | 0.00 | 0.00 | 0.00 |
April | 0.855806E+11 | 0.00 | 0.259022E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127354E+11 | 0.00 | 0.00 | 0.00 |
May | 0.267342E+11 | 0.00 | 0.192307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388413E+10 | 0.00 | 0.00 | 0.00 |
June | 0.422657E+11 | 0.00 | 0.246577E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88818619.60 | 0.00 | 0.00 | 0.00 |
July | 0.698920E+11 | 0.00 | 0.337351E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437649E+09 | 0.00 | 0.00 | 0.00 |
August | 0.863130E+11 | 0.00 | 0.440714E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598528E+09 | 0.00 | 0.00 | 0.00 |
September | 0.258783E+11 | 0.00 | 0.190487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.902113E+09 | 0.00 | 0.00 | 0.00 |
October | 0.418130E+11 | 0.00 | 0.278204E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374082E+11 | 0.00 | 0.00 | 0.00 |
November | 0.628908E+11 | 0.00 | 0.236804E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609313E+11 | 0.00 | 0.00 | 0.00 |
December | 0.883893E+11 | 0.00 | 0.274652E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123144E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.660883E+12 | 0.00 | 0.247212E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351413E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.258783E+11 | 0.00 | 0.192307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88818619.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.883893E+11 | 0.00 | 0.440714E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123144E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.345252E+10 | 0.00 | 0.00 | 0.00 | 0.206322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311841E+10 | 0.00 | 0.00 | 0.00 | 0.297768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.345252E+10 | 0.00 | 0.00 | 0.00 | 0.442490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.334115E+10 | 0.00 | 0.00 | 0.00 | 0.570525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.345252E+10 | 0.00 | 0.00 | 0.00 | 0.221808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.334115E+10 | 0.00 | 0.00 | 0.00 | 0.342609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.345252E+10 | 0.00 | 0.00 | 0.00 | 0.475502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.345252E+10 | 0.00 | 0.00 | 0.00 | 0.621168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.334115E+10 | 0.00 | 0.00 | 0.00 | 0.227422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.345252E+10 | 0.00 | 0.00 | 0.00 | 0.356275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.334115E+10 | 0.00 | 0.00 | 0.00 | 0.432740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.345252E+10 | 0.00 | 0.00 | 0.00 | 0.577648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.406507E+11 | 0.00 | 0.00 | 0.00 | 0.477228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.311841E+10 | 0.00 | 0.00 | 0.00 | 0.206322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.345252E+10 | 0.00 | 0.00 | 0.00 | 0.621168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.330161E+11 | 0.00 | 0.00 | 0.00 | 0.141679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.298210E+11 | 0.00 | 0.00 | 0.00 | 0.228228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.330161E+11 | 0.00 | 0.00 | 0.00 | 0.348496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.319511E+11 | 0.00 | 0.00 | 0.00 | 0.453099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.330161E+11 | 0.00 | 0.00 | 0.00 | 0.165458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.319511E+11 | 0.00 | 0.00 | 0.00 | 0.272482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.330161E+11 | 0.00 | 0.00 | 0.00 | 0.380422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.330161E+11 | 0.00 | 0.00 | 0.00 | 0.495514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.319511E+11 | 0.00 | 0.00 | 0.00 | 0.172169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.330161E+11 | 0.00 | 0.00 | 0.00 | 0.280525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.319511E+11 | 0.00 | 0.00 | 0.00 | 0.340536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.330161E+11 | 0.00 | 0.00 | 0.00 | 0.449832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.388738E+12 | 0.00 | 0.00 | 0.00 | 0.372844E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.298210E+11 | 0.00 | 0.00 | 0.00 | 0.141679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.330161E+11 | 0.00 | 0.00 | 0.00 | 0.495514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.341278E+10 | 0.00 | 0.00 | 0.00 | 0.128089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308251E+10 | 0.00 | 0.00 | 0.00 | 0.242997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.341278E+10 | 0.00 | 0.00 | 0.00 | 0.390255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.330269E+10 | 0.00 | 0.00 | 0.00 | 0.514192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.341278E+10 | 0.00 | 0.00 | 0.00 | 0.181192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.330269E+10 | 0.00 | 0.00 | 0.00 | 0.315376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.341278E+10 | 0.00 | 0.00 | 0.00 | 0.446446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.341278E+10 | 0.00 | 0.00 | 0.00 | 0.573987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.330269E+10 | 0.00 | 0.00 | 0.00 | 0.192230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.341278E+10 | 0.00 | 0.00 | 0.00 | 0.315676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.330269E+10 | 0.00 | 0.00 | 0.00 | 0.378385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.341278E+10 | 0.00 | 0.00 | 0.00 | 0.490806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.401828E+11 | 0.00 | 0.00 | 0.00 | 0.416963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.308251E+10 | 0.00 | 0.00 | 0.00 | 0.128089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.341278E+10 | 0.00 | 0.00 | 0.00 | 0.573987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.441904E+10 | 0.118711E+09 | 0.00 | 0.170898E+09 | 0.00 | 0.00 | 0.467041E+11 | 0.00 | 0.94 |
February | 0.617027E+10 | 6133471.68 | 0.00 | 0.373467E+09 | 0.00 | 0.00 | 0.415502E+11 | 0.00 | 0.94 |
March | 0.807592E+10 | 78832396.52 | 0.00 | 0.457718E+09 | 0.00 | 0.00 | 0.507041E+11 | 0.00 | 0.99 |
April | 0.326843E+10 | 0.122151E+09 | 0.00 | 0.173783E+09 | 0.00 | 0.00 | 0.424461E+11 | 0.00 | 1.07 |
May | 0.254049E+10 | 8151001.61 | 0.00 | 0.147897E+09 | 0.00 | 0.00 | 0.416880E+11 | 0.00 | 1.03 |
June | 0.142122E+10 | 0.287375E+10 | 0.00 | 0.483891E+09 | 0.00 | 0.00 | 0.255396E+11 | 0.00 | 1.06 |
July | 0.212089E+09 | 0.123232E+11 | 0.00 | 0.247603E+09 | 70359728.55 | 0.00 | 0.112906E+11 | 0.00 | 0.94 |
August | 0.150167E+09 | 0.168475E+11 | 0.00 | 85290220.63 | 46876935.14 | 0.00 | 0.985147E+10 | 0.00 | 1.04 |
September | 0.679435E+09 | 0.591627E+10 | 0.00 | 0.111284E+09 | 41462950.38 | 0.00 | 0.214999E+11 | 0.00 | 1.02 |
October | 0.111818E+10 | 0.738423E+10 | 0.00 | 0.381811E+09 | 21895609.98 | 0.00 | 0.242343E+11 | 0.00 | 0.95 |
November | 0.469982E+10 | 5099925.30 | 0.00 | 0.533022E+09 | 0.00 | 0.00 | 0.512603E+11 | 0.00 | 1.16 |
December | 0.486738E+10 | 0.00 | 0.00 | 0.221948E+09 | 0.00 | 0.00 | 0.461169E+11 | 0.00 | 0.95 |
Annual Sum or Average | 0.376224E+11 | 0.456840E+11 | 0.00 | 0.338861E+10 | 0.180595E+09 | 0.00 | 0.412885E+12 | 0.00 | 1.01 |
Minimum of Months | 0.150167E+09 | 0.00 | 0.00 | 85290220.63 | 0.00 | 0.00 | 0.985147E+10 | 0.00 | 0.94 |
Maximum of Months | 0.807592E+10 | 0.168475E+11 | 0.00 | 0.533022E+09 | 70359728.55 | 0.00 | 0.512603E+11 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.562576E+10 | 33853986.09 | 0.00 | 0.174701E+09 | 42768879.06 | 0.00 | 0.406727E+11 | 0.00 | 0.84 |
February | 0.104618E+11 | 16927899.97 | 0.00 | 0.393756E+09 | 0.00 | 0.00 | 0.364514E+11 | 0.00 | 0.89 |
March | 0.699072E+10 | 0.00 | 0.00 | 0.611842E+09 | 3303488.72 | 0.00 | 0.506829E+11 | 0.00 | 0.96 |
April | 0.473052E+10 | 12212474.12 | 0.00 | 0.215285E+09 | 41928700.58 | 0.00 | 0.447574E+11 | 0.00 | 1.09 |
May | 0.515030E+10 | 27373639.81 | 0.00 | 0.151622E+09 | 0.00 | 0.00 | 0.422598E+11 | 0.00 | 1.06 |
June | 0.346858E+10 | 0.562562E+09 | 0.00 | 0.477788E+09 | 42626.77 | 0.00 | 0.324480E+11 | 0.00 | 1.14 |
July | 0.311417E+10 | 0.383123E+10 | 0.00 | 0.246382E+09 | 0.191166E+09 | 0.00 | 0.161631E+11 | 0.00 | 1.03 |
August | 0.116461E+10 | 0.584624E+10 | 0.00 | 0.110495E+09 | 0.194731E+09 | 0.00 | 0.161319E+11 | 0.00 | 1.15 |
September | 0.269203E+10 | 0.161055E+10 | 0.00 | 0.114573E+09 | 37246838.71 | 0.00 | 0.263753E+11 | 0.00 | 1.05 |
October | 0.331358E+10 | 0.322953E+10 | 0.00 | 0.347026E+09 | 0.216852E+09 | 0.00 | 0.230018E+11 | 0.00 | 0.93 |
November | 0.480009E+10 | 5970972.76 | 0.00 | 0.597792E+09 | 28495923.68 | 0.00 | 0.454115E+11 | 0.00 | 1.00 |
December | 0.541722E+10 | 4087785.31 | 0.00 | 0.253187E+09 | 0.00 | 0.00 | 0.426091E+11 | 0.00 | 0.90 |
Annual Sum or Average | 0.569293E+11 | 0.151805E+11 | 0.00 | 0.369445E+10 | 0.756537E+09 | 0.00 | 0.416965E+12 | 0.00 | 1.00 |
Minimum of Months | 0.116461E+10 | 0.00 | 0.00 | 0.110495E+09 | 0.00 | 0.00 | 0.161319E+11 | 0.00 | 0.84 |
Maximum of Months | 0.104618E+11 | 0.584624E+10 | 0.00 | 0.611842E+09 | 0.216852E+09 | 0.00 | 0.506829E+11 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.137760E+12 | 0.117173E+09 | 0.00 | 0.965090E+09 | 0.873285E+09 | 0.00 | 0.203736E+12 | 0.00 | 0.64 |
February | 0.140809E+12 | 0.192953E+09 | 0.00 | 0.248689E+10 | 0.00 | 0.00 | 0.219317E+12 | 0.00 | 0.71 |
March | 0.153003E+12 | 0.00 | 0.00 | 0.338868E+10 | 0.192482E+09 | 0.00 | 0.270368E+12 | 0.00 | 0.73 |
April | 0.117418E+12 | 0.106184E+09 | 0.00 | 0.100696E+10 | 0.763401E+09 | 0.00 | 0.241742E+12 | 0.00 | 0.83 |
May | 0.994631E+11 | 0.303698E+09 | 0.00 | 0.939889E+09 | 0.00 | 0.00 | 0.275060E+12 | 0.00 | 0.87 |
June | 0.914813E+11 | 0.462635E+10 | 0.00 | 0.272089E+10 | 31346125.45 | 0.00 | 0.194184E+12 | 0.00 | 0.95 |
July | 0.570649E+11 | 0.300578E+11 | 0.00 | 0.881206E+09 | 0.330174E+10 | 0.00 | 0.797729E+11 | 0.00 | 0.81 |
August | 0.245205E+11 | 0.441500E+11 | 0.00 | 0.507818E+09 | 0.354563E+10 | 0.00 | 0.927733E+11 | 0.00 | 0.87 |
September | 0.511373E+11 | 0.139046E+11 | 0.00 | 0.676962E+09 | 0.115817E+10 | 0.00 | 0.177286E+12 | 0.00 | 0.87 |
October | 0.802739E+11 | 0.276702E+11 | 0.00 | 0.183615E+10 | 0.328139E+10 | 0.00 | 0.119172E+12 | 0.00 | 0.75 |
November | 0.136512E+12 | 55919622.69 | 0.00 | 0.311210E+10 | 0.273436E+09 | 0.00 | 0.219927E+12 | 0.00 | 0.73 |
December | 0.144019E+12 | 0.110445E+09 | 0.00 | 0.119976E+10 | 27078585.15 | 0.00 | 0.191635E+12 | 0.00 | 0.65 |
Annual Sum or Average | 0.123346E+13 | 0.121295E+12 | 0.00 | 0.197224E+11 | 0.134480E+11 | 0.00 | 0.228497E+13 | 0.00 | 0.78 |
Minimum of Months | 0.245205E+11 | 0.00 | 0.00 | 0.507818E+09 | 0.00 | 0.00 | 0.797729E+11 | 0.00 | 0.64 |
Maximum of Months | 0.153003E+12 | 0.441500E+11 | 0.00 | 0.338868E+10 | 0.354563E+10 | 0.00 | 0.275060E+12 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.192799E+11 | 1531729.23 | 0.00 | 43128554.51 | 43178100.75 | 0.443458E+09 | 0.113301E+11 | 0.00 | 0.61 |
February | 0.191782E+11 | 529329.05 | 0.00 | 0.134194E+09 | 0.00 | 0.148951E+09 | 0.139887E+11 | 0.00 | 0.68 |
March | 0.231176E+11 | 0.00 | 0.00 | 0.176619E+09 | 14374250.84 | 17793607.40 | 0.178434E+11 | 0.00 | 0.71 |
April | 0.155040E+11 | 0.00 | 0.00 | 76335182.45 | 24092692.98 | 0.00 | 0.248019E+11 | 0.00 | 0.87 |
May | 0.142716E+11 | 4441472.64 | 0.00 | 75058490.99 | 0.00 | 1988438.00 | 0.283346E+11 | 0.00 | 0.93 |
June | 0.108630E+11 | 76391839.32 | 0.00 | 0.245334E+09 | 0.00 | 0.00 | 0.238283E+11 | 0.00 | 1.04 |
July | 0.650563E+10 | 0.166558E+10 | 0.00 | 74909576.43 | 0.167032E+09 | 0.00 | 0.109774E+11 | 0.00 | 0.88 |
August | 0.364200E+10 | 0.212319E+10 | 0.00 | 52556961.94 | 0.336319E+09 | 0.00 | 0.999314E+10 | 0.00 | 0.93 |
September | 0.857061E+10 | 0.756825E+09 | 0.00 | 55581975.06 | 0.117981E+09 | 0.00 | 0.169029E+11 | 0.00 | 0.91 |
October | 0.107312E+11 | 0.194449E+10 | 0.00 | 0.100918E+09 | 0.447584E+09 | 9754665.20 | 0.825021E+10 | 0.00 | 0.74 |
November | 0.185779E+11 | 0.00 | 0.00 | 0.159591E+09 | 5522830.59 | 0.190506E+09 | 0.140546E+11 | 0.00 | 0.70 |
December | 0.188321E+11 | 1330297.42 | 0.00 | 51121266.50 | 1861122.23 | 0.222386E+09 | 0.994433E+10 | 0.00 | 0.62 |
Annual Sum or Average | 0.169074E+12 | 0.657431E+10 | 0.00 | 0.124535E+10 | 0.115794E+10 | 0.103484E+10 | 0.190250E+12 | 0.00 | 0.80 |
Minimum of Months | 0.364200E+10 | 0.00 | 0.00 | 43128554.51 | 0.00 | 0.00 | 0.825021E+10 | 0.00 | 0.61 |
Maximum of Months | 0.231176E+11 | 0.212319E+10 | 0.00 | 0.245334E+09 | 0.447584E+09 | 0.443458E+09 | 0.283346E+11 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.477338E+10 | 3213681.09 | 0.00 | 3150575.25 | 9814684.30 | 0.276314E+09 | 0.912336E+09 | 0.00 | 0.83 |
February | 0.448210E+10 | 2384334.23 | 0.00 | 15590006.58 | 0.00 | 84787142.63 | 0.149319E+10 | 0.00 | 0.89 |
March | 0.517312E+10 | 0.00 | 0.00 | 23771652.26 | 584036.78 | 0.120356E+09 | 0.200733E+10 | 0.00 | 0.96 |
April | 0.361183E+10 | 1832566.90 | 0.00 | 10441700.37 | 7412740.13 | 4445317.23 | 0.300850E+10 | 0.00 | 1.17 |
May | 0.328911E+10 | 4514024.93 | 0.00 | 11293376.06 | 0.00 | 0.00 | 0.364030E+10 | 0.00 | 1.25 |
June | 0.223511E+10 | 99922980.19 | 0.00 | 43744127.66 | 7536.15 | 0.00 | 0.330109E+10 | 0.00 | 1.44 |
July | 0.138534E+10 | 0.705803E+09 | 0.00 | 12639647.92 | 34474341.01 | 0.00 | 0.147818E+10 | 0.00 | 1.30 |
August | 0.117917E+10 | 0.972518E+09 | 0.00 | 5420492.33 | 34755239.65 | 0.00 | 0.107998E+10 | 0.00 | 1.33 |
September | 0.223696E+10 | 0.276378E+09 | 0.00 | 6851749.25 | 13410444.46 | 0.00 | 0.179376E+10 | 0.00 | 1.20 |
October | 0.263628E+10 | 0.527248E+09 | 0.00 | 12515567.11 | 55943812.18 | 0.00 | 0.966215E+09 | 0.00 | 1.02 |
November | 0.450041E+10 | 636936.01 | 0.00 | 18351948.51 | 5130770.15 | 1684738.01 | 0.162082E+10 | 0.00 | 0.94 |
December | 0.491755E+10 | 480853.39 | 0.00 | 5138002.68 | 0.00 | 65865822.16 | 0.928966E+09 | 0.00 | 0.86 |
Annual Sum or Average | 0.404204E+11 | 0.259493E+10 | 0.00 | 0.168909E+09 | 0.161534E+09 | 0.553453E+09 | 0.222307E+11 | 0.00 | 1.10 |
Minimum of Months | 0.117917E+10 | 0.00 | 0.00 | 3150575.25 | 0.00 | 0.00 | 0.912336E+09 | 0.00 | 0.83 |
Maximum of Months | 0.517312E+10 | 0.972518E+09 | 0.00 | 43744127.66 | 55943812.18 | 0.276314E+09 | 0.364030E+10 | 0.00 | 1.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.605970E+10 | 2191996.12 | 0.00 | 6835135.40 | 15574890.87 | 0.333390E+09 | 0.197012E+10 | 0.00 | 1.77 |
February | 0.680768E+10 | 1986981.67 | 0.00 | 14677268.69 | 237766.28 | 0.226247E+09 | 0.143008E+10 | 0.00 | 1.92 |
March | 0.775059E+10 | 220621.82 | 0.00 | 22390232.84 | 645709.06 | 0.224312E+09 | 0.208321E+10 | 0.00 | 2.02 |
April | 0.472352E+10 | 4362384.88 | 0.00 | 18419057.12 | 9026385.70 | 26670318.34 | 0.451290E+10 | 0.00 | 2.46 |
May | 0.511822E+10 | 5446141.54 | 0.00 | 12171265.21 | 0.00 | 2222515.87 | 0.401563E+10 | 0.00 | 2.45 |
June | 0.417603E+10 | 88943377.55 | 0.00 | 32828311.27 | 628389.54 | 0.00 | 0.275548E+10 | 0.00 | 2.67 |
July | 0.200940E+10 | 0.689209E+09 | 0.00 | 20131611.45 | 55385008.19 | 414203.89 | 0.190907E+10 | 0.00 | 2.53 |
August | 0.181658E+10 | 0.111864E+10 | 0.00 | 8633061.43 | 40062279.87 | 0.00 | 0.141281E+10 | 0.00 | 2.65 |
September | 0.334387E+10 | 0.234537E+09 | 0.00 | 9841456.32 | 28862254.05 | 1133804.08 | 0.218649E+10 | 0.00 | 2.36 |
October | 0.366951E+10 | 0.418442E+09 | 0.00 | 14576223.84 | 0.118370E+09 | 5642833.47 | 0.130824E+10 | 0.00 | 1.98 |
November | 0.677946E+10 | 585081.93 | 0.00 | 14258366.18 | 7132385.80 | 52357365.88 | 0.159472E+10 | 0.00 | 1.96 |
December | 0.652565E+10 | 515485.44 | 0.00 | 5645564.71 | 0.00 | 0.237278E+09 | 0.141251E+10 | 0.00 | 1.81 |
Annual Sum or Average | 0.587802E+11 | 0.256508E+10 | 0.00 | 0.180408E+09 | 0.275925E+09 | 0.110967E+10 | 0.265913E+11 | 0.00 | 2.22 |
Minimum of Months | 0.181658E+10 | 220621.82 | 0.00 | 5645564.71 | 0.00 | 0.00 | 0.130824E+10 | 0.00 | 1.77 |
Maximum of Months | 0.775059E+10 | 0.111864E+10 | 0.00 | 32828311.27 | 0.118370E+09 | 0.333390E+09 | 0.451290E+10 | 0.00 | 2.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.455806E+10 | 47109103.46 | 0.00 | 54203798.18 | 5429446.22 | 0.406891E+09 | 0.997905E+10 | 0.00 | 2.30 |
February | 0.550523E+10 | 8493877.05 | 0.00 | 93047848.95 | 0.00 | 0.284901E+09 | 0.705271E+10 | 0.00 | 2.09 |
March | 0.720095E+10 | 513227.53 | 0.00 | 73039039.56 | 667711.92 | 0.396906E+09 | 0.609386E+10 | 0.00 | 1.96 |
April | 0.582462E+10 | 5657112.86 | 0.00 | 18945450.86 | 10065635.28 | 55785060.48 | 0.532604E+10 | 0.00 | 2.07 |
May | 0.638293E+10 | 6009363.36 | 0.00 | 9655420.46 | 0.00 | 17561577.08 | 0.353550E+10 | 0.00 | 1.75 |
June | 0.517278E+10 | 0.116303E+09 | 0.00 | 16853850.58 | 11890.39 | 0.00 | 0.211510E+10 | 0.00 | 1.81 |
July | 0.278149E+10 | 0.817843E+09 | 0.00 | 5207037.42 | 58922540.79 | 0.00 | 0.112215E+10 | 0.00 | 1.65 |
August | 0.220001E+10 | 0.143719E+10 | 0.00 | 6130338.71 | 69140647.12 | 0.00 | 0.121228E+10 | 0.00 | 2.00 |
September | 0.360993E+10 | 0.516567E+09 | 0.00 | 17483568.62 | 27535200.16 | 0.00 | 0.358685E+10 | 0.00 | 2.32 |
October | 0.369249E+10 | 0.105653E+10 | 0.00 | 43873367.44 | 88279639.56 | 2399305.83 | 0.290094E+10 | 0.00 | 2.02 |
November | 0.524746E+10 | 11306954.03 | 0.00 | 0.117843E+09 | 1747538.85 | 52868298.63 | 0.885660E+10 | 0.00 | 2.44 |
December | 0.487234E+10 | 1528757.50 | 0.00 | 68861391.41 | 0.00 | 0.219394E+09 | 0.895166E+10 | 0.00 | 2.36 |
Annual Sum or Average | 0.570483E+11 | 0.402505E+10 | 0.00 | 0.525145E+09 | 0.261800E+09 | 0.143671E+10 | 0.607327E+11 | 0.00 | 2.06 |
Minimum of Months | 0.220001E+10 | 513227.53 | 0.00 | 5207037.42 | 0.00 | 0.00 | 0.112215E+10 | 0.00 | 1.65 |
Maximum of Months | 0.720095E+10 | 0.143719E+10 | 0.00 | 0.117843E+09 | 88279639.56 | 0.406891E+09 | 0.997905E+10 | 0.00 | 2.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.794852E+10 | 14187507.23 | 0.00 | 9914240.99 | 10939501.95 | 94059046.37 | 0.237968E+10 | 0.00 | 2.23 |
February | 0.820811E+10 | 3263753.70 | 0.00 | 27435320.63 | 61975.72 | 3108348.41 | 0.247009E+10 | 0.00 | 2.45 |
March | 0.919813E+10 | 0.00 | 0.00 | 38545670.98 | 984946.19 | 7000948.63 | 0.367619E+10 | 0.00 | 2.64 |
April | 0.567684E+10 | 7679835.83 | 0.00 | 24687415.78 | 8772990.57 | 828740.18 | 0.616919E+10 | 0.00 | 3.25 |
May | 0.607925E+10 | 4132070.04 | 0.00 | 14457771.67 | 0.00 | 1220759.54 | 0.526039E+10 | 0.00 | 3.08 |
June | 0.481393E+10 | 0.124344E+09 | 0.00 | 50018053.69 | 3592.98 | 0.00 | 0.389423E+10 | 0.00 | 3.44 |
July | 0.239286E+10 | 0.104889E+10 | 0.00 | 19301991.68 | 19751288.68 | 0.00 | 0.229382E+10 | 0.00 | 3.13 |
August | 0.142184E+10 | 0.148712E+10 | 0.00 | 12825209.16 | 29718562.16 | 0.00 | 0.230613E+10 | 0.00 | 3.40 |
September | 0.390749E+10 | 0.319512E+09 | 0.00 | 11623380.43 | 36359587.84 | 0.00 | 0.302669E+10 | 0.00 | 3.04 |
October | 0.465879E+10 | 0.597697E+09 | 0.00 | 16171594.75 | 98587863.93 | 0.00 | 0.127871E+10 | 0.00 | 2.46 |
November | 0.782884E+10 | 7316765.35 | 0.00 | 35003202.36 | 2909013.58 | 1151379.08 | 0.298263E+10 | 0.00 | 2.58 |
December | 0.757944E+10 | 829199.82 | 0.00 | 15412498.07 | 0.00 | 1602341.26 | 0.282572E+10 | 0.00 | 2.37 |
Annual Sum or Average | 0.697140E+11 | 0.361498E+10 | 0.00 | 0.275396E+09 | 0.208089E+09 | 0.108972E+09 | 0.385635E+11 | 0.00 | 2.84 |
Minimum of Months | 0.142184E+10 | 0.00 | 0.00 | 9914240.99 | 0.00 | 0.00 | 0.127871E+10 | 0.00 | 2.23 |
Maximum of Months | 0.919813E+10 | 0.148712E+10 | 0.00 | 50018053.69 | 98587863.93 | 94059046.37 | 0.616919E+10 | 0.00 | 3.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.399793E+11 | 3196491.79 | 0.00 | 8427607.46 | 0.173288E+09 | 0.111642E+11 | 0.191508E+10 | 0.00 | 0.75 |
February | 0.435938E+11 | 23883453.68 | 0.00 | 13698629.82 | 0.00 | 0.835178E+10 | 0.151400E+10 | 0.00 | 0.81 |
March | 0.484129E+11 | 0.00 | 0.00 | 37626511.94 | 35243788.38 | 0.970907E+10 | 0.433368E+10 | 0.00 | 0.82 |
April | 0.357398E+11 | 12169410.43 | 0.00 | 44281490.94 | 0.140746E+09 | 0.209210E+10 | 0.149128E+11 | 0.00 | 0.95 |
May | 0.340934E+11 | 46309302.11 | 0.00 | 64018678.26 | 0.00 | 0.338180E+09 | 0.221575E+11 | 0.00 | 1.04 |
June | 0.242524E+11 | 0.811760E+09 | 0.00 | 0.256666E+09 | 5739524.89 | 3073490.43 | 0.209973E+11 | 0.00 | 1.22 |
July | 0.140284E+11 | 0.575682E+10 | 0.00 | 50428984.41 | 0.446835E+09 | 0.00 | 0.843107E+10 | 0.00 | 1.07 |
August | 0.129969E+11 | 0.716840E+10 | 0.00 | 27680463.65 | 0.728666E+09 | 0.00 | 0.520884E+10 | 0.00 | 1.08 |
September | 0.242148E+11 | 0.241109E+10 | 0.00 | 36790875.53 | 0.171329E+09 | 26562037.74 | 0.992343E+10 | 0.00 | 1.03 |
October | 0.229429E+11 | 0.445567E+10 | 0.00 | 59442596.72 | 0.755782E+09 | 0.215407E+10 | 0.505148E+10 | 0.00 | 0.88 |
November | 0.432855E+11 | 4811758.67 | 0.00 | 12675949.45 | 51591941.41 | 0.601609E+10 | 0.206283E+10 | 0.00 | 0.80 |
December | 0.399533E+11 | 10663143.05 | 0.00 | 4438215.08 | 6835021.15 | 0.955163E+10 | 0.157071E+10 | 0.00 | 0.76 |
Annual Sum or Average | 0.383493E+12 | 0.207048E+11 | 0.00 | 0.616176E+09 | 0.251606E+10 | 0.494067E+11 | 0.980788E+11 | 0.00 | 0.93 |
Minimum of Months | 0.129969E+11 | 0.00 | 0.00 | 4438215.08 | 0.00 | 0.00 | 0.151400E+10 | 0.00 | 0.75 |
Maximum of Months | 0.484129E+11 | 0.716840E+10 | 0.00 | 0.256666E+09 | 0.755782E+09 | 0.111642E+11 | 0.221575E+11 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.478796E+11 | 25458783.34 | 0.00 | 41271010.91 | 0.158228E+09 | 0.105186E+11 | 0.107973E+11 | 0.00 | 1.46 |
February | 0.501037E+11 | 27249087.84 | 0.00 | 0.110492E+09 | 3981221.69 | 0.896109E+10 | 0.973467E+10 | 0.00 | 1.58 |
March | 0.571439E+11 | 5806486.15 | 0.00 | 0.180906E+09 | 46358296.50 | 0.976776E+10 | 0.146813E+11 | 0.00 | 1.68 |
April | 0.404904E+11 | 65819280.35 | 0.00 | 0.144959E+09 | 0.170546E+09 | 0.203012E+10 | 0.347681E+11 | 0.00 | 2.17 |
May | 0.451557E+11 | 69400625.79 | 0.00 | 0.102483E+09 | 0.00 | 0.482551E+09 | 0.313886E+11 | 0.00 | 2.15 |
June | 0.385726E+11 | 0.762165E+09 | 0.00 | 0.274352E+09 | 21413396.53 | 8537711.66 | 0.219043E+11 | 0.00 | 2.43 |
July | 0.185638E+11 | 0.644098E+10 | 0.00 | 0.154038E+09 | 0.751749E+09 | 4048185.90 | 0.149647E+11 | 0.00 | 2.35 |
August | 0.171479E+11 | 0.105478E+11 | 0.00 | 65185948.22 | 0.519659E+09 | 19715402.61 | 0.109421E+11 | 0.00 | 2.46 |
September | 0.307586E+11 | 0.216478E+10 | 0.00 | 80726153.04 | 0.325069E+09 | 0.143789E+09 | 0.174350E+11 | 0.00 | 2.15 |
October | 0.302855E+11 | 0.394983E+10 | 0.00 | 0.111126E+09 | 0.126391E+10 | 0.253590E+10 | 0.923493E+10 | 0.00 | 1.76 |
November | 0.543127E+11 | 5628640.73 | 0.00 | 0.102697E+09 | 67710645.73 | 0.418729E+10 | 0.946008E+10 | 0.00 | 1.59 |
December | 0.507901E+11 | 11673989.47 | 0.00 | 30618419.41 | 7074988.42 | 0.857805E+10 | 0.641513E+10 | 0.00 | 1.48 |
Annual Sum or Average | 0.481205E+12 | 0.240766E+11 | 0.00 | 0.139885E+10 | 0.333570E+10 | 0.472374E+11 | 0.191726E+12 | 0.00 | 1.94 |
Minimum of Months | 0.171479E+11 | 5628640.73 | 0.00 | 30618419.41 | 0.00 | 4048185.90 | 0.641513E+10 | 0.00 | 1.46 |
Maximum of Months | 0.571439E+11 | 0.105478E+11 | 0.00 | 0.274352E+09 | 0.126391E+10 | 0.105186E+11 | 0.347681E+11 | 0.00 | 2.46 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.377789E+11 | 0.605209E+09 | 0.00 | 0.535461E+09 | 84913880.79 | 0.855842E+10 | 0.849548E+11 | 0.00 | 2.11 |
February | 0.462323E+11 | 0.115155E+09 | 0.00 | 0.858081E+09 | 0.00 | 0.880453E+10 | 0.595400E+11 | 0.00 | 1.95 |
March | 0.620091E+11 | 31183629.07 | 0.00 | 0.606634E+09 | 33573009.70 | 0.106657E+11 | 0.480553E+11 | 0.00 | 1.80 |
April | 0.503877E+11 | 85344371.03 | 0.00 | 0.146556E+09 | 0.181092E+09 | 0.318942E+10 | 0.419405E+11 | 0.00 | 1.85 |
May | 0.587158E+11 | 63638401.56 | 0.00 | 67636395.67 | 0.00 | 0.220351E+10 | 0.251820E+11 | 0.00 | 1.57 |
June | 0.499825E+11 | 0.984060E+09 | 0.00 | 0.108093E+09 | 10895386.07 | 28791150.33 | 0.142297E+11 | 0.00 | 1.65 |
July | 0.250758E+11 | 0.704892E+10 | 0.00 | 33144885.60 | 0.101047E+10 | 4250984.12 | 0.799397E+10 | 0.00 | 1.49 |
August | 0.210739E+11 | 0.124287E+11 | 0.00 | 46746682.57 | 0.124750E+10 | 0.00 | 0.833850E+10 | 0.00 | 1.82 |
September | 0.334158E+11 | 0.523764E+10 | 0.00 | 0.151922E+09 | 0.431623E+09 | 18640307.82 | 0.308105E+11 | 0.00 | 2.19 |
October | 0.315241E+11 | 0.110261E+11 | 0.00 | 0.387727E+09 | 0.930587E+09 | 0.173272E+10 | 0.240131E+11 | 0.00 | 1.90 |
November | 0.432939E+11 | 0.153620E+09 | 0.00 | 0.109389E+10 | 13054127.80 | 0.421301E+10 | 0.722160E+11 | 0.00 | 2.17 |
December | 0.398695E+11 | 86968234.80 | 0.00 | 0.670249E+09 | 0.00 | 0.723612E+10 | 0.719397E+11 | 0.00 | 2.14 |
Annual Sum or Average | 0.499360E+12 | 0.378665E+11 | 0.00 | 0.470614E+10 | 0.394371E+10 | 0.466551E+11 | 0.489214E+12 | 0.00 | 1.88 |
Minimum of Months | 0.210739E+11 | 31183629.07 | 0.00 | 33144885.60 | 0.00 | 0.00 | 0.799397E+10 | 0.00 | 1.49 |
Maximum of Months | 0.620091E+11 | 0.124287E+11 | 0.00 | 0.109389E+10 | 0.124750E+10 | 0.106657E+11 | 0.849548E+11 | 0.00 | 2.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.600042E+11 | 0.101822E+09 | 0.00 | 52385462.05 | 0.187426E+09 | 0.125996E+11 | 0.115452E+11 | 0.00 | 1.85 |
February | 0.635028E+11 | 26179898.35 | 0.00 | 0.165707E+09 | 8184871.80 | 0.101712E+11 | 0.131667E+11 | 0.00 | 2.06 |
March | 0.731254E+11 | 0.00 | 0.00 | 0.221532E+09 | 54840373.25 | 0.102741E+11 | 0.199574E+11 | 0.00 | 2.16 |
April | 0.568290E+11 | 57765722.90 | 0.00 | 0.133480E+09 | 0.181949E+09 | 0.177047E+10 | 0.332622E+11 | 0.00 | 2.62 |
May | 0.591448E+11 | 41291559.99 | 0.00 | 97694439.52 | 6153930.50 | 0.916839E+09 | 0.324494E+11 | 0.00 | 2.61 |
June | 0.448838E+11 | 0.985399E+09 | 0.00 | 0.373959E+09 | 34157113.20 | 25064996.72 | 0.270322E+11 | 0.00 | 2.95 |
July | 0.224738E+11 | 0.780826E+10 | 0.00 | 0.119603E+09 | 0.112651E+10 | 0.00 | 0.144315E+11 | 0.00 | 2.61 |
August | 0.204448E+11 | 0.968916E+10 | 0.00 | 56185232.56 | 0.222538E+10 | 0.00 | 0.919273E+10 | 0.00 | 2.76 |
September | 0.379920E+11 | 0.237496E+10 | 0.00 | 79071471.91 | 0.929535E+09 | 31752890.10 | 0.195281E+11 | 0.00 | 2.63 |
October | 0.387848E+11 | 0.468204E+10 | 0.00 | 0.101507E+09 | 0.158238E+10 | 0.212538E+10 | 0.681538E+10 | 0.00 | 2.10 |
November | 0.621286E+11 | 17184456.72 | 0.00 | 0.185792E+09 | 74250225.50 | 0.701307E+10 | 0.138782E+11 | 0.00 | 2.04 |
December | 0.604271E+11 | 16477422.60 | 0.00 | 56681080.91 | 14671023.94 | 0.112956E+11 | 0.923550E+10 | 0.00 | 1.90 |
Annual Sum or Average | 0.599741E+12 | 0.258005E+11 | 0.00 | 0.164360E+10 | 0.642544E+10 | 0.562231E+11 | 0.210494E+12 | 0.00 | 2.36 |
Minimum of Months | 0.204448E+11 | 0.00 | 0.00 | 52385462.05 | 6153930.50 | 0.00 | 0.681538E+10 | 0.00 | 1.85 |
Maximum of Months | 0.731254E+11 | 0.968916E+10 | 0.00 | 0.373959E+09 | 0.222538E+10 | 0.125996E+11 | 0.332622E+11 | 0.00 | 2.95 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.417872E+10 | 0.00 | 61226.52 | 380752.93 | 9246020.35 | 0.171675E+10 | 0.154876E+09 | 39239.71 | 0.94 |
February | 0.486226E+10 | 67681.38 | 0.00 | 412644.70 | 0.00 | 0.129964E+10 | 74692278.28 | 0.00 | 1.01 |
March | 0.578420E+10 | 0.00 | 0.00 | 1593551.56 | 3002820.55 | 0.143051E+10 | 0.371335E+09 | 0.00 | 1.03 |
April | 0.406166E+10 | 0.00 | 0.00 | 4036118.08 | 5033029.85 | 0.709948E+09 | 0.202597E+10 | 0.00 | 1.16 |
May | 0.409937E+10 | 634370.82 | 0.00 | 5804183.08 | 0.00 | 0.417009E+09 | 0.284439E+10 | 0.00 | 1.26 |
June | 0.328663E+10 | 12598784.43 | 0.00 | 22930376.28 | 0.00 | 28843333.13 | 0.275888E+10 | 0.00 | 1.43 |
July | 0.173347E+10 | 0.300076E+09 | 0.00 | 6568147.23 | 40474118.87 | 436905.07 | 0.140122E+10 | 0.00 | 1.24 |
August | 0.141904E+10 | 0.319454E+09 | 0.00 | 4925158.11 | 0.103648E+09 | 594275.86 | 0.942498E+09 | 0.00 | 1.25 |
September | 0.278527E+10 | 0.116925E+09 | 0.00 | 4513094.95 | 51670144.17 | 0.121839E+09 | 0.146331E+10 | 0.00 | 1.22 |
October | 0.246801E+10 | 0.293631E+09 | 0.00 | 3608802.88 | 0.131609E+09 | 0.475191E+09 | 0.514918E+09 | 0.00 | 1.05 |
November | 0.486611E+10 | 0.00 | 0.00 | 180783.44 | 1153734.51 | 0.113175E+10 | 0.126834E+09 | 0.00 | 1.03 |
December | 0.400091E+10 | 0.00 | 0.00 | 195256.01 | 666696.34 | 0.159399E+10 | 92234461.64 | 0.00 | 0.96 |
Annual Sum or Average | 0.435456E+11 | 0.104339E+10 | 61226.52 | 55148869.24 | 0.346503E+09 | 0.892651E+10 | 0.127712E+11 | 39239.71 | 1.13 |
Minimum of Months | 0.141904E+10 | 0.00 | 0.00 | 180783.44 | 0.00 | 436905.07 | 74692278.28 | 0.00 | 0.94 |
Maximum of Months | 0.578420E+10 | 0.319454E+09 | 61226.52 | 22930376.28 | 0.131609E+09 | 0.171675E+10 | 0.284439E+10 | 39239.71 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.490050E+10 | 886774.12 | 72636.18 | 1409517.40 | 9443682.00 | 0.128250E+10 | 0.578706E+09 | 27313.22 | 1.64 |
February | 0.531720E+10 | 75676.91 | 0.00 | 3915633.88 | 0.00 | 0.116187E+10 | 0.527842E+09 | 0.00 | 1.76 |
March | 0.622362E+10 | 441614.70 | 0.00 | 10860816.41 | 2915943.99 | 0.121221E+10 | 0.122000E+10 | 0.00 | 1.85 |
April | 0.358292E+10 | 615362.01 | 0.00 | 13457148.59 | 5176975.02 | 0.518308E+09 | 0.422350E+10 | 0.00 | 2.27 |
May | 0.443215E+10 | 969492.44 | 0.00 | 9252616.06 | 0.00 | 0.304448E+09 | 0.385487E+10 | 0.00 | 2.31 |
June | 0.395382E+10 | 12734064.40 | 0.00 | 25587239.50 | 0.00 | 37541877.73 | 0.304682E+10 | 0.00 | 2.59 |
July | 0.167123E+10 | 0.347696E+09 | 0.00 | 16039032.42 | 34532953.16 | 5624119.51 | 0.217583E+10 | 0.00 | 2.40 |
August | 0.138547E+10 | 0.609075E+09 | 0.00 | 8937661.12 | 23118000.76 | 4642156.23 | 0.156175E+10 | 0.00 | 2.50 |
September | 0.276424E+10 | 0.117029E+09 | 0.00 | 8649891.45 | 62673076.42 | 0.111559E+09 | 0.230806E+10 | 0.00 | 2.25 |
October | 0.277569E+10 | 0.304487E+09 | 0.00 | 8056960.57 | 0.137482E+09 | 0.349091E+09 | 0.859822E+09 | 0.00 | 1.84 |
November | 0.561114E+10 | 0.00 | 0.00 | 2179139.52 | 1290030.91 | 0.818523E+09 | 0.417475E+09 | 0.00 | 1.80 |
December | 0.490994E+10 | 697924.80 | 0.00 | 729890.35 | 236712.01 | 0.119698E+10 | 0.243274E+09 | 0.00 | 1.67 |
Annual Sum or Average | 0.475279E+11 | 0.139471E+10 | 72636.18 | 0.109076E+09 | 0.276869E+09 | 0.700329E+10 | 0.210180E+11 | 27313.22 | 2.07 |
Minimum of Months | 0.138547E+10 | 0.00 | 0.00 | 729890.35 | 0.00 | 4642156.23 | 0.243274E+09 | 0.00 | 1.64 |
Maximum of Months | 0.622362E+10 | 0.609075E+09 | 72636.18 | 25587239.50 | 0.137482E+09 | 0.128250E+10 | 0.422350E+10 | 27313.22 | 2.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.321255E+10 | 36957418.19 | 95699.79 | 47018167.85 | 767991.52 | 0.102110E+10 | 0.909221E+10 | 26799.16 | 2.21 |
February | 0.428245E+10 | 309167.82 | 0.00 | 76029288.93 | 0.00 | 0.121447E+10 | 0.618983E+10 | 0.00 | 1.99 |
March | 0.593746E+10 | 76597.21 | 0.00 | 55299579.45 | 4038458.76 | 0.150037E+10 | 0.570652E+10 | 0.00 | 1.89 |
April | 0.456699E+10 | 399655.19 | 0.00 | 14830945.28 | 6545603.10 | 0.918617E+09 | 0.575058E+10 | 0.00 | 1.97 |
May | 0.585099E+10 | 884419.93 | 0.00 | 7075468.46 | 0.00 | 0.716281E+09 | 0.356799E+10 | 0.00 | 1.74 |
June | 0.528090E+10 | 15527285.26 | 0.00 | 13015383.35 | 0.00 | 0.117046E+09 | 0.246446E+10 | 0.00 | 1.82 |
July | 0.260499E+10 | 0.353849E+09 | 0.00 | 6087801.63 | 73974162.96 | 5266157.00 | 0.153567E+10 | 0.00 | 1.62 |
August | 0.191999E+10 | 0.517191E+09 | 0.00 | 9032358.73 | 0.140352E+09 | 4240663.81 | 0.160263E+10 | 0.00 | 1.92 |
September | 0.311910E+10 | 0.224424E+09 | 0.00 | 18345296.07 | 82140314.35 | 94399238.38 | 0.456058E+10 | 0.00 | 2.29 |
October | 0.270861E+10 | 0.718348E+09 | 0.00 | 34616695.87 | 0.142077E+09 | 0.450053E+09 | 0.291319E+10 | 0.00 | 1.98 |
November | 0.389774E+10 | 1581970.75 | 0.00 | 95193496.44 | 344802.99 | 0.781587E+09 | 0.788933E+10 | 0.00 | 2.29 |
December | 0.354853E+10 | 2704818.10 | 0.00 | 55875787.97 | 0.00 | 0.929712E+09 | 0.723376E+10 | 0.00 | 2.23 |
Annual Sum or Average | 0.469303E+11 | 0.187225E+10 | 95699.79 | 0.432420E+09 | 0.450241E+09 | 0.775315E+10 | 0.585068E+11 | 26799.16 | 1.99 |
Minimum of Months | 0.191999E+10 | 76597.21 | 0.00 | 6087801.63 | 0.00 | 4240663.81 | 0.153567E+10 | 0.00 | 1.62 |
Maximum of Months | 0.593746E+10 | 0.718348E+09 | 95699.79 | 95193496.44 | 0.142077E+09 | 0.150037E+10 | 0.909221E+10 | 26799.16 | 2.29 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.517558E+10 | 6705819.96 | 66927.62 | 5205395.25 | 6445133.45 | 0.146558E+10 | 0.144125E+10 | 10301.53 | 1.96 |
February | 0.574501E+10 | 90610.28 | 0.00 | 16593611.50 | 0.00 | 0.125028E+10 | 0.155871E+10 | 0.00 | 2.16 |
March | 0.689484E+10 | 0.00 | 0.00 | 22379136.87 | 3923643.42 | 0.132857E+10 | 0.246741E+10 | 0.00 | 2.27 |
April | 0.524251E+10 | 778839.85 | 0.00 | 13948872.00 | 5908310.41 | 0.624600E+09 | 0.442418E+10 | 0.00 | 2.74 |
May | 0.573366E+10 | 643780.07 | 0.00 | 10521753.56 | 0.00 | 0.442222E+09 | 0.433456E+10 | 0.00 | 2.77 |
June | 0.456585E+10 | 12881488.06 | 0.00 | 40148344.36 | 231978.83 | 34510705.65 | 0.397625E+10 | 0.00 | 3.12 |
July | 0.217437E+10 | 0.394110E+09 | 0.00 | 15988584.97 | 73132465.41 | 755006.59 | 0.234795E+10 | 0.00 | 2.71 |
August | 0.178028E+10 | 0.407407E+09 | 0.00 | 9225123.90 | 0.174226E+09 | 1167443.28 | 0.160428E+10 | 0.00 | 2.85 |
September | 0.360334E+10 | 0.103907E+09 | 0.00 | 9450072.67 | 0.102607E+09 | 58088026.87 | 0.277823E+10 | 0.00 | 2.75 |
October | 0.333831E+10 | 0.306416E+09 | 0.00 | 10751846.76 | 0.185137E+09 | 0.477115E+09 | 0.941526E+09 | 0.00 | 2.20 |
November | 0.561298E+10 | 0.00 | 0.00 | 17813421.59 | 1507530.25 | 0.103716E+10 | 0.171649E+10 | 0.00 | 2.21 |
December | 0.513617E+10 | 0.00 | 0.00 | 5449468.11 | 871140.54 | 0.130878E+10 | 0.115798E+10 | 0.00 | 2.02 |
Annual Sum or Average | 0.550029E+11 | 0.123294E+10 | 66927.62 | 0.177476E+09 | 0.553991E+09 | 0.802882E+10 | 0.287488E+11 | 10301.53 | 2.48 |
Minimum of Months | 0.178028E+10 | 0.00 | 0.00 | 5205395.25 | 0.00 | 755006.59 | 0.941526E+09 | 0.00 | 1.96 |
Maximum of Months | 0.689484E+10 | 0.407407E+09 | 66927.62 | 40148344.36 | 0.185137E+09 | 0.146558E+10 | 0.442418E+10 | 10301.53 | 3.12 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 2603.29 | 0.00 | 8378575.06 | 0.00 | 0.00 | 0.342403E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 47815843.20 | 0.00 | 0.00 | 0.270313E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 97654463.00 | 0.00 | 0.00 | 0.278476E+09 | 0.00 | 0.31 |
April | 0.00 | 165029.96 | 0.00 | 40794441.14 | 0.00 | 0.00 | 0.190325E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 7276857.41 | 0.00 | 0.00 | 0.264033E+09 | 0.00 | 0.29 |
June | 0.00 | 5897482.99 | 0.00 | 45853254.08 | 0.00 | 0.00 | 0.104251E+09 | 0.00 | 0.30 |
July | 0.00 | 51352735.46 | 0.00 | 19939757.84 | 0.00 | 0.00 | 22210368.36 | 0.00 | 0.28 |
August | 0.00 | 74052240.63 | 0.00 | 9772599.90 | 0.00 | 0.00 | 19530774.96 | 0.00 | 0.31 |
September | 0.00 | 11763996.84 | 0.00 | 4739715.81 | 0.00 | 0.00 | 0.108345E+09 | 0.00 | 0.29 |
October | 0.00 | 20183693.73 | 0.00 | 31592650.24 | 0.00 | 0.00 | 0.130113E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 84794404.90 | 0.00 | 0.00 | 0.218018E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 49699253.90 | 0.00 | 0.00 | 0.286615E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.163418E+09 | 0.00 | 0.448312E+09 | 0.00 | 0.00 | 0.223463E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 4739715.81 | 0.00 | 0.00 | 19530774.96 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 74052240.63 | 0.00 | 97654463.00 | 0.00 | 0.00 | 0.342403E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 9873.89 | 0.00 | 65118996.48 | 0.00 | 0.00 | 0.344648E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 0.430775E+09 | 0.00 | 0.00 | 0.275298E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.901799E+09 | 0.00 | 0.00 | 0.286099E+10 | 0.00 | 0.31 |
April | 0.00 | 1578043.97 | 0.00 | 0.383092E+09 | 0.00 | 0.00 | 0.193875E+10 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 61007475.23 | 0.00 | 0.00 | 0.266325E+10 | 0.00 | 0.29 |
June | 0.00 | 57081278.52 | 0.00 | 0.427347E+09 | 0.00 | 0.00 | 0.108087E+10 | 0.00 | 0.30 |
July | 0.00 | 0.504576E+09 | 0.00 | 0.189307E+09 | 0.00 | 0.00 | 0.236671E+09 | 0.00 | 0.28 |
August | 0.00 | 0.728507E+09 | 0.00 | 92525411.22 | 0.00 | 0.00 | 0.205198E+09 | 0.00 | 0.31 |
September | 0.00 | 0.111389E+09 | 0.00 | 40453149.21 | 0.00 | 0.00 | 0.110700E+10 | 0.00 | 0.29 |
October | 0.00 | 0.198173E+09 | 0.00 | 0.288613E+09 | 0.00 | 0.00 | 0.133134E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.783865E+09 | 0.00 | 0.00 | 0.224519E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.462092E+09 | 0.00 | 0.00 | 0.290330E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.160131E+10 | 0.00 | 0.412599E+10 | 0.00 | 0.00 | 0.227720E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 40453149.21 | 0.00 | 0.00 | 0.205198E+09 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.728507E+09 | 0.00 | 0.901799E+09 | 0.00 | 0.00 | 0.344648E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 45284013.46 | 2097.38 | 0.00 | 5209979.58 | 0.00 | 0.00 | 0.301139E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 39594634.53 | 0.00 | 0.00 | 0.279137E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 86522547.04 | 0.00 | 0.00 | 0.290078E+09 | 0.00 | 0.31 |
April | 0.00 | 153001.67 | 0.00 | 37573063.43 | 0.00 | 0.00 | 0.196806E+09 | 0.00 | 0.29 |
May | 3283765.65 | 0.00 | 0.00 | 5616251.80 | 0.00 | 0.00 | 0.263670E+09 | 0.00 | 0.29 |
June | 0.00 | 5791409.05 | 0.00 | 41962578.03 | 0.00 | 0.00 | 0.108952E+09 | 0.00 | 0.30 |
July | 0.00 | 50518667.72 | 0.00 | 18698554.27 | 0.00 | 0.00 | 23988959.31 | 0.00 | 0.28 |
August | 0.00 | 72298304.21 | 0.00 | 9186497.90 | 0.00 | 0.00 | 21199029.68 | 0.00 | 0.31 |
September | 0.00 | 11160125.17 | 0.00 | 3710613.25 | 0.00 | 0.00 | 0.111165E+09 | 0.00 | 0.29 |
October | 0.00 | 19819959.30 | 0.00 | 27046857.77 | 0.00 | 0.00 | 0.135097E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 74664995.55 | 0.00 | 0.00 | 0.228540E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 44281506.19 | 0.00 | 0.00 | 0.293926E+09 | 0.00 | 0.28 |
Annual Sum or Average | 48567779.11 | 0.159744E+09 | 0.00 | 0.394068E+09 | 0.00 | 0.00 | 0.225370E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3710613.25 | 0.00 | 0.00 | 21199029.68 | 0.00 | 0.28 |
Maximum of Months | 45284013.46 | 72298304.21 | 0.00 | 86522547.04 | 0.00 | 0.00 | 0.301139E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.881068E+09 | 0.00 | 0.00 | 0.311302E+12 | 0.00 | 12.60 |
February | 0.109942E+10 | 0.00 | 0.00 | 0.308001E+10 | 0.00 | 0.00 | 0.407644E+12 | 0.00 | 21.19 |
March | 76076525.92 | 0.00 | 0.00 | 0.676301E+10 | 0.00 | 0.00 | 0.630098E+12 | 0.00 | 29.99 |
April | 0.00 | 139661.10 | 0.00 | 0.438822E+10 | 0.00 | 0.00 | 0.788848E+12 | 0.00 | 49.72 |
May | 0.00 | 0.00 | 0.00 | 0.816304E+09 | 0.00 | 0.00 | 0.270833E+12 | 0.00 | 15.49 |
June | 0.593282E+09 | 46853492.34 | 0.00 | 0.329608E+10 | 1323946.32 | 0.00 | 0.301498E+12 | 0.00 | 27.12 |
July | 0.00 | 0.321177E+10 | 0.00 | 0.583058E+10 | 0.00 | 0.00 | 0.476456E+12 | 0.00 | 43.38 |
August | 0.00 | 0.192120E+10 | 0.00 | 0.276487E+10 | 0.00 | 0.00 | 0.623831E+12 | 0.00 | 54.57 |
September | 0.00 | 90315481.73 | 0.00 | 0.697636E+09 | 0.00 | 0.00 | 0.244211E+12 | 0.00 | 18.30 |
October | 0.547628E+09 | 0.209870E+10 | 0.00 | 0.289500E+10 | 14020186.01 | 0.00 | 0.322014E+12 | 0.00 | 25.44 |
November | 0.166320E+09 | 0.00 | 0.00 | 0.660506E+10 | 0.00 | 0.00 | 0.631283E+12 | 0.00 | 33.14 |
December | 0.00 | 0.00 | 0.00 | 0.494553E+10 | 0.00 | 0.00 | 0.915541E+12 | 0.00 | 44.43 |
Annual Sum or Average | 0.248272E+10 | 0.736897E+10 | 0.00 | 0.429634E+11 | 15344132.33 | 0.00 | 0.592356E+13 | 0.00 | 31.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.697636E+09 | 0.00 | 0.00 | 0.244211E+12 | 0.00 | 12.60 |
Maximum of Months | 0.109942E+10 | 0.321177E+10 | 0.00 | 0.676301E+10 | 14020186.01 | 0.00 | 0.915541E+12 | 0.00 | 54.57 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:26:21
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.492463E+12 | 0.804398E+10 | 0.00 | 0.278680E+13 | 0.580203E+12 |
February | 0.577196E+12 | 0.947979E+10 | 0.00 | 0.283328E+13 | 0.615839E+12 |
March | 0.783905E+12 | 0.987508E+10 | 0.00 | 0.323295E+13 | 0.905074E+12 |
April | 0.101292E+13 | 0.589434E+10 | 0.00 | 0.323363E+13 | 0.124531E+13 |
May | 0.105563E+13 | 0.704692E+10 | 0.00 | 0.277936E+13 | 0.690769E+12 |
June | 0.103783E+13 | 0.360519E+10 | 0.00 | 0.242365E+13 | 0.145045E+13 |
July | 0.111774E+13 | 0.135132E+10 | 0.00 | 0.183343E+13 | 0.230078E+13 |
August | 0.103735E+13 | 0.127687E+10 | 0.00 | 0.166425E+13 | 0.279443E+13 |
September | 0.815374E+12 | 0.279450E+10 | 0.00 | 0.207224E+13 | 0.128496E+13 |
October | 0.588788E+12 | 0.471748E+10 | 0.00 | 0.215016E+13 | 0.189265E+13 |
November | 0.526307E+12 | 0.783481E+10 | 0.00 | 0.325822E+13 | 0.105507E+13 |
December | 0.453132E+12 | 0.894019E+10 | 0.00 | 0.356130E+13 | 0.126232E+13 |
Annual Sum or Average | 0.949863E+13 | 0.708605E+11 | 0.00 | 0.318293E+14 | 0.160779E+14 |
Minimum of Months | 0.453132E+12 | 0.127687E+10 | 0.00 | 0.166425E+13 | 0.580203E+12 |
Maximum of Months | 0.111774E+13 | 0.987508E+10 | 0.00 | 0.356130E+13 | 0.279443E+13 |