Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:25
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2024-07-03 12:25:32
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 35084.92 | 757.44 | 757.44 |
Net Site Energy | 35084.92 | 757.44 | 757.44 |
Total Source Energy | 105979.64 | 2287.97 | 2287.97 |
Net Source Energy | 105979.64 | 2287.97 | 2287.97 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2464.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2063.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1006.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3429.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 941.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 79.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7919.46 |
Humidification | 1739.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 647.08 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 450.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 32620.06 | 2464.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10846.71 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2464.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2063.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 1006.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 56.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 3429.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 941.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 79.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7919.46 |
Humidification | General | 1739.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 647.08 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 450.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 2464.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2063.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 1006.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 3429.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 941.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 79.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7919.46 |
Humidification | Unassigned | 1739.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 647.08 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 450.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 187.89 | 53.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 704.23 | 53.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 187.89 | 53.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 704.23 | 53.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 32620.057 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 32620.057 | 100.00 |
Total On-Site and Utility Electric Sources | 32620.057 | 100.00 |
Total Electricity End Uses | 32620.057 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 10846.71 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 10846.71 | 100.00 |
Total Water End Uses | 10846.71 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 47.67 |
Time Setpoint Not Met During Occupied Cooling | 481.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5342.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS SZVAV FAN | AIRLOOP DATACENTER BASEMENT SYS11 FAN | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 11.6510 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 11.6510 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 11.6510 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.6510 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 11.6510 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.6510 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 11.6510 | 18.58 | 484.4232 | |
Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.6100 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-AUG-15:20 | 06-FEB-06:10 | - | - | - | - | - | - | - | - | - | - | 26-JUN-16:10 |
Heating | 0.00 | 1707687.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 389222.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235096.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 379135.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 83757.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 48194.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 33176.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2436855.34 | 1707687.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1707687.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 389222.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 379135.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 83757.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 48194.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 33176.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2671.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6533.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17769.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3187.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8307.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10860.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2980.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 252.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 5508.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1426.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 103307.72 | 2671.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 57.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 141.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 234.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 64.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 5.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 118.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 30.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2230.29 | 57.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 57.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 141.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 234.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 64.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 5.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 118.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 30.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2230.29 | 57.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 8.49 | 0.249505 | 0.300000 | 2.55 |
DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | 38.69 | 0.015433 | 0.500000 | 19.35 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 9.07 | 0.209800 | 0.300000 | 2.72 | 0.559466 | 0.500000 | 0.001816 | 0.000192 | 2.72 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 86.26 | 0.220498 | 0.300000 | 25.88 | 0.587993 | 0.500000 | 0.001728 | 0.004690 | 27.59 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 9.80 | 0.194156 | 0.300000 | 2.94 | 0.517750 | 0.500000 | 0.001962 | 0.001606 | 9.53 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.59 | 0.149805 | 0.300000 | 0.478263 | 0.399480 | 0.500000 | 0.002543 | 0.000237 | 1.41 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 2.00 | 0.076789 | 0.300000 | 0.601280 | 0.300000 | 0.500000 | 0.004962 | 0.000165 | 0.980340 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 2.29 | 0.104504 | 0.300000 | 0.685601 | 0.300000 | 0.500000 | 0.003646 | 0.000272 | 1.61 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 2.56 | 0.060129 | 0.300000 | 0.767879 | 0.300000 | 0.500000 | 0.006336 | 0.000136 | 0.809164 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 20.79 | 0.114883 | 0.300000 | 6.24 | 0.306355 | 0.500000 | 0.003316 | 0.003500 | 20.79 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 21.17 | 0.300000 | 0.500000 | 0.005241 | 0.002370 | 14.08 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 22.40 | 0.106637 | 0.300000 | 6.72 | 0.300000 | 0.500000 | 0.003573 | 0.003567 | 21.19 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 23.87 | 0.064468 | 0.300000 | 7.16 | 0.300000 | 0.500000 | 0.005910 | 0.002288 | 13.59 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 2.81 | 0.084955 | 0.300000 | 0.843343 | 0.300000 | 0.500000 | 0.004485 | 0.000473 | 2.81 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 2.13 | 0.072158 | 0.300000 | 0.639871 | 0.300000 | 0.500000 | 0.005280 | 0.000316 | 1.88 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 2.85 | 0.083734 | 0.300000 | 0.855655 | 0.300000 | 0.500000 | 0.004550 | 0.000480 | 2.85 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 2.61 | 0.059008 | 0.300000 | 0.782466 | 0.300000 | 0.500000 | 0.006457 | 0.000312 | 1.85 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 21987.86 | 0.000192 | 443.58 | |
CORE_MID VAV BOX REHEAT COIL | 536132.60 | 0.004690 | 12555.29 | |
CORE_TOP VAV BOX REHEAT COIL | 183626.35 | 0.001606 | 4290.33 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 27107.87 | 0.000237 | 633.24 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 18879.69 | 0.000165 | 441.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 31093.44 | 0.000272 | 726.28 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 15591.85 | 0.000136 | 364.26 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 400071.27 | 0.003500 | 9343.34 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 270919.25 | 0.002370 | 6326.95 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 407697.08 | 0.003567 | 9521.35 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 261516.55 | 0.002288 | 6107.45 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 54078.57 | 0.000473 | 1262.82 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 36156.12 | 0.000316 | 844.29 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 54867.14 | 0.000480 | 1281.22 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 35670.90 | 0.000312 | 832.96 | |
VAV_BOT WITH REHEAT HEATING COIL | 66649.78 | 0.000583 | 1104.52 | |
VAV_MID WITH REHEAT HEATING COIL | 498116.06 | 0.004358 | 8400.42 | |
VAV_TOP WITH REHEAT HEATING COIL | 39862.64 | 0.000349 | 695.06 | |
CAV_BAS HEATING COIL | 0.000875 | 2620.43 | 100000.00 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 559092.26 | 0.000875 | 2620.43 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.925303 |
DATACENTER_MID_ZN_6 DIRECT AIR | 8.90 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.921118 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 8.75 | 5.25 | 17.51 | 5.89 | 14.93 | 14.93 | 0.300000 | 0.394347 | 14.93 |
VAV_MID WITH REHEAT | 87.25 | 52.35 | 174.49 | 97.23 | 138.43 | 138.43 | 0.300000 | 0.702359 | 138.43 |
VAV_TOP WITH REHEAT | 10.10 | 6.06 | 20.20 | 18.92 | 17.56 | 18.92 | 0.300000 | 1.00 | 18.92 |
CAV_BAS | 2.55 | 2.55 | 8.49 | 2.55 | 8.49 | 8.49 | 1.00 | 0.300000 | 8.49 |
AIRLOOP DATACENTER BASEMENT | 19.35 | 19.35 | 38.69 | 19.35 | 38.69 | 38.69 | 1.00 | 0.499996 | 38.69 |
AIRLOOP DATACENTER BOT | 0.925303 | 0.925303 | 0.925303 | 0.925303 | 0.925303 | 0.925303 | 1.00 | 1.00 | 0.925303 |
AIRLOOP DATACENTER MID | 8.90 | 8.90 | 8.90 | 8.90 | 8.90 | 8.90 | 1.00 | 1.000000 | 8.90 |
AIRLOOP DATACENTER TOP | 0.921118 | 0.921118 | 0.921118 | 0.921118 | 0.921118 | 0.921118 | 1.00 | 1.00 | 0.921118 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 14.93 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 138.43 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 18.92 | |
CAV_BAS_OA_CONTROLLER | 8.49 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 38.69 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.925303 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 8.90 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.921118 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.35 | 6.67 | 10.70 | 0.007041 | 0.007041 | 217599.54 | 0.007772 | 14.93 |
VAV_MID WITH REHEAT COOLING COIL | 25.46 | 6.67 | 10.70 | 0.007030 | 0.007030 | 2032555.51 | 0.072598 | 138.43 |
VAV_TOP WITH REHEAT COOLING COIL | 25.15 | 6.67 | 10.71 | 0.007028 | 0.007028 | 271733.53 | 0.009706 | 18.92 |
CAV_BAS COOLING COIL | 25.25 | 6.67 | 10.68 | 0.007144 | 0.007144 | 122974.27 | 0.004392 | 8.49 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 27.06 | 6.67 | 14.85 | 0.007019 | 0.007019 | 456935.54 | 0.016321 | 38.69 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 14.93 |
VAV_MID WITH REHEAT FAN | 138.43 |
VAV_TOP WITH REHEAT FAN | 18.92 |
CAV_BAS SZVAV FAN | 8.49 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | 38.69 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007772 | 0.000061 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000583 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.072598 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.004358 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.009706 | 0.000049 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000349 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | Design Size Minimum Supply Air Temperature [C] | User-Specified Minimum Supply Air Temperature [C] | User-Specified Maximum Supply Air Temperature [C] | User-Specified Nominal Cooling Capacity [W] | Design Size Maximum Supply Air Temperature [C] | |
CAV_BAS_UNITARY_PACKAGE_DX | 8.49 | 8.49 | 8.49 | 2.55 | 122974.27 | 100000.00 | 1.00 | 5.34 | 12.89 | 32.11 | ||
AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | 38.69 | 38.69 | 38.69 | 19.35 | 456935.54 | 100000.00 | 1.00 | 15.89 | 29.11 | |||
AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | 0.925303 | 0.925303 | 0.925303 | 0.925303 | 26730.58 | 1.00 | 15317.05 | 29.11 | ||||
AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | 8.90 | 8.90 | 8.90 | 8.90 | 257305.99 | 1.00 | 147380.87 | 29.11 | ||||
AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | 0.921118 | 0.921118 | 0.921118 | 0.921118 | 26610.93 | 1.00 | 15247.77 | 29.11 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000257 | 0.000037 | 96450.70 | 100000.00 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | 0.925303 | 1537.85 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | 8.90 | 15310.42 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | 0.921118 | 1530.90 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
AIRLOOP DATACENTER BOT COOLING COIL | 0.925300 | 0.462651 | 0.616867 | 15317.05 | 7658.52 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER MID COOLING COIL | 8.90 | 4.45 | 5.94 | 147380.87 | 73690.43 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.921120 | 0.460559 | 0.614080 | 15247.77 | 7623.89 | 0.800660 | 0.800660 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BOT HEATING COIL | 26730.58 |
AIRLOOP DATACENTER MID HEATING COIL | 257305.99 |
AIRLOOP DATACENTER TOP HEATING COIL | 26610.93 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.110789 | 22829.54 | |
HEATSYS1 PUMP | 0.027645 | 8325.54 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.110789 | 13.29 |
HEATSYS1 | 0.027645 | 3.32 |
COOLSYS1_SUPPLY | 0.110789 | 13.29 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.110789 | 0.110789 | 465037.24 | 6.67 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3160025.02 | 3160025.02 | 0.027645 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.055395 | 10536.88 |
COOLSYS1 CHILLER2 PUMP | 0.055395 | 10536.88 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.110789 | 0.056080 | 1570090.66 | 1570096.54 | 0.078688 |
COOLSYS1 CHILLER2 | 0.110789 | 0.056080 | 1570090.66 | 1570096.54 | 0.078688 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.157375 | 18.89 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.157375 | 54876.99 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 78.13 | 1881963.43 | 15.63 | 235245.43 |
TOWERWATERSYS COOLTOWER 2 | 78.13 | 1881963.43 | 15.63 | 235245.43 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 11.651 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 16.493 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 11.651 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 496.074 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 32383.100 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 32383.100 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 9130.649 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 9130.649 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
26 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
27 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
35 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
47 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
48 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
49 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
50 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
51 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
52 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
53 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
54 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
55 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
56 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
57 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
58 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
59 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
60 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
61 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
62 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
63 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
64 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
65 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
66 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
67 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
68 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
69 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
70 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
71 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
72 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
73 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
74 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
75 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
76 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
77 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
78 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
79 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
80 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
81 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
82 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
83 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
84 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
85 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
86 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
87 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
88 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
89 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
90 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
91 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
92 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
93 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
94 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
95 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
96 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
97 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
98 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
99 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
100 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
101 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
102 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
103 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
104 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
105 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
106 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
107 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
108 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
109 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
110 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
111 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
112 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
113 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
114 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
115 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
116 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
117 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
118 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
119 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
120 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
121 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone BASEMENT | 1.2500 |
3 | Zone CORE_BOTTOM | 1.2500 |
4 | Zone CORE_MID | 1.2500 |
5 | Zone CORE_TOP | 1.2500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.2500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.2500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.2500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone BASEMENT | 1.1500 |
3 | Zone CORE_BOTTOM | 1.1500 |
4 | Zone CORE_MID | 1.1500 |
5 | Zone CORE_TOP | 1.1500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.1500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.1500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.1500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 82265.74354 | 94605.60507 | 7.38131 | 8.48850 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90000 | 9.55238E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 87867.17011 | 101047.24563 | 7.88348 | 9.06600 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -17.90000 | 9.55238E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 836179.55231 | 961606.48516 | 75.00995 | 86.26145 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 250493.86505 | 313117.33131 | 22.06878 | 27.58598 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 94156.27618 | 108279.71761 | 8.51867 | 9.79647 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90000 | 5.47527E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 85289.59742 | 106611.99678 | 7.62106 | 9.52633 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 15322.74423 | 17621.15587 | 1.38627 | 1.59421 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.90000 | 5.47527E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 12586.83890 | 15733.54863 | 1.12584 | 1.40730 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 19264.20209 | 22153.83241 | 1.74284 | 2.00427 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 25.29133 | 5.46218E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 8764.92136 | 10956.15171 | 0.78427 | 0.98034 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 21965.60508 | 25260.44584 | 1.98725 | 2.28534 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 33.28333 | 5.47432E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 14433.87189 | 18042.33986 | 1.29177 | 1.61472 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 24601.86290 | 28292.14234 | 2.22574 | 2.55960 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 7241.72707 | 9052.15884 | 0.64733 | 0.80916 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 145991.96268 | 167890.75708 | 13.20790 | 15.18909 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.90000 | 5.47527E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 185665.87964 | 232082.34955 | 16.63053 | 20.78816 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 203492.38618 | 234016.24410 | 18.40978 | 21.17125 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 26.17933 | 5.46350E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 125720.86688 | 157151.08360 | 11.26277 | 14.07847 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 215264.99622 | 247554.74565 | 19.47497 | 22.39621 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 33.40667 | 5.47451E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 189199.70345 | 236499.62931 | 16.94807 | 21.18508 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 229461.29343 | 263880.48744 | 20.75917 | 23.87305 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 121362.86577 | 151703.58221 | 10.87134 | 13.58917 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 17956.77017 | 20650.28569 | 1.62454 | 1.86822 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90000 | 5.47527E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 25089.35487 | 31361.69359 | 2.24891 | 2.81114 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 20501.00972 | 23576.16118 | 1.85470 | 2.13290 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 27.01800 | 5.46476E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 16773.85135 | 20967.31419 | 1.50366 | 1.87957 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 24649.14843 | 28346.52069 | 2.22999 | 2.56448 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.47489E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 25454.82575 | 31818.53219 | 2.28175 | 2.85218 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 25069.67214 | 28830.12296 | 2.26802 | 2.60822 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 16548.86698 | 20686.08372 | 1.48347 | 1.85434 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8893.40208 | 10227.41240 | 0.80461 | 0.92530 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 28.49800 | 5.46700E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 | -17.90000 | 9.55238E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 85572.08292 | 98407.89536 | 7.74198 | 8.90328 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 28.49800 | 5.46700E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -17.90000 | 9.55238E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8853.17521 | 10181.15149 | 0.80097 | 0.92112 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 28.86800 | 5.46756E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 | -17.90000 | 9.55238E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 371897.70089 | 427682.35602 | 33.64599 | 38.69289 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 20.43200 | 5.45503E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:50:00 | -17.90000 | 9.55238E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 182689.85 | 14.93444 | 14.93444 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 63035.74 | 5.88935 | 5.88935 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1700326.20 | 138.42891 | 138.42891 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 613501.84 | 97.22686 | 97.22686 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 211142.30 | 17.56476 | 17.56476 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 61340.15 | 18.92356 | 18.92356 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:00:00 |
7 | CAV_BAS | Cooling | Sensible | 93205.93 | 8.48850 | 8.48850 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 58950.66 | 1.20016 | 1.20016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 424080.14 | 38.69324 | 38.69324 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 15624.47 | 0.33839 | 0.33839 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 10119.87 | 0.92530 | 0.92530 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 721.79 | 1.56323E-002 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 97381.81 | 8.90328 | 8.90328 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 7217.86 | 0.15632 | 0.15632 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 10079.88 | 0.92112 | 0.92112 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 721.79 | 1.56323E-002 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 8.48850 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.24950 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 2.54655 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.06600 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20980 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.71980 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55947 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.81602E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.92359E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.71980 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21987.86466 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.92359E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 443.58407 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 86.26145 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22050 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 25.87843 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58799 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.72791E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.69032E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 27.58598 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 536132.59796 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.69032E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 12555.28673 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.79647 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19416 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.93894 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51775 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.96234E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.60644E-003 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.52633 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 183626.35422 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.60644E-003 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4290.32987 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.59421 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14980 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.47826 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39948 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54331E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.37151E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.40730 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27107.86878 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.37151E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 633.23873 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.00427 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.67888E-002 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.60128 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.96166E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.65168E-004 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.98034 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18879.69137 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.65168E-004 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 441.00334 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.28534 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10450 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.68560 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.64581E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.72019E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61472 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 31093.43644 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.72019E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 726.27821 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.55960 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.01286E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76788 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.33641E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.36404E-004 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.80916 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15591.85156 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.36404E-004 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 364.26060 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 20.78816 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11488 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.23645 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30635 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.31642E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.50000E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 20.78816 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 400071.26916 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.50000E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 9343.33743 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 21.17125 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.24105E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.37012E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 14.07847 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 270919.24648 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.37012E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6326.94881 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 22.39621 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10664 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.71886 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.57288E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.56671E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 21.18508 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 407697.08291 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.56671E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 9521.34727 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 23.87305 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.44681E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 7.16191 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.90990E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.28786E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 13.58917 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 261516.55032 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.28786E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6107.44594 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.81114 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.49550E-002 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.84334 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.48473E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.73103E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.81114 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 54078.56959 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.73103E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1262.81644 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.13290 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.21575E-002 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63987 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.28011E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.16309E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.87957 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 36156.11523 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.16309E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 844.28954 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.85218 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.37344E-002 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.85565 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.55010E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.80002E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.85218 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 54867.14354 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.80002E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1281.22494 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.60822 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.90077E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78247 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.45679E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.12065E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.85434 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 35670.89626 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.12065E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 832.96054 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.92530 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 8.90328 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.92112 |
215 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 38.69289 |
216 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 1.54334E-002 |
217 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
218 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 19.34644 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 8.75470 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.25282 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 17.50941 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.88935 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 14.93444 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 14.93444 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.39435 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 87.24506 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 52.34704 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 174.49012 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 97.22686 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 138.42891 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 138.42891 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.70236 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 10.10046 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.06027 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 20.20092 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 18.92356 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 17.56476 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 18.92356 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 1.00000 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.54655 |
244 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.54655 |
245 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.48850 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.54655 |
247 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.48850 |
248 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 8.48850 |
249 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.30000 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 19.34644 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 19.34644 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 38.69289 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 19.34644 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 38.69324 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 38.69324 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.50000 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.92530 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.92530 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.92530 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.92530 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.92530 |
264 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.92530 |
265 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 8.90328 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 8.90328 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.90328 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 8.90328 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.90328 |
272 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 8.90328 |
273 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
274 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.92112 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.92112 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.92112 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.92112 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.92112 |
280 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.92112 |
281 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
282 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
283 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 14.93444 |
284 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 138.42891 |
285 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 18.92356 |
286 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 8.48850 |
287 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 38.69324 |
288 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.92530 |
289 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 8.90328 |
290 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.92112 |
291 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 14.93444 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.34512 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.70103 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.04105E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.04105E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 217599.53985 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.77215E-003 |
299 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 14.93444 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 66649.78457 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.83081E-004 |
302 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1104.52408 |
303 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 14.93444 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.77215E-003 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.12688E-005 |
306 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.83081E-004 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 138.42891 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.45866 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.70098 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.03002E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.03002E-003 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2032555.51213 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.25982E-002 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 138.42891 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 498116.05667 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.35774E-003 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 8400.41704 |
319 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 138.42891 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.25982E-002 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.55926E-006 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.35774E-003 |
323 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 18.92356 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.14509 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.71249 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.02770E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.02770E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 271733.53156 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.70569E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 18.92356 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 39862.63721 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.48736E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 695.05663 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 18.92356 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.70569E-003 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.90630E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.48736E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.48850 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 8.48850 |
342 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 8.48850 |
343 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.48850 |
344 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.54655 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.24520 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68041 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.14440E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.14440E-003 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 122974.27057 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.39236E-003 |
352 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.48850 |
353 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 122974.27057 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
355 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
356 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2620.42996 |
357 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
358 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
359 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Minimum Supply Air Temperature [C] | 5.34202 |
360 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 12.88890 |
361 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 32.11110 |
362 | Fan:VariableVolume | CAV_BAS SZVAV FAN | Design Size Maximum Flow Rate [m3/s] | 8.48850 |
363 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 38.69324 |
364 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
365 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 38.69324 |
366 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 38.69324 |
367 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 38.69324 |
368 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 19.34662 |
369 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.05812 |
370 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
371 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 14.85094 |
372 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.01933E-003 |
373 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.01933E-003 |
374 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Coil Load [W] | 456935.54093 |
375 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.63207E-002 |
376 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 38.69324 |
377 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 456935.54093 |
378 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Capacity [W] | 559092.26106 |
379 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
380 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
381 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2620.42996 |
382 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
383 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
384 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 15.88890 |
385 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 29.11110 |
386 | Fan:VariableVolume | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Design Size Maximum Flow Rate [m3/s] | 38.69324 |
387 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.57271E-004 |
388 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
389 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
390 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
391 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.92530 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
393 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.92530 |
394 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1537.85071 |
395 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.92530 |
396 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.92530 |
397 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.92530 |
398 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.92530 |
399 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.92530 |
400 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.46265 |
401 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.61687 |
402 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 15317.05000 |
403 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7658.52500 |
404 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
405 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
406 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15317.05000 |
407 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26730.58177 |
408 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
409 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
410 | Coil:Heating:Fuel | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Nominal Capacity [W] | 26730.58177 |
411 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.90328 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
413 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 8.90328 |
414 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 15310.42405 |
415 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 8.90328 |
416 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 8.90328 |
417 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.90328 |
418 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 8.90328 |
419 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 8.90328 |
420 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 4.45164 |
421 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.93552 |
422 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 147380.87000 |
423 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 73690.43500 |
424 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
425 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
426 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 147380.87000 |
427 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 257305.99090 |
428 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
429 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
430 | Coil:Heating:Fuel | AIRLOOP DATACENTER MID HEATING COIL | Design Size Nominal Capacity [W] | 257305.99090 |
431 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.92112 |
432 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
433 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.92112 |
434 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1530.89518 |
435 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.92112 |
436 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.92112 |
437 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.92112 |
438 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.92112 |
439 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.92112 |
440 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.46056 |
441 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.61408 |
442 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 15247.77000 |
443 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7623.88500 |
444 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
445 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
446 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15247.77000 |
447 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26610.92524 |
448 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
449 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
450 | Coil:Heating:Fuel | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Nominal Capacity [W] | 26610.92524 |
451 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.11079 |
452 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 22829.53597 |
453 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.11079 |
454 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 13.29469 |
455 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.11079 |
456 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.11079 |
457 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 465037.24064 |
458 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 6.67000 |
459 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.76453E-002 |
460 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 3.31743 |
461 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.76453E-002 |
462 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 8325.54351 |
463 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
464 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3160025.01694 |
465 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 3160025.02000 |
466 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.76453E-002 |
467 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.11079 |
468 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 13.29469 |
469 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 5.53945E-002 |
470 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 10536.87776 |
471 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 5.53945E-002 |
472 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 10536.87776 |
473 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.11079 |
474 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.60800E-002 |
475 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1570090.66346 |
476 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1570096.54500 |
477 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 7.86877E-002 |
478 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.11079 |
479 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.60800E-002 |
480 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1570090.66346 |
481 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1570096.54500 |
482 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 7.86877E-002 |
483 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
484 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
485 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
486 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
487 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
488 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.15738 |
489 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 18.88505 |
490 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.15738 |
491 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 54876.99010 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 78.13291 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1881963.43117 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 15.62658 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 235245.42890 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 78.13291 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1881963.43117 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 15.62658 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 235245.42890 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 20879.40 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 508823.03 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 174273.91 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 25727.23 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 17918.13 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 29509.81 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 14797.73 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 379695.35 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 257121.15 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 386932.78 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 248197.33 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 51324.32 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 34314.67 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 52072.74 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 33854.16 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 51943.73 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 402108.15 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 34312.30 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94850.22 |
20 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | 94850.22 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 297617.88 | 194312.81 | 103305.07 | 0.65 | 34227.57 | 347.15 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2768338.34 | 1804678.32 | 963660.02 | 0.65 | 317752.11 | 3222.82 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 374351.10 | 245163.19 | 129187.91 | 0.65 | 43151.12 | 437.66 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 168945.77 | 110395.93 | 58549.84 | 0.65 | 19515.78 | 197.94 |
5 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | 568651.42 | 397067.53 | 171583.88 | 0.70 | 48329.05 | 490.18 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | 14591.9 | 9.16 | 9.16 | |||
2 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | 140403.3 | 10.40 | 10.40 | |||
3 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | 14525.9 | 9.16 | 9.16 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 6.37 | 21.74 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 6.37 | 21.74 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.7981251702E-003 | 1.5269115520E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1054005604 | 0.2005309828 | Pass | Pass | 0.1329962608 | 0.3379655308 | Pass | Fail |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1159377131 | 9.1243138185E-002 | Pass | Pass | 0.3640971178 | 0.4803121249 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.0912838659E-002 | 4.7591882969E-002 | Pass | Pass | 1.2335757073 | 7.6590925687 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 9.4959239336E-002 | 0.1531079387 | Pass | Pass | 0.1331006257 | 0.3357249769 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2418069799 | 0.3891875180 | Pass | Pass | 0.1392454345 | 0.3468870578 | Pass | Fail |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3384387936 | 0.5618342942 | Pass | Pass | 0.1394169186 | 0.3419457732 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2436723151 | 0.4297597251 | Pass | Pass | 0.1344768534 | 0.3306361893 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1521994420 | 0.1998010064 | Pass | Pass | 0.5155037987 | 0.7351857949 | Fail | Fail |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1908796912 | 0.2141076592 | Pass | Pass | 0.6728955820 | 2.7172207296 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3523989922 | 0.4362914586 | Pass | Pass | 0.4396762302 | 0.7232112541 | Fail | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1656591794 | 0.1990622994 | Pass | Pass | 0.7961937482 | 2.9021523427 | Fail | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4195587585 | 0.4853775663 | Pass | Pass | 3.4264429672 | 33.1393172201 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3622729436 | 0.4244477061 | Pass | Pass | 0.7598474282 | 1.5795430934 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4178518619 | 0.4414888933 | Pass | Pass | 0.6609237998 | 1.0123022263 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2768068036 | 0.3303540579 | Pass | Pass | 1.3208849513 | 8.1136939119 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.0906802954E-002 | 3.8759854884E-002 | Pass | Pass | 0.1759706720 | 0.4163036865 | Fail | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.1894897294E-002 | 5.7966068013E-002 | Pass | Pass | 0.3954344039 | 0.5078142961 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.2105565864 | 0.1778106167 | Pass | Pass | 0.5908300706 | 0.8027271159 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.3237801536E-006 | 3.3069047619E-006 | Pass | Pass | 1.2342345703E-002 | 1.2410459764E-002 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.1957385011E-003 | 5.6174762061E-003 | Pass | Pass | 0.1810039060 | 1.1441888874 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.8456347509E-002 | 3.1542002195E-002 | Pass | Pass | 4.2127619982E-002 | 0.1174248219 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.4849705282E-002 | 2.5985521667E-002 | Pass | Pass | 1.7185408039E-003 | 1.4488105436E-003 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7807.16 | 184.27 | 0.00 | 30661.69 | 16048.97 | 54702.09 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
North Total or Average | 1390.74 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 3.241 | 0.391 | 0.431 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 11.6510 | 2779.43 | 32383.10 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 333.79 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.6510 | 24961.20 | 290822.99 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 2997.66 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.6510 | 3134.13 | 36515.73 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.6510 | 3134.20 | 36516.53 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 11.6510 | 783.68 | 9130.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 94.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 22.3674 | 362.03 | 8097.60 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 83.47 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
Interior Lighting Total | 11.7515 | 46320.38 | 544334.28 | 1723.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 64082.80 | AstronomicalClock | - | 83.67 | 83.67 | 1006.50 | |
Exterior Lighting Total | 64082.80 | 1006.50 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3093716.44 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 3160025.02 | 0.79 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1570096.54 | 6.11 | 1562435.33 | 6.08 | 6.37 | 21.74 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1570096.54 | 6.11 | 1562435.33 | 6.08 | 6.37 | 21.74 |
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1881963.43 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1881963.43 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 217599.54 | 297617.88 | 194312.81 | 103305.07 | 0.65 | - | 34227.57 | 347.15 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2032555.51 | 2768338.34 | 1804678.32 | 963660.02 | 0.65 | - | 317752.11 | 3222.82 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 271733.53 | 374351.10 | 245163.19 | 129187.91 | 0.65 | - | 43151.12 | 437.66 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 122974.27 | 168945.77 | 110395.93 | 58549.84 | 0.65 | - | 19515.78 | 197.94 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | 456935.54 | 568651.42 | 397067.53 | 171583.88 | 0.70 | - | 48329.05 | 490.18 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15317.05 | 12263.75 | 3053.30 | 0.80 | 3.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | 147380.87 | 118001.97 | 29378.90 | 0.80 | 3.50 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15247.77 | 12208.28 | 3039.49 | 0.80 | 3.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
AIRLOOP DATACENTER BOT COOLING COIL | 14591.9 | 9.16 | 9.16 | ||||
AIRLOOP DATACENTER MID COOLING COIL | 140403.3 | 10.40 | 10.40 | ||||
AIRLOOP DATACENTER TOP COOLING COIL | 14525.9 | 9.16 | 9.16 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 21987.86 | 20879.40 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 536132.60 | 508823.03 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 183626.35 | 174273.91 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 27107.87 | 25727.23 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 18879.69 | 17918.13 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 31093.44 | 29509.81 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 15591.85 | 14797.73 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 400071.27 | 379695.35 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 270919.25 | 257121.15 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 407697.08 | 386932.78 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 261516.55 | 248197.33 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 54078.57 | 51324.32 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 36156.12 | 34314.67 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 54867.14 | 52072.74 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 35670.90 | 33854.16 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 66649.78 | 51943.73 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 498116.06 | 402108.15 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 39862.64 | 34312.30 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94850.22 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | 100000.00 | 94850.22 | - |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | 26730.58 | 0.80 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | 257305.99 | 0.79 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | 26610.93 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 14.93 | 32510.03 | 2176.85 | 1.00 | 1.11 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 138.43 | 301338.95 | 2176.85 | 1.00 | 1.08 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1337.13 | 18.92 | 40976.94 | 2165.39 | 1.00 | 1.11 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
CAV_BAS SZVAV FAN | Fan:VariableVolume | 0.61 | 1337.13 | 8.49 | 18655.87 | 2197.78 | 1.00 | 1.12 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 0.62 | 637.69 | 38.69 | 39958.30 | 1032.69 | 1.00 | 1.20 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 0.93 | 1537.85 | 1662.00 | 1.00 | 1.35 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 8.90 | 15310.42 | 1719.64 | 1.00 | 1.08 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 0.92 | 1530.90 | 1662.00 | 1.00 | 1.36 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.83 | 0.110789 | 22829.54 | 206063.11 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.027645 | 8325.54 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.055395 | 10536.88 | 190215.15 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.055395 | 10536.88 | 190215.15 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 209234.68 | 0.157375 | 54876.99 | 348701.22 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 82265.74 | 94605.61 | 34.04 | 7.381 | 8.489 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00742 | 22.95 | 0.00546 | 1.200 | 0.00 |
CORE_BOTTOM | 87867.17 | 101047.25 | 40.48 | 7.883 | 9.066 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00735 | 22.95 | 0.00546 | 1.078 | 0.00 |
CORE_MID | 836179.55 | 961606.49 | 385.24 | 75.010 | 86.261 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00737 | 22.95 | 0.00546 | 10.778 | 0.00 |
CORE_TOP | 94156.28 | 108279.72 | 43.38 | 8.519 | 9.796 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00732 | 33.90 | 0.00548 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 15322.74 | 17621.16 | 56.22 | 1.386 | 1.594 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00722 | 33.90 | 0.00548 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 19264.20 | 22153.83 | 109.69 | 1.743 | 2.004 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00711 | 25.29 | 0.00546 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 21965.61 | 25260.45 | 80.60 | 1.987 | 2.285 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00715 | 33.28 | 0.00547 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 24601.86 | 28292.14 | 140.08 | 2.226 | 2.560 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00709 | 32.03 | 0.00547 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 145991.96 | 167890.76 | 535.69 | 13.208 | 15.189 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00720 | 33.90 | 0.00548 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 203492.39 | 234016.24 | 1158.64 | 18.410 | 21.171 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00709 | 26.18 | 0.00546 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 215265.00 | 247554.75 | 789.85 | 19.475 | 22.396 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00713 | 33.41 | 0.00547 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 229461.29 | 263880.49 | 1306.50 | 20.759 | 23.873 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00708 | 31.83 | 0.00547 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 17956.77 | 20650.29 | 65.89 | 1.625 | 1.868 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00715 | 33.90 | 0.00548 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 20501.01 | 23576.16 | 116.73 | 1.855 | 2.133 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00708 | 27.02 | 0.00546 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 24649.15 | 28346.52 | 90.44 | 2.230 | 2.564 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00711 | 33.65 | 0.00547 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 25069.67 | 28830.12 | 142.74 | 2.268 | 2.608 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00707 | 32.03 | 0.00547 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8893.40 | 10227.41 | 282.50 | 0.805 | 0.925 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00706 | 28.50 | 0.00547 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 85572.08 | 98407.90 | 2718.24 | 7.742 | 8.903 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00707 | 28.50 | 0.00547 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8853.18 | 10181.15 | 281.23 | 0.801 | 0.921 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00706 | 28.87 | 0.00547 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 371897.70 | 427682.36 | 545.74 | 33.646 | 38.693 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00703 | 20.43 | 0.00546 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 23.55 | 0.00096 | -17.90 | 0.00096 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 17.60 | 21.23 | 0.00096 | -17.90 | 0.00096 | 1.078 | 0.00 |
CORE_MID | 250493.87 | 313117.33 | 125.44 | 22.069 | 27.586 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 10.778 | 0.00 |
CORE_TOP | 85289.60 | 106612.00 | 42.71 | 7.621 | 9.526 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12586.84 | 15733.55 | 50.20 | 1.126 | 1.407 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 8764.92 | 10956.15 | 54.25 | 0.784 | 0.980 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -17.90 | 0.00096 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 14433.87 | 18042.34 | 57.57 | 1.292 | 1.615 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 7241.73 | 9052.16 | 44.82 | 0.647 | 0.809 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -17.90 | 0.00096 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 185665.88 | 232082.35 | 740.50 | 16.631 | 20.788 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -17.90 | 0.00096 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 125720.87 | 157151.08 | 778.07 | 11.263 | 14.078 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -17.90 | 0.00096 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 189199.70 | 236499.63 | 754.58 | 16.948 | 21.185 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -17.90 | 0.00096 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 121362.87 | 151703.58 | 751.10 | 10.871 | 13.589 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -17.90 | 0.00096 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 25089.35 | 31361.69 | 100.07 | 2.249 | 2.811 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16773.85 | 20967.31 | 103.81 | 1.504 | 1.880 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -17.90 | 0.00096 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 25454.83 | 31818.53 | 101.52 | 2.282 | 2.852 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16548.87 | 20686.08 | 102.42 | 1.483 | 1.854 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -17.90 | 0.00096 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 | 18.00 | 24.98 | 0.00179 | -17.90 | 0.00096 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 22.72 | 0.00179 | -17.90 | 0.00096 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 | 18.00 | 19.48 | 0.00179 | -17.90 | 0.00096 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 09:50:00 | 18.00 | 27.00 | 0.00700 | -17.90 | 0.00096 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 14.93 | 14.93 | 5.89 | 5.89 | 14.9344 | 5.8893 | 14.9344 | 0.3943 | 0.3000 |
VAV_MID WITH REHEAT | 138.43 | 138.43 | 97.23 | 97.23 | 138.4289 | 97.2269 | 138.4289 | 0.7024 | 0.3000 |
VAV_TOP WITH REHEAT | 17.56 | 17.56 | 18.92 | 18.92 | 17.5648 | 18.9236 | 18.9236 | 1.0000 | 0.3000 |
CAV_BAS | 8.49 | 8.49 | 1.20 | 1.20 | 8.4885 | 2.5466 | 8.4885 | 0.3000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 38.69 | 38.69 | 0.34 | 0.34 | 38.6932 | 19.3464 | 38.6932 | 0.5000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.93 | 0.93 | 0.02 | 0.02 | 0.9253 | 0.9253 | 0.9253 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 8.90 | 8.90 | 0.16 | 0.16 | 8.9033 | 8.9033 | 8.9033 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.92 | 0.92 | 0.02 | 0.02 | 0.9211 | 0.9211 | 0.9211 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 21987.865 | 21987.865 | 2.719800 | 0.00019236 | 443.584 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 21987.86 | 21987.86 | 2.719800 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 22097.43 | 22097.43 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 536132.598 | 536132.598 | 27.585981 | 0.00469032 | 12555.287 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 536132.60 | 536132.60 | 27.585981 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 313117.33 | 0.00 | 538588.09 | 538588.09 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 183626.354 | 183626.354 | 9.526328 | 0.00160644 | 4290.330 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 183626.35 | 183626.35 | 9.526328 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 106612.00 | 0.00 | 184468.14 | 184468.14 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 27107.869 | 27107.869 | 1.407300 | 0.00023715 | 633.239 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 27107.87 | 27107.87 | 1.407300 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00789307 | 41.4267 | 15733.55 | 0.00 | 27232.15 | 27232.15 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 18879.691 | 18879.691 | 0.980340 | 0.00016517 | 441.003 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18879.69 | 18879.69 | 0.980340 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00789796 | 41.4520 | 10956.15 | 0.00 | 18966.25 | 18966.25 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 31093.436 | 31093.436 | 1.614717 | 0.00027202 | 726.278 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 31093.44 | 31093.44 | 1.614717 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00790678 | 41.4977 | 18042.34 | 0.00 | 31235.99 | 31235.99 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 15591.852 | 15591.852 | 0.809164 | 0.00013640 | 364.261 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15591.85 | 15591.85 | 0.809164 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00787413 | 41.3286 | 9052.16 | 0.00 | 15663.33 | 15663.33 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 400071.269 | 400071.269 | 20.788158 | 0.00350000 | 9343.337 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 400071.27 | 398277.26 | 20.788158 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00783128 | 41.1076 | 232082.35 | 0.00 | 401905.62 | 401905.62 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 270919.246 | 270919.246 | 14.078466 | 0.00237012 | 6326.949 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 270919.25 | 270919.25 | 14.078466 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00783369 | 41.1201 | 157151.08 | 0.00 | 272161.44 | 272161.44 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 407697.083 | 407697.083 | 21.185084 | 0.00356671 | 9521.347 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 407697.08 | 407697.08 | 21.185084 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00783433 | 41.1234 | 236499.63 | 0.00 | 409566.41 | 409566.41 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 261516.550 | 261516.550 | 13.589173 | 0.00228786 | 6107.446 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 261516.55 | 261516.55 | 13.589173 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00782810 | 41.0912 | 151703.58 | 0.00 | 262715.62 | 262715.62 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 54078.570 | 54078.570 | 2.811143 | 0.00047310 | 1262.816 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 54078.57 | 53858.27 | 2.811143 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00784357 | 41.1717 | 31361.69 | 0.00 | 54326.53 | 54326.53 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 36156.115 | 36156.115 | 1.879572 | 0.00031631 | 844.290 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 36156.12 | 36156.12 | 1.879572 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00784396 | 41.1738 | 20967.31 | 0.00 | 36321.90 | 36321.90 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 54867.144 | 54867.144 | 2.852182 | 0.00048000 | 1281.225 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 54867.14 | 54644.54 | 2.852182 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00784577 | 41.1831 | 31818.53 | 0.00 | 55118.72 | 55118.72 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 35670.896 | 35670.896 | 1.854336 | 0.00031206 | 832.961 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 35670.90 | 35670.90 | 1.854336 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00784209 | 41.1641 | 20686.08 | 0.00 | 35834.46 | 35834.46 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 217599.540 | -999.000 | 14.934440 | 0.00777215 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 217599.54 | 217599.54 | 14.934440 | 25.35 | 13.50 | 0.00704105 | 10.70 | 7.93 | 0.00704105 | 33.90 | 0.00547527 | 15.07 | 13.5961 | 24.00 | 0.00728747 | 31.9064 | 143522.26 | 0.00 | 190318.28 | 190318.28 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 66649.785 | 66649.785 | 4.480332 | 0.00058308 | 1104.524 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 66649.78 | 66649.78 | 4.480332 | -2.26 | -3.31 | 0.00314899 | 12.89 | 9.77 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 45.3203 | 19.28 | 0.00447065 | 26.2430 | 20237.57 | 0.00 | 62832.69 | 62832.69 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2032555.512 | -999.000 | 138.428913 | 0.07259817 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2032555.51 | 2032555.51 | 138.428913 | 25.46 | 13.53 | 0.00703002 | 10.70 | 7.92 | 0.00703002 | 33.90 | 0.00547527 | 15.07 | 14.6689 | 24.00 | 0.00729890 | 31.9558 | 1323729.02 | 0.00 | 1777309.96 | 1777309.96 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 498116.057 | 498116.057 | 41.528674 | 0.00435774 | 8400.417 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 498116.06 | 498116.06 | 41.528674 | 0.68 | -0.12 | 0.00432711 | 12.89 | 9.77 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 48.8963 | 18.41 | 0.00773139 | 47.6631 | 126796.33 | 0.00 | 486577.86 | 486577.86 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 271733.532 | -999.000 | 18.923561 | 0.00970569 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 271733.53 | 271733.53 | 18.923561 | 25.15 | 13.42 | 0.00702770 | 10.71 | 7.92 | 0.00702770 | 33.90 | 0.00547527 | 15.07 | 10.7300 | 24.00 | 0.00723095 | 31.6616 | 168583.65 | 0.00 | 236912.69 | 236912.69 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 39862.637 | 39862.637 | 5.677068 | 0.00034874 | 695.057 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 39862.64 | 39862.64 | 5.677068 | 5.74 | 3.74 | 0.00528568 | 12.89 | 9.77 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 35.7667 | 17.24 | 0.00789138 | 52.3552 | 12667.02 | 0.00 | 41532.60 | 41532.60 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 122974.271 | -999.000 | 8.488504 | 0.00439236 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 122974.27 | 120742.67 | 8.488504 | 25.25 | 13.55 | 0.00714440 | 10.68 | 7.88 | 0.00700000 | 31.98 | 0.00547231 | 14.44 | 14.1386 | 24.00 | 0.00745410 | 32.6278 | 73813.88 | 0.00 | 108690.59 | 108690.59 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.743149 | 0.00087484 | 2620.430 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 100000.00 | 100000.00 | 3.743149 | -2.53 | -7.04 | 0.00095524 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 32.0627 | 23.67 | 0.00095524 | 4.3102 | 0.00 | 0.00 | 100031.84 | 100031.84 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 456935.541 | -999.000 | 38.693236 | 0.01632068 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 456935.54 | 455901.99 | 38.693236 | 27.06 | 14.06 | 0.00701933 | 14.85 | 9.58 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | 0.8746 | 27.00 | 0.00703296 | 25.7789 | 371513.28 | 0.00 | 393995.97 | 393995.97 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 100000.000 | 100000.000 | 3.743149 | 0.00087484 | 2620.430 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 100000.00 | 100000.00 | 3.743149 | -0.16 | -0.16 | 0.00694714 | 29.11 | 15.52 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 9.0403 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | 100031.84 | 100031.84 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER BOT | 15317.050 | 12263.749 | 0.925300 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 7658.52 | 7625.79 | 0.616867 | 27.02 | 14.07 | 0.00703654 | 14.22 | 9.33 | 0.00700000 | 28.50 | 0.00546700 | 13.26 | 2.5342 | 27.00 | 0.00706352 | 25.8880 | 8893.40 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER BOT | 26730.582 | 26730.582 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 26730.58 | 26730.58 | 0.925303 | -0.30 | -4.37 | 0.00177439 | 29.11 | 15.52 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 1.6894 | 25.72 | 0.00178846 | 7.1291 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER MID | 147380.870 | 118001.967 | 8.903280 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 73690.43 | 73363.76 | 5.935520 | 27.03 | 14.07 | 0.00703791 | 14.16 | 9.31 | 0.00700000 | 28.50 | 0.00546700 | 13.26 | 2.6337 | 27.00 | 0.00706598 | 25.8970 | 85572.08 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER MID | 257305.991 | 257305.991 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 257305.99 | 257305.99 | 8.903278 | -0.31 | -4.38 | 0.00177386 | 29.11 | 15.52 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 1.7558 | 23.84 | 0.00178849 | 7.9755 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER TOP | 15247.770 | 12208.280 | 0.921120 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 7623.89 | 7591.22 | 0.614080 | 27.03 | 14.07 | 0.00703664 | 14.22 | 9.33 | 0.00700000 | 28.87 | 0.00546756 | 13.38 | 2.5457 | 27.00 | 0.00706373 | 25.8888 | 8853.18 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER TOP | 26610.925 | 26610.925 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 26610.93 | 26610.93 | 0.921118 | -0.30 | -4.37 | 0.00177342 | 29.11 | 15.52 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 1.6971 | 21.72 | 0.00178754 | 9.0671 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 21987.865 | 21987.865 | 2.719800 | 0.00019236 | 443.584 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 27.64245727 | 54.44 | 82.22 | 27.78 | 3223621.78 | 0.6821 | 0.695813 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | Sensible | 21987.86 | 21987.86 | 1.0000 | 2.65843435 | 2.719800 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.19233981 | 60.00 | 32.22 | 27.78 | 0.000 | 21987.86 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 22097.43 | 22097.43 | 2.65843435 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 20.95 | 14.83 | 0.00800000 | 41372.0 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 536132.598 | 536132.598 | 27.585981 | 0.00469032 | 12555.287 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 27.64245727 | 54.44 | 82.22 | 27.78 | 3223621.78 | 16.6314 | 16.966087 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 536132.60 | 536132.60 | 1.0000 | 26.96357533 | 27.585981 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 4.68984339 | 60.00 | 32.22 | 27.78 | 0.000 | 536132.60 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 313117.33 | 0.00 | 538588.09 | 538588.09 | 26.96357533 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.39 | 18.82 | 0.00800000 | 53034.5 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 183626.354 | 183626.354 | 9.526328 | 0.00160644 | 4290.330 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 27.64245727 | 54.44 | 82.22 | 27.78 | 3223621.78 | 5.6963 | 5.810915 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 183626.35 | 183626.35 | 1.0000 | 9.31139137 | 9.526328 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 1.60627958 | 60.00 | 32.22 | 27.78 | 0.000 | 183626.35 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 106612.00 | 0.00 | 184468.14 | 184468.14 | 9.31139137 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52870.8 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 27107.869 | 27107.869 | 1.407300 | 0.00023715 | 633.239 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 27.64245727 | 54.44 | 82.22 | 27.78 | 3223621.78 | 0.8409 | 0.857837 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 27107.87 | 27107.87 | 1.0000 | 1.37554835 | 1.407300 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.23712727 | 60.00 | 32.22 | 27.78 | 0.000 | 27107.87 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00789307 | 21.00 | 0.00789307 | 41.4267 | 15733.55 | 0.00 | 27232.15 | 27232.15 | 1.37554835 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52857.1 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18879.691 | 18879.691 | 0.980340 | 0.00016517 | 441.003 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 27.64245727 | 54.44 | 82.22 | 27.78 | 3223621.78 | 0.5857 | 0.597454 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 18879.69 | 18879.69 | 1.0000 | 0.95822133 | 0.980340 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.16515093 | 60.00 | 32.22 | 27.78 | 0.000 | 18879.69 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00789796 | 21.00 | 0.00789796 | 41.4520 | 10956.15 | 0.00 | 18966.25 | 18966.25 | 0.95822133 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52853.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 31093.436 | 31093.436 | 1.614717 | 0.00027202 | 726.278 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 27.64245727 | 54.44 | 82.22 | 27.78 | 3223621.78 | 0.9645 | 0.983962 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 31093.44 | 31093.44 | 1.0000 | 1.57828500 | 1.614717 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.27199120 | 60.00 | 32.22 | 27.78 | 0.000 | 31093.44 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00790678 | 21.00 | 0.00790678 | 41.4977 | 18042.34 | 0.00 | 31235.99 | 31235.99 | 1.57828500 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52850.9 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15591.852 | 15591.852 | 0.809164 | 0.00013640 | 364.261 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 27.64245727 | 54.44 | 82.22 | 27.78 | 3223621.78 | 0.4837 | 0.493409 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15591.85 | 15591.85 | 1.0000 | 0.79090703 | 0.809164 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.13639040 | 60.00 | 32.22 | 27.78 | 0.000 | 15591.85 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00787413 | 21.00 | 0.00787413 | 41.3286 | 9052.16 | 0.00 | 15663.33 | 15663.33 | 0.79090703 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52864.1 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 400071.269 | 400071.269 | 20.788158 | 0.00350000 | 9343.337 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 27.64245727 | 54.44 | 82.22 | 27.78 | 3223621.78 | 12.4106 | 12.660383 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 400071.27 | 398277.26 | 1.0000 | 20.31912751 | 20.788158 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 3.49964095 | 60.00 | 32.22 | 27.78 | 0.000 | 400071.27 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.94 | 0.00783128 | 21.00 | 0.00783128 | 41.1076 | 232082.35 | 0.00 | 401905.62 | 401905.62 | 20.31912751 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52839.5 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 270919.246 | 270919.246 | 14.078466 | 0.00237012 | 6326.949 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 27.64245727 | 54.44 | 82.22 | 27.78 | 3223621.78 | 8.4042 | 8.573326 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 270919.25 | 270919.25 | 1.0000 | 13.76082173 | 14.078466 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 2.36987798 | 60.00 | 32.22 | 27.78 | 0.000 | 270919.25 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.94 | 0.00783369 | 21.00 | 0.00783369 | 41.1201 | 157151.08 | 0.00 | 272161.44 | 272161.44 | 13.76082173 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52837.8 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 407697.083 | 407697.083 | 21.185084 | 0.00356671 | 9521.347 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 27.64245727 | 54.44 | 82.22 | 27.78 | 3223621.78 | 12.6472 | 12.901704 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 407697.08 | 407697.08 | 1.0000 | 20.70709841 | 21.185084 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 3.56634809 | 60.00 | 32.22 | 27.78 | 0.000 | 407697.08 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.94 | 0.00783433 | 21.00 | 0.00783433 | 41.1234 | 236499.63 | 0.00 | 409566.41 | 409566.41 | 20.70709841 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52838.9 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 261516.550 | 261516.550 | 13.589173 | 0.00228786 | 6107.446 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 27.64245727 | 54.44 | 82.22 | 27.78 | 3223621.78 | 8.1125 | 8.275775 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 261516.55 | 261516.55 | 1.0000 | 13.28256894 | 13.589173 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 2.28762748 | 60.00 | 32.22 | 27.78 | 0.000 | 261516.55 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.94 | 0.00782810 | 21.00 | 0.00782810 | 41.0912 | 151703.58 | 0.00 | 262715.62 | 262715.62 | 13.28256894 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52838.8 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 54078.570 | 54078.570 | 2.811143 | 0.00047310 | 1262.816 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 27.64245727 | 54.44 | 82.22 | 27.78 | 3223621.78 | 1.6776 | 1.711334 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 54078.57 | 53858.27 | 1.0000 | 2.74771673 | 2.811143 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.47305466 | 60.00 | 32.22 | 27.78 | 0.000 | 54078.57 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.94 | 0.00784357 | 21.00 | 0.00784357 | 41.1717 | 31361.69 | 0.00 | 54326.53 | 54326.53 | 2.74771673 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52831.3 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 36156.115 | 36156.115 | 1.879572 | 0.00031631 | 844.290 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 27.64245727 | 54.44 | 82.22 | 27.78 | 3223621.78 | 1.1216 | 1.144172 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 36156.12 | 36156.12 | 1.0000 | 1.83716411 | 1.879572 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.31627720 | 60.00 | 32.22 | 27.78 | 0.000 | 36156.12 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.94 | 0.00784396 | 21.00 | 0.00784396 | 41.1738 | 20967.31 | 0.00 | 36321.90 | 36321.90 | 1.83716411 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52830.5 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 54867.144 | 54867.144 | 2.852182 | 0.00048000 | 1281.225 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 27.64245727 | 54.44 | 82.22 | 27.78 | 3223621.78 | 1.7020 | 1.736288 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 54867.14 | 54644.54 | 1.0000 | 2.78783026 | 2.852182 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.47995274 | 60.00 | 32.22 | 27.78 | 0.000 | 54867.14 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.94 | 0.00784577 | 21.00 | 0.00784577 | 41.1831 | 31818.53 | 0.00 | 55118.72 | 55118.72 | 2.78783026 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52831.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 35670.896 | 35670.896 | 1.854336 | 0.00031206 | 832.961 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 27.64245727 | 54.44 | 82.22 | 27.78 | 3223621.78 | 1.1065 | 1.128817 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 35670.90 | 35670.90 | 1.0000 | 1.81249771 | 1.854336 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.31203273 | 60.00 | 32.22 | 27.78 | 0.000 | 35670.90 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.94 | 0.00784209 | 21.00 | 0.00784209 | 41.1641 | 20686.08 | 0.00 | 35834.46 | 35834.46 | 1.81249771 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52830.6 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 217599.540 | -999.000 | 14.934440 | 0.00777215 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9290 | 1004.8586 | 0.9774 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 14.934440 | 14.59748302 | 4197.9300 | 999.8980 | 110.77775014 | 13.34 | 6.67 | 6.67 | 3101798.40 | 7.0153 | 7.015270 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 217599.54 | 217599.54 | 1.0000 | 14.59748302 | 14.934440 | 25.35 | 13.50 | 0.00704105 | 43408.8 | 10.70 | 7.93 | 0.00704105 | 28502.1 | 7.77135854 | 6.67 | 13.34 | 6.67 | 32510.032 | 185089.51 | 33.90 | 0.00547527 | 15.07 | 2.03050000 | 13.5961 | 24.00 | 0.00728747 | 24.00 | 0.00728747 | 31.9064 | 143522.26 | 0.00 | 190318.28 | 190318.28 | 14.59748302 | 25.35 | 15.60 | 0.00704105 | 43408.8 | 12.54 | 10.49 | 0.00704105 | 30371.0 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 66649.785 | 66649.785 | 4.480332 | 0.00058308 | 1104.524 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 14.934440 | 14.59748302 | 4197.9300 | 999.8980 | 27.64245727 | 54.44 | 82.22 | 27.78 | 3223621.78 | 2.0675 | 2.109154 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 66649.78 | 66649.78 | 1.0000 | 4.37924491 | 4.480332 | -2.26 | -3.31 | 0.00314899 | 5594.3 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 0.58302191 | 60.00 | 32.22 | 27.78 | 0.000 | 66649.78 | -17.90 | 0.00095524 | -17.90 | 2.03050000 | 45.3203 | 10.71 | 0.00496724 | 19.28 | 0.00447065 | 26.2430 | 20237.57 | 0.00 | 62832.69 | 62832.69 | 4.37924491 | 2.80 | 0.74 | 0.00314899 | 10705.4 | 17.00 | 8.18 | 0.00314899 | 25053.2 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2032555.512 | -999.000 | 138.428913 | 0.07259817 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9085 | 1004.8586 | 0.9774 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 138.428913 | 135.30562645 | 4197.9300 | 999.8980 | 110.77775014 | 13.34 | 6.67 | 6.67 | 3101798.40 | 65.5283 | 65.528292 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2032555.51 | 2032555.51 | 1.0000 | 135.30562645 | 138.428913 | 25.46 | 13.53 | 0.00703002 | 43496.2 | 10.70 | 7.92 | 0.00703002 | 28474.3 | 72.59076767 | 6.67 | 13.34 | 6.67 | 301338.954 | 1731216.56 | 33.90 | 0.00547527 | 15.07 | 20.30600000 | 14.6689 | 24.00 | 0.00729890 | 24.00 | 0.00729890 | 31.9558 | 1323729.02 | 0.00 | 1777309.96 | 1777309.96 | 135.30562645 | 25.46 | 15.63 | 0.00703002 | 43496.2 | 12.55 | 10.48 | 0.00703002 | 30360.7 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 498116.057 | 498116.057 | 41.528674 | 0.00435774 | 8400.417 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 138.428913 | 135.30562645 | 4197.9300 | 999.8980 | 27.64245727 | 54.44 | 82.22 | 27.78 | 3223621.78 | 15.4521 | 15.763042 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 498116.06 | 498116.06 | 1.0000 | 40.59168793 | 41.528674 | 0.68 | -0.12 | 0.00432711 | 11507.4 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 4.35729203 | 60.00 | 32.22 | 27.78 | 0.000 | 498116.06 | -17.90 | 0.00095524 | -17.90 | 20.30600000 | 48.8963 | 18.45 | 0.00755333 | 18.41 | 0.00773139 | 47.6631 | 126796.33 | 0.00 | 486577.86 | 486577.86 | 40.59168793 | 2.80 | 2.40 | 0.00432711 | 13657.9 | 14.63 | 8.44 | 0.00432711 | 25645.0 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 271733.532 | -999.000 | 18.923561 | 0.00970569 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9041 | 1004.8586 | 0.9774 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 18.923561 | 18.49660019 | 4197.9300 | 999.8980 | 110.77775014 | 13.34 | 6.67 | 6.67 | 3101798.40 | 8.7605 | 8.760516 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 271733.53 | 271733.53 | 1.0000 | 18.49660019 | 18.923561 | 25.15 | 13.42 | 0.00702770 | 43171.2 | 10.71 | 7.92 | 0.00702770 | 28480.2 | 9.70470206 | 6.67 | 13.34 | 6.67 | 40976.941 | 230756.59 | 33.90 | 0.00547527 | 15.07 | 2.03050000 | 10.7300 | 24.00 | 0.00723095 | 24.00 | 0.00723095 | 31.6616 | 168583.65 | 0.00 | 236912.69 | 236912.69 | 18.49660019 | 25.15 | 15.51 | 0.00702770 | 43171.2 | 12.56 | 10.48 | 0.00702770 | 30362.7 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 39862.637 | 39862.637 | 5.677068 | 0.00034874 | 695.057 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 18.923561 | 18.49660019 | 4197.9300 | 999.8980 | 27.64245727 | 54.44 | 82.22 | 27.78 | 3223621.78 | 1.2366 | 1.261466 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 39862.64 | 39862.64 | 1.0000 | 5.54898006 | 5.677068 | 5.74 | 3.74 | 0.00528568 | 19043.2 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 0.34870017 | 60.00 | 32.22 | 27.78 | 0.000 | 39862.64 | -17.90 | 0.00095524 | -17.90 | 2.03050000 | 35.7667 | 18.90 | 0.00769698 | 17.24 | 0.00789138 | 52.3552 | 12667.02 | 0.00 | 41532.60 | 41532.60 | 5.54898006 | 2.80 | 2.80 | 0.00528568 | 16060.2 | 10.18 | 7.44 | 0.00528568 | 23545.0 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 122974.271 | -999.000 | 8.488504 | 0.00439236 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.1211 | 1004.8586 | 0.9774 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 8.488504 | 8.29698299 | 4197.9300 | 999.8980 | 110.77775014 | 13.34 | 6.67 | 6.67 | 3101798.40 | 3.9646 | 3.964612 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 122974.27 | 120742.67 | 1.0000 | 8.29698299 | 8.488504 | 25.25 | 13.55 | 0.00714440 | 43570.4 | 10.68 | 7.88 | 0.00700000 | 28377.7 | 4.39190795 | 6.67 | 13.34 | 6.67 | 18655.873 | 104318.40 | 31.98 | 0.00547231 | 14.44 | 1.20015641 | 14.1386 | 24.00 | 0.00745410 | 24.00 | 0.00745410 | 32.6278 | 73813.88 | 0.00 | 108690.59 | 108690.59 | 8.29698299 | 25.25 | 15.65 | 0.00714440 | 43570.4 | 12.38 | 10.53 | 0.00714440 | 30470.4 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.743149 | 0.00087484 | 2620.430 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 8.488504 | 8.29698299 | 4197.9300 | 999.8980 | 27.64245727 | 54.44 | 82.22 | 27.78 | 3223621.78 | 3.1021 | 3.164532 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.743149 | -2.53 | -7.04 | 0.00095524 | -158.6 | 32.11 | 16.46 | 0.00800000 | 52750.5 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -17.90 | 0.00095524 | -17.90 | 1.20015641 | 32.0627 | 0.00 | 0.00095524 | 23.67 | 0.00095524 | 4.3102 | 0.00 | 0.00 | 100031.84 | 100031.84 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.01 | 14.59 | 0.00000000 | 40228.1 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 456935.541 | -999.000 | 38.693236 | 0.01632068 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8886 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 38.693236 | 37.82022387 | 4197.9300 | 999.8980 | 110.77775014 | 13.34 | 6.67 | 6.67 | 3101798.40 | 14.7313 | 14.731310 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 456935.54 | 455901.99 | 1.0000 | 37.82022387 | 38.693236 | 27.06 | 14.06 | 0.00701933 | 45097.1 | 14.85 | 9.58 | 0.00700000 | 32622.6 | 16.31901392 | 6.67 | 13.34 | 6.67 | 39958.301 | 416977.24 | 33.90 | 0.00547527 | 15.07 | 0.33839277 | 0.8746 | 27.00 | 0.00703296 | 27.00 | 0.00703296 | 25.7789 | 371513.28 | 0.00 | 393995.97 | 393995.97 | 37.82022387 | 27.06 | 16.20 | 0.00701933 | 45097.1 | 16.82 | 12.28 | 0.00701933 | 34679.5 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.743149 | 0.00087484 | 2620.430 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 38.693236 | 37.82022387 | 4197.9300 | 999.8980 | 27.64245727 | 54.44 | 82.22 | 27.78 | 3223621.78 | 3.1021 | 3.164532 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.743149 | -0.16 | -0.16 | 0.00694714 | 17215.0 | 29.11 | 15.52 | 0.00800000 | 49691.3 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -17.90 | 0.00095524 | -17.90 | 0.33839277 | 9.0403 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | 100031.84 | 100031.84 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.01 | 14.59 | 0.00000000 | 40228.1 | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15317.050 | 12263.749 | 0.925300 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9206 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.925303 | 0.90442567 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 7658.52 | 7625.79 | 1.0000 | 0.60294868 | 0.616867 | 27.02 | 14.07 | 0.00703654 | 45106.3 | 14.22 | 9.33 | 0.00700000 | 31978.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7658.52 | 28.50 | 0.00546700 | 13.26 | 0.01563234 | 2.5342 | 27.00 | 0.00706352 | 27.00 | 0.00706352 | 25.8880 | 8893.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26730.582 | 26730.582 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.925303 | 0.90442567 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 26730.58 | 26730.58 | 1.0000 | 0.90442567 | 0.925303 | -0.30 | -4.37 | 0.00177439 | 4132.8 | 29.11 | 15.52 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26730.58 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 1.6894 | 0.00 | 0.00178846 | 25.72 | 0.00178846 | 7.1291 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 147380.870 | 118001.967 | 8.903280 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9231 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 8.903278 | 8.70239902 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 73690.43 | 73363.76 | 1.0000 | 5.80160050 | 5.935520 | 27.03 | 14.07 | 0.00703791 | 45110.8 | 14.16 | 9.31 | 0.00700000 | 31919.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 73690.43 | 28.50 | 0.00546700 | 13.26 | 0.15632344 | 2.6337 | 27.00 | 0.00706598 | 27.00 | 0.00706598 | 25.8970 | 85572.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 257305.991 | 257305.991 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 8.903278 | 8.70239902 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 257305.99 | 257305.99 | 1.0000 | 8.70239902 | 8.903278 | -0.31 | -4.38 | 0.00177386 | 4119.5 | 29.11 | 15.52 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 257305.99 | -17.90 | 0.00095524 | -17.90 | 0.15632344 | 1.7558 | 0.00 | 0.00178849 | 23.84 | 0.00178849 | 7.9755 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15247.770 | 12208.280 | 0.921120 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9208 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.921118 | 0.90033505 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 7623.89 | 7591.22 | 1.0000 | 0.60022489 | 0.614080 | 27.03 | 14.07 | 0.00703664 | 45113.1 | 14.22 | 9.33 | 0.00700000 | 31978.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7623.89 | 28.87 | 0.00546756 | 13.38 | 0.01563234 | 2.5457 | 27.00 | 0.00706373 | 27.00 | 0.00706373 | 25.8888 | 8853.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26610.925 | 26610.925 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.921118 | 0.90033505 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 26610.93 | 26610.93 | 1.0000 | 0.90033505 | 0.921118 | -0.30 | -4.37 | 0.00177342 | 4129.0 | 29.11 | 15.52 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26610.93 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 1.6971 | 0.00 | 0.00178754 | 21.72 | 0.00178754 | 9.0671 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 14.93 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 138.43 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 18.92 | - | |||
CAV_BAS_OA_CONTROLLER | FixedDryBulb | 1.20 | 8.49 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 38.69 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1666.67 | 2270.67 | 41.67 |
CORE_BOTTOM | 1636.50 | 1824.17 | 153.67 |
CORE_MID | 1173.67 | 3430.83 | 274.00 |
CORE_TOP | 2037.50 | 4221.33 | 1181.17 |
PERIMETER_BOT_ZN_3 | 2079.50 | 3883.67 | 807.83 |
PERIMETER_BOT_ZN_2 | 2372.17 | 3765.00 | 847.50 |
PERIMETER_BOT_ZN_1 | 2891.33 | 3092.33 | 857.50 |
PERIMETER_BOT_ZN_4 | 2357.00 | 3532.17 | 529.00 |
PERIMETER_MID_ZN_3 | 2813.67 | 4549.17 | 1927.33 |
PERIMETER_MID_ZN_2 | 2445.67 | 3554.83 | 1406.33 |
PERIMETER_MID_ZN_1 | 3072.83 | 3303.50 | 1194.00 |
PERIMETER_MID_ZN_4 | 2659.50 | 4347.17 | 1504.00 |
PERIMETER_TOP_ZN_3 | 3337.00 | 4839.67 | 2574.17 |
PERIMETER_TOP_ZN_2 | 3319.33 | 4193.17 | 2018.83 |
PERIMETER_TOP_ZN_1 | 3357.33 | 3683.50 | 1668.17 |
PERIMETER_TOP_ZN_4 | 3168.67 | 4480.67 | 2077.83 |
DATACENTER_BOT_ZN_6 | 5931.17 | 976.50 | 976.50 |
DATACENTER_MID_ZN_6 | 5626.33 | 388.33 | 372.33 |
DATACENTER_TOP_ZN_6 | 4884.33 | 799.67 | 565.17 |
DATACENTER_BASEMENT_ZN_6 | 5924.00 | 3873.67 | 3873.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5932.00 | 5342.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 18.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_MID | 0.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 13.67 | 0.00 | 0.33 | 0.00 |
PERIMETER_BOT_ZN_3 | 5.00 | 2.17 | 0.17 | 2.17 |
PERIMETER_BOT_ZN_2 | 7.17 | 22.17 | 0.17 | 22.17 |
PERIMETER_BOT_ZN_1 | 8.67 | 43.83 | 0.33 | 43.83 |
PERIMETER_BOT_ZN_4 | 2.50 | 38.17 | 0.00 | 25.17 |
PERIMETER_MID_ZN_3 | 69.33 | 0.50 | 9.17 | 0.50 |
PERIMETER_MID_ZN_2 | 99.67 | 21.00 | 6.67 | 21.00 |
PERIMETER_MID_ZN_1 | 46.50 | 67.00 | 4.83 | 66.83 |
PERIMETER_MID_ZN_4 | 44.83 | 20.50 | 3.83 | 12.83 |
PERIMETER_TOP_ZN_3 | 209.33 | 0.83 | 39.00 | 0.83 |
PERIMETER_TOP_ZN_2 | 191.17 | 20.33 | 27.00 | 20.33 |
PERIMETER_TOP_ZN_1 | 154.67 | 29.33 | 22.83 | 29.17 |
PERIMETER_TOP_ZN_4 | 139.83 | 20.67 | 22.00 | 13.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 347.00 | 0.00 | 297.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 297.00 | 568.50 | 47.67 | 481.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 1.091 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 1.066 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.841 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.801 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 1.189 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 2.330 | 0.044 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 2.219 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 2.823 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 1.318 | 0.100 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 2.225 | 0.112 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 2.128 | 0.101 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 2.449 | 0.104 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 1.610 | 0.124 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 2.162 | 0.129 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 2.242 | 0.125 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 2.479 | 0.129 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 24.280 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 60.99 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.86 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.79 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.20 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1010.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 44319795.98 | 0.00 | 44319795.98 | 0.00 | 44319795.98 | 37848132.68 | 4216.19 | 2500.62 | 2043.19 | 169.79 |
CORE_BOTTOM | 44772801.39 | 0.00 | 44772801.39 | 0.00 | 44772801.39 | 33990283.35 | 5150.88 | 32.56 | 3576.56 | 253.39 |
CORE_MID | 0.35E+09 | 0.00 | 0.35E+09 | 0.00 | 0.35E+09 | 0.34E+09 | 5762.87 | 36.31 | 2960.83 | 336.98 |
CORE_TOP | 32946718.41 | 0.00 | 32946718.41 | 0.00 | 32946718.41 | 33990283.35 | 6023.71 | 33.03 | 2703.26 | 399.78 |
PERIMETER_BOT_ZN_3 | 6328676.70 | 0.00 | 6328676.70 | 451114.65 | 6779791.34 | 4267819.30 | 3778.99 | 30.12 | 4950.89 | 253.39 |
PERIMETER_BOT_ZN_2 | 8001508.16 | 0.00 | 8001508.16 | 300742.89 | 8302251.05 | 2750345.05 | 3630.70 | 0.27 | 5129.02 | 253.39 |
PERIMETER_BOT_ZN_1 | 11675474.75 | 0.00 | 11675474.75 | 451114.65 | 12126589.40 | 4267912.63 | 3659.43 | 2.49 | 5098.08 | 253.39 |
PERIMETER_BOT_ZN_4 | 9725504.47 | 0.00 | 9725504.47 | 300742.89 | 10026247.36 | 2750345.05 | 3629.83 | 0.00 | 5130.17 | 253.39 |
PERIMETER_MID_ZN_3 | 69886443.02 | 0.00 | 69886443.02 | 1057988.21 | 70944431.23 | 42678193.03 | 3794.91 | 17.04 | 4948.05 | 336.98 |
PERIMETER_MID_ZN_2 | 72344380.34 | 0.00 | 72344380.34 | 705324.99 | 73049705.33 | 27503450.52 | 3946.26 | 6.05 | 4807.69 | 941.42 |
PERIMETER_MID_ZN_1 | 0.11E+09 | 0.00 | 0.11E+09 | 1057988.21 | 0.11E+09 | 42679126.28 | 3728.54 | 10.34 | 5021.12 | 336.98 |
PERIMETER_MID_ZN_4 | 83557319.81 | 0.00 | 83557319.81 | 705324.99 | 84262644.80 | 27503450.52 | 3562.17 | 0.50 | 5197.33 | 336.98 |
PERIMETER_TOP_ZN_3 | 8376092.70 | 0.00 | 8376092.70 | 1313602.61 | 9689695.31 | 4267819.30 | 3980.14 | 18.59 | 4761.27 | 399.78 |
PERIMETER_TOP_ZN_2 | 7211952.05 | 0.00 | 7211952.05 | 875734.47 | 8087686.52 | 2750345.05 | 3903.70 | 5.12 | 4851.17 | 399.78 |
PERIMETER_TOP_ZN_1 | 11551101.70 | 0.00 | 11551101.70 | 1313602.61 | 12864704.31 | 4267912.63 | 3944.66 | 6.60 | 4808.74 | 399.78 |
PERIMETER_TOP_ZN_4 | 8291507.54 | 0.00 | 8291507.54 | 875734.47 | 9167242.02 | 2750345.05 | 3858.09 | 5.32 | 4896.59 | 399.78 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.41E+09 | 0.00 | 0.41E+09 | 0.00 | 0.41E+09 | 10671554.30 | 512.37 | 1100.99 | 7146.64 | 2557.76 |
Total Facility | 0.75E+10 | 0.00 | 0.75E+10 | 41148653.23 | 0.75E+10 | 0.50E+10 | 6577.82 | 4410.54 | 8334.49 | 3219.05 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.0312 | 0.0000 | 2.0312 | 0.0000 | 2.0312 | 1.2002 | 1461.70 | 2499.49 | 1981.82 |
CORE_BOTTOM | 2.0041 | 0.0000 | 2.0041 | 0.0000 | 2.0041 | 1.0778 | 2519.18 | 31.38 | 3392.44 |
CORE_MID | 15.8225 | 0.0000 | 15.8225 | 0.0000 | 15.8225 | 10.7782 | 3024.66 | 35.03 | 2883.31 |
CORE_TOP | 1.5105 | 0.0000 | 1.5105 | 0.0000 | 1.5105 | 1.0778 | 3240.78 | 30.93 | 2671.30 |
PERIMETER_BOT_ZN_3 | 0.2814 | 0.0000 | 0.2814 | 0.0102 | 0.2916 | 0.1353 | 1181.41 | 27.98 | 4733.61 |
PERIMETER_BOT_ZN_2 | 0.3559 | 0.0000 | 0.3559 | 0.0068 | 0.3627 | 0.0872 | 1067.08 | 0.27 | 4875.65 |
PERIMETER_BOT_ZN_1 | 0.5250 | 0.0000 | 0.5250 | 0.0102 | 0.5352 | 0.1353 | 1086.26 | 2.19 | 4854.55 |
PERIMETER_BOT_ZN_4 | 0.4311 | 0.0000 | 0.4311 | 0.0068 | 0.4378 | 0.0872 | 1066.22 | 0.00 | 4876.78 |
PERIMETER_MID_ZN_3 | 3.1289 | 0.0000 | 3.1289 | 0.0239 | 3.1528 | 1.3533 | 1182.06 | 12.17 | 4748.78 |
PERIMETER_MID_ZN_2 | 3.4010 | 0.0000 | 3.4010 | 0.0171 | 3.4181 | 0.8721 | 1078.13 | 0.86 | 3955.01 |
PERIMETER_MID_ZN_1 | 5.0367 | 0.0000 | 5.0367 | 0.0239 | 5.0606 | 1.3533 | 1132.00 | 3.96 | 4807.04 |
PERIMETER_MID_ZN_4 | 3.7480 | 0.0000 | 3.7480 | 0.0159 | 3.7639 | 0.8721 | 1075.46 | 0.05 | 4867.49 |
PERIMETER_TOP_ZN_3 | 0.3830 | 0.0000 | 0.3830 | 0.0297 | 0.4127 | 0.1353 | 1251.51 | 16.37 | 4675.12 |
PERIMETER_TOP_ZN_2 | 0.3307 | 0.0000 | 0.3307 | 0.0198 | 0.3504 | 0.0872 | 1196.11 | 2.61 | 4744.27 |
PERIMETER_TOP_ZN_1 | 0.5313 | 0.0000 | 0.5313 | 0.0297 | 0.5610 | 0.1353 | 1216.76 | 4.34 | 4721.91 |
PERIMETER_TOP_ZN_4 | 0.3796 | 0.0000 | 0.3796 | 0.0198 | 0.3994 | 0.0872 | 1173.87 | 2.33 | 4766.80 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 12.6438 | 0.0000 | 12.6438 | 0.0000 | 12.6438 | 0.3384 | 252.53 | 1100.98 | 4589.50 |
Total Facility | 333.9430 | 0.0000 | 333.9430 | 0.9407 | 334.8837 | 158.4706 | 3760.82 | 4378.22 | 5739.90 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 76912231.17 | 0.00 | 76912231.17 | 48026705.38 | 3762.75 | 460.16 | 4537.08 | 253.39 |
VAV_MID WITH REHEAT | 0.66E+09 | 0.00 | 0.66E+09 | 0.48E+09 | 3896.51 | 228.79 | 4634.69 | 336.98 |
VAV_TOP WITH REHEAT | 65326669.63 | 0.00 | 65326669.63 | 48026705.38 | 4100.31 | 378.38 | 4281.31 | 399.73 |
CAV_BAS | 42217234.01 | 0.00 | 42217234.01 | 37848132.68 | 6762.09 | 18.31 | 1979.59 | 169.79 |
AIRLOOP DATACENTER BASEMENT | 0.39E+09 | 0.00 | 0.39E+09 | 10671554.30 | 1613.52 | 0.03 | 7146.44 | 2557.76 |
AIRLOOP DATACENTER BOT | 233396.58 | 0.00 | 233396.58 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 2333965.77 | 0.00 | 2333965.77 | 4929815.99 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 233396.58 | 0.00 | 233396.58 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.4369 | 0.0000 | 3.4369 | 1.5229 | 1157.90 | 458.07 | 4327.03 |
VAV_MID WITH REHEAT | 29.5962 | 0.0000 | 29.5962 | 15.2292 | 1208.03 | 225.78 | 4509.18 |
VAV_TOP WITH REHEAT | 2.9953 | 0.0000 | 2.9953 | 1.5229 | 1338.39 | 377.66 | 4226.96 |
CAV_BAS | 1.9347 | 0.0000 | 1.9347 | 1.2002 | 4005.02 | 16.98 | 1921.00 |
AIRLOOP DATACENTER BASEMENT | 12.0798 | 0.0000 | 12.0798 | 0.3384 | 1353.65 | 0.03 | 4589.32 |
AIRLOOP DATACENTER BOT | 0.0109 | 0.0000 | 0.0109 | 0.0156 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.1091 | 0.0000 | 0.1091 | 0.1563 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.0109 | 0.0000 | 0.0109 | 0.0156 | 5943.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 39.67 | 4003.22 | 0.00 | 0.00 | 0.00 | 1087.28 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 101.53 | 3978.51 | 0.00 | 0.00 | 0.00 | 1126.38 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 32.40 | 3708.18 | 0.00 | 0.00 | 0.00 | 1538.31 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 2518.69 | 2217.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 1101.03 | 7147.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 1.8498 | 4.9709 | 0.0000 | 0.0000 | 0.0000 | 1.5739 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 19.2333 | 42.7601 | 0.0000 | 0.0000 | 0.0000 | 16.1942 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 1.8630 | 4.6172 | 0.0000 | 0.0000 | 0.0000 | 1.6026 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.1469 | 4.2062 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3233 | 15.5630 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0149 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1493 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0149 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1343 |
Defaulted Fields | 1287 |
Fields with Defaults | 3878 |
Autosized Fields | 320 |
Autosizable Fields | 465 |
Autocalculated Fields | 223 |
Autocalculatable Fields | 468 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 32620.06 | 294905.62 | 29-MAY-04:40 | 2436855.34 | 16-AUG-15:20 |
Electricity:Building | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 758.19 | 15076.70 | 01-JAN-00:10 | 42602.33 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 589.38 | 5907.35 | 01-JAN-00:10 | 43380.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5893.79 | 59073.32 | 01-JAN-00:10 | 433806.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 589.38 | 5907.33 | 01-JAN-00:10 | 43380.63 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 740.04 | 7417.49 | 01-JAN-00:10 | 54469.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 476.91 | 4780.12 | 01-JAN-00:10 | 35102.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 740.05 | 7417.62 | 01-JAN-00:10 | 54470.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 476.91 | 4780.09 | 01-JAN-00:10 | 35102.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7588.97 | 95364.66 | 01-JAN-00:10 | 387850.11 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1622.27 | 19890.94 | 01-JAN-00:10 | 85232.07 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:HVAC | 5704.01 | 39128.26 | 21-MAY-02:30 | 424108.86 | 26-JUN-14:40 |
ExteriorEquipment:Electricity | 2623.11 | 22123.82 | 01-JAN-00:10 | 235096.12 | 03-APR-07:20 |
Transformer:ExteriorEquipment:Electricity | 56.04 | 979.82 | 01-JAN-00:10 | 3543.78 | 03-APR-07:20 |
ElectricityPurchased:Facility | 32620.06 | 294905.62 | 29-MAY-04:40 | 2436855.34 | 16-AUG-15:20 |
ElectricityPurchased:Plant | 32620.06 | 294905.62 | 29-MAY-04:40 | 2436855.34 | 16-AUG-15:20 |
Cogeneration:ElectricityPurchased | 32620.06 | 294905.62 | 29-MAY-04:40 | 2436855.34 | 16-AUG-15:20 |
General:Cogeneration:ElectricityPurchased | 32620.06 | 294905.62 | 29-MAY-04:40 | 2436855.34 | 16-AUG-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 32620.06 | 294905.62 | 29-MAY-04:40 | 2436855.34 | 16-AUG-15:20 |
ElectricityNet:Plant | 32620.06 | 294905.62 | 29-MAY-04:40 | 2436855.34 | 16-AUG-15:20 |
Cogeneration:ElectricityNet | 32620.06 | 294905.62 | 29-MAY-04:40 | 2436855.34 | 16-AUG-15:20 |
General:Cogeneration:ElectricityNet | 32620.06 | 294905.62 | 29-MAY-04:40 | 2436855.34 | 16-AUG-15:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 2063.06 | 732.60 | 01-JAN-07:30 | 389419.53 | 16-AUG-15:30 |
General:Cooling:Electricity | 2063.06 | 732.60 | 01-JAN-07:30 | 389419.53 | 16-AUG-15:30 |
Fans:Electricity | 3429.19 | 30365.66 | 01-JAN-09:20 | 397151.93 | 26-JUN-14:40 |
General:Fans:Electricity | 3429.19 | 30365.66 | 01-JAN-09:20 | 397151.93 | 26-JUN-14:40 |
ExteriorLights:Electricity | 1006.50 | 0.00 | 01-JAN-07:30 | 64082.80 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 1006.50 | 0.00 | 01-JAN-07:30 | 64082.80 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.31 | 1944.00 | 01-JAN-00:10 | 1944.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1739.47 | 0.00 | 17-MAR-07:10 | 100000.00 | 09-JAN-10:10 |
General:Humidifier:Electricity | 1739.47 | 0.00 | 17-MAR-07:10 | 100000.00 | 09-JAN-10:10 |
Electricity:Plant | 3055.34 | 0.00 | 04-JAN-00:10 | 519269.38 | 16-AUG-15:30 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 450.55 | 0.00 | 01-JAN-00:10 | 55493.62 | 14-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 450.55 | 0.00 | 01-JAN-00:10 | 55493.62 | 14-FEB-12:50 |
HeatRejection:Electricity | 79.78 | 0.00 | 01-JAN-00:10 | 48194.65 | 28-JUL-13:10 |
General:HeatRejection:Electricity | 79.78 | 0.00 | 01-JAN-00:10 | 48194.65 | 28-JUL-13:10 |
Pumps:Electricity | 941.26 | 0.00 | 03-JAN-00:10 | 97555.15 | 18-JUL-15:10 |
General:Pumps:Electricity | 941.26 | 0.00 | 03-JAN-00:10 | 97555.15 | 18-JUL-15:10 |
WIRED_LTG_ELECTRICITY | 157.66 | 0.00 | 01-JAN-00:10 | 13766.21 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2464.87 | 0.00 | 01-JAN-09:20 | 1707687.40 | 06-FEB-06:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 2464.87 | 0.00 | 01-JAN-09:20 | 1707687.40 | 06-FEB-06:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 2464.87 | 0.00 | 01-JAN-09:20 | 1707687.40 | 06-FEB-06:10 |
Boiler:Heating:NaturalGas | 2464.87 | 0.00 | 01-JAN-09:20 | 1707687.40 | 06-FEB-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 9305.98 | 0.00 | 01-JAN-01:50 | 2458090.11 | 16-AUG-15:20 |
PlantLoopCoolingDemand:HVAC | 9305.98 | 0.00 | 01-JAN-01:50 | 2458090.11 | 16-AUG-15:20 |
CoolingCoils:PlantLoopCoolingDemand | 9305.98 | 0.00 | 01-JAN-01:50 | 2458090.11 | 16-AUG-15:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 10846.71 | 0.00 | 14-APR-01:30 | 0.00 | 26-JUN-16:10 |
Water:HVAC | 647.08 | 0.00 | 17-MAR-07:10 | 0.00 | 21-JAN-09:00 |
Humidifier:Water | 647.08 | 0.00 | 17-MAR-07:10 | 0.00 | 21-JAN-09:00 |
General:Humidifier:Water | 647.08 | 0.00 | 17-MAR-07:10 | 0.00 | 21-JAN-09:00 |
MainsWater:Facility | 10846.71 | 0.00 | 14-APR-01:30 | 0.00 | 26-JUN-16:10 |
MainsWater:HVAC | 647.08 | 0.00 | 17-MAR-07:10 | 0.00 | 21-JAN-09:00 |
Humidifier:MainsWater | 647.08 | 0.00 | 17-MAR-07:10 | 0.00 | 21-JAN-09:00 |
General:Humidifier:MainsWater | 647.08 | 0.00 | 17-MAR-07:10 | 0.00 | 21-JAN-09:00 |
Water:Plant | 10199.63 | 0.00 | 01-JAN-00:20 | 0.00 | 26-JUN-16:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 15-MAR-11:20 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 15-MAR-11:20 |
MainsWater:Plant | 10199.63 | 0.00 | 01-JAN-00:20 | 0.00 | 26-JUN-16:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 15-MAR-11:20 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 15-MAR-11:20 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 7919.46 | 0.00 | 01-JAN-00:20 | 0.00 | 26-JUN-16:10 |
General:HeatRejection:Water | 7919.46 | 0.00 | 01-JAN-00:20 | 0.00 | 26-JUN-16:10 |
HeatRejection:MainsWater | 7919.46 | 0.00 | 01-JAN-00:20 | 0.00 | 26-JUN-16:10 |
General:HeatRejection:MainsWater | 7919.46 | 0.00 | 01-JAN-00:20 | 0.00 | 26-JUN-16:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 66792.09 | 104034.49 | 08-JAN-05:30 | 12313224.40 | 16-AUG-15:20 |
EnergyTransfer:Building | 21486.22 | 86919.94 | 07-JAN-19:20 | 1950352.93 | 16-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 689.65 | 0.00 | 01-JAN-00:10 | 75229.82 | 02-JAN-08:40 |
Heating:EnergyTransfer | 771.01 | 0.00 | 09-JAN-17:40 | 1050289.49 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.92 | 0.00 | 01-JAN-00:10 | 12619.34 | 15-JUL-16:10 |
General:Heating:EnergyTransfer | 771.01 | 0.00 | 09-JAN-17:40 | 1050289.49 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.92 | 0.00 | 01-JAN-00:10 | 12619.34 | 15-JUL-16:10 |
Cooling:EnergyTransfer | 20715.21 | 84578.17 | 08-JAN-11:00 | 1950352.93 | 16-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 688.72 | 0.00 | 01-JAN-00:10 | 75229.82 | 02-JAN-08:40 |
General:Cooling:EnergyTransfer | 20715.21 | 84578.17 | 08-JAN-11:00 | 1950352.93 | 16-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 688.72 | 0.00 | 01-JAN-00:10 | 75229.82 | 02-JAN-08:40 |
EnergyTransfer:Zone:CORE_BOTTOM | 639.92 | 0.00 | 01-JAN-00:10 | 58331.27 | 07-AUG-13:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 639.92 | 0.00 | 01-JAN-00:10 | 58331.27 | 07-AUG-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 639.92 | 0.00 | 01-JAN-00:10 | 58331.27 | 07-AUG-13:10 |
EnergyTransfer:Zone:CORE_MID | 5037.54 | 0.00 | 01-JAN-00:10 | 501479.41 | 18-JUL-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 3.84 | 0.00 | 01-JAN-00:10 | 248505.00 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 3.84 | 0.00 | 01-JAN-00:10 | 248505.00 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5033.70 | 0.00 | 01-JAN-00:10 | 501479.41 | 18-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5033.70 | 0.00 | 01-JAN-00:10 | 501479.41 | 18-JUL-16:00 |
EnergyTransfer:Zone:CORE_TOP | 469.45 | 0.00 | 01-JAN-00:40 | 90008.21 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 23.19 | 0.00 | 01-JAN-00:20 | 90008.21 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 23.19 | 0.00 | 01-JAN-00:20 | 90008.21 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 446.26 | 0.00 | 01-JAN-00:10 | 63283.56 | 16-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 446.26 | 0.00 | 01-JAN-00:10 | 63283.56 | 16-AUG-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 84.52 | 0.00 | 01-JAN-00:10 | 14318.66 | 17-JUL-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.75 | 0.00 | 01-JAN-00:10 | 13002.31 | 23-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.75 | 0.00 | 01-JAN-00:10 | 13002.31 | 23-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 81.77 | 0.00 | 01-JAN-00:10 | 14318.66 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 81.77 | 0.00 | 01-JAN-00:10 | 14318.66 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 92.40 | 0.00 | 01-JAN-00:10 | 17374.34 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.15 | 0.00 | 01-JAN-00:10 | 10116.97 | 23-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.15 | 0.00 | 01-JAN-00:10 | 10116.97 | 23-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 90.25 | 0.00 | 01-JAN-00:10 | 17374.34 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 90.25 | 0.00 | 01-JAN-00:10 | 17374.34 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 152.90 | 0.00 | 01-JAN-00:10 | 27017.86 | 28-SEP-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 3.85 | 0.00 | 01-JAN-00:10 | 15078.56 | 23-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 3.85 | 0.00 | 01-JAN-00:10 | 15078.56 | 23-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 149.05 | 0.00 | 01-JAN-00:10 | 27017.86 | 28-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 149.05 | 0.00 | 01-JAN-00:10 | 27017.86 | 28-SEP-13:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 120.53 | 0.00 | 01-JAN-00:10 | 23751.96 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.48 | 0.00 | 01-JAN-00:10 | 5935.13 | 21-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.48 | 0.00 | 01-JAN-00:10 | 5935.13 | 21-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 120.05 | 0.00 | 01-JAN-00:10 | 23751.96 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 120.05 | 0.00 | 01-JAN-00:10 | 23751.96 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 836.05 | 0.00 | 01-JAN-00:10 | 202310.69 | 21-DEC-05:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 168.21 | 0.00 | 01-JAN-00:10 | 202310.69 | 21-DEC-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 168.21 | 0.00 | 01-JAN-00:10 | 202310.69 | 21-DEC-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 667.83 | 0.00 | 01-JAN-00:10 | 134969.70 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 667.83 | 0.00 | 01-JAN-00:10 | 134969.70 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 859.29 | 0.00 | 01-JAN-00:10 | 183971.80 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 94.16 | 0.00 | 01-JAN-00:10 | 143322.69 | 23-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 94.16 | 0.00 | 01-JAN-00:10 | 143322.69 | 23-DEC-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 765.14 | 0.00 | 01-JAN-00:10 | 183971.80 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 765.14 | 0.00 | 01-JAN-00:10 | 183971.80 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1517.34 | 0.00 | 01-JAN-00:10 | 278967.80 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 105.79 | 0.00 | 01-JAN-00:10 | 205358.67 | 21-DEC-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 105.79 | 0.00 | 01-JAN-00:10 | 205358.67 | 21-DEC-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1411.55 | 0.00 | 01-JAN-00:10 | 278967.80 | 28-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1411.55 | 0.00 | 01-JAN-00:10 | 278967.80 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 900.00 | 0.00 | 01-JAN-00:10 | 215187.33 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 76.77 | 0.00 | 01-JAN-00:10 | 136480.81 | 21-DEC-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 76.77 | 0.00 | 01-JAN-00:10 | 136480.81 | 21-DEC-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 823.23 | 0.00 | 01-JAN-00:10 | 215187.33 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 823.23 | 0.00 | 01-JAN-00:10 | 215187.33 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 111.94 | 0.00 | 01-JAN-00:40 | 28126.49 | 21-DEC-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 44.42 | 0.00 | 01-JAN-00:40 | 28126.49 | 21-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 44.42 | 0.00 | 01-JAN-00:40 | 28126.49 | 21-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 67.52 | 0.00 | 01-JAN-00:10 | 14994.28 | 17-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 67.52 | 0.00 | 01-JAN-00:10 | 14994.28 | 17-JUL-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 99.99 | 0.00 | 01-JAN-00:40 | 19212.72 | 21-DEC-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 24.83 | 0.00 | 01-JAN-00:40 | 19212.72 | 21-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 24.83 | 0.00 | 01-JAN-00:40 | 19212.72 | 21-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 75.16 | 0.00 | 01-JAN-00:10 | 18444.17 | 17-JUL-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 75.16 | 0.00 | 01-JAN-00:10 | 18444.17 | 17-JUL-08:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 166.81 | 0.00 | 01-JAN-00:40 | 32008.52 | 28-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 31.16 | 0.00 | 01-JAN-00:40 | 28209.23 | 21-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 31.16 | 0.00 | 01-JAN-00:40 | 28209.23 | 21-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 135.65 | 0.00 | 01-JAN-00:10 | 32008.52 | 28-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 135.65 | 0.00 | 01-JAN-00:10 | 32008.52 | 28-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 99.41 | 0.00 | 01-JAN-00:40 | 22803.39 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 20.00 | 0.00 | 01-JAN-00:40 | 18571.35 | 21-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 20.00 | 0.00 | 01-JAN-00:40 | 18571.35 | 21-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 79.42 | 0.00 | 01-JAN-00:10 | 22803.39 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 79.42 | 0.00 | 01-JAN-00:10 | 22803.39 | 16-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 87.29 | 0.00 | 01-JAN-00:10 | 10729.11 | 17-JUL-14:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.92 | 0.00 | 01-JAN-00:10 | 3470.00 | 25-DEC-11:10 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.92 | 0.00 | 01-JAN-00:10 | 3470.00 | 25-DEC-11:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 86.37 | 0.00 | 01-JAN-00:10 | 10729.11 | 17-JUL-14:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 86.37 | 0.00 | 01-JAN-00:10 | 10729.11 | 17-JUL-14:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 702.70 | 0.00 | 01-JAN-00:10 | 110779.31 | 26-DEC-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 68.80 | 0.00 | 01-JAN-00:10 | 110779.31 | 26-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 68.80 | 0.00 | 01-JAN-00:10 | 110779.31 | 26-DEC-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 633.90 | 0.00 | 01-JAN-00:10 | 104079.17 | 05-MAR-04:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 633.90 | 0.00 | 01-JAN-00:10 | 104079.17 | 05-MAR-04:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 220.60 | 0.00 | 01-JAN-00:40 | 44137.34 | 23-DEC-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 92.43 | 0.00 | 01-JAN-00:40 | 44137.34 | 23-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 92.43 | 0.00 | 01-JAN-00:40 | 44137.34 | 23-DEC-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 128.16 | 0.00 | 01-JAN-00:10 | 40528.96 | 26-JUN-13:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 128.16 | 0.00 | 01-JAN-00:10 | 40528.96 | 26-JUN-13:20 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.65 | 246.69 | 05-JAN-05:20 | 8672.12 | 13-AUG-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.65 | 246.69 | 05-JAN-05:20 | 8672.12 | 13-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.65 | 246.69 | 05-JAN-05:20 | 8672.12 | 13-AUG-18:20 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1184.23 | 5.22 | 15-JAN-20:10 | 82417.32 | 11-AUG-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 3.40 | 0.00 | 01-JAN-15:50 | 15367.01 | 01-JAN-05:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 3.40 | 0.00 | 01-JAN-15:50 | 15367.01 | 01-JAN-05:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1180.83 | 0.00 | 01-JAN-00:10 | 82417.32 | 11-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1180.83 | 0.00 | 01-JAN-00:10 | 82417.32 | 11-AUG-18:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 106.14 | 3.33 | 21-JAN-09:40 | 8401.24 | 11-AUG-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.99 | 0.00 | 02-JAN-10:40 | 1585.49 | 16-JAN-20:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.99 | 0.00 | 02-JAN-10:40 | 1585.49 | 16-JAN-20:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 104.15 | 0.00 | 01-JAN-00:10 | 8401.24 | 11-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 104.15 | 0.00 | 01-JAN-00:10 | 8401.24 | 11-AUG-18:10 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7172.88 | 83841.63 | 08-JAN-12:10 | 393312.48 | 15-AUG-04:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.95 | 0.00 | 01-JAN-00:10 | 3186.57 | 30-SEP-23:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.95 | 0.00 | 01-JAN-00:10 | 3186.57 | 30-SEP-23:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7171.92 | 83841.63 | 08-JAN-12:10 | 393312.48 | 15-AUG-04:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7171.92 | 83841.63 | 08-JAN-12:10 | 393312.48 | 15-AUG-04:00 |
PlantLoopHeatingDemand:Facility | 2124.84 | 0.00 | 02-JAN-00:20 | 1322202.10 | 23-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 445.14 | 0.00 | 01-JAN-00:10 | 54678.49 | 13-FEB-12:50 |
WaterSystems:PlantLoopHeatingDemand | 445.14 | 0.00 | 01-JAN-00:10 | 54678.49 | 13-FEB-12:50 |
General:WaterSystems:PlantLoopHeatingDemand | 445.14 | 0.00 | 01-JAN-00:10 | 54678.49 | 13-FEB-12:50 |
EnergyTransfer:HVAC | 12940.38 | 2394.37 | 02-JAN-03:40 | 2571383.21 | 16-AUG-15:20 |
HeatingCoils:EnergyTransfer | 1679.70 | 0.00 | 01-JAN-09:20 | 1312297.72 | 06-FEB-06:10 |
PlantLoopHeatingDemand:HVAC | 1679.70 | 0.00 | 01-JAN-09:20 | 1312297.72 | 06-FEB-06:10 |
HeatingCoils:PlantLoopHeatingDemand | 1679.70 | 0.00 | 01-JAN-09:20 | 1312297.72 | 06-FEB-06:10 |
CoolingCoils:EnergyTransfer | 11260.68 | 2356.33 | 01-JAN-07:40 | 2571383.21 | 16-AUG-15:20 |
EnergyTransfer:Plant | 32365.50 | 0.00 | 03-JAN-00:10 | 7791488.26 | 16-AUG-15:20 |
LoopToLoop:EnergyTransfer | 9456.52 | 0.00 | 01-JAN-01:50 | 2458670.28 | 16-AUG-15:20 |
WaterSystems:EnergyTransfer | 445.14 | 0.00 | 01-JAN-00:10 | 54678.49 | 13-FEB-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 445.14 | 0.00 | 01-JAN-00:10 | 54678.49 | 13-FEB-12:50 |
Boilers:EnergyTransfer | 1670.95 | 0.00 | 01-JAN-09:20 | 1327381.27 | 06-FEB-06:10 |
Chillers:EnergyTransfer | 9604.57 | 0.00 | 01-JAN-00:20 | 2473057.97 | 16-AUG-15:20 |
HeatRejection:EnergyTransfer | 11188.32 | 0.00 | 01-JAN-00:20 | 2826356.01 | 16-AUG-15:20 |
General:HeatRejection:EnergyTransfer | 11188.32 | 0.00 | 01-JAN-00:20 | 2826356.01 | 16-AUG-15:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.924 | -688.717 | 0.000 | 0.000 | 93.897 | 333.789 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -164.290 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -639.918 | 0.000 | 0.000 | 83.619 | 299.766 | 289.614 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -33.081 |
CORE_MID | 0.000 | 0.000 | 3.839 | -5033.681 | 0.000 | 0.000 | 848.456 | 2997.664 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1712.406 |
CORE_TOP | 0.000 | 0.000 | 23.190 | -446.261 | 0.000 | 0.000 | 88.959 | 299.766 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -255.267 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 2.752 | -81.767 | 0.000 | 0.000 | 11.121 | 37.639 | 36.365 | 32.657 | 0.000 | 0.135 | 71.500 | 0.000 | -104.209 | 0.000 | -6.192 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 2.154 | -90.247 | 0.000 | 0.000 | 7.190 | 24.256 | 23.435 | 79.964 | 0.000 | 0.100 | 21.244 | 0.000 | -64.025 | 0.000 | -4.071 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 3.849 | -149.046 | 0.000 | 0.000 | 10.916 | 37.639 | 36.366 | 166.932 | 0.000 | 0.135 | 0.001 | 0.000 | -94.836 | 0.000 | -6.219 | -5.738 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.482 | -120.053 | 0.000 | 0.000 | 7.228 | 24.256 | 23.435 | 72.658 | 0.000 | 0.089 | 67.757 | 0.000 | -71.447 | 0.000 | -4.406 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 168.213 | -667.830 | 0.000 | 0.000 | 116.192 | 376.387 | 363.654 | 344.249 | 0.000 | 3.455 | 387.040 | 0.000 | -960.545 | 0.000 | -130.813 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 94.155 | -765.133 | 0.000 | 0.000 | 53.639 | 242.558 | 234.352 | 795.672 | 0.000 | 2.198 | 43.833 | 0.000 | -611.660 | 0.000 | -89.614 | -0.003 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 105.788 | -1411.545 | 0.000 | 0.000 | 110.056 | 376.395 | 363.660 | 1655.645 | 0.000 | 3.086 | 0.027 | 0.000 | -933.891 | 0.000 | -140.413 | -128.781 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 76.772 | -823.228 | 0.000 | 0.000 | 75.021 | 242.558 | 234.351 | 743.178 | 0.000 | 2.256 | 187.049 | 0.000 | -646.596 | 0.000 | -91.361 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 44.418 | -67.517 | 0.000 | 0.000 | 11.831 | 37.639 | 36.365 | 35.308 | 0.000 | 0.447 | 6.130 | 0.000 | -89.416 | 0.000 | -15.204 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 24.834 | -75.159 | 0.000 | 0.000 | 7.377 | 24.256 | 23.435 | 80.365 | 0.000 | 0.262 | 0.000 | 0.000 | -57.226 | 0.000 | -10.465 | -17.680 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 31.158 | -135.653 | 0.000 | 0.000 | 11.222 | 37.639 | 36.366 | 166.640 | 0.000 | 0.391 | 0.003 | 0.000 | -86.764 | 0.000 | -16.287 | -44.712 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 19.995 | -79.416 | 0.000 | 0.000 | 7.554 | 24.256 | 23.435 | 74.313 | 0.000 | 0.277 | 1.278 | 0.000 | -60.928 | 0.000 | -10.765 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -134.648 | 0.000 | 0.000 | 0.950 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -28.530 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 3.397 | -1180.829 | 0.000 | 0.000 | 9.502 | 83.466 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -454.342 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 1.988 | -104.153 | 0.000 | 0.000 | 0.950 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -61.013 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.953 | -7171.603 | 0.000 | 0.000 | 22.521 | 94.114 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -440.843 |
GROUNDFLOOR_PLENUM | 0.917 | -86.370 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.242 | 99.020 | 0.000 | 0.000 | 0.000 | -13.809 | 0.000 |
MIDFLOOR_PLENUM | 68.800 | -633.897 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.558 | 796.478 | 0.000 | 0.000 | 0.000 | -235.940 | -0.003 |
TOPFLOOR_PLENUM | 92.431 | -128.163 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.335 | 58.341 | 0.000 | 0.000 | 0.000 | -22.944 | -0.007 |
Total Facility | 162.148 | -848.430 | 608.859 | -19866.403 | 0.000 | 0.000 | 1578.202 | 5610.736 | 14676.396 | 4247.582 | 0.000 | 17.966 | 1739.701 | 0.000 | -3781.542 | 0.000 | -798.502 | -3346.696 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 05-JUN-04:11 | 0.00 | 0.00 | 0.00 | -133993.95 | 0.00 | 0.00 | 0.00 | 3238.31 | 13457.54 | 0.00 | 0.00 | 0.00 | 117298.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 05-SEP-04:11 | 0.00 | 0.00 | 0.00 | -118114.26 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.65 | 0.00 | 0.00 | 0.00 | 109268.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 30-JUN-04:11 | 0.00 | 0.00 | 0.00 | -1054434.94 | 0.00 | 0.00 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 965976.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-04:11 | 0.00 | 0.00 | 0.00 | -114680.59 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.62 | 0.00 | 0.00 | 0.00 | 105834.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 16-JUL-13:01 | 0.00 | 0.00 | 0.00 | -21969.53 | 0.00 | 0.00 | 40.41 | 182.58 | 720.18 | 9120.11 | 0.00 | 197.67 | 11708.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 06-AUG-08:51 | 0.00 | 0.00 | 0.00 | -32964.63 | 0.00 | 0.00 | 17.11 | 117.66 | 464.11 | 20845.65 | 0.00 | 0.00 | 11555.73 | 0.00 | -0.00 | 0.00 | -35.63 | 0.00 |
PERIMETER_BOT_ZN_1 | 05-NOV-13:01 | 0.00 | 0.00 | 0.00 | -39395.35 | 0.00 | 0.00 | 23.65 | 182.58 | 720.19 | 36516.89 | 0.00 | 0.00 | 1984.22 | 0.00 | -0.00 | 0.00 | -32.18 | 0.00 |
PERIMETER_BOT_ZN_4 | 25-JUN-16:21 | 0.00 | 0.00 | 0.00 | -42967.91 | 0.00 | 0.00 | 12.64 | 117.66 | 464.11 | 22656.50 | 0.00 | 44.77 | 19672.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-15:11 | 0.00 | 0.00 | 0.00 | -277939.35 | 0.00 | 0.00 | 400.62 | 1825.79 | 7201.84 | 64430.76 | 0.00 | 7075.07 | 197005.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 16-JUL-09:11 | 0.00 | 0.00 | 0.00 | -347097.53 | 0.00 | 0.00 | 165.10 | 1176.61 | 4641.14 | 175086.51 | 0.00 | 1161.75 | 164866.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 05-NOV-12:51 | 0.00 | 0.00 | 0.00 | -403547.23 | 0.00 | 0.00 | 195.37 | 1825.83 | 7201.95 | 369111.11 | 0.00 | 0.00 | 25921.36 | 0.00 | -0.00 | 0.00 | -708.38 | 0.00 |
PERIMETER_MID_ZN_4 | 25-JUN-16:31 | 0.00 | 0.00 | 0.00 | -407177.04 | 0.00 | 0.00 | 123.51 | 1176.61 | 4641.11 | 210681.38 | 0.00 | 988.64 | 189565.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-14:42 | 0.00 | 0.00 | 0.00 | -17054.46 | 0.00 | 0.00 | 37.50 | 182.58 | 720.18 | 9598.50 | 0.00 | 912.26 | 5603.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 20-AUG-08:21 | 0.00 | 0.00 | 0.00 | -33736.90 | 0.00 | 0.00 | 18.49 | 117.66 | 464.11 | 22495.47 | 0.00 | 0.00 | 10847.44 | 0.00 | -0.00 | 0.00 | -206.28 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-12:51 | 0.00 | 0.00 | 0.00 | -46488.82 | 0.00 | 0.00 | 26.66 | 182.58 | 720.19 | 24771.45 | 0.00 | 0.00 | 20797.76 | 0.00 | -0.00 | 0.00 | -9.83 | 0.00 |
PERIMETER_TOP_ZN_4 | 04-JUN-16:41 | 0.00 | 0.00 | 0.00 | -43263.22 | 0.00 | 0.00 | 14.36 | 117.66 | 464.11 | 17252.93 | 0.00 | 0.00 | 25430.78 | 0.00 | -0.00 | 0.00 | -16.62 | 0.00 |
DATACENTER_BOT_ZN_6 | 13-AUG-18:13 | 0.00 | 0.00 | 0.00 | -8672.12 | 0.00 | 0.00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 837.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 11-AUG-18:15 | 0.00 | 0.00 | 0.00 | -82413.03 | 0.00 | 0.00 | 106.16 | 2429.28 | 77944.22 | 0.00 | 0.00 | 0.00 | 1933.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 11-AUG-18:10 | 0.00 | 0.00 | 0.00 | -8400.50 | 0.00 | 0.00 | 10.62 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 352.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 16-NOV-12:32 | 0.00 | 0.00 | 0.00 | -502051.68 | 0.00 | 0.00 | 1495.57 | 8217.58 | 284724.39 | 0.00 | 0.00 | 0.00 | 207614.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 06-JAN-05:01 | 0.00 | -14306.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15357.58 | 0.00 | -0.00 | 0.00 | -1051.45 | 0.00 |
MIDFLOOR_PLENUM | 12-FEB-05:01 | 0.00 | -242097.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278097.67 | 0.00 | -0.00 | 0.00 | -36000.15 | 0.00 |
TOPFLOOR_PLENUM | 26-JUN-13:05 | 0.00 | -40570.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.97 | 40446.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-AUG-04:11 | 0.00 | 78330.08 | 0.00 | -2142898.15 | 0.00 | 0.00 | 0.00 | 54433.43 | 587299.42 | 0.00 | 0.00 | 0.00 | 1601525.65 | 0.00 | -156238.46 | 0.00 | -22451.97 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 15-JUL-16:01 | 0.00 | 0.00 | 13634.97 | 0.00 | 0.00 | 0.00 | 520.15 | 1619.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29231.82 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 06-FEB-05:01 | 0.00 | 0.00 | 493833.01 | 0.00 | 0.00 | 0.00 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -582291.54 |
CORE_TOP | 06-FEB-04:01 | 0.00 | 0.00 | 115810.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1454.11 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -123202.72 |
PERIMETER_BOT_ZN_3 | 22-DEC-04:01 | 0.00 | 0.00 | 17951.44 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11314.64 | 0.00 | -1171.95 | -6392.99 |
PERIMETER_BOT_ZN_2 | 22-DEC-04:01 | 0.00 | 0.00 | 17384.99 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7430.06 | 0.00 | -775.55 | -9777.51 |
PERIMETER_BOT_ZN_1 | 22-DEC-04:01 | 0.00 | 0.00 | 24065.81 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11429.75 | 0.00 | -1151.31 | -12412.91 |
PERIMETER_BOT_ZN_4 | 21-DEC-05:01 | 0.00 | 0.00 | 15010.20 | 0.00 | 0.00 | 0.00 | 0.00 | 235.32 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9941.04 | 0.00 | -590.55 | -5194.40 |
PERIMETER_MID_ZN_3 | 19-MAR-08:11 | 0.00 | 0.00 | 272806.00 | 0.00 | 0.00 | 0.00 | 922.91 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -66535.30 | 0.00 | -40024.49 | -176196.76 |
PERIMETER_MID_ZN_2 | 19-MAR-08:11 | 0.00 | 0.00 | 246538.85 | 0.00 | 0.00 | 0.00 | 596.32 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -39596.33 | 0.00 | -26936.92 | -186419.67 |
PERIMETER_MID_ZN_1 | 19-MAR-08:11 | 0.00 | 0.00 | 292613.41 | 0.00 | 0.00 | 0.00 | 922.54 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -59716.23 | 0.00 | -40179.55 | -202667.95 |
PERIMETER_MID_ZN_4 | 19-MAR-08:11 | 0.00 | 0.00 | 257100.76 | 0.00 | 0.00 | 0.00 | 592.61 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44943.67 | 0.00 | -27309.17 | -191258.25 |
PERIMETER_TOP_ZN_3 | 19-MAR-07:51 | 0.00 | 0.00 | 38571.65 | 0.00 | 0.00 | 0.00 | 94.79 | 182.58 | 720.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8807.20 | 0.00 | -5235.94 | -25526.06 |
PERIMETER_TOP_ZN_2 | 19-MAR-07:51 | 0.00 | 0.00 | 29141.29 | 0.00 | 0.00 | 0.00 | 61.18 | 117.66 | 464.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5854.53 | 0.00 | -3507.76 | -20421.96 |
PERIMETER_TOP_ZN_1 | 19-MAR-07:51 | 0.00 | 0.00 | 39081.64 | 0.00 | 0.00 | 0.00 | 94.76 | 182.58 | 720.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8820.01 | 0.00 | -5243.69 | -26015.47 |
PERIMETER_TOP_ZN_4 | 19-MAR-07:51 | 0.00 | 0.00 | 32032.65 | 0.00 | 0.00 | 0.00 | 60.75 | 117.66 | 464.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6011.31 | 0.00 | -3591.60 | -23072.27 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 01-JAN-06:03 | 0.00 | 0.00 | 15373.46 | 0.00 | 0.00 | 0.00 | 53.38 | 404.88 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -35317.78 |
DATACENTER_TOP_ZN_6 | 16-JAN-18:53 | 0.00 | 0.00 | 1590.41 | 0.00 | 0.00 | 0.00 | 0.00 | 40.49 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3579.50 |
DATACENTER_BASEMENT_ZN_6 | 30-SEP-23:11 | 0.00 | 0.00 | 31869.52 | 0.00 | 0.00 | 0.00 | 0.00 | 456.53 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -222142.32 |
GROUNDFLOOR_PLENUM | 05-NOV-15:01 | 16323.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -118.46 | -16204.85 |
MIDFLOOR_PLENUM | 01-JAN-13:52 | 180957.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -16561.41 | -164395.86 |
TOPFLOOR_PLENUM | 23-DEC-06:12 | 56306.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1403.19 | -54903.57 |
Total Facility | 13-FEB-05:01 | -104298.00 | 108921.05 | 1646897.83 | -108921.05 | 0.00 | 0.00 | 0.00 | 54433.43 | 350716.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -338479.53 | 0.00 | -106752.16 | -1502518.20 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 17.5094 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 14.9344 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 174.4901 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 138.4289 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 20.2009 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 17.5648 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 8.4885 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 8.4885 | 0.1414 | 1.0000 | Not calculated | 1.2002 | 0.1414 | ||
AIRLOOP DATACENTER BASEMENT | 38.6929 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 38.6932 | 0.0087 | 1.0000 | Not calculated | 0.3384 | 0.0087 | ||
AIRLOOP DATACENTER BOT | 0.9253 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.9253 | 0.0169 | 1.0000 | Not calculated | 0.0156 | 0.0169 | ||
AIRLOOP DATACENTER MID | 8.9033 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 8.9033 | 0.0176 | 1.0000 | Not calculated | 0.1563 | 0.0176 | ||
AIRLOOP DATACENTER TOP | 0.9211 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.9211 | 0.0170 | 1.0000 | Not calculated | 0.0156 | 0.0170 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 8.7547 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.2528 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 87.2451 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 52.3470 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.1005 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.0603 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 2.5466 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 2.5466 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.4713 | ||
AIRLOOP DATACENTER BASEMENT | 19.3464 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 19.3464 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0175 | ||
AIRLOOP DATACENTER BOT | 0.9253 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.9253 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0169 | ||
AIRLOOP DATACENTER MID | 8.9033 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 8.9033 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0176 | ||
AIRLOOP DATACENTER TOP | 0.9211 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.9211 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0170 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 8.4885 | 8.4885 | 2.5466 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.0660 | 9.0660 | 2.7198 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 86.2614 | 86.2614 | 25.8784 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.7965 | 9.7965 | 2.9389 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5942 | 1.5942 | 0.4783 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0043 | 2.0043 | 0.6013 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2853 | 2.2853 | 0.6856 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5596 | 2.5596 | 0.7679 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 20.7882 | 20.7882 | 6.2364 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 21.1713 | 21.1713 | 6.3514 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 22.3962 | 22.3962 | 6.7189 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 23.8730 | 23.8730 | 7.1619 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8111 | 2.8111 | 0.8433 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1329 | 2.1329 | 0.6399 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8522 | 2.8522 | 0.8557 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6082 | 2.6082 | 0.7825 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9253 | 0.9253 | 0.9253 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 8.9033 | 8.9033 | 8.9033 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9211 | 0.9211 | 0.9211 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 38.6929 | 38.6929 | 19.3464 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 17.5094 | 14.9344 | 17.5094 | 5.2528 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 174.4901 | 138.4289 | 174.4901 | 52.3470 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 20.2009 | 17.5648 | 20.2009 | 6.0603 | 0.0000 | 1.0000 |
CAV_BAS | 8.4885 | 8.4885 | 8.4885 | 2.5466 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 38.6929 | 38.6932 | 38.6929 | 19.3464 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.9253 | 0.9253 | 0.9253 | 0.9253 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 8.9033 | 8.9033 | 8.9033 | 8.9033 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.9211 | 0.9211 | 0.9211 | 0.9211 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 2.5466 | 2.5466 | 2.5466 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.5330 | 4.5330 | 2.7198 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 43.1307 | 43.1307 | 25.8784 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.8982 | 4.8982 | 2.9389 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7971 | 0.7971 | 0.4783 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0021 | 1.0021 | 0.6013 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1427 | 1.1427 | 0.6856 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2798 | 1.2798 | 0.7679 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.3941 | 10.3941 | 6.2364 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.5856 | 10.5856 | 6.3514 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.1981 | 11.1981 | 6.7189 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.9365 | 11.9365 | 7.1619 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4056 | 1.4056 | 0.8433 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0665 | 1.0665 | 0.6399 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4261 | 1.4261 | 0.8557 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3041 | 1.3041 | 0.7825 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9253 | 0.9253 | 0.9253 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 8.9033 | 8.9033 | 8.9033 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9211 | 0.9211 | 0.9211 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 19.3464 | 19.3464 | 19.3464 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 8.7547 | 5.2528 | 5.2528 | 5.2528 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 87.2451 | 52.3470 | 52.3470 | 52.3470 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.1005 | 6.0603 | 6.0603 | 6.0603 | 0.0000 | 1.0000 |
CAV_BAS | 2.5466 | 2.5466 | 2.5466 | 2.5466 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 19.3464 | 19.3464 | 19.3464 | 19.3464 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.9253 | 0.9253 | 0.9253 | 0.9253 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 8.9033 | 8.9033 | 8.9033 | 8.9033 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.9211 | 0.9211 | 0.9211 | 0.9211 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 47.67 |
Number of hours cooling loads not met | 481.00 |
Number of hours not met | 528.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 2464.87 | 1707687.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2063.06 | 389419.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 5610.74 | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 1006.50 | 64082.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 56.04 | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.31 | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 3429.19 | 397151.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 941.26 | 97555.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 79.78 | 48194.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1739.47 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 450.55 | 55493.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 32620.06 |
Natural Gas | 0.00 | 2464.87 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 35084.92 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 121.13 |
Space Heating | 0.00 |
Space Cooling | 44.54 |
Fans (All) | 74.03 |
Service Water Heating | 9.73 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 704.23 |
Subtotal | 704.23 |
Natural Gas [MJ/m2] | |
Space Heating | 53.21 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 53.21 |
Subtotal | 53.21 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.99 |
Space Heating | 7.03 |
Space Cooling | 5.88 |
Fans (All) | 9.77 |
Service Water Heating | 1.28 |
Receptacle Equipment | 41.83 |
Miscellaneous | 18.21 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
LTG_SCH_DATACENTER | 2939. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8688.33 | 71.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8740.83 | 19.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8742.83 | 17.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8729.83 | 30.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8638.33 | 121.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8742.17 | 17.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8729.17 | 30.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8739.83 | 20.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8739.67 | 20.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8738.33 | 21.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8740.33 | 19.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7987.00 | 773.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8696.83 | 63.17 | 0.00 | 0.00 | 0.00 |
Min | 7987.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 773.00 | 0.00 | 0.00 | 0.00 |
Average | 8706.62 | 53.38 | 0.00 | 0.00 | 0.00 |
Sum | 200252.33 | 1227.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368451.50 | 164.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 92724.83 | 10670.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368451.50 | 10670.17 | 0.00 | 0.00 | 0.00 |
Average | 79863.84 | 471.07 | 0.00 | 0.00 | 0.00 |
Sum | 1836868.33 | 10834.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8613.83 | 146.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8632.50 | 127.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8690.17 | 69.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8754.00 | 6.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8740.33 | 19.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8742.83 | 17.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8731.83 | 28.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8596.50 | 163.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8744.33 | 15.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8743.17 | 16.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8733.83 | 26.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8737.50 | 22.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8745.00 | 15.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8738.67 | 21.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8263.83 | 496.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8722.33 | 37.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8663.17 | 96.83 | 0.00 | 0.00 | 0.00 |
Min | 8263.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 496.17 | 0.00 | 0.00 | 0.00 |
Average | 8702.29 | 57.71 | 0.00 | 0.00 | 0.00 |
Sum | 200152.67 | 1327.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 368231.00 | 385.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330672.00 | 141.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330730.00 | 83.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330796.00 | 17.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 96071.17 | 7323.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368231.00 | 7323.83 | 0.00 | 0.00 | 0.00 |
Average | 79989.27 | 345.64 | 0.00 | 0.00 | 0.00 |
Sum | 1839753.17 | 7949.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:32
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.511228E+11 | 125563.88 | 30-JAN-05:01 | -1.0 | -1.0 | 0.539326E+10 | 7499.33 | 24-JAN-14:50 | -1.0 | -1.0 |
February | 0.420668E+11 | 125365.84 | 23-FEB-05:01 | -1.0 | -1.0 | 0.500853E+10 | 7499.23 | 07-FEB-10:39 | -1.0 | -1.0 |
March | 0.511998E+11 | 123869.34 | 01-MAR-05:01 | -5.0 | -5.0 | 0.602604E+10 | 7499.34 | 09-MAR-14:09 | 17.00 | 4.49 |
April | 0.495430E+11 | 109637.20 | 10-APR-04:11 | 2.67 | -3.2 | 0.530320E+10 | 7499.32 | 13-APR-13:20 | 17.00 | 9.55 |
May | 0.535026E+11 | 120208.13 | 12-MAY-05:02 | 1.50 | 0.50 | 0.576622E+10 | 7499.33 | 15-MAY-09:20 | 17.67 | 10.59 |
June | 0.601868E+11 | 134038.79 | 05-JUN-04:11 | 12.37 | 8.77 | 0.587461E+10 | 7581.43 | 19-JUN-09:39 | 26.63 | 15.72 |
July | 0.602428E+11 | 116963.60 | 03-JUL-04:11 | 11.00 | 7.64 | 0.546838E+10 | 7499.33 | 28-JUL-09:09 | 18.17 | 16.07 |
August | 0.712886E+11 | 115067.14 | 15-AUG-04:11 | 14.67 | 9.88 | 0.612742E+10 | 7499.28 | 15-AUG-09:50 | 16.67 | 11.86 |
September | 0.666619E+11 | 127718.24 | 05-SEP-04:11 | 14.40 | 9.51 | 0.541866E+10 | 7552.76 | 06-SEP-09:00 | 27.70 | 12.29 |
October | 0.637146E+11 | 133877.88 | 16-OCT-04:11 | 2.33 | -1.2 | 0.559762E+10 | 7499.33 | 18-OCT-09:39 | 17.00 | 5.66 |
November | 0.611359E+11 | 124292.92 | 01-NOV-04:01 | -3.0 | -3.0 | 0.553334E+10 | 7499.33 | 08-NOV-10:50 | 16.67 | 6.10 |
December | 0.580573E+11 | 116058.53 | 18-DEC-05:11 | 2.00 | -2.3 | 0.527320E+10 | 7499.19 | 13-DEC-14:00 | 2.00 | -2.3 |
Annual Sum or Average | 0.688723E+12 | 0.667905E+11 | ||||||||
Minimum of Months | 0.420668E+11 | 109637.20 | -5.0 | -5.0 | 0.500853E+10 | 7499.19 | -1.0 | -2.3 | ||
Maximum of Months | 0.712886E+11 | 134038.79 | 14.67 | 9.88 | 0.612742E+10 | 7581.43 | 27.70 | 16.07 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.426120E+11 | 105486.21 | 25-JAN-06:01 | 3.00 | -0.7 | 0.503311E+10 | 6734.88 | 10-JAN-10:20 | 3.00 | -0.7 |
February | 0.379919E+11 | 104221.15 | 23-FEB-06:01 | -1.0 | -1.0 | 0.455417E+10 | 6734.90 | 08-FEB-14:09 | -1.0 | -1.0 |
March | 0.508024E+11 | 110329.89 | 15-MAR-04:11 | 11.67 | 3.65 | 0.546869E+10 | 6734.89 | 27-MAR-09:39 | 0.67 | -0.6 |
April | 0.478294E+11 | 110006.44 | 21-APR-04:11 | 7.33 | 4.92 | 0.487026E+10 | 6734.97 | 13-APR-13:00 | 7.33 | 4.92 |
May | 0.528778E+11 | 106960.06 | 18-MAY-04:12 | 11.67 | 7.63 | 0.527933E+10 | 6734.91 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.631564E+11 | 114136.22 | 20-JUN-04:11 | 14.80 | 11.84 | 0.526742E+10 | 6734.87 | 09-JUN-09:09 | 14.80 | 11.84 |
July | 0.664077E+11 | 117228.71 | 31-JUL-04:11 | 15.33 | 13.37 | 0.489398E+10 | 6734.89 | 20-JUL-09:09 | 15.33 | 13.37 |
August | 0.750535E+11 | 117661.39 | 07-AUG-04:11 | 15.93 | 11.39 | 0.549634E+10 | 6734.88 | 10-AUG-09:39 | 24.67 | 13.62 |
September | 0.579317E+11 | 118124.32 | 05-SEP-04:11 | 14.40 | 9.51 | 0.487908E+10 | 6735.43 | 05-SEP-09:09 | 16.47 | 11.53 |
October | 0.505428E+11 | 113966.87 | 10-OCT-04:11 | 9.00 | 5.09 | 0.506382E+10 | 6734.92 | 03-OCT-13:09 | 9.00 | 5.09 |
November | 0.490434E+11 | 109879.31 | 09-NOV-05:11 | 8.33 | 4.83 | 0.501425E+10 | 6734.87 | 29-NOV-10:09 | -9.0 | -9.0 |
December | 0.456707E+11 | 107130.28 | 05-DEC-05:01 | -1.3 | -3.6 | 0.486904E+10 | 6734.85 | 06-DEC-10:09 | -2.0 | -3.4 |
Annual Sum or Average | 0.639920E+12 | 0.606895E+11 | ||||||||
Minimum of Months | 0.379919E+11 | 104221.15 | -1.3 | -3.6 | 0.455417E+10 | 6734.85 | -9.0 | -9.0 | ||
Maximum of Months | 0.750535E+11 | 118124.32 | 15.93 | 13.37 | 0.549634E+10 | 6735.43 | 24.67 | 13.62 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.336590E+11 | 65220.56 | 21-JAN-06:02 | 8.17 | 1.79 | 0.482311E+10 | 6734.85 | 10-JAN-10:50 | 8.17 | 1.79 |
February | 0.313347E+11 | 87806.11 | 18-FEB-06:01 | 7.00 | 2.02 | 0.435671E+10 | 6734.89 | 23-FEB-10:20 | 4.67 | 3.22 |
March | 0.399701E+11 | 98928.49 | 17-MAR-05:01 | 6.83 | 4.95 | 0.532111E+10 | 6734.88 | 29-MAR-13:00 | 1.00 | -2.1 |
April | 0.352831E+11 | 99186.69 | 21-APR-05:01 | 5.83 | 3.87 | 0.475036E+10 | 6734.96 | 13-APR-13:00 | 5.83 | 3.87 |
May | 0.452478E+11 | 100796.61 | 31-MAY-05:01 | 12.17 | 9.76 | 0.525156E+10 | 6734.90 | 26-MAY-13:09 | 12.17 | 9.76 |
June | 0.540595E+11 | 105405.71 | 30-JUN-04:11 | 19.60 | 10.11 | 0.525823E+10 | 6734.87 | 09-JUN-09:09 | 19.60 | 10.11 |
July | 0.528326E+11 | 104745.89 | 25-JUL-04:11 | 17.00 | 13.73 | 0.488463E+10 | 6734.88 | 20-JUL-09:09 | 17.00 | 13.73 |
August | 0.556449E+11 | 104322.25 | 11-AUG-04:11 | 16.00 | 11.53 | 0.549001E+10 | 6734.88 | 10-AUG-09:39 | 16.00 | 11.53 |
September | 0.476704E+11 | 103462.40 | 13-SEP-04:11 | 20.33 | 11.99 | 0.485974E+10 | 6735.34 | 05-SEP-09:09 | 20.33 | 11.99 |
October | 0.394386E+11 | 99656.44 | 11-OCT-05:01 | 10.17 | 3.29 | 0.497344E+10 | 6734.91 | 03-OCT-13:09 | 10.17 | 3.29 |
November | 0.350029E+11 | 96925.74 | 09-NOV-06:01 | 9.17 | 4.69 | 0.489536E+10 | 6734.89 | 17-NOV-14:20 | 13.33 | 5.89 |
December | 0.332266E+11 | 37417.73 | 15-DEC-16:13 | 4.67 | 1.42 | 0.459861E+10 | 6734.86 | 06-DEC-10:09 | 4.67 | 1.42 |
Annual Sum or Average | 0.503370E+12 | 0.594629E+11 | ||||||||
Minimum of Months | 0.313347E+11 | 37417.73 | 4.67 | 1.42 | 0.435671E+10 | 6734.85 | 1.00 | -2.1 | ||
Maximum of Months | 0.556449E+11 | 105405.71 | 20.33 | 13.73 | 0.549001E+10 | 6735.34 | 20.33 | 13.73 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233950E+11 | 35159.43 | 20-JAN-16:14 | 16.00 | 6.84 | 0.421346E+10 | 6734.72 | 25-JAN-14:00 | 14.00 | 4.48 |
February | 0.217517E+11 | 31413.60 | 17-FEB-16:53 | 13.00 | 6.46 | 0.386944E+10 | 6734.87 | 17-FEB-14:00 | 13.00 | 6.46 |
March | 0.312220E+11 | 49979.37 | 15-MAR-15:30 | 19.50 | 5.56 | 0.486573E+10 | 6734.87 | 30-MAR-13:09 | 12.83 | 5.50 |
April | 0.310120E+11 | 50550.33 | 21-APR-13:53 | 15.00 | 5.55 | 0.437585E+10 | 6734.95 | 13-APR-13:00 | 15.00 | 5.55 |
May | 0.421023E+11 | 56077.33 | 31-MAY-15:40 | 28.00 | 14.79 | 0.504101E+10 | 6734.88 | 26-MAY-13:09 | 28.00 | 14.79 |
June | 0.590493E+11 | 111061.98 | 16-JUN-05:01 | 15.00 | 12.19 | 0.522169E+10 | 6734.86 | 15-JUN-09:09 | 15.00 | 12.19 |
July | 0.568941E+11 | 114724.78 | 24-JUL-04:11 | 18.00 | 14.77 | 0.485619E+10 | 6734.88 | 20-JUL-09:09 | 18.00 | 14.77 |
August | 0.586843E+11 | 110915.88 | 11-AUG-05:01 | 16.17 | 11.25 | 0.544926E+10 | 6734.88 | 10-AUG-09:39 | 16.17 | 11.25 |
September | 0.454669E+11 | 108289.03 | 13-SEP-05:02 | 19.72 | 11.93 | 0.473895E+10 | 6735.26 | 05-SEP-09:09 | 19.72 | 11.93 |
October | 0.300669E+11 | 49030.49 | 11-OCT-15:30 | 25.00 | 9.04 | 0.446630E+10 | 6734.90 | 03-OCT-13:09 | 25.00 | 9.04 |
November | 0.252597E+11 | 36703.15 | 08-NOV-16:13 | 16.33 | 7.18 | 0.427110E+10 | 6734.86 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.213593E+11 | 27041.83 | 01-DEC-16:12 | 16.00 | 5.88 | 0.398050E+10 | 6675.89 | 14-DEC-14:00 | 16.00 | 4.43 |
Annual Sum or Average | 0.446263E+12 | 0.553495E+11 | ||||||||
Minimum of Months | 0.213593E+11 | 27041.83 | 13.00 | 5.55 | 0.386944E+10 | 6675.89 | 12.83 | 4.43 | ||
Maximum of Months | 0.590493E+11 | 114724.78 | 28.00 | 14.79 | 0.544926E+10 | 6735.26 | 28.00 | 14.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.321821E+10 | 5099.44 | 20-JAN-14:30 | 20.50 | 6.87 | 0.523487E+09 | 820.99 | 23-JAN-14:00 | 19.00 | 5.82 |
February | 0.276295E+10 | 4937.98 | 26-FEB-14:31 | 17.00 | 4.38 | 0.469533E+09 | 840.45 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.483596E+10 | 8101.27 | 14-MAR-14:30 | 23.00 | 7.59 | 0.613089E+09 | 845.63 | 07-MAR-14:09 | 23.00 | 7.59 |
April | 0.527575E+10 | 8916.03 | 20-APR-13:30 | 21.50 | 8.83 | 0.564995E+09 | 845.65 | 13-APR-13:30 | 21.50 | 8.83 |
May | 0.772809E+10 | 11157.80 | 17-MAY-13:30 | 29.00 | 11.78 | 0.646608E+09 | 845.64 | 18-MAY-13:09 | 24.00 | 11.61 |
June | 0.120531E+11 | 21956.99 | 25-JUN-17:41 | 31.78 | 13.99 | 0.660552E+09 | 845.78 | 14-JUN-13:39 | 31.78 | 13.99 |
July | 0.124541E+11 | 21969.80 | 16-JUL-13:01 | 36.67 | 14.80 | 0.614084E+09 | 845.85 | 18-JUL-13:39 | 32.33 | 15.11 |
August | 0.125431E+11 | 13382.63 | 18-AUG-13:50 | 34.67 | 13.33 | 0.687598E+09 | 845.84 | 18-AUG-13:50 | 34.67 | 13.33 |
September | 0.864695E+10 | 11932.11 | 11-SEP-14:30 | 28.85 | 13.58 | 0.601667E+09 | 845.71 | 05-SEP-09:09 | 28.85 | 13.58 |
October | 0.506352E+10 | 8472.84 | 10-OCT-14:50 | 25.00 | 8.50 | 0.571406E+09 | 845.64 | 03-OCT-13:09 | 25.00 | 8.50 |
November | 0.414945E+10 | 6837.20 | 09-NOV-13:30 | 20.00 | 8.78 | 0.541134E+09 | 845.63 | 17-NOV-14:09 | 13.67 | 6.17 |
December | 0.303612E+10 | 5334.46 | 04-DEC-14:04 | 19.83 | 6.62 | 0.504429E+09 | 845.62 | 04-DEC-14:20 | 19.67 | 6.52 |
Annual Sum or Average | 0.817673E+11 | 0.699858E+10 | ||||||||
Minimum of Months | 0.276295E+10 | 4937.98 | 17.00 | 4.38 | 0.469533E+09 | 820.99 | 13.67 | 4.75 | ||
Maximum of Months | 0.125431E+11 | 21969.80 | 36.67 | 14.80 | 0.687598E+09 | 845.85 | 34.67 | 15.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.390326E+10 | 8907.63 | 20-JAN-09:25 | 12.00 | 3.86 | 0.339690E+09 | 544.96 | 10-JAN-10:09 | 12.00 | 3.86 |
February | 0.384181E+10 | 19364.40 | 26-FEB-09:11 | 11.00 | 2.57 | 0.313371E+09 | 544.96 | 23-FEB-10:09 | 11.00 | 2.57 |
March | 0.623945E+10 | 29996.62 | 12-MAR-09:11 | 14.33 | 5.23 | 0.395112E+09 | 544.96 | 27-MAR-09:09 | 1.67 | -0.8 |
April | 0.621783E+10 | 22525.29 | 09-APR-08:22 | 10.50 | 4.84 | 0.360928E+09 | 544.98 | 13-APR-13:30 | 16.50 | 9.66 |
May | 0.858952E+10 | 15430.89 | 16-MAY-08:30 | 21.50 | 11.33 | 0.413533E+09 | 545.01 | 31-MAY-09:39 | 24.33 | 13.31 |
June | 0.125272E+11 | 31020.15 | 11-JUN-08:61 | 17.67 | 10.77 | 0.423476E+09 | 545.00 | 20-JUN-09:30 | 25.00 | 15.04 |
July | 0.122042E+11 | 30426.01 | 09-JUL-08:31 | 23.33 | 12.65 | 0.392526E+09 | 545.61 | 17-JUL-09:09 | 31.50 | 14.04 |
August | 0.130892E+11 | 32967.14 | 06-AUG-08:51 | 25.00 | 15.42 | 0.439842E+09 | 545.49 | 07-AUG-09:09 | 26.33 | 14.81 |
September | 0.970026E+10 | 29441.43 | 17-SEP-09:11 | 18.50 | 10.61 | 0.385038E+09 | 545.03 | 05-SEP-09:09 | 18.50 | 10.61 |
October | 0.600895E+10 | 28038.91 | 01-OCT-09:01 | 13.17 | 7.72 | 0.360804E+09 | 544.96 | 03-OCT-09:09 | 8.50 | 7.11 |
November | 0.460298E+10 | 23909.35 | 05-NOV-09:01 | 13.00 | 4.07 | 0.342984E+09 | 544.96 | 14-NOV-10:09 | 3.17 | 2.15 |
December | 0.332253E+10 | 6789.11 | 01-DEC-09:21 | 11.00 | 3.52 | 0.319758E+09 | 544.96 | 01-DEC-10:09 | 14.83 | 5.40 |
Annual Sum or Average | 0.902471E+11 | 0.448706E+10 | ||||||||
Minimum of Months | 0.332253E+10 | 6789.11 | 10.50 | 2.57 | 0.313371E+09 | 544.96 | 1.67 | -0.8 | ||
Maximum of Months | 0.130892E+11 | 32967.14 | 25.00 | 15.42 | 0.439842E+09 | 545.61 | 31.50 | 15.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113653E+11 | 33040.85 | 22-JAN-12:31 | 6.67 | 3.45 | 0.588333E+09 | 873.37 | 20-JAN-14:09 | 6.67 | 3.45 |
February | 0.100942E+11 | 37475.25 | 26-FEB-13:11 | 17.67 | 4.65 | 0.531882E+09 | 845.66 | 08-FEB-14:09 | 17.67 | 4.65 |
March | 0.112768E+11 | 36539.93 | 12-MAR-12:31 | 18.67 | 6.04 | 0.629206E+09 | 847.28 | 14-MAR-13:00 | 23.00 | 7.59 |
April | 0.852845E+10 | 18842.09 | 19-APR-13:10 | 22.00 | 8.49 | 0.558421E+09 | 845.69 | 13-APR-13:30 | 22.00 | 8.49 |
May | 0.100978E+11 | 15989.52 | 07-MAY-13:31 | 21.00 | 9.43 | 0.629822E+09 | 845.67 | 18-MAY-13:09 | 24.00 | 11.61 |
June | 0.140066E+11 | 31965.82 | 25-JUN-13:41 | 32.70 | 13.05 | 0.652362E+09 | 845.67 | 16-JUN-13:20 | 32.70 | 13.05 |
July | 0.148517E+11 | 30978.62 | 04-JUL-14:01 | 27.83 | 12.39 | 0.608348E+09 | 845.66 | 27-JUL-13:09 | 28.50 | 17.50 |
August | 0.180122E+11 | 34224.97 | 27-AUG-13:11 | 26.00 | 15.04 | 0.682285E+09 | 846.90 | 29-AUG-13:09 | 28.83 | 16.25 |
September | 0.156065E+11 | 36002.15 | 17-SEP-12:31 | 25.53 | 10.74 | 0.599900E+09 | 905.95 | 28-SEP-13:09 | 30.50 | 11.31 |
October | 0.128242E+11 | 38311.87 | 09-OCT-13:21 | 22.00 | 8.88 | 0.579313E+09 | 877.15 | 10-OCT-13:09 | 24.17 | 8.07 |
November | 0.123293E+11 | 39398.01 | 05-NOV-13:01 | 21.00 | 6.54 | 0.585579E+09 | 870.89 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.100532E+11 | 34586.95 | 17-DEC-12:51 | 18.00 | 5.78 | 0.558038E+09 | 846.33 | 04-DEC-14:09 | 18.00 | 5.78 |
Annual Sum or Average | 0.149046E+12 | 0.720349E+10 | ||||||||
Minimum of Months | 0.852845E+10 | 15989.52 | 6.67 | 3.45 | 0.531882E+09 | 845.66 | 6.67 | 3.45 | ||
Maximum of Months | 0.180122E+11 | 39398.01 | 32.70 | 15.04 | 0.682285E+09 | 905.95 | 32.70 | 17.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.584275E+10 | 12437.82 | 20-JAN-15:40 | 18.67 | 7.30 | 0.338912E+09 | 544.95 | 09-JAN-14:39 | 18.67 | 7.30 |
February | 0.550568E+10 | 31091.51 | 26-FEB-15:51 | 18.00 | 5.19 | 0.307401E+09 | 544.96 | 14-FEB-14:00 | 18.00 | 5.19 |
March | 0.902409E+10 | 39348.32 | 26-MAR-16:51 | 13.00 | 6.02 | 0.385720E+09 | 544.96 | 16-MAR-13:39 | 13.00 | 6.02 |
April | 0.904555E+10 | 23529.05 | 08-APR-17:42 | 14.33 | 4.60 | 0.358897E+09 | 544.98 | 13-APR-13:30 | 16.50 | 9.66 |
May | 0.103360E+11 | 18547.69 | 29-MAY-15:51 | 16.00 | 11.20 | 0.396829E+09 | 544.97 | 18-MAY-13:09 | 16.00 | 11.20 |
June | 0.146294E+11 | 42968.28 | 25-JUN-16:21 | 32.70 | 13.84 | 0.418448E+09 | 544.97 | 16-JUN-13:20 | 32.70 | 13.84 |
July | 0.149287E+11 | 38557.04 | 02-JUL-16:31 | 28.00 | 12.40 | 0.392576E+09 | 544.97 | 14-JUL-09:09 | 24.33 | 11.85 |
August | 0.171204E+11 | 38302.98 | 13-AUG-16:51 | 22.00 | 9.79 | 0.441712E+09 | 544.98 | 28-AUG-13:30 | 24.50 | 16.32 |
September | 0.113367E+11 | 40592.05 | 17-SEP-16:31 | 26.27 | 10.77 | 0.374247E+09 | 545.01 | 01-SEP-13:00 | 26.27 | 10.77 |
October | 0.843954E+10 | 38554.04 | 08-OCT-16:41 | 17.17 | 8.30 | 0.352330E+09 | 544.96 | 10-OCT-13:30 | 24.50 | 8.32 |
November | 0.751559E+10 | 36358.15 | 05-NOV-15:01 | 20.67 | 6.59 | 0.348915E+09 | 544.96 | 30-NOV-14:00 | 5.00 | 0.20 |
December | 0.632872E+10 | 18840.68 | 17-DEC-15:31 | 16.50 | 5.23 | 0.332487E+09 | 544.96 | 15-DEC-14:39 | 16.50 | 5.23 |
Annual Sum or Average | 0.120053E+12 | 0.444847E+10 | ||||||||
Minimum of Months | 0.550568E+10 | 12437.82 | 13.00 | 4.60 | 0.307401E+09 | 544.95 | 5.00 | 0.20 | ||
Maximum of Months | 0.171204E+11 | 42968.28 | 32.70 | 13.84 | 0.441712E+09 | 545.01 | 32.70 | 16.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194448E+10 | 5706.37 | 20-JAN-15:02 | 19.67 | 6.93 | 0.473176E+09 | 700.08 | 20-JAN-14:00 | 19.67 | 6.93 |
February | 0.166356E+10 | 5391.70 | 17-FEB-14:51 | 15.00 | 6.93 | 0.427127E+09 | 689.53 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.356774E+10 | 6571.66 | 14-MAR-13:40 | 23.33 | 7.70 | 0.543733E+09 | 842.78 | 16-MAR-13:00 | 16.00 | 5.44 |
April | 0.379723E+10 | 6822.92 | 20-APR-13:30 | 21.50 | 8.83 | 0.504040E+09 | 845.62 | 28-APR-13:00 | 18.00 | 12.50 |
May | 0.711804E+10 | 10539.59 | 17-MAY-13:30 | 29.00 | 11.78 | 0.608488E+09 | 845.64 | 18-MAY-13:09 | 24.00 | 11.61 |
June | 0.113475E+11 | 19008.98 | 25-JUN-17:51 | 31.60 | 13.99 | 0.652522E+09 | 845.64 | 20-JUN-09:30 | 31.60 | 13.99 |
July | 0.111262E+11 | 27794.17 | 16-JUL-15:11 | 35.67 | 14.48 | 0.605675E+09 | 845.64 | 14-JUL-09:09 | 35.67 | 14.48 |
August | 0.103785E+11 | 12201.25 | 18-AUG-14:00 | 35.00 | 13.50 | 0.672324E+09 | 845.64 | 28-AUG-13:30 | 24.50 | 16.32 |
September | 0.786588E+10 | 11006.20 | 11-SEP-14:30 | 28.85 | 13.58 | 0.573175E+09 | 845.67 | 01-SEP-13:00 | 28.85 | 13.58 |
October | 0.407640E+10 | 6838.70 | 11-OCT-15:00 | 26.00 | 9.46 | 0.509025E+09 | 831.00 | 11-OCT-13:00 | 26.00 | 9.46 |
November | 0.246631E+10 | 6076.90 | 09-NOV-12:00 | 20.00 | 9.32 | 0.478719E+09 | 811.87 | 09-NOV-14:20 | 19.33 | 8.45 |
December | 0.143159E+10 | 5576.06 | 01-DEC-14:50 | 21.17 | 7.46 | 0.452187E+09 | 718.12 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.667834E+11 | 0.650019E+10 | ||||||||
Minimum of Months | 0.143159E+10 | 5391.70 | 15.00 | 6.93 | 0.427127E+09 | 689.53 | 14.00 | 4.75 | ||
Maximum of Months | 0.113475E+11 | 27794.17 | 35.67 | 14.48 | 0.672324E+09 | 845.67 | 35.67 | 16.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231069E+10 | 8085.32 | 20-JAN-11:03 | 18.33 | 6.81 | 0.238294E+09 | 548.49 | 19-JAN-15:09 | 18.33 | 6.81 |
February | 0.255613E+10 | 14288.87 | 27-FEB-11:01 | 12.33 | 3.94 | 0.221643E+09 | 548.49 | 17-FEB-15:09 | 12.33 | 3.94 |
March | 0.474883E+10 | 29965.61 | 12-MAR-09:01 | 14.17 | 5.14 | 0.282200E+09 | 548.49 | 27-MAR-10:09 | 0.33 | -0.4 |
April | 0.481836E+10 | 16076.54 | 11-APR-10:01 | 8.33 | 1.60 | 0.257042E+09 | 548.50 | 28-APR-14:09 | 17.83 | 12.33 |
May | 0.778390E+10 | 23923.07 | 28-MAY-09:12 | 12.67 | 8.79 | 0.298352E+09 | 548.55 | 16-MAY-10:09 | 12.67 | 8.79 |
June | 0.124171E+11 | 31663.29 | 11-JUN-07:41 | 16.83 | 10.75 | 0.310730E+09 | 548.52 | 09-JUN-12:09 | 16.83 | 10.75 |
July | 0.117257E+11 | 34709.33 | 16-JUL-09:11 | 33.33 | 14.70 | 0.288116E+09 | 548.53 | 05-JUL-10:09 | 33.33 | 14.70 |
August | 0.121556E+11 | 33769.85 | 20-AUG-08:21 | 24.50 | 14.15 | 0.321669E+09 | 548.53 | 29-AUG-10:09 | 22.62 | 14.51 |
September | 0.897038E+10 | 30919.71 | 04-SEP-08:41 | 23.85 | 13.24 | 0.279160E+09 | 548.53 | 01-SEP-14:09 | 23.85 | 13.24 |
October | 0.451977E+10 | 22294.26 | 01-OCT-10:11 | 14.33 | 8.00 | 0.257154E+09 | 548.50 | 10-OCT-14:09 | 25.00 | 8.67 |
November | 0.279630E+10 | 13908.76 | 07-NOV-11:01 | 16.67 | 5.90 | 0.241398E+09 | 548.49 | 06-NOV-15:09 | 16.67 | 5.90 |
December | 0.171083E+10 | 9255.86 | 29-DEC-11:01 | 8.17 | 2.65 | 0.222057E+09 | 548.49 | 14-DEC-15:09 | 8.17 | 2.65 |
Annual Sum or Average | 0.765136E+11 | 0.321781E+10 | ||||||||
Minimum of Months | 0.171083E+10 | 8085.32 | 8.17 | 1.60 | 0.221643E+09 | 548.49 | 0.33 | -0.4 | ||
Maximum of Months | 0.124171E+11 | 34709.33 | 33.33 | 14.70 | 0.321669E+09 | 548.55 | 33.33 | 14.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116816E+11 | 32733.32 | 22-JAN-12:42 | 6.83 | 3.54 | 0.583758E+09 | 943.59 | 20-JAN-14:09 | 6.83 | 3.54 |
February | 0.105180E+11 | 38196.01 | 26-FEB-13:31 | 17.33 | 4.46 | 0.527057E+09 | 882.38 | 17-FEB-14:09 | 17.33 | 4.46 |
March | 0.107038E+11 | 36537.26 | 12-MAR-12:21 | 18.50 | 6.07 | 0.618419E+09 | 875.99 | 15-MAR-13:30 | 20.50 | 6.02 |
April | 0.716900E+10 | 18998.37 | 12-APR-13:15 | 21.00 | 7.79 | 0.543484E+09 | 846.32 | 12-APR-13:20 | 21.00 | 7.79 |
May | 0.921097E+10 | 15426.33 | 16-MAY-13:20 | 27.33 | 12.20 | 0.619215E+09 | 845.68 | 10-MAY-13:09 | 27.33 | 12.20 |
June | 0.131026E+11 | 30897.85 | 25-JUN-15:11 | 33.43 | 13.65 | 0.646707E+09 | 845.67 | 16-JUN-13:20 | 33.43 | 13.65 |
July | 0.132812E+11 | 31887.61 | 30-JUL-13:51 | 29.00 | 19.75 | 0.603016E+09 | 845.66 | 27-JUL-13:09 | 29.00 | 19.75 |
August | 0.159022E+11 | 33844.95 | 27-AUG-13:11 | 26.00 | 15.04 | 0.675635E+09 | 863.34 | 31-AUG-13:20 | 30.00 | 11.86 |
September | 0.152706E+11 | 37731.35 | 04-SEP-13:21 | 29.40 | 13.40 | 0.594849E+09 | 958.84 | 28-SEP-13:20 | 30.50 | 11.31 |
October | 0.127835E+11 | 38962.39 | 09-OCT-13:11 | 22.00 | 8.98 | 0.572384E+09 | 917.89 | 10-OCT-13:30 | 24.50 | 8.32 |
November | 0.121043E+11 | 40359.99 | 05-NOV-12:51 | 21.00 | 6.57 | 0.581113E+09 | 930.36 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.942759E+10 | 36825.42 | 03-DEC-12:21 | 16.60 | 5.97 | 0.548493E+09 | 888.96 | 01-DEC-14:09 | 16.60 | 5.97 |
Annual Sum or Average | 0.141155E+12 | 0.711413E+10 | ||||||||
Minimum of Months | 0.716900E+10 | 15426.33 | 6.83 | 3.54 | 0.527057E+09 | 845.66 | 6.83 | 3.54 | ||
Maximum of Months | 0.159022E+11 | 40359.99 | 33.43 | 19.75 | 0.675635E+09 | 958.84 | 33.43 | 19.75 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.332631E+10 | 10587.31 | 20-JAN-15:50 | 18.33 | 7.40 | 0.322465E+09 | 544.04 | 20-JAN-14:00 | 18.33 | 7.40 |
February | 0.325937E+10 | 12004.83 | 17-FEB-16:23 | 13.50 | 6.66 | 0.293172E+09 | 544.96 | 17-FEB-14:00 | 13.50 | 6.66 |
March | 0.549983E+10 | 34209.67 | 26-MAR-16:51 | 13.00 | 6.02 | 0.355833E+09 | 544.96 | 03-MAR-14:39 | 13.00 | 6.02 |
April | 0.524054E+10 | 23960.86 | 08-APR-17:03 | 15.67 | 5.07 | 0.322692E+09 | 544.95 | 21-APR-13:00 | 15.00 | 5.55 |
May | 0.814106E+10 | 26123.14 | 07-MAY-15:41 | 22.17 | 8.70 | 0.374641E+09 | 544.96 | 18-MAY-13:20 | 24.00 | 11.54 |
June | 0.124897E+11 | 40718.58 | 25-JUN-16:31 | 32.70 | 13.89 | 0.403614E+09 | 544.96 | 20-JUN-13:00 | 32.70 | 13.89 |
July | 0.112811E+11 | 35809.92 | 01-JUL-17:41 | 28.17 | 10.55 | 0.375467E+09 | 544.96 | 18-JUL-13:00 | 31.00 | 15.59 |
August | 0.118290E+11 | 38348.59 | 20-AUG-15:41 | 28.00 | 14.08 | 0.416339E+09 | 544.97 | 28-AUG-13:30 | 24.50 | 16.32 |
September | 0.915575E+10 | 35521.45 | 10-SEP-16:31 | 31.07 | 12.39 | 0.353012E+09 | 544.99 | 01-SEP-13:00 | 31.07 | 12.39 |
October | 0.571318E+10 | 35723.41 | 08-OCT-16:31 | 17.33 | 8.37 | 0.330444E+09 | 544.96 | 20-OCT-13:00 | 20.00 | 5.78 |
November | 0.384350E+10 | 22334.29 | 05-NOV-15:31 | 19.67 | 6.02 | 0.322452E+09 | 544.96 | 22-NOV-14:39 | 14.33 | 4.83 |
December | 0.254382E+10 | 9499.10 | 01-DEC-15:30 | 19.50 | 7.14 | 0.304577E+09 | 544.90 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.823232E+11 | 0.417471E+10 | ||||||||
Minimum of Months | 0.254382E+10 | 9499.10 | 13.00 | 5.07 | 0.293172E+09 | 544.04 | 13.00 | 4.83 | ||
Maximum of Months | 0.124897E+11 | 40718.58 | 32.70 | 14.08 | 0.416339E+09 | 544.99 | 32.70 | 16.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124205E+10 | 6670.72 | 20-JAN-13:30 | 21.00 | 6.97 | 0.465887E+09 | 673.22 | 20-JAN-14:00 | 20.00 | 6.78 |
February | 0.114777E+10 | 5782.81 | 26-FEB-15:21 | 17.50 | 4.81 | 0.422726E+09 | 662.47 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.317034E+10 | 7162.36 | 14-MAR-13:10 | 23.83 | 7.85 | 0.526686E+09 | 807.10 | 14-MAR-13:00 | 23.00 | 7.59 |
April | 0.375380E+10 | 7361.89 | 20-APR-13:30 | 21.50 | 8.83 | 0.482141E+09 | 845.58 | 20-APR-13:00 | 21.00 | 8.51 |
May | 0.734942E+10 | 11191.55 | 17-MAY-13:40 | 29.00 | 11.73 | 0.571079E+09 | 845.64 | 18-MAY-13:09 | 24.00 | 11.61 |
June | 0.126476E+11 | 14604.88 | 26-JUN-15:00 | 39.40 | 15.63 | 0.635195E+09 | 845.64 | 16-JUN-13:20 | 39.40 | 15.63 |
July | 0.123900E+11 | 17054.07 | 16-JUL-14:42 | 35.83 | 14.69 | 0.588706E+09 | 845.63 | 18-JUL-13:00 | 31.00 | 15.59 |
August | 0.115238E+11 | 13467.38 | 16-AUG-14:00 | 37.00 | 16.36 | 0.648394E+09 | 845.65 | 28-AUG-13:30 | 24.50 | 16.32 |
September | 0.831033E+10 | 11766.22 | 11-SEP-14:30 | 28.85 | 13.58 | 0.543753E+09 | 845.67 | 01-SEP-13:00 | 28.85 | 13.58 |
October | 0.344001E+10 | 7993.18 | 11-OCT-13:20 | 26.33 | 9.54 | 0.488508E+09 | 800.46 | 11-OCT-15:39 | 24.67 | 8.90 |
November | 0.167720E+10 | 6676.39 | 07-NOV-13:30 | 21.00 | 7.19 | 0.467353E+09 | 751.49 | 09-NOV-14:09 | 19.67 | 8.52 |
December | 0.865444E+09 | 5699.39 | 01-DEC-13:40 | 21.67 | 7.88 | 0.448192E+09 | 675.87 | 01-DEC-14:00 | 21.00 | 7.36 |
Annual Sum or Average | 0.675178E+11 | 0.628862E+10 | ||||||||
Minimum of Months | 0.865444E+09 | 5699.39 | 17.50 | 4.81 | 0.422726E+09 | 662.47 | 14.00 | 4.75 | ||
Maximum of Months | 0.126476E+11 | 17054.07 | 39.40 | 16.36 | 0.648394E+09 | 845.67 | 39.40 | 16.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205080E+10 | 5778.49 | 20-JAN-13:10 | 21.00 | 6.97 | 0.310823E+09 | 544.43 | 20-JAN-10:30 | 21.00 | 6.97 |
February | 0.231388E+10 | 6283.36 | 26-FEB-11:21 | 15.50 | 4.06 | 0.291460E+09 | 544.96 | 23-FEB-10:20 | 15.50 | 4.06 |
March | 0.439914E+10 | 12756.78 | 12-MAR-09:11 | 14.33 | 5.23 | 0.376857E+09 | 544.97 | 14-MAR-13:09 | 23.83 | 7.85 |
April | 0.466738E+10 | 13781.29 | 21-APR-09:02 | 12.00 | 5.90 | 0.342377E+09 | 544.98 | 13-APR-13:30 | 12.00 | 5.90 |
May | 0.752807E+10 | 15228.42 | 16-MAY-09:00 | 23.00 | 11.65 | 0.398326E+09 | 545.02 | 31-MAY-09:39 | 24.33 | 13.31 |
June | 0.128966E+11 | 31042.88 | 11-JUN-08:61 | 17.67 | 10.77 | 0.422037E+09 | 545.01 | 20-JUN-09:30 | 25.00 | 15.04 |
July | 0.121668E+11 | 32622.66 | 09-JUL-09:01 | 24.67 | 12.86 | 0.389359E+09 | 545.67 | 17-JUL-09:39 | 33.00 | 14.28 |
August | 0.125047E+11 | 33730.20 | 20-AUG-08:21 | 24.50 | 14.15 | 0.437193E+09 | 545.62 | 16-AUG-09:39 | 24.50 | 14.15 |
September | 0.879958E+10 | 31045.10 | 04-SEP-10:11 | 26.47 | 13.30 | 0.376685E+09 | 545.03 | 05-SEP-09:09 | 16.47 | 11.53 |
October | 0.402255E+10 | 10051.83 | 11-OCT-09:50 | 22.53 | 8.38 | 0.344427E+09 | 544.96 | 03-OCT-09:09 | 22.53 | 8.38 |
November | 0.233467E+10 | 6171.01 | 07-NOV-09:32 | 14.00 | 4.09 | 0.316932E+09 | 544.96 | 07-NOV-10:39 | 15.33 | 5.06 |
December | 0.147531E+10 | 4753.52 | 01-DEC-13:40 | 21.67 | 7.88 | 0.293165E+09 | 476.47 | 01-DEC-10:09 | 21.67 | 7.88 |
Annual Sum or Average | 0.751594E+11 | 0.429964E+10 | ||||||||
Minimum of Months | 0.147531E+10 | 4753.52 | 12.00 | 4.06 | 0.291460E+09 | 476.47 | 12.00 | 4.06 | ||
Maximum of Months | 0.128966E+11 | 33730.20 | 26.47 | 14.15 | 0.437193E+09 | 545.67 | 33.00 | 15.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101524E+11 | 30586.57 | 20-JAN-13:20 | 21.00 | 6.97 | 0.563028E+09 | 846.15 | 20-JAN-14:00 | 20.00 | 6.78 |
February | 0.922736E+10 | 45513.59 | 26-FEB-13:21 | 17.50 | 4.55 | 0.511288E+09 | 845.66 | 08-FEB-14:09 | 17.50 | 4.55 |
March | 0.986742E+10 | 44035.48 | 12-MAR-13:11 | 18.33 | 5.83 | 0.599299E+09 | 847.05 | 14-MAR-13:00 | 23.00 | 7.59 |
April | 0.680669E+10 | 19710.69 | 12-APR-13:30 | 21.00 | 7.78 | 0.526886E+09 | 845.69 | 13-APR-13:30 | 16.50 | 9.66 |
May | 0.910500E+10 | 16602.17 | 16-MAY-13:30 | 27.50 | 12.26 | 0.594484E+09 | 845.68 | 10-MAY-13:09 | 27.50 | 12.26 |
June | 0.141983E+11 | 21869.84 | 25-JUN-14:42 | 33.62 | 13.52 | 0.632005E+09 | 845.67 | 16-JUN-13:20 | 33.62 | 13.52 |
July | 0.143728E+11 | 39781.23 | 09-JUL-13:41 | 34.67 | 13.78 | 0.588734E+09 | 845.66 | 27-JUL-13:09 | 28.50 | 17.50 |
August | 0.167560E+11 | 42541.02 | 20-AUG-15:01 | 28.00 | 13.92 | 0.660149E+09 | 846.29 | 30-AUG-13:00 | 28.00 | 11.66 |
September | 0.151796E+11 | 46491.36 | 04-SEP-12:51 | 29.40 | 13.53 | 0.577534E+09 | 856.76 | 28-SEP-13:09 | 30.50 | 11.31 |
October | 0.115986E+11 | 45997.14 | 01-OCT-13:21 | 17.00 | 8.82 | 0.554932E+09 | 846.26 | 10-OCT-13:00 | 25.00 | 8.71 |
November | 0.103335E+11 | 43724.22 | 19-NOV-13:11 | 9.00 | 3.85 | 0.562000E+09 | 846.46 | 07-NOV-14:00 | 9.00 | 3.85 |
December | 0.805585E+10 | 41561.47 | 03-DEC-13:31 | 17.73 | 6.51 | 0.527198E+09 | 845.83 | 01-DEC-14:39 | 17.73 | 6.51 |
Annual Sum or Average | 0.135654E+12 | 0.689754E+10 | ||||||||
Minimum of Months | 0.680669E+10 | 16602.17 | 9.00 | 3.85 | 0.511288E+09 | 845.66 | 9.00 | 3.85 | ||
Maximum of Months | 0.167560E+11 | 46491.36 | 34.67 | 13.92 | 0.660149E+09 | 856.76 | 33.62 | 17.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.271330E+10 | 10746.99 | 20-JAN-15:50 | 18.33 | 7.40 | 0.319224E+09 | 544.82 | 23-JAN-14:00 | 19.00 | 5.82 |
February | 0.276735E+10 | 12179.72 | 17-FEB-16:23 | 13.50 | 6.66 | 0.291973E+09 | 544.96 | 17-FEB-14:50 | 13.50 | 6.66 |
March | 0.499301E+10 | 35852.65 | 26-MAR-16:51 | 13.00 | 6.02 | 0.353681E+09 | 544.96 | 08-MAR-14:00 | 13.00 | 6.02 |
April | 0.493692E+10 | 24994.16 | 08-APR-17:03 | 15.67 | 5.07 | 0.318692E+09 | 544.95 | 19-APR-13:00 | 22.00 | 9.00 |
May | 0.786359E+10 | 22445.83 | 28-MAY-15:31 | 20.00 | 9.85 | 0.366563E+09 | 544.96 | 18-MAY-13:20 | 20.00 | 9.85 |
June | 0.130113E+11 | 43267.24 | 04-JUN-16:41 | 29.50 | 12.29 | 0.397875E+09 | 544.96 | 09-JUN-13:50 | 24.62 | 12.38 |
July | 0.117632E+11 | 39085.83 | 01-JUL-17:41 | 28.17 | 10.55 | 0.369200E+09 | 544.96 | 18-JUL-13:00 | 31.00 | 15.59 |
August | 0.121838E+11 | 42392.46 | 20-AUG-15:41 | 28.00 | 14.08 | 0.409528E+09 | 544.97 | 28-AUG-13:30 | 24.50 | 16.32 |
September | 0.899539E+10 | 38829.68 | 10-SEP-16:11 | 31.63 | 12.58 | 0.346557E+09 | 545.00 | 01-SEP-13:00 | 31.63 | 12.58 |
October | 0.502609E+10 | 37736.68 | 08-OCT-16:31 | 17.33 | 8.37 | 0.328305E+09 | 544.96 | 05-OCT-13:00 | 17.33 | 8.37 |
November | 0.313624E+10 | 12663.80 | 07-NOV-15:30 | 21.50 | 7.27 | 0.319332E+09 | 544.96 | 16-NOV-14:00 | 16.00 | 6.90 |
December | 0.202632E+10 | 9637.97 | 01-DEC-15:30 | 19.50 | 7.14 | 0.301756E+09 | 544.96 | 13-DEC-14:00 | 16.00 | 4.14 |
Annual Sum or Average | 0.794166E+11 | 0.412269E+10 | ||||||||
Minimum of Months | 0.202632E+10 | 9637.97 | 13.00 | 5.07 | 0.291973E+09 | 544.82 | 13.00 | 4.14 | ||
Maximum of Months | 0.130113E+11 | 43267.24 | 31.63 | 14.08 | 0.409528E+09 | 545.00 | 31.63 | 16.32 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.434736E+10 | 14306.07 | 06-JAN-05:01 | -7.8 | -7.9 | 0.00 | 0.00 | 01-JAN-00:10 | -7.8 | -7.9 |
February | 0.343679E+10 | 13805.06 | 12-FEB-05:11 | -19.7 | -19.7 | 0.00 | 0.00 | 01-FEB-00:10 | -19.7 | -19.7 |
March | 0.564355E+10 | 10817.43 | 18-MAR-05:01 | -0.2 | -0.3 | 0.00 | 0.00 | 01-MAR-00:10 | -0.2 | -0.3 |
April | 0.554385E+10 | 11297.18 | 03-APR-04:01 | -8.0 | -8.0 | 0.00 | 0.00 | 01-APR-00:10 | -8.0 | -8.0 |
May | 0.724787E+10 | 9436.78 | 24-MAY-05:10 | 11.33 | 7.85 | 0.00 | 0.00 | 01-MAY-00:10 | 11.33 | 7.85 |
June | 0.108229E+11 | 10526.11 | 26-JUN-14:40 | 38.83 | 15.50 | 0.00 | 0.00 | 01-JUN-00:10 | 38.83 | 15.50 |
July | 0.113912E+11 | 11327.28 | 19-JUL-05:02 | 19.00 | 10.88 | 0.00 | 0.00 | 01-JUL-00:10 | 19.00 | 10.88 |
August | 0.124152E+11 | 10478.67 | 02-AUG-15:40 | 31.00 | 14.96 | 0.00 | 0.00 | 01-AUG-00:10 | 31.00 | 14.96 |
September | 0.934585E+10 | 11008.94 | 05-SEP-05:12 | 14.20 | 8.43 | 0.00 | 0.00 | 01-SEP-00:10 | 14.20 | 8.43 |
October | 0.651586E+10 | 13460.17 | 30-OCT-04:01 | -10.0 | -10.0 | 0.00 | 0.00 | 01-OCT-00:10 | -10.0 | -10.0 |
November | 0.545948E+10 | 12267.73 | 29-NOV-05:01 | -10.0 | -10.0 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.0 |
December | 0.420084E+10 | 13555.91 | 21-DEC-04:41 | -18.2 | -18.3 | 0.00 | 0.00 | 01-DEC-00:10 | -18.2 | -18.3 |
Annual Sum or Average | 0.863707E+11 | 0.00 | ||||||||
Minimum of Months | 0.343679E+10 | 9436.78 | -19.7 | -19.7 | 0.00 | 0.00 | -19.7 | -19.7 | ||
Maximum of Months | 0.124152E+11 | 14306.07 | 38.83 | 15.50 | 0.00 | 0.00 | 38.83 | 15.50 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.261145E+10 | 18268.60 | 06-JAN-04:01 | -11.3 | -11.3 | 0.00 | 0.00 | 01-JAN-00:10 | -11.3 | -11.3 |
February | 0.281731E+10 | 24209.37 | 12-FEB-05:01 | -19.8 | -19.8 | 0.00 | 0.00 | 01-FEB-00:10 | -19.8 | -19.8 |
March | 0.399822E+10 | 23119.23 | 18-MAR-23:31 | -8.9 | -8.9 | 0.00 | 0.00 | 01-MAR-00:10 | -8.9 | -8.9 |
April | 0.324681E+10 | 16891.33 | 17-APR-03:01 | -8.0 | -8.4 | 0.00 | 0.00 | 01-APR-00:10 | -8.0 | -8.4 |
May | 0.558558E+10 | 12074.06 | 03-MAY-04:11 | 1.67 | -1.5 | 0.00 | 0.00 | 01-MAY-00:10 | 1.67 | -1.5 |
June | 0.902162E+10 | 9902.02 | 09-JUN-05:05 | 6.97 | 3.89 | 0.00 | 0.00 | 01-JUN-00:10 | 6.97 | 3.89 |
July | 0.913038E+10 | 10026.33 | 18-JUL-15:00 | 31.00 | 14.77 | 0.00 | 0.00 | 01-JUL-00:10 | 31.00 | 14.77 |
August | 0.933929E+10 | 9503.66 | 18-AUG-05:07 | 15.50 | 7.47 | 0.00 | 0.00 | 01-AUG-00:10 | 15.50 | 7.47 |
September | 0.746918E+10 | 11021.99 | 22-SEP-05:01 | -1.7 | -2.9 | 0.00 | 0.00 | 01-SEP-00:10 | -1.7 | -2.9 |
October | 0.450378E+10 | 16548.62 | 30-OCT-02:41 | -8.9 | -8.9 | 0.00 | 0.00 | 01-OCT-00:10 | -8.9 | -8.9 |
November | 0.288613E+10 | 20847.87 | 30-NOV-04:01 | -13.8 | -14.3 | 0.00 | 0.00 | 01-NOV-00:10 | -13.8 | -14.3 |
December | 0.278012E+10 | 18890.94 | 22-DEC-04:01 | -21.8 | -21.8 | 0.00 | 0.00 | 01-DEC-00:10 | -21.8 | -21.8 |
Annual Sum or Average | 0.633899E+11 | 0.00 | ||||||||
Minimum of Months | 0.261145E+10 | 9503.66 | -21.8 | -21.8 | 0.00 | 0.00 | -21.8 | -21.8 | ||
Maximum of Months | 0.933929E+10 | 24209.37 | 31.00 | 14.77 | 0.00 | 0.00 | 31.00 | 14.77 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186498E+10 | 13972.08 | 20-JAN-13:00 | 21.00 | 6.97 | 0.00 | 0.00 | 01-JAN-00:10 | 21.00 | 6.97 |
February | 0.261451E+10 | 14640.11 | 26-FEB-13:24 | 17.50 | 4.55 | 0.00 | 0.00 | 01-FEB-00:10 | 17.50 | 4.55 |
March | 0.633987E+10 | 24209.93 | 14-MAR-13:50 | 23.17 | 7.65 | 0.00 | 0.00 | 01-MAR-00:10 | 23.17 | 7.65 |
April | 0.710847E+10 | 24131.74 | 19-APR-13:50 | 22.00 | 8.90 | 0.00 | 0.00 | 01-APR-00:10 | 22.00 | 8.90 |
May | 0.129512E+11 | 31833.19 | 31-MAY-14:05 | 28.00 | 14.83 | 0.00 | 0.00 | 01-MAY-00:10 | 28.00 | 14.83 |
June | 0.249866E+11 | 40571.18 | 26-JUN-13:05 | 36.78 | 15.39 | 0.00 | 0.00 | 01-JUN-00:10 | 36.78 | 15.39 |
July | 0.228558E+11 | 35771.84 | 07-JUL-14:30 | 31.50 | 14.08 | 0.00 | 0.00 | 01-JUL-00:10 | 31.50 | 14.08 |
August | 0.231869E+11 | 40456.91 | 16-AUG-14:00 | 37.00 | 16.36 | 0.00 | 0.00 | 01-AUG-00:10 | 37.00 | 16.36 |
September | 0.153379E+11 | 31101.30 | 12-SEP-14:05 | 29.40 | 13.78 | 0.00 | 0.00 | 01-SEP-00:10 | 29.40 | 13.78 |
October | 0.664940E+10 | 22839.31 | 11-OCT-14:05 | 26.83 | 9.68 | 0.00 | 0.00 | 01-OCT-00:10 | 26.83 | 9.68 |
November | 0.301901E+10 | 14941.50 | 05-NOV-13:14 | 21.00 | 6.50 | 0.00 | 0.00 | 01-NOV-00:10 | 21.00 | 6.50 |
December | 0.124989E+10 | 10884.81 | 01-DEC-13:35 | 21.67 | 7.88 | 0.00 | 0.00 | 01-DEC-00:10 | 21.67 | 7.88 |
Annual Sum or Average | 0.128165E+12 | 0.00 | ||||||||
Minimum of Months | 0.124989E+10 | 10884.81 | 17.50 | 4.55 | 0.00 | 0.00 | 17.50 | 4.55 | ||
Maximum of Months | 0.249866E+11 | 40571.18 | 37.00 | 16.36 | 0.00 | 0.00 | 37.00 | 16.36 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.300052E+10 | 2774.07 | 23-JAN-16:40 | 15.67 | 5.76 | 95230000.39 | 126.82 | 02-JAN-10:09 | 15.67 | 5.76 |
February | 0.705323E+10 | 4674.62 | 23-FEB-16:52 | 5.00 | 2.11 | 86396487.34 | 126.82 | 28-FEB-10:20 | 2.67 | 1.45 |
March | 0.134871E+11 | 7001.75 | 31-MAR-23:53 | 6.10 | 2.00 | 0.103236E+09 | 126.82 | 13-MAR-13:00 | 6.10 | 2.00 |
April | 0.181237E+11 | 8392.60 | 20-APR-17:54 | 17.00 | 8.49 | 91605122.63 | 126.82 | 28-APR-13:00 | 18.00 | 12.50 |
May | 0.419798E+10 | 3432.11 | 31-MAY-23:51 | 16.00 | 10.67 | 99233435.16 | 126.83 | 22-MAY-13:50 | 16.00 | 10.67 |
June | 0.947398E+10 | 5364.02 | 30-JUN-23:25 | 23.20 | 11.06 | 98958167.72 | 126.83 | 21-JUN-09:50 | 23.20 | 11.06 |
July | 0.148700E+11 | 7208.66 | 31-JUL-24:00 | 18.90 | 16.75 | 91881182.01 | 126.82 | 31-JUL-09:09 | 18.90 | 16.75 |
August | 0.200211E+11 | 8672.12 | 13-AUG-18:13 | 22.33 | 10.27 | 0.103237E+09 | 126.83 | 04-AUG-13:00 | 22.33 | 10.27 |
September | 0.443920E+10 | 3224.14 | 30-SEP-24:00 | 10.40 | 8.79 | 91605283.16 | 126.83 | 01-SEP-13:00 | 10.40 | 8.79 |
October | 0.867848E+10 | 4708.30 | 09-OCT-16:54 | 21.00 | 8.75 | 95230023.14 | 126.82 | 03-OCT-13:00 | 21.00 | 8.75 |
November | 0.131691E+11 | 6670.19 | 07-NOV-16:12 | 19.00 | 6.82 | 94300283.76 | 126.82 | 06-NOV-14:09 | 19.00 | 6.82 |
December | 0.181335E+11 | 8267.20 | 01-DEC-16:00 | 18.00 | 6.81 | 91880853.16 | 126.82 | 13-DEC-14:09 | 16.00 | 4.01 |
Annual Sum or Average | 0.134648E+12 | 0.114279E+10 | ||||||||
Minimum of Months | 0.300052E+10 | 2774.07 | 5.00 | 2.00 | 86396487.34 | 126.82 | 2.67 | 1.45 | ||
Maximum of Months | 0.200211E+11 | 8672.12 | 23.20 | 16.75 | 0.103237E+09 | 126.83 | 23.20 | 16.75 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155012E+10 | 2557.45 | 23-JAN-16:47 | 14.83 | 5.56 | 95229440.29 | 126.82 | 20-JAN-14:09 | 14.83 | 5.56 |
February | 0.557945E+10 | 4503.03 | 17-FEB-16:51 | 13.00 | 6.46 | 86396487.34 | 126.82 | 23-FEB-10:20 | 4.67 | 3.22 |
March | 0.118204E+11 | 6496.20 | 31-MAR-23:15 | 6.97 | 2.22 | 0.103236E+09 | 126.82 | 13-MAR-13:00 | 6.97 | 2.22 |
April | 0.162420E+11 | 8068.48 | 07-APR-17:50 | 17.33 | 7.10 | 91605128.07 | 126.82 | 28-APR-13:00 | 18.00 | 12.50 |
May | 0.340350E+10 | 3208.24 | 31-MAY-23:41 | 16.12 | 10.64 | 99233436.97 | 126.83 | 22-MAY-13:50 | 16.12 | 10.64 |
June | 0.884280E+10 | 5229.02 | 30-JUN-23:55 | 22.50 | 11.08 | 98958195.91 | 126.83 | 21-JUN-09:00 | 22.50 | 11.08 |
July | 0.139526E+11 | 6750.12 | 31-JUL-24:00 | 18.90 | 16.75 | 91881255.07 | 126.82 | 28-JUL-13:09 | 18.90 | 16.75 |
August | 0.188251E+11 | 8241.73 | 11-AUG-18:15 | 30.33 | 11.29 | 0.103237E+09 | 126.83 | 04-AUG-09:00 | 30.33 | 11.29 |
September | 0.364151E+10 | 2762.05 | 12-SEP-17:40 | 28.27 | 13.58 | 91605303.26 | 126.83 | 01-SEP-13:00 | 28.27 | 13.58 |
October | 0.735886E+10 | 4546.97 | 05-OCT-16:50 | 19.12 | 7.42 | 95230023.43 | 126.82 | 03-OCT-13:00 | 19.12 | 7.42 |
November | 0.113342E+11 | 6304.29 | 07-NOV-16:12 | 19.00 | 6.82 | 94300283.54 | 126.82 | 06-NOV-14:09 | 19.00 | 6.82 |
December | 0.155325E+11 | 7794.11 | 01-DEC-16:00 | 18.00 | 6.81 | 91880857.36 | 126.82 | 13-DEC-14:09 | 16.00 | 4.01 |
Annual Sum or Average | 0.118083E+12 | 0.114279E+10 | ||||||||
Minimum of Months | 0.155012E+10 | 2557.45 | 6.97 | 2.22 | 86396487.34 | 126.82 | 4.67 | 2.22 | ||
Maximum of Months | 0.188251E+11 | 8241.73 | 30.33 | 16.75 | 0.103237E+09 | 126.83 | 30.33 | 16.75 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.790366E+09 | 2564.80 | 20-JAN-16:33 | 14.00 | 6.06 | 95027236.60 | 127.69 | 09-JAN-10:09 | 14.00 | 6.06 |
February | 0.382934E+10 | 4512.27 | 17-FEB-16:51 | 13.00 | 6.46 | 86396487.34 | 126.82 | 28-FEB-10:30 | 3.00 | 1.61 |
March | 0.101781E+11 | 6503.51 | 31-MAR-17:22 | 17.00 | 7.52 | 0.103236E+09 | 126.82 | 13-MAR-13:00 | 17.00 | 7.52 |
April | 0.145676E+11 | 8182.12 | 07-APR-17:50 | 17.33 | 7.10 | 91605110.55 | 126.82 | 28-APR-13:00 | 18.00 | 12.50 |
May | 0.263742E+10 | 3047.53 | 31-MAY-23:12 | 16.47 | 10.53 | 99232295.21 | 126.83 | 22-MAY-13:50 | 16.47 | 10.53 |
June | 0.867294E+10 | 5167.29 | 30-JUN-23:40 | 22.97 | 11.07 | 98958210.50 | 126.83 | 21-JUN-09:00 | 22.97 | 11.07 |
July | 0.138208E+11 | 6802.00 | 01-JUL-18:40 | 26.67 | 10.19 | 91881342.22 | 126.83 | 28-JUL-13:00 | 24.00 | 17.79 |
August | 0.186328E+11 | 8401.24 | 11-AUG-18:10 | 30.67 | 11.40 | 0.103237E+09 | 126.83 | 04-AUG-13:00 | 30.67 | 11.40 |
September | 0.306495E+10 | 2991.38 | 10-SEP-17:25 | 29.95 | 12.03 | 91605321.61 | 126.83 | 01-SEP-13:00 | 29.95 | 12.03 |
October | 0.558006E+10 | 4609.04 | 05-OCT-16:50 | 19.12 | 7.42 | 95230024.08 | 126.82 | 03-OCT-13:00 | 19.12 | 7.42 |
November | 0.914452E+10 | 6314.33 | 07-NOV-16:12 | 19.00 | 6.82 | 94300283.48 | 126.82 | 06-NOV-14:09 | 19.00 | 6.82 |
December | 0.132342E+11 | 7769.66 | 01-DEC-16:00 | 18.00 | 6.81 | 91880859.66 | 126.82 | 13-DEC-14:09 | 16.00 | 4.01 |
Annual Sum or Average | 0.104153E+12 | 0.114259E+10 | ||||||||
Minimum of Months | 0.790366E+09 | 2564.80 | 13.00 | 6.06 | 86396487.34 | 126.82 | 3.00 | 1.61 | ||
Maximum of Months | 0.186328E+11 | 8401.24 | 30.67 | 12.03 | 0.103237E+09 | 127.69 | 30.67 | 17.79 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234013E+12 | 101791.72 | 24-JAN-05:11 | 2.67 | -1.5 | 0.209107E+10 | 2866.36 | 23-JAN-14:09 | 2.67 | -1.5 |
February | 0.435977E+12 | 452343.44 | 17-FEB-15:12 | 14.67 | 6.92 | 0.152769E+10 | 2630.03 | 07-FEB-14:09 | 14.67 | 6.92 |
March | 0.722869E+12 | 497411.45 | 03-MAR-15:12 | 10.00 | 1.56 | 0.187186E+10 | 2859.83 | 14-MAR-13:09 | 23.83 | 7.85 |
April | 0.945107E+12 | 469825.22 | 03-APR-05:01 | -8.0 | -8.0 | 0.165833E+10 | 2861.53 | 18-APR-13:09 | 19.00 | 6.84 |
May | 0.235825E+12 | 439407.93 | 31-MAY-23:58 | 16.00 | 10.67 | 0.218419E+10 | 2880.38 | 04-MAY-09:09 | 16.00 | 10.67 |
June | 0.471439E+12 | 451747.46 | 09-JUN-00:48 | 10.97 | 8.40 | 0.207085E+10 | 2876.04 | 09-JUN-13:09 | 23.08 | 11.47 |
July | 0.731064E+12 | 463994.08 | 07-JUL-04:22 | 15.50 | 8.45 | 0.197025E+10 | 2966.49 | 18-JUL-07:30 | 25.00 | 13.11 |
August | 0.976976E+12 | 481680.69 | 15-AUG-04:24 | 14.50 | 9.90 | 0.231122E+10 | 3411.65 | 18-AUG-09:09 | 27.67 | 11.77 |
September | 0.236307E+12 | 431862.34 | 30-SEP-23:28 | 10.70 | 8.93 | 0.201102E+10 | 2874.33 | 25-SEP-13:09 | 10.70 | 8.93 |
October | 0.491073E+12 | 486746.23 | 31-OCT-23:53 | -5.8 | -5.8 | 0.169631E+10 | 2862.79 | 10-OCT-13:09 | -5.8 | -5.8 |
November | 0.709684E+12 | 502360.40 | 16-NOV-12:32 | 15.00 | 5.81 | 0.179779E+10 | 2850.25 | 09-NOV-14:09 | 15.00 | 5.81 |
December | 0.981589E+12 | 484026.06 | 14-DEC-15:13 | 15.00 | 4.59 | 0.159509E+10 | 2832.32 | 04-DEC-14:09 | 15.00 | 4.59 |
Annual Sum or Average | 0.717192E+13 | 0.227857E+11 | ||||||||
Minimum of Months | 0.234013E+12 | 101791.72 | -8.0 | -8.0 | 0.152769E+10 | 2630.03 | -5.8 | -5.8 | ||
Maximum of Months | 0.981589E+12 | 502360.40 | 16.00 | 10.67 | 0.231122E+10 | 3411.65 | 27.67 | 13.11 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 54547156.60 | 3567.84 | 09-JAN-06:45 | 4.00 |
February | 61873837.38 | 3170.40 | 04-FEB-06:03 | -5.0 |
March | 95685352.75 | 3072.70 | 23-MAR-05:03 | 4.00 |
April | 75478228.23 | 3108.05 | 05-APR-05:03 | 0.17 |
May | 70194157.06 | 3623.87 | 27-MAY-05:05 | 4.67 |
June | 93899886.03 | 10916.21 | 24-JUN-16:01 | 31.60 |
July | 0.129566E+09 | 13635.02 | 15-JUL-16:01 | 34.00 |
August | 76543131.87 | 12098.95 | 26-AUG-16:01 | 32.67 |
September | 63294376.94 | 8494.93 | 02-SEP-16:01 | 29.62 |
October | 74066272.31 | 3226.28 | 23-OCT-05:11 | -4.0 |
November | 70311323.46 | 3269.00 | 27-NOV-06:11 | -6.7 |
December | 58519028.55 | 3023.68 | 21-DEC-06:04 | -19.0 |
Annual Sum or Average | 0.923979E+09 | |||
Minimum of Months | 54547156.60 | 3023.68 | -19.0 | |
Maximum of Months | 0.129566E+09 | 13635.02 | 34.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:03 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130089E+09 | 46499.66 | 02-JAN-05:01 | -2.2 |
February | 76454730.52 | 49383.09 | 06-FEB-05:01 | -10.0 |
March | 27568913.97 | 41019.27 | 20-MAR-04:01 | 0.83 |
April | 2547619.64 | 42460.33 | 03-APR-05:01 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 4059983.81 | 43566.97 | 30-OCT-05:01 | -10.0 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 |
December | 0.143182E+09 | 44270.20 | 11-DEC-06:01 | -5.8 |
Annual Sum or Average | 0.383903E+09 | |||
Minimum of Months | 0.00 | 0.00 | -10.0 | |
Maximum of Months | 0.143182E+09 | 49383.09 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.426522E+10 | 114012.01 | 02-JAN-04:01 | -2.8 |
February | 0.420825E+10 | 115810.25 | 06-FEB-04:01 | -10.0 |
March | 0.198157E+10 | 112902.30 | 20-MAR-03:11 | -1.0 |
April | 0.215011E+10 | 115422.25 | 03-APR-03:01 | -8.0 |
May | 0.313141E+09 | 84333.29 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 16470205.49 | 88147.76 | 22-SEP-05:01 | -1.7 |
October | 0.178916E+10 | 115132.79 | 30-OCT-03:01 | -9.2 |
November | 0.298916E+10 | 110590.79 | 27-NOV-04:11 | -7.0 |
December | 0.547649E+10 | 114584.80 | 11-DEC-04:01 | -6.8 |
Annual Sum or Average | 0.231896E+11 | |||
Minimum of Months | 0.00 | 0.00 | -10.0 | |
Maximum of Months | 0.547649E+10 | 115810.25 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.474788E+09 | 17025.12 | 06-JAN-05:01 | -7.8 |
February | 0.611360E+09 | 17510.52 | 13-FEB-04:01 | -11.8 |
March | 0.176078E+09 | 15336.24 | 29-MAR-05:01 | -7.2 |
April | 82831383.42 | 16406.99 | 03-APR-04:01 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 502542.36 | 6041.70 | 22-SEP-05:01 | -1.7 |
October | 0.144634E+09 | 16700.88 | 30-OCT-04:01 | -10.0 |
November | 0.222529E+09 | 16772.33 | 29-NOV-05:01 | -10.0 |
December | 0.103941E+10 | 17951.32 | 22-DEC-04:01 | -21.8 |
Annual Sum or Average | 0.275213E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.8 | |
Maximum of Months | 0.103941E+10 | 17951.32 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.332032E+09 | 15834.68 | 06-JAN-05:01 | -7.8 |
February | 0.438657E+09 | 15753.03 | 13-FEB-05:21 | -11.0 |
March | 0.155502E+09 | 14258.33 | 02-MAR-05:01 | -8.0 |
April | 86229633.39 | 15503.52 | 03-APR-04:01 | -8.0 |
May | 142732.67 | 926.65 | 03-MAY-05:02 | 1.17 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 1601139.93 | 8693.33 | 22-SEP-05:01 | -1.7 |
October | 0.129943E+09 | 15573.57 | 30-OCT-04:01 | -10.0 |
November | 0.215799E+09 | 15645.74 | 30-NOV-05:01 | -12.8 |
December | 0.793672E+09 | 17384.63 | 22-DEC-04:01 | -21.8 |
Annual Sum or Average | 0.215358E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.8 | |
Maximum of Months | 0.793672E+09 | 17384.63 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.570910E+09 | 22218.98 | 06-JAN-05:01 | -7.8 |
February | 0.792566E+09 | 24008.89 | 06-FEB-04:01 | -10.0 |
March | 0.383429E+09 | 20576.18 | 02-MAR-05:01 | -8.0 |
April | 0.259085E+09 | 21648.05 | 03-APR-04:01 | -8.0 |
May | 11572104.21 | 12454.31 | 01-MAY-05:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 6821288.61 | 15223.14 | 22-SEP-05:01 | -1.7 |
October | 0.328111E+09 | 21723.42 | 30-OCT-04:01 | -10.0 |
November | 0.388162E+09 | 22145.37 | 30-NOV-05:01 | -12.8 |
December | 0.110839E+10 | 24065.50 | 22-DEC-04:01 | -21.8 |
Annual Sum or Average | 0.384905E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.8 | |
Maximum of Months | 0.110839E+10 | 24065.50 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105902E+09 | 14548.11 | 05-JAN-05:01 | -17.0 |
February | 0.132141E+09 | 14968.67 | 06-FEB-05:01 | -10.0 |
March | 10554120.05 | 12312.42 | 29-MAR-05:01 | -7.2 |
April | 5805758.95 | 11898.33 | 17-APR-04:01 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 28079.50 | 421.19 | 22-SEP-05:02 | -1.7 |
October | 26679787.71 | 14391.69 | 30-OCT-04:01 | -10.0 |
November | 25719668.39 | 13967.42 | 29-NOV-05:01 | -10.0 |
December | 0.174986E+09 | 15010.14 | 21-DEC-05:01 | -18.2 |
Annual Sum or Average | 0.481817E+09 | |||
Minimum of Months | 0.00 | 0.00 | -18.2 | |
Maximum of Months | 0.174986E+09 | 15010.14 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265577E+10 | 24478.19 | 05-JAN-04:11 | -16.3 |
February | 0.324982E+10 | 27078.09 | 12-FEB-05:41 | -19.2 |
March | 0.189767E+10 | 27281.01 | 19-MAR-08:11 | -13.0 |
April | 0.984321E+09 | 24528.12 | 17-APR-03:01 | -8.0 |
May | 76948510.96 | 18500.54 | 03-MAY-04:11 | 1.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 35248475.76 | 19108.06 | 22-SEP-05:01 | -1.7 |
October | 0.115982E+10 | 25258.21 | 30-OCT-02:41 | -8.9 |
November | 0.174706E+10 | 24683.37 | 30-NOV-04:01 | -13.8 |
December | 0.501466E+10 | 26420.64 | 24-DEC-00:11 | -21.7 |
Annual Sum or Average | 0.168213E+11 | |||
Minimum of Months | 0.00 | 0.00 | -21.7 | |
Maximum of Months | 0.501466E+10 | 27281.01 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136595E+10 | 21831.89 | 05-JAN-04:11 | -16.3 |
February | 0.177704E+10 | 24449.79 | 12-FEB-05:41 | -19.2 |
March | 0.106564E+10 | 24654.26 | 19-MAR-08:11 | -13.0 |
April | 0.564877E+09 | 21536.77 | 17-APR-03:01 | -8.0 |
May | 36197753.07 | 14901.13 | 03-MAY-04:11 | 1.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 25250.39 | 294.59 | 23-AUG-05:03 | 11.17 |
September | 19191580.10 | 15143.03 | 22-SEP-05:01 | -1.7 |
October | 0.754612E+09 | 21732.68 | 30-OCT-03:21 | -9.5 |
November | 0.102513E+10 | 22194.59 | 30-NOV-04:01 | -13.8 |
December | 0.280683E+10 | 23868.52 | 24-DEC-00:11 | -21.7 |
Annual Sum or Average | 0.941550E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.7 | |
Maximum of Months | 0.280683E+10 | 24654.26 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127263E+10 | 26191.27 | 05-JAN-04:11 | -16.3 |
February | 0.202246E+10 | 28809.19 | 12-FEB-05:41 | -19.2 |
March | 0.147160E+10 | 29261.77 | 19-MAR-08:11 | -13.0 |
April | 0.877400E+09 | 26401.29 | 17-APR-03:01 | -8.0 |
May | 85779875.03 | 19126.68 | 03-MAY-04:11 | 1.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 28182576.60 | 19934.93 | 22-SEP-05:01 | -1.7 |
October | 0.926059E+09 | 26058.01 | 30-OCT-03:21 | -9.5 |
November | 0.106160E+10 | 26166.48 | 30-NOV-04:01 | -13.8 |
December | 0.283308E+10 | 27569.75 | 25-DEC-04:41 | -6.3 |
Annual Sum or Average | 0.105788E+11 | |||
Minimum of Months | 0.00 | 0.00 | -19.2 | |
Maximum of Months | 0.283308E+10 | 29261.77 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112038E+10 | 22591.98 | 05-JAN-04:11 | -16.3 |
February | 0.144509E+10 | 25405.56 | 12-FEB-05:41 | -19.2 |
March | 0.891749E+09 | 25710.47 | 19-MAR-08:11 | -13.0 |
April | 0.479721E+09 | 22377.04 | 17-APR-03:01 | -8.0 |
May | 44354634.02 | 14718.91 | 03-MAY-04:11 | 1.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 30399.97 | 354.67 | 23-AUG-05:03 | 11.17 |
September | 20905014.59 | 15533.01 | 22-SEP-05:01 | -1.7 |
October | 0.576115E+09 | 22437.78 | 30-OCT-03:01 | -9.2 |
November | 0.819721E+09 | 22755.41 | 30-NOV-04:01 | -13.8 |
December | 0.227910E+10 | 24390.68 | 24-DEC-00:11 | -21.7 |
Annual Sum or Average | 0.767718E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.7 | |
Maximum of Months | 0.227910E+10 | 25710.47 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.714620E+10 | 34419.49 | 15-JAN-07:32 | -9.3 |
February | 0.758554E+10 | 38071.21 | 12-FEB-05:41 | -19.2 |
March | 0.514889E+10 | 38573.59 | 19-MAR-07:51 | -12.9 |
April | 0.381171E+10 | 34571.96 | 03-APR-03:01 | -8.0 |
May | 0.525665E+09 | 28051.41 | 03-MAY-04:11 | 1.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 3288169.50 | 11702.08 | 23-AUG-05:01 | 11.17 |
September | 0.271016E+09 | 27804.22 | 22-SEP-05:01 | -1.7 |
October | 0.387771E+10 | 36492.75 | 29-OCT-22:51 | -8.0 |
November | 0.534853E+10 | 35611.63 | 30-NOV-04:01 | -13.8 |
December | 0.106990E+11 | 37222.95 | 22-DEC-04:11 | -21.7 |
Annual Sum or Average | 0.444176E+11 | |||
Minimum of Months | 0.00 | 0.00 | -21.7 | |
Maximum of Months | 0.106990E+11 | 38573.59 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.377349E+10 | 25757.81 | 05-JAN-04:11 | -16.3 |
February | 0.416283E+10 | 28775.42 | 12-FEB-05:41 | -19.2 |
March | 0.286999E+10 | 29142.57 | 19-MAR-07:51 | -12.9 |
April | 0.218385E+10 | 26066.98 | 03-APR-03:01 | -8.0 |
May | 0.251091E+09 | 19989.36 | 03-MAY-04:11 | 1.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 1357156.03 | 6518.74 | 23-AUG-05:01 | 11.17 |
September | 0.127180E+09 | 19691.92 | 22-SEP-05:01 | -1.7 |
October | 0.236370E+10 | 27532.50 | 29-OCT-22:51 | -8.0 |
November | 0.299691E+10 | 27009.96 | 30-NOV-04:01 | -13.8 |
December | 0.610381E+10 | 28173.28 | 22-DEC-04:11 | -21.7 |
Annual Sum or Average | 0.248342E+11 | |||
Minimum of Months | 0.00 | 0.00 | -21.7 | |
Maximum of Months | 0.610381E+10 | 29142.57 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.404144E+10 | 34591.57 | 05-JAN-04:11 | -16.3 |
February | 0.516317E+10 | 38226.29 | 12-FEB-05:41 | -19.2 |
March | 0.414209E+10 | 39083.55 | 19-MAR-07:51 | -12.9 |
April | 0.349344E+10 | 35064.67 | 03-APR-03:01 | -8.0 |
May | 0.567385E+09 | 28140.17 | 03-MAY-04:11 | 1.67 |
June | 1120766.88 | 9831.46 | 09-JUN-05:01 | 6.97 |
July | 54542.78 | 636.33 | 06-JUL-05:04 | 14.50 |
August | 2722674.70 | 8343.23 | 23-AUG-05:01 | 11.17 |
September | 0.199856E+09 | 28152.19 | 22-SEP-05:01 | -1.7 |
October | 0.319962E+10 | 36918.64 | 29-OCT-22:51 | -8.0 |
November | 0.345690E+10 | 35998.57 | 30-NOV-04:01 | -13.8 |
December | 0.689052E+10 | 37703.54 | 22-DEC-04:11 | -21.7 |
Annual Sum or Average | 0.311583E+11 | |||
Minimum of Months | 54542.78 | 636.33 | -21.7 | |
Maximum of Months | 0.689052E+10 | 39083.55 | 14.50 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304294E+10 | 28126.06 | 05-JAN-04:11 | -16.3 |
February | 0.341438E+10 | 31475.43 | 12-FEB-05:41 | -19.2 |
March | 0.239451E+10 | 32033.85 | 19-MAR-07:51 | -12.9 |
April | 0.170214E+10 | 28116.90 | 03-APR-03:01 | -8.0 |
May | 0.252767E+09 | 20622.12 | 03-MAY-04:11 | 1.67 |
June | 55877.71 | 648.92 | 10-JUN-05:02 | 9.77 |
July | 3293.97 | 54.90 | 29-JUL-05:05 | 16.17 |
August | 796644.38 | 3127.28 | 23-AUG-05:01 | 11.17 |
September | 0.116182E+09 | 21147.42 | 22-SEP-05:01 | -1.7 |
October | 0.182292E+10 | 29956.62 | 29-OCT-22:51 | -8.0 |
November | 0.232675E+10 | 29414.90 | 30-NOV-03:21 | -14.0 |
December | 0.492200E+10 | 31044.95 | 22-DEC-04:11 | -21.7 |
Annual Sum or Average | 0.199954E+11 | |||
Minimum of Months | 3293.97 | 54.90 | -21.7 | |
Maximum of Months | 0.492200E+10 | 32033.85 | 16.17 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55940892.88 | 9655.49 | 16-JAN-14:01 | 1.67 |
February | 0.183158E+09 | 12744.36 | 26-FEB-15:51 | 18.00 |
March | 58845737.94 | 14359.92 | 12-MAR-15:52 | 18.00 |
April | 27245605.99 | 10030.89 | 18-APR-05:02 | 7.67 |
May | 46317347.96 | 6904.75 | 07-MAY-12:01 | 20.33 |
June | 56819179.64 | 12452.11 | 25-JUN-15:41 | 32.88 |
July | 87921965.21 | 10815.67 | 27-JUL-04:11 | 19.67 |
August | 98181847.97 | 14617.36 | 20-AUG-15:11 | 28.00 |
September | 69299476.39 | 13556.39 | 10-SEP-14:51 | 31.60 |
October | 53343403.25 | 14732.43 | 09-OCT-15:21 | 22.00 |
November | 68990650.22 | 16323.70 | 05-NOV-15:01 | 20.67 |
December | 0.110959E+09 | 11288.75 | 01-DEC-06:01 | 10.00 |
Annual Sum or Average | 0.917024E+09 | |||
Minimum of Months | 27245605.99 | 6904.75 | 1.67 | |
Maximum of Months | 0.183158E+09 | 16323.70 | 32.88 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136667E+10 | 18095.95 | 01-JAN-13:52 | 6.00 |
February | 0.143812E+10 | 11704.08 | 26-FEB-13:32 | 17.33 |
March | 0.736920E+09 | 15249.47 | 12-MAR-16:21 | 18.00 |
April | 0.514461E+09 | 6246.17 | 09-APR-16:16 | 12.67 |
May | 59065744.38 | 7281.17 | 21-MAY-14:48 | 18.83 |
June | 46223698.82 | 12077.90 | 25-JUN-16:31 | 32.70 |
July | 58019978.16 | 11144.17 | 16-JUL-15:11 | 35.67 |
August | 44329630.64 | 12259.14 | 20-AUG-15:01 | 28.00 |
September | 56970288.89 | 13914.30 | 10-SEP-15:51 | 32.20 |
October | 0.264203E+09 | 15953.76 | 09-OCT-15:51 | 22.00 |
November | 0.534674E+09 | 13886.32 | 05-NOV-15:31 | 19.67 |
December | 0.176028E+10 | 13498.65 | 26-DEC-06:13 | 7.00 |
Annual Sum or Average | 0.687994E+10 | |||
Minimum of Months | 44329630.64 | 6246.17 | 6.00 | |
Maximum of Months | 0.176028E+10 | 18095.95 | 35.67 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154704E+11 | 44762.72 | 05-JAN-06:01 | -17.0 |
February | 0.146555E+11 | 50115.25 | 13-FEB-05:05 | -11.0 |
March | 0.102092E+11 | 35530.86 | 06-MAR-05:04 | -0.7 |
April | 0.771253E+10 | 48450.42 | 17-APR-04:21 | -8.0 |
May | 0.194952E+10 | 30605.76 | 01-MAY-04:23 | 6.00 |
June | 0.207820E+09 | 34000.12 | 08-JUN-05:01 | 13.90 |
July | 0.137022E+09 | 28586.15 | 12-JUL-05:01 | 14.50 |
August | 0.187032E+09 | 28275.64 | 18-AUG-05:01 | 15.50 |
September | 0.126955E+10 | 28640.89 | 01-SEP-05:01 | 12.20 |
October | 0.878973E+10 | 42313.97 | 30-OCT-04:14 | -10.0 |
November | 0.117140E+11 | 45009.46 | 30-NOV-05:21 | -12.5 |
December | 0.201289E+11 | 56306.60 | 23-DEC-06:12 | -22.1 |
Annual Sum or Average | 0.924312E+11 | |||
Minimum of Months | 0.137022E+09 | 28275.64 | -22.1 | |
Maximum of Months | 0.201289E+11 | 56306.60 | 15.50 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:03 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.339696E+09 | 1537.35 | 01-JAN-06:03 | -3.2 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:03 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 2.77 |
Annual Sum or Average | 0.339696E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.339696E+09 | 1537.35 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163013E+10 | 1590.41 | 16-JAN-18:53 | -2.0 |
February | 0.163709E+09 | 1222.56 | 07-FEB-05:53 | -7.0 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 |
April | 5566501.58 | 1563.62 | 30-APR-23:50 | 5.38 |
May | 98297791.38 | 1563.30 | 01-MAY-00:05 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 46116761.02 | 966.49 | 22-SEP-04:00 | 0.00 |
October | 44548885.64 | 1283.53 | 29-OCT-10:11 | -2.0 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 2.77 |
Annual Sum or Average | 0.198836E+10 | |||
Minimum of Months | 0.00 | 0.00 | -7.0 | |
Maximum of Months | 0.163013E+10 | 1590.41 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 0.659820E+09 | 20707.20 | 26-FEB-10:51 | 14.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:03 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 5.43 |
June | 0.140864E+09 | 30864.75 | 04-JUN-05:01 | 13.27 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 1911944.52 | 31865.74 | 30-SEP-23:11 | 10.80 |
October | 0.150087E+09 | 20674.04 | 16-OCT-13:31 | 11.67 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 2.77 |
Annual Sum or Average | 0.952683E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.659820E+09 | 31865.74 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.278508E+11 | 29144.79 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.252627E+11 | 29144.79 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.300191E+11 | 29144.79 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.268132E+11 | 29144.79 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.289349E+11 | 29144.79 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.287951E+11 | 29144.79 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.269531E+11 | 29144.79 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.300191E+11 | 29144.79 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.268132E+11 | 29144.79 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.278508E+11 | 29144.79 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.275243E+11 | 29144.79 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.269531E+11 | 29144.79 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.333789E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.252627E+11 | 29144.79 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.300191E+11 | 29144.79 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.785272E+10 | 8217.58 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.712300E+10 | 8217.58 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.846411E+10 | 8217.58 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.756018E+10 | 8217.58 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.815842E+10 | 8217.58 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.811897E+10 | 8217.58 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.759962E+10 | 8217.58 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.846411E+10 | 8217.58 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.756018E+10 | 8217.58 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.785272E+10 | 8217.58 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.776069E+10 | 8217.58 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.759962E+10 | 8217.58 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.941143E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.712300E+10 | 8217.58 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.846411E+10 | 8217.58 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.289349E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.287951E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.275243E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.333789E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466696E+09 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722808E+09 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.72 | 0.786982E+09 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853082E+09 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1770425.98 | 0.428787E+09 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39162449.71 | 0.181230E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51362101.51 | 0.177846E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26467368.94 | 0.175183E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15602199.60 | 0.269432E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 250101.90 | 0.599720E+09 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529905E+09 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100062E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134615E+09 | 0.619229E+10 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175183E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51362101.51 | 0.100062E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312964E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484216E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.84 | 0.522294E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559689E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1305124.61 | 0.278267E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28530461.61 | 0.114278E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38657649.05 | 0.110418E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19359511.82 | 0.103213E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11798018.09 | 0.175539E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 195613.53 | 0.399540E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349990E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 555.76 | 0.660956E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99847164.31 | 0.407136E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103213E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38657649.05 | 0.660956E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485215E+09 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740711E+09 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792585E+09 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830051E+09 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1782036.26 | 0.414283E+09 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40668591.42 | 0.171104E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53887937.74 | 0.168127E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25639590.28 | 0.170434E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13124772.18 | 0.272642E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 233649.20 | 0.609421E+09 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542645E+09 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102151E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135337E+09 | 0.621873E+10 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168127E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53887937.74 | 0.102151E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325958E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504148E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.06 | 0.556927E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611940E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1283320.13 | 0.300263E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26151485.53 | 0.135052E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33869691.41 | 0.135628E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17528164.92 | 0.137947E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10291831.30 | 0.194431E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 217890.47 | 0.418594E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373467E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711496E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89342473.83 | 0.440585E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135052E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33869691.41 | 0.711496E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982981E+09 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156059E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10400.50 | 0.167134E+10 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176550E+10 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4329969.43 | 0.918094E+09 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97258856.26 | 0.385062E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131348E+09 | 0.380809E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66713729.98 | 0.373288E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44578236.50 | 0.553515E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1147027.70 | 0.125048E+10 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50116.63 | 0.111998E+10 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31956.95 | 0.211966E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345469E+09 | 0.130813E+11 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373288E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131348E+09 | 0.211966E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676826E+09 |
February | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106909E+10 |
March | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.88 | 0.115256E+10 |
April | 0.688021E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121260E+10 |
May | 0.744847E+09 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2716928.46 | 0.623711E+09 |
June | 0.742030E+09 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63883275.20 | 0.256923E+09 |
July | 0.690839E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84140283.97 | 0.261998E+09 |
August | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41673124.46 | 0.254691E+09 |
September | 0.688021E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26981474.44 | 0.385453E+09 |
October | 0.715730E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 430885.81 | 0.869137E+09 |
November | 0.708685E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 527.66 | 0.764218E+09 |
December | 0.690839E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143421E+10 |
Annual Sum or Average | 0.858171E+10 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219827E+09 | 0.896142E+10 |
Minimum of Months | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254691E+09 |
Maximum of Months | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84140283.97 | 0.143421E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110668E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168948E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179384E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182858E+10 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3978164.74 | 0.940167E+09 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94116885.88 | 0.380572E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123056E+09 | 0.383483E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58094359.89 | 0.401219E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28987665.93 | 0.615881E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 401255.02 | 0.138030E+10 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123327E+10 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228778E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308634E+09 | 0.140413E+11 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380572E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123056E+09 | 0.228778E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686963E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108153E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34362.19 | 0.116718E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122570E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3471570.21 | 0.641135E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63490746.87 | 0.277198E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85762966.94 | 0.270782E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45153277.20 | 0.277094E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26859540.62 | 0.399292E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 791381.38 | 0.876903E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 543.26 | 0.777702E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145457E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225564E+09 | 0.913605E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270782E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85762966.94 | 0.145457E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114723E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184774E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21013.78 | 0.197011E+10 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204009E+10 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6286101.47 | 0.104221E+10 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123616E+09 | 0.442408E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167953E+09 | 0.439035E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85038087.87 | 0.426319E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61232341.92 | 0.613950E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2213088.10 | 0.141983E+10 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 388344.09 | 0.129068E+10 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115302.02 | 0.252427E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446863E+09 | 0.152039E+11 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426319E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167953E+09 | 0.252427E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779339E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126027E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135699E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140643E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3437467.71 | 0.722938E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76259257.13 | 0.307864E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99575593.65 | 0.315356E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50203927.33 | 0.304375E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31822486.35 | 0.441693E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 468296.17 | 0.994019E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7903.38 | 0.879068E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19712.42 | 0.169670E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261795E+09 | 0.104650E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304375E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99575593.65 | 0.169670E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126308E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198883E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210837E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211795E+10 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5198817.46 | 0.107713E+10 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118625E+09 | 0.441506E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156756E+09 | 0.445667E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72778319.83 | 0.464631E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36661763.13 | 0.696289E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 612222.60 | 0.157803E+10 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142109E+10 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268434E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390631E+09 | 0.162869E+11 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441506E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156756E+09 | 0.268434E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.799590E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128760E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15033.14 | 0.138951E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143292E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4362981.13 | 0.752785E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78121168.68 | 0.330274E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105201E+09 | 0.323421E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55019880.57 | 0.329456E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33361934.27 | 0.462658E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 851336.34 | 0.101662E+10 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12646.01 | 0.906585E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173321E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276946E+09 | 0.107646E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323421E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105201E+09 | 0.173321E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.785272E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.712300E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.846411E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.756018E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.815842E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.811897E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.759962E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.846411E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.756018E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.785272E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.776069E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.759962E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.941143E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.712300E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.846411E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105116E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162269E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177134E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189953E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2601492.65 | 0.933903E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71217944.98 | 0.387682E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97574761.99 | 0.383600E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45171604.80 | 0.389027E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25482569.80 | 0.599868E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253059.72 | 0.134727E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118426E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223879E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242301E+09 | 0.138091E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383600E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97574761.99 | 0.223879E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178091E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278105E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302612E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323857E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4813211.76 | 0.162796E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132333E+09 | 0.672128E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182996E+09 | 0.663629E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84868614.43 | 0.674241E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50272201.23 | 0.103187E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 540663.34 | 0.232117E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202810E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374823E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455823E+09 | 0.235940E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663629E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182996E+09 | 0.374823E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170568E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274620E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299108E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314666E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1860038.67 | 0.164182E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103290E+09 | 0.650158E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137331E+09 | 0.650540E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61265206.96 | 0.663307E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31513435.90 | 0.954301E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40530.00 | 0.218724E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194229E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366471E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335301E+09 | 0.229440E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650158E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137331E+09 | 0.366471E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 29144.79 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 29144.79 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 29144.79 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 29144.79 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 29144.79 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 29144.79 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 29144.79 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 29144.79 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 29144.79 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 29144.79 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 29144.79 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 29144.79 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 901.79 | 13-JAN-04:55 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1096.90 | 05-FEB-22:51 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14-MAR-13:00 | 2288.53 | 19-MAR-06:51 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 1628.75 | 16-APR-14:53 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.97 | 17-MAY-14:50 | 917.47 | 03-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 274.01 | 25-JUN-17:51 | 538.00 | 08-JUN-23:00 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 390.49 | 16-JUL-11:51 | 504.71 | 03-JUL-03:01 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.10 | 06-AUG-12:00 | 622.50 | 27-AUG-18:00 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.89 | 10-SEP-15:00 | 583.94 | 22-SEP-02:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | 11-OCT-14:00 | 1382.81 | 29-OCT-08:51 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1377.20 | 01-NOV-04:03 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1985.48 | 21-DEC-22:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.71 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 390.49 | 2288.53 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 619.23 | 08-JAN-09:00 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 722.93 | 23-FEB-23:52 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 | 14-MAR-13:00 | 1509.30 | 19-MAR-06:54 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 1086.40 | 16-APR-14:53 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 | 17-MAY-14:50 | 599.04 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 251.21 | 25-JUN-17:51 | 345.74 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.85 | 16-JUL-11:53 | 372.18 | 02-JUL-08:30 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.11 | 06-AUG-16:20 | 360.73 | 27-AUG-18:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.40 | 10-SEP-15:00 | 383.99 | 22-SEP-02:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.23 | 11-OCT-14:00 | 916.91 | 29-OCT-08:51 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 916.30 | 01-NOV-04:06 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 | 02-DEC-15:00 | 1303.12 | 21-DEC-22:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.74 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 276.85 | 1509.30 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 890.04 | 13-JAN-04:55 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1119.16 | 19-FEB-16:51 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2257.37 | 19-MAR-06:55 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 1583.23 | 15-APR-04:57 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.97 | 17-MAY-14:50 | 885.84 | 03-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.53 | 25-JUN-17:51 | 525.82 | 08-JUN-23:00 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 400.60 | 16-JUL-11:53 | 491.24 | 03-JUL-03:01 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.54 | 02-AUG-16:00 | 650.14 | 27-AUG-18:00 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.15 | 10-SEP-14:54 | 567.43 | 22-SEP-02:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 11-OCT-14:10 | 1332.77 | 29-OCT-08:51 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1374.45 | 01-NOV-04:09 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1980.78 | 21-DEC-22:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.24 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 400.60 | 2257.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 630.78 | 13-JAN-04:55 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 774.50 | 19-FEB-16:51 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | 14-MAR-13:00 | 1584.55 | 19-MAR-06:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 1174.90 | 16-APR-14:53 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.64 | 17-MAY-14:50 | 647.83 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.73 | 25-JUN-17:44 | 415.03 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.68 | 16-JUL-12:00 | 380.44 | 03-JUL-03:01 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.77 | 06-AUG-15:42 | 519.59 | 27-AUG-18:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.08 | 04-SEP-11:50 | 399.86 | 22-SEP-02:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 11-OCT-14:00 | 957.82 | 29-OCT-08:51 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 947.46 | 01-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1384.01 | 21-DEC-22:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.44 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 287.68 | 1584.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1980.31 | 13-JAN-05:04 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2389.08 | 05-FEB-22:53 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.38 | 14-MAR-13:00 | 5275.50 | 19-MAR-06:59 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 3664.77 | 15-APR-04:52 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.47 | 17-MAY-14:50 | 1896.32 | 03-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 710.49 | 25-JUN-18:00 | 1162.38 | 08-JUN-23:00 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 978.16 | 16-JUL-12:00 | 1060.06 | 03-JUL-03:01 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 393.01 | 06-AUG-16:00 | 1299.11 | 27-AUG-17:55 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 479.08 | 10-SEP-14:40 | 1253.46 | 22-SEP-02:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.34 | 11-OCT-14:00 | 2737.28 | 29-OCT-08:51 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.37 | 05-NOV-15:00 | 3238.85 | 01-NOV-04:05 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.04 | 02-DEC-15:00 | 4384.47 | 21-DEC-22:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1060.06 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 978.16 | 5275.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1319.62 | 13-JAN-05:07 |
February | 1239.33 | 01-FEB-08:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1579.35 | 05-FEB-22:56 |
March | 1239.33 | 01-MAR-08:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 14-MAR-13:00 | 3555.33 | 19-MAR-06:53 |
April | 1239.33 | 03-APR-07:10 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 2442.30 | 15-APR-04:52 |
May | 1239.33 | 01-MAY-07:10 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.98 | 17-MAY-14:50 | 1263.94 | 02-MAY-05:00 |
June | 1239.33 | 01-JUN-07:10 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 586.91 | 25-JUN-18:00 | 755.54 | 08-JUN-23:00 |
July | 1239.33 | 03-JUL-07:10 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 668.41 | 16-JUL-12:00 | 923.78 | 02-JUL-08:50 |
August | 1239.33 | 01-AUG-07:10 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.13 | 06-AUG-16:00 | 884.32 | 27-AUG-17:55 |
September | 1239.33 | 01-SEP-07:10 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.84 | 10-SEP-14:40 | 834.77 | 22-SEP-02:00 |
October | 1239.33 | 02-OCT-07:10 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.04 | 11-OCT-14:20 | 1843.04 | 29-OCT-08:51 |
November | 1239.33 | 01-NOV-07:10 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 | 05-NOV-15:00 | 2159.25 | 01-NOV-04:05 |
December | 1239.33 | 01-DEC-08:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2923.02 | 21-DEC-22:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 755.54 | |||||
Maximum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 668.41 | 3555.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1979.45 | 13-JAN-05:09 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2604.96 | 19-FEB-16:51 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 5275.50 | 19-MAR-06:57 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 3667.75 | 15-APR-04:52 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.47 | 17-MAY-14:50 | 1922.74 | 03-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 747.53 | 25-JUN-18:00 | 1145.52 | 08-JUN-23:00 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 965.84 | 16-JUL-12:00 | 1071.71 | 03-JUL-03:01 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.60 | 02-AUG-16:00 | 1566.90 | 27-AUG-17:55 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.46 | 10-SEP-14:54 | 1260.21 | 22-SEP-02:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.01 | 11-OCT-15:00 | 2848.17 | 29-OCT-08:51 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 3238.86 | 01-NOV-04:09 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4424.73 | 21-DEC-22:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1071.71 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 965.84 | 5275.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1319.65 | 13-JAN-05:07 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1620.56 | 19-FEB-16:51 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 | 14-MAR-13:00 | 3546.98 | 19-MAR-06:53 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 2444.27 | 15-APR-04:52 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.98 | 17-MAY-14:50 | 1314.45 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 432.02 | 25-JUN-10:00 | 851.12 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 763.37 | 16-JUL-12:00 | 783.75 | 03-JUL-03:01 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 302.29 | 20-AUG-12:30 | 1020.19 | 27-AUG-17:55 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.85 | 04-SEP-12:10 | 827.85 | 22-SEP-02:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.74 | 11-OCT-11:40 | 1857.62 | 29-OCT-08:51 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 | 05-NOV-12:21 | 2160.06 | 01-NOV-04:03 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2938.86 | 21-DEC-22:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 783.75 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 763.37 | 3546.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2469.62 | 13-JAN-05:10 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2956.27 | 05-FEB-22:55 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 14-MAR-13:00 | 6573.12 | 19-MAR-06:51 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 4650.58 | 15-APR-04:55 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.93 | 17-MAY-14:50 | 2368.05 | 02-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 851.03 | 25-JUN-18:10 | 1359.99 | 08-JUN-23:00 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1184.92 | 16-JUL-11:51 | 1225.07 | 03-JUL-03:00 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 483.83 | 06-AUG-15:52 | 1583.10 | 27-AUG-17:55 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 646.22 | 10-SEP-15:00 | 1438.11 | 22-SEP-04:52 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.43 | 09-OCT-15:00 | 3408.82 | 29-OCT-18:53 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.87 | 05-NOV-15:00 | 4040.39 | 01-NOV-04:07 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.64 | 17-DEC-12:51 | 5461.59 | 21-DEC-22:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1225.07 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1184.92 | 6573.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1646.42 | 13-JAN-05:06 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1970.85 | 05-FEB-22:57 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 4382.10 | 19-MAR-07:00 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 3100.42 | 15-APR-04:57 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.95 | 17-MAY-14:50 | 1578.73 | 02-MAY-04:58 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 648.22 | 25-JUN-18:10 | 895.29 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 765.61 | 16-JUL-12:10 | 1041.15 | 02-JUL-08:30 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.85 | 06-AUG-12:06 | 1100.89 | 27-AUG-17:55 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 441.78 | 10-SEP-15:00 | 958.47 | 22-SEP-04:52 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.78 | 11-OCT-14:00 | 2261.56 | 29-OCT-18:53 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.48 | 05-NOV-14:40 | 2693.67 | 01-NOV-04:08 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.20 | 02-DEC-15:00 | 3641.00 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 895.29 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 765.61 | 4382.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2469.60 | 13-JAN-05:06 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2956.24 | 05-FEB-22:57 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 6573.13 | 19-MAR-06:59 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 4650.71 | 15-APR-04:55 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.93 | 17-MAY-14:50 | 2368.14 | 02-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 942.51 | 25-JUN-18:10 | 1340.45 | 08-JUN-23:00 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1144.12 | 16-JUL-12:10 | 1240.02 | 03-JUL-03:00 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.53 | 02-AUG-16:00 | 1905.59 | 27-AUG-17:55 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.16 | 10-SEP-14:54 | 1441.45 | 21-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.52 | 11-OCT-14:00 | 3400.95 | 29-OCT-18:53 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 4040.42 | 01-NOV-04:06 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 5461.59 | 21-DEC-22:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1240.02 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1144.12 | 6573.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1646.44 | 13-JAN-05:07 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1970.83 | 05-FEB-22:52 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.80 | 14-MAR-13:00 | 4382.11 | 19-MAR-07:00 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 3100.41 | 15-APR-04:53 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.95 | 17-MAY-14:50 | 1578.78 | 02-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 516.00 | 25-JUN-10:10 | 1010.09 | 08-JUN-22:01 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 863.47 | 16-JUL-12:10 | 919.66 | 03-JUL-03:00 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.63 | 20-AUG-09:50 | 1252.65 | 27-AUG-17:55 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.80 | 10-SEP-13:00 | 959.48 | 22-SEP-04:52 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.78 | 11-OCT-14:00 | 2239.16 | 29-OCT-18:56 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.93 | 05-NOV-12:00 | 2693.65 | 01-NOV-04:10 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3640.88 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 919.66 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 863.47 | 4382.11 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 8217.58 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 8217.58 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 8217.58 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 8217.58 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 8217.58 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 8217.58 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 8217.58 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 8217.58 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 8217.58 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 8217.58 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 8217.58 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 8217.58 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 8217.58 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 8217.58 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2112.00 | 13-JAN-04:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2554.14 | 05-FEB-22:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 5347.24 | 19-MAR-06:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 3571.63 | 16-APR-14:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.35 | 17-MAY-14:40 | 2094.89 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.70 | 25-JUN-18:00 | 1139.65 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 833.71 | 16-JUL-12:00 | 1084.47 | 03-JUL-03:01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.22 | 06-AUG-12:00 | 1245.01 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.38 | 10-SEP-15:00 | 1328.51 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.25 | 11-OCT-14:00 | 3122.52 | 29-OCT-08:51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 3136.21 | 01-NOV-03:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4434.85 | 21-DEC-22:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.47 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 833.71 | 5347.24 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3595.10 | 13-JAN-04:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 4309.45 | 23-FEB-23:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 9061.90 | 19-MAR-06:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 6193.42 | 15-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.60 | 17-MAY-14:40 | 3609.18 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1035.13 | 25-JUN-18:00 | 2001.16 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1532.41 | 16-JUL-12:00 | 1864.88 | 03-JUL-03:01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 518.76 | 06-AUG-12:00 | 2137.10 | 27-AUG-17:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 639.70 | 10-SEP-15:00 | 2348.48 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.35 | 11-OCT-14:00 | 5322.67 | 29-OCT-08:51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 5176.10 | 01-NOV-03:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 7679.48 | 21-DEC-22:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1864.88 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1532.41 | 9061.90 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3300.38 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 4232.83 | 19-FEB-16:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 8990.07 | 19-MAR-06:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 6116.93 | 15-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.91 | 17-MAY-13:00 | 3089.93 | 02-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 819.69 | 25-JUN-17:50 | 1921.90 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1421.14 | 16-JUL-11:51 | 1745.21 | 03-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.14 | 02-AUG-16:00 | 2659.15 | 27-AUG-17:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.81 | 10-SEP-15:00 | 2157.06 | 21-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.02 | 11-OCT-14:00 | 4829.16 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 5079.28 | 01-NOV-04:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 7942.75 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1745.21 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1421.14 | 8990.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 125563.88 | 30-JAN-05:01 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 125365.84 | 23-FEB-05:01 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 123869.34 | 01-MAR-05:01 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 109637.20 | 10-APR-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 120208.13 | 12-MAY-05:02 | 8976.13 | 16191.55 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 134038.79 | 05-JUN-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 116963.60 | 03-JUL-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 115067.14 | 15-AUG-04:11 | 0.00 | 25906.48 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 127718.24 | 05-SEP-04:11 | 0.00 | 22668.17 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 133877.88 | 16-OCT-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 124292.92 | 01-NOV-04:01 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 116058.53 | 18-DEC-05:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 109637.20 | 0.00 | 16191.55 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 134038.79 | 8976.13 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 105486.21 | 25-JAN-06:01 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 104221.15 | 23-FEB-06:01 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 110329.89 | 15-MAR-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 110006.44 | 21-APR-04:11 | 0.00 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 106960.06 | 18-MAY-04:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 114136.22 | 20-JUN-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 117228.71 | 31-JUL-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 117661.39 | 07-AUG-04:11 | 0.00 | 23265.84 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 118124.32 | 05-SEP-04:11 | 0.00 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 113966.87 | 10-OCT-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 109879.31 | 09-NOV-05:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 107130.28 | 05-DEC-05:01 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 104221.15 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 118124.32 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 65220.56 | 21-JAN-06:02 | 8061.19 | 14541.15 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 87806.11 | 18-FEB-06:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 98928.49 | 17-MAR-05:01 | 12897.91 | 23265.84 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 99186.69 | 21-APR-05:01 | 12897.91 | 23265.84 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 100796.61 | 31-MAY-05:01 | 14510.15 | 26174.07 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 105405.71 | 30-JUN-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 104745.89 | 25-JUL-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 104322.25 | 11-AUG-04:11 | 0.00 | 23265.84 | 47500.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 103462.40 | 13-SEP-04:11 | 0.00 | 23265.84 | 47500.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 99656.44 | 11-OCT-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 96925.74 | 09-NOV-06:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 37417.73 | 15-DEC-16:13 | 45948.79 | 78522.21 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 37417.73 | 0.00 | 14541.15 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 105405.71 | 45948.79 | 78522.21 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 35159.43 | 20-JAN-16:14 | 76581.32 | 130870.35 | 86032.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 31413.60 | 17-FEB-16:53 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 49979.37 | 15-MAR-15:30 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 50550.33 | 21-APR-13:53 | 48043.74 | 78522.21 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 56077.33 | 31-MAY-15:40 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 111061.98 | 16-JUN-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 114724.78 | 24-JUL-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 110915.88 | 11-AUG-05:01 | 11285.67 | 20357.61 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 108289.03 | 13-SEP-05:02 | 9673.43 | 17449.38 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 49030.49 | 11-OCT-15:30 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36703.15 | 08-NOV-16:13 | 107213.85 | 183218.49 | 120445.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27041.83 | 01-DEC-16:12 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 27041.83 | 0.00 | 17449.38 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 114724.78 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5099.44 | 20-JAN-14:30 | 4021.58 | 6572.83 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 |
February | 4937.98 | 26-FEB-14:31 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.57 |
March | 8101.27 | 14-MAR-14:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 |
April | 8916.03 | 20-APR-13:30 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 |
May | 11157.80 | 17-MAY-13:30 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 34.84 | 0.00 |
June | 21956.99 | 25-JUN-17:41 | 0.00 | 1825.79 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 210.89 | 0.00 |
July | 21969.80 | 16-JUL-13:01 | 708.51 | 1278.05 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 197.67 | 0.00 |
August | 13382.63 | 18-AUG-13:50 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 39.21 | 0.00 |
September | 11932.11 | 11-SEP-14:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 53.94 | 0.00 |
October | 8472.84 | 10-OCT-14:50 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 0.00 |
November | 6837.20 | 09-NOV-13:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.38 |
December | 5334.46 | 04-DEC-14:04 | 10053.95 | 16432.08 | 10802.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4937.98 | 0.00 | 1278.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21969.80 | 10053.95 | 16432.08 | 10802.76 | 0.00 | 0.00 | 0.00 | 0.00 | 210.89 | 189.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8907.63 | 20-JAN-09:25 | 4957.30 | 8471.56 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.72 |
February | 19364.40 | 26-FEB-09:11 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.20 |
March | 29996.62 | 12-MAR-09:11 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.21 |
April | 22525.29 | 09-APR-08:22 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 743.86 |
May | 15430.89 | 16-MAY-08:30 | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 |
June | 31020.15 | 11-JUN-08:61 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.61 |
July | 30426.01 | 09-JUL-08:31 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.03 |
August | 32967.14 | 06-AUG-08:51 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.63 |
September | 29441.43 | 17-SEP-09:11 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.55 |
October | 28038.91 | 01-OCT-09:01 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.35 |
November | 23909.35 | 05-NOV-09:01 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.06 |
December | 6789.11 | 01-DEC-09:21 | 9914.60 | 16943.13 | 11138.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6789.11 | 391.37 | 705.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 | |
Maximum of Months | 32967.14 | 9914.60 | 16943.13 | 11138.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 743.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33040.85 | 22-JAN-12:31 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.94 |
February | 37475.25 | 26-FEB-13:11 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.22 |
March | 36539.93 | 12-MAR-12:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.01 |
April | 18842.09 | 19-APR-13:10 | 4021.67 | 6572.98 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.28 |
May | 15989.52 | 07-MAY-13:31 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.96 |
June | 31965.82 | 25-JUN-13:41 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 63.25 | 0.00 |
July | 30978.62 | 04-JUL-14:01 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 14.43 | 0.00 |
August | 34224.97 | 27-AUG-13:11 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.80 |
September | 36002.15 | 17-SEP-12:31 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.35 |
October | 38311.87 | 09-OCT-13:21 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.89 |
November | 39398.01 | 05-NOV-13:01 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.18 |
December | 34586.95 | 17-DEC-12:51 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15989.52 | 708.53 | 1278.08 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39398.01 | 4021.67 | 6572.98 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 63.25 | 594.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12437.82 | 20-JAN-15:40 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.85 |
February | 31091.51 | 26-FEB-15:51 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.95 |
March | 39348.32 | 26-MAR-16:51 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.54 |
April | 23529.05 | 08-APR-17:42 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.83 |
May | 18547.69 | 29-MAY-15:51 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.40 |
June | 42968.28 | 25-JUN-16:21 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 44.77 | 0.00 |
July | 38557.04 | 02-JUL-16:31 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.60 |
August | 38302.98 | 13-AUG-16:51 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.00 |
September | 40592.05 | 17-SEP-16:31 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.36 |
October | 38554.04 | 08-OCT-16:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.58 |
November | 36358.15 | 05-NOV-15:01 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.47 |
December | 18840.68 | 17-DEC-15:31 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12437.82 | 391.37 | 705.96 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42968.28 | 1239.33 | 2117.89 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 44.77 | 230.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5706.37 | 20-JAN-15:02 | 9615.55 | 16432.08 | 10802.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.07 |
February | 5391.70 | 17-FEB-14:51 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.08 |
March | 6571.66 | 14-MAR-13:40 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 |
April | 6822.92 | 20-APR-13:30 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.25 |
May | 10539.59 | 17-MAY-13:30 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 79.94 | 0.00 |
June | 19008.98 | 25-JUN-17:51 | 0.00 | 1825.79 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 527.67 | 0.00 |
July | 27794.17 | 16-JUL-15:11 | 708.51 | 1278.05 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 707.51 | 0.00 |
August | 12201.25 | 18-AUG-14:00 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 93.82 | 0.00 |
September | 11006.20 | 11-SEP-14:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 123.65 | 0.00 |
October | 6838.70 | 11-OCT-15:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 | 0.00 |
November | 6076.90 | 09-NOV-12:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.75 |
December | 5576.06 | 01-DEC-14:50 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5391.70 | 0.00 | 1278.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27794.17 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 707.51 | 73.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8085.32 | 20-JAN-11:03 | 3717.98 | 6353.67 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.96 |
February | 14288.87 | 27-FEB-11:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.19 |
March | 29965.61 | 12-MAR-09:01 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 697.90 |
April | 16076.54 | 11-APR-10:01 | 9914.60 | 16943.13 | 11138.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.68 |
May | 23923.07 | 28-MAY-09:12 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.45 |
June | 31663.29 | 11-JUN-07:41 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.93 |
July | 34709.33 | 16-JUL-09:11 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 116.18 | 0.00 |
August | 33769.85 | 20-AUG-08:21 | 587.05 | 1058.95 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.21 |
September | 30919.71 | 04-SEP-08:41 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.34 |
October | 22294.26 | 01-OCT-10:11 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 726.69 |
November | 13908.76 | 07-NOV-11:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 |
December | 9255.86 | 29-DEC-11:01 | 9914.60 | 16943.13 | 11138.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8085.32 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34709.33 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 116.18 | 726.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 32733.32 | 22-JAN-12:42 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1474.63 |
February | 38196.01 | 26-FEB-13:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 985.77 |
March | 36537.26 | 12-MAR-12:21 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 903.09 |
April | 18998.37 | 12-APR-13:15 | 4021.67 | 6572.98 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.86 |
May | 15426.33 | 16-MAY-13:20 | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 52.38 | 0.00 |
June | 30897.85 | 25-JUN-15:11 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 183.01 | 0.00 |
July | 31887.61 | 30-JUL-13:51 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 85.24 | 0.00 |
August | 33844.95 | 27-AUG-13:11 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.02 |
September | 37731.35 | 04-SEP-13:21 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 |
October | 38962.39 | 09-OCT-13:11 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.73 |
November | 40359.99 | 05-NOV-12:51 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.84 |
December | 36825.42 | 03-DEC-12:21 | 910.97 | 1643.24 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1071.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15426.33 | 607.31 | 1095.50 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40359.99 | 4021.67 | 6572.98 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 183.01 | 1474.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10587.31 | 20-JAN-15:50 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 |
February | 12004.83 | 17-FEB-16:23 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.25 |
March | 34209.67 | 26-MAR-16:51 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.69 |
April | 23960.86 | 08-APR-17:03 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.43 |
May | 26123.14 | 07-MAY-15:41 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.06 |
June | 40718.58 | 25-JUN-16:31 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 98.86 | 0.00 |
July | 35809.92 | 01-JUL-17:41 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 |
August | 38348.59 | 20-AUG-15:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.91 |
September | 35521.45 | 10-SEP-16:31 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 68.49 | 0.00 |
October | 35723.41 | 08-OCT-16:31 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.57 |
November | 22334.29 | 05-NOV-15:31 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.44 |
December | 9499.10 | 01-DEC-15:30 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9499.10 | 456.59 | 823.62 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40718.58 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 98.86 | 508.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6670.72 | 20-JAN-13:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 |
February | 5782.81 | 26-FEB-15:21 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.01 |
March | 7162.36 | 14-MAR-13:10 | 6032.37 | 9859.25 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 7.40 | 0.00 |
April | 7361.89 | 20-APR-13:30 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.07 |
May | 11191.55 | 17-MAY-13:40 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 95.35 | 0.00 |
June | 14604.88 | 26-JUN-15:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 283.62 | 0.00 |
July | 17054.07 | 16-JUL-14:42 | 506.08 | 912.89 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 912.26 | 0.00 |
August | 13467.38 | 16-AUG-14:00 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 188.18 | 0.00 |
September | 11766.22 | 11-SEP-14:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 150.00 | 0.00 |
October | 7993.18 | 11-OCT-13:20 | 4021.58 | 6572.83 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.45 | 0.00 |
November | 6676.39 | 07-NOV-13:30 | 3846.22 | 6572.83 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.79 |
December | 5699.39 | 01-DEC-13:40 | 3846.22 | 6572.83 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5699.39 | 506.08 | 912.89 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17054.07 | 6032.37 | 9859.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 912.26 | 257.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5778.49 | 20-JAN-13:10 | 6196.63 | 10589.46 | 6961.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 |
February | 6283.36 | 26-FEB-11:21 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.45 |
March | 12756.78 | 12-MAR-09:11 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 896.79 |
April | 13781.29 | 21-APR-09:02 | 5183.32 | 8471.56 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.61 |
May | 15228.42 | 16-MAY-09:00 | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.05 |
June | 31042.88 | 11-JUN-08:61 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.50 |
July | 32622.66 | 09-JUL-09:01 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.42 |
August | 33730.20 | 20-AUG-08:21 | 587.05 | 1058.95 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.28 |
September | 31045.10 | 04-SEP-10:11 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.76 |
October | 10051.83 | 11-OCT-09:50 | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.38 |
November | 6171.01 | 07-NOV-09:32 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.12 |
December | 4753.52 | 01-DEC-13:40 | 2478.65 | 4235.78 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4753.52 | 456.59 | 823.62 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 | |
Maximum of Months | 33730.20 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 896.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 30586.57 | 20-JAN-13:20 | 3846.30 | 6572.98 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.52 |
February | 45513.59 | 26-FEB-13:21 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1099.67 |
March | 44035.48 | 12-MAR-13:11 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1733.29 |
April | 19710.69 | 12-APR-13:30 | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.88 |
May | 16602.17 | 16-MAY-13:30 | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 63.84 | 0.00 |
June | 21869.84 | 25-JUN-14:42 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 171.86 | 0.00 |
July | 39781.23 | 09-JUL-13:41 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 454.24 | 0.00 |
August | 42541.02 | 20-AUG-15:01 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.91 |
September | 46491.36 | 04-SEP-12:51 | 910.97 | 1643.24 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 |
October | 45997.14 | 01-OCT-13:21 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 935.93 |
November | 43724.22 | 19-NOV-13:11 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1718.62 |
December | 41561.47 | 03-DEC-13:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 922.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16602.17 | 607.31 | 1095.50 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46491.36 | 3846.30 | 6572.98 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 454.24 | 1733.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10746.99 | 20-JAN-15:50 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.55 |
February | 12179.72 | 17-FEB-16:23 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.15 |
March | 35852.65 | 26-MAR-16:51 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.33 |
April | 24994.16 | 08-APR-17:03 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 627.66 |
May | 22445.83 | 28-MAY-15:31 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.07 |
June | 43267.24 | 04-JUN-16:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 |
July | 39085.83 | 01-JUL-17:41 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.05 |
August | 42392.46 | 20-AUG-15:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.60 |
September | 38829.68 | 10-SEP-16:11 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 86.50 | 0.00 |
October | 37736.68 | 08-OCT-16:31 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.21 |
November | 12663.80 | 07-NOV-15:30 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.25 |
December | 9637.97 | 01-DEC-15:30 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9637.97 | 456.59 | 823.62 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43267.24 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 86.50 | 627.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14306.07 | 06-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1051.45 |
February | 13805.06 | 12-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2105.87 |
March | 10817.43 | 18-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 643.38 |
April | 11297.18 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1209.43 |
May | 9436.78 | 24-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.93 |
June | 10526.11 | 26-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.80 | 0.00 |
July | 11327.28 | 19-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.15 |
August | 10478.67 | 02-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.99 | 0.00 |
September | 11008.94 | 05-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.29 |
October | 13460.17 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.61 |
November | 12267.73 | 29-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1312.12 |
December | 13555.91 | 21-DEC-04:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1688.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9436.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14306.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.99 | 2105.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18268.60 | 06-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 955.23 |
February | 24209.37 | 12-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3600.01 |
March | 23119.23 | 18-MAR-23:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7493.63 |
April | 16891.33 | 17-APR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2686.91 |
May | 12074.06 | 03-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2689.42 |
June | 9902.02 | 09-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.93 |
July | 10026.33 | 18-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.00 | 0.00 |
August | 9503.66 | 18-AUG-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.56 |
September | 11021.99 | 22-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.04 |
October | 16548.62 | 30-OCT-02:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2115.21 |
November | 20847.87 | 30-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2896.20 |
December | 18890.94 | 22-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4485.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9503.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24209.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.00 | 7493.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13972.08 | 20-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.96 |
February | 14640.11 | 26-FEB-13:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 905.00 |
March | 24209.93 | 14-MAR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.53 |
April | 24131.74 | 19-APR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.88 |
May | 31833.19 | 31-MAY-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.27 | 0.00 |
June | 40571.18 | 26-JUN-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.97 | 0.00 |
July | 35771.84 | 07-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.73 | 0.00 |
August | 40456.91 | 16-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.29 | 0.00 |
September | 31101.30 | 12-SEP-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.57 | 0.00 |
October | 22839.31 | 11-OCT-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.07 | 0.00 |
November | 14941.50 | 05-NOV-13:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.94 |
December | 10884.81 | 01-DEC-13:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 10884.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40571.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.29 | 905.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2774.07 | 23-JAN-16:40 | 444.28 | 1457.57 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4674.62 | 23-FEB-16:52 | 2221.41 | 7287.84 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7001.75 | 31-MAR-23:53 | 0.00 | 242.93 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8392.60 | 20-APR-17:54 | 233.83 | 2429.28 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3432.11 | 31-MAY-23:51 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5364.02 | 30-JUN-23:25 | 0.00 | 161.95 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7208.66 | 31-JUL-24:00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8672.12 | 13-AUG-18:13 | 0.00 | 283.42 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3224.14 | 30-SEP-24:00 | 0.00 | 80.98 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4708.30 | 09-OCT-16:54 | 58.46 | 202.44 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6670.19 | 07-NOV-16:12 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8267.20 | 01-DEC-16:00 | 222.14 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2774.07 | 0.00 | 40.49 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8672.12 | 2221.41 | 7287.84 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2557.45 | 23-JAN-16:47 | 666.42 | 2186.35 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4503.03 | 17-FEB-16:51 | 2221.41 | 7287.84 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6496.20 | 31-MAR-23:15 | 0.00 | 161.95 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8068.48 | 07-APR-17:50 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3208.24 | 31-MAY-23:41 | 0.00 | 283.42 | 27280.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5229.02 | 30-JUN-23:55 | 0.00 | 161.95 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6750.12 | 31-JUL-24:00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8241.73 | 11-AUG-18:15 | 46.77 | 485.86 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2762.05 | 12-SEP-17:40 | 23.38 | 242.93 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4546.97 | 05-OCT-16:50 | 70.15 | 404.88 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6304.29 | 07-NOV-16:12 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7794.11 | 01-DEC-16:00 | 222.14 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2557.45 | 0.00 | 40.49 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8241.73 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2564.80 | 20-JAN-16:33 | 666.42 | 2186.35 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4512.27 | 17-FEB-16:51 | 2221.41 | 7287.84 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6503.51 | 31-MAR-17:22 | 233.83 | 2429.28 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8182.12 | 07-APR-17:50 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3047.53 | 31-MAY-23:12 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5167.29 | 30-JUN-23:40 | 0.00 | 80.98 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6802.00 | 01-JUL-18:40 | 0.00 | 80.98 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8401.24 | 11-AUG-18:10 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2991.38 | 10-SEP-17:25 | 0.00 | 404.88 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4609.04 | 05-OCT-16:50 | 70.15 | 404.88 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6314.33 | 07-NOV-16:12 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7769.66 | 01-DEC-16:00 | 222.14 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2564.80 | 0.00 | 80.98 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8401.24 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 101791.72 | 24-JAN-05:11 | 0.00 | 9130.65 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 452343.44 | 17-FEB-15:12 | 48086.79 | 82175.84 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 497411.45 | 03-MAR-15:12 | 48086.79 | 82175.84 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 469825.22 | 03-APR-05:01 | 5061.77 | 9130.65 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 439407.93 | 31-MAY-23:58 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 451747.46 | 09-JUN-00:48 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 463994.08 | 07-JUL-04:22 | 0.00 | 9130.65 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 481680.69 | 15-AUG-04:24 | 0.00 | 9130.65 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 431862.34 | 30-SEP-23:28 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 486746.23 | 31-OCT-23:53 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 502360.40 | 16-NOV-12:32 | 26462.74 | 82175.84 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 484026.06 | 14-DEC-15:13 | 48086.79 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 101791.72 | 0.00 | 4565.32 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 502360.40 | 48086.79 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.200084E+13 | 1643340.22 | 24-JAN-15:09 | 0.404621E+12 | 1571801.14 | 02-JAN-06:10 |
February | 0.219922E+13 | 1749680.90 | 27-FEB-15:09 | 0.406369E+12 | 1707687.40 | 06-FEB-06:10 |
March | 0.300374E+13 | 2140753.97 | 13-MAR-15:20 | 0.281953E+12 | 1378468.77 | 20-MAR-04:10 |
April | 0.315743E+13 | 2131206.29 | 07-APR-15:39 | 0.187404E+12 | 1232273.66 | 03-APR-04:10 |
May | 0.212756E+13 | 1893940.19 | 18-MAY-14:20 | 0.365870E+11 | 918325.54 | 01-MAY-04:19 |
June | 0.268804E+13 | 2167221.02 | 26-JUN-14:39 | 0.792353E+09 | 54227.51 | 09-JUN-05:10 |
July | 0.308670E+13 | 2293009.10 | 18-JUL-14:00 | 0.413788E+09 | 19742.16 | 29-JUL-06:30 |
August | 0.356613E+13 | 2436855.34 | 16-AUG-15:20 | 0.163147E+10 | 173199.70 | 23-AUG-05:10 |
September | 0.219142E+13 | 1927914.74 | 12-SEP-15:39 | 0.210204E+11 | 667087.48 | 22-SEP-05:10 |
October | 0.247727E+13 | 1955170.84 | 11-OCT-10:39 | 0.228824E+12 | 1330351.88 | 30-OCT-05:10 |
November | 0.281964E+13 | 1986705.12 | 07-NOV-15:30 | 0.296704E+12 | 1179174.61 | 30-NOV-06:10 |
December | 0.330206E+13 | 2063458.54 | 04-DEC-15:09 | 0.598548E+12 | 1682305.51 | 26-DEC-06:19 |
Annual Sum or Average | 0.326201E+14 | 0.246487E+13 | ||||
Minimum of Months | 0.200084E+13 | 1643340.22 | 0.413788E+09 | 19742.16 | ||
Maximum of Months | 0.356613E+13 | 2436855.34 | 0.598548E+12 | 1707687.40 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.468149E+12 | 0.103391E+12 | 0.766053E+12 | 0.218140E+12 | 0.219261E+12 | 0.184966E+11 | 0.00 | 0.280594E+11 | 38856634.70 | 0.137840E+12 | 0.00 | 0.414152E+11 | 0.00 |
February | 0.424646E+12 | 0.870501E+11 | 0.978954E+12 | 0.199667E+12 | 0.227565E+12 | 0.341725E+11 | 0.00 | 0.704113E+11 | 28588319.22 | 0.138638E+12 | 0.00 | 0.380839E+11 | 0.00 |
March | 0.504598E+12 | 0.874346E+11 | 0.141687E+13 | 0.230864E+12 | 0.282424E+12 | 0.101217E+12 | 0.00 | 0.116267E+12 | 0.207531E+09 | 0.219731E+12 | 0.00 | 0.441295E+11 | 0.00 |
April | 0.450709E+12 | 0.755536E+11 | 0.165903E+13 | 0.216144E+12 | 0.289235E+12 | 0.891082E+11 | 0.00 | 0.121602E+12 | 0.257545E+09 | 0.217281E+12 | 0.00 | 0.385126E+11 | 0.00 |
May | 0.486374E+12 | 0.702091E+11 | 0.774844E+12 | 0.224502E+12 | 0.248160E+12 | 0.435973E+11 | 0.00 | 0.110535E+12 | 0.241153E+10 | 0.128022E+12 | 0.00 | 0.389101E+11 | 0.00 |
June | 0.484022E+12 | 0.637880E+11 | 0.106252E+13 | 0.222585E+12 | 0.325108E+12 | 0.100218E+12 | 0.00 | 0.326833E+12 | 0.204674E+11 | 0.461502E+11 | 0.00 | 0.363478E+11 | 0.00 |
July | 0.453060E+12 | 0.677868E+11 | 0.139340E+13 | 0.218061E+12 | 0.346915E+12 | 0.122288E+12 | 0.00 | 0.365758E+12 | 0.258905E+11 | 0.604629E+11 | 0.00 | 0.330760E+11 | 0.00 |
August | 0.504598E+12 | 0.745924E+11 | 0.173200E+13 | 0.230864E+12 | 0.394923E+12 | 0.126143E+12 | 0.00 | 0.385211E+12 | 0.221386E+11 | 0.600438E+11 | 0.00 | 0.356134E+11 | 0.00 |
September | 0.450709E+12 | 0.806674E+11 | 0.740713E+12 | 0.216143E+12 | 0.273657E+12 | 0.666560E+11 | 0.00 | 0.200856E+12 | 0.747419E+10 | 0.121611E+12 | 0.00 | 0.329373E+11 | 0.00 |
October | 0.468149E+12 | 0.927022E+11 | 0.108340E+13 | 0.218140E+12 | 0.264031E+12 | 0.454157E+11 | 0.00 | 0.117243E+12 | 0.640006E+09 | 0.151959E+12 | 0.00 | 0.355912E+11 | 0.00 |
November | 0.462662E+12 | 0.977006E+11 | 0.135889E+13 | 0.209941E+12 | 0.259457E+12 | 0.964486E+11 | 0.00 | 0.107090E+12 | 0.152265E+09 | 0.190280E+12 | 0.00 | 0.370165E+11 | 0.00 |
December | 0.453060E+12 | 0.105621E+12 | 0.170972E+13 | 0.218060E+12 | 0.298453E+12 | 0.974962E+11 | 0.00 | 0.113197E+12 | 73983776.48 | 0.267455E+12 | 0.00 | 0.389196E+11 | 0.00 |
Annual Sum or Average | 0.561074E+13 | 0.100650E+13 | 0.146764E+14 | 0.262311E+13 | 0.342919E+13 | 0.941257E+12 | 0.00 | 0.206306E+13 | 0.797811E+11 | 0.173947E+13 | 0.00 | 0.450553E+12 | 0.00 |
Minimum of Months | 0.424646E+12 | 0.637880E+11 | 0.740713E+12 | 0.199667E+12 | 0.219261E+12 | 0.184966E+11 | 0.00 | 0.280594E+11 | 28588319.22 | 0.461502E+11 | 0.00 | 0.329373E+11 | 0.00 |
Maximum of Months | 0.504598E+12 | 0.105621E+12 | 0.173200E+13 | 0.230864E+12 | 0.394923E+12 | 0.126143E+12 | 0.00 | 0.385211E+12 | 0.258905E+11 | 0.267455E+12 | 0.00 | 0.441295E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.404621E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.406369E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.281953E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.187404E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.365870E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.792353E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.413788E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.163147E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.210204E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.228824E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.296704E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.598548E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.246487E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.413788E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.598548E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 489900.85 | 02-JAN-08:09 | 64082.80 | 01-JAN-00:10 | 423497.50 | 02-JAN-08:09 | 235096.12 | 02-JAN-08:20 | 223513.68 | 20-JAN-16:10 | 41459.05 | 25-JAN-14:50 | 0.00 | 01-JAN-00:10 |
February | 489900.85 | 01-FEB-08:09 | 64082.80 | 01-FEB-00:10 | 541788.89 | 01-FEB-08:09 | 235096.12 | 01-FEB-08:20 | 228716.38 | 17-FEB-16:10 | 41373.48 | 17-FEB-14:20 | 0.00 | 01-FEB-00:10 |
March | 489900.85 | 01-MAR-08:09 | 64082.80 | 01-MAR-00:10 | 660080.29 | 01-MAR-08:09 | 235096.12 | 01-MAR-08:20 | 297915.10 | 15-MAR-15:00 | 82376.01 | 14-MAR-13:20 | 0.00 | 01-MAR-00:10 |
April | 489900.85 | 03-APR-07:10 | 64082.80 | 01-APR-00:10 | 778371.69 | 03-APR-07:10 | 235096.12 | 03-APR-07:19 | 266604.35 | 07-APR-15:39 | 40888.50 | 05-APR-13:30 | 0.00 | 01-APR-00:10 |
May | 489900.85 | 01-MAY-07:10 | 64082.80 | 01-MAY-00:10 | 423497.50 | 01-MAY-07:10 | 235096.12 | 01-MAY-07:19 | 262681.55 | 18-MAY-14:30 | 83787.14 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 489900.85 | 01-JUN-07:10 | 64082.80 | 01-JUN-00:10 | 541788.89 | 01-JUN-07:10 | 235096.12 | 01-JUN-07:19 | 397151.93 | 26-JUN-14:39 | 94292.65 | 26-JUN-14:39 | 0.00 | 01-JUN-00:10 |
July | 489900.85 | 03-JUL-07:10 | 64082.80 | 01-JUL-00:10 | 660080.29 | 03-JUL-07:10 | 235096.12 | 03-JUL-07:19 | 393833.47 | 18-JUL-14:00 | 97555.15 | 18-JUL-15:09 | 0.00 | 01-JUL-00:10 |
August | 489900.85 | 01-AUG-07:10 | 64082.80 | 01-AUG-00:10 | 778371.69 | 01-AUG-07:10 | 235096.12 | 01-AUG-07:19 | 381623.28 | 16-AUG-14:00 | 96927.22 | 02-AUG-15:50 | 0.00 | 01-AUG-00:10 |
September | 489900.85 | 01-SEP-07:10 | 64082.80 | 01-SEP-00:10 | 423497.50 | 01-SEP-07:10 | 235096.12 | 01-SEP-07:19 | 322842.36 | 12-SEP-15:39 | 91829.49 | 12-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 489900.85 | 02-OCT-07:10 | 64082.80 | 01-OCT-00:10 | 541788.89 | 02-OCT-07:10 | 235096.12 | 02-OCT-07:19 | 279505.52 | 19-OCT-15:39 | 84200.18 | 11-OCT-11:00 | 0.00 | 01-OCT-00:10 |
November | 489900.85 | 01-NOV-07:10 | 64082.80 | 01-NOV-00:10 | 660080.29 | 01-NOV-07:10 | 235096.12 | 01-NOV-07:19 | 262984.72 | 08-NOV-15:09 | 42329.66 | 07-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 489900.85 | 01-DEC-08:09 | 64082.80 | 01-DEC-00:10 | 778371.69 | 01-DEC-08:09 | 235096.12 | 01-DEC-08:20 | 229776.74 | 14-DEC-15:50 | 42696.41 | 26-DEC-06:19 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 489900.85 | 64082.80 | 423497.50 | 235096.12 | 223513.68 | 40888.50 | 0.00 | |||||||
Maximum of Months | 489900.85 | 64082.80 | 778371.69 | 235096.12 | 397151.93 | 97555.15 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 148847.20 | 24-JAN-15:09 | 1862.79 | 19-JAN-14:50 | 100000.00 | 09-JAN-10:09 | 0.00 | 55409.00 | 31-JAN-12:39 | 0.00 |
February | 153541.79 | 18-FEB-13:09 | 2462.03 | 18-FEB-13:09 | 100000.00 | 18-FEB-11:50 | 0.00 | 55493.62 | 14-FEB-12:50 | 0.00 |
March | 290771.74 | 14-MAR-13:20 | 8937.21 | 14-MAR-12:50 | 100000.00 | 02-MAR-12:30 | 0.00 | 55227.54 | 06-MAR-12:00 | 0.00 |
April | 196784.22 | 19-APR-13:50 | 4877.54 | 19-APR-13:50 | 100000.00 | 01-APR-00:10 | 0.00 | 53035.75 | 03-APR-11:20 | 0.00 |
May | 293048.21 | 31-MAY-13:30 | 33822.09 | 31-MAY-13:00 | 100000.00 | 01-MAY-11:09 | 0.00 | 51279.63 | 01-MAY-11:50 | 0.00 |
June | 349375.18 | 26-JUN-14:39 | 48194.65 | 16-JUN-14:30 | 100000.00 | 04-JUN-19:00 | 0.00 | 47622.95 | 01-JUN-11:00 | 0.00 |
July | 362421.84 | 18-JUL-14:00 | 48194.65 | 19-JUL-10:20 | 100000.00 | 01-JUL-02:30 | 0.00 | 45267.35 | 03-JUL-11:30 | 0.00 |
August | 389419.53 | 16-AUG-15:30 | 48194.65 | 03-AUG-13:20 | 100000.00 | 01-AUG-07:30 | 0.00 | 44051.99 | 31-AUG-11:00 | 0.00 |
September | 313113.69 | 06-SEP-10:09 | 33550.20 | 13-SEP-14:30 | 100000.00 | 07-SEP-04:00 | 0.00 | 45440.16 | 29-SEP-11:39 | 0.00 |
October | 293598.51 | 10-OCT-13:30 | 11923.94 | 11-OCT-14:39 | 100000.00 | 05-OCT-16:19 | 0.00 | 47825.01 | 31-OCT-11:30 | 0.00 |
November | 210108.30 | 07-NOV-14:00 | 4661.50 | 07-NOV-14:00 | 100000.00 | 02-NOV-12:39 | 0.00 | 51301.37 | 29-NOV-12:30 | 0.00 |
December | 199098.04 | 01-DEC-13:00 | 4340.81 | 01-DEC-13:00 | 100000.00 | 01-DEC-00:30 | 0.00 | 53225.89 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 148847.20 | 1862.79 | 100000.00 | 0.00 | 44051.99 | 0.00 | ||||
Maximum of Months | 389419.53 | 48194.65 | 100000.00 | 0.00 | 55493.62 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1643340.22 | 24-JAN-15:09 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 171632.46 | 40963.81 | 0.00 | 148847.20 | 1711.94 |
February | 1749680.90 | 27-FEB-15:09 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 189748.33 | 40314.84 | 0.00 | 130952.28 | 89.49 |
March | 2140753.97 | 13-MAR-15:20 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 249265.35 | 79961.93 | 0.00 | 282683.70 | 1705.62 |
April | 2131206.29 | 07-APR-15:39 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 266604.35 | 40471.99 | 0.00 | 176679.11 | 3256.53 |
May | 1893940.19 | 18-MAY-14:20 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 259603.30 | 79232.09 | 0.00 | 264261.18 | 14172.36 |
June | 2167221.02 | 26-JUN-14:39 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 397151.93 | 94292.65 | 0.00 | 349375.18 | 32916.63 |
July | 2293009.10 | 18-JUL-14:00 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 393833.47 | 96761.99 | 0.00 | 362421.84 | 29032.86 |
August | 2436855.34 | 16-AUG-15:20 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 379135.53 | 83757.97 | 0.00 | 389222.41 | 48194.65 |
September | 1927914.74 | 12-SEP-15:39 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 322842.36 | 90794.13 | 0.00 | 299591.26 | 31835.88 |
October | 1955170.84 | 11-OCT-10:39 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 193681.64 | 79915.59 | 0.00 | 267050.62 | 9393.90 |
November | 1986705.12 | 07-NOV-15:30 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 229223.56 | 41761.73 | 0.00 | 198378.83 | 4067.74 |
December | 2063458.54 | 04-DEC-15:09 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 224565.55 | 40037.35 | 0.00 | 164558.36 | 1501.53 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1643340.22 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 171632.46 | 40037.35 | 0.00 | 130952.28 | 89.49 | |
Maximum of Months | 2436855.34 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 397151.93 | 96761.99 | 0.00 | 389222.41 | 48194.65 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1571801.14 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1707687.40 | 06-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1378468.77 | 20-MAR-04:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 1232273.66 | 03-APR-04:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 918325.54 | 01-MAY-04:19 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 54227.51 | 09-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 19742.16 | 29-JUL-06:30 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 173199.70 | 23-AUG-05:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 667087.48 | 22-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 1330351.88 | 30-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 1179174.61 | 30-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 1682305.51 | 26-DEC-06:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 19742.16 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 1707687.40 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.76 | 0.00 | 25.76 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.71 | 0.00 | 25.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.74 | 0.00 | 25.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 25.95 | 0.00 | 25.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 26.02 | 0.00 | 26.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.73 | 0.00 | 25.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 25.83 | 0.00 | 25.83 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.75 | 0.00 | 25.75 |
Annual Sum or Average | 0.00 | 0.00 | 18.00 | 25.89 | 0.00 | 25.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 26.02 | 0.00 | 26.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.63 | 0.00 | 25.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.63 | 0.00 | 25.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.63 | 0.00 | 25.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
Annual Sum or Average | 0.17 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 |
February | 2.33 | 18.17 | 0.00 | 18.17 | 0.00 | 18.17 | 0.00 | 18.17 |
March | 0.83 | 17.81 | 0.00 | 17.81 | 0.00 | 17.81 | 0.00 | 17.81 |
April | 1.67 | 18.26 | 0.17 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 |
May | 0.17 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.33 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 |
November | 1.67 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
December | 3.17 | 18.60 | 0.17 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 |
Annual Sum or Average | 13.67 | 18.39 | 0.33 | 18.43 | 0.00 | 18.43 | 0.00 | 18.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.16 | 0.17 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
February | 1.17 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
March | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
April | 0.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.62 | 2.17 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
November | 0.33 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
December | 2.17 | 18.22 | 0.17 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
Annual Sum or Average | 5.00 | 18.69 | 0.17 | 18.74 | 2.17 | 21.37 | 2.17 | 22.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 19.44 | 0.17 | 19.44 | 2.17 | 27.62 | 2.17 | 27.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
February | 1.67 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
March | 0.17 | 19.21 | 0.00 | 19.21 | 1.50 | 27.03 | 1.50 | 27.44 |
April | 0.67 | 19.18 | 0.00 | 19.18 | 0.67 | 23.39 | 0.67 | 24.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.69 | 0.67 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.10 | 3.50 | 28.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.46 | 7.67 | 28.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.73 | 3.50 | 28.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.33 | 2.83 | 28.33 |
October | 0.50 | 19.23 | 0.00 | 19.23 | 1.83 | 25.97 | 1.83 | 26.78 |
November | 0.67 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
December | 2.50 | 18.18 | 0.17 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
Annual Sum or Average | 7.17 | 18.76 | 0.17 | 18.79 | 22.17 | 25.93 | 22.17 | 26.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.32 | 0.00 | 18.32 |
Maximum of Months | 2.50 | 19.23 | 0.17 | 19.23 | 7.67 | 28.73 | 7.67 | 28.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 18.66 | 0.00 | 18.66 | 4.50 | 26.31 | 4.50 | 27.19 |
February | 2.33 | 18.62 | 0.17 | 18.74 | 2.50 | 23.56 | 2.50 | 25.16 |
March | 0.17 | 18.76 | 0.00 | 18.76 | 2.50 | 27.72 | 2.50 | 28.01 |
April | 1.00 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.71 | 1.00 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.71 | 5.00 | 27.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.12 | 4.33 | 28.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.81 | 7.83 | 27.81 |
October | 0.50 | 18.81 | 0.00 | 18.81 | 6.33 | 28.10 | 6.33 | 28.45 |
November | 0.83 | 19.11 | 0.00 | 19.11 | 6.00 | 27.46 | 6.00 | 28.00 |
December | 2.67 | 18.03 | 0.17 | 18.16 | 3.83 | 24.23 | 3.83 | 25.86 |
Annual Sum or Average | 8.67 | 18.54 | 0.33 | 18.61 | 43.83 | 26.63 | 43.83 | 27.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 19.11 | 0.17 | 19.11 | 7.83 | 28.12 | 7.83 | 28.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
February | 0.83 | 19.20 | 0.00 | 19.20 | 0.33 | 21.54 | 0.33 | 22.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.89 | 1.17 | 28.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 28.07 | 0.33 | 28.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.59 | 1.33 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 29.21 | 3.67 | 29.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.36 | 6.67 | 28.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.36 | 3.00 | 28.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.45 | 4.67 | 28.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.47 | 2.50 | 28.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 28.44 | 0.67 | 28.44 |
December | 1.33 | 19.06 | 0.00 | 19.06 | 0.83 | 22.33 | 0.83 | 23.79 |
Annual Sum or Average | 2.50 | 19.12 | 0.00 | 19.12 | 38.17 | 27.91 | 25.17 | 28.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.15 | 0.00 | 19.15 |
Maximum of Months | 1.33 | 19.20 | 0.00 | 19.20 | 10.00 | 29.21 | 6.67 | 29.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.00 | 17.44 | 0.67 | 17.35 | 0.00 | 17.35 | 0.00 | 17.35 |
February | 17.00 | 16.31 | 3.17 | 16.21 | 0.00 | 16.21 | 0.00 | 16.21 |
March | 8.67 | 16.66 | 1.83 | 16.32 | 0.00 | 16.32 | 0.00 | 16.32 |
April | 3.33 | 18.25 | 0.17 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 |
May | 0.50 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.58 | 0.50 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
October | 3.33 | 17.29 | 0.00 | 17.29 | 0.00 | 17.29 | 0.00 | 17.29 |
November | 5.67 | 18.46 | 0.67 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
December | 23.67 | 15.80 | 2.67 | 15.74 | 0.00 | 15.74 | 0.00 | 15.74 |
Annual Sum or Average | 69.33 | 16.64 | 9.17 | 16.54 | 0.50 | 16.61 | 0.50 | 16.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.67 | 19.43 | 3.17 | 19.43 | 0.50 | 27.58 | 0.50 | 27.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.83 | 18.44 | 0.17 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 |
February | 21.83 | 17.01 | 2.67 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 |
March | 14.17 | 17.57 | 1.83 | 17.19 | 0.50 | 17.51 | 0.50 | 17.81 |
April | 4.17 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
May | 0.50 | 19.26 | 0.00 | 19.26 | 0.67 | 24.07 | 0.67 | 25.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.21 | 3.67 | 28.21 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.49 | 9.33 | 28.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.74 | 4.00 | 28.74 |
September | 0.17 | 19.40 | 0.00 | 19.40 | 2.50 | 27.68 | 2.50 | 27.94 |
October | 8.33 | 18.35 | 0.00 | 18.35 | 0.33 | 18.71 | 0.33 | 19.04 |
November | 7.33 | 18.62 | 0.17 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
December | 33.33 | 16.80 | 1.83 | 16.71 | 0.00 | 16.71 | 0.00 | 16.71 |
Annual Sum or Average | 99.67 | 17.46 | 6.67 | 17.31 | 21.00 | 19.14 | 21.00 | 20.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 0.00 | 16.71 |
Maximum of Months | 33.33 | 19.40 | 2.67 | 19.40 | 9.33 | 28.74 | 9.33 | 28.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 18.23 | 0.00 | 18.23 | 12.50 | 24.31 | 12.50 | 25.18 |
February | 11.17 | 16.93 | 1.50 | 16.89 | 3.17 | 19.22 | 3.17 | 20.77 |
March | 7.83 | 16.80 | 1.67 | 16.45 | 2.67 | 19.08 | 2.67 | 20.77 |
April | 3.00 | 18.14 | 0.17 | 18.25 | 0.00 | 18.25 | 0.00 | 18.25 |
May | 0.50 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.73 | 1.00 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.78 | 3.67 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.08 | 4.00 | 28.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.40 | 10.00 | 27.40 |
October | 1.83 | 18.05 | 0.00 | 18.05 | 11.00 | 26.07 | 11.00 | 26.69 |
November | 4.33 | 18.47 | 0.33 | 18.61 | 13.67 | 24.71 | 13.67 | 25.60 |
December | 13.67 | 16.40 | 1.17 | 16.37 | 5.17 | 19.29 | 5.17 | 21.01 |
Annual Sum or Average | 46.50 | 17.16 | 4.83 | 17.07 | 67.00 | 22.84 | 66.83 | 24.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.25 | 0.00 | 18.25 |
Maximum of Months | 13.67 | 19.33 | 1.67 | 19.33 | 13.67 | 28.08 | 13.67 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 |
February | 10.50 | 16.87 | 1.00 | 16.76 | 0.00 | 16.76 | 0.00 | 16.76 |
March | 7.17 | 16.71 | 1.50 | 16.28 | 1.17 | 17.69 | 0.83 | 18.51 |
April | 2.67 | 18.21 | 0.00 | 18.21 | 0.17 | 18.82 | 0.17 | 19.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.45 | 0.50 | 27.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 29.16 | 3.17 | 29.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.69 | 2.67 | 28.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.94 | 1.67 | 29.00 |
September | 0.17 | 19.38 | 0.00 | 19.38 | 3.50 | 28.27 | 2.50 | 28.47 |
October | 1.67 | 17.99 | 0.00 | 17.99 | 1.67 | 23.18 | 1.33 | 24.69 |
November | 4.17 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 |
December | 13.83 | 16.25 | 1.33 | 16.16 | 0.00 | 16.16 | 0.00 | 16.16 |
Annual Sum or Average | 44.83 | 17.06 | 3.83 | 16.89 | 20.50 | 20.41 | 12.83 | 21.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.16 | 0.00 | 16.16 |
Maximum of Months | 13.83 | 19.38 | 1.50 | 19.38 | 5.83 | 29.16 | 3.17 | 29.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 37.17 | 15.33 | 5.33 | 15.24 | 0.00 | 15.24 | 0.00 | 15.24 |
February | 36.67 | 15.29 | 7.00 | 15.14 | 0.00 | 15.14 | 0.00 | 15.14 |
March | 24.50 | 15.59 | 4.83 | 15.43 | 0.00 | 15.43 | 0.00 | 15.43 |
April | 24.00 | 15.36 | 6.33 | 15.24 | 0.00 | 15.24 | 0.00 | 15.24 |
May | 1.67 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.59 | 0.83 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.83 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 |
October | 16.50 | 16.01 | 3.00 | 15.79 | 0.00 | 15.79 | 0.00 | 15.79 |
November | 20.83 | 16.09 | 1.33 | 16.09 | 0.00 | 16.09 | 0.00 | 16.09 |
December | 47.17 | 14.97 | 11.17 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
Annual Sum or Average | 209.33 | 15.44 | 39.00 | 15.31 | 0.83 | 15.35 | 0.83 | 15.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.17 | 18.65 | 11.17 | 18.65 | 0.83 | 27.59 | 0.83 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.33 | 15.42 | 2.50 | 15.38 | 0.00 | 15.38 | 0.00 | 15.38 |
February | 32.67 | 15.22 | 4.50 | 15.09 | 0.00 | 15.09 | 0.00 | 15.09 |
March | 22.33 | 15.43 | 3.67 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 |
April | 23.67 | 15.35 | 5.50 | 15.24 | 0.00 | 15.24 | 0.00 | 15.24 |
May | 2.00 | 18.03 | 0.00 | 18.03 | 0.00 | 18.03 | 0.00 | 18.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.01 | 4.33 | 28.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.50 | 9.83 | 28.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.54 | 4.33 | 28.54 |
September | 0.83 | 18.39 | 0.00 | 18.39 | 1.83 | 24.91 | 1.83 | 26.12 |
October | 15.50 | 16.04 | 2.83 | 15.80 | 0.00 | 15.80 | 0.00 | 15.80 |
November | 19.50 | 15.98 | 1.17 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 |
December | 42.33 | 14.91 | 6.83 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
Annual Sum or Average | 191.17 | 15.42 | 27.00 | 15.31 | 20.33 | 16.42 | 20.33 | 17.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.87 | 0.00 | 14.87 |
Maximum of Months | 42.33 | 18.39 | 6.83 | 18.39 | 9.83 | 28.54 | 9.83 | 28.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.33 | 16.02 | 2.00 | 15.92 | 1.17 | 16.51 | 1.17 | 17.04 |
February | 27.17 | 15.50 | 4.33 | 15.32 | 1.33 | 15.85 | 1.33 | 16.34 |
March | 20.83 | 15.69 | 3.83 | 15.45 | 1.50 | 16.20 | 1.50 | 16.86 |
April | 23.67 | 15.38 | 6.33 | 15.26 | 0.00 | 15.26 | 0.00 | 15.26 |
May | 1.67 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.92 | 1.33 | 27.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.89 | 4.00 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.20 | 3.50 | 28.20 |
September | 0.67 | 18.24 | 0.00 | 18.24 | 5.83 | 27.63 | 5.67 | 28.15 |
October | 13.67 | 16.05 | 2.33 | 15.84 | 5.67 | 19.22 | 5.67 | 21.21 |
November | 14.17 | 16.57 | 0.50 | 16.63 | 2.83 | 18.60 | 2.83 | 20.03 |
December | 32.50 | 15.19 | 3.50 | 15.12 | 2.17 | 15.88 | 2.17 | 16.56 |
Annual Sum or Average | 154.67 | 15.70 | 22.83 | 15.56 | 29.33 | 17.39 | 29.17 | 18.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.26 | 0.00 | 15.26 |
Maximum of Months | 32.50 | 18.46 | 6.33 | 18.46 | 5.83 | 28.20 | 5.67 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.17 | 15.80 | 3.33 | 15.65 | 0.00 | 15.65 | 0.00 | 15.65 |
February | 25.50 | 15.52 | 4.50 | 15.33 | 0.00 | 15.33 | 0.00 | 15.33 |
March | 19.00 | 15.72 | 3.50 | 15.46 | 0.83 | 15.90 | 0.50 | 16.16 |
April | 16.00 | 15.53 | 3.50 | 15.40 | 0.17 | 15.51 | 0.17 | 15.62 |
May | 1.00 | 18.80 | 0.00 | 18.80 | 0.67 | 22.25 | 0.67 | 23.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 29.37 | 3.00 | 29.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.84 | 3.33 | 28.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 29.15 | 1.83 | 29.21 |
September | 0.50 | 17.92 | 0.00 | 17.92 | 3.50 | 27.39 | 2.67 | 27.95 |
October | 11.00 | 16.26 | 2.17 | 16.01 | 1.17 | 17.01 | 1.17 | 17.86 |
November | 11.50 | 16.77 | 0.17 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
December | 33.17 | 15.25 | 4.83 | 15.16 | 0.00 | 15.16 | 0.00 | 15.16 |
Annual Sum or Average | 139.83 | 15.72 | 22.00 | 15.56 | 20.67 | 17.07 | 13.33 | 17.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.16 | 0.00 | 15.16 |
Maximum of Months | 33.17 | 18.80 | 4.83 | 18.80 | 6.00 | 29.37 | 3.33 | 29.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.57 | 0.17 | 27.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 49.83 | 27.60 | 41.17 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.59 | 3.67 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 27.80 | 20.50 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 200.67 | 28.30 | 195.50 | 28.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 58.67 | 27.59 | 34.17 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.58 | 1.83 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 347.00 | 28.02 | 297.00 | 28.04 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 200.67 | 28.30 | 195.50 | 28.30 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 388.17 | 23.68 | 32.00 | 23.86 | 12.50 | 23.94 |
February | 339.00 | 23.75 | 31.83 | 23.93 | 0.00 | 23.93 |
March | 382.00 | 23.83 | 14.67 | 23.90 | 0.00 | 23.90 |
April | 255.50 | 23.73 | 42.83 | 23.99 | 0.00 | 23.99 |
May | 188.67 | 23.66 | 118.17 | 24.28 | 0.00 | 24.28 |
June | 12.17 | 24.34 | 287.00 | 24.67 | 3.00 | 24.68 |
July | 31.17 | 25.01 | 346.17 | 24.80 | 20.33 | 24.84 |
August | 7.17 | 24.40 | 347.33 | 24.67 | 5.83 | 24.67 |
September | 47.33 | 23.64 | 190.67 | 25.00 | 0.00 | 25.00 |
October | 127.83 | 23.80 | 105.83 | 24.97 | 0.00 | 24.97 |
November | 127.67 | 23.77 | 101.33 | 24.91 | 0.00 | 24.91 |
December | 364.00 | 23.63 | 48.83 | 23.92 | 0.00 | 23.92 |
Annual Sum or Average | 2270.67 | 23.75 | 1666.67 | 24.34 | 41.67 | 24.35 |
Minimum of Months | 7.17 | 23.63 | 14.67 | 23.86 | 0.00 | 23.90 |
Maximum of Months | 388.17 | 25.01 | 347.33 | 25.00 | 20.33 | 25.00 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 275.17 | 23.67 | 7.00 | 23.71 | 0.00 | 23.71 |
February | 298.33 | 23.63 | 9.67 | 23.69 | 0.00 | 23.69 |
March | 259.83 | 23.74 | 20.50 | 23.84 | 0.00 | 23.84 |
April | 125.33 | 23.80 | 56.00 | 24.24 | 0.00 | 24.24 |
May | 82.83 | 23.77 | 143.00 | 24.40 | 0.00 | 24.40 |
June | 46.83 | 24.18 | 327.67 | 24.29 | 39.83 | 24.29 |
July | 91.83 | 24.33 | 379.67 | 24.32 | 87.33 | 24.32 |
August | 26.50 | 24.16 | 391.00 | 24.29 | 26.50 | 24.28 |
September | 42.00 | 23.85 | 178.00 | 24.53 | 0.00 | 24.53 |
October | 139.00 | 23.81 | 57.00 | 24.25 | 0.00 | 24.25 |
November | 137.67 | 23.80 | 54.50 | 24.33 | 0.00 | 24.33 |
December | 298.83 | 23.79 | 12.50 | 23.87 | 0.00 | 23.87 |
Annual Sum or Average | 1824.17 | 23.79 | 1636.50 | 24.14 | 153.67 | 24.14 |
Minimum of Months | 26.50 | 23.63 | 7.00 | 23.69 | 0.00 | 23.69 |
Maximum of Months | 298.83 | 24.33 | 391.00 | 24.53 | 87.33 | 24.53 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 437.33 | 22.92 | 24.17 | 22.77 | 24.17 | 22.62 |
February | 411.17 | 22.96 | 30.67 | 22.80 | 30.67 | 22.66 |
March | 444.00 | 23.24 | 22.00 | 23.17 | 15.17 | 23.09 |
April | 352.17 | 23.35 | 12.50 | 23.39 | 0.00 | 23.39 |
May | 174.00 | 23.61 | 80.50 | 23.90 | 0.00 | 23.90 |
June | 79.83 | 23.84 | 250.17 | 24.16 | 39.67 | 24.16 |
July | 131.67 | 24.01 | 294.17 | 24.16 | 90.50 | 24.16 |
August | 53.50 | 23.88 | 304.50 | 24.22 | 29.33 | 24.20 |
September | 128.50 | 23.60 | 105.83 | 24.05 | 0.00 | 24.05 |
October | 337.67 | 23.45 | 5.50 | 23.45 | 2.00 | 23.44 |
November | 391.83 | 23.36 | 1.17 | 23.37 | 0.00 | 23.37 |
December | 489.17 | 22.83 | 42.50 | 22.62 | 42.50 | 22.44 |
Annual Sum or Average | 3430.83 | 23.24 | 1173.67 | 23.41 | 274.00 | 23.36 |
Minimum of Months | 53.50 | 22.83 | 1.17 | 22.62 | 0.00 | 22.44 |
Maximum of Months | 489.17 | 24.01 | 304.50 | 24.22 | 90.50 | 24.20 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.67 | 21.24 | 179.67 | 20.82 | 179.67 | 20.58 |
February | 449.33 | 21.45 | 161.50 | 21.08 | 161.50 | 20.86 |
March | 491.17 | 22.02 | 95.50 | 21.67 | 95.50 | 21.42 |
April | 414.00 | 21.84 | 102.50 | 21.43 | 97.83 | 21.13 |
May | 300.83 | 22.83 | 61.00 | 22.98 | 6.83 | 22.94 |
June | 127.67 | 23.35 | 283.83 | 23.89 | 40.00 | 23.89 |
July | 157.33 | 23.65 | 313.33 | 23.97 | 94.17 | 23.96 |
August | 114.50 | 23.39 | 283.50 | 23.93 | 34.67 | 23.92 |
September | 225.50 | 22.91 | 86.83 | 23.26 | 1.17 | 23.25 |
October | 465.67 | 22.06 | 87.33 | 21.78 | 87.33 | 21.59 |
November | 478.67 | 21.63 | 141.50 | 21.32 | 141.50 | 21.12 |
December | 497.00 | 21.04 | 241.00 | 20.68 | 241.00 | 20.49 |
Annual Sum or Average | 4221.33 | 21.94 | 2037.50 | 21.98 | 1181.17 | 21.74 |
Minimum of Months | 114.50 | 21.04 | 61.00 | 20.68 | 1.17 | 20.49 |
Maximum of Months | 499.67 | 23.65 | 313.33 | 23.97 | 241.00 | 23.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.46 | 132.50 | 21.25 | 132.50 | 21.12 |
February | 454.00 | 21.37 | 154.67 | 21.11 | 154.67 | 20.96 |
March | 489.67 | 22.05 | 65.17 | 21.82 | 65.17 | 21.63 |
April | 397.17 | 22.22 | 45.17 | 22.09 | 39.17 | 21.96 |
May | 236.83 | 22.98 | 104.67 | 23.39 | 0.00 | 23.39 |
June | 50.50 | 23.92 | 378.00 | 24.22 | 34.00 | 24.22 |
July | 86.00 | 24.29 | 409.83 | 24.32 | 79.17 | 24.33 |
August | 54.17 | 23.53 | 365.33 | 24.11 | 21.17 | 24.11 |
September | 182.83 | 23.03 | 142.17 | 23.64 | 0.00 | 23.64 |
October | 458.50 | 22.32 | 43.50 | 22.18 | 43.50 | 22.05 |
November | 475.00 | 21.92 | 47.50 | 21.82 | 47.50 | 21.74 |
December | 497.00 | 21.40 | 191.00 | 21.13 | 191.00 | 20.98 |
Annual Sum or Average | 3883.67 | 22.04 | 2079.50 | 22.39 | 807.83 | 22.23 |
Minimum of Months | 50.50 | 21.37 | 43.50 | 21.11 | 0.00 | 20.96 |
Maximum of Months | 502.00 | 24.29 | 409.83 | 24.32 | 191.00 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 466.67 | 21.37 | 115.00 | 21.24 | 109.50 | 21.13 |
February | 403.17 | 21.30 | 158.00 | 21.19 | 135.50 | 21.03 |
March | 415.67 | 21.62 | 115.17 | 21.68 | 69.50 | 21.52 |
April | 354.17 | 21.67 | 104.00 | 21.85 | 45.67 | 21.71 |
May | 232.33 | 22.44 | 171.17 | 23.24 | 2.00 | 23.26 |
June | 99.00 | 23.46 | 374.83 | 24.02 | 38.17 | 24.07 |
July | 147.83 | 23.87 | 393.67 | 24.15 | 95.83 | 24.21 |
August | 143.50 | 23.15 | 342.00 | 23.84 | 38.50 | 23.91 |
September | 192.00 | 22.67 | 219.83 | 23.55 | 11.00 | 23.63 |
October | 393.67 | 21.84 | 109.00 | 22.04 | 56.17 | 21.95 |
November | 440.50 | 21.59 | 83.00 | 21.61 | 61.33 | 21.52 |
December | 476.50 | 21.21 | 186.50 | 21.02 | 184.33 | 20.90 |
Annual Sum or Average | 3765.00 | 21.83 | 2372.17 | 22.36 | 847.50 | 22.25 |
Minimum of Months | 99.00 | 21.21 | 83.00 | 21.02 | 2.00 | 20.90 |
Maximum of Months | 476.50 | 23.87 | 393.67 | 24.15 | 184.33 | 24.21 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 321.67 | 21.74 | 221.83 | 22.30 | 91.83 | 22.16 |
February | 292.67 | 21.42 | 231.33 | 21.85 | 119.00 | 21.61 |
March | 348.83 | 21.67 | 179.33 | 21.97 | 82.50 | 21.79 |
April | 344.33 | 21.56 | 135.00 | 21.70 | 68.33 | 21.49 |
May | 265.17 | 22.44 | 129.33 | 23.02 | 3.00 | 23.00 |
June | 120.17 | 23.11 | 326.83 | 23.91 | 34.33 | 23.92 |
July | 146.83 | 23.71 | 370.17 | 24.11 | 83.50 | 24.15 |
August | 108.83 | 23.50 | 368.33 | 24.05 | 37.17 | 24.12 |
September | 174.00 | 23.23 | 255.00 | 23.97 | 26.67 | 24.12 |
October | 322.17 | 22.17 | 222.50 | 22.66 | 89.33 | 22.60 |
November | 301.50 | 22.06 | 213.50 | 22.71 | 75.33 | 22.66 |
December | 346.17 | 21.60 | 238.17 | 21.88 | 146.50 | 21.71 |
Annual Sum or Average | 3092.33 | 22.10 | 2891.33 | 22.79 | 857.50 | 22.68 |
Minimum of Months | 108.83 | 21.42 | 129.33 | 21.70 | 3.00 | 21.49 |
Maximum of Months | 348.83 | 23.71 | 370.17 | 24.11 | 146.50 | 24.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 436.67 | 21.45 | 92.33 | 21.53 | 58.17 | 21.43 |
February | 386.50 | 21.36 | 108.33 | 21.46 | 68.17 | 21.33 |
March | 406.33 | 21.88 | 91.33 | 22.13 | 26.83 | 22.07 |
April | 311.83 | 22.21 | 104.50 | 22.68 | 5.17 | 22.69 |
May | 240.00 | 22.36 | 187.33 | 23.27 | 4.33 | 23.30 |
June | 129.00 | 23.60 | 386.83 | 24.14 | 65.33 | 24.20 |
July | 123.50 | 24.39 | 431.83 | 24.36 | 99.50 | 24.42 |
August | 82.83 | 24.48 | 451.83 | 24.35 | 67.17 | 24.41 |
September | 196.33 | 22.73 | 222.50 | 23.69 | 18.17 | 23.82 |
October | 399.17 | 22.02 | 97.50 | 22.37 | 26.00 | 22.39 |
November | 386.83 | 21.88 | 78.33 | 22.19 | 16.50 | 22.16 |
December | 433.17 | 21.66 | 104.33 | 21.69 | 73.67 | 21.56 |
Annual Sum or Average | 3532.17 | 22.08 | 2357.00 | 22.82 | 529.00 | 22.83 |
Minimum of Months | 82.83 | 21.36 | 78.33 | 21.46 | 4.33 | 21.33 |
Maximum of Months | 436.67 | 24.48 | 451.83 | 24.36 | 99.50 | 24.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.38 | 311.83 | 20.19 | 311.83 | 20.11 |
February | 454.00 | 20.43 | 306.67 | 20.29 | 306.67 | 20.24 |
March | 514.00 | 21.01 | 214.17 | 20.73 | 214.17 | 20.58 |
April | 467.33 | 21.12 | 152.33 | 20.78 | 149.50 | 20.56 |
May | 365.50 | 22.35 | 65.67 | 22.52 | 12.83 | 22.47 |
June | 128.33 | 23.09 | 295.33 | 23.76 | 33.83 | 23.75 |
July | 152.33 | 23.22 | 331.17 | 23.80 | 76.17 | 23.76 |
August | 173.67 | 22.79 | 256.17 | 23.52 | 23.50 | 23.50 |
September | 307.33 | 22.41 | 92.33 | 22.73 | 10.83 | 22.68 |
October | 498.67 | 21.22 | 141.50 | 20.98 | 141.50 | 20.82 |
November | 489.00 | 20.75 | 251.17 | 20.56 | 251.17 | 20.47 |
December | 497.00 | 20.21 | 395.33 | 20.10 | 395.33 | 20.06 |
Annual Sum or Average | 4549.17 | 21.20 | 2813.67 | 21.31 | 1927.33 | 21.09 |
Minimum of Months | 128.33 | 20.21 | 65.67 | 20.10 | 10.83 | 20.06 |
Maximum of Months | 514.00 | 23.22 | 395.33 | 23.80 | 395.33 | 23.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 420.00 | 20.71 | 216.67 | 20.47 | 216.67 | 20.35 |
February | 362.17 | 20.70 | 194.83 | 20.47 | 185.67 | 20.32 |
March | 375.17 | 21.10 | 168.50 | 20.98 | 140.83 | 20.77 |
April | 331.67 | 20.91 | 154.00 | 20.82 | 117.00 | 20.56 |
May | 247.83 | 22.14 | 124.67 | 22.83 | 9.67 | 22.80 |
June | 112.33 | 23.25 | 278.67 | 23.94 | 34.50 | 24.00 |
July | 156.00 | 23.68 | 310.83 | 24.11 | 92.67 | 24.17 |
August | 157.67 | 23.02 | 258.67 | 23.76 | 41.50 | 23.85 |
September | 212.33 | 22.37 | 152.00 | 23.18 | 13.83 | 23.22 |
October | 360.17 | 21.29 | 130.33 | 21.26 | 101.67 | 21.07 |
November | 397.83 | 20.99 | 174.67 | 20.81 | 170.50 | 20.70 |
December | 421.67 | 20.41 | 281.83 | 20.19 | 281.83 | 20.09 |
Annual Sum or Average | 3554.83 | 21.33 | 2445.67 | 21.66 | 1406.33 | 21.45 |
Minimum of Months | 112.33 | 20.41 | 124.67 | 20.19 | 9.67 | 20.09 |
Maximum of Months | 421.67 | 23.68 | 310.83 | 24.11 | 281.83 | 24.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 332.33 | 21.56 | 264.33 | 22.03 | 140.83 | 21.86 |
February | 295.17 | 21.16 | 266.00 | 21.60 | 151.33 | 21.35 |
March | 354.83 | 21.35 | 231.50 | 21.61 | 134.50 | 21.39 |
April | 360.50 | 21.02 | 183.33 | 21.03 | 122.33 | 20.75 |
May | 289.17 | 22.21 | 128.67 | 22.76 | 12.67 | 22.70 |
June | 152.00 | 22.85 | 291.67 | 23.69 | 34.33 | 23.69 |
July | 175.83 | 23.30 | 342.17 | 23.91 | 81.83 | 23.92 |
August | 144.83 | 23.07 | 331.17 | 23.88 | 35.33 | 23.94 |
September | 199.50 | 23.05 | 241.17 | 23.80 | 33.83 | 23.94 |
October | 327.33 | 21.88 | 246.00 | 22.37 | 116.00 | 22.27 |
November | 309.83 | 21.82 | 257.33 | 22.41 | 123.83 | 22.29 |
December | 362.17 | 21.20 | 289.50 | 21.39 | 207.17 | 21.19 |
Annual Sum or Average | 3303.50 | 21.82 | 3072.83 | 22.44 | 1194.00 | 22.27 |
Minimum of Months | 144.83 | 21.02 | 128.67 | 21.03 | 12.67 | 20.75 |
Maximum of Months | 362.17 | 23.30 | 342.17 | 23.91 | 207.17 | 23.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 472.67 | 20.76 | 229.67 | 20.60 | 218.50 | 20.47 |
February | 415.83 | 20.74 | 236.50 | 20.63 | 217.50 | 20.50 |
March | 446.17 | 20.99 | 192.83 | 21.00 | 150.67 | 20.83 |
April | 412.50 | 21.02 | 156.17 | 20.97 | 114.67 | 20.75 |
May | 337.17 | 21.97 | 131.83 | 22.59 | 10.17 | 22.57 |
June | 196.00 | 22.75 | 295.83 | 23.60 | 59.50 | 23.66 |
July | 205.17 | 22.77 | 321.00 | 23.53 | 85.17 | 23.54 |
August | 201.50 | 22.49 | 286.33 | 23.45 | 40.83 | 23.49 |
September | 303.50 | 22.21 | 147.83 | 22.91 | 18.17 | 22.98 |
October | 427.17 | 21.17 | 167.50 | 21.29 | 116.50 | 21.15 |
November | 448.17 | 21.02 | 190.00 | 20.95 | 169.17 | 20.83 |
December | 481.33 | 20.55 | 304.00 | 20.35 | 303.17 | 20.26 |
Annual Sum or Average | 4347.17 | 21.31 | 2659.50 | 21.64 | 1504.00 | 21.46 |
Minimum of Months | 196.00 | 20.55 | 131.83 | 20.35 | 10.17 | 20.26 |
Maximum of Months | 481.33 | 22.77 | 321.00 | 23.60 | 303.17 | 23.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.98 | 393.33 | 19.85 | 393.33 | 19.79 |
February | 454.00 | 20.10 | 368.17 | 20.00 | 368.17 | 19.96 |
March | 514.00 | 20.63 | 296.83 | 20.40 | 296.83 | 20.29 |
April | 473.67 | 20.60 | 221.50 | 20.23 | 221.50 | 20.04 |
May | 418.00 | 21.78 | 90.67 | 21.84 | 50.67 | 21.72 |
June | 193.00 | 22.48 | 262.00 | 23.31 | 34.33 | 23.29 |
July | 210.67 | 22.62 | 305.67 | 23.35 | 82.67 | 23.31 |
August | 237.67 | 22.26 | 226.17 | 23.04 | 27.67 | 23.02 |
September | 350.33 | 21.83 | 114.67 | 22.07 | 41.00 | 21.93 |
October | 500.33 | 20.64 | 258.83 | 20.39 | 258.83 | 20.26 |
November | 489.00 | 20.17 | 352.00 | 20.00 | 352.00 | 19.93 |
December | 497.00 | 19.91 | 447.17 | 19.85 | 447.17 | 19.82 |
Annual Sum or Average | 4839.67 | 20.82 | 3337.00 | 20.86 | 2574.17 | 20.65 |
Minimum of Months | 193.00 | 19.91 | 90.67 | 19.85 | 27.67 | 19.79 |
Maximum of Months | 514.00 | 22.62 | 447.17 | 23.35 | 447.17 | 23.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.33 | 20.28 | 307.67 | 20.02 | 307.67 | 19.90 |
February | 441.00 | 20.50 | 261.33 | 20.21 | 261.33 | 20.08 |
March | 441.50 | 20.91 | 220.00 | 20.68 | 202.83 | 20.49 |
April | 384.67 | 20.54 | 210.33 | 20.39 | 169.83 | 20.11 |
May | 295.67 | 21.89 | 163.67 | 22.52 | 25.50 | 22.42 |
June | 128.67 | 23.18 | 356.00 | 23.89 | 43.00 | 23.94 |
July | 181.17 | 23.58 | 387.50 | 24.01 | 110.33 | 24.07 |
August | 166.83 | 22.90 | 344.83 | 23.74 | 46.17 | 23.81 |
September | 234.00 | 22.08 | 219.00 | 22.99 | 24.33 | 22.93 |
October | 439.33 | 21.07 | 211.00 | 20.87 | 189.83 | 20.67 |
November | 483.00 | 20.61 | 263.17 | 20.33 | 263.17 | 20.20 |
December | 497.00 | 20.09 | 374.83 | 19.92 | 374.83 | 19.86 |
Annual Sum or Average | 4193.17 | 21.04 | 3319.33 | 21.36 | 2018.83 | 21.11 |
Minimum of Months | 128.67 | 20.09 | 163.67 | 19.92 | 24.33 | 19.86 |
Maximum of Months | 500.33 | 23.58 | 387.50 | 24.01 | 374.83 | 24.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 351.33 | 20.71 | 309.33 | 21.06 | 202.00 | 20.79 |
February | 319.33 | 20.67 | 292.67 | 20.98 | 197.83 | 20.72 |
March | 375.00 | 20.91 | 285.83 | 21.11 | 198.50 | 20.89 |
April | 375.67 | 20.48 | 244.83 | 20.46 | 186.67 | 20.19 |
May | 334.67 | 21.74 | 155.67 | 22.17 | 47.83 | 22.03 |
June | 197.00 | 22.43 | 272.50 | 23.35 | 37.67 | 23.36 |
July | 215.67 | 22.77 | 322.83 | 23.54 | 88.17 | 23.56 |
August | 195.00 | 22.53 | 304.67 | 23.51 | 40.00 | 23.56 |
September | 244.17 | 22.47 | 241.17 | 23.25 | 47.33 | 23.27 |
October | 347.33 | 21.20 | 302.67 | 21.60 | 183.67 | 21.40 |
November | 333.17 | 21.05 | 296.17 | 21.49 | 176.83 | 21.25 |
December | 395.17 | 20.63 | 329.00 | 20.71 | 261.67 | 20.50 |
Annual Sum or Average | 3683.50 | 21.29 | 3357.33 | 21.80 | 1668.17 | 21.55 |
Minimum of Months | 195.00 | 20.48 | 155.67 | 20.46 | 37.67 | 20.19 |
Maximum of Months | 395.17 | 22.77 | 329.00 | 23.54 | 261.67 | 23.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 477.33 | 20.40 | 311.50 | 20.22 | 302.83 | 20.11 |
February | 416.17 | 20.45 | 287.83 | 20.34 | 269.17 | 20.22 |
March | 445.83 | 20.76 | 257.67 | 20.74 | 215.67 | 20.58 |
April | 412.83 | 20.61 | 222.83 | 20.53 | 177.83 | 20.29 |
May | 349.83 | 21.69 | 156.50 | 22.24 | 39.33 | 22.16 |
June | 223.33 | 22.58 | 290.00 | 23.44 | 70.67 | 23.53 |
July | 236.00 | 22.59 | 315.67 | 23.36 | 97.83 | 23.39 |
August | 236.00 | 22.35 | 278.17 | 23.27 | 53.00 | 23.33 |
September | 317.83 | 21.96 | 168.33 | 22.59 | 39.83 | 22.58 |
October | 428.17 | 20.80 | 246.00 | 20.84 | 197.00 | 20.66 |
November | 452.67 | 20.61 | 273.33 | 20.48 | 254.83 | 20.36 |
December | 484.67 | 20.23 | 360.83 | 20.04 | 359.83 | 19.97 |
Annual Sum or Average | 4480.67 | 21.04 | 3168.67 | 21.30 | 2077.83 | 21.10 |
Minimum of Months | 223.33 | 20.23 | 156.50 | 20.04 | 39.33 | 19.97 |
Maximum of Months | 484.67 | 22.59 | 360.83 | 23.44 | 359.83 | 23.53 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.83 | 27.00 | 501.83 | 27.00 | 9.83 | 27.00 |
February | 12.33 | 27.00 | 447.00 | 27.00 | 12.33 | 27.00 |
March | 23.00 | 27.00 | 514.00 | 27.00 | 23.00 | 27.00 |
April | 62.33 | 27.00 | 485.00 | 27.00 | 62.33 | 27.00 |
May | 26.67 | 27.00 | 508.00 | 27.00 | 26.67 | 27.00 |
June | 157.67 | 27.00 | 496.00 | 27.00 | 157.67 | 27.00 |
July | 229.83 | 27.00 | 497.00 | 27.00 | 229.83 | 27.00 |
August | 330.00 | 27.00 | 514.00 | 27.00 | 330.00 | 27.00 |
September | 49.33 | 27.00 | 485.00 | 27.00 | 49.33 | 27.00 |
October | 27.33 | 27.00 | 502.00 | 27.00 | 27.33 | 27.00 |
November | 30.83 | 27.00 | 489.00 | 27.00 | 30.83 | 27.00 |
December | 17.33 | 27.00 | 492.33 | 27.00 | 17.33 | 27.00 |
Annual Sum or Average | 976.50 | 27.00 | 5931.17 | 27.00 | 976.50 | 27.00 |
Minimum of Months | 9.83 | 27.00 | 447.00 | 27.00 | 9.83 | 27.00 |
Maximum of Months | 330.00 | 27.00 | 514.00 | 27.00 | 330.00 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 27.00 | 440.17 | 27.00 | 2.50 | 27.00 |
February | 10.50 | 27.00 | 385.50 | 27.00 | 7.00 | 27.00 |
March | 9.83 | 27.00 | 484.17 | 27.00 | 9.83 | 27.00 |
April | 10.17 | 27.00 | 463.67 | 27.00 | 10.17 | 27.00 |
May | 7.83 | 27.00 | 508.00 | 27.00 | 7.83 | 27.00 |
June | 73.00 | 27.00 | 496.00 | 27.00 | 73.00 | 27.00 |
July | 94.33 | 27.00 | 497.00 | 27.00 | 94.33 | 27.00 |
August | 121.33 | 27.00 | 514.00 | 27.00 | 121.33 | 27.00 |
September | 22.50 | 27.00 | 485.00 | 27.00 | 22.50 | 27.00 |
October | 12.83 | 27.00 | 473.83 | 27.00 | 12.83 | 27.00 |
November | 9.83 | 27.00 | 475.83 | 27.00 | 9.83 | 27.00 |
December | 13.67 | 27.00 | 403.17 | 27.00 | 1.17 | 27.00 |
Annual Sum or Average | 388.33 | 27.00 | 5626.33 | 27.00 | 372.33 | 27.00 |
Minimum of Months | 2.50 | 27.00 | 385.50 | 27.00 | 1.17 | 27.00 |
Maximum of Months | 121.33 | 27.00 | 514.00 | 27.00 | 121.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 63.33 | 25.86 | 316.17 | 26.81 | 1.83 | 26.81 |
February | 44.50 | 27.00 | 267.17 | 27.00 | 6.17 | 27.00 |
March | 32.00 | 27.00 | 398.00 | 27.00 | 11.50 | 27.00 |
April | 43.50 | 27.00 | 402.33 | 27.00 | 17.33 | 27.00 |
May | 24.50 | 26.99 | 498.17 | 27.00 | 24.17 | 27.00 |
June | 134.50 | 27.00 | 496.00 | 27.00 | 134.50 | 27.00 |
July | 142.00 | 27.00 | 497.00 | 27.00 | 142.00 | 27.00 |
August | 169.00 | 27.00 | 514.00 | 27.00 | 169.00 | 27.00 |
September | 37.17 | 27.00 | 474.00 | 27.00 | 37.17 | 27.00 |
October | 32.83 | 27.00 | 397.50 | 27.00 | 13.50 | 27.00 |
November | 18.17 | 27.00 | 360.83 | 27.00 | 7.17 | 27.00 |
December | 58.17 | 27.00 | 263.17 | 27.00 | 0.83 | 27.00 |
Annual Sum or Average | 799.67 | 26.91 | 4884.33 | 26.99 | 565.17 | 26.99 |
Minimum of Months | 18.17 | 25.86 | 263.17 | 26.81 | 0.83 | 26.81 |
Maximum of Months | 169.00 | 27.00 | 514.00 | 27.00 | 169.00 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 408.17 | 27.20 | 502.00 | 27.20 | 408.17 | 27.20 |
February | 0.00 | 0.00 | 450.83 | 24.47 | 0.00 | 24.47 |
March | 170.50 | 25.97 | 504.00 | 25.75 | 170.33 | 25.79 |
April | 252.00 | 25.80 | 485.00 | 25.21 | 252.00 | 25.36 |
May | 466.50 | 27.22 | 508.00 | 27.22 | 466.50 | 27.22 |
June | 373.33 | 26.97 | 495.50 | 26.61 | 373.33 | 26.72 |
July | 478.00 | 26.94 | 496.50 | 26.87 | 478.00 | 26.89 |
August | 510.67 | 27.31 | 514.00 | 27.30 | 510.67 | 27.30 |
September | 485.00 | 27.18 | 485.00 | 27.18 | 485.00 | 27.18 |
October | 30.33 | 27.20 | 498.50 | 24.69 | 30.33 | 24.83 |
November | 450.00 | 25.79 | 487.67 | 25.69 | 450.00 | 25.72 |
December | 249.17 | 25.33 | 497.00 | 24.89 | 249.17 | 25.00 |
Annual Sum or Average | 3873.67 | 26.73 | 5924.00 | 26.29 | 3873.50 | 26.42 |
Minimum of Months | 0.00 | 0.00 | 450.83 | 24.47 | 0.00 | 24.47 |
Maximum of Months | 510.67 | 27.31 | 514.00 | 27.30 | 510.67 | 27.30 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 19.70164 | 0.73227 | 16.49970 |
February | 454.00000 | 27.00000 | 17.14888 | 0.72175 | 16.23047 |
March | 514.00000 | 27.00000 | 17.79511 | 0.78912 | 18.33319 |
April | 485.00000 | 27.00000 | 21.03756 | 0.85694 | 20.71072 |
May | 508.00000 | 27.00003 | 24.97182 | 0.17475 | 5.88226 |
June | 496.00000 | 27.00007 | 28.59259 | 0.30516 | 7.13265 |
July | 497.00000 | 27.00004 | 28.90063 | 0.35455 | 7.78424 |
August | 514.00000 | 27.00009 | 28.58357 | 0.40590 | 8.59266 |
September | 485.00000 | 27.00002 | 24.62763 | 0.21011 | 6.20309 |
October | 502.00000 | 27.00000 | 19.78351 | 0.79079 | 18.40340 |
November | 489.00000 | 27.00000 | 20.26418 | 0.81435 | 19.18531 |
December | 497.00000 | 27.00000 | 14.64108 | 0.76025 | 17.39644 |
Annual Sum or Average | 5943.00000 | 27.00002 | 22.21276 | 0.57486 | 13.49579 |
Minimum of Months | 454.00000 | 27.00000 | 14.64108 | 0.17475 | 5.88226 |
Maximum of Months | 514.00000 | 27.00009 | 28.90063 | 0.85694 | 20.71072 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99952 | 19.68876 | 0.64052 | 13.92555 |
February | 454.00000 | 27.00000 | 17.14449 | 0.63641 | 13.88529 |
March | 514.00000 | 27.00000 | 17.79111 | 0.69092 | 15.35046 |
April | 485.00000 | 27.00000 | 21.04358 | 0.73755 | 16.79319 |
May | 508.00000 | 27.00003 | 24.95879 | 0.09564 | 5.53071 |
June | 496.00000 | 27.00007 | 28.58232 | 0.22964 | 6.36997 |
July | 497.00000 | 27.00004 | 28.90298 | 0.24354 | 6.48373 |
August | 514.00000 | 27.00009 | 28.61920 | 0.26835 | 6.76246 |
September | 485.00000 | 27.00002 | 24.61039 | 0.12125 | 5.68010 |
October | 502.00000 | 27.00000 | 19.77690 | 0.71110 | 15.94983 |
November | 489.00000 | 27.00000 | 20.26064 | 0.70095 | 15.60198 |
December | 497.00000 | 27.00000 | 14.63751 | 0.61628 | 13.31720 |
Annual Sum or Average | 5943.00000 | 26.99998 | 22.21023 | 0.47276 | 11.27486 |
Minimum of Months | 454.00000 | 26.99952 | 14.63751 | 0.09564 | 5.53071 |
Maximum of Months | 514.00000 | 27.00009 | 28.90298 | 0.73755 | 16.79319 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.85556 | 19.88892 | 0.52659 | 11.82866 |
February | 454.00000 | 27.00000 | 17.14835 | 0.55920 | 12.15459 |
March | 514.00000 | 27.00000 | 17.79474 | 0.63039 | 13.91050 |
April | 485.00000 | 27.00000 | 21.05371 | 0.67608 | 15.31964 |
May | 508.00000 | 26.99973 | 24.98101 | 0.05227 | 5.78906 |
June | 496.00000 | 27.00008 | 28.60818 | 0.23820 | 6.70852 |
July | 497.00000 | 27.00005 | 28.91721 | 0.25022 | 6.76878 |
August | 514.00000 | 27.00007 | 28.76707 | 0.26975 | 7.02372 |
September | 485.00000 | 27.00006 | 24.63677 | 0.09154 | 5.90690 |
October | 502.00000 | 27.00012 | 19.78309 | 0.63733 | 14.12415 |
November | 489.00000 | 27.00000 | 20.26375 | 0.61094 | 13.31762 |
December | 497.00000 | 27.00000 | 14.64065 | 0.52656 | 11.32754 |
Annual Sum or Average | 5943.00000 | 26.98781 | 22.24981 | 0.42111 | 10.32745 |
Minimum of Months | 454.00000 | 26.85556 | 14.64065 | 0.05227 | 5.78906 |
Maximum of Months | 514.00000 | 27.00012 | 28.91721 | 0.67608 | 15.31964 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.19095 | 29.49005 | 1.03509 | 27.65668 |
February | 454.00000 | 24.46255 | 27.67823 | 0.61332 | 12.98566 |
March | 514.00000 | 25.58788 | 22.84318 | 0.90056 | 22.55594 |
April | 485.00000 | 24.90177 | 24.51814 | 0.94988 | 24.85500 |
May | 508.00000 | 27.21022 | 29.09047 | 0.46040 | 9.50154 |
June | 496.00000 | 26.33991 | 33.69240 | 0.49088 | 11.66785 |
July | 497.00000 | 26.79051 | 34.95765 | 0.84561 | 21.32571 |
August | 514.00000 | 27.28628 | 32.73493 | 1.18943 | 36.07235 |
September | 485.00000 | 27.18238 | 28.75484 | 0.59152 | 12.41528 |
October | 502.00000 | 24.51836 | 26.86115 | 0.71297 | 16.07644 |
November | 489.00000 | 25.58411 | 25.54528 | 1.01339 | 27.09574 |
December | 497.00000 | 24.66586 | 21.67395 | 0.91016 | 22.89923 |
Annual Sum or Average | 5943.00000 | 25.99260 | 28.16519 | 0.81160 | 20.51223 |
Minimum of Months | 454.00000 | 24.46255 | 21.67395 | 0.46040 | 9.50154 |
Maximum of Months | 514.00000 | 27.28628 | 34.95765 | 1.18943 | 36.07235 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.98962 | 19.86285 | 0.21986 | 6.86112 |
February | 454.00000 | 24.04375 | 17.18969 | 0.20273 | 6.22786 |
March | 514.00000 | 24.08349 | 16.96324 | 0.21896 | 6.19901 |
April | 485.00000 | 24.12909 | 20.76750 | 0.25806 | 6.65056 |
May | 508.00000 | 24.18949 | 25.21614 | -0.5758 | 12.68650 |
June | 496.00000 | 24.39750 | 33.35354 | -0.4237 | 9.46772 |
July | 497.00000 | 24.55063 | 34.85265 | -0.3646 | 8.65892 |
August | 514.00000 | 24.45300 | 33.82500 | -0.3767 | 8.91299 |
September | 485.00000 | 24.48199 | 24.72490 | -0.4343 | 10.22335 |
October | 502.00000 | 24.42476 | 18.80116 | 0.34057 | 8.10119 |
November | 489.00000 | 24.39806 | 19.36082 | 0.33518 | 7.98175 |
December | 497.00000 | 24.06568 | 13.33913 | 0.20658 | 6.46919 |
Annual Sum or Average | 5943.00000 | 24.26828 | 23.24656 | -0.0354 | 8.22016 |
Minimum of Months | 454.00000 | 23.98962 | 13.33913 | -0.5758 | 6.19901 |
Maximum of Months | 514.00000 | 24.55063 | 34.85265 | 0.34057 | 12.68650 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.94798 | 18.93680 | 0.20510 | 6.17359 |
February | 454.00000 | 23.88331 | 17.31883 | 0.17550 | 6.03374 |
March | 514.00000 | 24.00855 | 16.82750 | 0.22102 | 6.26678 |
April | 485.00000 | 24.19560 | 21.01582 | 0.29474 | 7.07297 |
May | 508.00000 | 24.20955 | 25.57612 | -0.5319 | 11.39375 |
June | 496.00000 | 24.21330 | 35.30909 | -0.4207 | 9.11740 |
July | 497.00000 | 24.25446 | 37.78174 | -0.3798 | 8.44801 |
August | 514.00000 | 24.23679 | 36.29490 | -0.3819 | 8.44413 |
September | 485.00000 | 24.26354 | 25.92682 | -0.4818 | 10.42183 |
October | 502.00000 | 24.20135 | 19.28569 | 0.28880 | 6.99793 |
November | 489.00000 | 24.20877 | 19.68412 | 0.29041 | 7.00357 |
December | 497.00000 | 24.04813 | 13.94551 | 0.20025 | 6.16296 |
Annual Sum or Average | 5943.00000 | 24.14059 | 24.05561 | -0.0458 | 7.80657 |
Minimum of Months | 454.00000 | 23.88331 | 13.94551 | -0.5319 | 6.03374 |
Maximum of Months | 514.00000 | 24.26354 | 37.78174 | 0.29474 | 11.39375 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.07314 | 20.19272 | -0.0257 | 6.63202 |
February | 454.00000 | 23.07025 | 18.24083 | -0.0382 | 6.50069 |
March | 514.00000 | 23.37912 | 17.94968 | 0.04680 | 6.10206 |
April | 485.00000 | 23.56529 | 22.36951 | 0.11838 | 5.96141 |
May | 508.00000 | 24.01823 | 26.12236 | -0.6203 | 13.63790 |
June | 496.00000 | 24.09543 | 35.53612 | -0.4900 | 10.46736 |
July | 497.00000 | 24.11674 | 38.05884 | -0.4662 | 10.00382 |
August | 514.00000 | 24.14851 | 36.15692 | -0.4685 | 9.95372 |
September | 485.00000 | 24.05817 | 26.42227 | -0.5840 | 12.77422 |
October | 502.00000 | 23.71034 | 20.35204 | 0.14871 | 6.01178 |
November | 489.00000 | 23.51605 | 21.43640 | 0.09669 | 5.77596 |
December | 497.00000 | 22.85059 | 15.35875 | -0.1140 | 7.07492 |
Annual Sum or Average | 5943.00000 | 23.63797 | 24.90941 | -0.2015 | 8.42511 |
Minimum of Months | 454.00000 | 22.85059 | 15.35875 | -0.6203 | 5.77596 |
Maximum of Months | 514.00000 | 24.14851 | 38.05884 | 0.14871 | 13.63790 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.25004 | 22.32640 | -0.4902 | 13.77829 |
February | 454.00000 | 21.47681 | 19.89736 | -0.4496 | 12.60849 |
March | 514.00000 | 22.10965 | 19.36937 | -0.2760 | 9.93147 |
April | 485.00000 | 22.15541 | 23.87747 | -0.2273 | 10.37217 |
May | 508.00000 | 23.33258 | 27.18964 | -0.8543 | 22.70746 |
June | 496.00000 | 23.92710 | 36.06082 | -0.5168 | 11.45515 |
July | 497.00000 | 23.98850 | 38.51881 | -0.4838 | 10.64930 |
August | 514.00000 | 23.97239 | 36.71288 | -0.5063 | 11.11071 |
September | 485.00000 | 23.56122 | 27.23718 | -0.7496 | 18.94085 |
October | 502.00000 | 22.19768 | 22.38728 | -0.2326 | 8.69221 |
November | 489.00000 | 21.67635 | 23.73824 | -0.3710 | 10.28293 |
December | 497.00000 | 21.04048 | 16.80518 | -0.5815 | 15.58474 |
Annual Sum or Average | 5943.00000 | 22.56771 | 26.23239 | -0.4786 | 13.01039 |
Minimum of Months | 454.00000 | 21.04048 | 16.80518 | -0.8543 | 8.69221 |
Maximum of Months | 514.00000 | 23.98850 | 38.51881 | -0.2273 | 22.70746 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.45719 | 20.64689 | -0.4189 | 10.10935 |
February | 454.00000 | 21.36839 | 18.61420 | -0.4543 | 11.14289 |
March | 514.00000 | 22.13806 | 17.93641 | -0.2460 | 8.47502 |
April | 485.00000 | 22.53804 | 21.99417 | -0.1092 | 7.30750 |
May | 508.00000 | 23.60487 | 25.80774 | -0.7234 | 17.94141 |
June | 496.00000 | 24.17726 | 34.58491 | -0.3739 | 8.49050 |
July | 497.00000 | 24.26625 | 37.12389 | -0.3210 | 7.95077 |
August | 514.00000 | 24.08710 | 36.01981 | -0.4033 | 9.11176 |
September | 485.00000 | 23.77768 | 26.02183 | -0.6358 | 15.67343 |
October | 502.00000 | 22.46537 | 20.69955 | -0.1446 | 7.18463 |
November | 489.00000 | 21.98253 | 21.61429 | -0.2694 | 7.80273 |
December | 497.00000 | 21.40040 | 14.96226 | -0.4721 | 11.66672 |
Annual Sum or Average | 5943.00000 | 22.78348 | 24.72635 | -0.3808 | 10.23334 |
Minimum of Months | 454.00000 | 21.36839 | 14.96226 | -0.7234 | 7.18463 |
Maximum of Months | 514.00000 | 24.26625 | 37.12389 | -0.1092 | 17.94141 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.56720 | 20.03868 | -0.3507 | 9.63266 |
February | 454.00000 | 21.62330 | 17.88011 | -0.3426 | 10.85839 |
March | 514.00000 | 22.09677 | 17.45664 | -0.1866 | 9.45055 |
April | 485.00000 | 22.29726 | 21.92267 | -0.0977 | 8.52949 |
May | 508.00000 | 23.35080 | 25.82338 | -0.6912 | 18.75080 |
June | 496.00000 | 23.94721 | 34.89116 | -0.3086 | 9.27456 |
July | 497.00000 | 24.02681 | 37.62967 | -0.2758 | 9.68627 |
August | 514.00000 | 23.74945 | 36.53297 | -0.3715 | 11.18092 |
September | 485.00000 | 23.55151 | 26.07412 | -0.5763 | 16.31191 |
October | 502.00000 | 22.34522 | 20.25089 | -0.1102 | 8.55053 |
November | 489.00000 | 21.85179 | 21.22797 | -0.2543 | 8.51585 |
December | 497.00000 | 21.33753 | 14.51072 | -0.4551 | 11.66862 |
Annual Sum or Average | 5943.00000 | 22.65426 | 24.58196 | -0.3353 | 11.04048 |
Minimum of Months | 454.00000 | 21.33753 | 14.51072 | -0.6912 | 8.51585 |
Maximum of Months | 514.00000 | 24.02681 | 37.62967 | -0.0977 | 18.75080 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.64217 | 18.84219 | -0.0335 | 10.93937 |
February | 454.00000 | 22.41617 | 17.14409 | -0.1043 | 12.07075 |
March | 514.00000 | 22.46322 | 17.17470 | -0.0880 | 10.52291 |
April | 485.00000 | 22.27871 | 22.02709 | -0.1232 | 9.39241 |
May | 508.00000 | 23.24538 | 26.14777 | -0.7901 | 21.70042 |
June | 496.00000 | 23.88666 | 35.13861 | -0.4310 | 10.79557 |
July | 497.00000 | 24.03304 | 37.57162 | -0.3520 | 9.75974 |
August | 514.00000 | 23.95670 | 36.17926 | -0.3468 | 10.02147 |
September | 485.00000 | 23.83907 | 25.65330 | -0.4750 | 14.95025 |
October | 502.00000 | 22.87318 | 19.69015 | 0.05073 | 10.86203 |
November | 489.00000 | 22.90354 | 19.95582 | 0.05425 | 10.78922 |
December | 497.00000 | 22.41177 | 13.72081 | -0.1406 | 11.99781 |
Annual Sum or Average | 5943.00000 | 23.08463 | 24.16930 | -0.2332 | 11.99029 |
Minimum of Months | 454.00000 | 22.27871 | 13.72081 | -0.7901 | 9.39241 |
Maximum of Months | 514.00000 | 24.03304 | 37.57162 | 0.05425 | 21.70042 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.79045 | 19.59653 | -0.2525 | 8.70852 |
February | 454.00000 | 21.77459 | 17.61088 | -0.2624 | 9.56827 |
March | 514.00000 | 22.35952 | 17.07381 | -0.0719 | 8.33919 |
April | 485.00000 | 22.86219 | 21.05177 | 0.08613 | 7.68220 |
May | 508.00000 | 23.32711 | 25.79479 | -0.6539 | 18.22345 |
June | 496.00000 | 23.99983 | 34.82864 | -0.2453 | 9.65867 |
July | 497.00000 | 24.18402 | 37.16306 | -0.1657 | 7.99575 |
August | 514.00000 | 24.17984 | 35.57544 | -0.1484 | 7.77816 |
September | 485.00000 | 23.56913 | 26.01843 | -0.5301 | 15.82718 |
October | 502.00000 | 22.45413 | 20.04875 | -0.0355 | 8.14663 |
November | 489.00000 | 22.36760 | 20.46808 | -0.0726 | 7.59821 |
December | 497.00000 | 21.99802 | 13.83598 | -0.2299 | 8.80982 |
Annual Sum or Average | 5943.00000 | 22.91455 | 24.14979 | -0.2151 | 9.86165 |
Minimum of Months | 454.00000 | 21.77459 | 13.83598 | -0.6539 | 7.59821 |
Maximum of Months | 514.00000 | 24.18402 | 37.16306 | 0.08613 | 18.22345 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.37960 | 21.60980 | -0.7241 | 18.30231 |
February | 454.00000 | 20.42768 | 19.28438 | -0.7284 | 18.16260 |
March | 514.00000 | 21.01053 | 18.89415 | -0.5438 | 13.69821 |
April | 485.00000 | 21.22539 | 23.61389 | -0.4397 | 12.48222 |
May | 508.00000 | 22.81901 | 26.99865 | -0.9855 | 28.29641 |
June | 496.00000 | 23.80838 | 35.16446 | -0.5075 | 11.48749 |
July | 497.00000 | 23.86631 | 37.85532 | -0.4727 | 10.98876 |
August | 514.00000 | 23.61612 | 36.88720 | -0.5890 | 13.87263 |
September | 485.00000 | 23.02017 | 27.10367 | -0.8943 | 25.07471 |
October | 502.00000 | 21.23457 | 21.98371 | -0.4540 | 11.26525 |
November | 489.00000 | 20.74754 | 23.12473 | -0.6035 | 13.94557 |
December | 497.00000 | 20.21174 | 15.68176 | -0.8213 | 21.56275 |
Annual Sum or Average | 5943.00000 | 21.87700 | 25.74146 | -0.6465 | 16.58171 |
Minimum of Months | 454.00000 | 20.21174 | 15.68176 | -0.9855 | 10.98876 |
Maximum of Months | 514.00000 | 23.86631 | 37.85532 | -0.4397 | 28.29641 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.76422 | 20.81915 | -0.5944 | 15.06066 |
February | 385.00000 | 20.90616 | 18.43824 | -0.5606 | 15.99869 |
March | 433.00000 | 21.51299 | 17.95200 | -0.3672 | 12.74199 |
April | 410.00000 | 21.51480 | 23.03620 | -0.3132 | 12.64571 |
May | 430.00000 | 22.99071 | 26.56627 | -0.8318 | 24.37912 |
June | 418.00000 | 23.85063 | 34.77610 | -0.3601 | 10.91432 |
July | 422.00000 | 23.97336 | 37.37495 | -0.3178 | 11.53775 |
August | 433.00000 | 23.67384 | 36.47737 | -0.4332 | 13.30216 |
September | 410.00000 | 23.22554 | 26.44341 | -0.7148 | 21.35296 |
October | 427.00000 | 21.75019 | 20.91970 | -0.2916 | 11.13732 |
November | 417.00000 | 21.13545 | 22.22375 | -0.4743 | 12.17276 |
December | 422.00000 | 20.40917 | 15.12921 | -0.7385 | 19.56911 |
Annual Sum or Average | 5034.00000 | 22.15146 | 25.06153 | -0.4994 | 15.05978 |
Minimum of Months | 385.00000 | 20.40917 | 15.12921 | -0.8318 | 10.91432 |
Maximum of Months | 433.00000 | 23.97336 | 37.37495 | -0.2916 | 24.37912 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.46820 | 19.00972 | -0.0813 | 12.79520 |
February | 454.00000 | 22.22586 | 17.28159 | -0.1553 | 14.29960 |
March | 514.00000 | 22.21599 | 17.56664 | -0.1616 | 12.44389 |
April | 485.00000 | 21.80417 | 22.75145 | -0.2521 | 12.22833 |
May | 508.00000 | 23.04340 | 26.54963 | -0.8689 | 25.15643 |
June | 496.00000 | 23.73308 | 35.25678 | -0.4982 | 12.63598 |
July | 497.00000 | 23.88159 | 37.71597 | -0.4256 | 11.56540 |
August | 514.00000 | 23.82723 | 36.23401 | -0.4174 | 11.99140 |
September | 485.00000 | 23.69536 | 25.82715 | -0.5264 | 17.25418 |
October | 502.00000 | 22.66618 | 20.01305 | -0.0025 | 12.54825 |
November | 489.00000 | 22.72411 | 20.39146 | 0.00314 | 12.46259 |
December | 497.00000 | 22.02616 | 14.00411 | -0.2525 | 14.78706 |
Annual Sum or Average | 5943.00000 | 22.86512 | 24.44898 | -0.3049 | 14.18669 |
Minimum of Months | 454.00000 | 21.80417 | 14.00411 | -0.8689 | 11.56540 |
Maximum of Months | 514.00000 | 23.88159 | 37.71597 | 0.00314 | 25.15643 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.94462 | 20.56821 | -0.5287 | 14.25123 |
February | 454.00000 | 21.01663 | 18.37211 | -0.5181 | 14.86136 |
March | 514.00000 | 21.40927 | 18.17483 | -0.3740 | 12.48128 |
April | 485.00000 | 21.46140 | 23.03489 | -0.3158 | 11.84638 |
May | 508.00000 | 22.70614 | 26.83514 | -0.9125 | 27.78767 |
June | 496.00000 | 23.51806 | 35.70978 | -0.4582 | 14.44631 |
July | 497.00000 | 23.51862 | 38.56233 | -0.4676 | 13.55927 |
August | 514.00000 | 23.40937 | 37.15653 | -0.5133 | 14.98846 |
September | 485.00000 | 22.90865 | 27.03416 | -0.8026 | 24.82443 |
October | 502.00000 | 21.60904 | 21.16735 | -0.2944 | 11.04264 |
November | 489.00000 | 21.26795 | 22.07999 | -0.4194 | 11.41523 |
December | 497.00000 | 20.65147 | 14.96320 | -0.6578 | 17.56488 |
Annual Sum or Average | 5943.00000 | 22.04476 | 25.36759 | -0.5220 | 15.76336 |
Minimum of Months | 454.00000 | 20.65147 | 14.96320 | -0.9125 | 11.04264 |
Maximum of Months | 514.00000 | 23.51862 | 38.56233 | -0.2944 | 27.78767 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.97783 | 22.34580 | -0.8823 | 24.42906 |
February | 454.00000 | 20.09764 | 19.74868 | -0.8652 | 23.36872 |
March | 514.00000 | 20.63036 | 19.14698 | -0.6762 | 17.58014 |
April | 485.00000 | 20.67088 | 24.50296 | -0.6024 | 17.38387 |
May | 508.00000 | 22.16020 | 27.93039 | -1.2028 | 38.24184 |
June | 496.00000 | 23.40526 | 36.21728 | -0.6027 | 15.31937 |
July | 497.00000 | 23.45983 | 38.99701 | -0.5699 | 14.71849 |
August | 514.00000 | 23.15918 | 38.10142 | -0.7048 | 18.63473 |
September | 485.00000 | 22.42682 | 27.99397 | -1.0806 | 33.32480 |
October | 502.00000 | 20.65231 | 22.65110 | -0.6371 | 16.53407 |
November | 489.00000 | 20.17319 | 23.97029 | -0.7967 | 21.14364 |
December | 497.00000 | 19.90774 | 16.07353 | -0.9642 | 27.31198 |
Annual Sum or Average | 5943.00000 | 21.40596 | 26.53289 | -0.7982 | 22.31780 |
Minimum of Months | 454.00000 | 19.90774 | 16.07353 | -1.2028 | 14.71849 |
Maximum of Months | 514.00000 | 23.45983 | 38.99701 | -0.5699 | 38.24184 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.28718 | 21.85856 | -0.7503 | 20.34051 |
February | 454.00000 | 20.59467 | 19.12069 | -0.6773 | 19.19496 |
March | 514.00000 | 21.36003 | 18.40190 | -0.4376 | 14.75702 |
April | 485.00000 | 21.26183 | 23.68226 | -0.3999 | 16.14400 |
May | 508.00000 | 22.80792 | 26.76410 | -0.8997 | 27.43899 |
June | 496.00000 | 23.82999 | 35.12268 | -0.3289 | 10.64940 |
July | 497.00000 | 23.91510 | 37.94445 | -0.2990 | 11.50764 |
August | 514.00000 | 23.65848 | 36.72256 | -0.3994 | 13.08466 |
September | 485.00000 | 23.13247 | 26.71021 | -0.7387 | 22.59780 |
October | 502.00000 | 21.45181 | 21.53437 | -0.4037 | 13.81694 |
November | 489.00000 | 20.65189 | 23.21155 | -0.6363 | 16.89755 |
December | 497.00000 | 20.08527 | 15.82026 | -0.8688 | 24.18848 |
Annual Sum or Average | 5943.00000 | 21.93282 | 25.63131 | -0.5689 | 17.53103 |
Minimum of Months | 454.00000 | 20.08527 | 15.82026 | -0.8997 | 10.64940 |
Maximum of Months | 514.00000 | 23.91510 | 37.94445 | -0.2990 | 27.43899 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.76331 | 20.07714 | -0.2973 | 15.85595 |
February | 454.00000 | 21.70154 | 18.00697 | -0.3285 | 17.14133 |
March | 514.00000 | 21.77303 | 18.03307 | -0.3053 | 14.95192 |
April | 485.00000 | 21.28753 | 23.70901 | -0.4070 | 16.78396 |
May | 508.00000 | 22.54182 | 27.32571 | -1.0434 | 33.04263 |
June | 496.00000 | 23.40897 | 36.16219 | -0.5723 | 16.09427 |
July | 497.00000 | 23.53686 | 38.73082 | -0.5063 | 15.01708 |
August | 514.00000 | 23.48497 | 37.27086 | -0.5030 | 15.66989 |
September | 485.00000 | 23.27867 | 26.54208 | -0.6650 | 22.73143 |
October | 502.00000 | 22.10316 | 20.79927 | -0.1803 | 15.50148 |
November | 489.00000 | 22.07687 | 21.34054 | -0.2037 | 14.86105 |
December | 497.00000 | 21.34896 | 14.76037 | -0.4639 | 19.09761 |
Annual Sum or Average | 5943.00000 | 22.36524 | 25.29559 | -0.4577 | 18.07482 |
Minimum of Months | 454.00000 | 21.28753 | 14.76037 | -1.0434 | 14.86105 |
Maximum of Months | 514.00000 | 23.53686 | 38.73082 | -0.1803 | 33.04263 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.56538 | 21.37572 | -0.6684 | 18.87893 |
February | 454.00000 | 20.74404 | 18.88970 | -0.6300 | 18.55240 |
March | 514.00000 | 21.19915 | 18.44821 | -0.4626 | 15.01004 |
April | 485.00000 | 21.10592 | 23.78253 | -0.4287 | 15.71707 |
May | 508.00000 | 22.43885 | 27.29503 | -1.0153 | 32.93163 |
June | 496.00000 | 23.35059 | 36.28021 | -0.4887 | 16.63069 |
July | 497.00000 | 23.33853 | 39.21223 | -0.5031 | 15.85100 |
August | 514.00000 | 23.22129 | 37.84444 | -0.5552 | 17.41903 |
September | 485.00000 | 22.67261 | 27.47552 | -0.8861 | 28.99436 |
October | 502.00000 | 21.28019 | 21.69622 | -0.4151 | 14.52348 |
November | 489.00000 | 20.85610 | 22.81812 | -0.5659 | 15.95172 |
December | 497.00000 | 20.31955 | 15.52597 | -0.7895 | 22.41947 |
Annual Sum or Average | 5943.00000 | 21.76788 | 25.94926 | -0.6172 | 19.40826 |
Minimum of Months | 454.00000 | 20.31955 | 15.52597 | -1.0153 | 14.52348 |
Maximum of Months | 514.00000 | 23.35059 | 39.21223 | -0.4151 | 32.93163 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.122611E+11 | 151523.45 | 25-JAN-14:50 | 131.58 | 0.658722E+11 | 0.00 | 0.781333E+11 | 0.83 | 6.93 | 25-JAN-14:50 | 0.00 | 0.00 |
February | 0.433943E+11 | 157842.73 | 23-FEB-14:29 | 236.05 | 0.204635E+12 | 0.00 | 0.248030E+12 | 1.63 | 6.96 | 23-FEB-14:29 | 0.00 | 0.00 |
March | 0.711770E+11 | 223716.92 | 14-MAR-12:30 | 718.31 | 0.367989E+12 | 0.00 | 0.439166E+12 | 4.68 | 7.01 | 13-MAR-13:00 | 0.00 | 0.00 |
April | 0.674893E+11 | 172657.35 | 19-APR-13:50 | 633.59 | 0.347151E+12 | 0.00 | 0.414640E+12 | 4.28 | 7.00 | 19-APR-13:50 | 0.00 | 0.00 |
May | 0.819681E+11 | 211432.59 | 15-MAY-14:00 | 293.30 | 0.480693E+12 | 0.00 | 0.562661E+12 | 2.09 | 7.17 | 15-MAY-15:20 | 0.00 | 0.00 |
June | 0.220195E+12 | 226825.94 | 22-JUN-14:40 | 543.06 | 0.139563E+13 | 0.00 | 0.161583E+13 | 4.50 | 7.16 | 19-JUN-10:00 | 0.00 | 0.00 |
July | 0.239616E+12 | 231074.91 | 22-JUL-13:50 | 691.31 | 0.152667E+13 | 0.00 | 0.176629E+13 | 5.38 | 7.16 | 14-JUL-18:10 | 0.00 | 0.00 |
August | 0.233518E+12 | 229913.79 | 28-AUG-12:00 | 696.26 | 0.148933E+13 | 0.00 | 0.172285E+13 | 5.38 | 7.13 | 04-AUG-05:03 | 0.00 | 0.00 |
September | 0.148408E+12 | 223639.97 | 01-SEP-12:05 | 400.60 | 0.926825E+12 | 0.00 | 0.107523E+13 | 3.22 | 7.20 | 18-SEP-10:20 | 0.00 | 0.00 |
October | 0.802500E+11 | 221655.34 | 10-OCT-12:20 | 304.66 | 0.429049E+12 | 0.00 | 0.509299E+12 | 2.05 | 7.09 | 09-OCT-14:32 | 0.00 | 0.00 |
November | 0.645015E+11 | 194685.82 | 05-NOV-14:13 | 687.29 | 0.330401E+12 | 0.00 | 0.394902E+12 | 4.62 | 7.10 | 05-NOV-14:53 | 0.00 | 0.00 |
December | 0.608063E+11 | 176480.62 | 01-DEC-14:00 | 693.26 | 0.302842E+12 | 0.00 | 0.363648E+12 | 4.49 | 7.01 | 01-DEC-14:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132358E+13 | 6029.27 | 0.786709E+13 | 0.00 | 0.919067E+13 | 3.60 | 0.00 | 0.00 | ||||
Minimum of Months | 0.122611E+11 | 151523.45 | 131.58 | 0.658722E+11 | 0.00 | 0.781333E+11 | 0.83 | 6.93 | 0.00 | 0.00 | ||
Maximum of Months | 0.239616E+12 | 231074.91 | 718.31 | 0.152667E+13 | 0.00 | 0.176629E+13 | 5.38 | 7.20 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.822818E+09 | 143453.32 | 14-MAR-13:25 | 1.75 | 0.528971E+10 | 0.00 | 0.611253E+10 | 0.02 | 6.77 | 14-MAR-13:25 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 |
May | 0.499076E+10 | 152305.92 | 18-MAY-13:05 | 11.33 | 0.322367E+11 | 0.00 | 0.372275E+11 | 0.10 | 6.88 | 16-MAY-12:05 | 0.00 | 0.00 |
June | 0.658628E+11 | 162992.92 | 26-JUN-14:30 | 137.08 | 0.437312E+12 | 0.00 | 0.503175E+12 | 1.26 | 6.97 | 26-JUN-14:30 | 0.00 | 0.00 |
July | 0.720539E+11 | 204335.24 | 31-JUL-15:51 | 146.01 | 0.481211E+12 | 0.00 | 0.553265E+12 | 1.31 | 6.99 | 18-JUL-15:00 | 0.00 | 0.00 |
August | 0.853800E+11 | 220868.85 | 15-AUG-12:52 | 165.97 | 0.578161E+12 | 0.00 | 0.663541E+12 | 1.51 | 7.01 | 11-AUG-07:52 | 0.00 | 0.00 |
September | 0.276442E+11 | 173949.00 | 13-SEP-12:10 | 59.50 | 0.181018E+12 | 0.00 | 0.208662E+12 | 0.54 | 6.97 | 13-SEP-12:10 | 0.00 | 0.00 |
October | 0.341333E+10 | 184209.69 | 10-OCT-13:02 | 7.32 | 0.222485E+11 | 0.00 | 0.256618E+11 | 0.06 | 6.97 | 10-OCT-13:02 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.260168E+12 | 528.97 | 0.173748E+13 | 0.00 | 0.199764E+13 | 0.40 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.853800E+11 | 220868.85 | 165.97 | 0.578161E+12 | 0.00 | 0.663541E+12 | 1.51 | 7.01 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 38856634.70 | 29.21 | 1874.76 | 20-JAN-13:08 | 1129502.56 | 24-JAN-15:03 | 21.13 | 21.02 | 6.38 |
February | 28588319.22 | 173.27 | 2694.28 | 18-FEB-13:10 | 1148261.44 | 18-FEB-13:10 | 22.02 | 21.68 | 25.22 |
March | 0.201481E+09 | 84.89 | 6209.60 | 14-MAR-12:30 | 1768200.59 | 14-MAR-12:30 | 21.36 | 20.77 | 46.03 |
April | 0.257545E+09 | 91.06 | 4877.54 | 19-APR-13:50 | 1404285.61 | 19-APR-13:50 | 21.38 | 20.82 | 46.51 |
May | 0.211839E+10 | 215.75 | 17855.30 | 31-MAY-13:50 | 1665122.67 | 18-MAY-14:50 | 21.83 | 21.14 | 27.24 |
June | 0.144588E+11 | 522.32 | 24097.32 | 16-JUN-13:00 | 1773322.24 | 22-JUN-14:40 | 23.57 | 21.41 | 58.91 |
July | 0.187028E+11 | 576.01 | 24097.32 | 19-JUL-08:20 | 1783446.26 | 21-JUL-09:20 | 23.39 | 21.15 | 70.38 |
August | 0.152723E+11 | 569.87 | 24097.32 | 02-AUG-17:30 | 1805339.76 | 28-AUG-17:00 | 23.30 | 21.11 | 70.83 |
September | 0.572022E+10 | 350.32 | 24097.32 | 01-SEP-12:00 | 1789271.94 | 01-SEP-12:05 | 22.61 | 21.20 | 41.55 |
October | 0.525922E+09 | 267.25 | 6870.98 | 11-OCT-12:20 | 1742099.74 | 10-OCT-12:20 | 22.35 | 21.73 | 31.37 |
November | 0.152265E+09 | 59.24 | 4661.50 | 07-NOV-15:00 | 1546699.58 | 07-NOV-15:00 | 21.31 | 20.76 | 45.61 |
December | 73983776.48 | 32.22 | 4386.69 | 01-DEC-14:00 | 1431813.46 | 01-DEC-14:00 | 21.22 | 20.73 | 42.14 |
Annual Sum or Average | 0.575511E+11 | 2971.40 | 22.12 | 21.12 | 42.76 | ||||
Minimum of Months | 28588319.22 | 29.21 | 1874.76 | 1129502.56 | 21.13 | 20.73 | 6.38 | ||
Maximum of Months | 0.187028E+11 | 576.01 | 24097.32 | 1805339.76 | 23.57 | 21.73 | 70.83 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.13 | 21.13 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 22.02 | 22.02 | 0.00 |
March | 6049993.28 | 0.42 | 4468.61 | 14-MAR-12:50 | 1460894.85 | 14-MAR-12:50 | 21.36 | 21.35 | 0.04 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 21.38 | 21.38 | 0.00 |
May | 0.293139E+09 | 8.75 | 16911.05 | 31-MAY-14:00 | 1589091.16 | 31-MAY-13:30 | 21.83 | 21.78 | 0.92 |
June | 0.600869E+10 | 126.25 | 24097.32 | 16-JUN-14:30 | 1629858.65 | 28-JUN-15:20 | 23.57 | 22.81 | 13.74 |
July | 0.718765E+10 | 131.47 | 24097.32 | 19-JUL-10:20 | 1630278.20 | 07-JUL-12:50 | 23.39 | 22.65 | 13.85 |
August | 0.686637E+10 | 156.17 | 24097.32 | 03-AUG-13:20 | 1734807.70 | 15-AUG-12:52 | 23.30 | 22.42 | 16.45 |
September | 0.175397E+10 | 53.00 | 16775.10 | 13-SEP-14:30 | 1626219.06 | 12-SEP-15:20 | 22.61 | 22.28 | 5.77 |
October | 0.114084E+09 | 6.26 | 5961.97 | 11-OCT-14:40 | 1538074.58 | 11-OCT-11:05 | 22.35 | 22.32 | 0.66 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 21.31 | 21.31 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 21.22 | 21.22 | 0.00 |
Annual Sum or Average | 0.222300E+11 | 482.32 | 22.12 | 21.89 | 4.31 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 | 21.13 | 0.00 | ||
Maximum of Months | 0.718765E+10 | 156.17 | 24097.32 | 1734807.70 | 23.57 | 22.81 | 16.45 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.268760E+12 | 0.00 | 510.27 | 2888159.97 | 02-JAN-05:01 | 0.00 | 29.01 | 59.93 | 0.57 | 0.00 | 0.03 | 0.91 | 02-JAN-05:01 |
February | 0.275505E+12 | 0.00 | 470.29 | 2758953.67 | 13-FEB-05:01 | 0.00 | 28.86 | 61.17 | 0.64 | 0.00 | 0.04 | 0.87 | 13-FEB-05:01 |
March | 0.188756E+12 | 0.00 | 411.28 | 2745258.37 | 01-MAR-05:01 | 0.00 | 27.16 | 51.66 | 0.41 | 0.00 | 0.02 | 0.87 | 01-MAR-05:01 |
April | 0.123574E+12 | 0.00 | 330.60 | 2593687.04 | 15-APR-04:01 | 0.00 | 26.22 | 46.47 | 0.28 | 0.00 | 0.02 | 0.82 | 15-APR-04:01 |
May | 0.228607E+11 | 0.00 | 145.62 | 2578388.65 | 01-MAY-04:11 | 0.00 | 23.23 | 31.60 | 0.05 | 0.00 | 0.00 | 0.82 | 01-MAY-04:11 |
June | 0.472856E+09 | 0.00 | 37.54 | 43291.31 | 09-JUN-05:08 | 0.00 | 20.84 | 23.17 | 0.00 | 0.00 | 0.00 | 0.01 | 09-JUN-05:08 |
July | 0.246254E+09 | 0.00 | 24.24 | 30320.31 | 29-JUL-05:09 | 0.00 | 20.16 | 21.64 | 0.00 | 0.00 | 0.00 | 0.01 | 29-JUL-05:09 |
August | 0.970949E+09 | 0.00 | 43.81 | 123054.20 | 23-AUG-05:01 | 0.00 | 20.04 | 22.72 | 0.00 | 0.00 | 0.00 | 0.04 | 23-AUG-05:01 |
September | 0.129205E+11 | 0.00 | 97.61 | 2450609.47 | 22-SEP-05:01 | 0.00 | 21.56 | 27.55 | 0.03 | 0.00 | 0.00 | 0.78 | 22-SEP-05:01 |
October | 0.152832E+12 | 0.00 | 336.63 | 2772657.12 | 25-OCT-04:01 | 0.00 | 25.15 | 45.39 | 0.31 | 0.00 | 0.02 | 0.88 | 25-OCT-04:01 |
November | 0.199211E+12 | 0.00 | 410.91 | 2569993.26 | 14-NOV-05:01 | 0.00 | 26.95 | 53.21 | 0.43 | 0.00 | 0.02 | 0.81 | 14-NOV-05:01 |
December | 0.424843E+12 | 0.00 | 538.26 | 2670756.45 | 06-DEC-05:01 | 0.00 | 30.71 | 62.27 | 0.98 | 0.00 | 0.05 | 0.85 | 06-DEC-05:01 |
Annual Sum or Average | 0.167095E+13 | 0.00 | 3357.06 | 0.00 | 24.97 | 42.12 | 0.31 | 0.00 | 0.02 | ||||
Minimum of Months | 0.246254E+09 | 0.00 | 24.24 | 30320.31 | 0.00 | 20.04 | 21.64 | 0.00 | 0.00 | 0.00 | 0.01 | ||
Maximum of Months | 0.424843E+12 | 0.00 | 538.26 | 2888159.97 | 0.00 | 30.71 | 62.27 | 0.98 | 0.00 | 0.05 | 0.91 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.400442E+10 | 0.00 | 35.20 | 0.400442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76782.80 | 20-JAN-14:00 | 76782.80 | 20-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.130829E+10 | 0.00 | 21.10 | 0.130829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51891.35 | 26-FEB-15:51 | 51891.35 | 26-FEB-15:51 | 0.00 | 0.00 | 0.00 |
March | 0.110260E+11 | 0.00 | 89.31 | 0.110260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115077.71 | 14-MAR-13:00 | 115077.71 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.118068E+11 | 0.00 | 100.20 | 0.118068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92839.77 | 19-APR-13:30 | 92839.77 | 19-APR-13:30 | 0.00 | 0.00 | 0.00 |
May | 0.410908E+11 | 0.00 | 249.45 | 0.410908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125024.98 | 31-MAY-15:20 | 125024.98 | 31-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.126629E+12 | 0.00 | 452.90 | 0.126247E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 173096.05 | 26-JUN-14:40 | 173096.05 | 26-JUN-14:40 | 0.00 | 0.00 | 0.00 |
July | 0.136349E+12 | 0.00 | 479.44 | 0.132753E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 164026.20 | 17-JUL-13:40 | 164026.20 | 17-JUL-13:40 | 0.00 | 0.00 | 0.00 |
August | 0.138471E+12 | 0.00 | 500.30 | 0.137596E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 174232.25 | 16-AUG-14:50 | 174232.25 | 16-AUG-14:50 | 0.00 | 0.00 | 0.00 |
September | 0.888651E+11 | 0.00 | 371.32 | 0.888651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149612.31 | 12-SEP-15:50 | 149612.31 | 12-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.186088E+11 | 0.00 | 125.35 | 0.186088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135888.84 | 10-OCT-15:30 | 135888.84 | 10-OCT-15:30 | 0.00 | 0.00 | 0.00 |
November | 0.746031E+10 | 0.00 | 54.80 | 0.746031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99110.11 | 07-NOV-14:30 | 99110.11 | 07-NOV-14:30 | 0.00 | 0.00 | 0.00 |
December | 0.449252E+10 | 0.00 | 38.28 | 0.449252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89098.95 | 01-DEC-13:55 | 89098.95 | 01-DEC-13:55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.590112E+12 | 0.00 | 2517.64 | 0.585260E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.130829E+10 | 0.00 | 21.10 | 0.130829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51891.35 | 51891.35 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.138471E+12 | 0.00 | 500.30 | 0.137596E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 174232.25 | 174232.25 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.454386E+11 | 0.00 | 132.61 | 0.454386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 797044.62 | 24-JAN-15:03 | 797044.62 | 24-JAN-15:03 | 0.00 | 0.00 | 0.00 |
February | 0.308652E+11 | 0.00 | 116.82 | 0.308652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 766243.65 | 17-FEB-15:01 | 766243.65 | 17-FEB-15:01 | 0.00 | 0.00 | 0.00 |
March | 0.105745E+12 | 0.00 | 181.87 | 0.105745E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1015059.33 | 14-MAR-13:00 | 1015059.33 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.984448E+11 | 0.00 | 167.54 | 0.984448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 733084.87 | 20-APR-13:00 | 733084.87 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.377351E+12 | 0.00 | 260.62 | 0.377351E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1186539.56 | 16-MAY-14:05 | 1186539.56 | 16-MAY-14:05 | 0.00 | 0.00 | 0.00 |
June | 0.114350E+13 | 0.00 | 446.92 | 0.114006E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1597773.80 | 26-JUN-14:20 | 1597773.80 | 26-JUN-14:20 | 0.00 | 0.00 | 0.00 |
July | 0.115971E+13 | 0.00 | 448.44 | 0.113087E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1524303.49 | 18-JUL-15:00 | 1524303.49 | 18-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.112500E+13 | 0.00 | 444.64 | 0.111937E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1594578.95 | 16-AUG-15:20 | 1594578.95 | 16-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.793099E+12 | 0.00 | 377.56 | 0.793099E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1422396.57 | 12-SEP-16:00 | 1422396.57 | 12-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.183162E+12 | 0.00 | 173.30 | 0.183162E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1199011.95 | 11-OCT-15:00 | 1199011.95 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.783584E+11 | 0.00 | 135.05 | 0.783584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 857770.75 | 07-NOV-15:02 | 857770.75 | 07-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.436046E+11 | 0.00 | 115.46 | 0.436046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 744382.55 | 01-DEC-13:55 | 744382.55 | 01-DEC-13:55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.518428E+13 | 0.00 | 3000.84 | 0.514637E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.308652E+11 | 0.00 | 115.46 | 0.308652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 733084.87 | 733084.87 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.115971E+13 | 0.00 | 448.44 | 0.114006E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1597773.80 | 1597773.80 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.279982E+10 | 0.00 | 32.91 | 0.279982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71931.06 | 20-JAN-13:20 | 71931.06 | 20-JAN-13:20 | 0.00 | 0.00 | 0.00 |
February | 0.105001E+10 | 0.00 | 17.20 | 0.105001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49285.74 | 26-FEB-12:42 | 49285.74 | 26-FEB-12:42 | 0.00 | 0.00 | 0.00 |
March | 0.902552E+10 | 0.00 | 85.50 | 0.902552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119848.17 | 14-MAR-13:00 | 119848.17 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.954250E+10 | 0.00 | 97.71 | 0.954250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79926.17 | 19-APR-13:40 | 79926.17 | 19-APR-13:40 | 0.00 | 0.00 | 0.00 |
May | 0.410394E+11 | 0.00 | 237.56 | 0.410394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 157221.66 | 31-MAY-15:20 | 157221.66 | 31-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.137473E+12 | 0.00 | 436.82 | 0.137188E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 215069.20 | 26-JUN-15:20 | 215069.20 | 26-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.136129E+12 | 0.00 | 439.73 | 0.133465E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 192028.86 | 17-JUL-13:50 | 192028.86 | 17-JUL-13:50 | 0.00 | 0.00 | 0.00 |
August | 0.132010E+12 | 0.00 | 433.93 | 0.131616E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 209531.53 | 16-AUG-14:30 | 209531.53 | 16-AUG-14:30 | 0.00 | 0.00 | 0.00 |
September | 0.867169E+11 | 0.00 | 358.24 | 0.867169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 169852.99 | 12-SEP-14:05 | 169852.99 | 12-SEP-14:05 | 0.00 | 0.00 | 0.00 |
October | 0.157543E+11 | 0.00 | 120.65 | 0.157543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143730.87 | 11-OCT-15:00 | 143730.87 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.503686E+10 | 0.00 | 49.63 | 0.503686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77614.74 | 07-NOV-14:40 | 77614.74 | 07-NOV-14:40 | 0.00 | 0.00 | 0.00 |
December | 0.317106E+10 | 0.00 | 38.20 | 0.317106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68460.24 | 01-DEC-14:00 | 68460.24 | 01-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.579748E+12 | 0.00 | 2348.08 | 0.576406E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.105001E+10 | 0.00 | 17.20 | 0.105001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49285.74 | 49285.74 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.137473E+12 | 0.00 | 439.73 | 0.137188E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 215069.20 | 215069.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.894344E+10 | 0.00 | 94.23 | 0.889014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 100665.88 | 04-JAN-05:17 | 100665.88 | 04-JAN-05:17 | 0.00 | 0.00 | 0.00 |
February | 0.417485E+10 | 0.00 | 55.90 | 0.417485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 121228.42 | 21-FEB-04:55 | 121228.42 | 21-FEB-04:55 | 0.00 | 0.00 | 0.00 |
March | 0.944969E+10 | 0.00 | 129.53 | 0.944969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109241.69 | 01-MAR-05:46 | 109241.69 | 01-MAR-05:46 | 0.00 | 0.00 | 0.00 |
April | 0.114192E+11 | 0.00 | 168.57 | 0.114192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97287.68 | 24-APR-04:59 | 97287.68 | 24-APR-04:59 | 0.00 | 0.00 | 0.00 |
May | 0.274727E+11 | 0.00 | 279.26 | 0.272175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75239.47 | 22-MAY-13:42 | 66483.55 | 08-MAY-12:22 | 0.00 | 0.00 | 0.00 |
June | 0.621576E+11 | 0.00 | 393.81 | 0.601084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92470.17 | 21-JUN-04:11 | 78498.58 | 30-JUN-04:11 | 0.00 | 0.00 | 0.00 |
July | 0.656468E+11 | 0.00 | 383.69 | 0.605168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97114.04 | 28-JUL-05:27 | 79874.11 | 18-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.688282E+11 | 0.00 | 421.82 | 0.665467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106537.86 | 07-AUG-02:14 | 106537.86 | 07-AUG-02:14 | 0.00 | 0.00 | 0.00 |
September | 0.521530E+11 | 0.00 | 379.66 | 0.519541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 127231.44 | 04-SEP-13:21 | 127231.44 | 04-SEP-13:21 | 0.00 | 0.00 | 0.00 |
October | 0.189234E+11 | 0.00 | 211.63 | 0.189111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130100.22 | 09-OCT-08:38 | 130100.22 | 09-OCT-08:38 | 0.00 | 0.00 | 0.00 |
November | 0.104830E+11 | 0.00 | 165.26 | 0.104830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115817.77 | 13-NOV-01:59 | 115817.77 | 13-NOV-01:59 | 0.00 | 0.00 | 0.00 |
December | 0.761540E+10 | 0.00 | 128.37 | 0.761540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103530.87 | 20-DEC-05:48 | 103530.87 | 20-DEC-05:48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.347267E+12 | 0.00 | 2811.73 | 0.337287E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.417485E+10 | 0.00 | 55.90 | 0.417485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75239.47 | 66483.55 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.688282E+11 | 0.00 | 421.82 | 0.665467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130100.22 | 130100.22 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 4944593.79 | 0.00 | 222.17 | 4944593.79 | 0.00 | 0.00 | 0.00 | 0.00 | 117.43 | 09-JAN-15:02 | 117.43 | 09-JAN-15:02 | 0.00 | 0.00 | 0.00 |
February | 0.157880E+12 | 0.00 | 430.18 | 0.157880E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 301637.03 | 18-FEB-13:08 | 301637.03 | 18-FEB-13:08 | 0.00 | 0.00 | 0.00 |
March | 0.207748E+12 | 0.00 | 741.16 | 0.207748E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 289931.25 | 14-MAR-13:00 | 289931.25 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.192450E+12 | 0.00 | 719.94 | 0.192450E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 258317.24 | 08-APR-13:47 | 258317.24 | 08-APR-13:47 | 0.00 | 0.00 | 0.00 |
May | 0.192044E+11 | 0.00 | 319.19 | 0.192044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 245964.04 | 31-MAY-23:46 | 245964.04 | 31-MAY-23:46 | 0.00 | 0.00 | 0.00 |
June | 0.329468E+12 | 0.00 | 579.45 | 0.318910E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 396195.10 | 22-JUN-13:10 | 306279.55 | 08-JUN-09:38 | 0.00 | 0.00 | 0.00 |
July | 0.458445E+12 | 0.00 | 744.00 | 0.442875E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 459601.40 | 31-JUL-16:21 | 350853.71 | 16-JUL-20:22 | 0.00 | 0.00 | 0.00 |
August | 0.554557E+12 | 0.00 | 743.72 | 0.549461E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 478532.07 | 09-AUG-12:18 | 478532.07 | 09-AUG-12:18 | 0.00 | 0.00 | 0.00 |
September | 0.646257E+11 | 0.00 | 424.60 | 0.646257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 230017.63 | 30-SEP-23:16 | 230017.63 | 30-SEP-23:16 | 0.00 | 0.00 | 0.00 |
October | 0.200059E+12 | 0.00 | 465.64 | 0.200059E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 324296.04 | 11-OCT-17:11 | 324296.04 | 11-OCT-17:11 | 0.00 | 0.00 | 0.00 |
November | 0.202550E+12 | 0.00 | 717.80 | 0.202550E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 288917.03 | 03-NOV-13:32 | 288917.03 | 03-NOV-13:32 | 0.00 | 0.00 | 0.00 |
December | 0.217590E+12 | 0.00 | 744.00 | 0.217590E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 277270.35 | 14-DEC-15:14 | 277270.35 | 14-DEC-15:14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.260458E+13 | 0.00 | 6851.86 | 0.257336E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4944593.79 | 0.00 | 222.17 | 4944593.79 | 0.00 | 0.00 | 0.00 | 0.00 | 117.43 | 117.43 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.554557E+12 | 0.00 | 744.00 | 0.549461E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 478532.07 | 478532.07 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.663993E+10 | 0.203425E+10 | 744.00 | 0.663963E+10 | 304455.16 | 0.00 | 0.59 | 23-JAN-16:35 | 0.20 | 05-JAN-07:03 | 4136.81 | 23-JAN-16:35 | 4136.81 | 23-JAN-16:35 | 21.41 | 02-JAN-07:03 | 1193.43 | 23-JAN-16:40 | 0.00 | 01-JAN-00:05 |
February | 0.103151E+11 | 0.295809E+10 | 672.00 | 0.103151E+11 | -0.0 | 0.00 | 0.79 | 17-FEB-16:51 | 0.44 | 06-FEB-07:01 | 5982.74 | 17-FEB-16:53 | 5982.74 | 17-FEB-16:53 | 0.00 | 28-FEB-14:39 | 1632.71 | 17-FEB-17:00 | 0.00 | 01-FEB-00:01 |
March | 0.171763E+11 | 0.458373E+10 | 744.00 | 0.171763E+11 | 40850.77 | 0.00 | 1.00 | 12-MAR-17:11 | 0.71 | 19-MAR-08:30 | 8539.60 | 31-MAR-23:53 | 8539.60 | 31-MAR-23:53 | 26.38 | 17-MAR-16:00 | 2182.81 | 31-MAR-23:53 | 0.00 | 01-MAR-00:01 |
April | 0.217623E+11 | 0.556568E+10 | 720.00 | 0.217601E+11 | 2207882.21 | 0.00 | 1.00 | 01-APR-00:03 | 0.42 | 30-APR-24:00 | 9786.62 | 08-APR-17:53 | 9786.62 | 08-APR-17:53 | 118.91 | 28-APR-14:20 | 2542.27 | 08-APR-17:53 | 0.00 | 01-APR-00:03 |
May | 0.810801E+10 | 0.246358E+10 | 744.00 | 0.809753E+10 | 10475834.16 | 0.00 | 0.67 | 31-MAY-24:00 | 0.33 | 03-MAY-06:10 | 4969.96 | 31-MAY-23:51 | 4969.96 | 31-MAY-23:51 | 150.91 | 22-MAY-14:00 | 1409.42 | 31-MAY-23:51 | 0.00 | 01-MAY-00:05 |
June | 0.134828E+11 | 0.402643E+10 | 720.00 | 0.134271E+11 | 55688354.68 | 0.00 | 0.89 | 30-JUN-23:25 | 0.61 | 09-JUN-06:07 | 6901.87 | 30-JUN-23:25 | 6901.87 | 30-JUN-23:25 | 253.15 | 22-JUN-13:10 | 2327.94 | 26-JUN-15:40 | 0.00 | 01-JUN-00:01 |
July | 0.190368E+11 | 0.534030E+10 | 744.00 | 0.189601E+11 | 76677288.44 | 0.00 | 1.00 | 01-JUL-17:31 | 0.84 | 29-JUL-06:31 | 8774.40 | 31-JUL-24:00 | 8746.34 | 31-JUL-24:00 | 338.01 | 31-JUL-16:00 | 2673.83 | 17-JUL-13:00 | 0.00 | 01-JUL-00:05 |
August | 0.241491E+11 | 0.658510E+10 | 744.00 | 0.240903E+11 | 58817045.81 | 0.00 | 1.00 | 01-AUG-00:10 | 0.49 | 31-AUG-23:55 | 10209.97 | 13-AUG-18:13 | 10209.97 | 13-AUG-18:13 | 321.31 | 29-AUG-14:50 | 3619.84 | 16-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.831523E+10 | 0.257479E+10 | 720.00 | 0.830958E+10 | 5651118.09 | 0.00 | 0.66 | 30-SEP-23:55 | 0.31 | 22-SEP-06:05 | 4761.99 | 30-SEP-24:00 | 4761.99 | 30-SEP-24:00 | 131.27 | 01-SEP-14:30 | 1509.39 | 10-SEP-17:11 | 0.00 | 01-SEP-00:10 |
October | 0.124425E+11 | 0.353432E+10 | 744.00 | 0.124421E+11 | 430911.87 | 0.00 | 0.82 | 09-OCT-16:52 | 0.49 | 30-OCT-06:01 | 6246.15 | 09-OCT-16:54 | 6246.15 | 09-OCT-16:54 | 39.37 | 03-OCT-14:00 | 1708.04 | 10-OCT-16:00 | 0.00 | 01-OCT-00:01 |
November | 0.167252E+11 | 0.446620E+10 | 720.00 | 0.167252E+11 | -0.0 | 0.00 | 1.00 | 07-NOV-16:00 | 0.73 | 30-NOV-07:03 | 8084.15 | 07-NOV-16:11 | 8084.15 | 07-NOV-16:11 | 0.00 | 17-NOV-15:20 | 2052.84 | 07-NOV-16:11 | 0.00 | 01-NOV-00:01 |
December | 0.217296E+11 | 0.554831E+10 | 744.00 | 0.217296E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-00:05 | 0.89 | 23-DEC-07:03 | 9665.61 | 01-DEC-16:00 | 9665.61 | 01-DEC-16:00 | 0.00 | 12-DEC-19:10 | 2504.51 | 01-DEC-16:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.179883E+12 | 0.496808E+11 | 8760.00 | 0.179673E+12 | 0.210294E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.663993E+10 | 0.203425E+10 | 672.00 | 0.663963E+10 | -0.0 | 0.00 | 0.59 | 0.20 | 4136.81 | 4136.81 | 0.00 | 1193.43 | 0.00 | |||||||
Maximum of Months | 0.241491E+11 | 0.658510E+10 | 744.00 | 0.240903E+11 | 76677288.44 | 0.00 | 1.00 | 0.89 | 10209.97 | 10209.97 | 338.01 | 3619.84 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.483177E+11 | 0.128881E+11 | 738.36 | 0.483146E+11 | 3013875.27 | 0.00 | 0.58 | 23-JAN-16:35 | 0.00 | 01-JAN-05:10 | 39082.58 | 23-JAN-16:35 | 39082.58 | 23-JAN-16:35 | 178.94 | 01-JAN-16:02 | 9690.00 | 23-JAN-16:40 | 0.00 | 01-JAN-00:05 |
February | 0.882491E+11 | 0.219998E+11 | 672.00 | 0.882491E+11 | -0.0 | 0.00 | 0.79 | 17-FEB-16:51 | 0.29 | 06-FEB-04:21 | 58168.30 | 17-FEB-16:53 | 58168.30 | 17-FEB-16:53 | 0.00 | 17-FEB-15:48 | 13579.07 | 17-FEB-17:00 | 0.00 | 01-FEB-00:01 |
March | 0.154914E+12 | 0.358553E+11 | 744.00 | 0.154914E+12 | 732099.40 | 0.00 | 1.00 | 13-MAR-17:20 | 0.57 | 20-MAR-03:03 | 80272.40 | 31-MAR-23:15 | 80272.40 | 31-MAR-23:15 | 325.45 | 17-MAR-16:00 | 17538.28 | 31-MAR-23:15 | 0.00 | 01-MAR-00:01 |
April | 0.198628E+12 | 0.437746E+11 | 720.00 | 0.198607E+12 | 21269269.19 | 0.00 | 1.00 | 01-APR-00:03 | 0.27 | 30-APR-23:55 | 94496.57 | 07-APR-17:50 | 94496.57 | 07-APR-17:50 | 1182.70 | 28-APR-14:20 | 21017.22 | 07-APR-17:50 | 0.00 | 01-APR-00:03 |
May | 0.729529E+11 | 0.191232E+11 | 744.00 | 0.728483E+11 | 0.104626E+09 | 0.00 | 0.66 | 31-MAY-23:41 | 0.22 | 01-MAY-06:05 | 47392.85 | 31-MAY-23:41 | 47392.85 | 31-MAY-23:41 | 1502.96 | 22-MAY-14:00 | 11537.28 | 31-MAY-23:41 | 0.00 | 01-MAY-00:05 |
June | 0.128339E+12 | 0.329230E+11 | 720.00 | 0.127783E+12 | 0.555976E+09 | 0.00 | 0.90 | 30-JUN-23:12 | 0.59 | 10-JUN-06:01 | 67600.59 | 30-JUN-23:55 | 67600.59 | 30-JUN-23:55 | 2519.52 | 22-JUN-13:10 | 19278.57 | 26-JUN-16:00 | 0.00 | 01-JUN-00:01 |
July | 0.181010E+12 | 0.436435E+11 | 744.00 | 0.180245E+12 | 0.765794E+09 | 0.00 | 1.00 | 01-JUL-17:25 | 0.81 | 29-JUL-06:31 | 83002.79 | 31-JUL-24:00 | 82810.49 | 31-JUL-24:00 | 3369.52 | 31-JUL-16:00 | 21959.34 | 17-JUL-13:00 | 0.00 | 01-JUL-00:05 |
August | 0.229343E+12 | 0.535388E+11 | 744.00 | 0.228761E+12 | 0.582170E+09 | 0.00 | 1.00 | 01-AUG-00:10 | 0.46 | 31-AUG-23:55 | 98254.76 | 11-AUG-18:10 | 98254.76 | 11-AUG-18:10 | 3190.78 | 29-AUG-14:50 | 29719.38 | 16-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.749991E+11 | 0.200574E+11 | 720.00 | 0.749426E+11 | 56554910.10 | 0.00 | 0.65 | 10-SEP-17:39 | 0.24 | 22-SEP-06:05 | 43125.57 | 12-SEP-17:40 | 43125.57 | 12-SEP-17:40 | 1294.67 | 01-SEP-14:40 | 12471.13 | 10-SEP-17:22 | 0.00 | 01-SEP-00:10 |
October | 0.111047E+12 | 0.273195E+11 | 744.00 | 0.111043E+12 | 4630009.78 | 0.00 | 0.81 | 05-OCT-16:50 | 0.36 | 30-OCT-06:01 | 59557.24 | 05-OCT-16:50 | 59557.24 | 05-OCT-16:50 | 391.96 | 03-OCT-14:00 | 14022.03 | 11-OCT-16:00 | 0.00 | 01-OCT-00:01 |
November | 0.148726E+12 | 0.345728E+11 | 720.00 | 0.148726E+12 | -0.0 | 0.00 | 1.00 | 07-NOV-16:11 | 0.64 | 30-NOV-07:03 | 77114.44 | 07-NOV-16:11 | 77114.44 | 07-NOV-16:11 | 0.00 | 09-NOV-16:42 | 16771.51 | 07-NOV-16:20 | 0.00 | 01-NOV-00:01 |
December | 0.191104E+12 | 0.423593E+11 | 744.00 | 0.191104E+12 | -0.0 | 0.00 | 1.00 | 01-DEC-09:11 | 0.77 | 25-DEC-05:42 | 91857.16 | 01-DEC-16:00 | 91857.16 | 01-DEC-16:00 | 0.00 | 15-DEC-17:32 | 20375.31 | 01-DEC-16:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.162763E+13 | 0.388055E+12 | 8754.36 | 0.162554E+13 | 0.209477E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.483177E+11 | 0.128881E+11 | 672.00 | 0.483146E+11 | -0.0 | 0.00 | 0.58 | 0.00 | 39082.58 | 39082.58 | 0.00 | 9690.00 | 0.00 | |||||||
Maximum of Months | 0.229343E+12 | 0.535388E+11 | 744.00 | 0.228761E+12 | 0.765794E+09 | 0.00 | 1.00 | 0.81 | 98254.76 | 98254.76 | 3369.52 | 29719.38 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.278290E+10 | 0.875975E+09 | 573.48 | 0.278266E+10 | 238065.79 | 0.00 | 0.56 | 20-JAN-16:33 | 0.00 | 01-JAN-00:05 | 3894.53 | 20-JAN-16:33 | 3894.53 | 20-JAN-16:33 | 33.42 | 01-JAN-16:02 | 1133.55 | 20-JAN-16:40 | 0.00 | 01-JAN-00:05 |
February | 0.691079E+10 | 0.205905E+10 | 671.85 | 0.691079E+10 | -0.0 | 0.00 | 0.77 | 17-FEB-16:51 | 0.00 | 07-FEB-01:31 | 5825.94 | 17-FEB-16:53 | 5825.94 | 17-FEB-16:53 | 0.00 | 17-FEB-17:04 | 1596.76 | 17-FEB-17:00 | 0.00 | 01-FEB-00:01 |
March | 0.138487E+11 | 0.382789E+10 | 744.00 | 0.138487E+11 | 42626.08 | 0.00 | 0.99 | 31-MAR-17:30 | 0.36 | 19-MAR-08:50 | 7879.58 | 31-MAR-17:22 | 7879.58 | 31-MAR-17:22 | 26.05 | 17-MAR-16:00 | 2006.46 | 31-MAR-17:21 | 0.00 | 01-MAR-00:01 |
April | 0.181824E+11 | 0.477271E+10 | 719.17 | 0.181805E+11 | 1953829.19 | 0.00 | 1.00 | 04-APR-13:25 | 0.00 | 30-APR-23:15 | 9563.17 | 07-APR-17:50 | 9563.17 | 07-APR-17:50 | 117.69 | 28-APR-14:05 | 2475.89 | 07-APR-17:50 | 0.00 | 01-APR-00:03 |
May | 0.643086E+10 | 0.198911E+10 | 737.62 | 0.642049E+10 | 10376033.87 | 0.00 | 0.62 | 31-MAY-23:11 | 0.00 | 01-MAY-00:05 | 4578.65 | 31-MAY-23:11 | 4578.43 | 31-MAY-23:12 | 149.53 | 22-MAY-14:00 | 1314.79 | 31-MAY-23:11 | 0.00 | 01-MAY-00:05 |
June | 0.126637E+11 | 0.382508E+10 | 720.00 | 0.126081E+11 | 55605712.33 | 0.00 | 0.88 | 26-JUN-16:00 | 0.50 | 10-JUN-06:01 | 6698.18 | 30-JUN-23:40 | 6698.18 | 30-JUN-23:40 | 253.16 | 22-JUN-13:10 | 2344.60 | 26-JUN-15:50 | 0.00 | 01-JUN-00:01 |
July | 0.179686E+11 | 0.510422E+10 | 744.00 | 0.178922E+11 | 76405575.55 | 0.00 | 1.00 | 01-JUL-17:31 | 0.75 | 29-JUL-06:31 | 8332.89 | 01-JUL-18:40 | 8332.89 | 01-JUL-18:40 | 337.33 | 31-JUL-16:00 | 2622.67 | 17-JUL-13:00 | 0.00 | 01-JUL-00:05 |
August | 0.227396E+11 | 0.618911E+10 | 744.00 | 0.226834E+11 | 56229373.86 | 0.00 | 1.00 | 01-AUG-08:30 | 0.44 | 31-AUG-23:55 | 9987.73 | 11-AUG-18:10 | 9987.73 | 11-AUG-18:10 | 317.62 | 29-AUG-14:50 | 3558.47 | 16-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.687683E+10 | 0.217225E+10 | 719.86 | 0.687129E+10 | 5538568.94 | 0.00 | 0.66 | 10-SEP-17:25 | 0.00 | 22-SEP-07:42 | 4522.27 | 10-SEP-17:22 | 4522.27 | 10-SEP-17:22 | 130.33 | 01-SEP-14:40 | 1536.14 | 10-SEP-17:11 | 0.00 | 01-SEP-00:10 |
October | 0.928102E+10 | 0.272612E+10 | 743.75 | 0.928059E+10 | 425005.29 | 0.00 | 0.80 | 11-OCT-16:40 | 0.00 | 22-OCT-20:51 | 6017.66 | 05-OCT-16:50 | 6017.66 | 05-OCT-16:50 | 38.79 | 03-OCT-14:00 | 1676.42 | 11-OCT-16:00 | 0.00 | 01-OCT-00:01 |
November | 0.126826E+11 | 0.354989E+10 | 720.00 | 0.126826E+11 | -0.0 | 0.00 | 0.98 | 07-NOV-16:11 | 0.42 | 27-NOV-04:24 | 7721.35 | 07-NOV-16:11 | 7721.35 | 07-NOV-16:11 | 0.00 | 17-NOV-10:24 | 1975.07 | 07-NOV-16:20 | 0.00 | 01-NOV-00:01 |
December | 0.168117E+11 | 0.448271E+10 | 744.00 | 0.168117E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-12:25 | 0.57 | 24-DEC-07:39 | 9161.14 | 01-DEC-16:00 | 9161.14 | 01-DEC-16:00 | 0.00 | 13-DEC-15:15 | 2361.62 | 01-DEC-16:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.147180E+12 | 0.415741E+11 | 8581.73 | 0.146973E+12 | 0.206815E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.278290E+10 | 0.875975E+09 | 573.48 | 0.278266E+10 | -0.0 | 0.00 | 0.56 | 0.00 | 3894.53 | 3894.53 | 0.00 | 1133.55 | 0.00 | |||||||
Maximum of Months | 0.227396E+11 | 0.618911E+10 | 744.00 | 0.226834E+11 | 76405575.55 | 0.00 | 1.00 | 0.75 | 9987.73 | 9987.73 | 337.33 | 3558.47 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.34 | 0.00 | 142.34 | 8.39 | 1046.86 | 0.00 | 0.00 | 0.00 |
February | 178.90 | 0.00 | 178.90 | 12.49 | 1062.39 | 0.00 | 0.00 | 0.00 |
March | 243.42 | 0.00 | 243.42 | 61.28 | 815.61 | 0.00 | 0.00 | 0.00 |
April | 305.70 | 1.70 | 304.01 | 104.70 | 723.51 | 0.00 | 0.00 | 0.00 |
May | 417.61 | 13.80 | 403.81 | 306.45 | 391.36 | 0.00 | 0.00 | 0.00 |
June | 457.94 | 50.77 | 407.17 | 587.13 | 209.11 | 0.00 | 0.00 | 0.00 |
July | 433.09 | 28.03 | 405.05 | 565.35 | 199.86 | 0.00 | 0.00 | 0.00 |
August | 344.70 | 8.15 | 336.55 | 422.02 | 232.13 | 0.00 | 0.00 | 0.00 |
September | 289.55 | 0.07 | 289.48 | 301.60 | 356.50 | 0.00 | 0.00 | 0.00 |
October | 207.39 | 0.00 | 207.39 | 73.84 | 773.07 | 0.00 | 0.00 | 0.00 |
November | 157.43 | 0.00 | 157.43 | 20.46 | 959.37 | 0.00 | 0.00 | 0.00 |
December | 133.17 | 0.00 | 133.17 | 8.75 | 1187.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 276.44 | 8.56 | 267.88 | 207.11 | 660.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 133.17 | 0.00 | 133.17 | 8.39 | 199.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 457.94 | 50.77 | 407.17 | 587.13 | 1187.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.34 | 0.00 | 142.34 | 8.39 | 1046.86 | 0.00 | 0.00 | 0.00 |
February | 178.90 | 0.00 | 178.90 | 12.49 | 1062.39 | 0.00 | 0.00 | 0.00 |
March | 243.42 | 0.00 | 243.42 | 61.28 | 815.61 | 0.00 | 0.00 | 0.00 |
April | 305.70 | 1.70 | 304.01 | 104.70 | 723.51 | 0.00 | 0.00 | 0.00 |
May | 417.61 | 13.80 | 403.81 | 306.45 | 391.36 | 0.00 | 0.00 | 0.00 |
June | 457.94 | 50.77 | 407.17 | 587.13 | 209.11 | 0.00 | 0.00 | 0.00 |
July | 433.09 | 28.03 | 405.05 | 565.35 | 199.86 | 0.00 | 0.00 | 0.00 |
August | 344.70 | 8.15 | 336.55 | 422.02 | 232.13 | 0.00 | 0.00 | 0.00 |
September | 289.55 | 0.07 | 289.48 | 301.60 | 356.50 | 0.00 | 0.00 | 0.00 |
October | 207.39 | 0.00 | 207.39 | 73.84 | 773.07 | 0.00 | 0.00 | 0.00 |
November | 157.43 | 0.00 | 157.43 | 20.46 | 959.37 | 0.00 | 0.00 | 0.00 |
December | 133.17 | 0.00 | 133.17 | 8.75 | 1187.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 276.44 | 8.56 | 267.88 | 207.11 | 660.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 133.17 | 0.00 | 133.17 | 8.39 | 199.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 457.94 | 50.77 | 407.17 | 587.13 | 1187.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.34 | 0.00 | 142.34 | 8.39 | 1046.86 | 0.00 | 0.00 | 0.00 |
February | 178.90 | 0.00 | 178.90 | 12.49 | 1062.39 | 0.00 | 0.00 | 0.00 |
March | 243.42 | 0.00 | 243.42 | 61.28 | 815.61 | 0.00 | 0.00 | 0.00 |
April | 305.70 | 1.70 | 304.01 | 104.70 | 723.51 | 0.00 | 0.00 | 0.00 |
May | 417.61 | 13.80 | 403.81 | 306.45 | 391.36 | 0.00 | 0.00 | 0.00 |
June | 457.94 | 50.77 | 407.17 | 587.13 | 209.11 | 0.00 | 0.00 | 0.00 |
July | 433.09 | 28.03 | 405.05 | 565.35 | 199.86 | 0.00 | 0.00 | 0.00 |
August | 344.70 | 8.15 | 336.55 | 422.02 | 232.13 | 0.00 | 0.00 | 0.00 |
September | 289.55 | 0.07 | 289.48 | 301.60 | 356.50 | 0.00 | 0.00 | 0.00 |
October | 207.39 | 0.00 | 207.39 | 73.84 | 773.07 | 0.00 | 0.00 | 0.00 |
November | 157.43 | 0.00 | 157.43 | 20.46 | 959.37 | 0.00 | 0.00 | 0.00 |
December | 133.17 | 0.00 | 133.17 | 8.75 | 1187.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 276.44 | 8.56 | 267.88 | 207.11 | 660.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 133.17 | 0.00 | 133.17 | 8.39 | 199.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 457.94 | 50.77 | 407.17 | 587.13 | 1187.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.34 | 0.00 | 142.34 | 8.39 | 1046.86 | 0.00 | 0.00 | 0.00 |
February | 178.90 | 0.00 | 178.90 | 12.49 | 1062.39 | 0.00 | 0.00 | 0.00 |
March | 243.42 | 0.00 | 243.42 | 61.28 | 815.61 | 0.00 | 0.00 | 0.00 |
April | 305.70 | 1.70 | 304.01 | 104.70 | 723.51 | 0.00 | 0.00 | 0.00 |
May | 417.61 | 13.80 | 403.81 | 306.45 | 391.36 | 0.00 | 0.00 | 0.00 |
June | 457.94 | 50.77 | 407.17 | 587.13 | 209.11 | 0.00 | 0.00 | 0.00 |
July | 433.09 | 28.03 | 405.05 | 565.35 | 199.86 | 0.00 | 0.00 | 0.00 |
August | 344.70 | 8.15 | 336.55 | 422.02 | 232.13 | 0.00 | 0.00 | 0.00 |
September | 289.55 | 0.07 | 289.48 | 301.60 | 356.50 | 0.00 | 0.00 | 0.00 |
October | 207.39 | 0.00 | 207.39 | 73.84 | 773.07 | 0.00 | 0.00 | 0.00 |
November | 157.43 | 0.00 | 157.43 | 20.46 | 959.37 | 0.00 | 0.00 | 0.00 |
December | 133.17 | 0.00 | 133.17 | 8.75 | 1187.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 276.44 | 8.56 | 267.88 | 207.11 | 660.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 133.17 | 0.00 | 133.17 | 8.39 | 199.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 457.94 | 50.77 | 407.17 | 587.13 | 1187.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.33 | 0.00 | 142.33 | 8.39 | 1046.82 | 0.00 | 0.00 | 0.00 |
February | 178.89 | 0.00 | 178.89 | 12.49 | 1062.35 | 0.00 | 0.00 | 0.00 |
March | 243.41 | 0.00 | 243.41 | 61.28 | 815.58 | 0.00 | 0.00 | 0.00 |
April | 305.69 | 1.70 | 304.00 | 104.70 | 723.48 | 0.00 | 0.00 | 0.00 |
May | 417.59 | 13.80 | 403.79 | 306.44 | 391.34 | 0.00 | 0.00 | 0.00 |
June | 457.92 | 50.77 | 407.15 | 587.11 | 209.10 | 0.00 | 0.00 | 0.00 |
July | 433.07 | 28.03 | 405.04 | 565.33 | 199.85 | 0.00 | 0.00 | 0.00 |
August | 344.69 | 8.15 | 336.54 | 422.00 | 232.12 | 0.00 | 0.00 | 0.00 |
September | 289.54 | 0.07 | 289.47 | 301.59 | 356.49 | 0.00 | 0.00 | 0.00 |
October | 207.38 | 0.00 | 207.38 | 73.84 | 773.04 | 0.00 | 0.00 | 0.00 |
November | 157.43 | 0.00 | 157.43 | 20.46 | 959.33 | 0.00 | 0.00 | 0.00 |
December | 133.17 | 0.00 | 133.17 | 8.75 | 1187.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 276.43 | 8.56 | 267.87 | 207.10 | 660.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 133.17 | 0.00 | 133.17 | 8.39 | 199.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 457.92 | 50.77 | 407.15 | 587.11 | 1187.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 495.22 | 303.48 | 191.73 | 367.33 | 1050.78 | 0.00 | 0.00 | 0.00 |
February | 657.84 | 415.29 | 242.55 | 541.48 | 1087.95 | 0.00 | 0.00 | 0.00 |
March | 794.00 | 463.13 | 330.86 | 719.24 | 832.29 | 0.00 | 0.00 | 0.00 |
April | 814.29 | 396.65 | 417.63 | 716.69 | 743.33 | 0.00 | 0.00 | 0.00 |
May | 951.89 | 397.61 | 554.28 | 993.87 | 416.09 | 0.00 | 0.00 | 0.00 |
June | 1161.40 | 609.70 | 551.70 | 1540.70 | 221.95 | 0.00 | 0.00 | 0.00 |
July | 1055.80 | 502.75 | 553.06 | 1419.19 | 206.95 | 0.00 | 0.00 | 0.00 |
August | 1064.92 | 586.52 | 478.40 | 1415.54 | 233.55 | 0.00 | 0.00 | 0.00 |
September | 886.07 | 481.34 | 404.73 | 1094.96 | 361.82 | 0.00 | 0.00 | 0.00 |
October | 641.69 | 351.61 | 290.08 | 611.21 | 809.85 | 0.00 | 0.00 | 0.00 |
November | 499.47 | 282.01 | 217.47 | 402.07 | 977.83 | 0.00 | 0.00 | 0.00 |
December | 432.41 | 249.10 | 183.31 | 303.04 | 1205.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 788.41 | 419.72 | 368.69 | 845.22 | 676.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 432.41 | 249.10 | 183.31 | 303.04 | 206.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1161.40 | 609.70 | 554.28 | 1540.70 | 1205.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 495.22 | 303.48 | 191.73 | 367.33 | 1050.78 | 0.00 | 0.00 | 0.00 |
February | 657.84 | 415.29 | 242.55 | 541.48 | 1087.95 | 0.00 | 0.00 | 0.00 |
March | 794.00 | 463.13 | 330.86 | 719.24 | 832.29 | 0.00 | 0.00 | 0.00 |
April | 814.29 | 396.65 | 417.63 | 716.69 | 743.33 | 0.00 | 0.00 | 0.00 |
May | 951.89 | 397.61 | 554.28 | 993.87 | 416.09 | 0.00 | 0.00 | 0.00 |
June | 1161.40 | 609.70 | 551.70 | 1540.70 | 221.95 | 0.00 | 0.00 | 0.00 |
July | 1055.80 | 502.75 | 553.06 | 1419.19 | 206.95 | 0.00 | 0.00 | 0.00 |
August | 1064.92 | 586.52 | 478.40 | 1415.54 | 233.55 | 0.00 | 0.00 | 0.00 |
September | 886.07 | 481.34 | 404.73 | 1094.96 | 361.82 | 0.00 | 0.00 | 0.00 |
October | 641.69 | 351.61 | 290.08 | 611.21 | 809.85 | 0.00 | 0.00 | 0.00 |
November | 499.47 | 282.01 | 217.47 | 402.07 | 977.83 | 0.00 | 0.00 | 0.00 |
December | 432.41 | 249.10 | 183.31 | 303.04 | 1205.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 788.41 | 419.72 | 368.69 | 845.22 | 676.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 432.41 | 249.10 | 183.31 | 303.04 | 206.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1161.40 | 609.70 | 554.28 | 1540.70 | 1205.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 495.21 | 303.48 | 191.73 | 367.32 | 1050.76 | 0.00 | 0.00 | 0.00 |
February | 657.83 | 415.28 | 242.54 | 541.47 | 1087.93 | 0.00 | 0.00 | 0.00 |
March | 793.98 | 463.12 | 330.86 | 719.23 | 832.28 | 0.00 | 0.00 | 0.00 |
April | 814.27 | 396.65 | 417.63 | 716.68 | 743.31 | 0.00 | 0.00 | 0.00 |
May | 951.87 | 397.60 | 554.27 | 993.85 | 416.08 | 0.00 | 0.00 | 0.00 |
June | 1161.38 | 609.69 | 551.69 | 1540.67 | 221.95 | 0.00 | 0.00 | 0.00 |
July | 1055.79 | 502.74 | 553.05 | 1419.17 | 206.95 | 0.00 | 0.00 | 0.00 |
August | 1064.90 | 586.51 | 478.39 | 1415.52 | 233.54 | 0.00 | 0.00 | 0.00 |
September | 886.05 | 481.33 | 404.72 | 1094.94 | 361.81 | 0.00 | 0.00 | 0.00 |
October | 641.68 | 351.60 | 290.08 | 611.20 | 809.83 | 0.00 | 0.00 | 0.00 |
November | 499.47 | 282.00 | 217.46 | 402.06 | 977.81 | 0.00 | 0.00 | 0.00 |
December | 432.40 | 249.10 | 183.31 | 303.03 | 1205.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 788.40 | 419.72 | 368.68 | 845.21 | 676.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 432.40 | 249.10 | 183.31 | 303.03 | 206.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1161.38 | 609.69 | 554.27 | 1540.67 | 1205.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1364.13 | 1122.14 | 241.99 | 1443.91 | 873.41 | 0.00 | 0.00 | 0.00 |
February | 1308.45 | 1043.18 | 265.27 | 1363.30 | 914.51 | 0.00 | 0.00 | 0.00 |
March | 964.69 | 634.71 | 329.98 | 1023.16 | 749.92 | 0.00 | 0.00 | 0.00 |
April | 624.81 | 251.24 | 373.57 | 585.22 | 695.77 | 0.00 | 0.00 | 0.00 |
May | 572.57 | 104.95 | 467.62 | 598.90 | 412.73 | 0.00 | 0.00 | 0.00 |
June | 527.89 | 96.48 | 431.40 | 754.90 | 225.59 | 0.00 | 0.00 | 0.00 |
July | 549.52 | 98.40 | 451.12 | 789.92 | 210.81 | 0.00 | 0.00 | 0.00 |
August | 699.65 | 292.48 | 407.17 | 1002.96 | 237.11 | 0.00 | 0.00 | 0.00 |
September | 900.17 | 502.29 | 397.88 | 1198.33 | 354.85 | 0.00 | 0.00 | 0.00 |
October | 1076.34 | 763.69 | 312.65 | 1240.30 | 725.38 | 0.00 | 0.00 | 0.00 |
November | 1311.37 | 1045.35 | 266.02 | 1431.99 | 837.86 | 0.00 | 0.00 | 0.00 |
December | 1254.01 | 1014.98 | 239.03 | 1292.29 | 1000.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 927.32 | 578.20 | 349.12 | 1058.69 | 601.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 527.89 | 96.48 | 239.03 | 585.22 | 210.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1364.13 | 1122.14 | 467.62 | 1443.91 | 1000.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1364.13 | 1122.14 | 241.99 | 1443.91 | 873.41 | 0.00 | 0.00 | 0.00 |
February | 1308.45 | 1043.18 | 265.27 | 1363.30 | 914.51 | 0.00 | 0.00 | 0.00 |
March | 964.69 | 634.71 | 329.98 | 1023.16 | 749.92 | 0.00 | 0.00 | 0.00 |
April | 624.81 | 251.24 | 373.57 | 585.22 | 695.77 | 0.00 | 0.00 | 0.00 |
May | 572.57 | 104.95 | 467.62 | 598.89 | 412.73 | 0.00 | 0.00 | 0.00 |
June | 527.89 | 96.48 | 431.40 | 754.90 | 225.59 | 0.00 | 0.00 | 0.00 |
July | 549.52 | 98.40 | 451.12 | 789.92 | 210.81 | 0.00 | 0.00 | 0.00 |
August | 699.65 | 292.48 | 407.17 | 1002.96 | 237.11 | 0.00 | 0.00 | 0.00 |
September | 900.17 | 502.29 | 397.88 | 1198.33 | 354.85 | 0.00 | 0.00 | 0.00 |
October | 1076.34 | 763.68 | 312.65 | 1240.30 | 725.38 | 0.00 | 0.00 | 0.00 |
November | 1311.37 | 1045.35 | 266.02 | 1431.99 | 837.86 | 0.00 | 0.00 | 0.00 |
December | 1254.01 | 1014.98 | 239.03 | 1292.29 | 1000.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 927.32 | 578.20 | 349.12 | 1058.69 | 601.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 527.89 | 96.48 | 239.03 | 585.22 | 210.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1364.13 | 1122.14 | 467.62 | 1443.91 | 1000.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1364.13 | 1122.14 | 241.99 | 1443.91 | 873.41 | 0.00 | 0.00 | 0.00 |
February | 1308.45 | 1043.18 | 265.27 | 1363.30 | 914.51 | 0.00 | 0.00 | 0.00 |
March | 964.69 | 634.71 | 329.98 | 1023.16 | 749.92 | 0.00 | 0.00 | 0.00 |
April | 624.81 | 251.24 | 373.57 | 585.22 | 695.77 | 0.00 | 0.00 | 0.00 |
May | 572.57 | 104.95 | 467.62 | 598.90 | 412.73 | 0.00 | 0.00 | 0.00 |
June | 527.89 | 96.48 | 431.40 | 754.90 | 225.59 | 0.00 | 0.00 | 0.00 |
July | 549.52 | 98.40 | 451.12 | 789.92 | 210.81 | 0.00 | 0.00 | 0.00 |
August | 699.65 | 292.48 | 407.17 | 1002.96 | 237.11 | 0.00 | 0.00 | 0.00 |
September | 900.17 | 502.29 | 397.88 | 1198.33 | 354.85 | 0.00 | 0.00 | 0.00 |
October | 1076.34 | 763.69 | 312.65 | 1240.30 | 725.38 | 0.00 | 0.00 | 0.00 |
November | 1311.37 | 1045.35 | 266.02 | 1431.99 | 837.86 | 0.00 | 0.00 | 0.00 |
December | 1254.01 | 1014.98 | 239.03 | 1292.29 | 1000.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 927.32 | 578.20 | 349.12 | 1058.69 | 601.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 527.89 | 96.48 | 239.03 | 585.22 | 210.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1364.13 | 1122.14 | 467.62 | 1443.91 | 1000.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1364.13 | 1122.14 | 241.99 | 1443.91 | 873.41 | 0.00 | 0.00 | 0.00 |
February | 1308.45 | 1043.18 | 265.27 | 1363.30 | 914.51 | 0.00 | 0.00 | 0.00 |
March | 964.69 | 634.71 | 329.98 | 1023.16 | 749.92 | 0.00 | 0.00 | 0.00 |
April | 624.81 | 251.24 | 373.57 | 585.22 | 695.77 | 0.00 | 0.00 | 0.00 |
May | 572.57 | 104.95 | 467.62 | 598.89 | 412.73 | 0.00 | 0.00 | 0.00 |
June | 527.89 | 96.48 | 431.40 | 754.90 | 225.59 | 0.00 | 0.00 | 0.00 |
July | 549.52 | 98.40 | 451.12 | 789.92 | 210.81 | 0.00 | 0.00 | 0.00 |
August | 699.65 | 292.48 | 407.17 | 1002.96 | 237.11 | 0.00 | 0.00 | 0.00 |
September | 900.17 | 502.29 | 397.88 | 1198.33 | 354.85 | 0.00 | 0.00 | 0.00 |
October | 1076.34 | 763.68 | 312.65 | 1240.30 | 725.38 | 0.00 | 0.00 | 0.00 |
November | 1311.37 | 1045.35 | 266.02 | 1431.99 | 837.86 | 0.00 | 0.00 | 0.00 |
December | 1254.01 | 1014.98 | 239.03 | 1292.29 | 1000.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 927.32 | 578.20 | 349.12 | 1058.69 | 601.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 527.89 | 96.48 | 239.03 | 585.22 | 210.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1364.13 | 1122.14 | 467.62 | 1443.91 | 1000.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1364.08 | 1122.10 | 241.98 | 1443.85 | 873.37 | 0.00 | 0.00 | 0.00 |
February | 1308.40 | 1043.14 | 265.26 | 1363.25 | 914.48 | 0.00 | 0.00 | 0.00 |
March | 964.65 | 634.69 | 329.97 | 1023.12 | 749.89 | 0.00 | 0.00 | 0.00 |
April | 624.78 | 251.23 | 373.55 | 585.20 | 695.75 | 0.00 | 0.00 | 0.00 |
May | 572.54 | 104.94 | 467.60 | 598.87 | 412.72 | 0.00 | 0.00 | 0.00 |
June | 527.87 | 96.48 | 431.39 | 754.87 | 225.58 | 0.00 | 0.00 | 0.00 |
July | 549.50 | 98.40 | 451.10 | 789.89 | 210.80 | 0.00 | 0.00 | 0.00 |
August | 699.62 | 292.47 | 407.15 | 1002.92 | 237.10 | 0.00 | 0.00 | 0.00 |
September | 900.13 | 502.27 | 397.86 | 1198.29 | 354.84 | 0.00 | 0.00 | 0.00 |
October | 1076.29 | 763.65 | 312.64 | 1240.25 | 725.35 | 0.00 | 0.00 | 0.00 |
November | 1311.31 | 1045.31 | 266.01 | 1431.94 | 837.82 | 0.00 | 0.00 | 0.00 |
December | 1253.96 | 1014.94 | 239.02 | 1292.24 | 1000.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 927.28 | 578.17 | 349.11 | 1058.64 | 601.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 527.87 | 96.48 | 239.02 | 585.20 | 210.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1364.08 | 1122.10 | 467.60 | 1443.85 | 1000.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 526.80 | 333.81 | 192.99 | 435.15 | 1125.60 | 0.00 | 0.00 | 0.00 |
February | 635.25 | 393.66 | 241.58 | 525.03 | 1153.87 | 0.00 | 0.00 | 0.00 |
March | 743.83 | 410.39 | 333.44 | 660.70 | 921.79 | 0.00 | 0.00 | 0.00 |
April | 700.35 | 296.52 | 403.84 | 574.33 | 853.56 | 0.00 | 0.00 | 0.00 |
May | 856.01 | 301.78 | 554.23 | 889.95 | 481.63 | 0.00 | 0.00 | 0.00 |
June | 1046.95 | 503.73 | 543.22 | 1402.32 | 287.04 | 0.00 | 0.00 | 0.00 |
July | 853.02 | 312.44 | 540.57 | 1135.12 | 275.39 | 0.00 | 0.00 | 0.00 |
August | 890.31 | 439.83 | 450.48 | 1156.36 | 314.09 | 0.00 | 0.00 | 0.00 |
September | 789.44 | 378.59 | 410.85 | 980.32 | 425.47 | 0.00 | 0.00 | 0.00 |
October | 664.13 | 379.60 | 284.53 | 662.31 | 874.45 | 0.00 | 0.00 | 0.00 |
November | 544.95 | 330.85 | 214.10 | 464.80 | 1066.20 | 0.00 | 0.00 | 0.00 |
December | 440.17 | 260.02 | 180.15 | 317.29 | 1309.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 724.49 | 361.33 | 363.16 | 767.99 | 755.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 440.17 | 260.02 | 180.15 | 317.29 | 275.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1046.95 | 503.73 | 554.23 | 1402.32 | 1309.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 526.80 | 333.81 | 192.99 | 435.15 | 1125.60 | 0.00 | 0.00 | 0.00 |
February | 635.25 | 393.66 | 241.58 | 525.03 | 1153.87 | 0.00 | 0.00 | 0.00 |
March | 743.83 | 410.39 | 333.44 | 660.70 | 921.79 | 0.00 | 0.00 | 0.00 |
April | 700.35 | 296.52 | 403.84 | 574.33 | 853.56 | 0.00 | 0.00 | 0.00 |
May | 856.01 | 301.78 | 554.23 | 889.95 | 481.63 | 0.00 | 0.00 | 0.00 |
June | 1046.95 | 503.73 | 543.22 | 1402.32 | 287.04 | 0.00 | 0.00 | 0.00 |
July | 853.02 | 312.44 | 540.57 | 1135.12 | 275.39 | 0.00 | 0.00 | 0.00 |
August | 890.31 | 439.83 | 450.48 | 1156.36 | 314.09 | 0.00 | 0.00 | 0.00 |
September | 789.44 | 378.59 | 410.85 | 980.32 | 425.47 | 0.00 | 0.00 | 0.00 |
October | 664.13 | 379.60 | 284.53 | 662.31 | 874.45 | 0.00 | 0.00 | 0.00 |
November | 544.95 | 330.85 | 214.10 | 464.80 | 1066.20 | 0.00 | 0.00 | 0.00 |
December | 440.17 | 260.02 | 180.15 | 317.29 | 1309.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 724.49 | 361.33 | 363.16 | 767.99 | 755.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 440.17 | 260.02 | 180.15 | 317.29 | 275.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1046.95 | 503.73 | 554.23 | 1402.32 | 1309.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 526.79 | 333.80 | 192.99 | 435.14 | 1125.58 | 0.00 | 0.00 | 0.00 |
February | 635.23 | 393.66 | 241.58 | 525.02 | 1153.84 | 0.00 | 0.00 | 0.00 |
March | 743.82 | 410.38 | 333.44 | 660.69 | 921.77 | 0.00 | 0.00 | 0.00 |
April | 700.34 | 296.51 | 403.83 | 574.32 | 853.55 | 0.00 | 0.00 | 0.00 |
May | 855.99 | 301.77 | 554.22 | 889.93 | 481.62 | 0.00 | 0.00 | 0.00 |
June | 1046.93 | 503.72 | 543.21 | 1402.29 | 287.03 | 0.00 | 0.00 | 0.00 |
July | 853.00 | 312.44 | 540.56 | 1135.10 | 275.38 | 0.00 | 0.00 | 0.00 |
August | 890.29 | 439.82 | 450.48 | 1156.33 | 314.08 | 0.00 | 0.00 | 0.00 |
September | 789.42 | 378.58 | 410.84 | 980.30 | 425.47 | 0.00 | 0.00 | 0.00 |
October | 664.11 | 379.59 | 284.52 | 662.30 | 874.44 | 0.00 | 0.00 | 0.00 |
November | 544.94 | 330.85 | 214.09 | 464.79 | 1066.18 | 0.00 | 0.00 | 0.00 |
December | 440.16 | 260.02 | 180.15 | 317.28 | 1309.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 724.48 | 361.33 | 363.15 | 767.98 | 755.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 440.16 | 260.02 | 180.15 | 317.28 | 275.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1046.93 | 503.72 | 554.22 | 1402.29 | 1309.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 711.67 | 0.00 | 711.67 | 67.43 | 4823.23 | 0.00 | 0.00 | 0.00 |
February | 894.49 | 0.00 | 894.49 | 88.89 | 4973.29 | 0.00 | 0.00 | 0.00 |
March | 1217.10 | 0.00 | 1217.10 | 372.77 | 3758.87 | 0.00 | 0.00 | 0.00 |
April | 1528.51 | 8.48 | 1520.03 | 595.84 | 3254.44 | 0.00 | 0.00 | 0.00 |
May | 2088.03 | 69.02 | 2019.01 | 1598.28 | 1835.58 | 0.00 | 0.00 | 0.00 |
June | 2289.67 | 253.85 | 2035.82 | 2990.99 | 985.94 | 0.00 | 0.00 | 0.00 |
July | 2165.41 | 140.17 | 2025.24 | 2890.10 | 935.20 | 0.00 | 0.00 | 0.00 |
August | 1723.50 | 40.77 | 1682.73 | 2182.43 | 1066.82 | 0.00 | 0.00 | 0.00 |
September | 1447.74 | 0.34 | 1447.40 | 1584.98 | 1631.60 | 0.00 | 0.00 | 0.00 |
October | 1036.93 | 0.00 | 1036.93 | 445.86 | 3560.34 | 0.00 | 0.00 | 0.00 |
November | 787.16 | 0.00 | 787.16 | 142.50 | 4375.92 | 0.00 | 0.00 | 0.00 |
December | 665.86 | 0.00 | 665.86 | 72.75 | 5473.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1382.20 | 42.82 | 1339.38 | 1091.61 | 3045.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 665.86 | 0.00 | 665.86 | 67.43 | 935.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2289.67 | 253.85 | 2035.82 | 2990.99 | 5473.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1485.63 | 910.44 | 575.19 | 1120.83 | 2990.70 | 0.00 | 0.00 | 0.00 |
February | 1973.50 | 1245.86 | 727.64 | 1624.42 | 3143.98 | 0.00 | 0.00 | 0.00 |
March | 2381.96 | 1389.38 | 992.58 | 2143.03 | 2387.89 | 0.00 | 0.00 | 0.00 |
April | 2442.83 | 1189.95 | 1252.89 | 2130.54 | 2086.97 | 0.00 | 0.00 | 0.00 |
May | 2855.63 | 1192.81 | 1662.82 | 2951.92 | 1209.95 | 0.00 | 0.00 | 0.00 |
June | 3484.16 | 1829.09 | 1655.07 | 4583.74 | 645.31 | 0.00 | 0.00 | 0.00 |
July | 3167.38 | 1508.23 | 1659.15 | 4221.40 | 617.60 | 0.00 | 0.00 | 0.00 |
August | 3194.74 | 1759.55 | 1435.19 | 4211.35 | 698.79 | 0.00 | 0.00 | 0.00 |
September | 2658.18 | 1444.00 | 1214.18 | 3265.54 | 1034.53 | 0.00 | 0.00 | 0.00 |
October | 1925.06 | 1054.82 | 870.24 | 1823.83 | 2313.38 | 0.00 | 0.00 | 0.00 |
November | 1498.41 | 846.02 | 652.39 | 1218.81 | 2789.15 | 0.00 | 0.00 | 0.00 |
December | 1297.22 | 747.29 | 549.93 | 930.02 | 3434.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2365.21 | 1259.16 | 1106.05 | 2523.06 | 1939.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1297.22 | 747.29 | 549.93 | 930.02 | 617.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3484.16 | 1829.09 | 1662.82 | 4583.74 | 3434.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 6820.57 | 5610.66 | 1209.92 | 7147.07 | 4340.43 | 0.00 | 0.00 | 0.00 |
February | 6542.20 | 5215.85 | 1326.34 | 6714.41 | 4555.02 | 0.00 | 0.00 | 0.00 |
March | 4823.41 | 3173.53 | 1649.88 | 5053.67 | 3686.12 | 0.00 | 0.00 | 0.00 |
April | 3124.00 | 1256.17 | 1867.83 | 2902.29 | 3345.80 | 0.00 | 0.00 | 0.00 |
May | 2862.80 | 524.73 | 2338.07 | 2974.38 | 2038.49 | 0.00 | 0.00 | 0.00 |
June | 2639.41 | 482.41 | 2157.00 | 3778.87 | 1091.80 | 0.00 | 0.00 | 0.00 |
July | 2747.56 | 492.01 | 2255.55 | 3958.06 | 1025.09 | 0.00 | 0.00 | 0.00 |
August | 3498.20 | 1462.38 | 2035.82 | 5004.96 | 1154.59 | 0.00 | 0.00 | 0.00 |
September | 4500.78 | 2511.41 | 1989.37 | 5945.11 | 1743.92 | 0.00 | 0.00 | 0.00 |
October | 5381.62 | 3818.38 | 1563.24 | 6137.62 | 3592.66 | 0.00 | 0.00 | 0.00 |
November | 6556.75 | 5226.68 | 1330.07 | 7079.59 | 4153.66 | 0.00 | 0.00 | 0.00 |
December | 6269.97 | 5074.83 | 1195.14 | 6404.13 | 4914.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4636.54 | 2890.95 | 1745.59 | 5250.02 | 2961.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2639.41 | 482.41 | 1195.14 | 2902.29 | 1025.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6820.57 | 5610.66 | 2338.07 | 7147.07 | 4914.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1580.38 | 1001.42 | 578.97 | 1339.68 | 3120.16 | 0.00 | 0.00 | 0.00 |
February | 1905.72 | 1180.98 | 724.74 | 1599.56 | 3235.67 | 0.00 | 0.00 | 0.00 |
March | 2231.47 | 1231.15 | 1000.32 | 2028.40 | 2509.17 | 0.00 | 0.00 | 0.00 |
April | 2101.04 | 889.54 | 1211.49 | 1787.60 | 2207.49 | 0.00 | 0.00 | 0.00 |
May | 2568.00 | 905.32 | 1662.69 | 2711.58 | 1341.26 | 0.00 | 0.00 | 0.00 |
June | 3140.82 | 1511.17 | 1629.65 | 4253.04 | 779.28 | 0.00 | 0.00 | 0.00 |
July | 2559.03 | 937.32 | 1621.70 | 3487.02 | 711.32 | 0.00 | 0.00 | 0.00 |
August | 2670.90 | 1319.46 | 1351.44 | 3566.84 | 794.58 | 0.00 | 0.00 | 0.00 |
September | 2368.29 | 1135.75 | 1232.54 | 2991.84 | 1161.10 | 0.00 | 0.00 | 0.00 |
October | 1992.36 | 1138.78 | 853.58 | 2025.75 | 2417.83 | 0.00 | 0.00 | 0.00 |
November | 1634.84 | 992.55 | 642.29 | 1446.17 | 2888.56 | 0.00 | 0.00 | 0.00 |
December | 1320.50 | 780.05 | 540.45 | 1002.43 | 3514.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2173.46 | 1083.99 | 1089.47 | 2356.60 | 2050.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1320.50 | 780.05 | 540.45 | 1002.43 | 711.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3140.82 | 1511.17 | 1662.69 | 4253.04 | 3514.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 711.67 | 0.00 | 711.67 | 84.13 | 4508.29 | 0.00 | 0.00 | 0.00 |
February | 894.49 | 0.00 | 894.49 | 106.50 | 4695.55 | 0.00 | 0.00 | 0.00 |
March | 1217.10 | 0.00 | 1217.10 | 398.33 | 3518.79 | 0.00 | 0.00 | 0.00 |
April | 1528.51 | 8.48 | 1520.03 | 620.77 | 2966.42 | 0.00 | 0.00 | 0.00 |
May | 2088.03 | 69.02 | 2019.01 | 1667.74 | 1681.26 | 0.00 | 0.00 | 0.00 |
June | 2289.67 | 253.85 | 2035.82 | 3007.80 | 930.56 | 0.00 | 0.00 | 0.00 |
July | 2165.41 | 140.17 | 2025.24 | 2905.09 | 886.65 | 0.00 | 0.00 | 0.00 |
August | 1723.50 | 40.77 | 1682.73 | 2200.83 | 997.65 | 0.00 | 0.00 | 0.00 |
September | 1447.74 | 0.34 | 1447.40 | 1626.93 | 1491.07 | 0.00 | 0.00 | 0.00 |
October | 1036.93 | 0.00 | 1036.93 | 488.67 | 3261.11 | 0.00 | 0.00 | 0.00 |
November | 787.16 | 0.00 | 787.16 | 172.36 | 4018.09 | 0.00 | 0.00 | 0.00 |
December | 665.86 | 0.00 | 665.86 | 88.87 | 5186.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1382.20 | 42.82 | 1339.38 | 1119.62 | 2835.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 665.86 | 0.00 | 665.86 | 84.13 | 886.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2289.67 | 253.85 | 2035.82 | 3007.80 | 5186.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1485.63 | 910.44 | 575.19 | 1172.54 | 2780.61 | 0.00 | 0.00 | 0.00 |
February | 1973.50 | 1245.86 | 727.64 | 1665.12 | 2960.75 | 0.00 | 0.00 | 0.00 |
March | 2381.96 | 1389.38 | 992.58 | 2174.03 | 2239.58 | 0.00 | 0.00 | 0.00 |
April | 2442.83 | 1189.95 | 1252.89 | 2160.03 | 1915.28 | 0.00 | 0.00 | 0.00 |
May | 2855.63 | 1192.81 | 1662.82 | 2988.49 | 1133.63 | 0.00 | 0.00 | 0.00 |
June | 3484.16 | 1829.09 | 1655.07 | 4569.58 | 623.79 | 0.00 | 0.00 | 0.00 |
July | 3167.38 | 1508.23 | 1659.15 | 4208.94 | 600.35 | 0.00 | 0.00 | 0.00 |
August | 3194.74 | 1759.55 | 1435.19 | 4201.73 | 673.19 | 0.00 | 0.00 | 0.00 |
September | 2658.18 | 1444.00 | 1214.18 | 3280.55 | 969.95 | 0.00 | 0.00 | 0.00 |
October | 1925.06 | 1054.82 | 870.24 | 1867.24 | 2137.29 | 0.00 | 0.00 | 0.00 |
November | 1498.41 | 846.02 | 652.39 | 1272.17 | 2566.82 | 0.00 | 0.00 | 0.00 |
December | 1297.22 | 747.29 | 549.93 | 969.61 | 3246.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2365.21 | 1259.16 | 1106.05 | 2548.37 | 1814.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1297.22 | 747.29 | 549.93 | 969.61 | 600.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3484.16 | 1829.09 | 1662.82 | 4569.58 | 3246.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 6820.57 | 5610.66 | 1209.92 | 7233.30 | 4011.89 | 0.00 | 0.00 | 0.00 |
February | 6542.20 | 5215.85 | 1326.34 | 6763.66 | 4277.04 | 0.00 | 0.00 | 0.00 |
March | 4823.41 | 3173.53 | 1649.88 | 5085.86 | 3444.00 | 0.00 | 0.00 | 0.00 |
April | 3124.00 | 1256.17 | 1867.83 | 2920.83 | 3060.94 | 0.00 | 0.00 | 0.00 |
May | 2862.80 | 524.73 | 2338.07 | 3013.93 | 1881.06 | 0.00 | 0.00 | 0.00 |
June | 2639.41 | 482.41 | 2157.00 | 3773.58 | 1029.57 | 0.00 | 0.00 | 0.00 |
July | 2747.56 | 492.01 | 2255.55 | 3955.95 | 971.04 | 0.00 | 0.00 | 0.00 |
August | 3498.20 | 1462.38 | 2035.82 | 4999.41 | 1085.57 | 0.00 | 0.00 | 0.00 |
September | 4500.78 | 2511.41 | 1989.37 | 5960.02 | 1613.37 | 0.00 | 0.00 | 0.00 |
October | 5381.62 | 3818.38 | 1563.24 | 6178.77 | 3303.22 | 0.00 | 0.00 | 0.00 |
November | 6556.75 | 5226.68 | 1330.07 | 7152.57 | 3824.27 | 0.00 | 0.00 | 0.00 |
December | 6269.97 | 5074.83 | 1195.14 | 6471.68 | 4613.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4636.54 | 2890.95 | 1745.59 | 5284.11 | 2751.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2639.41 | 482.41 | 1195.14 | 2920.83 | 971.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6820.57 | 5610.66 | 2338.07 | 7233.30 | 4613.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1580.38 | 1001.42 | 578.97 | 1353.75 | 2930.84 | 0.00 | 0.00 | 0.00 |
February | 1905.72 | 1180.98 | 724.74 | 1603.39 | 3073.50 | 0.00 | 0.00 | 0.00 |
March | 2231.47 | 1231.15 | 1000.32 | 2026.63 | 2373.04 | 0.00 | 0.00 | 0.00 |
April | 2101.04 | 889.54 | 1211.49 | 1785.27 | 2044.47 | 0.00 | 0.00 | 0.00 |
May | 2568.00 | 905.32 | 1662.69 | 2715.48 | 1258.37 | 0.00 | 0.00 | 0.00 |
June | 3140.82 | 1511.17 | 1629.65 | 4234.33 | 746.74 | 0.00 | 0.00 | 0.00 |
July | 2559.03 | 937.32 | 1621.70 | 3471.63 | 684.74 | 0.00 | 0.00 | 0.00 |
August | 2670.90 | 1319.46 | 1351.44 | 3553.44 | 761.20 | 0.00 | 0.00 | 0.00 |
September | 2368.29 | 1135.75 | 1232.54 | 2989.79 | 1091.36 | 0.00 | 0.00 | 0.00 |
October | 1992.36 | 1138.78 | 853.58 | 2032.08 | 2254.63 | 0.00 | 0.00 | 0.00 |
November | 1634.84 | 992.55 | 642.29 | 1459.52 | 2692.02 | 0.00 | 0.00 | 0.00 |
December | 1320.50 | 780.05 | 540.45 | 1013.05 | 3346.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2173.46 | 1083.99 | 1089.47 | 2356.46 | 1932.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1320.50 | 780.05 | 540.45 | 1013.05 | 684.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3140.82 | 1511.17 | 1662.69 | 4234.33 | 3346.51 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.381233E+09 | 0.00 | 0.381233E+09 | 22481462.82 | 0.280390E+10 |
February | 0.432794E+09 | 0.00 | 0.432794E+09 | 30227240.04 | 0.257015E+10 |
March | 0.651985E+09 | 0.00 | 0.651985E+09 | 0.164133E+09 | 0.218454E+10 |
April | 0.792387E+09 | 4395822.56 | 0.787991E+09 | 0.271382E+09 | 0.187534E+10 |
May | 0.111853E+10 | 36974112.20 | 0.108156E+10 | 0.820794E+09 | 0.104821E+10 |
June | 0.118698E+10 | 0.131596E+09 | 0.105538E+10 | 0.152185E+10 | 0.542011E+09 |
July | 0.115998E+10 | 75087467.78 | 0.108489E+10 | 0.151424E+10 | 0.535292E+09 |
August | 0.923255E+09 | 21841105.20 | 0.901414E+09 | 0.113033E+10 | 0.621746E+09 |
September | 0.750517E+09 | 176283.16 | 0.750341E+09 | 0.781746E+09 | 0.924060E+09 |
October | 0.555470E+09 | 0.00 | 0.555470E+09 | 0.197769E+09 | 0.207059E+10 |
November | 0.408069E+09 | 0.00 | 0.408069E+09 | 53023341.70 | 0.248668E+10 |
December | 0.356692E+09 | 0.00 | 0.356692E+09 | 23425897.93 | 0.317947E+10 |
Annual Sum or Average | 0.871789E+10 | 0.270071E+09 | 0.844782E+10 | 0.653140E+10 | 0.208420E+11 |
Minimum of Months | 0.356692E+09 | 0.00 | 0.356692E+09 | 22481462.82 | 0.535292E+09 |
Maximum of Months | 0.118698E+10 | 0.131596E+09 | 0.108489E+10 | 0.152185E+10 | 0.317947E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.381233E+09 | 0.00 | 0.381233E+09 | 22481414.01 | 0.280390E+10 |
February | 0.432793E+09 | 0.00 | 0.432793E+09 | 30227189.26 | 0.257015E+10 |
March | 0.651985E+09 | 0.00 | 0.651985E+09 | 0.164133E+09 | 0.218454E+10 |
April | 0.792386E+09 | 4395817.28 | 0.787991E+09 | 0.271381E+09 | 0.187534E+10 |
May | 0.111853E+10 | 36974067.83 | 0.108156E+10 | 0.820793E+09 | 0.104821E+10 |
June | 0.118698E+10 | 0.131596E+09 | 0.105538E+10 | 0.152185E+10 | 0.542011E+09 |
July | 0.115998E+10 | 75087377.68 | 0.108489E+10 | 0.151424E+10 | 0.535292E+09 |
August | 0.923254E+09 | 21841078.99 | 0.901413E+09 | 0.113033E+10 | 0.621746E+09 |
September | 0.750516E+09 | 176282.95 | 0.750340E+09 | 0.781746E+09 | 0.924059E+09 |
October | 0.555469E+09 | 0.00 | 0.555469E+09 | 0.197769E+09 | 0.207059E+10 |
November | 0.408069E+09 | 0.00 | 0.408069E+09 | 53023272.08 | 0.248668E+10 |
December | 0.356691E+09 | 0.00 | 0.356691E+09 | 23425868.53 | 0.317947E+10 |
Annual Sum or Average | 0.871788E+10 | 0.270070E+09 | 0.844781E+10 | 0.653140E+10 | 0.208420E+11 |
Minimum of Months | 0.356691E+09 | 0.00 | 0.356691E+09 | 22481414.01 | 0.535292E+09 |
Maximum of Months | 0.118698E+10 | 0.131596E+09 | 0.108489E+10 | 0.152185E+10 | 0.317947E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.381233E+09 | 0.00 | 0.381233E+09 | 22481462.82 | 0.280390E+10 |
February | 0.432794E+09 | 0.00 | 0.432794E+09 | 30227240.04 | 0.257015E+10 |
March | 0.651985E+09 | 0.00 | 0.651985E+09 | 0.164133E+09 | 0.218454E+10 |
April | 0.792387E+09 | 4395822.56 | 0.787991E+09 | 0.271382E+09 | 0.187534E+10 |
May | 0.111853E+10 | 36974112.20 | 0.108156E+10 | 0.820794E+09 | 0.104821E+10 |
June | 0.118698E+10 | 0.131596E+09 | 0.105538E+10 | 0.152185E+10 | 0.542011E+09 |
July | 0.115998E+10 | 75087467.78 | 0.108489E+10 | 0.151424E+10 | 0.535292E+09 |
August | 0.923255E+09 | 21841105.20 | 0.901414E+09 | 0.113033E+10 | 0.621746E+09 |
September | 0.750517E+09 | 176283.16 | 0.750341E+09 | 0.781746E+09 | 0.924060E+09 |
October | 0.555470E+09 | 0.00 | 0.555470E+09 | 0.197769E+09 | 0.207059E+10 |
November | 0.408069E+09 | 0.00 | 0.408069E+09 | 53023341.70 | 0.248668E+10 |
December | 0.356692E+09 | 0.00 | 0.356692E+09 | 23425897.93 | 0.317947E+10 |
Annual Sum or Average | 0.871789E+10 | 0.270071E+09 | 0.844782E+10 | 0.653140E+10 | 0.208420E+11 |
Minimum of Months | 0.356692E+09 | 0.00 | 0.356692E+09 | 22481462.82 | 0.535292E+09 |
Maximum of Months | 0.118698E+10 | 0.131596E+09 | 0.108489E+10 | 0.152185E+10 | 0.317947E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.381233E+09 | 0.00 | 0.381233E+09 | 22481414.01 | 0.280390E+10 |
February | 0.432793E+09 | 0.00 | 0.432793E+09 | 30227189.26 | 0.257015E+10 |
March | 0.651985E+09 | 0.00 | 0.651985E+09 | 0.164133E+09 | 0.218454E+10 |
April | 0.792386E+09 | 4395817.28 | 0.787991E+09 | 0.271381E+09 | 0.187534E+10 |
May | 0.111853E+10 | 36974067.83 | 0.108156E+10 | 0.820793E+09 | 0.104821E+10 |
June | 0.118698E+10 | 0.131596E+09 | 0.105538E+10 | 0.152185E+10 | 0.542011E+09 |
July | 0.115998E+10 | 75087377.68 | 0.108489E+10 | 0.151424E+10 | 0.535292E+09 |
August | 0.923254E+09 | 21841078.99 | 0.901413E+09 | 0.113033E+10 | 0.621746E+09 |
September | 0.750516E+09 | 176282.95 | 0.750340E+09 | 0.781746E+09 | 0.924059E+09 |
October | 0.555469E+09 | 0.00 | 0.555469E+09 | 0.197769E+09 | 0.207059E+10 |
November | 0.408069E+09 | 0.00 | 0.408069E+09 | 53023272.08 | 0.248668E+10 |
December | 0.356691E+09 | 0.00 | 0.356691E+09 | 23425868.53 | 0.317947E+10 |
Annual Sum or Average | 0.871788E+10 | 0.270070E+09 | 0.844781E+10 | 0.653140E+10 | 0.208420E+11 |
Minimum of Months | 0.356691E+09 | 0.00 | 0.356691E+09 | 22481414.01 | 0.535292E+09 |
Maximum of Months | 0.118698E+10 | 0.131596E+09 | 0.108489E+10 | 0.152185E+10 | 0.317947E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.381218E+09 | 0.00 | 0.381218E+09 | 22480556.72 | 0.280379E+10 |
February | 0.432776E+09 | 0.00 | 0.432776E+09 | 30226021.75 | 0.257004E+10 |
March | 0.651959E+09 | 0.00 | 0.651959E+09 | 0.164126E+09 | 0.218445E+10 |
April | 0.792355E+09 | 4395645.39 | 0.787959E+09 | 0.271371E+09 | 0.187526E+10 |
May | 0.111849E+10 | 36972621.98 | 0.108151E+10 | 0.820761E+09 | 0.104817E+10 |
June | 0.118693E+10 | 0.131591E+09 | 0.105534E+10 | 0.152179E+10 | 0.541989E+09 |
July | 0.115993E+10 | 75084441.42 | 0.108485E+10 | 0.151418E+10 | 0.535271E+09 |
August | 0.923218E+09 | 21840224.91 | 0.901378E+09 | 0.113029E+10 | 0.621721E+09 |
September | 0.750487E+09 | 176276.06 | 0.750310E+09 | 0.781715E+09 | 0.924022E+09 |
October | 0.555447E+09 | 0.00 | 0.555447E+09 | 0.197761E+09 | 0.207051E+10 |
November | 0.408053E+09 | 0.00 | 0.408053E+09 | 53021204.63 | 0.248658E+10 |
December | 0.356677E+09 | 0.00 | 0.356677E+09 | 23424953.76 | 0.317935E+10 |
Annual Sum or Average | 0.871754E+10 | 0.270060E+09 | 0.844748E+10 | 0.653114E+10 | 0.208412E+11 |
Minimum of Months | 0.356677E+09 | 0.00 | 0.356677E+09 | 22480556.72 | 0.535271E+09 |
Maximum of Months | 0.118693E+10 | 0.131591E+09 | 0.108485E+10 | 0.152179E+10 | 0.317935E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132639E+10 | 0.812851E+09 | 0.513537E+09 | 0.983848E+09 | 0.281440E+10 |
February | 0.159145E+10 | 0.100467E+10 | 0.586773E+09 | 0.130994E+10 | 0.263198E+10 |
March | 0.212664E+10 | 0.124045E+10 | 0.886188E+09 | 0.192641E+10 | 0.222921E+10 |
April | 0.211063E+10 | 0.102812E+10 | 0.108250E+10 | 0.185767E+10 | 0.192671E+10 |
May | 0.254953E+10 | 0.106495E+10 | 0.148458E+10 | 0.266198E+10 | 0.111446E+10 |
June | 0.301035E+10 | 0.158035E+10 | 0.142999E+10 | 0.399350E+10 | 0.575292E+09 |
July | 0.282787E+10 | 0.134656E+10 | 0.148131E+10 | 0.380117E+10 | 0.554297E+09 |
August | 0.285229E+10 | 0.157094E+10 | 0.128135E+10 | 0.379139E+10 | 0.625536E+09 |
September | 0.229669E+10 | 0.124763E+10 | 0.104907E+10 | 0.283814E+10 | 0.937827E+09 |
October | 0.171871E+10 | 0.941752E+09 | 0.776955E+09 | 0.163707E+10 | 0.216909E+10 |
November | 0.129464E+10 | 0.730966E+09 | 0.563673E+09 | 0.104216E+10 | 0.253454E+10 |
December | 0.115817E+10 | 0.667189E+09 | 0.490982E+09 | 0.811654E+09 | 0.322837E+10 |
Annual Sum or Average | 0.248634E+11 | 0.132364E+11 | 0.116269E+11 | 0.266549E+11 | 0.213417E+11 |
Minimum of Months | 0.115817E+10 | 0.667189E+09 | 0.490982E+09 | 0.811654E+09 | 0.554297E+09 |
Maximum of Months | 0.301035E+10 | 0.158035E+10 | 0.148458E+10 | 0.399350E+10 | 0.322837E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132639E+10 | 0.812851E+09 | 0.513537E+09 | 0.983848E+09 | 0.281440E+10 |
February | 0.159145E+10 | 0.100467E+10 | 0.586773E+09 | 0.130994E+10 | 0.263198E+10 |
March | 0.212664E+10 | 0.124045E+10 | 0.886188E+09 | 0.192641E+10 | 0.222921E+10 |
April | 0.211063E+10 | 0.102812E+10 | 0.108250E+10 | 0.185767E+10 | 0.192671E+10 |
May | 0.254953E+10 | 0.106495E+10 | 0.148458E+10 | 0.266198E+10 | 0.111446E+10 |
June | 0.301035E+10 | 0.158035E+10 | 0.142999E+10 | 0.399350E+10 | 0.575292E+09 |
July | 0.282787E+10 | 0.134656E+10 | 0.148131E+10 | 0.380117E+10 | 0.554297E+09 |
August | 0.285229E+10 | 0.157094E+10 | 0.128135E+10 | 0.379139E+10 | 0.625536E+09 |
September | 0.229669E+10 | 0.124763E+10 | 0.104907E+10 | 0.283814E+10 | 0.937827E+09 |
October | 0.171871E+10 | 0.941752E+09 | 0.776955E+09 | 0.163707E+10 | 0.216909E+10 |
November | 0.129464E+10 | 0.730966E+09 | 0.563673E+09 | 0.104216E+10 | 0.253454E+10 |
December | 0.115817E+10 | 0.667189E+09 | 0.490982E+09 | 0.811654E+09 | 0.322837E+10 |
Annual Sum or Average | 0.248634E+11 | 0.132364E+11 | 0.116269E+11 | 0.266549E+11 | 0.213417E+11 |
Minimum of Months | 0.115817E+10 | 0.667189E+09 | 0.490982E+09 | 0.811654E+09 | 0.554297E+09 |
Maximum of Months | 0.301035E+10 | 0.158035E+10 | 0.148458E+10 | 0.399350E+10 | 0.322837E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132636E+10 | 0.812836E+09 | 0.513528E+09 | 0.983830E+09 | 0.281435E+10 |
February | 0.159142E+10 | 0.100466E+10 | 0.586762E+09 | 0.130991E+10 | 0.263193E+10 |
March | 0.212660E+10 | 0.124043E+10 | 0.886172E+09 | 0.192638E+10 | 0.222917E+10 |
April | 0.211059E+10 | 0.102810E+10 | 0.108248E+10 | 0.185763E+10 | 0.192667E+10 |
May | 0.254949E+10 | 0.106493E+10 | 0.148456E+10 | 0.266193E+10 | 0.111444E+10 |
June | 0.301029E+10 | 0.158032E+10 | 0.142997E+10 | 0.399342E+10 | 0.575282E+09 |
July | 0.282781E+10 | 0.134654E+10 | 0.148128E+10 | 0.380110E+10 | 0.554287E+09 |
August | 0.285224E+10 | 0.157091E+10 | 0.128133E+10 | 0.379132E+10 | 0.625524E+09 |
September | 0.229665E+10 | 0.124761E+10 | 0.104905E+10 | 0.283809E+10 | 0.937810E+09 |
October | 0.171868E+10 | 0.941735E+09 | 0.776941E+09 | 0.163704E+10 | 0.216905E+10 |
November | 0.129462E+10 | 0.730953E+09 | 0.563662E+09 | 0.104214E+10 | 0.253449E+10 |
December | 0.115815E+10 | 0.667177E+09 | 0.490973E+09 | 0.811639E+09 | 0.322831E+10 |
Annual Sum or Average | 0.248629E+11 | 0.132362E+11 | 0.116267E+11 | 0.266544E+11 | 0.213413E+11 |
Minimum of Months | 0.115815E+10 | 0.667177E+09 | 0.490973E+09 | 0.811639E+09 | 0.554287E+09 |
Maximum of Months | 0.301029E+10 | 0.158032E+10 | 0.148456E+10 | 0.399342E+10 | 0.322831E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365369E+10 | 0.300555E+10 | 0.648136E+09 | 0.386737E+10 | 0.233933E+10 |
February | 0.316541E+10 | 0.252367E+10 | 0.641746E+09 | 0.329810E+10 | 0.221239E+10 |
March | 0.258384E+10 | 0.170002E+10 | 0.883818E+09 | 0.274043E+10 | 0.200858E+10 |
April | 0.161950E+10 | 0.651207E+09 | 0.968293E+09 | 0.151690E+10 | 0.180345E+10 |
May | 0.153356E+10 | 0.281091E+09 | 0.125247E+10 | 0.160408E+10 | 0.110546E+10 |
June | 0.136828E+10 | 0.250084E+09 | 0.111820E+10 | 0.195671E+10 | 0.584730E+09 |
July | 0.147183E+10 | 0.263564E+09 | 0.120827E+10 | 0.211572E+10 | 0.564625E+09 |
August | 0.187394E+10 | 0.783378E+09 | 0.109056E+10 | 0.268633E+10 | 0.635082E+09 |
September | 0.233323E+10 | 0.130193E+10 | 0.103130E+10 | 0.310608E+10 | 0.919773E+09 |
October | 0.288286E+10 | 0.204546E+10 | 0.837405E+09 | 0.332203E+10 | 0.194285E+10 |
November | 0.339906E+10 | 0.270955E+10 | 0.689516E+09 | 0.371173E+10 | 0.217173E+10 |
December | 0.335874E+10 | 0.271852E+10 | 0.640221E+09 | 0.346127E+10 | 0.267935E+10 |
Annual Sum or Average | 0.292440E+11 | 0.182340E+11 | 0.110099E+11 | 0.333867E+11 | 0.189673E+11 |
Minimum of Months | 0.136828E+10 | 0.250084E+09 | 0.640221E+09 | 0.151690E+10 | 0.564625E+09 |
Maximum of Months | 0.365369E+10 | 0.300555E+10 | 0.125247E+10 | 0.386737E+10 | 0.267935E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365368E+10 | 0.300555E+10 | 0.648135E+09 | 0.386737E+10 | 0.233933E+10 |
February | 0.316541E+10 | 0.252367E+10 | 0.641745E+09 | 0.329809E+10 | 0.221239E+10 |
March | 0.258383E+10 | 0.170002E+10 | 0.883817E+09 | 0.274043E+10 | 0.200858E+10 |
April | 0.161950E+10 | 0.651207E+09 | 0.968292E+09 | 0.151690E+10 | 0.180345E+10 |
May | 0.153356E+10 | 0.281091E+09 | 0.125247E+10 | 0.160408E+10 | 0.110546E+10 |
June | 0.136828E+10 | 0.250084E+09 | 0.111820E+10 | 0.195671E+10 | 0.584730E+09 |
July | 0.147183E+10 | 0.263564E+09 | 0.120827E+10 | 0.211572E+10 | 0.564625E+09 |
August | 0.187394E+10 | 0.783377E+09 | 0.109056E+10 | 0.268633E+10 | 0.635082E+09 |
September | 0.233323E+10 | 0.130193E+10 | 0.103130E+10 | 0.310608E+10 | 0.919773E+09 |
October | 0.288286E+10 | 0.204545E+10 | 0.837405E+09 | 0.332202E+10 | 0.194285E+10 |
November | 0.339906E+10 | 0.270954E+10 | 0.689516E+09 | 0.371172E+10 | 0.217173E+10 |
December | 0.335873E+10 | 0.271851E+10 | 0.640220E+09 | 0.346127E+10 | 0.267935E+10 |
Annual Sum or Average | 0.292439E+11 | 0.182340E+11 | 0.110099E+11 | 0.333867E+11 | 0.189673E+11 |
Minimum of Months | 0.136828E+10 | 0.250084E+09 | 0.640220E+09 | 0.151690E+10 | 0.564625E+09 |
Maximum of Months | 0.365368E+10 | 0.300555E+10 | 0.125247E+10 | 0.386737E+10 | 0.267935E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365369E+10 | 0.300555E+10 | 0.648136E+09 | 0.386737E+10 | 0.233933E+10 |
February | 0.316541E+10 | 0.252367E+10 | 0.641746E+09 | 0.329810E+10 | 0.221239E+10 |
March | 0.258384E+10 | 0.170002E+10 | 0.883818E+09 | 0.274043E+10 | 0.200858E+10 |
April | 0.161950E+10 | 0.651207E+09 | 0.968293E+09 | 0.151690E+10 | 0.180345E+10 |
May | 0.153356E+10 | 0.281091E+09 | 0.125247E+10 | 0.160408E+10 | 0.110546E+10 |
June | 0.136828E+10 | 0.250084E+09 | 0.111820E+10 | 0.195671E+10 | 0.584730E+09 |
July | 0.147183E+10 | 0.263564E+09 | 0.120827E+10 | 0.211572E+10 | 0.564625E+09 |
August | 0.187394E+10 | 0.783378E+09 | 0.109056E+10 | 0.268633E+10 | 0.635082E+09 |
September | 0.233323E+10 | 0.130193E+10 | 0.103130E+10 | 0.310608E+10 | 0.919773E+09 |
October | 0.288286E+10 | 0.204546E+10 | 0.837405E+09 | 0.332203E+10 | 0.194285E+10 |
November | 0.339906E+10 | 0.270955E+10 | 0.689516E+09 | 0.371173E+10 | 0.217173E+10 |
December | 0.335874E+10 | 0.271852E+10 | 0.640221E+09 | 0.346127E+10 | 0.267935E+10 |
Annual Sum or Average | 0.292440E+11 | 0.182340E+11 | 0.110099E+11 | 0.333867E+11 | 0.189673E+11 |
Minimum of Months | 0.136828E+10 | 0.250084E+09 | 0.640221E+09 | 0.151690E+10 | 0.564625E+09 |
Maximum of Months | 0.365369E+10 | 0.300555E+10 | 0.125247E+10 | 0.386737E+10 | 0.267935E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365368E+10 | 0.300555E+10 | 0.648135E+09 | 0.386737E+10 | 0.233933E+10 |
February | 0.316541E+10 | 0.252367E+10 | 0.641745E+09 | 0.329809E+10 | 0.221239E+10 |
March | 0.258383E+10 | 0.170002E+10 | 0.883817E+09 | 0.274043E+10 | 0.200858E+10 |
April | 0.161950E+10 | 0.651207E+09 | 0.968292E+09 | 0.151690E+10 | 0.180345E+10 |
May | 0.153356E+10 | 0.281091E+09 | 0.125247E+10 | 0.160408E+10 | 0.110546E+10 |
June | 0.136828E+10 | 0.250084E+09 | 0.111820E+10 | 0.195671E+10 | 0.584730E+09 |
July | 0.147183E+10 | 0.263564E+09 | 0.120827E+10 | 0.211572E+10 | 0.564625E+09 |
August | 0.187394E+10 | 0.783377E+09 | 0.109056E+10 | 0.268633E+10 | 0.635082E+09 |
September | 0.233323E+10 | 0.130193E+10 | 0.103130E+10 | 0.310608E+10 | 0.919773E+09 |
October | 0.288286E+10 | 0.204545E+10 | 0.837405E+09 | 0.332202E+10 | 0.194285E+10 |
November | 0.339906E+10 | 0.270954E+10 | 0.689516E+09 | 0.371172E+10 | 0.217173E+10 |
December | 0.335873E+10 | 0.271851E+10 | 0.640220E+09 | 0.346127E+10 | 0.267935E+10 |
Annual Sum or Average | 0.292439E+11 | 0.182340E+11 | 0.110099E+11 | 0.333867E+11 | 0.189673E+11 |
Minimum of Months | 0.136828E+10 | 0.250084E+09 | 0.640220E+09 | 0.151690E+10 | 0.564625E+09 |
Maximum of Months | 0.365368E+10 | 0.300555E+10 | 0.125247E+10 | 0.386737E+10 | 0.267935E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365354E+10 | 0.300543E+10 | 0.648110E+09 | 0.386722E+10 | 0.233924E+10 |
February | 0.316529E+10 | 0.252357E+10 | 0.641720E+09 | 0.329796E+10 | 0.221230E+10 |
March | 0.258373E+10 | 0.169995E+10 | 0.883782E+09 | 0.274032E+10 | 0.200850E+10 |
April | 0.161944E+10 | 0.651181E+09 | 0.968254E+09 | 0.151684E+10 | 0.180337E+10 |
May | 0.153350E+10 | 0.281080E+09 | 0.125242E+10 | 0.160402E+10 | 0.110542E+10 |
June | 0.136823E+10 | 0.250074E+09 | 0.111816E+10 | 0.195663E+10 | 0.584707E+09 |
July | 0.147177E+10 | 0.263553E+09 | 0.120822E+10 | 0.211563E+10 | 0.564602E+09 |
August | 0.187387E+10 | 0.783346E+09 | 0.109052E+10 | 0.268622E+10 | 0.635057E+09 |
September | 0.233314E+10 | 0.130188E+10 | 0.103126E+10 | 0.310596E+10 | 0.919736E+09 |
October | 0.288274E+10 | 0.204537E+10 | 0.837372E+09 | 0.332189E+10 | 0.194277E+10 |
November | 0.339893E+10 | 0.270944E+10 | 0.689489E+09 | 0.371158E+10 | 0.217164E+10 |
December | 0.335860E+10 | 0.271841E+10 | 0.640195E+09 | 0.346113E+10 | 0.267924E+10 |
Annual Sum or Average | 0.292428E+11 | 0.182333E+11 | 0.110095E+11 | 0.333854E+11 | 0.189666E+11 |
Minimum of Months | 0.136823E+10 | 0.250074E+09 | 0.640195E+09 | 0.151684E+10 | 0.564602E+09 |
Maximum of Months | 0.365354E+10 | 0.300543E+10 | 0.125242E+10 | 0.386722E+10 | 0.267924E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141098E+10 | 0.894074E+09 | 0.516906E+09 | 0.116549E+10 | 0.301482E+10 |
February | 0.153679E+10 | 0.952353E+09 | 0.584434E+09 | 0.127016E+10 | 0.279143E+10 |
March | 0.199228E+10 | 0.109918E+10 | 0.893094E+09 | 0.176961E+10 | 0.246892E+10 |
April | 0.181531E+10 | 0.768573E+09 | 0.104674E+10 | 0.148868E+10 | 0.221243E+10 |
May | 0.229274E+10 | 0.808275E+09 | 0.148446E+10 | 0.238364E+10 | 0.128999E+10 |
June | 0.271370E+10 | 0.130567E+10 | 0.140803E+10 | 0.363481E+10 | 0.744006E+09 |
July | 0.228472E+10 | 0.836852E+09 | 0.144787E+10 | 0.304031E+10 | 0.737594E+09 |
August | 0.238460E+10 | 0.117803E+10 | 0.120658E+10 | 0.309718E+10 | 0.841258E+09 |
September | 0.204622E+10 | 0.981300E+09 | 0.106492E+10 | 0.254099E+10 | 0.110283E+10 |
October | 0.177880E+10 | 0.101671E+10 | 0.762081E+09 | 0.177393E+10 | 0.234213E+10 |
November | 0.141251E+10 | 0.857570E+09 | 0.554942E+09 | 0.120477E+10 | 0.276360E+10 |
December | 0.117895E+10 | 0.696440E+09 | 0.482514E+09 | 0.849826E+09 | 0.350670E+10 |
Annual Sum or Average | 0.228476E+11 | 0.113950E+11 | 0.114526E+11 | 0.242194E+11 | 0.238157E+11 |
Minimum of Months | 0.117895E+10 | 0.696440E+09 | 0.482514E+09 | 0.849826E+09 | 0.737594E+09 |
Maximum of Months | 0.271370E+10 | 0.130567E+10 | 0.148446E+10 | 0.363481E+10 | 0.350670E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141098E+10 | 0.894074E+09 | 0.516906E+09 | 0.116549E+10 | 0.301482E+10 |
February | 0.153679E+10 | 0.952353E+09 | 0.584434E+09 | 0.127016E+10 | 0.279143E+10 |
March | 0.199228E+10 | 0.109918E+10 | 0.893094E+09 | 0.176961E+10 | 0.246892E+10 |
April | 0.181531E+10 | 0.768573E+09 | 0.104674E+10 | 0.148868E+10 | 0.221243E+10 |
May | 0.229274E+10 | 0.808275E+09 | 0.148446E+10 | 0.238364E+10 | 0.128999E+10 |
June | 0.271370E+10 | 0.130567E+10 | 0.140803E+10 | 0.363481E+10 | 0.744006E+09 |
July | 0.228472E+10 | 0.836852E+09 | 0.144787E+10 | 0.304031E+10 | 0.737594E+09 |
August | 0.238460E+10 | 0.117803E+10 | 0.120658E+10 | 0.309718E+10 | 0.841258E+09 |
September | 0.204622E+10 | 0.981300E+09 | 0.106492E+10 | 0.254099E+10 | 0.110283E+10 |
October | 0.177880E+10 | 0.101671E+10 | 0.762081E+09 | 0.177393E+10 | 0.234213E+10 |
November | 0.141251E+10 | 0.857570E+09 | 0.554942E+09 | 0.120477E+10 | 0.276360E+10 |
December | 0.117895E+10 | 0.696440E+09 | 0.482514E+09 | 0.849826E+09 | 0.350670E+10 |
Annual Sum or Average | 0.228476E+11 | 0.113950E+11 | 0.114526E+11 | 0.242194E+11 | 0.238157E+11 |
Minimum of Months | 0.117895E+10 | 0.696440E+09 | 0.482514E+09 | 0.849826E+09 | 0.737594E+09 |
Maximum of Months | 0.271370E+10 | 0.130567E+10 | 0.148446E+10 | 0.363481E+10 | 0.350670E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141095E+10 | 0.894058E+09 | 0.516897E+09 | 0.116547E+10 | 0.301476E+10 |
February | 0.153676E+10 | 0.952336E+09 | 0.584423E+09 | 0.127014E+10 | 0.279138E+10 |
March | 0.199224E+10 | 0.109916E+10 | 0.893078E+09 | 0.176958E+10 | 0.246888E+10 |
April | 0.181528E+10 | 0.768558E+09 | 0.104672E+10 | 0.148865E+10 | 0.221239E+10 |
May | 0.229269E+10 | 0.808260E+09 | 0.148443E+10 | 0.238359E+10 | 0.128996E+10 |
June | 0.271365E+10 | 0.130564E+10 | 0.140801E+10 | 0.363474E+10 | 0.743993E+09 |
July | 0.228468E+10 | 0.836837E+09 | 0.144785E+10 | 0.304025E+10 | 0.737581E+09 |
August | 0.238456E+10 | 0.117801E+10 | 0.120655E+10 | 0.309713E+10 | 0.841242E+09 |
September | 0.204618E+10 | 0.981282E+09 | 0.106490E+10 | 0.254094E+10 | 0.110281E+10 |
October | 0.177876E+10 | 0.101670E+10 | 0.762067E+09 | 0.177390E+10 | 0.234209E+10 |
November | 0.141249E+10 | 0.857554E+09 | 0.554932E+09 | 0.120474E+10 | 0.276355E+10 |
December | 0.117893E+10 | 0.696427E+09 | 0.482506E+09 | 0.849810E+09 | 0.350664E+10 |
Annual Sum or Average | 0.228472E+11 | 0.113948E+11 | 0.114524E+11 | 0.242189E+11 | 0.238153E+11 |
Minimum of Months | 0.117893E+10 | 0.696427E+09 | 0.482506E+09 | 0.849810E+09 | 0.737581E+09 |
Maximum of Months | 0.271365E+10 | 0.130564E+10 | 0.148443E+10 | 0.363474E+10 | 0.350664E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190614E+10 | 0.00 | 0.190614E+10 | 0.180599E+09 | 0.129185E+11 |
February | 0.216394E+10 | 0.00 | 0.216394E+10 | 0.215031E+09 | 0.120314E+11 |
March | 0.325989E+10 | 0.00 | 0.325989E+10 | 0.998436E+09 | 0.100678E+11 |
April | 0.396189E+10 | 21978847.02 | 0.393991E+10 | 0.154440E+10 | 0.843551E+10 |
May | 0.559259E+10 | 0.184868E+09 | 0.540772E+10 | 0.428083E+10 | 0.491641E+10 |
June | 0.593483E+10 | 0.657972E+09 | 0.527685E+10 | 0.775264E+10 | 0.255557E+10 |
July | 0.579982E+10 | 0.375433E+09 | 0.542439E+10 | 0.774083E+10 | 0.250484E+10 |
August | 0.461622E+10 | 0.109204E+09 | 0.450702E+10 | 0.584543E+10 | 0.285738E+10 |
September | 0.375254E+10 | 881405.17 | 0.375166E+10 | 0.410826E+10 | 0.422911E+10 |
October | 0.277731E+10 | 0.00 | 0.277731E+10 | 0.119420E+10 | 0.953603E+10 |
November | 0.204032E+10 | 0.00 | 0.204032E+10 | 0.369370E+09 | 0.113424E+11 |
December | 0.178344E+10 | 0.00 | 0.178344E+10 | 0.194867E+09 | 0.146596E+11 |
Annual Sum or Average | 0.435889E+11 | 0.135034E+10 | 0.422386E+11 | 0.344249E+11 | 0.960545E+11 |
Minimum of Months | 0.178344E+10 | 0.00 | 0.178344E+10 | 0.180599E+09 | 0.250484E+10 |
Maximum of Months | 0.593483E+10 | 0.657972E+09 | 0.542439E+10 | 0.775264E+10 | 0.146596E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.397912E+10 | 0.243853E+10 | 0.154060E+10 | 0.300204E+10 | 0.801029E+10 |
February | 0.477429E+10 | 0.301399E+10 | 0.176030E+10 | 0.392981E+10 | 0.760591E+10 |
March | 0.637985E+10 | 0.372131E+10 | 0.265854E+10 | 0.573990E+10 | 0.639571E+10 |
April | 0.633182E+10 | 0.308434E+10 | 0.324748E+10 | 0.552235E+10 | 0.540942E+10 |
May | 0.764852E+10 | 0.319482E+10 | 0.445370E+10 | 0.790641E+10 | 0.324074E+10 |
June | 0.903095E+10 | 0.474101E+10 | 0.428994E+10 | 0.118811E+11 | 0.167265E+10 |
July | 0.848351E+10 | 0.403964E+10 | 0.444387E+10 | 0.113066E+11 | 0.165418E+10 |
August | 0.855679E+10 | 0.471277E+10 | 0.384402E+10 | 0.112797E+11 | 0.187164E+10 |
September | 0.689001E+10 | 0.374285E+10 | 0.314716E+10 | 0.846429E+10 | 0.268149E+10 |
October | 0.515607E+10 | 0.282523E+10 | 0.233084E+10 | 0.488495E+10 | 0.619617E+10 |
November | 0.388388E+10 | 0.219288E+10 | 0.169100E+10 | 0.315915E+10 | 0.722948E+10 |
December | 0.347448E+10 | 0.200155E+10 | 0.147293E+10 | 0.249097E+10 | 0.919828E+10 |
Annual Sum or Average | 0.745893E+11 | 0.397089E+11 | 0.348804E+11 | 0.795672E+11 | 0.611660E+11 |
Minimum of Months | 0.347448E+10 | 0.200155E+10 | 0.147293E+10 | 0.249097E+10 | 0.165418E+10 |
Maximum of Months | 0.903095E+10 | 0.474101E+10 | 0.445370E+10 | 0.118811E+11 | 0.919828E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182682E+11 | 0.150276E+11 | 0.324064E+10 | 0.191427E+11 | 0.116254E+11 |
February | 0.158269E+11 | 0.126182E+11 | 0.320869E+10 | 0.162435E+11 | 0.110195E+11 |
March | 0.129190E+11 | 0.849998E+10 | 0.441904E+10 | 0.135357E+11 | 0.987290E+10 |
April | 0.809740E+10 | 0.325600E+10 | 0.484141E+10 | 0.752274E+10 | 0.867232E+10 |
May | 0.766772E+10 | 0.140544E+10 | 0.626229E+10 | 0.796658E+10 | 0.545988E+10 |
June | 0.684134E+10 | 0.125041E+10 | 0.559094E+10 | 0.979484E+10 | 0.282996E+10 |
July | 0.735907E+10 | 0.131780E+10 | 0.604126E+10 | 0.106013E+11 | 0.274561E+10 |
August | 0.936959E+10 | 0.391684E+10 | 0.545275E+10 | 0.134053E+11 | 0.309245E+10 |
September | 0.116660E+11 | 0.650958E+10 | 0.515645E+10 | 0.154097E+11 | 0.452024E+10 |
October | 0.144141E+11 | 0.102272E+11 | 0.418698E+10 | 0.164390E+11 | 0.962258E+10 |
November | 0.169951E+11 | 0.135476E+11 | 0.344754E+10 | 0.183503E+11 | 0.107663E+11 |
December | 0.167935E+11 | 0.135924E+11 | 0.320107E+10 | 0.171528E+11 | 0.131620E+11 |
Annual Sum or Average | 0.146218E+12 | 0.911690E+11 | 0.550490E+11 | 0.165565E+12 | 0.933891E+11 |
Minimum of Months | 0.684134E+10 | 0.125041E+10 | 0.320107E+10 | 0.752274E+10 | 0.274561E+10 |
Maximum of Months | 0.182682E+11 | 0.150276E+11 | 0.626229E+10 | 0.191427E+11 | 0.131620E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.423290E+10 | 0.268219E+10 | 0.155070E+10 | 0.358821E+10 | 0.835705E+10 |
February | 0.461031E+10 | 0.285703E+10 | 0.175328E+10 | 0.386966E+10 | 0.782772E+10 |
March | 0.597678E+10 | 0.329752E+10 | 0.267926E+10 | 0.543286E+10 | 0.672057E+10 |
April | 0.544588E+10 | 0.230569E+10 | 0.314019E+10 | 0.463345E+10 | 0.572180E+10 |
May | 0.687814E+10 | 0.242480E+10 | 0.445334E+10 | 0.726269E+10 | 0.359242E+10 |
June | 0.814102E+10 | 0.391696E+10 | 0.422406E+10 | 0.110239E+11 | 0.201989E+10 |
July | 0.685410E+10 | 0.251053E+10 | 0.434357E+10 | 0.933964E+10 | 0.190521E+10 |
August | 0.715374E+10 | 0.353405E+10 | 0.361969E+10 | 0.955343E+10 | 0.212819E+10 |
September | 0.613860E+10 | 0.294387E+10 | 0.319473E+10 | 0.775485E+10 | 0.300958E+10 |
October | 0.533633E+10 | 0.305011E+10 | 0.228622E+10 | 0.542578E+10 | 0.647591E+10 |
November | 0.423749E+10 | 0.257268E+10 | 0.166481E+10 | 0.374847E+10 | 0.748715E+10 |
December | 0.353683E+10 | 0.208930E+10 | 0.144753E+10 | 0.268491E+10 | 0.941411E+10 |
Annual Sum or Average | 0.685421E+11 | 0.341847E+11 | 0.343574E+11 | 0.743178E+11 | 0.646596E+11 |
Minimum of Months | 0.353683E+10 | 0.208930E+10 | 0.144753E+10 | 0.268491E+10 | 0.190521E+10 |
Maximum of Months | 0.814102E+10 | 0.391696E+10 | 0.445334E+10 | 0.110239E+11 | 0.941411E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190614E+10 | 0.00 | 0.190614E+10 | 0.225325E+09 | 0.120750E+11 |
February | 0.216394E+10 | 0.00 | 0.216394E+10 | 0.257653E+09 | 0.113595E+11 |
March | 0.325989E+10 | 0.00 | 0.325989E+10 | 0.106688E+10 | 0.942471E+10 |
April | 0.396189E+10 | 21978847.02 | 0.393991E+10 | 0.160903E+10 | 0.768895E+10 |
May | 0.559259E+10 | 0.184868E+09 | 0.540772E+10 | 0.446689E+10 | 0.450309E+10 |
June | 0.593483E+10 | 0.657972E+09 | 0.527685E+10 | 0.779621E+10 | 0.241200E+10 |
July | 0.579982E+10 | 0.375433E+09 | 0.542439E+10 | 0.778099E+10 | 0.237482E+10 |
August | 0.461622E+10 | 0.109204E+09 | 0.450702E+10 | 0.589471E+10 | 0.267210E+10 |
September | 0.375254E+10 | 881405.17 | 0.375166E+10 | 0.421699E+10 | 0.386486E+10 |
October | 0.277731E+10 | 0.00 | 0.277731E+10 | 0.130885E+10 | 0.873456E+10 |
November | 0.204032E+10 | 0.00 | 0.204032E+10 | 0.446751E+09 | 0.104149E+11 |
December | 0.178344E+10 | 0.00 | 0.178344E+10 | 0.238017E+09 | 0.138916E+11 |
Annual Sum or Average | 0.435889E+11 | 0.135034E+10 | 0.422386E+11 | 0.353083E+11 | 0.894161E+11 |
Minimum of Months | 0.178344E+10 | 0.00 | 0.178344E+10 | 0.225325E+09 | 0.237482E+10 |
Maximum of Months | 0.593483E+10 | 0.657972E+09 | 0.542439E+10 | 0.779621E+10 | 0.138916E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.397912E+10 | 0.243853E+10 | 0.154060E+10 | 0.314054E+10 | 0.744759E+10 |
February | 0.477429E+10 | 0.301399E+10 | 0.176030E+10 | 0.402826E+10 | 0.716264E+10 |
March | 0.637985E+10 | 0.372131E+10 | 0.265854E+10 | 0.582293E+10 | 0.599849E+10 |
April | 0.633182E+10 | 0.308434E+10 | 0.324748E+10 | 0.559879E+10 | 0.496440E+10 |
May | 0.764852E+10 | 0.319482E+10 | 0.445370E+10 | 0.800437E+10 | 0.303631E+10 |
June | 0.903095E+10 | 0.474101E+10 | 0.428994E+10 | 0.118444E+11 | 0.161686E+10 |
July | 0.848351E+10 | 0.403964E+10 | 0.444387E+10 | 0.112732E+11 | 0.160799E+10 |
August | 0.855679E+10 | 0.471277E+10 | 0.384402E+10 | 0.112539E+11 | 0.180308E+10 |
September | 0.689001E+10 | 0.374285E+10 | 0.314716E+10 | 0.850319E+10 | 0.251410E+10 |
October | 0.515607E+10 | 0.282523E+10 | 0.233084E+10 | 0.500121E+10 | 0.572452E+10 |
November | 0.388388E+10 | 0.219288E+10 | 0.169100E+10 | 0.329746E+10 | 0.665319E+10 |
December | 0.347448E+10 | 0.200155E+10 | 0.147293E+10 | 0.259701E+10 | 0.869649E+10 |
Annual Sum or Average | 0.745893E+11 | 0.397089E+11 | 0.348804E+11 | 0.803653E+11 | 0.572257E+11 |
Minimum of Months | 0.347448E+10 | 0.200155E+10 | 0.147293E+10 | 0.259701E+10 | 0.160799E+10 |
Maximum of Months | 0.903095E+10 | 0.474101E+10 | 0.445370E+10 | 0.118444E+11 | 0.869649E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182682E+11 | 0.150276E+11 | 0.324064E+10 | 0.193737E+11 | 0.107454E+11 |
February | 0.158269E+11 | 0.126182E+11 | 0.320869E+10 | 0.163626E+11 | 0.103470E+11 |
March | 0.129190E+11 | 0.849998E+10 | 0.441904E+10 | 0.136220E+11 | 0.922441E+10 |
April | 0.809740E+10 | 0.325600E+10 | 0.484141E+10 | 0.757079E+10 | 0.793396E+10 |
May | 0.766772E+10 | 0.140544E+10 | 0.626229E+10 | 0.807252E+10 | 0.503822E+10 |
June | 0.684134E+10 | 0.125041E+10 | 0.559094E+10 | 0.978113E+10 | 0.266865E+10 |
July | 0.735907E+10 | 0.131780E+10 | 0.604126E+10 | 0.105956E+11 | 0.260082E+10 |
August | 0.936959E+10 | 0.391684E+10 | 0.545275E+10 | 0.133904E+11 | 0.290759E+10 |
September | 0.116660E+11 | 0.650958E+10 | 0.515645E+10 | 0.154484E+11 | 0.418186E+10 |
October | 0.144141E+11 | 0.102272E+11 | 0.418698E+10 | 0.165492E+11 | 0.884733E+10 |
November | 0.169951E+11 | 0.135476E+11 | 0.344754E+10 | 0.185395E+11 | 0.991250E+10 |
December | 0.167935E+11 | 0.135924E+11 | 0.320107E+10 | 0.173338E+11 | 0.123563E+11 |
Annual Sum or Average | 0.146218E+12 | 0.911690E+11 | 0.550490E+11 | 0.166640E+12 | 0.867641E+11 |
Minimum of Months | 0.684134E+10 | 0.125041E+10 | 0.320107E+10 | 0.757079E+10 | 0.260082E+10 |
Maximum of Months | 0.182682E+11 | 0.150276E+11 | 0.626229E+10 | 0.193737E+11 | 0.123563E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.423290E+10 | 0.268219E+10 | 0.155070E+10 | 0.362588E+10 | 0.784997E+10 |
February | 0.461031E+10 | 0.285703E+10 | 0.175328E+10 | 0.387892E+10 | 0.743540E+10 |
March | 0.597678E+10 | 0.329752E+10 | 0.267926E+10 | 0.542814E+10 | 0.635596E+10 |
April | 0.544588E+10 | 0.230569E+10 | 0.314019E+10 | 0.462741E+10 | 0.529927E+10 |
May | 0.687814E+10 | 0.242480E+10 | 0.445334E+10 | 0.727313E+10 | 0.337043E+10 |
June | 0.814102E+10 | 0.391696E+10 | 0.422406E+10 | 0.109754E+11 | 0.193556E+10 |
July | 0.685410E+10 | 0.251053E+10 | 0.434357E+10 | 0.929840E+10 | 0.183400E+10 |
August | 0.715374E+10 | 0.353405E+10 | 0.361969E+10 | 0.951754E+10 | 0.203879E+10 |
September | 0.613860E+10 | 0.294387E+10 | 0.319473E+10 | 0.774954E+10 | 0.282880E+10 |
October | 0.533633E+10 | 0.305011E+10 | 0.228622E+10 | 0.544271E+10 | 0.603879E+10 |
November | 0.423749E+10 | 0.257268E+10 | 0.166481E+10 | 0.378307E+10 | 0.697773E+10 |
December | 0.353683E+10 | 0.208930E+10 | 0.144753E+10 | 0.271335E+10 | 0.896329E+10 |
Annual Sum or Average | 0.685421E+11 | 0.341847E+11 | 0.343574E+11 | 0.743135E+11 | 0.609280E+11 |
Minimum of Months | 0.353683E+10 | 0.208930E+10 | 0.144753E+10 | 0.271335E+10 | 0.183400E+10 |
Maximum of Months | 0.814102E+10 | 0.391696E+10 | 0.445334E+10 | 0.109754E+11 | 0.896329E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 41.97 | 5234.25 | 711.68 | 0.00 | 711.68 | 0.00 | 0.00 |
February | 62.47 | 5311.93 | 894.49 | 0.00 | 894.49 | 0.00 | 0.00 |
March | 306.40 | 4078.03 | 1217.11 | 0.00 | 1217.11 | 0.00 | 0.00 |
April | 523.49 | 3617.52 | 1528.51 | 8.48 | 1520.03 | 0.00 | 0.00 |
May | 1532.23 | 1956.77 | 2088.04 | 69.02 | 2019.02 | 0.00 | 0.00 |
June | 2935.64 | 1045.54 | 2289.68 | 253.85 | 2035.83 | 0.00 | 0.00 |
July | 2826.73 | 999.27 | 2165.41 | 140.17 | 2025.24 | 0.00 | 0.00 |
August | 2110.07 | 1160.66 | 1723.51 | 40.77 | 1682.73 | 0.00 | 0.00 |
September | 1507.99 | 1782.51 | 1447.74 | 0.34 | 1447.40 | 0.00 | 0.00 |
October | 369.19 | 3865.33 | 1036.93 | 0.00 | 1036.93 | 0.00 | 0.00 |
November | 102.28 | 4796.80 | 787.16 | 0.00 | 787.16 | 0.00 | 0.00 |
December | 43.73 | 5935.35 | 665.86 | 0.00 | 665.86 | 0.00 | 0.00 |
Annual Sum or Average | 1035.54 | 3304.45 | 1382.20 | 42.82 | 1339.38 | 0.00 | 0.00 |
Minimum of Months | 41.97 | 999.27 | 665.86 | 0.00 | 665.86 | 0.00 | 0.00 |
Maximum of Months | 2935.64 | 5935.35 | 2289.68 | 253.85 | 2035.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1101.97 | 3152.31 | 1485.64 | 910.45 | 575.20 | 0.00 | 0.00 |
February | 1624.42 | 3263.84 | 1973.51 | 1245.87 | 727.64 | 0.00 | 0.00 |
March | 2157.70 | 2496.86 | 2381.97 | 1389.38 | 992.59 | 0.00 | 0.00 |
April | 2150.07 | 2229.97 | 2442.84 | 1189.95 | 1252.89 | 0.00 | 0.00 |
May | 2981.59 | 1248.26 | 2855.64 | 1192.81 | 1662.83 | 0.00 | 0.00 |
June | 4622.07 | 665.84 | 3484.18 | 1829.10 | 1655.08 | 0.00 | 0.00 |
July | 4257.56 | 620.85 | 3167.39 | 1508.24 | 1659.16 | 0.00 | 0.00 |
August | 4246.60 | 700.64 | 3194.75 | 1759.55 | 1435.20 | 0.00 | 0.00 |
September | 3284.86 | 1085.44 | 2658.20 | 1444.01 | 1214.19 | 0.00 | 0.00 |
October | 1833.63 | 2429.52 | 1925.06 | 1054.82 | 870.24 | 0.00 | 0.00 |
November | 1206.20 | 2933.47 | 1498.42 | 846.02 | 652.40 | 0.00 | 0.00 |
December | 909.10 | 3615.98 | 1297.23 | 747.30 | 549.93 | 0.00 | 0.00 |
Annual Sum or Average | 2535.65 | 2030.21 | 2365.22 | 1259.17 | 1106.05 | 0.00 | 0.00 |
Minimum of Months | 909.10 | 620.85 | 1297.23 | 747.30 | 549.93 | 0.00 | 0.00 |
Maximum of Months | 4622.07 | 3615.98 | 3484.18 | 1829.10 | 1662.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7219.50 | 4367.00 | 6820.60 | 5610.68 | 1209.92 | 0.00 | 0.00 |
February | 6816.45 | 4572.53 | 6542.22 | 5215.87 | 1326.35 | 0.00 | 0.00 |
March | 5115.75 | 3749.57 | 4823.43 | 3173.54 | 1649.89 | 0.00 | 0.00 |
April | 2926.09 | 3478.84 | 3124.01 | 1256.18 | 1867.83 | 0.00 | 0.00 |
May | 2994.45 | 2063.65 | 2862.81 | 524.73 | 2338.08 | 0.00 | 0.00 |
June | 3774.49 | 1127.94 | 2639.42 | 482.41 | 2157.00 | 0.00 | 0.00 |
July | 3949.56 | 1054.03 | 2747.57 | 492.01 | 2255.56 | 0.00 | 0.00 |
August | 5014.76 | 1185.55 | 3498.22 | 1462.39 | 2035.83 | 0.00 | 0.00 |
September | 5991.62 | 1774.24 | 4500.80 | 2511.42 | 1989.38 | 0.00 | 0.00 |
October | 6201.46 | 3626.85 | 5381.64 | 3818.40 | 1563.24 | 0.00 | 0.00 |
November | 7159.90 | 4189.25 | 6556.78 | 5226.70 | 1330.07 | 0.00 | 0.00 |
December | 6461.40 | 5001.73 | 6269.99 | 5074.84 | 1195.15 | 0.00 | 0.00 |
Annual Sum or Average | 5293.39 | 3007.23 | 4636.56 | 2890.96 | 1745.60 | 0.00 | 0.00 |
Minimum of Months | 2926.09 | 1054.03 | 2639.42 | 482.41 | 1195.15 | 0.00 | 0.00 |
Maximum of Months | 7219.50 | 5001.73 | 6820.60 | 5610.68 | 2338.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1305.43 | 3376.79 | 1580.39 | 1001.42 | 578.97 | 0.00 | 0.00 |
February | 1575.09 | 3461.58 | 1905.73 | 1180.99 | 724.74 | 0.00 | 0.00 |
March | 1982.08 | 2765.36 | 2231.48 | 1231.16 | 1000.32 | 0.00 | 0.00 |
April | 1722.99 | 2560.67 | 2101.04 | 889.55 | 1211.50 | 0.00 | 0.00 |
May | 2669.83 | 1444.87 | 2568.01 | 905.32 | 1662.69 | 0.00 | 0.00 |
June | 4206.92 | 861.11 | 3140.84 | 1511.18 | 1629.66 | 0.00 | 0.00 |
July | 3405.34 | 826.15 | 2559.04 | 937.33 | 1621.71 | 0.00 | 0.00 |
August | 3469.04 | 942.26 | 2670.91 | 1319.47 | 1351.44 | 0.00 | 0.00 |
September | 2940.94 | 1276.41 | 2368.30 | 1135.76 | 1232.54 | 0.00 | 0.00 |
October | 1986.92 | 2623.34 | 1992.37 | 1138.79 | 853.58 | 0.00 | 0.00 |
November | 1394.40 | 3198.59 | 1634.84 | 992.55 | 642.29 | 0.00 | 0.00 |
December | 951.86 | 3927.73 | 1320.51 | 780.06 | 540.45 | 0.00 | 0.00 |
Annual Sum or Average | 2303.96 | 2265.56 | 2173.47 | 1084.00 | 1089.47 | 0.00 | 0.00 |
Minimum of Months | 951.86 | 826.15 | 1320.51 | 780.06 | 540.45 | 0.00 | 0.00 |
Maximum of Months | 4206.92 | 3927.73 | 3140.84 | 1511.18 | 1662.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 67.43 | 4823.23 | 711.67 | 0.00 | 711.67 | 0.00 | 0.00 |
February | 88.89 | 4973.29 | 894.49 | 0.00 | 894.49 | 0.00 | 0.00 |
March | 372.77 | 3758.87 | 1217.10 | 0.00 | 1217.10 | 0.00 | 0.00 |
April | 595.84 | 3254.44 | 1528.51 | 8.48 | 1520.03 | 0.00 | 0.00 |
May | 1598.28 | 1835.58 | 2088.03 | 69.02 | 2019.01 | 0.00 | 0.00 |
June | 2990.99 | 985.94 | 2289.67 | 253.85 | 2035.82 | 0.00 | 0.00 |
July | 2890.10 | 935.20 | 2165.41 | 140.17 | 2025.24 | 0.00 | 0.00 |
August | 2182.43 | 1066.82 | 1723.50 | 40.77 | 1682.73 | 0.00 | 0.00 |
September | 1584.98 | 1631.60 | 1447.74 | 0.34 | 1447.40 | 0.00 | 0.00 |
October | 445.86 | 3560.34 | 1036.93 | 0.00 | 1036.93 | 0.00 | 0.00 |
November | 142.50 | 4375.92 | 787.16 | 0.00 | 787.16 | 0.00 | 0.00 |
December | 72.75 | 5473.28 | 665.86 | 0.00 | 665.86 | 0.00 | 0.00 |
Annual Sum or Average | 1091.61 | 3045.87 | 1382.20 | 42.82 | 1339.38 | 0.00 | 0.00 |
Minimum of Months | 67.43 | 935.20 | 665.86 | 0.00 | 665.86 | 0.00 | 0.00 |
Maximum of Months | 2990.99 | 5473.28 | 2289.67 | 253.85 | 2035.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1120.83 | 2990.70 | 1485.63 | 910.44 | 575.19 | 0.00 | 0.00 |
February | 1624.42 | 3143.98 | 1973.50 | 1245.86 | 727.64 | 0.00 | 0.00 |
March | 2143.03 | 2387.89 | 2381.96 | 1389.38 | 992.58 | 0.00 | 0.00 |
April | 2130.54 | 2086.97 | 2442.83 | 1189.95 | 1252.89 | 0.00 | 0.00 |
May | 2951.92 | 1209.95 | 2855.63 | 1192.81 | 1662.82 | 0.00 | 0.00 |
June | 4583.74 | 645.31 | 3484.16 | 1829.09 | 1655.07 | 0.00 | 0.00 |
July | 4221.40 | 617.60 | 3167.38 | 1508.23 | 1659.15 | 0.00 | 0.00 |
August | 4211.35 | 698.79 | 3194.74 | 1759.55 | 1435.19 | 0.00 | 0.00 |
September | 3265.54 | 1034.53 | 2658.18 | 1444.00 | 1214.18 | 0.00 | 0.00 |
October | 1823.83 | 2313.38 | 1925.06 | 1054.82 | 870.24 | 0.00 | 0.00 |
November | 1218.81 | 2789.15 | 1498.41 | 846.02 | 652.39 | 0.00 | 0.00 |
December | 930.02 | 3434.24 | 1297.22 | 747.29 | 549.93 | 0.00 | 0.00 |
Annual Sum or Average | 2523.06 | 1939.56 | 2365.21 | 1259.16 | 1106.05 | 0.00 | 0.00 |
Minimum of Months | 930.02 | 617.60 | 1297.22 | 747.29 | 549.93 | 0.00 | 0.00 |
Maximum of Months | 4583.74 | 3434.24 | 3484.16 | 1829.09 | 1662.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7147.07 | 4340.43 | 6820.57 | 5610.66 | 1209.92 | 0.00 | 0.00 |
February | 6714.41 | 4555.02 | 6542.20 | 5215.85 | 1326.34 | 0.00 | 0.00 |
March | 5053.67 | 3686.12 | 4823.41 | 3173.53 | 1649.88 | 0.00 | 0.00 |
April | 2902.29 | 3345.80 | 3124.00 | 1256.17 | 1867.83 | 0.00 | 0.00 |
May | 2974.38 | 2038.49 | 2862.80 | 524.73 | 2338.07 | 0.00 | 0.00 |
June | 3778.87 | 1091.80 | 2639.41 | 482.41 | 2157.00 | 0.00 | 0.00 |
July | 3958.06 | 1025.09 | 2747.56 | 492.01 | 2255.55 | 0.00 | 0.00 |
August | 5004.96 | 1154.59 | 3498.20 | 1462.38 | 2035.82 | 0.00 | 0.00 |
September | 5945.11 | 1743.92 | 4500.78 | 2511.41 | 1989.37 | 0.00 | 0.00 |
October | 6137.62 | 3592.66 | 5381.62 | 3818.38 | 1563.24 | 0.00 | 0.00 |
November | 7079.59 | 4153.66 | 6556.75 | 5226.68 | 1330.07 | 0.00 | 0.00 |
December | 6404.13 | 4914.12 | 6269.97 | 5074.83 | 1195.14 | 0.00 | 0.00 |
Annual Sum or Average | 5250.02 | 2961.35 | 4636.54 | 2890.95 | 1745.59 | 0.00 | 0.00 |
Minimum of Months | 2902.29 | 1025.09 | 2639.41 | 482.41 | 1195.14 | 0.00 | 0.00 |
Maximum of Months | 7147.07 | 4914.12 | 6820.57 | 5610.66 | 2338.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1339.68 | 3120.16 | 1580.38 | 1001.42 | 578.97 | 0.00 | 0.00 |
February | 1599.56 | 3235.67 | 1905.72 | 1180.98 | 724.74 | 0.00 | 0.00 |
March | 2028.40 | 2509.17 | 2231.47 | 1231.15 | 1000.32 | 0.00 | 0.00 |
April | 1787.60 | 2207.49 | 2101.04 | 889.54 | 1211.49 | 0.00 | 0.00 |
May | 2711.58 | 1341.26 | 2568.00 | 905.32 | 1662.69 | 0.00 | 0.00 |
June | 4253.04 | 779.28 | 3140.82 | 1511.17 | 1629.65 | 0.00 | 0.00 |
July | 3487.02 | 711.32 | 2559.03 | 937.32 | 1621.70 | 0.00 | 0.00 |
August | 3566.84 | 794.58 | 2670.90 | 1319.46 | 1351.44 | 0.00 | 0.00 |
September | 2991.84 | 1161.10 | 2368.29 | 1135.75 | 1232.54 | 0.00 | 0.00 |
October | 2025.75 | 2417.83 | 1992.36 | 1138.78 | 853.58 | 0.00 | 0.00 |
November | 1446.17 | 2888.56 | 1634.84 | 992.55 | 642.29 | 0.00 | 0.00 |
December | 1002.43 | 3514.82 | 1320.50 | 780.05 | 540.45 | 0.00 | 0.00 |
Annual Sum or Average | 2356.60 | 2050.34 | 2173.46 | 1083.99 | 1089.47 | 0.00 | 0.00 |
Minimum of Months | 1002.43 | 711.32 | 1320.50 | 780.05 | 540.45 | 0.00 | 0.00 |
Maximum of Months | 4253.04 | 3514.82 | 3140.82 | 1511.17 | 1662.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 84.13 | 4508.29 | 711.67 | 0.00 | 711.67 | 0.00 | 0.00 |
February | 106.50 | 4695.55 | 894.49 | 0.00 | 894.49 | 0.00 | 0.00 |
March | 398.33 | 3518.79 | 1217.10 | 0.00 | 1217.10 | 0.00 | 0.00 |
April | 620.77 | 2966.42 | 1528.51 | 8.48 | 1520.03 | 0.00 | 0.00 |
May | 1667.74 | 1681.26 | 2088.03 | 69.02 | 2019.01 | 0.00 | 0.00 |
June | 3007.80 | 930.56 | 2289.67 | 253.85 | 2035.82 | 0.00 | 0.00 |
July | 2905.09 | 886.65 | 2165.41 | 140.17 | 2025.24 | 0.00 | 0.00 |
August | 2200.83 | 997.65 | 1723.50 | 40.77 | 1682.73 | 0.00 | 0.00 |
September | 1626.93 | 1491.07 | 1447.74 | 0.34 | 1447.40 | 0.00 | 0.00 |
October | 488.67 | 3261.11 | 1036.93 | 0.00 | 1036.93 | 0.00 | 0.00 |
November | 172.36 | 4018.09 | 787.16 | 0.00 | 787.16 | 0.00 | 0.00 |
December | 88.87 | 5186.55 | 665.86 | 0.00 | 665.86 | 0.00 | 0.00 |
Annual Sum or Average | 1119.62 | 2835.37 | 1382.20 | 42.82 | 1339.38 | 0.00 | 0.00 |
Minimum of Months | 84.13 | 886.65 | 665.86 | 0.00 | 665.86 | 0.00 | 0.00 |
Maximum of Months | 3007.80 | 5186.55 | 2289.67 | 253.85 | 2035.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1172.54 | 2780.61 | 1485.63 | 910.44 | 575.19 | 0.00 | 0.00 |
February | 1665.12 | 2960.75 | 1973.50 | 1245.86 | 727.64 | 0.00 | 0.00 |
March | 2174.03 | 2239.58 | 2381.96 | 1389.38 | 992.58 | 0.00 | 0.00 |
April | 2160.03 | 1915.28 | 2442.83 | 1189.95 | 1252.89 | 0.00 | 0.00 |
May | 2988.49 | 1133.63 | 2855.63 | 1192.81 | 1662.82 | 0.00 | 0.00 |
June | 4569.58 | 623.79 | 3484.16 | 1829.09 | 1655.07 | 0.00 | 0.00 |
July | 4208.94 | 600.35 | 3167.38 | 1508.23 | 1659.15 | 0.00 | 0.00 |
August | 4201.73 | 673.19 | 3194.74 | 1759.55 | 1435.19 | 0.00 | 0.00 |
September | 3280.55 | 969.95 | 2658.18 | 1444.00 | 1214.18 | 0.00 | 0.00 |
October | 1867.24 | 2137.29 | 1925.06 | 1054.82 | 870.24 | 0.00 | 0.00 |
November | 1272.17 | 2566.82 | 1498.41 | 846.02 | 652.39 | 0.00 | 0.00 |
December | 969.61 | 3246.90 | 1297.22 | 747.29 | 549.93 | 0.00 | 0.00 |
Annual Sum or Average | 2548.37 | 1814.61 | 2365.21 | 1259.16 | 1106.05 | 0.00 | 0.00 |
Minimum of Months | 969.61 | 600.35 | 1297.22 | 747.29 | 549.93 | 0.00 | 0.00 |
Maximum of Months | 4569.58 | 3246.90 | 3484.16 | 1829.09 | 1662.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7233.30 | 4011.89 | 6820.57 | 5610.66 | 1209.92 | 0.00 | 0.00 |
February | 6763.66 | 4277.04 | 6542.20 | 5215.85 | 1326.34 | 0.00 | 0.00 |
March | 5085.86 | 3444.00 | 4823.41 | 3173.53 | 1649.88 | 0.00 | 0.00 |
April | 2920.83 | 3060.94 | 3124.00 | 1256.17 | 1867.83 | 0.00 | 0.00 |
May | 3013.93 | 1881.06 | 2862.80 | 524.73 | 2338.07 | 0.00 | 0.00 |
June | 3773.58 | 1029.57 | 2639.41 | 482.41 | 2157.00 | 0.00 | 0.00 |
July | 3955.95 | 971.04 | 2747.56 | 492.01 | 2255.55 | 0.00 | 0.00 |
August | 4999.41 | 1085.57 | 3498.20 | 1462.38 | 2035.82 | 0.00 | 0.00 |
September | 5960.02 | 1613.37 | 4500.78 | 2511.41 | 1989.37 | 0.00 | 0.00 |
October | 6178.77 | 3303.22 | 5381.62 | 3818.38 | 1563.24 | 0.00 | 0.00 |
November | 7152.57 | 3824.27 | 6556.75 | 5226.68 | 1330.07 | 0.00 | 0.00 |
December | 6471.68 | 4613.31 | 6269.97 | 5074.83 | 1195.14 | 0.00 | 0.00 |
Annual Sum or Average | 5284.11 | 2751.27 | 4636.54 | 2890.95 | 1745.59 | 0.00 | 0.00 |
Minimum of Months | 2920.83 | 971.04 | 2639.41 | 482.41 | 1195.14 | 0.00 | 0.00 |
Maximum of Months | 7233.30 | 4613.31 | 6820.57 | 5610.66 | 2338.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1353.75 | 2930.84 | 1580.38 | 1001.42 | 578.97 | 0.00 | 0.00 |
February | 1603.39 | 3073.50 | 1905.72 | 1180.98 | 724.74 | 0.00 | 0.00 |
March | 2026.63 | 2373.04 | 2231.47 | 1231.15 | 1000.32 | 0.00 | 0.00 |
April | 1785.27 | 2044.47 | 2101.04 | 889.54 | 1211.49 | 0.00 | 0.00 |
May | 2715.48 | 1258.37 | 2568.00 | 905.32 | 1662.69 | 0.00 | 0.00 |
June | 4234.33 | 746.74 | 3140.82 | 1511.17 | 1629.65 | 0.00 | 0.00 |
July | 3471.63 | 684.74 | 2559.03 | 937.32 | 1621.70 | 0.00 | 0.00 |
August | 3553.44 | 761.20 | 2670.90 | 1319.46 | 1351.44 | 0.00 | 0.00 |
September | 2989.79 | 1091.36 | 2368.29 | 1135.75 | 1232.54 | 0.00 | 0.00 |
October | 2032.08 | 2254.63 | 1992.36 | 1138.78 | 853.58 | 0.00 | 0.00 |
November | 1459.52 | 2692.02 | 1634.84 | 992.55 | 642.29 | 0.00 | 0.00 |
December | 1013.05 | 3346.51 | 1320.50 | 780.05 | 540.45 | 0.00 | 0.00 |
Annual Sum or Average | 2356.46 | 1932.01 | 2173.46 | 1083.99 | 1089.47 | 0.00 | 0.00 |
Minimum of Months | 1013.05 | 684.74 | 1320.50 | 780.05 | 540.45 | 0.00 | 0.00 |
Maximum of Months | 4234.33 | 3346.51 | 3140.82 | 1511.17 | 1662.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112406E+09 | 0.140194E+11 | 0.190615E+10 | 0.00 | 0.190615E+10 | 0.00 | 0.00 |
February | 0.151135E+09 | 0.128506E+11 | 0.216395E+10 | 0.00 | 0.216395E+10 | 0.00 | 0.00 |
March | 0.820658E+09 | 0.109226E+11 | 0.325990E+10 | 0.00 | 0.325990E+10 | 0.00 | 0.00 |
April | 0.135690E+10 | 0.937661E+10 | 0.396190E+10 | 21978925.07 | 0.393992E+10 | 0.00 | 0.00 |
May | 0.410394E+10 | 0.524103E+10 | 0.559261E+10 | 0.184869E+09 | 0.540774E+10 | 0.00 | 0.00 |
June | 0.760918E+10 | 0.271003E+10 | 0.593485E+10 | 0.657974E+09 | 0.527687E+10 | 0.00 | 0.00 |
July | 0.757112E+10 | 0.267644E+10 | 0.579984E+10 | 0.375434E+09 | 0.542441E+10 | 0.00 | 0.00 |
August | 0.565162E+10 | 0.310871E+10 | 0.461624E+10 | 0.109205E+09 | 0.450703E+10 | 0.00 | 0.00 |
September | 0.390870E+10 | 0.462026E+10 | 0.375255E+10 | 881408.30 | 0.375167E+10 | 0.00 | 0.00 |
October | 0.988838E+09 | 0.103529E+11 | 0.277732E+10 | 0.00 | 0.277732E+10 | 0.00 | 0.00 |
November | 0.265114E+09 | 0.124333E+11 | 0.204033E+10 | 0.00 | 0.204033E+10 | 0.00 | 0.00 |
December | 0.117128E+09 | 0.158972E+11 | 0.178344E+10 | 0.00 | 0.178344E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.326567E+11 | 0.104209E+12 | 0.435891E+11 | 0.135034E+10 | 0.422387E+11 | 0.00 | 0.00 |
Minimum of Months | 0.112406E+09 | 0.267644E+10 | 0.178344E+10 | 0.00 | 0.178344E+10 | 0.00 | 0.00 |
Maximum of Months | 0.760918E+10 | 0.158972E+11 | 0.593485E+10 | 0.657974E+09 | 0.542441E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.295153E+10 | 0.844316E+10 | 0.397914E+10 | 0.243854E+10 | 0.154060E+10 | 0.00 | 0.00 |
February | 0.392979E+10 | 0.789588E+10 | 0.477431E+10 | 0.301401E+10 | 0.176031E+10 | 0.00 | 0.00 |
March | 0.577920E+10 | 0.668759E+10 | 0.637987E+10 | 0.372132E+10 | 0.265855E+10 | 0.00 | 0.00 |
April | 0.557297E+10 | 0.578009E+10 | 0.633184E+10 | 0.308435E+10 | 0.324749E+10 | 0.00 | 0.00 |
May | 0.798589E+10 | 0.334335E+10 | 0.764855E+10 | 0.319483E+10 | 0.445372E+10 | 0.00 | 0.00 |
June | 0.119804E+11 | 0.172587E+10 | 0.903099E+10 | 0.474103E+10 | 0.428996E+10 | 0.00 | 0.00 |
July | 0.114034E+11 | 0.166288E+10 | 0.848355E+10 | 0.403966E+10 | 0.444389E+10 | 0.00 | 0.00 |
August | 0.113741E+11 | 0.187660E+10 | 0.855682E+10 | 0.471279E+10 | 0.384403E+10 | 0.00 | 0.00 |
September | 0.851436E+10 | 0.281346E+10 | 0.689004E+10 | 0.374287E+10 | 0.314718E+10 | 0.00 | 0.00 |
October | 0.491119E+10 | 0.650723E+10 | 0.515609E+10 | 0.282524E+10 | 0.233085E+10 | 0.00 | 0.00 |
November | 0.312646E+10 | 0.760356E+10 | 0.388389E+10 | 0.219288E+10 | 0.169101E+10 | 0.00 | 0.00 |
December | 0.243495E+10 | 0.968504E+10 | 0.347449E+10 | 0.200156E+10 | 0.147294E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.799643E+11 | 0.640247E+11 | 0.745896E+11 | 0.397091E+11 | 0.348805E+11 | 0.00 | 0.00 |
Minimum of Months | 0.243495E+10 | 0.166288E+10 | 0.347449E+10 | 0.200156E+10 | 0.147294E+10 | 0.00 | 0.00 |
Maximum of Months | 0.119804E+11 | 0.968504E+10 | 0.903099E+10 | 0.474103E+10 | 0.445372E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.193367E+11 | 0.116966E+11 | 0.182683E+11 | 0.150276E+11 | 0.324065E+10 | 0.00 | 0.00 |
February | 0.164903E+11 | 0.110619E+11 | 0.158269E+11 | 0.126182E+11 | 0.320870E+10 | 0.00 | 0.00 |
March | 0.137020E+11 | 0.100428E+11 | 0.129191E+11 | 0.850001E+10 | 0.441905E+10 | 0.00 | 0.00 |
April | 0.758443E+10 | 0.901716E+10 | 0.809743E+10 | 0.325601E+10 | 0.484142E+10 | 0.00 | 0.00 |
May | 0.802033E+10 | 0.552728E+10 | 0.766775E+10 | 0.140544E+10 | 0.626231E+10 | 0.00 | 0.00 |
June | 0.978348E+10 | 0.292363E+10 | 0.684137E+10 | 0.125041E+10 | 0.559096E+10 | 0.00 | 0.00 |
July | 0.105785E+11 | 0.282310E+10 | 0.735910E+10 | 0.131781E+10 | 0.604129E+10 | 0.00 | 0.00 |
August | 0.134315E+11 | 0.317539E+10 | 0.936963E+10 | 0.391686E+10 | 0.545277E+10 | 0.00 | 0.00 |
September | 0.155303E+11 | 0.459883E+10 | 0.116661E+11 | 0.650960E+10 | 0.515647E+10 | 0.00 | 0.00 |
October | 0.166100E+11 | 0.971416E+10 | 0.144142E+11 | 0.102272E+11 | 0.418699E+10 | 0.00 | 0.00 |
November | 0.185585E+11 | 0.108585E+11 | 0.169952E+11 | 0.135476E+11 | 0.344755E+10 | 0.00 | 0.00 |
December | 0.173062E+11 | 0.133966E+11 | 0.167935E+11 | 0.135925E+11 | 0.320108E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.166932E+12 | 0.948360E+11 | 0.146219E+12 | 0.911693E+11 | 0.550492E+11 | 0.00 | 0.00 |
Minimum of Months | 0.758443E+10 | 0.282310E+10 | 0.684137E+10 | 0.125041E+10 | 0.320108E+10 | 0.00 | 0.00 |
Maximum of Months | 0.193367E+11 | 0.133966E+11 | 0.182683E+11 | 0.150276E+11 | 0.626231E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.349646E+10 | 0.904440E+10 | 0.423292E+10 | 0.268221E+10 | 0.155071E+10 | 0.00 | 0.00 |
February | 0.381047E+10 | 0.837424E+10 | 0.461033E+10 | 0.285704E+10 | 0.175329E+10 | 0.00 | 0.00 |
March | 0.530881E+10 | 0.740673E+10 | 0.597680E+10 | 0.329753E+10 | 0.267927E+10 | 0.00 | 0.00 |
April | 0.446600E+10 | 0.663726E+10 | 0.544591E+10 | 0.230570E+10 | 0.314020E+10 | 0.00 | 0.00 |
May | 0.715087E+10 | 0.386993E+10 | 0.687817E+10 | 0.242481E+10 | 0.445336E+10 | 0.00 | 0.00 |
June | 0.109043E+11 | 0.223201E+10 | 0.814105E+10 | 0.391697E+10 | 0.422408E+10 | 0.00 | 0.00 |
July | 0.912086E+10 | 0.221277E+10 | 0.685413E+10 | 0.251054E+10 | 0.434359E+10 | 0.00 | 0.00 |
August | 0.929149E+10 | 0.252376E+10 | 0.715377E+10 | 0.353406E+10 | 0.361970E+10 | 0.00 | 0.00 |
September | 0.762293E+10 | 0.330846E+10 | 0.613863E+10 | 0.294388E+10 | 0.319475E+10 | 0.00 | 0.00 |
October | 0.532176E+10 | 0.702635E+10 | 0.533635E+10 | 0.305012E+10 | 0.228623E+10 | 0.00 | 0.00 |
November | 0.361427E+10 | 0.829074E+10 | 0.423751E+10 | 0.257269E+10 | 0.166482E+10 | 0.00 | 0.00 |
December | 0.254946E+10 | 0.105200E+11 | 0.353684E+10 | 0.208931E+10 | 0.144753E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.726577E+11 | 0.714467E+11 | 0.685424E+11 | 0.341849E+11 | 0.343575E+11 | 0.00 | 0.00 |
Minimum of Months | 0.254946E+10 | 0.221277E+10 | 0.353684E+10 | 0.208931E+10 | 0.144753E+10 | 0.00 | 0.00 |
Maximum of Months | 0.109043E+11 | 0.105200E+11 | 0.814105E+10 | 0.391697E+10 | 0.445336E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.180599E+09 | 0.129185E+11 | 0.190614E+10 | 0.00 | 0.190614E+10 | 0.00 | 0.00 |
February | 0.215031E+09 | 0.120314E+11 | 0.216394E+10 | 0.00 | 0.216394E+10 | 0.00 | 0.00 |
March | 0.998436E+09 | 0.100678E+11 | 0.325989E+10 | 0.00 | 0.325989E+10 | 0.00 | 0.00 |
April | 0.154440E+10 | 0.843551E+10 | 0.396189E+10 | 21978847.02 | 0.393991E+10 | 0.00 | 0.00 |
May | 0.428083E+10 | 0.491641E+10 | 0.559259E+10 | 0.184868E+09 | 0.540772E+10 | 0.00 | 0.00 |
June | 0.775264E+10 | 0.255557E+10 | 0.593483E+10 | 0.657972E+09 | 0.527685E+10 | 0.00 | 0.00 |
July | 0.774083E+10 | 0.250484E+10 | 0.579982E+10 | 0.375433E+09 | 0.542439E+10 | 0.00 | 0.00 |
August | 0.584543E+10 | 0.285738E+10 | 0.461622E+10 | 0.109204E+09 | 0.450702E+10 | 0.00 | 0.00 |
September | 0.410826E+10 | 0.422911E+10 | 0.375254E+10 | 881405.17 | 0.375166E+10 | 0.00 | 0.00 |
October | 0.119420E+10 | 0.953603E+10 | 0.277731E+10 | 0.00 | 0.277731E+10 | 0.00 | 0.00 |
November | 0.369370E+09 | 0.113424E+11 | 0.204032E+10 | 0.00 | 0.204032E+10 | 0.00 | 0.00 |
December | 0.194867E+09 | 0.146596E+11 | 0.178344E+10 | 0.00 | 0.178344E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.344249E+11 | 0.960545E+11 | 0.435889E+11 | 0.135034E+10 | 0.422386E+11 | 0.00 | 0.00 |
Minimum of Months | 0.180599E+09 | 0.250484E+10 | 0.178344E+10 | 0.00 | 0.178344E+10 | 0.00 | 0.00 |
Maximum of Months | 0.775264E+10 | 0.146596E+11 | 0.593483E+10 | 0.657972E+09 | 0.542439E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.300204E+10 | 0.801029E+10 | 0.397912E+10 | 0.243853E+10 | 0.154060E+10 | 0.00 | 0.00 |
February | 0.392981E+10 | 0.760591E+10 | 0.477429E+10 | 0.301399E+10 | 0.176030E+10 | 0.00 | 0.00 |
March | 0.573990E+10 | 0.639571E+10 | 0.637985E+10 | 0.372131E+10 | 0.265854E+10 | 0.00 | 0.00 |
April | 0.552235E+10 | 0.540942E+10 | 0.633182E+10 | 0.308434E+10 | 0.324748E+10 | 0.00 | 0.00 |
May | 0.790641E+10 | 0.324074E+10 | 0.764852E+10 | 0.319482E+10 | 0.445370E+10 | 0.00 | 0.00 |
June | 0.118811E+11 | 0.167265E+10 | 0.903095E+10 | 0.474101E+10 | 0.428994E+10 | 0.00 | 0.00 |
July | 0.113066E+11 | 0.165418E+10 | 0.848351E+10 | 0.403964E+10 | 0.444387E+10 | 0.00 | 0.00 |
August | 0.112797E+11 | 0.187164E+10 | 0.855679E+10 | 0.471277E+10 | 0.384402E+10 | 0.00 | 0.00 |
September | 0.846429E+10 | 0.268149E+10 | 0.689001E+10 | 0.374285E+10 | 0.314716E+10 | 0.00 | 0.00 |
October | 0.488495E+10 | 0.619617E+10 | 0.515607E+10 | 0.282523E+10 | 0.233084E+10 | 0.00 | 0.00 |
November | 0.315915E+10 | 0.722948E+10 | 0.388388E+10 | 0.219288E+10 | 0.169100E+10 | 0.00 | 0.00 |
December | 0.249097E+10 | 0.919828E+10 | 0.347448E+10 | 0.200155E+10 | 0.147293E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.795672E+11 | 0.611660E+11 | 0.745893E+11 | 0.397089E+11 | 0.348804E+11 | 0.00 | 0.00 |
Minimum of Months | 0.249097E+10 | 0.165418E+10 | 0.347448E+10 | 0.200155E+10 | 0.147293E+10 | 0.00 | 0.00 |
Maximum of Months | 0.118811E+11 | 0.919828E+10 | 0.903095E+10 | 0.474101E+10 | 0.445370E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.191427E+11 | 0.116254E+11 | 0.182682E+11 | 0.150276E+11 | 0.324064E+10 | 0.00 | 0.00 |
February | 0.162435E+11 | 0.110195E+11 | 0.158269E+11 | 0.126182E+11 | 0.320869E+10 | 0.00 | 0.00 |
March | 0.135357E+11 | 0.987290E+10 | 0.129190E+11 | 0.849998E+10 | 0.441904E+10 | 0.00 | 0.00 |
April | 0.752274E+10 | 0.867232E+10 | 0.809740E+10 | 0.325600E+10 | 0.484141E+10 | 0.00 | 0.00 |
May | 0.796658E+10 | 0.545988E+10 | 0.766772E+10 | 0.140544E+10 | 0.626229E+10 | 0.00 | 0.00 |
June | 0.979484E+10 | 0.282996E+10 | 0.684134E+10 | 0.125041E+10 | 0.559094E+10 | 0.00 | 0.00 |
July | 0.106013E+11 | 0.274561E+10 | 0.735907E+10 | 0.131780E+10 | 0.604126E+10 | 0.00 | 0.00 |
August | 0.134053E+11 | 0.309245E+10 | 0.936959E+10 | 0.391684E+10 | 0.545275E+10 | 0.00 | 0.00 |
September | 0.154097E+11 | 0.452024E+10 | 0.116660E+11 | 0.650958E+10 | 0.515645E+10 | 0.00 | 0.00 |
October | 0.164390E+11 | 0.962258E+10 | 0.144141E+11 | 0.102272E+11 | 0.418698E+10 | 0.00 | 0.00 |
November | 0.183503E+11 | 0.107663E+11 | 0.169951E+11 | 0.135476E+11 | 0.344754E+10 | 0.00 | 0.00 |
December | 0.171528E+11 | 0.131620E+11 | 0.167935E+11 | 0.135924E+11 | 0.320107E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.165565E+12 | 0.933891E+11 | 0.146218E+12 | 0.911690E+11 | 0.550490E+11 | 0.00 | 0.00 |
Minimum of Months | 0.752274E+10 | 0.274561E+10 | 0.684134E+10 | 0.125041E+10 | 0.320107E+10 | 0.00 | 0.00 |
Maximum of Months | 0.191427E+11 | 0.131620E+11 | 0.182682E+11 | 0.150276E+11 | 0.626229E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.358821E+10 | 0.835705E+10 | 0.423290E+10 | 0.268219E+10 | 0.155070E+10 | 0.00 | 0.00 |
February | 0.386966E+10 | 0.782772E+10 | 0.461031E+10 | 0.285703E+10 | 0.175328E+10 | 0.00 | 0.00 |
March | 0.543286E+10 | 0.672057E+10 | 0.597678E+10 | 0.329752E+10 | 0.267926E+10 | 0.00 | 0.00 |
April | 0.463345E+10 | 0.572180E+10 | 0.544588E+10 | 0.230569E+10 | 0.314019E+10 | 0.00 | 0.00 |
May | 0.726269E+10 | 0.359242E+10 | 0.687814E+10 | 0.242480E+10 | 0.445334E+10 | 0.00 | 0.00 |
June | 0.110239E+11 | 0.201989E+10 | 0.814102E+10 | 0.391696E+10 | 0.422406E+10 | 0.00 | 0.00 |
July | 0.933964E+10 | 0.190521E+10 | 0.685410E+10 | 0.251053E+10 | 0.434357E+10 | 0.00 | 0.00 |
August | 0.955343E+10 | 0.212819E+10 | 0.715374E+10 | 0.353405E+10 | 0.361969E+10 | 0.00 | 0.00 |
September | 0.775485E+10 | 0.300958E+10 | 0.613860E+10 | 0.294387E+10 | 0.319473E+10 | 0.00 | 0.00 |
October | 0.542578E+10 | 0.647591E+10 | 0.533633E+10 | 0.305011E+10 | 0.228622E+10 | 0.00 | 0.00 |
November | 0.374847E+10 | 0.748715E+10 | 0.423749E+10 | 0.257268E+10 | 0.166481E+10 | 0.00 | 0.00 |
December | 0.268491E+10 | 0.941411E+10 | 0.353683E+10 | 0.208930E+10 | 0.144753E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.743178E+11 | 0.646596E+11 | 0.685421E+11 | 0.341847E+11 | 0.343574E+11 | 0.00 | 0.00 |
Minimum of Months | 0.268491E+10 | 0.190521E+10 | 0.353683E+10 | 0.208930E+10 | 0.144753E+10 | 0.00 | 0.00 |
Maximum of Months | 0.110239E+11 | 0.941411E+10 | 0.814102E+10 | 0.391696E+10 | 0.445334E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.225325E+09 | 0.120750E+11 | 0.190614E+10 | 0.00 | 0.190614E+10 | 0.00 | 0.00 |
February | 0.257653E+09 | 0.113595E+11 | 0.216394E+10 | 0.00 | 0.216394E+10 | 0.00 | 0.00 |
March | 0.106688E+10 | 0.942471E+10 | 0.325989E+10 | 0.00 | 0.325989E+10 | 0.00 | 0.00 |
April | 0.160903E+10 | 0.768895E+10 | 0.396189E+10 | 21978847.02 | 0.393991E+10 | 0.00 | 0.00 |
May | 0.446689E+10 | 0.450309E+10 | 0.559259E+10 | 0.184868E+09 | 0.540772E+10 | 0.00 | 0.00 |
June | 0.779621E+10 | 0.241200E+10 | 0.593483E+10 | 0.657972E+09 | 0.527685E+10 | 0.00 | 0.00 |
July | 0.778099E+10 | 0.237482E+10 | 0.579982E+10 | 0.375433E+09 | 0.542439E+10 | 0.00 | 0.00 |
August | 0.589471E+10 | 0.267210E+10 | 0.461622E+10 | 0.109204E+09 | 0.450702E+10 | 0.00 | 0.00 |
September | 0.421699E+10 | 0.386486E+10 | 0.375254E+10 | 881405.17 | 0.375166E+10 | 0.00 | 0.00 |
October | 0.130885E+10 | 0.873456E+10 | 0.277731E+10 | 0.00 | 0.277731E+10 | 0.00 | 0.00 |
November | 0.446751E+09 | 0.104149E+11 | 0.204032E+10 | 0.00 | 0.204032E+10 | 0.00 | 0.00 |
December | 0.238017E+09 | 0.138916E+11 | 0.178344E+10 | 0.00 | 0.178344E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.353083E+11 | 0.894161E+11 | 0.435889E+11 | 0.135034E+10 | 0.422386E+11 | 0.00 | 0.00 |
Minimum of Months | 0.225325E+09 | 0.237482E+10 | 0.178344E+10 | 0.00 | 0.178344E+10 | 0.00 | 0.00 |
Maximum of Months | 0.779621E+10 | 0.138916E+11 | 0.593483E+10 | 0.657972E+09 | 0.542439E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.314054E+10 | 0.744759E+10 | 0.397912E+10 | 0.243853E+10 | 0.154060E+10 | 0.00 | 0.00 |
February | 0.402826E+10 | 0.716264E+10 | 0.477429E+10 | 0.301399E+10 | 0.176030E+10 | 0.00 | 0.00 |
March | 0.582293E+10 | 0.599849E+10 | 0.637985E+10 | 0.372131E+10 | 0.265854E+10 | 0.00 | 0.00 |
April | 0.559879E+10 | 0.496440E+10 | 0.633182E+10 | 0.308434E+10 | 0.324748E+10 | 0.00 | 0.00 |
May | 0.800437E+10 | 0.303631E+10 | 0.764852E+10 | 0.319482E+10 | 0.445370E+10 | 0.00 | 0.00 |
June | 0.118444E+11 | 0.161686E+10 | 0.903095E+10 | 0.474101E+10 | 0.428994E+10 | 0.00 | 0.00 |
July | 0.112732E+11 | 0.160799E+10 | 0.848351E+10 | 0.403964E+10 | 0.444387E+10 | 0.00 | 0.00 |
August | 0.112539E+11 | 0.180308E+10 | 0.855679E+10 | 0.471277E+10 | 0.384402E+10 | 0.00 | 0.00 |
September | 0.850319E+10 | 0.251410E+10 | 0.689001E+10 | 0.374285E+10 | 0.314716E+10 | 0.00 | 0.00 |
October | 0.500121E+10 | 0.572452E+10 | 0.515607E+10 | 0.282523E+10 | 0.233084E+10 | 0.00 | 0.00 |
November | 0.329746E+10 | 0.665319E+10 | 0.388388E+10 | 0.219288E+10 | 0.169100E+10 | 0.00 | 0.00 |
December | 0.259701E+10 | 0.869649E+10 | 0.347448E+10 | 0.200155E+10 | 0.147293E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.803653E+11 | 0.572257E+11 | 0.745893E+11 | 0.397089E+11 | 0.348804E+11 | 0.00 | 0.00 |
Minimum of Months | 0.259701E+10 | 0.160799E+10 | 0.347448E+10 | 0.200155E+10 | 0.147293E+10 | 0.00 | 0.00 |
Maximum of Months | 0.118444E+11 | 0.869649E+10 | 0.903095E+10 | 0.474101E+10 | 0.445370E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.193737E+11 | 0.107454E+11 | 0.182682E+11 | 0.150276E+11 | 0.324064E+10 | 0.00 | 0.00 |
February | 0.163626E+11 | 0.103470E+11 | 0.158269E+11 | 0.126182E+11 | 0.320869E+10 | 0.00 | 0.00 |
March | 0.136220E+11 | 0.922441E+10 | 0.129190E+11 | 0.849998E+10 | 0.441904E+10 | 0.00 | 0.00 |
April | 0.757079E+10 | 0.793396E+10 | 0.809740E+10 | 0.325600E+10 | 0.484141E+10 | 0.00 | 0.00 |
May | 0.807252E+10 | 0.503822E+10 | 0.766772E+10 | 0.140544E+10 | 0.626229E+10 | 0.00 | 0.00 |
June | 0.978113E+10 | 0.266865E+10 | 0.684134E+10 | 0.125041E+10 | 0.559094E+10 | 0.00 | 0.00 |
July | 0.105956E+11 | 0.260082E+10 | 0.735907E+10 | 0.131780E+10 | 0.604126E+10 | 0.00 | 0.00 |
August | 0.133904E+11 | 0.290759E+10 | 0.936959E+10 | 0.391684E+10 | 0.545275E+10 | 0.00 | 0.00 |
September | 0.154484E+11 | 0.418186E+10 | 0.116660E+11 | 0.650958E+10 | 0.515645E+10 | 0.00 | 0.00 |
October | 0.165492E+11 | 0.884733E+10 | 0.144141E+11 | 0.102272E+11 | 0.418698E+10 | 0.00 | 0.00 |
November | 0.185395E+11 | 0.991250E+10 | 0.169951E+11 | 0.135476E+11 | 0.344754E+10 | 0.00 | 0.00 |
December | 0.173338E+11 | 0.123563E+11 | 0.167935E+11 | 0.135924E+11 | 0.320107E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.166640E+12 | 0.867641E+11 | 0.146218E+12 | 0.911690E+11 | 0.550490E+11 | 0.00 | 0.00 |
Minimum of Months | 0.757079E+10 | 0.260082E+10 | 0.684134E+10 | 0.125041E+10 | 0.320107E+10 | 0.00 | 0.00 |
Maximum of Months | 0.193737E+11 | 0.123563E+11 | 0.182682E+11 | 0.150276E+11 | 0.626229E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.362588E+10 | 0.784997E+10 | 0.423290E+10 | 0.268219E+10 | 0.155070E+10 | 0.00 | 0.00 |
February | 0.387892E+10 | 0.743540E+10 | 0.461031E+10 | 0.285703E+10 | 0.175328E+10 | 0.00 | 0.00 |
March | 0.542814E+10 | 0.635596E+10 | 0.597678E+10 | 0.329752E+10 | 0.267926E+10 | 0.00 | 0.00 |
April | 0.462741E+10 | 0.529927E+10 | 0.544588E+10 | 0.230569E+10 | 0.314019E+10 | 0.00 | 0.00 |
May | 0.727313E+10 | 0.337043E+10 | 0.687814E+10 | 0.242480E+10 | 0.445334E+10 | 0.00 | 0.00 |
June | 0.109754E+11 | 0.193556E+10 | 0.814102E+10 | 0.391696E+10 | 0.422406E+10 | 0.00 | 0.00 |
July | 0.929840E+10 | 0.183400E+10 | 0.685410E+10 | 0.251053E+10 | 0.434357E+10 | 0.00 | 0.00 |
August | 0.951754E+10 | 0.203879E+10 | 0.715374E+10 | 0.353405E+10 | 0.361969E+10 | 0.00 | 0.00 |
September | 0.774954E+10 | 0.282880E+10 | 0.613860E+10 | 0.294387E+10 | 0.319473E+10 | 0.00 | 0.00 |
October | 0.544271E+10 | 0.603879E+10 | 0.533633E+10 | 0.305011E+10 | 0.228622E+10 | 0.00 | 0.00 |
November | 0.378307E+10 | 0.697773E+10 | 0.423749E+10 | 0.257268E+10 | 0.166481E+10 | 0.00 | 0.00 |
December | 0.271335E+10 | 0.896329E+10 | 0.353683E+10 | 0.208930E+10 | 0.144753E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.743135E+11 | 0.609280E+11 | 0.685421E+11 | 0.341847E+11 | 0.343574E+11 | 0.00 | 0.00 |
Minimum of Months | 0.271335E+10 | 0.183400E+10 | 0.353683E+10 | 0.208930E+10 | 0.144753E+10 | 0.00 | 0.00 |
Maximum of Months | 0.109754E+11 | 0.896329E+10 | 0.814102E+10 | 0.391696E+10 | 0.445334E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.414153E+11 | -0.409636E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -451654351.4 | 60.05 | 0.00 | 0.00 |
February | 0.380841E+11 | -0.376755E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -408552964.9 | 60.05 | 0.00 | 0.00 |
March | 0.441294E+11 | -0.436775E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -451918307.2 | 60.05 | 0.00 | 0.00 |
April | 0.385124E+11 | -0.380765E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -435940943.8 | 60.05 | 0.00 | 0.00 |
May | 0.389102E+11 | -0.384611E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -449141094.0 | 60.05 | 0.00 | 0.00 |
June | 0.363481E+11 | -0.359163E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -431745757.8 | 60.05 | 0.00 | 0.00 |
July | 0.330758E+11 | -0.326323E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443514089.6 | 60.05 | 0.00 | 0.00 |
August | 0.356135E+11 | -0.351690E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444481843.7 | 60.05 | 0.00 | 0.00 |
September | 0.329373E+11 | -0.325077E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -429594945.7 | 60.05 | 0.00 | 0.00 |
October | 0.355908E+11 | -0.351455E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -445272923.6 | 60.05 | 0.00 | 0.00 |
November | 0.370165E+11 | -0.365849E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -431634750.1 | 60.05 | 0.00 | 0.00 |
December | 0.389197E+11 | -0.384693E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -450413556.0 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.450553E+12 | -0.445279E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.527387E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.329373E+11 | -0.436775E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -451918307.2 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.441294E+11 | -0.325077E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -408552964.9 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 245.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 415.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 421.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 430.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 394.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 354.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 262.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 257.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 251.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3902.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 245.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 430.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171228E+10 | 27552.32 | 05-JAN-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141298E+10 | 17734.48 | 11-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.537218E+09 | 14399.88 | 04-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 84366360.52 | 9987.75 | 17-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471641E+09 | 13616.68 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.610078E+09 | 20613.87 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.442686E+10 | 35890.00 | 23-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.925543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.442686E+10 | 35890.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.155712E+10 | 19280.96 | 05-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176788E+10 | 19267.25 | 07-FEB-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.810152E+09 | 19048.59 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.323097E+09 | 19219.15 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5471099.27 | 2011.63 | 02-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14534403.17 | 9629.31 | 22-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.540490E+09 | 19266.52 | 30-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.808552E+09 | 19284.85 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.232503E+10 | 19279.66 | 20-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.815233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.232503E+10 | 19284.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.191631E+10 | 18483.16 | 06-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.199391E+10 | 18490.76 | 06-FEB-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129339E+10 | 18421.48 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.796155E+09 | 18478.03 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45248151.88 | 5496.95 | 03-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 472922.26 | 1497.51 | 23-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 58920742.87 | 13195.34 | 22-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105708E+10 | 18489.37 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145573E+10 | 18510.96 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.277427E+10 | 18480.11 | 23-DEC-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.277427E+10 | 18510.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.173520E+10 | 24894.59 | 05-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.208759E+10 | 24892.66 | 08-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153356E+10 | 24842.49 | 02-MAR-05:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104216E+10 | 24888.41 | 17-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151429E+09 | 20571.78 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 64552210.44 | 23416.86 | 22-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132669E+10 | 24893.71 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137293E+10 | 25365.04 | 27-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.257124E+10 | 24890.98 | 22-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.257124E+10 | 25365.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.152802E+10 | 18567.60 | 05-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159072E+10 | 18619.34 | 06-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.701512E+09 | 18563.78 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.230841E+09 | 17634.14 | 15-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44629792.63 | 4294.74 | 12-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 44358483.99 | 4866.94 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.749456E+09 | 18565.91 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.687379E+09 | 18568.09 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134358E+10 | 18611.08 | 23-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.159072E+10 | 18619.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.408844E+11 | 526990.19 | 12-JAN-10:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.315670E+11 | 472818.94 | 28-FEB-10:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110542E+11 | 503578.80 | 02-MAR-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.468849E+10 | 458414.07 | 05-APR-09:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.282422E+09 | 326708.12 | 02-MAY-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29066311.66 | 50056.39 | 22-SEP-09:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183272E+11 | 353398.08 | 12-OCT-13:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.186543E+11 | 391028.04 | 18-NOV-10:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.877084E+11 | 489502.80 | 18-DEC-10:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213195E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.877084E+11 | 526990.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.356009E+10 | 598732.76 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.377106E+10 | 638224.76 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161710E+10 | 567530.45 | 20-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.364264E+09 | 633696.71 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.399132E+09 | 633609.93 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.446189E+10 | 630101.72 | 11-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.446189E+10 | 638224.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.589629E+11 | 252279.06 | 04-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.638532E+11 | 253403.75 | 06-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.422912E+11 | 252153.31 | 02-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.258537E+11 | 254311.52 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.327862E+10 | 219346.19 | 03-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 42863384.93 | 25759.74 | 23-AUG-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.218353E+10 | 241163.03 | 22-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.287339E+11 | 253436.05 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.453425E+11 | 253018.75 | 24-NOV-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.866675E+11 | 252107.21 | 07-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.357210E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.866675E+11 | 254311.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.367758E+11 | 224691.38 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.382060E+11 | 224820.35 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.282034E+11 | 224357.63 | 19-MAR-06:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178895E+11 | 224283.36 | 03-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.275239E+10 | 185451.19 | 03-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1405354.55 | 8027.80 | 09-JUN-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7429341.63 | 12009.96 | 29-JUL-05:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119014E+09 | 42123.26 | 23-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.201059E+10 | 204191.68 | 22-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.226399E+11 | 224390.16 | 30-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.307419E+11 | 224445.19 | 02-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.546237E+11 | 224359.21 | 19-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233971E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1405354.55 | 8027.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.546237E+11 | 224820.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.281910E+11 | 271825.95 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.363315E+11 | 273228.72 | 06-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.319544E+11 | 271511.80 | 02-MAR-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.229428E+11 | 271755.82 | 03-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.419852E+10 | 241853.79 | 12-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11459249.66 | 9032.45 | 09-JUN-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43218959.94 | 16855.39 | 23-AUG-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162739E+10 | 253750.60 | 22-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.229054E+11 | 270975.22 | 31-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.249865E+11 | 271671.99 | 27-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.485083E+11 | 270160.77 | 11-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221701E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.485083E+11 | 273228.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.427382E+11 | 236711.75 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.440682E+11 | 236867.92 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.332008E+11 | 236258.74 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223743E+11 | 236281.61 | 03-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.554556E+10 | 204709.45 | 12-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158880E+09 | 28876.48 | 10-JUN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 37070810.50 | 15802.59 | 29-JUL-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.266904E+09 | 47729.48 | 23-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.335385E+10 | 214980.82 | 22-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.255156E+11 | 236240.13 | 31-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.357370E+11 | 236317.95 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.590846E+11 | 236181.69 | 19-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.272081E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 37070810.50 | 15802.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.590846E+11 | 236867.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.743820E+10 | 40806.75 | 05-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.676298E+10 | 31285.59 | 11-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.301371E+10 | 32619.72 | 04-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135836E+10 | 26953.68 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24001116.42 | 6842.09 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43177990.13 | 11134.29 | 22-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.334979E+10 | 30225.33 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.453245E+10 | 36837.63 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142740E+11 | 42903.18 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.407966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.142740E+11 | 42903.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.981533E+10 | 118477.02 | 06-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.941955E+10 | 118614.23 | 04-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.584521E+10 | 117973.05 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.473290E+10 | 118906.79 | 03-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.689551E+09 | 107361.13 | 03-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.209646E+09 | 112251.25 | 22-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471325E+10 | 118540.26 | 31-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.709294E+10 | 119278.69 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125751E+11 | 118361.31 | 11-DEC-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.550935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.125751E+11 | 119278.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125195E+11 | 34268.35 | 07-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125183E+11 | 34263.71 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.948416E+10 | 34290.16 | 02-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.703650E+10 | 33994.43 | 15-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181839E+10 | 30518.00 | 02-MAY-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36634751.79 | 3819.76 | 10-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35182212.00 | 3963.98 | 03-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132341E+09 | 16212.94 | 23-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111113E+10 | 32901.58 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.759088E+10 | 34236.71 | 23-OCT-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102363E+11 | 34336.13 | 27-NOV-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164721E+11 | 34224.32 | 19-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.789914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 35182212.00 | 3819.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.164721E+11 | 34336.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.696870E+10 | 25765.01 | 05-JAN-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.680932E+10 | 25777.79 | 08-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.526651E+10 | 25750.84 | 04-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.399867E+10 | 25716.12 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.846164E+09 | 21642.00 | 03-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16278516.20 | 2637.82 | 09-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 26269685.71 | 2939.45 | 03-JUL-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 62795254.10 | 9942.26 | 23-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.517409E+09 | 23366.59 | 22-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.455146E+10 | 25734.39 | 31-OCT-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.593806E+10 | 25770.25 | 02-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.974592E+10 | 25767.74 | 08-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.447476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 16278516.20 | 2637.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.974592E+10 | 25777.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.681963E+10 | 34685.87 | 04-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.785611E+10 | 34763.35 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.716572E+10 | 34790.18 | 02-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.618837E+10 | 34490.14 | 15-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181735E+10 | 30794.25 | 02-MAY-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125433E+09 | 14415.19 | 09-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 61991946.91 | 5239.84 | 06-JUL-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122701E+09 | 12928.36 | 23-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.816481E+09 | 33381.35 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.575857E+10 | 34735.95 | 23-OCT-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.613891E+10 | 34836.81 | 27-NOV-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102361E+11 | 34652.24 | 07-DEC-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.531074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 61991946.91 | 5239.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102361E+11 | 34836.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.703731E+10 | 28439.04 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.703524E+10 | 28502.98 | 09-FEB-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.577880E+10 | 28493.20 | 04-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.430602E+10 | 28435.23 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143750E+10 | 23910.83 | 03-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137491E+09 | 4840.87 | 10-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84567882.36 | 4292.49 | 29-JUL-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174363E+09 | 7325.15 | 23-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.883228E+09 | 25831.44 | 22-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.478082E+10 | 28474.96 | 31-OCT-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.596749E+10 | 28500.51 | 29-NOV-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.940341E+10 | 28497.54 | 19-DEC-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.470262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 84567882.36 | 4292.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.940341E+10 | 28502.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.400442E+10 | 0.400442E+10 | 76782.80 | 20-JAN-14:00 | 76782.80 | 0.00 |
February | 0.00 | 0.00 | 0.130829E+10 | 0.130829E+10 | 51891.35 | 26-FEB-15:51 | 51891.35 | 0.00 |
March | 0.00 | 0.00 | 0.110260E+11 | 0.110260E+11 | 115077.71 | 14-MAR-13:00 | 115077.71 | 0.00 |
April | 0.00 | 0.00 | 0.118068E+11 | 0.118068E+11 | 92839.77 | 19-APR-13:30 | 92839.77 | 0.00 |
May | 0.00 | 0.00 | 0.410908E+11 | 0.410908E+11 | 125024.98 | 31-MAY-15:20 | 125024.98 | 0.03 |
June | 0.00 | 0.00 | 0.126629E+12 | 0.126247E+12 | 173096.05 | 26-JUN-14:40 | 173096.05 | 0.29 |
July | 0.00 | 0.00 | 0.136349E+12 | 0.132753E+12 | 164026.20 | 17-JUL-13:40 | 164026.20 | 0.32 |
August | 0.00 | 0.00 | 0.138471E+12 | 0.137596E+12 | 174232.25 | 16-AUG-14:50 | 174232.25 | 0.35 |
September | 0.00 | 0.00 | 0.888651E+11 | 0.888651E+11 | 149612.31 | 12-SEP-15:50 | 149612.31 | 0.06 |
October | 0.00 | 0.00 | 0.186088E+11 | 0.186088E+11 | 135888.84 | 10-OCT-15:30 | 135888.84 | 0.00 |
November | 0.00 | 0.00 | 0.746031E+10 | 0.746031E+10 | 99110.11 | 07-NOV-14:30 | 99110.11 | 0.00 |
December | 0.00 | 0.00 | 0.449252E+10 | 0.449252E+10 | 89098.95 | 01-DEC-13:55 | 89098.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.590112E+12 | 0.585260E+12 | 0.09 | |||
Minimum of Months | 0.00 | 0.00 | 0.130829E+10 | 0.130829E+10 | 51891.35 | 51891.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.138471E+12 | 0.137596E+12 | 174232.25 | 174232.25 | 0.35 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.454386E+11 | 0.454386E+11 | 797044.62 | 24-JAN-15:03 | 797044.62 | 0.00 |
February | 0.00 | 0.00 | 0.308652E+11 | 0.308652E+11 | 766243.65 | 17-FEB-15:01 | 766243.65 | 0.00 |
March | 0.00 | 0.00 | 0.105745E+12 | 0.105745E+12 | 1015059.33 | 14-MAR-13:00 | 1015059.33 | 0.00 |
April | 0.00 | 0.00 | 0.984448E+11 | 0.984448E+11 | 733084.87 | 20-APR-13:00 | 733084.87 | 0.00 |
May | 0.00 | 0.00 | 0.377351E+12 | 0.377351E+12 | 1186539.56 | 16-MAY-14:05 | 1186539.56 | 0.03 |
June | 0.00 | 0.00 | 0.114350E+13 | 0.114006E+13 | 1597773.80 | 26-JUN-14:20 | 1597773.80 | 0.28 |
July | 0.00 | 0.00 | 0.115971E+13 | 0.113087E+13 | 1524303.49 | 18-JUL-15:00 | 1524303.49 | 0.30 |
August | 0.00 | 0.00 | 0.112500E+13 | 0.111937E+13 | 1594578.95 | 16-AUG-15:20 | 1594578.95 | 0.31 |
September | 0.00 | 0.00 | 0.793099E+12 | 0.793099E+12 | 1422396.57 | 12-SEP-16:00 | 1422396.57 | 0.06 |
October | 0.00 | 0.00 | 0.183162E+12 | 0.183162E+12 | 1199011.95 | 11-OCT-15:00 | 1199011.95 | 0.00 |
November | 0.00 | 0.00 | 0.783584E+11 | 0.783584E+11 | 857770.75 | 07-NOV-15:02 | 857770.75 | 0.00 |
December | 0.00 | 0.00 | 0.436046E+11 | 0.436046E+11 | 744382.55 | 01-DEC-13:55 | 744382.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.518428E+13 | 0.514637E+13 | 0.08 | |||
Minimum of Months | 0.00 | 0.00 | 0.308652E+11 | 0.308652E+11 | 733084.87 | 733084.87 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.115971E+13 | 0.114006E+13 | 1597773.80 | 1597773.80 | 0.31 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.279982E+10 | 0.279982E+10 | 71931.06 | 20-JAN-13:20 | 71931.06 | 0.00 |
February | 0.00 | 0.00 | 0.105001E+10 | 0.105001E+10 | 49285.74 | 26-FEB-12:42 | 49285.74 | 0.00 |
March | 0.00 | 0.00 | 0.902552E+10 | 0.902552E+10 | 119848.17 | 14-MAR-13:00 | 119848.17 | 0.00 |
April | 0.00 | 0.00 | 0.954250E+10 | 0.954250E+10 | 79926.17 | 19-APR-13:40 | 79926.17 | 0.00 |
May | 0.00 | 0.00 | 0.410394E+11 | 0.410394E+11 | 157221.66 | 31-MAY-15:20 | 157221.66 | 0.03 |
June | 0.00 | 0.00 | 0.137473E+12 | 0.137188E+12 | 215069.20 | 26-JUN-15:20 | 215069.20 | 0.28 |
July | 0.00 | 0.00 | 0.136129E+12 | 0.133465E+12 | 192028.86 | 17-JUL-13:50 | 192028.86 | 0.30 |
August | 0.00 | 0.00 | 0.132010E+12 | 0.131616E+12 | 209531.53 | 16-AUG-14:30 | 209531.53 | 0.31 |
September | 0.00 | 0.00 | 0.867169E+11 | 0.867169E+11 | 169852.99 | 12-SEP-14:05 | 169852.99 | 0.06 |
October | 0.00 | 0.00 | 0.157543E+11 | 0.157543E+11 | 143730.87 | 11-OCT-15:00 | 143730.87 | 0.00 |
November | 0.00 | 0.00 | 0.503686E+10 | 0.503686E+10 | 77614.74 | 07-NOV-14:40 | 77614.74 | 0.00 |
December | 0.00 | 0.00 | 0.317106E+10 | 0.317106E+10 | 68460.24 | 01-DEC-14:00 | 68460.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.579748E+12 | 0.576406E+12 | 0.08 | |||
Minimum of Months | 0.00 | 0.00 | 0.105001E+10 | 0.105001E+10 | 49285.74 | 49285.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.137473E+12 | 0.137188E+12 | 215069.20 | 215069.20 | 0.31 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.894344E+10 | 0.889014E+10 | 100665.88 | 04-JAN-05:17 | 100665.88 | 0.00 |
February | 0.00 | 0.00 | 0.417485E+10 | 0.417485E+10 | 121228.42 | 21-FEB-04:55 | 121228.42 | 0.00 |
March | 0.00 | 0.00 | 0.944969E+10 | 0.944969E+10 | 109241.69 | 01-MAR-05:46 | 109241.69 | 0.00 |
April | 0.00 | 0.00 | 0.114192E+11 | 0.114192E+11 | 97287.68 | 24-APR-04:59 | 97287.68 | 0.00 |
May | 0.00 | 0.00 | 0.274727E+11 | 0.272175E+11 | 75239.47 | 22-MAY-13:42 | 59338.89 | 0.04 |
June | 0.00 | 0.00 | 0.621576E+11 | 0.601084E+11 | 92470.17 | 21-JUN-04:11 | 39752.86 | 0.24 |
July | 0.00 | 0.00 | 0.656468E+11 | 0.605168E+11 | 97114.04 | 28-JUL-05:27 | 44221.00 | 0.26 |
August | 0.00 | 0.00 | 0.688282E+11 | 0.665467E+11 | 106537.86 | 07-AUG-02:14 | 106537.86 | 0.26 |
September | 0.00 | 0.00 | 0.521530E+11 | 0.519541E+11 | 127231.44 | 04-SEP-13:21 | 127231.44 | 0.06 |
October | 0.00 | 0.00 | 0.189234E+11 | 0.189111E+11 | 130100.22 | 09-OCT-08:38 | 130100.22 | 0.00 |
November | 0.00 | 0.00 | 0.104830E+11 | 0.104830E+11 | 115817.77 | 13-NOV-01:59 | 115817.77 | 0.00 |
December | 0.00 | 0.00 | 0.761540E+10 | 0.761540E+10 | 103530.87 | 20-DEC-05:48 | 103530.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.347267E+12 | 0.337287E+12 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 0.417485E+10 | 0.417485E+10 | 75239.47 | 39752.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.688282E+11 | 0.665467E+11 | 130100.22 | 130100.22 | 0.26 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4944593.79 | 4944593.79 | 117.43 | 09-JAN-15:02 | 117.43 | 0.05 |
February | 0.00 | 0.00 | 0.157880E+12 | 0.157880E+12 | 301637.03 | 18-FEB-13:08 | 301637.03 | 0.00 |
March | 0.00 | 0.00 | 0.207748E+12 | 0.207748E+12 | 289931.25 | 14-MAR-13:00 | 289931.25 | 0.00 |
April | 0.00 | 0.00 | 0.192450E+12 | 0.192450E+12 | 258317.24 | 08-APR-13:47 | 258317.24 | 0.00 |
May | 0.00 | 0.00 | 0.192044E+11 | 0.192044E+11 | 245964.04 | 31-MAY-23:46 | 245964.04 | 0.08 |
June | 0.00 | 0.00 | 0.329468E+12 | 0.318910E+12 | 396195.10 | 22-JUN-13:10 | 217879.21 | 0.54 |
July | 0.00 | 0.00 | 0.458445E+12 | 0.442875E+12 | 459601.40 | 31-JUL-16:21 | 193986.00 | 0.66 |
August | 0.00 | 0.00 | 0.554557E+12 | 0.549461E+12 | 478532.07 | 09-AUG-12:18 | 478532.07 | 0.66 |
September | 0.00 | 0.00 | 0.646257E+11 | 0.646257E+11 | 230017.63 | 30-SEP-23:16 | 230017.63 | 0.22 |
October | 0.00 | 0.00 | 0.200059E+12 | 0.200059E+12 | 324296.04 | 11-OCT-17:11 | 324296.04 | 0.01 |
November | 0.00 | 0.00 | 0.202550E+12 | 0.202550E+12 | 288917.03 | 03-NOV-13:32 | 288917.03 | 0.00 |
December | 0.00 | 0.00 | 0.217590E+12 | 0.217590E+12 | 277270.35 | 14-DEC-15:14 | 277270.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.260458E+13 | 0.257336E+13 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 4944593.79 | 4944593.79 | 117.43 | 117.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.554557E+12 | 0.549461E+12 | 478532.07 | 478532.07 | 0.66 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.663993E+10 | 0.663963E+10 | 4136.81 | 23-JAN-16:35 | 4136.81 | 0.00 |
February | 0.00 | 0.00 | 0.103151E+11 | 0.103151E+11 | 5982.74 | 17-FEB-16:53 | 5982.74 | 0.00 |
March | 0.00 | 0.00 | 0.171763E+11 | 0.171763E+11 | 8539.60 | 31-MAR-23:53 | 8539.60 | 0.00 |
April | 0.00 | 0.00 | 0.217623E+11 | 0.217601E+11 | 9786.62 | 08-APR-17:53 | 9786.62 | 0.00 |
May | 0.00 | 0.00 | 0.810801E+10 | 0.809753E+10 | 4969.96 | 31-MAY-23:51 | 4969.96 | 0.00 |
June | 0.00 | 0.00 | 0.134828E+11 | 0.134271E+11 | 6901.87 | 30-JUN-23:25 | 6901.87 | 0.00 |
July | 0.00 | 0.00 | 0.190368E+11 | 0.189601E+11 | 8774.40 | 31-JUL-24:00 | 8746.34 | 0.00 |
August | 0.00 | 0.00 | 0.241491E+11 | 0.240903E+11 | 10209.97 | 13-AUG-18:13 | 10209.97 | 0.00 |
September | 0.00 | 0.00 | 0.831523E+10 | 0.830958E+10 | 4761.99 | 30-SEP-24:00 | 4761.99 | 0.00 |
October | 0.00 | 0.00 | 0.124425E+11 | 0.124421E+11 | 6246.15 | 09-OCT-16:54 | 6246.15 | 0.00 |
November | 0.00 | 0.00 | 0.167252E+11 | 0.167252E+11 | 8084.15 | 07-NOV-16:11 | 8084.15 | 0.00 |
December | 0.00 | 0.00 | 0.217296E+11 | 0.217296E+11 | 9665.61 | 01-DEC-16:00 | 9665.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.179883E+12 | 0.179673E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.663993E+10 | 0.663963E+10 | 4136.81 | 4136.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.241491E+11 | 0.240903E+11 | 10209.97 | 10209.97 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.483177E+11 | 0.483146E+11 | 39082.58 | 23-JAN-16:35 | 39082.58 | 0.00 |
February | 0.00 | 0.00 | 0.882491E+11 | 0.882491E+11 | 58168.30 | 17-FEB-16:53 | 58168.30 | 0.00 |
March | 0.00 | 0.00 | 0.154914E+12 | 0.154914E+12 | 80272.40 | 31-MAR-23:15 | 80272.40 | 0.00 |
April | 0.00 | 0.00 | 0.198628E+12 | 0.198607E+12 | 94496.57 | 07-APR-17:50 | 94496.57 | 0.00 |
May | 0.00 | 0.00 | 0.729529E+11 | 0.728483E+11 | 47392.85 | 31-MAY-23:41 | 47392.85 | 0.00 |
June | 0.00 | 0.00 | 0.128339E+12 | 0.127783E+12 | 67600.59 | 30-JUN-23:55 | 67600.59 | 0.00 |
July | 0.00 | 0.00 | 0.181010E+12 | 0.180245E+12 | 83002.79 | 31-JUL-24:00 | 82810.49 | 0.00 |
August | 0.00 | 0.00 | 0.229343E+12 | 0.228761E+12 | 98254.76 | 11-AUG-18:10 | 98254.76 | 0.00 |
September | 0.00 | 0.00 | 0.749991E+11 | 0.749426E+11 | 43125.57 | 12-SEP-17:40 | 43125.57 | 0.00 |
October | 0.00 | 0.00 | 0.111047E+12 | 0.111043E+12 | 59557.24 | 05-OCT-16:50 | 59557.24 | 0.00 |
November | 0.00 | 0.00 | 0.148726E+12 | 0.148726E+12 | 77114.44 | 07-NOV-16:11 | 77114.44 | 0.00 |
December | 0.00 | 0.00 | 0.191104E+12 | 0.191104E+12 | 91857.16 | 01-DEC-16:00 | 91857.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.162763E+13 | 0.162554E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.483177E+11 | 0.483146E+11 | 39082.58 | 39082.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.229343E+12 | 0.228761E+12 | 98254.76 | 98254.76 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.278290E+10 | 0.278266E+10 | 3894.53 | 20-JAN-16:33 | 3894.53 | 0.00 |
February | 0.00 | 0.00 | 0.691079E+10 | 0.691079E+10 | 5825.94 | 17-FEB-16:53 | 5825.94 | 0.00 |
March | 0.00 | 0.00 | 0.138487E+11 | 0.138487E+11 | 7879.58 | 31-MAR-17:22 | 7879.58 | 0.00 |
April | 0.00 | 0.00 | 0.181824E+11 | 0.181805E+11 | 9563.17 | 07-APR-17:50 | 9563.17 | 0.00 |
May | 0.00 | 0.00 | 0.643086E+10 | 0.642049E+10 | 4578.65 | 31-MAY-23:11 | 4578.43 | 0.00 |
June | 0.00 | 0.00 | 0.126637E+11 | 0.126081E+11 | 6698.18 | 30-JUN-23:40 | 6698.18 | 0.00 |
July | 0.00 | 0.00 | 0.179686E+11 | 0.178922E+11 | 8332.89 | 01-JUL-18:40 | 8332.89 | 0.00 |
August | 0.00 | 0.00 | 0.227396E+11 | 0.226834E+11 | 9987.73 | 11-AUG-18:10 | 9987.73 | 0.00 |
September | 0.00 | 0.00 | 0.687683E+10 | 0.687129E+10 | 4522.27 | 10-SEP-17:22 | 4522.27 | 0.00 |
October | 0.00 | 0.00 | 0.928102E+10 | 0.928059E+10 | 6017.66 | 05-OCT-16:50 | 6017.66 | 0.00 |
November | 0.00 | 0.00 | 0.126826E+11 | 0.126826E+11 | 7721.35 | 07-NOV-16:11 | 7721.35 | 0.00 |
December | 0.00 | 0.00 | 0.168117E+11 | 0.168117E+11 | 9161.14 | 01-DEC-16:00 | 9161.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.147180E+12 | 0.146973E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.278290E+10 | 0.278266E+10 | 3894.53 | 3894.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.227396E+11 | 0.226834E+11 | 9987.73 | 9987.73 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 100343.49 | 2888159.97 | 02-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 113882.64 | 2758953.67 | 13-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 70473.32 | 2745258.37 | 01-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:03 | 47675.16 | 2593687.04 | 15-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8535.19 | 2578388.65 | 01-MAY-04:11 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 182.43 | 43291.31 | 09-JUN-05:08 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 91.94 | 30320.31 | 29-JUL-05:09 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 362.51 | 123054.20 | 23-AUG-05:01 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 4984.76 | 2450609.47 | 22-SEP-05:01 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 57060.87 | 2772657.12 | 25-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 76856.19 | 2569993.26 | 14-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 158618.16 | 2670756.45 | 06-DEC-05:01 |
Annual Sum or Average | 0.00 | 52985.53 | ||||
Minimum of Months | 0.00 | 0.00 | 91.94 | 30320.31 | ||
Maximum of Months | 0.00 | 0.00 | 158618.16 | 2888159.97 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 24593.86 | 1049887.46 | 25-JAN-14:50 | 227393.03 | 808826.01 | 18-JAN-05:11 |
February | 84587.97 | 1098268.26 | 23-FEB-14:29 | 141317.61 | 663505.13 | 22-FEB-21:31 |
March | 139868.18 | 1942091.54 | 14-MAR-13:25 | 1529.64 | 726676.15 | 01-MAR-00:01 |
April | 133931.99 | 1208896.17 | 19-APR-13:50 | 5532.38 | 665667.68 | 30-APR-24:00 |
May | 199133.97 | 2090849.26 | 18-MAY-13:05 | 213127.81 | 808747.37 | 29-MAY-13:50 |
June | 720964.89 | 2273235.44 | 26-JUN-14:30 | 35179.39 | 756244.81 | 05-JUN-22:11 |
July | 757134.53 | 2799440.28 | 31-JUL-15:51 | 6058.84 | 513562.39 | 30-JUL-20:14 |
August | 776590.61 | 3051561.98 | 15-AUG-12:52 | 5935.05 | 703573.56 | 09-AUG-03:30 |
September | 436277.52 | 2423401.85 | 13-SEP-12:10 | 166228.84 | 808697.13 | 23-SEP-00:30 |
October | 169415.86 | 2567900.44 | 10-OCT-13:02 | 125049.54 | 693511.02 | 09-OCT-22:51 |
November | 127469.42 | 1361489.00 | 05-NOV-14:13 | 2100.36 | 619604.02 | 01-NOV-00:11 |
December | 113068.24 | 1236512.51 | 01-DEC-14:00 | 2574.03 | 411478.98 | 05-DEC-18:01 |
Annual Sum or Average | 308223.95 | 77424.19 | ||||
Minimum of Months | 24593.86 | 1049887.46 | 1529.64 | 411478.98 | ||
Maximum of Months | 776590.61 | 3051561.98 | 227393.03 | 808826.01 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 27172.10 | 1048210.32 | 24-JAN-15:02 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 109382.95 | 1308385.60 | 18-FEB-12:42 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 242403.14 | 1798538.71 | 14-MAR-13:20 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 235009.81 | 1218214.34 | 19-APR-13:40 | 0.00 | 0.00 | 01-APR-00:03 |
May | 210522.96 | 1847698.53 | 31-MAY-13:10 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 747275.29 | 3788293.46 | 14-JUN-04:11 | 0.00 | 0.00 | 01-JUN-00:01 |
July | 799228.21 | 4353165.99 | 17-JUL-04:11 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 819022.68 | 3479633.03 | 01-AUG-04:11 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 450178.40 | 2529704.92 | 13-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 200704.05 | 2061383.04 | 11-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 232551.61 | 1347419.86 | 05-NOV-12:51 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 223477.82 | 1256147.68 | 14-DEC-15:05 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 359483.93 | 0.00 | ||||
Minimum of Months | 27172.10 | 1048210.32 | 0.00 | 0.00 | ||
Maximum of Months | 819022.68 | 4353165.99 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15209.29 | 54426.03 | 31-JAN-12:43 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 15488.42 | 54570.11 | 13-FEB-12:52 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 16221.18 | 54357.70 | 01-MAR-12:55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 14606.00 | 52666.96 | 03-APR-11:32 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14276.07 | 50263.19 | 01-MAY-11:23 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13773.60 | 47256.21 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 12102.70 | 44631.62 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 13048.56 | 43387.84 | 31-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12460.27 | 44814.18 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 13039.77 | 47514.10 | 31-OCT-11:59 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14031.16 | 50425.26 | 30-NOV-12:55 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 14279.23 | 52860.47 | 29-DEC-12:43 |
Annual Sum or Average | 0.00 | 14036.40 | ||||
Minimum of Months | 0.00 | 0.00 | 12102.70 | 43387.84 | ||
Maximum of Months | 0.00 | 0.00 | 16221.18 | 54570.11 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 25688.43 | 1129502.56 | 24-JAN-15:03 | 3289.60 | 174340.95 | 24-JAN-05:14 |
February | 99119.14 | 1148261.44 | 18-FEB-13:10 | 595.34 | 75855.34 | 21-FEB-10:48 |
March | 90636.32 | 2921789.71 | 14-MAR-12:50 | 5512.27 | 91806.75 | 21-MAR-11:31 |
April | 94619.25 | 1404285.61 | 19-APR-13:50 | 7404.17 | 145023.32 | 05-APR-02:20 |
May | 238376.25 | 3178182.32 | 31-MAY-13:30 | 1364.78 | 162221.57 | 03-MAY-04:14 |
June | 972950.37 | 3259717.29 | 28-JUN-15:20 | 38.75 | 33879.75 | 14-JUN-01:20 |
July | 1002076.88 | 3803064.39 | 31-JUL-15:51 | 655.65 | 106517.47 | 01-JUL-02:70 |
August | 1009250.42 | 3469615.41 | 15-AUG-12:52 | 597.46 | 97053.19 | 19-AUG-01:10 |
September | 573705.92 | 3252438.12 | 12-SEP-15:20 | 866.18 | 123715.98 | 24-SEP-01:40 |
October | 212281.17 | 3076149.16 | 11-OCT-11:05 | 193.78 | 69247.36 | 23-OCT-15:27 |
November | 70566.84 | 1546699.58 | 07-NOV-15:00 | 5167.86 | 85710.31 | 22-NOV-19:50 |
December | 45430.68 | 1431813.46 | 01-DEC-14:00 | 9718.48 | 155107.57 | 05-DEC-06:30 |
Annual Sum or Average | 371141.24 | 2965.13 | ||||
Minimum of Months | 25688.43 | 1129502.56 | 38.75 | 33879.75 | ||
Maximum of Months | 1009250.42 | 3803064.39 | 9718.48 | 174340.95 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.115270E+11 | 0.66 | 24715.14 | 04-JAN-06:01 | 1.96 |
February | 0.105834E+11 | 0.67 | 24715.14 | 15-FEB-06:01 | 1.96 |
March | 0.141421E+11 | 0.75 | 24715.14 | 21-MAR-05:01 | 1.95 |
April | 0.132067E+11 | 0.70 | 24715.14 | 05-APR-05:01 | 1.95 |
May | 0.147050E+11 | 0.75 | 22332.87 | 01-MAY-05:01 | 1.87 |
June | 0.208434E+11 | 0.92 | 32480.77 | 26-JUN-14:50 | 2.18 |
July | 0.213796E+11 | 0.91 | 32480.77 | 17-JUL-04:11 | 2.19 |
August | 0.246326E+11 | 1.01 | 32049.77 | 02-AUG-15:40 | 2.17 |
September | 0.177585E+11 | 0.83 | 25663.27 | 13-SEP-04:11 | 1.98 |
October | 0.139796E+11 | 0.72 | 23283.92 | 11-OCT-15:40 | 1.91 |
November | 0.132417E+11 | 0.72 | 24715.14 | 03-NOV-05:01 | 1.96 |
December | 0.121010E+11 | 0.68 | 24715.14 | 06-DEC-06:01 | 1.96 |
Annual Sum or Average | 0.188101E+12 | 0.78 | |||
Minimum of Months | 0.105834E+11 | 0.66 | 22332.87 | 1.87 | |
Maximum of Months | 0.246326E+11 | 1.01 | 32480.77 | 2.19 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.107419E+12 | 0.70 | 214122.52 | 21-JAN-06:02 | 1.90 |
February | 0.103389E+12 | 0.74 | 268792.05 | 18-FEB-06:01 | 2.10 |
March | 0.125252E+12 | 0.77 | 253943.14 | 08-MAR-06:01 | 2.05 |
April | 0.105558E+12 | 0.67 | 237132.83 | 29-APR-05:01 | 1.97 |
May | 0.132186E+12 | 0.73 | 248069.24 | 12-MAY-05:02 | 2.02 |
June | 0.186289E+12 | 0.89 | 301067.75 | 26-JUN-14:20 | 2.18 |
July | 0.176295E+12 | 0.84 | 300437.65 | 18-JUL-15:00 | 2.18 |
August | 0.188928E+12 | 0.88 | 259895.57 | 16-AUG-15:00 | 2.05 |
September | 0.152797E+12 | 0.80 | 237967.41 | 12-SEP-15:40 | 1.97 |
October | 0.119451E+12 | 0.71 | 271080.52 | 03-OCT-05:01 | 2.09 |
November | 0.105754E+12 | 0.69 | 271080.52 | 07-NOV-06:01 | 2.11 |
December | 0.109725E+12 | 0.74 | 135327.53 | 14-DEC-15:37 | 1.57 |
Annual Sum or Average | 0.161304E+13 | 0.76 | |||
Minimum of Months | 0.103389E+12 | 0.67 | 135327.53 | 1.57 | |
Maximum of Months | 0.188928E+12 | 0.89 | 301067.75 | 2.18 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.121420E+11 | 0.72 | 13743.74 | 02-JAN-04:01 | 1.38 |
February | 0.110976E+11 | 0.72 | 13743.74 | 01-FEB-05:01 | 1.38 |
March | 0.124222E+11 | 0.70 | 18791.11 | 15-MAR-15:20 | 1.58 |
April | 0.113489E+11 | 0.67 | 16080.90 | 07-APR-15:30 | 1.47 |
May | 0.118225E+11 | 0.61 | 19741.60 | 31-MAY-15:40 | 1.59 |
June | 0.179170E+11 | 0.76 | 30823.63 | 26-JUN-15:20 | 1.92 |
July | 0.166494E+11 | 0.71 | 24973.24 | 17-JUL-13:50 | 1.76 |
August | 0.178440E+11 | 0.74 | 27769.13 | 16-AUG-15:20 | 1.84 |
September | 0.136967E+11 | 0.66 | 22629.83 | 12-SEP-15:30 | 1.69 |
October | 0.115447E+11 | 0.64 | 19303.58 | 11-OCT-15:20 | 1.59 |
November | 0.110705E+11 | 0.66 | 13743.74 | 01-NOV-04:01 | 1.38 |
December | 0.123241E+11 | 0.74 | 13743.74 | 01-DEC-06:01 | 1.38 |
Annual Sum or Average | 0.159880E+12 | 0.69 | |||
Minimum of Months | 0.110705E+11 | 0.61 | 13743.74 | 1.38 | |
Maximum of Months | 0.179170E+11 | 0.76 | 30823.63 | 1.92 |
Report: FanReportMonthly
For: CAV_BAS SZVAV FAN
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.684209E+10 | 0.60 | 18639.08 | 02-JAN-04:01 | 2.20 |
February | 0.531979E+10 | 0.58 | 18639.08 | 01-FEB-06:01 | 2.22 |
March | 0.812767E+10 | 0.68 | 18639.08 | 01-MAR-05:46 | 2.21 |
April | 0.810479E+10 | 0.66 | 18639.08 | 01-APR-05:01 | 2.22 |
May | 0.807930E+10 | 0.67 | 18639.08 | 01-MAY-04:11 | 2.21 |
June | 0.786243E+10 | 0.72 | 18639.08 | 01-JUN-04:11 | 2.20 |
July | 0.815453E+10 | 0.68 | 18639.08 | 01-JUL-04:11 | 2.22 |
August | 0.108900E+11 | 0.81 | 18639.08 | 01-AUG-04:11 | 2.21 |
September | 0.106763E+11 | 0.80 | 18639.08 | 01-SEP-04:11 | 2.20 |
October | 0.105902E+11 | 0.74 | 18639.08 | 02-OCT-01:49 | 2.19 |
November | 0.103686E+11 | 0.73 | 18639.08 | 01-NOV-04:01 | 2.22 |
December | 0.814885E+10 | 0.64 | 18639.08 | 01-DEC-05:11 | 2.23 |
Annual Sum or Average | 0.103165E+12 | 0.69 | |||
Minimum of Months | 0.531979E+10 | 0.58 | 18639.08 | 2.19 | |
Maximum of Months | 0.108900E+11 | 0.81 | 18639.08 | 2.23 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SYS11 FAN
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.321046E+11 | 0.62 | 11986.49 | 01-JAN-00:05 | 0.62 |
February | 0.527126E+11 | 0.77 | 39922.34 | 01-FEB-00:03 | 1.04 |
March | 0.732526E+11 | 0.85 | 39922.34 | 01-MAR-00:02 | 1.04 |
April | 0.103378E+12 | 1.04 | 39922.34 | 01-APR-00:03 | 1.04 |
May | 0.321403E+11 | 0.62 | 39922.34 | 31-MAY-23:03 | 1.04 |
June | 0.445576E+11 | 0.70 | 39922.34 | 01-JUN-00:03 | 1.03 |
July | 0.752095E+11 | 0.87 | 39922.34 | 01-JUL-00:05 | 1.04 |
August | 0.103402E+12 | 1.02 | 39922.34 | 01-AUG-00:10 | 1.03 |
September | 0.310899E+11 | 0.62 | 39922.34 | 30-SEP-23:04 | 1.04 |
October | 0.592387E+11 | 0.78 | 39922.34 | 01-OCT-00:03 | 1.04 |
November | 0.713833E+11 | 0.86 | 39922.34 | 01-NOV-00:01 | 1.04 |
December | 0.106928E+12 | 1.04 | 39922.34 | 01-DEC-00:05 | 1.04 |
Annual Sum or Average | 0.785397E+12 | 0.82 | |||
Minimum of Months | 0.310899E+11 | 0.62 | 11986.49 | 0.62 | |
Maximum of Months | 0.106928E+12 | 1.04 | 39922.34 | 1.04 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.411898E+10 | 1.68 | 1537.85 | 01-JAN-00:05 | 1.67 |
February | 0.372037E+10 | 1.68 | 1537.85 | 01-FEB-00:15 | 1.67 |
March | 0.411898E+10 | 1.68 | 1537.85 | 01-MAR-00:11 | 1.67 |
April | 0.398611E+10 | 1.67 | 1537.85 | 01-APR-02:12 | 1.68 |
May | 0.411898E+10 | 1.67 | 1537.85 | 01-MAY-00:20 | 1.67 |
June | 0.398611E+10 | 1.67 | 1537.85 | 01-JUN-00:04 | 1.67 |
July | 0.411898E+10 | 1.67 | 1537.85 | 01-JUL-01:20 | 1.67 |
August | 0.411898E+10 | 1.67 | 1537.85 | 01-AUG-00:30 | 1.67 |
September | 0.398611E+10 | 1.67 | 1537.85 | 01-SEP-01:00 | 1.67 |
October | 0.411898E+10 | 1.68 | 1537.85 | 01-OCT-00:02 | 1.67 |
November | 0.398611E+10 | 1.68 | 1537.85 | 01-NOV-00:03 | 1.68 |
December | 0.411898E+10 | 1.68 | 1537.85 | 01-DEC-00:53 | 1.68 |
Annual Sum or Average | 0.484977E+11 | 1.67 | |||
Minimum of Months | 0.372037E+10 | 1.67 | 1537.85 | 1.67 | |
Maximum of Months | 0.411898E+10 | 1.68 | 1537.85 | 1.68 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.410074E+11 | 1.73 | 15310.42 | 01-JAN-00:47 | 1.72 |
February | 0.370390E+11 | 1.74 | 15310.42 | 01-FEB-00:07 | 1.73 |
March | 0.410074E+11 | 1.74 | 15310.42 | 07-MAR-17:25 | 1.74 |
April | 0.396846E+11 | 1.73 | 15310.42 | 05-APR-20:15 | 1.73 |
May | 0.410074E+11 | 1.73 | 15310.42 | 01-MAY-00:15 | 1.72 |
June | 0.396846E+11 | 1.73 | 15310.42 | 01-JUN-00:34 | 1.72 |
July | 0.410074E+11 | 1.73 | 15310.42 | 01-JUL-01:10 | 1.73 |
August | 0.410074E+11 | 1.73 | 15310.42 | 23-AUG-05:10 | 1.72 |
September | 0.396846E+11 | 1.73 | 15310.42 | 01-SEP-01:40 | 1.73 |
October | 0.410074E+11 | 1.73 | 15310.42 | 01-OCT-01:33 | 1.73 |
November | 0.396846E+11 | 1.73 | 15310.42 | 01-NOV-00:32 | 1.74 |
December | 0.410074E+11 | 1.74 | 15310.42 | 05-DEC-01:06 | 1.74 |
Annual Sum or Average | 0.482830E+12 | 1.73 | |||
Minimum of Months | 0.370390E+11 | 1.73 | 15310.42 | 1.72 | |
Maximum of Months | 0.410074E+11 | 1.74 | 15310.42 | 1.74 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.410035E+10 | 1.68 | 1530.90 | 03-JAN-09:33 | 1.67 |
February | 0.370354E+10 | 1.68 | 1530.90 | 01-FEB-23:43 | 1.68 |
March | 0.410035E+10 | 1.68 | 1530.90 | 02-MAR-22:10 | 1.68 |
April | 0.396808E+10 | 1.67 | 1530.90 | 04-APR-15:30 | 1.68 |
May | 0.410035E+10 | 1.67 | 1530.90 | 01-MAY-13:18 | 1.67 |
June | 0.396808E+10 | 1.67 | 1530.90 | 11-JUN-15:59 | 1.68 |
July | 0.410035E+10 | 1.67 | 1530.90 | 01-JUL-15:32 | 1.68 |
August | 0.410035E+10 | 1.67 | 1530.90 | 01-AUG-02:50 | 1.67 |
September | 0.396808E+10 | 1.67 | 1530.90 | 01-SEP-04:00 | 1.67 |
October | 0.410035E+10 | 1.68 | 1530.90 | 01-OCT-05:49 | 1.67 |
November | 0.396808E+10 | 1.68 | 1530.90 | 01-NOV-12:57 | 1.67 |
December | 0.410035E+10 | 1.68 | 1530.90 | 01-DEC-01:33 | 1.68 |
Annual Sum or Average | 0.482783E+11 | 1.67 | |||
Minimum of Months | 0.370354E+10 | 1.67 | 1530.90 | 1.67 | |
Maximum of Months | 0.410035E+10 | 1.68 | 1530.90 | 1.68 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.258218E+09 | 0.232396E+09 | 4717.74 | 17-JAN-06:01 | 4245.96 | 4245.96 | 50.48 | 20.41 |
February | 0.263948E+09 | 0.237553E+09 | 4152.30 | 13-FEB-06:02 | 3737.07 | 3737.07 | 57.27 | 18.91 |
March | 0.185813E+09 | 0.167232E+09 | 4726.05 | 20-MAR-05:01 | 4253.45 | 4253.45 | 52.59 | 20.41 |
April | 0.124348E+09 | 0.111913E+09 | 4102.13 | 03-APR-05:01 | 3691.92 | 3691.92 | 50.97 | 18.83 |
May | 23521355.62 | 21169220.06 | 2913.62 | 01-MAY-05:01 | 2622.25 | 2622.25 | 42.25 | 15.19 |
June | 435486.07 | 391937.46 | 37.96 | 10-JUN-05:04 | 34.17 | 34.17 | 21.17 | 0.22 |
July | 223572.99 | 201215.69 | 27.38 | 29-JUL-05:09 | 24.64 | 24.64 | 19.98 | 0.16 |
August | 891375.01 | 802237.51 | 110.16 | 23-AUG-05:01 | 99.14 | 99.14 | 19.98 | 0.65 |
September | 12137004.70 | 10923304.23 | 2980.25 | 22-SEP-05:01 | 2682.22 | 2682.22 | 39.29 | 15.44 |
October | 0.142321E+09 | 0.128089E+09 | 4121.63 | 30-OCT-05:01 | 3709.46 | 3709.46 | 53.41 | 18.86 |
November | 0.187399E+09 | 0.168659E+09 | 3078.23 | 01-NOV-05:01 | 2770.41 | 2770.41 | 51.09 | 15.71 |
December | 0.443074E+09 | 0.398767E+09 | 4719.32 | 26-DEC-06:01 | 4247.39 | 4247.39 | 50.88 | 20.41 |
Annual Sum or Average | 0.164233E+10 | 0.147810E+10 | ||||||
Minimum of Months | 223572.99 | 201215.69 | 27.38 | 24.64 | 24.64 | 19.98 | 0.16 | |
Maximum of Months | 0.443074E+09 | 0.398767E+09 | 4726.05 | 4253.45 | 4253.45 | 57.27 | 20.41 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.316782E+09 | 0.285104E+09 | 4079.26 | 25-JAN-14:43 | 3671.33 | 3671.33 | 9.31 | 35.84 |
February | 0.172726E+10 | 0.155453E+10 | 5269.79 | 17-FEB-14:14 | 4742.81 | 4742.81 | 8.48 | 44.78 |
March | 0.303279E+10 | 0.272951E+10 | 6669.75 | 14-MAR-13:20 | 6002.77 | 6002.77 | 8.19 | 53.92 |
April | 0.273623E+10 | 0.246260E+10 | 3967.20 | 28-APR-15:30 | 3570.48 | 3570.48 | 8.48 | 34.95 |
May | 0.163350E+10 | 0.147015E+10 | 11276.29 | 31-MAY-12:30 | 10148.66 | 10148.66 | 8.13 | 76.50 |
June | 0.686818E+10 | 0.618136E+10 | 21520.15 | 21-JUN-05:01 | 19368.13 | 19368.13 | 9.07 | 107.43 |
July | 0.777355E+10 | 0.699619E+10 | 22973.36 | 24-JUL-04:11 | 20676.03 | 20676.03 | 10.46 | 110.78 |
August | 0.844438E+10 | 0.759994E+10 | 21543.97 | 31-AUG-05:01 | 19389.58 | 19389.58 | 10.58 | 107.48 |
September | 0.347464E+10 | 0.312718E+10 | 16054.90 | 12-SEP-14:00 | 14449.41 | 14449.41 | 6.74 | 92.99 |
October | 0.265893E+10 | 0.239303E+10 | 8501.88 | 11-OCT-12:00 | 7651.69 | 7651.69 | 8.21 | 64.04 |
November | 0.290844E+10 | 0.261760E+10 | 6249.88 | 15-NOV-14:22 | 5624.89 | 5624.89 | 8.98 | 51.32 |
December | 0.289992E+10 | 0.260992E+10 | 5486.17 | 15-DEC-12:50 | 4937.55 | 4937.55 | 9.67 | 46.28 |
Annual Sum or Average | 0.444746E+11 | 0.400271E+11 | ||||||
Minimum of Months | 0.316782E+09 | 0.285104E+09 | 3967.20 | 3570.48 | 3570.48 | 6.74 | 34.95 | |
Maximum of Months | 0.844438E+10 | 0.759994E+10 | 22973.36 | 20676.03 | 20676.03 | 10.58 | 110.78 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.499103E+10 | 0.449193E+10 | 10536.88 | 01-JAN-00:10 | 9483.19 | 9483.19 | 6.74 | 55.39 |
February | 0.895403E+10 | 0.805863E+10 | 10536.88 | 01-FEB-00:03 | 9483.19 | 9483.19 | 6.99 | 55.39 |
March | 0.272488E+11 | 0.245240E+11 | 10536.88 | 01-MAR-00:04 | 9483.19 | 9483.19 | 7.45 | 55.39 |
April | 0.240458E+11 | 0.216412E+11 | 10536.88 | 01-APR-00:10 | 9483.19 | 9483.19 | 10.34 | 55.39 |
May | 0.111258E+11 | 0.100132E+11 | 10536.88 | 01-MAY-01:25 | 9483.19 | 9483.19 | 6.84 | 55.39 |
June | 0.206028E+11 | 0.185425E+11 | 10536.88 | 01-JUN-00:01 | 9483.19 | 9483.19 | 7.28 | 55.39 |
July | 0.262297E+11 | 0.236068E+11 | 10536.88 | 01-JUL-00:05 | 9483.19 | 9483.19 | 10.09 | 55.39 |
August | 0.264154E+11 | 0.237738E+11 | 10536.88 | 01-AUG-00:10 | 9483.19 | 9483.19 | 10.29 | 55.39 |
September | 0.151957E+11 | 0.136761E+11 | 10536.88 | 01-SEP-00:50 | 9483.19 | 9483.19 | 6.80 | 55.39 |
October | 0.115567E+11 | 0.104010E+11 | 10536.88 | 01-OCT-00:03 | 9483.19 | 9483.19 | 7.86 | 55.39 |
November | 0.260706E+11 | 0.234636E+11 | 10536.88 | 01-NOV-00:03 | 9483.19 | 9483.19 | 7.79 | 55.39 |
December | 0.262974E+11 | 0.236676E+11 | 10536.88 | 01-DEC-00:05 | 9483.19 | 9483.19 | 10.52 | 55.39 |
Annual Sum or Average | 0.228734E+12 | 0.205860E+12 | ||||||
Minimum of Months | 0.499103E+10 | 0.449193E+10 | 10536.88 | 9483.19 | 9483.19 | 6.74 | 55.39 | |
Maximum of Months | 0.272488E+11 | 0.245240E+11 | 10536.88 | 9483.19 | 9483.19 | 10.52 | 55.39 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.75 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 6.79 | 0.00 |
March | 91670836.50 | 82503752.85 | 10536.88 | 13-MAR-14:30 | 9483.19 | 9483.19 | 13.56 | 27.69 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 9.97 | 0.00 |
May | 0.793427E+09 | 0.714084E+09 | 10536.88 | 04-MAY-14:20 | 9483.19 | 9483.19 | 13.19 | 27.69 |
June | 0.579107E+10 | 0.521196E+10 | 10536.88 | 01-JUN-10:50 | 9483.19 | 9483.19 | 13.73 | 27.69 |
July | 0.588739E+10 | 0.529865E+10 | 10536.88 | 01-JUL-09:50 | 9483.19 | 9483.19 | 12.93 | 27.69 |
August | 0.649767E+10 | 0.584790E+10 | 10536.88 | 02-AUG-09:50 | 9483.19 | 9483.19 | 14.03 | 27.69 |
September | 0.266162E+10 | 0.239545E+10 | 10536.88 | 05-SEP-13:30 | 9483.19 | 9483.19 | 13.62 | 27.69 |
October | 0.318741E+09 | 0.286866E+09 | 10536.88 | 10-OCT-12:30 | 9483.19 | 9483.19 | 13.61 | 27.69 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 7.76 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 10.52 | 0.00 |
Annual Sum or Average | 0.220416E+11 | 0.198374E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.75 | 0.00 | |
Maximum of Months | 0.649767E+10 | 0.584790E+10 | 10536.88 | 9483.19 | 9483.19 | 14.03 | 27.69 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 57.07 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 57.07 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 57.07 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:01 | 16.86 | 16.86 | 57.10 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:01 | 16.86 | 16.86 | 57.56 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:01 | 16.86 | 16.86 | 57.46 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:01 | 16.86 | 16.86 | 57.51 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:01 | 16.86 | 16.86 | 57.60 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:01 | 16.86 | 16.86 | 57.63 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:01 | 16.86 | 16.86 | 57.60 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 57.45 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 57.23 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 57.07 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.63 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128176E+11 | 0.115359E+11 | 27289.12 | 24-JAN-15:03 | 24560.21 | 24560.21 | 24.55 | 78.35 |
February | 0.231253E+11 | 0.208128E+11 | 27290.25 | 18-FEB-13:10 | 24561.23 | 24561.23 | 24.61 | 78.35 |
March | 0.705453E+11 | 0.634908E+11 | 54621.89 | 14-MAR-12:50 | 49159.70 | 49159.70 | 25.56 | 156.71 |
April | 0.620926E+11 | 0.558833E+11 | 27306.88 | 19-APR-13:50 | 24576.19 | 24576.19 | 25.39 | 78.35 |
May | 0.299081E+11 | 0.269173E+11 | 54639.80 | 31-MAY-13:30 | 49175.82 | 49175.82 | 25.95 | 156.71 |
June | 0.668459E+11 | 0.601613E+11 | 54645.50 | 28-JUN-15:20 | 49180.95 | 49180.95 | 26.08 | 156.71 |
July | 0.822838E+11 | 0.740554E+11 | 54683.52 | 31-JUL-15:51 | 49215.17 | 49215.17 | 26.91 | 156.71 |
August | 0.846719E+11 | 0.762047E+11 | 54660.18 | 15-AUG-12:52 | 49194.17 | 49194.17 | 26.40 | 156.71 |
September | 0.452027E+11 | 0.406824E+11 | 54645.00 | 12-SEP-15:20 | 49180.50 | 49180.50 | 26.07 | 156.71 |
October | 0.306261E+11 | 0.275635E+11 | 54632.67 | 11-OCT-11:05 | 49169.41 | 49169.41 | 25.80 | 156.71 |
November | 0.671729E+11 | 0.604556E+11 | 27316.85 | 07-NOV-15:00 | 24585.17 | 24585.17 | 25.82 | 78.35 |
December | 0.677429E+11 | 0.609686E+11 | 27308.81 | 01-DEC-14:00 | 24577.93 | 24577.93 | 25.47 | 78.35 |
Annual Sum or Average | 0.643035E+12 | 0.578732E+12 | ||||||
Minimum of Months | 0.128176E+11 | 0.115359E+11 | 27289.12 | 24560.21 | 24560.21 | 24.55 | 78.35 | |
Maximum of Months | 0.846719E+11 | 0.762047E+11 | 54683.52 | 49215.17 | 49215.17 | 26.91 | 156.71 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 31.00 | 31.00 | 100343.49 | 2888159.97 | 02-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 27.85 | 27.85 | 113882.64 | 2758953.67 | 13-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 26.02 | 26.02 | 70473.32 | 2745258.37 | 01-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.72 | 23.72 | 47675.16 | 2593687.04 | 15-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.64 | 20.64 | 8535.19 | 2578388.65 | 01-MAY-04:11 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 22.04 | 22.04 | 182.43 | 43291.31 | 09-JUN-05:08 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 20.33 | 20.33 | 91.94 | 30320.31 | 29-JUL-05:09 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 19.72 | 19.72 | 362.51 | 123054.20 | 23-AUG-05:01 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.15 | 21.15 | 4984.76 | 2450609.47 | 22-SEP-05:01 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 21.44 | 21.44 | 57060.87 | 2772657.12 | 25-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 34.39 | 81.20 | 76856.19 | 2569993.26 | 14-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 28.94 | 28.94 | 158618.16 | 2670756.45 | 06-DEC-05:01 |
Annual Sum or Average | 0.00 | 52985.53 | ||||||
Minimum of Months | 0.00 | 0.00 | 19.72 | 19.72 | 91.94 | 30320.31 | ||
Maximum of Months | 0.00 | 0.00 | 34.39 | 81.20 | 158618.16 | 2888159.97 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 24593.86 | 1049887.46 | 25-JAN-14:50 | 11.39 | 6.87 | 227393.03 | 808826.01 | 18-JAN-05:11 |
February | 84587.97 | 1098268.26 | 23-FEB-14:29 | 11.50 | 6.77 | 141317.61 | 663505.13 | 22-FEB-21:31 |
March | 139868.18 | 1942091.54 | 14-MAR-13:25 | 10.88 | 6.70 | 1529.64 | 726676.15 | 01-MAR-00:01 |
April | 133931.99 | 1208896.17 | 19-APR-13:50 | 11.91 | 6.70 | 5532.38 | 665667.68 | 30-APR-24:00 |
May | 199133.97 | 2090849.26 | 18-MAY-13:05 | 11.21 | 6.70 | 213127.81 | 808747.37 | 29-MAY-13:50 |
June | 720964.89 | 2273235.44 | 26-JUN-14:30 | 11.60 | 6.70 | 35179.39 | 756244.81 | 05-JUN-22:11 |
July | 757134.53 | 2799440.28 | 31-JUL-15:51 | 12.73 | 6.70 | 6058.84 | 513562.39 | 30-JUL-20:14 |
August | 776590.61 | 3051561.98 | 15-AUG-12:52 | 13.28 | 6.70 | 5935.05 | 703573.56 | 09-AUG-03:30 |
September | 436277.52 | 2423401.85 | 13-SEP-12:10 | 11.92 | 6.70 | 166228.84 | 808697.13 | 23-SEP-00:30 |
October | 169415.86 | 2567900.44 | 10-OCT-13:02 | 12.23 | 6.70 | 125049.54 | 693511.02 | 09-OCT-22:51 |
November | 127469.42 | 1361489.00 | 05-NOV-14:13 | 12.57 | 6.70 | 2100.36 | 619604.02 | 01-NOV-00:11 |
December | 113068.24 | 1236512.51 | 01-DEC-14:00 | 12.03 | 6.70 | 2574.03 | 411478.98 | 05-DEC-18:01 |
Annual Sum or Average | 308223.95 | 77424.19 | ||||||
Minimum of Months | 24593.86 | 1049887.46 | 10.88 | 6.70 | 1529.64 | 411478.98 | ||
Maximum of Months | 776590.61 | 3051561.98 | 13.28 | 6.87 | 227393.03 | 808826.01 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 27172.10 | 1048210.32 | 24-JAN-15:02 | 14.65 | 6.92 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 109382.95 | 1308385.60 | 18-FEB-12:42 | 15.24 | 6.78 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 242403.14 | 1798538.71 | 14-MAR-13:20 | 14.67 | 8.55 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 235009.81 | 1218214.34 | 19-APR-13:40 | 17.64 | 6.70 | 0.00 | 0.00 | 01-APR-00:03 |
May | 210522.96 | 1847698.53 | 31-MAY-13:10 | 12.54 | 8.25 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 747275.29 | 3788293.46 | 14-JUN-04:11 | 16.92 | 12.20 | 0.00 | 0.00 | 01-JUN-00:01 |
July | 799228.21 | 4353165.99 | 17-JUL-04:11 | 17.70 | 12.67 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 819022.68 | 3479633.03 | 01-AUG-04:11 | 16.13 | 11.93 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 450178.40 | 2529704.92 | 13-SEP-05:02 | 15.20 | 10.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 200704.05 | 2061383.04 | 11-OCT-12:00 | 14.39 | 8.14 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 232551.61 | 1347419.86 | 05-NOV-12:51 | 17.70 | 9.72 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 223477.82 | 1256147.68 | 14-DEC-15:05 | 14.26 | 7.12 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 359483.93 | 0.00 | ||||||
Minimum of Months | 27172.10 | 1048210.32 | 12.54 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 819022.68 | 4353165.99 | 17.70 | 12.67 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 58.03 | 58.03 | 15209.29 | 54426.03 | 31-JAN-12:43 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 57.46 | 57.46 | 15488.42 | 54570.11 | 13-FEB-12:52 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 57.46 | 57.46 | 16221.18 | 54357.70 | 01-MAR-12:55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 57.53 | 57.53 | 14606.00 | 52666.96 | 03-APR-11:32 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 58.13 | 58.13 | 14276.07 | 50263.19 | 01-MAY-11:23 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 57.80 | 57.80 | 13773.60 | 47256.21 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 57.92 | 57.92 | 12102.70 | 44631.62 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.99 | 57.99 | 13048.56 | 43387.84 | 31-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.98 | 57.98 | 12460.27 | 44814.18 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 57.91 | 57.91 | 13039.77 | 47514.10 | 31-OCT-11:59 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 57.79 | 57.79 | 14031.16 | 50425.26 | 30-NOV-12:55 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 57.65 | 57.65 | 14279.23 | 52860.47 | 29-DEC-12:43 |
Annual Sum or Average | 0.00 | 14036.40 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.46 | 57.46 | 12102.70 | 43387.84 | ||
Maximum of Months | 0.00 | 0.00 | 58.13 | 58.13 | 16221.18 | 54570.11 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 25688.43 | 1129502.56 | 24-JAN-15:03 | 24.55 | 21.10 | 3289.60 | 174340.95 | 24-JAN-05:14 |
February | 99119.14 | 1148261.44 | 18-FEB-13:10 | 24.61 | 21.10 | 595.34 | 75855.34 | 21-FEB-10:48 |
March | 90636.32 | 2921789.71 | 14-MAR-12:50 | 25.56 | 21.10 | 5512.27 | 91806.75 | 21-MAR-11:31 |
April | 94619.25 | 1404285.61 | 19-APR-13:50 | 25.39 | 21.10 | 7404.17 | 145023.32 | 05-APR-02:20 |
May | 238376.25 | 3178182.32 | 31-MAY-13:30 | 25.95 | 21.10 | 1364.78 | 162221.57 | 03-MAY-04:14 |
June | 972950.37 | 3259717.29 | 28-JUN-15:20 | 26.08 | 21.10 | 38.75 | 33879.75 | 14-JUN-01:20 |
July | 1002076.88 | 3803064.39 | 31-JUL-15:51 | 26.91 | 22.25 | 655.65 | 106517.47 | 01-JUL-02:70 |
August | 1009250.42 | 3469615.41 | 15-AUG-12:52 | 26.40 | 21.10 | 597.46 | 97053.19 | 19-AUG-01:10 |
September | 573705.92 | 3252438.12 | 12-SEP-15:20 | 26.07 | 21.10 | 866.18 | 123715.98 | 24-SEP-01:40 |
October | 212281.17 | 3076149.16 | 11-OCT-11:05 | 25.80 | 21.10 | 193.78 | 69247.36 | 23-OCT-15:27 |
November | 70566.84 | 1546699.58 | 07-NOV-15:00 | 25.82 | 21.10 | 5167.86 | 85710.31 | 22-NOV-19:50 |
December | 45430.68 | 1431813.46 | 01-DEC-14:00 | 25.47 | 21.10 | 9718.48 | 155107.57 | 05-DEC-06:30 |
Annual Sum or Average | 371141.24 | 2965.13 | ||||||
Minimum of Months | 25688.43 | 1129502.56 | 24.55 | 21.10 | 38.75 | 33879.75 | ||
Maximum of Months | 1009250.42 | 3803064.39 | 26.91 | 22.25 | 9718.48 | 174340.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.844894E+10 | 0.00 | 0.400442E+10 | 0.115270E+11 | 0.00 | 0.00 |
February | 0.885308E+10 | 0.00 | 0.130829E+10 | 0.105834E+11 | 0.00 | 0.00 |
March | 0.487583E+10 | 0.00 | 0.110260E+11 | 0.141421E+11 | 0.00 | 0.00 |
April | 0.247662E+10 | 0.00 | 0.118068E+11 | 0.132067E+11 | 0.00 | 0.00 |
May | 0.246778E+09 | 0.00 | 0.410908E+11 | 0.147050E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.126629E+12 | 0.208434E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.136349E+12 | 0.213796E+11 | 0.00 | 0.00 |
August | 472922.26 | 0.00 | 0.138471E+12 | 0.246326E+11 | 0.00 | 0.00 |
September | 0.182366E+09 | 0.00 | 0.888651E+11 | 0.177585E+11 | 0.00 | 0.00 |
October | 0.414536E+10 | 0.00 | 0.186088E+11 | 0.139796E+11 | 0.00 | 0.00 |
November | 0.493466E+10 | 0.00 | 0.746031E+10 | 0.132417E+11 | 0.00 | 0.00 |
December | 0.134410E+11 | 0.00 | 0.449252E+10 | 0.121010E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.476051E+11 | 0.00 | 0.590112E+12 | 0.188101E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.130829E+10 | 0.105834E+11 | 0.00 | 0.00 |
Maximum of Months | 0.134410E+11 | 0.00 | 0.138471E+12 | 0.246326E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.211112E+12 | 0.00 | 0.454386E+11 | 0.107419E+12 | 0.00 | 0.00 |
February | 0.217797E+12 | 0.00 | 0.308652E+11 | 0.103389E+12 | 0.00 | 0.00 |
March | 0.148321E+12 | 0.00 | 0.105745E+12 | 0.125252E+12 | 0.00 | 0.00 |
April | 0.941131E+11 | 0.00 | 0.984448E+11 | 0.105558E+12 | 0.00 | 0.00 |
May | 0.160575E+11 | 0.00 | 0.377351E+12 | 0.132186E+12 | 0.00 | 0.00 |
June | 0.171745E+09 | 0.00 | 0.114350E+13 | 0.186289E+12 | 0.00 | 0.00 |
July | 44500152.13 | 0.00 | 0.115971E+13 | 0.176295E+12 | 0.00 | 0.00 |
August | 0.472000E+09 | 0.00 | 0.112500E+13 | 0.188928E+12 | 0.00 | 0.00 |
September | 0.920442E+10 | 0.00 | 0.793099E+12 | 0.152797E+12 | 0.00 | 0.00 |
October | 0.118521E+12 | 0.00 | 0.183162E+12 | 0.119451E+12 | 0.00 | 0.00 |
November | 0.155462E+12 | 0.00 | 0.783584E+11 | 0.105754E+12 | 0.00 | 0.00 |
December | 0.341054E+12 | 0.00 | 0.436046E+11 | 0.109725E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.131233E+13 | 0.00 | 0.518428E+13 | 0.161304E+13 | 0.00 | 0.00 |
Minimum of Months | 44500152.13 | 0.00 | 0.308652E+11 | 0.103389E+12 | 0.00 | 0.00 |
Maximum of Months | 0.341054E+12 | 0.00 | 0.115971E+13 | 0.188928E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.505987E+11 | 0.00 | 0.279982E+10 | 0.121420E+11 | 0.00 | 0.00 |
February | 0.504015E+11 | 0.00 | 0.105001E+10 | 0.110976E+11 | 0.00 | 0.00 |
March | 0.365541E+11 | 0.00 | 0.902552E+10 | 0.124222E+11 | 0.00 | 0.00 |
April | 0.276208E+11 | 0.00 | 0.954250E+10 | 0.113489E+11 | 0.00 | 0.00 |
May | 0.663296E+10 | 0.00 | 0.410394E+11 | 0.118225E+11 | 0.00 | 0.00 |
June | 0.315838E+09 | 0.00 | 0.137473E+12 | 0.179170E+11 | 0.00 | 0.00 |
July | 0.208012E+09 | 0.00 | 0.136129E+12 | 0.166494E+11 | 0.00 | 0.00 |
August | 0.492201E+09 | 0.00 | 0.132010E+12 | 0.178440E+11 | 0.00 | 0.00 |
September | 0.358107E+10 | 0.00 | 0.867169E+11 | 0.136967E+11 | 0.00 | 0.00 |
October | 0.307448E+11 | 0.00 | 0.157543E+11 | 0.115447E+11 | 0.00 | 0.00 |
November | 0.399062E+11 | 0.00 | 0.503686E+10 | 0.110705E+11 | 0.00 | 0.00 |
December | 0.727066E+11 | 0.00 | 0.317106E+10 | 0.123241E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.319763E+12 | 0.00 | 0.579748E+12 | 0.159880E+12 | 0.00 | 0.00 |
Minimum of Months | 0.208012E+09 | 0.00 | 0.105001E+10 | 0.110705E+11 | 0.00 | 0.00 |
Maximum of Months | 0.727066E+11 | 0.00 | 0.137473E+12 | 0.179170E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.894344E+10 | 0.684209E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.417485E+10 | 0.531979E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.944969E+10 | 0.812767E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.114192E+11 | 0.810479E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.274727E+11 | 0.807930E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.621576E+11 | 0.786243E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.656468E+11 | 0.815453E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.688282E+11 | 0.108900E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.521530E+11 | 0.106763E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.189234E+11 | 0.105902E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.104830E+11 | 0.103686E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.761540E+10 | 0.814885E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.347267E+12 | 0.103165E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.417485E+10 | 0.531979E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.688282E+11 | 0.108900E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 4944593.79 | 0.169945E+12 | 0.00 | 51.28 |
February | 0.00 | 0.00 | 0.157880E+12 | 0.191351E+12 | 0.00 | 51.57 |
March | 0.00 | 0.00 | 0.207748E+12 | 0.292984E+12 | 0.00 | 81.74 |
April | 0.00 | 0.00 | 0.192450E+12 | 0.320659E+12 | 0.00 | 80.83 |
May | 0.00 | 0.00 | 0.192044E+11 | 0.160162E+12 | 0.00 | 47.62 |
June | 0.00 | 0.00 | 0.329468E+12 | 0.907078E+11 | 0.00 | 17.17 |
July | 0.00 | 0.00 | 0.458445E+12 | 0.135672E+12 | 0.00 | 22.49 |
August | 0.00 | 0.00 | 0.554557E+12 | 0.163446E+12 | 0.00 | 22.34 |
September | 0.00 | 0.00 | 0.646257E+11 | 0.152701E+12 | 0.00 | 45.24 |
October | 0.00 | 0.00 | 0.200059E+12 | 0.211198E+12 | 0.00 | 56.53 |
November | 0.00 | 0.00 | 0.202550E+12 | 0.261663E+12 | 0.00 | 70.78 |
December | 0.00 | 0.00 | 0.217590E+12 | 0.374383E+12 | 0.00 | 99.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.260458E+13 | 0.252487E+13 | 0.00 | 647.08 |
Minimum of Months | 0.00 | 0.00 | 4944593.79 | 0.907078E+11 | 0.00 | 17.17 |
Maximum of Months | 0.00 | 0.00 | 0.554557E+12 | 0.374383E+12 | 0.00 | 99.49 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.615323E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.667846E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.870271E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.955179E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.658256E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.801254E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.945928E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.107041E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.656090E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.765330E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.845231E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.966729E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.981784E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.615323E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.107041E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.538956E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.590388E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.768627E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.834592E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.601306E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.726076E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.846510E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.945462E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.597420E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.683270E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.742574E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.833668E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.870885E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.538956E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.945462E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.497633E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.576259E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.792824E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.874079E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.608946E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.779316E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.920457E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.102895E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.614033E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.682647E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.751797E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.858305E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.898524E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.497633E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.102895E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.115270E+11 | 0.400442E+10 | 0.844894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105834E+11 | 0.130829E+10 | 0.885308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141421E+11 | 0.110260E+11 | 0.487583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132067E+11 | 0.118068E+11 | 0.247662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147050E+11 | 0.410908E+11 | 0.246778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.208434E+11 | 0.126629E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.213796E+11 | 0.136349E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.246326E+11 | 0.138471E+12 | 472922.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.177585E+11 | 0.888651E+11 | 0.182366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139796E+11 | 0.186088E+11 | 0.414536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132417E+11 | 0.746031E+10 | 0.493466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121010E+11 | 0.449252E+10 | 0.134410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188101E+12 | 0.590112E+12 | 0.476051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.105834E+11 | 0.130829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.246326E+11 | 0.138471E+12 | 0.134410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.107419E+12 | 0.454386E+11 | 0.211112E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103389E+12 | 0.308652E+11 | 0.217797E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125252E+12 | 0.105745E+12 | 0.148321E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105558E+12 | 0.984448E+11 | 0.941131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132186E+12 | 0.377351E+12 | 0.160575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.186289E+12 | 0.114350E+13 | 0.171745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176295E+12 | 0.115971E+13 | 44500152.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.188928E+12 | 0.112500E+13 | 0.472000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152797E+12 | 0.793099E+12 | 0.920442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119451E+12 | 0.183162E+12 | 0.118521E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105754E+12 | 0.783584E+11 | 0.155462E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109725E+12 | 0.436046E+11 | 0.341054E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161304E+13 | 0.518428E+13 | 0.131233E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103389E+12 | 0.308652E+11 | 44500152.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.188928E+12 | 0.115971E+13 | 0.341054E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.121420E+11 | 0.279982E+10 | 0.505987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110976E+11 | 0.105001E+10 | 0.504015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124222E+11 | 0.902552E+10 | 0.365541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113489E+11 | 0.954250E+10 | 0.276208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.118225E+11 | 0.410394E+11 | 0.663296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.179170E+11 | 0.137473E+12 | 0.315838E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166494E+11 | 0.136129E+12 | 0.208012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178440E+11 | 0.132010E+12 | 0.492201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136967E+11 | 0.867169E+11 | 0.358107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115447E+11 | 0.157543E+11 | 0.307448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110705E+11 | 0.503686E+10 | 0.399062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123241E+11 | 0.317106E+10 | 0.727066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159880E+12 | 0.579748E+12 | 0.319763E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110705E+11 | 0.105001E+10 | 0.208012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.179170E+11 | 0.137473E+12 | 0.727066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.684209E+10 | 0.894344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.531979E+10 | 0.417485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.812767E+10 | 0.944969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.810479E+10 | 0.114192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.807930E+10 | 0.274727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.786243E+10 | 0.621576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.815453E+10 | 0.656468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108900E+11 | 0.688282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106763E+11 | 0.521530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105902E+11 | 0.189234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103686E+11 | 0.104830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.814885E+10 | 0.761540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103165E+12 | 0.347267E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.531979E+10 | 0.417485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108900E+11 | 0.688282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.321046E+11 | 4944593.79 | 0.00 | 0.00 | 0.00 | 0.137223E+12 | 0.00 | 0.00 |
February | 0.527126E+11 | 0.157880E+12 | 0.00 | 0.00 | 0.00 | 0.138017E+12 | 0.00 | 0.00 |
March | 0.732526E+11 | 0.207748E+12 | 0.00 | 0.00 | 0.00 | 0.218746E+12 | 0.00 | 0.00 |
April | 0.103378E+12 | 0.192450E+12 | 0.00 | 0.00 | 0.00 | 0.216307E+12 | 0.00 | 0.00 |
May | 0.321403E+11 | 0.192044E+11 | 0.00 | 0.00 | 0.00 | 0.127448E+12 | 0.00 | 0.00 |
June | 0.445576E+11 | 0.329468E+12 | 0.00 | 0.00 | 0.00 | 0.459433E+11 | 0.00 | 0.00 |
July | 0.752095E+11 | 0.458445E+12 | 0.00 | 0.00 | 0.00 | 0.601919E+11 | 0.00 | 0.00 |
August | 0.103402E+12 | 0.554557E+12 | 0.00 | 0.00 | 0.00 | 0.597747E+11 | 0.00 | 0.00 |
September | 0.310899E+11 | 0.646257E+11 | 0.00 | 0.00 | 0.00 | 0.121066E+12 | 0.00 | 0.00 |
October | 0.592387E+11 | 0.200059E+12 | 0.00 | 0.00 | 0.00 | 0.151278E+12 | 0.00 | 0.00 |
November | 0.713833E+11 | 0.202550E+12 | 0.00 | 0.00 | 0.00 | 0.189427E+12 | 0.00 | 0.00 |
December | 0.106928E+12 | 0.217590E+12 | 0.00 | 0.00 | 0.00 | 0.266256E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.785397E+12 | 0.260458E+13 | 0.00 | 0.00 | 0.00 | 0.173168E+13 | 0.00 | 0.00 |
Minimum of Months | 0.310899E+11 | 4944593.79 | 0.00 | 0.00 | 0.00 | 0.459433E+11 | 0.00 | 0.00 |
Maximum of Months | 0.106928E+12 | 0.554557E+12 | 0.00 | 0.00 | 0.00 | 0.266256E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.411898E+10 | 0.663993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.372037E+10 | 0.103151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.411898E+10 | 0.171763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.398611E+10 | 0.217623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.411898E+10 | 0.810801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.398611E+10 | 0.134828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.411898E+10 | 0.190368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.411898E+10 | 0.241491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.398611E+10 | 0.831523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.411898E+10 | 0.124425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.398611E+10 | 0.167252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.411898E+10 | 0.217296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.484977E+11 | 0.179883E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.372037E+10 | 0.663993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.411898E+10 | 0.241491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.410074E+11 | 0.483177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.370390E+11 | 0.882491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.410074E+11 | 0.154914E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.396846E+11 | 0.198628E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.410074E+11 | 0.729529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.396846E+11 | 0.128339E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.410074E+11 | 0.181010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.410074E+11 | 0.229343E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.396846E+11 | 0.749991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.410074E+11 | 0.111047E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.396846E+11 | 0.148726E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.410074E+11 | 0.191104E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.482830E+12 | 0.162763E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.370390E+11 | 0.483177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.410074E+11 | 0.229343E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.410035E+10 | 0.278290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.370354E+10 | 0.691079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.410035E+10 | 0.138487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.396808E+10 | 0.181824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.410035E+10 | 0.643086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.396808E+10 | 0.126637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.410035E+10 | 0.179686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.410035E+10 | 0.227396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.396808E+10 | 0.687683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.410035E+10 | 0.928102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.396808E+10 | 0.126826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.410035E+10 | 0.168117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.482783E+11 | 0.147180E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.370354E+10 | 0.278290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.410035E+10 | 0.227396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.115270E+11 | 0.844894E+10 | 0.400442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105834E+11 | 0.885308E+10 | 0.130829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141421E+11 | 0.487583E+10 | 0.110260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132067E+11 | 0.247662E+10 | 0.118068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147050E+11 | 0.246778E+09 | 0.410908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.208434E+11 | 0.00 | 0.126629E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.213796E+11 | 0.00 | 0.136349E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.246326E+11 | 472922.26 | 0.138471E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.177585E+11 | 0.182366E+09 | 0.888651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139796E+11 | 0.414536E+10 | 0.186088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132417E+11 | 0.493466E+10 | 0.746031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121010E+11 | 0.134410E+11 | 0.449252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188101E+12 | 0.476051E+11 | 0.590112E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.105834E+11 | 0.00 | 0.130829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.246326E+11 | 0.134410E+11 | 0.138471E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.107419E+12 | 0.211112E+12 | 0.454386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103389E+12 | 0.217797E+12 | 0.308652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125252E+12 | 0.148321E+12 | 0.105745E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105558E+12 | 0.941131E+11 | 0.984448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132186E+12 | 0.160575E+11 | 0.377351E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.186289E+12 | 0.171745E+09 | 0.114350E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176295E+12 | 44500152.13 | 0.115971E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.188928E+12 | 0.472000E+09 | 0.112500E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152797E+12 | 0.920442E+10 | 0.793099E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119451E+12 | 0.118521E+12 | 0.183162E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105754E+12 | 0.155462E+12 | 0.783584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109725E+12 | 0.341054E+12 | 0.436046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161304E+13 | 0.131233E+13 | 0.518428E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103389E+12 | 44500152.13 | 0.308652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.188928E+12 | 0.341054E+12 | 0.115971E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.121420E+11 | 0.505987E+11 | 0.279982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110976E+11 | 0.504015E+11 | 0.105001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124222E+11 | 0.365541E+11 | 0.902552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113489E+11 | 0.276208E+11 | 0.954250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.118225E+11 | 0.663296E+10 | 0.410394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.179170E+11 | 0.315838E+09 | 0.137473E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166494E+11 | 0.208012E+09 | 0.136129E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178440E+11 | 0.492201E+09 | 0.132010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136967E+11 | 0.358107E+10 | 0.867169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115447E+11 | 0.307448E+11 | 0.157543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110705E+11 | 0.399062E+11 | 0.503686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123241E+11 | 0.727066E+11 | 0.317106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159880E+12 | 0.319763E+12 | 0.579748E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110705E+11 | 0.208012E+09 | 0.105001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.179170E+11 | 0.727066E+11 | 0.137473E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.684209E+10 | 0.00 | 0.894344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.531979E+10 | 0.00 | 0.417485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.812767E+10 | 0.00 | 0.944969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.810479E+10 | 0.00 | 0.114192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.807930E+10 | 0.00 | 0.274727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.786243E+10 | 0.00 | 0.621576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.815453E+10 | 0.00 | 0.656468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108900E+11 | 0.00 | 0.688282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106763E+11 | 0.00 | 0.521530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105902E+11 | 0.00 | 0.189234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103686E+11 | 0.00 | 0.104830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.814885E+10 | 0.00 | 0.761540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103165E+12 | 0.00 | 0.347267E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.531979E+10 | 0.00 | 0.417485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108900E+11 | 0.00 | 0.688282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.321046E+11 | 0.00 | 4944593.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137840E+12 | 0.00 | 0.00 | 0.00 |
February | 0.527126E+11 | 0.00 | 0.157880E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138638E+12 | 0.00 | 0.00 | 0.00 |
March | 0.732526E+11 | 0.00 | 0.207748E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219731E+12 | 0.00 | 0.00 | 0.00 |
April | 0.103378E+12 | 0.00 | 0.192450E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217281E+12 | 0.00 | 0.00 | 0.00 |
May | 0.321403E+11 | 0.00 | 0.192044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128022E+12 | 0.00 | 0.00 | 0.00 |
June | 0.445576E+11 | 0.00 | 0.329468E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461502E+11 | 0.00 | 0.00 | 0.00 |
July | 0.752095E+11 | 0.00 | 0.458445E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604629E+11 | 0.00 | 0.00 | 0.00 |
August | 0.103402E+12 | 0.00 | 0.554557E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600438E+11 | 0.00 | 0.00 | 0.00 |
September | 0.310899E+11 | 0.00 | 0.646257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121611E+12 | 0.00 | 0.00 | 0.00 |
October | 0.592387E+11 | 0.00 | 0.200059E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151959E+12 | 0.00 | 0.00 | 0.00 |
November | 0.713833E+11 | 0.00 | 0.202550E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190280E+12 | 0.00 | 0.00 | 0.00 |
December | 0.106928E+12 | 0.00 | 0.217590E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267455E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.785397E+12 | 0.00 | 0.260458E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173947E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.310899E+11 | 0.00 | 4944593.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461502E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.106928E+12 | 0.00 | 0.554557E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267455E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.411898E+10 | 0.00 | 0.00 | 0.00 | 0.203425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.372037E+10 | 0.00 | 0.00 | 0.00 | 0.295809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.411898E+10 | 0.00 | 0.00 | 0.00 | 0.458373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.398611E+10 | 0.00 | 0.00 | 0.00 | 0.556568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.411898E+10 | 0.00 | 0.00 | 0.00 | 0.246358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.398611E+10 | 0.00 | 0.00 | 0.00 | 0.402643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.411898E+10 | 0.00 | 0.00 | 0.00 | 0.534030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.411898E+10 | 0.00 | 0.00 | 0.00 | 0.658510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.398611E+10 | 0.00 | 0.00 | 0.00 | 0.257479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.411898E+10 | 0.00 | 0.00 | 0.00 | 0.353432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.398611E+10 | 0.00 | 0.00 | 0.00 | 0.446620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.411898E+10 | 0.00 | 0.00 | 0.00 | 0.554831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.484977E+11 | 0.00 | 0.00 | 0.00 | 0.496808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.372037E+10 | 0.00 | 0.00 | 0.00 | 0.203425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.411898E+10 | 0.00 | 0.00 | 0.00 | 0.658510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.410074E+11 | 0.00 | 0.00 | 0.00 | 0.128881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.370390E+11 | 0.00 | 0.00 | 0.00 | 0.219998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.410074E+11 | 0.00 | 0.00 | 0.00 | 0.358553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.396846E+11 | 0.00 | 0.00 | 0.00 | 0.437746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.410074E+11 | 0.00 | 0.00 | 0.00 | 0.191232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.396846E+11 | 0.00 | 0.00 | 0.00 | 0.329230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.410074E+11 | 0.00 | 0.00 | 0.00 | 0.436435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.410074E+11 | 0.00 | 0.00 | 0.00 | 0.535388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.396846E+11 | 0.00 | 0.00 | 0.00 | 0.200574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.410074E+11 | 0.00 | 0.00 | 0.00 | 0.273195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.396846E+11 | 0.00 | 0.00 | 0.00 | 0.345728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.410074E+11 | 0.00 | 0.00 | 0.00 | 0.423593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.482830E+12 | 0.00 | 0.00 | 0.00 | 0.388055E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.370390E+11 | 0.00 | 0.00 | 0.00 | 0.128881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.410074E+11 | 0.00 | 0.00 | 0.00 | 0.535388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.410035E+10 | 0.00 | 0.00 | 0.00 | 0.875975E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.370354E+10 | 0.00 | 0.00 | 0.00 | 0.205905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.410035E+10 | 0.00 | 0.00 | 0.00 | 0.382789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.396808E+10 | 0.00 | 0.00 | 0.00 | 0.477271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.410035E+10 | 0.00 | 0.00 | 0.00 | 0.198911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.396808E+10 | 0.00 | 0.00 | 0.00 | 0.382508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.410035E+10 | 0.00 | 0.00 | 0.00 | 0.510422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.410035E+10 | 0.00 | 0.00 | 0.00 | 0.618911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.396808E+10 | 0.00 | 0.00 | 0.00 | 0.217225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.410035E+10 | 0.00 | 0.00 | 0.00 | 0.272612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.396808E+10 | 0.00 | 0.00 | 0.00 | 0.354989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.410035E+10 | 0.00 | 0.00 | 0.00 | 0.448271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.482783E+11 | 0.00 | 0.00 | 0.00 | 0.415741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.370354E+10 | 0.00 | 0.00 | 0.00 | 0.875975E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.410035E+10 | 0.00 | 0.00 | 0.00 | 0.618911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106836E+11 | 0.00 | 0.00 | 94855025.52 | 0.00 | 0.00 | 0.445566E+11 | 0.00 | 0.57 |
February | 0.219252E+11 | 0.00 | 0.00 | 0.218534E+09 | 0.00 | 0.00 | 0.258764E+11 | 0.00 | 0.48 |
March | 0.166347E+11 | 0.00 | 0.00 | 0.318165E+09 | 0.00 | 0.00 | 0.391484E+11 | 0.00 | 0.73 |
April | 0.757479E+10 | 0.00 | 0.00 | 0.163843E+09 | 0.00 | 0.00 | 0.442925E+11 | 0.00 | 0.76 |
May | 0.344786E+10 | 12162893.76 | 0.00 | 0.118100E+09 | 479825.03 | 0.00 | 0.371702E+11 | 0.00 | 0.86 |
June | 0.335402E+09 | 0.194197E+10 | 0.00 | 0.219369E+09 | 25448103.43 | 0.00 | 0.130921E+11 | 0.00 | 0.73 |
July | 63745962.53 | 0.303460E+10 | 0.00 | 0.171080E+09 | 79993206.80 | 0.00 | 0.107851E+11 | 0.00 | 0.70 |
August | 0.257516E+09 | 0.186393E+10 | 0.00 | 0.149232E+09 | 25612306.67 | 0.00 | 0.209735E+11 | 0.00 | 0.91 |
September | 0.124256E+10 | 0.299131E+09 | 0.00 | 0.152905E+09 | 22529204.64 | 0.00 | 0.297123E+11 | 0.00 | 1.00 |
October | 0.113469E+11 | 0.00 | 0.00 | 0.485150E+09 | 0.00 | 0.00 | 0.491418E+11 | 0.00 | 0.89 |
November | 0.141217E+11 | 0.00 | 0.00 | 0.433061E+09 | 0.00 | 0.00 | 0.518317E+11 | 0.00 | 0.80 |
December | 0.186816E+11 | 0.00 | 0.00 | 0.188937E+09 | 0.00 | 0.00 | 0.451099E+11 | 0.00 | 0.62 |
Annual Sum or Average | 0.106316E+12 | 0.715179E+10 | 0.00 | 0.271323E+10 | 0.154063E+09 | 0.00 | 0.411690E+12 | 0.00 | 0.75 |
Minimum of Months | 63745962.53 | 0.00 | 0.00 | 94855025.52 | 0.00 | 0.00 | 0.107851E+11 | 0.00 | 0.48 |
Maximum of Months | 0.219252E+11 | 0.303460E+10 | 0.00 | 0.485150E+09 | 79993206.80 | 0.00 | 0.518317E+11 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.934169E+10 | 0.00 | 0.00 | 0.145253E+09 | 0.00 | 0.00 | 0.415991E+11 | 0.00 | 0.54 |
February | 0.165400E+11 | 0.00 | 0.00 | 0.384998E+09 | 0.00 | 0.00 | 0.293222E+11 | 0.00 | 0.49 |
March | 0.137037E+11 | 0.00 | 0.00 | 0.540259E+09 | 0.00 | 0.00 | 0.439210E+11 | 0.00 | 0.79 |
April | 0.661303E+10 | 0.00 | 0.00 | 0.254267E+09 | 0.00 | 0.00 | 0.470577E+11 | 0.00 | 0.84 |
May | 0.338862E+10 | 4944742.83 | 0.00 | 0.167944E+09 | 1822350.66 | 0.00 | 0.430542E+11 | 0.00 | 1.00 |
June | 0.244741E+10 | 0.671013E+09 | 0.00 | 0.224595E+09 | 59784355.47 | 0.00 | 0.154744E+11 | 0.00 | 0.75 |
July | 0.243897E+10 | 0.725463E+09 | 0.00 | 0.180142E+09 | 0.163334E+09 | 0.00 | 0.131287E+11 | 0.00 | 0.74 |
August | 0.394609E+10 | 0.654009E+09 | 0.00 | 0.162613E+09 | 0.218458E+09 | 0.00 | 0.227810E+11 | 0.00 | 0.94 |
September | 0.199511E+10 | 0.123531E+09 | 0.00 | 0.140787E+09 | 29067760.42 | 0.00 | 0.269138E+11 | 0.00 | 0.90 |
October | 0.107035E+11 | 0.00 | 0.00 | 0.565753E+09 | 0.00 | 0.00 | 0.432604E+11 | 0.00 | 0.81 |
November | 0.105802E+11 | 0.00 | 0.00 | 0.583852E+09 | 0.00 | 0.00 | 0.459536E+11 | 0.00 | 0.69 |
December | 0.124162E+11 | 0.00 | 0.00 | 0.253978E+09 | 0.00 | 0.00 | 0.427123E+11 | 0.00 | 0.55 |
Annual Sum or Average | 0.941145E+11 | 0.217896E+10 | 0.00 | 0.360444E+10 | 0.472466E+09 | 0.00 | 0.415178E+12 | 0.00 | 0.76 |
Minimum of Months | 0.199511E+10 | 0.00 | 0.00 | 0.140787E+09 | 0.00 | 0.00 | 0.131287E+11 | 0.00 | 0.49 |
Maximum of Months | 0.165400E+11 | 0.725463E+09 | 0.00 | 0.583852E+09 | 0.218458E+09 | 0.00 | 0.470577E+11 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.218523E+12 | 0.00 | 0.00 | 0.669910E+09 | 0.00 | 0.154917E+10 | 0.182897E+12 | 0.00 | 0.43 |
February | 0.245006E+12 | 0.00 | 0.00 | 0.170192E+10 | 0.00 | 0.225494E+10 | 0.125819E+12 | 0.00 | 0.40 |
March | 0.220229E+12 | 0.00 | 0.00 | 0.273408E+10 | 0.00 | 0.723920E+09 | 0.219128E+12 | 0.00 | 0.61 |
April | 0.167826E+12 | 0.00 | 0.00 | 0.111573E+10 | 0.00 | 16819785.05 | 0.214857E+12 | 0.00 | 0.62 |
May | 0.655346E+11 | 1985995.22 | 0.00 | 0.122348E+10 | 0.139514E+09 | 0.00 | 0.316290E+12 | 0.00 | 0.86 |
June | 0.318939E+11 | 0.723978E+10 | 0.00 | 0.150179E+10 | 0.794819E+09 | 0.00 | 0.112219E+12 | 0.00 | 0.64 |
July | 0.207867E+11 | 0.738954E+10 | 0.00 | 0.120445E+10 | 0.153159E+10 | 0.00 | 0.901675E+11 | 0.00 | 0.58 |
August | 0.206704E+11 | 0.681482E+10 | 0.00 | 0.111394E+10 | 0.400818E+09 | 0.00 | 0.158036E+12 | 0.00 | 0.68 |
September | 0.413085E+11 | 0.136803E+10 | 0.00 | 0.919404E+09 | 0.270082E+09 | 0.00 | 0.180061E+12 | 0.00 | 0.73 |
October | 0.184809E+12 | 0.00 | 0.00 | 0.310609E+10 | 0.00 | 34718202.05 | 0.225279E+12 | 0.00 | 0.64 |
November | 0.212883E+12 | 0.00 | 0.00 | 0.234545E+10 | 0.00 | 0.00 | 0.178695E+12 | 0.00 | 0.49 |
December | 0.286456E+12 | 0.00 | 0.00 | 0.749778E+09 | 0.00 | 0.135567E+10 | 0.127429E+12 | 0.00 | 0.41 |
Annual Sum or Average | 0.171593E+13 | 0.228142E+11 | 0.00 | 0.183860E+11 | 0.313682E+10 | 0.593524E+10 | 0.213088E+13 | 0.00 | 0.59 |
Minimum of Months | 0.206704E+11 | 0.00 | 0.00 | 0.669910E+09 | 0.00 | 0.00 | 0.901675E+11 | 0.00 | 0.40 |
Maximum of Months | 0.286456E+12 | 0.738954E+10 | 0.00 | 0.310609E+10 | 0.153159E+10 | 0.225494E+10 | 0.316290E+12 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.266880E+11 | 0.00 | 0.00 | 8267318.92 | 0.00 | 0.267310E+10 | 0.278427E+10 | 0.00 | 0.38 |
February | 0.251444E+11 | 0.00 | 0.00 | 23010447.78 | 0.00 | 0.299487E+10 | 0.207338E+10 | 0.00 | 0.35 |
March | 0.270564E+11 | 0.00 | 0.00 | 89194755.80 | 0.00 | 0.157656E+10 | 0.928052E+10 | 0.00 | 0.57 |
April | 0.215382E+11 | 0.00 | 0.00 | 45963406.00 | 0.00 | 0.997806E+09 | 0.132068E+11 | 0.00 | 0.60 |
May | 0.137435E+11 | 0.00 | 0.00 | 73372828.25 | 7818482.25 | 0.159699E+09 | 0.216261E+11 | 0.00 | 0.81 |
June | 0.529128E+10 | 0.368881E+09 | 0.00 | 0.113641E+09 | 63432798.43 | 0.00 | 0.859815E+10 | 0.00 | 0.64 |
July | 0.358818E+10 | 0.350523E+09 | 0.00 | 95398990.86 | 61430548.45 | 0.00 | 0.658910E+10 | 0.00 | 0.56 |
August | 0.492912E+10 | 0.409195E+09 | 0.00 | 92455409.82 | 29379777.47 | 0.00 | 0.112796E+11 | 0.00 | 0.65 |
September | 0.801325E+10 | 49130692.18 | 0.00 | 60389728.70 | 46635736.85 | 9761429.01 | 0.112546E+11 | 0.00 | 0.70 |
October | 0.249492E+11 | 0.00 | 0.00 | 89050709.07 | 0.00 | 0.126862E+10 | 0.761720E+10 | 0.00 | 0.58 |
November | 0.266784E+11 | 0.00 | 0.00 | 34780352.27 | 0.00 | 0.176100E+10 | 0.342986E+10 | 0.00 | 0.44 |
December | 0.261295E+11 | 0.00 | 0.00 | 6074341.74 | 0.00 | 0.483830E+10 | 0.116930E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.213749E+12 | 0.117773E+10 | 0.00 | 0.731599E+09 | 0.208697E+09 | 0.162797E+11 | 0.989088E+11 | 0.00 | 0.55 |
Minimum of Months | 0.358818E+10 | 0.00 | 0.00 | 6074341.74 | 0.00 | 0.00 | 0.116930E+10 | 0.00 | 0.35 |
Maximum of Months | 0.270564E+11 | 0.409195E+09 | 0.00 | 0.113641E+09 | 63432798.43 | 0.483830E+10 | 0.216261E+11 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.546568E+10 | 0.00 | 0.00 | 214345.80 | 0.00 | 0.131838E+10 | 0.183170E+09 | 0.00 | 0.56 |
February | 0.492605E+10 | 0.00 | 0.00 | 291433.68 | 0.00 | 0.145537E+10 | 31985092.38 | 0.00 | 0.53 |
March | 0.582746E+10 | 0.00 | 0.00 | 11341054.42 | 0.00 | 0.625012E+09 | 0.109672E+10 | 0.00 | 0.81 |
April | 0.454450E+10 | 0.00 | 0.00 | 9375601.37 | 0.00 | 0.200958E+09 | 0.230864E+10 | 0.00 | 0.89 |
May | 0.275774E+10 | 1053823.27 | 0.00 | 14778501.91 | 320451.11 | 0.00 | 0.381037E+10 | 0.00 | 1.19 |
June | 0.991172E+09 | 0.159194E+09 | 0.00 | 24699952.23 | 10839103.16 | 0.00 | 0.179657E+10 | 0.00 | 1.01 |
July | 0.856272E+09 | 0.174396E+09 | 0.00 | 19487553.13 | 28721472.03 | 0.00 | 0.148340E+10 | 0.00 | 0.98 |
August | 0.148957E+10 | 0.143015E+09 | 0.00 | 17799508.39 | 38414653.91 | 0.00 | 0.226762E+10 | 0.00 | 1.13 |
September | 0.188196E+10 | 29532403.16 | 0.00 | 11364587.69 | 5111418.03 | 2249573.35 | 0.202153E+10 | 0.00 | 1.01 |
October | 0.537171E+10 | 0.00 | 0.00 | 13582124.70 | 0.00 | 0.412675E+09 | 0.111099E+10 | 0.00 | 0.82 |
November | 0.598091E+10 | 0.00 | 0.00 | 4656380.70 | 0.00 | 0.585559E+09 | 0.467262E+09 | 0.00 | 0.67 |
December | 0.514913E+10 | 0.00 | 0.00 | 613786.27 | 0.00 | 0.191491E+10 | 0.140750E+09 | 0.00 | 0.55 |
Annual Sum or Average | 0.452421E+11 | 0.507192E+09 | 0.00 | 0.128205E+09 | 83407098.24 | 0.651511E+10 | 0.167190E+11 | 0.00 | 0.85 |
Minimum of Months | 0.856272E+09 | 0.00 | 0.00 | 214345.80 | 0.00 | 0.00 | 31985092.38 | 0.00 | 0.53 |
Maximum of Months | 0.598091E+10 | 0.174396E+09 | 0.00 | 24699952.23 | 38414653.91 | 0.191491E+10 | 0.381037E+10 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.633748E+10 | 0.00 | 0.00 | 3288185.65 | 0.00 | 0.151641E+10 | 0.102053E+10 | 0.00 | 1.12 |
February | 0.546654E+10 | 0.00 | 0.00 | 16651676.42 | 0.00 | 0.164546E+10 | 0.131529E+10 | 0.00 | 1.09 |
March | 0.643869E+10 | 0.00 | 0.00 | 35571929.52 | 0.00 | 0.857242E+09 | 0.307945E+10 | 0.00 | 1.68 |
April | 0.523733E+10 | 0.00 | 0.00 | 17678969.24 | 0.00 | 0.361457E+09 | 0.380335E+10 | 0.00 | 1.74 |
May | 0.358429E+10 | 1093158.80 | 0.00 | 16373921.71 | 402876.09 | 1654422.22 | 0.459869E+10 | 0.00 | 2.20 |
June | 0.134700E+10 | 0.116970E+09 | 0.00 | 34529672.80 | 16436127.21 | 0.00 | 0.257600E+10 | 0.00 | 1.99 |
July | 0.140461E+10 | 0.131357E+09 | 0.00 | 18337467.95 | 36969101.12 | 0.00 | 0.146625E+10 | 0.00 | 1.69 |
August | 0.206959E+10 | 0.106897E+09 | 0.00 | 20670970.01 | 52943006.87 | 0.00 | 0.318112E+10 | 0.00 | 2.26 |
September | 0.247717E+10 | 22020778.29 | 0.00 | 14704123.00 | 12349533.94 | 15617907.12 | 0.282341E+10 | 0.00 | 2.05 |
October | 0.635264E+10 | 0.00 | 0.00 | 25801068.80 | 0.00 | 0.626984E+09 | 0.222914E+10 | 0.00 | 1.68 |
November | 0.694683E+10 | 0.00 | 0.00 | 11833392.03 | 0.00 | 0.952050E+09 | 0.111036E+10 | 0.00 | 1.31 |
December | 0.595485E+10 | 0.00 | 0.00 | 2795313.76 | 0.00 | 0.258671E+10 | 0.533523E+09 | 0.00 | 1.08 |
Annual Sum or Average | 0.536170E+11 | 0.378337E+09 | 0.00 | 0.218237E+09 | 0.119101E+09 | 0.856359E+10 | 0.277371E+11 | 0.00 | 1.66 |
Minimum of Months | 0.134700E+10 | 0.00 | 0.00 | 2795313.76 | 0.00 | 0.00 | 0.533523E+09 | 0.00 | 1.08 |
Maximum of Months | 0.694683E+10 | 0.131357E+09 | 0.00 | 35571929.52 | 52943006.87 | 0.258671E+10 | 0.459869E+10 | 0.00 | 2.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.406318E+10 | 0.00 | 0.00 | 46188643.61 | 0.00 | 0.140774E+10 | 0.103168E+11 | 0.00 | 1.46 |
February | 0.366793E+10 | 0.00 | 0.00 | 0.131516E+09 | 0.00 | 0.163491E+10 | 0.961832E+10 | 0.00 | 1.37 |
March | 0.556714E+10 | 0.00 | 0.00 | 0.103912E+09 | 0.00 | 0.130052E+10 | 0.831081E+10 | 0.00 | 1.81 |
April | 0.547488E+10 | 0.00 | 0.00 | 26620269.21 | 0.00 | 0.686747E+09 | 0.562284E+10 | 0.00 | 1.55 |
May | 0.466795E+10 | 1493214.91 | 0.00 | 17320313.43 | 459374.12 | 73217433.35 | 0.443998E+10 | 0.00 | 1.65 |
June | 0.217845E+10 | 0.173696E+09 | 0.00 | 17305588.35 | 16164777.57 | 0.00 | 0.134938E+10 | 0.00 | 1.22 |
July | 0.182826E+10 | 0.208835E+09 | 0.00 | 16201029.09 | 41036260.24 | 0.00 | 0.113843E+10 | 0.00 | 1.19 |
August | 0.257426E+10 | 0.208516E+09 | 0.00 | 23275610.79 | 55068299.96 | 0.00 | 0.266702E+10 | 0.00 | 1.59 |
September | 0.261410E+10 | 56941266.41 | 0.00 | 23221009.78 | 7327336.65 | 45193621.87 | 0.374268E+10 | 0.00 | 1.78 |
October | 0.504232E+10 | 0.00 | 0.00 | 0.127184E+09 | 0.00 | 0.933475E+09 | 0.896749E+10 | 0.00 | 2.04 |
November | 0.461854E+10 | 0.00 | 0.00 | 0.142991E+09 | 0.00 | 0.105898E+10 | 0.105526E+11 | 0.00 | 1.74 |
December | 0.430593E+10 | 0.00 | 0.00 | 60202635.75 | 0.00 | 0.222622E+10 | 0.859553E+10 | 0.00 | 1.37 |
Annual Sum or Average | 0.466030E+11 | 0.649482E+09 | 0.00 | 0.735938E+09 | 0.120056E+09 | 0.936700E+10 | 0.753218E+11 | 0.00 | 1.56 |
Minimum of Months | 0.182826E+10 | 0.00 | 0.00 | 16201029.09 | 0.00 | 0.00 | 0.113843E+10 | 0.00 | 1.19 |
Maximum of Months | 0.556714E+10 | 0.208835E+09 | 0.00 | 0.142991E+09 | 55068299.96 | 0.222622E+10 | 0.105526E+11 | 0.00 | 2.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.862830E+10 | 0.00 | 0.00 | 6903220.24 | 0.00 | 0.802436E+09 | 0.204651E+10 | 0.00 | 1.47 |
February | 0.810023E+10 | 0.00 | 0.00 | 24850625.13 | 0.00 | 0.859361E+09 | 0.193863E+10 | 0.00 | 1.43 |
March | 0.970194E+10 | 0.00 | 0.00 | 39591051.43 | 0.00 | 57775873.87 | 0.331438E+10 | 0.00 | 2.24 |
April | 0.691371E+10 | 0.00 | 0.00 | 21419050.49 | 0.00 | 29922649.78 | 0.487925E+10 | 0.00 | 2.31 |
May | 0.549821E+10 | 1679677.49 | 0.00 | 13190245.14 | 514502.93 | 0.00 | 0.421291E+10 | 0.00 | 2.65 |
June | 0.236570E+10 | 0.219654E+09 | 0.00 | 15868306.61 | 11587495.94 | 0.00 | 0.134023E+10 | 0.00 | 1.97 |
July | 0.177351E+10 | 0.234496E+09 | 0.00 | 16984628.64 | 28909914.55 | 0.00 | 0.143176E+10 | 0.00 | 1.95 |
August | 0.215990E+10 | 0.222972E+09 | 0.00 | 24505967.12 | 53923154.43 | 0.00 | 0.309620E+10 | 0.00 | 2.44 |
September | 0.337582E+10 | 40904715.17 | 0.00 | 11906152.23 | 7166609.57 | 586750.70 | 0.247090E+10 | 0.00 | 2.29 |
October | 0.886285E+10 | 0.00 | 0.00 | 34056989.51 | 0.00 | 0.255252E+09 | 0.261878E+10 | 0.00 | 2.22 |
November | 0.920086E+10 | 0.00 | 0.00 | 28640824.01 | 0.00 | 0.201635E+09 | 0.242118E+10 | 0.00 | 1.77 |
December | 0.902712E+10 | 0.00 | 0.00 | 9553619.87 | 0.00 | 0.110342E+10 | 0.174407E+10 | 0.00 | 1.45 |
Annual Sum or Average | 0.756081E+11 | 0.719707E+09 | 0.00 | 0.247471E+09 | 0.102102E+09 | 0.331039E+10 | 0.315148E+11 | 0.00 | 2.02 |
Minimum of Months | 0.177351E+10 | 0.00 | 0.00 | 6903220.24 | 0.00 | 0.00 | 0.134023E+10 | 0.00 | 1.43 |
Maximum of Months | 0.970194E+10 | 0.234496E+09 | 0.00 | 39591051.43 | 53923154.43 | 0.110342E+10 | 0.487925E+10 | 0.00 | 2.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.462494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438837E+11 | 0.00 | 0.00 | 0.74 |
February | 0.420007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424753E+11 | 0.00 | 0.00 | 0.70 |
March | 0.611529E+11 | 0.00 | 0.00 | 9521069.58 | 0.00 | 0.285376E+11 | 0.197437E+10 | 0.00 | 0.96 |
April | 0.529118E+11 | 0.00 | 0.00 | 13825512.21 | 0.00 | 0.181565E+11 | 0.635407E+10 | 0.00 | 0.95 |
May | 0.487931E+11 | 13294587.58 | 0.00 | 63266554.04 | 20766613.21 | 0.154709E+10 | 0.189557E+11 | 0.00 | 1.25 |
June | 0.177350E+11 | 0.188672E+10 | 0.00 | 0.128770E+09 | 0.196729E+09 | 0.00 | 0.103361E+11 | 0.00 | 1.03 |
July | 0.140120E+11 | 0.201490E+10 | 0.00 | 0.107038E+09 | 0.314778E+09 | 0.00 | 0.791156E+10 | 0.00 | 0.93 |
August | 0.209365E+11 | 0.158949E+10 | 0.00 | 0.106663E+09 | 0.138167E+09 | 0.00 | 0.118016E+11 | 0.00 | 1.02 |
September | 0.314034E+11 | 0.273292E+09 | 0.00 | 60565827.75 | 0.126785E+09 | 0.106306E+10 | 0.908607E+10 | 0.00 | 1.08 |
October | 0.605060E+11 | 0.00 | 0.00 | 3002213.85 | 0.00 | 0.221626E+11 | 0.490769E+09 | 0.00 | 0.99 |
November | 0.522429E+11 | 0.00 | 0.00 | 170693.22 | 0.00 | 0.324545E+11 | 0.206000E+09 | 0.00 | 0.80 |
December | 0.358964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600143E+11 | 0.00 | 0.00 | 0.73 |
Annual Sum or Average | 0.483840E+12 | 0.577769E+10 | 0.00 | 0.492822E+09 | 0.797225E+09 | 0.250295E+12 | 0.671162E+11 | 0.00 | 0.93 |
Minimum of Months | 0.140120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 |
Maximum of Months | 0.611529E+11 | 0.201490E+10 | 0.00 | 0.128770E+09 | 0.314778E+09 | 0.600143E+11 | 0.189557E+11 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.412317E+11 | 0.00 | 0.00 | 16077919.65 | 0.00 | 0.311026E+11 | 0.442706E+10 | 0.00 | 0.95 |
February | 0.372675E+11 | 0.00 | 0.00 | 0.102663E+09 | 0.00 | 0.299119E+11 | 0.718567E+10 | 0.00 | 0.96 |
March | 0.446309E+11 | 0.00 | 0.00 | 0.294196E+09 | 0.00 | 0.210291E+11 | 0.234242E+11 | 0.00 | 1.50 |
April | 0.359298E+11 | 0.00 | 0.00 | 0.141271E+09 | 0.00 | 0.135313E+11 | 0.285140E+11 | 0.00 | 1.54 |
May | 0.348656E+11 | 17098578.24 | 0.00 | 0.145268E+09 | 16328561.52 | 0.101604E+10 | 0.370703E+11 | 0.00 | 2.05 |
June | 0.137922E+11 | 0.147535E+10 | 0.00 | 0.313025E+09 | 0.235453E+09 | 0.00 | 0.222977E+11 | 0.00 | 1.96 |
July | 0.125412E+11 | 0.168439E+10 | 0.00 | 0.158336E+09 | 0.343480E+09 | 0.00 | 0.121795E+11 | 0.00 | 1.59 |
August | 0.155755E+11 | 0.138268E+10 | 0.00 | 0.191031E+09 | 0.207285E+09 | 7060212.24 | 0.280308E+11 | 0.00 | 2.01 |
September | 0.242314E+11 | 0.285342E+09 | 0.00 | 0.125013E+09 | 0.127150E+09 | 0.905127E+09 | 0.219696E+11 | 0.00 | 1.93 |
October | 0.427864E+11 | 0.00 | 0.00 | 0.210207E+09 | 0.00 | 0.189562E+11 | 0.163125E+11 | 0.00 | 1.47 |
November | 0.433355E+11 | 0.00 | 0.00 | 72513183.37 | 0.00 | 0.245506E+11 | 0.594962E+10 | 0.00 | 1.08 |
December | 0.340336E+11 | 0.00 | 0.00 | 4633704.48 | 0.00 | 0.459663E+11 | 0.569038E+09 | 0.00 | 0.93 |
Annual Sum or Average | 0.380221E+12 | 0.484486E+10 | 0.00 | 0.177423E+10 | 0.929696E+09 | 0.186976E+12 | 0.207930E+12 | 0.00 | 1.50 |
Minimum of Months | 0.125412E+11 | 0.00 | 0.00 | 4633704.48 | 0.00 | 0.00 | 0.569038E+09 | 0.00 | 0.93 |
Maximum of Months | 0.446309E+11 | 0.168439E+10 | 0.00 | 0.313025E+09 | 0.343480E+09 | 0.459663E+11 | 0.370703E+11 | 0.00 | 2.05 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.336973E+11 | 0.00 | 0.00 | 0.508892E+09 | 0.00 | 0.228486E+11 | 0.975639E+11 | 0.00 | 1.45 |
February | 0.307185E+11 | 0.00 | 0.00 | 0.145584E+10 | 0.00 | 0.247385E+11 | 0.911996E+11 | 0.00 | 1.35 |
March | 0.437338E+11 | 0.00 | 0.00 | 0.105507E+10 | 0.00 | 0.224271E+11 | 0.770907E+11 | 0.00 | 1.77 |
April | 0.434764E+11 | 0.00 | 0.00 | 0.226870E+09 | 0.00 | 0.149762E+11 | 0.450951E+11 | 0.00 | 1.42 |
May | 0.435014E+11 | 24608500.18 | 0.00 | 0.151983E+09 | 17273325.50 | 0.199956E+10 | 0.374605E+11 | 0.00 | 1.55 |
June | 0.206813E+11 | 0.207923E+10 | 0.00 | 0.142161E+09 | 0.225591E+09 | 0.00 | 0.105864E+11 | 0.00 | 1.17 |
July | 0.158518E+11 | 0.254170E+10 | 0.00 | 0.127608E+09 | 0.319758E+09 | 0.00 | 0.868346E+10 | 0.00 | 1.07 |
August | 0.208615E+11 | 0.263158E+10 | 0.00 | 0.198156E+09 | 0.107150E+09 | 0.00 | 0.203802E+11 | 0.00 | 1.36 |
September | 0.253082E+11 | 0.737452E+09 | 0.00 | 0.225396E+09 | 59907252.67 | 0.726257E+09 | 0.314964E+11 | 0.00 | 1.72 |
October | 0.374119E+11 | 0.00 | 0.00 | 0.137414E+10 | 0.00 | 0.184448E+11 | 0.845060E+11 | 0.00 | 2.00 |
November | 0.343222E+11 | 0.00 | 0.00 | 0.156245E+10 | 0.00 | 0.188517E+11 | 0.958403E+11 | 0.00 | 1.64 |
December | 0.351489E+11 | 0.00 | 0.00 | 0.598231E+09 | 0.00 | 0.360176E+11 | 0.731965E+11 | 0.00 | 1.32 |
Annual Sum or Average | 0.384713E+12 | 0.801457E+10 | 0.00 | 0.762680E+10 | 0.729679E+09 | 0.161030E+12 | 0.673099E+12 | 0.00 | 1.49 |
Minimum of Months | 0.158518E+11 | 0.00 | 0.00 | 0.127608E+09 | 0.00 | 0.00 | 0.868346E+10 | 0.00 | 1.07 |
Maximum of Months | 0.437338E+11 | 0.263158E+10 | 0.00 | 0.156245E+10 | 0.319758E+09 | 0.360176E+11 | 0.975639E+11 | 0.00 | 2.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.605055E+11 | 0.00 | 0.00 | 29920545.38 | 0.00 | 0.345647E+11 | 0.904606E+10 | 0.00 | 1.33 |
February | 0.551953E+11 | 0.00 | 0.00 | 0.146853E+09 | 0.00 | 0.336600E+11 | 0.107294E+11 | 0.00 | 1.29 |
March | 0.686086E+11 | 0.00 | 0.00 | 0.244776E+09 | 0.00 | 0.246877E+11 | 0.192480E+11 | 0.00 | 1.94 |
April | 0.594676E+11 | 0.00 | 0.00 | 0.101715E+09 | 0.00 | 0.145358E+11 | 0.211320E+11 | 0.00 | 1.87 |
May | 0.547720E+11 | 29568195.03 | 0.00 | 87577367.97 | 12222681.50 | 0.201912E+10 | 0.258123E+11 | 0.00 | 2.33 |
June | 0.240407E+11 | 0.249716E+10 | 0.00 | 92441018.09 | 0.166317E+09 | 0.00 | 0.723757E+10 | 0.00 | 1.79 |
July | 0.182769E+11 | 0.224963E+10 | 0.00 | 78923443.89 | 0.392524E+09 | 0.00 | 0.649344E+10 | 0.00 | 1.61 |
August | 0.262388E+11 | 0.212859E+10 | 0.00 | 0.113658E+09 | 0.270066E+09 | 7961210.66 | 0.108875E+11 | 0.00 | 1.83 |
September | 0.366062E+11 | 0.326969E+09 | 0.00 | 73514931.72 | 0.165911E+09 | 0.749524E+09 | 0.119445E+11 | 0.00 | 2.03 |
October | 0.636919E+11 | 0.00 | 0.00 | 0.219401E+09 | 0.00 | 0.216299E+11 | 0.156312E+11 | 0.00 | 1.93 |
November | 0.636641E+11 | 0.00 | 0.00 | 0.112319E+09 | 0.00 | 0.267463E+11 | 0.861804E+10 | 0.00 | 1.47 |
December | 0.534490E+11 | 0.00 | 0.00 | 19731340.20 | 0.00 | 0.521995E+11 | 0.397714E+10 | 0.00 | 1.31 |
Annual Sum or Average | 0.584517E+12 | 0.723192E+10 | 0.00 | 0.132083E+10 | 0.100704E+10 | 0.210800E+12 | 0.150757E+12 | 0.00 | 1.73 |
Minimum of Months | 0.182769E+11 | 0.00 | 0.00 | 19731340.20 | 0.00 | 0.00 | 0.397714E+10 | 0.00 | 1.29 |
Maximum of Months | 0.686086E+11 | 0.249716E+10 | 0.00 | 0.244776E+09 | 0.392524E+09 | 0.521995E+11 | 0.258123E+11 | 0.00 | 2.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.380831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537374E+10 | 0.00 | 0.00 | 0.85 |
February | 0.394287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468860E+10 | 0.00 | 0.00 | 0.79 |
March | 0.645961E+10 | 0.00 | 0.00 | 189825.70 | 0.00 | 0.361072E+10 | 0.189512E+09 | 0.00 | 1.17 |
April | 0.606727E+10 | 0.00 | 0.00 | 717364.56 | 0.00 | 0.257459E+10 | 0.662767E+09 | 0.00 | 1.19 |
May | 0.636353E+10 | 0.00 | 0.00 | 3961637.51 | 2243550.73 | 0.674356E+09 | 0.157841E+10 | 0.00 | 1.55 |
June | 0.220312E+10 | 85521637.51 | 0.00 | 12253243.14 | 24114350.16 | 0.00 | 0.101722E+10 | 0.00 | 1.18 |
July | 0.159243E+10 | 86668094.35 | 0.00 | 11986530.46 | 21167565.03 | 0.00 | 0.832593E+09 | 0.00 | 1.07 |
August | 0.260708E+10 | 81529237.44 | 0.00 | 10596584.80 | 26569496.09 | 22184041.75 | 0.112324E+10 | 0.00 | 1.21 |
September | 0.338233E+10 | 12538622.59 | 0.00 | 5551292.99 | 14726147.46 | 0.450596E+09 | 0.876025E+09 | 0.00 | 1.35 |
October | 0.623568E+10 | 0.00 | 0.00 | 176871.58 | 0.00 | 0.298781E+10 | 33540486.56 | 0.00 | 1.22 |
November | 0.450944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449633E+10 | 0.00 | 0.00 | 0.96 |
December | 0.286786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637790E+10 | 0.00 | 0.00 | 0.82 |
Annual Sum or Average | 0.500396E+11 | 0.266258E+09 | 0.00 | 45433350.74 | 88821109.47 | 0.312568E+11 | 0.631331E+10 | 0.00 | 1.12 |
Minimum of Months | 0.159243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 |
Maximum of Months | 0.645961E+10 | 86668094.35 | 0.00 | 12253243.14 | 26569496.09 | 0.637790E+10 | 0.157841E+10 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.402323E+10 | 0.00 | 0.00 | 173095.44 | 0.00 | 0.287008E+10 | 70194139.55 | 0.00 | 1.01 |
February | 0.391260E+10 | 0.00 | 0.00 | 1747935.23 | 0.00 | 0.246460E+10 | 0.167165E+09 | 0.00 | 0.94 |
March | 0.446778E+10 | 0.00 | 0.00 | 19130828.04 | 0.00 | 0.197086E+10 | 0.176653E+10 | 0.00 | 1.49 |
April | 0.367015E+10 | 0.00 | 0.00 | 10823951.68 | 0.00 | 0.146543E+10 | 0.264971E+10 | 0.00 | 1.59 |
May | 0.336275E+10 | 0.00 | 0.00 | 11952127.79 | 1702253.14 | 0.278770E+09 | 0.357504E+10 | 0.00 | 2.06 |
June | 0.103230E+10 | 68369165.10 | 0.00 | 31496729.51 | 16347209.34 | 0.00 | 0.231653E+10 | 0.00 | 1.89 |
July | 0.941025E+09 | 77777104.05 | 0.00 | 17601024.31 | 13984446.40 | 0.00 | 0.123782E+10 | 0.00 | 1.53 |
August | 0.117184E+10 | 76122792.88 | 0.00 | 20326214.21 | 15071651.35 | 9534821.84 | 0.282348E+10 | 0.00 | 1.93 |
September | 0.190514E+10 | 15130739.77 | 0.00 | 11896491.13 | 9144291.29 | 0.209546E+09 | 0.204105E+10 | 0.00 | 1.89 |
October | 0.435367E+10 | 0.00 | 0.00 | 9261196.67 | 0.00 | 0.190448E+10 | 0.881683E+09 | 0.00 | 1.49 |
November | 0.419478E+10 | 0.00 | 0.00 | 860095.86 | 0.00 | 0.244427E+10 | 0.194716E+09 | 0.00 | 1.13 |
December | 0.314528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385010E+10 | 0.00 | 0.00 | 0.96 |
Annual Sum or Average | 0.361806E+11 | 0.237400E+09 | 0.00 | 0.135270E+09 | 56249851.53 | 0.174677E+11 | 0.177239E+11 | 0.00 | 1.50 |
Minimum of Months | 0.941025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 |
Maximum of Months | 0.446778E+10 | 77777104.05 | 0.00 | 31496729.51 | 16347209.34 | 0.385010E+10 | 0.357504E+10 | 0.00 | 2.06 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.297453E+10 | 0.00 | 0.00 | 37356474.62 | 0.00 | 0.248044E+10 | 0.809496E+10 | 0.00 | 1.42 |
February | 0.272518E+10 | 0.00 | 0.00 | 0.118150E+09 | 0.00 | 0.237457E+10 | 0.840324E+10 | 0.00 | 1.34 |
March | 0.415282E+10 | 0.00 | 0.00 | 88078868.62 | 0.00 | 0.250419E+10 | 0.785410E+10 | 0.00 | 1.84 |
April | 0.405162E+10 | 0.00 | 0.00 | 19236019.25 | 0.00 | 0.224415E+10 | 0.494773E+10 | 0.00 | 1.53 |
May | 0.481289E+10 | 0.00 | 0.00 | 12091023.03 | 2276304.01 | 0.720951E+09 | 0.383756E+10 | 0.00 | 1.72 |
June | 0.217044E+10 | 87756791.06 | 0.00 | 16338677.01 | 25920108.44 | 1731867.29 | 0.128985E+10 | 0.00 | 1.27 |
July | 0.157559E+10 | 99823588.27 | 0.00 | 15932049.19 | 21035053.82 | 350286.00 | 0.104018E+10 | 0.00 | 1.16 |
August | 0.227506E+10 | 0.134699E+09 | 0.00 | 21743382.61 | 12394769.65 | 22092126.72 | 0.218200E+10 | 0.00 | 1.45 |
September | 0.239764E+10 | 36826540.37 | 0.00 | 21674641.46 | 3952615.67 | 0.318811E+09 | 0.338282E+10 | 0.00 | 1.82 |
October | 0.324875E+10 | 0.00 | 0.00 | 0.112627E+09 | 0.00 | 0.235679E+10 | 0.845920E+10 | 0.00 | 2.08 |
November | 0.308572E+10 | 0.00 | 0.00 | 0.112946E+09 | 0.00 | 0.235178E+10 | 0.825689E+10 | 0.00 | 1.65 |
December | 0.318502E+10 | 0.00 | 0.00 | 42525122.36 | 0.00 | 0.344086E+10 | 0.562018E+10 | 0.00 | 1.25 |
Annual Sum or Average | 0.366553E+11 | 0.359106E+09 | 0.00 | 0.618699E+09 | 65578851.59 | 0.188167E+11 | 0.633687E+11 | 0.00 | 1.55 |
Minimum of Months | 0.157559E+10 | 0.00 | 0.00 | 12091023.03 | 0.00 | 350286.00 | 0.104018E+10 | 0.00 | 1.16 |
Maximum of Months | 0.481289E+10 | 0.134699E+09 | 0.00 | 0.118150E+09 | 25920108.44 | 0.344086E+10 | 0.845920E+10 | 0.00 | 2.08 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.440746E+10 | 0.00 | 0.00 | 2411508.20 | 0.00 | 0.333209E+10 | 0.849420E+09 | 0.00 | 1.26 |
February | 0.416893E+10 | 0.00 | 0.00 | 14467320.63 | 0.00 | 0.295125E+10 | 0.113886E+10 | 0.00 | 1.19 |
March | 0.573511E+10 | 0.00 | 0.00 | 24588398.40 | 0.00 | 0.234009E+10 | 0.227741E+10 | 0.00 | 1.92 |
April | 0.497412E+10 | 0.00 | 0.00 | 10160833.26 | 0.00 | 0.182914E+10 | 0.256154E+10 | 0.00 | 1.92 |
May | 0.505650E+10 | 0.00 | 0.00 | 8684904.17 | 2081600.68 | 0.481176E+09 | 0.294157E+10 | 0.00 | 2.41 |
June | 0.207795E+10 | 0.108862E+09 | 0.00 | 12487714.98 | 17370354.34 | 775252.63 | 0.965107E+09 | 0.00 | 1.78 |
July | 0.149809E+10 | 93992507.17 | 0.00 | 10914240.60 | 18579933.83 | 421152.86 | 0.819726E+09 | 0.00 | 1.60 |
August | 0.230757E+10 | 0.109872E+09 | 0.00 | 13823191.31 | 19033629.74 | 19423486.14 | 0.124722E+10 | 0.00 | 1.83 |
September | 0.294734E+10 | 13978366.96 | 0.00 | 7999272.55 | 13952130.74 | 0.308630E+09 | 0.139593E+10 | 0.00 | 2.09 |
October | 0.518086E+10 | 0.00 | 0.00 | 21459598.29 | 0.00 | 0.222526E+10 | 0.177659E+10 | 0.00 | 1.94 |
November | 0.477502E+10 | 0.00 | 0.00 | 9565490.67 | 0.00 | 0.285227E+10 | 0.893004E+09 | 0.00 | 1.44 |
December | 0.374577E+10 | 0.00 | 0.00 | 1818530.60 | 0.00 | 0.446567E+10 | 0.357223E+09 | 0.00 | 1.19 |
Annual Sum or Average | 0.468747E+11 | 0.326705E+09 | 0.00 | 0.138381E+09 | 71017649.34 | 0.208062E+11 | 0.172236E+11 | 0.00 | 1.72 |
Minimum of Months | 0.149809E+10 | 0.00 | 0.00 | 1818530.60 | 0.00 | 421152.86 | 0.357223E+09 | 0.00 | 1.19 |
Maximum of Months | 0.573511E+10 | 0.109872E+09 | 0.00 | 24588398.40 | 19033629.74 | 0.446567E+10 | 0.294157E+10 | 0.00 | 2.41 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 7490875.49 | 0.00 | 0.00 | 0.577891E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 62267447.64 | 0.00 | 0.00 | 0.481480E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.108800E+09 | 0.00 | 0.00 | 0.423306E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 60573551.27 | 0.00 | 0.00 | 0.374488E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 7734107.03 | 0.00 | 0.00 | 0.303226E+09 | 0.00 | 0.29 |
June | 0.00 | 6996404.80 | 0.00 | 16470928.82 | 0.00 | 0.00 | 75054304.98 | 0.00 | 0.30 |
July | 0.00 | 18050714.18 | 0.00 | 12876652.56 | 0.00 | 0.00 | 45510417.28 | 0.00 | 0.28 |
August | 0.00 | 10164928.27 | 0.00 | 21833727.25 | 0.00 | 0.00 | 88117952.25 | 0.00 | 0.30 |
September | 0.00 | 362840.95 | 0.00 | 5866253.39 | 0.00 | 0.00 | 0.198585E+09 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.00 | 63882351.37 | 0.00 | 0.00 | 0.388300E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.100825E+09 | 0.00 | 0.00 | 0.421817E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 67218478.38 | 0.00 | 0.00 | 0.548583E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 35574888.20 | 0.00 | 0.535839E+09 | 0.00 | 0.00 | 0.392636E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 5866253.39 | 0.00 | 0.00 | 45510417.28 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 18050714.18 | 0.00 | 0.108800E+09 | 0.00 | 0.00 | 0.577891E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.301983E+09 | 0.00 | 0.00 | 53124048.71 | 0.00 | 0.00 | 0.549705E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 0.541704E+09 | 0.00 | 0.00 | 0.489569E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.991912E+09 | 0.00 | 0.00 | 0.432937E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.560400E+09 | 0.00 | 0.00 | 0.379189E+10 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 65811562.48 | 0.00 | 0.00 | 0.304382E+10 | 0.00 | 0.29 |
June | 0.00 | 69377801.07 | 0.00 | 0.155320E+09 | 0.00 | 0.00 | 0.759439E+09 | 0.00 | 0.30 |
July | 0.00 | 0.178581E+09 | 0.00 | 0.122861E+09 | 0.00 | 0.00 | 0.461149E+09 | 0.00 | 0.28 |
August | 0.00 | 0.100132E+09 | 0.00 | 0.206352E+09 | 0.00 | 0.00 | 0.897889E+09 | 0.00 | 0.30 |
September | 0.00 | 3756401.97 | 0.00 | 49283709.54 | 0.00 | 0.00 | 0.199462E+10 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.00 | 0.568854E+09 | 0.00 | 0.00 | 0.395269E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.905914E+09 | 0.00 | 0.00 | 0.432067E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.606307E+09 | 0.00 | 0.00 | 0.555216E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.301983E+09 | 0.351847E+09 | 0.00 | 0.482784E+10 | 0.00 | 0.00 | 0.394964E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 49283709.54 | 0.00 | 0.00 | 0.461149E+09 | 0.00 | 0.28 |
Maximum of Months | 0.301983E+09 | 0.178581E+09 | 0.00 | 0.991912E+09 | 0.00 | 0.00 | 0.555216E+10 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.190365E+09 | 0.00 | 0.00 | 3495756.00 | 0.00 | 0.00 | 0.391373E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 46136375.94 | 0.00 | 0.00 | 0.497610E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 91991705.83 | 0.00 | 0.00 | 0.440118E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 53338258.57 | 0.00 | 0.00 | 0.381944E+09 | 0.00 | 0.29 |
May | 13664047.46 | 0.00 | 0.00 | 5668131.12 | 0.00 | 0.00 | 0.291813E+09 | 0.00 | 0.29 |
June | 0.00 | 6919202.12 | 0.00 | 15116176.12 | 0.00 | 0.00 | 76627035.79 | 0.00 | 0.30 |
July | 0.00 | 17834406.52 | 0.00 | 12250496.88 | 0.00 | 0.00 | 46231223.08 | 0.00 | 0.28 |
August | 0.00 | 9774801.64 | 0.00 | 20590660.16 | 0.00 | 0.00 | 91537884.71 | 0.00 | 0.30 |
September | 7593819.33 | 364178.11 | 0.00 | 4293531.60 | 0.00 | 0.00 | 0.192702E+09 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.00 | 48782427.41 | 0.00 | 0.00 | 0.403404E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 81192645.25 | 0.00 | 0.00 | 0.441451E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 55769281.56 | 0.00 | 0.00 | 0.560038E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.211622E+09 | 34892588.39 | 0.00 | 0.438625E+09 | 0.00 | 0.00 | 0.381485E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3495756.00 | 0.00 | 0.00 | 46231223.08 | 0.00 | 0.28 |
Maximum of Months | 0.190365E+09 | 17834406.52 | 0.00 | 91991705.83 | 0.00 | 0.00 | 0.560038E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.956297E+09 | 0.00 | 0.00 | 0.403951E+12 | 0.00 | 8.47 |
February | 0.420940E+10 | 0.00 | 0.00 | 0.351265E+10 | 0.00 | 0.00 | 0.511769E+12 | 0.00 | 12.90 |
March | 0.170915E+09 | 0.00 | 0.00 | 0.794324E+10 | 0.00 | 0.00 | 0.854492E+12 | 0.00 | 25.75 |
April | 0.00 | 0.00 | 0.00 | 0.527869E+10 | 0.00 | 0.00 | 0.106354E+13 | 0.00 | 39.62 |
May | 0.00 | 0.00 | 0.00 | 0.807283E+09 | 0.00 | 0.00 | 0.377302E+12 | 0.00 | 15.54 |
June | 0.420738E+09 | 7099683.21 | 0.00 | 0.208167E+10 | 0.00 | 0.00 | 0.252346E+12 | 0.00 | 22.44 |
July | 0.00 | 0.290694E+09 | 0.00 | 0.343833E+10 | 0.00 | 0.00 | 0.414599E+12 | 0.00 | 36.81 |
August | 0.00 | 0.173278E+09 | 0.00 | 0.360936E+10 | 0.00 | 0.00 | 0.584339E+12 | 0.00 | 47.50 |
September | 0.00 | 0.00 | 0.00 | 0.681099E+09 | 0.00 | 0.00 | 0.324950E+12 | 0.00 | 16.93 |
October | 0.323284E+10 | 0.00 | 0.00 | 0.364300E+10 | 0.00 | 0.00 | 0.550260E+12 | 0.00 | 18.83 |
November | 0.00 | 0.00 | 0.00 | 0.784723E+10 | 0.00 | 0.00 | 0.806145E+12 | 0.00 | 23.26 |
December | 0.00 | 0.00 | 0.00 | 0.658215E+10 | 0.00 | 0.00 | 0.112841E+13 | 0.00 | 29.30 |
Annual Sum or Average | 0.803390E+10 | 0.471071E+09 | 0.00 | 0.463810E+11 | 0.00 | 0.00 | 0.727211E+13 | 0.00 | 24.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.681099E+09 | 0.00 | 0.00 | 0.252346E+12 | 0.00 | 8.47 |
Maximum of Months | 0.420940E+10 | 0.290694E+09 | 0.00 | 0.794324E+10 | 0.00 | 0.00 | 0.112841E+13 | 0.00 | 47.50 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:25:32
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.440816E+12 | 0.142568E+11 | 0.00 | 0.258616E+13 | 0.302617E+12 |
February | 0.558531E+12 | 0.223750E+11 | 0.00 | 0.244568E+13 | 0.532728E+12 |
March | 0.692681E+12 | 0.240275E+11 | 0.00 | 0.308046E+13 | 0.840546E+12 |
April | 0.730468E+12 | 0.253152E+11 | 0.00 | 0.336776E+13 | 0.838281E+12 |
May | 0.853259E+12 | 0.125694E+11 | 0.00 | 0.271017E+13 | 0.776860E+12 |
June | 0.893530E+12 | 0.537420E+10 | 0.00 | 0.168896E+13 | 0.269217E+13 |
July | 0.829794E+12 | 0.406743E+10 | 0.00 | 0.159725E+13 | 0.291873E+13 |
August | 0.822207E+12 | 0.431531E+10 | 0.00 | 0.184014E+13 | 0.305314E+13 |
September | 0.612746E+12 | 0.785116E+10 | 0.00 | 0.205979E+13 | 0.160532E+13 |
October | 0.534908E+12 | 0.175929E+11 | 0.00 | 0.297265E+13 | 0.820607E+12 |
November | 0.468629E+12 | 0.161322E+11 | 0.00 | 0.312910E+13 | 0.785075E+12 |
December | 0.369594E+12 | 0.303881E+11 | 0.00 | 0.318338E+13 | 0.882907E+12 |
Annual Sum or Average | 0.780716E+13 | 0.184265E+12 | 0.00 | 0.306615E+14 | 0.160490E+14 |
Minimum of Months | 0.369594E+12 | 0.406743E+10 | 0.00 | 0.159725E+13 | 0.302617E+12 |
Maximum of Months | 0.893530E+12 | 0.303881E+11 | 0.00 | 0.336776E+13 | 0.305314E+13 |