Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470

Simulation Timestamp: 2024-07-03 12:26:37


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 39680.02 856.64 856.64
Net Site Energy 39680.02 856.64 856.64
Total Source Energy 108689.17 2346.47 2346.47
Net Source Energy 108689.17 2346.47 2346.47


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 8150.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1735.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 5610.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1004.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2623.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 3022.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 939.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 121.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5080.70
Humidification 1280.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 476.27
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 514.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 31529.54 8150.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7837.15
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 8150.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 1735.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 5610.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 1004.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5334.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 56.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 2505.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 61.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 3022.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 939.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 121.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5080.70
Humidification General 1280.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 476.27
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 514.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 8150.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 1735.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 5610.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 1004.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 2623.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 3022.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 939.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 121.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5080.70
Humidification Unassigned 1280.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 476.27
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 514.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 142.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 164.39 175.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.17
Other 373.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 680.68 175.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.17


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 142.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 164.39 175.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.17
Other 373.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 680.68 175.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.17


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 31529.536 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 31529.536 100.00
     
Total On-Site and Utility Electric Sources 31529.536 100.00
Total Electricity End Uses 31529.536 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 7837.15 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 7837.15 100.00
Total Water End Uses 7837.15 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 129.67
Time Setpoint Not Met During Occupied Cooling 234.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 5487.83


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| Environment |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS SZVAV FAN | AIRLOOP DATACENTER BASEMENT SYS11 FAN | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26
RunPeriod RUNPERIOD 1
Weather File International Falls Intl Ap MN USA TMY3 WMO#=727470
Latitude [deg] 48.57
Longitude [deg] -93.4
Elevation [m] 359.00
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 11.6510 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 11.6510 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 11.6510 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 11.6510 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 11.6510 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 11.6510 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 11.6510 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 11.6510 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 115.90 115.90 11.6510 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 11.6510 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 115.90 115.90 11.6510 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 11.6510 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 11.6510 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 11.6510 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 11.6510 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 11.6510 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 22.3674 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 22.3674 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 22.3674 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 11.6510 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 11.7515 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 11.7515 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 11.6510 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 11.6510 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 11.6510 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 11.6510 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 11.6510 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 11.6510 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 11.6510 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 11.6510 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 11.6510 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 11.6510 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 11.6510 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 11.6510 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 11.6510 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 11.6510 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 11.6510 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 11.6510 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 22.3674 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 22.3674 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 22.3674 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 11.6510 18.58 484.4232  
Total 46320.38             11.7515 9.29 17.8789  
Conditioned Total 46320.38             11.7515 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 3.6100 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 08-AUG-15:20 09-JAN-07:30 - - - - - - - - - - 18-MAY-15:09
Heating 0.00 3228629.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 457589.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 489900.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 778371.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 235096.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 303257.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 96563.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 55784.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 38891.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 2455455.28 3228629.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 3228629.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 457589.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 489900.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 3543.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 229608.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 1944.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 303257.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 96563.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 55784.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 38891.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 8835.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 5497.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 17769.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 3181.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 46480.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 8307.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 9573.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 2975.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 385.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 4054.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 1628.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 99854.04 8835.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 190.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 118.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 383.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 68.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 179.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 206.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 64.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 8.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 87.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 35.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2155.73 190.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 190.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 118.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 383.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 68.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 179.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 206.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 64.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 8.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 87.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 35.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2155.73 190.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

AirTerminal:SingleDuct:VAV:NoReheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s]
BASEMENT PSZ-VAV DIFFUSER 7.50 0.282430 0.300000 2.25
DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER 32.88 0.018159 0.500000 16.44
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 7.77 0.244906 0.300000 2.33 0.653084 0.500000 0.001556 0.000267 2.33 12.89 0.008000
CORE_MID VAV BOX COMPONENT 73.35 0.259327 0.300000 22.00 0.691537 0.500000 0.001469 0.005765 28.73 12.89 0.008000
CORE_TOP VAV BOX COMPONENT 9.65 0.197014 0.300000 2.90 0.525371 0.500000 0.001934 0.001922 9.65 12.89 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 1.73 0.138223 0.300000 0.518339 0.368594 0.500000 0.002756 0.000344 1.73 12.89 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.96 0.078465 0.300000 0.588438 0.300000 0.500000 0.004856 0.000233 1.17 12.89 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 2.43 0.098316 0.300000 0.728752 0.300000 0.500000 0.003875 0.000379 1.91 12.89 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 2.36 0.065186 0.300000 0.708304 0.300000 0.500000 0.005845 0.000204 1.03 12.89 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 22.94 0.104125 0.300000 6.88 0.300000 0.500000 0.003659 0.004558 22.94 12.89 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 20.92       0.300000 0.500000 0.005179 0.003029 15.24 12.89 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 24.82 0.096236 0.300000 7.44 0.300000 0.500000 0.003959 0.004659 23.44 12.89 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 22.52 0.068353 0.300000 6.75 0.300000 0.500000 0.005574 0.003026 15.23 12.89 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 3.06 0.078014 0.300000 0.918376 0.300000 0.500000 0.004884 0.000608 3.06 12.89 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 2.10 0.073416 0.300000 0.628900 0.300000 0.500000 0.005190 0.000401 2.02 12.89 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 3.11 0.076681 0.300000 0.934358 0.300000 0.500000 0.004969 0.000619 3.11 12.89 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 2.41 0.063803 0.300000 0.723660 0.300000 0.500000 0.005972 0.000406 2.04 12.89 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K] User-Specified Rated Capacity [W]
CORE_BOTTOM VAV BOX REHEAT COIL 30574.13 0.000267 640.21  
CORE_MID VAV BOX REHEAT COIL 658977.35 0.005765 15430.05  
CORE_TOP VAV BOX REHEAT COIL 219686.05 0.001922 5132.78  
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 39271.36 0.000344 917.25  
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 26601.41 0.000233 621.31  
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 43292.91 0.000379 1011.13  
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 23364.07 0.000204 545.74  
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 521019.10 0.004558 12167.41  
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 346211.43 0.003029 8085.00  
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 532536.00 0.004659 12436.25  
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 345869.13 0.003026 8076.99  
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 69515.92 0.000608 1623.25  
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 45832.54 0.000401 1070.22  
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 70724.46 0.000619 1651.47  
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 46435.92 0.000406 1084.30  
VAV_BOT WITH REHEAT HEATING COIL 94972.66 0.000831 1525.16  
VAV_MID WITH REHEAT HEATING COIL 960493.12 0.008403 15280.34  
VAV_TOP WITH REHEAT HEATING COIL 84131.47 0.000736 1419.05  
CAV_BAS HEATING COIL 129267.29 0.000875 2622.30 100000.00
AIRLOOP DATACENTER BASEMENT HEATING COIL 567830.08 0.000875 2622.30 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
DATACENTER_BOT_ZN_6 DIRECT AIR 0.815034
DATACENTER_MID_ZN_6 DIRECT AIR 7.87
DATACENTER_TOP_ZN_6 DIRECT AIR 0.807895
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 8.12 4.87 16.25 6.91 13.16 13.16 0.300000 0.524815 13.16
VAV_MID WITH REHEAT 82.27 49.36 164.54 105.58 122.27 122.27 0.300000 0.863483 122.27
VAV_TOP WITH REHEAT 10.17 6.10 20.34 19.89 15.02 19.89 0.300000 1.00 19.89
CAV_BAS 2.25 2.25 7.50 2.25 7.50 7.50 1.00 0.300000 7.50
AIRLOOP DATACENTER BASEMENT 16.44 16.44 32.88 16.44 32.88 32.88 1.00 0.500000 32.88
AIRLOOP DATACENTER BOT 0.815034 0.815034 0.815034 0.815034 0.815034 0.815034 1.00 1.00 0.815034
AIRLOOP DATACENTER MID 7.87 7.87 7.87 7.87 7.87 7.87 1.00 1.00 7.87
AIRLOOP DATACENTER TOP 0.807895 0.807895 0.807895 0.807895 0.807895 0.807895 1.00 1.00 0.807895
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 13.16  
VAV_MID WITH REHEAT_OA_CONTROLLER 122.27  
VAV_TOP WITH REHEAT_OA_CONTROLLER 19.89  
CAV_BAS_OA_CONTROLLER 7.50 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 32.88 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.815034 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 7.87 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.807895 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 24.94 6.67 11.04 0.009418 0.008500 251110.40 0.008969 13.16
VAV_MID WITH REHEAT COOLING COIL 25.01 6.67 11.04 0.009520 0.008500 2379307.07 0.084983 122.27
VAV_TOP WITH REHEAT COOLING COIL 24.82 6.67 11.06 0.009354 0.008500 372423.84 0.013302 19.89
CAV_BAS COOLING COIL 24.79 6.67 11.03 0.009601 0.008500 141841.05 0.005066 7.50
AIRLOOP DATACENTER BASEMENT COOLING COIL 27.03 6.67 15.01 0.008576 0.008500 456895.97 0.016319 32.88
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 13.16
VAV_MID WITH REHEAT FAN 122.27
VAV_TOP WITH REHEAT FAN 19.89
CAV_BAS SZVAV FAN 7.50
AIRLOOP DATACENTER BASEMENT SYS11 FAN 32.88
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.008969 0.000053
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000831  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.084983 0.000006
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.008403  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.013302 0.000036
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000736  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitarySystem

Design Size Supply Air Flow Rate [m3/s] Design Size Heating Supply Air Flow Rate [m3/s] Design Size Cooling Supply Air Flow Rate [m3/s] Design Size No Load Supply Air Flow Rate [m3/s] Design Size Nominal Cooling Capacity [W] Design Size Nominal Heating Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone Design Size Minimum Supply Air Temperature [C] User-Specified Minimum Supply Air Temperature [C] User-Specified Maximum Supply Air Temperature [C] User-Specified Nominal Cooling Capacity [W] Design Size Maximum Supply Air Temperature [C]
CAV_BAS_UNITARY_PACKAGE_DX 7.50 7.50 7.50 2.25 141841.05 100000.00 1.00 5.33 12.89 32.11    
AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX 32.88 32.88 32.88 16.44 456895.97 100000.00 1.00   15.89 29.11    
AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX 0.815034 0.815034 0.815034 0.815034   28103.35 1.00       13491.71 29.11
AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX 7.87 7.87 7.87 7.87   271511.16 1.00       130247.14 29.11
AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX 0.807895 0.807895 0.807895 0.807895   27862.37 1.00       13373.52 29.11
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000304 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:SystemModel

Design Size Design Maximum Air Flow Rate [m3/s] Design Electric Power Consumption [W]
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN 0.815034 1401.56
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN 7.87 13530.51
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN 0.807895 1389.29
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:MultiSpeed

User-Specified Speed 2 Rated Air Flow Rate [m3/s] Design Size Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] User-Specified Speed 2 Rated Sensible Heat Ratio User-Specified Speed 1 Rated Sensible Heat Ratio
AIRLOOP DATACENTER BOT COOLING COIL 0.815030 0.407517 0.543353 13491.71 6745.85 0.800660 0.800660
AIRLOOP DATACENTER MID COOLING COIL 7.87 3.93 5.25 130247.14 65123.57 0.800660 0.800660
AIRLOOP DATACENTER TOP COOLING COIL 0.807890 0.403947 0.538593 13373.52 6686.76 0.800660 0.800660
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BOT HEATING COIL 28103.35
AIRLOOP DATACENTER MID HEATING COIL 271511.16
AIRLOOP DATACENTER TOP HEATING COIL 27862.37
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.128640 26507.96  
HEATSYS1 PUMP 0.038139 11485.76 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.128640 15.44
HEATSYS1 0.038139 4.58
COOLSYS1_SUPPLY 0.128640 15.44
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.128640 0.128640 539966.77 6.67
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 4359509.04 4359509.04 0.038139
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 CHILLER1 PUMP 0.064320 12234.64
COOLSYS1 CHILLER2 PUMP 0.064320 12234.64
SWHSYS1 PUMP 0.000440 56.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.128640 0.064910 1817307.15 1817360.45 0.091080
COOLSYS1 CHILLER2 0.128640 0.064910 1817307.15 1817360.45 0.091080
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.182159 21.86
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.182159 63519.20
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 76.61 2176855.80 15.32 272106.97
TOWERWATERSYS COOLTOWER 2 76.61 2176855.80 15.32 272106.97
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 5.40 -2.00 -14.60 -16.90 -11.50 -6.20 4.00 13.40 18.00 19.70 17.90 12.30


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 International Falls Intl Ap MN USA TMY3 WMO#=727470 48.57 -93.40 -6.00 359.00 97086 1.1539


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 3.29 36.60 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 76.91 115.90 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 76.91 115.90 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 11.651 4.842 0.000 0.000 0.000 0.000 16.493 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 22.367 215.299 0.000 0.000 0.000 0.000 237.667 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 22.367 215.299 0.000 0.000 0.000 0.000 237.667 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 22.367 215.299 0.000 0.000 0.000 0.000 237.667 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 11.651 484.423 0.000 0.000 0.000 0.000 496.074 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 32383.100 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 32383.100
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 29082.299 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 29082.299
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 29082.299 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 29082.299
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 29082.299 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 29082.299
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 3651.573 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3651.573
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 2353.212 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2353.212
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 3651.653 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3651.653
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 2353.212 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2353.212
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 3651.573 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3651.573
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 2353.212 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2353.212
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 3651.653 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3651.653
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 2353.212 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2353.212
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 3651.573 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3651.573
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 2353.212 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2353.212
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 3651.653 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3651.653
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 2353.212 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2353.212
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 9130.649 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 9130.649
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 809.760 22.367 415.559 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 809.760
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 809.760 22.367 415.559 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 809.760
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 809.760 22.367 415.559 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 809.760


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 9.815 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.3762 0.900 0.900 0.700 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 4 7 0.167 0.3843 0.900 0.900 0.700 0.700 Smooth
10 NONRES_EXT_WALL_MID 21 4 7 0.167 0.3843 0.900 0.900 0.700 0.700 Smooth
11 NONRES_EXT_WALL_TOP 22 4 7 0.167 0.3843 0.900 0.900 0.700 0.700 Smooth
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.1019
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 2.599
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
16 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
17 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 2.368
18 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
19 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
20 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
21 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 2.368
22 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
23 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
24 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
25 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 2.368
26 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
27 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.312
28 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
29 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.312
30 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
31 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.312
32 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
33 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.312
34 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
35 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 2.312
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 2.312
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 9.8148919 9.8148919 9.8148919  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.61039648E-06 0.16815647E-08 -0.37447326E-05 0.10149002E-16
47 2 0.76989337 0.22941655E-02 1.0458372 -0.71793422E-06
48 1 -21.843031 0.15409339 -6.3407615 0.20050303
49 0 21.373924 0.14439780 5.5957134  
50 7 -0.35963630E-12 0.61482467E-15 -0.13288964E-12 0.15093609E-15
51 6 0.33258387E-07 0.11249777E-09 0.75805110E-08 -0.16019892E-12
52 5 -0.21313350E-03 0.93714421E-06 -0.10927814E-03 0.74776115E-08
53 4 0.31870195 0.44521373E-03 0.10925225 -0.37358013E-04
54 3 -7.7913368 0.13499397E-01 -2.4947666 0.31584435E-01
55 2 42.601618 0.47079245E-01 15.902165 -0.35261900
56 1 -81.870774 0.20888078E-01 -29.712230 1.1068570
57 0 46.824331 0.41326549E-03 16.278015  
58 7 -0.35963630E-12 0.61482467E-15 -0.13288964E-12 0.15093609E-15
59 6 0.33258387E-07 0.11249777E-09 0.75805110E-08 -0.16019892E-12
60 5 -0.21313350E-03 0.93714421E-06 -0.10927814E-03 0.74776115E-08
61 4 0.31870195 0.44521373E-03 0.10925225 -0.37358013E-04
62 3 -7.7913368 0.13499397E-01 -2.4947666 0.31584435E-01
63 2 42.601618 0.47079245E-01 15.902165 -0.35261900
64 1 -81.870774 0.20888078E-01 -29.712230 1.1068570
65 0 46.824331 0.41326549E-03 16.278015  
66 7 -0.35963630E-12 0.61482467E-15 -0.13288964E-12 0.15093609E-15
67 6 0.33258387E-07 0.11249777E-09 0.75805110E-08 -0.16019892E-12
68 5 -0.21313350E-03 0.93714421E-06 -0.10927814E-03 0.74776115E-08
69 4 0.31870195 0.44521373E-03 0.10925225 -0.37358013E-04
70 3 -7.7913368 0.13499397E-01 -2.4947666 0.31584435E-01
71 2 42.601618 0.47079245E-01 15.902165 -0.35261900
72 1 -81.870774 0.20888078E-01 -29.712230 1.1068570
73 0 46.824331 0.41326549E-03 16.278015  
74 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
75 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
76 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
77 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
78 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
79 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
80 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
81 0 0.43108349 0.21254961E-04 60.838472  
82 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
83 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
84 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
85 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
86 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
87 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
88 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
89 0 0.43108349 0.21254961E-04 60.838472  
90 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
91 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
92 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
93 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
94 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
95 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
96 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
97 0 0.43108349 0.21254961E-04 60.838472  
98 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
99 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
100 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
101 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
102 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
103 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
104 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
105 0 0.43108349 0.21254961E-04 60.838472  
106 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
107 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
108 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
109 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
110 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
111 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
112 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
113 0 0.43108349 0.21254961E-04 60.838472  
114 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
115 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
116 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
117 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
118 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
119 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
120 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
121 0 0.43108349 0.21254961E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.57_SHGC_EAST_0.49 35 1 VerySmooth 3.241 3.241 1.000 0.491    
2 WINDOW_U_0.57_SHGC_SOUTH_0.49 36 1 VerySmooth 3.241 3.241 1.000 0.491    
3 WINDOW_U_0.57_SHGC_WEST_0.49 37 1 VerySmooth 3.241 3.241 1.000 0.491    
4 WINDOW_U_0.57_SHGC_NORTH_0.49 38 1 VerySmooth 3.241 3.241 1.000 0.491    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   2.00000E-003 0.40797 0.37250 0.37250 0.53900 0.12971 0.15583 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   2.00000E-003 0.40797 0.37250 0.37250 0.53900 0.12971 0.15583 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   2.00000E-003 0.40797 0.37250 0.37250 0.53900 0.12971 0.15583 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   2.00000E-003 0.40797 0.37250 0.37250 0.53900 0.12971 0.15583 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 13.342 0.7435


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2500
2 Zone BASEMENT 1.2500
3 Zone CORE_BOTTOM 1.2500
4 Zone CORE_MID 1.2500
5 Zone CORE_TOP 1.2500
6 Zone PERIMETER_BOT_ZN_3 1.2500
7 Zone PERIMETER_BOT_ZN_2 1.2500
8 Zone PERIMETER_BOT_ZN_1 1.2500
9 Zone PERIMETER_BOT_ZN_4 1.2500
10 Zone PERIMETER_MID_ZN_3 1.2500
11 Zone PERIMETER_MID_ZN_2 1.2500
12 Zone PERIMETER_MID_ZN_1 1.2500
13 Zone PERIMETER_MID_ZN_4 1.2500
14 Zone PERIMETER_TOP_ZN_3 1.2500
15 Zone PERIMETER_TOP_ZN_2 1.2500
16 Zone PERIMETER_TOP_ZN_1 1.2500
17 Zone PERIMETER_TOP_ZN_4 1.2500
18 Zone DATACENTER_BOT_ZN_6 1.2500
19 Zone DATACENTER_MID_ZN_6 1.2500
20 Zone DATACENTER_TOP_ZN_6 1.2500
21 Zone DATACENTER_BASEMENT_ZN_6 1.2500


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.1500
2 Zone BASEMENT 1.1500
3 Zone CORE_BOTTOM 1.1500
4 Zone CORE_MID 1.1500
5 Zone CORE_TOP 1.1500
6 Zone PERIMETER_BOT_ZN_3 1.1500
7 Zone PERIMETER_BOT_ZN_2 1.1500
8 Zone PERIMETER_BOT_ZN_1 1.1500
9 Zone PERIMETER_BOT_ZN_4 1.1500
10 Zone PERIMETER_MID_ZN_3 1.1500
11 Zone PERIMETER_MID_ZN_2 1.1500
12 Zone PERIMETER_MID_ZN_1 1.1500
13 Zone PERIMETER_MID_ZN_4 1.1500
14 Zone PERIMETER_TOP_ZN_3 1.1500
15 Zone PERIMETER_TOP_ZN_2 1.1500
16 Zone PERIMETER_TOP_ZN_1 1.1500
17 Zone PERIMETER_TOP_ZN_4 1.1500
18 Zone DATACENTER_BOT_ZN_6 1.1500
19 Zone DATACENTER_MID_ZN_6 1.1500
20 Zone DATACENTER_TOP_ZN_6 1.1500
21 Zone DATACENTER_BASEMENT_ZN_6 1.1500


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 86066.67921 98976.68109 6.52081 7.49894 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 20.92400 1.27099E-002 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 89147.73353 102519.89356 6.75340 7.76641 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 20.92400 1.27099E-002 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 6669.69577 8337.11972 0.50008 1.07782 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 842087.61326 968400.75525 63.77870 73.34551 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 20.92400 1.27099E-002 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 307786.43100 384733.03875 22.98756 28.73446 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 91268.72696 104959.03600 6.97531 8.02161 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 29.97600 1.27256E-002 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 102035.21924 127544.02406 7.72348 9.65435 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 15115.92654 17383.31552 1.15528 1.32857 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 30.10000 1.27259E-002 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 18228.06644 22785.08306 1.38224 1.72780 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 22317.05974 25664.61870 1.70562 1.96146 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:40:00 22.49467 1.27126E-002 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 12346.29514 15432.86892 0.93639 1.17048 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 27638.43039 31784.19495 2.11232 2.42917 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 29.68667 1.27251E-002 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 20091.85416 25114.81770 1.52406 1.90507 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 26863.10956 30892.57599 2.05306 2.36101 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 28.15733 1.27224E-002 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 10846.14187 13557.67734 0.82221 1.02776 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 143125.00631 164593.75726 10.93922 12.58010 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.10000 1.27259E-002 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 241771.81788 302214.77235 18.34877 22.93596 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 238019.69863 273722.65342 18.19188 20.92066 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:10:00 23.63133 1.27146E-002 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 160649.66528 200812.08159 12.19314 15.24142 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 282344.24295 324695.87939 21.57968 24.81663 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 29.79000 1.27253E-002 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 247109.06706 308886.33383 18.75497 23.44371 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 256173.29432 294599.28847 19.57934 22.51624 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 27.95067 1.27221E-002 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 160490.28304 200612.85380 12.18115 15.22644 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 17223.45463 19806.97282 1.31643 1.51389 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 30.10000 1.27259E-002 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 32249.86864 40312.33580 2.44900 3.06125 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 23850.09052 27427.60409 1.82290 2.09633 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 24.33400 1.27158E-002 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 21262.36936 26577.96170 1.61469 2.01837 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 30998.87774 35648.70940 2.36929 2.72469 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 29.89333 1.27255E-002 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 32810.00667 41012.50834 2.49162 3.11453 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 27443.83921 31560.41510 2.09757 2.41220 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 27.95067 1.27221E-002 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 21541.92895 26927.41119 1.63598 2.04498 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70000 1.83376E-004 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 9273.43215 10664.44697 0.70873 0.81503 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 24.80933 1.27166E-002 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 05:30:00 -32.70000 1.83376E-004 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 89524.20294 102952.83338 6.84194 7.86823 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 24.80933 1.27166E-002 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -32.70000 1.83376E-004 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 9192.19894 10571.02878 0.70252 0.80789 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 24.80933 1.27166E-002 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 05:30:00 -32.70000 1.83376E-004 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 374133.82275 430253.89616 28.59565 32.88500 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 25.26400 1.27174E-002 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 13:20:00 -32.70000 1.83376E-004 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 183951.81 13.16452 13.16452 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 107240.73 6.90893 6.90893 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
3 VAV_MID WITH REHEAT Cooling Sensible 1718467.76 122.27455 122.27455 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 1068709.57 105.58199 105.58199 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:00:00
5 VAV_TOP WITH REHEAT Cooling Sensible 207559.62 15.01877 15.01877 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 101782.47 19.89347 19.89347 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:00:00
7 CAV_BAS Cooling Sensible 93999.94 7.49894 7.49894 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CAV_BAS Heating Sensible 90190.82 1.20016 1.20016 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 424271.39 32.88500 32.88500 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 24252.82 0.33839 0.33839 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 10459.85 0.81503 0.81503 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 1120.38 1.56323E-002 1.56323E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 100963.97 7.86823 7.86823 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 11203.80 0.15632 0.15632 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 10367.88 0.80789 0.80789 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 1120.38 1.56323E-002 1.56323E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:NoReheat BASEMENT PSZ-VAV DIFFUSER Design Size Maximum Air Flow Rate [m3/s] 7.49894
2 AirTerminal:SingleDuct:VAV:NoReheat BASEMENT PSZ-VAV DIFFUSER Design Size Constant Minimum Air Flow Fraction 0.28243
3 AirTerminal:SingleDuct:VAV:NoReheat BASEMENT PSZ-VAV DIFFUSER User-Specified Constant Minimum Air Flow Fraction 0.30000
4 AirTerminal:SingleDuct:VAV:NoReheat BASEMENT PSZ-VAV DIFFUSER Design Size Minimum Air Flow Rate [m3/s] 2.24968
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 7.76641
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24491
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.32992
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.65308
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.55570E-003
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.67476E-004
13 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.32992
14 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
15 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
16 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 30574.13112
17 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.67476E-004
18 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 640.20865
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 73.34551
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.25933
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 22.00365
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.69154
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.46919E-003
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.76502E-003
27 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 28.73446
28 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
29 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
30 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 658977.34574
31 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.76502E-003
32 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 15430.05203
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.65435
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19701
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.89631
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52537
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.93387E-003
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.92191E-003
41 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.65435
42 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
43 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
44 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 219686.05355
45 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.92191E-003
46 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 5132.78404
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.72780
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13822
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.51834
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.36859
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.75642E-003
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.43563E-004
55 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.72780
56 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
57 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
58 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 39271.36226
59 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.43563E-004
60 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 917.25211
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.96146
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.84646E-002
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.58844
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.85570E-003
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.32721E-004
69 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.17048
70 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
71 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
72 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 26601.41045
73 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.32721E-004
74 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 621.30537
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.42917
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.83157E-002
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.72875
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.87527E-003
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.78745E-004
83 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.90507
84 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
85 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
86 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 43292.91227
87 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.78745E-004
88 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1011.13267
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.36101
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.51860E-002
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.70830
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.84481E-003
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.04399E-004
97 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.02776
98 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
99 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
100 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 23364.06798
101 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.04399E-004
102 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 545.73528
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 22.93596
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10412
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 6.88079
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.65907E-003
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.55810E-003
111 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 22.93596
112 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
113 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
114 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 521019.09837
115 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.55810E-003
116 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 12167.40658
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 20.92066
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.17902E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.02881E-003
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 15.24142
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 346211.42739
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.02881E-003
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 8084.99999
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 24.81663
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.62362E-002
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 7.44499
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.95901E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.65886E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 23.44371
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 532536.00096
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.65886E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 12436.25037
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 22.51624
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.83529E-002
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 6.75487
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.57401E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.02581E-003
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 15.22644
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 345869.13155
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.02581E-003
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 8076.99445
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.06125
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.80140E-002
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.91838
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.88374E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.08156E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.06125
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 69515.92094
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.08156E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1623.25469
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.09633
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.34163E-002
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.62890
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.18958E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.00963E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.01837
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 45832.53754
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.00963E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1070.22017
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.11453
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.66813E-002
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.93436
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.96862E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.18728E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.11453
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 70724.46291
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.18728E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1651.46732
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.41220
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.38027E-002
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.72366
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.97153E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.06242E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.04498
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 46435.91800
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.06242E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1084.30383
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.81503
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 7.86823
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.80789
215 AirTerminal:SingleDuct:VAV:NoReheat DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER Design Size Maximum Air Flow Rate [m3/s] 32.88500
216 AirTerminal:SingleDuct:VAV:NoReheat DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER Design Size Constant Minimum Air Flow Fraction 1.81592E-002
217 AirTerminal:SingleDuct:VAV:NoReheat DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER User-Specified Constant Minimum Air Flow Fraction 0.50000
218 AirTerminal:SingleDuct:VAV:NoReheat DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER Design Size Minimum Air Flow Rate [m3/s] 16.44250
219 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 8.12293
220 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.87376
221 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 16.24586
222 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 6.90893
223 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 13.16452
224 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 13.16452
225 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
226 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.52481
227 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 82.26750
228 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 49.36050
229 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 164.53500
230 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 105.58199
231 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 122.27455
232 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 122.27455
233 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
234 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.86348
235 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 10.16933
236 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 6.10160
237 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 20.33866
238 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 19.89347
239 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 15.01877
240 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 19.89347
241 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
242 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 1.00000
243 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.24968
244 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.24968
245 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 7.49894
246 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 2.24968
247 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 7.49894
248 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 7.49894
249 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
250 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 0.30000
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 16.44250
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 16.44250
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 32.88500
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 16.44250
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 32.88500
256 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 32.88500
257 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
258 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.50000
259 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.81503
260 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.81503
261 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.81503
262 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.81503
263 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.81503
264 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.81503
265 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
266 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
267 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 7.86823
268 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 7.86823
269 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 7.86823
270 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 7.86823
271 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 7.86823
272 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 7.86823
273 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
274 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
275 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.80789
276 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.80789
277 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.80789
278 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.80789
279 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.80789
280 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.80789
281 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
282 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
283 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 13.16452
284 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 122.27455
285 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 19.89347
286 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 7.49894
287 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 32.88500
288 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.81503
289 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 7.86823
290 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.80789
291 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 13.16452
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 24.93972
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.03582
295 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 9.41841E-003
296 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
297 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 251110.39998
298 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 8.96908E-003
299 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 13.16452
300 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 94972.66125
301 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.30862E-004
302 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1525.15858
303 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 13.16452
304 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 8.96908E-003
305 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 5.30924E-005
306 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 8.30862E-004
307 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 122.27455
308 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.01187
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.03616
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 9.52020E-003
312 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
313 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 2379307.07353
314 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 8.49833E-002
315 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 122.27455
316 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 960493.12055
317 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.40281E-003
318 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 15280.33789
319 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 122.27455
320 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 8.49833E-002
321 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 5.60334E-006
322 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 8.40281E-003
323 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 19.89347
324 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 24.82444
325 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
326 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.06086
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 9.35431E-003
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
329 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 372423.84485
330 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.33021E-002
331 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 19.89347
332 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 84131.47296
333 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 7.36019E-004
334 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1419.04768
335 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 19.89347
336 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.33021E-002
337 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 3.57981E-005
338 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 7.36019E-004
339 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 7.49894
340 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
341 AirLoopHVAC:UnitarySystem CAV_BAS_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 7.49894
342 AirLoopHVAC:UnitarySystem CAV_BAS_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 7.49894
343 AirLoopHVAC:UnitarySystem CAV_BAS_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 7.49894
344 AirLoopHVAC:UnitarySystem CAV_BAS_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 2.24968
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 24.78964
346 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
347 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.02654
348 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 9.60108E-003
349 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
350 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 141841.04758
351 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.06623E-003
352 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 7.49894
353 AirLoopHVAC:UnitarySystem CAV_BAS_UNITARY_PACKAGE_DX Design Size Nominal Cooling Capacity [W] 141841.04758
354 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 129267.29103
355 Coil:Heating:Water CAV_BAS HEATING COIL User-Specified Rated Capacity [W] 100000.00000
356 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.74844E-004
357 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 2622.29956
358 AirLoopHVAC:UnitarySystem CAV_BAS_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 100000.00000
359 AirLoopHVAC:UnitarySystem CAV_BAS_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
360 AirLoopHVAC:UnitarySystem CAV_BAS_UNITARY_PACKAGE_DX Design Size Minimum Supply Air Temperature [C] 5.33423
361 AirLoopHVAC:UnitarySystem CAV_BAS_UNITARY_PACKAGE_DX User-Specified Minimum Supply Air Temperature [C] 12.88890
362 AirLoopHVAC:UnitarySystem CAV_BAS_UNITARY_PACKAGE_DX User-Specified Maximum Supply Air Temperature [C] 32.11110
363 Fan:VariableVolume CAV_BAS SZVAV FAN Design Size Maximum Flow Rate [m3/s] 7.49894
364 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 32.88500
365 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
366 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 32.88500
367 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 32.88500
368 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 32.88500
369 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 16.44250
370 Coil:Cooling:Water AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.02990
371 Coil:Cooling:Water AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
372 Coil:Cooling:Water AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Design Outlet Air Temperature [C] 15.00754
373 Coil:Cooling:Water AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57607E-003
374 Coil:Cooling:Water AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
375 Coil:Cooling:Water AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Design Coil Load [W] 456895.96598
376 Coil:Cooling:Water AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.63193E-002
377 Coil:Cooling:Water AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Design Air Flow Rate [m3/s] 32.88500
378 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX Design Size Nominal Cooling Capacity [W] 456895.96598
379 Coil:Heating:Water AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Capacity [W] 567830.08062
380 Coil:Heating:Water AIRLOOP DATACENTER BASEMENT HEATING COIL User-Specified Rated Capacity [W] 100000.00000
381 Coil:Heating:Water AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.74844E-004
382 Coil:Heating:Water AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size U-Factor Times Area Value [W/K] 2622.29956
383 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 100000.00000
384 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
385 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX User-Specified Minimum Supply Air Temperature [C] 15.88890
386 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX User-Specified Maximum Supply Air Temperature [C] 29.11110
387 Fan:VariableVolume AIRLOOP DATACENTER BASEMENT SYS11 FAN Design Size Maximum Flow Rate [m3/s] 32.88500
388 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 3.04012E-004
389 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
390 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
391 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
392 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.81503
393 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
394 Fan:SystemModel AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 0.81503
395 Fan:SystemModel AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 1401.56406
396 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 0.81503
397 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 0.81503
398 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 0.81503
399 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.81503
400 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER BOT COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 0.81503
401 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER BOT COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.40752
402 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER BOT COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.54335
403 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER BOT COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 13491.71000
404 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER BOT COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 6745.85500
405 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER BOT COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.80066
406 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER BOT COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.80066
407 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 13491.71000
408 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 28103.34539
409 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 29.11000
410 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
411 Coil:Heating:Fuel AIRLOOP DATACENTER BOT HEATING COIL Design Size Nominal Capacity [W] 28103.34539
412 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 7.86823
413 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
414 Fan:SystemModel AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 7.86823
415 Fan:SystemModel AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 13530.51476
416 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 7.86823
417 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 7.86823
418 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 7.86823
419 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 7.86823
420 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER MID COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 7.86823
421 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER MID COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 3.93411
422 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER MID COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 5.24549
423 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER MID COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 130247.14000
424 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER MID COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 65123.57000
425 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER MID COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.80066
426 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER MID COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.80066
427 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 130247.14000
428 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 271511.15554
429 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 29.11000
430 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
431 Coil:Heating:Fuel AIRLOOP DATACENTER MID HEATING COIL Design Size Nominal Capacity [W] 271511.15554
432 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.80789
433 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
434 Fan:SystemModel AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 0.80789
435 Fan:SystemModel AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 1389.28704
436 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 0.80789
437 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 0.80789
438 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 0.80789
439 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.80789
440 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER TOP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 0.80789
441 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER TOP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.40395
442 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER TOP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.53859
443 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER TOP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 13373.52000
444 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER TOP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 6686.76000
445 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER TOP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.80066
446 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER TOP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.80066
447 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 13373.52000
448 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 27862.36587
449 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 29.11000
450 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
451 Coil:Heating:Fuel AIRLOOP DATACENTER TOP HEATING COIL Design Size Nominal Capacity [W] 27862.36587
452 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 0.12864
453 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 26507.96461
454 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 0.12864
455 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 15.43680
456 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 0.12864
457 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 0.12864
458 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 539966.76640
459 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 6.67000
460 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 3.81389E-002
461 PlantLoop HEATSYS1 Plant Loop Volume [m3] 4.57667
462 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 3.81389E-002
463 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 11485.75785
464 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
465 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 4359509.03576
466 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 4359509.04000
467 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 3.81389E-002
468 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 0.12864
469 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 15.43680
470 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Flow Rate [m3/s] 6.43200E-002
471 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Power Consumption [W] 12234.64126
472 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Flow Rate [m3/s] 6.43200E-002
473 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Power Consumption [W] 12234.64126
474 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 0.12864
475 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 6.49100E-002
476 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1817307.14988
477 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1817360.44500
478 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 9.10797E-002
479 Chiller:Electric:EIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 0.12864
480 Chiller:Electric:EIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 6.49100E-002
481 Chiller:Electric:EIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1817307.14988
482 Chiller:Electric:EIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1817360.44500
483 Chiller:Electric:EIR COOLSYS1 CHILLER2 Design Size Reference Condenser Fluid Flow Rate [m3/s] 9.10797E-002
484 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
485 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
486 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
487 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 56.20530
488 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
489 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.18216
490 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 21.85912
491 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.18216
492 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 63519.19662
493 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 76.60573
494 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 2176855.79541
495 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 15.32115
496 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 272106.97443
497 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 76.60573
498 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 2176855.79541
499 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 15.32115
500 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 272106.97443


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 29023.99
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 625183.04
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 208421.84
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 37257.81
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 25237.48
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 41073.17
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 22166.12
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 494305.30
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 328460.42
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 505231.72
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 328135.68
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 65951.71
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 43482.62
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 67098.29
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 44055.07
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 69376.55
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 687594.87
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 67939.16
19 Coil:Heating:Water CAV_BAS HEATING COIL 94839.37
20 Coil:Heating:Water AIRLOOP DATACENTER BASEMENT HEATING COIL 94839.37


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 315932.54 218988.53 96944.01 0.69 39924.89 404.94
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2958482.28 2044131.15 914351.13 0.69 372641.75 3779.54
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 473428.07 329202.78 144225.28 0.70 59889.63 607.43
4 Coil:Cooling:Water CAV_BAS COOLING COIL 181811.34 125742.77 56068.57 0.69 23726.85 240.65
5 Coil:Cooling:Water AIRLOOP DATACENTER BASEMENT COOLING COIL 586444.53 441693.20 144751.33 0.75 58409.46 592.42


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER BOT COOLING COIL 12853.0     9.16 9.16  
2 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER MID COOLING COIL 124080.7     10.40 10.40  
3 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER TOP COOLING COIL 12740.4     9.16 9.16  


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 6.37 21.74
2 Chiller:Electric:EIR COOLSYS1 CHILLER2 6.37 21.74


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.419 0.394   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.384 0.363   76.91 200.61 76.91 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.49 N/A 3.241 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.49 N/A 3.241 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.49 N/A 3.241 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.49 N/A 3.241 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.49 N/A 3.241 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.384 0.363   52.57 133.74 52.57 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_EAST_0.49 N/A 3.241 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_EAST_0.49 N/A 3.241 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_EAST_0.49 N/A 3.241 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.384 0.363   76.91 200.61 76.91 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.49 N/A 3.241 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.49 N/A 3.241 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.49 N/A 3.241 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.49 N/A 3.241 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.49 N/A 3.241 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.384 0.363   52.57 133.74 52.57 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_WEST_0.49 N/A 3.241 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_WEST_0.49 N/A 3.241 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_WEST_0.49 N/A 3.241 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.384 0.363   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.49 N/A 3.241 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.384 0.363   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_EAST_0.49 N/A 3.241 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.384 0.363   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.49 N/A 3.241 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.384 0.363   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_WEST_0.49 N/A 3.241 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.384 0.363   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.49 N/A 3.241 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.384 0.363   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_EAST_0.49 N/A 3.241 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.384 0.363   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.49 N/A 3.241 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.384 0.363   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_WEST_0.49 N/A 3.241 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.384 0.363   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.384 0.363   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.384 0.363   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.384 0.363   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.384 0.363   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.384 0.363   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.384 0.363   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.384 0.363   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.384 0.363   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.384 0.363   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.384 0.363   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.384 0.363   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.419 0.394   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 2.4532538422E-003 1.5818918593E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 0.1336546512 9.2693420926E-002 Pass Pass 0.4864254472 0.4979982157 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 3.1382955923E-002 2.2255870643E-002 Pass Pass 0.4873288802 0.4957581681 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 0.2370609745 0.2572844817 Pass Pass 0.5928400565 0.5921987347 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 0.5010203415 0.5091185729 Pass Pass 0.6277636427 0.5467037147 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 0.4512683582 0.5182552036 Pass Pass 2.4190211479 21.4914046937 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 0.4580440523 0.4851291879 Pass Pass 1.8543323998 11.6991999823 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 0.2420030670 0.2783017540 Pass Pass 0.6482394917 0.8493228651 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 1.1185153919 1.0763747820 Pass Pass 0.6037649057 0.5336166440 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.9880211524 1.0340540171 Pass Pass 0.6155129681 0.5520288512 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.7232433463 0.8395326649 Pass Pass 0.6284920588 0.5888412974 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.9350710120 1.0013415924 Pass Pass 0.6292565304 0.5635302373 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 1.4290431753 1.3874518574 Pass Pass 0.5739932964 0.5330484245 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 1.3016858941 1.3188759512 Pass Pass 0.5834486341 0.5386958121 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.9612456452 1.1435969219 Pass Pass 0.6176117673 0.6621785903 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 1.2557267591 1.3024106925 Pass Pass 0.5907764190 0.5359358906 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 3.6305891749E-002 3.0803624980E-002 Pass Pass 0.6759716488 0.8610150771 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 0.1049030813 7.2972685017E-002 Pass Pass 0.4807659078 0.4846504100 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 0.4827283677 0.3916625225 Pass Pass 0.4885526897 0.4942412084 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 2.6547290364E-003 6.5773364106E-003 Pass Pass 0.1131345707 0.6654367782 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 3.9066834645E-002 5.0855796842E-002 Pass Pass 7.8135281518E-003 1.2968803847E-002 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 4.7934904822E-002 5.2036633351E-002 Pass Pass 1.0000040007E-002 1.3545871481E-002 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 3.8054466361E-002 2.6747275582E-002 Pass Pass 2.0195297023E-003 1.4277152955E-003 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 6414.33 293.55 0.00 32219.05 14269.05 53195.99



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB -32.70 0.00 -32.70 Wetbulb [C] 2.40 210.00
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 30.10 12.40 21.10 Wetbulb [C] 4.70 200.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 12.00 13      
Apr 16.00 23      
May 0.00 0      
Jun 190.00 53      
Jul 136.00 41      
Aug 87.00 42      
Sep 0.00 0      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.399 0.419 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.399 0.419 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.363 0.384 200.61 76.91 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.363 0.384 133.74 52.57 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.363 0.384 200.61 76.91 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.363 0.384 133.74 52.57 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.363 0.384 2006.06 847.11 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.363 0.384 1337.37 564.74 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.363 0.384 2006.06 847.11 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.363 0.384 1337.37 564.74 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.363 0.384 200.61 84.71 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.363 0.384 133.74 56.47 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.363 0.384 200.61 84.71 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.363 0.384 133.74 56.47 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.363 0.384 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 0.363 0.384 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.363 0.384 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.363 0.384 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.363 0.384 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.363 0.384 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.363 0.384 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.363 0.384 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.363 0.384 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.363 0.384 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.363 0.384 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.363 0.384 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.30 0.358 0.376 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.399 0.419 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.399 0.419 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.57_SHGC_NORTH_0.49   23.18 0.00 0.00 23.18 23.18 3.241 0.491 0.541             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.57_SHGC_NORTH_0.49   23.18 0.00 0.00 23.18 23.18 3.241 0.491 0.541             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.57_SHGC_NORTH_0.49   23.18 0.00 0.00 23.18 23.18 3.241 0.491 0.541             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.57_SHGC_NORTH_0.49   23.18 0.00 0.00 23.18 23.18 3.241 0.491 0.541             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.57_SHGC_NORTH_0.49   23.18 0.00 0.00 23.18 23.18 3.241 0.491 0.541             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.57_SHGC_EAST_0.49   25.75 0.00 0.00 25.75 25.75 3.241 0.491 0.541             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.57_SHGC_EAST_0.49   25.75 0.00 0.00 25.75 25.75 3.241 0.491 0.541             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.57_SHGC_EAST_0.49   25.75 0.00 0.00 25.75 25.75 3.241 0.491 0.541             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.57_SHGC_SOUTH_0.49   23.18 0.00 0.00 23.18 23.18 3.241 0.491 0.541             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.57_SHGC_SOUTH_0.49   23.18 0.00 0.00 23.18 23.18 3.241 0.491 0.541             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.57_SHGC_SOUTH_0.49   23.18 0.00 0.00 23.18 23.18 3.241 0.491 0.541             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.57_SHGC_SOUTH_0.49   23.18 0.00 0.00 23.18 23.18 3.241 0.491 0.541             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.57_SHGC_SOUTH_0.49   23.18 0.00 0.00 23.18 23.18 3.241 0.491 0.541             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.57_SHGC_WEST_0.49   25.75 0.00 0.00 25.75 25.75 3.241 0.491 0.541             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.57_SHGC_WEST_0.49   25.75 0.00 0.00 25.75 25.75 3.241 0.491 0.541             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.57_SHGC_WEST_0.49   25.75 0.00 0.00 25.75 25.75 3.241 0.491 0.541             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.57_SHGC_NORTH_0.49   115.90 0.00 0.00 115.90 1158.95 3.241 0.491 0.541             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.57_SHGC_EAST_0.49   77.26 0.00 0.00 77.26 772.63 3.241 0.491 0.541             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.57_SHGC_SOUTH_0.49   115.90 0.00 0.00 115.90 1158.95 3.241 0.491 0.541             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.57_SHGC_WEST_0.49   77.26 0.00 0.00 77.26 772.63 3.241 0.491 0.541             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.57_SHGC_NORTH_0.49   115.90 0.00 0.00 115.90 115.90 3.241 0.491 0.541             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.57_SHGC_EAST_0.49   77.26 0.00 0.00 77.26 77.26 3.241 0.491 0.541             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.57_SHGC_SOUTH_0.49   115.90 0.00 0.00 115.90 115.90 3.241 0.491 0.541             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.57_SHGC_WEST_0.49   77.26 0.00 0.00 77.26 77.26 3.241 0.491 0.541             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             4635.80 3.241 0.491 0.541                      
North Total or Average             1390.74 3.241 0.491 0.541                      
Non-North Total or Average             3245.06 3.241 0.491 0.541                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 11.6510 2779.43 32383.10 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 333.79
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 11.6510 2496.12 29082.30 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 299.77
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 11.6510 24961.20 290822.99 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 2997.66
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 11.6510 2496.12 29082.30 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 299.77
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 11.6510 313.41 3651.57 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 37.64
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 11.6510 201.98 2353.21 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 24.26
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 11.6510 313.42 3651.65 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 37.64
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 11.6510 201.98 2353.21 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 24.26
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 11.6510 3134.13 36515.73 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 376.39
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 11.6510 2019.75 23532.12 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 242.56
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 11.6510 3134.20 36516.53 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 376.39
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 11.6510 2019.75 23532.12 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 242.56
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 11.6510 313.41 3651.57 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 37.64
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 11.6510 201.98 2353.21 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 24.26
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 11.6510 313.42 3651.65 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 37.64
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 11.6510 201.98 2353.21 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 24.26
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 11.6510 783.68 9130.65 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 94.11
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 22.3674 36.20 809.76 LightsWired LTG_SCH_DATACENTER 56.37 168.00 54.91 0.0000 Y 8.35
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 22.3674 362.03 8097.60 LightsWired LTG_SCH_DATACENTER 56.37 168.00 54.91 0.0000 Y 83.47
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 22.3674 36.20 809.76 LightsWired LTG_SCH_DATACENTER 56.37 168.00 54.91 0.0000 Y 8.35
Interior Lighting Total       11.7515 46320.38 544334.28               1723.61


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS 64082.80 AstronomicalClock -   83.52 83.52 1004.65
Exterior Lighting Total 64082.80           1004.65



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 3592194.17          
HEATSYS1 BOILER Boiler:HotWater 4359509.04 0.79        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 1817360.45 6.11 1808492.71 6.08 6.37 21.74
COOLSYS1 CHILLER2 Chiller:Electric:EIR 1817360.45 6.11 1808492.71 6.08 6.37 21.74
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 2176855.80          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 2176855.80          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 251110.40 315932.54 218988.53 96944.01 0.69 - 39924.89 404.94
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 2379307.07 2958482.28 2044131.15 914351.13 0.69 - 372641.75 3779.54
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 372423.84 473428.07 329202.78 144225.28 0.70 - 59889.63 607.43
CAV_BAS COOLING COIL Coil:Cooling:Water 141841.05 181811.34 125742.77 56068.57 0.69 - 23726.85 240.65
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:Water 456895.97 586444.53 441693.20 144751.33 0.75 - 58409.46 592.42
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:DX:MultiSpeed   13491.71 10802.27 2689.44 0.80 3.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:DX:MultiSpeed   130247.14 104283.68 25963.46 0.80 3.50    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:DX:MultiSpeed   13373.52 10707.64 2665.88 0.80 3.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
AIRLOOP DATACENTER BOT COOLING COIL   12853.0     9.16 9.16  
AIRLOOP DATACENTER MID COOLING COIL   124080.7     10.40 10.40  
AIRLOOP DATACENTER TOP COOLING COIL   12740.4     9.16 9.16  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:DX:MultiSpeed                
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:DX:MultiSpeed                
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:DX:MultiSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 30574.13 29023.99 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 658977.35 625183.04 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 219686.05 208421.84 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 39271.36 37257.81 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 26601.41 25237.48 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 43292.91 41073.17 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 23364.07 22166.12 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 521019.10 494305.30 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 346211.43 328460.42 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 532536.00 505231.72 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 345869.13 328135.68 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 69515.92 65951.71 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 45832.54 43482.62 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 70724.46 67098.29 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 46435.92 44055.07 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 94972.66 69376.55 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 960493.12 687594.87 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 84131.47 67939.16 -
CAV_BAS HEATING COIL Coil:Heating:Water 100000.00 94839.37 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:Water 100000.00 94839.37 -
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:Fuel   28103.35 0.80
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:Fuel   271511.16 0.79
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:Fuel   27862.37 0.80
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1337.13 13.16 28778.99 2186.10 1.00 1.11 General INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1337.13 122.27 267304.78 2186.10 1.00 1.08 General INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.62 1337.13 19.89 42896.57 2156.31 1.00 1.12 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00
CAV_BAS SZVAV FAN Fan:VariableVolume 0.61 1337.13 7.50 16481.02 2197.78 1.00 1.13 General INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
AIRLOOP DATACENTER BASEMENT SYS11 FAN Fan:VariableVolume 0.61 637.69 32.88 34139.85 1038.16 1.00 1.19 General INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.56 966.87 0.82 1401.56 1719.64 1.00 1.34 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.56 966.87 7.87 13530.51 1719.64 1.00 1.08 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.56 966.87 0.81 1389.29 1719.64 1.00 1.34 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.83 0.128640 26507.96 206063.11 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.038139 11485.76 301156.09 0.90 General
COOLSYS1 CHILLER1 PUMP Pump:ConstantSpeed Intermittent 123258.43 0.064320 12234.64 190215.15 0.90 General
COOLSYS1 CHILLER2 PUMP Pump:ConstantSpeed Intermittent 123258.43 0.064320 12234.64 190215.15 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000440 56.21 127739.32 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 209234.68 0.182159 63519.20 348701.22 0.90 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 1.00 13.34 0.74



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 86066.68 98976.68 35.61 6.521 7.499 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00890 20.92 0.01271 1.200 0.00
CORE_BOTTOM 89147.73 102519.89 41.07 6.753 7.766 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00885 20.92 0.01271 1.078 0.00
CORE_MID 842087.61 968400.76 387.96 63.779 73.346 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00887 20.92 0.01271 10.778 0.00
CORE_TOP 91268.73 104959.04 42.05 6.975 8.022 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 24.00 0.00883 29.98 0.01273 1.078 0.00
PERIMETER_BOT_ZN_3 15115.93 17383.32 55.46 1.155 1.329 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 24.00 24.00 0.00884 30.10 0.01273 0.135 0.00
PERIMETER_BOT_ZN_2 22317.06 25664.62 127.07 1.706 1.961 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:40:00 24.00 24.00 0.00865 22.49 0.01271 0.087 0.00
PERIMETER_BOT_ZN_1 27638.43 31784.19 101.41 2.112 2.429 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 24.00 24.00 0.00869 29.69 0.01273 0.135 0.00
PERIMETER_BOT_ZN_4 26863.11 30892.58 152.95 2.053 2.361 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 24.00 24.00 0.00863 28.16 0.01272 0.087 0.00
PERIMETER_MID_ZN_3 143125.01 164593.76 525.17 10.939 12.580 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00898 30.10 0.01273 1.353 0.00
PERIMETER_MID_ZN_2 238019.70 273722.65 1355.23 18.192 20.921 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:10:00 24.00 24.00 0.00870 23.63 0.01271 0.872 0.00
PERIMETER_MID_ZN_1 282344.24 324695.88 1035.98 21.580 24.817 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 24.00 24.00 0.00875 29.79 0.01273 1.353 0.00
PERIMETER_MID_ZN_4 256173.29 294599.29 1458.59 19.579 22.516 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 24.00 24.00 0.00868 27.95 0.01272 0.872 0.00
PERIMETER_TOP_ZN_3 17223.45 19806.97 63.20 1.316 1.514 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 24.00 0.00894 30.10 0.01273 0.135 0.00
PERIMETER_TOP_ZN_2 23850.09 27427.60 135.80 1.823 2.096 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 24.00 24.00 0.00872 24.33 0.01272 0.087 0.00
PERIMETER_TOP_ZN_1 30998.88 35648.71 113.74 2.369 2.725 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 24.00 24.00 0.00875 29.89 0.01273 0.135 0.00
PERIMETER_TOP_ZN_4 27443.84 31560.42 156.26 2.098 2.412 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 24.00 24.00 0.00869 27.95 0.01272 0.087 0.00
DATACENTER_BOT_ZN_6 9273.43 10664.45 294.58 0.709 0.815 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 27.00 27.00 0.00856 24.81 0.01272 0.016 0.00
DATACENTER_MID_ZN_6 89524.20 102952.83 2843.79 6.842 7.868 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 27.00 27.00 0.00856 24.81 0.01272 0.156 0.00
DATACENTER_TOP_ZN_6 9192.20 10571.03 292.00 0.703 0.808 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 27.00 27.00 0.00856 24.81 0.01272 0.016 0.00
DATACENTER_BASEMENT_ZN_6 374133.82 430253.90 549.02 28.596 32.885 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.00 27.00 0.00853 25.26 0.01272 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 22.48 0.00018 -32.70 0.00018 1.200 0.00
CORE_BOTTOM 6669.70 8337.12 3.34 0.500 1.078 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -32.70 0.00018 1.078 0.00
CORE_MID 307786.43 384733.04 154.13 22.988 28.734 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -32.70 0.00018 10.778 0.00
CORE_TOP 102035.22 127544.02 51.10 7.723 9.654 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -32.70 0.00018 1.078 0.00
PERIMETER_BOT_ZN_3 18228.07 22785.08 72.70 1.382 1.728 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00790 -32.70 0.00018 0.135 0.00
PERIMETER_BOT_ZN_2 12346.30 15432.87 76.41 0.936 1.170 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00790 -32.70 0.00018 0.087 0.00
PERIMETER_BOT_ZN_1 20091.85 25114.82 80.13 1.524 1.905 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00791 -32.70 0.00018 0.135 0.00
PERIMETER_BOT_ZN_4 10846.14 13557.68 67.13 0.822 1.028 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00789 -32.70 0.00018 0.087 0.00
PERIMETER_MID_ZN_3 241771.82 302214.77 964.27 18.349 22.936 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00783 -32.70 0.00018 1.353 0.00
PERIMETER_MID_ZN_2 160649.67 200812.08 994.24 12.193 15.241 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00783 -32.70 0.00018 0.872 0.00
PERIMETER_MID_ZN_1 247109.07 308886.33 985.54 18.755 23.444 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00783 -32.70 0.00018 1.353 0.00
PERIMETER_MID_ZN_4 160490.28 200612.85 993.26 12.181 15.226 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00783 -32.70 0.00018 0.872 0.00
PERIMETER_TOP_ZN_3 32249.87 40312.34 128.62 2.449 3.061 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00784 -32.70 0.00018 0.135 0.00
PERIMETER_TOP_ZN_2 21262.37 26577.96 131.59 1.615 2.018 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00784 -32.70 0.00018 0.087 0.00
PERIMETER_TOP_ZN_1 32810.01 41012.51 130.85 2.492 3.115 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00784 -32.70 0.00018 0.135 0.00
PERIMETER_TOP_ZN_4 21541.93 26927.41 133.32 1.636 2.045 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00784 -32.70 0.00018 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 05:30:00 18.00 24.11 0.00099 -32.70 0.00018 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 22.17 0.00099 -32.70 0.00018 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 05:30:00 18.00 18.49 0.00098 -32.70 0.00018 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 13:20:00 18.00 27.00 0.00850 -32.70 0.00018 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 13.16 13.16 6.91 6.91 13.1645 6.9089 13.1645 0.5248 0.3000
VAV_MID WITH REHEAT 122.27 122.27 105.58 105.58 122.2745 105.5820 122.2745 0.8635 0.3000
VAV_TOP WITH REHEAT 15.02 15.02 19.89 19.89 15.0188 19.8935 19.8935 1.0000 0.3000
CAV_BAS 7.50 7.50 1.20 1.20 7.4989 2.2497 7.4989 0.3000 1.0000
AIRLOOP DATACENTER BASEMENT 32.88 32.88 0.34 0.34 32.8850 16.4425 32.8850 0.5000 1.0000
AIRLOOP DATACENTER BOT 0.82 0.82 0.02 0.02 0.8150 0.8150 0.8150 1.0000 1.0000
AIRLOOP DATACENTER MID 7.87 7.87 0.16 0.16 7.8682 7.8682 7.8682 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.81 0.81 0.02 0.02 0.8079 0.8079 0.8079 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 30574.131 30574.131 2.329924 0.00026748 640.209 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 30574.13 30574.13 2.329924 12.89 11.26 0.00800000 32.11 18.27 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.00 0.00799998 49.5594 8337.12 0.00 30724.45 30724.45
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 658977.346 658977.346 28.734456 0.00576502 15430.052 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 658977.35 658977.35 28.734456 12.89 11.26 0.00800000 32.11 18.27 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.00 0.00800000 49.5595 384733.04 0.00 661995.63 661995.63
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 219686.054 219686.054 9.654352 0.00192191 5132.784 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 219686.05 218364.03 9.654352 12.89 11.26 0.00800000 32.11 18.27 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.00 0.00800000 49.5595 127544.02 0.00 220693.15 220693.15
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 39271.362 39271.362 1.727797 0.00034356 917.252 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 39271.36 39079.66 1.727797 12.89 11.26 0.00800000 32.11 18.27 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.00 0.00790137 48.9577 22785.08 0.00 39451.42 39451.42
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 26601.410 26601.410 1.170485 0.00023272 621.305 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 26601.41 26601.41 1.170485 12.89 11.26 0.00800000 32.11 18.27 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.00 0.00790286 48.9669 15432.87 0.00 26723.38 26723.38
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 43292.912 43292.912 1.905069 0.00037875 1011.133 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 43292.91 43292.91 1.905069 12.89 11.26 0.00800000 32.11 18.27 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.00 0.00791024 49.0119 25114.82 0.00 43491.41 43491.41
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 23364.068 23364.068 1.027757 0.00020440 545.735 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 23364.07 23364.07 1.027757 12.89 11.26 0.00800000 32.11 18.27 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.00 0.00788963 48.8859 13557.68 0.00 23471.19 23471.19
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 521019.098 521019.098 22.935964 0.00455810 12167.407 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 521019.10 518770.15 22.935964 12.89 11.26 0.00800000 32.11 18.27 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.00 0.00782651 48.5014 302214.77 0.00 523408.05 523408.05
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 346211.427 346211.427 15.241423 0.00302881 8085.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 346211.43 346211.43 15.241423 12.89 11.26 0.00800000 32.11 18.27 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.00 0.00782587 48.4975 200812.08 0.00 347798.87 347798.87
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 532536.001 532536.001 23.443712 0.00465886 12436.250 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 532536.00 532536.00 23.443712 12.89 11.26 0.00800000 32.11 18.27 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.00 0.00783016 48.5237 308886.33 0.00 534977.77 534977.77
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 345869.132 345869.132 15.226435 0.00302581 8076.994 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 345869.13 345869.13 15.226435 12.89 11.26 0.00800000 32.11 18.27 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.00 0.00782586 48.4975 200612.85 0.00 347455.00 347455.00
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 69515.921 69515.921 3.061252 0.00060816 1623.255 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 69515.92 69240.01 3.061252 12.89 11.26 0.00800000 32.11 18.27 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.00 0.00783749 48.5692 40312.34 0.00 69834.67 69834.67
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 45832.538 45832.538 2.018367 0.00040096 1070.220 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 45832.54 45832.54 2.018367 12.89 11.26 0.00800000 32.11 18.27 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.00 0.00783568 48.5582 26577.96 0.00 46042.70 46042.70
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 70724.463 70724.463 3.114526 0.00061873 1651.467 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 70724.46 70444.96 3.114526 12.89 11.26 0.00800000 32.11 18.27 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.00 0.00784023 48.5859 41012.51 0.00 71048.76 71048.76
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 46435.918 46435.918 2.044977 0.00040624 1084.304 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 46435.92 46435.92 2.044977 12.89 11.26 0.00800000 32.11 18.27 0.00800000 -32.70 0.00018338 -32.70 0.0000 21.00 0.00783796 48.5721 26927.41 0.00 46648.84 46648.84
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 251110.400 -999.000 13.164517 0.00896908 -999.000 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 251110.40 215746.53 13.164517 24.94 17.04 0.00941841 11.04 10.99 0.00850000 30.10 0.01272586 21.13 15.4240 24.00 0.00881523 45.4542 149782.76 0.00 259364.59 210528.39
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 94972.661 94972.661 3.949355 0.00083086 1525.159 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 94972.66 94972.66 3.949355 -7.85 -7.85 0.00387135 12.89 11.26 0.00800000 -32.70 0.00018338 -32.70 51.4135 18.79 0.00782839 55.6292 15036.87 0.00 83939.24 83939.24
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 2379307.074 -999.000 122.274549 0.08498333 -999.000 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 2379307.07 2014387.45 122.274549 25.01 17.15 0.00952020 11.04 10.99 0.00850000 30.10 0.01272586 21.13 16.6069 24.00 0.00888168 45.7927 1390901.36 0.00 2455773.44 1966952.66
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 960493.121 960493.121 36.682365 0.00840281 15280.338 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 960493.12 960493.12 36.682365 -9.69 -9.69 0.00355120 12.89 11.26 0.00800000 -32.70 0.00018338 -32.70 55.3563 18.61 0.00784356 56.3547 158503.38 0.00 831803.35 831803.35
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 372423.845 -999.000 19.893475 0.01330212 -999.000 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 372423.84 322800.34 19.893475 24.82 16.95 0.00935431 11.06 11.00 0.00850000 30.10 0.01272586 21.13 10.2069 24.00 0.00882636 45.5116 170633.07 0.00 384788.96 314963.85
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 84131.473 84131.473 5.968042 0.00073602 1419.048 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 84131.47 84131.47 5.968042 0.73 0.73 0.00512091 12.89 11.26 0.00800000 -32.70 0.00018338 -32.70 34.0229 16.76 0.00785590 63.4570 29434.96 0.00 82238.03 82238.03
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 141841.048 -999.000 7.498936 0.00506623 -999.000 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 141841.05 118336.30 7.498936 24.79 17.14 0.00960108 11.03 10.99 0.00850000 28.49 0.01272303 20.66 16.0044 24.00 0.00893341 46.0548 77505.03 0.00 150554.62 119036.65
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 100000.000 100000.000 3.170652 0.00087484 2622.300 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 100000.00 100000.00 3.170652 -5.23 -9.59 0.00018338 32.11 18.27 0.00800000 -32.70 0.00018338 -32.70 37.8520 22.59 0.00018338 1.0438 0.00 0.00 100072.50 100072.50
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:Water AirLoopHVAC AIRLOOP DATACENTER BASEMENT 456895.966 -999.000 32.884996 0.01631927 -999.000 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 456895.97 451554.48 32.884996 27.03 17.06 0.00857607 15.01 12.60 0.00850000 30.10 0.01272586 21.13 1.0290 27.00 0.00853287 36.8357 373651.11 0.00 488445.44 488445.44
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:Water AirLoopHVAC AIRLOOP DATACENTER BASEMENT 100000.000 100000.000 3.170652 0.00087484 2622.300 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 100000.00 100000.00 3.170652 -0.34 -0.34 0.00841442 29.11 17.29 0.00800000 -32.70 0.00018338 -32.70 10.6727 27.00 0.00850000 36.6913 0.00 0.00 100072.50 100072.50
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC AIRLOOP DATACENTER BOT 13491.710 10802.273 0.815030 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 6745.85 6600.78 0.543353 26.96 17.09 0.00864070 14.43 12.38 0.00850000 24.81 0.01271660 19.55 2.8770 27.00 0.00856100 36.9535 9273.43 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:Fuel AirLoopHVAC AIRLOOP DATACENTER BOT 28103.345 28103.345 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 28103.35 28103.35 0.815034 -0.63 -5.10 0.00096991 29.11 17.29 0.00800000 -32.70 0.00018338 -32.70 1.9180 24.77 0.00098529 4.9117 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC AIRLOOP DATACENTER MID 130247.140 104283.675 7.868230 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 65123.57 63674.57 5.245487 26.96 17.09 0.00864567 14.43 12.38 0.00850000 24.81 0.01271660 19.55 2.9802 27.00 0.00856315 36.9627 89524.20 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:Fuel AirLoopHVAC AIRLOOP DATACENTER MID 271511.156 271511.156 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 271511.16 271511.16 7.868230 -0.65 -5.12 0.00096939 29.11 17.29 0.00800000 -32.70 0.00018338 -32.70 1.9868 23.39 0.00098533 5.3374 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC AIRLOOP DATACENTER TOP 13373.520 10707.643 0.807890 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 6686.76 6541.62 0.538593 26.96 17.09 0.00864203 14.43 12.38 0.00850000 24.81 0.01271660 19.55 2.9024 27.00 0.00856163 36.9562 9192.20 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:Fuel AirLoopHVAC AIRLOOP DATACENTER TOP 27862.366 27862.366 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 27862.37 27862.37 0.807895 -0.63 -5.11 0.00096819 29.11 17.29 0.00800000 -32.70 0.00018338 -32.70 1.9349 20.78 0.00098367 6.2476 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 30574.131 30574.131 2.329924 0.00026748 640.209 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.13499627 54.44 82.22 27.78 4447245.89 0.6875 0.701321 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 30574.13 30574.13 1.0000 2.68855725 2.329924 12.89 11.26 0.00800000 33150.5 32.11 18.27 0.00800000 52751.6 0.26744855 60.00 32.22 27.78 0.000 30574.13 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.83 0.00799998 21.00 0.00799998 49.5594 8337.12 0.00 30724.45 30724.45 2.68855725 12.80 11.60 0.00800000 33059.8 24.01 15.96 0.00800000 44487.7
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 658977.346 658977.346 28.734456 0.00576502 15430.052 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.13499627 54.44 82.22 27.78 4447245.89 14.8177 15.115861 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 658977.35 658977.35 1.0000 33.15740281 28.734456 12.89 11.26 0.00800000 33150.5 32.11 18.27 0.00800000 52751.6 5.76443320 60.00 32.22 27.78 0.000 658977.35 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.87 0.00800000 21.00 0.00800000 49.5595 384733.04 0.00 661995.63 661995.63 33.15740281 12.80 11.60 0.00800000 33059.8 32.38 18.82 0.00800000 53025.1
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 219686.054 219686.054 9.654352 0.00192191 5132.784 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.13499627 54.44 82.22 27.78 4447245.89 4.9398 5.039238 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 219686.05 218364.03 1.0000 11.14039676 9.654352 12.89 11.26 0.00800000 33150.5 32.11 18.27 0.00800000 52751.6 1.92171338 60.00 32.22 27.78 0.000 219686.05 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.95 0.00800000 21.00 0.00800000 49.5595 127544.02 0.00 220693.15 220693.15 11.14039676 12.80 11.60 0.00800000 33059.8 32.23 18.77 0.00800000 52870.0
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 39271.362 39271.362 1.727797 0.00034356 917.252 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.13499627 54.44 82.22 27.78 4447245.89 0.8830 0.900821 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 39271.36 39079.66 1.0000 1.99374813 1.727797 12.89 11.26 0.00800000 33150.5 32.11 18.27 0.00800000 52751.6 0.34352796 60.00 32.22 27.78 0.000 39271.36 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.95 0.00790137 21.00 0.00790137 48.9577 22785.08 0.00 39451.42 39451.42 1.99374813 12.80 11.60 0.00800000 33059.8 32.21 18.76 0.00800000 52847.4
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 26601.410 26601.410 1.170485 0.00023272 621.305 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.13499627 54.44 82.22 27.78 4447245.89 0.5982 0.610193 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 26601.41 26601.41 1.0000 1.35065171 1.170485 12.89 11.26 0.00800000 33150.5 32.11 18.27 0.00800000 52751.6 0.23269700 60.00 32.22 27.78 0.000 26601.41 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.95 0.00790286 21.00 0.00790286 48.9669 15432.87 0.00 26723.38 26723.38 1.35065171 12.80 11.60 0.00800000 33059.8 32.20 18.76 0.00800000 52845.4
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 43292.912 43292.912 1.905069 0.00037875 1011.133 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.13499627 54.44 82.22 27.78 4447245.89 0.9735 0.993069 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 43292.91 43292.91 1.0000 2.19830686 1.905069 12.89 11.26 0.00800000 33150.5 32.11 18.27 0.00800000 52751.6 0.37870665 60.00 32.22 27.78 0.000 43292.91 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.95 0.00791024 21.00 0.00791024 49.0119 25114.82 0.00 43491.41 43491.41 2.19830686 12.80 11.60 0.00800000 33059.8 32.20 18.76 0.00800000 52843.9
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 23364.068 23364.068 1.027757 0.00020440 545.735 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.13499627 54.44 82.22 27.78 4447245.89 0.5254 0.535933 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 23364.07 23364.07 1.0000 1.18595379 1.027757 12.89 11.26 0.00800000 33150.5 32.11 18.27 0.00800000 52751.6 0.20437821 60.00 32.22 27.78 0.000 23364.07 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.95 0.00788963 21.00 0.00788963 48.8859 13557.68 0.00 23471.19 23471.19 1.18595379 12.80 11.60 0.00800000 33059.8 32.21 18.77 0.00800000 52850.8
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 521019.098 521019.098 22.935964 0.00455810 12167.407 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.13499627 54.44 82.22 27.78 4447245.89 11.7155 11.951325 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 521019.10 518770.15 1.0000 26.46637894 22.935964 12.89 11.26 0.00800000 33150.5 32.11 18.27 0.00800000 52751.6 4.55763739 60.00 32.22 27.78 0.000 521019.10 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.94 0.00782651 21.00 0.00782651 48.5014 302214.77 0.00 523408.05 523408.05 26.46637894 12.80 11.60 0.00800000 33059.8 32.19 18.76 0.00800000 52836.2
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 346211.427 346211.427 15.241423 0.00302881 8085.000 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.13499627 54.44 82.22 27.78 4447245.89 7.7849 7.941523 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 346211.43 346211.43 1.0000 17.58745641 15.241423 12.89 11.26 0.00800000 33150.5 32.11 18.27 0.00800000 52751.6 3.02849963 60.00 32.22 27.78 0.000 346211.43 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.94 0.00782587 21.00 0.00782587 48.4975 200812.08 0.00 347798.87 347798.87 17.58745641 12.80 11.60 0.00800000 33059.8 32.19 18.76 0.00800000 52835.2
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 532536.001 532536.001 23.443712 0.00465886 12436.250 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.13499627 54.44 82.22 27.78 4447245.89 11.9745 12.215504 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 532536.00 532536.00 1.0000 27.05228172 23.443712 12.89 11.26 0.00800000 33150.5 32.11 18.27 0.00800000 52751.6 4.65838200 60.00 32.22 27.78 0.000 532536.00 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.94 0.00783016 21.00 0.00783016 48.5237 308886.33 0.00 534977.77 534977.77 27.05228172 12.80 11.60 0.00800000 33059.8 32.19 18.76 0.00800000 52835.5
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 345869.132 345869.132 15.226435 0.00302581 8076.994 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.13499627 54.44 82.22 27.78 4447245.89 7.7772 7.933672 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 345869.13 345869.13 1.0000 17.57016187 15.226435 12.89 11.26 0.00800000 33150.5 32.11 18.27 0.00800000 52751.6 3.02550538 60.00 32.22 27.78 0.000 345869.13 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.94 0.00782586 21.00 0.00782586 48.4975 200612.85 0.00 347455.00 347455.00 17.57016187 12.80 11.60 0.00800000 33059.8 32.19 18.76 0.00800000 52835.1
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 69515.921 69515.921 3.061252 0.00060816 1623.255 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.13499627 54.44 82.22 27.78 4447245.89 1.5631 1.594581 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 69515.92 69240.01 1.0000 3.53245531 3.061252 12.89 11.26 0.00800000 33150.5 32.11 18.27 0.00800000 52751.6 0.60809356 60.00 32.22 27.78 0.000 69515.92 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.94 0.00783749 21.00 0.00783749 48.5692 40312.34 0.00 69834.67 69834.67 3.53245531 12.80 11.60 0.00800000 33059.8 32.19 18.76 0.00800000 52829.3
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 45832.538 45832.538 2.018367 0.00040096 1070.220 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.13499627 54.44 82.22 27.78 4447245.89 1.0306 1.051323 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 45832.54 45832.54 1.0000 2.32904398 2.018367 12.89 11.26 0.00800000 33150.5 32.11 18.27 0.00800000 52751.6 0.40092213 60.00 32.22 27.78 0.000 45832.54 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.94 0.00783568 21.00 0.00783568 48.5582 26577.96 0.00 46042.70 46042.70 2.32904398 12.80 11.60 0.00800000 33059.8 32.19 18.76 0.00800000 52828.8
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 70724.463 70724.463 3.114526 0.00061873 1651.467 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.13499627 54.44 82.22 27.78 4447245.89 1.5903 1.622303 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 70724.46 70444.96 1.0000 3.59392895 3.114526 12.89 11.26 0.00800000 33150.5 32.11 18.27 0.00800000 52751.6 0.61866534 60.00 32.22 27.78 0.000 70724.46 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.94 0.00784023 21.00 0.00784023 48.5859 41012.51 0.00 71048.76 71048.76 3.59392895 12.80 11.60 0.00800000 33059.8 32.19 18.76 0.00800000 52828.9
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 46435.918 46435.918 2.044977 0.00040624 1084.304 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.13499627 54.44 82.22 27.78 4447245.89 1.0442 1.065164 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 46435.92 46435.92 1.0000 2.35975018 2.044977 12.89 11.26 0.00800000 33150.5 32.11 18.27 0.00800000 52751.6 0.40620023 60.00 32.22 27.78 0.000 46435.92 -32.70 0.00018338 -32.70 0.00000000 0.0000 20.94 0.00783796 21.00 0.00783796 48.5721 26927.41 0.00 46648.84 46648.84 2.35975018 12.80 11.60 0.00800000 33059.8 32.19 18.76 0.00800000 52828.4
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 251110.400 -999.000 13.164517 0.00896908 -999.000 -999.0000 1.00000 1.00000 1022.3484 1004.8586 1.1539 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 13.164517 15.19086392   4197.9300 999.8980 128.62691050 13.34 6.67 6.67 3601578.33 6.9722 6.972232 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 Sensible 251110.40 215746.53 1.0000 15.19086392 13.164517 24.94 17.04 0.00941841 49052.0 11.04 10.99 0.00850000 32521.6 8.96816672 6.67 13.34 6.67 28778.993 222331.41 30.10 0.01272586 21.13 2.03050000 15.4240 24.00 0.00881523 24.00 0.00881523 45.4542 149782.76 0.00 259364.59 210528.39 15.19086392 24.94 17.49 0.00941841 49052.0 11.38 11.14 0.00814374 31978.2
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 94972.661 94972.661 3.949355 0.00083086 1525.159 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 13.164517 15.19086392   4197.9300 999.8980 38.13499627 54.44 82.22 27.78 4447245.89 2.1355 2.178517 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 94972.66 94972.66 1.0000 4.55725918 3.949355 -7.85 -7.85 0.00387135 1737.3 12.89 11.26 0.00800000 33150.5 0.83077751 60.00 32.22 27.78 0.000 94972.66 -32.70 0.00018338 -32.70 2.03050000 51.4135 18.45 0.00777391 18.79 0.00782839 55.6292 15036.87 0.00 83939.24 83939.24 4.55725918 2.80 1.77 0.00387135 12515.7 21.00 10.79 0.00387135 30934.5
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 2379307.074 -999.000 122.274549 0.08498333 -999.000 -999.0000 1.00000 1.00000 1022.5376 1004.8586 1.1539 VAV_MID WITH REHEAT FAN Fan:VariableVolume 122.274549 141.09564197   4197.9300 999.8980 128.62691050 13.34 6.67 6.67 3601578.33 66.0629 66.062899 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 Sensible 2379307.07 2014387.45 1.0000 141.09564197 122.274549 25.01 17.15 0.00952020 49385.0 11.04 10.99 0.00850000 32522.0 84.97466660 6.67 13.34 6.67 267304.779 2112002.29 30.10 0.01272586 21.13 20.30600000 16.6069 24.00 0.00888168 24.00 0.00888168 45.7927 1390901.36 0.00 2455773.44 1966952.66 141.09564197 25.01 17.60 0.00952020 49385.0 11.38 11.14 0.00814656 31980.0
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 960493.121 960493.121 36.682365 0.00840281 15280.338 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 VAV_MID WITH REHEAT FAN Fan:VariableVolume 122.274549 141.09564197   4197.9300 999.8980 38.13499627 54.44 82.22 27.78 4447245.89 21.5975 22.032140 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 960493.12 960493.12 1.0000 42.32869259 36.682365 -9.69 -9.69 0.00355120 -922.3 12.89 11.26 0.00800000 33150.5 8.40195565 60.00 32.22 27.78 0.000 960493.12 -32.70 0.00018338 -32.70 20.30600000 55.3563 18.84 0.00772715 18.61 0.00784356 56.3547 158503.38 0.00 831803.35 831803.35 42.32869259 2.80 1.31 0.00355120 11713.4 22.23 10.98 0.00355120 31364.4
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 372423.845 -999.000 19.893475 0.01330212 -999.000 -999.0000 1.00000 1.00000 1022.2292 1004.8586 1.1539 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 19.893475 22.95557518   4197.9300 999.8980 128.62691050 13.34 6.67 6.67 3601578.33 10.3406 10.340573 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 Sensible 372423.84 322800.34 1.0000 22.95557518 19.893475 24.82 16.95 0.00935431 48770.8 11.06 11.00 0.00850000 32547.2 13.30075987 6.67 13.34 6.67 42896.568 329527.28 30.10 0.01272586 21.13 2.03050000 10.2069 24.00 0.00882636 24.00 0.00882636 45.5116 170633.07 0.00 384788.96 314963.85 22.95557518 24.82 17.40 0.00935431 48770.8 11.40 11.16 0.00814829 32008.5
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 84131.473 84131.473 5.968042 0.00073602 1419.048 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 19.893475 22.95557518   4197.9300 999.8980 38.13499627 54.44 82.22 27.78 4447245.89 1.8918 1.929838 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 84131.47 84131.47 1.0000 6.88667256 5.968042 0.73 0.73 0.00512091 13549.0 12.89 11.26 0.00800000 33150.5 0.73594375 60.00 32.22 27.78 0.000 84131.47 -32.70 0.00018338 -32.70 2.03050000 34.0229 17.97 0.00766708 16.76 0.00785590 63.4570 29434.96 0.00 82238.03 82238.03 6.88667256 2.80 2.80 0.00512091 15647.3 14.57 9.31 0.00512091 27588.9
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 141841.048 -999.000 7.498936 0.00506623 -999.000 -999.0000 1.00000 1.00000 1022.6879 1004.8586 1.1539 CAV_BAS SZVAV FAN Fan:VariableVolume 7.498936 8.65320852   4197.9300 999.8980 128.62691050 13.34 6.67 6.67 3601578.33 3.9383 3.938302 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 141841.05 118336.30 1.0000 8.65320852 7.498936 24.79 17.14 0.00960108 49363.8 11.03 10.99 0.00850000 32512.1 5.06571676 6.67 13.34 6.67 16481.019 125360.03 28.49 0.01272303 20.66 1.20015641 16.0044 24.00 0.00893341 24.00 0.00893341 46.0548 77505.03 0.00 150554.62 119036.65 8.65320852 24.79 17.59 0.00960108 49363.8 11.34 11.14 0.00815686 31965.1
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 100000.000 100000.000 3.170652 0.00087484 2622.300 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 CAV_BAS SZVAV FAN Fan:VariableVolume 7.498936 8.65320852   4197.9300 999.8980 38.13499627 54.44 82.22 27.78 4447245.89 2.2486 2.293836 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 100000.00 100000.00 1.0000 3.65869449 3.170652 -5.23 -9.59 0.00018338 -4801.9 32.11 18.27 0.00800000 52750.5 0.87475438 60.00 32.22 27.78 0.000 100000.00 -32.70 0.00018338 -32.70 1.20015641 37.8520 0.00 0.00018338 22.59 0.00018338 1.0438 0.00 0.00 100072.50 100072.50 3.65869449 12.80 1.98 0.00000000 12887.2 40.02 14.59 0.00000000 40239.2
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes Yes Yes No 456895.966 -999.000 32.884996 0.01631927 -999.000 -999.0000 1.00000 1.00000 1020.7825 1004.8586 1.1539 AIRLOOP DATACENTER BASEMENT SYS11 FAN Fan:VariableVolume 32.884996 37.94681391   4197.9300 999.8980 128.62691050 13.34 6.67 6.67 3601578.33 12.6860 12.685993 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 456895.97 451554.48 1.0000 37.94681391 32.884996 27.03 17.06 0.00857607 49039.9 15.01 12.60 0.00850000 36575.3 16.31760054 6.67 13.34 6.67 34139.845 422756.12 30.10 0.01272586 21.13 0.33839277 1.0290 27.00 0.00853287 27.00 0.00853287 36.8357 373651.11 0.00 488445.44 488445.44 37.94681391 27.03 17.51 0.00857607 49039.9 14.42 12.84 0.00857607 36168.0
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes Yes Yes No 100000.000 100000.000 3.170652 0.00087484 2622.300 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 AIRLOOP DATACENTER BASEMENT SYS11 FAN Fan:VariableVolume 32.884996 37.94681391   4197.9300 999.8980 38.13499627 54.44 82.22 27.78 4447245.89 2.2486 2.293836 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 100000.00 100000.00 1.0000 3.65869449 3.170652 -0.34 -0.34 0.00841442 20700.6 29.11 17.29 0.00800000 49691.3 0.87475438 60.00 32.22 27.78 0.000 100000.00 -32.70 0.00018338 -32.70 0.33839277 10.6727 0.00 0.00850000 27.00 0.00850000 36.6913 0.00 0.00 100072.50 100072.50 3.65869449 12.80 1.98 0.00000000 12887.2 40.02 14.59 0.00000000 40239.2
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A No No unknown No 13491.710 10802.273 0.815030 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.9026 1004.8586 1.1539 AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.815034 0.94048789   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 Sensible 6745.85 6600.78 1.0000 0.62698892 0.543353 26.96 17.09 0.00864070 49130.2 14.43 12.38 0.00850000 35985.0 -999.0 -999.00 -999.00 -999.00 0.000 6745.85 24.81 0.01271660 19.55 0.01563234 2.8770 27.00 0.00856100 27.00 0.00856100 36.9535 9273.43 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 28103.345 28103.345 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.815034 0.94048789   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 28103.35 28103.35 1.0000 0.94048789 0.815034 -0.63 -5.10 0.00096991 1794.3 29.11 17.29 0.00800000 49691.3 -999.0 -999.00 -999.00 -999.00 0.000 28103.35 -32.70 0.00018338 -32.70 0.01563234 1.9180 0.00 0.00098529 24.77 0.00098529 4.9117 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A No No unknown No 130247.140 104283.675 7.868230 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.9119 1004.8586 1.1539 AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 7.868230 9.07934616   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 Sensible 65123.57 63674.57 1.0000 6.05289745 5.245487 26.96 17.09 0.00864567 49141.3 14.43 12.38 0.00850000 35985.0 -999.0 -999.00 -999.00 -999.00 0.000 65123.57 24.81 0.01271660 19.55 0.15632344 2.9802 27.00 0.00856315 27.00 0.00856315 36.9627 89524.20 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 271511.156 271511.156 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 7.868230 9.07934616   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 271511.16 271511.16 1.0000 9.07934616 7.868230 -0.65 -5.12 0.00096939 1770.4 29.11 17.29 0.00800000 49691.3 -999.0 -999.00 -999.00 -999.00 0.000 271511.16 -32.70 0.00018338 -32.70 0.15632344 1.9868 0.00 0.00098533 23.39 0.00098533 5.3374 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A No No unknown No 13373.520 10707.643 0.807890 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.9051 1004.8586 1.1539 AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.807895 0.93224967   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 Sensible 6686.76 6541.62 1.0000 0.62149623 0.538593 26.96 17.09 0.00864203 49133.2 14.43 12.38 0.00850000 35985.0 -999.0 -999.00 -999.00 -999.00 0.000 6686.76 24.81 0.01271660 19.55 0.01563234 2.9024 27.00 0.00856163 27.00 0.00856163 36.9562 9192.20 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 27862.366 27862.366 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.807895 0.93224967   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 27862.37 27862.37 1.0000 0.93224967 0.807895 -0.63 -5.11 0.00096819 1784.5 29.11 17.29 0.00800000 49691.3 -999.0 -999.00 -999.00 -999.00 0.000 27862.37 -32.70 0.00018338 -32.70 0.01563234 1.9349 0.00 0.00098367 20.78 0.00098367 6.2476 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER FixedDryBulb 0.00 13.16 -      
VAV_MID WITH REHEAT_OA_CONTROLLER FixedDryBulb 0.00 122.27 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER FixedDryBulb 0.00 19.89 -      
CAV_BAS_OA_CONTROLLER FixedDryBulb 1.20 7.50 -      
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER DifferentialDryBulb 0.34 32.88 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 1888.33 2943.67 50.50
CORE_BOTTOM 1914.00 2588.67 47.83
CORE_MID 1953.83 3612.67 521.50
CORE_TOP 2969.00 4597.50 2014.33
PERIMETER_BOT_ZN_3 3295.00 4110.50 1898.83
PERIMETER_BOT_ZN_2 3181.00 4267.00 1883.83
PERIMETER_BOT_ZN_1 3193.00 3880.33 1651.83
PERIMETER_BOT_ZN_4 2935.33 4074.00 1426.83
PERIMETER_MID_ZN_3 3491.50 4846.67 2656.67
PERIMETER_MID_ZN_2 3028.33 3905.33 2152.33
PERIMETER_MID_ZN_1 3342.83 4121.67 1973.00
PERIMETER_MID_ZN_4 3360.83 4750.00 2435.67
PERIMETER_TOP_ZN_3 3682.67 5204.50 3134.33
PERIMETER_TOP_ZN_2 3873.33 4682.67 2854.00
PERIMETER_TOP_ZN_1 3599.17 4507.50 2490.50
PERIMETER_TOP_ZN_4 3675.00 4910.17 2868.67
DATACENTER_BOT_ZN_6 5561.17 1131.83 1121.33
DATACENTER_MID_ZN_6 4722.17 676.33 499.17
DATACENTER_TOP_ZN_6 3981.17 1180.50 572.33
DATACENTER_BASEMENT_ZN_6 5938.50 3336.67 3336.67
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5941.50 5487.83
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 1.33 12.83 1.33 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 2.33 0.00 0.50 0.00
CORE_TOP 40.00 0.00 3.50 0.00
PERIMETER_BOT_ZN_3 60.67 0.00 10.33 0.00
PERIMETER_BOT_ZN_2 59.50 13.17 6.00 13.17
PERIMETER_BOT_ZN_1 63.83 21.50 6.00 21.50
PERIMETER_BOT_ZN_4 22.50 30.83 1.00 16.50
PERIMETER_MID_ZN_3 225.67 0.00 45.83 0.00
PERIMETER_MID_ZN_2 352.00 12.00 39.00 12.00
PERIMETER_MID_ZN_1 172.00 24.67 23.00 24.67
PERIMETER_MID_ZN_4 173.50 20.67 30.00 10.50
PERIMETER_TOP_ZN_3 392.00 0.00 95.83 0.00
PERIMETER_TOP_ZN_2 377.17 10.00 83.83 10.00
PERIMETER_TOP_ZN_1 329.83 13.00 62.33 13.00
PERIMETER_TOP_ZN_4 307.67 19.50 66.17 10.33
DATACENTER_BOT_ZN_6 0.00 279.00 0.00 143.67
DATACENTER_MID_ZN_6 0.00 225.00 0.00 115.17
DATACENTER_TOP_ZN_6 0.00 161.00 0.00 76.67
DATACENTER_BASEMENT_ZN_6 0.00 1.17 0.00 0.67
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 714.17 405.33 129.67 234.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.32 149.60 6779.02 0.927 0.000 0.000 0.000
CORE_BOTTOM 55.97 134.35 6849.35 0.875 0.000 0.000 0.000
CORE_MID 55.97 134.35 6849.35 0.712 0.000 0.000 0.000
CORE_TOP 55.97 134.35 6849.35 0.705 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.03 16.87 860.00 1.191 0.044 0.000 0.000
PERIMETER_BOT_ZN_2 4.53 10.87 554.22 2.141 0.046 0.000 0.000
PERIMETER_BOT_ZN_1 7.03 16.87 860.02 1.876 0.044 0.000 0.000
PERIMETER_BOT_ZN_4 4.53 10.87 554.22 2.537 0.046 0.000 0.000
PERIMETER_MID_ZN_3 7.03 16.87 860.00 1.406 0.104 0.000 0.000
PERIMETER_MID_ZN_2 3.96 10.87 554.22 2.106 0.113 0.000 0.000
PERIMETER_MID_ZN_1 7.03 16.87 860.02 1.898 0.104 0.000 0.000
PERIMETER_MID_ZN_4 4.53 10.87 554.22 2.327 0.107 0.000 0.000
PERIMETER_TOP_ZN_3 7.03 16.87 860.00 1.649 0.128 0.000 0.000
PERIMETER_TOP_ZN_2 4.53 10.87 554.22 1.989 0.133 0.000 0.000
PERIMETER_TOP_ZN_1 7.03 16.87 860.02 1.960 0.129 0.000 0.000
PERIMETER_TOP_ZN_4 4.53 10.87 554.22 2.220 0.133 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.57 42.18 1911.37 19.589 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.32 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 55.97 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 55.97 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 55.97 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.03 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.53 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 7.03 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.53 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 7.03 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.96 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 7.03 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.53 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 7.03 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.53 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 7.03 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.53 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.57 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 62.32 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 55.97 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 55.97 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 55.97 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 7.03 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.53 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 7.03 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.53 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 7.03 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.96 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 7.03 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.53 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 7.03 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.53 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 7.03 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.53 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.81 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.57 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1032.96 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 37294843.79 0.00 37294843.79 0.00 37294843.79 37848132.68 4275.88 2849.75 1634.37 136.13
CORE_BOTTOM 36562201.27 0.00 36562201.27 0.00 36562201.27 33990283.35 5861.65 33.09 2865.26 421.60
CORE_MID 0.30E+09 0.00 0.30E+09 0.00 0.30E+09 0.34E+09 6408.57 26.74 2324.69 701.45
CORE_TOP 28907341.25 0.00 28907341.25 0.00 28907341.25 33990283.35 6444.78 31.44 2283.78 353.86
PERIMETER_BOT_ZN_3 6333399.46 0.00 6333399.46 431999.69 6765399.14 4267819.30 3822.54 10.76 4926.69 421.60
PERIMETER_BOT_ZN_2 7338934.90 0.00 7338934.90 287999.59 7626934.49 2750345.05 3664.76 5.99 5089.26 421.60
PERIMETER_BOT_ZN_1 9921554.26 0.00 9921554.26 431999.69 10353553.95 4267912.63 3730.66 5.62 5023.72 421.60
PERIMETER_BOT_ZN_4 8712383.59 0.00 8712383.59 287999.59 9000383.19 2750345.05 3582.58 13.08 5164.34 421.60
PERIMETER_MID_ZN_3 75059159.71 0.00 75059159.71 1013169.02 76072328.74 42678193.03 3847.66 12.57 4899.77 701.45
PERIMETER_MID_ZN_2 68354250.07 0.00 68354250.07 675445.55 69029695.62 27503450.52 4139.17 17.76 4603.07 1114.29
PERIMETER_MID_ZN_1 99950453.18 0.00 99950453.18 1013169.02 0.10E+09 42679126.28 3800.73 14.27 4945.00 701.45
PERIMETER_MID_ZN_4 79711824.20 0.00 79711824.20 675445.55 80387269.75 27503450.52 3527.68 21.78 5210.54 701.45
PERIMETER_TOP_ZN_3 8539672.66 0.00 8539672.66 1257968.18 9797640.84 4267819.30 4020.10 4.42 4735.48 353.84
PERIMETER_TOP_ZN_2 6599611.26 0.00 6599611.26 838644.88 7438256.14 2750345.05 4007.16 3.76 4749.08 353.84
PERIMETER_TOP_ZN_1 10081475.12 0.00 10081475.12 1257968.18 11339443.30 4267912.63 4015.39 3.40 4741.20 353.84
PERIMETER_TOP_ZN_4 7384779.35 0.00 7384779.35 838644.88 8223424.23 2750345.05 3980.72 4.46 4774.82 353.84
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.31E+09 0.00 0.31E+09 0.00 0.31E+09 10671554.30 422.48 687.71 7649.81 2587.09
Total Facility 0.67E+10 0.00 0.67E+10 39405516.14 0.68E+10 0.50E+10 6973.47 4460.46 8431.94 3080.74


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.7135 0.0000 1.7135 0.0000 1.7135 1.2002 1505.80 2848.58 1588.62
CORE_BOTTOM 1.6311 0.0000 1.6311 0.0000 1.6311 1.0778 3203.85 31.85 2707.30
CORE_MID 13.2930 0.0000 13.2930 0.0000 13.2930 10.7782 3672.68 26.47 2243.85
CORE_TOP 1.3198 0.0000 1.3198 0.0000 1.3198 1.0778 3676.30 30.60 2236.10
PERIMETER_BOT_ZN_3 0.2797 0.0000 0.2797 0.0105 0.2902 0.1353 1208.29 8.69 4726.02
PERIMETER_BOT_ZN_2 0.3246 0.0000 0.3246 0.0070 0.3316 0.0872 1128.82 2.51 4811.67
PERIMETER_BOT_ZN_1 0.4408 0.0000 0.4408 0.0105 0.4513 0.1353 1155.25 3.01 4784.74
PERIMETER_BOT_ZN_4 0.3843 0.0000 0.3843 0.0070 0.3913 0.0872 1105.45 4.34 4833.20
PERIMETER_MID_ZN_3 3.3156 0.0000 3.3156 0.0246 3.3402 1.3533 1222.41 7.48 4713.12
PERIMETER_MID_ZN_2 3.1967 0.0000 3.1967 0.0173 3.2140 0.8721 1122.52 5.37 3906.12
PERIMETER_MID_ZN_1 4.4645 0.0000 4.4645 0.0246 4.4891 1.3533 1199.99 5.09 4737.92
PERIMETER_MID_ZN_4 3.5341 0.0000 3.5341 0.0164 3.5505 0.8721 1098.65 9.14 4835.21
PERIMETER_TOP_ZN_3 0.3892 0.0000 0.3892 0.0305 0.4197 0.1353 1292.72 3.11 4647.17
PERIMETER_TOP_ZN_2 0.3017 0.0000 0.3017 0.0204 0.3220 0.0872 1283.86 2.13 4657.01
PERIMETER_TOP_ZN_1 0.4611 0.0000 0.4611 0.0305 0.4916 0.1353 1288.81 2.21 4651.98
PERIMETER_TOP_ZN_4 0.3370 0.0000 0.3370 0.0204 0.3573 0.0872 1268.45 2.60 4671.95
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 10.1190 0.0000 10.1190 0.0000 10.1190 0.3384 178.50 687.34 5077.16
Total Facility 296.9053 0.0000 296.9053 0.9658 297.8711 158.4706 4156.47 4395.57 5809.25


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 91701308.60 0.00 91701308.60 48026705.38 3789.59 3.87 4966.54 421.60
VAV_MID WITH REHEAT 0.83E+09 0.00 0.83E+09 0.48E+09 3907.73 3.35 4848.92 701.45
VAV_TOP WITH REHEAT 81907019.26 0.00 81907019.26 48026705.38 4056.19 2.66 4701.15 353.74
CAV_BAS 49485471.75 0.00 49485471.75 37848132.68 4254.46 1.16 4504.38 136.13
AIRLOOP DATACENTER BASEMENT 0.42E+09 0.00 0.42E+09 10671554.30 417.46 0.25 8342.29 2587.05
AIRLOOP DATACENTER BOT 325290.55 0.00 325290.55 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 3252905.49 0.00 3252905.49 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 325290.55 0.00 325290.55 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 4.0752 0.0000 4.0752 1.5229 1182.03 2.68 4758.29
VAV_MID WITH REHEAT 36.7875 0.0000 36.7875 15.2292 1241.15 0.62 4701.23
VAV_TOP WITH REHEAT 3.7400 0.0000 3.7400 1.5229 1317.11 1.85 4624.04
CAV_BAS 2.2734 0.0000 2.2734 1.2002 1493.64 0.66 4448.69
AIRLOOP DATACENTER BASEMENT 13.4739 0.0000 13.4739 0.3384 177.28 0.07 5765.65
AIRLOOP DATACENTER BOT 0.0152 0.0000 0.0152 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1520 0.0000 0.1520 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0152 0.0000 0.0152 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 24.52 3653.58 0.00 0.00 0.00 1621.74 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 103.76 4076.42 0.00 0.00 0.00 1485.45 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 18.21 3279.79 0.00 0.00 0.00 1938.55 0.00 0.00 0.00
CAV_BAS 0.00 2868.58 1807.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 686.91 7671.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 2.5671 6.2939 0.0000 0.0000 0.0000 2.3556 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 26.4972 53.1924 0.0000 0.0000 0.0000 24.4945 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 2.7099 6.0574 0.0000 0.0000 0.0000 2.2996 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.5984 5.3421 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4512 15.6896 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0208 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2082 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0208 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1343
Defaulted Fields 1287
Fields with Defaults 3878
Autosized Fields 320
Autosizable Fields 465
Autocalculated Fields 223
Autocalculatable Fields 468



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 31529.54 291299.00 28-MAY-05:00 2455455.28 08-AUG-15:20
Electricity:Building 20287.13 234472.87 01-JAN-00:10 1268272.53 03-APR-07:10
Electricity:Zone:BASEMENT 758.19 15076.70 01-JAN-00:10 42602.33 02-JAN-08:10
Electricity:SpaceType:GENERAL 20287.13 234472.87 01-JAN-00:10 1268272.53 03-APR-07:10
InteriorLights:Electricity 5610.74 27216.71 01-JAN-00:10 489900.85 02-JAN-08:10
InteriorLights:Electricity:Zone:BASEMENT 333.79 1619.15 01-JAN-00:10 29144.79 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 5610.74 27216.71 01-JAN-00:10 489900.85 02-JAN-08:10
LightsWired:InteriorLights:Electricity 5610.74 27216.71 01-JAN-00:10 489900.85 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 333.79 1619.15 01-JAN-00:10 29144.79 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 5610.74 27216.71 01-JAN-00:10 489900.85 02-JAN-08:10
Electricity:Zone:CORE_BOTTOM 589.38 5907.35 01-JAN-00:10 43380.70 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 299.77 1454.11 01-JAN-00:10 26174.07 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 299.77 1454.11 01-JAN-00:10 26174.07 02-JAN-08:10
Electricity:Zone:CORE_MID 5893.79 59073.32 01-JAN-00:10 433806.32 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 2997.66 14541.15 01-JAN-00:10 261740.70 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 2997.66 14541.15 01-JAN-00:10 261740.70 02-JAN-08:10
Electricity:Zone:CORE_TOP 589.38 5907.33 01-JAN-00:10 43380.63 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 299.77 1454.11 01-JAN-00:10 26174.07 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 299.77 1454.11 01-JAN-00:10 26174.07 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 74.00 741.75 01-JAN-00:10 5446.97 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 37.64 182.58 01-JAN-00:10 3286.42 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 37.64 182.58 01-JAN-00:10 3286.42 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_2 47.69 478.01 01-JAN-00:10 3510.23 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 24.26 117.66 01-JAN-00:10 2117.89 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 24.26 117.66 01-JAN-00:10 2117.89 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_1 74.01 741.76 01-JAN-00:10 5447.07 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 37.64 182.58 01-JAN-00:10 3286.49 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 37.64 182.58 01-JAN-00:10 3286.49 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_4 47.69 478.01 01-JAN-00:10 3510.22 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 24.26 117.66 01-JAN-00:10 2117.89 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 24.26 117.66 01-JAN-00:10 2117.89 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_3 740.04 7417.49 01-JAN-00:10 54469.67 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 376.39 1825.79 01-JAN-00:10 32864.16 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 376.39 1825.79 01-JAN-00:10 32864.16 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_2 476.91 4780.12 01-JAN-00:10 35102.33 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 242.56 1176.61 01-JAN-00:10 21178.91 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 242.56 1176.61 01-JAN-00:10 21178.91 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_1 740.05 7417.62 01-JAN-00:10 54470.72 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 376.39 1825.83 01-JAN-00:10 32864.88 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 376.39 1825.83 01-JAN-00:10 32864.88 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_4 476.91 4780.09 01-JAN-00:10 35102.24 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 242.56 1176.61 01-JAN-00:10 21178.91 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 242.56 1176.61 01-JAN-00:10 21178.91 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_3 74.00 741.75 01-JAN-00:10 5446.97 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 37.64 182.58 01-JAN-00:10 3286.42 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 37.64 182.58 01-JAN-00:10 3286.42 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_2 47.69 478.01 01-JAN-00:10 3510.23 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 24.26 117.66 01-JAN-00:10 2117.89 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 24.26 117.66 01-JAN-00:10 2117.89 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_1 74.01 741.76 01-JAN-00:10 5447.07 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 37.64 182.58 01-JAN-00:10 3286.49 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 37.64 182.58 01-JAN-00:10 3286.49 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_4 47.69 478.01 01-JAN-00:10 3510.22 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 24.26 117.66 01-JAN-00:10 2117.89 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 24.26 117.66 01-JAN-00:10 2117.89 02-JAN-08:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7588.97 95364.66 01-JAN-00:10 387850.11 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 94.11 456.53 01-JAN-00:10 8217.58 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 94.11 456.53 01-JAN-00:10 8217.58 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 162.23 1989.09 01-JAN-00:10 8523.21 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 8.35 40.49 01-JAN-00:10 728.78 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 8.35 40.49 01-JAN-00:10 728.78 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1622.27 19890.94 01-JAN-00:10 85232.07 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 83.47 404.88 01-JAN-00:10 7287.84 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 83.47 404.88 01-JAN-00:10 7287.84 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 162.23 1989.09 01-JAN-00:10 8523.21 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 8.35 40.49 01-JAN-00:10 728.78 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 8.35 40.49 01-JAN-00:10 728.78 02-JAN-08:10
InteriorEquipment:Electricity 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:HVAC 4774.62 33905.91 30-SEP-04:50 374681.83 21-APR-15:40
ExteriorEquipment:Electricity 2623.11 22123.82 01-JAN-00:10 235096.12 03-APR-07:20
Transformer:ExteriorEquipment:Electricity 56.04 979.82 01-JAN-00:10 3543.78 03-APR-07:20
ElectricityPurchased:Facility 31529.54 291299.00 28-MAY-05:00 2455455.28 08-AUG-15:20
ElectricityPurchased:Plant 31529.54 291299.00 28-MAY-05:00 2455455.28 08-AUG-15:20
Cogeneration:ElectricityPurchased 31529.54 291299.00 28-MAY-05:00 2455455.28 08-AUG-15:20
General:Cogeneration:ElectricityPurchased 31529.54 291299.00 28-MAY-05:00 2455455.28 08-AUG-15:20
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 31529.54 291299.00 28-MAY-05:00 2455455.28 08-AUG-15:20
ElectricityNet:Plant 31529.54 291299.00 28-MAY-05:00 2455455.28 08-AUG-15:20
Cogeneration:ElectricityNet 31529.54 291299.00 28-MAY-05:00 2455455.28 08-AUG-15:20
General:Cogeneration:ElectricityNet 31529.54 291299.00 28-MAY-05:00 2455455.28 08-AUG-15:20
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 1735.95 0.00 01-JAN-01:10 590463.98 05-JUL-10:20
General:Cooling:Electricity 1735.95 0.00 01-JAN-01:10 590463.98 05-JUL-10:20
Fans:Electricity 3022.89 26562.47 02-JAN-22:30 303816.83 30-JUN-15:00
General:Fans:Electricity 3022.89 26562.47 02-JAN-22:30 303816.83 30-JUN-15:00
ExteriorLights:Electricity 1004.65 0.00 01-JAN-08:20 64082.80 01-JAN-00:10
General:ExteriorLights:Electricity 1004.65 0.00 01-JAN-08:20 64082.80 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 2505.76 19200.00 01-JAN-00:10 229608.34 02-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 61.31 1944.00 01-JAN-00:10 1944.00 01-JAN-00:10
Humidifier:Electricity 1280.30 0.00 15-APR-01:20 100000.00 31-MAR-23:50
General:Humidifier:Electricity 1280.30 0.00 15-APR-01:20 100000.00 31-MAR-23:50
Electricity:Plant 2896.06 0.00 19-JAN-00:10 770868.62 05-JUL-13:00
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:Electricity 514.24 0.00 01-JAN-00:10 62804.56 24-FEB-12:40
Water Heater:WaterSystems:Electricity 514.24 0.00 01-JAN-00:10 62804.56 24-FEB-12:40
HeatRejection:Electricity 121.82 0.00 01-JAN-00:10 55784.63 19-JUN-13:10
General:HeatRejection:Electricity 121.82 0.00 01-JAN-00:10 55784.63 19-JUN-13:10
Pumps:Electricity 939.44 0.00 19-JAN-00:10 111901.83 05-JUL-10:40
General:Pumps:Electricity 939.44 0.00 19-JAN-00:10 111901.83 05-JUL-10:40
WIRED_LTG_ELECTRICITY 157.66 0.00 01-JAN-00:10 13766.21 02-JAN-08:20
WIRED_INT_EQUIP 5334.97 88964.76 31-MAR-23:10 305206.10 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 8150.49 0.00 01-JAN-00:40 3228629.56 09-JAN-07:30
NaturalGas:HVAC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:NaturalGas 8150.49 0.00 01-JAN-00:40 3228629.56 09-JAN-07:30
General:Heating:NaturalGas 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
NaturalGas:Plant 8150.49 0.00 01-JAN-00:40 3228629.56 09-JAN-07:30
Boiler:Heating:NaturalGas 8150.49 0.00 01-JAN-00:40 3228629.56 09-JAN-07:30


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 7340.63 0.00 01-JAN-00:20 4052242.55 05-JUL-10:40
PlantLoopCoolingDemand:HVAC 7340.63 0.00 01-JAN-00:20 4052242.55 05-JUL-10:40
CoolingCoils:PlantLoopCoolingDemand 7340.63 0.00 01-JAN-00:20 4052242.55 05-JUL-10:40


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 7837.15 0.00 23-APR-23:50 0.00 18-MAY-15:10
Water:HVAC 476.27 0.00 15-APR-01:20 0.00 02-APR-15:10
Humidifier:Water 476.27 0.00 15-APR-01:20 0.00 02-APR-15:10
General:Humidifier:Water 476.27 0.00 15-APR-01:20 0.00 02-APR-15:10
MainsWater:Facility 7837.15 0.00 23-APR-23:50 0.00 18-MAY-15:10
MainsWater:HVAC 476.27 0.00 15-APR-01:20 0.00 02-APR-15:10
Humidifier:MainsWater 476.27 0.00 15-APR-01:20 0.00 02-APR-15:10
General:Humidifier:MainsWater 476.27 0.00 15-APR-01:20 0.00 02-APR-15:10
Water:Plant 7360.87 0.00 01-JAN-00:10 0.00 18-MAY-15:10
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 26-APR-12:00
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 26-APR-12:00
MainsWater:Plant 7360.87 0.00 01-JAN-00:10 0.00 18-MAY-15:10
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 26-APR-12:00
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 26-APR-12:00
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 5080.70 0.00 01-JAN-00:10 0.00 18-MAY-15:10
General:HeatRejection:Water 5080.70 0.00 01-JAN-00:10 0.00 18-MAY-15:10
HeatRejection:MainsWater 5080.70 0.00 01-JAN-00:10 0.00 18-MAY-15:10
General:HeatRejection:MainsWater 5080.70 0.00 01-JAN-00:10 0.00 18-MAY-15:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 66956.14 101495.27 01-JAN-00:40 17316377.27 05-JUL-10:40
EnergyTransfer:Building 21717.16 88354.41 19-JAN-23:00 2140340.86 26-DEC-06:10
EnergyTransfer:Zone:BASEMENT 723.01 0.00 01-JAN-00:10 84402.81 05-SEP-09:20
Heating:EnergyTransfer 2401.93 0.00 04-FEB-17:30 1977141.40 02-JAN-05:10
Heating:EnergyTransfer:Zone:BASEMENT 0.89 0.00 01-JAN-00:10 15792.43 09-JAN-07:10
General:Heating:EnergyTransfer 2401.93 0.00 04-FEB-17:30 1977141.40 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:BASEMENT 0.89 0.00 01-JAN-00:10 15792.43 09-JAN-07:10
Cooling:EnergyTransfer 19315.23 80368.52 02-JAN-06:50 1931077.18 08-AUG-15:20
Cooling:EnergyTransfer:Zone:BASEMENT 722.12 0.00 01-JAN-00:10 84402.81 05-SEP-09:20
General:Cooling:EnergyTransfer 19315.23 80368.52 02-JAN-06:50 1931077.18 08-AUG-15:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 722.12 0.00 01-JAN-00:10 84402.81 05-SEP-09:20
EnergyTransfer:Zone:CORE_BOTTOM 589.41 0.00 01-JAN-00:40 58982.74 05-JUL-10:50
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.03 0.00 01-JAN-00:10 11962.48 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.03 0.00 01-JAN-00:10 11962.48 02-JAN-06:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 589.37 0.00 01-JAN-00:40 58982.74 05-JUL-10:50
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 589.37 0.00 01-JAN-00:40 58982.74 05-JUL-10:50
EnergyTransfer:Zone:CORE_MID 4690.52 0.00 01-JAN-00:40 570431.29 02-JAN-05:10
Heating:EnergyTransfer:Zone:CORE_MID 27.70 0.00 01-JAN-00:20 570431.29 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:CORE_MID 27.70 0.00 01-JAN-00:20 570431.29 02-JAN-05:10
Cooling:EnergyTransfer:Zone:CORE_MID 4662.82 0.00 01-JAN-00:40 499523.08 30-JUN-16:00
General:Cooling:EnergyTransfer:Zone:CORE_MID 4662.82 0.00 01-JAN-00:40 499523.08 30-JUN-16:00
EnergyTransfer:Zone:CORE_TOP 444.74 0.00 01-JAN-00:40 112146.92 09-JAN-05:10
Heating:EnergyTransfer:Zone:CORE_TOP 62.74 0.00 01-JAN-00:40 112146.92 09-JAN-05:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 62.74 0.00 01-JAN-00:40 112146.92 09-JAN-05:10
Cooling:EnergyTransfer:Zone:CORE_TOP 382.00 0.00 01-JAN-00:10 62771.25 30-JUN-15:20
General:Cooling:EnergyTransfer:Zone:CORE_TOP 382.00 0.00 01-JAN-00:10 62771.25 30-JUN-15:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 90.72 0.00 01-JAN-00:40 20931.57 09-JAN-05:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 20.46 0.00 01-JAN-00:40 20931.57 09-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 20.46 0.00 01-JAN-00:40 20931.57 09-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 70.26 0.00 01-JAN-00:20 13656.79 29-JUN-14:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 70.26 0.00 01-JAN-00:20 13656.79 29-JUN-14:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 87.06 0.00 01-JAN-00:40 19269.54 31-JUL-08:10
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 13.00 0.00 01-JAN-00:40 15176.35 09-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 13.00 0.00 01-JAN-00:40 15176.35 09-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 74.07 0.00 01-JAN-00:20 19269.54 31-JUL-08:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 74.07 0.00 01-JAN-00:20 19269.54 31-JUL-08:10
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 138.10 0.00 01-JAN-00:40 30393.51 01-SEP-13:10
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 17.97 0.00 01-JAN-00:40 23848.80 09-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 17.97 0.00 01-JAN-00:40 23848.80 09-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 120.13 0.00 01-JAN-00:20 30393.51 01-SEP-13:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 120.13 0.00 01-JAN-00:20 30393.51 01-SEP-13:10
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 108.60 0.00 01-JAN-00:40 23119.13 24-JUL-17:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 5.11 0.00 01-JAN-00:40 13003.52 09-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 5.11 0.00 01-JAN-00:40 13003.52 09-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 103.49 0.00 01-JAN-00:20 23119.13 24-JUL-17:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 103.49 0.00 01-JAN-00:20 23119.13 24-JUL-17:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 1134.00 0.00 01-JAN-00:40 291626.91 13-FEB-05:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 560.21 0.00 01-JAN-00:40 291626.91 13-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 560.21 0.00 01-JAN-00:40 291626.91 13-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 573.80 0.00 01-JAN-00:10 133821.49 29-JUN-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 573.80 0.00 01-JAN-00:10 133821.49 29-JUN-15:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 926.85 0.00 01-JAN-00:40 201623.81 13-FEB-05:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 315.91 0.00 01-JAN-00:40 201623.81 13-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 315.91 0.00 01-JAN-00:40 201623.81 13-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 610.94 0.00 01-JAN-00:20 201468.88 24-JUL-08:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 610.94 0.00 01-JAN-00:20 201468.88 24-JUL-08:50
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1495.04 0.00 01-JAN-00:40 328381.49 01-SEP-13:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 365.86 0.00 01-JAN-00:40 294165.89 09-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 365.86 0.00 01-JAN-00:40 294165.89 09-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1129.18 0.00 01-JAN-00:20 328381.49 01-SEP-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1129.18 0.00 01-JAN-00:20 328381.49 01-SEP-13:20
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 973.12 0.00 01-JAN-00:40 228816.90 30-JUN-17:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 277.40 0.00 01-JAN-00:40 199464.13 13-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 277.40 0.00 01-JAN-00:40 199464.13 13-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 695.72 0.00 01-JAN-00:20 228816.90 30-JUN-17:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 695.72 0.00 01-JAN-00:20 228816.90 30-JUN-17:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 157.00 0.00 01-JAN-00:40 37712.55 13-FEB-05:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 101.90 0.00 01-JAN-00:40 37712.55 13-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 101.90 0.00 01-JAN-00:40 37712.55 13-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 55.10 0.00 01-JAN-00:10 14644.29 29-JUN-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 55.10 0.00 01-JAN-00:10 14644.29 29-JUN-15:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 116.81 0.00 01-JAN-00:40 24812.56 13-FEB-05:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 59.43 0.00 01-JAN-00:40 24812.56 13-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 59.43 0.00 01-JAN-00:40 24812.56 13-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 57.38 0.00 01-JAN-00:10 20130.14 24-JUL-09:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 57.38 0.00 01-JAN-00:10 20130.14 24-JUL-09:10
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 178.79 0.00 01-JAN-00:40 37151.92 13-FEB-05:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 74.49 0.00 01-JAN-00:40 37151.92 13-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 74.49 0.00 01-JAN-00:40 37151.92 13-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 104.30 0.00 01-JAN-00:10 33947.82 01-SEP-13:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 104.30 0.00 01-JAN-00:10 33947.82 01-SEP-13:10
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 115.29 0.00 01-JAN-00:40 24675.90 04-JAN-05:40
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 50.82 0.00 01-JAN-00:40 24675.90 04-JAN-05:40
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 50.82 0.00 01-JAN-00:40 24675.90 04-JAN-05:40
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 64.47 0.00 01-JAN-00:10 23927.99 30-JUN-17:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 64.47 0.00 01-JAN-00:10 23927.99 30-JUN-17:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 84.93 0.00 01-JAN-00:40 12433.89 02-JAN-06:20
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 5.15 0.00 01-JAN-00:10 12433.89 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 5.15 0.00 01-JAN-00:10 12433.89 02-JAN-06:20
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 79.77 0.00 01-JAN-00:40 11024.48 30-MAY-05:10
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 79.77 0.00 01-JAN-00:40 11024.48 30-MAY-05:10
EnergyTransfer:Zone:MIDFLOOR_PLENUM 863.94 0.00 01-JAN-00:40 256959.26 02-JAN-06:20
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 210.50 0.00 01-JAN-00:40 256959.26 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 210.50 0.00 01-JAN-00:40 256959.26 02-JAN-06:20
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 653.43 0.00 01-JAN-00:10 123963.43 12-MAR-03:00
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 653.43 0.00 01-JAN-00:10 123963.43 12-MAR-03:00
EnergyTransfer:Zone:TOPFLOOR_PLENUM 287.17 0.00 01-JAN-00:40 71262.24 09-JAN-05:10
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 202.64 0.00 01-JAN-00:40 71262.24 09-JAN-05:10
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 202.64 0.00 01-JAN-00:40 71262.24 09-JAN-05:10
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 84.52 0.00 01-JAN-00:10 37249.27 30-JUN-14:00
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 84.52 0.00 01-JAN-00:10 37249.27 30-JUN-14:00
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 127.39 3.01 25-JAN-20:30 11683.06 20-DEC-11:10
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 1.34 0.00 01-JAN-16:00 1431.54 04-JAN-24:00
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 1.34 0.00 01-JAN-16:00 1431.54 04-JAN-24:00
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 126.05 0.00 01-JAN-00:10 11683.06 20-DEC-11:10
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 126.05 0.00 01-JAN-00:10 11683.06 20-DEC-11:10
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1109.72 7.37 25-JAN-09:20 108987.00 20-DEC-11:10
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 22.95 0.00 02-JAN-13:40 14464.29 01-JAN-17:10
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 22.95 0.00 02-JAN-13:40 14464.29 01-JAN-17:10
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1086.77 0.00 01-JAN-00:10 108987.00 20-DEC-11:10
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1086.77 0.00 01-JAN-00:10 108987.00 20-DEC-11:10
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 96.23 5.10 09-OCT-10:30 9966.83 20-DEC-11:10
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 3.57 0.00 02-JAN-13:40 1493.20 01-JAN-17:10
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 3.57 0.00 02-JAN-13:40 1493.20 01-JAN-17:10
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 92.66 0.00 01-JAN-00:10 9966.83 20-DEC-11:10
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 92.66 0.00 01-JAN-00:10 9966.83 20-DEC-11:10
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7178.72 79835.68 01-JAN-00:20 395724.40 24-APR-08:00
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 1.83 0.00 01-JAN-00:10 3065.44 20-FEB-15:20
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 1.83 0.00 01-JAN-00:10 3065.44 20-FEB-15:20
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7176.89 79835.68 01-JAN-00:20 395724.40 24-APR-08:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7176.89 79835.68 01-JAN-00:20 395724.40 24-APR-08:00
PlantLoopHeatingDemand:Facility 6311.54 0.00 01-JAN-00:40 2597885.81 09-JAN-07:10
PlantLoopHeatingDemand:Plant 508.68 0.00 01-JAN-00:10 62462.67 24-FEB-12:10
WaterSystems:PlantLoopHeatingDemand 508.68 0.00 01-JAN-00:10 62462.67 24-FEB-12:10
General:WaterSystems:PlantLoopHeatingDemand 508.68 0.00 01-JAN-00:10 62462.67 24-FEB-12:10
EnergyTransfer:HVAC 14869.47 0.47 27-JAN-23:00 4139136.26 05-JUL-10:40
HeatingCoils:EnergyTransfer 5802.86 0.00 01-JAN-00:40 2577738.34 09-JAN-07:10
PlantLoopHeatingDemand:HVAC 5802.86 0.00 01-JAN-00:40 2577738.34 09-JAN-07:10
HeatingCoils:PlantLoopHeatingDemand 5802.86 0.00 01-JAN-00:40 2577738.34 09-JAN-07:10
CoolingCoils:EnergyTransfer 9066.61 0.00 01-JAN-01:10 4139136.26 05-JUL-10:40
EnergyTransfer:Plant 30369.51 0.00 19-JAN-00:10 11717585.10 05-JUL-10:40
LoopToLoop:EnergyTransfer 7487.14 0.00 01-JAN-00:20 3863639.36 05-JUL-10:40
WaterSystems:EnergyTransfer 508.68 0.00 01-JAN-00:10 62462.67 24-FEB-12:10
WaterUse:WaterSystems:EnergyTransfer 508.68 0.00 01-JAN-00:10 62462.67 24-FEB-12:10
Boilers:EnergyTransfer 5770.01 0.00 01-JAN-00:40 2529642.91 09-JAN-07:30
Chillers:EnergyTransfer 7641.56 0.00 01-JAN-00:20 3634720.89 05-JUL-10:20
HeatRejection:EnergyTransfer 8962.12 0.00 01-JAN-00:20 4205208.14 05-JUL-10:20
General:HeatRejection:EnergyTransfer 8962.12 0.00 01-JAN-00:20 4205208.14 05-JUL-10:20
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.892 -722.111 0.000 0.000 96.809 333.789 424.397 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -133.776
CORE_BOTTOM 0.000 0.000 0.035 -589.373 0.000 0.000 84.246 299.766 289.614 0.000 0.000 0.000 0.001 0.000 0.000 0.000 0.000 -84.289
CORE_MID 0.000 0.000 27.702 -4662.807 0.000 0.000 864.288 2997.664 2896.128 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -2122.974
CORE_TOP 0.000 0.000 62.744 -381.996 0.000 0.000 92.210 299.766 289.613 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -362.337
PERIMETER_BOT_ZN_3 0.000 0.000 20.456 -70.259 0.000 0.000 11.514 37.639 36.365 29.210 0.000 0.037 87.296 0.000 -142.463 0.000 -9.795 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 12.997 -74.067 0.000 0.000 7.479 24.256 23.435 64.535 0.000 0.029 33.848 0.000 -86.043 0.000 -6.471 0.000
PERIMETER_BOT_ZN_1 0.000 0.000 17.973 -120.131 0.000 0.000 11.371 37.639 36.366 137.696 0.000 0.035 10.376 0.000 -121.513 0.000 -9.814 -0.001
PERIMETER_BOT_ZN_4 0.000 0.000 5.111 -103.489 0.000 0.000 7.454 24.256 23.435 65.089 0.000 0.023 80.291 0.000 -95.296 0.000 -6.874 0.000
PERIMETER_MID_ZN_3 0.000 0.000 560.208 -573.794 0.000 0.000 119.026 376.387 363.654 308.501 0.000 1.031 417.064 0.000 -1358.130 0.000 -213.948 -0.004
PERIMETER_MID_ZN_2 0.000 0.000 315.909 -610.938 0.000 0.000 55.603 242.558 234.352 640.888 0.000 0.623 97.745 0.000 -831.968 0.000 -144.772 -0.000
PERIMETER_MID_ZN_1 0.000 0.000 365.863 -1129.177 0.000 0.000 114.985 376.395 363.660 1364.907 0.000 0.764 0.000 0.000 -1202.328 0.000 -223.057 -32.010
PERIMETER_MID_ZN_4 0.000 0.000 277.396 -695.717 0.000 0.000 77.014 242.558 234.351 663.937 0.000 0.599 232.204 0.000 -885.477 0.000 -146.864 -0.006
PERIMETER_TOP_ZN_3 0.000 0.000 101.903 -55.100 0.000 0.000 12.130 37.639 36.365 32.214 0.000 0.151 0.000 0.000 -129.633 0.000 -25.611 -10.058
PERIMETER_TOP_ZN_2 0.000 0.000 59.433 -57.376 0.000 0.000 7.625 24.256 23.435 65.060 0.000 0.075 0.001 0.000 -79.637 0.000 -17.387 -25.486
PERIMETER_TOP_ZN_1 0.000 0.000 74.490 -104.296 0.000 0.000 11.737 37.639 36.366 138.006 0.000 0.099 0.002 0.000 -113.840 0.000 -26.543 -53.659
PERIMETER_TOP_ZN_4 0.000 0.000 50.820 -64.472 0.000 0.000 7.761 24.256 23.435 66.627 0.000 0.074 0.001 0.000 -85.088 0.000 -17.697 -5.715
DATACENTER_BOT_ZN_6 0.000 0.000 1.341 -126.052 0.000 0.000 0.941 8.347 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -38.457
DATACENTER_MID_ZN_6 0.000 0.000 22.952 -1086.764 0.000 0.000 9.432 83.466 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -567.892
DATACENTER_TOP_ZN_6 0.000 0.000 3.571 -92.658 0.000 0.000 0.948 8.347 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -74.088
DATACENTER_BASEMENT_ZN_6 0.000 0.000 1.834 -7176.629 0.000 0.000 22.965 94.114 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -437.141
GROUNDFLOOR_PLENUM 5.152 -79.774 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.057 96.139 0.000 0.000 0.000 -21.574 -0.000
MIDFLOOR_PLENUM 210.504 -653.432 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.109 810.165 0.000 0.000 0.000 -368.345 -0.011
TOPFLOOR_PLENUM 202.643 -84.524 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.071 0.000 0.000 0.000 0.000 -37.674 -80.516
Total Facility 418.299 -817.730 1983.632 -18497.207 0.000 0.000 1615.538 5610.736 14676.396 3576.671 0.000 4.779 1865.133 0.000 -5131.417 0.000 -1276.427 -4028.420


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 23-OCT-04:11 0.00 0.00 0.00 -147965.66 0.00 0.00 0.00 3238.31 13457.54 0.00 0.00 0.00 131269.81 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 31-JUL-04:11 0.00 0.00 0.00 -122248.21 0.00 0.00 0.00 2908.23 5937.65 0.00 0.00 0.00 113402.33 0.00 -0.00 0.00 0.00 0.00
CORE_MID 30-MAY-04:12 0.00 0.00 0.00 -1084515.33 0.00 0.00 0.00 29082.30 59376.23 0.00 0.00 0.00 996056.80 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 26-MAY-05:02 0.00 0.00 0.00 -129176.12 0.00 0.00 844.33 2908.23 7647.36 0.00 0.00 0.00 117776.20 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 03-JUL-04:11 0.00 0.00 0.00 -18243.34 0.00 0.00 0.00 365.16 745.56 0.00 0.00 0.00 19527.31 0.00 -2297.48 0.00 -97.21 0.00
PERIMETER_BOT_ZN_2 25-JUN-08:61 0.00 0.00 0.00 -38607.69 0.00 0.00 16.35 117.66 464.11 25522.01 0.00 0.00 12614.53 0.00 -0.00 0.00 -126.98 0.00
PERIMETER_BOT_ZN_1 22-OCT-13:11 0.00 0.00 0.00 -49053.16 0.00 0.00 24.60 182.58 720.19 38791.14 0.00 0.00 9645.87 0.00 -0.00 0.00 -311.23 0.00
PERIMETER_BOT_ZN_4 16-JUL-16:51 0.00 0.00 0.00 -48077.00 0.00 0.00 12.53 117.66 464.11 22147.03 0.00 0.00 25680.02 0.00 -0.00 0.00 -344.35 0.00
PERIMETER_MID_ZN_3 28-JUN-05:01 0.00 0.00 0.00 -183342.86 0.00 0.00 1117.09 3651.57 9602.45 64701.11 0.00 0.00 104270.63 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 25-JUN-08:11 0.00 0.00 0.00 -415644.69 0.00 0.00 154.15 1176.61 4641.14 248993.86 0.00 0.00 163644.00 0.00 -0.00 0.00 -2965.07 0.00
PERIMETER_MID_ZN_1 22-OCT-13:11 0.00 0.00 0.00 -526575.67 0.00 0.00 197.79 1825.83 7201.95 382871.56 0.00 0.00 142385.01 0.00 -0.00 0.00 -7906.46 0.00
PERIMETER_MID_ZN_4 23-APR-17:41 0.00 0.00 0.00 -449325.01 0.00 0.00 0.00 1176.61 3603.49 211308.04 0.00 0.00 237920.34 0.00 -0.00 0.00 -4683.46 0.00
PERIMETER_TOP_ZN_3 28-JUN-05:01 0.00 0.00 0.00 -17678.86 0.00 0.00 112.89 365.16 960.25 6592.23 0.00 0.00 9648.34 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 18-JUN-09:51 0.00 0.00 0.00 -39482.19 0.00 0.00 17.83 117.66 464.11 17525.82 0.00 0.00 21832.71 0.00 -0.00 0.00 -475.95 0.00
PERIMETER_TOP_ZN_1 22-OCT-13:11 0.00 0.00 0.00 -62326.89 0.00 0.00 23.33 182.58 720.19 38416.01 0.00 0.00 23897.61 0.00 -0.00 0.00 -912.83 0.00
PERIMETER_TOP_ZN_4 23-APR-16:51 0.00 0.00 0.00 -48301.01 0.00 0.00 13.14 117.66 464.11 26952.76 0.00 0.00 21189.87 0.00 -0.00 0.00 -436.54 0.00
DATACENTER_BOT_ZN_6 12-MAR-07:01 0.00 0.00 0.00 -12335.45 0.00 0.00 0.00 40.49 5845.82 0.00 0.00 0.00 6449.15 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 26-DEC-09:41 0.00 0.00 0.00 -115818.56 0.00 0.00 1008.50 7287.84 77944.22 0.00 0.00 0.00 29577.99 0.00 -0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 26-DEC-09:41 0.00 0.00 0.00 -11696.39 0.00 0.00 100.85 728.78 7794.42 0.00 0.00 0.00 3072.34 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 31-MAR-15:52 0.00 0.00 0.00 -525101.16 0.00 0.00 2723.28 8217.58 284724.39 0.00 0.00 0.00 229435.90 0.00 -0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 25-FEB-04:01 0.00 -21404.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21404.69 0.00 -0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 02-DEC-02:61 0.00 -259287.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 301708.62 0.00 -0.00 0.00 -42421.12 0.00
TOPFLOOR_PLENUM 30-JUN-14:00 0.00 -37248.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 216.41 37032.03 0.00 -0.00 0.00 0.00 0.00
Total Facility 07-JUL-05:01 0.00 27334.06 0.00 -2284944.80 0.00 0.00 16307.27 54433.43 497997.76 164863.68 0.00 0.00 1575380.64 0.00 -45146.07 0.00 -6225.97 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 06-JAN-07:10 0.00 0.00 95204.70 0.00 0.00 0.00 2152.86 9714.93 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -120530.03
CORE_BOTTOM 02-JAN-05:01 0.00 0.00 19864.71 0.00 0.00 0.00 0.00 2908.23 5937.65 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -28710.59
CORE_MID 02-JAN-04:01 0.00 0.00 682329.88 0.00 0.00 0.00 0.00 14541.15 59376.23 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -756247.26
CORE_TOP 09-JAN-04:01 0.00 0.00 140107.80 0.00 0.00 0.00 0.00 1454.11 5937.62 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -147499.54
PERIMETER_BOT_ZN_3 24-DEC-08:11 0.00 0.00 25491.42 0.00 0.00 0.00 89.42 182.58 720.18 0.00 0.00 0.00 0.00 0.00 -13284.75 0.00 -1852.59 -11346.27
PERIMETER_BOT_ZN_2 25-DEC-04:51 0.00 0.00 24593.62 0.00 0.00 0.00 0.00 117.66 360.35 0.00 0.00 0.00 0.00 0.00 -8714.50 0.00 -822.56 -15534.58
PERIMETER_BOT_ZN_1 24-DEC-08:11 0.00 0.00 34454.75 0.00 0.00 0.00 90.20 182.58 720.19 0.00 0.00 0.00 0.00 0.00 -3960.38 0.00 -1849.54 -29637.81
PERIMETER_BOT_ZN_4 02-JAN-04:01 0.00 0.00 23329.38 0.00 0.00 0.00 0.00 117.66 480.46 0.00 0.00 0.00 0.00 0.00 -6816.07 0.00 -750.29 -16361.15
PERIMETER_MID_ZN_3 24-DEC-09:21 0.00 0.00 367402.72 0.00 0.00 0.00 940.68 1825.79 7201.84 0.00 0.00 0.00 0.00 0.00 -116791.32 0.00 -46006.99 -214572.71
PERIMETER_MID_ZN_2 12-FEB-23:01 0.00 0.00 308601.71 0.00 0.00 0.00 0.00 1176.61 3603.51 0.00 0.00 0.00 0.00 0.00 -63121.16 0.00 -44875.53 -205385.13
PERIMETER_MID_ZN_1 12-FEB-23:01 0.00 0.00 394674.10 0.00 0.00 0.00 0.00 1825.83 5591.79 0.00 0.00 0.00 0.00 0.00 -95728.00 0.00 -66947.50 -239416.22
PERIMETER_MID_ZN_4 12-FEB-23:01 0.00 0.00 321568.33 0.00 0.00 0.00 0.00 1176.61 3603.49 0.00 0.00 0.00 0.00 0.00 -67645.22 0.00 -44959.34 -213743.86
PERIMETER_TOP_ZN_3 24-DEC-08:41 0.00 0.00 50957.65 0.00 0.00 0.00 96.19 182.58 720.18 0.00 0.00 0.00 0.00 0.00 -12161.16 0.00 -5406.78 -34388.67
PERIMETER_TOP_ZN_2 24-DEC-08:61 0.00 0.00 34695.06 0.00 0.00 0.00 61.91 117.66 464.11 0.00 0.00 0.00 0.00 0.00 -8299.11 0.00 -3287.18 -23752.45
PERIMETER_TOP_ZN_1 24-DEC-08:61 0.00 0.00 51286.42 0.00 0.00 0.00 95.82 182.58 720.19 0.00 0.00 0.00 0.00 0.00 -12488.62 0.00 -4942.68 -34853.71
PERIMETER_TOP_ZN_4 13-FEB-03:51 0.00 0.00 38565.13 0.00 0.00 0.00 0.00 117.66 480.46 0.00 0.00 0.00 0.00 0.00 -7449.42 0.00 -4274.64 -27439.19
DATACENTER_BOT_ZN_6 02-DEC-01:52 0.00 0.00 2082.82 0.00 0.00 0.00 0.00 40.49 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -9917.73
DATACENTER_MID_ZN_6 21-DEC-00:02 0.00 0.00 17937.63 0.00 0.00 0.00 0.00 404.88 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -96286.73
DATACENTER_TOP_ZN_6 12-MAR-07:02 0.00 0.00 2141.16 0.00 0.00 0.00 3.56 40.49 5845.82 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -8031.03
DATACENTER_BASEMENT_ZN_6 22-OCT-09:51 0.00 0.00 26067.48 0.00 0.00 0.00 152.42 456.53 189816.26 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -216492.70
GROUNDFLOOR_PLENUM 26-MAR-15:31 21831.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -898.02 -20933.21
MIDFLOOR_PLENUM 02-JAN-06:12 280734.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -6028.08 -274706.04
TOPFLOOR_PLENUM 06-JAN-05:11 76147.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -3792.84 -72354.38
Total Facility 02-JAN-05:21 102372.37 92045.57 2254913.88 -92045.57 0.00 0.00 0.00 54433.43 232425.23 0.00 0.00 0.00 0.00 0.00 -387720.87 0.00 -110414.39 -2146009.65



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 16.2459 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 13.1645 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 164.5350 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 122.2745 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 20.3387 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 15.0188 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 7.4989 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 7.4989 0.1600 1.0000 Not calculated 1.2002 0.1600    
AIRLOOP DATACENTER BASEMENT 32.8850 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 32.8850 0.0103 1.0000 Not calculated 0.3384 0.0103    
AIRLOOP DATACENTER BOT 0.8150 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.8150 0.0192 1.0000 Not calculated 0.0156 0.0192    
AIRLOOP DATACENTER MID 7.8682 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 7.8682 0.0199 1.0000 Not calculated 0.1563 0.0199    
AIRLOOP DATACENTER TOP 0.8079 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.8079 0.0193 1.0000 Not calculated 0.0156 0.0193    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 8.1229 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.8738 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 82.2675 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 49.3605 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 10.1693 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 6.1016 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 2.2497 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 2.2497 1.0000 1.0000 Not calculated 1.2002 0.5335    
AIRLOOP DATACENTER BASEMENT 16.4425 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 16.4425 1.0000 1.0000 Not calculated 0.3384 0.0206    
AIRLOOP DATACENTER BOT 0.8150 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.8150 1.0000 1.0000 Not calculated 0.0156 0.0192    
AIRLOOP DATACENTER MID 7.8682 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 7.8682 1.0000 1.0000 Not calculated 0.1563 0.0199    
AIRLOOP DATACENTER TOP 0.8079 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.8079 1.0000 1.0000 Not calculated 0.0156 0.0193    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT 7.4989 7.4989 2.2497 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.7664 7.7664 2.3299 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 73.3455 73.3455 22.0037 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.6544 9.6544 2.8963 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7278 1.7278 0.5183 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.9615 1.9615 0.5884 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4292 2.4292 0.7288 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.3610 2.3610 0.7083 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 22.9360 22.9360 6.8808 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 20.9207 20.9207 6.2762 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 24.8166 24.8166 7.4450 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 22.5162 22.5162 6.7549 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.0613 3.0613 0.9184 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.0963 2.0963 0.6289 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.1145 3.1145 0.9344 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4122 2.4122 0.7237 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8150 0.8150 0.8150 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 7.8682 7.8682 7.8682 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8079 0.8079 0.8079 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT 32.8850 32.8850 16.4425 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 16.2459 13.1645 16.2459 4.8738 0.0000 1.0000
VAV_MID WITH REHEAT 164.5350 122.2745 164.5350 49.3605 0.0000 1.0000
VAV_TOP WITH REHEAT 20.3387 15.0188 20.3387 6.1016 0.0000 1.0000
CAV_BAS 7.4989 7.4989 7.4989 2.2497 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 32.8850 32.8850 32.8850 16.4425 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.8150 0.8150 0.8150 0.8150 0.0156 1.0000
AIRLOOP DATACENTER MID 7.8682 7.8682 7.8682 7.8682 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.8079 0.8079 0.8079 0.8079 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT 2.2497 2.2497 2.2497 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.8832 3.8832 2.3299 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 36.6728 36.6728 22.0037 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.8272 4.8272 2.8963 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8639 0.8639 0.5183 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9807 0.9807 0.5884 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2146 1.2146 0.7288 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1805 1.1805 0.7083 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.4680 11.4680 6.8808 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.4603 10.4603 6.2762 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 12.4083 12.4083 7.4450 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.2581 11.2581 6.7549 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5306 1.5306 0.9184 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0482 1.0482 0.6289 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5573 1.5573 0.9344 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2061 1.2061 0.7237 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8150 0.8150 0.8150 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 7.8682 7.8682 7.8682 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8079 0.8079 0.8079 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT 16.4425 16.4425 16.4425 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 8.1229 4.8738 4.8738 4.8738 0.0000 1.0000
VAV_MID WITH REHEAT 82.2675 49.3605 49.3605 49.3605 0.0000 1.0000
VAV_TOP WITH REHEAT 10.1693 6.1016 6.1016 6.1016 0.0000 1.0000
CAV_BAS 2.2497 2.2497 2.2497 2.2497 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 16.4425 16.4425 16.4425 16.4425 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.8150 0.8150 0.8150 0.8150 0.0156 1.0000
AIRLOOP DATACENTER MID 7.8682 7.8682 7.8682 7.8682 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.8079 0.8079 0.8079 0.8079 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 129.67
Number of hours cooling loads not met 234.83
Number of hours not met 348.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 8150.49 3228629.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 1735.95 590463.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 5610.74 489900.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 1004.65 64082.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5334.97 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 56.04 3543.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 2505.76 229608.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 61.31 1944.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 3022.89 303816.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 939.44 111901.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 121.82 55784.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 1280.30 100000.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 514.24 62804.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 14676.40 31529.54
Natural Gas 0.00 8150.49
Additional 0.00 0.00
Total 14676.40 39680.02


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 121.13
Space Heating 0.00
Space Cooling 37.48
Fans (All) 65.26
Service Water Heating 11.10
Receptacle Equipment 316.85
Miscellaneous (All) 680.68
Subtotal 680.68


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 175.96
Service Water Heating 0.00
Miscellaneous (All) 175.96
Subtotal 175.96


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 14.14
Space Heating 20.54
Space Cooling 4.37
Fans (All) 7.62
Service Water Heating 1.30
Receptacle Equipment 36.99
Miscellaneous 15.04


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
ELEVATOR_RUNNING_SCH 675. 3744.
ELEVATOR_STANDBY_SCH 7740. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2939. 8760.
LTG_SCH_DATACENTER 2939. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4049. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 2347. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365
HTGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL January 20.44 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8516.00 244.00 0.00 0.00 0.00
CORE_BOTTOM 8727.50 32.50 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8759.17 0.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8739.33 20.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8734.50 25.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8486.83 273.17 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8759.00 1.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8733.17 26.83 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8728.33 31.67 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8707.33 52.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8758.00 2.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8737.33 22.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8739.00 21.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8716.83 43.17 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 6449.50 2212.83 97.67 0.00 0.00
DATACENTER_MID_ZN_6 6502.33 2175.33 82.33 0.00 0.00
DATACENTER_TOP_ZN_6 6482.67 2244.17 33.17 0.00 0.00
DATACENTER_BASEMENT_ZN_6 7473.00 1287.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8739.33 20.67 0.00 0.00 0.00
Min 6449.50 0.00 0.00 0.00 0.00
Max 8760.00 2244.17 97.67 0.00 0.00
Average 8370.83 379.90 9.27 0.00 0.00
Sum 192529.17 8737.67 213.17 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 367869.33 746.67 0.00 0.00 0.00
CORE_BOTTOM 330799.00 14.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330813.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1536.67 722.33 9.00 0.00 0.00
DATACENTER_MID_ZN_6 1548.50 710.50 9.00 0.00 0.00
DATACENTER_TOP_ZN_6 1552.50 706.67 8.83 0.00 0.00
DATACENTER_BASEMENT_ZN_6 84748.67 18646.33 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 367869.33 18646.33 9.00 0.00 0.00
Average 79396.94 936.80 1.17 0.00 0.00
Sum 1826129.67 21546.50 26.83 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8339.83 420.17 0.00 0.00 0.00
CORE_BOTTOM 8265.17 494.83 0.00 0.00 0.00
CORE_MID 8373.67 386.33 0.00 0.00 0.00
CORE_TOP 8600.00 160.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8562.67 197.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8671.17 88.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8602.50 157.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8276.67 483.33 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8632.33 127.67 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8616.33 143.67 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8574.50 185.50 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8477.83 282.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8675.17 84.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8626.50 133.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8621.67 138.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8517.67 242.33 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 7993.17 766.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 7980.50 779.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 7949.00 811.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 7483.83 1276.17 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8392.83 367.17 0.00 0.00 0.00
MIDFLOOR_PLENUM 8596.17 163.83 0.00 0.00 0.00
TOPFLOOR_PLENUM 8354.00 406.00 0.00 0.00 0.00
Min 7483.83 84.83 0.00 0.00 0.00
Max 8675.17 1276.17 0.00 0.00 0.00
Average 8399.27 360.73 0.00 0.00 0.00
Sum 193183.17 8296.83 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 367042.17 1573.83 0.00 0.00 0.00
CORE_BOTTOM 330050.00 763.00 0.00 0.00 0.00
CORE_MID 330232.00 581.00 0.00 0.00 0.00
CORE_TOP 330542.00 271.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1867.50 400.50 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1842.00 426.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1812.17 455.83 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 85145.67 18249.33 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 367042.17 18249.33 0.00 0.00 0.00
Average 79347.07 987.85 0.00 0.00 0.00
Sum 1824982.50 22720.50 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:37

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7

For: Environment

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

For: Environment

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS

For: Environment

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE

For: Environment

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.566717E+11 127840.40 20-JAN-06:01 -6.8 -7.3 0.442904E+10 7044.30 20-JAN-14:00 -5.0 -6.8
February 0.511706E+11 131286.20 09-FEB-06:01 -3.2 -4.5 0.439248E+10 7499.22 07-FEB-14:09 -3.2 -4.5
March 0.561413E+11 130589.47 02-MAR-06:01 -8.3 -8.8 0.565174E+10 7498.39 27-MAR-13:30 6.15 2.33
April 0.529242E+11 122318.50 24-APR-04:11 4.40 3.41 0.527339E+10 7499.30 12-APR-13:50 4.40 3.41
May 0.602321E+11 141290.34 30-MAY-04:12 10.60 8.25 0.576729E+10 7499.46 26-MAY-13:09 10.60 8.25
June 0.626353E+11 140154.55 08-JUN-04:11 8.87 8.40 0.585967E+10 7499.34 13-JUN-09:39 17.23 14.20
July 0.660415E+11 126457.95 10-JUL-04:11 8.33 7.93 0.547048E+10 7618.07 05-JUL-13:39 8.33 7.93
August 0.743529E+11 124610.95 25-AUG-04:11 8.53 8.43 0.610963E+10 7521.78 28-AUG-13:50 20.60 18.71
September 0.643769E+11 139287.92 13-SEP-04:11 3.50 3.23 0.529854E+10 7499.34 19-SEP-09:20 15.93 15.73
October 0.608499E+11 147975.18 23-OCT-04:11 5.60 4.25 0.554796E+10 7499.32 20-OCT-13:09 5.60 4.25
November 0.561191E+11 124419.62 13-NOV-04:01 -8.2 -8.9 0.546666E+10 7499.28 21-NOV-14:09 13.77 12.33
December 0.606006E+11 114538.36 01-DEC-05:01 -18.3 -18.5 0.461101E+10 7482.93 05-DEC-14:00 -0.6 -0.6
                     
Annual Sum or Average 0.722116E+12         0.638779E+11        
Minimum of Months 0.511706E+11 114538.36   -18.3 -18.5 0.439248E+10 7044.30   -5.0 -6.8
Maximum of Months 0.743529E+11 147975.18   10.60 8.43 0.610963E+10 7618.07   20.60 18.71



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.330114E+11 33761.18 20-JAN-16:30 -6.4 -7.8 0.470672E+10 6734.75 13-JAN-14:30 -6.4 -7.8
February 0.316838E+11 38740.60 08-FEB-16:53 3.30 -1.3 0.445256E+10 6734.89 28-FEB-10:20 -5.0 -6.8
March 0.436018E+11 107545.89 28-MAR-05:01 1.70 0.50 0.542506E+10 6734.89 08-MAR-10:09 1.70 0.50
April 0.489935E+11 114350.32 24-APR-04:11 4.40 3.41 0.486792E+10 6734.88 07-APR-09:00 4.40 3.41
May 0.558684E+11 120351.10 30-MAY-04:12 10.60 8.25 0.528086E+10 6734.89 15-MAY-09:20 10.60 8.25
June 0.609581E+11 118583.07 26-JUN-04:11 16.87 15.70 0.526712E+10 6734.90 13-JUN-09:00 16.87 15.70
July 0.666176E+11 122183.51 31-JUL-04:11 15.20 13.38 0.489714E+10 6734.90 27-JUL-13:39 15.20 13.38
August 0.713459E+11 120590.04 28-AUG-04:11 13.90 12.96 0.549779E+10 6734.88 03-AUG-09:00 13.90 12.96
September 0.518920E+11 116605.74 05-SEP-04:12 6.33 5.88 0.487344E+10 6734.92 14-SEP-09:09 13.27 10.50
October 0.463864E+11 111747.50 23-OCT-04:11 5.60 4.25 0.505440E+10 6734.91 25-OCT-09:00 3.30 3.04
November 0.415403E+11 107809.90 15-NOV-06:01 -1.4 -1.4 0.499202E+10 6734.90 20-NOV-10:09 6.28 5.15
December 0.374746E+11 42670.36 06-DEC-06:01 -0.8 -0.8 0.474709E+10 6734.89 21-DEC-10:39 -24.3 -24.7
                     
Annual Sum or Average 0.589374E+12         0.600621E+11        
Minimum of Months 0.316838E+11 33761.18   -6.4 -7.8 0.445256E+10 6734.75   -24.3 -24.7
Maximum of Months 0.713459E+11 122183.51   16.87 15.70 0.549779E+10 6734.92   16.87 15.70



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.285262E+11 24795.51 27-JAN-16:37 -15.9 -16.8 0.430255E+10 6734.42 27-JAN-14:00 -15.9 -16.8
February 0.282551E+11 29081.23 08-FEB-16:53 3.30 -1.3 0.409411E+10 6734.87 10-FEB-14:09 -12.6 -13.9
March 0.348271E+11 37494.44 31-MAR-15:53 8.90 3.77 0.516402E+10 6734.89 24-MAR-09:09 8.90 3.77
April 0.360352E+11 99255.41 14-APR-05:01 2.12 1.45 0.476079E+10 6734.88 18-APR-09:09 17.88 10.72
May 0.468851E+11 108482.17 30-MAY-04:12 10.60 8.25 0.525615E+10 6734.91 15-MAY-09:20 10.60 8.25
June 0.510107E+11 107551.91 28-JUN-04:11 15.20 14.63 0.525059E+10 6734.90 13-JUN-09:00 15.20 14.63
July 0.512670E+11 107505.30 31-JUL-04:11 15.20 13.38 0.488750E+10 6734.91 27-JUL-13:50 15.20 13.38
August 0.525043E+11 104865.63 25-AUG-04:11 8.53 8.43 0.547689E+10 6734.88 03-AUG-09:00 8.53 8.43
September 0.418155E+11 102878.00 01-SEP-04:11 15.93 15.93 0.483973E+10 6734.91 14-SEP-09:09 13.27 10.50
October 0.351380E+11 98846.18 20-OCT-05:01 7.52 7.52 0.495124E+10 6734.90 25-OCT-09:00 3.30 3.04
November 0.302828E+11 35374.40 17-NOV-16:13 8.90 2.59 0.466664E+10 6734.89 01-NOV-13:50 8.90 2.59
December 0.297350E+11 25633.80 01-DEC-17:00 -19.7 -20.2 0.422948E+10 6734.83 01-DEC-14:30 -19.7 -20.2
                     
Annual Sum or Average 0.466282E+12         0.578797E+11        
Minimum of Months 0.282551E+11 24795.51   -19.7 -20.2 0.409411E+10 6734.42   -19.7 -20.2
Maximum of Months 0.525043E+11 108482.17   15.93 15.93 0.547689E+10 6734.91   17.88 14.63



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.134656E+11 22148.41 19-JAN-17:00 -2.8 -3.6 0.375897E+10 5509.70 19-JAN-14:00 -2.8 -3.6
February 0.161625E+11 25266.07 08-FEB-17:00 3.30 -1.3 0.348981E+10 5980.85 08-FEB-14:00 3.30 -1.3
March 0.244917E+11 27423.10 31-MAR-16:00 8.90 3.77 0.432625E+10 6323.08 29-MAR-13:00 8.90 3.77
April 0.300985E+11 41960.76 13-APR-16:00 20.00 8.11 0.416000E+10 6734.84 14-APR-13:30 16.10 7.07
May 0.439824E+11 129203.89 26-MAY-05:02 19.40 15.69 0.496966E+10 6734.87 19-MAY-09:20 19.40 15.69
June 0.515512E+11 125473.27 28-JUN-05:01 15.15 14.73 0.512904E+10 6734.90 13-JUN-09:00 15.15 14.73
July 0.528944E+11 127457.15 13-JUL-05:01 15.00 14.67 0.479525E+10 6734.91 27-JUL-13:00 16.70 15.64
August 0.510499E+11 127150.02 10-AUG-05:01 15.50 14.84 0.531928E+10 6734.91 10-AUG-13:39 19.03 16.37
September 0.363261E+11 123799.95 01-SEP-05:02 15.68 15.63 0.442926E+10 6734.79 12-SEP-13:39 13.13 10.05
October 0.268943E+11 37090.94 20-OCT-15:53 18.30 9.93 0.417115E+10 6734.86 20-OCT-13:00 18.30 9.93
November 0.207981E+11 26047.45 01-NOV-16:00 17.80 13.26 0.391827E+10 6096.22 17-NOV-14:00 10.60 3.43
December 0.142833E+11 22426.17 28-DEC-17:00 -2.4 -4.0 0.363195E+10 5604.32 28-DEC-14:00 -2.4 -4.0
                     
Annual Sum or Average 0.381998E+12         0.520989E+11        
Minimum of Months 0.134656E+11 22148.41   -2.8 -4.0 0.348981E+10 5509.70   -2.8 -4.0
Maximum of Months 0.528944E+11 129203.89   20.00 15.69 0.531928E+10 6734.91   19.40 16.37



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.243096E+09 3356.58 30-JAN-06:05 -4.0 -4.6 0.464750E+09 632.65 19-JAN-14:09 -4.0 -4.6
February 0.918997E+09 3978.68 08-FEB-14:41 5.00 -0.5 0.427368E+09 708.70 08-FEB-14:50 5.00 -0.5
March 0.280196E+10 5414.67 26-MAR-16:51 10.00 4.91 0.532534E+09 807.01 28-MAR-13:00 6.10 2.91
April 0.555781E+10 7835.41 18-APR-14:00 17.80 10.49 0.532867E+09 845.63 14-APR-13:30 17.80 10.49
May 0.915366E+10 11197.07 23-MAY-14:40 26.40 17.14 0.640944E+09 845.64 24-MAY-09:09 22.38 16.32
June 0.113813E+11 15333.56 29-JUN-04:11 22.20 19.58 0.655155E+09 845.65 14-JUN-13:00 22.20 19.58
July 0.125593E+11 18245.13 03-JUL-04:11 18.13 16.58 0.611931E+09 845.64 27-JUL-13:39 16.33 15.15
August 0.115684E+11 12012.62 08-AUG-15:00 30.60 23.36 0.680805E+09 845.65 10-AUG-13:30 18.85 16.08
September 0.730349E+10 9804.07 01-SEP-15:10 26.10 17.79 0.575246E+09 845.64 11-SEP-13:50 18.90 14.67
October 0.525264E+10 6614.31 01-OCT-14:31 15.20 9.17 0.541156E+09 845.63 20-OCT-13:00 18.90 10.07
November 0.299850E+10 5529.25 21-NOV-06:02 10.10 9.75 0.493376E+09 836.20 01-NOV-13:00 10.10 9.75
December 0.520074E+09 3543.25 06-DEC-06:02 -0.8 -0.8 0.449076E+09 653.68 05-DEC-14:09 -0.8 -0.8
                     
Annual Sum or Average 0.702592E+11         0.660521E+10        
Minimum of Months 0.243096E+09 3356.58   -4.0 -4.6 0.427368E+09 632.65   -4.0 -4.6
Maximum of Months 0.125593E+11 18245.13   30.60 23.36 0.680805E+09 845.65   22.38 19.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.389107E+09 3920.79 25-JAN-10:10 -23.2 -23.5 0.299454E+09 417.98 25-JAN-10:20 -23.1 -23.4
February 0.142638E+10 5583.43 28-FEB-09:55 -6.1 -7.7 0.278191E+09 531.95 28-FEB-10:09 -5.5 -7.3
March 0.353296E+10 11457.46 26-MAR-10:11 3.33 0.54 0.353099E+09 544.96 23-MAR-09:09 3.33 0.54
April 0.689432E+10 32711.07 30-APR-08:51 7.80 4.07 0.352037E+09 544.96 18-APR-09:09 7.80 4.07
May 0.985265E+10 23477.94 21-MAY-09:02 12.52 7.56 0.406226E+09 544.98 24-MAY-09:09 22.38 16.32
June 0.119452E+11 38626.46 25-JUN-08:61 24.08 20.82 0.415269E+09 544.98 14-JUN-13:00 24.08 20.82
July 0.129573E+11 33477.26 23-JUL-09:31 26.13 22.79 0.390150E+09 544.96 31-JUL-13:00 20.60 14.60
August 0.112592E+11 35376.94 20-AUG-10:11 23.17 15.92 0.421917E+09 544.97 04-AUG-09:00 23.17 15.92
September 0.785880E+10 17545.77 24-SEP-09:32 15.20 10.71 0.354035E+09 544.97 14-SEP-09:09 15.20 10.71
October 0.495657E+10 32004.90 22-OCT-09:11 13.67 11.29 0.329715E+09 544.96 19-OCT-09:00 13.67 11.29
November 0.255968E+10 5832.11 11-NOV-10:21 -3.0 -5.4 0.308278E+09 531.73 16-NOV-10:09 2.15 -0.3
December 0.434614E+09 4098.94 28-DEC-10:00 -3.2 -4.3 0.289225E+09 428.77 01-DEC-10:20 -3.2 -4.3
                     
Annual Sum or Average 0.740668E+11         0.419760E+10        
Minimum of Months 0.389107E+09 3920.79   -23.2 -23.5 0.278191E+09 417.98   -23.1 -23.4
Maximum of Months 0.129573E+11 38626.46   26.13 22.79 0.421917E+09 544.98   24.08 20.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.342094E+10 19197.27 27-JAN-13:30 -15.0 -16.1 0.507505E+09 845.65 05-JAN-14:20 -15.0 -16.1
February 0.554818E+10 39223.81 20-FEB-13:31 4.83 0.32 0.484539E+09 845.65 28-FEB-14:09 4.27 0.38
March 0.756829E+10 45028.44 26-MAR-13:31 8.70 4.42 0.584002E+09 845.65 20-MAR-13:00 8.70 4.42
April 0.106339E+11 41049.98 23-APR-13:12 23.33 15.57 0.547436E+09 845.91 13-APR-13:30 23.33 15.57
May 0.133065E+11 39938.88 21-MAY-13:41 20.83 11.09 0.626244E+09 845.67 10-MAY-13:00 20.83 11.09
June 0.148012E+11 42106.75 18-JUN-13:01 26.20 17.95 0.637272E+09 845.70 14-JUN-13:00 26.20 17.95
July 0.171092E+11 42999.19 16-JUL-12:51 23.90 18.44 0.601044E+09 845.79 31-JUL-13:30 20.00 14.03
August 0.173874E+11 45607.04 20-AUG-12:51 25.00 15.37 0.663619E+09 846.20 25-AUG-13:00 28.30 18.83
September 0.129513E+11 43921.08 03-SEP-14:21 21.40 16.15 0.562057E+09 846.25 01-SEP-13:00 21.40 16.15
October 0.914709E+10 49044.76 22-OCT-13:11 18.67 12.99 0.539042E+09 845.65 19-OCT-09:00 18.67 12.99
November 0.564754E+10 22687.20 17-NOV-13:02 10.10 3.25 0.520218E+09 845.65 29-NOV-10:30 -8.6 -9.6
December 0.260971E+10 15187.50 20-DEC-13:15 -21.1 -21.6 0.475293E+09 845.65 20-DEC-14:20 -19.8 -20.5
                     
Annual Sum or Average 0.120131E+12         0.674827E+10        
Minimum of Months 0.260971E+10 15187.50   -21.1 -21.6 0.475293E+09 845.65   -19.8 -20.5
Maximum of Months 0.173874E+11 49044.76   26.20 18.44 0.663619E+09 846.25   28.30 18.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.127284E+10 6319.09 27-JAN-15:50 -14.4 -15.6 0.304105E+09 485.44 27-JAN-15:00 -14.4 -15.6
February 0.277981E+10 10727.06 28-FEB-15:32 6.10 1.55 0.286613E+09 544.96 28-FEB-14:50 6.10 1.55
March 0.627675E+10 43017.52 26-MAR-16:51 10.00 4.91 0.354711E+09 544.96 31-MAR-13:00 8.30 3.10
April 0.998339E+10 43396.05 23-APR-16:31 26.30 16.77 0.346376E+09 544.96 14-APR-13:30 26.30 16.77
May 0.125225E+11 44043.34 21-MAY-16:21 22.25 11.27 0.396749E+09 544.97 10-MAY-13:00 22.25 11.27
June 0.139524E+11 41165.46 17-JUN-19:41 18.03 12.13 0.409122E+09 544.99 14-JUN-13:00 18.03 12.13
July 0.163868E+11 48077.44 16-JUL-16:51 21.10 15.60 0.391065E+09 544.97 31-JUL-13:00 20.60 14.60
August 0.158818E+11 40868.92 05-AUG-17:41 22.30 14.14 0.434463E+09 544.98 22-AUG-13:09 23.98 16.30
September 0.986625E+10 45612.43 03-SEP-17:01 21.52 16.01 0.349555E+09 544.96 07-SEP-13:39 23.90 14.37
October 0.718342E+10 38612.41 22-OCT-15:51 18.90 12.36 0.335968E+09 544.96 17-OCT-13:00 18.90 12.36
November 0.481164E+10 8707.11 17-NOV-15:23 10.30 3.32 0.320628E+09 544.96 16-NOV-14:39 10.30 3.32
December 0.257183E+10 5972.76 20-DEC-15:30 -19.5 -20.3 0.293609E+09 471.12 20-DEC-14:00 -19.5 -20.3
                     
Annual Sum or Average 0.103489E+12         0.422296E+10        
Minimum of Months 0.127284E+10 5972.76   -19.5 -20.3 0.286613E+09 471.12   -19.5 -20.3
Maximum of Months 0.163868E+11 48077.44   26.30 16.77 0.434463E+09 544.99   26.30 16.77



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 34341681.26 4347.62 19-JAN-06:04 -3.3 -3.7 0.463032E+09 626.08 09-JAN-10:09 -3.3 -3.7
February 0.224087E+09 4455.85 22-FEB-06:04 -10.3 -10.6 0.420843E+09 625.79 13-FEB-10:09 -10.3 -10.6
March 0.126103E+10 5562.82 31-MAR-14:02 8.30 3.02 0.507328E+09 679.44 28-MAR-13:00 8.30 3.02
April 0.377870E+10 8813.13 23-APR-16:22 26.40 16.81 0.471759E+09 796.16 18-APR-13:00 26.40 16.81
May 0.865774E+10 10450.69 24-MAY-14:30 27.45 17.67 0.594948E+09 845.63 19-MAY-13:20 27.45 17.67
June 0.108686E+11 18337.60 28-JUN-05:01 15.15 14.73 0.630211E+09 845.64 14-JUN-13:00 15.15 14.73
July 0.111923E+11 14727.03 21-JUL-05:01 17.98 17.55 0.594707E+09 845.63 17-JUL-13:30 17.98 17.55
August 0.101949E+11 10797.24 09-AUG-15:30 27.25 21.19 0.634898E+09 845.63 22-AUG-13:09 23.98 16.30
September 0.666636E+10 8691.72 01-SEP-13:30 25.00 18.03 0.512293E+09 844.52 07-SEP-13:00 23.90 14.48
October 0.345766E+10 7266.70 01-OCT-14:11 15.40 9.25 0.478750E+09 723.19 02-OCT-13:50 10.18 9.48
November 0.100074E+10 5397.26 01-NOV-14:02 17.88 13.29 0.461433E+09 707.97 01-NOV-13:00 17.88 13.29
December 43178692.75 4522.43 06-DEC-06:03 -0.8 -0.8 0.446551E+09 625.98 21-DEC-14:09 -17.0 -17.8
                     
Annual Sum or Average 0.573796E+11         0.621675E+10        
Minimum of Months 34341681.26 4347.62   -10.3 -10.6 0.420843E+09 625.79   -17.0 -17.8
Maximum of Months 0.111923E+11 18337.60   27.45 21.19 0.634898E+09 845.64   27.45 17.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 80358400.71 4226.12 25-JAN-11:03 -22.4 -22.8 0.215440E+09 425.04 25-JAN-11:09 -22.4 -22.8
February 0.539761E+09 12822.02 28-FEB-11:01 -2.4 -4.8 0.199568E+09 548.49 28-FEB-11:09 -2.4 -4.8
March 0.213897E+10 19049.51 31-MAR-10:01 2.07 -0.7 0.252272E+09 548.49 23-MAR-10:09 2.07 -0.7
April 0.529565E+10 17857.42 22-APR-10:02 13.58 4.72 0.251974E+09 548.50 18-APR-10:09 13.58 4.72
May 0.900738E+10 37742.55 21-MAY-08:51 12.20 7.39 0.293254E+09 548.51 23-MAY-10:09 18.85 13.45
June 0.115740E+11 41588.27 25-JUN-08:11 24.27 20.87 0.302399E+09 548.52 07-JUN-12:09 24.27 20.87
July 0.122942E+11 36350.01 23-JUL-09:31 26.13 22.79 0.286262E+09 548.51 31-JUL-14:09 20.50 14.52
August 0.100032E+11 34918.23 20-AUG-09:12 21.33 15.66 0.303759E+09 548.52 04-AUG-10:09 21.33 15.66
September 0.638722E+10 27263.00 10-SEP-09:42 15.22 10.50 0.253437E+09 548.50 07-SEP-14:09 15.22 10.50
October 0.280878E+10 16850.12 19-OCT-10:01 14.27 10.24 0.235157E+09 548.49 25-OCT-10:09 4.05 3.56
November 0.876224E+09 11966.11 16-NOV-11:01 4.68 0.79 0.220234E+09 548.49 01-NOV-14:09 4.68 0.79
December 88325029.07 4654.27 28-DEC-11:02 -2.3 -3.6 0.207651E+09 441.88 28-DEC-11:09 -2.3 -3.6
                     
Annual Sum or Average 0.610940E+11         0.302141E+10        
Minimum of Months 80358400.71 4226.12   -22.4 -22.8 0.199568E+09 425.04   -22.4 -22.8
Maximum of Months 0.122942E+11 41588.27   26.13 22.79 0.303759E+09 548.52   24.27 20.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.329413E+10 22180.00 27-JAN-13:40 -14.8 -15.9 0.502861E+09 845.65 05-JAN-14:30 -14.8 -15.9
February 0.577820E+10 39149.95 20-FEB-14:21 6.95 1.52 0.479270E+09 845.65 28-FEB-10:30 -4.4 -6.4
March 0.748845E+10 47604.79 26-MAR-14:21 9.75 4.96 0.577202E+09 845.72 31-MAR-13:20 7.23 2.44
April 0.972347E+10 46855.01 23-APR-13:01 23.07 15.44 0.536296E+09 846.24 13-APR-13:30 23.07 15.44
May 0.128855E+11 41520.47 21-MAY-14:51 22.80 11.46 0.614772E+09 846.34 18-MAY-13:20 22.80 11.46
June 0.141885E+11 41925.53 25-JUN-11:31 27.07 21.57 0.625934E+09 846.28 30-JUN-13:20 31.50 24.23
July 0.157954E+11 42417.02 23-JUL-13:32 30.00 22.59 0.592061E+09 846.32 31-JUL-13:20 19.80 13.84
August 0.159959E+11 42405.75 13-AUG-13:32 23.13 14.35 0.645388E+09 846.44 29-AUG-13:20 24.80 19.85
September 0.126457E+11 48245.93 04-SEP-12:01 15.68 9.30 0.548739E+09 849.25 01-SEP-13:20 15.68 9.30
October 0.854897E+10 52647.81 22-OCT-13:11 18.67 12.99 0.524199E+09 846.49 19-OCT-13:30 18.67 12.99
November 0.459578E+10 24628.61 17-NOV-13:02 10.10 3.25 0.504651E+09 845.65 17-NOV-10:30 10.10 3.25
December 0.197802E+10 15916.43 20-DEC-13:24 -20.9 -21.5 0.469902E+09 845.65 26-DEC-14:09 -19.4 -20.1
                     
Annual Sum or Average 0.112918E+12         0.662127E+10        
Minimum of Months 0.197802E+10 15916.43   -20.9 -21.5 0.469902E+09 845.65   -19.4 -20.1
Maximum of Months 0.159959E+11 52647.81   30.00 22.59 0.645388E+09 849.25   31.50 24.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.391306E+09 5417.19 27-JAN-15:50 -14.4 -15.6 0.299584E+09 449.91 27-JAN-15:00 -14.4 -15.6
February 0.120112E+10 8143.48 08-FEB-16:23 3.85 -1.1 0.277864E+09 521.20 08-FEB-16:00 3.30 -1.3
March 0.295961E+10 37181.96 26-MAR-17:01 9.82 4.83 0.337994E+09 521.20 31-MAR-15:00 8.90 3.77
April 0.581861E+10 44931.38 23-APR-17:41 25.68 16.51 0.313345E+09 544.36 13-APR-13:00 25.68 16.51
May 0.104542E+11 44668.79 14-MAY-17:11 20.00 8.46 0.372991E+09 544.95 17-MAY-13:50 26.02 16.16
June 0.117723E+11 39865.63 17-JUN-19:41 18.03 12.13 0.386342E+09 544.97 14-JUN-13:00 18.03 12.13
July 0.127408E+11 43471.51 04-JUL-16:11 24.27 19.86 0.367949E+09 544.96 17-JUL-13:30 18.60 14.13
August 0.114098E+11 38583.77 05-AUG-17:41 22.30 14.14 0.393583E+09 544.95 02-AUG-13:00 22.30 14.14
September 0.729462E+10 38259.10 03-SEP-17:11 21.33 15.90 0.322302E+09 544.68 07-SEP-13:00 23.90 14.48
October 0.393682E+10 23440.36 22-OCT-15:51 18.90 12.36 0.314820E+09 521.20 06-OCT-15:00 18.90 12.36
November 0.137164E+10 6107.61 17-NOV-15:40 10.20 3.28 0.300626E+09 490.62 17-NOV-15:50 10.10 3.24
December 0.221156E+09 4365.49 20-DEC-15:30 -19.5 -20.3 0.288024E+09 403.43 11-DEC-14:00 -19.5 -20.3
                     
Annual Sum or Average 0.695719E+11         0.397543E+10        
Minimum of Months 0.221156E+09 4365.49   -19.5 -20.3 0.277864E+09 403.43   -19.5 -20.3
Maximum of Months 0.127408E+11 44931.38   25.68 19.86 0.393583E+09 544.97   26.02 16.51



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 26420151.92 5219.38 21-JAN-17:01 -5.0 -7.1 0.462660E+09 626.08 09-JAN-14:00 -5.0 -7.1
February 0.146975E+09 5979.91 07-FEB-06:04 -7.7 -8.0 0.420278E+09 625.80 10-FEB-10:09 -18.5 -19.0
March 0.662267E+09 6000.96 23-MAR-05:04 -17.1 -17.4 0.504295E+09 625.80 15-MAR-09:09 -17.1 -17.4
April 0.302061E+10 10965.48 23-APR-16:11 26.50 16.86 0.456386E+09 743.93 18-APR-13:00 26.50 16.86
May 0.870990E+10 11462.68 18-MAY-15:00 28.90 16.60 0.553885E+09 845.62 24-MAY-13:20 26.57 17.52
June 0.115148E+11 17679.81 28-JUN-05:01 15.15 14.73 0.592122E+09 845.64 21-JUN-13:50 15.15 14.73
July 0.120685E+11 13587.73 23-JUL-16:11 29.43 22.47 0.562547E+09 845.62 12-JUL-13:20 29.43 22.47
August 0.106731E+11 11907.57 08-AUG-15:50 30.60 23.05 0.589999E+09 845.61 23-AUG-13:20 25.77 20.28
September 0.584397E+10 10973.44 03-SEP-14:21 21.40 16.15 0.475102E+09 811.68 01-SEP-13:00 21.40 16.15
October 0.195976E+10 8043.88 22-OCT-14:31 19.40 12.77 0.467285E+09 686.27 20-OCT-13:00 19.40 12.77
November 0.441425E+09 6021.39 01-NOV-15:00 18.30 13.44 0.458983E+09 635.22 01-NOV-13:00 18.30 13.44
December 32372159.09 6148.57 06-DEC-06:03 -0.8 -0.8 0.446110E+09 626.08 11-DEC-14:00 -17.8 -18.7
                     
Annual Sum or Average 0.551001E+11         0.598965E+10        
Minimum of Months 26420151.92 5219.38   -17.1 -17.4 0.420278E+09 625.80   -18.5 -19.0
Maximum of Months 0.120685E+11 17679.81   30.60 23.05 0.592122E+09 845.64   29.43 22.47



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 19941136.60 4081.92 17-JAN-06:04 -5.9 -6.4 0.298164E+09 403.48 19-JAN-14:09 -2.8 -3.6
February 0.410138E+09 4713.29 28-FEB-10:30 -4.4 -6.4 0.271314E+09 449.89 28-FEB-10:39 -3.9 -5.9
March 0.175081E+10 6670.72 31-MAR-09:51 1.70 -0.9 0.336176E+09 544.96 20-MAR-09:39 1.70 -0.9
April 0.465312E+10 14767.91 18-APR-09:25 18.05 10.95 0.334006E+09 544.96 18-APR-09:09 18.05 10.95
May 0.858625E+10 18002.41 18-MAY-09:30 24.55 16.00 0.389228E+09 544.98 24-MAY-09:09 22.38 16.32
June 0.114468E+11 39501.05 18-JUN-09:51 23.30 16.38 0.407058E+09 544.98 14-JUN-13:00 23.30 16.38
July 0.122474E+11 36347.53 23-JUL-09:31 26.13 22.79 0.386419E+09 544.96 31-JUL-13:00 20.60 14.60
August 0.982544E+10 37552.50 20-AUG-10:21 23.35 15.88 0.404224E+09 544.98 22-AUG-13:09 23.98 16.30
September 0.573194E+10 16921.04 01-SEP-09:30 20.85 17.74 0.331079E+09 544.97 07-SEP-13:09 23.90 14.19
October 0.207840E+10 8720.34 19-OCT-09:33 12.97 9.35 0.310319E+09 544.96 19-OCT-09:00 13.90 10.03
November 0.590543E+09 4370.60 16-NOV-10:01 2.15 -0.3 0.295987E+09 427.79 16-NOV-10:09 2.15 -0.3
December 35046217.53 4187.09 06-DEC-06:03 -0.8 -0.8 0.287499E+09 403.45 11-DEC-14:00 -17.8 -18.7
                     
Annual Sum or Average 0.573758E+11         0.405147E+10        
Minimum of Months 19941136.60 4081.92   -5.9 -6.4 0.271314E+09 403.45   -17.8 -18.7
Maximum of Months 0.122474E+11 39501.05   26.13 22.79 0.407058E+09 544.98   23.98 16.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.266056E+10 19186.38 27-JAN-13:50 -14.6 -15.8 0.489796E+09 845.65 09-JAN-14:20 -14.6 -15.8
February 0.495298E+10 27422.00 28-FEB-13:31 3.33 -0.5 0.463680E+09 845.65 28-FEB-10:50 3.33 -0.5
March 0.623273E+10 54300.19 26-MAR-14:31 10.03 5.07 0.559356E+09 845.65 20-MAR-13:00 10.03 5.07
April 0.856161E+10 56176.46 23-APR-14:51 25.60 16.48 0.519074E+09 845.65 14-APR-13:30 25.60 16.48
May 0.125382E+11 31380.53 14-MAY-14:41 19.82 8.15 0.586412E+09 845.68 10-MAY-13:00 19.82 8.15
June 0.143157E+11 31374.36 18-JUN-14:32 26.30 18.90 0.602564E+09 845.71 14-JUN-13:00 26.30 18.90
July 0.161410E+11 53644.41 16-JUL-14:21 24.15 18.35 0.573195E+09 845.68 31-JUL-13:00 20.60 14.60
August 0.159332E+11 57078.13 20-AUG-13:41 25.00 16.26 0.615326E+09 845.70 22-AUG-13:09 23.98 16.30
September 0.113215E+11 56756.93 04-SEP-12:01 15.68 9.30 0.519455E+09 846.13 01-SEP-13:00 15.68 9.30
October 0.662910E+10 62316.52 22-OCT-13:11 18.67 12.99 0.504419E+09 845.65 19-OCT-09:39 18.67 12.99
November 0.351647E+10 21889.39 17-NOV-13:12 10.20 3.29 0.490417E+09 845.65 07-NOV-14:30 10.20 3.29
December 0.149309E+10 13339.31 26-DEC-13:23 -19.8 -20.4 0.458661E+09 845.65 20-DEC-14:20 -19.8 -20.4
                     
Annual Sum or Average 0.104296E+12         0.638236E+10        
Minimum of Months 0.149309E+10 13339.31   -19.8 -20.4 0.458661E+09 845.65   -19.8 -20.4
Maximum of Months 0.161410E+11 62316.52   26.30 18.90 0.615326E+09 846.13   26.30 18.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.288070E+09 5280.78 27-JAN-15:50 -14.4 -15.6 0.298515E+09 422.49 27-JAN-15:00 -14.4 -15.6
February 0.999657E+09 7970.31 28-FEB-15:51 6.10 1.55 0.275963E+09 521.20 08-FEB-16:49 6.10 1.55
March 0.241695E+10 23680.14 26-MAR-17:11 9.63 4.75 0.335322E+09 521.20 31-MAR-15:00 8.90 3.77
April 0.510533E+10 48298.82 23-APR-16:51 26.10 16.67 0.309176E+09 544.10 13-APR-13:00 26.10 16.67
May 0.996260E+10 47174.20 14-MAY-17:21 20.00 8.49 0.363637E+09 544.95 17-MAY-13:39 25.93 16.13
June 0.116065E+11 42396.48 17-JUN-19:41 18.03 12.13 0.378451E+09 544.98 14-JUN-13:00 18.03 12.13
July 0.127085E+11 48165.04 16-JUL-16:21 21.95 16.03 0.360612E+09 544.96 17-JUL-13:50 19.13 14.51
August 0.111048E+11 41100.15 05-AUG-17:41 22.30 14.14 0.382846E+09 544.95 22-AUG-13:00 24.40 16.49
September 0.636367E+10 46040.32 03-SEP-17:01 21.52 16.01 0.314665E+09 544.95 01-SEP-13:00 21.52 16.01
October 0.285542E+10 13321.75 19-OCT-16:00 21.70 13.55 0.311335E+09 524.96 19-OCT-13:00 21.70 13.55
November 0.937825E+09 6040.97 17-NOV-15:40 10.20 3.28 0.297891E+09 462.96 17-NOV-15:50 10.10 3.24
December 0.123221E+09 4669.35 06-DEC-06:03 -0.8 -0.8 0.287643E+09 403.46 04-DEC-10:50 -0.8 -0.8
                     
Annual Sum or Average 0.644725E+11         0.391606E+10        
Minimum of Months 0.123221E+09 4669.35   -14.4 -15.6 0.275963E+09 403.46   -14.4 -15.6
Maximum of Months 0.127085E+11 48298.82   26.10 16.67 0.382846E+09 544.98   26.10 16.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.207712E+10 20582.03 28-JAN-04:01 -26.7 -26.9 0.00 0.00 01-JAN-00:10 -26.7 -26.9
February 0.217552E+10 21405.67 25-FEB-04:01 -27.5 -27.7 0.00 0.00 01-FEB-00:10 -27.5 -27.7
March 0.420558E+10 18045.35 16-MAR-03:01 -25.8 -25.9 0.00 0.00 01-MAR-00:10 -25.8 -25.9
April 0.650924E+10 10685.43 05-APR-04:01 -12.4 -13.3 0.00 0.00 01-APR-00:10 -12.4 -13.3
May 0.882190E+10 12490.47 30-MAY-04:18 10.60 8.25 0.00 0.00 01-MAY-00:10 10.60 8.25
June 0.104095E+11 10456.81 17-JUN-04:18 4.60 4.37 0.00 0.00 01-JUN-00:10 4.60 4.37
July 0.118024E+11 11549.53 21-JUL-05:02 17.98 17.55 0.00 0.00 01-JUL-00:10 17.98 17.55
August 0.118374E+11 11527.12 28-AUG-05:12 13.90 13.22 0.00 0.00 01-AUG-00:10 13.90 13.22
September 0.827186E+10 11455.01 05-SEP-04:18 6.33 5.88 0.00 0.00 01-SEP-00:10 6.33 5.88
October 0.647824E+10 13716.85 30-OCT-04:01 -10.0 -10.7 0.00 0.00 01-OCT-00:10 -10.0 -10.7
November 0.426891E+10 14671.40 24-NOV-05:01 -10.6 -11.2 0.00 0.00 01-NOV-00:10 -10.6 -11.2
December 0.291628E+10 20186.10 02-DEC-04:01 -26.8 -27.0 0.00 0.00 01-DEC-00:10 -26.8 -27.0
                     
Annual Sum or Average 0.797739E+11         0.00        
Minimum of Months 0.207712E+10 10456.81   -27.5 -27.7 0.00 0.00   -27.5 -27.7
Maximum of Months 0.118374E+11 21405.67   17.98 17.55 0.00 0.00   17.98 17.55



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.342120E+10 24436.17 28-JAN-04:01 -26.7 -26.9 0.00 0.00 01-JAN-00:10 -26.7 -26.9
February 0.314566E+10 25684.29 11-FEB-04:01 -17.1 -17.6 0.00 0.00 01-FEB-00:10 -17.1 -17.6
March 0.325487E+10 25859.63 05-MAR-01:51 -24.4 -24.7 0.00 0.00 01-MAR-00:10 -24.4 -24.7
April 0.411811E+10 19404.89 03-APR-03:01 -7.4 -8.6 0.00 0.00 01-APR-00:10 -7.4 -8.6
May 0.712217E+10 12345.90 30-MAY-05:06 10.60 8.25 0.00 0.00 01-MAY-00:10 10.60 8.25
June 0.868818E+10 11351.84 17-JUN-04:18 4.60 4.37 0.00 0.00 01-JUN-00:10 4.60 4.37
July 0.943745E+10 11372.41 08-JUL-05:05 11.70 10.47 0.00 0.00 01-JUL-00:10 11.70 10.47
August 0.904890E+10 10702.46 25-AUG-05:06 7.88 7.62 0.00 0.00 01-AUG-00:10 7.88 7.62
September 0.651007E+10 10982.66 02-SEP-05:10 13.80 10.55 0.00 0.00 01-SEP-00:10 13.80 10.55
October 0.409396E+10 24636.66 30-OCT-03:01 -9.5 -10.3 0.00 0.00 01-OCT-00:10 -9.5 -10.3
November 0.320356E+10 22171.43 23-NOV-18:41 -9.4 -10.3 0.00 0.00 01-NOV-00:10 -9.4 -10.3
December 0.329928E+10 25928.33 02-DEC-02:61 -25.4 -25.6 0.00 0.00 01-DEC-00:10 -25.4 -25.6
                     
Annual Sum or Average 0.653434E+11         0.00        
Minimum of Months 0.314566E+10 10702.46   -26.7 -26.9 0.00 0.00   -26.7 -26.9
Maximum of Months 0.943745E+10 25928.33   13.80 10.55 0.00 0.00   13.80 10.55



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:01 -21.9 -22.1 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 92200463.97 3357.79 08-FEB-14:21 5.00 -0.5 0.00 0.00 01-FEB-00:10 5.00 -0.5
March 0.112330E+10 9664.56 26-MAR-13:14 8.50 4.25 0.00 0.00 01-MAR-00:10 8.50 4.25
April 0.536584E+10 19424.81 13-APR-14:30 19.45 7.77 0.00 0.00 01-APR-00:10 19.45 7.77
May 0.137393E+11 32990.60 18-MAY-14:00 28.50 16.75 0.00 0.00 01-MAY-00:10 28.50 16.75
June 0.181875E+11 37249.27 30-JUN-14:00 31.10 23.76 0.00 0.00 01-JUN-00:10 31.10 23.76
July 0.203311E+11 33978.59 24-JUL-14:00 29.40 19.87 0.00 0.00 01-JUL-00:10 29.40 19.87
August 0.158322E+11 31787.91 08-AUG-14:05 30.10 22.94 0.00 0.00 01-AUG-00:10 30.10 22.94
September 0.761586E+10 27153.83 01-SEP-14:05 25.68 18.06 0.00 0.00 01-SEP-00:10 25.68 18.06
October 0.205799E+10 14651.49 22-OCT-13:14 18.67 12.99 0.00 0.00 01-OCT-00:10 18.67 12.99
November 0.179133E+09 6021.82 01-NOV-16:10 17.62 13.19 0.00 0.00 01-NOV-00:10 17.62 13.19
December 0.00 0.00 01-DEC-00:01 -8.8 -9.9 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.845244E+11         0.00        
Minimum of Months 0.00 0.00   -21.9 -22.1 0.00 0.00   -21.9 -22.1
Maximum of Months 0.203311E+11 37249.27   31.10 23.76 0.00 0.00   31.10 23.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.100772E+10 5507.27 14-JAN-04:21 -24.7 -24.9 98547020.93 176.71 05-JAN-16:40 -24.7 -24.9
February 0.575370E+10 10916.86 14-FEB-10:01 -24.6 -25.0 87851462.58 206.24 14-FEB-10:09 -24.6 -25.0
March 0.126618E+11 12335.52 12-MAR-07:01 -24.5 -24.8 0.103297E+09 126.82 21-MAR-13:09 0.00 -1.0
April 0.182496E+11 9045.14 23-APR-18:12 24.83 15.88 91605076.43 126.82 19-APR-09:09 24.83 15.88
May 0.448249E+10 3161.67 31-MAY-23:51 11.20 9.10 99233940.42 126.83 26-MAY-13:09 11.20 9.10
June 0.932025E+10 5370.32 30-JUN-23:02 17.35 13.59 98958841.39 126.83 30-JUN-09:09 17.35 13.59
July 0.149938E+11 7253.20 31-JUL-24:00 17.00 15.17 91881266.11 126.82 21-JUL-13:00 17.00 15.17
August 0.198972E+11 8786.90 02-AUG-18:40 18.53 13.51 0.103239E+09 126.83 08-AUG-13:00 30.00 22.85
September 0.407019E+10 3359.49 05-SEP-17:42 15.78 9.39 91605832.64 126.83 01-SEP-09:00 15.78 9.39
October 0.835501E+10 4692.96 18-OCT-16:43 15.28 10.42 95230031.06 126.82 02-OCT-13:00 15.28 10.42
November 0.123790E+11 6317.80 09-NOV-16:02 0.82 -3.8 94300291.49 126.82 21-NOV-10:00 12.80 12.80
December 0.148818E+11 12262.37 20-DEC-11:12 -24.3 -24.6 96701623.21 232.27 19-DEC-10:09 -24.3 -24.6
                     
Annual Sum or Average 0.126053E+12         0.115245E+10        
Minimum of Months 0.100772E+10 3161.67   -24.7 -25.0 87851462.58 126.82   -24.7 -25.0
Maximum of Months 0.198972E+11 12335.52   24.83 15.88 0.103297E+09 232.27   30.00 22.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.403631E+09 2700.74 06-JAN-12:42 -24.8 -25.1 96236506.01 167.09 05-JAN-16:40 -24.8 -25.1
February 0.397274E+10 10481.51 17-FEB-09:21 -24.8 -25.1 87467092.42 186.58 14-FEB-10:09 -24.8 -25.1
March 0.107694E+11 10822.46 12-MAR-07:01 -24.5 -24.8 0.103289E+09 126.82 21-MAR-13:09 0.00 -1.0
April 0.164323E+11 8680.33 21-APR-18:15 10.53 2.25 91605079.83 126.82 19-APR-09:09 10.53 2.25
May 0.371644E+10 3001.86 14-MAY-18:41 18.17 8.43 99233975.28 126.83 26-MAY-13:09 23.17 17.97
June 0.857783E+10 5259.91 30-JUN-23:22 16.85 13.54 98958967.92 126.83 19-JUN-13:00 16.85 13.54
July 0.140378E+11 6844.29 31-JUL-24:00 17.00 15.17 91881364.63 126.82 03-JUL-09:09 17.00 15.17
August 0.185573E+11 8501.21 02-AUG-18:40 18.53 13.51 0.103240E+09 126.83 08-AUG-13:09 29.50 22.73
September 0.308191E+10 3254.22 05-SEP-17:42 15.78 9.39 91605826.12 126.83 01-SEP-09:00 15.78 9.39
October 0.683608E+10 4514.79 18-OCT-16:43 15.28 10.42 95230031.51 126.82 02-OCT-13:00 15.28 10.42
November 0.987621E+10 5854.04 09-NOV-16:12 0.53 -4.0 94300294.36 126.82 21-NOV-10:00 12.80 12.80
December 0.124148E+11 11581.93 26-DEC-09:41 -24.6 -24.9 96700593.72 232.27 19-DEC-10:09 -24.6 -24.9
                     
Annual Sum or Average 0.108677E+12         0.114975E+10        
Minimum of Months 0.403631E+09 2700.74   -24.8 -25.1 87467092.42 126.82   -24.8 -25.1
Maximum of Months 0.185573E+11 11581.93   18.53 15.17 0.103289E+09 232.27   29.50 22.73



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.150970E+09 1607.57 25-JAN-16:25 -18.4 -19.1 92207372.89 151.03 05-JAN-16:40 -18.4 -19.1
February 0.243321E+10 10457.40 14-FEB-10:01 -24.6 -25.0 86973451.19 166.01 14-FEB-10:09 -24.6 -25.0
March 0.852789E+10 10149.40 12-MAR-07:01 -24.5 -24.8 0.103263E+09 126.82 21-MAR-13:09 0.00 -1.0
April 0.145632E+11 8622.71 21-APR-18:02 10.82 2.42 91605082.33 126.82 19-APR-09:09 10.82 2.42
May 0.286419E+10 3129.25 25-MAY-18:50 27.57 18.64 99236306.56 126.83 26-MAY-13:09 23.17 17.97
June 0.802555E+10 5174.69 30-JUN-23:02 17.35 13.59 98958972.68 126.83 19-JUN-13:00 17.35 13.59
July 0.136269E+11 6602.49 31-JUL-23:50 16.95 15.06 91881530.08 126.82 03-JUL-09:09 16.95 15.06
August 0.179893E+11 8560.75 02-AUG-18:40 18.53 13.51 0.103239E+09 126.83 31-AUG-13:00 27.20 22.12
September 0.193237E+10 3225.84 05-SEP-17:42 15.78 9.39 91606605.13 126.83 01-SEP-13:09 15.78 9.39
October 0.459824E+10 4466.10 18-OCT-16:43 15.28 10.42 95230033.11 126.82 02-OCT-13:00 15.28 10.42
November 0.746767E+10 5534.85 09-NOV-16:12 0.53 -4.0 94300298.32 126.82 21-NOV-10:00 12.80 12.80
December 0.104784E+11 11696.47 26-DEC-09:41 -24.6 -24.9 96654774.07 232.27 19-DEC-10:09 -24.6 -24.9
                     
Annual Sum or Average 0.926579E+11         0.114516E+10        
Minimum of Months 0.150970E+09 1607.57   -24.6 -25.0 86973451.19 126.82   -24.6 -25.0
Maximum of Months 0.179893E+11 11696.47   27.57 18.64 0.103263E+09 232.27   27.20 22.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.229974E+12 96350.12 12-JAN-15:01 -18.9 -19.7 0.208445E+10 2793.30 27-JAN-14:00 -14.4 -15.6
February 0.436233E+12 489288.91 01-FEB-00:12 -23.0 -23.4 0.155017E+10 2647.20 08-FEB-14:00 5.00 -0.5
March 0.721456E+12 525268.20 31-MAR-15:52 8.90 3.77 0.184759E+10 2326.28 23-MAR-13:30 8.90 3.77
April 0.946541E+12 495373.02 26-APR-11:54 0.00 -0.3 0.159487E+10 2851.55 18-APR-13:09 0.00 -0.3
May 0.240085E+12 478066.61 31-MAY-23:09 10.37 8.33 0.216235E+10 2864.06 03-MAY-13:09 10.37 8.33
June 0.474137E+12 488108.90 17-JUN-00:22 6.40 6.02 0.198986E+10 2834.45 16-JUN-13:00 6.40 6.02
July 0.735923E+12 495741.12 07-JUL-23:42 7.98 7.67 0.194071E+10 2875.05 05-JUL-10:00 7.98 7.67
August 0.983492E+12 492282.96 25-AUG-05:37 8.13 8.03 0.210757E+10 2764.39 31-AUG-13:09 25.37 21.98
September 0.236043E+12 468375.25 30-SEP-23:56 7.80 6.76 0.198939E+10 2810.55 08-SEP-13:09 7.80 6.76
October 0.491410E+12 511611.61 31-OCT-23:53 3.30 -0.4 0.174817E+10 2745.22 02-OCT-09:30 3.30 -0.4
November 0.703777E+12 517248.59 01-NOV-00:52 5.10 3.87 0.171732E+10 2744.00 02-NOV-09:00 2.80 2.54
December 0.977817E+12 488110.99 21-DEC-10:23 -24.8 -25.1 0.160988E+10 2711.27 21-DEC-10:39 -24.3 -24.7
                     
Annual Sum or Average 0.717689E+13         0.223423E+11        
Minimum of Months 0.229974E+12 96350.12   -24.8 -25.1 0.155017E+10 2326.28   -24.3 -24.7
Maximum of Months 0.983492E+12 525268.20   10.37 8.33 0.216235E+10 2875.05   25.37 21.98



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.163002E+09 95205.80 06-JAN-07:10 -35.0
February 77672184.75 2922.76 09-FEB-06:03 -3.2
March 41678466.66 2870.36 02-MAR-06:03 -8.3
April 74068220.60 3131.61 15-APR-05:12 5.60
May 56046802.08 3176.96 10-MAY-05:45 4.25
June 82379236.38 8700.55 24-JUN-16:01 28.98
July 0.102500E+09 10812.43 29-JUL-16:01 30.50
August 38752374.39 5202.14 26-AUG-16:02 26.60
September 46369269.33 3029.12 29-SEP-05:05 7.20
October 82483250.01 2649.47 14-OCT-05:03 -0.2
November 73838410.96 3046.31 13-NOV-06:11 -8.5
December 52887497.12 2883.35 08-DEC-06:04 -21.0
         
Annual Sum or Average 0.891677E+09      
Minimum of Months 38752374.39 2649.47   -35.0
Maximum of Months 0.163002E+09 95205.80   30.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 34772176.83 19864.72 02-JAN-05:01 -18.2
February 0.00 0.00 01-FEB-00:01 -23.1
March 0.00 0.00 01-MAR-00:01 -1.3
April 0.00 0.00 01-APR-00:03 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:01 11.35
July 0.00 0.00 01-JUL-00:01 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:02 19.75
October 0.00 0.00 01-OCT-00:01 7.52
November 0.00 0.00 01-NOV-00:01 3.60
December 0.00 0.00 01-DEC-00:01 -8.8
         
Annual Sum or Average 34772176.83      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 34772176.83 19864.72   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.138935E+10 68233.01 02-JAN-04:01 -18.8
February 0.326617E+09 57052.14 27-FEB-05:01 -17.4
March 85613853.90 57344.12 06-MAR-05:01 -18.4
April 0.00 0.00 01-APR-00:03 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:01 11.35
July 0.00 0.00 01-JUL-00:01 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:02 19.75
October 0.00 0.00 01-OCT-00:01 7.52
November 0.216751E+09 60389.36 27-NOV-05:01 -7.2
December 0.751870E+09 61586.26 26-DEC-05:01 -25.9
         
Annual Sum or Average 0.277020E+10      
Minimum of Months 0.00 0.00   -25.9
Maximum of Months 0.138935E+10 68233.01   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.186107E+11 140106.84 09-JAN-04:01 -32.4
February 0.107774E+11 137293.29 13-FEB-03:51 -22.8
March 0.666236E+10 134016.49 06-MAR-04:01 -17.4
April 0.207291E+10 129930.82 03-APR-03:01 -7.4
May 0.176001E+09 110654.80 01-MAY-05:01 -3.4
June 0.00 0.00 01-JUN-00:01 11.35
July 0.00 0.00 01-JUL-00:01 15.83
August 2521380.32 37820.70 19-AUG-05:01 4.60
September 17522173.99 83968.23 23-SEP-05:01 4.90
October 0.200555E+10 134897.42 30-OCT-03:11 -9.6
November 0.682918E+10 136288.02 13-NOV-04:01 -8.2
December 0.155902E+11 139589.65 25-DEC-04:41 -29.9
         
Annual Sum or Average 0.627444E+11      
Minimum of Months 0.00 0.00   -32.4
Maximum of Months 0.186107E+11 140106.84   15.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.858107E+10 24999.64 09-JAN-03:11 -32.2
February 0.392864E+10 24618.50 13-FEB-04:01 -22.9
March 0.163326E+10 23502.09 06-MAR-04:01 -17.4
April 0.105737E+09 20379.79 05-APR-04:01 -12.4
May 14946.07 199.28 01-MAY-05:01 -3.4
June 0.00 0.00 01-JUN-00:01 11.35
July 0.00 0.00 01-JUL-00:01 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:02 19.75
October 43219250.65 20887.96 30-OCT-04:01 -10.0
November 0.708081E+09 21943.48 25-NOV-05:21 -19.1
December 0.545619E+10 25491.40 24-DEC-08:11 -31.1
         
Annual Sum or Average 0.204562E+11      
Minimum of Months 0.00 0.00   -32.2
Maximum of Months 0.858107E+10 25491.40   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.517159E+10 23877.24 09-JAN-03:11 -32.2
February 0.228825E+10 23462.05 13-FEB-04:01 -22.9
March 0.106506E+10 22188.44 06-MAR-04:01 -17.4
April 90710705.25 18835.03 05-APR-04:01 -12.4
May 279612.31 3728.16 01-MAY-05:01 -3.4
June 0.00 0.00 01-JUN-00:01 11.35
July 0.00 0.00 01-JUL-00:01 15.83
August 108058.39 1620.88 19-AUG-05:03 4.60
September 532047.60 1990.19 06-SEP-05:02 1.28
October 52368532.51 19714.41 30-OCT-04:01 -10.0
November 0.582608E+09 20456.54 25-NOV-05:21 -19.1
December 0.374604E+10 24593.59 25-DEC-04:51 -29.8
         
Annual Sum or Average 0.129976E+11      
Minimum of Months 0.00 0.00   -32.2
Maximum of Months 0.517159E+10 24593.59   15.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.666056E+10 33759.69 09-JAN-03:11 -32.2
February 0.326536E+10 33749.97 13-FEB-04:01 -22.9
March 0.172848E+10 32879.49 05-MAR-06:31 -28.3
April 0.254288E+09 27488.91 05-APR-04:01 -12.4
May 7718219.53 20464.26 01-MAY-05:01 -3.4
June 0.00 0.00 01-JUN-00:01 11.35
July 0.00 0.00 01-JUL-00:01 15.83
August 177900.53 2668.51 19-AUG-05:03 4.60
September 948220.55 7052.79 13-SEP-05:01 3.98
October 0.165693E+09 28681.07 30-OCT-04:01 -10.0
November 0.103339E+10 30668.45 25-NOV-04:01 -18.0
December 0.485675E+10 34454.75 24-DEC-08:11 -31.1
         
Annual Sum or Average 0.179734E+11      
Minimum of Months 0.00 0.00   -32.2
Maximum of Months 0.666056E+10 34454.75   15.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.287407E+10 23329.37 02-JAN-04:01 -18.8
February 0.107869E+10 22765.07 13-FEB-04:01 -22.9
March 0.266539E+09 20406.50 06-MAR-05:01 -18.4
April 6563554.01 16324.70 04-APR-05:01 -9.0
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:01 11.35
July 0.00 0.00 01-JUL-00:01 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:02 19.75
October 12487598.87 18720.53 30-OCT-04:01 -10.0
November 0.118628E+09 20071.35 25-NOV-05:01 -19.0
December 0.754417E+09 22234.46 26-DEC-04:01 -25.0
         
Annual Sum or Average 0.511139E+10      
Minimum of Months 0.00 0.00   -25.0
Maximum of Months 0.287407E+10 23329.37   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.171819E+11 36344.35 04-JAN-04:11 -28.0
February 0.104920E+11 36696.74 12-FEB-23:01 -17.4
March 0.586123E+10 34862.71 06-MAR-04:11 -17.6
April 0.123837E+10 31480.37 03-APR-03:01 -7.4
May 53798185.58 25314.12 01-MAY-05:01 -3.4
June 123927.41 2065.46 10-JUN-05:03 14.60
July 0.00 0.00 01-JUL-00:01 15.83
August 404116.67 3136.16 19-AUG-05:01 4.60
September 44078755.29 18514.35 23-SEP-05:01 4.90
October 0.821766E+09 31072.39 30-OCT-03:01 -9.5
November 0.496333E+10 34018.73 25-NOV-04:11 -18.2
December 0.153639E+11 36740.57 24-DEC-09:21 -30.5
         
Annual Sum or Average 0.560209E+11      
Minimum of Months 0.00 0.00   -30.5
Maximum of Months 0.171819E+11 36740.57   15.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.983614E+10 30421.20 04-JAN-04:11 -28.0
February 0.555157E+10 30860.93 12-FEB-23:01 -17.4
March 0.296273E+10 29145.72 06-MAR-04:11 -17.6
April 0.592050E+09 25655.55 03-APR-03:01 -7.4
May 20106641.76 16015.02 01-MAY-05:01 -3.4
June 44636.46 743.94 10-JUN-05:02 14.60
July 37323.76 622.06 08-JUL-05:04 11.70
August 560138.74 4008.04 19-AUG-05:01 4.60
September 24734026.20 13505.35 23-SEP-05:01 4.90
October 0.509130E+09 25687.22 30-OCT-03:01 -9.5
November 0.298986E+10 28503.33 25-NOV-04:11 -18.2
December 0.910402E+10 30851.69 24-DEC-08:61 -31.1
         
Annual Sum or Average 0.315910E+11      
Minimum of Months 37323.76 622.06   -31.1
Maximum of Months 0.983614E+10 30860.93   14.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.111860E+11 38902.42 04-JAN-04:11 -28.0
February 0.623709E+10 39468.21 12-FEB-23:01 -17.4
March 0.359566E+10 37062.73 06-MAR-04:11 -17.6
April 0.881836E+09 32314.76 03-APR-03:01 -7.4
May 43636146.89 26081.33 01-MAY-05:01 -3.4
June 96007.06 1600.12 10-JUN-05:03 14.60
July 0.00 0.00 01-JUL-00:01 15.83
August 148047.64 1507.96 18-AUG-05:04 11.60
September 28863551.12 18966.47 20-SEP-05:01 5.60
October 0.603129E+09 33219.65 30-OCT-03:01 -9.5
November 0.351297E+10 36394.78 27-NOV-00:01 -6.7
December 0.104969E+11 39225.22 24-DEC-08:61 -31.1
         
Annual Sum or Average 0.365864E+11      
Minimum of Months 0.00 0.00   -31.1
Maximum of Months 0.111860E+11 39468.21   15.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.911194E+10 31492.00 04-JAN-04:11 -28.0
February 0.505136E+10 32157.68 12-FEB-23:01 -17.4
March 0.258814E+10 29788.90 06-MAR-04:11 -17.6
April 0.506494E+09 24112.98 04-APR-04:21 -8.1
May 20201115.87 16640.92 01-MAY-05:01 -3.4
June 97877.08 819.41 03-JUN-05:04 7.30
July 0.00 0.00 01-JUL-00:01 15.83
August 66186.51 882.49 18-AUG-05:04 11.60
September 17450383.13 13526.30 20-SEP-05:01 5.60
October 0.396106E+09 25832.07 30-OCT-03:01 -9.5
November 0.244957E+10 29160.09 23-NOV-22:01 -10.7
December 0.759817E+10 31051.94 24-DEC-08:41 -31.1
         
Annual Sum or Average 0.277396E+11      
Minimum of Months 0.00 0.00   -31.1
Maximum of Months 0.911194E+10 32157.68   15.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.259933E+11 49965.14 09-JAN-04:01 -32.4
February 0.182136E+11 50426.42 12-FEB-23:11 -17.6
March 0.122111E+11 48045.54 06-MAR-03:51 -17.2
April 0.426631E+10 42875.52 05-APR-03:11 -12.2
May 0.561562E+09 36234.59 01-MAY-05:01 -3.4
June 8190734.25 24854.05 10-JUN-05:01 14.60
July 2791794.03 12100.66 10-JUL-05:01 9.68
August 39467626.79 26022.98 19-AUG-05:01 4.60
September 0.704589E+09 29762.67 28-SEP-04:11 6.30
October 0.378055E+10 45130.84 30-OCT-03:11 -9.6
November 0.113736E+11 47107.84 23-NOV-22:01 -10.7
December 0.247485E+11 50958.33 24-DEC-08:41 -31.1
         
Annual Sum or Average 0.101904E+12      
Minimum of Months 2791794.03 12100.66   -32.4
Maximum of Months 0.259933E+11 50958.33   14.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.156043E+11 34157.20 09-JAN-04:01 -32.4
February 0.102026E+11 34411.39 13-FEB-03:51 -22.8
March 0.647874E+10 32789.34 06-MAR-03:51 -17.2
April 0.214271E+10 29301.07 05-APR-03:11 -12.2
May 0.241757E+09 24089.77 01-MAY-05:01 -3.4
June 3685133.59 16724.60 10-JUN-05:01 14.60
July 1892237.43 9293.27 10-JUL-04:11 8.33
August 19162536.54 17395.10 19-AUG-05:01 4.60
September 0.369479E+09 20141.73 28-SEP-04:11 6.30
October 0.221939E+10 30913.11 30-OCT-03:11 -9.6
November 0.687389E+10 32109.41 23-NOV-22:01 -10.7
December 0.152760E+11 34695.47 24-DEC-08:61 -31.1
         
Annual Sum or Average 0.594335E+11      
Minimum of Months 1892237.43 9293.27   -32.4
Maximum of Months 0.156043E+11 34695.47   14.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.188415E+11 50787.26 09-JAN-04:01 -32.4
February 0.123710E+11 50882.43 12-FEB-23:11 -17.6
March 0.847637E+10 48525.60 05-MAR-03:51 -28.3
April 0.333063E+10 43087.36 05-APR-03:11 -12.2
May 0.529329E+09 36466.79 01-MAY-05:01 -3.4
June 23382949.66 26197.71 03-JUN-05:01 7.30
July 6854100.60 25259.28 10-JUL-05:01 9.68
August 40638226.54 26434.37 19-AUG-05:01 4.60
September 0.526109E+09 30232.52 28-SEP-04:11 6.30
October 0.286157E+10 45910.92 30-OCT-03:11 -9.6
November 0.867919E+10 47662.87 23-NOV-22:01 -10.7
December 0.188032E+11 51286.99 24-DEC-08:61 -31.1
         
Annual Sum or Average 0.744897E+11      
Minimum of Months 6854100.60 25259.28   -32.4
Maximum of Months 0.188415E+11 51286.99   9.68



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.143324E+11 38433.74 09-JAN-04:01 -32.4
February 0.899098E+10 38565.60 13-FEB-03:51 -22.8
March 0.548884E+10 36557.73 06-MAR-03:51 -17.2
April 0.172158E+10 32360.59 05-APR-03:11 -12.2
May 0.219885E+09 25401.65 01-MAY-05:01 -3.4
June 3102268.10 14186.51 10-JUN-05:01 14.60
July 241175.45 2025.31 18-JUL-05:03 8.27
August 18296054.28 18381.45 19-AUG-05:01 4.60
September 0.265270E+09 20642.55 28-SEP-04:11 6.30
October 0.155016E+10 33991.45 30-OCT-03:11 -9.6
November 0.545180E+10 35751.84 25-NOV-01:51 -15.6
December 0.127778E+11 38427.26 24-DEC-08:41 -31.1
         
Annual Sum or Average 0.508204E+11      
Minimum of Months 241175.45 2025.31   -32.4
Maximum of Months 0.143324E+11 38565.60   14.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.267294E+10 15657.72 02-JAN-06:06 -17.8
February 0.720987E+09 16484.13 20-FEB-14:11 6.50
March 0.210557E+09 21831.22 26-MAR-15:31 10.93
April 50863038.69 20111.66 23-APR-15:11 25.97
May 60043640.44 13935.09 21-MAY-15:01 22.73
June 58209696.57 12098.07 25-JUN-11:21 27.25
July 0.104302E+09 16538.51 23-JUL-15:31 30.00
August 99302243.00 18305.71 20-AUG-14:51 25.60
September 59791826.09 16677.49 03-SEP-15:41 21.70
October 41632908.87 14497.68 22-OCT-15:11 19.23
November 53738559.74 10237.13 21-NOV-06:01 10.10
December 0.101911E+10 8515.81 26-DEC-11:52 -20.6
         
Annual Sum or Average 0.515148E+10      
Minimum of Months 41632908.87 8515.81   -20.6
Maximum of Months 0.267294E+10 21831.22   30.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.746960E+10 28073.40 02-JAN-06:12 -17.8
February 0.381378E+10 22296.49 20-FEB-15:01 8.40
March 0.184916E+10 23203.69 26-MAR-16:21 10.55
April 0.371073E+09 22414.23 23-APR-15:41 26.52
May 52912107.39 15417.50 14-MAY-15:11 20.00
June 49387965.78 14663.62 25-JUN-11:31 27.07
July 67654324.48 17294.59 23-JUL-16:11 29.43
August 62183481.01 14670.18 20-AUG-15:12 25.20
September 48509918.13 17292.90 03-SEP-15:52 21.70
October 0.107589E+09 15232.91 22-OCT-13:12 18.67
November 0.200413E+10 16713.60 27-NOV-06:05 -7.1
December 0.515430E+10 22614.13 26-DEC-06:06 -26.7
         
Annual Sum or Average 0.210503E+11      
Minimum of Months 48509918.13 14663.62   -26.7
Maximum of Months 0.746960E+10 28073.40   29.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.489648E+11 76147.20 06-JAN-05:11 -34.8
February 0.336592E+11 71407.55 13-FEB-05:16 -23.5
March 0.244630E+11 63269.74 06-MAR-05:15 -18.5
April 0.988718E+10 48996.85 03-APR-04:22 -5.0
May 0.214791E+10 30402.50 01-MAY-05:01 -3.4
June 0.442303E+09 40904.01 28-JUN-05:01 15.15
July 0.323036E+09 38615.43 01-JUL-05:01 9.78
August 0.484033E+09 30662.32 24-AUG-05:01 14.90
September 0.263289E+10 20822.37 23-SEP-05:01 4.90
October 0.100092E+11 48851.78 30-OCT-05:01 -9.9
November 0.236573E+11 54438.55 29-NOV-05:13 -19.8
December 0.459725E+11 71008.34 20-DEC-05:11 -28.8
         
Annual Sum or Average 0.202643E+12      
Minimum of Months 0.323036E+09 20822.37   -34.8
Maximum of Months 0.489648E+11 76147.20   15.15



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.737674E+09 1910.66 14-JAN-04:22 -24.7
February 0.177483E+09 1663.50 13-FEB-22:32 -25.5
March 51992957.87 1910.06 16-MAR-02:32 -25.2
April 0.00 0.00 01-APR-00:03 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:01 11.35
July 0.00 0.00 01-JUL-00:01 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:02 19.75
October 0.00 0.00 01-OCT-00:01 7.52
November 0.00 0.00 01-NOV-00:01 3.60
December 0.374277E+09 2082.82 02-DEC-01:52 -25.2
         
Annual Sum or Average 0.134143E+10      
Minimum of Months 0.00 0.00   -25.5
Maximum of Months 0.737674E+09 2082.82   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.171143E+10 1568.18 07-JAN-00:03 -24.9
February 0.171378E+09 1524.65 13-FEB-22:32 -25.5
March 50990823.30 1623.26 16-MAR-02:32 -25.2
April 0.00 0.00 01-APR-00:03 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:01 11.35
July 0.00 0.00 01-JUL-00:01 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:02 19.75
October 0.00 0.00 01-OCT-00:01 7.52
November 0.00 0.00 01-NOV-00:01 3.60
December 0.361384E+09 1793.76 21-DEC-00:02 -25.1
         
Annual Sum or Average 0.229518E+10      
Minimum of Months 0.00 0.00   -25.5
Maximum of Months 0.171143E+10 1793.76   19.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.228490E+10 1493.20 01-JAN-17:10 -19.1
February 0.563267E+09 1801.28 15-FEB-05:32 -24.6
March 53585821.34 2141.16 12-MAR-07:02 -24.5
April 1439621.47 538.40 30-APR-24:00 0.10
May 0.118121E+09 1290.89 01-MAY-04:01 -2.9
June 0.00 0.00 01-JUN-00:01 11.35
July 0.00 0.00 01-JUL-00:01 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.114768E+09 1029.71 11-SEP-04:12 12.40
October 57915607.07 1182.86 15-OCT-06:41 1.10
November 0.00 0.00 01-NOV-00:01 3.60
December 0.376947E+09 1676.78 21-DEC-00:02 -25.1
         
Annual Sum or Average 0.357095E+10      
Minimum of Months 0.00 0.00   -25.1
Maximum of Months 0.228490E+10 2141.16   17.07



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:01 -21.9
February 0.120665E+10 19358.30 20-FEB-14:11 6.50
March 0.00 0.00 01-MAR-00:01 -1.3
April 0.00 0.00 01-APR-00:03 3.52
May 202513.82 3296.84 31-MAY-23:10 10.37
June 0.271751E+09 25809.75 11-JUN-06:01 11.10
July 0.00 0.00 01-JUL-00:01 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 44564.16 742.74 30-SEP-23:54 7.80
October 0.355834E+09 26068.22 22-OCT-09:51 14.40
November 0.00 0.00 01-NOV-00:01 3.60
December 0.00 0.00 01-DEC-00:01 -8.8
         
Annual Sum or Average 0.183448E+10      
Minimum of Months 0.00 0.00   -21.9
Maximum of Months 0.120665E+10 26068.22   17.07



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.278508E+11 29144.79 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.252627E+11 29144.79 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.300191E+11 29144.79 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.268132E+11 29144.79 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.289349E+11 29144.79 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.287951E+11 29144.79 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.269531E+11 29144.79 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.300191E+11 29144.79 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.268132E+11 29144.79 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.278508E+11 29144.79 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.275243E+11 29144.79 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.269531E+11 29144.79 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.333789E+12     0.424397E+12    
Minimum of Months 0.252627E+11 29144.79   0.325565E+11 13457.54  
Maximum of Months 0.300191E+11 29144.79   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.250119E+11 26174.07 02-JAN-08:09 0.243681E+11 17206.63 02-JAN-08:09
February 0.226877E+11 26174.07 01-FEB-08:09 0.220609E+11 17206.63 01-FEB-08:09
March 0.269593E+11 26174.07 01-MAR-08:09 0.253549E+11 17206.63 01-MAR-08:09
April 0.240801E+11 26174.07 03-APR-07:10 0.235306E+11 17206.63 03-APR-07:10
May 0.259856E+11 26174.07 01-MAY-07:10 0.248615E+11 17206.63 01-MAY-07:10
June 0.258600E+11 26174.07 01-JUN-07:10 0.244160E+11 17206.63 01-JUN-07:10
July 0.242058E+11 26174.07 03-JUL-07:10 0.239708E+11 17206.63 03-JUL-07:10
August 0.269593E+11 26174.07 01-AUG-07:10 0.253549E+11 17206.63 01-AUG-07:10
September 0.240801E+11 26174.07 01-SEP-07:10 0.235199E+11 17206.63 01-SEP-07:10
October 0.250119E+11 26174.07 02-OCT-07:10 0.243735E+11 17206.63 02-OCT-07:10
November 0.247188E+11 26174.07 01-NOV-07:10 0.238373E+11 17206.63 01-NOV-07:10
December 0.242058E+11 26174.07 01-DEC-08:09 0.239654E+11 17206.63 01-DEC-08:09
             
Annual Sum or Average 0.299766E+12     0.289614E+12    
Minimum of Months 0.226877E+11 26174.07   0.220609E+11 17206.63  
Maximum of Months 0.269593E+11 26174.07   0.253549E+11 17206.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.250119E+11 26174.07 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.226877E+11 26174.07 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.269593E+11 26174.07 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.240801E+11 26174.07 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.259856E+11 26174.07 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.258600E+11 26174.07 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.242058E+11 26174.07 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.269593E+11 26174.07 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.240801E+11 26174.07 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.250119E+11 26174.07 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.247188E+11 26174.07 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.242058E+11 26174.07 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.299766E+12     0.289613E+12    
Minimum of Months 0.226877E+11 26174.07   0.220609E+11 17206.56  
Maximum of Months 0.269593E+11 26174.07   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.250119E+11 26174.07 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.226877E+11 26174.07 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.269593E+11 26174.07 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.240801E+11 26174.07 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.259856E+11 26174.07 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.258600E+11 26174.07 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.242058E+11 26174.07 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.269593E+11 26174.07 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.240801E+11 26174.07 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.250119E+11 26174.07 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.247188E+11 26174.07 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.242058E+11 26174.07 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.299766E+12     0.289613E+12    
Minimum of Months 0.226877E+11 26174.07   0.220609E+11 17206.56  
Maximum of Months 0.269593E+11 26174.07   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.314050E+10 3286.42 02-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.284867E+10 3286.42 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.338501E+10 3286.42 01-MAR-08:09 0.318369E+10 2160.55 01-MAR-08:09
April 0.302350E+10 3286.42 03-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.326275E+10 3286.42 01-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.324698E+10 3286.42 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.303928E+10 3286.42 03-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.338501E+10 3286.42 01-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.302350E+10 3286.42 01-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.314050E+10 3286.42 02-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.310369E+10 3286.42 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.303928E+10 3286.42 01-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.376387E+11     0.363654E+11    
Minimum of Months 0.284867E+10 3286.42   0.277008E+10 2160.55  
Maximum of Months 0.338501E+10 3286.42   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.202386E+10 2117.89 02-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.183579E+10 2117.89 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.218143E+10 2117.89 01-MAR-08:09 0.205169E+10 1392.34 01-MAR-08:09
April 0.194846E+10 2117.89 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.210264E+10 2117.89 01-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.209248E+10 2117.89 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.195863E+10 2117.89 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.218143E+10 2117.89 01-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.194846E+10 2117.89 01-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.202386E+10 2117.89 02-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.200014E+10 2117.89 01-NOV-07:10 0.192889E+10 1392.34 01-NOV-07:10
December 0.195863E+10 2117.89 01-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.242558E+11     0.234352E+11    
Minimum of Months 0.183579E+10 2117.89   0.178515E+10 1392.34  
Maximum of Months 0.218143E+10 2117.89   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.314057E+10 3286.49 02-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.284873E+10 3286.49 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.338508E+10 3286.49 01-MAR-08:09 0.318374E+10 2160.58 01-MAR-08:09
April 0.302357E+10 3286.49 03-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.326282E+10 3286.49 01-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.324705E+10 3286.49 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.303934E+10 3286.49 03-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.338508E+10 3286.49 01-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.302357E+10 3286.49 01-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.314057E+10 3286.49 02-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.310376E+10 3286.49 01-NOV-07:10 0.299318E+10 2160.58 01-NOV-07:10
December 0.303934E+10 3286.49 01-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.376395E+11     0.363660E+11    
Minimum of Months 0.284873E+10 3286.49   0.277013E+10 2160.58  
Maximum of Months 0.338508E+10 3286.49   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.202386E+10 2117.89 02-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.183579E+10 2117.89 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.218143E+10 2117.89 01-MAR-08:09 0.205168E+10 1392.33 01-MAR-08:09
April 0.194846E+10 2117.89 03-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.210264E+10 2117.89 01-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.209248E+10 2117.89 01-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.195863E+10 2117.89 03-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.218143E+10 2117.89 01-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.194846E+10 2117.89 01-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.202386E+10 2117.89 02-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.200014E+10 2117.89 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.195863E+10 2117.89 01-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.242558E+11     0.234351E+11    
Minimum of Months 0.183579E+10 2117.89   0.178514E+10 1392.33  
Maximum of Months 0.218143E+10 2117.89   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.314050E+10 3286.42 02-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.284867E+10 3286.42 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.338501E+10 3286.42 01-MAR-08:09 0.318369E+10 2160.55 01-MAR-08:09
April 0.302350E+10 3286.42 03-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.326275E+10 3286.42 01-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.324698E+10 3286.42 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.303928E+10 3286.42 03-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.338501E+10 3286.42 01-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.302350E+10 3286.42 01-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.314050E+10 3286.42 02-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.310369E+10 3286.42 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.303928E+10 3286.42 01-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.376387E+11     0.363654E+11    
Minimum of Months 0.284867E+10 3286.42   0.277008E+10 2160.55  
Maximum of Months 0.338501E+10 3286.42   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.202386E+10 2117.89 02-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.183579E+10 2117.89 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.218143E+10 2117.89 01-MAR-08:09 0.205169E+10 1392.34 01-MAR-08:09
April 0.194846E+10 2117.89 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.210264E+10 2117.89 01-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.209248E+10 2117.89 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.195863E+10 2117.89 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.218143E+10 2117.89 01-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.194846E+10 2117.89 01-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.202386E+10 2117.89 02-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.200014E+10 2117.89 01-NOV-07:10 0.192889E+10 1392.34 01-NOV-07:10
December 0.195863E+10 2117.89 01-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.242558E+11     0.234352E+11    
Minimum of Months 0.183579E+10 2117.89   0.178515E+10 1392.34  
Maximum of Months 0.218143E+10 2117.89   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.314057E+10 3286.49 02-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.284873E+10 3286.49 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.338508E+10 3286.49 01-MAR-08:09 0.318374E+10 2160.58 01-MAR-08:09
April 0.302357E+10 3286.49 03-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.326282E+10 3286.49 01-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.324705E+10 3286.49 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.303934E+10 3286.49 03-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.338508E+10 3286.49 01-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.302357E+10 3286.49 01-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.314057E+10 3286.49 02-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.310376E+10 3286.49 01-NOV-07:10 0.299318E+10 2160.58 01-NOV-07:10
December 0.303934E+10 3286.49 01-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.376395E+11     0.363660E+11    
Minimum of Months 0.284873E+10 3286.49   0.277013E+10 2160.58  
Maximum of Months 0.338508E+10 3286.49   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.202386E+10 2117.89 02-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.183579E+10 2117.89 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.218143E+10 2117.89 01-MAR-08:09 0.205168E+10 1392.33 01-MAR-08:09
April 0.194846E+10 2117.89 03-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.210264E+10 2117.89 01-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.209248E+10 2117.89 01-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.195863E+10 2117.89 03-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.218143E+10 2117.89 01-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.194846E+10 2117.89 01-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.202386E+10 2117.89 02-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.200014E+10 2117.89 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.195863E+10 2117.89 01-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.242558E+11     0.234351E+11    
Minimum of Months 0.183579E+10 2117.89   0.178514E+10 1392.33  
Maximum of Months 0.218143E+10 2117.89   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.314050E+10 3286.42 02-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.284867E+10 3286.42 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.338501E+10 3286.42 01-MAR-08:09 0.318369E+10 2160.55 01-MAR-08:09
April 0.302350E+10 3286.42 03-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.326275E+10 3286.42 01-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.324698E+10 3286.42 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.303928E+10 3286.42 03-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.338501E+10 3286.42 01-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.302350E+10 3286.42 01-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.314050E+10 3286.42 02-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.310369E+10 3286.42 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.303928E+10 3286.42 01-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.376387E+11     0.363654E+11    
Minimum of Months 0.284867E+10 3286.42   0.277008E+10 2160.55  
Maximum of Months 0.338501E+10 3286.42   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.202386E+10 2117.89 02-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.183579E+10 2117.89 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.218143E+10 2117.89 01-MAR-08:09 0.205169E+10 1392.34 01-MAR-08:09
April 0.194846E+10 2117.89 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.210264E+10 2117.89 01-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.209248E+10 2117.89 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.195863E+10 2117.89 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.218143E+10 2117.89 01-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.194846E+10 2117.89 01-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.202386E+10 2117.89 02-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.200014E+10 2117.89 01-NOV-07:10 0.192889E+10 1392.34 01-NOV-07:10
December 0.195863E+10 2117.89 01-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.242558E+11     0.234352E+11    
Minimum of Months 0.183579E+10 2117.89   0.178515E+10 1392.34  
Maximum of Months 0.218143E+10 2117.89   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.314057E+10 3286.49 02-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.284873E+10 3286.49 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.338508E+10 3286.49 01-MAR-08:09 0.318374E+10 2160.58 01-MAR-08:09
April 0.302357E+10 3286.49 03-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.326282E+10 3286.49 01-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.324705E+10 3286.49 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.303934E+10 3286.49 03-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.338508E+10 3286.49 01-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.302357E+10 3286.49 01-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.314057E+10 3286.49 02-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.310376E+10 3286.49 01-NOV-07:10 0.299318E+10 2160.58 01-NOV-07:10
December 0.303934E+10 3286.49 01-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.376395E+11     0.363660E+11    
Minimum of Months 0.284873E+10 3286.49   0.277013E+10 2160.58  
Maximum of Months 0.338508E+10 3286.49   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.202386E+10 2117.89 02-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.183579E+10 2117.89 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.218143E+10 2117.89 01-MAR-08:09 0.205168E+10 1392.33 01-MAR-08:09
April 0.194846E+10 2117.89 03-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.210264E+10 2117.89 01-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.209248E+10 2117.89 01-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.195863E+10 2117.89 03-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.218143E+10 2117.89 01-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.194846E+10 2117.89 01-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.202386E+10 2117.89 02-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.200014E+10 2117.89 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.195863E+10 2117.89 01-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.242558E+11     0.234351E+11    
Minimum of Months 0.183579E+10 2117.89   0.178514E+10 1392.33  
Maximum of Months 0.218143E+10 2117.89   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.696426E+09 728.78 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.631710E+09 728.78 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.750648E+09 728.78 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.670482E+09 728.78 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.723537E+09 728.78 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.720039E+09 728.78 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.673980E+09 728.78 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.750648E+09 728.78 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.670482E+09 728.78 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.696426E+09 728.78 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.688264E+09 728.78 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.673980E+09 728.78 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.834662E+10     0.153881E+12    
Minimum of Months 0.631710E+09 728.78   0.505780E+10 1948.61  
Maximum of Months 0.750648E+09 728.78   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.696426E+09 728.78 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.631710E+09 728.78 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.750648E+09 728.78 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.670482E+09 728.78 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.723537E+09 728.78 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.720039E+09 728.78 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.673980E+09 728.78 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.750648E+09 728.78 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.670482E+09 728.78 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.696426E+09 728.78 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.688264E+09 728.78 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.673980E+09 728.78 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.834662E+10     0.153881E+12    
Minimum of Months 0.631710E+09 728.78   0.505780E+10 1948.61  
Maximum of Months 0.750648E+09 728.78   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.696426E+09 728.78 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.631710E+09 728.78 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.750648E+09 728.78 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.670482E+09 728.78 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.723537E+09 728.78 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.720039E+09 728.78 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.673980E+09 728.78 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.750648E+09 728.78 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.670482E+09 728.78 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.696426E+09 728.78 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.688264E+09 728.78 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.673980E+09 728.78 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.834662E+10     0.153881E+12    
Minimum of Months 0.631710E+09 728.78   0.505780E+10 1948.61  
Maximum of Months 0.750648E+09 728.78   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.785272E+10 8217.58 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.712300E+10 8217.58 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.846411E+10 8217.58 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.756018E+10 8217.58 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.815842E+10 8217.58 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.811897E+10 8217.58 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.759962E+10 8217.58 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.846411E+10 8217.58 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.756018E+10 8217.58 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.785272E+10 8217.58 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.776069E+10 8217.58 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.759962E+10 8217.58 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.941143E+11     0.749486E+13    
Minimum of Months 0.712300E+10 8217.58   0.246344E+12 94908.13  
Maximum of Months 0.846411E+10 8217.58   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.278508E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.252627E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.300191E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.268132E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.289349E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.287951E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.269531E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.300191E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.268132E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.278508E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.275243E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.269531E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.333789E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.252627E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.300191E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.250119E+11 0.243681E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.226877E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.269593E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.240801E+11 0.235306E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.259856E+11 0.248615E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.258600E+11 0.244160E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.242058E+11 0.239708E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.269593E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.240801E+11 0.235199E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.250119E+11 0.243735E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.247188E+11 0.238373E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.242058E+11 0.239654E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.299766E+12 0.289614E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.226877E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.269593E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.250119E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.226877E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.269593E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.240801E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.259856E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.258600E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.242058E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.269593E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.240801E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.250119E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.247188E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.242058E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.299766E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.226877E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.269593E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.250119E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.226877E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.269593E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.240801E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.259856E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.258600E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.242058E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.269593E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.240801E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.250119E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.247188E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.242058E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.299766E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.226877E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.269593E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.314050E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.159582E+10
February 0.136985E+10 0.284867E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.138739E+10
March 0.163685E+10 0.338501E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.959231E+09
April 0.145243E+10 0.302350E+10 0.295462E+10 0.00 0.00 0.00 0.00 1777899.15 0.907969E+09
May 0.157338E+10 0.326275E+10 0.312174E+10 0.00 0.00 0.00 0.00 2793980.87 0.428035E+09
June 0.156900E+10 0.324698E+10 0.306580E+10 0.00 0.00 0.00 0.00 13041449.53 0.231004E+09
July 0.145680E+10 0.303928E+10 0.300989E+10 0.00 0.00 0.00 0.00 14344668.10 0.163323E+09
August 0.163685E+10 0.338501E+10 0.318369E+10 0.00 0.00 0.00 0.00 4656538.16 0.232527E+09
September 0.145243E+10 0.302350E+10 0.295328E+10 0.00 0.00 0.00 0.00 140595.19 0.405316E+09
October 0.150991E+10 0.314050E+10 0.306046E+10 0.00 0.00 0.00 0.00 0.00 0.636312E+09
November 0.149516E+10 0.310369E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.113723E+10
December 0.145680E+10 0.303928E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.171110E+10
                   
Annual Sum or Average 0.181194E+11 0.376387E+11 0.363654E+11 0.00 0.00 0.00 0.00 36755131.00 0.979525E+10
Minimum of Months 0.136985E+10 0.284867E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.163323E+09
Maximum of Months 0.163685E+10 0.338501E+10 0.318369E+10 0.00 0.00 0.00 0.00 14344668.10 0.171110E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.202386E+10 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.106022E+10
February 0.882782E+09 0.183579E+10 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.926562E+09
March 0.105485E+10 0.218143E+10 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.640913E+09
April 0.936002E+09 0.194846E+10 0.190407E+10 0.00 0.00 0.00 0.00 2175164.99 0.602461E+09
May 0.101394E+10 0.210264E+10 0.201177E+10 0.00 0.00 0.00 0.00 2076352.63 0.282210E+09
June 0.101113E+10 0.209248E+10 0.197572E+10 0.00 0.00 0.00 0.00 10183609.20 0.148808E+09
July 0.938820E+09 0.195863E+10 0.193969E+10 0.00 0.00 0.00 0.00 11247919.94 98332790.00
August 0.105485E+10 0.218143E+10 0.205169E+10 0.00 0.00 0.00 0.00 3606272.47 0.144963E+09
September 0.936002E+09 0.194846E+10 0.190321E+10 0.00 0.00 0.00 0.00 107244.17 0.263805E+09
October 0.973041E+09 0.202386E+10 0.197228E+10 0.00 0.00 0.00 0.00 0.00 0.419007E+09
November 0.963541E+09 0.200014E+10 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.750630E+09
December 0.938820E+09 0.195863E+10 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.113281E+10
                   
Annual Sum or Average 0.116768E+11 0.242558E+11 0.234352E+11 0.00 0.00 0.00 0.00 29396563.40 0.647072E+10
Minimum of Months 0.882782E+09 0.183579E+10 0.178515E+10 0.00 0.00 0.00 0.00 0.00 98332790.00
Maximum of Months 0.105485E+10 0.218143E+10 0.205169E+10 0.00 0.00 0.00 0.00 11247919.94 0.113281E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.314057E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.160059E+10
February 0.136988E+10 0.284873E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.141577E+10
March 0.163688E+10 0.338508E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.976538E+09
April 0.145246E+10 0.302357E+10 0.295467E+10 0.00 0.00 0.00 0.00 444960.72 0.911250E+09
May 0.157341E+10 0.326282E+10 0.312179E+10 0.00 0.00 0.00 0.00 2844378.41 0.420142E+09
June 0.156904E+10 0.324705E+10 0.306585E+10 0.00 0.00 0.00 0.00 13359070.76 0.218247E+09
July 0.145684E+10 0.303934E+10 0.300994E+10 0.00 0.00 0.00 0.00 14254883.09 0.154290E+09
August 0.163688E+10 0.338508E+10 0.318374E+10 0.00 0.00 0.00 0.00 4380276.10 0.230316E+09
September 0.145246E+10 0.302357E+10 0.295333E+10 0.00 0.00 0.00 0.00 140227.21 0.410494E+09
October 0.150994E+10 0.314057E+10 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.634998E+09
November 0.149520E+10 0.310376E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.112686E+10
December 0.145684E+10 0.303934E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.171465E+10
                   
Annual Sum or Average 0.181198E+11 0.376395E+11 0.363660E+11 0.00 0.00 0.00 0.00 35423796.29 0.981415E+10
Minimum of Months 0.136988E+10 0.284873E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.154290E+09
Maximum of Months 0.163688E+10 0.338508E+10 0.318374E+10 0.00 0.00 0.00 0.00 14254883.09 0.171465E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.202386E+10 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.108977E+10
February 0.882782E+09 0.183579E+10 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.965440E+09
March 0.105485E+10 0.218143E+10 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.674327E+09
April 0.936002E+09 0.194846E+10 0.190406E+10 0.00 0.00 0.00 0.00 449.47 0.658279E+09
May 0.101394E+10 0.210264E+10 0.201175E+10 0.00 0.00 0.00 0.00 1876897.88 0.304376E+09
June 0.101113E+10 0.209248E+10 0.197570E+10 0.00 0.00 0.00 0.00 9163636.36 0.165148E+09
July 0.938820E+09 0.195863E+10 0.193968E+10 0.00 0.00 0.00 0.00 9026701.96 0.125135E+09
August 0.105485E+10 0.218143E+10 0.205168E+10 0.00 0.00 0.00 0.00 2962000.04 0.179099E+09
September 0.936002E+09 0.194846E+10 0.190319E+10 0.00 0.00 0.00 0.00 97227.47 0.284165E+09
October 0.973041E+09 0.202386E+10 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.443447E+09
November 0.963541E+09 0.200014E+10 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.793282E+09
December 0.938820E+09 0.195863E+10 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.119142E+10
                   
Annual Sum or Average 0.116768E+11 0.242558E+11 0.234351E+11 0.00 0.00 0.00 0.00 23126913.17 0.687389E+10
Minimum of Months 0.882782E+09 0.183579E+10 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.125135E+09
Maximum of Months 0.105485E+10 0.218143E+10 0.205168E+10 0.00 0.00 0.00 0.00 9163636.36 0.119142E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.314050E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.364246E+10
February 0.136985E+10 0.284867E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.310511E+10
March 0.163685E+10 0.338501E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.212260E+10
April 0.145243E+10 0.302350E+10 0.295462E+10 0.00 0.00 0.00 0.00 9023737.55 0.189268E+10
May 0.157338E+10 0.326275E+10 0.312174E+10 0.00 0.00 0.00 0.00 6467303.51 0.907997E+09
June 0.156900E+10 0.324698E+10 0.306580E+10 0.00 0.00 0.00 0.00 33920248.65 0.481769E+09
July 0.145680E+10 0.303928E+10 0.300989E+10 0.00 0.00 0.00 0.00 37715604.66 0.346638E+09
August 0.163685E+10 0.338501E+10 0.318369E+10 0.00 0.00 0.00 0.00 15576219.37 0.458478E+09
September 0.145243E+10 0.302350E+10 0.295328E+10 0.00 0.00 0.00 0.00 415458.86 0.826956E+09
October 0.150991E+10 0.314050E+10 0.306046E+10 0.00 0.00 0.00 0.00 0.00 0.132111E+10
November 0.149516E+10 0.310369E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.242167E+10
December 0.145680E+10 0.303928E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.386728E+10
                   
Annual Sum or Average 0.181194E+11 0.376387E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.103119E+09 0.213948E+11
Minimum of Months 0.136985E+10 0.284867E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.346638E+09
Maximum of Months 0.163685E+10 0.338501E+10 0.318369E+10 0.00 0.00 0.00 0.00 37715604.66 0.386728E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.202386E+10 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.242129E+10
February 0.649041E+09 0.183579E+10 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.207880E+10
March 0.773965E+09 0.218143E+10 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.144043E+10
April 0.688021E+09 0.194846E+10 0.190407E+10 0.00 0.00 0.00 0.00 5954411.21 0.132043E+10
May 0.744847E+09 0.210264E+10 0.201177E+10 0.00 0.00 0.00 0.00 4474547.85 0.635763E+09
June 0.742030E+09 0.209248E+10 0.197572E+10 0.00 0.00 0.00 0.00 20349589.17 0.334738E+09
July 0.690839E+09 0.195863E+10 0.193969E+10 0.00 0.00 0.00 0.00 23313860.96 0.233117E+09
August 0.773965E+09 0.218143E+10 0.205169E+10 0.00 0.00 0.00 0.00 8033114.44 0.330909E+09
September 0.688021E+09 0.194846E+10 0.190321E+10 0.00 0.00 0.00 0.00 220929.06 0.581166E+09
October 0.715730E+09 0.202386E+10 0.197228E+10 0.00 0.00 0.00 0.00 0.00 0.904485E+09
November 0.708685E+09 0.200014E+10 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.162412E+10
December 0.690839E+09 0.195863E+10 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.257200E+10
                   
Annual Sum or Average 0.858171E+10 0.242558E+11 0.234352E+11 0.00 0.00 0.00 0.00 62346452.70 0.144772E+11
Minimum of Months 0.649041E+09 0.183579E+10 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.233117E+09
Maximum of Months 0.773965E+09 0.218143E+10 0.205169E+10 0.00 0.00 0.00 0.00 23313860.96 0.257200E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.314057E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.368346E+10
February 0.136988E+10 0.284873E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.323214E+10
March 0.163688E+10 0.338508E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.223765E+10
April 0.145246E+10 0.302357E+10 0.295467E+10 0.00 0.00 0.00 0.00 356528.41 0.204335E+10
May 0.157341E+10 0.326282E+10 0.312179E+10 0.00 0.00 0.00 0.00 6334379.38 0.956802E+09
June 0.156904E+10 0.324705E+10 0.306585E+10 0.00 0.00 0.00 0.00 28079160.79 0.488600E+09
July 0.145684E+10 0.303934E+10 0.300994E+10 0.00 0.00 0.00 0.00 31435626.76 0.359155E+09
August 0.163688E+10 0.338508E+10 0.318374E+10 0.00 0.00 0.00 0.00 9887136.51 0.518352E+09
September 0.145246E+10 0.302357E+10 0.295333E+10 0.00 0.00 0.00 0.00 298815.97 0.933617E+09
October 0.150994E+10 0.314057E+10 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.142745E+10
November 0.149520E+10 0.310376E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.250881E+10
December 0.145684E+10 0.303934E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.391634E+10
                   
Annual Sum or Average 0.181198E+11 0.376395E+11 0.363660E+11 0.00 0.00 0.00 0.00 76391647.82 0.223057E+11
Minimum of Months 0.136988E+10 0.284873E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.359155E+09
Maximum of Months 0.163688E+10 0.338508E+10 0.318374E+10 0.00 0.00 0.00 0.00 31435626.76 0.391634E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.202386E+10 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.243722E+10
February 0.882782E+09 0.183579E+10 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.210513E+10
March 0.105485E+10 0.218143E+10 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.146272E+10
April 0.936002E+09 0.194846E+10 0.190406E+10 0.00 0.00 0.00 0.00 121718.52 0.134184E+10
May 0.101394E+10 0.210264E+10 0.201175E+10 0.00 0.00 0.00 0.00 4493400.72 0.655887E+09
June 0.101113E+10 0.209248E+10 0.197570E+10 0.00 0.00 0.00 0.00 22383186.04 0.339263E+09
July 0.938820E+09 0.195863E+10 0.193968E+10 0.00 0.00 0.00 0.00 23279807.03 0.260511E+09
August 0.105485E+10 0.218143E+10 0.205168E+10 0.00 0.00 0.00 0.00 9222806.15 0.344600E+09
September 0.936002E+09 0.194846E+10 0.190319E+10 0.00 0.00 0.00 0.00 426394.22 0.589811E+09
October 0.973041E+09 0.202386E+10 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.918377E+09
November 0.963541E+09 0.200014E+10 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.163885E+10
December 0.938820E+09 0.195863E+10 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.259223E+10
                   
Annual Sum or Average 0.116768E+11 0.242558E+11 0.234351E+11 0.00 0.00 0.00 0.00 59927312.68 0.146864E+11
Minimum of Months 0.882782E+09 0.183579E+10 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.260511E+09
Maximum of Months 0.105485E+10 0.218143E+10 0.205168E+10 0.00 0.00 0.00 0.00 23279807.03 0.259223E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.314050E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.450857E+10
February 0.136985E+10 0.284867E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.382717E+10
March 0.163685E+10 0.338501E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.256465E+10
April 0.145243E+10 0.302350E+10 0.295462E+10 0.00 0.00 0.00 0.00 15760303.95 0.218381E+10
May 0.157338E+10 0.326275E+10 0.312174E+10 0.00 0.00 0.00 0.00 9503940.91 0.102067E+10
June 0.156900E+10 0.324698E+10 0.306580E+10 0.00 0.00 0.00 0.00 47140834.90 0.532644E+09
July 0.145680E+10 0.303928E+10 0.300989E+10 0.00 0.00 0.00 0.00 51828490.63 0.384695E+09
August 0.163685E+10 0.338501E+10 0.318369E+10 0.00 0.00 0.00 0.00 24681664.74 0.498246E+09
September 0.145243E+10 0.302350E+10 0.295328E+10 0.00 0.00 0.00 0.00 1992716.36 0.910392E+09
October 0.150991E+10 0.314050E+10 0.306046E+10 0.00 0.00 0.00 0.00 3779.28 0.148716E+10
November 0.149516E+10 0.310369E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.291508E+10
December 0.145680E+10 0.303928E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.477798E+10
                   
Annual Sum or Average 0.181194E+11 0.376387E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.150912E+09 0.256111E+11
Minimum of Months 0.136985E+10 0.284867E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.384695E+09
Maximum of Months 0.163685E+10 0.338501E+10 0.318369E+10 0.00 0.00 0.00 0.00 51828490.63 0.477798E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.202386E+10 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.300599E+10
February 0.882782E+09 0.183579E+10 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.255527E+10
March 0.105485E+10 0.218143E+10 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.172789E+10
April 0.936002E+09 0.194846E+10 0.190407E+10 0.00 0.00 0.00 0.00 8434458.38 0.152380E+10
May 0.101394E+10 0.210264E+10 0.201177E+10 0.00 0.00 0.00 0.00 5382548.89 0.733912E+09
June 0.101113E+10 0.209248E+10 0.197572E+10 0.00 0.00 0.00 0.00 23784206.53 0.388051E+09
July 0.938820E+09 0.195863E+10 0.193969E+10 0.00 0.00 0.00 0.00 27693586.85 0.274688E+09
August 0.105485E+10 0.218143E+10 0.205169E+10 0.00 0.00 0.00 0.00 9572829.08 0.380377E+09
September 0.936002E+09 0.194846E+10 0.190321E+10 0.00 0.00 0.00 0.00 255502.21 0.651895E+09
October 0.973041E+09 0.202386E+10 0.197228E+10 0.00 0.00 0.00 0.00 0.00 0.101473E+10
November 0.963541E+09 0.200014E+10 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.194451E+10
December 0.938820E+09 0.195863E+10 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.318566E+10
                   
Annual Sum or Average 0.116768E+11 0.242558E+11 0.234352E+11 0.00 0.00 0.00 0.00 75123131.95 0.173868E+11
Minimum of Months 0.882782E+09 0.183579E+10 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.274688E+09
Maximum of Months 0.105485E+10 0.218143E+10 0.205169E+10 0.00 0.00 0.00 0.00 27693586.85 0.318566E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.314057E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.453573E+10
February 0.136988E+10 0.284873E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.392272E+10
March 0.163688E+10 0.338508E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.267079E+10
April 0.145246E+10 0.302357E+10 0.295467E+10 0.00 0.00 0.00 0.00 1523755.38 0.235339E+10
May 0.157341E+10 0.326282E+10 0.312179E+10 0.00 0.00 0.00 0.00 7698628.29 0.108813E+10
June 0.156904E+10 0.324705E+10 0.306585E+10 0.00 0.00 0.00 0.00 37048177.48 0.551138E+09
July 0.145684E+10 0.303934E+10 0.300994E+10 0.00 0.00 0.00 0.00 40653459.97 0.407807E+09
August 0.163688E+10 0.338508E+10 0.318374E+10 0.00 0.00 0.00 0.00 12117301.65 0.579979E+09
September 0.145246E+10 0.302357E+10 0.295333E+10 0.00 0.00 0.00 0.00 339415.10 0.105260E+10
October 0.150994E+10 0.314057E+10 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.160599E+10
November 0.149520E+10 0.310376E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.296758E+10
December 0.145684E+10 0.303934E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.480719E+10
                   
Annual Sum or Average 0.181198E+11 0.376395E+11 0.363660E+11 0.00 0.00 0.00 0.00 99380737.89 0.265430E+11
Minimum of Months 0.136988E+10 0.284873E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.407807E+09
Maximum of Months 0.163688E+10 0.338508E+10 0.318374E+10 0.00 0.00 0.00 0.00 40653459.97 0.480719E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.202386E+10 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.301267E+10
February 0.882782E+09 0.183579E+10 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.257963E+10
March 0.105485E+10 0.218143E+10 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.176221E+10
April 0.936002E+09 0.194846E+10 0.190406E+10 0.00 0.00 0.00 0.00 558205.90 0.156508E+10
May 0.101394E+10 0.210264E+10 0.201175E+10 0.00 0.00 0.00 0.00 5362755.31 0.769112E+09
June 0.101113E+10 0.209248E+10 0.197570E+10 0.00 0.00 0.00 0.00 27415684.53 0.399408E+09
July 0.938820E+09 0.195863E+10 0.193968E+10 0.00 0.00 0.00 0.00 28411014.61 0.309621E+09
August 0.105485E+10 0.218143E+10 0.205168E+10 0.00 0.00 0.00 0.00 11446368.89 0.402521E+09
September 0.936002E+09 0.194846E+10 0.190319E+10 0.00 0.00 0.00 0.00 436832.65 0.682114E+09
October 0.973041E+09 0.202386E+10 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.105248E+10
November 0.963541E+09 0.200014E+10 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.196484E+10
December 0.938820E+09 0.195863E+10 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.319751E+10
                   
Annual Sum or Average 0.116768E+11 0.242558E+11 0.234351E+11 0.00 0.00 0.00 0.00 73630861.89 0.176972E+11
Minimum of Months 0.882782E+09 0.183579E+10 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.309621E+09
Maximum of Months 0.105485E+10 0.218143E+10 0.205168E+10 0.00 0.00 0.00 0.00 28411014.61 0.319751E+10



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.696426E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.631710E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.750648E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.670482E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.723537E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.720039E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.673980E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.750648E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.670482E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.696426E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.688264E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.673980E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.834662E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.631710E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.750648E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.696426E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.631710E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.750648E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.670482E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.723537E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.720039E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.673980E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.750648E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.670482E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.696426E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.688264E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.673980E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.834662E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.631710E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.750648E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.696426E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.631710E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.750648E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.670482E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.723537E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.720039E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.673980E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.750648E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.670482E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.696426E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.688264E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.673980E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.834662E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.631710E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.750648E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.785272E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.712300E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.846411E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.756018E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.815842E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.811897E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.759962E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.846411E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.756018E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.785272E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.776069E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.759962E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.941143E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.712300E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.846411E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.344094E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.306605E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.211892E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1392895.89 0.202169E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3971023.80 0.933806E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21633571.56 0.501416E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23722001.34 0.358078E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6079133.57 0.518840E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 143984.77 0.904669E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.141866E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.254095E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.374982E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 56942610.93 0.215738E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.358078E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23722001.34 0.374982E+10



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.592094E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.521863E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.365620E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4877939.58 0.345087E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7263888.47 0.162740E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40595572.32 0.862605E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 45340637.50 0.618774E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12558242.71 0.870791E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 264600.98 0.155635E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.242013E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.424961E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.638224E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.110901E+09 0.368345E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.618774E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 45340637.50 0.638224E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.634010E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.546156E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.376676E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2421258.21 0.339971E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3196752.36 0.164026E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32293237.36 0.867450E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27370023.35 0.633373E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6020337.13 0.868252E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9917.93 0.149976E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.226869E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.420778E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.672075E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 71311526.34 0.376745E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.633373E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32293237.36 0.672075E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 29144.79 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 29144.79 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 29144.79 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 29144.79 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 29144.79 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 29144.79 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 29144.79 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 29144.79 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 29144.79 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 29144.79 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 29144.79 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 29144.79 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   29144.79   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   29144.79   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 26174.07 02-JAN-08:09 17206.63 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 26174.07 01-FEB-08:09 17206.63 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 26174.07 01-MAR-08:09 17206.63 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 26174.07 03-APR-07:10 17206.63 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 26174.07 01-MAY-07:10 17206.63 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 26174.07 01-JUN-07:10 17206.63 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 26174.07 03-JUL-07:10 17206.63 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 26174.07 01-AUG-07:10 17206.63 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 26174.07 01-SEP-07:10 17206.63 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 26174.07 02-OCT-07:10 17206.63 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 26174.07 01-NOV-07:10 17206.63 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 26174.07 01-DEC-08:09 17206.63 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   26174.07   17206.63   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   26174.07   17206.63   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 26174.07 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 26174.07 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 26174.07 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 26174.07 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 26174.07 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 26174.07 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 26174.07 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 26174.07 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 26174.07 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 26174.07 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 26174.07 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 26174.07 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   26174.07   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   26174.07   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 26174.07 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 26174.07 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 26174.07 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 26174.07 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 26174.07 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 26174.07 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 26174.07 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 26174.07 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 26174.07 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 26174.07 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 26174.07 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 26174.07 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   26174.07   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   26174.07   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 3286.42 02-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 2932.15 04-JAN-05:57
February 2010.79 01-FEB-10:09 3286.42 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 3331.93 12-FEB-22:51
March 2010.79 01-MAR-10:09 3286.42 01-MAR-08:09 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 1775.50 15-MAR-04:51
April 2010.79 03-APR-09:09 3286.42 03-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 241.48 23-APR-16:00 1453.91 09-APR-12:53
May 2010.79 01-MAY-09:09 3286.42 01-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 36.46 24-MAY-15:00 728.81 08-MAY-24:00
June 2010.79 01-JUN-09:09 3286.42 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 147.67 24-JUN-17:10 507.14 20-JUN-03:51
July 2010.79 03-JUL-09:09 3286.42 03-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 250.28 23-JUL-15:00 492.21 09-JUL-10:00
August 2010.79 01-AUG-09:09 3286.42 01-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 80.02 08-AUG-16:00 659.53 27-AUG-05:53
September 2010.79 01-SEP-09:09 3286.42 01-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 12.80 01-SEP-15:00 867.17 20-SEP-01:00
October 2010.79 02-OCT-09:09 3286.42 02-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 1144.91 31-OCT-21:01
November 2010.79 01-NOV-09:09 3286.42 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 2056.00 22-NOV-01:51
December 2010.79 01-DEC-10:09 3286.42 01-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 2876.36 16-DEC-05:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   3286.42   2160.55   0.00 0.00 0.00 0.00 0.00   492.21  
Maximum of Months 2010.79   3286.42   2160.55   0.00 0.00 0.00 0.00 250.28   3331.93  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 2117.89 02-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 1954.82 04-JAN-05:59
February 1295.83 01-FEB-10:09 2117.89 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 2221.31 12-FEB-22:51
March 1295.83 01-MAR-10:09 2117.89 01-MAR-08:09 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 1183.37 15-MAR-04:51
April 1295.83 03-APR-09:09 2117.89 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 225.18 23-APR-16:00 947.53 01-APR-18:55
May 1295.83 01-MAY-09:09 2117.89 01-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 24.61 24-MAY-18:00 554.37 14-MAY-08:10
June 1295.83 01-JUN-09:09 2117.89 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 131.18 24-JUN-17:10 341.28 18-JUN-07:00
July 1295.83 03-JUL-09:09 2117.89 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 212.30 23-JUL-15:00 324.53 09-JUL-09:51
August 1295.83 01-AUG-09:09 2117.89 01-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 57.29 20-AUG-14:20 423.12 27-AUG-06:00
September 1295.83 01-SEP-09:09 2117.89 01-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 8.54 01-SEP-15:00 562.42 20-SEP-01:00
October 1295.83 02-OCT-09:09 2117.89 02-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 762.74 31-OCT-21:01
November 1295.83 01-NOV-09:09 2117.89 01-NOV-07:10 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 1338.33 22-NOV-01:51
December 1295.83 01-DEC-10:09 2117.89 01-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 1915.45 16-DEC-05:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   2117.89   1392.34   0.00 0.00 0.00 0.00 0.00   324.53  
Maximum of Months 1295.83   2117.89   1392.34   0.00 0.00 0.00 0.00 225.18   2221.31  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 3286.49 02-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 2932.13 04-JAN-05:57
February 2010.83 01-FEB-10:09 3286.49 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 3332.08 12-FEB-22:51
March 2010.83 01-MAR-10:09 3286.49 01-MAR-08:09 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 1775.17 15-MAR-04:51
April 2010.83 03-APR-09:09 3286.49 03-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 123.52 23-APR-18:00 1648.44 16-APR-12:10
May 2010.83 01-MAY-09:09 3286.49 01-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 36.46 24-MAY-15:00 725.68 29-MAY-17:55
June 2010.83 01-JUN-09:09 3286.49 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 166.33 24-JUN-17:10 485.50 20-JUN-03:51
July 2010.83 03-JUL-09:09 3286.49 03-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 235.99 23-JUL-14:57 452.22 09-JUL-10:00
August 2010.83 01-AUG-09:09 3286.49 01-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 80.02 08-AUG-16:00 643.90 27-AUG-05:53
September 2010.83 01-SEP-09:09 3286.49 01-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 12.74 01-SEP-15:00 837.12 20-SEP-01:00
October 2010.83 02-OCT-09:09 3286.49 02-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 1143.85 31-OCT-21:01
November 2010.83 01-NOV-09:09 3286.49 01-NOV-07:10 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 1963.69 22-NOV-01:51
December 2010.83 01-DEC-10:09 3286.49 01-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 2873.10 16-DEC-05:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   3286.49   2160.58   0.00 0.00 0.00 0.00 0.00   452.22  
Maximum of Months 2010.83   3286.49   2160.58   0.00 0.00 0.00 0.00 235.99   3332.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 2117.89 02-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 1954.78 04-JAN-05:57
February 1295.83 01-FEB-10:09 2117.89 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 2284.82 12-FEB-22:51
March 1295.83 01-MAR-10:09 2117.89 01-MAR-08:09 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 1186.63 15-MAR-04:51
April 1295.83 03-APR-09:09 2117.89 03-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 5.34 23-APR-15:54 1069.43 09-APR-12:53
May 1295.83 01-MAY-09:09 2117.89 01-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 24.31 24-MAY-15:00 510.18 29-MAY-17:55
June 1295.83 01-JUN-09:09 2117.89 01-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 128.11 18-JUN-12:30 367.92 20-JUN-03:51
July 1295.83 03-JUL-09:09 2117.89 03-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 158.05 15-JUL-17:30 404.39 16-JUL-16:50
August 1295.83 01-AUG-09:09 2117.89 01-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 53.35 08-AUG-16:00 520.77 27-AUG-05:53
September 1295.83 01-SEP-09:09 2117.89 01-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 8.54 01-SEP-15:00 598.70 20-SEP-01:00
October 1295.83 02-OCT-09:09 2117.89 02-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 770.84 31-OCT-21:10
November 1295.83 01-NOV-09:09 2117.89 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 1431.25 22-NOV-01:51
December 1295.83 01-DEC-10:09 2117.89 01-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 1924.06 16-DEC-05:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   2117.89   1392.33   0.00 0.00 0.00 0.00 0.00   367.92  
Maximum of Months 1295.83   2117.89   1392.33   0.00 0.00 0.00 0.00 158.05   2284.82  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 3286.42 02-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 6892.63 04-JAN-05:57
February 2010.79 01-FEB-10:09 3286.42 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 7752.37 12-FEB-22:51
March 2010.79 01-MAR-10:09 3286.42 01-MAR-08:09 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 4200.01 15-MAR-04:56
April 2010.79 03-APR-09:09 3286.42 03-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 768.06 23-APR-15:50 3018.05 01-APR-18:32
May 2010.79 01-MAY-09:09 3286.42 01-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 83.06 24-MAY-15:00 1619.40 29-MAY-17:55
June 2010.79 01-JUN-09:09 3286.42 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 423.67 18-JUN-12:50 1046.72 20-JUN-03:51
July 2010.79 03-JUL-09:09 3286.42 03-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 767.16 23-JUL-15:00 1072.74 06-JUL-21:51
August 2010.79 01-AUG-09:09 3286.42 01-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 369.14 20-AUG-14:00 1335.96 27-AUG-05:53
September 2010.79 01-SEP-09:09 3286.42 01-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 36.64 24-SEP-15:00 1778.22 20-SEP-01:00
October 2010.79 02-OCT-09:09 3286.42 02-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 2683.44 31-OCT-21:01
November 2010.79 01-NOV-09:09 3286.42 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 4193.66 21-NOV-22:01
December 2010.79 01-DEC-10:09 3286.42 01-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 6814.18 16-DEC-05:59
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   3286.42   2160.55   0.00 0.00 0.00 0.00 0.00   1046.72  
Maximum of Months 2010.79   3286.42   2160.55   0.00 0.00 0.00 0.00 768.06   7752.37  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 2117.89 02-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 4595.08 04-JAN-05:54
February 1239.33 01-FEB-08:09 2117.89 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 5167.60 12-FEB-22:51
March 1239.33 01-MAR-08:09 2117.89 01-MAR-08:09 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 2800.02 15-MAR-04:56
April 1239.33 03-APR-07:10 2117.89 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 531.58 23-APR-15:50 2320.13 16-APR-11:52
May 1239.33 01-MAY-07:10 2117.89 01-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 57.35 24-MAY-18:00 1271.42 14-MAY-08:30
June 1239.33 01-JUN-07:10 2117.89 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 310.24 24-JUN-17:10 798.64 18-JUN-08:40
July 1239.33 03-JUL-07:10 2117.89 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 453.27 23-JUL-15:00 675.78 09-JUL-09:51
August 1239.33 01-AUG-07:10 2117.89 01-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 123.05 08-AUG-16:00 904.57 27-AUG-05:53
September 1239.33 01-SEP-07:10 2117.89 01-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 18.98 01-SEP-15:00 1182.88 20-SEP-01:00
October 1239.33 02-OCT-07:10 2117.89 02-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 1789.04 31-OCT-21:01
November 1239.33 01-NOV-07:10 2117.89 01-NOV-07:10 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 2794.81 21-NOV-22:01
December 1239.33 01-DEC-08:09 2117.89 01-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 4542.84 16-DEC-05:57
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   2117.89   1392.34   0.00 0.00 0.00 0.00 0.00   675.78  
Maximum of Months 1239.33   2117.89   1392.34   0.00 0.00 0.00 0.00 531.58   5167.60  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 3286.49 02-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 6892.44 04-JAN-05:53
February 2010.83 01-FEB-10:09 3286.49 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 7760.46 12-FEB-22:51
March 2010.83 01-MAR-10:09 3286.49 01-MAR-08:09 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 4200.00 15-MAR-04:57
April 2010.83 03-APR-09:09 3286.49 03-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 156.79 23-APR-17:50 3897.03 16-APR-11:58
May 2010.83 01-MAY-09:09 3286.49 01-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 83.06 24-MAY-15:00 1666.72 29-MAY-17:55
June 2010.83 01-JUN-09:09 3286.49 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 382.72 24-JUN-17:10 1036.83 20-JUN-03:51
July 2010.83 03-JUL-09:09 3286.49 03-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 529.75 23-JUL-14:55 1055.24 06-JUL-21:51
August 2010.83 01-AUG-09:09 3286.49 01-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 184.57 08-AUG-16:00 1394.28 27-AUG-05:53
September 2010.83 01-SEP-09:09 3286.49 01-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 28.32 01-SEP-15:00 1840.96 04-SEP-12:00
October 2010.83 02-OCT-09:09 3286.49 02-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 2684.94 31-OCT-21:01
November 2010.83 01-NOV-09:09 3286.49 01-NOV-07:10 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 4192.98 21-NOV-22:01
December 2010.83 01-DEC-10:09 3286.49 01-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 6814.17 16-DEC-05:59
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   3286.49   2160.58   0.00 0.00 0.00 0.00 0.00   1036.83  
Maximum of Months 2010.83   3286.49   2160.58   0.00 0.00 0.00 0.00 529.75   7760.46  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 2117.89 02-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 4595.05 04-JAN-05:53
February 1295.83 01-FEB-10:09 2117.89 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 5172.96 12-FEB-22:51
March 1295.83 01-MAR-10:09 2117.89 01-MAR-08:09 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 2800.00 15-MAR-04:55
April 1295.83 03-APR-09:09 2117.89 03-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 97.55 23-APR-13:10 2101.16 16-APR-15:58
May 1295.83 01-MAY-09:09 2117.89 01-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 55.38 24-MAY-15:00 1130.44 29-MAY-17:55
June 1295.83 01-JUN-09:09 2117.89 01-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 358.83 18-JUN-12:10 703.22 20-JUN-03:51
July 1295.83 03-JUL-09:09 2117.89 03-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 361.02 15-JUL-17:02 943.26 16-JUL-17:10
August 1295.83 01-AUG-09:09 2117.89 01-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 240.96 20-AUG-10:42 973.86 27-AUG-05:53
September 1295.83 01-SEP-09:09 2117.89 01-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 20.74 07-SEP-12:05 1182.12 20-SEP-01:00
October 1295.83 02-OCT-09:09 2117.89 02-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 1789.51 31-OCT-21:01
November 1295.83 01-NOV-09:09 2117.89 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 2795.67 21-NOV-22:01
December 1295.83 01-DEC-10:09 2117.89 01-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 4542.67 16-DEC-05:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   2117.89   1392.33   0.00 0.00 0.00 0.00 0.00   703.22  
Maximum of Months 1295.83   2117.89   1392.33   0.00 0.00 0.00 0.00 361.02   5172.96  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 3286.42 02-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 8577.54 04-JAN-05:57
February 2010.79 01-FEB-10:09 3286.42 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 9767.66 12-FEB-22:53
March 2010.79 01-MAR-10:09 3286.42 01-MAR-08:09 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 5143.77 15-MAR-04:51
April 2010.79 03-APR-09:09 3286.42 03-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 1087.54 23-APR-15:41 3433.12 01-APR-18:12
May 2010.79 01-MAY-09:09 3286.42 01-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 146.75 21-MAY-15:20 1943.61 29-MAY-17:55
June 2010.79 01-JUN-09:09 3286.42 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 675.13 18-JUN-12:40 1162.22 20-JUN-03:51
July 2010.79 03-JUL-09:09 3286.42 03-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 1031.22 23-JUL-15:00 1232.71 06-JUL-21:51
August 2010.79 01-AUG-09:09 3286.42 01-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 604.46 20-AUG-11:10 1456.67 27-AUG-05:53
September 2010.79 01-SEP-09:09 3286.42 01-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 199.33 24-SEP-14:33 2160.58 20-SEP-04:19
October 2010.79 02-OCT-09:09 3286.42 02-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 13.15 22-OCT-14:00 3334.39 31-OCT-21:01
November 2010.79 01-NOV-09:09 3286.42 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 5210.68 21-NOV-22:01
December 2010.79 01-DEC-10:09 3286.42 01-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 8486.33 16-DEC-05:58
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   3286.42   2160.55   0.00 0.00 0.00 0.00 0.00   1162.22  
Maximum of Months 2010.79   3286.42   2160.55   0.00 0.00 0.00 0.00 1087.54   9767.66  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 2117.89 02-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 5718.36 04-JAN-05:57
February 1295.83 01-FEB-10:09 2117.89 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 6511.79 12-FEB-22:53
March 1295.83 01-MAR-10:09 2117.89 01-MAR-08:09 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 3429.88 15-MAR-04:51
April 1295.83 03-APR-09:09 2117.89 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 693.17 23-APR-15:41 2497.80 16-APR-11:52
May 1295.83 01-MAY-09:09 2117.89 01-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 66.72 24-MAY-15:00 1446.59 14-MAY-08:10
June 1295.83 01-JUN-09:09 2117.89 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 365.83 24-JUN-17:10 940.63 18-JUN-08:30
July 1295.83 03-JUL-09:09 2117.89 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 533.91 23-JUL-15:00 789.30 06-JUL-21:51
August 1295.83 01-AUG-09:09 2117.89 01-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 150.21 08-AUG-16:00 1000.97 27-AUG-05:53
September 1295.83 01-SEP-09:09 2117.89 01-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 22.28 01-SEP-15:00 1440.36 20-SEP-04:17
October 1295.83 02-OCT-09:09 2117.89 02-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 2222.70 31-OCT-21:01
November 1295.83 01-NOV-09:09 2117.89 01-NOV-07:10 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 3471.63 21-NOV-22:01
December 1295.83 01-DEC-10:09 2117.89 01-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 5657.70 16-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   2117.89   1392.34   0.00 0.00 0.00 0.00 0.00   789.30  
Maximum of Months 1295.83   2117.89   1392.34   0.00 0.00 0.00 0.00 693.17   6511.79  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 3286.49 02-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 8577.29 04-JAN-06:00
February 2010.83 01-FEB-10:09 3286.49 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 9767.57 12-FEB-22:57
March 2010.83 01-MAR-10:09 3286.49 01-MAR-08:09 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 5150.46 15-MAR-04:51
April 2010.83 03-APR-09:09 3286.49 03-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 350.80 23-APR-17:40 4275.92 16-APR-12:00
May 2010.83 01-MAY-09:09 3286.49 01-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 100.08 24-MAY-15:00 2002.35 29-MAY-17:55
June 2010.83 01-JUN-09:09 3286.49 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 494.90 24-JUN-17:10 1155.95 20-JUN-03:51
July 2010.83 03-JUL-09:09 3286.49 03-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 711.39 23-JUL-14:57 1227.40 06-JUL-21:51
August 2010.83 01-AUG-09:09 3286.49 01-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 225.31 08-AUG-16:00 1540.16 27-AUG-05:53
September 2010.83 01-SEP-09:09 3286.49 01-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 33.42 01-SEP-15:00 2198.91 04-SEP-12:00
October 2010.83 02-OCT-09:09 3286.49 02-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 3336.43 31-OCT-21:01
November 2010.83 01-NOV-09:09 3286.49 01-NOV-07:10 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 5209.09 21-NOV-22:01
December 2010.83 01-DEC-10:09 3286.49 01-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 8486.63 16-DEC-06:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   3286.49   2160.58   0.00 0.00 0.00 0.00 0.00   1155.95  
Maximum of Months 2010.83   3286.49   2160.58   0.00 0.00 0.00 0.00 711.39   9767.57  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 2117.89 02-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 5718.36 04-JAN-05:57
February 1295.83 01-FEB-10:09 2117.89 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 6511.77 12-FEB-22:54
March 1295.83 01-MAR-10:09 2117.89 01-MAR-08:09 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 3433.56 15-MAR-04:51
April 1295.83 03-APR-09:09 2117.89 03-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 205.59 23-APR-13:01 2505.82 16-APR-16:00
May 1295.83 01-MAY-09:09 2117.89 01-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 66.72 24-MAY-15:00 1366.51 29-MAY-17:55
June 1295.83 01-JUN-09:09 2117.89 01-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 449.16 18-JUN-12:00 827.94 08-JUN-23:51
July 1295.83 03-JUL-09:09 2117.89 03-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 447.21 23-JUL-14:57 1213.47 16-JUL-17:00
August 1295.83 01-AUG-09:09 2117.89 01-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 353.28 20-AUG-11:10 1096.89 27-AUG-05:53
September 1295.83 01-SEP-09:09 2117.89 01-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 23.66 07-SEP-12:05 1440.27 20-SEP-04:20
October 1295.83 02-OCT-09:09 2117.89 02-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 2224.86 31-OCT-21:01
November 1295.83 01-NOV-09:09 2117.89 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 3474.86 21-NOV-22:01
December 1295.83 01-DEC-10:09 2117.89 01-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 5657.77 16-DEC-05:56
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   2117.89   1392.33   0.00 0.00 0.00 0.00 0.00   827.94  
Maximum of Months 1295.83   2117.89   1392.33   0.00 0.00 0.00 0.00 449.16   6511.77  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 728.78 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 728.78 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 728.78 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 728.78 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 728.78 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 728.78 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 728.78 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 728.78 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 728.78 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 728.78 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 728.78 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 728.78 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   728.78   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   728.78   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 728.78 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 728.78 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 728.78 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 728.78 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 728.78 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 728.78 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 728.78 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 728.78 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 728.78 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 728.78 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 728.78 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 728.78 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   728.78   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   728.78   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 728.78 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 728.78 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 728.78 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 728.78 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 728.78 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 728.78 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 728.78 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 728.78 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 728.78 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 728.78 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 728.78 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 728.78 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   728.78   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   728.78   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 8217.58 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 8217.58 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 8217.58 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 8217.58 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 8217.58 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 8217.58 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 8217.58 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 8217.58 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 8217.58 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 8217.58 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 8217.58 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 8217.58 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   8217.58   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   8217.58   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 5817.71 04-JAN-06:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 7548.84 12-FEB-22:51
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 3709.31 15-MAR-05:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 218.64 23-APR-16:00 3279.51 01-APR-18:55
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 60.12 24-MAY-15:00 1624.85 08-MAY-24:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 288.43 24-JUN-17:01 1097.31 20-JUN-03:51
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 446.84 23-JUL-15:00 984.51 06-JUL-21:51
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 141.74 08-AUG-16:00 1467.57 27-AUG-05:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16.87 01-SEP-15:00 1938.49 20-SEP-01:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 2484.28 31-OCT-21:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 4683.53 22-NOV-01:51
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 5981.23 16-DEC-06:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   984.51  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 446.84   7548.84  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 10268.96 04-JAN-06:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 12858.42 12-FEB-23:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 6452.31 15-MAR-05:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 569.38 23-APR-16:00 5626.20 01-APR-18:55
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 108.80 24-MAY-15:00 2835.09 20-MAY-04:53
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 556.91 24-JUN-17:01 1871.12 20-JUN-03:51
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 877.31 23-JUL-15:00 1803.11 06-JUL-21:51
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 258.24 08-AUG-16:00 2506.83 27-AUG-05:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.25 01-SEP-15:00 3344.60 20-SEP-01:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 4326.22 31-OCT-21:01
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 7881.44 22-NOV-01:51
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 10333.03 16-DEC-06:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   1803.11  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 877.31   12858.42  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 11440.96 04-JAN-06:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 13014.26 12-FEB-23:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 6915.05 15-MAR-04:51
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 424.06 23-APR-16:00 5413.78 01-APR-18:12
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 65.70 24-MAY-16:00 3114.22 29-MAY-17:55
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 499.03 29-JUN-21:02 1717.85 20-JUN-03:51
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 755.91 15-JUL-17:02 1651.06 16-JUL-17:01
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 233.22 08-AUG-16:00 2296.44 27-AUG-05:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.51 01-SEP-16:00 3089.52 20-SEP-01:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 4676.64 31-OCT-21:01
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 7467.61 22-NOV-01:51
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 11067.21 16-DEC-06:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   1651.06  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 755.91   13014.26  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 127840.40 20-JAN-06:01 14361.80 25906.48 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
February 131286.20 09-FEB-06:01 17952.25 32383.10 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
March 130589.47 02-MAR-06:01 17952.25 32383.10 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
April 122318.50 24-APR-04:11 0.00 32383.10 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
May 141290.34 30-MAY-04:12 0.00 19429.86 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
June 140154.55 08-JUN-04:11 0.00 32383.10 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
July 126457.95 10-JUL-04:11 0.00 22668.17 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
August 124610.95 25-AUG-04:11 0.00 32383.10 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
September 139287.92 13-SEP-04:11 0.00 22668.17 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
October 147975.18 23-OCT-04:11 0.00 32383.10 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
November 124419.62 13-NOV-04:01 0.00 16191.55 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
December 114538.36 01-DEC-05:01 0.00 22668.17 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 114538.36   0.00 16191.55 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 147975.18   17952.25 32383.10 134575.44 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 33761.18 20-JAN-16:30 30632.53 52348.14 34413.26 0.00 0.00 0.00 0.00 0.00 0.00
February 38740.60 08-FEB-16:53 153162.65 261740.70 172066.28 0.00 0.00 0.00 0.00 0.00 0.00
March 107545.89 28-MAR-05:01 16122.38 29082.30 76473.90 0.00 0.00 0.00 0.00 0.00 0.00
April 114350.32 24-APR-04:11 0.00 29082.30 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
May 120351.10 30-MAY-04:12 0.00 17449.38 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
June 118583.07 26-JUN-04:11 0.00 29082.30 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
July 122183.51 31-JUL-04:11 0.00 29082.30 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
August 120590.04 28-AUG-04:11 0.00 20357.61 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
September 116605.74 05-SEP-04:12 0.00 17449.38 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
October 111747.50 23-OCT-04:11 0.00 29082.30 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
November 107809.90 15-NOV-06:01 16122.38 29082.30 76473.90 0.00 0.00 0.00 0.00 0.00 0.00
December 42670.36 06-DEC-06:01 14510.15 26174.07 68826.51 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 33761.18   0.00 17449.38 34413.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 122183.51   153162.65 261740.70 172066.28 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 24795.51 27-JAN-16:37 45948.79 78522.21 51619.69 0.00 0.00 0.00 0.00 0.00 0.00
February 29081.23 08-FEB-16:53 153162.65 261740.70 172065.63 0.00 0.00 0.00 0.00 0.00 0.00
March 37494.44 31-MAR-15:53 153162.65 261740.70 172065.63 0.00 0.00 0.00 0.00 0.00 0.00
April 99255.41 14-APR-05:01 12897.91 23265.84 61178.89 0.00 0.00 0.00 0.00 0.00 0.00
May 108482.17 30-MAY-04:12 0.00 17449.38 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
June 107551.91 28-JUN-04:11 0.00 29082.30 59376.23 0.00 0.00 0.00 0.00 0.00 0.00
July 107505.30 31-JUL-04:11 0.00 29082.30 59376.23 0.00 0.00 0.00 0.00 0.00 0.00
August 104865.63 25-AUG-04:11 0.00 29082.30 59376.23 0.00 0.00 0.00 0.00 0.00 0.00
September 102878.00 01-SEP-04:11 0.00 23265.84 47500.98 0.00 0.00 0.00 0.00 0.00 0.00
October 98846.18 20-OCT-05:01 16122.38 29082.30 76473.61 0.00 0.00 0.00 0.00 0.00 0.00
November 35374.40 17-NOV-16:13 153162.65 261740.70 172065.63 0.00 0.00 0.00 0.00 0.00 0.00
December 25633.80 01-DEC-17:00 15316.26 26174.07 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 24795.51   0.00 17449.38 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 108482.17   153162.65 261740.70 172065.63 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 22148.41 19-JAN-17:00 15316.26 26174.07 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
February 25266.07 08-FEB-17:00 153162.65 261740.70 172065.63 0.00 0.00 0.00 0.00 0.00 0.00
March 27423.10 31-MAR-16:00 153162.65 261740.70 172065.63 0.00 0.00 0.00 0.00 0.00 0.00
April 41960.76 13-APR-16:00 15316.26 26174.07 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
May 129203.89 26-MAY-05:02 9673.43 17449.38 45884.17 0.00 0.00 0.00 0.00 0.00 0.00
June 125473.27 28-JUN-05:01 16122.38 29082.30 76473.61 0.00 0.00 0.00 0.00 0.00 0.00
July 127457.15 13-JUL-05:01 16122.38 29082.30 76473.61 0.00 0.00 0.00 0.00 0.00 0.00
August 127150.02 10-AUG-05:01 11285.67 20357.61 53531.53 0.00 0.00 0.00 0.00 0.00 0.00
September 123799.95 01-SEP-05:02 9673.43 17449.38 45884.17 0.00 0.00 0.00 0.00 0.00 0.00
October 37090.94 20-OCT-15:53 153162.65 261740.70 172065.63 0.00 0.00 0.00 0.00 0.00 0.00
November 26047.45 01-NOV-16:00 61265.06 104696.28 68826.25 0.00 0.00 0.00 0.00 0.00 0.00
December 22426.17 28-DEC-17:00 30632.53 52348.14 34413.13 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 22148.41   9673.43 17449.38 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 129203.89   153162.65 261740.70 172065.63 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3356.58 30-JAN-06:05 1214.60 2190.94 5761.47 0.00 0.00 0.00 0.00 0.00 181.41
February 3978.68 08-FEB-14:41 20107.90 32864.16 21605.52 0.00 0.00 0.00 0.00 0.00 144.65
March 5414.67 26-MAR-16:51 1012.16 1825.79 7201.84 0.00 0.00 0.00 0.00 0.00 387.61
April 7835.41 18-APR-14:00 2010.79 3286.42 2160.55 0.00 0.00 0.00 0.00 0.00 110.13
May 11197.07 23-MAY-14:40 1923.11 3286.42 2160.55 0.00 0.00 0.00 0.00 14.86 0.00
June 15333.56 29-JUN-04:11 0.00 2921.26 5964.49 0.00 0.00 0.00 0.00 0.00 72.34
July 18245.13 03-JUL-04:11 0.00 3651.57 7455.61 0.00 0.00 0.00 0.00 0.00 97.21
August 12012.62 08-AUG-15:00 1923.11 3286.42 2160.55 0.00 0.00 0.00 0.00 74.47 0.00
September 9804.07 01-SEP-15:10 1923.11 3286.42 2160.55 0.00 0.00 0.00 0.00 12.51 0.00
October 6614.31 01-OCT-14:31 1012.16 1825.79 7201.84 0.00 0.00 0.00 0.00 0.00 210.73
November 5529.25 21-NOV-06:02 1821.89 3286.42 8642.21 0.00 0.00 0.00 0.00 0.00 88.56
December 3543.25 06-DEC-06:02 1821.89 3286.42 8642.21 0.00 0.00 0.00 0.00 0.00 149.07
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3356.58   0.00 1825.79 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18245.13   20107.90 32864.16 21605.52 0.00 0.00 0.00 0.00 74.47 387.61



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3920.79 25-JAN-10:10 2591.66 4235.78 2784.68 0.00 0.00 0.00 0.00 0.00 197.82
February 5583.43 28-FEB-09:55 12393.25 21178.91 13923.42 0.00 0.00 0.00 0.00 0.00 137.80
March 11457.46 26-MAR-10:11 652.28 1176.61 4641.14 0.00 0.00 0.00 0.00 0.00 519.19
April 32711.07 30-APR-08:51 587.05 1058.95 4177.03 0.00 0.00 0.00 0.00 0.00 246.07
May 23477.94 21-MAY-09:02 326.14 588.30 2320.57 0.00 0.00 0.00 0.00 0.00 148.35
June 38626.46 25-JUN-08:61 652.28 1176.61 4641.14 0.00 0.00 0.00 0.00 0.00 126.98
July 33477.26 23-JUL-09:31 456.59 823.62 3248.80 0.00 0.00 0.00 0.00 0.00 17.89
August 35376.94 20-AUG-10:11 521.82 941.28 3712.91 0.00 0.00 0.00 0.00 0.00 204.02
September 17545.77 24-SEP-09:32 391.37 705.96 2784.68 0.00 0.00 0.00 0.00 0.00 269.00
October 32004.90 22-OCT-09:11 652.28 1176.61 4641.14 0.00 0.00 0.00 0.00 0.00 331.35
November 5832.11 11-NOV-10:21 652.28 1176.61 4641.14 0.00 0.00 0.00 0.00 0.00 704.49
December 4098.94 28-DEC-10:00 3717.98 6353.67 4177.03 0.00 0.00 0.00 0.00 0.00 127.73
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3920.79   326.14 588.30 2320.57 0.00 0.00 0.00 0.00 0.00 17.89
Maximum of Months 38626.46   12393.25 21178.91 13923.42 0.00 0.00 0.00 0.00 0.00 704.49



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19197.27 27-JAN-13:30 1923.15 3286.49 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
February 39223.81 20-FEB-13:31 1012.19 1825.83 7201.95 0.00 0.00 0.00 0.00 0.00 1378.64
March 45028.44 26-MAR-13:31 1012.19 1825.83 7201.95 0.00 0.00 0.00 0.00 0.00 732.76
April 41049.98 23-APR-13:12 607.31 1095.50 4321.17 0.00 0.00 0.00 0.00 0.00 276.60
May 39938.88 21-MAY-13:41 708.53 1278.08 5041.36 0.00 0.00 0.00 0.00 0.00 151.85
June 42106.75 18-JUN-13:01 708.53 1278.08 5041.36 0.00 0.00 0.00 0.00 0.00 87.43
July 42999.19 16-JUL-12:51 708.53 1278.08 5041.36 0.00 0.00 0.00 0.00 0.00 171.64
August 45607.04 20-AUG-12:51 809.75 1460.66 5761.56 0.00 0.00 0.00 0.00 0.00 175.88
September 43921.08 03-SEP-14:21 809.75 1460.66 5761.56 0.00 0.00 0.00 0.00 0.00 351.98
October 49044.76 22-OCT-13:11 1012.19 1825.83 7201.95 0.00 0.00 0.00 0.00 0.00 311.23
November 22687.20 17-NOV-13:02 19231.52 32864.88 21605.85 0.00 0.00 0.00 0.00 0.00 181.62
December 15187.50 20-DEC-13:15 3846.30 6572.98 4321.17 0.00 0.00 0.00 0.00 0.00 309.48
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 15187.50   607.31 1095.50 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 49044.76   19231.52 32864.88 21605.85 0.00 0.00 0.00 0.00 0.00 1378.64



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6319.09 27-JAN-15:50 1239.33 2117.89 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
February 10727.06 28-FEB-15:32 12393.25 21178.91 13923.33 0.00 0.00 0.00 0.00 0.00 121.17
March 43017.52 26-MAR-16:51 652.28 1176.61 4641.11 0.00 0.00 0.00 0.00 0.00 402.83
April 43396.05 23-APR-16:31 521.82 941.28 3712.89 0.00 0.00 0.00 0.00 0.00 92.52
May 44043.34 21-MAY-16:21 587.05 1058.95 4177.00 0.00 0.00 0.00 0.00 0.00 125.76
June 41165.46 17-JUN-19:41 0.00 1176.61 3603.49 0.00 0.00 0.00 0.00 0.00 156.62
July 48077.44 16-JUL-16:51 652.28 1176.61 4641.11 0.00 0.00 0.00 0.00 0.00 344.35
August 40868.92 05-AUG-17:41 456.59 823.62 3248.78 0.00 0.00 0.00 0.00 0.00 79.32
September 45612.43 03-SEP-17:01 0.00 1176.61 3603.49 0.00 0.00 0.00 0.00 0.00 191.81
October 38612.41 22-OCT-15:51 652.28 1176.61 4641.11 0.00 0.00 0.00 0.00 0.00 118.08
November 8707.11 17-NOV-15:23 12393.25 21178.91 13923.33 0.00 0.00 0.00 0.00 0.00 113.58
December 5972.76 20-DEC-15:30 8675.28 14825.24 9746.33 0.00 0.00 0.00 0.00 0.00 187.81
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5972.76   0.00 823.62 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 48077.44   12393.25 21178.91 13923.33 0.00 0.00 0.00 0.00 0.00 402.83



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4347.62 19-JAN-06:04 1417.03 2556.10 6721.72 0.00 0.00 0.00 0.00 0.00 281.16
February 4455.85 22-FEB-06:04 2024.33 3651.57 9602.45 0.00 0.00 0.00 0.00 0.00 0.00
March 5562.82 31-MAR-14:02 19231.10 32864.16 21605.52 0.00 0.00 0.00 0.00 0.00 257.37
April 8813.13 23-APR-16:22 1012.16 1825.79 7201.84 0.00 0.00 0.00 0.00 424.21 0.00
May 10450.69 24-MAY-14:30 1923.11 3286.42 2160.55 0.00 0.00 0.00 0.00 71.98 0.00
June 18337.60 28-JUN-05:01 2024.33 3651.57 9602.45 0.00 0.00 0.00 0.00 0.00 0.00
July 14727.03 21-JUL-05:01 2024.33 3651.57 9602.45 0.00 0.00 0.00 0.00 0.00 40.17
August 10797.24 09-AUG-15:30 1923.11 3286.42 2160.55 0.00 0.00 0.00 0.00 38.76 0.00
September 8691.72 01-SEP-13:30 4021.58 6572.83 4321.10 0.00 0.00 0.00 0.00 19.76 0.00
October 7266.70 01-OCT-14:11 1012.16 1825.79 7201.84 0.00 0.00 0.00 0.00 0.00 306.59
November 5397.26 01-NOV-14:02 19231.10 32864.16 21605.52 0.00 0.00 0.00 0.00 0.00 93.54
December 4522.43 06-DEC-06:03 1821.89 3286.42 8642.21 0.00 0.00 0.00 0.00 0.00 352.99
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4347.62   1012.16 1825.79 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18337.60   19231.10 32864.16 21605.52 0.00 0.00 0.00 0.00 424.21 352.99



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4226.12 25-JAN-11:03 3717.98 6353.67 4177.03 0.00 0.00 0.00 0.00 0.00 236.22
February 12822.02 28-FEB-11:01 12393.25 21178.91 13923.42 0.00 0.00 0.00 0.00 0.00 244.58
March 19049.51 31-MAR-10:01 12393.25 21178.91 13923.42 0.00 0.00 0.00 0.00 0.00 396.35
April 17857.42 22-APR-10:02 1956.83 3529.82 3867.62 0.00 0.00 0.00 0.00 0.00 106.57
May 37742.55 21-MAY-08:51 521.82 941.28 3712.91 0.00 0.00 0.00 0.00 0.00 383.73
June 41588.27 25-JUN-08:11 652.28 1176.61 4641.14 0.00 0.00 0.00 0.00 0.00 296.51
July 36350.01 23-JUL-09:31 456.59 823.62 3248.80 0.00 0.00 0.00 0.00 0.00 54.82
August 34918.23 20-AUG-09:12 391.37 705.96 2784.68 0.00 0.00 0.00 0.00 0.00 474.39
September 27263.00 10-SEP-09:42 391.37 705.96 2784.68 0.00 0.00 0.00 0.00 0.00 513.52
October 16850.12 19-OCT-10:01 8675.28 14825.24 9746.39 0.00 0.00 0.00 0.00 0.00 140.81
November 11966.11 16-NOV-11:01 12393.25 21178.91 13923.42 0.00 0.00 0.00 0.00 0.00 229.88
December 4654.27 28-DEC-11:02 7435.95 12707.35 8354.05 0.00 0.00 0.00 0.00 0.00 293.58
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4226.12   391.37 705.96 2784.68 0.00 0.00 0.00 0.00 0.00 54.82
Maximum of Months 41588.27   12393.25 21178.91 13923.42 0.00 0.00 0.00 0.00 0.00 513.52



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 22180.00 27-JAN-13:40 1923.15 3286.49 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
February 39149.95 20-FEB-14:21 1012.19 1825.83 7201.95 0.00 0.00 0.00 0.00 0.00 2860.64
March 47604.79 26-MAR-14:21 1012.19 1825.83 7201.95 0.00 0.00 0.00 0.00 0.00 1502.73
April 46855.01 23-APR-13:01 809.75 1460.66 5761.56 0.00 0.00 0.00 0.00 0.00 981.52
May 41520.47 21-MAY-14:51 809.75 1460.66 5761.56 0.00 0.00 0.00 0.00 0.00 317.91
June 41925.53 25-JUN-11:31 708.53 1278.08 5041.36 0.00 0.00 0.00 0.00 0.00 44.32
July 42417.02 23-JUL-13:32 607.31 1095.50 4321.17 0.00 0.00 0.00 0.00 196.50 0.00
August 42405.75 13-AUG-13:32 607.31 1095.50 4321.17 0.00 0.00 0.00 0.00 0.00 392.21
September 48245.93 04-SEP-12:01 910.97 1643.24 6481.75 0.00 0.00 0.00 0.00 0.00 1622.94
October 52647.81 22-OCT-13:11 1012.19 1825.83 7201.95 0.00 0.00 0.00 0.00 0.00 790.65
November 24628.61 17-NOV-13:02 19231.52 32864.88 21605.85 0.00 0.00 0.00 0.00 0.00 429.29
December 15916.43 20-DEC-13:24 9615.76 16432.44 10802.92 0.00 0.00 0.00 0.00 0.00 726.99
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 15916.43   607.31 1095.50 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 52647.81   19231.52 32864.88 21605.85 0.00 0.00 0.00 0.00 196.50 2860.64



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5417.19 27-JAN-15:50 1239.33 2117.89 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
February 8143.48 08-FEB-16:23 12393.25 21178.91 13923.33 0.00 0.00 0.00 0.00 0.00 220.06
March 37181.96 26-MAR-17:01 0.00 1176.61 3603.49 0.00 0.00 0.00 0.00 0.00 908.87
April 44931.38 23-APR-17:41 0.00 1176.61 3603.49 0.00 0.00 0.00 0.00 0.00 468.35
May 44668.79 14-MAY-17:11 0.00 1176.61 3603.49 0.00 0.00 0.00 0.00 0.00 658.32
June 39865.63 17-JUN-19:41 0.00 1176.61 3603.49 0.00 0.00 0.00 0.00 0.00 379.76
July 43471.51 04-JUL-16:11 652.28 1176.61 4641.11 0.00 0.00 0.00 0.00 0.00 233.70
August 38583.77 05-AUG-17:41 456.59 823.62 3248.78 0.00 0.00 0.00 0.00 0.00 184.69
September 38259.10 03-SEP-17:11 0.00 823.62 2522.44 0.00 0.00 0.00 0.00 0.00 355.98
October 23440.36 22-OCT-15:51 652.28 1176.61 4641.11 0.00 0.00 0.00 0.00 0.00 266.44
November 6107.61 17-NOV-15:40 12393.25 21178.91 13923.33 0.00 0.00 0.00 0.00 0.00 248.81
December 4365.49 20-DEC-15:30 8675.28 14825.24 9746.33 0.00 0.00 0.00 0.00 0.00 424.06
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4365.49   0.00 823.62 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 44931.38   12393.25 21178.91 13923.33 0.00 0.00 0.00 0.00 0.00 908.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5219.38 21-JAN-17:01 809.73 1460.63 5761.47 0.00 0.00 0.00 0.00 0.00 1157.00
February 5979.91 07-FEB-06:04 2024.33 3651.57 9602.45 0.00 0.00 0.00 0.00 0.00 509.34
March 6000.96 23-MAR-05:04 2024.33 3651.57 9602.45 0.00 0.00 0.00 0.00 0.00 0.00
April 10965.48 23-APR-16:11 1012.16 1825.79 7201.84 0.00 0.00 0.00 0.00 612.64 0.00
May 11462.68 18-MAY-15:00 1923.11 3286.42 2160.55 0.00 0.00 0.00 0.00 71.29 0.00
June 17679.81 28-JUN-05:01 2024.33 3651.57 9602.45 0.00 0.00 0.00 0.00 0.00 0.00
July 13587.73 23-JUL-16:11 809.73 1460.63 5761.47 0.00 0.00 0.00 0.00 360.63 0.00
August 11907.57 08-AUG-15:50 1923.11 3286.42 2160.55 0.00 0.00 0.00 0.00 222.71 0.00
September 10973.44 03-SEP-14:21 809.73 1460.63 5761.47 0.00 0.00 0.00 0.00 0.00 274.49
October 8043.88 22-OCT-14:31 1012.16 1825.79 7201.84 0.00 0.00 0.00 0.00 0.00 120.99
November 6021.39 01-NOV-15:00 5769.33 9859.25 6481.66 0.00 0.00 0.00 0.00 0.00 47.79
December 6148.57 06-DEC-06:03 1821.89 3286.42 8642.21 0.00 0.00 0.00 0.00 0.00 441.95
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5219.38   809.73 1460.63 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17679.81   5769.33 9859.25 9602.45 0.00 0.00 0.00 0.00 612.64 1157.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4081.92 17-JAN-06:04 1304.55 2353.21 6188.19 0.00 0.00 0.00 0.00 0.00 257.70
February 4713.29 28-FEB-10:30 12958.30 21178.91 13923.42 0.00 0.00 0.00 0.00 0.00 332.17
March 6670.72 31-MAR-09:51 12958.30 21178.91 13923.42 0.00 0.00 0.00 0.00 0.00 502.27
April 14767.91 18-APR-09:25 2591.66 4235.78 2784.68 0.00 0.00 0.00 0.00 0.00 174.56
May 18002.41 18-MAY-09:30 1295.83 2117.89 1392.34 0.00 0.00 0.00 0.00 2.71 0.00
June 39501.05 18-JUN-09:51 587.05 1058.95 4177.03 0.00 0.00 0.00 0.00 0.00 475.95
July 36347.53 23-JUL-09:31 456.59 823.62 3248.80 0.00 0.00 0.00 0.00 0.00 69.35
August 37552.50 20-AUG-10:21 521.82 941.28 3712.91 0.00 0.00 0.00 0.00 0.00 596.02
September 16921.04 01-SEP-09:30 1295.83 2117.89 1392.34 0.00 0.00 0.00 0.00 0.00 52.39
October 8720.34 19-OCT-09:33 9070.81 14825.24 9746.39 0.00 0.00 0.00 0.00 0.00 189.11
November 4370.60 16-NOV-10:01 12958.30 21178.91 13923.42 0.00 0.00 0.00 0.00 0.00 260.70
December 4187.09 06-DEC-06:03 1174.10 2117.89 5569.37 0.00 0.00 0.00 0.00 0.00 294.21
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4081.92   456.59 823.62 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 39501.05   12958.30 21178.91 13923.42 0.00 0.00 0.00 0.00 2.71 596.02



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19186.38 27-JAN-13:50 1923.15 3286.49 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
February 27422.00 28-FEB-13:31 19231.52 32864.88 21605.85 0.00 0.00 0.00 0.00 0.00 601.97
March 54300.19 26-MAR-14:31 1012.19 1825.83 7201.95 0.00 0.00 0.00 0.00 0.00 1710.03
April 56176.46 23-APR-14:51 910.97 1643.24 6481.75 0.00 0.00 0.00 0.00 0.00 601.16
May 31380.53 14-MAY-14:41 809.75 1460.66 5761.56 0.00 0.00 0.00 0.00 0.00 540.35
June 31374.36 18-JUN-14:32 607.31 1095.50 4321.17 0.00 0.00 0.00 0.00 0.00 101.83
July 53644.41 16-JUL-14:21 809.75 1460.66 5761.56 0.00 0.00 0.00 0.00 0.00 475.24
August 57078.13 20-AUG-13:41 809.75 1460.66 5761.56 0.00 0.00 0.00 0.00 0.00 584.89
September 56756.93 04-SEP-12:01 910.97 1643.24 6481.75 0.00 0.00 0.00 0.00 0.00 1885.32
October 62316.52 22-OCT-13:11 1012.19 1825.83 7201.95 0.00 0.00 0.00 0.00 0.00 912.83
November 21889.39 17-NOV-13:12 19231.52 32864.88 21605.85 0.00 0.00 0.00 0.00 0.00 539.17
December 13339.31 26-DEC-13:23 5769.46 9859.46 6481.75 0.00 0.00 0.00 0.00 0.00 194.11
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 13339.31   607.31 1095.50 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 62316.52   19231.52 32864.88 21605.85 0.00 0.00 0.00 0.00 0.00 1885.32



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5280.78 27-JAN-15:50 1239.33 2117.89 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
February 7970.31 28-FEB-15:51 12393.25 21178.91 13923.33 0.00 0.00 0.00 0.00 0.00 335.63
March 23680.14 26-MAR-17:11 0.00 1176.61 3603.49 0.00 0.00 0.00 0.00 0.00 1140.30
April 48298.82 23-APR-16:51 652.28 1176.61 4641.11 0.00 0.00 0.00 0.00 0.00 436.54
May 47174.20 14-MAY-17:21 0.00 1176.61 3603.49 0.00 0.00 0.00 0.00 0.00 826.24
June 42396.48 17-JUN-19:41 0.00 1176.61 3603.49 0.00 0.00 0.00 0.00 0.00 468.62
July 48165.04 16-JUL-16:21 652.28 1176.61 4641.11 0.00 0.00 0.00 0.00 0.00 842.14
August 41100.15 05-AUG-17:41 456.59 823.62 3248.78 0.00 0.00 0.00 0.00 0.00 228.78
September 46040.32 03-SEP-17:01 0.00 1176.61 3603.49 0.00 0.00 0.00 0.00 0.00 553.95
October 13321.75 19-OCT-16:00 1239.33 2117.89 1392.33 0.00 0.00 0.00 0.00 0.00 44.02
November 6040.97 17-NOV-15:40 12393.25 21178.91 13923.33 0.00 0.00 0.00 0.00 0.00 297.59
December 4669.35 06-DEC-06:03 1174.10 2117.89 5569.33 0.00 0.00 0.00 0.00 0.00 291.88
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4669.35   0.00 823.62 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 48298.82   12393.25 21178.91 13923.33 0.00 0.00 0.00 0.00 0.00 1140.30



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 20582.03 28-JAN-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2086.39
February 21405.67 25-FEB-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 18045.35 16-MAR-03:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 277.98
April 10685.43 05-APR-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1200.91
May 12490.47 30-MAY-04:18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1033.17
June 10456.81 17-JUN-04:18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 11549.53 21-JUL-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 39.65
August 11527.12 28-AUG-05:12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 113.13
September 11455.01 05-SEP-04:18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 749.09
October 13716.85 30-OCT-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 757.05
November 14671.40 24-NOV-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1108.42
December 20186.10 02-DEC-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2232.48
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 10456.81   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21405.67   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2232.48



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 24436.17 28-JAN-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3648.49
February 25684.29 11-FEB-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 385.11
March 25859.63 05-MAR-01:51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3397.08
April 19404.89 03-APR-03:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2133.61
May 12345.90 30-MAY-05:06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 398.67
June 11351.84 17-JUN-04:18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 11372.41 08-JUL-05:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 151.03
August 10702.46 25-AUG-05:06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 10982.66 02-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 165.33
October 24636.66 30-OCT-03:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 216.46
November 22171.43 23-NOV-18:41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5219.71
December 25928.33 02-DEC-02:61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4242.11
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 10702.46   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25928.33   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5219.71



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3771.16
February 3357.79 08-FEB-14:21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 525.79
March 9664.56 26-MAR-13:14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2234.14
April 19424.81 13-APR-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 221.95
May 32990.60 18-MAY-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 47.81 0.00
June 37249.27 30-JUN-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 216.41 0.00
July 33978.59 24-JUL-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 84.49 0.00
August 31787.91 08-AUG-14:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 179.60 0.00
September 27153.83 01-SEP-14:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.87
October 14651.49 22-OCT-13:14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 653.91
November 6021.82 01-NOV-16:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 101.28
December 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3800.87
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 37249.27   0.00 0.00 0.00 0.00 0.00 0.00 0.00 216.41 3800.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5507.27 14-JAN-04:21 0.00 323.90 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
February 10916.86 14-FEB-10:01 2322.69 7287.84 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
March 12335.52 12-MAR-07:01 116.92 404.88 58458.17 0.00 0.00 0.00 0.00 0.00 0.00
April 9045.14 23-APR-18:12 0.00 404.88 77944.22 0.00 0.00 0.00 0.00 0.00 0.00
May 3161.67 31-MAY-23:51 0.00 404.88 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
June 5370.32 30-JUN-23:02 0.00 404.88 58458.17 0.00 0.00 0.00 0.00 0.00 0.00
July 7253.20 31-JUL-24:00 0.00 40.49 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
August 8786.90 02-AUG-18:40 23.38 242.93 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3359.49 05-SEP-17:42 93.53 971.71 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
October 4692.96 18-OCT-16:43 420.90 2429.28 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
November 6317.80 09-NOV-16:02 2221.41 7287.84 58458.17 0.00 0.00 0.00 0.00 0.00 0.00
December 12262.37 20-DEC-11:12 2221.41 7287.84 77944.22 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 3161.67   0.00 40.49 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12335.52   2322.69 7287.84 77944.22 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2700.74 06-JAN-12:42 611.23 3643.92 9743.03 0.00 0.00 0.00 0.00 0.00 0.00
February 10481.51 17-FEB-09:21 2221.41 7287.84 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
March 10822.46 12-MAR-07:01 116.92 404.88 58458.17 0.00 0.00 0.00 0.00 0.00 0.00
April 8680.33 21-APR-18:15 46.77 485.86 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
May 3001.86 14-MAY-18:41 0.00 323.90 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
June 5259.91 30-JUN-23:22 0.00 242.93 35074.90 0.00 0.00 0.00 0.00 0.00 0.00
July 6844.29 31-JUL-24:00 0.00 40.49 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
August 8501.21 02-AUG-18:40 23.38 242.93 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3254.22 05-SEP-17:42 93.53 971.71 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
October 4514.79 18-OCT-16:43 420.90 2429.28 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
November 5854.04 09-NOV-16:12 2221.41 7287.84 58458.17 0.00 0.00 0.00 0.00 0.00 0.00
December 11581.93 26-DEC-09:41 1999.27 6559.06 70149.80 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2700.74   0.00 40.49 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11581.93   2221.41 7287.84 70149.80 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1607.57 25-JAN-16:25 444.28 1457.57 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
February 10457.40 14-FEB-10:01 2322.69 7287.84 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
March 10149.40 12-MAR-07:01 116.92 404.88 58458.17 0.00 0.00 0.00 0.00 0.00 0.00
April 8622.71 21-APR-18:02 116.92 1214.64 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
May 3129.25 25-MAY-18:50 23.38 242.93 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
June 5174.69 30-JUN-23:02 0.00 404.88 58458.17 0.00 0.00 0.00 0.00 0.00 0.00
July 6602.49 31-JUL-23:50 0.00 40.49 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
August 8560.75 02-AUG-18:40 23.38 242.93 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3225.84 05-SEP-17:42 93.53 971.71 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
October 4466.10 18-OCT-16:43 420.90 2429.28 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
November 5534.85 09-NOV-16:12 2221.41 7287.84 58458.17 0.00 0.00 0.00 0.00 0.00 0.00
December 11696.47 26-DEC-09:41 1999.27 6559.06 70149.80 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1607.57   0.00 40.49 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11696.47   2322.69 7287.84 70149.80 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 96350.12 12-JAN-15:01 48086.79 82175.84 949081.30 0.00 0.00 0.00 0.00 0.00 0.00
February 489288.91 01-FEB-00:12 0.00 4565.32 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00
March 525268.20 31-MAR-15:52 48086.79 82175.84 2847243.91 0.00 0.00 0.00 0.00 0.00 0.00
April 495373.02 26-APR-11:54 23816.47 73958.25 3416692.70 0.00 0.00 0.00 0.00 0.00 0.00
May 478066.61 31-MAY-23:09 0.00 4565.32 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00
June 488108.90 17-JUN-00:22 0.00 4565.32 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00
July 495741.12 07-JUL-23:42 0.00 4565.32 2847243.91 0.00 0.00 0.00 0.00 0.00 0.00
August 492282.96 25-AUG-05:37 5061.77 9130.65 3796325.22 0.00 0.00 0.00 0.00 0.00 0.00
September 468375.25 30-SEP-23:56 0.00 4565.32 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00
October 511611.61 31-OCT-23:53 0.00 4565.32 2847243.91 0.00 0.00 0.00 0.00 0.00 0.00
November 517248.59 01-NOV-00:52 0.00 4565.32 2847243.91 0.00 0.00 0.00 0.00 0.00 0.00
December 488110.99 21-DEC-10:23 50279.21 82175.84 3796325.22 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 96350.12   0.00 4565.32 949081.30 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 525268.20   50279.21 82175.84 3796325.22 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.195010E+13 1411037.64 20-JAN-16:49 0.227280E+13 3228629.56 09-JAN-07:30
February 0.215148E+13 1613703.27 22-FEB-16:10 0.143653E+13 2541652.64 14-FEB-07:19
March 0.291237E+13 1881391.90 31-MAR-14:09 0.981184E+12 2068651.25 06-MAR-07:19
April 0.316097E+13 2109627.04 13-APR-15:20 0.291123E+12 1154886.55 05-APR-06:10
May 0.210178E+13 1935541.39 25-MAY-15:20 0.477369E+11 896432.45 01-MAY-04:10
June 0.257228E+13 2219626.51 30-JUN-15:09 0.980893E+10 287627.87 10-JUN-05:10
July 0.301800E+13 2430776.02 05-JUL-10:39 0.367347E+10 112929.16 08-JUL-06:10
August 0.339611E+13 2455455.28 08-AUG-15:20 0.137261E+11 449777.55 19-AUG-05:10
September 0.189770E+13 1934622.79 01-SEP-10:00 0.820879E+11 744917.13 23-SEP-05:10
October 0.233376E+13 1778982.47 19-OCT-15:09 0.293954E+12 1290716.56 30-OCT-06:49
November 0.277412E+13 1829678.30 17-NOV-11:09 0.785211E+12 2027579.43 27-NOV-05:10
December 0.326087E+13 1933435.77 29-DEC-16:40 0.193265E+13 2877322.87 26-DEC-07:19
             
Annual Sum or Average 0.315295E+14     0.815049E+13    
Minimum of Months 0.189770E+13 1411037.64   0.367347E+10 112929.16  
Maximum of Months 0.339611E+13 2455455.28   0.227280E+13 3228629.56  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.468149E+12 0.110235E+12 0.766053E+12 0.218140E+12 0.220223E+12 0.205284E+11 0.00 0.568356E+10 0.00 0.943659E+11 0.00 0.467233E+11 0.00
February 0.424646E+12 0.905490E+11 0.978954E+12 0.199667E+12 0.211671E+12 0.338880E+11 0.00 0.568413E+11 781527.11 0.111872E+12 0.00 0.433902E+11 0.00
March 0.504598E+12 0.880113E+11 0.141687E+13 0.230864E+12 0.239964E+12 0.993857E+11 0.00 0.926424E+11 814328.51 0.189219E+12 0.00 0.508127E+11 0.00
April 0.450709E+12 0.728621E+11 0.165903E+13 0.216144E+12 0.266726E+12 0.944699E+11 0.00 0.118109E+12 0.467794E+09 0.237716E+12 0.00 0.447369E+11 0.00
May 0.486374E+12 0.642110E+11 0.774844E+12 0.224502E+12 0.239435E+12 0.500166E+11 0.00 0.125839E+12 0.819991E+10 0.829277E+11 0.00 0.454307E+11 0.00
June 0.484022E+12 0.561365E+11 0.106252E+13 0.222585E+12 0.272940E+12 0.900481E+11 0.00 0.287492E+12 0.298884E+11 0.242339E+11 0.00 0.424111E+11 0.00
July 0.453060E+12 0.608274E+11 0.139340E+13 0.218061E+12 0.311051E+12 0.130016E+12 0.00 0.366206E+12 0.460621E+11 0.101895E+10 0.00 0.382940E+11 0.00
August 0.504598E+12 0.703245E+11 0.173200E+13 0.230864E+12 0.326550E+12 0.124255E+12 0.00 0.332478E+12 0.333739E+11 0.945052E+09 0.00 0.407235E+11 0.00
September 0.450709E+12 0.797831E+11 0.740713E+12 0.216143E+12 0.216615E+12 0.401540E+11 0.00 0.804860E+11 0.345950E+10 0.324847E+11 0.00 0.371526E+11 0.00
October 0.468149E+12 0.952014E+11 0.108340E+13 0.218140E+12 0.216749E+12 0.417050E+11 0.00 0.820856E+11 0.308089E+09 0.882482E+11 0.00 0.397770E+11 0.00
November 0.462662E+12 0.103314E+12 0.135889E+13 0.209941E+12 0.225381E+12 0.107729E+12 0.00 0.873678E+11 61828819.44 0.177513E+12 0.00 0.412547E+11 0.00
December 0.453060E+12 0.113196E+12 0.170972E+13 0.218060E+12 0.275583E+12 0.107241E+12 0.00 0.100716E+12 7175.43 0.239762E+12 0.00 0.435331E+11 0.00
                           
Annual Sum or Average 0.561074E+13 0.100465E+13 0.146764E+14 0.262311E+13 0.302289E+13 0.939436E+12 0.00 0.173595E+13 0.121823E+12 0.128030E+13 0.00 0.514240E+12 0.00
Minimum of Months 0.424646E+12 0.561365E+11 0.740713E+12 0.199667E+12 0.211671E+12 0.205284E+11 0.00 0.568356E+10 0.00 0.945052E+09 0.00 0.371526E+11 0.00
Maximum of Months 0.504598E+12 0.113196E+12 0.173200E+13 0.230864E+12 0.326550E+12 0.130016E+12 0.00 0.366206E+12 0.460621E+11 0.239762E+12 0.00 0.508127E+11 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.227280E+13 0.00 0.00 0.00 0.00
February 0.00 0.00 0.143653E+13 0.00 0.00 0.00 0.00
March 0.00 0.00 0.981184E+12 0.00 0.00 0.00 0.00
April 0.00 0.00 0.291123E+12 0.00 0.00 0.00 0.00
May 0.00 0.00 0.477369E+11 0.00 0.00 0.00 0.00
June 0.00 0.00 0.980893E+10 0.00 0.00 0.00 0.00
July 0.00 0.00 0.367347E+10 0.00 0.00 0.00 0.00
August 0.00 0.00 0.137261E+11 0.00 0.00 0.00 0.00
September 0.00 0.00 0.820879E+11 0.00 0.00 0.00 0.00
October 0.00 0.00 0.293954E+12 0.00 0.00 0.00 0.00
November 0.00 0.00 0.785211E+12 0.00 0.00 0.00 0.00
December 0.00 0.00 0.193265E+13 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.815049E+13 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.367347E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.227280E+13 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 489900.85 02-JAN-08:09 64082.80 01-JAN-00:10 423497.50 02-JAN-08:09 235096.12 02-JAN-08:20 157466.77 02-JAN-06:19 44840.22 31-JAN-06:30 0.00 01-JAN-00:10
February 489900.85 01-FEB-08:09 64082.80 01-FEB-00:10 541788.89 01-FEB-08:09 235096.12 01-FEB-08:20 157362.17 08-FEB-13:00 44566.28 22-FEB-14:39 0.00 01-FEB-00:10
March 489900.85 01-MAR-08:09 64082.80 01-MAR-00:10 660080.29 01-MAR-08:09 235096.12 01-MAR-08:20 209906.51 31-MAR-14:00 46683.63 31-MAR-13:20 0.00 01-MAR-00:10
April 489900.85 03-APR-07:10 64082.80 01-APR-00:10 778371.69 03-APR-07:10 235096.12 03-APR-07:19 247552.58 21-APR-15:39 51132.61 23-APR-15:50 0.00 01-APR-00:10
May 489900.85 01-MAY-07:10 64082.80 01-MAY-00:10 423497.50 01-MAY-07:10 235096.12 01-MAY-07:19 274796.82 18-MAY-14:00 95357.45 16-MAY-15:20 0.00 01-MAY-00:10
June 489900.85 01-JUN-07:10 64082.80 01-JUN-00:10 541788.89 01-JUN-07:10 235096.12 01-JUN-07:19 303816.83 30-JUN-14:00 98854.08 08-JUN-14:00 0.00 01-JUN-00:10
July 489900.85 03-JUL-07:10 64082.80 01-JUL-00:10 660080.29 03-JUL-07:10 235096.12 03-JUL-07:19 295966.20 21-JUL-15:20 111901.83 05-JUL-10:39 0.00 01-JUL-00:10
August 489900.85 01-AUG-07:10 64082.80 01-AUG-00:10 778371.69 01-AUG-07:10 235096.12 01-AUG-07:19 303257.48 08-AUG-15:20 97182.87 31-AUG-12:39 0.00 01-AUG-00:10
September 489900.85 01-SEP-07:10 64082.80 01-SEP-00:10 423497.50 01-SEP-07:10 235096.12 01-SEP-07:19 287714.19 01-SEP-15:39 95525.22 01-SEP-10:50 0.00 01-SEP-00:10
October 489900.85 02-OCT-07:10 64082.80 01-OCT-00:10 541788.89 02-OCT-07:10 235096.12 02-OCT-07:19 225769.13 18-OCT-15:20 49740.24 19-OCT-12:20 0.00 01-OCT-00:10
November 489900.85 01-NOV-07:10 64082.80 01-NOV-00:10 660080.29 01-NOV-07:10 235096.12 01-NOV-07:19 189490.07 17-NOV-13:30 46881.47 01-NOV-15:30 0.00 01-NOV-00:10
December 489900.85 01-DEC-08:09 64082.80 01-DEC-00:10 778371.69 01-DEC-08:09 235096.12 01-DEC-08:20 165761.35 26-DEC-06:10 48376.69 26-DEC-06:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 489900.85   64082.80   423497.50   235096.12   157362.17   44566.28   0.00  
Maximum of Months 489900.85   64082.80   778371.69   235096.12   303816.83   111901.83   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 8414.85 20-JAN-16:30 0.00 01-JAN-00:10 46307.27 21-JAN-15:00 0.00 62564.32 31-JAN-12:00 0.00
February 77523.42 06-FEB-06:00 18.61 21-FEB-14:09 78541.97 08-FEB-15:50 0.00 62804.56 24-FEB-12:39 0.00
March 144623.79 31-MAR-13:20 82.10 31-MAR-14:09 100000.00 31-MAR-23:49 0.00 62796.63 01-MAR-12:00 0.00
April 229972.72 23-APR-16:30 27892.31 23-APR-15:00 100000.00 01-APR-00:10 0.00 61856.52 04-APR-11:50 0.00
May 342573.39 25-MAY-12:09 55784.63 17-MAY-13:30 100000.00 02-MAY-11:00 0.00 59258.61 01-MAY-11:20 0.00
June 458631.14 29-JUN-15:00 55784.63 19-JUN-13:09 100000.00 01-JUN-16:30 0.00 55934.55 01-JUN-11:30 0.00
July 590463.98 05-JUL-10:20 55784.63 03-JUL-13:09 68459.63 07-JUL-17:00 0.00 52595.67 03-JUL-11:00 0.00
August 488761.13 31-AUG-12:39 55784.63 31-AUG-12:20 75856.83 31-AUG-12:50 0.00 50875.51 02-AUG-11:50 0.00
September 367217.61 01-SEP-10:00 55784.63 01-SEP-10:30 99705.13 08-SEP-15:00 0.00 51317.80 29-SEP-11:20 0.00
October 187429.93 19-OCT-14:00 9477.56 19-OCT-14:00 92214.84 21-OCT-15:00 0.00 53280.87 31-OCT-11:30 0.00
November 141633.25 01-NOV-14:09 4651.88 01-NOV-14:09 98854.58 21-NOV-17:30 0.00 56905.21 30-NOV-12:39 0.00
December 84438.69 05-DEC-16:30 4.91 26-DEC-06:40 100000.00 01-DEC-02:00 0.00 60393.88 29-DEC-12:20 0.00
                     
Annual Sum or Average             0.00     0.00
Minimum of Months 8414.85   0.00   46307.27   0.00 50875.51   0.00
Maximum of Months 590463.98   55784.63   100000.00   0.00 62804.56   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1411037.64 20-JAN-16:49 489900.85 423497.50 64082.80 235096.12 101499.55 284.91 0.00 8084.50 0.00
February 1613703.27 22-FEB-16:10 489900.85 541788.89 0.00 235096.12 127080.52 31296.93 0.00 74623.35 9.65
March 1881391.90 31-MAR-14:09 489900.85 660080.29 0.00 235096.12 188469.49 46552.12 0.00 143216.44 82.10
April 2109627.04 13-APR-15:20 489900.85 778371.69 0.00 235096.12 244136.00 46076.50 0.00 167228.78 2107.99
May 1935541.39 25-MAY-15:20 489900.85 423497.50 0.00 235096.12 265145.19 93338.07 0.00 328826.89 55784.63
June 2219626.51 30-JUN-15:09 489900.85 541788.89 0.00 235096.12 302866.88 96396.49 0.00 458242.84 55784.63
July 2430776.02 05-JUL-10:39 489900.85 660080.29 0.00 235096.12 272737.06 111901.83 0.00 561907.26 55784.63
August 2455455.28 08-AUG-15:20 489900.85 778371.69 0.00 235096.12 303257.48 96563.23 0.00 457589.48 55784.63
September 1934622.79 01-SEP-10:00 489900.85 423497.50 0.00 235096.12 228091.54 93876.93 0.00 367217.61 55784.63
October 1778982.47 19-OCT-15:09 489900.85 541788.89 0.00 235096.12 214485.94 49434.61 0.00 185506.79 9327.26
November 1829678.30 17-NOV-11:09 489900.85 660080.29 0.00 235096.12 162944.38 45923.83 0.00 103923.10 31.75
December 1933435.77 29-DEC-16:40 489900.85 778371.69 64082.80 235096.12 121552.18 45664.49 0.00 54484.61 0.00
                       
Annual Sum or Average                      
Minimum of Months 1411037.64   489900.85 423497.50 0.00 235096.12 101499.55 284.91 0.00 8084.50 0.00
Maximum of Months 2455455.28   489900.85 778371.69 64082.80 235096.12 303257.48 111901.83 0.00 561907.26 55784.63



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 3228629.56 09-JAN-07:30 0.00 0.00 0.00
February 0.00 0.00 2541652.64 14-FEB-07:19 0.00 0.00 0.00
March 0.00 0.00 2068651.25 06-MAR-07:19 0.00 0.00 0.00
April 0.00 0.00 1154886.55 05-APR-06:10 0.00 0.00 0.00
May 0.00 0.00 896432.45 01-MAY-04:10 0.00 0.00 0.00
June 0.00 0.00 287627.87 10-JUN-05:10 0.00 0.00 0.00
July 0.00 0.00 112929.16 08-JUL-06:10 0.00 0.00 0.00
August 0.00 0.00 449777.55 19-AUG-05:10 0.00 0.00 0.00
September 0.00 0.00 744917.13 23-SEP-05:10 0.00 0.00 0.00
October 0.00 0.00 1290716.56 30-OCT-06:49 0.00 0.00 0.00
November 0.00 0.00 2027579.43 27-NOV-05:10 0.00 0.00 0.00
December 0.00 0.00 2877322.87 26-DEC-07:19 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 112929.16   0.00 0.00 0.00
Maximum of Months 0.00 0.00 3228629.56   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.33 20.34 1.33 20.34 0.00 20.34 0.00 20.34
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 25.58 0.00 25.58
May 0.00 0.00 0.00 0.00 0.33 26.70 0.00 26.70
June 0.00 0.00 0.00 0.00 0.83 25.66 0.00 25.66
July 0.00 0.00 0.00 0.00 4.00 26.06 0.00 26.06
August 0.00 0.00 0.00 0.00 4.50 25.83 0.00 25.83
September 0.00 0.00 0.00 0.00 2.00 26.10 0.00 26.10
October 0.00 0.00 0.00 0.00 0.67 25.77 0.00 25.77
November 0.00 0.00 0.00 0.00 0.33 25.67 0.00 25.67
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1.33 20.34 1.33 20.34 12.83 24.98 0.00 24.98
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.33 20.34 1.33 20.34 4.50 26.70 0.00 26.70



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.50 19.21 0.33 19.34 0.00 19.34 0.00 19.34
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.83 19.45 0.17 19.60 0.00 19.60 0.00 19.60
                 
Annual Sum or Average 2.33 19.30 0.50 19.43 0.00 19.43 0.00 19.43
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.50 19.45 0.33 19.60 0.00 19.60 0.00 19.60



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 13.17 17.36 1.33 17.32 0.00 17.32 0.00 17.32
February 6.50 18.55 0.17 18.59 0.00 18.59 0.00 18.59
March 4.17 18.60 0.00 18.60 0.00 18.60 0.00 18.60
April 1.00 18.76 0.00 18.76 0.00 18.76 0.00 18.76
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 1.33 18.09 0.00 18.09 0.00 18.09 0.00 18.09
November 4.17 18.56 0.67 18.80 0.00 18.80 0.00 18.80
December 9.67 17.88 1.33 17.84 0.00 17.84 0.00 17.84
                 
Annual Sum or Average 40.00 17.99 3.50 17.99 0.00 17.99 0.00 17.99
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13.17 18.76 1.33 18.80 0.00 18.80 0.00 18.80



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 26.50 16.23 5.17 16.07 0.00 16.07 0.00 16.07
February 9.50 18.29 1.00 18.47 0.00 18.47 0.00 18.47
March 4.33 18.66 0.33 18.78 0.00 18.78 0.00 18.78
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 1.50 18.98 0.00 18.98 0.00 18.98 0.00 18.98
December 18.83 16.45 3.83 16.25 0.00 16.25 0.00 16.25
                 
Annual Sum or Average 60.67 16.86 10.33 16.72 0.00 16.72 0.00 16.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 26.50 18.98 5.17 18.98 0.00 18.98 0.00 18.98



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 24.83 16.01 3.00 15.94 0.00 15.94 0.00 15.94
February 9.33 17.69 0.67 17.69 0.00 17.69 0.00 17.69
March 4.17 18.34 0.00 18.34 0.00 18.34 0.00 18.34
April 0.17 19.42 0.00 19.42 0.33 24.93 0.33 26.04
May 0.00 0.00 0.00 0.00 2.00 28.25 2.00 28.25
June 0.00 0.00 0.00 0.00 3.67 28.86 3.67 28.86
July 0.00 0.00 0.00 0.00 2.33 28.44 2.33 28.44
August 0.00 0.00 0.00 0.00 3.50 28.70 3.50 28.70
September 0.00 0.00 0.00 0.00 1.17 27.81 1.17 27.81
October 0.17 19.41 0.00 19.41 0.17 23.35 0.17 24.66
November 1.50 18.80 0.00 18.80 0.00 18.80 0.00 18.80
December 19.33 16.13 2.33 16.02 0.00 16.02 0.00 16.02
                 
Annual Sum or Average 59.50 16.57 6.00 16.47 13.17 18.48 13.17 19.92
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.94 0.00 15.94
Maximum of Months 24.83 19.42 3.00 19.42 3.67 28.86 3.67 28.86



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 25.50 16.11 2.50 16.05 0.00 16.05 0.00 16.05
February 11.50 17.48 1.17 17.52 0.00 17.52 0.00 17.52
March 4.83 18.21 0.17 18.10 2.33 21.31 2.33 22.97
April 0.50 19.36 0.00 19.36 1.50 26.21 1.50 27.18
May 0.00 0.00 0.00 0.00 1.17 27.68 1.17 27.68
June 0.00 0.00 0.00 0.00 1.33 28.02 1.33 28.02
July 0.00 0.00 0.00 0.00 3.17 28.34 3.17 28.34
August 0.00 0.00 0.00 0.00 4.83 28.38 4.83 28.38
September 0.00 0.00 0.00 0.00 4.00 28.39 4.00 28.39
October 0.17 18.88 0.00 18.88 3.17 28.10 3.17 28.34
November 2.50 18.57 0.00 18.57 0.00 18.57 0.00 18.57
December 18.83 16.39 2.17 16.28 0.00 16.28 0.00 16.28
                 
Annual Sum or Average 63.83 16.73 6.00 16.66 21.50 19.40 21.50 21.11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 16.05 0.00 16.05
Maximum of Months 25.50 19.36 2.50 19.36 4.83 28.39 4.83 28.39



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 12.17 17.21 1.00 17.10 0.00 17.10 0.00 17.10
February 5.00 18.63 0.00 18.63 0.00 18.63 0.00 18.63
March 1.17 19.19 0.00 19.19 1.33 24.19 0.83 25.29
April 0.00 0.00 0.00 0.00 2.67 29.18 1.50 29.19
May 0.00 0.00 0.00 0.00 4.67 28.83 2.50 28.82
June 0.00 0.00 0.00 0.00 3.00 28.52 1.00 28.59
July 0.00 0.00 0.00 0.00 9.50 28.80 5.17 28.91
August 0.00 0.00 0.00 0.00 7.67 28.71 4.00 28.81
September 0.00 0.00 0.00 0.00 1.50 29.12 1.00 29.17
October 0.00 0.00 0.00 0.00 0.50 27.51 0.50 27.51
November 0.67 19.24 0.00 19.24 0.00 19.24 0.00 19.24
December 3.50 18.90 0.00 18.90 0.00 18.90 0.00 18.90
                 
Annual Sum or Average 22.50 17.95 1.00 17.86 30.83 24.05 16.50 25.20
Minimum of Months 0.00 0.00 0.00 0.00 0.00 17.10 0.00 17.10
Maximum of Months 12.17 19.24 1.00 19.24 9.50 29.18 5.17 29.19



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 67.50 14.97 17.50 14.89 0.00 14.89 0.00 14.89
February 45.67 15.47 7.17 15.43 0.00 15.43 0.00 15.43
March 22.17 16.34 2.00 16.24 0.00 16.24 0.00 16.24
April 4.00 18.47 0.00 18.47 0.00 18.47 0.00 18.47
May 0.17 19.40 0.00 19.40 0.00 19.40 0.00 19.40
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 1.83 18.84 0.00 18.84 0.00 18.84 0.00 18.84
November 23.00 15.91 4.33 15.80 0.00 15.80 0.00 15.80
December 61.33 14.90 14.83 14.78 0.00 14.78 0.00 14.78
                 
Annual Sum or Average 225.67 15.38 45.83 15.26 0.00 15.26 0.00 15.26
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 67.50 19.40 17.50 19.40 0.00 19.40 0.00 19.40



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 115.00 16.42 16.33 16.21 0.00 16.21 0.00 16.21
February 56.83 16.46 3.50 16.42 0.00 16.42 0.00 16.42
March 28.50 17.32 0.83 17.25 0.00 17.25 0.00 17.25
April 4.00 18.48 0.00 18.48 0.00 18.48 0.00 18.48
May 0.00 0.00 0.00 0.00 1.50 28.57 1.50 28.57
June 0.00 0.00 0.00 0.00 3.83 29.02 3.83 29.02
July 0.00 0.00 0.00 0.00 2.83 28.46 2.83 28.46
August 0.00 0.00 0.00 0.00 3.33 28.70 3.33 28.70
September 0.00 0.00 0.00 0.00 0.50 27.62 0.50 27.62
October 1.83 18.79 0.00 18.79 0.00 18.79 0.00 18.79
November 35.17 17.01 4.33 16.82 0.00 16.82 0.00 16.82
December 110.67 16.62 14.00 16.37 0.00 16.37 0.00 16.37
                 
Annual Sum or Average 352.00 16.66 39.00 16.47 12.00 16.83 12.00 17.17
Minimum of Months 0.00 0.00 0.00 0.00 0.00 16.21 0.00 16.21
Maximum of Months 115.00 18.79 16.33 18.79 3.83 29.02 3.83 29.02



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 51.17 15.15 8.83 15.14 0.00 15.14 0.00 15.14
February 32.83 15.87 3.00 15.88 0.00 15.88 0.00 15.88
March 14.83 16.79 0.83 16.68 3.33 18.74 3.33 20.19
April 3.50 18.54 0.00 18.54 1.50 21.58 1.50 23.22
May 0.00 0.00 0.00 0.00 1.67 27.91 1.67 27.91
June 0.00 0.00 0.00 0.00 1.83 27.85 1.83 27.85
July 0.00 0.00 0.00 0.00 3.17 28.40 3.17 28.40
August 0.00 0.00 0.00 0.00 4.67 28.44 4.67 28.44
September 0.00 0.00 0.00 0.00 4.67 28.45 4.67 28.45
October 1.67 18.88 0.00 18.88 3.83 25.84 3.83 27.09
November 17.00 16.23 2.00 16.18 0.00 16.18 0.00 16.18
December 51.00 15.18 8.33 15.12 0.00 15.12 0.00 15.12
                 
Annual Sum or Average 172.00 15.65 23.00 15.59 24.67 17.03 24.67 18.18
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.12 0.00 15.12
Maximum of Months 51.17 18.88 8.83 18.88 4.67 28.45 4.67 28.45



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 52.83 15.04 12.17 14.97 0.00 14.97 0.00 14.97
February 33.83 15.62 4.33 15.60 0.00 15.60 0.00 15.60
March 13.67 16.75 0.67 16.66 0.33 16.91 0.17 17.03
April 3.00 18.70 0.00 18.70 1.50 22.27 0.83 23.44
May 0.00 0.00 0.00 0.00 3.67 29.18 1.50 29.18
June 0.00 0.00 0.00 0.00 2.17 28.72 0.83 28.68
July 0.00 0.00 0.00 0.00 7.17 28.77 3.67 28.84
August 0.00 0.00 0.00 0.00 4.50 28.49 2.83 28.47
September 0.00 0.00 0.00 0.00 1.33 28.95 0.67 29.01
October 1.33 18.78 0.00 18.78 0.00 18.78 0.00 18.78
November 16.00 16.22 1.67 16.10 0.00 16.10 0.00 16.10
December 52.83 15.15 11.17 15.05 0.00 15.05 0.00 15.05
                 
Annual Sum or Average 173.50 15.52 30.00 15.41 20.67 16.65 10.50 17.19
Minimum of Months 0.00 0.00 0.00 0.00 0.00 14.97 0.00 14.97
Maximum of Months 52.83 18.78 12.17 18.78 7.17 29.18 3.67 29.18



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 86.83 14.27 22.67 14.21 0.00 14.21 0.00 14.21
February 72.50 14.71 17.50 14.70 0.00 14.70 0.00 14.70
March 48.50 15.26 9.17 15.19 0.00 15.19 0.00 15.19
April 19.33 15.93 2.67 15.82 0.00 15.82 0.00 15.82
May 1.83 18.76 0.00 18.76 0.00 18.76 0.00 18.76
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 1.67 19.27 0.00 19.27 0.00 19.27 0.00 19.27
October 15.67 16.20 3.00 16.04 0.00 16.04 0.00 16.04
November 57.67 15.02 16.83 14.94 0.00 14.94 0.00 14.94
December 88.00 14.29 24.00 14.21 0.00 14.21 0.00 14.21
                 
Annual Sum or Average 392.00 14.79 95.83 14.70 0.00 14.70 0.00 14.70
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 88.00 19.27 24.00 19.27 0.00 19.27 0.00 19.27



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 87.33 14.27 23.00 14.24 0.00 14.24 0.00 14.24
February 69.50 14.72 14.50 14.73 0.00 14.73 0.00 14.73
March 43.67 15.36 5.00 15.34 0.00 15.34 0.00 15.34
April 17.67 16.02 1.67 15.95 0.00 15.95 0.00 15.95
May 1.50 18.69 0.00 18.69 0.50 20.94 0.50 22.28
June 0.00 0.00 0.00 0.00 3.33 28.80 3.33 28.80
July 0.00 0.00 0.00 0.00 3.17 28.30 3.17 28.30
August 0.00 0.00 0.00 0.00 2.83 28.24 2.83 28.24
September 1.33 19.22 0.00 19.22 0.17 20.11 0.17 20.83
October 13.83 16.31 2.17 16.17 0.00 16.17 0.00 16.17
November 55.17 15.03 13.83 14.95 0.00 14.95 0.00 14.95
December 87.17 14.29 23.67 14.23 0.00 14.23 0.00 14.23
                 
Annual Sum or Average 377.17 14.79 83.83 14.72 10.00 15.01 10.00 15.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 14.23 0.00 14.23
Maximum of Months 87.33 19.22 23.67 19.22 3.33 28.80 3.33 28.80



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 80.83 14.45 18.17 14.44 0.00 14.44 0.00 14.44
February 58.00 14.89 9.17 14.89 0.00 14.89 0.00 14.89
March 36.83 15.64 4.00 15.61 1.00 15.90 1.00 16.18
April 14.83 16.28 1.83 16.15 1.00 16.86 1.00 17.50
May 1.33 18.66 0.00 18.66 0.00 18.66 0.00 18.66
June 0.00 0.00 0.00 0.00 1.00 27.81 1.00 27.81
July 0.00 0.00 0.00 0.00 2.50 28.63 2.50 28.63
August 0.00 0.00 0.00 0.00 3.17 28.48 3.17 28.48
September 1.00 19.23 0.00 19.23 2.50 25.81 2.50 26.91
October 11.00 16.53 1.50 16.33 1.83 17.92 1.83 19.15
November 47.50 15.18 10.33 15.10 0.00 15.10 0.00 15.10
December 78.50 14.48 17.33 14.46 0.00 14.46 0.00 14.46
                 
Annual Sum or Average 329.83 14.96 62.33 14.90 13.00 15.33 13.00 15.74
Minimum of Months 0.00 0.00 0.00 0.00 0.00 14.44 0.00 14.44
Maximum of Months 80.83 19.23 18.17 19.23 3.17 28.63 3.17 28.63



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 82.00 14.40 20.67 14.36 0.00 14.36 0.00 14.36
February 54.83 14.83 9.33 14.81 0.00 14.81 0.00 14.81
March 32.67 15.57 4.67 15.49 0.00 15.49 0.00 15.49
April 11.50 16.83 1.00 16.66 1.50 18.00 0.83 18.64
May 1.00 19.02 0.00 19.02 3.67 26.83 1.50 27.34
June 0.00 0.00 0.00 0.00 2.00 28.80 0.83 28.72
July 0.00 0.00 0.00 0.00 6.83 28.85 3.83 28.94
August 0.00 0.00 0.00 0.00 4.17 28.48 2.50 28.47
September 0.67 19.27 0.00 19.27 1.33 25.58 0.83 26.56
October 7.00 17.03 0.17 16.98 0.00 16.98 0.00 16.98
November 41.00 15.23 10.67 15.11 0.00 15.11 0.00 15.11
December 77.00 14.52 19.67 14.47 0.00 14.47 0.00 14.47
                 
Annual Sum or Average 307.67 14.92 66.17 14.83 19.50 15.52 10.33 15.86
Minimum of Months 0.00 0.00 0.00 0.00 0.00 14.36 0.00 14.36
Maximum of Months 82.00 19.27 20.67 19.27 6.83 28.85 3.83 28.94



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 127.50 29.36 76.83 29.37
February 0.00 0.00 0.00 0.00 44.50 33.64 19.00 33.57
March 0.00 0.00 0.00 0.00 11.83 35.71 3.33 35.67
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 95.17 40.24 44.50 40.29
                 
Annual Sum or Average 0.00   0.00   279.00 34.02 143.67 33.84
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 127.50 40.24 76.83 40.29



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 73.83 28.57 48.67 28.63
February 0.00 0.00 0.00 0.00 44.50 31.82 19.00 31.84
March 0.00 0.00 0.00 0.00 11.50 33.73 3.00 33.84
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 95.17 37.90 44.50 38.04
                 
Annual Sum or Average 0.00   0.00   225.00 33.42 115.17 33.31
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 95.17 37.90 48.67 38.04



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 10.33 28.40 10.33 28.40
February 0.00 0.00 0.00 0.00 44.50 29.34 19.00 29.48
March 0.00 0.00 0.00 0.00 11.00 31.19 2.83 31.18
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 95.17 35.33 44.50 35.54
                 
Annual Sum or Average 0.00   0.00   161.00 32.95 76.67 33.05
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 95.17 35.33 44.50 35.54



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 27.67 0.17 27.67
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.00 27.93 0.50 27.94
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1.17 27.90 0.67 27.89
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.00 27.93 0.50 27.94



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.92 8.00 21.90 8.00 21.88
February 449.50 22.60 1.33 22.60 1.33 22.59
March 478.83 23.23 0.00 23.23 0.00 23.23
April 353.17 23.72 27.50 23.87 0.00 23.87
May 147.83 23.59 187.50 24.34 0.00 24.34
June 32.67 24.94 353.50 24.59 18.50 24.64
July 14.17 26.77 483.17 24.67 14.17 24.73
August 6.33 24.00 469.83 24.49 6.33 24.48
September 60.67 23.31 193.67 24.72 1.33 24.71
October 103.67 23.77 105.17 24.91 0.00 24.91
November 304.33 23.67 57.83 23.99 0.00 23.99
December 490.50 22.56 0.83 22.55 0.83 22.55
             
Annual Sum or Average 2943.67 22.98 1888.33 23.68 50.50 23.69
Minimum of Months 6.33 21.92 0.00 21.90 0.00 21.88
Maximum of Months 502.00 26.77 483.17 24.91 18.50 24.91



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 22.71 36.50 22.56 36.50 22.43
February 452.67 23.32 1.33 23.31 1.33 23.30
March 412.33 23.62 0.67 23.62 0.00 23.62
April 212.67 23.85 17.33 23.97 0.00 23.97
May 89.83 23.78 199.17 24.34 0.00 24.34
June 12.83 24.07 373.83 24.28 2.17 24.29
July 0.00 0.00 491.00 24.31 0.00 24.31
August 0.00 0.00 494.50 24.27 0.00 24.27
September 33.00 23.63 220.67 24.41 0.00 24.41
October 130.83 23.66 51.33 24.05 0.00 24.05
November 264.83 23.73 19.83 23.77 0.00 23.77
December 477.67 23.32 7.83 23.28 7.83 23.25
             
Annual Sum or Average 2588.67 23.38 1914.00 23.76 47.83 23.73
Minimum of Months 0.00 0.00 0.67 22.56 0.00 22.43
Maximum of Months 502.00 24.07 494.50 24.41 36.50 24.41



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.56 188.83 21.19 188.83 20.97
February 454.00 22.17 95.67 21.87 95.67 21.65
March 498.83 22.88 37.67 22.73 37.67 22.60
April 427.67 23.45 0.00 23.45 0.00 23.45
May 163.67 23.55 152.67 24.00 0.00 24.00
June 55.83 23.53 299.50 24.11 4.17 24.12
July 5.50 23.20 449.83 24.22 0.00 24.22
August 46.17 23.31 406.83 24.07 0.00 24.07
September 142.17 23.39 118.50 23.83 0.00 23.83
October 355.83 23.28 3.17 23.29 0.00 23.29
November 464.00 22.71 57.83 22.51 51.83 22.33
December 497.00 21.80 143.33 21.47 143.33 21.26
             
Annual Sum or Average 3612.67 22.61 1953.83 22.82 521.50 22.61
Minimum of Months 5.50 21.56 0.00 21.19 0.00 20.97
Maximum of Months 502.00 23.55 449.83 24.22 188.83 24.22



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.18 446.33 20.10 446.33 20.07
February 454.00 20.47 342.00 20.30 342.00 20.23
March 514.00 21.01 273.33 20.76 273.33 20.64
April 472.83 21.73 122.00 21.40 122.00 21.19
May 308.00 22.48 131.17 22.85 21.00 22.74
June 172.67 22.48 230.00 23.37 7.83 23.35
July 110.00 22.55 335.67 23.75 0.00 23.75
August 184.67 22.59 260.00 23.43 0.67 23.43
September 401.33 22.35 37.50 22.45 10.17 22.44
October 492.00 21.35 100.50 21.05 100.50 20.84
November 489.00 20.67 267.50 20.37 267.50 20.22
December 497.00 20.22 423.00 20.12 423.00 20.08
             
Annual Sum or Average 4597.50 21.22 2969.00 21.28 2014.33 21.02
Minimum of Months 110.00 20.18 37.50 20.10 0.00 20.07
Maximum of Months 514.00 22.59 446.33 23.75 446.33 23.75



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.08 483.50 20.06 483.50 20.06
February 454.00 20.44 383.00 20.37 383.00 20.35
March 514.00 20.96 284.67 20.80 284.67 20.72
April 449.83 22.01 48.33 21.92 44.33 21.82
May 238.33 22.71 166.17 23.37 0.00 23.37
June 82.83 22.99 326.83 23.92 0.00 23.92
July 25.67 23.19 445.67 24.17 3.83 24.18
August 73.33 22.79 372.83 23.88 0.00 23.88
September 299.00 22.46 84.50 22.84 0.00 22.84
October 490.00 21.89 24.67 21.83 24.67 21.78
November 484.50 21.03 219.83 20.84 219.83 20.74
December 497.00 20.17 455.00 20.13 455.00 20.12
             
Annual Sum or Average 4110.50 21.23 3295.00 21.54 1898.83 21.27
Minimum of Months 25.67 20.08 24.67 20.06 0.00 20.06
Maximum of Months 514.00 23.19 483.50 24.17 483.50 24.18



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.06 476.83 20.04 476.83 20.03
February 454.00 20.55 334.83 20.44 334.83 20.39
March 483.17 21.01 239.33 20.89 228.83 20.79
April 370.00 21.64 106.17 21.89 45.17 21.79
May 244.67 22.33 193.50 23.26 6.17 23.31
June 148.17 22.87 315.00 23.77 21.50 23.88
July 107.67 23.06 382.17 23.88 33.50 23.96
August 191.17 22.44 280.17 23.42 15.67 23.52
September 316.33 21.95 113.33 22.57 5.83 22.61
October 466.00 21.45 56.67 21.56 32.50 21.51
November 486.83 20.86 226.83 20.71 226.83 20.63
December 497.00 20.12 456.17 20.09 456.17 20.07
             
Annual Sum or Average 4267.00 21.16 3181.00 21.49 1883.83 21.28
Minimum of Months 107.67 20.06 56.67 20.04 5.83 20.03
Maximum of Months 502.00 23.06 476.83 23.88 476.83 23.96



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 467.33 20.32 379.50 20.16 372.67 20.08
February 376.17 20.77 288.67 20.74 256.00 20.59
March 415.00 21.19 263.83 21.25 216.83 21.11
April 347.83 21.69 153.17 21.98 79.00 21.84
May 238.00 22.21 202.17 23.13 7.67 23.11
June 164.33 22.42 277.33 23.50 6.33 23.55
July 105.00 22.95 369.33 23.93 16.83 24.02
August 162.50 22.87 326.67 23.77 20.50 23.89
September 284.83 22.31 179.50 23.14 19.33 23.27
October 417.83 21.64 129.50 21.94 66.33 21.89
November 431.17 20.92 240.50 20.88 207.50 20.72
December 470.33 20.38 382.83 20.24 382.83 20.19
             
Annual Sum or Average 3880.33 21.33 3193.00 21.75 1651.83 21.52
Minimum of Months 105.00 20.32 129.50 20.16 6.33 20.08
Maximum of Months 470.33 22.95 382.83 23.93 382.83 24.02



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.42 417.50 20.34 417.50 20.31
February 438.50 20.91 259.00 20.80 253.33 20.72
March 463.00 21.34 151.50 21.38 121.83 21.29
April 354.17 22.16 95.33 22.63 11.17 22.68
May 241.17 22.55 219.83 23.48 28.17 23.58
June 148.17 22.85 339.83 23.81 40.33 23.89
July 113.17 24.53 448.17 24.40 84.33 24.52
August 105.17 24.16 428.17 24.24 66.17 24.35
September 295.33 22.15 141.17 22.87 10.33 22.94
October 444.17 21.70 43.33 21.91 4.00 21.91
November 472.17 21.34 88.83 21.25 87.00 21.17
December 497.00 20.71 302.67 20.59 302.67 20.53
             
Annual Sum or Average 4074.00 21.56 2935.33 22.06 1426.83 21.92
Minimum of Months 105.17 20.42 43.33 20.34 4.00 20.31
Maximum of Months 502.00 24.53 448.17 24.40 417.50 24.52



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.73 502.00 19.73 502.00 19.73
February 454.00 19.90 437.83 19.88 437.83 19.87
March 514.00 20.33 420.33 20.25 420.33 20.22
April 485.00 20.92 202.83 20.70 202.83 20.57
May 350.17 21.98 121.00 22.38 22.33 22.29
June 199.33 22.36 232.50 23.24 2.17 23.25
July 128.33 22.75 327.17 23.69 18.00 23.74
August 279.17 22.12 177.83 22.79 0.00 22.79
September 446.67 21.72 25.00 21.78 6.17 21.76
October 502.00 20.76 158.33 20.57 158.33 20.45
November 489.00 20.05 389.67 19.94 389.67 19.89
December 497.00 19.74 497.00 19.74 497.00 19.74
             
Annual Sum or Average 4846.67 20.74 3491.50 20.80 2656.67 20.59
Minimum of Months 128.33 19.73 25.00 19.73 0.00 19.73
Maximum of Months 514.00 22.75 502.00 23.69 502.00 23.74



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 19.50 427.00 19.50 427.00 19.50
February 385.00 19.81 348.83 19.74 348.83 19.72
March 421.33 20.54 297.00 20.38 294.83 20.31
April 340.83 21.10 155.00 21.09 118.33 20.89
May 243.33 22.02 147.50 22.94 9.17 22.98
June 170.17 22.69 229.50 23.59 24.50 23.75
July 142.00 23.20 288.50 23.89 47.83 24.03
August 218.67 22.18 193.33 23.10 16.00 23.24
September 311.50 21.65 69.00 22.09 6.67 22.10
October 406.50 20.88 141.50 20.78 128.00 20.63
November 417.00 19.99 311.67 19.83 311.67 19.76
December 422.00 19.52 419.50 19.51 419.50 19.51
             
Annual Sum or Average 3905.33 20.73 3028.33 20.93 2152.33 20.70
Minimum of Months 142.00 19.50 69.00 19.50 6.67 19.50
Maximum of Months 427.00 23.20 427.00 23.89 427.00 24.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 468.17 19.99 403.17 19.87 392.83 19.79
February 378.67 20.42 310.17 20.37 276.17 20.22
March 417.50 20.96 313.67 21.04 260.33 20.90
April 356.17 21.30 203.00 21.51 128.50 21.32
May 260.33 22.03 192.00 22.86 19.50 22.81
June 202.67 22.20 247.33 23.28 8.67 23.33
July 157.83 22.87 333.00 23.81 32.33 23.94
August 225.17 22.48 273.50 23.43 24.33 23.57
September 311.67 22.10 168.00 22.93 24.00 23.07
October 426.83 21.33 177.00 21.56 115.50 21.46
November 440.00 20.41 301.50 20.34 270.33 20.19
December 476.67 20.03 420.50 19.91 420.50 19.86
             
Annual Sum or Average 4121.67 21.07 3342.83 21.42 1973.00 21.18
Minimum of Months 157.83 19.99 168.00 19.87 8.67 19.79
Maximum of Months 476.67 22.87 420.50 23.81 420.50 23.94



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.81 479.50 19.78 479.50 19.77
February 446.67 20.15 375.83 20.04 375.83 20.01
March 483.50 20.60 337.33 20.53 320.00 20.44
April 419.67 21.10 190.00 21.16 142.00 21.01
May 324.83 22.01 170.50 22.75 35.33 22.81
June 243.83 22.17 229.33 23.15 30.83 23.24
July 200.83 22.96 314.83 23.77 67.50 23.93
August 285.83 22.17 221.83 23.02 36.50 23.16
September 389.33 21.63 76.33 22.06 7.00 22.11
October 467.50 20.87 145.83 20.84 121.67 20.70
November 489.00 20.25 335.67 20.08 335.67 20.00
December 497.00 19.82 483.83 19.80 483.83 19.80
             
Annual Sum or Average 4750.00 20.88 3360.83 21.06 2435.67 20.88
Minimum of Months 200.83 19.81 76.33 19.78 7.00 19.77
Maximum of Months 502.00 22.96 483.83 23.77 483.83 23.93



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.65 502.00 19.65 502.00 19.65
February 454.00 19.77 445.83 19.76 445.83 19.76
March 514.00 20.10 467.83 20.06 467.83 20.05
April 485.00 20.43 301.17 20.25 301.17 20.17
May 410.50 21.44 141.83 21.61 70.67 21.44
June 285.83 21.79 158.00 22.47 9.67 22.44
July 225.67 22.11 236.00 23.00 20.83 23.07
August 366.50 21.60 110.67 22.05 3.50 22.04
September 473.00 21.12 78.17 21.03 71.67 20.94
October 502.00 20.24 302.17 20.04 302.17 19.95
November 489.00 19.80 442.00 19.74 442.00 19.72
December 497.00 19.64 497.00 19.64 497.00 19.64
             
Annual Sum or Average 5204.50 20.49 3682.67 20.45 3134.33 20.29
Minimum of Months 225.67 19.64 78.17 19.64 3.50 19.64
Maximum of Months 514.00 22.11 502.00 23.00 502.00 23.07



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.65 502.00 19.65 502.00 19.65
February 454.00 19.80 419.33 19.75 419.33 19.74
March 508.17 20.35 389.83 20.19 389.83 20.13
April 414.17 20.85 231.17 20.69 200.17 20.49
May 294.50 21.69 197.83 22.51 31.67 22.40
June 205.83 22.42 274.50 23.40 29.83 23.53
July 177.67 22.97 348.67 23.75 56.33 23.88
August 267.67 21.88 227.17 22.88 15.83 22.96
September 386.83 21.33 113.83 21.62 46.83 21.52
October 485.83 20.47 258.67 20.27 251.83 20.15
November 489.00 19.82 413.33 19.72 413.33 19.68
December 497.00 19.64 497.00 19.64 497.00 19.64
             
Annual Sum or Average 4682.67 20.59 3873.33 20.79 2854.00 20.58
Minimum of Months 177.67 19.64 113.83 19.64 15.83 19.64
Maximum of Months 508.17 22.97 502.00 23.75 502.00 23.88



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 479.17 19.79 422.83 19.67 418.83 19.61
February 405.00 20.13 337.67 20.03 313.83 19.90
March 439.83 20.55 359.17 20.56 319.33 20.43
April 380.83 20.82 275.83 20.91 213.83 20.72
May 320.83 21.59 200.33 22.15 59.17 21.96
June 258.67 21.77 215.00 22.74 17.67 22.75
July 208.33 22.30 288.33 23.36 34.33 23.47
August 287.50 21.94 222.67 22.89 30.17 23.02
September 347.33 21.50 181.50 22.13 66.50 22.09
October 434.00 20.61 283.83 20.73 225.67 20.56
November 457.50 19.98 363.17 19.89 342.33 19.78
December 488.50 19.81 448.83 19.71 448.83 19.68
             
Annual Sum or Average 4507.50 20.71 3599.17 20.94 2490.50 20.71
Minimum of Months 208.33 19.79 181.50 19.67 17.67 19.61
Maximum of Months 488.50 22.30 448.83 23.36 448.83 23.47



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.69 485.50 19.66 485.50 19.66
February 447.83 19.93 390.83 19.84 390.83 19.80
March 488.50 20.37 387.67 20.30 372.67 20.23
April 422.00 20.72 260.17 20.75 213.67 20.59
May 350.67 21.76 198.67 22.33 76.17 22.28
June 278.33 22.00 219.83 22.89 44.67 22.98
July 240.33 22.72 292.67 23.55 78.83 23.72
August 320.83 21.95 195.50 22.74 42.17 22.90
September 402.33 21.33 106.67 21.64 47.17 21.61
October 471.33 20.47 248.83 20.34 228.33 20.20
November 489.00 19.92 395.67 19.79 395.67 19.75
December 497.00 19.69 493.00 19.69 493.00 19.68
             
Annual Sum or Average 4910.17 20.67 3675.00 20.81 2868.67 20.64
Minimum of Months 240.33 19.69 106.67 19.66 42.17 19.66
Maximum of Months 502.00 22.72 493.00 23.55 493.00 23.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 23.67 29.02 293.17 27.73 13.17 27.85
February 21.50 32.58 334.17 27.68 21.50 27.96
March 15.17 28.86 502.83 27.11 15.17 27.16
April 35.17 27.00 485.00 27.00 35.17 27.00
May 68.83 27.00 508.00 27.00 68.83 27.00
June 182.67 27.00 496.00 27.00 182.67 27.00
July 326.33 27.00 497.00 27.00 326.33 27.00
August 346.00 27.00 514.00 27.00 346.00 27.00
September 48.50 27.00 485.00 27.00 48.50 27.00
October 16.67 27.00 502.00 27.00 16.67 27.00
November 1.50 27.00 477.83 27.00 1.50 27.00
December 45.83 40.01 466.17 29.33 45.83 30.21
             
Annual Sum or Average 1131.83 27.70 5561.17 27.26 1121.33 27.32
Minimum of Months 1.50 27.00 293.17 27.00 1.50 27.00
Maximum of Months 346.00 40.01 514.00 29.33 346.00 30.21



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 102.00 26.49 134.00 27.12 4.50 27.18
February 55.33 28.55 203.83 27.69 17.17 27.96
March 9.00 29.32 356.17 27.12 8.67 27.17
April 12.83 27.00 463.17 27.00 12.83 27.00
May 38.50 27.00 508.00 27.00 38.50 27.00
June 93.83 27.00 496.00 27.00 93.83 27.00
July 143.83 27.00 497.00 27.00 143.83 27.00
August 103.83 27.00 514.00 27.00 103.83 27.00
September 22.67 27.00 485.00 27.00 22.67 27.00
October 8.67 27.00 493.67 27.00 8.67 27.00
November 13.17 27.00 325.50 27.00 0.00 27.00
December 72.67 33.94 245.83 30.17 44.67 31.17
             
Annual Sum or Average 676.33 27.83 4722.17 27.23 499.17 27.32
Minimum of Months 8.67 26.49 134.00 27.00 0.00 27.00
Maximum of Months 143.83 33.94 514.00 30.17 143.83 31.17



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 243.83 25.29 78.17 25.33 33.33 25.12
February 110.00 27.03 113.17 27.22 0.67 27.24
March 65.67 27.00 227.33 27.04 2.67 27.04
April 33.67 27.00 357.00 27.00 11.67 27.00
May 54.83 27.00 480.83 27.00 54.83 27.00
June 118.17 27.00 491.67 27.00 118.17 27.00
July 162.67 27.00 497.00 27.00 162.67 27.00
August 115.17 27.00 514.00 27.00 115.17 27.00
September 23.33 27.00 477.00 27.00 23.33 27.00
October 26.00 27.00 399.67 27.00 6.17 27.00
November 90.00 27.00 208.83 27.00 0.00 27.00
December 137.17 29.91 136.50 29.92 43.67 30.78
             
Annual Sum or Average 1180.50 26.99 3981.17 27.06 572.33 27.10
Minimum of Months 23.33 25.29 78.17 25.33 0.00 25.12
Maximum of Months 243.83 29.91 514.00 29.92 162.67 30.78



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 87.33 27.18 502.00 27.14 87.33 27.14
February 0.00 0.00 454.00 24.66 0.00 24.66
March 240.83 25.83 514.00 25.70 240.83 25.73
April 205.00 25.60 485.00 24.88 205.00 25.05
May 486.17 27.10 508.00 27.10 486.17 27.10
June 276.00 26.78 495.17 26.19 276.00 26.34
July 494.00 26.68 497.00 26.67 494.00 26.68
August 495.17 26.50 514.00 26.43 495.17 26.46
September 485.00 27.04 485.00 27.04 485.00 27.04
October 14.83 26.85 499.17 24.74 14.83 24.80
November 418.33 25.84 488.17 25.78 418.33 25.80
December 134.00 25.20 497.00 24.56 134.00 24.67
             
Annual Sum or Average 3336.67 26.50 5938.50 26.07 3336.67 26.18
Minimum of Months 0.00 0.00 454.00 24.56 0.00 24.66
Maximum of Months 495.17 27.18 514.00 27.14 495.17 27.14



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.36984 10.64051 0.60755 13.44050
February 454.00000 27.26763 11.18830 0.66298 15.18553
March 514.00000 27.05550 14.55886 0.72794 16.54835
April 485.00000 27.00000 17.98058 0.83566 19.92609
May 508.00000 27.00007 29.93166 0.24438 6.66691
June 496.00000 27.00014 36.13196 0.35204 7.90488
July 497.00000 27.00004 38.21768 0.44747 9.35941
August 514.00000 27.00029 36.95803 0.45483 9.50845
September 485.00000 27.00007 34.10995 0.24289 6.52824
October 502.00000 27.00000 26.98581 0.82485 19.53092
November 489.00000 27.00000 17.33985 0.73578 16.64400
December 497.00000 28.19968 11.31934 0.86911 21.92483
           
Annual Sum or Average 5943.00000 27.15686 23.88311 0.58287 13.57298
Minimum of Months 454.00000 27.00000 10.64051 0.24289 6.52824
Maximum of Months 514.00000 28.19968 38.21768 0.86911 21.92483



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.04114 10.58770 0.45371 10.22643
February 454.00000 27.20500 11.18086 0.55193 12.18070
March 514.00000 27.04252 14.55579 0.62054 13.56778
April 485.00000 27.00000 17.97572 0.71836 16.16714
May 508.00000 27.00007 29.93497 0.16444 6.13356
June 496.00000 27.00015 36.17374 0.26751 6.92572
July 497.00000 27.00005 38.27143 0.33378 7.60722
August 514.00000 27.00029 37.08073 0.30300 7.22669
September 485.00000 27.00007 34.13490 0.14324 5.79528
October 502.00000 27.00000 26.98064 0.73782 16.70536
November 489.00000 27.00000 17.33479 0.60017 12.95684
December 497.00000 28.01537 11.35158 0.69572 18.03604
           
Annual Sum or Average 5943.00000 27.10778 23.90017 0.46486 11.10912
Minimum of Months 454.00000 27.00000 10.58770 0.14324 5.79528
Maximum of Months 514.00000 28.01537 38.27143 0.73782 18.03604



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.19811 10.64929 0.21596 8.55566
February 454.00000 27.11698 11.17837 0.44997 9.82509
March 514.00000 27.02297 14.56026 0.52621 11.33537
April 485.00000 27.00000 17.97936 0.63871 14.13607
May 508.00000 27.00102 29.94051 0.10874 6.31688
June 496.00000 27.00015 36.19008 0.24053 7.02928
July 497.00000 27.00006 38.28034 0.31395 7.65208
August 514.00000 27.00024 37.26115 0.26571 7.06660
September 485.00000 27.00059 34.18665 0.05737 5.74909
October 502.00000 27.00012 26.99153 0.64120 14.05439
November 489.00000 27.00000 17.34151 0.50378 10.86138
December 497.00000 27.80676 11.39698 0.56858 14.73616
           
Annual Sum or Average 5943.00000 27.01084 23.93355 0.37670 9.76736
Minimum of Months 454.00000 26.19811 10.64929 0.05737 5.74909
Maximum of Months 514.00000 27.80676 38.28034 0.64120 14.73616



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.13133 29.98109 0.97134 25.00455
February 454.00000 24.65727 28.10988 0.65020 13.93684
March 514.00000 25.63849 26.85362 0.93508 23.63958
April 485.00000 24.57921 24.97569 0.92901 23.99250
May 508.00000 27.09535 32.46237 0.52282 10.84859
June 496.00000 25.84793 41.65762 0.45332 11.68321
July 497.00000 26.65984 44.86360 0.94907 24.83912
August 514.00000 26.37274 44.52089 1.04013 29.79253
September 485.00000 27.04160 33.88777 0.57608 12.12101
October 502.00000 24.65984 31.38450 0.76390 17.51990
November 489.00000 25.73002 27.52842 1.00815 26.63222
December 497.00000 24.38863 28.20035 0.88203 21.66570
           
Annual Sum or Average 5943.00000 25.82896 32.93453 0.80851 20.20794
Minimum of Months 454.00000 24.38863 24.97569 0.45332 10.84859
Maximum of Months 514.00000 27.13133 44.86360 1.04013 29.79253



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.92092 10.48812 -0.3179 7.84501
February 454.00000 22.62780 11.75788 -0.1441 6.51084
March 514.00000 23.35506 15.32044 0.04708 5.82471
April 485.00000 24.11665 17.33627 0.23828 6.49631
May 508.00000 24.24726 31.51348 -0.4921 11.21344
June 496.00000 24.36920 42.03017 -0.3637 8.57495
July 497.00000 24.58793 46.67681 -0.2487 7.56997
August 514.00000 24.42829 46.63371 -0.2858 7.68588
September 485.00000 24.26043 36.53136 -0.4311 10.30604
October 502.00000 24.30562 27.74394 0.36990 8.45144
November 489.00000 24.14875 17.88276 0.25481 6.95440
December 497.00000 22.59102 11.65812 -0.1432 6.43151
           
Annual Sum or Average 5943.00000 23.75293 26.43341 -0.1272 7.83095
Minimum of Months 454.00000 21.92092 10.48812 -0.4921 5.82471
Maximum of Months 514.00000 24.58793 46.67681 0.36990 11.21344



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.71395 11.23762 -0.1819 6.99241
February 454.00000 23.32027 12.84797 -0.0164 5.73248
March 514.00000 23.74501 15.80951 0.12852 5.82622
April 485.00000 24.15946 17.76294 0.26650 6.68477
May 508.00000 24.22383 32.20920 -0.4708 10.43627
June 496.00000 24.21027 45.17968 -0.3608 8.21996
July 497.00000 24.30701 51.45448 -0.2684 6.92489
August 514.00000 24.25480 50.95771 -0.2831 7.06478
September 485.00000 24.21156 38.16489 -0.4375 9.60239
October 502.00000 24.11657 28.39319 0.32183 7.39477
November 489.00000 24.06091 18.99598 0.22626 6.46338
December 497.00000 23.35251 12.50456 -0.0079 5.84496
           
Annual Sum or Average 5943.00000 23.89277 28.10349 -0.0916 7.27513
Minimum of Months 454.00000 22.71395 11.23762 -0.4708 5.73248
Maximum of Months 514.00000 24.30701 51.45448 0.32183 10.43627



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.56079 11.66124 -0.4716 12.18295
February 454.00000 22.16632 13.27850 -0.3084 8.87031
March 514.00000 22.91201 16.52511 -0.0933 6.69067
April 485.00000 23.53937 19.11617 0.09181 5.73927
May 508.00000 24.03595 32.88213 -0.5611 12.72577
June 496.00000 24.04564 45.96494 -0.4465 9.74847
July 497.00000 24.18181 52.31758 -0.3546 8.02716
August 514.00000 24.03322 52.20022 -0.4083 8.96847
September 485.00000 23.90974 39.32975 -0.5682 12.40557
October 502.00000 23.52123 30.25252 0.15822 6.09366
November 489.00000 22.77817 20.54583 -0.1082 7.24591
December 497.00000 21.79963 12.99970 -0.3986 10.42018
           
Annual Sum or Average 5943.00000 23.21480 29.06824 -0.2894 9.09684
Minimum of Months 454.00000 21.56079 11.66124 -0.5682 5.73927
Maximum of Months 514.00000 24.18181 52.31758 0.15822 12.72577



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.17798 12.27685 -0.8641 23.52500
February 454.00000 20.46543 13.91678 -0.7618 20.02376
March 514.00000 21.00959 17.93779 -0.5815 14.65188
April 485.00000 21.78341 20.76622 -0.3411 10.13543
May 508.00000 23.13850 34.31171 -0.8623 24.46676
June 496.00000 23.48485 47.92262 -0.6170 15.49381
July 497.00000 23.72197 54.44605 -0.4856 11.58551
August 514.00000 23.44755 54.72189 -0.5951 14.24142
September 485.00000 22.62159 42.52833 -1.0100 28.84431
October 502.00000 21.39822 32.88610 -0.3717 10.48347
November 489.00000 20.67026 22.18259 -0.6428 17.34361
December 497.00000 20.21559 13.85321 -0.8387 22.67614
           
Annual Sum or Average 5943.00000 21.85723 30.79706 -0.6634 17.75913
Minimum of Months 454.00000 20.17798 12.27685 -1.0100 10.13543
Maximum of Months 514.00000 23.72197 54.72189 -0.3411 28.84431



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.07989 10.80657 -0.9369 25.37923
February 454.00000 20.44113 12.65560 -0.7756 19.25578
March 514.00000 20.96475 16.45400 -0.5712 13.49564
April 485.00000 22.15976 18.68000 -0.2114 7.56058
May 508.00000 23.49347 32.19384 -0.6842 17.95991
June 496.00000 23.91484 45.05684 -0.4050 9.70678
July 497.00000 24.11986 51.37250 -0.2728 7.41123
August 514.00000 23.82922 51.49773 -0.4028 9.50592
September 485.00000 23.05550 39.72398 -0.8168 21.59831
October 502.00000 21.93307 30.01711 -0.2039 7.00970
November 489.00000 21.05060 20.05480 -0.5111 12.12551
December 497.00000 20.17311 12.65178 -0.8570 22.55354
           
Annual Sum or Average 5943.00000 22.11477 28.57509 -0.5526 14.42475
Minimum of Months 454.00000 20.07989 10.80657 -0.9369 7.00970
Maximum of Months 514.00000 24.11986 51.49773 -0.2039 25.37923



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.06053 10.39595 -0.9232 25.01707
February 454.00000 20.55413 12.19982 -0.7184 17.64587
March 514.00000 21.20815 15.87207 -0.4773 12.47675
April 485.00000 22.22786 18.24853 -0.1214 8.61673
May 508.00000 23.27708 32.47677 -0.6364 18.66112
June 496.00000 23.61207 45.76133 -0.3690 12.16031
July 497.00000 23.73496 52.32551 -0.2615 9.73970
August 514.00000 23.29131 53.04660 -0.4675 13.99164
September 485.00000 22.64739 40.44603 -0.8481 24.89617
October 502.00000 21.65400 30.05165 -0.2335 7.93512
November 489.00000 20.87736 19.94680 -0.5396 12.63259
December 497.00000 20.12486 12.28585 -0.8684 23.01135
           
Annual Sum or Average 5943.00000 21.95073 28.73904 -0.5375 15.54395
Minimum of Months 454.00000 20.06053 10.39595 -0.9232 7.93512
Maximum of Months 514.00000 23.73496 53.04660 -0.1214 25.01707



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.57044 10.27968 -0.7397 21.67504
February 454.00000 21.36565 11.72223 -0.4748 15.97074
March 514.00000 21.77189 15.45894 -0.3251 12.73176
April 485.00000 22.39781 18.10648 -0.0895 9.65159
May 508.00000 23.25547 32.45172 -0.6815 20.16134
June 496.00000 23.46605 46.11883 -0.4861 13.92718
July 497.00000 23.79219 52.21517 -0.2967 10.21213
August 514.00000 23.59889 52.05501 -0.3728 12.31121
September 485.00000 23.04615 39.52687 -0.7067 22.57231
October 502.00000 22.07420 29.41995 -0.1234 9.71416
November 489.00000 21.31636 19.58584 -0.4190 13.01695
December 497.00000 20.58237 12.24296 -0.7193 19.92662
           
Annual Sum or Average 5943.00000 22.27820 28.41646 -0.4528 15.14435
Minimum of Months 454.00000 20.57044 10.27968 -0.7397 9.65159
Maximum of Months 514.00000 23.79219 52.21517 -0.0895 22.57231



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.42371 10.06276 -0.7747 19.58743
February 454.00000 21.01901 11.73345 -0.5533 13.67652
March 514.00000 21.60464 15.39401 -0.3176 9.99080
April 485.00000 22.73076 17.57231 0.05033 8.23103
May 508.00000 23.38238 32.08937 -0.5393 17.27723
June 496.00000 23.67586 45.45762 -0.3036 11.12795
July 497.00000 24.18444 50.91646 -0.0412 8.54032
August 514.00000 23.98772 50.71179 -0.1387 9.03408
September 485.00000 22.86979 39.72436 -0.7220 21.09677
October 502.00000 21.97656 29.41122 -0.1134 7.16973
November 489.00000 21.43992 19.29015 -0.3524 9.04807
December 497.00000 20.70619 11.82389 -0.6309 14.74591
           
Annual Sum or Average 5943.00000 22.34470 27.99485 -0.3682 12.44120
Minimum of Months 454.00000 20.42371 10.06276 -0.7747 7.16973
Maximum of Months 514.00000 24.18444 50.91646 0.05033 21.09677



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.73096 10.42118 -1.1044 32.61795
February 454.00000 19.90007 12.35232 -0.9841 27.76831
March 514.00000 20.32655 16.38354 -0.7951 20.44553
April 485.00000 20.92334 19.91733 -0.5329 12.88377
May 508.00000 22.61295 33.51352 -0.9732 29.29401
June 496.00000 23.27153 46.85909 -0.6184 15.78365
July 497.00000 23.59173 53.55295 -0.4596 11.36175
August 514.00000 22.84805 54.78122 -0.7340 18.96659
September 485.00000 21.86886 42.44678 -1.2075 37.36086
October 502.00000 20.76499 31.71885 -0.5110 11.86056
November 489.00000 20.05318 20.88291 -0.8274 22.42605
December 497.00000 19.73892 12.03975 -1.0726 31.37565
           
Annual Sum or Average 5943.00000 21.31599 29.72671 -0.8169 22.62803
Minimum of Months 454.00000 19.73096 10.42118 -1.2075 11.36175
Maximum of Months 514.00000 23.59173 54.78122 -0.4596 37.36086



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 19.50444 10.16832 -1.1357 34.29469
February 385.00000 19.80813 11.91216 -0.9618 27.25115
March 433.00000 20.63326 15.47355 -0.6752 17.85124
April 410.00000 21.63128 18.85967 -0.3018 11.52698
May 430.00000 22.97987 32.67076 -0.7586 23.68896
June 418.00000 23.40725 46.40230 -0.4512 15.06633
July 422.00000 23.65512 53.10977 -0.3114 11.66482
August 433.00000 22.97374 54.17830 -0.5980 18.37116
September 410.00000 22.19970 41.56999 -1.0318 32.08686
October 427.00000 21.04828 30.59675 -0.4279 11.49400
November 417.00000 19.99409 20.16648 -0.8289 22.74183
December 422.00000 19.51801 11.81006 -1.1118 33.28161
           
Annual Sum or Average 5034.00000 21.45746 29.03823 -0.7146 21.56221
Minimum of Months 385.00000 19.50444 10.16832 -1.1357 11.49400
Maximum of Months 433.00000 23.65512 54.17830 -0.3018 34.29469



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.26445 10.06190 -0.8387 25.86792
February 454.00000 21.03443 11.43615 -0.5647 19.46670
March 514.00000 21.56767 15.22988 -0.3917 15.28830
April 485.00000 22.07556 18.58017 -0.1772 11.71020
May 508.00000 23.05589 32.79364 -0.7490 23.16540
June 496.00000 23.24291 46.83749 -0.5655 16.78878
July 497.00000 23.63670 53.21997 -0.3598 12.31391
August 514.00000 23.27924 53.31785 -0.4888 16.08348
September 485.00000 22.81652 40.16817 -0.7809 26.31516
October 502.00000 21.75859 29.82114 -0.2071 11.73854
November 489.00000 20.79680 20.08400 -0.5754 17.87797
December 497.00000 20.19067 11.77300 -0.8635 25.28934
           
Annual Sum or Average 5943.00000 21.98585 28.76543 -0.5467 18.47722
Minimum of Months 454.00000 20.19067 10.06190 -0.8635 11.71020
Maximum of Months 514.00000 23.63670 53.31785 -0.1772 26.31516



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.81068 10.12009 -1.0307 29.89344
February 454.00000 20.20991 11.84543 -0.8431 23.28828
March 514.00000 20.80451 15.70574 -0.6122 16.87313
April 485.00000 21.50673 19.09654 -0.3182 11.85217
May 508.00000 22.75810 33.25005 -0.7929 26.11511
June 496.00000 23.04948 47.29659 -0.5604 17.95554
July 497.00000 23.50418 53.57673 -0.3404 13.37049
August 514.00000 22.86337 54.55500 -0.5982 18.83084
September 485.00000 22.06363 41.82839 -1.0506 33.29758
October 502.00000 21.08629 30.87994 -0.3934 10.77889
November 489.00000 20.24695 20.46778 -0.7462 19.68472
December 497.00000 19.81967 11.73960 -0.9997 28.50749
           
Annual Sum or Average 5943.00000 21.48896 29.35277 -0.6891 20.83989
Minimum of Months 454.00000 19.81068 10.12009 -1.0506 10.77889
Maximum of Months 514.00000 23.50418 54.55500 -0.3182 33.29758



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.64637 10.83234 -1.1976 36.52826
February 454.00000 19.77260 12.66883 -1.0892 32.22395
March 514.00000 20.10459 16.92975 -0.9206 25.30047
April 485.00000 20.43447 20.55165 -0.6981 18.03134
May 508.00000 21.89921 34.84268 -1.2138 39.34970
June 496.00000 22.58031 49.05577 -0.8228 23.53829
July 497.00000 22.94679 56.22696 -0.6406 17.16654
August 514.00000 22.12638 57.69096 -0.9535 27.51924
September 485.00000 21.17934 44.23278 -1.4736 49.81397
October 502.00000 20.23901 33.04661 -0.7033 18.12319
November 489.00000 19.80256 21.36804 -0.9690 28.02687
December 497.00000 19.63799 12.54598 -1.1747 35.51548
           
Annual Sum or Average 5943.00000 20.87521 30.99701 -0.9871 29.22291
Minimum of Months 454.00000 19.63799 10.83234 -1.4736 17.16654
Maximum of Months 514.00000 22.94679 57.69096 -0.6406 49.81397



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.65126 10.79896 -1.1625 35.24073
February 454.00000 19.80471 12.61300 -1.0230 29.89448
March 514.00000 20.38532 16.60547 -0.7848 21.46648
April 485.00000 21.30822 19.56254 -0.4135 14.47135
May 508.00000 22.72914 33.50084 -0.8519 27.31938
June 496.00000 23.26145 47.19185 -0.4882 16.62831
July 497.00000 23.55000 54.06407 -0.3214 12.70967
August 514.00000 22.80781 55.49125 -0.6487 20.50146
September 485.00000 21.86525 42.64882 -1.1820 38.72861
October 502.00000 20.58468 32.24811 -0.5956 16.06449
November 489.00000 19.81870 21.31847 -0.9380 27.01299
December 497.00000 19.64398 12.51402 -1.1507 34.66113
           
Annual Sum or Average 5943.00000 21.29783 30.03631 -0.7947 24.49594
Minimum of Months 454.00000 19.64398 10.79896 -1.1820 12.70967
Maximum of Months 514.00000 23.55000 55.49125 -0.3214 38.72861



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.97823 10.64146 -0.9749 30.47199
February 454.00000 20.54697 12.07030 -0.7392 24.53644
March 514.00000 21.07825 16.00028 -0.5684 19.19659
April 485.00000 21.51828 19.32532 -0.3552 15.33855
May 508.00000 22.49340 33.85970 -0.9487 30.89660
June 496.00000 22.78272 48.49167 -0.7075 22.35419
July 497.00000 23.20930 55.27595 -0.4818 16.53802
August 514.00000 22.76208 55.60253 -0.6528 22.05533
September 485.00000 22.23755 41.72628 -1.0158 35.55925
October 502.00000 21.11441 31.29782 -0.4211 16.04361
November 489.00000 20.23523 20.90077 -0.7732 23.71862
December 497.00000 19.87797 12.42768 -1.0108 30.45203
           
Annual Sum or Average 5943.00000 21.49564 29.96283 -0.7205 23.91299
Minimum of Months 454.00000 19.87797 10.64146 -1.0158 15.33855
Maximum of Months 514.00000 23.20930 55.60253 -0.3552 35.55925



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.68806 10.70499 -1.1268 33.91022
February 454.00000 19.98391 12.38805 -0.9535 27.81356
March 514.00000 20.54889 16.38827 -0.7291 20.75477
April 485.00000 21.15240 19.67612 -0.4440 15.39838
May 508.00000 22.46643 33.87003 -0.9085 31.28044
June 496.00000 22.82672 48.32453 -0.6314 21.31316
July 497.00000 23.28433 54.98799 -0.4015 15.98715
August 514.00000 22.58990 56.09658 -0.6895 22.71191
September 485.00000 21.76016 42.75214 -1.1954 40.18006
October 502.00000 20.67522 32.06717 -0.5446 15.28251
November 489.00000 19.92025 21.13421 -0.8833 25.04720
December 497.00000 19.69163 12.41340 -1.0978 32.59475
           
Annual Sum or Average 5943.00000 21.22767 30.22695 -0.7989 25.15137
Minimum of Months 454.00000 19.68806 10.70499 -1.1954 15.28251
Maximum of Months 514.00000 23.28433 56.09658 -0.4015 40.18006



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.106025E+10 3510.23 31-JAN-06:06 119.26 0.473220E+10 0.00 0.579245E+10 0.72 4.50 07-JAN-21:10 0.00 0.00
February 0.372380E+11 146645.02 08-FEB-17:53 199.34 0.167796E+12 0.00 0.205034E+12 1.34 6.54 08-FEB-17:53 0.00 0.00
March 0.538954E+11 153103.61 31-MAR-14:02 611.14 0.253933E+12 0.00 0.307828E+12 3.90 6.63 31-MAR-14:02 0.00 0.00
April 0.651158E+11 227124.93 23-APR-16:23 580.99 0.321431E+12 0.00 0.386546E+12 3.88 7.02 23-APR-19:03 0.00 0.00
May 0.946965E+11 266365.59 18-MAY-10:20 285.71 0.558675E+12 0.00 0.653371E+12 2.03 7.01 18-MAY-09:15 0.00 0.00
June 0.214462E+12 270625.37 29-JUN-04:14 473.58 0.131417E+13 0.00 0.152863E+13 3.76 7.11 08-JUN-16:10 0.00 0.00
July 0.248117E+12 285243.63 05-JUL-10:20 660.86 0.152649E+13 0.00 0.177461E+13 4.95 7.15 21-JUL-04:12 0.00 0.00
August 0.218746E+12 264132.68 22-AUG-12:20 657.21 0.132665E+13 0.00 0.154539E+13 4.83 7.11 31-AUG-04:13 0.00 0.00
September 0.573792E+11 257268.03 07-SEP-14:30 239.90 0.309173E+12 0.00 0.366552E+12 1.64 7.01 07-SEP-14:10 0.00 0.00
October 0.517641E+11 193581.45 26-OCT-13:20 250.87 0.248145E+12 0.00 0.299909E+12 1.57 6.99 26-OCT-13:20 0.00 0.00
November 0.504076E+11 147875.80 21-NOV-06:14 666.02 0.241403E+12 0.00 0.291811E+12 4.42 6.55 20-NOV-03:34 0.00 0.00
December 0.601031E+11 105890.38 06-DEC-05:10 653.98 0.287262E+12 0.00 0.347365E+12 4.21 4.85 17-DEC-00:15 0.00 0.00
                         
Annual Sum or Average 0.115298E+13     5398.86 0.655986E+13 0.00 0.771284E+13 3.11     0.00 0.00
Minimum of Months 0.106025E+10 3510.23   119.26 0.473220E+10 0.00 0.579245E+10 0.72 4.50   0.00 0.00
Maximum of Months 0.248117E+12 285243.63   666.02 0.152649E+13 0.00 0.177461E+13 4.95 7.15   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 0.00 0.00
February 0.00 0.00 01-FEB-00:01 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 0.00 0.00
March 0.00 0.00 01-MAR-00:01 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:03 0.00 0.00
May 0.834421E+10 187352.59 26-MAY-12:05 15.75 0.537525E+11 0.00 0.620967E+11 0.14 6.80 18-MAY-13:05 0.00 0.00
June 0.365671E+11 270625.37 29-JUN-04:14 61.11 0.234313E+12 0.00 0.270881E+12 0.54 6.92 21-JUN-14:05 0.00 0.00
July 0.678668E+11 285243.63 05-JUL-10:20 116.40 0.437298E+12 0.00 0.505165E+12 1.00 6.89 05-JUL-05:04 0.00 0.00
August 0.520024E+11 231885.23 31-AUG-12:40 88.83 0.338257E+12 0.00 0.390259E+12 0.77 6.94 01-AUG-04:14 0.00 0.00
September 0.279704E+10 178376.67 01-SEP-11:00 5.42 0.180825E+11 0.00 0.208796E+11 0.05 6.78 01-SEP-11:00 0.00 0.00
October 0.00 0.00 01-OCT-00:01 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 0.00 0.00
November 0.00 0.00 01-NOV-00:01 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 0.00 0.00
                         
Annual Sum or Average 0.167577E+12     287.52 0.108170E+13 0.00 0.124928E+13 0.21     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.678668E+11 285243.63   116.40 0.437298E+12 0.00 0.505165E+12 1.00 6.94   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:01 313699.73 23-JAN-06:30 21.03 21.01 2.85
February 781527.11 29.87 54.37 21-FEB-14:08 715774.95 06-FEB-02:28 21.56 21.31 25.92
March 814328.51 10.82 97.60 31-MAR-14:05 1069132.13 31-MAR-14:05 21.18 20.80 40.72
April 0.467794E+09 56.29 27892.31 23-APR-14:26 1621607.65 23-APR-14:27 21.27 20.81 48.44
May 0.703081E+10 209.29 27892.31 16-MAY-12:30 2066143.42 16-MAY-13:40 21.89 21.21 30.76
June 0.221710E+11 461.41 27892.31 06-JUN-10:00 2026043.23 08-JUN-14:50 23.63 22.03 58.42
July 0.323266E+11 563.47 27892.31 03-JUL-08:20 2129253.66 05-JUL-14:00 23.74 21.93 78.01
August 0.240438E+11 509.82 27892.31 01-AUG-04:14 2008427.04 22-AUG-12:20 23.12 21.53 77.10
September 0.301601E+10 162.88 27892.31 01-SEP-08:35 2050645.47 07-SEP-14:30 21.58 21.18 26.35
October 0.308089E+09 155.86 9477.56 19-OCT-15:00 1404031.76 18-OCT-13:34 21.90 21.58 28.66
November 61828819.44 18.27 5287.43 01-NOV-14:06 937668.30 01-NOV-14:06 21.16 20.78 42.80
December 7175.43 0.51 12.16 26-DEC-06:40 435530.39 26-DEC-06:40 21.12 20.69 47.52
                   
Annual Sum or Average 0.894276E+11 2178.48         21.94 21.24 42.41
Minimum of Months 0.00 0.00 0.00   313699.73   21.03 20.69 2.85
Maximum of Months 0.323266E+11 563.47 27892.31   2129253.66   23.74 22.03 78.01



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:01 0.00 01-JAN-00:01 21.03 21.03 0.00
February 0.00 0.00 0.00 01-FEB-00:01 0.00 01-FEB-00:01 21.56 21.56 0.00
March 0.00 0.00 0.00 01-MAR-00:01 0.00 01-MAR-00:01 21.18 21.18 0.00
April 0.00 0.00 0.00 01-APR-00:03 0.00 01-APR-00:03 21.27 21.27 0.00
May 0.116911E+10 11.92 27892.31 17-MAY-13:30 1711861.41 16-MAY-15:30 21.89 21.83 1.45
June 0.771736E+10 77.15 27892.31 19-JUN-10:01 1878444.90 08-JUN-15:50 23.63 23.23 8.57
July 0.137355E+11 136.92 27892.31 03-JUL-12:15 2129253.66 05-JUL-14:00 23.74 23.07 15.20
August 0.933010E+10 93.12 27892.31 01-AUG-04:14 1724042.47 31-AUG-12:40 23.12 22.67 10.98
September 0.443488E+09 4.42 27892.31 01-SEP-10:30 1489935.58 01-SEP-15:40 21.58 21.56 0.56
October 0.00 0.00 0.00 01-OCT-00:01 0.00 01-OCT-00:01 21.90 21.90 0.00
November 0.00 0.00 0.00 01-NOV-00:01 0.00 01-NOV-00:01 21.16 21.16 0.00
December 0.00 0.00 0.00 01-DEC-00:01 0.00 01-DEC-00:01 21.12 21.12 0.00
                   
Annual Sum or Average 0.323956E+11 323.53         21.94 21.80 3.10
Minimum of Months 0.00 0.00 0.00   0.00   21.03 21.03 0.00
Maximum of Months 0.137355E+11 136.92 27892.31   2129253.66   23.74 23.23 15.20



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.164629E+13 0.00 698.57 3841106.31 02-JAN-04:01 0.00 37.38 78.79 3.68 0.00 0.14 0.88 02-JAN-04:01
February 0.101537E+13 0.00 603.80 3458925.58 28-FEB-06:01 0.00 36.03 75.70 2.40 0.00 0.10 0.79 28-FEB-06:01
March 0.672435E+12 0.00 586.98 3530184.95 31-MAR-04:01 0.00 31.08 68.80 1.32 0.00 0.06 0.81 31-MAR-04:01
April 0.188653E+12 0.00 404.65 3581806.44 07-APR-04:01 0.00 24.74 51.37 0.38 0.00 0.02 0.82 07-APR-04:01
May 0.292723E+11 0.00 162.52 3152227.31 01-MAY-05:01 0.00 22.59 32.20 0.06 0.00 0.00 0.72 01-MAY-05:01
June 0.584273E+10 0.00 87.40 378596.41 10-JUN-05:01 0.00 20.43 25.89 0.01 0.00 0.00 0.09 10-JUN-05:01
July 0.218617E+10 0.00 49.07 160465.17 10-JUL-05:01 0.00 20.28 23.26 0.00 0.00 0.00 0.04 10-JUL-05:01
August 0.819376E+10 0.00 116.11 901814.53 19-AUG-05:01 0.00 20.53 27.56 0.02 0.00 0.00 0.21 19-AUG-05:01
September 0.493372E+11 0.00 246.76 3143504.72 23-SEP-05:01 0.00 21.92 36.96 0.11 0.00 0.00 0.72 23-SEP-05:01
October 0.184287E+12 0.00 435.44 3684137.74 06-OCT-04:01 0.00 24.85 51.51 0.38 0.00 0.02 0.85 06-OCT-04:01
November 0.543033E+12 0.00 567.50 3676641.31 24-NOV-05:01 0.00 31.29 67.04 1.13 0.00 0.05 0.84 24-NOV-05:01
December 0.142511E+13 0.00 682.45 3790532.22 26-DEC-04:01 0.00 36.68 77.52 3.07 0.00 0.12 0.87 26-DEC-04:01
                           
Annual Sum or Average 0.577001E+13 0.00 4641.25     0.00 27.27 51.25 1.04 0.00 0.04    
Minimum of Months 0.218617E+10 0.00 49.07 160465.17   0.00 20.28 23.26 0.00 0.00 0.00 0.04  
Maximum of Months 0.164629E+13 0.00 698.57 3841106.31   0.00 37.38 78.79 3.68 0.00 0.14 0.88  



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 288.56 0.00 0.17 288.56 0.00 0.00 0.00 0.00 0.48 02-JAN-04:30 0.48 02-JAN-04:30 0.00 0.00 0.00
February 3610.96 0.00 2.35 3610.96 0.00 0.00 0.00 0.00 0.94 06-FEB-04:01 0.94 06-FEB-04:01 0.00 0.00 0.00
March 278.72 0.00 0.20 278.72 0.00 0.00 0.00 0.00 0.85 26-MAR-11:09 0.85 26-MAR-11:09 0.00 0.00 0.00
April 0.572825E+10 0.00 61.09 0.572825E+10 0.00 0.00 0.00 0.00 130055.91 23-APR-15:11 130055.91 23-APR-15:11 0.00 0.00 0.00
May 0.459015E+11 0.00 236.19 0.450256E+11 0.00 0.00 0.00 0.00 155114.15 25-MAY-15:00 144036.71 18-MAY-15:00 0.00 0.00 0.00
June 0.104210E+12 0.00 377.17 0.846726E+11 0.00 0.00 0.00 0.00 232922.76 30-JUN-05:02 167855.29 29-JUN-16:00 0.00 0.00 0.00
July 0.140679E+12 0.00 441.98 0.110014E+12 0.00 0.00 0.00 0.00 345221.92 05-JUL-10:32 159883.58 24-JUL-15:00 0.00 0.00 0.00
August 0.112835E+12 0.00 433.14 0.860685E+11 0.00 0.00 0.00 0.00 244247.05 31-AUG-12:40 165324.29 08-AUG-15:00 0.00 0.00 0.00
September 0.242210E+11 0.00 176.90 0.216531E+11 0.00 0.00 0.00 0.00 162304.66 01-SEP-11:00 150277.66 01-SEP-15:30 0.00 0.00 0.00
October 0.398972E+10 0.00 43.96 0.398972E+10 0.00 0.00 0.00 0.00 90498.14 19-OCT-15:00 90498.14 19-OCT-15:00 0.00 0.00 0.00
November 0.559479E+09 0.00 11.42 0.559479E+09 0.00 0.00 0.00 0.00 31145.94 01-NOV-14:53 31145.94 01-NOV-14:53 0.00 0.00 0.00
December 1062893.78 0.00 0.34 1062893.78 0.00 0.00 0.00 0.00 3541.92 05-DEC-17:05 3541.92 05-DEC-17:05 0.00 0.00 0.00
                               
Annual Sum or Average 0.438125E+12 0.00 1784.91 0.357712E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 278.72 0.00 0.17 278.72 0.00 0.00 0.00 0.00 0.48   0.48   0.00 0.00 0.00
Maximum of Months 0.140679E+12 0.00 441.98 0.110014E+12 0.00 0.00 0.00 0.00 345221.92   167855.29   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 79687.54 0.00 26.16 79687.54 0.00 0.00 0.00 0.00 6.61 01-JAN-10:01 6.61 01-JAN-10:01 0.00 0.00 0.00
February 61724729.79 0.00 42.88 61724729.79 0.00 0.00 0.00 0.00 42371.69 28-FEB-12:01 42371.69 28-FEB-12:01 0.00 0.00 0.00
March 0.470785E+10 0.00 90.42 0.470785E+10 0.00 0.00 0.00 0.00 587690.75 31-MAR-14:01 587690.75 31-MAR-14:01 0.00 0.00 0.00
April 0.550520E+11 0.00 136.55 0.550520E+11 0.00 0.00 0.00 0.00 1247381.17 23-APR-15:42 1247381.17 23-APR-15:42 0.00 0.00 0.00
May 0.438669E+12 0.00 259.64 0.430534E+12 0.00 0.00 0.00 0.00 1513706.04 25-MAY-15:20 1408259.49 18-MAY-14:05 0.00 0.00 0.00
June 0.953687E+12 0.00 378.04 0.772718E+12 0.00 0.00 0.00 0.00 2261485.18 30-JUN-04:01 1629983.59 29-JUN-16:00 0.00 0.00 0.00
July 0.118708E+13 0.00 412.50 0.937635E+12 0.00 0.00 0.00 0.00 2942040.52 05-JUL-10:40 1480876.72 21-JUL-15:30 0.00 0.00 0.00
August 0.937522E+12 0.00 410.10 0.721937E+12 0.00 0.00 0.00 0.00 1955308.36 31-AUG-12:40 1465930.27 08-AUG-15:20 0.00 0.00 0.00
September 0.237851E+12 0.00 202.07 0.215535E+12 0.00 0.00 0.00 0.00 1533265.15 01-SEP-12:05 1396832.20 01-SEP-15:40 0.00 0.00 0.00
October 0.481928E+11 0.00 128.52 0.481928E+11 0.00 0.00 0.00 0.00 865478.87 19-OCT-15:00 865478.87 19-OCT-15:00 0.00 0.00 0.00
November 0.596113E+10 0.00 86.41 0.596113E+10 0.00 0.00 0.00 0.00 493339.80 01-NOV-14:01 493339.80 01-NOV-14:01 0.00 0.00 0.00
December 178120.37 0.00 52.16 178120.37 0.00 0.00 0.00 0.00 5.72 12-DEC-04:11 5.72 12-DEC-04:11 0.00 0.00 0.00
                               
Annual Sum or Average 0.386878E+13 0.00 2225.43 0.319233E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 79687.54 0.00 26.16 79687.54 0.00 0.00 0.00 0.00 5.72   5.72   0.00 0.00 0.00
Maximum of Months 0.118708E+13 0.00 412.50 0.937635E+12 0.00 0.00 0.00 0.00 2942040.52   1629983.59   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 4814712.23 0.00 2.87 4814712.23 0.00 0.00 0.00 0.00 2831.93 24-JAN-06:04 2831.93 24-JAN-06:04 0.00 0.00 0.00
February 7252520.35 0.00 6.67 7252520.35 0.00 0.00 0.00 0.00 6353.30 27-FEB-06:12 6353.30 27-FEB-06:12 0.00 0.00 0.00
March 7324451.20 0.00 4.88 7324451.20 0.00 0.00 0.00 0.00 5454.29 15-MAR-05:12 5454.29 15-MAR-05:12 0.00 0.00 0.00
April 0.485663E+10 0.00 58.29 0.485663E+10 0.00 0.00 0.00 0.00 164348.04 23-APR-15:31 164348.04 23-APR-15:31 0.00 0.00 0.00
May 0.467508E+11 0.00 225.28 0.461067E+11 0.00 0.00 0.00 0.00 181602.21 25-MAY-15:00 172803.29 18-MAY-14:50 0.00 0.00 0.00
June 0.102742E+12 0.00 362.87 0.849439E+11 0.00 0.00 0.00 0.00 335691.33 29-JUN-05:02 198531.29 30-JUN-15:00 0.00 0.00 0.00
July 0.128762E+12 0.00 398.01 0.104887E+12 0.00 0.00 0.00 0.00 278746.12 05-JUL-05:01 190246.12 23-JUL-15:31 0.00 0.00 0.00
August 0.973381E+11 0.00 395.69 0.775754E+11 0.00 0.00 0.00 0.00 216477.12 08-AUG-15:00 179577.67 08-AUG-15:00 0.00 0.00 0.00
September 0.214093E+11 0.00 166.85 0.197024E+11 0.00 0.00 0.00 0.00 169740.45 01-SEP-15:30 163382.33 01-SEP-15:30 0.00 0.00 0.00
October 0.349811E+10 0.00 39.30 0.349811E+10 0.00 0.00 0.00 0.00 78710.99 19-OCT-15:00 78710.99 19-OCT-15:00 0.00 0.00 0.00
November 0.463047E+09 0.00 21.33 0.463047E+09 0.00 0.00 0.00 0.00 25093.39 01-NOV-14:53 25093.39 01-NOV-14:53 0.00 0.00 0.00
December 12223538.73 0.00 8.15 12223538.73 0.00 0.00 0.00 0.00 4197.05 11-DEC-06:12 4197.05 11-DEC-06:12 0.00 0.00 0.00
                               
Annual Sum or Average 0.405851E+12 0.00 1690.19 0.342065E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 4814712.23 0.00 2.87 4814712.23 0.00 0.00 0.00 0.00 2831.93   2831.93   0.00 0.00 0.00
Maximum of Months 0.128762E+12 0.00 398.01 0.104887E+12 0.00 0.00 0.00 0.00 335691.33   198531.29   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 19249109.70 0.00 0.74 19249109.70 0.00 0.00 0.00 0.00 61179.83 31-JAN-06:01 61179.83 31-JAN-06:01 0.00 0.00 0.00
February 0.156135E+09 0.00 3.02 0.156135E+09 0.00 0.00 0.00 0.00 56924.67 24-FEB-06:02 56924.67 24-FEB-06:02 0.00 0.00 0.00
March 0.120275E+10 0.00 22.67 0.120275E+10 0.00 0.00 0.00 0.00 114495.45 27-MAR-04:56 114495.45 27-MAR-04:56 0.00 0.00 0.00
April 0.742352E+10 0.00 111.00 0.742352E+10 0.00 0.00 0.00 0.00 115256.54 03-APR-04:49 115256.54 03-APR-04:49 0.00 0.00 0.00
May 0.320570E+11 0.00 268.30 0.302008E+11 0.00 0.00 0.00 0.00 105668.57 26-MAY-04:11 71948.41 09-MAY-10:32 0.00 0.00 0.00
June 0.605015E+11 0.00 353.37 0.444672E+11 0.00 0.00 0.00 0.00 171815.73 29-JUN-04:52 129788.40 30-JUN-05:02 0.00 0.00 0.00
July 0.765549E+11 0.00 379.83 0.530869E+11 0.00 0.00 0.00 0.00 207444.01 05-JUL-10:25 120252.11 03-JUL-03:25 0.00 0.00 0.00
August 0.704768E+11 0.00 403.75 0.465001E+11 0.00 0.00 0.00 0.00 147905.02 27-AUG-14:31 129966.69 13-AUG-17:50 0.00 0.00 0.00
September 0.265505E+11 0.00 248.97 0.225827E+11 0.00 0.00 0.00 0.00 134277.39 04-SEP-11:58 134277.39 04-SEP-11:58 0.00 0.00 0.00
October 0.117722E+11 0.00 127.27 0.116014E+11 0.00 0.00 0.00 0.00 139903.78 25-OCT-03:25 139903.78 25-OCT-03:25 0.00 0.00 0.00
November 0.440852E+10 0.00 78.59 0.425696E+10 0.00 0.00 0.00 0.00 114346.49 30-NOV-05:49 114346.49 30-NOV-05:49 0.00 0.00 0.00
December 0.121492E+09 0.00 5.63 0.121492E+09 0.00 0.00 0.00 0.00 110640.78 01-DEC-05:50 110640.78 01-DEC-05:50 0.00 0.00 0.00
                               
Annual Sum or Average 0.291245E+12 0.00 2003.16 0.221619E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 19249109.70 0.00 0.74 19249109.70 0.00 0.00 0.00 0.00 56924.67   56924.67   0.00 0.00 0.00
Maximum of Months 0.765549E+11 0.00 403.75 0.530869E+11 0.00 0.00 0.00 0.00 207444.01   139903.78   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 3383165.69 0.00 183.58 3383165.69 0.00 0.00 0.00 0.00 63.72 28-JAN-13:02 63.72 28-JAN-13:02 0.00 0.00 0.00
February 0.158739E+12 0.00 415.12 0.158739E+12 0.00 0.00 0.00 0.00 277305.49 14-FEB-10:01 277305.49 14-FEB-10:01 0.00 0.00 0.00
March 0.222015E+12 0.00 653.48 0.222015E+12 0.00 0.00 0.00 0.00 267717.00 31-MAR-23:17 267717.00 31-MAR-23:17 0.00 0.00 0.00
April 0.223204E+12 0.00 719.72 0.223204E+12 0.00 0.00 0.00 0.00 434430.17 23-APR-15:46 434430.17 23-APR-15:46 0.00 0.00 0.00
May 0.224752E+11 0.00 323.14 0.224752E+11 0.00 0.00 0.00 0.00 219021.98 31-MAY-23:47 219021.98 31-MAY-23:47 0.00 0.00 0.00
June 0.292250E+12 0.00 501.38 0.236831E+12 0.00 0.00 0.00 0.00 564778.66 19-JUN-10:52 344780.65 15-JUN-12:53 0.00 0.00 0.00
July 0.381050E+12 0.00 742.81 0.330387E+12 0.00 0.00 0.00 0.00 569313.14 03-JUL-23:48 300840.35 05-JUL-11:05 0.00 0.00 0.00
August 0.402103E+12 0.00 743.50 0.348310E+12 0.00 0.00 0.00 0.00 596664.11 31-AUG-19:10 410511.41 20-AUG-12:33 0.00 0.00 0.00
September 0.394863E+10 0.00 242.34 0.394863E+10 0.00 0.00 0.00 0.00 242164.60 30-SEP-23:53 242164.60 30-SEP-23:53 0.00 0.00 0.00
October 0.169996E+12 0.00 438.54 0.169706E+12 0.00 0.00 0.00 0.00 319211.33 21-OCT-14:07 319211.33 21-OCT-14:07 0.00 0.00 0.00
November 0.201866E+12 0.00 718.57 0.201426E+12 0.00 0.00 0.00 0.00 326964.90 01-NOV-00:22 326964.90 01-NOV-00:22 0.00 0.00 0.00
December 0.258978E+12 0.00 744.00 0.258978E+12 0.00 0.00 0.00 0.00 262395.00 25-DEC-08:00 262395.00 25-DEC-08:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.233663E+13 0.00 6426.19 0.217602E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 3383165.69 0.00 183.58 3383165.69 0.00 0.00 0.00 0.00 63.72   63.72   0.00 0.00 0.00
Maximum of Months 0.402103E+12 0.00 744.00 0.348310E+12 0.00 0.00 0.00 0.00 596664.11   434430.17   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.297686E+10 0.939306E+09 600.44 0.297686E+10 -0.0 0.00 1.00 07-JAN-00:01 0.00 01-JAN-00:55 8839.70 14-JAN-04:21 8839.70 14-JAN-04:21 0.00 26-JAN-16:37 2291.12 14-JAN-04:21 0.00 01-JAN-00:01
February 0.815117E+10 0.235474E+10 627.50 0.815117E+10 -0.0 0.00 1.00 02-FEB-08:61 0.00 01-FEB-18:51 13831.56 15-FEB-05:31 13831.56 15-FEB-05:31 0.00 02-FEB-08:61 3713.92 14-FEB-10:01 0.00 01-FEB-00:01
March 0.155617E+11 0.413150E+10 733.00 0.155617E+11 -0.0 0.00 1.00 05-MAR-08:21 0.00 05-MAR-02:21 14361.92 05-MAR-08:21 14361.92 05-MAR-08:21 0.00 27-MAR-18:04 3872.87 05-MAR-08:21 0.00 01-MAR-00:01
April 0.213917E+11 0.552513E+10 720.00 0.213917E+11 -0.0 0.00 1.00 01-APR-00:03 0.48 30-APR-24:00 10446.70 23-APR-18:12 10446.70 23-APR-18:12 0.00 15-APR-08:51 2981.99 23-APR-18:05 0.00 01-APR-00:03
May 0.799389E+10 0.240760E+10 744.00 0.796483E+10 29061935.37 0.00 0.69 14-MAY-18:41 0.33 13-MAY-06:30 4563.23 31-MAY-23:51 4563.23 31-MAY-23:51 235.84 26-MAY-13:05 1413.91 25-MAY-18:40 0.00 01-MAY-00:10
June 0.129604E+11 0.366220E+10 720.00 0.127937E+11 0.166700E+09 0.00 0.92 30-JUN-23:01 0.63 10-JUN-06:11 6782.81 30-JUN-23:01 6771.86 30-JUN-23:02 472.63 30-JUN-16:00 2083.97 29-JUN-16:00 0.00 01-JUN-00:01
July 0.188705E+11 0.499322E+10 744.00 0.186351E+11 0.235467E+09 0.00 1.00 01-JUL-18:10 0.86 08-JUL-16:51 8708.06 31-JUL-24:00 8654.48 31-JUL-24:00 495.81 05-JUL-11:00 2378.03 21-JUL-16:00 0.00 01-JUL-00:01
August 0.237184E+11 0.621847E+10 744.00 0.234656E+11 0.252779E+09 0.00 1.00 01-AUG-00:10 0.51 31-AUG-24:00 10090.44 25-AUG-18:20 10086.36 05-AUG-18:37 418.10 08-AUG-15:30 3069.62 08-AUG-16:00 0.00 01-AUG-00:10
September 0.742465E+10 0.223487E+10 720.00 0.738802E+10 36632472.39 0.00 0.69 09-SEP-17:53 0.32 23-SEP-06:55 4640.80 03-SEP-17:52 4637.36 03-SEP-18:00 229.92 18-SEP-16:00 1306.21 03-SEP-17:52 0.00 01-SEP-00:02
October 0.116344E+11 0.330118E+10 744.00 0.116323E+11 2019335.09 0.00 0.86 31-OCT-23:57 0.50 30-OCT-06:02 5948.54 31-OCT-23:52 5948.54 31-OCT-23:52 64.82 02-OCT-14:02 1585.13 19-OCT-16:44 0.00 01-OCT-00:01
November 0.153998E+11 0.408795E+10 720.00 0.153953E+11 4433217.30 0.00 1.00 09-NOV-15:51 0.72 25-NOV-07:01 7243.11 09-NOV-16:02 7243.11 09-NOV-16:02 172.20 21-NOV-12:00 1841.11 17-NOV-16:00 0.00 01-NOV-00:01
December 0.172946E+11 0.441767E+10 650.50 0.172946E+11 -0.0 0.00 1.00 01-DEC-00:01 0.00 02-DEC-01:41 14838.87 20-DEC-11:01 14838.87 20-DEC-11:01 0.00 29-DEC-13:32 3987.56 20-DEC-11:01 0.00 01-DEC-00:01
                                         
Annual Sum or Average 0.163378E+12 0.442738E+11 8467.44 0.162651E+12 0.727092E+09 0.00                            
Minimum of Months 0.297686E+10 0.939306E+09 600.44 0.297686E+10 -0.0 0.00 0.69   0.00   4563.23   4563.23   0.00   1306.21   0.00  
Maximum of Months 0.237184E+11 0.621847E+10 744.00 0.234656E+11 0.252779E+09 0.00 1.00   0.86   14838.87   14838.87   495.81   3987.56   0.00  



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.127309E+11 0.350585E+10 467.67 0.127309E+11 -0.0 0.00 0.68 06-JAN-12:42 0.00 01-JAN-00:01 42699.05 06-JAN-12:42 42699.05 06-JAN-12:42 0.00 27-JAN-16:10 10275.42 06-JAN-12:42 0.00 01-JAN-00:01
February 0.626017E+11 0.159072E+11 627.50 0.626017E+11 -0.0 0.00 1.00 02-FEB-08:61 0.00 01-FEB-18:51 131398.12 17-FEB-09:21 131398.12 17-FEB-09:21 0.00 14-FEB-10:02 30225.92 17-FEB-09:21 0.00 01-FEB-00:01
March 0.135406E+12 0.314302E+11 733.00 0.135406E+12 -0.0 0.00 1.00 05-MAR-08:21 0.00 05-MAR-02:21 136134.98 16-MAR-04:41 136134.98 16-MAR-04:41 0.00 28-MAR-18:16 31438.74 05-MAR-08:21 0.00 01-MAR-00:01
April 0.194487E+12 0.428693E+11 720.00 0.194487E+12 -0.0 0.00 1.00 01-APR-00:03 0.36 30-APR-24:00 99360.65 23-APR-18:01 99360.65 23-APR-18:01 0.00 17-APR-08:24 24366.82 23-APR-17:59 0.00 01-APR-00:03
May 0.709772E+11 0.184799E+11 744.00 0.706885E+11 0.288664E+09 0.00 0.69 25-MAY-18:50 0.20 01-MAY-06:05 44815.98 25-MAY-18:50 43563.50 25-MAY-18:50 2343.49 26-MAY-13:05 11911.38 25-MAY-18:40 0.00 01-MAY-00:10
June 0.120915E+12 0.294600E+11 720.00 0.119255E+12 0.166005E+10 0.00 0.93 30-JUN-23:11 0.59 10-JUN-06:01 66190.55 30-JUN-23:11 66129.49 30-JUN-23:30 4719.08 30-JUN-16:00 17163.22 29-JUN-16:00 0.00 01-JUN-00:01
July 0.177837E+12 0.405377E+11 744.00 0.175492E+12 0.234575E+10 0.00 1.00 01-JUL-18:11 0.82 08-JUL-16:51 82437.91 31-JUL-24:00 81970.89 31-JUL-24:00 4890.54 05-JUL-11:05 19511.20 21-JUL-16:00 0.00 01-JUL-00:01
August 0.222468E+12 0.498419E+11 744.00 0.219958E+12 0.250956E+10 0.00 1.00 01-AUG-00:10 0.45 31-AUG-24:00 97320.42 25-AUG-18:20 96982.73 02-AUG-18:40 4181.68 08-AUG-15:30 25050.75 08-AUG-16:00 0.00 01-AUG-00:10
September 0.631021E+11 0.164847E+11 720.00 0.627402E+11 0.361918E+09 0.00 0.68 05-SEP-17:50 0.26 23-SEP-06:55 44018.27 05-SEP-17:42 44018.27 05-SEP-17:42 2271.38 18-SEP-16:00 10654.29 05-SEP-17:42 0.00 01-SEP-00:02
October 0.998551E+11 0.247067E+11 744.00 0.998349E+11 20134204.68 0.00 0.83 18-OCT-16:50 0.37 30-OCT-06:02 56574.07 19-OCT-16:42 56574.07 19-OCT-16:42 641.68 02-OCT-14:02 13063.04 19-OCT-16:46 0.00 01-OCT-00:01
November 0.127713E+12 0.299143E+11 720.00 0.127668E+12 44353476.18 0.00 0.98 09-NOV-16:20 0.55 27-NOV-04:03 67408.35 17-NOV-16:03 67408.35 17-NOV-16:03 1706.95 21-NOV-12:00 14837.09 17-NOV-16:10 0.00 01-NOV-00:01
December 0.147129E+12 0.327502E+11 650.50 0.147129E+12 -0.0 0.00 1.00 01-DEC-12:53 0.00 02-DEC-01:41 141692.18 20-DEC-11:01 141692.18 20-DEC-11:01 0.00 06-DEC-12:33 32686.90 20-DEC-11:01 0.00 01-DEC-00:01
                                         
Annual Sum or Average 0.143522E+13 0.335888E+12 8334.67 0.142799E+13 0.723044E+10 0.00                            
Minimum of Months 0.127309E+11 0.350585E+10 467.67 0.127309E+11 -0.0 0.00 0.68   0.00   42699.05   42699.05   0.00   10275.42   0.00  
Maximum of Months 0.222468E+12 0.498419E+11 744.00 0.219958E+12 0.250956E+10 0.00 1.00   0.82   141692.18   141692.18   4890.54   32686.90   0.00  



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.551483E+09 0.178148E+09 229.68 0.551483E+09 -0.0 0.00 0.39 20-JAN-16:25 0.00 01-JAN-00:01 2287.93 20-JAN-16:25 2287.93 20-JAN-16:25 0.00 20-JAN-16:30 699.05 20-JAN-16:30 0.00 01-JAN-00:01
February 0.441808E+10 0.134133E+10 625.23 0.441808E+10 -0.0 0.00 1.00 02-FEB-08:61 0.00 01-FEB-00:01 13239.78 14-FEB-10:01 13239.78 14-FEB-10:01 0.00 06-FEB-16:44 3549.49 14-FEB-10:01 0.00 01-FEB-00:01
March 0.113937E+11 0.318527E+10 732.98 0.113937E+11 -0.0 0.00 1.00 05-MAR-08:21 0.00 05-MAR-02:21 13617.15 16-MAR-04:41 13617.15 16-MAR-04:41 0.00 28-MAR-17:49 3652.17 16-MAR-04:41 0.00 01-MAR-00:01
April 0.176721E+11 0.459914E+10 720.00 0.176721E+11 -0.0 0.00 1.00 04-APR-12:32 0.15 30-APR-24:00 9808.42 23-APR-18:01 9808.42 23-APR-18:01 0.00 25-APR-14:40 2806.06 23-APR-17:52 0.00 01-APR-00:03
May 0.622485E+10 0.191081E+10 743.05 0.619597E+10 28886356.12 0.00 0.70 25-MAY-18:40 0.00 01-MAY-06:05 4653.45 25-MAY-18:50 4528.84 25-MAY-18:50 236.59 26-MAY-13:05 1442.30 25-MAY-18:40 0.00 01-MAY-00:10
June 0.116331E+11 0.334067E+10 720.00 0.114672E+11 0.165948E+09 0.00 0.91 30-JUN-23:01 0.40 04-JUN-05:30 6575.11 30-JUN-23:01 6563.94 30-JUN-23:02 473.57 30-JUN-16:00 2075.23 29-JUN-16:00 0.00 01-JUN-00:01
July 0.174697E+11 0.469156E+10 744.00 0.172352E+11 0.234481E+09 0.00 1.00 01-JUL-18:35 0.72 10-JUL-06:10 8186.79 28-JUL-18:50 7991.61 31-JUL-23:50 489.42 05-JUL-11:05 2345.23 21-JUL-16:00 0.00 01-JUL-00:01
August 0.217737E+11 0.566940E+10 744.00 0.215249E+11 0.248804E+09 0.00 1.00 01-AUG-00:10 0.41 31-AUG-24:00 9881.25 25-AUG-18:20 9794.04 02-AUG-18:40 418.88 08-AUG-15:30 2995.90 08-AUG-16:00 0.00 01-AUG-00:10
September 0.513994E+10 0.159025E+10 719.08 0.510419E+10 35749667.69 0.00 0.66 05-SEP-17:50 0.00 11-SEP-03:33 4409.70 05-SEP-17:42 4409.70 05-SEP-17:42 229.68 18-SEP-16:00 1255.83 01-SEP-17:30 0.00 01-SEP-00:02
October 0.778680E+10 0.231359E+10 743.72 0.778484E+10 1968869.08 0.00 0.81 19-OCT-16:44 0.00 15-OCT-06:31 5709.40 19-OCT-16:42 5709.40 19-OCT-16:42 63.32 02-OCT-14:02 1543.49 19-OCT-16:45 0.00 01-OCT-00:01
November 0.104566E+11 0.295788E+10 720.00 0.104522E+11 4382657.40 0.00 0.93 17-NOV-16:01 0.37 24-NOV-03:33 6505.99 17-NOV-16:03 6505.99 17-NOV-16:03 169.43 21-NOV-12:00 1695.44 17-NOV-16:10 0.00 01-NOV-00:01
December 0.128602E+11 0.344542E+10 650.50 0.128602E+11 -0.0 0.00 1.00 02-DEC-09:31 0.00 02-DEC-01:41 14372.78 20-DEC-11:01 14372.78 20-DEC-11:01 0.00 26-DEC-09:54 3872.88 20-DEC-11:01 0.00 01-DEC-00:01
                                         
Annual Sum or Average 0.127380E+12 0.352235E+11 8092.24 0.126660E+12 0.720221E+09 0.00                            
Minimum of Months 0.551483E+09 0.178148E+09 229.68 0.551483E+09 -0.0 0.00 0.39   0.00   2287.93   2287.93   0.00   699.05   0.00  
Maximum of Months 0.217737E+11 0.566940E+10 744.00 0.215249E+11 0.248804E+09 0.00 1.00   0.72   14372.78   14372.78   489.42   3872.88   0.00  



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 152.94 0.00 152.94 0.01 1895.06 0.00 0.00 0.00
February 234.93 0.00 234.93 3.18 1556.58 0.00 0.00 0.00
March 289.04 0.00 289.04 10.76 1250.41 0.00 0.00 0.00
April 378.91 2.96 375.95 93.57 766.79 0.00 0.00 0.00
May 532.92 28.70 504.23 373.18 371.65 0.00 0.00 0.00
June 594.75 65.38 529.37 558.15 255.52 0.00 0.00 0.00
July 568.08 48.75 519.33 572.59 233.33 0.00 0.00 0.00
August 431.48 7.41 424.07 375.14 286.19 0.00 0.00 0.00
September 336.24 0.08 336.15 183.99 466.30 0.00 0.00 0.00
October 233.47 0.00 233.47 33.77 764.41 0.00 0.00 0.00
November 154.58 0.00 154.58 4.27 1196.50 0.00 0.00 0.00
December 129.58 0.00 129.58 0.00 1832.52 0.00 0.00 0.00
                 
Annual Sum or Average 336.92 12.83 324.09 185.25 903.50 0.00 0.00 0.00
Minimum of Months 129.58 0.00 129.58 0.00 233.33 0.00 0.00 0.00
Maximum of Months 594.75 65.38 529.37 572.59 1895.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 152.94 0.00 152.94 0.01 1895.06 0.00 0.00 0.00
February 234.93 0.00 234.93 3.18 1556.58 0.00 0.00 0.00
March 289.04 0.00 289.04 10.76 1250.41 0.00 0.00 0.00
April 378.91 2.96 375.95 93.57 766.79 0.00 0.00 0.00
May 532.92 28.70 504.23 373.18 371.65 0.00 0.00 0.00
June 594.75 65.38 529.37 558.14 255.52 0.00 0.00 0.00
July 568.08 48.75 519.33 572.59 233.33 0.00 0.00 0.00
August 431.47 7.41 424.07 375.14 286.19 0.00 0.00 0.00
September 336.24 0.08 336.15 183.99 466.30 0.00 0.00 0.00
October 233.46 0.00 233.46 33.77 764.41 0.00 0.00 0.00
November 154.58 0.00 154.58 4.27 1196.50 0.00 0.00 0.00
December 129.58 0.00 129.58 0.00 1832.52 0.00 0.00 0.00
                 
Annual Sum or Average 336.92 12.83 324.09 185.25 903.50 0.00 0.00 0.00
Minimum of Months 129.58 0.00 129.58 0.00 233.33 0.00 0.00 0.00
Maximum of Months 594.75 65.38 529.37 572.59 1895.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 152.94 0.00 152.94 0.01 1895.06 0.00 0.00 0.00
February 234.93 0.00 234.93 3.18 1556.58 0.00 0.00 0.00
March 289.04 0.00 289.04 10.76 1250.41 0.00 0.00 0.00
April 378.91 2.96 375.95 93.57 766.79 0.00 0.00 0.00
May 532.92 28.70 504.23 373.18 371.65 0.00 0.00 0.00
June 594.75 65.38 529.37 558.15 255.52 0.00 0.00 0.00
July 568.08 48.75 519.33 572.59 233.33 0.00 0.00 0.00
August 431.48 7.41 424.07 375.14 286.19 0.00 0.00 0.00
September 336.24 0.08 336.15 183.99 466.30 0.00 0.00 0.00
October 233.47 0.00 233.47 33.77 764.41 0.00 0.00 0.00
November 154.58 0.00 154.58 4.27 1196.50 0.00 0.00 0.00
December 129.58 0.00 129.58 0.00 1832.52 0.00 0.00 0.00
                 
Annual Sum or Average 336.92 12.83 324.09 185.25 903.50 0.00 0.00 0.00
Minimum of Months 129.58 0.00 129.58 0.00 233.33 0.00 0.00 0.00
Maximum of Months 594.75 65.38 529.37 572.59 1895.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 152.94 0.00 152.94 0.01 1895.06 0.00 0.00 0.00
February 234.93 0.00 234.93 3.18 1556.58 0.00 0.00 0.00
March 289.04 0.00 289.04 10.76 1250.41 0.00 0.00 0.00
April 378.91 2.96 375.95 93.57 766.79 0.00 0.00 0.00
May 532.92 28.70 504.23 373.18 371.65 0.00 0.00 0.00
June 594.75 65.38 529.37 558.14 255.52 0.00 0.00 0.00
July 568.08 48.75 519.33 572.59 233.33 0.00 0.00 0.00
August 431.47 7.41 424.07 375.14 286.19 0.00 0.00 0.00
September 336.24 0.08 336.15 183.99 466.30 0.00 0.00 0.00
October 233.46 0.00 233.46 33.77 764.41 0.00 0.00 0.00
November 154.58 0.00 154.58 4.27 1196.50 0.00 0.00 0.00
December 129.58 0.00 129.58 0.00 1832.52 0.00 0.00 0.00
                 
Annual Sum or Average 336.92 12.83 324.09 185.25 903.50 0.00 0.00 0.00
Minimum of Months 129.58 0.00 129.58 0.00 233.33 0.00 0.00 0.00
Maximum of Months 594.75 65.38 529.37 572.59 1895.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 152.93 0.00 152.93 0.01 1894.98 0.00 0.00 0.00
February 234.92 0.00 234.92 3.18 1556.52 0.00 0.00 0.00
March 289.03 0.00 289.03 10.76 1250.36 0.00 0.00 0.00
April 378.90 2.96 375.94 93.56 766.75 0.00 0.00 0.00
May 532.90 28.70 504.21 373.17 371.63 0.00 0.00 0.00
June 594.73 65.38 529.35 558.12 255.51 0.00 0.00 0.00
July 568.06 48.75 519.31 572.57 233.32 0.00 0.00 0.00
August 431.46 7.41 424.05 375.12 286.18 0.00 0.00 0.00
September 336.22 0.08 336.14 183.98 466.28 0.00 0.00 0.00
October 233.46 0.00 233.46 33.77 764.38 0.00 0.00 0.00
November 154.58 0.00 154.58 4.27 1196.45 0.00 0.00 0.00
December 129.58 0.00 129.58 0.00 1832.45 0.00 0.00 0.00
                 
Annual Sum or Average 336.90 12.83 324.07 185.24 903.47 0.00 0.00 0.00
Minimum of Months 129.58 0.00 129.58 0.00 233.32 0.00 0.00 0.00
Maximum of Months 594.73 65.38 529.35 572.57 1894.98 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 372.56 155.52 217.04 81.12 1895.28 0.00 0.00 0.00
February 585.45 249.73 335.72 239.86 1525.84 0.00 0.00 0.00
March 797.71 400.14 397.57 471.70 1233.38 0.00 0.00 0.00
April 1105.86 596.48 509.38 889.41 755.42 0.00 0.00 0.00
May 1196.87 526.16 670.71 1162.04 398.35 0.00 0.00 0.00
June 1354.94 648.14 706.79 1494.60 279.87 0.00 0.00 0.00
July 1327.34 623.23 704.10 1523.39 246.97 0.00 0.00 0.00
August 1023.38 447.29 576.09 1108.73 292.28 0.00 0.00 0.00
September 819.56 366.83 452.73 746.95 473.12 0.00 0.00 0.00
October 496.26 188.18 308.08 289.70 776.52 0.00 0.00 0.00
November 315.92 105.62 210.30 102.11 1208.81 0.00 0.00 0.00
December 288.27 106.55 181.72 49.52 1857.76 0.00 0.00 0.00
                 
Annual Sum or Average 807.82 368.12 439.70 682.14 909.47 0.00 0.00 0.00
Minimum of Months 288.27 105.62 181.72 49.52 246.97 0.00 0.00 0.00
Maximum of Months 1354.94 648.14 706.79 1523.39 1895.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 372.56 155.52 217.04 81.12 1895.28 0.00 0.00 0.00
February 585.45 249.73 335.72 239.86 1525.84 0.00 0.00 0.00
March 797.71 400.14 397.57 471.70 1233.38 0.00 0.00 0.00
April 1105.86 596.48 509.38 889.41 755.42 0.00 0.00 0.00
May 1196.87 526.16 670.71 1162.04 398.35 0.00 0.00 0.00
June 1354.94 648.14 706.79 1494.60 279.87 0.00 0.00 0.00
July 1327.34 623.23 704.10 1523.39 246.97 0.00 0.00 0.00
August 1023.38 447.29 576.09 1108.73 292.28 0.00 0.00 0.00
September 819.56 366.83 452.73 746.95 473.12 0.00 0.00 0.00
October 496.26 188.18 308.08 289.70 776.52 0.00 0.00 0.00
November 315.92 105.62 210.30 102.11 1208.81 0.00 0.00 0.00
December 288.27 106.55 181.72 49.52 1857.76 0.00 0.00 0.00
                 
Annual Sum or Average 807.82 368.12 439.70 682.14 909.47 0.00 0.00 0.00
Minimum of Months 288.27 105.62 181.72 49.52 246.97 0.00 0.00 0.00
Maximum of Months 1354.94 648.14 706.79 1523.39 1895.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 372.56 155.52 217.04 81.12 1895.24 0.00 0.00 0.00
February 585.44 249.72 335.72 239.86 1525.82 0.00 0.00 0.00
March 797.70 400.14 397.56 471.69 1233.36 0.00 0.00 0.00
April 1105.84 596.47 509.37 889.39 755.40 0.00 0.00 0.00
May 1196.84 526.15 670.70 1162.02 398.34 0.00 0.00 0.00
June 1354.91 648.13 706.78 1494.58 279.86 0.00 0.00 0.00
July 1327.31 623.22 704.09 1523.36 246.96 0.00 0.00 0.00
August 1023.36 447.28 576.08 1108.71 292.27 0.00 0.00 0.00
September 819.54 366.82 452.72 746.94 473.11 0.00 0.00 0.00
October 496.25 188.18 308.07 289.69 776.50 0.00 0.00 0.00
November 315.91 105.62 210.30 102.11 1208.79 0.00 0.00 0.00
December 288.27 106.55 181.72 49.52 1857.73 0.00 0.00 0.00
                 
Annual Sum or Average 807.81 368.11 439.69 682.13 909.45 0.00 0.00 0.00
Minimum of Months 288.27 105.62 181.72 49.52 246.96 0.00 0.00 0.00
Maximum of Months 1354.91 648.13 706.78 1523.36 1895.24 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1053.15 732.66 320.50 700.75 1476.49 0.00 0.00 0.00
February 1333.55 900.72 432.82 1052.25 1247.01 0.00 0.00 0.00
March 1175.02 743.62 431.39 961.54 1061.32 0.00 0.00 0.00
April 1064.53 577.80 486.73 978.76 717.47 0.00 0.00 0.00
May 894.99 305.97 589.01 922.49 394.98 0.00 0.00 0.00
June 803.05 214.05 589.00 905.77 272.13 0.00 0.00 0.00
July 878.00 278.15 599.85 1048.85 246.17 0.00 0.00 0.00
August 937.65 392.21 545.44 1076.50 290.56 0.00 0.00 0.00
September 1004.37 534.90 469.47 1044.86 448.60 0.00 0.00 0.00
October 857.66 504.43 353.23 753.80 677.59 0.00 0.00 0.00
November 763.98 479.48 284.51 563.61 981.99 0.00 0.00 0.00
December 813.16 533.20 279.96 487.39 1458.06 0.00 0.00 0.00
                 
Annual Sum or Average 962.51 513.98 448.52 873.27 770.64 0.00 0.00 0.00
Minimum of Months 763.98 214.05 279.96 487.39 246.17 0.00 0.00 0.00
Maximum of Months 1333.55 900.72 599.85 1076.50 1476.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1053.15 732.65 320.50 700.75 1476.49 0.00 0.00 0.00
February 1333.54 900.72 432.82 1052.25 1247.01 0.00 0.00 0.00
March 1175.01 743.62 431.39 961.54 1061.32 0.00 0.00 0.00
April 1064.53 577.79 486.73 978.75 717.47 0.00 0.00 0.00
May 894.99 305.97 589.01 922.49 394.98 0.00 0.00 0.00
June 803.05 214.05 589.00 905.76 272.13 0.00 0.00 0.00
July 878.00 278.15 599.85 1048.85 246.17 0.00 0.00 0.00
August 937.65 392.21 545.44 1076.50 290.56 0.00 0.00 0.00
September 1004.36 534.90 469.47 1044.86 448.60 0.00 0.00 0.00
October 857.66 504.43 353.23 753.80 677.59 0.00 0.00 0.00
November 763.98 479.48 284.51 563.61 981.99 0.00 0.00 0.00
December 813.16 533.20 279.96 487.39 1458.06 0.00 0.00 0.00
                 
Annual Sum or Average 962.51 513.98 448.52 873.27 770.64 0.00 0.00 0.00
Minimum of Months 763.98 214.05 279.96 487.39 246.17 0.00 0.00 0.00
Maximum of Months 1333.54 900.72 599.85 1076.50 1476.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1053.15 732.66 320.50 700.75 1476.49 0.00 0.00 0.00
February 1333.55 900.72 432.82 1052.25 1247.01 0.00 0.00 0.00
March 1175.02 743.62 431.39 961.54 1061.32 0.00 0.00 0.00
April 1064.53 577.80 486.73 978.76 717.47 0.00 0.00 0.00
May 894.99 305.97 589.01 922.49 394.98 0.00 0.00 0.00
June 803.05 214.05 589.00 905.77 272.13 0.00 0.00 0.00
July 878.00 278.15 599.85 1048.85 246.17 0.00 0.00 0.00
August 937.65 392.21 545.44 1076.50 290.56 0.00 0.00 0.00
September 1004.37 534.90 469.47 1044.86 448.60 0.00 0.00 0.00
October 857.66 504.43 353.23 753.80 677.59 0.00 0.00 0.00
November 763.98 479.48 284.51 563.61 981.99 0.00 0.00 0.00
December 813.16 533.20 279.96 487.39 1458.06 0.00 0.00 0.00
                 
Annual Sum or Average 962.51 513.98 448.52 873.27 770.64 0.00 0.00 0.00
Minimum of Months 763.98 214.05 279.96 487.39 246.17 0.00 0.00 0.00
Maximum of Months 1333.55 900.72 599.85 1076.50 1476.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1053.15 732.65 320.50 700.75 1476.49 0.00 0.00 0.00
February 1333.54 900.72 432.82 1052.25 1247.01 0.00 0.00 0.00
March 1175.01 743.62 431.39 961.54 1061.32 0.00 0.00 0.00
April 1064.53 577.79 486.73 978.75 717.47 0.00 0.00 0.00
May 894.99 305.97 589.01 922.49 394.98 0.00 0.00 0.00
June 803.05 214.05 589.00 905.76 272.13 0.00 0.00 0.00
July 878.00 278.15 599.85 1048.85 246.17 0.00 0.00 0.00
August 937.65 392.21 545.44 1076.50 290.56 0.00 0.00 0.00
September 1004.36 534.90 469.47 1044.86 448.60 0.00 0.00 0.00
October 857.66 504.43 353.23 753.80 677.59 0.00 0.00 0.00
November 763.98 479.48 284.51 563.61 981.99 0.00 0.00 0.00
December 813.16 533.20 279.96 487.39 1458.06 0.00 0.00 0.00
                 
Annual Sum or Average 962.51 513.98 448.52 873.27 770.64 0.00 0.00 0.00
Minimum of Months 763.98 214.05 279.96 487.39 246.17 0.00 0.00 0.00
Maximum of Months 1333.54 900.72 599.85 1076.50 1476.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1053.11 732.63 320.49 700.72 1476.43 0.00 0.00 0.00
February 1333.49 900.69 432.81 1052.21 1246.96 0.00 0.00 0.00
March 1174.97 743.59 431.38 961.50 1061.28 0.00 0.00 0.00
April 1064.48 577.77 486.71 978.72 717.44 0.00 0.00 0.00
May 894.95 305.96 588.99 922.45 394.96 0.00 0.00 0.00
June 803.02 214.04 588.98 905.73 272.12 0.00 0.00 0.00
July 877.96 278.13 599.83 1048.80 246.16 0.00 0.00 0.00
August 937.61 392.20 545.42 1076.46 290.55 0.00 0.00 0.00
September 1004.33 534.88 469.45 1044.82 448.58 0.00 0.00 0.00
October 857.62 504.41 353.21 753.77 677.56 0.00 0.00 0.00
November 763.95 479.46 284.50 563.59 981.95 0.00 0.00 0.00
December 813.13 533.18 279.95 487.37 1458.00 0.00 0.00 0.00
                 
Annual Sum or Average 962.47 513.96 448.51 873.24 770.60 0.00 0.00 0.00
Minimum of Months 763.95 214.04 279.95 487.37 246.16 0.00 0.00 0.00
Maximum of Months 1333.49 900.69 599.83 1076.46 1476.43 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 376.55 157.68 218.87 96.27 2005.73 0.00 0.00 0.00
February 613.51 280.21 333.30 295.64 1656.31 0.00 0.00 0.00
March 807.33 413.11 394.23 506.61 1352.72 0.00 0.00 0.00
April 1031.33 522.36 508.97 811.66 887.66 0.00 0.00 0.00
May 1267.17 604.44 662.72 1279.51 467.89 0.00 0.00 0.00
June 1222.79 528.72 694.06 1333.93 334.21 0.00 0.00 0.00
July 1305.44 606.90 698.55 1478.68 321.39 0.00 0.00 0.00
August 1074.29 488.15 586.14 1157.13 382.62 0.00 0.00 0.00
September 839.60 377.22 462.38 776.08 538.67 0.00 0.00 0.00
October 530.38 212.92 317.46 340.04 851.40 0.00 0.00 0.00
November 322.13 108.61 213.52 104.34 1312.44 0.00 0.00 0.00
December 287.16 100.51 186.65 46.83 2008.22 0.00 0.00 0.00
                 
Annual Sum or Average 807.54 367.26 440.28 687.99 1007.28 0.00 0.00 0.00
Minimum of Months 287.16 100.51 186.65 46.83 321.39 0.00 0.00 0.00
Maximum of Months 1305.44 606.90 698.55 1478.68 2008.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 376.55 157.68 218.87 96.27 2005.73 0.00 0.00 0.00
February 613.51 280.21 333.30 295.64 1656.31 0.00 0.00 0.00
March 807.33 413.11 394.23 506.61 1352.72 0.00 0.00 0.00
April 1031.33 522.36 508.97 811.66 887.66 0.00 0.00 0.00
May 1267.17 604.44 662.72 1279.51 467.89 0.00 0.00 0.00
June 1222.79 528.72 694.06 1333.93 334.21 0.00 0.00 0.00
July 1305.44 606.90 698.55 1478.68 321.39 0.00 0.00 0.00
August 1074.29 488.15 586.14 1157.13 382.62 0.00 0.00 0.00
September 839.60 377.22 462.38 776.08 538.67 0.00 0.00 0.00
October 530.38 212.92 317.46 340.04 851.40 0.00 0.00 0.00
November 322.13 108.61 213.52 104.34 1312.44 0.00 0.00 0.00
December 287.16 100.51 186.65 46.83 2008.22 0.00 0.00 0.00
                 
Annual Sum or Average 807.54 367.26 440.28 687.99 1007.28 0.00 0.00 0.00
Minimum of Months 287.16 100.51 186.65 46.83 321.39 0.00 0.00 0.00
Maximum of Months 1305.44 606.90 698.55 1478.68 2008.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 376.54 157.67 218.87 96.27 2005.70 0.00 0.00 0.00
February 613.50 280.21 333.29 295.63 1656.28 0.00 0.00 0.00
March 807.32 413.10 394.22 506.61 1352.70 0.00 0.00 0.00
April 1031.31 522.35 508.96 811.64 887.65 0.00 0.00 0.00
May 1267.14 604.43 662.71 1279.49 467.89 0.00 0.00 0.00
June 1222.77 528.71 694.05 1333.91 334.20 0.00 0.00 0.00
July 1305.42 606.89 698.54 1478.66 321.38 0.00 0.00 0.00
August 1074.27 488.14 586.13 1157.11 382.61 0.00 0.00 0.00
September 839.59 377.21 462.37 776.07 538.66 0.00 0.00 0.00
October 530.37 212.91 317.46 340.03 851.39 0.00 0.00 0.00
November 322.12 108.61 213.51 104.34 1312.42 0.00 0.00 0.00
December 287.15 100.51 186.65 46.83 2008.18 0.00 0.00 0.00
                 
Annual Sum or Average 807.52 367.25 440.28 687.98 1007.26 0.00 0.00 0.00
Minimum of Months 287.15 100.51 186.65 46.83 321.38 0.00 0.00 0.00
Maximum of Months 1305.42 606.89 698.54 1478.66 2008.18 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 764.69 0.00 764.69 1.09 9360.78 0.00 0.00 0.00
February 1174.62 0.00 1174.62 29.50 7596.47 0.00 0.00 0.00
March 1445.17 0.00 1445.17 75.36 6009.84 0.00 0.00 0.00
April 1894.53 14.79 1879.74 551.59 3516.08 0.00 0.00 0.00
May 2664.58 143.48 2521.10 1946.81 1739.29 0.00 0.00 0.00
June 2973.72 326.89 2646.83 2866.50 1188.43 0.00 0.00 0.00
July 2840.37 243.76 2596.61 2937.03 1089.47 0.00 0.00 0.00
August 2157.35 37.05 2120.30 1985.30 1262.92 0.00 0.00 0.00
September 1681.16 0.41 1680.75 1017.20 2124.74 0.00 0.00 0.00
October 1167.31 0.00 1167.31 225.96 3482.95 0.00 0.00 0.00
November 772.91 0.00 772.91 28.65 5528.31 0.00 0.00 0.00
December 647.91 0.00 647.91 0.00 8941.28 0.00 0.00 0.00
                 
Annual Sum or Average 1684.57 64.15 1620.42 978.25 4306.60 0.00 0.00 0.00
Minimum of Months 647.91 0.00 647.91 0.00 1089.47 0.00 0.00 0.00
Maximum of Months 2973.72 326.89 2646.83 2937.03 9360.78 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1117.68 466.55 651.12 242.37 5597.64 0.00 0.00 0.00
February 1756.33 749.17 1007.16 727.46 4477.71 0.00 0.00 0.00
March 2393.11 1200.42 1192.69 1410.79 3607.82 0.00 0.00 0.00
April 3317.55 1789.42 1528.13 2648.94 2160.37 0.00 0.00 0.00
May 3590.56 1578.45 2012.11 3443.13 1156.44 0.00 0.00 0.00
June 4064.76 1944.40 2120.36 4441.23 807.27 0.00 0.00 0.00
July 3981.97 1869.68 2112.29 4533.66 725.98 0.00 0.00 0.00
August 3070.11 1341.85 1728.26 3302.21 837.42 0.00 0.00 0.00
September 2458.64 1100.48 1358.17 2223.16 1353.45 0.00 0.00 0.00
October 1488.75 564.53 924.22 872.33 2192.76 0.00 0.00 0.00
November 947.75 316.85 630.90 313.75 3393.66 0.00 0.00 0.00
December 864.81 319.65 545.16 149.93 5433.79 0.00 0.00 0.00
                 
Annual Sum or Average 2423.44 1104.35 1319.09 2032.24 2638.15 0.00 0.00 0.00
Minimum of Months 864.81 316.85 545.16 149.93 725.98 0.00 0.00 0.00
Maximum of Months 4064.76 1944.40 2120.36 4533.66 5597.64 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 5265.71 3663.24 1602.47 3459.82 7405.11 0.00 0.00 0.00
February 6667.65 4503.56 2164.09 5184.39 6232.65 0.00 0.00 0.00
March 5875.01 3718.06 2156.94 4743.60 5285.42 0.00 0.00 0.00
April 5322.57 2888.94 2433.63 4845.74 3510.59 0.00 0.00 0.00
May 4474.88 1529.86 2945.03 4568.13 1951.25 0.00 0.00 0.00
June 4015.22 1070.23 2944.99 4510.70 1321.42 0.00 0.00 0.00
July 4389.94 1390.71 2999.23 5222.57 1203.07 0.00 0.00 0.00
August 4688.21 1961.04 2727.16 5359.99 1396.17 0.00 0.00 0.00
September 5021.77 2674.47 2347.30 5168.70 2220.03 0.00 0.00 0.00
October 4288.24 2522.13 1766.11 3734.32 3332.98 0.00 0.00 0.00
November 3819.87 2397.36 1422.52 2802.51 4768.93 0.00 0.00 0.00
December 4065.76 2665.97 1399.79 2419.98 7246.63 0.00 0.00 0.00
                 
Annual Sum or Average 4812.48 2569.89 2242.59 4328.09 3812.56 0.00 0.00 0.00
Minimum of Months 3819.87 1070.23 1399.79 2419.98 1203.07 0.00 0.00 0.00
Maximum of Months 6667.65 4503.56 2999.23 5359.99 7405.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1129.64 473.03 656.61 293.09 5834.59 0.00 0.00 0.00
February 1840.52 840.63 999.89 901.36 4742.75 0.00 0.00 0.00
March 2421.98 1239.31 1182.67 1545.88 3798.45 0.00 0.00 0.00
April 3093.95 1567.05 1526.89 2499.94 2369.04 0.00 0.00 0.00
May 3801.46 1813.32 1988.15 3875.98 1311.78 0.00 0.00 0.00
June 3668.33 1586.16 2082.17 4058.83 905.53 0.00 0.00 0.00
July 3916.29 1820.67 2095.62 4506.90 857.90 0.00 0.00 0.00
August 3222.85 1464.44 1758.41 3570.77 956.33 0.00 0.00 0.00
September 2518.78 1131.65 1387.13 2378.59 1476.86 0.00 0.00 0.00
October 1591.13 638.75 952.38 1058.10 2315.19 0.00 0.00 0.00
November 966.37 325.82 640.55 337.76 3541.19 0.00 0.00 0.00
December 861.47 301.52 559.95 147.81 5676.81 0.00 0.00 0.00
                 
Annual Sum or Average 2422.59 1101.75 1320.84 2105.33 2807.83 0.00 0.00 0.00
Minimum of Months 861.47 301.52 559.95 147.81 857.90 0.00 0.00 0.00
Maximum of Months 3916.29 1820.67 2095.62 4506.90 5834.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 764.69 0.00 764.69 1.92 9209.74 0.00 0.00 0.00
February 1174.62 0.00 1174.62 34.21 7410.99 0.00 0.00 0.00
March 1445.17 0.00 1445.17 89.96 5767.63 0.00 0.00 0.00
April 1894.53 14.79 1879.74 602.71 3242.31 0.00 0.00 0.00
May 2664.58 143.48 2521.10 2034.80 1579.92 0.00 0.00 0.00
June 2973.72 326.89 2646.83 2951.82 1083.28 0.00 0.00 0.00
July 2840.37 243.76 2596.61 3005.78 1003.72 0.00 0.00 0.00
August 2157.35 37.05 2120.30 2057.91 1138.64 0.00 0.00 0.00
September 1681.16 0.41 1680.75 1097.91 1906.80 0.00 0.00 0.00
October 1167.31 0.00 1167.31 272.10 3137.78 0.00 0.00 0.00
November 772.91 0.00 772.91 32.69 5239.68 0.00 0.00 0.00
December 647.91 0.00 647.91 0.00 8766.32 0.00 0.00 0.00
                 
Annual Sum or Average 1684.57 64.15 1620.42 1021.50 4110.65 0.00 0.00 0.00
Minimum of Months 647.91 0.00 647.91 0.00 1003.72 0.00 0.00 0.00
Maximum of Months 2973.72 326.89 2646.83 3005.78 9209.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1117.68 466.55 651.12 247.26 5527.20 0.00 0.00 0.00
February 1756.33 749.17 1007.16 747.44 4364.14 0.00 0.00 0.00
March 2393.11 1200.42 1192.69 1451.80 3446.15 0.00 0.00 0.00
April 3317.55 1789.42 1528.13 2707.52 1994.12 0.00 0.00 0.00
May 3590.56 1578.45 2012.11 3489.82 1075.58 0.00 0.00 0.00
June 4064.76 1944.40 2120.36 4462.39 755.22 0.00 0.00 0.00
July 3981.97 1869.68 2112.29 4542.25 687.80 0.00 0.00 0.00
August 3070.11 1341.85 1728.26 3328.02 779.90 0.00 0.00 0.00
September 2458.64 1100.48 1358.17 2283.90 1231.71 0.00 0.00 0.00
October 1488.75 564.53 924.22 931.60 1971.43 0.00 0.00 0.00
November 947.75 316.85 630.90 332.27 3205.22 0.00 0.00 0.00
December 864.81 319.65 545.16 154.40 5348.56 0.00 0.00 0.00
                 
Annual Sum or Average 2423.44 1104.35 1319.09 2063.04 2525.26 0.00 0.00 0.00
Minimum of Months 864.81 316.85 545.16 154.40 687.80 0.00 0.00 0.00
Maximum of Months 4064.76 1944.40 2120.36 4542.25 5527.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 5265.71 3663.24 1602.47 3492.93 7240.31 0.00 0.00 0.00
February 6667.65 4503.56 2164.09 5232.06 6013.67 0.00 0.00 0.00
March 5875.01 3718.06 2156.94 4799.32 5015.31 0.00 0.00 0.00
April 5322.57 2888.94 2433.63 4903.46 3229.96 0.00 0.00 0.00
May 4474.88 1529.86 2945.03 4619.98 1785.34 0.00 0.00 0.00
June 4015.22 1070.23 2944.99 4546.34 1211.27 0.00 0.00 0.00
July 4389.94 1390.71 2999.23 5245.85 1114.58 0.00 0.00 0.00
August 4688.21 1961.04 2727.16 5392.90 1276.37 0.00 0.00 0.00
September 5021.77 2674.47 2347.30 5230.13 2013.86 0.00 0.00 0.00
October 4288.24 2522.13 1766.11 3814.62 3002.11 0.00 0.00 0.00
November 3819.87 2397.36 1422.52 2862.38 4474.61 0.00 0.00 0.00
December 4065.76 2665.97 1399.79 2457.73 7060.22 0.00 0.00 0.00
                 
Annual Sum or Average 4812.48 2569.89 2242.59 4376.14 3609.85 0.00 0.00 0.00
Minimum of Months 3819.87 1070.23 1399.79 2457.73 1114.58 0.00 0.00 0.00
Maximum of Months 6667.65 4503.56 2999.23 5392.90 7240.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1129.64 473.03 656.61 295.85 5739.77 0.00 0.00 0.00
February 1840.52 840.63 999.89 903.92 4626.44 0.00 0.00 0.00
March 2421.98 1239.31 1182.67 1554.94 3649.02 0.00 0.00 0.00
April 3093.95 1567.05 1526.89 2515.78 2211.05 0.00 0.00 0.00
May 3801.46 1813.32 1988.15 3885.14 1227.07 0.00 0.00 0.00
June 3668.33 1586.16 2082.17 4059.26 852.69 0.00 0.00 0.00
July 3916.29 1820.67 2095.62 4502.08 815.20 0.00 0.00 0.00
August 3222.85 1464.44 1758.41 3574.95 899.84 0.00 0.00 0.00
September 2518.78 1131.65 1387.13 2394.83 1369.66 0.00 0.00 0.00
October 1591.13 638.75 952.38 1079.79 2127.07 0.00 0.00 0.00
November 966.37 325.82 640.55 347.86 3375.30 0.00 0.00 0.00
December 861.47 301.52 559.95 149.28 5574.85 0.00 0.00 0.00
                 
Annual Sum or Average 2422.59 1101.75 1320.84 2112.72 2698.13 0.00 0.00 0.00
Minimum of Months 861.47 301.52 559.95 149.28 815.20 0.00 0.00 0.00
Maximum of Months 3916.29 1820.67 2095.62 4502.08 5739.77 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.409635E+09 0.00 0.409635E+09 15494.19 0.507572E+10
February 0.568337E+09 0.00 0.568337E+09 7688772.75 0.376569E+10
March 0.774159E+09 0.00 0.774159E+09 28813541.59 0.334910E+10
April 0.982136E+09 7665453.47 0.974470E+09 0.242524E+09 0.198751E+10
May 0.142738E+10 76862393.79 0.135052E+10 0.999530E+09 0.995425E+09
June 0.154159E+10 0.169462E+09 0.137213E+10 0.144671E+10 0.662318E+09
July 0.152155E+10 0.130578E+09 0.139097E+10 0.153364E+10 0.624957E+09
August 0.115566E+10 19846271.01 0.113582E+10 0.100476E+10 0.766523E+09
September 0.871524E+09 213638.54 0.871310E+09 0.476897E+09 0.120865E+10
October 0.625313E+09 0.00 0.625313E+09 90459769.23 0.204740E+10
November 0.400681E+09 0.00 0.400681E+09 11062046.09 0.310133E+10
December 0.347075E+09 0.00 0.347075E+09 0.00 0.490823E+10
           
Annual Sum or Average 0.106250E+11 0.404628E+09 0.102204E+11 0.584211E+10 0.284928E+11
Minimum of Months 0.347075E+09 0.00 0.347075E+09 0.00 0.624957E+09
Maximum of Months 0.154159E+10 0.169462E+09 0.139097E+10 0.153364E+10 0.507572E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.409634E+09 0.00 0.409634E+09 15493.65 0.507572E+10
February 0.568337E+09 0.00 0.568337E+09 7688726.96 0.376569E+10
March 0.774158E+09 0.00 0.774158E+09 28813432.26 0.334910E+10
April 0.982135E+09 7665444.27 0.974470E+09 0.242524E+09 0.198751E+10
May 0.142738E+10 76862301.57 0.135052E+10 0.999528E+09 0.995425E+09
June 0.154159E+10 0.169462E+09 0.137213E+10 0.144671E+10 0.662318E+09
July 0.152155E+10 0.130577E+09 0.139097E+10 0.153364E+10 0.624957E+09
August 0.115566E+10 19846247.20 0.113582E+10 0.100476E+10 0.766523E+09
September 0.871523E+09 213638.29 0.871309E+09 0.476896E+09 0.120865E+10
October 0.625313E+09 0.00 0.625313E+09 90459504.17 0.204740E+10
November 0.400680E+09 0.00 0.400680E+09 11062019.05 0.310133E+10
December 0.347075E+09 0.00 0.347075E+09 0.00 0.490823E+10
           
Annual Sum or Average 0.106250E+11 0.404627E+09 0.102204E+11 0.584210E+10 0.284929E+11
Minimum of Months 0.347075E+09 0.00 0.347075E+09 0.00 0.624957E+09
Maximum of Months 0.154159E+10 0.169462E+09 0.139097E+10 0.153364E+10 0.507572E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.409635E+09 0.00 0.409635E+09 15494.19 0.507572E+10
February 0.568337E+09 0.00 0.568337E+09 7688772.75 0.376569E+10
March 0.774159E+09 0.00 0.774159E+09 28813541.59 0.334910E+10
April 0.982136E+09 7665453.47 0.974470E+09 0.242524E+09 0.198751E+10
May 0.142738E+10 76862393.79 0.135052E+10 0.999530E+09 0.995425E+09
June 0.154159E+10 0.169462E+09 0.137213E+10 0.144671E+10 0.662318E+09
July 0.152155E+10 0.130578E+09 0.139097E+10 0.153364E+10 0.624957E+09
August 0.115566E+10 19846271.01 0.113582E+10 0.100476E+10 0.766523E+09
September 0.871524E+09 213638.54 0.871310E+09 0.476897E+09 0.120865E+10
October 0.625313E+09 0.00 0.625313E+09 90459769.23 0.204740E+10
November 0.400681E+09 0.00 0.400681E+09 11062046.09 0.310133E+10
December 0.347075E+09 0.00 0.347075E+09 0.00 0.490823E+10
           
Annual Sum or Average 0.106250E+11 0.404628E+09 0.102204E+11 0.584211E+10 0.284928E+11
Minimum of Months 0.347075E+09 0.00 0.347075E+09 0.00 0.624957E+09
Maximum of Months 0.154159E+10 0.169462E+09 0.139097E+10 0.153364E+10 0.507572E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.409634E+09 0.00 0.409634E+09 15493.65 0.507572E+10
February 0.568337E+09 0.00 0.568337E+09 7688726.96 0.376569E+10
March 0.774158E+09 0.00 0.774158E+09 28813432.26 0.334910E+10
April 0.982135E+09 7665444.27 0.974470E+09 0.242524E+09 0.198751E+10
May 0.142738E+10 76862301.57 0.135052E+10 0.999528E+09 0.995425E+09
June 0.154159E+10 0.169462E+09 0.137213E+10 0.144671E+10 0.662318E+09
July 0.152155E+10 0.130577E+09 0.139097E+10 0.153364E+10 0.624957E+09
August 0.115566E+10 19846247.20 0.113582E+10 0.100476E+10 0.766523E+09
September 0.871523E+09 213638.29 0.871309E+09 0.476896E+09 0.120865E+10
October 0.625313E+09 0.00 0.625313E+09 90459504.17 0.204740E+10
November 0.400680E+09 0.00 0.400680E+09 11062019.05 0.310133E+10
December 0.347075E+09 0.00 0.347075E+09 0.00 0.490823E+10
           
Annual Sum or Average 0.106250E+11 0.404627E+09 0.102204E+11 0.584210E+10 0.284929E+11
Minimum of Months 0.347075E+09 0.00 0.347075E+09 0.00 0.624957E+09
Maximum of Months 0.154159E+10 0.169462E+09 0.139097E+10 0.153364E+10 0.507572E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.409618E+09 0.00 0.409618E+09 15493.56 0.507552E+10
February 0.568314E+09 0.00 0.568314E+09 7688462.86 0.376554E+10
March 0.774127E+09 0.00 0.774127E+09 28812380.28 0.334897E+10
April 0.982096E+09 7665144.52 0.974431E+09 0.242515E+09 0.198743E+10
May 0.142732E+10 76859295.90 0.135046E+10 0.999489E+09 0.995385E+09
June 0.154153E+10 0.169456E+09 0.137208E+10 0.144665E+10 0.662292E+09
July 0.152149E+10 0.130572E+09 0.139091E+10 0.153358E+10 0.624932E+09
August 0.115562E+10 19845471.12 0.113577E+10 0.100472E+10 0.766492E+09
September 0.871488E+09 213629.93 0.871275E+09 0.476878E+09 0.120860E+10
October 0.625288E+09 0.00 0.625288E+09 90456123.30 0.204732E+10
November 0.400665E+09 0.00 0.400665E+09 11061600.24 0.310120E+10
December 0.347061E+09 0.00 0.347061E+09 0.00 0.490803E+10
           
Annual Sum or Average 0.106246E+11 0.404611E+09 0.102200E+11 0.584187E+10 0.284917E+11
Minimum of Months 0.347061E+09 0.00 0.347061E+09 0.00 0.624932E+09
Maximum of Months 0.154153E+10 0.169456E+09 0.139091E+10 0.153358E+10 0.507552E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.997873E+09 0.416543E+09 0.581330E+09 0.217264E+09 0.507631E+10
February 0.141632E+10 0.604139E+09 0.812181E+09 0.580271E+09 0.369132E+10
March 0.213659E+10 0.107175E+10 0.106485E+10 0.126340E+10 0.330348E+10
April 0.286639E+10 0.154607E+10 0.132032E+10 0.230534E+10 0.195804E+10
May 0.320569E+10 0.140926E+10 0.179643E+10 0.311241E+10 0.106694E+10
June 0.351199E+10 0.167998E+10 0.183201E+10 0.387402E+10 0.725414E+09
July 0.355514E+10 0.166927E+10 0.188587E+10 0.408024E+10 0.661479E+09
August 0.274102E+10 0.119802E+10 0.154300E+10 0.296961E+10 0.782831E+09
September 0.212429E+10 0.950821E+09 0.117347E+10 0.193611E+10 0.122632E+10
October 0.132917E+10 0.504019E+09 0.825152E+09 0.775922E+09 0.207983E+10
November 0.818865E+09 0.273765E+09 0.545100E+09 0.264670E+09 0.313324E+10
December 0.772114E+09 0.285386E+09 0.486728E+09 0.132628E+09 0.497583E+10
           
Annual Sum or Average 0.254755E+11 0.116090E+11 0.138664E+11 0.215119E+11 0.286810E+11
Minimum of Months 0.772114E+09 0.273765E+09 0.486728E+09 0.132628E+09 0.661479E+09
Maximum of Months 0.355514E+10 0.167998E+10 0.188587E+10 0.408024E+10 0.507631E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.997873E+09 0.416543E+09 0.581330E+09 0.217264E+09 0.507631E+10
February 0.141632E+10 0.604139E+09 0.812181E+09 0.580271E+09 0.369132E+10
March 0.213659E+10 0.107175E+10 0.106485E+10 0.126340E+10 0.330348E+10
April 0.286639E+10 0.154607E+10 0.132032E+10 0.230534E+10 0.195804E+10
May 0.320569E+10 0.140926E+10 0.179643E+10 0.311241E+10 0.106694E+10
June 0.351199E+10 0.167998E+10 0.183201E+10 0.387402E+10 0.725414E+09
July 0.355514E+10 0.166927E+10 0.188587E+10 0.408024E+10 0.661479E+09
August 0.274102E+10 0.119802E+10 0.154300E+10 0.296961E+10 0.782831E+09
September 0.212429E+10 0.950821E+09 0.117347E+10 0.193611E+10 0.122632E+10
October 0.132917E+10 0.504019E+09 0.825152E+09 0.775922E+09 0.207983E+10
November 0.818865E+09 0.273765E+09 0.545100E+09 0.264670E+09 0.313324E+10
December 0.772114E+09 0.285386E+09 0.486728E+09 0.132628E+09 0.497583E+10
           
Annual Sum or Average 0.254755E+11 0.116090E+11 0.138664E+11 0.215119E+11 0.286810E+11
Minimum of Months 0.772114E+09 0.273765E+09 0.486728E+09 0.132628E+09 0.661479E+09
Maximum of Months 0.355514E+10 0.167998E+10 0.188587E+10 0.408024E+10 0.507631E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.997855E+09 0.416536E+09 0.581319E+09 0.217260E+09 0.507621E+10
February 0.141629E+10 0.604128E+09 0.812166E+09 0.580260E+09 0.369126E+10
March 0.213655E+10 0.107173E+10 0.106483E+10 0.126338E+10 0.330342E+10
April 0.286634E+10 0.154605E+10 0.132029E+10 0.230530E+10 0.195801E+10
May 0.320563E+10 0.140923E+10 0.179640E+10 0.311235E+10 0.106692E+10
June 0.351193E+10 0.167995E+10 0.183198E+10 0.387395E+10 0.725400E+09
July 0.355508E+10 0.166924E+10 0.188584E+10 0.408017E+10 0.661467E+09
August 0.274097E+10 0.119800E+10 0.154297E+10 0.296956E+10 0.782817E+09
September 0.212425E+10 0.950803E+09 0.117345E+10 0.193607E+10 0.122630E+10
October 0.132915E+10 0.504010E+09 0.825137E+09 0.775908E+09 0.207979E+10
November 0.818850E+09 0.273760E+09 0.545090E+09 0.264666E+09 0.313318E+10
December 0.772100E+09 0.285380E+09 0.486719E+09 0.132625E+09 0.497574E+10
           
Annual Sum or Average 0.254750E+11 0.116088E+11 0.138662E+11 0.215115E+11 0.286805E+11
Minimum of Months 0.772100E+09 0.273760E+09 0.486719E+09 0.132625E+09 0.661467E+09
Maximum of Months 0.355508E+10 0.167995E+10 0.188584E+10 0.408017E+10 0.507621E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.282077E+10 0.196235E+10 0.858423E+09 0.187690E+10 0.395463E+10
February 0.322611E+10 0.217903E+10 0.104708E+10 0.254561E+10 0.301677E+10
March 0.314716E+10 0.199172E+10 0.115545E+10 0.257538E+10 0.284265E+10
April 0.275925E+10 0.149765E+10 0.126161E+10 0.253693E+10 0.185967E+10
May 0.239713E+10 0.819523E+09 0.157761E+10 0.247080E+10 0.105792E+10
June 0.208152E+10 0.554815E+09 0.152670E+10 0.234774E+10 0.705363E+09
July 0.235163E+10 0.744986E+09 0.160665E+10 0.280923E+10 0.659339E+09
August 0.251141E+10 0.105050E+10 0.146090E+10 0.288331E+10 0.778227E+09
September 0.260332E+10 0.138646E+10 0.121686E+10 0.270828E+10 0.116277E+10
October 0.229715E+10 0.135107E+10 0.946081E+09 0.201898E+10 0.181486E+10
November 0.198025E+10 0.124280E+10 0.737441E+09 0.146087E+10 0.254532E+10
December 0.217797E+10 0.142812E+10 0.749849E+09 0.130542E+10 0.390525E+10
           
Annual Sum or Average 0.303537E+11 0.162090E+11 0.141446E+11 0.275395E+11 0.243028E+11
Minimum of Months 0.198025E+10 0.554815E+09 0.737441E+09 0.130542E+10 0.659339E+09
Maximum of Months 0.322611E+10 0.217903E+10 0.160665E+10 0.288331E+10 0.395463E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.282077E+10 0.196234E+10 0.858422E+09 0.187689E+10 0.395463E+10
February 0.322611E+10 0.217903E+10 0.104708E+10 0.254561E+10 0.301677E+10
March 0.314716E+10 0.199171E+10 0.115544E+10 0.257538E+10 0.284265E+10
April 0.275925E+10 0.149764E+10 0.126161E+10 0.253693E+10 0.185967E+10
May 0.239713E+10 0.819522E+09 0.157761E+10 0.247080E+10 0.105792E+10
June 0.208151E+10 0.554815E+09 0.152670E+10 0.234774E+10 0.705363E+09
July 0.235163E+10 0.744985E+09 0.160664E+10 0.280923E+10 0.659339E+09
August 0.251141E+10 0.105050E+10 0.146090E+10 0.288331E+10 0.778227E+09
September 0.260331E+10 0.138646E+10 0.121685E+10 0.270827E+10 0.116277E+10
October 0.229715E+10 0.135107E+10 0.946080E+09 0.201898E+10 0.181486E+10
November 0.198024E+10 0.124280E+10 0.737440E+09 0.146087E+10 0.254532E+10
December 0.217797E+10 0.142812E+10 0.749848E+09 0.130541E+10 0.390526E+10
           
Annual Sum or Average 0.303536E+11 0.162090E+11 0.141446E+11 0.275394E+11 0.243028E+11
Minimum of Months 0.198024E+10 0.554815E+09 0.737440E+09 0.130541E+10 0.659339E+09
Maximum of Months 0.322611E+10 0.217903E+10 0.160664E+10 0.288331E+10 0.395463E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.282077E+10 0.196235E+10 0.858423E+09 0.187690E+10 0.395463E+10
February 0.322611E+10 0.217903E+10 0.104708E+10 0.254561E+10 0.301677E+10
March 0.314716E+10 0.199172E+10 0.115545E+10 0.257538E+10 0.284265E+10
April 0.275925E+10 0.149765E+10 0.126161E+10 0.253693E+10 0.185967E+10
May 0.239713E+10 0.819523E+09 0.157761E+10 0.247080E+10 0.105792E+10
June 0.208152E+10 0.554815E+09 0.152670E+10 0.234774E+10 0.705363E+09
July 0.235163E+10 0.744986E+09 0.160665E+10 0.280923E+10 0.659339E+09
August 0.251141E+10 0.105050E+10 0.146090E+10 0.288331E+10 0.778227E+09
September 0.260332E+10 0.138646E+10 0.121686E+10 0.270828E+10 0.116277E+10
October 0.229715E+10 0.135107E+10 0.946081E+09 0.201898E+10 0.181486E+10
November 0.198025E+10 0.124280E+10 0.737441E+09 0.146087E+10 0.254532E+10
December 0.217797E+10 0.142812E+10 0.749849E+09 0.130542E+10 0.390525E+10
           
Annual Sum or Average 0.303537E+11 0.162090E+11 0.141446E+11 0.275395E+11 0.243028E+11
Minimum of Months 0.198025E+10 0.554815E+09 0.737441E+09 0.130542E+10 0.659339E+09
Maximum of Months 0.322611E+10 0.217903E+10 0.160665E+10 0.288331E+10 0.395463E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.282077E+10 0.196234E+10 0.858422E+09 0.187689E+10 0.395463E+10
February 0.322611E+10 0.217903E+10 0.104708E+10 0.254561E+10 0.301677E+10
March 0.314716E+10 0.199171E+10 0.115544E+10 0.257538E+10 0.284265E+10
April 0.275925E+10 0.149764E+10 0.126161E+10 0.253693E+10 0.185967E+10
May 0.239713E+10 0.819522E+09 0.157761E+10 0.247080E+10 0.105792E+10
June 0.208151E+10 0.554815E+09 0.152670E+10 0.234774E+10 0.705363E+09
July 0.235163E+10 0.744985E+09 0.160664E+10 0.280923E+10 0.659339E+09
August 0.251141E+10 0.105050E+10 0.146090E+10 0.288331E+10 0.778227E+09
September 0.260331E+10 0.138646E+10 0.121685E+10 0.270827E+10 0.116277E+10
October 0.229715E+10 0.135107E+10 0.946080E+09 0.201898E+10 0.181486E+10
November 0.198024E+10 0.124280E+10 0.737440E+09 0.146087E+10 0.254532E+10
December 0.217797E+10 0.142812E+10 0.749848E+09 0.130541E+10 0.390526E+10
           
Annual Sum or Average 0.303536E+11 0.162090E+11 0.141446E+11 0.275394E+11 0.243028E+11
Minimum of Months 0.198024E+10 0.554815E+09 0.737440E+09 0.130541E+10 0.659339E+09
Maximum of Months 0.322611E+10 0.217903E+10 0.160664E+10 0.288331E+10 0.395463E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.282065E+10 0.196227E+10 0.858388E+09 0.187682E+10 0.395447E+10
February 0.322598E+10 0.217894E+10 0.104704E+10 0.254551E+10 0.301665E+10
March 0.314704E+10 0.199164E+10 0.115540E+10 0.257528E+10 0.284253E+10
April 0.275914E+10 0.149759E+10 0.126156E+10 0.253683E+10 0.185960E+10
May 0.239704E+10 0.819490E+09 0.157755E+10 0.247070E+10 0.105787E+10
June 0.208143E+10 0.554793E+09 0.152664E+10 0.234765E+10 0.705334E+09
July 0.235154E+10 0.744956E+09 0.160658E+10 0.280912E+10 0.659313E+09
August 0.251131E+10 0.105046E+10 0.146085E+10 0.288319E+10 0.778196E+09
September 0.260321E+10 0.138641E+10 0.121681E+10 0.270817E+10 0.116273E+10
October 0.229706E+10 0.135101E+10 0.946043E+09 0.201890E+10 0.181479E+10
November 0.198017E+10 0.124275E+10 0.737411E+09 0.146081E+10 0.254522E+10
December 0.217788E+10 0.142806E+10 0.749819E+09 0.130536E+10 0.390510E+10
           
Annual Sum or Average 0.303524E+11 0.162084E+11 0.141441E+11 0.275384E+11 0.243018E+11
Minimum of Months 0.198017E+10 0.554793E+09 0.737411E+09 0.130536E+10 0.659313E+09
Maximum of Months 0.322598E+10 0.217894E+10 0.160658E+10 0.288319E+10 0.395447E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.100855E+10 0.422323E+09 0.586231E+09 0.257842E+09 0.537216E+10
February 0.148421E+10 0.677888E+09 0.806321E+09 0.715211E+09 0.400694E+10
March 0.216237E+10 0.110647E+10 0.105590E+10 0.135692E+10 0.362314E+10
April 0.267320E+10 0.135395E+10 0.131925E+10 0.210382E+10 0.230082E+10
May 0.339398E+10 0.161894E+10 0.177504E+10 0.342704E+10 0.125321E+10
June 0.316947E+10 0.137045E+10 0.179901E+10 0.345756E+10 0.866273E+09
July 0.349650E+10 0.162551E+10 0.187099E+10 0.396051E+10 0.860809E+09
August 0.287739E+10 0.130747E+10 0.156992E+10 0.309925E+10 0.102481E+10
September 0.217625E+10 0.977756E+09 0.119849E+10 0.201161E+10 0.139623E+10
October 0.142058E+10 0.570281E+09 0.850294E+09 0.910756E+09 0.228039E+10
November 0.834956E+09 0.281515E+09 0.553441E+09 0.270459E+09 0.340186E+10
December 0.769127E+09 0.269200E+09 0.499927E+09 0.125435E+09 0.537882E+10
           
Annual Sum or Average 0.254666E+11 0.115818E+11 0.138848E+11 0.216964E+11 0.317655E+11
Minimum of Months 0.769127E+09 0.269200E+09 0.499927E+09 0.125435E+09 0.860809E+09
Maximum of Months 0.349650E+10 0.162551E+10 0.187099E+10 0.396051E+10 0.537882E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.100855E+10 0.422323E+09 0.586231E+09 0.257842E+09 0.537216E+10
February 0.148421E+10 0.677888E+09 0.806321E+09 0.715211E+09 0.400694E+10
March 0.216237E+10 0.110647E+10 0.105590E+10 0.135692E+10 0.362314E+10
April 0.267320E+10 0.135395E+10 0.131925E+10 0.210382E+10 0.230082E+10
May 0.339398E+10 0.161894E+10 0.177504E+10 0.342704E+10 0.125321E+10
June 0.316947E+10 0.137045E+10 0.179901E+10 0.345756E+10 0.866273E+09
July 0.349650E+10 0.162551E+10 0.187099E+10 0.396051E+10 0.860809E+09
August 0.287739E+10 0.130747E+10 0.156992E+10 0.309925E+10 0.102481E+10
September 0.217625E+10 0.977756E+09 0.119849E+10 0.201161E+10 0.139623E+10
October 0.142058E+10 0.570281E+09 0.850294E+09 0.910756E+09 0.228039E+10
November 0.834956E+09 0.281515E+09 0.553441E+09 0.270459E+09 0.340186E+10
December 0.769127E+09 0.269200E+09 0.499927E+09 0.125435E+09 0.537882E+10
           
Annual Sum or Average 0.254666E+11 0.115818E+11 0.138848E+11 0.216964E+11 0.317655E+11
Minimum of Months 0.769127E+09 0.269200E+09 0.499927E+09 0.125435E+09 0.860809E+09
Maximum of Months 0.349650E+10 0.162551E+10 0.187099E+10 0.396051E+10 0.537882E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.100854E+10 0.422315E+09 0.586220E+09 0.257837E+09 0.537206E+10
February 0.148418E+10 0.677875E+09 0.806306E+09 0.715198E+09 0.400687E+10
March 0.216233E+10 0.110645E+10 0.105588E+10 0.135689E+10 0.362307E+10
April 0.267315E+10 0.135392E+10 0.131922E+10 0.210378E+10 0.230078E+10
May 0.339392E+10 0.161891E+10 0.177500E+10 0.342697E+10 0.125318E+10
June 0.316941E+10 0.137043E+10 0.179898E+10 0.345749E+10 0.866257E+09
July 0.349644E+10 0.162548E+10 0.187096E+10 0.396043E+10 0.860793E+09
August 0.287734E+10 0.130744E+10 0.156989E+10 0.309919E+10 0.102480E+10
September 0.217621E+10 0.977738E+09 0.119847E+10 0.201157E+10 0.139620E+10
October 0.142055E+10 0.570271E+09 0.850279E+09 0.910739E+09 0.228035E+10
November 0.834941E+09 0.281510E+09 0.553430E+09 0.270454E+09 0.340179E+10
December 0.769113E+09 0.269195E+09 0.499918E+09 0.125433E+09 0.537872E+10
           
Annual Sum or Average 0.254661E+11 0.115815E+11 0.138846E+11 0.216960E+11 0.317649E+11
Minimum of Months 0.769113E+09 0.269195E+09 0.499918E+09 0.125433E+09 0.860793E+09
Maximum of Months 0.349644E+10 0.162548E+10 0.187096E+10 0.396043E+10 0.537872E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.204815E+10 0.00 0.204815E+10 2911096.12 0.250719E+11
February 0.284165E+10 0.00 0.284165E+10 71357880.51 0.183774E+11
March 0.387075E+10 0.00 0.387075E+10 0.201856E+09 0.160968E+11
April 0.491062E+10 38326803.89 0.487229E+10 0.142972E+10 0.911368E+10
May 0.713682E+10 0.384307E+09 0.675252E+10 0.521433E+10 0.465851E+10
June 0.770788E+10 0.847302E+09 0.686058E+10 0.742997E+10 0.308041E+10
July 0.760764E+10 0.652880E+09 0.695476E+10 0.786654E+10 0.291804E+10
August 0.577825E+10 99230155.17 0.567901E+10 0.531744E+10 0.338260E+10
September 0.435757E+10 1068179.80 0.435650E+10 0.263658E+10 0.550733E+10
October 0.312653E+10 0.00 0.312653E+10 0.605201E+09 0.932874E+10
November 0.200338E+10 0.00 0.200338E+10 74248998.35 0.143294E+11
December 0.173536E+10 0.00 0.173536E+10 0.00 0.239483E+11
           
Annual Sum or Average 0.531246E+11 0.202311E+10 0.511015E+11 0.308501E+11 0.135813E+12
Minimum of Months 0.173536E+10 0.00 0.173536E+10 0.00 0.291804E+10
Maximum of Months 0.770788E+10 0.847302E+09 0.695476E+10 0.786654E+10 0.250719E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.299359E+10 0.124962E+10 0.174397E+10 0.649162E+09 0.149927E+11
February 0.424892E+10 0.181240E+10 0.243652E+10 0.175988E+10 0.108325E+11
March 0.640971E+10 0.321521E+10 0.319451E+10 0.377865E+10 0.966319E+10
April 0.859908E+10 0.463817E+10 0.396091E+10 0.686606E+10 0.559969E+10
May 0.961696E+10 0.422772E+10 0.538923E+10 0.922208E+10 0.309741E+10
June 0.105359E+11 0.503989E+10 0.549598E+10 0.115117E+11 0.209246E+10
July 0.106653E+11 0.500776E+10 0.565755E+10 0.121430E+11 0.194445E+10
August 0.822298E+10 0.359402E+10 0.462896E+10 0.884464E+10 0.224294E+10
September 0.637280E+10 0.285243E+10 0.352037E+10 0.576244E+10 0.350813E+10
October 0.398747E+10 0.151204E+10 0.247543E+10 0.233644E+10 0.587310E+10
November 0.245657E+10 0.821288E+09 0.163528E+10 0.813244E+09 0.879638E+10
December 0.231632E+10 0.856148E+09 0.146017E+10 0.401580E+09 0.145539E+11
           
Annual Sum or Average 0.764256E+11 0.348267E+11 0.415989E+11 0.640888E+11 0.831968E+11
Minimum of Months 0.231632E+10 0.821288E+09 0.146017E+10 0.401580E+09 0.194445E+10
Maximum of Months 0.106653E+11 0.503989E+10 0.565755E+10 0.121430E+11 0.149927E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141037E+11 0.981161E+10 0.429206E+10 0.926678E+10 0.198338E+11
February 0.161304E+11 0.108950E+11 0.523536E+10 0.125421E+11 0.150780E+11
March 0.157356E+11 0.995846E+10 0.577716E+10 0.127053E+11 0.141565E+11
April 0.137961E+11 0.748814E+10 0.630796E+10 0.125602E+11 0.909946E+10
May 0.119855E+11 0.409757E+10 0.788796E+10 0.122353E+11 0.522622E+10
June 0.104075E+11 0.277404E+10 0.763341E+10 0.116917E+11 0.342513E+10
July 0.117580E+11 0.372488E+10 0.803313E+10 0.139881E+11 0.322231E+10
August 0.125569E+11 0.525245E+10 0.730444E+10 0.143562E+11 0.373951E+10
September 0.130164E+11 0.693222E+10 0.608420E+10 0.133973E+11 0.575432E+10
October 0.114856E+11 0.675526E+10 0.473035E+10 0.100020E+11 0.892707E+10
November 0.990111E+10 0.621395E+10 0.368716E+10 0.726411E+10 0.123611E+11
December 0.108897E+11 0.714052E+10 0.374920E+10 0.648167E+10 0.194094E+11
           
Annual Sum or Average 0.151767E+12 0.810441E+11 0.707224E+11 0.136491E+12 0.120233E+12
Minimum of Months 0.990111E+10 0.277404E+10 0.368716E+10 0.648167E+10 0.322231E+10
Maximum of Months 0.161304E+11 0.108950E+11 0.803313E+10 0.143562E+11 0.198338E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.302563E+10 0.126696E+10 0.175867E+10 0.785001E+09 0.156274E+11
February 0.445258E+10 0.203364E+10 0.241894E+10 0.218057E+10 0.114737E+11
March 0.648703E+10 0.331937E+10 0.316766E+10 0.414048E+10 0.101738E+11
April 0.801951E+10 0.406180E+10 0.395770E+10 0.647984E+10 0.614055E+10
May 0.101818E+11 0.485678E+10 0.532505E+10 0.103814E+11 0.351347E+10
June 0.950830E+10 0.411132E+10 0.539699E+10 0.105205E+11 0.234714E+10
July 0.104894E+11 0.487649E+10 0.561292E+10 0.120713E+11 0.229781E+10
August 0.863208E+10 0.392237E+10 0.470971E+10 0.956394E+10 0.256143E+10
September 0.652868E+10 0.293324E+10 0.359544E+10 0.616530E+10 0.382803E+10
October 0.426168E+10 0.171083E+10 0.255086E+10 0.283401E+10 0.620100E+10
November 0.250484E+10 0.844538E+09 0.166030E+10 0.875476E+09 0.917875E+10
December 0.230736E+10 0.807592E+09 0.149977E+10 0.395905E+09 0.152048E+11
           
Annual Sum or Average 0.763989E+11 0.347449E+11 0.416540E+11 0.663937E+11 0.885477E+11
Minimum of Months 0.230736E+10 0.807592E+09 0.149977E+10 0.395905E+09 0.229781E+10
Maximum of Months 0.104894E+11 0.487649E+10 0.561292E+10 0.120713E+11 0.156274E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.204815E+10 0.00 0.204815E+10 5147764.17 0.246674E+11
February 0.284165E+10 0.00 0.284165E+10 82759066.79 0.179287E+11
March 0.387075E+10 0.00 0.387075E+10 0.240959E+09 0.154480E+11
April 0.491062E+10 38326803.89 0.487229E+10 0.156223E+10 0.840406E+10
May 0.713682E+10 0.384307E+09 0.675252E+10 0.545001E+10 0.423164E+10
June 0.770788E+10 0.847302E+09 0.686058E+10 0.765112E+10 0.280786E+10
July 0.760764E+10 0.652880E+09 0.695476E+10 0.805069E+10 0.268835E+10
August 0.577825E+10 99230155.17 0.567901E+10 0.551191E+10 0.304973E+10
September 0.435757E+10 1068179.80 0.435650E+10 0.284578E+10 0.494243E+10
October 0.312653E+10 0.00 0.312653E+10 0.728804E+09 0.840424E+10
November 0.200338E+10 0.00 0.200338E+10 84721079.64 0.135812E+11
December 0.173536E+10 0.00 0.173536E+10 0.00 0.234797E+11
           
Annual Sum or Average 0.531246E+11 0.202311E+10 0.511015E+11 0.322141E+11 0.129633E+12
Minimum of Months 0.173536E+10 0.00 0.173536E+10 0.00 0.268835E+10
Maximum of Months 0.770788E+10 0.847302E+09 0.695476E+10 0.805069E+10 0.246674E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.299359E+10 0.124962E+10 0.174397E+10 0.662251E+09 0.148041E+11
February 0.424892E+10 0.181240E+10 0.243652E+10 0.180819E+10 0.105577E+11
March 0.640971E+10 0.321521E+10 0.319451E+10 0.388849E+10 0.923018E+10
April 0.859908E+10 0.463817E+10 0.396091E+10 0.701788E+10 0.516876E+10
May 0.961696E+10 0.422772E+10 0.538923E+10 0.934713E+10 0.288083E+10
June 0.105359E+11 0.503989E+10 0.549598E+10 0.115665E+11 0.195754E+10
July 0.106653E+11 0.500776E+10 0.565755E+10 0.121660E+11 0.184220E+10
August 0.822298E+10 0.359402E+10 0.462896E+10 0.891376E+10 0.208887E+10
September 0.637280E+10 0.285243E+10 0.352037E+10 0.591987E+10 0.319259E+10
October 0.398747E+10 0.151204E+10 0.247543E+10 0.249520E+10 0.528028E+10
November 0.245657E+10 0.821288E+09 0.163528E+10 0.861238E+09 0.830793E+10
December 0.231632E+10 0.856148E+09 0.146017E+10 0.413544E+09 0.143256E+11
           
Annual Sum or Average 0.764256E+11 0.348267E+11 0.415989E+11 0.650600E+11 0.796366E+11
Minimum of Months 0.231632E+10 0.821288E+09 0.146017E+10 0.413544E+09 0.184220E+10
Maximum of Months 0.106653E+11 0.503989E+10 0.565755E+10 0.121660E+11 0.148041E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141037E+11 0.981161E+10 0.429206E+10 0.935545E+10 0.193925E+11
February 0.161304E+11 0.108950E+11 0.523536E+10 0.126574E+11 0.145483E+11
March 0.157356E+11 0.995846E+10 0.577716E+10 0.128545E+11 0.134330E+11
April 0.137961E+11 0.748814E+10 0.630796E+10 0.127098E+11 0.837204E+10
May 0.119855E+11 0.409757E+10 0.788796E+10 0.123741E+11 0.478186E+10
June 0.104075E+11 0.277404E+10 0.763341E+10 0.117841E+11 0.313961E+10
July 0.117580E+11 0.372488E+10 0.803313E+10 0.140505E+11 0.298528E+10
August 0.125569E+11 0.525245E+10 0.730444E+10 0.144444E+11 0.341862E+10
September 0.130164E+11 0.693222E+10 0.608420E+10 0.135565E+11 0.521992E+10
October 0.114856E+11 0.675526E+10 0.473035E+10 0.102171E+11 0.804085E+10
November 0.990111E+10 0.621395E+10 0.368716E+10 0.741928E+10 0.115982E+11
December 0.108897E+11 0.714052E+10 0.374920E+10 0.658279E+10 0.189101E+11
           
Annual Sum or Average 0.151767E+12 0.810441E+11 0.707224E+11 0.138006E+12 0.113840E+12
Minimum of Months 0.990111E+10 0.277404E+10 0.368716E+10 0.658279E+10 0.298528E+10
Maximum of Months 0.161304E+11 0.108950E+11 0.803313E+10 0.144444E+11 0.193925E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.302563E+10 0.126696E+10 0.175867E+10 0.792400E+09 0.153734E+11
February 0.445258E+10 0.203364E+10 0.241894E+10 0.218676E+10 0.111923E+11
March 0.648703E+10 0.331937E+10 0.316766E+10 0.416474E+10 0.977353E+10
April 0.801951E+10 0.406180E+10 0.395770E+10 0.652090E+10 0.573103E+10
May 0.101818E+11 0.485678E+10 0.532505E+10 0.104060E+11 0.328658E+10
June 0.950830E+10 0.411132E+10 0.539699E+10 0.105216E+11 0.221016E+10
July 0.104894E+11 0.487649E+10 0.561292E+10 0.120584E+11 0.218343E+10
August 0.863208E+10 0.392237E+10 0.470971E+10 0.957515E+10 0.241012E+10
September 0.652868E+10 0.293324E+10 0.359544E+10 0.620740E+10 0.355015E+10
October 0.426168E+10 0.171083E+10 0.255086E+10 0.289210E+10 0.569714E+10
November 0.250484E+10 0.844538E+09 0.166030E+10 0.901645E+09 0.874877E+10
December 0.230736E+10 0.807592E+09 0.149977E+10 0.399833E+09 0.149317E+11
           
Annual Sum or Average 0.763989E+11 0.347449E+11 0.416540E+11 0.666269E+11 0.850883E+11
Minimum of Months 0.230736E+10 0.807592E+09 0.149977E+10 0.399833E+09 0.218343E+10
Maximum of Months 0.104894E+11 0.487649E+10 0.561292E+10 0.120584E+11 0.153734E+11



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.03 9475.21 764.69 0.00 764.69 0.00 0.00
February 15.89 7782.86 1174.63 0.00 1174.63 0.00 0.00
March 53.79 6252.01 1445.18 0.00 1445.18 0.00 0.00
April 467.83 3833.90 1894.54 14.79 1879.75 0.00 0.00
May 1865.89 1858.23 2664.59 143.48 2521.11 0.00 0.00
June 2790.70 1277.61 2973.73 326.89 2646.84 0.00 0.00
July 2862.95 1166.65 2840.38 243.76 2596.62 0.00 0.00
August 1875.66 1430.92 2157.36 37.05 2120.31 0.00 0.00
September 919.93 2331.49 1681.17 0.41 1680.75 0.00 0.00
October 168.87 3822.02 1167.32 0.00 1167.32 0.00 0.00
November 21.34 5982.45 772.91 0.00 772.91 0.00 0.00
December 0.00 9162.54 647.91 0.00 647.91 0.00 0.00
               
Annual Sum or Average 926.25 4517.48 1684.58 64.15 1620.42 0.00 0.00
Minimum of Months 0.00 1166.65 647.91 0.00 647.91 0.00 0.00
Maximum of Months 2862.95 9475.21 2973.73 326.89 2646.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 243.35 5685.79 1117.68 466.56 651.13 0.00 0.00
February 719.58 4577.51 1756.34 749.18 1007.16 0.00 0.00
March 1415.09 3700.12 2393.12 1200.43 1192.70 0.00 0.00
April 2668.21 2266.24 3317.56 1789.43 1528.14 0.00 0.00
May 3486.10 1195.04 3590.58 1578.46 2012.12 0.00 0.00
June 4483.79 839.59 4064.78 1944.41 2120.37 0.00 0.00
July 4570.14 740.90 3981.99 1869.69 2112.30 0.00 0.00
August 3326.16 876.82 3070.12 1341.86 1728.26 0.00 0.00
September 2240.85 1419.34 2458.65 1100.48 1358.17 0.00 0.00
October 869.08 2329.54 1488.76 564.53 924.22 0.00 0.00
November 306.33 3626.41 947.75 316.86 630.90 0.00 0.00
December 148.55 5573.25 864.82 319.65 545.17 0.00 0.00
               
Annual Sum or Average 2046.40 2728.39 2423.45 1104.35 1319.10 0.00 0.00
Minimum of Months 148.55 740.90 864.82 316.86 545.17 0.00 0.00
Maximum of Months 4570.14 5685.79 4064.78 1944.41 2120.37 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3503.73 7382.39 5265.73 3663.25 1602.48 0.00 0.00
February 5261.23 6235.02 6667.67 4503.58 2164.09 0.00 0.00
March 4807.65 5306.57 5875.03 3718.08 2156.95 0.00 0.00
April 4893.73 3587.30 5322.59 2888.95 2433.64 0.00 0.00
May 4612.42 1974.89 4474.90 1529.86 2945.04 0.00 0.00
June 4528.79 1360.64 4015.24 1070.24 2945.00 0.00 0.00
July 5244.19 1230.84 4389.96 1390.72 2999.24 0.00 0.00
August 5382.48 1452.77 4688.22 1961.05 2727.17 0.00 0.00
September 5224.26 2242.99 5021.79 2674.48 2347.31 0.00 0.00
October 3768.98 3387.93 4288.25 2522.13 1766.12 0.00 0.00
November 2818.02 4909.91 3819.89 2397.37 1422.52 0.00 0.00
December 2436.91 7290.22 4065.77 2665.98 1399.80 0.00 0.00
               
Annual Sum or Average 4366.32 3853.15 4812.50 2569.90 2242.60 0.00 0.00
Minimum of Months 2436.91 1230.84 3819.89 1070.24 1399.80 0.00 0.00
Maximum of Months 5382.48 7382.39 6667.67 4503.58 2999.24 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 288.80 6017.16 1129.65 473.03 656.62 0.00 0.00
February 886.91 4968.90 1840.53 840.63 999.90 0.00 0.00
March 1519.83 4058.15 2421.99 1239.32 1182.67 0.00 0.00
April 2434.96 2662.97 3093.96 1567.06 1526.90 0.00 0.00
May 3838.50 1403.67 3801.48 1813.32 1988.15 0.00 0.00
June 4001.78 1002.62 3668.34 1586.16 2082.18 0.00 0.00
July 4436.02 964.16 3916.31 1820.68 2095.63 0.00 0.00
August 3471.36 1147.86 3222.86 1464.45 1758.41 0.00 0.00
September 2328.23 1615.99 2518.79 1131.66 1387.13 0.00 0.00
October 1020.11 2554.19 1591.14 638.75 952.38 0.00 0.00
November 313.03 3937.31 966.38 325.83 640.55 0.00 0.00
December 140.50 6024.63 861.47 301.52 559.95 0.00 0.00
               
Annual Sum or Average 2063.95 3021.81 2422.60 1101.76 1320.85 0.00 0.00
Minimum of Months 140.50 964.16 861.47 301.52 559.95 0.00 0.00
Maximum of Months 4436.02 6024.63 3916.31 1820.68 2095.63 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1.09 9360.78 764.69 0.00 764.69 0.00 0.00
February 29.50 7596.47 1174.62 0.00 1174.62 0.00 0.00
March 75.36 6009.84 1445.17 0.00 1445.17 0.00 0.00
April 551.59 3516.08 1894.53 14.79 1879.74 0.00 0.00
May 1946.81 1739.29 2664.58 143.48 2521.10 0.00 0.00
June 2866.50 1188.43 2973.72 326.89 2646.83 0.00 0.00
July 2937.03 1089.47 2840.37 243.76 2596.61 0.00 0.00
August 1985.30 1262.92 2157.35 37.05 2120.30 0.00 0.00
September 1017.20 2124.74 1681.16 0.41 1680.75 0.00 0.00
October 225.96 3482.95 1167.31 0.00 1167.31 0.00 0.00
November 28.65 5528.31 772.91 0.00 772.91 0.00 0.00
December 0.00 8941.28 647.91 0.00 647.91 0.00 0.00
               
Annual Sum or Average 978.25 4306.60 1684.57 64.15 1620.42 0.00 0.00
Minimum of Months 0.00 1089.47 647.91 0.00 647.91 0.00 0.00
Maximum of Months 2937.03 9360.78 2973.72 326.89 2646.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 242.37 5597.64 1117.68 466.55 651.12 0.00 0.00
February 727.46 4477.71 1756.33 749.17 1007.16 0.00 0.00
March 1410.79 3607.82 2393.11 1200.42 1192.69 0.00 0.00
April 2648.94 2160.37 3317.55 1789.42 1528.13 0.00 0.00
May 3443.13 1156.44 3590.56 1578.45 2012.11 0.00 0.00
June 4441.23 807.27 4064.76 1944.40 2120.36 0.00 0.00
July 4533.66 725.98 3981.97 1869.68 2112.29 0.00 0.00
August 3302.21 837.42 3070.11 1341.85 1728.26 0.00 0.00
September 2223.16 1353.45 2458.64 1100.48 1358.17 0.00 0.00
October 872.33 2192.76 1488.75 564.53 924.22 0.00 0.00
November 313.75 3393.66 947.75 316.85 630.90 0.00 0.00
December 149.93 5433.79 864.81 319.65 545.16 0.00 0.00
               
Annual Sum or Average 2032.24 2638.15 2423.44 1104.35 1319.09 0.00 0.00
Minimum of Months 149.93 725.98 864.81 316.85 545.16 0.00 0.00
Maximum of Months 4533.66 5597.64 4064.76 1944.40 2120.36 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3459.82 7405.11 5265.71 3663.24 1602.47 0.00 0.00
February 5184.39 6232.65 6667.65 4503.56 2164.09 0.00 0.00
March 4743.60 5285.42 5875.01 3718.06 2156.94 0.00 0.00
April 4845.74 3510.59 5322.57 2888.94 2433.63 0.00 0.00
May 4568.13 1951.25 4474.88 1529.86 2945.03 0.00 0.00
June 4510.70 1321.42 4015.22 1070.23 2944.99 0.00 0.00
July 5222.57 1203.07 4389.94 1390.71 2999.23 0.00 0.00
August 5359.99 1396.17 4688.21 1961.04 2727.16 0.00 0.00
September 5168.70 2220.03 5021.77 2674.47 2347.30 0.00 0.00
October 3734.32 3332.98 4288.24 2522.13 1766.11 0.00 0.00
November 2802.51 4768.93 3819.87 2397.36 1422.52 0.00 0.00
December 2419.98 7246.63 4065.76 2665.97 1399.79 0.00 0.00
               
Annual Sum or Average 4328.09 3812.56 4812.48 2569.89 2242.59 0.00 0.00
Minimum of Months 2419.98 1203.07 3819.87 1070.23 1399.79 0.00 0.00
Maximum of Months 5359.99 7405.11 6667.65 4503.56 2999.23 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 293.09 5834.59 1129.64 473.03 656.61 0.00 0.00
February 901.36 4742.75 1840.52 840.63 999.89 0.00 0.00
March 1545.88 3798.45 2421.98 1239.31 1182.67 0.00 0.00
April 2499.94 2369.04 3093.95 1567.05 1526.89 0.00 0.00
May 3875.98 1311.78 3801.46 1813.32 1988.15 0.00 0.00
June 4058.83 905.53 3668.33 1586.16 2082.17 0.00 0.00
July 4506.90 857.90 3916.29 1820.67 2095.62 0.00 0.00
August 3570.77 956.33 3222.85 1464.44 1758.41 0.00 0.00
September 2378.59 1476.86 2518.78 1131.65 1387.13 0.00 0.00
October 1058.10 2315.19 1591.13 638.75 952.38 0.00 0.00
November 337.76 3541.19 966.37 325.82 640.55 0.00 0.00
December 147.81 5676.81 861.47 301.52 559.95 0.00 0.00
               
Annual Sum or Average 2105.33 2807.83 2422.59 1101.75 1320.84 0.00 0.00
Minimum of Months 147.81 857.90 861.47 301.52 559.95 0.00 0.00
Maximum of Months 4506.90 5834.59 3916.29 1820.67 2095.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1.92 9209.74 764.69 0.00 764.69 0.00 0.00
February 34.21 7410.99 1174.62 0.00 1174.62 0.00 0.00
March 89.96 5767.63 1445.17 0.00 1445.17 0.00 0.00
April 602.71 3242.31 1894.53 14.79 1879.74 0.00 0.00
May 2034.80 1579.92 2664.58 143.48 2521.10 0.00 0.00
June 2951.82 1083.28 2973.72 326.89 2646.83 0.00 0.00
July 3005.78 1003.72 2840.37 243.76 2596.61 0.00 0.00
August 2057.91 1138.64 2157.35 37.05 2120.30 0.00 0.00
September 1097.91 1906.80 1681.16 0.41 1680.75 0.00 0.00
October 272.10 3137.78 1167.31 0.00 1167.31 0.00 0.00
November 32.69 5239.68 772.91 0.00 772.91 0.00 0.00
December 0.00 8766.32 647.91 0.00 647.91 0.00 0.00
               
Annual Sum or Average 1021.50 4110.65 1684.57 64.15 1620.42 0.00 0.00
Minimum of Months 0.00 1003.72 647.91 0.00 647.91 0.00 0.00
Maximum of Months 3005.78 9209.74 2973.72 326.89 2646.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 247.26 5527.20 1117.68 466.55 651.12 0.00 0.00
February 747.44 4364.14 1756.33 749.17 1007.16 0.00 0.00
March 1451.80 3446.15 2393.11 1200.42 1192.69 0.00 0.00
April 2707.52 1994.12 3317.55 1789.42 1528.13 0.00 0.00
May 3489.82 1075.58 3590.56 1578.45 2012.11 0.00 0.00
June 4462.39 755.22 4064.76 1944.40 2120.36 0.00 0.00
July 4542.25 687.80 3981.97 1869.68 2112.29 0.00 0.00
August 3328.02 779.90 3070.11 1341.85 1728.26 0.00 0.00
September 2283.90 1231.71 2458.64 1100.48 1358.17 0.00 0.00
October 931.60 1971.43 1488.75 564.53 924.22 0.00 0.00
November 332.27 3205.22 947.75 316.85 630.90 0.00 0.00
December 154.40 5348.56 864.81 319.65 545.16 0.00 0.00
               
Annual Sum or Average 2063.04 2525.26 2423.44 1104.35 1319.09 0.00 0.00
Minimum of Months 154.40 687.80 864.81 316.85 545.16 0.00 0.00
Maximum of Months 4542.25 5527.20 4064.76 1944.40 2120.36 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3492.93 7240.31 5265.71 3663.24 1602.47 0.00 0.00
February 5232.06 6013.67 6667.65 4503.56 2164.09 0.00 0.00
March 4799.32 5015.31 5875.01 3718.06 2156.94 0.00 0.00
April 4903.46 3229.96 5322.57 2888.94 2433.63 0.00 0.00
May 4619.98 1785.34 4474.88 1529.86 2945.03 0.00 0.00
June 4546.34 1211.27 4015.22 1070.23 2944.99 0.00 0.00
July 5245.85 1114.58 4389.94 1390.71 2999.23 0.00 0.00
August 5392.90 1276.37 4688.21 1961.04 2727.16 0.00 0.00
September 5230.13 2013.86 5021.77 2674.47 2347.30 0.00 0.00
October 3814.62 3002.11 4288.24 2522.13 1766.11 0.00 0.00
November 2862.38 4474.61 3819.87 2397.36 1422.52 0.00 0.00
December 2457.73 7060.22 4065.76 2665.97 1399.79 0.00 0.00
               
Annual Sum or Average 4376.14 3609.85 4812.48 2569.89 2242.59 0.00 0.00
Minimum of Months 2457.73 1114.58 3819.87 1070.23 1399.79 0.00 0.00
Maximum of Months 5392.90 7240.31 6667.65 4503.56 2999.23 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 295.85 5739.77 1129.64 473.03 656.61 0.00 0.00
February 903.92 4626.44 1840.52 840.63 999.89 0.00 0.00
March 1554.94 3649.02 2421.98 1239.31 1182.67 0.00 0.00
April 2515.78 2211.05 3093.95 1567.05 1526.89 0.00 0.00
May 3885.14 1227.07 3801.46 1813.32 1988.15 0.00 0.00
June 4059.26 852.69 3668.33 1586.16 2082.17 0.00 0.00
July 4502.08 815.20 3916.29 1820.67 2095.62 0.00 0.00
August 3574.95 899.84 3222.85 1464.44 1758.41 0.00 0.00
September 2394.83 1369.66 2518.78 1131.65 1387.13 0.00 0.00
October 1079.79 2127.07 1591.13 638.75 952.38 0.00 0.00
November 347.86 3375.30 966.37 325.82 640.55 0.00 0.00
December 149.28 5574.85 861.47 301.52 559.95 0.00 0.00
               
Annual Sum or Average 2112.72 2698.13 2422.59 1101.75 1320.84 0.00 0.00
Minimum of Months 149.28 815.20 861.47 301.52 559.95 0.00 0.00
Maximum of Months 4502.08 5739.77 3916.29 1820.67 2095.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 77469.23 0.253784E+11 0.204816E+10 0.00 0.204816E+10 0.00 0.00
February 38443462.28 0.188283E+11 0.284166E+10 0.00 0.284166E+10 0.00 0.00
March 0.144066E+09 0.167454E+11 0.387076E+10 0.00 0.387076E+10 0.00 0.00
April 0.121261E+10 0.993746E+10 0.491064E+10 38326939.99 0.487231E+10 0.00 0.00
May 0.499761E+10 0.497709E+10 0.713685E+10 0.384309E+09 0.675254E+10 0.00 0.00
June 0.723350E+10 0.331156E+10 0.770791E+10 0.847305E+09 0.686060E+10 0.00 0.00
July 0.766813E+10 0.312476E+10 0.760767E+10 0.652883E+09 0.695479E+10 0.00 0.00
August 0.502378E+10 0.383258E+10 0.577827E+10 99230507.55 0.567904E+10 0.00 0.00
September 0.238447E+10 0.604321E+10 0.435758E+10 1068183.59 0.435651E+10 0.00 0.00
October 0.452295E+09 0.102369E+11 0.312654E+10 0.00 0.312654E+10 0.00 0.00
November 55309730.54 0.155065E+11 0.200339E+10 0.00 0.200339E+10 0.00 0.00
December 0.00 0.245409E+11 0.173536E+10 0.00 0.173536E+10 0.00 0.00
               
Annual Sum or Average 0.292103E+11 0.142463E+12 0.531248E+11 0.202312E+10 0.511017E+11 0.00 0.00
Minimum of Months 0.00 0.312476E+10 0.173536E+10 0.00 0.173536E+10 0.00 0.00
Maximum of Months 0.766813E+10 0.253784E+11 0.770791E+10 0.847305E+09 0.695479E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.651788E+09 0.152288E+11 0.299360E+10 0.124962E+10 0.174398E+10 0.00 0.00
February 0.174080E+10 0.110739E+11 0.424893E+10 0.181240E+10 0.243653E+10 0.00 0.00
March 0.379019E+10 0.991039E+10 0.640974E+10 0.321522E+10 0.319452E+10 0.00 0.00
April 0.691599E+10 0.587409E+10 0.859912E+10 0.463819E+10 0.396093E+10 0.00 0.00
May 0.933716E+10 0.320080E+10 0.961700E+10 0.422774E+10 0.538926E+10 0.00 0.00
June 0.116220E+11 0.217623E+10 0.105359E+11 0.503991E+10 0.549600E+10 0.00 0.00
July 0.122407E+11 0.198442E+10 0.106654E+11 0.500778E+10 0.565758E+10 0.00 0.00
August 0.890879E+10 0.234848E+10 0.822301E+10 0.359403E+10 0.462898E+10 0.00 0.00
September 0.580828E+10 0.367893E+10 0.637283E+10 0.285244E+10 0.352038E+10 0.00 0.00
October 0.232775E+10 0.623944E+10 0.398749E+10 0.151205E+10 0.247544E+10 0.00 0.00
November 0.794007E+09 0.939967E+10 0.245658E+10 0.821291E+09 0.163529E+10 0.00 0.00
December 0.397881E+09 0.149274E+11 0.231633E+10 0.856151E+09 0.146018E+10 0.00 0.00
               
Annual Sum or Average 0.645353E+11 0.860426E+11 0.764259E+11 0.348268E+11 0.415990E+11 0.00 0.00
Minimum of Months 0.397881E+09 0.198442E+10 0.231633E+10 0.821291E+09 0.146018E+10 0.00 0.00
Maximum of Months 0.122407E+11 0.152288E+11 0.106654E+11 0.503991E+10 0.565758E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.938439E+10 0.197730E+11 0.141037E+11 0.981164E+10 0.429208E+10 0.00 0.00
February 0.127280E+11 0.150838E+11 0.161304E+11 0.108951E+11 0.523538E+10 0.00 0.00
March 0.128768E+11 0.142131E+11 0.157357E+11 0.995850E+10 0.577718E+10 0.00 0.00
April 0.126846E+11 0.929828E+10 0.137961E+11 0.748816E+10 0.630799E+10 0.00 0.00
May 0.123539E+11 0.528954E+10 0.119856E+11 0.409758E+10 0.788799E+10 0.00 0.00
June 0.117386E+11 0.352679E+10 0.104075E+11 0.277405E+10 0.763344E+10 0.00 0.00
July 0.140460E+11 0.329667E+10 0.117581E+11 0.372490E+10 0.803316E+10 0.00 0.00
August 0.144164E+11 0.389110E+10 0.125569E+11 0.525247E+10 0.730446E+10 0.00 0.00
September 0.135413E+11 0.581382E+10 0.130165E+11 0.693225E+10 0.608423E+10 0.00 0.00
October 0.100948E+11 0.907423E+10 0.114857E+11 0.675528E+10 0.473037E+10 0.00 0.00
November 0.730430E+10 0.127265E+11 0.990115E+10 0.621397E+10 0.368717E+10 0.00 0.00
December 0.652703E+10 0.195261E+11 0.108898E+11 0.714055E+10 0.374921E+10 0.00 0.00
               
Annual Sum or Average 0.137696E+12 0.121513E+12 0.151767E+12 0.810444E+11 0.707227E+11 0.00 0.00
Minimum of Months 0.652703E+10 0.329667E+10 0.990115E+10 0.277405E+10 0.368717E+10 0.00 0.00
Maximum of Months 0.144164E+11 0.197730E+11 0.161304E+11 0.108951E+11 0.803316E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.773520E+09 0.161164E+11 0.302564E+10 0.126696E+10 0.175868E+10 0.00 0.00
February 0.214562E+10 0.120208E+11 0.445260E+10 0.203365E+10 0.241895E+10 0.00 0.00
March 0.407072E+10 0.108693E+11 0.648706E+10 0.331938E+10 0.316767E+10 0.00 0.00
April 0.631141E+10 0.690243E+10 0.801954E+10 0.406182E+10 0.395772E+10 0.00 0.00
May 0.102810E+11 0.375960E+10 0.101819E+11 0.485680E+10 0.532507E+10 0.00 0.00
June 0.103726E+11 0.259880E+10 0.950834E+10 0.411133E+10 0.539701E+10 0.00 0.00
July 0.118814E+11 0.258241E+10 0.104894E+11 0.487651E+10 0.561294E+10 0.00 0.00
August 0.929769E+10 0.307442E+10 0.863211E+10 0.392238E+10 0.470973E+10 0.00 0.00
September 0.603478E+10 0.418865E+10 0.652870E+10 0.293325E+10 0.359545E+10 0.00 0.00
October 0.273225E+10 0.684114E+10 0.426170E+10 0.171083E+10 0.255087E+10 0.00 0.00
November 0.811373E+09 0.102055E+11 0.250485E+10 0.844541E+09 0.166031E+10 0.00 0.00
December 0.376303E+09 0.161364E+11 0.230737E+10 0.807595E+09 0.149977E+10 0.00 0.00
               
Annual Sum or Average 0.650888E+11 0.952958E+11 0.763992E+11 0.347451E+11 0.416542E+11 0.00 0.00
Minimum of Months 0.376303E+09 0.258241E+10 0.230737E+10 0.807595E+09 0.149977E+10 0.00 0.00
Maximum of Months 0.118814E+11 0.161364E+11 0.104894E+11 0.487651E+10 0.561294E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 2911096.12 0.250719E+11 0.204815E+10 0.00 0.204815E+10 0.00 0.00
February 71357880.51 0.183774E+11 0.284165E+10 0.00 0.284165E+10 0.00 0.00
March 0.201856E+09 0.160968E+11 0.387075E+10 0.00 0.387075E+10 0.00 0.00
April 0.142972E+10 0.911368E+10 0.491062E+10 38326803.89 0.487229E+10 0.00 0.00
May 0.521433E+10 0.465851E+10 0.713682E+10 0.384307E+09 0.675252E+10 0.00 0.00
June 0.742997E+10 0.308041E+10 0.770788E+10 0.847302E+09 0.686058E+10 0.00 0.00
July 0.786654E+10 0.291804E+10 0.760764E+10 0.652880E+09 0.695476E+10 0.00 0.00
August 0.531744E+10 0.338260E+10 0.577825E+10 99230155.17 0.567901E+10 0.00 0.00
September 0.263658E+10 0.550733E+10 0.435757E+10 1068179.80 0.435650E+10 0.00 0.00
October 0.605201E+09 0.932874E+10 0.312653E+10 0.00 0.312653E+10 0.00 0.00
November 74248998.35 0.143294E+11 0.200338E+10 0.00 0.200338E+10 0.00 0.00
December 0.00 0.239483E+11 0.173536E+10 0.00 0.173536E+10 0.00 0.00
               
Annual Sum or Average 0.308501E+11 0.135813E+12 0.531246E+11 0.202311E+10 0.511015E+11 0.00 0.00
Minimum of Months 0.00 0.291804E+10 0.173536E+10 0.00 0.173536E+10 0.00 0.00
Maximum of Months 0.786654E+10 0.250719E+11 0.770788E+10 0.847302E+09 0.695476E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.649162E+09 0.149927E+11 0.299359E+10 0.124962E+10 0.174397E+10 0.00 0.00
February 0.175988E+10 0.108325E+11 0.424892E+10 0.181240E+10 0.243652E+10 0.00 0.00
March 0.377865E+10 0.966319E+10 0.640971E+10 0.321521E+10 0.319451E+10 0.00 0.00
April 0.686606E+10 0.559969E+10 0.859908E+10 0.463817E+10 0.396091E+10 0.00 0.00
May 0.922208E+10 0.309741E+10 0.961696E+10 0.422772E+10 0.538923E+10 0.00 0.00
June 0.115117E+11 0.209246E+10 0.105359E+11 0.503989E+10 0.549598E+10 0.00 0.00
July 0.121430E+11 0.194445E+10 0.106653E+11 0.500776E+10 0.565755E+10 0.00 0.00
August 0.884464E+10 0.224294E+10 0.822298E+10 0.359402E+10 0.462896E+10 0.00 0.00
September 0.576244E+10 0.350813E+10 0.637280E+10 0.285243E+10 0.352037E+10 0.00 0.00
October 0.233644E+10 0.587310E+10 0.398747E+10 0.151204E+10 0.247543E+10 0.00 0.00
November 0.813244E+09 0.879638E+10 0.245657E+10 0.821288E+09 0.163528E+10 0.00 0.00
December 0.401580E+09 0.145539E+11 0.231632E+10 0.856148E+09 0.146017E+10 0.00 0.00
               
Annual Sum or Average 0.640888E+11 0.831968E+11 0.764256E+11 0.348267E+11 0.415989E+11 0.00 0.00
Minimum of Months 0.401580E+09 0.194445E+10 0.231632E+10 0.821288E+09 0.146017E+10 0.00 0.00
Maximum of Months 0.121430E+11 0.149927E+11 0.106653E+11 0.503989E+10 0.565755E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.926678E+10 0.198338E+11 0.141037E+11 0.981161E+10 0.429206E+10 0.00 0.00
February 0.125421E+11 0.150780E+11 0.161304E+11 0.108950E+11 0.523536E+10 0.00 0.00
March 0.127053E+11 0.141565E+11 0.157356E+11 0.995846E+10 0.577716E+10 0.00 0.00
April 0.125602E+11 0.909946E+10 0.137961E+11 0.748814E+10 0.630796E+10 0.00 0.00
May 0.122353E+11 0.522622E+10 0.119855E+11 0.409757E+10 0.788796E+10 0.00 0.00
June 0.116917E+11 0.342513E+10 0.104075E+11 0.277404E+10 0.763341E+10 0.00 0.00
July 0.139881E+11 0.322231E+10 0.117580E+11 0.372488E+10 0.803313E+10 0.00 0.00
August 0.143562E+11 0.373951E+10 0.125569E+11 0.525245E+10 0.730444E+10 0.00 0.00
September 0.133973E+11 0.575432E+10 0.130164E+11 0.693222E+10 0.608420E+10 0.00 0.00
October 0.100020E+11 0.892707E+10 0.114856E+11 0.675526E+10 0.473035E+10 0.00 0.00
November 0.726411E+10 0.123611E+11 0.990111E+10 0.621395E+10 0.368716E+10 0.00 0.00
December 0.648167E+10 0.194094E+11 0.108897E+11 0.714052E+10 0.374920E+10 0.00 0.00
               
Annual Sum or Average 0.136491E+12 0.120233E+12 0.151767E+12 0.810441E+11 0.707224E+11 0.00 0.00
Minimum of Months 0.648167E+10 0.322231E+10 0.990111E+10 0.277404E+10 0.368716E+10 0.00 0.00
Maximum of Months 0.143562E+11 0.198338E+11 0.161304E+11 0.108950E+11 0.803313E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.785001E+09 0.156274E+11 0.302563E+10 0.126696E+10 0.175867E+10 0.00 0.00
February 0.218057E+10 0.114737E+11 0.445258E+10 0.203364E+10 0.241894E+10 0.00 0.00
March 0.414048E+10 0.101738E+11 0.648703E+10 0.331937E+10 0.316766E+10 0.00 0.00
April 0.647984E+10 0.614055E+10 0.801951E+10 0.406180E+10 0.395770E+10 0.00 0.00
May 0.103814E+11 0.351347E+10 0.101818E+11 0.485678E+10 0.532505E+10 0.00 0.00
June 0.105205E+11 0.234714E+10 0.950830E+10 0.411132E+10 0.539699E+10 0.00 0.00
July 0.120713E+11 0.229781E+10 0.104894E+11 0.487649E+10 0.561292E+10 0.00 0.00
August 0.956394E+10 0.256143E+10 0.863208E+10 0.392237E+10 0.470971E+10 0.00 0.00
September 0.616530E+10 0.382803E+10 0.652868E+10 0.293324E+10 0.359544E+10 0.00 0.00
October 0.283401E+10 0.620100E+10 0.426168E+10 0.171083E+10 0.255086E+10 0.00 0.00
November 0.875476E+09 0.917875E+10 0.250484E+10 0.844538E+09 0.166030E+10 0.00 0.00
December 0.395905E+09 0.152048E+11 0.230736E+10 0.807592E+09 0.149977E+10 0.00 0.00
               
Annual Sum or Average 0.663937E+11 0.885477E+11 0.763989E+11 0.347449E+11 0.416540E+11 0.00 0.00
Minimum of Months 0.395905E+09 0.229781E+10 0.230736E+10 0.807592E+09 0.149977E+10 0.00 0.00
Maximum of Months 0.120713E+11 0.156274E+11 0.104894E+11 0.487649E+10 0.561292E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 5147764.17 0.246674E+11 0.204815E+10 0.00 0.204815E+10 0.00 0.00
February 82759066.79 0.179287E+11 0.284165E+10 0.00 0.284165E+10 0.00 0.00
March 0.240959E+09 0.154480E+11 0.387075E+10 0.00 0.387075E+10 0.00 0.00
April 0.156223E+10 0.840406E+10 0.491062E+10 38326803.89 0.487229E+10 0.00 0.00
May 0.545001E+10 0.423164E+10 0.713682E+10 0.384307E+09 0.675252E+10 0.00 0.00
June 0.765112E+10 0.280786E+10 0.770788E+10 0.847302E+09 0.686058E+10 0.00 0.00
July 0.805069E+10 0.268835E+10 0.760764E+10 0.652880E+09 0.695476E+10 0.00 0.00
August 0.551191E+10 0.304973E+10 0.577825E+10 99230155.17 0.567901E+10 0.00 0.00
September 0.284578E+10 0.494243E+10 0.435757E+10 1068179.80 0.435650E+10 0.00 0.00
October 0.728804E+09 0.840424E+10 0.312653E+10 0.00 0.312653E+10 0.00 0.00
November 84721079.64 0.135812E+11 0.200338E+10 0.00 0.200338E+10 0.00 0.00
December 0.00 0.234797E+11 0.173536E+10 0.00 0.173536E+10 0.00 0.00
               
Annual Sum or Average 0.322141E+11 0.129633E+12 0.531246E+11 0.202311E+10 0.511015E+11 0.00 0.00
Minimum of Months 0.00 0.268835E+10 0.173536E+10 0.00 0.173536E+10 0.00 0.00
Maximum of Months 0.805069E+10 0.246674E+11 0.770788E+10 0.847302E+09 0.695476E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.662251E+09 0.148041E+11 0.299359E+10 0.124962E+10 0.174397E+10 0.00 0.00
February 0.180819E+10 0.105577E+11 0.424892E+10 0.181240E+10 0.243652E+10 0.00 0.00
March 0.388849E+10 0.923018E+10 0.640971E+10 0.321521E+10 0.319451E+10 0.00 0.00
April 0.701788E+10 0.516876E+10 0.859908E+10 0.463817E+10 0.396091E+10 0.00 0.00
May 0.934713E+10 0.288083E+10 0.961696E+10 0.422772E+10 0.538923E+10 0.00 0.00
June 0.115665E+11 0.195754E+10 0.105359E+11 0.503989E+10 0.549598E+10 0.00 0.00
July 0.121660E+11 0.184220E+10 0.106653E+11 0.500776E+10 0.565755E+10 0.00 0.00
August 0.891376E+10 0.208887E+10 0.822298E+10 0.359402E+10 0.462896E+10 0.00 0.00
September 0.591987E+10 0.319259E+10 0.637280E+10 0.285243E+10 0.352037E+10 0.00 0.00
October 0.249520E+10 0.528028E+10 0.398747E+10 0.151204E+10 0.247543E+10 0.00 0.00
November 0.861238E+09 0.830793E+10 0.245657E+10 0.821288E+09 0.163528E+10 0.00 0.00
December 0.413544E+09 0.143256E+11 0.231632E+10 0.856148E+09 0.146017E+10 0.00 0.00
               
Annual Sum or Average 0.650600E+11 0.796366E+11 0.764256E+11 0.348267E+11 0.415989E+11 0.00 0.00
Minimum of Months 0.413544E+09 0.184220E+10 0.231632E+10 0.821288E+09 0.146017E+10 0.00 0.00
Maximum of Months 0.121660E+11 0.148041E+11 0.106653E+11 0.503989E+10 0.565755E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.935545E+10 0.193925E+11 0.141037E+11 0.981161E+10 0.429206E+10 0.00 0.00
February 0.126574E+11 0.145483E+11 0.161304E+11 0.108950E+11 0.523536E+10 0.00 0.00
March 0.128545E+11 0.134330E+11 0.157356E+11 0.995846E+10 0.577716E+10 0.00 0.00
April 0.127098E+11 0.837204E+10 0.137961E+11 0.748814E+10 0.630796E+10 0.00 0.00
May 0.123741E+11 0.478186E+10 0.119855E+11 0.409757E+10 0.788796E+10 0.00 0.00
June 0.117841E+11 0.313961E+10 0.104075E+11 0.277404E+10 0.763341E+10 0.00 0.00
July 0.140505E+11 0.298528E+10 0.117580E+11 0.372488E+10 0.803313E+10 0.00 0.00
August 0.144444E+11 0.341862E+10 0.125569E+11 0.525245E+10 0.730444E+10 0.00 0.00
September 0.135565E+11 0.521992E+10 0.130164E+11 0.693222E+10 0.608420E+10 0.00 0.00
October 0.102171E+11 0.804085E+10 0.114856E+11 0.675526E+10 0.473035E+10 0.00 0.00
November 0.741928E+10 0.115982E+11 0.990111E+10 0.621395E+10 0.368716E+10 0.00 0.00
December 0.658279E+10 0.189101E+11 0.108897E+11 0.714052E+10 0.374920E+10 0.00 0.00
               
Annual Sum or Average 0.138006E+12 0.113840E+12 0.151767E+12 0.810441E+11 0.707224E+11 0.00 0.00
Minimum of Months 0.658279E+10 0.298528E+10 0.990111E+10 0.277404E+10 0.368716E+10 0.00 0.00
Maximum of Months 0.144444E+11 0.193925E+11 0.161304E+11 0.108950E+11 0.803313E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.792400E+09 0.153734E+11 0.302563E+10 0.126696E+10 0.175867E+10 0.00 0.00
February 0.218676E+10 0.111923E+11 0.445258E+10 0.203364E+10 0.241894E+10 0.00 0.00
March 0.416474E+10 0.977353E+10 0.648703E+10 0.331937E+10 0.316766E+10 0.00 0.00
April 0.652090E+10 0.573103E+10 0.801951E+10 0.406180E+10 0.395770E+10 0.00 0.00
May 0.104060E+11 0.328658E+10 0.101818E+11 0.485678E+10 0.532505E+10 0.00 0.00
June 0.105216E+11 0.221016E+10 0.950830E+10 0.411132E+10 0.539699E+10 0.00 0.00
July 0.120584E+11 0.218343E+10 0.104894E+11 0.487649E+10 0.561292E+10 0.00 0.00
August 0.957515E+10 0.241012E+10 0.863208E+10 0.392237E+10 0.470971E+10 0.00 0.00
September 0.620740E+10 0.355015E+10 0.652868E+10 0.293324E+10 0.359544E+10 0.00 0.00
October 0.289210E+10 0.569714E+10 0.426168E+10 0.171083E+10 0.255086E+10 0.00 0.00
November 0.901645E+09 0.874877E+10 0.250484E+10 0.844538E+09 0.166030E+10 0.00 0.00
December 0.399833E+09 0.149317E+11 0.230736E+10 0.807592E+09 0.149977E+10 0.00 0.00
               
Annual Sum or Average 0.666269E+11 0.850883E+11 0.763989E+11 0.347449E+11 0.416540E+11 0.00 0.00
Minimum of Months 0.399833E+09 0.218343E+10 0.230736E+10 0.807592E+09 0.149977E+10 0.00 0.00
Maximum of Months 0.120584E+11 0.153734E+11 0.104894E+11 0.487649E+10 0.561292E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January -16.9 -17.4 -20.0 3.73 -31.9 33.25 98.18 0.00
February -11.6 -12.7 -16.7 4.33 -26.7 48.91 138.70 0.00
March -6.2 -7.6 -10.8 3.55 -19.4 56.69 163.76 0.01
April 3.97 0.41 -4.8 4.72 -9.1 70.41 207.70 0.01
May 13.43 8.45 3.53 3.60 2.20 102.27 202.62 0.00
June 18.03 14.19 11.55 3.74 7.84 104.36 210.60 0.06
July 19.67 16.51 14.78 3.14 8.97 101.67 223.82 0.04
August 17.94 15.20 13.59 3.45 8.99 87.39 175.79 0.04
September 12.29 9.87 7.80 3.78 3.34 70.27 143.96 0.00
October 5.42 3.47 1.07 3.53 -4.7 51.74 90.11 0.00
November -2.0 -3.6 -6.9 4.42 -13.7 34.68 65.95 0.00
December -14.6 -15.1 -18.1 3.91 -28.3 29.58 68.99 0.00
                 
Annual Sum or Average 3.36 1.04 -2.0 3.82 -8.4 66.03 149.18 0.01
Minimum of Months -16.9 -17.4 -20.0 3.14 -31.9 29.58 65.95 0.00
Maximum of Months 19.67 16.51 14.78 4.72 8.99 104.36 223.82 0.06



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 1.10 29-JAN-14:00 -1.0 -4.4 2.60 -11.4 145.00 110.00
February 8.90 20-FEB-15:00 2.87 -6.7 8.80 -9.0 49.00 646.00
March 11.10 26-MAR-15:00 5.48 -1.1 5.20 -5.7 53.00 842.00
April 26.70 23-APR-15:00 16.95 11.10 11.30 12.03 75.50 811.00
May 29.40 25-MAY-17:00 19.26 13.90 1.50 16.49 47.50 582.00
June 35.00 29-JUN-15:00 24.72 21.10 6.70 24.66 132.00 705.00
July 31.10 15-JUL-14:20 25.35 23.33 8.07 19.93 299.67 518.33
August 30.60 08-AUG-14:00 23.36 20.60 6.70 17.93 163.50 672.50
September 26.10 01-SEP-14:00 17.82 13.30 3.60 14.28 112.00 751.50
October 22.20 19-OCT-14:00 13.62 7.20 6.70 8.15 35.50 701.50
November 18.30 01-NOV-14:00 13.44 10.00 3.10 11.84 105.00 30.50
December 1.10 28-DEC-02:00 0.43 -0.6 4.60 -5.5 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 1.10   -1.0 -6.7 1.50 -11.4 0.00 0.00
Maximum of Months 35.00   25.35 23.33 11.30 24.66 299.67 842.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -35.6 06-JAN-08:00 -35.7 -37.8 0.00 -57.8 27.00 381.00
February -33.3 14-FEB-06:00 -33.4 -36.7 0.00 -55.6 0.00 0.00
March -28.9 05-MAR-06:00 -29.1 -32.2 1.50 -50.6 27.00 41.50
April -13.9 05-APR-05:00 -14.4 -16.1 0.00 -32.5 14.50 199.00
May -3.9 01-MAY-05:00 -6.2 -12.2 0.00 -22.4 35.00 415.00
June 1.10 04-JUN-04:00 0.62 0.00 0.00 -14.9 37.00 169.50
July 6.10 02-JUL-04:00 6.10 6.10 0.00 -8.8 33.50 204.50
August 4.40 19-AUG-03:00 4.40 4.40 0.00 -10.7 0.00 0.00
September 1.10 06-SEP-03:00 1.10 1.10 0.00 -14.7 0.00 0.00
October -10.0 30-OCT-03:00 -10.7 -12.8 1.50 -28.2 0.00 0.00
November -20.6 29-NOV-05:00 -20.8 -22.2 2.10 -37.8 0.00 0.00
December -31.1 24-DEC-06:19 -31.3 -35.1 3.33 -53.1 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -35.6   -35.7 -37.8 0.00 -57.8 0.00 0.00
Maximum of Months 6.10   6.10 6.10 3.33 -8.8 37.00 415.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -0.5 16-JAN-12:00 0.00 -1.1 5.70 -6.6 172.50 3.00
February 3.34 21-FEB-12:00 6.70 -1.1 7.70 -6.0 270.00 303.00
March 5.48 26-MAR-15:00 11.10 -1.1 5.20 -5.7 53.00 842.00
April 16.95 23-APR-15:00 26.70 11.10 11.30 12.03 75.50 811.00
May 19.91 26-MAY-11:00 25.60 17.20 6.20 22.64 300.50 6.00
June 24.72 29-JUN-15:00 35.00 21.10 6.70 24.66 132.00 705.00
July 25.76 15-JUL-13:00 31.10 23.90 7.70 18.99 333.00 421.00
August 23.36 08-AUG-14:00 30.60 20.60 6.70 17.93 163.50 672.50
September 18.67 01-SEP-00:00 19.00 17.50 2.80 16.30 0.00 0.00
October 13.72 19-OCT-13:00 21.70 7.80 5.70 7.75 54.50 739.00
November 14.29 21-NOV-12:00 15.00 13.90 5.20 11.46 134.50 25.50
December 0.43 28-DEC-02:00 1.10 -0.6 4.60 -5.5 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -0.5   0.00 -1.1 2.80 -6.6 0.00 0.00
Maximum of Months 25.76   35.00 23.90 11.30 24.66 333.00 842.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -1.1 16-JAN-11:00 -0.6 -0.8 5.70 -7.3 164.50 5.00
February -0.6 21-FEB-08:00 4.40 2.25 8.80 -6.6 123.00 89.50
March 0.00 29-MAR-20:00 1.70 0.95 1.50 -4.8 0.00 0.00
April 11.10 23-APR-13:00 24.40 16.08 10.80 9.72 98.50 903.50
May 17.20 26-MAY-11:00 25.60 19.91 6.20 22.64 300.50 6.00
June 22.80 29-JUN-23:19 26.30 23.71 5.20 14.28 0.00 0.00
July 23.90 15-JUL-13:00 31.10 25.76 7.70 18.99 333.00 421.00
August 20.60 08-AUG-14:00 30.60 23.36 6.70 17.93 163.50 672.50
September 17.92 01-SEP-00:10 19.75 18.15 3.22 13.23 0.00 0.00
October 12.20 07-OCT-12:20 14.47 13.17 3.43 9.20 163.17 18.50
November 13.90 21-NOV-12:00 15.00 14.29 5.20 11.46 134.50 25.50
December -0.0 05-DEC-17:00 0.00 -0.0 1.50 -6.4 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -1.1   -0.6 -0.8 1.50 -7.3 0.00 0.00
Maximum of Months 23.90   31.10 25.76 10.80 22.64 333.00 903.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 1.89 11.66 0.00
February 18.00 13.00 16.00 0.58 19.92 0.00
March 18.00 13.00 16.00 0.81 26.63 0.00
April 18.00 13.00 16.00 2.58 37.52 0.00
May 18.00 13.00 16.00 5.43 45.25 0.00
June 18.00 13.00 16.00 8.61 47.76 0.00
July 18.00 13.00 16.00 11.25 48.86 0.00
August 18.00 13.00 16.00 12.66 38.94 0.00
September 18.00 13.00 16.00 12.41 29.23 0.00
October 18.00 13.00 16.00 10.60 17.37 0.00
November 18.00 13.00 16.00 7.72 10.89 0.00
December 18.00 13.00 16.00 4.55 9.11 0.00
             
Annual Sum or Average 18.00 13.00 16.00 6.63 28.63 0.00
Minimum of Months 18.00 13.00 16.00 0.58 9.11 0.00
Maximum of Months 18.00 13.00 16.00 12.66 48.86 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.467235E+11 -0.462454E+11 0.00 0.00 744.00 0.00 -478079936.6 60.05 0.00 0.00
February 0.433902E+11 -0.429664E+11 0.00 0.00 672.00 0.00 -423755389.3 60.05 0.00 0.00
March 0.508126E+11 -0.503523E+11 0.00 0.00 744.00 0.00 -460335531.3 60.05 0.00 0.00
April 0.447371E+11 -0.443016E+11 0.00 0.00 720.00 0.00 -435590137.1 60.05 0.00 0.00
May 0.454304E+11 -0.449826E+11 0.00 0.00 744.00 0.00 -447751808.3 60.05 0.00 0.00
June 0.424110E+11 -0.419792E+11 0.00 0.00 720.00 0.00 -431874345.5 60.05 0.00 0.00
July 0.382943E+11 -0.378517E+11 0.00 0.00 744.00 0.00 -442606403.7 60.05 0.00 0.00
August 0.407234E+11 -0.402787E+11 0.00 0.00 744.00 0.00 -444650471.9 60.05 0.00 0.00
September 0.371525E+11 -0.367204E+11 0.00 0.00 720.00 0.00 -432147233.6 60.05 0.00 0.00
October 0.397766E+11 -0.393298E+11 0.00 0.00 744.00 0.00 -446894983.9 60.05 0.00 0.00
November 0.412547E+11 -0.408194E+11 0.00 0.00 720.00 0.00 -435277183.0 60.05 0.00 0.00
December 0.435331E+11 -0.430645E+11 0.00 0.00 744.00 0.00 -468627884.5 60.05 0.00 0.00
                     
Annual Sum or Average 0.514240E+12 -0.508892E+12 0.00 0.00 8760.00 0.00 -0.534759E+10 60.05 0.00 0.00
Minimum of Months 0.371525E+11 -0.503523E+11 0.00 0.00 672.00 0.00 -478079936.6 60.05 0.00 0.00
Maximum of Months 0.508126E+11 -0.367204E+11 0.00 0.00 744.00 0.00 -423755389.3 60.05 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: Environment

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME []
January 243.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 265.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 254.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 296.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 437.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 401.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 409.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 352.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 344.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 299.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 255.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 226.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average 3785.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 226.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 437.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.527659E+11 83187.48 06-JAN-08:13 0.00 0.00 0.00 0.00 0.00
February 0.286564E+11 77060.03 14-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.131319E+11 54855.02 15-MAR-06:51 0.00 0.00 0.00 0.00 0.00
April 0.742184E+09 30332.99 05-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 15331415.47 7318.26 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.276885E+09 22834.84 30-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.546742E+10 44230.47 25-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.367165E+11 69021.98 20-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.137772E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.527659E+11 83187.48   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.241226E+09 36639.37 02-JAN-06:14 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:01 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:01 0.00 0.00 0.00 0.00 0.00
December 2800876.28 3099.64 26-DEC-06:11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.244027E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.241226E+09 36639.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.131223E+11 24768.53 02-JAN-05:04 0.00 0.00 0.00 0.00 0.00
February 0.741720E+10 24656.52 06-FEB-05:03 0.00 0.00 0.00 0.00 0.00
March 0.433357E+10 24655.38 06-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.651497E+09 26348.42 07-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 10543763.32 4860.15 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 19548813.38 1330.14 23-SEP-05:25 0.00 0.00 0.00 0.00 0.00
October 0.504308E+09 24422.05 30-OCT-04:31 0.00 0.00 0.00 0.00 0.00
November 0.252664E+10 25737.35 17-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.962750E+10 24662.57 01-DEC-05:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.382131E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.131223E+11 26348.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.101692E+11 23419.91 23-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.590405E+10 23427.88 06-FEB-05:22 0.00 0.00 0.00 0.00 0.00
March 0.410978E+10 23421.82 08-MAR-05:22 0.00 0.00 0.00 0.00 0.00
April 0.108895E+10 23770.54 07-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 83836724.57 9009.69 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 9266586.23 2678.39 10-JUN-05:05 0.00 0.00 0.00 0.00 0.00
July 1215024.45 278.48 08-JUL-05:52 0.00 0.00 0.00 0.00 0.00
August 13814640.72 5790.93 19-AUG-05:03 0.00 0.00 0.00 0.00 0.00
September 0.295601E+09 6939.09 06-SEP-05:02 0.00 0.00 0.00 0.00 0.00
October 0.131252E+10 23376.58 30-OCT-04:31 0.00 0.00 0.00 0.00 0.00
November 0.329956E+10 23427.77 27-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.863222E+10 23426.52 01-DEC-05:22 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.349200E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1215024.45 278.48   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.101692E+11 23770.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.112618E+11 32812.47 25-JAN-04:02 0.00 0.00 0.00 0.00 0.00
February 0.644193E+10 32820.73 18-FEB-05:22 0.00 0.00 0.00 0.00 0.00
March 0.487510E+10 32804.04 10-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.151860E+10 33280.79 07-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.249865E+09 30705.86 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 6232190.38 3187.51 03-JUN-05:06 0.00 0.00 0.00 0.00 0.00
July 31883.04 531.38 10-JUL-05:02 0.00 0.00 0.00 0.00 0.00
August 15840847.23 7830.97 19-AUG-05:03 0.00 0.00 0.00 0.00 0.00
September 0.315102E+09 13671.18 13-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.150112E+10 32844.41 30-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.378000E+10 32823.92 24-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.968026E+10 32817.54 18-DEC-04:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.396459E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 31883.04 531.38   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.112618E+11 33280.79   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.824069E+10 24203.97 23-JAN-05:02 0.00 0.00 0.00 0.00 0.00
February 0.468747E+10 24209.33 06-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.257389E+10 24204.30 06-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.294530E+09 22436.17 04-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 50845703.40 3777.87 10-MAY-05:08 0.00 0.00 0.00 0.00 0.00
June 101117.22 1225.17 10-JUN-05:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.118967E+09 3906.37 28-SEP-05:08 0.00 0.00 0.00 0.00 0.00
October 0.727046E+09 24153.81 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.191998E+10 24203.82 25-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.488572E+10 24203.28 13-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.234992E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.824069E+10 24209.33   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.612956E+12 894716.54 06-JAN-08:35 0.00 0.00 0.00 0.00 0.00
February 0.368773E+12 840589.32 14-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.218089E+12 1038447.05 23-MAR-13:19 0.00 0.00 0.00 0.00 0.00
April 0.244184E+11 764648.51 28-APR-13:18 0.00 0.00 0.00 0.00 0.00
May 0.163944E+10 557817.30 08-MAY-09:58 0.00 0.00 0.00 0.00 0.00
June 2418008.80 40300.15 09-JUN-13:15 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 7228207.27 43236.54 18-AUG-09:58 0.00 0.00 0.00 0.00 0.00
September 0.559928E+09 392372.38 27-SEP-13:45 0.00 0.00 0.00 0.00 0.00
October 0.943906E+10 491653.70 25-OCT-09:27 0.00 0.00 0.00 0.00 0.00
November 0.120028E+12 722174.44 16-NOV-10:09 0.00 0.00 0.00 0.00 0.00
December 0.504185E+12 772896.83 20-DEC-08:61 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.186010E+13     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.612956E+12 1038447.05   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.378663E+11 719505.20 03-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.111750E+11 719197.32 28-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.407958E+10 718862.69 07-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:01 0.00 0.00 0.00 0.00 0.00
November 0.942859E+10 719551.44 28-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.207808E+11 719373.01 27-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.833303E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.378663E+11 719551.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.235110E+12 330640.49 30-JAN-05:13 0.00 0.00 0.00 0.00 0.00
February 0.160589E+12 328595.71 17-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.115430E+12 328656.48 06-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.414532E+11 327325.61 03-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.489772E+10 322162.05 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.252416E+09 69798.52 10-JUN-05:03 0.00 0.00 0.00 0.00 0.00
July 66150945.90 13389.08 08-JUL-05:08 0.00 0.00 0.00 0.00 0.00
August 0.746100E+09 93695.22 19-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.928154E+10 279212.07 13-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.393194E+11 328123.39 30-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.100550E+12 329770.56 27-NOV-05:23 0.00 0.00 0.00 0.00 0.00
December 0.215673E+12 328651.33 11-DEC-05:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.923368E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 66150945.90 13389.08   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.235110E+12 330640.49   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.144304E+12 273244.32 23-JAN-05:04 0.00 0.00 0.00 0.00 0.00
February 0.935260E+11 273048.90 27-FEB-05:42 0.00 0.00 0.00 0.00 0.00
March 0.658548E+11 272670.37 20-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.235170E+11 271655.87 04-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.356155E+10 227036.91 09-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.737009E+09 68075.33 10-JUN-05:02 0.00 0.00 0.00 0.00 0.00
July 0.298947E+09 46082.91 08-JUL-05:04 0.00 0.00 0.00 0.00 0.00
August 0.160015E+10 96877.40 19-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.883384E+10 220266.28 13-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.300885E+11 272636.59 30-OCT-04:22 0.00 0.00 0.00 0.00 0.00
November 0.667450E+11 273241.64 13-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.136181E+12 273060.85 18-DEC-05:52 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.575248E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.298947E+09 46082.91   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144304E+12 273244.32   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.162076E+12 355558.97 23-JAN-05:04 0.00 0.00 0.00 0.00 0.00
February 0.983019E+11 354325.30 27-FEB-05:42 0.00 0.00 0.00 0.00 0.00
March 0.750400E+11 355787.38 06-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.305052E+11 354017.13 04-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.525922E+10 333501.37 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.894517E+09 69172.19 10-JUN-05:03 0.00 0.00 0.00 0.00 0.00
July 0.181767E+09 25190.86 10-JUL-05:07 0.00 0.00 0.00 0.00 0.00
August 0.965687E+09 72767.12 19-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.744031E+10 294797.84 13-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.290712E+11 355026.80 30-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.735083E+11 356894.34 27-NOV-05:23 0.00 0.00 0.00 0.00 0.00
December 0.160423E+12 355644.90 18-DEC-05:14 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.643668E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.181767E+09 25190.86   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.162076E+12 356894.34   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.149200E+12 284000.76 11-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.974117E+11 283985.91 27-FEB-05:42 0.00 0.00 0.00 0.00 0.00
March 0.722822E+11 283425.10 02-MAR-05:22 0.00 0.00 0.00 0.00 0.00
April 0.292126E+11 282584.90 04-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.558987E+10 236154.79 09-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.164758E+10 53064.66 14-JUN-05:02 0.00 0.00 0.00 0.00 0.00
July 0.399312E+09 23389.73 18-JUL-05:06 0.00 0.00 0.00 0.00 0.00
August 0.186296E+10 60099.62 19-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.105408E+11 228304.14 13-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.335243E+11 283535.11 30-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.712384E+11 283422.43 28-NOV-05:32 0.00 0.00 0.00 0.00 0.00
December 0.134924E+12 284005.08 18-DEC-05:52 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.607833E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.399312E+09 23389.73   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.149200E+12 284005.08   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.697185E+11 87143.04 09-JAN-07:15 0.00 0.00 0.00 0.00 0.00
February 0.411099E+11 84109.48 14-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.223785E+11 67908.28 16-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.281234E+10 43942.28 05-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 75839971.75 19496.42 01-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 5491844.19 3318.64 06-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 0.158879E+10 36247.61 30-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.143096E+11 58426.80 25-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.592864E+11 82578.15 20-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.211285E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.697185E+11 87143.04   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.357230E+11 138213.77 17-JAN-04:03 0.00 0.00 0.00 0.00 0.00
February 0.233741E+11 138430.06 22-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.167272E+11 138229.06 27-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.633677E+10 137819.81 03-APR-04:13 0.00 0.00 0.00 0.00 0.00
May 0.830871E+09 135507.61 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 2394236.11 3537.38 05-JUN-05:53 0.00 0.00 0.00 0.00 0.00
July 29254312.45 15464.98 10-JUL-05:08 0.00 0.00 0.00 0.00 0.00
August 42750544.46 55572.07 19-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.682149E+09 112256.07 23-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.716279E+10 138257.62 30-OCT-03:13 0.00 0.00 0.00 0.00 0.00
November 0.165032E+11 138236.75 06-NOV-05:03 0.00 0.00 0.00 0.00 0.00
December 0.317084E+11 138000.83 07-DEC-05:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.139123E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2394236.11 3537.38   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.357230E+11 138430.06   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.344694E+11 43804.38 28-JAN-04:02 0.00 0.00 0.00 0.00 0.00
February 0.257539E+11 43926.28 22-FEB-05:32 0.00 0.00 0.00 0.00 0.00
March 0.206914E+11 44024.20 20-MAR-03:02 0.00 0.00 0.00 0.00 0.00
April 0.985767E+10 43887.83 04-APR-04:23 0.00 0.00 0.00 0.00 0.00
May 0.244392E+10 42879.80 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.629927E+09 33925.30 10-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 0.322981E+09 17862.76 10-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.994608E+09 35069.39 19-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.394330E+10 37534.01 07-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.103285E+11 43594.30 06-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.190449E+11 43811.92 08-NOV-05:13 0.00 0.00 0.00 0.00 0.00
December 0.330170E+11 43831.35 25-DEC-08:42 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.161498E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.322981E+09 17862.76   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.344694E+11 44024.20   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.213903E+11 29926.49 31-JAN-05:32 0.00 0.00 0.00 0.00 0.00
February 0.150643E+11 30008.23 22-FEB-05:32 0.00 0.00 0.00 0.00 0.00
March 0.112738E+11 30077.77 04-MAR-05:52 0.00 0.00 0.00 0.00 0.00
April 0.474740E+10 30066.65 04-APR-04:23 0.00 0.00 0.00 0.00 0.00
May 0.105017E+10 28897.77 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.256021E+09 22854.04 10-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 0.150838E+09 12522.87 10-JUL-04:11 0.00 0.00 0.00 0.00 0.00
August 0.486615E+09 23626.53 19-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.207864E+10 25289.55 07-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.624246E+10 29889.20 06-OCT-04:42 0.00 0.00 0.00 0.00 0.00
November 0.118506E+11 29985.76 07-NOV-05:42 0.00 0.00 0.00 0.00 0.00
December 0.209173E+11 30021.92 29-DEC-05:42 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.955085E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.150838E+09 12522.87   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.213903E+11 30077.77   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.256926E+11 44561.49 31-JAN-05:32 0.00 0.00 0.00 0.00 0.00
February 0.175093E+11 44689.94 22-FEB-05:32 0.00 0.00 0.00 0.00 0.00
March 0.144248E+11 44625.72 04-MAR-05:52 0.00 0.00 0.00 0.00 0.00
April 0.731693E+10 44650.82 04-APR-04:23 0.00 0.00 0.00 0.00 0.00
May 0.215540E+10 43625.28 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.885958E+09 35352.95 03-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 0.475740E+09 34605.81 10-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.867951E+09 35679.08 19-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.298359E+10 38186.54 07-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.789903E+10 44352.20 06-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.147475E+11 44558.30 29-NOV-05:53 0.00 0.00 0.00 0.00 0.00
December 0.261654E+11 44565.98 01-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.121124E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.475740E+09 34605.81   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.261654E+11 44689.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.206934E+11 33765.76 12-JAN-05:04 0.00 0.00 0.00 0.00 0.00
February 0.142070E+11 33764.03 13-FEB-03:12 0.00 0.00 0.00 0.00 0.00
March 0.110253E+11 33775.98 02-MAR-05:52 0.00 0.00 0.00 0.00 0.00
April 0.516330E+10 33630.03 05-APR-03:11 0.00 0.00 0.00 0.00 0.00
May 0.147446E+10 31443.95 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.571080E+09 18856.96 10-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 0.263241E+09 6622.90 18-JUL-05:03 0.00 0.00 0.00 0.00 0.00
August 0.617170E+09 25679.99 19-AUG-05:01 0.00 0.00 0.00 0.00 0.00
September 0.239168E+10 26268.98 13-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.591850E+10 33718.15 30-OCT-04:32 0.00 0.00 0.00 0.00 0.00
November 0.109898E+11 33776.55 28-NOV-05:52 0.00 0.00 0.00 0.00 0.00
December 0.191812E+11 33772.23 16-DEC-05:53 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.924962E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.263241E+09 6622.90   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.206934E+11 33776.55   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.110469E+11 186541.79 06-JAN-07:43 0.00 0.00 0.00 0.00 0.00
February 0.150776E+10 184165.54 14-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 9182823.29 7765.50 16-MAR-06:11 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:01 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:01 0.00 0.00 0.00 0.00 0.00
December 0.142412E+10 27955.92 20-DEC-07:26 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.139880E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.110469E+11 186541.79   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:01 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:01 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:01 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:01 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:01 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:01 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:01 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:01 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:01 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 288.56 288.56 0.48 02-JAN-04:30 0.48 0.00
February 0.00 0.00 3610.96 3610.96 0.94 06-FEB-04:01 0.94 0.00
March 0.00 0.00 278.72 278.72 0.85 26-MAR-11:09 0.85 0.00
April 0.00 0.00 0.572825E+10 0.572825E+10 130055.91 23-APR-15:11 130055.91 0.01
May 0.00 0.00 0.459015E+11 0.450256E+11 155114.15 25-MAY-15:00 141105.96 0.18
June 0.00 0.00 0.104210E+12 0.846726E+11 232922.76 30-JUN-05:02 162044.20 0.41
July 0.00 0.00 0.140679E+12 0.110014E+12 345221.92 05-JUL-10:32 122594.09 0.59
August 0.00 0.00 0.112835E+12 0.860685E+11 244247.05 31-AUG-12:40 112154.68 0.58
September 0.00 0.00 0.242210E+11 0.216531E+11 162304.66 01-SEP-11:00 115217.53 0.13
October 0.00 0.00 0.398972E+10 0.398972E+10 90498.14 19-OCT-15:00 90498.14 0.01
November 0.00 0.00 0.559479E+09 0.559479E+09 31145.94 01-NOV-14:53 31145.94 0.01
December 0.00 0.00 1062893.78 1062893.78 3541.92 05-DEC-17:05 3541.92 0.00
                 
Annual Sum or Average 0.00 0.00 0.438125E+12 0.357712E+12       0.16
Minimum of Months 0.00 0.00 278.72 278.72 0.48   0.48 0.00
Maximum of Months 0.00 0.00 0.140679E+12 0.110014E+12 345221.92   162044.20 0.59



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 79687.54 79687.54 6.61 01-JAN-10:01 6.61 0.00
February 0.00 0.00 61724729.79 61724729.79 42371.69 28-FEB-12:01 42371.69 0.00
March 0.00 0.00 0.470785E+10 0.470785E+10 587690.75 31-MAR-14:01 587690.75 0.00
April 0.00 0.00 0.550520E+11 0.550520E+11 1247381.17 23-APR-15:42 1247381.17 0.01
May 0.00 0.00 0.438669E+12 0.430534E+12 1513706.04 25-MAY-15:20 1374168.27 0.18
June 0.00 0.00 0.953687E+12 0.772718E+12 2261485.18 30-JUN-04:01 1415995.73 0.41
July 0.00 0.00 0.118708E+13 0.937635E+12 2942040.52 05-JUL-10:40 1047839.17 0.55
August 0.00 0.00 0.937522E+12 0.721937E+12 1955308.36 31-AUG-12:40 901345.66 0.55
September 0.00 0.00 0.237851E+12 0.215535E+12 1533265.15 01-SEP-12:05 1213433.73 0.14
October 0.00 0.00 0.481928E+11 0.481928E+11 865478.87 19-OCT-15:00 865478.87 0.01
November 0.00 0.00 0.596113E+10 0.596113E+10 493339.80 01-NOV-14:01 493339.80 0.01
December 0.00 0.00 178120.37 178120.37 5.72 12-DEC-04:11 5.72 0.00
                 
Annual Sum or Average 0.00 0.00 0.386878E+13 0.319233E+13       0.16
Minimum of Months 0.00 0.00 79687.54 79687.54 5.72   5.72 0.00
Maximum of Months 0.00 0.00 0.118708E+13 0.937635E+12 2942040.52   1415995.73 0.55



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 4814712.23 4814712.23 2831.93 24-JAN-06:04 2831.93 0.00
February 0.00 0.00 7252520.35 7252520.35 6353.30 27-FEB-06:12 6353.30 0.00
March 0.00 0.00 7324451.20 7324451.20 5454.29 15-MAR-05:12 5454.29 0.00
April 0.00 0.00 0.485663E+10 0.485663E+10 164348.04 23-APR-15:31 164348.04 0.01
May 0.00 0.00 0.467508E+11 0.461067E+11 181602.21 25-MAY-15:00 168285.01 0.18
June 0.00 0.00 0.102742E+12 0.849439E+11 335691.33 29-JUN-05:02 157328.31 0.39
July 0.00 0.00 0.128762E+12 0.104887E+12 278746.12 05-JUL-05:01 109315.00 0.53
August 0.00 0.00 0.973381E+11 0.775754E+11 216477.12 08-AUG-15:00 179577.67 0.53
September 0.00 0.00 0.214093E+11 0.197024E+11 169740.45 01-SEP-15:30 163382.33 0.12
October 0.00 0.00 0.349811E+10 0.349811E+10 78710.99 19-OCT-15:00 78710.99 0.01
November 0.00 0.00 0.463047E+09 0.463047E+09 25093.39 01-NOV-14:53 25093.39 0.01
December 0.00 0.00 12223538.73 12223538.73 4197.05 11-DEC-06:12 4197.05 0.00
                 
Annual Sum or Average 0.00 0.00 0.405851E+12 0.342065E+12       0.15
Minimum of Months 0.00 0.00 4814712.23 4814712.23 2831.93   2831.93 0.00
Maximum of Months 0.00 0.00 0.128762E+12 0.104887E+12 335691.33   179577.67 0.53



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 19249109.70 19249109.70 61179.83 31-JAN-06:01 61179.83 0.00
February 0.00 0.00 0.156135E+09 0.156135E+09 56924.67 24-FEB-06:02 56924.67 0.00
March 0.00 0.00 0.120275E+10 0.120275E+10 114495.45 27-MAR-04:56 114495.45 0.00
April 0.00 0.00 0.742352E+10 0.742352E+10 115256.54 03-APR-04:49 115256.54 0.00
May 0.00 0.00 0.320570E+11 0.302008E+11 105668.57 26-MAY-04:11 71892.54 0.18
June 0.00 0.00 0.605015E+11 0.444672E+11 171815.73 29-JUN-04:52 81473.07 0.39
July 0.00 0.00 0.765549E+11 0.530869E+11 207444.01 05-JUL-10:25 74594.45 0.50
August 0.00 0.00 0.704768E+11 0.465001E+11 147905.02 27-AUG-14:31 89221.03 0.53
September 0.00 0.00 0.265505E+11 0.225827E+11 134277.39 04-SEP-11:58 134277.39 0.18
October 0.00 0.00 0.117722E+11 0.116014E+11 139903.78 25-OCT-03:25 139903.78 0.02
November 0.00 0.00 0.440852E+10 0.425696E+10 114346.49 30-NOV-05:49 114346.49 0.01
December 0.00 0.00 0.121492E+09 0.121492E+09 110640.78 01-DEC-05:50 110640.78 0.00
                 
Annual Sum or Average 0.00 0.00 0.291245E+12 0.221619E+12       0.15
Minimum of Months 0.00 0.00 19249109.70 19249109.70 56924.67   56924.67 0.00
Maximum of Months 0.00 0.00 0.765549E+11 0.530869E+11 207444.01   139903.78 0.53



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 3383165.69 3383165.69 63.72 28-JAN-13:02 63.72 0.02
February 0.00 0.00 0.158739E+12 0.158739E+12 277305.49 14-FEB-10:01 277305.49 0.00
March 0.00 0.00 0.222015E+12 0.222015E+12 267717.00 31-MAR-23:17 267717.00 0.00
April 0.00 0.00 0.223204E+12 0.223204E+12 434430.17 23-APR-15:46 434430.17 0.01
May 0.00 0.00 0.224752E+11 0.224752E+11 219021.98 31-MAY-23:47 219021.98 0.17
June 0.00 0.00 0.292250E+12 0.236831E+12 564778.66 19-JUN-10:52 228932.14 0.53
July 0.00 0.00 0.381050E+12 0.330387E+12 569313.14 03-JUL-23:48 195322.79 0.95
August 0.00 0.00 0.402103E+12 0.348310E+12 596664.11 31-AUG-19:10 280587.13 0.90
September 0.00 0.00 0.394863E+10 0.394863E+10 242164.60 30-SEP-23:53 242164.60 0.19
October 0.00 0.00 0.169996E+12 0.169706E+12 319211.33 21-OCT-14:07 319211.33 0.04
November 0.00 0.00 0.201866E+12 0.201426E+12 326964.90 01-NOV-00:22 326964.90 0.03
December 0.00 0.00 0.258978E+12 0.258978E+12 262395.00 25-DEC-08:00 262395.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.233663E+13 0.217602E+13       0.24
Minimum of Months 0.00 0.00 3383165.69 3383165.69 63.72   63.72 0.00
Maximum of Months 0.00 0.00 0.402103E+12 0.348310E+12 596664.11   434430.17 0.95



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.297686E+10 0.297686E+10 8839.70 14-JAN-04:21 8839.70 0.00
February 0.00 0.00 0.815117E+10 0.815117E+10 13831.56 15-FEB-05:31 13831.56 0.00
March 0.00 0.00 0.155617E+11 0.155617E+11 14361.92 05-MAR-08:21 14361.92 0.00
April 0.00 0.00 0.213917E+11 0.213917E+11 10446.70 23-APR-18:12 10446.70 0.00
May 0.00 0.00 0.799389E+10 0.796483E+10 4563.23 31-MAY-23:51 4563.23 0.00
June 0.00 0.00 0.129604E+11 0.127937E+11 6782.81 30-JUN-23:01 6771.81 0.00
July 0.00 0.00 0.188705E+11 0.186351E+11 8708.06 31-JUL-24:00 8654.48 0.00
August 0.00 0.00 0.237184E+11 0.234656E+11 10090.44 25-AUG-18:20 9843.60 0.00
September 0.00 0.00 0.742465E+10 0.738802E+10 4640.80 03-SEP-17:52 4637.35 0.00
October 0.00 0.00 0.116344E+11 0.116323E+11 5948.54 31-OCT-23:52 5948.54 0.00
November 0.00 0.00 0.153998E+11 0.153953E+11 7243.11 09-NOV-16:02 7243.11 0.00
December 0.00 0.00 0.172946E+11 0.172946E+11 14838.87 20-DEC-11:01 14838.87 0.00
                 
Annual Sum or Average 0.00 0.00 0.163378E+12 0.162651E+12       0.00
Minimum of Months 0.00 0.00 0.297686E+10 0.297686E+10 4563.23   4563.23 0.00
Maximum of Months 0.00 0.00 0.237184E+11 0.234656E+11 14838.87   14838.87 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.127309E+11 0.127309E+11 42699.05 06-JAN-12:42 42699.05 0.00
February 0.00 0.00 0.626017E+11 0.626017E+11 131398.12 17-FEB-09:21 131398.12 0.00
March 0.00 0.00 0.135406E+12 0.135406E+12 136134.98 16-MAR-04:41 136134.98 0.00
April 0.00 0.00 0.194487E+12 0.194487E+12 99360.65 23-APR-18:01 99360.65 0.00
May 0.00 0.00 0.709772E+11 0.706885E+11 44815.98 25-MAY-18:50 43563.50 0.00
June 0.00 0.00 0.120915E+12 0.119255E+12 66190.55 30-JUN-23:11 66123.97 0.00
July 0.00 0.00 0.177837E+12 0.175492E+12 82437.91 31-JUL-24:00 81970.89 0.00
August 0.00 0.00 0.222468E+12 0.219958E+12 97320.42 25-AUG-18:20 94854.32 0.00
September 0.00 0.00 0.631021E+11 0.627402E+11 44018.27 05-SEP-17:42 44018.27 0.00
October 0.00 0.00 0.998551E+11 0.998349E+11 56574.07 19-OCT-16:42 56574.07 0.00
November 0.00 0.00 0.127713E+12 0.127668E+12 67408.35 17-NOV-16:03 67408.35 0.00
December 0.00 0.00 0.147129E+12 0.147129E+12 141692.18 20-DEC-11:01 141692.18 0.00
                 
Annual Sum or Average 0.00 0.00 0.143522E+13 0.142799E+13       0.00
Minimum of Months 0.00 0.00 0.127309E+11 0.127309E+11 42699.05   42699.05 0.00
Maximum of Months 0.00 0.00 0.222468E+12 0.219958E+12 141692.18   141692.18 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.551483E+09 0.551483E+09 2287.93 20-JAN-16:25 2287.93 0.00
February 0.00 0.00 0.441808E+10 0.441808E+10 13239.78 14-FEB-10:01 13239.78 0.00
March 0.00 0.00 0.113937E+11 0.113937E+11 13617.15 16-MAR-04:41 13617.15 0.00
April 0.00 0.00 0.176721E+11 0.176721E+11 9808.42 23-APR-18:01 9808.42 0.00
May 0.00 0.00 0.622485E+10 0.619597E+10 4653.45 25-MAY-18:50 4528.84 0.00
June 0.00 0.00 0.116331E+11 0.114672E+11 6575.11 30-JUN-23:01 6563.89 0.00
July 0.00 0.00 0.174697E+11 0.172352E+11 8186.79 28-JUL-18:50 7919.52 0.00
August 0.00 0.00 0.217737E+11 0.215249E+11 9881.25 25-AUG-18:20 9635.61 0.00
September 0.00 0.00 0.513994E+10 0.510419E+10 4409.70 05-SEP-17:42 4409.70 0.00
October 0.00 0.00 0.778680E+10 0.778484E+10 5709.40 19-OCT-16:42 5709.40 0.00
November 0.00 0.00 0.104566E+11 0.104522E+11 6505.99 17-NOV-16:03 6505.99 0.00
December 0.00 0.00 0.128602E+11 0.128602E+11 14372.78 20-DEC-11:01 14372.78 0.00
                 
Annual Sum or Average 0.00 0.00 0.127380E+12 0.126660E+12       0.00
Minimum of Months 0.00 0.00 0.551483E+09 0.551483E+09 2287.93   2287.93 0.00
Maximum of Months 0.00 0.00 0.217737E+11 0.215249E+11 14372.78   14372.78 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:01 614655.02 3841106.31 02-JAN-04:01
February 0.00 0.00 01-FEB-00:01 419712.02 3458925.58 28-FEB-06:01
March 0.00 0.00 01-MAR-00:01 251058.35 3530184.95 31-MAR-04:01
April 0.00 0.00 01-APR-00:03 72782.66 3581806.44 07-APR-04:01
May 0.00 0.00 01-MAY-00:10 10929.04 3152227.31 01-MAY-05:01
June 0.00 0.00 01-JUN-00:01 2254.14 378596.41 10-JUN-05:01
July 0.00 0.00 01-JUL-00:01 816.22 160465.17 10-JUL-05:01
August 0.00 0.00 01-AUG-00:10 3059.20 901814.53 19-AUG-05:01
September 0.00 0.00 01-SEP-00:02 19034.41 3143504.72 23-SEP-05:01
October 0.00 0.00 01-OCT-00:01 68805.01 3684137.74 06-OCT-04:01
November 0.00 0.00 01-NOV-00:01 209503.51 3676641.31 24-NOV-05:01
December 0.00 0.00 01-DEC-00:01 532073.82 3790532.22 26-DEC-04:01
             
Annual Sum or Average 0.00     182965.68    
Minimum of Months 0.00 0.00   816.22 160465.17  
Maximum of Months 0.00 0.00   614655.02 3841106.31  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 1766.80 15725.27 31-JAN-06:06 89560.22 939044.95 19-JAN-02:50
February 69360.22 958761.07 08-FEB-17:53 178375.81 933242.29 01-FEB-00:01
March 94807.73 1014555.08 31-MAR-14:02 8521.35 763910.47 05-MAR-15:58
April 124010.18 1587601.76 23-APR-16:23 12502.54 882033.71 30-APR-24:00
May 233024.43 2529863.12 26-MAY-12:05 248247.75 939036.65 09-MAY-19:20
June 606536.21 3716886.64 29-JUN-04:14 60391.75 846514.80 01-JUN-00:22
July 751397.14 6011431.27 05-JUL-10:40 13192.06 507186.24 24-JUL-21:07
August 632764.31 3057420.12 31-AUG-12:40 11810.14 484910.60 23-AUG-04:04
September 126613.31 2420471.29 01-SEP-11:00 260899.48 938999.33 05-SEP-22:40
October 92646.68 1352940.02 26-OCT-13:20 171466.55 905143.36 07-OCT-16:42
November 93135.54 966922.08 21-NOV-06:14 5947.09 831398.97 01-NOV-01:10
December 107251.84 494040.88 06-DEC-05:10 5790.82 336603.32 06-DEC-06:47
             
Annual Sum or Average 245957.18     88200.01    
Minimum of Months 1766.80 15725.27   5790.82 336603.32  
Maximum of Months 751397.14 6011431.27   260899.48 939044.95  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 1.81 16450.24 31-JAN-06:01 0.00 0.00 01-JAN-00:01
February 78725.39 487167.03 08-FEB-15:13 0.00 0.00 01-FEB-00:01
March 170191.76 1139507.38 31-MAR-14:04 0.00 0.00 01-MAR-00:01
April 231845.04 3051937.30 23-APR-17:01 0.00 0.00 01-APR-00:03
May 248904.46 3414610.53 26-MAY-05:02 0.00 0.00 01-MAY-00:10
June 634301.02 5422966.27 30-JUN-03:01 0.00 0.00 01-JUN-00:01
July 802098.87 6095476.17 05-JUL-10:40 0.00 0.00 01-JUL-00:01
August 693730.03 4090903.93 01-AUG-04:11 0.00 0.00 01-AUG-00:10
September 145176.38 3785161.10 01-SEP-04:11 0.00 0.00 01-SEP-00:02
October 113326.38 1533874.95 18-OCT-13:32 0.00 0.00 01-OCT-00:01
November 196590.29 1080763.58 01-NOV-14:02 0.00 0.00 01-NOV-00:01
December 216675.89 567288.18 15-DEC-06:01 0.00 0.00 01-DEC-00:01
             
Annual Sum or Average 295984.92     0.00    
Minimum of Months 1.81 16450.24   0.00 0.00  
Maximum of Months 802098.87 6095476.17   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:01 17178.46 61748.42 31-JAN-12:15
February 0.00 0.00 01-FEB-00:01 17672.25 62342.89 24-FEB-12:40
March 0.00 0.00 01-MAR-00:01 18709.63 62329.18 01-MAR-12:35
April 0.00 0.00 01-APR-00:03 17004.36 61076.40 03-APR-11:16
May 0.00 0.00 01-MAY-00:10 16707.80 58693.69 01-MAY-11:38
June 0.00 0.00 01-JUN-00:01 16109.70 55326.83 01-JUN-11:20
July 0.00 0.00 01-JUL-00:01 14048.94 52009.52 03-JUL-11:22
August 0.00 0.00 01-AUG-00:10 14953.83 49961.46 01-AUG-12:00
September 0.00 0.00 01-SEP-00:02 14083.47 50382.78 29-SEP-11:50
October 0.00 0.00 01-OCT-00:01 14600.02 53040.62 31-OCT-11:37
November 0.00 0.00 01-NOV-00:01 15662.82 56303.10 30-NOV-12:27
December 0.00 0.00 01-DEC-00:01 15992.61 59350.51 29-DEC-12:13
             
Annual Sum or Average 0.00     16050.86    
Minimum of Months 0.00 0.00   14048.94 49961.46  
Maximum of Months 0.00 0.00   18709.63 62342.89  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 243.92 27124.95 23-JAN-06:30 4681.27 179565.13 03-JAN-04:01
February 47443.80 715774.95 06-FEB-02:28 185.15 62103.74 08-FEB-14:21
March 19042.43 1069132.13 31-MAR-14:05 6485.80 85607.20 24-MAR-10:30
April 67557.59 1702964.53 23-APR-15:48 8223.59 172608.63 30-APR-05:20
May 300323.94 4077019.11 26-MAY-12:05 1617.76 196194.44 10-MAY-04:15
June 1025202.35 8383710.01 29-JUN-16:00 16.01 38770.35 02-JUN-17:29
July 1298262.06 8926733.85 05-JUL-10:50 145.73 63814.48 08-JUL-02:35
August 977995.84 7468137.21 08-AUG-15:10 392.26 58726.58 19-AUG-02:30
September 159011.06 3593562.36 01-SEP-15:40 1338.37 134596.17 08-SEP-22:10
October 102560.57 1404031.76 18-OCT-13:34 316.40 73577.78 05-OCT-09:57
November 22838.48 937668.30 01-NOV-14:06 8173.16 159562.53 14-NOV-21:37
December 19450.85 435530.39 26-DEC-06:40 11432.99 185382.56 19-DEC-20:20
             
Annual Sum or Average 339235.56     3602.62    
Minimum of Months 243.92 27124.95   16.01 38770.35  
Maximum of Months 1298262.06 8926733.85   11432.99 196194.44  



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.952048E+10 0.62 12388.75 02-JAN-06:02 1.31
February 0.829771E+10 0.57 11259.71 08-FEB-14:09 1.26
March 0.107759E+11 0.62 21950.19 27-MAR-05:01 1.67
April 0.124939E+11 0.63 22812.25 07-APR-05:01 1.70
May 0.146500E+11 0.68 21589.03 26-MAY-04:11 1.64
June 0.169305E+11 0.74 28753.09 29-JUN-04:11 1.85
July 0.191776E+11 0.77 28753.09 05-JUL-10:34 1.84
August 0.192378E+11 0.80 25242.08 01-AUG-04:11 1.75
September 0.129357E+11 0.64 23069.43 01-SEP-15:20 1.68
October 0.109840E+11 0.57 20321.75 04-OCT-05:01 1.61
November 0.972406E+10 0.55 22812.25 17-NOV-06:01 1.70
December 0.952947E+10 0.60 12951.38 06-DEC-06:01 1.33
           
Annual Sum or Average 0.154257E+12 0.65      
Minimum of Months 0.829771E+10 0.55 11259.71   1.26
Maximum of Months 0.192378E+11 0.80 28753.09   1.85



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.122954E+12 0.80 133684.06 02-JAN-04:01 1.40
February 0.104611E+12 0.74 133684.06 06-FEB-06:01 1.40
March 0.109859E+12 0.68 141387.42 31-MAR-14:52 1.43
April 0.107012E+12 0.61 193600.56 24-APR-05:01 1.62
May 0.135027E+12 0.67 254446.99 09-MAY-05:01 1.83
June 0.152636E+12 0.72 267064.21 30-JUN-03:01 1.85
July 0.158470E+12 0.71 267064.21 05-JUL-10:40 1.84
August 0.151353E+12 0.72 211819.90 08-AUG-15:20 1.67
September 0.115970E+12 0.62 254446.99 20-SEP-05:01 1.82
October 0.967308E+11 0.57 254446.99 03-OCT-05:01 1.83
November 0.975235E+11 0.64 133684.06 13-NOV-05:01 1.40
December 0.116119E+12 0.76 133684.06 04-DEC-05:01 1.40
           
Annual Sum or Average 0.146826E+13 0.69      
Minimum of Months 0.967308E+11 0.57 133684.06   1.40
Maximum of Months 0.158470E+12 0.80 267064.21   1.85



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.135361E+11 0.70 13363.10 01-JAN-04:01 1.13
February 0.120099E+11 0.68 13363.10 01-FEB-05:01 1.13
March 0.123205E+11 0.63 13363.10 01-MAR-05:01 1.13
April 0.104675E+11 0.54 13363.10 03-APR-03:01 1.13
May 0.110578E+11 0.50 20381.15 26-MAY-05:02 1.33
June 0.124175E+11 0.54 26783.41 30-JUN-03:01 1.49
July 0.128323E+11 0.52 23410.20 21-JUL-05:01 1.41
August 0.121295E+11 0.53 20015.10 01-AUG-05:02 1.32
September 0.954863E+10 0.48 20015.10 01-SEP-05:02 1.32
October 0.100657E+11 0.51 13363.10 02-OCT-05:01 1.12
November 0.117639E+11 0.63 13363.10 01-NOV-05:01 1.12
December 0.132431E+11 0.69 13363.10 01-DEC-05:01 1.13
           
Annual Sum or Average 0.141392E+12 0.58      
Minimum of Months 0.954863E+10 0.48 13363.10   1.12
Maximum of Months 0.135361E+11 0.70 26783.41   1.49



Table of Contents

Report: FanReportMonthly

For: CAV_BAS SZVAV FAN

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.306736E+10 0.42 16466.19 04-JAN-07:47 1.89
February 0.276148E+10 0.43 16466.19 06-FEB-06:01 1.88
March 0.385722E+10 0.47 16466.19 01-MAR-06:01 1.88
April 0.647065E+10 0.54 16466.19 01-APR-04:01 1.88
May 0.752318E+10 0.58 16466.19 01-MAY-04:01 1.89
June 0.807700E+10 0.63 16466.19 01-JUN-05:01 1.87
July 0.874081E+10 0.62 16466.19 01-JUL-04:11 1.87
August 0.112929E+11 0.73 16466.19 01-AUG-04:11 1.86
September 0.929932E+10 0.64 16466.19 01-SEP-04:11 1.86
October 0.746308E+10 0.55 16466.19 02-OCT-04:11 1.87
November 0.551366E+10 0.51 16466.19 01-NOV-04:11 1.87
December 0.294949E+10 0.41 16466.19 01-DEC-05:01 1.89
           
Annual Sum or Average 0.770161E+11 0.54      
Minimum of Months 0.276148E+10 0.41 16466.19   1.86
Maximum of Months 0.112929E+11 0.73 16466.19   1.89



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SYS11 FAN

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.274298E+11 0.53 10241.10 01-JAN-00:01 0.53
February 0.445061E+11 0.65 34109.12 01-FEB-00:03 0.89
March 0.594368E+11 0.71 34109.12 01-MAR-00:02 0.89
April 0.879777E+11 0.89 34109.12 01-APR-00:03 0.89
May 0.274613E+11 0.53 34109.12 31-MAY-23:03 0.88
June 0.405739E+11 0.61 34109.12 01-JUN-00:01 0.88
July 0.681149E+11 0.76 34109.12 01-JUL-00:01 0.88
August 0.888216E+11 0.87 34109.12 01-AUG-00:10 0.88
September 0.265571E+11 0.53 34109.12 30-SEP-23:34 0.88
October 0.477906E+11 0.64 34109.12 01-OCT-00:02 0.88
November 0.585505E+11 0.72 34109.12 01-NOV-00:01 0.89
December 0.900273E+11 0.88 34109.12 01-DEC-00:02 0.89
           
Annual Sum or Average 0.667248E+12 0.69      
Minimum of Months 0.265571E+11 0.53 10241.10   0.53
Maximum of Months 0.900273E+11 0.89 34109.12   0.89



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.375395E+10 1.48 1401.56 16-JAN-04:36 1.48
February 0.339066E+10 1.48 1401.56 01-FEB-00:19 1.48
March 0.375395E+10 1.47 1401.56 01-MAR-00:06 1.47
April 0.363285E+10 1.47 1401.56 10-APR-10:48 1.47
May 0.375395E+10 1.46 1401.56 01-MAY-00:10 1.47
June 0.363285E+10 1.46 1401.56 01-JUN-00:03 1.46
July 0.375395E+10 1.46 1401.56 01-JUL-00:20 1.46
August 0.375395E+10 1.46 1401.56 01-AUG-00:20 1.46
September 0.363285E+10 1.46 1401.56 01-SEP-00:02 1.46
October 0.375395E+10 1.47 1401.56 01-OCT-00:12 1.46
November 0.363285E+10 1.47 1401.56 01-NOV-00:03 1.47
December 0.375395E+10 1.48 1401.56 01-DEC-00:06 1.47
           
Annual Sum or Average 0.441997E+11 1.47      
Minimum of Months 0.339066E+10 1.46 1401.56   1.46
Maximum of Months 0.375395E+10 1.48 1401.56   1.48



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.362401E+11 1.48 13530.51 03-JAN-01:23 1.48
February 0.327330E+11 1.48 13530.51 20-FEB-22:12 1.48
March 0.362401E+11 1.47 13530.51 10-MAR-17:01 1.47
April 0.350711E+11 1.47 13530.51 01-APR-05:18 1.47
May 0.362401E+11 1.46 13530.51 01-MAY-01:50 1.47
June 0.350711E+11 1.46 13530.51 01-JUN-00:04 1.46
July 0.362401E+11 1.46 13530.51 01-JUL-19:36 1.46
August 0.362401E+11 1.46 13530.51 02-AUG-06:05 1.46
September 0.350711E+11 1.46 13530.51 30-SEP-11:20 1.46
October 0.362401E+11 1.47 13530.51 01-OCT-00:55 1.46
November 0.350711E+11 1.47 13530.51 09-NOV-15:56 1.47
December 0.362401E+11 1.48 13530.51 01-DEC-01:33 1.47
           
Annual Sum or Average 0.426698E+12 1.47      
Minimum of Months 0.327330E+11 1.46 13530.51   1.46
Maximum of Months 0.362401E+11 1.48 13530.51   1.48



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.372107E+10 1.48 1389.29 02-JAN-22:02 1.48
February 0.336096E+10 1.48 1389.29 01-FEB-00:19 1.48
March 0.372107E+10 1.47 1389.29 02-MAR-16:45 1.47
April 0.360103E+10 1.47 1389.29 01-APR-05:13 1.47
May 0.372107E+10 1.46 1389.29 01-MAY-21:17 1.47
June 0.360103E+10 1.46 1389.29 01-JUN-04:50 1.46
July 0.372107E+10 1.46 1389.29 01-JUL-04:00 1.46
August 0.372107E+10 1.46 1389.29 01-AUG-04:25 1.46
September 0.360103E+10 1.46 1389.29 01-SEP-00:04 1.46
October 0.372107E+10 1.47 1389.29 01-OCT-06:03 1.46
November 0.360103E+10 1.47 1389.29 01-NOV-14:12 1.46
December 0.372107E+10 1.48 1389.29 01-DEC-11:27 1.47
           
Annual Sum or Average 0.438126E+11 1.47      
Minimum of Months 0.336096E+10 1.46 1389.29   1.46
Maximum of Months 0.372107E+10 1.48 1389.29   1.48



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.165363E+10 0.148827E+10 5499.48 30-JAN-06:02 4949.53 4949.53 50.68 25.54
February 0.972326E+09 0.875093E+09 5708.68 21-FEB-06:01 5137.81 5137.81 47.54 26.15
March 0.597257E+09 0.537531E+09 4996.41 06-MAR-06:01 4496.77 4496.77 55.46 24.03
April 0.169087E+09 0.152179E+09 3870.40 10-APR-05:01 3483.36 3483.36 45.22 20.38
May 27389337.85 24650404.07 3629.66 01-MAY-05:01 3266.69 3266.69 40.30 19.51
June 5369745.41 4832770.87 342.86 10-JUN-05:01 308.58 308.58 21.07 2.03
July 1990550.85 1791495.76 145.17 10-JUL-05:01 130.66 130.66 20.74 0.85
August 7554299.33 6798869.39 800.72 19-AUG-05:01 720.65 720.65 26.50 4.85
September 46652442.66 41987198.39 3542.57 23-SEP-05:01 3188.31 3188.31 31.57 19.23
October 0.173234E+09 0.155911E+09 3724.55 13-OCT-05:01 3352.10 3352.10 40.89 19.87
November 0.497049E+09 0.447344E+09 5033.47 27-NOV-06:02 4530.12 4530.12 54.65 24.15
December 0.137677E+10 0.123909E+10 5689.52 05-DEC-06:01 5120.57 5120.57 46.64 26.11
                 
Annual Sum or Average 0.552830E+10 0.497547E+10            
Minimum of Months 1990550.85 1791495.76 145.17   130.66 130.66 20.74 0.85
Maximum of Months 0.165363E+10 0.148827E+10 5708.68   5137.81 5137.81 55.46 26.15



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 268624.41 241761.97 586.63 21-JAN-06:01 527.97 527.97 6.71 5.07
February 0.141646E+10 0.127482E+10 2392.74 08-FEB-15:51 2153.47 2153.47 9.91 21.38
March 0.253983E+10 0.228585E+10 4354.58 31-MAR-13:12 3919.12 3919.12 9.72 38.53
April 0.278393E+10 0.250554E+10 17790.99 23-APR-17:42 16011.89 16011.89 9.63 105.37
May 0.213840E+10 0.192456E+10 19241.57 26-MAY-05:02 17317.41 17317.41 9.69 109.73
June 0.521475E+10 0.469327E+10 25102.57 24-JUN-05:01 22592.32 22592.32 9.41 125.01
July 0.661313E+10 0.595181E+10 26674.96 14-JUL-05:01 24007.47 24007.47 10.11 128.63
August 0.591677E+10 0.532510E+10 21897.90 08-AUG-05:02 19708.11 19708.11 10.31 117.07
September 0.133493E+10 0.120143E+10 20087.65 01-SEP-05:02 18078.88 18078.88 10.40 112.15
October 0.191438E+10 0.172294E+10 8017.68 19-OCT-12:18 7215.91 7215.91 7.81 64.24
November 0.257864E+10 0.232077E+10 4194.53 01-NOV-14:02 3775.08 3775.08 8.10 37.20
December 0.275225E+10 0.247703E+10 2392.74 08-DEC-06:37 2153.47 2153.47 9.88 21.38
                 
Annual Sum or Average 0.352037E+11 0.316834E+11            
Minimum of Months 268624.41 241761.97 586.63   527.97 527.97 6.71 5.07
Maximum of Months 0.661313E+10 0.595181E+10 26674.96   24007.47 24007.47 10.40 128.63



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER1 PUMP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.525297E+10 0.472767E+10 12234.64 01-JAN-00:01 11011.18 11011.18 6.75 64.31
February 0.878126E+10 0.790313E+10 12234.64 01-FEB-00:03 11011.18 11011.18 6.80 64.31
March 0.269176E+11 0.242258E+11 12234.64 01-MAR-00:02 11011.18 11011.18 7.73 64.31
April 0.256014E+11 0.230413E+11 12234.64 01-APR-00:03 11011.18 11011.18 10.38 64.31
May 0.125839E+11 0.113255E+11 12234.64 01-MAY-03:06 11011.18 11011.18 6.91 64.31
June 0.208589E+11 0.187730E+11 12234.64 01-JUN-00:03 11011.18 11011.18 7.25 64.31
July 0.291109E+11 0.261998E+11 12234.64 01-JUL-00:27 11011.18 11011.18 10.24 64.31
August 0.289623E+11 0.260661E+11 12234.64 01-AUG-00:10 11011.18 11011.18 10.19 64.31
September 0.105663E+11 0.950967E+10 12234.64 01-SEP-00:02 11011.18 11011.18 9.67 64.31
October 0.110495E+11 0.994454E+10 12234.64 01-OCT-00:04 11011.18 11011.18 7.98 64.31
November 0.293384E+11 0.264045E+11 12234.64 01-NOV-00:03 11011.18 11011.18 7.74 64.31
December 0.288116E+11 0.259305E+11 12234.64 01-DEC-00:01 11011.18 11011.18 10.23 64.31
                 
Annual Sum or Average 0.237835E+12 0.214052E+12            
Minimum of Months 0.525297E+10 0.472767E+10 12234.64   11011.18 11011.18 6.75 64.31
Maximum of Months 0.293384E+11 0.264045E+11 12234.64   11011.18 11011.18 10.38 64.31



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER2 PUMP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.00 0.00 0.00 01-JAN-00:01 0.00 0.00 6.75 0.00
February 0.00 0.00 0.00 01-FEB-00:01 0.00 0.00 6.74 0.00
March 0.00 0.00 0.00 01-MAR-00:01 0.00 0.00 7.67 0.00
April 0.00 0.00 0.00 01-APR-00:03 0.00 0.00 10.38 0.00
May 0.891905E+09 0.802715E+09 12234.64 16-MAY-13:50 11011.18 11011.18 13.80 32.16
June 0.303699E+10 0.273329E+10 12234.64 06-JUN-12:05 11011.18 11011.18 10.24 64.31
July 0.574853E+10 0.517368E+10 12234.64 03-JUL-12:20 11011.18 11011.18 13.45 32.16
August 0.435113E+10 0.391602E+10 12234.64 01-AUG-04:12 11011.18 11011.18 13.67 32.16
September 0.245916E+09 0.221325E+09 12234.64 01-SEP-10:20 11011.18 11011.18 14.09 32.16
October 0.00 0.00 0.00 01-OCT-00:01 0.00 0.00 7.85 0.00
November 0.00 0.00 0.00 01-NOV-00:01 0.00 0.00 7.71 0.00
December 0.00 0.00 0.00 01-DEC-00:01 0.00 0.00 10.23 0.00
                 
Annual Sum or Average 0.142745E+11 0.128470E+11            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 6.74 0.00
Maximum of Months 0.574853E+10 0.517368E+10 12234.64   11011.18 11011.18 14.09 64.31



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.112905E+09 33871561.48 56.21 01-JAN-06:01 16.86 16.86 57.10 0.44
February 0.101979E+09 30593668.43 56.21 01-FEB-06:01 16.86 16.86 56.67 0.44
March 0.112905E+09 33871561.48 56.21 01-MAR-06:01 16.86 16.86 56.64 0.44
April 0.109263E+09 32778930.46 56.21 01-APR-05:01 16.86 16.86 56.67 0.44
May 0.112905E+09 33871561.48 56.21 01-MAY-05:01 16.86 16.86 57.09 0.44
June 0.109263E+09 32778930.46 56.21 01-JUN-05:01 16.86 16.86 57.02 0.44
July 0.112905E+09 33871561.48 56.21 01-JUL-05:01 16.86 16.86 57.19 0.44
August 0.112905E+09 33871561.48 56.21 01-AUG-05:02 16.86 16.86 57.18 0.44
September 0.109263E+09 32778930.46 56.21 01-SEP-05:02 16.86 16.86 57.22 0.44
October 0.112905E+09 33871561.48 56.21 01-OCT-05:01 16.86 16.86 57.29 0.44
November 0.109263E+09 32778930.46 56.21 01-NOV-05:01 16.86 16.86 57.08 0.44
December 0.112905E+09 33871561.48 56.21 01-DEC-06:01 16.86 16.86 56.97 0.44
                 
Annual Sum or Average 0.132937E+10 0.398810E+09            
Minimum of Months 0.101979E+09 30593668.43 56.21   16.86 16.86 56.64 0.44
Maximum of Months 0.112905E+09 33871561.48 56.21   16.86 16.86 57.29 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.135086E+11 0.121577E+11 31510.06 23-JAN-06:30 28359.06 28359.06 21.17 90.69
February 0.226159E+11 0.203543E+11 31551.25 06-FEB-02:28 28396.13 28396.13 22.99 90.69
March 0.692182E+11 0.622964E+11 31572.42 31-MAR-14:05 28415.18 28415.18 23.92 90.69
April 0.658061E+11 0.592255E+11 31612.69 23-APR-15:48 28451.42 28451.42 25.59 90.69
May 0.342620E+11 0.308358E+11 63272.51 26-MAY-12:05 56945.26 56945.26 26.48 181.39
June 0.608228E+11 0.547405E+11 63430.27 29-JUN-11:30 57087.24 57087.24 29.62 181.39
July 0.884281E+11 0.795853E+11 63430.27 03-JUL-13:10 57087.24 57087.24 29.57 181.39
August 0.849045E+11 0.764140E+11 63430.27 08-AUG-12:20 57087.24 57087.24 29.61 181.39
September 0.278509E+11 0.250658E+11 63238.71 01-SEP-15:40 56914.84 56914.84 25.84 181.39
October 0.284550E+11 0.256095E+11 31592.50 18-OCT-13:34 28433.25 28433.25 24.80 90.69
November 0.752052E+11 0.676847E+11 31564.54 01-NOV-14:06 28408.09 28408.09 23.57 90.69
December 0.741871E+11 0.667684E+11 31534.48 26-DEC-06:40 28381.03 28381.03 22.25 90.69
                 
Annual Sum or Average 0.645265E+12 0.580738E+12            
Minimum of Months 0.135086E+11 0.121577E+11 31510.06   28359.06 28359.06 21.17 90.69
Maximum of Months 0.884281E+11 0.795853E+11 63430.27   57087.24 57087.24 29.62 181.39



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:01 39.64 39.64 614655.02 3841106.31 02-JAN-04:01
February 0.00 0.00 01-FEB-00:01 36.37 82.20 419712.02 3458925.58 28-FEB-06:01
March 0.00 0.00 01-MAR-00:01 26.63 26.63 251058.35 3530184.95 31-MAR-04:01
April 0.00 0.00 01-APR-00:03 23.28 23.28 72782.66 3581806.44 07-APR-04:01
May 0.00 0.00 01-MAY-00:10 20.24 20.24 10929.04 3152227.31 01-MAY-05:01
June 0.00 0.00 01-JUN-00:01 22.47 22.47 2254.14 378596.41 10-JUN-05:01
July 0.00 0.00 01-JUL-00:01 19.62 19.62 816.22 160465.17 10-JUL-05:01
August 0.00 0.00 01-AUG-00:10 20.22 20.22 3059.20 901814.53 19-AUG-05:01
September 0.00 0.00 01-SEP-00:02 19.73 19.73 19034.41 3143504.72 23-SEP-05:01
October 0.00 0.00 01-OCT-00:01 21.47 21.47 68805.01 3684137.74 06-OCT-04:01
November 0.00 0.00 01-NOV-00:01 27.74 27.74 209503.51 3676641.31 24-NOV-05:01
December 0.00 0.00 01-DEC-00:01 28.59 28.59 532073.82 3790532.22 26-DEC-04:01
                 
Annual Sum or Average 0.00         182965.68    
Minimum of Months 0.00 0.00   19.62 19.62 816.22 160465.17  
Maximum of Months 0.00 0.00   39.64 82.20 614655.02 3841106.31  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 1766.80 15725.27 31-JAN-06:06 6.76 6.70 89560.22 939044.95 19-JAN-02:50
February 69360.22 958761.07 08-FEB-17:53 10.26 6.70 178375.81 933242.29 01-FEB-00:01
March 94807.73 1014555.08 31-MAR-14:02 10.48 6.72 8521.35 763910.47 05-MAR-15:58
April 124010.18 1587601.76 23-APR-16:23 12.59 6.70 12502.54 882033.71 30-APR-24:00
May 233024.43 2529863.12 26-MAY-12:05 11.39 6.70 248247.75 939036.65 09-MAY-19:20
June 606536.21 3716886.64 29-JUN-04:14 13.60 6.85 60391.75 846514.80 01-JUN-00:22
July 751397.14 6011431.27 05-JUL-10:40 17.87 11.12 13192.06 507186.24 24-JUL-21:07
August 632764.31 3057420.12 31-AUG-12:40 12.38 6.70 11810.14 484910.60 23-AUG-04:04
September 126613.31 2420471.29 01-SEP-11:00 11.19 6.70 260899.48 938999.33 05-SEP-22:40
October 92646.68 1352940.02 26-OCT-13:20 11.72 6.70 171466.55 905143.36 07-OCT-16:42
November 93135.54 966922.08 21-NOV-06:14 10.29 6.70 5947.09 831398.97 01-NOV-01:10
December 107251.84 494040.88 06-DEC-05:10 10.48 8.65 5790.82 336603.32 06-DEC-06:47
                 
Annual Sum or Average 245957.18         88200.01    
Minimum of Months 1766.80 15725.27   6.76 6.70 5790.82 336603.32  
Maximum of Months 751397.14 6011431.27   17.87 11.12 260899.48 939044.95  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 1.81 16450.24 31-JAN-06:01 7.47 6.72 0.00 0.00 01-JAN-00:01
February 78725.39 487167.03 08-FEB-15:13 12.14 9.67 0.00 0.00 01-FEB-00:01
March 170191.76 1139507.38 31-MAR-14:04 14.18 7.03 0.00 0.00 01-MAR-00:01
April 231845.04 3051937.30 23-APR-17:01 13.63 10.84 0.00 0.00 01-APR-00:03
May 248904.46 3414610.53 26-MAY-05:02 14.13 10.58 0.00 0.00 01-MAY-00:10
June 634301.02 5422966.27 30-JUN-03:01 17.62 12.83 0.00 0.00 01-JUN-00:01
July 802098.87 6095476.17 05-JUL-10:40 18.45 10.85 0.00 0.00 01-JUL-00:01
August 693730.03 4090903.93 01-AUG-04:11 16.29 11.94 0.00 0.00 01-AUG-00:10
September 145176.38 3785161.10 01-SEP-04:11 15.84 10.31 0.00 0.00 01-SEP-00:02
October 113326.38 1533874.95 18-OCT-13:32 13.01 6.71 0.00 0.00 01-OCT-00:01
November 196590.29 1080763.58 01-NOV-14:02 13.64 7.94 0.00 0.00 01-NOV-00:01
December 216675.89 567288.18 15-DEC-06:01 13.04 9.71 0.00 0.00 01-DEC-00:01
                 
Annual Sum or Average 295984.92         0.00    
Minimum of Months 1.81 16450.24   7.47 6.71 0.00 0.00  
Maximum of Months 802098.87 6095476.17   18.45 12.83 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:01 57.78 57.78 17178.46 61748.42 31-JAN-12:15
February 0.00 0.00 01-FEB-00:01 57.11 57.11 17672.25 62342.89 24-FEB-12:40
March 0.00 0.00 01-MAR-00:01 57.08 57.08 18709.63 62329.18 01-MAR-12:35
April 0.00 0.00 01-APR-00:03 57.13 57.13 17004.36 61076.40 03-APR-11:16
May 0.00 0.00 01-MAY-00:10 57.81 57.81 16707.80 58693.69 01-MAY-11:38
June 0.00 0.00 01-JUN-00:01 57.41 57.41 16109.70 55326.83 01-JUN-11:20
July 0.00 0.00 01-JUL-00:01 57.56 57.56 14048.94 52009.52 03-JUL-11:22
August 0.00 0.00 01-AUG-00:10 57.67 57.67 14953.83 49961.46 01-AUG-12:00
September 0.00 0.00 01-SEP-00:02 57.70 57.70 14083.47 50382.78 29-SEP-11:50
October 0.00 0.00 01-OCT-00:01 57.65 57.65 14600.02 53040.62 31-OCT-11:37
November 0.00 0.00 01-NOV-00:01 57.52 57.52 15662.82 56303.10 30-NOV-12:27
December 0.00 0.00 01-DEC-00:01 57.37 57.37 15992.61 59350.51 29-DEC-12:13
                 
Annual Sum or Average 0.00         16050.86    
Minimum of Months 0.00 0.00   57.08 57.08 14048.94 49961.46  
Maximum of Months 0.00 0.00   57.81 57.81 18709.63 62342.89  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 243.92 27124.95 23-JAN-06:30 21.17 20.34 4681.27 179565.13 03-JAN-04:01
February 47443.80 715774.95 06-FEB-02:28 22.99 21.10 185.15 62103.74 08-FEB-14:21
March 19042.43 1069132.13 31-MAR-14:05 23.92 21.10 6485.80 85607.20 24-MAR-10:30
April 67557.59 1702964.53 23-APR-15:48 25.59 21.46 8223.59 172608.63 30-APR-05:20
May 300323.94 4077019.11 26-MAY-12:05 26.48 23.02 1617.76 196194.44 10-MAY-04:15
June 1025202.35 8383710.01 29-JUN-16:00 32.16 27.83 16.01 38770.35 02-JUN-17:29
July 1298262.06 8926733.85 05-JUL-10:50 32.87 27.30 145.73 63814.48 08-JUL-02:35
August 977995.84 7468137.21 08-AUG-15:10 30.95 26.66 392.26 58726.58 19-AUG-02:30
September 159011.06 3593562.36 01-SEP-15:40 25.84 21.91 1338.37 134596.17 08-SEP-22:10
October 102560.57 1404031.76 18-OCT-13:34 24.80 21.10 316.40 73577.78 05-OCT-09:57
November 22838.48 937668.30 01-NOV-14:06 23.57 21.10 8173.16 159562.53 14-NOV-21:37
December 19450.85 435530.39 26-DEC-06:40 22.25 21.10 11432.99 185382.56 19-DEC-20:20
                 
Annual Sum or Average 339235.56         3602.62    
Minimum of Months 243.92 27124.95   21.17 20.34 16.01 38770.35  
Maximum of Months 1298262.06 8926733.85   32.87 27.83 11432.99 196194.44  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.958012E+11 0.00 288.56 0.952048E+10 0.00 0.00
February 0.531070E+11 0.00 3610.96 0.829771E+10 0.00 0.00
March 0.290243E+11 0.00 278.72 0.107759E+11 0.00 0.00
April 0.429576E+10 0.00 0.572825E+10 0.124939E+11 0.00 0.00
May 0.410422E+09 0.00 0.459015E+11 0.146500E+11 0.00 0.00
June 15599893.83 0.00 0.104210E+12 0.169305E+11 0.00 0.00
July 1246907.48 0.00 0.140679E+12 0.191776E+11 0.00 0.00
August 29655487.95 0.00 0.112835E+12 0.192378E+11 0.00 0.00
September 0.749219E+09 0.00 0.242210E+11 0.129357E+11 0.00 0.00
October 0.432187E+10 0.00 0.398972E+10 0.109840E+11 0.00 0.00
November 0.169936E+11 0.00 0.559479E+09 0.972406E+10 0.00 0.00
December 0.695450E+11 0.00 1062893.78 0.952947E+10 0.00 0.00
             
Annual Sum or Average 0.274295E+12 0.00 0.438125E+12 0.154257E+12 0.00 0.00
Minimum of Months 1246907.48 0.00 278.72 0.829771E+10 0.00 0.00
Maximum of Months 0.958012E+11 0.00 0.140679E+12 0.192378E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.134151E+13 0.00 79687.54 0.122954E+12 0.00 0.00
February 0.829777E+12 0.00 61724729.79 0.104611E+12 0.00 0.00
March 0.550775E+12 0.00 0.470785E+10 0.109859E+12 0.00 0.00
April 0.149107E+12 0.00 0.550520E+11 0.107012E+12 0.00 0.00
May 0.209478E+11 0.00 0.438669E+12 0.135027E+12 0.00 0.00
June 0.353394E+10 0.00 0.953687E+12 0.152636E+12 0.00 0.00
July 0.946177E+09 0.00 0.118708E+13 0.158470E+12 0.00 0.00
August 0.518212E+10 0.00 0.937522E+12 0.151353E+12 0.00 0.00
September 0.366564E+11 0.00 0.237851E+12 0.115970E+12 0.00 0.00
October 0.141443E+12 0.00 0.481928E+11 0.967308E+11 0.00 0.00
November 0.441498E+12 0.00 0.596113E+10 0.975235E+11 0.00 0.00
December 0.117217E+13 0.00 178120.37 0.116119E+12 0.00 0.00
             
Annual Sum or Average 0.469354E+13 0.00 0.386878E+13 0.146826E+13 0.00 0.00
Minimum of Months 0.946177E+09 0.00 79687.54 0.967308E+11 0.00 0.00
Maximum of Months 0.134151E+13 0.00 0.118708E+13 0.158470E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.207687E+12 0.00 4814712.23 0.135361E+11 0.00 0.00
February 0.137018E+12 0.00 7252520.35 0.120099E+11 0.00 0.00
March 0.965210E+11 0.00 7324451.20 0.123205E+11 0.00 0.00
April 0.362344E+11 0.00 0.485663E+10 0.104675E+11 0.00 0.00
May 0.803066E+10 0.00 0.467508E+11 0.110578E+11 0.00 0.00
June 0.234538E+10 0.00 0.102742E+12 0.124175E+11 0.00 0.00
July 0.124205E+10 0.00 0.128762E+12 0.128323E+11 0.00 0.00
August 0.300910E+10 0.00 0.973381E+11 0.121295E+11 0.00 0.00
September 0.120849E+11 0.00 0.214093E+11 0.954863E+10 0.00 0.00
October 0.391401E+11 0.00 0.349811E+10 0.100657E+11 0.00 0.00
November 0.874457E+11 0.00 0.463047E+09 0.117639E+11 0.00 0.00
December 0.190276E+12 0.00 12223538.73 0.132431E+11 0.00 0.00
             
Annual Sum or Average 0.821035E+12 0.00 0.405851E+12 0.141392E+12 0.00 0.00
Minimum of Months 0.124205E+10 0.00 4814712.23 0.954863E+10 0.00 0.00
Maximum of Months 0.207687E+12 0.00 0.128762E+12 0.135361E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.110469E+11 0.00 19249109.70 0.306736E+10 0.00 0.00
February 0.150776E+10 0.00 0.156135E+09 0.276148E+10 0.00 0.00
March 9182823.29 0.00 0.120275E+10 0.385722E+10 0.00 0.00
April 0.00 0.00 0.742352E+10 0.647065E+10 0.00 0.00
May 0.00 0.00 0.320570E+11 0.752318E+10 0.00 0.00
June 0.00 0.00 0.605015E+11 0.807700E+10 0.00 0.00
July 0.00 0.00 0.765549E+11 0.874081E+10 0.00 0.00
August 0.00 0.00 0.704768E+11 0.112929E+11 0.00 0.00
September 0.00 0.00 0.265505E+11 0.929932E+10 0.00 0.00
October 0.00 0.00 0.117722E+11 0.746308E+10 0.00 0.00
November 0.00 0.00 0.440852E+10 0.551366E+10 0.00 0.00
December 0.142412E+10 0.00 0.121492E+09 0.294949E+10 0.00 0.00
             
Annual Sum or Average 0.139880E+11 0.00 0.291245E+12 0.770161E+11 0.00 0.00
Minimum of Months 0.00 0.00 19249109.70 0.276148E+10 0.00 0.00
Maximum of Months 0.110469E+11 0.00 0.765549E+11 0.112929E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 3383165.69 0.121796E+12 0.00 35.10
February 0.00 0.00 0.158739E+12 0.156378E+12 0.00 41.62
March 0.00 0.00 0.222015E+12 0.248655E+12 0.00 70.39
April 0.00 0.00 0.223204E+12 0.325694E+12 0.00 88.43
May 0.00 0.00 0.224752E+11 0.110389E+12 0.00 30.85
June 0.00 0.00 0.292250E+12 0.648078E+11 0.00 9.02
July 0.00 0.00 0.381050E+12 0.691339E+11 0.00 0.38
August 0.00 0.00 0.402103E+12 0.897666E+11 0.00 0.35
September 0.00 0.00 0.394863E+10 0.590418E+11 0.00 12.08
October 0.00 0.00 0.169996E+12 0.136039E+12 0.00 32.83
November 0.00 0.00 0.201866E+12 0.236063E+12 0.00 66.03
December 0.00 0.00 0.258978E+12 0.329789E+12 0.00 89.19
             
Annual Sum or Average 0.00 0.00 0.233663E+13 0.194755E+13 0.00 476.27
Minimum of Months 0.00 0.00 3383165.69 0.590418E+11 0.00 0.35
Maximum of Months 0.00 0.00 0.402103E+12 0.329789E+12 0.00 89.19



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.469326E+10 0.00 0.00
February 0.00 0.00 0.00 0.574541E+10 0.00 0.00
March 0.00 0.00 0.00 0.788545E+10 0.00 0.00
April 0.00 0.00 0.00 0.915799E+10 0.00 0.00
May 0.00 0.00 0.00 0.616155E+10 0.00 0.00
June 0.00 0.00 0.00 0.729505E+10 0.00 0.00
July 0.00 0.00 0.00 0.874717E+10 0.00 0.00
August 0.00 0.00 0.00 0.997242E+10 0.00 0.00
September 0.00 0.00 0.00 0.586772E+10 0.00 0.00
October 0.00 0.00 0.00 0.705513E+10 0.00 0.00
November 0.00 0.00 0.00 0.772080E+10 0.00 0.00
December 0.00 0.00 0.00 0.817162E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.884736E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.469326E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.997242E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.397460E+11 0.00 0.00
February 0.00 0.00 0.00 0.486402E+11 0.00 0.00
March 0.00 0.00 0.00 0.676704E+11 0.00 0.00
April 0.00 0.00 0.00 0.779403E+11 0.00 0.00
May 0.00 0.00 0.00 0.547200E+11 0.00 0.00
June 0.00 0.00 0.00 0.645311E+11 0.00 0.00
July 0.00 0.00 0.00 0.767779E+11 0.00 0.00
August 0.00 0.00 0.00 0.860820E+11 0.00 0.00
September 0.00 0.00 0.00 0.515558E+11 0.00 0.00
October 0.00 0.00 0.00 0.609468E+11 0.00 0.00
November 0.00 0.00 0.00 0.649854E+11 0.00 0.00
December 0.00 0.00 0.00 0.689904E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.762586E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.397460E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.860820E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.389921E+10 0.00 0.00
February 0.00 0.00 0.00 0.470229E+10 0.00 0.00
March 0.00 0.00 0.00 0.690634E+10 0.00 0.00
April 0.00 0.00 0.00 0.820017E+10 0.00 0.00
May 0.00 0.00 0.00 0.563187E+10 0.00 0.00
June 0.00 0.00 0.00 0.694171E+10 0.00 0.00
July 0.00 0.00 0.00 0.841263E+10 0.00 0.00
August 0.00 0.00 0.00 0.939047E+10 0.00 0.00
September 0.00 0.00 0.00 0.519129E+10 0.00 0.00
October 0.00 0.00 0.00 0.603466E+10 0.00 0.00
November 0.00 0.00 0.00 0.655891E+10 0.00 0.00
December 0.00 0.00 0.00 0.716649E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.790360E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.389921E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.939047E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.952048E+10 288.56 0.958012E+11 0.00 0.00 0.00 0.00 0.00
February 0.829771E+10 3610.96 0.531070E+11 0.00 0.00 0.00 0.00 0.00
March 0.107759E+11 278.72 0.290243E+11 0.00 0.00 0.00 0.00 0.00
April 0.124939E+11 0.572825E+10 0.429576E+10 0.00 0.00 0.00 0.00 0.00
May 0.146500E+11 0.459015E+11 0.410422E+09 0.00 0.00 0.00 0.00 0.00
June 0.169305E+11 0.104210E+12 15599893.83 0.00 0.00 0.00 0.00 0.00
July 0.191776E+11 0.140679E+12 1246907.48 0.00 0.00 0.00 0.00 0.00
August 0.192378E+11 0.112835E+12 29655487.95 0.00 0.00 0.00 0.00 0.00
September 0.129357E+11 0.242210E+11 0.749219E+09 0.00 0.00 0.00 0.00 0.00
October 0.109840E+11 0.398972E+10 0.432187E+10 0.00 0.00 0.00 0.00 0.00
November 0.972406E+10 0.559479E+09 0.169936E+11 0.00 0.00 0.00 0.00 0.00
December 0.952947E+10 1062893.78 0.695450E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.154257E+12 0.438125E+12 0.274295E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.829771E+10 278.72 1246907.48 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.192378E+11 0.140679E+12 0.958012E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.122954E+12 79687.54 0.134151E+13 0.00 0.00 0.00 0.00 0.00
February 0.104611E+12 61724729.79 0.829777E+12 0.00 0.00 0.00 0.00 0.00
March 0.109859E+12 0.470785E+10 0.550775E+12 0.00 0.00 0.00 0.00 0.00
April 0.107012E+12 0.550520E+11 0.149107E+12 0.00 0.00 0.00 0.00 0.00
May 0.135027E+12 0.438669E+12 0.209478E+11 0.00 0.00 0.00 0.00 0.00
June 0.152636E+12 0.953687E+12 0.353394E+10 0.00 0.00 0.00 0.00 0.00
July 0.158470E+12 0.118708E+13 0.946177E+09 0.00 0.00 0.00 0.00 0.00
August 0.151353E+12 0.937522E+12 0.518212E+10 0.00 0.00 0.00 0.00 0.00
September 0.115970E+12 0.237851E+12 0.366564E+11 0.00 0.00 0.00 0.00 0.00
October 0.967308E+11 0.481928E+11 0.141443E+12 0.00 0.00 0.00 0.00 0.00
November 0.975235E+11 0.596113E+10 0.441498E+12 0.00 0.00 0.00 0.00 0.00
December 0.116119E+12 178120.37 0.117217E+13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.146826E+13 0.386878E+13 0.469354E+13 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.967308E+11 79687.54 0.946177E+09 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.158470E+12 0.118708E+13 0.134151E+13 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.135361E+11 4814712.23 0.207687E+12 0.00 0.00 0.00 0.00 0.00
February 0.120099E+11 7252520.35 0.137018E+12 0.00 0.00 0.00 0.00 0.00
March 0.123205E+11 7324451.20 0.965210E+11 0.00 0.00 0.00 0.00 0.00
April 0.104675E+11 0.485663E+10 0.362344E+11 0.00 0.00 0.00 0.00 0.00
May 0.110578E+11 0.467508E+11 0.803066E+10 0.00 0.00 0.00 0.00 0.00
June 0.124175E+11 0.102742E+12 0.234538E+10 0.00 0.00 0.00 0.00 0.00
July 0.128323E+11 0.128762E+12 0.124205E+10 0.00 0.00 0.00 0.00 0.00
August 0.121295E+11 0.973381E+11 0.300910E+10 0.00 0.00 0.00 0.00 0.00
September 0.954863E+10 0.214093E+11 0.120849E+11 0.00 0.00 0.00 0.00 0.00
October 0.100657E+11 0.349811E+10 0.391401E+11 0.00 0.00 0.00 0.00 0.00
November 0.117639E+11 0.463047E+09 0.874457E+11 0.00 0.00 0.00 0.00 0.00
December 0.132431E+11 12223538.73 0.190276E+12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.141392E+12 0.405851E+12 0.821035E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.954863E+10 4814712.23 0.124205E+10 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.135361E+11 0.128762E+12 0.207687E+12 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.306736E+10 19249109.70 0.110469E+11 0.00 0.00 0.00 0.00 0.00
February 0.276148E+10 0.156135E+09 0.150776E+10 0.00 0.00 0.00 0.00 0.00
March 0.385722E+10 0.120275E+10 9182823.29 0.00 0.00 0.00 0.00 0.00
April 0.647065E+10 0.742352E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.752318E+10 0.320570E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.807700E+10 0.605015E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.874081E+10 0.765549E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.112929E+11 0.704768E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.929932E+10 0.265505E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.746308E+10 0.117722E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.551366E+10 0.440852E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.294949E+10 0.121492E+09 0.142412E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.770161E+11 0.291245E+12 0.139880E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.276148E+10 19249109.70 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.112929E+11 0.765549E+11 0.110469E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.274298E+11 3383165.69 0.00 0.00 0.00 0.939431E+11 0.00 0.00
February 0.445061E+11 0.158739E+12 0.00 0.00 0.00 0.111370E+12 0.00 0.00
March 0.594368E+11 0.222015E+12 0.00 0.00 0.00 0.188371E+12 0.00 0.00
April 0.879777E+11 0.223204E+12 0.00 0.00 0.00 0.236651E+12 0.00 0.00
May 0.274613E+11 0.224752E+11 0.00 0.00 0.00 0.825561E+11 0.00 0.00
June 0.405739E+11 0.292250E+12 0.00 0.00 0.00 0.241253E+11 0.00 0.00
July 0.681149E+11 0.381050E+12 0.00 0.00 0.00 0.101437E+10 0.00 0.00
August 0.888216E+11 0.402103E+12 0.00 0.00 0.00 0.940817E+09 0.00 0.00
September 0.265571E+11 0.394863E+10 0.00 0.00 0.00 0.323391E+11 0.00 0.00
October 0.477906E+11 0.169996E+12 0.00 0.00 0.00 0.878527E+11 0.00 0.00
November 0.585505E+11 0.201866E+12 0.00 0.00 0.00 0.176717E+12 0.00 0.00
December 0.900273E+11 0.258978E+12 0.00 0.00 0.00 0.238687E+12 0.00 0.00
                 
Annual Sum or Average 0.667248E+12 0.233663E+13 0.00 0.00 0.00 0.127457E+13 0.00 0.00
Minimum of Months 0.265571E+11 3383165.69 0.00 0.00 0.00 0.940817E+09 0.00 0.00
Maximum of Months 0.900273E+11 0.402103E+12 0.00 0.00 0.00 0.238687E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.375395E+10 0.297686E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.339066E+10 0.815117E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.375395E+10 0.155617E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363285E+10 0.213917E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.375395E+10 0.799389E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.363285E+10 0.129604E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.375395E+10 0.188705E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.375395E+10 0.237184E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363285E+10 0.742465E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.375395E+10 0.116344E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.363285E+10 0.153998E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.375395E+10 0.172946E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.441997E+11 0.163378E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.339066E+10 0.297686E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.375395E+10 0.237184E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.362401E+11 0.127309E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.327330E+11 0.626017E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.362401E+11 0.135406E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.350711E+11 0.194487E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.362401E+11 0.709772E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.350711E+11 0.120915E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.362401E+11 0.177837E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.362401E+11 0.222468E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.350711E+11 0.631021E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.362401E+11 0.998551E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.350711E+11 0.127713E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.362401E+11 0.147129E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.426698E+12 0.143522E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.327330E+11 0.127309E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.362401E+11 0.222468E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.372107E+10 0.551483E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.336096E+10 0.441808E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.372107E+10 0.113937E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.360103E+10 0.176721E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.372107E+10 0.622485E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.360103E+10 0.116331E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.372107E+10 0.174697E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.372107E+10 0.217737E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.360103E+10 0.513994E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.372107E+10 0.778680E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.360103E+10 0.104566E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.372107E+10 0.128602E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.438126E+11 0.127380E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.336096E+10 0.551483E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.372107E+10 0.217737E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.952048E+10 0.958012E+11 288.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.829771E+10 0.531070E+11 3610.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.107759E+11 0.290243E+11 278.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.124939E+11 0.429576E+10 0.572825E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.146500E+11 0.410422E+09 0.459015E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.169305E+11 15599893.83 0.104210E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.191776E+11 1246907.48 0.140679E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.192378E+11 29655487.95 0.112835E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.129357E+11 0.749219E+09 0.242210E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.109840E+11 0.432187E+10 0.398972E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.972406E+10 0.169936E+11 0.559479E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.952947E+10 0.695450E+11 1062893.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.154257E+12 0.274295E+12 0.438125E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.829771E+10 1246907.48 278.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.192378E+11 0.958012E+11 0.140679E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.122954E+12 0.134151E+13 79687.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.104611E+12 0.829777E+12 61724729.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.109859E+12 0.550775E+12 0.470785E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.107012E+12 0.149107E+12 0.550520E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.135027E+12 0.209478E+11 0.438669E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.152636E+12 0.353394E+10 0.953687E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.158470E+12 0.946177E+09 0.118708E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.151353E+12 0.518212E+10 0.937522E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115970E+12 0.366564E+11 0.237851E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.967308E+11 0.141443E+12 0.481928E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.975235E+11 0.441498E+12 0.596113E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116119E+12 0.117217E+13 178120.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.146826E+13 0.469354E+13 0.386878E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.967308E+11 0.946177E+09 79687.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.158470E+12 0.134151E+13 0.118708E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.135361E+11 0.207687E+12 4814712.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.120099E+11 0.137018E+12 7252520.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.123205E+11 0.965210E+11 7324451.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.104675E+11 0.362344E+11 0.485663E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.110578E+11 0.803066E+10 0.467508E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124175E+11 0.234538E+10 0.102742E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.128323E+11 0.124205E+10 0.128762E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.121295E+11 0.300910E+10 0.973381E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.954863E+10 0.120849E+11 0.214093E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.100657E+11 0.391401E+11 0.349811E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.117639E+11 0.874457E+11 0.463047E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.132431E+11 0.190276E+12 12223538.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.141392E+12 0.821035E+12 0.405851E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.954863E+10 0.124205E+10 4814712.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.135361E+11 0.207687E+12 0.128762E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.306736E+10 0.110469E+11 19249109.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.276148E+10 0.150776E+10 0.156135E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.385722E+10 9182823.29 0.120275E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.647065E+10 0.00 0.742352E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.752318E+10 0.00 0.320570E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.807700E+10 0.00 0.605015E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.874081E+10 0.00 0.765549E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.112929E+11 0.00 0.704768E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.929932E+10 0.00 0.265505E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.746308E+10 0.00 0.117722E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.551366E+10 0.00 0.440852E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.294949E+10 0.142412E+10 0.121492E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.770161E+11 0.139880E+11 0.291245E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.276148E+10 0.00 19249109.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.112929E+11 0.110469E+11 0.765549E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.274298E+11 0.00 3383165.69 0.00 0.00 0.00 0.00 0.00 0.943659E+11 0.00 0.00 0.00
February 0.445061E+11 0.00 0.158739E+12 0.00 0.00 0.00 0.00 0.00 0.111872E+12 0.00 0.00 0.00
March 0.594368E+11 0.00 0.222015E+12 0.00 0.00 0.00 0.00 0.00 0.189219E+12 0.00 0.00 0.00
April 0.879777E+11 0.00 0.223204E+12 0.00 0.00 0.00 0.00 0.00 0.237716E+12 0.00 0.00 0.00
May 0.274613E+11 0.00 0.224752E+11 0.00 0.00 0.00 0.00 0.00 0.829277E+11 0.00 0.00 0.00
June 0.405739E+11 0.00 0.292250E+12 0.00 0.00 0.00 0.00 0.00 0.242339E+11 0.00 0.00 0.00
July 0.681149E+11 0.00 0.381050E+12 0.00 0.00 0.00 0.00 0.00 0.101895E+10 0.00 0.00 0.00
August 0.888216E+11 0.00 0.402103E+12 0.00 0.00 0.00 0.00 0.00 0.945052E+09 0.00 0.00 0.00
September 0.265571E+11 0.00 0.394863E+10 0.00 0.00 0.00 0.00 0.00 0.324847E+11 0.00 0.00 0.00
October 0.477906E+11 0.00 0.169996E+12 0.00 0.00 0.00 0.00 0.00 0.882482E+11 0.00 0.00 0.00
November 0.585505E+11 0.00 0.201866E+12 0.00 0.00 0.00 0.00 0.00 0.177513E+12 0.00 0.00 0.00
December 0.900273E+11 0.00 0.258978E+12 0.00 0.00 0.00 0.00 0.00 0.239762E+12 0.00 0.00 0.00
                         
Annual Sum or Average 0.667248E+12 0.00 0.233663E+13 0.00 0.00 0.00 0.00 0.00 0.128030E+13 0.00 0.00 0.00
Minimum of Months 0.265571E+11 0.00 3383165.69 0.00 0.00 0.00 0.00 0.00 0.945052E+09 0.00 0.00 0.00
Maximum of Months 0.900273E+11 0.00 0.402103E+12 0.00 0.00 0.00 0.00 0.00 0.239762E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.375395E+10 0.00 0.00 0.00 0.939306E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.339066E+10 0.00 0.00 0.00 0.235474E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.375395E+10 0.00 0.00 0.00 0.413150E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363285E+10 0.00 0.00 0.00 0.552513E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.375395E+10 0.00 0.00 0.00 0.240760E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.363285E+10 0.00 0.00 0.00 0.366220E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.375395E+10 0.00 0.00 0.00 0.499322E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.375395E+10 0.00 0.00 0.00 0.621847E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363285E+10 0.00 0.00 0.00 0.223487E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.375395E+10 0.00 0.00 0.00 0.330118E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.363285E+10 0.00 0.00 0.00 0.408795E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.375395E+10 0.00 0.00 0.00 0.441767E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.441997E+11 0.00 0.00 0.00 0.442738E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.339066E+10 0.00 0.00 0.00 0.939306E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.375395E+10 0.00 0.00 0.00 0.621847E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.362401E+11 0.00 0.00 0.00 0.350585E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.327330E+11 0.00 0.00 0.00 0.159072E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.362401E+11 0.00 0.00 0.00 0.314302E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.350711E+11 0.00 0.00 0.00 0.428693E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.362401E+11 0.00 0.00 0.00 0.184799E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.350711E+11 0.00 0.00 0.00 0.294600E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.362401E+11 0.00 0.00 0.00 0.405377E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.362401E+11 0.00 0.00 0.00 0.498419E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.350711E+11 0.00 0.00 0.00 0.164847E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.362401E+11 0.00 0.00 0.00 0.247067E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.350711E+11 0.00 0.00 0.00 0.299143E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.362401E+11 0.00 0.00 0.00 0.327502E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.426698E+12 0.00 0.00 0.00 0.335888E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.327330E+11 0.00 0.00 0.00 0.350585E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.362401E+11 0.00 0.00 0.00 0.498419E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.372107E+10 0.00 0.00 0.00 0.178148E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.336096E+10 0.00 0.00 0.00 0.134133E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.372107E+10 0.00 0.00 0.00 0.318527E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.360103E+10 0.00 0.00 0.00 0.459914E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.372107E+10 0.00 0.00 0.00 0.191081E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.360103E+10 0.00 0.00 0.00 0.334067E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.372107E+10 0.00 0.00 0.00 0.469156E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.372107E+10 0.00 0.00 0.00 0.566940E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.360103E+10 0.00 0.00 0.00 0.159025E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.372107E+10 0.00 0.00 0.00 0.231359E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.360103E+10 0.00 0.00 0.00 0.295788E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.372107E+10 0.00 0.00 0.00 0.344542E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.438126E+11 0.00 0.00 0.00 0.352235E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.336096E+10 0.00 0.00 0.00 0.178148E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.372107E+10 0.00 0.00 0.00 0.566940E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.714185E+11 0.00 0.00 990659.99 0.00 0.238799E+10 0.125865E+10 0.00 0.31
February 0.564996E+11 0.00 0.00 27794191.58 0.00 61016382.95 0.289650E+10 0.00 0.32
March 0.522027E+11 0.00 0.00 96832849.07 0.00 0.00 0.117763E+11 0.00 0.38
April 0.135704E+11 0.00 0.00 0.163938E+09 0.00 0.00 0.435832E+11 0.00 0.59
May 0.471625E+10 0.760404E+09 0.00 0.128514E+09 0.00 0.00 0.380575E+11 0.00 0.76
June 0.201942E+10 0.104643E+11 0.00 0.320036E+09 75598197.90 0.00 0.243127E+11 0.00 0.92
July 0.642112E+09 0.154586E+11 0.00 0.234017E+09 0.243043E+09 0.00 0.185639E+11 0.00 0.88
August 0.119020E+10 0.118467E+11 0.00 0.175621E+09 32462660.35 0.00 0.315968E+11 0.00 1.17
September 0.578455E+10 0.398312E+09 0.00 0.157663E+09 0.00 0.00 0.477449E+11 0.00 0.92
October 0.165854E+11 0.00 0.00 0.331847E+09 0.00 0.00 0.450147E+11 0.00 0.62
November 0.297026E+11 0.00 0.00 0.252009E+09 0.00 0.00 0.320664E+11 0.00 0.48
December 0.641966E+11 0.00 0.00 15663969.59 0.00 0.00 0.510759E+10 0.00 0.31
                   
Annual Sum or Average 0.318528E+12 0.389283E+11 0.00 0.190493E+10 0.351104E+09 0.244900E+10 0.301979E+12 0.00 0.64
Minimum of Months 0.642112E+09 0.00 0.00 990659.99 0.00 0.00 0.125865E+10 0.00 0.31
Maximum of Months 0.714185E+11 0.154586E+11 0.00 0.331847E+09 0.243043E+09 0.238799E+10 0.477449E+11 0.00 1.17



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.446516E+11 0.00 0.00 14413127.04 0.00 88984174.48 0.159334E+11 0.00 0.25
February 0.333535E+11 0.00 0.00 0.186038E+09 0.00 0.00 0.156084E+11 0.00 0.26
March 0.246175E+11 0.00 0.00 0.421814E+09 0.00 0.00 0.318360E+11 0.00 0.34
April 0.854019E+10 0.00 0.00 0.274044E+09 22134261.43 0.00 0.486277E+11 0.00 0.61
May 0.509725E+10 0.174657E+09 0.00 0.184771E+09 0.00 0.00 0.424772E+11 0.00 0.84
June 0.328324E+10 0.526902E+10 0.00 0.370132E+09 0.343748E+09 0.00 0.270297E+11 0.00 0.97
July 0.359105E+10 0.760556E+10 0.00 0.224252E+09 0.111055E+10 0.00 0.192859E+11 0.00 0.91
August 0.418364E+10 0.498722E+10 0.00 0.187389E+09 0.104742E+09 0.00 0.326660E+11 0.00 1.18
September 0.538256E+10 52536882.26 0.00 0.198913E+09 0.00 0.00 0.470959E+11 0.00 0.88
October 0.129476E+11 0.00 0.00 0.466748E+09 0.00 0.00 0.404321E+11 0.00 0.55
November 0.159205E+11 0.00 0.00 0.452322E+09 0.00 0.00 0.342324E+11 0.00 0.39
December 0.345230E+11 0.00 0.00 0.100890E+09 0.00 0.00 0.233270E+11 0.00 0.25
                   
Annual Sum or Average 0.196092E+12 0.180890E+11 0.00 0.308173E+10 0.158118E+10 88984174.48 0.378552E+12 0.00 0.62
Minimum of Months 0.328324E+10 0.00 0.00 14413127.04 0.00 0.00 0.156084E+11 0.00 0.25
Maximum of Months 0.446516E+11 0.760556E+10 0.00 0.466748E+09 0.111055E+10 88984174.48 0.486277E+11 0.00 1.18



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.551938E+12 0.00 0.00 24060147.88 0.00 0.152169E+11 0.316660E+11 0.00 0.26
February 0.450667E+12 0.00 0.00 0.250972E+09 0.00 0.624678E+10 0.230087E+11 0.00 0.27
March 0.376222E+12 0.00 0.00 0.152593E+10 0.00 0.249486E+10 0.112778E+12 0.00 0.29
April 0.180676E+12 0.00 0.00 0.129721E+10 0.528044E+09 0.00 0.231751E+12 0.00 0.45
May 0.801011E+11 0.172354E+10 0.00 0.132662E+10 0.00 0.00 0.295948E+12 0.00 0.71
June 0.616614E+11 0.469915E+11 0.00 0.232598E+10 0.429218E+10 0.00 0.178814E+12 0.00 0.82
July 0.444757E+11 0.660410E+11 0.00 0.127725E+10 0.450054E+10 0.00 0.124300E+12 0.00 0.71
August 0.578697E+11 0.411449E+11 0.00 0.973912E+09 0.798090E+09 0.00 0.191646E+12 0.00 0.87
September 0.105162E+12 0.637065E+09 0.00 0.128151E+10 0.00 0.00 0.296114E+12 0.00 0.71
October 0.189523E+12 0.00 0.00 0.244855E+10 0.00 0.00 0.201590E+12 0.00 0.42
November 0.300056E+12 0.00 0.00 0.121235E+10 0.00 0.245581E+10 0.919519E+11 0.00 0.30
December 0.524038E+12 0.00 0.00 48312468.83 0.00 0.950057E+10 0.219401E+11 0.00 0.26
                   
Annual Sum or Average 0.292239E+13 0.156538E+12 0.00 0.139926E+11 0.101189E+11 0.359150E+11 0.180151E+13 0.00 0.51
Minimum of Months 0.444757E+11 0.00 0.00 24060147.88 0.00 0.00 0.219401E+11 0.00 0.26
Maximum of Months 0.551938E+12 0.660410E+11 0.00 0.244855E+10 0.450054E+10 0.152169E+11 0.296114E+12 0.00 0.87



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.277733E+11 0.00 0.00 0.00 0.00 0.197938E+11 0.00 0.00 0.21
February 0.282334E+11 0.00 0.00 0.00 0.00 0.105758E+11 0.00 0.00 0.23
March 0.354225E+11 0.00 0.00 0.00 0.00 0.597183E+10 0.00 0.00 0.27
April 0.303440E+11 0.00 0.00 21945789.28 58266153.19 0.142465E+10 0.549278E+10 0.00 0.44
May 0.211768E+11 84706493.86 0.00 51784901.11 0.00 0.162910E+09 0.136989E+11 0.00 0.70
June 0.110653E+11 0.374506E+10 0.00 0.122870E+09 0.117234E+10 0.00 0.128372E+11 0.00 0.83
July 0.721165E+10 0.440665E+10 0.00 58836392.71 0.195054E+10 0.00 0.937486E+10 0.00 0.71
August 0.127794E+11 0.288806E+10 0.00 39085436.55 0.440964E+09 1260653.13 0.101758E+11 0.00 0.87
September 0.274586E+11 0.00 0.00 21867855.25 0.00 16221404.61 0.803828E+10 0.00 0.69
October 0.310770E+11 0.00 0.00 9660719.95 0.00 0.160636E+10 0.872886E+09 0.00 0.41
November 0.266648E+11 0.00 273072.02 0.00 3752055.82 0.565644E+10 0.00 8016.77 0.28
December 0.264820E+11 0.00 0.00 0.00 0.00 0.168470E+11 0.00 0.00 0.21
                   
Annual Sum or Average 0.285689E+12 0.111245E+11 273072.02 0.326051E+09 0.362587E+10 0.620563E+11 0.604907E+11 8016.77 0.49
Minimum of Months 0.721165E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.21
Maximum of Months 0.354225E+11 0.440665E+10 273072.02 0.122870E+09 0.195054E+10 0.197938E+11 0.136989E+11 8016.77 0.87



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.109989E+10 0.00 0.00 0.00 0.00 0.123694E+11 0.00 0.00 0.43
February 0.280240E+10 0.00 0.00 0.00 0.00 0.753485E+10 0.00 0.00 0.44
March 0.643187E+10 0.00 0.00 0.00 0.00 0.411873E+10 0.00 0.00 0.49
April 0.743855E+10 0.00 0.00 4363779.89 4924218.26 0.409438E+09 0.102875E+10 0.00 0.74
May 0.438236E+10 37780400.41 0.00 14651285.53 0.00 644732.36 0.355351E+10 0.00 1.15
June 0.215063E+10 0.114251E+10 0.00 38198289.64 83450624.54 0.00 0.313349E+10 0.00 1.41
July 0.172411E+10 0.153028E+10 0.00 18305443.68 0.265956E+09 0.00 0.227076E+10 0.00 1.32
August 0.283472E+10 0.898372E+09 0.00 11757436.99 25249806.04 0.00 0.288382E+10 0.00 1.53
September 0.567983E+10 8919206.06 0.00 7970095.54 0.00 0.00 0.259244E+10 0.00 1.12
October 0.823640E+10 0.00 0.00 1334219.27 0.00 0.178171E+09 0.173980E+09 0.00 0.69
November 0.631647E+10 0.00 0.00 119763.85 0.00 0.212245E+10 38304078.52 0.00 0.50
December 0.208806E+10 0.00 0.00 0.00 0.00 0.994181E+10 0.00 0.00 0.41
                   
Annual Sum or Average 0.511853E+11 0.361787E+10 0.00 96700314.39 0.379580E+09 0.366755E+11 0.156751E+11 0.00 0.85
Minimum of Months 0.109989E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.41
Maximum of Months 0.823640E+10 0.153028E+10 0.00 38198289.64 0.265956E+09 0.123694E+11 0.355351E+10 0.00 1.53



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.277167E+10 0.00 0.00 0.00 0.00 0.124236E+11 0.00 0.00 0.76
February 0.479381E+10 0.00 0.00 201.23 0.00 0.692081E+10 2306891.58 0.00 0.77
March 0.727532E+10 0.00 0.00 10313765.13 0.00 0.404595E+10 0.849746E+09 0.00 0.87
April 0.692971E+10 124363.01 0.00 18814862.39 5465792.58 0.523105E+09 0.379234E+10 0.00 1.45
May 0.539133E+10 27534446.54 0.00 16346774.40 0.00 731924.13 0.410722E+10 0.00 2.08
June 0.259731E+10 0.861484E+09 0.00 45999759.93 0.210140E+09 0.00 0.412968E+10 0.00 2.52
July 0.194440E+10 0.126188E+10 0.00 29011921.19 0.461851E+09 0.00 0.307273E+10 0.00 2.41
August 0.400578E+10 0.658252E+09 0.00 13020106.25 0.171658E+09 628250.07 0.261051E+10 0.00 2.61
September 0.691914E+10 8499320.67 0.00 10703024.51 0.00 5733630.73 0.302308E+10 0.00 2.06
October 0.895223E+10 0.00 0.00 5509839.88 0.00 0.390814E+09 0.547057E+09 0.00 1.24
November 0.692329E+10 0.00 0.00 46458.24 0.00 0.268545E+10 15167129.72 0.00 0.88
December 0.268612E+10 0.00 0.00 0.00 0.00 0.109430E+11 0.00 0.00 0.73
                   
Annual Sum or Average 0.611901E+11 0.281777E+10 0.00 0.149767E+09 0.849115E+09 0.379398E+11 0.221498E+11 0.00 1.53
Minimum of Months 0.194440E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.73
Maximum of Months 0.895223E+10 0.126188E+10 0.00 45999759.93 0.461851E+09 0.124236E+11 0.412968E+10 0.00 2.61



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.508304E+10 0.00 0.00 5145682.60 0.00 0.114870E+11 0.344108E+10 0.00 0.64
February 0.564969E+10 0.00 0.00 54269154.49 0.00 0.640075E+10 0.444399E+10 0.00 0.72
March 0.710808E+10 0.00 0.00 70870064.94 0.00 0.479503E+10 0.529303E+10 0.00 0.82
April 0.736907E+10 4222335.30 0.00 39691668.69 3897283.24 0.977397E+09 0.762302E+10 0.00 1.44
May 0.641283E+10 52543282.76 0.00 22304157.22 0.00 48137156.87 0.527123E+10 0.00 1.73
June 0.432703E+10 0.135276E+10 0.00 27653532.39 0.218018E+09 0.00 0.286169E+10 0.00 1.91
July 0.302710E+10 0.191846E+10 0.00 14949859.20 0.525091E+09 0.00 0.246885E+10 0.00 1.80
August 0.502536E+10 0.132514E+10 0.00 14530190.39 67585716.74 778057.20 0.322422E+10 0.00 2.26
September 0.774475E+10 27668574.78 0.00 24550656.02 0.00 6790199.69 0.625808E+10 0.00 2.02
October 0.942719E+10 0.00 0.00 51359938.42 0.00 0.784901E+09 0.410271E+10 0.00 1.29
November 0.739597E+10 0.00 0.00 40009287.55 0.00 0.306150E+10 0.301537E+10 0.00 0.80
December 0.522795E+10 0.00 0.00 6988081.06 0.00 0.103207E+11 0.187434E+10 0.00 0.60
                   
Annual Sum or Average 0.737980E+11 0.468078E+10 0.00 0.372322E+09 0.814592E+09 0.378830E+11 0.498776E+11 0.00 1.34
Minimum of Months 0.302710E+10 0.00 0.00 5145682.60 0.00 0.00 0.187434E+10 0.00 0.60
Maximum of Months 0.942719E+10 0.191846E+10 0.00 70870064.94 0.525091E+09 0.114870E+11 0.762302E+10 0.00 2.26



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.638998E+10 0.00 0.00 46231.68 0.00 0.117184E+11 0.163376E+09 0.00 0.92
February 0.792865E+10 0.00 0.00 5456457.06 0.00 0.580840E+10 0.437240E+09 0.00 0.93
March 0.115810E+11 0.00 0.00 25299515.60 0.00 0.145830E+10 0.197847E+10 0.00 1.09
April 0.888281E+10 149696.12 0.00 24779049.66 6579190.72 7229629.80 0.493962E+10 0.00 1.86
May 0.630131E+10 54781743.13 0.00 18475072.11 0.00 0.00 0.473772E+10 0.00 2.49
June 0.407834E+10 0.133784E+10 0.00 26855966.15 0.112252E+09 0.00 0.269866E+10 0.00 2.76
July 0.249814E+10 0.196053E+10 0.00 20237211.44 0.325504E+09 0.00 0.264173E+10 0.00 2.64
August 0.374979E+10 0.117302E+10 0.00 17100210.00 16580255.86 0.00 0.395242E+10 0.00 3.17
September 0.858505E+10 10477059.81 0.00 9492887.92 0.00 0.00 0.310147E+10 0.00 2.47
October 0.108372E+11 0.00 0.00 13605254.75 0.00 94869165.93 0.114023E+10 0.00 1.55
November 0.105058E+11 0.00 0.00 3053106.17 0.00 0.801426E+09 0.285888E+09 0.00 1.07
December 0.109565E+11 0.00 0.00 920.50 0.00 0.541739E+10 6615552.31 0.00 0.88
                   
Annual Sum or Average 0.922946E+11 0.453680E+10 0.00 0.164402E+09 0.460915E+09 0.253060E+11 0.260834E+11 0.00 1.82
Minimum of Months 0.249814E+10 0.00 0.00 920.50 0.00 0.00 6615552.31 0.00 0.88
Maximum of Months 0.115810E+11 0.196053E+10 0.00 26855966.15 0.325504E+09 0.117184E+11 0.493962E+10 0.00 3.17



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.353041E+10 0.00 0.00 0.00 0.00 0.185280E+12 0.00 0.00 0.64
February 0.135952E+11 0.00 0.00 0.00 0.00 0.136903E+12 0.00 0.00 0.66
March 0.452380E+11 0.00 0.00 0.00 0.00 0.102626E+12 0.00 0.00 0.69
April 0.791190E+11 0.00 0.00 555469.44 0.165125E+09 0.283927E+11 0.103287E+10 0.00 0.90
May 0.717198E+11 0.383198E+09 0.00 49717171.38 0.00 0.219389E+10 0.147237E+11 0.00 1.29
June 0.409922E+11 0.107209E+11 0.00 0.111725E+09 0.220151E+10 3815492.76 0.142753E+11 0.00 1.48
July 0.263824E+11 0.139051E+11 0.00 60403849.07 0.328121E+10 0.00 0.131362E+11 0.00 1.29
August 0.474087E+11 0.719801E+10 0.00 26924686.24 0.199482E+10 0.132380E+09 0.102547E+11 0.00 1.56
September 0.867977E+11 0.117692E+09 0.00 6972624.79 0.00 0.391847E+10 0.532979E+10 0.00 1.33
October 0.807667E+11 0.00 0.00 0.00 0.00 0.252611E+11 0.00 0.00 0.88
November 0.361534E+11 0.00 0.00 0.00 0.00 0.822663E+11 0.00 0.00 0.71
December 0.492808E+10 0.00 0.00 0.00 0.00 0.169954E+12 0.00 0.00 0.64
                   
Annual Sum or Average 0.536632E+12 0.323249E+11 0.00 0.256299E+09 0.764267E+10 0.736932E+12 0.587526E+11 0.00 1.01
Minimum of Months 0.353041E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.64
Maximum of Months 0.867977E+11 0.139051E+11 0.00 0.111725E+09 0.328121E+10 0.185280E+12 0.147237E+11 0.00 1.56



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.881596E+10 0.00 0.00 0.00 0.00 0.131148E+12 0.00 0.00 0.74
February 0.227166E+11 0.00 0.00 1684067.92 0.00 0.895750E+11 0.116751E+09 0.00 0.76
March 0.458568E+11 0.00 0.00 80578471.03 0.00 0.617048E+11 0.612242E+10 0.00 0.83
April 0.494724E+11 0.00 0.00 0.168097E+09 0.150616E+09 0.166426E+11 0.308572E+11 0.00 1.30
May 0.472439E+11 0.298477E+09 0.00 0.161489E+09 1515385.11 0.996273E+09 0.351110E+11 0.00 1.96
June 0.250790E+11 0.879900E+10 0.00 0.428414E+09 0.241564E+10 3458679.69 0.364941E+11 0.00 2.44
July 0.179728E+11 0.131615E+11 0.00 0.254520E+09 0.335760E+10 4358415.93 0.269612E+11 0.00 2.26
August 0.323083E+11 0.628689E+10 0.00 0.112674E+09 0.237279E+10 0.156898E+09 0.212784E+11 0.00 2.35
September 0.564270E+11 0.116896E+09 0.00 99367432.06 0.00 0.244334E+10 0.247532E+11 0.00 1.85
October 0.568841E+11 0.00 0.00 49054563.34 0.00 0.200497E+11 0.421293E+10 0.00 1.06
November 0.288072E+11 0.00 0.00 1887939.38 0.00 0.595848E+11 97288038.72 0.00 0.82
December 0.698817E+10 0.00 0.00 0.00 0.00 0.122570E+12 0.00 0.00 0.73
                   
Annual Sum or Average 0.398572E+12 0.286627E+11 0.00 0.135777E+10 0.829817E+10 0.504879E+12 0.186004E+12 0.00 1.43
Minimum of Months 0.698817E+10 0.00 0.00 0.00 0.00 3458679.69 0.00 0.00 0.73
Maximum of Months 0.568841E+11 0.131615E+11 0.00 0.428414E+09 0.335760E+10 0.131148E+12 0.364941E+11 0.00 2.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.472443E+11 0.00 0.00 56097560.78 0.00 0.133277E+12 0.382204E+11 0.00 0.74
February 0.549375E+11 0.00 0.00 0.603397E+09 0.00 0.824653E+11 0.484498E+11 0.00 0.84
March 0.629292E+11 0.00 0.00 0.800783E+09 0.00 0.665115E+11 0.570742E+11 0.00 0.90
April 0.595182E+11 0.176098E+09 0.00 0.392877E+09 61378251.29 0.225303E+11 0.708166E+11 0.00 1.43
May 0.607564E+11 0.584018E+09 0.00 0.207546E+09 0.00 0.222740E+10 0.461843E+11 0.00 1.70
June 0.421341E+11 0.135375E+11 0.00 0.232120E+09 0.293823E+10 4128348.94 0.245449E+11 0.00 1.87
July 0.282318E+11 0.197129E+11 0.00 0.113758E+09 0.414365E+10 0.00 0.211146E+11 0.00 1.68
August 0.449967E+11 0.131385E+11 0.00 0.122325E+09 0.140424E+10 16113963.37 0.257866E+11 0.00 2.11
September 0.705724E+11 0.410081E+09 0.00 0.249666E+09 0.00 0.265921E+10 0.582776E+11 0.00 2.01
October 0.785924E+11 0.00 0.00 0.583499E+09 0.00 0.187711E+11 0.392557E+11 0.00 1.29
November 0.535114E+11 0.00 0.00 0.378515E+09 0.00 0.616700E+11 0.269890E+11 0.00 0.86
December 0.387836E+11 0.00 0.00 57694196.34 0.00 0.137040E+12 0.176546E+11 0.00 0.71
                   
Annual Sum or Average 0.642208E+12 0.475591E+11 0.00 0.379828E+10 0.854750E+10 0.527172E+12 0.474368E+12 0.00 1.35
Minimum of Months 0.282318E+11 0.00 0.00 56097560.78 0.00 0.00 0.176546E+11 0.00 0.71
Maximum of Months 0.785924E+11 0.197129E+11 0.00 0.800783E+09 0.414365E+10 0.137040E+12 0.708166E+11 0.00 2.11



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.211003E+11 0.00 0.00 0.00 0.00 0.162795E+12 0.00 0.00 0.98
February 0.359102E+11 0.00 0.00 24703339.32 0.00 0.109264E+12 0.194325E+10 0.00 1.00
March 0.626167E+11 0.00 0.00 0.130789E+09 0.00 0.747707E+11 0.103949E+11 0.00 1.08
April 0.696634E+11 0.00 0.00 0.152182E+09 0.162103E+09 0.202000E+11 0.281166E+11 0.00 1.60
May 0.653426E+11 0.574891E+09 0.00 0.137801E+09 0.00 0.158819E+10 0.284223E+11 0.00 2.28
June 0.409338E+11 0.110741E+11 0.00 0.183382E+09 0.286254E+10 15195373.96 0.176684E+11 0.00 2.52
July 0.267072E+11 0.159004E+11 0.00 93283247.37 0.377188E+10 0.00 0.154454E+11 0.00 2.22
August 0.456367E+11 0.890089E+10 0.00 58280024.31 0.167955E+10 5736179.98 0.143760E+11 0.00 2.61
September 0.788603E+11 0.139399E+09 0.00 59763508.77 7433305.26 0.236107E+10 0.182921E+11 0.00 2.20
October 0.808037E+11 0.00 0.00 86711385.53 0.00 0.178099E+11 0.710726E+10 0.00 1.38
November 0.476835E+11 0.00 0.00 0.00 0.00 0.683585E+11 0.00 0.00 1.08
December 0.192636E+11 0.00 0.00 0.00 0.00 0.151332E+12 0.00 0.00 0.97
                   
Annual Sum or Average 0.594522E+12 0.365896E+11 0.00 0.926895E+09 0.848351E+10 0.608500E+12 0.141766E+12 0.00 1.66
Minimum of Months 0.192636E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.97
Maximum of Months 0.808037E+11 0.159004E+11 0.00 0.183382E+09 0.377188E+10 0.162795E+12 0.284223E+11 0.00 2.61



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.112386E+09 0.00 0.00 0.00 0.00 0.150048E+11 0.00 0.00 0.54
February 0.870065E+09 0.00 0.00 0.00 0.00 0.114477E+11 0.00 0.00 0.59
March 0.295619E+10 0.00 0.00 0.00 0.00 0.101743E+11 0.00 0.00 0.68
April 0.724397E+10 0.00 0.00 4088.16 18475336.83 0.430966E+10 40321666.35 0.00 1.07
May 0.855057E+10 17851577.00 0.00 2869254.45 0.00 0.897488E+09 0.978348E+09 0.00 1.61
June 0.525357E+10 0.787631E+09 0.00 4013568.78 0.522722E+09 21367334.41 0.129848E+10 0.00 1.80
July 0.316851E+10 0.961678E+09 0.00 3468495.83 0.751548E+09 10940535.77 0.129151E+10 0.00 1.53
August 0.564209E+10 0.426659E+09 0.00 1829687.52 0.445131E+09 0.136830E+09 0.913479E+09 0.00 1.97
September 0.934260E+10 0.00 0.00 362026.95 0.00 0.142897E+10 0.210160E+09 0.00 1.68
October 0.589422E+10 0.00 0.00 0.00 0.00 0.472851E+10 0.00 0.00 1.02
November 0.204026E+10 0.00 958203.79 0.00 85471.75 0.821055E+10 0.00 349630.49 0.72
December 0.120257E+09 0.00 0.00 0.00 0.00 0.136350E+11 0.00 0.00 0.54
                   
Annual Sum or Average 0.511947E+11 0.219382E+10 958203.79 12547121.70 0.173796E+10 0.700061E+11 0.473229E+10 349630.49 1.15
Minimum of Months 0.112386E+09 0.00 0.00 0.00 0.00 10940535.77 0.00 0.00 0.54
Maximum of Months 0.934260E+10 0.961678E+09 958203.79 4013568.78 0.751548E+09 0.150048E+11 0.129848E+10 349630.49 1.97



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.128208E+09 0.00 0.00 0.00 0.00 0.102119E+11 0.00 0.00 0.57
February 0.147010E+10 0.00 0.00 0.00 0.00 0.695960E+10 0.00 0.00 0.62
March 0.367408E+10 0.00 0.00 1382002.23 0.00 0.520981E+10 0.106554E+09 0.00 0.73
April 0.428543E+10 0.00 0.00 11986540.39 12651831.97 0.199336E+10 0.219938E+10 0.00 1.24
May 0.464545E+10 13688719.57 0.00 12869633.34 0.00 0.359084E+09 0.286331E+10 0.00 1.95
June 0.231743E+10 0.755410E+09 0.00 35959362.01 0.269608E+09 16715817.20 0.355685E+10 0.00 2.45
July 0.140282E+10 0.106725E+10 0.00 22157405.04 0.350001E+09 9534461.26 0.274061E+10 0.00 2.20
August 0.309397E+10 0.424783E+09 0.00 9371911.85 0.255319E+09 61627912.98 0.194755E+10 0.00 2.41
September 0.520544E+10 0.00 0.00 7492348.93 0.00 0.808161E+09 0.189366E+10 0.00 1.91
October 0.438818E+10 0.00 0.00 1839814.89 0.00 0.271308E+10 0.186504E+09 0.00 1.09
November 0.220064E+10 0.00 663558.50 0.00 58530.69 0.481809E+10 0.00 232040.84 0.76
December 0.187101E+09 0.00 0.00 0.00 0.00 0.922522E+10 0.00 0.00 0.57
                   
Annual Sum or Average 0.329988E+11 0.226113E+10 663558.50 0.103059E+09 0.887638E+09 0.423862E+11 0.154944E+11 232040.84 1.38
Minimum of Months 0.128208E+09 0.00 0.00 0.00 0.00 9534461.26 0.00 0.00 0.57
Maximum of Months 0.520544E+10 0.106725E+10 663558.50 35959362.01 0.350001E+09 0.102119E+11 0.355685E+10 232040.84 2.45



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.334905E+10 0.00 0.00 3217136.38 0.00 0.105549E+11 0.190949E+10 0.00 0.56
February 0.389765E+10 0.00 0.00 43099995.90 0.00 0.695420E+10 0.286170E+10 0.00 0.67
March 0.474048E+10 0.00 0.00 52309004.62 0.00 0.640830E+10 0.360097E+10 0.00 0.78
April 0.492275E+10 7327381.54 0.00 32516549.77 13478680.91 0.312353E+10 0.639910E+10 0.00 1.41
May 0.671065E+10 25750503.56 0.00 15572195.95 0.00 0.865292E+09 0.408968E+10 0.00 1.85
June 0.471090E+10 0.102554E+10 0.00 15604502.74 0.507935E+09 0.112062E+09 0.266731E+10 0.00 2.07
July 0.284225E+10 0.133869E+10 0.00 10071618.51 0.725980E+09 46879946.83 0.241864E+10 0.00 1.81
August 0.486956E+10 0.827183E+09 0.00 11458318.27 0.303756E+09 0.131593E+09 0.267156E+10 0.00 2.33
September 0.697697E+10 0.00 0.00 19177103.38 0.00 0.122087E+10 0.513887E+10 0.00 2.14
October 0.589020E+10 0.00 0.00 45449706.69 0.00 0.328084E+10 0.335185E+10 0.00 1.32
November 0.386683E+10 0.00 916414.31 26988699.10 161479.08 0.556127E+10 0.163349E+10 339659.68 0.78
December 0.253002E+10 0.00 0.00 2402604.75 0.00 0.109405E+11 0.602325E+09 0.00 0.55
                   
Annual Sum or Average 0.553073E+11 0.322449E+10 916414.31 0.277867E+09 0.155131E+10 0.492003E+11 0.373450E+11 339659.68 1.36
Minimum of Months 0.253002E+10 0.00 0.00 2402604.75 0.00 46879946.83 0.602325E+09 0.00 0.55
Maximum of Months 0.697697E+10 0.133869E+10 916414.31 52309004.62 0.725980E+09 0.109405E+11 0.639910E+10 339659.68 2.33



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.103876E+10 0.00 0.00 0.00 0.00 0.108432E+11 0.00 0.00 0.66
February 0.211817E+10 0.00 0.00 1571295.70 0.00 0.743672E+10 0.141951E+09 0.00 0.72
March 0.384817E+10 0.00 0.00 10594277.01 0.00 0.594411E+10 0.754672E+09 0.00 0.86
April 0.509155E+10 0.00 0.00 14486545.37 14558169.06 0.230372E+10 0.283926E+10 0.00 1.51
May 0.557983E+10 27111962.73 0.00 12855517.56 0.00 0.535904E+09 0.305345E+10 0.00 2.28
June 0.363303E+10 0.853992E+09 0.00 18265304.24 0.362775E+09 18807795.85 0.220778E+10 0.00 2.55
July 0.225460E+10 0.114775E+10 0.00 9397587.17 0.480077E+09 1673864.91 0.181643E+10 0.00 2.20
August 0.402695E+10 0.588127E+09 0.00 6036933.34 0.235778E+09 65934774.05 0.162034E+10 0.00 2.66
September 0.650170E+10 0.00 0.00 6008704.80 0.00 0.800222E+09 0.186949E+10 0.00 2.21
October 0.539265E+10 0.00 0.00 7063736.43 0.00 0.247627E+10 0.627731E+09 0.00 1.29
November 0.284988E+10 0.00 821057.61 0.00 67349.91 0.522475E+10 0.00 165432.03 0.88
December 0.672517E+09 0.00 0.00 0.00 0.00 0.101510E+11 0.00 0.00 0.66
                   
Annual Sum or Average 0.430078E+11 0.261698E+10 821057.61 86279901.63 0.109326E+10 0.458024E+11 0.149311E+11 165432.03 1.54
Minimum of Months 0.672517E+09 0.00 0.00 0.00 0.00 1673864.91 0.00 0.00 0.66
Maximum of Months 0.650170E+10 0.114775E+10 821057.61 18265304.24 0.480077E+09 0.108432E+11 0.305345E+10 165432.03 2.66



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 27343061.37 0.00 0.00 4733386.17 0.00 0.00 0.111572E+10 0.00 0.28
February 0.00 0.00 0.00 71444452.89 0.00 0.00 0.830139E+09 0.00 0.28
March 0.00 0.00 0.00 0.117549E+09 0.00 0.00 0.786529E+09 0.00 0.30
April 0.00 0.00 0.00 65241705.50 0.00 0.00 0.517889E+09 0.00 0.29
May 0.00 3605765.89 0.00 8254164.91 0.00 0.00 0.335530E+09 0.00 0.29
June 0.00 75187217.90 0.00 29815615.77 0.00 0.00 0.138650E+09 0.00 0.30
July 0.00 0.106396E+09 0.00 21932664.48 0.00 0.00 54836554.16 0.00 0.28
August 0.00 70825099.14 0.00 24122080.56 0.00 0.00 83848241.01 0.00 0.31
September 0.00 596581.55 0.00 8910794.26 0.00 0.00 0.364051E+09 0.00 0.29
October 0.00 0.00 0.00 59060896.12 0.00 0.00 0.508624E+09 0.00 0.28
November 0.00 0.00 0.00 0.101324E+09 0.00 0.00 0.603916E+09 0.00 0.28
December 0.00 0.00 0.00 77180642.68 0.00 0.00 0.982187E+09 0.00 0.28
                   
Annual Sum or Average 27343061.37 0.256611E+09 0.00 0.589569E+09 0.00 0.00 0.632192E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 4733386.17 0.00 0.00 54836554.16 0.00 0.28
Maximum of Months 27343061.37 0.106396E+09 0.00 0.117549E+09 0.00 0.00 0.111572E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.374342E+10 0.00 0.00 20886937.74 0.00 0.00 0.762860E+10 0.00 0.28
February 0.00 0.00 0.00 0.578899E+09 0.00 0.00 0.842296E+10 0.00 0.28
March 0.00 0.00 0.00 0.105369E+10 0.00 0.00 0.798704E+10 0.00 0.30
April 0.00 0.00 0.00 0.605022E+09 0.00 0.00 0.522629E+10 0.00 0.29
May 0.00 35322943.48 0.00 70119937.47 0.00 0.00 0.336975E+10 0.00 0.29
June 0.00 0.745763E+09 0.00 0.278267E+09 0.00 0.00 0.140852E+10 0.00 0.30
July 0.00 0.105612E+10 0.00 0.204841E+09 0.00 0.00 0.564802E+09 0.00 0.28
August 0.00 0.699463E+09 0.00 0.226521E+09 0.00 0.00 0.864337E+09 0.00 0.31
September 0.00 4909731.73 0.00 72277793.01 0.00 0.00 0.366167E+10 0.00 0.29
October 0.00 0.00 0.00 0.517928E+09 0.00 0.00 0.515870E+10 0.00 0.28
November 0.00 0.00 0.00 0.878904E+09 0.00 0.00 0.617365E+10 0.00 0.28
December 0.00 0.00 0.00 0.679780E+09 0.00 0.00 0.989083E+10 0.00 0.28
                   
Annual Sum or Average 0.374342E+10 0.254157E+10 0.00 0.518714E+10 0.00 0.00 0.603571E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 20886937.74 0.00 0.00 0.564802E+09 0.00 0.28
Maximum of Months 0.374342E+10 0.105612E+10 0.00 0.105369E+10 0.00 0.00 0.989083E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.791456E+09 0.00 0.00 653231.22 0.00 0.00 0.330864E+09 0.00 0.28
February 2067644.60 0.00 0.00 42585740.92 0.00 0.00 0.853590E+09 0.00 0.28
March 0.00 0.00 0.00 92914313.43 0.00 0.00 0.811130E+09 0.00 0.30
April 0.00 0.00 0.00 56725583.38 0.00 0.00 0.526405E+09 0.00 0.29
May 20104810.31 3565592.67 0.00 5772874.92 0.00 0.00 0.318103E+09 0.00 0.29
June 0.00 74549297.94 0.00 26428360.73 0.00 0.00 0.142462E+09 0.00 0.30
July 0.00 0.105618E+09 0.00 19501001.14 0.00 0.00 57607584.23 0.00 0.28
August 0.00 69401572.64 0.00 21900893.85 0.00 0.00 89058509.68 0.00 0.31
September 30769962.33 505062.22 0.00 5269877.63 0.00 0.00 0.338077E+09 0.00 0.29
October 0.00 0.00 0.00 42152934.37 0.00 0.00 0.525577E+09 0.00 0.28
November 0.00 0.00 0.00 77038626.55 0.00 0.00 0.628262E+09 0.00 0.28
December 0.00 0.00 0.00 60724465.36 0.00 0.00 0.994091E+09 0.00 0.28
                   
Annual Sum or Average 0.844398E+09 0.253640E+09 0.00 0.451668E+09 0.00 0.00 0.561523E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 653231.22 0.00 0.00 57607584.23 0.00 0.28
Maximum of Months 0.791456E+09 0.105618E+09 0.00 92914313.43 0.00 0.00 0.994091E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.119088E+10 0.00 0.00 0.351895E+12 0.00 3.88
February 0.845472E+10 0.00 0.00 0.347074E+10 0.00 0.00 0.464167E+12 0.00 7.06
March 0.292717E+10 0.00 0.00 0.797030E+10 0.00 0.00 0.791459E+12 0.00 12.36
April 0.00 0.00 0.00 0.513818E+10 0.00 0.00 0.103990E+13 0.00 28.29
May 996971.51 397846.05 0.00 0.880773E+09 0.00 0.00 0.328857E+12 0.00 12.84
June 0.625841E+09 0.376739E+10 0.00 0.249642E+10 15624102.96 0.00 0.278248E+12 0.00 22.66
July 23196456.39 0.104657E+11 0.00 0.425865E+10 0.00 0.00 0.444680E+12 0.00 37.29
August 0.00 0.388260E+10 0.00 0.416372E+10 0.00 0.00 0.672742E+12 0.00 51.20
September 0.00 0.00 0.00 0.915721E+09 0.00 0.00 0.292273E+12 0.00 12.67
October 0.349257E+10 0.00 0.00 0.343409E+10 0.00 0.00 0.504041E+12 0.00 13.72
November 11415530.70 0.00 0.00 0.791914E+10 0.00 0.00 0.779963E+12 0.00 14.85
December 0.00 0.00 0.00 0.609137E+10 0.00 0.00 0.104214E+13 0.00 13.55
                   
Annual Sum or Average 0.155359E+11 0.181161E+11 0.00 0.479300E+11 15624102.96 0.00 0.699036E+13 0.00 19.29
Minimum of Months 0.00 0.00 0.00 0.880773E+09 0.00 0.00 0.278248E+12 0.00 3.88
Maximum of Months 0.845472E+10 0.104657E+11 0.00 0.797030E+10 15624102.96 0.00 0.104214E+13 0.00 51.20



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:26:37

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.327427E+12 0.495178E+11 0.00 0.232527E+13 0.673732E+12
February 0.430577E+12 0.431226E+11 0.00 0.230230E+13 0.742463E+12
March 0.586513E+12 0.300599E+11 0.00 0.304101E+13 0.888998E+12
April 0.703485E+12 0.272805E+11 0.00 0.348015E+13 0.848064E+12
May 0.797482E+12 0.131076E+11 0.00 0.296161E+13 0.886608E+12
June 0.807506E+12 0.443220E+10 0.00 0.197787E+13 0.207006E+13
July 0.820660E+12 0.175116E+10 0.00 0.175003E+13 0.266946E+13
August 0.687726E+12 0.581062E+10 0.00 0.254734E+13 0.238680E+13
September 0.511586E+12 0.120312E+11 0.00 0.292833E+13 0.547221E+12
October 0.309685E+12 0.193145E+11 0.00 0.310858E+13 0.587560E+12
November 0.185102E+12 0.339389E+11 0.00 0.278289E+13 0.801933E+12
December 0.246582E+12 0.531862E+11 0.00 0.301366E+13 0.116615E+13
           
Annual Sum or Average 0.641433E+13 0.293553E+12 0.00 0.322190E+14 0.142690E+14
Minimum of Months 0.185102E+12 0.175116E+10 0.00 0.175003E+13 0.547221E+12
Maximum of Months 0.820660E+12 0.531862E+11 0.00 0.348015E+13 0.266946E+13