Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2024-07-03 12:26:25
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 38690.25 | 835.28 | 835.28 |
Net Site Energy | 38690.25 | 835.28 | 835.28 |
Total Source Energy | 107589.58 | 2322.73 | 2322.73 |
Net Source Energy | 107589.58 | 2322.73 | 2322.73 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 7173.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1965.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1006.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2912.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1008.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 176.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6305.85 |
Humidification | 1053.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.74 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 484.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 31516.73 | 7173.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8977.76 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 7173.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1965.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 1006.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 56.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2912.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 1008.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 176.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6305.85 |
Humidification | General | 1053.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.74 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 484.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 7173.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1965.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 1006.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2912.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 1008.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 176.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6305.85 |
Humidification | Unassigned | 1053.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.74 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 484.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 164.09 | 154.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 680.41 | 154.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 164.09 | 154.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 680.41 | 154.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 31516.729 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 31516.729 | 100.00 |
Total On-Site and Utility Electric Sources | 31516.729 | 100.00 |
Total Electricity End Uses | 31516.729 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 8977.76 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 8977.76 | 100.00 |
Total Water End Uses | 8977.76 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 118.33 |
Time Setpoint Not Met During Occupied Cooling | 173.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5281.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS SZVAV FAN | AIRLOOP DATACENTER BASEMENT SYS11 FAN | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 11.6510 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 11.6510 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 11.6510 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.6510 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 11.6510 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.6510 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 11.6510 | 18.58 | 484.4232 | |
Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.6100 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-15:30 | 30-JAN-07:30 | - | - | - | - | - | - | - | - | - | - | 07-SEP-14:20 |
Heating | 0.00 | 3142160.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 515044.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235096.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 305773.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 102278.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 58522.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35451.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2520439.57 | 3142160.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3142160.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 515044.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 305773.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 102278.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 58522.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 35451.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 7776.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6224.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17769.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3185.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8307.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3193.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 559.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 3335.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1535.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 99813.48 | 7776.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 167.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 134.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 199.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 68.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 12.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 72.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 33.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2154.85 | 167.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 167.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 134.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 199.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 68.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 12.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 72.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 33.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2154.85 | 167.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 7.24 | 0.292441 | 0.300000 | 2.17 |
DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | 32.85 | 0.018177 | 0.500000 | 16.43 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 7.72 | 0.246427 | 0.300000 | 2.32 | 0.657138 | 0.500000 | 0.001546 | 0.000314 | 2.32 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 73.32 | 0.259431 | 0.300000 | 21.99 | 0.691816 | 0.500000 | 0.001469 | 0.006670 | 33.45 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 9.32 | 0.204083 | 0.300000 | 2.80 | 0.544221 | 0.500000 | 0.001867 | 0.001847 | 9.32 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.82 | 0.131035 | 0.300000 | 0.546772 | 0.349426 | 0.500000 | 0.002908 | 0.000361 | 1.82 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.74 | 0.088265 | 0.300000 | 0.523101 | 0.300000 | 0.500000 | 0.004317 | 0.000238 | 1.20 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 2.03 | 0.117465 | 0.300000 | 0.609951 | 0.313240 | 0.500000 | 0.003244 | 0.000376 | 1.90 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 2.13 | 0.072411 | 0.300000 | 0.637629 | 0.300000 | 0.500000 | 0.005262 | 0.000209 | 1.06 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 25.42 | 0.093963 | 0.300000 | 7.62 | 0.300000 | 0.500000 | 0.004055 | 0.005026 | 25.42 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 18.41 | 0.300000 | 0.500000 | 0.004556 | 0.003262 | 16.50 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 24.84 | 0.096156 | 0.300000 | 7.45 | 0.300000 | 0.500000 | 0.003962 | 0.004912 | 24.84 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 19.83 | 0.077607 | 0.300000 | 5.95 | 0.300000 | 0.500000 | 0.004909 | 0.003268 | 16.53 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 3.29 | 0.072585 | 0.300000 | 0.987072 | 0.300000 | 0.500000 | 0.005249 | 0.000650 | 3.29 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 2.13 | 0.072188 | 0.300000 | 0.639603 | 0.300000 | 0.500000 | 0.005278 | 0.000421 | 2.13 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 3.23 | 0.073932 | 0.300000 | 0.969098 | 0.300000 | 0.500000 | 0.005153 | 0.000639 | 3.23 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 2.16 | 0.071255 | 0.300000 | 0.647980 | 0.300000 | 0.500000 | 0.005347 | 0.000427 | 2.16 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 35943.51 | 0.000314 | 772.99 | |
CORE_MID VAV BOX REHEAT COIL | 762425.37 | 0.006670 | 17844.44 | |
CORE_TOP VAV BOX REHEAT COIL | 211115.18 | 0.001847 | 4932.69 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 41224.38 | 0.000361 | 962.81 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 27239.17 | 0.000238 | 636.17 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 42991.00 | 0.000376 | 1004.06 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 23917.28 | 0.000209 | 558.63 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 574504.89 | 0.005026 | 13415.34 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 372878.55 | 0.003262 | 8707.10 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 561430.16 | 0.004912 | 13110.13 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 373526.03 | 0.003268 | 8722.19 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 74351.27 | 0.000650 | 1736.05 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 48177.52 | 0.000421 | 1124.91 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 72998.39 | 0.000639 | 1704.47 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 48807.77 | 0.000427 | 1139.62 | |
VAV_BOT WITH REHEAT HEATING COIL | 80348.33 | 0.000703 | 1306.68 | |
VAV_MID WITH REHEAT HEATING COIL | 817832.28 | 0.007155 | 13190.66 | |
VAV_TOP WITH REHEAT HEATING COIL | 69215.72 | 0.000606 | 1184.36 | |
CAV_BAS HEATING COIL | 116808.39 | 0.000875 | 2622.25 | 100000.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 562104.91 | 0.000875 | 2622.25 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.790752 |
DATACENTER_MID_ZN_6 DIRECT AIR | 7.61 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.783349 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 7.72 | 4.63 | 15.44 | 7.06 | 12.60 | 12.60 | 0.300000 | 0.560338 | 12.60 |
VAV_MID WITH REHEAT | 80.90 | 48.54 | 161.81 | 116.73 | 118.36 | 118.36 | 0.300000 | 0.986216 | 118.36 |
VAV_TOP WITH REHEAT | 10.07 | 6.04 | 20.13 | 20.13 | 14.60 | 20.13 | 0.300000 | 1.00 | 20.13 |
CAV_BAS | 2.17 | 2.17 | 7.24 | 2.17 | 7.24 | 7.24 | 1.00 | 0.300000 | 7.24 |
AIRLOOP DATACENTER BASEMENT | 16.43 | 16.43 | 32.85 | 16.43 | 32.85 | 32.85 | 1.00 | 0.499997 | 32.85 |
AIRLOOP DATACENTER BOT | 0.790752 | 0.790752 | 0.790752 | 0.790752 | 0.790752 | 0.790752 | 1.00 | 1.00 | 0.790752 |
AIRLOOP DATACENTER MID | 7.61 | 7.61 | 7.61 | 7.61 | 7.61 | 7.61 | 1.00 | 1.00 | 7.61 |
AIRLOOP DATACENTER TOP | 0.783349 | 0.783349 | 0.783349 | 0.783349 | 0.783349 | 0.783349 | 1.00 | 1.00 | 0.783349 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 12.60 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 118.36 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 20.13 | |
CAV_BAS_OA_CONTROLLER | 7.24 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 32.85 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.790752 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 7.61 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.783349 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.16 | 6.67 | 11.03 | 0.009921 | 0.008500 | 261222.41 | 0.009330 | 12.60 |
VAV_MID WITH REHEAT COOLING COIL | 25.26 | 6.67 | 11.03 | 0.010115 | 0.008500 | 2533061.11 | 0.090475 | 118.36 |
VAV_TOP WITH REHEAT COOLING COIL | 25.00 | 6.67 | 11.05 | 0.009833 | 0.008500 | 407681.49 | 0.014561 | 20.13 |
CAV_BAS COOLING COIL | 23.94 | 6.67 | 11.02 | 0.009983 | 0.008500 | 137571.78 | 0.004914 | 7.24 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 27.04 | 6.67 | 15.00 | 0.008603 | 0.008500 | 457412.79 | 0.016338 | 32.85 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 12.60 |
VAV_MID WITH REHEAT FAN | 118.36 |
VAV_TOP WITH REHEAT FAN | 20.13 |
CAV_BAS SZVAV FAN | 7.24 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | 32.85 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.009330 | 0.000051 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000703 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.090475 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.007155 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.014561 | 0.000033 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000606 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | Design Size Minimum Supply Air Temperature [C] | User-Specified Minimum Supply Air Temperature [C] | User-Specified Maximum Supply Air Temperature [C] | User-Specified Nominal Cooling Capacity [W] | Design Size Maximum Supply Air Temperature [C] | |
CAV_BAS_UNITARY_PACKAGE_DX | 7.24 | 7.24 | 7.24 | 2.17 | 137571.78 | 100000.00 | 1.00 | 5.33 | 12.89 | 32.11 | ||
AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | 32.85 | 32.85 | 32.85 | 16.43 | 457412.79 | 100000.00 | 1.00 | 15.89 | 29.11 | |||
AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | 0.790752 | 0.790752 | 0.790752 | 0.790752 | 27039.51 | 1.00 | 13089.75 | 29.11 | ||||
AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | 7.61 | 7.61 | 7.61 | 7.61 | 260351.50 | 1.00 | 125948.91 | 29.11 | ||||
AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | 0.783349 | 0.783349 | 0.783349 | 0.783349 | 26790.80 | 1.00 | 12967.21 | 29.11 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000296 | 0.000037 | 96450.70 | 100000.00 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | 0.790752 | 1359.81 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | 7.61 | 13084.00 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | 0.783349 | 1347.08 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
AIRLOOP DATACENTER BOT COOLING COIL | 0.790750 | 0.395376 | 0.527167 | 13089.75 | 6544.88 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER MID COOLING COIL | 7.61 | 3.80 | 5.07 | 125948.91 | 62974.46 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.783350 | 0.391674 | 0.522233 | 12967.21 | 6483.60 | 0.800660 | 0.800660 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BOT HEATING COIL | 27039.51 |
AIRLOOP DATACENTER MID HEATING COIL | 260351.50 |
AIRLOOP DATACENTER TOP HEATING COIL | 26790.80 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.135618 | 27945.92 | |
HEATSYS1 PUMP | 0.038834 | 11695.00 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.135618 | 16.27 |
HEATSYS1 | 0.038834 | 4.66 |
COOLSYS1_SUPPLY | 0.135618 | 16.27 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.135618 | 0.135618 | 569257.81 | 6.67 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 4438926.80 | 4438926.80 | 0.038834 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.067809 | 12898.32 |
COOLSYS1 CHILLER2 PUMP | 0.067809 | 12898.32 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.135618 | 0.068385 | 1914597.90 | 1914622.11 | 0.095954 |
COOLSYS1 CHILLER2 | 0.135618 | 0.068385 | 1914597.90 | 1914622.11 | 0.095954 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.191908 | 23.03 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.191908 | 66918.62 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 80.74 | 2292209.93 | 16.15 | 286526.24 |
TOWERWATERSYS COOLTOWER 2 | 80.74 | 2292209.93 | 16.15 | 286526.24 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 11.651 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 16.493 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 11.651 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 496.074 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 32383.100 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 32383.100 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 9130.649 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 9130.649 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
26 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
27 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
35 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
47 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
48 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
49 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
50 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
51 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
52 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
53 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
54 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
55 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
56 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
57 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
58 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
59 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
60 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
61 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
62 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
63 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
64 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
65 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
66 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
67 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
68 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
69 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
70 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
71 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
72 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
73 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
74 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
75 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
76 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
77 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
78 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
79 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
80 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
81 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
82 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
83 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
84 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
85 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
86 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
87 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
88 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
89 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
90 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
91 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
92 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
93 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
94 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
95 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
96 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
97 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
98 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
99 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
100 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
101 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
102 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
103 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
104 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
105 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
106 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
107 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
108 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
109 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
110 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
111 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
112 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
113 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
114 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
115 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
116 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
117 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
118 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
119 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
120 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
121 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone BASEMENT | 1.2500 |
3 | Zone CORE_BOTTOM | 1.2500 |
4 | Zone CORE_MID | 1.2500 |
5 | Zone CORE_TOP | 1.2500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.2500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.2500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.2500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone BASEMENT | 1.1500 |
3 | Zone CORE_BOTTOM | 1.1500 |
4 | Zone CORE_MID | 1.1500 |
5 | Zone CORE_TOP | 1.1500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.1500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.1500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.1500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 82743.46439 | 95154.98405 | 6.29759 | 7.24223 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 88186.72540 | 101414.73421 | 6.71173 | 7.71849 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 11157.21920 | 13946.52401 | 0.83332 | 1.07782 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 837830.45162 | 963505.01936 | 63.75306 | 73.31602 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 355704.54839 | 444630.68548 | 26.76254 | 33.45318 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 91963.97358 | 105758.56961 | 7.06130 | 8.12050 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53651E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 98062.78115 | 122578.47644 | 7.45597 | 9.31996 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 14811.80246 | 17033.57283 | 1.13738 | 1.30799 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 31.20000 | 1.53651E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 19135.52228 | 23919.40285 | 1.45806 | 1.82257 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 19745.79952 | 22707.66945 | 1.51624 | 1.74367 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 25.03433 | 1.53537E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 12643.48519 | 15804.35649 | 0.96347 | 1.20433 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 23024.05507 | 26477.66333 | 1.76797 | 2.03317 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53644E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 19954.44421 | 24943.05526 | 1.52063 | 1.90079 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 24069.07256 | 27679.43344 | 1.84820 | 2.12543 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 11104.04964 | 13880.06205 | 0.84576 | 1.05719 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 141648.12652 | 162895.34549 | 10.87809 | 12.50981 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53651E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 266623.93016 | 333279.91271 | 20.33313 | 25.41641 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 208413.06402 | 239675.02362 | 16.00520 | 18.40598 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 25.67033 | 1.53549E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 173051.50622 | 216314.38277 | 13.19729 | 16.49662 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 229285.37490 | 263678.18114 | 17.60816 | 20.24938 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53646E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 260563.93719 | 325704.92148 | 19.86984 | 24.83729 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 224552.04804 | 258234.85524 | 17.24454 | 19.83122 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53617E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 173350.83032 | 216688.53790 | 13.22033 | 16.52541 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 17274.28287 | 19865.42531 | 1.32665 | 1.52565 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 31.20000 | 1.53651E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 34499.91421 | 43124.89277 | 2.63219 | 3.29024 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 21112.86600 | 24279.79590 | 1.62144 | 1.86466 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 26.27100 | 1.53560E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 22355.19203 | 27943.99004 | 1.70561 | 2.13201 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 25859.99384 | 29738.99292 | 1.98601 | 2.28391 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53648E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 33872.78222 | 42340.97777 | 2.58426 | 3.23033 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 24356.22070 | 28009.65380 | 1.87051 | 2.15109 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 22647.24943 | 28309.06179 | 1.72795 | 2.15993 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8955.26543 | 10298.55525 | 0.68761 | 0.79075 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.87167 | 1.53571E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -26.20000 | 3.61342E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 86166.78277 | 99091.80019 | 6.61615 | 7.60857 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.87167 | 1.53571E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -26.20000 | 3.61342E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8871.42180 | 10202.13508 | 0.68117 | 0.78335 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.06600 | 1.53574E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -26.20000 | 3.61342E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372062.20038 | 427871.53043 | 28.56746 | 32.85258 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 21.55400 | 1.53473E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20000 | 3.61342E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 178170.59 | 12.60438 | 12.60438 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 91570.85 | 7.06272 | 7.06272 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1660228.11 | 118.36041 | 118.36041 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 891479.61 | 116.72891 | 116.72891 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 203773.68 | 14.59770 | 14.59770 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 84417.07 | 20.13247 | 20.13247 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 |
7 | CAV_BAS | Cooling | Sensible | 92408.00 | 7.24223 | 7.24223 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 80767.74 | 1.20016 | 1.20016 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 422416.69 | 32.85278 | 32.85278 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 21601.39 | 0.33839 | 0.33839 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 10137.01 | 0.79075 | 0.79075 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 997.89 | 1.56323E-002 | 1.56323E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 97536.58 | 7.60857 | 7.60857 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 9978.95 | 0.15632 | 0.15632 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 10045.59 | 0.78335 | 0.78335 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 997.89 | 1.56323E-002 | 1.56323E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 7.24223 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.29244 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 2.17267 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.71849 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24643 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.31555 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65714 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.54610E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.14450E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.31555 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 35943.51052 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.14450E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 772.98791 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 73.31602 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25943 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 21.99481 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69182 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.46860E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.67003E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 33.45318 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 762425.37185 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.67003E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 17844.43890 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.31996 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20408 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.79599 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54422 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.86689E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.84693E-003 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.31996 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 211115.18056 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.84693E-003 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4932.69485 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.82257 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13103 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.54677 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34943 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.90763E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.60649E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.82257 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 41224.37628 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.60649E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 962.81352 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.74367 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.82650E-002 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.52310 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.31655E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.38300E-004 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20433 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27239.16875 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.38300E-004 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 636.17426 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.03317 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11746 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.60995 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31324 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.24352E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.76104E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.90079 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 42990.99880 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.76104E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1004.05702 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.12543 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.24112E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63763 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.26162E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.09239E-004 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.05719 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23917.27751 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.09239E-004 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 558.62998 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 25.41641 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.39631E-002 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 7.62492 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.05478E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.02602E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 25.41641 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 574504.89433 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.02602E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 13415.33736 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.40598 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.55650E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.26210E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.49662 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 372878.55302 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.26210E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8707.09620 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 24.83729 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.61561E-002 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 7.45119 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.96231E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.91164E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 24.83729 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 561430.15870 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.91164E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 13110.12770 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 19.83122 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.76075E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.94937 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.90932E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.26777E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.52541 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 373526.03494 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.26777E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8722.19427 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.29024 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.25845E-002 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.98707 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.24905E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.50457E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.29024 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 74351.27467 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.50457E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1736.05461 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.13201 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.21878E-002 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63960 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.27790E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.21478E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.13201 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 48177.52180 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.21478E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1124.91041 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.23033 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.39324E-002 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.96910 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.15336E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.38622E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.23033 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 72998.38842 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.38622E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1704.47231 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.15993 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.12545E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.64798 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.34703E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.26992E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.15993 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 48807.76870 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.26992E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1139.62129 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.79075 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.60857 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.78335 |
215 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 32.85258 |
216 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 1.81771E-002 |
217 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
218 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 16.42629 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.72167 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.63300 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 15.44334 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 7.06272 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 12.60438 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 12.60438 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.56034 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 80.90346 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 48.54208 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 161.80693 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 116.72891 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 118.36041 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 118.36041 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.98622 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 10.06624 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.03974 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 20.13247 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 20.13247 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 14.59770 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 20.13247 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 1.00000 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.17267 |
244 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.17267 |
245 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.24223 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.17267 |
247 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.24223 |
248 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 7.24223 |
249 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.30000 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 16.42629 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 16.42629 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 32.85258 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 16.42629 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 32.85278 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 32.85278 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.50000 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.79075 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.79075 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.79075 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.79075 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.79075 |
264 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.79075 |
265 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.60857 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.60857 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.60857 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 7.60857 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.60857 |
272 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 7.60857 |
273 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
274 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.78335 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.78335 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.78335 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.78335 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.78335 |
280 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.78335 |
281 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
282 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
283 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 12.60438 |
284 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 118.36041 |
285 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 20.13247 |
286 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 7.24223 |
287 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 32.85278 |
288 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.79075 |
289 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 7.60857 |
290 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.78335 |
291 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 12.60438 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.16083 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.02886 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.92108E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 261222.41150 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.33026E-003 |
299 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 12.60438 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 80348.32589 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.02922E-004 |
302 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1306.68012 |
303 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 12.60438 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.33026E-003 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.10372E-005 |
306 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.02922E-004 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 118.36041 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.25505 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.02951 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.01147E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2533061.11232 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.04751E-002 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 118.36041 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 817832.27959 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.15475E-003 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 13190.66037 |
319 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 118.36041 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.04751E-002 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.26322E-006 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.15475E-003 |
323 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 20.13247 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.00096 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.05391 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.83306E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 407681.49438 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.45614E-002 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 20.13247 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 69215.71663 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.05529E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1184.35574 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 20.13247 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.45614E-002 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.27022E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.05529E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.24223 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.24223 |
342 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.24223 |
343 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.24223 |
344 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.17267 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 23.94445 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.01913 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.98344E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 137571.77760 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.91375E-003 |
352 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.24223 |
353 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 137571.77760 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 116808.39385 |
355 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
356 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
357 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.25111 |
358 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
359 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
360 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Minimum Supply Air Temperature [C] | 5.33258 |
361 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 12.88890 |
362 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 32.11110 |
363 | Fan:VariableVolume | CAV_BAS SZVAV FAN | Design Size Maximum Flow Rate [m3/s] | 7.24223 |
364 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 32.85278 |
365 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
366 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 32.85278 |
367 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 32.85278 |
368 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 32.85278 |
369 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 16.42639 |
370 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.04124 |
371 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
372 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 15.00346 |
373 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60349E-003 |
374 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
375 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Coil Load [W] | 457412.79274 |
376 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.63377E-002 |
377 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 32.85278 |
378 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 457412.79274 |
379 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Capacity [W] | 562104.90989 |
380 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
381 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
382 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.25111 |
383 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
384 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
385 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 15.88890 |
386 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 29.11110 |
387 | Fan:VariableVolume | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Design Size Maximum Flow Rate [m3/s] | 32.85278 |
388 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.95807E-004 |
389 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
390 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
391 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.79075 |
393 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
394 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.79075 |
395 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1359.80750 |
396 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.79075 |
397 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.79075 |
398 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.79075 |
399 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.79075 |
400 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.79075 |
401 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.39538 |
402 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.52717 |
403 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 13089.75000 |
404 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6544.87500 |
405 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
406 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
407 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 13089.75000 |
408 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27039.50747 |
409 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
410 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
411 | Coil:Heating:Fuel | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Nominal Capacity [W] | 27039.50747 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.60857 |
413 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
414 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.60857 |
415 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 13083.99998 |
416 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.60857 |
417 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.60857 |
418 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.60857 |
419 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 7.60857 |
420 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.60857 |
421 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.80429 |
422 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.07238 |
423 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 125948.91000 |
424 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 62974.45500 |
425 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
426 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
427 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 125948.91000 |
428 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 260351.49502 |
429 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
430 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
431 | Coil:Heating:Fuel | AIRLOOP DATACENTER MID HEATING COIL | Design Size Nominal Capacity [W] | 260351.49502 |
432 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.78335 |
433 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
434 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.78335 |
435 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1347.07742 |
436 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.78335 |
437 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.78335 |
438 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.78335 |
439 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.78335 |
440 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.78335 |
441 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.39167 |
442 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.52223 |
443 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 12967.21000 |
444 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6483.60500 |
445 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
446 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
447 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 12967.21000 |
448 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26790.79739 |
449 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
450 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
451 | Coil:Heating:Fuel | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Nominal Capacity [W] | 26790.79739 |
452 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.13562 |
453 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 27945.91594 |
454 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.13562 |
455 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 16.27419 |
456 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.13562 |
457 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.13562 |
458 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 569257.80938 |
459 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 6.67000 |
460 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.88337E-002 |
461 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 4.66004 |
462 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.88337E-002 |
463 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 11694.99545 |
464 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
465 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 4438926.80098 |
466 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 4438926.80000 |
467 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.88337E-002 |
468 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.13562 |
469 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 16.27419 |
470 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 6.78091E-002 |
471 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 12898.32174 |
472 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 6.78091E-002 |
473 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 12898.32174 |
474 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.13562 |
475 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.83850E-002 |
476 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1914597.89624 |
477 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1914622.11500 |
478 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 9.59541E-002 |
479 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.13562 |
480 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.83850E-002 |
481 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1914597.89624 |
482 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1914622.11500 |
483 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 9.59541E-002 |
484 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
485 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
486 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
487 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
488 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
489 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.19191 |
490 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 23.02898 |
491 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.19191 |
492 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 66918.62306 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 80.74065 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 2292209.92710 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 16.14813 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 286526.24089 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 80.74065 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 2292209.92710 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 16.14813 |
500 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 286526.24089 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 34114.94 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 723334.11 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 200292.27 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 39111.06 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 25842.79 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 40787.12 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 22691.18 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 545054.03 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 353763.68 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 532649.53 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 354377.97 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 70539.83 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 45707.81 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 69256.29 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 46305.75 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 60258.63 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 602756.27 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 57474.08 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94839.65 |
20 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | 94839.65 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 314812.92 | 214234.54 | 100578.38 | 0.68 | 39575.03 | 401.39 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2998609.73 | 2029802.55 | 968807.18 | 0.68 | 375521.47 | 3808.75 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 497455.53 | 339890.64 | 157564.88 | 0.68 | 62681.76 | 635.75 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 177077.39 | 121739.76 | 55337.63 | 0.69 | 23475.87 | 238.11 |
5 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | 588527.44 | 441537.86 | 146989.58 | 0.75 | 58894.90 | 597.34 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | 12470.0 | 9.16 | 9.16 | |||
2 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | 119986.0 | 10.40 | 10.40 | |||
3 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | 12353.3 | 9.16 | 9.16 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 6.37 | 21.74 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 6.37 | 21.74 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.0624874014E-003 | 1.5566294810E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.5310375774E-003 | 6.2391289845E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.1283950404E-002 | 2.5762289177E-002 | Pass | Pass | 0.4888341982 | 0.4916354852 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 7.1436026040E-002 | 8.5724459318E-002 | Pass | Pass | 2.9350625499 | 18.9587987305 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.2854155281E-002 | 1.8992038013E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.7074374368E-002 | 3.9078251055E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 3.8144908437E-002 | 6.3231414960E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 2.3753028381E-002 | 1.9942148041E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4300065884 | 0.4482956145 | Pass | Pass | 0.7773750587 | 0.7645519621 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4360698968 | 0.4606252543 | Pass | Pass | 0.7557524609 | 0.6832660721 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3759596978 | 0.4219069832 | Pass | Pass | 0.7843514012 | 0.7251525756 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2985389362 | 0.3239898391 | Pass | Pass | 0.7873250274 | 0.7515070535 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6178655210 | 0.6365186999 | Pass | Pass | 0.7895179309 | 1.2048084396 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6219260044 | 0.6481067301 | Pass | Pass | 0.7172295278 | 0.7302084203 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5620588899 | 0.6055378526 | Pass | Pass | 0.7083499027 | 0.6697400285 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4883433067 | 0.5149225098 | Pass | Pass | 0.7393888010 | 0.8054660891 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.2912116418E-003 | 5.3795975743E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.9937787015E-002 | 2.7819822792E-002 | Pass | Pass | 0.4869152097 | 0.4671638918 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.2495841730 | 0.1796756271 | Pass | Pass | 0.4927374382 | 0.4846512897 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.2735763369E-002 | 6.5732499087E-002 | Pass | Pass | 21.4365744191 | 211.6536879243 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.4344046207E-003 | 4.7770741507E-003 | Pass | Pass | 1.2932498548E-003 | 1.1945108784E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 9.9296382607E-003 | 8.8644142614E-003 | Pass | Pass | 2.5571210890E-003 | 2.0370184040E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.1364768138E-002 | 2.1809378117E-002 | Pass | Pass | 1.6572625453E-003 | 1.2827898246E-003 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6902.28 | 373.33 | 0.00 | 27950.73 | 15804.19 | 51030.53 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
North Total or Average | 1390.74 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 3.241 | 0.391 | 0.431 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 11.6510 | 2779.43 | 32383.10 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 333.79 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.6510 | 24961.20 | 290822.99 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 2997.66 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.6510 | 3134.13 | 36515.73 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.6510 | 3134.20 | 36516.53 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 11.6510 | 783.68 | 9130.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 94.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 22.3674 | 362.03 | 8097.60 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 83.47 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
Interior Lighting Total | 11.7515 | 46320.38 | 544334.28 | 1723.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 64082.80 | AstronomicalClock | - | 83.63 | 83.63 | 1006.00 | |
Exterior Lighting Total | 64082.80 | 1006.00 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3787056.37 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 4438926.80 | 0.79 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1914622.11 | 6.11 | 1905279.80 | 6.08 | 6.37 | 21.74 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1914622.11 | 6.11 | 1905279.80 | 6.08 | 6.37 | 21.74 |
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 2292209.93 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 2292209.93 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 261222.41 | 314812.92 | 214234.54 | 100578.38 | 0.68 | - | 39575.03 | 401.39 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2533061.11 | 2998609.73 | 2029802.55 | 968807.18 | 0.68 | - | 375521.47 | 3808.75 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 407681.49 | 497455.53 | 339890.64 | 157564.88 | 0.68 | - | 62681.76 | 635.75 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 137571.78 | 177077.39 | 121739.76 | 55337.63 | 0.69 | - | 23475.87 | 238.11 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | 457412.79 | 588527.44 | 441537.86 | 146989.58 | 0.75 | - | 58894.90 | 597.34 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | 13089.75 | 10480.44 | 2609.31 | 0.80 | 3.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | 125948.91 | 100842.25 | 25106.66 | 0.80 | 3.50 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 12967.21 | 10382.33 | 2584.88 | 0.80 | 3.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
AIRLOOP DATACENTER BOT COOLING COIL | 12470.0 | 9.16 | 9.16 | ||||
AIRLOOP DATACENTER MID COOLING COIL | 119986.0 | 10.40 | 10.40 | ||||
AIRLOOP DATACENTER TOP COOLING COIL | 12353.3 | 9.16 | 9.16 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 35943.51 | 34114.94 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 762425.37 | 723334.11 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 211115.18 | 200292.27 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 41224.38 | 39111.06 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 27239.17 | 25842.79 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 42991.00 | 40787.12 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 23917.28 | 22691.18 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 574504.89 | 545054.03 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 372878.55 | 353763.68 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 561430.16 | 532649.53 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 373526.03 | 354377.97 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 74351.27 | 70539.83 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 48177.52 | 45707.81 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 72998.39 | 69256.29 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 48807.77 | 46305.75 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 80348.33 | 60258.63 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 817832.28 | 602756.27 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 69215.72 | 57474.08 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94839.65 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | 100000.00 | 94839.65 | - |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | 27039.51 | 0.80 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | 260351.50 | 0.79 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | 26790.80 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 12.60 | 27554.47 | 2186.10 | 1.00 | 1.11 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 118.36 | 258748.06 | 2186.10 | 1.00 | 1.08 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1337.13 | 20.13 | 43411.92 | 2156.31 | 1.00 | 1.12 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
CAV_BAS SZVAV FAN | Fan:VariableVolume | 0.61 | 1337.13 | 7.24 | 15916.84 | 2197.78 | 1.00 | 1.13 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 0.61 | 637.69 | 32.85 | 34106.41 | 1038.16 | 1.00 | 1.19 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.79 | 1359.81 | 1719.64 | 1.00 | 1.35 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 7.61 | 13084.00 | 1719.64 | 1.00 | 1.08 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.78 | 1347.08 | 1719.64 | 1.00 | 1.35 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.83 | 0.135618 | 27945.92 | 206063.11 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.038834 | 11695.00 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.067809 | 12898.32 | 190215.15 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.067809 | 12898.32 | 190215.15 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 209234.68 | 0.191908 | 66918.62 | 348701.22 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 82743.46 | 95154.98 | 34.24 | 6.298 | 7.242 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 23.36 | 0.01535 | 1.200 | 0.00 |
CORE_BOTTOM | 88186.73 | 101414.73 | 40.63 | 6.712 | 7.718 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00885 | 23.36 | 0.01535 | 1.078 | 0.00 |
CORE_MID | 837830.45 | 963505.02 | 386.00 | 63.753 | 73.316 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00887 | 23.36 | 0.01535 | 10.778 | 0.00 |
CORE_TOP | 91963.97 | 105758.57 | 42.37 | 7.061 | 8.120 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00883 | 31.20 | 0.01537 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 14811.80 | 17033.57 | 54.35 | 1.137 | 1.308 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00897 | 31.20 | 0.01537 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 19745.80 | 22707.67 | 112.43 | 1.516 | 1.744 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00874 | 25.03 | 0.01535 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 23024.06 | 26477.66 | 84.48 | 1.768 | 2.033 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00880 | 30.85 | 0.01536 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 24069.07 | 27679.43 | 137.04 | 1.848 | 2.125 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00869 | 29.54 | 0.01536 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 141648.13 | 162895.35 | 519.75 | 10.878 | 12.510 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00926 | 31.20 | 0.01537 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 208413.06 | 239675.02 | 1186.66 | 16.005 | 18.406 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00886 | 25.67 | 0.01535 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 229285.37 | 263678.18 | 841.29 | 17.608 | 20.249 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00898 | 30.93 | 0.01536 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 224552.05 | 258234.86 | 1278.55 | 17.245 | 19.831 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00883 | 29.36 | 0.01536 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 17274.28 | 19865.43 | 63.38 | 1.327 | 1.526 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00922 | 31.20 | 0.01537 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 21112.87 | 24279.80 | 120.21 | 1.621 | 1.865 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00891 | 26.27 | 0.01536 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 25859.99 | 29738.99 | 94.89 | 1.986 | 2.284 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00900 | 31.02 | 0.01536 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 24356.22 | 28009.65 | 138.68 | 1.871 | 2.151 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00885 | 29.54 | 0.01536 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8955.27 | 10298.56 | 284.47 | 0.688 | 0.791 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00856 | 26.87 | 0.01536 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 86166.78 | 99091.80 | 2737.14 | 6.616 | 7.609 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00857 | 26.87 | 0.01536 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8871.42 | 10202.14 | 281.81 | 0.681 | 0.783 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.00 | 27.00 | 0.00856 | 27.07 | 0.01536 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372062.20 | 427871.53 | 545.98 | 28.567 | 32.853 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00853 | 21.55 | 0.01535 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.96 | 0.00036 | -26.20 | 0.00036 | 1.200 | 0.00 |
CORE_BOTTOM | 11157.22 | 13946.52 | 5.59 | 0.833 | 1.078 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 1.078 | 0.00 |
CORE_MID | 355704.55 | 444630.69 | 178.13 | 26.763 | 33.453 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 10.778 | 0.00 |
CORE_TOP | 98062.78 | 122578.48 | 49.11 | 7.456 | 9.320 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 19135.52 | 23919.40 | 76.32 | 1.458 | 1.823 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -26.20 | 0.00036 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 12643.49 | 15804.36 | 78.25 | 0.963 | 1.204 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -26.20 | 0.00036 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 19954.44 | 24943.06 | 79.58 | 1.521 | 1.901 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -26.20 | 0.00036 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 11104.05 | 13880.06 | 68.72 | 0.846 | 1.057 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -26.20 | 0.00036 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 266623.93 | 333279.91 | 1063.39 | 20.333 | 25.416 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -26.20 | 0.00036 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 173051.51 | 216314.38 | 1071.00 | 13.197 | 16.497 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -26.20 | 0.00036 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 260563.94 | 325704.92 | 1039.20 | 19.870 | 24.837 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -26.20 | 0.00036 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 173350.83 | 216688.54 | 1072.85 | 13.220 | 16.525 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -26.20 | 0.00036 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 34499.91 | 43124.89 | 137.60 | 2.632 | 3.290 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -26.20 | 0.00036 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 22355.19 | 27943.99 | 138.35 | 1.706 | 2.132 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -26.20 | 0.00036 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 33872.78 | 42340.98 | 135.09 | 2.584 | 3.230 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -26.20 | 0.00036 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 22647.25 | 28309.06 | 140.16 | 1.728 | 2.160 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -26.20 | 0.00036 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 23.93 | 0.00116 | -26.20 | 0.00036 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.00 | 0.00116 | -26.20 | 0.00036 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 18.73 | 0.00116 | -26.20 | 0.00036 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 18.00 | 27.00 | 0.00850 | -26.20 | 0.00036 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 12.60 | 12.60 | 7.06 | 7.06 | 12.6044 | 7.0627 | 12.6044 | 0.5603 | 0.3000 |
VAV_MID WITH REHEAT | 118.36 | 118.36 | 116.73 | 116.73 | 118.3604 | 116.7289 | 118.3604 | 0.9862 | 0.3000 |
VAV_TOP WITH REHEAT | 14.60 | 14.60 | 20.13 | 20.13 | 14.5977 | 20.1325 | 20.1325 | 1.0000 | 0.3000 |
CAV_BAS | 7.24 | 7.24 | 1.20 | 1.20 | 7.2422 | 2.1727 | 7.2422 | 0.3000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 32.85 | 32.85 | 0.34 | 0.34 | 32.8528 | 16.4263 | 32.8528 | 0.5000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.79 | 0.79 | 0.02 | 0.02 | 0.7908 | 0.7908 | 0.7908 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 7.61 | 7.61 | 0.16 | 0.16 | 7.6086 | 7.6086 | 7.6086 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.78 | 0.78 | 0.02 | 0.02 | 0.7833 | 0.7833 | 0.7833 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 35943.511 | 35943.511 | 2.315548 | 0.00031445 | 772.988 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35943.51 | 35943.51 | 2.315548 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 13946.52 | 0.00 | 36115.90 | 36115.90 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 762425.372 | 762425.372 | 33.453180 | 0.00667003 | 17844.439 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 762425.37 | 762425.37 | 33.453180 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 444630.69 | 0.00 | 765918.09 | 765918.09 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 211115.181 | 211115.181 | 9.319962 | 0.00184693 | 4932.695 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 211115.18 | 209819.91 | 9.319962 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3290 | 122578.48 | 0.00 | 212082.98 | 212082.98 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 41224.376 | 41224.376 | 1.822574 | 0.00036065 | 962.814 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 41224.38 | 41031.54 | 1.822574 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00779187 | 48.0647 | 23919.40 | 0.00 | 41413.39 | 41413.39 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 27239.169 | 27239.169 | 1.204332 | 0.00023830 | 636.174 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27239.17 | 27239.17 | 1.204332 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00778992 | 48.0529 | 15804.36 | 0.00 | 27364.06 | 27364.06 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 42990.999 | 42990.999 | 1.900793 | 0.00037610 | 1004.057 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 42991.00 | 42991.00 | 1.900793 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00779979 | 48.1129 | 24943.06 | 0.00 | 43188.11 | 43188.11 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 23917.278 | 23917.278 | 1.057194 | 0.00020924 | 558.630 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23917.28 | 23917.28 | 1.057194 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00776198 | 47.8828 | 13880.06 | 0.00 | 24026.93 | 24026.93 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 574504.894 | 574504.894 | 25.416412 | 0.00502602 | 13415.337 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 574504.89 | 572198.62 | 25.416412 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00765445 | 47.2310 | 333279.91 | 0.00 | 577139.17 | 577139.17 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 372878.553 | 372878.553 | 16.496616 | 0.00326210 | 8707.096 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 372878.55 | 372878.55 | 16.496616 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00764537 | 47.1759 | 216314.38 | 0.00 | 374588.32 | 374588.32 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 561430.159 | 561430.159 | 24.837294 | 0.00491164 | 13110.128 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 561430.16 | 559160.95 | 24.837294 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00764679 | 47.1844 | 325704.92 | 0.00 | 564004.48 | 564004.48 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 373526.035 | 373526.035 | 16.525407 | 0.00326777 | 8722.194 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 373526.03 | 373526.03 | 16.525407 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00764632 | 47.1817 | 216688.54 | 0.00 | 375238.77 | 375238.77 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 74351.275 | 74351.275 | 3.290241 | 0.00065046 | 1736.055 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 74351.27 | 74073.05 | 3.290241 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00766664 | 47.3067 | 43124.89 | 0.00 | 74692.21 | 74692.21 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 48177.522 | 48177.522 | 2.132009 | 0.00042148 | 1124.910 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 48177.52 | 47997.84 | 2.132009 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00765735 | 47.2502 | 27943.99 | 0.00 | 48398.44 | 48398.44 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 72998.388 | 72998.388 | 3.230326 | 0.00063862 | 1704.472 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 72998.39 | 72724.19 | 3.230326 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00766068 | 47.2704 | 42340.98 | 0.00 | 73333.12 | 73333.12 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 48807.769 | 48807.769 | 2.159933 | 0.00042699 | 1139.621 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 48807.77 | 48626.49 | 2.159933 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00766196 | 47.2784 | 28309.06 | 0.00 | 49031.57 | 49031.57 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 261222.411 | -999.000 | 12.604378 | 0.00933026 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 261222.41 | 209229.94 | 12.604378 | 25.16 | 17.47 | 0.00992108 | 11.03 | 10.95 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 16.1095 | 24.00 | 0.00887321 | 45.5368 | 142458.39 | 0.00 | 270206.29 | 205224.97 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 80348.326 | 80348.326 | 3.781313 | 0.00070292 | 1306.680 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 80348.33 | 80348.33 | 3.781313 | -5.52 | -5.52 | 0.00369333 | 12.89 | 11.21 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 53.6983 | 18.65 | 0.00766933 | 54.7503 | 14817.79 | 0.00 | 72908.28 | 72908.28 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2533061.112 | -999.000 | 118.360409 | 0.09047507 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2533061.11 | 1978157.00 | 118.360409 | 25.26 | 17.66 | 0.01011468 | 11.03 | 10.95 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 17.1561 | 24.00 | 0.00900434 | 46.2017 | 1317272.71 | 0.00 | 2618503.46 | 1942916.94 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 817832.280 | 817832.280 | 35.508123 | 0.00715475 | 13190.660 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 817832.28 | 817832.28 | 35.508123 | -7.07 | -7.07 | 0.00337843 | 12.89 | 11.21 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 57.1869 | 18.34 | 0.00766451 | 55.7817 | 206216.20 | 0.00 | 729191.40 | 729191.40 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 407681.494 | -999.000 | 20.132471 | 0.01456144 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 407681.49 | 329915.18 | 20.132471 | 25.00 | 17.35 | 0.00983306 | 11.05 | 10.96 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 10.0857 | 24.00 | 0.00893778 | 45.8653 | 165070.23 | 0.00 | 421890.32 | 323516.49 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 69215.717 | 69215.717 | 6.039741 | 0.00060553 | 1184.356 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 69215.72 | 69215.72 | 6.039741 | 2.96 | 2.96 | 0.00497777 | 12.89 | 11.21 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 33.6190 | 16.82 | 0.00768789 | 61.5817 | 34622.82 | 0.00 | 69570.77 | 69570.77 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 137571.778 | -999.000 | 7.242230 | 0.00491375 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 137571.78 | 107200.72 | 7.242230 | 23.94 | 17.12 | 0.00998344 | 11.02 | 10.94 | 0.00850000 | 23.36 | 0.01535063 | 20.94 | 16.5716 | 24.00 | 0.00891734 | 45.7594 | 82743.46 | 0.00 | 146243.54 | 107938.81 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.185474 | 0.00087484 | 2622.251 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.185474 | -4.34 | -8.65 | 0.00036134 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 37.6759 | 22.08 | 0.00036134 | 2.1110 | 0.00 | 0.00 | 100071.45 | 100071.45 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 457412.793 | -999.000 | 32.852785 | 0.01633772 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 457412.79 | 450204.00 | 32.852785 | 27.04 | 17.04 | 0.00860349 | 15.00 | 12.56 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 1.0300 | 27.00 | 0.00853305 | 36.6651 | 371638.55 | 0.00 | 490747.74 | 490747.74 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 100000.000 | 100000.000 | 3.185474 | 0.00087484 | 2622.251 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.185474 | -0.27 | -0.27 | 0.00841617 | 29.11 | 17.24 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 10.6230 | 27.00 | 0.00850000 | 36.5206 | 0.00 | 0.00 | 100071.45 | 100071.45 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER BOT | 13089.750 | 10480.439 | 0.790750 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 6544.88 | 6350.28 | 0.527167 | 27.00 | 17.10 | 0.00869751 | 14.42 | 12.33 | 0.00850000 | 26.87 | 0.01535708 | 21.94 | 2.9654 | 27.00 | 0.00856320 | 36.7909 | 8955.27 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER BOT | 27039.507 | 27039.507 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 27039.51 | 27039.51 | 0.790752 | -0.52 | -4.75 | 0.00114674 | 29.11 | 17.24 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 1.9769 | 24.62 | 0.00116258 | 5.8178 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER MID | 125948.910 | 100842.254 | 7.608570 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 62974.46 | 61031.44 | 5.072380 | 27.00 | 17.10 | 0.00870520 | 14.42 | 12.33 | 0.00850000 | 26.87 | 0.01535708 | 21.94 | 3.0819 | 27.00 | 0.00856566 | 36.8014 | 86166.78 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER MID | 260351.495 | 260351.495 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 260351.50 | 260351.50 | 7.608574 | -0.54 | -4.76 | 0.00114614 | 29.11 | 17.24 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 2.0546 | 23.26 | 0.00116261 | 6.3151 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER TOP | 12967.210 | 10382.326 | 0.783350 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6483.60 | 6289.20 | 0.522233 | 27.00 | 17.10 | 0.00869928 | 14.42 | 12.33 | 0.00850000 | 27.07 | 0.01535744 | 22.00 | 2.9934 | 27.00 | 0.00856371 | 36.7931 | 8871.42 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER TOP | 26790.797 | 26790.797 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 26790.80 | 26790.80 | 0.783349 | -0.52 | -4.75 | 0.00114519 | 29.11 | 17.24 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 1.9956 | 21.00 | 0.00116115 | 7.2364 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 35943.511 | 35943.511 | 2.315548 | 0.00031445 | 772.988 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.82970665 | 54.44 | 82.22 | 27.78 | 4528261.97 | 0.7938 | 0.809734 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 35943.51 | 35943.51 | 1.0000 | 2.65953587 | 2.315548 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.31441743 | 60.00 | 32.22 | 27.78 | 0.000 | 35943.51 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.72 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 13946.52 | 0.00 | 36115.90 | 36115.90 | 2.65953587 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 26.12 | 16.71 | 0.00800000 | 46639.6 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 762425.372 | 762425.372 | 33.453180 | 0.00667003 | 17844.439 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.82970665 | 54.44 | 82.22 | 27.78 | 4528261.97 | 16.8370 | 17.175894 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 762425.37 | 762425.37 | 1.0000 | 38.42284473 | 33.453180 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 6.66934934 | 60.00 | 32.22 | 27.78 | 0.000 | 762425.37 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 444630.69 | 0.00 | 765918.09 | 765918.09 | 38.42284473 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.35 | 18.81 | 0.00800000 | 52993.8 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 211115.181 | 211115.181 | 9.319962 | 0.00184693 | 4932.695 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.82970665 | 54.44 | 82.22 | 27.78 | 4528261.97 | 4.6622 | 4.755996 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 211115.18 | 209819.91 | 1.0000 | 10.70449627 | 9.319962 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 1.84673929 | 60.00 | 32.22 | 27.78 | 0.000 | 211115.18 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 49.3290 | 122578.48 | 0.00 | 212082.98 | 212082.98 | 10.70449627 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52872.3 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 41224.376 | 41224.376 | 1.822574 | 0.00036065 | 962.814 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.82970665 | 54.44 | 82.22 | 27.78 | 4528261.97 | 0.9104 | 0.928701 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 41224.38 | 41031.54 | 1.0000 | 2.09332827 | 1.822574 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.36061204 | 60.00 | 32.22 | 27.78 | 0.000 | 41224.38 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00779187 | 21.00 | 0.00779187 | 48.0647 | 23919.40 | 0.00 | 41413.39 | 41413.39 | 2.09332827 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52843.3 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 27239.169 | 27239.169 | 1.204332 | 0.00023830 | 636.174 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.82970665 | 54.44 | 82.22 | 27.78 | 4528261.97 | 0.6015 | 0.613643 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27239.17 | 27239.17 | 1.0000 | 1.38324198 | 1.204332 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.23827582 | 60.00 | 32.22 | 27.78 | 0.000 | 27239.17 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00778992 | 21.00 | 0.00778992 | 48.0529 | 15804.36 | 0.00 | 27364.06 | 27364.06 | 1.38324198 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52842.4 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 42990.999 | 42990.999 | 1.900793 | 0.00037610 | 1004.057 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.82970665 | 54.44 | 82.22 | 27.78 | 4528261.97 | 0.9494 | 0.968500 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 42991.00 | 42991.00 | 1.0000 | 2.18316671 | 1.900793 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.37606565 | 60.00 | 32.22 | 27.78 | 0.000 | 42991.00 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00779979 | 21.00 | 0.00779979 | 48.1129 | 24943.06 | 0.00 | 43188.11 | 43188.11 | 2.18316671 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52842.2 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23917.278 | 23917.278 | 1.057194 | 0.00020924 | 558.630 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.82970665 | 54.44 | 82.22 | 27.78 | 4528261.97 | 0.5282 | 0.538808 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23917.28 | 23917.28 | 1.0000 | 1.21424689 | 1.057194 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.20921743 | 60.00 | 32.22 | 27.78 | 0.000 | 23917.28 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00776198 | 21.00 | 0.00776198 | 47.8828 | 13880.06 | 0.00 | 24026.93 | 24026.93 | 1.21424689 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.76 | 0.00800000 | 52847.3 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 574504.894 | 574504.894 | 25.416412 | 0.00502602 | 13415.337 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.82970665 | 54.44 | 82.22 | 27.78 | 4528261.97 | 12.6871 | 12.942428 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 574504.89 | 572198.62 | 1.0000 | 29.19216836 | 25.416412 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 5.02550673 | 60.00 | 32.22 | 27.78 | 0.000 | 574504.89 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00765445 | 21.00 | 0.00765445 | 47.2310 | 333279.91 | 0.00 | 577139.17 | 577139.17 | 29.19216836 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52830.2 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 372878.553 | 372878.553 | 16.496616 | 0.00326210 | 8707.096 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.82970665 | 54.44 | 82.22 | 27.78 | 4528261.97 | 8.2345 | 8.400196 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 372878.55 | 372878.55 | 1.0000 | 18.94728475 | 16.496616 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 3.26177148 | 60.00 | 32.22 | 27.78 | 0.000 | 372878.55 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00764537 | 21.00 | 0.00764537 | 47.1759 | 216314.38 | 0.00 | 374588.32 | 374588.32 | 18.94728475 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52829.9 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 561430.159 | 561430.159 | 24.837294 | 0.00491164 | 13110.128 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.82970665 | 54.44 | 82.22 | 27.78 | 4528261.97 | 12.3984 | 12.647881 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 561430.16 | 559160.95 | 1.0000 | 28.52701864 | 24.837294 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 4.91113491 | 60.00 | 32.22 | 27.78 | 0.000 | 561430.16 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00764679 | 21.00 | 0.00764679 | 47.1844 | 325704.92 | 0.00 | 564004.48 | 564004.48 | 28.52701864 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52830.7 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 373526.035 | 373526.035 | 16.525407 | 0.00326777 | 8722.194 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.82970665 | 54.44 | 82.22 | 27.78 | 4528261.97 | 8.2488 | 8.414782 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 373526.03 | 373526.03 | 1.0000 | 18.98035288 | 16.525407 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 3.26743535 | 60.00 | 32.22 | 27.78 | 0.000 | 373526.03 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00764632 | 21.00 | 0.00764632 | 47.1817 | 216688.54 | 0.00 | 375238.77 | 375238.77 | 18.98035288 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52829.7 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 74351.275 | 74351.275 | 3.290241 | 0.00065046 | 1736.055 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.82970665 | 54.44 | 82.22 | 27.78 | 4528261.97 | 1.6419 | 1.674983 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 74351.27 | 74073.05 | 1.0000 | 3.77902526 | 3.290241 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.65039103 | 60.00 | 32.22 | 27.78 | 0.000 | 74351.27 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00766664 | 21.00 | 0.00766664 | 47.3067 | 43124.89 | 0.00 | 74692.21 | 74692.21 | 3.77902526 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.18 | 18.76 | 0.00800000 | 52824.8 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 48177.522 | 48177.522 | 2.132009 | 0.00042148 | 1124.910 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.82970665 | 54.44 | 82.22 | 27.78 | 4528261.97 | 1.0639 | 1.085342 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 48177.52 | 47997.84 | 1.0000 | 2.44873168 | 2.132009 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.42143498 | 60.00 | 32.22 | 27.78 | 0.000 | 48177.52 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00765735 | 21.00 | 0.00765735 | 47.2502 | 27943.99 | 0.00 | 48398.44 | 48398.44 | 2.44873168 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.18 | 18.76 | 0.00800000 | 52824.5 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 72998.388 | 72998.388 | 3.230326 | 0.00063862 | 1704.472 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.82970665 | 54.44 | 82.22 | 27.78 | 4528261.97 | 1.6121 | 1.644505 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 72998.39 | 72724.19 | 1.0000 | 3.71020975 | 3.230326 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.63855660 | 60.00 | 32.22 | 27.78 | 0.000 | 72998.39 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00766068 | 21.00 | 0.00766068 | 47.2704 | 42340.98 | 0.00 | 73333.12 | 73333.12 | 3.71020975 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.18 | 18.76 | 0.00800000 | 52825.1 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 48807.769 | 48807.769 | 2.159933 | 0.00042699 | 1139.621 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.82970665 | 54.44 | 82.22 | 27.78 | 4528261.97 | 1.0778 | 1.099540 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 48807.77 | 48626.49 | 1.0000 | 2.48080417 | 2.159933 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.42694809 | 60.00 | 32.22 | 27.78 | 0.000 | 48807.77 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00766196 | 21.00 | 0.00766196 | 47.2784 | 28309.06 | 0.00 | 49031.57 | 49031.57 | 2.48080417 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.18 | 18.76 | 0.00800000 | 52824.2 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 261222.411 | -999.000 | 12.604378 | 0.00933026 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2828 | 1004.8586 | 1.1486 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 12.604378 | 14.47683153 | 4197.9300 | 999.8980 | 135.60440726 | 13.34 | 6.67 | 6.67 | 3796949.59 | 6.8798 | 6.879797 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 261222.41 | 209229.94 | 1.0000 | 14.47683153 | 12.604378 | 25.16 | 17.47 | 0.00992108 | 50558.7 | 11.03 | 10.95 | 0.00850000 | 32514.5 | 9.32930750 | 6.67 | 13.34 | 6.67 | 27554.470 | 233667.94 | 31.20 | 0.01536508 | 23.13 | 2.03050000 | 16.1095 | 24.00 | 0.00887321 | 24.00 | 0.00887321 | 45.5368 | 142458.39 | 0.00 | 270206.29 | 205224.97 | 14.47683153 | 25.16 | 17.98 | 0.00992108 | 50558.7 | 11.31 | 11.11 | 0.00814126 | 31893.9 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 80348.326 | 80348.326 | 3.781313 | 0.00070292 | 1306.680 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 12.604378 | 14.47683153 | 4197.9300 | 999.8980 | 38.82970665 | 54.44 | 82.22 | 27.78 | 4528261.97 | 1.7744 | 1.810084 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 80348.33 | 80348.33 | 1.0000 | 4.34304946 | 3.781313 | -5.52 | -5.52 | 0.00369333 | 3650.1 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 0.70285050 | 60.00 | 32.22 | 27.78 | 0.000 | 80348.33 | -26.20 | 0.00036134 | -26.20 | 2.03050000 | 53.6983 | 18.46 | 0.00755760 | 18.65 | 0.00766933 | 54.7503 | 14817.79 | 0.00 | 72908.28 | 72908.28 | 4.34304946 | 2.80 | 1.52 | 0.00369333 | 12069.6 | 19.39 | 9.89 | 0.00369333 | 28856.9 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2533061.112 | -999.000 | 118.360409 | 0.09047507 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6427 | 1004.8586 | 1.1486 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 118.360409 | 135.94353720 | 4197.9300 | 999.8980 | 135.60440726 | 13.34 | 6.67 | 6.67 | 3796949.59 | 66.7131 | 66.713056 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2533061.11 | 1978157.00 | 1.0000 | 135.94353720 | 118.360409 | 25.26 | 17.66 | 0.01011468 | 51148.3 | 11.03 | 10.95 | 0.00850000 | 32515.2 | 90.46584441 | 6.67 | 13.34 | 6.67 | 258748.064 | 2274313.05 | 31.20 | 0.01536508 | 23.13 | 20.30600000 | 17.1561 | 24.00 | 0.00900434 | 24.00 | 0.00900434 | 46.2017 | 1317272.71 | 0.00 | 2618503.46 | 1942916.94 | 135.94353720 | 25.26 | 18.16 | 0.01011468 | 51148.3 | 11.29 | 11.10 | 0.00814412 | 31886.6 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 817832.280 | 817832.280 | 35.508123 | 0.00715475 | 13190.660 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 118.360409 | 135.94353720 | 4197.9300 | 999.8980 | 38.82970665 | 54.44 | 82.22 | 27.78 | 4528261.97 | 18.0606 | 18.424099 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 817832.28 | 817832.28 | 1.0000 | 40.78306116 | 35.508123 | -7.07 | -7.07 | 0.00337843 | 1303.3 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 7.15402369 | 60.00 | 32.22 | 27.78 | 0.000 | 817832.28 | -26.20 | 0.00036134 | -26.20 | 20.30600000 | 57.1869 | 18.49 | 0.00740845 | 18.34 | 0.00766451 | 55.7817 | 206216.20 | 0.00 | 729191.40 | 729191.40 | 40.78306116 | 2.80 | 1.07 | 0.00337843 | 11280.4 | 20.48 | 10.03 | 0.00337843 | 29160.1 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 407681.494 | -999.000 | 20.132471 | 0.01456144 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.1192 | 1004.8586 | 1.1486 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 20.132471 | 23.12326713 | 4197.9300 | 999.8980 | 135.60440726 | 13.34 | 6.67 | 6.67 | 3796949.59 | 10.7371 | 10.737079 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 407681.49 | 329915.18 | 1.0000 | 23.12326713 | 20.132471 | 25.00 | 17.35 | 0.00983306 | 50170.9 | 11.05 | 10.96 | 0.00850000 | 32540.1 | 14.55995296 | 6.67 | 13.34 | 6.67 | 43411.919 | 364269.57 | 31.20 | 0.01536508 | 23.13 | 2.03050000 | 10.0857 | 24.00 | 0.00893778 | 24.00 | 0.00893778 | 45.8653 | 165070.23 | 0.00 | 421890.32 | 323516.49 | 23.12326713 | 25.00 | 17.85 | 0.00983306 | 50170.9 | 11.33 | 11.12 | 0.00814617 | 31925.6 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 69215.717 | 69215.717 | 6.039741 | 0.00060553 | 1184.356 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 20.132471 | 23.12326713 | 4197.9300 | 999.8980 | 38.82970665 | 54.44 | 82.22 | 27.78 | 4528261.97 | 1.5285 | 1.559289 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 69215.72 | 69215.72 | 1.0000 | 6.93698014 | 6.039741 | 2.96 | 2.96 | 0.00497777 | 15450.2 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 0.60546751 | 60.00 | 32.22 | 27.78 | 0.000 | 69215.72 | -26.20 | 0.00036134 | -26.20 | 2.03050000 | 33.6190 | 17.73 | 0.00731578 | 16.82 | 0.00768789 | 61.5817 | 34622.82 | 0.00 | 69570.77 | 69570.77 | 6.93698014 | 2.80 | 2.80 | 0.00497777 | 15288.6 | 12.69 | 8.28 | 0.00497777 | 25317.5 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 137571.778 | -999.000 | 7.242230 | 0.00491375 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.3987 | 1004.8586 | 1.1486 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 7.242230 | 8.31810566 | 4197.9300 | 999.8980 | 135.60440726 | 13.34 | 6.67 | 6.67 | 3796949.59 | 3.6232 | 3.623218 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 137571.78 | 107200.72 | 1.0000 | 8.31810566 | 7.242230 | 23.94 | 17.12 | 0.00998344 | 49472.7 | 11.02 | 10.94 | 0.00850000 | 32504.6 | 4.91324389 | 6.67 | 13.34 | 6.67 | 15916.836 | 121654.94 | 23.36 | 0.01535063 | 20.94 | 1.20015641 | 16.5716 | 24.06 | 0.00891734 | 24.00 | 0.00891734 | 45.7594 | 82743.46 | 0.00 | 146243.54 | 107938.81 | 8.31810566 | 23.94 | 17.62 | 0.00998344 | 49472.7 | 11.26 | 11.11 | 0.00815743 | 31891.4 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.185474 | 0.00087484 | 2622.251 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 7.242230 | 8.31810566 | 4197.9300 | 999.8980 | 38.82970665 | 54.44 | 82.22 | 27.78 | 4528261.97 | 2.2084 | 2.252797 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.185474 | -4.34 | -8.65 | 0.00036134 | -3462.0 | 32.11 | 18.22 | 0.00800000 | 52750.5 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -26.20 | 0.00036134 | -26.20 | 1.20015641 | 37.6759 | 0.00 | 0.00036134 | 22.08 | 0.00036134 | 2.1110 | 0.00 | 0.00 | 100071.45 | 100071.45 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40238.9 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 457412.793 | -999.000 | 32.852785 | 0.01633772 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8335 | 1004.8586 | 1.1486 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 32.852785 | 37.73325713 | 4197.9300 | 999.8980 | 135.60440726 | 13.34 | 6.67 | 6.67 | 3796949.59 | 12.0468 | 12.046849 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 457412.79 | 450204.00 | 1.0000 | 37.73325713 | 32.852785 | 27.04 | 17.04 | 0.00860349 | 49121.4 | 15.00 | 12.56 | 0.00850000 | 36571.1 | 16.33605851 | 6.67 | 13.34 | 6.67 | 34106.405 | 423306.39 | 31.20 | 0.01536508 | 23.13 | 0.33839277 | 1.0300 | 27.00 | 0.00853305 | 27.00 | 0.00853305 | 36.6651 | 371638.55 | 0.00 | 490747.74 | 490747.74 | 37.73325713 | 27.04 | 17.53 | 0.00860349 | 49121.4 | 14.30 | 12.81 | 0.00860349 | 36115.7 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.185474 | 0.00087484 | 2622.251 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 32.852785 | 37.73325713 | 4197.9300 | 999.8980 | 38.82970665 | 54.44 | 82.22 | 27.78 | 4528261.97 | 2.2084 | 2.252797 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.185474 | -0.27 | -0.27 | 0.00841617 | 20772.9 | 29.11 | 17.24 | 0.00800000 | 49691.3 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -26.20 | 0.00036134 | -26.20 | 0.33839277 | 10.6230 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 36.5206 | 0.00 | 0.00 | 100071.45 | 100071.45 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40238.9 | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13089.750 | 10480.439 | 0.790750 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0082 | 1004.8586 | 1.1486 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.790752 | 0.90822253 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 6544.88 | 6350.28 | 1.0000 | 0.60548035 | 0.527167 | 27.00 | 17.10 | 0.00869751 | 49315.4 | 14.42 | 12.33 | 0.00850000 | 35978.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6544.88 | 26.87 | 0.01535708 | 21.94 | 0.01563234 | 2.9654 | 27.00 | 0.00856320 | 27.00 | 0.00856320 | 36.7909 | 8955.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27039.507 | 27039.507 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.790752 | 0.90822253 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 27039.51 | 27039.51 | 1.0000 | 0.90822253 | 0.790752 | -0.52 | -4.75 | 0.00114674 | 2346.4 | 29.11 | 17.24 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27039.51 | -26.20 | 0.00036134 | -26.20 | 0.01563234 | 1.9769 | 0.00 | 0.00116258 | 24.62 | 0.00116258 | 5.8178 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 125948.910 | 100842.254 | 7.608570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0225 | 1004.8586 | 1.1486 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.608574 | 8.73887186 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 62974.46 | 61031.44 | 1.0000 | 5.82591161 | 5.072380 | 27.00 | 17.10 | 0.00870520 | 49334.9 | 14.42 | 12.33 | 0.00850000 | 35978.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 62974.46 | 26.87 | 0.01535708 | 21.94 | 0.15632344 | 3.0819 | 27.00 | 0.00856566 | 27.00 | 0.00856566 | 36.8014 | 86166.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 260351.495 | 260351.495 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.608574 | 8.73887186 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 260351.50 | 260351.50 | 1.0000 | 8.73887186 | 7.608574 | -0.54 | -4.76 | 0.00114614 | 2324.4 | 29.11 | 17.24 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 260351.50 | -26.20 | 0.00036134 | -26.20 | 0.15632344 | 2.0546 | 0.00 | 0.00116261 | 23.26 | 0.00116261 | 6.3151 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12967.210 | 10382.326 | 0.783350 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0115 | 1004.8586 | 1.1486 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.783349 | 0.89972004 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6483.60 | 6289.20 | 1.0000 | 0.59981414 | 0.522233 | 27.00 | 17.10 | 0.00869928 | 49323.9 | 14.42 | 12.33 | 0.00850000 | 35978.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6483.60 | 27.07 | 0.01535744 | 22.00 | 0.01563234 | 2.9934 | 27.00 | 0.00856371 | 27.00 | 0.00856371 | 36.7931 | 8871.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26790.797 | 26790.797 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.783349 | 0.89972004 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 26790.80 | 26790.80 | 1.0000 | 0.89972004 | 0.783349 | -0.52 | -4.75 | 0.00114519 | 2337.6 | 29.11 | 17.24 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26790.80 | -26.20 | 0.00036134 | -26.20 | 0.01563234 | 1.9956 | 0.00 | 0.00116115 | 21.00 | 0.00116115 | 7.2364 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 12.60 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 118.36 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 20.13 | - | |||
CAV_BAS_OA_CONTROLLER | FixedDryBulb | 1.20 | 7.24 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 32.85 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2189.83 | 2655.00 | 40.67 |
CORE_BOTTOM | 2308.50 | 2425.50 | 54.17 |
CORE_MID | 2219.17 | 3283.33 | 483.83 |
CORE_TOP | 2949.33 | 4328.50 | 1692.00 |
PERIMETER_BOT_ZN_3 | 3253.67 | 4045.50 | 1689.17 |
PERIMETER_BOT_ZN_2 | 3173.33 | 4111.83 | 1697.17 |
PERIMETER_BOT_ZN_1 | 3218.00 | 3693.67 | 1475.83 |
PERIMETER_BOT_ZN_4 | 2916.67 | 3885.50 | 1196.17 |
PERIMETER_MID_ZN_3 | 3257.33 | 4894.83 | 2482.50 |
PERIMETER_MID_ZN_2 | 3011.83 | 3821.67 | 2036.00 |
PERIMETER_MID_ZN_1 | 3231.17 | 4151.67 | 1841.67 |
PERIMETER_MID_ZN_4 | 3351.33 | 4541.17 | 2233.50 |
PERIMETER_TOP_ZN_3 | 3487.33 | 5200.17 | 2921.67 |
PERIMETER_TOP_ZN_2 | 3758.00 | 4660.50 | 2664.33 |
PERIMETER_TOP_ZN_1 | 3406.17 | 4577.33 | 2306.50 |
PERIMETER_TOP_ZN_4 | 3619.50 | 4764.00 | 2664.67 |
DATACENTER_BOT_ZN_6 | 5635.50 | 1133.83 | 1129.83 |
DATACENTER_MID_ZN_6 | 4860.00 | 692.00 | 508.50 |
DATACENTER_TOP_ZN_6 | 4245.67 | 1125.83 | 609.67 |
DATACENTER_BASEMENT_ZN_6 | 5917.83 | 2856.50 | 2854.83 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5941.67 | 5281.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.83 | 7.83 | 0.83 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 1.67 | 0.00 | 0.33 | 0.00 |
CORE_TOP | 26.33 | 0.00 | 1.50 | 0.00 |
PERIMETER_BOT_ZN_3 | 49.00 | 0.00 | 5.83 | 0.00 |
PERIMETER_BOT_ZN_2 | 50.83 | 14.00 | 3.67 | 14.00 |
PERIMETER_BOT_ZN_1 | 55.33 | 16.17 | 3.83 | 16.17 |
PERIMETER_BOT_ZN_4 | 17.33 | 37.83 | 0.17 | 21.50 |
PERIMETER_MID_ZN_3 | 213.67 | 0.00 | 48.00 | 0.00 |
PERIMETER_MID_ZN_2 | 343.50 | 13.33 | 41.17 | 13.33 |
PERIMETER_MID_ZN_1 | 167.00 | 11.83 | 25.33 | 11.83 |
PERIMETER_MID_ZN_4 | 168.00 | 21.83 | 32.17 | 11.83 |
PERIMETER_TOP_ZN_3 | 354.17 | 0.00 | 89.33 | 0.00 |
PERIMETER_TOP_ZN_2 | 343.33 | 9.00 | 77.17 | 9.00 |
PERIMETER_TOP_ZN_1 | 304.33 | 8.17 | 57.50 | 8.17 |
PERIMETER_TOP_ZN_4 | 289.17 | 21.67 | 62.50 | 11.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 136.17 | 0.00 | 90.67 |
DATACENTER_MID_ZN_6 | 0.00 | 97.67 | 0.00 | 68.50 |
DATACENTER_TOP_ZN_6 | 0.00 | 89.00 | 0.00 | 62.50 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 2.83 | 0.00 | 2.83 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 648.00 | 252.67 | 118.33 | 173.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.43 | 149.60 | 6779.02 | 0.795 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 56.07 | 134.35 | 6849.35 | 0.755 | 0.000 | 0.000 | 0.000 |
CORE_MID | 56.07 | 134.35 | 6849.35 | 0.617 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 56.07 | 134.35 | 6849.35 | 0.602 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.04 | 16.87 | 860.00 | 1.056 | 0.063 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.54 | 10.87 | 554.22 | 1.642 | 0.065 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.04 | 16.87 | 860.02 | 1.351 | 0.063 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.54 | 10.87 | 554.22 | 1.988 | 0.066 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.04 | 16.87 | 860.00 | 1.385 | 0.148 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.97 | 10.87 | 554.22 | 1.622 | 0.162 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.04 | 16.87 | 860.02 | 1.516 | 0.148 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.54 | 10.87 | 554.22 | 1.788 | 0.153 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.04 | 16.87 | 860.00 | 1.582 | 0.183 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.54 | 10.87 | 554.22 | 1.676 | 0.190 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.04 | 16.87 | 860.02 | 1.643 | 0.184 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.54 | 10.87 | 554.22 | 1.712 | 0.190 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.60 | 42.18 | 1911.37 | 16.549 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.43 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 56.07 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 56.07 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 56.07 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.04 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.04 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.04 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.97 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.04 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.04 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.04 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.60 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.43 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 56.07 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 56.07 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 56.07 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.04 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.04 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.04 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.97 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.04 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.04 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.04 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.60 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1034.72 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 31930320.69 | 0.00 | 31930320.69 | 0.00 | 31930320.69 | 37848132.68 | 4282.16 | 3227.77 | 1250.06 | 93.91 |
CORE_BOTTOM | 31553764.01 | 0.00 | 31553764.01 | 0.00 | 31553764.01 | 33990283.35 | 6315.02 | 28.11 | 2416.86 | 355.13 |
CORE_MID | 0.26E+09 | 0.00 | 0.26E+09 | 0.00 | 0.26E+09 | 0.34E+09 | 6796.38 | 25.99 | 1937.63 | 624.60 |
CORE_TOP | 24604523.61 | 0.00 | 24604523.61 | 0.00 | 24604523.61 | 33990283.35 | 6836.36 | 21.08 | 1902.56 | 380.76 |
PERIMETER_BOT_ZN_3 | 5627795.96 | 0.00 | 5627795.96 | 650322.70 | 6278118.65 | 4267819.30 | 3908.66 | 20.02 | 4831.32 | 355.13 |
PERIMETER_BOT_ZN_2 | 5626839.55 | 0.00 | 5626839.55 | 433548.17 | 6060387.71 | 2750345.05 | 3790.34 | 3.99 | 4965.67 | 355.13 |
PERIMETER_BOT_ZN_1 | 7142969.11 | 0.00 | 7142969.11 | 650322.70 | 7793291.81 | 4267912.63 | 3854.70 | 5.44 | 4899.86 | 355.13 |
PERIMETER_BOT_ZN_4 | 6815662.07 | 0.00 | 6815662.07 | 433548.17 | 7249210.24 | 2750345.05 | 3737.66 | 6.90 | 5015.44 | 355.13 |
PERIMETER_MID_ZN_3 | 74028932.57 | 0.00 | 74028932.57 | 1525195.93 | 75554128.50 | 42678193.03 | 3801.83 | 17.03 | 4941.14 | 624.60 |
PERIMETER_MID_ZN_2 | 51164551.81 | 0.00 | 51164551.81 | 1016796.59 | 52181348.40 | 27503450.52 | 4260.97 | 18.26 | 4480.78 | 1043.82 |
PERIMETER_MID_ZN_1 | 80321668.68 | 0.00 | 80321668.68 | 1525195.93 | 81846864.61 | 42679126.28 | 3811.66 | 11.29 | 4937.05 | 624.60 |
PERIMETER_MID_ZN_4 | 61252358.51 | 0.00 | 61252358.51 | 1016796.59 | 62269155.10 | 27503450.52 | 3653.99 | 11.59 | 5094.43 | 624.60 |
PERIMETER_TOP_ZN_3 | 8166907.85 | 0.00 | 8166907.85 | 1893702.01 | 10060609.86 | 4267819.30 | 4058.57 | 4.36 | 4697.07 | 380.76 |
PERIMETER_TOP_ZN_2 | 5559030.15 | 0.00 | 5559030.15 | 1262467.14 | 6821497.29 | 2750345.05 | 4057.58 | 4.13 | 4698.30 | 380.74 |
PERIMETER_TOP_ZN_1 | 8454121.78 | 0.00 | 8454121.78 | 1893702.01 | 10347823.79 | 4267912.63 | 4062.60 | 4.49 | 4692.92 | 380.76 |
PERIMETER_TOP_ZN_4 | 5678017.03 | 0.00 | 5678017.03 | 1262467.14 | 6940484.18 | 2750345.05 | 4054.75 | 4.72 | 4700.53 | 380.74 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.29E+09 | 0.00 | 0.29E+09 | 0.00 | 0.29E+09 | 10671554.30 | 681.22 | 1172.00 | 6906.79 | 2480.18 |
Total Facility | 0.57E+10 | 0.00 | 0.57E+10 | 59319930.40 | 0.58E+10 | 0.50E+10 | 7312.27 | 4430.89 | 8162.47 | 2973.15 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.4688 | 0.0000 | 1.4688 | 0.0000 | 1.4688 | 1.2002 | 1503.96 | 3226.84 | 1212.19 |
CORE_BOTTOM | 1.4081 | 0.0000 | 1.4081 | 0.0000 | 1.4081 | 1.0778 | 3629.41 | 27.85 | 2285.74 |
CORE_MID | 11.5258 | 0.0000 | 11.5258 | 0.0000 | 11.5258 | 10.7782 | 4035.86 | 25.59 | 1881.54 |
CORE_TOP | 1.1272 | 0.0000 | 1.1272 | 0.0000 | 1.1272 | 1.0778 | 4049.31 | 20.49 | 1873.20 |
PERIMETER_BOT_ZN_3 | 0.2484 | 0.0000 | 0.2484 | 0.0149 | 0.2633 | 0.1353 | 1278.61 | 17.86 | 4646.53 |
PERIMETER_BOT_ZN_2 | 0.2490 | 0.0000 | 0.2490 | 0.0100 | 0.2590 | 0.0872 | 1201.54 | 2.85 | 4738.61 |
PERIMETER_BOT_ZN_1 | 0.3175 | 0.0000 | 0.3175 | 0.0149 | 0.3324 | 0.1353 | 1240.15 | 4.26 | 4698.59 |
PERIMETER_BOT_ZN_4 | 0.3013 | 0.0000 | 0.3013 | 0.0100 | 0.3113 | 0.0872 | 1183.74 | 1.67 | 4757.59 |
PERIMETER_MID_ZN_3 | 3.2712 | 0.0000 | 3.2712 | 0.0351 | 3.3063 | 1.3533 | 1251.40 | 8.10 | 4683.51 |
PERIMETER_MID_ZN_2 | 2.4628 | 0.0000 | 2.4628 | 0.0248 | 2.4876 | 0.8721 | 1214.82 | 7.52 | 3811.67 |
PERIMETER_MID_ZN_1 | 3.5702 | 0.0000 | 3.5702 | 0.0351 | 3.6052 | 1.3533 | 1250.54 | 2.62 | 4689.84 |
PERIMETER_MID_ZN_4 | 2.7162 | 0.0000 | 2.7162 | 0.0234 | 2.7396 | 0.8721 | 1192.37 | 5.46 | 4745.17 |
PERIMETER_TOP_ZN_3 | 0.3736 | 0.0000 | 0.3736 | 0.0435 | 0.4172 | 0.1353 | 1318.89 | 3.04 | 4621.08 |
PERIMETER_TOP_ZN_2 | 0.2546 | 0.0000 | 0.2546 | 0.0290 | 0.2836 | 0.0872 | 1318.23 | 2.92 | 4621.85 |
PERIMETER_TOP_ZN_1 | 0.3872 | 0.0000 | 0.3872 | 0.0435 | 0.4307 | 0.1353 | 1321.59 | 2.77 | 4618.64 |
PERIMETER_TOP_ZN_4 | 0.2601 | 0.0000 | 0.2601 | 0.0290 | 0.2891 | 0.0872 | 1315.98 | 3.39 | 4623.63 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8.5619 | 0.0000 | 8.5619 | 0.0000 | 8.5619 | 0.3384 | 307.64 | 1171.45 | 4463.92 |
Total Facility | 251.5845 | 0.0000 | 251.5845 | 1.3774 | 252.9619 | 158.4706 | 4495.27 | 4382.23 | 5674.55 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 74885963.70 | 0.00 | 74885963.70 | 48026705.38 | 3863.10 | 6.66 | 4890.24 | 355.13 |
VAV_MID WITH REHEAT | 0.69E+09 | 0.00 | 0.69E+09 | 0.48E+09 | 3966.01 | 9.75 | 4784.23 | 624.60 |
VAV_TOP WITH REHEAT | 69207638.33 | 0.00 | 69207638.33 | 48026705.38 | 4123.02 | 3.94 | 4633.03 | 380.72 |
CAV_BAS | 42012504.48 | 0.00 | 42012504.48 | 37848132.68 | 4260.85 | 1.01 | 4498.14 | 93.91 |
AIRLOOP DATACENTER BASEMENT | 0.38E+09 | 0.00 | 0.38E+09 | 10671554.30 | 670.85 | 0.70 | 8088.45 | 2480.06 |
AIRLOOP DATACENTER BOT | 322270.54 | 0.00 | 322270.54 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3222705.41 | 0.00 | 3222705.41 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 322270.54 | 0.00 | 322270.54 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.3301 | 0.0000 | 3.3301 | 1.5229 | 1230.63 | 4.06 | 4708.32 |
VAV_MID WITH REHEAT | 30.7877 | 0.0000 | 30.7877 | 15.2292 | 1289.29 | 4.29 | 4649.42 |
VAV_TOP WITH REHEAT | 3.1696 | 0.0000 | 3.1696 | 1.5229 | 1363.92 | 3.13 | 4575.95 |
CAV_BAS | 1.9326 | 0.0000 | 1.9326 | 1.2002 | 1490.68 | 0.55 | 4451.77 |
AIRLOOP DATACENTER BASEMENT | 11.2948 | 0.0000 | 11.2948 | 0.3384 | 304.37 | 0.18 | 5638.45 |
AIRLOOP DATACENTER BOT | 0.0151 | 0.0000 | 0.0151 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1506 | 0.0000 | 0.1506 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0151 | 0.0000 | 0.0151 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 34.56 | 3171.72 | 0.00 | 0.00 | 0.00 | 1938.85 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 98.74 | 3540.60 | 0.00 | 0.00 | 0.00 | 1869.16 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 22.67 | 2916.02 | 0.00 | 0.00 | 0.00 | 2262.29 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 3241.49 | 1391.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 1170.96 | 6963.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.4710 | 5.4364 | 0.0000 | 0.0000 | 0.0000 | 2.2661 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 26.6014 | 46.6823 | 0.0000 | 0.0000 | 0.0000 | 23.6591 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.7100 | 5.3698 | 0.0000 | 0.0000 | 0.0000 | 2.2822 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.5835 | 4.8984 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4468 | 14.8566 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0206 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2062 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0206 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1343 |
Defaulted Fields | 1287 |
Fields with Defaults | 3878 |
Autosized Fields | 320 |
Autosizable Fields | 465 |
Autocalculated Fields | 223 |
Autocalculatable Fields | 468 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 31516.73 | 290095.75 | 28-MAY-05:00 | 2520439.57 | 04-AUG-15:30 |
Electricity:Building | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 758.19 | 15076.70 | 01-JAN-00:10 | 42602.33 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 589.38 | 5907.35 | 01-JAN-00:10 | 43380.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5893.79 | 59073.32 | 01-JAN-00:10 | 433806.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 589.38 | 5907.33 | 01-JAN-00:10 | 43380.63 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 740.04 | 7417.49 | 01-JAN-00:10 | 54469.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 476.91 | 4780.12 | 01-JAN-00:10 | 35102.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 740.05 | 7417.62 | 01-JAN-00:10 | 54470.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 476.91 | 4780.09 | 01-JAN-00:10 | 35102.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7588.97 | 95364.66 | 01-JAN-00:10 | 387850.11 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1622.27 | 19890.94 | 01-JAN-00:10 | 85232.07 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:HVAC | 4441.73 | 33075.97 | 14-MAY-05:50 | 374397.01 | 17-APR-15:30 |
ExteriorEquipment:Electricity | 2623.11 | 22123.82 | 01-JAN-00:10 | 235096.12 | 03-APR-07:20 |
Transformer:ExteriorEquipment:Electricity | 56.04 | 979.82 | 01-JAN-00:10 | 3543.78 | 03-APR-07:20 |
ElectricityPurchased:Facility | 31516.73 | 290095.75 | 28-MAY-05:00 | 2520439.57 | 04-AUG-15:30 |
ElectricityPurchased:Plant | 31516.73 | 290095.75 | 28-MAY-05:00 | 2520439.57 | 04-AUG-15:30 |
Cogeneration:ElectricityPurchased | 31516.73 | 290095.75 | 28-MAY-05:00 | 2520439.57 | 04-AUG-15:30 |
General:Cogeneration:ElectricityPurchased | 31516.73 | 290095.75 | 28-MAY-05:00 | 2520439.57 | 04-AUG-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 31516.73 | 290095.75 | 28-MAY-05:00 | 2520439.57 | 04-AUG-15:30 |
ElectricityNet:Plant | 31516.73 | 290095.75 | 28-MAY-05:00 | 2520439.57 | 04-AUG-15:30 |
Cogeneration:ElectricityNet | 31516.73 | 290095.75 | 28-MAY-05:00 | 2520439.57 | 04-AUG-15:30 |
General:Cogeneration:ElectricityNet | 31516.73 | 290095.75 | 28-MAY-05:00 | 2520439.57 | 04-AUG-15:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1965.43 | 0.00 | 06-JAN-00:30 | 515044.72 | 04-AUG-15:30 |
General:Cooling:Electricity | 1965.43 | 0.00 | 06-JAN-00:30 | 515044.72 | 04-AUG-15:30 |
Fans:Electricity | 2912.16 | 26021.95 | 01-JAN-10:40 | 305773.99 | 04-AUG-15:30 |
General:Fans:Electricity | 2912.16 | 26021.95 | 01-JAN-10:40 | 305773.99 | 04-AUG-15:30 |
ExteriorLights:Electricity | 1006.00 | 0.00 | 01-JAN-08:00 | 64082.80 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 1006.00 | 0.00 | 01-JAN-08:00 | 64082.80 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.31 | 1944.00 | 01-JAN-00:10 | 1944.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1053.07 | 0.00 | 18-MAR-13:40 | 100000.00 | 25-MAR-15:20 |
General:Humidifier:Electricity | 1053.07 | 0.00 | 18-MAR-13:40 | 100000.00 | 25-MAR-15:20 |
Electricity:Plant | 3214.80 | 0.00 | 12-JAN-00:10 | 686412.04 | 04-AUG-13:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 484.77 | 0.00 | 01-JAN-00:10 | 60480.04 | 21-FEB-12:30 |
Water Heater:WaterSystems:Electricity | 484.77 | 0.00 | 01-JAN-00:10 | 60480.04 | 21-FEB-12:30 |
HeatRejection:Electricity | 176.75 | 0.00 | 01-JAN-00:10 | 58522.13 | 11-JUN-15:10 |
General:HeatRejection:Electricity | 176.75 | 0.00 | 01-JAN-00:10 | 58522.13 | 11-JUN-15:10 |
Pumps:Electricity | 1008.31 | 0.00 | 12-JAN-00:10 | 102278.78 | 04-AUG-15:30 |
General:Pumps:Electricity | 1008.31 | 0.00 | 12-JAN-00:10 | 102278.78 | 04-AUG-15:30 |
WIRED_LTG_ELECTRICITY | 157.66 | 0.00 | 01-JAN-00:10 | 13766.21 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 7173.53 | 0.00 | 01-JAN-00:40 | 3142160.44 | 30-JAN-07:30 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 7173.53 | 0.00 | 01-JAN-00:40 | 3142160.44 | 30-JAN-07:30 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 7173.53 | 0.00 | 01-JAN-00:40 | 3142160.44 | 30-JAN-07:30 |
Boiler:Heating:NaturalGas | 7173.53 | 0.00 | 01-JAN-00:40 | 3142160.44 | 30-JAN-07:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 8725.08 | 0.00 | 01-JAN-00:20 | 3035141.26 | 04-AUG-15:30 |
PlantLoopCoolingDemand:HVAC | 8725.08 | 0.00 | 01-JAN-00:20 | 3035141.26 | 04-AUG-15:30 |
CoolingCoils:PlantLoopCoolingDemand | 8725.08 | 0.00 | 01-JAN-00:20 | 3035141.26 | 04-AUG-15:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 8977.76 | 0.00 | 20-MAR-00:40 | 0.00 | 07-SEP-14:20 |
Water:HVAC | 391.74 | 0.00 | 18-MAR-13:40 | 0.00 | 06-APR-14:30 |
Humidifier:Water | 391.74 | 0.00 | 18-MAR-13:40 | 0.00 | 06-APR-14:30 |
General:Humidifier:Water | 391.74 | 0.00 | 18-MAR-13:40 | 0.00 | 06-APR-14:30 |
MainsWater:Facility | 8977.76 | 0.00 | 20-MAR-00:40 | 0.00 | 07-SEP-14:20 |
MainsWater:HVAC | 391.74 | 0.00 | 18-MAR-13:40 | 0.00 | 06-APR-14:30 |
Humidifier:MainsWater | 391.74 | 0.00 | 18-MAR-13:40 | 0.00 | 06-APR-14:30 |
General:Humidifier:MainsWater | 391.74 | 0.00 | 18-MAR-13:40 | 0.00 | 06-APR-14:30 |
Water:Plant | 8586.02 | 0.00 | 01-JAN-00:10 | 0.00 | 07-SEP-14:20 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 19-APR-11:30 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 19-APR-11:30 |
MainsWater:Plant | 8586.02 | 0.00 | 01-JAN-00:10 | 0.00 | 07-SEP-14:20 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 19-APR-11:30 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 19-APR-11:30 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 6305.85 | 0.00 | 01-JAN-00:10 | 0.00 | 07-SEP-14:20 |
General:HeatRejection:Water | 6305.85 | 0.00 | 01-JAN-00:10 | 0.00 | 07-SEP-14:20 |
HeatRejection:MainsWater | 6305.85 | 0.00 | 01-JAN-00:10 | 0.00 | 07-SEP-14:20 |
General:HeatRejection:MainsWater | 6305.85 | 0.00 | 01-JAN-00:10 | 0.00 | 07-SEP-14:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 70819.02 | 100530.63 | 10-JAN-00:50 | 14746100.91 | 04-AUG-15:30 |
EnergyTransfer:Building | 21112.43 | 87381.63 | 11-JAN-22:30 | 2156948.42 | 11-DEC-05:10 |
EnergyTransfer:Zone:BASEMENT | 651.33 | 0.00 | 01-JAN-00:10 | 82894.31 | 05-SEP-05:10 |
Heating:EnergyTransfer | 2277.14 | 0.00 | 07-FEB-22:10 | 1927492.62 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 1.31 | 0.00 | 01-JAN-00:10 | 27625.22 | 02-FEB-07:40 |
General:Heating:EnergyTransfer | 2277.14 | 0.00 | 07-FEB-22:10 | 1927492.62 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 1.31 | 0.00 | 01-JAN-00:10 | 27625.22 | 02-FEB-07:40 |
Cooling:EnergyTransfer | 18835.29 | 80561.81 | 30-JAN-05:10 | 1938973.38 | 04-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 650.02 | 0.00 | 01-JAN-00:10 | 82564.03 | 05-SEP-05:10 |
General:Cooling:EnergyTransfer | 18835.29 | 80561.81 | 30-JAN-05:10 | 1938973.38 | 04-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 650.02 | 0.00 | 01-JAN-00:10 | 82564.03 | 05-SEP-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 582.40 | 0.00 | 01-JAN-00:10 | 57063.05 | 14-AUG-15:50 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.01 | 0.00 | 01-JAN-00:10 | 10533.46 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.01 | 0.00 | 01-JAN-00:10 | 10533.46 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 582.39 | 0.00 | 01-JAN-00:10 | 57063.05 | 14-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 582.39 | 0.00 | 01-JAN-00:10 | 57063.05 | 14-AUG-15:50 |
EnergyTransfer:Zone:CORE_MID | 4623.92 | 0.00 | 01-JAN-00:40 | 567759.46 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 29.95 | 0.00 | 01-JAN-00:20 | 567759.46 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 29.95 | 0.00 | 01-JAN-00:20 | 567759.46 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4593.97 | 0.00 | 01-JAN-00:40 | 495605.76 | 30-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4593.97 | 0.00 | 01-JAN-00:40 | 495605.76 | 30-JUN-16:00 |
EnergyTransfer:Zone:CORE_TOP | 447.03 | 0.00 | 01-JAN-00:40 | 109071.36 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 48.95 | 0.00 | 01-JAN-00:40 | 109071.36 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 48.95 | 0.00 | 01-JAN-00:40 | 109071.36 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 398.08 | 0.00 | 01-JAN-00:20 | 61703.34 | 04-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 398.08 | 0.00 | 01-JAN-00:20 | 61703.34 | 04-AUG-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 89.59 | 0.00 | 01-JAN-00:10 | 22287.57 | 30-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 17.23 | 0.00 | 01-JAN-00:10 | 22287.57 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 17.23 | 0.00 | 01-JAN-00:10 | 22287.57 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 72.37 | 0.00 | 01-JAN-00:10 | 12627.97 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 72.37 | 0.00 | 01-JAN-00:10 | 12627.97 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 79.56 | 0.00 | 01-JAN-00:10 | 16154.49 | 02-AUG-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 11.21 | 0.00 | 01-JAN-00:10 | 15539.50 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 11.21 | 0.00 | 01-JAN-00:10 | 15539.50 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 68.35 | 0.00 | 01-JAN-00:10 | 16154.49 | 02-AUG-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 68.35 | 0.00 | 01-JAN-00:10 | 16154.49 | 02-AUG-08:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 120.92 | 0.00 | 01-JAN-00:10 | 25742.76 | 07-SEP-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 15.57 | 0.00 | 01-JAN-00:10 | 23109.21 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 15.57 | 0.00 | 01-JAN-00:10 | 23109.21 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 105.35 | 0.00 | 01-JAN-00:10 | 25742.76 | 07-SEP-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 105.35 | 0.00 | 01-JAN-00:10 | 25742.76 | 07-SEP-12:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 102.75 | 0.00 | 01-JAN-00:10 | 21213.67 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 4.62 | 0.00 | 01-JAN-00:10 | 13430.14 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 4.62 | 0.00 | 01-JAN-00:10 | 13430.14 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 98.13 | 0.00 | 01-JAN-00:10 | 21213.67 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 98.13 | 0.00 | 01-JAN-00:10 | 21213.67 | 02-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1131.24 | 0.00 | 01-JAN-00:40 | 320203.07 | 19-JAN-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 529.73 | 0.00 | 01-JAN-00:40 | 320203.07 | 19-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 529.73 | 0.00 | 01-JAN-00:40 | 320203.07 | 19-JAN-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 601.51 | 0.00 | 01-JAN-00:20 | 118501.11 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 601.51 | 0.00 | 01-JAN-00:20 | 118501.11 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 847.46 | 0.00 | 01-JAN-00:40 | 218354.00 | 09-DEC-05:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 301.83 | 0.00 | 01-JAN-00:40 | 218354.00 | 09-DEC-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 301.83 | 0.00 | 01-JAN-00:40 | 218354.00 | 09-DEC-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 545.64 | 0.00 | 01-JAN-00:20 | 166816.57 | 02-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 545.64 | 0.00 | 01-JAN-00:20 | 166816.57 | 02-AUG-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1351.15 | 0.00 | 01-JAN-00:40 | 311886.38 | 19-JAN-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 359.45 | 0.00 | 01-JAN-00:40 | 311886.38 | 19-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 359.45 | 0.00 | 01-JAN-00:40 | 311886.38 | 19-JAN-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 991.70 | 0.00 | 01-JAN-00:20 | 269526.32 | 07-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 991.70 | 0.00 | 01-JAN-00:20 | 269526.32 | 07-SEP-13:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 905.48 | 0.00 | 01-JAN-00:40 | 219612.71 | 09-DEC-05:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 268.91 | 0.00 | 01-JAN-00:40 | 219612.71 | 09-DEC-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 268.91 | 0.00 | 01-JAN-00:40 | 219612.71 | 09-DEC-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 636.57 | 0.00 | 01-JAN-00:20 | 187316.45 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 636.57 | 0.00 | 01-JAN-00:20 | 187316.45 | 02-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 151.99 | 0.00 | 01-JAN-00:40 | 43135.23 | 09-DEC-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 92.76 | 0.00 | 01-JAN-00:40 | 43135.23 | 09-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 92.76 | 0.00 | 01-JAN-00:40 | 43135.23 | 09-DEC-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 59.23 | 0.00 | 01-JAN-00:20 | 13569.14 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 59.23 | 0.00 | 01-JAN-00:20 | 13569.14 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 109.93 | 0.00 | 01-JAN-00:40 | 27988.71 | 09-DEC-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 54.88 | 0.00 | 01-JAN-00:40 | 27988.71 | 09-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 54.88 | 0.00 | 01-JAN-00:40 | 27988.71 | 09-DEC-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 55.05 | 0.00 | 01-JAN-00:20 | 16640.09 | 26-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 55.05 | 0.00 | 01-JAN-00:20 | 16640.09 | 26-JUN-09:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 165.23 | 0.00 | 01-JAN-00:40 | 42269.05 | 09-DEC-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 69.76 | 0.00 | 01-JAN-00:40 | 42269.05 | 09-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 69.76 | 0.00 | 01-JAN-00:40 | 42269.05 | 09-DEC-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 95.47 | 0.00 | 01-JAN-00:20 | 28182.79 | 07-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 95.47 | 0.00 | 01-JAN-00:20 | 28182.79 | 07-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 107.57 | 0.00 | 01-JAN-00:40 | 27993.10 | 09-DEC-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 47.05 | 0.00 | 01-JAN-00:40 | 27993.10 | 09-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 47.05 | 0.00 | 01-JAN-00:40 | 27993.10 | 09-DEC-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 60.52 | 0.00 | 01-JAN-00:20 | 19675.32 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 60.52 | 0.00 | 01-JAN-00:20 | 19675.32 | 02-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 77.43 | 0.00 | 01-JAN-00:10 | 10098.00 | 04-AUG-15:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 5.53 | 0.00 | 01-JAN-00:10 | 9503.70 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 5.53 | 0.00 | 01-JAN-00:10 | 9503.70 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 71.90 | 0.00 | 01-JAN-00:10 | 10098.00 | 04-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 71.90 | 0.00 | 01-JAN-00:10 | 10098.00 | 04-AUG-15:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 820.44 | 0.00 | 01-JAN-00:40 | 233188.19 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 227.02 | 0.00 | 01-JAN-00:40 | 233188.19 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 227.02 | 0.00 | 01-JAN-00:40 | 233188.19 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 593.43 | 0.00 | 01-JAN-00:10 | 107759.34 | 11-NOV-05:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 593.43 | 0.00 | 01-JAN-00:10 | 107759.34 | 11-NOV-05:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 263.86 | 0.00 | 01-JAN-00:40 | 71051.08 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 168.04 | 0.00 | 01-JAN-00:40 | 71051.08 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 168.04 | 0.00 | 01-JAN-00:40 | 71051.08 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 95.82 | 0.00 | 01-JAN-00:10 | 35257.58 | 30-JUN-13:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 95.82 | 0.00 | 01-JAN-00:10 | 35257.58 | 30-JUN-13:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 128.20 | 3.59 | 01-JAN-02:20 | 8484.50 | 29-AUG-17:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.62 | 0.00 | 01-JAN-01:50 | 1390.59 | 31-JAN-00:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.62 | 0.00 | 01-JAN-01:50 | 1390.59 | 31-JAN-00:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 127.58 | 0.00 | 01-JAN-00:20 | 8484.50 | 29-AUG-17:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 127.58 | 0.00 | 01-JAN-00:20 | 8484.50 | 29-AUG-17:40 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1116.20 | 5.20 | 19-JAN-19:10 | 81274.07 | 29-AUG-17:40 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 18.12 | 0.00 | 02-JAN-13:10 | 13571.40 | 16-JAN-18:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 18.12 | 0.00 | 02-JAN-13:10 | 13571.40 | 16-JAN-18:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1098.08 | 0.00 | 01-JAN-00:10 | 81274.07 | 29-AUG-17:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1098.08 | 0.00 | 01-JAN-00:10 | 81274.07 | 29-AUG-17:40 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 98.92 | 0.22 | 24-JAN-12:50 | 8229.25 | 29-AUG-17:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 2.97 | 0.00 | 02-JAN-12:50 | 1429.23 | 30-JAN-23:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 2.97 | 0.00 | 02-JAN-12:50 | 1429.23 | 30-JAN-23:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 95.95 | 0.00 | 01-JAN-00:10 | 8229.25 | 29-AUG-17:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 95.95 | 0.00 | 01-JAN-00:10 | 8229.25 | 29-AUG-17:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7139.83 | 80390.90 | 30-JAN-06:50 | 389863.52 | 12-APR-14:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 1.64 | 0.00 | 01-JAN-00:10 | 4042.32 | 05-JUN-01:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 1.64 | 0.00 | 01-JAN-00:10 | 4042.32 | 05-JUN-01:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7138.18 | 80390.90 | 30-JAN-06:50 | 389863.52 | 12-APR-14:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7138.18 | 80390.90 | 30-JAN-06:50 | 389863.52 | 12-APR-14:00 |
PlantLoopHeatingDemand:Facility | 5539.79 | 0.00 | 01-JAN-00:40 | 2524409.38 | 30-JAN-07:30 |
PlantLoopHeatingDemand:Plant | 479.24 | 0.00 | 01-JAN-00:10 | 59652.47 | 21-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 479.24 | 0.00 | 01-JAN-00:10 | 59652.47 | 21-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 479.24 | 0.00 | 01-JAN-00:10 | 59652.47 | 21-FEB-12:10 |
EnergyTransfer:HVAC | 15530.18 | 2.97 | 30-JAN-22:10 | 3151635.41 | 04-AUG-15:30 |
HeatingCoils:EnergyTransfer | 5060.55 | 0.00 | 01-JAN-00:40 | 2504667.12 | 30-JAN-07:30 |
PlantLoopHeatingDemand:HVAC | 5060.55 | 0.00 | 01-JAN-00:40 | 2504667.12 | 30-JAN-07:30 |
HeatingCoils:PlantLoopHeatingDemand | 5060.55 | 0.00 | 01-JAN-00:40 | 2504667.12 | 30-JAN-07:30 |
CoolingCoils:EnergyTransfer | 10469.63 | 0.00 | 06-JAN-00:30 | 3151635.41 | 04-AUG-15:30 |
EnergyTransfer:Plant | 34176.41 | 0.00 | 12-JAN-00:10 | 9655492.13 | 04-AUG-15:30 |
LoopToLoop:EnergyTransfer | 8984.32 | 0.00 | 01-JAN-00:20 | 3035264.83 | 04-AUG-15:30 |
WaterSystems:EnergyTransfer | 479.24 | 0.00 | 01-JAN-00:10 | 59652.47 | 21-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 479.24 | 0.00 | 01-JAN-00:10 | 59652.47 | 21-FEB-12:10 |
Boilers:EnergyTransfer | 5032.59 | 0.00 | 01-JAN-00:40 | 2459808.16 | 30-JAN-07:30 |
Chillers:EnergyTransfer | 9067.64 | 0.00 | 01-JAN-00:20 | 3051598.03 | 04-AUG-15:30 |
HeatRejection:EnergyTransfer | 10612.61 | 0.00 | 01-JAN-00:20 | 3533052.13 | 04-AUG-15:30 |
General:HeatRejection:EnergyTransfer | 10612.61 | 0.00 | 01-JAN-00:20 | 3533052.13 | 04-AUG-15:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 1.311 | -650.016 | 0.000 | 0.000 | 96.186 | 333.789 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -205.668 |
CORE_BOTTOM | 0.000 | 0.000 | 0.015 | -582.386 | 0.000 | 0.000 | 84.261 | 299.766 | 289.614 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -91.270 |
CORE_MID | 0.000 | 0.000 | 29.952 | -4593.957 | 0.000 | 0.000 | 864.951 | 2997.664 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -2194.737 |
CORE_TOP | 0.000 | 0.000 | 48.951 | -398.076 | 0.000 | 0.000 | 91.424 | 299.766 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -331.678 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 17.225 | -72.369 | 0.000 | 0.000 | 11.517 | 37.639 | 36.365 | 25.850 | 0.000 | 0.108 | 81.686 | 0.000 | -125.235 | 0.000 | -12.788 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 11.209 | -68.352 | 0.000 | 0.000 | 7.440 | 24.256 | 23.435 | 53.553 | 0.000 | 0.081 | 32.377 | 0.000 | -75.528 | 0.000 | -8.469 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 15.569 | -105.349 | 0.000 | 0.000 | 11.289 | 37.639 | 36.366 | 110.320 | 0.000 | 0.095 | 14.655 | 0.000 | -107.736 | 0.000 | -12.849 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 4.616 | -98.134 | 0.000 | 0.000 | 7.399 | 24.256 | 23.435 | 55.407 | 0.000 | 0.060 | 76.358 | 0.000 | -84.346 | 0.000 | -9.052 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 529.729 | -601.508 | 0.000 | 0.000 | 119.652 | 376.387 | 363.654 | 277.576 | 0.000 | 3.353 | 387.556 | 0.000 | -1181.060 | 0.000 | -275.339 | -0.017 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 301.825 | -545.634 | 0.000 | 0.000 | 55.449 | 242.558 | 234.352 | 532.164 | 0.000 | 1.773 | 88.386 | 0.000 | -723.866 | 0.000 | -187.006 | -0.003 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 359.445 | -991.698 | 0.000 | 0.000 | 115.333 | 376.395 | 363.660 | 1097.180 | 0.000 | 2.333 | 18.421 | 0.000 | -1053.544 | 0.000 | -287.525 | -0.000 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 268.907 | -636.571 | 0.000 | 0.000 | 76.587 | 242.558 | 234.351 | 566.868 | 0.000 | 1.572 | 209.861 | 0.000 | -773.776 | 0.000 | -190.355 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 92.763 | -59.232 | 0.000 | 0.000 | 12.157 | 37.639 | 36.365 | 28.704 | 0.000 | 0.454 | 0.000 | 0.000 | -112.828 | 0.000 | -32.948 | -3.073 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 54.881 | -55.045 | 0.000 | 0.000 | 7.648 | 24.256 | 23.435 | 54.177 | 0.000 | 0.226 | 0.000 | 0.000 | -69.168 | 0.000 | -22.339 | -18.070 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 69.755 | -95.472 | 0.000 | 0.000 | 11.788 | 37.639 | 36.366 | 110.958 | 0.000 | 0.316 | 0.000 | 0.000 | -99.696 | 0.000 | -34.113 | -37.541 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 47.055 | -60.516 | 0.000 | 0.000 | 7.722 | 24.256 | 23.435 | 56.755 | 0.000 | 0.192 | 0.000 | 0.000 | -74.370 | 0.000 | -22.884 | -1.645 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.617 | -127.581 | 0.000 | 0.000 | 0.941 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -36.204 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 18.115 | -1098.081 | 0.000 | 0.000 | 9.437 | 83.466 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -551.743 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 2.970 | -95.948 | 0.000 | 0.000 | 0.948 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -70.197 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 1.641 | -7138.003 | 0.000 | 0.000 | 22.796 | 94.114 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -475.405 |
GROUNDFLOOR_PLENUM | 5.532 | -71.901 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.171 | 94.588 | 0.000 | 0.000 | 0.000 | -28.390 | 0.000 |
MIDFLOOR_PLENUM | 227.016 | -593.424 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.518 | 842.419 | 0.000 | 0.000 | 0.000 | -479.529 | -0.009 |
TOPFLOOR_PLENUM | 168.039 | -95.817 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.217 | 0.000 | 0.000 | 0.000 | 0.000 | -48.652 | -23.786 |
Total Facility | 400.587 | -761.142 | 1876.551 | -18073.928 | 0.000 | 0.000 | 1614.923 | 5610.736 | 14676.396 | 2969.512 | 0.000 | 14.468 | 1846.308 | 0.000 | -4481.154 | 0.000 | -1652.241 | -4041.049 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 23-OCT-03:01 | 0.00 | 0.00 | 0.00 | -137632.77 | 0.00 | 0.00 | 0.00 | 1619.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 122556.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 15-AUG-04:11 | 0.00 | 0.00 | 0.00 | -117377.90 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.65 | 0.00 | 0.00 | 0.00 | 108532.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 29-JUN-04:11 | 0.00 | 0.00 | 0.00 | -1075687.10 | 0.00 | 0.00 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 987228.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 03-AUG-04:01 | 0.00 | 0.00 | 0.00 | -129386.33 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.62 | 0.00 | 0.00 | 0.00 | 120540.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 25-JUN-18:31 | 0.00 | 0.00 | 0.00 | -19430.23 | 0.00 | 0.00 | 0.00 | 182.58 | 559.17 | 7387.65 | 0.00 | 180.65 | 11120.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 02-JUL-08:41 | 0.00 | 0.00 | 0.00 | -33122.56 | 0.00 | 0.00 | 18.36 | 117.66 | 464.11 | 20374.18 | 0.00 | 0.00 | 12248.04 | 0.00 | -0.00 | 0.00 | -99.80 | 0.00 |
PERIMETER_BOT_ZN_1 | 29-OCT-13:21 | 0.00 | 0.00 | 0.00 | -35981.78 | 0.00 | 0.00 | 35.82 | 182.58 | 720.19 | 28730.03 | 0.00 | 0.00 | 7417.36 | 0.00 | -0.00 | 0.00 | -1104.20 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JUL-16:41 | 0.00 | 0.00 | 0.00 | -43243.12 | 0.00 | 0.00 | 13.15 | 117.66 | 464.11 | 21173.10 | 0.00 | 0.00 | 21511.34 | 0.00 | -0.00 | 0.00 | -36.23 | 0.00 |
PERIMETER_MID_ZN_3 | 26-JUN-14:30 | 0.00 | 0.00 | 0.00 | -118499.07 | 0.00 | 0.00 | 11143.82 | 32864.16 | 21605.52 | 86401.05 | 0.00 | 1491.13 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -35006.61 |
PERIMETER_MID_ZN_2 | 30-JUL-09:21 | 0.00 | 0.00 | 0.00 | -341983.15 | 0.00 | 0.00 | 187.09 | 1176.61 | 4641.14 | 176159.60 | 0.00 | 0.00 | 161482.54 | 0.00 | -0.00 | 0.00 | -1663.82 | 0.00 |
PERIMETER_MID_ZN_1 | 01-OCT-13:41 | 0.00 | 0.00 | 0.00 | -456686.07 | 0.00 | 0.00 | 318.72 | 1825.83 | 7201.95 | 276167.83 | 0.00 | 0.00 | 183832.36 | 0.00 | -0.00 | 0.00 | -12660.61 | 0.00 |
PERIMETER_MID_ZN_4 | 14-MAY-17:01 | 0.00 | 0.00 | 0.00 | -370229.66 | 0.00 | 0.00 | 0.00 | 1176.61 | 3603.49 | 193229.23 | 0.00 | 0.00 | 174658.18 | 0.00 | -0.00 | 0.00 | -2437.83 | 0.00 |
PERIMETER_TOP_ZN_3 | 25-JUN-17:41 | 0.00 | 0.00 | 0.00 | -15667.15 | 0.00 | 0.00 | 0.00 | 182.58 | 559.17 | 7188.22 | 0.00 | 854.67 | 6882.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 25-JUN-08:21 | 0.00 | 0.00 | 0.00 | -38717.30 | 0.00 | 0.00 | 19.19 | 117.66 | 464.11 | 20832.77 | 0.00 | 0.00 | 17669.19 | 0.00 | -0.00 | 0.00 | -385.63 | 0.00 |
PERIMETER_TOP_ZN_1 | 17-SEP-13:31 | 0.00 | 0.00 | 0.00 | -57709.87 | 0.00 | 0.00 | 30.76 | 182.58 | 720.19 | 23815.72 | 0.00 | 0.00 | 33336.27 | 0.00 | -0.00 | 0.00 | -375.67 | 0.00 |
PERIMETER_TOP_ZN_4 | 25-JUN-17:01 | 0.00 | 0.00 | 0.00 | -44605.34 | 0.00 | 0.00 | 0.00 | 117.66 | 360.35 | 21311.39 | 0.00 | 116.03 | 22699.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 04-FEB-10:31 | 0.00 | 0.00 | 0.00 | -10396.54 | 0.00 | 0.00 | 14.32 | 242.93 | 3897.21 | 0.00 | 0.00 | 0.00 | 6242.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 04-FEB-10:31 | 0.00 | 0.00 | 0.00 | -99824.88 | 0.00 | 0.00 | 185.52 | 2429.28 | 38972.11 | 0.00 | 0.00 | 0.00 | 58237.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 26-NOV-08:11 | 0.00 | 0.00 | 0.00 | -9246.38 | 0.00 | 0.00 | 3.16 | 40.49 | 5845.82 | 0.00 | 0.00 | 0.00 | 3356.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 24-MAR-15:52 | 0.00 | 0.00 | 0.00 | -521569.93 | 0.00 | 0.00 | 2733.21 | 8217.58 | 284724.39 | 0.00 | 0.00 | 0.00 | 225894.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 06-JAN-04:11 | 0.00 | -19776.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22587.00 | 0.00 | -0.00 | 0.00 | -2810.51 | 0.00 |
MIDFLOOR_PLENUM | 09-DEC-02:12 | 0.00 | -267151.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441353.67 | 0.00 | -0.00 | 0.00 | -174201.67 | 0.00 |
TOPFLOOR_PLENUM | 30-JUN-13:50 | 0.00 | -35256.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.78 | 35187.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-JUL-05:01 | 0.00 | 23075.58 | 0.00 | -2177088.91 | 0.00 | 0.00 | 16533.22 | 54433.43 | 497997.76 | 16673.32 | 0.00 | 0.00 | 1626080.81 | 0.00 | -48790.04 | 0.00 | -8915.16 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 03-FEB-07:08 | 0.00 | 0.00 | 92597.73 | 0.00 | 0.00 | 0.00 | 2208.58 | 9714.93 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -117978.78 |
CORE_BOTTOM | 06-FEB-06:01 | 0.00 | 0.00 | 23948.39 | 0.00 | 0.00 | 0.00 | 1161.27 | 2908.23 | 7647.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -35665.28 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 695322.54 | 0.00 | 0.00 | 0.00 | 0.00 | 14541.15 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -769239.92 |
CORE_TOP | 30-JAN-03:21 | 0.00 | 0.00 | 134329.20 | 0.00 | 0.00 | 0.00 | 0.00 | 1454.11 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -141720.94 |
PERIMETER_BOT_ZN_3 | 02-FEB-04:11 | 0.00 | 0.00 | 27298.27 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -14951.66 | 0.00 | -2202.11 | -11072.64 |
PERIMETER_BOT_ZN_2 | 02-FEB-04:11 | 0.00 | 0.00 | 23520.65 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9581.74 | 0.00 | -1472.71 | -13064.34 |
PERIMETER_BOT_ZN_1 | 02-FEB-04:11 | 0.00 | 0.00 | 30318.86 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -14385.48 | 0.00 | -2207.07 | -14654.47 |
PERIMETER_BOT_ZN_4 | 02-FEB-04:11 | 0.00 | 0.00 | 22875.88 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10303.78 | 0.00 | -1524.25 | -11645.98 |
PERIMETER_MID_ZN_3 | 09-DEC-02:11 | 0.00 | 0.00 | 423704.60 | 0.00 | 0.00 | 0.00 | 0.00 | 1825.79 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -115113.95 | 0.00 | -93654.50 | -222353.64 |
PERIMETER_MID_ZN_2 | 09-DEC-02:11 | 0.00 | 0.00 | 304282.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.61 | 3603.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -72260.38 | 0.00 | -62901.49 | -173900.57 |
PERIMETER_MID_ZN_1 | 09-DEC-02:11 | 0.00 | 0.00 | 407781.31 | 0.00 | 0.00 | 0.00 | 0.00 | 1825.83 | 5591.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -109212.05 | 0.00 | -94865.50 | -211121.39 |
PERIMETER_MID_ZN_4 | 09-DEC-02:11 | 0.00 | 0.00 | 319705.24 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -77411.02 | 0.00 | -63459.95 | -183614.36 |
PERIMETER_TOP_ZN_3 | 09-DEC-02:61 | 0.00 | 0.00 | 56190.33 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 | 559.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11186.74 | 0.00 | -12213.69 | -33531.65 |
PERIMETER_TOP_ZN_2 | 09-DEC-02:61 | 0.00 | 0.00 | 36444.86 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6999.37 | 0.00 | -8135.43 | -21788.07 |
PERIMETER_TOP_ZN_1 | 09-DEC-02:61 | 0.00 | 0.00 | 55003.51 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 | 559.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10532.15 | 0.00 | -12245.88 | -32967.24 |
PERIMETER_TOP_ZN_4 | 09-DEC-02:61 | 0.00 | 0.00 | 36636.07 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7540.52 | 0.00 | -8191.33 | -21382.22 |
DATACENTER_BOT_ZN_6 | 26-NOV-03:02 | 0.00 | 0.00 | 1673.39 | 0.00 | 0.00 | 0.00 | 0.00 | 40.49 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7559.69 |
DATACENTER_MID_ZN_6 | 26-NOV-03:02 | 0.00 | 0.00 | 14576.39 | 0.00 | 0.00 | 0.00 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -73439.43 |
DATACENTER_TOP_ZN_6 | 29-JAN-17:21 | 0.00 | 0.00 | 1446.71 | 0.00 | 0.00 | 0.00 | 6.23 | 40.49 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3442.04 |
DATACENTER_BASEMENT_ZN_6 | 05-JUN-01:01 | 0.00 | 0.00 | 39816.80 | 0.00 | 0.00 | 0.00 | 0.00 | 456.53 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -230089.59 |
GROUNDFLOOR_PLENUM | 16-APR-15:31 | 14387.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.87 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14936.21 |
MIDFLOOR_PLENUM | 02-JAN-06:12 | 266296.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -11019.71 | -255276.50 |
TOPFLOOR_PLENUM | 02-FEB-05:31 | 77369.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -6416.40 | -70953.59 |
Total Facility | 11-DEC-05:21 | -415139.41 | 521003.64 | 2267868.41 | -521003.64 | 0.00 | 0.00 | 0.00 | 54433.43 | 587299.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -446133.91 | 0.00 | -169264.46 | -1879063.47 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 15.4433 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 12.6044 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 161.8069 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 118.3604 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 20.1325 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 14.5977 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 7.2422 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 7.2422 | 0.1657 | 1.0000 | Not calculated | 1.2002 | 0.1657 | ||
AIRLOOP DATACENTER BASEMENT | 32.8526 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 32.8528 | 0.0103 | 1.0000 | Not calculated | 0.3384 | 0.0103 | ||
AIRLOOP DATACENTER BOT | 0.7908 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7908 | 0.0198 | 1.0000 | Not calculated | 0.0156 | 0.0198 | ||
AIRLOOP DATACENTER MID | 7.6086 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 7.6086 | 0.0205 | 1.0000 | Not calculated | 0.1563 | 0.0205 | ||
AIRLOOP DATACENTER TOP | 0.7833 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7833 | 0.0200 | 1.0000 | Not calculated | 0.0156 | 0.0200 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 7.7217 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6330 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 80.9035 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 48.5421 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.0662 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.0397 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 2.1727 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 2.1727 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.5524 | ||
AIRLOOP DATACENTER BASEMENT | 16.4263 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 16.4263 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0206 | ||
AIRLOOP DATACENTER BOT | 0.7908 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7908 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0198 | ||
AIRLOOP DATACENTER MID | 7.6086 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 7.6086 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0205 | ||
AIRLOOP DATACENTER TOP | 0.7833 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7833 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0200 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 7.2422 | 7.2422 | 2.1727 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.7185 | 7.7185 | 2.3155 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 73.3160 | 73.3160 | 21.9948 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.3200 | 9.3200 | 2.7960 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8226 | 1.8226 | 0.5468 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7437 | 1.7437 | 0.5231 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0332 | 2.0332 | 0.6100 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1254 | 2.1254 | 0.6376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 25.4164 | 25.4164 | 7.6249 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.4060 | 18.4060 | 5.5218 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 24.8373 | 24.8373 | 7.4512 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 19.8312 | 19.8312 | 5.9494 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2902 | 3.2902 | 0.9871 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1320 | 2.1320 | 0.6396 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2303 | 3.2303 | 0.9691 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1599 | 2.1599 | 0.6480 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7908 | 0.7908 | 0.7908 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.6086 | 7.6086 | 7.6086 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7833 | 0.7833 | 0.7833 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 32.8526 | 32.8526 | 16.4263 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 15.4433 | 12.6044 | 15.4433 | 4.6330 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 161.8069 | 118.3604 | 161.8069 | 48.5421 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 20.1325 | 14.5977 | 20.1325 | 6.0397 | 0.0000 | 1.0000 |
CAV_BAS | 7.2422 | 7.2422 | 7.2422 | 2.1727 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 32.8526 | 32.8528 | 32.8526 | 16.4263 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.7908 | 0.7908 | 0.7908 | 0.7908 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 7.6086 | 7.6086 | 7.6086 | 7.6086 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.7833 | 0.7833 | 0.7833 | 0.7833 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 2.1727 | 2.1727 | 2.1727 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.8592 | 3.8592 | 2.3155 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 36.6580 | 36.6580 | 21.9948 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.6600 | 4.6600 | 2.7960 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9113 | 0.9113 | 0.5468 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8718 | 0.8718 | 0.5231 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0166 | 1.0166 | 0.6100 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0627 | 1.0627 | 0.6376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.7082 | 12.7082 | 7.6249 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.2030 | 9.2030 | 5.5218 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.4186 | 12.4186 | 7.4512 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.9156 | 9.9156 | 5.9494 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6451 | 1.6451 | 0.9871 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0660 | 1.0660 | 0.6396 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6152 | 1.6152 | 0.9691 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0800 | 1.0800 | 0.6480 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7908 | 0.7908 | 0.7908 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.6086 | 7.6086 | 7.6086 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7833 | 0.7833 | 0.7833 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 16.4263 | 16.4263 | 16.4263 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 7.7217 | 4.6330 | 4.6330 | 4.6330 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 80.9035 | 48.5421 | 48.5421 | 48.5421 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.0662 | 6.0397 | 6.0397 | 6.0397 | 0.0000 | 1.0000 |
CAV_BAS | 2.1727 | 2.1727 | 2.1727 | 2.1727 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 16.4263 | 16.4263 | 16.4263 | 16.4263 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.7908 | 0.7908 | 0.7908 | 0.7908 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 7.6086 | 7.6086 | 7.6086 | 7.6086 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.7833 | 0.7833 | 0.7833 | 0.7833 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 118.33 |
Number of hours cooling loads not met | 173.17 |
Number of hours not met | 286.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 7173.53 | 3142160.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1965.43 | 515044.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 5610.74 | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 1006.00 | 64082.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 56.04 | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.31 | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2912.16 | 305773.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 1008.31 | 102278.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 176.75 | 58522.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1053.07 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 484.77 | 60480.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 31516.73 |
Natural Gas | 0.00 | 7173.53 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 38690.25 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 121.13 |
Space Heating | 0.00 |
Space Cooling | 42.43 |
Fans (All) | 62.87 |
Service Water Heating | 10.47 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 680.41 |
Subtotal | 680.41 |
Natural Gas [MJ/m2] | |
Space Heating | 154.87 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 154.87 |
Subtotal | 154.87 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.50 |
Space Heating | 18.54 |
Space Cooling | 5.08 |
Fans (All) | 7.53 |
Service Water Heating | 1.25 |
Receptacle Equipment | 37.93 |
Miscellaneous | 15.16 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
LTG_SCH_DATACENTER | 2939. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8568.17 | 191.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8739.67 | 20.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8726.17 | 33.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8729.83 | 30.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8378.00 | 382.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8719.50 | 40.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8736.67 | 23.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8685.17 | 74.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8729.33 | 30.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8745.00 | 15.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8690.83 | 69.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6028.00 | 2725.00 | 7.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6034.50 | 2724.50 | 1.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6024.67 | 2735.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6742.67 | 2017.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8705.33 | 54.67 | 0.00 | 0.00 | 0.00 |
Min | 6024.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2735.33 | 7.00 | 0.00 | 0.00 |
Average | 8274.07 | 485.59 | 0.35 | 0.00 | 0.00 |
Sum | 190303.50 | 11168.50 | 8.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368126.00 | 490.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330811.00 | 2.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1371.67 | 893.50 | 2.83 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1376.67 | 890.83 | 0.50 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1371.50 | 896.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 74629.50 | 28765.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368126.00 | 28765.50 | 2.83 | 0.00 | 0.00 |
Average | 78946.14 | 1388.62 | 0.14 | 0.00 | 0.00 |
Sum | 1815761.33 | 31938.33 | 3.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8217.83 | 542.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8087.83 | 672.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8249.50 | 510.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8500.00 | 260.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8432.67 | 327.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8556.67 | 203.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8444.67 | 315.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8033.17 | 726.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8563.83 | 196.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8468.50 | 291.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8464.83 | 295.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8286.00 | 474.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8578.67 | 181.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8491.00 | 269.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8510.50 | 249.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8343.83 | 416.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7763.83 | 996.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7756.67 | 1003.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7748.50 | 1011.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6689.00 | 2071.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8146.83 | 613.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8486.50 | 273.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8015.33 | 744.67 | 0.00 | 0.00 | 0.00 |
Min | 6689.00 | 181.33 | 0.00 | 0.00 | 0.00 |
Max | 8578.67 | 2071.00 | 0.00 | 0.00 | 0.00 |
Average | 8210.27 | 549.73 | 0.00 | 0.00 | 0.00 |
Sum | 188836.17 | 12643.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 367099.17 | 1516.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 329937.00 | 876.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330069.00 | 744.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330453.00 | 360.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1669.50 | 598.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1658.50 | 609.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1656.00 | 612.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 74980.00 | 28415.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367099.17 | 28415.00 | 0.00 | 0.00 | 0.00 |
Average | 78868.31 | 1466.60 | 0.00 | 0.00 | 0.00 |
Sum | 1813971.17 | 33731.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:25
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.532822E+11 | 124702.25 | 14-JAN-06:01 | -3.4 | -4.1 | 0.453413E+10 | 7368.72 | 13-JAN-14:09 | -3.4 | -4.1 |
February | 0.423157E+11 | 123244.69 | 24-FEB-06:01 | 0.40 | -1.6 | 0.445969E+10 | 7499.22 | 24-FEB-10:09 | 4.60 | 1.53 |
March | 0.465823E+11 | 120310.84 | 25-MAR-05:01 | -1.5 | -2.5 | 0.571312E+10 | 7498.89 | 31-MAR-09:50 | 3.72 | 1.12 |
April | 0.418739E+11 | 113138.40 | 19-APR-13:24 | 10.60 | 7.03 | 0.523468E+10 | 7499.23 | 10-APR-09:30 | 10.60 | 7.03 |
May | 0.471684E+11 | 125089.30 | 18-MAY-05:02 | 5.28 | 4.19 | 0.574943E+10 | 7499.36 | 30-MAY-13:09 | 26.70 | 19.86 |
June | 0.559556E+11 | 133453.03 | 19-JUN-04:11 | 12.03 | 10.64 | 0.584082E+10 | 7499.32 | 22-JUN-09:50 | 17.52 | 12.29 |
July | 0.598227E+11 | 121305.34 | 24-JUL-04:11 | 10.00 | 9.40 | 0.546742E+10 | 7499.33 | 11-JUL-09:20 | 10.00 | 9.40 |
August | 0.704961E+11 | 122927.14 | 07-AUG-04:12 | 8.50 | 7.60 | 0.612966E+10 | 7499.39 | 16-AUG-13:09 | 22.88 | 15.15 |
September | 0.628687E+11 | 133566.64 | 27-SEP-04:11 | 5.93 | 5.19 | 0.535052E+10 | 7499.34 | 13-SEP-09:50 | 5.93 | 5.19 |
October | 0.601119E+11 | 137659.95 | 23-OCT-03:01 | -1.2 | -2.2 | 0.557035E+10 | 7499.34 | 02-OCT-13:50 | -1.2 | -2.2 |
November | 0.560387E+11 | 135351.93 | 01-NOV-04:11 | 5.00 | 4.07 | 0.542066E+10 | 7499.24 | 08-NOV-14:09 | 13.90 | 12.22 |
December | 0.535050E+11 | 112070.72 | 04-DEC-05:01 | -9.6 | -9.9 | 0.503058E+10 | 7485.88 | 19-DEC-14:09 | -1.7 | -3.4 |
Annual Sum or Average | 0.650021E+12 | 0.645011E+11 | ||||||||
Minimum of Months | 0.418739E+11 | 112070.72 | -9.6 | -9.9 | 0.445969E+10 | 7368.72 | -3.4 | -4.1 | ||
Maximum of Months | 0.704961E+11 | 137659.95 | 12.03 | 10.64 | 0.612966E+10 | 7499.39 | 26.70 | 19.86 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.320379E+11 | 35261.86 | 13-JAN-16:55 | 2.20 | 0.77 | 0.474266E+10 | 6734.80 | 12-JAN-10:30 | 2.20 | 0.77 |
February | 0.310777E+11 | 97582.52 | 25-FEB-06:01 | 0.00 | -0.6 | 0.440247E+10 | 6734.90 | 22-FEB-10:09 | 0.00 | -0.6 |
March | 0.420149E+11 | 106365.89 | 30-MAR-05:01 | 1.10 | 0.61 | 0.542843E+10 | 6734.89 | 28-MAR-13:09 | 1.10 | 0.61 |
April | 0.470455E+11 | 112600.27 | 17-APR-04:11 | 12.43 | 10.73 | 0.485241E+10 | 6734.91 | 11-APR-13:09 | 12.43 | 10.73 |
May | 0.519316E+11 | 111408.00 | 30-MAY-04:12 | 14.40 | 14.40 | 0.526906E+10 | 6734.94 | 09-MAY-09:09 | 14.40 | 14.40 |
June | 0.594040E+11 | 115990.49 | 28-JUN-04:11 | 17.60 | 16.08 | 0.526704E+10 | 6734.90 | 15-JUN-09:20 | 17.60 | 16.08 |
July | 0.658032E+11 | 116389.55 | 19-JUL-04:11 | 11.87 | 11.14 | 0.489535E+10 | 6734.88 | 11-JUL-13:00 | 11.87 | 11.14 |
August | 0.718855E+11 | 117402.96 | 15-AUG-04:11 | 15.40 | 14.38 | 0.549933E+10 | 6735.25 | 08-AUG-09:09 | 15.40 | 14.38 |
September | 0.534742E+11 | 115726.76 | 01-SEP-04:11 | 13.30 | 11.05 | 0.487448E+10 | 6734.89 | 21-SEP-13:09 | 12.80 | 11.83 |
October | 0.467935E+11 | 109575.37 | 11-OCT-04:11 | 10.87 | 9.98 | 0.505896E+10 | 6734.90 | 20-OCT-09:09 | 12.70 | 8.99 |
November | 0.427289E+11 | 109538.13 | 08-NOV-05:11 | 12.20 | 11.27 | 0.497358E+10 | 6734.91 | 01-NOV-09:20 | 12.20 | 11.27 |
December | 0.381893E+11 | 42223.81 | 05-DEC-16:15 | -5.2 | -8.3 | 0.478416E+10 | 6734.88 | 18-DEC-10:09 | -2.3 | -3.2 |
Annual Sum or Average | 0.582386E+12 | 0.600479E+11 | ||||||||
Minimum of Months | 0.310777E+11 | 35261.86 | -5.2 | -8.3 | 0.440247E+10 | 6734.80 | -2.3 | -3.2 | ||
Maximum of Months | 0.718855E+11 | 117402.96 | 17.60 | 16.08 | 0.549933E+10 | 6735.25 | 17.60 | 16.08 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.277499E+11 | 28456.77 | 13-JAN-16:55 | 2.20 | 0.77 | 0.425903E+10 | 6734.68 | 13-JAN-14:20 | 2.20 | 0.77 |
February | 0.268889E+11 | 29143.87 | 24-FEB-16:52 | 7.20 | 5.13 | 0.405939E+10 | 6734.89 | 24-FEB-14:20 | 7.20 | 5.13 |
March | 0.337370E+11 | 89702.57 | 24-MAR-05:01 | 7.12 | 4.33 | 0.518108E+10 | 6734.89 | 23-MAR-13:30 | 7.12 | 4.33 |
April | 0.359467E+11 | 98619.05 | 17-APR-05:01 | 11.42 | 9.68 | 0.473406E+10 | 6734.91 | 07-APR-09:20 | 11.42 | 9.68 |
May | 0.440838E+11 | 102298.75 | 13-MAY-05:01 | 13.22 | 12.93 | 0.523995E+10 | 6734.92 | 09-MAY-09:09 | 13.22 | 12.93 |
June | 0.501474E+11 | 107596.43 | 29-JUN-04:11 | 17.60 | 16.30 | 0.524994E+10 | 6734.90 | 15-JUN-09:20 | 17.60 | 16.30 |
July | 0.504905E+11 | 105790.21 | 01-JUL-04:11 | 15.20 | 13.63 | 0.488231E+10 | 6734.88 | 11-JUL-13:00 | 17.80 | 16.71 |
August | 0.528691E+11 | 102745.07 | 11-AUG-04:11 | 13.50 | 12.44 | 0.548228E+10 | 6735.18 | 08-AUG-09:09 | 13.50 | 12.44 |
September | 0.432799E+11 | 103697.97 | 08-SEP-04:11 | 17.40 | 14.82 | 0.484221E+10 | 6734.89 | 21-SEP-13:09 | 12.80 | 11.83 |
October | 0.345954E+11 | 94961.42 | 21-OCT-05:01 | 10.33 | 8.13 | 0.496345E+10 | 6734.91 | 20-OCT-09:30 | 10.33 | 8.13 |
November | 0.309327E+11 | 94464.67 | 09-NOV-06:01 | 14.82 | 12.81 | 0.464205E+10 | 6734.91 | 01-NOV-09:20 | 14.82 | 12.81 |
December | 0.286754E+11 | 25689.96 | 07-DEC-16:53 | -7.2 | -9.8 | 0.427767E+10 | 6734.80 | 07-DEC-14:20 | -7.2 | -9.8 |
Annual Sum or Average | 0.459397E+12 | 0.578134E+11 | ||||||||
Minimum of Months | 0.268889E+11 | 25689.96 | -7.2 | -9.8 | 0.405939E+10 | 6734.68 | -7.2 | -9.8 | ||
Maximum of Months | 0.528691E+11 | 107596.43 | 17.60 | 16.30 | 0.548228E+10 | 6735.18 | 17.80 | 16.71 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143185E+11 | 23505.48 | 13-JAN-17:00 | 2.20 | 0.77 | 0.379128E+10 | 5916.58 | 13-JAN-14:00 | 2.20 | 0.77 |
February | 0.171362E+11 | 25549.76 | 24-FEB-17:00 | 7.20 | 5.13 | 0.353684E+10 | 6181.32 | 24-FEB-14:00 | 7.20 | 5.13 |
March | 0.266649E+11 | 32688.99 | 24-MAR-15:53 | 10.60 | 5.50 | 0.447715E+10 | 6734.85 | 24-MAR-13:00 | 10.60 | 5.50 |
April | 0.312694E+11 | 53703.53 | 18-APR-15:50 | 25.55 | 19.61 | 0.425348E+10 | 6734.83 | 19-APR-13:00 | 10.60 | 7.03 |
May | 0.426577E+11 | 91174.43 | 31-MAY-05:02 | 16.38 | 14.96 | 0.498150E+10 | 6734.86 | 05-MAY-09:20 | 16.38 | 14.96 |
June | 0.524491E+11 | 129304.36 | 14-JUN-05:01 | 17.80 | 17.37 | 0.512584E+10 | 6734.90 | 15-JUN-09:20 | 15.97 | 13.78 |
July | 0.535778E+11 | 122374.22 | 28-JUL-05:01 | 17.80 | 16.77 | 0.481289E+10 | 6734.88 | 11-JUL-13:00 | 17.80 | 16.77 |
August | 0.540510E+11 | 129417.28 | 03-AUG-04:01 | 23.80 | 22.62 | 0.538360E+10 | 6734.80 | 23-AUG-09:20 | 19.60 | 18.34 |
September | 0.391631E+11 | 121041.59 | 12-SEP-05:02 | 16.02 | 15.69 | 0.453359E+10 | 6734.82 | 12-SEP-13:20 | 21.67 | 16.01 |
October | 0.274293E+11 | 36144.59 | 20-OCT-16:00 | 21.30 | 12.72 | 0.428994E+10 | 6734.72 | 20-OCT-13:00 | 21.30 | 12.72 |
November | 0.224083E+11 | 32269.58 | 03-NOV-15:53 | 15.00 | 9.33 | 0.400832E+10 | 6706.95 | 03-NOV-13:00 | 15.00 | 9.33 |
December | 0.169528E+11 | 23143.19 | 01-DEC-16:30 | -2.8 | -4.8 | 0.368980E+10 | 5872.22 | 01-DEC-14:00 | -2.8 | -4.8 |
Annual Sum or Average | 0.398078E+12 | 0.528842E+11 | ||||||||
Minimum of Months | 0.143185E+11 | 23143.19 | -2.8 | -4.8 | 0.353684E+10 | 5872.22 | -2.8 | -4.8 | ||
Maximum of Months | 0.540510E+11 | 129417.28 | 25.55 | 22.62 | 0.538360E+10 | 6734.90 | 21.67 | 18.34 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303710E+09 | 3826.02 | 13-JAN-14:20 | 3.90 | 1.72 | 0.465574E+09 | 667.98 | 13-JAN-14:30 | 3.90 | 1.72 |
February | 0.116796E+10 | 4241.87 | 24-FEB-15:30 | 8.30 | 5.75 | 0.425618E+09 | 712.38 | 24-FEB-14:00 | 8.30 | 5.75 |
March | 0.359650E+10 | 6411.26 | 19-MAR-13:21 | 17.50 | 13.24 | 0.543366E+09 | 828.03 | 28-MAR-13:00 | 16.70 | 10.30 |
April | 0.591878E+10 | 10964.84 | 18-APR-15:00 | 28.30 | 20.65 | 0.525164E+09 | 845.63 | 13-APR-13:09 | 28.30 | 20.65 |
May | 0.842678E+10 | 10904.01 | 31-MAY-14:50 | 29.90 | 19.65 | 0.628338E+09 | 845.64 | 08-MAY-13:00 | 29.90 | 19.65 |
June | 0.108262E+11 | 19433.48 | 25-JUN-18:31 | 29.97 | 21.56 | 0.648573E+09 | 845.64 | 15-JUN-09:20 | 29.97 | 21.56 |
July | 0.120444E+11 | 12187.37 | 03-JUL-13:40 | 29.23 | 24.20 | 0.610199E+09 | 845.64 | 18-JUL-09:30 | 21.40 | 14.62 |
August | 0.122517E+11 | 12610.50 | 04-AUG-15:20 | 33.90 | 25.66 | 0.682257E+09 | 845.68 | 08-AUG-09:09 | 20.28 | 15.58 |
September | 0.803471E+10 | 14441.78 | 11-SEP-04:11 | 20.40 | 17.35 | 0.573440E+09 | 845.63 | 18-SEP-09:20 | 21.30 | 16.23 |
October | 0.545892E+10 | 6453.39 | 01-OCT-14:51 | 19.40 | 12.33 | 0.546365E+09 | 845.63 | 02-OCT-13:09 | 16.65 | 14.10 |
November | 0.339793E+10 | 6335.99 | 09-NOV-06:02 | 14.82 | 12.81 | 0.503077E+09 | 820.94 | 07-NOV-14:20 | 14.82 | 12.81 |
December | 0.941590E+09 | 3577.10 | 01-DEC-06:03 | -2.3 | -3.2 | 0.450104E+09 | 631.37 | 01-DEC-14:00 | -1.1 | -3.6 |
Annual Sum or Average | 0.723692E+11 | 0.660207E+10 | ||||||||
Minimum of Months | 0.303710E+09 | 3577.10 | -2.3 | -3.2 | 0.425618E+09 | 631.37 | -1.1 | -3.6 | ||
Maximum of Months | 0.122517E+11 | 19433.48 | 33.90 | 25.66 | 0.682257E+09 | 845.68 | 29.97 | 21.56 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.466717E+09 | 3999.50 | 12-JAN-10:13 | -1.9 | -2.6 | 0.300426E+09 | 456.57 | 12-JAN-10:20 | -1.9 | -2.6 |
February | 0.131464E+10 | 6236.30 | 24-FEB-09:31 | 3.87 | 1.06 | 0.278128E+09 | 544.96 | 24-FEB-10:50 | 5.40 | 2.22 |
March | 0.350182E+10 | 9382.68 | 28-MAR-09:03 | 7.67 | 4.71 | 0.359059E+09 | 544.96 | 17-MAR-09:39 | 7.67 | 4.71 |
April | 0.558910E+10 | 26246.06 | 30-APR-08:32 | 9.43 | 4.96 | 0.335991E+09 | 544.96 | 13-APR-09:09 | 9.43 | 4.96 |
May | 0.837043E+10 | 28737.87 | 29-MAY-09:01 | 22.48 | 18.29 | 0.403853E+09 | 544.98 | 05-MAY-09:09 | 22.48 | 18.29 |
June | 0.104306E+11 | 32153.56 | 25-JUN-07:51 | 23.90 | 20.49 | 0.411799E+09 | 544.96 | 01-JUN-09:39 | 23.90 | 20.49 |
July | 0.113789E+11 | 33138.61 | 02-JUL-08:41 | 25.32 | 20.92 | 0.389092E+09 | 544.99 | 18-JUL-09:30 | 21.40 | 14.62 |
August | 0.109423E+11 | 30598.39 | 27-AUG-09:11 | 23.33 | 19.50 | 0.435701E+09 | 545.02 | 08-AUG-09:09 | 23.33 | 19.50 |
September | 0.795389E+10 | 21256.85 | 04-SEP-08:52 | 16.10 | 13.09 | 0.369221E+09 | 544.97 | 05-SEP-09:30 | 21.95 | 14.90 |
October | 0.488035E+10 | 10541.53 | 01-OCT-08:48 | 12.78 | 9.88 | 0.350095E+09 | 544.96 | 20-OCT-09:09 | 12.70 | 8.99 |
November | 0.267795E+10 | 5650.48 | 09-NOV-05:11 | 15.00 | 13.04 | 0.312320E+09 | 498.65 | 03-NOV-10:39 | 15.00 | 13.04 |
December | 0.845592E+09 | 4242.75 | 05-DEC-09:40 | -6.3 | -8.4 | 0.291391E+09 | 473.04 | 05-DEC-10:09 | -5.9 | -8.1 |
Annual Sum or Average | 0.683523E+11 | 0.423708E+10 | ||||||||
Minimum of Months | 0.466717E+09 | 3999.50 | -6.3 | -8.4 | 0.278128E+09 | 456.57 | -5.9 | -8.1 | ||
Maximum of Months | 0.113789E+11 | 33138.61 | 25.32 | 20.92 | 0.435701E+09 | 545.02 | 23.90 | 20.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280413E+10 | 15112.47 | 12-JAN-12:30 | 1.95 | 0.38 | 0.511497E+09 | 845.65 | 30-JAN-14:20 | -24.2 | -24.6 |
February | 0.370104E+10 | 19931.08 | 24-FEB-13:23 | 7.25 | 4.63 | 0.476482E+09 | 845.65 | 16-FEB-14:20 | 7.25 | 4.63 |
March | 0.619794E+10 | 33268.89 | 19-MAR-12:41 | 16.42 | 12.53 | 0.587765E+09 | 845.65 | 28-MAR-13:09 | 15.78 | 9.88 |
April | 0.862874E+10 | 34708.58 | 16-APR-11:32 | 24.63 | 19.46 | 0.537196E+09 | 846.14 | 18-APR-13:39 | 27.93 | 20.65 |
May | 0.102811E+11 | 23478.78 | 29-MAY-12:22 | 24.45 | 18.92 | 0.623132E+09 | 845.66 | 08-MAY-13:00 | 24.45 | 18.92 |
June | 0.126564E+11 | 34592.98 | 25-JUN-13:51 | 32.20 | 22.49 | 0.638184E+09 | 845.66 | 21-JUN-13:30 | 32.20 | 22.49 |
July | 0.145190E+11 | 34307.85 | 02-JUL-12:42 | 28.40 | 22.40 | 0.604715E+09 | 845.66 | 18-JUL-09:30 | 21.40 | 14.62 |
August | 0.161113E+11 | 25063.17 | 13-AUG-11:21 | 21.10 | 18.55 | 0.677549E+09 | 846.10 | 02-AUG-13:00 | 21.10 | 18.55 |
September | 0.127676E+11 | 34678.20 | 10-SEP-14:31 | 27.43 | 17.62 | 0.577960E+09 | 846.10 | 05-SEP-13:00 | 27.43 | 17.62 |
October | 0.930077E+10 | 35982.21 | 29-OCT-13:21 | 13.35 | 7.41 | 0.576781E+09 | 845.85 | 20-OCT-13:39 | 13.35 | 7.41 |
November | 0.511875E+10 | 32885.93 | 12-NOV-12:31 | -0.4 | -3.0 | 0.523845E+09 | 845.65 | 14-NOV-10:50 | 5.95 | 3.65 |
December | 0.326233E+10 | 25795.94 | 03-DEC-13:12 | 5.60 | 2.35 | 0.495655E+09 | 845.65 | 28-DEC-14:09 | -4.9 | -6.1 |
Annual Sum or Average | 0.105349E+12 | 0.683076E+10 | ||||||||
Minimum of Months | 0.280413E+10 | 15112.47 | -0.4 | -3.0 | 0.476482E+09 | 845.65 | -24.2 | -24.6 | ||
Maximum of Months | 0.161113E+11 | 35982.21 | 32.20 | 22.49 | 0.677549E+09 | 846.14 | 32.20 | 22.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127132E+10 | 5895.14 | 12-JAN-15:40 | 2.80 | 1.13 | 0.304615E+09 | 498.95 | 12-JAN-15:50 | 2.80 | 1.13 |
February | 0.264502E+10 | 10002.01 | 24-FEB-16:21 | 7.75 | 5.51 | 0.284934E+09 | 544.96 | 24-FEB-14:50 | 7.75 | 5.51 |
March | 0.589587E+10 | 11733.17 | 19-MAR-16:03 | 18.80 | 13.89 | 0.361196E+09 | 544.96 | 28-MAR-13:50 | 16.52 | 10.22 |
April | 0.938546E+10 | 42036.42 | 16-APR-16:11 | 28.70 | 20.49 | 0.350323E+09 | 544.96 | 12-APR-13:00 | 28.70 | 20.49 |
May | 0.100943E+11 | 38508.26 | 21-MAY-16:21 | 18.35 | 10.29 | 0.391960E+09 | 544.97 | 08-MAY-13:00 | 18.35 | 10.29 |
June | 0.128159E+11 | 42746.18 | 25-JUN-17:11 | 31.50 | 21.73 | 0.409661E+09 | 544.96 | 21-JUN-13:30 | 31.50 | 21.73 |
July | 0.152645E+11 | 43262.52 | 02-JUL-16:41 | 28.98 | 21.21 | 0.392887E+09 | 544.97 | 18-JUL-09:30 | 21.40 | 14.62 |
August | 0.158942E+11 | 36780.93 | 13-AUG-16:01 | 25.50 | 20.53 | 0.441348E+09 | 544.97 | 07-AUG-13:09 | 25.50 | 20.53 |
September | 0.985144E+10 | 33277.80 | 10-SEP-14:31 | 27.43 | 17.62 | 0.359531E+09 | 544.96 | 07-SEP-13:00 | 27.43 | 17.62 |
October | 0.708701E+10 | 33610.45 | 01-OCT-16:11 | 17.70 | 11.56 | 0.351329E+09 | 544.96 | 19-OCT-13:39 | 17.67 | 10.18 |
November | 0.492410E+10 | 10982.92 | 03-NOV-15:23 | 15.55 | 9.47 | 0.327729E+09 | 544.95 | 03-NOV-13:39 | 15.55 | 9.47 |
December | 0.300479E+10 | 6675.82 | 01-DEC-15:23 | -1.4 | -3.8 | 0.302136E+09 | 537.17 | 01-DEC-14:00 | -1.4 | -3.8 |
Annual Sum or Average | 0.981339E+11 | 0.427765E+10 | ||||||||
Minimum of Months | 0.127132E+10 | 5895.14 | -1.4 | -3.8 | 0.284934E+09 | 498.95 | -1.4 | -3.8 | ||
Maximum of Months | 0.158942E+11 | 43262.52 | 31.50 | 21.73 | 0.441348E+09 | 544.97 | 31.50 | 21.73 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 87796233.93 | 5030.61 | 11-JAN-06:04 | -4.4 | -4.6 | 0.462951E+09 | 626.10 | 18-JAN-10:00 | -13.9 | -14.4 |
February | 0.215244E+09 | 4846.95 | 14-FEB-06:04 | -3.3 | -4.4 | 0.420787E+09 | 625.80 | 02-FEB-14:00 | -3.3 | -4.4 |
March | 0.177554E+10 | 5865.50 | 28-MAR-15:30 | 16.40 | 10.50 | 0.509555E+09 | 695.44 | 28-MAR-13:00 | 16.40 | 10.50 |
April | 0.420428E+10 | 10094.88 | 16-APR-16:21 | 28.60 | 20.44 | 0.470051E+09 | 845.61 | 18-APR-13:20 | 27.57 | 20.63 |
May | 0.836113E+10 | 10423.22 | 31-MAY-15:00 | 30.00 | 19.70 | 0.562655E+09 | 845.61 | 31-MAY-13:20 | 30.00 | 19.70 |
June | 0.107072E+11 | 11850.11 | 26-JUN-14:30 | 31.40 | 21.97 | 0.608539E+09 | 845.63 | 21-JUN-13:30 | 31.40 | 21.97 |
July | 0.111773E+11 | 10956.37 | 26-JUL-15:20 | 30.00 | 25.67 | 0.578052E+09 | 845.62 | 21-JUL-13:20 | 30.00 | 25.67 |
August | 0.109021E+11 | 11834.59 | 04-AUG-15:30 | 33.90 | 25.83 | 0.637153E+09 | 845.62 | 09-AUG-13:20 | 26.50 | 16.73 |
September | 0.744346E+10 | 10265.69 | 11-SEP-14:30 | 28.60 | 20.18 | 0.515091E+09 | 845.62 | 07-SEP-13:20 | 28.60 | 20.18 |
October | 0.361088E+10 | 7136.14 | 01-OCT-15:01 | 19.18 | 12.23 | 0.478219E+09 | 716.08 | 02-OCT-13:00 | 17.40 | 14.50 |
November | 0.161568E+10 | 6805.14 | 08-NOV-06:01 | 12.20 | 11.27 | 0.464235E+09 | 691.14 | 03-NOV-13:00 | 12.20 | 11.27 |
December | 50701590.82 | 5075.71 | 30-DEC-06:03 | -1.7 | -2.2 | 0.446857E+09 | 626.03 | 11-DEC-14:09 | -1.7 | -2.2 |
Annual Sum or Average | 0.601512E+11 | 0.615414E+10 | ||||||||
Minimum of Months | 50701590.82 | 4846.95 | -4.4 | -4.6 | 0.420787E+09 | 625.80 | -13.9 | -14.4 | ||
Maximum of Months | 0.111773E+11 | 11850.11 | 33.90 | 25.83 | 0.637153E+09 | 845.63 | 31.40 | 25.67 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137894E+09 | 4631.78 | 12-JAN-11:02 | 0.28 | -1.0 | 0.215198E+09 | 486.21 | 12-JAN-11:09 | 0.28 | -1.0 |
February | 0.439527E+09 | 13105.47 | 24-FEB-11:01 | 5.68 | 2.52 | 0.199268E+09 | 548.49 | 24-FEB-11:09 | 5.68 | 2.52 |
March | 0.193552E+10 | 17504.61 | 28-MAR-10:01 | 10.47 | 6.54 | 0.253311E+09 | 548.49 | 28-MAR-10:09 | 10.47 | 6.54 |
April | 0.391703E+10 | 21095.39 | 30-APR-09:02 | 10.18 | 5.26 | 0.240955E+09 | 548.49 | 14-APR-12:09 | 10.18 | 5.26 |
May | 0.732481E+10 | 29725.76 | 14-MAY-08:52 | 15.60 | 12.96 | 0.290342E+09 | 548.52 | 04-MAY-10:09 | 15.60 | 12.96 |
June | 0.983540E+10 | 31266.32 | 25-JUN-09:22 | 26.95 | 21.50 | 0.299301E+09 | 548.49 | 08-JUN-12:09 | 26.95 | 21.50 |
July | 0.105211E+11 | 34218.91 | 30-JUL-09:21 | 23.35 | 19.20 | 0.284999E+09 | 548.50 | 18-JUL-10:09 | 23.35 | 19.20 |
August | 0.970747E+10 | 32132.56 | 20-AUG-09:01 | 20.97 | 18.46 | 0.315627E+09 | 548.50 | 30-AUG-10:09 | 18.68 | 15.67 |
September | 0.676295E+10 | 30732.21 | 04-SEP-08:41 | 15.63 | 12.89 | 0.264267E+09 | 548.50 | 18-SEP-10:09 | 21.97 | 16.57 |
October | 0.281315E+10 | 14534.15 | 20-OCT-10:01 | 15.68 | 10.42 | 0.243429E+09 | 548.49 | 20-OCT-14:09 | 22.72 | 13.08 |
November | 0.103027E+10 | 12878.08 | 04-NOV-10:01 | 9.60 | 5.18 | 0.221570E+09 | 548.49 | 03-NOV-10:09 | 9.60 | 5.18 |
December | 0.138421E+09 | 4175.53 | 01-DEC-11:02 | -2.1 | -4.0 | 0.208553E+09 | 452.41 | 01-DEC-11:09 | -2.1 | -4.0 |
Annual Sum or Average | 0.545636E+11 | 0.303682E+10 | ||||||||
Minimum of Months | 0.137894E+09 | 4175.53 | -2.1 | -4.0 | 0.199268E+09 | 452.41 | -2.1 | -4.0 | ||
Maximum of Months | 0.105211E+11 | 34218.91 | 26.95 | 21.50 | 0.315627E+09 | 548.52 | 26.95 | 21.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.268406E+10 | 15509.83 | 12-JAN-12:40 | 2.03 | 0.42 | 0.500221E+09 | 845.65 | 30-JAN-14:30 | -24.1 | -24.5 |
February | 0.359138E+10 | 22012.65 | 24-FEB-13:32 | 7.43 | 4.81 | 0.464521E+09 | 845.65 | 24-FEB-14:20 | 7.97 | 5.32 |
March | 0.569974E+10 | 31658.92 | 19-MAR-13:11 | 17.23 | 13.08 | 0.566192E+09 | 845.66 | 24-MAR-13:30 | 12.75 | 6.50 |
April | 0.762549E+10 | 31983.54 | 16-APR-13:42 | 27.62 | 20.47 | 0.515775E+09 | 845.66 | 19-APR-13:20 | 10.60 | 7.03 |
May | 0.101669E+11 | 18089.69 | 30-MAY-13:30 | 26.70 | 19.86 | 0.594228E+09 | 845.66 | 22-MAY-13:00 | 26.70 | 19.86 |
June | 0.124112E+11 | 18772.75 | 30-JUN-13:10 | 29.40 | 21.96 | 0.615997E+09 | 845.65 | 21-JUN-13:20 | 29.40 | 21.96 |
July | 0.135402E+11 | 41232.62 | 30-JUL-14:01 | 27.20 | 19.47 | 0.585839E+09 | 845.65 | 11-JUL-13:00 | 27.20 | 19.47 |
August | 0.148569E+11 | 41695.74 | 13-AUG-13:11 | 25.37 | 19.81 | 0.655998E+09 | 845.68 | 07-AUG-13:09 | 25.37 | 19.81 |
September | 0.127105E+11 | 45539.79 | 17-SEP-14:21 | 27.20 | 18.12 | 0.557058E+09 | 846.63 | 05-SEP-13:20 | 27.20 | 18.12 |
October | 0.890064E+10 | 45667.80 | 01-OCT-13:41 | 18.95 | 12.28 | 0.552333E+09 | 846.32 | 20-OCT-13:30 | 22.20 | 12.82 |
November | 0.417340E+10 | 23460.94 | 03-NOV-13:30 | 15.85 | 10.76 | 0.495975E+09 | 845.68 | 03-NOV-13:39 | 15.93 | 10.67 |
December | 0.280971E+10 | 17778.94 | 01-DEC-13:23 | -0.9 | -3.3 | 0.482297E+09 | 845.65 | 14-DEC-14:09 | 1.20 | 0.19 |
Annual Sum or Average | 0.991701E+11 | 0.658643E+10 | ||||||||
Minimum of Months | 0.268406E+10 | 15509.83 | -0.9 | -3.3 | 0.464521E+09 | 845.65 | -24.1 | -24.5 | ||
Maximum of Months | 0.148569E+11 | 45667.80 | 29.40 | 21.96 | 0.655998E+09 | 846.63 | 29.40 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363678E+09 | 4800.69 | 12-JAN-15:50 | 2.80 | 1.13 | 0.299255E+09 | 451.99 | 12-JAN-15:00 | 2.80 | 1.13 |
February | 0.926125E+09 | 7963.85 | 24-FEB-16:22 | 7.75 | 5.51 | 0.275963E+09 | 521.20 | 24-FEB-15:50 | 7.75 | 5.51 |
March | 0.246962E+10 | 8097.71 | 23-MAR-15:53 | 17.20 | 10.15 | 0.337817E+09 | 521.20 | 22-MAR-15:20 | 17.20 | 10.15 |
April | 0.531054E+10 | 33692.38 | 16-APR-16:21 | 28.60 | 20.44 | 0.317108E+09 | 544.94 | 18-APR-13:20 | 27.57 | 20.63 |
May | 0.793291E+10 | 37022.61 | 14-MAY-17:01 | 21.42 | 15.87 | 0.366257E+09 | 544.95 | 31-MAY-13:20 | 29.80 | 19.61 |
June | 0.105423E+11 | 35576.87 | 25-JUN-16:41 | 31.78 | 21.74 | 0.388636E+09 | 544.96 | 15-JUN-13:39 | 31.78 | 21.74 |
July | 0.114058E+11 | 35100.77 | 02-JUL-16:51 | 28.90 | 21.17 | 0.371563E+09 | 544.95 | 21-JUL-13:20 | 22.40 | 16.99 |
August | 0.110964E+11 | 34563.85 | 13-AUG-16:31 | 25.20 | 20.49 | 0.412361E+09 | 544.95 | 07-AUG-13:00 | 25.20 | 20.49 |
September | 0.745651E+10 | 35604.67 | 04-SEP-17:21 | 21.40 | 14.23 | 0.334511E+09 | 544.95 | 07-SEP-13:20 | 31.87 | 18.17 |
October | 0.396136E+10 | 12018.06 | 20-OCT-15:30 | 22.30 | 13.06 | 0.323573E+09 | 544.22 | 20-OCT-13:00 | 22.30 | 13.06 |
November | 0.171169E+10 | 8206.86 | 03-NOV-15:22 | 15.55 | 9.47 | 0.301545E+09 | 521.19 | 03-NOV-15:00 | 15.00 | 9.33 |
December | 0.480497E+09 | 4801.17 | 01-DEC-15:40 | -1.5 | -3.9 | 0.289533E+09 | 453.13 | 01-DEC-15:50 | -1.6 | -4.0 |
Annual Sum or Average | 0.636575E+11 | 0.401812E+10 | ||||||||
Minimum of Months | 0.363678E+09 | 4800.69 | -1.5 | -3.9 | 0.275963E+09 | 451.99 | -1.6 | -4.0 | ||
Maximum of Months | 0.114058E+11 | 37022.61 | 31.78 | 21.74 | 0.412361E+09 | 544.96 | 31.87 | 21.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 42967367.45 | 5577.65 | 14-JAN-17:01 | -7.4 | -8.6 | 0.462614E+09 | 626.12 | 05-JAN-10:00 | -7.4 | -8.6 |
February | 0.132775E+09 | 6612.02 | 25-FEB-06:03 | 0.00 | -0.6 | 0.420350E+09 | 625.82 | 03-FEB-14:20 | 0.00 | -0.6 |
March | 0.111933E+10 | 6865.74 | 28-MAR-15:30 | 16.40 | 10.50 | 0.505689E+09 | 648.61 | 28-MAR-13:00 | 16.40 | 10.50 |
April | 0.357865E+10 | 13199.80 | 16-APR-16:21 | 28.60 | 20.44 | 0.460096E+09 | 841.58 | 18-APR-13:00 | 28.30 | 20.65 |
May | 0.837554E+10 | 11774.72 | 31-MAY-15:00 | 30.00 | 19.70 | 0.529758E+09 | 845.61 | 31-MAY-13:20 | 30.00 | 19.70 |
June | 0.116103E+11 | 15668.61 | 25-JUN-17:41 | 31.20 | 21.79 | 0.575638E+09 | 845.61 | 28-JUN-13:20 | 28.90 | 20.51 |
July | 0.123217E+11 | 14591.60 | 02-JUL-17:51 | 28.30 | 21.02 | 0.546298E+09 | 845.61 | 05-JUL-13:20 | 26.87 | 20.29 |
August | 0.117064E+11 | 13336.83 | 04-AUG-15:30 | 33.90 | 25.83 | 0.601361E+09 | 845.60 | 11-AUG-13:39 | 27.77 | 18.47 |
September | 0.700796E+10 | 12929.57 | 17-SEP-14:11 | 27.20 | 18.12 | 0.488092E+09 | 845.61 | 11-SEP-13:20 | 27.20 | 18.12 |
October | 0.237349E+10 | 7543.60 | 01-OCT-14:31 | 19.27 | 12.32 | 0.467044E+09 | 672.44 | 20-OCT-13:00 | 22.60 | 13.03 |
November | 0.919529E+09 | 6715.94 | 07-NOV-06:02 | 10.50 | 9.67 | 0.459369E+09 | 638.24 | 03-NOV-13:00 | 10.50 | 9.67 |
December | 43503618.61 | 5678.74 | 02-DEC-17:01 | 1.70 | 0.90 | 0.446310E+09 | 626.01 | 27-DEC-14:00 | -6.7 | -8.4 |
Annual Sum or Average | 0.592320E+11 | 0.596262E+10 | ||||||||
Minimum of Months | 42967367.45 | 5577.65 | -7.4 | -8.6 | 0.420350E+09 | 625.82 | -7.4 | -8.6 | ||
Maximum of Months | 0.123217E+11 | 15668.61 | 33.90 | 25.83 | 0.601361E+09 | 845.61 | 30.00 | 20.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 85794262.84 | 3614.55 | 14-JAN-17:01 | -7.4 | -8.6 | 0.298141E+09 | 403.47 | 03-JAN-14:50 | -7.4 | -8.6 |
February | 0.377824E+09 | 4960.29 | 24-FEB-10:20 | 4.80 | 1.70 | 0.271562E+09 | 460.75 | 24-FEB-10:30 | 5.00 | 1.88 |
March | 0.177252E+10 | 6049.79 | 28-MAR-10:00 | 10.00 | 6.30 | 0.333182E+09 | 529.46 | 28-MAR-09:00 | 10.00 | 6.30 |
April | 0.376583E+10 | 14432.81 | 18-APR-09:40 | 24.67 | 19.90 | 0.315551E+09 | 544.96 | 13-APR-09:09 | 24.67 | 19.90 |
May | 0.751325E+10 | 23119.46 | 29-MAY-09:01 | 22.48 | 18.29 | 0.375856E+09 | 544.98 | 04-MAY-09:50 | 22.48 | 18.29 |
June | 0.103030E+11 | 38743.01 | 25-JUN-08:21 | 25.00 | 20.84 | 0.399604E+09 | 544.96 | 21-JUN-13:20 | 25.00 | 20.84 |
July | 0.110306E+11 | 36759.21 | 02-JUL-07:51 | 23.90 | 20.48 | 0.380063E+09 | 545.00 | 18-JUL-09:30 | 21.40 | 14.62 |
August | 0.101413E+11 | 28460.75 | 27-AUG-09:21 | 23.60 | 19.50 | 0.421376E+09 | 545.02 | 08-AUG-09:09 | 23.60 | 19.50 |
September | 0.665157E+10 | 18182.84 | 03-SEP-09:52 | 18.30 | 13.33 | 0.342601E+09 | 544.97 | 06-SEP-09:00 | 25.60 | 18.61 |
October | 0.256818E+10 | 6171.41 | 01-OCT-13:51 | 19.00 | 12.30 | 0.307088E+09 | 536.61 | 20-OCT-09:00 | 15.20 | 10.20 |
November | 0.778143E+09 | 4562.45 | 03-NOV-10:36 | 13.87 | 11.30 | 0.296527E+09 | 429.50 | 03-NOV-13:00 | 16.10 | 10.47 |
December | 57061171.72 | 3690.30 | 02-DEC-17:01 | 1.70 | 0.90 | 0.287654E+09 | 403.49 | 11-DEC-14:09 | -19.4 | -20.1 |
Annual Sum or Average | 0.550452E+11 | 0.402921E+10 | ||||||||
Minimum of Months | 57061171.72 | 3614.55 | -7.4 | -8.6 | 0.271562E+09 | 403.47 | -19.4 | -20.1 | ||
Maximum of Months | 0.110306E+11 | 38743.01 | 25.00 | 20.84 | 0.421376E+09 | 545.02 | 25.60 | 20.84 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226856E+10 | 13051.41 | 12-JAN-12:40 | 2.03 | 0.42 | 0.485538E+09 | 845.65 | 02-JAN-14:20 | 2.03 | 0.42 |
February | 0.330791E+10 | 20843.89 | 24-FEB-13:43 | 7.62 | 4.99 | 0.446136E+09 | 845.65 | 24-FEB-14:20 | 7.97 | 5.32 |
March | 0.480300E+10 | 18596.32 | 24-MAR-13:32 | 12.93 | 6.50 | 0.546990E+09 | 845.65 | 28-MAR-13:09 | 15.78 | 9.88 |
April | 0.686055E+10 | 29309.51 | 16-APR-13:42 | 27.62 | 20.47 | 0.502181E+09 | 845.67 | 14-APR-13:39 | 27.62 | 20.47 |
May | 0.102174E+11 | 19599.75 | 30-MAY-13:30 | 26.70 | 19.86 | 0.561676E+09 | 845.66 | 22-MAY-13:00 | 26.70 | 19.86 |
June | 0.130959E+11 | 52955.55 | 25-JUN-14:21 | 32.20 | 22.49 | 0.591637E+09 | 845.66 | 21-JUN-13:20 | 32.20 | 22.49 |
July | 0.144419E+11 | 48975.01 | 02-JUL-14:31 | 29.23 | 21.69 | 0.562945E+09 | 845.65 | 18-JUL-13:20 | 24.07 | 16.16 |
August | 0.153896E+11 | 42996.93 | 13-AUG-13:11 | 25.37 | 19.81 | 0.631567E+09 | 845.68 | 07-AUG-13:09 | 25.37 | 19.81 |
September | 0.120548E+11 | 57722.24 | 17-SEP-13:31 | 26.67 | 18.01 | 0.530189E+09 | 845.66 | 12-SEP-13:20 | 26.67 | 18.01 |
October | 0.730594E+10 | 52768.46 | 01-OCT-13:51 | 19.00 | 12.30 | 0.527496E+09 | 845.65 | 20-OCT-13:09 | 21.93 | 12.68 |
November | 0.333665E+10 | 22461.04 | 03-NOV-13:22 | 15.85 | 10.76 | 0.475765E+09 | 845.65 | 03-NOV-13:09 | 15.85 | 10.76 |
December | 0.239023E+10 | 15757.47 | 01-DEC-13:23 | -0.9 | -3.3 | 0.470127E+09 | 845.65 | 14-DEC-14:09 | 1.20 | 0.19 |
Annual Sum or Average | 0.954725E+11 | 0.633225E+10 | ||||||||
Minimum of Months | 0.226856E+10 | 13051.41 | -0.9 | -3.3 | 0.446136E+09 | 845.65 | 1.20 | 0.19 | ||
Maximum of Months | 0.153896E+11 | 57722.24 | 32.20 | 22.49 | 0.631567E+09 | 845.68 | 32.20 | 22.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.268087E+09 | 4882.98 | 12-JAN-15:50 | 2.80 | 1.13 | 0.298544E+09 | 431.90 | 12-JAN-15:00 | 2.80 | 1.13 |
February | 0.768216E+09 | 7717.33 | 24-FEB-16:24 | 7.75 | 5.51 | 0.274371E+09 | 521.20 | 24-FEB-15:50 | 7.75 | 5.51 |
March | 0.198633E+10 | 7863.95 | 23-MAR-15:51 | 17.20 | 10.15 | 0.334840E+09 | 521.20 | 22-MAR-15:30 | 17.20 | 10.15 |
April | 0.474404E+10 | 36874.77 | 16-APR-16:21 | 28.60 | 20.44 | 0.313351E+09 | 544.94 | 18-APR-13:20 | 27.57 | 20.63 |
May | 0.766947E+10 | 32141.97 | 14-MAY-16:32 | 21.70 | 15.60 | 0.356783E+09 | 544.94 | 31-MAY-13:20 | 29.80 | 19.61 |
June | 0.106801E+11 | 44624.61 | 25-JUN-17:01 | 31.60 | 21.70 | 0.380753E+09 | 544.96 | 07-JUN-13:00 | 31.60 | 21.70 |
July | 0.116303E+11 | 43671.98 | 02-JUL-17:11 | 28.70 | 21.12 | 0.363540E+09 | 544.95 | 18-JUL-13:39 | 24.23 | 16.07 |
August | 0.111503E+11 | 37653.38 | 13-AUG-16:31 | 25.20 | 20.49 | 0.402635E+09 | 544.95 | 09-AUG-13:20 | 25.20 | 20.49 |
September | 0.693258E+10 | 38167.72 | 04-SEP-17:21 | 21.40 | 14.23 | 0.326300E+09 | 544.95 | 05-SEP-13:00 | 27.20 | 16.61 |
October | 0.311251E+10 | 12221.42 | 20-OCT-15:30 | 22.30 | 13.06 | 0.317338E+09 | 539.32 | 20-OCT-13:00 | 22.30 | 13.06 |
November | 0.121938E+10 | 7874.93 | 03-NOV-15:22 | 15.55 | 9.47 | 0.298195E+09 | 521.19 | 03-NOV-15:00 | 15.00 | 9.33 |
December | 0.355281E+09 | 4842.76 | 01-DEC-15:40 | -1.5 | -3.9 | 0.288232E+09 | 431.27 | 01-DEC-14:00 | -1.5 | -3.9 |
Annual Sum or Average | 0.605166E+11 | 0.395488E+10 | ||||||||
Minimum of Months | 0.268087E+09 | 4842.76 | -1.5 | -3.9 | 0.274371E+09 | 431.27 | -1.5 | -3.9 | ||
Maximum of Months | 0.116303E+11 | 44624.61 | 31.60 | 21.70 | 0.402635E+09 | 544.96 | 31.60 | 21.70 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140397E+10 | 19776.40 | 06-JAN-04:11 | -26.3 | -26.5 | 0.00 | 0.00 | 01-JAN-00:10 | -26.3 | -26.5 |
February | 0.192301E+10 | 17785.30 | 04-FEB-04:11 | -30.9 | -31.1 | 0.00 | 0.00 | 01-FEB-00:10 | -30.9 | -31.1 |
March | 0.348671E+10 | 12217.35 | 06-MAR-04:01 | -16.0 | -16.5 | 0.00 | 0.00 | 01-MAR-00:10 | -16.0 | -16.5 |
April | 0.560932E+10 | 11471.02 | 03-APR-04:01 | -6.8 | -7.6 | 0.00 | 0.00 | 01-APR-00:10 | -6.8 | -7.6 |
May | 0.710202E+10 | 9225.22 | 06-MAY-05:06 | 9.40 | 6.46 | 0.00 | 0.00 | 01-MAY-00:10 | 9.40 | 6.46 |
June | 0.964715E+10 | 9728.24 | 26-JUN-15:30 | 31.40 | 21.97 | 0.00 | 0.00 | 01-JUN-00:10 | 31.40 | 21.97 |
July | 0.108507E+11 | 10129.68 | 31-JUL-05:04 | 16.88 | 15.09 | 0.00 | 0.00 | 01-JUL-00:10 | 16.88 | 15.09 |
August | 0.116336E+11 | 10579.10 | 14-AUG-05:12 | 15.77 | 15.05 | 0.00 | 0.00 | 01-AUG-00:10 | 15.77 | 15.05 |
September | 0.828964E+10 | 10721.95 | 09-SEP-05:12 | 13.70 | 13.03 | 0.00 | 0.00 | 01-SEP-00:10 | 13.70 | 13.03 |
October | 0.563924E+10 | 11254.10 | 23-OCT-05:01 | -2.7 | -3.7 | 0.00 | 0.00 | 01-OCT-00:10 | -2.7 | -3.7 |
November | 0.416137E+10 | 17211.05 | 26-NOV-02:41 | -24.9 | -25.2 | 0.00 | 0.00 | 01-NOV-00:10 | -24.9 | -25.2 |
December | 0.215454E+10 | 19070.09 | 09-DEC-04:01 | -22.8 | -23.0 | 0.00 | 0.00 | 01-DEC-00:10 | -22.8 | -23.0 |
Annual Sum or Average | 0.719013E+11 | 0.00 | ||||||||
Minimum of Months | 0.140397E+10 | 9225.22 | -30.9 | -31.1 | 0.00 | 0.00 | -30.9 | -31.1 | ||
Maximum of Months | 0.116336E+11 | 19776.40 | 31.40 | 21.97 | 0.00 | 0.00 | 31.40 | 21.97 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.257073E+10 | 20726.82 | 06-JAN-04:01 | -26.2 | -26.5 | 0.00 | 0.00 | 01-JAN-00:10 | -26.2 | -26.5 |
February | 0.247886E+10 | 23207.85 | 18-FEB-04:11 | -15.6 | -16.0 | 0.00 | 0.00 | 01-FEB-00:10 | -15.6 | -16.0 |
March | 0.230159E+10 | 22385.37 | 21-MAR-03:01 | -6.7 | -7.9 | 0.00 | 0.00 | 01-MAR-00:10 | -6.7 | -7.9 |
April | 0.395272E+10 | 18800.28 | 22-APR-04:01 | -0.6 | -1.1 | 0.00 | 0.00 | 01-APR-00:10 | -0.6 | -1.1 |
May | 0.601346E+10 | 15396.50 | 02-MAY-04:11 | 2.60 | 0.50 | 0.00 | 0.00 | 01-MAY-00:10 | 2.60 | 0.50 |
June | 0.838969E+10 | 10159.42 | 22-JUN-05:06 | 9.68 | 8.78 | 0.00 | 0.00 | 01-JUN-00:10 | 9.68 | 8.78 |
July | 0.888101E+10 | 10473.61 | 06-JUL-05:08 | 18.90 | 18.18 | 0.00 | 0.00 | 01-JUL-00:10 | 18.90 | 18.18 |
August | 0.899366E+10 | 10640.02 | 30-AUG-05:10 | 13.90 | 12.58 | 0.00 | 0.00 | 01-AUG-00:10 | 13.90 | 12.58 |
September | 0.682522E+10 | 18396.41 | 30-SEP-04:01 | -0.5 | -1.9 | 0.00 | 0.00 | 01-SEP-00:10 | -0.5 | -1.9 |
October | 0.340868E+10 | 17940.54 | 27-OCT-04:01 | 0.00 | -1.2 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | -1.2 |
November | 0.319270E+10 | 20907.71 | 10-NOV-04:01 | -1.7 | -2.3 | 0.00 | 0.00 | 01-NOV-00:10 | -1.7 | -2.3 |
December | 0.233434E+10 | 26715.49 | 09-DEC-02:12 | -22.6 | -22.9 | 0.00 | 0.00 | 01-DEC-00:10 | -22.6 | -22.9 |
Annual Sum or Average | 0.593426E+11 | 0.00 | ||||||||
Minimum of Months | 0.230159E+10 | 10159.42 | -26.2 | -26.5 | 0.00 | 0.00 | -26.2 | -26.5 | ||
Maximum of Months | 0.899366E+10 | 26715.49 | 18.90 | 18.18 | 0.00 | 0.00 | 18.90 | 18.18 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5055198.05 | 677.57 | 13-JAN-13:00 | 3.90 | 1.72 | 0.00 | 0.00 | 01-JAN-00:10 | 3.90 | 1.72 |
February | 0.219825E+09 | 6389.05 | 24-FEB-13:50 | 7.62 | 4.99 | 0.00 | 0.00 | 01-FEB-00:10 | 7.62 | 4.99 |
March | 0.187498E+10 | 14243.29 | 19-MAR-13:03 | 16.97 | 12.93 | 0.00 | 0.00 | 01-MAR-00:10 | 16.97 | 12.93 |
April | 0.651486E+10 | 27152.02 | 18-APR-13:40 | 27.93 | 20.65 | 0.00 | 0.00 | 01-APR-00:10 | 27.93 | 20.65 |
May | 0.130289E+11 | 31668.28 | 31-MAY-13:50 | 29.50 | 19.49 | 0.00 | 0.00 | 01-MAY-00:10 | 29.50 | 19.49 |
June | 0.193032E+11 | 35257.58 | 30-JUN-13:50 | 29.40 | 21.96 | 0.00 | 0.00 | 01-JUN-00:10 | 29.40 | 21.96 |
July | 0.209468E+11 | 34028.23 | 05-JUL-13:50 | 27.12 | 19.90 | 0.00 | 0.00 | 01-JUL-00:10 | 27.12 | 19.90 |
August | 0.193111E+11 | 34891.45 | 04-AUG-14:30 | 33.60 | 25.57 | 0.00 | 0.00 | 01-AUG-00:10 | 33.60 | 25.57 |
September | 0.108718E+11 | 33068.34 | 07-SEP-13:30 | 31.95 | 18.23 | 0.00 | 0.00 | 01-SEP-00:10 | 31.95 | 18.23 |
October | 0.311880E+10 | 15603.56 | 20-OCT-14:30 | 22.95 | 13.19 | 0.00 | 0.00 | 01-OCT-00:10 | 22.95 | 13.19 |
November | 0.622275E+09 | 9167.18 | 03-NOV-13:01 | 15.68 | 10.94 | 0.00 | 0.00 | 01-NOV-00:10 | 15.68 | 10.94 |
December | 42943.42 | 134.55 | 03-DEC-14:15 | 5.40 | 2.13 | 0.00 | 0.00 | 01-DEC-00:10 | 5.40 | 2.13 |
Annual Sum or Average | 0.958176E+11 | 0.00 | ||||||||
Minimum of Months | 42943.42 | 134.55 | 3.90 | 1.72 | 0.00 | 0.00 | 3.90 | 1.72 | ||
Maximum of Months | 0.209468E+11 | 35257.58 | 33.60 | 25.57 | 0.00 | 0.00 | 33.60 | 25.57 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112873E+10 | 6798.01 | 30-JAN-13:01 | -24.9 | -25.2 | 96253310.48 | 154.44 | 19-JAN-10:00 | -24.9 | -25.2 |
February | 0.533245E+10 | 10396.54 | 04-FEB-10:31 | -24.8 | -25.2 | 94468169.12 | 222.14 | 02-FEB-16:49 | -24.8 | -25.2 |
March | 0.128528E+11 | 6618.61 | 31-MAR-23:47 | -0.8 | -1.9 | 0.103236E+09 | 126.82 | 24-MAR-13:00 | -0.8 | -1.9 |
April | 0.180738E+11 | 8329.20 | 16-APR-17:57 | 26.70 | 19.84 | 91605448.10 | 126.83 | 18-APR-13:09 | 27.38 | 20.62 |
May | 0.408172E+10 | 3461.20 | 31-MAY-23:51 | 15.10 | 10.22 | 99235205.19 | 126.83 | 30-MAY-13:09 | 15.10 | 10.22 |
June | 0.927105E+10 | 5369.73 | 30-JUN-23:51 | 19.10 | 15.95 | 98959367.83 | 126.83 | 26-JUN-09:09 | 19.10 | 15.95 |
July | 0.149242E+11 | 7255.02 | 31-JUL-24:00 | 18.20 | 17.87 | 91881475.16 | 126.82 | 03-JUL-13:00 | 18.20 | 17.87 |
August | 0.199462E+11 | 8484.50 | 29-AUG-17:40 | 21.67 | 14.89 | 0.103240E+09 | 126.83 | 04-AUG-09:09 | 21.67 | 14.89 |
September | 0.416255E+10 | 2843.58 | 30-SEP-23:51 | 3.90 | 1.09 | 91606517.16 | 126.83 | 11-SEP-09:00 | 3.90 | 1.09 |
October | 0.846482E+10 | 4730.37 | 31-OCT-23:52 | 1.50 | -0.9 | 95230060.73 | 126.82 | 10-OCT-13:09 | 1.50 | -0.9 |
November | 0.123018E+11 | 9904.18 | 26-NOV-08:11 | -24.8 | -25.2 | 94344881.20 | 126.82 | 08-NOV-10:00 | -24.8 | -25.2 |
December | 0.170412E+11 | 7867.82 | 01-DEC-16:03 | -2.1 | -4.3 | 91880866.73 | 126.82 | 05-DEC-14:20 | -3.9 | -7.4 |
Annual Sum or Average | 0.127581E+12 | 0.115194E+10 | ||||||||
Minimum of Months | 0.112873E+10 | 2843.58 | -24.9 | -25.2 | 91605448.10 | 126.82 | -24.9 | -25.2 | ||
Maximum of Months | 0.199462E+11 | 10396.54 | 26.70 | 19.84 | 0.103240E+09 | 222.14 | 27.38 | 20.62 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.399714E+09 | 1800.11 | 12-JAN-16:40 | 2.07 | 0.72 | 94914838.43 | 135.62 | 06-JAN-10:09 | 2.07 | 0.72 |
February | 0.363062E+10 | 9982.48 | 04-FEB-10:31 | -24.8 | -25.2 | 93190390.17 | 217.27 | 03-FEB-16:00 | -24.8 | -25.2 |
March | 0.109252E+11 | 5963.77 | 31-MAR-23:12 | -0.3 | -1.4 | 0.103236E+09 | 126.82 | 24-MAR-13:00 | -0.3 | -1.4 |
April | 0.163957E+11 | 7852.62 | 15-APR-18:10 | 27.85 | 18.48 | 91605456.91 | 126.83 | 18-APR-13:09 | 27.38 | 20.62 |
May | 0.327144E+10 | 3267.67 | 31-MAY-23:40 | 15.90 | 10.90 | 99235157.57 | 126.83 | 30-MAY-13:00 | 15.90 | 10.90 |
June | 0.854844E+10 | 5200.13 | 30-JUN-23:51 | 19.10 | 15.95 | 98959515.88 | 126.83 | 30-JUN-09:00 | 19.10 | 15.95 |
July | 0.139443E+11 | 6778.70 | 31-JUL-24:00 | 18.20 | 17.87 | 91881496.47 | 126.82 | 03-JUL-13:00 | 18.20 | 17.87 |
August | 0.186612E+11 | 8127.41 | 29-AUG-17:40 | 21.67 | 14.89 | 0.103241E+09 | 126.83 | 04-AUG-09:09 | 21.67 | 14.89 |
September | 0.322588E+10 | 2554.22 | 01-SEP-17:50 | 22.07 | 14.32 | 91606517.22 | 126.83 | 11-SEP-13:09 | 28.40 | 20.30 |
October | 0.686008E+10 | 4228.77 | 11-OCT-16:52 | 16.70 | 11.06 | 95230063.77 | 126.82 | 10-OCT-13:00 | 16.70 | 11.06 |
November | 0.993435E+10 | 9354.19 | 26-NOV-08:11 | -24.8 | -25.2 | 94335219.00 | 126.82 | 08-NOV-10:00 | -24.8 | -25.2 |
December | 0.140112E+11 | 7292.86 | 01-DEC-16:03 | -2.1 | -4.3 | 91880868.78 | 126.82 | 05-DEC-14:20 | -3.9 | -7.4 |
Annual Sum or Average | 0.109808E+12 | 0.114932E+10 | ||||||||
Minimum of Months | 0.399714E+09 | 1800.11 | -24.8 | -25.2 | 91605456.91 | 126.82 | -24.8 | -25.2 | ||
Maximum of Months | 0.186612E+11 | 9982.48 | 27.85 | 18.48 | 0.103241E+09 | 217.27 | 28.40 | 20.62 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157431E+09 | 1586.17 | 12-JAN-16:40 | 2.07 | 0.72 | 92405414.75 | 128.11 | 26-JAN-14:50 | -12.3 | -12.7 |
February | 0.232062E+10 | 8266.63 | 04-FEB-10:31 | -24.8 | -25.2 | 91244992.21 | 200.63 | 02-FEB-16:00 | -24.8 | -25.2 |
March | 0.905826E+10 | 5724.66 | 21-MAR-17:32 | -1.8 | -4.9 | 0.103236E+09 | 126.82 | 24-MAR-13:00 | 13.30 | 6.51 |
April | 0.149642E+11 | 8020.34 | 16-APR-17:57 | 26.70 | 19.84 | 91605408.39 | 126.83 | 18-APR-13:09 | 27.38 | 20.62 |
May | 0.252430E+10 | 3147.02 | 31-MAY-23:20 | 16.70 | 11.57 | 99236878.33 | 126.83 | 30-MAY-13:09 | 16.70 | 11.57 |
June | 0.812456E+10 | 5093.88 | 30-JUN-23:30 | 19.60 | 15.96 | 98959516.64 | 126.83 | 13-JUN-13:09 | 19.60 | 15.96 |
July | 0.136512E+11 | 6512.29 | 31-JUL-23:50 | 18.27 | 17.81 | 91881650.99 | 126.82 | 03-JUL-13:00 | 18.27 | 17.81 |
August | 0.182648E+11 | 8229.25 | 29-AUG-17:40 | 21.67 | 14.89 | 0.103240E+09 | 126.83 | 04-AUG-09:09 | 21.67 | 14.89 |
September | 0.237472E+10 | 2652.94 | 01-SEP-17:40 | 22.43 | 14.32 | 91610726.13 | 126.83 | 11-SEP-13:09 | 28.40 | 20.30 |
October | 0.481198E+10 | 4220.85 | 11-OCT-16:41 | 16.88 | 11.21 | 95230115.54 | 126.82 | 10-OCT-13:00 | 16.88 | 11.21 |
November | 0.785097E+10 | 9246.42 | 26-NOV-08:11 | -24.8 | -25.2 | 94318130.10 | 126.82 | 08-NOV-10:00 | -24.8 | -25.2 |
December | 0.118451E+11 | 7031.56 | 01-DEC-16:03 | -2.1 | -4.3 | 91880869.74 | 126.82 | 05-DEC-14:20 | -3.9 | -7.4 |
Annual Sum or Average | 0.959481E+11 | 0.114485E+10 | ||||||||
Minimum of Months | 0.157431E+09 | 1586.17 | -24.8 | -25.2 | 91244992.21 | 126.82 | -24.8 | -25.2 | ||
Maximum of Months | 0.182648E+11 | 9246.42 | 26.70 | 19.84 | 0.103240E+09 | 200.63 | 28.40 | 20.62 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227885E+12 | 95031.73 | 18-JAN-13:01 | -16.2 | -16.5 | 0.208450E+10 | 2793.44 | 11-JAN-14:09 | -16.2 | -16.5 |
February | 0.430858E+12 | 484674.86 | 01-FEB-00:12 | -24.4 | -24.7 | 0.155635E+10 | 2634.97 | 08-FEB-14:00 | 2.20 | 0.97 |
March | 0.720801E+12 | 521666.13 | 24-MAR-15:52 | 10.60 | 5.50 | 0.188083E+10 | 2742.35 | 24-MAR-09:09 | 10.60 | 5.50 |
April | 0.939351E+12 | 490466.75 | 19-APR-09:42 | 5.60 | 4.05 | 0.161599E+10 | 2802.90 | 17-APR-13:00 | 5.60 | 4.05 |
May | 0.233752E+12 | 466173.84 | 31-MAY-23:56 | 15.10 | 10.22 | 0.215333E+10 | 2813.48 | 22-MAY-13:09 | 15.10 | 10.22 |
June | 0.469441E+12 | 487183.82 | 03-JUN-02:22 | 5.85 | 5.59 | 0.200615E+10 | 2745.24 | 19-JUN-09:09 | 15.18 | 12.11 |
July | 0.730836E+12 | 488467.29 | 24-JUL-02:52 | 10.00 | 9.40 | 0.197130E+10 | 2746.06 | 14-JUL-09:09 | 10.00 | 9.40 |
August | 0.979023E+12 | 496623.96 | 06-AUG-19:34 | 14.60 | 10.55 | 0.220072E+10 | 2991.14 | 07-AUG-15:20 | 22.80 | 14.05 |
September | 0.234971E+12 | 481570.91 | 30-SEP-23:12 | 3.77 | 0.73 | 0.198824E+10 | 2794.55 | 15-SEP-13:30 | 3.77 | 0.73 |
October | 0.490316E+12 | 510496.12 | 31-OCT-23:53 | 1.50 | -0.9 | 0.176766E+10 | 2745.17 | 11-OCT-09:50 | 1.50 | -0.9 |
November | 0.703448E+12 | 517651.82 | 01-NOV-02:42 | 3.97 | 3.17 | 0.170453E+10 | 2729.36 | 15-NOV-14:09 | 7.07 | 4.91 |
December | 0.977503E+12 | 486450.79 | 13-DEC-13:04 | -5.5 | -5.9 | 0.158179E+10 | 2632.37 | 08-DEC-14:00 | -5.5 | -5.9 |
Annual Sum or Average | 0.713818E+13 | 0.225114E+11 | ||||||||
Minimum of Months | 0.227885E+12 | 95031.73 | -24.4 | -24.7 | 0.155635E+10 | 2632.37 | -16.2 | -16.5 | ||
Maximum of Months | 0.979023E+12 | 521666.13 | 15.10 | 10.55 | 0.220072E+10 | 2991.14 | 22.80 | 14.05 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136478E+09 | 91097.77 | 31-JAN-07:10 | -30.5 |
February | 0.529258E+09 | 92598.48 | 03-FEB-07:08 | -33.9 |
March | 40658174.29 | 2881.31 | 25-MAR-05:11 | -1.3 |
April | 73487402.21 | 10173.63 | 15-APR-16:01 | 30.00 |
May | 62116073.69 | 3268.28 | 03-MAY-05:05 | 1.38 |
June | 83564874.63 | 6163.81 | 10-JUN-16:01 | 27.20 |
July | 51288683.50 | 6106.88 | 29-JUL-16:01 | 27.20 |
August | 38833379.21 | 4467.71 | 05-AUG-16:01 | 26.02 |
September | 86735601.22 | 7898.07 | 16-SEP-16:02 | 28.62 |
October | 80884108.57 | 2695.15 | 23-OCT-05:04 | -2.7 |
November | 65911170.68 | 2946.03 | 13-NOV-06:11 | -3.1 |
December | 61706228.02 | 3474.65 | 27-DEC-06:12 | -9.6 |
Annual Sum or Average | 0.131092E+10 | |||
Minimum of Months | 38833379.21 | 2695.15 | -33.9 | |
Maximum of Months | 0.529258E+09 | 92598.48 | 30.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8294301.76 | 23479.40 | 30-JAN-06:01 | -28.4 |
February | 6320078.39 | 23948.61 | 06-FEB-06:01 | -15.0 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:03 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 |
Annual Sum or Average | 14614380.15 | |||
Minimum of Months | 0.00 | 0.00 | -28.4 | |
Maximum of Months | 8294301.76 | 23948.61 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.156821E+10 | 69532.47 | 02-JAN-04:01 | -4.0 |
February | 0.442404E+09 | 66369.50 | 06-FEB-05:01 | -14.5 |
March | 0.111465E+09 | 63762.90 | 06-MAR-05:01 | -15.4 |
April | 8313135.41 | 57350.92 | 03-APR-05:01 | -7.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 0.278211E+09 | 66654.05 | 27-NOV-05:01 | -9.4 |
December | 0.586586E+09 | 65891.96 | 11-DEC-05:01 | -22.2 |
Annual Sum or Average | 0.299519E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.2 | |
Maximum of Months | 0.156821E+10 | 69532.47 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150433E+11 | 134327.99 | 30-JAN-03:21 | -26.9 |
February | 0.925446E+10 | 132635.39 | 06-FEB-02:61 | -17.9 |
March | 0.442678E+10 | 130902.62 | 06-MAR-04:01 | -16.0 |
April | 0.131304E+10 | 128947.37 | 03-APR-03:01 | -6.2 |
May | 34928832.20 | 81066.54 | 22-MAY-05:02 | 4.78 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.121038E+09 | 99905.81 | 30-SEP-05:01 | 0.10 |
October | 0.144860E+10 | 112999.31 | 23-OCT-04:01 | -1.9 |
November | 0.627752E+10 | 132086.01 | 27-NOV-00:01 | -12.6 |
December | 0.110313E+11 | 133490.55 | 11-DEC-04:01 | -21.8 |
Annual Sum or Average | 0.489510E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.9 | |
Maximum of Months | 0.150433E+11 | 134327.99 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.742857E+10 | 26385.04 | 30-JAN-03:51 | -27.2 |
February | 0.429137E+10 | 27298.32 | 02-FEB-04:11 | -35.4 |
March | 0.947796E+09 | 24988.01 | 06-MAR-04:01 | -16.0 |
April | 0.120388E+09 | 22732.68 | 03-APR-04:01 | -6.8 |
May | 276428.25 | 1842.85 | 02-MAY-05:03 | 2.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 4635388.32 | 17207.71 | 30-SEP-05:01 | 0.10 |
October | 25274584.73 | 20213.76 | 23-OCT-05:01 | -2.7 |
November | 0.116734E+10 | 25978.42 | 26-NOV-04:41 | -25.0 |
December | 0.323976E+10 | 26337.26 | 11-DEC-02:61 | -21.7 |
Annual Sum or Average | 0.172254E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.742857E+10 | 27298.32 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.448960E+10 | 22594.62 | 30-JAN-03:51 | -27.2 |
February | 0.251488E+10 | 23520.68 | 02-FEB-04:11 | -35.4 |
March | 0.699316E+09 | 21183.26 | 06-MAR-04:01 | -16.0 |
April | 0.121434E+09 | 19062.54 | 03-APR-04:01 | -6.8 |
May | 533331.81 | 2868.88 | 02-MAY-05:03 | 2.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 6286255.34 | 12864.12 | 30-SEP-05:01 | 0.10 |
October | 34082634.83 | 15478.47 | 23-OCT-05:01 | -2.7 |
November | 0.866714E+09 | 22346.68 | 26-NOV-04:41 | -25.0 |
December | 0.247609E+10 | 22660.19 | 11-DEC-02:61 | -21.7 |
Annual Sum or Average | 0.112089E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.448960E+10 | 23520.68 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.587065E+10 | 29393.63 | 30-JAN-03:51 | -27.2 |
February | 0.319683E+10 | 30318.91 | 02-FEB-04:11 | -35.4 |
March | 0.116593E+10 | 27899.06 | 06-MAR-04:21 | -15.9 |
April | 0.259931E+09 | 26669.74 | 03-APR-03:01 | -6.2 |
May | 5492577.10 | 10220.19 | 02-MAY-05:03 | 2.20 |
June | 15219.15 | 101.46 | 03-JUN-05:03 | 5.78 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 25774198.20 | 19227.07 | 30-SEP-05:01 | 0.10 |
October | 0.128808E+09 | 21774.01 | 23-OCT-05:01 | -2.7 |
November | 0.137305E+10 | 29337.58 | 26-NOV-07:21 | -27.2 |
December | 0.354305E+10 | 29543.33 | 11-DEC-02:61 | -21.7 |
Annual Sum or Average | 0.155695E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.587065E+10 | 30318.91 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255783E+10 | 22543.47 | 31-JAN-04:01 | -31.0 |
February | 0.113667E+10 | 22875.90 | 02-FEB-04:11 | -35.4 |
March | 0.116758E+09 | 19498.53 | 06-MAR-05:01 | -15.4 |
April | 10520145.38 | 18627.31 | 03-APR-04:01 | -6.8 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 103486.05 | 1724.77 | 29-SEP-05:03 | 0.92 |
October | 1807098.19 | 15348.63 | 23-OCT-05:01 | -2.7 |
November | 0.234893E+09 | 20819.72 | 27-NOV-04:01 | -10.4 |
December | 0.557570E+09 | 21835.41 | 11-DEC-04:01 | -21.8 |
Annual Sum or Average | 0.461615E+10 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.255783E+10 | 22875.90 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174791E+11 | 41082.86 | 19-JAN-04:11 | -26.5 |
February | 0.103341E+11 | 40855.62 | 02-FEB-03:31 | -35.0 |
March | 0.458778E+10 | 38829.64 | 06-MAR-00:01 | -16.3 |
April | 0.128253E+10 | 36854.25 | 03-APR-01:41 | -6.1 |
May | 85774610.21 | 27137.74 | 02-MAY-04:11 | 2.60 |
June | 4428058.19 | 18928.74 | 02-JUN-05:01 | 7.20 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 18.93 |
August | 85947.37 | 859.47 | 07-AUG-05:03 | 8.80 |
September | 0.182498E+09 | 28132.19 | 30-SEP-04:01 | -0.5 |
October | 0.914020E+09 | 30797.70 | 23-OCT-05:01 | -2.7 |
November | 0.594156E+10 | 39747.23 | 26-NOV-04:01 | -25.0 |
December | 0.121611E+11 | 42372.00 | 09-DEC-02:11 | -22.6 |
Annual Sum or Average | 0.529729E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.174791E+11 | 42372.00 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100512E+11 | 29670.23 | 19-JAN-04:11 | -26.5 |
February | 0.559123E+10 | 29453.74 | 02-FEB-03:31 | -35.0 |
March | 0.246809E+10 | 27976.22 | 06-MAR-04:01 | -16.0 |
April | 0.703816E+09 | 26568.02 | 03-APR-01:41 | -6.1 |
May | 31529502.93 | 18406.34 | 02-MAY-04:11 | 2.60 |
June | 1583052.67 | 12503.09 | 02-JUN-05:01 | 7.20 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 18.93 |
August | 32782.02 | 194.83 | 17-AUG-05:03 | 10.68 |
September | 94058821.83 | 19073.47 | 30-SEP-04:01 | -0.5 |
October | 0.492395E+09 | 21104.31 | 23-OCT-05:01 | -2.7 |
November | 0.354366E+10 | 28667.49 | 26-NOV-04:01 | -25.0 |
December | 0.720494E+10 | 30429.25 | 09-DEC-02:11 | -22.6 |
Annual Sum or Average | 0.301825E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.100512E+11 | 30429.25 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116864E+11 | 40056.83 | 19-JAN-04:11 | -26.5 |
February | 0.627674E+10 | 39560.74 | 02-FEB-02:51 | -35.0 |
March | 0.320985E+10 | 37743.16 | 06-MAR-04:01 | -16.0 |
April | 0.101660E+10 | 35864.64 | 03-APR-01:41 | -6.1 |
May | 68248700.11 | 26094.02 | 02-MAY-04:11 | 2.60 |
June | 3512760.71 | 18293.55 | 02-JUN-05:01 | 7.20 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.129802E+09 | 27231.25 | 30-SEP-04:01 | -0.5 |
October | 0.584881E+09 | 29976.40 | 23-OCT-05:01 | -2.7 |
November | 0.413799E+10 | 38671.29 | 26-NOV-03:21 | -25.0 |
December | 0.883056E+10 | 40779.52 | 09-DEC-02:11 | -22.6 |
Annual Sum or Average | 0.359446E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.116864E+11 | 40779.52 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.932948E+10 | 31203.47 | 19-JAN-04:11 | -26.5 |
February | 0.495436E+10 | 30705.71 | 02-FEB-03:31 | -35.0 |
March | 0.215709E+10 | 29107.30 | 06-MAR-04:01 | -16.0 |
April | 0.537526E+09 | 26694.50 | 03-APR-03:01 | -6.2 |
May | 34237276.07 | 18876.50 | 02-MAY-04:11 | 2.60 |
June | 1935516.16 | 12870.37 | 02-JUN-05:01 | 7.20 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 93646335.77 | 19863.84 | 30-SEP-04:01 | -0.5 |
October | 0.421161E+09 | 21603.96 | 23-OCT-05:01 | -2.7 |
November | 0.300983E+10 | 30094.04 | 26-NOV-03:21 | -25.0 |
December | 0.635144E+10 | 31971.44 | 09-DEC-02:11 | -22.6 |
Annual Sum or Average | 0.268907E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.932948E+10 | 31971.44 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255482E+11 | 55408.06 | 29-JAN-10:41 | -22.3 |
February | 0.172604E+11 | 54644.46 | 02-FEB-04:01 | -35.2 |
March | 0.930518E+10 | 52020.84 | 06-MAR-04:01 | -16.0 |
April | 0.372048E+10 | 48912.67 | 03-APR-02:41 | -6.1 |
May | 0.473738E+09 | 38838.53 | 02-MAY-04:11 | 2.60 |
June | 0.114422E+09 | 30290.83 | 05-JUN-04:11 | 9.13 |
July | 1896452.17 | 21190.22 | 24-JUL-05:01 | 10.28 |
August | 22498465.84 | 20078.26 | 07-AUG-05:02 | 8.80 |
September | 0.908305E+09 | 39187.47 | 30-SEP-03:01 | -0.1 |
October | 0.338106E+10 | 42798.04 | 23-OCT-04:31 | -2.3 |
November | 0.116100E+11 | 53329.77 | 26-NOV-04:01 | -25.0 |
December | 0.204165E+11 | 56194.12 | 09-DEC-02:61 | -22.7 |
Annual Sum or Average | 0.927627E+11 | |||
Minimum of Months | 1896452.17 | 20078.26 | -35.2 | |
Maximum of Months | 0.255482E+11 | 56194.12 | 10.28 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154355E+11 | 35794.67 | 29-JAN-06:41 | -22.0 |
February | 0.989386E+10 | 35356.55 | 02-FEB-04:01 | -35.2 |
March | 0.521464E+10 | 33746.11 | 06-MAR-04:01 | -16.0 |
April | 0.214373E+10 | 31700.14 | 03-APR-02:41 | -6.1 |
May | 0.198783E+09 | 25106.50 | 02-MAY-04:11 | 2.60 |
June | 63165475.12 | 19412.65 | 05-JUN-04:11 | 9.13 |
July | 409964.60 | 5691.41 | 24-JUL-05:01 | 10.28 |
August | 9740309.09 | 12949.66 | 07-AUG-05:02 | 8.80 |
September | 0.471744E+09 | 25306.28 | 30-SEP-03:01 | -0.1 |
October | 0.183492E+10 | 27771.12 | 23-OCT-04:31 | -2.3 |
November | 0.706343E+10 | 34521.68 | 26-NOV-04:01 | -25.0 |
December | 0.125515E+11 | 36447.43 | 09-DEC-02:61 | -22.7 |
Annual Sum or Average | 0.548814E+11 | |||
Minimum of Months | 409964.60 | 5691.41 | -35.2 | |
Maximum of Months | 0.154355E+11 | 36447.43 | 10.28 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188832E+11 | 53948.16 | 29-JAN-06:41 | -22.0 |
February | 0.121077E+11 | 53107.39 | 02-FEB-04:01 | -35.2 |
March | 0.715860E+10 | 50811.72 | 06-MAR-04:01 | -16.0 |
April | 0.320708E+10 | 47941.04 | 03-APR-02:41 | -6.1 |
May | 0.444614E+09 | 37674.87 | 02-MAY-04:11 | 2.60 |
June | 0.113863E+09 | 29496.05 | 05-JUN-04:11 | 9.13 |
July | 2724205.97 | 16324.18 | 24-JUL-05:01 | 10.28 |
August | 12095670.24 | 19217.72 | 07-AUG-05:02 | 8.80 |
September | 0.716188E+09 | 38191.37 | 30-SEP-03:01 | -0.1 |
October | 0.238226E+10 | 41881.33 | 23-OCT-04:31 | -2.3 |
November | 0.887212E+10 | 52041.66 | 26-NOV-04:01 | -25.0 |
December | 0.158550E+11 | 55007.19 | 09-DEC-02:61 | -22.7 |
Annual Sum or Average | 0.697555E+11 | |||
Minimum of Months | 2724205.97 | 16324.18 | -35.2 | |
Maximum of Months | 0.188832E+11 | 55007.19 | 10.28 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141462E+11 | 36282.99 | 29-JAN-10:41 | -22.3 |
February | 0.850993E+10 | 35411.13 | 02-FEB-04:01 | -35.2 |
March | 0.437566E+10 | 33491.92 | 06-MAR-04:01 | -16.0 |
April | 0.156778E+10 | 31473.43 | 03-APR-02:41 | -6.1 |
May | 0.195463E+09 | 24781.76 | 02-MAY-04:11 | 2.60 |
June | 53444496.51 | 19073.84 | 05-JUN-04:11 | 9.13 |
July | 5920.56 | 98.68 | 11-JUL-05:04 | 13.98 |
August | 2293094.15 | 11035.18 | 07-AUG-05:02 | 8.80 |
September | 0.416586E+09 | 25182.08 | 30-SEP-03:01 | -0.1 |
October | 0.143534E+10 | 27584.43 | 23-OCT-04:31 | -2.3 |
November | 0.575680E+10 | 34460.16 | 26-NOV-03:21 | -25.0 |
December | 0.105955E+11 | 36638.51 | 09-DEC-02:61 | -22.7 |
Annual Sum or Average | 0.470549E+11 | |||
Minimum of Months | 5920.56 | 98.68 | -35.2 | |
Maximum of Months | 0.141462E+11 | 36638.51 | 13.98 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238690E+10 | 12119.47 | 30-JAN-06:11 | -28.5 |
February | 0.133580E+10 | 11309.38 | 20-FEB-13:12 | 2.80 |
March | 0.189233E+09 | 11671.49 | 19-MAR-11:27 | 14.70 |
April | 86695860.38 | 14387.34 | 16-APR-15:31 | 28.70 |
May | 58695608.24 | 9426.94 | 14-MAY-16:32 | 21.70 |
June | 57434364.72 | 11064.67 | 25-JUN-15:11 | 32.20 |
July | 0.101191E+09 | 11844.33 | 30-JUL-14:52 | 27.20 |
August | 78013193.58 | 12528.01 | 31-AUG-04:11 | 19.07 |
September | 55197957.76 | 9660.34 | 04-SEP-15:32 | 22.20 |
October | 45340820.46 | 13956.66 | 01-OCT-14:51 | 19.40 |
November | 0.360526E+09 | 10956.61 | 09-NOV-05:11 | 15.00 |
December | 0.777130E+09 | 8409.43 | 03-DEC-13:12 | 5.60 |
Annual Sum or Average | 0.553216E+10 | |||
Minimum of Months | 45340820.46 | 8409.43 | -28.5 | |
Maximum of Months | 0.238690E+10 | 14387.34 | 32.20 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.819870E+10 | 26629.72 | 02-JAN-06:12 | -5.2 |
February | 0.431120E+10 | 21997.61 | 06-FEB-06:05 | -15.0 |
March | 0.175855E+10 | 14746.30 | 06-MAR-06:05 | -14.1 |
April | 0.494741E+09 | 13363.38 | 16-APR-15:42 | 28.80 |
May | 45907047.63 | 9962.76 | 21-MAY-16:32 | 18.17 |
June | 43237841.97 | 10004.68 | 11-JUN-15:22 | 33.05 |
July | 61056905.94 | 12734.87 | 30-JUL-15:21 | 27.50 |
August | 31459833.90 | 11958.92 | 13-AUG-15:11 | 25.93 |
September | 39496416.96 | 14555.72 | 04-SEP-16:01 | 22.20 |
October | 0.202712E+09 | 13984.23 | 01-OCT-14:21 | 19.20 |
November | 0.254362E+10 | 19918.62 | 27-NOV-06:05 | -9.4 |
December | 0.497083E+10 | 21565.95 | 11-DEC-06:05 | -22.1 |
Annual Sum or Average | 0.227015E+11 | |||
Minimum of Months | 31459833.90 | 9962.76 | -22.1 | |
Maximum of Months | 0.819870E+10 | 26629.72 | 33.05 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.431551E+11 | 75701.38 | 31-JAN-05:11 | -30.6 |
February | 0.292754E+11 | 77369.96 | 02-FEB-05:31 | -36.5 |
March | 0.168212E+11 | 63350.64 | 06-MAR-05:25 | -15.0 |
April | 0.788419E+10 | 54127.81 | 03-APR-04:11 | -6.9 |
May | 0.155078E+10 | 27651.54 | 31-MAY-05:02 | 16.38 |
June | 0.543023E+09 | 35019.81 | 01-JUN-05:01 | 5.65 |
July | 0.171445E+09 | 34030.16 | 13-JUL-05:01 | 13.27 |
August | 0.392949E+09 | 29276.88 | 24-AUG-05:01 | 12.30 |
September | 0.272370E+10 | 27940.33 | 08-SEP-05:02 | 14.32 |
October | 0.790218E+10 | 41074.04 | 16-OCT-04:21 | 1.35 |
November | 0.211943E+11 | 59500.11 | 24-NOV-05:04 | -14.7 |
December | 0.364245E+11 | 67721.97 | 11-DEC-05:31 | -22.2 |
Annual Sum or Average | 0.168039E+12 | |||
Minimum of Months | 0.171445E+09 | 27651.54 | -36.5 | |
Maximum of Months | 0.431551E+11 | 77369.96 | 16.38 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.390224E+09 | 1587.41 | 20-JAN-04:03 | -24.9 |
February | 0.201442E+09 | 1524.94 | 01-FEB-00:52 | -25.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:03 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 25401730.69 | 1673.39 | 26-NOV-03:02 | -25.0 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 |
Annual Sum or Average | 0.617068E+09 | |||
Minimum of Months | 0.00 | 0.00 | -25.3 | |
Maximum of Months | 0.390224E+09 | 1673.39 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159470E+10 | 1361.20 | 30-JAN-23:55 | -28.9 |
February | 0.192199E+09 | 1400.56 | 01-FEB-00:52 | -25.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:03 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 24623748.81 | 1457.64 | 26-NOV-03:02 | -25.0 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 |
Annual Sum or Average | 0.181153E+10 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.159470E+10 | 1457.64 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217409E+10 | 1446.72 | 29-JAN-17:21 | -22.2 |
February | 0.536700E+09 | 1409.75 | 01-FEB-23:01 | -31.9 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:03 | -1.2 |
May | 86543682.00 | 996.56 | 14-MAY-09:50 | 16.93 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.138704E+09 | 1292.17 | 30-SEP-04:09 | -0.5 |
October | 8191797.38 | 1103.33 | 23-OCT-01:34 | -0.1 |
November | 25618663.84 | 1411.72 | 26-NOV-03:02 | -25.0 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 |
Annual Sum or Average | 0.296985E+10 | |||
Minimum of Months | 0.00 | 0.00 | -31.9 | |
Maximum of Months | 0.217409E+10 | 1446.72 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -2.8 |
February | 0.101447E+10 | 19252.08 | 01-FEB-00:31 | -24.8 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:03 | -1.2 |
May | 162626.57 | 2050.35 | 31-MAY-23:54 | 15.10 |
June | 0.292225E+09 | 39815.56 | 05-JUN-01:01 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 2831811.97 | 18013.64 | 30-SEP-23:31 | 3.83 |
October | 0.331041E+09 | 27125.60 | 10-OCT-05:01 | 11.27 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 |
Annual Sum or Average | 0.164073E+10 | |||
Minimum of Months | 0.00 | 0.00 | -24.8 | |
Maximum of Months | 0.101447E+10 | 39815.56 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.278508E+11 | 29144.79 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.252627E+11 | 29144.79 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.300191E+11 | 29144.79 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.268132E+11 | 29144.79 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.289349E+11 | 29144.79 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.287951E+11 | 29144.79 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.269531E+11 | 29144.79 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.300191E+11 | 29144.79 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.268132E+11 | 29144.79 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.278508E+11 | 29144.79 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.275243E+11 | 29144.79 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.269531E+11 | 29144.79 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.333789E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.252627E+11 | 29144.79 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.300191E+11 | 29144.79 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.785272E+10 | 8217.58 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.712300E+10 | 8217.58 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.846411E+10 | 8217.58 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.756018E+10 | 8217.58 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.815842E+10 | 8217.58 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.811897E+10 | 8217.58 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.759962E+10 | 8217.58 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.846411E+10 | 8217.58 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.756018E+10 | 8217.58 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.785272E+10 | 8217.58 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.776069E+10 | 8217.58 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.759962E+10 | 8217.58 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.941143E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.712300E+10 | 8217.58 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.846411E+10 | 8217.58 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.289349E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.287951E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.275243E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.333789E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231970E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173995E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152994E+10 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11241128.88 | 0.960015E+09 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2872530.51 | 0.502848E+09 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45970277.06 | 0.294823E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16905872.90 | 0.202769E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15740825.89 | 0.287592E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15636399.04 | 0.464863E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.946912E+09 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153335E+10 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200480E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108367E+09 | 0.127876E+11 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202769E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45970277.06 | 0.231970E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154259E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115952E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101861E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9209603.49 | 0.634299E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2023039.12 | 0.333536E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32708542.28 | 0.190745E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13130507.90 | 0.125467E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12908887.34 | 0.176342E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11037815.70 | 0.310498E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634392E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101349E+10 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132974E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81018395.83 | 0.846922E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125467E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32708542.28 | 0.154259E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232898E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175701E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154501E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8219654.55 | 0.960068E+09 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2830845.59 | 0.498801E+09 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43826646.09 | 0.283404E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15153436.49 | 0.195314E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14480359.10 | 0.285578E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10127875.87 | 0.477488E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.966017E+09 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153118E+10 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201993E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94638817.70 | 0.128488E+11 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195314E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43826646.09 | 0.232898E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158702E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120676E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108837E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4378743.76 | 0.713979E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2050497.13 | 0.359862E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26824493.99 | 0.217141E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8807424.35 | 0.164603E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9356150.49 | 0.232988E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8529789.42 | 0.337746E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670770E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107181E+10 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140054E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59947099.14 | 0.905160E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164603E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26824493.99 | 0.158702E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527479E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385243E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328610E+10 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38812179.92 | 0.198419E+10 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8445489.70 | 0.103382E+10 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129474E+09 | 0.607435E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54539530.01 | 0.409269E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50565280.46 | 0.568478E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53434636.61 | 0.937375E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72412.90 | 0.189782E+10 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326297E+10 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441925E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335343E+09 | 0.275339E+11 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409269E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129474E+09 | 0.527479E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350596E+10 |
February | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257328E+10 |
March | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222641E+10 |
April | 0.688021E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20779257.71 | 0.138722E+10 |
May | 0.744847E+09 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4408373.18 | 0.745282E+09 |
June | 0.742030E+09 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72018217.01 | 0.426569E+09 |
July | 0.690839E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27499967.92 | 0.296608E+09 |
August | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27118942.77 | 0.399221E+09 |
September | 0.688021E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25437258.15 | 0.674589E+09 |
October | 0.715730E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133340E+10 |
November | 0.708685E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218889E+10 |
December | 0.690839E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294321E+10 |
Annual Sum or Average | 0.858171E+10 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177262E+09 | 0.187006E+11 |
Minimum of Months | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296608E+09 |
Maximum of Months | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72018217.01 | 0.350596E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533424E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397442E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343622E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19721522.69 | 0.211974E+10 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6742079.57 | 0.110083E+10 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109319E+09 | 0.619076E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39130801.75 | 0.429779E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34715756.36 | 0.617923E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23627880.82 | 0.105903E+10 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212904E+10 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339120E+10 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454103E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233257E+09 | 0.287525E+11 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429779E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109319E+09 | 0.533424E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352882E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261436E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225582E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12963437.85 | 0.143854E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5160980.21 | 0.758030E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65802700.93 | 0.441637E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23999237.87 | 0.329176E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26395761.58 | 0.441152E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22887352.16 | 0.693586E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134271E+10 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221613E+10 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297557E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157209E+09 | 0.190355E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329176E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65802700.93 | 0.352882E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652123E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473427E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392205E+10 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50629373.96 | 0.231715E+10 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11916146.20 | 0.117101E+10 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166982E+09 | 0.681113E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76262529.19 | 0.454479E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73170434.21 | 0.632339E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74549365.16 | 0.104723E+10 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 493735.75 | 0.208109E+10 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394558E+10 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544068E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454004E+09 | 0.329482E+11 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454479E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166982E+09 | 0.652123E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434807E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315786E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263820E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26209317.48 | 0.161347E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5496035.93 | 0.844410E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89273195.62 | 0.484965E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35007664.07 | 0.339659E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36109959.58 | 0.450310E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33615021.72 | 0.753499E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4613.51 | 0.144595E+10 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263478E+10 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362826E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225716E+09 | 0.223394E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339659E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89273195.62 | 0.434807E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656029E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480701E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406171E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26652306.79 | 0.247345E+10 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8661841.97 | 0.124875E+10 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144456E+09 | 0.698331E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55253641.14 | 0.481153E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48066623.30 | 0.692878E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32978719.22 | 0.119123E+10 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234978E+10 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403658E+10 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551216E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316069E+09 | 0.341133E+11 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481153E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144456E+09 | 0.656029E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435876E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318883E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269484E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15623837.28 | 0.169739E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6014545.87 | 0.886888E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79207318.04 | 0.516968E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29445103.59 | 0.389027E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33057821.23 | 0.516557E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28798266.39 | 0.804650E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151457E+10 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267015E+10 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364578E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192147E+09 | 0.228844E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389027E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79207318.04 | 0.435876E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.785272E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.712300E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.846411E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.756018E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.815842E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.811897E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.759962E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.846411E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.756018E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.785272E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.776069E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.759962E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.941143E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.712300E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.846411E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506322E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382452E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340740E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17659950.16 | 0.216465E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4244836.95 | 0.112597E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82587798.18 | 0.644827E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24040233.15 | 0.458454E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21580779.24 | 0.650691E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21078930.64 | 0.105005E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213748E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342692E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443615E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171193E+09 | 0.283903E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458454E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82587798.18 | 0.506322E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.858646E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651708E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577103E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39967660.36 | 0.366052E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8145890.89 | 0.193701E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162284E+09 | 0.110399E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50837882.66 | 0.773494E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44706320.57 | 0.108928E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45836461.62 | 0.178553E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358603E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571114E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743134E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351779E+09 | 0.479529E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.773494E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162284E+09 | 0.858646E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.915092E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678656E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586111E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22279338.45 | 0.362208E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3913313.01 | 0.196488E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116011E+09 | 0.108316E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21558024.58 | 0.765147E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25956461.61 | 0.106279E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26946184.86 | 0.166984E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327496E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570814E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770251E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216664E+09 | 0.486521E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765147E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116011E+09 | 0.915092E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 29144.79 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 29144.79 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 29144.79 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 29144.79 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 29144.79 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 29144.79 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 29144.79 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 29144.79 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 29144.79 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 29144.79 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 29144.79 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 29144.79 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4371.73 | 29-JAN-10:53 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3089.81 | 10-FEB-22:01 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2605.33 | 12-MAR-15:51 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 470.29 | 15-APR-17:10 | 1950.37 | 02-APR-23:51 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.81 | 31-MAY-13:00 | 1264.50 | 01-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 554.36 | 18-JUN-16:20 | 1020.88 | 02-JUN-05:00 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.03 | 02-JUL-15:30 | 443.37 | 09-JUL-20:51 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.47 | 13-AUG-14:10 | 626.16 | 06-AUG-09:00 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.82 | 17-SEP-14:40 | 908.60 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 1434.35 | 24-OCT-04:51 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 3381.00 | 20-NOV-22:01 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 5114.41 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.37 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 554.36 | 5114.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2954.84 | 29-JAN-10:51 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2058.91 | 10-FEB-22:01 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1843.69 | 05-MAR-09:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 360.71 | 15-APR-17:10 | 1277.06 | 02-APR-23:51 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.20 | 31-MAY-13:00 | 836.02 | 01-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 428.63 | 18-JUN-16:20 | 666.15 | 02-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.76 | 02-JUL-15:30 | 305.27 | 09-JUL-10:30 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.58 | 13-AUG-14:10 | 408.41 | 06-AUG-09:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.23 | 17-SEP-14:40 | 595.80 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 949.86 | 29-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2252.39 | 20-NOV-22:01 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 3407.50 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.27 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 428.63 | 3407.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4689.44 | 29-JAN-13:00 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3088.11 | 10-FEB-22:01 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2871.78 | 05-MAR-13:51 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 416.63 | 15-APR-17:10 | 1830.85 | 02-APR-23:51 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.81 | 31-MAY-13:00 | 1245.49 | 01-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 540.48 | 18-JUN-16:20 | 985.36 | 02-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.19 | 02-JUL-16:10 | 433.21 | 09-JUL-20:51 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.45 | 04-AUG-16:40 | 649.88 | 06-AUG-14:00 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.95 | 10-SEP-15:20 | 967.75 | 24-SEP-12:45 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 1381.79 | 24-OCT-04:51 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 3378.35 | 20-NOV-22:01 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 5108.52 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.21 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 540.48 | 5108.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2914.48 | 29-JAN-10:55 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2064.82 | 10-FEB-22:01 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1901.23 | 05-MAR-15:00 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.54 | 15-APR-17:10 | 1400.79 | 02-APR-23:51 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.20 | 31-MAY-13:00 | 889.14 | 01-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.42 | 11-JUN-16:30 | 710.53 | 02-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.35 | 02-JUL-11:30 | 357.08 | 09-JUL-20:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.63 | 04-AUG-16:40 | 493.32 | 06-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.72 | 17-SEP-12:00 | 683.29 | 24-SEP-16:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 1004.46 | 24-OCT-04:51 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2260.21 | 20-NOV-22:01 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 3450.97 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.08 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 341.42 | 3450.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 10282.74 | 29-JAN-10:58 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 7220.97 | 10-FEB-22:01 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 5784.13 | 06-MAR-05:51 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1347.43 | 15-APR-17:01 | 4101.21 | 02-APR-23:54 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.05 | 29-MAY-10:00 | 2595.88 | 01-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1445.56 | 18-JUN-16:00 | 2140.48 | 02-JUN-04:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 687.37 | 02-JUL-15:40 | 958.52 | 09-JUL-20:51 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 464.98 | 13-AUG-14:00 | 1271.95 | 06-AUG-09:00 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 999.52 | 17-SEP-15:10 | 1867.95 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.75 | 20-OCT-15:00 | 3321.28 | 24-OCT-04:53 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 7887.25 | 20-NOV-22:01 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 12059.66 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 958.52 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1445.56 | 12059.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 6855.36 | 29-JAN-10:55 |
February | 1239.33 | 01-FEB-08:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 4813.39 | 10-FEB-22:01 |
March | 1239.33 | 01-MAR-08:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 3854.46 | 06-MAR-05:51 |
April | 1239.33 | 03-APR-07:10 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 836.98 | 15-APR-17:10 | 2734.11 | 02-APR-23:56 |
May | 1239.33 | 01-MAY-07:10 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.88 | 31-MAY-13:00 | 1761.50 | 01-MAY-24:00 |
June | 1239.33 | 01-JUN-07:10 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 985.52 | 18-JUN-16:20 | 1445.09 | 02-JUN-04:51 |
July | 1239.33 | 03-JUL-07:10 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 354.40 | 02-JUL-15:40 | 698.27 | 04-JUL-09:30 |
August | 1239.33 | 01-AUG-07:10 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 297.52 | 13-AUG-14:00 | 879.24 | 06-AUG-09:00 |
September | 1239.33 | 01-SEP-07:10 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 494.31 | 17-SEP-15:10 | 1256.02 | 18-SEP-23:00 |
October | 1239.33 | 02-OCT-07:10 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2220.10 | 24-OCT-04:53 |
November | 1239.33 | 01-NOV-07:10 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 5257.18 | 20-NOV-22:01 |
December | 1239.33 | 01-DEC-08:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 8039.67 | 09-DEC-01:59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 698.27 | |||||
Maximum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 985.52 | 8039.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 10375.73 | 29-JAN-12:51 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 7225.41 | 10-FEB-22:01 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 6181.46 | 05-MAR-14:00 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1001.86 | 15-APR-17:10 | 4101.14 | 02-APR-23:51 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.32 | 31-MAY-13:00 | 2659.15 | 01-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1326.06 | 18-JUN-16:20 | 2166.58 | 02-JUN-04:51 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 464.78 | 02-JUL-16:20 | 984.17 | 09-JUL-20:51 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.32 | 04-AUG-16:40 | 1446.93 | 06-AUG-14:00 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 280.14 | 10-SEP-14:53 | 2199.50 | 24-SEP-13:40 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 3327.35 | 24-OCT-04:53 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 7892.51 | 20-NOV-22:01 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 12059.52 | 09-DEC-01:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 984.17 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1326.06 | 12059.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 6855.17 | 29-JAN-10:59 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 4814.51 | 10-FEB-22:01 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 3861.13 | 06-MAR-05:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 527.10 | 16-APR-13:10 | 2734.15 | 02-APR-23:57 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.00 | 29-MAY-10:00 | 1768.46 | 01-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 754.24 | 25-JUN-12:10 | 1431.18 | 02-JUN-04:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 390.27 | 02-JUL-11:00 | 728.70 | 09-JUL-20:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.11 | 13-AUG-13:20 | 930.69 | 06-AUG-09:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 466.84 | 17-SEP-11:50 | 1480.05 | 24-SEP-17:18 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2208.81 | 24-OCT-04:53 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 5260.36 | 20-NOV-22:01 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 8039.74 | 09-DEC-01:58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 728.70 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 754.24 | 8039.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 12804.69 | 29-JAN-10:59 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 8957.68 | 10-FEB-22:01 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 7162.91 | 06-MAR-05:51 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1715.12 | 15-APR-17:01 | 5068.05 | 03-APR-00:03 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.22 | 29-MAY-10:30 | 3005.07 | 02-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1933.58 | 18-JUN-16:00 | 2646.62 | 02-JUN-04:54 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 859.36 | 02-JUL-15:20 | 1118.24 | 09-JUL-20:51 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 692.60 | 13-AUG-14:00 | 1405.21 | 06-AUG-09:00 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1327.31 | 17-SEP-15:00 | 2108.21 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.64 | 01-OCT-14:41 | 4048.84 | 24-OCT-04:43 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 9787.58 | 20-NOV-22:01 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 14736.99 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1118.24 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1933.58 | 14736.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 8536.56 | 29-JAN-10:54 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 5970.43 | 10-FEB-22:01 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 4773.05 | 06-MAR-05:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1047.87 | 15-APR-17:10 | 3378.46 | 03-APR-00:03 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.62 | 31-MAY-13:00 | 2003.42 | 02-MAY-04:58 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1263.32 | 18-JUN-16:00 | 1764.45 | 02-JUN-04:54 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 463.37 | 02-JUL-16:00 | 869.35 | 04-JUL-09:30 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 388.96 | 13-AUG-14:00 | 975.59 | 06-AUG-09:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 700.23 | 17-SEP-15:00 | 1419.04 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.37 | 20-OCT-15:00 | 2699.20 | 24-OCT-04:44 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 6524.10 | 20-NOV-22:01 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 9822.26 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 869.35 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1263.32 | 9822.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 12804.74 | 29-JAN-10:55 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 8964.27 | 10-FEB-22:01 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 7173.77 | 05-MAR-14:00 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1307.65 | 15-APR-17:10 | 5068.23 | 03-APR-00:03 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.43 | 31-MAY-13:00 | 3005.20 | 02-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1793.16 | 18-JUN-16:00 | 2646.67 | 02-JUN-04:56 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 737.52 | 02-JUL-16:00 | 1148.94 | 09-JUL-20:51 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.68 | 05-AUG-17:10 | 1713.70 | 06-AUG-13:50 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 565.79 | 10-SEP-15:20 | 2383.11 | 24-SEP-14:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 4048.83 | 24-OCT-04:47 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 9793.68 | 20-NOV-22:01 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 14744.61 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1148.94 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1793.16 | 14744.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 8536.43 | 29-JAN-11:00 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 5975.34 | 10-FEB-22:01 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 4783.43 | 06-MAR-05:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 726.48 | 16-APR-13:10 | 3378.41 | 03-APR-00:03 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.25 | 29-MAY-10:30 | 2017.72 | 01-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 954.13 | 11-JUN-15:05 | 1764.39 | 02-JUN-04:59 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 464.85 | 02-JUL-11:20 | 871.11 | 09-JUL-20:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.18 | 13-AUG-13:20 | 1054.20 | 06-AUG-09:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 585.53 | 17-SEP-11:40 | 1830.67 | 24-SEP-17:22 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2699.05 | 24-OCT-04:50 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 6530.20 | 20-NOV-22:01 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 9828.66 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 871.11 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 954.13 | 9828.66 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 8217.58 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 8217.58 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 8217.58 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 8217.58 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 8217.58 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 8217.58 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 8217.58 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 8217.58 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 8217.58 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 8217.58 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 8217.58 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 8217.58 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 8217.58 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 8217.58 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 9443.57 | 29-JAN-10:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 6589.79 | 10-FEB-22:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 5730.68 | 12-MAR-15:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 800.38 | 15-APR-17:01 | 4508.40 | 02-APR-23:51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.46 | 31-MAY-13:00 | 2873.07 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1035.68 | 11-JUN-14:51 | 2354.95 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.90 | 02-JUL-15:10 | 918.02 | 09-JUL-20:51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.52 | 04-AUG-16:40 | 1306.25 | 06-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 354.78 | 17-SEP-15:00 | 2063.36 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 3330.40 | 24-OCT-04:51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 7180.66 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 11599.50 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 918.02 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1035.68 | 11599.50 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 16238.12 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 11626.11 | 10-FEB-22:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 9509.13 | 12-MAR-15:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1618.45 | 15-APR-17:01 | 7273.66 | 02-APR-23:51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.53 | 31-MAY-13:00 | 4895.58 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1965.75 | 11-JUN-15:00 | 4186.04 | 02-JUN-04:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 689.39 | 02-JUL-16:00 | 1566.83 | 09-JUL-20:51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.99 | 04-AUG-16:40 | 2214.93 | 06-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 786.08 | 17-SEP-14:51 | 3559.83 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 5534.03 | 24-OCT-04:51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 12222.71 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 19907.30 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1566.83 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1965.75 | 19907.30 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 17437.46 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 12583.11 | 10-FEB-22:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 9748.92 | 20-MAR-21:01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1479.91 | 15-APR-17:10 | 6864.17 | 02-APR-23:51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.99 | 31-MAY-13:00 | 4576.31 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.84 | 18-JUN-16:00 | 3907.76 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.77 | 25-JUL-21:02 | 1748.91 | 09-JUL-12:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.77 | 04-AUG-16:30 | 2406.23 | 06-AUG-13:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.52 | 10-SEP-15:00 | 3339.53 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 5207.12 | 24-OCT-04:51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 13654.78 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 20366.00 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1748.91 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.84 | 20366.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 124702.25 | 14-JAN-06:01 | 12566.58 | 22668.17 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 123244.69 | 24-FEB-06:01 | 17952.25 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 120310.84 | 25-MAR-05:01 | 17952.25 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 113138.40 | 19-APR-13:24 | 89161.06 | 145723.95 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 125089.30 | 18-MAY-05:02 | 8976.13 | 16191.55 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 133453.03 | 19-JUN-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 121305.34 | 24-JUL-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 122927.14 | 07-AUG-04:12 | 0.00 | 19429.86 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 133566.64 | 27-SEP-04:11 | 0.00 | 29144.79 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 137659.95 | 23-OCT-03:01 | 0.00 | 16191.55 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 135351.93 | 01-NOV-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 112070.72 | 04-DEC-05:01 | 0.00 | 22668.17 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 112070.72 | 0.00 | 16191.55 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 137659.95 | 89161.06 | 145723.95 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 35261.86 | 13-JAN-16:55 | 30632.53 | 52348.14 | 34413.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 97582.52 | 25-FEB-06:01 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 106365.89 | 30-MAR-05:01 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 112600.27 | 17-APR-04:11 | 0.00 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 111408.00 | 30-MAY-04:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 115990.49 | 28-JUN-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 116389.55 | 19-JUL-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 117402.96 | 15-AUG-04:11 | 0.00 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 115726.76 | 01-SEP-04:11 | 0.00 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 109575.37 | 11-OCT-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 109538.13 | 08-NOV-05:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 42223.81 | 05-DEC-16:15 | 61265.06 | 104696.28 | 68826.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 35261.86 | 0.00 | 17449.38 | 34413.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 117402.96 | 61265.06 | 104696.28 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 28456.77 | 13-JAN-16:55 | 30632.53 | 52348.14 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 29143.87 | 24-FEB-16:52 | 122530.12 | 209392.56 | 137652.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 89702.57 | 24-MAR-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 98619.05 | 17-APR-05:01 | 12897.91 | 23265.84 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 102298.75 | 13-MAY-05:01 | 14510.15 | 26174.07 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 107596.43 | 29-JUN-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 105790.21 | 01-JUL-04:11 | 0.00 | 14541.15 | 44532.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 102745.07 | 11-AUG-04:11 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 103697.97 | 08-SEP-04:11 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 94961.42 | 21-OCT-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 94464.67 | 09-NOV-06:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 25689.96 | 07-DEC-16:53 | 61265.06 | 104696.28 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 25689.96 | 0.00 | 14541.15 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 107596.43 | 122530.12 | 209392.56 | 137652.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 23505.48 | 13-JAN-17:00 | 30632.53 | 52348.14 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25549.76 | 24-FEB-17:00 | 122530.12 | 209392.56 | 137652.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 32688.99 | 24-MAR-15:53 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 53703.53 | 18-APR-15:50 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 91174.43 | 31-MAY-05:02 | 8061.19 | 14541.15 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 129304.36 | 14-JUN-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 122374.22 | 28-JUL-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 129417.28 | 03-AUG-04:01 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 121041.59 | 12-SEP-05:02 | 9673.43 | 17449.38 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36144.59 | 20-OCT-16:00 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32269.58 | 03-NOV-15:53 | 61265.06 | 104696.28 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23143.19 | 01-DEC-16:30 | 61265.06 | 104696.28 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 23143.19 | 0.00 | 14541.15 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 129417.28 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3826.02 | 13-JAN-14:20 | 4021.58 | 6572.83 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.98 |
February | 4241.87 | 24-FEB-15:30 | 15384.88 | 26291.33 | 17284.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.89 |
March | 6411.26 | 19-MAR-13:21 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.58 |
April | 10964.84 | 18-APR-15:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 92.16 | 0.00 |
May | 10904.01 | 31-MAY-14:50 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 55.84 | 0.00 |
June | 19433.48 | 25-JUN-18:31 | 0.00 | 1643.21 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 180.65 | 0.00 |
July | 12187.37 | 03-JUL-13:40 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 | 0.00 |
August | 12610.50 | 04-AUG-15:20 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 74.41 | 0.00 |
September | 14441.78 | 11-SEP-04:11 | 0.00 | 2556.10 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.13 |
October | 6453.39 | 01-OCT-14:51 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.69 |
November | 6335.99 | 09-NOV-06:02 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.04 |
December | 3577.10 | 01-DEC-06:03 | 1417.03 | 2556.10 | 6721.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3577.10 | 0.00 | 1643.21 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19433.48 | 15384.88 | 26291.33 | 17284.41 | 0.00 | 0.00 | 0.00 | 0.00 | 180.65 | 355.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3999.50 | 12-JAN-10:13 | 3887.49 | 6353.67 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.43 |
February | 6236.30 | 24-FEB-09:31 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.98 |
March | 9382.68 | 28-MAR-09:03 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.05 |
April | 26246.06 | 30-APR-08:32 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.14 |
May | 28737.87 | 29-MAY-09:01 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.00 |
June | 32153.56 | 25-JUN-07:51 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.37 |
July | 33138.61 | 02-JUL-08:41 | 587.05 | 1058.95 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.80 |
August | 30598.39 | 27-AUG-09:11 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.31 |
September | 21256.85 | 04-SEP-08:52 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.68 |
October | 10541.53 | 01-OCT-08:48 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.91 |
November | 5650.48 | 09-NOV-05:11 | 0.00 | 2353.21 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.70 |
December | 4242.75 | 05-DEC-09:40 | 4957.30 | 8471.56 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3999.50 | 0.00 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.00 | |
Maximum of Months | 33138.61 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15112.47 | 12-JAN-12:30 | 1058.33 | 3286.49 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.21 |
February | 19931.08 | 24-FEB-13:23 | 15385.22 | 26291.90 | 17284.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.75 |
March | 33268.89 | 19-MAR-12:41 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 585.51 |
April | 34708.58 | 16-APR-11:32 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.33 |
May | 23478.78 | 29-MAY-12:22 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.07 |
June | 34592.98 | 25-JUN-13:51 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 269.37 | 0.00 |
July | 34307.85 | 02-JUL-12:42 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 37.45 | 0.00 |
August | 25063.17 | 13-AUG-11:21 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.95 |
September | 34678.20 | 10-SEP-14:31 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.74 |
October | 35982.21 | 29-OCT-13:21 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.20 |
November | 32885.93 | 12-NOV-12:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.53 |
December | 25795.94 | 03-DEC-13:12 | 506.09 | 912.91 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1581.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15112.47 | 506.09 | 912.91 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35982.21 | 15385.22 | 26291.90 | 17284.68 | 0.00 | 0.00 | 0.00 | 0.00 | 269.37 | 1581.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5895.14 | 12-JAN-15:40 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.57 |
February | 10002.01 | 24-FEB-16:21 | 9914.60 | 16943.13 | 11138.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.92 |
March | 11733.17 | 19-MAR-16:03 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.49 |
April | 42036.42 | 16-APR-16:11 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.10 |
May | 38508.26 | 21-MAY-16:21 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.83 |
June | 42746.18 | 25-JUN-17:11 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 65.02 | 0.00 |
July | 43262.52 | 02-JUL-16:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.23 |
August | 36780.93 | 13-AUG-16:01 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.15 |
September | 33277.80 | 10-SEP-14:31 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 22.72 | 0.00 |
October | 33610.45 | 01-OCT-16:11 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.86 |
November | 10982.92 | 03-NOV-15:23 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.43 |
December | 6675.82 | 01-DEC-15:23 | 4957.30 | 8471.56 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5895.14 | 0.00 | 823.62 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43262.52 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 65.02 | 311.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5030.61 | 11-JAN-06:04 | 1619.46 | 2921.26 | 7681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441.47 |
February | 4846.95 | 14-FEB-06:04 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.25 |
March | 5865.50 | 28-MAR-15:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.24 |
April | 10094.88 | 16-APR-16:21 | 708.51 | 1278.05 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 910.64 | 0.00 |
May | 10423.22 | 31-MAY-15:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 130.70 | 0.00 |
June | 11850.11 | 26-JUN-14:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 149.11 | 0.00 |
July | 10956.37 | 26-JUL-15:20 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 118.70 | 0.00 |
August | 11834.59 | 04-AUG-15:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 172.58 | 0.00 |
September | 10265.69 | 11-SEP-14:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 186.12 | 0.00 |
October | 7136.14 | 01-OCT-15:01 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.88 |
November | 6805.14 | 08-NOV-06:01 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.16 |
December | 5075.71 | 30-DEC-06:03 | 1821.89 | 3286.42 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4846.95 | 708.51 | 1278.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11850.11 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 910.64 | 487.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4631.78 | 12-JAN-11:02 | 4957.30 | 8471.56 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.31 |
February | 13105.47 | 24-FEB-11:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.31 |
March | 17504.61 | 28-MAR-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.20 |
April | 21095.39 | 30-APR-09:02 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.62 |
May | 29725.76 | 14-MAY-08:52 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.77 |
June | 31266.32 | 25-JUN-09:22 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.38 |
July | 34218.91 | 30-JUL-09:21 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.38 |
August | 32132.56 | 20-AUG-09:01 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.62 |
September | 30732.21 | 04-SEP-08:41 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.44 |
October | 14534.15 | 20-OCT-10:01 | 8675.28 | 14825.24 | 9746.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.36 |
November | 12878.08 | 04-NOV-10:01 | 3913.66 | 7059.64 | 7735.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.64 |
December | 4175.53 | 01-DEC-11:02 | 4957.30 | 8471.56 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 527.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4175.53 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.38 | |
Maximum of Months | 34218.91 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 527.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15509.83 | 12-JAN-12:40 | 1058.33 | 3286.49 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.98 |
February | 22012.65 | 24-FEB-13:32 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.89 |
March | 31658.92 | 19-MAR-13:11 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1391.28 |
April | 31983.54 | 16-APR-13:42 | 506.09 | 912.91 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 102.75 | 0.00 |
May | 18089.69 | 30-MAY-13:30 | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 42.56 | 0.00 |
June | 18772.75 | 30-JUN-13:10 | 4021.67 | 6572.98 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 74.95 | 0.00 |
July | 41232.62 | 30-JUL-14:01 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 0.00 |
August | 41695.74 | 13-AUG-13:11 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.69 |
September | 45539.79 | 17-SEP-14:21 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.54 |
October | 45667.80 | 01-OCT-13:41 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1266.06 |
November | 23460.94 | 03-NOV-13:30 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.24 |
December | 17778.94 | 01-DEC-13:23 | 7692.61 | 13145.95 | 8642.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 590.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15509.83 | 506.09 | 912.91 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45667.80 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 102.75 | 1391.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4800.69 | 12-JAN-15:50 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.82 |
February | 7963.85 | 24-FEB-16:22 | 9914.60 | 16943.13 | 11138.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.92 |
March | 8097.71 | 23-MAR-15:53 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.01 |
April | 33692.38 | 16-APR-16:21 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 155.59 | 0.00 |
May | 37022.61 | 14-MAY-17:01 | 0.00 | 1058.95 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.78 |
June | 35576.87 | 25-JUN-16:41 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 396.86 | 0.00 |
July | 35100.77 | 02-JUL-16:51 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 55.80 | 0.00 |
August | 34563.85 | 13-AUG-16:31 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.02 |
September | 35604.67 | 04-SEP-17:21 | 0.00 | 941.28 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.46 |
October | 12018.06 | 20-OCT-15:30 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.43 |
November | 8206.86 | 03-NOV-15:22 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.93 |
December | 4801.17 | 01-DEC-15:40 | 4957.30 | 8471.56 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4800.69 | 0.00 | 823.62 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37022.61 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 396.86 | 414.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5577.65 | 14-JAN-17:01 | 809.73 | 1460.63 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1006.47 |
February | 6612.02 | 25-FEB-06:03 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.32 |
March | 6865.74 | 28-MAR-15:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.59 |
April | 13199.80 | 16-APR-16:21 | 708.51 | 1278.05 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1095.09 | 0.00 |
May | 11774.72 | 31-MAY-15:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 159.27 | 0.00 |
June | 15668.61 | 25-JUN-17:41 | 0.00 | 1825.79 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 854.67 | 0.00 |
July | 14591.60 | 02-JUL-17:51 | 0.00 | 1825.79 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 345.69 | 0.00 |
August | 13336.83 | 04-AUG-15:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 211.89 | 0.00 |
September | 12929.57 | 17-SEP-14:11 | 809.73 | 1460.63 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 693.67 | 0.00 |
October | 7543.60 | 01-OCT-14:31 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.09 |
November | 6715.94 | 07-NOV-06:02 | 1619.46 | 2921.26 | 7681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.78 |
December | 5678.74 | 02-DEC-17:01 | 708.51 | 1278.05 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5577.65 | 0.00 | 1278.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15668.61 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 1095.09 | 1006.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3614.55 | 14-JAN-17:01 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 670.99 |
February | 4960.29 | 24-FEB-10:20 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.74 |
March | 6049.79 | 28-MAR-10:00 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543.46 |
April | 14432.81 | 18-APR-09:40 | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 20.46 | 0.00 |
May | 23119.46 | 29-MAY-09:01 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.40 |
June | 38743.01 | 25-JUN-08:21 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.63 |
July | 36759.21 | 02-JUL-07:51 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.33 |
August | 28460.75 | 27-AUG-09:21 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.18 |
September | 18182.84 | 03-SEP-09:52 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 782.05 |
October | 6171.41 | 01-OCT-13:51 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.16 |
November | 4562.45 | 03-NOV-10:36 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.57 |
December | 3690.30 | 02-DEC-17:01 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3614.55 | 391.37 | 705.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38743.01 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 20.46 | 782.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13051.41 | 12-JAN-12:40 | 1058.33 | 3286.49 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526.52 |
February | 20843.89 | 24-FEB-13:43 | 13462.06 | 23005.41 | 15124.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.66 |
March | 18596.32 | 24-MAR-13:32 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 681.11 |
April | 29309.51 | 16-APR-13:42 | 506.09 | 912.91 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 109.64 | 0.00 |
May | 19599.75 | 30-MAY-13:30 | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 50.62 | 0.00 |
June | 52955.55 | 25-JUN-14:21 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 859.99 | 0.00 |
July | 48975.01 | 02-JUL-14:31 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 267.17 | 0.00 |
August | 42996.93 | 13-AUG-13:11 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.25 |
September | 57722.24 | 17-SEP-13:31 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.67 |
October | 52768.46 | 01-OCT-13:51 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1304.25 |
November | 22461.04 | 03-NOV-13:22 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.17 |
December | 15757.47 | 01-DEC-13:23 | 7692.61 | 13145.95 | 8642.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 736.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13051.41 | 506.09 | 912.91 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57722.24 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 859.99 | 1304.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4882.98 | 12-JAN-15:50 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.21 |
February | 7717.33 | 24-FEB-16:24 | 9914.60 | 16943.13 | 11138.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.87 |
March | 7863.95 | 23-MAR-15:51 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.34 |
April | 36874.77 | 16-APR-16:21 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 177.45 | 0.00 |
May | 32141.97 | 14-MAY-16:32 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.67 |
June | 44624.61 | 25-JUN-17:01 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 116.03 | 0.00 |
July | 43671.98 | 02-JUL-17:11 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.66 |
August | 37653.38 | 13-AUG-16:31 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.06 |
September | 38167.72 | 04-SEP-17:21 | 0.00 | 941.28 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.88 |
October | 12221.42 | 20-OCT-15:30 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.01 |
November | 7874.93 | 03-NOV-15:22 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.50 |
December | 4842.76 | 01-DEC-15:40 | 4957.30 | 8471.56 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4842.76 | 0.00 | 705.96 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44624.61 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 177.45 | 506.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19776.40 | 06-JAN-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2810.51 |
February | 17785.30 | 04-FEB-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1804.69 |
March | 12217.35 | 06-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3849.84 |
April | 11471.02 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3073.22 |
May | 9225.22 | 06-MAY-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.35 |
June | 9728.24 | 26-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.86 | 0.00 |
July | 10129.68 | 31-JUL-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.12 |
August | 10579.10 | 14-AUG-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.17 |
September | 10721.95 | 09-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.86 |
October | 11254.10 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.36 |
November | 17211.05 | 26-NOV-02:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4211.01 |
December | 19070.09 | 09-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7549.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9225.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19776.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.86 | 7549.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20726.82 | 06-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4892.36 |
February | 23207.85 | 18-FEB-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2815.47 |
March | 22385.37 | 21-MAR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8641.24 |
April | 18800.28 | 22-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2748.26 |
May | 15396.50 | 02-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3887.66 |
June | 10159.42 | 22-JUN-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.16 |
July | 10473.61 | 06-JUL-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.85 |
August | 10640.02 | 30-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.86 |
September | 18396.41 | 30-SEP-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2850.27 |
October | 17940.54 | 27-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2809.23 |
November | 20907.71 | 10-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7836.61 |
December | 26715.49 | 09-DEC-02:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17420.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 10159.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.85 | |
Maximum of Months | 26715.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17420.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 677.57 | 13-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1043.45 |
February | 6389.05 | 24-FEB-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 694.48 |
March | 14243.29 | 19-MAR-13:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1601.09 |
April | 27152.02 | 18-APR-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.74 | 0.00 |
May | 31668.28 | 31-MAY-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.21 | 0.00 |
June | 35257.58 | 30-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.78 | 0.00 |
July | 34028.23 | 05-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 0.00 |
August | 34891.45 | 04-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.06 | 0.00 |
September | 33068.34 | 07-SEP-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.70 | 0.00 |
October | 15603.56 | 20-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.14 |
November | 9167.18 | 03-NOV-13:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.04 |
December | 134.55 | 03-DEC-14:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4140.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 134.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35257.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.06 | 4140.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6798.01 | 30-JAN-13:01 | 2221.41 | 7287.84 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10396.54 | 04-FEB-10:31 | 733.48 | 2429.28 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6618.61 | 31-MAR-23:47 | 0.00 | 121.46 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8329.20 | 16-APR-17:57 | 0.00 | 121.46 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3461.20 | 31-MAY-23:51 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5369.73 | 30-JUN-23:51 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7255.02 | 31-JUL-24:00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8484.50 | 29-AUG-17:40 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2843.58 | 30-SEP-23:51 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4730.37 | 31-OCT-23:52 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9904.18 | 26-NOV-08:11 | 116.92 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7867.82 | 01-DEC-16:03 | 888.56 | 2915.14 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2843.58 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10396.54 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1800.11 | 12-JAN-16:40 | 222.14 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9982.48 | 04-FEB-10:31 | 733.48 | 2429.28 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5963.77 | 31-MAR-23:12 | 0.00 | 364.39 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7852.62 | 15-APR-18:10 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3267.67 | 31-MAY-23:40 | 0.00 | 40.49 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5200.13 | 30-JUN-23:51 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6778.70 | 31-JUL-24:00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8127.41 | 29-AUG-17:40 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2554.22 | 01-SEP-17:50 | 23.38 | 242.93 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4228.77 | 11-OCT-16:52 | 701.50 | 4048.80 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9354.19 | 26-NOV-08:11 | 116.92 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7292.86 | 01-DEC-16:03 | 888.56 | 2915.14 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1800.11 | 0.00 | 40.49 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9982.48 | 888.56 | 4048.80 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1586.17 | 12-JAN-16:40 | 222.14 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8266.63 | 04-FEB-10:31 | 733.48 | 2429.28 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5724.66 | 21-MAR-17:32 | 233.83 | 2429.28 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8020.34 | 16-APR-17:57 | 0.00 | 121.46 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3147.02 | 31-MAY-23:20 | 0.00 | 40.49 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5093.88 | 30-JUN-23:30 | 0.00 | 40.49 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6512.29 | 31-JUL-23:50 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8229.25 | 29-AUG-17:40 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2652.94 | 01-SEP-17:40 | 23.38 | 242.93 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4220.85 | 11-OCT-16:41 | 701.50 | 4048.80 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9246.42 | 26-NOV-08:11 | 116.92 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7031.56 | 01-DEC-16:03 | 888.56 | 2915.14 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1586.17 | 0.00 | 40.49 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9246.42 | 888.56 | 4048.80 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 95031.73 | 18-JAN-13:01 | 48086.79 | 82175.84 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 484674.86 | 01-FEB-00:12 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 521666.13 | 24-MAR-15:52 | 48086.79 | 82175.84 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 490466.75 | 19-APR-09:42 | 50279.21 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 466173.84 | 31-MAY-23:56 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 487183.82 | 03-JUN-02:22 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 488467.29 | 24-JUL-02:52 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 496623.96 | 06-AUG-19:34 | 0.00 | 4565.32 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 481570.91 | 30-SEP-23:12 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 510496.12 | 31-OCT-23:53 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 517651.82 | 01-NOV-02:42 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 486450.79 | 13-DEC-13:04 | 48086.79 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 95031.73 | 0.00 | 4565.32 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 521666.13 | 50279.21 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.194125E+13 | 1411334.87 | 13-JAN-16:49 | 0.211102E+13 | 3142160.44 | 30-JAN-07:30 |
February | 0.213091E+13 | 1546355.86 | 10-FEB-16:10 | 0.132262E+13 | 2952795.65 | 02-FEB-07:30 |
March | 0.286958E+13 | 1884423.17 | 24-MAR-14:09 | 0.729913E+12 | 2224171.88 | 06-MAR-05:10 |
April | 0.310537E+13 | 2342252.82 | 18-APR-15:09 | 0.303491E+12 | 1530995.70 | 03-APR-05:10 |
May | 0.201438E+13 | 1920782.27 | 31-MAY-15:09 | 0.522952E+11 | 946584.36 | 02-MAY-04:19 |
June | 0.255638E+13 | 2103830.87 | 30-JUN-15:20 | 0.176633E+11 | 605771.10 | 02-JUN-05:10 |
July | 0.304160E+13 | 2283152.47 | 26-JUL-15:09 | 0.223742E+10 | 114833.67 | 24-JUL-05:10 |
August | 0.353133E+13 | 2520439.57 | 04-AUG-15:30 | 0.682291E+10 | 271304.58 | 07-AUG-05:10 |
September | 0.199616E+13 | 1955108.29 | 06-SEP-15:09 | 0.847214E+11 | 990306.41 | 30-SEP-04:10 |
October | 0.233109E+13 | 1791039.00 | 20-OCT-15:09 | 0.247987E+12 | 1292711.53 | 16-OCT-04:19 |
November | 0.273841E+13 | 1870211.36 | 03-NOV-14:09 | 0.806248E+12 | 2301408.96 | 27-NOV-05:10 |
December | 0.326027E+13 | 1944767.24 | 21-DEC-16:00 | 0.148851E+13 | 2628534.69 | 11-DEC-07:19 |
Annual Sum or Average | 0.315167E+14 | 0.717353E+13 | ||||
Minimum of Months | 0.194125E+13 | 1411334.87 | 0.223742E+10 | 114833.67 | ||
Maximum of Months | 0.353133E+13 | 2520439.57 | 0.211102E+13 | 3142160.44 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.468149E+12 | 0.106275E+12 | 0.766053E+12 | 0.218140E+12 | 0.217220E+12 | 0.188885E+11 | 0.00 | 0.605601E+10 | 0.00 | 0.956652E+11 | 0.00 | 0.448078E+11 | 0.00 |
February | 0.424646E+12 | 0.885496E+11 | 0.978954E+12 | 0.199667E+12 | 0.204177E+12 | 0.368794E+11 | 0.00 | 0.553881E+11 | 536429.58 | 0.101147E+12 | 0.00 | 0.415063E+11 | 0.00 |
March | 0.504598E+12 | 0.877422E+11 | 0.141687E+13 | 0.230864E+12 | 0.230426E+12 | 0.967965E+11 | 0.00 | 0.984368E+11 | 43747488.51 | 0.155483E+12 | 0.00 | 0.483130E+11 | 0.00 |
April | 0.450709E+12 | 0.743617E+11 | 0.165903E+13 | 0.216144E+12 | 0.255042E+12 | 0.103474E+12 | 0.00 | 0.143128E+12 | 0.548371E+10 | 0.155814E+12 | 0.00 | 0.421876E+11 | 0.00 |
May | 0.486374E+12 | 0.676330E+11 | 0.774844E+12 | 0.224502E+12 | 0.215789E+12 | 0.532724E+11 | 0.00 | 0.111152E+12 | 0.828423E+10 | 0.300785E+11 | 0.00 | 0.424529E+11 | 0.00 |
June | 0.484022E+12 | 0.608274E+11 | 0.106252E+13 | 0.222585E+12 | 0.256422E+12 | 0.964670E+11 | 0.00 | 0.295994E+12 | 0.370735E+11 | 0.115680E+10 | 0.00 | 0.393094E+11 | 0.00 |
July | 0.453060E+12 | 0.648262E+11 | 0.139340E+13 | 0.218061E+12 | 0.286446E+12 | 0.134590E+12 | 0.00 | 0.399126E+12 | 0.563215E+11 | 0.406189E+09 | 0.00 | 0.353631E+11 | 0.00 |
August | 0.504598E+12 | 0.727852E+11 | 0.173200E+13 | 0.230864E+12 | 0.318629E+12 | 0.144022E+12 | 0.00 | 0.431333E+12 | 0.555318E+11 | 0.387331E+10 | 0.00 | 0.376926E+11 | 0.00 |
September | 0.450709E+12 | 0.802060E+11 | 0.740713E+12 | 0.216143E+12 | 0.222737E+12 | 0.579105E+11 | 0.00 | 0.146147E+12 | 0.135503E+11 | 0.333688E+11 | 0.00 | 0.346697E+11 | 0.00 |
October | 0.468149E+12 | 0.937788E+11 | 0.108340E+13 | 0.218140E+12 | 0.213680E+12 | 0.430041E+11 | 0.00 | 0.849705E+11 | 0.429446E+09 | 0.880261E+11 | 0.00 | 0.375117E+11 | 0.00 |
November | 0.462662E+12 | 0.100161E+12 | 0.135889E+13 | 0.209941E+12 | 0.225367E+12 | 0.111315E+12 | 0.00 | 0.878474E+11 | 30181880.84 | 0.142918E+12 | 0.00 | 0.392732E+11 | 0.00 |
December | 0.453060E+12 | 0.108851E+12 | 0.170972E+13 | 0.218060E+12 | 0.266226E+12 | 0.111692E+12 | 0.00 | 0.105851E+12 | 71270.49 | 0.245132E+12 | 0.00 | 0.416784E+11 | 0.00 |
Annual Sum or Average | 0.561074E+13 | 0.100600E+13 | 0.146764E+14 | 0.262311E+13 | 0.291216E+13 | 0.100831E+13 | 0.00 | 0.196543E+13 | 0.176749E+12 | 0.105307E+13 | 0.00 | 0.484766E+12 | 0.00 |
Minimum of Months | 0.424646E+12 | 0.608274E+11 | 0.740713E+12 | 0.199667E+12 | 0.204177E+12 | 0.188885E+11 | 0.00 | 0.605601E+10 | 0.00 | 0.406189E+09 | 0.00 | 0.346697E+11 | 0.00 |
Maximum of Months | 0.504598E+12 | 0.108851E+12 | 0.173200E+13 | 0.230864E+12 | 0.318629E+12 | 0.144022E+12 | 0.00 | 0.431333E+12 | 0.563215E+11 | 0.245132E+12 | 0.00 | 0.483130E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.211102E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.132262E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.729913E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.303491E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.522952E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.176633E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.223742E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.682291E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.847214E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.247987E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.806248E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.148851E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.717353E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.223742E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.211102E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 489900.85 | 02-JAN-08:09 | 64082.80 | 01-JAN-00:10 | 423497.50 | 02-JAN-08:09 | 235096.12 | 02-JAN-08:20 | 149711.72 | 30-JAN-05:10 | 47998.42 | 09-JAN-05:49 | 0.00 | 01-JAN-00:10 |
February | 489900.85 | 01-FEB-08:09 | 64082.80 | 01-FEB-00:10 | 541788.89 | 01-FEB-08:09 | 235096.12 | 01-FEB-08:20 | 151203.03 | 06-FEB-06:10 | 47113.70 | 08-FEB-13:30 | 0.00 | 01-FEB-00:10 |
March | 489900.85 | 01-MAR-08:09 | 64082.80 | 01-MAR-00:10 | 660080.29 | 01-MAR-08:09 | 235096.12 | 01-MAR-08:20 | 184912.85 | 24-MAR-14:09 | 48978.55 | 28-MAR-14:39 | 0.00 | 01-MAR-00:10 |
April | 489900.85 | 03-APR-07:10 | 64082.80 | 01-APR-00:10 | 778371.69 | 03-APR-07:10 | 235096.12 | 03-APR-07:19 | 259233.09 | 18-APR-14:00 | 99137.04 | 18-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 489900.85 | 01-MAY-07:10 | 64082.80 | 01-MAY-00:10 | 423497.50 | 01-MAY-07:10 | 235096.12 | 01-MAY-07:19 | 239428.74 | 31-MAY-14:00 | 97982.74 | 31-MAY-14:30 | 0.00 | 01-MAY-00:10 |
June | 489900.85 | 01-JUN-07:10 | 64082.80 | 01-JUN-00:10 | 541788.89 | 01-JUN-07:10 | 235096.12 | 01-JUN-07:19 | 267693.67 | 30-JUN-15:20 | 99028.39 | 27-JUN-14:09 | 0.00 | 01-JUN-00:10 |
July | 489900.85 | 03-JUL-07:10 | 64082.80 | 01-JUL-00:10 | 660080.29 | 03-JUL-07:10 | 235096.12 | 03-JUL-07:19 | 257378.41 | 05-JUL-15:39 | 100616.03 | 26-JUL-14:00 | 0.00 | 01-JUL-00:10 |
August | 489900.85 | 01-AUG-07:10 | 64082.80 | 01-AUG-00:10 | 778371.69 | 01-AUG-07:10 | 235096.12 | 01-AUG-07:19 | 305773.99 | 04-AUG-15:30 | 102278.78 | 04-AUG-15:30 | 0.00 | 01-AUG-00:10 |
September | 489900.85 | 01-SEP-07:10 | 64082.80 | 01-SEP-00:10 | 423497.50 | 01-SEP-07:10 | 235096.12 | 01-SEP-07:19 | 275387.60 | 07-SEP-15:20 | 99617.76 | 01-SEP-14:30 | 0.00 | 01-SEP-00:10 |
October | 489900.85 | 02-OCT-07:10 | 64082.80 | 01-OCT-00:10 | 541788.89 | 02-OCT-07:10 | 235096.12 | 02-OCT-07:19 | 205058.12 | 20-OCT-14:00 | 52607.83 | 20-OCT-12:00 | 0.00 | 01-OCT-00:10 |
November | 489900.85 | 01-NOV-07:10 | 64082.80 | 01-NOV-00:10 | 660080.29 | 01-NOV-07:10 | 235096.12 | 01-NOV-07:19 | 202982.74 | 03-NOV-14:30 | 50910.09 | 03-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 489900.85 | 01-DEC-08:09 | 64082.80 | 01-DEC-00:10 | 778371.69 | 01-DEC-08:09 | 235096.12 | 01-DEC-08:20 | 160760.10 | 11-DEC-05:10 | 51119.68 | 11-DEC-05:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 489900.85 | 64082.80 | 423497.50 | 235096.12 | 149711.72 | 47113.70 | 0.00 | |||||||
Maximum of Months | 489900.85 | 64082.80 | 778371.69 | 235096.12 | 305773.99 | 102278.78 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 10816.03 | 13-JAN-22:10 | 0.00 | 01-JAN-00:10 | 42402.75 | 14-JAN-14:09 | 0.00 | 60019.34 | 30-JAN-12:00 | 0.00 |
February | 79137.94 | 08-FEB-17:10 | 17.44 | 15-FEB-05:00 | 56954.31 | 09-FEB-14:50 | 0.00 | 60480.04 | 21-FEB-12:30 | 0.00 |
March | 151350.54 | 23-MAR-14:09 | 3061.30 | 19-MAR-15:30 | 100000.00 | 25-MAR-15:20 | 0.00 | 60429.63 | 02-MAR-12:00 | 0.00 |
April | 383202.79 | 18-APR-14:00 | 58522.13 | 15-APR-11:00 | 100000.00 | 01-APR-09:09 | 0.00 | 58465.80 | 03-APR-11:20 | 0.00 |
May | 356725.98 | 30-MAY-14:09 | 58522.13 | 12-MAY-14:20 | 100000.00 | 05-MAY-19:30 | 0.00 | 55773.48 | 01-MAY-11:00 | 0.00 |
June | 382974.25 | 27-JUN-14:09 | 58522.13 | 11-JUN-15:09 | 32804.46 | 03-JUN-03:30 | 0.00 | 52183.01 | 01-JUN-11:30 | 0.00 |
July | 455018.98 | 26-JUL-14:00 | 58522.13 | 03-JUL-07:49 | 82160.22 | 03-JUL-07:40 | 0.00 | 48427.27 | 03-JUL-11:20 | 0.00 |
August | 515044.72 | 04-AUG-15:30 | 58522.13 | 03-AUG-04:30 | 100000.00 | 07-AUG-09:00 | 0.00 | 46612.12 | 01-AUG-11:30 | 0.00 |
September | 371578.73 | 06-SEP-12:09 | 58522.13 | 05-SEP-14:39 | 100000.00 | 23-SEP-12:50 | 0.00 | 47561.67 | 29-SEP-11:30 | 0.00 |
October | 233724.24 | 20-OCT-12:00 | 11838.55 | 20-OCT-14:00 | 68963.25 | 31-OCT-14:00 | 0.00 | 51313.56 | 31-OCT-11:50 | 0.00 |
November | 192434.87 | 03-NOV-13:39 | 4606.37 | 03-NOV-13:50 | 99943.34 | 14-NOV-17:49 | 0.00 | 54641.99 | 30-NOV-12:39 | 0.00 |
December | 91267.33 | 03-DEC-00:40 | 20.45 | 05-DEC-16:10 | 100000.00 | 01-DEC-11:39 | 0.00 | 57639.36 | 27-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 10816.03 | 0.00 | 32804.46 | 0.00 | 46612.12 | 0.00 | ||||
Maximum of Months | 515044.72 | 58522.13 | 100000.00 | 0.00 | 60480.04 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1411334.87 | 13-JAN-16:49 | 489900.85 | 423497.50 | 64082.80 | 235096.12 | 110674.14 | 106.64 | 0.00 | 7948.42 | 0.00 |
February | 1546355.86 | 10-FEB-16:10 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 118808.33 | 46835.47 | 0.00 | 20949.18 | 0.00 |
March | 1884423.17 | 24-MAR-14:09 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 184912.85 | 48776.05 | 0.00 | 150096.84 | 516.91 |
April | 2342252.82 | 18-APR-15:09 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 258401.37 | 99068.02 | 0.00 | 380332.29 | 58522.13 |
May | 1920782.27 | 31-MAY-15:09 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 239133.43 | 97458.79 | 0.00 | 338335.13 | 58522.13 |
June | 2103830.87 | 30-JUN-15:20 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 267693.67 | 98888.61 | 0.00 | 373921.64 | 58522.13 |
July | 2283152.47 | 26-JUL-15:09 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 249844.10 | 100582.76 | 0.00 | 454076.26 | 58522.13 |
August | 2520439.57 | 04-AUG-15:30 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 305773.99 | 102278.78 | 0.00 | 515044.72 | 58522.13 |
September | 1955108.29 | 06-SEP-15:09 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 268448.13 | 98298.56 | 0.00 | 346507.89 | 58522.13 |
October | 1791039.00 | 20-OCT-15:09 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 203941.78 | 52364.37 | 0.00 | 219842.27 | 11519.85 |
November | 1870211.36 | 03-NOV-14:09 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 198127.03 | 50735.52 | 0.00 | 171634.49 | 3870.10 |
December | 1944767.24 | 21-DEC-16:00 | 489900.85 | 778371.69 | 64082.80 | 235096.12 | 120765.18 | 48357.98 | 0.00 | 67806.15 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1411334.87 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 110674.14 | 106.64 | 0.00 | 7948.42 | 0.00 | |
Maximum of Months | 2520439.57 | 489900.85 | 778371.69 | 64082.80 | 235096.12 | 305773.99 | 102278.78 | 0.00 | 515044.72 | 58522.13 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 3142160.44 | 30-JAN-07:30 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 2952795.65 | 02-FEB-07:30 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 2224171.88 | 06-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 1530995.70 | 03-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 946584.36 | 02-MAY-04:19 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 605771.10 | 02-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 114833.67 | 24-JUL-05:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 271304.58 | 07-AUG-05:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 990306.41 | 30-SEP-04:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 1292711.53 | 16-OCT-04:19 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 2301408.96 | 27-NOV-05:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 2628534.69 | 11-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 114833.67 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 3142160.44 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.39 | 0.33 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
February | 0.50 | 20.42 | 0.50 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.58 | 0.00 | 25.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.74 | 0.00 | 25.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.82 | 0.00 | 25.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 26.47 | 0.00 | 26.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.63 | 0.00 | 25.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.69 | 0.00 | 25.69 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 20.40 | 0.83 | 20.40 | 7.83 | 24.99 | 0.00 | 24.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.42 | 0.50 | 20.42 | 2.50 | 26.47 | 0.00 | 26.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 19.28 | 0.33 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Annual Sum or Average | 1.67 | 19.26 | 0.33 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.28 | 0.33 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.33 | 18.10 | 0.50 | 18.21 | 0.00 | 18.21 | 0.00 | 18.21 |
February | 5.67 | 18.36 | 0.33 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
March | 2.17 | 18.38 | 0.17 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 |
April | 0.67 | 18.00 | 0.00 | 18.00 | 0.00 | 18.00 | 0.00 | 18.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.83 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
November | 3.00 | 18.29 | 0.17 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 |
December | 5.67 | 18.36 | 0.33 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
Annual Sum or Average | 26.33 | 18.29 | 1.50 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.33 | 19.26 | 0.50 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.67 | 16.60 | 3.67 | 16.45 | 0.00 | 16.45 | 0.00 | 16.45 |
February | 13.83 | 16.46 | 1.17 | 16.50 | 0.00 | 16.50 | 0.00 | 16.50 |
March | 2.33 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
April | 0.33 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.83 | 17.63 | 0.00 | 17.63 | 0.00 | 17.63 | 0.00 | 17.63 |
December | 10.00 | 16.75 | 1.00 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 |
Annual Sum or Average | 49.00 | 16.76 | 5.83 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 19.67 | 18.93 | 3.67 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.83 | 16.51 | 1.50 | 16.46 | 0.00 | 16.46 | 0.00 | 16.46 |
February | 14.50 | 16.24 | 1.00 | 16.32 | 0.00 | 16.32 | 0.00 | 16.32 |
March | 2.83 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
April | 0.33 | 18.80 | 0.00 | 18.80 | 0.50 | 24.14 | 0.50 | 25.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.86 | 2.50 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.60 | 2.67 | 28.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.49 | 4.33 | 28.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.21 | 1.83 | 28.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.18 | 2.17 | 28.18 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4.00 | 16.91 | 0.33 | 16.76 | 0.00 | 16.76 | 0.00 | 16.76 |
December | 11.33 | 16.75 | 0.83 | 16.76 | 0.00 | 16.76 | 0.00 | 16.76 |
Annual Sum or Average | 50.83 | 16.66 | 3.67 | 16.64 | 14.00 | 19.02 | 14.00 | 20.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.83 | 18.80 | 1.50 | 18.80 | 4.33 | 28.60 | 4.33 | 28.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.50 | 16.67 | 1.33 | 16.67 | 0.00 | 16.67 | 0.00 | 16.67 |
February | 13.50 | 16.49 | 1.00 | 16.55 | 0.00 | 16.55 | 0.00 | 16.55 |
March | 3.33 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
April | 0.50 | 18.07 | 0.00 | 18.07 | 1.50 | 25.67 | 1.50 | 26.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.80 | 2.50 | 27.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.97 | 3.00 | 27.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.72 | 3.00 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.30 | 3.83 | 28.30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.07 | 2.00 | 28.07 |
November | 6.33 | 16.57 | 0.50 | 16.44 | 0.17 | 16.71 | 0.17 | 16.96 |
December | 12.17 | 16.82 | 1.00 | 16.86 | 0.17 | 16.99 | 0.17 | 17.12 |
Annual Sum or Average | 55.33 | 16.78 | 3.83 | 16.78 | 16.17 | 19.19 | 16.17 | 20.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 19.50 | 18.60 | 1.33 | 18.60 | 3.83 | 28.30 | 3.83 | 28.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.50 | 17.65 | 0.17 | 17.69 | 0.00 | 17.69 | 0.00 | 17.69 |
February | 4.17 | 17.96 | 0.00 | 17.96 | 0.00 | 17.96 | 0.00 | 17.96 |
March | 0.50 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.67 | 2.50 | 28.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.35 | 1.83 | 28.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.72 | 3.67 | 28.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.63 | 5.67 | 28.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.10 | 4.33 | 28.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.02 | 3.17 | 28.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.47 | 0.33 | 27.47 |
November | 1.50 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
December | 1.67 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
Annual Sum or Average | 17.33 | 17.93 | 0.17 | 17.95 | 37.83 | 25.12 | 21.50 | 26.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.69 | 0.00 | 17.69 |
Maximum of Months | 9.50 | 19.22 | 0.17 | 19.22 | 12.00 | 28.72 | 5.67 | 28.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 74.83 | 14.91 | 19.83 | 14.85 | 0.00 | 14.85 | 0.00 | 14.85 |
February | 40.00 | 15.39 | 8.67 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 |
March | 19.83 | 16.20 | 3.50 | 16.05 | 0.00 | 16.05 | 0.00 | 16.05 |
April | 4.50 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
May | 0.17 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.33 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
October | 2.50 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
November | 25.00 | 15.48 | 4.50 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
December | 46.50 | 15.15 | 11.50 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 |
Annual Sum or Average | 213.67 | 15.35 | 48.00 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.83 | 19.24 | 19.83 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 125.67 | 16.43 | 18.17 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
February | 59.67 | 16.63 | 6.17 | 16.52 | 0.00 | 16.52 | 0.00 | 16.52 |
March | 24.33 | 17.13 | 1.33 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
April | 7.67 | 18.05 | 0.00 | 18.05 | 0.17 | 18.24 | 0.17 | 18.43 |
May | 0.17 | 19.15 | 0.00 | 19.15 | 2.33 | 27.30 | 2.33 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.64 | 3.17 | 28.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.67 | 4.17 | 28.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.18 | 1.50 | 28.18 |
September | 0.33 | 19.26 | 0.00 | 19.26 | 2.00 | 26.62 | 2.00 | 27.19 |
October | 2.33 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
November | 37.00 | 16.79 | 4.50 | 16.63 | 0.00 | 16.63 | 0.00 | 16.63 |
December | 86.33 | 16.82 | 11.00 | 16.62 | 0.00 | 16.62 | 0.00 | 16.62 |
Annual Sum or Average | 343.50 | 16.71 | 41.17 | 16.54 | 13.33 | 16.93 | 13.33 | 17.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 | 0.00 | 16.23 |
Maximum of Months | 125.67 | 19.26 | 18.17 | 19.26 | 4.17 | 28.67 | 4.17 | 28.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 59.83 | 15.13 | 10.17 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
February | 30.50 | 15.72 | 3.67 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 |
March | 14.33 | 16.79 | 0.83 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
April | 3.67 | 17.00 | 0.00 | 17.00 | 1.33 | 19.95 | 1.33 | 21.66 |
May | 0.17 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.72 | 1.83 | 27.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.94 | 2.17 | 27.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.72 | 1.17 | 27.72 |
September | 0.33 | 19.29 | 0.00 | 19.29 | 3.33 | 27.62 | 3.33 | 28.02 |
October | 1.67 | 19.10 | 0.00 | 19.10 | 1.83 | 23.85 | 1.83 | 25.34 |
November | 20.00 | 15.70 | 3.50 | 15.62 | 0.17 | 15.70 | 0.17 | 15.79 |
December | 36.50 | 15.43 | 7.17 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 |
Annual Sum or Average | 167.00 | 15.61 | 25.33 | 15.57 | 11.83 | 16.29 | 11.83 | 16.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.13 | 0.00 | 15.13 |
Maximum of Months | 59.83 | 19.29 | 10.17 | 19.29 | 3.33 | 27.94 | 3.33 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.33 | 15.02 | 14.33 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 |
February | 30.67 | 15.61 | 5.17 | 15.57 | 0.00 | 15.57 | 0.00 | 15.57 |
March | 15.00 | 16.70 | 1.83 | 16.59 | 0.00 | 16.59 | 0.00 | 16.59 |
April | 3.33 | 17.10 | 0.00 | 17.10 | 2.17 | 21.58 | 1.33 | 22.95 |
May | 0.17 | 19.18 | 0.00 | 19.18 | 2.83 | 27.82 | 1.50 | 28.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.96 | 2.50 | 28.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.70 | 3.50 | 28.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.35 | 1.17 | 28.39 |
September | 0.33 | 19.24 | 0.00 | 19.24 | 2.33 | 26.87 | 1.83 | 27.28 |
October | 1.83 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
November | 18.83 | 15.52 | 3.67 | 15.46 | 0.00 | 15.46 | 0.00 | 15.46 |
December | 35.50 | 15.42 | 7.17 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 |
Annual Sum or Average | 168.00 | 15.52 | 32.17 | 15.43 | 21.83 | 16.73 | 11.83 | 17.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 0.00 | 15.00 |
Maximum of Months | 62.33 | 19.24 | 14.33 | 19.24 | 7.83 | 28.96 | 3.50 | 28.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 90.83 | 14.27 | 26.67 | 14.24 | 0.00 | 14.24 | 0.00 | 14.24 |
February | 66.67 | 14.60 | 17.17 | 14.55 | 0.00 | 14.55 | 0.00 | 14.55 |
March | 32.50 | 15.24 | 4.33 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 |
April | 16.50 | 15.82 | 4.17 | 15.58 | 0.00 | 15.58 | 0.00 | 15.58 |
May | 1.33 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
June | 0.50 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2.00 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
October | 11.67 | 16.76 | 0.67 | 16.66 | 0.00 | 16.66 | 0.00 | 16.66 |
November | 52.50 | 14.76 | 15.33 | 14.69 | 0.00 | 14.69 | 0.00 | 14.69 |
December | 79.67 | 14.51 | 21.00 | 14.47 | 0.00 | 14.47 | 0.00 | 14.47 |
Annual Sum or Average | 354.17 | 14.75 | 89.33 | 14.66 | 0.00 | 14.66 | 0.00 | 14.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.83 | 19.29 | 26.67 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 90.33 | 14.28 | 26.17 | 14.27 | 0.00 | 14.27 | 0.00 | 14.27 |
February | 63.17 | 14.61 | 13.67 | 14.57 | 0.00 | 14.57 | 0.00 | 14.57 |
March | 31.00 | 15.28 | 3.33 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 |
April | 16.33 | 15.79 | 3.33 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 |
May | 1.33 | 19.01 | 0.00 | 19.01 | 0.50 | 21.32 | 0.50 | 22.64 |
June | 0.33 | 19.26 | 0.00 | 19.26 | 4.00 | 27.56 | 4.00 | 27.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.44 | 3.67 | 28.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.41 | 0.83 | 27.41 |
September | 2.00 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
October | 11.17 | 16.84 | 0.50 | 16.76 | 0.00 | 16.76 | 0.00 | 16.76 |
November | 49.17 | 14.75 | 11.33 | 14.69 | 0.00 | 14.69 | 0.00 | 14.69 |
December | 78.50 | 14.54 | 18.83 | 14.51 | 0.00 | 14.51 | 0.00 | 14.51 |
Annual Sum or Average | 343.33 | 14.76 | 77.17 | 14.69 | 9.00 | 14.97 | 9.00 | 15.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 0.00 | 14.27 |
Maximum of Months | 90.33 | 19.26 | 26.17 | 19.26 | 4.00 | 28.44 | 4.00 | 28.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 82.00 | 14.44 | 19.67 | 14.45 | 0.00 | 14.45 | 0.00 | 14.45 |
February | 57.00 | 14.77 | 11.50 | 14.73 | 0.00 | 14.73 | 0.00 | 14.73 |
March | 26.50 | 15.50 | 1.67 | 15.46 | 0.00 | 15.46 | 0.00 | 15.46 |
April | 15.33 | 15.86 | 3.83 | 15.62 | 1.00 | 16.24 | 1.00 | 16.80 |
May | 1.17 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
June | 0.33 | 19.23 | 0.00 | 19.23 | 1.83 | 26.39 | 1.83 | 26.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.87 | 1.67 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.53 | 0.83 | 27.53 |
September | 2.00 | 18.41 | 0.00 | 18.41 | 2.50 | 23.91 | 2.50 | 25.48 |
October | 10.00 | 17.09 | 0.50 | 16.98 | 0.33 | 17.30 | 0.33 | 17.60 |
November | 44.00 | 14.88 | 9.17 | 14.82 | 0.00 | 14.82 | 0.00 | 14.82 |
December | 66.00 | 14.66 | 11.17 | 14.64 | 0.00 | 14.64 | 0.00 | 14.64 |
Annual Sum or Average | 304.33 | 14.91 | 57.50 | 14.85 | 8.17 | 15.14 | 8.17 | 15.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 | 0.00 | 14.45 |
Maximum of Months | 82.00 | 19.23 | 19.67 | 19.23 | 2.50 | 27.87 | 2.50 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 86.33 | 14.43 | 24.17 | 14.41 | 0.00 | 14.41 | 0.00 | 14.41 |
February | 53.17 | 14.82 | 10.50 | 14.76 | 0.00 | 14.76 | 0.00 | 14.76 |
March | 24.67 | 15.60 | 2.50 | 15.51 | 0.00 | 15.51 | 0.00 | 15.51 |
April | 11.00 | 16.12 | 3.00 | 15.86 | 1.67 | 17.24 | 1.00 | 17.95 |
May | 0.83 | 19.06 | 0.00 | 19.06 | 2.67 | 26.10 | 1.50 | 26.71 |
June | 0.33 | 19.34 | 0.00 | 19.34 | 4.67 | 28.52 | 2.67 | 28.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.73 | 3.50 | 28.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.27 | 1.17 | 28.33 |
September | 1.83 | 18.43 | 0.00 | 18.43 | 2.17 | 23.57 | 1.67 | 24.83 |
October | 6.33 | 18.03 | 0.00 | 18.03 | 0.00 | 18.03 | 0.00 | 18.03 |
November | 40.17 | 14.98 | 8.33 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
December | 64.50 | 14.71 | 14.00 | 14.66 | 0.00 | 14.66 | 0.00 | 14.66 |
Annual Sum or Average | 289.17 | 14.93 | 62.50 | 14.84 | 21.67 | 15.64 | 11.50 | 16.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.41 | 0.00 | 14.41 |
Maximum of Months | 86.33 | 19.34 | 24.17 | 19.34 | 8.17 | 28.73 | 3.50 | 28.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 48.83 | 28.85 | 29.83 | 28.85 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 81.83 | 33.32 | 58.50 | 33.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 35.69 | 2.33 | 35.83 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 136.17 | 31.81 | 90.67 | 31.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 81.83 | 35.69 | 58.50 | 35.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 28.03 | 7.67 | 28.08 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 81.83 | 32.25 | 58.50 | 32.37 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 33.13 | 2.33 | 33.26 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 97.67 | 31.86 | 68.50 | 31.95 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 81.83 | 33.13 | 58.50 | 33.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.30 | 1.83 | 28.30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 81.83 | 30.26 | 58.50 | 30.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 30.45 | 2.17 | 30.55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 89.00 | 30.23 | 62.50 | 30.46 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 81.83 | 30.45 | 58.50 | 30.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.67 | 0.50 | 27.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.07 | 2.33 | 28.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.83 | 28.00 | 2.83 | 28.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.07 | 2.33 | 28.07 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 488.67 | 22.08 | 5.83 | 22.06 | 5.83 | 22.04 |
February | 437.83 | 22.66 | 25.17 | 22.56 | 25.17 | 22.47 |
March | 434.00 | 23.24 | 6.17 | 23.27 | 0.00 | 23.27 |
April | 293.67 | 23.61 | 56.00 | 23.78 | 0.00 | 23.78 |
May | 118.67 | 23.55 | 219.33 | 24.20 | 0.67 | 24.20 |
June | 2.17 | 23.79 | 391.50 | 24.45 | 0.33 | 24.45 |
July | 5.17 | 24.00 | 493.17 | 24.54 | 5.17 | 24.53 |
August | 2.83 | 25.76 | 502.17 | 24.47 | 2.83 | 24.48 |
September | 81.83 | 23.55 | 261.33 | 24.58 | 0.00 | 24.58 |
October | 118.83 | 23.81 | 126.17 | 24.76 | 0.00 | 24.76 |
November | 221.17 | 23.43 | 97.83 | 23.98 | 0.00 | 23.98 |
December | 450.17 | 23.19 | 5.17 | 23.21 | 0.67 | 23.20 |
Annual Sum or Average | 2655.00 | 23.03 | 2189.83 | 23.74 | 40.67 | 23.72 |
Minimum of Months | 2.17 | 22.08 | 5.17 | 22.06 | 0.00 | 22.04 |
Maximum of Months | 488.67 | 25.76 | 502.17 | 24.76 | 25.17 | 24.76 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.33 | 22.85 | 34.33 | 22.77 | 34.33 | 22.70 |
February | 424.83 | 23.16 | 15.00 | 23.09 | 15.00 | 23.02 |
March | 355.67 | 23.60 | 16.17 | 23.67 | 0.00 | 23.67 |
April | 204.17 | 23.73 | 92.17 | 23.93 | 0.00 | 23.93 |
May | 54.83 | 23.65 | 278.00 | 24.16 | 0.00 | 24.16 |
June | 6.67 | 23.48 | 454.00 | 24.24 | 0.00 | 24.24 |
July | 0.00 | 0.00 | 492.83 | 24.28 | 0.00 | 24.28 |
August | 0.00 | 0.00 | 507.00 | 24.29 | 0.00 | 24.29 |
September | 46.00 | 23.67 | 278.83 | 24.33 | 0.00 | 24.33 |
October | 139.50 | 23.71 | 73.00 | 24.09 | 0.00 | 24.09 |
November | 236.00 | 23.57 | 62.33 | 23.74 | 0.00 | 23.74 |
December | 463.50 | 23.56 | 4.83 | 23.53 | 4.83 | 23.51 |
Annual Sum or Average | 2425.50 | 23.38 | 2308.50 | 23.81 | 54.17 | 23.78 |
Minimum of Months | 0.00 | 0.00 | 4.83 | 22.77 | 0.00 | 22.70 |
Maximum of Months | 494.33 | 23.73 | 507.00 | 24.33 | 34.33 | 24.33 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.46 | 199.17 | 21.08 | 199.17 | 20.87 |
February | 452.67 | 22.10 | 95.83 | 21.80 | 95.83 | 21.59 |
March | 460.00 | 22.90 | 22.00 | 22.78 | 22.00 | 22.68 |
April | 325.33 | 23.15 | 41.50 | 23.26 | 2.00 | 23.25 |
May | 133.17 | 23.37 | 211.83 | 23.85 | 0.00 | 23.85 |
June | 21.17 | 23.23 | 379.17 | 24.11 | 0.00 | 24.11 |
July | 13.83 | 23.33 | 453.33 | 24.15 | 0.00 | 24.15 |
August | 5.33 | 23.29 | 443.50 | 24.17 | 0.00 | 24.17 |
September | 112.50 | 23.35 | 182.83 | 23.93 | 0.00 | 23.93 |
October | 352.00 | 23.32 | 9.50 | 23.34 | 0.00 | 23.34 |
November | 408.33 | 22.50 | 72.33 | 22.32 | 56.67 | 22.13 |
December | 497.00 | 21.95 | 108.17 | 21.65 | 108.17 | 21.43 |
Annual Sum or Average | 3283.33 | 22.48 | 2219.17 | 22.83 | 483.83 | 22.62 |
Minimum of Months | 5.33 | 21.46 | 9.50 | 21.08 | 0.00 | 20.87 |
Maximum of Months | 502.00 | 23.37 | 453.33 | 24.17 | 199.17 | 24.17 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.23 | 415.17 | 20.11 | 415.17 | 20.06 |
February | 454.00 | 20.57 | 287.00 | 20.32 | 287.00 | 20.22 |
March | 511.50 | 21.41 | 176.67 | 21.15 | 176.67 | 21.00 |
April | 423.67 | 21.80 | 111.17 | 21.62 | 83.33 | 21.40 |
May | 307.00 | 22.56 | 135.17 | 22.98 | 4.33 | 22.96 |
June | 128.83 | 22.53 | 290.67 | 23.62 | 0.00 | 23.62 |
July | 91.33 | 22.74 | 367.33 | 23.81 | 0.83 | 23.81 |
August | 118.67 | 22.69 | 333.67 | 23.71 | 0.00 | 23.71 |
September | 317.83 | 22.45 | 116.33 | 22.82 | 8.50 | 22.79 |
October | 491.83 | 21.63 | 106.00 | 21.34 | 106.00 | 21.14 |
November | 484.83 | 20.87 | 226.00 | 20.51 | 226.00 | 20.33 |
December | 497.00 | 20.38 | 384.17 | 20.23 | 384.17 | 20.17 |
Annual Sum or Average | 4328.50 | 21.32 | 2949.33 | 21.49 | 1692.00 | 21.21 |
Minimum of Months | 91.33 | 20.23 | 106.00 | 20.11 | 0.00 | 20.06 |
Maximum of Months | 511.50 | 22.74 | 415.17 | 23.81 | 415.17 | 23.81 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.13 | 472.67 | 20.10 | 472.67 | 20.09 |
February | 454.00 | 20.44 | 325.83 | 20.33 | 325.83 | 20.29 |
March | 510.17 | 21.25 | 182.17 | 21.05 | 182.17 | 20.94 |
April | 412.67 | 21.73 | 97.83 | 21.82 | 53.83 | 21.69 |
May | 281.50 | 22.53 | 159.33 | 23.08 | 0.00 | 23.08 |
June | 92.33 | 22.68 | 354.50 | 23.87 | 2.33 | 23.88 |
July | 24.17 | 22.91 | 440.33 | 24.07 | 0.83 | 24.08 |
August | 51.00 | 22.78 | 412.83 | 23.94 | 1.67 | 23.95 |
September | 265.17 | 22.35 | 152.33 | 22.99 | 2.00 | 22.98 |
October | 474.33 | 21.90 | 25.83 | 21.90 | 17.83 | 21.86 |
November | 481.17 | 21.14 | 201.67 | 20.88 | 201.67 | 20.74 |
December | 497.00 | 20.42 | 428.33 | 20.38 | 428.33 | 20.37 |
Annual Sum or Average | 4045.50 | 21.25 | 3253.67 | 21.64 | 1689.17 | 21.38 |
Minimum of Months | 24.17 | 20.13 | 25.83 | 20.10 | 0.00 | 20.09 |
Maximum of Months | 510.17 | 22.91 | 472.67 | 24.07 | 472.67 | 24.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.14 | 463.33 | 20.10 | 463.33 | 20.08 |
February | 451.67 | 20.52 | 297.33 | 20.38 | 297.33 | 20.32 |
March | 483.67 | 21.21 | 180.83 | 21.08 | 171.50 | 20.97 |
April | 382.67 | 21.51 | 138.67 | 21.83 | 61.83 | 21.70 |
May | 261.00 | 22.39 | 194.50 | 23.19 | 13.00 | 23.28 |
June | 147.83 | 22.70 | 323.33 | 23.74 | 16.50 | 23.84 |
July | 86.50 | 23.41 | 381.83 | 24.03 | 21.33 | 24.15 |
August | 114.17 | 22.61 | 347.83 | 23.66 | 10.17 | 23.72 |
September | 247.67 | 22.21 | 200.83 | 23.13 | 13.50 | 23.21 |
October | 451.33 | 21.76 | 43.67 | 21.81 | 27.50 | 21.76 |
November | 486.33 | 20.99 | 193.67 | 20.78 | 193.67 | 20.66 |
December | 497.00 | 20.44 | 407.50 | 20.37 | 407.50 | 20.35 |
Annual Sum or Average | 4111.83 | 21.25 | 3173.33 | 21.65 | 1697.17 | 21.44 |
Minimum of Months | 86.50 | 20.14 | 43.67 | 20.10 | 10.17 | 20.08 |
Maximum of Months | 502.00 | 23.41 | 463.33 | 24.03 | 463.33 | 24.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 469.67 | 20.41 | 372.83 | 20.23 | 366.17 | 20.14 |
February | 410.17 | 20.86 | 257.33 | 20.69 | 239.17 | 20.53 |
March | 422.50 | 21.34 | 213.67 | 21.33 | 173.00 | 21.17 |
April | 346.50 | 21.60 | 168.33 | 21.99 | 73.33 | 21.85 |
May | 256.50 | 22.24 | 187.67 | 23.05 | 4.00 | 23.06 |
June | 152.00 | 22.72 | 309.00 | 23.73 | 15.67 | 23.81 |
July | 77.17 | 23.34 | 396.83 | 24.06 | 16.67 | 24.15 |
August | 93.50 | 23.14 | 396.17 | 23.97 | 17.17 | 24.05 |
September | 231.17 | 22.50 | 227.50 | 23.43 | 21.67 | 23.54 |
October | 364.67 | 21.92 | 132.00 | 22.35 | 39.67 | 22.30 |
November | 426.50 | 21.14 | 200.00 | 21.04 | 170.33 | 20.84 |
December | 443.33 | 20.67 | 356.67 | 20.60 | 339.00 | 20.50 |
Annual Sum or Average | 3693.67 | 21.43 | 3218.00 | 21.93 | 1475.83 | 21.69 |
Minimum of Months | 77.17 | 20.41 | 132.00 | 20.23 | 4.00 | 20.14 |
Maximum of Months | 469.67 | 23.34 | 396.83 | 24.06 | 366.17 | 24.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.00 | 20.47 | 393.17 | 20.37 | 393.17 | 20.34 |
February | 437.67 | 20.87 | 217.00 | 20.77 | 208.00 | 20.68 |
March | 451.00 | 21.52 | 95.83 | 21.64 | 58.33 | 21.56 |
April | 324.00 | 22.19 | 132.33 | 22.83 | 19.83 | 22.94 |
May | 254.83 | 22.42 | 205.83 | 23.20 | 15.67 | 23.29 |
June | 134.33 | 23.24 | 362.83 | 24.01 | 40.33 | 24.13 |
July | 89.83 | 25.34 | 465.17 | 24.53 | 81.00 | 24.67 |
August | 84.17 | 24.80 | 483.17 | 24.40 | 68.00 | 24.50 |
September | 251.00 | 22.35 | 202.17 | 23.25 | 22.00 | 23.37 |
October | 412.17 | 21.91 | 58.67 | 22.21 | 0.67 | 22.21 |
November | 453.67 | 21.42 | 101.33 | 21.30 | 90.00 | 21.16 |
December | 491.83 | 21.01 | 199.17 | 20.86 | 199.17 | 20.78 |
Annual Sum or Average | 3885.50 | 21.66 | 2916.67 | 22.25 | 1196.17 | 22.13 |
Minimum of Months | 84.17 | 20.47 | 58.67 | 20.37 | 0.67 | 20.34 |
Maximum of Months | 501.00 | 25.34 | 483.17 | 24.53 | 393.17 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.72 | 492.17 | 19.71 | 492.17 | 19.71 |
February | 454.00 | 19.90 | 415.17 | 19.85 | 415.17 | 19.83 |
March | 514.00 | 20.53 | 335.00 | 20.42 | 335.00 | 20.37 |
April | 464.17 | 20.86 | 184.33 | 20.71 | 169.50 | 20.57 |
May | 418.00 | 21.70 | 73.50 | 21.91 | 15.83 | 21.87 |
June | 220.50 | 22.10 | 207.17 | 22.98 | 7.67 | 23.01 |
July | 182.33 | 22.34 | 260.83 | 23.25 | 9.83 | 23.28 |
August | 253.83 | 22.20 | 198.33 | 22.90 | 6.67 | 22.92 |
September | 398.00 | 21.62 | 83.67 | 21.85 | 23.50 | 21.80 |
October | 502.00 | 20.75 | 186.33 | 20.57 | 186.33 | 20.46 |
November | 489.00 | 20.12 | 323.83 | 19.92 | 323.83 | 19.83 |
December | 497.00 | 19.80 | 497.00 | 19.80 | 497.00 | 19.80 |
Annual Sum or Average | 4894.83 | 20.74 | 3257.33 | 20.78 | 2482.50 | 20.58 |
Minimum of Months | 182.33 | 19.72 | 73.50 | 19.71 | 6.67 | 19.71 |
Maximum of Months | 514.00 | 22.34 | 497.00 | 23.25 | 497.00 | 23.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.50 | 414.83 | 19.48 | 414.83 | 19.47 |
February | 385.00 | 19.79 | 337.83 | 19.69 | 337.83 | 19.66 |
March | 423.17 | 20.63 | 239.83 | 20.43 | 238.50 | 20.33 |
April | 337.33 | 21.05 | 164.17 | 21.18 | 112.17 | 20.98 |
May | 266.83 | 22.06 | 138.17 | 22.84 | 18.00 | 22.93 |
June | 171.83 | 22.57 | 235.17 | 23.57 | 25.00 | 23.72 |
July | 131.50 | 23.29 | 287.00 | 24.00 | 34.33 | 24.19 |
August | 170.67 | 22.45 | 235.50 | 23.37 | 15.50 | 23.46 |
September | 252.50 | 21.83 | 143.50 | 22.60 | 27.17 | 22.62 |
October | 416.83 | 21.11 | 125.50 | 20.94 | 122.33 | 20.82 |
November | 417.00 | 20.12 | 275.33 | 19.90 | 275.33 | 19.81 |
December | 422.00 | 19.64 | 415.00 | 19.63 | 415.00 | 19.63 |
Annual Sum or Average | 3821.67 | 20.78 | 3011.83 | 21.03 | 2036.00 | 20.80 |
Minimum of Months | 131.50 | 19.50 | 125.50 | 19.48 | 15.50 | 19.47 |
Maximum of Months | 427.00 | 23.29 | 415.00 | 24.00 | 415.00 | 24.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 473.33 | 19.96 | 399.17 | 19.81 | 392.33 | 19.73 |
February | 419.00 | 20.43 | 302.00 | 20.26 | 284.00 | 20.11 |
March | 440.83 | 20.90 | 266.67 | 20.89 | 226.00 | 20.74 |
April | 369.67 | 21.14 | 211.67 | 21.44 | 126.17 | 21.24 |
May | 323.17 | 21.84 | 146.83 | 22.48 | 12.50 | 22.44 |
June | 224.17 | 22.26 | 247.83 | 23.24 | 18.33 | 23.33 |
July | 160.50 | 22.64 | 311.17 | 23.64 | 22.00 | 23.74 |
August | 183.67 | 22.39 | 296.33 | 23.43 | 14.17 | 23.49 |
September | 267.67 | 22.06 | 209.50 | 22.99 | 33.17 | 23.06 |
October | 385.17 | 21.36 | 184.33 | 21.73 | 96.17 | 21.60 |
November | 445.00 | 20.57 | 258.00 | 20.45 | 231.50 | 20.26 |
December | 459.50 | 20.20 | 397.67 | 20.12 | 385.33 | 20.04 |
Annual Sum or Average | 4151.67 | 21.05 | 3231.17 | 21.40 | 1841.67 | 21.15 |
Minimum of Months | 160.50 | 19.96 | 146.83 | 19.81 | 12.50 | 19.73 |
Maximum of Months | 473.33 | 22.64 | 399.17 | 23.64 | 392.33 | 23.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.78 | 471.83 | 19.74 | 471.83 | 19.72 |
February | 449.67 | 20.15 | 357.83 | 20.02 | 356.00 | 19.97 |
March | 489.83 | 20.73 | 271.00 | 20.61 | 263.67 | 20.52 |
April | 393.83 | 21.12 | 184.17 | 21.33 | 115.67 | 21.17 |
May | 359.00 | 21.83 | 126.33 | 22.41 | 16.67 | 22.47 |
June | 215.50 | 22.28 | 263.67 | 23.35 | 27.33 | 23.47 |
July | 177.83 | 23.01 | 325.83 | 23.83 | 50.50 | 23.99 |
August | 182.00 | 22.32 | 297.17 | 23.40 | 23.50 | 23.48 |
September | 332.67 | 21.73 | 148.33 | 22.41 | 29.17 | 22.45 |
October | 459.67 | 20.99 | 152.50 | 20.94 | 129.67 | 20.81 |
November | 482.17 | 20.31 | 290.17 | 20.11 | 287.00 | 20.00 |
December | 497.00 | 19.94 | 462.50 | 19.90 | 462.50 | 19.88 |
Annual Sum or Average | 4541.17 | 20.88 | 3351.33 | 21.15 | 2233.50 | 20.94 |
Minimum of Months | 177.83 | 19.78 | 126.33 | 19.74 | 16.67 | 19.72 |
Maximum of Months | 502.00 | 23.01 | 471.83 | 23.83 | 471.83 | 23.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.65 | 499.50 | 19.64 | 499.50 | 19.64 |
February | 454.00 | 19.78 | 437.50 | 19.76 | 437.50 | 19.75 |
March | 514.00 | 20.26 | 404.17 | 20.17 | 404.17 | 20.14 |
April | 468.50 | 20.57 | 251.50 | 20.41 | 239.50 | 20.29 |
May | 449.50 | 21.23 | 87.50 | 21.31 | 46.67 | 21.21 |
June | 300.33 | 21.72 | 172.00 | 22.37 | 21.17 | 22.35 |
July | 268.83 | 21.92 | 201.67 | 22.65 | 20.00 | 22.70 |
August | 331.17 | 21.76 | 150.83 | 22.30 | 10.33 | 22.33 |
September | 423.83 | 21.20 | 120.67 | 21.26 | 80.83 | 21.15 |
October | 502.00 | 20.22 | 293.50 | 20.02 | 293.50 | 19.92 |
November | 489.00 | 19.86 | 371.50 | 19.70 | 371.50 | 19.64 |
December | 497.00 | 19.68 | 497.00 | 19.68 | 497.00 | 19.68 |
Annual Sum or Average | 5200.17 | 20.52 | 3487.33 | 20.48 | 2921.67 | 20.31 |
Minimum of Months | 268.83 | 19.65 | 87.50 | 19.64 | 10.33 | 19.64 |
Maximum of Months | 514.00 | 21.92 | 499.50 | 22.65 | 499.50 | 22.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.65 | 487.67 | 19.63 | 487.67 | 19.63 |
February | 454.00 | 19.80 | 411.33 | 19.74 | 411.33 | 19.72 |
March | 512.00 | 20.42 | 324.83 | 20.23 | 324.83 | 20.14 |
April | 415.33 | 20.86 | 232.67 | 20.89 | 184.67 | 20.72 |
May | 343.17 | 21.63 | 144.17 | 22.28 | 28.50 | 22.27 |
June | 221.33 | 22.19 | 284.67 | 23.22 | 37.00 | 23.33 |
July | 181.00 | 22.69 | 327.00 | 23.64 | 39.67 | 23.79 |
August | 223.83 | 22.01 | 277.83 | 23.04 | 17.00 | 23.10 |
September | 322.33 | 21.40 | 189.50 | 22.02 | 55.83 | 21.88 |
October | 499.50 | 20.51 | 227.00 | 20.28 | 226.50 | 20.15 |
November | 489.00 | 19.90 | 355.83 | 19.73 | 355.83 | 19.65 |
December | 497.00 | 19.69 | 495.50 | 19.69 | 495.50 | 19.69 |
Annual Sum or Average | 4660.50 | 20.60 | 3758.00 | 20.83 | 2664.33 | 20.62 |
Minimum of Months | 181.00 | 19.65 | 144.17 | 19.63 | 17.00 | 19.63 |
Maximum of Months | 512.00 | 22.69 | 495.50 | 23.64 | 495.50 | 23.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.33 | 19.80 | 419.17 | 19.65 | 416.33 | 19.59 |
February | 433.83 | 20.07 | 342.17 | 19.93 | 328.83 | 19.83 |
March | 462.67 | 20.52 | 323.00 | 20.45 | 295.67 | 20.33 |
April | 389.83 | 20.83 | 259.67 | 21.03 | 186.67 | 20.83 |
May | 373.33 | 21.38 | 139.50 | 21.83 | 39.33 | 21.72 |
June | 276.67 | 21.84 | 222.33 | 22.72 | 29.33 | 22.76 |
July | 229.50 | 22.13 | 263.67 | 23.12 | 30.17 | 23.22 |
August | 251.00 | 21.93 | 247.33 | 22.93 | 16.67 | 22.98 |
September | 317.67 | 21.61 | 212.50 | 22.31 | 73.33 | 22.25 |
October | 409.50 | 20.64 | 253.67 | 20.79 | 184.33 | 20.57 |
November | 469.33 | 20.18 | 308.17 | 20.01 | 294.33 | 19.87 |
December | 476.67 | 19.91 | 415.00 | 19.80 | 411.50 | 19.75 |
Annual Sum or Average | 4577.33 | 20.72 | 3406.17 | 20.94 | 2306.50 | 20.71 |
Minimum of Months | 229.50 | 19.80 | 139.50 | 19.65 | 16.67 | 19.59 |
Maximum of Months | 487.33 | 22.13 | 419.17 | 23.12 | 416.33 | 23.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.69 | 481.00 | 19.66 | 481.00 | 19.65 |
February | 450.33 | 19.93 | 394.00 | 19.84 | 392.50 | 19.81 |
March | 495.17 | 20.48 | 328.50 | 20.34 | 323.67 | 20.26 |
April | 400.00 | 20.86 | 241.67 | 21.01 | 175.50 | 20.82 |
May | 380.83 | 21.59 | 145.33 | 22.08 | 48.17 | 22.06 |
June | 251.83 | 22.13 | 252.83 | 23.09 | 48.00 | 23.21 |
July | 231.17 | 22.81 | 302.17 | 23.60 | 72.00 | 23.78 |
August | 245.00 | 22.23 | 263.67 | 23.14 | 37.83 | 23.24 |
September | 358.50 | 21.52 | 176.33 | 22.05 | 71.50 | 22.02 |
October | 467.83 | 20.57 | 230.17 | 20.40 | 213.00 | 20.25 |
November | 484.33 | 20.01 | 331.83 | 19.81 | 329.50 | 19.72 |
December | 497.00 | 19.76 | 472.00 | 19.72 | 472.00 | 19.71 |
Annual Sum or Average | 4764.00 | 20.72 | 3619.50 | 20.91 | 2664.67 | 20.72 |
Minimum of Months | 231.17 | 19.69 | 145.33 | 19.66 | 37.83 | 19.65 |
Maximum of Months | 502.00 | 22.81 | 481.00 | 23.60 | 481.00 | 23.78 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 30.00 | 314.83 | 27.18 | 1.33 | 27.20 |
February | 64.33 | 32.89 | 381.33 | 28.70 | 60.33 | 29.24 |
March | 2.33 | 27.00 | 512.00 | 27.00 | 2.33 | 27.00 |
April | 72.83 | 27.00 | 485.00 | 27.00 | 72.83 | 27.00 |
May | 33.67 | 27.00 | 508.00 | 27.00 | 33.67 | 27.00 |
June | 178.83 | 27.00 | 496.00 | 27.00 | 178.83 | 27.00 |
July | 295.33 | 27.00 | 497.00 | 27.00 | 295.33 | 27.00 |
August | 390.17 | 27.00 | 514.00 | 27.00 | 390.17 | 27.00 |
September | 72.50 | 27.00 | 485.00 | 27.00 | 72.50 | 27.00 |
October | 16.50 | 27.00 | 502.00 | 27.00 | 16.50 | 27.00 |
November | 5.83 | 30.66 | 470.00 | 27.09 | 5.83 | 27.13 |
December | 0.17 | 27.00 | 470.33 | 27.00 | 0.17 | 27.00 |
Annual Sum or Average | 1133.83 | 27.36 | 5635.50 | 27.13 | 1129.83 | 27.16 |
Minimum of Months | 0.17 | 27.00 | 314.83 | 27.00 | 0.17 | 27.00 |
Maximum of Months | 390.17 | 32.89 | 514.00 | 28.70 | 390.17 | 29.24 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 102.50 | 26.25 | 125.50 | 26.69 | 0.00 | 26.69 |
February | 86.17 | 30.47 | 273.50 | 28.73 | 52.17 | 29.24 |
March | 0.17 | 27.00 | 412.50 | 27.00 | 0.00 | 27.00 |
April | 21.17 | 27.00 | 465.83 | 27.00 | 21.17 | 27.00 |
May | 18.67 | 27.00 | 508.00 | 27.00 | 18.67 | 27.00 |
June | 99.00 | 27.00 | 496.00 | 27.00 | 99.00 | 27.00 |
July | 125.50 | 27.00 | 497.00 | 27.00 | 125.50 | 27.00 |
August | 146.50 | 27.00 | 514.00 | 27.00 | 146.50 | 27.00 |
September | 36.67 | 27.00 | 485.00 | 27.00 | 36.67 | 27.00 |
October | 5.17 | 27.00 | 484.67 | 27.00 | 5.17 | 27.00 |
November | 14.83 | 28.02 | 350.17 | 27.08 | 3.67 | 27.12 |
December | 35.67 | 27.00 | 247.83 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 692.00 | 27.34 | 4860.00 | 27.11 | 508.50 | 27.15 |
Minimum of Months | 0.17 | 26.25 | 125.50 | 26.69 | 0.00 | 26.69 |
Maximum of Months | 146.50 | 30.47 | 514.00 | 28.73 | 146.50 | 29.24 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 217.00 | 25.23 | 84.17 | 25.41 | 25.67 | 25.24 |
February | 109.17 | 28.29 | 199.83 | 28.14 | 27.33 | 28.47 |
March | 32.67 | 27.00 | 311.83 | 27.00 | 0.00 | 27.00 |
April | 42.50 | 27.00 | 403.50 | 27.00 | 26.00 | 27.00 |
May | 30.67 | 27.00 | 499.67 | 27.00 | 30.67 | 27.00 |
June | 132.50 | 27.00 | 496.00 | 27.00 | 132.50 | 27.00 |
July | 153.67 | 27.00 | 497.00 | 27.00 | 153.67 | 27.00 |
August | 163.17 | 27.00 | 514.00 | 27.00 | 163.17 | 27.00 |
September | 45.00 | 27.00 | 475.83 | 27.00 | 45.00 | 27.00 |
October | 23.83 | 27.00 | 377.17 | 27.00 | 4.33 | 27.00 |
November | 77.67 | 27.00 | 260.17 | 27.02 | 1.33 | 27.02 |
December | 98.00 | 27.00 | 126.50 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 1125.83 | 26.78 | 4245.67 | 26.98 | 609.67 | 26.99 |
Minimum of Months | 23.83 | 25.23 | 84.17 | 25.41 | 0.00 | 25.24 |
Maximum of Months | 217.00 | 28.29 | 514.00 | 28.14 | 163.17 | 28.47 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 23.33 | 27.17 | 502.00 | 27.13 | 23.33 | 27.14 |
February | 0.00 | 0.00 | 452.33 | 24.57 | 0.00 | 24.57 |
March | 41.50 | 25.77 | 499.17 | 25.52 | 40.50 | 25.55 |
April | 173.33 | 26.25 | 485.00 | 25.15 | 173.33 | 25.38 |
May | 339.50 | 27.03 | 508.00 | 27.03 | 339.50 | 27.03 |
June | 300.67 | 26.86 | 493.00 | 26.35 | 300.00 | 26.49 |
July | 496.83 | 26.80 | 497.00 | 26.80 | 496.83 | 26.80 |
August | 507.67 | 26.72 | 514.00 | 26.70 | 507.67 | 26.71 |
September | 485.00 | 27.04 | 485.00 | 27.04 | 485.00 | 27.04 |
October | 36.83 | 26.89 | 499.50 | 24.99 | 36.83 | 25.11 |
November | 373.83 | 25.83 | 485.83 | 25.75 | 373.83 | 25.77 |
December | 78.00 | 25.18 | 497.00 | 24.37 | 78.00 | 24.47 |
Annual Sum or Average | 2856.50 | 26.65 | 5917.83 | 26.13 | 2854.83 | 26.26 |
Minimum of Months | 0.00 | 0.00 | 452.33 | 24.37 | 0.00 | 24.47 |
Maximum of Months | 507.67 | 27.17 | 514.00 | 27.13 | 507.67 | 27.14 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.11341 | 13.06163 | 0.58493 | 12.44040 |
February | 454.00000 | 27.83407 | 15.14419 | 0.78597 | 20.21948 |
March | 514.00000 | 27.00000 | 19.51547 | 0.75898 | 17.37600 |
April | 485.00000 | 27.00003 | 25.40073 | 0.88414 | 21.81640 |
May | 508.00000 | 27.00019 | 34.84358 | 0.23618 | 6.40542 |
June | 496.00000 | 27.00018 | 37.99437 | 0.35861 | 7.90530 |
July | 497.00000 | 27.00006 | 38.35611 | 0.43657 | 9.11383 |
August | 514.00000 | 27.00037 | 37.10689 | 0.46849 | 9.72351 |
September | 485.00000 | 27.00012 | 34.27881 | 0.25578 | 6.73048 |
October | 502.00000 | 27.00000 | 25.39416 | 0.82194 | 19.47559 |
November | 489.00000 | 27.04369 | 21.08087 | 0.77543 | 18.12807 |
December | 497.00000 | 27.00000 | 14.04939 | 0.68730 | 15.10999 |
Annual Sum or Average | 5943.00000 | 27.07697 | 26.43927 | 0.58598 | 13.63869 |
Minimum of Months | 454.00000 | 27.00000 | 13.06163 | 0.23618 | 6.40542 |
Maximum of Months | 514.00000 | 27.83407 | 38.35611 | 0.88414 | 21.81640 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.86550 | 13.11082 | 0.43644 | 9.57809 |
February | 454.00000 | 27.71444 | 15.13523 | 0.66974 | 16.64228 |
March | 514.00000 | 27.00000 | 19.51579 | 0.65272 | 14.27813 |
April | 485.00000 | 27.00003 | 25.41324 | 0.77341 | 18.02856 |
May | 508.00000 | 27.00018 | 34.90123 | 0.15686 | 5.84285 |
June | 496.00000 | 27.00019 | 38.04917 | 0.27556 | 6.90240 |
July | 497.00000 | 27.00006 | 38.43167 | 0.31810 | 7.33850 |
August | 514.00000 | 27.00038 | 37.21310 | 0.32335 | 7.45253 |
September | 485.00000 | 27.00012 | 34.30960 | 0.15889 | 5.99759 |
October | 502.00000 | 27.00000 | 25.38798 | 0.72841 | 16.46797 |
November | 489.00000 | 27.03128 | 21.07388 | 0.64062 | 14.20487 |
December | 497.00000 | 27.00000 | 14.04180 | 0.53338 | 11.22097 |
Annual Sum or Average | 5943.00000 | 27.04587 | 26.46957 | 0.47038 | 11.10802 |
Minimum of Months | 454.00000 | 26.86550 | 13.11082 | 0.15686 | 5.84285 |
Maximum of Months | 514.00000 | 27.71444 | 38.43167 | 0.77341 | 18.02856 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.23240 | 13.31907 | 0.24887 | 8.63773 |
February | 454.00000 | 27.49894 | 15.13369 | 0.55443 | 13.06486 |
March | 514.00000 | 27.00000 | 19.51579 | 0.57905 | 12.48314 |
April | 485.00000 | 27.00003 | 25.45431 | 0.71292 | 16.41752 |
May | 508.00000 | 27.00053 | 34.94010 | 0.11139 | 5.92239 |
June | 496.00000 | 27.00019 | 38.05358 | 0.25802 | 7.05872 |
July | 497.00000 | 27.00008 | 38.43927 | 0.30746 | 7.45288 |
August | 514.00000 | 27.00034 | 37.33821 | 0.30328 | 7.46778 |
September | 485.00000 | 27.00111 | 34.34293 | 0.09593 | 6.07113 |
October | 502.00000 | 27.00000 | 25.39743 | 0.64300 | 14.19321 |
November | 489.00000 | 27.01686 | 21.08308 | 0.55264 | 12.07451 |
December | 497.00000 | 27.00000 | 14.04752 | 0.45193 | 9.62033 |
Annual Sum or Average | 5943.00000 | 26.97485 | 26.51030 | 0.40004 | 10.00402 |
Minimum of Months | 454.00000 | 26.23240 | 13.31907 | 0.09593 | 5.92239 |
Maximum of Months | 514.00000 | 27.49894 | 38.43927 | 0.71292 | 16.41752 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.13297 | 29.97745 | 0.94398 | 23.88149 |
February | 454.00000 | 24.56583 | 29.26283 | 0.60083 | 12.64481 |
March | 514.00000 | 25.38581 | 28.09979 | 0.87197 | 21.45807 |
April | 485.00000 | 24.76216 | 31.08243 | 0.93577 | 24.72981 |
May | 508.00000 | 27.03641 | 38.17910 | 0.44501 | 9.29455 |
June | 496.00000 | 26.01522 | 45.08610 | 0.46924 | 12.00198 |
July | 497.00000 | 26.79961 | 46.04688 | 0.96148 | 24.87256 |
August | 514.00000 | 26.67779 | 44.44979 | 1.10595 | 31.76524 |
September | 485.00000 | 27.04156 | 36.52776 | 0.58231 | 12.29143 |
October | 502.00000 | 24.83231 | 30.88989 | 0.78958 | 18.49690 |
November | 489.00000 | 25.64815 | 29.21764 | 0.99297 | 26.14698 |
December | 497.00000 | 24.24772 | 27.88972 | 0.84394 | 20.23460 |
Annual Sum or Average | 5943.00000 | 25.85823 | 34.78273 | 0.79717 | 19.88987 |
Minimum of Months | 454.00000 | 24.24772 | 27.88972 | 0.44501 | 9.29455 |
Maximum of Months | 514.00000 | 27.13297 | 46.04688 | 1.10595 | 31.76524 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.13721 | 13.50635 | -0.2551 | 7.49409 |
February | 454.00000 | 22.73874 | 16.51270 | -0.1091 | 6.59037 |
March | 514.00000 | 23.43957 | 21.40168 | 0.08820 | 5.90120 |
April | 485.00000 | 23.90143 | 28.56891 | 0.24273 | 6.82286 |
May | 508.00000 | 24.12821 | 40.78224 | -0.5038 | 11.01648 |
June | 496.00000 | 24.31948 | 46.20726 | -0.3715 | 8.56733 |
July | 497.00000 | 24.53770 | 47.65735 | -0.2772 | 7.52887 |
August | 514.00000 | 24.44593 | 47.51388 | -0.2829 | 7.66055 |
September | 485.00000 | 24.36151 | 37.43773 | -0.3947 | 9.86602 |
October | 502.00000 | 24.32851 | 25.96193 | 0.36076 | 8.17209 |
November | 489.00000 | 24.06262 | 22.38174 | 0.26593 | 7.43229 |
December | 497.00000 | 23.38254 | 14.84921 | 0.04795 | 5.97832 |
Annual Sum or Average | 5943.00000 | 23.82171 | 30.35374 | -0.1000 | 7.75947 |
Minimum of Months | 454.00000 | 22.13721 | 13.50635 | -0.5038 | 5.90120 |
Maximum of Months | 514.00000 | 24.53770 | 47.65735 | 0.36076 | 11.01648 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.86458 | 15.42081 | -0.1196 | 6.34822 |
February | 454.00000 | 23.22315 | 17.76777 | -0.0095 | 6.15748 |
March | 514.00000 | 23.81563 | 21.85342 | 0.18375 | 6.22082 |
April | 485.00000 | 24.01398 | 28.76711 | 0.30367 | 7.40256 |
May | 508.00000 | 24.09725 | 42.93189 | -0.4519 | 9.80815 |
June | 496.00000 | 24.22239 | 50.35849 | -0.3280 | 7.64187 |
July | 497.00000 | 24.27735 | 54.04917 | -0.2646 | 6.80743 |
August | 514.00000 | 24.28314 | 52.91121 | -0.2594 | 6.80067 |
September | 485.00000 | 24.23162 | 39.67597 | -0.4132 | 9.30230 |
October | 502.00000 | 24.16247 | 27.24520 | 0.32514 | 7.50190 |
November | 489.00000 | 23.97801 | 23.27943 | 0.23780 | 6.94799 |
December | 497.00000 | 23.62226 | 15.72536 | 0.08376 | 5.79581 |
Annual Sum or Average | 5943.00000 | 23.90372 | 32.63631 | -0.0604 | 7.23161 |
Minimum of Months | 454.00000 | 22.86458 | 15.42081 | -0.4519 | 5.79581 |
Maximum of Months | 514.00000 | 24.28314 | 54.04917 | 0.32514 | 9.80815 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.45689 | 14.35628 | -0.4816 | 12.41968 |
February | 454.00000 | 22.10709 | 18.30626 | -0.2923 | 8.81641 |
March | 514.00000 | 23.01850 | 22.75037 | -0.0287 | 6.47477 |
April | 485.00000 | 23.44250 | 30.24187 | 0.14410 | 6.49432 |
May | 508.00000 | 23.88300 | 43.73959 | -0.5474 | 12.06272 |
June | 496.00000 | 24.05386 | 51.12643 | -0.4121 | 9.00610 |
July | 497.00000 | 24.11951 | 55.03804 | -0.3603 | 8.09822 |
August | 514.00000 | 24.10002 | 54.23658 | -0.3710 | 8.23036 |
September | 485.00000 | 23.95065 | 40.82466 | -0.5394 | 12.00152 |
October | 502.00000 | 23.54158 | 28.88891 | 0.15148 | 6.09238 |
November | 489.00000 | 22.75941 | 24.77285 | -0.0825 | 7.67258 |
December | 497.00000 | 21.95231 | 16.56869 | -0.3412 | 9.47583 |
Annual Sum or Average | 5943.00000 | 23.20726 | 33.54191 | -0.2637 | 8.90219 |
Minimum of Months | 454.00000 | 21.45689 | 14.35628 | -0.5474 | 6.09238 |
Maximum of Months | 514.00000 | 24.11951 | 55.03804 | 0.15148 | 12.41968 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.23483 | 15.14141 | -0.8256 | 22.44799 |
February | 454.00000 | 20.56591 | 19.25871 | -0.6999 | 18.54137 |
March | 514.00000 | 21.42070 | 24.30079 | -0.4336 | 11.23028 |
April | 485.00000 | 22.06502 | 32.03571 | -0.1943 | 9.45532 |
May | 508.00000 | 23.11070 | 45.71432 | -0.8018 | 21.32978 |
June | 496.00000 | 23.60004 | 52.95489 | -0.5419 | 13.31918 |
July | 497.00000 | 23.77489 | 57.08095 | -0.4471 | 10.33153 |
August | 514.00000 | 23.69329 | 56.41532 | -0.4873 | 11.23289 |
September | 485.00000 | 22.98626 | 43.27080 | -0.8673 | 24.08007 |
October | 502.00000 | 21.67179 | 31.59310 | -0.3106 | 9.41842 |
November | 489.00000 | 20.89859 | 26.76659 | -0.5522 | 15.67954 |
December | 497.00000 | 20.37805 | 17.71231 | -0.7658 | 20.18054 |
Annual Sum or Average | 5943.00000 | 22.04641 | 35.32989 | -0.5764 | 15.56437 |
Minimum of Months | 454.00000 | 20.23483 | 15.14141 | -0.8673 | 9.41842 |
Maximum of Months | 514.00000 | 23.77489 | 57.08095 | -0.1943 | 24.08007 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.13058 | 13.75315 | -0.8919 | 23.67438 |
February | 454.00000 | 20.43826 | 18.01246 | -0.7415 | 18.40741 |
March | 514.00000 | 21.26688 | 23.06736 | -0.4384 | 10.85098 |
April | 485.00000 | 22.07228 | 30.27991 | -0.1542 | 8.28882 |
May | 508.00000 | 23.15426 | 43.91515 | -0.7367 | 19.16049 |
June | 496.00000 | 23.83051 | 50.68347 | -0.4093 | 10.45644 |
July | 497.00000 | 24.01925 | 54.40024 | -0.3004 | 7.60749 |
August | 514.00000 | 23.88798 | 53.47969 | -0.3555 | 8.57955 |
September | 485.00000 | 23.10356 | 41.09985 | -0.7719 | 21.25171 |
October | 502.00000 | 22.00866 | 29.18612 | -0.1857 | 7.11336 |
November | 489.00000 | 21.17397 | 24.87628 | -0.4506 | 12.24691 |
December | 497.00000 | 20.42459 | 16.31912 | -0.7438 | 18.01381 |
Annual Sum or Average | 5943.00000 | 22.13995 | 33.39348 | -0.5134 | 13.75893 |
Minimum of Months | 454.00000 | 20.13058 | 13.75315 | -0.8919 | 7.11336 |
Maximum of Months | 514.00000 | 24.01925 | 54.40024 | -0.1542 | 23.67438 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.13690 | 13.46739 | -0.8738 | 23.11743 |
February | 454.00000 | 20.53709 | 17.64178 | -0.6950 | 17.25251 |
March | 514.00000 | 21.38294 | 22.71739 | -0.3855 | 10.53401 |
April | 485.00000 | 22.08042 | 30.10856 | -0.1125 | 9.31693 |
May | 508.00000 | 23.14255 | 43.90533 | -0.6488 | 18.55517 |
June | 496.00000 | 23.60105 | 51.08985 | -0.3816 | 12.53559 |
July | 497.00000 | 23.81384 | 54.86487 | -0.2621 | 9.46713 |
August | 514.00000 | 23.55685 | 54.31835 | -0.3751 | 10.68950 |
September | 485.00000 | 23.09018 | 40.91133 | -0.6864 | 21.10535 |
October | 502.00000 | 22.00540 | 29.04372 | -0.1553 | 7.33335 |
November | 489.00000 | 21.00298 | 25.04612 | -0.4800 | 12.29223 |
December | 497.00000 | 20.44265 | 16.03519 | -0.7422 | 18.12887 |
Annual Sum or Average | 5943.00000 | 22.07884 | 33.40406 | -0.4818 | 14.15992 |
Minimum of Months | 454.00000 | 20.13690 | 13.46739 | -0.8738 | 7.33335 |
Maximum of Months | 514.00000 | 23.81384 | 54.86487 | -0.1125 | 23.11743 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.63789 | 13.33045 | -0.7074 | 20.41287 |
February | 454.00000 | 21.18602 | 17.17795 | -0.5098 | 15.47482 |
March | 514.00000 | 21.83916 | 22.25910 | -0.2750 | 10.63318 |
April | 485.00000 | 22.34134 | 29.68429 | -0.0575 | 10.31670 |
May | 508.00000 | 23.12455 | 43.98096 | -0.7093 | 19.96416 |
June | 496.00000 | 23.61056 | 51.20076 | -0.4460 | 12.90676 |
July | 497.00000 | 23.91472 | 54.64307 | -0.2883 | 8.97804 |
August | 514.00000 | 23.84361 | 53.47272 | -0.3005 | 9.48713 |
September | 485.00000 | 23.36450 | 40.34137 | -0.5937 | 19.61787 |
October | 502.00000 | 22.54609 | 28.17588 | -0.0117 | 8.77138 |
November | 489.00000 | 21.56597 | 24.45904 | -0.3381 | 12.54194 |
December | 497.00000 | 21.06557 | 15.68687 | -0.5668 | 16.61006 |
Annual Sum or Average | 5943.00000 | 22.43045 | 33.00958 | -0.3998 | 13.78597 |
Minimum of Months | 454.00000 | 20.63789 | 13.33045 | -0.7093 | 8.77138 |
Maximum of Months | 514.00000 | 23.91472 | 54.64307 | -0.0117 | 20.41287 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.47209 | 13.06503 | -0.7377 | 18.21631 |
February | 454.00000 | 21.00291 | 17.03674 | -0.5285 | 13.37628 |
March | 514.00000 | 21.85405 | 21.91044 | -0.2174 | 8.46703 |
April | 485.00000 | 22.81718 | 28.66984 | 0.13316 | 9.40224 |
May | 508.00000 | 23.12015 | 43.81589 | -0.6135 | 17.50538 |
June | 496.00000 | 23.81087 | 50.38391 | -0.2564 | 10.85096 |
July | 497.00000 | 24.26937 | 53.30298 | -0.0278 | 7.94581 |
August | 514.00000 | 24.23257 | 52.05701 | -0.0416 | 7.34946 |
September | 485.00000 | 23.16946 | 40.61844 | -0.6108 | 19.21970 |
October | 502.00000 | 22.30169 | 28.31131 | -0.0414 | 7.15858 |
November | 489.00000 | 21.60172 | 24.05316 | -0.2827 | 9.52546 |
December | 497.00000 | 21.03923 | 15.37381 | -0.5184 | 12.12284 |
Annual Sum or Average | 5943.00000 | 22.48639 | 32.52111 | -0.3103 | 11.73300 |
Minimum of Months | 454.00000 | 20.47209 | 13.06503 | -0.7377 | 7.15858 |
Maximum of Months | 514.00000 | 24.26937 | 53.30298 | 0.13316 | 19.21970 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.72328 | 13.17594 | -1.0836 | 31.91752 |
February | 454.00000 | 19.89626 | 17.85870 | -0.9513 | 26.74410 |
March | 514.00000 | 20.52531 | 23.59612 | -0.6773 | 16.53965 |
April | 485.00000 | 20.97360 | 32.10178 | -0.4444 | 12.21450 |
May | 508.00000 | 22.02720 | 46.62856 | -1.0960 | 33.02705 |
June | 496.00000 | 22.99432 | 53.29371 | -0.6762 | 17.90561 |
July | 497.00000 | 23.20088 | 57.63358 | -0.5696 | 13.77265 |
August | 514.00000 | 22.91137 | 57.17118 | -0.6818 | 17.11354 |
September | 485.00000 | 21.99648 | 43.77962 | -1.1417 | 35.57490 |
October | 502.00000 | 20.74807 | 31.32464 | -0.5128 | 11.78151 |
November | 489.00000 | 20.11942 | 26.08204 | -0.7722 | 21.23081 |
December | 497.00000 | 19.80398 | 16.03575 | -1.0074 | 28.68752 |
Annual Sum or Average | 5943.00000 | 21.25581 | 35.04169 | -0.8000 | 22.16016 |
Minimum of Months | 454.00000 | 19.72328 | 13.17594 | -1.1417 | 11.78151 |
Maximum of Months | 514.00000 | 23.20088 | 57.63358 | -0.4444 | 35.57490 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.49885 | 13.09783 | -1.1139 | 33.54936 |
February | 385.00000 | 19.78525 | 17.59189 | -0.9409 | 26.84050 |
March | 433.00000 | 20.70378 | 23.03048 | -0.5996 | 15.67097 |
April | 410.00000 | 21.62165 | 30.51290 | -0.2619 | 12.08543 |
May | 430.00000 | 22.80292 | 44.51113 | -0.7836 | 24.13248 |
June | 418.00000 | 23.38220 | 51.86195 | -0.4734 | 15.89959 |
July | 422.00000 | 23.71895 | 55.77557 | -0.3159 | 11.60783 |
August | 433.00000 | 23.26631 | 55.64949 | -0.4988 | 14.19940 |
September | 410.00000 | 22.65824 | 41.87532 | -0.8652 | 27.92128 |
October | 427.00000 | 21.18690 | 30.13226 | -0.3887 | 10.03875 |
November | 417.00000 | 20.11929 | 25.35774 | -0.7655 | 21.13905 |
December | 422.00000 | 19.64274 | 15.92831 | -1.0309 | 29.81355 |
Annual Sum or Average | 5034.00000 | 21.54377 | 33.89571 | -0.6682 | 20.18278 |
Minimum of Months | 385.00000 | 19.49885 | 13.09783 | -1.1139 | 10.03875 |
Maximum of Months | 433.00000 | 23.71895 | 55.77557 | -0.2619 | 33.54936 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.19348 | 12.83718 | -0.8441 | 25.73342 |
February | 454.00000 | 20.72814 | 16.91773 | -0.6344 | 19.69226 |
March | 514.00000 | 21.35235 | 22.39993 | -0.4058 | 13.39566 |
April | 485.00000 | 21.86887 | 30.41093 | -0.1822 | 12.20700 |
May | 508.00000 | 22.61489 | 45.23963 | -0.8687 | 25.91379 |
June | 496.00000 | 23.15724 | 52.72248 | -0.5906 | 17.31327 |
July | 497.00000 | 23.49733 | 56.56174 | -0.4288 | 12.41295 |
August | 514.00000 | 23.35357 | 55.57806 | -0.4658 | 13.67475 |
September | 485.00000 | 22.96507 | 41.37279 | -0.7197 | 24.58922 |
October | 502.00000 | 22.02088 | 29.08620 | -0.1349 | 10.25481 |
November | 489.00000 | 20.93562 | 25.04154 | -0.5156 | 16.76623 |
December | 497.00000 | 20.50354 | 15.33856 | -0.7491 | 22.34269 |
Annual Sum or Average | 5943.00000 | 21.94275 | 33.77651 | -0.5446 | 17.83452 |
Minimum of Months | 454.00000 | 20.19348 | 12.83718 | -0.8687 | 10.25481 |
Maximum of Months | 514.00000 | 23.49733 | 56.56174 | -0.1349 | 25.91379 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.78119 | 13.01186 | -1.0158 | 29.45736 |
February | 454.00000 | 20.18197 | 17.36312 | -0.8210 | 22.60465 |
March | 514.00000 | 20.88252 | 22.94395 | -0.5437 | 14.12070 |
April | 485.00000 | 21.66411 | 30.74544 | -0.2186 | 11.74757 |
May | 508.00000 | 22.42166 | 45.67167 | -0.8941 | 27.62646 |
June | 496.00000 | 23.19399 | 52.47469 | -0.5118 | 17.03252 |
July | 497.00000 | 23.57008 | 56.22653 | -0.3382 | 12.46011 |
August | 514.00000 | 23.28849 | 55.73445 | -0.4489 | 13.68693 |
September | 485.00000 | 22.43185 | 42.57878 | -0.9183 | 30.09572 |
October | 502.00000 | 21.23708 | 30.31683 | -0.3555 | 10.23498 |
November | 489.00000 | 20.36072 | 25.64437 | -0.6806 | 18.49901 |
December | 497.00000 | 19.94496 | 15.75083 | -0.9271 | 25.65633 |
Annual Sum or Average | 5943.00000 | 21.59213 | 34.18783 | -0.6381 | 19.39213 |
Minimum of Months | 454.00000 | 19.78119 | 13.01186 | -1.0158 | 10.23498 |
Maximum of Months | 514.00000 | 23.57008 | 56.22653 | -0.2186 | 30.09572 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.64707 | 13.61647 | -1.1645 | 35.24539 |
February | 454.00000 | 19.78108 | 18.22089 | -1.0452 | 30.61419 |
March | 514.00000 | 20.26373 | 24.08343 | -0.7951 | 20.71088 |
April | 485.00000 | 20.66652 | 32.87810 | -0.5600 | 15.49149 |
May | 508.00000 | 21.49211 | 48.19637 | -1.2800 | 41.29036 |
June | 496.00000 | 22.43416 | 55.57111 | -0.8358 | 24.09228 |
July | 497.00000 | 22.61652 | 60.59313 | -0.7233 | 19.07175 |
August | 514.00000 | 22.32714 | 59.96612 | -0.8463 | 23.24232 |
September | 485.00000 | 21.48352 | 45.34559 | -1.3367 | 44.51003 |
October | 502.00000 | 20.22460 | 32.30680 | -0.6928 | 17.79107 |
November | 489.00000 | 19.85816 | 26.57749 | -0.9040 | 26.02333 |
December | 497.00000 | 19.68157 | 16.51372 | -1.1071 | 32.85436 |
Annual Sum or Average | 5943.00000 | 20.88319 | 36.31689 | -0.9401 | 27.54060 |
Minimum of Months | 454.00000 | 19.64707 | 13.61647 | -1.3367 | 15.49149 |
Maximum of Months | 514.00000 | 22.61652 | 60.59313 | -0.5600 | 44.51003 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.65271 | 13.60403 | -1.1301 | 34.01559 |
February | 454.00000 | 19.80224 | 18.18642 | -0.9915 | 28.85146 |
March | 514.00000 | 20.43170 | 23.76375 | -0.7036 | 18.61226 |
April | 485.00000 | 21.30804 | 31.56291 | -0.3676 | 13.78620 |
May | 508.00000 | 22.38600 | 45.93299 | -0.9196 | 29.08139 |
June | 496.00000 | 23.10213 | 53.31862 | -0.5369 | 18.70841 |
July | 497.00000 | 23.44005 | 57.67066 | -0.3684 | 13.20167 |
August | 514.00000 | 22.98782 | 57.60403 | -0.5578 | 16.50533 |
September | 485.00000 | 22.25644 | 43.19398 | -1.0082 | 33.62781 |
October | 502.00000 | 20.52853 | 31.69584 | -0.5820 | 14.57425 |
November | 489.00000 | 19.89985 | 26.49767 | -0.8726 | 24.86520 |
December | 497.00000 | 19.69224 | 16.48989 | -1.0809 | 31.90965 |
Annual Sum or Average | 5943.00000 | 21.30340 | 35.11231 | -0.7581 | 23.08077 |
Minimum of Months | 454.00000 | 19.65271 | 13.60403 | -1.1301 | 13.20167 |
Maximum of Months | 514.00000 | 23.44005 | 57.67066 | -0.3676 | 34.01559 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.91648 | 13.39802 | -0.9673 | 29.87665 |
February | 454.00000 | 20.23755 | 17.64104 | -0.8016 | 24.34854 |
March | 514.00000 | 20.87288 | 23.14275 | -0.5652 | 17.30485 |
April | 485.00000 | 21.49024 | 31.25090 | -0.3118 | 14.88502 |
May | 508.00000 | 22.05271 | 46.83841 | -1.0604 | 33.98572 |
June | 496.00000 | 22.68595 | 54.73198 | -0.7259 | 22.73828 |
July | 497.00000 | 23.01148 | 59.18840 | -0.5559 | 16.79012 |
August | 514.00000 | 22.86803 | 58.06615 | -0.6035 | 18.55123 |
September | 485.00000 | 22.44212 | 42.87352 | -0.9168 | 32.42424 |
October | 502.00000 | 21.30280 | 30.33739 | -0.3508 | 14.02501 |
November | 489.00000 | 20.34540 | 25.89530 | -0.7097 | 21.33309 |
December | 497.00000 | 20.07799 | 16.09986 | -0.9073 | 27.38736 |
Annual Sum or Average | 5943.00000 | 21.45201 | 35.11324 | -0.7059 | 22.78292 |
Minimum of Months | 454.00000 | 19.91648 | 13.39802 | -1.0604 | 14.02501 |
Maximum of Months | 514.00000 | 23.01148 | 59.18840 | -0.3118 | 33.98572 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.68599 | 13.55701 | -1.0961 | 32.76893 |
February | 454.00000 | 19.95650 | 17.94648 | -0.9247 | 26.61069 |
March | 514.00000 | 20.60783 | 23.48883 | -0.6511 | 17.54551 |
April | 485.00000 | 21.42059 | 31.41324 | -0.3104 | 14.33295 |
May | 508.00000 | 22.15065 | 46.53833 | -0.9970 | 32.64334 |
June | 496.00000 | 22.96876 | 53.77462 | -0.5753 | 20.28791 |
July | 497.00000 | 23.33080 | 58.06456 | -0.3953 | 14.91918 |
August | 514.00000 | 23.02513 | 57.50895 | -0.5221 | 16.69370 |
September | 485.00000 | 22.14734 | 43.56583 | -1.0391 | 35.81377 |
October | 502.00000 | 20.79551 | 31.15137 | -0.5034 | 14.41398 |
November | 489.00000 | 20.04531 | 26.25705 | -0.8063 | 23.01394 |
December | 497.00000 | 19.75753 | 16.39707 | -1.0269 | 29.84536 |
Annual Sum or Average | 5943.00000 | 21.33634 | 35.12533 | -0.7359 | 23.19276 |
Minimum of Months | 454.00000 | 19.68599 | 13.55701 | -1.0961 | 14.33295 |
Maximum of Months | 514.00000 | 23.33080 | 58.06456 | -0.3104 | 35.81377 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.980059E+09 | 20959.75 | 13-JAN-22:03 | 103.84 | 0.437438E+10 | 0.00 | 0.535444E+10 | 0.62 | 4.50 | 13-JAN-22:50 | 0.00 | 0.00 |
February | 0.370377E+11 | 153978.25 | 24-FEB-19:02 | 207.65 | 0.167128E+12 | 0.00 | 0.204165E+12 | 1.39 | 6.54 | 24-FEB-19:02 | 0.00 | 0.00 |
March | 0.590651E+11 | 166321.28 | 23-MAR-13:32 | 564.59 | 0.276727E+12 | 0.00 | 0.335792E+12 | 3.59 | 6.71 | 23-MAR-13:32 | 0.00 | 0.00 |
April | 0.858220E+11 | 272923.35 | 18-APR-09:10 | 595.26 | 0.458823E+12 | 0.00 | 0.544645E+12 | 4.05 | 7.04 | 15-APR-17:41 | 0.00 | 0.00 |
May | 0.872156E+11 | 272337.82 | 30-MAY-10:30 | 303.54 | 0.489633E+12 | 0.00 | 0.576849E+12 | 2.06 | 7.01 | 28-MAY-17:32 | 0.00 | 0.00 |
June | 0.228807E+12 | 286893.39 | 18-JUN-15:33 | 490.33 | 0.139819E+13 | 0.00 | 0.162700E+13 | 3.87 | 7.12 | 13-JUN-04:13 | 0.00 | 0.00 |
July | 0.289025E+12 | 283167.05 | 18-JUL-12:50 | 657.67 | 0.179603E+13 | 0.00 | 0.208506E+13 | 5.03 | 7.12 | 28-JUL-04:12 | 0.00 | 0.00 |
August | 0.294136E+12 | 294685.66 | 03-AUG-05:03 | 692.44 | 0.182792E+13 | 0.00 | 0.212205E+13 | 5.25 | 7.20 | 29-AUG-13:40 | 0.00 | 0.00 |
September | 0.114335E+12 | 280018.36 | 05-SEP-14:00 | 311.75 | 0.694738E+12 | 0.00 | 0.809073E+12 | 2.36 | 7.09 | 11-SEP-05:03 | 0.00 | 0.00 |
October | 0.548636E+11 | 220090.00 | 20-OCT-13:00 | 245.71 | 0.262237E+12 | 0.00 | 0.317101E+12 | 1.53 | 7.01 | 20-OCT-13:00 | 0.00 | 0.00 |
November | 0.511387E+11 | 178190.74 | 03-NOV-11:15 | 652.06 | 0.245786E+12 | 0.00 | 0.296925E+12 | 4.33 | 6.92 | 03-NOV-13:32 | 0.00 | 0.00 |
December | 0.597620E+11 | 141791.28 | 05-DEC-13:38 | 649.39 | 0.285976E+12 | 0.00 | 0.345738E+12 | 4.18 | 6.23 | 05-DEC-13:38 | 0.00 | 0.00 |
Annual Sum or Average | 0.136219E+13 | 5474.21 | 0.790756E+13 | 0.00 | 0.926975E+13 | 3.20 | 0.00 | 0.00 | ||||
Minimum of Months | 0.980059E+09 | 20959.75 | 103.84 | 0.437438E+10 | 0.00 | 0.535444E+10 | 0.62 | 4.50 | 0.00 | 0.00 | ||
Maximum of Months | 0.294136E+12 | 294685.66 | 692.44 | 0.182792E+13 | 0.00 | 0.212205E+13 | 5.25 | 7.20 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.412852E+10 | 185899.06 | 18-APR-09:20 | 6.83 | 0.264633E+11 | 0.00 | 0.305918E+11 | 0.06 | 6.75 | 18-APR-09:20 | 0.00 | 0.00 |
May | 0.263919E+10 | 189729.15 | 30-MAY-14:05 | 4.67 | 0.168379E+11 | 0.00 | 0.194771E+11 | 0.04 | 6.68 | 30-MAY-14:05 | 0.00 | 0.00 |
June | 0.308780E+11 | 264282.76 | 30-JUN-04:14 | 52.05 | 0.195339E+12 | 0.00 | 0.226217E+12 | 0.46 | 6.85 | 27-JUN-04:14 | 0.00 | 0.00 |
July | 0.603377E+11 | 260677.26 | 27-JUL-04:14 | 101.89 | 0.381569E+12 | 0.00 | 0.441907E+12 | 0.86 | 6.90 | 15-JUL-04:14 | 0.00 | 0.00 |
August | 0.739969E+11 | 294685.66 | 03-AUG-05:03 | 121.19 | 0.471177E+12 | 0.00 | 0.545174E+12 | 1.03 | 6.90 | 29-AUG-12:05 | 0.00 | 0.00 |
September | 0.108068E+11 | 197579.54 | 11-SEP-12:05 | 19.50 | 0.686910E+11 | 0.00 | 0.794978E+11 | 0.17 | 6.80 | 07-SEP-12:05 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.182787E+12 | 306.14 | 0.116008E+13 | 0.00 | 0.134286E+13 | 0.22 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.739969E+11 | 294685.66 | 121.19 | 0.471177E+12 | 0.00 | 0.545174E+12 | 1.03 | 6.90 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 330796.47 | 14-JAN-00:20 | 21.02 | 21.00 | 2.43 |
February | 536429.58 | 14.76 | 45.69 | 09-FEB-18:39 | 735973.34 | 15-FEB-05:55 | 21.31 | 21.07 | 27.76 |
March | 43747488.51 | 85.09 | 4612.22 | 19-MAR-14:15 | 1132062.74 | 23-MAR-13:34 | 21.36 | 20.98 | 46.07 |
April | 0.434692E+10 | 130.36 | 29261.06 | 14-APR-13:30 | 2007487.23 | 14-APR-14:20 | 21.56 | 20.96 | 57.06 |
May | 0.759074E+10 | 234.04 | 29261.06 | 04-MAY-13:40 | 2089443.74 | 05-MAY-16:00 | 21.85 | 21.28 | 35.56 |
June | 0.299084E+11 | 483.26 | 29261.06 | 08-JUN-11:00 | 2188556.56 | 23-JUN-15:00 | 23.76 | 22.15 | 63.92 |
July | 0.431134E+11 | 615.95 | 29261.06 | 01-JUL-07:40 | 2199175.30 | 18-JUL-12:50 | 24.17 | 22.17 | 82.31 |
August | 0.406679E+11 | 585.15 | 29261.06 | 01-AUG-06:55 | 2155491.28 | 17-AUG-10:40 | 24.11 | 22.04 | 85.57 |
September | 0.115700E+11 | 251.35 | 29261.06 | 01-SEP-15:00 | 2170200.40 | 05-SEP-14:00 | 22.12 | 21.31 | 38.08 |
October | 0.429446E+09 | 174.28 | 11838.55 | 20-OCT-15:00 | 1768402.04 | 20-OCT-13:00 | 21.95 | 21.63 | 30.53 |
November | 30181880.84 | 21.51 | 5484.46 | 03-NOV-13:40 | 1384260.22 | 03-NOV-13:40 | 21.19 | 20.83 | 48.50 |
December | 71270.49 | 1.19 | 44.51 | 05-DEC-16:08 | 769891.28 | 05-DEC-16:08 | 21.12 | 20.71 | 47.70 |
Annual Sum or Average | 0.137701E+12 | 2596.94 | 22.13 | 21.35 | 47.23 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 330796.47 | 21.02 | 20.71 | 2.43 | ||
Maximum of Months | 0.431134E+11 | 615.95 | 29261.06 | 2199175.30 | 24.17 | 22.17 | 85.57 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 21.02 | 21.02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 21.31 | 21.31 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 21.36 | 21.36 | 0.00 |
April | 0.113679E+10 | 10.79 | 29261.06 | 15-APR-12:00 | 1367936.93 | 18-APR-15:10 | 21.56 | 21.50 | 1.17 |
May | 0.693487E+09 | 6.58 | 29261.06 | 12-MAY-14:20 | 1487533.89 | 31-MAY-14:05 | 21.85 | 21.82 | 0.72 |
June | 0.716512E+10 | 68.14 | 29261.06 | 09-JUN-09:50 | 1729495.56 | 23-JUN-15:20 | 23.76 | 23.43 | 7.96 |
July | 0.132081E+11 | 125.55 | 29261.06 | 02-JUL-12:21 | 1781958.68 | 18-JUL-15:40 | 24.17 | 23.58 | 14.49 |
August | 0.148639E+11 | 141.52 | 29261.06 | 01-AUG-07:20 | 1816002.86 | 16-AUG-13:10 | 24.11 | 23.42 | 16.51 |
September | 0.198035E+10 | 18.83 | 29261.06 | 05-SEP-14:05 | 1814698.49 | 01-SEP-14:05 | 22.12 | 22.03 | 2.42 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 21.95 | 21.95 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 21.19 | 21.19 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 21.12 | 21.12 | 0.00 |
Annual Sum or Average | 0.390477E+11 | 371.41 | 22.13 | 21.98 | 3.64 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 | 21.02 | 0.00 | ||
Maximum of Months | 0.148639E+11 | 141.52 | 29261.06 | 1816002.86 | 24.17 | 23.58 | 16.51 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.151239E+13 | 0.00 | 676.42 | 4543504.69 | 02-JAN-04:01 | 0.00 | 37.04 | 76.58 | 3.46 | 0.00 | 0.13 | 1.02 | 02-JAN-04:01 |
February | 0.940972E+12 | 0.00 | 587.61 | 3940492.96 | 21-FEB-05:01 | 0.00 | 35.01 | 72.84 | 2.39 | 0.00 | 0.09 | 0.89 | 21-FEB-05:01 |
March | 0.489610E+12 | 0.00 | 535.54 | 3505456.42 | 25-MAR-04:01 | 0.00 | 27.93 | 61.85 | 0.98 | 0.00 | 0.04 | 0.79 | 25-MAR-04:01 |
April | 0.196402E+12 | 0.00 | 379.48 | 3657453.71 | 01-APR-04:01 | 0.00 | 24.55 | 48.95 | 0.41 | 0.00 | 0.02 | 0.82 | 01-APR-04:01 |
May | 0.319122E+11 | 0.00 | 197.91 | 3267873.93 | 02-MAY-04:11 | 0.00 | 21.67 | 33.26 | 0.07 | 0.00 | 0.00 | 0.74 | 02-MAY-04:11 |
June | 0.106214E+11 | 0.00 | 97.14 | 2871209.72 | 02-JUN-05:01 | 0.00 | 20.63 | 26.61 | 0.02 | 0.00 | 0.00 | 0.65 | 02-JUN-05:01 |
July | 0.133153E+10 | 0.00 | 49.95 | 208703.21 | 24-JUL-05:01 | 0.00 | 20.20 | 23.25 | 0.00 | 0.00 | 0.00 | 0.05 | 24-JUL-05:01 |
August | 0.406522E+10 | 0.00 | 84.30 | 388786.70 | 07-AUG-05:02 | 0.00 | 20.40 | 25.51 | 0.01 | 0.00 | 0.00 | 0.09 | 07-AUG-05:02 |
September | 0.518923E+11 | 0.00 | 222.73 | 3359021.90 | 30-SEP-04:01 | 0.00 | 22.23 | 35.66 | 0.11 | 0.00 | 0.00 | 0.76 | 30-SEP-04:01 |
October | 0.155409E+12 | 0.00 | 411.39 | 3615852.69 | 16-OCT-04:11 | 0.00 | 24.41 | 49.00 | 0.33 | 0.00 | 0.01 | 0.81 | 16-OCT-04:11 |
November | 0.562531E+12 | 0.00 | 555.89 | 3718956.36 | 28-NOV-05:01 | 0.00 | 30.71 | 64.57 | 1.24 | 0.00 | 0.05 | 0.84 | 28-NOV-05:01 |
December | 0.107545E+13 | 0.00 | 665.41 | 3831784.04 | 18-DEC-05:01 | 0.00 | 34.07 | 75.21 | 2.28 | 0.00 | 0.09 | 0.86 | 18-DEC-05:01 |
Annual Sum or Average | 0.503259E+13 | 0.00 | 4463.77 | 0.00 | 26.52 | 49.31 | 0.94 | 0.00 | 0.04 | ||||
Minimum of Months | 0.133153E+10 | 0.00 | 49.95 | 208703.21 | 0.00 | 20.20 | 23.25 | 0.00 | 0.00 | 0.00 | 0.05 | ||
Maximum of Months | 0.151239E+13 | 0.00 | 676.42 | 4543504.69 | 0.00 | 37.04 | 76.58 | 3.46 | 0.00 | 0.13 | 1.02 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3659.99 | 0.00 | 2.70 | 3659.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 | 08-JAN-02:03 | 0.52 | 08-JAN-02:03 | 0.00 | 0.00 | 0.00 |
February | 183693.85 | 0.00 | 0.62 | 183693.85 | 0.00 | 0.00 | 0.00 | 0.00 | 2221.65 | 10-FEB-17:01 | 2221.65 | 10-FEB-17:01 | 0.00 | 0.00 | 0.00 |
March | 0.883886E+09 | 0.00 | 19.04 | 0.883886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39800.80 | 19-MAR-13:21 | 39800.80 | 19-MAR-13:21 | 0.00 | 0.00 | 0.00 |
April | 0.164551E+11 | 0.00 | 96.36 | 0.151966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167381.03 | 16-APR-14:51 | 142272.94 | 18-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.369068E+11 | 0.00 | 261.16 | 0.335970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 145765.81 | 31-MAY-15:00 | 134178.08 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.103571E+12 | 0.00 | 372.07 | 0.882616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 227806.42 | 26-JUN-04:11 | 172318.52 | 26-JUN-04:11 | 0.00 | 0.00 | 0.00 |
July | 0.150557E+12 | 0.00 | 478.94 | 0.119646E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 208762.35 | 27-JUL-05:03 | 162009.71 | 26-JUL-04:11 | 0.00 | 0.00 | 0.00 |
August | 0.151392E+12 | 0.00 | 470.49 | 0.121754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 231607.67 | 03-AUG-05:02 | 166247.73 | 04-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.575551E+11 | 0.00 | 250.14 | 0.550442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 175118.89 | 11-SEP-04:11 | 152609.98 | 06-SEP-15:20 | 0.00 | 0.00 | 0.00 |
October | 0.518290E+10 | 0.00 | 61.11 | 0.518290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107946.67 | 20-OCT-15:00 | 107946.67 | 20-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.335923E+09 | 0.00 | 11.64 | 0.335535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48686.93 | 09-NOV-06:02 | 42227.79 | 09-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 166115.13 | 0.00 | 0.60 | 166115.13 | 0.00 | 0.00 | 0.00 | 0.00 | 750.52 | 01-DEC-17:03 | 750.52 | 01-DEC-17:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.522840E+12 | 0.00 | 2024.86 | 0.439902E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3659.99 | 0.00 | 0.60 | 3659.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 | 0.52 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.151392E+12 | 0.00 | 478.94 | 0.121754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 231607.67 | 172318.52 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 127639.66 | 0.00 | 43.64 | 127639.66 | 0.00 | 0.00 | 0.00 | 0.00 | 5.36 | 01-JAN-16:43 | 5.36 | 01-JAN-16:43 | 0.00 | 0.00 | 0.00 |
February | 554628.57 | 0.00 | 37.51 | 554628.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7452.31 | 24-FEB-10:01 | 7452.31 | 24-FEB-10:01 | 0.00 | 0.00 | 0.00 |
March | 0.136351E+11 | 0.00 | 82.80 | 0.136351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 642619.62 | 24-MAR-14:01 | 642619.62 | 24-MAR-14:01 | 0.00 | 0.00 | 0.00 |
April | 0.147229E+12 | 0.00 | 179.35 | 0.134721E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1498924.52 | 18-APR-14:05 | 1257048.60 | 18-APR-14:05 | 0.00 | 0.00 | 0.00 |
May | 0.357255E+12 | 0.00 | 272.38 | 0.325491E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1403143.10 | 31-MAY-14:05 | 1283721.90 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.953554E+12 | 0.00 | 372.84 | 0.802116E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2146880.78 | 13-JUN-05:01 | 1423933.09 | 30-JUN-04:11 | 0.00 | 0.00 | 0.00 |
July | 0.128437E+13 | 0.00 | 441.84 | 0.100749E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2047954.22 | 27-JUL-05:03 | 1328430.81 | 26-JUL-04:11 | 0.00 | 0.00 | 0.00 |
August | 0.124624E+13 | 0.00 | 435.02 | 0.985155E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2598503.78 | 03-AUG-05:02 | 1586144.32 | 03-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.525828E+12 | 0.00 | 259.98 | 0.504184E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1595941.38 | 06-SEP-14:05 | 1452921.56 | 07-SEP-14:05 | 0.00 | 0.00 | 0.00 |
October | 0.600434E+11 | 0.00 | 103.38 | 0.600434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 981527.99 | 20-OCT-15:00 | 981527.99 | 20-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.627949E+10 | 0.00 | 60.95 | 0.627949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 734801.32 | 03-NOV-14:02 | 734801.32 | 03-NOV-14:02 | 0.00 | 0.00 | 0.00 |
December | 114693.28 | 0.00 | 40.74 | 114693.28 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 02-DEC-16:07 | 5.59 | 02-DEC-16:07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.459444E+13 | 0.00 | 2330.44 | 0.383911E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 114693.28 | 0.00 | 37.51 | 114693.28 | 0.00 | 0.00 | 0.00 | 0.00 | 5.36 | 5.36 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.128437E+13 | 0.00 | 441.84 | 0.100749E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2598503.78 | 1586144.32 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3783396.36 | 0.00 | 3.95 | 3783396.36 | 0.00 | 0.00 | 0.00 | 0.00 | 3347.61 | 02-JAN-06:01 | 3347.61 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 |
February | 3968659.65 | 0.00 | 8.70 | 3968659.65 | 0.00 | 0.00 | 0.00 | 0.00 | 8640.76 | 06-FEB-06:12 | 8640.76 | 06-FEB-06:12 | 0.00 | 0.00 | 0.00 |
March | 0.633974E+09 | 0.00 | 21.43 | 0.633974E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28778.33 | 25-MAR-14:57 | 28778.33 | 25-MAR-14:57 | 0.00 | 0.00 | 0.00 |
April | 0.160024E+11 | 0.00 | 93.03 | 0.148713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 183505.27 | 16-APR-16:21 | 151047.48 | 18-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.391425E+11 | 0.00 | 246.74 | 0.364163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 173833.49 | 31-MAY-15:00 | 163358.85 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.108946E+12 | 0.00 | 355.34 | 0.943255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 291819.28 | 25-JUN-15:01 | 219349.98 | 25-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.144089E+12 | 0.00 | 429.80 | 0.117918E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 284430.01 | 20-JUL-05:02 | 199564.03 | 02-JUL-14:31 | 0.00 | 0.00 | 0.00 |
August | 0.137558E+12 | 0.00 | 422.87 | 0.112298E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 352989.54 | 03-AUG-04:01 | 190722.33 | 04-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.565082E+11 | 0.00 | 236.88 | 0.547364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 218712.19 | 11-SEP-05:02 | 176503.75 | 07-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.432015E+10 | 0.00 | 56.02 | 0.432015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 101476.74 | 20-OCT-15:00 | 101476.74 | 20-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.146621E+09 | 0.00 | 21.51 | 0.146621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12066.10 | 03-NOV-14:45 | 12066.10 | 03-NOV-14:45 | 0.00 | 0.00 | 0.00 |
December | 13278601.60 | 0.00 | 13.35 | 13278601.60 | 0.00 | 0.00 | 0.00 | 0.00 | 7464.80 | 09-DEC-06:12 | 7464.80 | 09-DEC-06:12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.507367E+12 | 0.00 | 1909.63 | 0.435687E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3783396.36 | 0.00 | 3.95 | 3783396.36 | 0.00 | 0.00 | 0.00 | 0.00 | 3347.61 | 3347.61 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.144089E+12 | 0.00 | 429.80 | 0.117918E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 352989.54 | 219349.98 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 91396726.16 | 0.00 | 1.44 | 91396726.16 | 0.00 | 0.00 | 0.00 | 0.00 | 57352.63 | 14-JAN-06:06 | 57352.63 | 14-JAN-06:06 | 0.00 | 0.00 | 0.00 |
February | 0.141126E+09 | 0.00 | 3.32 | 0.141126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 71888.09 | 24-FEB-06:02 | 71888.09 | 24-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.159179E+10 | 0.00 | 26.26 | 0.159179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 111024.43 | 27-MAR-04:02 | 111024.43 | 27-MAR-04:02 | 0.00 | 0.00 | 0.00 |
April | 0.839460E+10 | 0.00 | 92.05 | 0.729454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 101866.56 | 19-APR-05:00 | 101866.56 | 19-APR-05:00 | 0.00 | 0.00 | 0.00 |
May | 0.265414E+11 | 0.00 | 237.58 | 0.205393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109014.91 | 11-MAY-15:55 | 81197.26 | 10-MAY-04:17 | 0.00 | 0.00 | 0.00 |
June | 0.584613E+11 | 0.00 | 343.21 | 0.427109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 156178.16 | 27-JUN-04:51 | 118280.74 | 07-JUN-04:54 | 0.00 | 0.00 | 0.00 |
July | 0.797603E+11 | 0.00 | 377.18 | 0.537192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 141753.47 | 06-JUL-04:53 | 97522.12 | 26-JUL-04:11 | 0.00 | 0.00 | 0.00 |
August | 0.866746E+11 | 0.00 | 416.63 | 0.604414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 147078.68 | 21-AUG-03:50 | 117329.13 | 03-AUG-03:01 | 0.00 | 0.00 | 0.00 |
September | 0.406882E+11 | 0.00 | 291.13 | 0.358761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132418.92 | 04-SEP-16:49 | 132418.92 | 04-SEP-16:49 | 0.00 | 0.00 | 0.00 |
October | 0.130509E+11 | 0.00 | 146.96 | 0.127358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133113.02 | 13-OCT-03:13 | 133113.02 | 13-OCT-03:13 | 0.00 | 0.00 | 0.00 |
November | 0.524580E+10 | 0.00 | 87.42 | 0.511697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 110622.20 | 22-NOV-05:46 | 110622.20 | 22-NOV-05:46 | 0.00 | 0.00 | 0.00 |
December | 0.626302E+09 | 0.00 | 12.54 | 0.626302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 111808.05 | 06-DEC-06:00 | 111808.05 | 06-DEC-06:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.321268E+12 | 0.00 | 2035.72 | 0.240885E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 91396726.16 | 0.00 | 1.44 | 91396726.16 | 0.00 | 0.00 | 0.00 | 0.00 | 57352.63 | 57352.63 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.866746E+11 | 0.00 | 416.63 | 0.604414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 156178.16 | 133113.02 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3673730.69 | 0.00 | 172.45 | 3673730.69 | 0.00 | 0.00 | 0.00 | 0.00 | 59.12 | 07-JAN-21:52 | 59.12 | 07-JAN-21:52 | 0.00 | 0.00 | 0.00 |
February | 0.157489E+12 | 0.00 | 397.52 | 0.157489E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 319619.24 | 03-FEB-19:01 | 319619.24 | 03-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.234796E+12 | 0.00 | 626.90 | 0.234796E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 323587.96 | 06-MAR-14:22 | 323587.96 | 06-MAR-14:22 | 0.00 | 0.00 | 0.00 |
April | 0.266969E+12 | 0.00 | 720.00 | 0.266155E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 524759.64 | 18-APR-08:35 | 395993.95 | 16-APR-16:24 | 0.00 | 0.00 | 0.00 |
May | 0.257935E+11 | 0.00 | 300.37 | 0.257935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 232181.06 | 31-MAY-23:53 | 232181.06 | 31-MAY-23:53 | 0.00 | 0.00 | 0.00 |
June | 0.332473E+12 | 0.00 | 510.09 | 0.284726E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 546139.23 | 13-JUN-06:52 | 320976.17 | 22-JUN-15:03 | 0.00 | 0.00 | 0.00 |
July | 0.466481E+12 | 0.00 | 743.95 | 0.427794E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 517195.35 | 06-JUL-05:51 | 294799.82 | 04-JUL-23:07 | 0.00 | 0.00 | 0.00 |
August | 0.610095E+12 | 0.00 | 743.33 | 0.548152E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 560533.96 | 31-AUG-12:03 | 410106.39 | 04-AUG-05:05 | 0.00 | 0.00 | 0.00 |
September | 0.564076E+11 | 0.00 | 363.22 | 0.564076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 266531.88 | 30-SEP-23:21 | 266531.88 | 30-SEP-23:21 | 0.00 | 0.00 | 0.00 |
October | 0.168013E+12 | 0.00 | 448.46 | 0.167061E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 344387.31 | 20-OCT-16:13 | 344387.31 | 20-OCT-16:13 | 0.00 | 0.00 | 0.00 |
November | 0.204747E+12 | 0.00 | 716.18 | 0.204462E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 326592.57 | 01-NOV-00:22 | 326592.57 | 01-NOV-00:22 | 0.00 | 0.00 | 0.00 |
December | 0.255899E+12 | 0.00 | 744.00 | 0.255899E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 260591.73 | 19-DEC-06:10 | 260591.73 | 19-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.277917E+13 | 0.00 | 6486.48 | 0.262874E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3673730.69 | 0.00 | 172.45 | 3673730.69 | 0.00 | 0.00 | 0.00 | 0.00 | 59.12 | 59.12 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.610095E+12 | 0.00 | 744.00 | 0.548152E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 560533.96 | 410106.39 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.344206E+10 | 0.108602E+10 | 683.60 | 0.344206E+10 | -0.0 | 0.00 | 1.00 | 30-JAN-13:01 | 0.00 | 01-JAN-00:07 | 8799.44 | 30-JAN-13:01 | 8799.44 | 30-JAN-13:01 | 0.00 | 19-JAN-12:02 | 2289.18 | 30-JAN-13:01 | 0.00 | 01-JAN-00:02 |
February | 0.766102E+10 | 0.220850E+10 | 590.17 | 0.766102E+10 | -0.0 | 0.00 | 1.00 | 04-FEB-10:31 | 0.00 | 01-FEB-00:41 | 13114.04 | 04-FEB-10:31 | 13114.04 | 04-FEB-10:31 | 0.00 | 08-FEB-15:13 | 3515.78 | 04-FEB-10:31 | 0.00 | 01-FEB-00:01 |
March | 0.158367E+11 | 0.418902E+10 | 744.00 | 0.158364E+11 | 260576.55 | 0.00 | 1.00 | 05-MAR-17:21 | 0.72 | 06-MAR-07:01 | 7978.41 | 31-MAR-23:47 | 7978.41 | 31-MAR-23:47 | 42.40 | 29-MAR-16:00 | 2058.16 | 31-MAR-23:47 | 0.00 | 01-MAR-00:01 |
April | 0.211777E+11 | 0.550263E+10 | 720.00 | 0.211511E+11 | 26587787.50 | 0.00 | 1.00 | 01-APR-00:03 | 0.49 | 30-APR-24:00 | 9692.42 | 16-APR-17:53 | 9688.98 | 16-APR-18:00 | 347.62 | 18-APR-15:50 | 2845.91 | 15-APR-17:53 | 0.00 | 01-APR-00:03 |
May | 0.754346E+10 | 0.227628E+10 | 744.00 | 0.744951E+10 | 93950998.22 | 0.00 | 0.72 | 31-MAY-23:30 | 0.32 | 02-MAY-06:10 | 4855.11 | 31-MAY-23:20 | 4821.01 | 31-MAY-23:51 | 258.35 | 12-MAY-16:00 | 1348.56 | 31-MAY-23:20 | 0.00 | 01-MAY-00:10 |
June | 0.128432E+11 | 0.364407E+10 | 720.00 | 0.126384E+11 | 0.204784E+09 | 0.00 | 0.94 | 30-JUN-23:51 | 0.60 | 03-JUN-06:51 | 6732.73 | 30-JUN-23:51 | 6729.52 | 30-JUN-23:51 | 456.36 | 13-JUN-15:00 | 1869.56 | 26-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.187805E+11 | 0.495672E+10 | 744.00 | 0.184692E+11 | 0.311301E+09 | 0.00 | 1.00 | 01-JUL-17:42 | 0.89 | 24-JUL-06:10 | 8677.40 | 31-JUL-24:00 | 8614.48 | 31-JUL-24:00 | 595.60 | 26-JUL-15:40 | 2389.97 | 26-JUL-16:00 | 0.00 | 01-JUL-00:05 |
August | 0.237950E+11 | 0.634373E+10 | 744.00 | 0.234714E+11 | 0.323615E+09 | 0.00 | 1.00 | 01-AUG-00:10 | 0.52 | 31-AUG-24:00 | 10140.29 | 04-AUG-16:00 | 9746.19 | 29-AUG-17:40 | 634.00 | 04-AUG-13:00 | 3319.43 | 04-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.751511E+10 | 0.228373E+10 | 720.00 | 0.745684E+10 | 58267402.49 | 0.00 | 0.67 | 30-SEP-23:51 | 0.29 | 30-SEP-07:00 | 4203.39 | 30-SEP-23:51 | 4203.39 | 30-SEP-23:51 | 260.01 | 11-SEP-10:40 | 1340.10 | 06-SEP-15:20 | 0.00 | 01-SEP-00:10 |
October | 0.116843E+11 | 0.329108E+10 | 744.00 | 0.116785E+11 | 5872912.17 | 0.00 | 0.90 | 31-OCT-23:57 | 0.56 | 23-OCT-06:01 | 6090.18 | 31-OCT-23:52 | 6090.18 | 31-OCT-23:52 | 154.36 | 02-OCT-14:00 | 1597.13 | 31-OCT-23:52 | 0.00 | 01-OCT-00:01 |
November | 0.152345E+11 | 0.402959E+10 | 714.67 | 0.152251E+11 | 9339870.11 | 0.00 | 1.00 | 03-NOV-15:53 | 0.00 | 26-NOV-02:51 | 13741.04 | 26-NOV-08:11 | 13741.04 | 26-NOV-08:11 | 133.87 | 08-NOV-11:00 | 3699.87 | 26-NOV-08:11 | 0.00 | 01-NOV-00:01 |
December | 0.198902E+11 | 0.509560E+10 | 744.00 | 0.198902E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-00:01 | 0.89 | 11-DEC-07:02 | 8700.57 | 01-DEC-16:08 | 8700.57 | 01-DEC-16:08 | 0.00 | 03-DEC-18:35 | 2264.82 | 01-DEC-16:10 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.165404E+12 | 0.449070E+11 | 8612.43 | 0.164370E+12 | 0.103398E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.344206E+10 | 0.108602E+10 | 590.17 | 0.344206E+10 | -0.0 | 0.00 | 0.67 | 0.00 | 4203.39 | 4203.39 | 0.00 | 1340.10 | 0.00 | |||||||
Maximum of Months | 0.237950E+11 | 0.634373E+10 | 744.00 | 0.234714E+11 | 0.323615E+09 | 0.00 | 1.00 | 0.89 | 13741.04 | 13741.04 | 634.00 | 3699.87 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.137109E+11 | 0.377815E+10 | 495.47 | 0.137109E+11 | 0.00 | 0.00 | 0.49 | 19-JAN-12:02 | 0.00 | 01-JAN-00:02 | 28259.09 | 19-JAN-12:02 | 28259.09 | 19-JAN-12:02 | 0.00 | 13-JAN-17:00 | 7181.45 | 19-JAN-12:02 | 0.00 | 01-JAN-00:02 |
February | 0.584684E+11 | 0.148424E+11 | 590.17 | 0.584684E+11 | -0.0 | 0.00 | 1.00 | 04-FEB-10:31 | 0.00 | 01-FEB-00:41 | 124749.76 | 04-FEB-10:31 | 124749.76 | 04-FEB-10:31 | 0.00 | 08-FEB-15:54 | 28666.72 | 04-FEB-10:31 | 0.00 | 01-FEB-00:01 |
March | 0.137715E+12 | 0.318510E+11 | 744.00 | 0.137713E+12 | 2677893.09 | 0.00 | 1.00 | 21-MAR-17:27 | 0.56 | 06-MAR-04:16 | 72721.72 | 31-MAR-23:12 | 72721.72 | 31-MAR-23:12 | 423.43 | 29-MAR-16:00 | 15981.90 | 31-MAR-23:12 | 0.00 | 01-MAR-00:01 |
April | 0.193661E+12 | 0.429739E+11 | 720.00 | 0.193398E+12 | 0.263352E+09 | 0.00 | 1.00 | 01-APR-00:03 | 0.37 | 30-APR-24:00 | 92202.27 | 18-APR-15:40 | 91606.97 | 15-APR-18:10 | 3461.10 | 18-APR-15:50 | 23197.02 | 15-APR-17:53 | 0.00 | 01-APR-00:03 |
May | 0.659448E+11 | 0.172173E+11 | 744.00 | 0.650156E+11 | 0.929190E+09 | 0.00 | 0.72 | 31-MAY-23:20 | 0.21 | 02-MAY-06:10 | 46230.13 | 31-MAY-23:20 | 45759.87 | 31-MAY-23:40 | 2581.15 | 12-MAY-16:00 | 11027.26 | 31-MAY-23:20 | 0.00 | 01-MAY-00:10 |
June | 0.119865E+12 | 0.293073E+11 | 720.00 | 0.117826E+12 | 0.203917E+10 | 0.00 | 0.94 | 30-JUN-23:30 | 0.56 | 03-JUN-06:05 | 65168.77 | 30-JUN-23:02 | 65085.20 | 30-JUN-23:51 | 4555.49 | 13-JUN-15:00 | 15359.66 | 26-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.176618E+12 | 0.401331E+11 | 744.00 | 0.173516E+12 | 0.310146E+10 | 0.00 | 1.00 | 01-JUL-17:55 | 0.85 | 22-JUL-06:42 | 81417.47 | 31-JUL-23:50 | 80868.06 | 31-JUL-24:00 | 5943.80 | 26-JUL-15:40 | 19572.26 | 26-JUL-16:00 | 0.00 | 01-JUL-00:05 |
August | 0.223708E+12 | 0.510056E+11 | 744.00 | 0.220487E+12 | 0.322088E+10 | 0.00 | 1.00 | 01-AUG-00:10 | 0.44 | 31-AUG-24:00 | 97185.12 | 04-AUG-16:00 | 93376.79 | 29-AUG-17:40 | 6326.81 | 04-AUG-13:00 | 27244.06 | 04-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.644457E+11 | 0.169909E+11 | 720.00 | 0.638693E+11 | 0.576310E+09 | 0.00 | 0.64 | 06-SEP-17:30 | 0.19 | 30-SEP-06:10 | 39444.16 | 06-SEP-17:30 | 37874.30 | 04-SEP-17:50 | 2591.70 | 11-SEP-10:40 | 10924.40 | 06-SEP-17:00 | 0.00 | 01-SEP-00:10 |
October | 0.994194E+11 | 0.244580E+11 | 744.00 | 0.993606E+11 | 58792012.26 | 0.00 | 0.85 | 31-OCT-23:13 | 0.44 | 23-OCT-06:02 | 54222.79 | 31-OCT-23:13 | 54222.79 | 31-OCT-23:13 | 1533.57 | 02-OCT-14:00 | 12410.14 | 11-OCT-16:50 | 0.00 | 01-OCT-00:01 |
November | 0.127347E+12 | 0.296646E+11 | 714.67 | 0.127253E+12 | 93514500.64 | 0.00 | 1.00 | 26-NOV-08:11 | 0.00 | 26-NOV-02:51 | 129138.08 | 26-NOV-08:11 | 129138.08 | 26-NOV-08:11 | 1328.87 | 08-NOV-11:00 | 29698.32 | 26-NOV-08:11 | 0.00 | 01-NOV-00:01 |
December | 0.167225E+12 | 0.370855E+11 | 744.00 | 0.167225E+12 | -0.0 | 0.00 | 1.00 | 01-DEC-09:15 | 0.77 | 11-DEC-07:02 | 80742.34 | 01-DEC-16:08 | 80742.34 | 01-DEC-16:08 | 0.00 | 13-DEC-14:13 | 17949.74 | 01-DEC-16:10 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.144813E+13 | 0.339308E+12 | 8424.30 | 0.143784E+13 | 0.102854E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.137109E+11 | 0.377815E+10 | 495.47 | 0.137109E+11 | -0.0 | 0.00 | 0.49 | 0.00 | 28259.09 | 28259.09 | 0.00 | 7181.45 | 0.00 | |||||||
Maximum of Months | 0.223708E+12 | 0.510056E+11 | 744.00 | 0.220487E+12 | 0.322088E+10 | 0.00 | 1.00 | 0.85 | 129138.08 | 129138.08 | 6326.81 | 29698.32 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.655072E+09 | 0.211784E+09 | 278.17 | 0.655072E+09 | 0.00 | 0.00 | 0.42 | 12-JAN-16:30 | 0.00 | 01-JAN-00:02 | 2483.49 | 12-JAN-16:30 | 2483.49 | 12-JAN-16:30 | 0.00 | 04-JAN-16:10 | 753.52 | 12-JAN-16:30 | 0.00 | 01-JAN-00:02 |
February | 0.429078E+10 | 0.129949E+10 | 583.22 | 0.429078E+10 | -0.0 | 0.00 | 1.00 | 04-FEB-10:31 | 0.00 | 01-FEB-00:01 | 10507.25 | 04-FEB-10:31 | 10507.25 | 04-FEB-10:31 | 0.00 | 08-FEB-17:35 | 2779.89 | 04-FEB-10:31 | 0.00 | 01-FEB-00:01 |
March | 0.120082E+11 | 0.333168E+10 | 744.00 | 0.120079E+11 | 258244.50 | 0.00 | 0.96 | 21-MAR-17:38 | 0.34 | 06-MAR-04:12 | 6655.90 | 23-MAR-17:00 | 6655.90 | 23-MAR-17:00 | 42.05 | 29-MAR-16:00 | 1726.37 | 23-MAR-16:56 | 0.00 | 01-MAR-00:01 |
April | 0.180343E+11 | 0.470094E+10 | 720.00 | 0.180086E+11 | 25737058.62 | 0.00 | 1.00 | 03-APR-13:52 | 0.28 | 30-APR-24:00 | 9429.27 | 18-APR-15:40 | 9367.38 | 16-APR-18:00 | 347.29 | 18-APR-15:50 | 2745.38 | 15-APR-17:53 | 0.00 | 01-APR-00:03 |
May | 0.586428E+10 | 0.180327E+10 | 743.28 | 0.577173E+10 | 92551484.83 | 0.00 | 0.69 | 31-MAY-23:10 | 0.00 | 02-MAY-07:21 | 4549.17 | 31-MAY-23:10 | 4493.98 | 31-MAY-23:20 | 262.32 | 30-MAY-11:00 | 1276.08 | 31-MAY-23:10 | 0.00 | 01-MAY-00:10 |
June | 0.116630E+11 | 0.335772E+10 | 720.00 | 0.114590E+11 | 0.204088E+09 | 0.00 | 0.92 | 30-JUN-23:02 | 0.42 | 04-JUN-05:40 | 6460.26 | 30-JUN-23:02 | 6440.91 | 30-JUN-23:30 | 459.67 | 13-JUN-15:00 | 1867.82 | 26-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.174722E+11 | 0.467349E+10 | 744.00 | 0.171622E+11 | 0.310063E+09 | 0.00 | 1.00 | 01-JUL-17:55 | 0.77 | 24-JUL-06:10 | 8001.66 | 03-JUL-16:00 | 7859.16 | 31-JUL-23:50 | 597.75 | 26-JUL-15:40 | 2349.24 | 26-JUL-16:00 | 0.00 | 01-JUL-00:05 |
August | 0.220767E+11 | 0.585022E+10 | 744.00 | 0.217559E+11 | 0.320784E+09 | 0.00 | 1.00 | 01-AUG-00:10 | 0.39 | 31-AUG-24:00 | 9970.97 | 04-AUG-16:00 | 9478.20 | 29-AUG-17:40 | 635.31 | 04-AUG-13:00 | 3261.12 | 04-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.555530E+10 | 0.173066E+10 | 718.90 | 0.549774E+10 | 57564480.26 | 0.00 | 0.64 | 06-SEP-17:00 | 0.00 | 05-SEP-04:43 | 4119.97 | 06-SEP-17:30 | 3916.39 | 01-SEP-17:40 | 263.71 | 11-SEP-10:50 | 1333.42 | 06-SEP-17:00 | 0.00 | 01-SEP-00:10 |
October | 0.798918E+10 | 0.235778E+10 | 743.86 | 0.798339E+10 | 5787793.89 | 0.00 | 0.80 | 11-OCT-16:49 | 0.00 | 15-OCT-21:11 | 5382.91 | 11-OCT-16:50 | 5382.91 | 11-OCT-16:50 | 153.01 | 02-OCT-14:02 | 1463.32 | 11-OCT-16:50 | 0.00 | 01-OCT-00:01 |
November | 0.107505E+11 | 0.301448E+10 | 714.67 | 0.107413E+11 | 9223961.15 | 0.00 | 1.00 | 26-NOV-08:11 | 0.00 | 26-NOV-02:51 | 12894.34 | 26-NOV-08:11 | 12894.34 | 26-NOV-08:11 | 132.01 | 08-NOV-11:00 | 3456.88 | 26-NOV-08:11 | 0.00 | 01-NOV-00:01 |
December | 0.146601E+11 | 0.390797E+10 | 744.00 | 0.146601E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-13:10 | 0.58 | 11-DEC-03:31 | 7851.66 | 01-DEC-16:08 | 7851.66 | 01-DEC-16:08 | 0.00 | 28-DEC-15:35 | 2024.15 | 01-DEC-16:10 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.131020E+12 | 0.362395E+11 | 8198.10 | 0.129993E+12 | 0.102606E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.655072E+09 | 0.211784E+09 | 278.17 | 0.655072E+09 | -0.0 | 0.00 | 0.42 | 0.00 | 2483.49 | 2483.49 | 0.00 | 753.52 | 0.00 | |||||||
Maximum of Months | 0.220767E+11 | 0.585022E+10 | 744.00 | 0.217559E+11 | 0.320784E+09 | 0.00 | 1.00 | 0.77 | 12894.34 | 12894.34 | 635.31 | 3456.88 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 133.97 | 0.00 | 133.97 | 0.00 | 1726.79 | 0.00 | 0.00 | 0.00 |
February | 169.85 | 0.00 | 169.85 | 0.22 | 1427.89 | 0.00 | 0.00 | 0.00 |
March | 254.55 | 0.00 | 254.55 | 27.91 | 953.34 | 0.00 | 0.00 | 0.00 |
April | 293.87 | 1.45 | 292.42 | 103.68 | 665.66 | 0.00 | 0.00 | 0.00 |
May | 383.21 | 14.40 | 368.80 | 264.75 | 343.40 | 0.00 | 0.00 | 0.00 |
June | 447.88 | 40.65 | 407.23 | 462.46 | 238.50 | 0.00 | 0.00 | 0.00 |
July | 420.04 | 28.10 | 391.94 | 459.44 | 198.12 | 0.00 | 0.00 | 0.00 |
August | 351.70 | 6.23 | 345.46 | 382.15 | 240.30 | 0.00 | 0.00 | 0.00 |
September | 269.65 | 0.07 | 269.58 | 211.61 | 430.32 | 0.00 | 0.00 | 0.00 |
October | 200.49 | 0.00 | 200.49 | 38.67 | 703.93 | 0.00 | 0.00 | 0.00 |
November | 140.25 | 0.00 | 140.25 | 4.63 | 1097.30 | 0.00 | 0.00 | 0.00 |
December | 90.97 | 0.00 | 90.97 | 0.00 | 1542.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 263.53 | 7.60 | 255.92 | 163.94 | 794.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.97 | 0.00 | 90.97 | 0.00 | 198.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 447.88 | 40.65 | 407.23 | 462.46 | 1726.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 133.97 | 0.00 | 133.97 | 0.00 | 1726.79 | 0.00 | 0.00 | 0.00 |
February | 169.85 | 0.00 | 169.85 | 0.22 | 1427.89 | 0.00 | 0.00 | 0.00 |
March | 254.55 | 0.00 | 254.55 | 27.91 | 953.34 | 0.00 | 0.00 | 0.00 |
April | 293.86 | 1.45 | 292.42 | 103.68 | 665.66 | 0.00 | 0.00 | 0.00 |
May | 383.21 | 14.40 | 368.80 | 264.75 | 343.40 | 0.00 | 0.00 | 0.00 |
June | 447.88 | 40.65 | 407.23 | 462.46 | 238.50 | 0.00 | 0.00 | 0.00 |
July | 420.04 | 28.10 | 391.94 | 459.44 | 198.12 | 0.00 | 0.00 | 0.00 |
August | 351.70 | 6.23 | 345.46 | 382.15 | 240.30 | 0.00 | 0.00 | 0.00 |
September | 269.65 | 0.07 | 269.58 | 211.61 | 430.32 | 0.00 | 0.00 | 0.00 |
October | 200.49 | 0.00 | 200.49 | 38.66 | 703.93 | 0.00 | 0.00 | 0.00 |
November | 140.25 | 0.00 | 140.25 | 4.63 | 1097.30 | 0.00 | 0.00 | 0.00 |
December | 90.97 | 0.00 | 90.97 | 0.00 | 1542.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 263.53 | 7.60 | 255.92 | 163.94 | 794.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.97 | 0.00 | 90.97 | 0.00 | 198.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 447.88 | 40.65 | 407.23 | 462.46 | 1726.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 133.97 | 0.00 | 133.97 | 0.00 | 1726.79 | 0.00 | 0.00 | 0.00 |
February | 169.85 | 0.00 | 169.85 | 0.22 | 1427.89 | 0.00 | 0.00 | 0.00 |
March | 254.55 | 0.00 | 254.55 | 27.91 | 953.34 | 0.00 | 0.00 | 0.00 |
April | 293.87 | 1.45 | 292.42 | 103.68 | 665.66 | 0.00 | 0.00 | 0.00 |
May | 383.21 | 14.40 | 368.80 | 264.75 | 343.40 | 0.00 | 0.00 | 0.00 |
June | 447.88 | 40.65 | 407.23 | 462.46 | 238.50 | 0.00 | 0.00 | 0.00 |
July | 420.04 | 28.10 | 391.94 | 459.44 | 198.12 | 0.00 | 0.00 | 0.00 |
August | 351.70 | 6.23 | 345.46 | 382.15 | 240.30 | 0.00 | 0.00 | 0.00 |
September | 269.65 | 0.07 | 269.58 | 211.61 | 430.32 | 0.00 | 0.00 | 0.00 |
October | 200.49 | 0.00 | 200.49 | 38.67 | 703.93 | 0.00 | 0.00 | 0.00 |
November | 140.25 | 0.00 | 140.25 | 4.63 | 1097.30 | 0.00 | 0.00 | 0.00 |
December | 90.97 | 0.00 | 90.97 | 0.00 | 1542.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 263.53 | 7.60 | 255.92 | 163.94 | 794.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.97 | 0.00 | 90.97 | 0.00 | 198.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 447.88 | 40.65 | 407.23 | 462.46 | 1726.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 133.97 | 0.00 | 133.97 | 0.00 | 1726.79 | 0.00 | 0.00 | 0.00 |
February | 169.85 | 0.00 | 169.85 | 0.22 | 1427.89 | 0.00 | 0.00 | 0.00 |
March | 254.55 | 0.00 | 254.55 | 27.91 | 953.34 | 0.00 | 0.00 | 0.00 |
April | 293.86 | 1.45 | 292.42 | 103.68 | 665.66 | 0.00 | 0.00 | 0.00 |
May | 383.21 | 14.40 | 368.80 | 264.75 | 343.40 | 0.00 | 0.00 | 0.00 |
June | 447.88 | 40.65 | 407.23 | 462.46 | 238.50 | 0.00 | 0.00 | 0.00 |
July | 420.04 | 28.10 | 391.94 | 459.44 | 198.12 | 0.00 | 0.00 | 0.00 |
August | 351.70 | 6.23 | 345.46 | 382.15 | 240.30 | 0.00 | 0.00 | 0.00 |
September | 269.65 | 0.07 | 269.58 | 211.61 | 430.32 | 0.00 | 0.00 | 0.00 |
October | 200.49 | 0.00 | 200.49 | 38.66 | 703.93 | 0.00 | 0.00 | 0.00 |
November | 140.25 | 0.00 | 140.25 | 4.63 | 1097.30 | 0.00 | 0.00 | 0.00 |
December | 90.97 | 0.00 | 90.97 | 0.00 | 1542.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 263.53 | 7.60 | 255.92 | 163.94 | 794.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.97 | 0.00 | 90.97 | 0.00 | 198.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 447.88 | 40.65 | 407.23 | 462.46 | 1726.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 133.97 | 0.00 | 133.97 | 0.00 | 1726.72 | 0.00 | 0.00 | 0.00 |
February | 169.84 | 0.00 | 169.84 | 0.22 | 1427.83 | 0.00 | 0.00 | 0.00 |
March | 254.54 | 0.00 | 254.54 | 27.91 | 953.30 | 0.00 | 0.00 | 0.00 |
April | 293.85 | 1.45 | 292.41 | 103.68 | 665.63 | 0.00 | 0.00 | 0.00 |
May | 383.19 | 14.40 | 368.79 | 264.74 | 343.39 | 0.00 | 0.00 | 0.00 |
June | 447.86 | 40.65 | 407.21 | 462.44 | 238.49 | 0.00 | 0.00 | 0.00 |
July | 420.02 | 28.10 | 391.93 | 459.42 | 198.11 | 0.00 | 0.00 | 0.00 |
August | 351.68 | 6.23 | 345.45 | 382.13 | 240.29 | 0.00 | 0.00 | 0.00 |
September | 269.64 | 0.07 | 269.57 | 211.60 | 430.30 | 0.00 | 0.00 | 0.00 |
October | 200.48 | 0.00 | 200.48 | 38.66 | 703.90 | 0.00 | 0.00 | 0.00 |
November | 140.24 | 0.00 | 140.24 | 4.63 | 1097.25 | 0.00 | 0.00 | 0.00 |
December | 90.97 | 0.00 | 90.97 | 0.00 | 1542.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 263.52 | 7.60 | 255.91 | 163.93 | 794.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.97 | 0.00 | 90.97 | 0.00 | 198.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 447.86 | 40.65 | 407.21 | 462.44 | 1726.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 318.97 | 131.26 | 187.71 | 78.50 | 1721.87 | 0.00 | 0.00 | 0.00 |
February | 422.80 | 185.91 | 236.88 | 164.67 | 1389.07 | 0.00 | 0.00 | 0.00 |
March | 574.45 | 228.02 | 346.43 | 331.26 | 937.15 | 0.00 | 0.00 | 0.00 |
April | 705.37 | 308.90 | 396.47 | 581.38 | 671.53 | 0.00 | 0.00 | 0.00 |
May | 885.89 | 387.09 | 498.80 | 903.14 | 365.96 | 0.00 | 0.00 | 0.00 |
June | 974.90 | 424.55 | 550.34 | 1166.32 | 254.76 | 0.00 | 0.00 | 0.00 |
July | 985.37 | 454.67 | 530.70 | 1220.28 | 206.27 | 0.00 | 0.00 | 0.00 |
August | 830.65 | 358.11 | 472.54 | 1029.23 | 244.96 | 0.00 | 0.00 | 0.00 |
September | 740.86 | 350.10 | 390.77 | 816.40 | 438.63 | 0.00 | 0.00 | 0.00 |
October | 472.13 | 197.20 | 274.92 | 323.59 | 700.13 | 0.00 | 0.00 | 0.00 |
November | 278.56 | 90.48 | 188.08 | 92.50 | 1113.56 | 0.00 | 0.00 | 0.00 |
December | 215.78 | 92.66 | 123.12 | 59.15 | 1570.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 618.11 | 267.80 | 350.31 | 566.05 | 798.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 215.78 | 90.48 | 123.12 | 59.15 | 206.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 985.37 | 454.67 | 550.34 | 1220.28 | 1721.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 318.97 | 131.26 | 187.71 | 78.50 | 1721.87 | 0.00 | 0.00 | 0.00 |
February | 422.80 | 185.91 | 236.88 | 164.67 | 1389.07 | 0.00 | 0.00 | 0.00 |
March | 574.45 | 228.02 | 346.43 | 331.26 | 937.15 | 0.00 | 0.00 | 0.00 |
April | 705.37 | 308.90 | 396.47 | 581.38 | 671.53 | 0.00 | 0.00 | 0.00 |
May | 885.89 | 387.09 | 498.80 | 903.14 | 365.96 | 0.00 | 0.00 | 0.00 |
June | 974.90 | 424.55 | 550.34 | 1166.32 | 254.76 | 0.00 | 0.00 | 0.00 |
July | 985.37 | 454.67 | 530.70 | 1220.28 | 206.27 | 0.00 | 0.00 | 0.00 |
August | 830.65 | 358.11 | 472.54 | 1029.23 | 244.96 | 0.00 | 0.00 | 0.00 |
September | 740.86 | 350.10 | 390.77 | 816.40 | 438.63 | 0.00 | 0.00 | 0.00 |
October | 472.13 | 197.20 | 274.92 | 323.59 | 700.13 | 0.00 | 0.00 | 0.00 |
November | 278.56 | 90.48 | 188.08 | 92.50 | 1113.56 | 0.00 | 0.00 | 0.00 |
December | 215.78 | 92.66 | 123.12 | 59.15 | 1570.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 618.11 | 267.80 | 350.31 | 566.05 | 798.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 215.78 | 90.48 | 123.12 | 59.15 | 206.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 985.37 | 454.67 | 550.34 | 1220.28 | 1721.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 318.97 | 131.26 | 187.71 | 78.50 | 1721.84 | 0.00 | 0.00 | 0.00 |
February | 422.79 | 185.91 | 236.88 | 164.67 | 1389.04 | 0.00 | 0.00 | 0.00 |
March | 574.44 | 228.01 | 346.43 | 331.26 | 937.14 | 0.00 | 0.00 | 0.00 |
April | 705.36 | 308.90 | 396.46 | 581.37 | 671.52 | 0.00 | 0.00 | 0.00 |
May | 885.87 | 387.09 | 498.79 | 903.12 | 365.95 | 0.00 | 0.00 | 0.00 |
June | 974.88 | 424.54 | 550.33 | 1166.30 | 254.75 | 0.00 | 0.00 | 0.00 |
July | 985.35 | 454.66 | 530.69 | 1220.26 | 206.27 | 0.00 | 0.00 | 0.00 |
August | 830.63 | 358.10 | 472.53 | 1029.21 | 244.96 | 0.00 | 0.00 | 0.00 |
September | 740.85 | 350.09 | 390.76 | 816.38 | 438.62 | 0.00 | 0.00 | 0.00 |
October | 472.12 | 197.20 | 274.92 | 323.58 | 700.12 | 0.00 | 0.00 | 0.00 |
November | 278.56 | 90.48 | 188.08 | 92.50 | 1113.54 | 0.00 | 0.00 | 0.00 |
December | 215.77 | 92.66 | 123.11 | 59.15 | 1570.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 618.10 | 267.79 | 350.30 | 566.04 | 798.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 215.77 | 90.48 | 123.11 | 59.15 | 206.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 985.35 | 454.66 | 550.33 | 1220.26 | 1721.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 833.17 | 570.16 | 263.01 | 592.55 | 1357.65 | 0.00 | 0.00 | 0.00 |
February | 892.73 | 603.13 | 289.59 | 675.38 | 1109.87 | 0.00 | 0.00 | 0.00 |
March | 776.87 | 409.08 | 367.80 | 629.93 | 824.89 | 0.00 | 0.00 | 0.00 |
April | 699.91 | 327.22 | 372.69 | 677.21 | 631.27 | 0.00 | 0.00 | 0.00 |
May | 579.85 | 157.21 | 422.65 | 604.37 | 360.72 | 0.00 | 0.00 | 0.00 |
June | 562.95 | 114.62 | 448.33 | 686.40 | 250.63 | 0.00 | 0.00 | 0.00 |
July | 595.92 | 150.16 | 445.76 | 766.60 | 207.85 | 0.00 | 0.00 | 0.00 |
August | 671.41 | 240.78 | 430.62 | 884.87 | 250.09 | 0.00 | 0.00 | 0.00 |
September | 813.60 | 428.70 | 384.90 | 983.42 | 416.40 | 0.00 | 0.00 | 0.00 |
October | 849.57 | 532.99 | 316.58 | 841.43 | 620.41 | 0.00 | 0.00 | 0.00 |
November | 641.00 | 401.28 | 239.72 | 503.66 | 917.64 | 0.00 | 0.00 | 0.00 |
December | 683.53 | 517.77 | 165.77 | 549.30 | 1276.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 715.67 | 369.77 | 345.91 | 699.65 | 683.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 562.95 | 114.62 | 165.77 | 503.66 | 207.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 892.73 | 603.13 | 448.33 | 983.42 | 1357.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 833.17 | 570.16 | 263.01 | 592.55 | 1357.65 | 0.00 | 0.00 | 0.00 |
February | 892.73 | 603.13 | 289.59 | 675.38 | 1109.87 | 0.00 | 0.00 | 0.00 |
March | 776.87 | 409.08 | 367.80 | 629.93 | 824.89 | 0.00 | 0.00 | 0.00 |
April | 699.91 | 327.22 | 372.69 | 677.21 | 631.27 | 0.00 | 0.00 | 0.00 |
May | 579.85 | 157.21 | 422.65 | 604.37 | 360.72 | 0.00 | 0.00 | 0.00 |
June | 562.95 | 114.62 | 448.33 | 686.40 | 250.63 | 0.00 | 0.00 | 0.00 |
July | 595.92 | 150.16 | 445.76 | 766.60 | 207.85 | 0.00 | 0.00 | 0.00 |
August | 671.40 | 240.78 | 430.62 | 884.87 | 250.09 | 0.00 | 0.00 | 0.00 |
September | 813.60 | 428.70 | 384.90 | 983.42 | 416.40 | 0.00 | 0.00 | 0.00 |
October | 849.57 | 532.99 | 316.58 | 841.43 | 620.41 | 0.00 | 0.00 | 0.00 |
November | 641.00 | 401.28 | 239.72 | 503.66 | 917.64 | 0.00 | 0.00 | 0.00 |
December | 683.53 | 517.77 | 165.76 | 549.30 | 1276.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 715.67 | 369.77 | 345.91 | 699.65 | 683.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 562.95 | 114.62 | 165.76 | 503.66 | 207.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 892.73 | 603.13 | 448.33 | 983.42 | 1357.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 833.17 | 570.16 | 263.01 | 592.55 | 1357.65 | 0.00 | 0.00 | 0.00 |
February | 892.73 | 603.13 | 289.59 | 675.38 | 1109.87 | 0.00 | 0.00 | 0.00 |
March | 776.87 | 409.08 | 367.80 | 629.93 | 824.89 | 0.00 | 0.00 | 0.00 |
April | 699.91 | 327.22 | 372.69 | 677.21 | 631.27 | 0.00 | 0.00 | 0.00 |
May | 579.85 | 157.21 | 422.65 | 604.37 | 360.72 | 0.00 | 0.00 | 0.00 |
June | 562.95 | 114.62 | 448.33 | 686.40 | 250.63 | 0.00 | 0.00 | 0.00 |
July | 595.92 | 150.16 | 445.76 | 766.60 | 207.85 | 0.00 | 0.00 | 0.00 |
August | 671.41 | 240.78 | 430.62 | 884.87 | 250.09 | 0.00 | 0.00 | 0.00 |
September | 813.60 | 428.70 | 384.90 | 983.42 | 416.40 | 0.00 | 0.00 | 0.00 |
October | 849.57 | 532.99 | 316.58 | 841.43 | 620.41 | 0.00 | 0.00 | 0.00 |
November | 641.00 | 401.28 | 239.72 | 503.66 | 917.64 | 0.00 | 0.00 | 0.00 |
December | 683.53 | 517.77 | 165.77 | 549.30 | 1276.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 715.67 | 369.77 | 345.91 | 699.65 | 683.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 562.95 | 114.62 | 165.77 | 503.66 | 207.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 892.73 | 603.13 | 448.33 | 983.42 | 1357.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 833.17 | 570.16 | 263.01 | 592.55 | 1357.65 | 0.00 | 0.00 | 0.00 |
February | 892.73 | 603.13 | 289.59 | 675.38 | 1109.87 | 0.00 | 0.00 | 0.00 |
March | 776.87 | 409.08 | 367.80 | 629.93 | 824.89 | 0.00 | 0.00 | 0.00 |
April | 699.91 | 327.22 | 372.69 | 677.21 | 631.27 | 0.00 | 0.00 | 0.00 |
May | 579.85 | 157.21 | 422.65 | 604.37 | 360.72 | 0.00 | 0.00 | 0.00 |
June | 562.95 | 114.62 | 448.33 | 686.40 | 250.63 | 0.00 | 0.00 | 0.00 |
July | 595.92 | 150.16 | 445.76 | 766.60 | 207.85 | 0.00 | 0.00 | 0.00 |
August | 671.40 | 240.78 | 430.62 | 884.87 | 250.09 | 0.00 | 0.00 | 0.00 |
September | 813.60 | 428.70 | 384.90 | 983.42 | 416.40 | 0.00 | 0.00 | 0.00 |
October | 849.57 | 532.99 | 316.58 | 841.43 | 620.41 | 0.00 | 0.00 | 0.00 |
November | 641.00 | 401.28 | 239.72 | 503.66 | 917.64 | 0.00 | 0.00 | 0.00 |
December | 683.53 | 517.77 | 165.76 | 549.30 | 1276.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 715.67 | 369.77 | 345.91 | 699.65 | 683.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 562.95 | 114.62 | 165.76 | 503.66 | 207.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 892.73 | 603.13 | 448.33 | 983.42 | 1357.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 833.14 | 570.13 | 263.00 | 592.53 | 1357.59 | 0.00 | 0.00 | 0.00 |
February | 892.69 | 603.11 | 289.58 | 675.36 | 1109.82 | 0.00 | 0.00 | 0.00 |
March | 776.84 | 409.06 | 367.78 | 629.91 | 824.86 | 0.00 | 0.00 | 0.00 |
April | 699.88 | 327.21 | 372.67 | 677.19 | 631.25 | 0.00 | 0.00 | 0.00 |
May | 579.83 | 157.20 | 422.63 | 604.35 | 360.71 | 0.00 | 0.00 | 0.00 |
June | 562.93 | 114.61 | 448.31 | 686.37 | 250.62 | 0.00 | 0.00 | 0.00 |
July | 595.90 | 150.15 | 445.75 | 766.57 | 207.84 | 0.00 | 0.00 | 0.00 |
August | 671.38 | 240.77 | 430.61 | 884.83 | 250.08 | 0.00 | 0.00 | 0.00 |
September | 813.57 | 428.68 | 384.88 | 983.38 | 416.38 | 0.00 | 0.00 | 0.00 |
October | 849.54 | 532.97 | 316.57 | 841.40 | 620.39 | 0.00 | 0.00 | 0.00 |
November | 640.97 | 401.26 | 239.71 | 503.64 | 917.61 | 0.00 | 0.00 | 0.00 |
December | 683.51 | 517.75 | 165.76 | 549.28 | 1276.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 715.64 | 369.75 | 345.89 | 699.62 | 683.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 562.93 | 114.61 | 165.76 | 503.64 | 207.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 892.69 | 603.11 | 448.31 | 983.38 | 1357.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 316.34 | 128.00 | 188.35 | 86.04 | 1828.78 | 0.00 | 0.00 | 0.00 |
February | 463.86 | 228.58 | 235.28 | 212.75 | 1505.22 | 0.00 | 0.00 | 0.00 |
March | 553.75 | 206.03 | 347.73 | 299.51 | 1047.37 | 0.00 | 0.00 | 0.00 |
April | 807.76 | 399.42 | 408.34 | 718.33 | 790.04 | 0.00 | 0.00 | 0.00 |
May | 810.10 | 323.61 | 486.48 | 823.84 | 425.90 | 0.00 | 0.00 | 0.00 |
June | 950.55 | 411.95 | 538.61 | 1135.05 | 315.64 | 0.00 | 0.00 | 0.00 |
July | 1020.60 | 484.80 | 535.80 | 1255.37 | 282.43 | 0.00 | 0.00 | 0.00 |
August | 892.27 | 409.49 | 482.77 | 1096.97 | 333.21 | 0.00 | 0.00 | 0.00 |
September | 722.26 | 342.82 | 379.44 | 800.03 | 505.21 | 0.00 | 0.00 | 0.00 |
October | 503.30 | 223.76 | 279.54 | 374.73 | 789.99 | 0.00 | 0.00 | 0.00 |
November | 301.26 | 111.41 | 189.85 | 125.17 | 1212.49 | 0.00 | 0.00 | 0.00 |
December | 231.68 | 109.22 | 122.47 | 78.02 | 1697.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 631.82 | 281.64 | 350.17 | 585.65 | 891.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 231.68 | 109.22 | 122.47 | 78.02 | 282.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1020.60 | 484.80 | 538.61 | 1255.37 | 1828.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 316.34 | 128.00 | 188.35 | 86.04 | 1828.78 | 0.00 | 0.00 | 0.00 |
February | 463.86 | 228.58 | 235.28 | 212.75 | 1505.22 | 0.00 | 0.00 | 0.00 |
March | 553.75 | 206.03 | 347.73 | 299.51 | 1047.37 | 0.00 | 0.00 | 0.00 |
April | 807.76 | 399.42 | 408.34 | 718.33 | 790.04 | 0.00 | 0.00 | 0.00 |
May | 810.10 | 323.61 | 486.48 | 823.84 | 425.90 | 0.00 | 0.00 | 0.00 |
June | 950.55 | 411.95 | 538.61 | 1135.05 | 315.64 | 0.00 | 0.00 | 0.00 |
July | 1020.60 | 484.80 | 535.80 | 1255.37 | 282.43 | 0.00 | 0.00 | 0.00 |
August | 892.27 | 409.49 | 482.77 | 1096.97 | 333.21 | 0.00 | 0.00 | 0.00 |
September | 722.26 | 342.82 | 379.44 | 800.03 | 505.21 | 0.00 | 0.00 | 0.00 |
October | 503.30 | 223.76 | 279.54 | 374.73 | 789.99 | 0.00 | 0.00 | 0.00 |
November | 301.26 | 111.41 | 189.85 | 125.17 | 1212.49 | 0.00 | 0.00 | 0.00 |
December | 231.68 | 109.22 | 122.47 | 78.02 | 1697.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 631.82 | 281.64 | 350.17 | 585.65 | 891.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 231.68 | 109.22 | 122.47 | 78.02 | 282.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1020.60 | 484.80 | 538.61 | 1255.37 | 1828.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 316.34 | 127.99 | 188.34 | 86.04 | 1828.75 | 0.00 | 0.00 | 0.00 |
February | 463.85 | 228.57 | 235.28 | 212.75 | 1505.19 | 0.00 | 0.00 | 0.00 |
March | 553.74 | 206.02 | 347.72 | 299.50 | 1047.35 | 0.00 | 0.00 | 0.00 |
April | 807.75 | 399.42 | 408.33 | 718.32 | 790.03 | 0.00 | 0.00 | 0.00 |
May | 810.08 | 323.61 | 486.47 | 823.83 | 425.89 | 0.00 | 0.00 | 0.00 |
June | 950.54 | 411.94 | 538.60 | 1135.03 | 315.63 | 0.00 | 0.00 | 0.00 |
July | 1020.59 | 484.79 | 535.79 | 1255.35 | 282.42 | 0.00 | 0.00 | 0.00 |
August | 892.25 | 409.48 | 482.76 | 1096.95 | 333.21 | 0.00 | 0.00 | 0.00 |
September | 722.25 | 342.82 | 379.43 | 800.02 | 505.21 | 0.00 | 0.00 | 0.00 |
October | 503.29 | 223.76 | 279.53 | 374.72 | 789.98 | 0.00 | 0.00 | 0.00 |
November | 301.25 | 111.40 | 189.85 | 125.17 | 1212.47 | 0.00 | 0.00 | 0.00 |
December | 231.68 | 109.22 | 122.46 | 78.02 | 1697.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 631.80 | 281.64 | 350.16 | 585.64 | 891.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 231.68 | 109.22 | 122.46 | 78.02 | 282.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1020.59 | 484.79 | 538.60 | 1255.35 | 1828.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 669.85 | 0.00 | 669.85 | 0.00 | 8489.76 | 0.00 | 0.00 | 0.00 |
February | 849.24 | 0.00 | 849.24 | 4.74 | 6933.74 | 0.00 | 0.00 | 0.00 |
March | 1272.75 | 0.00 | 1272.75 | 171.74 | 4517.03 | 0.00 | 0.00 | 0.00 |
April | 1469.31 | 7.24 | 1462.07 | 593.98 | 3050.00 | 0.00 | 0.00 | 0.00 |
May | 1916.01 | 72.02 | 1843.99 | 1428.98 | 1571.84 | 0.00 | 0.00 | 0.00 |
June | 2239.37 | 203.25 | 2036.12 | 2402.14 | 1085.45 | 0.00 | 0.00 | 0.00 |
July | 2100.18 | 140.48 | 1959.70 | 2408.77 | 890.17 | 0.00 | 0.00 | 0.00 |
August | 1758.47 | 31.16 | 1727.30 | 2029.55 | 1052.81 | 0.00 | 0.00 | 0.00 |
September | 1348.24 | 0.33 | 1347.90 | 1153.10 | 1938.14 | 0.00 | 0.00 | 0.00 |
October | 1002.44 | 0.00 | 1002.44 | 263.62 | 3161.69 | 0.00 | 0.00 | 0.00 |
November | 701.22 | 0.00 | 701.22 | 42.57 | 5070.10 | 0.00 | 0.00 | 0.00 |
December | 454.85 | 0.00 | 454.85 | 0.00 | 7365.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1317.63 | 38.02 | 1279.60 | 880.19 | 3745.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 454.85 | 0.00 | 454.85 | 0.00 | 890.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2239.37 | 203.25 | 2036.12 | 2408.77 | 8489.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 956.91 | 393.77 | 563.14 | 234.57 | 5049.03 | 0.00 | 0.00 | 0.00 |
February | 1268.37 | 557.73 | 710.64 | 496.98 | 4033.38 | 0.00 | 0.00 | 0.00 |
March | 1723.33 | 684.04 | 1039.29 | 992.22 | 2705.00 | 0.00 | 0.00 | 0.00 |
April | 2116.09 | 926.70 | 1189.38 | 1726.78 | 1921.92 | 0.00 | 0.00 | 0.00 |
May | 2657.64 | 1161.27 | 1496.37 | 2666.63 | 1056.01 | 0.00 | 0.00 | 0.00 |
June | 2924.66 | 1273.64 | 1651.02 | 3463.62 | 734.95 | 0.00 | 0.00 | 0.00 |
July | 2956.08 | 1364.00 | 1592.08 | 3624.01 | 600.66 | 0.00 | 0.00 | 0.00 |
August | 2491.92 | 1074.32 | 1417.60 | 3065.52 | 705.84 | 0.00 | 0.00 | 0.00 |
September | 2222.57 | 1050.28 | 1172.29 | 2437.27 | 1246.18 | 0.00 | 0.00 | 0.00 |
October | 1416.37 | 591.61 | 824.77 | 988.03 | 1954.14 | 0.00 | 0.00 | 0.00 |
November | 835.67 | 271.44 | 564.23 | 290.75 | 3137.61 | 0.00 | 0.00 | 0.00 |
December | 647.32 | 277.98 | 369.35 | 185.89 | 4498.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1854.30 | 803.38 | 1050.92 | 1687.48 | 2295.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 647.32 | 271.44 | 369.35 | 185.89 | 600.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2956.08 | 1364.00 | 1651.02 | 3624.01 | 5049.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4165.81 | 2850.75 | 1315.05 | 2919.06 | 6762.48 | 0.00 | 0.00 | 0.00 |
February | 4463.59 | 3015.63 | 1447.95 | 3323.03 | 5510.02 | 0.00 | 0.00 | 0.00 |
March | 3884.32 | 2045.36 | 1838.97 | 3106.84 | 4054.84 | 0.00 | 0.00 | 0.00 |
April | 3499.51 | 1636.09 | 1863.42 | 3354.26 | 3057.32 | 0.00 | 0.00 | 0.00 |
May | 2899.23 | 786.02 | 2113.21 | 3011.62 | 1746.31 | 0.00 | 0.00 | 0.00 |
June | 2814.71 | 573.09 | 2241.62 | 3441.96 | 1191.42 | 0.00 | 0.00 | 0.00 |
July | 2979.57 | 750.77 | 2228.80 | 3849.53 | 979.80 | 0.00 | 0.00 | 0.00 |
August | 3356.99 | 1203.90 | 2153.09 | 4431.09 | 1174.61 | 0.00 | 0.00 | 0.00 |
September | 4067.96 | 2143.48 | 1924.48 | 4883.54 | 2018.34 | 0.00 | 0.00 | 0.00 |
October | 4247.81 | 2664.90 | 1582.90 | 4170.79 | 3014.52 | 0.00 | 0.00 | 0.00 |
November | 3204.96 | 2006.37 | 1198.59 | 2510.51 | 4458.04 | 0.00 | 0.00 | 0.00 |
December | 3417.63 | 2588.81 | 828.82 | 2741.12 | 6246.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3578.32 | 1848.81 | 1729.51 | 3479.14 | 3340.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2814.71 | 573.09 | 828.82 | 2510.51 | 979.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4463.59 | 3015.63 | 2241.62 | 4883.54 | 6762.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 949.02 | 383.98 | 565.03 | 261.92 | 5279.20 | 0.00 | 0.00 | 0.00 |
February | 1391.56 | 685.72 | 705.84 | 648.07 | 4295.95 | 0.00 | 0.00 | 0.00 |
March | 1661.24 | 618.07 | 1043.17 | 934.06 | 2870.22 | 0.00 | 0.00 | 0.00 |
April | 2423.26 | 1198.26 | 1225.00 | 2199.93 | 2084.19 | 0.00 | 0.00 | 0.00 |
May | 2430.27 | 970.83 | 1459.43 | 2511.78 | 1173.36 | 0.00 | 0.00 | 0.00 |
June | 2851.63 | 1235.83 | 1615.80 | 3449.75 | 843.36 | 0.00 | 0.00 | 0.00 |
July | 3061.78 | 1454.40 | 1607.39 | 3837.27 | 733.07 | 0.00 | 0.00 | 0.00 |
August | 2676.77 | 1228.46 | 1448.31 | 3386.40 | 826.92 | 0.00 | 0.00 | 0.00 |
September | 2166.77 | 1028.46 | 1138.31 | 2442.37 | 1372.00 | 0.00 | 0.00 | 0.00 |
October | 1509.89 | 671.28 | 838.61 | 1170.01 | 2114.79 | 0.00 | 0.00 | 0.00 |
November | 903.77 | 334.21 | 569.56 | 406.20 | 3269.19 | 0.00 | 0.00 | 0.00 |
December | 695.05 | 327.66 | 367.39 | 253.53 | 4687.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1895.43 | 844.93 | 1050.50 | 1797.53 | 2453.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 695.05 | 327.66 | 367.39 | 253.53 | 733.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3061.78 | 1454.40 | 1615.80 | 3837.27 | 5279.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 669.85 | 0.00 | 669.85 | 0.00 | 8368.10 | 0.00 | 0.00 | 0.00 |
February | 849.24 | 0.00 | 849.24 | 6.99 | 6765.90 | 0.00 | 0.00 | 0.00 |
March | 1272.75 | 0.00 | 1272.75 | 190.65 | 4306.86 | 0.00 | 0.00 | 0.00 |
April | 1469.31 | 7.24 | 1462.07 | 617.42 | 2841.01 | 0.00 | 0.00 | 0.00 |
May | 1916.01 | 72.02 | 1843.99 | 1486.31 | 1435.57 | 0.00 | 0.00 | 0.00 |
June | 2239.37 | 203.25 | 2036.12 | 2449.16 | 993.02 | 0.00 | 0.00 | 0.00 |
July | 2100.18 | 140.48 | 1959.70 | 2457.34 | 818.34 | 0.00 | 0.00 | 0.00 |
August | 1758.47 | 31.16 | 1727.30 | 2079.28 | 960.58 | 0.00 | 0.00 | 0.00 |
September | 1348.24 | 0.33 | 1347.90 | 1201.09 | 1762.29 | 0.00 | 0.00 | 0.00 |
October | 1002.44 | 0.00 | 1002.44 | 313.28 | 2847.28 | 0.00 | 0.00 | 0.00 |
November | 701.22 | 0.00 | 701.22 | 55.52 | 4825.88 | 0.00 | 0.00 | 0.00 |
December | 454.85 | 0.00 | 454.85 | 0.00 | 7191.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1317.63 | 38.02 | 1279.60 | 910.20 | 3577.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 454.85 | 0.00 | 454.85 | 0.00 | 818.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2239.37 | 203.25 | 2036.12 | 2457.34 | 8368.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 956.91 | 393.77 | 563.14 | 237.65 | 4999.23 | 0.00 | 0.00 | 0.00 |
February | 1268.37 | 557.73 | 710.64 | 508.27 | 3931.09 | 0.00 | 0.00 | 0.00 |
March | 1723.33 | 684.04 | 1039.29 | 1032.83 | 2564.02 | 0.00 | 0.00 | 0.00 |
April | 2116.09 | 926.70 | 1189.38 | 1765.16 | 1786.05 | 0.00 | 0.00 | 0.00 |
May | 2657.64 | 1161.27 | 1496.37 | 2718.87 | 971.57 | 0.00 | 0.00 | 0.00 |
June | 2924.66 | 1273.64 | 1651.02 | 3481.90 | 679.50 | 0.00 | 0.00 | 0.00 |
July | 2956.08 | 1364.00 | 1592.08 | 3637.80 | 561.52 | 0.00 | 0.00 | 0.00 |
August | 2491.92 | 1074.32 | 1417.60 | 3090.70 | 654.20 | 0.00 | 0.00 | 0.00 |
September | 2222.57 | 1050.28 | 1172.29 | 2483.64 | 1135.24 | 0.00 | 0.00 | 0.00 |
October | 1416.37 | 591.61 | 824.77 | 1068.52 | 1743.30 | 0.00 | 0.00 | 0.00 |
November | 835.67 | 271.44 | 564.23 | 318.22 | 2980.86 | 0.00 | 0.00 | 0.00 |
December | 647.32 | 277.98 | 369.35 | 192.59 | 4410.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1854.30 | 803.38 | 1050.92 | 1717.94 | 2193.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 647.32 | 271.44 | 369.35 | 192.59 | 561.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2956.08 | 1364.00 | 1651.02 | 3637.80 | 4999.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4165.81 | 2850.75 | 1315.05 | 2943.43 | 6620.89 | 0.00 | 0.00 | 0.00 |
February | 4463.59 | 3015.63 | 1447.95 | 3367.17 | 5303.71 | 0.00 | 0.00 | 0.00 |
March | 3884.32 | 2045.36 | 1838.97 | 3148.79 | 3828.40 | 0.00 | 0.00 | 0.00 |
April | 3499.51 | 1636.09 | 1863.42 | 3375.87 | 2837.56 | 0.00 | 0.00 | 0.00 |
May | 2899.23 | 786.02 | 2113.21 | 3056.11 | 1596.42 | 0.00 | 0.00 | 0.00 |
June | 2814.71 | 573.09 | 2241.62 | 3464.42 | 1091.23 | 0.00 | 0.00 | 0.00 |
July | 2979.57 | 750.77 | 2228.80 | 3872.66 | 902.25 | 0.00 | 0.00 | 0.00 |
August | 3356.99 | 1203.90 | 2153.09 | 4454.36 | 1078.48 | 0.00 | 0.00 | 0.00 |
September | 4067.96 | 2143.48 | 1924.48 | 4922.12 | 1841.62 | 0.00 | 0.00 | 0.00 |
October | 4247.81 | 2664.90 | 1582.90 | 4254.86 | 2708.51 | 0.00 | 0.00 | 0.00 |
November | 3204.96 | 2006.37 | 1198.59 | 2575.24 | 4203.43 | 0.00 | 0.00 | 0.00 |
December | 3417.63 | 2588.81 | 828.82 | 2780.22 | 6044.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3578.32 | 1848.81 | 1729.51 | 3518.45 | 3161.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2814.71 | 573.09 | 828.82 | 2575.24 | 902.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4463.59 | 3015.63 | 2241.62 | 4922.12 | 6620.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 949.02 | 383.98 | 565.03 | 261.16 | 5201.62 | 0.00 | 0.00 | 0.00 |
February | 1391.56 | 685.72 | 705.84 | 650.45 | 4190.12 | 0.00 | 0.00 | 0.00 |
March | 1661.24 | 618.07 | 1043.17 | 940.03 | 2746.52 | 0.00 | 0.00 | 0.00 |
April | 2423.26 | 1198.26 | 1225.00 | 2196.31 | 1960.55 | 0.00 | 0.00 | 0.00 |
May | 2430.27 | 970.83 | 1459.43 | 2514.72 | 1096.85 | 0.00 | 0.00 | 0.00 |
June | 2851.63 | 1235.83 | 1615.80 | 3441.24 | 795.86 | 0.00 | 0.00 | 0.00 |
July | 3061.78 | 1454.40 | 1607.39 | 3828.23 | 696.81 | 0.00 | 0.00 | 0.00 |
August | 2676.77 | 1228.46 | 1448.31 | 3383.02 | 781.48 | 0.00 | 0.00 | 0.00 |
September | 2166.77 | 1028.46 | 1138.31 | 2448.99 | 1280.44 | 0.00 | 0.00 | 0.00 |
October | 1509.89 | 671.28 | 838.61 | 1190.75 | 1940.74 | 0.00 | 0.00 | 0.00 |
November | 903.77 | 334.21 | 569.56 | 416.09 | 3129.78 | 0.00 | 0.00 | 0.00 |
December | 695.05 | 327.66 | 367.39 | 256.24 | 4582.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1895.43 | 844.93 | 1050.50 | 1799.70 | 2358.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 695.05 | 327.66 | 367.39 | 256.24 | 696.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3061.78 | 1454.40 | 1615.80 | 3828.23 | 5201.62 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.358831E+09 | 0.00 | 0.358831E+09 | 0.00 | 0.462502E+10 |
February | 0.410903E+09 | 0.00 | 0.410903E+09 | 528942.77 | 0.345435E+10 |
March | 0.681797E+09 | 0.00 | 0.681797E+09 | 74755236.65 | 0.255342E+10 |
April | 0.761698E+09 | 3752853.26 | 0.757946E+09 | 0.268750E+09 | 0.172539E+10 |
May | 0.102638E+10 | 38579183.16 | 0.987799E+09 | 0.709098E+09 | 0.919773E+09 |
June | 0.116090E+10 | 0.105367E+09 | 0.105554E+10 | 0.119871E+10 | 0.618198E+09 |
July | 0.112504E+10 | 75252695.95 | 0.104979E+10 | 0.123056E+10 | 0.530642E+09 |
August | 0.941986E+09 | 16694634.24 | 0.925292E+09 | 0.102355E+10 | 0.643628E+09 |
September | 0.698936E+09 | 173304.80 | 0.698762E+09 | 0.548502E+09 | 0.111539E+10 |
October | 0.536994E+09 | 0.00 | 0.536994E+09 | 0.103560E+09 | 0.188541E+10 |
November | 0.363516E+09 | 0.00 | 0.363516E+09 | 11996884.78 | 0.284419E+10 |
December | 0.243658E+09 | 0.00 | 0.243658E+09 | 0.00 | 0.413175E+10 |
Annual Sum or Average | 0.831064E+10 | 0.239820E+09 | 0.807082E+10 | 0.517000E+10 | 0.250472E+11 |
Minimum of Months | 0.243658E+09 | 0.00 | 0.243658E+09 | 0.00 | 0.530642E+09 |
Maximum of Months | 0.116090E+10 | 0.105367E+09 | 0.105554E+10 | 0.123056E+10 | 0.462502E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.358831E+09 | 0.00 | 0.358831E+09 | 0.00 | 0.462502E+10 |
February | 0.410902E+09 | 0.00 | 0.410902E+09 | 528935.05 | 0.345436E+10 |
March | 0.681797E+09 | 0.00 | 0.681797E+09 | 74755031.55 | 0.255342E+10 |
April | 0.761698E+09 | 3752848.76 | 0.757945E+09 | 0.268749E+09 | 0.172539E+10 |
May | 0.102638E+10 | 38579136.87 | 0.987798E+09 | 0.709097E+09 | 0.919773E+09 |
June | 0.116090E+10 | 0.105367E+09 | 0.105554E+10 | 0.119870E+10 | 0.618198E+09 |
July | 0.112504E+10 | 75252605.65 | 0.104978E+10 | 0.123055E+10 | 0.530642E+09 |
August | 0.941986E+09 | 16694614.21 | 0.925291E+09 | 0.102355E+10 | 0.643627E+09 |
September | 0.698935E+09 | 173304.59 | 0.698762E+09 | 0.548501E+09 | 0.111539E+10 |
October | 0.536994E+09 | 0.00 | 0.536994E+09 | 0.103560E+09 | 0.188541E+10 |
November | 0.363515E+09 | 0.00 | 0.363515E+09 | 11996836.04 | 0.284419E+10 |
December | 0.243658E+09 | 0.00 | 0.243658E+09 | 0.00 | 0.413175E+10 |
Annual Sum or Average | 0.831063E+10 | 0.239820E+09 | 0.807081E+10 | 0.517000E+10 | 0.250472E+11 |
Minimum of Months | 0.243658E+09 | 0.00 | 0.243658E+09 | 0.00 | 0.530642E+09 |
Maximum of Months | 0.116090E+10 | 0.105367E+09 | 0.105554E+10 | 0.123055E+10 | 0.462502E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.358831E+09 | 0.00 | 0.358831E+09 | 0.00 | 0.462502E+10 |
February | 0.410903E+09 | 0.00 | 0.410903E+09 | 528942.77 | 0.345435E+10 |
March | 0.681797E+09 | 0.00 | 0.681797E+09 | 74755236.65 | 0.255342E+10 |
April | 0.761698E+09 | 3752853.26 | 0.757946E+09 | 0.268750E+09 | 0.172539E+10 |
May | 0.102638E+10 | 38579183.16 | 0.987799E+09 | 0.709098E+09 | 0.919773E+09 |
June | 0.116090E+10 | 0.105367E+09 | 0.105554E+10 | 0.119871E+10 | 0.618198E+09 |
July | 0.112504E+10 | 75252695.95 | 0.104979E+10 | 0.123056E+10 | 0.530642E+09 |
August | 0.941986E+09 | 16694634.24 | 0.925292E+09 | 0.102355E+10 | 0.643628E+09 |
September | 0.698936E+09 | 173304.80 | 0.698762E+09 | 0.548502E+09 | 0.111539E+10 |
October | 0.536994E+09 | 0.00 | 0.536994E+09 | 0.103560E+09 | 0.188541E+10 |
November | 0.363516E+09 | 0.00 | 0.363516E+09 | 11996884.78 | 0.284419E+10 |
December | 0.243658E+09 | 0.00 | 0.243658E+09 | 0.00 | 0.413175E+10 |
Annual Sum or Average | 0.831064E+10 | 0.239820E+09 | 0.807082E+10 | 0.517000E+10 | 0.250472E+11 |
Minimum of Months | 0.243658E+09 | 0.00 | 0.243658E+09 | 0.00 | 0.530642E+09 |
Maximum of Months | 0.116090E+10 | 0.105367E+09 | 0.105554E+10 | 0.123056E+10 | 0.462502E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.358831E+09 | 0.00 | 0.358831E+09 | 0.00 | 0.462502E+10 |
February | 0.410902E+09 | 0.00 | 0.410902E+09 | 528935.05 | 0.345436E+10 |
March | 0.681797E+09 | 0.00 | 0.681797E+09 | 74755031.55 | 0.255342E+10 |
April | 0.761698E+09 | 3752848.76 | 0.757945E+09 | 0.268749E+09 | 0.172539E+10 |
May | 0.102638E+10 | 38579136.87 | 0.987798E+09 | 0.709097E+09 | 0.919773E+09 |
June | 0.116090E+10 | 0.105367E+09 | 0.105554E+10 | 0.119870E+10 | 0.618198E+09 |
July | 0.112504E+10 | 75252605.65 | 0.104978E+10 | 0.123055E+10 | 0.530642E+09 |
August | 0.941986E+09 | 16694614.21 | 0.925291E+09 | 0.102355E+10 | 0.643627E+09 |
September | 0.698935E+09 | 173304.59 | 0.698762E+09 | 0.548501E+09 | 0.111539E+10 |
October | 0.536994E+09 | 0.00 | 0.536994E+09 | 0.103560E+09 | 0.188541E+10 |
November | 0.363515E+09 | 0.00 | 0.363515E+09 | 11996836.04 | 0.284419E+10 |
December | 0.243658E+09 | 0.00 | 0.243658E+09 | 0.00 | 0.413175E+10 |
Annual Sum or Average | 0.831063E+10 | 0.239820E+09 | 0.807081E+10 | 0.517000E+10 | 0.250472E+11 |
Minimum of Months | 0.243658E+09 | 0.00 | 0.243658E+09 | 0.00 | 0.530642E+09 |
Maximum of Months | 0.116090E+10 | 0.105367E+09 | 0.105554E+10 | 0.123055E+10 | 0.462502E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.358817E+09 | 0.00 | 0.358817E+09 | 0.00 | 0.462484E+10 |
February | 0.410886E+09 | 0.00 | 0.410886E+09 | 528921.45 | 0.345422E+10 |
March | 0.681770E+09 | 0.00 | 0.681770E+09 | 74752223.68 | 0.255331E+10 |
April | 0.761668E+09 | 3752702.01 | 0.757915E+09 | 0.268739E+09 | 0.172532E+10 |
May | 0.102634E+10 | 38577628.25 | 0.987759E+09 | 0.709069E+09 | 0.919735E+09 |
June | 0.116086E+10 | 0.105363E+09 | 0.105549E+10 | 0.119866E+10 | 0.618173E+09 |
July | 0.112499E+10 | 75249662.93 | 0.104974E+10 | 0.123051E+10 | 0.530621E+09 |
August | 0.941948E+09 | 16693961.37 | 0.925255E+09 | 0.102351E+10 | 0.643602E+09 |
September | 0.698907E+09 | 173297.81 | 0.698734E+09 | 0.548480E+09 | 0.111535E+10 |
October | 0.536972E+09 | 0.00 | 0.536972E+09 | 0.103556E+09 | 0.188533E+10 |
November | 0.363501E+09 | 0.00 | 0.363501E+09 | 11996401.26 | 0.284408E+10 |
December | 0.243648E+09 | 0.00 | 0.243648E+09 | 0.00 | 0.413158E+10 |
Annual Sum or Average | 0.831031E+10 | 0.239810E+09 | 0.807050E+10 | 0.516979E+10 | 0.250462E+11 |
Minimum of Months | 0.243648E+09 | 0.00 | 0.243648E+09 | 0.00 | 0.530621E+09 |
Maximum of Months | 0.116086E+10 | 0.105363E+09 | 0.105549E+10 | 0.123051E+10 | 0.462484E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.854335E+09 | 0.351561E+09 | 0.502773E+09 | 0.210251E+09 | 0.461186E+10 |
February | 0.102283E+10 | 0.449758E+09 | 0.573070E+09 | 0.398372E+09 | 0.336043E+10 |
March | 0.153861E+10 | 0.610719E+09 | 0.927888E+09 | 0.887259E+09 | 0.251008E+10 |
April | 0.182832E+10 | 0.800680E+09 | 0.102764E+10 | 0.150693E+10 | 0.174061E+10 |
May | 0.237276E+10 | 0.103679E+10 | 0.133597E+10 | 0.241896E+10 | 0.980177E+09 |
June | 0.252693E+10 | 0.110044E+10 | 0.142649E+10 | 0.302309E+10 | 0.660333E+09 |
July | 0.263922E+10 | 0.121779E+10 | 0.142142E+10 | 0.326840E+10 | 0.552482E+09 |
August | 0.222481E+10 | 0.959165E+09 | 0.126564E+10 | 0.275669E+10 | 0.656111E+09 |
September | 0.192032E+10 | 0.907451E+09 | 0.101287E+10 | 0.211611E+10 | 0.113692E+10 |
October | 0.126455E+10 | 0.528194E+09 | 0.736358E+09 | 0.866699E+09 | 0.187524E+10 |
November | 0.722029E+09 | 0.234529E+09 | 0.487501E+09 | 0.239767E+09 | 0.288634E+10 |
December | 0.577933E+09 | 0.248179E+09 | 0.329755E+09 | 0.158418E+09 | 0.420571E+10 |
Annual Sum or Average | 0.194926E+11 | 0.844526E+10 | 0.110474E+11 | 0.178510E+11 | 0.251763E+11 |
Minimum of Months | 0.577933E+09 | 0.234529E+09 | 0.329755E+09 | 0.158418E+09 | 0.552482E+09 |
Maximum of Months | 0.263922E+10 | 0.121779E+10 | 0.142649E+10 | 0.326840E+10 | 0.461186E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.854335E+09 | 0.351561E+09 | 0.502773E+09 | 0.210251E+09 | 0.461186E+10 |
February | 0.102283E+10 | 0.449758E+09 | 0.573070E+09 | 0.398372E+09 | 0.336043E+10 |
March | 0.153861E+10 | 0.610719E+09 | 0.927888E+09 | 0.887259E+09 | 0.251008E+10 |
April | 0.182832E+10 | 0.800680E+09 | 0.102764E+10 | 0.150693E+10 | 0.174061E+10 |
May | 0.237276E+10 | 0.103679E+10 | 0.133597E+10 | 0.241896E+10 | 0.980177E+09 |
June | 0.252693E+10 | 0.110044E+10 | 0.142649E+10 | 0.302309E+10 | 0.660333E+09 |
July | 0.263922E+10 | 0.121779E+10 | 0.142142E+10 | 0.326840E+10 | 0.552482E+09 |
August | 0.222481E+10 | 0.959165E+09 | 0.126564E+10 | 0.275669E+10 | 0.656111E+09 |
September | 0.192032E+10 | 0.907451E+09 | 0.101287E+10 | 0.211611E+10 | 0.113692E+10 |
October | 0.126455E+10 | 0.528194E+09 | 0.736358E+09 | 0.866699E+09 | 0.187524E+10 |
November | 0.722029E+09 | 0.234529E+09 | 0.487501E+09 | 0.239767E+09 | 0.288634E+10 |
December | 0.577933E+09 | 0.248179E+09 | 0.329755E+09 | 0.158418E+09 | 0.420571E+10 |
Annual Sum or Average | 0.194926E+11 | 0.844526E+10 | 0.110474E+11 | 0.178510E+11 | 0.251763E+11 |
Minimum of Months | 0.577933E+09 | 0.234529E+09 | 0.329755E+09 | 0.158418E+09 | 0.552482E+09 |
Maximum of Months | 0.263922E+10 | 0.121779E+10 | 0.142649E+10 | 0.326840E+10 | 0.461186E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.854319E+09 | 0.351555E+09 | 0.502764E+09 | 0.210247E+09 | 0.461178E+10 |
February | 0.102281E+10 | 0.449750E+09 | 0.573059E+09 | 0.398364E+09 | 0.336037E+10 |
March | 0.153858E+10 | 0.610708E+09 | 0.927871E+09 | 0.887243E+09 | 0.251003E+10 |
April | 0.182829E+10 | 0.800665E+09 | 0.102762E+10 | 0.150690E+10 | 0.174058E+10 |
May | 0.237272E+10 | 0.103677E+10 | 0.133595E+10 | 0.241892E+10 | 0.980159E+09 |
June | 0.252688E+10 | 0.110042E+10 | 0.142647E+10 | 0.302304E+10 | 0.660321E+09 |
July | 0.263917E+10 | 0.121777E+10 | 0.142140E+10 | 0.326834E+10 | 0.552472E+09 |
August | 0.222477E+10 | 0.959147E+09 | 0.126562E+10 | 0.275664E+10 | 0.656099E+09 |
September | 0.192028E+10 | 0.907434E+09 | 0.101285E+10 | 0.211607E+10 | 0.113690E+10 |
October | 0.126453E+10 | 0.528184E+09 | 0.736345E+09 | 0.866683E+09 | 0.187521E+10 |
November | 0.722016E+09 | 0.234524E+09 | 0.487492E+09 | 0.239762E+09 | 0.288629E+10 |
December | 0.577923E+09 | 0.248174E+09 | 0.329749E+09 | 0.158415E+09 | 0.420564E+10 |
Annual Sum or Average | 0.194923E+11 | 0.844510E+10 | 0.110472E+11 | 0.178506E+11 | 0.251758E+11 |
Minimum of Months | 0.577923E+09 | 0.234524E+09 | 0.329749E+09 | 0.158415E+09 | 0.552472E+09 |
Maximum of Months | 0.263917E+10 | 0.121777E+10 | 0.142647E+10 | 0.326834E+10 | 0.461178E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223157E+10 | 0.152711E+10 | 0.704457E+09 | 0.158709E+10 | 0.363632E+10 |
February | 0.215969E+10 | 0.145910E+10 | 0.700585E+09 | 0.163389E+10 | 0.268500E+10 |
March | 0.208078E+10 | 0.109567E+10 | 0.985109E+09 | 0.168721E+10 | 0.220940E+10 |
April | 0.181417E+10 | 0.848161E+09 | 0.966010E+09 | 0.175533E+10 | 0.163626E+10 |
May | 0.155308E+10 | 0.421061E+09 | 0.113202E+10 | 0.161875E+10 | 0.966164E+09 |
June | 0.145916E+10 | 0.297094E+09 | 0.116207E+10 | 0.177915E+10 | 0.649622E+09 |
July | 0.159612E+10 | 0.402179E+09 | 0.119394E+10 | 0.205326E+10 | 0.556694E+09 |
August | 0.179829E+10 | 0.644911E+09 | 0.115338E+10 | 0.237003E+10 | 0.669843E+09 |
September | 0.210886E+10 | 0.111119E+10 | 0.997662E+09 | 0.254903E+10 | 0.107931E+10 |
October | 0.227549E+10 | 0.142755E+10 | 0.847940E+09 | 0.225370E+10 | 0.166171E+10 |
November | 0.166147E+10 | 0.104011E+10 | 0.621359E+09 | 0.130549E+10 | 0.237853E+10 |
December | 0.183078E+10 | 0.138679E+10 | 0.443985E+09 | 0.147125E+10 | 0.341852E+10 |
Annual Sum or Average | 0.225694E+11 | 0.116609E+11 | 0.109085E+11 | 0.220642E+11 | 0.215474E+11 |
Minimum of Months | 0.145916E+10 | 0.297094E+09 | 0.443985E+09 | 0.130549E+10 | 0.556694E+09 |
Maximum of Months | 0.227549E+10 | 0.152711E+10 | 0.119394E+10 | 0.254903E+10 | 0.363632E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223156E+10 | 0.152711E+10 | 0.704456E+09 | 0.158708E+10 | 0.363632E+10 |
February | 0.215969E+10 | 0.145910E+10 | 0.700585E+09 | 0.163388E+10 | 0.268500E+10 |
March | 0.208078E+10 | 0.109567E+10 | 0.985108E+09 | 0.168721E+10 | 0.220940E+10 |
April | 0.181417E+10 | 0.848159E+09 | 0.966009E+09 | 0.175533E+10 | 0.163626E+10 |
May | 0.155308E+10 | 0.421060E+09 | 0.113202E+10 | 0.161875E+10 | 0.966164E+09 |
June | 0.145916E+10 | 0.297094E+09 | 0.116207E+10 | 0.177915E+10 | 0.649622E+09 |
July | 0.159611E+10 | 0.402179E+09 | 0.119394E+10 | 0.205326E+10 | 0.556694E+09 |
August | 0.179829E+10 | 0.644910E+09 | 0.115338E+10 | 0.237003E+10 | 0.669843E+09 |
September | 0.210885E+10 | 0.111119E+10 | 0.997661E+09 | 0.254903E+10 | 0.107931E+10 |
October | 0.227549E+10 | 0.142755E+10 | 0.847940E+09 | 0.225369E+10 | 0.166171E+10 |
November | 0.166147E+10 | 0.104011E+10 | 0.621359E+09 | 0.130549E+10 | 0.237853E+10 |
December | 0.183077E+10 | 0.138679E+10 | 0.443985E+09 | 0.147124E+10 | 0.341852E+10 |
Annual Sum or Average | 0.225694E+11 | 0.116609E+11 | 0.109085E+11 | 0.220641E+11 | 0.215474E+11 |
Minimum of Months | 0.145916E+10 | 0.297094E+09 | 0.443985E+09 | 0.130549E+10 | 0.556694E+09 |
Maximum of Months | 0.227549E+10 | 0.152711E+10 | 0.119394E+10 | 0.254903E+10 | 0.363632E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223157E+10 | 0.152711E+10 | 0.704457E+09 | 0.158709E+10 | 0.363632E+10 |
February | 0.215969E+10 | 0.145910E+10 | 0.700585E+09 | 0.163389E+10 | 0.268500E+10 |
March | 0.208078E+10 | 0.109567E+10 | 0.985109E+09 | 0.168721E+10 | 0.220940E+10 |
April | 0.181417E+10 | 0.848161E+09 | 0.966010E+09 | 0.175533E+10 | 0.163626E+10 |
May | 0.155308E+10 | 0.421061E+09 | 0.113202E+10 | 0.161875E+10 | 0.966164E+09 |
June | 0.145916E+10 | 0.297094E+09 | 0.116207E+10 | 0.177915E+10 | 0.649622E+09 |
July | 0.159612E+10 | 0.402179E+09 | 0.119394E+10 | 0.205326E+10 | 0.556694E+09 |
August | 0.179829E+10 | 0.644911E+09 | 0.115338E+10 | 0.237003E+10 | 0.669843E+09 |
September | 0.210886E+10 | 0.111119E+10 | 0.997662E+09 | 0.254903E+10 | 0.107931E+10 |
October | 0.227549E+10 | 0.142755E+10 | 0.847940E+09 | 0.225370E+10 | 0.166171E+10 |
November | 0.166147E+10 | 0.104011E+10 | 0.621359E+09 | 0.130549E+10 | 0.237853E+10 |
December | 0.183078E+10 | 0.138679E+10 | 0.443985E+09 | 0.147125E+10 | 0.341852E+10 |
Annual Sum or Average | 0.225694E+11 | 0.116609E+11 | 0.109085E+11 | 0.220642E+11 | 0.215474E+11 |
Minimum of Months | 0.145916E+10 | 0.297094E+09 | 0.443985E+09 | 0.130549E+10 | 0.556694E+09 |
Maximum of Months | 0.227549E+10 | 0.152711E+10 | 0.119394E+10 | 0.254903E+10 | 0.363632E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223156E+10 | 0.152711E+10 | 0.704456E+09 | 0.158708E+10 | 0.363632E+10 |
February | 0.215969E+10 | 0.145910E+10 | 0.700585E+09 | 0.163388E+10 | 0.268500E+10 |
March | 0.208078E+10 | 0.109567E+10 | 0.985108E+09 | 0.168721E+10 | 0.220940E+10 |
April | 0.181417E+10 | 0.848159E+09 | 0.966009E+09 | 0.175533E+10 | 0.163626E+10 |
May | 0.155308E+10 | 0.421060E+09 | 0.113202E+10 | 0.161875E+10 | 0.966164E+09 |
June | 0.145916E+10 | 0.297094E+09 | 0.116207E+10 | 0.177915E+10 | 0.649622E+09 |
July | 0.159611E+10 | 0.402179E+09 | 0.119394E+10 | 0.205326E+10 | 0.556694E+09 |
August | 0.179829E+10 | 0.644910E+09 | 0.115338E+10 | 0.237003E+10 | 0.669843E+09 |
September | 0.210885E+10 | 0.111119E+10 | 0.997661E+09 | 0.254903E+10 | 0.107931E+10 |
October | 0.227549E+10 | 0.142755E+10 | 0.847940E+09 | 0.225369E+10 | 0.166171E+10 |
November | 0.166147E+10 | 0.104011E+10 | 0.621359E+09 | 0.130549E+10 | 0.237853E+10 |
December | 0.183077E+10 | 0.138679E+10 | 0.443985E+09 | 0.147124E+10 | 0.341852E+10 |
Annual Sum or Average | 0.225694E+11 | 0.116609E+11 | 0.109085E+11 | 0.220641E+11 | 0.215474E+11 |
Minimum of Months | 0.145916E+10 | 0.297094E+09 | 0.443985E+09 | 0.130549E+10 | 0.556694E+09 |
Maximum of Months | 0.227549E+10 | 0.152711E+10 | 0.119394E+10 | 0.254903E+10 | 0.363632E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223148E+10 | 0.152705E+10 | 0.704429E+09 | 0.158702E+10 | 0.363617E+10 |
February | 0.215960E+10 | 0.145904E+10 | 0.700557E+09 | 0.163382E+10 | 0.268489E+10 |
March | 0.208069E+10 | 0.109563E+10 | 0.985069E+09 | 0.168714E+10 | 0.220931E+10 |
April | 0.181410E+10 | 0.848126E+09 | 0.965971E+09 | 0.175526E+10 | 0.163619E+10 |
May | 0.155302E+10 | 0.421044E+09 | 0.113197E+10 | 0.161869E+10 | 0.966125E+09 |
June | 0.145910E+10 | 0.297082E+09 | 0.116202E+10 | 0.177908E+10 | 0.649596E+09 |
July | 0.159605E+10 | 0.402163E+09 | 0.119389E+10 | 0.205318E+10 | 0.556672E+09 |
August | 0.179822E+10 | 0.644885E+09 | 0.115333E+10 | 0.236993E+10 | 0.669816E+09 |
September | 0.210877E+10 | 0.111115E+10 | 0.997622E+09 | 0.254893E+10 | 0.107927E+10 |
October | 0.227540E+10 | 0.142749E+10 | 0.847906E+09 | 0.225361E+10 | 0.166165E+10 |
November | 0.166140E+10 | 0.104007E+10 | 0.621334E+09 | 0.130544E+10 | 0.237844E+10 |
December | 0.183070E+10 | 0.138674E+10 | 0.443967E+09 | 0.147119E+10 | 0.341838E+10 |
Annual Sum or Average | 0.225685E+11 | 0.116605E+11 | 0.109081E+11 | 0.220633E+11 | 0.215465E+11 |
Minimum of Months | 0.145910E+10 | 0.297082E+09 | 0.443967E+09 | 0.130544E+10 | 0.556672E+09 |
Maximum of Months | 0.227540E+10 | 0.152705E+10 | 0.119389E+10 | 0.254893E+10 | 0.363617E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.847290E+09 | 0.342824E+09 | 0.504466E+09 | 0.230448E+09 | 0.489820E+10 |
February | 0.112217E+10 | 0.552971E+09 | 0.569198E+09 | 0.514691E+09 | 0.364142E+10 |
March | 0.148317E+10 | 0.551821E+09 | 0.931350E+09 | 0.802198E+09 | 0.280528E+10 |
April | 0.209371E+10 | 0.103531E+10 | 0.105841E+10 | 0.186192E+10 | 0.204779E+10 |
May | 0.216976E+10 | 0.866769E+09 | 0.130299E+10 | 0.220658E+10 | 0.114072E+10 |
June | 0.246383E+10 | 0.106776E+10 | 0.139607E+10 | 0.294204E+10 | 0.818139E+09 |
July | 0.273359E+10 | 0.129850E+10 | 0.143509E+10 | 0.336238E+10 | 0.756450E+09 |
August | 0.238984E+10 | 0.109678E+10 | 0.129306E+10 | 0.293812E+10 | 0.892479E+09 |
September | 0.187211E+10 | 0.888598E+09 | 0.983509E+09 | 0.207368E+10 | 0.130952E+10 |
October | 0.134805E+10 | 0.599327E+09 | 0.748720E+09 | 0.100367E+10 | 0.211591E+10 |
November | 0.780866E+09 | 0.288764E+09 | 0.492102E+09 | 0.324434E+09 | 0.314278E+10 |
December | 0.620544E+09 | 0.292533E+09 | 0.328011E+09 | 0.208978E+09 | 0.454687E+10 |
Annual Sum or Average | 0.199249E+11 | 0.888196E+10 | 0.110430E+11 | 0.184691E+11 | 0.281156E+11 |
Minimum of Months | 0.620544E+09 | 0.288764E+09 | 0.328011E+09 | 0.208978E+09 | 0.756450E+09 |
Maximum of Months | 0.273359E+10 | 0.129850E+10 | 0.143509E+10 | 0.336238E+10 | 0.489820E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.847290E+09 | 0.342824E+09 | 0.504466E+09 | 0.230448E+09 | 0.489820E+10 |
February | 0.112217E+10 | 0.552971E+09 | 0.569198E+09 | 0.514691E+09 | 0.364142E+10 |
March | 0.148317E+10 | 0.551821E+09 | 0.931350E+09 | 0.802198E+09 | 0.280528E+10 |
April | 0.209371E+10 | 0.103531E+10 | 0.105841E+10 | 0.186192E+10 | 0.204779E+10 |
May | 0.216976E+10 | 0.866769E+09 | 0.130299E+10 | 0.220658E+10 | 0.114072E+10 |
June | 0.246383E+10 | 0.106776E+10 | 0.139607E+10 | 0.294204E+10 | 0.818139E+09 |
July | 0.273359E+10 | 0.129850E+10 | 0.143509E+10 | 0.336238E+10 | 0.756450E+09 |
August | 0.238984E+10 | 0.109678E+10 | 0.129306E+10 | 0.293812E+10 | 0.892479E+09 |
September | 0.187211E+10 | 0.888598E+09 | 0.983509E+09 | 0.207368E+10 | 0.130952E+10 |
October | 0.134805E+10 | 0.599327E+09 | 0.748720E+09 | 0.100367E+10 | 0.211591E+10 |
November | 0.780866E+09 | 0.288764E+09 | 0.492102E+09 | 0.324434E+09 | 0.314278E+10 |
December | 0.620544E+09 | 0.292533E+09 | 0.328011E+09 | 0.208978E+09 | 0.454687E+10 |
Annual Sum or Average | 0.199249E+11 | 0.888196E+10 | 0.110430E+11 | 0.184691E+11 | 0.281156E+11 |
Minimum of Months | 0.620544E+09 | 0.288764E+09 | 0.328011E+09 | 0.208978E+09 | 0.756450E+09 |
Maximum of Months | 0.273359E+10 | 0.129850E+10 | 0.143509E+10 | 0.336238E+10 | 0.489820E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.847275E+09 | 0.342818E+09 | 0.504457E+09 | 0.230444E+09 | 0.489811E+10 |
February | 0.112215E+10 | 0.552961E+09 | 0.569187E+09 | 0.514681E+09 | 0.364136E+10 |
March | 0.148314E+10 | 0.551811E+09 | 0.931333E+09 | 0.802184E+09 | 0.280523E+10 |
April | 0.209368E+10 | 0.103529E+10 | 0.105839E+10 | 0.186189E+10 | 0.204775E+10 |
May | 0.216972E+10 | 0.866753E+09 | 0.130297E+10 | 0.220654E+10 | 0.114070E+10 |
June | 0.246379E+10 | 0.106775E+10 | 0.139604E+10 | 0.294199E+10 | 0.818124E+09 |
July | 0.273354E+10 | 0.129847E+10 | 0.143506E+10 | 0.336232E+10 | 0.756436E+09 |
August | 0.238980E+10 | 0.109676E+10 | 0.129304E+10 | 0.293806E+10 | 0.892463E+09 |
September | 0.187207E+10 | 0.888582E+09 | 0.983491E+09 | 0.207364E+10 | 0.130949E+10 |
October | 0.134802E+10 | 0.599316E+09 | 0.748706E+09 | 0.100365E+10 | 0.211587E+10 |
November | 0.780852E+09 | 0.288758E+09 | 0.492093E+09 | 0.324429E+09 | 0.314272E+10 |
December | 0.620533E+09 | 0.292528E+09 | 0.328005E+09 | 0.208975E+09 | 0.454679E+10 |
Annual Sum or Average | 0.199246E+11 | 0.888179E+10 | 0.110428E+11 | 0.184688E+11 | 0.281150E+11 |
Minimum of Months | 0.620533E+09 | 0.288758E+09 | 0.328005E+09 | 0.208975E+09 | 0.756436E+09 |
Maximum of Months | 0.273354E+10 | 0.129847E+10 | 0.143506E+10 | 0.336232E+10 | 0.489811E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179414E+10 | 0.00 | 0.179414E+10 | 0.00 | 0.227390E+11 |
February | 0.205449E+10 | 0.00 | 0.205449E+10 | 11461168.83 | 0.167741E+11 |
March | 0.340895E+10 | 0.00 | 0.340895E+10 | 0.459985E+09 | 0.120984E+11 |
April | 0.380845E+10 | 18764039.42 | 0.378968E+10 | 0.153959E+10 | 0.790559E+10 |
May | 0.513183E+10 | 0.192894E+09 | 0.493893E+10 | 0.382737E+10 | 0.421002E+10 |
June | 0.580445E+10 | 0.526829E+09 | 0.527762E+10 | 0.622634E+10 | 0.281348E+10 |
July | 0.562512E+10 | 0.376259E+09 | 0.524886E+10 | 0.645164E+10 | 0.238422E+10 |
August | 0.470988E+10 | 83472161.85 | 0.462640E+10 | 0.543594E+10 | 0.281985E+10 |
September | 0.349464E+10 | 866513.52 | 0.349377E+10 | 0.298885E+10 | 0.502367E+10 |
October | 0.268494E+10 | 0.00 | 0.268494E+10 | 0.706085E+09 | 0.846827E+10 |
November | 0.181756E+10 | 0.00 | 0.181756E+10 | 0.110334E+09 | 0.131417E+11 |
December | 0.121828E+10 | 0.00 | 0.121828E+10 | 0.00 | 0.197277E+11 |
Annual Sum or Average | 0.415527E+11 | 0.119908E+10 | 0.403536E+11 | 0.277576E+11 | 0.118106E+12 |
Minimum of Months | 0.121828E+10 | 0.00 | 0.121828E+10 | 0.00 | 0.238422E+10 |
Maximum of Months | 0.580445E+10 | 0.526829E+09 | 0.527762E+10 | 0.645164E+10 | 0.227390E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.256298E+10 | 0.105467E+10 | 0.150830E+10 | 0.628261E+09 | 0.135233E+11 |
February | 0.306845E+10 | 0.134926E+10 | 0.171919E+10 | 0.120229E+10 | 0.975755E+10 |
March | 0.461578E+10 | 0.183214E+10 | 0.278364E+10 | 0.265757E+10 | 0.724508E+10 |
April | 0.548490E+10 | 0.240201E+10 | 0.308289E+10 | 0.447582E+10 | 0.498161E+10 |
May | 0.711822E+10 | 0.311034E+10 | 0.400788E+10 | 0.714231E+10 | 0.282841E+10 |
June | 0.758072E+10 | 0.330128E+10 | 0.427943E+10 | 0.897771E+10 | 0.190500E+10 |
July | 0.791757E+10 | 0.365335E+10 | 0.426422E+10 | 0.970654E+10 | 0.160880E+10 |
August | 0.667436E+10 | 0.287746E+10 | 0.379689E+10 | 0.821069E+10 | 0.189053E+10 |
September | 0.576090E+10 | 0.272233E+10 | 0.303857E+10 | 0.631742E+10 | 0.323011E+10 |
October | 0.379362E+10 | 0.158456E+10 | 0.220905E+10 | 0.264633E+10 | 0.523398E+10 |
November | 0.216607E+10 | 0.703579E+09 | 0.146249E+10 | 0.753612E+09 | 0.813268E+10 |
December | 0.173378E+10 | 0.744528E+09 | 0.989254E+09 | 0.497886E+09 | 0.120495E+11 |
Annual Sum or Average | 0.584773E+11 | 0.253355E+11 | 0.331418E+11 | 0.532164E+11 | 0.723866E+11 |
Minimum of Months | 0.173378E+10 | 0.703579E+09 | 0.989254E+09 | 0.497886E+09 | 0.160880E+10 |
Maximum of Months | 0.791757E+10 | 0.365335E+10 | 0.427943E+10 | 0.970654E+10 | 0.135233E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111577E+11 | 0.763545E+10 | 0.352224E+10 | 0.781842E+10 | 0.181126E+11 |
February | 0.107983E+11 | 0.729542E+10 | 0.350288E+10 | 0.803907E+10 | 0.133298E+11 |
March | 0.104038E+11 | 0.547828E+10 | 0.492548E+10 | 0.832137E+10 | 0.108605E+11 |
April | 0.907074E+10 | 0.424075E+10 | 0.482999E+10 | 0.869424E+10 | 0.792456E+10 |
May | 0.776529E+10 | 0.210528E+10 | 0.566002E+10 | 0.806631E+10 | 0.467731E+10 |
June | 0.729573E+10 | 0.148545E+10 | 0.581028E+10 | 0.892155E+10 | 0.308816E+10 |
July | 0.798048E+10 | 0.201087E+10 | 0.596961E+10 | 0.103106E+11 | 0.262429E+10 |
August | 0.899135E+10 | 0.322452E+10 | 0.576684E+10 | 0.118682E+11 | 0.314608E+10 |
September | 0.105441E+11 | 0.555590E+10 | 0.498825E+10 | 0.126581E+11 | 0.523154E+10 |
October | 0.113773E+11 | 0.713767E+10 | 0.423965E+10 | 0.111710E+11 | 0.807408E+10 |
November | 0.830726E+10 | 0.520050E+10 | 0.310676E+10 | 0.650725E+10 | 0.115552E+11 |
December | 0.915377E+10 | 0.693387E+10 | 0.221990E+10 | 0.734182E+10 | 0.167302E+11 |
Annual Sum or Average | 0.112846E+12 | 0.583040E+11 | 0.545419E+11 | 0.109718E+12 | 0.105354E+12 |
Minimum of Months | 0.729573E+10 | 0.148545E+10 | 0.221990E+10 | 0.650725E+10 | 0.262429E+10 |
Maximum of Months | 0.113773E+11 | 0.763545E+10 | 0.596961E+10 | 0.126581E+11 | 0.181126E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.254184E+10 | 0.102846E+10 | 0.151338E+10 | 0.701536E+09 | 0.141398E+11 |
February | 0.336647E+10 | 0.165890E+10 | 0.170758E+10 | 0.156780E+10 | 0.103928E+11 |
March | 0.444947E+10 | 0.165545E+10 | 0.279402E+10 | 0.250179E+10 | 0.768760E+10 |
April | 0.628108E+10 | 0.310588E+10 | 0.317519E+10 | 0.570221E+10 | 0.540222E+10 |
May | 0.650922E+10 | 0.260028E+10 | 0.390894E+10 | 0.672754E+10 | 0.314273E+10 |
June | 0.739142E+10 | 0.320326E+10 | 0.418816E+10 | 0.894176E+10 | 0.218598E+10 |
July | 0.820068E+10 | 0.389545E+10 | 0.430523E+10 | 0.102777E+11 | 0.196345E+10 |
August | 0.716946E+10 | 0.329031E+10 | 0.387914E+10 | 0.907012E+10 | 0.221483E+10 |
September | 0.561626E+10 | 0.266577E+10 | 0.295050E+10 | 0.633062E+10 | 0.355622E+10 |
October | 0.404410E+10 | 0.179796E+10 | 0.224614E+10 | 0.313375E+10 | 0.566425E+10 |
November | 0.234257E+10 | 0.866282E+09 | 0.147629E+10 | 0.105286E+10 | 0.847374E+10 |
December | 0.186161E+10 | 0.877591E+09 | 0.984022E+09 | 0.679051E+09 | 0.125541E+11 |
Annual Sum or Average | 0.597742E+11 | 0.266456E+11 | 0.331286E+11 | 0.566868E+11 | 0.773776E+11 |
Minimum of Months | 0.186161E+10 | 0.866282E+09 | 0.984022E+09 | 0.679051E+09 | 0.196345E+10 |
Maximum of Months | 0.820068E+10 | 0.389545E+10 | 0.430523E+10 | 0.102777E+11 | 0.141398E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179414E+10 | 0.00 | 0.179414E+10 | 0.00 | 0.224131E+11 |
February | 0.205449E+10 | 0.00 | 0.205449E+10 | 16909952.99 | 0.163681E+11 |
March | 0.340895E+10 | 0.00 | 0.340895E+10 | 0.510626E+09 | 0.115355E+11 |
April | 0.380845E+10 | 18764039.42 | 0.378968E+10 | 0.160035E+10 | 0.736391E+10 |
May | 0.513183E+10 | 0.192894E+09 | 0.493893E+10 | 0.398094E+10 | 0.384503E+10 |
June | 0.580445E+10 | 0.526829E+09 | 0.527762E+10 | 0.634823E+10 | 0.257391E+10 |
July | 0.562512E+10 | 0.376259E+09 | 0.524886E+10 | 0.658174E+10 | 0.219184E+10 |
August | 0.470988E+10 | 83472161.85 | 0.462640E+10 | 0.556914E+10 | 0.257282E+10 |
September | 0.349464E+10 | 866513.52 | 0.349377E+10 | 0.311322E+10 | 0.456785E+10 |
October | 0.268494E+10 | 0.00 | 0.268494E+10 | 0.839100E+09 | 0.762616E+10 |
November | 0.181756E+10 | 0.00 | 0.181756E+10 | 0.143914E+09 | 0.125087E+11 |
December | 0.121828E+10 | 0.00 | 0.121828E+10 | 0.00 | 0.192616E+11 |
Annual Sum or Average | 0.415527E+11 | 0.119908E+10 | 0.403536E+11 | 0.287042E+11 | 0.112828E+12 |
Minimum of Months | 0.121828E+10 | 0.00 | 0.121828E+10 | 0.00 | 0.219184E+10 |
Maximum of Months | 0.580445E+10 | 0.526829E+09 | 0.527762E+10 | 0.658174E+10 | 0.224131E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.256298E+10 | 0.105467E+10 | 0.150830E+10 | 0.636515E+09 | 0.133899E+11 |
February | 0.306845E+10 | 0.134926E+10 | 0.171919E+10 | 0.122962E+10 | 0.951009E+10 |
March | 0.461578E+10 | 0.183214E+10 | 0.278364E+10 | 0.276634E+10 | 0.686747E+10 |
April | 0.548490E+10 | 0.240201E+10 | 0.308289E+10 | 0.457529E+10 | 0.462944E+10 |
May | 0.711822E+10 | 0.311034E+10 | 0.400788E+10 | 0.728222E+10 | 0.260225E+10 |
June | 0.758072E+10 | 0.330128E+10 | 0.427943E+10 | 0.902509E+10 | 0.176125E+10 |
July | 0.791757E+10 | 0.365335E+10 | 0.426422E+10 | 0.974348E+10 | 0.150398E+10 |
August | 0.667436E+10 | 0.287746E+10 | 0.379689E+10 | 0.827814E+10 | 0.175222E+10 |
September | 0.576090E+10 | 0.272233E+10 | 0.303857E+10 | 0.643760E+10 | 0.294255E+10 |
October | 0.379362E+10 | 0.158456E+10 | 0.220905E+10 | 0.286193E+10 | 0.466927E+10 |
November | 0.216607E+10 | 0.703579E+09 | 0.146249E+10 | 0.824832E+09 | 0.772640E+10 |
December | 0.173378E+10 | 0.744528E+09 | 0.989254E+09 | 0.515829E+09 | 0.118132E+11 |
Annual Sum or Average | 0.584773E+11 | 0.253355E+11 | 0.331418E+11 | 0.541769E+11 | 0.691680E+11 |
Minimum of Months | 0.173378E+10 | 0.703579E+09 | 0.989254E+09 | 0.515829E+09 | 0.150398E+10 |
Maximum of Months | 0.791757E+10 | 0.365335E+10 | 0.427943E+10 | 0.974348E+10 | 0.133899E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111577E+11 | 0.763545E+10 | 0.352224E+10 | 0.788368E+10 | 0.177334E+11 |
February | 0.107983E+11 | 0.729542E+10 | 0.350288E+10 | 0.814585E+10 | 0.128307E+11 |
March | 0.104038E+11 | 0.547828E+10 | 0.492548E+10 | 0.843371E+10 | 0.102540E+11 |
April | 0.907074E+10 | 0.424075E+10 | 0.482999E+10 | 0.875025E+10 | 0.735495E+10 |
May | 0.776529E+10 | 0.210528E+10 | 0.566002E+10 | 0.818548E+10 | 0.427585E+10 |
June | 0.729573E+10 | 0.148545E+10 | 0.581028E+10 | 0.897978E+10 | 0.282848E+10 |
July | 0.798048E+10 | 0.201087E+10 | 0.596961E+10 | 0.103725E+11 | 0.241658E+10 |
August | 0.899135E+10 | 0.322452E+10 | 0.576684E+10 | 0.119306E+11 | 0.288860E+10 |
September | 0.105441E+11 | 0.555590E+10 | 0.498825E+10 | 0.127581E+11 | 0.477347E+10 |
October | 0.113773E+11 | 0.713767E+10 | 0.423965E+10 | 0.113962E+11 | 0.725448E+10 |
November | 0.830726E+10 | 0.520050E+10 | 0.310676E+10 | 0.667501E+10 | 0.108953E+11 |
December | 0.915377E+10 | 0.693387E+10 | 0.221990E+10 | 0.744655E+10 | 0.161904E+11 |
Annual Sum or Average | 0.112846E+12 | 0.583040E+11 | 0.545419E+11 | 0.110958E+12 | 0.996962E+11 |
Minimum of Months | 0.729573E+10 | 0.148545E+10 | 0.221990E+10 | 0.667501E+10 | 0.241658E+10 |
Maximum of Months | 0.113773E+11 | 0.763545E+10 | 0.596961E+10 | 0.127581E+11 | 0.177334E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.254184E+10 | 0.102846E+10 | 0.151338E+10 | 0.699502E+09 | 0.139320E+11 |
February | 0.336647E+10 | 0.165890E+10 | 0.170758E+10 | 0.157357E+10 | 0.101367E+11 |
March | 0.444947E+10 | 0.165545E+10 | 0.279402E+10 | 0.251779E+10 | 0.735627E+10 |
April | 0.628108E+10 | 0.310588E+10 | 0.317519E+10 | 0.569283E+10 | 0.508175E+10 |
May | 0.650922E+10 | 0.260028E+10 | 0.390894E+10 | 0.673542E+10 | 0.293780E+10 |
June | 0.739142E+10 | 0.320326E+10 | 0.418816E+10 | 0.891970E+10 | 0.206287E+10 |
July | 0.820068E+10 | 0.389545E+10 | 0.430523E+10 | 0.102535E+11 | 0.186633E+10 |
August | 0.716946E+10 | 0.329031E+10 | 0.387914E+10 | 0.906109E+10 | 0.209311E+10 |
September | 0.561626E+10 | 0.266577E+10 | 0.295050E+10 | 0.634778E+10 | 0.331889E+10 |
October | 0.404410E+10 | 0.179796E+10 | 0.224614E+10 | 0.318931E+10 | 0.519807E+10 |
November | 0.234257E+10 | 0.866282E+09 | 0.147629E+10 | 0.107850E+10 | 0.811238E+10 |
December | 0.186161E+10 | 0.877591E+09 | 0.984022E+09 | 0.686324E+09 | 0.122736E+11 |
Annual Sum or Average | 0.597742E+11 | 0.266456E+11 | 0.331286E+11 | 0.567554E+11 | 0.743698E+11 |
Minimum of Months | 0.186161E+10 | 0.866282E+09 | 0.984022E+09 | 0.686324E+09 | 0.186633E+10 |
Maximum of Months | 0.820068E+10 | 0.389545E+10 | 0.430523E+10 | 0.102535E+11 | 0.139320E+11 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 8633.86 | 669.86 | 0.00 | 669.86 | 0.00 | 0.00 |
February | 1.09 | 7139.40 | 849.25 | 0.00 | 849.25 | 0.00 | 0.00 |
March | 139.55 | 4766.64 | 1272.76 | 0.00 | 1272.76 | 0.00 | 0.00 |
April | 518.42 | 3328.27 | 1469.31 | 7.24 | 1462.07 | 0.00 | 0.00 |
May | 1323.72 | 1717.00 | 1916.01 | 72.02 | 1843.99 | 0.00 | 0.00 |
June | 2312.30 | 1192.50 | 2239.38 | 203.25 | 2036.13 | 0.00 | 0.00 |
July | 2297.16 | 990.59 | 2100.19 | 140.48 | 1959.71 | 0.00 | 0.00 |
August | 1910.73 | 1201.51 | 1758.47 | 31.17 | 1727.31 | 0.00 | 0.00 |
September | 1058.06 | 2151.58 | 1348.24 | 0.33 | 1347.91 | 0.00 | 0.00 |
October | 193.32 | 3519.62 | 1002.44 | 0.00 | 1002.44 | 0.00 | 0.00 |
November | 23.14 | 5486.44 | 701.22 | 0.00 | 701.22 | 0.00 | 0.00 |
December | 0.00 | 7713.03 | 454.85 | 0.00 | 454.85 | 0.00 | 0.00 |
Annual Sum or Average | 819.69 | 3971.17 | 1317.63 | 38.02 | 1279.61 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 990.59 | 454.85 | 0.00 | 454.85 | 0.00 | 0.00 |
Maximum of Months | 2312.30 | 8633.86 | 2239.38 | 203.25 | 2036.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 235.49 | 5165.58 | 956.91 | 393.77 | 563.14 | 0.00 | 0.00 |
February | 494.01 | 4167.17 | 1268.38 | 557.73 | 710.65 | 0.00 | 0.00 |
March | 993.79 | 2811.45 | 1723.34 | 684.05 | 1039.30 | 0.00 | 0.00 |
April | 1744.12 | 2014.59 | 2116.10 | 926.71 | 1189.39 | 0.00 | 0.00 |
May | 2709.39 | 1097.86 | 2657.65 | 1161.27 | 1496.38 | 0.00 | 0.00 |
June | 3498.93 | 764.27 | 2924.67 | 1273.65 | 1651.02 | 0.00 | 0.00 |
July | 3660.82 | 618.82 | 2956.09 | 1364.01 | 1592.08 | 0.00 | 0.00 |
August | 3087.67 | 734.89 | 2491.93 | 1074.33 | 1417.60 | 0.00 | 0.00 |
September | 2449.18 | 1315.87 | 2222.58 | 1050.28 | 1172.29 | 0.00 | 0.00 |
October | 970.76 | 2100.39 | 1416.38 | 591.61 | 824.77 | 0.00 | 0.00 |
November | 277.51 | 3340.65 | 835.68 | 271.44 | 564.23 | 0.00 | 0.00 |
December | 177.44 | 4710.67 | 647.32 | 277.98 | 369.35 | 0.00 | 0.00 |
Annual Sum or Average | 1698.14 | 2394.99 | 1854.31 | 803.39 | 1050.92 | 0.00 | 0.00 |
Minimum of Months | 177.44 | 618.82 | 647.32 | 271.44 | 369.35 | 0.00 | 0.00 |
Maximum of Months | 3660.82 | 5165.58 | 2956.09 | 1364.01 | 1651.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2962.72 | 6788.17 | 4165.82 | 2850.76 | 1315.06 | 0.00 | 0.00 |
February | 3376.88 | 5549.30 | 4463.60 | 3015.64 | 1447.96 | 0.00 | 0.00 |
March | 3149.64 | 4124.44 | 3884.33 | 2045.36 | 1838.97 | 0.00 | 0.00 |
April | 3386.03 | 3156.33 | 3499.53 | 1636.10 | 1863.43 | 0.00 | 0.00 |
May | 3021.84 | 1803.61 | 2899.24 | 786.02 | 2113.22 | 0.00 | 0.00 |
June | 3431.98 | 1253.12 | 2814.72 | 573.09 | 2241.63 | 0.00 | 0.00 |
July | 3832.96 | 1039.22 | 2979.58 | 750.78 | 2228.80 | 0.00 | 0.00 |
August | 4424.30 | 1250.44 | 3357.00 | 1203.90 | 2153.10 | 0.00 | 0.00 |
September | 4917.07 | 2081.99 | 4067.97 | 2143.49 | 1924.49 | 0.00 | 0.00 |
October | 4207.13 | 3102.04 | 4247.82 | 2664.91 | 1582.91 | 0.00 | 0.00 |
November | 2518.29 | 4588.18 | 3204.97 | 2006.37 | 1198.60 | 0.00 | 0.00 |
December | 2746.48 | 6381.59 | 3417.64 | 2588.82 | 828.82 | 0.00 | 0.00 |
Annual Sum or Average | 3498.22 | 3416.29 | 3578.33 | 1848.81 | 1729.52 | 0.00 | 0.00 |
Minimum of Months | 2518.29 | 1039.22 | 2814.72 | 573.09 | 828.82 | 0.00 | 0.00 |
Maximum of Months | 4917.07 | 6788.17 | 4463.60 | 3015.64 | 2241.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 258.12 | 5486.30 | 949.02 | 383.99 | 565.03 | 0.00 | 0.00 |
February | 638.25 | 4515.63 | 1391.57 | 685.72 | 705.85 | 0.00 | 0.00 |
March | 898.51 | 3142.09 | 1661.25 | 618.08 | 1043.17 | 0.00 | 0.00 |
April | 2154.99 | 2370.11 | 2423.27 | 1198.26 | 1225.00 | 0.00 | 0.00 |
May | 2471.51 | 1277.68 | 2430.28 | 970.84 | 1459.44 | 0.00 | 0.00 |
June | 3405.12 | 946.91 | 2851.64 | 1235.83 | 1615.81 | 0.00 | 0.00 |
July | 3766.09 | 847.27 | 3061.79 | 1454.40 | 1607.39 | 0.00 | 0.00 |
August | 3290.88 | 999.63 | 2676.78 | 1228.47 | 1448.31 | 0.00 | 0.00 |
September | 2400.08 | 1515.63 | 2166.78 | 1028.46 | 1138.31 | 0.00 | 0.00 |
October | 1124.18 | 2369.96 | 1509.90 | 671.28 | 838.62 | 0.00 | 0.00 |
November | 375.50 | 3637.45 | 903.77 | 334.22 | 569.56 | 0.00 | 0.00 |
December | 234.07 | 5092.79 | 695.05 | 327.66 | 367.39 | 0.00 | 0.00 |
Annual Sum or Average | 1756.95 | 2674.60 | 1895.43 | 844.93 | 1050.51 | 0.00 | 0.00 |
Minimum of Months | 234.07 | 847.27 | 695.05 | 327.66 | 367.39 | 0.00 | 0.00 |
Maximum of Months | 3766.09 | 5486.30 | 3061.79 | 1454.40 | 1615.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 8489.76 | 669.85 | 0.00 | 669.85 | 0.00 | 0.00 |
February | 4.74 | 6933.74 | 849.24 | 0.00 | 849.24 | 0.00 | 0.00 |
March | 171.74 | 4517.03 | 1272.75 | 0.00 | 1272.75 | 0.00 | 0.00 |
April | 593.98 | 3050.00 | 1469.31 | 7.24 | 1462.07 | 0.00 | 0.00 |
May | 1428.98 | 1571.84 | 1916.01 | 72.02 | 1843.99 | 0.00 | 0.00 |
June | 2402.14 | 1085.45 | 2239.37 | 203.25 | 2036.12 | 0.00 | 0.00 |
July | 2408.77 | 890.17 | 2100.18 | 140.48 | 1959.70 | 0.00 | 0.00 |
August | 2029.55 | 1052.81 | 1758.47 | 31.16 | 1727.30 | 0.00 | 0.00 |
September | 1153.10 | 1938.14 | 1348.24 | 0.33 | 1347.90 | 0.00 | 0.00 |
October | 263.62 | 3161.69 | 1002.44 | 0.00 | 1002.44 | 0.00 | 0.00 |
November | 42.57 | 5070.10 | 701.22 | 0.00 | 701.22 | 0.00 | 0.00 |
December | 0.00 | 7365.47 | 454.85 | 0.00 | 454.85 | 0.00 | 0.00 |
Annual Sum or Average | 880.19 | 3745.12 | 1317.63 | 38.02 | 1279.60 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 890.17 | 454.85 | 0.00 | 454.85 | 0.00 | 0.00 |
Maximum of Months | 2408.77 | 8489.76 | 2239.37 | 203.25 | 2036.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 234.57 | 5049.03 | 956.91 | 393.77 | 563.14 | 0.00 | 0.00 |
February | 496.98 | 4033.38 | 1268.37 | 557.73 | 710.64 | 0.00 | 0.00 |
March | 992.22 | 2705.00 | 1723.33 | 684.04 | 1039.29 | 0.00 | 0.00 |
April | 1726.78 | 1921.92 | 2116.09 | 926.70 | 1189.38 | 0.00 | 0.00 |
May | 2666.63 | 1056.01 | 2657.64 | 1161.27 | 1496.37 | 0.00 | 0.00 |
June | 3463.62 | 734.95 | 2924.66 | 1273.64 | 1651.02 | 0.00 | 0.00 |
July | 3624.01 | 600.66 | 2956.08 | 1364.00 | 1592.08 | 0.00 | 0.00 |
August | 3065.52 | 705.84 | 2491.92 | 1074.32 | 1417.60 | 0.00 | 0.00 |
September | 2437.27 | 1246.18 | 2222.57 | 1050.28 | 1172.29 | 0.00 | 0.00 |
October | 988.03 | 1954.14 | 1416.37 | 591.61 | 824.77 | 0.00 | 0.00 |
November | 290.75 | 3137.61 | 835.67 | 271.44 | 564.23 | 0.00 | 0.00 |
December | 185.89 | 4498.79 | 647.32 | 277.98 | 369.35 | 0.00 | 0.00 |
Annual Sum or Average | 1687.48 | 2295.36 | 1854.30 | 803.38 | 1050.92 | 0.00 | 0.00 |
Minimum of Months | 185.89 | 600.66 | 647.32 | 271.44 | 369.35 | 0.00 | 0.00 |
Maximum of Months | 3624.01 | 5049.03 | 2956.08 | 1364.00 | 1651.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2919.06 | 6762.48 | 4165.81 | 2850.75 | 1315.05 | 0.00 | 0.00 |
February | 3323.03 | 5510.02 | 4463.59 | 3015.63 | 1447.95 | 0.00 | 0.00 |
March | 3106.84 | 4054.84 | 3884.32 | 2045.36 | 1838.97 | 0.00 | 0.00 |
April | 3354.26 | 3057.32 | 3499.51 | 1636.09 | 1863.42 | 0.00 | 0.00 |
May | 3011.62 | 1746.31 | 2899.23 | 786.02 | 2113.21 | 0.00 | 0.00 |
June | 3441.96 | 1191.42 | 2814.71 | 573.09 | 2241.62 | 0.00 | 0.00 |
July | 3849.53 | 979.80 | 2979.57 | 750.77 | 2228.80 | 0.00 | 0.00 |
August | 4431.09 | 1174.61 | 3356.99 | 1203.90 | 2153.09 | 0.00 | 0.00 |
September | 4883.54 | 2018.34 | 4067.96 | 2143.48 | 1924.48 | 0.00 | 0.00 |
October | 4170.79 | 3014.52 | 4247.81 | 2664.90 | 1582.90 | 0.00 | 0.00 |
November | 2510.51 | 4458.04 | 3204.96 | 2006.37 | 1198.59 | 0.00 | 0.00 |
December | 2741.12 | 6246.33 | 3417.63 | 2588.81 | 828.82 | 0.00 | 0.00 |
Annual Sum or Average | 3479.14 | 3340.77 | 3578.32 | 1848.81 | 1729.51 | 0.00 | 0.00 |
Minimum of Months | 2510.51 | 979.80 | 2814.71 | 573.09 | 828.82 | 0.00 | 0.00 |
Maximum of Months | 4883.54 | 6762.48 | 4463.59 | 3015.63 | 2241.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 261.92 | 5279.20 | 949.02 | 383.98 | 565.03 | 0.00 | 0.00 |
February | 648.07 | 4295.95 | 1391.56 | 685.72 | 705.84 | 0.00 | 0.00 |
March | 934.06 | 2870.22 | 1661.24 | 618.07 | 1043.17 | 0.00 | 0.00 |
April | 2199.93 | 2084.19 | 2423.26 | 1198.26 | 1225.00 | 0.00 | 0.00 |
May | 2511.78 | 1173.36 | 2430.27 | 970.83 | 1459.43 | 0.00 | 0.00 |
June | 3449.75 | 843.36 | 2851.63 | 1235.83 | 1615.80 | 0.00 | 0.00 |
July | 3837.27 | 733.07 | 3061.78 | 1454.40 | 1607.39 | 0.00 | 0.00 |
August | 3386.40 | 826.92 | 2676.77 | 1228.46 | 1448.31 | 0.00 | 0.00 |
September | 2442.37 | 1372.00 | 2166.77 | 1028.46 | 1138.31 | 0.00 | 0.00 |
October | 1170.01 | 2114.79 | 1509.89 | 671.28 | 838.61 | 0.00 | 0.00 |
November | 406.20 | 3269.19 | 903.77 | 334.21 | 569.56 | 0.00 | 0.00 |
December | 253.53 | 4687.15 | 695.05 | 327.66 | 367.39 | 0.00 | 0.00 |
Annual Sum or Average | 1797.53 | 2453.63 | 1895.43 | 844.93 | 1050.50 | 0.00 | 0.00 |
Minimum of Months | 253.53 | 733.07 | 695.05 | 327.66 | 367.39 | 0.00 | 0.00 |
Maximum of Months | 3837.27 | 5279.20 | 3061.78 | 1454.40 | 1615.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 8368.10 | 669.85 | 0.00 | 669.85 | 0.00 | 0.00 |
February | 6.99 | 6765.90 | 849.24 | 0.00 | 849.24 | 0.00 | 0.00 |
March | 190.65 | 4306.86 | 1272.75 | 0.00 | 1272.75 | 0.00 | 0.00 |
April | 617.42 | 2841.01 | 1469.31 | 7.24 | 1462.07 | 0.00 | 0.00 |
May | 1486.31 | 1435.57 | 1916.01 | 72.02 | 1843.99 | 0.00 | 0.00 |
June | 2449.16 | 993.02 | 2239.37 | 203.25 | 2036.12 | 0.00 | 0.00 |
July | 2457.34 | 818.34 | 2100.18 | 140.48 | 1959.70 | 0.00 | 0.00 |
August | 2079.28 | 960.58 | 1758.47 | 31.16 | 1727.30 | 0.00 | 0.00 |
September | 1201.09 | 1762.29 | 1348.24 | 0.33 | 1347.90 | 0.00 | 0.00 |
October | 313.28 | 2847.28 | 1002.44 | 0.00 | 1002.44 | 0.00 | 0.00 |
November | 55.52 | 4825.88 | 701.22 | 0.00 | 701.22 | 0.00 | 0.00 |
December | 0.00 | 7191.46 | 454.85 | 0.00 | 454.85 | 0.00 | 0.00 |
Annual Sum or Average | 910.20 | 3577.77 | 1317.63 | 38.02 | 1279.60 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 818.34 | 454.85 | 0.00 | 454.85 | 0.00 | 0.00 |
Maximum of Months | 2457.34 | 8368.10 | 2239.37 | 203.25 | 2036.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 237.65 | 4999.23 | 956.91 | 393.77 | 563.14 | 0.00 | 0.00 |
February | 508.27 | 3931.09 | 1268.37 | 557.73 | 710.64 | 0.00 | 0.00 |
March | 1032.83 | 2564.02 | 1723.33 | 684.04 | 1039.29 | 0.00 | 0.00 |
April | 1765.16 | 1786.05 | 2116.09 | 926.70 | 1189.38 | 0.00 | 0.00 |
May | 2718.87 | 971.57 | 2657.64 | 1161.27 | 1496.37 | 0.00 | 0.00 |
June | 3481.90 | 679.50 | 2924.66 | 1273.64 | 1651.02 | 0.00 | 0.00 |
July | 3637.80 | 561.52 | 2956.08 | 1364.00 | 1592.08 | 0.00 | 0.00 |
August | 3090.70 | 654.20 | 2491.92 | 1074.32 | 1417.60 | 0.00 | 0.00 |
September | 2483.64 | 1135.24 | 2222.57 | 1050.28 | 1172.29 | 0.00 | 0.00 |
October | 1068.52 | 1743.30 | 1416.37 | 591.61 | 824.77 | 0.00 | 0.00 |
November | 318.22 | 2980.86 | 835.67 | 271.44 | 564.23 | 0.00 | 0.00 |
December | 192.59 | 4410.53 | 647.32 | 277.98 | 369.35 | 0.00 | 0.00 |
Annual Sum or Average | 1717.94 | 2193.30 | 1854.30 | 803.38 | 1050.92 | 0.00 | 0.00 |
Minimum of Months | 192.59 | 561.52 | 647.32 | 271.44 | 369.35 | 0.00 | 0.00 |
Maximum of Months | 3637.80 | 4999.23 | 2956.08 | 1364.00 | 1651.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2943.43 | 6620.89 | 4165.81 | 2850.75 | 1315.05 | 0.00 | 0.00 |
February | 3367.17 | 5303.71 | 4463.59 | 3015.63 | 1447.95 | 0.00 | 0.00 |
March | 3148.79 | 3828.40 | 3884.32 | 2045.36 | 1838.97 | 0.00 | 0.00 |
April | 3375.87 | 2837.56 | 3499.51 | 1636.09 | 1863.42 | 0.00 | 0.00 |
May | 3056.11 | 1596.42 | 2899.23 | 786.02 | 2113.21 | 0.00 | 0.00 |
June | 3464.42 | 1091.23 | 2814.71 | 573.09 | 2241.62 | 0.00 | 0.00 |
July | 3872.66 | 902.25 | 2979.57 | 750.77 | 2228.80 | 0.00 | 0.00 |
August | 4454.36 | 1078.48 | 3356.99 | 1203.90 | 2153.09 | 0.00 | 0.00 |
September | 4922.12 | 1841.62 | 4067.96 | 2143.48 | 1924.48 | 0.00 | 0.00 |
October | 4254.86 | 2708.51 | 4247.81 | 2664.90 | 1582.90 | 0.00 | 0.00 |
November | 2575.24 | 4203.43 | 3204.96 | 2006.37 | 1198.59 | 0.00 | 0.00 |
December | 2780.22 | 6044.79 | 3417.63 | 2588.81 | 828.82 | 0.00 | 0.00 |
Annual Sum or Average | 3518.45 | 3161.34 | 3578.32 | 1848.81 | 1729.51 | 0.00 | 0.00 |
Minimum of Months | 2575.24 | 902.25 | 2814.71 | 573.09 | 828.82 | 0.00 | 0.00 |
Maximum of Months | 4922.12 | 6620.89 | 4463.59 | 3015.63 | 2241.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 261.16 | 5201.62 | 949.02 | 383.98 | 565.03 | 0.00 | 0.00 |
February | 650.45 | 4190.12 | 1391.56 | 685.72 | 705.84 | 0.00 | 0.00 |
March | 940.03 | 2746.52 | 1661.24 | 618.07 | 1043.17 | 0.00 | 0.00 |
April | 2196.31 | 1960.55 | 2423.26 | 1198.26 | 1225.00 | 0.00 | 0.00 |
May | 2514.72 | 1096.85 | 2430.27 | 970.83 | 1459.43 | 0.00 | 0.00 |
June | 3441.24 | 795.86 | 2851.63 | 1235.83 | 1615.80 | 0.00 | 0.00 |
July | 3828.23 | 696.81 | 3061.78 | 1454.40 | 1607.39 | 0.00 | 0.00 |
August | 3383.02 | 781.48 | 2676.77 | 1228.46 | 1448.31 | 0.00 | 0.00 |
September | 2448.99 | 1280.44 | 2166.77 | 1028.46 | 1138.31 | 0.00 | 0.00 |
October | 1190.75 | 1940.74 | 1509.89 | 671.28 | 838.61 | 0.00 | 0.00 |
November | 416.09 | 3129.78 | 903.77 | 334.21 | 569.56 | 0.00 | 0.00 |
December | 256.24 | 4582.44 | 695.05 | 327.66 | 367.39 | 0.00 | 0.00 |
Annual Sum or Average | 1799.70 | 2358.25 | 1895.43 | 844.93 | 1050.50 | 0.00 | 0.00 |
Minimum of Months | 256.24 | 696.81 | 695.05 | 327.66 | 367.39 | 0.00 | 0.00 |
Maximum of Months | 3828.23 | 5201.62 | 3061.78 | 1454.40 | 1615.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.231249E+11 | 0.179414E+10 | 0.00 | 0.179414E+10 | 0.00 | 0.00 |
February | 2644677.08 | 0.172716E+11 | 0.205450E+10 | 0.00 | 0.205450E+10 | 0.00 | 0.00 |
March | 0.373773E+09 | 0.127670E+11 | 0.340896E+10 | 0.00 | 0.340896E+10 | 0.00 | 0.00 |
April | 0.134374E+10 | 0.862687E+10 | 0.380846E+10 | 18764106.05 | 0.378970E+10 | 0.00 | 0.00 |
May | 0.354546E+10 | 0.459883E+10 | 0.513185E+10 | 0.192894E+09 | 0.493895E+10 | 0.00 | 0.00 |
June | 0.599348E+10 | 0.309097E+10 | 0.580447E+10 | 0.526831E+09 | 0.527764E+10 | 0.00 | 0.00 |
July | 0.615273E+10 | 0.265319E+10 | 0.562514E+10 | 0.376260E+09 | 0.524888E+10 | 0.00 | 0.00 |
August | 0.511770E+10 | 0.321811E+10 | 0.470989E+10 | 83472458.26 | 0.462642E+10 | 0.00 | 0.00 |
September | 0.274249E+10 | 0.557691E+10 | 0.349465E+10 | 866516.60 | 0.349378E+10 | 0.00 | 0.00 |
October | 0.517797E+09 | 0.942696E+10 | 0.268495E+10 | 0.00 | 0.268495E+10 | 0.00 | 0.00 |
November | 59983842.91 | 0.142208E+11 | 0.181756E+10 | 0.00 | 0.181756E+10 | 0.00 | 0.00 |
December | 0.00 | 0.206586E+11 | 0.121828E+10 | 0.00 | 0.121828E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.258498E+11 | 0.125235E+12 | 0.415529E+11 | 0.119909E+10 | 0.403538E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.265319E+10 | 0.121828E+10 | 0.00 | 0.121828E+10 | 0.00 | 0.00 |
Maximum of Months | 0.615273E+10 | 0.231249E+11 | 0.580447E+10 | 0.526831E+09 | 0.527764E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.630749E+09 | 0.138355E+11 | 0.256299E+10 | 0.105468E+10 | 0.150831E+10 | 0.00 | 0.00 |
February | 0.119511E+10 | 0.100812E+11 | 0.306846E+10 | 0.134926E+10 | 0.171920E+10 | 0.00 | 0.00 |
March | 0.266176E+10 | 0.753018E+10 | 0.461579E+10 | 0.183215E+10 | 0.278365E+10 | 0.00 | 0.00 |
April | 0.452077E+10 | 0.522181E+10 | 0.548492E+10 | 0.240202E+10 | 0.308290E+10 | 0.00 | 0.00 |
May | 0.725684E+10 | 0.294051E+10 | 0.711825E+10 | 0.311035E+10 | 0.400790E+10 | 0.00 | 0.00 |
June | 0.906923E+10 | 0.198099E+10 | 0.758075E+10 | 0.330130E+10 | 0.427945E+10 | 0.00 | 0.00 |
July | 0.980515E+10 | 0.165744E+10 | 0.791760E+10 | 0.365336E+10 | 0.426424E+10 | 0.00 | 0.00 |
August | 0.827003E+10 | 0.196832E+10 | 0.667439E+10 | 0.287748E+10 | 0.379691E+10 | 0.00 | 0.00 |
September | 0.634828E+10 | 0.341073E+10 | 0.576092E+10 | 0.272234E+10 | 0.303859E+10 | 0.00 | 0.00 |
October | 0.260008E+10 | 0.562569E+10 | 0.379363E+10 | 0.158457E+10 | 0.220906E+10 | 0.00 | 0.00 |
November | 0.719296E+09 | 0.865896E+10 | 0.216607E+10 | 0.703581E+09 | 0.146249E+10 | 0.00 | 0.00 |
December | 0.475251E+09 | 0.126171E+11 | 0.173379E+10 | 0.744531E+09 | 0.989258E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.535525E+11 | 0.755284E+11 | 0.584776E+11 | 0.253356E+11 | 0.331419E+11 | 0.00 | 0.00 |
Minimum of Months | 0.475251E+09 | 0.165744E+10 | 0.173379E+10 | 0.703581E+09 | 0.989258E+09 | 0.00 | 0.00 |
Maximum of Months | 0.980515E+10 | 0.138355E+11 | 0.791760E+10 | 0.365336E+10 | 0.427945E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.793536E+10 | 0.181814E+11 | 0.111577E+11 | 0.763548E+10 | 0.352225E+10 | 0.00 | 0.00 |
February | 0.816935E+10 | 0.134249E+11 | 0.107983E+11 | 0.729545E+10 | 0.350290E+10 | 0.00 | 0.00 |
March | 0.843598E+10 | 0.110469E+11 | 0.104038E+11 | 0.547830E+10 | 0.492550E+10 | 0.00 | 0.00 |
April | 0.877660E+10 | 0.818121E+10 | 0.907078E+10 | 0.424077E+10 | 0.483001E+10 | 0.00 | 0.00 |
May | 0.809369E+10 | 0.483078E+10 | 0.776532E+10 | 0.210528E+10 | 0.566004E+10 | 0.00 | 0.00 |
June | 0.889570E+10 | 0.324808E+10 | 0.729576E+10 | 0.148546E+10 | 0.581030E+10 | 0.00 | 0.00 |
July | 0.102662E+11 | 0.278345E+10 | 0.798051E+10 | 0.201088E+10 | 0.596963E+10 | 0.00 | 0.00 |
August | 0.118500E+11 | 0.334919E+10 | 0.899139E+10 | 0.322453E+10 | 0.576686E+10 | 0.00 | 0.00 |
September | 0.127451E+11 | 0.539652E+10 | 0.105442E+11 | 0.555592E+10 | 0.498827E+10 | 0.00 | 0.00 |
October | 0.112684E+11 | 0.830850E+10 | 0.113774E+11 | 0.713770E+10 | 0.423967E+10 | 0.00 | 0.00 |
November | 0.652741E+10 | 0.118926E+11 | 0.830729E+10 | 0.520052E+10 | 0.310677E+10 | 0.00 | 0.00 |
December | 0.735617E+10 | 0.170925E+11 | 0.915380E+10 | 0.693390E+10 | 0.221991E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.110320E+12 | 0.107736E+12 | 0.112846E+12 | 0.583042E+11 | 0.545421E+11 | 0.00 | 0.00 |
Minimum of Months | 0.652741E+10 | 0.278345E+10 | 0.729576E+10 | 0.148546E+10 | 0.221991E+10 | 0.00 | 0.00 |
Maximum of Months | 0.127451E+11 | 0.181814E+11 | 0.113774E+11 | 0.763548E+10 | 0.596963E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.691340E+09 | 0.146945E+11 | 0.254186E+10 | 0.102847E+10 | 0.151339E+10 | 0.00 | 0.00 |
February | 0.154406E+10 | 0.109242E+11 | 0.336649E+10 | 0.165890E+10 | 0.170758E+10 | 0.00 | 0.00 |
March | 0.240658E+10 | 0.841578E+10 | 0.444948E+10 | 0.165545E+10 | 0.279403E+10 | 0.00 | 0.00 |
April | 0.558573E+10 | 0.614333E+10 | 0.628110E+10 | 0.310590E+10 | 0.317521E+10 | 0.00 | 0.00 |
May | 0.661969E+10 | 0.342215E+10 | 0.650925E+10 | 0.260029E+10 | 0.390896E+10 | 0.00 | 0.00 |
June | 0.882607E+10 | 0.245440E+10 | 0.739145E+10 | 0.320327E+10 | 0.418818E+10 | 0.00 | 0.00 |
July | 0.100871E+11 | 0.226934E+10 | 0.820071E+10 | 0.389547E+10 | 0.430524E+10 | 0.00 | 0.00 |
August | 0.881430E+10 | 0.267742E+10 | 0.716949E+10 | 0.329033E+10 | 0.387916E+10 | 0.00 | 0.00 |
September | 0.622100E+10 | 0.392852E+10 | 0.561629E+10 | 0.266578E+10 | 0.295051E+10 | 0.00 | 0.00 |
October | 0.301099E+10 | 0.634770E+10 | 0.404412E+10 | 0.179797E+10 | 0.224615E+10 | 0.00 | 0.00 |
November | 0.973297E+09 | 0.942828E+10 | 0.234258E+10 | 0.866286E+09 | 0.147630E+10 | 0.00 | 0.00 |
December | 0.626932E+09 | 0.136405E+11 | 0.186162E+10 | 0.877595E+09 | 0.984026E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.554071E+11 | 0.843462E+11 | 0.597744E+11 | 0.266457E+11 | 0.331287E+11 | 0.00 | 0.00 |
Minimum of Months | 0.626932E+09 | 0.226934E+10 | 0.186162E+10 | 0.866286E+09 | 0.984026E+09 | 0.00 | 0.00 |
Maximum of Months | 0.100871E+11 | 0.146945E+11 | 0.820071E+10 | 0.389547E+10 | 0.430524E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.227390E+11 | 0.179414E+10 | 0.00 | 0.179414E+10 | 0.00 | 0.00 |
February | 11461168.83 | 0.167741E+11 | 0.205449E+10 | 0.00 | 0.205449E+10 | 0.00 | 0.00 |
March | 0.459985E+09 | 0.120984E+11 | 0.340895E+10 | 0.00 | 0.340895E+10 | 0.00 | 0.00 |
April | 0.153959E+10 | 0.790559E+10 | 0.380845E+10 | 18764039.42 | 0.378968E+10 | 0.00 | 0.00 |
May | 0.382737E+10 | 0.421002E+10 | 0.513183E+10 | 0.192894E+09 | 0.493893E+10 | 0.00 | 0.00 |
June | 0.622634E+10 | 0.281348E+10 | 0.580445E+10 | 0.526829E+09 | 0.527762E+10 | 0.00 | 0.00 |
July | 0.645164E+10 | 0.238422E+10 | 0.562512E+10 | 0.376259E+09 | 0.524886E+10 | 0.00 | 0.00 |
August | 0.543594E+10 | 0.281985E+10 | 0.470988E+10 | 83472161.85 | 0.462640E+10 | 0.00 | 0.00 |
September | 0.298885E+10 | 0.502367E+10 | 0.349464E+10 | 866513.52 | 0.349377E+10 | 0.00 | 0.00 |
October | 0.706085E+09 | 0.846827E+10 | 0.268494E+10 | 0.00 | 0.268494E+10 | 0.00 | 0.00 |
November | 0.110334E+09 | 0.131417E+11 | 0.181756E+10 | 0.00 | 0.181756E+10 | 0.00 | 0.00 |
December | 0.00 | 0.197277E+11 | 0.121828E+10 | 0.00 | 0.121828E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.277576E+11 | 0.118106E+12 | 0.415527E+11 | 0.119908E+10 | 0.403536E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.238422E+10 | 0.121828E+10 | 0.00 | 0.121828E+10 | 0.00 | 0.00 |
Maximum of Months | 0.645164E+10 | 0.227390E+11 | 0.580445E+10 | 0.526829E+09 | 0.527762E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.628261E+09 | 0.135233E+11 | 0.256298E+10 | 0.105467E+10 | 0.150830E+10 | 0.00 | 0.00 |
February | 0.120229E+10 | 0.975755E+10 | 0.306845E+10 | 0.134926E+10 | 0.171919E+10 | 0.00 | 0.00 |
March | 0.265757E+10 | 0.724508E+10 | 0.461578E+10 | 0.183214E+10 | 0.278364E+10 | 0.00 | 0.00 |
April | 0.447582E+10 | 0.498161E+10 | 0.548490E+10 | 0.240201E+10 | 0.308289E+10 | 0.00 | 0.00 |
May | 0.714231E+10 | 0.282841E+10 | 0.711822E+10 | 0.311034E+10 | 0.400788E+10 | 0.00 | 0.00 |
June | 0.897771E+10 | 0.190500E+10 | 0.758072E+10 | 0.330128E+10 | 0.427943E+10 | 0.00 | 0.00 |
July | 0.970654E+10 | 0.160880E+10 | 0.791757E+10 | 0.365335E+10 | 0.426422E+10 | 0.00 | 0.00 |
August | 0.821069E+10 | 0.189053E+10 | 0.667436E+10 | 0.287746E+10 | 0.379689E+10 | 0.00 | 0.00 |
September | 0.631742E+10 | 0.323011E+10 | 0.576090E+10 | 0.272233E+10 | 0.303857E+10 | 0.00 | 0.00 |
October | 0.264633E+10 | 0.523398E+10 | 0.379362E+10 | 0.158456E+10 | 0.220905E+10 | 0.00 | 0.00 |
November | 0.753612E+09 | 0.813268E+10 | 0.216607E+10 | 0.703579E+09 | 0.146249E+10 | 0.00 | 0.00 |
December | 0.497886E+09 | 0.120495E+11 | 0.173378E+10 | 0.744528E+09 | 0.989254E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.532164E+11 | 0.723866E+11 | 0.584773E+11 | 0.253355E+11 | 0.331418E+11 | 0.00 | 0.00 |
Minimum of Months | 0.497886E+09 | 0.160880E+10 | 0.173378E+10 | 0.703579E+09 | 0.989254E+09 | 0.00 | 0.00 |
Maximum of Months | 0.970654E+10 | 0.135233E+11 | 0.791757E+10 | 0.365335E+10 | 0.427943E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.781842E+10 | 0.181126E+11 | 0.111577E+11 | 0.763545E+10 | 0.352224E+10 | 0.00 | 0.00 |
February | 0.803907E+10 | 0.133298E+11 | 0.107983E+11 | 0.729542E+10 | 0.350288E+10 | 0.00 | 0.00 |
March | 0.832137E+10 | 0.108605E+11 | 0.104038E+11 | 0.547828E+10 | 0.492548E+10 | 0.00 | 0.00 |
April | 0.869424E+10 | 0.792456E+10 | 0.907074E+10 | 0.424075E+10 | 0.482999E+10 | 0.00 | 0.00 |
May | 0.806631E+10 | 0.467731E+10 | 0.776529E+10 | 0.210528E+10 | 0.566002E+10 | 0.00 | 0.00 |
June | 0.892155E+10 | 0.308816E+10 | 0.729573E+10 | 0.148545E+10 | 0.581028E+10 | 0.00 | 0.00 |
July | 0.103106E+11 | 0.262429E+10 | 0.798048E+10 | 0.201087E+10 | 0.596961E+10 | 0.00 | 0.00 |
August | 0.118682E+11 | 0.314608E+10 | 0.899135E+10 | 0.322452E+10 | 0.576684E+10 | 0.00 | 0.00 |
September | 0.126581E+11 | 0.523154E+10 | 0.105441E+11 | 0.555590E+10 | 0.498825E+10 | 0.00 | 0.00 |
October | 0.111710E+11 | 0.807408E+10 | 0.113773E+11 | 0.713767E+10 | 0.423965E+10 | 0.00 | 0.00 |
November | 0.650725E+10 | 0.115552E+11 | 0.830726E+10 | 0.520050E+10 | 0.310676E+10 | 0.00 | 0.00 |
December | 0.734182E+10 | 0.167302E+11 | 0.915377E+10 | 0.693387E+10 | 0.221990E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.109718E+12 | 0.105354E+12 | 0.112846E+12 | 0.583040E+11 | 0.545419E+11 | 0.00 | 0.00 |
Minimum of Months | 0.650725E+10 | 0.262429E+10 | 0.729573E+10 | 0.148545E+10 | 0.221990E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126581E+11 | 0.181126E+11 | 0.113773E+11 | 0.763545E+10 | 0.596961E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.701536E+09 | 0.141398E+11 | 0.254184E+10 | 0.102846E+10 | 0.151338E+10 | 0.00 | 0.00 |
February | 0.156780E+10 | 0.103928E+11 | 0.336647E+10 | 0.165890E+10 | 0.170758E+10 | 0.00 | 0.00 |
March | 0.250179E+10 | 0.768760E+10 | 0.444947E+10 | 0.165545E+10 | 0.279402E+10 | 0.00 | 0.00 |
April | 0.570221E+10 | 0.540222E+10 | 0.628108E+10 | 0.310588E+10 | 0.317519E+10 | 0.00 | 0.00 |
May | 0.672754E+10 | 0.314273E+10 | 0.650922E+10 | 0.260028E+10 | 0.390894E+10 | 0.00 | 0.00 |
June | 0.894176E+10 | 0.218598E+10 | 0.739142E+10 | 0.320326E+10 | 0.418816E+10 | 0.00 | 0.00 |
July | 0.102777E+11 | 0.196345E+10 | 0.820068E+10 | 0.389545E+10 | 0.430523E+10 | 0.00 | 0.00 |
August | 0.907012E+10 | 0.221483E+10 | 0.716946E+10 | 0.329031E+10 | 0.387914E+10 | 0.00 | 0.00 |
September | 0.633062E+10 | 0.355622E+10 | 0.561626E+10 | 0.266577E+10 | 0.295050E+10 | 0.00 | 0.00 |
October | 0.313375E+10 | 0.566425E+10 | 0.404410E+10 | 0.179796E+10 | 0.224614E+10 | 0.00 | 0.00 |
November | 0.105286E+10 | 0.847374E+10 | 0.234257E+10 | 0.866282E+09 | 0.147629E+10 | 0.00 | 0.00 |
December | 0.679051E+09 | 0.125541E+11 | 0.186161E+10 | 0.877591E+09 | 0.984022E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.566868E+11 | 0.773776E+11 | 0.597742E+11 | 0.266456E+11 | 0.331286E+11 | 0.00 | 0.00 |
Minimum of Months | 0.679051E+09 | 0.196345E+10 | 0.186161E+10 | 0.866282E+09 | 0.984022E+09 | 0.00 | 0.00 |
Maximum of Months | 0.102777E+11 | 0.141398E+11 | 0.820068E+10 | 0.389545E+10 | 0.430523E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.224131E+11 | 0.179414E+10 | 0.00 | 0.179414E+10 | 0.00 | 0.00 |
February | 16909952.99 | 0.163681E+11 | 0.205449E+10 | 0.00 | 0.205449E+10 | 0.00 | 0.00 |
March | 0.510626E+09 | 0.115355E+11 | 0.340895E+10 | 0.00 | 0.340895E+10 | 0.00 | 0.00 |
April | 0.160035E+10 | 0.736391E+10 | 0.380845E+10 | 18764039.42 | 0.378968E+10 | 0.00 | 0.00 |
May | 0.398094E+10 | 0.384503E+10 | 0.513183E+10 | 0.192894E+09 | 0.493893E+10 | 0.00 | 0.00 |
June | 0.634823E+10 | 0.257391E+10 | 0.580445E+10 | 0.526829E+09 | 0.527762E+10 | 0.00 | 0.00 |
July | 0.658174E+10 | 0.219184E+10 | 0.562512E+10 | 0.376259E+09 | 0.524886E+10 | 0.00 | 0.00 |
August | 0.556914E+10 | 0.257282E+10 | 0.470988E+10 | 83472161.85 | 0.462640E+10 | 0.00 | 0.00 |
September | 0.311322E+10 | 0.456785E+10 | 0.349464E+10 | 866513.52 | 0.349377E+10 | 0.00 | 0.00 |
October | 0.839100E+09 | 0.762616E+10 | 0.268494E+10 | 0.00 | 0.268494E+10 | 0.00 | 0.00 |
November | 0.143914E+09 | 0.125087E+11 | 0.181756E+10 | 0.00 | 0.181756E+10 | 0.00 | 0.00 |
December | 0.00 | 0.192616E+11 | 0.121828E+10 | 0.00 | 0.121828E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.287042E+11 | 0.112828E+12 | 0.415527E+11 | 0.119908E+10 | 0.403536E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.219184E+10 | 0.121828E+10 | 0.00 | 0.121828E+10 | 0.00 | 0.00 |
Maximum of Months | 0.658174E+10 | 0.224131E+11 | 0.580445E+10 | 0.526829E+09 | 0.527762E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.636515E+09 | 0.133899E+11 | 0.256298E+10 | 0.105467E+10 | 0.150830E+10 | 0.00 | 0.00 |
February | 0.122962E+10 | 0.951009E+10 | 0.306845E+10 | 0.134926E+10 | 0.171919E+10 | 0.00 | 0.00 |
March | 0.276634E+10 | 0.686747E+10 | 0.461578E+10 | 0.183214E+10 | 0.278364E+10 | 0.00 | 0.00 |
April | 0.457529E+10 | 0.462944E+10 | 0.548490E+10 | 0.240201E+10 | 0.308289E+10 | 0.00 | 0.00 |
May | 0.728222E+10 | 0.260225E+10 | 0.711822E+10 | 0.311034E+10 | 0.400788E+10 | 0.00 | 0.00 |
June | 0.902509E+10 | 0.176125E+10 | 0.758072E+10 | 0.330128E+10 | 0.427943E+10 | 0.00 | 0.00 |
July | 0.974348E+10 | 0.150398E+10 | 0.791757E+10 | 0.365335E+10 | 0.426422E+10 | 0.00 | 0.00 |
August | 0.827814E+10 | 0.175222E+10 | 0.667436E+10 | 0.287746E+10 | 0.379689E+10 | 0.00 | 0.00 |
September | 0.643760E+10 | 0.294255E+10 | 0.576090E+10 | 0.272233E+10 | 0.303857E+10 | 0.00 | 0.00 |
October | 0.286193E+10 | 0.466927E+10 | 0.379362E+10 | 0.158456E+10 | 0.220905E+10 | 0.00 | 0.00 |
November | 0.824832E+09 | 0.772640E+10 | 0.216607E+10 | 0.703579E+09 | 0.146249E+10 | 0.00 | 0.00 |
December | 0.515829E+09 | 0.118132E+11 | 0.173378E+10 | 0.744528E+09 | 0.989254E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.541769E+11 | 0.691680E+11 | 0.584773E+11 | 0.253355E+11 | 0.331418E+11 | 0.00 | 0.00 |
Minimum of Months | 0.515829E+09 | 0.150398E+10 | 0.173378E+10 | 0.703579E+09 | 0.989254E+09 | 0.00 | 0.00 |
Maximum of Months | 0.974348E+10 | 0.133899E+11 | 0.791757E+10 | 0.365335E+10 | 0.427943E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.788368E+10 | 0.177334E+11 | 0.111577E+11 | 0.763545E+10 | 0.352224E+10 | 0.00 | 0.00 |
February | 0.814585E+10 | 0.128307E+11 | 0.107983E+11 | 0.729542E+10 | 0.350288E+10 | 0.00 | 0.00 |
March | 0.843371E+10 | 0.102540E+11 | 0.104038E+11 | 0.547828E+10 | 0.492548E+10 | 0.00 | 0.00 |
April | 0.875025E+10 | 0.735495E+10 | 0.907074E+10 | 0.424075E+10 | 0.482999E+10 | 0.00 | 0.00 |
May | 0.818548E+10 | 0.427585E+10 | 0.776529E+10 | 0.210528E+10 | 0.566002E+10 | 0.00 | 0.00 |
June | 0.897978E+10 | 0.282848E+10 | 0.729573E+10 | 0.148545E+10 | 0.581028E+10 | 0.00 | 0.00 |
July | 0.103725E+11 | 0.241658E+10 | 0.798048E+10 | 0.201087E+10 | 0.596961E+10 | 0.00 | 0.00 |
August | 0.119306E+11 | 0.288860E+10 | 0.899135E+10 | 0.322452E+10 | 0.576684E+10 | 0.00 | 0.00 |
September | 0.127581E+11 | 0.477347E+10 | 0.105441E+11 | 0.555590E+10 | 0.498825E+10 | 0.00 | 0.00 |
October | 0.113962E+11 | 0.725448E+10 | 0.113773E+11 | 0.713767E+10 | 0.423965E+10 | 0.00 | 0.00 |
November | 0.667501E+10 | 0.108953E+11 | 0.830726E+10 | 0.520050E+10 | 0.310676E+10 | 0.00 | 0.00 |
December | 0.744655E+10 | 0.161904E+11 | 0.915377E+10 | 0.693387E+10 | 0.221990E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.110958E+12 | 0.996962E+11 | 0.112846E+12 | 0.583040E+11 | 0.545419E+11 | 0.00 | 0.00 |
Minimum of Months | 0.667501E+10 | 0.241658E+10 | 0.729573E+10 | 0.148545E+10 | 0.221990E+10 | 0.00 | 0.00 |
Maximum of Months | 0.127581E+11 | 0.177334E+11 | 0.113773E+11 | 0.763545E+10 | 0.596961E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.699502E+09 | 0.139320E+11 | 0.254184E+10 | 0.102846E+10 | 0.151338E+10 | 0.00 | 0.00 |
February | 0.157357E+10 | 0.101367E+11 | 0.336647E+10 | 0.165890E+10 | 0.170758E+10 | 0.00 | 0.00 |
March | 0.251779E+10 | 0.735627E+10 | 0.444947E+10 | 0.165545E+10 | 0.279402E+10 | 0.00 | 0.00 |
April | 0.569283E+10 | 0.508175E+10 | 0.628108E+10 | 0.310588E+10 | 0.317519E+10 | 0.00 | 0.00 |
May | 0.673542E+10 | 0.293780E+10 | 0.650922E+10 | 0.260028E+10 | 0.390894E+10 | 0.00 | 0.00 |
June | 0.891970E+10 | 0.206287E+10 | 0.739142E+10 | 0.320326E+10 | 0.418816E+10 | 0.00 | 0.00 |
July | 0.102535E+11 | 0.186633E+10 | 0.820068E+10 | 0.389545E+10 | 0.430523E+10 | 0.00 | 0.00 |
August | 0.906109E+10 | 0.209311E+10 | 0.716946E+10 | 0.329031E+10 | 0.387914E+10 | 0.00 | 0.00 |
September | 0.634778E+10 | 0.331889E+10 | 0.561626E+10 | 0.266577E+10 | 0.295050E+10 | 0.00 | 0.00 |
October | 0.318931E+10 | 0.519807E+10 | 0.404410E+10 | 0.179796E+10 | 0.224614E+10 | 0.00 | 0.00 |
November | 0.107850E+10 | 0.811238E+10 | 0.234257E+10 | 0.866282E+09 | 0.147629E+10 | 0.00 | 0.00 |
December | 0.686324E+09 | 0.122736E+11 | 0.186161E+10 | 0.877591E+09 | 0.984022E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.567554E+11 | 0.743698E+11 | 0.597742E+11 | 0.266456E+11 | 0.331286E+11 | 0.00 | 0.00 |
Minimum of Months | 0.686324E+09 | 0.186633E+10 | 0.186161E+10 | 0.866282E+09 | 0.984022E+09 | 0.00 | 0.00 |
Maximum of Months | 0.102535E+11 | 0.139320E+11 | 0.820068E+10 | 0.389545E+10 | 0.430523E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.448078E+11 | -0.443322E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -475521631.1 | 60.05 | 0.00 | 0.00 |
February | 0.415062E+11 | -0.410826E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -423664310.7 | 60.05 | 0.00 | 0.00 |
March | 0.483134E+11 | -0.478530E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -460412629.4 | 60.05 | 0.00 | 0.00 |
April | 0.421874E+11 | -0.417478E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -439679277.3 | 60.05 | 0.00 | 0.00 |
May | 0.424530E+11 | -0.420023E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -450631271.9 | 60.05 | 0.00 | 0.00 |
June | 0.393092E+11 | -0.388760E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -433183918.4 | 60.05 | 0.00 | 0.00 |
July | 0.353633E+11 | -0.349195E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443767777.2 | 60.05 | 0.00 | 0.00 |
August | 0.376925E+11 | -0.372479E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444598804.7 | 60.05 | 0.00 | 0.00 |
September | 0.346700E+11 | -0.342388E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -431170733.7 | 60.05 | 0.00 | 0.00 |
October | 0.375115E+11 | -0.370647E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -446871944.5 | 60.05 | 0.00 | 0.00 |
November | 0.392728E+11 | -0.388367E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -436189687.5 | 60.05 | 0.00 | 0.00 |
December | 0.416785E+11 | -0.412190E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -459453848.6 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.484766E+12 | -0.479420E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.534515E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.346700E+11 | -0.478530E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -475521631.1 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.483134E+11 | -0.342388E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -423664310.7 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 214.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 334.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 285.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 400.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 414.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 326.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 254.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3807.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.428249E+11 | 74755.51 | 31-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236946E+11 | 85636.49 | 02-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.600778E+10 | 34681.28 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125733E+10 | 21060.58 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11409058.42 | 1962.85 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131444E+09 | 8521.31 | 23-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.734678E+10 | 50894.37 | 25-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187968E+11 | 57239.16 | 11-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100071E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.428249E+11 | 85636.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 98915681.72 | 43244.81 | 30-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 73588601.21 | 43257.99 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 362137.08 | 1071.30 | 11-DEC-06:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172866E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 98915681.72 | 43257.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.121303E+11 | 25983.43 | 02-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.771323E+10 | 25860.27 | 15-FEB-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311521E+10 | 25869.41 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.818583E+09 | 26791.22 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25903203.23 | 6802.47 | 02-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126035E+09 | 25133.30 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.557563E+09 | 25854.16 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.309464E+10 | 25861.59 | 21-NOV-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.722607E+10 | 25868.85 | 22-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.348076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121303E+11 | 26791.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.879383E+10 | 22061.25 | 10-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.563054E+10 | 22060.04 | 15-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.287153E+10 | 22065.46 | 13-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114434E+10 | 22160.97 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 53185181.31 | 7604.61 | 02-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23719422.13 | 3017.46 | 02-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 89810.16 | 898.10 | 07-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.230683E+09 | 20313.19 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.835937E+09 | 20903.50 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.306134E+10 | 22063.59 | 24-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.635958E+10 | 22056.27 | 28-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.879383E+10 | 22160.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.965714E+10 | 28958.18 | 18-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.592054E+10 | 28817.01 | 15-FEB-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.336147E+10 | 28828.88 | 16-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128411E+10 | 29694.22 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141568E+09 | 15732.61 | 02-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32594620.43 | 3656.68 | 03-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.272979E+09 | 27244.31 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.820305E+09 | 28027.99 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.330504E+10 | 28821.34 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.720189E+10 | 28893.42 | 27-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.965714E+10 | 29694.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.721799E+10 | 23191.66 | 27-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.410555E+10 | 23190.37 | 16-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151991E+10 | 23161.71 | 06-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.260122E+09 | 23143.84 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 37960974.18 | 4266.54 | 02-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2753760.60 | 1279.25 | 03-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144621E+09 | 6224.30 | 29-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.416088E+09 | 21558.55 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171195E+10 | 23190.11 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.354645E+10 | 23187.73 | 12-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.721799E+10 | 23191.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.505457E+12 | 800793.71 | 30-JAN-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.299488E+12 | 908125.80 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113125E+12 | 436206.98 | 23-MAR-09:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.275174E+11 | 680584.84 | 05-APR-13:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.422803E+09 | 358197.37 | 01-MAY-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 70829068.18 | 196086.74 | 01-JUN-13:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.686080E+09 | 417280.91 | 30-SEP-09:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.442731E+10 | 581631.63 | 13-OCT-09:59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130098E+12 | 601692.59 | 25-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.319095E+12 | 634852.68 | 11-DEC-08:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140039E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.505457E+12 | 908125.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.434782E+11 | 774723.36 | 17-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153214E+11 | 772928.14 | 06-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.393458E+10 | 772519.81 | 06-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.769341E+09 | 768609.86 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104704E+11 | 773708.64 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180043E+11 | 772650.94 | 11-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.919781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.434782E+11 | 774723.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.243737E+12 | 363301.42 | 18-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164916E+12 | 361984.32 | 21-FEB-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103859E+12 | 361963.23 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.464024E+11 | 360417.09 | 03-APR-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.794981E+10 | 317028.12 | 02-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.203547E+10 | 298646.29 | 02-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 61555791.28 | 35795.32 | 24-JUL-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.800599E+09 | 58219.85 | 07-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137606E+11 | 338696.79 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.439926E+11 | 355189.03 | 23-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110553E+12 | 361953.52 | 27-NOV-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189925E+12 | 362207.08 | 26-DEC-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.927993E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 61555791.28 | 35795.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.243737E+12 | 363301.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.140270E+12 | 262742.50 | 18-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.894546E+11 | 262250.49 | 21-FEB-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.536732E+11 | 261706.69 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.244433E+11 | 260566.75 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.343102E+10 | 218936.49 | 02-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136629E+10 | 206167.56 | 02-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 42484792.23 | 12888.31 | 24-JUL-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.358866E+09 | 41161.01 | 17-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.680789E+10 | 233964.93 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.226810E+11 | 245400.31 | 23-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.655045E+11 | 261699.61 | 27-NOV-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111234E+12 | 262445.99 | 04-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.519267E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 42484792.23 | 12888.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.140270E+12 | 262742.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.167335E+12 | 355033.38 | 18-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102538E+12 | 353938.37 | 06-FEB-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.696382E+11 | 353725.64 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.341735E+11 | 352214.70 | 03-APR-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.642367E+10 | 309813.06 | 02-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.204652E+10 | 291849.61 | 02-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.192818E+09 | 29986.92 | 24-JUL-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.573994E+09 | 38919.62 | 07-AUG-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.870763E+10 | 330988.57 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.237103E+11 | 347105.48 | 23-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.779680E+11 | 353716.15 | 27-NOV-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139556E+12 | 353963.87 | 26-DEC-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.632863E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.192818E+09 | 29986.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.167335E+12 | 355033.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144076E+12 | 274515.04 | 18-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.912476E+11 | 274284.72 | 06-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.592564E+11 | 274337.67 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.249597E+11 | 273839.53 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.527027E+10 | 228226.29 | 02-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173264E+10 | 214864.14 | 02-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114970E+09 | 26889.22 | 12-JUL-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.383647E+09 | 30263.28 | 07-AUG-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.917315E+10 | 243937.90 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.256181E+11 | 255891.29 | 23-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.665819E+11 | 274330.62 | 27-NOV-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112757E+12 | 274413.67 | 04-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.541171E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.114970E+09 | 26889.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.144076E+12 | 274515.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.567238E+11 | 72942.24 | 30-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.313747E+11 | 73746.22 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103025E+11 | 49118.25 | 06-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.249679E+10 | 30704.65 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12164715.73 | 4098.16 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117739E+09 | 10995.96 | 29-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.867162E+09 | 20150.59 | 23-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153226E+11 | 68120.51 | 25-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.365055E+11 | 68758.72 | 09-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153723E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.567238E+11 | 73746.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.305554E+11 | 133043.02 | 17-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.206824E+11 | 132808.95 | 21-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116090E+11 | 132785.03 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.488500E+10 | 132966.15 | 03-APR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.396104E+09 | 109048.12 | 22-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 69217441.21 | 13736.94 | 03-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105357E+10 | 124322.99 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.539055E+10 | 130809.50 | 23-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140364E+11 | 132931.83 | 14-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243162E+11 | 133040.72 | 04-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112994E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.305554E+11 | 133043.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.346081E+11 | 46899.10 | 18-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.255992E+11 | 46846.79 | 05-FEB-20:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179322E+11 | 46873.27 | 02-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.960648E+10 | 46603.55 | 03-APR-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.290381E+10 | 41424.42 | 02-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107594E+10 | 37123.88 | 02-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.322817E+09 | 27939.03 | 24-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.789733E+09 | 26239.79 | 07-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.411785E+10 | 43801.08 | 30-SEP-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100167E+11 | 45677.57 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193277E+11 | 46829.17 | 14-NOV-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.292543E+11 | 46832.95 | 15-DEC-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155555E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.322817E+09 | 26239.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.346081E+11 | 46899.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.212519E+11 | 30389.29 | 18-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150176E+11 | 30355.39 | 05-FEB-20:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.989818E+10 | 30372.55 | 02-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.524149E+10 | 30197.78 | 03-APR-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116980E+10 | 26841.86 | 02-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.521529E+09 | 24055.22 | 02-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 89328021.17 | 9719.43 | 24-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.256399E+09 | 16941.45 | 07-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.188470E+10 | 28381.86 | 30-SEP-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.524004E+10 | 29597.77 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119019E+11 | 30343.98 | 14-NOV-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182550E+11 | 30346.42 | 15-DEC-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.907277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 89328021.17 | 9719.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.212519E+11 | 30389.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.260408E+11 | 46045.73 | 18-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.181131E+11 | 45990.25 | 11-FEB-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132470E+11 | 46020.36 | 02-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.772400E+10 | 45755.56 | 03-APR-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.245115E+10 | 40670.67 | 02-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112374E+10 | 36448.37 | 02-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.384021E+09 | 22422.68 | 24-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.653804E+09 | 25272.66 | 07-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.293681E+10 | 43004.08 | 30-SEP-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.645080E+10 | 44846.42 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149263E+11 | 45977.07 | 14-NOV-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229372E+11 | 45980.79 | 15-DEC-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116989E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.384021E+09 | 22422.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.260408E+11 | 46045.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.198592E+11 | 30786.83 | 18-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134409E+11 | 30749.75 | 11-FEB-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.907683E+10 | 30762.82 | 02-MAR-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.445756E+10 | 30592.81 | 03-APR-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134436E+10 | 27193.00 | 02-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.552879E+09 | 24369.91 | 02-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.125298E+09 | 4210.16 | 11-JUL-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.264723E+09 | 15082.71 | 07-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.202630E+10 | 28753.15 | 30-SEP-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.476531E+10 | 29984.97 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103145E+11 | 30740.93 | 14-NOV-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160967E+11 | 30743.40 | 15-DEC-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.823246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.125298E+09 | 4210.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.198592E+11 | 30786.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.703058E+10 | 181024.17 | 31-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119773E+11 | 187251.84 | 02-FEB-07:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.550974E+09 | 19780.58 | 11-DEC-21:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119773E+11 | 187251.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3659.99 | 3659.99 | 0.52 | 08-JAN-02:03 | 0.52 | 0.00 |
February | 0.00 | 0.00 | 183693.85 | 183693.85 | 2221.65 | 10-FEB-17:01 | 2221.65 | 0.00 |
March | 0.00 | 0.00 | 0.883886E+09 | 0.883886E+09 | 39800.80 | 19-MAR-13:21 | 39800.80 | 0.00 |
April | 0.00 | 0.00 | 0.164551E+11 | 0.151966E+11 | 167381.03 | 16-APR-14:51 | 122251.95 | 0.08 |
May | 0.00 | 0.00 | 0.369068E+11 | 0.335970E+11 | 145765.81 | 31-MAY-15:00 | 134178.08 | 0.27 |
June | 0.00 | 0.00 | 0.103571E+12 | 0.882616E+11 | 227806.42 | 26-JUN-04:11 | 172318.52 | 0.51 |
July | 0.00 | 0.00 | 0.150557E+12 | 0.119646E+12 | 208762.35 | 27-JUL-05:03 | 77323.24 | 0.64 |
August | 0.00 | 0.00 | 0.151392E+12 | 0.121754E+12 | 231607.67 | 03-AUG-05:02 | 161003.15 | 0.62 |
September | 0.00 | 0.00 | 0.575551E+11 | 0.550442E+11 | 175118.89 | 11-SEP-04:11 | 105109.56 | 0.27 |
October | 0.00 | 0.00 | 0.518290E+10 | 0.518290E+10 | 107946.67 | 20-OCT-15:00 | 107946.67 | 0.03 |
November | 0.00 | 0.00 | 0.335923E+09 | 0.335535E+09 | 48686.93 | 09-NOV-06:02 | 42227.79 | 0.00 |
December | 0.00 | 0.00 | 166115.13 | 166115.13 | 750.52 | 01-DEC-17:03 | 750.52 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.522840E+12 | 0.439902E+12 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 3659.99 | 3659.99 | 0.52 | 0.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.151392E+12 | 0.121754E+12 | 231607.67 | 172318.52 | 0.64 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 127639.66 | 127639.66 | 5.36 | 01-JAN-16:43 | 5.36 | 0.00 |
February | 0.00 | 0.00 | 554628.57 | 554628.57 | 7452.31 | 24-FEB-10:01 | 7452.31 | 0.00 |
March | 0.00 | 0.00 | 0.136351E+11 | 0.136351E+11 | 642619.62 | 24-MAR-14:01 | 642619.62 | 0.00 |
April | 0.00 | 0.00 | 0.147229E+12 | 0.134721E+12 | 1498924.52 | 18-APR-14:05 | 1257048.60 | 0.07 |
May | 0.00 | 0.00 | 0.357255E+12 | 0.325491E+12 | 1403143.10 | 31-MAY-14:05 | 1279931.93 | 0.27 |
June | 0.00 | 0.00 | 0.953554E+12 | 0.802116E+12 | 2146880.78 | 13-JUN-05:01 | 866109.57 | 0.50 |
July | 0.00 | 0.00 | 0.128437E+13 | 0.100749E+13 | 2047954.22 | 27-JUL-05:03 | 758011.47 | 0.59 |
August | 0.00 | 0.00 | 0.124624E+13 | 0.985155E+12 | 2598503.78 | 03-AUG-05:02 | 1586144.32 | 0.57 |
September | 0.00 | 0.00 | 0.525828E+12 | 0.504184E+12 | 1595941.38 | 06-SEP-14:05 | 1423082.45 | 0.27 |
October | 0.00 | 0.00 | 0.600434E+11 | 0.600434E+11 | 981527.99 | 20-OCT-15:00 | 981527.99 | 0.03 |
November | 0.00 | 0.00 | 0.627949E+10 | 0.627949E+10 | 734801.32 | 03-NOV-14:02 | 734801.32 | 0.00 |
December | 0.00 | 0.00 | 114693.28 | 114693.28 | 5.59 | 02-DEC-16:07 | 5.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.459444E+13 | 0.383911E+13 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 114693.28 | 114693.28 | 5.36 | 5.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.128437E+13 | 0.100749E+13 | 2598503.78 | 1586144.32 | 0.59 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3783396.36 | 3783396.36 | 3347.61 | 02-JAN-06:01 | 3347.61 | 0.00 |
February | 0.00 | 0.00 | 3968659.65 | 3968659.65 | 8640.76 | 06-FEB-06:12 | 8640.76 | 0.00 |
March | 0.00 | 0.00 | 0.633974E+09 | 0.633974E+09 | 28778.33 | 25-MAR-14:57 | 28778.33 | 0.00 |
April | 0.00 | 0.00 | 0.160024E+11 | 0.148713E+11 | 183505.27 | 16-APR-16:21 | 135094.35 | 0.07 |
May | 0.00 | 0.00 | 0.391425E+11 | 0.364163E+11 | 173833.49 | 31-MAY-15:00 | 163358.85 | 0.26 |
June | 0.00 | 0.00 | 0.108946E+12 | 0.943255E+11 | 291819.28 | 25-JUN-15:01 | 219349.98 | 0.48 |
July | 0.00 | 0.00 | 0.144089E+12 | 0.117918E+12 | 284430.01 | 20-JUL-05:02 | 102823.58 | 0.58 |
August | 0.00 | 0.00 | 0.137558E+12 | 0.112298E+12 | 352989.54 | 03-AUG-04:01 | 190698.39 | 0.55 |
September | 0.00 | 0.00 | 0.565082E+11 | 0.547364E+11 | 218712.19 | 11-SEP-05:02 | 116165.49 | 0.26 |
October | 0.00 | 0.00 | 0.432015E+10 | 0.432015E+10 | 101476.74 | 20-OCT-15:00 | 101476.74 | 0.03 |
November | 0.00 | 0.00 | 0.146621E+09 | 0.146621E+09 | 12066.10 | 03-NOV-14:45 | 12066.10 | 0.00 |
December | 0.00 | 0.00 | 13278601.60 | 13278601.60 | 7464.80 | 09-DEC-06:12 | 7464.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.507367E+12 | 0.435687E+12 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 3783396.36 | 3783396.36 | 3347.61 | 3347.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.144089E+12 | 0.117918E+12 | 352989.54 | 219349.98 | 0.58 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 91396726.16 | 91396726.16 | 57352.63 | 14-JAN-06:06 | 57352.63 | 0.00 |
February | 0.00 | 0.00 | 0.141126E+09 | 0.141126E+09 | 71888.09 | 24-FEB-06:02 | 71888.09 | 0.00 |
March | 0.00 | 0.00 | 0.159179E+10 | 0.159179E+10 | 111024.43 | 27-MAR-04:02 | 111024.43 | 0.00 |
April | 0.00 | 0.00 | 0.839460E+10 | 0.729454E+10 | 101866.56 | 19-APR-05:00 | 101866.56 | 0.06 |
May | 0.00 | 0.00 | 0.265414E+11 | 0.205393E+11 | 109014.91 | 11-MAY-15:55 | 43000.35 | 0.24 |
June | 0.00 | 0.00 | 0.584613E+11 | 0.427109E+11 | 156178.16 | 27-JUN-04:51 | 64644.94 | 0.46 |
July | 0.00 | 0.00 | 0.797603E+11 | 0.537192E+11 | 141753.47 | 06-JUL-04:53 | 56893.46 | 0.51 |
August | 0.00 | 0.00 | 0.866746E+11 | 0.604414E+11 | 147078.68 | 21-AUG-03:50 | 113358.76 | 0.54 |
September | 0.00 | 0.00 | 0.406882E+11 | 0.358761E+11 | 132418.92 | 04-SEP-16:49 | 132418.92 | 0.27 |
October | 0.00 | 0.00 | 0.130509E+11 | 0.127358E+11 | 133113.02 | 13-OCT-03:13 | 133113.02 | 0.05 |
November | 0.00 | 0.00 | 0.524580E+10 | 0.511697E+10 | 110622.20 | 22-NOV-05:46 | 110622.20 | 0.02 |
December | 0.00 | 0.00 | 0.626302E+09 | 0.626302E+09 | 111808.05 | 06-DEC-06:00 | 111808.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.321268E+12 | 0.240885E+12 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 91396726.16 | 91396726.16 | 57352.63 | 43000.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.866746E+11 | 0.604414E+11 | 156178.16 | 133113.02 | 0.54 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3673730.69 | 3673730.69 | 59.12 | 07-JAN-21:52 | 59.12 | 0.00 |
February | 0.00 | 0.00 | 0.157489E+12 | 0.157489E+12 | 319619.24 | 03-FEB-19:01 | 319619.24 | 0.00 |
March | 0.00 | 0.00 | 0.234796E+12 | 0.234796E+12 | 323587.96 | 06-MAR-14:22 | 323587.96 | 0.01 |
April | 0.00 | 0.00 | 0.266969E+12 | 0.266155E+12 | 524759.64 | 18-APR-08:35 | 383175.16 | 0.12 |
May | 0.00 | 0.00 | 0.257935E+11 | 0.257935E+11 | 232181.06 | 31-MAY-23:53 | 232181.06 | 0.25 |
June | 0.00 | 0.00 | 0.332473E+12 | 0.284726E+12 | 546139.23 | 13-JUN-06:52 | 196184.47 | 0.69 |
July | 0.00 | 0.00 | 0.466481E+12 | 0.427794E+12 | 517195.35 | 06-JUL-05:51 | 203815.29 | 0.99 |
August | 0.00 | 0.00 | 0.610095E+12 | 0.548152E+12 | 560533.96 | 31-AUG-12:03 | 391240.52 | 0.94 |
September | 0.00 | 0.00 | 0.564076E+11 | 0.564076E+11 | 266531.88 | 30-SEP-23:21 | 266531.88 | 0.37 |
October | 0.00 | 0.00 | 0.168013E+12 | 0.167061E+12 | 344387.31 | 20-OCT-16:13 | 344387.31 | 0.05 |
November | 0.00 | 0.00 | 0.204747E+12 | 0.204462E+12 | 326592.57 | 01-NOV-00:22 | 326592.57 | 0.07 |
December | 0.00 | 0.00 | 0.255899E+12 | 0.255899E+12 | 260591.73 | 19-DEC-06:10 | 260591.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.277917E+13 | 0.262874E+13 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 3673730.69 | 3673730.69 | 59.12 | 59.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.610095E+12 | 0.548152E+12 | 560533.96 | 391240.52 | 0.99 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.344206E+10 | 0.344206E+10 | 8799.44 | 30-JAN-13:01 | 8799.44 | 0.00 |
February | 0.00 | 0.00 | 0.766102E+10 | 0.766102E+10 | 13114.04 | 04-FEB-10:31 | 13114.04 | 0.00 |
March | 0.00 | 0.00 | 0.158367E+11 | 0.158364E+11 | 7978.41 | 31-MAR-23:47 | 7978.41 | 0.00 |
April | 0.00 | 0.00 | 0.211777E+11 | 0.211511E+11 | 9692.42 | 16-APR-17:53 | 9688.97 | 0.00 |
May | 0.00 | 0.00 | 0.754346E+10 | 0.744951E+10 | 4855.11 | 31-MAY-23:20 | 4804.62 | 0.00 |
June | 0.00 | 0.00 | 0.128432E+11 | 0.126384E+11 | 6732.73 | 30-JUN-23:51 | 6729.52 | 0.00 |
July | 0.00 | 0.00 | 0.187805E+11 | 0.184692E+11 | 8677.40 | 31-JUL-24:00 | 8614.48 | 0.00 |
August | 0.00 | 0.00 | 0.237950E+11 | 0.234714E+11 | 10140.29 | 04-AUG-16:00 | 9576.08 | 0.00 |
September | 0.00 | 0.00 | 0.751511E+10 | 0.745684E+10 | 4203.39 | 30-SEP-23:51 | 4203.39 | 0.00 |
October | 0.00 | 0.00 | 0.116843E+11 | 0.116785E+11 | 6090.18 | 31-OCT-23:52 | 6090.18 | 0.00 |
November | 0.00 | 0.00 | 0.152345E+11 | 0.152251E+11 | 13741.04 | 26-NOV-08:11 | 13741.04 | 0.00 |
December | 0.00 | 0.00 | 0.198902E+11 | 0.198902E+11 | 8700.57 | 01-DEC-16:08 | 8700.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.165404E+12 | 0.164370E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.344206E+10 | 0.344206E+10 | 4203.39 | 4203.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.237950E+11 | 0.234714E+11 | 13741.04 | 13741.04 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.137109E+11 | 0.137109E+11 | 28259.09 | 19-JAN-12:02 | 28259.09 | 0.00 |
February | 0.00 | 0.00 | 0.584684E+11 | 0.584684E+11 | 124749.76 | 04-FEB-10:31 | 124749.76 | 0.00 |
March | 0.00 | 0.00 | 0.137715E+12 | 0.137713E+12 | 72721.72 | 31-MAR-23:12 | 72721.72 | 0.00 |
April | 0.00 | 0.00 | 0.193661E+12 | 0.193398E+12 | 92202.27 | 18-APR-15:40 | 88746.63 | 0.00 |
May | 0.00 | 0.00 | 0.659448E+11 | 0.650156E+11 | 46230.13 | 31-MAY-23:20 | 45714.33 | 0.00 |
June | 0.00 | 0.00 | 0.119865E+12 | 0.117826E+12 | 65168.77 | 30-JUN-23:02 | 64917.61 | 0.00 |
July | 0.00 | 0.00 | 0.176618E+12 | 0.173516E+12 | 81417.47 | 31-JUL-23:50 | 80833.42 | 0.00 |
August | 0.00 | 0.00 | 0.223708E+12 | 0.220487E+12 | 97185.12 | 04-AUG-16:00 | 91546.37 | 0.00 |
September | 0.00 | 0.00 | 0.644457E+11 | 0.638693E+11 | 39444.16 | 06-SEP-17:30 | 37407.11 | 0.00 |
October | 0.00 | 0.00 | 0.994194E+11 | 0.993606E+11 | 54222.79 | 31-OCT-23:13 | 54222.79 | 0.00 |
November | 0.00 | 0.00 | 0.127347E+12 | 0.127253E+12 | 129138.08 | 26-NOV-08:11 | 129138.08 | 0.00 |
December | 0.00 | 0.00 | 0.167225E+12 | 0.167225E+12 | 80742.34 | 01-DEC-16:08 | 80742.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.144813E+13 | 0.143784E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.137109E+11 | 0.137109E+11 | 28259.09 | 28259.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.223708E+12 | 0.220487E+12 | 129138.08 | 129138.08 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.655072E+09 | 0.655072E+09 | 2483.49 | 12-JAN-16:30 | 2483.49 | 0.00 |
February | 0.00 | 0.00 | 0.429078E+10 | 0.429078E+10 | 10507.25 | 04-FEB-10:31 | 10507.25 | 0.00 |
March | 0.00 | 0.00 | 0.120082E+11 | 0.120079E+11 | 6655.90 | 23-MAR-17:00 | 6655.90 | 0.00 |
April | 0.00 | 0.00 | 0.180343E+11 | 0.180086E+11 | 9429.27 | 18-APR-15:40 | 9082.38 | 0.00 |
May | 0.00 | 0.00 | 0.586428E+10 | 0.577173E+10 | 4549.17 | 31-MAY-23:10 | 4490.55 | 0.00 |
June | 0.00 | 0.00 | 0.116630E+11 | 0.114590E+11 | 6460.26 | 30-JUN-23:02 | 6434.64 | 0.00 |
July | 0.00 | 0.00 | 0.174722E+11 | 0.171622E+11 | 8001.66 | 03-JUL-16:00 | 7453.32 | 0.00 |
August | 0.00 | 0.00 | 0.220767E+11 | 0.217559E+11 | 9970.97 | 04-AUG-16:00 | 9406.98 | 0.00 |
September | 0.00 | 0.00 | 0.555530E+10 | 0.549774E+10 | 4119.97 | 06-SEP-17:30 | 3915.41 | 0.00 |
October | 0.00 | 0.00 | 0.798918E+10 | 0.798339E+10 | 5382.91 | 11-OCT-16:50 | 5382.91 | 0.00 |
November | 0.00 | 0.00 | 0.107505E+11 | 0.107413E+11 | 12894.34 | 26-NOV-08:11 | 12894.34 | 0.00 |
December | 0.00 | 0.00 | 0.146601E+11 | 0.146601E+11 | 7851.66 | 01-DEC-16:08 | 7851.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.131020E+12 | 0.129993E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.655072E+09 | 0.655072E+09 | 2483.49 | 2483.49 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.220767E+11 | 0.217559E+11 | 12894.34 | 12894.34 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 564661.18 | 4543504.69 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 388960.08 | 3940492.96 | 21-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 182799.26 | 3505456.42 | 25-MAR-04:01 |
April | 0.00 | 0.00 | 01-APR-00:03 | 75772.34 | 3657453.71 | 01-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 11914.64 | 3267873.93 | 02-MAY-04:11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 4097.77 | 2871209.72 | 02-JUN-05:01 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 497.14 | 208703.21 | 24-JUL-05:01 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1517.78 | 388786.70 | 07-AUG-05:02 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 20020.19 | 3359021.90 | 30-SEP-04:01 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 58022.95 | 3615852.69 | 16-OCT-04:11 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 217025.88 | 3718956.36 | 28-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 401527.92 | 3831784.04 | 18-DEC-05:01 |
Annual Sum or Average | 0.00 | 159582.29 | ||||
Minimum of Months | 0.00 | 0.00 | 497.14 | 208703.21 | ||
Maximum of Months | 0.00 | 0.00 | 564661.18 | 4543504.69 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1633.21 | 93930.42 | 13-JAN-22:03 | 120702.01 | 990083.28 | 08-JAN-01:51 |
February | 69083.89 | 1006999.74 | 24-FEB-19:02 | 179153.81 | 878222.57 | 11-FEB-10:02 |
March | 103318.12 | 1115196.33 | 23-MAR-13:32 | 17456.60 | 814262.15 | 08-MAR-03:20 |
April | 189422.26 | 2508654.79 | 18-APR-09:20 | 10974.05 | 760177.81 | 21-APR-16:11 |
May | 192958.06 | 2533250.25 | 30-MAY-14:05 | 219451.16 | 990007.34 | 19-MAY-19:35 |
June | 633333.46 | 3582745.10 | 30-JUN-04:14 | 54308.92 | 948925.92 | 05-JUN-07:55 |
July | 842719.57 | 3525966.26 | 27-JUL-04:14 | 13396.54 | 521685.60 | 27-JUL-21:04 |
August | 883728.97 | 4143317.39 | 03-AUG-05:03 | 7909.91 | 486574.19 | 01-AUG-04:47 |
September | 300200.79 | 2668633.37 | 07-SEP-12:05 | 245613.49 | 989936.58 | 03-SEP-06:30 |
October | 97908.14 | 1542457.23 | 20-OCT-13:00 | 200567.06 | 946547.60 | 11-OCT-10:13 |
November | 94824.94 | 1224521.95 | 03-NOV-11:15 | 7993.43 | 795591.49 | 01-NOV-04:11 |
December | 106771.77 | 883464.89 | 05-DEC-13:38 | 6266.82 | 686295.36 | 01-DEC-16:33 |
Annual Sum or Average | 294706.76 | 89702.07 | ||||
Minimum of Months | 1633.21 | 93930.42 | 6266.82 | 486574.19 | ||
Maximum of Months | 883728.97 | 4143317.39 | 245613.49 | 990083.28 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16.43 | 33766.92 | 17-JAN-06:01 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 75611.05 | 381934.94 | 10-FEB-15:46 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 174412.00 | 1215698.81 | 23-MAR-14:02 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 289211.58 | 3516114.63 | 16-APR-16:21 | 0.00 | 0.00 | 01-APR-00:03 |
May | 216149.69 | 2668505.21 | 12-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 660012.06 | 5526759.29 | 30-JUN-04:11 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 880525.14 | 5383535.62 | 15-JUL-04:11 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 925329.86 | 4897302.16 | 03-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 316793.62 | 4261817.37 | 11-SEP-04:11 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 120833.24 | 1559126.99 | 20-OCT-13:00 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 199365.22 | 1368941.36 | 03-NOV-13:38 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 220497.65 | 557086.98 | 09-DEC-06:01 | 0.00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 341778.82 | 0.00 | ||||
Minimum of Months | 16.43 | 33766.92 | 0.00 | 0.00 | ||
Maximum of Months | 925329.86 | 5526759.29 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 16465.26 | 59153.19 | 31-JAN-12:13 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 16894.76 | 59537.17 | 21-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 17777.98 | 59447.59 | 01-MAR-12:32 |
April | 0.00 | 0.00 | 01-APR-00:03 | 16020.56 | 57772.50 | 03-APR-11:58 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15596.57 | 55044.03 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14913.99 | 51404.97 | 01-JUN-11:24 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 12955.52 | 48011.55 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 13823.67 | 46092.31 | 01-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 13127.28 | 47180.36 | 29-SEP-11:42 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 13755.39 | 50236.14 | 31-OCT-11:27 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14898.82 | 53759.55 | 30-NOV-12:45 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 15304.54 | 56889.92 | 29-DEC-12:13 |
Annual Sum or Average | 0.00 | 15117.59 | ||||
Minimum of Months | 0.00 | 0.00 | 12955.52 | 46092.31 | ||
Maximum of Months | 0.00 | 0.00 | 17777.98 | 59537.17 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 210.60 | 35220.19 | 14-JAN-00:20 | 4327.11 | 196715.69 | 05-JAN-02:37 |
February | 23609.35 | 735973.34 | 15-FEB-05:55 | 224.44 | 88544.08 | 08-FEB-12:59 |
March | 57738.26 | 1132062.74 | 23-MAR-13:34 | 4967.55 | 158151.20 | 19-MAR-04:07 |
April | 201500.29 | 4899639.69 | 18-APR-15:00 | 6962.58 | 183980.89 | 08-APR-00:50 |
May | 264931.65 | 4607326.93 | 31-MAY-14:05 | 1151.21 | 153115.92 | 19-MAY-04:18 |
June | 1090518.49 | 6700354.07 | 13-JUN-15:00 | 19.66 | 31907.91 | 15-JUN-05:50 |
July | 1520822.83 | 9129450.82 | 26-JUL-15:00 | 70.49 | 42948.55 | 24-JUL-05:30 |
August | 1595140.11 | 10278537.72 | 04-AUG-13:00 | 212.28 | 64343.31 | 07-AUG-02:13 |
September | 410218.01 | 5387904.16 | 11-SEP-12:05 | 1203.76 | 175805.81 | 29-SEP-23:20 |
October | 114693.73 | 1768402.04 | 20-OCT-13:00 | 167.43 | 76074.69 | 16-OCT-06:00 |
November | 30228.53 | 1384260.22 | 03-NOV-13:40 | 7092.48 | 132003.10 | 14-NOV-23:10 |
December | 18365.93 | 769891.28 | 05-DEC-16:08 | 13436.85 | 221022.84 | 13-DEC-16:20 |
Annual Sum or Average | 447572.65 | 3339.61 | ||||
Minimum of Months | 210.60 | 35220.19 | 19.66 | 31907.91 | ||
Maximum of Months | 1595140.11 | 10278537.72 | 13436.85 | 221022.84 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.849530E+10 | 0.58 | 11715.34 | 30-JAN-06:01 | 1.31 |
February | 0.787170E+10 | 0.58 | 22232.95 | 10-FEB-06:01 | 1.71 |
March | 0.977607E+10 | 0.59 | 22232.95 | 23-MAR-05:01 | 1.71 |
April | 0.113128E+11 | 0.63 | 22232.95 | 01-APR-05:01 | 1.72 |
May | 0.123024E+11 | 0.65 | 18478.75 | 01-MAY-04:11 | 1.58 |
June | 0.156374E+11 | 0.73 | 27529.67 | 30-JUN-04:11 | 1.86 |
July | 0.176843E+11 | 0.77 | 24972.57 | 26-JUL-04:11 | 1.78 |
August | 0.196492E+11 | 0.82 | 23749.51 | 04-AUG-14:40 | 1.74 |
September | 0.133602E+11 | 0.67 | 25962.87 | 11-SEP-04:11 | 1.81 |
October | 0.109151E+11 | 0.58 | 22232.95 | 24-OCT-05:01 | 1.72 |
November | 0.965274E+10 | 0.58 | 21601.34 | 16-NOV-06:01 | 1.69 |
December | 0.903797E+10 | 0.57 | 11295.92 | 05-DEC-13:23 | 1.29 |
Annual Sum or Average | 0.145695E+12 | 0.65 | |||
Minimum of Months | 0.787170E+10 | 0.57 | 11295.92 | 1.29 | |
Maximum of Months | 0.196492E+11 | 0.82 | 27529.67 | 1.86 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.123066E+12 | 0.82 | 133008.57 | 09-JAN-05:22 | 1.42 |
February | 0.991788E+11 | 0.73 | 133008.57 | 06-FEB-05:01 | 1.42 |
March | 0.101410E+12 | 0.65 | 255468.51 | 24-MAR-05:01 | 1.87 |
April | 0.102048E+12 | 0.62 | 192180.67 | 13-APR-05:03 | 1.65 |
May | 0.117718E+12 | 0.64 | 192013.38 | 04-MAY-05:02 | 1.65 |
June | 0.142969E+12 | 0.72 | 255468.51 | 02-JUN-05:01 | 1.86 |
July | 0.145323E+12 | 0.70 | 208088.18 | 05-JUL-04:11 | 1.69 |
August | 0.153102E+12 | 0.73 | 227024.03 | 03-AUG-05:02 | 1.76 |
September | 0.123383E+12 | 0.66 | 255468.51 | 23-SEP-05:01 | 1.87 |
October | 0.955314E+11 | 0.57 | 255468.51 | 05-OCT-05:01 | 1.86 |
November | 0.984552E+11 | 0.65 | 235463.22 | 02-NOV-05:01 | 1.80 |
December | 0.108510E+12 | 0.72 | 133008.57 | 19-DEC-06:01 | 1.42 |
Annual Sum or Average | 0.141069E+13 | 0.68 | |||
Minimum of Months | 0.955314E+11 | 0.57 | 133008.57 | 1.42 | |
Maximum of Months | 0.153102E+12 | 0.82 | 255468.51 | 1.87 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.130552E+11 | 0.69 | 13022.49 | 02-JAN-04:01 | 1.11 |
February | 0.113416E+11 | 0.66 | 13022.49 | 01-FEB-04:11 | 1.12 |
March | 0.109998E+11 | 0.58 | 13022.49 | 01-MAR-05:01 | 1.12 |
April | 0.983466E+10 | 0.52 | 14474.26 | 18-APR-15:00 | 1.15 |
May | 0.100066E+11 | 0.49 | 19057.14 | 31-MAY-05:02 | 1.29 |
June | 0.119640E+11 | 0.53 | 20521.45 | 12-JUN-05:01 | 1.33 |
July | 0.120765E+11 | 0.52 | 20314.85 | 03-JUL-05:02 | 1.33 |
August | 0.123579E+11 | 0.53 | 19823.38 | 03-AUG-05:02 | 1.31 |
September | 0.998335E+10 | 0.48 | 19057.14 | 11-SEP-05:02 | 1.29 |
October | 0.914583E+10 | 0.48 | 13022.49 | 02-OCT-05:01 | 1.11 |
November | 0.110954E+11 | 0.60 | 13022.49 | 01-NOV-05:01 | 1.11 |
December | 0.127432E+11 | 0.67 | 13022.49 | 01-DEC-05:01 | 1.11 |
Annual Sum or Average | 0.134604E+12 | 0.56 | |||
Minimum of Months | 0.914583E+10 | 0.48 | 13022.49 | 1.11 | |
Maximum of Months | 0.130552E+11 | 0.69 | 20521.45 | 1.33 |
Report: FanReportMonthly
For: CAV_BAS SZVAV FAN
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.290654E+10 | 0.42 | 15902.51 | 02-JAN-06:01 | 1.88 |
February | 0.332259E+10 | 0.45 | 15902.51 | 01-FEB-07:07 | 1.90 |
March | 0.391644E+10 | 0.48 | 15902.51 | 03-MAR-06:01 | 1.89 |
April | 0.457866E+10 | 0.48 | 15902.51 | 01-APR-05:01 | 1.89 |
May | 0.606045E+10 | 0.53 | 15902.51 | 01-MAY-05:02 | 1.89 |
June | 0.619596E+10 | 0.58 | 15902.51 | 01-JUN-04:11 | 1.88 |
July | 0.717946E+10 | 0.58 | 15902.51 | 01-JUL-04:11 | 1.87 |
August | 0.907025E+10 | 0.68 | 15902.51 | 01-AUG-04:11 | 1.87 |
September | 0.853330E+10 | 0.64 | 15902.51 | 01-SEP-04:11 | 1.88 |
October | 0.808937E+10 | 0.58 | 15902.51 | 02-OCT-04:11 | 1.88 |
November | 0.598694E+10 | 0.53 | 15902.51 | 01-NOV-04:11 | 1.89 |
December | 0.308257E+10 | 0.42 | 15902.51 | 01-DEC-06:01 | 1.89 |
Annual Sum or Average | 0.689225E+11 | 0.53 | |||
Minimum of Months | 0.290654E+10 | 0.42 | 15902.51 | 1.87 | |
Maximum of Months | 0.907025E+10 | 0.68 | 15902.51 | 1.90 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SYS11 FAN
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.274029E+11 | 0.53 | 10231.07 | 01-JAN-00:02 | 0.53 |
February | 0.442613E+11 | 0.65 | 34075.71 | 01-FEB-00:03 | 0.89 |
March | 0.620295E+11 | 0.73 | 34075.71 | 01-MAR-00:01 | 0.89 |
April | 0.863382E+11 | 0.88 | 34075.71 | 01-APR-00:03 | 0.89 |
May | 0.274072E+11 | 0.53 | 34075.71 | 31-MAY-23:53 | 0.89 |
June | 0.387261E+11 | 0.60 | 34075.71 | 01-JUN-00:12 | 0.89 |
July | 0.618888E+11 | 0.73 | 34075.71 | 01-JUL-00:05 | 0.88 |
August | 0.821546E+11 | 0.84 | 34075.71 | 01-AUG-00:10 | 0.88 |
September | 0.265475E+11 | 0.53 | 34075.71 | 30-SEP-23:03 | 0.89 |
October | 0.477042E+11 | 0.65 | 34075.71 | 01-OCT-00:02 | 0.89 |
November | 0.592467E+11 | 0.72 | 34075.71 | 01-NOV-00:01 | 0.89 |
December | 0.905581E+11 | 0.89 | 34075.71 | 01-DEC-00:02 | 0.89 |
Annual Sum or Average | 0.654265E+12 | 0.69 | |||
Minimum of Months | 0.265475E+11 | 0.53 | 10231.07 | 0.53 | |
Maximum of Months | 0.905581E+11 | 0.89 | 34075.71 | 0.89 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.364211E+10 | 1.48 | 1359.81 | 01-JAN-19:27 | 1.48 |
February | 0.328965E+10 | 1.48 | 1359.81 | 04-FEB-12:51 | 1.49 |
March | 0.364211E+10 | 1.48 | 1359.81 | 01-MAR-00:36 | 1.49 |
April | 0.352462E+10 | 1.47 | 1359.81 | 02-APR-06:10 | 1.48 |
May | 0.364211E+10 | 1.47 | 1359.81 | 02-MAY-14:03 | 1.47 |
June | 0.352462E+10 | 1.47 | 1359.81 | 01-JUN-00:12 | 1.47 |
July | 0.364211E+10 | 1.47 | 1359.81 | 02-JUL-17:58 | 1.47 |
August | 0.364211E+10 | 1.47 | 1359.81 | 01-AUG-05:00 | 1.47 |
September | 0.352462E+10 | 1.47 | 1359.81 | 02-SEP-12:50 | 1.47 |
October | 0.364211E+10 | 1.47 | 1359.81 | 31-OCT-23:18 | 1.48 |
November | 0.352462E+10 | 1.48 | 1359.81 | 02-NOV-09:43 | 1.47 |
December | 0.364211E+10 | 1.48 | 1359.81 | 01-DEC-00:04 | 1.48 |
Annual Sum or Average | 0.428829E+11 | 1.47 | |||
Minimum of Months | 0.328965E+10 | 1.47 | 1359.81 | 1.47 | |
Maximum of Months | 0.364211E+10 | 1.48 | 1359.81 | 1.49 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.350442E+11 | 1.48 | 13084.00 | 03-JAN-00:23 | 1.48 |
February | 0.316528E+11 | 1.48 | 13084.00 | 07-FEB-06:14 | 1.48 |
March | 0.350442E+11 | 1.48 | 13084.00 | 21-MAR-17:41 | 1.48 |
April | 0.339137E+11 | 1.47 | 13084.00 | 01-APR-02:13 | 1.48 |
May | 0.350442E+11 | 1.47 | 13084.00 | 06-MAY-05:04 | 1.47 |
June | 0.339137E+11 | 1.47 | 13084.00 | 01-JUN-01:15 | 1.47 |
July | 0.350442E+11 | 1.47 | 13084.00 | 01-JUL-01:08 | 1.47 |
August | 0.350442E+11 | 1.47 | 13084.00 | 01-AUG-04:05 | 1.47 |
September | 0.339137E+11 | 1.47 | 13084.00 | 21-SEP-01:20 | 1.47 |
October | 0.350442E+11 | 1.47 | 13084.00 | 01-OCT-03:11 | 1.48 |
November | 0.339137E+11 | 1.48 | 13084.00 | 01-NOV-00:43 | 1.48 |
December | 0.350442E+11 | 1.48 | 13084.00 | 04-DEC-22:02 | 1.48 |
Annual Sum or Average | 0.412617E+12 | 1.47 | |||
Minimum of Months | 0.316528E+11 | 1.47 | 13084.00 | 1.47 | |
Maximum of Months | 0.350442E+11 | 1.48 | 13084.00 | 1.48 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.360801E+10 | 1.48 | 1347.08 | 02-JAN-11:03 | 1.48 |
February | 0.325885E+10 | 1.48 | 1347.08 | 01-FEB-00:11 | 1.48 |
March | 0.360801E+10 | 1.48 | 1347.08 | 01-MAR-08:39 | 1.48 |
April | 0.349162E+10 | 1.47 | 1347.08 | 01-APR-01:13 | 1.48 |
May | 0.360801E+10 | 1.47 | 1347.08 | 01-MAY-02:50 | 1.47 |
June | 0.349162E+10 | 1.47 | 1347.08 | 01-JUN-00:14 | 1.47 |
July | 0.360801E+10 | 1.47 | 1347.08 | 01-JUL-01:15 | 1.47 |
August | 0.360801E+10 | 1.47 | 1347.08 | 01-AUG-04:13 | 1.47 |
September | 0.349162E+10 | 1.47 | 1347.08 | 01-SEP-02:50 | 1.47 |
October | 0.360801E+10 | 1.47 | 1347.08 | 01-OCT-00:51 | 1.48 |
November | 0.349162E+10 | 1.48 | 1347.08 | 01-NOV-01:51 | 1.48 |
December | 0.360801E+10 | 1.48 | 1347.08 | 01-DEC-00:08 | 1.48 |
Annual Sum or Average | 0.424814E+11 | 1.47 | |||
Minimum of Months | 0.325885E+10 | 1.47 | 1347.08 | 1.47 | |
Maximum of Months | 0.360801E+10 | 1.48 | 1347.08 | 1.48 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.155670E+10 | 0.140103E+10 | 6507.74 | 09-JAN-05:21 | 5856.97 | 5856.97 | 55.16 | 28.32 |
February | 0.978374E+09 | 0.880536E+09 | 6463.18 | 07-FEB-06:01 | 5816.86 | 5816.86 | 47.95 | 28.30 |
March | 0.447945E+09 | 0.403151E+09 | 5954.41 | 01-MAR-06:01 | 5358.97 | 5358.97 | 49.07 | 26.99 |
April | 0.179880E+09 | 0.161892E+09 | 5422.51 | 03-APR-05:01 | 4880.26 | 4880.26 | 53.93 | 25.47 |
May | 31035083.40 | 27931575.06 | 3365.69 | 02-MAY-04:11 | 3029.12 | 3029.12 | 30.95 | 18.60 |
June | 10179177.79 | 9161260.01 | 3366.43 | 02-JUN-05:01 | 3029.79 | 3029.79 | 31.47 | 18.60 |
July | 1211034.98 | 1089931.48 | 187.71 | 24-JUL-05:01 | 168.94 | 168.94 | 20.30 | 1.10 |
August | 3740351.52 | 3366316.37 | 352.10 | 07-AUG-05:02 | 316.89 | 316.89 | 22.26 | 2.09 |
September | 50359362.30 | 45323426.07 | 4130.60 | 30-SEP-05:01 | 3717.54 | 3717.54 | 44.90 | 21.45 |
October | 0.152173E+09 | 0.136956E+09 | 4182.09 | 23-OCT-05:01 | 3763.88 | 3763.88 | 44.45 | 21.63 |
November | 0.543483E+09 | 0.489135E+09 | 6453.39 | 20-NOV-06:01 | 5808.05 | 5808.05 | 46.02 | 28.30 |
December | 0.102887E+10 | 0.925981E+09 | 6382.70 | 18-DEC-05:02 | 5744.43 | 5744.43 | 52.67 | 28.04 |
Annual Sum or Average | 0.498395E+10 | 0.448556E+10 | ||||||
Minimum of Months | 1211034.98 | 1089931.48 | 187.71 | 168.94 | 168.94 | 20.30 | 1.10 | |
Maximum of Months | 0.155670E+10 | 0.140103E+10 | 6507.74 | 5856.97 | 5856.97 | 55.16 | 28.32 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1282061.06 | 1153854.95 | 580.86 | 02-JAN-06:01 | 522.78 | 522.78 | 6.70 | 5.01 |
February | 0.139359E+10 | 0.125423E+10 | 2380.22 | 25-FEB-06:02 | 2142.20 | 2142.20 | 7.94 | 21.25 |
March | 0.259852E+10 | 0.233867E+10 | 4183.24 | 24-MAR-13:12 | 3764.92 | 3764.92 | 9.76 | 37.22 |
April | 0.308316E+10 | 0.277485E+10 | 14627.14 | 16-APR-16:21 | 13164.42 | 13164.42 | 9.10 | 96.87 |
May | 0.174028E+10 | 0.156626E+10 | 13035.50 | 31-MAY-05:02 | 11731.95 | 11731.95 | 9.42 | 90.48 |
June | 0.515959E+10 | 0.464363E+10 | 27182.16 | 29-JUN-05:01 | 24463.95 | 24463.95 | 9.90 | 133.45 |
July | 0.674305E+10 | 0.606874E+10 | 27320.02 | 26-JUL-04:11 | 24588.01 | 24588.01 | 10.48 | 133.76 |
August | 0.733352E+10 | 0.660017E+10 | 26324.52 | 03-AUG-05:02 | 23692.07 | 23692.07 | 8.22 | 131.47 |
September | 0.246054E+10 | 0.221449E+10 | 21545.23 | 11-SEP-05:02 | 19390.71 | 19390.71 | 10.01 | 119.27 |
October | 0.196402E+10 | 0.176761E+10 | 6446.90 | 20-OCT-13:08 | 5802.21 | 5802.21 | 6.73 | 54.79 |
November | 0.261999E+10 | 0.235799E+10 | 6556.92 | 03-NOV-11:12 | 5901.23 | 5901.23 | 9.82 | 55.55 |
December | 0.283995E+10 | 0.255595E+10 | 2380.44 | 01-DEC-15:48 | 2142.39 | 2142.39 | 10.06 | 21.25 |
Annual Sum or Average | 0.379375E+11 | 0.341437E+11 | ||||||
Minimum of Months | 1282061.06 | 1153854.95 | 580.86 | 522.78 | 522.78 | 6.70 | 5.01 | |
Maximum of Months | 0.733352E+10 | 0.660017E+10 | 27320.02 | 24588.01 | 24588.01 | 10.48 | 133.76 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.482147E+10 | 0.433933E+10 | 12898.32 | 01-JAN-00:03 | 11608.49 | 11608.49 | 6.73 | 67.80 |
February | 0.964189E+10 | 0.867770E+10 | 12898.32 | 01-FEB-00:03 | 11608.49 | 11608.49 | 6.84 | 67.80 |
March | 0.262159E+11 | 0.235943E+11 | 12898.32 | 01-MAR-00:03 | 11608.49 | 11608.49 | 7.72 | 67.80 |
April | 0.276679E+11 | 0.249011E+11 | 12898.32 | 01-APR-00:03 | 11608.49 | 11608.49 | 10.33 | 67.80 |
May | 0.140982E+11 | 0.126884E+11 | 12898.32 | 01-MAY-04:14 | 11608.49 | 11608.49 | 9.81 | 67.80 |
June | 0.227881E+11 | 0.205093E+11 | 12898.32 | 01-JUN-00:15 | 11608.49 | 11608.49 | 9.02 | 67.80 |
July | 0.305382E+11 | 0.274844E+11 | 12898.32 | 01-JUL-00:11 | 11608.49 | 11608.49 | 9.82 | 67.80 |
August | 0.321565E+11 | 0.289408E+11 | 12898.32 | 01-AUG-00:10 | 11608.49 | 11608.49 | 10.21 | 67.80 |
September | 0.144757E+11 | 0.130281E+11 | 12898.32 | 01-SEP-00:10 | 11608.49 | 11608.49 | 7.95 | 67.80 |
October | 0.114092E+11 | 0.102683E+11 | 12898.32 | 01-OCT-00:04 | 11608.49 | 11608.49 | 7.66 | 67.80 |
November | 0.302792E+11 | 0.272513E+11 | 12898.32 | 01-NOV-00:03 | 11608.49 | 11608.49 | 7.69 | 67.80 |
December | 0.301693E+11 | 0.271523E+11 | 12898.32 | 01-DEC-00:01 | 11608.49 | 11608.49 | 10.21 | 67.80 |
Annual Sum or Average | 0.254262E+12 | 0.228835E+12 | ||||||
Minimum of Months | 0.482147E+10 | 0.433933E+10 | 12898.32 | 11608.49 | 11608.49 | 6.73 | 67.80 | |
Maximum of Months | 0.321565E+11 | 0.289408E+11 | 12898.32 | 11608.49 | 11608.49 | 10.33 | 67.80 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 6.72 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 6.73 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 7.59 | 0.00 |
April | 0.421775E+09 | 0.379598E+09 | 12898.32 | 14-APR-14:30 | 11608.49 | 11608.49 | 13.31 | 33.90 |
May | 0.406297E+09 | 0.365667E+09 | 12898.32 | 30-MAY-10:40 | 11608.49 | 11608.49 | 13.15 | 33.90 |
June | 0.326680E+10 | 0.294012E+10 | 12898.32 | 09-JUN-10:00 | 11608.49 | 11608.49 | 13.24 | 33.90 |
July | 0.611469E+10 | 0.550322E+10 | 12898.32 | 03-JUL-07:40 | 11608.49 | 11608.49 | 13.44 | 33.90 |
August | 0.676517E+10 | 0.608865E+10 | 12898.32 | 01-AUG-07:15 | 11608.49 | 11608.49 | 13.30 | 33.90 |
September | 0.114537E+10 | 0.103083E+10 | 12898.32 | 01-SEP-14:05 | 11608.49 | 11608.49 | 10.25 | 67.80 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 7.57 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 7.66 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 10.21 | 0.00 |
Annual Sum or Average | 0.181201E+11 | 0.163081E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 0.00 | |
Maximum of Months | 0.676517E+10 | 0.608865E+10 | 12898.32 | 11608.49 | 11608.49 | 13.44 | 67.80 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 56.83 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 56.81 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 56.80 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:01 | 16.86 | 16.86 | 56.81 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 57.06 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:01 | 16.86 | 16.86 | 57.21 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:01 | 16.86 | 16.86 | 57.41 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 57.40 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:01 | 16.86 | 16.86 | 57.49 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:05 | 16.86 | 16.86 | 57.07 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 57.30 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 57.01 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.80 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.49 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.123961E+11 | 0.111565E+11 | 33196.82 | 14-JAN-00:20 | 29877.14 | 29877.14 | 21.19 | 95.55 |
February | 0.247636E+11 | 0.222872E+11 | 33238.73 | 15-FEB-05:55 | 29914.86 | 29914.86 | 22.94 | 95.55 |
March | 0.674212E+11 | 0.606791E+11 | 33262.46 | 23-MAR-13:34 | 29936.21 | 29936.21 | 23.93 | 95.55 |
April | 0.720117E+11 | 0.648106E+11 | 66701.05 | 18-APR-15:00 | 60030.95 | 60030.95 | 27.23 | 191.09 |
May | 0.368837E+11 | 0.331953E+11 | 66680.58 | 31-MAY-14:05 | 60012.52 | 60012.52 | 26.87 | 191.09 |
June | 0.651331E+11 | 0.586198E+11 | 66824.94 | 13-JUN-14:30 | 60142.44 | 60142.44 | 29.45 | 191.09 |
July | 0.910804E+11 | 0.819723E+11 | 66824.94 | 03-JUL-12:10 | 60142.44 | 60142.44 | 29.49 | 191.09 |
August | 0.976499E+11 | 0.878849E+11 | 66824.94 | 02-AUG-15:40 | 60142.44 | 60142.44 | 29.45 | 191.09 |
September | 0.396692E+11 | 0.357023E+11 | 66735.27 | 11-SEP-12:05 | 60061.74 | 60061.74 | 27.85 | 191.09 |
October | 0.293658E+11 | 0.264292E+11 | 33302.74 | 20-OCT-13:00 | 29972.46 | 29972.46 | 25.53 | 95.55 |
November | 0.777628E+11 | 0.699865E+11 | 33277.58 | 03-NOV-13:40 | 29949.82 | 29949.82 | 24.57 | 95.55 |
December | 0.775406E+11 | 0.697865E+11 | 33240.76 | 05-DEC-16:08 | 29916.69 | 29916.69 | 23.03 | 95.55 |
Annual Sum or Average | 0.691678E+12 | 0.622510E+12 | ||||||
Minimum of Months | 0.123961E+11 | 0.111565E+11 | 33196.82 | 29877.14 | 29877.14 | 21.19 | 95.55 | |
Maximum of Months | 0.976499E+11 | 0.878849E+11 | 66824.94 | 60142.44 | 60142.44 | 29.49 | 191.09 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 30.87 | 30.87 | 564661.18 | 4543504.69 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 36.87 | 82.20 | 388960.08 | 3940492.96 | 21-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 35.23 | 35.23 | 182799.26 | 3505456.42 | 25-MAR-04:01 |
April | 0.00 | 0.00 | 01-APR-00:03 | 24.16 | 24.16 | 75772.34 | 3657453.71 | 01-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.75 | 20.75 | 11914.64 | 3267873.93 | 02-MAY-04:11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.20 | 20.20 | 4097.77 | 2871209.72 | 02-JUN-05:01 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 20.25 | 20.25 | 497.14 | 208703.21 | 24-JUL-05:01 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.44 | 20.44 | 1517.78 | 388786.70 | 07-AUG-05:02 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.88 | 19.88 | 20020.19 | 3359021.90 | 30-SEP-04:01 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 22.17 | 22.17 | 58022.95 | 3615852.69 | 16-OCT-04:11 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 25.08 | 25.08 | 217025.88 | 3718956.36 | 28-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 28.90 | 28.90 | 401527.92 | 3831784.04 | 18-DEC-05:01 |
Annual Sum or Average | 0.00 | 159582.29 | ||||||
Minimum of Months | 0.00 | 0.00 | 19.88 | 19.88 | 497.14 | 208703.21 | ||
Maximum of Months | 0.00 | 0.00 | 36.87 | 82.20 | 564661.18 | 4543504.69 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1633.21 | 93930.42 | 13-JAN-22:03 | 7.03 | 6.70 | 120702.01 | 990083.28 | 08-JAN-01:51 |
February | 69083.89 | 1006999.74 | 24-FEB-19:02 | 10.24 | 6.70 | 179153.81 | 878222.57 | 11-FEB-10:02 |
March | 103318.12 | 1115196.33 | 23-MAR-13:32 | 10.63 | 6.70 | 17456.60 | 814262.15 | 08-MAR-03:20 |
April | 189422.26 | 2508654.79 | 18-APR-09:20 | 11.23 | 6.82 | 10974.05 | 760177.81 | 21-APR-16:11 |
May | 192958.06 | 2533250.25 | 30-MAY-14:05 | 11.16 | 6.70 | 219451.16 | 990007.34 | 19-MAY-19:35 |
June | 633333.46 | 3582745.10 | 30-JUN-04:14 | 13.01 | 6.70 | 54308.92 | 948925.92 | 05-JUN-07:55 |
July | 842719.57 | 3525966.26 | 27-JUL-04:14 | 12.91 | 6.70 | 13396.54 | 521685.60 | 27-JUL-21:04 |
August | 883728.97 | 4143317.39 | 03-AUG-05:03 | 14.00 | 7.25 | 7909.91 | 486574.19 | 01-AUG-04:47 |
September | 300200.79 | 2668633.37 | 07-SEP-12:05 | 11.40 | 6.70 | 245613.49 | 989936.58 | 03-SEP-06:30 |
October | 97908.14 | 1542457.23 | 20-OCT-13:00 | 12.13 | 6.70 | 200567.06 | 946547.60 | 11-OCT-10:13 |
November | 94824.94 | 1224521.95 | 03-NOV-11:15 | 11.12 | 6.81 | 7993.43 | 795591.49 | 01-NOV-04:11 |
December | 106771.77 | 883464.89 | 05-DEC-13:38 | 9.81 | 6.70 | 6266.82 | 686295.36 | 01-DEC-16:33 |
Annual Sum or Average | 294706.76 | 89702.07 | ||||||
Minimum of Months | 1633.21 | 93930.42 | 7.03 | 6.70 | 6266.82 | 486574.19 | ||
Maximum of Months | 883728.97 | 4143317.39 | 14.00 | 7.25 | 245613.49 | 990083.28 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16.43 | 33766.92 | 17-JAN-06:01 | 8.34 | 6.74 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 75611.05 | 381934.94 | 10-FEB-15:46 | 12.28 | 9.74 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 174412.00 | 1215698.81 | 23-MAR-14:02 | 14.91 | 7.80 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 289211.58 | 3516114.63 | 16-APR-16:21 | 15.37 | 10.90 | 0.00 | 0.00 | 01-APR-00:03 |
May | 216149.69 | 2668505.21 | 12-MAY-05:02 | 14.00 | 9.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 660012.06 | 5526759.29 | 30-JUN-04:11 | 17.23 | 12.65 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 880525.14 | 5383535.62 | 15-JUL-04:11 | 17.33 | 13.05 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 925329.86 | 4897302.16 | 03-AUG-05:02 | 15.60 | 7.91 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 316793.62 | 4261817.37 | 11-SEP-04:11 | 16.43 | 10.82 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 120833.24 | 1559126.99 | 20-OCT-13:00 | 13.58 | 6.70 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 199365.22 | 1368941.36 | 03-NOV-13:38 | 15.24 | 6.90 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 220497.65 | 557086.98 | 09-DEC-06:01 | 12.96 | 9.75 | 0.00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 341778.82 | 0.00 | ||||||
Minimum of Months | 16.43 | 33766.92 | 8.34 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 925329.86 | 5526759.29 | 17.33 | 13.05 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 57.87 | 57.87 | 16465.26 | 59153.19 | 31-JAN-12:13 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 57.23 | 57.23 | 16894.76 | 59537.17 | 21-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 57.22 | 57.22 | 17777.98 | 59447.59 | 01-MAR-12:32 |
April | 0.00 | 0.00 | 01-APR-00:03 | 57.29 | 57.29 | 16020.56 | 57772.50 | 03-APR-11:58 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.95 | 57.95 | 15596.57 | 55044.03 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.60 | 57.60 | 14913.99 | 51404.97 | 01-JUN-11:24 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 57.75 | 57.75 | 12955.52 | 48011.55 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.85 | 57.85 | 13823.67 | 46092.31 | 01-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.87 | 57.87 | 13127.28 | 47180.36 | 29-SEP-11:42 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 57.80 | 57.80 | 13755.39 | 50236.14 | 31-OCT-11:27 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 57.66 | 57.66 | 14898.82 | 53759.55 | 30-NOV-12:45 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 57.49 | 57.49 | 15304.54 | 56889.92 | 29-DEC-12:13 |
Annual Sum or Average | 0.00 | 15117.59 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.22 | 57.22 | 12955.52 | 46092.31 | ||
Maximum of Months | 0.00 | 0.00 | 57.95 | 57.95 | 17777.98 | 59537.17 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 210.60 | 35220.19 | 14-JAN-00:20 | 21.19 | 20.36 | 4327.11 | 196715.69 | 05-JAN-02:37 |
February | 23609.35 | 735973.34 | 15-FEB-05:55 | 22.94 | 21.10 | 224.44 | 88544.08 | 08-FEB-12:59 |
March | 57738.26 | 1132062.74 | 23-MAR-13:34 | 23.93 | 21.10 | 4967.55 | 158151.20 | 19-MAR-04:07 |
April | 201500.29 | 4899639.69 | 18-APR-15:00 | 27.23 | 23.82 | 6962.58 | 183980.89 | 08-APR-00:50 |
May | 264931.65 | 4607326.93 | 31-MAY-14:05 | 26.87 | 23.14 | 1151.21 | 153115.92 | 19-MAY-04:18 |
June | 1090518.49 | 6700354.07 | 13-JUN-15:00 | 29.49 | 26.09 | 19.66 | 31907.91 | 15-JUN-05:50 |
July | 1520822.83 | 9129450.82 | 26-JUL-15:00 | 32.53 | 28.51 | 70.49 | 42948.55 | 24-JUL-05:30 |
August | 1595140.11 | 10278537.72 | 04-AUG-13:00 | 33.97 | 29.50 | 212.28 | 64343.31 | 07-AUG-02:13 |
September | 410218.01 | 5387904.16 | 11-SEP-12:05 | 27.85 | 24.19 | 1203.76 | 175805.81 | 29-SEP-23:20 |
October | 114693.73 | 1768402.04 | 20-OCT-13:00 | 25.53 | 21.10 | 167.43 | 76074.69 | 16-OCT-06:00 |
November | 30228.53 | 1384260.22 | 03-NOV-13:40 | 24.57 | 21.10 | 7092.48 | 132003.10 | 14-NOV-23:10 |
December | 18365.93 | 769891.28 | 05-DEC-16:08 | 23.03 | 21.10 | 13436.85 | 221022.84 | 13-DEC-16:20 |
Annual Sum or Average | 447572.65 | 3339.61 | ||||||
Minimum of Months | 210.60 | 35220.19 | 21.19 | 20.36 | 19.66 | 31907.91 | ||
Maximum of Months | 1595140.11 | 10278537.72 | 33.97 | 29.50 | 13436.85 | 221022.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.807231E+11 | 0.00 | 3659.99 | 0.849530E+10 | 0.00 | 0.00 |
February | 0.471380E+11 | 0.00 | 183693.85 | 0.787170E+10 | 0.00 | 0.00 |
March | 0.168759E+11 | 0.00 | 0.883886E+09 | 0.977607E+10 | 0.00 | 0.00 |
April | 0.476448E+10 | 0.00 | 0.164551E+11 | 0.113128E+11 | 0.00 | 0.00 |
May | 0.258618E+09 | 0.00 | 0.369068E+11 | 0.123024E+11 | 0.00 | 0.00 |
June | 59067803.16 | 0.00 | 0.103571E+12 | 0.156374E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.150557E+12 | 0.176843E+11 | 0.00 | 0.00 |
August | 89810.16 | 0.00 | 0.151392E+12 | 0.196492E+11 | 0.00 | 0.00 |
September | 0.785727E+09 | 0.00 | 0.575551E+11 | 0.133602E+11 | 0.00 | 0.00 |
October | 0.276134E+10 | 0.00 | 0.518290E+10 | 0.109151E+11 | 0.00 | 0.00 |
November | 0.185197E+11 | 0.00 | 0.335923E+09 | 0.965274E+10 | 0.00 | 0.00 |
December | 0.431312E+11 | 0.00 | 166115.13 | 0.903797E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.215017E+12 | 0.00 | 0.522840E+12 | 0.145695E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 3659.99 | 0.787170E+10 | 0.00 | 0.00 |
Maximum of Months | 0.807231E+11 | 0.00 | 0.151392E+12 | 0.196492E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.124435E+13 | 0.00 | 127639.66 | 0.123066E+12 | 0.00 | 0.00 |
February | 0.762966E+12 | 0.00 | 554628.57 | 0.991788E+11 | 0.00 | 0.00 |
March | 0.403487E+12 | 0.00 | 0.136351E+11 | 0.101410E+12 | 0.00 | 0.00 |
April | 0.158266E+12 | 0.00 | 0.147229E+12 | 0.102048E+12 | 0.00 | 0.00 |
May | 0.234976E+11 | 0.00 | 0.357255E+12 | 0.117718E+12 | 0.00 | 0.00 |
June | 0.725175E+10 | 0.00 | 0.953554E+12 | 0.142969E+12 | 0.00 | 0.00 |
July | 0.411828E+09 | 0.00 | 0.128437E+13 | 0.145323E+12 | 0.00 | 0.00 |
August | 0.211711E+10 | 0.00 | 0.124624E+13 | 0.153102E+12 | 0.00 | 0.00 |
September | 0.391353E+11 | 0.00 | 0.525828E+12 | 0.123383E+12 | 0.00 | 0.00 |
October | 0.120429E+12 | 0.00 | 0.600434E+11 | 0.955314E+11 | 0.00 | 0.00 |
November | 0.461176E+12 | 0.00 | 0.627949E+10 | 0.984552E+11 | 0.00 | 0.00 |
December | 0.890571E+12 | 0.00 | 114693.28 | 0.108510E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.411366E+13 | 0.00 | 0.459444E+13 | 0.141069E+13 | 0.00 | 0.00 |
Minimum of Months | 0.411828E+09 | 0.00 | 114693.28 | 0.955314E+11 | 0.00 | 0.00 |
Maximum of Months | 0.124435E+13 | 0.00 | 0.128437E+13 | 0.153102E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.189039E+12 | 0.00 | 3783396.36 | 0.130552E+11 | 0.00 | 0.00 |
February | 0.124228E+12 | 0.00 | 3968659.65 | 0.113416E+11 | 0.00 | 0.00 |
March | 0.720657E+11 | 0.00 | 0.633974E+09 | 0.109998E+11 | 0.00 | 0.00 |
April | 0.344113E+11 | 0.00 | 0.160024E+11 | 0.983466E+10 | 0.00 | 0.00 |
May | 0.827739E+10 | 0.00 | 0.391425E+11 | 0.100066E+11 | 0.00 | 0.00 |
June | 0.334330E+10 | 0.00 | 0.108946E+12 | 0.119640E+11 | 0.00 | 0.00 |
July | 0.921463E+09 | 0.00 | 0.144089E+12 | 0.120765E+11 | 0.00 | 0.00 |
August | 0.196466E+10 | 0.00 | 0.137558E+12 | 0.123579E+11 | 0.00 | 0.00 |
September | 0.121370E+11 | 0.00 | 0.565082E+11 | 0.998335E+10 | 0.00 | 0.00 |
October | 0.327306E+11 | 0.00 | 0.432015E+10 | 0.914583E+10 | 0.00 | 0.00 |
November | 0.858294E+11 | 0.00 | 0.146621E+09 | 0.110954E+11 | 0.00 | 0.00 |
December | 0.147365E+12 | 0.00 | 13278601.60 | 0.127432E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.712313E+12 | 0.00 | 0.507367E+12 | 0.134604E+12 | 0.00 | 0.00 |
Minimum of Months | 0.921463E+09 | 0.00 | 3783396.36 | 0.914583E+10 | 0.00 | 0.00 |
Maximum of Months | 0.189039E+12 | 0.00 | 0.144089E+12 | 0.130552E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.703058E+10 | 0.00 | 91396726.16 | 0.290654E+10 | 0.00 | 0.00 |
February | 0.119773E+11 | 0.00 | 0.141126E+09 | 0.332259E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.159179E+10 | 0.391644E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.839460E+10 | 0.457866E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.265414E+11 | 0.606045E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.584613E+11 | 0.619596E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.797603E+11 | 0.717946E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.866746E+11 | 0.907025E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.406882E+11 | 0.853330E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.130509E+11 | 0.808937E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.524580E+10 | 0.598694E+10 | 0.00 | 0.00 |
December | 0.550974E+09 | 0.00 | 0.626302E+09 | 0.308257E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.195589E+11 | 0.00 | 0.321268E+12 | 0.689225E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 91396726.16 | 0.290654E+10 | 0.00 | 0.00 |
Maximum of Months | 0.119773E+11 | 0.00 | 0.866746E+11 | 0.907025E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 3673730.69 | 0.123068E+12 | 0.00 | 35.59 |
February | 0.00 | 0.00 | 0.157489E+12 | 0.145409E+12 | 0.00 | 37.63 |
March | 0.00 | 0.00 | 0.234796E+12 | 0.217513E+12 | 0.00 | 57.84 |
April | 0.00 | 0.00 | 0.266969E+12 | 0.242152E+12 | 0.00 | 57.96 |
May | 0.00 | 0.00 | 0.257935E+11 | 0.574857E+11 | 0.00 | 11.19 |
June | 0.00 | 0.00 | 0.332473E+12 | 0.398829E+11 | 0.00 | 0.43 |
July | 0.00 | 0.00 | 0.466481E+12 | 0.622950E+11 | 0.00 | 0.15 |
August | 0.00 | 0.00 | 0.610095E+12 | 0.860279E+11 | 0.00 | 1.44 |
September | 0.00 | 0.00 | 0.564076E+11 | 0.599164E+11 | 0.00 | 12.41 |
October | 0.00 | 0.00 | 0.168013E+12 | 0.135730E+12 | 0.00 | 32.75 |
November | 0.00 | 0.00 | 0.204747E+12 | 0.202165E+12 | 0.00 | 53.17 |
December | 0.00 | 0.00 | 0.255899E+12 | 0.335690E+12 | 0.00 | 91.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.277917E+13 | 0.170733E+13 | 0.00 | 391.74 |
Minimum of Months | 0.00 | 0.00 | 3673730.69 | 0.398829E+11 | 0.00 | 0.15 |
Maximum of Months | 0.00 | 0.00 | 0.610095E+12 | 0.335690E+12 | 0.00 | 91.19 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.472813E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.549815E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.783112E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.902725E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.591839E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.716869E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.859883E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.998584E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.580835E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.693319E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.755421E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.873771E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.877899E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.472813E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.998584E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.388223E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.464952E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.668952E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.768876E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.522615E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.632210E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.751773E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.860498E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.509046E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.595022E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.635783E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.721297E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.751925E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.388223E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.860498E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.381980E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.455834E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.693969E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.819256E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.541128E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.684934E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.828150E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.945823E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.522229E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.596579E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.650610E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.751598E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.787209E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.381980E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.945823E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.849530E+10 | 3659.99 | 0.807231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.787170E+10 | 183693.85 | 0.471380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.977607E+10 | 0.883886E+09 | 0.168759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113128E+11 | 0.164551E+11 | 0.476448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.123024E+11 | 0.369068E+11 | 0.258618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156374E+11 | 0.103571E+12 | 59067803.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176843E+11 | 0.150557E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196492E+11 | 0.151392E+12 | 89810.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133602E+11 | 0.575551E+11 | 0.785727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109151E+11 | 0.518290E+10 | 0.276134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.965274E+10 | 0.335923E+09 | 0.185197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.903797E+10 | 166115.13 | 0.431312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145695E+12 | 0.522840E+12 | 0.215017E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.787170E+10 | 3659.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196492E+11 | 0.151392E+12 | 0.807231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.123066E+12 | 127639.66 | 0.124435E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.991788E+11 | 554628.57 | 0.762966E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101410E+12 | 0.136351E+11 | 0.403487E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102048E+12 | 0.147229E+12 | 0.158266E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117718E+12 | 0.357255E+12 | 0.234976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142969E+12 | 0.953554E+12 | 0.725175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145323E+12 | 0.128437E+13 | 0.411828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153102E+12 | 0.124624E+13 | 0.211711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.123383E+12 | 0.525828E+12 | 0.391353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.955314E+11 | 0.600434E+11 | 0.120429E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.984552E+11 | 0.627949E+10 | 0.461176E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108510E+12 | 114693.28 | 0.890571E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141069E+13 | 0.459444E+13 | 0.411366E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.955314E+11 | 114693.28 | 0.411828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153102E+12 | 0.128437E+13 | 0.124435E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.130552E+11 | 3783396.36 | 0.189039E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113416E+11 | 3968659.65 | 0.124228E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109998E+11 | 0.633974E+09 | 0.720657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.983466E+10 | 0.160024E+11 | 0.344113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100066E+11 | 0.391425E+11 | 0.827739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119640E+11 | 0.108946E+12 | 0.334330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120765E+11 | 0.144089E+12 | 0.921463E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123579E+11 | 0.137558E+12 | 0.196466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.998335E+10 | 0.565082E+11 | 0.121370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.914583E+10 | 0.432015E+10 | 0.327306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110954E+11 | 0.146621E+09 | 0.858294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127432E+11 | 13278601.60 | 0.147365E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134604E+12 | 0.507367E+12 | 0.712313E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.914583E+10 | 3783396.36 | 0.921463E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130552E+11 | 0.144089E+12 | 0.189039E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.290654E+10 | 91396726.16 | 0.703058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.332259E+10 | 0.141126E+09 | 0.119773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.391644E+10 | 0.159179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.457866E+10 | 0.839460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.606045E+10 | 0.265414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.619596E+10 | 0.584613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.717946E+10 | 0.797603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.907025E+10 | 0.866746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.853330E+10 | 0.406882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.808937E+10 | 0.130509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.598694E+10 | 0.524580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.308257E+10 | 0.626302E+09 | 0.550974E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.689225E+11 | 0.321268E+12 | 0.195589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.290654E+10 | 91396726.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.907025E+10 | 0.866746E+11 | 0.119773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.274029E+11 | 3673730.69 | 0.00 | 0.00 | 0.00 | 0.952365E+11 | 0.00 | 0.00 |
February | 0.442613E+11 | 0.157489E+12 | 0.00 | 0.00 | 0.00 | 0.100694E+12 | 0.00 | 0.00 |
March | 0.620295E+11 | 0.234796E+12 | 0.00 | 0.00 | 0.00 | 0.154787E+12 | 0.00 | 0.00 |
April | 0.863382E+11 | 0.266969E+12 | 0.00 | 0.00 | 0.00 | 0.155116E+12 | 0.00 | 0.00 |
May | 0.274072E+11 | 0.257935E+11 | 0.00 | 0.00 | 0.00 | 0.299437E+11 | 0.00 | 0.00 |
June | 0.387261E+11 | 0.332473E+12 | 0.00 | 0.00 | 0.00 | 0.115161E+10 | 0.00 | 0.00 |
July | 0.618888E+11 | 0.466481E+12 | 0.00 | 0.00 | 0.00 | 0.404367E+09 | 0.00 | 0.00 |
August | 0.821546E+11 | 0.610095E+12 | 0.00 | 0.00 | 0.00 | 0.385596E+10 | 0.00 | 0.00 |
September | 0.265475E+11 | 0.564076E+11 | 0.00 | 0.00 | 0.00 | 0.332193E+11 | 0.00 | 0.00 |
October | 0.477042E+11 | 0.168013E+12 | 0.00 | 0.00 | 0.00 | 0.876316E+11 | 0.00 | 0.00 |
November | 0.592467E+11 | 0.204747E+12 | 0.00 | 0.00 | 0.00 | 0.142277E+12 | 0.00 | 0.00 |
December | 0.905581E+11 | 0.255899E+12 | 0.00 | 0.00 | 0.00 | 0.244033E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.654265E+12 | 0.277917E+13 | 0.00 | 0.00 | 0.00 | 0.104835E+13 | 0.00 | 0.00 |
Minimum of Months | 0.265475E+11 | 3673730.69 | 0.00 | 0.00 | 0.00 | 0.404367E+09 | 0.00 | 0.00 |
Maximum of Months | 0.905581E+11 | 0.610095E+12 | 0.00 | 0.00 | 0.00 | 0.244033E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.364211E+10 | 0.344206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.328965E+10 | 0.766102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.364211E+10 | 0.158367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.352462E+10 | 0.211777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.364211E+10 | 0.754346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.352462E+10 | 0.128432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364211E+10 | 0.187805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.364211E+10 | 0.237950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.352462E+10 | 0.751511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.364211E+10 | 0.116843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.352462E+10 | 0.152345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364211E+10 | 0.198902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.428829E+11 | 0.165404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.328965E+10 | 0.344206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.364211E+10 | 0.237950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.350442E+11 | 0.137109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.316528E+11 | 0.584684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.350442E+11 | 0.137715E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.339137E+11 | 0.193661E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.350442E+11 | 0.659448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.339137E+11 | 0.119865E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.350442E+11 | 0.176618E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.350442E+11 | 0.223708E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.339137E+11 | 0.644457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.350442E+11 | 0.994194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.339137E+11 | 0.127347E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.350442E+11 | 0.167225E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.412617E+12 | 0.144813E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.316528E+11 | 0.137109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.350442E+11 | 0.223708E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.360801E+10 | 0.655072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.325885E+10 | 0.429078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.360801E+10 | 0.120082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.349162E+10 | 0.180343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.360801E+10 | 0.586428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.349162E+10 | 0.116630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.360801E+10 | 0.174722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.360801E+10 | 0.220767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.349162E+10 | 0.555530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.360801E+10 | 0.798918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.349162E+10 | 0.107505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.360801E+10 | 0.146601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.424814E+11 | 0.131020E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.325885E+10 | 0.655072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.360801E+10 | 0.220767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.849530E+10 | 0.807231E+11 | 3659.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.787170E+10 | 0.471380E+11 | 183693.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.977607E+10 | 0.168759E+11 | 0.883886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113128E+11 | 0.476448E+10 | 0.164551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.123024E+11 | 0.258618E+09 | 0.369068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156374E+11 | 59067803.16 | 0.103571E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176843E+11 | 0.00 | 0.150557E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196492E+11 | 89810.16 | 0.151392E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133602E+11 | 0.785727E+09 | 0.575551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109151E+11 | 0.276134E+10 | 0.518290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.965274E+10 | 0.185197E+11 | 0.335923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.903797E+10 | 0.431312E+11 | 166115.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145695E+12 | 0.215017E+12 | 0.522840E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.787170E+10 | 0.00 | 3659.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196492E+11 | 0.807231E+11 | 0.151392E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.123066E+12 | 0.124435E+13 | 127639.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.991788E+11 | 0.762966E+12 | 554628.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101410E+12 | 0.403487E+12 | 0.136351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102048E+12 | 0.158266E+12 | 0.147229E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117718E+12 | 0.234976E+11 | 0.357255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142969E+12 | 0.725175E+10 | 0.953554E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145323E+12 | 0.411828E+09 | 0.128437E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153102E+12 | 0.211711E+10 | 0.124624E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.123383E+12 | 0.391353E+11 | 0.525828E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.955314E+11 | 0.120429E+12 | 0.600434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.984552E+11 | 0.461176E+12 | 0.627949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108510E+12 | 0.890571E+12 | 114693.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141069E+13 | 0.411366E+13 | 0.459444E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.955314E+11 | 0.411828E+09 | 114693.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153102E+12 | 0.124435E+13 | 0.128437E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.130552E+11 | 0.189039E+12 | 3783396.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113416E+11 | 0.124228E+12 | 3968659.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109998E+11 | 0.720657E+11 | 0.633974E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.983466E+10 | 0.344113E+11 | 0.160024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100066E+11 | 0.827739E+10 | 0.391425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119640E+11 | 0.334330E+10 | 0.108946E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120765E+11 | 0.921463E+09 | 0.144089E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123579E+11 | 0.196466E+10 | 0.137558E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.998335E+10 | 0.121370E+11 | 0.565082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.914583E+10 | 0.327306E+11 | 0.432015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110954E+11 | 0.858294E+11 | 0.146621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127432E+11 | 0.147365E+12 | 13278601.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134604E+12 | 0.712313E+12 | 0.507367E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.914583E+10 | 0.921463E+09 | 3783396.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130552E+11 | 0.189039E+12 | 0.144089E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.290654E+10 | 0.703058E+10 | 91396726.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.332259E+10 | 0.119773E+11 | 0.141126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.391644E+10 | 0.00 | 0.159179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.457866E+10 | 0.00 | 0.839460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.606045E+10 | 0.00 | 0.265414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.619596E+10 | 0.00 | 0.584613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.717946E+10 | 0.00 | 0.797603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.907025E+10 | 0.00 | 0.866746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.853330E+10 | 0.00 | 0.406882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.808937E+10 | 0.00 | 0.130509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.598694E+10 | 0.00 | 0.524580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.308257E+10 | 0.550974E+09 | 0.626302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.689225E+11 | 0.195589E+11 | 0.321268E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.290654E+10 | 0.00 | 91396726.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.907025E+10 | 0.119773E+11 | 0.866746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.274029E+11 | 0.00 | 3673730.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.956652E+11 | 0.00 | 0.00 | 0.00 |
February | 0.442613E+11 | 0.00 | 0.157489E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101147E+12 | 0.00 | 0.00 | 0.00 |
March | 0.620295E+11 | 0.00 | 0.234796E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155483E+12 | 0.00 | 0.00 | 0.00 |
April | 0.863382E+11 | 0.00 | 0.266969E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155814E+12 | 0.00 | 0.00 | 0.00 |
May | 0.274072E+11 | 0.00 | 0.257935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300785E+11 | 0.00 | 0.00 | 0.00 |
June | 0.387261E+11 | 0.00 | 0.332473E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115680E+10 | 0.00 | 0.00 | 0.00 |
July | 0.618888E+11 | 0.00 | 0.466481E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406189E+09 | 0.00 | 0.00 | 0.00 |
August | 0.821546E+11 | 0.00 | 0.610095E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387331E+10 | 0.00 | 0.00 | 0.00 |
September | 0.265475E+11 | 0.00 | 0.564076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333688E+11 | 0.00 | 0.00 | 0.00 |
October | 0.477042E+11 | 0.00 | 0.168013E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.880261E+11 | 0.00 | 0.00 | 0.00 |
November | 0.592467E+11 | 0.00 | 0.204747E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142918E+12 | 0.00 | 0.00 | 0.00 |
December | 0.905581E+11 | 0.00 | 0.255899E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245132E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.654265E+12 | 0.00 | 0.277917E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105307E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.265475E+11 | 0.00 | 3673730.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406189E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.905581E+11 | 0.00 | 0.610095E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245132E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.364211E+10 | 0.00 | 0.00 | 0.00 | 0.108602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.328965E+10 | 0.00 | 0.00 | 0.00 | 0.220850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.364211E+10 | 0.00 | 0.00 | 0.00 | 0.418902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.352462E+10 | 0.00 | 0.00 | 0.00 | 0.550263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.364211E+10 | 0.00 | 0.00 | 0.00 | 0.227628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.352462E+10 | 0.00 | 0.00 | 0.00 | 0.364407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364211E+10 | 0.00 | 0.00 | 0.00 | 0.495672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.364211E+10 | 0.00 | 0.00 | 0.00 | 0.634373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.352462E+10 | 0.00 | 0.00 | 0.00 | 0.228373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.364211E+10 | 0.00 | 0.00 | 0.00 | 0.329108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.352462E+10 | 0.00 | 0.00 | 0.00 | 0.402959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364211E+10 | 0.00 | 0.00 | 0.00 | 0.509560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.428829E+11 | 0.00 | 0.00 | 0.00 | 0.449070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.328965E+10 | 0.00 | 0.00 | 0.00 | 0.108602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.364211E+10 | 0.00 | 0.00 | 0.00 | 0.634373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.350442E+11 | 0.00 | 0.00 | 0.00 | 0.377815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.316528E+11 | 0.00 | 0.00 | 0.00 | 0.148424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.350442E+11 | 0.00 | 0.00 | 0.00 | 0.318510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.339137E+11 | 0.00 | 0.00 | 0.00 | 0.429739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.350442E+11 | 0.00 | 0.00 | 0.00 | 0.172173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.339137E+11 | 0.00 | 0.00 | 0.00 | 0.293073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.350442E+11 | 0.00 | 0.00 | 0.00 | 0.401331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.350442E+11 | 0.00 | 0.00 | 0.00 | 0.510056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.339137E+11 | 0.00 | 0.00 | 0.00 | 0.169909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.350442E+11 | 0.00 | 0.00 | 0.00 | 0.244580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.339137E+11 | 0.00 | 0.00 | 0.00 | 0.296646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.350442E+11 | 0.00 | 0.00 | 0.00 | 0.370855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.412617E+12 | 0.00 | 0.00 | 0.00 | 0.339308E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.316528E+11 | 0.00 | 0.00 | 0.00 | 0.377815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.350442E+11 | 0.00 | 0.00 | 0.00 | 0.510056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.360801E+10 | 0.00 | 0.00 | 0.00 | 0.211784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.325885E+10 | 0.00 | 0.00 | 0.00 | 0.129949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.360801E+10 | 0.00 | 0.00 | 0.00 | 0.333168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.349162E+10 | 0.00 | 0.00 | 0.00 | 0.470094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.360801E+10 | 0.00 | 0.00 | 0.00 | 0.180327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.349162E+10 | 0.00 | 0.00 | 0.00 | 0.335772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.360801E+10 | 0.00 | 0.00 | 0.00 | 0.467349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.360801E+10 | 0.00 | 0.00 | 0.00 | 0.585022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.349162E+10 | 0.00 | 0.00 | 0.00 | 0.173066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.360801E+10 | 0.00 | 0.00 | 0.00 | 0.235778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.349162E+10 | 0.00 | 0.00 | 0.00 | 0.301448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.360801E+10 | 0.00 | 0.00 | 0.00 | 0.390797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.424814E+11 | 0.00 | 0.00 | 0.00 | 0.362395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.325885E+10 | 0.00 | 0.00 | 0.00 | 0.211784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.360801E+10 | 0.00 | 0.00 | 0.00 | 0.585022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.644703E+11 | 0.00 | 0.00 | 2976380.48 | 0.00 | 0.908775E+09 | 0.229873E+10 | 0.00 | 0.31 |
February | 0.475207E+11 | 0.00 | 0.00 | 19146338.25 | 0.00 | 0.118375E+11 | 0.223214E+10 | 0.00 | 0.32 |
March | 0.415399E+11 | 0.00 | 0.00 | 96341494.45 | 0.00 | 0.00 | 0.128116E+11 | 0.00 | 0.41 |
April | 0.171331E+11 | 0.675418E+09 | 0.00 | 93745843.78 | 10343452.91 | 0.00 | 0.270464E+11 | 0.00 | 0.48 |
May | 0.372455E+10 | 0.125194E+10 | 0.00 | 86210394.97 | 0.00 | 0.00 | 0.303377E+11 | 0.00 | 0.67 |
June | 0.209355E+10 | 0.948343E+10 | 0.00 | 0.224676E+09 | 86130630.16 | 0.00 | 0.169233E+11 | 0.00 | 0.64 |
July | 0.220228E+09 | 0.165903E+11 | 0.00 | 0.155564E+09 | 77163540.32 | 0.00 | 0.883517E+10 | 0.00 | 0.62 |
August | 0.287887E+09 | 0.160136E+11 | 0.00 | 98209784.09 | 0.109223E+09 | 0.00 | 0.146822E+11 | 0.00 | 0.76 |
September | 0.363436E+10 | 0.241947E+10 | 0.00 | 0.129019E+09 | 36399109.17 | 0.00 | 0.355248E+11 | 0.00 | 0.77 |
October | 0.139309E+11 | 0.00 | 0.00 | 0.378831E+09 | 0.00 | 0.00 | 0.463469E+11 | 0.00 | 0.70 |
November | 0.288255E+11 | 0.00 | 0.00 | 0.254323E+09 | 0.00 | 0.00 | 0.328807E+11 | 0.00 | 0.55 |
December | 0.458572E+11 | 0.00 | 0.00 | 40152115.04 | 0.00 | 0.00 | 0.152699E+11 | 0.00 | 0.32 |
Annual Sum or Average | 0.269238E+12 | 0.464342E+11 | 0.00 | 0.157919E+10 | 0.319260E+09 | 0.127463E+11 | 0.245189E+12 | 0.00 | 0.55 |
Minimum of Months | 0.220228E+09 | 0.00 | 0.00 | 2976380.48 | 0.00 | 0.00 | 0.223214E+10 | 0.00 | 0.31 |
Maximum of Months | 0.644703E+11 | 0.165903E+11 | 0.00 | 0.378831E+09 | 0.109223E+09 | 0.118375E+11 | 0.463469E+11 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.402556E+11 | 0.00 | 0.00 | 17849475.72 | 0.00 | 9325576.88 | 0.161419E+11 | 0.00 | 0.26 |
February | 0.331352E+11 | 0.00 | 0.00 | 0.160336E+09 | 0.00 | 6699712.70 | 0.130373E+11 | 0.00 | 0.28 |
March | 0.198842E+11 | 0.00 | 0.00 | 0.406844E+09 | 0.00 | 0.00 | 0.315122E+11 | 0.00 | 0.41 |
April | 0.113709E+11 | 0.359223E+09 | 0.00 | 0.206966E+09 | 11291516.75 | 0.00 | 0.387387E+11 | 0.00 | 0.57 |
May | 0.557182E+10 | 0.396402E+09 | 0.00 | 0.139764E+09 | 0.00 | 0.00 | 0.401993E+11 | 0.00 | 0.83 |
June | 0.291354E+10 | 0.419741E+10 | 0.00 | 0.302366E+09 | 92819907.90 | 0.00 | 0.234442E+11 | 0.00 | 0.69 |
July | 0.196149E+10 | 0.787766E+10 | 0.00 | 0.164960E+09 | 0.270263E+09 | 0.00 | 0.103802E+11 | 0.00 | 0.60 |
August | 0.242419E+10 | 0.769176E+10 | 0.00 | 0.111699E+09 | 0.208000E+09 | 0.00 | 0.163001E+11 | 0.00 | 0.71 |
September | 0.375536E+10 | 0.844649E+09 | 0.00 | 0.156995E+09 | 27556864.86 | 0.00 | 0.354179E+11 | 0.00 | 0.69 |
October | 0.114097E+11 | 0.00 | 0.00 | 0.500659E+09 | 0.00 | 0.00 | 0.425665E+11 | 0.00 | 0.63 |
November | 0.178451E+11 | 0.00 | 0.00 | 0.436887E+09 | 0.00 | 0.00 | 0.350615E+11 | 0.00 | 0.48 |
December | 0.264539E+11 | 0.00 | 0.00 | 0.126872E+09 | 0.00 | 0.00 | 0.249622E+11 | 0.00 | 0.27 |
Annual Sum or Average | 0.176981E+12 | 0.213671E+11 | 0.00 | 0.273220E+10 | 0.609930E+09 | 16025289.59 | 0.327762E+12 | 0.00 | 0.54 |
Minimum of Months | 0.196149E+10 | 0.00 | 0.00 | 17849475.72 | 0.00 | 0.00 | 0.103802E+11 | 0.00 | 0.26 |
Maximum of Months | 0.402556E+11 | 0.787766E+10 | 0.00 | 0.500659E+09 | 0.270263E+09 | 9325576.88 | 0.425665E+11 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.510636E+12 | 0.00 | 0.00 | 26227924.72 | 0.00 | 0.150362E+11 | 0.211606E+11 | 0.00 | 0.27 |
February | 0.410558E+12 | 0.00 | 0.00 | 0.248834E+09 | 0.00 | 0.527839E+10 | 0.204652E+11 | 0.00 | 0.27 |
March | 0.302785E+12 | 0.00 | 0.00 | 0.159015E+10 | 0.00 | 0.182208E+10 | 0.120404E+12 | 0.00 | 0.34 |
April | 0.177702E+12 | 0.242852E+10 | 0.00 | 0.108812E+10 | 0.130313E+10 | 45677809.69 | 0.195903E+12 | 0.00 | 0.44 |
May | 0.855608E+11 | 0.398406E+10 | 0.00 | 0.103694E+10 | 11556010.59 | 0.00 | 0.276628E+12 | 0.00 | 0.70 |
June | 0.539240E+11 | 0.397849E+11 | 0.00 | 0.193127E+10 | 0.208309E+10 | 0.00 | 0.156001E+12 | 0.00 | 0.59 |
July | 0.324922E+11 | 0.730174E+11 | 0.00 | 0.782268E+09 | 0.712173E+09 | 0.00 | 0.522293E+11 | 0.00 | 0.46 |
August | 0.309613E+11 | 0.688964E+11 | 0.00 | 0.553167E+09 | 0.375188E+10 | 0.00 | 0.926679E+11 | 0.00 | 0.53 |
September | 0.784280E+11 | 0.681149E+10 | 0.00 | 0.983907E+09 | 0.118171E+10 | 0.00 | 0.219873E+12 | 0.00 | 0.56 |
October | 0.172694E+12 | 0.00 | 0.00 | 0.262860E+10 | 15191959.79 | 0.00 | 0.204201E+12 | 0.00 | 0.45 |
November | 0.297621E+12 | 0.00 | 0.00 | 0.134711E+10 | 0.00 | 0.290889E+10 | 0.107131E+12 | 0.00 | 0.37 |
December | 0.423957E+12 | 0.00 | 0.00 | 0.102919E+09 | 0.00 | 0.648878E+10 | 0.324736E+11 | 0.00 | 0.26 |
Annual Sum or Average | 0.257732E+13 | 0.194923E+12 | 0.00 | 0.123195E+11 | 0.905873E+10 | 0.315801E+11 | 0.149914E+13 | 0.00 | 0.44 |
Minimum of Months | 0.309613E+11 | 0.00 | 0.00 | 26227924.72 | 0.00 | 0.00 | 0.204652E+11 | 0.00 | 0.26 |
Maximum of Months | 0.510636E+12 | 0.730174E+11 | 0.00 | 0.262860E+10 | 0.375188E+10 | 0.150362E+11 | 0.276628E+12 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.273464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152562E+11 | 0.00 | 0.00 | 0.22 |
February | 0.254764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969084E+10 | 0.00 | 0.00 | 0.24 |
March | 0.327647E+11 | 0.00 | 0.00 | 4992786.35 | 0.00 | 0.355952E+10 | 0.512178E+09 | 0.00 | 0.33 |
April | 0.266005E+11 | 0.167554E+09 | 0.00 | 23324146.91 | 0.111481E+09 | 0.120511E+10 | 0.588432E+10 | 0.00 | 0.43 |
May | 0.205049E+11 | 0.209397E+09 | 0.00 | 45475014.26 | 4135424.87 | 24732220.35 | 0.144290E+11 | 0.00 | 0.71 |
June | 0.101132E+11 | 0.308605E+10 | 0.00 | 0.103348E+09 | 0.489923E+09 | 0.00 | 0.962583E+10 | 0.00 | 0.58 |
July | 0.427099E+10 | 0.576753E+10 | 0.00 | 40431204.80 | 0.771574E+09 | 0.00 | 0.354659E+10 | 0.00 | 0.46 |
August | 0.527110E+10 | 0.551267E+10 | 0.00 | 37410096.37 | 0.113226E+10 | 0.00 | 0.554192E+10 | 0.00 | 0.51 |
September | 0.174477E+11 | 0.423910E+09 | 0.00 | 28206034.28 | 0.101396E+09 | 0.209085E+09 | 0.686908E+10 | 0.00 | 0.52 |
October | 0.308209E+11 | 0.00 | 0.00 | 5615556.79 | 4313201.18 | 0.147772E+10 | 0.591404E+09 | 0.00 | 0.44 |
November | 0.280127E+11 | 0.00 | 0.00 | 3304512.09 | 0.00 | 0.465353E+10 | 0.371403E+09 | 0.00 | 0.34 |
December | 0.262600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.979361E+10 | 0.00 | 0.00 | 0.22 |
Annual Sum or Average | 0.254889E+12 | 0.151671E+11 | 0.00 | 0.292108E+09 | 0.261508E+10 | 0.458703E+11 | 0.473718E+11 | 0.00 | 0.42 |
Minimum of Months | 0.427099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
Maximum of Months | 0.327647E+11 | 0.576753E+10 | 0.00 | 0.103348E+09 | 0.113226E+10 | 0.152562E+11 | 0.144290E+11 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.121493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120008E+11 | 0.00 | 0.00 | 0.48 |
February | 0.335133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710287E+10 | 0.00 | 0.00 | 0.49 |
March | 0.721421E+10 | 0.00 | 0.00 | 135608.59 | 0.00 | 0.268118E+10 | 41862870.72 | 0.00 | 0.61 |
April | 0.753333E+10 | 73748028.94 | 0.00 | 2537077.05 | 2666275.52 | 0.484073E+09 | 0.691436E+09 | 0.00 | 0.78 |
May | 0.536023E+10 | 79570828.88 | 0.00 | 7882969.33 | 0.00 | 1256239.74 | 0.269734E+10 | 0.00 | 1.16 |
June | 0.264097E+10 | 0.865160E+09 | 0.00 | 21728521.06 | 42218584.30 | 0.00 | 0.181306E+10 | 0.00 | 0.97 |
July | 0.125151E+10 | 0.145516E+10 | 0.00 | 10154418.39 | 0.107877E+09 | 0.00 | 0.893434E+09 | 0.00 | 0.85 |
August | 0.191532E+10 | 0.140312E+10 | 0.00 | 6630633.02 | 81314374.08 | 0.00 | 0.113801E+10 | 0.00 | 0.94 |
September | 0.507689E+10 | 0.164873E+09 | 0.00 | 5090351.70 | 6624519.39 | 55050001.37 | 0.131502E+10 | 0.00 | 0.90 |
October | 0.836772E+10 | 0.00 | 0.00 | 2761098.97 | 0.00 | 0.251739E+09 | 0.327695E+09 | 0.00 | 0.81 |
November | 0.673055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287426E+10 | 0.00 | 0.00 | 0.65 |
December | 0.363260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698968E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.542896E+11 | 0.404163E+10 | 0.00 | 56920678.11 | 0.240701E+09 | 0.324409E+11 | 0.891786E+10 | 0.00 | 0.76 |
Minimum of Months | 0.121493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.836772E+10 | 0.145516E+10 | 0.00 | 21728521.06 | 0.107877E+09 | 0.120008E+11 | 0.269734E+10 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.246687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101293E+11 | 0.00 | 0.00 | 0.70 |
February | 0.397965E+10 | 0.00 | 0.00 | 634579.40 | 0.00 | 0.592729E+10 | 48915843.50 | 0.00 | 0.72 |
March | 0.648829E+10 | 0.00 | 0.00 | 6381324.50 | 0.00 | 0.250710E+10 | 0.604985E+09 | 0.00 | 0.92 |
April | 0.650574E+10 | 70179672.83 | 0.00 | 7423111.84 | 2550845.78 | 0.733665E+09 | 0.149289E+10 | 0.00 | 1.22 |
May | 0.484885E+10 | 72449960.47 | 0.00 | 9532163.03 | 415253.78 | 3333119.82 | 0.334213E+10 | 0.00 | 1.83 |
June | 0.258578E+10 | 0.721433E+09 | 0.00 | 27729323.67 | 66128056.21 | 0.00 | 0.220185E+10 | 0.00 | 1.57 |
July | 0.122402E+10 | 0.106870E+10 | 0.00 | 14741154.53 | 0.236325E+09 | 0.00 | 0.116103E+10 | 0.00 | 1.39 |
August | 0.187768E+10 | 0.104004E+10 | 0.00 | 8420295.32 | 0.202721E+09 | 0.00 | 0.136926E+10 | 0.00 | 1.46 |
September | 0.421342E+10 | 0.140306E+09 | 0.00 | 9340424.22 | 6951945.84 | 60958135.45 | 0.218081E+10 | 0.00 | 1.43 |
October | 0.771203E+10 | 0.00 | 0.00 | 6070982.14 | 0.00 | 0.331467E+09 | 0.584911E+09 | 0.00 | 1.21 |
November | 0.632098E+10 | 0.00 | 0.00 | 44616.78 | 0.00 | 0.285378E+10 | 12837832.58 | 0.00 | 0.97 |
December | 0.336770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678435E+10 | 0.00 | 0.00 | 0.66 |
Annual Sum or Average | 0.515910E+11 | 0.311311E+10 | 0.00 | 90317975.43 | 0.515093E+09 | 0.293312E+11 | 0.129996E+11 | 0.00 | 1.18 |
Minimum of Months | 0.122402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.771203E+10 | 0.106870E+10 | 0.00 | 27729323.67 | 0.236325E+09 | 0.101293E+11 | 0.334213E+10 | 0.00 | 1.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.403509E+10 | 0.00 | 0.00 | 4423197.11 | 0.00 | 0.890179E+10 | 0.243100E+10 | 0.00 | 0.56 |
February | 0.530517E+10 | 0.00 | 0.00 | 23886927.28 | 0.00 | 0.512587E+10 | 0.196510E+10 | 0.00 | 0.60 |
March | 0.617241E+10 | 0.00 | 0.00 | 46535993.75 | 0.00 | 0.283478E+10 | 0.366240E+10 | 0.00 | 0.82 |
April | 0.641075E+10 | 0.159795E+09 | 0.00 | 20486390.45 | 2974357.59 | 0.963498E+09 | 0.402204E+10 | 0.00 | 1.08 |
May | 0.567184E+10 | 0.110769E+09 | 0.00 | 11835608.81 | 6484.09 | 42856218.12 | 0.380937E+10 | 0.00 | 1.40 |
June | 0.340192E+10 | 0.102819E+10 | 0.00 | 20522840.06 | 71290424.40 | 1183306.29 | 0.172927E+10 | 0.00 | 1.13 |
July | 0.159916E+10 | 0.169511E+10 | 0.00 | 8145864.25 | 0.178966E+09 | 0.00 | 0.788896E+09 | 0.00 | 0.97 |
August | 0.220911E+10 | 0.175403E+10 | 0.00 | 9379723.23 | 0.123566E+09 | 0.00 | 0.143307E+10 | 0.00 | 1.14 |
September | 0.468483E+10 | 0.324138E+09 | 0.00 | 16155620.79 | 7258898.16 | 99420407.22 | 0.342360E+10 | 0.00 | 1.24 |
October | 0.646472E+10 | 0.00 | 0.00 | 72842457.81 | 0.00 | 0.570978E+09 | 0.584112E+10 | 0.00 | 1.24 |
November | 0.668410E+10 | 0.00 | 0.00 | 24144148.05 | 0.00 | 0.287886E+10 | 0.203269E+10 | 0.00 | 0.82 |
December | 0.351748E+10 | 0.00 | 0.00 | 11746689.14 | 0.00 | 0.704105E+10 | 0.228742E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.561566E+11 | 0.507204E+10 | 0.00 | 0.270105E+09 | 0.384062E+09 | 0.284603E+11 | 0.334260E+11 | 0.00 | 0.96 |
Minimum of Months | 0.159916E+10 | 0.00 | 0.00 | 4423197.11 | 0.00 | 0.00 | 0.788896E+09 | 0.00 | 0.54 |
Maximum of Months | 0.668410E+10 | 0.175403E+10 | 0.00 | 72842457.81 | 0.178966E+09 | 0.890179E+10 | 0.584112E+10 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.553306E+10 | 0.00 | 0.00 | 38114.55 | 0.00 | 0.973373E+10 | 69358058.93 | 0.00 | 0.86 |
February | 0.742053E+10 | 0.00 | 0.00 | 2951201.24 | 0.00 | 0.447921E+10 | 0.255728E+09 | 0.00 | 0.88 |
March | 0.100036E+11 | 0.00 | 0.00 | 14868775.22 | 0.00 | 0.637792E+09 | 0.120833E+10 | 0.00 | 1.14 |
April | 0.740232E+10 | 0.105881E+09 | 0.00 | 17983043.42 | 194154.30 | 69191536.61 | 0.380647E+10 | 0.00 | 1.61 |
May | 0.621471E+10 | 0.101796E+09 | 0.00 | 8958222.41 | 0.00 | 0.00 | 0.341681E+10 | 0.00 | 2.16 |
June | 0.343047E+10 | 0.997163E+09 | 0.00 | 22224553.07 | 44037122.05 | 0.00 | 0.193990E+10 | 0.00 | 1.83 |
July | 0.142679E+10 | 0.187421E+10 | 0.00 | 11402111.74 | 76084255.53 | 0.00 | 0.113732E+10 | 0.00 | 1.59 |
August | 0.174133E+10 | 0.175204E+10 | 0.00 | 11835826.65 | 48986635.13 | 0.00 | 0.197025E+10 | 0.00 | 1.79 |
September | 0.581266E+10 | 0.219540E+09 | 0.00 | 6456264.24 | 2403775.74 | 454127.93 | 0.177993E+10 | 0.00 | 1.68 |
October | 0.902445E+10 | 0.00 | 0.00 | 20786377.05 | 0.00 | 6149594.61 | 0.180497E+10 | 0.00 | 1.55 |
November | 0.987989E+10 | 0.00 | 0.00 | 2490240.63 | 0.00 | 0.112982E+10 | 0.241476E+09 | 0.00 | 1.19 |
December | 0.939452E+10 | 0.00 | 0.00 | 441080.86 | 0.00 | 0.276923E+10 | 0.195885E+09 | 0.00 | 0.80 |
Annual Sum or Average | 0.772843E+11 | 0.505063E+10 | 0.00 | 0.120436E+09 | 0.171706E+09 | 0.188256E+11 | 0.178264E+11 | 0.00 | 1.43 |
Minimum of Months | 0.142679E+10 | 0.00 | 0.00 | 38114.55 | 0.00 | 0.00 | 69358058.93 | 0.00 | 0.80 |
Maximum of Months | 0.100036E+11 | 0.187421E+10 | 0.00 | 22224553.07 | 76084255.53 | 0.973373E+10 | 0.380647E+10 | 0.00 | 2.16 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.612650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184393E+12 | 0.00 | 0.00 | 0.73 |
February | 0.143661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137285E+12 | 0.00 | 0.00 | 0.75 |
March | 0.554291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837290E+11 | 0.00 | 0.00 | 0.87 |
April | 0.781248E+11 | 0.452382E+09 | 0.00 | 689022.12 | 0.500269E+09 | 0.321985E+11 | 0.864517E+09 | 0.00 | 1.01 |
May | 0.891342E+11 | 0.868051E+09 | 0.00 | 7287304.66 | 9778947.98 | 0.304709E+10 | 0.575520E+10 | 0.00 | 1.48 |
June | 0.468383E+11 | 0.833126E+10 | 0.00 | 32340136.44 | 0.196283E+10 | 0.531588E+09 | 0.535596E+10 | 0.00 | 1.16 |
July | 0.214303E+11 | 0.130459E+11 | 0.00 | 15295360.64 | 0.491272E+10 | 0.00 | 0.203450E+10 | 0.00 | 0.96 |
August | 0.292606E+11 | 0.115979E+11 | 0.00 | 20923855.00 | 0.595654E+10 | 8971525.32 | 0.396616E+10 | 0.00 | 1.08 |
September | 0.699480E+11 | 0.134211E+10 | 0.00 | 6261675.53 | 0.528699E+09 | 0.686694E+10 | 0.297556E+10 | 0.00 | 1.17 |
October | 0.845955E+11 | 0.00 | 0.00 | 0.00 | 5266585.61 | 0.285801E+11 | 0.00 | 0.00 | 1.06 |
November | 0.489557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835958E+11 | 0.00 | 0.00 | 0.92 |
December | 0.425829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156637E+12 | 0.00 | 0.00 | 0.72 |
Annual Sum or Average | 0.548467E+12 | 0.356376E+11 | 0.00 | 82797354.40 | 0.138761E+11 | 0.716873E+12 | 0.209519E+11 | 0.00 | 0.99 |
Minimum of Months | 0.425829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 |
Maximum of Months | 0.891342E+11 | 0.130459E+11 | 0.00 | 32340136.44 | 0.595654E+10 | 0.184393E+12 | 0.575520E+10 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.683290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106003E+12 | 0.00 | 0.00 | 0.68 |
February | 0.158172E+11 | 0.00 | 0.00 | 2103972.05 | 0.00 | 0.736923E+11 | 0.128479E+09 | 0.00 | 0.69 |
March | 0.381802E+11 | 0.00 | 0.00 | 41085673.81 | 0.00 | 0.426088E+11 | 0.306858E+10 | 0.00 | 0.82 |
April | 0.426486E+11 | 0.786145E+09 | 0.00 | 62722712.78 | 33634417.94 | 0.173844E+11 | 0.114549E+11 | 0.00 | 1.05 |
May | 0.422836E+11 | 0.818146E+09 | 0.00 | 85101469.64 | 13506099.87 | 0.891908E+09 | 0.260465E+11 | 0.00 | 1.66 |
June | 0.230860E+11 | 0.789550E+10 | 0.00 | 0.247137E+09 | 0.836777E+09 | 69749916.74 | 0.185944E+11 | 0.00 | 1.50 |
July | 0.106818E+11 | 0.113513E+11 | 0.00 | 0.120928E+09 | 0.308902E+10 | 0.00 | 0.897568E+10 | 0.00 | 1.28 |
August | 0.165974E+11 | 0.112127E+11 | 0.00 | 66116658.43 | 0.267002E+10 | 13487886.82 | 0.102288E+11 | 0.00 | 1.33 |
September | 0.363476E+11 | 0.144306E+10 | 0.00 | 68480841.88 | 0.110829E+09 | 0.306877E+10 | 0.143703E+11 | 0.00 | 1.29 |
October | 0.513813E+11 | 0.00 | 0.00 | 28295022.91 | 3813940.13 | 0.151138E+11 | 0.182118E+10 | 0.00 | 0.99 |
November | 0.281540E+11 | 0.00 | 0.00 | 2579562.97 | 0.00 | 0.503280E+11 | 0.136231E+09 | 0.00 | 0.84 |
December | 0.824080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875461E+11 | 0.00 | 0.00 | 0.66 |
Annual Sum or Average | 0.320252E+12 | 0.335068E+11 | 0.00 | 0.724551E+09 | 0.675760E+10 | 0.396720E+12 | 0.948251E+11 | 0.00 | 1.07 |
Minimum of Months | 0.683290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.513813E+11 | 0.113513E+11 | 0.00 | 0.247137E+09 | 0.308902E+10 | 0.106003E+12 | 0.260465E+11 | 0.00 | 1.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.426734E+11 | 0.00 | 0.00 | 38233404.07 | 0.00 | 0.125363E+12 | 0.220627E+11 | 0.00 | 0.74 |
February | 0.561447E+11 | 0.00 | 0.00 | 0.213392E+09 | 0.00 | 0.804544E+11 | 0.177104E+11 | 0.00 | 0.78 |
March | 0.620520E+11 | 0.00 | 0.00 | 0.399886E+09 | 0.00 | 0.550372E+11 | 0.294833E+11 | 0.00 | 0.95 |
April | 0.639090E+11 | 0.181750E+10 | 0.00 | 0.170448E+09 | 50536255.26 | 0.246308E+11 | 0.312397E+11 | 0.00 | 1.15 |
May | 0.717341E+11 | 0.125357E+10 | 0.00 | 77916219.10 | 10628136.17 | 0.270531E+10 | 0.247644E+11 | 0.00 | 1.53 |
June | 0.421641E+11 | 0.108504E+11 | 0.00 | 0.143929E+09 | 0.147071E+10 | 0.180861E+09 | 0.117885E+11 | 0.00 | 1.24 |
July | 0.189542E+11 | 0.173965E+11 | 0.00 | 43857893.19 | 0.390185E+10 | 0.00 | 0.433333E+10 | 0.00 | 1.02 |
August | 0.253308E+11 | 0.179161E+11 | 0.00 | 73735837.89 | 0.402734E+10 | 0.00 | 0.970608E+10 | 0.00 | 1.19 |
September | 0.538140E+11 | 0.351130E+10 | 0.00 | 0.129790E+09 | 0.126304E+09 | 0.459372E+10 | 0.269167E+11 | 0.00 | 1.36 |
October | 0.689795E+11 | 1996879.01 | 0.00 | 0.663783E+09 | 3668034.58 | 0.157576E+11 | 0.463677E+11 | 0.00 | 1.28 |
November | 0.658908E+11 | 0.00 | 0.00 | 0.180990E+09 | 0.00 | 0.550172E+11 | 0.143496E+11 | 0.00 | 0.97 |
December | 0.323556E+11 | 0.00 | 0.00 | 89349088.37 | 0.00 | 0.112195E+12 | 0.191537E+11 | 0.00 | 0.73 |
Annual Sum or Average | 0.604002E+12 | 0.527474E+11 | 0.00 | 0.222531E+10 | 0.959104E+10 | 0.475935E+12 | 0.257876E+12 | 0.00 | 1.08 |
Minimum of Months | 0.189542E+11 | 0.00 | 0.00 | 38233404.07 | 0.00 | 0.00 | 0.433333E+10 | 0.00 | 0.73 |
Maximum of Months | 0.717341E+11 | 0.179161E+11 | 0.00 | 0.663783E+09 | 0.402734E+10 | 0.125363E+12 | 0.463677E+11 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.171924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130797E+12 | 0.00 | 0.00 | 0.89 |
February | 0.330926E+11 | 0.00 | 0.00 | 8924485.79 | 0.00 | 0.839070E+11 | 0.857472E+09 | 0.00 | 0.91 |
March | 0.546869E+11 | 0.00 | 0.00 | 51672070.36 | 0.00 | 0.498192E+11 | 0.438691E+10 | 0.00 | 1.06 |
April | 0.569207E+11 | 0.757937E+09 | 0.00 | 86931401.41 | 0.186837E+09 | 0.171858E+11 | 0.178323E+11 | 0.00 | 1.34 |
May | 0.612775E+11 | 0.106023E+10 | 0.00 | 50461793.65 | 21129551.57 | 0.170119E+10 | 0.166932E+11 | 0.00 | 1.91 |
June | 0.337159E+11 | 0.898923E+10 | 0.00 | 0.149707E+09 | 0.123510E+10 | 0.203338E+09 | 0.115122E+11 | 0.00 | 1.65 |
July | 0.147805E+11 | 0.158899E+11 | 0.00 | 43067301.37 | 0.247360E+10 | 0.00 | 0.457696E+10 | 0.00 | 1.31 |
August | 0.198620E+11 | 0.134148E+11 | 0.00 | 51464893.90 | 0.317765E+10 | 0.00 | 0.798007E+10 | 0.00 | 1.46 |
September | 0.518002E+11 | 0.199273E+10 | 0.00 | 32345421.25 | 0.113924E+09 | 0.432693E+10 | 0.753978E+10 | 0.00 | 1.50 |
October | 0.680087E+11 | 0.00 | 0.00 | 86682878.76 | 4109266.41 | 0.143854E+11 | 0.706616E+10 | 0.00 | 1.31 |
November | 0.471806E+11 | 0.00 | 0.00 | 9371220.13 | 0.00 | 0.552765E+11 | 0.965181E+09 | 0.00 | 1.11 |
December | 0.181800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107049E+12 | 0.00 | 0.00 | 0.87 |
Annual Sum or Average | 0.476698E+12 | 0.421049E+11 | 0.00 | 0.570629E+09 | 0.721234E+10 | 0.464651E+12 | 0.794101E+11 | 0.00 | 1.28 |
Minimum of Months | 0.147805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Maximum of Months | 0.680087E+11 | 0.158899E+11 | 0.00 | 0.149707E+09 | 0.317765E+10 | 0.130797E+12 | 0.178323E+11 | 0.00 | 1.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.372213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146800E+11 | 0.00 | 0.00 | 0.60 |
February | 0.799069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116360E+11 | 0.00 | 0.00 | 0.66 |
March | 0.423294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876362E+10 | 0.00 | 0.00 | 0.91 |
April | 0.696490E+10 | 31205923.98 | 1053165.54 | 28125.89 | 45606028.36 | 0.447866E+10 | 0.100772E+09 | 6007.11 | 1.16 |
May | 0.104171E+11 | 42976158.76 | 0.00 | 414610.60 | 6712312.93 | 0.915725E+09 | 0.326954E+09 | 0.00 | 1.84 |
June | 0.520703E+10 | 0.618890E+09 | 0.00 | 1416033.08 | 0.307385E+09 | 0.267924E+09 | 0.567019E+09 | 0.00 | 1.38 |
July | 0.233232E+10 | 0.973415E+09 | 0.00 | 1110454.40 | 0.784943E+09 | 12662828.17 | 0.180903E+09 | 0.00 | 1.12 |
August | 0.299331E+10 | 0.882996E+09 | 0.00 | 1912514.09 | 0.922125E+09 | 0.116426E+09 | 0.339699E+09 | 0.00 | 1.26 |
September | 0.669230E+10 | 79905615.31 | 0.00 | 556575.92 | 56183618.35 | 0.154232E+10 | 76228893.71 | 0.00 | 1.38 |
October | 0.705849E+10 | 0.00 | 0.00 | 0.00 | 1522696.24 | 0.455215E+10 | 0.00 | 0.00 | 1.24 |
November | 0.343829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821858E+10 | 0.00 | 0.00 | 0.95 |
December | 0.127736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126058E+11 | 0.00 | 0.00 | 0.61 |
Annual Sum or Average | 0.506357E+11 | 0.262939E+10 | 1053165.54 | 5438313.96 | 0.212448E+10 | 0.677900E+11 | 0.159158E+10 | 6007.11 | 1.10 |
Minimum of Months | 0.127736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12662828.17 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.104171E+11 | 0.973415E+09 | 1053165.54 | 1912514.09 | 0.922125E+09 | 0.146800E+11 | 0.567019E+09 | 6007.11 | 1.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.426916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932473E+10 | 0.00 | 0.00 | 0.61 |
February | 0.110790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694674E+10 | 0.00 | 0.00 | 0.67 |
March | 0.419673E+10 | 0.00 | 0.00 | 628.70 | 0.00 | 0.422129E+10 | 3258198.01 | 0.00 | 0.92 |
April | 0.437164E+10 | 59146903.95 | 383339.05 | 3284103.33 | 4653359.04 | 0.244294E+10 | 0.795231E+09 | 1710.13 | 1.20 |
May | 0.549394E+10 | 44239656.44 | 0.00 | 4878290.65 | 1008672.77 | 0.366025E+09 | 0.191532E+10 | 0.00 | 1.94 |
June | 0.242823E+10 | 0.626423E+09 | 0.00 | 20756720.84 | 0.119901E+09 | 0.164789E+09 | 0.180536E+10 | 0.00 | 1.60 |
July | 0.106957E+10 | 0.903808E+09 | 0.00 | 9287584.71 | 0.398414E+09 | 1116817.11 | 0.797232E+09 | 0.00 | 1.31 |
August | 0.143851E+10 | 0.904144E+09 | 0.00 | 6474246.73 | 0.459490E+09 | 37524325.36 | 0.966219E+09 | 0.00 | 1.40 |
September | 0.415143E+10 | 92315599.88 | 0.00 | 4138202.15 | 13189518.96 | 0.662160E+09 | 0.628746E+09 | 0.00 | 1.44 |
October | 0.536597E+10 | 0.00 | 0.00 | 148320.83 | 986676.26 | 0.212289E+10 | 34477182.23 | 0.00 | 1.25 |
November | 0.249643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505649E+10 | 0.00 | 0.00 | 0.95 |
December | 0.390183E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.786054E+10 | 0.00 | 0.00 | 0.62 |
Annual Sum or Average | 0.329375E+11 | 0.263008E+10 | 383339.05 | 48968097.94 | 0.997643E+09 | 0.392072E+11 | 0.694585E+10 | 1710.13 | 1.16 |
Minimum of Months | 0.390183E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1116817.11 | 0.00 | 0.00 | 0.61 |
Maximum of Months | 0.549394E+10 | 0.904144E+09 | 383339.05 | 20756720.84 | 0.459490E+09 | 0.932473E+10 | 0.191532E+10 | 1710.13 | 1.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.352524E+10 | 0.00 | 0.00 | 1603668.25 | 0.00 | 0.102321E+11 | 0.105948E+10 | 0.00 | 0.60 |
February | 0.435718E+10 | 0.00 | 0.00 | 13517999.96 | 0.00 | 0.717048E+10 | 0.100274E+10 | 0.00 | 0.68 |
March | 0.569205E+10 | 0.00 | 0.00 | 23908116.52 | 0.00 | 0.559388E+10 | 0.191851E+10 | 0.00 | 0.94 |
April | 0.574668E+10 | 0.113517E+09 | 0.00 | 13090712.79 | 9203908.33 | 0.342061E+10 | 0.284891E+10 | 0.00 | 1.23 |
May | 0.850020E+10 | 58385831.12 | 0.00 | 5482069.62 | 4859518.59 | 0.910255E+09 | 0.218398E+10 | 0.00 | 1.85 |
June | 0.455023E+10 | 0.773781E+09 | 0.00 | 11593750.63 | 0.263577E+09 | 0.269148E+09 | 0.127463E+10 | 0.00 | 1.42 |
July | 0.208496E+10 | 0.122801E+10 | 0.00 | 3783950.94 | 0.703654E+09 | 22295520.22 | 0.406595E+09 | 0.00 | 1.15 |
August | 0.250057E+10 | 0.128820E+10 | 0.00 | 8841792.36 | 0.779146E+09 | 65956582.85 | 0.102199E+10 | 0.00 | 1.33 |
September | 0.556718E+10 | 0.191478E+09 | 0.00 | 10409319.01 | 20904306.51 | 0.110851E+10 | 0.184327E+10 | 0.00 | 1.48 |
October | 0.669978E+10 | 163155.78 | 0.00 | 43856213.90 | 1398291.75 | 0.245662E+10 | 0.331320E+10 | 0.00 | 1.36 |
November | 0.521503E+10 | 0.00 | 0.00 | 11040048.13 | 0.00 | 0.570923E+10 | 0.845213E+09 | 0.00 | 0.98 |
December | 0.240297E+10 | 0.00 | 0.00 | 4830751.24 | 0.00 | 0.932134E+10 | 0.900585E+09 | 0.00 | 0.61 |
Annual Sum or Average | 0.568421E+11 | 0.365353E+10 | 0.00 | 0.151958E+09 | 0.178274E+10 | 0.462804E+11 | 0.186191E+11 | 0.00 | 1.14 |
Minimum of Months | 0.208496E+10 | 0.00 | 0.00 | 1603668.25 | 0.00 | 22295520.22 | 0.406595E+09 | 0.00 | 0.60 |
Maximum of Months | 0.850020E+10 | 0.128820E+10 | 0.00 | 43856213.90 | 0.779146E+09 | 0.102321E+11 | 0.331320E+10 | 0.00 | 1.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.104955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882721E+10 | 0.00 | 0.00 | 0.62 |
February | 0.183763E+10 | 0.00 | 0.00 | 603564.64 | 0.00 | 0.626558E+10 | 54349887.05 | 0.00 | 0.68 |
March | 0.395189E+10 | 0.00 | 0.00 | 3050884.84 | 0.00 | 0.429806E+10 | 0.292197E+09 | 0.00 | 0.93 |
April | 0.434895E+10 | 46791458.69 | 0.00 | 7905394.53 | 16857968.13 | 0.195714E+10 | 0.175044E+10 | 0.00 | 1.28 |
May | 0.580993E+10 | 49144932.98 | 0.00 | 5094842.71 | 3431731.47 | 0.406084E+09 | 0.178701E+10 | 0.00 | 1.98 |
June | 0.299952E+10 | 0.650546E+09 | 0.00 | 15026110.36 | 0.144227E+09 | 0.143866E+09 | 0.131468E+10 | 0.00 | 1.64 |
July | 0.127092E+10 | 0.114793E+10 | 0.00 | 4288543.21 | 0.349822E+09 | 281735.21 | 0.510311E+09 | 0.00 | 1.28 |
August | 0.162584E+10 | 0.999648E+09 | 0.00 | 6268320.27 | 0.441857E+09 | 13664386.39 | 0.846818E+09 | 0.00 | 1.43 |
September | 0.419814E+10 | 0.112002E+09 | 0.00 | 3790765.10 | 15489274.59 | 0.718535E+09 | 0.677340E+09 | 0.00 | 1.48 |
October | 0.528867E+10 | 0.00 | 0.00 | 5779913.94 | 999599.35 | 0.187867E+10 | 0.529164E+09 | 0.00 | 1.28 |
November | 0.310505E+10 | 0.00 | 0.00 | 657926.60 | 0.00 | 0.447771E+10 | 74122566.09 | 0.00 | 0.97 |
December | 0.958403E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739630E+10 | 0.00 | 0.00 | 0.63 |
Annual Sum or Average | 0.364445E+11 | 0.300607E+10 | 0.00 | 52466266.19 | 0.972684E+09 | 0.363831E+11 | 0.783643E+10 | 0.00 | 1.19 |
Minimum of Months | 0.958403E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 281735.21 | 0.00 | 0.00 | 0.62 |
Maximum of Months | 0.580993E+10 | 0.114793E+10 | 0.00 | 15026110.36 | 0.441857E+09 | 0.882721E+10 | 0.178701E+10 | 0.00 | 1.98 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 19690365.26 | 0.00 | 0.00 | 3343517.34 | 0.00 | 0.00 | 0.101994E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 0.109631E+09 | 0.00 | 0.00 | 0.742417E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.112029E+09 | 0.00 | 0.00 | 0.646145E+09 | 0.00 | 0.30 |
April | 0.00 | 9862615.72 | 0.00 | 56910162.96 | 0.00 | 0.00 | 0.463962E+09 | 0.00 | 0.29 |
May | 0.00 | 9499522.47 | 0.00 | 6871928.89 | 0.00 | 0.00 | 0.282601E+09 | 0.00 | 0.29 |
June | 0.00 | 87120285.17 | 0.00 | 25987623.59 | 0.00 | 0.00 | 0.113916E+09 | 0.00 | 0.30 |
July | 0.00 | 0.150096E+09 | 0.00 | 12838906.84 | 0.00 | 0.00 | 15038808.43 | 0.00 | 0.28 |
August | 0.00 | 0.155698E+09 | 0.00 | 12473401.97 | 0.00 | 0.00 | 38973786.50 | 0.00 | 0.31 |
September | 0.00 | 16055378.98 | 0.00 | 6663407.24 | 0.00 | 0.00 | 0.280475E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 61987737.00 | 0.00 | 0.00 | 0.453505E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 99211629.46 | 0.00 | 0.00 | 0.560186E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 58769096.61 | 0.00 | 0.00 | 0.826099E+09 | 0.00 | 0.28 |
Annual Sum or Average | 19690365.26 | 0.428332E+09 | 0.00 | 0.566718E+09 | 0.00 | 0.00 | 0.544326E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3343517.34 | 0.00 | 0.00 | 15038808.43 | 0.00 | 0.28 |
Maximum of Months | 19690365.26 | 0.155698E+09 | 0.00 | 0.112029E+09 | 0.00 | 0.00 | 0.101994E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.378844E+10 | 0.00 | 0.00 | 12205870.01 | 0.00 | 0.00 | 0.657850E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 0.926777E+09 | 0.00 | 0.00 | 0.755362E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.100209E+10 | 0.00 | 0.00 | 0.658002E+10 | 0.00 | 0.30 |
April | 0.00 | 97724250.41 | 0.00 | 0.528170E+09 | 0.00 | 0.00 | 0.468258E+10 | 0.00 | 0.29 |
May | 0.00 | 92565768.46 | 0.00 | 57653249.51 | 0.00 | 0.00 | 0.284637E+10 | 0.00 | 0.29 |
June | 0.00 | 0.864265E+09 | 0.00 | 0.241059E+09 | 0.00 | 0.00 | 0.116108E+10 | 0.00 | 0.30 |
July | 0.00 | 0.149004E+10 | 0.00 | 0.121620E+09 | 0.00 | 0.00 | 0.159583E+09 | 0.00 | 0.28 |
August | 0.00 | 0.154475E+10 | 0.00 | 0.117601E+09 | 0.00 | 0.00 | 0.403020E+09 | 0.00 | 0.31 |
September | 0.00 | 0.157488E+09 | 0.00 | 53010204.63 | 0.00 | 0.00 | 0.282148E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 0.541381E+09 | 0.00 | 0.00 | 0.461369E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.861234E+09 | 0.00 | 0.00 | 0.573271E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.516828E+09 | 0.00 | 0.00 | 0.833147E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.378844E+10 | 0.424683E+10 | 0.00 | 0.497963E+10 | 0.00 | 0.00 | 0.514641E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 12205870.01 | 0.00 | 0.00 | 0.159583E+09 | 0.00 | 0.28 |
Maximum of Months | 0.378844E+10 | 0.154475E+10 | 0.00 | 0.100209E+10 | 0.00 | 0.00 | 0.833147E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.726954E+09 | 0.00 | 0.00 | 474501.14 | 0.00 | 0.00 | 0.300656E+09 | 0.00 | 0.28 |
February | 534718.40 | 0.00 | 0.00 | 70485199.48 | 0.00 | 0.00 | 0.770225E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 90612410.94 | 0.00 | 0.00 | 0.667575E+09 | 0.00 | 0.30 |
April | 0.00 | 9717525.47 | 0.00 | 49934629.77 | 0.00 | 0.00 | 0.471676E+09 | 0.00 | 0.29 |
May | 13072531.73 | 9367138.01 | 0.00 | 4856563.71 | 0.00 | 0.00 | 0.273118E+09 | 0.00 | 0.29 |
June | 0.00 | 86548468.66 | 0.00 | 22707311.27 | 0.00 | 0.00 | 0.117693E+09 | 0.00 | 0.30 |
July | 0.00 | 0.149002E+09 | 0.00 | 11774482.16 | 0.00 | 0.00 | 16480146.45 | 0.00 | 0.28 |
August | 0.00 | 0.153653E+09 | 0.00 | 11465298.64 | 0.00 | 0.00 | 41465584.25 | 0.00 | 0.31 |
September | 31755735.63 | 15807274.88 | 0.00 | 3912911.66 | 0.00 | 0.00 | 0.252303E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 45518120.38 | 0.00 | 0.00 | 0.470069E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 76908904.60 | 0.00 | 0.00 | 0.582580E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 47258682.96 | 0.00 | 0.00 | 0.837600E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.772317E+09 | 0.424095E+09 | 0.00 | 0.435909E+09 | 0.00 | 0.00 | 0.480144E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 474501.14 | 0.00 | 0.00 | 16480146.45 | 0.00 | 0.28 |
Maximum of Months | 0.726954E+09 | 0.153653E+09 | 0.00 | 90612410.94 | 0.00 | 0.00 | 0.837600E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.116205E+10 | 0.00 | 0.00 | 0.351026E+12 | 0.00 | 4.31 |
February | 0.775949E+10 | 0.00 | 0.00 | 0.326354E+10 | 0.00 | 0.00 | 0.452257E+12 | 0.00 | 8.01 |
March | 0.381769E+10 | 0.00 | 0.00 | 0.723896E+10 | 0.00 | 0.00 | 0.743052E+12 | 0.00 | 16.34 |
April | 0.00 | 0.139378E+09 | 0.00 | 0.484940E+10 | 0.00 | 0.00 | 0.907443E+12 | 0.00 | 29.79 |
May | 0.00 | 0.00 | 0.00 | 0.744680E+09 | 0.00 | 0.00 | 0.266908E+12 | 0.00 | 11.76 |
June | 0.448152E+09 | 0.197686E+10 | 0.00 | 0.208712E+10 | 18110689.68 | 0.00 | 0.203362E+12 | 0.00 | 17.05 |
July | 1248083.92 | 0.334384E+10 | 0.00 | 0.329357E+10 | 0.00 | 0.00 | 0.333876E+12 | 0.00 | 27.84 |
August | 0.00 | 0.409970E+10 | 0.00 | 0.254854E+10 | 0.00 | 0.00 | 0.457223E+12 | 0.00 | 35.19 |
September | 0.00 | 52560310.62 | 0.00 | 0.722947E+09 | 0.00 | 0.00 | 0.239945E+12 | 0.00 | 10.73 |
October | 0.313682E+10 | 0.00 | 0.00 | 0.362664E+10 | 0.00 | 0.00 | 0.500312E+12 | 0.00 | 15.16 |
November | 59050858.59 | 0.00 | 0.00 | 0.766764E+10 | 0.00 | 0.00 | 0.741473E+12 | 0.00 | 16.97 |
December | 0.00 | 0.00 | 0.00 | 0.561405E+10 | 0.00 | 0.00 | 0.105071E+13 | 0.00 | 16.48 |
Annual Sum or Average | 0.152225E+11 | 0.961234E+10 | 0.00 | 0.428191E+11 | 18110689.68 | 0.00 | 0.624758E+13 | 0.00 | 17.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.722947E+09 | 0.00 | 0.00 | 0.203362E+12 | 0.00 | 4.31 |
Maximum of Months | 0.775949E+10 | 0.409970E+10 | 0.00 | 0.766764E+10 | 18110689.68 | 0.00 | 0.105071E+13 | 0.00 | 35.19 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:26:25
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.406472E+12 | 0.721975E+11 | 0.00 | 0.212112E+13 | 0.643993E+12 |
February | 0.435956E+12 | 0.537504E+11 | 0.00 | 0.215216E+13 | 0.703968E+12 |
March | 0.627637E+12 | 0.471625E+11 | 0.00 | 0.286199E+13 | 0.850558E+12 |
April | 0.728156E+12 | 0.284130E+11 | 0.00 | 0.310337E+13 | 0.105544E+13 |
May | 0.824275E+12 | 0.152237E+11 | 0.00 | 0.266276E+13 | 0.756620E+12 |
June | 0.849107E+12 | 0.348268E+10 | 0.00 | 0.160886E+13 | 0.213123E+13 |
July | 0.851135E+12 | 0.779515E+09 | 0.00 | 0.111556E+13 | 0.292855E+13 |
August | 0.739512E+12 | 0.418926E+10 | 0.00 | 0.164179E+13 | 0.316972E+13 |
September | 0.520536E+12 | 0.134146E+11 | 0.00 | 0.221784E+13 | 0.106444E+13 |
October | 0.409658E+12 | 0.272519E+11 | 0.00 | 0.289689E+13 | 0.587176E+12 |
November | 0.273053E+12 | 0.456321E+11 | 0.00 | 0.269487E+13 | 0.809820E+12 |
December | 0.236778E+12 | 0.618361E+11 | 0.00 | 0.287348E+13 | 0.110268E+13 |
Annual Sum or Average | 0.690228E+13 | 0.373333E+12 | 0.00 | 0.279507E+14 | 0.158042E+14 |
Minimum of Months | 0.236778E+12 | 0.779515E+09 | 0.00 | 0.111556E+13 | 0.587176E+12 |
Maximum of Months | 0.851135E+12 | 0.721975E+11 | 0.00 | 0.310337E+13 | 0.316972E+13 |