Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2024-07-03 12:21:47
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 35677.68 | 770.24 | 770.24 |
Net Site Energy | 35677.68 | 770.24 | 770.24 |
Total Source Energy | 106346.34 | 2295.89 | 2295.89 |
Net Source Energy | 106346.34 | 2295.89 | 2295.89 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3190.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3021.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1006.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2679.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1226.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 325.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10351.15 |
Humidification | 891.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.70 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 426.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 32487.63 | 3190.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12963.02 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3190.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3021.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 1006.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 56.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2679.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 1226.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 325.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10351.15 |
Humidification | General | 891.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.70 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 426.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 3190.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3021.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 1006.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2679.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 1226.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 325.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10351.15 |
Humidification | Unassigned | 891.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.70 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 426.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 185.04 | 68.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 701.37 | 68.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 185.04 | 68.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 701.37 | 68.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 32487.628 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 32487.628 | 100.00 |
Total On-Site and Utility Electric Sources | 32487.628 | 100.00 |
Total Electricity End Uses | 32487.628 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 12963.02 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 12963.02 | 100.00 |
Total Water End Uses | 12963.02 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 40.50 |
Time Setpoint Not Met During Occupied Cooling | 120.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5327.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS SZVAV FAN | AIRLOOP DATACENTER BASEMENT SYS11 FAN | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 11.6510 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 11.6510 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 11.6510 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.6510 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 11.6510 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.6510 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 11.6510 | 18.58 | 484.4232 | |
Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.6100 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-AUG-15:09 | 02-JAN-06:19 | - | - | - | - | - | - | - | - | - | - | 30-AUG-15:09 |
Heating | 0.00 | 3138528.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 504144.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235096.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 285852.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 100801.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 57461.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 29906.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2481535.09 | 3138528.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3138528.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 504144.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 285852.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 100801.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 57461.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 29906.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3458.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9569.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17769.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3186.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8307.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8485.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3885.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1029.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 2823.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1350.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 102888.32 | 3458.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 74.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 206.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 183.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 83.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 22.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 60.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 29.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2221.23 | 74.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 74.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 206.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 183.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 83.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 22.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 60.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 29.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2221.23 | 74.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 7.01 | 0.302142 | 0.300000 | 2.10 |
DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | 31.40 | 0.019020 | 0.500000 | 15.70 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 7.41 | 0.256620 | 0.300000 | 2.22 | 0.684320 | 0.500000 | 0.001485 | 0.000247 | 2.22 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 70.39 | 0.270230 | 0.300000 | 21.12 | 0.720613 | 0.500000 | 0.001410 | 0.005804 | 27.72 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 7.89 | 0.241017 | 0.300000 | 2.37 | 0.642713 | 0.500000 | 0.001581 | 0.001498 | 7.20 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.32 | 0.180407 | 0.300000 | 0.397136 | 0.481085 | 0.500000 | 0.002112 | 0.000265 | 1.27 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.61 | 0.095585 | 0.300000 | 0.483043 | 0.300000 | 0.500000 | 0.003986 | 0.000176 | 0.850438 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.91 | 0.125226 | 0.300000 | 0.572146 | 0.333937 | 0.500000 | 0.003042 | 0.000282 | 1.36 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.96 | 0.078502 | 0.300000 | 0.588157 | 0.300000 | 0.500000 | 0.004853 | 0.000149 | 0.716559 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 19.38 | 0.123218 | 0.300000 | 5.81 | 0.328582 | 0.500000 | 0.003092 | 0.004018 | 19.38 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 17.04 | 0.300000 | 0.500000 | 0.004219 | 0.002618 | 12.63 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 19.02 | 0.125557 | 0.300000 | 5.71 | 0.334819 | 0.500000 | 0.003034 | 0.003943 | 19.02 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 18.07 | 0.085189 | 0.300000 | 5.42 | 0.300000 | 0.500000 | 0.004472 | 0.002585 | 12.47 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 2.49 | 0.095730 | 0.300000 | 0.748423 | 0.300000 | 0.500000 | 0.003980 | 0.000517 | 2.49 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.75 | 0.087878 | 0.300000 | 0.525407 | 0.300000 | 0.500000 | 0.004336 | 0.000336 | 1.62 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 2.46 | 0.097163 | 0.300000 | 0.737396 | 0.300000 | 0.500000 | 0.003921 | 0.000509 | 2.46 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.98 | 0.077899 | 0.300000 | 0.592708 | 0.300000 | 0.500000 | 0.004891 | 0.000336 | 1.62 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 28188.78 | 0.000247 | 584.24 | |
CORE_MID VAV BOX REHEAT COIL | 663484.30 | 0.005804 | 15537.58 | |
CORE_TOP VAV BOX REHEAT COIL | 171181.62 | 0.001498 | 4000.77 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 30234.88 | 0.000265 | 706.31 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 20172.43 | 0.000176 | 471.23 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 32246.68 | 0.000282 | 753.28 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 17005.98 | 0.000149 | 397.32 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 459261.51 | 0.004018 | 10725.34 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 299273.48 | 0.002618 | 6989.01 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 450730.08 | 0.003943 | 10526.19 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 295424.81 | 0.002585 | 6899.16 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 59090.56 | 0.000517 | 1379.82 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 38423.25 | 0.000336 | 897.21 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 58220.95 | 0.000509 | 1359.52 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 38415.57 | 0.000336 | 897.03 | |
VAV_BOT WITH REHEAT HEATING COIL | 46172.68 | 0.000404 | 788.07 | |
VAV_MID WITH REHEAT HEATING COIL | 480548.45 | 0.004204 | 8147.09 | |
VAV_TOP WITH REHEAT HEATING COIL | 39421.70 | 0.000345 | 687.87 | |
CAV_BAS HEATING COIL | 0.000875 | 2622.73 | 100000.00 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 557057.84 | 0.000875 | 2622.73 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.734336 |
DATACENTER_MID_ZN_6 DIRECT AIR | 7.04 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.727677 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 7.11 | 4.26 | 14.21 | 5.28 | 12.31 | 12.31 | 0.300000 | 0.428978 | 12.31 |
VAV_MID WITH REHEAT | 71.95 | 43.17 | 143.90 | 91.23 | 116.27 | 116.27 | 0.300000 | 0.784633 | 116.27 |
VAV_TOP WITH REHEAT | 8.29 | 4.97 | 16.57 | 15.40 | 14.20 | 15.40 | 0.300000 | 1.00 | 15.40 |
CAV_BAS | 2.10 | 2.10 | 7.01 | 2.10 | 7.01 | 7.01 | 1.00 | 0.300000 | 7.01 |
AIRLOOP DATACENTER BASEMENT | 15.70 | 15.70 | 31.40 | 15.70 | 31.40 | 31.40 | 1.00 | 0.499995 | 31.40 |
AIRLOOP DATACENTER BOT | 0.734336 | 0.734336 | 0.734336 | 0.734336 | 0.734336 | 0.734336 | 1.00 | 1.000000 | 0.734336 |
AIRLOOP DATACENTER MID | 7.04 | 7.04 | 7.04 | 7.04 | 7.04 | 7.04 | 1.00 | 1.00 | 7.04 |
AIRLOOP DATACENTER TOP | 0.727677 | 0.727677 | 0.727677 | 0.727677 | 0.727677 | 0.727677 | 1.00 | 1.00 | 0.727677 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 12.31 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 116.27 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 15.40 | |
CAV_BAS_OA_CONTROLLER | 7.01 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 31.40 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.734336 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 7.04 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.727677 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.34 | 6.67 | 11.11 | 0.009722 | 0.008500 | 261248.01 | 0.009331 | 12.31 |
VAV_MID WITH REHEAT COOLING COIL | 25.45 | 6.67 | 11.11 | 0.009874 | 0.008500 | 2538007.54 | 0.090652 | 116.27 |
VAV_TOP WITH REHEAT COOLING COIL | 25.16 | 6.67 | 11.12 | 0.009629 | 0.008500 | 318847.48 | 0.011388 | 15.40 |
CAV_BAS COOLING COIL | 24.50 | 6.67 | 11.10 | 0.009802 | 0.008500 | 139468.04 | 0.004981 | 7.01 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 27.05 | 6.67 | 15.04 | 0.008593 | 0.008500 | 455998.94 | 0.016287 | 31.40 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 12.31 |
VAV_MID WITH REHEAT FAN | 116.27 |
VAV_TOP WITH REHEAT FAN | 15.40 |
CAV_BAS SZVAV FAN | 7.01 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | 31.40 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.009331 | 0.000051 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000404 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.090652 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.004204 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.011388 | 0.000042 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000345 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | Design Size Minimum Supply Air Temperature [C] | User-Specified Minimum Supply Air Temperature [C] | User-Specified Maximum Supply Air Temperature [C] | User-Specified Nominal Cooling Capacity [W] | Design Size Maximum Supply Air Temperature [C] | |
CAV_BAS_UNITARY_PACKAGE_DX | 7.01 | 7.01 | 7.01 | 2.10 | 139468.04 | 100000.00 | 1.00 | 5.33 | 12.89 | 32.11 | ||
AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | 31.40 | 31.40 | 31.40 | 15.70 | 455998.94 | 100000.00 | 1.00 | 15.89 | 29.11 | |||
AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | 0.734336 | 0.734336 | 0.734336 | 0.734336 | 26055.99 | 1.00 | 12155.87 | 29.11 | ||||
AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | 7.04 | 7.04 | 7.04 | 7.04 | 250040.84 | 1.00 | 116612.90 | 29.11 | ||||
AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | 0.727677 | 0.727677 | 0.727677 | 0.727677 | 25821.52 | 1.00 | 12045.63 | 29.11 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000255 | 0.000037 | 96450.70 | 100000.00 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | 0.734336 | 1262.79 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | 7.04 | 12114.14 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | 0.727677 | 1251.34 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
AIRLOOP DATACENTER BOT COOLING COIL | 0.734340 | 0.367168 | 0.489560 | 12155.87 | 6077.94 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER MID COOLING COIL | 7.04 | 3.52 | 4.70 | 116612.90 | 58306.45 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.727680 | 0.363838 | 0.485120 | 12045.63 | 6022.81 | 0.800660 | 0.800660 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BOT HEATING COIL | 26055.99 |
AIRLOOP DATACENTER MID HEATING COIL | 250040.84 |
AIRLOOP DATACENTER TOP HEATING COIL | 25821.52 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.132640 | 27332.23 | |
HEATSYS1 PUMP | 0.029985 | 9030.24 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.132640 | 15.92 |
HEATSYS1 | 0.029985 | 3.60 |
COOLSYS1_SUPPLY | 0.132640 | 15.92 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.132640 | 0.132640 | 556757.12 | 6.67 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3427497.68 | 3427497.68 | 0.029985 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.066320 | 12615.08 |
COOLSYS1 CHILLER2 PUMP | 0.066320 | 12615.08 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.132640 | 0.066865 | 1872041.94 | 1871975.60 | 0.093817 |
COOLSYS1 CHILLER2 | 0.132640 | 0.066865 | 1872041.94 | 1871975.60 | 0.093817 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.187634 | 22.52 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.187634 | 65428.07 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 75.65 | 2241076.02 | 15.13 | 280134.50 |
TOWERWATERSYS COOLTOWER 2 | 75.65 | 2241076.02 | 15.13 | 280134.50 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 11.651 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 16.493 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 11.651 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 496.074 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 32383.100 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 32383.100 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 9130.649 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 9130.649 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
26 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
27 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
35 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
47 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
48 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
49 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
50 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
51 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
52 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
53 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
54 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
55 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
56 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
57 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
58 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
59 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
60 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
61 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
62 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
63 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
64 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
65 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
66 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
67 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
68 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
69 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
70 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
71 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
72 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
73 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
74 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
75 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
76 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
77 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
78 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
79 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
80 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
81 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
82 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
83 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
84 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
85 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
86 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
87 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
88 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
89 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
90 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
91 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
92 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
93 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
94 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
95 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
96 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
97 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
98 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
99 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
100 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
101 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
102 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
103 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
104 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
105 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
106 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
107 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
108 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
109 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
110 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
111 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
112 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
113 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
114 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
115 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
116 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
117 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
118 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
119 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
120 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
121 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone BASEMENT | 1.2500 |
3 | Zone CORE_BOTTOM | 1.2500 |
4 | Zone CORE_MID | 1.2500 |
5 | Zone CORE_TOP | 1.2500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.2500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.2500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.2500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone BASEMENT | 1.1500 |
3 | Zone CORE_BOTTOM | 1.1500 |
4 | Zone CORE_MID | 1.1500 |
5 | Zone CORE_TOP | 1.1500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.1500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.1500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.1500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 83933.55409 | 96523.58721 | 6.09539 | 7.00970 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | -10.70000 | 1.50390E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 88753.74413 | 102066.80575 | 6.44514 | 7.41191 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 4842.72501 | 6053.40626 | 0.34942 | 1.07782 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 843011.55824 | 969463.29198 | 61.20531 | 70.38611 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 309992.34856 | 387490.43570 | 22.17951 | 27.72439 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 93656.29344 | 107704.73746 | 6.86237 | 7.89173 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 32.10000 | 1.41196E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 79571.49555 | 99464.36943 | 5.76336 | 7.20421 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 15709.55306 | 18065.98602 | 1.15112 | 1.32379 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 32.10000 | 1.41196E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 14044.99505 | 17556.24381 | 1.01961 | 1.27452 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 19107.95300 | 21974.14595 | 1.40013 | 1.61014 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.41123E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 9369.95679 | 11712.44598 | 0.68035 | 0.85044 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 22632.55081 | 26027.43343 | 1.65839 | 1.90715 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 31.73000 | 1.41190E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 14977.44057 | 18721.80072 | 1.08762 | 1.35953 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 23266.08092 | 26755.99306 | 1.70480 | 1.96052 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 7903.03131 | 9878.78914 | 0.57325 | 0.71656 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 151162.35167 | 173836.70442 | 11.07724 | 12.73883 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 32.10000 | 1.41196E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 213231.33790 | 266539.17237 | 15.50553 | 19.38191 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 202250.18860 | 232587.71689 | 14.82083 | 17.04395 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 28.44933 | 1.41131E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 138950.02051 | 173687.52564 | 10.10432 | 12.63040 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 223226.64589 | 256710.64278 | 16.35804 | 18.81175 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 31.79167 | 1.41191E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 209277.35747 | 261596.69683 | 15.21701 | 19.02126 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 214382.85387 | 246540.28195 | 15.70989 | 18.06637 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 137165.50671 | 171456.88339 | 9.97425 | 12.46781 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 18329.10760 | 21078.47374 | 1.34320 | 1.54468 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 27428.14584 | 34285.18230 | 1.99579 | 2.49474 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 20781.69819 | 23898.95292 | 1.52292 | 1.75136 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 28.65900 | 1.41134E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 17835.08149 | 22293.85186 | 1.29778 | 1.62222 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 25342.87034 | 29144.30089 | 1.85717 | 2.13575 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 27025.07182 | 33781.33977 | 1.96639 | 2.45799 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 23443.76554 | 26960.33037 | 1.71799 | 1.97569 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 17831.41446 | 22289.26807 | 1.29753 | 1.62191 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8714.88588 | 10022.11876 | 0.63855 | 0.73434 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 29.58400 | 1.41151E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -10.70000 | 1.50390E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 83602.67890 | 96143.08073 | 6.12573 | 7.04459 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 29.58400 | 1.41151E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -10.70000 | 1.50390E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8635.84366 | 9931.22021 | 0.63276 | 0.72768 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.76900 | 1.41154E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -10.70000 | 1.50390E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372606.43500 | 428497.40025 | 27.30092 | 31.39606 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 25.36600 | 1.41076E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:20:00 | -10.70000 | 1.50390E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 184121.79 | 12.30569 | 12.30569 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 57184.96 | 5.27887 | 5.27887 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1718589.46 | 116.26547 | 116.26547 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 574735.53 | 91.22577 | 91.22577 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 210753.14 | 14.20495 | 14.20495 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 57238.21 | 15.40107 | 15.40107 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 |
7 | CAV_BAS | Cooling | Sensible | 98437.56 | 7.00970 | 7.00970 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 62139.59 | 1.20016 | 1.20016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 423532.43 | 31.39639 | 31.39639 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 16292.91 | 0.33839 | 0.33839 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 9916.02 | 0.73434 | 0.73434 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 752.66 | 1.56323E-002 | 1.56323E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 95145.16 | 7.04459 | 7.04459 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 7526.65 | 0.15632 | 0.15632 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 9830.02 | 0.72768 | 0.72768 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 752.66 | 1.56323E-002 | 1.56323E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 7.00970 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.30214 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 2.10291 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.41191 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25662 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.22357 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68432 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.48469E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.46608E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.22357 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 28188.77917 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.46608E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 584.24004 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 70.38611 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27023 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 21.11583 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72061 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.40991E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.80445E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 27.72439 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 663484.29604 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.80445E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 15537.57625 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.89173 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24102 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.36752 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64271 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.58080E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.49757E-003 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.20421 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 171181.61751 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49757E-003 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4000.76965 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.32379 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18041 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.39714 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48109 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.11189E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.64508E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.27452 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30234.87606 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.64508E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 706.31386 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.61014 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.55846E-002 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.48304 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.98600E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.76477E-004 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.85044 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20172.43438 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.76477E-004 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 471.23199 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.90715 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12523 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.57215 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33394 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.04249E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.82108E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.35953 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 32246.68413 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.82108E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 753.27939 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.96052 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.85020E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.58816 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.85338E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.48776E-004 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71656 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17005.97937 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.48776E-004 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 397.32240 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 19.38191 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12322 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.81457 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32858 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.09207E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.01782E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.38191 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 459261.50550 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.01782E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 10725.33988 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 17.04395 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.21932E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.61817E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 12.63040 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 299273.47539 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.61817E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6989.01312 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 19.02126 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12556 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.70638 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33482 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.03447E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.94318E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.02126 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 450730.07785 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.94318E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 10526.19472 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.06637 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.51887E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.41991 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.47243E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.58451E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 12.46781 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 295424.80749 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.58451E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6899.15833 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.49474 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.57295E-002 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.74842 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.97996E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.16950E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.49474 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 59090.55666 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.16950E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1379.81749 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.75136 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.78776E-002 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.52541 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.33558E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.36143E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.62222 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 38423.24859 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.36143E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 897.21216 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.45799 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.71632E-002 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.73740 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.92124E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.09342E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.45799 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 58220.94505 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.09342E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1359.51801 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.97569 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.78993E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.59271 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.89093E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.36076E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.62191 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 38415.56851 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.36076E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 897.03076 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.73434 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.04459 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.72768 |
215 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 31.39606 |
216 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 1.90203E-002 |
217 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
218 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 15.69803 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.10676 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.26406 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 14.21352 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.27887 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 12.30569 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 12.30569 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.42898 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 71.94980 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 43.16988 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 143.89960 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 91.22577 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 116.26547 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 116.26547 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.78463 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 8.28575 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.97145 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 16.57151 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 15.40107 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 14.20495 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 15.40107 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 1.00000 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.10291 |
244 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.10291 |
245 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.00970 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.10291 |
247 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.00970 |
248 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 7.00970 |
249 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.30000 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 15.69803 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 15.69803 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 31.39606 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 15.69803 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 31.39639 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 31.39639 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.49999 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.73434 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.73434 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.73434 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.73434 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.73434 |
264 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.73434 |
265 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.04459 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.04459 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.04459 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 7.04459 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.04459 |
272 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 7.04459 |
273 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
274 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.72768 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.72768 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.72768 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.72768 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.72768 |
280 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.72768 |
281 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
282 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
283 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 12.30569 |
284 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 116.26547 |
285 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 15.40107 |
286 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 7.00970 |
287 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 31.39639 |
288 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.73434 |
289 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 7.04459 |
290 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.72768 |
291 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 12.30569 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.34444 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.11327 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.72203E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 261248.01075 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.33117E-003 |
299 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 12.30569 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 46172.67773 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.03939E-004 |
302 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 788.07347 |
303 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 12.30569 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.33117E-003 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.10322E-005 |
306 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.03939E-004 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 116.26547 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.45276 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.11376 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.87423E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2538007.53700 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.06517E-002 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 116.26547 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 480548.44693 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.20405E-003 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 8147.09271 |
319 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 116.26547 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.06517E-002 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.25297E-006 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.20405E-003 |
323 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 15.40107 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.15621 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.12049 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.62866E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 318847.47610 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.13885E-002 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 15.40107 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 39421.69956 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.44878E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 687.87299 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 15.40107 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.13885E-002 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.18133E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.44878E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.00970 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.00970 |
342 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.00970 |
343 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.00970 |
344 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.10291 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.50008 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.10405 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.80170E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 139468.04172 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.98148E-003 |
352 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.00970 |
353 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 139468.04172 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
355 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
356 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.72740 |
357 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
358 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
359 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Minimum Supply Air Temperature [C] | 5.33042 |
360 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 12.88890 |
361 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 32.11110 |
362 | Fan:VariableVolume | CAV_BAS SZVAV FAN | Design Size Maximum Flow Rate [m3/s] | 7.00970 |
363 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 31.39639 |
364 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
365 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 31.39639 |
366 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 31.39639 |
367 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 31.39639 |
368 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 15.69819 |
369 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.05302 |
370 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
371 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 15.04394 |
372 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.59326E-003 |
373 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
374 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Coil Load [W] | 455998.93693 |
375 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.62872E-002 |
376 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 31.39639 |
377 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 455998.93693 |
378 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Capacity [W] | 557057.84114 |
379 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
380 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
381 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.72740 |
382 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
383 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
384 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 15.88890 |
385 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 29.11110 |
386 | Fan:VariableVolume | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Design Size Maximum Flow Rate [m3/s] | 31.39639 |
387 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.54587E-004 |
388 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
389 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
390 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
391 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.73434 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
393 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.73434 |
394 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1262.79342 |
395 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.73434 |
396 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.73434 |
397 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.73434 |
398 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.73434 |
399 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.73434 |
400 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.36717 |
401 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.48956 |
402 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 12155.87000 |
403 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6077.93500 |
404 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
405 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
406 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 12155.87000 |
407 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26055.99008 |
408 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
409 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
410 | Coil:Heating:Fuel | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Nominal Capacity [W] | 26055.99008 |
411 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.04459 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
413 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.04459 |
414 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 12114.14276 |
415 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.04459 |
416 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.04459 |
417 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.04459 |
418 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 7.04459 |
419 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.04459 |
420 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.52229 |
421 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.69639 |
422 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 116612.90000 |
423 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 58306.45000 |
424 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
425 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
426 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 116612.90000 |
427 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 250040.83661 |
428 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
429 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
430 | Coil:Heating:Fuel | AIRLOOP DATACENTER MID HEATING COIL | Design Size Nominal Capacity [W] | 250040.83661 |
431 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.72768 |
432 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
433 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.72768 |
434 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1251.34088 |
435 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.72768 |
436 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.72768 |
437 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.72768 |
438 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.72768 |
439 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.72768 |
440 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.36384 |
441 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.48512 |
442 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 12045.63000 |
443 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6022.81500 |
444 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
445 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
446 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 12045.63000 |
447 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25821.51751 |
448 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
449 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
450 | Coil:Heating:Fuel | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Nominal Capacity [W] | 25821.51751 |
451 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.13264 |
452 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 27332.23413 |
453 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.13264 |
454 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 15.91681 |
455 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.13264 |
456 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.13264 |
457 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 556757.12181 |
458 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 6.67000 |
459 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.99852E-002 |
460 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 3.59823 |
461 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.99852E-002 |
462 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 9030.23896 |
463 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
464 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3427497.67592 |
465 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 3427497.68000 |
466 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.99852E-002 |
467 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.13264 |
468 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 15.91681 |
469 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 6.63201E-002 |
470 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 12615.07944 |
471 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 6.63201E-002 |
472 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 12615.07944 |
473 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.13264 |
474 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.68650E-002 |
475 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1872041.94387 |
476 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1871975.60000 |
477 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 9.38168E-002 |
478 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.13264 |
479 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.68650E-002 |
480 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1872041.94387 |
481 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1871975.60000 |
482 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 9.38168E-002 |
483 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
484 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
485 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
486 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
487 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
488 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.18763 |
489 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 22.51603 |
490 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.18763 |
491 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 65428.06989 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 75.65175 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 2241076.01949 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 15.13035 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 280134.50244 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 75.65175 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 2241076.01949 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 15.13035 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 280134.50244 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 26759.58 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 629406.14 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 162390.80 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 28682.26 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 19136.55 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 30590.77 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 16132.68 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 435678.26 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 283905.69 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 427584.91 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 280254.64 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 56056.26 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 36450.22 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 55231.31 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 36442.94 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 38144.42 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 391822.60 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 33971.97 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94836.89 |
20 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | 94836.89 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 302747.64 | 213545.43 | 89202.21 | 0.71 | 35872.62 | 363.84 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2897037.84 | 2034016.58 | 863021.26 | 0.70 | 342460.22 | 3473.42 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 374608.14 | 265351.82 | 109256.32 | 0.71 | 44517.95 | 451.53 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 170080.87 | 120858.84 | 49222.03 | 0.71 | 20979.43 | 212.78 |
5 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | 559845.32 | 430633.13 | 129212.19 | 0.77 | 53899.88 | 546.68 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | 11580.4 | 9.16 | 9.16 | |||
2 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | 111092.0 | 10.40 | 10.40 | |||
3 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | 11475.3 | 9.16 | 9.16 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 6.37 | 21.74 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 6.37 | 21.74 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 2.2888783189E-003 | 1.7034910522E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.5301134848E-002 | 9.3424408229E-002 | Pass | Pass | 7.1097681398E-002 | 0.2560845024 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 2.8636940916E-002 | 1.9257251065E-002 | Pass | Pass | 0.4921757587 | 0.4851747258 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1057578796 | 0.1383435812 | Pass | Pass | 1.3891947122 | 5.0008849389 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.9395381760E-002 | 5.6657599304E-002 | Pass | Pass | 0.2321730253 | 1.4845056621 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.3181124951E-002 | 0.1028323514 | Pass | Pass | 0.2145887511 | 1.0113418735 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1483274972 | 0.1591922362 | Pass | Pass | 0.3442043783 | 1.8417486212 | Pass | Fail |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 7.1588015666E-002 | 6.0567981511E-002 | Pass | Pass | 7.5794218440E-002 | 0.2613943910 | Pass | Fail |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.7329516270 | 0.7471992913 | Pass | Pass | 0.6969880920 | 0.6161067393 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6292765788 | 0.7333700362 | Pass | Pass | 0.8562252528 | 1.8044609521 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5284160051 | 0.6394690743 | Pass | Pass | 0.6924974058 | 0.6881785661 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6399530430 | 0.6877685180 | Pass | Pass | 0.7408994407 | 0.7004747580 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.9413086396 | 0.9568272579 | Pass | Pass | 0.6566170147 | 0.5903112839 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.8395993245 | 0.9204779516 | Pass | Pass | 0.6787695894 | 0.6095197828 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.6928713892 | 0.8607924074 | Pass | Pass | 1.0598695322 | 4.2632053332 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.8525468571 | 0.9038239172 | Pass | Pass | 0.6873442778 | 0.6200538547 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.9038577988E-002 | 1.8066556522E-002 | Pass | Pass | 7.5015051901E-002 | 0.2641926628 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.9135559536E-002 | 6.2522187821E-002 | Pass | Pass | 0.4842859657 | 0.4833116584 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.2950746287 | 0.2281524542 | Pass | Pass | 0.4874562762 | 0.4913844525 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.1035238734E-003 | 9.1767459879E-003 | Pass | Pass | 8.3947757856E-002 | 0.2566480200 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.8263422412E-002 | 1.2243004601E-002 | Pass | Pass | 8.0929731042E-003 | 9.2959157055E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.6145356470E-002 | 1.7964949443E-002 | Pass | Pass | 9.9720561935E-003 | 1.1776770894E-002 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.4454444924E-002 | 3.2370707626E-002 | Pass | Pass | 2.4012115460E-003 | 1.8274859192E-003 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6821.45 | 210.94 | 0.00 | 13461.55 | 22295.98 | 42789.96 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
North Total or Average | 1390.74 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 3.241 | 0.391 | 0.431 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 11.6510 | 2779.43 | 32383.10 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 333.79 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.6510 | 24961.20 | 290822.99 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 2997.66 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.6510 | 3134.13 | 36515.73 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.6510 | 3134.20 | 36516.53 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 11.6510 | 783.68 | 9130.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 94.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 22.3674 | 362.03 | 8097.60 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 83.47 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
Interior Lighting Total | 11.7515 | 46320.38 | 544334.28 | 1723.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 64082.80 | AstronomicalClock | - | 83.64 | 83.64 | 1006.15 | |
Exterior Lighting Total | 64082.80 | 1006.15 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3703894.04 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 3427497.68 | 0.79 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1871975.60 | 6.11 | 1862841.37 | 6.08 | 6.37 | 21.74 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1871975.60 | 6.11 | 1862841.37 | 6.08 | 6.37 | 21.74 |
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 2241076.02 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 2241076.02 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 261248.01 | 302747.64 | 213545.43 | 89202.21 | 0.71 | - | 35872.62 | 363.84 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2538007.54 | 2897037.84 | 2034016.58 | 863021.26 | 0.70 | - | 342460.22 | 3473.42 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 318847.48 | 374608.14 | 265351.82 | 109256.32 | 0.71 | - | 44517.95 | 451.53 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 139468.04 | 170080.87 | 120858.84 | 49222.03 | 0.71 | - | 20979.43 | 212.78 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | 455998.94 | 559845.32 | 430633.13 | 129212.19 | 0.77 | - | 53899.88 | 546.68 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | 12155.87 | 9732.72 | 2423.15 | 0.80 | 3.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | 116612.90 | 93367.28 | 23245.62 | 0.80 | 3.50 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 12045.63 | 9644.45 | 2401.18 | 0.80 | 3.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
AIRLOOP DATACENTER BOT COOLING COIL | 11580.4 | 9.16 | 9.16 | ||||
AIRLOOP DATACENTER MID COOLING COIL | 111092.0 | 10.40 | 10.40 | ||||
AIRLOOP DATACENTER TOP COOLING COIL | 11475.3 | 9.16 | 9.16 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 28188.78 | 26759.58 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 663484.30 | 629406.14 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 171181.62 | 162390.80 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 30234.88 | 28682.26 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 20172.43 | 19136.55 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 32246.68 | 30590.77 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 17005.98 | 16132.68 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 459261.51 | 435678.26 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 299273.48 | 283905.69 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 450730.08 | 427584.91 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 295424.81 | 280254.64 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 59090.56 | 56056.26 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 38423.25 | 36450.22 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 58220.95 | 55231.31 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 38415.57 | 36442.94 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 46172.68 | 38144.42 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 480548.45 | 391822.60 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 39421.70 | 33971.97 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94836.89 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | 100000.00 | 94836.89 | - |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | 26055.99 | 0.80 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | 250040.84 | 0.79 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | 25821.52 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 12.31 | 26901.50 | 2186.10 | 1.00 | 1.12 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 116.27 | 254168.31 | 2186.10 | 1.00 | 1.08 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 15.40 | 33525.82 | 2176.85 | 1.00 | 1.11 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
CAV_BAS SZVAV FAN | Fan:VariableVolume | 0.61 | 1337.13 | 7.01 | 15405.78 | 2197.78 | 1.00 | 1.13 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 0.61 | 637.69 | 31.40 | 32594.43 | 1038.16 | 1.00 | 1.19 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.73 | 1262.79 | 1719.64 | 1.00 | 1.37 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 7.04 | 12114.14 | 1719.64 | 1.00 | 1.09 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.73 | 1251.34 | 1719.64 | 1.00 | 1.37 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.83 | 0.132640 | 27332.23 | 206063.11 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.029985 | 9030.24 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.066320 | 12615.08 | 190215.15 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.066320 | 12615.08 | 190215.15 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 209234.68 | 0.187634 | 65428.07 | 348701.22 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 83933.55 | 96523.59 | 34.73 | 6.095 | 7.010 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 26.62 | 0.01411 | 1.200 | 0.00 |
CORE_BOTTOM | 88753.74 | 102066.81 | 40.89 | 6.445 | 7.412 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00885 | 26.62 | 0.01411 | 1.078 | 0.00 |
CORE_MID | 843011.56 | 969463.29 | 388.39 | 61.205 | 70.386 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00887 | 26.62 | 0.01411 | 10.778 | 0.00 |
CORE_TOP | 93656.29 | 107704.74 | 43.15 | 6.862 | 7.892 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00882 | 32.10 | 0.01412 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 15709.55 | 18065.99 | 57.64 | 1.151 | 1.324 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00888 | 32.10 | 0.01412 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 19107.95 | 21974.15 | 108.80 | 1.400 | 1.610 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00871 | 28.03 | 0.01411 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 22632.55 | 26027.43 | 83.04 | 1.658 | 1.907 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 24.00 | 24.00 | 0.00877 | 31.73 | 0.01412 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 23266.08 | 26755.99 | 132.47 | 1.705 | 1.961 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00867 | 31.26 | 0.01412 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 151162.35 | 173836.70 | 554.66 | 11.077 | 12.739 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00908 | 32.10 | 0.01412 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 202250.19 | 232587.72 | 1151.57 | 14.821 | 17.044 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00880 | 28.45 | 0.01411 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 223226.65 | 256710.64 | 819.06 | 16.358 | 18.812 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00890 | 31.79 | 0.01412 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 214382.85 | 246540.28 | 1220.65 | 15.710 | 18.066 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00878 | 31.26 | 0.01412 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 18329.11 | 21078.47 | 67.25 | 1.343 | 1.545 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00905 | 32.10 | 0.01412 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 20781.70 | 23898.95 | 118.33 | 1.523 | 1.751 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00883 | 28.66 | 0.01411 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 25342.87 | 29144.30 | 92.99 | 1.857 | 2.136 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00891 | 31.85 | 0.01412 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 23443.77 | 26960.33 | 133.48 | 1.718 | 1.976 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00879 | 31.26 | 0.01412 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8714.89 | 10022.12 | 276.83 | 0.639 | 0.734 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00857 | 29.58 | 0.01412 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 83602.68 | 96143.08 | 2655.69 | 6.126 | 7.045 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00857 | 29.58 | 0.01412 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8635.84 | 9931.22 | 274.32 | 0.633 | 0.728 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 27.00 | 27.00 | 0.00857 | 29.77 | 0.01412 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372606.44 | 428497.40 | 546.78 | 27.301 | 31.396 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00853 | 25.37 | 0.01411 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | 21.00 | 22.73 | 0.00150 | -10.70 | 0.00150 | 1.200 | 0.00 |
CORE_BOTTOM | 4842.73 | 6053.41 | 2.43 | 0.349 | 1.078 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 1.078 | 0.00 |
CORE_MID | 309992.35 | 387490.44 | 155.24 | 22.180 | 27.724 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 10.778 | 0.00 |
CORE_TOP | 79571.50 | 99464.37 | 39.85 | 5.763 | 7.204 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 14045.00 | 17556.24 | 56.02 | 1.020 | 1.275 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 9369.96 | 11712.45 | 57.99 | 0.680 | 0.850 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 14977.44 | 18721.80 | 59.73 | 1.088 | 1.360 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 7903.03 | 9878.79 | 48.91 | 0.573 | 0.717 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 213231.34 | 266539.17 | 850.44 | 15.506 | 19.382 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00754 | -10.70 | 0.00150 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 138950.02 | 173687.53 | 859.95 | 10.104 | 12.630 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -10.70 | 0.00150 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 209277.36 | 261596.70 | 834.65 | 15.217 | 19.021 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -10.70 | 0.00150 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 137165.51 | 171456.88 | 848.90 | 9.974 | 12.468 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00752 | -10.70 | 0.00150 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 27428.15 | 34285.18 | 109.39 | 1.996 | 2.495 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00755 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 17835.08 | 22293.85 | 110.38 | 1.298 | 1.622 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00754 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 27025.07 | 33781.34 | 107.78 | 1.966 | 2.458 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00754 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 17831.41 | 22289.27 | 110.36 | 1.298 | 1.622 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00754 | -10.70 | 0.00150 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.53 | 0.00212 | -10.70 | 0.00150 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.54 | 0.00212 | -10.70 | 0.00150 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 19.89 | 0.00212 | -10.70 | 0.00150 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:20:00 | 18.00 | 27.00 | 0.00850 | -10.70 | 0.00150 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 12.31 | 12.31 | 5.28 | 5.28 | 12.3057 | 5.2789 | 12.3057 | 0.4290 | 0.3000 |
VAV_MID WITH REHEAT | 116.27 | 116.27 | 91.23 | 91.23 | 116.2655 | 91.2258 | 116.2655 | 0.7846 | 0.3000 |
VAV_TOP WITH REHEAT | 14.20 | 14.20 | 15.40 | 15.40 | 14.2049 | 15.4011 | 15.4011 | 1.0000 | 0.3000 |
CAV_BAS | 7.01 | 7.01 | 1.20 | 1.20 | 7.0097 | 2.1029 | 7.0097 | 0.3000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 31.40 | 31.40 | 0.34 | 0.34 | 31.3964 | 15.6980 | 31.3964 | 0.5000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.73 | 0.73 | 0.02 | 0.02 | 0.7343 | 0.7343 | 0.7343 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 7.04 | 7.04 | 0.16 | 0.16 | 7.0446 | 7.0446 | 7.0446 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.73 | 0.73 | 0.02 | 0.02 | 0.7277 | 0.7277 | 0.7277 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 28188.779 | 28188.779 | 2.223574 | 0.00024661 | 584.240 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28188.78 | 28188.78 | 2.223574 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00799728 | 51.6755 | 6053.41 | 0.00 | 28327.83 | 28327.83 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 663484.296 | 663484.296 | 27.724386 | 0.00580445 | 15537.576 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 663484.30 | 663484.30 | 27.724386 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 387490.44 | 0.00 | 666523.07 | 666523.07 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 171181.618 | 171181.618 | 7.204206 | 0.00149757 | 4000.770 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 171181.62 | 171181.62 | 7.204206 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 99464.37 | 0.00 | 171966.26 | 171966.26 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 30234.876 | 30234.876 | 1.274517 | 0.00026451 | 706.314 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30234.88 | 30234.88 | 1.274517 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00769119 | 49.7256 | 17556.24 | 0.00 | 30373.49 | 30373.49 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 20172.434 | 20172.434 | 0.850438 | 0.00017648 | 471.232 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20172.43 | 20172.43 | 0.850438 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00769237 | 49.7331 | 11712.45 | 0.00 | 20264.92 | 20264.92 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 32246.684 | 32246.684 | 1.359531 | 0.00028211 | 753.279 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 32246.68 | 32246.68 | 1.359531 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00771067 | 49.8498 | 18721.80 | 0.00 | 32394.52 | 32394.52 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 17005.979 | 17005.979 | 0.716559 | 0.00014878 | 397.322 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17005.98 | 17005.98 | 0.716559 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00762594 | 49.3093 | 9878.79 | 0.00 | 17083.94 | 17083.94 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 459261.506 | 459261.506 | 19.381911 | 0.00401782 | 10725.340 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 459261.51 | 457253.91 | 19.381911 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00753800 | 48.7509 | 266539.17 | 0.00 | 461367.27 | 461367.27 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 299273.475 | 299273.475 | 12.630397 | 0.00261817 | 6989.013 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 299273.48 | 299273.48 | 12.630397 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00752795 | 48.6869 | 173687.53 | 0.00 | 300645.68 | 300645.68 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 450730.078 | 450730.078 | 19.021258 | 0.00394318 | 10526.195 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 450730.08 | 448745.46 | 19.021258 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00752992 | 48.6993 | 261596.70 | 0.00 | 452796.72 | 452796.72 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 295424.807 | 295424.807 | 12.467812 | 0.00258451 | 6899.158 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 295424.81 | 295424.81 | 12.467812 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00752277 | 48.6539 | 171456.88 | 0.00 | 296779.37 | 296779.37 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 59090.557 | 59090.557 | 2.494743 | 0.00051695 | 1379.817 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 59090.56 | 58855.45 | 2.494743 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00755084 | 48.8344 | 34285.18 | 0.00 | 59361.51 | 59361.51 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 38423.249 | 38423.249 | 1.622224 | 0.00033614 | 897.212 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38423.25 | 38423.25 | 1.622224 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00754013 | 48.7662 | 22293.85 | 0.00 | 38599.43 | 38599.43 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 58220.945 | 58220.945 | 2.457985 | 0.00050934 | 1359.518 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 58220.95 | 57988.26 | 2.457985 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00754458 | 48.7944 | 33781.34 | 0.00 | 58487.91 | 58487.91 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 38415.569 | 38415.569 | 1.621913 | 0.00033608 | 897.031 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38415.57 | 38415.57 | 1.621913 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00754060 | 48.7692 | 22289.27 | 0.00 | 38591.72 | 38591.72 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 261248.011 | -999.000 | 12.305687 | 0.00933117 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 261248.01 | 213817.58 | 12.305687 | 25.34 | 17.87 | 0.00972203 | 11.11 | 11.11 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 16.5005 | 24.00 | 0.00884591 | 47.5737 | 145048.57 | 0.00 | 261648.61 | 206740.75 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 46172.678 | 46172.678 | 3.691706 | 0.00040394 | 788.073 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 46172.68 | 46172.68 | 3.691706 | 2.55 | 1.92 | 0.00408951 | 12.89 | 11.63 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 55.0017 | 19.22 | 0.00732590 | 52.9218 | 16025.05 | 0.00 | 46168.32 | 46168.32 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2538007.537 | -999.000 | 116.265470 | 0.09065175 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2538007.54 | 2034434.23 | 116.265470 | 25.45 | 18.03 | 0.00987423 | 11.11 | 11.11 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 17.4652 | 24.00 | 0.00894521 | 48.1013 | 1342160.03 | 0.00 | 2541916.96 | 1971340.73 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 480548.447 | 480548.447 | 34.879641 | 0.00420405 | 8147.093 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 480548.45 | 480548.45 | 34.879641 | 1.50 | 1.01 | 0.00386890 | 12.89 | 11.63 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 58.2173 | 18.31 | 0.00747664 | 57.1523 | 151846.45 | 0.00 | 474215.93 | 474215.93 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 318847.476 | -999.000 | 15.401072 | 0.01138849 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 318847.48 | 264013.73 | 15.401072 | 25.16 | 17.73 | 0.00962866 | 11.12 | 11.12 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 13.1841 | 24.00 | 0.00887964 | 47.7538 | 168568.98 | 0.00 | 319335.90 | 254929.14 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 39421.700 | 39421.700 | 4.620322 | 0.00034488 | 687.873 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39421.70 | 39421.70 | 4.620322 | 5.83 | 4.59 | 0.00474822 | 12.89 | 11.63 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 43.9472 | 17.65 | 0.00769256 | 61.2540 | 16996.30 | 0.00 | 41124.23 | 41124.23 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 139468.042 | -999.000 | 7.009698 | 0.00498148 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 139468.04 | 111432.68 | 7.009698 | 24.50 | 17.65 | 0.00980170 | 11.10 | 11.10 | 0.00850000 | 26.62 | 0.01410980 | 21.57 | 17.1214 | 24.00 | 0.00891172 | 47.9223 | 83933.55 | 0.00 | 143513.08 | 110926.69 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.039805 | 0.00087484 | 2622.727 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.039805 | -1.83 | -4.73 | 0.00150390 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 39.4814 | 22.82 | 0.00150390 | 8.7845 | 0.00 | 0.00 | 100081.81 | 100081.81 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 455998.937 | -999.000 | 31.396387 | 0.01628723 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 455998.94 | 449225.82 | 31.396387 | 27.05 | 17.52 | 0.00859326 | 15.04 | 13.01 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 1.0778 | 27.00 | 0.00853299 | 38.4217 | 372229.23 | 0.00 | 472824.23 | 472824.23 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 100000.000 | 100000.000 | 3.039805 | 0.00087484 | 2622.727 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.039805 | -0.12 | -0.12 | 0.00842460 | 29.11 | 17.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 11.1321 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | 100081.81 | 100081.81 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER BOT | 12155.870 | 9732.719 | 0.734340 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 6077.94 | 5903.13 | 0.489560 | 27.05 | 17.60 | 0.00868318 | 14.49 | 12.78 | 0.00850000 | 29.58 | 0.01411511 | 22.43 | 3.1931 | 27.00 | 0.00856504 | 38.5621 | 8714.89 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER BOT | 26055.990 | 26055.990 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 26055.99 | 26055.99 | 0.734336 | -0.23 | -2.74 | 0.00210565 | 29.11 | 17.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 2.1288 | 25.32 | 0.00211873 | 10.6415 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER MID | 116612.900 | 93367.285 | 7.044590 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 58306.45 | 56561.58 | 4.696393 | 27.06 | 17.60 | 0.00869086 | 14.49 | 12.78 | 0.00850000 | 29.58 | 0.01411511 | 22.43 | 3.3286 | 27.00 | 0.00856776 | 38.5743 | 83602.68 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER MID | 250040.837 | 250040.837 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 250040.84 | 250040.84 | 7.044585 | -0.24 | -2.75 | 0.00210510 | 29.11 | 17.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 2.2191 | 23.70 | 0.00211875 | 11.7240 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER TOP | 12045.630 | 9644.454 | 0.727680 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 6022.81 | 5848.15 | 0.485120 | 27.06 | 17.60 | 0.00868481 | 14.49 | 12.78 | 0.00850000 | 29.77 | 0.01411544 | 22.48 | 3.2224 | 27.00 | 0.00856558 | 38.5646 | 8635.84 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER TOP | 25821.518 | 25821.518 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 25821.52 | 25821.52 | 0.727677 | -0.23 | -2.74 | 0.00210486 | 29.11 | 17.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 2.1483 | 22.07 | 0.00211806 | 12.9384 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 28188.779 | 28188.779 | 2.223574 | 0.00024661 | 584.240 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.98218607 | 54.44 | 82.22 | 27.78 | 3496477.43 | 0.8062 | 0.822430 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 28188.78 | 28188.78 | 1.0000 | 2.67628215 | 2.223574 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.24658258 | 60.00 | 32.22 | 27.78 | 0.000 | 28188.78 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.88 | 0.00799728 | 21.00 | 0.00799728 | 51.6755 | 6053.41 | 0.00 | 28327.83 | 28327.83 | 2.67628215 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 23.18 | 15.66 | 0.00800000 | 43644.6 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 663484.296 | 663484.296 | 27.724386 | 0.00580445 | 15537.576 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.98218607 | 54.44 | 82.22 | 27.78 | 3496477.43 | 18.9758 | 19.357688 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 663484.30 | 663484.30 | 1.0000 | 33.36893189 | 27.724386 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 5.80385795 | 60.00 | 32.22 | 27.78 | 0.000 | 663484.30 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 387490.44 | 0.00 | 666523.07 | 666523.07 | 33.36893189 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.39 | 18.82 | 0.00800000 | 53034.2 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 171181.618 | 171181.618 | 7.204206 | 0.00149757 | 4000.770 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.98218607 | 54.44 | 82.22 | 27.78 | 3496477.43 | 4.8958 | 4.994361 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 171181.62 | 171181.62 | 1.0000 | 8.67094639 | 7.204206 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 1.49741870 | 60.00 | 32.22 | 27.78 | 0.000 | 171181.62 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 99464.37 | 0.00 | 171966.26 | 171966.26 | 8.67094639 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.25 | 18.78 | 0.00800000 | 52892.3 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30234.876 | 30234.876 | 1.274517 | 0.00026451 | 706.314 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.98218607 | 54.44 | 82.22 | 27.78 | 3496477.43 | 0.8647 | 0.882127 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30234.88 | 30234.88 | 1.0000 | 1.53400182 | 1.274517 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.26448090 | 60.00 | 32.22 | 27.78 | 0.000 | 30234.88 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00769119 | 21.00 | 0.00769119 | 49.7256 | 17556.24 | 0.00 | 30373.49 | 30373.49 | 1.53400182 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52860.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20172.434 | 20172.434 | 0.850438 | 0.00017648 | 471.232 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.98218607 | 54.44 | 82.22 | 27.78 | 3496477.43 | 0.5769 | 0.588547 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20172.43 | 20172.43 | 1.0000 | 1.02358308 | 0.850438 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.17645925 | 60.00 | 32.22 | 27.78 | 0.000 | 20172.43 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00769237 | 21.00 | 0.00769237 | 49.7331 | 11712.45 | 0.00 | 20264.92 | 20264.92 | 1.02358308 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52857.8 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 32246.684 | 32246.684 | 1.359531 | 0.00028211 | 753.279 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.98218607 | 54.44 | 82.22 | 27.78 | 3496477.43 | 0.9223 | 0.940823 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 32246.68 | 32246.68 | 1.0000 | 1.63632444 | 1.359531 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.28207928 | 60.00 | 32.22 | 27.78 | 0.000 | 32246.68 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00771067 | 21.00 | 0.00771067 | 49.8498 | 18721.80 | 0.00 | 32394.52 | 32394.52 | 1.63632444 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52857.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17005.979 | 17005.979 | 0.716559 | 0.00014878 | 397.322 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.98218607 | 54.44 | 82.22 | 27.78 | 3496477.43 | 0.4864 | 0.496163 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17005.98 | 17005.98 | 1.0000 | 0.86244732 | 0.716559 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.14876055 | 60.00 | 32.22 | 27.78 | 0.000 | 17005.98 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00762594 | 21.00 | 0.00762594 | 49.3093 | 9878.79 | 0.00 | 17083.94 | 17083.94 | 0.86244732 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52868.5 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 459261.506 | 459261.506 | 19.381911 | 0.00401782 | 10725.340 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.98218607 | 54.44 | 82.22 | 27.78 | 3496477.43 | 13.1350 | 13.399324 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 459261.51 | 457253.91 | 1.0000 | 23.32797136 | 19.381911 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 4.01741014 | 60.00 | 32.22 | 27.78 | 0.000 | 459261.51 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00753800 | 21.00 | 0.00753800 | 48.7509 | 266539.17 | 0.00 | 461367.27 | 461367.27 | 23.32797136 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52837.3 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 299273.475 | 299273.475 | 12.630397 | 0.00261817 | 6989.013 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.98218607 | 54.44 | 82.22 | 27.78 | 3496477.43 | 8.5593 | 8.731544 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 299273.48 | 299273.48 | 1.0000 | 15.20188292 | 12.630397 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 2.61790784 | 60.00 | 32.22 | 27.78 | 0.000 | 299273.48 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00752795 | 21.00 | 0.00752795 | 48.6869 | 173687.53 | 0.00 | 300645.68 | 300645.68 | 15.20188292 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52836.7 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 450730.078 | 450730.078 | 19.021258 | 0.00394318 | 10526.195 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.98218607 | 54.44 | 82.22 | 27.78 | 3496477.43 | 12.8910 | 13.150412 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 450730.08 | 448745.46 | 1.0000 | 22.89389116 | 19.021258 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 3.94278110 | 60.00 | 32.22 | 27.78 | 0.000 | 450730.08 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00752992 | 21.00 | 0.00752992 | 48.6993 | 261596.70 | 0.00 | 452796.72 | 452796.72 | 22.89389116 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52837.9 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 295424.807 | 295424.807 | 12.467812 | 0.00258451 | 6899.158 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.98218607 | 54.44 | 82.22 | 27.78 | 3496477.43 | 8.4492 | 8.619256 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 295424.81 | 295424.81 | 1.0000 | 15.00619640 | 12.467812 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 2.58424145 | 60.00 | 32.22 | 27.78 | 0.000 | 295424.81 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00752277 | 21.00 | 0.00752277 | 48.6539 | 171456.88 | 0.00 | 296779.37 | 296779.37 | 15.00619640 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52836.9 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 59090.557 | 59090.557 | 2.494743 | 0.00051695 | 1379.817 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.98218607 | 54.44 | 82.22 | 27.78 | 3496477.43 | 1.6900 | 1.724014 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 59090.56 | 58855.45 | 1.0000 | 3.00266047 | 2.494743 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.51689723 | 60.00 | 32.22 | 27.78 | 0.000 | 59090.56 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00755084 | 21.00 | 0.00755084 | 48.8344 | 34285.18 | 0.00 | 59361.51 | 59361.51 | 3.00266047 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52829.5 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 38423.249 | 38423.249 | 1.622224 | 0.00033614 | 897.212 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.98218607 | 54.44 | 82.22 | 27.78 | 3496477.43 | 1.0989 | 1.121029 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 38423.25 | 38423.25 | 1.0000 | 1.95250080 | 1.622224 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.33610905 | 60.00 | 32.22 | 27.78 | 0.000 | 38423.25 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00754013 | 21.00 | 0.00754013 | 48.7662 | 22293.85 | 0.00 | 38599.43 | 38599.43 | 1.95250080 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52829.1 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 58220.945 | 58220.945 | 2.457985 | 0.00050934 | 1359.518 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.98218607 | 54.44 | 82.22 | 27.78 | 3496477.43 | 1.6651 | 1.698643 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 58220.95 | 57988.26 | 1.0000 | 2.95841868 | 2.457985 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.50929027 | 60.00 | 32.22 | 27.78 | 0.000 | 58220.95 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00754458 | 21.00 | 0.00754458 | 48.7944 | 33781.34 | 0.00 | 58487.91 | 58487.91 | 2.95841868 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52829.8 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 38415.569 | 38415.569 | 1.621913 | 0.00033608 | 897.031 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.98218607 | 54.44 | 82.22 | 27.78 | 3496477.43 | 1.0987 | 1.120805 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 38415.57 | 38415.57 | 1.0000 | 1.95212677 | 1.621913 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.33604187 | 60.00 | 32.22 | 27.78 | 0.000 | 38415.57 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00754060 | 21.00 | 0.00754060 | 48.7692 | 22289.27 | 0.00 | 38591.72 | 38591.72 | 1.95212677 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52828.9 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 261248.011 | -999.000 | 12.305687 | 0.00933117 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.9128 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 12.305687 | 14.81106276 | 4197.9300 | 999.8980 | 132.62658544 | 13.34 | 6.67 | 6.67 | 3713570.00 | 7.0350 | 7.034956 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 261248.01 | 213817.58 | 1.0000 | 14.81106276 | 12.305687 | 25.34 | 17.87 | 0.00972203 | 50239.4 | 11.11 | 11.11 | 0.00850000 | 32600.7 | 9.33022175 | 6.67 | 13.34 | 6.67 | 26901.501 | 234346.51 | 32.10 | 0.01411964 | 23.13 | 2.03050000 | 16.5005 | 24.00 | 0.00884591 | 24.00 | 0.00884591 | 47.5737 | 145048.57 | 0.00 | 261648.61 | 206740.75 | 14.81106276 | 25.34 | 17.88 | 0.00972203 | 50239.4 | 11.70 | 11.39 | 0.00825248 | 32573.6 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 46172.678 | 46172.678 | 3.691706 | 0.00040394 | 788.073 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 12.305687 | 14.81106276 | 4197.9300 | 999.8980 | 29.98218607 | 54.44 | 82.22 | 27.78 | 3496477.43 | 1.3205 | 1.347125 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 46172.68 | 46172.68 | 1.0000 | 4.44331883 | 3.691706 | 2.55 | 1.92 | 0.00408951 | 12807.0 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 0.40389752 | 60.00 | 32.22 | 27.78 | 0.000 | 46172.68 | -10.70 | 0.00150390 | -10.70 | 2.03050000 | 55.0017 | 18.74 | 0.00724992 | 19.22 | 0.00732590 | 52.9218 | 16025.05 | 0.00 | 46168.32 | 46168.32 | 4.44331883 | 2.80 | 2.07 | 0.00408951 | 13062.5 | 13.06 | 7.42 | 0.00408951 | 23453.0 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2538007.537 | -999.000 | 116.265470 | 0.09065175 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.1957 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 116.265470 | 139.93653658 | 4197.9300 | 999.8980 | 132.62658544 | 13.34 | 6.67 | 6.67 | 3713570.00 | 68.3441 | 68.344141 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2538007.54 | 2034434.23 | 1.0000 | 139.93653658 | 116.265470 | 25.45 | 18.03 | 0.00987423 | 50738.0 | 11.11 | 11.11 | 0.00850000 | 32601.2 | 90.64250121 | 6.67 | 13.34 | 6.67 | 254168.312 | 2283839.22 | 32.10 | 0.01411964 | 23.13 | 20.30600000 | 17.4652 | 24.00 | 0.00894521 | 24.00 | 0.00894521 | 48.1013 | 1342160.03 | 0.00 | 2541916.96 | 1971340.73 | 139.93653658 | 25.45 | 18.04 | 0.00987423 | 50738.0 | 11.68 | 11.39 | 0.00825792 | 32573.2 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 480548.447 | 480548.447 | 34.879641 | 0.00420405 | 8147.093 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 116.265470 | 139.93653658 | 4197.9300 | 999.8980 | 29.98218607 | 54.44 | 82.22 | 27.78 | 3496477.43 | 13.7438 | 14.020387 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 480548.45 | 480548.45 | 1.0000 | 41.98096097 | 34.879641 | 1.50 | 1.01 | 0.00386890 | 11191.3 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 4.20361859 | 60.00 | 32.22 | 27.78 | 0.000 | 480548.45 | -10.70 | 0.00150390 | -10.70 | 20.30600000 | 58.2173 | 18.49 | 0.00716415 | 18.31 | 0.00747664 | 57.1523 | 151846.45 | 0.00 | 474215.93 | 474215.93 | 41.98096097 | 2.80 | 1.76 | 0.00386890 | 12509.6 | 13.96 | 7.59 | 0.00386890 | 23805.6 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 318847.476 | -999.000 | 15.401072 | 0.01138849 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.7392 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 15.401072 | 18.53665311 | 4197.9300 | 999.8980 | 132.62658544 | 13.34 | 6.67 | 6.67 | 3713570.00 | 8.5860 | 8.586010 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 318847.48 | 264013.73 | 1.0000 | 18.53665311 | 15.401072 | 25.16 | 17.73 | 0.00962866 | 49808.9 | 11.12 | 11.12 | 0.00850000 | 32608.0 | 11.38733133 | 6.67 | 13.34 | 6.67 | 33525.821 | 285321.66 | 32.10 | 0.01411964 | 23.13 | 2.03050000 | 13.1841 | 24.00 | 0.00887964 | 24.00 | 0.00887964 | 47.7538 | 168568.98 | 0.00 | 319335.90 | 254929.14 | 18.53665311 | 25.16 | 17.74 | 0.00962866 | 49808.9 | 11.71 | 11.39 | 0.00825134 | 32581.7 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 39421.700 | 39421.700 | 4.620322 | 0.00034488 | 687.873 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 15.401072 | 18.53665311 | 4197.9300 | 999.8980 | 29.98218607 | 54.44 | 82.22 | 27.78 | 3496477.43 | 1.1275 | 1.150160 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39421.70 | 39421.70 | 1.0000 | 5.56099593 | 4.620322 | 5.83 | 4.59 | 0.00474822 | 17788.9 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 0.34484304 | 60.00 | 32.22 | 27.78 | 0.000 | 39421.70 | -10.70 | 0.00150390 | -10.70 | 2.03050000 | 43.9472 | 18.80 | 0.00729186 | 17.65 | 0.00769256 | 61.2540 | 16996.30 | 0.00 | 41124.23 | 41124.23 | 5.56099593 | 2.80 | 2.80 | 0.00474822 | 14713.3 | 10.10 | 6.76 | 0.00474822 | 22108.4 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 139468.042 | -999.000 | 7.009698 | 0.00498148 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.0609 | 1004.8586 | 1.2036 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 7.009698 | 8.43683752 | 4197.9300 | 999.8980 | 132.62658544 | 13.34 | 6.67 | 6.67 | 3713570.00 | 3.7556 | 3.755632 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 139468.04 | 111432.68 | 1.0000 | 8.43683752 | 7.009698 | 24.50 | 17.65 | 0.00980170 | 49578.5 | 11.10 | 11.10 | 0.00850000 | 32591.2 | 4.98096714 | 6.67 | 13.34 | 6.67 | 15405.782 | 124062.26 | 26.62 | 0.01410980 | 21.57 | 1.20015641 | 17.1214 | 24.06 | 0.00891172 | 24.00 | 0.00891172 | 47.9223 | 83933.55 | 0.00 | 143513.08 | 110926.69 | 8.43683752 | 24.50 | 17.66 | 0.00980170 | 49578.5 | 11.65 | 11.39 | 0.00827058 | 32568.2 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.039805 | 0.00087484 | 2622.727 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 7.009698 | 8.43683752 | 4197.9300 | 999.8980 | 29.98218607 | 54.44 | 82.22 | 27.78 | 3496477.43 | 2.8600 | 2.917580 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.039805 | -1.83 | -4.73 | 0.00150390 | 1915.2 | 32.11 | 18.73 | 0.00800000 | 52750.5 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -10.70 | 0.00150390 | -10.70 | 1.20015641 | 39.4814 | 0.00 | 0.00150390 | 22.82 | 0.00150390 | 8.7845 | 0.00 | 0.00 | 100081.81 | 100081.81 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40241.7 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 455998.937 | -999.000 | 31.396387 | 0.01628723 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8144 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 31.396387 | 37.78853335 | 4197.9300 | 999.8980 | 132.62658544 | 13.34 | 6.67 | 6.67 | 3713570.00 | 12.2793 | 12.279261 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 455998.94 | 449225.82 | 1.0000 | 37.78853335 | 31.396387 | 27.05 | 17.52 | 0.00859326 | 49107.3 | 15.04 | 13.01 | 0.00850000 | 36612.5 | 16.28556401 | 6.67 | 13.34 | 6.67 | 32594.433 | 423404.50 | 32.10 | 0.01411964 | 23.13 | 0.33839277 | 1.0778 | 27.00 | 0.00853299 | 27.00 | 0.00853299 | 38.4217 | 372229.23 | 0.00 | 472824.23 | 472824.23 | 37.78853335 | 27.05 | 17.53 | 0.00859326 | 49107.3 | 14.80 | 13.00 | 0.00859326 | 36595.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.039805 | 0.00087484 | 2622.727 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 31.396387 | 37.78853335 | 4197.9300 | 999.8980 | 29.98218607 | 54.44 | 82.22 | 27.78 | 3496477.43 | 2.8600 | 2.917580 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.039805 | -0.12 | -0.12 | 0.00842460 | 20951.7 | 29.11 | 17.73 | 0.00800000 | 49691.3 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -10.70 | 0.00150390 | -10.70 | 0.33839277 | 11.1321 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | 100081.81 | 100081.81 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40241.7 | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12155.870 | 9732.719 | 0.734340 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9816 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.734336 | 0.88384357 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 6077.94 | 5903.13 | 1.0000 | 0.58923196 | 0.489560 | 27.05 | 17.60 | 0.00868318 | 49337.6 | 14.49 | 12.78 | 0.00850000 | 36046.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6077.94 | 29.58 | 0.01411511 | 22.43 | 0.01563234 | 3.1931 | 27.00 | 0.00856504 | 27.00 | 0.00856504 | 38.5621 | 8714.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26055.990 | 26055.990 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.734336 | 0.88384357 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 26055.99 | 26055.99 | 1.0000 | 0.88384357 | 0.734336 | -0.23 | -2.74 | 0.00210565 | 5036.3 | 29.11 | 17.73 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26055.99 | -10.70 | 0.00150390 | -10.70 | 0.01563234 | 2.1288 | 0.00 | 0.00211873 | 25.32 | 0.00211873 | 10.6415 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 116612.900 | 93367.285 | 7.044590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9959 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.044585 | 8.47882716 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 58306.45 | 56561.58 | 1.0000 | 5.65255545 | 4.696393 | 27.06 | 17.60 | 0.00869086 | 49359.5 | 14.49 | 12.78 | 0.00850000 | 36046.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58306.45 | 29.58 | 0.01411511 | 22.43 | 0.15632344 | 3.3286 | 27.00 | 0.00856776 | 27.00 | 0.00856776 | 38.5743 | 83602.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 250040.837 | 250040.837 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.044585 | 8.47882716 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 250040.84 | 250040.84 | 1.0000 | 8.47882716 | 7.044585 | -0.24 | -2.75 | 0.00210510 | 5025.2 | 29.11 | 17.73 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 250040.84 | -10.70 | 0.00150390 | -10.70 | 0.15632344 | 2.2191 | 0.00 | 0.00211875 | 23.70 | 0.00211875 | 11.7240 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12045.630 | 9644.454 | 0.727680 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9846 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.727677 | 0.87582780 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | Sensible | 6022.81 | 5848.15 | 1.0000 | 0.58388800 | 0.485120 | 27.06 | 17.60 | 0.00868481 | 49346.3 | 14.49 | 12.78 | 0.00850000 | 36046.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6022.81 | 29.77 | 0.01411544 | 22.48 | 0.01563234 | 3.2224 | 27.00 | 0.00856558 | 27.00 | 0.00856558 | 38.5646 | 8635.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25821.518 | 25821.518 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.727677 | 0.87582780 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 25821.52 | 25821.52 | 1.0000 | 0.87582780 | 0.727677 | -0.23 | -2.74 | 0.00210486 | 5032.3 | 29.11 | 17.73 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25821.52 | -10.70 | 0.00150390 | -10.70 | 0.01563234 | 2.1483 | 0.00 | 0.00211806 | 22.07 | 0.00211806 | 12.9384 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialEnthalpy | 0.34 | 31.40 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 3093.67 | 1421.17 | 60.33 |
CORE_BOTTOM | 2944.33 | 1313.67 | 2.83 |
CORE_MID | 2470.33 | 2662.17 | 137.33 |
CORE_TOP | 2864.00 | 3491.00 | 905.83 |
PERIMETER_BOT_ZN_3 | 2885.67 | 3253.33 | 660.83 |
PERIMETER_BOT_ZN_2 | 2584.33 | 3588.00 | 677.67 |
PERIMETER_BOT_ZN_1 | 3045.50 | 2949.50 | 661.50 |
PERIMETER_BOT_ZN_4 | 2838.83 | 3188.17 | 521.50 |
PERIMETER_MID_ZN_3 | 3152.83 | 4177.33 | 1748.50 |
PERIMETER_MID_ZN_2 | 2666.83 | 3477.67 | 1388.50 |
PERIMETER_MID_ZN_1 | 3248.50 | 3328.50 | 1151.17 |
PERIMETER_MID_ZN_4 | 3014.50 | 4048.67 | 1475.17 |
PERIMETER_TOP_ZN_3 | 3390.00 | 4507.00 | 2246.83 |
PERIMETER_TOP_ZN_2 | 3569.67 | 4127.67 | 2011.00 |
PERIMETER_TOP_ZN_1 | 3404.17 | 3794.17 | 1659.50 |
PERIMETER_TOP_ZN_4 | 3362.50 | 4272.67 | 1961.00 |
DATACENTER_BOT_ZN_6 | 5817.83 | 1410.50 | 1409.83 |
DATACENTER_MID_ZN_6 | 5392.17 | 721.00 | 650.83 |
DATACENTER_TOP_ZN_6 | 4819.50 | 1146.17 | 858.00 |
DATACENTER_BASEMENT_ZN_6 | 5917.67 | 3903.67 | 3902.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5937.83 | 5327.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 17.33 | 0.00 | 0.50 |
CORE_BOTTOM | 0.00 | 0.33 | 0.00 | 0.00 |
CORE_MID | 1.17 | 0.00 | 0.50 | 0.00 |
CORE_TOP | 11.83 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 4.67 | 0.17 | 0.33 | 0.17 |
PERIMETER_BOT_ZN_2 | 4.50 | 15.83 | 0.00 | 15.83 |
PERIMETER_BOT_ZN_1 | 6.50 | 22.83 | 0.00 | 22.83 |
PERIMETER_BOT_ZN_4 | 2.17 | 41.83 | 0.00 | 22.50 |
PERIMETER_MID_ZN_3 | 61.67 | 0.00 | 11.33 | 0.00 |
PERIMETER_MID_ZN_2 | 75.17 | 17.00 | 6.17 | 17.00 |
PERIMETER_MID_ZN_1 | 45.67 | 21.50 | 3.50 | 21.33 |
PERIMETER_MID_ZN_4 | 46.17 | 18.50 | 6.17 | 13.00 |
PERIMETER_TOP_ZN_3 | 167.67 | 0.00 | 33.33 | 0.00 |
PERIMETER_TOP_ZN_2 | 163.17 | 18.67 | 28.67 | 18.67 |
PERIMETER_TOP_ZN_1 | 126.00 | 17.00 | 18.00 | 16.83 |
PERIMETER_TOP_ZN_4 | 112.50 | 20.00 | 19.00 | 13.83 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 16.67 | 0.00 | 16.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 226.67 | 163.50 | 40.50 | 120.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.532 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.419 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.396 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.381 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.518 | 0.055 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.898 | 0.057 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.797 | 0.055 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 1.130 | 0.057 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.750 | 0.128 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 1.030 | 0.141 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.902 | 0.129 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 1.143 | 0.133 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.861 | 0.159 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 1.003 | 0.164 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.960 | 0.159 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 1.125 | 0.164 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.583 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.583 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.583 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 18.613 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.563 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.559 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.557 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.631 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 60.99 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.86 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.79 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.20 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1010.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 21317791.53 | 0.00 | 21317791.53 | 0.00 | 21317791.53 | 37848132.68 | 4193.40 | 4368.96 | 197.63 | 219.61 |
CORE_BOTTOM | 17977148.80 | 0.00 | 17977148.80 | 0.00 | 17977148.80 | 33990283.35 | 8218.81 | 116.74 | 424.45 | 372.92 |
CORE_MID | 0.17E+09 | 0.00 | 0.17E+09 | 0.00 | 0.17E+09 | 0.34E+09 | 8677.41 | 11.65 | 70.94 | 335.85 |
CORE_TOP | 17038361.04 | 0.00 | 17038361.04 | 0.00 | 17038361.04 | 33990283.35 | 8755.50 | 0.17 | 4.33 | 574.14 |
PERIMETER_BOT_ZN_3 | 2818743.57 | 0.00 | 2818743.57 | 542909.24 | 3361652.80 | 4267819.30 | 5085.30 | 104.53 | 3570.17 | 372.92 |
PERIMETER_BOT_ZN_2 | 3180009.08 | 0.00 | 3180009.08 | 361939.24 | 3541948.32 | 2750345.05 | 3462.38 | 13.97 | 5283.64 | 372.92 |
PERIMETER_BOT_ZN_1 | 4321664.38 | 0.00 | 4321664.38 | 542909.24 | 4864573.62 | 4267912.63 | 3563.37 | 30.08 | 5166.54 | 372.92 |
PERIMETER_BOT_ZN_4 | 3986937.06 | 0.00 | 3986937.06 | 361939.24 | 4348876.30 | 2750345.05 | 3453.04 | 0.00 | 5306.96 | 372.92 |
PERIMETER_MID_ZN_3 | 40855367.10 | 0.00 | 40855367.10 | 1273269.14 | 42128636.24 | 42678193.03 | 3687.48 | 36.27 | 5036.25 | 335.85 |
PERIMETER_MID_ZN_2 | 33401767.83 | 0.00 | 33401767.83 | 848845.52 | 34250613.34 | 27503450.52 | 4051.19 | 3.26 | 4705.54 | 863.38 |
PERIMETER_MID_ZN_1 | 48352599.79 | 0.00 | 48352599.79 | 1273269.14 | 49625868.94 | 42679126.28 | 3549.97 | 9.99 | 5200.04 | 335.85 |
PERIMETER_MID_ZN_4 | 39921934.32 | 0.00 | 39921934.32 | 848845.52 | 40770779.83 | 27503450.52 | 3513.17 | 0.00 | 5246.83 | 335.85 |
PERIMETER_TOP_ZN_3 | 4920119.76 | 0.00 | 4920119.76 | 1580892.99 | 6501012.75 | 4267819.30 | 3245.73 | 17.76 | 5496.51 | 574.14 |
PERIMETER_TOP_ZN_2 | 3660275.54 | 0.00 | 3660275.54 | 1053927.94 | 4714203.48 | 2750345.05 | 3220.30 | 0.31 | 5539.39 | 574.14 |
PERIMETER_TOP_ZN_1 | 5397480.34 | 0.00 | 5397480.34 | 1580892.99 | 6978373.34 | 4267912.63 | 3221.14 | 0.18 | 5538.68 | 574.14 |
PERIMETER_TOP_ZN_4 | 4106740.95 | 0.00 | 4106740.95 | 1053927.94 | 5160668.89 | 2750345.05 | 3216.30 | 0.03 | 5543.67 | 574.14 |
DATACENTER_BOT_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929815.99 | 0.00 | 4929815.99 | 0.00 | 4929815.99 | 4929815.99 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 0.30E+09 | 0.00 | 0.30E+09 | 0.00 | 0.30E+09 | 10671554.30 | 0.00 | 2076.55 | 6683.45 | 2817.00 |
Total Facility | 0.38E+10 | 0.00 | 0.38E+10 | 49521632.03 | 0.38E+10 | 0.50E+10 | 8760.00 | 8760.00 | 8232.91 | 3344.53 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9836 | 0.0000 | 0.9836 | 0.0000 | 0.9836 | 1.2002 | 1390.13 | 4355.23 | 197.63 |
CORE_BOTTOM | 0.7828 | 0.0000 | 0.7828 | 0.0000 | 0.7828 | 1.0778 | 5410.37 | 116.56 | 416.07 |
CORE_MID | 7.4003 | 0.0000 | 7.4003 | 0.0000 | 7.4003 | 10.7782 | 5864.63 | 11.49 | 66.88 |
CORE_TOP | 0.7144 | 0.0000 | 0.7144 | 0.0000 | 0.7144 | 1.0778 | 5940.04 | 0.08 | 2.87 |
PERIMETER_BOT_ZN_3 | 0.1217 | 0.0000 | 0.1217 | 0.0129 | 0.1346 | 0.1353 | 2624.59 | 104.18 | 3214.23 |
PERIMETER_BOT_ZN_2 | 0.1365 | 0.0000 | 0.1365 | 0.0086 | 0.1451 | 0.0872 | 1016.95 | 13.80 | 4912.25 |
PERIMETER_BOT_ZN_1 | 0.1875 | 0.0000 | 0.1875 | 0.0129 | 0.2005 | 0.1353 | 1106.47 | 29.77 | 4806.76 |
PERIMETER_BOT_ZN_4 | 0.1714 | 0.0000 | 0.1714 | 0.0086 | 0.1800 | 0.0872 | 1008.97 | 0.00 | 4934.03 |
PERIMETER_MID_ZN_3 | 1.7709 | 0.0000 | 1.7709 | 0.0303 | 1.8013 | 1.3533 | 1199.24 | 36.16 | 4707.61 |
PERIMETER_MID_ZN_2 | 1.5673 | 0.0000 | 1.5673 | 0.0215 | 1.5888 | 0.8721 | 1032.48 | 0.20 | 4001.32 |
PERIMETER_MID_ZN_1 | 2.1245 | 0.0000 | 2.1245 | 0.0303 | 2.1548 | 1.3533 | 1061.87 | 9.89 | 4871.24 |
PERIMETER_MID_ZN_4 | 1.7374 | 0.0000 | 1.7374 | 0.0202 | 1.7576 | 0.8721 | 1032.02 | 0.00 | 4910.98 |
PERIMETER_TOP_ZN_3 | 0.2037 | 0.0000 | 0.2037 | 0.0377 | 0.2413 | 0.1353 | 1001.08 | 17.67 | 4924.25 |
PERIMETER_TOP_ZN_2 | 0.1527 | 0.0000 | 0.1527 | 0.0251 | 0.1778 | 0.0872 | 976.08 | 0.18 | 4966.74 |
PERIMETER_TOP_ZN_1 | 0.2265 | 0.0000 | 0.2265 | 0.0377 | 0.2641 | 0.1353 | 976.55 | 0.13 | 4966.32 |
PERIMETER_TOP_ZN_4 | 0.1713 | 0.0000 | 0.1713 | 0.0251 | 0.1964 | 0.0872 | 973.39 | 0.03 | 4969.58 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1563 | 0.00 | 5943.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 9.6455 | 0.0000 | 9.6455 | 0.0000 | 9.6455 | 0.3384 | 0.00 | 1435.20 | 4507.80 |
Total Facility | 161.0958 | 0.0000 | 161.0958 | 1.1927 | 162.2885 | 158.4706 | 5943.00 | 5943.00 | 5809.19 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 46768654.98 | 0.00 | 46768654.98 | 48026705.38 | 3462.99 | 0.47 | 5296.54 | 372.92 |
VAV_MID WITH REHEAT | 0.48E+09 | 0.00 | 0.48E+09 | 0.48E+09 | 3518.89 | 0.26 | 5240.86 | 335.85 |
VAV_TOP WITH REHEAT | 50880581.74 | 0.00 | 50880581.74 | 48026705.38 | 3219.65 | 0.06 | 5540.29 | 574.14 |
CAV_BAS | 29484939.13 | 0.00 | 29484939.13 | 37848132.68 | 4095.54 | 0.61 | 4663.85 | 219.61 |
AIRLOOP DATACENTER BASEMENT | 0.43E+09 | 0.00 | 0.43E+09 | 10671554.30 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER BOT | 714153.30 | 0.00 | 714153.30 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 7141532.97 | 0.00 | 7141532.97 | 4929815.99 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 714153.30 | 0.00 | 714153.30 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.0280 | 0.0000 | 2.0280 | 1.5229 | 1013.73 | 0.27 | 4929.00 |
VAV_MID WITH REHEAT | 20.9666 | 0.0000 | 20.9666 | 15.2292 | 1035.44 | 0.18 | 4907.38 |
VAV_TOP WITH REHEAT | 2.1273 | 0.0000 | 2.1273 | 1.5229 | 975.61 | 0.03 | 4967.36 |
CAV_BAS | 1.3595 | 0.0000 | 1.3595 | 1.2002 | 1298.24 | 0.00 | 4644.76 |
AIRLOOP DATACENTER BASEMENT | 13.9730 | 0.0000 | 13.9730 | 0.3384 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER BOT | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2265 | 0.0000 | 0.2265 | 0.1563 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 54.81 | 0.00 | 0.00 | 0.00 | 0.00 | 5252.15 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 149.83 | 0.00 | 0.00 | 0.00 | 0.00 | 5097.09 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 44.38 | 0.00 | 0.00 | 0.00 | 0.00 | 5499.43 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 4880.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 2076.25 | 6683.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.1778 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.4456 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 26.7921 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 25.3380 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.2310 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.5459 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7338 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4902 | 18.2689 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2265 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1343 |
Defaulted Fields | 1287 |
Fields with Defaults | 3878 |
Autosized Fields | 320 |
Autosizable Fields | 465 |
Autocalculated Fields | 223 |
Autocalculatable Fields | 468 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 32487.63 | 287024.29 | 07-MAY-05:00 | 2481535.09 | 02-AUG-15:10 |
Electricity:Building | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 758.19 | 15076.70 | 01-JAN-00:10 | 42602.33 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 589.38 | 5907.35 | 01-JAN-00:10 | 43380.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5893.79 | 59073.32 | 01-JAN-00:10 | 433806.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 589.38 | 5907.33 | 01-JAN-00:10 | 43380.63 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 740.04 | 7417.49 | 01-JAN-00:10 | 54469.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 476.91 | 4780.12 | 01-JAN-00:10 | 35102.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 740.05 | 7417.62 | 01-JAN-00:10 | 54470.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 476.91 | 4780.09 | 01-JAN-00:10 | 35102.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7588.97 | 95364.66 | 01-JAN-00:10 | 387850.11 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1622.27 | 19890.94 | 01-JAN-00:10 | 85232.07 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:HVAC | 4062.85 | 25854.08 | 15-JAN-10:40 | 417197.45 | 30-AUG-15:30 |
ExteriorEquipment:Electricity | 2623.11 | 22123.82 | 01-JAN-00:10 | 235096.12 | 03-APR-07:20 |
Transformer:ExteriorEquipment:Electricity | 56.04 | 979.82 | 01-JAN-00:10 | 3543.78 | 03-APR-07:20 |
ElectricityPurchased:Facility | 32487.63 | 287024.29 | 07-MAY-05:00 | 2481535.09 | 02-AUG-15:10 |
ElectricityPurchased:Plant | 32487.63 | 287024.29 | 07-MAY-05:00 | 2481535.09 | 02-AUG-15:10 |
Cogeneration:ElectricityPurchased | 32487.63 | 287024.29 | 07-MAY-05:00 | 2481535.09 | 02-AUG-15:10 |
General:Cogeneration:ElectricityPurchased | 32487.63 | 287024.29 | 07-MAY-05:00 | 2481535.09 | 02-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 32487.63 | 287024.29 | 07-MAY-05:00 | 2481535.09 | 02-AUG-15:10 |
ElectricityNet:Plant | 32487.63 | 287024.29 | 07-MAY-05:00 | 2481535.09 | 02-AUG-15:10 |
Cogeneration:ElectricityNet | 32487.63 | 287024.29 | 07-MAY-05:00 | 2481535.09 | 02-AUG-15:10 |
General:Cogeneration:ElectricityNet | 32487.63 | 287024.29 | 07-MAY-05:00 | 2481535.09 | 02-AUG-15:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 3021.75 | 0.00 | 01-JAN-00:20 | 508172.57 | 04-AUG-14:10 |
General:Cooling:Electricity | 3021.75 | 0.00 | 01-JAN-00:20 | 508172.57 | 04-AUG-14:10 |
Fans:Electricity | 2679.35 | 24405.79 | 01-JAN-06:40 | 296507.39 | 18-AUG-14:40 |
General:Fans:Electricity | 2679.35 | 24405.79 | 01-JAN-06:40 | 296507.39 | 18-AUG-14:40 |
ExteriorLights:Electricity | 1006.15 | 0.00 | 01-JAN-07:30 | 64082.80 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 1006.15 | 0.00 | 01-JAN-07:30 | 64082.80 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.31 | 1944.00 | 01-JAN-00:10 | 1944.00 | 01-JAN-00:10 |
Humidifier:Electricity | 891.67 | 0.00 | 03-JAN-09:20 | 100000.00 | 02-MAR-22:20 |
General:Humidifier:Electricity | 891.67 | 0.00 | 03-JAN-09:20 | 100000.00 | 02-MAR-22:20 |
Electricity:Plant | 4564.43 | 0.00 | 04-JAN-00:10 | 670442.32 | 16-AUG-12:30 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 426.48 | 0.00 | 01-JAN-00:10 | 53278.86 | 09-FEB-12:30 |
Water Heater:WaterSystems:Electricity | 426.48 | 0.00 | 01-JAN-00:10 | 53278.86 | 09-FEB-12:30 |
HeatRejection:Electricity | 325.04 | 0.00 | 01-JAN-00:10 | 57461.26 | 07-APR-13:30 |
General:HeatRejection:Electricity | 325.04 | 0.00 | 01-JAN-00:10 | 57461.26 | 07-APR-13:30 |
Pumps:Electricity | 1226.95 | 0.00 | 04-JAN-00:10 | 107178.47 | 04-OCT-13:20 |
General:Pumps:Electricity | 1226.95 | 0.00 | 04-JAN-00:10 | 107178.47 | 04-OCT-13:20 |
WIRED_LTG_ELECTRICITY | 157.66 | 0.00 | 01-JAN-00:10 | 13766.21 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 3190.06 | 0.00 | 01-JAN-00:40 | 3138528.82 | 02-JAN-06:20 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 3190.06 | 0.00 | 01-JAN-00:40 | 3138528.82 | 02-JAN-06:20 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 3190.06 | 0.00 | 01-JAN-00:40 | 3138528.82 | 02-JAN-06:20 |
Boiler:Heating:NaturalGas | 3190.06 | 0.00 | 01-JAN-00:40 | 3138528.82 | 02-JAN-06:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 14856.85 | 0.00 | 01-JAN-00:20 | 3004460.48 | 04-AUG-14:10 |
PlantLoopCoolingDemand:HVAC | 14856.85 | 0.00 | 01-JAN-00:20 | 3004460.48 | 04-AUG-14:10 |
CoolingCoils:PlantLoopCoolingDemand | 14856.85 | 0.00 | 01-JAN-00:20 | 3004460.48 | 04-AUG-14:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 12963.02 | 0.00 | 24-JAN-00:10 | 0.00 | 30-AUG-15:10 |
Water:HVAC | 331.70 | 0.00 | 03-JAN-09:20 | 0.00 | 15-MAR-16:50 |
Humidifier:Water | 331.70 | 0.00 | 03-JAN-09:20 | 0.00 | 15-MAR-16:50 |
General:Humidifier:Water | 331.70 | 0.00 | 03-JAN-09:20 | 0.00 | 15-MAR-16:50 |
MainsWater:Facility | 12963.02 | 0.00 | 24-JAN-00:10 | 0.00 | 30-AUG-15:10 |
MainsWater:HVAC | 331.70 | 0.00 | 03-JAN-09:20 | 0.00 | 15-MAR-16:50 |
Humidifier:MainsWater | 331.70 | 0.00 | 03-JAN-09:20 | 0.00 | 15-MAR-16:50 |
General:Humidifier:MainsWater | 331.70 | 0.00 | 03-JAN-09:20 | 0.00 | 15-MAR-16:50 |
Water:Plant | 12631.32 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 04-APR-11:50 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 04-APR-11:50 |
MainsWater:Plant | 12631.32 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 04-APR-11:50 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 04-APR-11:50 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 10351.15 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:00 |
General:HeatRejection:Water | 10351.15 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:00 |
HeatRejection:MainsWater | 10351.15 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:00 |
General:HeatRejection:MainsWater | 10351.15 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 91099.92 | 94448.82 | 09-JAN-05:10 | 14607672.81 | 04-AUG-14:10 |
EnergyTransfer:Building | 21150.50 | 87306.44 | 16-JAN-16:40 | 1976481.64 | 02-JAN-06:20 |
EnergyTransfer:Zone:BASEMENT | 698.00 | 0.00 | 01-JAN-00:10 | 89997.61 | 13-NOV-09:20 |
Heating:EnergyTransfer | 771.78 | 0.00 | 19-JAN-22:10 | 1838768.36 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.07 | 0.00 | 01-JAN-00:10 | 5907.28 | 12-AUG-16:10 |
General:Heating:EnergyTransfer | 771.78 | 0.00 | 19-JAN-22:10 | 1838768.36 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.07 | 0.00 | 01-JAN-00:10 | 5907.28 | 12-AUG-16:10 |
Cooling:EnergyTransfer | 20378.73 | 82042.94 | 02-JAN-04:30 | 1972708.71 | 18-AUG-14:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 697.94 | 0.00 | 01-JAN-00:10 | 89997.61 | 13-NOV-09:20 |
General:Cooling:EnergyTransfer | 20378.73 | 82042.94 | 02-JAN-04:30 | 1972708.71 | 18-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 697.94 | 0.00 | 01-JAN-00:10 | 89997.61 | 13-NOV-09:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 648.12 | 0.00 | 01-JAN-00:40 | 58649.04 | 14-AUG-13:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 3164.95 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 3164.95 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 648.12 | 0.00 | 01-JAN-00:40 | 58649.04 | 14-AUG-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 648.12 | 0.00 | 01-JAN-00:40 | 58649.04 | 14-AUG-13:10 |
EnergyTransfer:Zone:CORE_MID | 5000.89 | 0.00 | 01-JAN-00:40 | 579189.43 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 10.98 | 0.00 | 01-JAN-00:10 | 579189.43 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 10.98 | 0.00 | 01-JAN-00:10 | 579189.43 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4989.91 | 0.00 | 01-JAN-00:40 | 517315.98 | 07-AUG-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4989.91 | 0.00 | 01-JAN-00:40 | 517315.98 | 07-AUG-13:10 |
EnergyTransfer:Zone:CORE_TOP | 479.71 | 0.00 | 01-JAN-00:40 | 98234.26 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 20.11 | 0.00 | 01-JAN-00:40 | 98234.26 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 20.11 | 0.00 | 01-JAN-00:40 | 98234.26 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 459.60 | 0.00 | 01-JAN-00:20 | 64667.59 | 10-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 459.60 | 0.00 | 01-JAN-00:20 | 64667.59 | 10-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 88.97 | 0.00 | 01-JAN-00:40 | 15154.86 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.36 | 0.00 | 01-JAN-00:40 | 15154.86 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.36 | 0.00 | 01-JAN-00:40 | 15154.86 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.61 | 0.00 | 01-JAN-00:20 | 14092.44 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.61 | 0.00 | 01-JAN-00:20 | 14092.44 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 86.59 | 0.00 | 01-JAN-00:40 | 16947.11 | 02-AUG-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.65 | 0.00 | 01-JAN-00:40 | 10576.75 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.65 | 0.00 | 01-JAN-00:40 | 10576.75 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 84.94 | 0.00 | 01-JAN-00:20 | 16947.11 | 02-AUG-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 84.94 | 0.00 | 01-JAN-00:20 | 16947.11 | 02-AUG-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 138.35 | 0.00 | 01-JAN-00:40 | 26401.46 | 28-SEP-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 3.02 | 0.00 | 01-JAN-00:40 | 17118.97 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 3.02 | 0.00 | 01-JAN-00:40 | 17118.97 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 135.33 | 0.00 | 01-JAN-00:20 | 26401.46 | 28-SEP-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 135.33 | 0.00 | 01-JAN-00:20 | 26401.46 | 28-SEP-12:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 118.52 | 0.00 | 01-JAN-00:40 | 21939.49 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.51 | 0.00 | 01-JAN-00:10 | 8598.28 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.51 | 0.00 | 01-JAN-00:10 | 8598.28 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 118.01 | 0.00 | 01-JAN-00:40 | 21939.49 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 118.01 | 0.00 | 01-JAN-00:40 | 21939.49 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 886.41 | 0.00 | 01-JAN-00:40 | 260870.54 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 169.69 | 0.00 | 01-JAN-00:40 | 260870.54 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 169.69 | 0.00 | 01-JAN-00:40 | 260870.54 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 716.71 | 0.00 | 01-JAN-00:10 | 135067.27 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 716.71 | 0.00 | 01-JAN-00:10 | 135067.27 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 771.31 | 0.00 | 01-JAN-00:40 | 183850.45 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 90.11 | 0.00 | 01-JAN-00:40 | 183850.45 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 90.11 | 0.00 | 01-JAN-00:40 | 183850.45 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 681.20 | 0.00 | 01-JAN-00:10 | 181930.64 | 14-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 681.20 | 0.00 | 01-JAN-00:10 | 181930.64 | 14-JUL-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1310.25 | 0.00 | 01-JAN-00:40 | 271485.53 | 28-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 104.63 | 0.00 | 01-JAN-00:40 | 253515.32 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 104.63 | 0.00 | 01-JAN-00:40 | 253515.32 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1205.62 | 0.00 | 01-JAN-00:10 | 271485.53 | 28-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1205.62 | 0.00 | 01-JAN-00:10 | 271485.53 | 28-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 857.53 | 0.00 | 01-JAN-00:40 | 200471.89 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 80.39 | 0.00 | 01-JAN-00:40 | 180271.92 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 80.39 | 0.00 | 01-JAN-00:40 | 180271.92 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 777.14 | 0.00 | 01-JAN-00:10 | 200471.89 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 777.14 | 0.00 | 01-JAN-00:10 | 200471.89 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 112.47 | 0.00 | 01-JAN-00:40 | 33659.38 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.61 | 0.00 | 01-JAN-00:40 | 33659.38 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.61 | 0.00 | 01-JAN-00:40 | 33659.38 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 72.86 | 0.00 | 01-JAN-00:10 | 15640.01 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 72.86 | 0.00 | 01-JAN-00:10 | 15640.01 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 90.24 | 0.00 | 01-JAN-00:40 | 22024.27 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 21.91 | 0.00 | 01-JAN-00:40 | 22024.27 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 21.91 | 0.00 | 01-JAN-00:40 | 22024.27 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 68.33 | 0.00 | 01-JAN-00:10 | 18540.42 | 14-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 68.33 | 0.00 | 01-JAN-00:10 | 18540.42 | 14-JUL-09:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 146.12 | 0.00 | 01-JAN-00:40 | 32818.68 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 27.69 | 0.00 | 01-JAN-00:40 | 32818.68 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 27.69 | 0.00 | 01-JAN-00:40 | 32818.68 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 118.43 | 0.00 | 01-JAN-00:10 | 29166.54 | 28-SEP-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 118.43 | 0.00 | 01-JAN-00:10 | 29166.54 | 28-SEP-12:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 94.20 | 0.00 | 01-JAN-00:40 | 21889.43 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 18.33 | 0.00 | 01-JAN-00:40 | 21889.43 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 18.33 | 0.00 | 01-JAN-00:40 | 21889.43 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 75.87 | 0.00 | 01-JAN-00:10 | 21011.25 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 75.87 | 0.00 | 01-JAN-00:10 | 21011.25 | 15-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 86.98 | 0.00 | 01-JAN-00:40 | 11551.77 | 05-SEP-14:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.76 | 0.00 | 01-JAN-00:10 | 6584.66 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.76 | 0.00 | 01-JAN-00:10 | 6584.66 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 85.22 | 0.00 | 01-JAN-00:40 | 11551.77 | 05-SEP-14:30 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 85.22 | 0.00 | 01-JAN-00:40 | 11551.77 | 05-SEP-14:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 722.48 | 0.00 | 01-JAN-00:40 | 257141.87 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 93.47 | 0.00 | 01-JAN-00:40 | 257141.87 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 93.47 | 0.00 | 01-JAN-00:40 | 257141.87 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 629.01 | 0.00 | 01-JAN-00:10 | 101678.73 | 18-AUG-14:40 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 629.01 | 0.00 | 01-JAN-00:10 | 101678.73 | 18-AUG-14:40 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 197.88 | 0.00 | 01-JAN-00:40 | 51538.21 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 77.30 | 0.00 | 01-JAN-00:40 | 51538.21 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 77.30 | 0.00 | 01-JAN-00:40 | 51538.21 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 120.57 | 0.00 | 01-JAN-00:10 | 41039.08 | 19-JUN-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 120.57 | 0.00 | 01-JAN-00:10 | 41039.08 | 19-JUN-13:30 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.61 | 5.69 | 16-JAN-06:20 | 8445.22 | 31-AUG-17:30 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.05 | 0.00 | 02-JAN-08:20 | 665.52 | 01-JAN-01:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.05 | 0.00 | 02-JAN-08:20 | 665.52 | 01-JAN-01:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.56 | 0.00 | 01-JAN-00:10 | 8445.22 | 31-AUG-17:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.56 | 0.00 | 01-JAN-00:10 | 8445.22 | 31-AUG-17:30 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1189.16 | 6.00 | 28-JAN-19:30 | 81128.34 | 31-AUG-17:30 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 5.95 | 0.00 | 02-JAN-13:50 | 8582.02 | 15-JAN-10:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 5.95 | 0.00 | 02-JAN-13:50 | 8582.02 | 15-JAN-10:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1183.21 | 0.00 | 01-JAN-00:10 | 81128.34 | 31-AUG-17:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1183.21 | 0.00 | 01-JAN-00:10 | 81128.34 | 31-AUG-17:30 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 107.87 | 5.09 | 26-FEB-04:00 | 8219.23 | 31-AUG-17:20 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.40 | 0.00 | 02-JAN-13:10 | 947.88 | 16-JAN-17:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.40 | 0.00 | 02-JAN-13:10 | 947.88 | 16-JAN-17:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 106.47 | 0.00 | 01-JAN-00:10 | 8219.23 | 31-AUG-17:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 106.47 | 0.00 | 01-JAN-00:10 | 8219.23 | 31-AUG-17:20 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7183.85 | 81550.51 | 01-JAN-00:20 | 395933.55 | 28-APR-14:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.77 | 0.00 | 01-JAN-00:10 | 2812.99 | 05-JUN-01:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.77 | 0.00 | 01-JAN-00:10 | 2812.99 | 05-JUN-01:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7183.08 | 81550.51 | 01-JAN-00:20 | 395933.55 | 28-APR-14:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7183.08 | 81550.51 | 01-JAN-00:20 | 395933.55 | 28-APR-14:20 |
PlantLoopHeatingDemand:Facility | 2620.55 | 0.00 | 01-JAN-00:40 | 2438493.69 | 02-JAN-06:20 |
PlantLoopHeatingDemand:Plant | 421.10 | 0.00 | 01-JAN-00:10 | 52999.32 | 09-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 421.10 | 0.00 | 01-JAN-00:10 | 52999.32 | 09-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 421.10 | 0.00 | 01-JAN-00:10 | 52999.32 | 09-FEB-12:10 |
EnergyTransfer:HVAC | 18860.90 | 7.44 | 01-JAN-02:00 | 3118227.87 | 04-AUG-14:10 |
HeatingCoils:EnergyTransfer | 2199.45 | 0.00 | 01-JAN-00:40 | 2432150.04 | 02-JAN-06:20 |
PlantLoopHeatingDemand:HVAC | 2199.45 | 0.00 | 01-JAN-00:40 | 2432150.04 | 02-JAN-06:20 |
HeatingCoils:PlantLoopHeatingDemand | 2199.45 | 0.00 | 01-JAN-00:40 | 2432150.04 | 02-JAN-06:20 |
CoolingCoils:EnergyTransfer | 16661.45 | 0.00 | 01-JAN-00:20 | 3118227.87 | 04-AUG-14:10 |
EnergyTransfer:Plant | 51088.52 | 0.00 | 04-JAN-00:10 | 9547905.57 | 04-AUG-14:10 |
LoopToLoop:EnergyTransfer | 15205.51 | -3.60 | 03-JAN-07:50 | 3004726.27 | 04-AUG-14:10 |
WaterSystems:EnergyTransfer | 421.10 | 0.00 | 01-JAN-00:10 | 52999.32 | 09-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 421.10 | 0.00 | 01-JAN-00:10 | 52999.32 | 09-FEB-12:10 |
Boilers:EnergyTransfer | 2188.71 | 0.00 | 01-JAN-00:40 | 2464647.07 | 02-JAN-06:20 |
Chillers:EnergyTransfer | 15343.62 | 0.00 | 01-JAN-00:20 | 3021597.41 | 04-AUG-14:10 |
HeatRejection:EnergyTransfer | 17929.58 | 0.00 | 01-JAN-00:20 | 3498591.32 | 04-AUG-14:10 |
General:HeatRejection:EnergyTransfer | 17929.58 | 0.00 | 01-JAN-00:20 | 3498591.32 | 04-AUG-14:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.068 | -697.933 | 0.000 | 0.000 | 93.528 | 333.789 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -153.849 |
CORE_BOTTOM | 0.000 | 0.000 | 0.002 | -648.118 | 0.000 | 0.000 | 83.674 | 299.766 | 289.614 | 0.000 | 0.000 | 0.000 | 0.003 | 0.000 | 0.000 | 0.000 | 0.000 | -24.939 |
CORE_MID | 0.000 | 0.000 | 10.984 | -4989.894 | 0.000 | 0.000 | 850.416 | 2997.664 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1765.298 |
CORE_TOP | 0.000 | 0.000 | 20.109 | -459.598 | 0.000 | 0.000 | 88.725 | 299.766 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -238.615 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 2.360 | -86.605 | 0.000 | 0.000 | 11.105 | 37.639 | 36.365 | 31.693 | 0.000 | 0.126 | 60.032 | 0.000 | -84.675 | 0.000 | -8.040 | -0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.654 | -84.938 | 0.000 | 0.000 | 7.250 | 24.256 | 23.435 | 60.501 | 0.000 | 0.108 | 23.766 | 0.000 | -50.779 | 0.000 | -5.253 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 3.017 | -135.334 | 0.000 | 0.000 | 11.002 | 37.639 | 36.366 | 123.436 | 0.000 | 0.131 | 6.158 | 0.000 | -74.389 | 0.000 | -8.026 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.510 | -118.009 | 0.000 | 0.000 | 7.207 | 24.256 | 23.435 | 60.472 | 0.000 | 0.085 | 65.676 | 0.000 | -57.893 | 0.000 | -5.739 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 169.693 | -716.704 | 0.000 | 0.000 | 116.178 | 376.387 | 363.654 | 333.911 | 0.000 | 3.274 | 281.279 | 0.000 | -762.229 | 0.000 | -165.442 | -0.007 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 90.108 | -681.191 | 0.000 | 0.000 | 54.167 | 242.558 | 234.352 | 601.458 | 0.000 | 2.006 | 44.632 | 0.000 | -475.256 | 0.000 | -112.835 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 104.631 | -1205.611 | 0.000 | 0.000 | 111.370 | 376.395 | 363.660 | 1224.693 | 0.000 | 2.701 | 0.007 | 0.000 | -718.651 | 0.000 | -177.387 | -81.799 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 80.388 | -777.131 | 0.000 | 0.000 | 74.818 | 242.558 | 234.351 | 618.844 | 0.000 | 2.021 | 148.821 | 0.000 | -508.779 | 0.000 | -115.890 | -0.012 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 39.609 | -72.862 | 0.000 | 0.000 | 11.811 | 37.639 | 36.365 | 34.122 | 0.000 | 0.421 | 2.557 | 0.000 | -70.488 | 0.000 | -19.174 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 21.915 | -68.327 | 0.000 | 0.000 | 7.452 | 24.256 | 23.435 | 60.814 | 0.000 | 0.235 | 0.001 | 0.000 | -44.045 | 0.000 | -13.099 | -12.636 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 27.690 | -118.427 | 0.000 | 0.000 | 11.381 | 37.639 | 36.366 | 123.409 | 0.000 | 0.347 | 0.001 | 0.000 | -66.021 | 0.000 | -20.403 | -31.981 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 18.329 | -75.866 | 0.000 | 0.000 | 7.550 | 24.256 | 23.435 | 61.890 | 0.000 | 0.247 | 1.400 | 0.000 | -47.658 | 0.000 | -13.582 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.052 | -134.559 | 0.000 | 0.000 | 0.950 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -28.671 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 5.950 | -1183.205 | 0.000 | 0.000 | 9.506 | 83.466 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -454.522 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 1.404 | -106.469 | 0.000 | 0.000 | 0.952 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -58.114 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.768 | -7182.897 | 0.000 | 0.000 | 22.583 | 94.114 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -429.424 |
GROUNDFLOOR_PLENUM | 1.763 | -85.221 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.203 | 101.273 | 0.000 | 0.000 | 0.000 | -18.017 | 0.000 |
MIDFLOOR_PLENUM | 93.473 | -629.003 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.717 | 833.500 | 0.000 | 0.000 | 0.000 | -301.688 | -0.005 |
TOPFLOOR_PLENUM | 77.303 | -120.573 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.269 | 72.417 | 0.000 | 0.000 | 0.000 | -29.416 | -0.011 |
Total Facility | 172.539 | -834.797 | 599.241 | -19543.679 | 0.000 | 0.000 | 1581.623 | 5610.736 | 14676.396 | 3335.243 | 0.000 | 15.891 | 1641.521 | 0.000 | -2960.863 | 0.000 | -1013.991 | -3279.884 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 09-OCT-05:57 | 0.00 | 0.00 | 0.00 | -127911.19 | 0.00 | 0.00 | 399.52 | 1619.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 112434.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 23-OCT-04:11 | 0.00 | 0.00 | 0.00 | -119037.78 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.65 | 0.00 | 0.00 | 0.00 | 110191.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 01-JUN-04:11 | 0.00 | 0.00 | 0.00 | -1069684.92 | 0.00 | 0.00 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 981226.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 12-JUN-04:11 | 0.00 | 0.00 | 0.00 | -115414.00 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.62 | 0.00 | 0.00 | 0.00 | 106568.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 14-JUL-05:02 | 0.00 | 0.00 | 0.00 | -16764.31 | 0.00 | 0.00 | 107.14 | 365.16 | 960.25 | 3988.09 | 0.00 | 0.00 | 11348.29 | 0.00 | -0.00 | 0.00 | -4.61 | 0.00 |
PERIMETER_BOT_ZN_2 | 10-SEP-09:01 | 0.00 | 0.00 | 0.00 | -31050.46 | 0.00 | 0.00 | 19.85 | 117.66 | 464.11 | 17651.55 | 0.00 | 0.00 | 13019.08 | 0.00 | -0.00 | 0.00 | -221.79 | 0.00 |
PERIMETER_BOT_ZN_1 | 03-SEP-12:01 | 0.00 | 0.00 | 0.00 | -37175.02 | 0.00 | 0.00 | 31.85 | 182.58 | 720.19 | 24318.87 | 0.00 | 0.00 | 12038.99 | 0.00 | -0.00 | 0.00 | -117.46 | 0.00 |
PERIMETER_BOT_ZN_4 | 10-SEP-16:21 | 0.00 | 0.00 | 0.00 | -38516.37 | 0.00 | 0.00 | 17.35 | 117.66 | 464.11 | 20104.10 | 0.00 | 0.00 | 17993.76 | 0.00 | -0.00 | 0.00 | -180.61 | 0.00 |
PERIMETER_MID_ZN_3 | 18-JUL-05:02 | 0.00 | 0.00 | 0.00 | -171809.40 | 0.00 | 0.00 | 1105.71 | 3651.57 | 9602.45 | 4893.38 | 0.00 | 15.59 | 152540.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 09-JUL-09:21 | 0.00 | 0.00 | 0.00 | -346017.27 | 0.00 | 0.00 | 173.81 | 1176.61 | 4641.14 | 166368.15 | 0.00 | 0.00 | 173772.93 | 0.00 | -0.00 | 0.00 | -115.36 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-13:11 | 0.00 | 0.00 | 0.00 | -391312.93 | 0.00 | 0.00 | 280.51 | 1825.83 | 7201.95 | 226047.22 | 0.00 | 0.00 | 158666.91 | 0.00 | -0.00 | 0.00 | -2709.48 | 0.00 |
PERIMETER_MID_ZN_4 | 13-AUG-15:51 | 0.00 | 0.00 | 0.00 | -355583.04 | 0.00 | 0.00 | 169.80 | 1176.61 | 4641.11 | 164114.46 | 0.00 | 148.26 | 185332.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-AUG-15:11 | 0.00 | 0.00 | 0.00 | -36611.71 | 0.00 | 0.00 | 42.54 | 182.58 | 720.18 | 5814.96 | 0.00 | 264.81 | 29586.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-SEP-09:21 | 0.00 | 0.00 | 0.00 | -34081.51 | 0.00 | 0.00 | 19.10 | 117.66 | 464.11 | 16452.80 | 0.00 | 0.00 | 17163.94 | 0.00 | -0.00 | 0.00 | -136.11 | 0.00 |
PERIMETER_TOP_ZN_1 | 03-SEP-12:41 | 0.00 | 0.00 | 0.00 | -47462.14 | 0.00 | 0.00 | 30.38 | 182.58 | 720.19 | 21311.13 | 0.00 | 0.00 | 25629.92 | 0.00 | -0.00 | 0.00 | -412.07 | 0.00 |
PERIMETER_TOP_ZN_4 | 10-SEP-16:11 | 0.00 | 0.00 | 0.00 | -38711.54 | 0.00 | 0.00 | 17.54 | 117.66 | 464.11 | 20172.42 | 0.00 | 0.00 | 18457.60 | 0.00 | -0.00 | 0.00 | -517.79 | 0.00 |
DATACENTER_BOT_ZN_6 | 31-AUG-17:30 | 0.00 | 0.00 | 0.00 | -8445.00 | 0.00 | 0.00 | 10.62 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 397.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 31-AUG-17:30 | 0.00 | 0.00 | 0.00 | -81126.08 | 0.00 | 0.00 | 106.15 | 2429.28 | 77944.22 | 0.00 | 0.00 | 0.00 | 646.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 31-AUG-17:20 | 0.00 | 0.00 | 0.00 | -8218.96 | 0.00 | 0.00 | 10.62 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 170.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 02-NOV-12:22 | 0.00 | 0.00 | 0.00 | -524330.74 | 0.00 | 0.00 | 2683.03 | 8217.58 | 284724.39 | 0.00 | 0.00 | 0.00 | 228705.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 05-SEP-05:02 | 0.00 | -13330.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13376.79 | 0.00 | -0.00 | 0.00 | -46.16 | 0.00 |
MIDFLOOR_PLENUM | 12-FEB-06:11 | 0.00 | -179532.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250056.02 | 0.00 | -0.00 | 0.00 | -70523.97 | 0.00 |
TOPFLOOR_PLENUM | 19-JUN-13:30 | 0.00 | -41038.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.00 | 40752.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-AUG-05:02 | 0.00 | -21118.19 | 0.00 | -2145019.69 | 0.00 | 0.00 | 15734.25 | 54433.43 | 616289.16 | 16774.19 | 0.00 | 401.62 | 1462654.47 | 0.00 | -149.23 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 12-AUG-16:03 | 0.00 | 0.00 | 6795.17 | 0.00 | 0.00 | 0.00 | 520.14 | 1619.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22392.01 |
CORE_BOTTOM | 02-JAN-06:01 | 0.00 | 0.00 | 12282.13 | 0.00 | 0.00 | 0.00 | 1133.04 | 2908.23 | 7647.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23970.79 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 702959.16 | 0.00 | 0.00 | 0.00 | 0.00 | 14541.15 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -776876.54 |
CORE_TOP | 13-FEB-04:01 | 0.00 | 0.00 | 111003.59 | 0.00 | 0.00 | 0.00 | 0.00 | 1454.11 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -118395.33 |
PERIMETER_BOT_ZN_3 | 02-JAN-04:01 | 0.00 | 0.00 | 19134.39 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8479.82 | 0.00 | -599.97 | -10982.74 |
PERIMETER_BOT_ZN_2 | 02-JAN-04:01 | 0.00 | 0.00 | 18322.66 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5507.29 | 0.00 | -403.65 | -13009.85 |
PERIMETER_BOT_ZN_1 | 02-JAN-04:01 | 0.00 | 0.00 | 25036.48 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8159.86 | 0.00 | -602.93 | -17201.85 |
PERIMETER_BOT_ZN_4 | 02-JAN-04:01 | 0.00 | 0.00 | 17561.19 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5847.11 | 0.00 | -412.89 | -11899.32 |
PERIMETER_MID_ZN_3 | 06-FEB-01:01 | 0.00 | 0.00 | 316711.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1825.79 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -87799.47 | 0.00 | -48180.45 | -190013.35 |
PERIMETER_MID_ZN_2 | 06-FEB-01:01 | 0.00 | 0.00 | 259052.73 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.61 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -56003.96 | 0.00 | -32386.39 | -176643.66 |
PERIMETER_MID_ZN_1 | 06-FEB-01:01 | 0.00 | 0.00 | 306909.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1825.83 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -85690.56 | 0.00 | -48800.96 | -181699.14 |
PERIMETER_MID_ZN_4 | 06-FEB-01:01 | 0.00 | 0.00 | 262141.68 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.61 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -59618.31 | 0.00 | -32849.40 | -175655.23 |
PERIMETER_TOP_ZN_3 | 06-FEB-01:41 | 0.00 | 0.00 | 40633.31 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8339.57 | 0.00 | -5386.83 | -27835.05 |
PERIMETER_TOP_ZN_2 | 06-FEB-01:41 | 0.00 | 0.00 | 27510.24 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5316.47 | 0.00 | -3605.17 | -19186.72 |
PERIMETER_TOP_ZN_1 | 06-FEB-01:41 | 0.00 | 0.00 | 39576.77 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8074.95 | 0.00 | -5451.78 | -26978.21 |
PERIMETER_TOP_ZN_4 | 06-FEB-01:41 | 0.00 | 0.00 | 28975.25 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5682.93 | 0.00 | -3655.93 | -20234.51 |
DATACENTER_BOT_ZN_6 | 01-JAN-01:20 | 0.00 | 0.00 | 668.11 | 0.00 | 0.00 | 0.00 | 0.00 | 40.49 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2657.21 |
DATACENTER_MID_ZN_6 | 15-JAN-10:05 | 0.00 | 0.00 | 8608.24 | 0.00 | 0.00 | 0.00 | 59.20 | 404.88 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -28558.37 |
DATACENTER_TOP_ZN_6 | 16-JAN-17:50 | 0.00 | 0.00 | 947.93 | 0.00 | 0.00 | 0.00 | 6.02 | 40.49 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2943.04 |
DATACENTER_BASEMENT_ZN_6 | 05-JUN-01:01 | 0.00 | 0.00 | 28123.46 | 0.00 | 0.00 | 0.00 | 0.00 | 456.53 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -218396.25 |
GROUNDFLOOR_PLENUM | 01-DEC-05:11 | 12792.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3201.93 | -9590.86 |
MIDFLOOR_PLENUM | 02-JAN-06:12 | 264327.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -6533.07 | -257794.84 |
TOPFLOOR_PLENUM | 06-FEB-05:12 | 60196.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7595.03 | -52600.97 |
Total Facility | 02-JAN-06:01 | 97982.14 | 131669.01 | 1936949.91 | -131669.01 | 0.00 | 0.00 | 23108.10 | 54433.43 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -335758.59 | 0.00 | -25729.03 | -2012400.92 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 14.2135 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 12.3057 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 143.8996 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 116.2655 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 16.5715 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 14.2049 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 7.0097 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 7.0097 | 0.1712 | 1.0000 | Not calculated | 1.2002 | 0.1712 | ||
AIRLOOP DATACENTER BASEMENT | 31.3961 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 31.3964 | 0.0108 | 1.0000 | Not calculated | 0.3384 | 0.0108 | ||
AIRLOOP DATACENTER BOT | 0.7343 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7343 | 0.0213 | 1.0000 | Not calculated | 0.0156 | 0.0213 | ||
AIRLOOP DATACENTER MID | 7.0446 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 7.0446 | 0.0222 | 1.0000 | Not calculated | 0.1563 | 0.0222 | ||
AIRLOOP DATACENTER TOP | 0.7277 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7277 | 0.0215 | 1.0000 | Not calculated | 0.0156 | 0.0215 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 7.1068 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.2641 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 71.9498 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 43.1699 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 8.2858 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9715 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 2.1029 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 2.1029 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.5707 | ||
AIRLOOP DATACENTER BASEMENT | 15.6980 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 15.6980 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0216 | ||
AIRLOOP DATACENTER BOT | 0.7343 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7343 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0213 | ||
AIRLOOP DATACENTER MID | 7.0446 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 7.0446 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0222 | ||
AIRLOOP DATACENTER TOP | 0.7277 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7277 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0215 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 7.0097 | 7.0097 | 2.1029 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.4119 | 7.4119 | 2.2236 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 70.3861 | 70.3861 | 21.1158 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.8917 | 7.8917 | 2.3675 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3238 | 1.3238 | 0.3971 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6101 | 1.6101 | 0.4830 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9072 | 1.9072 | 0.5721 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9605 | 1.9605 | 0.5882 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 19.3819 | 19.3819 | 5.8146 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 17.0439 | 17.0439 | 5.1132 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 19.0213 | 19.0213 | 5.7064 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.0664 | 18.0664 | 5.4199 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4947 | 2.4947 | 0.7484 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7514 | 1.7514 | 0.5254 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4580 | 2.4580 | 0.7374 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9757 | 1.9757 | 0.5927 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7343 | 0.7343 | 0.7343 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.0446 | 7.0446 | 7.0446 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7277 | 0.7277 | 0.7277 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 31.3961 | 31.3961 | 15.6980 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 14.2135 | 12.3057 | 14.2135 | 4.2641 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 143.8996 | 116.2655 | 143.8996 | 43.1699 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 16.5715 | 14.2049 | 16.5715 | 4.9715 | 0.0000 | 1.0000 |
CAV_BAS | 7.0097 | 7.0097 | 7.0097 | 2.1029 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 31.3961 | 31.3964 | 31.3961 | 15.6980 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.7343 | 0.7343 | 0.7343 | 0.7343 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 7.0446 | 7.0446 | 7.0446 | 7.0446 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.7277 | 0.7277 | 0.7277 | 0.7277 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 2.1029 | 2.1029 | 2.1029 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7060 | 3.7060 | 2.2236 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 35.1931 | 35.1931 | 21.1158 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.9459 | 3.9459 | 2.3675 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6619 | 0.6619 | 0.3971 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8051 | 0.8051 | 0.4830 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9536 | 0.9536 | 0.5721 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9803 | 0.9803 | 0.5882 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.6910 | 9.6910 | 5.8146 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.5220 | 8.5220 | 5.1132 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.5106 | 9.5106 | 5.7064 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.0332 | 9.0332 | 5.4199 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2474 | 1.2474 | 0.7484 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8757 | 0.8757 | 0.5254 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2290 | 1.2290 | 0.7374 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9878 | 0.9878 | 0.5927 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7343 | 0.7343 | 0.7343 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.0446 | 7.0446 | 7.0446 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7277 | 0.7277 | 0.7277 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 15.6980 | 15.6980 | 15.6980 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 7.1068 | 4.2641 | 4.2641 | 4.2641 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 71.9498 | 43.1699 | 43.1699 | 43.1699 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 8.2858 | 4.9715 | 4.9715 | 4.9715 | 0.0000 | 1.0000 |
CAV_BAS | 2.1029 | 2.1029 | 2.1029 | 2.1029 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 15.6980 | 15.6980 | 15.6980 | 15.6980 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.7343 | 0.7343 | 0.7343 | 0.7343 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 7.0446 | 7.0446 | 7.0446 | 7.0446 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.7277 | 0.7277 | 0.7277 | 0.7277 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 40.50 |
Number of hours cooling loads not met | 120.83 |
Number of hours not met | 161.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 3190.06 | 3138528.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3021.75 | 508172.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 5610.74 | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 1006.15 | 64082.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 56.04 | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.31 | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2679.35 | 296507.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 1226.95 | 107178.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 325.04 | 57461.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 891.67 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 426.48 | 53278.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 32487.63 |
Natural Gas | 0.00 | 3190.06 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 35677.68 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 121.13 |
Space Heating | 0.00 |
Space Cooling | 65.24 |
Fans (All) | 57.84 |
Service Water Heating | 9.21 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 701.37 |
Subtotal | 701.37 |
Natural Gas [MJ/m2] | |
Space Heating | 68.87 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 68.87 |
Subtotal | 68.87 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.73 |
Space Heating | 8.94 |
Space Cooling | 8.47 |
Fans (All) | 7.51 |
Service Water Heating | 1.20 |
Receptacle Equipment | 41.14 |
Miscellaneous | 17.02 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
LTG_SCH_DATACENTER | 2939. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8399.67 | 360.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8731.33 | 28.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8751.50 | 8.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8746.67 | 13.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8729.00 | 31.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8722.50 | 37.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8379.67 | 380.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8703.67 | 56.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8692.33 | 67.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8573.33 | 186.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8747.33 | 12.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8695.17 | 64.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8704.17 | 55.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8596.50 | 163.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 5272.50 | 3487.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 5259.83 | 3500.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 5248.17 | 3511.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6053.17 | 2706.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8614.83 | 145.17 | 0.00 | 0.00 | 0.00 |
Min | 5248.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 3511.83 | 0.00 | 0.00 | 0.00 |
Average | 8114.94 | 645.06 | 0.00 | 0.00 | 0.00 |
Sum | 186643.67 | 14836.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367504.17 | 1111.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330788.00 | 25.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330790.00 | 23.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1226.67 | 1041.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1222.67 | 1045.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1225.50 | 1042.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 68232.33 | 35162.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367504.17 | 35162.67 | 0.00 | 0.00 | 0.00 |
Average | 78619.62 | 1715.29 | 0.00 | 0.00 | 0.00 |
Sum | 1808251.33 | 39451.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8094.17 | 665.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 7854.83 | 905.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7903.50 | 856.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8106.50 | 653.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8093.00 | 667.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8395.67 | 364.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8206.67 | 553.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7882.17 | 877.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8104.00 | 656.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8074.00 | 686.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7978.83 | 781.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7960.67 | 799.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8151.00 | 609.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8076.83 | 683.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8042.17 | 717.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7973.83 | 786.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 5591.50 | 3168.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 5574.33 | 3185.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 5544.67 | 3215.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6109.50 | 2650.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 7829.00 | 931.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 7947.83 | 812.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7422.17 | 1337.83 | 0.00 | 0.00 | 0.00 |
Min | 5544.67 | 364.33 | 0.00 | 0.00 | 0.00 |
Max | 8395.67 | 3215.33 | 0.00 | 0.00 | 0.00 |
Average | 7605.08 | 1154.92 | 0.00 | 0.00 | 0.00 |
Sum | 174916.83 | 26563.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 366903.33 | 1712.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 329537.00 | 1276.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 329713.00 | 1100.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 329946.00 | 867.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38924.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38924.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38924.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38924.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1301.17 | 966.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1296.33 | 971.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1290.50 | 977.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 69338.67 | 34056.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 366903.33 | 34056.33 | 0.00 | 0.00 | 0.00 |
Average | 78511.88 | 1823.04 | 0.00 | 0.00 | 0.00 |
Sum | 1805773.17 | 41929.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.482305E+11 | 102562.46 | 30-JAN-05:59 | -5.0 | -6.1 | 0.539953E+10 | 7499.12 | 17-JAN-14:20 | -5.0 | -6.1 |
February | 0.441343E+11 | 119321.27 | 21-FEB-05:11 | 2.20 | 1.34 | 0.488703E+10 | 7499.27 | 24-FEB-14:30 | 8.85 | 2.78 |
March | 0.526534E+11 | 115213.59 | 01-MAR-06:01 | 3.98 | 1.92 | 0.604846E+10 | 7499.30 | 02-MAR-14:30 | 13.05 | 11.01 |
April | 0.501010E+11 | 99142.80 | 11-APR-04:11 | 6.10 | 1.61 | 0.540633E+10 | 7499.28 | 19-APR-13:09 | 10.10 | 5.64 |
May | 0.533042E+11 | 109119.93 | 30-MAY-04:12 | 17.80 | 14.10 | 0.589363E+10 | 7499.26 | 31-MAY-09:00 | 25.60 | 19.37 |
June | 0.606571E+11 | 113457.40 | 03-JUN-04:12 | 13.30 | 9.14 | 0.587875E+10 | 7499.44 | 29-JUN-13:50 | 22.70 | 19.82 |
July | 0.629706E+11 | 96805.72 | 11-JUL-04:53 | 19.40 | 15.02 | 0.547182E+10 | 7499.09 | 03-JUL-09:20 | 19.40 | 15.02 |
August | 0.729697E+11 | 104128.76 | 21-AUG-04:22 | 20.60 | 17.81 | 0.613814E+10 | 7499.19 | 28-AUG-09:00 | 25.00 | 16.57 |
September | 0.662787E+11 | 111718.01 | 25-SEP-04:11 | 14.40 | 11.46 | 0.545236E+10 | 7499.33 | 08-SEP-13:00 | 14.40 | 11.46 |
October | 0.679118E+11 | 127911.00 | 09-OCT-05:57 | 2.20 | 1.71 | 0.566856E+10 | 7499.26 | 10-OCT-13:09 | 18.40 | 12.77 |
November | 0.618768E+11 | 108140.06 | 06-NOV-04:57 | 5.00 | 2.64 | 0.557909E+10 | 7499.27 | 08-NOV-14:50 | 13.68 | 11.16 |
December | 0.568485E+11 | 103345.52 | 26-DEC-05:11 | 5.77 | 4.97 | 0.533601E+10 | 7499.24 | 19-DEC-14:30 | 5.77 | 4.97 |
Annual Sum or Average | 0.697937E+12 | 0.671597E+11 | ||||||||
Minimum of Months | 0.441343E+11 | 96805.72 | -5.0 | -6.1 | 0.488703E+10 | 7499.09 | -5.0 | -6.1 | ||
Maximum of Months | 0.729697E+11 | 127911.00 | 20.60 | 17.81 | 0.613814E+10 | 7499.44 | 25.60 | 19.82 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366314E+11 | 102525.15 | 20-JAN-06:01 | 4.90 | -0.5 | 0.496271E+10 | 6734.86 | 20-JAN-10:20 | 4.80 | 1.25 |
February | 0.345140E+11 | 103884.96 | 23-FEB-06:01 | 3.98 | 1.67 | 0.453597E+10 | 6734.91 | 28-FEB-10:09 | 7.12 | 6.63 |
March | 0.485482E+11 | 108615.57 | 27-MAR-05:01 | 7.88 | 7.88 | 0.547507E+10 | 6734.90 | 02-MAR-10:09 | 7.88 | 7.88 |
April | 0.515213E+11 | 113646.60 | 11-APR-04:11 | 6.10 | 1.61 | 0.487078E+10 | 6734.91 | 17-APR-09:20 | 13.30 | 12.17 |
May | 0.558458E+11 | 115922.32 | 30-MAY-04:12 | 17.80 | 14.10 | 0.527896E+10 | 6734.84 | 04-MAY-09:20 | 17.80 | 14.10 |
June | 0.635027E+11 | 115983.19 | 01-JUN-04:11 | 15.40 | 14.50 | 0.526925E+10 | 6734.91 | 05-JUN-09:09 | 19.60 | 15.98 |
July | 0.716048E+11 | 96460.44 | 14-JUL-05:02 | 23.48 | 21.04 | 0.489390E+10 | 6734.79 | 18-JUL-09:20 | 23.70 | 22.96 |
August | 0.798830E+11 | 111224.60 | 26-AUG-04:11 | 16.10 | 13.15 | 0.549524E+10 | 6734.78 | 08-AUG-09:20 | 16.10 | 13.15 |
September | 0.583658E+11 | 116122.13 | 18-SEP-04:11 | 17.07 | 16.12 | 0.488143E+10 | 6734.85 | 19-SEP-09:20 | 18.87 | 14.31 |
October | 0.560075E+11 | 118997.16 | 23-OCT-04:11 | 12.97 | 10.92 | 0.507425E+10 | 6734.92 | 16-OCT-09:09 | 12.97 | 10.92 |
November | 0.470204E+11 | 117745.80 | 13-NOV-05:11 | 5.60 | 4.52 | 0.502076E+10 | 6734.90 | 27-NOV-10:09 | 9.60 | 8.30 |
December | 0.446736E+11 | 106712.87 | 20-DEC-05:11 | 5.03 | 2.79 | 0.487606E+10 | 6734.90 | 27-DEC-10:09 | 1.70 | 1.21 |
Annual Sum or Average | 0.648119E+12 | 0.606344E+11 | ||||||||
Minimum of Months | 0.345140E+11 | 96460.44 | 3.98 | -0.5 | 0.453597E+10 | 6734.78 | 1.70 | 1.21 | ||
Maximum of Months | 0.798830E+11 | 118997.16 | 23.48 | 21.04 | 0.549524E+10 | 6734.92 | 23.70 | 22.96 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.282023E+11 | 32195.68 | 27-JAN-16:53 | 4.40 | 2.53 | 0.455218E+10 | 6734.83 | 25-JAN-14:09 | 4.40 | 2.53 |
February | 0.278680E+11 | 33633.40 | 24-FEB-16:52 | 6.70 | 1.42 | 0.423970E+10 | 6734.88 | 23-FEB-10:00 | 6.70 | 1.42 |
March | 0.361398E+11 | 93812.23 | 04-MAR-06:01 | 7.20 | 7.20 | 0.535620E+10 | 6734.91 | 02-MAR-10:09 | 7.20 | 7.20 |
April | 0.377713E+11 | 95812.15 | 27-APR-05:03 | 11.70 | 10.21 | 0.480059E+10 | 6734.91 | 17-APR-09:20 | 11.70 | 10.21 |
May | 0.469761E+11 | 104084.71 | 31-MAY-04:12 | 16.10 | 14.49 | 0.525282E+10 | 6734.85 | 05-MAY-09:20 | 16.10 | 14.49 |
June | 0.534604E+11 | 106983.39 | 01-JUN-04:11 | 15.40 | 14.50 | 0.526200E+10 | 6734.91 | 05-JUN-09:09 | 19.60 | 15.98 |
July | 0.548567E+11 | 94932.38 | 11-JUL-04:11 | 19.80 | 15.19 | 0.488998E+10 | 6734.80 | 18-JUL-09:20 | 23.70 | 22.96 |
August | 0.590148E+11 | 104067.51 | 26-AUG-04:11 | 16.10 | 13.15 | 0.549561E+10 | 6734.78 | 08-AUG-09:20 | 16.10 | 13.15 |
September | 0.480677E+11 | 104908.60 | 15-SEP-04:12 | 16.50 | 12.91 | 0.486317E+10 | 6734.85 | 19-SEP-09:20 | 18.87 | 14.31 |
October | 0.431263E+11 | 103875.35 | 05-OCT-04:11 | 15.60 | 14.32 | 0.503228E+10 | 6734.92 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.327181E+11 | 97923.56 | 04-NOV-05:01 | 10.50 | 9.29 | 0.486844E+10 | 6734.90 | 14-NOV-10:09 | 11.70 | 11.70 |
December | 0.307895E+11 | 34468.74 | 21-DEC-16:25 | 2.25 | -2.5 | 0.465384E+10 | 6734.88 | 20-DEC-10:30 | 2.25 | -2.5 |
Annual Sum or Average | 0.498991E+12 | 0.592668E+11 | ||||||||
Minimum of Months | 0.278680E+11 | 32195.68 | 2.25 | -2.5 | 0.423970E+10 | 6734.78 | 2.25 | -2.5 | ||
Maximum of Months | 0.590148E+11 | 106983.39 | 19.80 | 15.19 | 0.549561E+10 | 6734.92 | 23.70 | 22.96 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203375E+11 | 23373.76 | 19-JAN-16:57 | 7.80 | 2.37 | 0.403738E+10 | 6388.34 | 19-JAN-14:00 | 7.80 | 2.37 |
February | 0.197985E+11 | 23926.07 | 17-FEB-17:00 | 5.60 | 1.58 | 0.370704E+10 | 6513.39 | 17-FEB-14:00 | 5.60 | 1.58 |
March | 0.288721E+11 | 38316.19 | 03-MAR-16:11 | 14.27 | 7.97 | 0.480754E+10 | 6734.88 | 24-MAR-13:09 | 10.68 | 6.57 |
April | 0.327390E+11 | 53622.93 | 07-APR-15:40 | 25.60 | 16.07 | 0.449492E+10 | 6734.88 | 19-APR-13:09 | 10.10 | 5.64 |
May | 0.453003E+11 | 106706.35 | 30-MAY-05:02 | 18.17 | 14.31 | 0.511744E+10 | 6734.81 | 04-MAY-13:20 | 18.17 | 14.31 |
June | 0.573147E+11 | 115446.65 | 12-JUN-04:11 | 18.70 | 17.72 | 0.523729E+10 | 6734.91 | 05-JUN-09:09 | 18.70 | 17.72 |
July | 0.619290E+11 | 109429.56 | 14-JUL-05:02 | 23.48 | 21.04 | 0.488273E+10 | 6734.79 | 18-JUL-09:20 | 23.70 | 22.96 |
August | 0.646554E+11 | 115246.83 | 01-AUG-04:01 | 23.90 | 20.81 | 0.547935E+10 | 6734.76 | 23-AUG-09:20 | 23.17 | 15.83 |
September | 0.467841E+11 | 106738.94 | 02-SEP-04:11 | 22.60 | 16.46 | 0.478494E+10 | 6734.83 | 25-SEP-13:20 | 19.63 | 15.53 |
October | 0.362509E+11 | 100833.11 | 06-OCT-05:01 | 19.40 | 18.22 | 0.476954E+10 | 6734.88 | 19-OCT-13:50 | 15.60 | 10.42 |
November | 0.244626E+11 | 35621.24 | 03-NOV-15:55 | 15.00 | 10.26 | 0.430807E+10 | 6734.89 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.211565E+11 | 22717.51 | 20-DEC-17:00 | 6.70 | 3.52 | 0.395687E+10 | 6318.47 | 20-DEC-14:00 | 6.70 | 3.52 |
Annual Sum or Average | 0.459601E+12 | 0.555831E+11 | ||||||||
Minimum of Months | 0.197985E+11 | 22717.51 | 5.60 | 1.58 | 0.370704E+10 | 6318.47 | 5.60 | 1.58 | ||
Maximum of Months | 0.646554E+11 | 115446.65 | 25.60 | 21.04 | 0.547935E+10 | 6734.91 | 23.70 | 22.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225687E+10 | 3778.29 | 24-JAN-06:02 | 11.10 | 11.10 | 0.493874E+09 | 762.36 | 20-JAN-14:50 | 11.10 | 11.10 |
February | 0.208275E+10 | 4521.49 | 20-FEB-12:51 | 9.40 | 4.36 | 0.448609E+09 | 766.62 | 24-FEB-14:20 | 9.03 | 2.95 |
March | 0.455243E+10 | 6663.27 | 27-MAR-15:50 | 21.73 | 16.25 | 0.602294E+09 | 845.63 | 02-MAR-14:09 | 21.73 | 16.25 |
April | 0.608657E+10 | 9255.22 | 07-APR-13:50 | 26.20 | 16.03 | 0.575841E+09 | 845.64 | 17-APR-09:30 | 13.30 | 12.22 |
May | 0.842868E+10 | 11600.90 | 30-MAY-13:30 | 29.70 | 17.47 | 0.652032E+09 | 845.63 | 04-MAY-13:20 | 29.70 | 17.47 |
June | 0.115304E+11 | 14586.85 | 22-JUN-05:02 | 22.88 | 15.44 | 0.660275E+09 | 845.64 | 05-JUN-09:09 | 22.88 | 15.44 |
July | 0.139581E+11 | 16771.19 | 14-JUL-05:02 | 23.48 | 21.04 | 0.615129E+09 | 845.62 | 18-JUL-09:20 | 23.70 | 22.96 |
August | 0.145967E+11 | 16324.86 | 02-AUG-05:02 | 24.50 | 22.18 | 0.689342E+09 | 845.63 | 23-AUG-13:20 | 25.60 | 17.10 |
September | 0.881188E+10 | 15605.82 | 05-SEP-04:11 | 20.53 | 17.94 | 0.605754E+09 | 845.63 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.686969E+10 | 8833.70 | 04-OCT-13:20 | 24.80 | 18.68 | 0.613710E+09 | 845.64 | 13-OCT-13:39 | 21.70 | 17.54 |
November | 0.422024E+10 | 5816.52 | 03-NOV-13:51 | 17.80 | 10.67 | 0.558959E+09 | 845.63 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.321080E+10 | 4243.10 | 17-DEC-11:22 | 11.40 | 4.43 | 0.498915E+09 | 789.43 | 26-DEC-14:09 | 8.80 | 4.42 |
Annual Sum or Average | 0.866051E+11 | 0.701473E+10 | ||||||||
Minimum of Months | 0.208275E+10 | 3778.29 | 9.40 | 4.36 | 0.448609E+09 | 762.36 | 8.80 | 2.95 | ||
Maximum of Months | 0.145967E+11 | 16771.19 | 29.70 | 22.18 | 0.689342E+09 | 845.64 | 29.70 | 22.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230166E+10 | 4866.08 | 19-JAN-09:50 | 7.23 | 3.99 | 0.313398E+09 | 536.65 | 19-JAN-10:09 | 7.80 | 4.25 |
February | 0.246663E+10 | 5728.31 | 20-FEB-12:51 | 9.40 | 4.36 | 0.288824E+09 | 544.96 | 22-FEB-10:09 | 0.87 | -3.0 |
March | 0.501783E+10 | 14407.50 | 26-MAR-08:27 | 9.45 | 8.46 | 0.381496E+09 | 544.96 | 24-MAR-09:09 | 9.45 | 8.46 |
April | 0.651832E+10 | 28938.91 | 23-APR-09:01 | 12.07 | 8.10 | 0.360014E+09 | 544.96 | 05-APR-09:30 | 12.07 | 8.10 |
May | 0.904936E+10 | 28512.60 | 29-MAY-08:32 | 25.37 | 16.74 | 0.407830E+09 | 544.97 | 25-MAY-09:09 | 25.37 | 16.74 |
June | 0.103304E+11 | 29054.62 | 04-JUN-09:02 | 23.48 | 12.89 | 0.419077E+09 | 544.97 | 26-JUN-09:09 | 25.18 | 19.58 |
July | 0.122412E+11 | 28809.73 | 02-JUL-08:22 | 25.00 | 21.47 | 0.391852E+09 | 544.95 | 11-JUL-09:20 | 24.27 | 16.60 |
August | 0.135855E+11 | 28417.29 | 27-AUG-09:42 | 25.82 | 21.81 | 0.440777E+09 | 545.06 | 02-AUG-09:09 | 25.82 | 21.81 |
September | 0.881603E+10 | 31048.08 | 10-SEP-09:01 | 20.28 | 13.62 | 0.382394E+09 | 544.97 | 19-SEP-09:09 | 18.58 | 14.06 |
October | 0.736752E+10 | 27365.05 | 15-OCT-09:11 | 17.57 | 12.46 | 0.388130E+09 | 544.97 | 13-OCT-13:39 | 17.57 | 12.46 |
November | 0.425762E+10 | 7119.30 | 02-NOV-08:41 | 10.82 | 5.71 | 0.343027E+09 | 544.96 | 03-NOV-09:09 | 12.88 | 8.14 |
December | 0.298645E+10 | 5813.79 | 17-DEC-11:22 | 11.40 | 4.43 | 0.309740E+09 | 537.42 | 20-DEC-10:09 | 8.40 | 5.03 |
Annual Sum or Average | 0.849385E+11 | 0.442656E+10 | ||||||||
Minimum of Months | 0.230166E+10 | 4866.08 | 7.23 | 3.99 | 0.288824E+09 | 536.65 | 0.87 | -3.0 | ||
Maximum of Months | 0.135855E+11 | 31048.08 | 25.82 | 21.81 | 0.440777E+09 | 545.06 | 25.82 | 21.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.500133E+10 | 18040.99 | 17-JAN-13:07 | 10.18 | 5.51 | 0.533221E+09 | 845.65 | 20-JAN-10:20 | 4.80 | 1.25 |
February | 0.541860E+10 | 32790.74 | 20-FEB-13:31 | 9.07 | 4.47 | 0.496667E+09 | 845.65 | 10-FEB-14:09 | 9.07 | 4.47 |
March | 0.921830E+10 | 32164.61 | 26-MAR-12:31 | 13.33 | 10.81 | 0.616438E+09 | 845.65 | 14-MAR-13:09 | 13.33 | 10.81 |
April | 0.950132E+10 | 20846.95 | 07-APR-12:30 | 26.15 | 15.90 | 0.561807E+09 | 846.11 | 07-APR-13:09 | 26.60 | 16.32 |
May | 0.110484E+11 | 21409.42 | 21-MAY-13:02 | 21.88 | 13.40 | 0.631846E+09 | 845.65 | 15-MAY-13:00 | 21.88 | 13.40 |
June | 0.135504E+11 | 18718.27 | 19-JUN-12:40 | 35.57 | 24.06 | 0.653225E+09 | 845.66 | 05-JUN-09:09 | 35.57 | 24.06 |
July | 0.168097E+11 | 27985.01 | 09-JUL-14:22 | 29.45 | 24.51 | 0.611875E+09 | 845.64 | 18-JUL-09:20 | 23.70 | 22.96 |
August | 0.205841E+11 | 34900.12 | 27-AUG-11:42 | 28.12 | 22.37 | 0.686264E+09 | 846.15 | 16-AUG-13:39 | 28.12 | 22.37 |
September | 0.148396E+11 | 37174.16 | 03-SEP-12:01 | 24.32 | 15.70 | 0.600626E+09 | 849.11 | 28-SEP-13:09 | 22.98 | 13.55 |
October | 0.149063E+11 | 35277.67 | 22-OCT-12:52 | 22.20 | 16.91 | 0.615635E+09 | 846.42 | 13-OCT-13:39 | 22.20 | 16.91 |
November | 0.812365E+10 | 23830.14 | 02-NOV-12:31 | 15.40 | 8.14 | 0.576533E+09 | 845.65 | 27-NOV-10:09 | 9.60 | 8.30 |
December | 0.633320E+10 | 33433.44 | 03-DEC-12:52 | 8.30 | 3.59 | 0.533748E+09 | 845.65 | 18-DEC-10:09 | 4.60 | 1.51 |
Annual Sum or Average | 0.135335E+12 | 0.711789E+10 | ||||||||
Minimum of Months | 0.500133E+10 | 18040.99 | 8.30 | 3.59 | 0.496667E+09 | 845.64 | 4.60 | 1.25 | ||
Maximum of Months | 0.205841E+11 | 37174.16 | 35.57 | 24.51 | 0.686264E+09 | 849.11 | 35.57 | 24.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.364057E+10 | 7541.63 | 17-JAN-15:30 | 10.30 | 4.98 | 0.319060E+09 | 544.82 | 19-JAN-14:00 | 8.90 | 3.60 |
February | 0.379171E+10 | 12100.42 | 20-FEB-15:36 | 7.57 | 4.52 | 0.294427E+09 | 544.96 | 17-FEB-14:30 | 7.57 | 4.52 |
March | 0.789954E+10 | 33240.78 | 26-MAR-16:41 | 10.78 | 9.70 | 0.385249E+09 | 544.96 | 23-MAR-13:00 | 10.78 | 9.70 |
April | 0.965952E+10 | 34891.79 | 23-APR-16:01 | 13.30 | 9.28 | 0.366455E+09 | 544.96 | 26-APR-09:50 | 16.38 | 12.56 |
May | 0.107426E+11 | 34166.68 | 21-MAY-15:01 | 20.73 | 13.62 | 0.402396E+09 | 544.96 | 15-MAY-13:00 | 20.73 | 13.62 |
June | 0.136146E+11 | 36079.73 | 03-JUN-17:41 | 17.88 | 13.58 | 0.421088E+09 | 544.96 | 01-JUN-09:30 | 17.88 | 13.58 |
July | 0.166942E+11 | 35985.17 | 02-JUL-16:21 | 24.70 | 20.69 | 0.395693E+09 | 544.95 | 18-JUL-09:20 | 23.70 | 22.96 |
August | 0.194546E+11 | 35668.57 | 13-AUG-16:01 | 29.90 | 20.51 | 0.444357E+09 | 544.96 | 16-AUG-13:39 | 32.20 | 25.36 |
September | 0.107952E+11 | 38512.01 | 10-SEP-16:21 | 23.05 | 12.79 | 0.379892E+09 | 544.96 | 05-SEP-13:00 | 23.05 | 12.79 |
October | 0.969375E+10 | 31420.97 | 15-OCT-15:51 | 19.40 | 12.19 | 0.381799E+09 | 544.98 | 13-OCT-13:39 | 19.40 | 12.19 |
November | 0.624000E+10 | 10893.71 | 03-NOV-15:21 | 16.10 | 10.65 | 0.351132E+09 | 544.96 | 08-NOV-14:30 | 14.45 | 11.27 |
December | 0.578253E+10 | 8557.81 | 08-DEC-15:23 | 6.40 | 2.12 | 0.328374E+09 | 544.96 | 15-DEC-14:39 | 4.23 | 0.34 |
Annual Sum or Average | 0.118009E+12 | 0.446992E+10 | ||||||||
Minimum of Months | 0.364057E+10 | 7541.63 | 6.40 | 2.12 | 0.294427E+09 | 544.82 | 4.23 | 0.34 | ||
Maximum of Months | 0.194546E+11 | 38512.01 | 29.90 | 20.69 | 0.444357E+09 | 544.98 | 32.20 | 25.36 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.685405E+09 | 3888.77 | 20-JAN-14:50 | 7.70 | 3.92 | 0.464581E+09 | 631.56 | 20-JAN-14:00 | 7.80 | 3.97 |
February | 0.770897E+09 | 4302.49 | 20-FEB-13:01 | 9.32 | 4.39 | 0.422250E+09 | 640.55 | 24-FEB-14:20 | 9.03 | 2.95 |
March | 0.294922E+10 | 5452.82 | 27-MAR-16:00 | 22.20 | 16.34 | 0.523703E+09 | 766.15 | 28-MAR-13:00 | 13.30 | 8.41 |
April | 0.485416E+10 | 7577.37 | 09-APR-16:01 | 17.02 | 14.08 | 0.504481E+09 | 845.62 | 07-APR-13:20 | 17.02 | 14.08 |
May | 0.833246E+10 | 10776.68 | 30-MAY-14:00 | 29.40 | 16.93 | 0.606158E+09 | 845.63 | 15-MAY-13:00 | 29.40 | 16.93 |
June | 0.109371E+11 | 13506.73 | 19-JUN-14:30 | 33.85 | 23.48 | 0.646665E+09 | 845.63 | 02-JUN-13:09 | 33.85 | 23.48 |
July | 0.124011E+11 | 17187.62 | 18-JUL-05:02 | 24.40 | 22.88 | 0.609145E+09 | 845.62 | 11-JUL-09:20 | 24.40 | 22.88 |
August | 0.123361E+11 | 16168.97 | 05-AUG-05:02 | 26.20 | 23.65 | 0.679967E+09 | 845.63 | 23-AUG-13:20 | 25.60 | 17.10 |
September | 0.856855E+10 | 10837.05 | 02-SEP-05:03 | 22.12 | 16.30 | 0.572734E+09 | 845.63 | 19-SEP-13:20 | 21.70 | 16.49 |
October | 0.625882E+10 | 7739.54 | 04-OCT-14:05 | 24.32 | 18.98 | 0.544988E+09 | 845.56 | 25-OCT-13:00 | 24.40 | 11.67 |
November | 0.266516E+10 | 6020.56 | 02-NOV-13:10 | 15.68 | 8.29 | 0.477621E+09 | 761.31 | 03-NOV-13:00 | 17.80 | 10.67 |
December | 0.912309E+09 | 4160.49 | 17-DEC-13:12 | 12.20 | 5.06 | 0.449256E+09 | 638.99 | 20-DEC-14:09 | 9.72 | 5.77 |
Annual Sum or Average | 0.716712E+11 | 0.650155E+10 | ||||||||
Minimum of Months | 0.685405E+09 | 3888.77 | 7.70 | 3.92 | 0.422250E+09 | 631.56 | 7.80 | 2.95 | ||
Maximum of Months | 0.124011E+11 | 17187.62 | 33.85 | 23.65 | 0.679967E+09 | 845.63 | 33.85 | 23.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.717830E+09 | 6647.43 | 26-JAN-11:02 | 3.40 | -0.3 | 0.222172E+09 | 548.49 | 26-JAN-11:09 | 3.40 | -0.3 |
February | 0.104776E+10 | 12679.16 | 17-FEB-11:01 | 6.28 | 1.53 | 0.204166E+09 | 548.49 | 22-FEB-11:09 | 2.38 | -2.1 |
March | 0.301133E+10 | 18903.91 | 29-MAR-10:01 | 7.07 | 3.67 | 0.268143E+09 | 548.49 | 23-MAR-10:09 | 7.07 | 3.67 |
April | 0.486408E+10 | 28973.69 | 23-APR-09:01 | 12.07 | 8.10 | 0.256316E+09 | 548.49 | 06-APR-12:09 | 12.07 | 8.10 |
May | 0.815558E+10 | 34299.95 | 29-MAY-08:51 | 26.10 | 16.72 | 0.294596E+09 | 548.51 | 17-MAY-10:09 | 26.10 | 16.72 |
June | 0.980161E+10 | 29487.05 | 25-JUN-08:42 | 25.40 | 23.51 | 0.304563E+09 | 548.50 | 09-JUN-14:09 | 25.40 | 23.51 |
July | 0.111178E+11 | 34623.16 | 09-JUL-09:21 | 29.15 | 25.29 | 0.288510E+09 | 548.50 | 11-JUL-10:09 | 25.18 | 17.11 |
August | 0.122284E+11 | 31869.70 | 13-AUG-08:31 | 27.23 | 19.14 | 0.324190E+09 | 548.50 | 08-AUG-10:09 | 27.23 | 19.14 |
September | 0.798813E+10 | 33370.80 | 04-SEP-09:11 | 24.47 | 18.42 | 0.275626E+09 | 548.51 | 19-SEP-10:09 | 20.00 | 15.38 |
October | 0.588375E+10 | 20436.67 | 05-OCT-10:01 | 20.28 | 17.46 | 0.274509E+09 | 548.50 | 30-OCT-10:09 | 13.98 | 9.32 |
November | 0.222479E+10 | 15498.63 | 02-NOV-10:01 | 12.48 | 6.40 | 0.235856E+09 | 548.49 | 03-NOV-10:09 | 13.58 | 8.52 |
December | 0.107853E+10 | 6841.28 | 20-DEC-11:02 | 8.90 | 5.16 | 0.216380E+09 | 548.49 | 20-DEC-11:09 | 8.90 | 5.16 |
Annual Sum or Average | 0.681197E+11 | 0.316503E+10 | ||||||||
Minimum of Months | 0.717830E+09 | 6647.43 | 3.40 | -0.3 | 0.204166E+09 | 548.49 | 2.38 | -2.1 | ||
Maximum of Months | 0.122284E+11 | 34623.16 | 29.15 | 25.29 | 0.324190E+09 | 548.51 | 27.23 | 23.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.398350E+10 | 17947.41 | 19-JAN-13:30 | 9.40 | 3.94 | 0.521661E+09 | 845.65 | 26-JAN-14:30 | 4.40 | 1.03 |
February | 0.499808E+10 | 32472.76 | 20-FEB-13:41 | 8.98 | 4.49 | 0.485739E+09 | 845.65 | 17-FEB-14:09 | 8.98 | 4.49 |
March | 0.799707E+10 | 23913.84 | 01-MAR-13:02 | 13.90 | 6.68 | 0.600212E+09 | 845.65 | 14-MAR-13:09 | 2.98 | 0.20 |
April | 0.790510E+10 | 20840.43 | 07-APR-12:30 | 26.15 | 15.90 | 0.543379E+09 | 846.32 | 07-APR-13:20 | 26.50 | 16.25 |
May | 0.101570E+11 | 33978.15 | 29-MAY-12:52 | 27.20 | 16.98 | 0.617385E+09 | 845.65 | 15-MAY-13:39 | 27.20 | 16.98 |
June | 0.124527E+11 | 18566.04 | 19-JUN-13:10 | 34.90 | 23.89 | 0.646656E+09 | 845.65 | 05-JUN-09:30 | 34.90 | 23.89 |
July | 0.144499E+11 | 34497.12 | 30-JUL-13:21 | 27.20 | 24.02 | 0.610077E+09 | 845.64 | 18-JUL-09:20 | 27.20 | 24.02 |
August | 0.178612E+11 | 35360.19 | 27-AUG-12:32 | 27.97 | 22.65 | 0.684176E+09 | 846.26 | 25-AUG-13:20 | 27.97 | 22.65 |
September | 0.144237E+11 | 39141.99 | 04-SEP-13:11 | 26.10 | 18.36 | 0.592990E+09 | 880.17 | 28-SEP-13:20 | 23.17 | 13.55 |
October | 0.144361E+11 | 37272.92 | 22-OCT-12:21 | 21.65 | 16.58 | 0.606515E+09 | 861.95 | 04-OCT-13:20 | 21.65 | 16.58 |
November | 0.689590E+10 | 25430.71 | 02-NOV-12:41 | 15.50 | 8.17 | 0.556952E+09 | 845.65 | 08-NOV-14:20 | 14.83 | 11.30 |
December | 0.500178E+10 | 35197.48 | 17-DEC-13:12 | 12.20 | 5.06 | 0.516976E+09 | 845.65 | 14-DEC-14:09 | 12.20 | 5.06 |
Annual Sum or Average | 0.120562E+12 | 0.698272E+10 | ||||||||
Minimum of Months | 0.398350E+10 | 17947.41 | 8.98 | 3.94 | 0.485739E+09 | 845.64 | 2.98 | 0.20 | ||
Maximum of Months | 0.178612E+11 | 39141.99 | 34.90 | 24.02 | 0.684176E+09 | 880.17 | 34.90 | 24.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117624E+10 | 5239.06 | 31-JAN-16:00 | -1.1 | -5.7 | 0.305088E+09 | 500.04 | 31-JAN-16:10 | -1.3 | -5.8 |
February | 0.150257E+10 | 6653.05 | 22-FEB-16:13 | 4.03 | -0.7 | 0.281199E+09 | 523.65 | 17-FEB-14:00 | 4.03 | -0.7 |
March | 0.413029E+10 | 12234.66 | 26-MAR-16:44 | 10.78 | 9.70 | 0.352818E+09 | 544.96 | 02-MAR-14:30 | 10.78 | 9.70 |
April | 0.580930E+10 | 32964.26 | 09-APR-16:41 | 16.28 | 13.85 | 0.327536E+09 | 544.96 | 28-APR-13:00 | 16.10 | 9.86 |
May | 0.871345E+10 | 23047.37 | 27-MAY-17:04 | 21.60 | 11.98 | 0.378752E+09 | 544.96 | 15-MAY-13:00 | 21.60 | 11.98 |
June | 0.110787E+11 | 33047.62 | 03-JUN-17:41 | 17.88 | 13.58 | 0.407086E+09 | 544.96 | 02-JUN-13:09 | 17.88 | 13.58 |
July | 0.119718E+11 | 32868.68 | 02-JUL-16:21 | 24.70 | 20.69 | 0.388190E+09 | 544.95 | 27-JUL-13:20 | 29.27 | 21.70 |
August | 0.132870E+11 | 35574.81 | 13-AUG-15:51 | 30.00 | 20.46 | 0.434027E+09 | 544.96 | 23-AUG-13:20 | 25.60 | 17.10 |
September | 0.878520E+10 | 32948.27 | 04-SEP-16:31 | 24.80 | 18.90 | 0.360343E+09 | 544.95 | 12-SEP-13:20 | 22.40 | 15.58 |
October | 0.703093E+10 | 14961.19 | 04-OCT-15:30 | 23.35 | 19.12 | 0.352770E+09 | 544.96 | 13-OCT-13:39 | 21.70 | 17.54 |
November | 0.274357E+10 | 8120.90 | 03-NOV-15:21 | 16.10 | 10.65 | 0.312285E+09 | 541.38 | 06-NOV-14:00 | 13.30 | 7.72 |
December | 0.148472E+10 | 5680.33 | 17-DEC-13:52 | 12.20 | 5.29 | 0.294962E+09 | 493.73 | 08-DEC-14:00 | 12.20 | 5.29 |
Annual Sum or Average | 0.777137E+11 | 0.419505E+10 | ||||||||
Minimum of Months | 0.117624E+10 | 5239.06 | -1.1 | -5.7 | 0.281199E+09 | 493.73 | -1.3 | -5.8 | ||
Maximum of Months | 0.132870E+11 | 35574.81 | 30.00 | 20.69 | 0.434027E+09 | 544.96 | 29.27 | 21.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.349541E+09 | 5234.32 | 21-JAN-06:04 | -0.5 | -0.5 | 0.463534E+09 | 626.02 | 02-JAN-10:09 | -0.5 | -0.5 |
February | 0.375887E+09 | 5122.51 | 18-FEB-06:04 | 0.82 | -1.3 | 0.421046E+09 | 625.79 | 21-FEB-10:30 | 3.35 | 2.53 |
March | 0.224877E+10 | 6450.72 | 27-MAR-16:00 | 22.20 | 16.34 | 0.512720E+09 | 726.91 | 28-MAR-13:00 | 13.30 | 8.41 |
April | 0.451585E+10 | 8571.30 | 07-APR-15:20 | 25.60 | 16.01 | 0.481023E+09 | 845.61 | 07-APR-13:00 | 25.60 | 16.01 |
May | 0.877600E+10 | 12602.47 | 30-MAY-14:00 | 29.40 | 16.93 | 0.571226E+09 | 845.62 | 22-MAY-13:20 | 29.40 | 16.93 |
June | 0.121406E+11 | 15640.01 | 19-JUN-14:30 | 33.85 | 23.48 | 0.626226E+09 | 845.63 | 09-JUN-13:20 | 33.85 | 23.48 |
July | 0.140146E+11 | 30703.88 | 09-JUL-14:11 | 30.20 | 24.62 | 0.598885E+09 | 845.62 | 12-JUL-13:20 | 28.70 | 18.81 |
August | 0.137414E+11 | 36622.26 | 13-AUG-15:11 | 30.40 | 20.77 | 0.664777E+09 | 845.63 | 23-AUG-13:20 | 25.60 | 17.10 |
September | 0.901019E+10 | 12044.53 | 01-SEP-14:30 | 30.85 | 17.41 | 0.545124E+09 | 845.63 | 12-SEP-13:20 | 22.40 | 15.58 |
October | 0.570166E+10 | 8195.82 | 15-OCT-11:51 | 20.00 | 13.65 | 0.512864E+09 | 830.89 | 05-OCT-13:00 | 20.00 | 13.65 |
November | 0.173111E+10 | 6000.32 | 03-NOV-14:31 | 17.40 | 10.88 | 0.464109E+09 | 702.48 | 03-NOV-13:00 | 17.40 | 10.88 |
December | 0.257573E+09 | 5015.22 | 29-DEC-06:04 | 0.60 | -1.6 | 0.447272E+09 | 625.90 | 26-DEC-10:50 | 0.60 | -1.6 |
Annual Sum or Average | 0.728631E+11 | 0.630881E+10 | ||||||||
Minimum of Months | 0.257573E+09 | 5015.22 | -0.5 | -1.6 | 0.421046E+09 | 625.79 | -0.5 | -1.6 | ||
Maximum of Months | 0.140146E+11 | 36622.26 | 33.85 | 24.62 | 0.664777E+09 | 845.63 | 33.85 | 23.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.580414E+09 | 3961.47 | 19-JAN-10:20 | 7.80 | 4.36 | 0.299142E+09 | 438.06 | 19-JAN-10:30 | 7.80 | 4.48 |
February | 0.812861E+09 | 4144.42 | 22-FEB-10:10 | 0.87 | -3.0 | 0.272501E+09 | 452.44 | 22-FEB-10:20 | 1.13 | -2.8 |
March | 0.284344E+10 | 7272.90 | 29-MAR-09:41 | 6.52 | 3.33 | 0.351741E+09 | 544.96 | 03-MAR-10:00 | 6.52 | 3.33 |
April | 0.458755E+10 | 12601.87 | 07-APR-09:40 | 20.93 | 13.73 | 0.340425E+09 | 544.96 | 05-APR-09:30 | 20.93 | 13.73 |
May | 0.818331E+10 | 34056.72 | 29-MAY-08:21 | 25.00 | 16.74 | 0.392125E+09 | 544.97 | 25-MAY-09:09 | 25.00 | 16.74 |
June | 0.103708E+11 | 30572.53 | 04-JUN-10:32 | 25.20 | 13.32 | 0.410940E+09 | 544.96 | 05-JUN-09:09 | 19.60 | 15.98 |
July | 0.119568E+11 | 32391.48 | 09-JUL-09:31 | 29.43 | 25.37 | 0.390379E+09 | 545.39 | 14-JUL-09:39 | 30.03 | 21.41 |
August | 0.129196E+11 | 32726.39 | 13-AUG-08:31 | 27.23 | 19.14 | 0.440244E+09 | 545.33 | 02-AUG-09:09 | 27.23 | 19.14 |
September | 0.803625E+10 | 34092.67 | 04-SEP-09:21 | 24.75 | 18.34 | 0.369775E+09 | 544.97 | 19-SEP-09:09 | 18.58 | 14.06 |
October | 0.546812E+10 | 11365.19 | 15-OCT-09:12 | 17.57 | 12.46 | 0.363222E+09 | 544.96 | 16-OCT-09:39 | 17.43 | 14.32 |
November | 0.191048E+10 | 4767.53 | 02-NOV-09:50 | 12.02 | 6.15 | 0.305733E+09 | 497.38 | 02-NOV-09:00 | 12.20 | 6.20 |
December | 0.657927E+09 | 3889.75 | 20-DEC-10:00 | 8.30 | 5.00 | 0.288709E+09 | 433.14 | 20-DEC-10:09 | 8.40 | 5.03 |
Annual Sum or Average | 0.683275E+11 | 0.422494E+10 | ||||||||
Minimum of Months | 0.580414E+09 | 3889.75 | 0.87 | -3.0 | 0.272501E+09 | 433.14 | 1.13 | -2.8 | ||
Maximum of Months | 0.129196E+11 | 34092.67 | 29.43 | 25.37 | 0.440244E+09 | 545.39 | 30.03 | 21.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.333076E+10 | 17830.13 | 17-JAN-13:30 | 10.55 | 5.38 | 0.505525E+09 | 845.65 | 30-JAN-14:20 | 2.80 | -1.2 |
February | 0.409589E+10 | 18217.27 | 22-FEB-13:31 | 4.63 | -1.0 | 0.467920E+09 | 845.65 | 17-FEB-14:09 | 4.63 | -1.0 |
March | 0.698359E+10 | 23924.42 | 01-MAR-13:22 | 13.90 | 6.36 | 0.580062E+09 | 845.65 | 23-MAR-13:00 | 5.00 | 1.08 |
April | 0.739171E+10 | 21832.22 | 07-APR-12:40 | 26.33 | 16.06 | 0.522125E+09 | 845.65 | 19-APR-13:09 | 10.10 | 5.64 |
May | 0.104484E+11 | 43123.65 | 29-MAY-13:41 | 26.28 | 17.36 | 0.588738E+09 | 845.65 | 15-MAY-13:39 | 26.28 | 17.36 |
June | 0.135707E+11 | 20731.79 | 19-JUN-13:10 | 34.90 | 23.89 | 0.628230E+09 | 845.65 | 01-JUN-13:09 | 34.90 | 23.89 |
July | 0.160380E+11 | 44670.31 | 09-JUL-14:11 | 30.20 | 24.62 | 0.600114E+09 | 845.64 | 12-JUL-13:20 | 28.70 | 18.81 |
August | 0.191212E+11 | 45189.99 | 20-AUG-13:41 | 28.72 | 15.17 | 0.673126E+09 | 846.13 | 30-AUG-13:00 | 28.90 | 15.47 |
September | 0.145709E+11 | 47463.41 | 04-SEP-11:21 | 25.85 | 17.68 | 0.573989E+09 | 846.20 | 05-SEP-13:50 | 26.20 | 21.18 |
October | 0.133127E+11 | 43604.11 | 15-OCT-11:51 | 20.00 | 13.65 | 0.584639E+09 | 846.12 | 03-OCT-13:39 | 20.00 | 13.65 |
November | 0.576472E+10 | 24463.78 | 02-NOV-13:01 | 15.68 | 8.29 | 0.524606E+09 | 845.65 | 08-NOV-14:50 | 13.68 | 11.16 |
December | 0.380009E+10 | 16347.73 | 15-DEC-13:13 | 3.17 | -0.7 | 0.489920E+09 | 845.65 | 15-DEC-14:39 | 4.23 | 0.34 |
Annual Sum or Average | 0.118429E+12 | 0.673899E+10 | ||||||||
Minimum of Months | 0.333076E+10 | 16347.73 | 3.17 | -1.0 | 0.467920E+09 | 845.64 | 2.80 | -1.2 | ||
Maximum of Months | 0.191212E+11 | 47463.41 | 34.90 | 24.62 | 0.673126E+09 | 846.20 | 34.90 | 23.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.922994E+09 | 5532.65 | 17-JAN-15:50 | 10.10 | 4.92 | 0.302594E+09 | 485.21 | 17-JAN-15:00 | 10.00 | 4.89 |
February | 0.117117E+10 | 6187.36 | 22-FEB-16:11 | 4.03 | -0.7 | 0.278611E+09 | 521.20 | 22-FEB-16:40 | 3.67 | -0.7 |
March | 0.351643E+10 | 12318.31 | 15-MAR-15:52 | 14.40 | 5.70 | 0.348679E+09 | 544.96 | 03-MAR-14:20 | 14.40 | 5.70 |
April | 0.534343E+10 | 30691.06 | 09-APR-16:11 | 16.83 | 14.03 | 0.321014E+09 | 544.96 | 28-APR-13:00 | 16.10 | 9.86 |
May | 0.863017E+10 | 34000.66 | 14-MAY-15:51 | 13.30 | 9.05 | 0.369027E+09 | 544.96 | 15-MAY-13:00 | 17.80 | 11.36 |
June | 0.115401E+11 | 36162.42 | 04-JUN-15:51 | 22.20 | 14.53 | 0.399729E+09 | 544.96 | 02-JUN-13:09 | 22.20 | 14.53 |
July | 0.127425E+11 | 37351.59 | 09-JUL-15:31 | 27.20 | 24.21 | 0.383834E+09 | 544.95 | 12-JUL-13:20 | 28.70 | 18.81 |
August | 0.139240E+11 | 38467.30 | 13-AUG-15:51 | 30.00 | 20.46 | 0.428060E+09 | 544.96 | 23-AUG-13:20 | 25.60 | 17.10 |
September | 0.869668E+10 | 38709.68 | 10-SEP-16:11 | 23.13 | 12.82 | 0.352469E+09 | 544.95 | 12-SEP-13:20 | 22.40 | 15.58 |
October | 0.634882E+10 | 15601.10 | 04-OCT-15:30 | 23.35 | 19.12 | 0.345107E+09 | 544.96 | 19-OCT-13:00 | 15.60 | 10.54 |
November | 0.208785E+10 | 7828.51 | 03-NOV-15:21 | 16.10 | 10.65 | 0.306633E+09 | 524.94 | 02-NOV-13:00 | 16.10 | 10.65 |
December | 0.943104E+09 | 5205.87 | 08-DEC-15:40 | 6.30 | 2.04 | 0.291386E+09 | 467.15 | 08-DEC-14:00 | 6.30 | 2.04 |
Annual Sum or Average | 0.758673E+11 | 0.412714E+10 | ||||||||
Minimum of Months | 0.922994E+09 | 5205.87 | 4.03 | -0.7 | 0.278611E+09 | 467.15 | 3.67 | -0.7 | ||
Maximum of Months | 0.139240E+11 | 38709.68 | 30.00 | 24.21 | 0.428060E+09 | 544.96 | 28.70 | 18.81 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197311E+10 | 10654.73 | 14-JAN-05:01 | -7.3 | -8.0 | 0.00 | 0.00 | 01-JAN-00:10 | -7.3 | -8.0 |
February | 0.215976E+10 | 12306.85 | 06-FEB-04:01 | -13.3 | -14.8 | 0.00 | 0.00 | 01-FEB-00:10 | -13.3 | -14.8 |
March | 0.453807E+10 | 8451.72 | 22-MAR-05:01 | -2.3 | -5.1 | 0.00 | 0.00 | 01-MAR-00:10 | -2.3 | -5.1 |
April | 0.624918E+10 | 9182.77 | 08-APR-05:12 | 14.23 | 12.03 | 0.00 | 0.00 | 01-APR-00:10 | 14.23 | 12.03 |
May | 0.780752E+10 | 9916.77 | 30-MAY-15:10 | 28.30 | 17.27 | 0.00 | 0.00 | 01-MAY-00:10 | 28.30 | 17.27 |
June | 0.105490E+11 | 10490.44 | 27-JUN-05:02 | 21.20 | 21.12 | 0.00 | 0.00 | 01-JUN-00:10 | 21.20 | 21.12 |
July | 0.122472E+11 | 12497.05 | 10-JUL-05:13 | 26.10 | 20.74 | 0.00 | 0.00 | 01-JUL-00:10 | 26.10 | 20.74 |
August | 0.137158E+11 | 12624.67 | 21-AUG-05:12 | 20.60 | 17.79 | 0.00 | 0.00 | 01-AUG-00:10 | 20.60 | 17.79 |
September | 0.946773E+10 | 13331.36 | 05-SEP-05:02 | 20.60 | 18.00 | 0.00 | 0.00 | 01-SEP-00:10 | 20.60 | 18.00 |
October | 0.788725E+10 | 9257.72 | 06-OCT-05:02 | 19.40 | 18.22 | 0.00 | 0.00 | 01-OCT-00:10 | 19.40 | 18.22 |
November | 0.486034E+10 | 8569.64 | 20-NOV-06:01 | 0.00 | -1.2 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | -1.2 |
December | 0.376686E+10 | 8760.35 | 23-DEC-06:01 | 3.12 | 2.60 | 0.00 | 0.00 | 01-DEC-00:10 | 3.12 | 2.60 |
Annual Sum or Average | 0.852219E+11 | 0.00 | ||||||||
Minimum of Months | 0.197311E+10 | 8451.72 | -13.3 | -14.8 | 0.00 | 0.00 | -13.3 | -14.8 | ||
Maximum of Months | 0.137158E+11 | 13331.36 | 28.30 | 21.12 | 0.00 | 0.00 | 28.30 | 21.12 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157996E+10 | 16614.59 | 30-JAN-04:01 | -4.0 | -5.6 | 0.00 | 0.00 | 01-JAN-00:10 | -4.0 | -5.6 |
February | 0.167704E+10 | 17952.29 | 12-FEB-06:11 | -8.9 | -11.3 | 0.00 | 0.00 | 01-FEB-00:10 | -8.9 | -11.3 |
March | 0.236053E+10 | 16248.95 | 13-MAR-03:01 | 0.50 | -3.0 | 0.00 | 0.00 | 01-MAR-00:10 | 0.50 | -3.0 |
April | 0.390769E+10 | 13578.10 | 21-APR-04:11 | 5.60 | 5.12 | 0.00 | 0.00 | 01-APR-00:10 | 5.60 | 5.12 |
May | 0.611685E+10 | 8944.73 | 11-MAY-05:10 | 10.78 | 8.17 | 0.00 | 0.00 | 01-MAY-00:10 | 10.78 | 8.17 |
June | 0.881165E+10 | 10294.25 | 24-JUN-05:13 | 21.87 | 21.28 | 0.00 | 0.00 | 01-JUN-00:10 | 21.87 | 21.28 |
July | 0.100350E+11 | 10582.54 | 25-JUL-05:13 | 23.90 | 23.41 | 0.00 | 0.00 | 01-JUL-00:10 | 23.90 | 23.41 |
August | 0.110757E+11 | 10883.02 | 07-AUG-05:15 | 19.40 | 16.84 | 0.00 | 0.00 | 01-AUG-00:10 | 19.40 | 16.84 |
September | 0.779604E+10 | 10677.74 | 02-SEP-05:13 | 22.03 | 16.28 | 0.00 | 0.00 | 01-SEP-00:10 | 22.03 | 16.28 |
October | 0.564231E+10 | 9961.88 | 28-OCT-04:51 | 3.90 | 1.38 | 0.00 | 0.00 | 01-OCT-00:10 | 3.90 | 1.38 |
November | 0.244775E+10 | 15700.17 | 20-NOV-04:01 | 0.60 | -0.7 | 0.00 | 0.00 | 01-NOV-00:10 | 0.60 | -0.7 |
December | 0.145023E+10 | 16049.98 | 23-DEC-05:11 | 2.97 | 2.63 | 0.00 | 0.00 | 01-DEC-00:10 | 2.97 | 2.63 |
Annual Sum or Average | 0.629008E+11 | 0.00 | ||||||||
Minimum of Months | 0.145023E+10 | 8944.73 | -8.9 | -11.3 | 0.00 | 0.00 | -8.9 | -11.3 | ||
Maximum of Months | 0.110757E+11 | 17952.29 | 23.90 | 23.41 | 0.00 | 0.00 | 23.90 | 23.41 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114340E+09 | 3808.47 | 19-JAN-13:40 | 9.40 | 3.86 | 0.00 | 0.00 | 01-JAN-00:10 | 9.40 | 3.86 |
February | 0.455841E+09 | 6467.78 | 17-FEB-13:01 | 6.70 | 1.67 | 0.00 | 0.00 | 01-FEB-00:10 | 6.70 | 1.67 |
March | 0.364033E+10 | 14918.53 | 03-MAR-14:21 | 15.00 | 8.51 | 0.00 | 0.00 | 01-MAR-00:10 | 15.00 | 8.51 |
April | 0.725742E+10 | 27405.90 | 07-APR-13:05 | 26.60 | 16.32 | 0.00 | 0.00 | 01-APR-00:10 | 26.60 | 16.32 |
May | 0.140593E+11 | 36161.94 | 30-MAY-13:05 | 29.90 | 17.82 | 0.00 | 0.00 | 01-MAY-00:10 | 29.90 | 17.82 |
June | 0.209040E+11 | 41039.08 | 19-JUN-13:30 | 34.70 | 23.81 | 0.00 | 0.00 | 01-JUN-00:10 | 34.70 | 23.81 |
July | 0.245764E+11 | 38160.28 | 07-JUL-13:05 | 32.80 | 23.37 | 0.00 | 0.00 | 01-JUL-00:10 | 32.80 | 23.37 |
August | 0.258168E+11 | 37399.53 | 18-AUG-13:05 | 33.30 | 20.35 | 0.00 | 0.00 | 01-AUG-00:10 | 33.30 | 20.35 |
September | 0.139858E+11 | 32862.53 | 01-SEP-14:05 | 31.02 | 17.36 | 0.00 | 0.00 | 01-SEP-00:10 | 31.02 | 17.36 |
October | 0.822603E+10 | 23129.32 | 04-OCT-14:05 | 24.32 | 18.98 | 0.00 | 0.00 | 01-OCT-00:10 | 24.32 | 18.98 |
November | 0.142994E+10 | 10005.39 | 04-NOV-12:57 | 17.80 | 12.74 | 0.00 | 0.00 | 01-NOV-00:10 | 17.80 | 12.74 |
December | 0.107443E+09 | 4573.93 | 17-DEC-13:10 | 12.20 | 5.01 | 0.00 | 0.00 | 01-DEC-00:10 | 12.20 | 5.01 |
Annual Sum or Average | 0.120574E+12 | 0.00 | ||||||||
Minimum of Months | 0.107443E+09 | 3808.47 | 6.70 | 1.67 | 0.00 | 0.00 | 6.70 | 1.67 | ||
Maximum of Months | 0.258168E+11 | 41039.08 | 34.70 | 23.81 | 0.00 | 0.00 | 34.70 | 23.81 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222866E+10 | 2272.67 | 20-JAN-16:23 | 6.40 | 3.51 | 95229480.63 | 126.82 | 24-JAN-14:00 | 11.00 | 11.00 |
February | 0.670402E+10 | 4320.03 | 14-FEB-16:51 | 0.00 | -4.1 | 86396487.34 | 126.82 | 24-FEB-14:00 | 8.30 | 2.27 |
March | 0.135002E+11 | 6660.37 | 31-MAR-23:53 | 5.40 | 5.40 | 0.103236E+09 | 126.82 | 27-MAR-13:00 | 5.40 | 5.40 |
April | 0.183726E+11 | 8128.23 | 09-APR-17:24 | 15.55 | 13.44 | 91605362.51 | 126.83 | 10-APR-09:09 | 21.28 | 15.84 |
May | 0.432476E+10 | 3498.55 | 31-MAY-23:52 | 18.50 | 16.73 | 99234965.26 | 126.83 | 18-MAY-13:09 | 18.50 | 16.73 |
June | 0.948439E+10 | 5311.93 | 30-JUN-24:00 | 20.00 | 19.21 | 98959903.48 | 126.83 | 21-JUN-09:09 | 20.00 | 19.21 |
July | 0.149516E+11 | 7248.56 | 31-JUL-23:42 | 23.90 | 21.95 | 91882980.63 | 126.83 | 20-JUL-13:00 | 23.90 | 21.95 |
August | 0.200748E+11 | 8445.22 | 31-AUG-17:30 | 25.30 | 22.17 | 0.103240E+09 | 126.83 | 04-AUG-09:09 | 25.30 | 22.17 |
September | 0.447672E+10 | 3301.40 | 30-SEP-23:50 | 12.73 | 12.05 | 91608980.05 | 126.84 | 14-SEP-09:00 | 12.73 | 12.05 |
October | 0.920203E+10 | 4939.86 | 31-OCT-23:52 | 10.60 | 9.48 | 95230765.06 | 126.83 | 25-OCT-09:00 | 10.60 | 9.48 |
November | 0.130653E+11 | 6148.34 | 03-NOV-15:55 | 15.00 | 10.26 | 94300286.50 | 126.82 | 14-NOV-10:09 | 11.70 | 11.70 |
December | 0.181735E+11 | 7977.33 | 08-DEC-16:07 | 5.92 | 1.77 | 91880859.55 | 126.82 | 26-DEC-14:09 | 8.80 | 4.42 |
Annual Sum or Average | 0.134559E+12 | 0.114281E+10 | ||||||||
Minimum of Months | 0.222866E+10 | 2272.67 | 0.00 | -4.1 | 86396487.34 | 126.82 | 5.40 | 2.27 | ||
Maximum of Months | 0.200748E+11 | 8445.22 | 25.30 | 22.17 | 0.103240E+09 | 126.84 | 25.30 | 22.17 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.814344E+09 | 1957.67 | 20-JAN-16:23 | 6.40 | 3.51 | 94851291.34 | 126.82 | 24-JAN-14:00 | 11.00 | 11.00 |
February | 0.488472E+10 | 4028.41 | 22-FEB-16:51 | 3.30 | -0.7 | 86396487.34 | 126.82 | 24-FEB-14:00 | 8.30 | 2.27 |
March | 0.118151E+11 | 5989.95 | 31-MAR-23:22 | 5.80 | 5.80 | 0.103236E+09 | 126.82 | 06-MAR-10:20 | 5.80 | 5.80 |
April | 0.167654E+11 | 7724.70 | 12-APR-17:35 | 11.87 | 3.26 | 91605385.43 | 126.83 | 27-APR-13:00 | 17.20 | 14.14 |
May | 0.353858E+10 | 3302.83 | 31-MAY-23:52 | 18.50 | 16.73 | 99234891.20 | 126.83 | 18-MAY-13:00 | 18.50 | 16.73 |
June | 0.884533E+10 | 4971.00 | 30-JUN-24:00 | 20.00 | 19.21 | 98960128.39 | 126.83 | 21-JUN-13:09 | 20.00 | 19.21 |
July | 0.141852E+11 | 6939.73 | 31-JUL-24:00 | 23.90 | 22.01 | 91882995.80 | 126.83 | 20-JUL-13:00 | 23.90 | 22.01 |
August | 0.191203E+11 | 8112.83 | 31-AUG-17:30 | 25.30 | 22.17 | 0.103240E+09 | 126.83 | 04-AUG-09:09 | 25.30 | 22.17 |
September | 0.370370E+10 | 2913.84 | 30-SEP-23:20 | 13.13 | 12.30 | 91609036.04 | 126.84 | 14-SEP-09:00 | 13.13 | 12.30 |
October | 0.802265E+10 | 4309.61 | 31-OCT-23:32 | 10.97 | 9.90 | 95230828.26 | 126.83 | 25-OCT-09:00 | 10.97 | 9.90 |
November | 0.110289E+11 | 5830.81 | 03-NOV-15:55 | 15.00 | 10.26 | 94300291.82 | 126.82 | 10-NOV-10:09 | 16.02 | 15.59 |
December | 0.155964E+11 | 7451.56 | 08-DEC-16:03 | 5.92 | 1.77 | 91880863.84 | 126.82 | 26-DEC-14:09 | 8.80 | 4.42 |
Annual Sum or Average | 0.118321E+12 | 0.114243E+10 | ||||||||
Minimum of Months | 0.814344E+09 | 1957.67 | 3.30 | -0.7 | 86396487.34 | 126.82 | 5.80 | 2.27 | ||
Maximum of Months | 0.191203E+11 | 8112.83 | 25.30 | 22.17 | 0.103240E+09 | 126.84 | 25.30 | 22.17 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.408417E+09 | 1838.45 | 19-JAN-16:23 | 8.05 | 2.65 | 93837396.61 | 128.67 | 03-JAN-10:30 | 8.05 | 2.65 |
February | 0.312056E+10 | 3920.41 | 22-FEB-16:51 | 3.30 | -0.7 | 86393091.84 | 126.82 | 24-FEB-14:00 | 8.30 | 2.27 |
March | 0.100919E+11 | 5951.96 | 29-MAR-17:12 | 5.73 | 4.14 | 0.103236E+09 | 126.82 | 27-MAR-13:50 | 5.73 | 4.14 |
April | 0.155960E+11 | 7815.87 | 07-APR-16:00 | 25.60 | 16.13 | 91605364.12 | 126.83 | 27-APR-13:00 | 17.20 | 14.14 |
May | 0.294280E+10 | 3165.18 | 31-MAY-23:42 | 18.62 | 16.84 | 99237131.83 | 126.83 | 18-MAY-13:00 | 18.62 | 16.84 |
June | 0.871072E+10 | 4780.99 | 30-JUN-24:00 | 20.00 | 19.21 | 98960185.71 | 126.83 | 21-JUN-13:00 | 20.00 | 19.21 |
July | 0.142310E+11 | 6893.63 | 31-JUL-24:00 | 23.90 | 22.01 | 91882636.94 | 126.83 | 20-JUL-13:00 | 23.90 | 22.01 |
August | 0.190990E+11 | 8219.23 | 31-AUG-17:20 | 25.40 | 22.24 | 0.103240E+09 | 126.83 | 04-AUG-09:09 | 25.40 | 22.24 |
September | 0.323675E+10 | 2703.90 | 06-SEP-17:20 | 24.03 | 20.29 | 91609012.88 | 126.84 | 14-SEP-09:00 | 23.90 | 22.40 |
October | 0.673990E+10 | 4353.46 | 04-OCT-16:00 | 22.80 | 19.11 | 95230888.53 | 126.83 | 25-OCT-09:00 | 23.30 | 19.55 |
November | 0.907840E+10 | 5796.59 | 03-NOV-15:55 | 15.00 | 10.26 | 94300300.56 | 126.82 | 10-NOV-10:09 | 16.02 | 15.59 |
December | 0.132139E+11 | 7228.30 | 08-DEC-16:03 | 5.92 | 1.77 | 91880865.74 | 126.82 | 26-DEC-14:09 | 8.80 | 4.42 |
Annual Sum or Average | 0.106469E+12 | 0.114141E+10 | ||||||||
Minimum of Months | 0.408417E+09 | 1838.45 | 3.30 | -0.7 | 86393091.84 | 126.82 | 5.73 | 2.27 | ||
Maximum of Months | 0.190990E+11 | 8219.23 | 25.60 | 22.24 | 0.103240E+09 | 128.67 | 25.40 | 22.40 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233622E+12 | 101901.53 | 20-JAN-05:11 | 5.00 | -0.4 | 0.208072E+10 | 2808.41 | 19-JAN-14:09 | 5.00 | -0.4 |
February | 0.435210E+12 | 484377.79 | 27-FEB-10:12 | -0.9 | -1.5 | 0.157348E+10 | 2730.58 | 28-FEB-10:20 | 7.03 | 6.58 |
March | 0.726677E+12 | 522568.92 | 28-MAR-12:32 | 13.70 | 8.53 | 0.187053E+10 | 2743.53 | 27-MAR-13:30 | 13.70 | 8.53 |
April | 0.946177E+12 | 516294.67 | 28-APR-13:57 | 16.10 | 9.86 | 0.163682E+10 | 2909.25 | 07-APR-13:00 | 16.10 | 9.86 |
May | 0.236811E+12 | 395590.43 | 31-MAY-23:55 | 18.50 | 16.73 | 0.215986E+10 | 2860.39 | 15-MAY-13:09 | 18.50 | 16.73 |
June | 0.471377E+12 | 483601.06 | 03-JUN-03:56 | 13.30 | 9.03 | 0.208128E+10 | 2826.13 | 02-JUN-13:00 | 13.30 | 9.03 |
July | 0.730915E+12 | 380283.24 | 01-JUL-22:21 | 19.15 | 18.21 | 0.198595E+10 | 2743.25 | 18-JUL-09:20 | 23.70 | 22.96 |
August | 0.978256E+12 | 476681.91 | 08-AUG-02:46 | 16.10 | 13.43 | 0.223884E+10 | 3061.56 | 25-AUG-13:00 | 26.70 | 15.26 |
September | 0.236984E+12 | 176035.03 | 30-SEP-24:00 | 12.60 | 11.96 | 0.198585E+10 | 2828.00 | 11-SEP-13:09 | 12.60 | 11.96 |
October | 0.494419E+12 | 517570.33 | 31-OCT-23:22 | 11.15 | 10.10 | 0.182137E+10 | 2825.79 | 25-OCT-13:00 | 11.15 | 10.10 |
November | 0.710369E+12 | 524487.66 | 02-NOV-12:22 | 15.30 | 8.11 | 0.168095E+10 | 2733.77 | 03-NOV-13:09 | 17.30 | 10.61 |
December | 0.982263E+12 | 508846.51 | 12-DEC-13:24 | 3.60 | 2.97 | 0.160868E+10 | 2766.68 | 12-DEC-10:39 | 3.60 | 2.97 |
Annual Sum or Average | 0.718308E+13 | 0.227243E+11 | ||||||||
Minimum of Months | 0.233622E+12 | 101901.53 | -0.9 | -1.5 | 0.157348E+10 | 2730.58 | 3.60 | -0.4 | ||
Maximum of Months | 0.982263E+12 | 524487.66 | 19.15 | 18.21 | 0.223884E+10 | 3061.56 | 26.70 | 22.96 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 67338.92 | 504.48 | 20-MAY-16:02 | 23.22 |
June | 1285475.06 | 2247.82 | 24-JUN-16:03 | 24.72 |
July | 34937722.16 | 6440.68 | 15-JUL-16:03 | 27.52 |
August | 31711327.78 | 6793.38 | 12-AUG-16:03 | 27.80 |
September | 269958.93 | 994.60 | 02-SEP-16:03 | 23.80 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.97 |
Annual Sum or Average | 68271822.84 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 34937722.16 | 6793.38 | 27.80 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2115553.67 | 12282.19 | 02-JAN-06:01 | -11.7 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.97 |
Annual Sum or Average | 2115553.67 | |||
Minimum of Months | 0.00 | 0.00 | -11.7 | |
Maximum of Months | 2115553.67 | 12282.19 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.954526E+09 | 70295.92 | 02-JAN-04:01 | -11.8 |
February | 0.137026E+09 | 56574.37 | 06-FEB-05:01 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 5051844.48 | 48527.24 | 24-NOV-06:01 | -4.4 |
December | 1752922.64 | 26293.84 | 26-DEC-06:01 | 6.20 |
Annual Sum or Average | 0.109836E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.954526E+09 | 70295.92 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.698223E+10 | 109589.35 | 02-JAN-04:01 | -11.8 |
February | 0.529959E+10 | 111003.56 | 13-FEB-04:01 | -8.9 |
March | 0.157920E+10 | 99522.70 | 20-MAR-03:11 | -0.2 |
April | 0.306006E+09 | 87837.90 | 03-APR-04:11 | 2.80 |
May | 22887176.49 | 69692.81 | 01-MAY-05:01 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.114075E+09 | 75030.87 | 28-OCT-05:01 | 3.90 |
November | 0.248759E+10 | 110043.97 | 24-NOV-04:01 | -3.4 |
December | 0.331694E+10 | 99297.40 | 11-DEC-04:51 | 1.70 |
Annual Sum or Average | 0.201085E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 0.698223E+10 | 111003.56 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108142E+10 | 19134.39 | 02-JAN-04:01 | -11.8 |
February | 0.101449E+10 | 19106.34 | 06-FEB-04:01 | -13.3 |
March | 96156405.06 | 15157.35 | 22-MAR-05:01 | -2.3 |
April | 965441.29 | 10948.49 | 21-APR-05:01 | 5.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 13147.20 | 219.12 | 28-OCT-05:03 | 3.90 |
November | 66547108.87 | 16167.41 | 24-NOV-05:01 | -4.0 |
December | 0.100853E+09 | 15378.11 | 15-DEC-06:01 | -3.4 |
Annual Sum or Average | 0.236045E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.108142E+10 | 19134.39 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.723832E+09 | 18322.65 | 02-JAN-04:01 | -11.8 |
February | 0.607509E+09 | 18281.61 | 06-FEB-04:01 | -13.3 |
March | 0.101374E+09 | 13330.52 | 17-MAR-04:01 | -1.6 |
April | 7357907.47 | 8630.92 | 21-APR-05:01 | 5.60 |
May | 15716.94 | 104.78 | 04-MAY-05:05 | 10.17 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 350843.56 | 2076.97 | 31-OCT-05:03 | 4.60 |
November | 59621889.77 | 14232.40 | 24-NOV-05:01 | -4.0 |
December | 0.154010E+09 | 12963.45 | 15-DEC-06:01 | -3.4 |
Annual Sum or Average | 0.165407E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.723832E+09 | 18322.65 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123132E+10 | 25036.48 | 02-JAN-04:01 | -11.8 |
February | 0.102689E+10 | 25006.98 | 06-FEB-04:01 | -13.3 |
March | 0.231535E+09 | 19322.30 | 22-MAR-04:01 | -1.8 |
April | 26624212.79 | 14189.14 | 03-APR-05:01 | 2.70 |
May | 78717.44 | 918.37 | 01-MAY-05:01 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 414846.00 | 6273.32 | 28-OCT-05:01 | 3.90 |
November | 0.158870E+09 | 20793.31 | 24-NOV-05:01 | -4.0 |
December | 0.341678E+09 | 19492.73 | 15-DEC-05:01 | -2.9 |
Annual Sum or Average | 0.301741E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.123132E+10 | 25036.48 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267635E+09 | 17561.18 | 02-JAN-04:01 | -11.8 |
February | 0.229483E+09 | 17381.59 | 06-FEB-04:01 | -13.3 |
March | 3121461.12 | 11840.50 | 22-MAR-05:01 | -2.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 3779126.83 | 12541.26 | 24-NOV-06:01 | -4.4 |
December | 5942169.25 | 11888.26 | 15-DEC-06:01 | -3.4 |
Annual Sum or Average | 0.509960E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.267635E+09 | 17561.18 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.588013E+10 | 29929.36 | 02-JAN-00:01 | -10.7 |
February | 0.497779E+10 | 31671.14 | 06-FEB-01:01 | -13.3 |
March | 0.138342E+10 | 25969.25 | 13-MAR-03:01 | 0.50 |
April | 0.349237E+09 | 22731.11 | 03-APR-04:11 | 2.80 |
May | 5256772.59 | 15913.38 | 01-MAY-05:01 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.100770E+09 | 20230.36 | 28-OCT-04:51 | 3.90 |
November | 0.137991E+10 | 28771.26 | 24-NOV-00:21 | -3.3 |
December | 0.289283E+10 | 30390.66 | 31-DEC-21:31 | -7.0 |
Annual Sum or Average | 0.169693E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.588013E+10 | 31671.14 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.327423E+10 | 24162.86 | 02-JAN-04:01 | -11.8 |
February | 0.244542E+10 | 25905.23 | 06-FEB-01:01 | -13.3 |
March | 0.727126E+09 | 19640.73 | 23-MAR-04:01 | -5.0 |
April | 0.192380E+09 | 16755.17 | 03-APR-04:11 | 2.80 |
May | 3054225.55 | 11270.61 | 01-MAY-05:01 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 91701.91 | 504.30 | 29-SEP-05:05 | 11.78 |
October | 51989798.11 | 14767.62 | 28-OCT-04:51 | 3.90 |
November | 0.729270E+09 | 21296.47 | 24-NOV-04:01 | -3.4 |
December | 0.158728E+10 | 24718.41 | 31-DEC-21:31 | -7.0 |
Annual Sum or Average | 0.901085E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.327423E+10 | 25905.23 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388305E+10 | 29125.78 | 02-JAN-00:41 | -11.0 |
February | 0.277584E+10 | 30690.86 | 06-FEB-01:01 | -13.3 |
March | 0.900185E+09 | 24861.49 | 13-MAR-03:41 | 0.10 |
April | 0.277441E+09 | 21438.65 | 03-APR-04:11 | 2.80 |
May | 5398927.58 | 15614.71 | 01-MAY-05:01 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 36490677.51 | 19092.52 | 28-OCT-05:01 | 3.90 |
November | 0.788084E+09 | 26948.51 | 24-NOV-04:01 | -3.4 |
December | 0.179658E+10 | 28953.82 | 31-DEC-22:51 | -7.8 |
Annual Sum or Average | 0.104631E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.388305E+10 | 30690.86 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294547E+10 | 24646.33 | 02-JAN-04:01 | -11.8 |
February | 0.234882E+10 | 26214.13 | 06-FEB-01:01 | -13.3 |
March | 0.574236E+09 | 19960.28 | 23-MAR-04:01 | -5.0 |
April | 0.136169E+09 | 15872.24 | 03-APR-04:11 | 2.80 |
May | 1007763.41 | 3011.62 | 01-MAY-05:01 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 6284.95 | 52.37 | 30-SEP-05:06 | 10.68 |
October | 36035762.71 | 14379.14 | 28-OCT-05:01 | 3.90 |
November | 0.653359E+09 | 21738.07 | 24-NOV-04:01 | -3.4 |
December | 0.134367E+10 | 24887.76 | 31-DEC-22:51 | -7.8 |
Annual Sum or Average | 0.803878E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.294547E+10 | 26214.13 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108655E+11 | 38008.36 | 01-JAN-20:01 | -7.0 |
February | 0.101564E+11 | 40633.31 | 06-FEB-01:41 | -13.3 |
March | 0.405573E+10 | 36340.59 | 23-MAR-03:01 | -4.1 |
April | 0.145830E+10 | 32381.34 | 03-APR-04:11 | 2.80 |
May | 0.154837E+09 | 24887.08 | 01-MAY-04:11 | 6.50 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 25201245.00 | 21068.43 | 30-SEP-05:02 | 10.68 |
October | 0.706039E+09 | 28141.67 | 28-OCT-04:11 | 4.23 |
November | 0.430940E+10 | 38196.84 | 23-NOV-06:11 | -3.9 |
December | 0.787801E+10 | 39913.15 | 31-DEC-21:31 | -7.0 |
Annual Sum or Average | 0.396095E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.108655E+11 | 40633.31 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.629010E+10 | 25822.35 | 31-JAN-04:11 | -7.4 |
February | 0.539491E+10 | 27510.24 | 06-FEB-01:41 | -13.3 |
March | 0.218308E+10 | 24537.64 | 23-MAR-03:01 | -4.1 |
April | 0.812520E+09 | 21914.63 | 03-APR-04:11 | 2.80 |
May | 73679277.50 | 16920.68 | 01-MAY-04:11 | 6.50 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 9352542.53 | 13783.09 | 30-SEP-05:02 | 10.68 |
October | 0.362963E+09 | 18871.63 | 28-OCT-04:11 | 4.23 |
November | 0.233983E+10 | 25920.75 | 23-NOV-06:11 | -3.9 |
December | 0.444815E+10 | 27012.29 | 31-DEC-21:31 | -7.0 |
Annual Sum or Average | 0.219146E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.629010E+10 | 27510.24 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.792999E+10 | 37051.88 | 01-JAN-20:01 | -7.0 |
February | 0.665701E+10 | 39576.76 | 06-FEB-01:41 | -13.3 |
March | 0.293984E+10 | 35116.38 | 13-MAR-02:41 | 0.60 |
April | 0.126359E+10 | 31668.67 | 03-APR-04:11 | 2.80 |
May | 0.160377E+09 | 24462.21 | 01-MAY-04:11 | 6.50 |
June | 49757.22 | 331.71 | 03-JUN-05:03 | 13.48 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 5931764.29 | 13349.23 | 30-SEP-05:02 | 10.68 |
October | 0.426204E+09 | 26844.61 | 28-OCT-04:51 | 3.90 |
November | 0.288295E+10 | 37506.01 | 23-NOV-05:31 | -3.9 |
December | 0.542428E+10 | 38650.97 | 31-DEC-21:31 | -7.0 |
Annual Sum or Average | 0.276902E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.792999E+10 | 39576.76 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.559280E+10 | 27326.12 | 02-JAN-06:01 | -11.7 |
February | 0.477731E+10 | 28975.23 | 06-FEB-01:41 | -13.3 |
March | 0.164411E+10 | 25442.52 | 13-MAR-02:41 | 0.60 |
April | 0.588747E+09 | 22466.13 | 03-APR-04:11 | 2.80 |
May | 56349286.51 | 16299.29 | 01-MAY-04:11 | 6.50 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 3272053.18 | 7262.96 | 30-SEP-05:02 | 10.68 |
October | 0.264868E+09 | 19308.31 | 28-OCT-04:51 | 3.90 |
November | 0.193294E+10 | 27281.25 | 23-NOV-06:11 | -3.9 |
December | 0.346816E+10 | 28105.57 | 31-DEC-21:31 | -7.0 |
Annual Sum or Average | 0.183286E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.559280E+10 | 28975.23 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.748681E+09 | 11805.20 | 18-JAN-06:02 | 7.38 |
February | 0.355913E+09 | 10514.60 | 20-FEB-12:13 | 9.80 |
March | 46169760.64 | 10770.36 | 28-MAR-04:12 | 9.80 |
April | 68749742.51 | 11569.45 | 17-APR-04:12 | 12.43 |
May | 56516906.03 | 8471.96 | 03-MAY-04:12 | 11.70 |
June | 54224297.62 | 10087.54 | 15-JUN-04:11 | 20.93 |
July | 0.123265E+09 | 11364.25 | 24-JUL-04:11 | 20.93 |
August | 0.112507E+09 | 12298.80 | 13-AUG-15:21 | 30.30 |
September | 66589758.15 | 11655.02 | 10-SEP-15:01 | 24.22 |
October | 60610565.73 | 10226.64 | 30-OCT-04:11 | 12.20 |
November | 28146623.79 | 11301.38 | 30-NOV-05:11 | 5.00 |
December | 41398615.64 | 12792.95 | 01-DEC-05:11 | 5.73 |
Annual Sum or Average | 0.176277E+10 | |||
Minimum of Months | 28146623.79 | 8471.96 | 5.00 | |
Maximum of Months | 0.748681E+09 | 12792.95 | 30.30 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.445102E+10 | 26432.77 | 02-JAN-06:12 | -11.7 |
February | 0.237633E+10 | 13607.21 | 06-FEB-06:03 | -12.9 |
March | 0.609091E+09 | 10640.07 | 26-MAR-12:16 | 12.77 |
April | 0.148429E+09 | 9613.27 | 23-APR-12:17 | 14.80 |
May | 46205844.72 | 7429.94 | 29-MAY-08:52 | 26.10 |
June | 34298682.02 | 7429.41 | 12-JUN-04:11 | 18.70 |
July | 58731496.76 | 9615.13 | 09-JUL-14:41 | 27.95 |
August | 44192325.27 | 11477.15 | 13-AUG-15:11 | 30.40 |
September | 52790419.86 | 10983.98 | 10-SEP-15:52 | 23.30 |
October | 43248089.45 | 9180.96 | 09-OCT-14:12 | 13.70 |
November | 0.542043E+09 | 7610.85 | 05-NOV-10:25 | 11.65 |
December | 0.940863E+09 | 10123.69 | 17-DEC-14:32 | 12.20 |
Annual Sum or Average | 0.934724E+10 | |||
Minimum of Months | 34298682.02 | 7429.41 | -12.9 | |
Maximum of Months | 0.445102E+10 | 26432.77 | 30.40 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198631E+11 | 52259.04 | 02-JAN-05:32 | -11.9 |
February | 0.172843E+11 | 60195.91 | 06-FEB-05:12 | -13.1 |
March | 0.807833E+10 | 37948.77 | 13-MAR-04:04 | -0.1 |
April | 0.371350E+10 | 36077.18 | 03-APR-04:21 | 2.80 |
May | 0.711006E+09 | 28217.67 | 31-MAY-05:02 | 16.38 |
June | 0.104197E+09 | 29783.69 | 02-JUN-05:01 | 13.90 |
July | 77861223.53 | 21319.52 | 11-JUL-04:11 | 19.80 |
August | 92542933.39 | 26312.68 | 08-AUG-05:03 | 15.37 |
September | 0.435243E+09 | 24949.48 | 15-SEP-05:03 | 15.92 |
October | 0.231807E+10 | 20090.40 | 28-OCT-05:01 | 3.90 |
November | 0.904328E+10 | 40974.49 | 24-NOV-05:04 | -4.0 |
December | 0.155812E+11 | 35639.37 | 18-DEC-06:12 | 0.60 |
Annual Sum or Average | 0.773027E+11 | |||
Minimum of Months | 77861223.53 | 20090.40 | -13.1 | |
Maximum of Months | 0.198631E+11 | 60195.91 | 19.80 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52382002.43 | 668.11 | 01-JAN-01:20 | -4.4 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.97 |
Annual Sum or Average | 52382002.43 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 52382002.43 | 668.11 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.594960E+09 | 860.78 | 15-JAN-10:05 | 8.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.97 |
Annual Sum or Average | 0.594960E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 0.594960E+09 | 860.78 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122886E+10 | 947.88 | 16-JAN-17:50 | 3.98 |
February | 0.146529E+09 | 735.09 | 27-FEB-04:01 | -0.6 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 |
April | 79946.04 | 70.80 | 30-APR-24:00 | 10.50 |
May | 21843413.28 | 665.78 | 01-MAY-04:53 | 6.10 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 6825569.95 | 748.37 | 24-SEP-09:02 | 15.28 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.97 |
Annual Sum or Average | 0.140414E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.122886E+10 | 947.88 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 |
February | 0.352580E+09 | 12786.73 | 20-FEB-12:11 | 9.80 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 222523.06 | 3708.72 | 31-MAY-23:11 | 18.97 |
June | 69900920.35 | 28129.89 | 05-JUN-01:01 | 15.78 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.344868E+09 | 19574.44 | 22-OCT-22:31 | 15.20 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.97 |
Annual Sum or Average | 0.767571E+09 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.352580E+09 | 28129.89 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.278508E+11 | 29144.79 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.252627E+11 | 29144.79 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.300191E+11 | 29144.79 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.268132E+11 | 29144.79 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.289349E+11 | 29144.79 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.287951E+11 | 29144.79 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.269531E+11 | 29144.79 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.300191E+11 | 29144.79 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.268132E+11 | 29144.79 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.278508E+11 | 29144.79 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.275243E+11 | 29144.79 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.269531E+11 | 29144.79 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.333789E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.252627E+11 | 29144.79 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.300191E+11 | 29144.79 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.785272E+10 | 8217.58 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.712300E+10 | 8217.58 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.846411E+10 | 8217.58 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.756018E+10 | 8217.58 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.815842E+10 | 8217.58 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.811897E+10 | 8217.58 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.759962E+10 | 8217.58 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.846411E+10 | 8217.58 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.756018E+10 | 8217.58 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.785272E+10 | 8217.58 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.776069E+10 | 8217.58 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.759962E+10 | 8217.58 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.941143E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.712300E+10 | 8217.58 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.846411E+10 | 8217.58 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.289349E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.287951E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.275243E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.333789E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140600E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122690E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101989E+10 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 503799.10 | 0.679272E+09 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3009885.00 | 0.384928E+09 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18327159.60 | 0.195299E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44401427.71 | 55749943.24 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53540822.96 | 73790321.89 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6167451.31 | 0.210163E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95292.19 | 0.531094E+09 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102838E+10 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122848E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126046E+09 | 0.803996E+10 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55749943.24 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53540822.96 | 0.140600E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.931759E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823016E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669457E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 375490.37 | 0.442210E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1923560.51 | 0.247681E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15025988.20 | 0.116736E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40659751.94 | 23953167.52 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45306619.89 | 36561598.94 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5043106.45 | 0.134118E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63607.22 | 0.345954E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675439E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.806298E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108398E+09 | 0.525318E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23953167.52 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45306619.89 | 0.931759E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140018E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125629E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101651E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 504613.38 | 0.667498E+09 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2301598.10 | 0.369609E+09 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18901883.90 | 0.182815E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48055214.87 | 47700054.69 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55415611.56 | 68151109.56 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5953732.33 | 0.214571E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95001.00 | 0.551547E+09 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102189E+10 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122894E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131228E+09 | 0.802570E+10 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47700054.69 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55415611.56 | 0.140018E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.977480E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.857021E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727664E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 338522.04 | 0.500104E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2523306.00 | 0.271092E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12462062.53 | 0.149512E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30122447.84 | 51300344.19 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34534086.99 | 63710697.33 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4550679.57 | 0.154145E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72911.23 | 0.379811E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726931E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.880013E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84604016.20 | 0.573878E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51300344.19 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34534086.99 | 0.977480E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297425E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263938E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210967E+10 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1620537.96 | 0.136310E+10 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11725638.12 | 0.784278E+09 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50768682.93 | 0.401302E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116340E+09 | 0.130787E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124990E+09 | 0.175616E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21566476.13 | 0.399878E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 353002.30 | 0.103282E+10 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203216E+10 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250098E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327364E+09 | 0.165442E+11 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130787E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124990E+09 | 0.297425E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198615E+10 |
February | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178172E+10 |
March | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144232E+10 |
April | 0.688021E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 778840.35 | 0.958553E+09 |
May | 0.744847E+09 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3836498.00 | 0.546350E+09 |
June | 0.742030E+09 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31435732.70 | 0.266671E+09 |
July | 0.690839E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73995651.74 | 86007368.19 |
August | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79377780.69 | 0.121982E+09 |
September | 0.688021E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11149674.53 | 0.286893E+09 |
October | 0.715730E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74672.99 | 0.731981E+09 |
November | 0.708685E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139332E+10 |
December | 0.690839E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168155E+10 |
Annual Sum or Average | 0.858171E+10 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200649E+09 | 0.112835E+11 |
Minimum of Months | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86007368.19 |
Maximum of Months | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79377780.69 | 0.198615E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307998E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279892E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224812E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1112415.48 | 0.146451E+10 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5314135.51 | 0.820722E+09 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42492224.35 | 0.407822E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98995146.63 | 0.140771E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108757E+09 | 0.196322E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13277061.11 | 0.476559E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 148136.06 | 0.123365E+10 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220503E+10 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266633E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270096E+09 | 0.177387E+11 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140771E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108757E+09 | 0.307998E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201953E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180340E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148743E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1024288.61 | 0.982419E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6898665.35 | 0.563238E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30822229.74 | 0.302482E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72391616.09 | 0.118307E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78354348.83 | 0.145468E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12175226.48 | 0.297431E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 385426.58 | 0.756015E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139497E+10 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171832E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202052E+09 | 0.115890E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118307E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78354348.83 | 0.201953E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359370E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318412E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242740E+10 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2663023.30 | 0.153554E+10 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15145501.46 | 0.878545E+09 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63396605.17 | 0.458937E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147669E+09 | 0.149594E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161660E+09 | 0.199977E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29739039.17 | 0.431316E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 708958.72 | 0.111145E+10 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228057E+10 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292310E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420982E+09 | 0.191742E+11 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149594E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161660E+09 | 0.359370E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239628E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213537E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164575E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 941438.02 | 0.109172E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4049163.33 | 0.628034E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36065423.84 | 0.318422E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85245655.44 | 0.106194E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95919687.82 | 0.146648E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13090820.57 | 0.324196E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107073.33 | 0.799555E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154787E+10 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195868E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235419E+09 | 0.130987E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106194E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95919687.82 | 0.239628E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366999E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331469E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257158E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1363746.95 | 0.165813E+10 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7490985.46 | 0.926374E+09 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54385350.74 | 0.468867E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128486E+09 | 0.161805E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138517E+09 | 0.224616E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16829738.93 | 0.528450E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 160107.59 | 0.137212E+10 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244126E+10 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306548E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347233E+09 | 0.204034E+11 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161805E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138517E+09 | 0.366999E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242547E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216819E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172792E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1237988.29 | 0.113741E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8090833.36 | 0.656790E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37233868.96 | 0.360959E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87909627.48 | 0.142122E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96709560.51 | 0.172682E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15251355.01 | 0.342542E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 409531.34 | 0.856894E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158558E+10 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200503E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246843E+09 | 0.135816E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142122E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96709560.51 | 0.242547E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.785272E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.712300E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.846411E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.756018E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.815842E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.811897E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.759962E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.846411E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.756018E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.785272E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.776069E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.759962E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.941143E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.712300E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.846411E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315262E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276168E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227076E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 644852.77 | 0.151020E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5244189.89 | 0.843622E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29350277.36 | 0.423231E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74212659.01 | 0.127883E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85364601.21 | 0.175934E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8080377.11 | 0.469349E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15462.33 | 0.119931E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230521E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277744E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202912E+09 | 0.180172E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127883E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85364601.21 | 0.315262E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515274E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465202E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385877E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1292753.02 | 0.254313E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11915952.47 | 0.144916E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56569604.35 | 0.728078E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136491E+09 | 0.226818E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150159E+09 | 0.320358E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15192325.96 | 0.786108E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55171.30 | 0.202905E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382302E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459950E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371676E+09 | 0.301688E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226818E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150159E+09 | 0.515274E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515078E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462307E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378449E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98527.26 | 0.250753E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2342505.34 | 0.150828E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35437712.76 | 0.788174E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94073905.88 | 0.262953E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127039E+09 | 0.310222E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10348829.32 | 0.762259E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189274E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351227E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431336E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269341E+09 | 0.294161E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262953E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127039E+09 | 0.515078E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 29144.79 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 29144.79 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 29144.79 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 29144.79 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 29144.79 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 29144.79 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 29144.79 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 29144.79 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 29144.79 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 29144.79 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 29144.79 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 29144.79 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2360.99 | 31-JAN-00:53 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2310.23 | 05-FEB-07:51 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1859.48 | 12-MAR-10:00 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.53 | 07-APR-13:00 | 1452.73 | 11-APR-03:53 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.76 | 29-MAY-12:00 | 863.71 | 03-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.41 | 19-JUN-21:02 | 493.26 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.25 | 09-JUL-13:50 | 203.59 | 02-JUL-19:00 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.14 | 12-AUG-18:52 | 332.92 | 20-AUG-06:00 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.01 | 14-SEP-14:00 | 441.59 | 17-SEP-10:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.54 | 25-OCT-11:00 | 1242.97 | 08-OCT-08:00 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1956.00 | 23-NOV-01:51 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 2487.53 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.59 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 290.14 | 2487.53 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1563.26 | 31-JAN-00:53 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1720.48 | 05-FEB-08:50 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1431.35 | 12-MAR-09:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.69 | 07-APR-13:00 | 939.82 | 11-APR-03:53 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.53 | 29-MAY-12:00 | 562.66 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.17 | 25-JUN-18:53 | 312.13 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.02 | 09-JUL-13:50 | 117.18 | 11-JUL-04:50 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.45 | 12-AUG-18:52 | 221.76 | 20-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.34 | 14-SEP-14:00 | 310.95 | 10-SEP-08:20 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 25-OCT-11:00 | 971.79 | 08-OCT-08:30 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1289.98 | 23-NOV-01:51 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1644.51 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.18 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 234.45 | 1720.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2361.77 | 31-JAN-00:53 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2463.12 | 05-FEB-12:00 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2043.13 | 12-MAR-10:00 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.47 | 07-APR-13:00 | 1422.32 | 11-APR-03:53 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.90 | 29-MAY-11:58 | 839.18 | 03-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.78 | 25-JUN-18:53 | 479.96 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.38 | 09-JUL-13:46 | 188.99 | 02-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.04 | 12-AUG-18:52 | 320.14 | 20-AUG-06:00 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.92 | 14-SEP-14:00 | 432.14 | 30-SEP-24:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.53 | 25-OCT-11:00 | 1312.80 | 08-OCT-10:00 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1928.22 | 23-NOV-01:51 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 2460.04 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.99 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 314.04 | 2463.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1636.95 | 31-JAN-00:53 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1606.22 | 05-FEB-07:51 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1351.28 | 12-MAR-10:00 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.69 | 07-APR-13:00 | 1083.23 | 11-APR-03:53 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.56 | 29-MAY-12:00 | 629.99 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.94 | 19-JUN-21:02 | 395.86 | 03-JUN-17:40 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.92 | 09-JUL-13:46 | 242.36 | 02-JUL-17:40 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.39 | 12-AUG-19:10 | 274.07 | 20-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.59 | 04-SEP-12:20 | 324.31 | 17-SEP-12:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.03 | 25-OCT-11:00 | 877.30 | 08-OCT-08:00 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1380.51 | 23-NOV-01:51 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1800.20 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.36 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 188.39 | 1800.20 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5211.72 | 14-JAN-05:59 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 5334.68 | 06-FEB-00:44 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 4100.16 | 21-MAR-21:01 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.01 | 16-APR-17:10 | 2863.09 | 11-APR-03:53 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 499.91 | 29-MAY-12:20 | 1697.93 | 03-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 540.09 | 25-JUN-18:53 | 1044.35 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 585.50 | 09-JUL-14:10 | 461.68 | 11-JUL-04:55 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 654.73 | 04-AUG-21:02 | 669.88 | 20-AUG-06:00 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.94 | 04-SEP-14:00 | 885.24 | 23-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.37 | 25-OCT-11:00 | 2378.47 | 17-OCT-23:51 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 4012.41 | 22-NOV-22:01 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 5347.31 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.68 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 654.73 | 5347.31 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3474.44 | 14-JAN-05:56 |
February | 1239.33 | 01-FEB-08:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3556.40 | 06-FEB-00:50 |
March | 1239.33 | 01-MAR-08:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2765.76 | 12-MAR-09:51 |
April | 1239.33 | 03-APR-07:10 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.89 | 07-APR-17:00 | 1905.90 | 11-APR-03:53 |
May | 1239.33 | 01-MAY-07:10 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.04 | 29-MAY-12:20 | 1134.07 | 03-MAY-04:00 |
June | 1239.33 | 01-JUN-07:10 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 417.90 | 25-JUN-18:53 | 675.21 | 02-JUN-22:00 |
July | 1239.33 | 03-JUL-07:10 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.33 | 09-JUL-14:10 | 306.18 | 11-JUL-04:55 |
August | 1239.33 | 01-AUG-07:10 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 466.28 | 04-AUG-21:02 | 480.29 | 20-AUG-06:00 |
September | 1239.33 | 01-SEP-07:10 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.02 | 04-SEP-16:00 | 715.20 | 10-SEP-07:50 |
October | 1239.33 | 02-OCT-07:10 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.86 | 25-OCT-11:00 | 1914.76 | 08-OCT-08:30 |
November | 1239.33 | 01-NOV-07:10 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 2675.94 | 22-NOV-22:01 |
December | 1239.33 | 01-DEC-08:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 3564.85 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.18 | |||||
Maximum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 466.28 | 3564.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5211.70 | 14-JAN-05:56 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 5334.68 | 06-FEB-00:49 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 4148.09 | 12-MAR-10:00 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.32 | 07-APR-13:00 | 2948.94 | 11-APR-03:53 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.32 | 29-MAY-12:15 | 1749.28 | 03-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 527.68 | 25-JUN-18:53 | 1040.87 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 434.64 | 09-JUL-14:05 | 456.35 | 23-JUL-17:55 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 637.56 | 04-AUG-21:02 | 684.96 | 20-AUG-06:00 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.44 | 14-SEP-14:00 | 969.89 | 30-SEP-24:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 25-OCT-11:00 | 2822.76 | 08-OCT-10:00 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 4046.69 | 23-NOV-01:51 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 5347.34 | 31-DEC-21:54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.35 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 637.56 | 5347.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3474.51 | 14-JAN-05:55 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3556.45 | 06-FEB-00:42 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2742.47 | 21-MAR-21:01 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 | 08-APR-09:55 | 1999.00 | 11-APR-03:53 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 380.66 | 29-MAY-12:20 | 1206.21 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 317.03 | 19-JUN-21:02 | 917.96 | 03-JUN-17:40 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.98 | 09-JUL-13:30 | 551.25 | 02-JUL-17:40 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 439.86 | 04-AUG-21:02 | 493.45 | 20-AUG-05:51 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.87 | 04-SEP-12:00 | 650.32 | 10-SEP-20:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.24 | 25-OCT-11:00 | 1659.94 | 17-OCT-21:51 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 2676.97 | 22-NOV-22:01 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 3564.93 | 31-DEC-21:59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.45 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 439.86 | 3564.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6496.10 | 14-JAN-06:00 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 6648.68 | 06-FEB-00:46 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 5100.20 | 21-MAR-21:01 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.53 | 16-APR-17:00 | 3444.97 | 11-APR-04:14 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 619.97 | 29-MAY-11:50 | 1815.40 | 03-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 680.15 | 25-JUN-18:53 | 1192.54 | 02-JUN-21:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 745.88 | 09-JUL-13:40 | 535.71 | 11-JUL-05:00 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 983.44 | 12-AUG-19:00 | 720.00 | 06-AUG-22:51 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.95 | 04-SEP-14:10 | 952.58 | 23-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.50 | 25-OCT-11:00 | 2673.24 | 17-OCT-21:51 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 4982.74 | 22-NOV-22:01 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 6671.08 | 31-DEC-21:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 535.71 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 983.44 | 6671.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4330.62 | 14-JAN-05:57 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 4432.50 | 06-FEB-00:42 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 3401.53 | 21-MAR-21:01 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.70 | 07-APR-13:00 | 2296.48 | 11-APR-04:14 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.30 | 29-MAY-12:27 | 1244.61 | 14-MAY-13:52 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 466.88 | 25-JUN-18:53 | 788.91 | 02-JUN-21:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 433.61 | 09-JUL-13:40 | 369.20 | 11-JUL-05:00 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 659.54 | 12-AUG-19:00 | 519.96 | 20-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.56 | 14-SEP-14:00 | 869.33 | 10-SEP-08:10 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.56 | 25-OCT-11:00 | 1900.68 | 08-OCT-08:30 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 3322.70 | 22-NOV-22:01 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 4447.41 | 31-DEC-21:56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.20 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 659.54 | 4447.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6496.45 | 14-JAN-05:56 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 6648.71 | 06-FEB-00:47 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 5111.48 | 21-MAR-21:01 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.04 | 07-APR-13:00 | 3435.07 | 11-APR-04:14 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 317.44 | 29-MAY-11:50 | 2019.44 | 14-MAY-13:52 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 675.29 | 25-JUN-18:53 | 1193.64 | 02-JUN-21:51 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 582.27 | 09-JUL-13:35 | 579.62 | 23-JUL-15:00 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 956.09 | 12-AUG-19:00 | 735.16 | 20-AUG-05:51 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.83 | 14-SEP-14:00 | 1076.16 | 10-SEP-20:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.84 | 25-OCT-11:00 | 2900.16 | 17-OCT-21:51 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 4993.69 | 22-NOV-22:01 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 6671.06 | 31-DEC-21:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.62 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 956.09 | 6671.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4330.95 | 14-JAN-05:57 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 4432.46 | 06-FEB-00:47 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 3410.70 | 21-MAR-21:01 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.61 | 08-APR-09:55 | 2285.66 | 11-APR-04:16 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 455.05 | 29-MAY-11:50 | 1356.57 | 14-MAY-13:57 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 389.43 | 19-JUN-21:02 | 1146.71 | 03-JUN-17:40 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 432.07 | 09-JUL-13:40 | 727.24 | 02-JUL-17:20 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 616.93 | 12-AUG-19:00 | 540.56 | 20-AUG-05:51 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.72 | 04-SEP-12:10 | 806.69 | 10-SEP-20:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.73 | 25-OCT-11:00 | 1914.63 | 17-OCT-21:51 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 3325.78 | 22-NOV-22:01 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 4447.39 | 31-DEC-21:54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 540.56 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 616.93 | 4447.39 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 8217.58 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 8217.58 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 8217.58 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 8217.58 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 8217.58 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 8217.58 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 8217.58 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 8217.58 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 8217.58 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 8217.58 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 8217.58 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 8217.58 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 8217.58 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 8217.58 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5449.36 | 31-JAN-00:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 5393.39 | 06-FEB-00:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 4006.11 | 12-MAR-10:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.76 | 07-APR-13:00 | 3308.03 | 11-APR-03:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.32 | 29-MAY-12:00 | 1951.29 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.26 | 19-JUN-21:02 | 1065.40 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.24 | 09-JUL-14:00 | 453.84 | 11-JUL-04:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 559.29 | 12-AUG-18:52 | 707.87 | 20-AUG-05:51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.36 | 14-SEP-14:00 | 964.29 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 | 25-OCT-11:00 | 2817.88 | 08-OCT-08:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 4532.32 | 23-NOV-01:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 5783.50 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.84 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 559.29 | 5783.50 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 9229.71 | 31-JAN-00:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 8843.97 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 6760.61 | 21-MAR-21:01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.74 | 07-APR-13:00 | 5632.37 | 11-APR-03:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 581.19 | 29-MAY-12:00 | 3311.77 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 615.41 | 25-JUN-19:00 | 1871.25 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 839.25 | 09-JUL-13:51 | 815.04 | 11-JUL-04:57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 965.76 | 12-AUG-18:52 | 1233.62 | 20-AUG-05:51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.92 | 14-SEP-14:00 | 1664.54 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 25-OCT-11:00 | 4756.11 | 08-OCT-07:51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 7679.16 | 23-NOV-01:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 9080.89 | 31-DEC-21:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 815.04 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 965.76 | 9229.71 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 8880.14 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 8669.77 | 06-FEB-00:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 7285.22 | 21-MAR-21:01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.94 | 08-APR-09:55 | 4924.30 | 11-APR-03:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.10 | 29-MAY-11:50 | 3344.03 | 14-MAY-13:57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 723.05 | 19-JUN-21:02 | 1819.63 | 03-JUN-17:04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 733.12 | 07-JUL-21:52 | 970.17 | 02-JUL-18:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1111.71 | 12-AUG-19:00 | 1070.85 | 06-AUG-22:51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.66 | 14-SEP-14:00 | 1503.06 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4196.09 | 17-OCT-21:51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 7176.28 | 23-NOV-01:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 8654.86 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 970.17 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1111.71 | 8880.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 102562.46 | 30-JAN-05:59 | 0.00 | 29144.79 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 119321.27 | 21-FEB-05:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 115213.59 | 01-MAR-06:01 | 17952.25 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 99142.80 | 11-APR-04:11 | 0.00 | 22668.17 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 109119.93 | 30-MAY-04:12 | 0.00 | 19429.86 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 113457.40 | 03-JUN-04:12 | 0.00 | 8095.77 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 96805.72 | 11-JUL-04:53 | 0.00 | 12953.24 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 104128.76 | 21-AUG-04:22 | 0.00 | 19429.86 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 111718.01 | 25-SEP-04:11 | 0.00 | 22668.17 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 127911.00 | 09-OCT-05:57 | 8976.13 | 16191.55 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 108140.06 | 06-NOV-04:57 | 0.00 | 16191.55 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 103345.52 | 26-DEC-05:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 96805.72 | 0.00 | 8095.77 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 127911.00 | 17952.25 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 102525.15 | 20-JAN-06:01 | 12897.91 | 23265.84 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 103884.96 | 23-FEB-06:01 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 108615.57 | 27-MAR-05:01 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 113646.60 | 11-APR-04:11 | 0.00 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 115922.32 | 30-MAY-04:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 115983.19 | 01-JUN-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 96460.44 | 14-JUL-05:02 | 8061.19 | 14541.15 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 111224.60 | 26-AUG-04:11 | 0.00 | 13087.03 | 40079.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 116122.13 | 18-SEP-04:11 | 0.00 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 118997.16 | 23-OCT-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 117745.80 | 13-NOV-05:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 106712.87 | 20-DEC-05:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 96460.44 | 0.00 | 13087.03 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 118997.16 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 32195.68 | 27-JAN-16:53 | 61265.06 | 104696.28 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33633.40 | 24-FEB-16:52 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 93812.23 | 04-MAR-06:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 95812.15 | 27-APR-05:03 | 6448.95 | 11632.92 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 104084.71 | 31-MAY-04:12 | 0.00 | 17449.38 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 106983.39 | 01-JUN-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 94932.38 | 11-JUL-04:11 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 104067.51 | 26-AUG-04:11 | 0.00 | 13087.03 | 40078.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 104908.60 | 15-SEP-04:12 | 0.00 | 17449.38 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 103875.35 | 05-OCT-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 97923.56 | 04-NOV-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 34468.74 | 21-DEC-16:25 | 61265.06 | 104696.28 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 32195.68 | 0.00 | 11632.92 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 106983.39 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 23373.76 | 19-JAN-16:57 | 45948.79 | 78522.21 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23926.07 | 17-FEB-17:00 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 38316.19 | 03-MAR-16:11 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 53622.93 | 07-APR-15:40 | 30632.53 | 52348.14 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 106706.35 | 30-MAY-05:02 | 8061.19 | 14541.15 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 115446.65 | 12-JUN-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 109429.56 | 14-JUL-05:02 | 8061.19 | 14541.15 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 115246.83 | 01-AUG-04:01 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 106738.94 | 02-SEP-04:11 | 0.00 | 10178.80 | 31172.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 100833.11 | 06-OCT-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35621.24 | 03-NOV-15:55 | 61265.06 | 104696.28 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22717.51 | 20-DEC-17:00 | 45948.79 | 78522.21 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 22717.51 | 0.00 | 10178.80 | 31172.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 115446.65 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3778.29 | 24-JAN-06:02 | 1012.16 | 1825.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.86 |
February | 4521.49 | 20-FEB-12:51 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.79 |
March | 6663.27 | 27-MAR-15:50 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.05 |
April | 9255.22 | 07-APR-13:50 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 27.32 | 0.00 |
May | 11600.90 | 30-MAY-13:30 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 49.21 | 0.00 |
June | 14586.85 | 22-JUN-05:02 | 1214.60 | 2190.94 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.11 |
July | 16771.19 | 14-JUL-05:02 | 1012.16 | 1825.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.61 |
August | 16324.86 | 02-AUG-05:02 | 1012.16 | 1825.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 | 0.00 |
September | 15605.82 | 05-SEP-04:11 | 0.00 | 2556.10 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.21 |
October | 8833.70 | 04-OCT-13:20 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 | 0.00 |
November | 5816.52 | 03-NOV-13:51 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.76 |
December | 4243.10 | 17-DEC-11:22 | 506.08 | 912.89 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3778.29 | 0.00 | 912.89 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16771.19 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 49.21 | 394.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4866.08 | 19-JAN-09:50 | 2478.65 | 4235.78 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.65 |
February | 5728.31 | 20-FEB-12:51 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.11 |
March | 14407.50 | 26-MAR-08:27 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.30 |
April | 28938.91 | 23-APR-09:01 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.65 |
May | 28512.60 | 29-MAY-08:32 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.07 |
June | 29054.62 | 04-JUN-09:02 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.16 |
July | 28809.73 | 02-JUL-08:22 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.34 |
August | 28417.29 | 27-AUG-09:42 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.34 |
September | 31048.08 | 10-SEP-09:01 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.79 |
October | 27365.05 | 15-OCT-09:11 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.64 |
November | 7119.30 | 02-NOV-08:41 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
December | 5813.79 | 17-DEC-11:22 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4866.08 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.07 | |
Maximum of Months | 31048.08 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18040.99 | 17-JAN-13:07 | 5769.46 | 9859.46 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.87 |
February | 32790.74 | 20-FEB-13:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 595.87 |
March | 32164.61 | 26-MAR-12:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.78 |
April | 20846.95 | 07-APR-12:30 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 23.56 | 0.00 |
May | 21409.42 | 21-MAY-13:02 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.01 |
June | 18718.27 | 19-JUN-12:40 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 109.91 | 0.00 |
July | 27985.01 | 09-JUL-14:22 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 108.75 | 0.00 |
August | 34900.12 | 27-AUG-11:42 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 11.81 | 0.00 |
September | 37174.16 | 03-SEP-12:01 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.46 |
October | 35277.67 | 22-OCT-12:52 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23830.14 | 02-NOV-12:31 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.40 |
December | 33433.44 | 03-DEC-12:52 | 506.09 | 912.91 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18040.99 | 506.09 | 912.91 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37174.16 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 109.91 | 595.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7541.63 | 17-JAN-15:30 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.47 |
February | 12100.42 | 20-FEB-15:36 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.01 |
March | 33240.78 | 26-MAR-16:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.22 |
April | 34891.79 | 23-APR-16:01 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.96 |
May | 34166.68 | 21-MAY-15:01 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.27 |
June | 36079.73 | 03-JUN-17:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.31 |
July | 35985.17 | 02-JUL-16:21 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.52 |
August | 35668.57 | 13-AUG-16:01 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 40.22 | 0.00 |
September | 38512.01 | 10-SEP-16:21 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.61 |
October | 31420.97 | 15-OCT-15:51 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.33 |
November | 10893.71 | 03-NOV-15:21 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.96 |
December | 8557.81 | 08-DEC-15:23 | 3717.98 | 6353.67 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7541.63 | 456.59 | 823.62 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38512.01 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 40.22 | 582.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3888.77 | 20-JAN-14:50 | 8043.16 | 13145.66 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.42 |
February | 4302.49 | 20-FEB-13:01 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 720.60 |
March | 5452.82 | 27-MAR-16:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.72 |
April | 7577.37 | 09-APR-16:01 | 708.51 | 1278.05 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.73 |
May | 10776.68 | 30-MAY-14:00 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 100.65 | 0.00 |
June | 13506.73 | 19-JUN-14:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 203.17 | 0.00 |
July | 17187.62 | 18-JUL-05:02 | 1214.60 | 2190.94 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 | 0.00 |
August | 16168.97 | 05-AUG-05:02 | 1012.16 | 1825.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 16.82 | 0.00 |
September | 10837.05 | 02-SEP-05:03 | 809.73 | 1460.63 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.51 |
October | 7739.54 | 04-OCT-14:05 | 3846.22 | 6572.83 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.30 | 0.00 |
November | 6020.56 | 02-NOV-13:10 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.85 |
December | 4160.49 | 17-DEC-13:12 | 607.30 | 1095.47 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3888.77 | 607.30 | 1095.47 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17187.62 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 203.17 | 720.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6647.43 | 26-JAN-11:02 | 6196.63 | 10589.46 | 6961.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.86 |
February | 12679.16 | 17-FEB-11:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.42 |
March | 18903.91 | 29-MAR-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.93 |
April | 28973.69 | 23-APR-09:01 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 810.45 |
May | 34299.95 | 29-MAY-08:51 | 587.05 | 1058.95 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.73 |
June | 29487.05 | 25-JUN-08:42 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.58 |
July | 34623.16 | 09-JUL-09:21 | 587.05 | 1058.95 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 |
August | 31869.70 | 13-AUG-08:31 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.73 |
September | 33370.80 | 04-SEP-09:11 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.04 |
October | 20436.67 | 05-OCT-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.33 |
November | 15498.63 | 02-NOV-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.68 |
December | 6841.28 | 20-DEC-11:02 | 6196.63 | 10589.46 | 6961.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6647.43 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | |
Maximum of Months | 34623.16 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 810.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17947.41 | 19-JAN-13:30 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 564.19 |
February | 32472.76 | 20-FEB-13:41 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1432.25 |
March | 23913.84 | 01-MAR-13:02 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.22 |
April | 20840.43 | 07-APR-12:30 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 52.44 | 0.00 |
May | 33978.15 | 29-MAY-12:52 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.58 |
June | 18566.04 | 19-JUN-13:10 | 4021.67 | 6572.98 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 236.64 | 0.00 |
July | 34497.12 | 30-JUL-13:21 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.73 |
August | 35360.19 | 27-AUG-12:32 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.65 |
September | 39141.99 | 04-SEP-13:11 | 910.97 | 1643.24 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.95 |
October | 37272.92 | 22-OCT-12:21 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.03 |
November | 25430.71 | 02-NOV-12:41 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.44 |
December | 35197.48 | 17-DEC-13:12 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1145.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17947.41 | 607.31 | 1095.50 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39141.99 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 236.64 | 1432.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5239.06 | 31-JAN-16:00 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6653.05 | 22-FEB-16:13 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.14 |
March | 12234.66 | 26-MAR-16:44 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 777.91 |
April | 32964.26 | 09-APR-16:41 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.19 |
May | 23047.37 | 27-MAY-17:04 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.96 |
June | 33047.62 | 03-JUN-17:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 789.48 |
July | 32868.68 | 02-JUL-16:21 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.89 |
August | 35574.81 | 13-AUG-15:51 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 0.00 |
September | 32948.27 | 04-SEP-16:31 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.43 |
October | 14961.19 | 04-OCT-15:30 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.40 |
November | 8120.90 | 03-NOV-15:21 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.24 |
December | 5680.33 | 17-DEC-13:52 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 565.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5239.06 | 391.37 | 705.96 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35574.81 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 789.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5234.32 | 21-JAN-06:04 | 1619.46 | 2921.26 | 7681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.56 |
February | 5122.51 | 18-FEB-06:04 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.24 |
March | 6450.72 | 27-MAR-16:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.70 |
April | 8571.30 | 07-APR-15:20 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 47.69 | 0.00 |
May | 12602.47 | 30-MAY-14:00 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 122.39 | 0.00 |
June | 15640.01 | 19-JUN-14:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 249.42 | 0.00 |
July | 30703.88 | 09-JUL-14:11 | 809.73 | 1460.63 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 391.06 | 0.00 |
August | 36622.26 | 13-AUG-15:11 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 264.81 | 0.00 |
September | 12044.53 | 01-SEP-14:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 172.13 | 0.00 |
October | 8195.82 | 15-OCT-11:51 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.43 |
November | 6000.32 | 03-NOV-14:31 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.14 |
December | 5015.22 | 29-DEC-06:04 | 1417.03 | 2556.10 | 6721.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5015.22 | 809.73 | 1460.63 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36622.26 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 391.06 | 291.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3961.47 | 19-JAN-10:20 | 5183.32 | 8471.56 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.78 |
February | 4144.42 | 22-FEB-10:10 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.78 |
March | 7272.90 | 29-MAR-09:41 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.37 |
April | 12601.87 | 07-APR-09:40 | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.24 |
May | 34056.72 | 29-MAY-08:21 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.40 |
June | 30572.53 | 04-JUN-10:32 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.08 |
July | 32391.48 | 09-JUL-09:31 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 63.35 | 0.00 |
August | 32726.39 | 13-AUG-08:31 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.97 |
September | 34092.67 | 04-SEP-09:21 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.11 |
October | 11365.19 | 15-OCT-09:12 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 934.22 |
November | 4767.53 | 02-NOV-09:50 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.19 |
December | 3889.75 | 20-DEC-10:00 | 3717.98 | 6353.67 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3889.75 | 391.37 | 705.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34092.67 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 63.35 | 934.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17830.13 | 17-JAN-13:30 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.55 |
February | 18217.27 | 22-FEB-13:31 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.35 |
March | 23924.42 | 01-MAR-13:22 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.42 |
April | 21832.22 | 07-APR-12:40 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 67.45 | 0.00 |
May | 43123.65 | 29-MAY-13:41 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.74 |
June | 20731.79 | 19-JUN-13:10 | 4021.67 | 6572.98 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 290.84 | 0.00 |
July | 44670.31 | 09-JUL-14:11 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 216.22 | 0.00 |
August | 45189.99 | 20-AUG-13:41 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 33.33 | 0.00 |
September | 47463.41 | 04-SEP-11:21 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.68 |
October | 43604.11 | 15-OCT-11:51 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.90 |
November | 24463.78 | 02-NOV-13:01 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.99 |
December | 16347.73 | 15-DEC-13:13 | 5769.46 | 9859.46 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 828.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16347.73 | 708.53 | 1278.08 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47463.41 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 290.84 | 1072.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5532.65 | 17-JAN-15:50 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.87 |
February | 6187.36 | 22-FEB-16:11 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.73 |
March | 12318.31 | 15-MAR-15:52 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.11 |
April | 30691.06 | 09-APR-16:11 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543.36 |
May | 34000.66 | 14-MAY-15:51 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 928.79 |
June | 36162.42 | 04-JUN-15:51 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.24 |
July | 37351.59 | 09-JUL-15:31 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.75 |
August | 38467.30 | 13-AUG-15:51 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 |
September | 38709.68 | 10-SEP-16:11 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.79 |
October | 15601.10 | 04-OCT-15:30 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.75 |
November | 7828.51 | 03-NOV-15:21 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.65 |
December | 5205.87 | 08-DEC-15:40 | 8675.28 | 14825.24 | 9746.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5205.87 | 456.59 | 823.62 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 | |
Maximum of Months | 38709.68 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 928.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10654.73 | 14-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4032.74 |
February | 12306.85 | 06-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3972.44 |
March | 8451.72 | 22-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 806.24 |
April | 9182.77 | 08-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.50 |
May | 9916.77 | 30-MAY-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.62 | 0.00 |
June | 10490.44 | 27-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.90 |
July | 12497.05 | 10-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 0.00 |
August | 12624.67 | 21-AUG-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.82 |
September | 13331.36 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.16 |
October | 9257.72 | 06-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.54 |
November | 8569.64 | 20-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.35 |
December | 8760.35 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 702.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8451.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13331.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.62 | 4032.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16614.59 | 30-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1486.27 |
February | 17952.29 | 12-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7052.40 |
March | 16248.95 | 13-MAR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4909.90 |
April | 13578.10 | 21-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4482.67 |
May | 8944.73 | 11-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.02 |
June | 10294.25 | 24-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.76 |
July | 10582.54 | 25-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.05 |
August | 10883.02 | 07-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.98 |
September | 10677.74 | 02-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.50 |
October | 9961.88 | 28-OCT-04:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2436.26 |
November | 15700.17 | 20-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2236.07 |
December | 16049.98 | 23-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3762.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8944.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.05 | |
Maximum of Months | 17952.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7052.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3808.47 | 19-JAN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 986.41 |
February | 6467.78 | 17-FEB-13:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.44 |
March | 14918.53 | 03-MAR-14:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 732.64 |
April | 27405.90 | 07-APR-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 |
May | 36161.94 | 30-MAY-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.62 | 0.00 |
June | 41039.08 | 19-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.00 | 0.00 |
July | 38160.28 | 07-JUL-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.72 | 0.00 |
August | 37399.53 | 18-AUG-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.58 | 0.00 |
September | 32862.53 | 01-SEP-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.42 | 0.00 |
October | 23129.32 | 04-OCT-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.59 |
November | 10005.39 | 04-NOV-12:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.87 |
December | 4573.93 | 17-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1005.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3808.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41039.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.58 | 1005.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2272.67 | 20-JAN-16:23 | 666.42 | 2186.35 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4320.03 | 14-FEB-16:51 | 2221.41 | 7287.84 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6660.37 | 31-MAR-23:53 | 0.00 | 242.93 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8128.23 | 09-APR-17:24 | 0.00 | 202.44 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3498.55 | 31-MAY-23:52 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5311.93 | 30-JUN-24:00 | 0.00 | 40.49 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7248.56 | 31-JUL-23:42 | 0.00 | 202.44 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8445.22 | 31-AUG-17:30 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3301.40 | 30-SEP-23:50 | 0.00 | 40.49 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4939.86 | 31-OCT-23:52 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6148.34 | 03-NOV-15:55 | 888.56 | 2915.14 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7977.33 | 08-DEC-16:07 | 666.42 | 2186.35 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2272.67 | 0.00 | 40.49 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8445.22 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1957.67 | 20-JAN-16:23 | 666.42 | 2186.35 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4028.41 | 22-FEB-16:51 | 2221.41 | 7287.84 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5989.95 | 31-MAR-23:22 | 0.00 | 242.93 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7724.70 | 12-APR-17:35 | 233.83 | 2429.28 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3302.83 | 31-MAY-23:52 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4971.00 | 30-JUN-24:00 | 0.00 | 40.49 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6939.73 | 31-JUL-24:00 | 0.00 | 80.98 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8112.83 | 31-AUG-17:30 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2913.84 | 30-SEP-23:20 | 0.00 | 40.49 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4309.61 | 31-OCT-23:32 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5830.81 | 03-NOV-15:55 | 888.56 | 2915.14 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7451.56 | 08-DEC-16:03 | 666.42 | 2186.35 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1957.67 | 0.00 | 40.49 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8112.83 | 2221.41 | 7287.84 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1838.45 | 19-JAN-16:23 | 888.56 | 2915.14 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3920.41 | 22-FEB-16:51 | 2221.41 | 7287.84 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5951.96 | 29-MAR-17:12 | 93.53 | 971.71 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7815.87 | 07-APR-16:00 | 222.14 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3165.18 | 31-MAY-23:42 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4780.99 | 30-JUN-24:00 | 0.00 | 40.49 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6893.63 | 31-JUL-24:00 | 0.00 | 80.98 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8219.23 | 31-AUG-17:20 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2703.90 | 06-SEP-17:20 | 23.38 | 242.93 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4353.46 | 04-OCT-16:00 | 222.14 | 728.78 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5796.59 | 03-NOV-15:55 | 888.56 | 2915.14 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7228.30 | 08-DEC-16:03 | 666.42 | 2186.35 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1838.45 | 0.00 | 40.49 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8219.23 | 2221.41 | 7287.84 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 101901.53 | 20-JAN-05:11 | 0.00 | 9130.65 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 484377.79 | 27-FEB-10:12 | 50279.21 | 82175.84 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 522568.92 | 28-MAR-12:32 | 48086.79 | 82175.84 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 516294.67 | 28-APR-13:57 | 50279.21 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 395590.43 | 31-MAY-23:55 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 483601.06 | 03-JUN-03:56 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 380283.24 | 01-JUL-22:21 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 476681.91 | 08-AUG-02:46 | 0.00 | 4565.32 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176035.03 | 30-SEP-24:00 | 0.00 | 456.53 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 517570.33 | 31-OCT-23:22 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 524487.66 | 02-NOV-12:22 | 48086.79 | 82175.84 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 508846.51 | 12-DEC-13:24 | 48086.79 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 101901.53 | 0.00 | 456.53 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 524487.66 | 50279.21 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.191993E+13 | 1503357.62 | 19-JAN-16:00 | 0.997766E+12 | 3138528.82 | 02-JAN-06:19 |
February | 0.212631E+13 | 1684315.76 | 02-FEB-15:09 | 0.826038E+12 | 2646650.28 | 06-FEB-05:10 |
March | 0.288022E+13 | 1904744.41 | 15-MAR-15:20 | 0.321069E+12 | 1261872.80 | 13-MAR-05:10 |
April | 0.308625E+13 | 2267564.56 | 07-APR-15:39 | 0.124948E+12 | 912637.27 | 21-APR-04:19 |
May | 0.213639E+13 | 1903002.53 | 30-MAY-15:20 | 0.167800E+11 | 627808.46 | 01-MAY-05:10 |
June | 0.270280E+13 | 2132752.43 | 19-JUN-14:09 | 0.292952E+09 | 21170.83 | 03-JUN-05:10 |
July | 0.328177E+13 | 2291811.50 | 20-JUL-14:30 | 592135.18 | 735.53 | 04-JUL-17:49 |
August | 0.377363E+13 | 2481535.09 | 02-AUG-15:09 | 72131025.90 | 5770.55 | 08-AUG-14:00 |
September | 0.213997E+13 | 1954294.81 | 07-SEP-15:20 | 0.695380E+10 | 195319.09 | 30-SEP-05:10 |
October | 0.251826E+13 | 2009385.04 | 03-OCT-15:30 | 0.512415E+11 | 611438.09 | 31-OCT-05:10 |
November | 0.272975E+13 | 1902258.72 | 03-NOV-14:09 | 0.302439E+12 | 1602790.79 | 24-NOV-05:10 |
December | 0.319234E+13 | 2028654.90 | 19-DEC-16:40 | 0.542455E+12 | 1256274.46 | 15-DEC-06:10 |
Annual Sum or Average | 0.324876E+14 | 0.319006E+13 | ||||
Minimum of Months | 0.191993E+13 | 1503357.62 | 592135.18 | 735.53 | ||
Maximum of Months | 0.377363E+13 | 2481535.09 | 0.997766E+12 | 3138528.82 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.468149E+12 | 0.104122E+12 | 0.766053E+12 | 0.218140E+12 | 0.170995E+12 | 0.380141E+11 | 0.00 | 0.236097E+11 | 8231098.93 | 0.906243E+11 | 0.00 | 0.402196E+11 | 0.00 |
February | 0.424646E+12 | 0.873192E+11 | 0.978954E+12 | 0.199667E+12 | 0.171708E+12 | 0.449771E+11 | 0.00 | 0.660818E+11 | 4776730.73 | 0.116047E+12 | 0.00 | 0.369008E+11 | 0.00 |
March | 0.504598E+12 | 0.874346E+11 | 0.141687E+13 | 0.230864E+12 | 0.210649E+12 | 0.111494E+12 | 0.00 | 0.145820E+12 | 0.542544E+09 | 0.129529E+12 | 0.00 | 0.424212E+11 | 0.00 |
April | 0.450709E+12 | 0.753614E+11 | 0.165903E+13 | 0.216144E+12 | 0.235319E+12 | 0.107956E+12 | 0.00 | 0.206210E+12 | 0.326550E+10 | 0.956840E+11 | 0.00 | 0.365752E+11 | 0.00 |
May | 0.486374E+12 | 0.696708E+11 | 0.774844E+12 | 0.224502E+12 | 0.203443E+12 | 0.820361E+11 | 0.00 | 0.209927E+12 | 0.107912E+11 | 0.383736E+11 | 0.00 | 0.364325E+11 | 0.00 |
June | 0.484022E+12 | 0.630959E+11 | 0.106252E+13 | 0.222585E+12 | 0.240639E+12 | 0.124263E+12 | 0.00 | 0.401484E+12 | 0.615031E+11 | 0.911605E+10 | 0.00 | 0.335727E+11 | 0.00 |
July | 0.453060E+12 | 0.671331E+11 | 0.139340E+13 | 0.218061E+12 | 0.268851E+12 | 0.164768E+12 | 0.00 | 0.577124E+12 | 0.108941E+12 | 99001362.23 | 0.00 | 0.303303E+11 | 0.00 |
August | 0.504598E+12 | 0.741310E+11 | 0.173200E+13 | 0.230864E+12 | 0.325907E+12 | 0.170488E+12 | 0.00 | 0.603562E+12 | 0.901069E+11 | 0.924600E+10 | 0.00 | 0.327267E+11 | 0.00 |
September | 0.450709E+12 | 0.805521E+11 | 0.740713E+12 | 0.216143E+12 | 0.213240E+12 | 0.908572E+11 | 0.00 | 0.271535E+12 | 0.328625E+11 | 0.127404E+11 | 0.00 | 0.306145E+11 | 0.00 |
October | 0.468149E+12 | 0.928560E+11 | 0.108340E+13 | 0.218140E+12 | 0.218552E+12 | 0.873322E+11 | 0.00 | 0.245916E+12 | 0.161737E+11 | 0.541471E+11 | 0.00 | 0.335932E+11 | 0.00 |
November | 0.462662E+12 | 0.983158E+11 | 0.135889E+13 | 0.209941E+12 | 0.196735E+12 | 0.104724E+12 | 0.00 | 0.148782E+12 | 0.826093E+09 | 0.113421E+12 | 0.00 | 0.354479E+11 | 0.00 |
December | 0.453060E+12 | 0.106160E+12 | 0.170972E+13 | 0.218060E+12 | 0.223309E+12 | 0.100040E+12 | 0.00 | 0.121702E+12 | 11606280.68 | 0.222640E+12 | 0.00 | 0.376421E+11 | 0.00 |
Annual Sum or Average | 0.561074E+13 | 0.100615E+13 | 0.146764E+14 | 0.262311E+13 | 0.267935E+13 | 0.122695E+13 | 0.00 | 0.302175E+13 | 0.325037E+12 | 0.891668E+12 | 0.00 | 0.426477E+12 | 0.00 |
Minimum of Months | 0.424646E+12 | 0.630959E+11 | 0.740713E+12 | 0.199667E+12 | 0.170995E+12 | 0.380141E+11 | 0.00 | 0.236097E+11 | 4776730.73 | 99001362.23 | 0.00 | 0.303303E+11 | 0.00 |
Maximum of Months | 0.504598E+12 | 0.106160E+12 | 0.173200E+13 | 0.230864E+12 | 0.325907E+12 | 0.170488E+12 | 0.00 | 0.603562E+12 | 0.108941E+12 | 0.222640E+12 | 0.00 | 0.424212E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.997766E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.826038E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.321069E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.124948E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.167800E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.292952E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 592135.18 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 72131025.90 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.695380E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.512415E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.302439E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.542455E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.319006E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 592135.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.997766E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 489900.85 | 02-JAN-08:09 | 64082.80 | 01-JAN-00:10 | 423497.50 | 02-JAN-08:09 | 235096.12 | 02-JAN-08:20 | 142298.58 | 02-JAN-06:19 | 47686.02 | 24-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 489900.85 | 01-FEB-08:09 | 64082.80 | 01-FEB-00:10 | 541788.89 | 01-FEB-08:09 | 235096.12 | 01-FEB-08:20 | 141944.40 | 02-FEB-13:39 | 47207.75 | 24-FEB-15:20 | 0.00 | 01-FEB-00:10 |
March | 489900.85 | 01-MAR-08:09 | 64082.80 | 01-MAR-00:10 | 660080.29 | 01-MAR-08:09 | 235096.12 | 01-MAR-08:20 | 177562.22 | 29-MAR-15:30 | 48824.40 | 02-MAR-19:19 | 0.00 | 01-MAR-00:10 |
April | 489900.85 | 03-APR-07:10 | 64082.80 | 01-APR-00:10 | 778371.69 | 03-APR-07:10 | 235096.12 | 03-APR-07:19 | 238460.98 | 07-APR-14:00 | 99456.07 | 07-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 489900.85 | 01-MAY-07:10 | 64082.80 | 01-MAY-00:10 | 423497.50 | 01-MAY-07:10 | 235096.12 | 01-MAY-07:19 | 244399.73 | 30-MAY-14:30 | 96955.00 | 30-MAY-12:20 | 0.00 | 01-MAY-00:10 |
June | 489900.85 | 01-JUN-07:10 | 64082.80 | 01-JUN-00:10 | 541788.89 | 01-JUN-07:10 | 235096.12 | 01-JUN-07:19 | 265777.64 | 19-JUN-14:30 | 98413.36 | 19-JUN-14:09 | 0.00 | 01-JUN-00:10 |
July | 489900.85 | 03-JUL-07:10 | 64082.80 | 01-JUL-00:10 | 660080.29 | 03-JUL-07:10 | 235096.12 | 03-JUL-07:19 | 273168.63 | 10-JUL-14:09 | 99546.69 | 20-JUL-14:30 | 0.00 | 01-JUL-00:10 |
August | 489900.85 | 01-AUG-07:10 | 64082.80 | 01-AUG-00:10 | 778371.69 | 01-AUG-07:10 | 235096.12 | 01-AUG-07:19 | 296507.39 | 18-AUG-14:39 | 103899.52 | 30-AUG-11:00 | 0.00 | 01-AUG-00:10 |
September | 489900.85 | 01-SEP-07:10 | 64082.80 | 01-SEP-00:10 | 423497.50 | 01-SEP-07:10 | 235096.12 | 01-SEP-07:19 | 258437.23 | 01-SEP-15:09 | 99505.99 | 07-SEP-12:00 | 0.00 | 01-SEP-00:10 |
October | 489900.85 | 02-OCT-07:10 | 64082.80 | 01-OCT-00:10 | 541788.89 | 02-OCT-07:10 | 235096.12 | 02-OCT-07:19 | 225444.36 | 04-OCT-15:39 | 107178.47 | 04-OCT-13:20 | 0.00 | 01-OCT-00:10 |
November | 489900.85 | 01-NOV-07:10 | 64082.80 | 01-NOV-00:10 | 660080.29 | 01-NOV-07:10 | 235096.12 | 01-NOV-07:19 | 186666.06 | 03-NOV-14:09 | 51125.93 | 03-NOV-15:39 | 0.00 | 01-NOV-00:10 |
December | 489900.85 | 01-DEC-08:09 | 64082.80 | 01-DEC-00:10 | 778371.69 | 01-DEC-08:09 | 235096.12 | 01-DEC-08:20 | 161293.11 | 21-DEC-13:00 | 48769.55 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 489900.85 | 64082.80 | 423497.50 | 235096.12 | 141944.40 | 47207.75 | 0.00 | |||||||
Maximum of Months | 489900.85 | 64082.80 | 778371.69 | 235096.12 | 296507.39 | 107178.47 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 84993.50 | 19-JAN-13:09 | 621.39 | 24-JAN-11:00 | 60837.42 | 19-JAN-14:09 | 0.00 | 53163.27 | 31-JAN-12:39 | 0.00 |
February | 125396.32 | 24-FEB-15:09 | 58.28 | 24-FEB-13:00 | 84911.42 | 02-FEB-14:00 | 0.00 | 53278.86 | 09-FEB-12:30 | 0.00 |
March | 198272.21 | 27-MAR-15:00 | 21854.96 | 27-MAR-15:00 | 100000.00 | 02-MAR-22:19 | 0.00 | 52913.70 | 01-MAR-12:30 | 0.00 |
April | 355935.68 | 07-APR-15:39 | 57461.26 | 07-APR-13:30 | 100000.00 | 01-APR-01:00 | 0.00 | 51090.02 | 04-APR-11:20 | 0.00 |
May | 357522.06 | 31-MAY-12:09 | 57461.26 | 30-MAY-09:00 | 100000.00 | 20-MAY-17:40 | 0.00 | 47631.32 | 01-MAY-11:00 | 0.00 |
June | 419950.72 | 19-JUN-14:09 | 57461.26 | 01-JUN-10:50 | 100000.00 | 04-JUN-09:39 | 0.00 | 44516.93 | 01-JUN-11:30 | 0.00 |
July | 463842.16 | 20-JUL-14:30 | 57461.26 | 01-JUL-07:00 | 80415.03 | 05-JUL-07:30 | 0.00 | 41454.81 | 03-JUL-11:00 | 0.00 |
August | 508172.57 | 04-AUG-14:09 | 57461.26 | 01-AUG-05:30 | 100000.00 | 20-AUG-14:09 | 0.00 | 40351.85 | 31-AUG-11:50 | 0.00 |
September | 383404.77 | 07-SEP-14:09 | 57461.26 | 01-SEP-05:19 | 100000.00 | 10-SEP-17:49 | 0.00 | 42475.90 | 29-SEP-11:39 | 0.00 |
October | 355254.19 | 04-OCT-12:09 | 57461.26 | 03-OCT-11:30 | 100000.00 | 25-OCT-16:40 | 0.00 | 45760.13 | 31-OCT-11:00 | 0.00 |
November | 192717.93 | 03-NOV-13:00 | 11521.26 | 10-NOV-09:00 | 100000.00 | 18-NOV-07:40 | 0.00 | 49086.34 | 30-NOV-12:20 | 0.00 |
December | 165113.36 | 20-DEC-13:50 | 652.78 | 20-DEC-13:50 | 100000.00 | 01-DEC-05:30 | 0.00 | 52045.54 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 84993.50 | 58.28 | 60837.42 | 0.00 | 40351.85 | 0.00 | ||||
Maximum of Months | 508172.57 | 57461.26 | 100000.00 | 0.00 | 53278.86 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1503357.62 | 19-JAN-16:00 | 489900.85 | 423497.50 | 64082.80 | 235096.12 | 95326.43 | 46038.91 | 0.00 | 48050.53 | 0.10 |
February | 1684315.76 | 02-FEB-15:09 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 139685.57 | 47103.11 | 0.00 | 116466.53 | 23.79 |
March | 1904744.41 | 15-MAR-15:20 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 171524.07 | 48075.94 | 0.00 | 163673.11 | 863.21 |
April | 2267564.56 | 07-APR-15:39 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 227810.05 | 97549.76 | 0.00 | 355935.68 | 43872.38 |
May | 1903002.53 | 30-MAY-15:20 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 243713.95 | 95831.33 | 0.00 | 323025.36 | 57461.26 |
June | 2132752.43 | 19-JUN-14:09 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 265239.28 | 98413.36 | 0.00 | 419950.72 | 57461.26 |
July | 2291811.50 | 20-JUL-14:30 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 262328.46 | 99546.69 | 0.00 | 463842.16 | 57461.26 |
August | 2481535.09 | 02-AUG-15:09 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 285852.74 | 100801.18 | 0.00 | 504144.94 | 57461.26 |
September | 1954294.81 | 07-SEP-15:20 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 254760.12 | 97106.13 | 0.00 | 364976.75 | 57461.26 |
October | 2009385.04 | 03-OCT-15:30 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 213168.40 | 95598.77 | 0.00 | 343630.62 | 57461.26 |
November | 1902258.72 | 03-NOV-14:09 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 186666.06 | 50273.06 | 0.00 | 178858.34 | 5078.04 |
December | 2028654.90 | 19-DEC-16:40 | 489900.85 | 778371.69 | 64082.80 | 235096.12 | 128855.38 | 48158.25 | 0.00 | 160144.98 | 110.04 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1503357.62 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 95326.43 | 46038.91 | 0.00 | 48050.53 | 0.10 | |
Maximum of Months | 2481535.09 | 489900.85 | 778371.69 | 64082.80 | 235096.12 | 285852.74 | 100801.18 | 0.00 | 504144.94 | 57461.26 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 3138528.82 | 02-JAN-06:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 2646650.28 | 06-FEB-05:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1261872.80 | 13-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 912637.27 | 21-APR-04:19 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 627808.46 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 21170.83 | 03-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 735.53 | 04-JUL-17:49 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 5770.55 | 08-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 195319.09 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 611438.09 | 31-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 1602790.79 | 24-NOV-05:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 1256274.46 | 15-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 735.53 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 3138528.82 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.68 | 0.00 | 25.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.66 | 0.00 | 25.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 25.78 | 0.17 | 25.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 25.88 | 0.17 | 25.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.36 | 0.00 | 26.36 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 25.75 | 0.00 | 25.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.87 | 0.17 | 26.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.60 | 0.00 | 25.60 |
Annual Sum or Average | 0.00 | 0.00 | 17.33 | 25.93 | 0.50 | 25.92 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 26.36 | 0.17 | 26.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.70 | 0.00 | 25.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 25.64 | 0.00 | 25.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.70 | 0.00 | 25.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 19.23 | 0.50 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 19.23 | 0.50 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 19.23 | 0.50 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 18.79 | 0.67 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
February | 3.83 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 |
March | 0.83 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 18.96 | 0.17 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
December | 2.17 | 18.94 | 0.17 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
Annual Sum or Average | 11.83 | 18.65 | 1.00 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.83 | 18.96 | 0.67 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 |
February | 2.83 | 18.84 | 0.33 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.67 | 18.78 | 0.33 | 18.89 | 0.17 | 19.16 | 0.17 | 19.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 18.84 | 0.33 | 19.01 | 0.17 | 27.30 | 0.17 | 27.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
February | 2.67 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.83 | 1.17 | 27.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.32 | 3.50 | 28.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.27 | 1.67 | 28.27 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.37 | 4.00 | 28.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.14 | 2.33 | 28.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.48 | 3.17 | 28.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.50 | 18.63 | 0.00 | 18.63 | 15.83 | 26.16 | 15.83 | 27.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 18.65 | 0.00 | 18.65 | 4.00 | 28.48 | 4.00 | 28.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 |
February | 3.33 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
March | 0.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.69 | 1.67 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.39 | 0.33 | 27.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.88 | 4.50 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.26 | 4.00 | 28.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.54 | 5.00 | 28.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.00 | 5.17 | 28.00 |
November | 0.33 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.04 | 1.83 | 28.04 |
Annual Sum or Average | 6.50 | 18.71 | 0.00 | 18.71 | 22.83 | 26.02 | 22.83 | 26.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.57 | 0.00 | 18.57 |
Maximum of Months | 3.33 | 19.43 | 0.00 | 19.43 | 5.17 | 28.54 | 5.17 | 28.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.11 | 0.00 | 18.11 | 0.00 | 18.11 | 0.00 | 18.11 |
February | 1.50 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.57 | 1.83 | 28.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.94 | 2.83 | 27.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.34 | 3.50 | 28.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 28.02 | 6.67 | 28.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.82 | 4.50 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.53 | 2.50 | 28.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.96 | 0.67 | 27.96 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.17 | 18.46 | 0.00 | 18.46 | 41.83 | 27.60 | 22.50 | 27.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 18.61 | 0.00 | 18.61 | 15.17 | 28.57 | 6.67 | 28.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 23.00 | 15.96 | 5.00 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 |
February | 21.17 | 16.12 | 4.83 | 15.96 | 0.00 | 15.96 | 0.00 | 15.96 |
March | 4.50 | 18.87 | 0.17 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
April | 0.67 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.83 | 18.47 | 0.17 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
December | 8.50 | 17.28 | 1.17 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 |
Annual Sum or Average | 61.67 | 16.60 | 11.33 | 16.38 | 0.00 | 16.38 | 0.00 | 16.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.00 | 19.24 | 5.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.33 | 16.55 | 3.83 | 16.39 | 0.00 | 16.39 | 0.00 | 16.39 |
February | 23.00 | 17.00 | 1.67 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 |
March | 4.33 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
April | 0.83 | 19.27 | 0.00 | 19.27 | 0.33 | 21.56 | 0.33 | 22.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.38 | 3.50 | 28.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.34 | 1.83 | 28.34 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.42 | 5.00 | 28.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.23 | 3.17 | 28.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.48 | 3.17 | 28.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4.83 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
December | 12.83 | 18.18 | 0.67 | 18.01 | 0.00 | 18.01 | 0.00 | 18.01 |
Annual Sum or Average | 75.17 | 17.26 | 6.17 | 17.10 | 17.00 | 19.05 | 17.00 | 20.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 29.33 | 19.27 | 3.83 | 19.27 | 5.00 | 28.48 | 5.00 | 28.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.33 | 16.28 | 1.83 | 16.17 | 0.00 | 16.17 | 0.00 | 16.17 |
February | 13.50 | 16.78 | 1.17 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 |
March | 3.83 | 19.04 | 0.17 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
April | 0.50 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.69 | 1.50 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.92 | 4.00 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.31 | 3.83 | 28.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.63 | 5.17 | 28.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.15 | 5.17 | 28.15 |
November | 3.17 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
December | 6.33 | 17.97 | 0.33 | 17.82 | 1.67 | 19.87 | 1.67 | 21.24 |
Annual Sum or Average | 45.67 | 17.09 | 3.50 | 16.97 | 21.50 | 20.39 | 21.33 | 22.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 18.33 | 19.26 | 1.83 | 19.26 | 5.17 | 28.63 | 5.17 | 28.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.83 | 15.99 | 3.67 | 15.79 | 0.00 | 15.79 | 0.00 | 15.79 |
February | 15.50 | 16.40 | 2.50 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
March | 2.83 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
April | 0.33 | 19.27 | 0.00 | 19.27 | 1.33 | 26.04 | 1.00 | 26.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.82 | 2.00 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.44 | 2.33 | 28.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.51 | 3.83 | 28.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.67 | 1.67 | 28.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.49 | 2.00 | 28.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
November | 3.00 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
December | 6.67 | 18.02 | 0.00 | 18.02 | 0.00 | 18.02 | 0.00 | 18.02 |
Annual Sum or Average | 46.17 | 16.79 | 6.17 | 16.57 | 18.50 | 19.65 | 13.00 | 21.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.79 | 0.00 | 15.79 |
Maximum of Months | 17.83 | 19.27 | 3.67 | 19.27 | 5.83 | 28.67 | 3.83 | 28.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 53.83 | 15.01 | 12.33 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
February | 46.50 | 15.17 | 11.00 | 15.03 | 0.00 | 15.03 | 0.00 | 15.03 |
March | 13.00 | 16.87 | 1.67 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
April | 3.00 | 18.65 | 0.17 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
May | 0.33 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.67 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
November | 17.33 | 16.11 | 2.83 | 16.01 | 0.00 | 16.01 | 0.00 | 16.01 |
December | 32.00 | 15.54 | 5.33 | 15.39 | 0.00 | 15.39 | 0.00 | 15.39 |
Annual Sum or Average | 167.67 | 15.53 | 33.33 | 15.38 | 0.00 | 15.38 | 0.00 | 15.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.83 | 19.15 | 12.33 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.33 | 15.03 | 11.33 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
February | 43.33 | 15.24 | 9.17 | 15.15 | 0.00 | 15.15 | 0.00 | 15.15 |
March | 13.17 | 16.90 | 1.50 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 |
April | 3.17 | 18.70 | 0.17 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 |
May | 0.33 | 19.13 | 0.00 | 19.13 | 3.50 | 27.41 | 3.50 | 27.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.24 | 1.83 | 28.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.29 | 6.83 | 28.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.24 | 3.67 | 28.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.37 | 2.83 | 28.37 |
October | 1.50 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
November | 16.00 | 16.23 | 1.67 | 16.19 | 0.00 | 16.19 | 0.00 | 16.19 |
December | 31.33 | 15.55 | 4.83 | 15.43 | 0.00 | 15.43 | 0.00 | 15.43 |
Annual Sum or Average | 163.17 | 15.57 | 28.67 | 15.46 | 18.67 | 16.59 | 18.67 | 17.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.96 | 0.00 | 14.96 |
Maximum of Months | 54.33 | 19.13 | 11.33 | 19.13 | 6.83 | 28.37 | 6.83 | 28.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.83 | 15.16 | 7.33 | 15.08 | 0.00 | 15.08 | 0.00 | 15.08 |
February | 34.17 | 15.51 | 5.83 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
March | 9.50 | 17.47 | 0.83 | 17.44 | 0.00 | 17.44 | 0.00 | 17.44 |
April | 2.83 | 18.70 | 0.17 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 |
May | 0.33 | 19.20 | 0.00 | 19.20 | 1.50 | 26.15 | 1.50 | 26.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.32 | 0.33 | 27.32 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.06 | 4.33 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.49 | 3.67 | 28.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.64 | 5.00 | 28.64 |
October | 0.83 | 19.11 | 0.00 | 19.11 | 2.00 | 25.55 | 2.00 | 26.66 |
November | 13.00 | 16.52 | 1.33 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 |
December | 23.50 | 15.92 | 2.50 | 15.80 | 0.00 | 15.80 | 0.00 | 15.80 |
Annual Sum or Average | 126.00 | 15.83 | 18.00 | 15.72 | 17.00 | 17.05 | 16.83 | 18.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.08 | 0.00 | 15.08 |
Maximum of Months | 41.83 | 19.20 | 7.33 | 19.20 | 5.00 | 28.64 | 5.00 | 28.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.00 | 15.11 | 9.33 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
February | 30.67 | 15.37 | 5.83 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 |
March | 7.50 | 17.61 | 0.00 | 17.61 | 0.00 | 17.61 | 0.00 | 17.61 |
April | 1.67 | 18.89 | 0.00 | 18.89 | 0.83 | 21.88 | 0.67 | 23.14 |
May | 0.17 | 19.35 | 0.00 | 19.35 | 2.83 | 27.37 | 2.33 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.40 | 2.67 | 28.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.73 | 4.00 | 28.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.87 | 2.00 | 28.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.48 | 2.17 | 28.58 |
October | 0.83 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
November | 10.83 | 16.45 | 1.00 | 16.39 | 0.00 | 16.39 | 0.00 | 16.39 |
December | 18.83 | 16.09 | 2.83 | 15.90 | 0.00 | 15.90 | 0.00 | 15.90 |
Annual Sum or Average | 112.50 | 15.74 | 19.00 | 15.57 | 20.00 | 17.27 | 13.83 | 18.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.01 | 0.00 | 15.01 |
Maximum of Months | 42.00 | 19.35 | 9.33 | 19.35 | 6.17 | 28.87 | 4.00 | 28.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.69 | 0.50 | 27.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 28.02 | 15.50 | 28.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.67 | 28.01 | 16.00 | 28.02 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 28.02 | 15.50 | 28.03 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 381.33 | 23.52 | 52.00 | 23.65 | 12.17 | 23.65 |
February | 345.17 | 23.43 | 12.67 | 23.52 | 0.00 | 23.52 |
March | 212.17 | 23.75 | 72.00 | 24.06 | 0.00 | 24.06 |
April | 81.33 | 23.81 | 154.00 | 24.52 | 0.00 | 24.52 |
May | 10.33 | 23.95 | 313.67 | 24.59 | 0.00 | 24.59 |
June | 13.17 | 26.46 | 445.00 | 24.52 | 13.17 | 24.57 |
July | 18.00 | 26.73 | 495.00 | 24.66 | 18.00 | 24.73 |
August | 16.00 | 26.96 | 494.17 | 24.58 | 16.00 | 24.65 |
September | 1.00 | 27.17 | 440.33 | 24.61 | 1.00 | 24.62 |
October | 16.67 | 23.91 | 370.50 | 24.75 | 0.00 | 24.75 |
November | 61.50 | 23.83 | 173.33 | 25.02 | 0.00 | 25.02 |
December | 264.50 | 23.76 | 71.00 | 24.23 | 0.00 | 24.23 |
Annual Sum or Average | 1421.17 | 23.72 | 3093.67 | 24.39 | 60.33 | 24.41 |
Minimum of Months | 1.00 | 23.43 | 12.67 | 23.52 | 0.00 | 23.52 |
Maximum of Months | 381.33 | 27.17 | 495.00 | 25.02 | 18.00 | 25.02 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 368.17 | 23.43 | 21.17 | 23.44 | 2.83 | 23.42 |
February | 344.67 | 23.62 | 0.00 | 23.62 | 0.00 | 23.62 |
March | 172.33 | 23.71 | 64.33 | 23.96 | 0.00 | 23.96 |
April | 77.17 | 23.68 | 190.33 | 24.26 | 0.00 | 24.26 |
May | 22.33 | 23.72 | 319.17 | 24.28 | 0.00 | 24.28 |
June | 0.00 | 0.00 | 453.83 | 24.26 | 0.00 | 24.26 |
July | 0.00 | 0.00 | 497.00 | 24.25 | 0.00 | 24.25 |
August | 0.00 | 0.00 | 506.50 | 24.22 | 0.00 | 24.22 |
September | 4.83 | 23.70 | 424.17 | 24.34 | 0.00 | 24.34 |
October | 41.17 | 23.89 | 325.83 | 24.34 | 0.00 | 24.34 |
November | 86.33 | 23.72 | 129.00 | 24.49 | 0.00 | 24.49 |
December | 196.67 | 23.75 | 13.00 | 23.84 | 0.00 | 23.84 |
Annual Sum or Average | 1313.67 | 23.62 | 2944.33 | 24.12 | 2.83 | 24.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.44 | 0.00 | 23.42 |
Maximum of Months | 368.17 | 23.89 | 506.50 | 24.49 | 2.83 | 24.49 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 491.00 | 22.22 | 80.83 | 21.87 | 80.83 | 21.60 |
February | 448.17 | 22.67 | 42.50 | 22.50 | 42.50 | 22.35 |
March | 385.33 | 23.31 | 15.17 | 23.33 | 0.00 | 23.33 |
April | 230.83 | 23.22 | 66.67 | 23.45 | 0.00 | 23.45 |
May | 103.33 | 23.42 | 232.83 | 23.96 | 0.00 | 23.96 |
June | 21.50 | 23.52 | 429.33 | 24.18 | 0.00 | 24.18 |
July | 0.00 | 0.00 | 482.67 | 24.21 | 0.00 | 24.21 |
August | 0.00 | 0.00 | 480.33 | 24.24 | 0.00 | 24.24 |
September | 41.67 | 23.44 | 353.50 | 24.14 | 0.00 | 24.14 |
October | 143.33 | 23.43 | 224.50 | 23.90 | 0.00 | 23.90 |
November | 312.00 | 23.10 | 50.00 | 23.25 | 2.00 | 23.24 |
December | 485.00 | 22.97 | 12.00 | 22.91 | 12.00 | 22.85 |
Annual Sum or Average | 2662.17 | 22.92 | 2470.33 | 23.44 | 137.33 | 23.35 |
Minimum of Months | 0.00 | 0.00 | 12.00 | 21.87 | 0.00 | 21.60 |
Maximum of Months | 491.00 | 23.52 | 482.67 | 24.24 | 80.83 | 24.24 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.79 | 237.17 | 20.43 | 237.17 | 20.24 |
February | 454.00 | 21.03 | 217.83 | 20.70 | 217.83 | 20.54 |
March | 480.17 | 21.93 | 90.67 | 21.70 | 85.33 | 21.51 |
April | 365.00 | 22.23 | 80.33 | 22.29 | 29.50 | 22.16 |
May | 229.33 | 22.87 | 176.33 | 23.39 | 0.00 | 23.39 |
June | 37.00 | 23.10 | 392.33 | 24.08 | 0.00 | 24.08 |
July | 1.83 | 23.12 | 468.00 | 24.24 | 0.00 | 24.24 |
August | 18.00 | 23.20 | 458.00 | 24.19 | 0.17 | 24.19 |
September | 128.17 | 22.85 | 273.83 | 23.70 | 0.00 | 23.70 |
October | 315.33 | 22.24 | 165.00 | 22.53 | 39.33 | 22.35 |
November | 463.17 | 21.68 | 105.00 | 21.41 | 97.00 | 21.20 |
December | 497.00 | 21.02 | 199.50 | 20.67 | 199.50 | 20.48 |
Annual Sum or Average | 3491.00 | 21.66 | 2864.00 | 22.18 | 905.83 | 21.90 |
Minimum of Months | 1.83 | 20.79 | 80.33 | 20.43 | 0.00 | 20.24 |
Maximum of Months | 502.00 | 23.20 | 468.00 | 24.24 | 237.17 | 24.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.89 | 239.17 | 20.69 | 239.17 | 20.58 |
February | 454.00 | 21.00 | 219.33 | 20.81 | 219.33 | 20.72 |
March | 481.33 | 21.96 | 51.17 | 21.90 | 42.00 | 21.82 |
April | 329.33 | 22.44 | 85.00 | 22.76 | 2.17 | 22.75 |
May | 164.33 | 23.02 | 213.50 | 23.65 | 0.00 | 23.65 |
June | 18.50 | 24.15 | 443.33 | 24.22 | 7.17 | 24.24 |
July | 11.67 | 26.50 | 497.00 | 24.40 | 11.67 | 24.45 |
August | 9.00 | 24.70 | 488.50 | 24.23 | 3.83 | 24.25 |
September | 95.67 | 23.10 | 336.83 | 23.95 | 3.33 | 23.97 |
October | 252.50 | 22.61 | 163.33 | 23.17 | 0.00 | 23.17 |
November | 438.00 | 22.07 | 58.00 | 22.02 | 41.67 | 21.91 |
December | 497.00 | 21.42 | 90.50 | 21.29 | 90.50 | 21.20 |
Annual Sum or Average | 3253.33 | 21.82 | 2885.67 | 22.55 | 660.83 | 22.37 |
Minimum of Months | 9.00 | 20.89 | 51.17 | 20.69 | 0.00 | 20.58 |
Maximum of Months | 502.00 | 26.50 | 497.00 | 24.40 | 239.17 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.50 | 20.81 | 208.50 | 20.62 | 208.50 | 20.52 |
February | 447.67 | 21.06 | 178.67 | 20.89 | 177.33 | 20.79 |
March | 445.50 | 21.54 | 72.67 | 21.58 | 48.83 | 21.49 |
April | 331.50 | 21.93 | 112.33 | 22.50 | 7.17 | 22.54 |
May | 242.83 | 22.59 | 218.83 | 23.40 | 13.33 | 23.50 |
June | 95.33 | 23.02 | 366.67 | 23.91 | 14.83 | 23.97 |
July | 63.83 | 24.00 | 407.83 | 24.17 | 22.67 | 24.29 |
August | 69.50 | 23.24 | 402.17 | 23.96 | 12.33 | 24.02 |
September | 167.17 | 22.75 | 283.50 | 23.70 | 17.50 | 23.82 |
October | 284.17 | 22.14 | 163.50 | 22.86 | 2.83 | 22.86 |
November | 447.83 | 21.71 | 55.67 | 21.71 | 39.00 | 21.63 |
December | 492.17 | 21.19 | 114.00 | 21.07 | 113.33 | 20.99 |
Annual Sum or Average | 3588.00 | 21.68 | 2584.33 | 22.36 | 677.67 | 22.25 |
Minimum of Months | 63.83 | 20.81 | 55.67 | 20.62 | 2.83 | 20.52 |
Maximum of Months | 500.50 | 24.00 | 407.83 | 24.17 | 208.50 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 434.17 | 20.88 | 214.67 | 20.75 | 193.33 | 20.58 |
February | 365.50 | 21.24 | 185.17 | 21.20 | 154.33 | 21.03 |
March | 377.00 | 21.60 | 134.83 | 21.94 | 46.83 | 21.84 |
April | 317.17 | 21.97 | 132.33 | 22.58 | 9.50 | 22.57 |
May | 241.17 | 22.58 | 195.83 | 23.32 | 5.33 | 23.36 |
June | 73.17 | 23.23 | 379.33 | 24.04 | 12.67 | 24.08 |
July | 28.67 | 26.14 | 455.67 | 24.38 | 24.83 | 24.49 |
August | 39.67 | 24.61 | 455.83 | 24.24 | 18.00 | 24.33 |
September | 124.00 | 23.38 | 329.17 | 24.09 | 25.17 | 24.24 |
October | 198.33 | 22.65 | 272.00 | 23.61 | 18.33 | 23.68 |
November | 349.17 | 21.79 | 131.17 | 22.18 | 37.00 | 22.05 |
December | 401.50 | 21.40 | 159.50 | 21.50 | 116.17 | 21.37 |
Annual Sum or Average | 2949.50 | 21.83 | 3045.50 | 22.71 | 661.50 | 22.57 |
Minimum of Months | 28.67 | 20.88 | 131.17 | 20.75 | 5.33 | 20.58 |
Maximum of Months | 434.17 | 26.14 | 455.83 | 24.38 | 193.33 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 486.83 | 21.07 | 156.33 | 20.94 | 151.17 | 20.84 |
February | 429.33 | 21.26 | 121.00 | 21.20 | 110.33 | 21.10 |
March | 402.83 | 21.98 | 82.50 | 22.33 | 4.17 | 22.32 |
April | 259.17 | 22.41 | 172.33 | 23.23 | 9.50 | 23.30 |
May | 189.67 | 22.65 | 247.17 | 23.56 | 15.50 | 23.66 |
June | 61.33 | 24.45 | 439.00 | 24.30 | 35.17 | 24.41 |
July | 74.00 | 25.91 | 496.33 | 24.57 | 74.00 | 24.73 |
August | 86.33 | 25.10 | 506.83 | 24.43 | 86.33 | 24.52 |
September | 122.50 | 22.97 | 323.33 | 23.91 | 20.33 | 24.02 |
October | 220.00 | 22.29 | 223.50 | 23.24 | 2.33 | 23.26 |
November | 396.17 | 21.97 | 54.17 | 22.22 | 6.00 | 22.20 |
December | 460.00 | 21.76 | 16.33 | 21.81 | 6.67 | 21.80 |
Annual Sum or Average | 3188.17 | 22.07 | 2838.83 | 22.95 | 521.50 | 22.95 |
Minimum of Months | 61.33 | 21.07 | 16.33 | 20.94 | 2.33 | 20.84 |
Maximum of Months | 486.83 | 25.91 | 506.83 | 24.57 | 151.17 | 24.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.04 | 388.33 | 19.91 | 388.33 | 19.87 |
February | 454.00 | 20.17 | 372.33 | 20.09 | 372.33 | 20.05 |
March | 513.33 | 20.83 | 202.33 | 20.65 | 202.33 | 20.55 |
April | 442.83 | 21.39 | 86.00 | 21.31 | 72.67 | 21.19 |
May | 348.33 | 22.23 | 99.83 | 22.61 | 0.00 | 22.61 |
June | 111.00 | 22.79 | 330.17 | 23.74 | 10.50 | 23.76 |
July | 48.33 | 24.33 | 434.83 | 24.20 | 29.00 | 24.27 |
August | 82.50 | 23.36 | 391.83 | 24.03 | 19.17 | 24.10 |
September | 260.83 | 22.32 | 165.00 | 22.97 | 8.17 | 22.99 |
October | 428.17 | 21.58 | 94.50 | 21.57 | 58.33 | 21.43 |
November | 489.00 | 20.73 | 195.00 | 20.50 | 195.00 | 20.38 |
December | 497.00 | 20.26 | 392.67 | 20.17 | 392.67 | 20.13 |
Annual Sum or Average | 4177.33 | 21.07 | 3152.83 | 21.43 | 1748.50 | 21.19 |
Minimum of Months | 48.33 | 20.04 | 86.00 | 19.91 | 0.00 | 19.87 |
Maximum of Months | 513.33 | 24.33 | 434.83 | 24.20 | 392.67 | 24.27 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.93 | 321.17 | 19.76 | 321.17 | 19.69 |
February | 385.00 | 20.26 | 275.00 | 20.08 | 275.00 | 20.01 |
March | 411.00 | 20.99 | 151.83 | 20.78 | 144.17 | 20.62 |
April | 319.00 | 21.49 | 107.17 | 21.84 | 42.33 | 21.74 |
May | 256.50 | 22.24 | 151.50 | 23.07 | 14.33 | 23.20 |
June | 129.17 | 22.84 | 262.33 | 23.78 | 19.83 | 23.88 |
July | 102.00 | 24.40 | 338.00 | 24.40 | 55.17 | 24.59 |
August | 95.00 | 23.78 | 330.83 | 24.20 | 36.17 | 24.34 |
September | 207.50 | 22.44 | 189.17 | 23.34 | 21.67 | 23.48 |
October | 312.83 | 21.66 | 105.83 | 22.04 | 24.67 | 21.96 |
November | 410.67 | 20.88 | 143.50 | 20.61 | 143.50 | 20.45 |
December | 422.00 | 20.29 | 290.50 | 20.12 | 290.50 | 20.06 |
Annual Sum or Average | 3477.67 | 21.21 | 2666.83 | 21.65 | 1388.50 | 21.44 |
Minimum of Months | 95.00 | 19.93 | 105.83 | 19.76 | 14.33 | 19.69 |
Maximum of Months | 427.00 | 24.40 | 338.00 | 24.40 | 321.17 | 24.59 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 443.00 | 20.40 | 279.00 | 20.20 | 260.67 | 20.04 |
February | 377.67 | 20.82 | 244.33 | 20.74 | 214.00 | 20.57 |
March | 390.67 | 21.17 | 197.67 | 21.38 | 117.83 | 21.18 |
April | 346.50 | 21.55 | 149.67 | 22.03 | 46.50 | 21.90 |
May | 293.00 | 22.28 | 171.83 | 23.01 | 5.33 | 23.05 |
June | 117.50 | 22.91 | 337.67 | 23.85 | 16.33 | 23.89 |
July | 77.17 | 24.95 | 430.00 | 24.44 | 52.67 | 24.58 |
August | 78.50 | 24.43 | 433.83 | 24.34 | 37.17 | 24.48 |
September | 175.33 | 23.06 | 295.50 | 23.87 | 31.67 | 24.02 |
October | 234.00 | 22.37 | 262.83 | 23.31 | 34.83 | 23.36 |
November | 371.17 | 21.25 | 180.50 | 21.42 | 103.83 | 21.20 |
December | 424.00 | 20.93 | 265.67 | 20.88 | 230.33 | 20.72 |
Annual Sum or Average | 3328.50 | 21.55 | 3248.50 | 22.27 | 1151.17 | 22.06 |
Minimum of Months | 77.17 | 20.40 | 149.67 | 20.20 | 5.33 | 20.04 |
Maximum of Months | 443.00 | 24.95 | 433.83 | 24.44 | 260.67 | 24.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.26 | 328.00 | 20.06 | 328.00 | 19.97 |
February | 444.00 | 20.44 | 300.67 | 20.27 | 300.67 | 20.20 |
March | 455.00 | 21.03 | 166.33 | 21.05 | 132.17 | 20.92 |
April | 388.17 | 21.43 | 118.33 | 21.75 | 46.50 | 21.66 |
May | 326.17 | 22.14 | 143.67 | 22.79 | 11.83 | 22.88 |
June | 136.50 | 22.93 | 334.33 | 23.84 | 27.17 | 23.95 |
July | 102.67 | 24.35 | 411.00 | 24.33 | 58.33 | 24.49 |
August | 104.17 | 23.87 | 416.17 | 24.21 | 51.67 | 24.33 |
September | 255.50 | 22.31 | 192.50 | 23.12 | 20.67 | 23.24 |
October | 362.17 | 21.64 | 128.33 | 22.05 | 29.83 | 21.95 |
November | 475.33 | 20.85 | 164.33 | 20.68 | 157.50 | 20.55 |
December | 497.00 | 20.53 | 310.83 | 20.38 | 310.83 | 20.31 |
Annual Sum or Average | 4048.67 | 21.27 | 3014.50 | 21.76 | 1475.17 | 21.58 |
Minimum of Months | 102.67 | 20.26 | 118.33 | 20.06 | 11.83 | 19.97 |
Maximum of Months | 502.00 | 24.35 | 416.17 | 24.33 | 328.00 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 431.33 | 19.74 | 431.33 | 19.71 |
February | 454.00 | 19.94 | 417.17 | 19.90 | 417.17 | 19.88 |
March | 514.00 | 20.43 | 292.67 | 20.24 | 292.67 | 20.14 |
April | 456.50 | 20.94 | 153.17 | 20.75 | 143.83 | 20.60 |
May | 392.00 | 21.69 | 84.33 | 21.98 | 13.83 | 21.94 |
June | 175.67 | 22.30 | 272.50 | 23.32 | 12.50 | 23.34 |
July | 104.83 | 23.16 | 381.83 | 23.91 | 33.33 | 23.99 |
August | 142.33 | 22.68 | 337.50 | 23.69 | 19.67 | 23.76 |
September | 322.67 | 21.84 | 127.17 | 22.35 | 15.00 | 22.35 |
October | 457.00 | 20.95 | 140.33 | 20.77 | 115.50 | 20.56 |
November | 489.00 | 20.22 | 284.33 | 20.00 | 284.33 | 19.90 |
December | 497.00 | 19.88 | 467.67 | 19.84 | 467.67 | 19.83 |
Annual Sum or Average | 4507.00 | 20.75 | 3390.00 | 20.99 | 2246.83 | 20.75 |
Minimum of Months | 104.83 | 19.83 | 84.33 | 19.74 | 12.50 | 19.71 |
Maximum of Months | 514.00 | 23.16 | 467.67 | 23.91 | 467.67 | 23.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.84 | 405.00 | 19.72 | 405.00 | 19.67 |
February | 454.00 | 20.06 | 368.67 | 19.95 | 368.67 | 19.91 |
March | 499.50 | 20.70 | 218.83 | 20.40 | 215.83 | 20.22 |
April | 370.00 | 21.11 | 199.17 | 21.40 | 112.83 | 21.19 |
May | 290.50 | 21.83 | 193.33 | 22.81 | 17.33 | 22.89 |
June | 160.17 | 22.81 | 324.17 | 23.70 | 30.17 | 23.81 |
July | 127.67 | 24.24 | 408.83 | 24.32 | 70.00 | 24.50 |
August | 113.00 | 23.64 | 405.67 | 24.11 | 44.00 | 24.24 |
September | 246.83 | 22.17 | 223.83 | 23.12 | 25.33 | 23.22 |
October | 378.00 | 21.26 | 178.67 | 21.53 | 78.33 | 21.32 |
November | 489.00 | 20.41 | 231.17 | 20.11 | 231.17 | 19.96 |
December | 497.00 | 19.96 | 412.33 | 19.87 | 412.33 | 19.83 |
Annual Sum or Average | 4127.67 | 20.93 | 3569.67 | 21.39 | 2011.00 | 21.15 |
Minimum of Months | 113.00 | 19.84 | 178.67 | 19.72 | 17.33 | 19.67 |
Maximum of Months | 502.00 | 24.24 | 412.33 | 24.32 | 412.33 | 24.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 463.83 | 20.10 | 331.00 | 19.88 | 321.33 | 19.76 |
February | 397.17 | 20.39 | 304.33 | 20.28 | 285.00 | 20.15 |
March | 414.33 | 20.66 | 272.17 | 20.75 | 203.00 | 20.53 |
April | 367.00 | 21.04 | 206.83 | 21.38 | 113.67 | 21.17 |
May | 327.33 | 21.70 | 152.50 | 22.40 | 17.17 | 22.39 |
June | 179.00 | 22.41 | 292.17 | 23.46 | 19.33 | 23.51 |
July | 132.17 | 23.76 | 387.00 | 24.14 | 57.67 | 24.29 |
August | 123.67 | 23.37 | 388.50 | 24.06 | 37.17 | 24.20 |
September | 239.50 | 22.46 | 251.67 | 23.36 | 39.67 | 23.49 |
October | 284.33 | 21.58 | 253.17 | 22.43 | 66.00 | 22.28 |
November | 419.67 | 20.68 | 233.67 | 20.60 | 186.67 | 20.37 |
December | 446.17 | 20.30 | 331.17 | 20.18 | 312.83 | 20.05 |
Annual Sum or Average | 3794.17 | 21.11 | 3404.17 | 21.65 | 1659.50 | 21.41 |
Minimum of Months | 123.67 | 20.10 | 152.50 | 19.88 | 17.17 | 19.76 |
Maximum of Months | 463.83 | 23.76 | 388.50 | 24.14 | 321.33 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.98 | 376.33 | 19.81 | 376.33 | 19.74 |
February | 446.50 | 20.20 | 344.83 | 20.05 | 344.83 | 19.99 |
March | 461.50 | 20.70 | 245.17 | 20.63 | 213.67 | 20.48 |
April | 393.83 | 21.09 | 169.83 | 21.32 | 99.17 | 21.16 |
May | 351.50 | 21.89 | 147.17 | 22.55 | 23.00 | 22.64 |
June | 179.33 | 22.72 | 310.67 | 23.64 | 39.17 | 23.76 |
July | 142.00 | 23.84 | 393.00 | 24.17 | 72.00 | 24.34 |
August | 149.67 | 23.39 | 394.33 | 24.02 | 64.67 | 24.14 |
September | 290.50 | 22.08 | 182.17 | 22.84 | 27.33 | 22.93 |
October | 381.00 | 21.22 | 164.00 | 21.52 | 69.50 | 21.32 |
November | 477.83 | 20.43 | 239.67 | 20.20 | 236.00 | 20.07 |
December | 497.00 | 20.14 | 395.33 | 20.02 | 395.33 | 19.97 |
Annual Sum or Average | 4272.67 | 21.02 | 3362.50 | 21.42 | 1961.00 | 21.22 |
Minimum of Months | 142.00 | 19.98 | 147.17 | 19.81 | 23.00 | 19.74 |
Maximum of Months | 502.00 | 23.84 | 395.33 | 24.17 | 395.33 | 24.34 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 26.79 | 430.50 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 400.33 | 27.00 | 0.00 | 27.00 |
March | 20.00 | 27.00 | 514.00 | 27.00 | 20.00 | 27.00 |
April | 94.50 | 27.00 | 485.00 | 27.00 | 94.50 | 27.00 |
May | 43.00 | 27.00 | 508.00 | 27.00 | 43.00 | 27.00 |
June | 219.17 | 27.00 | 496.00 | 27.00 | 219.17 | 27.00 |
July | 359.00 | 27.00 | 497.00 | 27.00 | 359.00 | 27.00 |
August | 450.50 | 27.00 | 514.00 | 27.00 | 450.50 | 27.00 |
September | 117.00 | 27.00 | 485.00 | 27.00 | 117.00 | 27.00 |
October | 90.00 | 27.00 | 502.00 | 27.00 | 90.00 | 27.00 |
November | 14.67 | 27.00 | 489.00 | 27.00 | 14.67 | 27.00 |
December | 2.00 | 27.00 | 497.00 | 27.00 | 2.00 | 27.00 |
Annual Sum or Average | 1410.50 | 27.00 | 5817.83 | 27.00 | 1409.83 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 400.33 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 450.50 | 27.00 | 514.00 | 27.00 | 450.50 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 58.00 | 25.11 | 308.50 | 26.57 | 12.33 | 26.45 |
February | 24.50 | 27.00 | 277.83 | 27.00 | 0.00 | 27.00 |
March | 4.00 | 27.00 | 473.83 | 27.00 | 4.00 | 27.00 |
April | 25.50 | 27.00 | 483.00 | 27.00 | 25.50 | 27.00 |
May | 19.00 | 27.00 | 508.00 | 27.00 | 19.00 | 27.00 |
June | 110.00 | 27.00 | 496.00 | 27.00 | 110.00 | 27.00 |
July | 178.33 | 27.00 | 497.00 | 27.00 | 178.33 | 27.00 |
August | 217.50 | 27.00 | 514.00 | 27.00 | 217.50 | 27.00 |
September | 46.83 | 27.00 | 485.00 | 27.00 | 46.83 | 27.00 |
October | 36.33 | 27.00 | 498.00 | 27.00 | 36.33 | 27.00 |
November | 1.00 | 27.00 | 443.50 | 27.00 | 1.00 | 27.00 |
December | 0.00 | 0.00 | 407.50 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 721.00 | 26.85 | 5392.17 | 26.97 | 650.83 | 26.97 |
Minimum of Months | 0.00 | 0.00 | 277.83 | 26.57 | 0.00 | 26.45 |
Maximum of Months | 217.50 | 27.00 | 514.00 | 27.00 | 217.50 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 135.83 | 24.59 | 231.83 | 25.70 | 33.33 | 25.43 |
February | 77.83 | 26.99 | 184.33 | 27.00 | 0.00 | 27.00 |
March | 19.17 | 27.00 | 393.17 | 27.00 | 5.00 | 27.00 |
April | 37.00 | 27.00 | 445.50 | 27.00 | 33.00 | 27.00 |
May | 43.33 | 27.00 | 506.00 | 27.00 | 43.33 | 27.00 |
June | 152.00 | 27.00 | 496.00 | 27.00 | 152.00 | 27.00 |
July | 219.67 | 27.00 | 497.00 | 27.00 | 219.67 | 27.00 |
August | 248.33 | 27.00 | 514.00 | 27.00 | 248.33 | 27.00 |
September | 78.67 | 27.00 | 485.00 | 27.00 | 78.67 | 27.00 |
October | 54.50 | 27.00 | 449.67 | 27.00 | 43.67 | 27.00 |
November | 27.33 | 27.00 | 353.00 | 27.00 | 1.00 | 27.00 |
December | 52.50 | 27.00 | 264.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 1146.17 | 26.71 | 4819.50 | 26.92 | 858.00 | 26.91 |
Minimum of Months | 19.17 | 24.59 | 184.33 | 25.70 | 0.00 | 25.43 |
Maximum of Months | 248.33 | 27.00 | 514.00 | 27.00 | 248.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 245.67 | 27.14 | 502.00 | 27.13 | 245.67 | 27.13 |
February | 0.33 | 20.71 | 453.67 | 24.81 | 0.00 | 24.81 |
March | 265.17 | 25.85 | 494.50 | 25.65 | 264.50 | 25.70 |
April | 251.33 | 26.14 | 485.00 | 25.27 | 251.33 | 25.49 |
May | 413.67 | 27.07 | 508.00 | 27.06 | 413.67 | 27.06 |
June | 406.67 | 26.89 | 495.33 | 26.68 | 406.67 | 26.75 |
July | 497.00 | 26.98 | 497.00 | 26.98 | 497.00 | 26.98 |
August | 514.00 | 27.04 | 514.00 | 27.04 | 514.00 | 27.04 |
September | 485.00 | 27.02 | 485.00 | 27.02 | 485.00 | 27.02 |
October | 175.00 | 25.99 | 501.33 | 25.43 | 175.00 | 25.54 |
November | 414.00 | 25.83 | 484.83 | 25.62 | 414.00 | 25.69 |
December | 235.83 | 25.16 | 497.00 | 24.66 | 235.83 | 24.79 |
Annual Sum or Average | 3903.67 | 26.60 | 5917.67 | 26.25 | 3902.67 | 26.35 |
Minimum of Months | 0.33 | 20.71 | 453.67 | 24.66 | 0.00 | 24.79 |
Maximum of Months | 514.00 | 27.14 | 514.00 | 27.13 | 514.00 | 27.13 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99981 | 18.48702 | 0.67264 | 14.80464 |
February | 454.00000 | 27.00000 | 15.32934 | 0.67789 | 14.89787 |
March | 514.00000 | 27.00000 | 23.37969 | 0.83162 | 19.83442 |
April | 485.00000 | 27.00002 | 28.62641 | 0.93256 | 23.60403 |
May | 508.00000 | 27.00017 | 34.78495 | 0.26573 | 6.70772 |
June | 496.00000 | 27.00028 | 39.47853 | 0.39774 | 8.48271 |
July | 497.00000 | 27.00018 | 41.13683 | 0.47127 | 9.74574 |
August | 514.00000 | 27.00041 | 39.03738 | 0.50690 | 10.49996 |
September | 485.00000 | 27.00042 | 38.86811 | 0.32987 | 7.51975 |
October | 502.00000 | 27.00006 | 32.09342 | 0.92987 | 23.57929 |
November | 489.00000 | 27.00000 | 25.48033 | 0.84544 | 20.32746 |
December | 497.00000 | 27.00000 | 18.64836 | 0.78771 | 18.22197 |
Annual Sum or Average | 5943.00000 | 27.00011 | 29.71451 | 0.63670 | 14.83666 |
Minimum of Months | 454.00000 | 26.99981 | 15.32934 | 0.26573 | 6.70772 |
Maximum of Months | 514.00000 | 27.00042 | 41.13683 | 0.93256 | 23.60403 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.78049 | 18.60869 | 0.52104 | 12.04236 |
February | 454.00000 | 27.00000 | 15.34100 | 0.57614 | 12.31082 |
March | 514.00000 | 27.00000 | 23.38958 | 0.72992 | 16.54486 |
April | 485.00000 | 27.00002 | 28.65270 | 0.82093 | 19.53835 |
May | 508.00000 | 27.00017 | 34.86703 | 0.18624 | 6.05005 |
June | 496.00000 | 27.00029 | 39.58404 | 0.31951 | 7.36851 |
July | 497.00000 | 27.00018 | 41.26304 | 0.37521 | 8.09559 |
August | 514.00000 | 27.00043 | 39.11368 | 0.39604 | 8.47499 |
September | 485.00000 | 27.00042 | 39.04444 | 0.24478 | 6.59572 |
October | 502.00000 | 27.00007 | 32.14968 | 0.85119 | 20.70126 |
November | 489.00000 | 27.00000 | 25.48997 | 0.72195 | 16.31533 |
December | 497.00000 | 27.00000 | 18.65765 | 0.64222 | 13.88165 |
Annual Sum or Average | 5943.00000 | 26.98159 | 29.78237 | 0.53135 | 12.31545 |
Minimum of Months | 454.00000 | 26.78049 | 15.34100 | 0.18624 | 6.05005 |
Maximum of Months | 514.00000 | 27.00043 | 41.26304 | 0.85119 | 20.70126 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.34268 | 18.94643 | 0.36949 | 10.89161 |
February | 454.00000 | 26.99750 | 15.33221 | 0.49683 | 10.68322 |
March | 514.00000 | 27.00000 | 23.38773 | 0.66168 | 14.75100 |
April | 485.00000 | 27.00002 | 28.69709 | 0.77200 | 18.13722 |
May | 508.00000 | 27.00084 | 34.92684 | 0.15895 | 6.16049 |
June | 496.00000 | 27.00030 | 39.58479 | 0.32476 | 7.63877 |
July | 497.00000 | 27.00016 | 41.28170 | 0.39437 | 8.54864 |
August | 514.00000 | 27.00041 | 39.18668 | 0.40695 | 8.84007 |
September | 485.00000 | 27.00045 | 39.10143 | 0.22086 | 6.63313 |
October | 502.00000 | 27.00007 | 32.18427 | 0.79825 | 19.15730 |
November | 489.00000 | 27.00000 | 25.49065 | 0.63961 | 14.11751 |
December | 497.00000 | 27.00000 | 18.65041 | 0.54648 | 11.60548 |
Annual Sum or Average | 5943.00000 | 26.94448 | 29.83376 | 0.48204 | 11.42732 |
Minimum of Months | 454.00000 | 26.34268 | 15.33221 | 0.15895 | 6.16049 |
Maximum of Months | 514.00000 | 27.00084 | 41.28170 | 0.79825 | 19.15730 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.12674 | 30.40958 | 1.02156 | 27.10005 |
February | 454.00000 | 24.80782 | 28.91575 | 0.68774 | 15.05562 |
March | 514.00000 | 25.38272 | 29.58927 | 0.92570 | 23.86679 |
April | 485.00000 | 24.81160 | 32.40244 | 0.99353 | 27.29547 |
May | 508.00000 | 27.06163 | 36.91209 | 0.49266 | 10.21821 |
June | 496.00000 | 26.50663 | 46.17514 | 0.66651 | 15.97489 |
July | 497.00000 | 26.98295 | 43.51397 | 1.02019 | 27.01278 |
August | 514.00000 | 27.03697 | 41.20126 | 1.22982 | 36.77284 |
September | 485.00000 | 27.01877 | 45.46409 | 0.68353 | 15.18387 |
October | 502.00000 | 25.22302 | 38.80588 | 0.95620 | 25.02640 |
November | 489.00000 | 25.39655 | 30.77008 | 0.99808 | 26.71973 |
December | 497.00000 | 24.42711 | 27.86222 | 0.92619 | 23.55481 |
Annual Sum or Average | 5943.00000 | 25.99497 | 36.04245 | 0.88552 | 22.89861 |
Minimum of Months | 454.00000 | 24.42711 | 27.86222 | 0.49266 | 10.21821 |
Maximum of Months | 514.00000 | 27.12674 | 46.17514 | 1.22982 | 36.77284 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.76841 | 23.82180 | 0.18714 | 6.44781 |
February | 454.00000 | 23.76142 | 18.87593 | 0.15323 | 6.12819 |
March | 514.00000 | 24.13468 | 27.43889 | 0.30773 | 7.27788 |
April | 485.00000 | 24.29588 | 34.19058 | 0.39518 | 8.62604 |
May | 508.00000 | 24.38821 | 40.37343 | -0.4037 | 8.89085 |
June | 496.00000 | 24.41270 | 46.17750 | -0.3257 | 7.93982 |
July | 497.00000 | 24.57928 | 48.01797 | -0.2513 | 7.54975 |
August | 514.00000 | 24.48241 | 46.47525 | -0.2721 | 7.62781 |
September | 485.00000 | 24.54996 | 44.41110 | -0.2716 | 7.72708 |
October | 502.00000 | 24.58387 | 37.41710 | 0.51908 | 11.31147 |
November | 489.00000 | 24.47485 | 29.85398 | 0.42987 | 9.53260 |
December | 497.00000 | 24.25303 | 21.66267 | 0.30682 | 7.33589 |
Annual Sum or Average | 5943.00000 | 24.31023 | 35.01075 | 0.06285 | 8.04383 |
Minimum of Months | 454.00000 | 23.76142 | 18.87593 | -0.4037 | 6.12819 |
Maximum of Months | 514.00000 | 24.58387 | 48.01797 | 0.51908 | 11.31147 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.62686 | 23.73943 | 0.14022 | 6.24528 |
February | 454.00000 | 23.78162 | 20.11281 | 0.15666 | 5.92287 |
March | 514.00000 | 24.08383 | 28.81327 | 0.31678 | 7.39426 |
April | 485.00000 | 24.17859 | 35.64444 | 0.40484 | 8.78221 |
May | 508.00000 | 24.18411 | 44.12752 | -0.3998 | 8.78609 |
June | 496.00000 | 24.24344 | 52.19985 | -0.2920 | 7.15964 |
July | 497.00000 | 24.24840 | 55.03712 | -0.2573 | 6.62179 |
August | 514.00000 | 24.21493 | 52.90452 | -0.2682 | 6.71973 |
September | 485.00000 | 24.30117 | 49.57255 | -0.3021 | 7.43272 |
October | 502.00000 | 24.29464 | 41.81165 | 0.48476 | 10.38814 |
November | 489.00000 | 24.31600 | 31.67050 | 0.39385 | 8.82349 |
December | 497.00000 | 24.12474 | 22.98859 | 0.27954 | 6.84178 |
Annual Sum or Average | 5943.00000 | 24.13494 | 38.35514 | 0.05306 | 7.60195 |
Minimum of Months | 454.00000 | 23.62686 | 20.11281 | -0.3998 | 5.92287 |
Maximum of Months | 514.00000 | 24.31600 | 55.03712 | 0.48476 | 10.38814 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.25386 | 25.09396 | -0.2133 | 9.09130 |
February | 454.00000 | 22.69039 | 19.82132 | -0.1320 | 6.86562 |
March | 514.00000 | 23.49359 | 29.74852 | 0.14456 | 6.12537 |
April | 485.00000 | 23.68644 | 36.67307 | 0.25507 | 7.02574 |
May | 508.00000 | 23.96548 | 44.67137 | -0.5017 | 10.85545 |
June | 496.00000 | 24.14919 | 52.68888 | -0.3543 | 8.02378 |
July | 497.00000 | 24.19173 | 55.69885 | -0.3133 | 7.37546 |
August | 514.00000 | 24.21906 | 53.32661 | -0.3135 | 7.44028 |
September | 485.00000 | 24.09119 | 50.16089 | -0.4060 | 8.98933 |
October | 502.00000 | 23.91655 | 42.82609 | 0.36740 | 8.51311 |
November | 489.00000 | 23.48686 | 33.12392 | 0.16078 | 6.71954 |
December | 497.00000 | 22.99876 | 24.13292 | -0.0242 | 6.02456 |
Annual Sum or Average | 5943.00000 | 23.60199 | 39.14026 | -0.1114 | 7.76283 |
Minimum of Months | 454.00000 | 22.25386 | 19.82132 | -0.5017 | 6.02456 |
Maximum of Months | 514.00000 | 24.21906 | 55.69885 | 0.36740 | 10.85545 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.79243 | 26.52008 | -0.5924 | 16.32061 |
February | 454.00000 | 21.02890 | 20.96846 | -0.5627 | 14.84138 |
March | 514.00000 | 22.06458 | 31.96463 | -0.2147 | 8.38968 |
April | 485.00000 | 22.66196 | 38.44102 | 0.00013 | 7.55720 |
May | 508.00000 | 23.50579 | 46.16144 | -0.6527 | 15.83945 |
June | 496.00000 | 24.03758 | 53.37751 | -0.3677 | 8.52065 |
July | 497.00000 | 24.19294 | 55.94692 | -0.2799 | 7.06814 |
August | 514.00000 | 24.15558 | 53.94048 | -0.3051 | 7.56632 |
September | 485.00000 | 23.71104 | 51.83353 | -0.5272 | 12.45547 |
October | 502.00000 | 22.87881 | 45.65371 | 0.11243 | 8.35871 |
November | 489.00000 | 21.79655 | 36.07556 | -0.2661 | 9.54226 |
December | 497.00000 | 21.02015 | 26.29125 | -0.5310 | 13.71891 |
Annual Sum or Average | 5943.00000 | 22.66720 | 40.74169 | -0.3477 | 10.82022 |
Minimum of Months | 454.00000 | 20.79243 | 20.96846 | -0.6527 | 7.06814 |
Maximum of Months | 514.00000 | 24.19294 | 55.94692 | 0.11243 | 16.32061 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.89090 | 25.38916 | -0.5391 | 13.05926 |
February | 454.00000 | 20.99927 | 20.44470 | -0.5402 | 12.59823 |
March | 514.00000 | 22.08374 | 30.60428 | -0.1765 | 7.32489 |
April | 485.00000 | 22.95063 | 36.90032 | 0.10024 | 7.04450 |
May | 508.00000 | 23.72693 | 44.22968 | -0.5418 | 12.57785 |
June | 496.00000 | 24.16817 | 52.09862 | -0.2674 | 7.08944 |
July | 497.00000 | 24.35141 | 54.67654 | -0.1535 | 6.16767 |
August | 514.00000 | 24.19462 | 52.48243 | -0.2235 | 6.57588 |
September | 485.00000 | 23.91677 | 50.16808 | -0.4207 | 10.05045 |
October | 502.00000 | 23.27268 | 42.96031 | 0.22960 | 7.89298 |
November | 489.00000 | 22.27153 | 33.47827 | -0.1151 | 7.26150 |
December | 497.00000 | 21.42213 | 24.85709 | -0.3880 | 8.99616 |
Annual Sum or Average | 5943.00000 | 22.86765 | 39.16149 | -0.2515 | 8.86200 |
Minimum of Months | 454.00000 | 20.89090 | 20.44470 | -0.5418 | 6.16767 |
Maximum of Months | 514.00000 | 24.35141 | 54.67654 | 0.22960 | 13.05926 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.81452 | 25.11006 | -0.5378 | 12.82541 |
February | 454.00000 | 21.10708 | 19.91604 | -0.4847 | 11.52955 |
March | 514.00000 | 21.86233 | 30.62577 | -0.1807 | 7.87990 |
April | 485.00000 | 22.59515 | 37.29034 | 0.07899 | 8.25697 |
May | 508.00000 | 23.32963 | 45.11918 | -0.5594 | 15.89005 |
June | 496.00000 | 23.77665 | 53.06401 | -0.3108 | 9.18772 |
July | 497.00000 | 23.94254 | 55.64242 | -0.2039 | 8.23425 |
August | 514.00000 | 23.80649 | 53.41154 | -0.2431 | 8.39789 |
September | 485.00000 | 23.55093 | 50.99435 | -0.4392 | 12.90984 |
October | 502.00000 | 22.94144 | 43.59351 | 0.22021 | 8.56726 |
November | 489.00000 | 21.90823 | 33.80146 | -0.1621 | 7.50447 |
December | 497.00000 | 21.22146 | 24.64008 | -0.4152 | 9.56451 |
Annual Sum or Average | 5943.00000 | 22.58237 | 39.57832 | -0.2688 | 10.05404 |
Minimum of Months | 454.00000 | 20.81452 | 19.91604 | -0.5594 | 7.50447 |
Maximum of Months | 514.00000 | 23.94254 | 55.64242 | 0.22021 | 15.89005 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.32676 | 24.71074 | -0.4020 | 12.91568 |
February | 454.00000 | 21.84199 | 19.34409 | -0.2952 | 11.35311 |
March | 514.00000 | 22.25085 | 30.00668 | -0.0774 | 8.68623 |
April | 485.00000 | 22.71967 | 37.06821 | 0.09561 | 8.56056 |
May | 508.00000 | 23.33607 | 45.12540 | -0.6160 | 16.41041 |
June | 496.00000 | 23.91525 | 52.70092 | -0.3122 | 8.63861 |
July | 497.00000 | 24.17612 | 55.00334 | -0.1640 | 7.10562 |
August | 514.00000 | 24.08564 | 52.56357 | -0.1586 | 7.31531 |
September | 485.00000 | 23.88013 | 50.01865 | -0.3128 | 11.07419 |
October | 502.00000 | 23.53937 | 42.10068 | 0.40017 | 11.77903 |
November | 489.00000 | 22.47821 | 32.88680 | -0.0134 | 8.61746 |
December | 497.00000 | 21.94333 | 23.93872 | -0.2288 | 9.99311 |
Annual Sum or Average | 5943.00000 | 22.96598 | 38.93303 | -0.1735 | 10.20225 |
Minimum of Months | 454.00000 | 21.32676 | 19.34409 | -0.6160 | 7.10562 |
Maximum of Months | 514.00000 | 24.17612 | 55.00334 | 0.40017 | 16.41041 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.16793 | 24.50985 | -0.4173 | 10.45640 |
February | 454.00000 | 21.42738 | 19.43707 | -0.3716 | 9.80963 |
March | 514.00000 | 22.42502 | 29.35718 | 0.00580 | 7.36671 |
April | 485.00000 | 23.22925 | 35.76401 | 0.28394 | 9.51077 |
May | 508.00000 | 23.45332 | 44.62021 | -0.4767 | 13.34788 |
June | 496.00000 | 24.11487 | 51.78967 | -0.1174 | 7.76674 |
July | 497.00000 | 24.37077 | 54.04048 | 0.03556 | 7.08656 |
August | 514.00000 | 24.30036 | 51.71782 | 0.04511 | 6.66264 |
September | 485.00000 | 23.70818 | 50.35632 | -0.3365 | 10.95139 |
October | 502.00000 | 23.24109 | 42.64168 | 0.33283 | 9.87040 |
November | 489.00000 | 22.38635 | 32.67026 | -0.0123 | 7.08888 |
December | 497.00000 | 21.95344 | 23.50352 | -0.1863 | 7.05625 |
Annual Sum or Average | 5943.00000 | 22.99313 | 38.50669 | -0.0996 | 8.90482 |
Minimum of Months | 454.00000 | 21.16793 | 19.43707 | -0.4767 | 6.66264 |
Maximum of Months | 514.00000 | 24.37077 | 54.04048 | 0.33283 | 13.34788 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.03639 | 25.59316 | -0.8264 | 22.22349 |
February | 454.00000 | 20.16933 | 19.99653 | -0.8131 | 21.22213 |
March | 514.00000 | 20.83696 | 31.56379 | -0.5074 | 11.93606 |
April | 485.00000 | 21.59285 | 38.80419 | -0.2355 | 8.37881 |
May | 508.00000 | 22.72810 | 46.43709 | -0.8617 | 23.33203 |
June | 496.00000 | 23.69310 | 54.10249 | -0.4251 | 10.25026 |
July | 497.00000 | 24.03357 | 57.28021 | -0.2613 | 7.39703 |
August | 514.00000 | 23.88896 | 54.49672 | -0.3398 | 8.81752 |
September | 485.00000 | 22.99777 | 52.77868 | -0.7175 | 18.62046 |
October | 502.00000 | 21.86761 | 45.92693 | -0.0992 | 7.85020 |
November | 489.00000 | 20.72742 | 35.28276 | -0.5166 | 12.74876 |
December | 497.00000 | 20.25583 | 25.33707 | -0.7413 | 18.29579 |
Annual Sum or Average | 5943.00000 | 21.91712 | 40.78298 | -0.5268 | 14.20732 |
Minimum of Months | 454.00000 | 20.03639 | 19.99653 | -0.8617 | 7.39703 |
Maximum of Months | 514.00000 | 24.03357 | 57.28021 | -0.0992 | 23.33203 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.93074 | 25.07554 | -0.8279 | 22.72749 |
February | 385.00000 | 20.25834 | 19.22640 | -0.7507 | 19.67418 |
March | 433.00000 | 21.14368 | 30.63035 | -0.4002 | 11.23303 |
April | 410.00000 | 22.07249 | 37.44322 | -0.0845 | 8.88887 |
May | 430.00000 | 22.96268 | 45.55921 | -0.7036 | 21.45446 |
June | 418.00000 | 23.61553 | 54.19462 | -0.3785 | 11.36374 |
July | 422.00000 | 24.04536 | 57.12636 | -0.1825 | 9.01985 |
August | 433.00000 | 23.93304 | 54.12338 | -0.2270 | 9.06417 |
September | 410.00000 | 23.18745 | 52.13376 | -0.5818 | 17.41473 |
October | 427.00000 | 22.24696 | 44.44536 | 0.02773 | 8.26811 |
November | 417.00000 | 20.92115 | 34.42075 | -0.4463 | 11.82670 |
December | 422.00000 | 20.28913 | 24.85783 | -0.7072 | 17.51499 |
Annual Sum or Average | 5034.00000 | 22.06251 | 40.06895 | -0.4366 | 14.00233 |
Minimum of Months | 385.00000 | 19.93074 | 19.22640 | -0.8279 | 8.26811 |
Maximum of Months | 433.00000 | 24.04536 | 57.12636 | 0.02773 | 22.72749 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.84116 | 24.65249 | -0.5531 | 17.58862 |
February | 454.00000 | 21.40582 | 18.75098 | -0.4181 | 14.64574 |
March | 514.00000 | 21.86237 | 29.84194 | -0.1899 | 10.43726 |
April | 485.00000 | 22.29917 | 37.27777 | -0.0260 | 9.24772 |
May | 508.00000 | 23.02889 | 45.70738 | -0.7283 | 20.54325 |
June | 496.00000 | 23.75713 | 53.84906 | -0.3758 | 10.15884 |
July | 497.00000 | 24.15590 | 56.75172 | -0.1833 | 7.66521 |
August | 514.00000 | 24.11482 | 53.52634 | -0.1678 | 8.00276 |
September | 485.00000 | 23.66996 | 50.66171 | -0.3852 | 13.37452 |
October | 502.00000 | 23.29884 | 42.37501 | 0.34193 | 11.92077 |
November | 489.00000 | 21.93608 | 33.09950 | -0.1607 | 10.39576 |
December | 497.00000 | 21.41461 | 23.87912 | -0.3868 | 13.44600 |
Annual Sum or Average | 5943.00000 | 22.65881 | 39.34887 | -0.2688 | 12.27720 |
Minimum of Months | 454.00000 | 20.84116 | 18.75098 | -0.7283 | 7.66521 |
Maximum of Months | 514.00000 | 24.15590 | 56.75172 | 0.34193 | 20.54325 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.25588 | 25.04534 | -0.7352 | 19.47508 |
February | 454.00000 | 20.52013 | 19.38680 | -0.6803 | 17.82819 |
March | 514.00000 | 21.36933 | 30.42419 | -0.3249 | 10.30166 |
April | 485.00000 | 21.94179 | 37.89683 | -0.0913 | 8.96912 |
May | 508.00000 | 22.77471 | 46.26165 | -0.7479 | 22.07360 |
June | 496.00000 | 23.66120 | 53.86156 | -0.3225 | 10.95750 |
July | 497.00000 | 24.01634 | 56.87493 | -0.1599 | 8.66535 |
August | 514.00000 | 23.97489 | 53.86835 | -0.1702 | 8.65828 |
September | 485.00000 | 23.01947 | 52.47946 | -0.6111 | 17.94970 |
October | 502.00000 | 22.24754 | 44.81761 | 0.05562 | 8.58697 |
November | 489.00000 | 20.93395 | 34.67665 | -0.4363 | 11.28898 |
December | 497.00000 | 20.53105 | 24.68422 | -0.6386 | 15.29881 |
Annual Sum or Average | 5943.00000 | 22.11817 | 40.17158 | -0.4030 | 13.30321 |
Minimum of Months | 454.00000 | 20.25588 | 19.38680 | -0.7479 | 8.58697 |
Maximum of Months | 514.00000 | 24.01634 | 56.87493 | 0.05562 | 22.07360 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.82810 | 25.75064 | -0.9348 | 26.63765 |
February | 454.00000 | 19.94044 | 19.96784 | -0.9344 | 26.10402 |
March | 514.00000 | 20.43084 | 32.04894 | -0.6510 | 16.59172 |
April | 485.00000 | 21.08506 | 39.68370 | -0.3802 | 11.10584 |
May | 508.00000 | 22.14847 | 48.13017 | -1.0409 | 31.26308 |
June | 496.00000 | 23.29194 | 55.80771 | -0.5209 | 13.48219 |
July | 497.00000 | 23.75663 | 58.63629 | -0.3112 | 8.87033 |
August | 514.00000 | 23.56544 | 56.03885 | -0.4075 | 11.14994 |
September | 485.00000 | 22.44647 | 54.99266 | -0.8821 | 25.03490 |
October | 502.00000 | 21.16082 | 48.06339 | -0.2809 | 10.81151 |
November | 489.00000 | 20.21513 | 36.02764 | -0.6941 | 18.19868 |
December | 497.00000 | 19.87721 | 25.73213 | -0.9059 | 25.08183 |
Annual Sum or Average | 5943.00000 | 21.49280 | 41.89712 | -0.6600 | 18.64048 |
Minimum of Months | 454.00000 | 19.82810 | 19.96784 | -1.0409 | 8.87033 |
Maximum of Months | 514.00000 | 23.75663 | 58.63629 | -0.2809 | 31.26308 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.84176 | 25.68417 | -0.8969 | 25.46499 |
February | 454.00000 | 20.05870 | 19.75084 | -0.8512 | 23.15917 |
March | 514.00000 | 20.79217 | 31.42566 | -0.5176 | 14.68200 |
April | 485.00000 | 21.82513 | 38.03611 | -0.1652 | 10.60738 |
May | 508.00000 | 22.76916 | 46.66902 | -0.7625 | 24.47165 |
June | 496.00000 | 23.54548 | 54.95544 | -0.3671 | 11.72433 |
July | 497.00000 | 24.00519 | 57.53001 | -0.1502 | 9.03515 |
August | 514.00000 | 23.89664 | 54.68620 | -0.1904 | 9.01131 |
September | 485.00000 | 23.02992 | 53.22213 | -0.6231 | 19.25314 |
October | 502.00000 | 21.88888 | 46.07272 | -0.0678 | 10.09020 |
November | 489.00000 | 20.40578 | 35.56866 | -0.6116 | 16.34954 |
December | 497.00000 | 19.96441 | 25.54772 | -0.8489 | 23.02014 |
Annual Sum or Average | 5943.00000 | 21.85038 | 40.91520 | -0.5018 | 16.35486 |
Minimum of Months | 454.00000 | 19.84176 | 19.75084 | -0.8969 | 9.01131 |
Maximum of Months | 514.00000 | 24.00519 | 57.53001 | -0.0678 | 25.46499 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.39612 | 25.09959 | -0.7069 | 21.88074 |
February | 454.00000 | 20.87441 | 19.00070 | -0.5979 | 19.21104 |
March | 514.00000 | 21.31097 | 30.56981 | -0.3609 | 14.30304 |
April | 485.00000 | 21.78992 | 38.18082 | -0.1709 | 11.35988 |
May | 508.00000 | 22.50671 | 47.29956 | -0.8923 | 27.74698 |
June | 496.00000 | 23.38641 | 55.49074 | -0.4637 | 13.28262 |
July | 497.00000 | 23.87979 | 58.12142 | -0.2336 | 9.25971 |
August | 514.00000 | 23.84088 | 54.96368 | -0.2233 | 10.01079 |
September | 485.00000 | 23.21207 | 52.62405 | -0.5243 | 18.29833 |
October | 502.00000 | 22.67805 | 44.25133 | 0.17781 | 12.46595 |
November | 489.00000 | 21.13853 | 34.24732 | -0.3906 | 14.23757 |
December | 497.00000 | 20.71827 | 24.64855 | -0.6112 | 19.05482 |
Annual Sum or Average | 5943.00000 | 22.15535 | 40.53176 | -0.4154 | 15.91175 |
Minimum of Months | 454.00000 | 20.39612 | 19.00070 | -0.8923 | 9.25971 |
Maximum of Months | 514.00000 | 23.87979 | 58.12142 | 0.17781 | 27.74698 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.97896 | 25.41467 | -0.8472 | 23.79343 |
February | 454.00000 | 20.25730 | 19.48351 | -0.7944 | 21.99083 |
March | 514.00000 | 21.02722 | 30.83069 | -0.4440 | 13.62627 |
April | 485.00000 | 21.63600 | 38.37882 | -0.1885 | 10.81656 |
May | 508.00000 | 22.50086 | 47.21501 | -0.8387 | 26.64621 |
June | 496.00000 | 23.46269 | 55.05168 | -0.3632 | 12.83221 |
July | 497.00000 | 23.88122 | 57.89908 | -0.1724 | 9.71561 |
August | 514.00000 | 23.80505 | 55.00451 | -0.1973 | 10.07479 |
September | 485.00000 | 22.76349 | 53.88057 | -0.6913 | 21.41088 |
October | 502.00000 | 21.85207 | 46.17260 | -0.0571 | 10.35688 |
November | 489.00000 | 20.49916 | 35.27298 | -0.5834 | 15.48638 |
December | 497.00000 | 20.13809 | 25.16534 | -0.7895 | 20.86258 |
Annual Sum or Average | 5943.00000 | 21.83125 | 40.96749 | -0.4948 | 16.42457 |
Minimum of Months | 454.00000 | 19.97896 | 19.48351 | -0.8472 | 9.71561 |
Maximum of Months | 514.00000 | 23.88122 | 57.89908 | -0.0571 | 26.64621 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.160001E+11 | 141814.33 | 10-JAN-22:01 | 228.60 | 0.756260E+11 | 0.00 | 0.916261E+11 | 1.43 | 6.27 | 10-JAN-22:01 | 0.00 | 0.00 |
February | 0.457238E+11 | 153095.00 | 27-FEB-17:02 | 262.91 | 0.212823E+12 | 0.00 | 0.258547E+12 | 1.81 | 6.61 | 27-FEB-17:02 | 0.00 | 0.00 |
March | 0.106466E+12 | 179687.97 | 27-MAR-16:00 | 664.35 | 0.531423E+12 | 0.00 | 0.637889E+12 | 4.32 | 6.89 | 27-MAR-16:00 | 0.00 | 0.00 |
April | 0.152305E+12 | 267678.68 | 07-APR-13:10 | 633.20 | 0.833231E+12 | 0.00 | 0.985536E+12 | 4.45 | 7.05 | 28-APR-05:04 | 0.00 | 0.00 |
May | 0.185530E+12 | 275535.50 | 30-MAY-10:20 | 473.86 | 0.105548E+13 | 0.00 | 0.124101E+13 | 3.43 | 7.02 | 29-MAY-14:13 | 0.00 | 0.00 |
June | 0.313099E+12 | 280673.09 | 18-JUN-17:23 | 624.45 | 0.197073E+13 | 0.00 | 0.228383E+13 | 5.11 | 7.12 | 26-JUN-05:03 | 0.00 | 0.00 |
July | 0.393616E+12 | 291622.70 | 09-JUL-10:43 | 733.08 | 0.242120E+13 | 0.00 | 0.281481E+13 | 5.67 | 7.09 | 12-JUL-04:12 | 0.00 | 0.00 |
August | 0.384034E+12 | 291381.67 | 04-AUG-05:25 | 735.11 | 0.236178E+13 | 0.00 | 0.274582E+13 | 5.73 | 7.17 | 25-AUG-12:20 | 0.00 | 0.00 |
September | 0.226242E+12 | 283881.20 | 14-SEP-04:14 | 485.59 | 0.138489E+13 | 0.00 | 0.161113E+13 | 3.88 | 7.11 | 18-SEP-05:05 | 0.00 | 0.00 |
October | 0.205778E+12 | 270874.32 | 24-OCT-16:00 | 489.89 | 0.120860E+13 | 0.00 | 0.141438E+13 | 3.62 | 7.13 | 22-OCT-12:23 | 0.00 | 0.00 |
November | 0.111370E+12 | 205794.45 | 10-NOV-06:03 | 622.13 | 0.567083E+12 | 0.00 | 0.678453E+12 | 4.21 | 7.00 | 10-NOV-06:03 | 0.00 | 0.00 |
December | 0.735703E+11 | 157529.78 | 08-DEC-15:52 | 598.62 | 0.354495E+12 | 0.00 | 0.428065E+12 | 3.85 | 6.69 | 20-DEC-14:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.221374E+13 | 6551.78 | 0.129774E+14 | 0.00 | 0.151911E+14 | 3.97 | 0.00 | 0.00 | ||||
Minimum of Months | 0.160001E+11 | 141814.33 | 228.60 | 0.756260E+11 | 0.00 | 0.916261E+11 | 1.43 | 6.27 | 0.00 | 0.00 | ||
Maximum of Months | 0.393616E+12 | 291622.70 | 735.11 | 0.242120E+13 | 0.00 | 0.281481E+13 | 5.73 | 7.17 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.127523E+10 | 195237.13 | 07-APR-14:43 | 2.36 | 0.833770E+10 | 0.00 | 0.961294E+10 | 0.02 | 6.98 | 07-APR-14:43 | 0.00 | 0.00 |
May | 0.403000E+10 | 191981.95 | 31-MAY-12:05 | 7.33 | 0.256879E+11 | 0.00 | 0.297179E+11 | 0.06 | 6.73 | 30-MAY-14:05 | 0.00 | 0.00 |
June | 0.520564E+11 | 279066.24 | 16-JUN-05:03 | 90.02 | 0.329437E+12 | 0.00 | 0.381493E+12 | 0.79 | 6.92 | 22-JUN-05:05 | 0.00 | 0.00 |
July | 0.131257E+12 | 289715.93 | 22-JUL-05:05 | 211.01 | 0.830378E+12 | 0.00 | 0.961635E+12 | 1.79 | 6.85 | 11-JUL-12:05 | 0.00 | 0.00 |
August | 0.151936E+12 | 276415.55 | 07-AUG-04:14 | 238.14 | 0.970864E+12 | 0.00 | 0.112280E+13 | 2.04 | 6.94 | 25-AUG-04:14 | 0.00 | 0.00 |
September | 0.234975E+11 | 283881.20 | 14-SEP-04:14 | 40.25 | 0.148907E+12 | 0.00 | 0.172404E+12 | 0.35 | 6.95 | 02-SEP-04:14 | 0.00 | 0.00 |
October | 0.817822E+10 | 210924.89 | 24-OCT-10:14 | 14.74 | 0.526395E+11 | 0.00 | 0.608178E+11 | 0.13 | 6.85 | 12-OCT-15:51 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.372230E+12 | 603.86 | 0.236625E+13 | 0.00 | 0.273848E+13 | 0.44 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.151936E+12 | 289715.93 | 238.14 | 0.970864E+12 | 0.00 | 0.112280E+13 | 2.04 | 6.98 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 8231098.93 | 48.35 | 850.64 | 24-JAN-06:06 | 640922.62 | 26-JAN-22:15 | 21.21 | 21.10 | 14.11 |
February | 4776730.73 | 55.15 | 90.40 | 24-FEB-13:55 | 978026.22 | 24-FEB-13:55 | 21.46 | 21.15 | 32.05 |
March | 0.542544E+09 | 206.89 | 21854.96 | 27-MAR-16:00 | 1438754.72 | 27-MAR-16:00 | 21.63 | 20.95 | 62.07 |
April | 0.314803E+10 | 370.39 | 28730.63 | 07-APR-11:40 | 2065177.40 | 07-APR-12:00 | 22.09 | 21.04 | 73.17 |
May | 0.100419E+11 | 446.97 | 28730.63 | 18-MAY-09:50 | 2010374.64 | 30-MAY-11:40 | 22.47 | 21.24 | 57.90 |
June | 0.467209E+11 | 623.89 | 28730.63 | 01-JUN-09:11 | 2114558.89 | 22-JUN-09:50 | 24.71 | 22.40 | 77.50 |
July | 0.724617E+11 | 732.08 | 28730.63 | 01-JUL-04:11 | 2075654.30 | 11-JUL-09:30 | 26.79 | 24.04 | 83.06 |
August | 0.605700E+11 | 718.05 | 28730.63 | 01-AUG-00:03 | 2094118.59 | 25-AUG-10:20 | 25.97 | 23.24 | 88.14 |
September | 0.259031E+11 | 464.85 | 28730.63 | 01-SEP-03:00 | 1958577.99 | 15-SEP-14:40 | 23.49 | 21.85 | 60.31 |
October | 0.147181E+11 | 475.86 | 28730.63 | 02-OCT-12:20 | 2040054.46 | 13-OCT-14:30 | 22.95 | 21.56 | 61.50 |
November | 0.826093E+09 | 251.97 | 11737.34 | 10-NOV-09:58 | 1453901.13 | 03-NOV-13:56 | 21.77 | 21.04 | 62.61 |
December | 11606280.68 | 102.86 | 929.03 | 20-DEC-13:48 | 1133525.65 | 20-DEC-13:48 | 21.42 | 20.94 | 51.00 |
Annual Sum or Average | 0.234957E+12 | 4497.30 | 23.01 | 21.72 | 60.43 | ||||
Minimum of Months | 4776730.73 | 48.35 | 90.40 | 640922.62 | 21.21 | 20.94 | 14.11 | ||
Maximum of Months | 0.724617E+11 | 732.08 | 28730.63 | 2114558.89 | 26.79 | 24.04 | 88.14 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 21.21 | 21.21 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 21.46 | 21.46 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 21.63 | 21.63 | 0.00 |
April | 0.117466E+09 | 1.28 | 28730.63 | 07-APR-13:30 | 1761917.11 | 07-APR-14:20 | 22.09 | 22.08 | 0.17 |
May | 0.749302E+09 | 7.25 | 28730.63 | 30-MAY-10:00 | 1592536.62 | 30-MAY-14:00 | 22.47 | 22.44 | 0.87 |
June | 0.147822E+11 | 142.97 | 28730.63 | 01-JUN-10:05 | 1676175.95 | 01-JUN-15:30 | 24.71 | 23.97 | 14.98 |
July | 0.364791E+11 | 352.69 | 28730.63 | 01-JUL-05:04 | 1697900.24 | 20-JUL-05:05 | 26.79 | 24.98 | 35.29 |
August | 0.295369E+11 | 287.79 | 28730.63 | 01-AUG-04:18 | 1941566.12 | 30-AUG-15:00 | 25.97 | 24.51 | 32.34 |
September | 0.695942E+10 | 67.29 | 28730.63 | 01-SEP-04:13 | 1595764.64 | 07-SEP-05:05 | 23.49 | 23.14 | 6.96 |
October | 0.145560E+10 | 14.11 | 28730.63 | 03-OCT-11:05 | 1731845.26 | 13-OCT-15:11 | 22.95 | 22.89 | 1.75 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 21.77 | 21.77 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 21.42 | 21.42 | 0.00 |
Annual Sum or Average | 0.900800E+11 | 873.38 | 23.01 | 22.63 | 7.78 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.21 | 21.21 | 0.00 | ||
Maximum of Months | 0.364791E+11 | 352.69 | 28730.63 | 1941566.12 | 26.79 | 24.98 | 35.29 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.701354E+12 | 0.00 | 599.41 | 3340522.95 | 02-JAN-04:01 | 0.00 | 32.93 | 66.08 | 1.66 | 0.00 | 0.08 | 0.97 | 02-JAN-04:01 |
February | 0.583586E+12 | 0.00 | 520.10 | 2815692.34 | 10-FEB-05:01 | 0.00 | 33.74 | 66.26 | 1.48 | 0.00 | 0.07 | 0.82 | 10-FEB-05:01 |
March | 0.212508E+12 | 0.00 | 421.23 | 2804537.30 | 29-MAR-04:11 | 0.00 | 26.03 | 51.00 | 0.46 | 0.00 | 0.02 | 0.82 | 29-MAR-04:11 |
April | 0.784266E+11 | 0.00 | 255.37 | 2639959.14 | 19-APR-04:11 | 0.00 | 23.77 | 38.95 | 0.18 | 0.00 | 0.01 | 0.77 | 19-APR-04:11 |
May | 0.101149E+11 | 0.00 | 115.93 | 2083244.94 | 01-MAY-05:01 | 0.00 | 21.63 | 28.40 | 0.02 | 0.00 | 0.00 | 0.61 | 01-MAY-05:01 |
June | 0.174342E+09 | 0.00 | 15.96 | 34709.11 | 07-JUN-05:10 | 0.00 | 20.74 | 21.73 | 0.00 | 0.00 | 0.00 | 0.01 | 07-JUN-05:10 |
July | 369854.97 | 0.00 | 0.19 | 1457.26 | 04-JUL-17:42 | 0.00 | 20.63 | 20.64 | 0.00 | 0.00 | 0.00 | 0.00 | 04-JUL-17:42 |
August | 43571249.72 | 0.00 | 6.74 | 7258.58 | 08-AUG-05:10 | 0.00 | 20.66 | 21.07 | 0.00 | 0.00 | 0.00 | 0.00 | 08-AUG-05:10 |
September | 0.414046E+10 | 0.00 | 73.89 | 232138.10 | 30-SEP-05:02 | 0.00 | 20.57 | 25.17 | 0.01 | 0.00 | 0.00 | 0.07 | 30-SEP-05:02 |
October | 0.314769E+11 | 0.00 | 198.65 | 2206892.16 | 31-OCT-05:01 | 0.00 | 22.61 | 34.00 | 0.07 | 0.00 | 0.00 | 0.64 | 31-OCT-05:01 |
November | 0.200653E+12 | 0.00 | 417.21 | 2986541.48 | 24-NOV-06:01 | 0.00 | 26.91 | 51.14 | 0.47 | 0.00 | 0.02 | 0.87 | 24-NOV-06:01 |
December | 0.366231E+12 | 0.00 | 530.00 | 2593581.71 | 27-DEC-05:11 | 0.00 | 30.30 | 60.49 | 0.82 | 0.00 | 0.04 | 0.76 | 27-DEC-05:11 |
Annual Sum or Average | 0.218871E+13 | 0.00 | 3154.68 | 0.00 | 25.00 | 40.27 | 0.43 | 0.00 | 0.02 | ||||
Minimum of Months | 369854.97 | 0.00 | 0.19 | 1457.26 | 0.00 | 20.57 | 20.64 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.701354E+12 | 0.00 | 599.41 | 3340522.95 | 0.00 | 33.74 | 66.26 | 1.66 | 0.00 | 0.08 | 0.97 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.125085E+11 | 0.00 | 223.73 | 0.125085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100785.02 | 21-JAN-06:01 | 100785.02 | 21-JAN-06:01 | 0.00 | 0.00 | 0.00 |
February | 0.104330E+11 | 0.00 | 185.84 | 0.104330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102752.64 | 24-FEB-06:01 | 102752.64 | 24-FEB-06:01 | 0.00 | 0.00 | 0.00 |
March | 0.375796E+11 | 0.00 | 370.39 | 0.374502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114321.62 | 06-MAR-06:02 | 114321.62 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.633834E+11 | 0.00 | 418.24 | 0.633584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 137104.64 | 28-APR-04:12 | 130469.85 | 07-APR-14:30 | 0.00 | 0.00 | 0.00 |
May | 0.951743E+11 | 0.00 | 454.49 | 0.913979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 197949.22 | 19-MAY-04:12 | 146875.58 | 30-MAY-04:12 | 0.00 | 0.00 | 0.00 |
June | 0.159790E+12 | 0.00 | 465.69 | 0.132383E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 230931.57 | 13-JUN-04:11 | 162847.11 | 26-JUN-04:11 | 0.00 | 0.00 | 0.00 |
July | 0.223199E+12 | 0.00 | 538.70 | 0.165699E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 277125.24 | 14-JUL-05:02 | 188809.37 | 14-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.228441E+12 | 0.00 | 570.17 | 0.186759E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 281832.57 | 02-AUG-05:02 | 188694.88 | 02-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.127909E+12 | 0.00 | 433.47 | 0.113336E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 248927.55 | 22-SEP-04:11 | 184409.19 | 05-SEP-04:11 | 0.00 | 0.00 | 0.00 |
October | 0.944193E+11 | 0.00 | 427.53 | 0.872656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 222053.33 | 25-OCT-04:11 | 143015.30 | 25-OCT-04:11 | 0.00 | 0.00 | 0.00 |
November | 0.420371E+11 | 0.00 | 353.34 | 0.418952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138802.47 | 10-NOV-06:01 | 116395.47 | 10-NOV-05:11 | 0.00 | 0.00 | 0.00 |
December | 0.231118E+11 | 0.00 | 308.56 | 0.231118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104469.23 | 18-DEC-06:01 | 104469.23 | 18-DEC-06:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111799E+13 | 0.00 | 4750.17 | 0.965597E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.104330E+11 | 0.00 | 185.84 | 0.104330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100785.02 | 100785.02 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.228441E+12 | 0.00 | 570.17 | 0.186759E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 281832.57 | 188809.37 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.386193E+11 | 0.00 | 134.19 | 0.386193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 249466.95 | 20-JAN-15:30 | 249466.95 | 20-JAN-15:30 | 0.00 | 0.00 | 0.00 |
February | 0.334374E+11 | 0.00 | 111.70 | 0.334374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 362798.95 | 20-FEB-13:01 | 362798.95 | 20-FEB-13:01 | 0.00 | 0.00 | 0.00 |
March | 0.205377E+12 | 0.00 | 307.97 | 0.204546E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1163694.71 | 03-MAR-06:01 | 1163694.71 | 03-MAR-06:01 | 0.00 | 0.00 | 0.00 |
April | 0.427718E+12 | 0.00 | 394.12 | 0.427651E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1205836.71 | 10-APR-05:03 | 1138039.47 | 10-APR-05:03 | 0.00 | 0.00 | 0.00 |
May | 0.812443E+12 | 0.00 | 442.68 | 0.776788E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1634338.18 | 31-MAY-04:12 | 1330207.03 | 30-MAY-14:05 | 0.00 | 0.00 | 0.00 |
June | 0.141539E+13 | 0.00 | 446.52 | 0.114520E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2378903.62 | 27-JUN-05:02 | 1523392.01 | 19-JUN-14:05 | 0.00 | 0.00 | 0.00 |
July | 0.185975E+13 | 0.00 | 456.67 | 0.134724E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2704236.65 | 20-JUL-05:02 | 1657951.01 | 18-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.182709E+13 | 0.00 | 466.06 | 0.147575E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2794076.17 | 03-AUG-05:02 | 1732830.57 | 03-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.111819E+13 | 0.00 | 422.93 | 0.972187E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2312353.77 | 22-SEP-04:11 | 1524706.93 | 02-SEP-05:03 | 0.00 | 0.00 | 0.00 |
October | 0.755363E+12 | 0.00 | 413.57 | 0.684432E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2066540.77 | 25-OCT-04:11 | 1283676.78 | 25-OCT-04:11 | 0.00 | 0.00 | 0.00 |
November | 0.231328E+12 | 0.00 | 306.89 | 0.230223E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1280316.59 | 10-NOV-06:01 | 1156322.20 | 02-NOV-05:01 | 0.00 | 0.00 | 0.00 |
December | 0.585426E+11 | 0.00 | 182.64 | 0.585426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 459598.43 | 17-DEC-13:12 | 459598.43 | 17-DEC-13:12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.878324E+13 | 0.00 | 4085.94 | 0.739462E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.334374E+11 | 0.00 | 111.70 | 0.334374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 249466.95 | 249466.95 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.185975E+13 | 0.00 | 466.06 | 0.147575E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2794076.17 | 1732830.57 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.471924E+10 | 0.00 | 136.03 | 0.471924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30643.92 | 17-JAN-14:00 | 30643.92 | 17-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.304080E+10 | 0.00 | 99.66 | 0.304080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25361.32 | 17-FEB-14:00 | 25361.32 | 17-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.197796E+11 | 0.00 | 279.84 | 0.197385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79195.45 | 27-MAR-16:00 | 78471.87 | 03-MAR-14:21 | 0.00 | 0.00 | 0.00 |
April | 0.435138E+11 | 0.00 | 367.06 | 0.435127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 144160.40 | 07-APR-14:40 | 144160.40 | 07-APR-14:40 | 0.00 | 0.00 | 0.00 |
May | 0.889372E+11 | 0.00 | 437.07 | 0.855966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 187237.43 | 31-MAY-14:00 | 178608.92 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 0.159022E+12 | 0.00 | 437.42 | 0.132213E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 272714.45 | 27-JUN-05:02 | 205253.46 | 19-JUN-13:50 | 0.00 | 0.00 | 0.00 |
July | 0.210151E+12 | 0.00 | 454.68 | 0.158732E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 349287.43 | 09-JUL-14:11 | 231535.01 | 09-JUL-14:11 | 0.00 | 0.00 | 0.00 |
August | 0.204713E+12 | 0.00 | 460.07 | 0.169873E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 307956.94 | 05-AUG-03:01 | 229350.59 | 13-AUG-15:11 | 0.00 | 0.00 | 0.00 |
September | 0.117439E+12 | 0.00 | 411.89 | 0.103492E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 255176.18 | 14-SEP-05:03 | 185547.11 | 01-SEP-14:20 | 0.00 | 0.00 | 0.00 |
October | 0.709861E+11 | 0.00 | 393.45 | 0.648068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 224259.54 | 06-OCT-05:01 | 140645.12 | 04-OCT-14:30 | 0.00 | 0.00 | 0.00 |
November | 0.186540E+11 | 0.00 | 273.14 | 0.185746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69316.40 | 03-NOV-14:31 | 69316.40 | 03-NOV-14:31 | 0.00 | 0.00 | 0.00 |
December | 0.371001E+10 | 0.00 | 138.67 | 0.371001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20330.54 | 19-DEC-14:00 | 20330.54 | 19-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.944666E+12 | 0.00 | 3888.99 | 0.808010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.304080E+10 | 0.00 | 99.66 | 0.304080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20330.54 | 20330.54 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.210151E+12 | 0.00 | 460.07 | 0.169873E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 349287.43 | 231535.01 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.739839E+10 | 0.00 | 82.88 | 0.731618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88803.24 | 23-JAN-06:01 | 88803.24 | 23-JAN-06:01 | 0.00 | 0.00 | 0.00 |
February | 0.296783E+10 | 0.00 | 29.81 | 0.296783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 104935.89 | 24-FEB-05:11 | 104935.89 | 24-FEB-05:11 | 0.00 | 0.00 | 0.00 |
March | 0.155184E+11 | 0.00 | 176.90 | 0.152152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103045.57 | 01-MAR-06:01 | 103045.57 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 |
April | 0.292202E+11 | 0.00 | 288.36 | 0.288293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96048.89 | 27-APR-04:12 | 96048.89 | 27-APR-04:12 | 0.00 | 0.00 | 0.00 |
May | 0.480498E+11 | 0.00 | 404.47 | 0.429090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121749.64 | 19-MAY-04:12 | 117014.16 | 30-MAY-04:12 | 0.00 | 0.00 | 0.00 |
June | 0.854508E+11 | 0.00 | 410.18 | 0.631082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153379.19 | 26-JUN-04:23 | 117155.08 | 03-JUN-04:12 | 0.00 | 0.00 | 0.00 |
July | 0.109406E+12 | 0.00 | 397.50 | 0.725528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 165521.50 | 24-JUL-04:23 | 112104.53 | 14-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.113168E+12 | 0.00 | 446.45 | 0.835955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153293.16 | 02-AUG-05:02 | 114093.00 | 21-AUG-04:22 | 0.00 | 0.00 | 0.00 |
September | 0.805727E+11 | 0.00 | 409.82 | 0.651885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 150028.65 | 04-SEP-11:48 | 125112.64 | 04-SEP-11:48 | 0.00 | 0.00 | 0.00 |
October | 0.645474E+11 | 0.00 | 395.35 | 0.555860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 144999.21 | 15-OCT-20:09 | 121239.97 | 09-OCT-19:39 | 0.00 | 0.00 | 0.00 |
November | 0.314144E+11 | 0.00 | 274.33 | 0.307556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102065.16 | 12-NOV-15:41 | 102065.16 | 12-NOV-15:41 | 0.00 | 0.00 | 0.00 |
December | 0.126399E+11 | 0.00 | 122.20 | 0.126399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91469.59 | 26-DEC-05:11 | 91469.59 | 26-DEC-05:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.600354E+12 | 0.00 | 3438.25 | 0.480664E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.296783E+10 | 0.00 | 29.81 | 0.296783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88803.24 | 88803.24 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.113168E+12 | 0.00 | 446.45 | 0.835955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 165521.50 | 125112.64 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 4224781.43 | 0.00 | 247.39 | 4224781.43 | 0.00 | 0.00 | 0.00 | 0.00 | 66.77 | 03-JAN-10:15 | 66.77 | 03-JAN-10:15 | 0.00 | 0.00 | 0.00 |
February | 0.150762E+12 | 0.00 | 400.61 | 0.150762E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 272093.96 | 06-FEB-04:41 | 272093.96 | 06-FEB-04:41 | 0.00 | 0.00 | 0.00 |
March | 0.224280E+12 | 0.00 | 721.57 | 0.223237E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 392504.53 | 27-MAR-12:27 | 266317.40 | 01-MAR-00:15 | 0.00 | 0.00 | 0.00 |
April | 0.246311E+12 | 0.00 | 719.04 | 0.244274E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 363695.04 | 07-APR-13:05 | 363695.04 | 07-APR-13:05 | 0.00 | 0.00 | 0.00 |
May | 0.121009E+11 | 0.00 | 274.19 | 0.118633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 405561.33 | 31-MAY-23:10 | 227372.18 | 31-MAY-23:41 | 0.00 | 0.00 | 0.00 |
June | 0.405781E+12 | 0.00 | 641.28 | 0.354832E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 536530.71 | 13-JUN-19:02 | 332077.36 | 02-JUN-12:57 | 0.00 | 0.00 | 0.00 |
July | 0.757573E+12 | 0.00 | 744.00 | 0.737645E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 500258.60 | 05-JUL-07:30 | 392746.04 | 31-JUL-23:31 | 0.00 | 0.00 | 0.00 |
August | 0.882423E+12 | 0.00 | 744.00 | 0.863089E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 519443.68 | 10-AUG-07:30 | 513683.82 | 24-AUG-16:51 | 0.00 | 0.00 | 0.00 |
September | 0.425893E+11 | 0.00 | 387.67 | 0.416008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 186695.39 | 01-SEP-14:00 | 186695.39 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.240233E+12 | 0.00 | 462.87 | 0.182346E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 507610.04 | 24-OCT-09:36 | 333153.33 | 25-OCT-16:31 | 0.00 | 0.00 | 0.00 |
November | 0.216842E+12 | 0.00 | 706.44 | 0.212262E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 368009.81 | 10-NOV-10:00 | 315506.47 | 02-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.231698E+12 | 0.00 | 744.00 | 0.231698E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 279428.77 | 08-DEC-15:57 | 279428.77 | 08-DEC-15:57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.341060E+13 | 0.00 | 6793.07 | 0.325361E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4224781.43 | 0.00 | 247.39 | 4224781.43 | 0.00 | 0.00 | 0.00 | 0.00 | 66.77 | 66.77 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.882423E+12 | 0.00 | 744.00 | 0.863089E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 536530.71 | 513683.82 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.424548E+10 | 0.132074E+10 | 732.58 | 0.424378E+10 | 1695963.60 | 0.00 | 0.55 | 20-JAN-16:27 | 0.00 | 01-JAN-00:01 | 3143.16 | 20-JAN-16:30 | 3143.16 | 20-JAN-16:30 | 79.88 | 24-JAN-15:10 | 921.99 | 19-JAN-16:20 | 0.00 | 01-JAN-00:01 |
February | 0.851076E+10 | 0.243512E+10 | 672.00 | 0.851076E+10 | 0.00 | 0.00 | 0.83 | 22-FEB-16:51 | 0.39 | 06-FEB-04:20 | 5102.60 | 22-FEB-16:53 | 5102.60 | 22-FEB-16:53 | 0.00 | 08-FEB-16:26 | 1372.44 | 22-FEB-17:00 | 0.00 | 01-FEB-00:01 |
March | 0.157985E+11 | 0.413114E+10 | 744.00 | 0.157898E+11 | 8657140.03 | 0.00 | 1.00 | 01-MAR-15:21 | 0.84 | 01-MAR-00:01 | 7510.37 | 31-MAR-23:53 | 7510.37 | 31-MAR-23:53 | 195.56 | 27-MAR-13:30 | 1942.34 | 31-MAR-23:53 | 0.00 | 01-MAR-00:01 |
April | 0.208726E+11 | 0.543618E+10 | 720.00 | 0.208505E+11 | 22104786.95 | 0.00 | 1.00 | 01-APR-00:10 | 0.46 | 30-APR-24:00 | 9304.82 | 07-APR-16:00 | 9229.77 | 07-APR-16:00 | 169.65 | 27-APR-15:51 | 2607.85 | 07-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.724125E+10 | 0.217623E+10 | 744.00 | 0.714481E+10 | 96438494.79 | 0.00 | 0.75 | 31-MAY-23:01 | 0.36 | 04-MAY-06:00 | 4779.48 | 31-MAY-23:01 | 4597.32 | 31-MAY-23:52 | 263.98 | 19-MAY-11:00 | 1312.68 | 31-MAY-23:01 | 0.00 | 01-MAY-00:10 |
June | 0.129746E+11 | 0.361936E+10 | 720.00 | 0.124928E+11 | 0.481842E+09 | 0.00 | 0.98 | 30-JUN-24:00 | 0.69 | 03-JUN-07:00 | 6687.59 | 30-JUN-23:20 | 6438.99 | 30-JUN-24:00 | 506.44 | 15-JUN-14:00 | 1927.08 | 19-JUN-12:10 | 0.00 | 01-JUN-00:01 |
July | 0.190973E+11 | 0.515873E+10 | 744.00 | 0.182318E+11 | 0.865462E+09 | 0.00 | 1.00 | 01-JUL-09:05 | 0.96 | 11-JUL-06:00 | 8886.69 | 31-JUL-23:10 | 8450.86 | 31-JUL-23:50 | 600.64 | 20-JUL-15:00 | 2429.91 | 07-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.239776E+11 | 0.667194E+10 | 744.00 | 0.233421E+11 | 0.635471E+09 | 0.00 | 1.00 | 01-AUG-00:03 | 0.54 | 31-AUG-23:32 | 10060.45 | 31-AUG-17:20 | 9674.61 | 31-AUG-17:30 | 628.65 | 03-AUG-15:00 | 3147.53 | 24-AUG-15:30 | 0.00 | 01-AUG-00:03 |
September | 0.767160E+10 | 0.230148E+10 | 720.00 | 0.739881E+10 | 0.272795E+09 | 0.00 | 0.70 | 30-SEP-23:20 | 0.38 | 30-SEP-07:00 | 4294.12 | 30-SEP-23:30 | 4294.12 | 30-SEP-23:30 | 439.52 | 07-SEP-15:00 | 1248.80 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 |
October | 0.120814E+11 | 0.334813E+10 | 744.00 | 0.119191E+11 | 0.162297E+09 | 0.00 | 0.90 | 31-OCT-23:54 | 0.62 | 28-OCT-06:51 | 5908.09 | 04-OCT-16:00 | 5888.55 | 31-OCT-23:52 | 317.04 | 24-OCT-10:00 | 1584.90 | 04-OCT-16:00 | 0.00 | 01-OCT-00:10 |
November | 0.153780E+11 | 0.401877E+10 | 720.00 | 0.153654E+11 | 12568339.67 | 0.00 | 1.00 | 01-NOV-14:21 | 0.83 | 25-NOV-18:12 | 7181.45 | 03-NOV-15:55 | 7181.45 | 03-NOV-15:55 | 225.89 | 10-NOV-10:00 | 1844.11 | 03-NOV-15:53 | 0.00 | 01-NOV-00:05 |
December | 0.203499E+11 | 0.526284E+10 | 744.00 | 0.203499E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-00:01 | 1.00 | 01-DEC-00:01 | 8841.33 | 08-DEC-15:51 | 8841.33 | 08-DEC-15:51 | 0.00 | 05-DEC-05:12 | 2324.02 | 08-DEC-16:00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.168199E+12 | 0.458807E+11 | 8748.58 | 0.165640E+12 | 0.255933E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.424548E+10 | 0.132074E+10 | 672.00 | 0.424378E+10 | -0.0 | 0.00 | 0.55 | 0.00 | 3143.16 | 3143.16 | 0.00 | 921.99 | 0.00 | |||||||
Maximum of Months | 0.239776E+11 | 0.667194E+10 | 744.00 | 0.233421E+11 | 0.865462E+09 | 0.00 | 1.00 | 1.00 | 10060.45 | 9674.61 | 628.65 | 3147.53 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.216710E+11 | 0.588338E+10 | 578.67 | 0.216547E+11 | 16334606.98 | 0.00 | 0.51 | 20-JAN-16:27 | 0.00 | 01-JAN-00:01 | 27768.05 | 20-JAN-16:30 | 27768.05 | 20-JAN-16:30 | 756.05 | 24-JAN-15:20 | 7055.81 | 20-JAN-16:30 | 0.00 | 01-JAN-00:01 |
February | 0.656720E+11 | 0.164998E+11 | 672.00 | 0.656720E+11 | 0.00 | 0.00 | 0.81 | 22-FEB-16:51 | 0.11 | 06-FEB-04:10 | 47895.81 | 22-FEB-16:53 | 47895.81 | 22-FEB-16:53 | 0.00 | 14-FEB-16:37 | 11090.84 | 22-FEB-17:00 | 0.00 | 01-FEB-00:01 |
March | 0.139757E+12 | 0.318492E+11 | 744.00 | 0.139671E+12 | 86488188.16 | 0.00 | 1.00 | 03-MAR-15:11 | 0.70 | 13-MAR-03:51 | 70666.23 | 27-MAR-17:00 | 69895.65 | 27-MAR-17:20 | 1930.22 | 27-MAR-13:20 | 15518.72 | 27-MAR-17:20 | 0.00 | 01-MAR-00:01 |
April | 0.191318E+12 | 0.425117E+11 | 720.00 | 0.191101E+12 | 0.216923E+09 | 0.00 | 1.00 | 01-APR-00:10 | 0.34 | 30-APR-24:00 | 88857.73 | 07-APR-16:00 | 88106.69 | 07-APR-16:00 | 1704.18 | 27-APR-15:51 | 21336.01 | 07-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.631544E+11 | 0.164185E+11 | 744.00 | 0.622104E+11 | 0.943985E+09 | 0.00 | 0.74 | 31-MAY-23:01 | 0.28 | 01-MAY-06:00 | 45423.49 | 31-MAY-23:01 | 43502.16 | 31-MAY-23:52 | 2619.54 | 18-MAY-15:30 | 10711.64 | 31-MAY-23:01 | 0.00 | 01-MAY-00:10 |
June | 0.121996E+12 | 0.292804E+11 | 720.00 | 0.117205E+12 | 0.479067E+10 | 0.00 | 0.96 | 30-JUN-24:00 | 0.65 | 03-JUN-07:00 | 62989.76 | 30-JUN-23:20 | 60466.73 | 30-JUN-24:00 | 5031.99 | 15-JUN-14:00 | 15794.03 | 19-JUN-12:10 | 0.00 | 01-JUN-00:01 |
July | 0.181900E+12 | 0.421229E+11 | 744.00 | 0.173278E+12 | 0.862216E+10 | 0.00 | 1.00 | 01-JUL-14:40 | 0.95 | 01-JUL-07:00 | 85453.24 | 31-JUL-23:10 | 80906.31 | 31-JUL-24:00 | 5987.34 | 20-JUL-15:00 | 19937.43 | 07-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.228837E+12 | 0.545471E+11 | 744.00 | 0.222501E+12 | 0.633614E+10 | 0.00 | 1.00 | 01-AUG-00:03 | 0.51 | 31-AUG-23:22 | 96788.07 | 31-AUG-17:20 | 92908.35 | 31-AUG-17:30 | 6270.18 | 03-AUG-15:00 | 25748.85 | 24-AUG-15:50 | 0.00 | 01-AUG-00:03 |
September | 0.676051E+11 | 0.175455E+11 | 720.00 | 0.649264E+11 | 0.267877E+10 | 0.00 | 0.67 | 06-SEP-17:20 | 0.30 | 24-SEP-06:00 | 40067.64 | 06-SEP-17:20 | 38590.50 | 30-SEP-23:20 | 4374.21 | 07-SEP-15:10 | 10169.17 | 14-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 0.107631E+12 | 0.258732E+11 | 744.00 | 0.106021E+12 | 0.161000E+10 | 0.00 | 0.89 | 04-OCT-16:00 | 0.52 | 29-OCT-07:00 | 56384.01 | 04-OCT-16:00 | 53562.19 | 04-OCT-16:00 | 3158.16 | 24-OCT-10:00 | 12978.94 | 04-OCT-16:00 | 0.00 | 01-OCT-00:10 |
November | 0.132083E+12 | 0.302616E+11 | 720.00 | 0.131958E+12 | 0.125305E+09 | 0.00 | 1.00 | 01-NOV-15:01 | 0.62 | 24-NOV-04:20 | 68125.36 | 03-NOV-15:55 | 68125.36 | 03-NOV-15:55 | 2245.91 | 10-NOV-10:02 | 14974.61 | 03-NOV-15:53 | 0.00 | 01-NOV-00:05 |
December | 0.176352E+12 | 0.388384E+11 | 744.00 | 0.176352E+12 | -0.0 | 0.00 | 1.00 | 01-DEC-00:01 | 0.80 | 31-DEC-23:52 | 82618.10 | 08-DEC-16:03 | 82618.10 | 08-DEC-16:03 | 0.00 | 12-DEC-15:53 | 18569.90 | 08-DEC-16:10 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.149798E+13 | 0.351632E+12 | 8594.67 | 0.147255E+13 | 0.254268E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.216710E+11 | 0.588338E+10 | 578.67 | 0.216547E+11 | -0.0 | 0.00 | 0.51 | 0.00 | 27768.05 | 27768.05 | 0.00 | 7055.81 | 0.00 | |||||||
Maximum of Months | 0.228837E+12 | 0.545471E+11 | 744.00 | 0.222501E+12 | 0.862216E+10 | 0.00 | 1.00 | 0.95 | 96788.07 | 92908.35 | 6270.18 | 25748.85 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.127373E+10 | 0.405435E+09 | 369.00 | 0.127227E+10 | 1457291.74 | 0.00 | 0.49 | 19-JAN-16:30 | 0.00 | 01-JAN-00:01 | 2729.72 | 19-JAN-16:30 | 2729.72 | 19-JAN-16:30 | 70.78 | 24-JAN-15:20 | 815.23 | 19-JAN-16:23 | 0.00 | 01-JAN-00:01 |
February | 0.475471E+10 | 0.142305E+10 | 637.31 | 0.475471E+10 | 0.00 | 0.00 | 0.78 | 22-FEB-16:51 | 0.00 | 04-FEB-23:31 | 4721.52 | 22-FEB-16:53 | 4721.52 | 22-FEB-16:53 | 0.00 | 02-FEB-16:39 | 1287.52 | 22-FEB-17:00 | 0.00 | 01-FEB-00:01 |
March | 0.123594E+11 | 0.337411E+10 | 744.00 | 0.123509E+11 | 8547017.28 | 0.00 | 1.00 | 03-MAR-16:21 | 0.42 | 20-MAR-03:30 | 7131.12 | 27-MAR-17:00 | 7051.52 | 27-MAR-17:20 | 194.43 | 27-MAR-13:30 | 1821.65 | 27-MAR-17:00 | 0.00 | 01-MAR-00:01 |
April | 0.180641E+11 | 0.468109E+10 | 720.00 | 0.180442E+11 | 19925964.73 | 0.00 | 1.00 | 02-APR-14:42 | 0.16 | 30-APR-24:00 | 9114.65 | 07-APR-16:00 | 9039.60 | 07-APR-16:00 | 171.08 | 27-APR-15:51 | 2551.75 | 07-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.580301E+10 | 0.177216E+10 | 743.32 | 0.571066E+10 | 92350990.69 | 0.00 | 0.71 | 31-MAY-23:01 | 0.00 | 04-MAY-05:35 | 4454.71 | 31-MAY-23:01 | 4256.43 | 31-MAY-23:32 | 262.80 | 19-MAY-11:00 | 1237.22 | 31-MAY-23:01 | 0.00 | 01-MAY-00:10 |
June | 0.121682E+11 | 0.342929E+10 | 720.00 | 0.116894E+11 | 0.478842E+09 | 0.00 | 0.93 | 19-JUN-14:40 | 0.57 | 03-JUN-06:20 | 6161.21 | 30-JUN-23:20 | 5896.58 | 30-JUN-24:00 | 507.16 | 15-JUN-14:00 | 1926.16 | 19-JUN-12:10 | 0.00 | 01-JUN-00:01 |
July | 0.183418E+11 | 0.497016E+10 | 744.00 | 0.174805E+11 | 0.861356E+09 | 0.00 | 1.00 | 01-JUL-14:30 | 0.90 | 01-JUL-06:50 | 8521.35 | 31-JUL-23:10 | 8084.47 | 31-JUL-24:00 | 600.70 | 20-JUL-15:00 | 2412.30 | 07-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.229669E+11 | 0.637348E+10 | 744.00 | 0.223357E+11 | 0.631227E+09 | 0.00 | 1.00 | 01-AUG-00:03 | 0.49 | 31-AUG-23:32 | 9844.68 | 02-AUG-15:50 | 9439.05 | 31-AUG-17:20 | 628.14 | 03-AUG-15:00 | 3078.38 | 24-AUG-15:30 | 0.00 | 01-AUG-00:03 |
September | 0.638800E+10 | 0.194865E+10 | 719.88 | 0.612239E+10 | 0.265611E+09 | 0.00 | 0.67 | 06-SEP-17:20 | 0.00 | 24-SEP-00:35 | 4161.63 | 06-SEP-17:20 | 3897.63 | 06-SEP-17:20 | 443.28 | 14-SEP-10:00 | 1245.79 | 14-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 0.958637E+10 | 0.273806E+10 | 744.00 | 0.942633E+10 | 0.160043E+09 | 0.00 | 0.88 | 04-OCT-16:00 | 0.20 | 29-OCT-07:00 | 5805.96 | 04-OCT-16:00 | 5523.16 | 04-OCT-16:00 | 321.12 | 24-OCT-09:52 | 1560.34 | 04-OCT-16:00 | 0.00 | 01-OCT-00:10 |
November | 0.113613E+11 | 0.313103E+10 | 720.00 | 0.113489E+11 | 12387400.97 | 0.00 | 1.00 | 03-NOV-15:35 | 0.34 | 24-NOV-04:10 | 6818.27 | 03-NOV-15:55 | 6818.27 | 03-NOV-15:55 | 224.90 | 10-NOV-10:11 | 1741.88 | 03-NOV-15:53 | 0.00 | 01-NOV-00:05 |
December | 0.153597E+11 | 0.403062E+10 | 744.00 | 0.153597E+11 | 0.00 | 0.00 | 1.00 | 01-DEC-09:02 | 0.58 | 31-DEC-23:52 | 8078.51 | 08-DEC-16:03 | 8078.51 | 08-DEC-16:03 | 0.00 | 04-DEC-14:25 | 2107.26 | 08-DEC-16:10 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.138427E+12 | 0.382771E+11 | 8349.52 | 0.135896E+12 | 0.253175E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.127373E+10 | 0.405435E+09 | 369.00 | 0.127227E+10 | 0.00 | 0.00 | 0.49 | 0.00 | 2729.72 | 2729.72 | 0.00 | 815.23 | 0.00 | |||||||
Maximum of Months | 0.229669E+11 | 0.637348E+10 | 744.00 | 0.223357E+11 | 0.861356E+09 | 0.00 | 1.00 | 0.90 | 9844.68 | 9439.05 | 628.14 | 3078.38 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 130.03 | 0.00 | 130.03 | 0.17 | 1039.23 | 0.00 | 0.00 | 0.00 |
February | 177.93 | 0.00 | 177.93 | 2.86 | 1075.51 | 0.00 | 0.00 | 0.00 |
March | 246.75 | 0.00 | 246.75 | 38.59 | 734.55 | 0.00 | 0.00 | 0.00 |
April | 296.38 | 0.84 | 295.54 | 125.98 | 519.78 | 0.00 | 0.00 | 0.00 |
May | 393.20 | 13.10 | 380.10 | 306.56 | 293.78 | 0.00 | 0.00 | 0.00 |
June | 416.99 | 22.41 | 394.58 | 479.13 | 156.66 | 0.00 | 0.00 | 0.00 |
July | 402.98 | 14.57 | 388.40 | 557.69 | 83.64 | 0.00 | 0.00 | 0.00 |
August | 357.02 | 4.25 | 352.77 | 485.58 | 114.17 | 0.00 | 0.00 | 0.00 |
September | 269.13 | 0.05 | 269.08 | 255.29 | 245.78 | 0.00 | 0.00 | 0.00 |
October | 232.92 | 0.00 | 232.92 | 126.34 | 456.38 | 0.00 | 0.00 | 0.00 |
November | 163.37 | 0.00 | 163.37 | 16.76 | 764.00 | 0.00 | 0.00 | 0.00 |
December | 113.42 | 0.00 | 113.42 | 0.21 | 997.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 267.19 | 4.63 | 262.56 | 201.00 | 537.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 113.42 | 0.00 | 113.42 | 0.17 | 83.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 416.99 | 22.41 | 394.58 | 557.69 | 1075.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 130.03 | 0.00 | 130.03 | 0.17 | 1039.23 | 0.00 | 0.00 | 0.00 |
February | 177.93 | 0.00 | 177.93 | 2.86 | 1075.51 | 0.00 | 0.00 | 0.00 |
March | 246.75 | 0.00 | 246.75 | 38.59 | 734.55 | 0.00 | 0.00 | 0.00 |
April | 296.38 | 0.84 | 295.54 | 125.98 | 519.78 | 0.00 | 0.00 | 0.00 |
May | 393.20 | 13.10 | 380.10 | 306.56 | 293.78 | 0.00 | 0.00 | 0.00 |
June | 416.99 | 22.41 | 394.58 | 479.13 | 156.66 | 0.00 | 0.00 | 0.00 |
July | 402.98 | 14.57 | 388.40 | 557.69 | 83.64 | 0.00 | 0.00 | 0.00 |
August | 357.02 | 4.25 | 352.77 | 485.58 | 114.17 | 0.00 | 0.00 | 0.00 |
September | 269.13 | 0.05 | 269.08 | 255.29 | 245.78 | 0.00 | 0.00 | 0.00 |
October | 232.92 | 0.00 | 232.92 | 126.34 | 456.38 | 0.00 | 0.00 | 0.00 |
November | 163.37 | 0.00 | 163.37 | 16.76 | 764.00 | 0.00 | 0.00 | 0.00 |
December | 113.42 | 0.00 | 113.42 | 0.21 | 997.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 267.19 | 4.63 | 262.56 | 201.00 | 537.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 113.42 | 0.00 | 113.42 | 0.17 | 83.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 416.99 | 22.41 | 394.58 | 557.69 | 1075.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 130.03 | 0.00 | 130.03 | 0.17 | 1039.23 | 0.00 | 0.00 | 0.00 |
February | 177.93 | 0.00 | 177.93 | 2.86 | 1075.51 | 0.00 | 0.00 | 0.00 |
March | 246.75 | 0.00 | 246.75 | 38.59 | 734.55 | 0.00 | 0.00 | 0.00 |
April | 296.38 | 0.84 | 295.54 | 125.98 | 519.78 | 0.00 | 0.00 | 0.00 |
May | 393.20 | 13.10 | 380.10 | 306.56 | 293.78 | 0.00 | 0.00 | 0.00 |
June | 416.99 | 22.41 | 394.58 | 479.13 | 156.66 | 0.00 | 0.00 | 0.00 |
July | 402.98 | 14.57 | 388.40 | 557.69 | 83.64 | 0.00 | 0.00 | 0.00 |
August | 357.02 | 4.25 | 352.77 | 485.58 | 114.17 | 0.00 | 0.00 | 0.00 |
September | 269.13 | 0.05 | 269.08 | 255.29 | 245.78 | 0.00 | 0.00 | 0.00 |
October | 232.92 | 0.00 | 232.92 | 126.34 | 456.38 | 0.00 | 0.00 | 0.00 |
November | 163.37 | 0.00 | 163.37 | 16.76 | 764.00 | 0.00 | 0.00 | 0.00 |
December | 113.42 | 0.00 | 113.42 | 0.21 | 997.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 267.19 | 4.63 | 262.56 | 201.00 | 537.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 113.42 | 0.00 | 113.42 | 0.17 | 83.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 416.99 | 22.41 | 394.58 | 557.69 | 1075.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 130.03 | 0.00 | 130.03 | 0.17 | 1039.23 | 0.00 | 0.00 | 0.00 |
February | 177.93 | 0.00 | 177.93 | 2.86 | 1075.51 | 0.00 | 0.00 | 0.00 |
March | 246.75 | 0.00 | 246.75 | 38.59 | 734.55 | 0.00 | 0.00 | 0.00 |
April | 296.38 | 0.84 | 295.54 | 125.98 | 519.78 | 0.00 | 0.00 | 0.00 |
May | 393.20 | 13.10 | 380.10 | 306.56 | 293.78 | 0.00 | 0.00 | 0.00 |
June | 416.99 | 22.41 | 394.58 | 479.13 | 156.66 | 0.00 | 0.00 | 0.00 |
July | 402.98 | 14.57 | 388.40 | 557.69 | 83.64 | 0.00 | 0.00 | 0.00 |
August | 357.02 | 4.25 | 352.77 | 485.58 | 114.17 | 0.00 | 0.00 | 0.00 |
September | 269.13 | 0.05 | 269.08 | 255.29 | 245.78 | 0.00 | 0.00 | 0.00 |
October | 232.92 | 0.00 | 232.92 | 126.34 | 456.38 | 0.00 | 0.00 | 0.00 |
November | 163.37 | 0.00 | 163.37 | 16.76 | 764.00 | 0.00 | 0.00 | 0.00 |
December | 113.42 | 0.00 | 113.42 | 0.21 | 997.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 267.19 | 4.63 | 262.56 | 201.00 | 537.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 113.42 | 0.00 | 113.42 | 0.17 | 83.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 416.99 | 22.41 | 394.58 | 557.69 | 1075.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 130.02 | 0.00 | 130.02 | 0.17 | 1039.19 | 0.00 | 0.00 | 0.00 |
February | 177.93 | 0.00 | 177.93 | 2.86 | 1075.47 | 0.00 | 0.00 | 0.00 |
March | 246.74 | 0.00 | 246.74 | 38.58 | 734.52 | 0.00 | 0.00 | 0.00 |
April | 296.37 | 0.84 | 295.53 | 125.97 | 519.76 | 0.00 | 0.00 | 0.00 |
May | 393.19 | 13.10 | 380.09 | 306.55 | 293.77 | 0.00 | 0.00 | 0.00 |
June | 416.97 | 22.41 | 394.56 | 479.11 | 156.66 | 0.00 | 0.00 | 0.00 |
July | 402.96 | 14.57 | 388.39 | 557.67 | 83.64 | 0.00 | 0.00 | 0.00 |
August | 357.00 | 4.25 | 352.76 | 485.56 | 114.16 | 0.00 | 0.00 | 0.00 |
September | 269.12 | 0.05 | 269.07 | 255.28 | 245.77 | 0.00 | 0.00 | 0.00 |
October | 232.91 | 0.00 | 232.91 | 126.33 | 456.36 | 0.00 | 0.00 | 0.00 |
November | 163.36 | 0.00 | 163.36 | 16.76 | 763.97 | 0.00 | 0.00 | 0.00 |
December | 113.41 | 0.00 | 113.41 | 0.21 | 997.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 267.18 | 4.63 | 262.55 | 200.99 | 536.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 113.41 | 0.00 | 113.41 | 0.17 | 83.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 416.97 | 22.41 | 394.56 | 557.67 | 1075.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 301.79 | 120.99 | 180.79 | 139.81 | 1049.15 | 0.00 | 0.00 | 0.00 |
February | 468.00 | 218.32 | 249.68 | 257.07 | 1046.20 | 0.00 | 0.00 | 0.00 |
March | 597.03 | 253.92 | 343.11 | 438.94 | 750.71 | 0.00 | 0.00 | 0.00 |
April | 716.48 | 313.84 | 402.64 | 641.69 | 524.74 | 0.00 | 0.00 | 0.00 |
May | 868.93 | 347.28 | 521.66 | 931.86 | 315.26 | 0.00 | 0.00 | 0.00 |
June | 805.32 | 291.52 | 513.80 | 1013.06 | 163.90 | 0.00 | 0.00 | 0.00 |
July | 808.84 | 291.89 | 516.95 | 1135.23 | 75.26 | 0.00 | 0.00 | 0.00 |
August | 910.78 | 410.67 | 500.11 | 1265.98 | 104.94 | 0.00 | 0.00 | 0.00 |
September | 679.26 | 304.76 | 374.50 | 802.46 | 246.86 | 0.00 | 0.00 | 0.00 |
October | 615.80 | 279.10 | 336.70 | 617.88 | 464.00 | 0.00 | 0.00 | 0.00 |
November | 380.83 | 146.24 | 234.58 | 242.35 | 751.84 | 0.00 | 0.00 | 0.00 |
December | 296.69 | 139.31 | 157.38 | 155.15 | 982.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 621.80 | 260.11 | 361.68 | 639.49 | 536.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 296.69 | 120.99 | 157.38 | 139.81 | 75.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 910.78 | 410.67 | 521.66 | 1265.98 | 1049.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 301.79 | 120.99 | 180.79 | 139.81 | 1049.15 | 0.00 | 0.00 | 0.00 |
February | 468.00 | 218.32 | 249.68 | 257.07 | 1046.20 | 0.00 | 0.00 | 0.00 |
March | 597.03 | 253.92 | 343.11 | 438.94 | 750.71 | 0.00 | 0.00 | 0.00 |
April | 716.48 | 313.84 | 402.64 | 641.69 | 524.74 | 0.00 | 0.00 | 0.00 |
May | 868.93 | 347.28 | 521.66 | 931.86 | 315.26 | 0.00 | 0.00 | 0.00 |
June | 805.32 | 291.52 | 513.80 | 1013.06 | 163.90 | 0.00 | 0.00 | 0.00 |
July | 808.84 | 291.89 | 516.95 | 1135.23 | 75.26 | 0.00 | 0.00 | 0.00 |
August | 910.78 | 410.67 | 500.11 | 1265.98 | 104.94 | 0.00 | 0.00 | 0.00 |
September | 679.26 | 304.76 | 374.50 | 802.46 | 246.86 | 0.00 | 0.00 | 0.00 |
October | 615.80 | 279.10 | 336.70 | 617.88 | 464.00 | 0.00 | 0.00 | 0.00 |
November | 380.83 | 146.24 | 234.58 | 242.35 | 751.84 | 0.00 | 0.00 | 0.00 |
December | 296.69 | 139.31 | 157.38 | 155.15 | 982.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 621.80 | 260.11 | 361.68 | 639.49 | 536.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 296.69 | 120.99 | 157.38 | 139.81 | 75.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 910.78 | 410.67 | 521.66 | 1265.98 | 1049.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 301.78 | 120.99 | 180.79 | 139.81 | 1049.13 | 0.00 | 0.00 | 0.00 |
February | 468.00 | 218.32 | 249.68 | 257.07 | 1046.18 | 0.00 | 0.00 | 0.00 |
March | 597.02 | 253.92 | 343.10 | 438.93 | 750.69 | 0.00 | 0.00 | 0.00 |
April | 716.46 | 313.83 | 402.63 | 641.68 | 524.73 | 0.00 | 0.00 | 0.00 |
May | 868.92 | 347.27 | 521.65 | 931.84 | 315.25 | 0.00 | 0.00 | 0.00 |
June | 805.30 | 291.51 | 513.79 | 1013.05 | 163.89 | 0.00 | 0.00 | 0.00 |
July | 808.83 | 291.89 | 516.94 | 1135.21 | 75.26 | 0.00 | 0.00 | 0.00 |
August | 910.76 | 410.66 | 500.10 | 1265.96 | 104.93 | 0.00 | 0.00 | 0.00 |
September | 679.25 | 304.75 | 374.50 | 802.44 | 246.85 | 0.00 | 0.00 | 0.00 |
October | 615.79 | 279.10 | 336.69 | 617.87 | 463.99 | 0.00 | 0.00 | 0.00 |
November | 380.82 | 146.24 | 234.58 | 242.35 | 751.82 | 0.00 | 0.00 | 0.00 |
December | 296.68 | 139.30 | 157.38 | 155.15 | 982.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 621.79 | 260.11 | 361.68 | 639.48 | 536.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 296.68 | 120.99 | 157.38 | 139.81 | 75.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 910.76 | 410.66 | 521.65 | 1265.96 | 1049.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 672.65 | 440.46 | 232.19 | 576.19 | 868.41 | 0.00 | 0.00 | 0.00 |
February | 887.20 | 587.26 | 299.95 | 778.64 | 875.89 | 0.00 | 0.00 | 0.00 |
March | 800.43 | 444.25 | 356.18 | 757.30 | 661.02 | 0.00 | 0.00 | 0.00 |
April | 621.10 | 245.60 | 375.50 | 609.18 | 499.75 | 0.00 | 0.00 | 0.00 |
May | 544.30 | 113.53 | 430.77 | 579.49 | 301.03 | 0.00 | 0.00 | 0.00 |
June | 510.81 | 78.08 | 432.73 | 654.78 | 162.00 | 0.00 | 0.00 | 0.00 |
July | 535.43 | 93.00 | 442.43 | 785.04 | 80.90 | 0.00 | 0.00 | 0.00 |
August | 715.01 | 265.21 | 449.80 | 1055.29 | 114.59 | 0.00 | 0.00 | 0.00 |
September | 775.80 | 401.28 | 374.53 | 989.89 | 238.58 | 0.00 | 0.00 | 0.00 |
October | 1062.78 | 666.44 | 396.34 | 1242.10 | 427.58 | 0.00 | 0.00 | 0.00 |
November | 736.95 | 442.57 | 294.38 | 699.73 | 646.59 | 0.00 | 0.00 | 0.00 |
December | 729.05 | 517.58 | 211.47 | 660.19 | 813.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 715.15 | 356.78 | 358.38 | 782.83 | 471.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 510.81 | 78.08 | 211.47 | 576.19 | 80.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1062.78 | 666.44 | 449.80 | 1242.10 | 875.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 672.65 | 440.46 | 232.19 | 576.19 | 868.41 | 0.00 | 0.00 | 0.00 |
February | 887.20 | 587.26 | 299.95 | 778.64 | 875.89 | 0.00 | 0.00 | 0.00 |
March | 800.42 | 444.25 | 356.17 | 757.30 | 661.02 | 0.00 | 0.00 | 0.00 |
April | 621.10 | 245.60 | 375.50 | 609.18 | 499.75 | 0.00 | 0.00 | 0.00 |
May | 544.30 | 113.53 | 430.77 | 579.49 | 301.03 | 0.00 | 0.00 | 0.00 |
June | 510.81 | 78.08 | 432.73 | 654.77 | 162.00 | 0.00 | 0.00 | 0.00 |
July | 535.43 | 93.00 | 442.43 | 785.04 | 80.90 | 0.00 | 0.00 | 0.00 |
August | 715.01 | 265.21 | 449.80 | 1055.29 | 114.59 | 0.00 | 0.00 | 0.00 |
September | 775.80 | 401.28 | 374.53 | 989.89 | 238.58 | 0.00 | 0.00 | 0.00 |
October | 1062.78 | 666.44 | 396.34 | 1242.10 | 427.58 | 0.00 | 0.00 | 0.00 |
November | 736.95 | 442.57 | 294.38 | 699.73 | 646.59 | 0.00 | 0.00 | 0.00 |
December | 729.05 | 517.58 | 211.47 | 660.19 | 813.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 715.15 | 356.78 | 358.38 | 782.83 | 471.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 510.81 | 78.08 | 211.47 | 576.19 | 80.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1062.78 | 666.44 | 449.80 | 1242.10 | 875.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 672.65 | 440.46 | 232.19 | 576.19 | 868.41 | 0.00 | 0.00 | 0.00 |
February | 887.20 | 587.26 | 299.95 | 778.64 | 875.89 | 0.00 | 0.00 | 0.00 |
March | 800.43 | 444.25 | 356.18 | 757.30 | 661.02 | 0.00 | 0.00 | 0.00 |
April | 621.10 | 245.60 | 375.50 | 609.18 | 499.75 | 0.00 | 0.00 | 0.00 |
May | 544.30 | 113.53 | 430.77 | 579.49 | 301.03 | 0.00 | 0.00 | 0.00 |
June | 510.81 | 78.08 | 432.73 | 654.78 | 162.00 | 0.00 | 0.00 | 0.00 |
July | 535.43 | 93.00 | 442.43 | 785.04 | 80.90 | 0.00 | 0.00 | 0.00 |
August | 715.01 | 265.21 | 449.80 | 1055.29 | 114.59 | 0.00 | 0.00 | 0.00 |
September | 775.80 | 401.28 | 374.53 | 989.89 | 238.58 | 0.00 | 0.00 | 0.00 |
October | 1062.78 | 666.44 | 396.34 | 1242.10 | 427.58 | 0.00 | 0.00 | 0.00 |
November | 736.95 | 442.57 | 294.38 | 699.73 | 646.59 | 0.00 | 0.00 | 0.00 |
December | 729.05 | 517.58 | 211.47 | 660.19 | 813.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 715.15 | 356.78 | 358.38 | 782.83 | 471.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 510.81 | 78.08 | 211.47 | 576.19 | 80.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1062.78 | 666.44 | 449.80 | 1242.10 | 875.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 672.65 | 440.46 | 232.19 | 576.19 | 868.41 | 0.00 | 0.00 | 0.00 |
February | 887.20 | 587.26 | 299.95 | 778.64 | 875.89 | 0.00 | 0.00 | 0.00 |
March | 800.42 | 444.25 | 356.17 | 757.30 | 661.02 | 0.00 | 0.00 | 0.00 |
April | 621.10 | 245.60 | 375.50 | 609.18 | 499.75 | 0.00 | 0.00 | 0.00 |
May | 544.30 | 113.53 | 430.77 | 579.49 | 301.03 | 0.00 | 0.00 | 0.00 |
June | 510.81 | 78.08 | 432.73 | 654.77 | 162.00 | 0.00 | 0.00 | 0.00 |
July | 535.43 | 93.00 | 442.43 | 785.04 | 80.90 | 0.00 | 0.00 | 0.00 |
August | 715.01 | 265.21 | 449.80 | 1055.29 | 114.59 | 0.00 | 0.00 | 0.00 |
September | 775.80 | 401.28 | 374.53 | 989.89 | 238.58 | 0.00 | 0.00 | 0.00 |
October | 1062.78 | 666.44 | 396.34 | 1242.10 | 427.58 | 0.00 | 0.00 | 0.00 |
November | 736.95 | 442.57 | 294.38 | 699.73 | 646.59 | 0.00 | 0.00 | 0.00 |
December | 729.05 | 517.58 | 211.47 | 660.19 | 813.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 715.15 | 356.78 | 358.38 | 782.83 | 471.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 510.81 | 78.08 | 211.47 | 576.19 | 80.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1062.78 | 666.44 | 449.80 | 1242.10 | 875.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 672.62 | 440.44 | 232.19 | 576.17 | 868.38 | 0.00 | 0.00 | 0.00 |
February | 887.17 | 587.23 | 299.93 | 778.61 | 875.86 | 0.00 | 0.00 | 0.00 |
March | 800.39 | 444.23 | 356.16 | 757.27 | 660.99 | 0.00 | 0.00 | 0.00 |
April | 621.08 | 245.59 | 375.48 | 609.15 | 499.73 | 0.00 | 0.00 | 0.00 |
May | 544.28 | 113.53 | 430.75 | 579.47 | 301.02 | 0.00 | 0.00 | 0.00 |
June | 510.79 | 78.08 | 432.71 | 654.75 | 161.99 | 0.00 | 0.00 | 0.00 |
July | 535.41 | 93.00 | 442.41 | 785.00 | 80.89 | 0.00 | 0.00 | 0.00 |
August | 714.98 | 265.20 | 449.78 | 1055.25 | 114.58 | 0.00 | 0.00 | 0.00 |
September | 775.77 | 401.26 | 374.51 | 989.85 | 238.57 | 0.00 | 0.00 | 0.00 |
October | 1062.74 | 666.42 | 396.33 | 1242.05 | 427.56 | 0.00 | 0.00 | 0.00 |
November | 736.92 | 442.56 | 294.36 | 699.70 | 646.56 | 0.00 | 0.00 | 0.00 |
December | 729.02 | 517.56 | 211.47 | 660.17 | 813.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 715.13 | 356.76 | 358.36 | 782.80 | 471.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 510.79 | 78.08 | 211.47 | 576.17 | 80.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1062.74 | 666.42 | 449.78 | 1242.05 | 875.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 297.93 | 122.03 | 175.90 | 139.28 | 1130.94 | 0.00 | 0.00 | 0.00 |
February | 439.34 | 192.96 | 246.38 | 234.53 | 1153.37 | 0.00 | 0.00 | 0.00 |
March | 648.74 | 299.51 | 349.23 | 483.40 | 814.60 | 0.00 | 0.00 | 0.00 |
April | 709.04 | 303.38 | 405.66 | 620.13 | 623.24 | 0.00 | 0.00 | 0.00 |
May | 825.96 | 313.67 | 512.29 | 879.80 | 360.23 | 0.00 | 0.00 | 0.00 |
June | 903.99 | 364.61 | 539.39 | 1125.02 | 212.68 | 0.00 | 0.00 | 0.00 |
July | 846.64 | 318.82 | 527.82 | 1150.45 | 124.77 | 0.00 | 0.00 | 0.00 |
August | 936.61 | 433.59 | 503.02 | 1273.87 | 167.89 | 0.00 | 0.00 | 0.00 |
September | 664.92 | 290.57 | 374.35 | 787.50 | 293.49 | 0.00 | 0.00 | 0.00 |
October | 659.22 | 320.56 | 338.66 | 669.50 | 528.64 | 0.00 | 0.00 | 0.00 |
November | 309.57 | 89.47 | 220.10 | 147.77 | 857.60 | 0.00 | 0.00 | 0.00 |
December | 275.35 | 119.15 | 156.21 | 123.81 | 1113.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 627.76 | 264.63 | 363.12 | 639.19 | 611.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 275.35 | 89.47 | 156.21 | 123.81 | 124.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 936.61 | 433.59 | 539.39 | 1273.87 | 1153.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 297.93 | 122.03 | 175.90 | 139.28 | 1130.94 | 0.00 | 0.00 | 0.00 |
February | 439.34 | 192.96 | 246.38 | 234.53 | 1153.37 | 0.00 | 0.00 | 0.00 |
March | 648.74 | 299.51 | 349.23 | 483.40 | 814.60 | 0.00 | 0.00 | 0.00 |
April | 709.04 | 303.38 | 405.66 | 620.13 | 623.24 | 0.00 | 0.00 | 0.00 |
May | 825.96 | 313.67 | 512.29 | 879.80 | 360.23 | 0.00 | 0.00 | 0.00 |
June | 903.99 | 364.61 | 539.39 | 1125.02 | 212.68 | 0.00 | 0.00 | 0.00 |
July | 846.64 | 318.82 | 527.82 | 1150.45 | 124.77 | 0.00 | 0.00 | 0.00 |
August | 936.61 | 433.59 | 503.02 | 1273.87 | 167.89 | 0.00 | 0.00 | 0.00 |
September | 664.92 | 290.57 | 374.35 | 787.50 | 293.49 | 0.00 | 0.00 | 0.00 |
October | 659.22 | 320.56 | 338.66 | 669.50 | 528.64 | 0.00 | 0.00 | 0.00 |
November | 309.57 | 89.47 | 220.10 | 147.77 | 857.60 | 0.00 | 0.00 | 0.00 |
December | 275.35 | 119.15 | 156.21 | 123.81 | 1113.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 627.76 | 264.63 | 363.12 | 639.19 | 611.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 275.35 | 89.47 | 156.21 | 123.81 | 124.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 936.61 | 433.59 | 539.39 | 1273.87 | 1153.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 297.92 | 122.03 | 175.89 | 139.28 | 1130.91 | 0.00 | 0.00 | 0.00 |
February | 439.33 | 192.96 | 246.38 | 234.53 | 1153.35 | 0.00 | 0.00 | 0.00 |
March | 648.73 | 299.50 | 349.23 | 483.39 | 814.59 | 0.00 | 0.00 | 0.00 |
April | 709.03 | 303.38 | 405.65 | 620.12 | 623.22 | 0.00 | 0.00 | 0.00 |
May | 825.95 | 313.66 | 512.28 | 879.79 | 360.23 | 0.00 | 0.00 | 0.00 |
June | 903.97 | 364.60 | 539.38 | 1125.00 | 212.68 | 0.00 | 0.00 | 0.00 |
July | 846.62 | 318.81 | 527.81 | 1150.43 | 124.77 | 0.00 | 0.00 | 0.00 |
August | 936.59 | 433.58 | 503.01 | 1273.85 | 167.88 | 0.00 | 0.00 | 0.00 |
September | 664.91 | 290.56 | 374.34 | 787.49 | 293.48 | 0.00 | 0.00 | 0.00 |
October | 659.21 | 320.56 | 338.65 | 669.49 | 528.63 | 0.00 | 0.00 | 0.00 |
November | 309.56 | 89.47 | 220.10 | 147.76 | 857.59 | 0.00 | 0.00 | 0.00 |
December | 275.35 | 119.14 | 156.20 | 123.81 | 1113.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 627.74 | 264.63 | 363.12 | 639.17 | 611.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 275.35 | 89.47 | 156.20 | 123.81 | 124.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 936.59 | 433.58 | 539.38 | 1273.85 | 1153.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 650.12 | 0.00 | 650.12 | 4.66 | 4771.23 | 0.00 | 0.00 | 0.00 |
February | 889.66 | 0.00 | 889.66 | 29.62 | 5023.46 | 0.00 | 0.00 | 0.00 |
March | 1233.74 | 0.00 | 1233.74 | 252.51 | 3320.39 | 0.00 | 0.00 | 0.00 |
April | 1481.89 | 4.21 | 1477.67 | 736.10 | 2288.33 | 0.00 | 0.00 | 0.00 |
May | 1965.99 | 65.51 | 1900.49 | 1621.44 | 1326.27 | 0.00 | 0.00 | 0.00 |
June | 2084.91 | 112.03 | 1972.88 | 2443.82 | 711.95 | 0.00 | 0.00 | 0.00 |
July | 2014.86 | 72.86 | 1942.00 | 2834.09 | 387.06 | 0.00 | 0.00 | 0.00 |
August | 1785.07 | 21.24 | 1763.83 | 2478.98 | 532.87 | 0.00 | 0.00 | 0.00 |
September | 1345.65 | 0.25 | 1345.40 | 1354.80 | 1063.47 | 0.00 | 0.00 | 0.00 |
October | 1164.56 | 0.00 | 1164.56 | 731.19 | 1986.13 | 0.00 | 0.00 | 0.00 |
November | 816.83 | 0.00 | 816.83 | 128.32 | 3319.30 | 0.00 | 0.00 | 0.00 |
December | 567.08 | 0.00 | 567.08 | 4.56 | 4452.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1335.93 | 23.13 | 1312.79 | 1058.83 | 2417.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 567.08 | 0.00 | 567.08 | 4.56 | 387.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2084.91 | 112.03 | 1972.88 | 2834.09 | 5023.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 905.35 | 362.97 | 542.38 | 432.97 | 2920.50 | 0.00 | 0.00 | 0.00 |
February | 1404.00 | 654.97 | 749.03 | 787.46 | 2963.42 | 0.00 | 0.00 | 0.00 |
March | 1791.07 | 761.75 | 1029.31 | 1312.46 | 2126.92 | 0.00 | 0.00 | 0.00 |
April | 2149.41 | 941.51 | 1207.90 | 1915.33 | 1477.14 | 0.00 | 0.00 | 0.00 |
May | 2606.78 | 1041.83 | 1564.95 | 2762.01 | 896.87 | 0.00 | 0.00 | 0.00 |
June | 2415.93 | 874.55 | 1541.38 | 3006.71 | 473.34 | 0.00 | 0.00 | 0.00 |
July | 2426.51 | 875.67 | 1550.84 | 3359.12 | 251.33 | 0.00 | 0.00 | 0.00 |
August | 2732.31 | 1232.00 | 1500.31 | 3742.39 | 350.39 | 0.00 | 0.00 | 0.00 |
September | 2037.77 | 914.27 | 1123.50 | 2389.10 | 685.42 | 0.00 | 0.00 | 0.00 |
October | 1847.39 | 837.30 | 1010.09 | 1853.87 | 1284.35 | 0.00 | 0.00 | 0.00 |
November | 1142.47 | 438.72 | 703.75 | 747.44 | 2049.36 | 0.00 | 0.00 | 0.00 |
December | 890.05 | 417.91 | 472.14 | 483.17 | 2702.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1865.38 | 780.34 | 1085.04 | 1907.21 | 1507.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 890.05 | 362.97 | 472.14 | 432.97 | 251.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2732.31 | 1232.00 | 1564.95 | 3742.39 | 2963.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3363.21 | 2202.25 | 1160.96 | 2862.80 | 4184.58 | 0.00 | 0.00 | 0.00 |
February | 4435.96 | 2936.25 | 1499.72 | 3852.26 | 4283.08 | 0.00 | 0.00 | 0.00 |
March | 4002.08 | 2221.22 | 1780.85 | 3737.70 | 3206.87 | 0.00 | 0.00 | 0.00 |
April | 3105.47 | 1228.00 | 1877.47 | 3025.13 | 2388.14 | 0.00 | 0.00 | 0.00 |
May | 2721.48 | 567.66 | 2153.83 | 2874.28 | 1450.53 | 0.00 | 0.00 | 0.00 |
June | 2554.03 | 390.41 | 2163.62 | 3256.37 | 775.04 | 0.00 | 0.00 | 0.00 |
July | 2677.14 | 465.02 | 2212.12 | 3905.16 | 410.70 | 0.00 | 0.00 | 0.00 |
August | 3575.02 | 1326.03 | 2248.99 | 5242.58 | 589.06 | 0.00 | 0.00 | 0.00 |
September | 3878.97 | 2006.36 | 1872.61 | 4910.18 | 1145.27 | 0.00 | 0.00 | 0.00 |
October | 5313.86 | 3332.17 | 1981.69 | 6134.67 | 2085.71 | 0.00 | 0.00 | 0.00 |
November | 3684.71 | 2212.84 | 1471.86 | 3481.39 | 3075.36 | 0.00 | 0.00 | 0.00 |
December | 3645.22 | 2587.86 | 1057.36 | 3288.40 | 3889.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3575.73 | 1783.87 | 1791.86 | 3883.48 | 2278.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2554.03 | 390.41 | 1057.36 | 2862.80 | 410.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5313.86 | 3332.17 | 2248.99 | 6134.67 | 4283.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 893.78 | 366.10 | 527.69 | 435.14 | 3064.70 | 0.00 | 0.00 | 0.00 |
February | 1318.01 | 578.87 | 739.13 | 725.86 | 3178.11 | 0.00 | 0.00 | 0.00 |
March | 1946.20 | 898.51 | 1047.69 | 1491.57 | 2164.31 | 0.00 | 0.00 | 0.00 |
April | 2127.11 | 910.13 | 1216.97 | 1941.06 | 1587.56 | 0.00 | 0.00 | 0.00 |
May | 2477.86 | 941.00 | 1536.87 | 2677.25 | 972.51 | 0.00 | 0.00 | 0.00 |
June | 2711.95 | 1093.81 | 1618.14 | 3407.44 | 555.01 | 0.00 | 0.00 | 0.00 |
July | 2539.88 | 956.44 | 1583.44 | 3503.87 | 316.18 | 0.00 | 0.00 | 0.00 |
August | 2809.80 | 1300.75 | 1509.05 | 3884.71 | 430.02 | 0.00 | 0.00 | 0.00 |
September | 1994.74 | 871.70 | 1123.04 | 2410.12 | 756.81 | 0.00 | 0.00 | 0.00 |
October | 1977.63 | 961.67 | 1015.96 | 2060.05 | 1391.40 | 0.00 | 0.00 | 0.00 |
November | 928.69 | 268.40 | 660.29 | 494.17 | 2180.93 | 0.00 | 0.00 | 0.00 |
December | 826.05 | 357.43 | 468.62 | 410.24 | 2869.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1883.25 | 793.89 | 1089.36 | 1962.34 | 1613.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 826.05 | 268.40 | 468.62 | 410.24 | 316.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2809.80 | 1300.75 | 1618.14 | 3884.71 | 3178.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 650.12 | 0.00 | 650.12 | 6.54 | 4555.63 | 0.00 | 0.00 | 0.00 |
February | 889.66 | 0.00 | 889.66 | 42.19 | 4777.06 | 0.00 | 0.00 | 0.00 |
March | 1233.74 | 0.00 | 1233.74 | 275.58 | 3050.44 | 0.00 | 0.00 | 0.00 |
April | 1481.89 | 4.21 | 1477.67 | 780.62 | 2076.15 | 0.00 | 0.00 | 0.00 |
May | 1965.99 | 65.51 | 1900.49 | 1671.39 | 1206.17 | 0.00 | 0.00 | 0.00 |
June | 2084.91 | 112.03 | 1972.88 | 2455.67 | 664.38 | 0.00 | 0.00 | 0.00 |
July | 2014.86 | 72.86 | 1942.00 | 2825.03 | 364.36 | 0.00 | 0.00 | 0.00 |
August | 1785.07 | 21.24 | 1763.83 | 2479.75 | 495.69 | 0.00 | 0.00 | 0.00 |
September | 1345.65 | 0.25 | 1345.40 | 1393.58 | 951.02 | 0.00 | 0.00 | 0.00 |
October | 1164.56 | 0.00 | 1164.56 | 797.52 | 1748.54 | 0.00 | 0.00 | 0.00 |
November | 816.83 | 0.00 | 816.83 | 158.31 | 2995.55 | 0.00 | 0.00 | 0.00 |
December | 567.08 | 0.00 | 567.08 | 12.19 | 4110.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1335.93 | 23.13 | 1312.79 | 1082.01 | 2235.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 567.08 | 0.00 | 567.08 | 6.54 | 364.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2084.91 | 112.03 | 1972.88 | 2825.03 | 4777.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 905.35 | 362.97 | 542.38 | 446.42 | 2780.57 | 0.00 | 0.00 | 0.00 |
February | 1404.00 | 654.97 | 749.03 | 820.84 | 2800.71 | 0.00 | 0.00 | 0.00 |
March | 1791.07 | 761.75 | 1029.31 | 1352.46 | 1943.48 | 0.00 | 0.00 | 0.00 |
April | 2149.41 | 941.51 | 1207.90 | 1953.66 | 1353.49 | 0.00 | 0.00 | 0.00 |
May | 2606.78 | 1041.83 | 1564.95 | 2783.57 | 834.09 | 0.00 | 0.00 | 0.00 |
June | 2415.93 | 874.55 | 1541.38 | 3000.14 | 454.69 | 0.00 | 0.00 | 0.00 |
July | 2426.51 | 875.67 | 1550.84 | 3338.54 | 247.49 | 0.00 | 0.00 | 0.00 |
August | 2732.31 | 1232.00 | 1500.31 | 3726.35 | 338.91 | 0.00 | 0.00 | 0.00 |
September | 2037.77 | 914.27 | 1123.50 | 2405.87 | 631.71 | 0.00 | 0.00 | 0.00 |
October | 1847.39 | 837.30 | 1010.09 | 1908.56 | 1146.81 | 0.00 | 0.00 | 0.00 |
November | 1142.47 | 438.72 | 703.75 | 800.53 | 1838.34 | 0.00 | 0.00 | 0.00 |
December | 890.05 | 417.91 | 472.14 | 510.92 | 2483.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1865.38 | 780.34 | 1085.04 | 1928.39 | 1396.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 890.05 | 362.97 | 472.14 | 446.42 | 247.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2732.31 | 1232.00 | 1564.95 | 3726.35 | 2800.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3363.21 | 2202.25 | 1160.96 | 2895.66 | 3951.06 | 0.00 | 0.00 | 0.00 |
February | 4435.96 | 2936.25 | 1499.72 | 3905.71 | 4011.36 | 0.00 | 0.00 | 0.00 |
March | 4002.08 | 2221.22 | 1780.85 | 3771.19 | 2927.59 | 0.00 | 0.00 | 0.00 |
April | 3105.47 | 1228.00 | 1877.47 | 3060.68 | 2175.24 | 0.00 | 0.00 | 0.00 |
May | 2721.48 | 567.66 | 2153.83 | 2901.82 | 1323.88 | 0.00 | 0.00 | 0.00 |
June | 2554.03 | 390.41 | 2163.62 | 3254.13 | 724.05 | 0.00 | 0.00 | 0.00 |
July | 2677.14 | 465.02 | 2212.12 | 3887.89 | 385.42 | 0.00 | 0.00 | 0.00 |
August | 3575.02 | 1326.03 | 2248.99 | 5224.73 | 550.85 | 0.00 | 0.00 | 0.00 |
September | 3878.97 | 2006.36 | 1872.61 | 4926.40 | 1038.70 | 0.00 | 0.00 | 0.00 |
October | 5313.86 | 3332.17 | 1981.69 | 6181.94 | 1860.63 | 0.00 | 0.00 | 0.00 |
November | 3684.71 | 2212.84 | 1471.86 | 3560.17 | 2757.29 | 0.00 | 0.00 | 0.00 |
December | 3645.22 | 2587.86 | 1057.36 | 3360.66 | 3547.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3575.73 | 1783.87 | 1791.86 | 3913.27 | 2093.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2554.03 | 390.41 | 1057.36 | 2895.66 | 385.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5313.86 | 3332.17 | 2248.99 | 6181.94 | 4011.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 893.78 | 366.10 | 527.69 | 439.15 | 2928.52 | 0.00 | 0.00 | 0.00 |
February | 1318.01 | 578.87 | 739.13 | 731.39 | 3029.14 | 0.00 | 0.00 | 0.00 |
March | 1946.20 | 898.51 | 1047.69 | 1497.76 | 2011.16 | 0.00 | 0.00 | 0.00 |
April | 2127.11 | 910.13 | 1216.97 | 1947.00 | 1471.25 | 0.00 | 0.00 | 0.00 |
May | 2477.86 | 941.00 | 1536.87 | 2675.92 | 908.58 | 0.00 | 0.00 | 0.00 |
June | 2711.95 | 1093.81 | 1618.14 | 3389.76 | 529.75 | 0.00 | 0.00 | 0.00 |
July | 2539.88 | 956.44 | 1583.44 | 3479.58 | 304.74 | 0.00 | 0.00 | 0.00 |
August | 2809.80 | 1300.75 | 1509.05 | 3866.56 | 411.54 | 0.00 | 0.00 | 0.00 |
September | 1994.74 | 871.70 | 1123.04 | 2410.37 | 704.46 | 0.00 | 0.00 | 0.00 |
October | 1977.63 | 961.67 | 1015.96 | 2075.22 | 1267.16 | 0.00 | 0.00 | 0.00 |
November | 928.69 | 268.40 | 660.29 | 510.51 | 2002.80 | 0.00 | 0.00 | 0.00 |
December | 826.05 | 357.43 | 468.62 | 421.17 | 2669.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1883.25 | 793.89 | 1089.36 | 1962.53 | 1511.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 826.05 | 268.40 | 468.62 | 421.17 | 304.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2809.80 | 1300.75 | 1618.14 | 3866.56 | 3029.14 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.348261E+09 | 0.00 | 0.348261E+09 | 456065.79 | 0.278348E+10 |
February | 0.430459E+09 | 0.00 | 0.430459E+09 | 6913190.89 | 0.260187E+10 |
March | 0.660897E+09 | 0.00 | 0.660897E+09 | 0.103348E+09 | 0.196743E+10 |
April | 0.768220E+09 | 2185054.17 | 0.766035E+09 | 0.326535E+09 | 0.134726E+10 |
May | 0.105316E+10 | 35091748.52 | 0.101806E+10 | 0.821088E+09 | 0.786872E+09 |
June | 0.108083E+10 | 58077577.97 | 0.102275E+10 | 0.124192E+10 | 0.406069E+09 |
July | 0.107934E+10 | 39032395.63 | 0.104030E+10 | 0.149372E+10 | 0.224017E+09 |
August | 0.956240E+09 | 11380604.55 | 0.944860E+09 | 0.130058E+10 | 0.305791E+09 |
September | 0.697593E+09 | 130630.86 | 0.697462E+09 | 0.661700E+09 | 0.637056E+09 |
October | 0.623841E+09 | 0.00 | 0.623841E+09 | 0.338389E+09 | 0.122236E+10 |
November | 0.423449E+09 | 0.00 | 0.423449E+09 | 43437986.23 | 0.198029E+10 |
December | 0.303776E+09 | 0.00 | 0.303776E+09 | 556694.36 | 0.267268E+10 |
Annual Sum or Average | 0.842606E+10 | 0.145898E+09 | 0.828016E+10 | 0.633864E+10 | 0.169352E+11 |
Minimum of Months | 0.303776E+09 | 0.00 | 0.303776E+09 | 456065.79 | 0.224017E+09 |
Maximum of Months | 0.108083E+10 | 58077577.97 | 0.104030E+10 | 0.149372E+10 | 0.278348E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.348260E+09 | 0.00 | 0.348260E+09 | 456059.70 | 0.278348E+10 |
February | 0.430459E+09 | 0.00 | 0.430459E+09 | 6913150.33 | 0.260187E+10 |
March | 0.660896E+09 | 0.00 | 0.660896E+09 | 0.103348E+09 | 0.196743E+10 |
April | 0.768219E+09 | 2185051.55 | 0.766034E+09 | 0.326535E+09 | 0.134726E+10 |
May | 0.105316E+10 | 35091706.41 | 0.101806E+10 | 0.821087E+09 | 0.786872E+09 |
June | 0.108083E+10 | 58077508.28 | 0.102275E+10 | 0.124191E+10 | 0.406069E+09 |
July | 0.107934E+10 | 39032348.79 | 0.104030E+10 | 0.149372E+10 | 0.224017E+09 |
August | 0.956239E+09 | 11380590.89 | 0.944859E+09 | 0.130058E+10 | 0.305791E+09 |
September | 0.697593E+09 | 130630.70 | 0.697462E+09 | 0.661700E+09 | 0.637056E+09 |
October | 0.623840E+09 | 0.00 | 0.623840E+09 | 0.338388E+09 | 0.122236E+10 |
November | 0.423449E+09 | 0.00 | 0.423449E+09 | 43437861.25 | 0.198029E+10 |
December | 0.303776E+09 | 0.00 | 0.303776E+09 | 556688.69 | 0.267268E+10 |
Annual Sum or Average | 0.842605E+10 | 0.145898E+09 | 0.828015E+10 | 0.633864E+10 | 0.169352E+11 |
Minimum of Months | 0.303776E+09 | 0.00 | 0.303776E+09 | 456059.70 | 0.224017E+09 |
Maximum of Months | 0.108083E+10 | 58077508.28 | 0.104030E+10 | 0.149372E+10 | 0.278348E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.348261E+09 | 0.00 | 0.348261E+09 | 456065.79 | 0.278348E+10 |
February | 0.430459E+09 | 0.00 | 0.430459E+09 | 6913190.89 | 0.260187E+10 |
March | 0.660897E+09 | 0.00 | 0.660897E+09 | 0.103348E+09 | 0.196743E+10 |
April | 0.768220E+09 | 2185054.17 | 0.766035E+09 | 0.326535E+09 | 0.134726E+10 |
May | 0.105316E+10 | 35091748.52 | 0.101806E+10 | 0.821088E+09 | 0.786872E+09 |
June | 0.108083E+10 | 58077577.97 | 0.102275E+10 | 0.124192E+10 | 0.406069E+09 |
July | 0.107934E+10 | 39032395.63 | 0.104030E+10 | 0.149372E+10 | 0.224017E+09 |
August | 0.956240E+09 | 11380604.55 | 0.944860E+09 | 0.130058E+10 | 0.305791E+09 |
September | 0.697593E+09 | 130630.86 | 0.697462E+09 | 0.661700E+09 | 0.637056E+09 |
October | 0.623841E+09 | 0.00 | 0.623841E+09 | 0.338389E+09 | 0.122236E+10 |
November | 0.423449E+09 | 0.00 | 0.423449E+09 | 43437986.23 | 0.198029E+10 |
December | 0.303776E+09 | 0.00 | 0.303776E+09 | 556694.36 | 0.267268E+10 |
Annual Sum or Average | 0.842606E+10 | 0.145898E+09 | 0.828016E+10 | 0.633864E+10 | 0.169352E+11 |
Minimum of Months | 0.303776E+09 | 0.00 | 0.303776E+09 | 456065.79 | 0.224017E+09 |
Maximum of Months | 0.108083E+10 | 58077577.97 | 0.104030E+10 | 0.149372E+10 | 0.278348E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.348260E+09 | 0.00 | 0.348260E+09 | 456059.70 | 0.278348E+10 |
February | 0.430459E+09 | 0.00 | 0.430459E+09 | 6913150.33 | 0.260187E+10 |
March | 0.660896E+09 | 0.00 | 0.660896E+09 | 0.103348E+09 | 0.196743E+10 |
April | 0.768219E+09 | 2185051.55 | 0.766034E+09 | 0.326535E+09 | 0.134726E+10 |
May | 0.105316E+10 | 35091706.41 | 0.101806E+10 | 0.821087E+09 | 0.786872E+09 |
June | 0.108083E+10 | 58077508.28 | 0.102275E+10 | 0.124191E+10 | 0.406069E+09 |
July | 0.107934E+10 | 39032348.79 | 0.104030E+10 | 0.149372E+10 | 0.224017E+09 |
August | 0.956239E+09 | 11380590.89 | 0.944859E+09 | 0.130058E+10 | 0.305791E+09 |
September | 0.697593E+09 | 130630.70 | 0.697462E+09 | 0.661700E+09 | 0.637056E+09 |
October | 0.623840E+09 | 0.00 | 0.623840E+09 | 0.338388E+09 | 0.122236E+10 |
November | 0.423449E+09 | 0.00 | 0.423449E+09 | 43437861.25 | 0.198029E+10 |
December | 0.303776E+09 | 0.00 | 0.303776E+09 | 556688.69 | 0.267268E+10 |
Annual Sum or Average | 0.842605E+10 | 0.145898E+09 | 0.828015E+10 | 0.633864E+10 | 0.169352E+11 |
Minimum of Months | 0.303776E+09 | 0.00 | 0.303776E+09 | 456059.70 | 0.224017E+09 |
Maximum of Months | 0.108083E+10 | 58077508.28 | 0.104030E+10 | 0.149372E+10 | 0.278348E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.348247E+09 | 0.00 | 0.348247E+09 | 456047.41 | 0.278337E+10 |
February | 0.430442E+09 | 0.00 | 0.430442E+09 | 6912912.26 | 0.260177E+10 |
March | 0.660870E+09 | 0.00 | 0.660870E+09 | 0.103344E+09 | 0.196735E+10 |
April | 0.768189E+09 | 2184966.11 | 0.766004E+09 | 0.326522E+09 | 0.134721E+10 |
May | 0.105311E+10 | 35090334.16 | 0.101802E+10 | 0.821054E+09 | 0.786840E+09 |
June | 0.108079E+10 | 58075237.18 | 0.102271E+10 | 0.124187E+10 | 0.406052E+09 |
July | 0.107929E+10 | 39030822.45 | 0.104026E+10 | 0.149366E+10 | 0.224008E+09 |
August | 0.956202E+09 | 11380145.86 | 0.944821E+09 | 0.130053E+10 | 0.305779E+09 |
September | 0.697565E+09 | 130625.60 | 0.697434E+09 | 0.661674E+09 | 0.637030E+09 |
October | 0.623816E+09 | 0.00 | 0.623816E+09 | 0.338375E+09 | 0.122231E+10 |
November | 0.423432E+09 | 0.00 | 0.423432E+09 | 43436235.49 | 0.198021E+10 |
December | 0.303764E+09 | 0.00 | 0.303764E+09 | 556671.92 | 0.267257E+10 |
Annual Sum or Average | 0.842572E+10 | 0.145892E+09 | 0.827983E+10 | 0.633839E+10 | 0.169345E+11 |
Minimum of Months | 0.303764E+09 | 0.00 | 0.303764E+09 | 456047.41 | 0.224008E+09 |
Maximum of Months | 0.108079E+10 | 58075237.18 | 0.104026E+10 | 0.149366E+10 | 0.278337E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.808304E+09 | 0.324064E+09 | 0.484239E+09 | 0.374468E+09 | 0.281005E+10 |
February | 0.113220E+10 | 0.528171E+09 | 0.604027E+09 | 0.621908E+09 | 0.253098E+10 |
March | 0.159908E+10 | 0.680101E+09 | 0.918981E+09 | 0.117566E+10 | 0.201069E+10 |
April | 0.185711E+10 | 0.813469E+09 | 0.104364E+10 | 0.166326E+10 | 0.136013E+10 |
May | 0.232736E+10 | 0.930151E+09 | 0.139720E+10 | 0.249590E+10 | 0.844391E+09 |
June | 0.208739E+10 | 0.755619E+09 | 0.133177E+10 | 0.262586E+10 | 0.424822E+09 |
July | 0.216641E+10 | 0.781803E+09 | 0.138460E+10 | 0.304060E+10 | 0.201588E+09 |
August | 0.243943E+10 | 0.109994E+10 | 0.133949E+10 | 0.339080E+10 | 0.281061E+09 |
September | 0.176065E+10 | 0.789935E+09 | 0.970715E+09 | 0.207997E+10 | 0.639850E+09 |
October | 0.164937E+10 | 0.747548E+09 | 0.901817E+09 | 0.165493E+10 | 0.124278E+10 |
November | 0.987101E+09 | 0.379057E+09 | 0.608044E+09 | 0.628180E+09 | 0.194876E+10 |
December | 0.794642E+09 | 0.373115E+09 | 0.421527E+09 | 0.415566E+09 | 0.263132E+10 |
Annual Sum or Average | 0.196090E+11 | 0.820297E+10 | 0.114061E+11 | 0.201671E+11 | 0.169264E+11 |
Minimum of Months | 0.794642E+09 | 0.324064E+09 | 0.421527E+09 | 0.374468E+09 | 0.201588E+09 |
Maximum of Months | 0.243943E+10 | 0.109994E+10 | 0.139720E+10 | 0.339080E+10 | 0.281005E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.808304E+09 | 0.324064E+09 | 0.484239E+09 | 0.374468E+09 | 0.281005E+10 |
February | 0.113220E+10 | 0.528171E+09 | 0.604027E+09 | 0.621908E+09 | 0.253098E+10 |
March | 0.159908E+10 | 0.680101E+09 | 0.918981E+09 | 0.117566E+10 | 0.201069E+10 |
April | 0.185711E+10 | 0.813469E+09 | 0.104364E+10 | 0.166326E+10 | 0.136013E+10 |
May | 0.232736E+10 | 0.930151E+09 | 0.139720E+10 | 0.249590E+10 | 0.844391E+09 |
June | 0.208739E+10 | 0.755619E+09 | 0.133177E+10 | 0.262586E+10 | 0.424822E+09 |
July | 0.216641E+10 | 0.781803E+09 | 0.138460E+10 | 0.304060E+10 | 0.201588E+09 |
August | 0.243943E+10 | 0.109994E+10 | 0.133949E+10 | 0.339080E+10 | 0.281061E+09 |
September | 0.176065E+10 | 0.789935E+09 | 0.970715E+09 | 0.207997E+10 | 0.639850E+09 |
October | 0.164937E+10 | 0.747548E+09 | 0.901817E+09 | 0.165493E+10 | 0.124278E+10 |
November | 0.987101E+09 | 0.379057E+09 | 0.608044E+09 | 0.628180E+09 | 0.194876E+10 |
December | 0.794642E+09 | 0.373115E+09 | 0.421527E+09 | 0.415566E+09 | 0.263132E+10 |
Annual Sum or Average | 0.196090E+11 | 0.820297E+10 | 0.114061E+11 | 0.201671E+11 | 0.169264E+11 |
Minimum of Months | 0.794642E+09 | 0.324064E+09 | 0.421527E+09 | 0.374468E+09 | 0.201588E+09 |
Maximum of Months | 0.243943E+10 | 0.109994E+10 | 0.139720E+10 | 0.339080E+10 | 0.281005E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.808289E+09 | 0.324059E+09 | 0.484230E+09 | 0.374462E+09 | 0.281000E+10 |
February | 0.113218E+10 | 0.528161E+09 | 0.604016E+09 | 0.621897E+09 | 0.253093E+10 |
March | 0.159905E+10 | 0.680088E+09 | 0.918964E+09 | 0.117564E+10 | 0.201065E+10 |
April | 0.185707E+10 | 0.813455E+09 | 0.104362E+10 | 0.166323E+10 | 0.136010E+10 |
May | 0.232731E+10 | 0.930134E+09 | 0.139718E+10 | 0.249585E+10 | 0.844375E+09 |
June | 0.208735E+10 | 0.755605E+09 | 0.133174E+10 | 0.262581E+10 | 0.424814E+09 |
July | 0.216637E+10 | 0.781789E+09 | 0.138458E+10 | 0.304054E+10 | 0.201584E+09 |
August | 0.243938E+10 | 0.109992E+10 | 0.133947E+10 | 0.339073E+10 | 0.281056E+09 |
September | 0.176062E+10 | 0.789920E+09 | 0.970698E+09 | 0.207993E+10 | 0.639838E+09 |
October | 0.164934E+10 | 0.747535E+09 | 0.901800E+09 | 0.165490E+10 | 0.124275E+10 |
November | 0.987083E+09 | 0.379050E+09 | 0.608033E+09 | 0.628168E+09 | 0.194873E+10 |
December | 0.794627E+09 | 0.373108E+09 | 0.421519E+09 | 0.415558E+09 | 0.263127E+10 |
Annual Sum or Average | 0.196087E+11 | 0.820282E+10 | 0.114058E+11 | 0.201667E+11 | 0.169261E+11 |
Minimum of Months | 0.794627E+09 | 0.324059E+09 | 0.421519E+09 | 0.374462E+09 | 0.201584E+09 |
Maximum of Months | 0.243938E+10 | 0.109992E+10 | 0.139718E+10 | 0.339073E+10 | 0.281000E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.180163E+10 | 0.117972E+10 | 0.621910E+09 | 0.154327E+10 | 0.232595E+10 |
February | 0.214632E+10 | 0.142069E+10 | 0.725631E+09 | 0.188368E+10 | 0.211895E+10 |
March | 0.214386E+10 | 0.118988E+10 | 0.953980E+09 | 0.202836E+10 | 0.177047E+10 |
April | 0.160989E+10 | 0.636601E+09 | 0.973294E+09 | 0.157899E+10 | 0.129535E+10 |
May | 0.145786E+10 | 0.304087E+09 | 0.115378E+10 | 0.155211E+10 | 0.806285E+09 |
June | 0.132403E+10 | 0.202391E+09 | 0.112163E+10 | 0.169718E+10 | 0.419897E+09 |
July | 0.143411E+10 | 0.249104E+09 | 0.118500E+10 | 0.210264E+10 | 0.216673E+09 |
August | 0.191509E+10 | 0.710339E+09 | 0.120475E+10 | 0.282649E+10 | 0.306912E+09 |
September | 0.201088E+10 | 0.104011E+10 | 0.970772E+09 | 0.256579E+10 | 0.618399E+09 |
October | 0.284656E+10 | 0.178500E+10 | 0.106156E+10 | 0.332684E+10 | 0.114522E+10 |
November | 0.191018E+10 | 0.114715E+10 | 0.763024E+09 | 0.181370E+10 | 0.167596E+10 |
December | 0.195269E+10 | 0.138628E+10 | 0.566412E+09 | 0.176826E+10 | 0.217792E+10 |
Annual Sum or Average | 0.225531E+11 | 0.112514E+11 | 0.113017E+11 | 0.246873E+11 | 0.148780E+11 |
Minimum of Months | 0.132403E+10 | 0.202391E+09 | 0.566412E+09 | 0.154327E+10 | 0.216673E+09 |
Maximum of Months | 0.284656E+10 | 0.178500E+10 | 0.120475E+10 | 0.332684E+10 | 0.232595E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.180163E+10 | 0.117972E+10 | 0.621909E+09 | 0.154327E+10 | 0.232595E+10 |
February | 0.214632E+10 | 0.142069E+10 | 0.725631E+09 | 0.188368E+10 | 0.211895E+10 |
March | 0.214386E+10 | 0.118988E+10 | 0.953979E+09 | 0.202836E+10 | 0.177047E+10 |
April | 0.160989E+10 | 0.636600E+09 | 0.973293E+09 | 0.157899E+10 | 0.129535E+10 |
May | 0.145786E+10 | 0.304087E+09 | 0.115377E+10 | 0.155211E+10 | 0.806285E+09 |
June | 0.132402E+10 | 0.202391E+09 | 0.112163E+10 | 0.169718E+10 | 0.419897E+09 |
July | 0.143410E+10 | 0.249104E+09 | 0.118500E+10 | 0.210264E+10 | 0.216673E+09 |
August | 0.191509E+10 | 0.710338E+09 | 0.120475E+10 | 0.282649E+10 | 0.306912E+09 |
September | 0.201088E+10 | 0.104011E+10 | 0.970771E+09 | 0.256579E+10 | 0.618398E+09 |
October | 0.284656E+10 | 0.178500E+10 | 0.106156E+10 | 0.332684E+10 | 0.114522E+10 |
November | 0.191017E+10 | 0.114715E+10 | 0.763023E+09 | 0.181370E+10 | 0.167596E+10 |
December | 0.195269E+10 | 0.138628E+10 | 0.566411E+09 | 0.176826E+10 | 0.217792E+10 |
Annual Sum or Average | 0.225531E+11 | 0.112513E+11 | 0.113017E+11 | 0.246873E+11 | 0.148780E+11 |
Minimum of Months | 0.132402E+10 | 0.202391E+09 | 0.566411E+09 | 0.154327E+10 | 0.216673E+09 |
Maximum of Months | 0.284656E+10 | 0.178500E+10 | 0.120475E+10 | 0.332684E+10 | 0.232595E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.180163E+10 | 0.117972E+10 | 0.621910E+09 | 0.154327E+10 | 0.232595E+10 |
February | 0.214632E+10 | 0.142069E+10 | 0.725631E+09 | 0.188368E+10 | 0.211895E+10 |
March | 0.214386E+10 | 0.118988E+10 | 0.953980E+09 | 0.202836E+10 | 0.177047E+10 |
April | 0.160989E+10 | 0.636601E+09 | 0.973294E+09 | 0.157899E+10 | 0.129535E+10 |
May | 0.145786E+10 | 0.304087E+09 | 0.115378E+10 | 0.155211E+10 | 0.806285E+09 |
June | 0.132403E+10 | 0.202391E+09 | 0.112163E+10 | 0.169718E+10 | 0.419897E+09 |
July | 0.143411E+10 | 0.249104E+09 | 0.118500E+10 | 0.210264E+10 | 0.216673E+09 |
August | 0.191509E+10 | 0.710339E+09 | 0.120475E+10 | 0.282649E+10 | 0.306912E+09 |
September | 0.201088E+10 | 0.104011E+10 | 0.970772E+09 | 0.256579E+10 | 0.618399E+09 |
October | 0.284656E+10 | 0.178500E+10 | 0.106156E+10 | 0.332684E+10 | 0.114522E+10 |
November | 0.191018E+10 | 0.114715E+10 | 0.763024E+09 | 0.181370E+10 | 0.167596E+10 |
December | 0.195269E+10 | 0.138628E+10 | 0.566412E+09 | 0.176826E+10 | 0.217792E+10 |
Annual Sum or Average | 0.225531E+11 | 0.112514E+11 | 0.113017E+11 | 0.246873E+11 | 0.148780E+11 |
Minimum of Months | 0.132403E+10 | 0.202391E+09 | 0.566412E+09 | 0.154327E+10 | 0.216673E+09 |
Maximum of Months | 0.284656E+10 | 0.178500E+10 | 0.120475E+10 | 0.332684E+10 | 0.232595E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.180163E+10 | 0.117972E+10 | 0.621909E+09 | 0.154327E+10 | 0.232595E+10 |
February | 0.214632E+10 | 0.142069E+10 | 0.725631E+09 | 0.188368E+10 | 0.211895E+10 |
March | 0.214386E+10 | 0.118988E+10 | 0.953979E+09 | 0.202836E+10 | 0.177047E+10 |
April | 0.160989E+10 | 0.636600E+09 | 0.973293E+09 | 0.157899E+10 | 0.129535E+10 |
May | 0.145786E+10 | 0.304087E+09 | 0.115377E+10 | 0.155211E+10 | 0.806285E+09 |
June | 0.132402E+10 | 0.202391E+09 | 0.112163E+10 | 0.169718E+10 | 0.419897E+09 |
July | 0.143410E+10 | 0.249104E+09 | 0.118500E+10 | 0.210264E+10 | 0.216673E+09 |
August | 0.191509E+10 | 0.710338E+09 | 0.120475E+10 | 0.282649E+10 | 0.306912E+09 |
September | 0.201088E+10 | 0.104011E+10 | 0.970771E+09 | 0.256579E+10 | 0.618398E+09 |
October | 0.284656E+10 | 0.178500E+10 | 0.106156E+10 | 0.332684E+10 | 0.114522E+10 |
November | 0.191017E+10 | 0.114715E+10 | 0.763023E+09 | 0.181370E+10 | 0.167596E+10 |
December | 0.195269E+10 | 0.138628E+10 | 0.566411E+09 | 0.176826E+10 | 0.217792E+10 |
Annual Sum or Average | 0.225531E+11 | 0.112513E+11 | 0.113017E+11 | 0.246873E+11 | 0.148780E+11 |
Minimum of Months | 0.132402E+10 | 0.202391E+09 | 0.566411E+09 | 0.154327E+10 | 0.216673E+09 |
Maximum of Months | 0.284656E+10 | 0.178500E+10 | 0.120475E+10 | 0.332684E+10 | 0.232595E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.180156E+10 | 0.117967E+10 | 0.621885E+09 | 0.154321E+10 | 0.232586E+10 |
February | 0.214624E+10 | 0.142063E+10 | 0.725602E+09 | 0.188361E+10 | 0.211887E+10 |
March | 0.214377E+10 | 0.118983E+10 | 0.953941E+09 | 0.202828E+10 | 0.177040E+10 |
April | 0.160983E+10 | 0.636575E+09 | 0.973255E+09 | 0.157893E+10 | 0.129530E+10 |
May | 0.145780E+10 | 0.304075E+09 | 0.115373E+10 | 0.155205E+10 | 0.806252E+09 |
June | 0.132397E+10 | 0.202383E+09 | 0.112159E+10 | 0.169711E+10 | 0.419880E+09 |
July | 0.143405E+10 | 0.249094E+09 | 0.118495E+10 | 0.210255E+10 | 0.216664E+09 |
August | 0.191501E+10 | 0.710310E+09 | 0.120470E+10 | 0.282638E+10 | 0.306899E+09 |
September | 0.201080E+10 | 0.104007E+10 | 0.970732E+09 | 0.256569E+10 | 0.618374E+09 |
October | 0.284645E+10 | 0.178493E+10 | 0.106152E+10 | 0.332671E+10 | 0.114517E+10 |
November | 0.191010E+10 | 0.114711E+10 | 0.762993E+09 | 0.181363E+10 | 0.167589E+10 |
December | 0.195262E+10 | 0.138623E+10 | 0.566389E+09 | 0.176819E+10 | 0.217783E+10 |
Annual Sum or Average | 0.225522E+11 | 0.112509E+11 | 0.113013E+11 | 0.246863E+11 | 0.148774E+11 |
Minimum of Months | 0.132397E+10 | 0.202383E+09 | 0.566389E+09 | 0.154321E+10 | 0.216664E+09 |
Maximum of Months | 0.284645E+10 | 0.178493E+10 | 0.120470E+10 | 0.332671E+10 | 0.232586E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.797976E+09 | 0.326853E+09 | 0.471122E+09 | 0.373042E+09 | 0.302910E+10 |
February | 0.106285E+10 | 0.466809E+09 | 0.596043E+09 | 0.567382E+09 | 0.279022E+10 |
March | 0.173759E+10 | 0.802196E+09 | 0.935390E+09 | 0.129474E+10 | 0.218183E+10 |
April | 0.183784E+10 | 0.786364E+09 | 0.105147E+10 | 0.160737E+10 | 0.161543E+10 |
May | 0.221226E+10 | 0.840130E+09 | 0.137213E+10 | 0.235646E+10 | 0.964847E+09 |
June | 0.234315E+10 | 0.945058E+09 | 0.139809E+10 | 0.291605E+10 | 0.551273E+09 |
July | 0.226763E+10 | 0.853920E+09 | 0.141371E+10 | 0.308137E+10 | 0.334192E+09 |
August | 0.250862E+10 | 0.116132E+10 | 0.134729E+10 | 0.341194E+10 | 0.449666E+09 |
September | 0.172347E+10 | 0.753152E+09 | 0.970317E+09 | 0.204121E+10 | 0.760718E+09 |
October | 0.176565E+10 | 0.858591E+09 | 0.907056E+09 | 0.179318E+10 | 0.141592E+10 |
November | 0.802395E+09 | 0.231898E+09 | 0.570497E+09 | 0.383009E+09 | 0.222291E+10 |
December | 0.737505E+09 | 0.319120E+09 | 0.418384E+09 | 0.331616E+09 | 0.298158E+10 |
Annual Sum or Average | 0.197969E+11 | 0.834542E+10 | 0.114515E+11 | 0.201574E+11 | 0.192977E+11 |
Minimum of Months | 0.737505E+09 | 0.231898E+09 | 0.418384E+09 | 0.331616E+09 | 0.334192E+09 |
Maximum of Months | 0.250862E+10 | 0.116132E+10 | 0.141371E+10 | 0.341194E+10 | 0.302910E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.797976E+09 | 0.326853E+09 | 0.471122E+09 | 0.373042E+09 | 0.302910E+10 |
February | 0.106285E+10 | 0.466809E+09 | 0.596043E+09 | 0.567382E+09 | 0.279022E+10 |
March | 0.173759E+10 | 0.802196E+09 | 0.935390E+09 | 0.129474E+10 | 0.218183E+10 |
April | 0.183784E+10 | 0.786364E+09 | 0.105147E+10 | 0.160737E+10 | 0.161543E+10 |
May | 0.221226E+10 | 0.840130E+09 | 0.137213E+10 | 0.235646E+10 | 0.964847E+09 |
June | 0.234315E+10 | 0.945058E+09 | 0.139809E+10 | 0.291605E+10 | 0.551273E+09 |
July | 0.226763E+10 | 0.853920E+09 | 0.141371E+10 | 0.308137E+10 | 0.334192E+09 |
August | 0.250862E+10 | 0.116132E+10 | 0.134729E+10 | 0.341194E+10 | 0.449666E+09 |
September | 0.172347E+10 | 0.753152E+09 | 0.970317E+09 | 0.204121E+10 | 0.760718E+09 |
October | 0.176565E+10 | 0.858591E+09 | 0.907056E+09 | 0.179318E+10 | 0.141592E+10 |
November | 0.802395E+09 | 0.231898E+09 | 0.570497E+09 | 0.383009E+09 | 0.222291E+10 |
December | 0.737505E+09 | 0.319120E+09 | 0.418384E+09 | 0.331616E+09 | 0.298158E+10 |
Annual Sum or Average | 0.197969E+11 | 0.834542E+10 | 0.114515E+11 | 0.201574E+11 | 0.192977E+11 |
Minimum of Months | 0.737505E+09 | 0.231898E+09 | 0.418384E+09 | 0.331616E+09 | 0.334192E+09 |
Maximum of Months | 0.250862E+10 | 0.116132E+10 | 0.141371E+10 | 0.341194E+10 | 0.302910E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.797961E+09 | 0.326847E+09 | 0.471114E+09 | 0.373035E+09 | 0.302904E+10 |
February | 0.106283E+10 | 0.466800E+09 | 0.596032E+09 | 0.567372E+09 | 0.279017E+10 |
March | 0.173755E+10 | 0.802181E+09 | 0.935373E+09 | 0.129472E+10 | 0.218179E+10 |
April | 0.183780E+10 | 0.786350E+09 | 0.105146E+10 | 0.160734E+10 | 0.161540E+10 |
May | 0.221222E+10 | 0.840115E+09 | 0.137210E+10 | 0.235642E+10 | 0.964830E+09 |
June | 0.234310E+10 | 0.945041E+09 | 0.139806E+10 | 0.291600E+10 | 0.551263E+09 |
July | 0.226759E+10 | 0.853904E+09 | 0.141368E+10 | 0.308131E+10 | 0.334186E+09 |
August | 0.250857E+10 | 0.116130E+10 | 0.134727E+10 | 0.341188E+10 | 0.449658E+09 |
September | 0.172344E+10 | 0.753138E+09 | 0.970300E+09 | 0.204117E+10 | 0.760704E+09 |
October | 0.176562E+10 | 0.858576E+09 | 0.907040E+09 | 0.179315E+10 | 0.141589E+10 |
November | 0.802380E+09 | 0.231894E+09 | 0.570487E+09 | 0.383002E+09 | 0.222287E+10 |
December | 0.737491E+09 | 0.319115E+09 | 0.418377E+09 | 0.331610E+09 | 0.298153E+10 |
Annual Sum or Average | 0.197966E+11 | 0.834526E+10 | 0.114513E+11 | 0.201570E+11 | 0.192973E+11 |
Minimum of Months | 0.737491E+09 | 0.231894E+09 | 0.418377E+09 | 0.331610E+09 | 0.334186E+09 |
Maximum of Months | 0.250857E+10 | 0.116130E+10 | 0.141368E+10 | 0.341188E+10 | 0.302904E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174128E+10 | 0.00 | 0.174128E+10 | 12480350.67 | 0.127793E+11 |
February | 0.215227E+10 | 0.00 | 0.215227E+10 | 71664944.10 | 0.121528E+11 |
March | 0.330444E+10 | 0.00 | 0.330444E+10 | 0.676316E+09 | 0.889333E+10 |
April | 0.384105E+10 | 10925138.76 | 0.383013E+10 | 0.190796E+10 | 0.593135E+10 |
May | 0.526572E+10 | 0.175457E+09 | 0.509026E+10 | 0.434287E+10 | 0.355229E+10 |
June | 0.540409E+10 | 0.290384E+09 | 0.511370E+10 | 0.633439E+10 | 0.184537E+10 |
July | 0.539661E+10 | 0.195160E+09 | 0.520145E+10 | 0.759084E+10 | 0.103670E+10 |
August | 0.478114E+10 | 56902334.67 | 0.472424E+10 | 0.663970E+10 | 0.142724E+10 |
September | 0.348792E+10 | 653146.41 | 0.348727E+10 | 0.351165E+10 | 0.275650E+10 |
October | 0.311917E+10 | 0.00 | 0.311917E+10 | 0.195841E+10 | 0.531966E+10 |
November | 0.211722E+10 | 0.00 | 0.211722E+10 | 0.332616E+09 | 0.860362E+10 |
December | 0.151886E+10 | 0.00 | 0.151886E+10 | 12204579.35 | 0.119248E+11 |
Annual Sum or Average | 0.421298E+11 | 0.729481E+09 | 0.414003E+11 | 0.333911E+11 | 0.762229E+11 |
Minimum of Months | 0.151886E+10 | 0.00 | 0.151886E+10 | 12204579.35 | 0.103670E+10 |
Maximum of Months | 0.540409E+10 | 0.290384E+09 | 0.520145E+10 | 0.759084E+10 | 0.127793E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242489E+10 | 0.972184E+09 | 0.145270E+10 | 0.115966E+10 | 0.782228E+10 |
February | 0.339656E+10 | 0.158450E+10 | 0.181206E+10 | 0.190503E+10 | 0.716911E+10 |
March | 0.479720E+10 | 0.204028E+10 | 0.275691E+10 | 0.351530E+10 | 0.569675E+10 |
April | 0.557126E+10 | 0.244038E+10 | 0.313088E+10 | 0.496452E+10 | 0.382874E+10 |
May | 0.698199E+10 | 0.279043E+10 | 0.419157E+10 | 0.739777E+10 | 0.240219E+10 |
June | 0.626209E+10 | 0.226683E+10 | 0.399526E+10 | 0.779340E+10 | 0.122689E+10 |
July | 0.649916E+10 | 0.234539E+10 | 0.415377E+10 | 0.899707E+10 | 0.673160E+09 |
August | 0.731821E+10 | 0.329978E+10 | 0.401843E+10 | 0.100236E+11 | 0.938486E+09 |
September | 0.528190E+10 | 0.236978E+10 | 0.291212E+10 | 0.619254E+10 | 0.177660E+10 |
October | 0.494805E+10 | 0.224262E+10 | 0.270542E+10 | 0.496540E+10 | 0.344001E+10 |
November | 0.296127E+10 | 0.113716E+10 | 0.182411E+10 | 0.193737E+10 | 0.531195E+10 |
December | 0.238390E+10 | 0.111933E+10 | 0.126457E+10 | 0.129412E+10 | 0.723944E+10 |
Annual Sum or Average | 0.588265E+11 | 0.246087E+11 | 0.342178E+11 | 0.601458E+11 | 0.475256E+11 |
Minimum of Months | 0.238390E+10 | 0.972184E+09 | 0.126457E+10 | 0.115966E+10 | 0.673160E+09 |
Maximum of Months | 0.731821E+10 | 0.329978E+10 | 0.419157E+10 | 0.100236E+11 | 0.782228E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.900803E+10 | 0.589852E+10 | 0.310951E+10 | 0.766771E+10 | 0.112080E+11 |
February | 0.107315E+11 | 0.710337E+10 | 0.362811E+10 | 0.931940E+10 | 0.103616E+11 |
March | 0.107192E+11 | 0.594932E+10 | 0.476984E+10 | 0.100111E+11 | 0.858927E+10 |
April | 0.804938E+10 | 0.318297E+10 | 0.486641E+10 | 0.784114E+10 | 0.619007E+10 |
May | 0.728922E+10 | 0.152042E+10 | 0.576881E+10 | 0.769847E+10 | 0.388509E+10 |
June | 0.662005E+10 | 0.101194E+10 | 0.560811E+10 | 0.844050E+10 | 0.200890E+10 |
July | 0.717044E+10 | 0.124550E+10 | 0.592494E+10 | 0.104596E+11 | 0.110002E+10 |
August | 0.957533E+10 | 0.355165E+10 | 0.602368E+10 | 0.140417E+11 | 0.157774E+10 |
September | 0.100543E+11 | 0.520049E+10 | 0.485380E+10 | 0.127272E+11 | 0.296855E+10 |
October | 0.142326E+11 | 0.892489E+10 | 0.530775E+10 | 0.164311E+11 | 0.558637E+10 |
November | 0.955076E+10 | 0.573569E+10 | 0.381507E+10 | 0.902378E+10 | 0.797133E+10 |
December | 0.976336E+10 | 0.693133E+10 | 0.283203E+10 | 0.880766E+10 | 0.104182E+11 |
Annual Sum or Average | 0.112764E+12 | 0.562561E+11 | 0.565081E+11 | 0.122469E+12 | 0.718651E+11 |
Minimum of Months | 0.662005E+10 | 0.101194E+10 | 0.283203E+10 | 0.766771E+10 | 0.110002E+10 |
Maximum of Months | 0.142326E+11 | 0.892489E+10 | 0.602368E+10 | 0.164311E+11 | 0.112080E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239390E+10 | 0.980550E+09 | 0.141335E+10 | 0.116548E+10 | 0.820848E+10 |
February | 0.318852E+10 | 0.140041E+10 | 0.178811E+10 | 0.175599E+10 | 0.768848E+10 |
March | 0.521270E+10 | 0.240656E+10 | 0.280614E+10 | 0.399502E+10 | 0.579689E+10 |
April | 0.551346E+10 | 0.235907E+10 | 0.315439E+10 | 0.503124E+10 | 0.411497E+10 |
May | 0.663671E+10 | 0.252036E+10 | 0.411634E+10 | 0.717075E+10 | 0.260477E+10 |
June | 0.702937E+10 | 0.283514E+10 | 0.419422E+10 | 0.883207E+10 | 0.143858E+10 |
July | 0.680282E+10 | 0.256173E+10 | 0.424109E+10 | 0.938476E+10 | 0.846848E+09 |
August | 0.752577E+10 | 0.348394E+10 | 0.404183E+10 | 0.104048E+11 | 0.115176E+10 |
September | 0.517036E+10 | 0.225943E+10 | 0.291092E+10 | 0.624704E+10 | 0.196166E+10 |
October | 0.529689E+10 | 0.257575E+10 | 0.272114E+10 | 0.551764E+10 | 0.372674E+10 |
November | 0.240716E+10 | 0.695686E+09 | 0.171147E+10 | 0.128088E+10 | 0.565296E+10 |
December | 0.221249E+10 | 0.957352E+09 | 0.125514E+10 | 0.109877E+10 | 0.768572E+10 |
Annual Sum or Average | 0.593902E+11 | 0.250360E+11 | 0.343542E+11 | 0.618844E+11 | 0.508779E+11 |
Minimum of Months | 0.221249E+10 | 0.695686E+09 | 0.125514E+10 | 0.109877E+10 | 0.846848E+09 |
Maximum of Months | 0.752577E+10 | 0.348394E+10 | 0.424109E+10 | 0.104048E+11 | 0.820848E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174128E+10 | 0.00 | 0.174128E+10 | 17503988.93 | 0.122018E+11 |
February | 0.215227E+10 | 0.00 | 0.215227E+10 | 0.102077E+09 | 0.115567E+11 |
March | 0.330444E+10 | 0.00 | 0.330444E+10 | 0.738121E+09 | 0.817031E+10 |
April | 0.384105E+10 | 10925138.76 | 0.383013E+10 | 0.202336E+10 | 0.538139E+10 |
May | 0.526572E+10 | 0.175457E+09 | 0.509026E+10 | 0.447665E+10 | 0.323061E+10 |
June | 0.540409E+10 | 0.290384E+09 | 0.511370E+10 | 0.636509E+10 | 0.172208E+10 |
July | 0.539661E+10 | 0.195160E+09 | 0.520145E+10 | 0.756655E+10 | 0.975908E+09 |
August | 0.478114E+10 | 56902334.67 | 0.472424E+10 | 0.664176E+10 | 0.132767E+10 |
September | 0.348792E+10 | 653146.41 | 0.348727E+10 | 0.361217E+10 | 0.246504E+10 |
October | 0.311917E+10 | 0.00 | 0.311917E+10 | 0.213609E+10 | 0.468328E+10 |
November | 0.211722E+10 | 0.00 | 0.211722E+10 | 0.410341E+09 | 0.776446E+10 |
December | 0.151886E+10 | 0.00 | 0.151886E+10 | 32638142.23 | 0.110085E+11 |
Annual Sum or Average | 0.421298E+11 | 0.729481E+09 | 0.414003E+11 | 0.341224E+11 | 0.704877E+11 |
Minimum of Months | 0.151886E+10 | 0.00 | 0.151886E+10 | 17503988.93 | 0.975908E+09 |
Maximum of Months | 0.540409E+10 | 0.290384E+09 | 0.520145E+10 | 0.756655E+10 | 0.122018E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242489E+10 | 0.972184E+09 | 0.145270E+10 | 0.119570E+10 | 0.744747E+10 |
February | 0.339656E+10 | 0.158450E+10 | 0.181206E+10 | 0.198578E+10 | 0.677548E+10 |
March | 0.479720E+10 | 0.204028E+10 | 0.275691E+10 | 0.362244E+10 | 0.520541E+10 |
April | 0.557126E+10 | 0.244038E+10 | 0.313088E+10 | 0.506390E+10 | 0.350823E+10 |
May | 0.698199E+10 | 0.279043E+10 | 0.419157E+10 | 0.745552E+10 | 0.223402E+10 |
June | 0.626209E+10 | 0.226683E+10 | 0.399526E+10 | 0.777636E+10 | 0.117857E+10 |
July | 0.649916E+10 | 0.234539E+10 | 0.415377E+10 | 0.894196E+10 | 0.662875E+09 |
August | 0.731821E+10 | 0.329978E+10 | 0.401843E+10 | 0.998066E+10 | 0.907739E+09 |
September | 0.528190E+10 | 0.236978E+10 | 0.291212E+10 | 0.623601E+10 | 0.163739E+10 |
October | 0.494805E+10 | 0.224262E+10 | 0.270542E+10 | 0.511189E+10 | 0.307163E+10 |
November | 0.296127E+10 | 0.113716E+10 | 0.182411E+10 | 0.207499E+10 | 0.476498E+10 |
December | 0.238390E+10 | 0.111933E+10 | 0.126457E+10 | 0.136844E+10 | 0.665147E+10 |
Annual Sum or Average | 0.588265E+11 | 0.246087E+11 | 0.342178E+11 | 0.608136E+11 | 0.440453E+11 |
Minimum of Months | 0.238390E+10 | 0.972184E+09 | 0.126457E+10 | 0.119570E+10 | 0.662875E+09 |
Maximum of Months | 0.731821E+10 | 0.329978E+10 | 0.419157E+10 | 0.998066E+10 | 0.744747E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.900803E+10 | 0.589852E+10 | 0.310951E+10 | 0.775574E+10 | 0.105825E+11 |
February | 0.107315E+11 | 0.710337E+10 | 0.362811E+10 | 0.944869E+10 | 0.970428E+10 |
March | 0.107192E+11 | 0.594932E+10 | 0.476984E+10 | 0.101007E+11 | 0.784127E+10 |
April | 0.804938E+10 | 0.318297E+10 | 0.486641E+10 | 0.793328E+10 | 0.563823E+10 |
May | 0.728922E+10 | 0.152042E+10 | 0.576881E+10 | 0.777225E+10 | 0.354589E+10 |
June | 0.662005E+10 | 0.101194E+10 | 0.560811E+10 | 0.843472E+10 | 0.187674E+10 |
July | 0.717044E+10 | 0.124550E+10 | 0.592494E+10 | 0.104133E+11 | 0.103231E+10 |
August | 0.957533E+10 | 0.355165E+10 | 0.602368E+10 | 0.139939E+11 | 0.147538E+10 |
September | 0.100543E+11 | 0.520049E+10 | 0.485380E+10 | 0.127692E+11 | 0.269232E+10 |
October | 0.142326E+11 | 0.892489E+10 | 0.530775E+10 | 0.165577E+11 | 0.498352E+10 |
November | 0.955076E+10 | 0.573569E+10 | 0.381507E+10 | 0.922796E+10 | 0.714689E+10 |
December | 0.976336E+10 | 0.693133E+10 | 0.283203E+10 | 0.900118E+10 | 0.950154E+10 |
Annual Sum or Average | 0.112764E+12 | 0.562561E+11 | 0.565081E+11 | 0.123409E+12 | 0.660209E+11 |
Minimum of Months | 0.662005E+10 | 0.101194E+10 | 0.283203E+10 | 0.775574E+10 | 0.103231E+10 |
Maximum of Months | 0.142326E+11 | 0.892489E+10 | 0.602368E+10 | 0.165577E+11 | 0.105825E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239390E+10 | 0.980550E+09 | 0.141335E+10 | 0.117623E+10 | 0.784374E+10 |
February | 0.318852E+10 | 0.140041E+10 | 0.178811E+10 | 0.176939E+10 | 0.732810E+10 |
March | 0.521270E+10 | 0.240656E+10 | 0.280614E+10 | 0.401160E+10 | 0.538669E+10 |
April | 0.551346E+10 | 0.235907E+10 | 0.315439E+10 | 0.504664E+10 | 0.381349E+10 |
May | 0.663671E+10 | 0.252036E+10 | 0.411634E+10 | 0.716717E+10 | 0.243354E+10 |
June | 0.702937E+10 | 0.283514E+10 | 0.419422E+10 | 0.878625E+10 | 0.137312E+10 |
July | 0.680282E+10 | 0.256173E+10 | 0.424109E+10 | 0.931971E+10 | 0.816206E+09 |
August | 0.752577E+10 | 0.348394E+10 | 0.404183E+10 | 0.103562E+11 | 0.110226E+10 |
September | 0.517036E+10 | 0.225943E+10 | 0.291092E+10 | 0.624769E+10 | 0.182595E+10 |
October | 0.529689E+10 | 0.257575E+10 | 0.272114E+10 | 0.555827E+10 | 0.339397E+10 |
November | 0.240716E+10 | 0.695686E+09 | 0.171147E+10 | 0.132323E+10 | 0.519125E+10 |
December | 0.221249E+10 | 0.957352E+09 | 0.125514E+10 | 0.112806E+10 | 0.715013E+10 |
Annual Sum or Average | 0.593902E+11 | 0.250360E+11 | 0.343542E+11 | 0.618904E+11 | 0.476584E+11 |
Minimum of Months | 0.221249E+10 | 0.695686E+09 | 0.125514E+10 | 0.112806E+10 | 0.816206E+09 |
Maximum of Months | 0.752577E+10 | 0.348394E+10 | 0.424109E+10 | 0.103562E+11 | 0.784374E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.85 | 5196.12 | 650.12 | 0.00 | 650.12 | 0.00 | 0.00 |
February | 14.29 | 5377.51 | 889.67 | 0.00 | 889.67 | 0.00 | 0.00 |
March | 192.93 | 3672.74 | 1233.74 | 0.00 | 1233.74 | 0.00 | 0.00 |
April | 629.89 | 2598.86 | 1481.89 | 4.21 | 1477.68 | 0.00 | 0.00 |
May | 1532.78 | 1468.91 | 1966.00 | 65.51 | 1900.49 | 0.00 | 0.00 |
June | 2395.65 | 783.31 | 2084.92 | 112.03 | 1972.89 | 0.00 | 0.00 |
July | 2788.44 | 418.19 | 2014.87 | 72.86 | 1942.01 | 0.00 | 0.00 |
August | 2427.88 | 570.84 | 1785.08 | 21.24 | 1763.84 | 0.00 | 0.00 |
September | 1276.42 | 1228.88 | 1345.65 | 0.25 | 1345.40 | 0.00 | 0.00 |
October | 631.69 | 2281.87 | 1164.57 | 0.00 | 1164.57 | 0.00 | 0.00 |
November | 83.79 | 3819.98 | 816.83 | 0.00 | 816.83 | 0.00 | 0.00 |
December | 1.04 | 4989.28 | 567.08 | 0.00 | 567.08 | 0.00 | 0.00 |
Annual Sum or Average | 1004.98 | 2685.03 | 1335.93 | 23.13 | 1312.80 | 0.00 | 0.00 |
Minimum of Months | 0.85 | 418.19 | 567.08 | 0.00 | 567.08 | 0.00 | 0.00 |
Maximum of Months | 2788.44 | 5377.51 | 2084.92 | 112.03 | 1972.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 419.43 | 3147.44 | 905.35 | 362.97 | 542.38 | 0.00 | 0.00 |
February | 771.21 | 3138.59 | 1404.01 | 654.97 | 749.04 | 0.00 | 0.00 |
March | 1316.82 | 2252.10 | 1791.08 | 761.76 | 1029.32 | 0.00 | 0.00 |
April | 1925.06 | 1574.21 | 2149.41 | 941.51 | 1207.90 | 0.00 | 0.00 |
May | 2795.57 | 945.77 | 2606.79 | 1041.83 | 1564.96 | 0.00 | 0.00 |
June | 3039.17 | 491.69 | 2415.94 | 874.55 | 1541.39 | 0.00 | 0.00 |
July | 3405.67 | 225.79 | 2426.52 | 875.67 | 1550.85 | 0.00 | 0.00 |
August | 3797.91 | 314.81 | 2732.32 | 1232.00 | 1500.32 | 0.00 | 0.00 |
September | 2407.36 | 740.56 | 2037.78 | 914.27 | 1123.51 | 0.00 | 0.00 |
October | 1853.63 | 1391.99 | 1847.40 | 837.30 | 1010.09 | 0.00 | 0.00 |
November | 727.06 | 2255.50 | 1142.47 | 438.72 | 703.75 | 0.00 | 0.00 |
December | 465.46 | 2947.25 | 890.05 | 417.91 | 472.14 | 0.00 | 0.00 |
Annual Sum or Average | 1918.47 | 1610.19 | 1865.38 | 780.34 | 1085.04 | 0.00 | 0.00 |
Minimum of Months | 419.43 | 225.79 | 890.05 | 362.97 | 472.14 | 0.00 | 0.00 |
Maximum of Months | 3797.91 | 3147.44 | 2732.32 | 1232.00 | 1564.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2880.93 | 4342.02 | 3363.23 | 2202.26 | 1160.96 | 0.00 | 0.00 |
February | 3893.16 | 4379.42 | 4435.98 | 2936.26 | 1499.72 | 0.00 | 0.00 |
March | 3786.49 | 3305.07 | 4002.09 | 2221.23 | 1780.86 | 0.00 | 0.00 |
April | 3045.87 | 2498.73 | 3105.48 | 1228.00 | 1877.48 | 0.00 | 0.00 |
May | 2897.44 | 1505.15 | 2721.49 | 567.66 | 2153.83 | 0.00 | 0.00 |
June | 3273.85 | 809.98 | 2554.04 | 390.41 | 2163.63 | 0.00 | 0.00 |
July | 3925.15 | 404.48 | 2677.15 | 465.02 | 2212.13 | 0.00 | 0.00 |
August | 5276.42 | 572.93 | 3575.03 | 1326.04 | 2248.99 | 0.00 | 0.00 |
September | 4949.40 | 1192.89 | 3878.98 | 2006.37 | 1872.61 | 0.00 | 0.00 |
October | 6210.45 | 2137.86 | 5313.88 | 3332.18 | 1981.70 | 0.00 | 0.00 |
November | 3498.62 | 3232.92 | 3684.72 | 2212.85 | 1471.87 | 0.00 | 0.00 |
December | 3300.94 | 4065.68 | 3645.23 | 2587.87 | 1057.36 | 0.00 | 0.00 |
Annual Sum or Average | 3914.12 | 2358.87 | 3575.74 | 1783.88 | 1791.87 | 0.00 | 0.00 |
Minimum of Months | 2880.93 | 404.48 | 2554.04 | 390.41 | 1057.36 | 0.00 | 0.00 |
Maximum of Months | 6210.45 | 4379.42 | 5313.88 | 3332.18 | 2248.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 417.83 | 3392.79 | 893.78 | 366.10 | 527.69 | 0.00 | 0.00 |
February | 703.59 | 3460.08 | 1318.01 | 578.88 | 739.14 | 0.00 | 0.00 |
March | 1450.20 | 2443.79 | 1946.21 | 898.51 | 1047.70 | 0.00 | 0.00 |
April | 1860.37 | 1869.70 | 2127.11 | 910.14 | 1216.98 | 0.00 | 0.00 |
May | 2639.39 | 1080.69 | 2477.87 | 941.00 | 1536.87 | 0.00 | 0.00 |
June | 3375.04 | 638.04 | 2711.96 | 1093.81 | 1618.15 | 0.00 | 0.00 |
July | 3451.33 | 374.32 | 2539.89 | 956.45 | 1583.45 | 0.00 | 0.00 |
August | 3821.59 | 503.66 | 2809.81 | 1300.76 | 1509.05 | 0.00 | 0.00 |
September | 2362.49 | 880.46 | 1994.74 | 871.70 | 1123.05 | 0.00 | 0.00 |
October | 2008.48 | 1585.92 | 1977.64 | 961.68 | 1015.96 | 0.00 | 0.00 |
November | 443.29 | 2572.79 | 928.69 | 268.40 | 660.29 | 0.00 | 0.00 |
December | 371.43 | 3339.57 | 826.05 | 357.44 | 468.62 | 0.00 | 0.00 |
Annual Sum or Average | 1917.55 | 1835.77 | 1883.26 | 793.89 | 1089.37 | 0.00 | 0.00 |
Minimum of Months | 371.43 | 374.32 | 826.05 | 268.40 | 468.62 | 0.00 | 0.00 |
Maximum of Months | 3821.59 | 3460.08 | 2809.81 | 1300.76 | 1618.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.66 | 4771.23 | 650.12 | 0.00 | 650.12 | 0.00 | 0.00 |
February | 29.62 | 5023.46 | 889.66 | 0.00 | 889.66 | 0.00 | 0.00 |
March | 252.51 | 3320.39 | 1233.74 | 0.00 | 1233.74 | 0.00 | 0.00 |
April | 736.10 | 2288.33 | 1481.89 | 4.21 | 1477.67 | 0.00 | 0.00 |
May | 1621.44 | 1326.27 | 1965.99 | 65.51 | 1900.49 | 0.00 | 0.00 |
June | 2443.82 | 711.95 | 2084.91 | 112.03 | 1972.88 | 0.00 | 0.00 |
July | 2834.09 | 387.06 | 2014.86 | 72.86 | 1942.00 | 0.00 | 0.00 |
August | 2478.98 | 532.87 | 1785.07 | 21.24 | 1763.83 | 0.00 | 0.00 |
September | 1354.80 | 1063.47 | 1345.65 | 0.25 | 1345.40 | 0.00 | 0.00 |
October | 731.19 | 1986.13 | 1164.56 | 0.00 | 1164.56 | 0.00 | 0.00 |
November | 128.32 | 3319.30 | 816.83 | 0.00 | 816.83 | 0.00 | 0.00 |
December | 4.56 | 4452.21 | 567.08 | 0.00 | 567.08 | 0.00 | 0.00 |
Annual Sum or Average | 1058.83 | 2417.01 | 1335.93 | 23.13 | 1312.79 | 0.00 | 0.00 |
Minimum of Months | 4.56 | 387.06 | 567.08 | 0.00 | 567.08 | 0.00 | 0.00 |
Maximum of Months | 2834.09 | 5023.46 | 2084.91 | 112.03 | 1972.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 432.97 | 2920.50 | 905.35 | 362.97 | 542.38 | 0.00 | 0.00 |
February | 787.46 | 2963.42 | 1404.00 | 654.97 | 749.03 | 0.00 | 0.00 |
March | 1312.46 | 2126.92 | 1791.07 | 761.75 | 1029.31 | 0.00 | 0.00 |
April | 1915.33 | 1477.14 | 2149.41 | 941.51 | 1207.90 | 0.00 | 0.00 |
May | 2762.01 | 896.87 | 2606.78 | 1041.83 | 1564.95 | 0.00 | 0.00 |
June | 3006.71 | 473.34 | 2415.93 | 874.55 | 1541.38 | 0.00 | 0.00 |
July | 3359.12 | 251.33 | 2426.51 | 875.67 | 1550.84 | 0.00 | 0.00 |
August | 3742.39 | 350.39 | 2732.31 | 1232.00 | 1500.31 | 0.00 | 0.00 |
September | 2389.10 | 685.42 | 2037.77 | 914.27 | 1123.50 | 0.00 | 0.00 |
October | 1853.87 | 1284.35 | 1847.39 | 837.30 | 1010.09 | 0.00 | 0.00 |
November | 747.44 | 2049.36 | 1142.47 | 438.72 | 703.75 | 0.00 | 0.00 |
December | 483.17 | 2702.90 | 890.05 | 417.91 | 472.14 | 0.00 | 0.00 |
Annual Sum or Average | 1907.21 | 1507.03 | 1865.38 | 780.34 | 1085.04 | 0.00 | 0.00 |
Minimum of Months | 432.97 | 251.33 | 890.05 | 362.97 | 472.14 | 0.00 | 0.00 |
Maximum of Months | 3742.39 | 2963.42 | 2732.31 | 1232.00 | 1564.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2862.80 | 4184.58 | 3363.21 | 2202.25 | 1160.96 | 0.00 | 0.00 |
February | 3852.26 | 4283.08 | 4435.96 | 2936.25 | 1499.72 | 0.00 | 0.00 |
March | 3737.70 | 3206.87 | 4002.08 | 2221.22 | 1780.85 | 0.00 | 0.00 |
April | 3025.13 | 2388.14 | 3105.47 | 1228.00 | 1877.47 | 0.00 | 0.00 |
May | 2874.28 | 1450.53 | 2721.48 | 567.66 | 2153.83 | 0.00 | 0.00 |
June | 3256.37 | 775.04 | 2554.03 | 390.41 | 2163.62 | 0.00 | 0.00 |
July | 3905.16 | 410.70 | 2677.14 | 465.02 | 2212.12 | 0.00 | 0.00 |
August | 5242.58 | 589.06 | 3575.02 | 1326.03 | 2248.99 | 0.00 | 0.00 |
September | 4910.18 | 1145.27 | 3878.97 | 2006.36 | 1872.61 | 0.00 | 0.00 |
October | 6134.67 | 2085.71 | 5313.86 | 3332.17 | 1981.69 | 0.00 | 0.00 |
November | 3481.39 | 3075.36 | 3684.71 | 2212.84 | 1471.86 | 0.00 | 0.00 |
December | 3288.40 | 3889.71 | 3645.22 | 2587.86 | 1057.36 | 0.00 | 0.00 |
Annual Sum or Average | 3883.48 | 2278.83 | 3575.73 | 1783.87 | 1791.86 | 0.00 | 0.00 |
Minimum of Months | 2862.80 | 410.70 | 2554.03 | 390.41 | 1057.36 | 0.00 | 0.00 |
Maximum of Months | 6134.67 | 4283.08 | 5313.86 | 3332.17 | 2248.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 435.14 | 3064.70 | 893.78 | 366.10 | 527.69 | 0.00 | 0.00 |
February | 725.86 | 3178.11 | 1318.01 | 578.87 | 739.13 | 0.00 | 0.00 |
March | 1491.57 | 2164.31 | 1946.20 | 898.51 | 1047.69 | 0.00 | 0.00 |
April | 1941.06 | 1587.56 | 2127.11 | 910.13 | 1216.97 | 0.00 | 0.00 |
May | 2677.25 | 972.51 | 2477.86 | 941.00 | 1536.87 | 0.00 | 0.00 |
June | 3407.44 | 555.01 | 2711.95 | 1093.81 | 1618.14 | 0.00 | 0.00 |
July | 3503.87 | 316.18 | 2539.88 | 956.44 | 1583.44 | 0.00 | 0.00 |
August | 3884.71 | 430.02 | 2809.80 | 1300.75 | 1509.05 | 0.00 | 0.00 |
September | 2410.12 | 756.81 | 1994.74 | 871.70 | 1123.04 | 0.00 | 0.00 |
October | 2060.05 | 1391.40 | 1977.63 | 961.67 | 1015.96 | 0.00 | 0.00 |
November | 494.17 | 2180.93 | 928.69 | 268.40 | 660.29 | 0.00 | 0.00 |
December | 410.24 | 2869.52 | 826.05 | 357.43 | 468.62 | 0.00 | 0.00 |
Annual Sum or Average | 1962.34 | 1613.33 | 1883.25 | 793.89 | 1089.36 | 0.00 | 0.00 |
Minimum of Months | 410.24 | 316.18 | 826.05 | 268.40 | 468.62 | 0.00 | 0.00 |
Maximum of Months | 3884.71 | 3178.11 | 2809.80 | 1300.75 | 1618.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.54 | 4555.63 | 650.12 | 0.00 | 650.12 | 0.00 | 0.00 |
February | 42.19 | 4777.06 | 889.66 | 0.00 | 889.66 | 0.00 | 0.00 |
March | 275.58 | 3050.44 | 1233.74 | 0.00 | 1233.74 | 0.00 | 0.00 |
April | 780.62 | 2076.15 | 1481.89 | 4.21 | 1477.67 | 0.00 | 0.00 |
May | 1671.39 | 1206.17 | 1965.99 | 65.51 | 1900.49 | 0.00 | 0.00 |
June | 2455.67 | 664.38 | 2084.91 | 112.03 | 1972.88 | 0.00 | 0.00 |
July | 2825.03 | 364.36 | 2014.86 | 72.86 | 1942.00 | 0.00 | 0.00 |
August | 2479.75 | 495.69 | 1785.07 | 21.24 | 1763.83 | 0.00 | 0.00 |
September | 1393.58 | 951.02 | 1345.65 | 0.25 | 1345.40 | 0.00 | 0.00 |
October | 797.52 | 1748.54 | 1164.56 | 0.00 | 1164.56 | 0.00 | 0.00 |
November | 158.31 | 2995.55 | 816.83 | 0.00 | 816.83 | 0.00 | 0.00 |
December | 12.19 | 4110.09 | 567.08 | 0.00 | 567.08 | 0.00 | 0.00 |
Annual Sum or Average | 1082.01 | 2235.15 | 1335.93 | 23.13 | 1312.79 | 0.00 | 0.00 |
Minimum of Months | 6.54 | 364.36 | 567.08 | 0.00 | 567.08 | 0.00 | 0.00 |
Maximum of Months | 2825.03 | 4777.06 | 2084.91 | 112.03 | 1972.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 446.42 | 2780.57 | 905.35 | 362.97 | 542.38 | 0.00 | 0.00 |
February | 820.84 | 2800.71 | 1404.00 | 654.97 | 749.03 | 0.00 | 0.00 |
March | 1352.46 | 1943.48 | 1791.07 | 761.75 | 1029.31 | 0.00 | 0.00 |
April | 1953.66 | 1353.49 | 2149.41 | 941.51 | 1207.90 | 0.00 | 0.00 |
May | 2783.57 | 834.09 | 2606.78 | 1041.83 | 1564.95 | 0.00 | 0.00 |
June | 3000.14 | 454.69 | 2415.93 | 874.55 | 1541.38 | 0.00 | 0.00 |
July | 3338.54 | 247.49 | 2426.51 | 875.67 | 1550.84 | 0.00 | 0.00 |
August | 3726.35 | 338.91 | 2732.31 | 1232.00 | 1500.31 | 0.00 | 0.00 |
September | 2405.87 | 631.71 | 2037.77 | 914.27 | 1123.50 | 0.00 | 0.00 |
October | 1908.56 | 1146.81 | 1847.39 | 837.30 | 1010.09 | 0.00 | 0.00 |
November | 800.53 | 1838.34 | 1142.47 | 438.72 | 703.75 | 0.00 | 0.00 |
December | 510.92 | 2483.37 | 890.05 | 417.91 | 472.14 | 0.00 | 0.00 |
Annual Sum or Average | 1928.39 | 1396.67 | 1865.38 | 780.34 | 1085.04 | 0.00 | 0.00 |
Minimum of Months | 446.42 | 247.49 | 890.05 | 362.97 | 472.14 | 0.00 | 0.00 |
Maximum of Months | 3726.35 | 2800.71 | 2732.31 | 1232.00 | 1564.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2895.66 | 3951.06 | 3363.21 | 2202.25 | 1160.96 | 0.00 | 0.00 |
February | 3905.71 | 4011.36 | 4435.96 | 2936.25 | 1499.72 | 0.00 | 0.00 |
March | 3771.19 | 2927.59 | 4002.08 | 2221.22 | 1780.85 | 0.00 | 0.00 |
April | 3060.68 | 2175.24 | 3105.47 | 1228.00 | 1877.47 | 0.00 | 0.00 |
May | 2901.82 | 1323.88 | 2721.48 | 567.66 | 2153.83 | 0.00 | 0.00 |
June | 3254.13 | 724.05 | 2554.03 | 390.41 | 2163.62 | 0.00 | 0.00 |
July | 3887.89 | 385.42 | 2677.14 | 465.02 | 2212.12 | 0.00 | 0.00 |
August | 5224.73 | 550.85 | 3575.02 | 1326.03 | 2248.99 | 0.00 | 0.00 |
September | 4926.40 | 1038.70 | 3878.97 | 2006.36 | 1872.61 | 0.00 | 0.00 |
October | 6181.94 | 1860.63 | 5313.86 | 3332.17 | 1981.69 | 0.00 | 0.00 |
November | 3560.17 | 2757.29 | 3684.71 | 2212.84 | 1471.86 | 0.00 | 0.00 |
December | 3360.66 | 3547.47 | 3645.22 | 2587.86 | 1057.36 | 0.00 | 0.00 |
Annual Sum or Average | 3913.27 | 2093.51 | 3575.73 | 1783.87 | 1791.86 | 0.00 | 0.00 |
Minimum of Months | 2895.66 | 385.42 | 2554.03 | 390.41 | 1057.36 | 0.00 | 0.00 |
Maximum of Months | 6181.94 | 4011.36 | 5313.86 | 3332.17 | 2248.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 439.15 | 2928.52 | 893.78 | 366.10 | 527.69 | 0.00 | 0.00 |
February | 731.39 | 3029.14 | 1318.01 | 578.87 | 739.13 | 0.00 | 0.00 |
March | 1497.76 | 2011.16 | 1946.20 | 898.51 | 1047.69 | 0.00 | 0.00 |
April | 1947.00 | 1471.25 | 2127.11 | 910.13 | 1216.97 | 0.00 | 0.00 |
May | 2675.92 | 908.58 | 2477.86 | 941.00 | 1536.87 | 0.00 | 0.00 |
June | 3389.76 | 529.75 | 2711.95 | 1093.81 | 1618.14 | 0.00 | 0.00 |
July | 3479.58 | 304.74 | 2539.88 | 956.44 | 1583.44 | 0.00 | 0.00 |
August | 3866.56 | 411.54 | 2809.80 | 1300.75 | 1509.05 | 0.00 | 0.00 |
September | 2410.37 | 704.46 | 1994.74 | 871.70 | 1123.04 | 0.00 | 0.00 |
October | 2075.22 | 1267.16 | 1977.63 | 961.67 | 1015.96 | 0.00 | 0.00 |
November | 510.51 | 2002.80 | 928.69 | 268.40 | 660.29 | 0.00 | 0.00 |
December | 421.17 | 2669.55 | 826.05 | 357.43 | 468.62 | 0.00 | 0.00 |
Annual Sum or Average | 1962.53 | 1511.24 | 1883.25 | 793.89 | 1089.36 | 0.00 | 0.00 |
Minimum of Months | 421.17 | 304.74 | 826.05 | 268.40 | 468.62 | 0.00 | 0.00 |
Maximum of Months | 3866.56 | 3029.14 | 2809.80 | 1300.75 | 1618.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 2280298.39 | 0.139173E+11 | 0.174129E+10 | 0.00 | 0.174129E+10 | 0.00 | 0.00 |
February | 34565594.72 | 0.130093E+11 | 0.215228E+10 | 0.00 | 0.215228E+10 | 0.00 | 0.00 |
March | 0.516735E+09 | 0.983706E+10 | 0.330446E+10 | 0.00 | 0.330446E+10 | 0.00 | 0.00 |
April | 0.163266E+10 | 0.673625E+10 | 0.384107E+10 | 10925177.55 | 0.383014E+10 | 0.00 | 0.00 |
May | 0.410540E+10 | 0.393433E+10 | 0.526574E+10 | 0.175457E+09 | 0.509028E+10 | 0.00 | 0.00 |
June | 0.620953E+10 | 0.203033E+10 | 0.540411E+10 | 0.290385E+09 | 0.511372E+10 | 0.00 | 0.00 |
July | 0.746855E+10 | 0.112008E+10 | 0.539663E+10 | 0.195160E+09 | 0.520147E+10 | 0.00 | 0.00 |
August | 0.650284E+10 | 0.152894E+10 | 0.478116E+10 | 56902536.74 | 0.472426E+10 | 0.00 | 0.00 |
September | 0.330847E+10 | 0.318525E+10 | 0.348794E+10 | 653148.73 | 0.348728E+10 | 0.00 | 0.00 |
October | 0.169193E+10 | 0.611176E+10 | 0.311918E+10 | 0.00 | 0.311918E+10 | 0.00 | 0.00 |
November | 0.217188E+09 | 0.990139E+10 | 0.211723E+10 | 0.00 | 0.211723E+10 | 0.00 | 0.00 |
December | 2783438.01 | 0.133633E+11 | 0.151887E+10 | 0.00 | 0.151887E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.316929E+11 | 0.846752E+11 | 0.421299E+11 | 0.729484E+09 | 0.414005E+11 | 0.00 | 0.00 |
Minimum of Months | 2280298.39 | 0.112008E+10 | 0.151887E+10 | 0.00 | 0.151887E+10 | 0.00 | 0.00 |
Maximum of Months | 0.746855E+10 | 0.139173E+11 | 0.540411E+10 | 0.290385E+09 | 0.520147E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112340E+10 | 0.843010E+10 | 0.242490E+10 | 0.972188E+09 | 0.145271E+10 | 0.00 | 0.00 |
February | 0.186571E+10 | 0.759288E+10 | 0.339657E+10 | 0.158450E+10 | 0.181207E+10 | 0.00 | 0.00 |
March | 0.352696E+10 | 0.603204E+10 | 0.479722E+10 | 0.204029E+10 | 0.275693E+10 | 0.00 | 0.00 |
April | 0.498976E+10 | 0.408036E+10 | 0.557128E+10 | 0.244039E+10 | 0.313089E+10 | 0.00 | 0.00 |
May | 0.748765E+10 | 0.253316E+10 | 0.698202E+10 | 0.279044E+10 | 0.419159E+10 | 0.00 | 0.00 |
June | 0.787754E+10 | 0.127446E+10 | 0.626212E+10 | 0.226684E+10 | 0.399528E+10 | 0.00 | 0.00 |
July | 0.912173E+10 | 0.604760E+09 | 0.649918E+10 | 0.234539E+10 | 0.415379E+10 | 0.00 | 0.00 |
August | 0.101723E+11 | 0.843178E+09 | 0.731824E+10 | 0.329979E+10 | 0.401845E+10 | 0.00 | 0.00 |
September | 0.623987E+10 | 0.191954E+10 | 0.528192E+10 | 0.236979E+10 | 0.291213E+10 | 0.00 | 0.00 |
October | 0.496475E+10 | 0.372831E+10 | 0.494807E+10 | 0.224263E+10 | 0.270543E+10 | 0.00 | 0.00 |
November | 0.188453E+10 | 0.584626E+10 | 0.296129E+10 | 0.113716E+10 | 0.182412E+10 | 0.00 | 0.00 |
December | 0.124669E+10 | 0.789392E+10 | 0.238391E+10 | 0.111934E+10 | 0.126457E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.605009E+11 | 0.507790E+11 | 0.588267E+11 | 0.246088E+11 | 0.342179E+11 | 0.00 | 0.00 |
Minimum of Months | 0.112340E+10 | 0.604760E+09 | 0.238391E+10 | 0.972188E+09 | 0.126457E+10 | 0.00 | 0.00 |
Maximum of Months | 0.101723E+11 | 0.843010E+10 | 0.731824E+10 | 0.329979E+10 | 0.419159E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.771629E+10 | 0.116297E+11 | 0.900806E+10 | 0.589854E+10 | 0.310952E+10 | 0.00 | 0.00 |
February | 0.941833E+10 | 0.105947E+11 | 0.107315E+11 | 0.710339E+10 | 0.362813E+10 | 0.00 | 0.00 |
March | 0.101417E+11 | 0.885229E+10 | 0.107192E+11 | 0.594934E+10 | 0.476986E+10 | 0.00 | 0.00 |
April | 0.789490E+10 | 0.647671E+10 | 0.804941E+10 | 0.318298E+10 | 0.486643E+10 | 0.00 | 0.00 |
May | 0.776049E+10 | 0.403139E+10 | 0.728925E+10 | 0.152042E+10 | 0.576883E+10 | 0.00 | 0.00 |
June | 0.848581E+10 | 0.209947E+10 | 0.662007E+10 | 0.101195E+10 | 0.560813E+10 | 0.00 | 0.00 |
July | 0.105131E+11 | 0.108336E+10 | 0.717047E+10 | 0.124551E+10 | 0.592496E+10 | 0.00 | 0.00 |
August | 0.141324E+11 | 0.153455E+10 | 0.957537E+10 | 0.355166E+10 | 0.602371E+10 | 0.00 | 0.00 |
September | 0.128288E+11 | 0.309197E+10 | 0.100543E+11 | 0.520051E+10 | 0.485382E+10 | 0.00 | 0.00 |
October | 0.166341E+11 | 0.572606E+10 | 0.142327E+11 | 0.892492E+10 | 0.530777E+10 | 0.00 | 0.00 |
November | 0.906842E+10 | 0.837972E+10 | 0.955079E+10 | 0.573571E+10 | 0.381509E+10 | 0.00 | 0.00 |
December | 0.884124E+10 | 0.108895E+11 | 0.976339E+10 | 0.693135E+10 | 0.283204E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.123436E+12 | 0.743894E+11 | 0.112765E+12 | 0.562563E+11 | 0.565083E+11 | 0.00 | 0.00 |
Minimum of Months | 0.771629E+10 | 0.108336E+10 | 0.662007E+10 | 0.101195E+10 | 0.283204E+10 | 0.00 | 0.00 |
Maximum of Months | 0.166341E+11 | 0.116297E+11 | 0.142327E+11 | 0.892492E+10 | 0.602371E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111912E+10 | 0.908724E+10 | 0.239391E+10 | 0.980554E+09 | 0.141336E+10 | 0.00 | 0.00 |
February | 0.170214E+10 | 0.837062E+10 | 0.318854E+10 | 0.140042E+10 | 0.178812E+10 | 0.00 | 0.00 |
March | 0.388421E+10 | 0.654544E+10 | 0.521272E+10 | 0.240657E+10 | 0.280615E+10 | 0.00 | 0.00 |
April | 0.482209E+10 | 0.484626E+10 | 0.551348E+10 | 0.235908E+10 | 0.315440E+10 | 0.00 | 0.00 |
May | 0.706935E+10 | 0.289452E+10 | 0.663673E+10 | 0.252037E+10 | 0.411636E+10 | 0.00 | 0.00 |
June | 0.874809E+10 | 0.165381E+10 | 0.702939E+10 | 0.283516E+10 | 0.419424E+10 | 0.00 | 0.00 |
July | 0.924405E+10 | 0.100257E+10 | 0.680285E+10 | 0.256174E+10 | 0.424111E+10 | 0.00 | 0.00 |
August | 0.102358E+11 | 0.134899E+10 | 0.752580E+10 | 0.348395E+10 | 0.404185E+10 | 0.00 | 0.00 |
September | 0.612359E+10 | 0.228214E+10 | 0.517038E+10 | 0.225944E+10 | 0.291093E+10 | 0.00 | 0.00 |
October | 0.537951E+10 | 0.424773E+10 | 0.529691E+10 | 0.257576E+10 | 0.272115E+10 | 0.00 | 0.00 |
November | 0.114902E+10 | 0.666868E+10 | 0.240717E+10 | 0.695689E+09 | 0.171148E+10 | 0.00 | 0.00 |
December | 0.994842E+09 | 0.894469E+10 | 0.221250E+10 | 0.957356E+09 | 0.125514E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.604718E+11 | 0.578927E+11 | 0.593904E+11 | 0.250361E+11 | 0.343543E+11 | 0.00 | 0.00 |
Minimum of Months | 0.994842E+09 | 0.100257E+10 | 0.221250E+10 | 0.695689E+09 | 0.125514E+10 | 0.00 | 0.00 |
Maximum of Months | 0.102358E+11 | 0.908724E+10 | 0.752580E+10 | 0.348395E+10 | 0.424111E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 12480350.67 | 0.127793E+11 | 0.174128E+10 | 0.00 | 0.174128E+10 | 0.00 | 0.00 |
February | 71664944.10 | 0.121528E+11 | 0.215227E+10 | 0.00 | 0.215227E+10 | 0.00 | 0.00 |
March | 0.676316E+09 | 0.889333E+10 | 0.330444E+10 | 0.00 | 0.330444E+10 | 0.00 | 0.00 |
April | 0.190796E+10 | 0.593135E+10 | 0.384105E+10 | 10925138.76 | 0.383013E+10 | 0.00 | 0.00 |
May | 0.434287E+10 | 0.355229E+10 | 0.526572E+10 | 0.175457E+09 | 0.509026E+10 | 0.00 | 0.00 |
June | 0.633439E+10 | 0.184537E+10 | 0.540409E+10 | 0.290384E+09 | 0.511370E+10 | 0.00 | 0.00 |
July | 0.759084E+10 | 0.103670E+10 | 0.539661E+10 | 0.195160E+09 | 0.520145E+10 | 0.00 | 0.00 |
August | 0.663970E+10 | 0.142724E+10 | 0.478114E+10 | 56902334.67 | 0.472424E+10 | 0.00 | 0.00 |
September | 0.351165E+10 | 0.275650E+10 | 0.348792E+10 | 653146.41 | 0.348727E+10 | 0.00 | 0.00 |
October | 0.195841E+10 | 0.531966E+10 | 0.311917E+10 | 0.00 | 0.311917E+10 | 0.00 | 0.00 |
November | 0.332616E+09 | 0.860362E+10 | 0.211722E+10 | 0.00 | 0.211722E+10 | 0.00 | 0.00 |
December | 12204579.35 | 0.119248E+11 | 0.151886E+10 | 0.00 | 0.151886E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.333911E+11 | 0.762229E+11 | 0.421298E+11 | 0.729481E+09 | 0.414003E+11 | 0.00 | 0.00 |
Minimum of Months | 12204579.35 | 0.103670E+10 | 0.151886E+10 | 0.00 | 0.151886E+10 | 0.00 | 0.00 |
Maximum of Months | 0.759084E+10 | 0.127793E+11 | 0.540409E+10 | 0.290384E+09 | 0.520145E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115966E+10 | 0.782228E+10 | 0.242489E+10 | 0.972184E+09 | 0.145270E+10 | 0.00 | 0.00 |
February | 0.190503E+10 | 0.716911E+10 | 0.339656E+10 | 0.158450E+10 | 0.181206E+10 | 0.00 | 0.00 |
March | 0.351530E+10 | 0.569675E+10 | 0.479720E+10 | 0.204028E+10 | 0.275691E+10 | 0.00 | 0.00 |
April | 0.496452E+10 | 0.382874E+10 | 0.557126E+10 | 0.244038E+10 | 0.313088E+10 | 0.00 | 0.00 |
May | 0.739777E+10 | 0.240219E+10 | 0.698199E+10 | 0.279043E+10 | 0.419157E+10 | 0.00 | 0.00 |
June | 0.779340E+10 | 0.122689E+10 | 0.626209E+10 | 0.226683E+10 | 0.399526E+10 | 0.00 | 0.00 |
July | 0.899707E+10 | 0.673160E+09 | 0.649916E+10 | 0.234539E+10 | 0.415377E+10 | 0.00 | 0.00 |
August | 0.100236E+11 | 0.938486E+09 | 0.731821E+10 | 0.329978E+10 | 0.401843E+10 | 0.00 | 0.00 |
September | 0.619254E+10 | 0.177660E+10 | 0.528190E+10 | 0.236978E+10 | 0.291212E+10 | 0.00 | 0.00 |
October | 0.496540E+10 | 0.344001E+10 | 0.494805E+10 | 0.224262E+10 | 0.270542E+10 | 0.00 | 0.00 |
November | 0.193737E+10 | 0.531195E+10 | 0.296127E+10 | 0.113716E+10 | 0.182411E+10 | 0.00 | 0.00 |
December | 0.129412E+10 | 0.723944E+10 | 0.238390E+10 | 0.111933E+10 | 0.126457E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.601458E+11 | 0.475256E+11 | 0.588265E+11 | 0.246087E+11 | 0.342178E+11 | 0.00 | 0.00 |
Minimum of Months | 0.115966E+10 | 0.673160E+09 | 0.238390E+10 | 0.972184E+09 | 0.126457E+10 | 0.00 | 0.00 |
Maximum of Months | 0.100236E+11 | 0.782228E+10 | 0.731821E+10 | 0.329978E+10 | 0.419157E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.766771E+10 | 0.112080E+11 | 0.900803E+10 | 0.589852E+10 | 0.310951E+10 | 0.00 | 0.00 |
February | 0.931940E+10 | 0.103616E+11 | 0.107315E+11 | 0.710337E+10 | 0.362811E+10 | 0.00 | 0.00 |
March | 0.100111E+11 | 0.858927E+10 | 0.107192E+11 | 0.594932E+10 | 0.476984E+10 | 0.00 | 0.00 |
April | 0.784114E+10 | 0.619007E+10 | 0.804938E+10 | 0.318297E+10 | 0.486641E+10 | 0.00 | 0.00 |
May | 0.769847E+10 | 0.388509E+10 | 0.728922E+10 | 0.152042E+10 | 0.576881E+10 | 0.00 | 0.00 |
June | 0.844050E+10 | 0.200890E+10 | 0.662005E+10 | 0.101194E+10 | 0.560811E+10 | 0.00 | 0.00 |
July | 0.104596E+11 | 0.110002E+10 | 0.717044E+10 | 0.124550E+10 | 0.592494E+10 | 0.00 | 0.00 |
August | 0.140417E+11 | 0.157774E+10 | 0.957533E+10 | 0.355165E+10 | 0.602368E+10 | 0.00 | 0.00 |
September | 0.127272E+11 | 0.296855E+10 | 0.100543E+11 | 0.520049E+10 | 0.485380E+10 | 0.00 | 0.00 |
October | 0.164311E+11 | 0.558637E+10 | 0.142326E+11 | 0.892489E+10 | 0.530775E+10 | 0.00 | 0.00 |
November | 0.902378E+10 | 0.797133E+10 | 0.955076E+10 | 0.573569E+10 | 0.381507E+10 | 0.00 | 0.00 |
December | 0.880766E+10 | 0.104182E+11 | 0.976336E+10 | 0.693133E+10 | 0.283203E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.122469E+12 | 0.718651E+11 | 0.112764E+12 | 0.562561E+11 | 0.565081E+11 | 0.00 | 0.00 |
Minimum of Months | 0.766771E+10 | 0.110002E+10 | 0.662005E+10 | 0.101194E+10 | 0.283203E+10 | 0.00 | 0.00 |
Maximum of Months | 0.164311E+11 | 0.112080E+11 | 0.142326E+11 | 0.892489E+10 | 0.602368E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.116548E+10 | 0.820848E+10 | 0.239390E+10 | 0.980550E+09 | 0.141335E+10 | 0.00 | 0.00 |
February | 0.175599E+10 | 0.768848E+10 | 0.318852E+10 | 0.140041E+10 | 0.178811E+10 | 0.00 | 0.00 |
March | 0.399502E+10 | 0.579689E+10 | 0.521270E+10 | 0.240656E+10 | 0.280614E+10 | 0.00 | 0.00 |
April | 0.503124E+10 | 0.411497E+10 | 0.551346E+10 | 0.235907E+10 | 0.315439E+10 | 0.00 | 0.00 |
May | 0.717075E+10 | 0.260477E+10 | 0.663671E+10 | 0.252036E+10 | 0.411634E+10 | 0.00 | 0.00 |
June | 0.883207E+10 | 0.143858E+10 | 0.702937E+10 | 0.283514E+10 | 0.419422E+10 | 0.00 | 0.00 |
July | 0.938476E+10 | 0.846848E+09 | 0.680282E+10 | 0.256173E+10 | 0.424109E+10 | 0.00 | 0.00 |
August | 0.104048E+11 | 0.115176E+10 | 0.752577E+10 | 0.348394E+10 | 0.404183E+10 | 0.00 | 0.00 |
September | 0.624704E+10 | 0.196166E+10 | 0.517036E+10 | 0.225943E+10 | 0.291092E+10 | 0.00 | 0.00 |
October | 0.551764E+10 | 0.372674E+10 | 0.529689E+10 | 0.257575E+10 | 0.272114E+10 | 0.00 | 0.00 |
November | 0.128088E+10 | 0.565296E+10 | 0.240716E+10 | 0.695686E+09 | 0.171147E+10 | 0.00 | 0.00 |
December | 0.109877E+10 | 0.768572E+10 | 0.221249E+10 | 0.957352E+09 | 0.125514E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.618844E+11 | 0.508779E+11 | 0.593902E+11 | 0.250360E+11 | 0.343542E+11 | 0.00 | 0.00 |
Minimum of Months | 0.109877E+10 | 0.846848E+09 | 0.221249E+10 | 0.695686E+09 | 0.125514E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104048E+11 | 0.820848E+10 | 0.752577E+10 | 0.348394E+10 | 0.424109E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 17503988.93 | 0.122018E+11 | 0.174128E+10 | 0.00 | 0.174128E+10 | 0.00 | 0.00 |
February | 0.102077E+09 | 0.115567E+11 | 0.215227E+10 | 0.00 | 0.215227E+10 | 0.00 | 0.00 |
March | 0.738121E+09 | 0.817031E+10 | 0.330444E+10 | 0.00 | 0.330444E+10 | 0.00 | 0.00 |
April | 0.202336E+10 | 0.538139E+10 | 0.384105E+10 | 10925138.76 | 0.383013E+10 | 0.00 | 0.00 |
May | 0.447665E+10 | 0.323061E+10 | 0.526572E+10 | 0.175457E+09 | 0.509026E+10 | 0.00 | 0.00 |
June | 0.636509E+10 | 0.172208E+10 | 0.540409E+10 | 0.290384E+09 | 0.511370E+10 | 0.00 | 0.00 |
July | 0.756655E+10 | 0.975908E+09 | 0.539661E+10 | 0.195160E+09 | 0.520145E+10 | 0.00 | 0.00 |
August | 0.664176E+10 | 0.132767E+10 | 0.478114E+10 | 56902334.67 | 0.472424E+10 | 0.00 | 0.00 |
September | 0.361217E+10 | 0.246504E+10 | 0.348792E+10 | 653146.41 | 0.348727E+10 | 0.00 | 0.00 |
October | 0.213609E+10 | 0.468328E+10 | 0.311917E+10 | 0.00 | 0.311917E+10 | 0.00 | 0.00 |
November | 0.410341E+09 | 0.776446E+10 | 0.211722E+10 | 0.00 | 0.211722E+10 | 0.00 | 0.00 |
December | 32638142.23 | 0.110085E+11 | 0.151886E+10 | 0.00 | 0.151886E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.341224E+11 | 0.704877E+11 | 0.421298E+11 | 0.729481E+09 | 0.414003E+11 | 0.00 | 0.00 |
Minimum of Months | 17503988.93 | 0.975908E+09 | 0.151886E+10 | 0.00 | 0.151886E+10 | 0.00 | 0.00 |
Maximum of Months | 0.756655E+10 | 0.122018E+11 | 0.540409E+10 | 0.290384E+09 | 0.520145E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119570E+10 | 0.744747E+10 | 0.242489E+10 | 0.972184E+09 | 0.145270E+10 | 0.00 | 0.00 |
February | 0.198578E+10 | 0.677548E+10 | 0.339656E+10 | 0.158450E+10 | 0.181206E+10 | 0.00 | 0.00 |
March | 0.362244E+10 | 0.520541E+10 | 0.479720E+10 | 0.204028E+10 | 0.275691E+10 | 0.00 | 0.00 |
April | 0.506390E+10 | 0.350823E+10 | 0.557126E+10 | 0.244038E+10 | 0.313088E+10 | 0.00 | 0.00 |
May | 0.745552E+10 | 0.223402E+10 | 0.698199E+10 | 0.279043E+10 | 0.419157E+10 | 0.00 | 0.00 |
June | 0.777636E+10 | 0.117857E+10 | 0.626209E+10 | 0.226683E+10 | 0.399526E+10 | 0.00 | 0.00 |
July | 0.894196E+10 | 0.662875E+09 | 0.649916E+10 | 0.234539E+10 | 0.415377E+10 | 0.00 | 0.00 |
August | 0.998066E+10 | 0.907739E+09 | 0.731821E+10 | 0.329978E+10 | 0.401843E+10 | 0.00 | 0.00 |
September | 0.623601E+10 | 0.163739E+10 | 0.528190E+10 | 0.236978E+10 | 0.291212E+10 | 0.00 | 0.00 |
October | 0.511189E+10 | 0.307163E+10 | 0.494805E+10 | 0.224262E+10 | 0.270542E+10 | 0.00 | 0.00 |
November | 0.207499E+10 | 0.476498E+10 | 0.296127E+10 | 0.113716E+10 | 0.182411E+10 | 0.00 | 0.00 |
December | 0.136844E+10 | 0.665147E+10 | 0.238390E+10 | 0.111933E+10 | 0.126457E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.608136E+11 | 0.440453E+11 | 0.588265E+11 | 0.246087E+11 | 0.342178E+11 | 0.00 | 0.00 |
Minimum of Months | 0.119570E+10 | 0.662875E+09 | 0.238390E+10 | 0.972184E+09 | 0.126457E+10 | 0.00 | 0.00 |
Maximum of Months | 0.998066E+10 | 0.744747E+10 | 0.731821E+10 | 0.329978E+10 | 0.419157E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.775574E+10 | 0.105825E+11 | 0.900803E+10 | 0.589852E+10 | 0.310951E+10 | 0.00 | 0.00 |
February | 0.944869E+10 | 0.970428E+10 | 0.107315E+11 | 0.710337E+10 | 0.362811E+10 | 0.00 | 0.00 |
March | 0.101007E+11 | 0.784127E+10 | 0.107192E+11 | 0.594932E+10 | 0.476984E+10 | 0.00 | 0.00 |
April | 0.793328E+10 | 0.563823E+10 | 0.804938E+10 | 0.318297E+10 | 0.486641E+10 | 0.00 | 0.00 |
May | 0.777225E+10 | 0.354589E+10 | 0.728922E+10 | 0.152042E+10 | 0.576881E+10 | 0.00 | 0.00 |
June | 0.843472E+10 | 0.187674E+10 | 0.662005E+10 | 0.101194E+10 | 0.560811E+10 | 0.00 | 0.00 |
July | 0.104133E+11 | 0.103231E+10 | 0.717044E+10 | 0.124550E+10 | 0.592494E+10 | 0.00 | 0.00 |
August | 0.139939E+11 | 0.147538E+10 | 0.957533E+10 | 0.355165E+10 | 0.602368E+10 | 0.00 | 0.00 |
September | 0.127692E+11 | 0.269232E+10 | 0.100543E+11 | 0.520049E+10 | 0.485380E+10 | 0.00 | 0.00 |
October | 0.165577E+11 | 0.498352E+10 | 0.142326E+11 | 0.892489E+10 | 0.530775E+10 | 0.00 | 0.00 |
November | 0.922796E+10 | 0.714689E+10 | 0.955076E+10 | 0.573569E+10 | 0.381507E+10 | 0.00 | 0.00 |
December | 0.900118E+10 | 0.950154E+10 | 0.976336E+10 | 0.693133E+10 | 0.283203E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.123409E+12 | 0.660209E+11 | 0.112764E+12 | 0.562561E+11 | 0.565081E+11 | 0.00 | 0.00 |
Minimum of Months | 0.775574E+10 | 0.103231E+10 | 0.662005E+10 | 0.101194E+10 | 0.283203E+10 | 0.00 | 0.00 |
Maximum of Months | 0.165577E+11 | 0.105825E+11 | 0.142326E+11 | 0.892489E+10 | 0.602368E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117623E+10 | 0.784374E+10 | 0.239390E+10 | 0.980550E+09 | 0.141335E+10 | 0.00 | 0.00 |
February | 0.176939E+10 | 0.732810E+10 | 0.318852E+10 | 0.140041E+10 | 0.178811E+10 | 0.00 | 0.00 |
March | 0.401160E+10 | 0.538669E+10 | 0.521270E+10 | 0.240656E+10 | 0.280614E+10 | 0.00 | 0.00 |
April | 0.504664E+10 | 0.381349E+10 | 0.551346E+10 | 0.235907E+10 | 0.315439E+10 | 0.00 | 0.00 |
May | 0.716717E+10 | 0.243354E+10 | 0.663671E+10 | 0.252036E+10 | 0.411634E+10 | 0.00 | 0.00 |
June | 0.878625E+10 | 0.137312E+10 | 0.702937E+10 | 0.283514E+10 | 0.419422E+10 | 0.00 | 0.00 |
July | 0.931971E+10 | 0.816206E+09 | 0.680282E+10 | 0.256173E+10 | 0.424109E+10 | 0.00 | 0.00 |
August | 0.103562E+11 | 0.110226E+10 | 0.752577E+10 | 0.348394E+10 | 0.404183E+10 | 0.00 | 0.00 |
September | 0.624769E+10 | 0.182595E+10 | 0.517036E+10 | 0.225943E+10 | 0.291092E+10 | 0.00 | 0.00 |
October | 0.555827E+10 | 0.339397E+10 | 0.529689E+10 | 0.257575E+10 | 0.272114E+10 | 0.00 | 0.00 |
November | 0.132323E+10 | 0.519125E+10 | 0.240716E+10 | 0.695686E+09 | 0.171147E+10 | 0.00 | 0.00 |
December | 0.112806E+10 | 0.715013E+10 | 0.221249E+10 | 0.957352E+09 | 0.125514E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.618904E+11 | 0.476584E+11 | 0.593902E+11 | 0.250360E+11 | 0.343542E+11 | 0.00 | 0.00 |
Minimum of Months | 0.112806E+10 | 0.816206E+09 | 0.221249E+10 | 0.695686E+09 | 0.125514E+10 | 0.00 | 0.00 |
Maximum of Months | 0.103562E+11 | 0.784374E+10 | 0.752577E+10 | 0.348394E+10 | 0.424109E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.402200E+11 | -0.397645E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -455573424.7 | 60.05 | 0.00 | 0.00 |
February | 0.369008E+11 | -0.364896E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -411178859.1 | 60.05 | 0.00 | 0.00 |
March | 0.424212E+11 | -0.419703E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -450892387.5 | 60.05 | 0.00 | 0.00 |
April | 0.365751E+11 | -0.361413E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -433822175.5 | 60.05 | 0.00 | 0.00 |
May | 0.364322E+11 | -0.359852E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -447035012.3 | 60.05 | 0.00 | 0.00 |
June | 0.335728E+11 | -0.331414E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -431450881.0 | 60.05 | 0.00 | 0.00 |
July | 0.303301E+11 | -0.298871E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443028192.4 | 60.05 | 0.00 | 0.00 |
August | 0.327270E+11 | -0.322827E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444227969.8 | 60.05 | 0.00 | 0.00 |
September | 0.306142E+11 | -0.301854E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -428806053.2 | 60.05 | 0.00 | 0.00 |
October | 0.335934E+11 | -0.331507E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442676324.6 | 60.05 | 0.00 | 0.00 |
November | 0.354479E+11 | -0.350175E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -430463382.8 | 60.05 | 0.00 | 0.00 |
December | 0.376420E+11 | -0.371940E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -447996648.0 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.426477E+12 | -0.421210E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.526715E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.303301E+11 | -0.419703E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -455573424.7 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.424212E+11 | -0.298871E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -411178859.1 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 216.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 261.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 372.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 365.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 285.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 305.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 240.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 211.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3472.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.947725E+10 | 47571.09 | 02-JAN-03:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.893051E+10 | 46392.23 | 06-FEB-03:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127055E+10 | 17721.10 | 23-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7480697.21 | 1928.69 | 03-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24249.65 | 162.05 | 04-JUL-17:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 138684.07 | 179.26 | 08-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 263338.61 | 477.23 | 19-SEP-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.888346E+09 | 17701.26 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145281E+10 | 17408.27 | 22-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.947725E+10 | 47571.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 25739993.92 | 33719.82 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25739993.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25739993.92 | 33719.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.276297E+10 | 19743.22 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.259356E+10 | 19670.83 | 08-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.547070E+09 | 20484.32 | 23-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 63293435.41 | 17058.48 | 21-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11525736.64 | 3135.27 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.403058E+09 | 19453.69 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100315E+10 | 20128.24 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.738462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.276297E+10 | 20484.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.311369E+10 | 18977.80 | 14-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.257807E+10 | 18973.02 | 13-FEB-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114535E+10 | 19016.70 | 23-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.470994E+09 | 15767.73 | 21-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10602060.56 | 3672.03 | 04-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1369954.85 | 1365.13 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110224E+09 | 6258.39 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.919093E+09 | 18217.58 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196635E+10 | 18678.13 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.311369E+10 | 19016.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.345492E+10 | 25685.00 | 02-JAN-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.287760E+10 | 25687.87 | 06-FEB-04:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120170E+10 | 25891.86 | 23-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.491072E+09 | 22588.15 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26644842.82 | 6435.83 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 97525729.65 | 11745.63 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.905115E+09 | 24665.89 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193748E+10 | 25281.00 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.345492E+10 | 25891.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.246588E+10 | 19089.44 | 02-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.206819E+10 | 19094.12 | 13-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.358884E+09 | 17633.23 | 22-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39160806.07 | 2666.21 | 21-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2319688.25 | 1699.61 | 04-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 37194618.07 | 2548.28 | 28-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.347117E+09 | 18333.79 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.533770E+09 | 17981.55 | 15-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.585251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.246588E+10 | 19094.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.244536E+12 | 574696.64 | 02-JAN-02:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.213830E+12 | 565801.88 | 06-FEB-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.373754E+11 | 240926.74 | 23-MAR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138425E+10 | 74615.09 | 03-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7663873.08 | 4246.60 | 08-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15822.90 | 210.97 | 04-SEP-09:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2631572.57 | 6203.86 | 28-OCT-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.322616E+11 | 268223.35 | 23-NOV-05:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.729113E+11 | 416533.87 | 31-DEC-23:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.602310E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.244536E+12 | 574696.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.214505E+11 | 721270.12 | 02-JAN-05:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.566994E+10 | 721183.79 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.627624E+09 | 689923.69 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.273594E+09 | 396990.19 | 26-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.214505E+11 | 721270.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107405E+12 | 299429.63 | 02-JAN-02:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.933158E+11 | 289499.15 | 13-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.460370E+11 | 288651.97 | 23-MAR-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.184592E+11 | 257531.67 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134118E+10 | 240528.02 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.599158E+09 | 34462.62 | 30-SEP-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.785096E+10 | 250806.16 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.420710E+11 | 288294.54 | 24-NOV-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.748418E+11 | 288254.12 | 31-DEC-21:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391921E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107405E+12 | 299429.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.655328E+11 | 236705.90 | 02-JAN-02:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.516212E+11 | 233914.27 | 06-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.278194E+11 | 227142.54 | 23-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130814E+11 | 197666.66 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156512E+10 | 184411.29 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3523275.81 | 13158.33 | 07-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.792698E+09 | 42718.39 | 29-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.567501E+10 | 192448.73 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.263567E+11 | 224328.27 | 24-NOV-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.450756E+11 | 232887.31 | 31-DEC-22:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237523E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.655328E+11 | 236705.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.706362E+11 | 293867.30 | 02-JAN-02:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.527089E+11 | 284121.36 | 13-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.278581E+11 | 281666.74 | 23-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143703E+11 | 252747.61 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140318E+10 | 236059.87 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87257077.61 | 14657.89 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.326076E+10 | 246147.04 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.231288E+11 | 282167.12 | 25-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.446571E+11 | 281487.65 | 15-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238111E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.706362E+11 | 293867.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.702361E+11 | 242495.98 | 02-JAN-02:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.582600E+11 | 239626.04 | 06-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.294865E+11 | 232691.40 | 23-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136811E+11 | 202509.87 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.206432E+10 | 76433.81 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17030757.66 | 13469.73 | 07-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.980516E+09 | 38221.46 | 30-SEP-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.598654E+10 | 197150.91 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.312147E+11 | 229816.50 | 24-NOV-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.510244E+11 | 238499.18 | 31-DEC-22:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.262951E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.702361E+11 | 242495.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.362491E+11 | 49858.34 | 02-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.334786E+11 | 50320.55 | 06-FEB-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.940036E+10 | 43471.79 | 23-MAR-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138721E+10 | 27133.94 | 02-APR-02:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26096922.15 | 8418.90 | 01-MAY-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 63973.94 | 241.62 | 04-JUL-17:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 351369.76 | 585.62 | 08-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 48968.37 | 231.76 | 04-SEP-09:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.345182E+09 | 30213.13 | 09-OCT-05:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.987602E+10 | 45478.73 | 24-NOV-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207852E+11 | 46578.97 | 31-DEC-23:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111548E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.362491E+11 | 50320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.149852E+11 | 123589.82 | 02-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123421E+11 | 124725.67 | 06-FEB-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.456273E+10 | 116031.10 | 23-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156783E+10 | 101660.24 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151319E+09 | 91424.05 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.713542E+09 | 98246.64 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.600726E+10 | 115069.74 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.963587E+10 | 113567.37 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.499658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.149852E+11 | 124725.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.179939E+11 | 41123.84 | 02-JAN-02:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167433E+11 | 41712.66 | 06-FEB-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.959374E+10 | 37187.27 | 23-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.463751E+10 | 33295.78 | 03-APR-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112278E+10 | 29974.78 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32876705.93 | 3994.14 | 03-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16028388.02 | 3197.65 | 29-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.603397E+09 | 28807.97 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.294125E+10 | 32246.36 | 28-OCT-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.950030E+10 | 37648.78 | 23-NOV-06:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146950E+11 | 40626.86 | 31-DEC-22:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.778801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.179939E+11 | 41712.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109584E+11 | 27954.03 | 02-JAN-02:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.948749E+10 | 28355.49 | 06-FEB-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.516799E+10 | 25845.28 | 23-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.263931E+10 | 22618.14 | 03-APR-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.585309E+09 | 20354.75 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8880598.79 | 2486.77 | 07-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3023846.50 | 2589.37 | 08-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.303195E+09 | 19180.52 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142709E+10 | 21903.10 | 28-OCT-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.539681E+10 | 25584.89 | 23-NOV-06:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.878011E+10 | 27615.11 | 31-DEC-22:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.447576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109584E+11 | 28355.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131699E+11 | 40518.63 | 02-JAN-02:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110257E+11 | 41098.79 | 06-FEB-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.660556E+10 | 36556.80 | 23-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.383934E+10 | 32805.78 | 03-APR-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109074E+10 | 29533.65 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 71281303.50 | 5191.44 | 03-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11201518.36 | 1736.07 | 08-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.377745E+09 | 18118.79 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154999E+10 | 31727.90 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.604846E+10 | 37094.72 | 23-NOV-06:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.989546E+10 | 40028.97 | 31-DEC-22:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.536853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131699E+11 | 41098.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106738E+11 | 29897.41 | 02-JAN-02:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.926859E+10 | 30303.06 | 06-FEB-01:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.507637E+10 | 27615.10 | 23-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.265120E+10 | 23993.10 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.749322E+09 | 21733.86 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 47597592.42 | 3483.33 | 03-JUN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6111455.57 | 968.64 | 08-AUG-05:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.396631E+09 | 11096.05 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157241E+10 | 23364.71 | 28-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.549342E+10 | 27351.15 | 23-NOV-06:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.822729E+10 | 29492.20 | 31-DEC-23:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.441627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106738E+11 | 30303.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 11733177.55 | 5645.74 | 02-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 11733177.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11733177.55 | 5645.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.125085E+11 | 0.125085E+11 | 100785.02 | 21-JAN-06:01 | 100785.02 | 0.05 |
February | 0.00 | 0.00 | 0.104330E+11 | 0.104330E+11 | 102752.64 | 24-FEB-06:01 | 102752.64 | 0.00 |
March | 0.00 | 0.00 | 0.375796E+11 | 0.374502E+11 | 114321.62 | 06-MAR-06:02 | 114321.62 | 0.06 |
April | 0.00 | 0.00 | 0.633834E+11 | 0.633584E+11 | 137104.64 | 28-APR-04:12 | 125943.86 | 0.23 |
May | 0.00 | 0.00 | 0.951743E+11 | 0.913979E+11 | 197949.22 | 19-MAY-04:12 | 131501.60 | 0.42 |
June | 0.00 | 0.00 | 0.159790E+12 | 0.132383E+12 | 230931.57 | 13-JUN-04:11 | 147570.12 | 0.61 |
July | 0.00 | 0.00 | 0.223199E+12 | 0.165699E+12 | 277125.24 | 14-JUL-05:02 | 188809.37 | 0.72 |
August | 0.00 | 0.00 | 0.228441E+12 | 0.186759E+12 | 281832.57 | 02-AUG-05:02 | 188694.88 | 0.76 |
September | 0.00 | 0.00 | 0.127909E+12 | 0.113336E+12 | 248927.55 | 22-SEP-04:11 | 158524.56 | 0.55 |
October | 0.00 | 0.00 | 0.944193E+11 | 0.872656E+11 | 222053.33 | 25-OCT-04:11 | 143015.30 | 0.38 |
November | 0.00 | 0.00 | 0.420371E+11 | 0.418952E+11 | 138802.47 | 10-NOV-06:01 | 113900.99 | 0.11 |
December | 0.00 | 0.00 | 0.231118E+11 | 0.231118E+11 | 104469.23 | 18-DEC-06:01 | 104469.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.111799E+13 | 0.965597E+12 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 0.104330E+11 | 0.104330E+11 | 100785.02 | 100785.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.228441E+12 | 0.186759E+12 | 281832.57 | 188809.37 | 0.76 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.386193E+11 | 0.386193E+11 | 249466.95 | 20-JAN-15:30 | 249466.95 | 0.05 |
February | 0.00 | 0.00 | 0.334374E+11 | 0.334374E+11 | 362798.95 | 20-FEB-13:01 | 362798.95 | 0.00 |
March | 0.00 | 0.00 | 0.205377E+12 | 0.204546E+12 | 1163694.71 | 03-MAR-06:01 | 1163694.71 | 0.06 |
April | 0.00 | 0.00 | 0.427718E+12 | 0.427651E+12 | 1205836.71 | 10-APR-05:03 | 1138039.47 | 0.21 |
May | 0.00 | 0.00 | 0.812443E+12 | 0.776788E+12 | 1634338.18 | 31-MAY-04:12 | 1329447.59 | 0.40 |
June | 0.00 | 0.00 | 0.141539E+13 | 0.114520E+13 | 2378903.62 | 27-JUN-05:02 | 1342046.46 | 0.58 |
July | 0.00 | 0.00 | 0.185975E+13 | 0.134724E+13 | 2704236.65 | 20-JUL-05:02 | 1618192.76 | 0.61 |
August | 0.00 | 0.00 | 0.182709E+13 | 0.147575E+13 | 2794076.17 | 03-AUG-05:02 | 1732830.57 | 0.62 |
September | 0.00 | 0.00 | 0.111819E+13 | 0.972187E+12 | 2312353.77 | 22-SEP-04:11 | 1346895.10 | 0.53 |
October | 0.00 | 0.00 | 0.755363E+12 | 0.684432E+12 | 2066540.77 | 25-OCT-04:11 | 1283676.78 | 0.36 |
November | 0.00 | 0.00 | 0.231328E+12 | 0.230223E+12 | 1280316.59 | 10-NOV-06:01 | 1075454.82 | 0.10 |
December | 0.00 | 0.00 | 0.585426E+11 | 0.585426E+11 | 459598.43 | 17-DEC-13:12 | 459598.43 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.878324E+13 | 0.739462E+13 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 0.334374E+11 | 0.334374E+11 | 249466.95 | 249466.95 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.185975E+13 | 0.147575E+13 | 2794076.17 | 1732830.57 | 0.62 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.471924E+10 | 0.471924E+10 | 30643.92 | 17-JAN-14:00 | 30643.92 | 0.05 |
February | 0.00 | 0.00 | 0.304080E+10 | 0.304080E+10 | 25361.32 | 17-FEB-14:00 | 25361.32 | 0.00 |
March | 0.00 | 0.00 | 0.197796E+11 | 0.197385E+11 | 79195.45 | 27-MAR-16:00 | 75823.62 | 0.06 |
April | 0.00 | 0.00 | 0.435138E+11 | 0.435127E+11 | 144160.40 | 07-APR-14:40 | 144160.40 | 0.21 |
May | 0.00 | 0.00 | 0.889372E+11 | 0.855966E+11 | 187237.43 | 31-MAY-14:00 | 164706.77 | 0.40 |
June | 0.00 | 0.00 | 0.159022E+12 | 0.132213E+12 | 272714.45 | 27-JUN-05:02 | 143833.47 | 0.57 |
July | 0.00 | 0.00 | 0.210151E+12 | 0.158732E+12 | 349287.43 | 09-JUL-14:11 | 231535.01 | 0.61 |
August | 0.00 | 0.00 | 0.204713E+12 | 0.169873E+12 | 307956.94 | 05-AUG-03:01 | 202660.75 | 0.62 |
September | 0.00 | 0.00 | 0.117439E+12 | 0.103492E+12 | 255176.18 | 14-SEP-05:03 | 135002.79 | 0.52 |
October | 0.00 | 0.00 | 0.709861E+11 | 0.648068E+11 | 224259.54 | 06-OCT-05:01 | 123930.62 | 0.36 |
November | 0.00 | 0.00 | 0.186540E+11 | 0.185746E+11 | 69316.40 | 03-NOV-14:31 | 69316.40 | 0.10 |
December | 0.00 | 0.00 | 0.371001E+10 | 0.371001E+10 | 20330.54 | 19-DEC-14:00 | 20330.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.944666E+12 | 0.808010E+12 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 0.304080E+10 | 0.304080E+10 | 20330.54 | 20330.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.210151E+12 | 0.169873E+12 | 349287.43 | 231535.01 | 0.62 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.739839E+10 | 0.731618E+10 | 88803.24 | 23-JAN-06:01 | 88803.24 | 0.04 |
February | 0.00 | 0.00 | 0.296783E+10 | 0.296783E+10 | 104935.89 | 24-FEB-05:11 | 104935.89 | 0.00 |
March | 0.00 | 0.00 | 0.155184E+11 | 0.152152E+11 | 103045.57 | 01-MAR-06:01 | 103045.57 | 0.05 |
April | 0.00 | 0.00 | 0.292202E+11 | 0.288293E+11 | 96048.89 | 27-APR-04:12 | 96048.89 | 0.18 |
May | 0.00 | 0.00 | 0.480498E+11 | 0.429090E+11 | 121749.64 | 19-MAY-04:12 | 101800.56 | 0.38 |
June | 0.00 | 0.00 | 0.854508E+11 | 0.631082E+11 | 153379.19 | 26-JUN-04:23 | 97223.36 | 0.54 |
July | 0.00 | 0.00 | 0.109406E+12 | 0.725528E+11 | 165521.50 | 24-JUL-04:23 | 98657.77 | 0.53 |
August | 0.00 | 0.00 | 0.113168E+12 | 0.835955E+11 | 153293.16 | 02-AUG-05:02 | 113306.83 | 0.59 |
September | 0.00 | 0.00 | 0.805727E+11 | 0.651885E+11 | 150028.65 | 04-SEP-11:48 | 125112.64 | 0.52 |
October | 0.00 | 0.00 | 0.645474E+11 | 0.555860E+11 | 144999.21 | 15-OCT-20:09 | 114630.23 | 0.37 |
November | 0.00 | 0.00 | 0.314144E+11 | 0.307556E+11 | 102065.16 | 12-NOV-15:41 | 102065.16 | 0.11 |
December | 0.00 | 0.00 | 0.126399E+11 | 0.126399E+11 | 91469.59 | 26-DEC-05:11 | 91469.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.600354E+12 | 0.480664E+12 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 0.296783E+10 | 0.296783E+10 | 88803.24 | 88803.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.113168E+12 | 0.835955E+11 | 165521.50 | 125112.64 | 0.59 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4224781.43 | 4224781.43 | 66.77 | 03-JAN-10:15 | 66.77 | 0.01 |
February | 0.00 | 0.00 | 0.150762E+12 | 0.150762E+12 | 272093.96 | 06-FEB-04:41 | 272093.96 | 0.00 |
March | 0.00 | 0.00 | 0.224280E+12 | 0.223237E+12 | 392504.53 | 27-MAR-12:27 | 233550.95 | 0.04 |
April | 0.00 | 0.00 | 0.246311E+12 | 0.244274E+12 | 363695.04 | 07-APR-13:05 | 363695.04 | 0.27 |
May | 0.00 | 0.00 | 0.121009E+11 | 0.118633E+11 | 405561.33 | 31-MAY-23:10 | 208571.87 | 0.20 |
June | 0.00 | 0.00 | 0.405781E+12 | 0.354832E+12 | 536530.71 | 13-JUN-19:02 | 222934.36 | 0.83 |
July | 0.00 | 0.00 | 0.757573E+12 | 0.737645E+12 | 500258.60 | 05-JUL-07:30 | 287924.52 | 1.00 |
August | 0.00 | 0.00 | 0.882423E+12 | 0.863089E+12 | 519443.68 | 10-AUG-07:30 | 387537.53 | 0.96 |
September | 0.00 | 0.00 | 0.425893E+11 | 0.416008E+11 | 186695.39 | 01-SEP-14:00 | 186695.39 | 0.48 |
October | 0.00 | 0.00 | 0.240233E+12 | 0.182346E+12 | 507610.04 | 24-OCT-09:36 | 210516.10 | 0.35 |
November | 0.00 | 0.00 | 0.216842E+12 | 0.212262E+12 | 368009.81 | 10-NOV-10:00 | 150925.20 | 0.13 |
December | 0.00 | 0.00 | 0.231698E+12 | 0.231698E+12 | 279428.77 | 08-DEC-15:57 | 279428.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.341060E+13 | 0.325361E+13 | 0.36 | |||
Minimum of Months | 0.00 | 0.00 | 4224781.43 | 4224781.43 | 66.77 | 66.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.882423E+12 | 0.863089E+12 | 536530.71 | 387537.53 | 1.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.424548E+10 | 0.424378E+10 | 3143.16 | 20-JAN-16:30 | 3143.16 | 0.00 |
February | 0.00 | 0.00 | 0.851076E+10 | 0.851076E+10 | 5102.60 | 22-FEB-16:53 | 5102.60 | 0.00 |
March | 0.00 | 0.00 | 0.157985E+11 | 0.157898E+11 | 7510.37 | 31-MAR-23:53 | 7510.37 | 0.00 |
April | 0.00 | 0.00 | 0.208726E+11 | 0.208505E+11 | 9304.82 | 07-APR-16:00 | 9229.77 | 0.00 |
May | 0.00 | 0.00 | 0.724125E+10 | 0.714481E+10 | 4779.48 | 31-MAY-23:01 | 4568.25 | 0.00 |
June | 0.00 | 0.00 | 0.129746E+11 | 0.124928E+11 | 6687.59 | 30-JUN-23:20 | 6407.90 | 0.00 |
July | 0.00 | 0.00 | 0.190973E+11 | 0.182318E+11 | 8886.69 | 31-JUL-23:10 | 8381.27 | 0.00 |
August | 0.00 | 0.00 | 0.239776E+11 | 0.233421E+11 | 10060.45 | 31-AUG-17:20 | 9668.49 | 0.00 |
September | 0.00 | 0.00 | 0.767160E+10 | 0.739881E+10 | 4294.12 | 30-SEP-23:30 | 4294.12 | 0.00 |
October | 0.00 | 0.00 | 0.120814E+11 | 0.119191E+11 | 5908.09 | 04-OCT-16:00 | 5626.03 | 0.00 |
November | 0.00 | 0.00 | 0.153780E+11 | 0.153654E+11 | 7181.45 | 03-NOV-15:55 | 7181.45 | 0.00 |
December | 0.00 | 0.00 | 0.203499E+11 | 0.203499E+11 | 8841.33 | 08-DEC-15:51 | 8841.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.168199E+12 | 0.165640E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.424548E+10 | 0.424378E+10 | 3143.16 | 3143.16 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.239776E+11 | 0.233421E+11 | 10060.45 | 9668.49 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.216710E+11 | 0.216547E+11 | 27768.05 | 20-JAN-16:30 | 27768.05 | 0.00 |
February | 0.00 | 0.00 | 0.656720E+11 | 0.656720E+11 | 47895.81 | 22-FEB-16:53 | 47895.81 | 0.00 |
March | 0.00 | 0.00 | 0.139757E+12 | 0.139671E+12 | 70666.23 | 27-MAR-17:00 | 69668.21 | 0.00 |
April | 0.00 | 0.00 | 0.191318E+12 | 0.191101E+12 | 88857.73 | 07-APR-16:00 | 88106.69 | 0.00 |
May | 0.00 | 0.00 | 0.631544E+11 | 0.622104E+11 | 45423.49 | 31-MAY-23:01 | 43298.79 | 0.00 |
June | 0.00 | 0.00 | 0.121996E+12 | 0.117205E+12 | 62989.76 | 30-JUN-23:20 | 60158.75 | 0.00 |
July | 0.00 | 0.00 | 0.181900E+12 | 0.173278E+12 | 85453.24 | 31-JUL-23:10 | 80366.66 | 0.00 |
August | 0.00 | 0.00 | 0.228837E+12 | 0.222501E+12 | 96788.07 | 31-AUG-17:20 | 92857.38 | 0.00 |
September | 0.00 | 0.00 | 0.676051E+11 | 0.649264E+11 | 40067.64 | 06-SEP-17:20 | 37420.08 | 0.00 |
October | 0.00 | 0.00 | 0.107631E+12 | 0.106021E+12 | 56384.01 | 04-OCT-16:00 | 53562.19 | 0.00 |
November | 0.00 | 0.00 | 0.132083E+12 | 0.131958E+12 | 68125.36 | 03-NOV-15:55 | 68125.36 | 0.00 |
December | 0.00 | 0.00 | 0.176352E+12 | 0.176352E+12 | 82618.10 | 08-DEC-16:03 | 82618.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.149798E+13 | 0.147255E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.216710E+11 | 0.216547E+11 | 27768.05 | 27768.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.228837E+12 | 0.222501E+12 | 96788.07 | 92857.38 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.127373E+10 | 0.127227E+10 | 2729.72 | 19-JAN-16:30 | 2729.72 | 0.00 |
February | 0.00 | 0.00 | 0.475471E+10 | 0.475471E+10 | 4721.52 | 22-FEB-16:53 | 4721.52 | 0.00 |
March | 0.00 | 0.00 | 0.123594E+11 | 0.123509E+11 | 7131.12 | 27-MAR-17:00 | 7032.06 | 0.00 |
April | 0.00 | 0.00 | 0.180641E+11 | 0.180442E+11 | 9114.65 | 07-APR-16:00 | 9039.60 | 0.00 |
May | 0.00 | 0.00 | 0.580301E+10 | 0.571066E+10 | 4454.71 | 31-MAY-23:01 | 4244.80 | 0.00 |
June | 0.00 | 0.00 | 0.121682E+11 | 0.116894E+11 | 6161.21 | 30-JUN-23:20 | 5877.70 | 0.00 |
July | 0.00 | 0.00 | 0.183418E+11 | 0.174805E+11 | 8521.35 | 31-JUL-23:10 | 8027.98 | 0.00 |
August | 0.00 | 0.00 | 0.229669E+11 | 0.223357E+11 | 9844.68 | 02-AUG-15:50 | 9282.53 | 0.00 |
September | 0.00 | 0.00 | 0.638800E+10 | 0.612239E+10 | 4161.63 | 06-SEP-17:20 | 3897.63 | 0.00 |
October | 0.00 | 0.00 | 0.958637E+10 | 0.942633E+10 | 5805.96 | 04-OCT-16:00 | 5523.16 | 0.00 |
November | 0.00 | 0.00 | 0.113613E+11 | 0.113489E+11 | 6818.27 | 03-NOV-15:55 | 6818.27 | 0.00 |
December | 0.00 | 0.00 | 0.153597E+11 | 0.153597E+11 | 8078.51 | 08-DEC-16:03 | 8078.51 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.138427E+12 | 0.135896E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.127373E+10 | 0.127227E+10 | 2729.72 | 2729.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.229669E+11 | 0.223357E+11 | 9844.68 | 9282.53 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 261855.55 | 3340522.95 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 241230.81 | 2815692.34 | 10-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 79341.33 | 2804537.30 | 29-MAR-04:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 30257.16 | 2639959.14 | 19-APR-04:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 3776.47 | 2083244.94 | 01-MAY-05:01 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 67.26 | 34709.11 | 07-JUN-05:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.14 | 1457.26 | 04-JUL-17:42 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 16.27 | 7258.58 | 08-AUG-05:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1597.40 | 232138.10 | 30-SEP-05:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11752.14 | 2206892.16 | 31-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 77412.53 | 2986541.48 | 24-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 136734.95 | 2593581.71 | 27-DEC-05:11 |
Annual Sum or Average | 0.00 | 69403.49 | ||||
Minimum of Months | 0.00 | 0.00 | 0.14 | 1457.26 | ||
Maximum of Months | 0.00 | 0.00 | 261855.55 | 3340522.95 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 28235.50 | 889262.91 | 10-JAN-22:01 | 225137.52 | 968258.27 | 22-JAN-16:50 |
February | 87972.38 | 1011582.90 | 27-FEB-17:02 | 138443.75 | 860028.84 | 26-FEB-07:22 |
March | 198412.08 | 1238621.11 | 27-MAR-16:00 | 13197.90 | 843798.47 | 01-MAR-00:01 |
April | 325307.16 | 2724153.04 | 07-APR-14:43 | 9479.97 | 650097.15 | 15-APR-06:14 |
May | 405988.42 | 2565093.71 | 31-MAY-12:05 | 142643.53 | 968196.04 | 07-MAY-15:00 |
June | 908138.22 | 4412884.61 | 27-JUN-05:02 | 22504.05 | 826595.94 | 04-JUN-05:42 |
July | 1237602.09 | 4360693.19 | 20-JUL-05:03 | 1629.67 | 415484.53 | 05-JUL-04:44 |
August | 1265950.85 | 3748560.03 | 07-AUG-04:14 | 1429.07 | 450958.01 | 29-AUG-04:48 |
September | 599438.35 | 4340719.17 | 07-SEP-05:03 | 99868.58 | 968194.81 | 17-SEP-07:40 |
October | 476423.22 | 2884194.24 | 24-OCT-10:14 | 72546.17 | 912074.95 | 23-OCT-01:18 |
November | 218781.83 | 1440895.17 | 10-NOV-06:03 | 18489.70 | 717832.25 | 28-NOV-06:45 |
December | 132354.36 | 1050745.17 | 08-DEC-15:52 | 23474.12 | 828761.65 | 27-DEC-12:23 |
Annual Sum or Average | 493444.26 | 63749.29 | ||||
Minimum of Months | 28235.50 | 889262.91 | 1429.07 | 415484.53 | ||
Maximum of Months | 1265950.85 | 4412884.61 | 225137.52 | 968258.27 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 37236.02 | 761442.00 | 24-JAN-06:02 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 114354.03 | 1070331.58 | 17-FEB-13:55 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 309252.30 | 2485544.89 | 03-MAR-06:01 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 436401.77 | 3206217.43 | 11-APR-05:01 | 0.00 | 0.00 | 01-APR-00:10 |
May | 445329.72 | 3794262.69 | 19-MAY-05:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 930502.03 | 5381907.35 | 19-JUN-04:11 | 0.00 | 0.00 | 01-JUN-00:01 |
July | 1274085.97 | 5286598.82 | 24-JUL-04:13 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1303448.44 | 5049746.59 | 17-AUG-05:04 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 626279.78 | 5893626.14 | 14-SEP-04:11 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 520671.06 | 4247499.28 | 06-OCT-05:01 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 329005.78 | 3186005.43 | 03-NOV-05:02 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 246647.68 | 1163240.87 | 17-DEC-13:52 | 0.00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 550970.96 | 0.00 | ||||
Minimum of Months | 37236.02 | 761442.00 | 0.00 | 0.00 | ||
Maximum of Months | 1303448.44 | 5893626.14 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 14762.12 | 52818.51 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 14998.81 | 52891.24 | 09-FEB-12:52 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 15584.59 | 52483.55 | 01-MAR-12:41 |
April | 0.00 | 0.00 | 01-APR-00:10 | 13860.34 | 50267.45 | 03-APR-11:32 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 13352.86 | 47350.63 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12704.43 | 43855.34 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11079.10 | 40948.28 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 11972.37 | 39990.95 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 11565.51 | 41873.63 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12295.95 | 45157.19 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 13427.22 | 48542.82 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 13803.67 | 51250.62 | 29-DEC-12:33 |
Annual Sum or Average | 0.00 | 13274.14 | ||||
Minimum of Months | 0.00 | 0.00 | 11079.10 | 39990.95 | ||
Maximum of Months | 0.00 | 0.00 | 15584.59 | 52891.24 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 25201.71 | 640922.62 | 26-JAN-22:15 | 6433.41 | 203633.89 | 10-JAN-03:10 |
February | 56684.38 | 978026.22 | 24-FEB-13:55 | 1007.76 | 118900.31 | 28-FEB-21:11 |
March | 185788.27 | 1438754.72 | 27-MAR-16:00 | 4934.66 | 145903.33 | 01-MAR-23:51 |
April | 372155.01 | 3560125.66 | 07-APR-15:10 | 2788.62 | 152354.33 | 04-APR-02:21 |
May | 514310.66 | 4789128.59 | 31-MAY-12:05 | 513.94 | 108355.75 | 14-MAY-04:10 |
June | 1628509.68 | 7893282.18 | 15-JUN-12:10 | 0.00 | 0.00 | 01-JUN-00:01 |
July | 3055183.22 | 8917630.58 | 20-JUL-14:40 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 2823779.87 | 9618796.27 | 03-AUG-14:05 | 95.60 | 63809.14 | 26-AUG-03:00 |
September | 967199.14 | 6899738.78 | 07-SEP-14:05 | 230.34 | 77997.31 | 24-SEP-17:10 |
October | 616453.19 | 4150909.89 | 24-OCT-10:14 | 0.69 | 9231.29 | 09-OCT-04:45 |
November | 225784.96 | 1453901.13 | 03-NOV-13:56 | 4210.02 | 135115.69 | 20-NOV-21:51 |
December | 90208.50 | 1133525.65 | 20-DEC-13:48 | 8367.74 | 192219.96 | 11-DEC-19:10 |
Annual Sum or Average | 887767.98 | 2399.49 | ||||
Minimum of Months | 25201.71 | 640922.62 | 0.00 | 0.00 | ||
Maximum of Months | 3055183.22 | 9618796.27 | 8367.74 | 203633.89 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.759658E+10 | 0.49 | 21432.23 | 25-JAN-06:01 | 1.62 |
February | 0.717413E+10 | 0.50 | 20091.28 | 17-FEB-06:01 | 1.59 |
March | 0.102772E+11 | 0.57 | 20091.28 | 11-MAR-06:01 | 1.59 |
April | 0.113218E+11 | 0.59 | 20091.28 | 21-APR-05:01 | 1.58 |
May | 0.125350E+11 | 0.63 | 19327.88 | 30-MAY-14:00 | 1.54 |
June | 0.157649E+11 | 0.72 | 26877.29 | 19-JUN-04:11 | 1.77 |
July | 0.183877E+11 | 0.80 | 26877.29 | 08-JUL-05:02 | 1.77 |
August | 0.216258E+11 | 0.88 | 26877.29 | 05-AUG-05:02 | 1.77 |
September | 0.138496E+11 | 0.65 | 26877.29 | 02-SEP-04:11 | 1.78 |
October | 0.128679E+11 | 0.61 | 19380.41 | 06-OCT-04:11 | 1.54 |
November | 0.958565E+10 | 0.53 | 19207.35 | 06-NOV-06:01 | 1.55 |
December | 0.897067E+10 | 0.51 | 20091.28 | 09-DEC-06:01 | 1.58 |
Annual Sum or Average | 0.149957E+12 | 0.62 | |||
Minimum of Months | 0.717413E+10 | 0.49 | 19207.35 | 1.54 | |
Maximum of Months | 0.216258E+11 | 0.88 | 26877.29 | 1.78 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.839147E+11 | 0.59 | 109969.22 | 02-JAN-06:03 | 1.26 |
February | 0.750760E+11 | 0.58 | 109969.22 | 06-FEB-05:01 | 1.26 |
March | 0.856325E+11 | 0.55 | 220094.54 | 03-MAR-06:01 | 1.68 |
April | 0.892186E+11 | 0.54 | 220094.54 | 05-APR-05:01 | 1.68 |
May | 0.110520E+12 | 0.60 | 207268.93 | 01-MAY-05:01 | 1.63 |
June | 0.136163E+12 | 0.67 | 253939.56 | 19-JUN-05:03 | 1.77 |
July | 0.148364E+12 | 0.68 | 253939.56 | 07-JUL-05:02 | 1.77 |
August | 0.168553E+12 | 0.73 | 253939.56 | 03-AUG-03:01 | 1.77 |
September | 0.118553E+12 | 0.62 | 229278.67 | 02-SEP-04:11 | 1.70 |
October | 0.105392E+12 | 0.57 | 206600.35 | 31-OCT-05:01 | 1.64 |
November | 0.760789E+11 | 0.51 | 220094.54 | 02-NOV-05:01 | 1.69 |
December | 0.747768E+11 | 0.52 | 93087.92 | 21-DEC-13:48 | 1.17 |
Annual Sum or Average | 0.127224E+13 | 0.60 | |||
Minimum of Months | 0.747768E+11 | 0.51 | 93087.92 | 1.17 | |
Maximum of Months | 0.168553E+12 | 0.73 | 253939.56 | 1.77 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.101569E+11 | 0.62 | 11398.41 | 02-JAN-04:01 | 1.14 |
February | 0.902410E+10 | 0.61 | 11398.41 | 01-FEB-05:11 | 1.13 |
March | 0.877594E+10 | 0.52 | 11398.41 | 01-MAR-06:01 | 1.13 |
April | 0.842118E+10 | 0.48 | 15820.58 | 07-APR-15:20 | 1.28 |
May | 0.102799E+11 | 0.52 | 19739.63 | 30-MAY-14:00 | 1.41 |
June | 0.132099E+11 | 0.58 | 22346.29 | 19-JUN-14:00 | 1.49 |
July | 0.148564E+11 | 0.60 | 33495.65 | 10-JUL-03:01 | 1.76 |
August | 0.166159E+11 | 0.64 | 32116.54 | 05-AUG-05:02 | 1.73 |
September | 0.110305E+11 | 0.53 | 21152.94 | 01-SEP-14:20 | 1.45 |
October | 0.924199E+10 | 0.48 | 17144.32 | 06-OCT-05:01 | 1.33 |
November | 0.814285E+10 | 0.51 | 11398.41 | 01-NOV-05:01 | 1.12 |
December | 0.929445E+10 | 0.57 | 11398.41 | 01-DEC-06:01 | 1.13 |
Annual Sum or Average | 0.129050E+12 | 0.55 | |||
Minimum of Months | 0.814285E+10 | 0.48 | 11398.41 | 1.12 | |
Maximum of Months | 0.166159E+11 | 0.64 | 33495.65 | 1.76 |
Report: FanReportMonthly
For: CAV_BAS SZVAV FAN
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.395826E+10 | 0.44 | 15391.92 | 04-JAN-06:03 | 1.80 |
February | 0.290212E+10 | 0.42 | 15391.92 | 01-FEB-06:01 | 1.81 |
March | 0.455358E+10 | 0.49 | 15391.92 | 01-MAR-06:01 | 1.80 |
April | 0.512931E+10 | 0.51 | 15391.92 | 01-APR-04:11 | 1.79 |
May | 0.471084E+10 | 0.50 | 15391.92 | 01-MAY-04:11 | 1.79 |
June | 0.553186E+10 | 0.56 | 15391.92 | 01-JUN-04:11 | 1.79 |
July | 0.609088E+10 | 0.55 | 15391.92 | 01-JUL-04:11 | 1.78 |
August | 0.722048E+10 | 0.63 | 15391.92 | 01-AUG-03:01 | 1.79 |
September | 0.654714E+10 | 0.59 | 15391.92 | 01-SEP-04:11 | 1.78 |
October | 0.670184E+10 | 0.58 | 15391.92 | 01-OCT-23:54 | 1.79 |
November | 0.543598E+10 | 0.53 | 15391.92 | 01-NOV-04:11 | 1.79 |
December | 0.411210E+10 | 0.46 | 15391.92 | 01-DEC-05:11 | 1.80 |
Annual Sum or Average | 0.628944E+11 | 0.52 | |||
Minimum of Months | 0.290212E+10 | 0.42 | 15391.92 | 1.78 | |
Maximum of Months | 0.722048E+10 | 0.63 | 15391.92 | 1.81 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SYS11 FAN
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.261881E+11 | 0.51 | 9777.51 | 01-JAN-00:01 | 0.51 |
February | 0.421429E+11 | 0.62 | 32565.10 | 01-FEB-00:03 | 0.85 |
March | 0.622293E+11 | 0.71 | 32565.10 | 01-MAR-00:02 | 0.85 |
April | 0.833120E+11 | 0.84 | 32565.10 | 01-APR-00:10 | 0.85 |
May | 0.262168E+11 | 0.51 | 32565.10 | 31-MAY-23:02 | 0.84 |
June | 0.320525E+11 | 0.54 | 32565.10 | 01-JUN-00:01 | 0.84 |
July | 0.419721E+11 | 0.61 | 32565.10 | 01-JUL-22:10 | 0.84 |
August | 0.727112E+11 | 0.78 | 32565.10 | 01-AUG-03:03 | 0.84 |
September | 0.253433E+11 | 0.51 | 9777.51 | 01-SEP-00:10 | 0.51 |
October | 0.451686E+11 | 0.61 | 32565.10 | 01-OCT-03:23 | 0.85 |
November | 0.595747E+11 | 0.71 | 32565.10 | 01-NOV-00:05 | 0.85 |
December | 0.869742E+11 | 0.85 | 32565.10 | 01-DEC-00:02 | 0.85 |
Annual Sum or Average | 0.603886E+12 | 0.65 | |||
Minimum of Months | 0.253433E+11 | 0.51 | 9777.51 | 0.51 | |
Maximum of Months | 0.869742E+11 | 0.85 | 32565.10 | 0.85 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.338227E+10 | 1.41 | 1262.79 | 01-JAN-05:13 | 1.42 |
February | 0.305495E+10 | 1.41 | 1262.79 | 01-FEB-08:26 | 1.41 |
March | 0.338227E+10 | 1.41 | 1262.79 | 01-MAR-00:47 | 1.41 |
April | 0.327316E+10 | 1.41 | 1262.79 | 01-APR-02:19 | 1.41 |
May | 0.338227E+10 | 1.40 | 1262.79 | 01-MAY-05:13 | 1.40 |
June | 0.327316E+10 | 1.40 | 1262.79 | 01-JUN-00:23 | 1.40 |
July | 0.338227E+10 | 1.40 | 1262.79 | 01-JUL-01:40 | 1.40 |
August | 0.338227E+10 | 1.40 | 1262.79 | 01-AUG-00:03 | 1.40 |
September | 0.327316E+10 | 1.40 | 1262.79 | 01-SEP-00:14 | 1.40 |
October | 0.338227E+10 | 1.40 | 1262.79 | 01-OCT-03:33 | 1.40 |
November | 0.327316E+10 | 1.41 | 1262.79 | 01-NOV-01:00 | 1.40 |
December | 0.338227E+10 | 1.41 | 1262.79 | 01-DEC-00:09 | 1.41 |
Annual Sum or Average | 0.398235E+11 | 1.41 | |||
Minimum of Months | 0.305495E+10 | 1.40 | 1262.79 | 1.40 | |
Maximum of Months | 0.338227E+10 | 1.41 | 1262.79 | 1.42 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.324465E+11 | 1.41 | 12114.14 | 12-JAN-15:35 | 1.41 |
February | 0.293065E+11 | 1.41 | 12114.14 | 01-FEB-04:20 | 1.42 |
March | 0.324465E+11 | 1.41 | 12114.14 | 03-MAR-16:34 | 1.41 |
April | 0.313999E+11 | 1.41 | 12114.14 | 02-APR-01:20 | 1.41 |
May | 0.324465E+11 | 1.40 | 12114.14 | 01-MAY-13:20 | 1.41 |
June | 0.313999E+11 | 1.40 | 12114.14 | 01-JUN-00:02 | 1.40 |
July | 0.324465E+11 | 1.40 | 12114.14 | 06-JUL-11:10 | 1.40 |
August | 0.324465E+11 | 1.40 | 12114.14 | 01-AUG-06:40 | 1.40 |
September | 0.313999E+11 | 1.40 | 12114.14 | 02-SEP-17:37 | 1.40 |
October | 0.324465E+11 | 1.40 | 12114.14 | 08-OCT-03:38 | 1.41 |
November | 0.313999E+11 | 1.41 | 12114.14 | 02-NOV-13:31 | 1.41 |
December | 0.324465E+11 | 1.41 | 12114.14 | 02-DEC-20:30 | 1.42 |
Annual Sum or Average | 0.382032E+12 | 1.41 | |||
Minimum of Months | 0.293065E+11 | 1.40 | 12114.14 | 1.40 | |
Maximum of Months | 0.324465E+11 | 1.41 | 12114.14 | 1.42 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.335159E+10 | 1.41 | 1251.34 | 02-JAN-12:13 | 1.42 |
February | 0.302724E+10 | 1.41 | 1251.34 | 01-FEB-00:07 | 1.42 |
March | 0.335159E+10 | 1.41 | 1251.34 | 01-MAR-11:04 | 1.41 |
April | 0.324348E+10 | 1.41 | 1251.34 | 01-APR-00:41 | 1.41 |
May | 0.335159E+10 | 1.40 | 1251.34 | 01-MAY-01:00 | 1.40 |
June | 0.324348E+10 | 1.40 | 1251.34 | 01-JUN-00:08 | 1.40 |
July | 0.335159E+10 | 1.40 | 1251.34 | 01-JUL-01:40 | 1.40 |
August | 0.335159E+10 | 1.40 | 1251.34 | 01-AUG-01:40 | 1.40 |
September | 0.324348E+10 | 1.40 | 1251.34 | 01-SEP-00:54 | 1.40 |
October | 0.335159E+10 | 1.40 | 1251.34 | 01-OCT-05:02 | 1.40 |
November | 0.324348E+10 | 1.41 | 1251.34 | 01-NOV-00:10 | 1.40 |
December | 0.335159E+10 | 1.41 | 1251.34 | 01-DEC-01:03 | 1.41 |
Annual Sum or Average | 0.394623E+11 | 1.41 | |||
Minimum of Months | 0.302724E+10 | 1.40 | 1251.34 | 1.40 | |
Maximum of Months | 0.335159E+10 | 1.41 | 1251.34 | 1.42 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.763232E+09 | 0.686909E+09 | 6611.75 | 02-JAN-04:01 | 5950.58 | 5950.58 | 50.72 | 25.38 |
February | 0.610088E+09 | 0.549080E+09 | 5681.91 | 06-FEB-06:01 | 5113.72 | 5113.72 | 56.79 | 23.38 |
March | 0.210924E+09 | 0.189831E+09 | 3603.25 | 20-MAR-05:01 | 3242.93 | 3242.93 | 44.32 | 17.97 |
April | 80399053.61 | 72359148.25 | 3269.00 | 03-APR-05:01 | 2942.10 | 2942.10 | 45.14 | 16.84 |
May | 9999786.16 | 8999807.55 | 2613.50 | 01-MAY-05:01 | 2352.15 | 2352.15 | 34.71 | 14.41 |
June | 161852.99 | 145667.69 | 32.09 | 07-JUN-05:10 | 28.88 | 28.88 | 21.03 | 0.19 |
July | 339.76 | 305.78 | 1.34 | 04-JUL-17:42 | 1.20 | 1.20 | 20.61 | 0.01 |
August | 40027.85 | 36025.07 | 6.67 | 08-AUG-05:10 | 6.00 | 6.00 | 20.64 | 0.04 |
September | 3834359.63 | 3450923.66 | 217.03 | 30-SEP-05:02 | 195.33 | 195.33 | 22.26 | 1.28 |
October | 31867112.71 | 28680401.44 | 3166.08 | 28-OCT-05:01 | 2849.47 | 2849.47 | 41.19 | 16.50 |
November | 0.209224E+09 | 0.188301E+09 | 5237.74 | 24-NOV-06:01 | 4713.96 | 4713.96 | 48.13 | 22.45 |
December | 0.372545E+09 | 0.335290E+09 | 4697.19 | 26-DEC-06:01 | 4227.47 | 4227.47 | 46.84 | 21.12 |
Annual Sum or Average | 0.229231E+10 | 0.206308E+10 | ||||||
Minimum of Months | 339.76 | 305.78 | 1.34 | 1.20 | 1.20 | 20.61 | 0.01 | |
Maximum of Months | 0.763232E+09 | 0.686909E+09 | 6611.75 | 5950.58 | 5950.58 | 56.79 | 25.38 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.356403E+09 | 0.320763E+09 | 3192.90 | 24-JAN-06:02 | 2873.61 | 2873.61 | 9.67 | 28.59 |
February | 0.165795E+10 | 0.149216E+10 | 4085.28 | 20-FEB-13:01 | 3676.75 | 3676.75 | 9.37 | 36.35 |
March | 0.353465E+10 | 0.318119E+10 | 16785.48 | 03-MAR-06:01 | 15106.93 | 15106.93 | 10.11 | 103.61 |
April | 0.455799E+10 | 0.410219E+10 | 23343.98 | 28-APR-05:02 | 21009.58 | 21009.58 | 10.21 | 122.69 |
May | 0.364500E+10 | 0.328050E+10 | 20961.08 | 30-MAY-05:02 | 18864.97 | 18864.97 | 9.87 | 116.34 |
June | 0.692468E+10 | 0.623221E+10 | 27170.30 | 12-JUN-04:11 | 24453.27 | 24453.27 | 8.43 | 131.86 |
July | 0.984970E+10 | 0.886473E+10 | 27504.43 | 07-JUL-05:02 | 24753.98 | 24753.98 | 10.49 | 132.61 |
August | 0.109103E+11 | 0.981927E+10 | 27504.43 | 01-AUG-05:02 | 24753.98 | 24753.98 | 10.07 | 132.63 |
September | 0.486716E+10 | 0.438045E+10 | 22044.80 | 01-SEP-04:11 | 19840.32 | 19840.32 | 11.13 | 119.28 |
October | 0.490073E+10 | 0.441065E+10 | 24081.53 | 06-OCT-05:01 | 21673.38 | 21673.38 | 9.17 | 124.55 |
November | 0.364872E+10 | 0.328385E+10 | 22992.84 | 04-NOV-05:02 | 20693.55 | 20693.55 | 10.49 | 121.78 |
December | 0.304576E+10 | 0.274118E+10 | 4646.42 | 17-DEC-11:52 | 4181.78 | 4181.78 | 9.52 | 41.00 |
Annual Sum or Average | 0.578991E+11 | 0.521092E+11 | ||||||
Minimum of Months | 0.356403E+09 | 0.320763E+09 | 3192.90 | 2873.61 | 2873.61 | 8.43 | 28.59 | |
Maximum of Months | 0.109103E+11 | 0.981927E+10 | 27504.43 | 24753.98 | 24753.98 | 11.13 | 132.63 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.103815E+11 | 0.934335E+10 | 12615.08 | 01-JAN-00:01 | 11353.57 | 11353.57 | 6.73 | 66.31 |
February | 0.119400E+11 | 0.107460E+11 | 12615.08 | 01-FEB-00:03 | 11353.57 | 11353.57 | 7.30 | 66.31 |
March | 0.301937E+11 | 0.271744E+11 | 12615.08 | 01-MAR-00:04 | 11353.57 | 11353.57 | 7.51 | 66.31 |
April | 0.287751E+11 | 0.258976E+11 | 12615.08 | 01-APR-00:10 | 11353.57 | 11353.57 | 10.10 | 66.31 |
May | 0.215201E+11 | 0.193681E+11 | 12615.08 | 01-MAY-00:10 | 11353.57 | 11353.57 | 7.97 | 66.31 |
June | 0.283709E+11 | 0.255338E+11 | 12615.08 | 01-JUN-00:03 | 11353.57 | 11353.57 | 8.61 | 66.31 |
July | 0.332921E+11 | 0.299629E+11 | 12615.08 | 01-JUL-00:10 | 11353.57 | 11353.57 | 10.27 | 66.31 |
August | 0.333847E+11 | 0.300462E+11 | 12615.08 | 01-AUG-00:03 | 11353.57 | 11353.57 | 10.10 | 66.31 |
September | 0.220526E+11 | 0.198474E+11 | 12615.08 | 01-SEP-00:10 | 11353.57 | 11353.57 | 10.24 | 66.31 |
October | 0.222499E+11 | 0.200249E+11 | 12615.08 | 01-OCT-03:21 | 11353.57 | 11353.57 | 6.80 | 66.31 |
November | 0.282537E+11 | 0.254283E+11 | 12615.08 | 01-NOV-00:22 | 11353.57 | 11353.57 | 8.94 | 66.31 |
December | 0.271945E+11 | 0.244750E+11 | 12615.08 | 01-DEC-00:01 | 11353.57 | 11353.57 | 10.26 | 66.31 |
Annual Sum or Average | 0.297609E+12 | 0.267848E+12 | ||||||
Minimum of Months | 0.103815E+11 | 0.934335E+10 | 12615.08 | 11353.57 | 11353.57 | 6.73 | 66.31 | |
Maximum of Months | 0.333847E+11 | 0.300462E+11 | 12615.08 | 11353.57 | 11353.57 | 10.27 | 66.31 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 6.73 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 6.81 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 7.17 | 0.00 |
April | 0.129935E+09 | 0.116942E+09 | 12615.08 | 07-APR-12:05 | 11353.57 | 11353.57 | 10.43 | 66.31 |
May | 0.442789E+09 | 0.398510E+09 | 12615.08 | 30-MAY-10:30 | 11353.57 | 11353.57 | 13.68 | 33.16 |
June | 0.498899E+10 | 0.449009E+10 | 12615.08 | 01-JUN-10:20 | 11353.57 | 11353.57 | 13.29 | 33.16 |
July | 0.105694E+11 | 0.951249E+10 | 12615.08 | 01-JUL-05:04 | 11353.57 | 11353.57 | 14.08 | 33.16 |
August | 0.117586E+11 | 0.105828E+11 | 12615.08 | 01-AUG-05:04 | 11353.57 | 11353.57 | 14.01 | 33.16 |
September | 0.219129E+10 | 0.197216E+10 | 12615.08 | 01-SEP-04:13 | 11353.57 | 11353.57 | 14.87 | 33.16 |
October | 0.932002E+09 | 0.838802E+09 | 12615.08 | 03-OCT-10:40 | 11353.57 | 11353.57 | 13.47 | 33.16 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 7.79 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 10.26 | 0.00 |
Annual Sum or Average | 0.310131E+11 | 0.279118E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.73 | 0.00 | |
Maximum of Months | 0.117586E+11 | 0.105828E+11 | 12615.08 | 11353.57 | 11353.57 | 14.87 | 66.31 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:02 | 16.86 | 16.86 | 57.25 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 57.16 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 57.18 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:01 | 16.86 | 16.86 | 57.23 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:01 | 16.86 | 16.86 | 57.61 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:01 | 16.86 | 16.86 | 57.65 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 57.64 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 57.73 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.66 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:01 | 16.86 | 16.86 | 57.75 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 57.58 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 57.30 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 57.16 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.75 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.264000E+11 | 0.237600E+11 | 32493.66 | 26-JAN-22:15 | 29244.29 | 29244.29 | 22.74 | 93.42 |
February | 0.306671E+11 | 0.276004E+11 | 32513.85 | 24-FEB-13:55 | 29262.46 | 29262.46 | 23.60 | 93.42 |
March | 0.774420E+11 | 0.696978E+11 | 32541.47 | 27-MAR-16:00 | 29287.32 | 29287.32 | 24.79 | 93.42 |
April | 0.743028E+11 | 0.668726E+11 | 65129.27 | 07-APR-15:10 | 58616.34 | 58616.34 | 25.66 | 186.84 |
May | 0.563053E+11 | 0.506748E+11 | 65215.25 | 31-MAY-12:05 | 58693.72 | 58693.72 | 27.23 | 186.84 |
June | 0.838689E+11 | 0.754820E+11 | 65336.47 | 15-JUN-10:40 | 58802.82 | 58802.82 | 29.45 | 186.84 |
July | 0.110944E+12 | 0.998498E+11 | 65336.47 | 05-JUL-16:00 | 58802.82 | 58802.82 | 29.57 | 186.84 |
August | 0.114321E+12 | 0.102889E+12 | 65336.47 | 01-AUG-09:40 | 58802.82 | 58802.82 | 29.60 | 186.84 |
September | 0.616330E+11 | 0.554697E+11 | 65336.47 | 07-SEP-13:00 | 58802.82 | 58802.82 | 29.53 | 186.84 |
October | 0.591049E+11 | 0.531944E+11 | 65170.57 | 24-OCT-10:14 | 58653.52 | 58653.52 | 26.42 | 186.84 |
November | 0.725033E+11 | 0.652530E+11 | 32542.38 | 03-NOV-13:56 | 29288.14 | 29288.14 | 24.82 | 93.42 |
December | 0.693140E+11 | 0.623826E+11 | 32523.17 | 20-DEC-13:48 | 29270.85 | 29270.85 | 24.00 | 93.42 |
Annual Sum or Average | 0.836807E+12 | 0.753126E+12 | ||||||
Minimum of Months | 0.264000E+11 | 0.237600E+11 | 32493.66 | 29244.29 | 29244.29 | 22.74 | 93.42 | |
Maximum of Months | 0.114321E+12 | 0.102889E+12 | 65336.47 | 58802.82 | 58802.82 | 29.60 | 186.84 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 48.51 | 82.20 | 261855.55 | 3340522.95 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 32.48 | 32.48 | 241230.81 | 2815692.34 | 10-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 28.35 | 28.35 | 79341.33 | 2804537.30 | 29-MAR-04:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.12 | 25.12 | 30257.16 | 2639959.14 | 19-APR-04:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.49 | 20.49 | 3776.47 | 2083244.94 | 01-MAY-05:01 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 21.44 | 21.44 | 67.26 | 34709.11 | 07-JUN-05:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.60 | 20.60 | 0.14 | 1457.26 | 04-JUL-17:42 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.64 | 20.64 | 16.27 | 7258.58 | 08-AUG-05:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 20.53 | 20.53 | 1597.40 | 232138.10 | 30-SEP-05:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21.79 | 21.79 | 11752.14 | 2206892.16 | 31-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 21.96 | 21.96 | 77412.53 | 2986541.48 | 24-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 27.78 | 27.78 | 136734.95 | 2593581.71 | 27-DEC-05:11 |
Annual Sum or Average | 0.00 | 69403.49 | ||||||
Minimum of Months | 0.00 | 0.00 | 20.49 | 20.49 | 0.14 | 1457.26 | ||
Maximum of Months | 0.00 | 0.00 | 48.51 | 82.20 | 261855.55 | 3340522.95 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 28235.50 | 889262.91 | 10-JAN-22:01 | 9.90 | 6.70 | 225137.52 | 968258.27 | 22-JAN-16:50 |
February | 87972.38 | 1011582.90 | 27-FEB-17:02 | 10.34 | 6.70 | 138443.75 | 860028.84 | 26-FEB-07:22 |
March | 198412.08 | 1238621.11 | 27-MAR-16:00 | 11.16 | 6.70 | 13197.90 | 843798.47 | 01-MAR-00:01 |
April | 325307.16 | 2724153.04 | 07-APR-14:43 | 11.60 | 6.70 | 9479.97 | 650097.15 | 15-APR-06:14 |
May | 405988.42 | 2565093.71 | 31-MAY-12:05 | 11.32 | 6.70 | 142643.53 | 968196.04 | 07-MAY-15:00 |
June | 908138.22 | 4412884.61 | 27-JUN-05:02 | 14.65 | 7.91 | 22504.05 | 826595.94 | 04-JUN-05:42 |
July | 1237602.09 | 4360693.19 | 20-JUL-05:03 | 14.56 | 7.81 | 1629.67 | 415484.53 | 05-JUL-04:44 |
August | 1265950.85 | 3748560.03 | 07-AUG-04:14 | 13.45 | 6.71 | 1429.07 | 450958.01 | 29-AUG-04:48 |
September | 599438.35 | 4340719.17 | 07-SEP-05:03 | 14.52 | 7.78 | 99868.58 | 968194.81 | 17-SEP-07:40 |
October | 476423.22 | 2884194.24 | 24-OCT-10:14 | 11.89 | 6.70 | 72546.17 | 912074.95 | 23-OCT-01:18 |
November | 218781.83 | 1440895.17 | 10-NOV-06:03 | 11.89 | 6.70 | 18489.70 | 717832.25 | 28-NOV-06:45 |
December | 132354.36 | 1050745.17 | 08-DEC-15:52 | 10.76 | 6.98 | 23474.12 | 828761.65 | 27-DEC-12:23 |
Annual Sum or Average | 493444.26 | 63749.29 | ||||||
Minimum of Months | 28235.50 | 889262.91 | 9.90 | 6.70 | 1429.07 | 415484.53 | ||
Maximum of Months | 1265950.85 | 4412884.61 | 14.65 | 7.91 | 225137.52 | 968258.27 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 37236.02 | 761442.00 | 24-JAN-06:02 | 13.06 | 9.65 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 114354.03 | 1070331.58 | 17-FEB-13:55 | 14.78 | 8.25 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 309252.30 | 2485544.89 | 03-MAR-06:01 | 12.43 | 10.72 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 436401.77 | 3206217.43 | 11-APR-05:01 | 13.01 | 11.25 | 0.00 | 0.00 | 01-APR-00:10 |
May | 445329.72 | 3794262.69 | 19-MAY-05:03 | 15.17 | 11.53 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 930502.03 | 5381907.35 | 19-JUN-04:11 | 17.15 | 12.58 | 0.00 | 0.00 | 01-JUN-00:01 |
July | 1274085.97 | 5286598.82 | 24-JUL-04:13 | 16.23 | 11.88 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1303448.44 | 5049746.59 | 17-AUG-05:04 | 15.80 | 11.42 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 626279.78 | 5893626.14 | 14-SEP-04:11 | 18.80 | 13.30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 520671.06 | 4247499.28 | 06-OCT-05:01 | 14.85 | 11.64 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 329005.78 | 3186005.43 | 03-NOV-05:02 | 12.95 | 10.97 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 246647.68 | 1163240.87 | 17-DEC-13:52 | 13.52 | 9.53 | 0.00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 550970.96 | 0.00 | ||||||
Minimum of Months | 37236.02 | 761442.00 | 12.43 | 8.25 | 0.00 | 0.00 | ||
Maximum of Months | 1303448.44 | 5893626.14 | 18.80 | 13.30 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 58.09 | 58.09 | 14762.12 | 52818.51 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 57.53 | 57.53 | 14998.81 | 52891.24 | 09-FEB-12:52 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 57.55 | 57.55 | 15584.59 | 52483.55 | 01-MAR-12:41 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.64 | 57.64 | 13860.34 | 50267.45 | 03-APR-11:32 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.24 | 58.24 | 13352.86 | 47350.63 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 57.96 | 57.96 | 12704.43 | 43855.34 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.09 | 58.09 | 11079.10 | 40948.28 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 58.16 | 58.16 | 11972.37 | 39990.95 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.15 | 58.15 | 11565.51 | 41873.63 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 58.05 | 58.05 | 12295.95 | 45157.19 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 57.90 | 57.90 | 13427.22 | 48542.82 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 57.74 | 57.74 | 13803.67 | 51250.62 | 29-DEC-12:33 |
Annual Sum or Average | 0.00 | 13274.14 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.53 | 57.53 | 11079.10 | 39990.95 | ||
Maximum of Months | 0.00 | 0.00 | 58.24 | 58.24 | 15584.59 | 52891.24 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 25201.71 | 640922.62 | 26-JAN-22:15 | 22.74 | 21.10 | 6433.41 | 203633.89 | 10-JAN-03:10 |
February | 56684.38 | 978026.22 | 24-FEB-13:55 | 23.60 | 21.10 | 1007.76 | 118900.31 | 28-FEB-21:11 |
March | 185788.27 | 1438754.72 | 27-MAR-16:00 | 24.79 | 21.10 | 4934.66 | 145903.33 | 01-MAR-23:51 |
April | 372155.01 | 3560125.66 | 07-APR-15:10 | 25.66 | 21.15 | 2788.62 | 152354.33 | 04-APR-02:21 |
May | 514310.66 | 4789128.59 | 31-MAY-12:05 | 27.23 | 23.61 | 513.94 | 108355.75 | 14-MAY-04:10 |
June | 1628509.68 | 7893282.18 | 15-JUN-12:10 | 31.21 | 27.49 | 0.00 | 0.00 | 01-JUN-00:01 |
July | 3055183.22 | 8917630.58 | 20-JUL-14:40 | 32.52 | 28.29 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 2823779.87 | 9618796.27 | 03-AUG-14:05 | 33.42 | 28.87 | 95.60 | 63809.14 | 26-AUG-03:00 |
September | 967199.14 | 6899738.78 | 07-SEP-14:05 | 29.93 | 26.32 | 230.34 | 77997.31 | 24-SEP-17:10 |
October | 616453.19 | 4150909.89 | 24-OCT-10:14 | 26.42 | 22.60 | 0.69 | 9231.29 | 09-OCT-04:45 |
November | 225784.96 | 1453901.13 | 03-NOV-13:56 | 24.82 | 21.10 | 4210.02 | 135115.69 | 20-NOV-21:51 |
December | 90208.50 | 1133525.65 | 20-DEC-13:48 | 24.00 | 21.10 | 8367.74 | 192219.96 | 11-DEC-19:10 |
Annual Sum or Average | 887767.98 | 2399.49 | ||||||
Minimum of Months | 25201.71 | 640922.62 | 22.74 | 21.10 | 0.00 | 0.00 | ||
Maximum of Months | 3055183.22 | 9618796.27 | 33.42 | 28.87 | 8367.74 | 203633.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.213004E+11 | 0.00 | 0.125085E+11 | 0.759658E+10 | 0.00 | 0.00 |
February | 0.190479E+11 | 0.00 | 0.104330E+11 | 0.717413E+10 | 0.00 | 0.00 |
March | 0.452355E+10 | 0.00 | 0.375796E+11 | 0.102772E+11 | 0.00 | 0.00 |
April | 0.107200E+10 | 0.00 | 0.633834E+11 | 0.113218E+11 | 0.00 | 0.00 |
May | 39566591.63 | 0.00 | 0.951743E+11 | 0.125350E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.159790E+12 | 0.157649E+11 | 0.00 | 0.00 |
July | 24249.65 | 0.00 | 0.223199E+12 | 0.183877E+11 | 0.00 | 0.00 |
August | 138684.07 | 0.00 | 0.228441E+12 | 0.216258E+11 | 0.00 | 0.00 |
September | 1633293.46 | 0.00 | 0.127909E+12 | 0.138496E+11 | 0.00 | 0.00 |
October | 0.256470E+09 | 0.00 | 0.944193E+11 | 0.128679E+11 | 0.00 | 0.00 |
November | 0.346273E+10 | 0.00 | 0.420371E+11 | 0.958565E+10 | 0.00 | 0.00 |
December | 0.689355E+10 | 0.00 | 0.231118E+11 | 0.897067E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.565980E+11 | 0.00 | 0.111799E+13 | 0.149957E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.104330E+11 | 0.717413E+10 | 0.00 | 0.00 |
Maximum of Months | 0.213004E+11 | 0.00 | 0.228441E+12 | 0.216258E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.579797E+12 | 0.00 | 0.386193E+11 | 0.839147E+11 | 0.00 | 0.00 |
February | 0.475406E+12 | 0.00 | 0.334374E+11 | 0.750760E+11 | 0.00 | 0.00 |
March | 0.168576E+12 | 0.00 | 0.205377E+12 | 0.856325E+11 | 0.00 | 0.00 |
April | 0.609762E+11 | 0.00 | 0.427718E+12 | 0.892186E+11 | 0.00 | 0.00 |
May | 0.637380E+10 | 0.00 | 0.812443E+12 | 0.110520E+12 | 0.00 | 0.00 |
June | 20554033.47 | 0.00 | 0.141539E+13 | 0.136163E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.185975E+13 | 0.148364E+12 | 0.00 | 0.00 |
August | 7663873.08 | 0.00 | 0.182709E+13 | 0.168553E+12 | 0.00 | 0.00 |
September | 0.245964E+10 | 0.00 | 0.111819E+13 | 0.118553E+12 | 0.00 | 0.00 |
October | 0.227759E+11 | 0.00 | 0.755363E+12 | 0.105392E+12 | 0.00 | 0.00 |
November | 0.155660E+12 | 0.00 | 0.231328E+12 | 0.760789E+11 | 0.00 | 0.00 |
December | 0.288784E+12 | 0.00 | 0.585426E+11 | 0.747768E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.176084E+13 | 0.00 | 0.878324E+13 | 0.127224E+13 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.334374E+11 | 0.747768E+11 | 0.00 | 0.00 |
Maximum of Months | 0.579797E+12 | 0.00 | 0.185975E+13 | 0.168553E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.104030E+12 | 0.00 | 0.471924E+10 | 0.101569E+11 | 0.00 | 0.00 |
February | 0.923459E+11 | 0.00 | 0.304080E+10 | 0.902410E+10 | 0.00 | 0.00 |
March | 0.404068E+11 | 0.00 | 0.197796E+11 | 0.877594E+10 | 0.00 | 0.00 |
April | 0.167224E+11 | 0.00 | 0.435138E+11 | 0.842118E+10 | 0.00 | 0.00 |
May | 0.372557E+10 | 0.00 | 0.889372E+11 | 0.102799E+11 | 0.00 | 0.00 |
June | 0.160636E+09 | 0.00 | 0.159022E+12 | 0.132099E+11 | 0.00 | 0.00 |
July | 63973.94 | 0.00 | 0.210151E+12 | 0.148564E+11 | 0.00 | 0.00 |
August | 36716578.20 | 0.00 | 0.204713E+12 | 0.166159E+11 | 0.00 | 0.00 |
September | 0.168102E+10 | 0.00 | 0.117439E+12 | 0.110305E+11 | 0.00 | 0.00 |
October | 0.854946E+10 | 0.00 | 0.709861E+11 | 0.924199E+10 | 0.00 | 0.00 |
November | 0.423223E+11 | 0.00 | 0.186540E+11 | 0.814285E+10 | 0.00 | 0.00 |
December | 0.720189E+11 | 0.00 | 0.371001E+10 | 0.929445E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.382000E+12 | 0.00 | 0.944666E+12 | 0.129050E+12 | 0.00 | 0.00 |
Minimum of Months | 63973.94 | 0.00 | 0.304080E+10 | 0.814285E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104030E+12 | 0.00 | 0.210151E+12 | 0.166159E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 11733177.55 | 0.00 | 0.739839E+10 | 0.395826E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.296783E+10 | 0.290212E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.155184E+11 | 0.455358E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.292202E+11 | 0.512931E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.480498E+11 | 0.471084E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.854508E+11 | 0.553186E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.109406E+12 | 0.609088E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.113168E+12 | 0.722048E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.805727E+11 | 0.654714E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.645474E+11 | 0.670184E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.314144E+11 | 0.543598E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.126399E+11 | 0.411210E+10 | 0.00 | 0.00 |
Annual Sum or Average | 11733177.55 | 0.00 | 0.600354E+12 | 0.628944E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.296783E+10 | 0.290212E+10 | 0.00 | 0.00 |
Maximum of Months | 11733177.55 | 0.00 | 0.113168E+12 | 0.722048E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 4224781.43 | 0.116812E+12 | 0.00 | 33.71 |
February | 0.00 | 0.00 | 0.150762E+12 | 0.158190E+12 | 0.00 | 43.17 |
March | 0.00 | 0.00 | 0.224280E+12 | 0.191758E+12 | 0.00 | 48.18 |
April | 0.00 | 0.00 | 0.246311E+12 | 0.178996E+12 | 0.00 | 35.59 |
May | 0.00 | 0.00 | 0.121009E+11 | 0.645904E+11 | 0.00 | 14.27 |
June | 0.00 | 0.00 | 0.405781E+12 | 0.411686E+11 | 0.00 | 3.39 |
July | 0.00 | 0.00 | 0.757573E+12 | 0.420711E+11 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.882423E+12 | 0.819572E+11 | 0.00 | 3.44 |
September | 0.00 | 0.00 | 0.425893E+11 | 0.380838E+11 | 0.00 | 4.74 |
October | 0.00 | 0.00 | 0.240233E+12 | 0.993157E+11 | 0.00 | 20.14 |
November | 0.00 | 0.00 | 0.216842E+12 | 0.172996E+12 | 0.00 | 42.19 |
December | 0.00 | 0.00 | 0.231698E+12 | 0.309614E+12 | 0.00 | 82.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.341060E+13 | 0.149555E+13 | 0.00 | 331.70 |
Minimum of Months | 0.00 | 0.00 | 4224781.43 | 0.380838E+11 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.882423E+12 | 0.309614E+12 | 0.00 | 82.82 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.470300E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.549007E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.751341E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.870934E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.555850E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.689252E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.854099E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.100542E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.557464E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.673040E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.729193E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.864511E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.857041E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.470300E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.100542E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.383299E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.458064E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.642958E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.739115E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.488650E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.606803E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.745694E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.869936E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.489453E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.583197E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.616614E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.712849E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.733663E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.383299E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.869936E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.375703E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.445029E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.672570E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.792457E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.512375E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.667277E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.832175E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.972507E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.519213E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.608965E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.637450E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.738222E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.777394E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.375703E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.972507E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.759658E+10 | 0.125085E+11 | 0.213004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.717413E+10 | 0.104330E+11 | 0.190479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102772E+11 | 0.375796E+11 | 0.452355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113218E+11 | 0.633834E+11 | 0.107200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125350E+11 | 0.951743E+11 | 39566591.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.157649E+11 | 0.159790E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.183877E+11 | 0.223199E+12 | 24249.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.216258E+11 | 0.228441E+12 | 138684.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138496E+11 | 0.127909E+12 | 1633293.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128679E+11 | 0.944193E+11 | 0.256470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.958565E+10 | 0.420371E+11 | 0.346273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.897067E+10 | 0.231118E+11 | 0.689355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149957E+12 | 0.111799E+13 | 0.565980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.717413E+10 | 0.104330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.216258E+11 | 0.228441E+12 | 0.213004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.839147E+11 | 0.386193E+11 | 0.579797E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.750760E+11 | 0.334374E+11 | 0.475406E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.856325E+11 | 0.205377E+12 | 0.168576E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.892186E+11 | 0.427718E+12 | 0.609762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110520E+12 | 0.812443E+12 | 0.637380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136163E+12 | 0.141539E+13 | 20554033.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148364E+12 | 0.185975E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168553E+12 | 0.182709E+13 | 7663873.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118553E+12 | 0.111819E+13 | 0.245964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105392E+12 | 0.755363E+12 | 0.227759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.760789E+11 | 0.231328E+12 | 0.155660E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.747768E+11 | 0.585426E+11 | 0.288784E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127224E+13 | 0.878324E+13 | 0.176084E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.747768E+11 | 0.334374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.168553E+12 | 0.185975E+13 | 0.579797E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.101569E+11 | 0.471924E+10 | 0.104030E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.902410E+10 | 0.304080E+10 | 0.923459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.877594E+10 | 0.197796E+11 | 0.404068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.842118E+10 | 0.435138E+11 | 0.167224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102799E+11 | 0.889372E+11 | 0.372557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132099E+11 | 0.159022E+12 | 0.160636E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148564E+11 | 0.210151E+12 | 63973.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166159E+11 | 0.204713E+12 | 36716578.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110305E+11 | 0.117439E+12 | 0.168102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.924199E+10 | 0.709861E+11 | 0.854946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.814285E+10 | 0.186540E+11 | 0.423223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.929445E+10 | 0.371001E+10 | 0.720189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129050E+12 | 0.944666E+12 | 0.382000E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.814285E+10 | 0.304080E+10 | 63973.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166159E+11 | 0.210151E+12 | 0.104030E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.395826E+10 | 0.739839E+10 | 11733177.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.290212E+10 | 0.296783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.455358E+10 | 0.155184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.512931E+10 | 0.292202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.471084E+10 | 0.480498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.553186E+10 | 0.854508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.609088E+10 | 0.109406E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.722048E+10 | 0.113168E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.654714E+10 | 0.805727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.670184E+10 | 0.645474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.543598E+10 | 0.314144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.411210E+10 | 0.126399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.628944E+11 | 0.600354E+12 | 11733177.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.290212E+10 | 0.296783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.722048E+10 | 0.113168E+12 | 11733177.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.261881E+11 | 4224781.43 | 0.00 | 0.00 | 0.00 | 0.902182E+11 | 0.00 | 0.00 |
February | 0.421429E+11 | 0.150762E+12 | 0.00 | 0.00 | 0.00 | 0.115527E+12 | 0.00 | 0.00 |
March | 0.622293E+11 | 0.224280E+12 | 0.00 | 0.00 | 0.00 | 0.128948E+12 | 0.00 | 0.00 |
April | 0.833120E+11 | 0.246311E+12 | 0.00 | 0.00 | 0.00 | 0.952553E+11 | 0.00 | 0.00 |
May | 0.262168E+11 | 0.121009E+11 | 0.00 | 0.00 | 0.00 | 0.382016E+11 | 0.00 | 0.00 |
June | 0.320525E+11 | 0.405781E+12 | 0.00 | 0.00 | 0.00 | 0.907520E+10 | 0.00 | 0.00 |
July | 0.419721E+11 | 0.757573E+12 | 0.00 | 0.00 | 0.00 | 98556624.89 | 0.00 | 0.00 |
August | 0.727112E+11 | 0.882423E+12 | 0.00 | 0.00 | 0.00 | 0.920456E+10 | 0.00 | 0.00 |
September | 0.253433E+11 | 0.425893E+11 | 0.00 | 0.00 | 0.00 | 0.126834E+11 | 0.00 | 0.00 |
October | 0.451686E+11 | 0.240233E+12 | 0.00 | 0.00 | 0.00 | 0.539045E+11 | 0.00 | 0.00 |
November | 0.595747E+11 | 0.216842E+12 | 0.00 | 0.00 | 0.00 | 0.112913E+12 | 0.00 | 0.00 |
December | 0.869742E+11 | 0.231698E+12 | 0.00 | 0.00 | 0.00 | 0.221642E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.603886E+12 | 0.341060E+13 | 0.00 | 0.00 | 0.00 | 0.887672E+12 | 0.00 | 0.00 |
Minimum of Months | 0.253433E+11 | 4224781.43 | 0.00 | 0.00 | 0.00 | 98556624.89 | 0.00 | 0.00 |
Maximum of Months | 0.869742E+11 | 0.882423E+12 | 0.00 | 0.00 | 0.00 | 0.221642E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.338227E+10 | 0.424548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.305495E+10 | 0.851076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.338227E+10 | 0.157985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.327316E+10 | 0.208726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.338227E+10 | 0.724125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.327316E+10 | 0.129746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.338227E+10 | 0.190973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.338227E+10 | 0.239776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.327316E+10 | 0.767160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.338227E+10 | 0.120814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.327316E+10 | 0.153780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.338227E+10 | 0.203499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.398235E+11 | 0.168199E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.305495E+10 | 0.424548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.338227E+10 | 0.239776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.324465E+11 | 0.216710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.293065E+11 | 0.656720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.324465E+11 | 0.139757E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.313999E+11 | 0.191318E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.324465E+11 | 0.631544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.313999E+11 | 0.121996E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.324465E+11 | 0.181900E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.324465E+11 | 0.228837E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.313999E+11 | 0.676051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.324465E+11 | 0.107631E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.313999E+11 | 0.132083E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.324465E+11 | 0.176352E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.382032E+12 | 0.149798E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.293065E+11 | 0.216710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.324465E+11 | 0.228837E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.335159E+10 | 0.127373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.302724E+10 | 0.475471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.335159E+10 | 0.123594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.324348E+10 | 0.180641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.335159E+10 | 0.580301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.324348E+10 | 0.121682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.335159E+10 | 0.183418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.335159E+10 | 0.229669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.324348E+10 | 0.638800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.335159E+10 | 0.958637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324348E+10 | 0.113613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.335159E+10 | 0.153597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.394623E+11 | 0.138427E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.302724E+10 | 0.127373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.335159E+10 | 0.229669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.759658E+10 | 0.213004E+11 | 0.125085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.717413E+10 | 0.190479E+11 | 0.104330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102772E+11 | 0.452355E+10 | 0.375796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113218E+11 | 0.107200E+10 | 0.633834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125350E+11 | 39566591.63 | 0.951743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.157649E+11 | 0.00 | 0.159790E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.183877E+11 | 24249.65 | 0.223199E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.216258E+11 | 138684.07 | 0.228441E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138496E+11 | 1633293.46 | 0.127909E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128679E+11 | 0.256470E+09 | 0.944193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.958565E+10 | 0.346273E+10 | 0.420371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.897067E+10 | 0.689355E+10 | 0.231118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149957E+12 | 0.565980E+11 | 0.111799E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.717413E+10 | 0.00 | 0.104330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.216258E+11 | 0.213004E+11 | 0.228441E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.839147E+11 | 0.579797E+12 | 0.386193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.750760E+11 | 0.475406E+12 | 0.334374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.856325E+11 | 0.168576E+12 | 0.205377E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.892186E+11 | 0.609762E+11 | 0.427718E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110520E+12 | 0.637380E+10 | 0.812443E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136163E+12 | 20554033.47 | 0.141539E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148364E+12 | 0.00 | 0.185975E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168553E+12 | 7663873.08 | 0.182709E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118553E+12 | 0.245964E+10 | 0.111819E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105392E+12 | 0.227759E+11 | 0.755363E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.760789E+11 | 0.155660E+12 | 0.231328E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.747768E+11 | 0.288784E+12 | 0.585426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127224E+13 | 0.176084E+13 | 0.878324E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.747768E+11 | 0.00 | 0.334374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.168553E+12 | 0.579797E+12 | 0.185975E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.101569E+11 | 0.104030E+12 | 0.471924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.902410E+10 | 0.923459E+11 | 0.304080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.877594E+10 | 0.404068E+11 | 0.197796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.842118E+10 | 0.167224E+11 | 0.435138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102799E+11 | 0.372557E+10 | 0.889372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132099E+11 | 0.160636E+09 | 0.159022E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148564E+11 | 63973.94 | 0.210151E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166159E+11 | 36716578.20 | 0.204713E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110305E+11 | 0.168102E+10 | 0.117439E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.924199E+10 | 0.854946E+10 | 0.709861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.814285E+10 | 0.423223E+11 | 0.186540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.929445E+10 | 0.720189E+11 | 0.371001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129050E+12 | 0.382000E+12 | 0.944666E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.814285E+10 | 63973.94 | 0.304080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166159E+11 | 0.104030E+12 | 0.210151E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.395826E+10 | 11733177.55 | 0.739839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.290212E+10 | 0.00 | 0.296783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.455358E+10 | 0.00 | 0.155184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.512931E+10 | 0.00 | 0.292202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.471084E+10 | 0.00 | 0.480498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.553186E+10 | 0.00 | 0.854508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.609088E+10 | 0.00 | 0.109406E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.722048E+10 | 0.00 | 0.113168E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.654714E+10 | 0.00 | 0.805727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.670184E+10 | 0.00 | 0.645474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.543598E+10 | 0.00 | 0.314144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.411210E+10 | 0.00 | 0.126399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.628944E+11 | 11733177.55 | 0.600354E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.290212E+10 | 0.00 | 0.296783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.722048E+10 | 11733177.55 | 0.113168E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.261881E+11 | 0.00 | 4224781.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906243E+11 | 0.00 | 0.00 | 0.00 |
February | 0.421429E+11 | 0.00 | 0.150762E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116047E+12 | 0.00 | 0.00 | 0.00 |
March | 0.622293E+11 | 0.00 | 0.224280E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129529E+12 | 0.00 | 0.00 | 0.00 |
April | 0.833120E+11 | 0.00 | 0.246311E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.956840E+11 | 0.00 | 0.00 | 0.00 |
May | 0.262168E+11 | 0.00 | 0.121009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383736E+11 | 0.00 | 0.00 | 0.00 |
June | 0.320525E+11 | 0.00 | 0.405781E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911605E+10 | 0.00 | 0.00 | 0.00 |
July | 0.419721E+11 | 0.00 | 0.757573E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99001362.23 | 0.00 | 0.00 | 0.00 |
August | 0.727112E+11 | 0.00 | 0.882423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.924600E+10 | 0.00 | 0.00 | 0.00 |
September | 0.253433E+11 | 0.00 | 0.425893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127404E+11 | 0.00 | 0.00 | 0.00 |
October | 0.451686E+11 | 0.00 | 0.240233E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541471E+11 | 0.00 | 0.00 | 0.00 |
November | 0.595747E+11 | 0.00 | 0.216842E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113421E+12 | 0.00 | 0.00 | 0.00 |
December | 0.869742E+11 | 0.00 | 0.231698E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222640E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.603886E+12 | 0.00 | 0.341060E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.891668E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.253433E+11 | 0.00 | 4224781.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99001362.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.869742E+11 | 0.00 | 0.882423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222640E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.338227E+10 | 0.00 | 0.00 | 0.00 | 0.132074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.305495E+10 | 0.00 | 0.00 | 0.00 | 0.243512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.338227E+10 | 0.00 | 0.00 | 0.00 | 0.413114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.327316E+10 | 0.00 | 0.00 | 0.00 | 0.543618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.338227E+10 | 0.00 | 0.00 | 0.00 | 0.217623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.327316E+10 | 0.00 | 0.00 | 0.00 | 0.361936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.338227E+10 | 0.00 | 0.00 | 0.00 | 0.515873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.338227E+10 | 0.00 | 0.00 | 0.00 | 0.667194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.327316E+10 | 0.00 | 0.00 | 0.00 | 0.230148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.338227E+10 | 0.00 | 0.00 | 0.00 | 0.334813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.327316E+10 | 0.00 | 0.00 | 0.00 | 0.401877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.338227E+10 | 0.00 | 0.00 | 0.00 | 0.526284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.398235E+11 | 0.00 | 0.00 | 0.00 | 0.458807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.305495E+10 | 0.00 | 0.00 | 0.00 | 0.132074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.338227E+10 | 0.00 | 0.00 | 0.00 | 0.667194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.324465E+11 | 0.00 | 0.00 | 0.00 | 0.588338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.293065E+11 | 0.00 | 0.00 | 0.00 | 0.164998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.324465E+11 | 0.00 | 0.00 | 0.00 | 0.318492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.313999E+11 | 0.00 | 0.00 | 0.00 | 0.425117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.324465E+11 | 0.00 | 0.00 | 0.00 | 0.164185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.313999E+11 | 0.00 | 0.00 | 0.00 | 0.292804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.324465E+11 | 0.00 | 0.00 | 0.00 | 0.421229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.324465E+11 | 0.00 | 0.00 | 0.00 | 0.545471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.313999E+11 | 0.00 | 0.00 | 0.00 | 0.175455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.324465E+11 | 0.00 | 0.00 | 0.00 | 0.258732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.313999E+11 | 0.00 | 0.00 | 0.00 | 0.302616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.324465E+11 | 0.00 | 0.00 | 0.00 | 0.388384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.382032E+12 | 0.00 | 0.00 | 0.00 | 0.351632E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.293065E+11 | 0.00 | 0.00 | 0.00 | 0.588338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.324465E+11 | 0.00 | 0.00 | 0.00 | 0.545471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.335159E+10 | 0.00 | 0.00 | 0.00 | 0.405435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.302724E+10 | 0.00 | 0.00 | 0.00 | 0.142305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.335159E+10 | 0.00 | 0.00 | 0.00 | 0.337411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.324348E+10 | 0.00 | 0.00 | 0.00 | 0.468109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.335159E+10 | 0.00 | 0.00 | 0.00 | 0.177216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.324348E+10 | 0.00 | 0.00 | 0.00 | 0.342929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.335159E+10 | 0.00 | 0.00 | 0.00 | 0.497016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.335159E+10 | 0.00 | 0.00 | 0.00 | 0.637348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.324348E+10 | 0.00 | 0.00 | 0.00 | 0.194865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.335159E+10 | 0.00 | 0.00 | 0.00 | 0.273806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324348E+10 | 0.00 | 0.00 | 0.00 | 0.313103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.335159E+10 | 0.00 | 0.00 | 0.00 | 0.403062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.394623E+11 | 0.00 | 0.00 | 0.00 | 0.382771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.302724E+10 | 0.00 | 0.00 | 0.00 | 0.405435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.335159E+10 | 0.00 | 0.00 | 0.00 | 0.637348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.189291E+11 | 0.00 | 0.00 | 63776146.33 | 0.00 | 0.00 | 0.297298E+11 | 0.00 | 0.35 |
February | 0.371344E+11 | 0.00 | 0.00 | 96966288.54 | 0.00 | 0.00 | 0.928053E+10 | 0.00 | 0.36 |
March | 0.184042E+11 | 0.00 | 0.00 | 0.393016E+09 | 0.00 | 0.00 | 0.256888E+11 | 0.00 | 0.39 |
April | 0.423915E+10 | 161842.76 | 0.00 | 0.273524E+09 | 0.00 | 0.00 | 0.255798E+11 | 0.00 | 0.36 |
May | 0.296785E+09 | 0.833818E+09 | 0.00 | 0.109807E+09 | 0.00 | 0.00 | 0.162916E+11 | 0.00 | 0.35 |
June | 39519946.43 | 0.158284E+11 | 0.00 | 0.109687E+09 | 0.124988E+09 | 0.00 | 0.238263E+10 | 0.00 | 0.37 |
July | 0.00 | 0.347764E+11 | 0.00 | 3483487.37 | 0.377780E+09 | 0.00 | 54662230.89 | 0.00 | 0.34 |
August | 0.00 | 0.277762E+11 | 0.00 | 35082229.26 | 0.294999E+09 | 0.00 | 0.101846E+10 | 0.00 | 0.37 |
September | 0.108410E+09 | 0.953216E+10 | 0.00 | 97200272.83 | 61701273.80 | 0.00 | 0.712723E+10 | 0.00 | 0.35 |
October | 0.134256E+10 | 0.199387E+10 | 0.00 | 0.672148E+09 | 0.00 | 0.00 | 0.147782E+11 | 0.00 | 0.35 |
November | 0.894426E+10 | 0.00 | 0.00 | 0.664716E+09 | 0.00 | 0.00 | 0.272338E+11 | 0.00 | 0.38 |
December | 0.134648E+11 | 0.00 | 0.00 | 0.197451E+09 | 0.00 | 0.00 | 0.322586E+11 | 0.00 | 0.41 |
Annual Sum or Average | 0.102903E+12 | 0.907410E+11 | 0.00 | 0.271686E+10 | 0.859469E+09 | 0.00 | 0.191424E+12 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3483487.37 | 0.00 | 0.00 | 54662230.89 | 0.00 | 0.34 |
Maximum of Months | 0.371344E+11 | 0.347764E+11 | 0.00 | 0.672148E+09 | 0.377780E+09 | 0.00 | 0.322586E+11 | 0.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.169216E+11 | 0.00 | 0.00 | 74513099.47 | 0.00 | 9478446.86 | 0.221802E+11 | 0.00 | 0.27 |
February | 0.201738E+11 | 0.00 | 0.00 | 0.299379E+09 | 0.00 | 0.00 | 0.174648E+11 | 0.00 | 0.28 |
March | 0.111901E+11 | 0.00 | 0.00 | 0.551071E+09 | 0.00 | 0.00 | 0.254043E+11 | 0.00 | 0.30 |
April | 0.503190E+10 | 0.00 | 0.00 | 0.285824E+09 | 418254.28 | 0.00 | 0.214747E+11 | 0.00 | 0.30 |
May | 0.174932E+10 | 0.198600E+09 | 0.00 | 0.104990E+09 | 63154602.69 | 0.00 | 0.149812E+11 | 0.00 | 0.31 |
June | 0.551734E+09 | 0.727743E+10 | 0.00 | 0.152907E+09 | 0.142768E+10 | 0.00 | 0.287642E+10 | 0.00 | 0.32 |
July | 48671362.27 | 0.194189E+11 | 0.00 | 5307908.87 | 0.685820E+10 | 0.00 | 0.166669E+09 | 0.00 | 0.35 |
August | 0.641529E+09 | 0.150123E+11 | 0.00 | 52798611.36 | 0.475504E+10 | 0.00 | 0.190922E+10 | 0.00 | 0.37 |
September | 0.102281E+10 | 0.459950E+10 | 0.00 | 73747529.55 | 0.161055E+09 | 0.00 | 0.742671E+10 | 0.00 | 0.30 |
October | 0.309749E+10 | 0.437660E+09 | 0.00 | 0.560002E+09 | 0.00 | 0.00 | 0.138014E+11 | 0.00 | 0.29 |
November | 0.697476E+10 | 0.00 | 0.00 | 0.583402E+09 | 0.00 | 0.00 | 0.241205E+11 | 0.00 | 0.29 |
December | 0.104998E+11 | 0.00 | 0.00 | 0.240407E+09 | 0.00 | 0.00 | 0.279027E+11 | 0.00 | 0.28 |
Annual Sum or Average | 0.779036E+11 | 0.469444E+11 | 0.00 | 0.298435E+10 | 0.132656E+11 | 9478446.86 | 0.179709E+12 | 0.00 | 0.31 |
Minimum of Months | 48671362.27 | 0.00 | 0.00 | 5307908.87 | 0.00 | 0.00 | 0.166669E+09 | 0.00 | 0.27 |
Maximum of Months | 0.201738E+11 | 0.194189E+11 | 0.00 | 0.583402E+09 | 0.685820E+10 | 9478446.86 | 0.279027E+11 | 0.00 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.339633E+12 | 0.00 | 0.00 | 0.197572E+09 | 0.00 | 0.107982E+11 | 0.669224E+11 | 0.00 | 0.32 |
February | 0.342747E+12 | 0.00 | 0.00 | 0.809772E+09 | 0.00 | 0.529515E+10 | 0.492049E+11 | 0.00 | 0.31 |
March | 0.192511E+12 | 0.00 | 0.00 | 0.276918E+10 | 0.00 | 0.00 | 0.136336E+12 | 0.00 | 0.28 |
April | 0.105767E+12 | 2030807.92 | 0.00 | 0.145195E+10 | 16299976.17 | 0.00 | 0.119990E+12 | 0.00 | 0.27 |
May | 0.286166E+11 | 0.201686E+10 | 0.00 | 0.742246E+09 | 0.873723E+09 | 0.00 | 0.118723E+12 | 0.00 | 0.29 |
June | 0.756410E+10 | 0.699839E+11 | 0.00 | 0.102593E+10 | 0.106963E+11 | 0.00 | 0.229926E+11 | 0.00 | 0.30 |
July | 0.152671E+09 | 0.185465E+12 | 0.00 | 51668903.05 | 0.324957E+11 | 0.00 | 0.160150E+10 | 0.00 | 0.29 |
August | 0.250947E+10 | 0.144292E+12 | 0.00 | 0.415018E+09 | 0.136147E+11 | 0.00 | 0.175231E+11 | 0.00 | 0.29 |
September | 0.131808E+11 | 0.442418E+11 | 0.00 | 0.490849E+09 | 0.189016E+10 | 0.00 | 0.593308E+11 | 0.00 | 0.28 |
October | 0.683359E+11 | 0.461220E+10 | 0.00 | 0.300415E+10 | 18113871.69 | 0.00 | 0.753573E+11 | 0.00 | 0.27 |
November | 0.168885E+12 | 0.00 | 0.00 | 0.248731E+10 | 0.00 | 36764873.00 | 0.101889E+12 | 0.00 | 0.27 |
December | 0.254184E+12 | 0.00 | 0.00 | 0.665878E+09 | 0.00 | 8612025.98 | 0.975229E+11 | 0.00 | 0.28 |
Annual Sum or Average | 0.152409E+13 | 0.450614E+12 | 0.00 | 0.141115E+11 | 0.596050E+11 | 0.161387E+11 | 0.867393E+12 | 0.00 | 0.29 |
Minimum of Months | 0.152671E+09 | 0.00 | 0.00 | 51668903.05 | 0.00 | 0.00 | 0.160150E+10 | 0.00 | 0.27 |
Maximum of Months | 0.342747E+12 | 0.185465E+12 | 0.00 | 0.300415E+10 | 0.324957E+11 | 0.107982E+11 | 0.136336E+12 | 0.00 | 0.32 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.313221E+11 | 0.00 | 0.00 | 67466.79 | 245743.96 | 0.814065E+10 | 0.106164E+09 | 0.00 | 0.34 |
February | 0.320707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608871E+10 | 0.00 | 0.00 | 0.33 |
March | 0.258003E+11 | 0.00 | 0.00 | 62089343.30 | 0.00 | 0.200692E+10 | 0.247327E+10 | 0.00 | 0.28 |
April | 0.145818E+11 | 0.00 | 0.00 | 59945037.05 | 186474.95 | 0.223380E+09 | 0.542124E+10 | 0.00 | 0.26 |
May | 0.572522E+10 | 0.128329E+09 | 0.00 | 52156438.12 | 24671876.35 | 59535476.66 | 0.803812E+10 | 0.00 | 0.27 |
June | 0.100194E+10 | 0.605327E+10 | 0.00 | 79996634.43 | 0.102490E+10 | 0.00 | 0.216910E+10 | 0.00 | 0.29 |
July | 59428332.47 | 0.170190E+11 | 0.00 | 6538009.56 | 0.307334E+10 | 0.00 | 0.208201E+09 | 0.00 | 0.28 |
August | 0.351554E+09 | 0.132153E+11 | 0.00 | 37758737.62 | 0.139634E+10 | 0.00 | 0.171823E+10 | 0.00 | 0.28 |
September | 0.279572E+10 | 0.357865E+10 | 0.00 | 33627291.84 | 0.445534E+09 | 0.00 | 0.373105E+10 | 0.00 | 0.26 |
October | 0.867210E+10 | 0.163068E+09 | 0.00 | 0.127419E+09 | 48381773.48 | 0.148567E+09 | 0.350676E+10 | 0.00 | 0.25 |
November | 0.217771E+11 | 0.00 | 0.00 | 34379300.63 | 0.00 | 0.217187E+10 | 0.116292E+10 | 0.00 | 0.28 |
December | 0.295355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399525E+10 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.173694E+12 | 0.401576E+11 | 0.00 | 0.493977E+09 | 0.601360E+10 | 0.228349E+11 | 0.285351E+11 | 0.00 | 0.29 |
Minimum of Months | 59428332.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.320707E+11 | 0.170190E+11 | 0.00 | 0.127419E+09 | 0.307334E+10 | 0.814065E+10 | 0.803812E+10 | 0.00 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.371208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252084E+10 | 0.00 | 0.00 | 0.34 |
February | 0.361063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237776E+10 | 0.00 | 0.00 | 0.35 |
March | 0.452502E+10 | 0.00 | 0.00 | 5620122.08 | 0.00 | 0.414286E+09 | 0.168674E+09 | 0.00 | 0.33 |
April | 0.281239E+10 | 0.00 | 0.00 | 11565954.32 | 74701.35 | 1990054.13 | 0.868394E+09 | 0.00 | 0.34 |
May | 0.115169E+10 | 40635661.64 | 0.00 | 10651802.41 | 11279582.91 | 0.00 | 0.143028E+10 | 0.00 | 0.39 |
June | 0.229934E+09 | 0.144761E+10 | 0.00 | 15362758.26 | 0.271444E+09 | 0.00 | 0.352831E+09 | 0.00 | 0.46 |
July | 10091064.52 | 0.392570E+10 | 0.00 | 874456.84 | 0.123578E+10 | 0.00 | 27417246.69 | 0.00 | 0.53 |
August | 0.147106E+09 | 0.302081E+10 | 0.00 | 6582901.10 | 0.857985E+09 | 0.00 | 0.264618E+09 | 0.00 | 0.53 |
September | 0.639050E+09 | 0.745163E+09 | 0.00 | 6392300.73 | 42536444.48 | 0.00 | 0.616355E+09 | 0.00 | 0.37 |
October | 0.186331E+10 | 65479103.31 | 0.00 | 26881947.09 | 1585358.89 | 133161.22 | 0.495388E+09 | 0.00 | 0.32 |
November | 0.366051E+10 | 0.00 | 0.00 | 7119781.66 | 0.00 | 0.262222E+09 | 0.189580E+09 | 0.00 | 0.30 |
December | 0.472272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555851E+09 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.270845E+11 | 0.924540E+10 | 0.00 | 91052024.50 | 0.242068E+10 | 0.613309E+10 | 0.441354E+10 | 0.00 | 0.38 |
Minimum of Months | 10091064.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.472272E+10 | 0.392570E+10 | 0.00 | 26881947.09 | 0.123578E+10 | 0.252084E+10 | 0.143028E+10 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.457780E+10 | 0.00 | 0.00 | 109087.06 | 0.00 | 0.293343E+10 | 57098965.59 | 0.00 | 0.64 |
February | 0.491435E+10 | 0.00 | 0.00 | 567152.72 | 0.00 | 0.231921E+10 | 40505593.01 | 0.00 | 0.65 |
March | 0.502763E+10 | 0.00 | 0.00 | 17403270.39 | 0.00 | 0.600702E+09 | 0.742832E+09 | 0.00 | 0.63 |
April | 0.344198E+10 | 12563.17 | 0.00 | 14181151.05 | 78297.30 | 62985493.37 | 0.105176E+10 | 0.00 | 0.64 |
May | 0.172034E+10 | 41636524.67 | 0.00 | 10002385.09 | 9742794.36 | 212488.78 | 0.137988E+10 | 0.00 | 0.70 |
June | 0.293151E+09 | 0.110704E+10 | 0.00 | 15848265.55 | 0.443804E+09 | 0.00 | 0.396903E+09 | 0.00 | 0.70 |
July | 14335535.90 | 0.299141E+10 | 0.00 | 747762.56 | 0.183850E+10 | 0.00 | 29492870.99 | 0.00 | 0.81 |
August | 0.212025E+09 | 0.241143E+10 | 0.00 | 5739352.43 | 0.122685E+10 | 0.00 | 0.257442E+09 | 0.00 | 0.84 |
September | 0.857057E+09 | 0.512216E+09 | 0.00 | 7306648.82 | 0.227424E+09 | 0.00 | 0.630683E+09 | 0.00 | 0.63 |
October | 0.230496E+10 | 53681224.04 | 0.00 | 27892730.39 | 3431474.16 | 613397.59 | 0.572521E+09 | 0.00 | 0.59 |
November | 0.443191E+10 | 0.00 | 0.00 | 4173583.87 | 0.00 | 0.408945E+09 | 0.164528E+09 | 0.00 | 0.56 |
December | 0.514784E+10 | 0.00 | 0.00 | 128496.55 | 0.00 | 0.123846E+10 | 34747603.15 | 0.00 | 0.58 |
Annual Sum or Average | 0.329434E+11 | 0.711743E+10 | 0.00 | 0.104100E+09 | 0.374984E+10 | 0.756456E+10 | 0.535839E+10 | 0.00 | 0.66 |
Minimum of Months | 14335535.90 | 0.00 | 0.00 | 109087.06 | 0.00 | 0.00 | 29492870.99 | 0.00 | 0.56 |
Maximum of Months | 0.514784E+10 | 0.299141E+10 | 0.00 | 27892730.39 | 0.183850E+10 | 0.293343E+10 | 0.137988E+10 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.447608E+10 | 0.00 | 0.00 | 9016324.31 | 0.00 | 0.304904E+10 | 0.237007E+10 | 0.00 | 0.54 |
February | 0.470968E+10 | 0.00 | 0.00 | 46510348.92 | 0.00 | 0.252855E+10 | 0.247095E+10 | 0.00 | 0.56 |
March | 0.496015E+10 | 0.00 | 0.00 | 87241215.88 | 0.00 | 0.804858E+09 | 0.303172E+10 | 0.00 | 0.58 |
April | 0.389388E+10 | 8224.69 | 0.00 | 25613384.81 | 101246.30 | 0.187355E+09 | 0.168672E+10 | 0.00 | 0.53 |
May | 0.209701E+10 | 57187164.37 | 0.00 | 11213718.99 | 11300237.41 | 319489.87 | 0.155197E+10 | 0.00 | 0.54 |
June | 0.421264E+09 | 0.163159E+10 | 0.00 | 11085742.26 | 0.444169E+09 | 0.00 | 0.345208E+09 | 0.00 | 0.56 |
July | 20499085.14 | 0.460775E+10 | 0.00 | 1066769.73 | 0.181829E+10 | 0.00 | 24662796.40 | 0.00 | 0.67 |
August | 0.254959E+09 | 0.397870E+10 | 0.00 | 9690107.92 | 0.127884E+10 | 0.00 | 0.356471E+09 | 0.00 | 0.75 |
September | 0.898756E+09 | 0.104789E+10 | 0.00 | 17526981.35 | 0.151275E+09 | 0.00 | 0.123730E+10 | 0.00 | 0.61 |
October | 0.213942E+10 | 0.165766E+09 | 0.00 | 0.105340E+09 | 1710447.34 | 368412.14 | 0.230124E+10 | 0.00 | 0.63 |
November | 0.413777E+10 | 0.00 | 0.00 | 69028068.02 | 0.00 | 0.522266E+09 | 0.222091E+10 | 0.00 | 0.51 |
December | 0.464708E+10 | 0.00 | 0.00 | 24466519.50 | 0.00 | 0.152285E+10 | 0.242007E+10 | 0.00 | 0.51 |
Annual Sum or Average | 0.326565E+11 | 0.114889E+11 | 0.00 | 0.417799E+09 | 0.370569E+10 | 0.861561E+10 | 0.200173E+11 | 0.00 | 0.58 |
Minimum of Months | 20499085.14 | 0.00 | 0.00 | 1066769.73 | 0.00 | 0.00 | 24662796.40 | 0.00 | 0.51 |
Maximum of Months | 0.496015E+10 | 0.460775E+10 | 0.00 | 0.105340E+09 | 0.181829E+10 | 0.304904E+10 | 0.303172E+10 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.727749E+10 | 0.00 | 0.00 | 950741.90 | 0.00 | 0.159136E+10 | 0.350326E+09 | 0.00 | 0.78 |
February | 0.719625E+10 | 0.00 | 0.00 | 6395166.58 | 0.00 | 0.139024E+10 | 0.319920E+09 | 0.00 | 0.80 |
March | 0.653676E+10 | 0.00 | 0.00 | 35825676.79 | 0.00 | 6929498.98 | 0.143944E+10 | 0.00 | 0.80 |
April | 0.392378E+10 | 15297.00 | 0.00 | 24800625.16 | 95335.32 | 0.00 | 0.178970E+10 | 0.00 | 0.81 |
May | 0.180128E+10 | 49532106.00 | 0.00 | 10150102.25 | 14263282.03 | 0.00 | 0.188034E+10 | 0.00 | 0.84 |
June | 0.398788E+09 | 0.172471E+10 | 0.00 | 11143176.78 | 0.317358E+09 | 0.00 | 0.392054E+09 | 0.00 | 0.89 |
July | 14360493.90 | 0.481109E+10 | 0.00 | 2130493.51 | 0.156055E+10 | 0.00 | 33351143.39 | 0.00 | 1.04 |
August | 0.184196E+09 | 0.398734E+10 | 0.00 | 9909181.83 | 0.110855E+10 | 0.00 | 0.397593E+09 | 0.00 | 1.13 |
September | 0.991903E+09 | 0.858795E+09 | 0.00 | 7880224.99 | 95195880.17 | 0.00 | 0.779322E+09 | 0.00 | 0.77 |
October | 0.281529E+10 | 92750541.02 | 0.00 | 32854686.93 | 2408386.32 | 0.00 | 0.748439E+09 | 0.00 | 0.74 |
November | 0.580793E+10 | 0.00 | 0.00 | 10426788.69 | 0.00 | 6606284.63 | 0.303640E+09 | 0.00 | 0.68 |
December | 0.746500E+10 | 0.00 | 0.00 | 2901789.74 | 0.00 | 7362646.33 | 0.374886E+09 | 0.00 | 0.71 |
Annual Sum or Average | 0.444130E+11 | 0.115242E+11 | 0.00 | 0.155369E+09 | 0.309843E+10 | 0.300250E+10 | 0.880901E+10 | 0.00 | 0.83 |
Minimum of Months | 14360493.90 | 0.00 | 0.00 | 950741.90 | 0.00 | 0.00 | 33351143.39 | 0.00 | 0.68 |
Maximum of Months | 0.746500E+10 | 0.481109E+10 | 0.00 | 35825676.79 | 0.156055E+10 | 0.159136E+10 | 0.188034E+10 | 0.00 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.215387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.927484E+11 | 0.00 | 0.00 | 0.68 |
February | 0.241941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.844068E+11 | 0.00 | 0.00 | 0.66 |
March | 0.504289E+11 | 0.00 | 0.00 | 33299.84 | 0.00 | 0.327966E+11 | 25484253.43 | 0.00 | 0.56 |
April | 0.414274E+11 | 0.00 | 0.00 | 10801080.68 | 5047666.90 | 0.996504E+10 | 0.214945E+10 | 0.00 | 0.51 |
May | 0.248325E+11 | 0.423729E+09 | 0.00 | 42106135.34 | 0.240646E+09 | 0.225009E+09 | 0.765582E+10 | 0.00 | 0.51 |
June | 0.461751E+10 | 0.140646E+11 | 0.00 | 49611826.01 | 0.468614E+10 | 0.00 | 0.239149E+10 | 0.00 | 0.54 |
July | 0.110216E+09 | 0.393504E+11 | 0.00 | 7186704.79 | 0.129687E+11 | 0.00 | 0.258386E+09 | 0.00 | 0.55 |
August | 0.210893E+10 | 0.309891E+11 | 0.00 | 43575245.79 | 0.608168E+10 | 0.00 | 0.211275E+10 | 0.00 | 0.52 |
September | 0.130489E+11 | 0.599854E+10 | 0.00 | 22714275.84 | 0.342719E+10 | 0.00 | 0.321063E+10 | 0.00 | 0.49 |
October | 0.296511E+11 | 0.664759E+09 | 0.00 | 7788388.72 | 0.111675E+09 | 0.300900E+10 | 0.728646E+09 | 0.00 | 0.47 |
November | 0.389913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296449E+11 | 0.00 | 0.00 | 0.52 |
December | 0.320125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612593E+11 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.282962E+12 | 0.914911E+11 | 0.00 | 0.183817E+09 | 0.275211E+11 | 0.314055E+12 | 0.185326E+11 | 0.00 | 0.55 |
Minimum of Months | 0.110216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.504289E+11 | 0.393504E+11 | 0.00 | 49611826.01 | 0.129687E+11 | 0.927484E+11 | 0.765582E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.229393E+11 | 0.00 | 0.00 | 428352.33 | 0.00 | 0.619359E+11 | 69337247.20 | 0.00 | 0.78 |
February | 0.291242E+11 | 0.00 | 0.00 | 2495701.40 | 0.00 | 0.507777E+11 | 0.160463E+09 | 0.00 | 0.75 |
March | 0.374338E+11 | 0.00 | 0.00 | 0.105970E+09 | 0.00 | 0.205025E+11 | 0.485591E+10 | 0.00 | 0.65 |
April | 0.273343E+11 | 1327438.76 | 0.00 | 0.111966E+09 | 3248751.25 | 0.697642E+10 | 0.919579E+10 | 0.00 | 0.65 |
May | 0.168591E+11 | 0.502872E+09 | 0.00 | 88907676.34 | 0.143465E+09 | 0.115311E+09 | 0.123043E+11 | 0.00 | 0.72 |
June | 0.309102E+10 | 0.117262E+11 | 0.00 | 0.147942E+09 | 0.433990E+10 | 0.00 | 0.390861E+10 | 0.00 | 0.74 |
July | 71882099.07 | 0.335230E+11 | 0.00 | 7876469.63 | 0.123400E+11 | 0.00 | 0.345405E+09 | 0.00 | 0.77 |
August | 0.157481E+10 | 0.278574E+11 | 0.00 | 56379502.89 | 0.603805E+10 | 0.00 | 0.278631E+10 | 0.00 | 0.78 |
September | 0.872865E+10 | 0.494901E+10 | 0.00 | 60320693.50 | 0.310782E+10 | 5524230.67 | 0.546292E+10 | 0.00 | 0.67 |
October | 0.205564E+11 | 0.613340E+09 | 0.00 | 0.186480E+09 | 60630211.01 | 0.222040E+10 | 0.422783E+10 | 0.00 | 0.61 |
November | 0.300286E+11 | 0.00 | 0.00 | 20914528.20 | 0.00 | 0.195284E+11 | 0.726208E+09 | 0.00 | 0.59 |
December | 0.264917E+11 | 0.00 | 0.00 | 213536.78 | 0.00 | 0.411034E+11 | 24558457.50 | 0.00 | 0.65 |
Annual Sum or Average | 0.224234E+12 | 0.791731E+11 | 0.00 | 0.789895E+09 | 0.260331E+11 | 0.203166E+12 | 0.440676E+11 | 0.00 | 0.70 |
Minimum of Months | 71882099.07 | 0.00 | 0.00 | 213536.78 | 0.00 | 0.00 | 24558457.50 | 0.00 | 0.59 |
Maximum of Months | 0.374338E+11 | 0.335230E+11 | 0.00 | 0.186480E+09 | 0.123400E+11 | 0.619359E+11 | 0.123043E+11 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.399444E+11 | 0.00 | 0.00 | 81610253.72 | 0.00 | 0.566009E+11 | 0.260202E+11 | 0.00 | 0.73 |
February | 0.460642E+11 | 0.00 | 0.00 | 0.464387E+09 | 0.00 | 0.454499E+11 | 0.285743E+11 | 0.00 | 0.73 |
March | 0.463460E+11 | 0.00 | 0.00 | 0.821345E+09 | 0.00 | 0.186617E+11 | 0.330990E+11 | 0.00 | 0.68 |
April | 0.347819E+11 | 698180.99 | 0.00 | 0.218834E+09 | 4404932.48 | 0.847427E+10 | 0.164578E+11 | 0.00 | 0.59 |
May | 0.213314E+11 | 0.634454E+09 | 0.00 | 93985159.30 | 0.175014E+09 | 0.250023E+09 | 0.140589E+11 | 0.00 | 0.56 |
June | 0.437196E+10 | 0.164875E+11 | 0.00 | 82171351.27 | 0.459664E+10 | 0.00 | 0.316118E+10 | 0.00 | 0.59 |
July | 0.167546E+09 | 0.480906E+11 | 0.00 | 9549437.97 | 0.112770E+11 | 0.00 | 0.224027E+09 | 0.00 | 0.61 |
August | 0.184451E+10 | 0.440860E+11 | 0.00 | 91203451.15 | 0.469522E+10 | 0.00 | 0.368618E+10 | 0.00 | 0.69 |
September | 0.923681E+10 | 0.113191E+11 | 0.00 | 0.162459E+09 | 0.210245E+10 | 0.00 | 0.123359E+11 | 0.00 | 0.67 |
October | 0.192798E+11 | 0.216922E+10 | 0.00 | 0.103015E+10 | 31090717.29 | 0.178703E+10 | 0.246263E+11 | 0.00 | 0.71 |
November | 0.382597E+11 | 0.00 | 0.00 | 0.618419E+09 | 0.00 | 0.161471E+11 | 0.231921E+11 | 0.00 | 0.61 |
December | 0.428013E+11 | 0.00 | 0.00 | 0.201023E+09 | 0.00 | 0.354271E+11 | 0.237719E+11 | 0.00 | 0.64 |
Annual Sum or Average | 0.304429E+12 | 0.122788E+12 | 0.00 | 0.387513E+10 | 0.228818E+11 | 0.182798E+12 | 0.209208E+12 | 0.00 | 0.65 |
Minimum of Months | 0.167546E+09 | 0.00 | 0.00 | 9549437.97 | 0.00 | 0.00 | 0.224027E+09 | 0.00 | 0.56 |
Maximum of Months | 0.463460E+11 | 0.480906E+11 | 0.00 | 0.103015E+10 | 0.112770E+11 | 0.566009E+11 | 0.330990E+11 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.343108E+11 | 0.00 | 0.00 | 503911.06 | 0.00 | 0.710242E+11 | 0.717195E+09 | 0.00 | 0.98 |
February | 0.389302E+11 | 0.00 | 0.00 | 27016847.25 | 0.00 | 0.601743E+11 | 0.156286E+10 | 0.00 | 0.95 |
March | 0.522603E+11 | 0.00 | 0.00 | 0.170636E+09 | 0.00 | 0.190376E+11 | 0.821193E+10 | 0.00 | 0.83 |
April | 0.367979E+11 | 0.00 | 0.00 | 0.128288E+09 | 4705059.18 | 0.655404E+10 | 0.968937E+10 | 0.00 | 0.79 |
May | 0.211946E+11 | 0.511272E+09 | 0.00 | 64362686.78 | 0.198764E+09 | 44553835.20 | 0.119982E+11 | 0.00 | 0.81 |
June | 0.415618E+10 | 0.148435E+11 | 0.00 | 68910834.35 | 0.383248E+10 | 0.00 | 0.301308E+10 | 0.00 | 0.85 |
July | 0.161071E+09 | 0.384195E+11 | 0.00 | 11585756.90 | 0.125449E+11 | 0.00 | 0.211918E+09 | 0.00 | 0.84 |
August | 0.184328E+10 | 0.335740E+11 | 0.00 | 53532261.72 | 0.529676E+10 | 0.00 | 0.261036E+10 | 0.00 | 0.86 |
September | 0.113828E+11 | 0.689061E+10 | 0.00 | 46283135.68 | 0.269776E+10 | 3732951.81 | 0.481511E+10 | 0.00 | 0.76 |
October | 0.254360E+11 | 0.889277E+09 | 0.00 | 0.193755E+09 | 0.133742E+09 | 0.215027E+10 | 0.464470E+10 | 0.00 | 0.72 |
November | 0.410405E+11 | 0.00 | 0.00 | 25521836.14 | 0.00 | 0.222046E+11 | 0.697840E+09 | 0.00 | 0.75 |
December | 0.422965E+11 | 0.00 | 0.00 | 2560.45 | 0.00 | 0.445132E+11 | 8060680.84 | 0.00 | 0.84 |
Annual Sum or Average | 0.309810E+12 | 0.951281E+11 | 0.00 | 0.790399E+09 | 0.247091E+11 | 0.225706E+12 | 0.481806E+11 | 0.00 | 0.83 |
Minimum of Months | 0.161071E+09 | 0.00 | 0.00 | 2560.45 | 0.00 | 0.00 | 8060680.84 | 0.00 | 0.72 |
Maximum of Months | 0.522603E+11 | 0.384195E+11 | 0.00 | 0.193755E+09 | 0.125449E+11 | 0.710242E+11 | 0.119982E+11 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.149177E+10 | 0.00 | 69394.52 | 0.00 | 0.00 | 0.110556E+11 | 0.00 | 8290.36 | 0.86 |
February | 0.163574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105234E+11 | 0.00 | 0.00 | 0.84 |
March | 0.405412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543205E+10 | 0.00 | 0.00 | 0.70 |
April | 0.379179E+10 | 0.00 | 0.00 | 689495.61 | 58948.69 | 0.206243E+10 | 0.191054E+09 | 0.00 | 0.61 |
May | 0.290181E+10 | 24547455.20 | 0.00 | 3215726.04 | 8636698.53 | 0.211466E+09 | 0.673792E+09 | 0.00 | 0.59 |
June | 0.537539E+09 | 0.106512E+10 | 0.00 | 4047425.08 | 0.670763E+09 | 0.00 | 0.265156E+09 | 0.00 | 0.56 |
July | 29793247.36 | 0.313735E+10 | 0.00 | 1051845.42 | 0.190315E+10 | 0.00 | 33719326.67 | 0.00 | 0.58 |
August | 0.225378E+09 | 0.244227E+10 | 0.00 | 4540453.21 | 0.110473E+10 | 0.00 | 0.249916E+09 | 0.00 | 0.55 |
September | 0.142036E+10 | 0.420492E+09 | 0.00 | 1975569.07 | 0.529823E+09 | 66403958.31 | 0.282358E+09 | 0.00 | 0.55 |
October | 0.271146E+10 | 20953611.69 | 0.00 | 287510.96 | 25836283.43 | 0.879289E+09 | 67675532.94 | 0.00 | 0.56 |
November | 0.301281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491274E+10 | 0.00 | 0.00 | 0.70 |
December | 0.158670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903591E+10 | 0.00 | 0.00 | 0.80 |
Annual Sum or Average | 0.233993E+11 | 0.711074E+10 | 69394.52 | 15808025.39 | 0.424299E+10 | 0.441794E+11 | 0.176367E+10 | 8290.36 | 0.66 |
Minimum of Months | 29793247.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.405412E+10 | 0.313735E+10 | 69394.52 | 4540453.21 | 0.190315E+10 | 0.110556E+11 | 0.673792E+09 | 8290.36 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.192512E+10 | 0.00 | 48859.80 | 0.00 | 0.00 | 0.686924E+10 | 0.00 | 5676.47 | 0.94 |
February | 0.248638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602674E+10 | 0.00 | 0.00 | 0.92 |
March | 0.354999E+10 | 0.00 | 0.00 | 3470486.38 | 0.00 | 0.296530E+10 | 0.158885E+09 | 0.00 | 0.77 |
April | 0.238299E+10 | 58982.52 | 0.00 | 8337652.52 | 0.00 | 0.122866E+10 | 0.797490E+09 | 0.00 | 0.70 |
May | 0.158282E+10 | 29539192.16 | 0.00 | 8276964.58 | 2309658.63 | 98613121.90 | 0.127762E+10 | 0.00 | 0.73 |
June | 0.246397E+09 | 0.977519E+09 | 0.00 | 14038812.66 | 0.413232E+09 | 0.00 | 0.438968E+09 | 0.00 | 0.70 |
July | 14853573.61 | 0.296765E+10 | 0.00 | 1294502.54 | 0.109538E+10 | 0.00 | 45190293.06 | 0.00 | 0.72 |
August | 0.108472E+09 | 0.247444E+10 | 0.00 | 6375819.31 | 0.552832E+09 | 0.00 | 0.330824E+09 | 0.00 | 0.74 |
September | 0.766273E+09 | 0.393339E+09 | 0.00 | 5892000.22 | 0.339879E+09 | 20692687.88 | 0.557525E+09 | 0.00 | 0.66 |
October | 0.194085E+10 | 25077243.59 | 0.00 | 9412790.74 | 12736010.71 | 0.395711E+09 | 0.260208E+09 | 0.00 | 0.63 |
November | 0.289163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266839E+10 | 0.00 | 0.00 | 0.76 |
December | 0.221689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523694E+10 | 0.00 | 0.00 | 0.87 |
Annual Sum or Average | 0.201127E+11 | 0.686763E+10 | 48859.80 | 57099028.95 | 0.241637E+10 | 0.255103E+11 | 0.386671E+10 | 5676.47 | 0.76 |
Minimum of Months | 14853573.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
Maximum of Months | 0.354999E+10 | 0.296765E+10 | 48859.80 | 14038812.66 | 0.109538E+10 | 0.686924E+10 | 0.127762E+10 | 5676.47 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.337380E+10 | 0.00 | 68184.50 | 4942648.82 | 0.00 | 0.779983E+10 | 0.157845E+10 | 8355.76 | 0.87 |
February | 0.404966E+10 | 0.00 | 0.00 | 33049190.74 | 0.00 | 0.666210E+10 | 0.188741E+10 | 0.00 | 0.87 |
March | 0.407530E+10 | 0.00 | 0.00 | 66081620.65 | 0.00 | 0.366408E+10 | 0.268302E+10 | 0.00 | 0.78 |
April | 0.315874E+10 | 26656.58 | 0.00 | 18408998.41 | 31423.55 | 0.174587E+10 | 0.157032E+10 | 0.00 | 0.66 |
May | 0.239128E+10 | 32588842.48 | 0.00 | 8951513.03 | 8044556.27 | 0.225938E+09 | 0.138292E+10 | 0.00 | 0.62 |
June | 0.472793E+09 | 0.121990E+10 | 0.00 | 7520946.80 | 0.662438E+09 | 329050.93 | 0.387226E+09 | 0.00 | 0.60 |
July | 24956391.65 | 0.379266E+10 | 0.00 | 1685938.14 | 0.173487E+10 | 0.00 | 46133532.14 | 0.00 | 0.62 |
August | 0.172119E+09 | 0.349220E+10 | 0.00 | 10196114.80 | 0.874831E+09 | 0.00 | 0.462058E+09 | 0.00 | 0.68 |
September | 0.987569E+09 | 0.789562E+09 | 0.00 | 17833748.40 | 0.403374E+09 | 17450849.80 | 0.124864E+10 | 0.00 | 0.68 |
October | 0.180812E+10 | 67530424.39 | 0.00 | 83416097.52 | 17701257.61 | 0.500224E+09 | 0.227194E+10 | 0.00 | 0.74 |
November | 0.383819E+10 | 0.00 | 0.00 | 40227190.44 | 0.00 | 0.308035E+10 | 0.137464E+10 | 0.00 | 0.75 |
December | 0.362379E+10 | 0.00 | 0.00 | 11088099.53 | 0.00 | 0.589859E+10 | 0.130682E+10 | 0.00 | 0.81 |
Annual Sum or Average | 0.279763E+11 | 0.939447E+10 | 68184.50 | 0.303402E+09 | 0.370129E+10 | 0.295948E+11 | 0.161996E+11 | 8355.76 | 0.72 |
Minimum of Months | 24956391.65 | 0.00 | 0.00 | 1685938.14 | 0.00 | 0.00 | 46133532.14 | 0.00 | 0.60 |
Maximum of Months | 0.407530E+10 | 0.379266E+10 | 68184.50 | 83416097.52 | 0.173487E+10 | 0.779983E+10 | 0.268302E+10 | 8355.76 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.238071E+10 | 0.00 | 56889.42 | 30177.88 | 0.00 | 0.745994E+10 | 58023482.39 | 4632.51 | 1.06 |
February | 0.281116E+10 | 0.00 | 0.00 | 820156.38 | 0.00 | 0.665704E+10 | 0.101844E+09 | 0.00 | 1.03 |
March | 0.400918E+10 | 0.00 | 0.00 | 15193609.21 | 0.00 | 0.292028E+10 | 0.727292E+09 | 0.00 | 0.88 |
April | 0.292964E+10 | 0.00 | 0.00 | 12621387.76 | 46683.95 | 0.117492E+10 | 0.976559E+09 | 0.00 | 0.80 |
May | 0.195841E+10 | 26406383.11 | 0.00 | 7080281.57 | 6924844.77 | 0.131531E+09 | 0.120408E+10 | 0.00 | 0.80 |
June | 0.356661E+09 | 0.111848E+10 | 0.00 | 8174622.50 | 0.434482E+09 | 0.00 | 0.372381E+09 | 0.00 | 0.79 |
July | 16865245.96 | 0.313750E+10 | 0.00 | 2457650.18 | 0.128946E+10 | 0.00 | 42695282.88 | 0.00 | 0.78 |
August | 0.153781E+09 | 0.270531E+10 | 0.00 | 6427046.49 | 0.647912E+09 | 0.00 | 0.307636E+09 | 0.00 | 0.81 |
September | 0.100332E+10 | 0.497778E+09 | 0.00 | 5644316.77 | 0.346448E+09 | 16849003.00 | 0.507013E+09 | 0.00 | 0.73 |
October | 0.206045E+10 | 32202766.42 | 0.00 | 18158553.32 | 18423578.03 | 0.455462E+09 | 0.488207E+09 | 0.00 | 0.73 |
November | 0.319903E+10 | 0.00 | 0.00 | 1358319.60 | 0.00 | 0.302007E+10 | 48063388.87 | 0.00 | 0.86 |
December | 0.283419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556607E+10 | 0.00 | 0.00 | 0.98 |
Annual Sum or Average | 0.237134E+11 | 0.751768E+10 | 56889.42 | 77966121.66 | 0.274370E+10 | 0.274022E+11 | 0.483379E+10 | 4632.51 | 0.85 |
Minimum of Months | 16865245.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
Maximum of Months | 0.400918E+10 | 0.313750E+10 | 56889.42 | 18158553.32 | 0.128946E+10 | 0.745994E+10 | 0.120408E+10 | 4632.51 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 73966021.16 | 0.00 | 0.00 | 7066646.61 | 0.00 | 0.00 | 0.132969E+10 | 0.00 | 0.58 |
February | 0.00 | 0.00 | 0.00 | 0.106569E+09 | 0.00 | 0.00 | 0.122315E+10 | 0.00 | 0.58 |
March | 0.00 | 0.00 | 0.00 | 0.187754E+09 | 0.00 | 0.00 | 0.100188E+10 | 0.00 | 0.58 |
April | 0.00 | 43918.60 | 0.00 | 0.126981E+09 | 0.00 | 0.00 | 0.736437E+09 | 0.00 | 0.58 |
May | 0.00 | 3933778.26 | 0.00 | 10935146.79 | 0.00 | 0.00 | 0.559912E+09 | 0.00 | 0.58 |
June | 0.00 | 0.235278E+09 | 0.00 | 31461260.55 | 0.00 | 0.00 | 87728179.75 | 0.00 | 0.59 |
July | 0.00 | 0.675304E+09 | 0.00 | 931120.70 | 0.00 | 0.00 | 3119274.19 | 0.00 | 0.59 |
August | 0.00 | 0.480811E+09 | 0.00 | 16936854.86 | 0.00 | 0.00 | 45789579.13 | 0.00 | 0.59 |
September | 0.00 | 0.107319E+09 | 0.00 | 7863964.18 | 0.00 | 0.00 | 0.271115E+09 | 0.00 | 0.58 |
October | 0.00 | 8974706.12 | 0.00 | 0.113920E+09 | 0.00 | 0.00 | 0.491634E+09 | 0.00 | 0.58 |
November | 0.00 | 0.00 | 0.00 | 0.185985E+09 | 0.00 | 0.00 | 0.872103E+09 | 0.00 | 0.58 |
December | 0.00 | 0.00 | 0.00 | 0.132197E+09 | 0.00 | 0.00 | 0.116966E+10 | 0.00 | 0.58 |
Annual Sum or Average | 73966021.16 | 0.151166E+10 | 0.00 | 0.928601E+09 | 0.00 | 0.00 | 0.779222E+10 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 931120.70 | 0.00 | 0.00 | 3119274.19 | 0.00 | 0.58 |
Maximum of Months | 73966021.16 | 0.675304E+09 | 0.00 | 0.187754E+09 | 0.00 | 0.00 | 0.132969E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.687930E+10 | 0.00 | 0.00 | 26032395.56 | 0.00 | 0.00 | 0.701140E+10 | 0.00 | 0.58 |
February | 0.00 | 0.00 | 0.00 | 0.774682E+09 | 0.00 | 0.00 | 0.125232E+11 | 0.00 | 0.58 |
March | 0.00 | 0.00 | 0.00 | 0.164533E+10 | 0.00 | 0.00 | 0.102511E+11 | 0.00 | 0.58 |
April | 0.00 | 359461.25 | 0.00 | 0.115803E+10 | 0.00 | 0.00 | 0.748041E+10 | 0.00 | 0.58 |
May | 0.00 | 38427848.35 | 0.00 | 89031203.94 | 0.00 | 0.00 | 0.563907E+10 | 0.00 | 0.58 |
June | 0.00 | 0.232732E+10 | 0.00 | 0.294149E+09 | 0.00 | 0.00 | 0.901145E+09 | 0.00 | 0.59 |
July | 0.00 | 0.672097E+10 | 0.00 | 8926852.15 | 0.00 | 0.00 | 31779893.14 | 0.00 | 0.59 |
August | 0.00 | 0.479268E+10 | 0.00 | 0.162129E+09 | 0.00 | 0.00 | 0.468115E+09 | 0.00 | 0.59 |
September | 0.00 | 0.104171E+10 | 0.00 | 63317640.33 | 0.00 | 0.00 | 0.274415E+10 | 0.00 | 0.58 |
October | 0.00 | 85753736.68 | 0.00 | 0.990558E+09 | 0.00 | 0.00 | 0.507539E+10 | 0.00 | 0.58 |
November | 0.00 | 0.00 | 0.00 | 0.157006E+10 | 0.00 | 0.00 | 0.901073E+10 | 0.00 | 0.58 |
December | 0.00 | 0.00 | 0.00 | 0.113364E+10 | 0.00 | 0.00 | 0.118840E+11 | 0.00 | 0.58 |
Annual Sum or Average | 0.687930E+10 | 0.150072E+11 | 0.00 | 0.791589E+10 | 0.00 | 0.00 | 0.730205E+11 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 8926852.15 | 0.00 | 0.00 | 31779893.14 | 0.00 | 0.58 |
Maximum of Months | 0.687930E+10 | 0.672097E+10 | 0.00 | 0.164533E+10 | 0.00 | 0.00 | 0.125232E+11 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.971966E+09 | 0.00 | 0.00 | 1401364.61 | 0.00 | 0.00 | 0.377344E+09 | 0.00 | 0.58 |
February | 0.239618E+09 | 0.00 | 0.00 | 49513816.87 | 0.00 | 0.00 | 0.103902E+10 | 0.00 | 0.58 |
March | 0.00 | 0.00 | 0.00 | 0.141125E+09 | 0.00 | 0.00 | 0.104863E+10 | 0.00 | 0.58 |
April | 602247.94 | 28227.96 | 0.00 | 0.107521E+09 | 0.00 | 0.00 | 0.757318E+09 | 0.00 | 0.58 |
May | 36510837.68 | 3889063.13 | 0.00 | 7412246.02 | 0.00 | 0.00 | 0.531238E+09 | 0.00 | 0.58 |
June | 0.00 | 0.232600E+09 | 0.00 | 27923023.53 | 0.00 | 0.00 | 91866707.18 | 0.00 | 0.59 |
July | 0.00 | 0.671264E+09 | 0.00 | 886532.41 | 0.00 | 0.00 | 3195460.01 | 0.00 | 0.59 |
August | 0.00 | 0.477632E+09 | 0.00 | 16111158.33 | 0.00 | 0.00 | 47811648.18 | 0.00 | 0.59 |
September | 8009923.12 | 0.103477E+09 | 0.00 | 5315544.31 | 0.00 | 0.00 | 0.268898E+09 | 0.00 | 0.58 |
October | 0.00 | 8427114.38 | 0.00 | 80956837.24 | 0.00 | 0.00 | 0.526712E+09 | 0.00 | 0.58 |
November | 0.00 | 0.00 | 0.00 | 0.129281E+09 | 0.00 | 0.00 | 0.928985E+09 | 0.00 | 0.58 |
December | 0.00 | 0.00 | 0.00 | 96060455.55 | 0.00 | 0.00 | 0.120578E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.125671E+10 | 0.149732E+10 | 0.00 | 0.663507E+09 | 0.00 | 0.00 | 0.682679E+10 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 886532.41 | 0.00 | 0.00 | 3195460.01 | 0.00 | 0.58 |
Maximum of Months | 0.971966E+09 | 0.671264E+09 | 0.00 | 0.141125E+09 | 0.00 | 0.00 | 0.120578E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.838534E+09 | 0.00 | 0.00 | 0.351023E+12 | 0.00 | 6.30 |
February | 0.115025E+11 | 0.00 | 0.00 | 0.333157E+10 | 0.00 | 0.00 | 0.472932E+12 | 0.00 | 9.62 |
March | 0.499746E+09 | 0.00 | 0.00 | 0.680200E+10 | 0.00 | 0.00 | 0.735693E+12 | 0.00 | 18.76 |
April | 0.00 | 0.00 | 0.00 | 0.502999E+10 | 0.00 | 0.00 | 0.874144E+12 | 0.00 | 37.81 |
May | 1112888.18 | 22551425.63 | 0.00 | 0.621275E+09 | 0.00 | 0.00 | 0.290671E+12 | 0.00 | 15.36 |
June | 0.423569E+09 | 0.251847E+10 | 0.00 | 0.132143E+10 | 23102639.10 | 0.00 | 0.122973E+12 | 0.00 | 16.09 |
July | 0.00 | 0.131342E+11 | 0.00 | 0.255830E+09 | 0.00 | 0.00 | 0.305942E+11 | 0.00 | 4.32 |
August | 0.00 | 0.929973E+10 | 0.00 | 0.137193E+10 | 0.00 | 0.00 | 0.187885E+12 | 0.00 | 22.70 |
September | 0.00 | 90073634.88 | 0.00 | 0.616793E+09 | 0.00 | 0.00 | 0.234045E+12 | 0.00 | 21.48 |
October | 0.352295E+10 | 34777715.62 | 0.00 | 0.355049E+10 | 11414264.80 | 0.00 | 0.389192E+12 | 0.00 | 21.53 |
November | 0.206232E+09 | 0.00 | 0.00 | 0.692134E+10 | 0.00 | 0.00 | 0.704575E+12 | 0.00 | 21.11 |
December | 0.00 | 0.00 | 0.00 | 0.543045E+10 | 0.00 | 0.00 | 0.105063E+13 | 0.00 | 24.08 |
Annual Sum or Average | 0.161561E+11 | 0.250998E+11 | 0.00 | 0.360916E+11 | 34516903.90 | 0.00 | 0.544436E+13 | 0.00 | 18.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.255830E+09 | 0.00 | 0.00 | 0.305942E+11 | 0.00 | 4.32 |
Maximum of Months | 0.115025E+11 | 0.131342E+11 | 0.00 | 0.692134E+10 | 23102639.10 | 0.00 | 0.105063E+13 | 0.00 | 37.81 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.258229E+12 | 0.420934E+11 | 0.00 | 0.187257E+13 | 0.445904E+12 |
February | 0.395385E+12 | 0.374984E+11 | 0.00 | 0.197334E+13 | 0.633478E+12 |
March | 0.640784E+12 | 0.314247E+11 | 0.00 | 0.206662E+13 | 0.102796E+13 |
April | 0.681534E+12 | 0.209670E+11 | 0.00 | 0.181881E+13 | 0.139706E+13 |
May | 0.864069E+12 | 0.117627E+11 | 0.00 | 0.903628E+12 | 0.143584E+13 |
June | 0.834174E+12 | -698543389.7 | 0.00 | 0.119644E+11 | 0.297870E+13 |
July | 0.814677E+12 | -0.123544E+11 | 0.00 | -0.738725E+12 | 0.425176E+13 |
August | 0.783503E+12 | -0.574684E+10 | 0.00 | -0.267823E+12 | 0.444360E+13 |
September | 0.548865E+12 | 0.409786E+10 | 0.00 | 0.416762E+12 | 0.197756E+13 |
October | 0.526360E+12 | 0.156270E+11 | 0.00 | 0.108144E+13 | 0.171983E+13 |
November | 0.270427E+12 | 0.301582E+11 | 0.00 | 0.186089E+13 | 0.104456E+13 |
December | 0.203440E+12 | 0.361151E+11 | 0.00 | 0.246203E+13 | 0.939722E+12 |
Annual Sum or Average | 0.682145E+13 | 0.210945E+12 | 0.00 | 0.134615E+14 | 0.222960E+14 |
Minimum of Months | 0.203440E+12 | -0.123544E+11 | 0.00 | -0.738725E+12 | 0.445904E+12 |