Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:22
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2024-07-03 12:22:25
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 35417.04 | 764.61 | 764.61 |
Net Site Energy | 35417.04 | 764.61 | 764.61 |
Total Source Energy | 103160.84 | 2227.12 | 2227.12 |
Net Source Energy | 103160.84 | 2227.12 | 2227.12 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 4323.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1904.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1006.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2690.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 955.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 158.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6044.65 |
Humidification | 1007.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.70 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 459.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 31093.99 | 4323.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8699.52 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 4323.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1904.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 1006.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 56.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2690.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 955.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 158.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6044.65 |
Humidification | General | 1007.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.70 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 459.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 4323.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1904.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 1006.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2690.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 955.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 158.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6044.65 |
Humidification | Unassigned | 1007.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.70 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 459.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 154.95 | 93.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 671.28 | 93.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 154.95 | 93.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 671.28 | 93.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 31093.986 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 31093.986 | 100.00 |
Total On-Site and Utility Electric Sources | 31093.986 | 100.00 |
Total Electricity End Uses | 31093.986 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 8699.52 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 8699.52 | 100.00 |
Total Water End Uses | 8699.52 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 68.50 |
Time Setpoint Not Met During Occupied Cooling | 67.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5140.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS SZVAV FAN | AIRLOOP DATACENTER BASEMENT SYS11 FAN | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:22 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 11.6510 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 11.6510 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 11.6510 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.6510 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 11.6510 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.6510 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 11.6510 | 18.58 | 484.4232 | |
Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.6100 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 18-AUG-15:09 | 02-JAN-05:10 | - | - | - | - | - | - | - | - | - | - | 17-AUG-12:00 |
Heating | 0.00 | 2269990.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 396345.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235096.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 275713.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 93099.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 54364.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 33735.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2356626.12 | 2269990.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2269990.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 396345.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 275713.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 93099.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 54364.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 33735.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 4686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6032.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17769.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3187.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8307.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8521.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3027.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 501.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 3190.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1456.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 98474.65 | 4686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 101.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 130.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 183.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 65.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 10.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 68.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2125.95 | 101.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 101.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 130.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 183.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 65.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 10.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 68.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2125.95 | 101.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 7.09 | 0.298666 | 0.300000 | 2.13 |
DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | 32.15 | 0.018577 | 0.500000 | 16.07 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 7.54 | 0.252363 | 0.300000 | 2.26 | 0.672967 | 0.500000 | 0.001510 | 0.000251 | 2.26 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 71.56 | 0.265799 | 0.300000 | 21.47 | 0.708798 | 0.500000 | 0.001433 | 0.005444 | 26.65 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 7.90 | 0.240808 | 0.300000 | 2.37 | 0.642154 | 0.500000 | 0.001582 | 0.001599 | 7.89 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.38 | 0.173046 | 0.300000 | 0.414030 | 0.461455 | 0.500000 | 0.002202 | 0.000279 | 1.38 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.65 | 0.093489 | 0.300000 | 0.493872 | 0.300000 | 0.500000 | 0.004075 | 0.000186 | 0.919074 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.95 | 0.122662 | 0.300000 | 0.584105 | 0.327100 | 0.500000 | 0.003106 | 0.000304 | 1.50 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 2.01 | 0.076583 | 0.300000 | 0.602899 | 0.300000 | 0.500000 | 0.004975 | 0.000158 | 0.779767 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 19.89 | 0.120068 | 0.300000 | 5.97 | 0.320181 | 0.500000 | 0.003173 | 0.004022 | 19.89 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 17.38 | 0.300000 | 0.500000 | 0.004301 | 0.002617 | 12.95 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 19.89 | 0.120070 | 0.300000 | 5.97 | 0.320186 | 0.500000 | 0.003173 | 0.004022 | 19.89 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 18.55 | 0.082977 | 0.300000 | 5.56 | 0.300000 | 0.500000 | 0.004592 | 0.002591 | 12.81 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 2.61 | 0.091487 | 0.300000 | 0.783130 | 0.300000 | 0.500000 | 0.004165 | 0.000528 | 2.61 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.76 | 0.087295 | 0.300000 | 0.528916 | 0.300000 | 0.500000 | 0.004365 | 0.000342 | 1.69 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 2.61 | 0.091488 | 0.300000 | 0.783136 | 0.300000 | 0.500000 | 0.004164 | 0.000528 | 2.61 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 2.02 | 0.076309 | 0.300000 | 0.605059 | 0.300000 | 0.500000 | 0.004993 | 0.000344 | 1.70 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 28747.13 | 0.000251 | 597.97 | |
CORE_MID VAV BOX REHEAT COIL | 622313.75 | 0.005444 | 14575.62 | |
CORE_TOP VAV BOX REHEAT COIL | 182823.37 | 0.001599 | 4272.40 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 31927.33 | 0.000279 | 745.82 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 21259.93 | 0.000186 | 496.62 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 34734.76 | 0.000304 | 811.35 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 18046.31 | 0.000158 | 421.61 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 459714.64 | 0.004022 | 10736.06 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 299185.40 | 0.002617 | 6987.05 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 459716.88 | 0.004022 | 10736.11 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 296140.11 | 0.002591 | 6915.95 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 60308.85 | 0.000528 | 1408.28 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 39148.03 | 0.000342 | 914.15 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 60309.32 | 0.000528 | 1408.29 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 39291.10 | 0.000344 | 917.48 | |
VAV_BOT WITH REHEAT HEATING COIL | 59044.78 | 0.000517 | 987.13 | |
VAV_MID WITH REHEAT HEATING COIL | 607949.48 | 0.005319 | 10083.26 | |
VAV_TOP WITH REHEAT HEATING COIL | 50013.67 | 0.000438 | 863.68 | |
CAV_BAS HEATING COIL | 0.000875 | 2622.48 | 100000.00 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 558433.54 | 0.000875 | 2622.48 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.761187 |
DATACENTER_MID_ZN_6 DIRECT AIR | 7.31 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.753148 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 7.26 | 4.36 | 14.52 | 5.66 | 12.23 | 12.23 | 0.300000 | 0.462685 | 12.23 |
VAV_MID WITH REHEAT | 73.63 | 44.18 | 147.26 | 92.19 | 114.63 | 114.63 | 0.300000 | 0.804219 | 114.63 |
VAV_TOP WITH REHEAT | 8.45 | 5.07 | 16.90 | 16.51 | 14.08 | 16.51 | 0.300000 | 1.00 | 16.51 |
CAV_BAS | 2.13 | 2.13 | 7.09 | 2.13 | 7.09 | 7.09 | 1.00 | 0.300000 | 7.09 |
AIRLOOP DATACENTER BASEMENT | 16.07 | 16.07 | 32.15 | 16.07 | 32.15 | 32.15 | 1.00 | 0.499997 | 32.15 |
AIRLOOP DATACENTER BOT | 0.761187 | 0.761187 | 0.761187 | 0.761187 | 0.761187 | 0.761187 | 1.00 | 1.00 | 0.761187 |
AIRLOOP DATACENTER MID | 7.31 | 7.31 | 7.31 | 7.31 | 7.31 | 7.31 | 1.00 | 1.00 | 7.31 |
AIRLOOP DATACENTER TOP | 0.753148 | 0.753148 | 0.753148 | 0.753148 | 0.753148 | 0.753148 | 1.00 | 1.00 | 0.753148 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 12.23 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 114.63 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 16.51 | |
CAV_BAS_OA_CONTROLLER | 7.09 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 32.15 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.761187 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 7.31 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.753148 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.05 | 6.67 | 11.07 | 0.009599 | 0.008500 | 245023.19 | 0.008752 | 12.23 |
VAV_MID WITH REHEAT COOLING COIL | 25.14 | 6.67 | 11.07 | 0.009740 | 0.008500 | 2357080.43 | 0.084189 | 114.63 |
VAV_TOP WITH REHEAT COOLING COIL | 24.91 | 6.67 | 11.08 | 0.009523 | 0.008500 | 323915.64 | 0.011570 | 16.51 |
CAV_BAS COOLING COIL | 23.95 | 6.67 | 11.06 | 0.009668 | 0.008500 | 130970.70 | 0.004678 | 7.09 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 27.03 | 6.67 | 15.02 | 0.008584 | 0.008500 | 454621.01 | 0.016238 | 32.15 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 12.23 |
VAV_MID WITH REHEAT FAN | 114.63 |
VAV_TOP WITH REHEAT FAN | 16.51 |
CAV_BAS SZVAV FAN | 7.09 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | 32.15 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.008752 | 0.000054 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000517 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.084189 | 0.000006 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.005319 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.011570 | 0.000041 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000438 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | Design Size Minimum Supply Air Temperature [C] | User-Specified Minimum Supply Air Temperature [C] | User-Specified Maximum Supply Air Temperature [C] | User-Specified Nominal Cooling Capacity [W] | Design Size Maximum Supply Air Temperature [C] | |
CAV_BAS_UNITARY_PACKAGE_DX | 7.09 | 7.09 | 7.09 | 2.13 | 130970.70 | 100000.00 | 1.00 | 5.33 | 12.89 | 32.11 | ||
AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | 32.15 | 32.15 | 32.15 | 16.07 | 454621.01 | 100000.00 | 1.00 | 15.89 | 29.11 | |||
AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | 0.761187 | 0.761187 | 0.761187 | 0.761187 | 26438.98 | 1.00 | 12600.35 | 29.11 | ||||
AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | 7.31 | 7.31 | 7.31 | 7.31 | 254135.76 | 1.00 | 121060.40 | 29.11 | ||||
AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | 0.753148 | 0.753148 | 0.753148 | 0.753148 | 26162.92 | 1.00 | 12467.27 | 29.11 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000275 | 0.000037 | 96450.70 | 100000.00 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | 0.761187 | 1308.97 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | 7.31 | 12576.16 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | 0.753148 | 1295.14 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
AIRLOOP DATACENTER BOT COOLING COIL | 0.761190 | 0.380594 | 0.507460 | 12600.35 | 6300.18 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER MID COOLING COIL | 7.31 | 3.66 | 4.88 | 121060.40 | 60530.20 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.753150 | 0.376574 | 0.502100 | 12467.27 | 6233.64 | 0.800660 | 0.800660 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BOT HEATING COIL | 26438.98 |
AIRLOOP DATACENTER MID HEATING COIL | 254135.76 |
AIRLOOP DATACENTER TOP HEATING COIL | 26162.92 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.125427 | 25845.80 | |
HEATSYS1 PUMP | 0.031238 | 9407.46 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.125427 | 15.05 |
HEATSYS1 | 0.031238 | 3.75 |
COOLSYS1_SUPPLY | 0.125427 | 15.05 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.125427 | 0.125427 | 526478.41 | 6.67 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3570674.84 | 3570674.84 | 0.031238 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.062713 | 11929.02 |
COOLSYS1 CHILLER2 PUMP | 0.062713 | 11929.02 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.125427 | 0.063260 | 1771111.54 | 1771080.83 | 0.088760 |
COOLSYS1 CHILLER2 | 0.125427 | 0.063260 | 1771111.54 | 1771080.83 | 0.088760 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.177521 | 21.30 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.177521 | 61901.66 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 73.38 | 2120900.82 | 14.68 | 265112.60 |
TOWERWATERSYS COOLTOWER 2 | 73.38 | 2120900.82 | 14.68 | 265112.60 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 11.651 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 16.493 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 11.651 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 496.074 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 32383.100 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 32383.100 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 9130.649 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 9130.649 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
26 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
27 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
35 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
47 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
48 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
49 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
50 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
51 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
52 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
53 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
54 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
55 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
56 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
57 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
58 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
59 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
60 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
61 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
62 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
63 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
64 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
65 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
66 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
67 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
68 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
69 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
70 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
71 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
72 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
73 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
74 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
75 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
76 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
77 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
78 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
79 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
80 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
81 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
82 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
83 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
84 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
85 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
86 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
87 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
88 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
89 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
90 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
91 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
92 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
93 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
94 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
95 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
96 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
97 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
98 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
99 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
100 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
101 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
102 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
103 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
104 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
105 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
106 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
107 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
108 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
109 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
110 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
111 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
112 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
113 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
114 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
115 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
116 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
117 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
118 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
119 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
120 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
121 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone BASEMENT | 1.2500 |
3 | Zone CORE_BOTTOM | 1.2500 |
4 | Zone CORE_MID | 1.2500 |
5 | Zone CORE_TOP | 1.2500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.2500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.2500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.2500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone BASEMENT | 1.1500 |
3 | Zone CORE_BOTTOM | 1.1500 |
4 | Zone CORE_MID | 1.1500 |
5 | Zone CORE_TOP | 1.1500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.1500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.1500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.1500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 82814.62411 | 95236.81772 | 6.16633 | 7.09128 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 88021.06820 | 101224.22842 | 6.55386 | 7.53694 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 5434.53527 | 6793.16909 | 0.40130 | 1.07782 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 835887.12731 | 961270.19640 | 62.22562 | 71.55946 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 290866.94520 | 363583.68150 | 21.31765 | 26.64706 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 91426.97264 | 105141.01853 | 6.86835 | 7.89860 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 84959.33779 | 106199.17224 | 6.31333 | 7.89166 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 14695.81574 | 16900.18810 | 1.10405 | 1.26966 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30000 | 1.33670E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 14827.26694 | 18534.08368 | 1.10408 | 1.38010 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 19054.83648 | 21913.06195 | 1.43151 | 1.64624 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 25.44850 | 1.33584E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 9872.60290 | 12340.75362 | 0.73526 | 0.91907 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 22536.19375 | 25916.62282 | 1.69306 | 1.94702 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 29.99000 | 1.33664E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 16128.34698 | 20160.43373 | 1.20140 | 1.50175 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 23261.47474 | 26750.69595 | 1.74753 | 2.00966 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 8383.77944 | 10479.72429 | 0.62381 | 0.77977 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 139613.44744 | 160555.46455 | 10.48936 | 12.06276 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.30000 | 1.33670E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 213405.62843 | 266757.03553 | 15.91238 | 19.89048 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 201104.33672 | 231269.98723 | 15.10909 | 17.37545 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.97550 | 1.33593E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 138885.59631 | 173606.99539 | 10.35613 | 12.94516 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 222610.37162 | 256001.92737 | 16.72492 | 19.23366 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 213406.67585 | 266758.34482 | 15.91246 | 19.89058 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 214674.41332 | 246875.57532 | 16.12860 | 18.54789 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 137473.54595 | 171841.93244 | 10.25063 | 12.81328 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 16995.02839 | 19544.28265 | 1.27689 | 1.46842 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 27988.33446 | 34985.41808 | 2.08835 | 2.61043 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 20405.14419 | 23465.91582 | 1.53309 | 1.76305 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.23900 | 1.33598E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 18168.05229 | 22710.06537 | 1.35562 | 1.69453 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 25105.18771 | 28870.96587 | 1.88622 | 2.16915 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 27988.55465 | 34985.69331 | 2.08836 | 2.61045 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 23342.80551 | 26844.22634 | 1.75380 | 2.01686 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 18234.25623 | 22792.82028 | 1.36059 | 1.70074 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8810.85591 | 10132.48430 | 0.66190 | 0.76119 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.50250 | 1.33602E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -16.30000 | 9.24091E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 84651.71517 | 97349.47245 | 6.35936 | 7.31326 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.50250 | 1.33602E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -16.30000 | 9.24091E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8717.79218 | 10025.46101 | 0.65491 | 0.75315 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -16.30000 | 9.24091E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372099.23209 | 427914.11691 | 27.95285 | 32.14578 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 21.83700 | 1.33520E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 01:50:00 | -16.30000 | 9.24091E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 175111.26 | 12.22974 | 12.22974 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 69753.56 | 5.65852 | 5.65852 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1624489.21 | 114.62863 | 114.62863 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 694864.22 | 92.18656 | 92.18656 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 199352.38 | 14.07884 | 14.07884 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 68412.32 | 16.50781 | 16.50781 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 |
7 | CAV_BAS | Cooling | Sensible | 92547.24 | 7.09128 | 7.09128 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 68535.94 | 1.20016 | 1.20016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 422134.25 | 32.14598 | 32.14598 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 18126.67 | 0.33839 | 0.33839 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 9966.65 | 0.76119 | 0.76119 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 837.38 | 1.56323E-002 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 95752.61 | 7.31326 | 7.31326 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8373.77 | 0.15632 | 0.15632 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 9864.43 | 0.75315 | 0.75315 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 837.38 | 1.56323E-002 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 7.09128 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.29867 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 2.12738 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.53694 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25236 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.26108 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67297 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.50973E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.51492E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.26108 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 28747.13261 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.51492E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 597.97226 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 71.55946 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26580 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 21.46784 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70880 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.43341E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.44427E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 26.64706 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 622313.75394 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.44427E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 14575.61969 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.89860 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24081 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.36958 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64215 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.58218E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.59942E-003 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.89166 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 182823.37401 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.59942E-003 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4272.39572 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.38010 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17305 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41403 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46146 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.20173E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.79314E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.38010 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 31927.32768 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.79314E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 745.81707 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.64624 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.34889E-002 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.49387 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.07535E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.85991E-004 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.91907 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21259.93123 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.85991E-004 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 496.61564 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.94702 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12266 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.58411 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32710 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.10609E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.03875E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.50175 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 34734.75685 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.03875E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 811.35389 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.00966 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.65825E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.60290 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.97503E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.57877E-004 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.77977 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18046.31143 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.57877E-004 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 421.60518 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 19.89048 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12007 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.96714 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32018 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.17321E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.02178E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.89048 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 459714.63573 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.02178E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 10736.05597 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 17.37545 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.30138E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.61740E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 12.94516 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 299185.39542 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.61740E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6987.05244 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 19.89058 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12007 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.96717 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32019 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.17315E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.02180E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.89058 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 459716.88307 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.02180E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 10736.10856 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.54789 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.29771E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.56437 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.59163E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.59076E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 12.81328 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 296140.11367 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.59076E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6915.95141 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.61043 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.14870E-002 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78313 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.16453E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.27608E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.61043 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 60308.84551 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.27608E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1408.28022 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.76305 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.72946E-002 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.52892 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.36453E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.42484E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.69453 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 39148.03447 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.42484E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 914.14717 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.61045 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.14883E-002 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78314 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.16447E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.27612E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.61045 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 60309.31943 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.27612E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1408.29129 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.01686 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.63091E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.60506 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.99285E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.43736E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.70074 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 39291.09683 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.43736E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 917.48471 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.76119 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.31326 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.75315 |
215 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 32.14578 |
216 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 1.85767E-002 |
217 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
218 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 16.07289 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.25998 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.35599 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 14.51997 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.65852 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 12.22974 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 12.22974 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.46269 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 73.63193 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 44.17916 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 147.26385 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 92.18656 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 114.62863 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 114.62863 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.80422 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 8.44970 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.06982 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 16.89941 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 16.50781 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 14.07884 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 16.50781 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 1.00000 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.12738 |
244 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.12738 |
245 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.09128 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.12738 |
247 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.09128 |
248 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 7.09128 |
249 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.30000 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 16.07289 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 16.07289 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 32.14578 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 16.07289 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 32.14598 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 32.14598 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.50000 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.76119 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.76119 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.76119 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.76119 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.76119 |
264 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.76119 |
265 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.31326 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.31326 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.31326 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 7.31326 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.31326 |
272 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 7.31326 |
273 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
274 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.75315 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.75315 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.75315 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.75315 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.75315 |
280 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.75315 |
281 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
282 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
283 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 12.22974 |
284 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 114.62863 |
285 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 16.50781 |
286 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 7.09128 |
287 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 32.14598 |
288 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.76119 |
289 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 7.31326 |
290 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.75315 |
291 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 12.22974 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.04648 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.06799 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.59899E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 245023.19407 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.75166E-003 |
299 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 12.22974 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 59044.77924 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.16549E-004 |
302 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 987.12963 |
303 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 12.22974 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.75166E-003 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.44114E-005 |
306 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.16549E-004 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 114.62863 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.13627 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.06845 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.73958E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2357080.43312 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.41895E-002 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 114.62863 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 607949.47845 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.31861E-003 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 10083.26487 |
319 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 114.62863 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.41895E-002 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.65618E-006 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.31861E-003 |
323 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 16.50781 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.90824 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.08499 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.52317E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 323915.63971 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.15695E-002 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 16.50781 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 50013.66919 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.37541E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 863.68085 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 16.50781 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.15695E-002 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.11591E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.37541E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.09128 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.09128 |
342 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.09128 |
343 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.09128 |
344 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.12738 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 23.95242 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.05849 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.66830E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 130970.69749 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.67797E-003 |
352 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.09128 |
353 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 130970.69749 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
355 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
356 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.47617 |
357 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
358 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
359 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Minimum Supply Air Temperature [C] | 5.33118 |
360 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 12.88890 |
361 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 32.11110 |
362 | Fan:VariableVolume | CAV_BAS SZVAV FAN | Design Size Maximum Flow Rate [m3/s] | 7.09128 |
363 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 32.14598 |
364 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
365 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 32.14598 |
366 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 32.14598 |
367 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 32.14598 |
368 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 16.07299 |
369 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.03274 |
370 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
371 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 15.02257 |
372 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58398E-003 |
373 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
374 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Coil Load [W] | 454621.01392 |
375 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.62380E-002 |
376 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 32.14598 |
377 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 454621.01392 |
378 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Capacity [W] | 558433.54024 |
379 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
380 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
381 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.47617 |
382 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
383 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
384 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 15.88890 |
385 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 29.11110 |
386 | Fan:VariableVolume | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Design Size Maximum Flow Rate [m3/s] | 32.14598 |
387 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.75399E-004 |
388 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
389 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
390 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
391 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.76119 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
393 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.76119 |
394 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1308.96714 |
395 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.76119 |
396 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.76119 |
397 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.76119 |
398 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76119 |
399 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.76119 |
400 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.38059 |
401 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.50746 |
402 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 12600.35000 |
403 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6300.17500 |
404 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
405 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
406 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 12600.35000 |
407 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26438.98357 |
408 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
409 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
410 | Coil:Heating:Fuel | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Nominal Capacity [W] | 26438.98357 |
411 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.31326 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
413 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.31326 |
414 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 12576.16444 |
415 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.31326 |
416 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.31326 |
417 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.31326 |
418 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 7.31326 |
419 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.31326 |
420 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.65663 |
421 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.87551 |
422 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 121060.40000 |
423 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 60530.20000 |
424 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
425 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
426 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 121060.40000 |
427 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 254135.75605 |
428 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
429 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
430 | Coil:Heating:Fuel | AIRLOOP DATACENTER MID HEATING COIL | Design Size Nominal Capacity [W] | 254135.75605 |
431 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.75315 |
432 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
433 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.75315 |
434 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1295.14241 |
435 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.75315 |
436 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.75315 |
437 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.75315 |
438 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75315 |
439 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.75315 |
440 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.37657 |
441 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.50210 |
442 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 12467.27000 |
443 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6233.63500 |
444 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
445 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
446 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 12467.27000 |
447 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26162.92139 |
448 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
449 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
450 | Coil:Heating:Fuel | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Nominal Capacity [W] | 26162.92139 |
451 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.12543 |
452 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 25845.79619 |
453 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.12543 |
454 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 15.05119 |
455 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.12543 |
456 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.12543 |
457 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 526478.40754 |
458 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 6.67000 |
459 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.12378E-002 |
460 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 3.74854 |
461 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.12378E-002 |
462 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 9407.45993 |
463 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
464 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3570674.83876 |
465 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 3570674.84000 |
466 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.12378E-002 |
467 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.12543 |
468 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 15.05119 |
469 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 6.27133E-002 |
470 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 11929.02017 |
471 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 6.27133E-002 |
472 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 11929.02017 |
473 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12543 |
474 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.32600E-002 |
475 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1771111.54370 |
476 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1771080.83500 |
477 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 8.87603E-002 |
478 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12543 |
479 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.32600E-002 |
480 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1771111.54370 |
481 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1771080.83500 |
482 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 8.87603E-002 |
483 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
484 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
485 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
486 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
487 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
488 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.17752 |
489 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 21.30248 |
490 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.17752 |
491 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 61901.66189 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 73.38296 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 2120900.81853 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 14.67659 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 265112.60232 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 73.38296 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 2120900.81853 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 14.67659 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 265112.60232 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 27289.87 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 590378.68 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 173443.20 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 30289.28 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 20169.18 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 32952.68 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 17120.43 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 436129.18 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 283835.83 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 436131.31 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 280946.78 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 57214.75 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 37139.58 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 57215.20 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 37275.30 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 46834.21 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 474542.69 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 42262.84 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94838.35 |
20 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | 94838.35 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 297097.35 | 207319.16 | 89778.19 | 0.70 | 36481.24 | 370.01 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2818304.41 | 1957769.86 | 860534.55 | 0.69 | 344950.75 | 3498.68 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 397061.06 | 278120.13 | 118940.93 | 0.70 | 48874.35 | 495.71 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 169052.05 | 119096.26 | 49955.79 | 0.70 | 21748.77 | 220.59 |
5 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | 572927.12 | 435471.07 | 137456.05 | 0.76 | 56204.41 | 570.06 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | 12003.8 | 9.16 | 9.16 | |||
2 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | 115328.9 | 10.40 | 10.40 | |||
3 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | 11877.0 | 9.16 | 9.16 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 6.37 | 21.74 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 6.37 | 21.74 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 9.5649237986E-004 | 1.4651895950E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.5505621087E-003 | 6.1704778700E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.7486420606E-002 | 2.8188828676E-002 | Pass | Pass | 0.4877441172 | 0.4896484861 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.0731140208E-002 | 6.4424158249E-002 | Pass | Pass | 2.3496778292 | 10.7868159513 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.3774632639E-002 | 1.7993444208E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.3382698350E-002 | 1.6775100516E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 2.6493252314E-002 | 2.1047446887E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 2.5032870480E-002 | 1.9515645847E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3318885415 | 0.3432591663 | Pass | Pass | 2.7303255107 | 17.5266991092 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3365464345 | 0.3460954002 | Pass | Pass | 1.4588608380 | 7.0009515427 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3012698399 | 0.3214751371 | Pass | Pass | 1.5845535210 | 7.6874745616 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2057938560 | 0.2341573750 | Pass | Pass | 0.9619127264 | 1.0970414797 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5098355970 | 0.5160565019 | Pass | Pass | 2.2603866425 | 12.5190320577 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5140866025 | 0.5190723618 | Pass | Pass | 1.6981576084 | 8.3666872788 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4770264634 | 0.4927657369 | Pass | Pass | 1.6820929673 | 8.2889731913 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3836408598 | 0.4043799925 | Pass | Pass | 1.2922125405 | 5.4718736809 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.9231856053E-003 | 5.1233105595E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.9751714540E-002 | 1.9283953786E-002 | Pass | Pass | 0.4998862938 | 0.4621612509 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1991783678 | 0.1406480715 | Pass | Pass | 0.4945043360 | 0.4776666912 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.5506660279E-008 | 1.3807247319E-007 | Pass | Pass | 8.8175977698E-003 | 5.8687487258E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.1823322915E-003 | 4.2884772472E-003 | Pass | Pass | 1.3723679103E-003 | 1.3036899111E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.0683813125E-002 | 7.8965794597E-003 | Pass | Pass | 2.6008450005E-003 | 2.2239317999E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.0304162076E-002 | 1.9321063133E-002 | Pass | Pass | 1.6694111990E-003 | 1.3814095068E-003 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6727.66 | 291.42 | 0.00 | 28301.83 | 14610.63 | 49931.56 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
North Total or Average | 1390.74 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 3.241 | 0.391 | 0.431 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 11.6510 | 2779.43 | 32383.10 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 333.79 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.6510 | 24961.20 | 290822.99 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 2997.66 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.6510 | 3134.13 | 36515.73 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.6510 | 3134.20 | 36516.53 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 11.6510 | 783.68 | 9130.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 94.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 22.3674 | 362.03 | 8097.60 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 83.47 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
Interior Lighting Total | 11.7515 | 46320.38 | 544334.28 | 1723.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 64082.80 | AstronomicalClock | - | 83.67 | 83.67 | 1006.46 | |
Exterior Lighting Total | 64082.80 | 1006.46 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3502461.23 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 3570674.84 | 0.79 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1771080.83 | 6.11 | 1762438.92 | 6.08 | 6.37 | 21.74 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1771080.83 | 6.11 | 1762438.92 | 6.08 | 6.37 | 21.74 |
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 2120900.82 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 2120900.82 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 245023.19 | 297097.35 | 207319.16 | 89778.19 | 0.70 | - | 36481.24 | 370.01 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2357080.43 | 2818304.41 | 1957769.86 | 860534.55 | 0.69 | - | 344950.75 | 3498.68 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 323915.64 | 397061.06 | 278120.13 | 118940.93 | 0.70 | - | 48874.35 | 495.71 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 130970.70 | 169052.05 | 119096.26 | 49955.79 | 0.70 | - | 21748.77 | 220.59 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | 454621.01 | 572927.12 | 435471.07 | 137456.05 | 0.76 | - | 56204.41 | 570.06 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | 12600.35 | 10088.60 | 2511.75 | 0.80 | 3.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | 121060.40 | 96928.22 | 24132.18 | 0.80 | 3.50 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 12467.27 | 9982.04 | 2485.23 | 0.80 | 3.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
AIRLOOP DATACENTER BOT COOLING COIL | 12003.8 | 9.16 | 9.16 | ||||
AIRLOOP DATACENTER MID COOLING COIL | 115328.9 | 10.40 | 10.40 | ||||
AIRLOOP DATACENTER TOP COOLING COIL | 11877.0 | 9.16 | 9.16 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 28747.13 | 27289.87 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 622313.75 | 590378.68 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 182823.37 | 173443.20 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 31927.33 | 30289.28 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 21259.93 | 20169.18 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 34734.76 | 32952.68 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 18046.31 | 17120.43 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 459714.64 | 436129.18 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 299185.40 | 283835.83 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 459716.88 | 436131.31 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 296140.11 | 280946.78 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 60308.85 | 57214.75 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 39148.03 | 37139.58 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 60309.32 | 57215.20 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 39291.10 | 37275.30 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 59044.78 | 46834.21 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 607949.48 | 474542.69 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 50013.67 | 42262.84 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94838.35 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | 100000.00 | 94838.35 | - |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | 26438.98 | 0.80 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | 254135.76 | 0.79 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | 26162.92 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 12.23 | 26735.47 | 2186.10 | 1.00 | 1.12 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 114.63 | 250590.00 | 2186.10 | 1.00 | 1.08 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1337.13 | 16.51 | 35745.89 | 2165.39 | 1.00 | 1.12 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
CAV_BAS SZVAV FAN | Fan:VariableVolume | 0.61 | 1337.13 | 7.09 | 15585.08 | 2197.78 | 1.00 | 1.13 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 0.61 | 637.69 | 32.15 | 33372.63 | 1038.16 | 1.00 | 1.19 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.76 | 1308.97 | 1719.64 | 1.00 | 1.36 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 7.31 | 12576.16 | 1719.64 | 1.00 | 1.08 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.75 | 1295.14 | 1719.64 | 1.00 | 1.36 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.83 | 0.125427 | 25845.80 | 206063.11 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.031238 | 9407.46 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.062713 | 11929.02 | 190215.15 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.062713 | 11929.02 | 190215.15 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 209234.68 | 0.177521 | 61901.66 | 348701.22 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 82814.62 | 95236.82 | 34.26 | 6.166 | 7.091 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 23.42 | 0.01335 | 1.200 | 0.00 |
CORE_BOTTOM | 88021.07 | 101224.23 | 40.55 | 6.554 | 7.537 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00885 | 23.42 | 0.01335 | 1.078 | 0.00 |
CORE_MID | 835887.13 | 961270.20 | 385.11 | 62.226 | 71.559 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00887 | 23.42 | 0.01335 | 10.778 | 0.00 |
CORE_TOP | 91426.97 | 105141.02 | 42.12 | 6.868 | 7.899 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00883 | 30.30 | 0.01337 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 14695.82 | 16900.19 | 53.92 | 1.104 | 1.270 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00889 | 30.30 | 0.01337 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 19054.84 | 21913.06 | 108.49 | 1.432 | 1.646 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00870 | 25.45 | 0.01336 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 22536.19 | 25916.62 | 82.69 | 1.693 | 1.947 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00876 | 29.99 | 0.01337 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 23261.47 | 26750.70 | 132.45 | 1.748 | 2.010 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00866 | 28.84 | 0.01336 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 139613.45 | 160555.46 | 512.28 | 10.489 | 12.063 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00908 | 30.30 | 0.01337 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 201104.34 | 231269.99 | 1145.04 | 15.109 | 17.375 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00878 | 25.98 | 0.01336 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 222610.37 | 256001.93 | 816.80 | 16.725 | 19.234 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00887 | 30.07 | 0.01337 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 214674.41 | 246875.58 | 1222.31 | 16.129 | 18.548 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00876 | 28.84 | 0.01336 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 16995.03 | 19544.28 | 62.36 | 1.277 | 1.468 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00904 | 30.30 | 0.01337 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 20405.14 | 23465.92 | 116.18 | 1.533 | 1.763 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00881 | 26.24 | 0.01336 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 25105.19 | 28870.97 | 92.12 | 1.886 | 2.169 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00887 | 30.14 | 0.01337 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 23342.81 | 26844.23 | 132.91 | 1.754 | 2.017 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00877 | 28.84 | 0.01336 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8810.86 | 10132.48 | 279.88 | 0.662 | 0.761 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00856 | 26.50 | 0.01336 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 84651.72 | 97349.47 | 2689.01 | 6.359 | 7.313 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00857 | 26.50 | 0.01336 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8717.79 | 10025.46 | 276.93 | 0.655 | 0.753 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.00 | 27.00 | 0.00856 | 26.67 | 0.01336 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372099.23 | 427914.12 | 546.03 | 27.953 | 32.146 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00853 | 21.84 | 0.01335 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 22.41 | 0.00092 | -16.30 | 0.00092 | 1.200 | 0.00 |
CORE_BOTTOM | 5434.54 | 6793.17 | 2.72 | 0.401 | 1.078 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 1.078 | 0.00 |
CORE_MID | 290866.95 | 363583.68 | 145.66 | 21.318 | 26.647 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 10.778 | 0.00 |
CORE_TOP | 84959.34 | 106199.17 | 42.55 | 6.313 | 7.892 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 14827.27 | 18534.08 | 59.14 | 1.104 | 1.380 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 9872.60 | 12340.75 | 61.10 | 0.735 | 0.919 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -16.30 | 0.00092 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 16128.35 | 20160.43 | 64.32 | 1.201 | 1.502 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 8383.78 | 10479.72 | 51.89 | 0.624 | 0.780 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -16.30 | 0.00092 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 213405.63 | 266757.04 | 851.14 | 15.912 | 19.890 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -16.30 | 0.00092 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 138885.60 | 173607.00 | 859.55 | 10.356 | 12.945 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -16.30 | 0.00092 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 213406.68 | 266758.34 | 851.12 | 15.912 | 19.891 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -16.30 | 0.00092 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 137473.55 | 171841.93 | 850.81 | 10.251 | 12.813 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -16.30 | 0.00092 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 27988.33 | 34985.42 | 111.63 | 2.088 | 2.610 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 18168.05 | 22710.07 | 112.44 | 1.356 | 1.695 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -16.30 | 0.00092 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 27988.55 | 34985.69 | 111.63 | 2.088 | 2.610 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 18234.26 | 22792.82 | 112.85 | 1.361 | 1.701 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -16.30 | 0.00092 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.42 | 0.00163 | -16.30 | 0.00092 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.55 | 0.00163 | -16.30 | 0.00092 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 19.54 | 0.00163 | -16.30 | 0.00092 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 01:50:00 | 18.00 | 27.00 | 0.00850 | -16.30 | 0.00092 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 12.23 | 12.23 | 5.66 | 5.66 | 12.2297 | 5.6585 | 12.2297 | 0.4627 | 0.3000 |
VAV_MID WITH REHEAT | 114.63 | 114.63 | 92.19 | 92.19 | 114.6286 | 92.1866 | 114.6286 | 0.8042 | 0.3000 |
VAV_TOP WITH REHEAT | 14.08 | 14.08 | 16.51 | 16.51 | 14.0788 | 16.5078 | 16.5078 | 1.0000 | 0.3000 |
CAV_BAS | 7.09 | 7.09 | 1.20 | 1.20 | 7.0913 | 2.1274 | 7.0913 | 0.3000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 32.15 | 32.15 | 0.34 | 0.34 | 32.1460 | 16.0729 | 32.1460 | 0.5000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.76 | 0.76 | 0.02 | 0.02 | 0.7612 | 0.7612 | 0.7612 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 7.31 | 7.31 | 0.16 | 0.16 | 7.3133 | 7.3133 | 7.3133 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.75 | 0.75 | 0.02 | 0.02 | 0.7531 | 0.7531 | 0.7531 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 28747.133 | 28747.133 | 2.261083 | 0.00025149 | 597.972 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28747.13 | 28747.13 | 2.261083 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00799855 | 50.4095 | 6793.17 | 0.00 | 28888.77 | 28888.77 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 622313.754 | 622313.754 | 26.647062 | 0.00544427 | 14575.620 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 622313.75 | 622313.75 | 26.647062 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 363583.68 | 0.00 | 625163.79 | 625163.79 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 182823.374 | 182823.374 | 7.891660 | 0.00159942 | 4272.396 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 182823.37 | 181748.65 | 7.891660 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 106199.17 | 0.00 | 183661.42 | 183661.42 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 31927.328 | 31927.328 | 1.380102 | 0.00027931 | 745.817 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 31927.33 | 31756.45 | 1.380102 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00778103 | 49.0584 | 18534.08 | 0.00 | 32073.70 | 32073.70 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 21259.931 | 21259.931 | 0.919074 | 0.00018599 | 496.616 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21259.93 | 21259.93 | 0.919074 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00778114 | 49.0591 | 12340.75 | 0.00 | 21357.40 | 21357.40 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 34734.757 | 34734.757 | 1.501752 | 0.00030387 | 811.354 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 34734.76 | 34734.76 | 1.501752 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00779868 | 49.1681 | 20160.43 | 0.00 | 34894.01 | 34894.01 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 18046.311 | 18046.311 | 0.779767 | 0.00015788 | 421.605 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18046.31 | 18046.31 | 0.779767 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00773799 | 48.7906 | 10479.72 | 0.00 | 18129.04 | 18129.04 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 459714.636 | 459714.636 | 19.890479 | 0.00402178 | 10736.056 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 459714.64 | 457684.46 | 19.890479 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765078 | 48.2502 | 266757.04 | 0.00 | 461822.47 | 461822.47 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 299185.395 | 299185.395 | 12.945162 | 0.00261740 | 6987.052 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 299185.40 | 299185.40 | 12.945162 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00764256 | 48.1991 | 173607.00 | 0.00 | 300557.19 | 300557.19 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 459716.883 | 459716.883 | 19.890576 | 0.00402180 | 10736.109 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 459716.88 | 457686.68 | 19.890576 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765078 | 48.2502 | 266758.34 | 0.00 | 461824.73 | 461824.73 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 296140.114 | 296140.114 | 12.813284 | 0.00259076 | 6915.951 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 296140.11 | 296140.11 | 12.813284 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00763944 | 48.1797 | 171841.93 | 0.00 | 297497.95 | 297497.95 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 60308.846 | 60308.846 | 2.610432 | 0.00052761 | 1408.280 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 60308.85 | 60066.64 | 2.610432 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00766680 | 48.3510 | 34985.42 | 0.00 | 60585.38 | 60585.38 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 39148.034 | 39148.034 | 1.694526 | 0.00034248 | 914.147 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39148.03 | 39148.03 | 1.694526 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765810 | 48.2970 | 22710.07 | 0.00 | 39327.54 | 39327.54 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 60309.319 | 60309.319 | 2.610453 | 0.00052761 | 1408.291 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 60309.32 | 60067.12 | 2.610453 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00766680 | 48.3510 | 34985.69 | 0.00 | 60585.86 | 60585.86 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 39291.097 | 39291.097 | 1.700739 | 0.00034374 | 917.485 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39291.10 | 39291.10 | 1.700739 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765970 | 48.3070 | 22792.82 | 0.00 | 39471.26 | 39471.26 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 245023.194 | -999.000 | 12.229739 | 0.00875166 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 245023.19 | 204473.30 | 12.229739 | 25.05 | 17.41 | 0.00959899 | 11.07 | 11.07 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 16.6030 | 24.00 | 0.00884741 | 46.4087 | 141331.42 | 0.00 | 249715.97 | 198742.74 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 59044.779 | 59044.779 | 3.668922 | 0.00051655 | 987.130 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 59044.78 | 59044.78 | 3.668922 | -0.75 | -0.75 | 0.00382944 | 12.89 | 11.41 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 55.3432 | 19.17 | 0.00751005 | 53.0367 | 15112.87 | 0.00 | 56677.20 | 56677.20 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2357080.433 | -999.000 | 114.628627 | 0.08418945 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2357080.43 | 1928467.15 | 114.628627 | 25.14 | 17.55 | 0.00973958 | 11.07 | 11.07 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 17.7146 | 24.00 | 0.00894014 | 46.8892 | 1301463.54 | 0.00 | 2401578.97 | 1877311.95 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 607949.478 | 607949.478 | 34.388588 | 0.00531861 | 10083.265 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 607949.48 | 607949.48 | 34.388588 | -2.10 | -2.10 | 0.00354214 | 12.89 | 11.41 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 59.0487 | 18.31 | 0.00756919 | 56.4261 | 161173.06 | 0.00 | 574219.14 | 574219.14 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 323915.640 | -999.000 | 16.507811 | 0.01156952 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 323915.64 | 273006.48 | 16.507811 | 24.91 | 17.30 | 0.00952317 | 11.08 | 11.08 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 12.3002 | 24.00 | 0.00887438 | 46.5492 | 162740.87 | 0.00 | 330188.93 | 265195.89 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 50013.669 | 50013.669 | 4.952343 | 0.00043754 | 863.681 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 50013.67 | 50013.67 | 4.952343 | 4.33 | 3.65 | 0.00476153 | 12.89 | 11.41 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 41.0008 | 17.45 | 0.00775720 | 61.0098 | 18543.16 | 0.00 | 51158.58 | 51158.58 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 130970.697 | -999.000 | 7.091279 | 0.00467797 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 130970.70 | 106588.96 | 7.091279 | 23.95 | 17.09 | 0.00966830 | 11.06 | 11.06 | 0.00850000 | 23.42 | 0.01335480 | 19.78 | 16.9244 | 24.00 | 0.00891728 | 46.7697 | 82814.62 | 0.00 | 136961.64 | 106347.36 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.116633 | 0.00087484 | 2622.476 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.116633 | -2.76 | -6.46 | 0.00092409 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 38.5081 | 22.51 | 0.00092409 | 5.3708 | 0.00 | 0.00 | 100076.34 | 100076.34 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 454621.014 | -999.000 | 32.145980 | 0.01623801 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 454621.01 | 448666.86 | 32.145980 | 27.03 | 17.25 | 0.00858398 | 15.02 | 12.77 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 1.0527 | 27.00 | 0.00853304 | 37.4749 | 371674.40 | 0.00 | 479753.91 | 479753.91 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 100000.000 | 100000.000 | 3.116633 | 0.00087484 | 2622.476 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.116633 | -0.17 | -0.17 | 0.00842025 | 29.11 | 17.47 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 10.8576 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | 100076.34 | 100076.34 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER BOT | 12600.350 | 10088.596 | 0.761190 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 6300.18 | 6141.74 | 0.507460 | 26.99 | 17.30 | 0.00866280 | 14.45 | 12.54 | 0.00850000 | 26.50 | 0.01336023 | 20.72 | 3.0805 | 27.00 | 0.00856431 | 37.6084 | 8810.86 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER BOT | 26438.984 | 26438.984 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 26438.98 | 26438.98 | 0.761187 | -0.33 | -3.75 | 0.00161156 | 29.11 | 17.47 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 2.0537 | 25.20 | 0.00162598 | 8.0301 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER MID | 121060.400 | 96928.220 | 7.313260 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 60530.20 | 58948.20 | 4.875507 | 26.99 | 17.30 | 0.00866936 | 14.45 | 12.54 | 0.00850000 | 26.50 | 0.01336023 | 20.72 | 3.2063 | 27.00 | 0.00856690 | 37.6197 | 84651.72 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER MID | 254135.756 | 254135.756 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 254135.76 | 254135.76 | 7.313259 | -0.35 | -3.76 | 0.00161099 | 29.11 | 17.47 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 2.1375 | 23.71 | 0.00162599 | 8.7795 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER TOP | 12467.270 | 9982.044 | 0.753150 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6233.64 | 6075.34 | 0.502100 | 26.99 | 17.30 | 0.00866446 | 14.45 | 12.54 | 0.00850000 | 26.67 | 0.01336053 | 20.77 | 3.1134 | 27.00 | 0.00856493 | 37.6111 | 8717.79 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER TOP | 26162.921 | 26162.921 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 26162.92 | 26162.92 | 0.753148 | -0.34 | -3.75 | 0.00161059 | 29.11 | 17.47 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 2.0756 | 21.78 | 0.00162514 | 9.8627 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 28747.133 | 28747.133 | 2.261083 | 0.00025149 | 597.972 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 31.23463457 | 54.44 | 82.22 | 27.78 | 3642536.09 | 0.7892 | 0.805090 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 28747.13 | 28747.13 | 1.0000 | 2.65434258 | 2.261083 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.25146680 | 60.00 | 32.22 | 27.78 | 0.000 | 28747.13 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.86 | 0.00799855 | 21.00 | 0.00799855 | 50.4095 | 6793.17 | 0.00 | 28888.77 | 28888.77 | 2.65434258 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 23.47 | 15.76 | 0.00800000 | 43943.4 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 622313.754 | 622313.754 | 26.647062 | 0.00544427 | 14575.620 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 31.23463457 | 54.44 | 82.22 | 27.78 | 3642536.09 | 17.0846 | 17.428463 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 622313.75 | 622313.75 | 1.0000 | 31.28166023 | 26.647062 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 5.44371682 | 60.00 | 32.22 | 27.78 | 0.000 | 622313.75 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 363583.68 | 0.00 | 625163.79 | 625163.79 | 31.28166023 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.40 | 18.83 | 0.00800000 | 53044.8 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 182823.374 | 182823.374 | 7.891660 | 0.00159942 | 4272.396 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 31.23463457 | 54.44 | 82.22 | 27.78 | 3642536.09 | 5.0191 | 5.120135 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 182823.37 | 181748.65 | 1.0000 | 9.26421974 | 7.891660 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 1.59925547 | 60.00 | 32.22 | 27.78 | 0.000 | 182823.37 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 106199.17 | 0.00 | 183661.42 | 183661.42 | 9.26421974 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.24 | 18.78 | 0.00800000 | 52884.6 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 31927.328 | 31927.328 | 1.380102 | 0.00027931 | 745.817 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 31.23463457 | 54.44 | 82.22 | 27.78 | 3642536.09 | 0.8765 | 0.894154 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 31927.33 | 31756.45 | 1.0000 | 1.62013610 | 1.380102 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.27928570 | 60.00 | 32.22 | 27.78 | 0.000 | 31927.33 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00778103 | 21.00 | 0.00778103 | 49.0584 | 18534.08 | 0.00 | 32073.70 | 32073.70 | 1.62013610 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52856.7 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21259.931 | 21259.931 | 0.919074 | 0.00018599 | 496.616 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 31.23463457 | 54.44 | 82.22 | 27.78 | 3642536.09 | 0.5837 | 0.595404 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21259.93 | 21259.93 | 1.0000 | 1.07892481 | 0.919074 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.18597218 | 60.00 | 32.22 | 27.78 | 0.000 | 21259.93 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00778114 | 21.00 | 0.00778114 | 49.0591 | 12340.75 | 0.00 | 21357.40 | 21357.40 | 1.07892481 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52854.9 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34734.757 | 34734.757 | 1.501752 | 0.00030387 | 811.354 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 31.23463457 | 54.44 | 82.22 | 27.78 | 3642536.09 | 0.9536 | 0.972778 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 34734.76 | 34734.76 | 1.0000 | 1.76294417 | 1.501752 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.30384381 | 60.00 | 32.22 | 27.78 | 0.000 | 34734.76 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00779868 | 21.00 | 0.00779868 | 49.1681 | 20160.43 | 0.00 | 34894.01 | 34894.01 | 1.76294417 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52852.9 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18046.311 | 18046.311 | 0.779767 | 0.00015788 | 421.605 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 31.23463457 | 54.44 | 82.22 | 27.78 | 3642536.09 | 0.4954 | 0.505403 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18046.31 | 18046.31 | 1.0000 | 0.91538851 | 0.779767 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.15786090 | 60.00 | 32.22 | 27.78 | 0.000 | 18046.31 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00773799 | 21.00 | 0.00773799 | 48.7906 | 10479.72 | 0.00 | 18129.04 | 18129.04 | 0.91538851 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52864.6 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 459714.636 | 459714.636 | 19.890479 | 0.00402178 | 10736.056 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 31.23463457 | 54.44 | 82.22 | 27.78 | 3642536.09 | 12.6207 | 12.874727 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 459714.64 | 457684.46 | 1.0000 | 23.34993714 | 19.890479 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 4.02137392 | 60.00 | 32.22 | 27.78 | 0.000 | 459714.64 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00765078 | 21.00 | 0.00765078 | 48.2502 | 266757.04 | 0.00 | 461822.47 | 461822.47 | 23.34993714 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52838.1 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 299185.395 | 299185.395 | 12.945162 | 0.00261740 | 6987.052 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 31.23463457 | 54.44 | 82.22 | 27.78 | 3642536.09 | 8.2137 | 8.378959 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 299185.40 | 299185.40 | 1.0000 | 15.19665342 | 12.945162 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 2.61713735 | 60.00 | 32.22 | 27.78 | 0.000 | 299185.40 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00764256 | 21.00 | 0.00764256 | 48.1991 | 173607.00 | 0.00 | 300557.19 | 300557.19 | 15.19665342 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52837.7 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 459716.883 | 459716.883 | 19.890576 | 0.00402180 | 10736.109 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 31.23463457 | 54.44 | 82.22 | 27.78 | 3642536.09 | 12.6208 | 12.874790 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 459716.88 | 457686.68 | 1.0000 | 23.35005049 | 19.890576 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 4.02139357 | 60.00 | 32.22 | 27.78 | 0.000 | 459716.88 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00765078 | 21.00 | 0.00765078 | 48.2502 | 266758.34 | 0.00 | 461824.73 | 461824.73 | 23.35005049 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52838.1 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 296140.114 | 296140.114 | 12.813284 | 0.00259076 | 6915.951 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 31.23463457 | 54.44 | 82.22 | 27.78 | 3642536.09 | 8.1301 | 8.293674 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 296140.11 | 296140.11 | 1.0000 | 15.04183798 | 12.813284 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 2.59049862 | 60.00 | 32.22 | 27.78 | 0.000 | 296140.11 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00763944 | 21.00 | 0.00763944 | 48.1797 | 171841.93 | 0.00 | 297497.95 | 297497.95 | 15.04183798 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52837.9 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 60308.846 | 60308.846 | 2.610432 | 0.00052761 | 1408.280 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 31.23463457 | 54.44 | 82.22 | 27.78 | 3642536.09 | 1.6557 | 1.689004 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 60308.85 | 60066.64 | 1.0000 | 3.06445271 | 2.610432 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.52755427 | 60.00 | 32.22 | 27.78 | 0.000 | 60308.85 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00766680 | 21.00 | 0.00766680 | 48.3510 | 34985.42 | 0.00 | 60585.38 | 60585.38 | 3.06445271 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52830.2 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 39148.034 | 39148.034 | 1.694526 | 0.00034248 | 914.147 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 31.23463457 | 54.44 | 82.22 | 27.78 | 3642536.09 | 1.0747 | 1.096376 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39148.03 | 39148.03 | 1.0000 | 1.98924715 | 1.694526 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.34244915 | 60.00 | 32.22 | 27.78 | 0.000 | 39148.03 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00765810 | 21.00 | 0.00765810 | 48.2970 | 22710.07 | 0.00 | 39327.54 | 39327.54 | 1.98924715 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52829.9 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 60309.319 | 60309.319 | 2.610453 | 0.00052761 | 1408.291 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 31.23463457 | 54.44 | 82.22 | 27.78 | 3642536.09 | 1.6557 | 1.689017 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 60309.32 | 60067.12 | 1.0000 | 3.06447672 | 2.610453 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.52755841 | 60.00 | 32.22 | 27.78 | 0.000 | 60309.32 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00766680 | 21.00 | 0.00766680 | 48.3510 | 34985.69 | 0.00 | 60585.86 | 60585.86 | 3.06447672 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52830.2 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 39291.097 | 39291.097 | 1.700739 | 0.00034374 | 917.485 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 31.23463457 | 54.44 | 82.22 | 27.78 | 3642536.09 | 1.0787 | 1.100383 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39291.10 | 39291.10 | 1.0000 | 1.99654111 | 1.700739 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.34370059 | 60.00 | 32.22 | 27.78 | 0.000 | 39291.10 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00765970 | 21.00 | 0.00765970 | 48.3070 | 22792.82 | 0.00 | 39471.26 | 39471.26 | 1.99654111 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52829.6 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 245023.194 | -999.000 | 12.229739 | 0.00875166 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.6840 | 1004.8586 | 1.1739 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 12.229739 | 14.35679972 | 4197.9300 | 999.8980 | 125.41381289 | 13.34 | 6.67 | 6.67 | 3511610.98 | 6.9775 | 6.977515 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 245023.19 | 204473.30 | 1.0000 | 14.35679972 | 12.229739 | 25.05 | 17.41 | 0.00959899 | 49621.1 | 11.07 | 11.07 | 0.00850000 | 32554.4 | 8.75076801 | 6.67 | 13.34 | 6.67 | 26735.470 | 218287.72 | 30.30 | 0.01336696 | 21.83 | 2.03050000 | 16.6030 | 24.00 | 0.00884741 | 24.00 | 0.00884741 | 46.4087 | 141331.42 | 0.00 | 249715.97 | 198742.74 | 14.35679972 | 25.05 | 17.67 | 0.00959899 | 49621.1 | 11.51 | 11.25 | 0.00819138 | 32227.6 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 59044.779 | 59044.779 | 3.668922 | 0.00051655 | 987.130 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 12.229739 | 14.35679972 | 4197.9300 | 999.8980 | 31.23463457 | 54.44 | 82.22 | 27.78 | 3642536.09 | 1.6210 | 1.653603 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 59044.78 | 59044.78 | 1.0000 | 4.30703992 | 3.668922 | -0.75 | -0.75 | 0.00382944 | 8814.5 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 0.51649679 | 60.00 | 32.22 | 27.78 | 0.000 | 59044.78 | -16.30 | 0.00092409 | -16.30 | 2.03050000 | 55.3432 | 18.51 | 0.00743004 | 19.17 | 0.00751005 | 53.0367 | 15112.87 | 0.00 | 56677.20 | 56677.20 | 4.30703992 | 2.80 | 1.71 | 0.00382944 | 12410.7 | 15.80 | 8.41 | 0.00382944 | 25569.9 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2357080.433 | -999.000 | 114.628627 | 0.08418945 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.9454 | 1004.8586 | 1.1739 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 114.628627 | 134.56544646 | 4197.9300 | 999.8980 | 125.41381289 | 13.34 | 6.67 | 6.67 | 3511610.98 | 67.1225 | 67.122482 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2357080.43 | 1928467.15 | 1.0000 | 134.56544646 | 114.628627 | 25.14 | 17.55 | 0.00973958 | 50071.1 | 11.07 | 11.07 | 0.00850000 | 32554.9 | 84.18086349 | 6.67 | 13.34 | 6.67 | 250590.003 | 2106490.43 | 30.30 | 0.01336696 | 21.83 | 20.30600000 | 17.7146 | 24.00 | 0.00894014 | 24.00 | 0.00894014 | 46.8892 | 1301463.54 | 0.00 | 2401578.97 | 1877311.95 | 134.56544646 | 25.14 | 17.82 | 0.00973958 | 50071.1 | 11.50 | 11.24 | 0.00819497 | 32224.2 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 607949.478 | 607949.478 | 34.388588 | 0.00531861 | 10083.265 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 114.628627 | 134.56544646 | 4197.9300 | 999.8980 | 31.23463457 | 54.44 | 82.22 | 27.78 | 3642536.09 | 16.6903 | 17.026179 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 607949.48 | 607949.48 | 1.0000 | 40.36963394 | 34.388588 | -2.10 | -2.10 | 0.00354214 | 6736.9 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 5.31806470 | 60.00 | 32.22 | 27.78 | 0.000 | 607949.48 | -16.30 | 0.00092409 | -16.30 | 20.30600000 | 59.0487 | 18.38 | 0.00731717 | 18.31 | 0.00756919 | 56.4261 | 161173.06 | 0.00 | 574219.14 | 574219.14 | 40.36963394 | 2.80 | 1.30 | 0.00354214 | 11690.7 | 16.86 | 8.58 | 0.00354214 | 25914.7 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 323915.640 | -999.000 | 16.507811 | 0.01156952 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.5431 | 1004.8586 | 1.1739 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 16.507811 | 19.37893744 | 4197.9300 | 999.8980 | 125.41381289 | 13.34 | 6.67 | 6.67 | 3511610.98 | 9.2241 | 9.224132 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 323915.64 | 273006.48 | 1.0000 | 19.37893744 | 16.507811 | 24.91 | 17.30 | 0.00952317 | 49286.6 | 11.08 | 11.08 | 0.00850000 | 32571.8 | 11.56833592 | 6.67 | 13.34 | 6.67 | 35745.894 | 288169.75 | 30.30 | 0.01336696 | 21.83 | 2.03050000 | 12.3002 | 24.00 | 0.00887438 | 24.00 | 0.00887438 | 46.5492 | 162740.87 | 0.00 | 330188.93 | 265195.89 | 19.37893744 | 24.91 | 17.57 | 0.00952317 | 49286.6 | 11.53 | 11.25 | 0.00819354 | 32248.1 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 50013.669 | 50013.669 | 4.952343 | 0.00043754 | 863.681 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 16.507811 | 19.37893744 | 4197.9300 | 999.8980 | 31.23463457 | 54.44 | 82.22 | 27.78 | 3642536.09 | 1.3730 | 1.400678 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 50013.67 | 50013.67 | 1.0000 | 5.81368123 | 4.952343 | 4.33 | 3.65 | 0.00476153 | 16295.3 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 0.43749676 | 60.00 | 32.22 | 27.78 | 0.000 | 50013.67 | -16.30 | 0.00092409 | -16.30 | 2.03050000 | 41.0008 | 18.66 | 0.00742831 | 17.45 | 0.00775720 | 61.0098 | 18543.16 | 0.00 | 51158.58 | 51158.58 | 5.81368123 | 2.80 | 2.80 | 0.00476153 | 14746.6 | 11.48 | 7.45 | 0.00476153 | 23546.3 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 130970.697 | -999.000 | 7.091279 | 0.00467797 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.8129 | 1004.8586 | 1.1739 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 7.091279 | 8.32463140 | 4197.9300 | 999.8980 | 125.41381289 | 13.34 | 6.67 | 6.67 | 3511610.98 | 3.7296 | 3.729647 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 130970.70 | 106588.96 | 1.0000 | 8.32463140 | 7.091279 | 23.95 | 17.09 | 0.00966830 | 48678.7 | 11.06 | 11.06 | 0.00850000 | 32544.7 | 4.67749265 | 6.67 | 13.34 | 6.67 | 15585.078 | 115385.62 | 23.42 | 0.01335480 | 19.78 | 1.20015641 | 16.9244 | 24.06 | 0.00891728 | 24.00 | 0.00891728 | 46.7697 | 82814.62 | 0.00 | 136961.64 | 106347.36 | 8.32463140 | 23.95 | 17.36 | 0.00966830 | 48678.7 | 11.46 | 11.25 | 0.00821025 | 32226.1 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.116633 | 0.00087484 | 2622.476 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 7.091279 | 8.32463140 | 4197.9300 | 999.8980 | 31.23463457 | 54.44 | 82.22 | 27.78 | 3642536.09 | 2.7453 | 2.800591 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.116633 | -2.76 | -6.46 | 0.00092409 | -465.7 | 32.11 | 18.46 | 0.00800000 | 52750.5 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -16.30 | 0.00092409 | -16.30 | 1.20015641 | 38.5081 | 0.00 | 0.00092409 | 22.51 | 0.00092409 | 5.3708 | 0.00 | 0.00 | 100076.34 | 100076.34 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40240.2 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 454621.014 | -999.000 | 32.145980 | 0.01623801 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7972 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 32.145980 | 37.73697989 | 4197.9300 | 999.8980 | 125.41381289 | 13.34 | 6.67 | 6.67 | 3511610.98 | 12.9462 | 12.946224 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 454621.01 | 448666.86 | 1.0000 | 37.73697989 | 32.145980 | 27.03 | 17.25 | 0.00858398 | 49063.0 | 15.02 | 12.77 | 0.00850000 | 36590.6 | 16.23635281 | 6.67 | 13.34 | 6.67 | 33372.630 | 421248.38 | 30.30 | 0.01336696 | 21.83 | 0.33839277 | 1.0527 | 27.00 | 0.00853304 | 27.00 | 0.00853304 | 37.4749 | 371674.40 | 0.00 | 479753.91 | 479753.91 | 37.73697989 | 27.03 | 17.51 | 0.00858398 | 49063.0 | 14.58 | 12.91 | 0.00858398 | 36349.9 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.116633 | 0.00087484 | 2622.476 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 32.145980 | 37.73697989 | 4197.9300 | 999.8980 | 31.23463457 | 54.44 | 82.22 | 27.78 | 3642536.09 | 2.7453 | 2.800591 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.116633 | -0.17 | -0.17 | 0.00842025 | 20883.4 | 29.11 | 17.47 | 0.00800000 | 49691.3 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -16.30 | 0.00092409 | -16.30 | 0.33839277 | 10.8576 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | 100076.34 | 100076.34 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40240.2 | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12600.350 | 10088.596 | 0.761190 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9437 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.761187 | 0.89357691 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 6300.18 | 6141.74 | 1.0000 | 0.59572014 | 0.507460 | 26.99 | 17.30 | 0.00866280 | 49219.0 | 14.45 | 12.54 | 0.00850000 | 36010.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6300.18 | 26.50 | 0.01336023 | 20.72 | 0.01563234 | 3.0805 | 27.00 | 0.00856431 | 27.00 | 0.00856431 | 37.6084 | 8810.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26438.984 | 26438.984 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.761187 | 0.89357691 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 26438.98 | 26438.98 | 1.0000 | 0.89357691 | 0.761187 | -0.33 | -3.75 | 0.00161156 | 3693.0 | 29.11 | 17.47 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26438.98 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 2.0537 | 0.00 | 0.00162598 | 25.20 | 0.00162598 | 8.0301 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 121060.400 | 96928.220 | 7.313260 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9559 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.313259 | 8.58521946 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 60530.20 | 58948.20 | 1.0000 | 5.72348069 | 4.875507 | 26.99 | 17.30 | 0.00866936 | 49235.3 | 14.45 | 12.54 | 0.00850000 | 36010.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 60530.20 | 26.50 | 0.01336023 | 20.72 | 0.15632344 | 3.2063 | 27.00 | 0.00856690 | 27.00 | 0.00856690 | 37.6197 | 84651.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 254135.756 | 254135.756 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.313259 | 8.58521946 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 254135.76 | 254135.76 | 1.0000 | 8.58521946 | 7.313259 | -0.35 | -3.76 | 0.00161099 | 3677.8 | 29.11 | 17.47 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 254135.76 | -16.30 | 0.00092409 | -16.30 | 0.15632344 | 2.1375 | 0.00 | 0.00162599 | 23.71 | 0.00162599 | 8.7795 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12467.270 | 9982.044 | 0.753150 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9468 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.753148 | 0.88413935 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6233.64 | 6075.34 | 1.0000 | 0.58942790 | 0.502100 | 26.99 | 17.30 | 0.00866446 | 49226.7 | 14.45 | 12.54 | 0.00850000 | 36010.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6233.64 | 26.67 | 0.01336053 | 20.77 | 0.01563234 | 3.1134 | 27.00 | 0.00856493 | 27.00 | 0.00856493 | 37.6111 | 8717.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26162.921 | 26162.921 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.753148 | 0.88413935 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 26162.92 | 26162.92 | 1.0000 | 0.88413935 | 0.753148 | -0.34 | -3.75 | 0.00161059 | 3687.0 | 29.11 | 17.47 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26162.92 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 2.0756 | 0.00 | 0.00162514 | 21.78 | 0.00162514 | 9.8627 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 12.23 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 114.63 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 16.51 | - | |||
CAV_BAS_OA_CONTROLLER | FixedDryBulb | 1.20 | 7.09 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 32.15 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2165.33 | 2202.33 | 32.83 |
CORE_BOTTOM | 2311.33 | 1829.83 | 12.67 |
CORE_MID | 1903.67 | 3070.83 | 198.67 |
CORE_TOP | 2622.67 | 3959.33 | 1229.00 |
PERIMETER_BOT_ZN_3 | 2671.83 | 3756.00 | 1087.17 |
PERIMETER_BOT_ZN_2 | 2602.00 | 3979.83 | 1079.50 |
PERIMETER_BOT_ZN_1 | 2752.17 | 3611.17 | 1025.00 |
PERIMETER_BOT_ZN_4 | 2521.17 | 3671.00 | 695.50 |
PERIMETER_MID_ZN_3 | 2973.00 | 4668.17 | 2024.17 |
PERIMETER_MID_ZN_2 | 2686.00 | 3742.00 | 1679.33 |
PERIMETER_MID_ZN_1 | 3008.17 | 3922.83 | 1507.33 |
PERIMETER_MID_ZN_4 | 2966.83 | 4472.50 | 1800.83 |
PERIMETER_TOP_ZN_3 | 3267.50 | 4983.83 | 2558.83 |
PERIMETER_TOP_ZN_2 | 3593.17 | 4404.50 | 2356.67 |
PERIMETER_TOP_ZN_1 | 3294.33 | 4373.83 | 2080.50 |
PERIMETER_TOP_ZN_4 | 3330.67 | 4651.50 | 2282.00 |
DATACENTER_BOT_ZN_6 | 5840.83 | 1070.00 | 1070.00 |
DATACENTER_MID_ZN_6 | 5190.83 | 457.83 | 395.50 |
DATACENTER_TOP_ZN_6 | 4590.67 | 930.50 | 548.67 |
DATACENTER_BASEMENT_ZN_6 | 5917.67 | 3408.17 | 3407.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5928.83 | 5140.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 6.67 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 1.33 | 0.00 | 0.33 | 0.00 |
CORE_TOP | 19.50 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 12.67 | 0.00 | 0.83 | 0.00 |
PERIMETER_BOT_ZN_2 | 13.17 | 7.83 | 0.17 | 7.83 |
PERIMETER_BOT_ZN_1 | 17.00 | 12.33 | 0.83 | 12.33 |
PERIMETER_BOT_ZN_4 | 5.83 | 34.83 | 0.00 | 21.17 |
PERIMETER_MID_ZN_3 | 104.33 | 0.00 | 16.00 | 0.00 |
PERIMETER_MID_ZN_2 | 152.50 | 7.50 | 10.33 | 7.50 |
PERIMETER_MID_ZN_1 | 85.00 | 10.00 | 7.00 | 10.00 |
PERIMETER_MID_ZN_4 | 78.50 | 16.50 | 7.83 | 8.83 |
PERIMETER_TOP_ZN_3 | 252.33 | 0.00 | 57.33 | 0.00 |
PERIMETER_TOP_ZN_2 | 246.17 | 6.50 | 48.67 | 6.50 |
PERIMETER_TOP_ZN_1 | 208.67 | 7.00 | 35.33 | 7.00 |
PERIMETER_TOP_ZN_4 | 177.83 | 17.00 | 33.67 | 9.17 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 5.67 | 0.00 | 5.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 381.17 | 94.00 | 68.50 | 67.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 0.870 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.821 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.668 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.613 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.932 | 0.059 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.683 | 0.061 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 1.404 | 0.059 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 2.032 | 0.061 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 1.172 | 0.137 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.639 | 0.151 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 1.390 | 0.138 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.804 | 0.142 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 1.404 | 0.170 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.603 | 0.176 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 1.541 | 0.171 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.797 | 0.176 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 17.560 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.11 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.51 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1029.47 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 35010165.16 | 0.00 | 35010165.16 | 0.00 | 35010165.16 | 37848132.68 | 4265.37 | 3004.97 | 1489.66 | 108.98 |
CORE_BOTTOM | 34184042.11 | 0.00 | 34184042.11 | 0.00 | 34184042.11 | 33990283.35 | 5872.58 | 37.86 | 2849.57 | 245.92 |
CORE_MID | 0.28E+09 | 0.00 | 0.28E+09 | 0.00 | 0.28E+09 | 0.34E+09 | 6503.94 | 34.34 | 2221.73 | 393.95 |
CORE_TOP | 24979045.66 | 0.00 | 24979045.66 | 0.00 | 24979045.66 | 33990283.35 | 6758.03 | 27.02 | 1974.96 | 373.43 |
PERIMETER_BOT_ZN_3 | 4919181.51 | 0.00 | 4919181.51 | 584665.50 | 5503847.01 | 4267819.30 | 4062.24 | 51.72 | 4646.03 | 245.92 |
PERIMETER_BOT_ZN_2 | 5742376.13 | 0.00 | 5742376.13 | 389776.73 | 6132152.87 | 2750345.05 | 3772.90 | 1.24 | 4985.86 | 245.92 |
PERIMETER_BOT_ZN_1 | 7398239.32 | 0.00 | 7398239.32 | 584665.50 | 7982904.82 | 4267912.63 | 3838.58 | 5.26 | 4916.16 | 245.92 |
PERIMETER_BOT_ZN_4 | 6938949.47 | 0.00 | 6938949.47 | 389776.73 | 7328726.20 | 2750345.05 | 3762.64 | 0.00 | 4997.36 | 245.92 |
PERIMETER_MID_ZN_3 | 61885359.70 | 0.00 | 61885359.70 | 1371204.53 | 63256564.24 | 42678193.03 | 3964.76 | 23.65 | 4771.59 | 393.95 |
PERIMETER_MID_ZN_2 | 52197313.42 | 0.00 | 52197313.42 | 914135.73 | 53111449.15 | 27503450.52 | 4300.80 | 15.30 | 4443.90 | 859.08 |
PERIMETER_MID_ZN_1 | 72721594.73 | 0.00 | 72721594.73 | 1371204.53 | 74092799.27 | 42679126.28 | 3927.52 | 9.55 | 4822.92 | 393.95 |
PERIMETER_MID_ZN_4 | 61191763.27 | 0.00 | 61191763.27 | 914135.73 | 62105899.00 | 27503450.52 | 3751.67 | 11.36 | 4996.97 | 393.95 |
PERIMETER_TOP_ZN_3 | 7241327.83 | 0.00 | 7241327.83 | 1702496.76 | 8943824.59 | 4267819.30 | 4085.58 | 11.32 | 4663.11 | 373.41 |
PERIMETER_TOP_ZN_2 | 5307143.79 | 0.00 | 5307143.79 | 1134997.06 | 6442140.85 | 2750345.05 | 4064.73 | 3.49 | 4691.78 | 373.41 |
PERIMETER_TOP_ZN_1 | 7919783.48 | 0.00 | 7919783.48 | 1702496.76 | 9622280.24 | 4267912.63 | 4073.03 | 3.65 | 4683.32 | 373.41 |
PERIMETER_TOP_ZN_4 | 5959080.78 | 0.00 | 5959080.78 | 1134997.06 | 7094077.84 | 2750345.05 | 4045.26 | 3.02 | 4711.72 | 373.41 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.30E+09 | 0.00 | 0.30E+09 | 0.00 | 0.30E+09 | 10671554.30 | 657.51 | 1080.98 | 7021.51 | 2454.32 |
Total Facility | 0.57E+10 | 0.00 | 0.57E+10 | 53330677.35 | 0.58E+10 | 0.50E+10 | 7140.63 | 4399.37 | 8165.61 | 2976.71 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.6099 | 0.0000 | 1.6099 | 0.0000 | 1.6099 | 1.2002 | 1490.07 | 3004.00 | 1448.92 |
CORE_BOTTOM | 1.5332 | 0.0000 | 1.5332 | 0.0000 | 1.5332 | 1.0778 | 3203.22 | 36.87 | 2702.92 |
CORE_MID | 12.4855 | 0.0000 | 12.4855 | 0.0000 | 12.4855 | 10.7782 | 3747.72 | 34.14 | 2161.15 |
CORE_TOP | 1.1477 | 0.0000 | 1.1477 | 0.0000 | 1.1477 | 1.0778 | 3962.71 | 26.16 | 1954.14 |
PERIMETER_BOT_ZN_3 | 0.2191 | 0.0000 | 0.2191 | 0.0139 | 0.2329 | 0.1353 | 1420.72 | 49.19 | 4473.09 |
PERIMETER_BOT_ZN_2 | 0.2555 | 0.0000 | 0.2555 | 0.0092 | 0.2647 | 0.0872 | 1193.79 | 0.91 | 4748.31 |
PERIMETER_BOT_ZN_1 | 0.3305 | 0.0000 | 0.3305 | 0.0139 | 0.3443 | 0.1353 | 1231.49 | 4.05 | 4707.46 |
PERIMETER_BOT_ZN_4 | 0.3083 | 0.0000 | 0.3083 | 0.0092 | 0.3176 | 0.0872 | 1191.55 | 0.00 | 4751.45 |
PERIMETER_MID_ZN_3 | 2.7667 | 0.0000 | 2.7667 | 0.0325 | 2.7993 | 1.3533 | 1318.30 | 19.28 | 4605.42 |
PERIMETER_MID_ZN_2 | 2.4913 | 0.0000 | 2.4913 | 0.0230 | 2.5142 | 0.8721 | 1223.79 | 5.62 | 3804.59 |
PERIMETER_MID_ZN_1 | 3.2736 | 0.0000 | 3.2736 | 0.0325 | 3.3061 | 1.3533 | 1279.83 | 5.19 | 4657.99 |
PERIMETER_MID_ZN_4 | 2.7436 | 0.0000 | 2.7436 | 0.0217 | 2.7652 | 0.8721 | 1208.23 | 5.13 | 4729.65 |
PERIMETER_TOP_ZN_3 | 0.3319 | 0.0000 | 0.3319 | 0.0404 | 0.3722 | 0.1353 | 1340.32 | 10.09 | 4592.59 |
PERIMETER_TOP_ZN_2 | 0.2436 | 0.0000 | 0.2436 | 0.0269 | 0.2705 | 0.0872 | 1323.06 | 1.86 | 4618.08 |
PERIMETER_TOP_ZN_1 | 0.3636 | 0.0000 | 0.3636 | 0.0404 | 0.4040 | 0.1353 | 1327.67 | 2.41 | 4612.92 |
PERIMETER_TOP_ZN_4 | 0.2734 | 0.0000 | 0.2734 | 0.0269 | 0.3004 | 0.0872 | 1311.87 | 2.03 | 4629.10 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 9.0977 | 0.0000 | 9.0977 | 0.0000 | 9.0977 | 0.3384 | 285.32 | 1080.90 | 4576.78 |
Total Facility | 254.4858 | 0.0000 | 254.4858 | 1.2780 | 255.7638 | 158.4706 | 4323.63 | 4371.44 | 5686.79 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 81559842.12 | 0.00 | 81559842.12 | 48026705.38 | 3841.97 | 6.71 | 4911.32 | 245.92 |
VAV_MID WITH REHEAT | 0.72E+09 | 0.00 | 0.72E+09 | 0.48E+09 | 3954.44 | 8.55 | 4797.00 | 393.95 |
VAV_TOP WITH REHEAT | 70843166.05 | 0.00 | 70843166.05 | 48026705.38 | 4111.91 | 2.85 | 4645.24 | 373.30 |
CAV_BAS | 48044620.03 | 0.00 | 48044620.03 | 37848132.68 | 4239.82 | 1.24 | 4518.94 | 108.98 |
AIRLOOP DATACENTER BASEMENT | 0.41E+09 | 0.00 | 0.41E+09 | 10671554.30 | 653.88 | 0.13 | 8105.99 | 2454.28 |
AIRLOOP DATACENTER BOT | 336664.50 | 0.00 | 336664.50 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3366645.00 | 0.00 | 3366645.00 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 336664.50 | 0.00 | 336664.50 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.6472 | 0.0000 | 3.6472 | 1.5229 | 1223.63 | 3.69 | 4715.67 |
VAV_MID WITH REHEAT | 32.5232 | 0.0000 | 32.5232 | 15.2292 | 1282.98 | 3.77 | 4656.25 |
VAV_TOP WITH REHEAT | 3.2526 | 0.0000 | 3.2526 | 1.5229 | 1354.09 | 1.80 | 4587.11 |
CAV_BAS | 2.2091 | 0.0000 | 2.2091 | 1.2002 | 1474.74 | 0.54 | 4467.72 |
AIRLOOP DATACENTER BASEMENT | 12.5376 | 0.0000 | 12.5376 | 0.3384 | 284.07 | 0.02 | 5658.92 |
AIRLOOP DATACENTER BOT | 0.0157 | 0.0000 | 0.0157 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1574 | 0.0000 | 0.1574 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0157 | 0.0000 | 0.0157 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 32.87 | 3390.19 | 0.00 | 0.00 | 0.00 | 1574.32 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 85.26 | 3516.77 | 0.00 | 0.00 | 0.00 | 1567.39 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 22.01 | 2993.65 | 0.00 | 0.00 | 0.00 | 2168.14 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 3025.03 | 1635.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 1080.72 | 7034.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.5893 | 5.7015 | 0.0000 | 0.0000 | 0.0000 | 2.3277 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 27.5272 | 49.0300 | 0.0000 | 0.0000 | 0.0000 | 24.1559 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.7158 | 5.3506 | 0.0000 | 0.0000 | 0.0000 | 2.4212 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6540 | 5.3246 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4667 | 16.1587 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1343 |
Defaulted Fields | 1287 |
Fields with Defaults | 3878 |
Autosized Fields | 320 |
Autosizable Fields | 465 |
Autocalculated Fields | 223 |
Autocalculatable Fields | 468 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 31093.99 | 289144.14 | 14-MAY-05:00 | 2356626.12 | 18-AUG-15:10 |
Electricity:Building | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 758.19 | 15076.70 | 01-JAN-00:10 | 42602.33 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 589.38 | 5907.35 | 01-JAN-00:10 | 43380.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5893.79 | 59073.32 | 01-JAN-00:10 | 433806.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 589.38 | 5907.33 | 01-JAN-00:10 | 43380.63 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 740.04 | 7417.49 | 01-JAN-00:10 | 54469.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 476.91 | 4780.12 | 01-JAN-00:10 | 35102.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 740.05 | 7417.62 | 01-JAN-00:10 | 54470.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 476.91 | 4780.09 | 01-JAN-00:10 | 35102.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7588.97 | 95364.66 | 01-JAN-00:10 | 387850.11 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1622.27 | 19890.94 | 01-JAN-00:10 | 85232.07 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:HVAC | 4183.82 | 32529.48 | 29-SEP-04:50 | 340384.90 | 06-JUL-13:00 |
ExteriorEquipment:Electricity | 2623.11 | 22123.82 | 01-JAN-00:10 | 235096.12 | 03-APR-07:20 |
Transformer:ExteriorEquipment:Electricity | 56.04 | 979.82 | 01-JAN-00:10 | 3543.78 | 03-APR-07:20 |
ElectricityPurchased:Facility | 31093.99 | 289144.14 | 14-MAY-05:00 | 2356626.12 | 18-AUG-15:10 |
ElectricityPurchased:Plant | 31093.99 | 289144.14 | 14-MAY-05:00 | 2356626.12 | 18-AUG-15:10 |
Cogeneration:ElectricityPurchased | 31093.99 | 289144.14 | 14-MAY-05:00 | 2356626.12 | 18-AUG-15:10 |
General:Cogeneration:ElectricityPurchased | 31093.99 | 289144.14 | 14-MAY-05:00 | 2356626.12 | 18-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 31093.99 | 289144.14 | 14-MAY-05:00 | 2356626.12 | 18-AUG-15:10 |
ElectricityNet:Plant | 31093.99 | 289144.14 | 14-MAY-05:00 | 2356626.12 | 18-AUG-15:10 |
Cogeneration:ElectricityNet | 31093.99 | 289144.14 | 14-MAY-05:00 | 2356626.12 | 18-AUG-15:10 |
General:Cogeneration:ElectricityNet | 31093.99 | 289144.14 | 14-MAY-05:00 | 2356626.12 | 18-AUG-15:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1904.93 | 226.08 | 30-JAN-07:20 | 413679.13 | 20-JUL-13:40 |
General:Cooling:Electricity | 1904.93 | 226.08 | 30-JAN-07:20 | 413679.13 | 20-JUL-13:40 |
Fans:Electricity | 2690.85 | 25191.23 | 02-JAN-23:30 | 288370.61 | 09-AUG-15:20 |
General:Fans:Electricity | 2690.85 | 25191.23 | 02-JAN-23:30 | 288370.61 | 09-AUG-15:20 |
ExteriorLights:Electricity | 1006.46 | 0.00 | 01-JAN-08:00 | 64082.80 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 1006.46 | 0.00 | 01-JAN-08:00 | 64082.80 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.31 | 1944.00 | 01-JAN-00:10 | 1944.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1007.27 | 0.00 | 11-JAN-13:10 | 100000.00 | 22-MAR-12:50 |
General:Humidifier:Electricity | 1007.27 | 0.00 | 11-JAN-13:10 | 100000.00 | 22-MAR-12:50 |
Electricity:Plant | 3049.51 | 0.00 | 03-JAN-00:10 | 575797.00 | 20-JUL-13:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 459.97 | 0.00 | 01-JAN-00:10 | 56298.68 | 14-FEB-12:20 |
Water Heater:WaterSystems:Electricity | 459.97 | 0.00 | 01-JAN-00:10 | 56298.68 | 14-FEB-12:20 |
HeatRejection:Electricity | 158.44 | 0.00 | 01-JAN-00:10 | 54364.00 | 14-MAR-12:40 |
General:HeatRejection:Electricity | 158.44 | 0.00 | 01-JAN-00:10 | 54364.00 | 14-MAR-12:40 |
Pumps:Electricity | 955.83 | 0.00 | 03-JAN-00:10 | 95351.54 | 06-JUL-15:00 |
General:Pumps:Electricity | 955.83 | 0.00 | 03-JAN-00:10 | 95351.54 | 06-JUL-15:00 |
WIRED_LTG_ELECTRICITY | 157.66 | 0.00 | 01-JAN-00:10 | 13766.21 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4323.05 | 0.00 | 01-JAN-00:40 | 2269990.72 | 02-JAN-05:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 4323.05 | 0.00 | 01-JAN-00:40 | 2269990.72 | 02-JAN-05:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 4323.05 | 0.00 | 01-JAN-00:40 | 2269990.72 | 02-JAN-05:10 |
Boiler:Heating:NaturalGas | 4323.05 | 0.00 | 01-JAN-00:40 | 2269990.72 | 02-JAN-05:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 8290.07 | 0.00 | 01-JAN-00:20 | 2502332.35 | 20-JUL-13:40 |
PlantLoopCoolingDemand:HVAC | 8290.07 | 0.00 | 01-JAN-00:20 | 2502332.35 | 20-JUL-13:40 |
CoolingCoils:PlantLoopCoolingDemand | 8290.07 | 0.00 | 01-JAN-00:20 | 2502332.35 | 20-JUL-13:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 8699.52 | 0.00 | 11-MAR-01:10 | 0.00 | 17-AUG-13:00 |
Water:HVAC | 374.70 | 0.00 | 11-JAN-13:10 | 0.00 | 22-MAR-12:50 |
Humidifier:Water | 374.70 | 0.00 | 11-JAN-13:10 | 0.00 | 22-MAR-12:50 |
General:Humidifier:Water | 374.70 | 0.00 | 11-JAN-13:10 | 0.00 | 22-MAR-12:50 |
MainsWater:Facility | 8699.52 | 0.00 | 11-MAR-01:10 | 0.00 | 17-AUG-13:00 |
MainsWater:HVAC | 374.70 | 0.00 | 11-JAN-13:10 | 0.00 | 22-MAR-12:50 |
Humidifier:MainsWater | 374.70 | 0.00 | 11-JAN-13:10 | 0.00 | 22-MAR-12:50 |
General:Humidifier:MainsWater | 374.70 | 0.00 | 11-JAN-13:10 | 0.00 | 22-MAR-12:50 |
Water:Plant | 8324.81 | 0.00 | 01-JAN-00:10 | 0.00 | 17-AUG-13:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 11-APR-11:40 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 11-APR-11:40 |
MainsWater:Plant | 8324.81 | 0.00 | 01-JAN-00:10 | 0.00 | 17-AUG-13:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 11-APR-11:40 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 11-APR-11:40 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 6044.65 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-13:40 |
General:HeatRejection:Water | 6044.65 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-13:40 |
HeatRejection:MainsWater | 6044.65 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-13:40 |
General:HeatRejection:MainsWater | 6044.65 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-13:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 64058.74 | 100052.12 | 01-JAN-06:00 | 12224559.59 | 20-JUL-13:40 |
EnergyTransfer:Building | 20213.12 | 87518.42 | 10-JAN-22:40 | 1884768.91 | 09-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 669.86 | 0.00 | 01-JAN-00:10 | 87773.58 | 05-SEP-09:20 |
Heating:EnergyTransfer | 1204.31 | 0.00 | 01-FEB-01:30 | 1464174.17 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.61 | 0.00 | 01-JAN-00:10 | 6925.63 | 17-JUN-16:10 |
General:Heating:EnergyTransfer | 1204.31 | 0.00 | 01-FEB-01:30 | 1464174.17 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.61 | 0.00 | 01-JAN-00:10 | 6925.63 | 17-JUN-16:10 |
Cooling:EnergyTransfer | 19008.81 | 83151.05 | 30-JAN-06:00 | 1884768.91 | 09-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 669.25 | 0.00 | 01-JAN-00:10 | 87773.58 | 05-SEP-09:20 |
General:Cooling:EnergyTransfer | 19008.81 | 83151.05 | 30-JAN-06:00 | 1884768.91 | 09-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 669.25 | 0.00 | 01-JAN-00:10 | 87773.58 | 05-SEP-09:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 605.12 | 0.00 | 01-JAN-00:10 | 57216.70 | 14-AUG-16:00 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 605.12 | 0.00 | 01-JAN-00:10 | 57216.70 | 14-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 605.12 | 0.00 | 01-JAN-00:10 | 57216.70 | 14-AUG-16:00 |
EnergyTransfer:Zone:CORE_MID | 4722.09 | 0.00 | 01-JAN-00:40 | 496569.87 | 21-JUL-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 12.72 | 0.00 | 01-JAN-00:10 | 481489.91 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 12.72 | 0.00 | 01-JAN-00:10 | 481489.91 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4709.37 | 0.00 | 01-JAN-00:40 | 496569.87 | 21-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4709.37 | 0.00 | 01-JAN-00:40 | 496569.87 | 21-JUL-16:00 |
EnergyTransfer:Zone:CORE_TOP | 435.27 | 0.00 | 01-JAN-00:40 | 97288.61 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 29.32 | 0.00 | 01-JAN-00:40 | 97288.61 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 29.32 | 0.00 | 01-JAN-00:40 | 97288.61 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 405.95 | 0.00 | 01-JAN-00:20 | 62362.75 | 21-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 405.95 | 0.00 | 01-JAN-00:20 | 62362.75 | 21-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 77.66 | 0.00 | 01-JAN-00:10 | 14649.19 | 07-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 4.94 | 0.00 | 01-JAN-00:10 | 14649.19 | 07-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 4.94 | 0.00 | 01-JAN-00:10 | 14649.19 | 07-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 72.72 | 0.00 | 01-JAN-00:10 | 12584.35 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 72.72 | 0.00 | 01-JAN-00:10 | 12584.35 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 76.04 | 0.00 | 01-JAN-00:10 | 15918.85 | 13-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 3.63 | 0.00 | 01-JAN-00:10 | 10817.83 | 07-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 3.63 | 0.00 | 01-JAN-00:10 | 10817.83 | 07-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 72.41 | 0.00 | 01-JAN-00:10 | 15918.85 | 13-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 72.41 | 0.00 | 01-JAN-00:10 | 15918.85 | 13-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 114.07 | 0.00 | 01-JAN-00:10 | 24968.26 | 11-OCT-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 6.39 | 0.00 | 01-JAN-00:10 | 17576.24 | 07-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 6.39 | 0.00 | 01-JAN-00:10 | 17576.24 | 07-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 107.69 | 0.00 | 01-JAN-00:10 | 24968.26 | 11-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 107.69 | 0.00 | 01-JAN-00:10 | 24968.26 | 11-OCT-12:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 103.42 | 0.00 | 01-JAN-00:10 | 20344.94 | 17-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.15 | 0.00 | 01-JAN-00:10 | 8183.07 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.15 | 0.00 | 01-JAN-00:10 | 8183.07 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 102.28 | 0.00 | 01-JAN-00:10 | 20344.94 | 17-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 102.28 | 0.00 | 01-JAN-00:10 | 20344.94 | 17-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 856.56 | 0.00 | 01-JAN-00:40 | 260564.93 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 263.40 | 0.00 | 01-JAN-00:40 | 260564.93 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 263.40 | 0.00 | 01-JAN-00:40 | 260564.93 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 593.16 | 0.00 | 01-JAN-00:20 | 121206.41 | 21-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 593.16 | 0.00 | 01-JAN-00:20 | 121206.41 | 21-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 717.01 | 0.00 | 01-JAN-00:40 | 181189.79 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 151.45 | 0.00 | 01-JAN-00:40 | 181189.79 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 151.45 | 0.00 | 01-JAN-00:40 | 181189.79 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 565.57 | 0.00 | 01-JAN-00:20 | 164533.80 | 13-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 565.57 | 0.00 | 01-JAN-00:20 | 164533.80 | 13-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1124.95 | 0.00 | 01-JAN-00:40 | 266978.78 | 31-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 187.53 | 0.00 | 01-JAN-00:40 | 259425.01 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 187.53 | 0.00 | 01-JAN-00:40 | 259425.01 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 937.42 | 0.00 | 01-JAN-00:20 | 266978.78 | 31-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 937.42 | 0.00 | 01-JAN-00:20 | 266978.78 | 31-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 777.11 | 0.00 | 01-JAN-00:40 | 178247.35 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 133.40 | 0.00 | 01-JAN-00:40 | 177474.41 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 133.40 | 0.00 | 01-JAN-00:40 | 177474.41 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 643.71 | 0.00 | 01-JAN-00:20 | 178247.35 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 643.71 | 0.00 | 01-JAN-00:20 | 178247.35 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 115.91 | 0.00 | 01-JAN-00:40 | 32314.30 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 56.94 | 0.00 | 01-JAN-00:40 | 32314.30 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 56.94 | 0.00 | 01-JAN-00:40 | 32314.30 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 58.97 | 0.00 | 01-JAN-00:20 | 13714.96 | 21-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 58.97 | 0.00 | 01-JAN-00:20 | 13714.96 | 21-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 88.75 | 0.00 | 01-JAN-00:40 | 21645.02 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.58 | 0.00 | 01-JAN-00:40 | 21645.02 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.58 | 0.00 | 01-JAN-00:40 | 21645.02 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 55.17 | 0.00 | 01-JAN-00:20 | 16199.60 | 12-JUN-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 55.17 | 0.00 | 01-JAN-00:20 | 16199.60 | 12-JUN-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 134.68 | 0.00 | 01-JAN-00:40 | 32569.86 | 13-FEB-05:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 44.16 | 0.00 | 01-JAN-00:40 | 32569.86 | 13-FEB-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 44.16 | 0.00 | 01-JAN-00:40 | 32569.86 | 13-FEB-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 90.52 | 0.00 | 01-JAN-00:20 | 26124.21 | 11-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 90.52 | 0.00 | 01-JAN-00:20 | 26124.21 | 11-OCT-12:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 89.03 | 0.00 | 01-JAN-00:40 | 21209.01 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 27.90 | 0.00 | 01-JAN-00:40 | 21209.01 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 27.90 | 0.00 | 01-JAN-00:40 | 21209.01 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 61.12 | 0.00 | 01-JAN-00:20 | 18745.14 | 17-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 61.12 | 0.00 | 01-JAN-00:20 | 18745.14 | 17-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 76.37 | 0.00 | 01-JAN-00:10 | 9884.30 | 09-AUG-15:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.60 | 0.00 | 01-JAN-00:10 | 3495.81 | 30-JAN-12:00 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.60 | 0.00 | 01-JAN-00:10 | 3495.81 | 30-JAN-12:00 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 74.76 | 0.00 | 01-JAN-00:10 | 9884.30 | 09-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 74.76 | 0.00 | 01-JAN-00:10 | 9884.30 | 09-AUG-15:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 678.12 | 0.00 | 01-JAN-00:40 | 201362.35 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 124.38 | 0.00 | 01-JAN-00:40 | 201362.35 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 124.38 | 0.00 | 01-JAN-00:40 | 201362.35 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 553.74 | 0.00 | 01-JAN-00:10 | 96943.59 | 05-MAR-05:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 553.74 | 0.00 | 01-JAN-00:10 | 96943.59 | 05-MAR-05:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 200.11 | 0.00 | 01-JAN-00:40 | 53282.83 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 107.31 | 0.00 | 01-JAN-00:40 | 53282.83 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 107.31 | 0.00 | 01-JAN-00:40 | 53282.83 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 92.80 | 0.00 | 01-JAN-00:10 | 33461.14 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 92.80 | 0.00 | 01-JAN-00:10 | 33461.14 | 21-JUL-13:30 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 131.77 | 6.09 | 09-JAN-01:30 | 8419.43 | 02-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.01 | 0.00 | 01-JAN-00:10 | 391.33 | 29-JAN-21:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.01 | 0.00 | 01-JAN-00:10 | 391.33 | 29-JAN-21:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 131.76 | 0.00 | 09-JAN-01:20 | 8419.43 | 02-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 131.76 | 0.00 | 09-JAN-01:20 | 8419.43 | 02-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1151.42 | 5.12 | 24-JAN-22:20 | 81014.85 | 02-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 9.98 | 0.00 | 02-JAN-13:10 | 12763.51 | 29-JAN-18:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 9.98 | 0.00 | 02-JAN-13:10 | 12763.51 | 29-JAN-18:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1141.44 | 0.00 | 01-JAN-00:10 | 81014.85 | 02-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1141.44 | 0.00 | 01-JAN-00:10 | 81014.85 | 02-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 103.01 | 3.97 | 31-JAN-12:00 | 8192.73 | 02-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 2.33 | 0.00 | 02-JAN-12:40 | 1354.63 | 31-JAN-00:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 2.33 | 0.00 | 02-JAN-12:40 | 1354.63 | 31-JAN-00:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 100.68 | 0.00 | 01-JAN-00:10 | 8192.73 | 02-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 100.68 | 0.00 | 01-JAN-00:10 | 8192.73 | 02-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7164.79 | 76541.24 | 30-APR-23:10 | 391083.02 | 20-APR-12:30 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 1.58 | 0.00 | 01-JAN-00:10 | 3837.25 | 05-OCT-04:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 1.58 | 0.00 | 01-JAN-00:10 | 3837.25 | 05-OCT-04:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7163.21 | 76541.24 | 30-APR-23:10 | 391083.02 | 20-APR-12:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7163.21 | 76541.24 | 30-APR-23:10 | 391083.02 | 20-APR-12:30 |
PlantLoopHeatingDemand:Facility | 3443.49 | 0.00 | 01-JAN-00:40 | 1709372.61 | 11-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 454.52 | 0.00 | 01-JAN-00:10 | 56067.89 | 15-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 454.52 | 0.00 | 01-JAN-00:10 | 56067.89 | 15-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 454.52 | 0.00 | 01-JAN-00:10 | 56067.89 | 15-FEB-12:10 |
EnergyTransfer:HVAC | 13070.37 | 1173.00 | 30-JAN-03:40 | 2591548.00 | 20-JUL-13:40 |
HeatingCoils:EnergyTransfer | 2988.97 | 0.00 | 01-JAN-00:40 | 1691851.51 | 11-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 2988.97 | 0.00 | 01-JAN-00:40 | 1691851.51 | 11-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 2988.97 | 0.00 | 01-JAN-00:40 | 1691851.51 | 11-DEC-07:10 |
CoolingCoils:EnergyTransfer | 10081.40 | 660.37 | 30-JAN-07:10 | 2591548.00 | 20-JUL-13:40 |
EnergyTransfer:Plant | 30775.25 | 0.00 | 03-JAN-00:10 | 7957078.51 | 20-JUL-13:40 |
LoopToLoop:EnergyTransfer | 8548.19 | 0.00 | 01-JAN-00:20 | 2501908.91 | 20-JUL-13:40 |
WaterSystems:EnergyTransfer | 454.52 | 0.00 | 01-JAN-00:10 | 56067.89 | 15-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 454.52 | 0.00 | 01-JAN-00:10 | 56067.89 | 15-FEB-12:10 |
Boilers:EnergyTransfer | 2973.35 | 0.00 | 01-JAN-00:40 | 1771979.20 | 02-JAN-05:10 |
Chillers:EnergyTransfer | 8661.96 | 0.00 | 01-JAN-00:20 | 2519002.41 | 20-JUL-13:40 |
HeatRejection:EnergyTransfer | 10137.23 | 0.00 | 01-JAN-00:20 | 2909559.87 | 20-JUL-13:40 |
General:HeatRejection:EnergyTransfer | 10137.23 | 0.00 | 01-JAN-00:20 | 2909559.87 | 20-JUL-13:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.609 | -669.241 | 0.000 | 0.000 | 94.702 | 333.789 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -184.257 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -605.115 | 0.000 | 0.000 | 83.761 | 299.766 | 289.614 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -68.027 |
CORE_MID | 0.000 | 0.000 | 12.719 | -4709.358 | 0.000 | 0.000 | 855.725 | 2997.664 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -2052.877 |
CORE_TOP | 0.000 | 0.000 | 29.323 | -405.946 | 0.000 | 0.000 | 89.704 | 299.766 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -302.460 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 4.943 | -72.720 | 0.000 | 0.000 | 11.265 | 37.639 | 36.365 | 24.941 | 0.000 | 0.058 | 70.730 | 0.000 | -103.037 | 0.000 | -10.183 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 3.625 | -72.410 | 0.000 | 0.000 | 7.368 | 24.256 | 23.435 | 51.487 | 0.000 | 0.051 | 31.141 | 0.000 | -62.300 | 0.000 | -6.654 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 6.385 | -107.687 | 0.000 | 0.000 | 11.247 | 37.639 | 36.366 | 95.086 | 0.000 | 0.057 | 21.997 | 0.000 | -91.036 | 0.000 | -10.056 | 0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 1.146 | -102.278 | 0.000 | 0.000 | 7.326 | 24.256 | 23.435 | 50.816 | 0.000 | 0.038 | 73.154 | 0.000 | -70.698 | 0.000 | -7.195 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 263.399 | -593.161 | 0.000 | 0.000 | 117.754 | 376.387 | 363.654 | 265.303 | 0.000 | 1.713 | 363.357 | 0.000 | -944.920 | 0.000 | -213.485 | -0.039 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 151.448 | -565.563 | 0.000 | 0.000 | 54.978 | 242.558 | 234.352 | 511.722 | 0.000 | 1.016 | 102.587 | 0.000 | -588.588 | 0.000 | -144.510 | -0.030 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 187.531 | -937.412 | 0.000 | 0.000 | 114.211 | 376.395 | 363.660 | 942.601 | 0.000 | 1.253 | 61.378 | 0.000 | -886.161 | 0.000 | -223.455 | -0.014 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 133.403 | -643.702 | 0.000 | 0.000 | 76.125 | 242.558 | 234.351 | 520.327 | 0.000 | 0.995 | 215.982 | 0.000 | -632.282 | 0.000 | -147.757 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 56.940 | -58.965 | 0.000 | 0.000 | 12.000 | 37.639 | 36.365 | 27.417 | 0.000 | 0.227 | 2.122 | 0.000 | -88.568 | 0.000 | -25.176 | -0.002 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 33.581 | -55.169 | 0.000 | 0.000 | 7.550 | 24.256 | 23.435 | 51.868 | 0.000 | 0.115 | 0.000 | 0.000 | -55.348 | 0.000 | -17.090 | -13.198 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 44.162 | -90.521 | 0.000 | 0.000 | 11.673 | 37.639 | 36.366 | 95.399 | 0.000 | 0.165 | 0.000 | 0.000 | -82.520 | 0.000 | -26.119 | -26.245 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 27.904 | -61.124 | 0.000 | 0.000 | 7.680 | 24.256 | 23.435 | 52.068 | 0.000 | 0.119 | 3.133 | 0.000 | -59.915 | 0.000 | -17.557 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.007 | -131.765 | 0.000 | 0.000 | 0.950 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -31.420 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 9.980 | -1141.437 | 0.000 | 0.000 | 9.503 | 83.466 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -500.318 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 2.329 | -100.684 | 0.000 | 0.000 | 0.951 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -64.824 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 1.580 | -7163.069 | 0.000 | 0.000 | 22.767 | 94.114 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -450.250 |
GROUNDFLOOR_PLENUM | 1.601 | -74.765 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.093 | 95.668 | 0.000 | 0.000 | 0.000 | -22.597 | 0.000 |
MIDFLOOR_PLENUM | 124.385 | -553.732 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.865 | 807.625 | 0.000 | 0.000 | 0.000 | -380.143 | -0.006 |
TOPFLOOR_PLENUM | 107.308 | -92.803 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.087 | 23.408 | 0.000 | 0.000 | 0.000 | -38.000 | -0.012 |
Total Facility | 233.293 | -721.300 | 971.015 | -18287.325 | 0.000 | 0.000 | 1597.241 | 5610.736 | 14676.396 | 2689.034 | 0.000 | 7.852 | 1872.283 | 0.000 | -3665.371 | 0.000 | -1289.977 | -3693.979 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 02-OCT-04:11 | 0.00 | 0.00 | 0.00 | -139406.54 | 0.00 | 0.00 | 0.00 | 3238.31 | 13457.54 | 0.00 | 0.00 | 0.00 | 122710.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 21-AUG-04:11 | 0.00 | 0.00 | 0.00 | -118884.25 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.65 | 0.00 | 0.00 | 0.00 | 110038.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 09-AUG-04:11 | 0.00 | 0.00 | 0.00 | -1066877.98 | 0.00 | 0.00 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 978419.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 17-JUL-03:01 | 0.00 | 0.00 | 0.00 | -114800.05 | 0.00 | 0.00 | 0.00 | 1454.11 | 5937.62 | 0.00 | 0.00 | 0.00 | 107408.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 17-JUN-05:01 | 0.00 | 0.00 | 0.00 | -15688.33 | 0.00 | 0.00 | 111.38 | 365.16 | 960.25 | 0.00 | 0.00 | 0.00 | 14783.19 | 0.00 | -495.30 | 0.00 | -36.34 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUL-07:01 | 0.00 | 0.00 | 0.00 | -29133.27 | 0.00 | 0.00 | 23.99 | 117.66 | 464.11 | 19120.36 | 0.00 | 0.00 | 9588.74 | 0.00 | -0.00 | 0.00 | -181.60 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-SEP-13:02 | 0.00 | 0.00 | 0.00 | -35399.35 | 0.00 | 0.00 | 33.47 | 182.58 | 720.19 | 25970.48 | 0.00 | 0.00 | 8854.41 | 0.00 | -0.00 | 0.00 | -361.79 | 0.00 |
PERIMETER_BOT_ZN_4 | 11-JUN-16:41 | 0.00 | 0.00 | 0.00 | -39277.19 | 0.00 | 0.00 | 16.81 | 117.66 | 464.11 | 19444.41 | 0.00 | 0.00 | 19352.63 | 0.00 | -0.00 | 0.00 | -118.42 | 0.00 |
PERIMETER_MID_ZN_3 | 21-JUL-03:01 | 0.00 | 0.00 | 0.00 | -177955.06 | 0.00 | 0.00 | 0.00 | 1825.79 | 7455.61 | 5007.91 | 0.00 | 3606.96 | 160058.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-09:22 | 0.00 | 0.00 | 0.00 | -302510.84 | 0.00 | 0.00 | 175.82 | 1176.61 | 4641.14 | 180159.57 | 0.00 | 0.00 | 119313.63 | 0.00 | -0.00 | 0.00 | -2955.92 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-13:32 | 0.00 | 0.00 | 0.00 | -356289.17 | 0.00 | 0.00 | 343.86 | 1825.83 | 7201.95 | 216633.26 | 0.00 | 0.00 | 138993.12 | 0.00 | -0.00 | 0.00 | -8708.85 | 0.00 |
PERIMETER_MID_ZN_4 | 02-JUL-17:21 | 0.00 | 0.00 | 0.00 | -338197.18 | 0.00 | 0.00 | 0.00 | 1176.61 | 3603.49 | 207701.18 | 0.00 | 0.00 | 127804.80 | 0.00 | -0.00 | 0.00 | -2088.89 | 0.00 |
PERIMETER_TOP_ZN_3 | 21-JUL-03:01 | 0.00 | 0.00 | 0.00 | -25617.23 | 0.00 | 0.00 | 0.00 | 182.58 | 745.56 | 454.37 | 0.00 | 470.36 | 23764.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 11-JUN-10:02 | 0.00 | 0.00 | 0.00 | -30570.02 | 0.00 | 0.00 | 22.06 | 117.66 | 464.11 | 13024.27 | 0.00 | 0.00 | 17315.12 | 0.00 | -0.00 | 0.00 | -373.21 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-14:32 | 0.00 | 0.00 | 0.00 | -45328.64 | 0.00 | 0.00 | 34.07 | 182.58 | 720.19 | 17918.93 | 0.00 | 0.00 | 27338.70 | 0.00 | -0.00 | 0.00 | -865.84 | 0.00 |
PERIMETER_TOP_ZN_4 | 11-JUN-16:41 | 0.00 | 0.00 | 0.00 | -39504.71 | 0.00 | 0.00 | 16.83 | 117.66 | 464.11 | 19099.41 | 0.00 | 0.00 | 20170.93 | 0.00 | -0.00 | 0.00 | -364.23 | 0.00 |
DATACENTER_BOT_ZN_6 | 02-AUG-18:40 | 0.00 | 0.00 | 0.00 | -8419.29 | 0.00 | 0.00 | 10.62 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 371.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 02-AUG-18:40 | 0.00 | 0.00 | 0.00 | -81013.45 | 0.00 | 0.00 | 106.16 | 2429.28 | 77944.22 | 0.00 | 0.00 | 0.00 | 533.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 02-AUG-18:40 | 0.00 | 0.00 | 0.00 | -8192.59 | 0.00 | 0.00 | 10.62 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 144.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | -517875.27 | 0.00 | 0.00 | 0.00 | 456.53 | 284724.39 | 0.00 | 0.00 | 0.00 | 232694.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 06-FEB-04:01 | 0.00 | -14584.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18692.97 | 0.00 | -0.00 | 0.00 | -4108.60 | 0.00 |
MIDFLOOR_PLENUM | 04-MAR-04:01 | 0.00 | -204824.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232816.02 | 0.00 | -0.00 | 0.00 | -27991.83 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-13:30 | 0.00 | -33460.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.96 | 33267.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-JUL-05:01 | 0.00 | 16897.59 | 0.00 | -2170474.23 | 0.00 | 0.00 | 16434.29 | 54433.43 | 497997.76 | 942.24 | 0.00 | 0.00 | 1659054.63 | 0.00 | -69853.96 | 0.00 | -5431.76 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 17-JUN-16:03 | 0.00 | 0.00 | 7679.40 | 0.00 | 0.00 | 0.00 | 520.14 | 1619.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23276.24 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 585541.97 | 0.00 | 0.00 | 0.00 | 0.00 | 14541.15 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -659459.35 |
CORE_TOP | 26-DEC-04:11 | 0.00 | 0.00 | 114738.43 | 0.00 | 0.00 | 0.00 | 0.00 | 1454.11 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -122130.17 |
PERIMETER_BOT_ZN_3 | 06-FEB-04:01 | 0.00 | 0.00 | 19667.21 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9637.31 | 0.00 | -1815.01 | -9143.03 |
PERIMETER_BOT_ZN_2 | 06-FEB-04:01 | 0.00 | 0.00 | 19034.59 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6167.07 | 0.00 | -1217.85 | -12247.79 |
PERIMETER_BOT_ZN_1 | 06-FEB-04:01 | 0.00 | 0.00 | 26920.56 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9403.27 | 0.00 | -1784.46 | -16660.98 |
PERIMETER_BOT_ZN_4 | 06-FEB-04:01 | 0.00 | 0.00 | 18003.36 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6666.74 | 0.00 | -1260.29 | -10674.45 |
PERIMETER_MID_ZN_3 | 06-FEB-00:31 | 0.00 | 0.00 | 316287.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1825.79 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -84964.18 | 0.00 | -48617.18 | -191987.18 |
PERIMETER_MID_ZN_2 | 06-FEB-01:11 | 0.00 | 0.00 | 257890.31 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.61 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -54575.44 | 0.00 | -31913.59 | -177382.56 |
PERIMETER_MID_ZN_1 | 06-FEB-03:11 | 0.00 | 0.00 | 314993.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1825.83 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -89608.64 | 0.00 | -44737.57 | -189928.90 |
PERIMETER_MID_ZN_4 | 06-FEB-03:11 | 0.00 | 0.00 | 262509.22 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.61 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -60244.12 | 0.00 | -30297.33 | -177949.02 |
PERIMETER_TOP_ZN_3 | 06-FEB-02:51 | 0.00 | 0.00 | 42971.45 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8405.77 | 0.00 | -5706.00 | -29787.82 |
PERIMETER_TOP_ZN_2 | 06-FEB-02:51 | 0.00 | 0.00 | 28977.61 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5324.56 | 0.00 | -3813.29 | -20437.89 |
PERIMETER_TOP_ZN_1 | 06-FEB-02:51 | 0.00 | 0.00 | 42836.07 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8447.32 | 0.00 | -5725.14 | -29591.77 |
PERIMETER_TOP_ZN_4 | 06-FEB-02:51 | 0.00 | 0.00 | 32252.56 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5739.34 | 0.00 | -3892.06 | -23219.28 |
DATACENTER_BOT_ZN_6 | 29-JAN-21:08 | 0.00 | 0.00 | 981.51 | 0.00 | 0.00 | 0.00 | 0.00 | 40.49 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2970.60 |
DATACENTER_MID_ZN_6 | 29-JAN-18:10 | 0.00 | 0.00 | 12763.53 | 0.00 | 0.00 | 0.00 | 0.00 | 404.88 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -32654.46 |
DATACENTER_TOP_ZN_6 | 24-JAN-00:15 | 0.00 | 0.00 | 1358.21 | 0.00 | 0.00 | 0.00 | 0.00 | 40.49 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3347.30 |
DATACENTER_BASEMENT_ZN_6 | 05-OCT-03:51 | 0.00 | 0.00 | 38374.04 | 0.00 | 0.00 | 0.00 | 0.00 | 456.53 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -228646.84 |
GROUNDFLOOR_PLENUM | 27-NOV-05:11 | 12436.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -867.21 | -11569.54 |
MIDFLOOR_PLENUM | 02-JAN-06:13 | 231111.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5464.07 | -225647.45 |
TOPFLOOR_PLENUM | 06-FEB-05:06 | 55425.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7828.65 | -47596.94 |
Total Facility | 30-JAN-05:01 | -115023.55 | 99041.41 | 1932135.26 | -99041.41 | 0.00 | 0.00 | 0.00 | 54433.43 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -299646.22 | 0.00 | -136595.28 | -1667728.87 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 14.5200 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 12.2297 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 147.2639 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 114.6286 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 16.8994 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 14.0788 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 7.0913 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 7.0913 | 0.1692 | 1.0000 | Not calculated | 1.2002 | 0.1692 | ||
AIRLOOP DATACENTER BASEMENT | 32.1458 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 32.1460 | 0.0105 | 1.0000 | Not calculated | 0.3384 | 0.0105 | ||
AIRLOOP DATACENTER BOT | 0.7612 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7612 | 0.0205 | 1.0000 | Not calculated | 0.0156 | 0.0205 | ||
AIRLOOP DATACENTER MID | 7.3133 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 7.3133 | 0.0214 | 1.0000 | Not calculated | 0.1563 | 0.0214 | ||
AIRLOOP DATACENTER TOP | 0.7531 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7531 | 0.0208 | 1.0000 | Not calculated | 0.0156 | 0.0208 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 7.2600 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.3560 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 73.6319 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 44.1792 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 8.4497 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0698 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 2.1274 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 2.1274 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.5641 | ||
AIRLOOP DATACENTER BASEMENT | 16.0729 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 16.0729 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0211 | ||
AIRLOOP DATACENTER BOT | 0.7612 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7612 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0205 | ||
AIRLOOP DATACENTER MID | 7.3133 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 7.3133 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0214 | ||
AIRLOOP DATACENTER TOP | 0.7531 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7531 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0208 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 7.0913 | 7.0913 | 2.1274 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.5369 | 7.5369 | 2.2611 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 71.5595 | 71.5595 | 21.4678 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.8986 | 7.8986 | 2.3696 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3801 | 1.3801 | 0.4140 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6462 | 1.6462 | 0.4939 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9470 | 1.9470 | 0.5841 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0097 | 2.0097 | 0.6029 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 19.8905 | 19.8905 | 5.9671 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 17.3754 | 17.3754 | 5.2126 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 19.8906 | 19.8906 | 5.9672 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.5479 | 18.5479 | 5.5644 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6104 | 2.6104 | 0.7831 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7631 | 1.7631 | 0.5289 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6105 | 2.6105 | 0.7831 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0169 | 2.0169 | 0.6051 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7612 | 0.7612 | 0.7612 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.3133 | 7.3133 | 7.3133 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7531 | 0.7531 | 0.7531 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 32.1458 | 32.1458 | 16.0729 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 14.5200 | 12.2297 | 14.5200 | 4.3560 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 147.2639 | 114.6286 | 147.2639 | 44.1792 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 16.8994 | 14.0788 | 16.8994 | 5.0698 | 0.0000 | 1.0000 |
CAV_BAS | 7.0913 | 7.0913 | 7.0913 | 2.1274 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 32.1458 | 32.1460 | 32.1458 | 16.0729 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.7612 | 0.7612 | 0.7612 | 0.7612 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 7.3133 | 7.3133 | 7.3133 | 7.3133 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.7531 | 0.7531 | 0.7531 | 0.7531 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 2.1274 | 2.1274 | 2.1274 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7685 | 3.7685 | 2.2611 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 35.7797 | 35.7797 | 21.4678 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.9493 | 3.9493 | 2.3696 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6901 | 0.6901 | 0.4140 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8231 | 0.8231 | 0.4939 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9735 | 0.9735 | 0.5841 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0048 | 1.0048 | 0.6029 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.9452 | 9.9452 | 5.9671 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.6877 | 8.6877 | 5.2126 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.9453 | 9.9453 | 5.9672 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.2739 | 9.2739 | 5.5644 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3052 | 1.3052 | 0.7831 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8815 | 0.8815 | 0.5289 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3052 | 1.3052 | 0.7831 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0084 | 1.0084 | 0.6051 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7612 | 0.7612 | 0.7612 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.3133 | 7.3133 | 7.3133 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7531 | 0.7531 | 0.7531 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 16.0729 | 16.0729 | 16.0729 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 7.2600 | 4.3560 | 4.3560 | 4.3560 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 73.6319 | 44.1792 | 44.1792 | 44.1792 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 8.4497 | 5.0698 | 5.0698 | 5.0698 | 0.0000 | 1.0000 |
CAV_BAS | 2.1274 | 2.1274 | 2.1274 | 2.1274 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 16.0729 | 16.0729 | 16.0729 | 16.0729 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.7612 | 0.7612 | 0.7612 | 0.7612 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 7.3133 | 7.3133 | 7.3133 | 7.3133 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.7531 | 0.7531 | 0.7531 | 0.7531 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 68.50 |
Number of hours cooling loads not met | 67.50 |
Number of hours not met | 136.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 4323.05 | 2269990.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1904.93 | 413679.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 5610.74 | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 1006.46 | 64082.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 56.04 | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.31 | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2690.85 | 288370.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 955.83 | 95351.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 158.44 | 54364.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1007.27 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 459.97 | 56298.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 31093.99 |
Natural Gas | 0.00 | 4323.05 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 35417.04 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 121.13 |
Space Heating | 0.00 |
Space Cooling | 41.12 |
Fans (All) | 58.09 |
Service Water Heating | 9.93 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 671.28 |
Subtotal | 671.28 |
Natural Gas [MJ/m2] | |
Space Heating | 93.33 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 93.33 |
Subtotal | 93.33 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.84 |
Space Heating | 12.21 |
Space Cooling | 5.38 |
Fans (All) | 7.60 |
Service Water Heating | 1.30 |
Receptacle Equipment | 41.44 |
Miscellaneous | 16.24 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
LTG_SCH_DATACENTER | 2939. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8543.00 | 217.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8739.33 | 20.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8743.83 | 16.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8739.00 | 21.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8426.50 | 333.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8734.17 | 25.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8734.50 | 25.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8673.50 | 86.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8733.83 | 26.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8741.33 | 18.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8679.33 | 80.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6333.33 | 2426.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6320.00 | 2440.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6295.33 | 2464.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6932.83 | 1827.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8679.17 | 80.83 | 0.00 | 0.00 | 0.00 |
Min | 6295.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2464.67 | 0.00 | 0.00 | 0.00 |
Average | 8319.81 | 440.19 | 0.00 | 0.00 | 0.00 |
Sum | 191355.67 | 10124.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368161.00 | 455.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330812.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330808.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1368.33 | 899.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1364.00 | 904.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1362.50 | 905.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 79367.50 | 24027.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368161.00 | 24027.50 | 0.00 | 0.00 | 0.00 |
Average | 79152.41 | 1182.51 | 0.00 | 0.00 | 0.00 |
Sum | 1820505.33 | 27197.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8316.00 | 444.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8186.17 | 573.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8282.50 | 477.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8349.67 | 410.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8394.67 | 365.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8585.00 | 175.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8462.83 | 297.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8155.33 | 604.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8494.83 | 265.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8454.50 | 305.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8393.67 | 366.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8318.00 | 442.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8525.33 | 234.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8451.50 | 308.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8448.83 | 311.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8347.83 | 412.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7551.83 | 1208.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7513.00 | 1247.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7468.67 | 1291.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6965.67 | 1794.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8248.67 | 511.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8432.17 | 327.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8051.17 | 708.83 | 0.00 | 0.00 | 0.00 |
Min | 6965.67 | 175.00 | 0.00 | 0.00 | 0.00 |
Max | 8585.00 | 1794.33 | 0.00 | 0.00 | 0.00 |
Average | 8191.21 | 568.79 | 0.00 | 0.00 | 0.00 |
Sum | 188397.83 | 13082.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 366903.50 | 1712.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330012.00 | 801.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330121.00 | 692.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330269.00 | 544.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38924.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1637.17 | 630.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1626.67 | 641.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1605.00 | 663.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 80026.00 | 23369.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 366903.50 | 23369.00 | 0.00 | 0.00 | 0.00 |
Average | 79071.70 | 1263.21 | 0.00 | 0.00 | 0.00 |
Sum | 1818649.17 | 29053.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:25
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.495355E+11 | 129115.16 | 17-JAN-06:01 | 7.20 | 2.95 | 0.521633E+10 | 7493.56 | 17-JAN-10:39 | 7.23 | 4.26 |
February | 0.436329E+11 | 125735.94 | 18-FEB-06:01 | -1.7 | -1.7 | 0.465780E+10 | 7499.21 | 22-FEB-14:09 | 9.60 | 4.38 |
March | 0.500429E+11 | 114163.05 | 17-MAR-12:44 | 12.20 | 9.29 | 0.593652E+10 | 7499.29 | 15-MAR-09:20 | 12.20 | 9.29 |
April | 0.479758E+11 | 113772.35 | 10-APR-04:12 | 3.50 | 2.94 | 0.527835E+10 | 7499.23 | 19-APR-13:39 | 16.47 | 9.13 |
May | 0.503516E+11 | 125653.24 | 19-MAY-05:02 | 8.90 | 7.70 | 0.573340E+10 | 7499.30 | 30-MAY-13:20 | 17.80 | 14.66 |
June | 0.576604E+11 | 134567.07 | 03-JUN-04:11 | 11.50 | 8.63 | 0.585349E+10 | 7499.36 | 28-JUN-09:00 | 22.80 | 18.39 |
July | 0.607319E+11 | 121431.93 | 03-JUL-04:11 | 11.70 | 11.07 | 0.546752E+10 | 7506.89 | 05-JUL-09:09 | 22.88 | 19.40 |
August | 0.707576E+11 | 116042.75 | 03-AUG-04:12 | 11.10 | 9.59 | 0.612639E+10 | 7499.40 | 30-AUG-13:00 | 20.00 | 18.50 |
September | 0.630840E+11 | 134024.42 | 18-SEP-04:22 | 10.00 | 9.10 | 0.539774E+10 | 7499.37 | 25-SEP-13:00 | 24.40 | 19.51 |
October | 0.629606E+11 | 139418.51 | 02-OCT-04:11 | 7.93 | 7.62 | 0.556713E+10 | 7499.33 | 12-OCT-13:09 | 17.38 | 14.04 |
November | 0.588421E+11 | 136540.55 | 01-NOV-04:11 | 5.20 | 2.48 | 0.551725E+10 | 7499.28 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.536711E+11 | 115221.56 | 26-DEC-04:01 | -11.8 | -12.8 | 0.523286E+10 | 7498.67 | 13-DEC-14:39 | -11.8 | -12.8 |
Annual Sum or Average | 0.669246E+12 | 0.659848E+11 | ||||||||
Minimum of Months | 0.436329E+11 | 113772.35 | -11.8 | -12.8 | 0.465780E+10 | 7493.56 | -11.8 | -12.8 | ||
Maximum of Months | 0.707576E+11 | 139418.51 | 12.20 | 11.07 | 0.612639E+10 | 7506.89 | 24.40 | 19.51 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.347332E+11 | 36410.81 | 20-JAN-17:00 | -1.1 | -3.7 | 0.496806E+10 | 6734.93 | 11-JAN-10:20 | -1.1 | -3.7 |
February | 0.313090E+11 | 95961.27 | 23-FEB-06:01 | 2.30 | 1.81 | 0.448523E+10 | 6734.90 | 15-FEB-10:09 | 2.30 | 1.81 |
March | 0.468804E+11 | 111081.99 | 17-MAR-04:11 | 10.60 | 9.99 | 0.546411E+10 | 6734.92 | 16-MAR-13:00 | 10.60 | 9.99 |
April | 0.487370E+11 | 110172.02 | 20-APR-04:11 | 11.50 | 7.71 | 0.487160E+10 | 6734.90 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.519761E+11 | 111195.09 | 30-MAY-04:12 | 12.20 | 11.68 | 0.527617E+10 | 6734.88 | 10-MAY-09:09 | 12.20 | 11.68 |
June | 0.604272E+11 | 116163.63 | 19-JUN-04:12 | 16.70 | 15.97 | 0.526735E+10 | 6734.93 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.676051E+11 | 118184.40 | 10-JUL-04:11 | 13.70 | 13.03 | 0.489498E+10 | 6734.88 | 06-JUL-09:09 | 13.70 | 13.03 |
August | 0.742273E+11 | 118885.60 | 21-AUG-04:11 | 14.80 | 13.30 | 0.549809E+10 | 6734.87 | 24-AUG-09:20 | 15.77 | 15.06 |
September | 0.549850E+11 | 118023.82 | 18-SEP-04:12 | 10.20 | 9.28 | 0.487936E+10 | 6735.22 | 12-SEP-13:09 | 10.20 | 9.28 |
October | 0.489098E+11 | 112449.94 | 02-OCT-04:11 | 7.93 | 7.62 | 0.506745E+10 | 6734.90 | 03-OCT-09:39 | 12.07 | 9.92 |
November | 0.452323E+11 | 114174.33 | 06-NOV-05:11 | 8.90 | 6.96 | 0.501883E+10 | 6734.92 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.400934E+11 | 106219.09 | 01-DEC-06:01 | 10.10 | 8.62 | 0.485612E+10 | 6734.88 | 12-DEC-14:00 | -3.3 | -3.5 |
Annual Sum or Average | 0.605116E+12 | 0.605474E+11 | ||||||||
Minimum of Months | 0.313090E+11 | 36410.81 | -1.1 | -3.7 | 0.448523E+10 | 6734.87 | -3.3 | -3.7 | ||
Maximum of Months | 0.742273E+11 | 118885.60 | 16.70 | 15.97 | 0.549809E+10 | 6735.22 | 20.60 | 15.40 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.274957E+11 | 26790.26 | 20-JAN-17:00 | -1.1 | -3.7 | 0.447785E+10 | 6734.82 | 13-JAN-14:39 | -1.1 | -3.7 |
February | 0.262341E+11 | 28418.83 | 17-FEB-16:51 | 1.10 | 0.20 | 0.410482E+10 | 6734.88 | 03-FEB-14:09 | 1.10 | 0.20 |
March | 0.357908E+11 | 100302.78 | 17-MAR-05:01 | 10.50 | 9.94 | 0.529081E+10 | 6734.92 | 16-MAR-13:00 | 10.50 | 9.94 |
April | 0.360201E+11 | 94614.66 | 21-APR-05:02 | 2.80 | 1.46 | 0.479181E+10 | 6734.90 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.445118E+11 | 102074.00 | 18-MAY-05:01 | 8.48 | 5.49 | 0.525261E+10 | 6734.88 | 10-MAY-09:09 | 8.48 | 5.49 |
June | 0.511681E+11 | 106564.96 | 30-JUN-04:11 | 16.50 | 15.77 | 0.525308E+10 | 6734.93 | 22-JUN-13:09 | 16.50 | 15.77 |
July | 0.523073E+11 | 105822.35 | 25-JUL-04:11 | 15.00 | 13.80 | 0.488772E+10 | 6734.88 | 06-JUL-09:09 | 15.00 | 13.80 |
August | 0.550668E+11 | 106693.24 | 09-AUG-04:11 | 16.47 | 13.64 | 0.549030E+10 | 6734.89 | 24-AUG-09:20 | 15.77 | 15.06 |
September | 0.449221E+11 | 105885.74 | 18-SEP-04:12 | 10.20 | 9.28 | 0.485574E+10 | 6735.22 | 12-SEP-13:09 | 10.20 | 9.28 |
October | 0.369487E+11 | 101566.68 | 13-OCT-05:01 | 10.50 | 10.16 | 0.500039E+10 | 6734.90 | 03-OCT-09:39 | 10.50 | 10.16 |
November | 0.316805E+11 | 91173.48 | 01-NOV-05:01 | 5.68 | 3.03 | 0.489703E+10 | 6734.92 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.287911E+11 | 32111.53 | 01-DEC-16:53 | 7.20 | 4.89 | 0.443385E+10 | 6734.86 | 20-DEC-14:50 | 0.60 | 0.17 |
Annual Sum or Average | 0.470937E+12 | 0.587360E+11 | ||||||||
Minimum of Months | 0.262341E+11 | 26790.26 | -1.1 | -3.7 | 0.410482E+10 | 6734.82 | -1.1 | -3.7 | ||
Maximum of Months | 0.550668E+11 | 106693.24 | 16.50 | 15.77 | 0.549030E+10 | 6735.22 | 17.20 | 15.77 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.170404E+11 | 20856.40 | 11-JAN-17:00 | 11.10 | 9.84 | 0.391792E+10 | 5879.68 | 11-JAN-14:00 | 11.10 | 9.84 |
February | 0.171692E+11 | 21471.79 | 28-FEB-17:00 | -0.6 | -3.0 | 0.363194E+10 | 6062.20 | 23-FEB-14:00 | -0.6 | -3.0 |
March | 0.275227E+11 | 103265.59 | 16-MAR-05:01 | 14.03 | 11.42 | 0.473535E+10 | 6734.92 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.292293E+11 | 45228.11 | 20-APR-15:53 | 15.00 | 11.00 | 0.440652E+10 | 6734.89 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.405055E+11 | 105315.75 | 24-MAY-05:02 | 18.80 | 15.75 | 0.507545E+10 | 6734.84 | 17-MAY-09:30 | 18.80 | 15.75 |
June | 0.528277E+11 | 111970.53 | 21-JUN-05:01 | 18.30 | 16.18 | 0.520290E+10 | 6734.93 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.564916E+11 | 114831.44 | 17-JUL-03:01 | 24.22 | 21.20 | 0.486448E+10 | 6734.88 | 06-JUL-09:09 | 24.22 | 21.20 |
August | 0.559907E+11 | 111553.48 | 11-AUG-04:12 | 18.53 | 15.89 | 0.545121E+10 | 6734.89 | 24-AUG-09:20 | 15.77 | 15.06 |
September | 0.402532E+11 | 102866.38 | 14-SEP-05:02 | 20.60 | 19.14 | 0.471997E+10 | 6735.18 | 12-SEP-13:09 | 20.60 | 19.14 |
October | 0.284378E+11 | 42753.61 | 12-OCT-15:42 | 18.30 | 14.93 | 0.455972E+10 | 6734.89 | 06-OCT-13:39 | 18.30 | 14.93 |
November | 0.223760E+11 | 26259.00 | 01-NOV-15:53 | 9.40 | 6.91 | 0.422673E+10 | 6734.88 | 01-NOV-13:00 | 9.40 | 6.91 |
December | 0.181034E+11 | 21790.56 | 01-DEC-17:00 | 7.20 | 4.89 | 0.381274E+10 | 6196.08 | 01-DEC-14:00 | 7.20 | 4.89 |
Annual Sum or Average | 0.405948E+12 | 0.546049E+11 | ||||||||
Minimum of Months | 0.170404E+11 | 20856.40 | -0.6 | -3.0 | 0.363194E+10 | 5879.68 | -0.6 | -3.0 | ||
Maximum of Months | 0.564916E+11 | 114831.44 | 24.22 | 21.20 | 0.545121E+10 | 6735.18 | 24.22 | 21.20 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131730E+10 | 3377.57 | 11-JAN-16:00 | 11.70 | 10.14 | 0.475032E+09 | 715.36 | 11-JAN-14:00 | 11.70 | 10.14 |
February | 0.142342E+10 | 3403.19 | 22-FEB-16:00 | 10.60 | 5.02 | 0.435130E+09 | 727.34 | 22-FEB-14:00 | 10.60 | 5.02 |
March | 0.420101E+10 | 9164.68 | 15-MAR-14:00 | 26.10 | 16.06 | 0.586131E+09 | 845.65 | 16-MAR-13:50 | 18.15 | 14.69 |
April | 0.535951E+10 | 7868.47 | 07-APR-13:30 | 20.00 | 10.05 | 0.562454E+09 | 845.64 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.710374E+10 | 9332.54 | 23-MAY-14:40 | 23.90 | 13.32 | 0.641623E+09 | 845.64 | 31-MAY-13:20 | 21.30 | 14.21 |
June | 0.100774E+11 | 15693.84 | 17-JUN-05:01 | 20.00 | 17.21 | 0.657101E+09 | 845.64 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.121167E+11 | 14161.29 | 17-JUL-04:12 | 23.13 | 21.08 | 0.613942E+09 | 845.65 | 06-JUL-13:30 | 23.13 | 21.08 |
August | 0.120952E+11 | 14957.14 | 14-AUG-04:11 | 23.13 | 21.90 | 0.687091E+09 | 845.64 | 04-AUG-09:09 | 23.13 | 21.90 |
September | 0.755289E+10 | 9478.21 | 13-SEP-13:30 | 22.20 | 19.01 | 0.597464E+09 | 845.69 | 12-SEP-13:09 | 22.20 | 19.01 |
October | 0.527320E+10 | 6682.39 | 12-OCT-13:53 | 18.30 | 14.87 | 0.585036E+09 | 845.63 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.406221E+10 | 5194.92 | 27-NOV-05:11 | 17.97 | 12.28 | 0.542474E+09 | 845.64 | 16-NOV-14:20 | 17.97 | 12.28 |
December | 0.213787E+10 | 4390.57 | 01-DEC-06:02 | 10.10 | 8.62 | 0.471124E+09 | 778.72 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.727204E+11 | 0.685460E+10 | ||||||||
Minimum of Months | 0.131730E+10 | 3377.57 | 10.10 | 5.02 | 0.435130E+09 | 715.36 | 8.12 | 5.02 | ||
Maximum of Months | 0.121167E+11 | 15693.84 | 26.10 | 21.90 | 0.687091E+09 | 845.69 | 23.13 | 21.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134938E+10 | 3660.06 | 06-JAN-10:25 | -6.4 | -8.0 | 0.302185E+09 | 441.58 | 06-JAN-10:39 | -6.1 | -7.7 |
February | 0.152399E+10 | 5127.10 | 28-FEB-09:33 | -5.2 | -6.5 | 0.279372E+09 | 544.96 | 28-FEB-10:09 | -3.6 | -5.3 |
March | 0.437898E+10 | 8942.65 | 21-MAR-09:01 | 1.88 | -0.4 | 0.372109E+09 | 544.97 | 15-MAR-09:00 | 1.88 | -0.4 |
April | 0.602017E+10 | 13123.15 | 24-APR-08:23 | 5.55 | 2.59 | 0.353397E+09 | 544.96 | 21-APR-13:00 | 5.55 | 2.59 |
May | 0.802842E+10 | 16398.35 | 29-MAY-10:12 | 18.50 | 14.34 | 0.402504E+09 | 544.97 | 26-MAY-09:00 | 18.50 | 14.34 |
June | 0.100743E+11 | 29092.05 | 11-JUN-09:12 | 23.67 | 16.37 | 0.417696E+09 | 544.96 | 06-JUN-13:20 | 23.67 | 16.37 |
July | 0.114637E+11 | 29153.85 | 04-JUL-07:01 | 18.35 | 16.65 | 0.391225E+09 | 544.98 | 12-JUL-09:50 | 20.40 | 14.43 |
August | 0.111509E+11 | 21169.66 | 20-AUG-09:32 | 20.20 | 14.23 | 0.435802E+09 | 544.99 | 16-AUG-09:50 | 20.20 | 14.23 |
September | 0.790334E+10 | 19303.15 | 04-SEP-09:02 | 16.88 | 13.13 | 0.377035E+09 | 544.99 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.539999E+10 | 12849.87 | 09-OCT-08:25 | 5.55 | 4.21 | 0.362182E+09 | 544.96 | 03-OCT-09:50 | 5.55 | 4.21 |
November | 0.360883E+10 | 6228.99 | 03-NOV-09:01 | 4.18 | 2.03 | 0.322542E+09 | 544.96 | 03-NOV-09:09 | 4.18 | 2.03 |
December | 0.150843E+10 | 4851.11 | 21-DEC-06:02 | 1.02 | 0.58 | 0.292691E+09 | 485.14 | 04-DEC-10:09 | 1.02 | 0.58 |
Annual Sum or Average | 0.724105E+11 | 0.430874E+10 | ||||||||
Minimum of Months | 0.134938E+10 | 3660.06 | -6.4 | -8.0 | 0.279372E+09 | 441.58 | -6.1 | -7.7 | ||
Maximum of Months | 0.114637E+11 | 29153.85 | 23.67 | 16.65 | 0.435802E+09 | 544.99 | 23.67 | 16.55 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.297904E+10 | 14392.51 | 12-JAN-13:30 | -6.7 | -9.2 | 0.502304E+09 | 845.64 | 04-JAN-14:20 | -6.7 | -9.2 |
February | 0.330228E+10 | 17573.30 | 28-FEB-13:21 | 0.00 | -2.9 | 0.463538E+09 | 845.65 | 28-FEB-10:09 | 0.00 | -2.9 |
March | 0.775155E+10 | 21223.88 | 15-MAR-13:30 | 25.55 | 15.84 | 0.611553E+09 | 846.55 | 15-MAR-13:00 | 26.10 | 16.06 |
April | 0.836654E+10 | 23548.76 | 23-APR-13:11 | 16.67 | 9.22 | 0.552262E+09 | 845.66 | 20-APR-13:39 | 16.67 | 9.22 |
May | 0.100102E+11 | 15134.98 | 10-MAY-12:40 | 24.27 | 17.26 | 0.622112E+09 | 845.68 | 16-MAY-13:39 | 21.33 | 12.03 |
June | 0.124815E+11 | 30978.06 | 18-JUN-14:21 | 25.85 | 20.72 | 0.644923E+09 | 845.67 | 06-JUN-13:20 | 25.85 | 20.72 |
July | 0.151363E+11 | 22854.62 | 30-JUL-12:23 | 25.60 | 19.63 | 0.607469E+09 | 845.70 | 06-JUL-13:30 | 25.60 | 19.63 |
August | 0.164738E+11 | 31337.30 | 13-AUG-15:21 | 29.70 | 23.34 | 0.679756E+09 | 846.15 | 08-AUG-13:00 | 29.70 | 23.34 |
September | 0.127521E+11 | 35396.03 | 10-SEP-13:02 | 17.20 | 10.56 | 0.589473E+09 | 846.18 | 22-SEP-13:09 | 22.98 | 14.46 |
October | 0.939576E+10 | 24968.26 | 11-OCT-12:30 | 21.95 | 13.79 | 0.585420E+09 | 846.90 | 11-OCT-13:39 | 22.20 | 14.14 |
November | 0.592431E+10 | 19196.11 | 03-NOV-12:21 | 8.35 | 4.56 | 0.535416E+09 | 845.65 | 01-NOV-13:39 | 8.35 | 4.56 |
December | 0.311371E+10 | 14719.31 | 04-DEC-11:35 | -0.4 | -3.0 | 0.478080E+09 | 845.65 | 11-DEC-14:20 | -8.0 | -9.0 |
Annual Sum or Average | 0.107687E+12 | 0.687231E+10 | ||||||||
Minimum of Months | 0.297904E+10 | 14392.51 | -6.7 | -9.2 | 0.463538E+09 | 845.64 | -8.0 | -9.2 | ||
Maximum of Months | 0.164738E+11 | 35396.03 | 29.70 | 23.34 | 0.679756E+09 | 846.90 | 29.70 | 23.34 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240063E+10 | 5435.57 | 15-JAN-14:38 | 5.40 | 1.82 | 0.306158E+09 | 474.67 | 12-JAN-15:50 | 5.40 | 1.82 |
February | 0.280746E+10 | 8904.89 | 28-FEB-16:21 | 0.00 | -2.6 | 0.282955E+09 | 538.39 | 28-FEB-14:00 | 0.00 | -2.6 |
March | 0.706112E+10 | 18022.03 | 16-MAR-04:11 | 18.13 | 13.40 | 0.381159E+09 | 544.97 | 16-MAR-13:50 | 18.15 | 14.69 |
April | 0.883671E+10 | 24194.36 | 02-APR-18:01 | 5.73 | 4.61 | 0.360033E+09 | 544.96 | 20-APR-13:39 | 13.13 | 9.72 |
May | 0.990263E+10 | 28126.64 | 07-MAY-16:52 | 15.00 | 5.87 | 0.392718E+09 | 544.97 | 16-MAY-13:39 | 21.33 | 12.03 |
June | 0.128944E+11 | 39276.00 | 11-JUN-16:41 | 25.60 | 17.82 | 0.414509E+09 | 544.96 | 06-JUN-13:20 | 25.60 | 17.82 |
July | 0.152828E+11 | 36703.14 | 02-JUL-17:01 | 24.82 | 16.94 | 0.393911E+09 | 544.99 | 06-JUL-13:30 | 21.40 | 12.35 |
August | 0.160655E+11 | 35146.60 | 13-AUG-15:21 | 29.70 | 23.34 | 0.442299E+09 | 544.97 | 16-AUG-09:50 | 21.42 | 16.29 |
September | 0.961763E+10 | 35053.56 | 10-SEP-15:41 | 17.70 | 11.18 | 0.370156E+09 | 545.00 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.726450E+10 | 14710.51 | 11-OCT-16:00 | 21.70 | 14.52 | 0.359391E+09 | 544.96 | 30-OCT-13:00 | 15.00 | 8.94 |
November | 0.586185E+10 | 8920.90 | 15-NOV-14:52 | 11.70 | 6.59 | 0.340270E+09 | 544.96 | 09-NOV-14:00 | 11.70 | 6.59 |
December | 0.428278E+10 | 7131.29 | 01-DEC-06:01 | 10.10 | 8.62 | 0.307440E+09 | 529.26 | 04-DEC-14:00 | 0.00 | -2.9 |
Annual Sum or Average | 0.102278E+12 | 0.435100E+10 | ||||||||
Minimum of Months | 0.240063E+10 | 5435.57 | 0.00 | -2.6 | 0.282955E+09 | 474.67 | 0.00 | -2.9 | ||
Maximum of Months | 0.160655E+11 | 39276.00 | 29.70 | 23.34 | 0.442299E+09 | 545.00 | 25.60 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199205E+09 | 3733.75 | 27-JAN-06:04 | -5.0 | -6.2 | 0.463965E+09 | 625.97 | 31-JAN-14:09 | -11.1 | -12.5 |
February | 0.306755E+09 | 3693.24 | 18-FEB-17:01 | 0.82 | -0.6 | 0.421274E+09 | 625.78 | 02-FEB-10:39 | 0.82 | -0.6 |
March | 0.266492E+10 | 7507.04 | 15-MAR-14:40 | 25.77 | 16.18 | 0.528277E+09 | 845.62 | 15-MAR-13:20 | 25.77 | 16.18 |
April | 0.418555E+10 | 5786.74 | 07-APR-14:10 | 19.72 | 10.09 | 0.484104E+09 | 824.58 | 07-APR-13:00 | 19.72 | 10.09 |
May | 0.707795E+10 | 8373.44 | 23-MAY-14:40 | 23.90 | 13.32 | 0.583457E+09 | 845.63 | 26-MAY-13:50 | 21.42 | 13.71 |
June | 0.974398E+10 | 11104.25 | 27-JUN-13:20 | 29.47 | 23.48 | 0.630046E+09 | 845.64 | 22-JUN-13:09 | 29.47 | 23.48 |
July | 0.108203E+11 | 17810.45 | 21-JUL-03:01 | 28.53 | 24.64 | 0.600213E+09 | 845.64 | 06-JUL-13:30 | 28.53 | 24.64 |
August | 0.103491E+11 | 11286.24 | 09-AUG-14:40 | 29.40 | 18.10 | 0.662033E+09 | 845.64 | 02-AUG-13:09 | 29.40 | 18.10 |
September | 0.722719E+10 | 8443.07 | 15-SEP-14:00 | 25.60 | 21.03 | 0.550037E+09 | 845.68 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.430885E+10 | 6681.02 | 11-OCT-12:30 | 21.95 | 13.79 | 0.504366E+09 | 798.59 | 05-OCT-13:00 | 21.95 | 13.79 |
November | 0.206633E+10 | 4915.18 | 16-NOV-15:02 | 17.20 | 13.33 | 0.468451E+09 | 722.47 | 16-NOV-14:00 | 17.20 | 13.33 |
December | 0.366350E+09 | 4105.40 | 01-DEC-13:10 | 12.97 | 11.34 | 0.447749E+09 | 632.26 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.593165E+11 | 0.634397E+10 | ||||||||
Minimum of Months | 0.199205E+09 | 3693.24 | -5.0 | -6.2 | 0.421274E+09 | 625.78 | -11.1 | -12.5 | ||
Maximum of Months | 0.108203E+11 | 17810.45 | 29.47 | 24.64 | 0.662033E+09 | 845.68 | 29.47 | 24.64 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197156E+09 | 4162.33 | 06-JAN-11:02 | -5.3 | -7.0 | 0.218055E+09 | 462.37 | 06-JAN-11:09 | -5.3 | -7.0 |
February | 0.460877E+09 | 12311.46 | 28-FEB-11:01 | -2.0 | -4.1 | 0.199900E+09 | 548.49 | 28-FEB-11:09 | -2.0 | -4.1 |
March | 0.257257E+10 | 17169.87 | 21-MAR-10:01 | 2.88 | 0.57 | 0.260607E+09 | 548.50 | 15-MAR-10:09 | 2.88 | 0.57 |
April | 0.430331E+10 | 14823.71 | 20-APR-12:01 | 16.05 | 10.00 | 0.249878E+09 | 548.51 | 07-APR-12:09 | 16.05 | 10.00 |
May | 0.705882E+10 | 21595.32 | 21-MAY-09:02 | 16.60 | 11.79 | 0.289460E+09 | 548.51 | 26-MAY-10:09 | 18.98 | 12.55 |
June | 0.954431E+10 | 23304.48 | 06-JUN-10:01 | 17.57 | 10.72 | 0.302629E+09 | 548.50 | 15-JUN-10:09 | 17.30 | 11.04 |
July | 0.105467E+11 | 30265.76 | 04-JUL-09:22 | 21.65 | 17.37 | 0.287096E+09 | 548.52 | 12-JUL-10:09 | 20.87 | 14.79 |
August | 0.990885E+10 | 30005.46 | 06-AUG-09:12 | 24.47 | 17.45 | 0.316190E+09 | 548.51 | 16-AUG-10:09 | 21.97 | 16.33 |
September | 0.684265E+10 | 27996.94 | 04-SEP-09:32 | 17.43 | 13.19 | 0.270023E+09 | 548.53 | 12-SEP-12:09 | 20.68 | 15.09 |
October | 0.351837E+10 | 19561.95 | 11-OCT-10:01 | 17.15 | 12.50 | 0.252893E+09 | 548.49 | 11-OCT-14:09 | 22.20 | 14.22 |
November | 0.138006E+10 | 14049.16 | 03-NOV-10:01 | 5.78 | 3.09 | 0.226793E+09 | 548.49 | 16-NOV-13:09 | 18.62 | 13.01 |
December | 0.222954E+09 | 4493.92 | 01-DEC-13:02 | 12.97 | 11.34 | 0.210392E+09 | 484.30 | 01-DEC-13:09 | 12.97 | 11.34 |
Annual Sum or Average | 0.565566E+11 | 0.308392E+10 | ||||||||
Minimum of Months | 0.197156E+09 | 4162.33 | -5.3 | -7.0 | 0.199900E+09 | 462.37 | -5.3 | -7.0 | ||
Maximum of Months | 0.105467E+11 | 30265.76 | 24.47 | 17.45 | 0.316190E+09 | 548.53 | 22.20 | 16.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.209851E+10 | 14493.72 | 12-JAN-13:40 | -6.5 | -9.0 | 0.492542E+09 | 845.64 | 12-JAN-14:30 | -5.8 | -8.4 |
February | 0.255560E+10 | 19300.22 | 28-FEB-13:31 | 0.00 | -2.9 | 0.452729E+09 | 845.65 | 17-FEB-10:00 | 0.00 | -2.9 |
March | 0.668775E+10 | 21046.83 | 15-MAR-13:30 | 25.55 | 15.84 | 0.592000E+09 | 846.41 | 15-MAR-13:00 | 26.10 | 16.06 |
April | 0.695044E+10 | 20000.01 | 09-APR-14:23 | 16.65 | 11.08 | 0.530575E+09 | 845.66 | 03-APR-13:20 | 16.65 | 11.08 |
May | 0.923395E+10 | 16000.61 | 14-MAY-14:01 | 25.18 | 18.10 | 0.607172E+09 | 845.68 | 16-MAY-13:39 | 21.33 | 12.03 |
June | 0.115828E+11 | 17065.94 | 27-JUN-13:00 | 30.60 | 23.75 | 0.633284E+09 | 845.67 | 06-JUN-13:20 | 30.60 | 23.75 |
July | 0.133269E+11 | 21778.93 | 30-JUL-12:43 | 25.60 | 19.42 | 0.600174E+09 | 845.71 | 06-JUL-13:30 | 25.60 | 19.42 |
August | 0.143435E+11 | 34754.68 | 06-AUG-14:31 | 27.77 | 18.96 | 0.668999E+09 | 846.27 | 17-AUG-13:20 | 28.50 | 15.76 |
September | 0.121986E+11 | 35631.96 | 04-SEP-13:32 | 18.33 | 13.04 | 0.578649E+09 | 846.49 | 22-SEP-13:20 | 23.17 | 14.63 |
October | 0.854410E+10 | 26726.91 | 31-OCT-13:20 | 15.00 | 10.26 | 0.567308E+09 | 850.25 | 31-OCT-13:20 | 15.00 | 10.26 |
November | 0.450409E+10 | 20452.61 | 03-NOV-12:22 | 8.35 | 4.56 | 0.512893E+09 | 845.66 | 03-NOV-13:00 | 9.40 | 4.98 |
December | 0.171548E+10 | 12861.54 | 16-DEC-13:23 | 5.60 | 3.03 | 0.462366E+09 | 845.65 | 04-DEC-10:00 | 5.60 | 3.03 |
Annual Sum or Average | 0.937416E+11 | 0.669869E+10 | ||||||||
Minimum of Months | 0.171548E+10 | 12861.54 | -6.5 | -9.0 | 0.452729E+09 | 845.64 | -5.8 | -8.4 | ||
Maximum of Months | 0.143435E+11 | 35631.96 | 30.60 | 23.75 | 0.668999E+09 | 850.25 | 30.60 | 23.75 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.423178E+09 | 4080.84 | 06-JAN-15:40 | -2.2 | -4.8 | 0.299639E+09 | 418.86 | 06-JAN-14:00 | -2.2 | -4.8 |
February | 0.726651E+09 | 6358.96 | 28-FEB-16:21 | 0.00 | -2.6 | 0.274259E+09 | 521.20 | 28-FEB-16:19 | 0.00 | -2.6 |
March | 0.336037E+10 | 9300.27 | 21-MAR-15:52 | 4.40 | 1.34 | 0.347146E+09 | 544.94 | 15-MAR-13:00 | 4.40 | 1.34 |
April | 0.492091E+10 | 16760.71 | 30-APR-16:12 | 15.00 | 12.10 | 0.318020E+09 | 544.96 | 21-APR-13:00 | 15.00 | 12.10 |
May | 0.778553E+10 | 22970.69 | 07-MAY-16:32 | 15.00 | 5.92 | 0.367312E+09 | 544.95 | 22-MAY-13:00 | 16.70 | 11.28 |
June | 0.106427E+11 | 33676.74 | 04-JUN-17:01 | 19.22 | 11.55 | 0.394991E+09 | 544.96 | 23-JUN-13:39 | 19.23 | 12.79 |
July | 0.111832E+11 | 33833.37 | 02-JUL-17:21 | 24.45 | 16.81 | 0.378030E+09 | 544.95 | 12-JUL-13:20 | 22.60 | 14.71 |
August | 0.109106E+11 | 32560.39 | 06-AUG-16:31 | 27.80 | 18.98 | 0.417226E+09 | 544.96 | 02-AUG-13:20 | 27.80 | 18.98 |
September | 0.742878E+10 | 31778.51 | 04-SEP-17:32 | 17.23 | 12.32 | 0.345721E+09 | 544.94 | 22-SEP-13:00 | 23.90 | 15.30 |
October | 0.433844E+10 | 12809.94 | 11-OCT-16:00 | 21.70 | 14.52 | 0.326878E+09 | 544.96 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.212530E+10 | 5499.19 | 15-NOV-15:30 | 11.70 | 6.70 | 0.305929E+09 | 529.80 | 15-NOV-14:00 | 11.70 | 6.70 |
December | 0.524971E+09 | 4269.87 | 04-DEC-15:50 | -0.5 | -3.2 | 0.289144E+09 | 431.59 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.643707E+11 | 0.406429E+10 | ||||||||
Minimum of Months | 0.423178E+09 | 4080.84 | -2.2 | -4.8 | 0.274259E+09 | 418.86 | -2.2 | -4.8 | ||
Maximum of Months | 0.111832E+11 | 33833.37 | 27.80 | 18.98 | 0.417226E+09 | 544.96 | 27.80 | 18.98 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57510057.73 | 5188.19 | 02-JAN-06:04 | -1.1 | -1.7 | 0.463160E+09 | 626.09 | 23-JAN-10:09 | -7.0 | -8.8 |
February | 0.124734E+09 | 5207.92 | 02-FEB-06:04 | -1.0 | -1.2 | 0.420517E+09 | 625.79 | 23-FEB-10:39 | 0.33 | -0.4 |
March | 0.207610E+10 | 8313.40 | 16-MAR-05:01 | 14.03 | 11.42 | 0.515495E+09 | 832.83 | 15-MAR-13:00 | 14.03 | 11.42 |
April | 0.355628E+10 | 7046.24 | 09-APR-14:11 | 16.83 | 11.10 | 0.463489E+09 | 772.47 | 07-APR-13:00 | 16.83 | 11.10 |
May | 0.719074E+10 | 9021.37 | 24-MAY-05:02 | 18.80 | 15.75 | 0.544934E+09 | 844.51 | 23-MAY-13:00 | 18.80 | 15.75 |
June | 0.107798E+11 | 12763.02 | 12-JUN-14:50 | 30.10 | 20.02 | 0.599723E+09 | 845.63 | 08-JUN-13:50 | 30.10 | 20.02 |
July | 0.122141E+11 | 25650.63 | 21-JUL-03:01 | 28.53 | 24.64 | 0.579760E+09 | 845.62 | 07-JUL-13:20 | 28.53 | 24.64 |
August | 0.113582E+11 | 12547.77 | 09-AUG-15:00 | 29.40 | 18.10 | 0.632528E+09 | 845.63 | 02-AUG-13:20 | 29.40 | 18.10 |
September | 0.726590E+10 | 10045.18 | 17-SEP-14:31 | 22.60 | 18.98 | 0.513725E+09 | 845.61 | 15-SEP-13:20 | 22.60 | 18.98 |
October | 0.331296E+10 | 6723.00 | 12-OCT-15:30 | 18.30 | 15.05 | 0.478377E+09 | 738.20 | 05-OCT-13:00 | 18.30 | 15.05 |
November | 0.900987E+09 | 5414.04 | 16-NOV-15:00 | 17.20 | 13.27 | 0.461063E+09 | 650.84 | 16-NOV-14:00 | 17.20 | 13.27 |
December | 0.128278E+09 | 5282.80 | 21-DEC-06:04 | 1.02 | 0.58 | 0.446732E+09 | 626.00 | 12-DEC-10:09 | 1.02 | 0.58 |
Annual Sum or Average | 0.589657E+11 | 0.611950E+10 | ||||||||
Minimum of Months | 57510057.73 | 5188.19 | -1.1 | -1.7 | 0.420517E+09 | 625.79 | -7.0 | -8.8 | ||
Maximum of Months | 0.122141E+11 | 25650.63 | 30.10 | 24.64 | 0.632528E+09 | 845.63 | 30.10 | 24.64 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52449748.69 | 3525.26 | 02-JAN-06:04 | -1.1 | -1.7 | 0.298517E+09 | 403.42 | 24-JAN-14:00 | -6.7 | -9.3 |
February | 0.365483E+09 | 4056.56 | 28-FEB-10:20 | -3.3 | -5.1 | 0.271440E+09 | 451.44 | 28-FEB-10:30 | -3.0 | -4.8 |
March | 0.235950E+10 | 6864.39 | 14-MAR-10:50 | 21.73 | 17.44 | 0.343203E+09 | 544.95 | 15-MAR-13:20 | 25.37 | 15.76 |
April | 0.390829E+10 | 10239.64 | 24-APR-09:28 | 6.65 | 3.34 | 0.328978E+09 | 544.96 | 21-APR-13:00 | 6.65 | 3.34 |
May | 0.679524E+10 | 14368.80 | 31-MAY-09:10 | 17.88 | 13.30 | 0.385829E+09 | 544.97 | 16-MAY-13:39 | 17.88 | 13.30 |
June | 0.977987E+10 | 30569.53 | 11-JUN-10:02 | 24.50 | 16.94 | 0.409601E+09 | 544.97 | 06-JUN-13:20 | 24.50 | 16.94 |
July | 0.110635E+11 | 30348.59 | 04-JUL-09:02 | 21.28 | 17.22 | 0.388420E+09 | 544.98 | 03-JUL-09:50 | 21.28 | 17.22 |
August | 0.101574E+11 | 30467.59 | 06-AUG-10:02 | 25.78 | 17.83 | 0.427486E+09 | 545.00 | 16-AUG-09:50 | 21.42 | 16.29 |
September | 0.651949E+10 | 11662.49 | 21-SEP-09:50 | 21.23 | 15.72 | 0.362114E+09 | 544.99 | 12-SEP-13:09 | 21.23 | 15.72 |
October | 0.315502E+10 | 8274.45 | 11-OCT-09:42 | 16.42 | 12.11 | 0.324900E+09 | 544.96 | 11-OCT-09:20 | 16.42 | 12.11 |
November | 0.920230E+09 | 4208.88 | 03-NOV-10:00 | 5.60 | 2.99 | 0.298572E+09 | 461.02 | 03-NOV-09:00 | 5.60 | 2.99 |
December | 92740867.50 | 3562.44 | 21-DEC-06:04 | 1.02 | 0.58 | 0.287890E+09 | 403.41 | 29-DEC-10:39 | -5.8 | -7.1 |
Annual Sum or Average | 0.551692E+11 | 0.412695E+10 | ||||||||
Minimum of Months | 52449748.69 | 3525.26 | -3.3 | -5.1 | 0.271440E+09 | 403.41 | -6.7 | -9.3 | ||
Maximum of Months | 0.110635E+11 | 30569.53 | 25.78 | 17.83 | 0.427486E+09 | 545.00 | 25.37 | 17.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154154E+10 | 11575.03 | 12-JAN-13:50 | -6.3 | -8.9 | 0.479765E+09 | 845.64 | 12-JAN-14:20 | -5.9 | -8.5 |
February | 0.202942E+10 | 18356.33 | 28-FEB-13:41 | 0.00 | -3.0 | 0.440818E+09 | 845.65 | 22-FEB-14:09 | 0.00 | -3.0 |
March | 0.587905E+10 | 21502.46 | 15-MAR-13:30 | 25.55 | 15.84 | 0.565990E+09 | 845.65 | 01-MAR-14:09 | 25.55 | 15.84 |
April | 0.624062E+10 | 17876.39 | 19-APR-13:43 | 16.83 | 9.16 | 0.507365E+09 | 845.65 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.915186E+10 | 16232.78 | 26-MAY-13:30 | 20.85 | 13.56 | 0.577283E+09 | 845.68 | 16-MAY-13:39 | 20.85 | 13.56 |
June | 0.124320E+11 | 18742.70 | 12-JUN-13:20 | 29.80 | 19.89 | 0.610350E+09 | 845.67 | 06-JUN-13:20 | 29.80 | 19.89 |
July | 0.145762E+11 | 26713.42 | 21-JUL-03:01 | 28.53 | 24.64 | 0.583741E+09 | 845.71 | 06-JUL-13:30 | 28.53 | 24.64 |
August | 0.151032E+11 | 43565.60 | 06-AUG-12:42 | 27.12 | 18.21 | 0.646974E+09 | 845.67 | 02-AUG-13:09 | 27.12 | 18.21 |
September | 0.118243E+11 | 45328.56 | 10-SEP-14:32 | 17.20 | 10.67 | 0.555105E+09 | 845.72 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.738805E+10 | 26124.21 | 11-OCT-12:30 | 21.95 | 13.79 | 0.533832E+09 | 845.66 | 11-OCT-13:09 | 22.20 | 14.14 |
November | 0.318357E+10 | 18128.99 | 03-NOV-12:41 | 8.72 | 4.81 | 0.490360E+09 | 845.65 | 01-NOV-13:30 | 8.72 | 4.81 |
December | 0.117164E+10 | 10318.10 | 16-DEC-13:23 | 5.60 | 3.03 | 0.454692E+09 | 845.65 | 04-DEC-14:09 | 5.60 | 3.03 |
Annual Sum or Average | 0.905215E+11 | 0.644627E+10 | ||||||||
Minimum of Months | 0.117164E+10 | 10318.10 | -6.3 | -8.9 | 0.440818E+09 | 845.64 | -5.9 | -8.5 | ||
Maximum of Months | 0.151032E+11 | 45328.56 | 29.80 | 24.64 | 0.646974E+09 | 845.72 | 29.80 | 24.64 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237192E+09 | 4106.31 | 19-JAN-06:04 | 1.10 | -0.1 | 0.298761E+09 | 403.47 | 27-JAN-14:09 | -3.2 | -5.0 |
February | 0.535152E+09 | 6108.48 | 28-FEB-16:28 | 0.00 | -2.6 | 0.273159E+09 | 521.20 | 28-FEB-16:40 | -0.2 | -2.7 |
March | 0.287364E+10 | 9206.20 | 21-MAR-15:52 | 4.40 | 1.34 | 0.341741E+09 | 544.92 | 15-MAR-13:00 | 4.40 | 1.34 |
April | 0.430745E+10 | 14001.21 | 19-APR-15:55 | 17.20 | 8.76 | 0.312317E+09 | 539.54 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.741713E+10 | 21920.95 | 07-MAY-17:12 | 14.63 | 5.67 | 0.357980E+09 | 544.95 | 22-MAY-13:00 | 16.70 | 11.28 |
June | 0.108328E+11 | 39502.27 | 11-JUN-16:41 | 25.60 | 17.82 | 0.387427E+09 | 544.96 | 05-JUN-13:39 | 25.60 | 17.82 |
July | 0.116587E+11 | 36802.12 | 02-JUL-17:21 | 24.45 | 16.81 | 0.371824E+09 | 544.95 | 12-JUL-13:20 | 22.60 | 14.71 |
August | 0.111139E+11 | 38322.38 | 06-AUG-16:41 | 27.80 | 19.02 | 0.408026E+09 | 544.95 | 02-AUG-13:30 | 27.80 | 19.02 |
September | 0.701174E+10 | 24541.63 | 10-SEP-17:12 | 16.10 | 10.54 | 0.336327E+09 | 544.94 | 22-SEP-13:00 | 23.90 | 15.30 |
October | 0.352368E+10 | 13283.47 | 11-OCT-16:00 | 21.70 | 14.52 | 0.319587E+09 | 535.33 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.133368E+10 | 5610.77 | 15-NOV-15:30 | 11.70 | 6.70 | 0.301396E+09 | 504.75 | 15-NOV-14:00 | 11.70 | 6.70 |
December | 0.279317E+09 | 4249.95 | 04-DEC-15:43 | -0.5 | -3.2 | 0.288183E+09 | 407.70 | 04-DEC-15:50 | -0.5 | -3.2 |
Annual Sum or Average | 0.611244E+11 | 0.399673E+10 | ||||||||
Minimum of Months | 0.237192E+09 | 4106.31 | -0.5 | -3.2 | 0.273159E+09 | 403.47 | -3.2 | -5.0 | ||
Maximum of Months | 0.116587E+11 | 39502.27 | 27.80 | 19.02 | 0.408026E+09 | 544.96 | 27.80 | 19.02 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177061E+10 | 12331.17 | 04-JAN-05:01 | -12.2 | -12.8 | 0.00 | 0.00 | 01-JAN-00:10 | -12.2 | -12.8 |
February | 0.165316E+10 | 14584.12 | 06-FEB-04:01 | -15.0 | -15.8 | 0.00 | 0.00 | 01-FEB-00:10 | -15.0 | -15.8 |
March | 0.436488E+10 | 10935.22 | 06-MAR-05:01 | -11.1 | -11.9 | 0.00 | 0.00 | 01-MAR-00:10 | -11.1 | -11.9 |
April | 0.566721E+10 | 8639.33 | 10-APR-05:06 | 3.98 | 3.28 | 0.00 | 0.00 | 01-APR-00:10 | 3.98 | 3.28 |
May | 0.694191E+10 | 9396.64 | 30-MAY-05:07 | 12.20 | 11.93 | 0.00 | 0.00 | 01-MAY-00:10 | 12.20 | 11.93 |
June | 0.931423E+10 | 9494.59 | 13-JUN-05:12 | 8.90 | 8.22 | 0.00 | 0.00 | 01-JUN-00:10 | 8.90 | 8.22 |
July | 0.111157E+11 | 10925.46 | 31-JUL-05:11 | 17.60 | 16.78 | 0.00 | 0.00 | 01-JUL-00:10 | 17.60 | 16.78 |
August | 0.117678E+11 | 10518.23 | 21-AUG-05:12 | 14.40 | 13.12 | 0.00 | 0.00 | 01-AUG-00:10 | 14.40 | 13.12 |
September | 0.828035E+10 | 10269.20 | 19-SEP-05:12 | 10.60 | 9.56 | 0.00 | 0.00 | 01-SEP-00:10 | 10.60 | 9.56 |
October | 0.607787E+10 | 9225.68 | 30-OCT-05:01 | -0.1 | -0.9 | 0.00 | 0.00 | 01-OCT-00:10 | -0.1 | -0.9 |
November | 0.501914E+10 | 9329.65 | 25-NOV-06:01 | -1.7 | -2.5 | 0.00 | 0.00 | 01-NOV-00:10 | -1.7 | -2.5 |
December | 0.279190E+10 | 11934.37 | 11-DEC-04:01 | -17.2 | -17.4 | 0.00 | 0.00 | 01-DEC-00:10 | -17.2 | -17.4 |
Annual Sum or Average | 0.747648E+11 | 0.00 | ||||||||
Minimum of Months | 0.165316E+10 | 8639.33 | -17.2 | -17.4 | 0.00 | 0.00 | -17.2 | -17.4 | ||
Maximum of Months | 0.117678E+11 | 14584.12 | 17.60 | 16.78 | 0.00 | 0.00 | 17.60 | 16.78 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154865E+10 | 17578.25 | 28-JAN-04:01 | -6.3 | -7.8 | 0.00 | 0.00 | 01-JAN-00:10 | -6.3 | -7.8 |
February | 0.173443E+10 | 18897.76 | 05-FEB-04:41 | -13.2 | -13.6 | 0.00 | 0.00 | 01-FEB-00:10 | -13.2 | -13.6 |
March | 0.282795E+10 | 20483.40 | 04-MAR-04:01 | -10.0 | -11.2 | 0.00 | 0.00 | 01-MAR-00:10 | -10.0 | -11.2 |
April | 0.349163E+10 | 14546.04 | 17-APR-03:01 | -2.9 | -4.8 | 0.00 | 0.00 | 01-APR-00:10 | -2.9 | -4.8 |
May | 0.551852E+10 | 9043.49 | 27-MAY-05:08 | 8.58 | 6.54 | 0.00 | 0.00 | 01-MAY-00:10 | 8.58 | 6.54 |
June | 0.767824E+10 | 9252.90 | 10-JUN-05:05 | 6.88 | 6.30 | 0.00 | 0.00 | 01-JUN-00:10 | 6.88 | 6.30 |
July | 0.881458E+10 | 9571.30 | 28-JUL-05:13 | 20.20 | 19.05 | 0.00 | 0.00 | 01-JUL-00:10 | 20.20 | 19.05 |
August | 0.905899E+10 | 9825.95 | 11-AUG-05:13 | 17.80 | 15.36 | 0.00 | 0.00 | 01-AUG-00:10 | 17.80 | 15.36 |
September | 0.667879E+10 | 9930.86 | 19-SEP-05:10 | 10.60 | 9.47 | 0.00 | 0.00 | 01-SEP-00:10 | 10.60 | 9.47 |
October | 0.394007E+10 | 14261.83 | 24-OCT-04:01 | 0.10 | -1.0 | 0.00 | 0.00 | 01-OCT-00:10 | 0.10 | -1.0 |
November | 0.229192E+10 | 17272.91 | 24-NOV-04:01 | -3.2 | -3.8 | 0.00 | 0.00 | 01-NOV-00:10 | -3.2 | -3.8 |
December | 0.178974E+10 | 17758.85 | 08-DEC-04:01 | -8.3 | -9.1 | 0.00 | 0.00 | 01-DEC-00:10 | -8.3 | -9.1 |
Annual Sum or Average | 0.553735E+11 | 0.00 | ||||||||
Minimum of Months | 0.154865E+10 | 9043.49 | -13.2 | -13.6 | 0.00 | 0.00 | -13.2 | -13.6 | ||
Maximum of Months | 0.905899E+10 | 20483.40 | 20.20 | 19.05 | 0.00 | 0.00 | 20.20 | 19.05 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 413623.44 | 492.93 | 15-JAN-12:40 | 4.40 | 2.13 | 0.00 | 0.00 | 01-JAN-00:10 | 4.40 | 2.13 |
February | 83523007.75 | 2583.92 | 28-FEB-14:01 | 0.00 | -3.0 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | -3.0 |
March | 0.248259E+10 | 20379.70 | 15-MAR-14:00 | 26.10 | 16.06 | 0.00 | 0.00 | 01-MAR-00:10 | 26.10 | 16.06 |
April | 0.558370E+10 | 18877.30 | 19-APR-14:32 | 17.20 | 9.64 | 0.00 | 0.00 | 01-APR-00:10 | 17.20 | 9.64 |
May | 0.114617E+11 | 25686.80 | 31-MAY-14:20 | 21.70 | 14.12 | 0.00 | 0.00 | 01-MAY-00:10 | 21.70 | 14.12 |
June | 0.185623E+11 | 33019.32 | 27-JUN-13:30 | 28.90 | 23.32 | 0.00 | 0.00 | 01-JUN-00:10 | 28.90 | 23.32 |
July | 0.214917E+11 | 33461.14 | 21-JUL-13:30 | 31.15 | 21.91 | 0.00 | 0.00 | 01-JUL-00:10 | 31.15 | 21.91 |
August | 0.188418E+11 | 32904.89 | 09-AUG-13:50 | 29.32 | 18.11 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 18.11 |
September | 0.104504E+11 | 26159.45 | 21-SEP-14:05 | 25.68 | 16.62 | 0.00 | 0.00 | 01-SEP-00:10 | 25.68 | 16.62 |
October | 0.331480E+10 | 16324.70 | 11-OCT-13:00 | 22.20 | 14.14 | 0.00 | 0.00 | 01-OCT-00:10 | 22.20 | 14.14 |
November | 0.520766E+09 | 5984.59 | 16-NOV-13:01 | 18.62 | 13.01 | 0.00 | 0.00 | 01-NOV-00:10 | 18.62 | 13.01 |
December | 9666310.03 | 1336.22 | 01-DEC-13:02 | 12.97 | 11.34 | 0.00 | 0.00 | 01-DEC-00:10 | 12.97 | 11.34 |
Annual Sum or Average | 0.928033E+11 | 0.00 | ||||||||
Minimum of Months | 413623.44 | 492.93 | 0.00 | -3.0 | 0.00 | 0.00 | 0.00 | -3.0 | ||
Maximum of Months | 0.214917E+11 | 33461.14 | 31.15 | 23.32 | 0.00 | 0.00 | 31.15 | 23.32 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193874E+10 | 2054.21 | 12-JAN-16:35 | -6.5 | -8.3 | 95230128.50 | 126.82 | 12-JAN-10:20 | -6.5 | -8.3 |
February | 0.624589E+10 | 4276.58 | 28-FEB-16:51 | -0.6 | -3.0 | 86396487.34 | 126.82 | 21-FEB-10:09 | -0.6 | -3.0 |
March | 0.133253E+11 | 6691.58 | 31-MAR-23:57 | 4.20 | 3.93 | 0.103236E+09 | 126.82 | 14-MAR-13:00 | 4.20 | 3.93 |
April | 0.182806E+11 | 8085.45 | 24-APR-17:55 | 11.70 | 8.10 | 91605108.82 | 126.82 | 28-APR-13:00 | 10.00 | 9.06 |
May | 0.417329E+10 | 3430.64 | 31-MAY-23:51 | 17.10 | 14.03 | 99233606.58 | 126.83 | 17-MAY-13:00 | 17.10 | 14.03 |
June | 0.932427E+10 | 5350.87 | 30-JUN-23:51 | 16.90 | 13.02 | 98958613.04 | 126.83 | 27-JUN-09:09 | 16.90 | 13.02 |
July | 0.149310E+11 | 7224.86 | 31-JUL-23:04 | 20.43 | 17.98 | 91881727.34 | 126.82 | 20-JUL-13:00 | 20.43 | 17.98 |
August | 0.199444E+11 | 8419.43 | 02-AUG-18:40 | 22.07 | 14.68 | 0.103239E+09 | 126.83 | 14-AUG-09:09 | 24.32 | 21.72 |
September | 0.426444E+10 | 3073.43 | 30-SEP-23:51 | 14.40 | 12.09 | 91607429.45 | 126.83 | 14-SEP-13:09 | 14.40 | 12.09 |
October | 0.866083E+10 | 4902.65 | 31-OCT-23:52 | 6.60 | 4.77 | 95230132.23 | 126.82 | 26-OCT-09:00 | 6.60 | 4.77 |
November | 0.129964E+11 | 5998.06 | 24-NOV-16:11 | 3.87 | 1.42 | 94300281.15 | 126.82 | 10-NOV-14:30 | 3.87 | 1.42 |
December | 0.176794E+11 | 7751.45 | 04-DEC-16:12 | -1.1 | -3.7 | 91880866.20 | 126.82 | 01-DEC-14:09 | -1.1 | -3.7 |
Annual Sum or Average | 0.131765E+12 | 0.114280E+10 | ||||||||
Minimum of Months | 0.193874E+10 | 2054.21 | -6.5 | -8.3 | 86396487.34 | 126.82 | -6.5 | -8.3 | ||
Maximum of Months | 0.199444E+11 | 8419.43 | 22.07 | 17.98 | 0.103239E+09 | 126.83 | 24.32 | 21.72 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.595227E+09 | 1726.66 | 12-JAN-16:35 | -6.5 | -8.3 | 95109127.65 | 126.82 | 12-JAN-10:00 | -6.5 | -8.3 |
February | 0.426028E+10 | 3957.40 | 28-FEB-16:51 | -0.6 | -3.0 | 86396487.34 | 126.82 | 21-FEB-10:09 | -0.6 | -3.0 |
March | 0.114373E+11 | 6073.95 | 31-MAR-23:27 | 4.50 | 4.12 | 0.103236E+09 | 126.82 | 15-MAR-09:00 | 4.50 | 4.12 |
April | 0.165828E+11 | 7808.21 | 24-APR-17:55 | 11.70 | 8.10 | 91605111.75 | 126.82 | 28-APR-13:00 | 10.00 | 9.06 |
May | 0.340510E+10 | 3214.80 | 31-MAY-23:31 | 17.17 | 13.97 | 99233605.98 | 126.83 | 17-MAY-13:00 | 17.17 | 13.97 |
June | 0.865708E+10 | 5109.61 | 30-JUN-23:31 | 17.07 | 12.89 | 98958725.16 | 126.83 | 27-JUN-09:00 | 17.07 | 12.89 |
July | 0.140397E+11 | 6984.30 | 31-JUL-24:00 | 19.10 | 16.93 | 91881679.43 | 126.83 | 20-JUL-13:00 | 19.10 | 16.93 |
August | 0.187891E+11 | 8101.48 | 02-AUG-18:40 | 22.07 | 14.68 | 0.103240E+09 | 126.83 | 14-AUG-09:09 | 24.32 | 21.72 |
September | 0.341350E+10 | 2510.45 | 30-SEP-23:51 | 14.40 | 12.09 | 91607403.51 | 126.83 | 15-SEP-13:00 | 14.40 | 12.09 |
October | 0.722605E+10 | 4305.12 | 31-OCT-23:22 | 6.80 | 4.88 | 95230139.91 | 126.82 | 26-OCT-09:00 | 6.80 | 4.88 |
November | 0.110260E+11 | 5603.75 | 15-NOV-16:21 | 10.55 | 6.20 | 94300282.56 | 126.82 | 10-NOV-10:00 | 10.55 | 6.20 |
December | 0.147117E+11 | 7063.29 | 04-DEC-16:23 | -1.4 | -3.9 | 91880869.74 | 126.82 | 01-DEC-14:09 | -1.4 | -3.9 |
Annual Sum or Average | 0.114144E+12 | 0.114268E+10 | ||||||||
Minimum of Months | 0.595227E+09 | 1726.66 | -6.5 | -8.3 | 86396487.34 | 126.82 | -6.5 | -8.3 | ||
Maximum of Months | 0.187891E+11 | 8101.48 | 22.07 | 16.93 | 0.103240E+09 | 126.83 | 24.32 | 21.72 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222291E+09 | 1431.17 | 12-JAN-16:35 | -6.5 | -8.3 | 94015265.17 | 127.58 | 20-JAN-10:09 | -1.2 | -2.9 |
February | 0.267255E+10 | 3894.51 | 28-FEB-16:51 | -0.6 | -3.0 | 86396487.50 | 126.82 | 21-FEB-10:09 | -0.6 | -3.0 |
March | 0.955010E+10 | 5800.86 | 21-MAR-17:32 | 3.50 | 0.63 | 0.103236E+09 | 126.82 | 15-MAR-09:00 | 3.50 | 0.63 |
April | 0.151983E+11 | 7829.45 | 24-APR-17:55 | 11.70 | 8.10 | 91605109.26 | 126.82 | 28-APR-13:00 | 10.00 | 9.06 |
May | 0.267131E+10 | 3006.04 | 31-MAY-23:12 | 17.23 | 13.91 | 99236176.61 | 126.83 | 17-MAY-13:00 | 17.23 | 13.91 |
June | 0.839024E+10 | 4929.93 | 30-JUN-23:12 | 17.23 | 12.75 | 98958708.13 | 126.83 | 27-JUN-09:00 | 17.23 | 12.75 |
July | 0.139592E+11 | 6925.38 | 31-JUL-23:38 | 19.63 | 17.35 | 91881651.90 | 126.82 | 20-JUL-13:00 | 19.63 | 17.35 |
August | 0.185752E+11 | 8192.73 | 02-AUG-18:40 | 22.07 | 14.68 | 0.103239E+09 | 126.83 | 14-AUG-09:09 | 24.32 | 21.72 |
September | 0.268772E+10 | 2465.16 | 11-SEP-17:50 | 17.38 | 11.75 | 91608203.60 | 126.84 | 15-SEP-13:09 | 25.10 | 20.83 |
October | 0.545854E+10 | 4298.60 | 11-OCT-17:00 | 21.70 | 14.52 | 95230149.93 | 126.82 | 26-OCT-09:00 | 10.00 | 10.00 |
November | 0.883975E+10 | 5443.26 | 15-NOV-16:11 | 10.93 | 6.40 | 94300283.85 | 126.82 | 10-NOV-10:00 | 10.93 | 6.40 |
December | 0.124585E+11 | 6773.29 | 04-DEC-16:12 | -1.1 | -3.7 | 91880869.92 | 126.82 | 01-DEC-14:30 | -1.1 | -3.7 |
Annual Sum or Average | 0.100684E+12 | 0.114159E+10 | ||||||||
Minimum of Months | 0.222291E+09 | 1431.17 | -6.5 | -8.3 | 86396487.50 | 126.82 | -1.2 | -3.7 | ||
Maximum of Months | 0.185752E+11 | 8192.73 | 22.07 | 17.35 | 0.103239E+09 | 127.58 | 25.10 | 21.72 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231715E+12 | 95367.34 | 23-JAN-22:01 | -10.6 | -11.9 | 0.208772E+10 | 2805.79 | 13-JAN-14:30 | -10.6 | -11.9 |
February | 0.433555E+12 | 485896.80 | 01-FEB-00:12 | -2.9 | -4.1 | 0.156152E+10 | 2644.47 | 17-FEB-14:00 | 3.30 | 1.08 |
March | 0.725182E+12 | 512102.54 | 17-MAR-12:42 | 12.20 | 9.29 | 0.198033E+10 | 2742.37 | 14-MAR-13:20 | 12.20 | 9.29 |
April | 0.944049E+12 | 490062.06 | 27-APR-19:13 | 9.23 | 8.43 | 0.158837E+10 | 2848.81 | 07-APR-13:09 | 9.23 | 8.43 |
May | 0.234932E+12 | 436195.70 | 31-MAY-23:56 | 17.10 | 14.03 | 0.215985E+10 | 2851.31 | 09-MAY-13:09 | 17.10 | 14.03 |
June | 0.471172E+12 | 491837.34 | 25-JUN-02:52 | 11.70 | 10.15 | 0.195588E+10 | 2802.59 | 06-JUN-13:09 | 11.70 | 10.15 |
July | 0.730518E+12 | 485206.96 | 06-JUL-07:42 | 15.40 | 11.92 | 0.196801E+10 | 2819.96 | 06-JUL-13:09 | 20.87 | 12.22 |
August | 0.978825E+12 | 478565.67 | 02-AUG-22:25 | 16.40 | 12.36 | 0.218663E+10 | 2900.87 | 22-AUG-14:09 | 22.88 | 13.18 |
September | 0.235061E+12 | 464571.06 | 30-SEP-23:52 | 14.40 | 12.09 | 0.198461E+10 | 2806.16 | 19-SEP-13:00 | 14.40 | 12.09 |
October | 0.490538E+12 | 517788.58 | 31-OCT-23:52 | 6.60 | 4.77 | 0.181223E+10 | 2760.67 | 23-OCT-13:00 | 6.60 | 4.77 |
November | 0.708574E+12 | 517916.80 | 01-NOV-00:02 | 6.53 | 4.43 | 0.167762E+10 | 2723.17 | 08-NOV-10:00 | 5.00 | 4.51 |
December | 0.979088E+12 | 504259.28 | 13-DEC-17:04 | 2.88 | 2.59 | 0.157709E+10 | 2754.35 | 18-DEC-10:30 | 2.20 | 1.95 |
Annual Sum or Average | 0.716321E+13 | 0.225399E+11 | ||||||||
Minimum of Months | 0.231715E+12 | 95367.34 | -10.6 | -11.9 | 0.156152E+10 | 2644.47 | -10.6 | -11.9 | ||
Maximum of Months | 0.979088E+12 | 517916.80 | 17.10 | 14.03 | 0.218663E+10 | 2900.87 | 22.88 | 14.03 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38095334.85 | 3586.84 | 03-JAN-06:45 | -4.4 |
February | 34171744.35 | 2793.25 | 18-FEB-06:04 | -1.7 |
March | 55878535.26 | 2808.86 | 20-MAR-05:11 | -2.8 |
April | 58497750.71 | 2719.19 | 25-APR-05:04 | 6.70 |
May | 58075330.28 | 3096.31 | 08-MAY-05:05 | 3.40 |
June | 70354790.93 | 7678.32 | 17-JUN-16:03 | 28.40 |
July | 38719280.76 | 6354.18 | 15-JUL-16:03 | 27.65 |
August | 41919642.54 | 6102.78 | 05-AUG-16:02 | 27.30 |
September | 33673058.94 | 4807.02 | 16-SEP-16:03 | 26.60 |
October | 67013890.28 | 2873.66 | 16-OCT-05:05 | 1.20 |
November | 54742915.62 | 2628.86 | 24-NOV-06:04 | -3.8 |
December | 57626113.53 | 2856.82 | 29-DEC-06:05 | -8.1 |
Annual Sum or Average | 0.608768E+09 | |||
Minimum of Months | 33673058.94 | 2628.86 | -8.1 | |
Maximum of Months | 70354790.93 | 7678.32 | 28.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.746832E+09 | 58554.29 | 02-JAN-04:01 | -1.0 |
February | 0.274850E+09 | 54372.46 | 06-FEB-05:11 | -14.6 |
March | 19127109.13 | 50956.36 | 06-MAR-06:01 | -11.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.53 |
December | 0.231074E+09 | 55759.93 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.127188E+10 | |||
Minimum of Months | 0.00 | 0.00 | -14.6 | |
Maximum of Months | 0.746832E+09 | 58554.29 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.824466E+10 | 113192.41 | 09-JAN-04:11 | -9.4 |
February | 0.715101E+10 | 114555.41 | 06-FEB-03:31 | -14.6 |
March | 0.345455E+10 | 112185.60 | 06-MAR-04:01 | -11.1 |
April | 0.750814E+09 | 107583.07 | 17-APR-03:11 | -3.0 |
May | 26525852.64 | 68436.85 | 01-MAY-05:03 | 1.70 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.980945E+09 | 96765.79 | 30-OCT-04:01 | -0.5 |
November | 0.192254E+10 | 107876.85 | 24-NOV-04:01 | -3.2 |
December | 0.679202E+10 | 114734.02 | 26-DEC-04:11 | -11.9 |
Annual Sum or Average | 0.293231E+11 | |||
Minimum of Months | 0.00 | 0.00 | -14.6 | |
Maximum of Months | 0.824466E+10 | 114734.02 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176826E+10 | 18379.24 | 30-JAN-04:01 | -9.9 |
February | 0.178690E+10 | 19667.14 | 06-FEB-04:01 | -15.0 |
March | 0.458426E+09 | 17706.24 | 06-MAR-05:01 | -11.1 |
April | 10165073.66 | 15796.68 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 8889395.87 | 15011.42 | 30-OCT-05:01 | -0.1 |
November | 17859033.37 | 15995.28 | 24-NOV-06:01 | -3.8 |
December | 0.892611E+09 | 18532.98 | 11-DEC-04:01 | -17.2 |
Annual Sum or Average | 0.494311E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.2 | |
Maximum of Months | 0.178690E+10 | 19667.14 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120560E+10 | 17524.00 | 30-JAN-04:01 | -9.9 |
February | 0.121870E+10 | 19034.54 | 06-FEB-04:01 | -15.0 |
March | 0.308459E+09 | 16955.93 | 07-MAR-05:01 | -13.3 |
April | 17902930.51 | 13487.41 | 17-APR-05:01 | -4.0 |
May | 63231.74 | 331.02 | 01-MAY-05:05 | 1.70 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 12748740.65 | 12596.34 | 30-OCT-05:01 | -0.1 |
November | 36850317.60 | 13680.28 | 24-NOV-06:01 | -3.8 |
December | 0.825162E+09 | 18130.38 | 11-DEC-04:01 | -17.2 |
Annual Sum or Average | 0.362549E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.2 | |
Maximum of Months | 0.121870E+10 | 19034.54 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205958E+10 | 25562.36 | 30-JAN-04:01 | -9.9 |
February | 0.211505E+10 | 26920.47 | 06-FEB-04:01 | -15.0 |
March | 0.563824E+09 | 24293.84 | 06-MAR-04:01 | -11.1 |
April | 72863147.30 | 20552.43 | 17-APR-04:01 | -3.4 |
May | 51715.27 | 313.19 | 13-MAY-05:06 | 8.80 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 57274808.12 | 19413.35 | 30-OCT-04:01 | -0.5 |
November | 0.134412E+09 | 20914.63 | 24-NOV-05:01 | -3.0 |
December | 0.138211E+10 | 26046.80 | 26-DEC-04:01 | -11.8 |
Annual Sum or Average | 0.638516E+10 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.211505E+10 | 26920.47 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.500302E+09 | 16381.64 | 24-JAN-05:01 | -11.8 |
February | 0.502217E+09 | 18003.34 | 06-FEB-04:01 | -15.0 |
March | 31121882.95 | 15391.37 | 06-MAR-05:01 | -11.1 |
April | 772199.58 | 9009.00 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 861616.88 | 11759.12 | 30-OCT-05:01 | -0.1 |
November | 2336838.89 | 12839.93 | 24-NOV-06:01 | -3.8 |
December | 0.108480E+09 | 16291.66 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.114609E+10 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.502217E+09 | 18003.34 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.781197E+10 | 29201.45 | 09-JAN-02:11 | -8.7 |
February | 0.712668E+10 | 31628.98 | 06-FEB-00:31 | -12.8 |
March | 0.277420E+10 | 29723.28 | 06-MAR-03:41 | -11.0 |
April | 0.549961E+09 | 27149.71 | 17-APR-03:01 | -2.9 |
May | 19965082.72 | 17664.38 | 08-MAY-05:03 | 3.40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 8436974.67 | 11508.34 | 30-SEP-05:03 | 7.20 |
October | 0.368629E+09 | 24335.87 | 17-OCT-04:41 | -2.8 |
November | 0.110245E+10 | 26786.88 | 24-NOV-04:01 | -3.2 |
December | 0.657765E+10 | 31247.49 | 26-DEC-03:21 | -11.7 |
Annual Sum or Average | 0.263399E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.781197E+10 | 31628.98 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.443120E+10 | 23546.05 | 09-JAN-02:11 | -8.7 |
February | 0.414953E+10 | 25789.14 | 06-FEB-01:11 | -13.2 |
March | 0.132095E+10 | 24036.97 | 06-MAR-03:41 | -11.0 |
April | 0.272294E+09 | 20345.85 | 17-APR-03:01 | -2.9 |
May | 10213776.12 | 10019.95 | 08-MAY-05:03 | 3.40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 12122.86 | 141.43 | 31-AUG-05:03 | 11.20 |
September | 5097568.47 | 7817.43 | 30-SEP-05:03 | 7.20 |
October | 0.217307E+09 | 18136.32 | 17-OCT-04:41 | -2.8 |
November | 0.678858E+09 | 20474.44 | 24-NOV-04:01 | -3.2 |
December | 0.405935E+10 | 25407.50 | 26-DEC-02:41 | -11.7 |
Annual Sum or Average | 0.151448E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.443120E+10 | 25789.14 | 17.05 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.548074E+10 | 28967.17 | 09-JAN-02:11 | -8.7 |
February | 0.533064E+10 | 31499.53 | 06-FEB-03:11 | -14.3 |
March | 0.155247E+10 | 28916.61 | 06-MAR-03:41 | -11.0 |
April | 0.443393E+09 | 26235.56 | 17-APR-03:01 | -2.9 |
May | 16332329.70 | 13691.37 | 08-MAY-05:03 | 3.40 |
June | 633912.03 | 9415.62 | 14-JUN-05:01 | 6.78 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 4021298.83 | 7379.01 | 30-SEP-05:03 | 7.20 |
October | 0.240970E+09 | 24074.40 | 17-OCT-04:41 | -2.8 |
November | 0.841325E+09 | 26585.94 | 24-NOV-04:01 | -3.2 |
December | 0.484263E+10 | 31300.66 | 26-DEC-03:21 | -11.7 |
Annual Sum or Average | 0.187532E+11 | |||
Minimum of Months | 0.00 | 0.00 | -14.3 | |
Maximum of Months | 0.548074E+10 | 31499.53 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.414125E+10 | 23986.48 | 09-JAN-04:11 | -9.4 |
February | 0.374155E+10 | 26251.09 | 06-FEB-03:11 | -14.3 |
March | 0.113905E+10 | 23300.86 | 06-MAR-04:21 | -11.1 |
April | 0.214566E+09 | 19023.59 | 17-APR-04:01 | -3.4 |
May | 2710203.32 | 4239.74 | 03-MAY-05:02 | 6.10 |
June | 15590.96 | 259.85 | 14-JUN-05:02 | 6.78 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 2719586.48 | 4497.19 | 30-SEP-05:03 | 7.20 |
October | 0.166963E+09 | 18188.81 | 30-OCT-04:01 | -0.5 |
November | 0.556060E+09 | 19385.31 | 24-NOV-04:01 | -3.2 |
December | 0.337545E+10 | 25820.27 | 26-DEC-03:21 | -11.7 |
Annual Sum or Average | 0.133403E+11 | |||
Minimum of Months | 0.00 | 0.00 | -14.3 | |
Maximum of Months | 0.414125E+10 | 26251.09 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142280E+11 | 39752.72 | 24-JAN-05:11 | -11.9 |
February | 0.134103E+11 | 42972.02 | 06-FEB-02:51 | -13.9 |
March | 0.684714E+10 | 40739.93 | 06-MAR-03:51 | -11.1 |
April | 0.228061E+10 | 37562.03 | 17-APR-03:11 | -3.0 |
May | 0.356237E+09 | 26794.02 | 08-MAY-04:11 | 3.30 |
June | 19462437.44 | 23846.34 | 14-JUN-04:11 | 6.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 1243535.25 | 5901.20 | 31-AUG-05:01 | 11.20 |
September | 0.202511E+09 | 23927.66 | 30-SEP-04:12 | 7.20 |
October | 0.192650E+10 | 34781.82 | 30-OCT-03:51 | -0.6 |
November | 0.419166E+10 | 38789.94 | 24-NOV-04:01 | -3.2 |
December | 0.134768E+11 | 42633.11 | 26-DEC-04:11 | -11.9 |
Annual Sum or Average | 0.569405E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.9 | |
Maximum of Months | 0.142280E+11 | 42972.02 | 16.82 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.844739E+10 | 26813.43 | 24-JAN-05:11 | -11.9 |
February | 0.804799E+10 | 28977.99 | 06-FEB-02:51 | -13.9 |
March | 0.355592E+10 | 27471.80 | 06-MAR-03:51 | -11.1 |
April | 0.114585E+10 | 24916.17 | 17-APR-03:11 | -3.0 |
May | 0.167219E+09 | 17382.89 | 08-MAY-04:11 | 3.30 |
June | 10983579.06 | 15873.07 | 14-JUN-04:11 | 6.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 1306848.97 | 5126.10 | 31-AUG-05:01 | 11.20 |
September | 95820424.35 | 15860.73 | 30-SEP-04:12 | 7.20 |
October | 0.109214E+10 | 23166.98 | 30-OCT-03:51 | -0.6 |
November | 0.251801E+10 | 25858.99 | 24-NOV-04:01 | -3.2 |
December | 0.849880E+10 | 28840.35 | 26-DEC-04:11 | -11.9 |
Annual Sum or Average | 0.335814E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.9 | |
Maximum of Months | 0.849880E+10 | 28977.99 | 16.82 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107932E+11 | 39697.12 | 24-JAN-05:11 | -11.9 |
February | 0.107649E+11 | 42836.62 | 06-FEB-02:51 | -13.9 |
March | 0.463318E+10 | 40173.87 | 06-MAR-03:51 | -11.1 |
April | 0.193405E+10 | 37371.07 | 17-APR-03:11 | -3.0 |
May | 0.362281E+09 | 25842.07 | 08-MAY-04:11 | 3.30 |
June | 47183926.29 | 23778.93 | 14-JUN-04:11 | 6.70 |
July | 2627.95 | 43.80 | 06-JUL-05:04 | 11.88 |
August | 569458.33 | 3845.79 | 31-AUG-05:01 | 11.20 |
September | 0.123702E+09 | 23511.97 | 30-SEP-04:12 | 7.20 |
October | 0.143349E+10 | 34608.05 | 30-OCT-03:51 | -0.6 |
November | 0.326758E+10 | 38749.09 | 24-NOV-04:01 | -3.2 |
December | 0.108016E+11 | 42689.34 | 26-DEC-04:11 | -11.9 |
Annual Sum or Average | 0.441617E+11 | |||
Minimum of Months | 2627.95 | 43.80 | -13.9 | |
Maximum of Months | 0.108016E+11 | 42836.62 | 11.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.757626E+10 | 29933.66 | 24-JAN-05:11 | -11.9 |
February | 0.691066E+10 | 32252.82 | 06-FEB-02:51 | -13.9 |
March | 0.287332E+10 | 30066.59 | 06-MAR-03:51 | -11.1 |
April | 0.945653E+09 | 26219.30 | 17-APR-03:11 | -3.0 |
May | 0.125493E+09 | 15129.83 | 18-MAY-05:01 | 8.48 |
June | 11182573.07 | 15722.07 | 14-JUN-05:01 | 6.78 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 24791.07 | 289.23 | 31-AUG-05:03 | 11.20 |
September | 59917635.32 | 15060.87 | 30-SEP-04:12 | 7.20 |
October | 0.795481E+09 | 24136.26 | 30-OCT-03:51 | -0.6 |
November | 0.183843E+10 | 27078.09 | 24-NOV-04:01 | -3.2 |
December | 0.676781E+10 | 31849.41 | 26-DEC-04:11 | -11.9 |
Annual Sum or Average | 0.279042E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.9 | |
Maximum of Months | 0.757626E+10 | 32252.82 | 16.82 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.335644E+09 | 5694.86 | 15-JAN-12:28 | 4.40 |
February | 0.611933E+09 | 7902.71 | 23-FEB-06:01 | 2.30 |
March | 83116443.78 | 10512.32 | 13-MAR-05:01 | 8.80 |
April | 46643239.52 | 10645.80 | 20-APR-04:11 | 11.50 |
May | 50059940.89 | 8412.51 | 07-MAY-16:52 | 15.00 |
June | 53756095.32 | 10639.89 | 12-JUN-04:11 | 22.60 |
July | 94001127.49 | 11129.09 | 11-JUL-04:11 | 20.00 |
August | 94659410.89 | 12136.22 | 25-AUG-04:11 | 18.90 |
September | 52588896.29 | 10291.54 | 10-SEP-15:41 | 17.70 |
October | 36742016.59 | 10296.78 | 26-OCT-04:11 | 15.20 |
November | 27326417.34 | 12439.45 | 27-NOV-05:11 | 17.97 |
December | 0.114408E+09 | 11612.39 | 14-DEC-06:02 | 5.68 |
Annual Sum or Average | 0.160088E+10 | |||
Minimum of Months | 27326417.34 | 5694.86 | 2.30 | |
Maximum of Months | 0.611933E+09 | 12439.45 | 22.60 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.443284E+10 | 23111.18 | 02-JAN-06:13 | -1.1 |
February | 0.349017E+10 | 15392.02 | 06-FEB-06:02 | -13.9 |
March | 0.112115E+10 | 8480.04 | 07-MAR-11:01 | -5.8 |
April | 0.199625E+09 | 8471.81 | 09-APR-15:20 | 15.93 |
May | 40653303.70 | 7956.85 | 14-MAY-11:28 | 21.10 |
June | 36439138.91 | 8362.74 | 11-JUN-16:52 | 25.60 |
July | 49618892.44 | 9948.61 | 21-JUL-03:01 | 28.53 |
August | 39342366.02 | 12260.49 | 13-AUG-15:11 | 29.80 |
September | 37012848.16 | 10873.63 | 04-SEP-15:31 | 18.50 |
October | 0.108376E+09 | 8360.68 | 09-OCT-10:40 | 10.93 |
November | 0.162630E+09 | 4576.39 | 16-NOV-06:01 | 11.78 |
December | 0.272051E+10 | 15130.67 | 26-DEC-06:11 | -12.2 |
Annual Sum or Average | 0.124384E+11 | |||
Minimum of Months | 36439138.91 | 4576.39 | -13.9 | |
Maximum of Months | 0.443284E+10 | 23111.18 | 29.80 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.257062E+11 | 51092.13 | 24-JAN-05:22 | -11.9 |
February | 0.221631E+11 | 55425.62 | 06-FEB-05:06 | -14.8 |
March | 0.122645E+11 | 51060.99 | 06-MAR-05:15 | -11.1 |
April | 0.496143E+10 | 37738.86 | 17-APR-05:01 | -4.0 |
May | 0.159686E+10 | 18713.34 | 08-MAY-04:12 | 3.30 |
June | 0.387850E+09 | 30748.12 | 22-JUN-05:01 | 12.38 |
July | 0.162298E+09 | 32393.63 | 03-JUL-05:01 | 11.78 |
August | 0.266099E+09 | 30856.67 | 04-AUG-05:01 | 12.20 |
September | 0.111599E+10 | 31394.20 | 18-SEP-05:02 | 9.50 |
October | 0.501222E+10 | 34658.01 | 30-OCT-05:01 | -0.1 |
November | 0.970088E+10 | 36345.76 | 24-NOV-06:05 | -3.8 |
December | 0.239703E+11 | 55386.68 | 11-DEC-05:31 | -18.3 |
Annual Sum or Average | 0.107308E+12 | |||
Minimum of Months | 0.162298E+09 | 18713.34 | -18.3 | |
Maximum of Months | 0.257062E+11 | 55425.62 | 12.38 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7252352.88 | 981.51 | 29-JAN-21:08 | -8.5 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.95 |
Annual Sum or Average | 7252352.88 | |||
Minimum of Months | 0.00 | 0.00 | -8.5 | |
Maximum of Months | 7252352.88 | 981.51 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.998036E+09 | 1276.35 | 29-JAN-18:10 | -6.2 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.95 |
Annual Sum or Average | 0.998036E+09 | |||
Minimum of Months | 0.00 | 0.00 | -6.2 | |
Maximum of Months | 0.998036E+09 | 1276.35 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.195559E+10 | 1358.21 | 24-JAN-00:15 | -11.1 |
February | 0.307908E+09 | 1304.10 | 06-FEB-03:11 | -14.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 37894747.51 | 837.42 | 12-MAY-02:63 | 9.90 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 16682020.92 | 971.29 | 04-SEP-09:00 | 16.70 |
October | 11107013.79 | 1069.88 | 29-OCT-22:13 | 1.83 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.95 |
Annual Sum or Average | 0.232918E+10 | |||
Minimum of Months | 0.00 | 0.00 | -14.3 | |
Maximum of Months | 0.195559E+10 | 1358.21 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -1.0 |
February | 0.105395E+10 | 18905.24 | 05-FEB-23:11 | -12.8 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 1650840.22 | 13843.72 | 31-MAY-23:51 | 17.10 |
June | 0.239955E+09 | 25861.57 | 25-JUN-01:01 | 12.80 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 1498246.45 | 23732.92 | 30-SEP-23:41 | 14.37 |
October | 0.283110E+09 | 38372.51 | 05-OCT-03:51 | 10.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.95 |
Annual Sum or Average | 0.158017E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.105395E+10 | 38372.51 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.278508E+11 | 29144.79 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.252627E+11 | 29144.79 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.300191E+11 | 29144.79 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.268132E+11 | 29144.79 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.289349E+11 | 29144.79 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.287951E+11 | 29144.79 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.269531E+11 | 29144.79 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.300191E+11 | 29144.79 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.268132E+11 | 29144.79 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.278508E+11 | 29144.79 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.275243E+11 | 29144.79 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.269531E+11 | 29144.79 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.333789E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.252627E+11 | 29144.79 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.300191E+11 | 29144.79 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.785272E+10 | 8217.58 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.712300E+10 | 8217.58 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.846411E+10 | 8217.58 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.756018E+10 | 8217.58 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.815842E+10 | 8217.58 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.811897E+10 | 8217.58 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.759962E+10 | 8217.58 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.846411E+10 | 8217.58 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.756018E+10 | 8217.58 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.785272E+10 | 8217.58 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.776069E+10 | 8217.58 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.759962E+10 | 8217.58 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.941143E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.712300E+10 | 8217.58 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.846411E+10 | 8217.58 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.289349E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.287951E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.275243E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.333789E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163648E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172081E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 360166.97 | 0.108267E+10 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.884001E+09 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 597208.48 | 0.502854E+09 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10914839.68 | 0.283769E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25008776.76 | 0.159307E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19488052.06 | 0.187050E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1405518.61 | 0.296520E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692111E+09 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.962585E+09 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177496E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57774562.57 | 0.101831E+11 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159307E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25008776.76 | 0.177496E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108662E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113957E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 255827.72 | 0.714395E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573907E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 833516.29 | 0.329451E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9396675.48 | 0.178384E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22372590.81 | 91211186.04 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17306835.93 | 0.106869E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1191032.58 | 0.189410E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452653E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624668E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116647E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51356478.80 | 0.665361E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91211186.04 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22372590.81 | 0.116647E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162650E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169663E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 360001.67 | 0.109255E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.868743E+09 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 249872.47 | 0.494003E+09 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10915278.85 | 0.270754E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26059812.60 | 0.150893E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18457088.26 | 0.180597E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1354191.07 | 0.298211E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690271E+09 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936856E+09 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174958E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57396244.92 | 0.100556E+11 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150893E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26059812.60 | 0.174958E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112422E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118778E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 240477.31 | 0.774167E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642911E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 176280.28 | 0.358425E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7612935.63 | 0.210035E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16647577.34 | 0.128964E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12116848.14 | 0.149859E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 863919.93 | 0.210352E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483123E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675224E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125018E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37658038.63 | 0.719524E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128964E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16647577.34 | 0.125018E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351821E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374070E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 993703.55 | 0.229282E+10 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181180E+10 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2869274.99 | 0.103967E+10 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40081267.95 | 0.585003E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66540484.29 | 0.328308E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56379831.20 | 0.389670E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4451280.12 | 0.591745E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138617E+10 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193979E+10 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372463E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171316E+09 | 0.213485E+11 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328308E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66540484.29 | 0.374070E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234609E+10 |
February | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249471E+10 |
March | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 444364.61 | 0.155676E+10 |
April | 0.688021E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124848E+10 |
May | 0.744847E+09 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1844370.40 | 0.735373E+09 |
June | 0.742030E+09 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20667097.93 | 0.400734E+09 |
July | 0.690839E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41667151.23 | 0.226348E+09 |
August | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34449811.34 | 0.268635E+09 |
September | 0.688021E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2505006.87 | 0.416000E+09 |
October | 0.715730E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.964541E+09 |
November | 0.708685E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131341E+10 |
December | 0.690839E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247993E+10 |
Annual Sum or Average | 0.858171E+10 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101578E+09 | 0.144510E+11 |
Minimum of Months | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226348E+09 |
Maximum of Months | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41667151.23 | 0.249471E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361606E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380272E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 750336.31 | 0.244748E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191429E+10 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 411944.82 | 0.110919E+10 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27098128.15 | 0.600040E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53913974.21 | 0.349858E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40141307.57 | 0.428904E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2946098.18 | 0.670185E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153454E+10 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204526E+10 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382701E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125262E+09 | 0.223455E+11 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349858E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53913974.21 | 0.382701E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237184E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252370E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 816602.70 | 0.160360E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128633E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 534272.69 | 0.760168E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22658169.67 | 0.437188E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40497012.77 | 0.258735E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32461128.11 | 0.302002E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2522765.00 | 0.426033E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6146.86 | 0.964786E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132329E+10 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251802E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99496097.80 | 0.147757E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258735E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40497012.77 | 0.252370E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428449E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457432E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1782081.26 | 0.270806E+10 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208446E+10 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4124997.10 | 0.118519E+10 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52829639.14 | 0.673160E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85699418.57 | 0.376147E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75235102.09 | 0.443739E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6938599.57 | 0.653219E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 465644.82 | 0.151489E+10 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217129E+10 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450751E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227075E+09 | 0.251765E+11 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376147E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85699418.57 | 0.457432E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285709E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304953E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 588679.03 | 0.181637E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143412E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1882328.17 | 0.861202E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21971048.27 | 0.482559E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47061640.80 | 0.276348E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40535230.63 | 0.323356E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3074414.70 | 0.475957E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105235E+10 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145860E+10 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300249E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115113E+09 | 0.170900E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276348E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47061640.80 | 0.304953E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434219E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460732E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 830623.14 | 0.283096E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219862E+10 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 672299.59 | 0.127538E+10 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37683536.28 | 0.696992E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68634227.20 | 0.402300E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53652087.12 | 0.494109E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3981433.72 | 0.757149E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168854E+10 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226799E+10 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455775E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165454E+09 | 0.261193E+11 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402300E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68634227.20 | 0.460732E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287700E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307292E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1008726.33 | 0.188368E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150558E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 567550.32 | 0.899863E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26340148.48 | 0.525958E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48128896.41 | 0.311959E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39583966.06 | 0.360901E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3207729.53 | 0.495688E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23040.62 | 0.109004E+10 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150250E+10 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303043E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118860E+09 | 0.175565E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311959E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48128896.41 | 0.307292E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.785272E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.712300E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.846411E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.756018E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.815842E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.811897E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.759962E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.846411E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.756018E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.785272E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.776069E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.759962E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.941143E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.712300E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.846411E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364998E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380795E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391455.16 | 0.241215E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195308E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 856072.23 | 0.109550E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17249995.09 | 0.614782E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40021083.22 | 0.348232E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33102757.09 | 0.420843E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1758932.13 | 0.659460E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153585E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213833E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396127E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93380294.92 | 0.225974E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348232E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40021083.22 | 0.396127E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606941E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640229E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 978823.49 | 0.410795E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332250E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2364151.35 | 0.189252E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40306442.48 | 0.105730E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73893008.77 | 0.593372E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65307931.94 | 0.721837E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3653037.58 | 0.112634E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259736E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357300E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655039E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186503E+09 | 0.380143E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593372E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73893008.77 | 0.655039E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613070E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652430E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408588E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331717E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201750E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12311472.61 | 0.115589E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42056409.05 | 0.676841E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30884705.15 | 0.764171E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1345895.57 | 0.113140E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241481E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329755E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648366E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86598482.38 | 0.379999E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676841E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42056409.05 | 0.652430E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 29144.79 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 29144.79 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 29144.79 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 29144.79 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 29144.79 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 29144.79 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 29144.79 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 29144.79 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 29144.79 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 29144.79 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 29144.79 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 29144.79 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3018.37 | 12-JAN-05:46 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3155.95 | 13-FEB-05:52 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 15-MAR-14:00 | 1830.68 | 02-MAR-00:51 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1720.58 | 16-APR-01:51 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.88 | 14-MAY-15:00 | 1026.54 | 29-MAY-14:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.11 | 17-JUN-17:02 | 851.14 | 13-JUN-02:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.12 | 21-JUL-02:40 | 642.85 | 06-JUL-01:51 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.18 | 13-AUG-13:00 | 398.28 | 30-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.06 | 16-SEP-17:02 | 748.98 | 29-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 967.51 | 08-OCT-09:00 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1723.48 | 17-NOV-01:51 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 2848.80 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.28 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 314.18 | 3155.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2012.26 | 12-JAN-05:50 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2103.98 | 13-FEB-05:51 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.22 | 15-MAR-14:00 | 1225.49 | 26-MAR-10:00 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1126.59 | 16-APR-06:52 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.93 | 14-MAY-15:00 | 724.83 | 29-MAY-14:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.28 | 17-JUN-17:10 | 558.26 | 13-JUN-02:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.76 | 21-JUL-02:20 | 406.91 | 06-JUL-01:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.85 | 13-AUG-12:50 | 241.21 | 30-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.88 | 16-SEP-17:02 | 482.42 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 668.94 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1107.08 | 17-NOV-01:51 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1852.12 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.21 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 282.85 | 2103.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3018.41 | 12-JAN-05:50 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3155.93 | 13-FEB-05:57 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.30 | 15-MAR-14:00 | 1968.45 | 26-MAR-13:00 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1629.97 | 16-APR-01:51 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.64 | 14-MAY-15:00 | 1082.08 | 29-MAY-14:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.10 | 17-JUN-17:02 | 844.65 | 13-JUN-02:51 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 302.59 | 21-JUL-02:40 | 626.66 | 06-JUL-01:51 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.35 | 13-AUG-14:45 | 383.00 | 30-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.37 | 16-SEP-17:50 | 710.89 | 29-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 943.95 | 08-OCT-09:00 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1655.08 | 17-NOV-01:51 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 2794.73 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.00 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 302.59 | 3155.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2015.01 | 12-JAN-05:51 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2103.97 | 13-FEB-05:53 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.22 | 15-MAR-14:00 | 1338.97 | 02-MAR-00:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1247.88 | 16-APR-01:51 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.91 | 14-MAY-15:40 | 762.40 | 29-MAY-14:10 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.35 | 18-JUN-11:10 | 618.60 | 13-JUN-02:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.90 | 21-JUL-03:10 | 501.25 | 06-JUL-01:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.74 | 13-AUG-12:50 | 364.94 | 27-AUG-16:20 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.46 | 16-SEP-12:40 | 522.48 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 682.45 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1219.80 | 17-NOV-01:51 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1966.46 | 09-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.94 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 253.74 | 2103.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 7150.02 | 12-JAN-05:59 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 7317.11 | 13-FEB-05:44 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.11 | 15-MAR-14:00 | 4090.52 | 02-MAR-05:10 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3348.71 | 04-APR-21:02 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 460.78 | 14-MAY-14:50 | 2068.93 | 29-MAY-14:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 462.05 | 17-JUN-17:02 | 1793.51 | 13-JUN-02:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 648.61 | 21-JUL-03:10 | 1295.98 | 06-JUL-01:51 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 961.61 | 13-AUG-13:00 | 821.61 | 30-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 304.57 | 16-SEP-17:02 | 1483.68 | 29-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 1870.29 | 30-OCT-04:51 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 3532.98 | 17-NOV-05:53 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 6164.75 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 821.61 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 961.61 | 7317.11 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4766.71 | 12-JAN-05:56 |
February | 1239.33 | 01-FEB-08:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 4878.15 | 13-FEB-05:45 |
March | 1239.33 | 01-MAR-08:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.13 | 15-MAR-14:10 | 2727.07 | 02-MAR-05:05 |
April | 1239.33 | 03-APR-07:10 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2244.01 | 16-APR-06:52 |
May | 1239.33 | 01-MAY-07:10 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.57 | 14-MAY-14:50 | 1584.57 | 29-MAY-14:00 |
June | 1239.33 | 01-JUN-07:10 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.62 | 17-JUN-17:02 | 1201.25 | 13-JUN-02:51 |
July | 1239.33 | 03-JUL-07:10 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 492.46 | 21-JUL-03:10 | 853.38 | 06-JUL-01:51 |
August | 1239.33 | 01-AUG-07:10 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 658.50 | 13-AUG-13:20 | 530.72 | 30-AUG-21:10 |
September | 1239.33 | 01-SEP-07:10 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.63 | 16-SEP-17:02 | 981.56 | 29-SEP-04:00 |
October | 1239.33 | 02-OCT-07:10 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 1317.62 | 08-OCT-09:00 |
November | 1239.33 | 01-NOV-07:10 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2366.59 | 17-NOV-05:53 |
December | 1239.33 | 01-DEC-08:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 4063.21 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.72 | |||||
Maximum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 658.50 | 4878.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 7150.12 | 12-JAN-06:00 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 7317.05 | 13-FEB-05:41 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.04 | 15-MAR-14:00 | 4374.73 | 26-MAR-13:00 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3347.63 | 04-APR-21:02 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.74 | 14-MAY-14:50 | 2333.44 | 29-MAY-14:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 451.77 | 17-JUN-17:02 | 1819.67 | 13-JUN-02:51 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 638.18 | 21-JUL-03:10 | 1309.03 | 06-JUL-01:51 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 649.72 | 13-AUG-13:14 | 830.94 | 30-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.96 | 16-SEP-17:20 | 1492.93 | 29-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2114.30 | 09-OCT-11:50 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 3551.08 | 17-NOV-05:53 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 6228.28 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 830.94 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 649.72 | 7317.05 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4766.74 | 12-JAN-05:57 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 4878.06 | 13-FEB-05:50 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.07 | 15-MAR-14:00 | 2868.55 | 25-MAR-17:10 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2257.22 | 16-APR-01:51 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.95 | 14-MAY-13:30 | 1676.91 | 29-MAY-15:10 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 348.16 | 18-JUN-11:20 | 1237.23 | 13-JUN-02:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 499.56 | 21-JUL-03:10 | 909.95 | 06-JUL-01:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 695.77 | 13-AUG-12:40 | 750.10 | 27-AUG-17:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.45 | 16-SEP-12:40 | 984.01 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.74 | 22-OCT-12:40 | 1279.44 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2358.05 | 17-NOV-05:53 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 4148.86 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 750.10 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 695.77 | 4878.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 8860.22 | 12-JAN-05:48 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 9258.07 | 13-FEB-05:51 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.51 | 15-MAR-14:00 | 5108.22 | 02-MAR-05:06 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4149.45 | 04-APR-21:02 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 664.44 | 14-MAY-15:00 | 2492.17 | 29-MAY-14:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 614.35 | 25-JUN-15:50 | 2106.82 | 13-JUN-02:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 895.54 | 21-JUL-03:10 | 1470.91 | 06-JUL-01:51 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1309.60 | 13-AUG-12:50 | 957.09 | 30-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.20 | 16-SEP-17:02 | 1756.18 | 29-SEP-04:14 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.07 | 22-OCT-12:50 | 2356.45 | 30-OCT-04:58 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 4399.29 | 17-NOV-05:58 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 7365.07 | 09-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 957.09 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1309.60 | 9258.07 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 5906.81 | 12-JAN-05:44 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 6172.43 | 13-FEB-05:55 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.34 | 15-MAR-14:00 | 3405.45 | 02-MAR-05:10 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2764.59 | 04-APR-21:02 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.93 | 14-MAY-15:00 | 1932.28 | 29-MAY-14:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 401.60 | 17-JUN-17:50 | 1419.05 | 13-JUN-02:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 604.54 | 21-JUL-03:10 | 980.10 | 06-JUL-01:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 768.18 | 13-AUG-12:50 | 635.83 | 30-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.79 | 16-SEP-17:50 | 1170.52 | 29-SEP-04:14 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 1570.95 | 30-OCT-04:53 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2932.91 | 17-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 4912.05 | 09-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 635.83 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 768.18 | 6172.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 8860.29 | 12-JAN-05:43 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 9258.81 | 13-FEB-05:55 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.50 | 15-MAR-14:00 | 5108.00 | 02-MAR-05:10 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4147.70 | 04-APR-21:02 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.49 | 14-MAY-15:00 | 2813.82 | 29-MAY-14:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 598.52 | 17-JUN-17:50 | 2137.83 | 13-JUN-02:51 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 887.09 | 21-JUL-03:10 | 1486.40 | 06-JUL-01:51 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 869.63 | 13-AUG-12:50 | 1041.82 | 20-AUG-14:40 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.26 | 16-SEP-17:50 | 1753.56 | 29-SEP-04:14 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2356.45 | 30-OCT-04:53 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 4399.29 | 17-NOV-06:00 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 7396.98 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1041.82 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 887.09 | 9258.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 5906.71 | 12-JAN-05:49 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 6172.47 | 13-FEB-05:51 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.40 | 15-MAR-12:00 | 3442.22 | 25-MAR-17:10 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2769.42 | 04-APR-21:02 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.62 | 14-MAY-15:40 | 2093.49 | 29-MAY-15:20 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 403.80 | 18-JUN-11:20 | 1460.76 | 13-JUN-02:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 635.51 | 21-JUL-03:10 | 1047.73 | 06-JUL-01:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 884.51 | 13-AUG-12:50 | 965.93 | 27-AUG-17:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.67 | 16-SEP-12:30 | 1158.25 | 29-SEP-04:14 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.48 | 22-OCT-12:05 | 1570.95 | 30-OCT-04:51 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2932.95 | 17-NOV-05:58 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 4975.65 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 965.93 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 884.51 | 6172.47 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 8217.58 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 8217.58 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 8217.58 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 8217.58 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 8217.58 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 8217.58 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 8217.58 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 8217.58 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 8217.58 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 8217.58 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 8217.58 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 8217.58 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 8217.58 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 8217.58 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 6494.71 | 12-JAN-01:52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 6403.39 | 13-FEB-05:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.22 | 15-MAR-14:00 | 4229.64 | 02-MAR-00:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3940.67 | 16-APR-01:51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.64 | 14-MAY-14:53 | 1889.91 | 29-MAY-14:16 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.02 | 17-JUN-17:02 | 1852.24 | 13-JUN-02:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.70 | 21-JUL-02:40 | 1374.60 | 06-JUL-01:51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 658.19 | 13-AUG-13:00 | 859.32 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.92 | 16-SEP-17:02 | 1689.76 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2146.47 | 08-OCT-08:51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 3878.57 | 17-NOV-01:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 6339.19 | 09-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 859.32 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 658.19 | 6494.71 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 10898.97 | 12-JAN-01:52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 10829.71 | 13-FEB-05:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.67 | 15-MAR-14:00 | 7100.67 | 02-MAR-00:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 6623.33 | 16-APR-01:51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.09 | 14-MAY-15:00 | 3109.08 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 640.37 | 17-JUN-17:02 | 3201.23 | 13-JUN-02:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 692.24 | 21-JUL-02:52 | 2342.20 | 06-JUL-01:51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1323.96 | 13-AUG-13:00 | 1494.19 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.76 | 16-SEP-17:02 | 2906.02 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 3620.27 | 08-OCT-08:51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 6529.90 | 17-NOV-01:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 10818.73 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1494.19 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1323.96 | 10898.97 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 11347.36 | 12-JAN-05:50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 11781.64 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 6524.53 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 6027.61 | 16-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 4597.59 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.22 | 17-JUN-17:02 | 3280.06 | 13-JUN-02:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.43 | 21-JUL-01:52 | 2279.77 | 06-JUL-01:51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 862.92 | 13-AUG-13:00 | 1637.76 | 20-AUG-14:42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.04 | 16-SEP-17:02 | 2599.14 | 29-SEP-04:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 3089.27 | 19-OCT-22:51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 5899.96 | 17-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 11576.25 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1637.76 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 862.92 | 11781.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 129115.16 | 17-JAN-06:01 | 16157.03 | 29144.79 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 125735.94 | 18-FEB-06:01 | 14361.80 | 25906.48 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 114163.05 | 17-MAR-12:44 | 170546.39 | 291447.90 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 113772.35 | 10-APR-04:12 | 0.00 | 19429.86 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 125653.24 | 19-MAY-05:02 | 8976.13 | 16191.55 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 134567.07 | 03-JUN-04:11 | 0.00 | 16191.55 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 121431.93 | 03-JUL-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 116042.75 | 03-AUG-04:12 | 0.00 | 19429.86 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 134024.42 | 18-SEP-04:22 | 0.00 | 19429.86 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 139418.51 | 02-OCT-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 136540.55 | 01-NOV-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 115221.56 | 26-DEC-04:01 | 0.00 | 16191.55 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 113772.35 | 0.00 | 16191.55 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 139418.51 | 170546.39 | 291447.90 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 36410.81 | 20-JAN-17:00 | 15316.26 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 95961.27 | 23-FEB-06:01 | 12897.91 | 23265.84 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 111081.99 | 17-MAR-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 110172.02 | 20-APR-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 111195.09 | 30-MAY-04:12 | 0.00 | 14541.15 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 116163.63 | 19-JUN-04:12 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 118184.40 | 10-JUL-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 118885.60 | 21-AUG-04:11 | 0.00 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 118023.82 | 18-SEP-04:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 112449.94 | 02-OCT-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 114174.33 | 06-NOV-05:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 106219.09 | 01-DEC-06:01 | 12897.91 | 23265.84 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 36410.81 | 0.00 | 14541.15 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 118885.60 | 15316.26 | 29082.30 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 26790.26 | 20-JAN-17:00 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28418.83 | 17-FEB-16:51 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 100302.78 | 17-MAR-05:01 | 12897.91 | 23265.84 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 94614.66 | 21-APR-05:02 | 8061.19 | 14541.15 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 102074.00 | 18-MAY-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 106564.96 | 30-JUN-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 105822.35 | 25-JUL-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 106693.24 | 09-AUG-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 105885.74 | 18-SEP-04:12 | 0.00 | 17449.38 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 101566.68 | 13-OCT-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 91173.48 | 01-NOV-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 32111.53 | 01-DEC-16:53 | 107213.85 | 183218.49 | 120445.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 26790.26 | 0.00 | 14541.15 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 106693.24 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 20856.40 | 11-JAN-17:00 | 30632.53 | 52348.14 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21471.79 | 28-FEB-17:00 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 103265.59 | 16-MAR-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 45228.11 | 20-APR-15:53 | 45948.79 | 78522.21 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 105315.75 | 24-MAY-05:02 | 8061.19 | 14541.15 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 111970.53 | 21-JUN-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 114831.44 | 17-JUL-03:01 | 0.00 | 10178.80 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 111553.48 | 11-AUG-04:12 | 0.00 | 17449.38 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 102866.38 | 14-SEP-05:02 | 9673.43 | 17449.38 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 42753.61 | 12-OCT-15:42 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 26259.00 | 01-NOV-15:53 | 45948.79 | 78522.21 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21790.56 | 01-DEC-17:00 | 107213.85 | 183218.49 | 120445.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 20856.40 | 0.00 | 10178.80 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 114831.44 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3377.57 | 11-JAN-16:00 | 3846.22 | 6572.83 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.92 |
February | 3403.19 | 22-FEB-16:00 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.90 |
March | 9164.68 | 15-MAR-14:00 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 0.00 |
April | 7868.47 | 07-APR-13:30 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.68 |
May | 9332.54 | 23-MAY-14:40 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 |
June | 15693.84 | 17-JUN-05:01 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.34 |
July | 14161.29 | 17-JUL-04:12 | 0.00 | 2190.94 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.98 |
August | 14957.14 | 14-AUG-04:11 | 0.00 | 2556.10 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.24 |
September | 9478.21 | 13-SEP-13:30 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.95 |
October | 6682.39 | 12-OCT-13:53 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.67 |
November | 5194.92 | 27-NOV-05:11 | 0.00 | 3651.57 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.38 |
December | 4390.57 | 01-DEC-06:02 | 1619.46 | 2921.26 | 7681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3377.57 | 0.00 | 2190.94 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15693.84 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 390.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3660.06 | 06-JAN-10:25 | 2591.66 | 4235.78 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.15 |
February | 5127.10 | 28-FEB-09:33 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.62 |
March | 8942.65 | 21-MAR-09:01 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.86 |
April | 13123.15 | 24-APR-08:23 | 7435.95 | 12707.35 | 8354.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.27 |
May | 16398.35 | 29-MAY-10:12 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.10 |
June | 29092.05 | 11-JUN-09:12 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.17 |
July | 29153.85 | 04-JUL-07:01 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.60 |
August | 21169.66 | 20-AUG-09:32 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.35 |
September | 19303.15 | 04-SEP-09:02 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.64 |
October | 12849.87 | 09-OCT-08:25 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.98 |
November | 6228.99 | 03-NOV-09:01 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.99 |
December | 4851.11 | 21-DEC-06:02 | 1043.64 | 1882.57 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3660.06 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.15 | |
Maximum of Months | 29153.85 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14392.51 | 12-JAN-13:30 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 725.57 |
February | 17573.30 | 28-FEB-13:21 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.49 |
March | 21223.88 | 15-MAR-13:30 | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 | 0.00 |
April | 23548.76 | 23-APR-13:11 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.42 |
May | 15134.98 | 10-MAY-12:40 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.81 | 0.00 |
June | 30978.06 | 18-JUN-14:21 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.85 |
July | 22854.62 | 30-JUL-12:23 | 404.87 | 730.33 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.48 |
August | 31337.30 | 13-AUG-15:21 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 197.22 | 0.00 |
September | 35396.03 | 10-SEP-13:02 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.79 |
October | 24968.26 | 11-OCT-12:30 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.10 |
November | 19196.11 | 03-NOV-12:21 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.35 |
December | 14719.31 | 04-DEC-11:35 | 7692.61 | 13145.95 | 8642.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14392.51 | 404.87 | 730.33 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35396.03 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 197.22 | 725.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5435.57 | 15-JAN-14:38 | 326.14 | 588.30 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.55 |
February | 8904.89 | 28-FEB-16:21 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.96 |
March | 18022.03 | 16-MAR-04:11 | 0.00 | 1647.25 | 3363.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.51 |
April | 24194.36 | 02-APR-18:01 | 0.00 | 823.62 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 760.99 |
May | 28126.64 | 07-MAY-16:52 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.24 |
June | 39276.00 | 11-JUN-16:41 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.42 |
July | 36703.14 | 02-JUL-17:01 | 0.00 | 823.62 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.80 |
August | 35146.60 | 13-AUG-15:21 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 95.80 | 0.00 |
September | 35053.56 | 10-SEP-15:41 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.80 |
October | 14710.51 | 11-OCT-16:00 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 |
November | 8920.90 | 15-NOV-14:52 | 12958.30 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.32 |
December | 7131.29 | 01-DEC-06:01 | 1043.64 | 1882.57 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5435.57 | 0.00 | 588.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39276.00 | 12958.30 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 95.80 | 760.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3733.75 | 27-JAN-06:04 | 1417.03 | 2556.10 | 6721.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.16 |
February | 3693.24 | 18-FEB-17:01 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.15 |
March | 7507.04 | 15-MAR-14:40 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 35.66 | 0.00 |
April | 5786.74 | 07-APR-14:10 | 3846.22 | 6572.83 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.25 |
May | 8373.44 | 23-MAY-14:40 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 |
June | 11104.25 | 27-JUN-13:20 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 191.73 | 0.00 |
July | 17810.45 | 21-JUL-03:01 | 0.00 | 1278.05 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 360.70 | 0.00 |
August | 11286.24 | 09-AUG-14:40 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 114.22 | 0.00 |
September | 8443.07 | 15-SEP-14:00 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 18.85 | 0.00 |
October | 6681.02 | 11-OCT-12:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.07 |
November | 4915.18 | 16-NOV-15:02 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.04 |
December | 4105.40 | 01-DEC-13:10 | 7692.44 | 13145.66 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3693.24 | 0.00 | 1278.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17810.45 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 360.70 | 577.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4162.33 | 06-JAN-11:02 | 4957.30 | 8471.56 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.56 |
February | 12311.46 | 28-FEB-11:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 381.13 |
March | 17169.87 | 21-MAR-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.61 |
April | 14823.71 | 20-APR-12:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.64 |
May | 21595.32 | 21-MAY-09:02 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1006.40 |
June | 23304.48 | 06-JUN-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.47 |
July | 30265.76 | 04-JUL-09:22 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.59 |
August | 30005.46 | 06-AUG-09:12 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.45 |
September | 27996.94 | 04-SEP-09:32 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.95 |
October | 19561.95 | 11-OCT-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.76 |
November | 14049.16 | 03-NOV-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.86 |
December | 4493.92 | 01-DEC-13:02 | 4957.30 | 8471.56 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4162.33 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.56 | |
Maximum of Months | 30265.76 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1006.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14493.72 | 12-JAN-13:40 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1659.29 |
February | 19300.22 | 28-FEB-13:31 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 700.27 |
March | 21046.83 | 15-MAR-13:30 | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 42.17 | 0.00 |
April | 20000.01 | 09-APR-14:23 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.41 |
May | 16000.61 | 14-MAY-14:01 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.11 |
June | 17065.94 | 27-JUN-13:00 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 240.90 | 0.00 |
July | 21778.93 | 30-JUL-12:43 | 404.87 | 730.33 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.59 |
August | 34754.68 | 06-AUG-14:31 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 | 0.00 |
September | 35631.96 | 04-SEP-13:32 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 870.88 |
October | 26726.91 | 31-OCT-13:20 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.22 |
November | 20452.61 | 03-NOV-12:22 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.23 |
December | 12861.54 | 16-DEC-13:23 | 607.31 | 1643.24 | 2520.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12861.54 | 404.87 | 730.33 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35631.96 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 240.90 | 1659.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4080.84 | 06-JAN-15:40 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.37 |
February | 6358.96 | 28-FEB-16:21 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.97 |
March | 9300.27 | 21-MAR-15:52 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.07 |
April | 16760.71 | 30-APR-16:12 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 655.61 |
May | 22970.69 | 07-MAY-16:32 | 326.14 | 588.30 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 684.28 |
June | 33676.74 | 04-JUN-17:01 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 593.35 |
July | 33833.37 | 02-JUL-17:21 | 0.00 | 823.62 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.89 |
August | 32560.39 | 06-AUG-16:31 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 | 0.00 |
September | 31778.51 | 04-SEP-17:32 | 0.00 | 705.96 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.93 |
October | 12809.94 | 11-OCT-16:00 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.84 |
November | 5499.19 | 15-NOV-15:30 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.58 |
December | 4269.87 | 04-DEC-15:50 | 4957.30 | 8471.56 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4080.84 | 0.00 | 588.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33833.37 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 | 684.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5188.19 | 02-JAN-06:04 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.67 |
February | 5207.92 | 02-FEB-06:04 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.07 |
March | 8313.40 | 16-MAR-05:01 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.36 |
April | 7046.24 | 09-APR-14:11 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.82 |
May | 9021.37 | 24-MAY-05:02 | 1012.16 | 1825.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.66 |
June | 12763.02 | 12-JUN-14:50 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 226.50 | 0.00 |
July | 25650.63 | 21-JUL-03:01 | 0.00 | 1278.05 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 470.36 | 0.00 |
August | 12547.77 | 09-AUG-15:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 134.62 | 0.00 |
September | 10045.18 | 17-SEP-14:31 | 708.51 | 1278.05 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.02 |
October | 6723.00 | 12-OCT-15:30 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.89 |
November | 5414.04 | 16-NOV-15:00 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.26 |
December | 5282.80 | 21-DEC-06:04 | 1619.46 | 2921.26 | 7681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5188.19 | 0.00 | 1278.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25650.63 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 470.36 | 516.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3525.26 | 02-JAN-06:04 | 1304.55 | 2353.21 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.96 |
February | 4056.56 | 28-FEB-10:20 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.71 |
March | 6864.39 | 14-MAR-10:50 | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.56 |
April | 10239.64 | 24-APR-09:28 | 5183.32 | 8471.56 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.62 |
May | 14368.80 | 31-MAY-09:10 | 2591.66 | 4235.78 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.27 |
June | 30569.53 | 11-JUN-10:02 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.21 |
July | 30348.59 | 04-JUL-09:02 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.30 |
August | 30467.59 | 06-AUG-10:02 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.39 |
September | 11662.49 | 21-SEP-09:50 | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.68 |
October | 8274.45 | 11-OCT-09:42 | 6479.15 | 10589.46 | 6961.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.19 |
November | 4208.88 | 03-NOV-10:00 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.27 |
December | 3562.44 | 21-DEC-06:04 | 1043.64 | 1882.57 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3525.26 | 391.37 | 705.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.68 | |
Maximum of Months | 30569.53 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11575.03 | 12-JAN-13:50 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2007.86 |
February | 18356.33 | 28-FEB-13:41 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 884.38 |
March | 21502.46 | 15-MAR-13:30 | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 48.40 | 0.00 |
April | 17876.39 | 19-APR-13:43 | 8043.34 | 13145.95 | 8642.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.48 |
May | 16232.78 | 26-MAY-13:30 | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.86 |
June | 18742.70 | 12-JUN-13:20 | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 293.47 | 0.00 |
July | 26713.42 | 21-JUL-03:01 | 0.00 | 1278.08 | 5219.01 | 0.00 | 0.00 | 0.00 | 0.00 | 461.09 | 0.00 |
August | 43565.60 | 06-AUG-12:42 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.54 |
September | 45328.56 | 10-SEP-14:32 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 865.84 |
October | 26124.21 | 11-OCT-12:30 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.63 |
November | 18128.99 | 03-NOV-12:41 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.44 |
December | 10318.10 | 16-DEC-13:23 | 607.31 | 1643.24 | 2520.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10318.10 | 0.00 | 1095.50 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45328.56 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 461.09 | 2007.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4106.31 | 19-JAN-06:04 | 1043.64 | 1882.57 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.16 |
February | 6108.48 | 28-FEB-16:28 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.79 |
March | 9206.20 | 21-MAR-15:52 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.25 |
April | 14001.21 | 19-APR-15:55 | 4957.30 | 8471.56 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.09 |
May | 21920.95 | 07-MAY-17:12 | 0.00 | 588.30 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 883.14 |
June | 39502.27 | 11-JUN-16:41 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.23 |
July | 36802.12 | 02-JUL-17:21 | 0.00 | 823.62 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.43 |
August | 38322.38 | 06-AUG-16:41 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.58 |
September | 24541.63 | 10-SEP-17:12 | 0.00 | 705.96 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 601.61 |
October | 13283.47 | 11-OCT-16:00 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.96 |
November | 5610.77 | 15-NOV-15:30 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.07 |
December | 4249.95 | 04-DEC-15:43 | 4957.30 | 8471.56 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4106.31 | 0.00 | 588.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.96 | |
Maximum of Months | 39502.27 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 883.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12331.17 | 04-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1359.84 |
February | 14584.12 | 06-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4108.60 |
March | 10935.22 | 06-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1873.38 |
April | 8639.33 | 10-APR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.22 |
May | 9396.64 | 30-MAY-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.09 |
June | 9494.59 | 13-JUN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.77 |
July | 10925.46 | 31-JUL-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.70 |
August | 10518.23 | 21-AUG-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.70 |
September | 10269.20 | 19-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.47 |
October | 9225.68 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.77 |
November | 9329.65 | 25-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.79 |
December | 11934.37 | 11-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1530.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8639.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.70 | |
Maximum of Months | 14584.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4108.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17578.25 | 28-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4635.92 |
February | 18897.76 | 05-FEB-04:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2768.18 |
March | 20483.40 | 04-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2799.18 |
April | 14546.04 | 17-APR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1436.50 |
May | 9043.49 | 27-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.68 |
June | 9252.90 | 10-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.96 |
July | 9571.30 | 28-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.71 |
August | 9825.95 | 11-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.40 |
September | 9930.86 | 19-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.65 |
October | 14261.83 | 24-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1325.50 |
November | 17272.91 | 24-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1775.24 |
December | 17758.85 | 08-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4277.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9043.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.65 | |
Maximum of Months | 20483.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4635.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 492.93 | 15-JAN-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2786.02 |
February | 2583.92 | 28-FEB-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1272.82 |
March | 20379.70 | 15-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
April | 18877.30 | 19-APR-14:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.37 |
May | 25686.80 | 31-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.44 |
June | 33019.32 | 27-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.10 | 0.00 |
July | 33461.14 | 21-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.96 | 0.00 |
August | 32904.89 | 09-AUG-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.15 | 0.00 |
September | 26159.45 | 21-SEP-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.93 |
October | 16324.70 | 11-OCT-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.60 |
November | 5984.59 | 16-NOV-13:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.48 |
December | 1336.22 | 01-DEC-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 791.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 492.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33461.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.96 | 2786.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2054.21 | 12-JAN-16:35 | 444.28 | 1457.57 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4276.58 | 28-FEB-16:51 | 2221.41 | 7287.84 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6691.58 | 31-MAR-23:57 | 0.00 | 404.88 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8085.45 | 24-APR-17:55 | 93.53 | 971.71 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3430.64 | 31-MAY-23:51 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5350.87 | 30-JUN-23:51 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7224.86 | 31-JUL-23:04 | 0.00 | 202.44 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8419.43 | 02-AUG-18:40 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3073.43 | 30-SEP-23:51 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4902.65 | 31-OCT-23:52 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5998.06 | 24-NOV-16:11 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7751.45 | 04-DEC-16:12 | 888.56 | 2915.14 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2054.21 | 0.00 | 202.44 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8419.43 | 2221.41 | 7287.84 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1726.66 | 12-JAN-16:35 | 444.28 | 1457.57 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3957.40 | 28-FEB-16:51 | 2221.41 | 7287.84 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6073.95 | 31-MAR-23:27 | 0.00 | 121.46 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7808.21 | 24-APR-17:55 | 93.53 | 971.71 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3214.80 | 31-MAY-23:31 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5109.61 | 30-JUN-23:31 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6984.30 | 31-JUL-24:00 | 0.00 | 80.98 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8101.48 | 02-AUG-18:40 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2510.45 | 30-SEP-23:51 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4305.12 | 31-OCT-23:22 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5603.75 | 15-NOV-16:21 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7063.29 | 04-DEC-16:23 | 888.56 | 2915.14 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1726.66 | 0.00 | 80.98 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8101.48 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1431.17 | 12-JAN-16:35 | 444.28 | 1457.57 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3894.51 | 28-FEB-16:51 | 2221.41 | 7287.84 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5800.86 | 21-MAR-17:32 | 233.83 | 2429.28 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7829.45 | 24-APR-17:55 | 93.53 | 971.71 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3006.04 | 31-MAY-23:12 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4929.93 | 30-JUN-23:12 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6925.38 | 31-JUL-23:38 | 0.00 | 161.95 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8192.73 | 02-AUG-18:40 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2465.16 | 11-SEP-17:50 | 23.38 | 242.93 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4298.60 | 11-OCT-17:00 | 70.15 | 404.88 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5443.26 | 15-NOV-16:11 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6773.29 | 04-DEC-16:12 | 888.56 | 2915.14 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1431.17 | 0.00 | 161.95 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8192.73 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 95367.34 | 23-JAN-22:01 | 2277.80 | 8217.58 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 485896.80 | 01-FEB-00:12 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 512102.54 | 17-MAR-12:42 | 48086.79 | 82175.84 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 490062.06 | 27-APR-19:13 | 5061.77 | 18261.30 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 436195.70 | 31-MAY-23:56 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 491837.34 | 25-JUN-02:52 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 485206.96 | 06-JUL-07:42 | 48086.79 | 82175.84 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 478565.67 | 02-AUG-22:25 | 2530.88 | 4565.32 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 464571.06 | 30-SEP-23:52 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 517788.58 | 31-OCT-23:52 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 517916.80 | 01-NOV-00:02 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 504259.28 | 13-DEC-17:04 | 15185.30 | 45653.24 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 95367.34 | 0.00 | 4565.32 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 517916.80 | 48086.79 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.190380E+13 | 1426211.86 | 13-JAN-16:00 | 0.118263E+13 | 2269990.72 | 02-JAN-05:10 |
February | 0.210683E+13 | 1527711.75 | 17-FEB-16:00 | 0.103845E+13 | 2086474.84 | 06-FEB-07:19 |
March | 0.286047E+13 | 2062380.80 | 15-MAR-14:30 | 0.471035E+12 | 1643834.57 | 06-MAR-06:10 |
April | 0.303178E+13 | 2004846.67 | 07-APR-14:09 | 0.154857E+12 | 1008330.61 | 17-APR-04:10 |
May | 0.198182E+13 | 1801579.67 | 10-MAY-15:39 | 0.351863E+11 | 696960.18 | 08-MAY-05:10 |
June | 0.252280E+13 | 2060467.49 | 27-JUN-15:20 | 0.460078E+10 | 251512.26 | 14-JUN-05:10 |
July | 0.305903E+13 | 2236402.77 | 19-JUL-15:09 | 0.291195E+09 | 12420.45 | 07-JUL-05:30 |
August | 0.348690E+13 | 2356626.12 | 18-AUG-15:09 | 0.189032E+10 | 133576.50 | 31-AUG-05:40 |
September | 0.196399E+13 | 1872383.52 | 21-SEP-15:50 | 0.227508E+11 | 537514.46 | 30-SEP-05:10 |
October | 0.229346E+13 | 1834071.02 | 11-OCT-15:30 | 0.139830E+12 | 1004920.51 | 30-OCT-05:10 |
November | 0.269659E+13 | 1824853.19 | 03-NOV-14:09 | 0.305807E+12 | 1030762.78 | 24-NOV-06:10 |
December | 0.318655E+13 | 1928829.57 | 08-DEC-16:40 | 0.965721E+12 | 2110586.20 | 11-DEC-07:10 |
Annual Sum or Average | 0.310940E+14 | 0.432305E+13 | ||||
Minimum of Months | 0.190380E+13 | 1426211.86 | 0.291195E+09 | 12420.45 | ||
Maximum of Months | 0.348690E+13 | 2356626.12 | 0.118263E+13 | 2269990.72 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.468149E+12 | 0.105698E+12 | 0.766053E+12 | 0.218140E+12 | 0.176270E+12 | 0.145950E+11 | 0.00 | 0.892760E+10 | 0.00 | 0.103586E+12 | 0.00 | 0.423778E+11 | 0.00 |
February | 0.424646E+12 | 0.882036E+11 | 0.978954E+12 | 0.199667E+12 | 0.179258E+12 | 0.337617E+11 | 0.00 | 0.575343E+11 | 832249.46 | 0.105750E+12 | 0.00 | 0.390504E+11 | 0.00 |
March | 0.504598E+12 | 0.876268E+11 | 0.141687E+13 | 0.230864E+12 | 0.216183E+12 | 0.108754E+12 | 0.00 | 0.107389E+12 | 0.165871E+10 | 0.141230E+12 | 0.00 | 0.452905E+11 | 0.00 |
April | 0.450709E+12 | 0.746693E+11 | 0.165903E+13 | 0.216144E+12 | 0.236987E+12 | 0.882188E+11 | 0.00 | 0.109158E+12 | 0.106838E+09 | 0.157243E+12 | 0.00 | 0.395167E+11 | 0.00 |
May | 0.486374E+12 | 0.682482E+11 | 0.774844E+12 | 0.224502E+12 | 0.203124E+12 | 0.423642E+11 | 0.00 | 0.816508E+11 | 0.254942E+10 | 0.582998E+11 | 0.00 | 0.398648E+11 | 0.00 |
June | 0.484022E+12 | 0.617502E+11 | 0.106252E+13 | 0.222585E+12 | 0.245544E+12 | 0.914784E+11 | 0.00 | 0.270508E+12 | 0.291020E+11 | 0.181545E+11 | 0.00 | 0.371344E+11 | 0.00 |
July | 0.453060E+12 | 0.655183E+11 | 0.139340E+13 | 0.218061E+12 | 0.277535E+12 | 0.135455E+12 | 0.00 | 0.419397E+12 | 0.616341E+11 | 0.128527E+10 | 0.00 | 0.336767E+11 | 0.00 |
August | 0.504598E+12 | 0.731697E+11 | 0.173200E+13 | 0.230864E+12 | 0.309736E+12 | 0.136935E+12 | 0.00 | 0.413591E+12 | 0.486442E+11 | 0.119527E+10 | 0.00 | 0.361622E+11 | 0.00 |
September | 0.450709E+12 | 0.804367E+11 | 0.740713E+12 | 0.216143E+12 | 0.209700E+12 | 0.622683E+11 | 0.00 | 0.149197E+12 | 0.135411E+11 | 0.787148E+10 | 0.00 | 0.334062E+11 | 0.00 |
October | 0.468149E+12 | 0.935096E+11 | 0.108340E+13 | 0.218140E+12 | 0.200935E+12 | 0.446819E+11 | 0.00 | 0.928006E+11 | 0.106720E+10 | 0.546455E+11 | 0.00 | 0.361264E+11 | 0.00 |
November | 0.462662E+12 | 0.995078E+11 | 0.135889E+13 | 0.209941E+12 | 0.200199E+12 | 0.101086E+12 | 0.00 | 0.939339E+11 | 0.139195E+09 | 0.132570E+12 | 0.00 | 0.376561E+11 | 0.00 |
December | 0.453060E+12 | 0.108121E+12 | 0.170972E+13 | 0.218060E+12 | 0.235376E+12 | 0.962320E+11 | 0.00 | 0.100838E+12 | 1355920.07 | 0.225437E+12 | 0.00 | 0.397053E+11 | 0.00 |
Annual Sum or Average | 0.561074E+13 | 0.100646E+13 | 0.146764E+14 | 0.262311E+13 | 0.269085E+13 | 0.955830E+12 | 0.00 | 0.190493E+13 | 0.158445E+12 | 0.100727E+13 | 0.00 | 0.459967E+12 | 0.00 |
Minimum of Months | 0.424646E+12 | 0.617502E+11 | 0.740713E+12 | 0.199667E+12 | 0.176270E+12 | 0.145950E+11 | 0.00 | 0.892760E+10 | 0.00 | 0.119527E+10 | 0.00 | 0.334062E+11 | 0.00 |
Maximum of Months | 0.504598E+12 | 0.108121E+12 | 0.173200E+13 | 0.230864E+12 | 0.309736E+12 | 0.136935E+12 | 0.00 | 0.419397E+12 | 0.616341E+11 | 0.225437E+12 | 0.00 | 0.452905E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.118263E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.103845E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.471035E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.154857E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.351863E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.460078E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.291195E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.189032E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.227508E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.139830E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.305807E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.965721E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.432305E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.291195E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.118263E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 489900.85 | 02-JAN-08:09 | 64082.80 | 01-JAN-00:10 | 423497.50 | 02-JAN-08:09 | 235096.12 | 02-JAN-08:20 | 136022.43 | 02-JAN-06:19 | 44394.60 | 30-JAN-06:30 | 0.00 | 01-JAN-00:10 |
February | 489900.85 | 01-FEB-08:09 | 64082.80 | 01-FEB-00:10 | 541788.89 | 01-FEB-08:09 | 235096.12 | 01-FEB-08:20 | 131125.47 | 13-FEB-06:10 | 43344.26 | 17-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 489900.85 | 01-MAR-08:09 | 64082.80 | 01-MAR-00:10 | 660080.29 | 01-MAR-08:09 | 235096.12 | 01-MAR-08:20 | 197993.57 | 15-MAR-14:09 | 92278.29 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 |
April | 489900.85 | 03-APR-07:10 | 64082.80 | 01-APR-00:10 | 778371.69 | 03-APR-07:10 | 235096.12 | 03-APR-07:19 | 210784.10 | 21-APR-15:20 | 45716.92 | 08-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 489900.85 | 01-MAY-07:10 | 64082.80 | 01-MAY-00:10 | 423497.50 | 01-MAY-07:10 | 235096.12 | 01-MAY-07:19 | 199526.31 | 31-MAY-15:00 | 89578.67 | 10-MAY-15:39 | 0.00 | 01-MAY-00:10 |
June | 489900.85 | 01-JUN-07:10 | 64082.80 | 01-JUN-00:10 | 541788.89 | 01-JUN-07:10 | 235096.12 | 01-JUN-07:19 | 240089.29 | 27-JUN-14:30 | 94009.69 | 30-JUN-15:39 | 0.00 | 01-JUN-00:10 |
July | 489900.85 | 03-JUL-07:10 | 64082.80 | 01-JUL-00:10 | 660080.29 | 03-JUL-07:10 | 235096.12 | 03-JUL-07:19 | 262409.02 | 19-JUL-14:00 | 95351.54 | 06-JUL-14:00 | 0.00 | 01-JUL-00:10 |
August | 489900.85 | 01-AUG-07:10 | 64082.80 | 01-AUG-00:10 | 778371.69 | 01-AUG-07:10 | 235096.12 | 01-AUG-07:19 | 288370.61 | 09-AUG-15:20 | 94288.86 | 03-AUG-16:19 | 0.00 | 01-AUG-00:10 |
September | 489900.85 | 01-SEP-07:10 | 64082.80 | 01-SEP-00:10 | 423497.50 | 01-SEP-07:10 | 235096.12 | 01-SEP-07:19 | 240601.61 | 21-SEP-15:30 | 93437.74 | 20-SEP-13:39 | 0.00 | 01-SEP-00:10 |
October | 489900.85 | 02-OCT-07:10 | 64082.80 | 01-OCT-00:10 | 541788.89 | 02-OCT-07:10 | 235096.12 | 02-OCT-07:19 | 200448.24 | 11-OCT-15:30 | 49545.96 | 11-OCT-14:39 | 0.00 | 01-OCT-00:10 |
November | 489900.85 | 01-NOV-07:10 | 64082.80 | 01-NOV-00:10 | 660080.29 | 01-NOV-07:10 | 235096.12 | 01-NOV-07:19 | 171826.28 | 03-NOV-14:09 | 45868.39 | 16-NOV-14:09 | 0.00 | 01-NOV-00:10 |
December | 489900.85 | 01-DEC-08:09 | 64082.80 | 01-DEC-00:10 | 778371.69 | 01-DEC-08:09 | 235096.12 | 01-DEC-08:20 | 144643.48 | 26-DEC-06:10 | 46837.95 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 489900.85 | 64082.80 | 423497.50 | 235096.12 | 131125.47 | 43344.26 | 0.00 | |||||||
Maximum of Months | 489900.85 | 64082.80 | 778371.69 | 235096.12 | 288370.61 | 95351.54 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 16656.84 | 18-JAN-07:30 | 0.00 | 01-JAN-00:10 | 61654.29 | 13-JAN-18:10 | 0.00 | 56189.09 | 31-JAN-12:30 | 0.00 |
February | 71032.16 | 17-FEB-17:10 | 19.24 | 17-FEB-12:09 | 64654.19 | 17-FEB-17:00 | 0.00 | 56298.68 | 14-FEB-12:20 | 0.00 |
March | 319623.47 | 14-MAR-13:09 | 54364.00 | 14-MAR-12:39 | 100000.00 | 22-MAR-12:50 | 0.00 | 56179.84 | 02-MAR-12:30 | 0.00 |
April | 168237.43 | 25-APR-13:00 | 6407.41 | 08-APR-13:20 | 100000.00 | 01-APR-00:00 | 0.00 | 55032.92 | 03-APR-11:20 | 0.00 |
May | 297695.26 | 10-MAY-15:39 | 54364.00 | 10-MAY-15:39 | 100000.00 | 07-MAY-16:19 | 0.00 | 52290.62 | 01-MAY-11:30 | 0.00 |
June | 389424.09 | 27-JUN-12:00 | 54364.00 | 01-JUN-15:50 | 100000.00 | 03-JUN-15:39 | 0.00 | 48862.19 | 01-JUN-11:20 | 0.00 |
July | 413679.13 | 20-JUL-13:39 | 54364.00 | 03-JUL-10:39 | 100000.00 | 06-JUL-12:50 | 0.00 | 46097.15 | 03-JUL-11:39 | 0.00 |
August | 408720.13 | 14-AUG-14:39 | 54364.00 | 01-AUG-12:39 | 100000.00 | 01-AUG-19:30 | 0.00 | 44705.37 | 01-AUG-11:39 | 0.00 |
September | 353057.38 | 15-SEP-12:09 | 54364.00 | 08-SEP-13:39 | 66881.90 | 22-SEP-17:00 | 0.00 | 46044.28 | 29-SEP-11:20 | 0.00 |
October | 258344.04 | 11-OCT-15:09 | 24845.91 | 11-OCT-14:00 | 78766.17 | 25-OCT-14:39 | 0.00 | 48758.80 | 31-OCT-11:00 | 0.00 |
November | 157647.27 | 16-NOV-13:09 | 5411.03 | 16-NOV-13:09 | 100000.00 | 11-NOV-05:30 | 0.00 | 52163.05 | 30-NOV-12:20 | 0.00 |
December | 87079.77 | 16-DEC-05:30 | 494.94 | 01-DEC-11:09 | 100000.00 | 01-DEC-19:19 | 0.00 | 54880.78 | 28-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 16656.84 | 0.00 | 61654.29 | 0.00 | 44705.37 | 0.00 | ||||
Maximum of Months | 413679.13 | 54364.00 | 100000.00 | 0.00 | 56298.68 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1426211.86 | 13-JAN-16:00 | 489900.85 | 423497.50 | 64082.80 | 235096.12 | 94497.86 | 10808.72 | 0.00 | 8110.91 | 0.00 |
February | 1527711.75 | 17-FEB-16:00 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 111794.43 | 43344.26 | 0.00 | 21154.12 | 0.00 |
March | 2062380.80 | 15-MAR-14:30 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 191452.86 | 90901.51 | 0.00 | 308582.58 | 54364.00 |
April | 2004846.67 | 07-APR-14:09 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 179746.84 | 44558.45 | 0.00 | 143501.05 | 2133.97 |
May | 1801579.67 | 10-MAY-15:39 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 171954.50 | 89578.67 | 0.00 | 297695.26 | 54364.00 |
June | 2060467.49 | 27-JUN-15:20 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 238295.26 | 92268.63 | 0.00 | 372882.31 | 54364.00 |
July | 2236402.77 | 19-JUL-15:09 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 261450.48 | 93244.34 | 0.00 | 408314.18 | 54364.00 |
August | 2356626.12 | 18-AUG-15:09 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 275713.35 | 93099.29 | 0.00 | 396345.81 | 54364.00 |
September | 1872383.52 | 21-SEP-15:50 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 236875.80 | 90563.62 | 0.00 | 307173.06 | 54364.00 |
October | 1834071.02 | 11-OCT-15:30 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 200448.24 | 48928.31 | 0.00 | 257592.03 | 24389.59 |
November | 1824853.19 | 03-NOV-14:09 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 171826.28 | 45089.66 | 0.00 | 126942.44 | 62.40 |
December | 1928829.57 | 08-DEC-16:40 | 489900.85 | 778371.69 | 64082.80 | 235096.12 | 116407.18 | 44762.91 | 0.00 | 64316.98 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1426211.86 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 94497.86 | 10808.72 | 0.00 | 8110.91 | 0.00 | |
Maximum of Months | 2356626.12 | 489900.85 | 778371.69 | 64082.80 | 235096.12 | 275713.35 | 93244.34 | 0.00 | 408314.18 | 54364.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 2269990.72 | 02-JAN-05:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 2086474.84 | 06-FEB-07:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1643834.57 | 06-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 1008330.61 | 17-APR-04:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 696960.18 | 08-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 251512.26 | 14-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 12420.45 | 07-JUL-05:30 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 133576.50 | 31-AUG-05:40 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 537514.46 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 1004920.51 | 30-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 1030762.78 | 24-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 2110586.20 | 11-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 12420.45 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 2269990.72 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.60 | 0.00 | 25.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.76 | 0.00 | 25.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.75 | 0.00 | 25.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 26.49 | 0.00 | 26.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.67 | 0.00 | 25.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.76 | 0.00 | 25.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.67 | 25.95 | 0.00 | 25.95 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 26.49 | 0.00 | 26.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.42 | 0.33 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 |
February | 0.17 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
Annual Sum or Average | 1.33 | 19.27 | 0.33 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.42 | 0.33 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.67 | 18.41 | 0.50 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
February | 4.83 | 18.35 | 0.17 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
March | 2.00 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 |
April | 0.50 | 18.07 | 0.00 | 18.07 | 0.00 | 18.07 | 0.00 | 18.07 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.67 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 |
November | 1.33 | 18.85 | 0.17 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
December | 4.50 | 18.34 | 0.17 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 |
Annual Sum or Average | 19.50 | 18.38 | 1.00 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.67 | 18.85 | 0.50 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 18.95 | 0.17 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
February | 5.50 | 18.65 | 0.33 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
March | 1.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.50 | 19.10 | 0.33 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
Annual Sum or Average | 12.67 | 18.87 | 0.83 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.50 | 19.18 | 0.33 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 |
February | 5.67 | 18.48 | 0.17 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
March | 1.00 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.33 | 27.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.43 | 1.17 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.02 | 1.17 | 28.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.31 | 3.00 | 28.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.93 | 0.67 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.84 | 1.50 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.50 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
Annual Sum or Average | 13.17 | 18.61 | 0.17 | 18.64 | 7.83 | 22.09 | 7.83 | 23.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.67 | 19.04 | 0.17 | 19.04 | 3.00 | 28.31 | 3.00 | 28.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.17 | 18.54 | 0.17 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
February | 6.67 | 18.08 | 0.33 | 18.18 | 0.00 | 18.18 | 0.00 | 18.18 |
March | 1.33 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.43 | 0.50 | 27.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.50 | 27.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.34 | 0.67 | 27.34 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.64 | 3.67 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.93 | 3.50 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.10 | 3.17 | 28.10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.33 | 0.33 | 27.33 |
November | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
December | 3.67 | 18.73 | 0.33 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
Annual Sum or Average | 17.00 | 18.45 | 0.83 | 18.54 | 12.33 | 22.32 | 12.33 | 23.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.18 | 0.00 | 18.18 |
Maximum of Months | 6.67 | 19.42 | 0.33 | 19.42 | 3.67 | 28.10 | 3.67 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
February | 2.67 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.84 | 1.83 | 27.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.02 | 1.83 | 28.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.68 | 3.00 | 28.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 28.20 | 6.83 | 28.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.12 | 5.17 | 28.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.06 | 2.50 | 28.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Annual Sum or Average | 5.83 | 18.91 | 0.00 | 18.91 | 34.83 | 26.87 | 21.17 | 27.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 19.26 | 0.00 | 19.26 | 12.67 | 28.68 | 6.83 | 28.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 33.17 | 15.77 | 6.83 | 15.63 | 0.00 | 15.63 | 0.00 | 15.63 |
February | 30.50 | 15.91 | 4.17 | 15.92 | 0.00 | 15.92 | 0.00 | 15.92 |
March | 9.50 | 17.26 | 0.67 | 17.38 | 0.00 | 17.38 | 0.00 | 17.38 |
April | 1.67 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.83 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
November | 3.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
December | 25.67 | 16.01 | 4.33 | 15.93 | 0.00 | 15.93 | 0.00 | 15.93 |
Annual Sum or Average | 104.33 | 16.17 | 16.00 | 16.09 | 0.00 | 16.09 | 0.00 | 16.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.17 | 19.06 | 6.83 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 49.67 | 17.23 | 4.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
February | 44.50 | 16.84 | 3.00 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 |
March | 9.00 | 17.30 | 0.17 | 17.26 | 0.00 | 17.26 | 0.00 | 17.26 |
April | 1.83 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.44 | 0.33 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.01 | 1.33 | 28.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.22 | 4.00 | 28.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.98 | 1.00 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.59 | 0.83 | 27.59 |
October | 0.83 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
November | 3.00 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
December | 43.67 | 17.38 | 3.17 | 17.26 | 0.00 | 17.26 | 0.00 | 17.26 |
Annual Sum or Average | 152.50 | 17.23 | 10.33 | 17.12 | 7.50 | 17.60 | 7.50 | 18.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 | 0.00 | 16.78 |
Maximum of Months | 49.67 | 19.01 | 4.00 | 19.01 | 4.00 | 28.22 | 4.00 | 28.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.67 | 16.05 | 2.67 | 15.97 | 0.00 | 15.97 | 0.00 | 15.97 |
February | 26.33 | 16.13 | 2.50 | 16.19 | 0.00 | 16.19 | 0.00 | 16.19 |
March | 5.83 | 18.16 | 0.17 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 |
April | 1.17 | 19.14 | 0.00 | 19.14 | 0.33 | 20.97 | 0.33 | 22.13 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.33 | 0.50 | 27.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.63 | 2.83 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.94 | 3.00 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.18 | 3.17 | 28.18 |
October | 0.67 | 19.12 | 0.00 | 19.12 | 0.17 | 20.79 | 0.17 | 21.90 |
November | 2.83 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
December | 21.50 | 16.36 | 1.67 | 16.40 | 0.00 | 16.40 | 0.00 | 16.40 |
Annual Sum or Average | 85.00 | 16.46 | 7.00 | 16.45 | 10.00 | 17.57 | 10.00 | 18.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.67 | 19.14 | 2.67 | 19.14 | 3.17 | 28.18 | 3.17 | 28.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.00 | 16.08 | 3.17 | 15.97 | 0.00 | 15.97 | 0.00 | 15.97 |
February | 23.17 | 16.08 | 2.17 | 16.08 | 0.00 | 16.08 | 0.00 | 16.08 |
March | 5.83 | 18.08 | 0.00 | 18.08 | 0.00 | 18.08 | 0.00 | 18.08 |
April | 0.83 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.18 | 0.83 | 28.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.53 | 2.33 | 28.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.75 | 2.50 | 28.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.23 | 2.00 | 28.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.82 | 1.17 | 27.81 |
October | 0.67 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
November | 2.83 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
December | 20.17 | 16.19 | 2.50 | 16.16 | 0.00 | 16.16 | 0.00 | 16.16 |
Annual Sum or Average | 78.50 | 16.43 | 7.83 | 16.36 | 16.50 | 18.29 | 8.83 | 19.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.97 | 0.00 | 15.97 |
Maximum of Months | 25.00 | 19.18 | 3.17 | 19.18 | 5.00 | 28.75 | 2.50 | 28.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 66.00 | 14.94 | 15.83 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
February | 63.83 | 15.03 | 15.17 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
March | 30.50 | 15.59 | 5.17 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 |
April | 9.17 | 16.55 | 1.50 | 16.28 | 0.00 | 16.28 | 0.00 | 16.28 |
May | 0.67 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.33 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
October | 6.00 | 16.85 | 0.50 | 16.71 | 0.00 | 16.71 | 0.00 | 16.71 |
November | 13.33 | 16.78 | 1.67 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 |
December | 62.50 | 14.95 | 17.50 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
Annual Sum or Average | 252.33 | 15.26 | 57.33 | 15.16 | 0.00 | 15.16 | 0.00 | 15.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.00 | 19.34 | 17.50 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 65.83 | 14.95 | 14.83 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
February | 62.67 | 15.03 | 13.83 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
March | 27.33 | 15.64 | 2.33 | 15.67 | 0.00 | 15.67 | 0.00 | 15.67 |
April | 8.50 | 16.61 | 1.00 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 |
May | 0.50 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.86 | 1.17 | 27.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.24 | 4.33 | 28.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.98 | 1.00 | 27.98 |
September | 0.17 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
October | 6.33 | 16.91 | 0.33 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 |
November | 13.50 | 16.84 | 1.33 | 16.72 | 0.00 | 16.72 | 0.00 | 16.72 |
December | 61.33 | 14.94 | 15.00 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
Annual Sum or Average | 246.17 | 15.27 | 48.67 | 15.19 | 6.50 | 15.47 | 6.50 | 15.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.89 | 0.00 | 14.89 |
Maximum of Months | 65.83 | 19.22 | 15.00 | 19.22 | 4.33 | 28.24 | 4.33 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.33 | 15.06 | 10.33 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
February | 57.00 | 15.12 | 11.33 | 15.08 | 0.00 | 15.08 | 0.00 | 15.08 |
March | 22.00 | 16.01 | 2.00 | 16.02 | 0.00 | 16.02 | 0.00 | 16.02 |
April | 8.00 | 16.82 | 1.00 | 16.57 | 0.00 | 16.57 | 0.00 | 16.57 |
May | 0.50 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
June | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.78 | 2.50 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.86 | 2.67 | 27.86 |
September | 0.17 | 19.33 | 0.00 | 19.33 | 1.83 | 27.22 | 1.83 | 27.57 |
October | 4.67 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 |
November | 10.50 | 17.12 | 1.00 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
December | 51.33 | 15.10 | 9.67 | 15.06 | 0.00 | 15.06 | 0.00 | 15.06 |
Annual Sum or Average | 208.67 | 15.43 | 35.33 | 15.35 | 7.00 | 15.70 | 7.00 | 16.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.01 | 0.00 | 15.01 |
Maximum of Months | 57.00 | 19.40 | 11.33 | 19.40 | 2.67 | 27.86 | 2.67 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 52.00 | 15.00 | 12.17 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
February | 48.50 | 15.17 | 9.50 | 15.14 | 0.00 | 15.14 | 0.00 | 15.14 |
March | 17.83 | 16.01 | 1.33 | 15.91 | 0.00 | 15.91 | 0.00 | 15.91 |
April | 4.83 | 16.88 | 1.00 | 16.51 | 0.00 | 16.51 | 0.00 | 16.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.13 | 0.83 | 28.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.62 | 2.67 | 28.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.78 | 2.83 | 28.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.40 | 2.17 | 28.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.74 | 0.67 | 27.74 |
October | 3.33 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 |
November | 6.83 | 17.70 | 0.00 | 17.70 | 0.00 | 17.70 | 0.00 | 17.70 |
December | 44.50 | 15.18 | 9.67 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
Annual Sum or Average | 177.83 | 15.41 | 33.67 | 15.32 | 17.00 | 16.30 | 9.17 | 16.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 | 0.00 | 14.94 |
Maximum of Months | 52.00 | 18.26 | 12.17 | 18.26 | 5.67 | 28.78 | 2.83 | 28.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.80 | 5.67 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.67 | 27.80 | 5.67 | 27.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.80 | 5.67 | 27.80 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 449.67 | 23.26 | 12.83 | 23.31 | 2.50 | 23.32 |
February | 427.00 | 23.09 | 0.00 | 23.09 | 0.00 | 23.09 |
March | 337.33 | 23.60 | 39.67 | 23.68 | 0.00 | 23.68 |
April | 249.17 | 23.71 | 46.17 | 24.01 | 0.00 | 24.01 |
May | 171.17 | 23.61 | 122.67 | 24.21 | 0.00 | 24.21 |
June | 32.83 | 24.74 | 323.17 | 24.58 | 14.50 | 24.63 |
July | 12.17 | 26.31 | 480.33 | 24.62 | 12.17 | 24.66 |
August | 3.50 | 24.00 | 481.83 | 24.48 | 3.50 | 24.48 |
September | 11.50 | 23.26 | 339.33 | 24.67 | 0.17 | 24.67 |
October | 43.33 | 23.72 | 172.17 | 25.03 | 0.00 | 25.03 |
November | 109.00 | 23.83 | 113.83 | 24.91 | 0.00 | 24.91 |
December | 355.67 | 23.54 | 33.33 | 23.74 | 0.00 | 23.74 |
Annual Sum or Average | 2202.33 | 23.48 | 2165.33 | 24.12 | 32.83 | 24.14 |
Minimum of Months | 3.50 | 23.09 | 0.00 | 23.09 | 0.00 | 23.09 |
Maximum of Months | 449.67 | 26.31 | 481.83 | 25.03 | 14.50 | 25.03 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 466.83 | 23.56 | 12.00 | 23.57 | 12.00 | 23.57 |
February | 424.33 | 23.50 | 0.00 | 23.50 | 0.00 | 23.50 |
March | 257.83 | 23.74 | 66.00 | 23.87 | 0.00 | 23.87 |
April | 94.17 | 23.76 | 69.33 | 24.39 | 0.00 | 24.39 |
May | 78.33 | 23.74 | 171.33 | 24.35 | 0.00 | 24.35 |
June | 4.50 | 23.75 | 363.33 | 24.28 | 0.00 | 24.28 |
July | 0.00 | 0.00 | 492.17 | 24.27 | 0.00 | 24.27 |
August | 0.00 | 0.00 | 506.50 | 24.27 | 0.00 | 24.27 |
September | 11.67 | 23.74 | 368.33 | 24.35 | 0.67 | 24.35 |
October | 69.33 | 23.67 | 182.33 | 24.38 | 0.00 | 24.38 |
November | 109.33 | 23.76 | 73.67 | 24.43 | 0.00 | 24.43 |
December | 313.50 | 23.75 | 6.33 | 23.76 | 0.00 | 23.76 |
Annual Sum or Average | 1829.83 | 23.64 | 2311.33 | 24.07 | 12.67 | 24.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.50 | 0.00 | 23.50 |
Maximum of Months | 466.83 | 23.76 | 506.50 | 24.43 | 12.00 | 24.43 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.33 | 22.11 | 80.50 | 21.82 | 80.50 | 21.59 |
February | 454.00 | 22.32 | 57.67 | 22.13 | 57.67 | 21.98 |
March | 413.83 | 23.13 | 47.17 | 23.16 | 10.67 | 23.11 |
April | 293.33 | 23.38 | 4.17 | 23.40 | 0.00 | 23.40 |
May | 161.67 | 23.56 | 127.17 | 23.95 | 0.00 | 23.95 |
June | 59.17 | 23.55 | 296.67 | 24.09 | 0.00 | 24.09 |
July | 0.00 | 0.00 | 461.17 | 24.20 | 0.00 | 24.20 |
August | 0.00 | 0.00 | 448.67 | 24.21 | 0.00 | 24.21 |
September | 72.33 | 23.40 | 268.50 | 24.10 | 2.33 | 24.11 |
October | 256.17 | 23.42 | 61.33 | 23.57 | 0.00 | 23.57 |
November | 372.67 | 23.36 | 3.17 | 23.37 | 0.00 | 23.37 |
December | 486.33 | 22.43 | 47.50 | 22.26 | 47.50 | 22.12 |
Annual Sum or Average | 3070.83 | 22.85 | 1903.67 | 23.23 | 198.67 | 23.12 |
Minimum of Months | 0.00 | 0.00 | 3.17 | 21.82 | 0.00 | 21.59 |
Maximum of Months | 501.33 | 23.56 | 461.17 | 24.21 | 80.50 | 24.21 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.58 | 328.17 | 20.34 | 328.17 | 20.24 |
February | 454.00 | 20.76 | 262.50 | 20.46 | 262.50 | 20.33 |
March | 472.33 | 21.63 | 165.17 | 21.37 | 141.17 | 21.14 |
April | 424.67 | 22.25 | 38.67 | 22.07 | 37.50 | 21.90 |
May | 297.50 | 22.98 | 86.67 | 23.21 | 3.83 | 23.19 |
June | 112.83 | 23.12 | 273.83 | 23.85 | 0.00 | 23.85 |
July | 26.50 | 23.01 | 424.50 | 24.13 | 0.00 | 24.13 |
August | 52.67 | 23.11 | 394.50 | 24.04 | 0.00 | 24.04 |
September | 206.67 | 22.66 | 178.00 | 23.36 | 1.17 | 23.36 |
October | 427.83 | 21.98 | 84.50 | 21.75 | 68.50 | 21.52 |
November | 485.33 | 21.56 | 108.17 | 21.27 | 108.17 | 21.07 |
December | 497.00 | 20.67 | 278.00 | 20.39 | 278.00 | 20.26 |
Annual Sum or Average | 3959.33 | 21.60 | 2622.67 | 21.84 | 1229.00 | 21.54 |
Minimum of Months | 26.50 | 20.58 | 38.67 | 20.34 | 0.00 | 20.24 |
Maximum of Months | 502.00 | 23.12 | 424.50 | 24.13 | 328.17 | 24.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.68 | 370.17 | 20.59 | 370.17 | 20.55 |
February | 454.00 | 20.74 | 298.00 | 20.62 | 298.00 | 20.57 |
March | 465.50 | 21.61 | 160.83 | 21.50 | 134.17 | 21.35 |
April | 400.67 | 22.43 | 13.67 | 22.43 | 7.33 | 22.39 |
May | 269.83 | 22.91 | 93.33 | 23.26 | 0.00 | 23.26 |
June | 71.17 | 23.33 | 318.33 | 24.03 | 3.50 | 24.05 |
July | 9.17 | 24.85 | 476.33 | 24.29 | 5.50 | 24.31 |
August | 34.50 | 23.28 | 435.83 | 24.14 | 2.17 | 24.15 |
September | 177.50 | 22.93 | 202.50 | 23.62 | 6.33 | 23.65 |
October | 405.67 | 22.40 | 38.67 | 22.54 | 2.17 | 22.53 |
November | 469.00 | 21.98 | 23.33 | 21.98 | 17.00 | 21.94 |
December | 497.00 | 20.95 | 240.83 | 20.80 | 240.83 | 20.72 |
Annual Sum or Average | 3756.00 | 21.72 | 2671.83 | 22.14 | 1087.17 | 21.92 |
Minimum of Months | 9.17 | 20.68 | 13.67 | 20.59 | 0.00 | 20.55 |
Maximum of Months | 502.00 | 24.85 | 476.33 | 24.29 | 370.17 | 24.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.64 | 337.17 | 20.56 | 337.17 | 20.52 |
February | 453.00 | 20.71 | 276.00 | 20.59 | 276.00 | 20.54 |
March | 468.17 | 21.44 | 125.00 | 21.38 | 103.17 | 21.26 |
April | 370.67 | 21.84 | 60.00 | 22.12 | 7.67 | 22.09 |
May | 281.00 | 22.34 | 156.33 | 23.04 | 4.50 | 23.08 |
June | 131.67 | 22.74 | 306.67 | 23.74 | 10.00 | 23.80 |
July | 75.00 | 23.50 | 391.67 | 24.06 | 19.33 | 24.15 |
August | 115.33 | 22.53 | 346.17 | 23.69 | 4.50 | 23.72 |
September | 216.17 | 22.36 | 230.83 | 23.33 | 9.50 | 23.39 |
October | 402.50 | 21.89 | 62.50 | 22.17 | 5.67 | 22.16 |
November | 467.33 | 21.44 | 48.17 | 21.44 | 40.50 | 21.39 |
December | 497.00 | 20.75 | 261.50 | 20.64 | 261.50 | 20.59 |
Annual Sum or Average | 3979.83 | 21.48 | 2602.00 | 21.96 | 1079.50 | 21.79 |
Minimum of Months | 75.00 | 20.64 | 48.17 | 20.56 | 4.50 | 20.52 |
Maximum of Months | 502.00 | 23.50 | 391.67 | 24.06 | 337.17 | 24.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 475.00 | 20.79 | 298.17 | 20.62 | 293.17 | 20.52 |
February | 423.67 | 20.78 | 253.00 | 20.59 | 248.83 | 20.49 |
March | 390.33 | 21.54 | 151.00 | 21.63 | 98.00 | 21.47 |
April | 346.83 | 21.93 | 89.50 | 22.28 | 15.67 | 22.22 |
May | 279.83 | 22.37 | 132.50 | 22.98 | 3.17 | 22.99 |
June | 140.83 | 22.77 | 286.83 | 23.73 | 7.33 | 23.76 |
July | 64.00 | 24.02 | 420.00 | 24.23 | 24.17 | 24.33 |
August | 89.67 | 23.36 | 388.83 | 24.07 | 16.17 | 24.15 |
September | 187.00 | 22.77 | 265.33 | 23.70 | 17.17 | 23.81 |
October | 337.67 | 22.00 | 135.67 | 22.51 | 22.33 | 22.43 |
November | 403.67 | 21.53 | 99.67 | 21.71 | 55.33 | 21.60 |
December | 472.67 | 20.90 | 231.67 | 20.76 | 223.67 | 20.66 |
Annual Sum or Average | 3611.17 | 21.61 | 2752.17 | 22.17 | 1025.00 | 21.97 |
Minimum of Months | 64.00 | 20.78 | 89.50 | 20.59 | 3.17 | 20.49 |
Maximum of Months | 475.00 | 24.02 | 420.00 | 24.23 | 293.17 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.33 | 20.89 | 236.33 | 20.80 | 235.83 | 20.75 |
February | 448.67 | 21.03 | 181.83 | 20.92 | 181.00 | 20.86 |
March | 405.67 | 21.81 | 89.67 | 22.05 | 30.33 | 21.99 |
April | 299.83 | 22.42 | 121.17 | 23.05 | 5.83 | 23.10 |
May | 266.00 | 22.47 | 175.00 | 23.27 | 8.67 | 23.33 |
June | 102.67 | 23.36 | 357.50 | 24.11 | 26.83 | 24.22 |
July | 74.50 | 25.45 | 475.67 | 24.52 | 63.50 | 24.66 |
August | 72.83 | 25.05 | 476.67 | 24.45 | 59.67 | 24.56 |
September | 195.50 | 22.59 | 239.83 | 23.56 | 15.50 | 23.67 |
October | 372.00 | 22.07 | 69.50 | 22.45 | 0.00 | 22.45 |
November | 437.67 | 21.94 | 29.67 | 22.15 | 0.00 | 22.15 |
December | 495.33 | 21.40 | 68.33 | 21.31 | 68.33 | 21.24 |
Annual Sum or Average | 3671.00 | 21.90 | 2521.17 | 22.60 | 695.50 | 22.54 |
Minimum of Months | 72.83 | 20.89 | 29.67 | 20.80 | 0.00 | 20.75 |
Maximum of Months | 500.33 | 25.45 | 476.67 | 24.52 | 235.83 | 24.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.93 | 472.83 | 19.90 | 472.83 | 19.89 |
February | 454.00 | 20.00 | 418.00 | 19.96 | 418.00 | 19.94 |
March | 498.17 | 20.68 | 277.67 | 20.52 | 267.67 | 20.42 |
April | 485.00 | 21.26 | 94.33 | 21.06 | 94.33 | 20.91 |
May | 429.17 | 22.13 | 40.00 | 22.25 | 6.17 | 22.22 |
June | 220.67 | 22.59 | 204.67 | 23.27 | 4.00 | 23.29 |
July | 85.67 | 22.98 | 359.50 | 23.86 | 15.67 | 23.90 |
August | 158.33 | 22.45 | 278.83 | 23.45 | 0.67 | 23.45 |
September | 352.33 | 22.12 | 93.00 | 22.54 | 10.67 | 22.61 |
October | 496.83 | 21.23 | 90.67 | 21.04 | 90.67 | 20.90 |
November | 489.00 | 20.69 | 213.17 | 20.51 | 213.17 | 20.41 |
December | 497.00 | 19.97 | 430.33 | 19.90 | 430.33 | 19.87 |
Annual Sum or Average | 4668.17 | 21.01 | 2973.00 | 21.12 | 2024.17 | 20.89 |
Minimum of Months | 85.67 | 19.93 | 40.00 | 19.90 | 0.67 | 19.87 |
Maximum of Months | 502.00 | 22.98 | 472.83 | 23.86 | 472.83 | 23.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.79 | 403.83 | 19.76 | 403.83 | 19.75 |
February | 385.00 | 19.88 | 332.17 | 19.79 | 332.17 | 19.75 |
March | 413.83 | 20.79 | 199.17 | 20.60 | 189.00 | 20.46 |
April | 347.50 | 21.30 | 92.50 | 21.30 | 64.17 | 21.12 |
May | 284.17 | 22.02 | 103.50 | 22.64 | 4.67 | 22.66 |
June | 164.83 | 22.49 | 218.17 | 23.48 | 10.83 | 23.55 |
July | 108.00 | 23.58 | 309.33 | 24.12 | 35.50 | 24.28 |
August | 140.33 | 22.35 | 252.33 | 23.53 | 6.50 | 23.58 |
September | 245.67 | 22.10 | 142.67 | 22.91 | 13.50 | 23.01 |
October | 386.83 | 21.32 | 75.50 | 21.24 | 62.33 | 21.09 |
November | 416.83 | 20.78 | 180.83 | 20.58 | 180.83 | 20.47 |
December | 422.00 | 19.82 | 376.00 | 19.76 | 376.00 | 19.73 |
Annual Sum or Average | 3742.00 | 20.97 | 2686.00 | 21.23 | 1679.33 | 20.99 |
Minimum of Months | 108.00 | 19.79 | 75.50 | 19.76 | 4.67 | 19.73 |
Maximum of Months | 427.00 | 23.58 | 403.83 | 24.12 | 403.83 | 24.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 479.17 | 20.28 | 370.33 | 20.13 | 366.00 | 20.05 |
February | 426.67 | 20.28 | 310.00 | 20.09 | 305.67 | 20.00 |
March | 410.50 | 21.15 | 198.50 | 21.15 | 150.83 | 20.96 |
April | 369.00 | 21.42 | 127.17 | 21.64 | 64.00 | 21.47 |
May | 314.17 | 22.12 | 120.67 | 22.68 | 7.17 | 22.68 |
June | 186.17 | 22.48 | 253.17 | 23.44 | 7.00 | 23.47 |
July | 111.00 | 23.45 | 376.33 | 24.08 | 34.33 | 24.20 |
August | 135.50 | 22.85 | 341.67 | 23.84 | 16.17 | 23.93 |
September | 227.33 | 22.55 | 237.33 | 23.48 | 23.17 | 23.63 |
October | 360.33 | 21.59 | 145.17 | 22.02 | 44.33 | 21.87 |
November | 421.17 | 21.05 | 173.33 | 21.06 | 138.17 | 20.90 |
December | 481.83 | 20.30 | 354.50 | 20.16 | 350.50 | 20.09 |
Annual Sum or Average | 3922.83 | 21.25 | 3008.17 | 21.67 | 1507.33 | 21.43 |
Minimum of Months | 111.00 | 20.28 | 120.67 | 20.09 | 7.00 | 20.00 |
Maximum of Months | 481.83 | 23.45 | 376.33 | 24.08 | 366.00 | 24.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.04 | 444.33 | 19.98 | 444.33 | 19.96 |
February | 452.33 | 20.15 | 363.33 | 20.04 | 363.33 | 20.00 |
March | 476.33 | 20.91 | 209.50 | 20.80 | 193.00 | 20.67 |
April | 411.00 | 21.27 | 104.67 | 21.41 | 58.17 | 21.27 |
May | 362.83 | 21.98 | 112.33 | 22.53 | 7.50 | 22.58 |
June | 201.67 | 22.48 | 260.00 | 23.44 | 19.00 | 23.55 |
July | 142.00 | 23.13 | 354.00 | 23.96 | 41.00 | 24.08 |
August | 164.83 | 22.46 | 306.83 | 23.59 | 19.00 | 23.68 |
September | 318.50 | 22.05 | 143.67 | 22.74 | 15.33 | 22.85 |
October | 458.83 | 21.24 | 95.00 | 21.24 | 67.00 | 21.12 |
November | 485.17 | 20.85 | 173.33 | 20.67 | 173.33 | 20.57 |
December | 497.00 | 20.10 | 399.83 | 20.00 | 399.83 | 19.96 |
Annual Sum or Average | 4472.50 | 21.07 | 2966.83 | 21.36 | 1800.83 | 21.16 |
Minimum of Months | 142.00 | 20.04 | 95.00 | 19.98 | 7.50 | 19.96 |
Maximum of Months | 502.00 | 23.13 | 444.33 | 23.96 | 444.33 | 24.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.75 | 492.17 | 19.74 | 492.17 | 19.74 |
February | 454.00 | 19.83 | 437.83 | 19.80 | 437.83 | 19.80 |
March | 504.67 | 20.34 | 339.33 | 20.19 | 333.00 | 20.11 |
April | 485.00 | 20.76 | 185.67 | 20.52 | 185.67 | 20.39 |
May | 461.17 | 21.60 | 63.83 | 21.62 | 40.50 | 21.55 |
June | 276.50 | 22.06 | 166.17 | 22.73 | 6.83 | 22.73 |
July | 168.83 | 22.42 | 290.17 | 23.41 | 20.17 | 23.46 |
August | 241.33 | 22.05 | 208.33 | 22.91 | 1.67 | 22.91 |
September | 402.33 | 21.60 | 79.83 | 21.78 | 36.83 | 21.77 |
October | 502.00 | 20.57 | 180.83 | 20.27 | 180.83 | 20.10 |
November | 489.00 | 20.16 | 347.33 | 20.01 | 347.33 | 19.96 |
December | 497.00 | 19.77 | 476.00 | 19.75 | 476.00 | 19.74 |
Annual Sum or Average | 4983.83 | 20.69 | 3267.50 | 20.71 | 2558.83 | 20.50 |
Minimum of Months | 168.83 | 19.75 | 63.83 | 19.74 | 1.67 | 19.74 |
Maximum of Months | 504.67 | 22.42 | 492.17 | 23.41 | 492.17 | 23.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.77 | 492.83 | 19.76 | 492.83 | 19.75 |
February | 454.00 | 19.84 | 408.83 | 19.77 | 408.83 | 19.75 |
March | 495.00 | 20.46 | 285.67 | 20.27 | 270.17 | 20.13 |
April | 408.17 | 20.93 | 151.67 | 20.77 | 129.33 | 20.56 |
May | 325.83 | 21.76 | 152.17 | 22.41 | 23.17 | 22.35 |
June | 181.67 | 22.33 | 275.17 | 23.43 | 12.83 | 23.50 |
July | 128.67 | 23.47 | 374.83 | 24.04 | 43.67 | 24.20 |
August | 167.83 | 22.32 | 314.00 | 23.49 | 10.17 | 23.55 |
September | 276.17 | 21.77 | 188.17 | 22.62 | 24.17 | 22.62 |
October | 479.17 | 20.85 | 152.33 | 20.58 | 144.00 | 20.37 |
November | 489.00 | 20.25 | 321.67 | 20.08 | 321.67 | 20.01 |
December | 497.00 | 19.77 | 475.83 | 19.75 | 475.83 | 19.74 |
Annual Sum or Average | 4404.50 | 20.72 | 3593.17 | 21.01 | 2356.67 | 20.76 |
Minimum of Months | 128.67 | 19.77 | 151.67 | 19.75 | 10.17 | 19.74 |
Maximum of Months | 502.00 | 23.47 | 492.83 | 24.04 | 492.83 | 24.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 492.00 | 19.98 | 420.33 | 19.85 | 420.33 | 19.80 |
February | 439.00 | 19.97 | 354.50 | 19.81 | 350.67 | 19.74 |
March | 444.67 | 20.67 | 252.17 | 20.54 | 221.67 | 20.37 |
April | 398.50 | 20.93 | 196.67 | 20.99 | 144.50 | 20.78 |
May | 361.50 | 21.65 | 134.83 | 22.10 | 37.00 | 22.01 |
June | 236.50 | 22.03 | 224.00 | 22.97 | 14.33 | 22.98 |
July | 173.17 | 22.77 | 324.17 | 23.70 | 37.33 | 23.82 |
August | 196.17 | 22.29 | 285.33 | 23.39 | 16.00 | 23.48 |
September | 279.17 | 21.93 | 211.50 | 22.82 | 33.50 | 22.86 |
October | 405.33 | 20.90 | 197.17 | 21.04 | 123.67 | 20.79 |
November | 457.83 | 20.53 | 269.33 | 20.34 | 257.33 | 20.20 |
December | 490.00 | 19.94 | 424.33 | 19.84 | 424.17 | 19.80 |
Annual Sum or Average | 4373.83 | 20.86 | 3294.33 | 21.13 | 2080.50 | 20.88 |
Minimum of Months | 173.17 | 19.94 | 134.83 | 19.81 | 14.33 | 19.74 |
Maximum of Months | 492.00 | 22.77 | 424.33 | 23.70 | 424.17 | 23.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 471.00 | 19.80 | 471.00 | 19.78 |
February | 452.67 | 19.92 | 397.67 | 19.84 | 397.67 | 19.81 |
March | 482.67 | 20.58 | 268.67 | 20.41 | 254.33 | 20.28 |
April | 416.83 | 20.94 | 175.00 | 21.01 | 128.83 | 20.83 |
May | 382.67 | 21.75 | 128.67 | 22.24 | 30.33 | 22.22 |
June | 233.83 | 22.33 | 245.83 | 23.26 | 29.67 | 23.37 |
July | 180.00 | 22.91 | 335.83 | 23.79 | 54.00 | 23.93 |
August | 209.00 | 22.30 | 282.50 | 23.36 | 29.17 | 23.46 |
September | 338.83 | 21.74 | 139.50 | 22.38 | 25.00 | 22.45 |
October | 467.50 | 20.80 | 162.67 | 20.66 | 138.67 | 20.46 |
November | 488.50 | 20.40 | 276.00 | 20.19 | 276.00 | 20.09 |
December | 497.00 | 19.84 | 447.33 | 19.78 | 447.33 | 19.75 |
Annual Sum or Average | 4651.50 | 20.83 | 3330.67 | 21.05 | 2282.00 | 20.84 |
Minimum of Months | 180.00 | 19.83 | 128.67 | 19.78 | 25.00 | 19.75 |
Maximum of Months | 502.00 | 22.91 | 471.00 | 23.79 | 471.00 | 23.93 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 449.33 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 404.50 | 27.00 | 0.00 | 27.00 |
March | 21.33 | 27.00 | 514.00 | 27.00 | 21.33 | 27.00 |
April | 48.00 | 27.00 | 485.00 | 27.00 | 48.00 | 27.00 |
May | 28.50 | 27.00 | 508.00 | 27.00 | 28.50 | 27.00 |
June | 165.00 | 27.00 | 496.00 | 27.00 | 165.00 | 27.00 |
July | 304.67 | 27.00 | 497.00 | 27.00 | 304.67 | 27.00 |
August | 394.17 | 27.00 | 514.00 | 27.00 | 394.17 | 27.00 |
September | 78.00 | 27.00 | 485.00 | 27.00 | 78.00 | 27.00 |
October | 24.17 | 27.00 | 502.00 | 27.00 | 24.17 | 27.00 |
November | 6.17 | 27.00 | 489.00 | 27.00 | 6.17 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 1070.00 | 27.00 | 5840.83 | 27.00 | 1070.00 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 404.50 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 394.17 | 27.00 | 514.00 | 27.00 | 394.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.00 | 26.26 | 226.83 | 26.88 | 0.00 | 26.88 |
February | 17.67 | 27.00 | 231.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 433.33 | 27.00 | 0.00 | 27.00 |
April | 5.83 | 27.00 | 480.33 | 27.00 | 5.83 | 27.00 |
May | 14.00 | 27.00 | 508.00 | 27.00 | 14.00 | 27.00 |
June | 77.83 | 27.00 | 496.00 | 27.00 | 77.83 | 27.00 |
July | 137.33 | 27.00 | 497.00 | 27.00 | 137.33 | 27.00 |
August | 135.50 | 27.00 | 514.00 | 27.00 | 135.50 | 27.00 |
September | 21.00 | 27.00 | 485.00 | 27.00 | 21.00 | 27.00 |
October | 4.00 | 27.00 | 502.00 | 27.00 | 4.00 | 27.00 |
November | 0.00 | 0.00 | 472.17 | 27.00 | 0.00 | 27.00 |
December | 1.67 | 27.00 | 345.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 457.83 | 26.93 | 5190.83 | 26.99 | 395.50 | 26.99 |
Minimum of Months | 0.00 | 0.00 | 226.83 | 26.88 | 0.00 | 26.88 |
Maximum of Months | 137.33 | 27.00 | 514.00 | 27.00 | 137.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 137.33 | 25.30 | 121.17 | 26.10 | 0.00 | 26.10 |
February | 92.50 | 27.00 | 156.00 | 27.00 | 0.00 | 27.00 |
March | 44.83 | 27.00 | 345.83 | 27.00 | 4.50 | 27.00 |
April | 15.67 | 27.00 | 446.00 | 27.00 | 10.33 | 27.00 |
May | 27.17 | 27.00 | 501.83 | 27.00 | 27.17 | 27.00 |
June | 121.00 | 27.00 | 496.00 | 27.00 | 121.00 | 27.00 |
July | 180.83 | 27.00 | 497.00 | 27.00 | 180.83 | 27.00 |
August | 162.67 | 27.00 | 514.00 | 27.00 | 162.67 | 27.00 |
September | 37.50 | 27.00 | 485.00 | 27.00 | 37.50 | 27.00 |
October | 8.83 | 27.00 | 440.17 | 27.00 | 4.67 | 27.00 |
November | 21.33 | 27.00 | 359.67 | 27.00 | 0.00 | 27.00 |
December | 80.83 | 27.00 | 228.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 930.50 | 26.75 | 4590.67 | 26.96 | 548.67 | 26.96 |
Minimum of Months | 8.83 | 25.30 | 121.17 | 26.10 | 0.00 | 26.10 |
Maximum of Months | 180.83 | 27.00 | 514.00 | 27.00 | 180.83 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 137.50 | 27.19 | 502.00 | 27.16 | 137.50 | 27.17 |
February | 0.00 | 0.00 | 454.00 | 24.68 | 0.00 | 24.68 |
March | 318.17 | 25.94 | 498.00 | 25.79 | 317.83 | 25.83 |
April | 224.00 | 25.83 | 485.00 | 25.04 | 224.00 | 25.23 |
May | 314.33 | 27.08 | 508.00 | 27.08 | 314.33 | 27.08 |
June | 257.50 | 26.84 | 494.83 | 26.19 | 257.50 | 26.36 |
July | 495.50 | 26.88 | 497.00 | 26.88 | 495.50 | 26.88 |
August | 505.33 | 26.79 | 514.00 | 26.76 | 505.33 | 26.77 |
September | 485.00 | 27.01 | 485.00 | 27.01 | 485.00 | 27.01 |
October | 96.67 | 26.77 | 498.50 | 25.33 | 96.33 | 25.53 |
November | 390.50 | 25.88 | 484.33 | 25.62 | 390.50 | 25.70 |
December | 183.67 | 25.42 | 497.00 | 24.73 | 183.67 | 24.87 |
Annual Sum or Average | 3408.17 | 26.56 | 5917.67 | 26.15 | 3407.50 | 26.26 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 24.68 | 0.00 | 24.68 |
Maximum of Months | 505.33 | 27.19 | 514.00 | 27.16 | 505.33 | 27.17 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00023 | 17.08054 | 0.64314 | 13.82356 |
February | 454.00000 | 27.00000 | 15.71209 | 0.65328 | 14.13921 |
March | 514.00000 | 27.00000 | 21.90788 | 0.80915 | 19.13689 |
April | 485.00000 | 27.00000 | 26.75063 | 0.90949 | 22.60930 |
May | 508.00000 | 27.00004 | 31.31655 | 0.21863 | 6.24655 |
June | 496.00000 | 27.00012 | 36.22155 | 0.34889 | 7.76841 |
July | 497.00000 | 27.00008 | 38.89441 | 0.44487 | 9.24950 |
August | 514.00000 | 27.00027 | 37.25078 | 0.46940 | 9.72283 |
September | 485.00000 | 27.00023 | 37.77898 | 0.29483 | 7.01225 |
October | 502.00000 | 27.00001 | 30.83219 | 0.87757 | 21.43297 |
November | 489.00000 | 27.00000 | 25.51781 | 0.83617 | 19.90610 |
December | 497.00000 | 27.00000 | 18.97744 | 0.75784 | 17.23962 |
Annual Sum or Average | 5943.00000 | 27.00008 | 28.26941 | 0.60441 | 14.00705 |
Minimum of Months | 454.00000 | 27.00000 | 15.71209 | 0.21863 | 6.24655 |
Maximum of Months | 514.00000 | 27.00027 | 38.89441 | 0.90949 | 22.60930 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.93545 | 17.10736 | 0.51745 | 10.98441 |
February | 454.00000 | 27.00000 | 15.70916 | 0.54766 | 11.54398 |
March | 514.00000 | 27.00000 | 21.91085 | 0.69830 | 15.70808 |
April | 485.00000 | 27.00000 | 26.74470 | 0.79308 | 18.47914 |
May | 508.00000 | 27.00004 | 31.30815 | 0.14154 | 5.74088 |
June | 496.00000 | 27.00012 | 36.25391 | 0.26906 | 6.81544 |
July | 497.00000 | 27.00008 | 38.96465 | 0.33552 | 7.54207 |
August | 514.00000 | 27.00028 | 37.32567 | 0.33431 | 7.54765 |
September | 485.00000 | 27.00022 | 37.85802 | 0.20352 | 6.13866 |
October | 502.00000 | 27.00001 | 30.83006 | 0.78959 | 18.37336 |
November | 489.00000 | 27.00000 | 25.51110 | 0.71669 | 16.01581 |
December | 497.00000 | 27.00000 | 18.96941 | 0.60138 | 12.83811 |
Annual Sum or Average | 5943.00000 | 26.99461 | 28.29061 | 0.49476 | 11.46377 |
Minimum of Months | 454.00000 | 26.93545 | 15.70916 | 0.14154 | 5.74088 |
Maximum of Months | 514.00000 | 27.00028 | 38.96465 | 0.79308 | 18.47914 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.53165 | 17.34455 | 0.36538 | 9.34770 |
February | 454.00000 | 27.00005 | 15.71036 | 0.47349 | 10.09268 |
March | 514.00000 | 27.00000 | 21.91417 | 0.62566 | 13.91914 |
April | 485.00000 | 27.00000 | 26.76434 | 0.73328 | 16.74437 |
May | 508.00000 | 27.00071 | 31.33433 | 0.10080 | 5.84896 |
June | 496.00000 | 27.00012 | 36.25612 | 0.26476 | 7.03497 |
July | 497.00000 | 27.00008 | 38.96830 | 0.34319 | 7.84198 |
August | 514.00000 | 27.00026 | 37.40936 | 0.32707 | 7.65864 |
September | 485.00000 | 27.00053 | 37.89245 | 0.15947 | 6.09727 |
October | 502.00000 | 27.00001 | 30.84367 | 0.71524 | 16.22683 |
November | 489.00000 | 27.00000 | 25.51765 | 0.62212 | 13.47516 |
December | 497.00000 | 27.00000 | 18.97797 | 0.51454 | 10.89609 |
Annual Sum or Average | 5943.00000 | 26.96059 | 28.32780 | 0.43634 | 10.42444 |
Minimum of Months | 454.00000 | 26.53165 | 15.71036 | 0.10080 | 5.84896 |
Maximum of Months | 514.00000 | 27.00071 | 38.96830 | 0.73328 | 16.74437 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.15596 | 30.00896 | 0.99719 | 26.04094 |
February | 454.00000 | 24.67840 | 28.85922 | 0.64493 | 13.77857 |
March | 514.00000 | 25.56162 | 29.69968 | 0.97306 | 25.74704 |
April | 485.00000 | 24.67413 | 29.96082 | 0.94231 | 24.59315 |
May | 508.00000 | 27.07277 | 32.61573 | 0.42989 | 8.92972 |
June | 496.00000 | 25.84775 | 41.60835 | 0.41055 | 10.86421 |
July | 497.00000 | 26.87176 | 44.71110 | 0.97429 | 25.36588 |
August | 514.00000 | 26.73174 | 42.42667 | 1.11508 | 32.16078 |
September | 485.00000 | 27.01082 | 40.07334 | 0.60592 | 12.91878 |
October | 502.00000 | 25.02516 | 33.29629 | 0.84816 | 20.89047 |
November | 489.00000 | 25.37735 | 29.84368 | 0.97429 | 25.71445 |
December | 497.00000 | 24.46988 | 28.76032 | 0.91118 | 23.03367 |
Annual Sum or Average | 5943.00000 | 25.88670 | 34.36585 | 0.82095 | 20.91988 |
Minimum of Months | 454.00000 | 24.46988 | 28.76032 | 0.41055 | 8.92972 |
Maximum of Months | 514.00000 | 27.15596 | 44.71110 | 1.11508 | 32.16078 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.42967 | 18.31763 | 0.07315 | 5.87593 |
February | 454.00000 | 23.21221 | 17.34680 | 0.01080 | 5.73044 |
March | 514.00000 | 23.86266 | 24.10561 | 0.21518 | 6.51325 |
April | 485.00000 | 24.10736 | 27.88137 | 0.29950 | 7.14591 |
May | 508.00000 | 24.14616 | 33.10475 | -0.5430 | 11.86231 |
June | 496.00000 | 24.33708 | 41.83951 | -0.3918 | 8.87638 |
July | 497.00000 | 24.55130 | 47.48775 | -0.2710 | 7.62365 |
August | 514.00000 | 24.44181 | 45.95784 | -0.2954 | 7.76049 |
September | 485.00000 | 24.42751 | 42.12025 | -0.3389 | 8.59484 |
October | 502.00000 | 24.34223 | 32.59972 | 0.41719 | 9.16467 |
November | 489.00000 | 24.36441 | 26.00081 | 0.36923 | 8.38376 |
December | 497.00000 | 23.95558 | 20.06161 | 0.21773 | 6.47219 |
Annual Sum or Average | 5943.00000 | 24.10353 | 31.50856 | -0.0211 | 7.85075 |
Minimum of Months | 454.00000 | 23.21221 | 17.34680 | -0.5430 | 5.73044 |
Maximum of Months | 514.00000 | 24.55130 | 47.48775 | 0.41719 | 11.86231 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.59879 | 20.31392 | 0.10244 | 5.75573 |
February | 454.00000 | 23.54018 | 18.54955 | 0.07452 | 5.64539 |
March | 514.00000 | 24.00772 | 24.60155 | 0.26333 | 6.92889 |
April | 485.00000 | 24.19724 | 28.00965 | 0.34776 | 7.76773 |
May | 508.00000 | 24.18609 | 33.97056 | -0.4851 | 10.48109 |
June | 496.00000 | 24.21017 | 45.27947 | -0.3633 | 8.20992 |
July | 497.00000 | 24.27031 | 53.37912 | -0.2669 | 6.80781 |
August | 514.00000 | 24.26322 | 50.36652 | -0.2802 | 6.96778 |
September | 485.00000 | 24.27620 | 45.49658 | -0.3519 | 8.19279 |
October | 502.00000 | 24.24847 | 33.74389 | 0.39653 | 8.57803 |
November | 489.00000 | 24.28920 | 27.15130 | 0.35042 | 7.89669 |
December | 497.00000 | 23.99036 | 21.16688 | 0.21928 | 6.30825 |
Annual Sum or Average | 5943.00000 | 24.09309 | 33.61680 | -0.0009 | 7.47417 |
Minimum of Months | 454.00000 | 23.54018 | 18.54955 | -0.4851 | 5.64539 |
Maximum of Months | 514.00000 | 24.28920 | 53.37912 | 0.39653 | 10.48109 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.11469 | 19.25121 | -0.2884 | 8.93692 |
February | 454.00000 | 22.32039 | 19.05659 | -0.2375 | 7.66349 |
March | 514.00000 | 23.31286 | 25.89038 | 0.07217 | 6.48089 |
April | 485.00000 | 23.67814 | 29.61010 | 0.19885 | 6.31791 |
May | 508.00000 | 24.00548 | 34.58259 | -0.5686 | 12.41614 |
June | 496.00000 | 24.06123 | 45.97655 | -0.4407 | 9.58240 |
July | 497.00000 | 24.16793 | 54.12807 | -0.3420 | 7.78609 |
August | 514.00000 | 24.16346 | 51.12617 | -0.3623 | 8.02808 |
September | 485.00000 | 24.04516 | 46.44822 | -0.4610 | 10.14867 |
October | 502.00000 | 23.75683 | 35.45644 | 0.25691 | 6.86060 |
November | 489.00000 | 23.52151 | 29.45659 | 0.14112 | 6.00594 |
December | 497.00000 | 22.46770 | 22.69911 | -0.1745 | 7.21118 |
Annual Sum or Average | 5943.00000 | 23.47614 | 34.58681 | -0.1843 | 8.12793 |
Minimum of Months | 454.00000 | 22.11469 | 19.05659 | -0.5686 | 6.00594 |
Maximum of Months | 514.00000 | 24.16793 | 54.12807 | 0.25691 | 12.41614 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.57615 | 20.53574 | -0.6959 | 18.26447 |
February | 454.00000 | 20.76079 | 20.26978 | -0.6452 | 17.09240 |
March | 514.00000 | 21.81648 | 27.72057 | -0.3082 | 10.96707 |
April | 485.00000 | 22.46606 | 31.71386 | -0.1036 | 7.54218 |
May | 508.00000 | 23.42676 | 35.87901 | -0.7698 | 19.55824 |
June | 496.00000 | 23.85536 | 46.77541 | -0.4933 | 11.39705 |
July | 497.00000 | 24.08009 | 54.90215 | -0.3448 | 8.11256 |
August | 514.00000 | 23.99478 | 52.10715 | -0.4051 | 9.06846 |
September | 485.00000 | 23.46463 | 48.49006 | -0.6626 | 16.70352 |
October | 502.00000 | 22.27501 | 38.57113 | -0.1143 | 8.33464 |
November | 489.00000 | 21.58262 | 32.05818 | -0.3504 | 9.99005 |
December | 497.00000 | 20.67325 | 24.53151 | -0.6412 | 16.71051 |
Annual Sum or Average | 5943.00000 | 22.42797 | 36.24207 | -0.4602 | 12.78493 |
Minimum of Months | 454.00000 | 20.57615 | 20.26978 | -0.7698 | 7.54218 |
Maximum of Months | 514.00000 | 24.08009 | 54.90215 | -0.1036 | 19.55824 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.67815 | 19.09853 | -0.6486 | 14.90019 |
February | 454.00000 | 20.74085 | 19.00416 | -0.6297 | 14.46238 |
March | 514.00000 | 21.83249 | 25.91087 | -0.2721 | 9.37439 |
April | 485.00000 | 22.71228 | 29.23629 | -0.0170 | 6.53924 |
May | 508.00000 | 23.46281 | 34.77703 | -0.7231 | 17.97888 |
June | 496.00000 | 24.00970 | 45.20739 | -0.4002 | 9.44486 |
July | 497.00000 | 24.24679 | 53.07699 | -0.2291 | 6.68134 |
August | 514.00000 | 24.09729 | 50.25203 | -0.3134 | 7.85868 |
September | 485.00000 | 23.63724 | 46.49198 | -0.5693 | 13.76781 |
October | 502.00000 | 22.71166 | 35.54532 | 0.01746 | 6.58599 |
November | 489.00000 | 22.07584 | 28.78878 | -0.1944 | 7.09330 |
December | 497.00000 | 20.94640 | 22.61542 | -0.5350 | 12.09956 |
Annual Sum or Average | 5943.00000 | 22.60971 | 34.27923 | -0.3750 | 10.54675 |
Minimum of Months | 454.00000 | 20.67815 | 19.00416 | -0.7231 | 6.53924 |
Maximum of Months | 514.00000 | 24.24679 | 53.07699 | 0.01746 | 17.97888 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.63781 | 18.63940 | -0.6482 | 14.75266 |
February | 454.00000 | 20.71946 | 18.55234 | -0.6200 | 14.29267 |
March | 514.00000 | 21.65798 | 25.94552 | -0.2741 | 9.05875 |
April | 485.00000 | 22.37374 | 29.40176 | -0.0343 | 7.37020 |
May | 508.00000 | 23.12431 | 35.03779 | -0.7249 | 20.27720 |
June | 496.00000 | 23.65948 | 45.81966 | -0.4066 | 11.41741 |
July | 497.00000 | 23.86194 | 54.04294 | -0.2512 | 8.72858 |
August | 514.00000 | 23.62716 | 51.44743 | -0.3725 | 10.44096 |
September | 485.00000 | 23.28213 | 47.18301 | -0.5848 | 16.21386 |
October | 502.00000 | 22.31791 | 35.94310 | -0.0271 | 7.09008 |
November | 489.00000 | 21.58457 | 29.15129 | -0.2846 | 8.00828 |
December | 497.00000 | 20.74581 | 22.42489 | -0.5849 | 12.98143 |
Annual Sum or Average | 5943.00000 | 22.31150 | 34.58388 | -0.4001 | 11.70870 |
Minimum of Months | 454.00000 | 20.63781 | 18.55234 | -0.7249 | 7.09008 |
Maximum of Months | 514.00000 | 23.86194 | 54.04294 | -0.0271 | 20.27720 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.98013 | 18.56613 | -0.5593 | 14.69120 |
February | 454.00000 | 20.99384 | 18.43645 | -0.5448 | 14.48523 |
March | 514.00000 | 22.16197 | 25.41682 | -0.1505 | 9.40162 |
April | 485.00000 | 22.55931 | 29.14928 | -0.0093 | 7.85519 |
May | 508.00000 | 23.16003 | 35.08949 | -0.7610 | 21.13619 |
June | 496.00000 | 23.69203 | 45.83455 | -0.4560 | 12.12787 |
July | 497.00000 | 24.04302 | 53.54971 | -0.2412 | 8.23355 |
August | 514.00000 | 23.92400 | 50.56317 | -0.2918 | 9.19737 |
September | 485.00000 | 23.58454 | 46.37371 | -0.4793 | 14.33250 |
October | 502.00000 | 22.72909 | 35.16335 | 0.07747 | 8.44849 |
November | 489.00000 | 22.02638 | 28.59479 | -0.1829 | 8.54106 |
December | 497.00000 | 21.07443 | 22.31091 | -0.5017 | 12.68128 |
Annual Sum or Average | 5943.00000 | 22.58994 | 34.20321 | -0.3407 | 11.75117 |
Minimum of Months | 454.00000 | 20.98013 | 18.43645 | -0.7610 | 7.85519 |
Maximum of Months | 514.00000 | 24.04302 | 53.54971 | 0.07747 | 21.13619 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.90902 | 18.22400 | -0.5461 | 12.08601 |
February | 454.00000 | 21.06351 | 18.04656 | -0.4929 | 11.17982 |
March | 514.00000 | 22.29140 | 24.83195 | -0.0721 | 7.80284 |
April | 485.00000 | 23.12123 | 27.91374 | 0.19042 | 8.09315 |
May | 508.00000 | 23.26600 | 34.64964 | -0.6308 | 17.85982 |
June | 496.00000 | 23.90639 | 45.02889 | -0.2568 | 9.89351 |
July | 497.00000 | 24.30460 | 52.52207 | -0.0218 | 7.37536 |
August | 514.00000 | 24.25771 | 49.40669 | -0.0571 | 7.31284 |
September | 485.00000 | 23.43078 | 46.61996 | -0.4917 | 14.12049 |
October | 502.00000 | 22.59342 | 35.16218 | 0.07266 | 7.13714 |
November | 489.00000 | 22.22611 | 27.99078 | -0.0898 | 6.77671 |
December | 497.00000 | 21.40557 | 21.46889 | -0.3578 | 8.52903 |
Annual Sum or Average | 5943.00000 | 22.74411 | 33.60219 | -0.2279 | 9.83796 |
Minimum of Months | 454.00000 | 20.90902 | 18.04656 | -0.6308 | 6.77671 |
Maximum of Months | 514.00000 | 24.30460 | 52.52207 | 0.19042 | 17.85982 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.93243 | 18.82749 | -0.9203 | 25.29549 |
February | 454.00000 | 19.99744 | 18.90861 | -0.8836 | 23.90110 |
March | 514.00000 | 20.77347 | 27.16214 | -0.5658 | 15.04818 |
April | 485.00000 | 21.25585 | 31.41151 | -0.3715 | 9.65458 |
May | 508.00000 | 22.38989 | 36.85259 | -1.0615 | 31.06897 |
June | 496.00000 | 23.30904 | 47.19681 | -0.6264 | 15.66648 |
July | 497.00000 | 23.75198 | 55.39553 | -0.4011 | 9.60141 |
August | 514.00000 | 23.45403 | 52.52383 | -0.5399 | 13.02540 |
September | 485.00000 | 22.57267 | 49.49300 | -0.9132 | 25.83219 |
October | 502.00000 | 21.25423 | 38.34993 | -0.3323 | 9.02562 |
November | 489.00000 | 20.68874 | 30.99111 | -0.5586 | 12.87349 |
December | 497.00000 | 19.97043 | 22.95380 | -0.8637 | 23.34527 |
Annual Sum or Average | 5943.00000 | 21.62654 | 35.95993 | -0.6685 | 17.82676 |
Minimum of Months | 454.00000 | 19.93243 | 18.82749 | -1.0615 | 9.02562 |
Maximum of Months | 514.00000 | 23.75198 | 55.39553 | -0.3323 | 31.06897 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.79183 | 18.49054 | -0.9390 | 26.12461 |
February | 385.00000 | 19.88009 | 18.54978 | -0.8893 | 24.44826 |
March | 433.00000 | 20.91737 | 26.54378 | -0.4952 | 13.51264 |
April | 410.00000 | 21.72911 | 30.39645 | -0.2193 | 9.36740 |
May | 430.00000 | 22.74187 | 35.85839 | -0.8729 | 26.10731 |
June | 418.00000 | 23.39663 | 46.80393 | -0.5075 | 14.74448 |
July | 422.00000 | 23.85080 | 54.86573 | -0.2775 | 10.05486 |
August | 433.00000 | 23.46378 | 52.02719 | -0.4553 | 13.08956 |
September | 410.00000 | 22.85707 | 48.60403 | -0.7532 | 21.97923 |
October | 427.00000 | 21.56187 | 37.31626 | -0.2373 | 8.67815 |
November | 417.00000 | 20.78206 | 30.15462 | -0.5304 | 12.54313 |
December | 422.00000 | 19.82488 | 22.63788 | -0.8954 | 24.53064 |
Annual Sum or Average | 5034.00000 | 21.74519 | 35.28938 | -0.5877 | 17.05585 |
Minimum of Months | 385.00000 | 19.79183 | 18.49054 | -0.9390 | 8.67815 |
Maximum of Months | 433.00000 | 23.85080 | 54.86573 | -0.2193 | 26.12461 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.47330 | 18.26561 | -0.7212 | 20.40682 |
February | 454.00000 | 20.50244 | 18.35433 | -0.6900 | 19.66234 |
March | 514.00000 | 21.74834 | 25.99070 | -0.2636 | 11.42614 |
April | 485.00000 | 22.08632 | 29.98333 | -0.1354 | 9.28745 |
May | 508.00000 | 22.87603 | 35.84808 | -0.8591 | 25.11993 |
June | 496.00000 | 23.43460 | 46.81965 | -0.5494 | 14.88787 |
July | 497.00000 | 23.89116 | 54.79399 | -0.3081 | 9.73805 |
August | 514.00000 | 23.71945 | 51.51093 | -0.3794 | 11.42197 |
September | 485.00000 | 23.34371 | 47.28349 | -0.5615 | 17.50604 |
October | 502.00000 | 22.33207 | 36.05308 | -0.0205 | 9.29613 |
November | 489.00000 | 21.50003 | 29.66552 | -0.3258 | 10.80842 |
December | 497.00000 | 20.42438 | 22.41587 | -0.7050 | 18.93560 |
Annual Sum or Average | 5943.00000 | 22.20820 | 34.86862 | -0.4587 | 14.85071 |
Minimum of Months | 454.00000 | 20.42438 | 18.26561 | -0.8591 | 9.28745 |
Maximum of Months | 514.00000 | 23.89116 | 54.79399 | -0.0205 | 25.11993 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.04183 | 18.44039 | -0.8630 | 23.13977 |
February | 454.00000 | 20.16368 | 18.47376 | -0.8060 | 21.34824 |
March | 514.00000 | 21.14141 | 26.57197 | -0.4272 | 12.28908 |
April | 485.00000 | 21.71371 | 30.42156 | -0.2095 | 9.28806 |
May | 508.00000 | 22.59191 | 36.25876 | -0.8996 | 27.51102 |
June | 496.00000 | 23.33729 | 46.90230 | -0.4943 | 15.33276 |
July | 497.00000 | 23.73577 | 55.16088 | -0.2915 | 10.67060 |
August | 514.00000 | 23.46201 | 52.24847 | -0.4205 | 13.00128 |
September | 485.00000 | 22.67181 | 49.05265 | -0.7937 | 23.55912 |
October | 502.00000 | 21.46965 | 37.65949 | -0.2438 | 8.57812 |
November | 489.00000 | 20.87590 | 30.46363 | -0.4896 | 11.47287 |
December | 497.00000 | 20.09624 | 22.54651 | -0.8042 | 20.99928 |
Annual Sum or Average | 5943.00000 | 21.78883 | 35.47168 | -0.5603 | 16.40172 |
Minimum of Months | 454.00000 | 20.04183 | 18.44039 | -0.8996 | 8.57812 |
Maximum of Months | 514.00000 | 23.73577 | 55.16088 | -0.2095 | 27.51102 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.75366 | 19.11839 | -1.0293 | 29.88586 |
February | 454.00000 | 19.82613 | 19.12625 | -0.9902 | 28.39020 |
March | 514.00000 | 20.39798 | 27.85608 | -0.7054 | 19.40768 |
April | 485.00000 | 20.75799 | 32.38412 | -0.5224 | 13.08576 |
May | 508.00000 | 21.78784 | 38.09710 | -1.2626 | 40.23677 |
June | 496.00000 | 22.79089 | 48.80297 | -0.7656 | 21.10598 |
July | 497.00000 | 23.32527 | 57.34910 | -0.5004 | 12.83954 |
August | 514.00000 | 22.94727 | 54.51558 | -0.6754 | 17.82026 |
September | 485.00000 | 21.91194 | 51.55060 | -1.1306 | 35.16080 |
October | 502.00000 | 20.57249 | 39.97832 | -0.5325 | 14.08989 |
November | 489.00000 | 20.15806 | 32.06760 | -0.7510 | 19.59177 |
December | 497.00000 | 19.77232 | 23.45770 | -0.9864 | 28.34205 |
Annual Sum or Average | 5943.00000 | 21.17928 | 37.15276 | -0.8198 | 23.29736 |
Minimum of Months | 454.00000 | 19.75366 | 19.11839 | -1.2626 | 12.83954 |
Maximum of Months | 514.00000 | 23.32527 | 57.34910 | -0.5004 | 40.23677 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.76671 | 19.05976 | -1.0016 | 28.86063 |
February | 454.00000 | 19.83735 | 19.08645 | -0.9533 | 27.23538 |
March | 514.00000 | 20.58282 | 27.51885 | -0.6106 | 17.52695 |
April | 485.00000 | 21.41508 | 31.30533 | -0.3188 | 11.70287 |
May | 508.00000 | 22.59176 | 36.43651 | -0.9303 | 28.87824 |
June | 496.00000 | 23.37578 | 47.19955 | -0.4932 | 15.04585 |
July | 497.00000 | 23.80535 | 55.56458 | -0.2541 | 10.13904 |
August | 514.00000 | 23.42400 | 52.88402 | -0.4406 | 13.46559 |
September | 485.00000 | 22.68833 | 49.38799 | -0.8164 | 24.78229 |
October | 502.00000 | 20.97823 | 39.01015 | -0.4061 | 12.24304 |
November | 489.00000 | 20.25178 | 31.84675 | -0.7107 | 18.37184 |
December | 497.00000 | 19.77194 | 23.42897 | -0.9744 | 27.89497 |
Annual Sum or Average | 5943.00000 | 21.55507 | 36.18261 | -0.6572 | 19.62712 |
Minimum of Months | 454.00000 | 19.76671 | 19.05976 | -1.0016 | 10.13904 |
Maximum of Months | 514.00000 | 23.80535 | 55.56458 | -0.2541 | 28.87824 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.06581 | 18.75761 | -0.8755 | 25.47511 |
February | 454.00000 | 20.10446 | 18.82734 | -0.8399 | 25.03903 |
March | 514.00000 | 21.10796 | 26.92209 | -0.4532 | 15.43002 |
April | 485.00000 | 21.50592 | 31.12469 | -0.3017 | 12.02708 |
May | 508.00000 | 22.35163 | 36.98744 | -1.0392 | 33.03710 |
June | 496.00000 | 23.00793 | 48.25657 | -0.6643 | 19.50159 |
July | 497.00000 | 23.52141 | 56.59911 | -0.3925 | 12.61378 |
August | 514.00000 | 23.30484 | 53.27635 | -0.4904 | 15.35958 |
September | 485.00000 | 22.81221 | 49.03493 | -0.7428 | 24.24114 |
October | 502.00000 | 21.52817 | 37.87851 | -0.2428 | 12.30885 |
November | 489.00000 | 20.75058 | 31.02137 | -0.5583 | 16.02946 |
December | 497.00000 | 19.99519 | 23.16879 | -0.8722 | 24.73701 |
Annual Sum or Average | 5943.00000 | 21.68457 | 36.11263 | -0.6214 | 19.62117 |
Minimum of Months | 454.00000 | 19.99519 | 18.75761 | -1.0392 | 12.02708 |
Maximum of Months | 514.00000 | 23.52141 | 56.59911 | -0.2428 | 33.03710 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83296 | 18.90100 | -0.9679 | 27.51484 |
February | 454.00000 | 19.93497 | 18.89369 | -0.9094 | 25.67709 |
March | 514.00000 | 20.77599 | 27.22624 | -0.5518 | 15.97624 |
April | 485.00000 | 21.39328 | 31.16581 | -0.3162 | 11.47241 |
May | 508.00000 | 22.32735 | 36.93162 | -1.0013 | 32.48025 |
June | 496.00000 | 23.14786 | 47.78224 | -0.5429 | 17.90407 |
July | 497.00000 | 23.56306 | 56.39007 | -0.3223 | 12.37719 |
August | 514.00000 | 23.23595 | 53.47274 | -0.4790 | 15.51154 |
September | 485.00000 | 22.36481 | 50.21092 | -0.9072 | 28.64228 |
October | 502.00000 | 21.00788 | 38.86067 | -0.3882 | 11.98837 |
November | 489.00000 | 20.40622 | 31.49046 | -0.6524 | 16.63990 |
December | 497.00000 | 19.83826 | 23.26106 | -0.9227 | 25.92164 |
Annual Sum or Average | 5943.00000 | 21.49926 | 36.33986 | -0.6617 | 20.13801 |
Minimum of Months | 454.00000 | 19.83296 | 18.89369 | -1.0013 | 11.47241 |
Maximum of Months | 514.00000 | 23.56306 | 56.39007 | -0.3162 | 32.48025 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.100932E+10 | 26526.61 | 03-JAN-22:02 | 90.41 | 0.450808E+10 | 0.00 | 0.551740E+10 | 0.54 | 4.50 | 21-JAN-06:23 | 0.00 | 0.00 |
February | 0.367897E+11 | 139344.51 | 28-FEB-07:02 | 205.38 | 0.165491E+12 | 0.00 | 0.202281E+12 | 1.37 | 6.46 | 28-FEB-07:02 | 0.00 | 0.00 |
March | 0.662373E+11 | 257910.18 | 15-MAR-12:50 | 684.83 | 0.340491E+12 | 0.00 | 0.406728E+12 | 4.44 | 7.08 | 14-MAR-14:30 | 0.00 | 0.00 |
April | 0.558940E+11 | 169861.32 | 25-APR-13:54 | 555.40 | 0.267530E+12 | 0.00 | 0.323424E+12 | 3.68 | 6.89 | 25-APR-13:54 | 0.00 | 0.00 |
May | 0.606995E+11 | 244517.76 | 10-MAY-14:20 | 265.98 | 0.331985E+12 | 0.00 | 0.392685E+12 | 1.77 | 7.01 | 16-MAY-14:40 | 0.00 | 0.00 |
June | 0.209670E+12 | 256220.46 | 21-JUN-13:40 | 511.56 | 0.126931E+13 | 0.00 | 0.147898E+13 | 3.98 | 7.10 | 29-JUN-05:04 | 0.00 | 0.00 |
July | 0.291829E+12 | 272342.43 | 21-JUL-05:03 | 685.90 | 0.182827E+13 | 0.00 | 0.212010E+13 | 5.30 | 7.14 | 06-JUL-15:20 | 0.00 | 0.00 |
August | 0.278246E+12 | 264854.75 | 15-AUG-05:02 | 704.64 | 0.173360E+13 | 0.00 | 0.201184E+13 | 5.37 | 7.15 | 16-AUG-11:20 | 0.00 | 0.00 |
September | 0.122831E+12 | 257533.14 | 20-SEP-16:00 | 373.93 | 0.727170E+12 | 0.00 | 0.850001E+12 | 2.77 | 7.15 | 20-SEP-14:00 | 0.00 | 0.00 |
October | 0.620210E+11 | 243896.04 | 11-OCT-15:10 | 276.11 | 0.304839E+12 | 0.00 | 0.366860E+12 | 1.75 | 7.01 | 11-OCT-13:30 | 0.00 | 0.00 |
November | 0.548912E+11 | 167629.81 | 16-NOV-14:41 | 641.11 | 0.262839E+12 | 0.00 | 0.317731E+12 | 4.25 | 6.88 | 16-NOV-14:41 | 0.00 | 0.00 |
December | 0.532280E+11 | 135866.40 | 22-DEC-11:20 | 604.88 | 0.254701E+12 | 0.00 | 0.307929E+12 | 3.89 | 6.38 | 22-DEC-11:20 | 0.00 | 0.00 |
Annual Sum or Average | 0.129335E+13 | 5600.15 | 0.749073E+13 | 0.00 | 0.878408E+13 | 3.27 | 0.00 | 0.00 | ||||
Minimum of Months | 0.100932E+10 | 26526.61 | 90.41 | 0.450808E+10 | 0.00 | 0.551740E+10 | 0.54 | 4.50 | 0.00 | 0.00 | ||
Maximum of Months | 0.291829E+12 | 272342.43 | 704.64 | 0.182827E+13 | 0.00 | 0.212010E+13 | 5.37 | 7.15 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.971514E+09 | 157738.80 | 14-MAR-13:10 | 2.00 | 0.622703E+10 | 0.00 | 0.719855E+10 | 0.02 | 6.71 | 14-MAR-13:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 86051318.73 | 143418.86 | 10-MAY-15:40 | 0.17 | 0.552757E+09 | 0.00 | 0.638809E+09 | 0.00 | 6.42 | 10-MAY-15:40 | 0.00 | 0.00 |
June | 0.254248E+11 | 210134.17 | 21-JUN-09:11 | 46.83 | 0.162676E+12 | 0.00 | 0.188101E+12 | 0.41 | 6.88 | 08-JUN-13:31 | 0.00 | 0.00 |
July | 0.779094E+11 | 250819.02 | 29-JUL-05:05 | 140.04 | 0.499401E+12 | 0.00 | 0.577310E+12 | 1.20 | 6.87 | 14-JUL-10:05 | 0.00 | 0.00 |
August | 0.722411E+11 | 264854.75 | 15-AUG-05:02 | 131.71 | 0.468697E+12 | 0.00 | 0.540938E+12 | 1.14 | 6.98 | 22-AUG-13:58 | 0.00 | 0.00 |
September | 0.528428E+10 | 188267.73 | 15-SEP-12:05 | 10.58 | 0.336760E+11 | 0.00 | 0.389603E+11 | 0.09 | 6.78 | 14-SEP-05:07 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.181917E+12 | 331.33 | 0.117123E+13 | 0.00 | 0.135315E+13 | 0.24 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.779094E+11 | 264854.75 | 140.04 | 0.499401E+12 | 0.00 | 0.577310E+12 | 1.20 | 6.98 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 305970.88 | 21-JAN-06:13 | 21.02 | 21.00 | 2.06 |
February | 832249.46 | 26.30 | 58.31 | 01-FEB-07:18 | 693943.63 | 17-FEB-12:06 | 21.48 | 21.23 | 26.47 |
March | 0.155479E+10 | 59.84 | 27182.00 | 14-MAR-10:40 | 2008670.00 | 15-MAR-12:50 | 21.32 | 20.83 | 49.71 |
April | 0.106838E+09 | 97.36 | 6934.39 | 08-APR-13:20 | 1172630.45 | 25-APR-13:56 | 21.31 | 20.91 | 50.98 |
May | 0.253311E+10 | 180.96 | 27182.00 | 10-MAY-12:20 | 1878730.82 | 26-MAY-16:00 | 21.58 | 21.15 | 27.78 |
June | 0.234456E+11 | 497.39 | 27182.00 | 01-JUN-12:30 | 2036866.97 | 30-JUN-15:20 | 23.41 | 21.81 | 61.88 |
July | 0.446187E+11 | 641.55 | 27182.00 | 01-JUL-12:00 | 1961081.63 | 07-JUL-11:00 | 24.50 | 22.28 | 78.65 |
August | 0.360389E+11 | 607.76 | 27182.00 | 01-AUG-11:20 | 2037016.90 | 23-AUG-11:20 | 23.87 | 21.70 | 80.98 |
September | 0.124423E+11 | 315.64 | 27182.00 | 08-SEP-10:50 | 2032571.33 | 20-SEP-13:30 | 22.31 | 21.38 | 43.42 |
October | 0.106720E+10 | 216.90 | 24845.91 | 11-OCT-15:00 | 1960373.89 | 11-OCT-15:10 | 22.02 | 21.62 | 31.95 |
November | 0.139195E+09 | 56.20 | 6685.36 | 16-NOV-13:06 | 1164346.75 | 16-NOV-13:06 | 21.25 | 20.84 | 49.96 |
December | 1355920.07 | 7.96 | 686.93 | 01-DEC-11:10 | 828165.36 | 19-DEC-11:58 | 21.17 | 20.77 | 43.64 |
Annual Sum or Average | 0.121949E+12 | 2707.88 | 22.11 | 21.30 | 45.72 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 305970.88 | 21.02 | 20.77 | 2.06 | ||
Maximum of Months | 0.446187E+11 | 641.55 | 27182.00 | 2037016.90 | 24.50 | 22.28 | 80.98 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 21.02 | 21.02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 21.48 | 21.48 | 0.00 |
March | 0.103914E+09 | 1.08 | 27182.00 | 14-MAR-12:40 | 1723769.93 | 15-MAR-13:05 | 21.32 | 21.32 | 0.12 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.31 | 21.31 | 0.00 |
May | 16309200.70 | 0.17 | 27182.00 | 10-MAY-15:40 | 1397937.95 | 10-MAY-15:40 | 21.58 | 21.58 | 0.02 |
June | 0.565634E+10 | 58.00 | 27182.00 | 01-JUN-15:50 | 1815563.17 | 30-JUN-15:40 | 23.41 | 23.12 | 6.31 |
July | 0.170154E+11 | 174.96 | 27182.00 | 03-JUL-10:40 | 1725787.02 | 06-JUL-16:00 | 24.50 | 23.64 | 18.30 |
August | 0.126053E+11 | 135.94 | 27182.00 | 01-AUG-12:40 | 1722320.47 | 04-AUG-10:40 | 23.87 | 23.17 | 15.09 |
September | 0.109886E+10 | 11.50 | 27182.00 | 08-SEP-13:10 | 1615530.97 | 20-SEP-14:10 | 22.31 | 22.25 | 1.20 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 22.02 | 22.02 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 21.25 | 21.25 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 21.17 | 21.17 | 0.00 |
Annual Sum or Average | 0.364961E+11 | 381.65 | 22.11 | 21.95 | 3.47 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 | 21.02 | 0.00 | ||
Maximum of Months | 0.170154E+11 | 174.96 | 27182.00 | 1815563.17 | 24.50 | 23.64 | 18.30 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.813183E+12 | 0.00 | 611.79 | 3552217.06 | 02-JAN-04:01 | 0.00 | 33.68 | 70.10 | 1.76 | 0.00 | 0.09 | 0.99 | 02-JAN-04:01 |
February | 0.729147E+12 | 0.00 | 566.83 | 2694990.96 | 18-FEB-05:01 | 0.00 | 35.17 | 71.71 | 1.78 | 0.00 | 0.08 | 0.75 | 18-FEB-05:01 |
March | 0.322095E+12 | 0.00 | 479.24 | 2938011.79 | 03-MAR-05:01 | 0.00 | 28.05 | 57.31 | 0.67 | 0.00 | 0.03 | 0.82 | 03-MAR-05:01 |
April | 0.984282E+11 | 0.00 | 316.04 | 2703693.73 | 06-APR-04:01 | 0.00 | 24.05 | 43.56 | 0.22 | 0.00 | 0.01 | 0.76 | 06-APR-04:01 |
May | 0.212658E+11 | 0.00 | 162.95 | 1736157.88 | 08-MAY-05:03 | 0.00 | 22.30 | 31.75 | 0.04 | 0.00 | 0.00 | 0.49 | 08-MAY-05:03 |
June | 0.277914E+10 | 0.00 | 49.86 | 725659.79 | 14-JUN-05:01 | 0.00 | 21.84 | 24.88 | 0.01 | 0.00 | 0.00 | 0.20 | 14-JUN-05:01 |
July | 0.173297E+09 | 0.00 | 17.58 | 11520.18 | 06-JUL-05:10 | 0.00 | 21.08 | 22.13 | 0.00 | 0.00 | 0.00 | 0.00 | 06-JUL-05:10 |
August | 0.112583E+10 | 0.00 | 39.66 | 84763.07 | 31-AUG-05:24 | 0.00 | 20.44 | 22.84 | 0.00 | 0.00 | 0.00 | 0.02 | 31-AUG-05:24 |
September | 0.136319E+11 | 0.00 | 132.99 | 1145092.20 | 30-SEP-05:03 | 0.00 | 21.43 | 29.53 | 0.03 | 0.00 | 0.00 | 0.32 | 30-SEP-05:03 |
October | 0.874230E+11 | 0.00 | 336.02 | 2901026.02 | 17-OCT-04:01 | 0.00 | 23.46 | 43.19 | 0.19 | 0.00 | 0.01 | 0.81 | 17-OCT-04:01 |
November | 0.196088E+12 | 0.00 | 437.64 | 2861353.16 | 15-NOV-05:01 | 0.00 | 26.52 | 53.10 | 0.44 | 0.00 | 0.02 | 0.80 | 15-NOV-05:01 |
December | 0.688013E+12 | 0.00 | 604.89 | 2840983.49 | 30-DEC-05:01 | 0.00 | 32.62 | 68.49 | 1.50 | 0.00 | 0.07 | 0.80 | 30-DEC-05:01 |
Annual Sum or Average | 0.297335E+13 | 0.00 | 3755.49 | 0.00 | 25.84 | 44.74 | 0.55 | 0.00 | 0.03 | ||||
Minimum of Months | 0.173297E+09 | 0.00 | 17.58 | 11520.18 | 0.00 | 20.44 | 22.13 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.813183E+12 | 0.00 | 611.79 | 3552217.06 | 0.00 | 35.17 | 71.71 | 1.78 | 0.00 | 0.09 | 0.99 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 728034.12 | 0.00 | 2.77 | 728034.12 | 0.00 | 0.00 | 0.00 | 0.00 | 2416.54 | 19-JAN-17:05 | 2416.54 | 19-JAN-17:05 | 0.00 | 0.00 | 0.00 |
February | 118407.09 | 0.00 | 1.27 | 118407.09 | 0.00 | 0.00 | 0.00 | 0.00 | 957.39 | 28-FEB-17:01 | 957.39 | 28-FEB-17:01 | 0.00 | 0.00 | 0.00 |
March | 0.709597E+10 | 0.00 | 38.93 | 0.692450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 120191.35 | 15-MAR-13:50 | 120191.35 | 15-MAR-13:50 | 0.00 | 0.00 | 0.00 |
April | 0.293594E+10 | 0.00 | 58.61 | 0.293594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58183.21 | 07-APR-14:00 | 58183.21 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.244533E+11 | 0.00 | 225.24 | 0.240573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115313.92 | 10-MAY-14:30 | 108334.64 | 23-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.934731E+11 | 0.00 | 399.13 | 0.793829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 195230.94 | 29-JUN-04:11 | 175849.10 | 12-JUN-04:11 | 0.00 | 0.00 | 0.00 |
July | 0.158252E+12 | 0.00 | 489.90 | 0.132262E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 219620.97 | 17-JUL-04:12 | 171230.86 | 17-JUL-04:12 | 0.00 | 0.00 | 0.00 |
August | 0.141971E+12 | 0.00 | 488.77 | 0.123936E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 204948.03 | 08-AUG-04:11 | 168757.89 | 14-AUG-04:11 | 0.00 | 0.00 | 0.00 |
September | 0.595005E+11 | 0.00 | 327.34 | 0.523716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 205904.71 | 14-SEP-05:02 | 141720.45 | 16-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.873537E+10 | 0.00 | 99.82 | 0.872877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 112380.57 | 11-OCT-15:10 | 112380.57 | 11-OCT-15:10 | 0.00 | 0.00 | 0.00 |
November | 0.138038E+10 | 0.00 | 24.36 | 0.138038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78134.91 | 27-NOV-06:03 | 78134.91 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 8382228.71 | 0.00 | 3.87 | 8382228.71 | 0.00 | 0.00 | 0.00 | 0.00 | 3645.53 | 01-DEC-10:53 | 3645.53 | 01-DEC-10:53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.497807E+12 | 0.00 | 2160.02 | 0.431989E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 118407.09 | 0.00 | 1.27 | 118407.09 | 0.00 | 0.00 | 0.00 | 0.00 | 957.39 | 957.39 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.158252E+12 | 0.00 | 489.90 | 0.132262E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 219620.97 | 175849.10 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 82960.50 | 0.00 | 28.27 | 82960.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 | 29-JAN-19:20 | 4.24 | 29-JAN-19:20 | 0.00 | 0.00 | 0.00 |
February | 63452.91 | 0.00 | 22.87 | 63452.91 | 0.00 | 0.00 | 0.00 | 0.00 | 5.89 | 05-FEB-16:31 | 5.89 | 05-FEB-16:31 | 0.00 | 0.00 | 0.00 |
March | 0.643912E+11 | 0.00 | 104.84 | 0.630859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1030212.76 | 15-MAR-14:05 | 1030212.76 | 15-MAR-14:05 | 0.00 | 0.00 | 0.00 |
April | 0.286261E+11 | 0.00 | 127.52 | 0.286261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 629122.75 | 26-APR-13:03 | 629122.75 | 26-APR-13:03 | 0.00 | 0.00 | 0.00 |
May | 0.231662E+12 | 0.00 | 233.02 | 0.228152E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1108872.33 | 24-MAY-05:02 | 1003024.65 | 23-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.835483E+12 | 0.00 | 400.83 | 0.703289E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1782589.41 | 29-JUN-04:11 | 1282278.08 | 27-JUN-13:00 | 0.00 | 0.00 | 0.00 |
July | 0.132680E+13 | 0.00 | 439.23 | 0.108551E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2329149.32 | 21-JUL-04:02 | 1479254.46 | 21-JUL-03:01 | 0.00 | 0.00 | 0.00 |
August | 0.113584E+13 | 0.00 | 431.13 | 0.982873E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2372225.42 | 15-AUG-05:02 | 1573168.43 | 15-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.529400E+12 | 0.00 | 329.44 | 0.462964E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1957574.46 | 14-SEP-05:02 | 1302916.09 | 16-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.964522E+11 | 0.00 | 166.64 | 0.964291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 944162.66 | 11-OCT-15:20 | 944162.66 | 11-OCT-15:20 | 0.00 | 0.00 | 0.00 |
November | 0.159446E+11 | 0.00 | 131.52 | 0.159446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 526910.50 | 16-NOV-15:01 | 526910.50 | 16-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 23839953.82 | 0.00 | 65.25 | 23839953.82 | 0.00 | 0.00 | 0.00 | 0.00 | 14899.60 | 01-DEC-10:53 | 14899.60 | 01-DEC-10:53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.426462E+13 | 0.00 | 2480.57 | 0.366690E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 63452.91 | 0.00 | 22.87 | 63452.91 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 | 4.24 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.132680E+13 | 0.00 | 439.23 | 0.108551E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2372225.42 | 1573168.43 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6777671.26 | 0.00 | 5.70 | 6777671.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4626.88 | 23-JAN-06:01 | 4626.88 | 23-JAN-06:01 | 0.00 | 0.00 | 0.00 |
February | 5000413.77 | 0.00 | 7.09 | 5000413.77 | 0.00 | 0.00 | 0.00 | 0.00 | 5228.09 | 24-FEB-05:41 | 5228.09 | 24-FEB-05:41 | 0.00 | 0.00 | 0.00 |
March | 0.630187E+10 | 0.00 | 41.33 | 0.620231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 120708.94 | 15-MAR-14:00 | 120708.94 | 15-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.232517E+10 | 0.00 | 51.55 | 0.232517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44326.09 | 07-APR-14:00 | 44326.09 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.245202E+11 | 0.00 | 211.85 | 0.242568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133661.13 | 10-MAY-14:40 | 125970.57 | 10-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.951468E+11 | 0.00 | 380.88 | 0.823311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 213134.64 | 27-JUN-05:02 | 170174.22 | 12-JUN-14:00 | 0.00 | 0.00 | 0.00 |
July | 0.152692E+12 | 0.00 | 432.30 | 0.128671E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 345211.32 | 21-JUL-03:01 | 216142.60 | 21-JUL-03:01 | 0.00 | 0.00 | 0.00 |
August | 0.127072E+12 | 0.00 | 419.59 | 0.112174E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 274181.72 | 14-AUG-04:11 | 173451.02 | 09-AUG-14:50 | 0.00 | 0.00 | 0.00 |
September | 0.543672E+11 | 0.00 | 310.42 | 0.481608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 241169.68 | 14-SEP-05:02 | 145211.63 | 21-SEP-15:00 | 0.00 | 0.00 | 0.00 |
October | 0.663799E+10 | 0.00 | 91.75 | 0.663799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103871.76 | 11-OCT-15:20 | 103871.76 | 11-OCT-15:20 | 0.00 | 0.00 | 0.00 |
November | 0.110255E+10 | 0.00 | 24.10 | 0.110255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27701.05 | 27-NOV-06:03 | 27701.05 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 12406924.68 | 0.00 | 10.79 | 12406924.68 | 0.00 | 0.00 | 0.00 | 0.00 | 3602.33 | 08-DEC-06:01 | 3602.33 | 08-DEC-06:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.470189E+12 | 0.00 | 1987.36 | 0.411886E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5000413.77 | 0.00 | 5.70 | 5000413.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3602.33 | 3602.33 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.152692E+12 | 0.00 | 432.30 | 0.128671E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 345211.32 | 216142.60 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.108477E+10 | 0.00 | 12.31 | 0.102989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74873.30 | 02-JAN-06:13 | 73241.90 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.252618E+09 | 0.00 | 5.98 | 0.252618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55096.75 | 13-FEB-06:01 | 55096.75 | 13-FEB-06:01 | 0.00 | 0.00 | 0.00 |
March | 0.607925E+10 | 0.00 | 66.37 | 0.562742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108266.34 | 18-MAR-04:58 | 108266.34 | 18-MAR-04:58 | 0.00 | 0.00 | 0.00 |
April | 0.690275E+10 | 0.00 | 110.54 | 0.690166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107149.83 | 06-APR-04:36 | 107149.83 | 06-APR-04:36 | 0.00 | 0.00 | 0.00 |
May | 0.205594E+11 | 0.00 | 220.36 | 0.188720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96145.06 | 17-MAY-14:20 | 73325.61 | 19-MAY-04:18 | 0.00 | 0.00 | 0.00 |
June | 0.529069E+11 | 0.00 | 353.04 | 0.400045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 146168.54 | 27-JUN-04:53 | 118796.78 | 12-JUN-04:11 | 0.00 | 0.00 | 0.00 |
July | 0.814381E+11 | 0.00 | 381.89 | 0.591585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 155453.67 | 17-JUL-03:01 | 114173.74 | 05-JUL-04:05 | 0.00 | 0.00 | 0.00 |
August | 0.774254E+11 | 0.00 | 414.27 | 0.603662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 148951.92 | 28-AUG-04:32 | 115941.79 | 15-AUG-04:53 | 0.00 | 0.00 | 0.00 |
September | 0.455623E+11 | 0.00 | 339.30 | 0.358524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152645.39 | 16-SEP-04:53 | 107425.16 | 04-SEP-16:30 | 0.00 | 0.00 | 0.00 |
October | 0.164038E+11 | 0.00 | 187.74 | 0.155542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130046.18 | 17-OCT-03:59 | 130046.18 | 17-OCT-03:59 | 0.00 | 0.00 | 0.00 |
November | 0.790609E+10 | 0.00 | 136.45 | 0.789911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 120592.41 | 13-NOV-01:17 | 120592.41 | 13-NOV-01:17 | 0.00 | 0.00 | 0.00 |
December | 0.251648E+10 | 0.00 | 48.21 | 0.251521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109851.62 | 06-DEC-06:00 | 109851.62 | 06-DEC-06:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319038E+12 | 0.00 | 2276.44 | 0.254034E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.252618E+09 | 0.00 | 5.98 | 0.252618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55096.75 | 55096.75 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.814381E+11 | 0.00 | 414.27 | 0.603662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 155453.67 | 130046.18 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2990644.88 | 0.00 | 184.32 | 2990644.88 | 0.00 | 0.00 | 0.00 | 0.00 | 71.65 | 17-JAN-05:22 | 71.65 | 17-JAN-05:22 | 0.00 | 0.00 | 0.00 |
February | 0.156290E+12 | 0.00 | 418.88 | 0.156290E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 267551.81 | 01-FEB-00:21 | 267551.81 | 01-FEB-00:21 | 0.00 | 0.00 | 0.00 |
March | 0.228962E+12 | 0.00 | 740.19 | 0.227826E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 340288.64 | 16-MAR-15:06 | 286474.08 | 15-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.203353E+12 | 0.00 | 719.69 | 0.203353E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 271578.56 | 25-APR-14:00 | 271578.56 | 25-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.159683E+11 | 0.00 | 267.47 | 0.159180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 284967.52 | 31-MAY-23:41 | 249059.01 | 31-MAY-23:41 | 0.00 | 0.00 | 0.00 |
June | 0.315577E+12 | 0.00 | 513.63 | 0.276079E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 530116.82 | 21-JUN-10:34 | 317850.33 | 30-JUN-19:42 | 0.00 | 0.00 | 0.00 |
July | 0.537874E+12 | 0.00 | 743.87 | 0.515224E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 520630.36 | 17-JUL-17:10 | 311118.21 | 22-JUL-04:14 | 0.00 | 0.00 | 0.00 |
August | 0.637019E+12 | 0.00 | 743.27 | 0.595695E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 538604.23 | 07-AUG-07:05 | 427332.14 | 14-AUG-04:16 | 0.00 | 0.00 | 0.00 |
September | 0.439237E+11 | 0.00 | 308.40 | 0.439111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 219034.67 | 30-SEP-23:34 | 219034.67 | 30-SEP-23:34 | 0.00 | 0.00 | 0.00 |
October | 0.162603E+12 | 0.00 | 377.48 | 0.156855E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 353040.77 | 01-OCT-07:21 | 300624.72 | 11-OCT-17:22 | 0.00 | 0.00 | 0.00 |
November | 0.210075E+12 | 0.00 | 716.06 | 0.210060E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 290222.26 | 26-NOV-16:22 | 290222.26 | 26-NOV-16:22 | 0.00 | 0.00 | 0.00 |
December | 0.226767E+12 | 0.00 | 744.00 | 0.226767E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 257222.99 | 19-DEC-12:10 | 257222.99 | 19-DEC-12:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.273842E+13 | 0.00 | 6477.26 | 0.262798E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2990644.88 | 0.00 | 184.32 | 2990644.88 | 0.00 | 0.00 | 0.00 | 0.00 | 71.65 | 71.65 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.637019E+12 | 0.00 | 744.00 | 0.595695E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 538604.23 | 427332.14 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.470831E+10 | 0.146465E+10 | 743.61 | 0.470831E+10 | -0.0 | 0.00 | 0.48 | 15-JAN-16:35 | 0.00 | 09-JAN-00:52 | 2823.64 | 15-JAN-16:35 | 2823.64 | 15-JAN-16:35 | 0.00 | 17-JAN-16:00 | 842.41 | 15-JAN-16:40 | 0.00 | 01-JAN-00:02 |
February | 0.873912E+10 | 0.250682E+10 | 672.00 | 0.873912E+10 | -0.0 | 0.00 | 0.80 | 28-FEB-16:51 | 0.42 | 06-FEB-07:02 | 5074.15 | 28-FEB-16:53 | 5074.15 | 28-FEB-16:53 | 0.00 | 17-FEB-11:13 | 1376.56 | 28-FEB-17:00 | 0.00 | 01-FEB-00:01 |
March | 0.162489E+11 | 0.425145E+10 | 744.00 | 0.162351E+11 | 13813701.40 | 0.00 | 1.00 | 01-MAR-16:21 | 0.78 | 06-MAR-07:02 | 8000.55 | 31-MAR-23:57 | 8000.55 | 31-MAR-23:57 | 208.84 | 14-MAR-10:20 | 2073.63 | 31-MAR-23:55 | 0.00 | 01-MAR-00:01 |
April | 0.212421E+11 | 0.552436E+10 | 720.00 | 0.212407E+11 | 1316616.42 | 0.00 | 1.00 | 01-APR-00:10 | 0.49 | 30-APR-24:00 | 9233.37 | 02-APR-17:50 | 9233.37 | 02-APR-17:50 | 61.56 | 12-APR-16:00 | 2430.51 | 02-APR-17:50 | 0.00 | 01-APR-00:10 |
May | 0.740049E+10 | 0.222129E+10 | 744.00 | 0.737941E+10 | 21084594.29 | 0.00 | 0.73 | 31-MAY-23:53 | 0.35 | 12-MAY-06:10 | 4739.61 | 31-MAY-23:53 | 4739.61 | 31-MAY-23:53 | 207.27 | 17-MAY-15:00 | 1313.31 | 31-MAY-23:53 | 0.00 | 01-MAY-00:10 |
June | 0.126878E+11 | 0.354105E+10 | 720.00 | 0.125391E+11 | 0.148767E+09 | 0.00 | 0.97 | 30-JUN-23:53 | 0.64 | 10-JUN-06:15 | 6659.84 | 30-JUN-23:53 | 6659.84 | 30-JUN-23:53 | 469.72 | 27-JUN-15:00 | 1752.17 | 27-JUN-13:00 | 0.00 | 01-JUN-00:01 |
July | 0.186362E+11 | 0.492808E+10 | 744.00 | 0.183594E+11 | 0.276816E+09 | 0.00 | 1.00 | 02-JUL-14:51 | 0.92 | 13-JUL-06:30 | 8650.09 | 31-JUL-23:02 | 8533.28 | 31-JUL-23:10 | 468.32 | 20-JUL-15:00 | 2346.45 | 19-JUL-15:00 | 0.00 | 01-JUL-00:01 |
August | 0.235399E+11 | 0.629555E+10 | 744.00 | 0.233283E+11 | 0.211513E+09 | 0.00 | 1.00 | 01-AUG-00:05 | 0.51 | 31-AUG-24:00 | 9705.38 | 14-AUG-16:00 | 9674.72 | 04-AUG-18:40 | 469.58 | 15-AUG-14:05 | 2904.14 | 18-AUG-15:00 | 0.00 | 01-AUG-00:05 |
September | 0.755055E+10 | 0.225887E+10 | 720.00 | 0.744636E+10 | 0.104190E+09 | 0.00 | 0.69 | 30-SEP-23:52 | 0.34 | 30-SEP-07:00 | 4382.40 | 30-SEP-23:51 | 4382.40 | 30-SEP-23:52 | 322.75 | 15-SEP-15:10 | 1231.92 | 30-SEP-23:52 | 0.00 | 01-SEP-00:10 |
October | 0.117972E+11 | 0.330771E+10 | 744.00 | 0.117805E+11 | 16666965.87 | 0.00 | 0.91 | 31-OCT-23:52 | 0.57 | 30-OCT-06:05 | 6211.61 | 31-OCT-23:52 | 6211.61 | 31-OCT-23:52 | 177.79 | 26-OCT-09:01 | 1628.83 | 31-OCT-23:52 | 0.00 | 01-OCT-00:01 |
November | 0.159095E+11 | 0.416081E+10 | 720.00 | 0.159084E+11 | 1163042.03 | 0.00 | 1.00 | 15-NOV-15:41 | 0.83 | 24-NOV-07:01 | 6984.38 | 15-NOV-16:13 | 6984.38 | 15-NOV-16:13 | 105.70 | 16-NOV-16:00 | 1784.47 | 15-NOV-16:11 | 0.00 | 01-NOV-00:01 |
December | 0.205011E+11 | 0.528658E+10 | 744.00 | 0.205011E+11 | 80972.05 | 0.00 | 1.00 | 01-DEC-00:01 | 0.97 | 11-DEC-07:03 | 8539.02 | 04-DEC-16:17 | 8539.02 | 04-DEC-16:17 | 19.07 | 01-DEC-13:53 | 2227.99 | 04-DEC-16:20 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.168961E+12 | 0.457472E+11 | 8759.61 | 0.168166E+12 | 0.795411E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.470831E+10 | 0.146465E+10 | 672.00 | 0.470831E+10 | -0.0 | 0.00 | 0.48 | 0.00 | 2823.64 | 2823.64 | 0.00 | 842.41 | 0.00 | |||||||
Maximum of Months | 0.235399E+11 | 0.629555E+10 | 744.00 | 0.233283E+11 | 0.276816E+09 | 0.00 | 1.00 | 0.97 | 9705.38 | 9674.72 | 469.72 | 2904.14 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.223573E+11 | 0.612855E+10 | 660.22 | 0.223573E+11 | -0.0 | 0.00 | 0.43 | 12-JAN-16:40 | 0.00 | 01-JAN-00:02 | 23648.92 | 12-JAN-16:40 | 23648.92 | 12-JAN-16:40 | 0.00 | 17-JAN-16:00 | 6125.06 | 12-JAN-16:35 | 0.00 | 01-JAN-00:02 |
February | 0.662931E+11 | 0.167786E+11 | 672.00 | 0.662931E+11 | -0.0 | 0.00 | 0.78 | 28-FEB-16:51 | 0.25 | 06-FEB-07:02 | 47036.30 | 28-FEB-16:53 | 47036.30 | 28-FEB-16:53 | 0.00 | 18-FEB-17:30 | 11014.36 | 28-FEB-17:00 | 0.00 | 01-FEB-00:01 |
March | 0.142234E+12 | 0.325178E+11 | 744.00 | 0.142096E+12 | 0.137780E+09 | 0.00 | 1.00 | 01-MAR-16:41 | 0.61 | 06-MAR-07:02 | 73315.63 | 31-MAR-23:27 | 73315.63 | 31-MAR-23:27 | 2079.01 | 14-MAR-10:30 | 16203.24 | 31-MAR-23:23 | 0.00 | 01-MAR-00:01 |
April | 0.194112E+12 | 0.430518E+11 | 720.00 | 0.194099E+12 | 13251643.65 | 0.00 | 1.00 | 01-APR-00:10 | 0.39 | 30-APR-24:00 | 87807.67 | 24-APR-17:55 | 87807.67 | 24-APR-17:55 | 579.42 | 12-APR-16:00 | 19797.29 | 24-APR-17:55 | 0.00 | 01-APR-00:10 |
May | 0.649464E+11 | 0.168634E+11 | 744.00 | 0.647369E+11 | 0.209575E+09 | 0.00 | 0.72 | 31-MAY-23:33 | 0.26 | 01-MAY-06:05 | 44724.15 | 31-MAY-23:33 | 44724.15 | 31-MAY-23:33 | 2037.02 | 17-MAY-15:00 | 10657.21 | 31-MAY-23:33 | 0.00 | 01-MAY-00:10 |
June | 0.118870E+12 | 0.285628E+11 | 720.00 | 0.117388E+12 | 0.148211E+10 | 0.00 | 0.97 | 30-JUN-23:33 | 0.61 | 14-JUN-06:02 | 63672.23 | 30-JUN-23:33 | 63672.23 | 30-JUN-23:33 | 4671.50 | 27-JUN-15:00 | 14338.31 | 27-JUN-13:00 | 0.00 | 01-JUN-00:01 |
July | 0.176061E+12 | 0.400258E+11 | 744.00 | 0.173305E+12 | 0.275617E+10 | 0.00 | 1.00 | 02-JUL-15:31 | 0.88 | 06-JUL-06:16 | 83338.66 | 31-JUL-23:02 | 82417.19 | 31-JUL-24:00 | 4669.16 | 20-JUL-15:00 | 19203.89 | 19-JUL-15:00 | 0.00 | 01-JUL-00:01 |
August | 0.222458E+12 | 0.509168E+11 | 744.00 | 0.220355E+12 | 0.210327E+10 | 0.00 | 1.00 | 01-AUG-00:05 | 0.42 | 31-AUG-24:00 | 93135.68 | 04-AUG-18:40 | 93135.68 | 04-AUG-18:40 | 4671.51 | 15-AUG-14:05 | 23709.01 | 18-AUG-15:20 | 0.00 | 01-AUG-00:05 |
September | 0.656522E+11 | 0.170148E+11 | 720.00 | 0.646233E+11 | 0.102890E+10 | 0.00 | 0.63 | 30-SEP-23:52 | 0.27 | 30-SEP-07:00 | 37680.67 | 30-SEP-23:52 | 37680.67 | 30-SEP-23:52 | 3209.32 | 15-SEP-15:00 | 9398.98 | 21-SEP-17:00 | 0.00 | 01-SEP-00:10 |
October | 0.102249E+12 | 0.249771E+11 | 744.00 | 0.102082E+12 | 0.166265E+09 | 0.00 | 0.87 | 31-OCT-23:22 | 0.45 | 30-OCT-06:05 | 55627.39 | 31-OCT-23:22 | 55627.39 | 31-OCT-23:22 | 1751.87 | 26-OCT-09:02 | 12700.06 | 31-OCT-23:22 | 0.00 | 01-OCT-00:01 |
November | 0.138060E+12 | 0.316386E+11 | 720.00 | 0.138048E+12 | 11914223.87 | 0.00 | 0.99 | 15-NOV-16:11 | 0.71 | 24-NOV-07:01 | 65618.84 | 15-NOV-16:13 | 65618.84 | 15-NOV-16:13 | 1051.00 | 16-NOV-16:00 | 14394.33 | 15-NOV-16:20 | 0.00 | 01-NOV-00:01 |
December | 0.173960E+12 | 0.383056E+11 | 744.00 | 0.173959E+12 | 1006148.73 | 0.00 | 1.00 | 01-DEC-00:01 | 0.82 | 11-DEC-07:03 | 77992.22 | 04-DEC-16:17 | 77992.22 | 04-DEC-16:17 | 204.52 | 01-DEC-13:53 | 17354.44 | 04-DEC-16:20 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.148725E+13 | 0.346782E+12 | 8676.22 | 0.147934E+13 | 0.791023E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.223573E+11 | 0.612855E+10 | 660.22 | 0.223573E+11 | -0.0 | 0.00 | 0.43 | 0.00 | 23648.92 | 23648.92 | 0.00 | 6125.06 | 0.00 | |||||||
Maximum of Months | 0.222458E+12 | 0.509168E+11 | 744.00 | 0.220355E+12 | 0.275617E+10 | 0.00 | 1.00 | 0.88 | 93135.68 | 93135.68 | 4671.51 | 23709.01 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.100599E+10 | 0.325080E+09 | 390.42 | 0.100599E+10 | 0.00 | 0.00 | 0.38 | 12-JAN-16:40 | 0.00 | 01-JAN-00:02 | 2106.97 | 12-JAN-16:40 | 2106.97 | 12-JAN-16:40 | 0.00 | 11-JAN-17:25 | 646.18 | 12-JAN-16:35 | 0.00 | 01-JAN-00:02 |
February | 0.482452E+10 | 0.145919E+10 | 668.13 | 0.482452E+10 | -0.0 | 0.00 | 0.76 | 28-FEB-16:51 | 0.00 | 06-FEB-01:01 | 4678.29 | 28-FEB-16:53 | 4678.29 | 28-FEB-16:53 | 0.00 | 22-FEB-16:42 | 1286.68 | 28-FEB-17:00 | 0.00 | 01-FEB-00:01 |
March | 0.124367E+11 | 0.341139E+10 | 744.00 | 0.124229E+11 | 13757572.49 | 0.00 | 1.00 | 15-MAR-14:30 | 0.38 | 06-MAR-04:02 | 6980.22 | 15-MAR-15:20 | 6901.15 | 15-MAR-15:20 | 209.21 | 14-MAR-10:30 | 1888.46 | 15-MAR-15:00 | 0.00 | 01-MAR-00:01 |
April | 0.181238E+11 | 0.468752E+10 | 720.00 | 0.181227E+11 | 1090115.21 | 0.00 | 1.00 | 01-APR-10:53 | 0.27 | 30-APR-24:00 | 8839.54 | 24-APR-17:55 | 8839.54 | 24-APR-17:55 | 51.58 | 28-APR-16:00 | 2320.25 | 24-APR-17:55 | 0.00 | 01-APR-00:10 |
May | 0.582349E+10 | 0.178055E+10 | 743.25 | 0.580276E+10 | 20723105.32 | 0.00 | 0.68 | 31-MAY-23:12 | 0.00 | 03-MAY-02:23 | 4301.18 | 31-MAY-23:12 | 4301.18 | 31-MAY-23:12 | 202.60 | 17-MAY-15:00 | 1210.19 | 31-MAY-23:12 | 0.00 | 01-MAY-00:10 |
June | 0.117175E+11 | 0.330880E+10 | 720.00 | 0.115692E+11 | 0.148288E+09 | 0.00 | 0.93 | 30-JUN-23:12 | 0.48 | 14-JUN-06:02 | 6225.08 | 30-JUN-23:12 | 6225.08 | 30-JUN-23:12 | 470.61 | 27-JUN-15:00 | 1734.86 | 27-JUN-13:00 | 0.00 | 01-JUN-00:01 |
July | 0.176261E+11 | 0.470471E+10 | 744.00 | 0.173506E+11 | 0.275522E+09 | 0.00 | 1.00 | 02-JUL-15:11 | 0.82 | 13-JUL-06:20 | 8308.90 | 31-JUL-23:02 | 8220.21 | 31-JUL-23:40 | 466.37 | 20-JUL-15:00 | 2313.26 | 19-JUL-15:00 | 0.00 | 01-JUL-00:01 |
August | 0.221314E+11 | 0.589192E+10 | 744.00 | 0.219222E+11 | 0.209219E+09 | 0.00 | 1.00 | 01-AUG-00:05 | 0.35 | 31-AUG-24:00 | 9475.50 | 04-AUG-18:30 | 9475.24 | 04-AUG-18:30 | 468.70 | 15-AUG-14:05 | 2834.31 | 18-AUG-15:10 | 0.00 | 01-AUG-00:05 |
September | 0.591995E+10 | 0.180806E+10 | 719.67 | 0.581725E+10 | 0.102694E+09 | 0.00 | 0.61 | 21-SEP-17:20 | 0.00 | 03-SEP-03:53 | 3758.10 | 21-SEP-17:30 | 3685.48 | 21-SEP-17:30 | 323.00 | 15-SEP-15:00 | 1144.14 | 21-SEP-17:00 | 0.00 | 01-SEP-00:10 |
October | 0.854664E+10 | 0.249480E+10 | 743.89 | 0.853015E+10 | 16490249.70 | 0.00 | 0.83 | 11-OCT-17:00 | 0.00 | 16-OCT-01:31 | 5517.77 | 11-OCT-17:00 | 5494.40 | 11-OCT-17:00 | 172.76 | 26-OCT-09:02 | 1491.44 | 11-OCT-17:00 | 0.00 | 01-OCT-00:01 |
November | 0.117171E+11 | 0.324327E+10 | 720.00 | 0.117159E+11 | 1154664.64 | 0.00 | 0.96 | 15-NOV-16:11 | 0.45 | 24-NOV-04:13 | 6439.29 | 15-NOV-16:13 | 6439.29 | 15-NOV-16:13 | 104.17 | 16-NOV-16:00 | 1667.46 | 15-NOV-16:20 | 0.00 | 01-NOV-00:01 |
December | 0.152433E+11 | 0.401738E+10 | 744.00 | 0.152432E+11 | 52053.98 | 0.00 | 1.00 | 01-DEC-09:13 | 0.62 | 26-DEC-03:43 | 7547.12 | 04-DEC-16:17 | 7547.12 | 04-DEC-16:17 | 9.27 | 01-DEC-14:13 | 1946.37 | 04-DEC-16:20 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.135116E+12 | 0.371326E+11 | 8401.38 | 0.134327E+12 | 0.788991E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.100599E+10 | 0.325080E+09 | 390.42 | 0.100599E+10 | -0.0 | 0.00 | 0.38 | 0.00 | 2106.97 | 2106.97 | 0.00 | 646.18 | 0.00 | |||||||
Maximum of Months | 0.221314E+11 | 0.589192E+10 | 744.00 | 0.219222E+11 | 0.275522E+09 | 0.00 | 1.00 | 0.82 | 9475.50 | 9475.24 | 470.61 | 2834.31 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 133.48 | 0.00 | 133.48 | 0.00 | 1248.74 | 0.00 | 0.00 | 0.00 |
February | 203.38 | 0.00 | 203.38 | 0.36 | 1185.45 | 0.00 | 0.00 | 0.00 |
March | 246.64 | 0.00 | 246.64 | 38.98 | 872.02 | 0.00 | 0.00 | 0.00 |
April | 314.27 | 1.25 | 313.02 | 92.75 | 612.42 | 0.00 | 0.00 | 0.00 |
May | 365.17 | 15.49 | 349.68 | 214.78 | 365.77 | 0.00 | 0.00 | 0.00 |
June | 439.22 | 37.39 | 401.83 | 417.84 | 225.94 | 0.00 | 0.00 | 0.00 |
July | 407.43 | 26.30 | 381.13 | 478.99 | 156.12 | 0.00 | 0.00 | 0.00 |
August | 352.54 | 5.36 | 347.18 | 382.70 | 213.03 | 0.00 | 0.00 | 0.00 |
September | 268.29 | 0.06 | 268.24 | 200.24 | 356.49 | 0.00 | 0.00 | 0.00 |
October | 200.56 | 0.00 | 200.56 | 49.52 | 604.45 | 0.00 | 0.00 | 0.00 |
November | 134.77 | 0.00 | 134.77 | 9.39 | 821.83 | 0.00 | 0.00 | 0.00 |
December | 124.94 | 0.00 | 124.94 | 0.11 | 1211.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 266.15 | 7.19 | 258.96 | 158.17 | 653.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 124.94 | 0.00 | 124.94 | 0.00 | 156.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.22 | 37.39 | 401.83 | 478.99 | 1248.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 133.48 | 0.00 | 133.48 | 0.00 | 1248.74 | 0.00 | 0.00 | 0.00 |
February | 203.38 | 0.00 | 203.38 | 0.36 | 1185.45 | 0.00 | 0.00 | 0.00 |
March | 246.64 | 0.00 | 246.64 | 38.98 | 872.02 | 0.00 | 0.00 | 0.00 |
April | 314.27 | 1.25 | 313.02 | 92.75 | 612.42 | 0.00 | 0.00 | 0.00 |
May | 365.17 | 15.49 | 349.68 | 214.78 | 365.77 | 0.00 | 0.00 | 0.00 |
June | 439.22 | 37.39 | 401.83 | 417.84 | 225.94 | 0.00 | 0.00 | 0.00 |
July | 407.43 | 26.30 | 381.13 | 478.99 | 156.12 | 0.00 | 0.00 | 0.00 |
August | 352.54 | 5.36 | 347.18 | 382.70 | 213.03 | 0.00 | 0.00 | 0.00 |
September | 268.29 | 0.06 | 268.24 | 200.24 | 356.49 | 0.00 | 0.00 | 0.00 |
October | 200.56 | 0.00 | 200.56 | 49.52 | 604.45 | 0.00 | 0.00 | 0.00 |
November | 134.77 | 0.00 | 134.77 | 9.39 | 821.83 | 0.00 | 0.00 | 0.00 |
December | 124.94 | 0.00 | 124.94 | 0.11 | 1211.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 266.15 | 7.19 | 258.96 | 158.17 | 653.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 124.94 | 0.00 | 124.94 | 0.00 | 156.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.22 | 37.39 | 401.83 | 478.99 | 1248.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 133.48 | 0.00 | 133.48 | 0.00 | 1248.74 | 0.00 | 0.00 | 0.00 |
February | 203.38 | 0.00 | 203.38 | 0.36 | 1185.45 | 0.00 | 0.00 | 0.00 |
March | 246.64 | 0.00 | 246.64 | 38.98 | 872.02 | 0.00 | 0.00 | 0.00 |
April | 314.27 | 1.25 | 313.02 | 92.75 | 612.42 | 0.00 | 0.00 | 0.00 |
May | 365.17 | 15.49 | 349.68 | 214.78 | 365.77 | 0.00 | 0.00 | 0.00 |
June | 439.22 | 37.39 | 401.83 | 417.84 | 225.94 | 0.00 | 0.00 | 0.00 |
July | 407.43 | 26.30 | 381.13 | 478.99 | 156.12 | 0.00 | 0.00 | 0.00 |
August | 352.54 | 5.36 | 347.18 | 382.70 | 213.03 | 0.00 | 0.00 | 0.00 |
September | 268.29 | 0.06 | 268.24 | 200.24 | 356.49 | 0.00 | 0.00 | 0.00 |
October | 200.56 | 0.00 | 200.56 | 49.52 | 604.45 | 0.00 | 0.00 | 0.00 |
November | 134.77 | 0.00 | 134.77 | 9.39 | 821.83 | 0.00 | 0.00 | 0.00 |
December | 124.94 | 0.00 | 124.94 | 0.11 | 1211.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 266.15 | 7.19 | 258.96 | 158.17 | 653.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 124.94 | 0.00 | 124.94 | 0.00 | 156.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.22 | 37.39 | 401.83 | 478.99 | 1248.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 133.48 | 0.00 | 133.48 | 0.00 | 1248.74 | 0.00 | 0.00 | 0.00 |
February | 203.38 | 0.00 | 203.38 | 0.36 | 1185.45 | 0.00 | 0.00 | 0.00 |
March | 246.64 | 0.00 | 246.64 | 38.98 | 872.02 | 0.00 | 0.00 | 0.00 |
April | 314.27 | 1.25 | 313.02 | 92.75 | 612.42 | 0.00 | 0.00 | 0.00 |
May | 365.17 | 15.49 | 349.68 | 214.78 | 365.77 | 0.00 | 0.00 | 0.00 |
June | 439.22 | 37.39 | 401.83 | 417.84 | 225.94 | 0.00 | 0.00 | 0.00 |
July | 407.43 | 26.30 | 381.13 | 478.99 | 156.12 | 0.00 | 0.00 | 0.00 |
August | 352.54 | 5.36 | 347.18 | 382.70 | 213.03 | 0.00 | 0.00 | 0.00 |
September | 268.29 | 0.06 | 268.24 | 200.24 | 356.49 | 0.00 | 0.00 | 0.00 |
October | 200.56 | 0.00 | 200.56 | 49.52 | 604.45 | 0.00 | 0.00 | 0.00 |
November | 134.77 | 0.00 | 134.77 | 9.39 | 821.83 | 0.00 | 0.00 | 0.00 |
December | 124.94 | 0.00 | 124.94 | 0.11 | 1211.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 266.15 | 7.19 | 258.96 | 158.17 | 653.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 124.94 | 0.00 | 124.94 | 0.00 | 156.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.22 | 37.39 | 401.83 | 478.99 | 1248.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 133.48 | 0.00 | 133.48 | 0.00 | 1248.69 | 0.00 | 0.00 | 0.00 |
February | 203.37 | 0.00 | 203.37 | 0.36 | 1185.40 | 0.00 | 0.00 | 0.00 |
March | 246.63 | 0.00 | 246.63 | 38.97 | 871.98 | 0.00 | 0.00 | 0.00 |
April | 314.26 | 1.25 | 313.00 | 92.74 | 612.40 | 0.00 | 0.00 | 0.00 |
May | 365.15 | 15.48 | 349.67 | 214.77 | 365.76 | 0.00 | 0.00 | 0.00 |
June | 439.20 | 37.39 | 401.81 | 417.82 | 225.93 | 0.00 | 0.00 | 0.00 |
July | 407.42 | 26.30 | 381.12 | 478.97 | 156.11 | 0.00 | 0.00 | 0.00 |
August | 352.53 | 5.36 | 347.17 | 382.68 | 213.02 | 0.00 | 0.00 | 0.00 |
September | 268.28 | 0.06 | 268.23 | 200.23 | 356.48 | 0.00 | 0.00 | 0.00 |
October | 200.55 | 0.00 | 200.55 | 49.52 | 604.42 | 0.00 | 0.00 | 0.00 |
November | 134.77 | 0.00 | 134.77 | 9.39 | 821.80 | 0.00 | 0.00 | 0.00 |
December | 124.93 | 0.00 | 124.93 | 0.11 | 1211.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 266.14 | 7.18 | 258.95 | 158.17 | 653.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 124.93 | 0.00 | 124.93 | 0.00 | 156.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.20 | 37.39 | 401.81 | 478.97 | 1248.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.41 | 87.52 | 183.89 | 65.42 | 1251.73 | 0.00 | 0.00 | 0.00 |
February | 398.25 | 119.50 | 278.74 | 124.42 | 1185.28 | 0.00 | 0.00 | 0.00 |
March | 571.47 | 239.33 | 332.14 | 357.18 | 851.71 | 0.00 | 0.00 | 0.00 |
April | 756.38 | 334.21 | 422.17 | 602.27 | 601.28 | 0.00 | 0.00 | 0.00 |
May | 847.41 | 374.86 | 472.56 | 839.77 | 390.27 | 0.00 | 0.00 | 0.00 |
June | 946.42 | 418.27 | 528.15 | 1097.91 | 241.93 | 0.00 | 0.00 | 0.00 |
July | 908.81 | 400.14 | 508.67 | 1167.99 | 158.06 | 0.00 | 0.00 | 0.00 |
August | 820.76 | 344.51 | 476.25 | 1020.90 | 210.63 | 0.00 | 0.00 | 0.00 |
September | 683.01 | 302.96 | 380.05 | 735.40 | 357.64 | 0.00 | 0.00 | 0.00 |
October | 463.48 | 191.71 | 271.77 | 343.41 | 602.16 | 0.00 | 0.00 | 0.00 |
November | 262.89 | 84.33 | 178.56 | 118.18 | 834.70 | 0.00 | 0.00 | 0.00 |
December | 211.64 | 43.73 | 167.91 | 29.26 | 1248.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 596.05 | 245.68 | 350.36 | 544.22 | 658.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 211.64 | 43.73 | 167.91 | 29.26 | 158.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 946.42 | 418.27 | 528.15 | 1167.99 | 1251.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.41 | 87.52 | 183.89 | 65.42 | 1251.73 | 0.00 | 0.00 | 0.00 |
February | 398.25 | 119.50 | 278.74 | 124.42 | 1185.28 | 0.00 | 0.00 | 0.00 |
March | 571.47 | 239.33 | 332.14 | 357.18 | 851.71 | 0.00 | 0.00 | 0.00 |
April | 756.38 | 334.21 | 422.17 | 602.27 | 601.28 | 0.00 | 0.00 | 0.00 |
May | 847.41 | 374.86 | 472.56 | 839.77 | 390.27 | 0.00 | 0.00 | 0.00 |
June | 946.42 | 418.27 | 528.15 | 1097.91 | 241.93 | 0.00 | 0.00 | 0.00 |
July | 908.81 | 400.14 | 508.67 | 1167.99 | 158.06 | 0.00 | 0.00 | 0.00 |
August | 820.76 | 344.51 | 476.25 | 1020.90 | 210.63 | 0.00 | 0.00 | 0.00 |
September | 683.01 | 302.96 | 380.05 | 735.40 | 357.64 | 0.00 | 0.00 | 0.00 |
October | 463.48 | 191.71 | 271.77 | 343.41 | 602.16 | 0.00 | 0.00 | 0.00 |
November | 262.89 | 84.33 | 178.56 | 118.18 | 834.70 | 0.00 | 0.00 | 0.00 |
December | 211.64 | 43.73 | 167.91 | 29.26 | 1248.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 596.05 | 245.68 | 350.36 | 544.22 | 658.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 211.64 | 43.73 | 167.91 | 29.26 | 158.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 946.42 | 418.27 | 528.15 | 1167.99 | 1251.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.41 | 87.52 | 183.89 | 65.42 | 1251.71 | 0.00 | 0.00 | 0.00 |
February | 398.24 | 119.50 | 278.74 | 124.41 | 1185.26 | 0.00 | 0.00 | 0.00 |
March | 571.46 | 239.32 | 332.14 | 357.17 | 851.69 | 0.00 | 0.00 | 0.00 |
April | 756.36 | 334.20 | 422.16 | 602.26 | 601.27 | 0.00 | 0.00 | 0.00 |
May | 847.40 | 374.85 | 472.55 | 839.75 | 390.26 | 0.00 | 0.00 | 0.00 |
June | 946.40 | 418.26 | 528.14 | 1097.89 | 241.93 | 0.00 | 0.00 | 0.00 |
July | 908.79 | 400.13 | 508.66 | 1167.97 | 158.05 | 0.00 | 0.00 | 0.00 |
August | 820.74 | 344.50 | 476.24 | 1020.88 | 210.62 | 0.00 | 0.00 | 0.00 |
September | 683.00 | 302.95 | 380.05 | 735.39 | 357.63 | 0.00 | 0.00 | 0.00 |
October | 463.47 | 191.70 | 271.77 | 343.41 | 602.15 | 0.00 | 0.00 | 0.00 |
November | 262.89 | 84.33 | 178.56 | 118.17 | 834.69 | 0.00 | 0.00 | 0.00 |
December | 211.64 | 43.73 | 167.91 | 29.26 | 1248.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 596.03 | 245.68 | 350.36 | 544.21 | 658.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 211.64 | 43.73 | 167.91 | 29.26 | 158.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 946.40 | 418.26 | 528.14 | 1167.97 | 1251.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 573.98 | 335.05 | 238.93 | 379.56 | 1018.95 | 0.00 | 0.00 | 0.00 |
February | 655.34 | 316.00 | 339.34 | 410.71 | 990.60 | 0.00 | 0.00 | 0.00 |
March | 799.89 | 449.45 | 350.43 | 673.06 | 736.71 | 0.00 | 0.00 | 0.00 |
April | 662.43 | 264.71 | 397.72 | 590.10 | 585.65 | 0.00 | 0.00 | 0.00 |
May | 579.69 | 168.37 | 411.32 | 583.81 | 386.37 | 0.00 | 0.00 | 0.00 |
June | 563.27 | 119.36 | 443.91 | 658.93 | 243.88 | 0.00 | 0.00 | 0.00 |
July | 575.01 | 139.52 | 435.49 | 771.24 | 165.60 | 0.00 | 0.00 | 0.00 |
August | 645.54 | 209.30 | 436.24 | 847.58 | 216.65 | 0.00 | 0.00 | 0.00 |
September | 750.57 | 365.58 | 384.99 | 892.39 | 345.49 | 0.00 | 0.00 | 0.00 |
October | 718.18 | 410.24 | 307.94 | 702.26 | 535.33 | 0.00 | 0.00 | 0.00 |
November | 514.35 | 290.37 | 223.98 | 420.69 | 710.97 | 0.00 | 0.00 | 0.00 |
December | 479.96 | 248.40 | 231.56 | 292.34 | 1018.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 626.32 | 276.21 | 350.11 | 603.04 | 577.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 479.96 | 119.36 | 223.98 | 292.34 | 165.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 799.89 | 449.45 | 443.91 | 892.39 | 1018.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 573.98 | 335.05 | 238.93 | 379.56 | 1018.95 | 0.00 | 0.00 | 0.00 |
February | 655.34 | 316.00 | 339.34 | 410.71 | 990.60 | 0.00 | 0.00 | 0.00 |
March | 799.88 | 449.45 | 350.43 | 673.06 | 736.71 | 0.00 | 0.00 | 0.00 |
April | 662.43 | 264.71 | 397.72 | 590.10 | 585.65 | 0.00 | 0.00 | 0.00 |
May | 579.69 | 168.37 | 411.32 | 583.81 | 386.37 | 0.00 | 0.00 | 0.00 |
June | 563.27 | 119.36 | 443.91 | 658.93 | 243.88 | 0.00 | 0.00 | 0.00 |
July | 575.00 | 139.51 | 435.49 | 771.24 | 165.60 | 0.00 | 0.00 | 0.00 |
August | 645.54 | 209.30 | 436.24 | 847.58 | 216.65 | 0.00 | 0.00 | 0.00 |
September | 750.57 | 365.58 | 384.99 | 892.39 | 345.49 | 0.00 | 0.00 | 0.00 |
October | 718.18 | 410.24 | 307.94 | 702.26 | 535.33 | 0.00 | 0.00 | 0.00 |
November | 514.35 | 290.37 | 223.98 | 420.69 | 710.97 | 0.00 | 0.00 | 0.00 |
December | 479.96 | 248.40 | 231.56 | 292.34 | 1018.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 626.32 | 276.21 | 350.11 | 603.04 | 577.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 479.96 | 119.36 | 223.98 | 292.34 | 165.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 799.88 | 449.45 | 443.91 | 892.39 | 1018.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 573.98 | 335.05 | 238.93 | 379.56 | 1018.95 | 0.00 | 0.00 | 0.00 |
February | 655.34 | 316.00 | 339.34 | 410.71 | 990.60 | 0.00 | 0.00 | 0.00 |
March | 799.89 | 449.45 | 350.43 | 673.06 | 736.71 | 0.00 | 0.00 | 0.00 |
April | 662.43 | 264.71 | 397.72 | 590.10 | 585.65 | 0.00 | 0.00 | 0.00 |
May | 579.69 | 168.37 | 411.32 | 583.81 | 386.37 | 0.00 | 0.00 | 0.00 |
June | 563.27 | 119.36 | 443.91 | 658.93 | 243.88 | 0.00 | 0.00 | 0.00 |
July | 575.01 | 139.52 | 435.49 | 771.24 | 165.60 | 0.00 | 0.00 | 0.00 |
August | 645.54 | 209.30 | 436.24 | 847.58 | 216.65 | 0.00 | 0.00 | 0.00 |
September | 750.57 | 365.58 | 384.99 | 892.39 | 345.49 | 0.00 | 0.00 | 0.00 |
October | 718.18 | 410.24 | 307.94 | 702.26 | 535.33 | 0.00 | 0.00 | 0.00 |
November | 514.35 | 290.37 | 223.98 | 420.69 | 710.97 | 0.00 | 0.00 | 0.00 |
December | 479.96 | 248.40 | 231.56 | 292.34 | 1018.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 626.32 | 276.21 | 350.11 | 603.04 | 577.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 479.96 | 119.36 | 223.98 | 292.34 | 165.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 799.89 | 449.45 | 443.91 | 892.39 | 1018.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 573.98 | 335.05 | 238.93 | 379.56 | 1018.95 | 0.00 | 0.00 | 0.00 |
February | 655.34 | 316.00 | 339.34 | 410.71 | 990.60 | 0.00 | 0.00 | 0.00 |
March | 799.88 | 449.45 | 350.43 | 673.06 | 736.71 | 0.00 | 0.00 | 0.00 |
April | 662.43 | 264.71 | 397.72 | 590.10 | 585.65 | 0.00 | 0.00 | 0.00 |
May | 579.69 | 168.37 | 411.32 | 583.81 | 386.37 | 0.00 | 0.00 | 0.00 |
June | 563.27 | 119.36 | 443.91 | 658.93 | 243.88 | 0.00 | 0.00 | 0.00 |
July | 575.00 | 139.51 | 435.49 | 771.24 | 165.60 | 0.00 | 0.00 | 0.00 |
August | 645.54 | 209.30 | 436.24 | 847.58 | 216.65 | 0.00 | 0.00 | 0.00 |
September | 750.57 | 365.58 | 384.99 | 892.39 | 345.49 | 0.00 | 0.00 | 0.00 |
October | 718.18 | 410.24 | 307.94 | 702.26 | 535.33 | 0.00 | 0.00 | 0.00 |
November | 514.35 | 290.37 | 223.98 | 420.69 | 710.97 | 0.00 | 0.00 | 0.00 |
December | 479.96 | 248.40 | 231.56 | 292.34 | 1018.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 626.32 | 276.21 | 350.11 | 603.04 | 577.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 479.96 | 119.36 | 223.98 | 292.34 | 165.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 799.88 | 449.45 | 443.91 | 892.39 | 1018.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 573.96 | 335.03 | 238.92 | 379.55 | 1018.91 | 0.00 | 0.00 | 0.00 |
February | 655.31 | 315.99 | 339.33 | 410.69 | 990.56 | 0.00 | 0.00 | 0.00 |
March | 799.85 | 449.43 | 350.42 | 673.04 | 736.68 | 0.00 | 0.00 | 0.00 |
April | 662.40 | 264.70 | 397.71 | 590.08 | 585.62 | 0.00 | 0.00 | 0.00 |
May | 579.66 | 168.36 | 411.30 | 583.78 | 386.35 | 0.00 | 0.00 | 0.00 |
June | 563.25 | 119.35 | 443.89 | 658.91 | 243.87 | 0.00 | 0.00 | 0.00 |
July | 574.98 | 139.51 | 435.47 | 771.21 | 165.59 | 0.00 | 0.00 | 0.00 |
August | 645.51 | 209.29 | 436.22 | 847.55 | 216.64 | 0.00 | 0.00 | 0.00 |
September | 750.54 | 365.57 | 384.97 | 892.35 | 345.47 | 0.00 | 0.00 | 0.00 |
October | 718.15 | 410.22 | 307.93 | 702.23 | 535.31 | 0.00 | 0.00 | 0.00 |
November | 514.33 | 290.35 | 223.97 | 420.67 | 710.94 | 0.00 | 0.00 | 0.00 |
December | 479.94 | 248.39 | 231.55 | 292.32 | 1018.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 626.30 | 276.20 | 350.09 | 603.01 | 577.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 479.94 | 119.35 | 223.97 | 292.32 | 165.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 799.85 | 449.43 | 443.89 | 892.35 | 1018.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 232.87 | 54.67 | 178.20 | 37.25 | 1363.02 | 0.00 | 0.00 | 0.00 |
February | 377.41 | 97.00 | 280.42 | 100.39 | 1294.03 | 0.00 | 0.00 | 0.00 |
March | 591.53 | 253.28 | 338.25 | 365.30 | 947.47 | 0.00 | 0.00 | 0.00 |
April | 724.25 | 296.97 | 427.28 | 556.40 | 720.29 | 0.00 | 0.00 | 0.00 |
May | 854.37 | 386.12 | 468.25 | 847.77 | 454.43 | 0.00 | 0.00 | 0.00 |
June | 1030.82 | 484.85 | 545.96 | 1199.18 | 305.29 | 0.00 | 0.00 | 0.00 |
July | 921.59 | 404.06 | 517.53 | 1159.97 | 226.66 | 0.00 | 0.00 | 0.00 |
August | 833.52 | 354.42 | 479.10 | 1019.31 | 291.60 | 0.00 | 0.00 | 0.00 |
September | 654.57 | 282.68 | 371.89 | 699.84 | 416.43 | 0.00 | 0.00 | 0.00 |
October | 424.33 | 149.47 | 274.85 | 296.36 | 677.49 | 0.00 | 0.00 | 0.00 |
November | 251.46 | 72.46 | 179.00 | 101.32 | 931.11 | 0.00 | 0.00 | 0.00 |
December | 217.99 | 47.50 | 170.49 | 33.32 | 1372.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 593.87 | 240.99 | 352.88 | 537.13 | 747.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 217.99 | 47.50 | 170.49 | 33.32 | 226.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1030.82 | 484.85 | 545.96 | 1199.18 | 1372.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 232.87 | 54.67 | 178.20 | 37.25 | 1363.02 | 0.00 | 0.00 | 0.00 |
February | 377.41 | 97.00 | 280.42 | 100.39 | 1294.03 | 0.00 | 0.00 | 0.00 |
March | 591.53 | 253.28 | 338.25 | 365.30 | 947.47 | 0.00 | 0.00 | 0.00 |
April | 724.25 | 296.97 | 427.28 | 556.40 | 720.29 | 0.00 | 0.00 | 0.00 |
May | 854.37 | 386.12 | 468.25 | 847.77 | 454.43 | 0.00 | 0.00 | 0.00 |
June | 1030.82 | 484.85 | 545.96 | 1199.18 | 305.29 | 0.00 | 0.00 | 0.00 |
July | 921.59 | 404.06 | 517.53 | 1159.97 | 226.66 | 0.00 | 0.00 | 0.00 |
August | 833.52 | 354.42 | 479.10 | 1019.31 | 291.60 | 0.00 | 0.00 | 0.00 |
September | 654.57 | 282.68 | 371.89 | 699.84 | 416.43 | 0.00 | 0.00 | 0.00 |
October | 424.33 | 149.47 | 274.85 | 296.36 | 677.49 | 0.00 | 0.00 | 0.00 |
November | 251.46 | 72.46 | 179.00 | 101.32 | 931.11 | 0.00 | 0.00 | 0.00 |
December | 217.99 | 47.50 | 170.49 | 33.32 | 1372.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 593.87 | 240.99 | 352.88 | 537.13 | 747.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 217.99 | 47.50 | 170.49 | 33.32 | 226.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1030.82 | 484.85 | 545.96 | 1199.18 | 1372.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 232.86 | 54.67 | 178.20 | 37.25 | 1362.99 | 0.00 | 0.00 | 0.00 |
February | 377.41 | 97.00 | 280.41 | 100.38 | 1294.01 | 0.00 | 0.00 | 0.00 |
March | 591.52 | 253.27 | 338.24 | 365.29 | 947.46 | 0.00 | 0.00 | 0.00 |
April | 724.23 | 296.97 | 427.27 | 556.39 | 720.28 | 0.00 | 0.00 | 0.00 |
May | 854.35 | 386.11 | 468.24 | 847.75 | 454.42 | 0.00 | 0.00 | 0.00 |
June | 1030.80 | 484.85 | 545.95 | 1199.16 | 305.29 | 0.00 | 0.00 | 0.00 |
July | 921.57 | 404.05 | 517.52 | 1159.95 | 226.66 | 0.00 | 0.00 | 0.00 |
August | 833.51 | 354.42 | 479.09 | 1019.30 | 291.59 | 0.00 | 0.00 | 0.00 |
September | 654.56 | 282.68 | 371.89 | 699.83 | 416.42 | 0.00 | 0.00 | 0.00 |
October | 424.32 | 149.47 | 274.85 | 296.35 | 677.48 | 0.00 | 0.00 | 0.00 |
November | 251.45 | 72.46 | 178.99 | 101.32 | 931.10 | 0.00 | 0.00 | 0.00 |
December | 217.99 | 47.50 | 170.49 | 33.32 | 1372.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 593.86 | 240.98 | 352.88 | 537.12 | 747.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 217.99 | 47.50 | 170.49 | 33.32 | 226.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1030.80 | 484.85 | 545.95 | 1199.16 | 1372.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 667.41 | 0.00 | 667.41 | 0.00 | 5867.28 | 0.00 | 0.00 | 0.00 |
February | 1016.88 | 0.00 | 1016.88 | 3.56 | 5614.74 | 0.00 | 0.00 | 0.00 |
March | 1233.19 | 0.00 | 1233.19 | 228.04 | 4026.18 | 0.00 | 0.00 | 0.00 |
April | 1571.33 | 6.27 | 1565.06 | 560.32 | 2736.86 | 0.00 | 0.00 | 0.00 |
May | 1825.81 | 77.42 | 1748.38 | 1159.69 | 1671.19 | 0.00 | 0.00 | 0.00 |
June | 2196.06 | 186.94 | 2009.12 | 2159.26 | 1041.33 | 0.00 | 0.00 | 0.00 |
July | 2037.14 | 131.50 | 1905.64 | 2462.51 | 717.29 | 0.00 | 0.00 | 0.00 |
August | 1762.69 | 26.82 | 1735.88 | 1984.04 | 962.62 | 0.00 | 0.00 | 0.00 |
September | 1341.45 | 0.28 | 1341.17 | 1079.16 | 1585.43 | 0.00 | 0.00 | 0.00 |
October | 1002.79 | 0.00 | 1002.79 | 319.67 | 2674.40 | 0.00 | 0.00 | 0.00 |
November | 673.85 | 0.00 | 673.85 | 72.92 | 3642.38 | 0.00 | 0.00 | 0.00 |
December | 624.67 | 0.00 | 624.67 | 1.34 | 5573.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1330.73 | 35.93 | 1294.81 | 841.27 | 2996.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 624.67 | 0.00 | 624.67 | 0.00 | 717.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2196.06 | 186.94 | 2009.12 | 2462.51 | 5867.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 814.23 | 262.55 | 551.68 | 202.92 | 3529.30 | 0.00 | 0.00 | 0.00 |
February | 1194.72 | 358.51 | 836.22 | 382.06 | 3392.98 | 0.00 | 0.00 | 0.00 |
March | 1714.40 | 717.98 | 996.42 | 1072.31 | 2434.65 | 0.00 | 0.00 | 0.00 |
April | 2269.11 | 1002.62 | 1266.50 | 1797.99 | 1707.38 | 0.00 | 0.00 | 0.00 |
May | 2542.22 | 1124.56 | 1417.66 | 2487.40 | 1122.90 | 0.00 | 0.00 | 0.00 |
June | 2839.23 | 1254.80 | 1584.43 | 3258.57 | 695.64 | 0.00 | 0.00 | 0.00 |
July | 2726.41 | 1200.40 | 1526.01 | 3462.96 | 473.73 | 0.00 | 0.00 | 0.00 |
August | 2462.24 | 1033.52 | 1428.73 | 3028.44 | 629.78 | 0.00 | 0.00 | 0.00 |
September | 2049.01 | 908.86 | 1140.15 | 2190.24 | 1009.48 | 0.00 | 0.00 | 0.00 |
October | 1390.43 | 575.12 | 815.31 | 1038.09 | 1681.17 | 0.00 | 0.00 | 0.00 |
November | 788.67 | 253.00 | 535.68 | 370.09 | 2318.04 | 0.00 | 0.00 | 0.00 |
December | 634.92 | 131.19 | 503.73 | 97.12 | 3493.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1788.12 | 737.04 | 1051.07 | 1622.66 | 1866.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 634.92 | 131.19 | 503.73 | 97.12 | 473.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2839.23 | 1254.80 | 1584.43 | 3462.96 | 3529.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2869.86 | 1675.22 | 1194.64 | 1881.90 | 4971.02 | 0.00 | 0.00 | 0.00 |
February | 3276.66 | 1579.98 | 1696.68 | 2017.31 | 4890.15 | 0.00 | 0.00 | 0.00 |
March | 3999.38 | 2247.23 | 1752.15 | 3314.33 | 3607.20 | 0.00 | 0.00 | 0.00 |
April | 3312.12 | 1323.53 | 1988.58 | 2927.63 | 2834.63 | 0.00 | 0.00 | 0.00 |
May | 2898.40 | 841.82 | 2056.58 | 2881.65 | 1890.33 | 0.00 | 0.00 | 0.00 |
June | 2816.31 | 596.79 | 2219.52 | 3272.46 | 1173.16 | 0.00 | 0.00 | 0.00 |
July | 2874.99 | 697.57 | 2177.42 | 3839.01 | 802.23 | 0.00 | 0.00 | 0.00 |
August | 3227.65 | 1046.49 | 2181.17 | 4217.90 | 1050.70 | 0.00 | 0.00 | 0.00 |
September | 3752.80 | 1827.89 | 1924.91 | 4419.83 | 1679.98 | 0.00 | 0.00 | 0.00 |
October | 3590.87 | 2051.18 | 1539.70 | 3471.33 | 2603.89 | 0.00 | 0.00 | 0.00 |
November | 2571.71 | 1451.82 | 1119.89 | 2092.02 | 3434.56 | 0.00 | 0.00 | 0.00 |
December | 2399.77 | 1241.99 | 1157.78 | 1462.62 | 4915.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3131.57 | 1381.06 | 1750.51 | 2988.97 | 2810.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2399.77 | 596.79 | 1119.89 | 1462.62 | 802.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3999.38 | 2247.23 | 2219.52 | 4419.83 | 4971.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 698.60 | 164.00 | 534.59 | 118.73 | 3780.61 | 0.00 | 0.00 | 0.00 |
February | 1132.23 | 290.99 | 841.24 | 306.73 | 3602.19 | 0.00 | 0.00 | 0.00 |
March | 1774.57 | 759.83 | 1014.74 | 1137.02 | 2545.64 | 0.00 | 0.00 | 0.00 |
April | 2172.72 | 890.90 | 1281.82 | 1745.77 | 1866.87 | 0.00 | 0.00 | 0.00 |
May | 2563.07 | 1158.34 | 1404.73 | 2567.60 | 1254.32 | 0.00 | 0.00 | 0.00 |
June | 3092.42 | 1454.55 | 1637.87 | 3621.14 | 829.81 | 0.00 | 0.00 | 0.00 |
July | 2764.74 | 1212.16 | 1552.58 | 3540.03 | 585.68 | 0.00 | 0.00 | 0.00 |
August | 2500.55 | 1063.26 | 1437.29 | 3137.44 | 729.67 | 0.00 | 0.00 | 0.00 |
September | 1963.70 | 848.04 | 1115.67 | 2142.31 | 1112.18 | 0.00 | 0.00 | 0.00 |
October | 1272.97 | 448.41 | 824.56 | 940.35 | 1787.81 | 0.00 | 0.00 | 0.00 |
November | 754.37 | 217.38 | 536.98 | 339.24 | 2414.76 | 0.00 | 0.00 | 0.00 |
December | 653.97 | 142.49 | 511.48 | 113.27 | 3646.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1781.59 | 722.95 | 1058.64 | 1649.94 | 2004.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 653.97 | 142.49 | 511.48 | 113.27 | 585.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3092.42 | 1454.55 | 1637.87 | 3621.14 | 3780.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 667.41 | 0.00 | 667.41 | 0.84 | 5666.90 | 0.00 | 0.00 | 0.00 |
February | 1016.88 | 0.00 | 1016.88 | 6.59 | 5415.36 | 0.00 | 0.00 | 0.00 |
March | 1233.19 | 0.00 | 1233.19 | 249.09 | 3782.62 | 0.00 | 0.00 | 0.00 |
April | 1571.33 | 6.27 | 1565.06 | 606.88 | 2509.64 | 0.00 | 0.00 | 0.00 |
May | 1825.81 | 77.42 | 1748.38 | 1212.96 | 1525.13 | 0.00 | 0.00 | 0.00 |
June | 2196.06 | 186.94 | 2009.12 | 2192.41 | 974.06 | 0.00 | 0.00 | 0.00 |
July | 2037.14 | 131.50 | 1905.64 | 2478.78 | 679.59 | 0.00 | 0.00 | 0.00 |
August | 1762.69 | 26.82 | 1735.88 | 2011.09 | 895.44 | 0.00 | 0.00 | 0.00 |
September | 1341.45 | 0.28 | 1341.17 | 1132.46 | 1425.89 | 0.00 | 0.00 | 0.00 |
October | 1002.79 | 0.00 | 1002.79 | 376.58 | 2371.41 | 0.00 | 0.00 | 0.00 |
November | 673.85 | 0.00 | 673.85 | 96.70 | 3281.34 | 0.00 | 0.00 | 0.00 |
December | 624.67 | 0.00 | 624.67 | 2.47 | 5328.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1330.73 | 35.93 | 1294.81 | 869.38 | 2808.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 624.67 | 0.00 | 624.67 | 0.84 | 679.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2196.06 | 186.94 | 2009.12 | 2478.78 | 5666.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 814.23 | 262.55 | 551.68 | 212.49 | 3409.66 | 0.00 | 0.00 | 0.00 |
February | 1194.72 | 358.51 | 836.22 | 396.45 | 3271.92 | 0.00 | 0.00 | 0.00 |
March | 1714.40 | 717.98 | 996.42 | 1111.43 | 2268.51 | 0.00 | 0.00 | 0.00 |
April | 2269.11 | 1002.62 | 1266.50 | 1851.73 | 1570.80 | 0.00 | 0.00 | 0.00 |
May | 2542.22 | 1124.56 | 1417.66 | 2514.83 | 1048.08 | 0.00 | 0.00 | 0.00 |
June | 2839.23 | 1254.80 | 1584.43 | 3255.38 | 670.03 | 0.00 | 0.00 | 0.00 |
July | 2726.41 | 1200.40 | 1526.01 | 3450.42 | 463.78 | 0.00 | 0.00 | 0.00 |
August | 2462.24 | 1033.52 | 1428.73 | 3025.82 | 605.61 | 0.00 | 0.00 | 0.00 |
September | 2049.01 | 908.86 | 1140.15 | 2217.56 | 931.00 | 0.00 | 0.00 | 0.00 |
October | 1390.43 | 575.12 | 815.31 | 1105.44 | 1489.62 | 0.00 | 0.00 | 0.00 |
November | 788.67 | 253.00 | 535.68 | 406.80 | 2074.03 | 0.00 | 0.00 | 0.00 |
December | 634.92 | 131.19 | 503.73 | 104.58 | 3347.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1788.12 | 737.04 | 1051.07 | 1644.71 | 1755.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 634.92 | 131.19 | 503.73 | 104.58 | 463.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2839.23 | 1254.80 | 1584.43 | 3450.42 | 3409.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2869.86 | 1675.22 | 1194.64 | 1920.65 | 4752.06 | 0.00 | 0.00 | 0.00 |
February | 3276.66 | 1579.98 | 1696.68 | 2051.95 | 4683.66 | 0.00 | 0.00 | 0.00 |
March | 3999.38 | 2247.23 | 1752.15 | 3370.11 | 3341.60 | 0.00 | 0.00 | 0.00 |
April | 3312.12 | 1323.53 | 1988.58 | 2979.88 | 2603.51 | 0.00 | 0.00 | 0.00 |
May | 2898.40 | 841.82 | 2056.58 | 2910.48 | 1736.97 | 0.00 | 0.00 | 0.00 |
June | 2816.31 | 596.79 | 2219.52 | 3277.23 | 1097.57 | 0.00 | 0.00 | 0.00 |
July | 2874.99 | 697.57 | 2177.42 | 3835.11 | 758.72 | 0.00 | 0.00 | 0.00 |
August | 3227.65 | 1046.49 | 2181.17 | 4220.93 | 981.55 | 0.00 | 0.00 | 0.00 |
September | 3752.80 | 1827.89 | 1924.91 | 4450.62 | 1527.74 | 0.00 | 0.00 | 0.00 |
October | 3590.87 | 2051.18 | 1539.70 | 3551.08 | 2309.49 | 0.00 | 0.00 | 0.00 |
November | 2571.71 | 1451.82 | 1119.89 | 2163.61 | 3077.06 | 0.00 | 0.00 | 0.00 |
December | 2399.77 | 1241.99 | 1157.78 | 1500.11 | 4660.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3131.57 | 1381.06 | 1750.51 | 3025.09 | 2616.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2399.77 | 596.79 | 1119.89 | 1500.11 | 758.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3999.38 | 2247.23 | 2219.52 | 4450.62 | 4752.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 698.60 | 164.00 | 534.59 | 121.77 | 3657.06 | 0.00 | 0.00 | 0.00 |
February | 1132.23 | 290.99 | 841.24 | 307.77 | 3485.90 | 0.00 | 0.00 | 0.00 |
March | 1774.57 | 759.83 | 1014.74 | 1146.53 | 2397.09 | 0.00 | 0.00 | 0.00 |
April | 2172.72 | 890.90 | 1281.82 | 1755.51 | 1740.00 | 0.00 | 0.00 | 0.00 |
May | 2563.07 | 1158.34 | 1404.73 | 2564.07 | 1176.10 | 0.00 | 0.00 | 0.00 |
June | 3092.42 | 1454.55 | 1637.87 | 3600.11 | 793.70 | 0.00 | 0.00 | 0.00 |
July | 2764.74 | 1212.16 | 1552.58 | 3518.54 | 566.30 | 0.00 | 0.00 | 0.00 |
August | 2500.55 | 1063.26 | 1437.29 | 3126.73 | 697.53 | 0.00 | 0.00 | 0.00 |
September | 1963.70 | 848.04 | 1115.67 | 2147.95 | 1034.97 | 0.00 | 0.00 | 0.00 |
October | 1272.97 | 448.41 | 824.56 | 963.60 | 1627.78 | 0.00 | 0.00 | 0.00 |
November | 754.37 | 217.38 | 536.98 | 354.55 | 2213.48 | 0.00 | 0.00 | 0.00 |
December | 653.97 | 142.49 | 511.48 | 116.15 | 3503.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1781.59 | 722.95 | 1058.64 | 1651.07 | 1899.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 653.97 | 142.49 | 511.48 | 116.15 | 566.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3092.42 | 1454.55 | 1637.87 | 3600.11 | 3657.06 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.357521E+09 | 0.00 | 0.357521E+09 | 0.00 | 0.334461E+10 |
February | 0.492012E+09 | 0.00 | 0.492012E+09 | 859577.45 | 0.286784E+10 |
March | 0.660601E+09 | 0.00 | 0.660601E+09 | 0.104391E+09 | 0.233562E+10 |
April | 0.814588E+09 | 3250527.68 | 0.811337E+09 | 0.240400E+09 | 0.158740E+10 |
May | 0.978061E+09 | 41475352.83 | 0.936586E+09 | 0.575259E+09 | 0.979686E+09 |
June | 0.113845E+10 | 96910929.73 | 0.104154E+10 | 0.108303E+10 | 0.585633E+09 |
July | 0.109127E+10 | 70443851.01 | 0.102082E+10 | 0.128292E+10 | 0.418148E+09 |
August | 0.944251E+09 | 14364725.36 | 0.929886E+09 | 0.102502E+10 | 0.570581E+09 |
September | 0.695415E+09 | 144477.05 | 0.695270E+09 | 0.519027E+09 | 0.924030E+09 |
October | 0.537181E+09 | 0.00 | 0.537181E+09 | 0.132645E+09 | 0.161895E+10 |
November | 0.349328E+09 | 0.00 | 0.349328E+09 | 24351569.02 | 0.213019E+10 |
December | 0.334629E+09 | 0.00 | 0.334629E+09 | 281493.20 | 0.324483E+10 |
Annual Sum or Average | 0.839331E+10 | 0.226590E+09 | 0.816672E+10 | 0.498819E+10 | 0.206075E+11 |
Minimum of Months | 0.334629E+09 | 0.00 | 0.334629E+09 | 0.00 | 0.418148E+09 |
Maximum of Months | 0.113845E+10 | 96910929.73 | 0.104154E+10 | 0.128292E+10 | 0.334461E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.357520E+09 | 0.00 | 0.357520E+09 | 0.00 | 0.334462E+10 |
February | 0.492012E+09 | 0.00 | 0.492012E+09 | 859570.45 | 0.286784E+10 |
March | 0.660600E+09 | 0.00 | 0.660600E+09 | 0.104391E+09 | 0.233562E+10 |
April | 0.814587E+09 | 3250523.78 | 0.811336E+09 | 0.240400E+09 | 0.158740E+10 |
May | 0.978060E+09 | 41475303.07 | 0.936585E+09 | 0.575258E+09 | 0.979686E+09 |
June | 0.113845E+10 | 96910813.45 | 0.104154E+10 | 0.108303E+10 | 0.585633E+09 |
July | 0.109127E+10 | 70443766.48 | 0.102082E+10 | 0.128292E+10 | 0.418148E+09 |
August | 0.944250E+09 | 14364708.13 | 0.929885E+09 | 0.102502E+10 | 0.570581E+09 |
September | 0.695414E+09 | 144476.88 | 0.695270E+09 | 0.519026E+09 | 0.924030E+09 |
October | 0.537180E+09 | 0.00 | 0.537180E+09 | 0.132645E+09 | 0.161895E+10 |
November | 0.349328E+09 | 0.00 | 0.349328E+09 | 24351503.95 | 0.213019E+10 |
December | 0.334628E+09 | 0.00 | 0.334628E+09 | 281490.88 | 0.324483E+10 |
Annual Sum or Average | 0.839330E+10 | 0.226590E+09 | 0.816671E+10 | 0.498818E+10 | 0.206075E+11 |
Minimum of Months | 0.334628E+09 | 0.00 | 0.334628E+09 | 0.00 | 0.418148E+09 |
Maximum of Months | 0.113845E+10 | 96910813.45 | 0.104154E+10 | 0.128292E+10 | 0.334462E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.357521E+09 | 0.00 | 0.357521E+09 | 0.00 | 0.334461E+10 |
February | 0.492012E+09 | 0.00 | 0.492012E+09 | 859577.45 | 0.286784E+10 |
March | 0.660601E+09 | 0.00 | 0.660601E+09 | 0.104391E+09 | 0.233562E+10 |
April | 0.814588E+09 | 3250527.68 | 0.811337E+09 | 0.240400E+09 | 0.158740E+10 |
May | 0.978061E+09 | 41475352.83 | 0.936586E+09 | 0.575259E+09 | 0.979686E+09 |
June | 0.113845E+10 | 96910929.73 | 0.104154E+10 | 0.108303E+10 | 0.585633E+09 |
July | 0.109127E+10 | 70443851.01 | 0.102082E+10 | 0.128292E+10 | 0.418148E+09 |
August | 0.944251E+09 | 14364725.36 | 0.929886E+09 | 0.102502E+10 | 0.570581E+09 |
September | 0.695415E+09 | 144477.05 | 0.695270E+09 | 0.519027E+09 | 0.924030E+09 |
October | 0.537181E+09 | 0.00 | 0.537181E+09 | 0.132645E+09 | 0.161895E+10 |
November | 0.349328E+09 | 0.00 | 0.349328E+09 | 24351569.02 | 0.213019E+10 |
December | 0.334629E+09 | 0.00 | 0.334629E+09 | 281493.20 | 0.324483E+10 |
Annual Sum or Average | 0.839331E+10 | 0.226590E+09 | 0.816672E+10 | 0.498819E+10 | 0.206075E+11 |
Minimum of Months | 0.334629E+09 | 0.00 | 0.334629E+09 | 0.00 | 0.418148E+09 |
Maximum of Months | 0.113845E+10 | 96910929.73 | 0.104154E+10 | 0.128292E+10 | 0.334461E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.357520E+09 | 0.00 | 0.357520E+09 | 0.00 | 0.334462E+10 |
February | 0.492012E+09 | 0.00 | 0.492012E+09 | 859570.45 | 0.286784E+10 |
March | 0.660600E+09 | 0.00 | 0.660600E+09 | 0.104391E+09 | 0.233562E+10 |
April | 0.814587E+09 | 3250523.78 | 0.811336E+09 | 0.240400E+09 | 0.158740E+10 |
May | 0.978060E+09 | 41475303.07 | 0.936585E+09 | 0.575258E+09 | 0.979686E+09 |
June | 0.113845E+10 | 96910813.45 | 0.104154E+10 | 0.108303E+10 | 0.585633E+09 |
July | 0.109127E+10 | 70443766.48 | 0.102082E+10 | 0.128292E+10 | 0.418148E+09 |
August | 0.944250E+09 | 14364708.13 | 0.929885E+09 | 0.102502E+10 | 0.570581E+09 |
September | 0.695414E+09 | 144476.88 | 0.695270E+09 | 0.519026E+09 | 0.924030E+09 |
October | 0.537180E+09 | 0.00 | 0.537180E+09 | 0.132645E+09 | 0.161895E+10 |
November | 0.349328E+09 | 0.00 | 0.349328E+09 | 24351503.95 | 0.213019E+10 |
December | 0.334628E+09 | 0.00 | 0.334628E+09 | 281490.88 | 0.324483E+10 |
Annual Sum or Average | 0.839330E+10 | 0.226590E+09 | 0.816671E+10 | 0.498818E+10 | 0.206075E+11 |
Minimum of Months | 0.334628E+09 | 0.00 | 0.334628E+09 | 0.00 | 0.418148E+09 |
Maximum of Months | 0.113845E+10 | 96910813.45 | 0.104154E+10 | 0.128292E+10 | 0.334462E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.357506E+09 | 0.00 | 0.357506E+09 | 0.00 | 0.334448E+10 |
February | 0.491992E+09 | 0.00 | 0.491992E+09 | 859542.81 | 0.286772E+10 |
March | 0.660574E+09 | 0.00 | 0.660574E+09 | 0.104387E+09 | 0.233552E+10 |
April | 0.814555E+09 | 3250396.67 | 0.811304E+09 | 0.240391E+09 | 0.158734E+10 |
May | 0.978022E+09 | 41473681.19 | 0.936548E+09 | 0.575236E+09 | 0.979646E+09 |
June | 0.113841E+10 | 96907023.80 | 0.104150E+10 | 0.108299E+10 | 0.585610E+09 |
July | 0.109122E+10 | 70441011.81 | 0.102078E+10 | 0.128287E+10 | 0.418131E+09 |
August | 0.944213E+09 | 14364146.40 | 0.929848E+09 | 0.102498E+10 | 0.570558E+09 |
September | 0.695387E+09 | 144471.23 | 0.695242E+09 | 0.519006E+09 | 0.923993E+09 |
October | 0.537159E+09 | 0.00 | 0.537159E+09 | 0.132640E+09 | 0.161888E+10 |
November | 0.349314E+09 | 0.00 | 0.349314E+09 | 24350587.54 | 0.213011E+10 |
December | 0.334615E+09 | 0.00 | 0.334615E+09 | 281481.86 | 0.324470E+10 |
Annual Sum or Average | 0.839297E+10 | 0.226581E+09 | 0.816639E+10 | 0.498799E+10 | 0.206067E+11 |
Minimum of Months | 0.334615E+09 | 0.00 | 0.334615E+09 | 0.00 | 0.418131E+09 |
Maximum of Months | 0.113841E+10 | 96907023.80 | 0.104150E+10 | 0.128287E+10 | 0.334448E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.726953E+09 | 0.234410E+09 | 0.492542E+09 | 0.175225E+09 | 0.335265E+10 |
February | 0.963436E+09 | 0.289103E+09 | 0.674332E+09 | 0.300987E+09 | 0.286744E+10 |
March | 0.153063E+10 | 0.641018E+09 | 0.889611E+09 | 0.956666E+09 | 0.228121E+10 |
April | 0.196053E+10 | 0.866269E+09 | 0.109426E+10 | 0.156110E+10 | 0.155852E+10 |
May | 0.226972E+10 | 0.100402E+10 | 0.126570E+10 | 0.224923E+10 | 0.104529E+10 |
June | 0.245312E+10 | 0.108416E+10 | 0.136896E+10 | 0.284578E+10 | 0.627094E+09 |
July | 0.243416E+10 | 0.107173E+10 | 0.136243E+10 | 0.312835E+10 | 0.423335E+09 |
August | 0.219831E+10 | 0.922732E+09 | 0.127558E+10 | 0.273438E+10 | 0.564144E+09 |
September | 0.177037E+10 | 0.785267E+09 | 0.985100E+09 | 0.190617E+10 | 0.926998E+09 |
October | 0.124139E+10 | 0.513470E+09 | 0.727915E+09 | 0.919795E+09 | 0.161282E+10 |
November | 0.681422E+09 | 0.218592E+09 | 0.462830E+09 | 0.306315E+09 | 0.216355E+10 |
December | 0.566865E+09 | 0.117127E+09 | 0.449739E+09 | 78361005.76 | 0.334374E+10 |
Annual Sum or Average | 0.187969E+11 | 0.774789E+10 | 0.110490E+11 | 0.171624E+11 | 0.207668E+11 |
Minimum of Months | 0.566865E+09 | 0.117127E+09 | 0.449739E+09 | 78361005.76 | 0.423335E+09 |
Maximum of Months | 0.245312E+10 | 0.108416E+10 | 0.136896E+10 | 0.312835E+10 | 0.335265E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.726953E+09 | 0.234410E+09 | 0.492542E+09 | 0.175225E+09 | 0.335265E+10 |
February | 0.963436E+09 | 0.289103E+09 | 0.674332E+09 | 0.300987E+09 | 0.286744E+10 |
March | 0.153063E+10 | 0.641018E+09 | 0.889611E+09 | 0.956666E+09 | 0.228121E+10 |
April | 0.196053E+10 | 0.866269E+09 | 0.109426E+10 | 0.156110E+10 | 0.155852E+10 |
May | 0.226972E+10 | 0.100402E+10 | 0.126570E+10 | 0.224923E+10 | 0.104529E+10 |
June | 0.245312E+10 | 0.108416E+10 | 0.136896E+10 | 0.284578E+10 | 0.627094E+09 |
July | 0.243416E+10 | 0.107173E+10 | 0.136243E+10 | 0.312835E+10 | 0.423335E+09 |
August | 0.219831E+10 | 0.922732E+09 | 0.127558E+10 | 0.273438E+10 | 0.564144E+09 |
September | 0.177037E+10 | 0.785267E+09 | 0.985100E+09 | 0.190617E+10 | 0.926998E+09 |
October | 0.124139E+10 | 0.513470E+09 | 0.727915E+09 | 0.919795E+09 | 0.161282E+10 |
November | 0.681422E+09 | 0.218592E+09 | 0.462830E+09 | 0.306315E+09 | 0.216355E+10 |
December | 0.566865E+09 | 0.117127E+09 | 0.449739E+09 | 78361005.76 | 0.334374E+10 |
Annual Sum or Average | 0.187969E+11 | 0.774789E+10 | 0.110490E+11 | 0.171624E+11 | 0.207668E+11 |
Minimum of Months | 0.566865E+09 | 0.117127E+09 | 0.449739E+09 | 78361005.76 | 0.423335E+09 |
Maximum of Months | 0.245312E+10 | 0.108416E+10 | 0.136896E+10 | 0.312835E+10 | 0.335265E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.726939E+09 | 0.234406E+09 | 0.492533E+09 | 0.175222E+09 | 0.335258E+10 |
February | 0.963418E+09 | 0.289098E+09 | 0.674320E+09 | 0.300981E+09 | 0.286738E+10 |
March | 0.153060E+10 | 0.641006E+09 | 0.889595E+09 | 0.956649E+09 | 0.228117E+10 |
April | 0.196050E+10 | 0.866253E+09 | 0.109424E+10 | 0.156107E+10 | 0.155850E+10 |
May | 0.226967E+10 | 0.100400E+10 | 0.126568E+10 | 0.224919E+10 | 0.104528E+10 |
June | 0.245308E+10 | 0.108414E+10 | 0.136894E+10 | 0.284573E+10 | 0.627083E+09 |
July | 0.243412E+10 | 0.107171E+10 | 0.136241E+10 | 0.312830E+10 | 0.423327E+09 |
August | 0.219827E+10 | 0.922715E+09 | 0.127556E+10 | 0.273433E+10 | 0.564134E+09 |
September | 0.177033E+10 | 0.785252E+09 | 0.985082E+09 | 0.190613E+10 | 0.926981E+09 |
October | 0.124136E+10 | 0.513461E+09 | 0.727902E+09 | 0.919779E+09 | 0.161279E+10 |
November | 0.681409E+09 | 0.218588E+09 | 0.462821E+09 | 0.306309E+09 | 0.216351E+10 |
December | 0.566855E+09 | 0.117124E+09 | 0.449730E+09 | 78359573.93 | 0.334368E+10 |
Annual Sum or Average | 0.187966E+11 | 0.774775E+10 | 0.110488E+11 | 0.171621E+11 | 0.207664E+11 |
Minimum of Months | 0.566855E+09 | 0.117124E+09 | 0.449730E+09 | 78359573.93 | 0.423327E+09 |
Maximum of Months | 0.245308E+10 | 0.108414E+10 | 0.136894E+10 | 0.312830E+10 | 0.335258E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.153734E+10 | 0.897393E+09 | 0.639951E+09 | 0.101661E+10 | 0.272915E+10 |
February | 0.158540E+10 | 0.764465E+09 | 0.820933E+09 | 0.993584E+09 | 0.239646E+10 |
March | 0.214241E+10 | 0.120381E+10 | 0.938605E+09 | 0.180273E+10 | 0.197320E+10 |
April | 0.171702E+10 | 0.686127E+09 | 0.103089E+10 | 0.152955E+10 | 0.151799E+10 |
May | 0.155263E+10 | 0.450949E+09 | 0.110168E+10 | 0.156367E+10 | 0.103484E+10 |
June | 0.145999E+10 | 0.309379E+09 | 0.115061E+10 | 0.170795E+10 | 0.632128E+09 |
July | 0.154009E+10 | 0.373677E+09 | 0.116642E+10 | 0.206569E+10 | 0.443537E+09 |
August | 0.172901E+10 | 0.560588E+09 | 0.116842E+10 | 0.227017E+10 | 0.580267E+09 |
September | 0.194547E+10 | 0.947590E+09 | 0.997884E+09 | 0.231307E+10 | 0.895507E+09 |
October | 0.192358E+10 | 0.109879E+10 | 0.824795E+09 | 0.188094E+10 | 0.143384E+10 |
November | 0.133319E+10 | 0.752630E+09 | 0.580559E+09 | 0.109042E+10 | 0.184284E+10 |
December | 0.128552E+10 | 0.665317E+09 | 0.620207E+09 | 0.782994E+09 | 0.272756E+10 |
Annual Sum or Average | 0.197517E+11 | 0.871071E+10 | 0.110410E+11 | 0.190174E+11 | 0.182073E+11 |
Minimum of Months | 0.128552E+10 | 0.309379E+09 | 0.580559E+09 | 0.782994E+09 | 0.443537E+09 |
Maximum of Months | 0.214241E+10 | 0.120381E+10 | 0.116842E+10 | 0.231307E+10 | 0.272915E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.153734E+10 | 0.897392E+09 | 0.639950E+09 | 0.101661E+10 | 0.272915E+10 |
February | 0.158540E+10 | 0.764464E+09 | 0.820932E+09 | 0.993582E+09 | 0.239646E+10 |
March | 0.214241E+10 | 0.120381E+10 | 0.938604E+09 | 0.180273E+10 | 0.197320E+10 |
April | 0.171702E+10 | 0.686126E+09 | 0.103089E+10 | 0.152954E+10 | 0.151799E+10 |
May | 0.155263E+10 | 0.450949E+09 | 0.110168E+10 | 0.156366E+10 | 0.103484E+10 |
June | 0.145999E+10 | 0.309379E+09 | 0.115061E+10 | 0.170795E+10 | 0.632128E+09 |
July | 0.154009E+10 | 0.373677E+09 | 0.116642E+10 | 0.206568E+10 | 0.443537E+09 |
August | 0.172901E+10 | 0.560587E+09 | 0.116842E+10 | 0.227016E+10 | 0.580266E+09 |
September | 0.194547E+10 | 0.947589E+09 | 0.997883E+09 | 0.231306E+10 | 0.895507E+09 |
October | 0.192358E+10 | 0.109879E+10 | 0.824794E+09 | 0.188094E+10 | 0.143384E+10 |
November | 0.133319E+10 | 0.752629E+09 | 0.580559E+09 | 0.109042E+10 | 0.184284E+10 |
December | 0.128552E+10 | 0.665317E+09 | 0.620207E+09 | 0.782993E+09 | 0.272756E+10 |
Annual Sum or Average | 0.197517E+11 | 0.871070E+10 | 0.110409E+11 | 0.190173E+11 | 0.182073E+11 |
Minimum of Months | 0.128552E+10 | 0.309379E+09 | 0.580559E+09 | 0.782993E+09 | 0.443537E+09 |
Maximum of Months | 0.214241E+10 | 0.120381E+10 | 0.116842E+10 | 0.231306E+10 | 0.272915E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.153734E+10 | 0.897393E+09 | 0.639951E+09 | 0.101661E+10 | 0.272915E+10 |
February | 0.158540E+10 | 0.764465E+09 | 0.820933E+09 | 0.993584E+09 | 0.239646E+10 |
March | 0.214241E+10 | 0.120381E+10 | 0.938605E+09 | 0.180273E+10 | 0.197320E+10 |
April | 0.171702E+10 | 0.686127E+09 | 0.103089E+10 | 0.152955E+10 | 0.151799E+10 |
May | 0.155263E+10 | 0.450949E+09 | 0.110168E+10 | 0.156367E+10 | 0.103484E+10 |
June | 0.145999E+10 | 0.309379E+09 | 0.115061E+10 | 0.170795E+10 | 0.632128E+09 |
July | 0.154009E+10 | 0.373677E+09 | 0.116642E+10 | 0.206569E+10 | 0.443537E+09 |
August | 0.172901E+10 | 0.560588E+09 | 0.116842E+10 | 0.227017E+10 | 0.580267E+09 |
September | 0.194547E+10 | 0.947590E+09 | 0.997884E+09 | 0.231307E+10 | 0.895507E+09 |
October | 0.192358E+10 | 0.109879E+10 | 0.824795E+09 | 0.188094E+10 | 0.143384E+10 |
November | 0.133319E+10 | 0.752630E+09 | 0.580559E+09 | 0.109042E+10 | 0.184284E+10 |
December | 0.128552E+10 | 0.665317E+09 | 0.620207E+09 | 0.782994E+09 | 0.272756E+10 |
Annual Sum or Average | 0.197517E+11 | 0.871071E+10 | 0.110410E+11 | 0.190174E+11 | 0.182073E+11 |
Minimum of Months | 0.128552E+10 | 0.309379E+09 | 0.580559E+09 | 0.782994E+09 | 0.443537E+09 |
Maximum of Months | 0.214241E+10 | 0.120381E+10 | 0.116842E+10 | 0.231307E+10 | 0.272915E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.153734E+10 | 0.897392E+09 | 0.639950E+09 | 0.101661E+10 | 0.272915E+10 |
February | 0.158540E+10 | 0.764464E+09 | 0.820932E+09 | 0.993582E+09 | 0.239646E+10 |
March | 0.214241E+10 | 0.120381E+10 | 0.938604E+09 | 0.180273E+10 | 0.197320E+10 |
April | 0.171702E+10 | 0.686126E+09 | 0.103089E+10 | 0.152954E+10 | 0.151799E+10 |
May | 0.155263E+10 | 0.450949E+09 | 0.110168E+10 | 0.156366E+10 | 0.103484E+10 |
June | 0.145999E+10 | 0.309379E+09 | 0.115061E+10 | 0.170795E+10 | 0.632128E+09 |
July | 0.154009E+10 | 0.373677E+09 | 0.116642E+10 | 0.206568E+10 | 0.443537E+09 |
August | 0.172901E+10 | 0.560587E+09 | 0.116842E+10 | 0.227016E+10 | 0.580266E+09 |
September | 0.194547E+10 | 0.947589E+09 | 0.997883E+09 | 0.231306E+10 | 0.895507E+09 |
October | 0.192358E+10 | 0.109879E+10 | 0.824794E+09 | 0.188094E+10 | 0.143384E+10 |
November | 0.133319E+10 | 0.752629E+09 | 0.580559E+09 | 0.109042E+10 | 0.184284E+10 |
December | 0.128552E+10 | 0.665317E+09 | 0.620207E+09 | 0.782993E+09 | 0.272756E+10 |
Annual Sum or Average | 0.197517E+11 | 0.871070E+10 | 0.110409E+11 | 0.190173E+11 | 0.182073E+11 |
Minimum of Months | 0.128552E+10 | 0.309379E+09 | 0.580559E+09 | 0.782993E+09 | 0.443537E+09 |
Maximum of Months | 0.214241E+10 | 0.120381E+10 | 0.116842E+10 | 0.231306E+10 | 0.272915E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.153728E+10 | 0.897357E+09 | 0.639925E+09 | 0.101657E+10 | 0.272904E+10 |
February | 0.158533E+10 | 0.764434E+09 | 0.820900E+09 | 0.993544E+09 | 0.239636E+10 |
March | 0.214233E+10 | 0.120376E+10 | 0.938567E+09 | 0.180266E+10 | 0.197312E+10 |
April | 0.171695E+10 | 0.686099E+09 | 0.103085E+10 | 0.152949E+10 | 0.151793E+10 |
May | 0.155257E+10 | 0.450931E+09 | 0.110164E+10 | 0.156360E+10 | 0.103480E+10 |
June | 0.145993E+10 | 0.309367E+09 | 0.115056E+10 | 0.170788E+10 | 0.632103E+09 |
July | 0.154003E+10 | 0.373662E+09 | 0.116637E+10 | 0.206560E+10 | 0.443520E+09 |
August | 0.172894E+10 | 0.560566E+09 | 0.116837E+10 | 0.227007E+10 | 0.580243E+09 |
September | 0.194540E+10 | 0.947552E+09 | 0.997843E+09 | 0.231297E+10 | 0.895471E+09 |
October | 0.192350E+10 | 0.109874E+10 | 0.824761E+09 | 0.188087E+10 | 0.143378E+10 |
November | 0.133314E+10 | 0.752600E+09 | 0.580536E+09 | 0.109038E+10 | 0.184276E+10 |
December | 0.128547E+10 | 0.665291E+09 | 0.620182E+09 | 0.782963E+09 | 0.272745E+10 |
Annual Sum or Average | 0.197509E+11 | 0.871036E+10 | 0.110405E+11 | 0.190166E+11 | 0.182066E+11 |
Minimum of Months | 0.128547E+10 | 0.309367E+09 | 0.580536E+09 | 0.782963E+09 | 0.443520E+09 |
Maximum of Months | 0.214233E+10 | 0.120376E+10 | 0.116837E+10 | 0.231297E+10 | 0.272904E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.623712E+09 | 0.146423E+09 | 0.477289E+09 | 99776188.04 | 0.365071E+10 |
February | 0.913041E+09 | 0.234658E+09 | 0.678382E+09 | 0.242854E+09 | 0.313052E+10 |
March | 0.158435E+10 | 0.678383E+09 | 0.905970E+09 | 0.978412E+09 | 0.253771E+10 |
April | 0.187725E+10 | 0.769748E+09 | 0.110750E+10 | 0.144218E+10 | 0.186700E+10 |
May | 0.228833E+10 | 0.103418E+10 | 0.125415E+10 | 0.227066E+10 | 0.121714E+10 |
June | 0.267188E+10 | 0.125674E+10 | 0.141514E+10 | 0.310828E+10 | 0.791321E+09 |
July | 0.246839E+10 | 0.108223E+10 | 0.138616E+10 | 0.310686E+10 | 0.607095E+09 |
August | 0.223251E+10 | 0.949285E+09 | 0.128323E+10 | 0.273013E+10 | 0.781022E+09 |
September | 0.169666E+10 | 0.732713E+09 | 0.963945E+09 | 0.181400E+10 | 0.107937E+10 |
October | 0.113652E+10 | 0.400346E+09 | 0.736171E+09 | 0.793766E+09 | 0.181460E+10 |
November | 0.651778E+09 | 0.187819E+09 | 0.463959E+09 | 0.262630E+09 | 0.241345E+10 |
December | 0.583868E+09 | 0.127218E+09 | 0.456650E+09 | 89250135.48 | 0.367616E+10 |
Annual Sum or Average | 0.187283E+11 | 0.759974E+10 | 0.111285E+11 | 0.169388E+11 | 0.235661E+11 |
Minimum of Months | 0.583868E+09 | 0.127218E+09 | 0.456650E+09 | 89250135.48 | 0.607095E+09 |
Maximum of Months | 0.267188E+10 | 0.125674E+10 | 0.141514E+10 | 0.310828E+10 | 0.367616E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.623712E+09 | 0.146423E+09 | 0.477289E+09 | 99776188.04 | 0.365071E+10 |
February | 0.913041E+09 | 0.234658E+09 | 0.678382E+09 | 0.242854E+09 | 0.313052E+10 |
March | 0.158435E+10 | 0.678383E+09 | 0.905970E+09 | 0.978412E+09 | 0.253771E+10 |
April | 0.187725E+10 | 0.769748E+09 | 0.110750E+10 | 0.144218E+10 | 0.186700E+10 |
May | 0.228833E+10 | 0.103418E+10 | 0.125415E+10 | 0.227066E+10 | 0.121714E+10 |
June | 0.267188E+10 | 0.125674E+10 | 0.141514E+10 | 0.310828E+10 | 0.791321E+09 |
July | 0.246839E+10 | 0.108223E+10 | 0.138616E+10 | 0.310686E+10 | 0.607095E+09 |
August | 0.223251E+10 | 0.949285E+09 | 0.128323E+10 | 0.273013E+10 | 0.781022E+09 |
September | 0.169666E+10 | 0.732713E+09 | 0.963945E+09 | 0.181400E+10 | 0.107937E+10 |
October | 0.113652E+10 | 0.400346E+09 | 0.736171E+09 | 0.793766E+09 | 0.181460E+10 |
November | 0.651778E+09 | 0.187819E+09 | 0.463959E+09 | 0.262630E+09 | 0.241345E+10 |
December | 0.583868E+09 | 0.127218E+09 | 0.456650E+09 | 89250135.48 | 0.367616E+10 |
Annual Sum or Average | 0.187283E+11 | 0.759974E+10 | 0.111285E+11 | 0.169388E+11 | 0.235661E+11 |
Minimum of Months | 0.583868E+09 | 0.127218E+09 | 0.456650E+09 | 89250135.48 | 0.607095E+09 |
Maximum of Months | 0.267188E+10 | 0.125674E+10 | 0.141514E+10 | 0.310828E+10 | 0.367616E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.623701E+09 | 0.146421E+09 | 0.477280E+09 | 99774364.92 | 0.365064E+10 |
February | 0.913024E+09 | 0.234654E+09 | 0.678370E+09 | 0.242850E+09 | 0.313046E+10 |
March | 0.158432E+10 | 0.678370E+09 | 0.905953E+09 | 0.978394E+09 | 0.253767E+10 |
April | 0.187722E+10 | 0.769734E+09 | 0.110748E+10 | 0.144216E+10 | 0.186696E+10 |
May | 0.228829E+10 | 0.103416E+10 | 0.125413E+10 | 0.227062E+10 | 0.121712E+10 |
June | 0.267183E+10 | 0.125672E+10 | 0.141511E+10 | 0.310823E+10 | 0.791306E+09 |
July | 0.246834E+10 | 0.108221E+10 | 0.138614E+10 | 0.310680E+10 | 0.607084E+09 |
August | 0.223247E+10 | 0.949268E+09 | 0.128320E+10 | 0.273008E+10 | 0.781008E+09 |
September | 0.169663E+10 | 0.732699E+09 | 0.963928E+09 | 0.181396E+10 | 0.107935E+10 |
October | 0.113650E+10 | 0.400339E+09 | 0.736157E+09 | 0.793752E+09 | 0.181457E+10 |
November | 0.651766E+09 | 0.187816E+09 | 0.463951E+09 | 0.262625E+09 | 0.241340E+10 |
December | 0.583857E+09 | 0.127216E+09 | 0.456641E+09 | 89248504.69 | 0.367609E+10 |
Annual Sum or Average | 0.187279E+11 | 0.759960E+10 | 0.111283E+11 | 0.169385E+11 | 0.235657E+11 |
Minimum of Months | 0.583857E+09 | 0.127216E+09 | 0.456641E+09 | 89248504.69 | 0.607084E+09 |
Maximum of Months | 0.267183E+10 | 0.125672E+10 | 0.141511E+10 | 0.310823E+10 | 0.367609E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.178758E+10 | 0.00 | 0.178758E+10 | 0.00 | 0.157149E+11 |
February | 0.246003E+10 | 0.00 | 0.246003E+10 | 8611162.58 | 0.135832E+11 |
March | 0.330296E+10 | 0.00 | 0.330296E+10 | 0.610789E+09 | 0.107837E+11 |
April | 0.407289E+10 | 16252441.88 | 0.405664E+10 | 0.145235E+10 | 0.709394E+10 |
May | 0.489025E+10 | 0.207374E+09 | 0.468287E+10 | 0.310611E+10 | 0.447611E+10 |
June | 0.569220E+10 | 0.484549E+09 | 0.520765E+10 | 0.559679E+10 | 0.269913E+10 |
July | 0.545628E+10 | 0.352215E+09 | 0.510406E+10 | 0.659560E+10 | 0.192120E+10 |
August | 0.472120E+10 | 71822758.33 | 0.464937E+10 | 0.531406E+10 | 0.257827E+10 |
September | 0.347703E+10 | 722376.53 | 0.347631E+10 | 0.279717E+10 | 0.410944E+10 |
October | 0.268587E+10 | 0.00 | 0.268587E+10 | 0.856193E+09 | 0.716310E+10 |
November | 0.174662E+10 | 0.00 | 0.174662E+10 | 0.189003E+09 | 0.944105E+10 |
December | 0.167312E+10 | 0.00 | 0.167312E+10 | 3601448.41 | 0.149279E+11 |
Annual Sum or Average | 0.419660E+11 | 0.113294E+10 | 0.408331E+11 | 0.265303E+11 | 0.944920E+11 |
Minimum of Months | 0.167312E+10 | 0.00 | 0.167312E+10 | 0.00 | 0.192120E+10 |
Maximum of Months | 0.569220E+10 | 0.484549E+09 | 0.520765E+10 | 0.659560E+10 | 0.157149E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.218084E+10 | 0.703223E+09 | 0.147761E+10 | 0.543502E+09 | 0.945288E+10 |
February | 0.289028E+10 | 0.867301E+09 | 0.202298E+10 | 0.924270E+09 | 0.820831E+10 |
March | 0.459184E+10 | 0.192303E+10 | 0.266881E+10 | 0.287208E+10 | 0.652098E+10 |
April | 0.588154E+10 | 0.259878E+10 | 0.328276E+10 | 0.466040E+10 | 0.442552E+10 |
May | 0.680908E+10 | 0.301202E+10 | 0.379706E+10 | 0.666226E+10 | 0.300757E+10 |
June | 0.735928E+10 | 0.325244E+10 | 0.410684E+10 | 0.844621E+10 | 0.180309E+10 |
July | 0.730241E+10 | 0.321515E+10 | 0.408726E+10 | 0.927520E+10 | 0.126883E+10 |
August | 0.659487E+10 | 0.276817E+10 | 0.382671E+10 | 0.811136E+10 | 0.168681E+10 |
September | 0.531105E+10 | 0.235578E+10 | 0.295527E+10 | 0.567710E+10 | 0.261657E+10 |
October | 0.372412E+10 | 0.154040E+10 | 0.218372E+10 | 0.278042E+10 | 0.450286E+10 |
November | 0.204424E+10 | 0.655770E+09 | 0.138847E+10 | 0.959277E+09 | 0.600836E+10 |
December | 0.170058E+10 | 0.351376E+09 | 0.134920E+10 | 0.260129E+09 | 0.935700E+10 |
Annual Sum or Average | 0.563901E+11 | 0.232434E+11 | 0.331467E+11 | 0.511722E+11 | 0.588588E+11 |
Minimum of Months | 0.170058E+10 | 0.351376E+09 | 0.134920E+10 | 0.260129E+09 | 0.126883E+10 |
Maximum of Months | 0.735928E+10 | 0.325244E+10 | 0.410684E+10 | 0.927520E+10 | 0.945288E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.768663E+10 | 0.448691E+10 | 0.319972E+10 | 0.504048E+10 | 0.133144E+11 |
February | 0.792689E+10 | 0.382228E+10 | 0.410461E+10 | 0.488028E+10 | 0.118302E+11 |
March | 0.107119E+11 | 0.601897E+10 | 0.469297E+10 | 0.887709E+10 | 0.966153E+10 |
April | 0.858500E+10 | 0.343059E+10 | 0.515441E+10 | 0.758842E+10 | 0.734736E+10 |
May | 0.776306E+10 | 0.225472E+10 | 0.550834E+10 | 0.771820E+10 | 0.506305E+10 |
June | 0.729986E+10 | 0.154688E+10 | 0.575299E+10 | 0.848221E+10 | 0.304083E+10 |
July | 0.770038E+10 | 0.186836E+10 | 0.583201E+10 | 0.102824E+11 | 0.214869E+10 |
August | 0.864494E+10 | 0.280291E+10 | 0.584203E+10 | 0.112972E+11 | 0.281419E+10 |
September | 0.972725E+10 | 0.473789E+10 | 0.498936E+10 | 0.114562E+11 | 0.435450E+10 |
October | 0.961779E+10 | 0.549387E+10 | 0.412392E+10 | 0.929760E+10 | 0.697425E+10 |
November | 0.666587E+10 | 0.376311E+10 | 0.290276E+10 | 0.542251E+10 | 0.890238E+10 |
December | 0.642755E+10 | 0.332655E+10 | 0.310100E+10 | 0.391748E+10 | 0.131647E+11 |
Annual Sum or Average | 0.987572E+11 | 0.435530E+11 | 0.552041E+11 | 0.942601E+11 | 0.886161E+11 |
Minimum of Months | 0.642755E+10 | 0.154688E+10 | 0.290276E+10 | 0.391748E+10 | 0.214869E+10 |
Maximum of Months | 0.107119E+11 | 0.601897E+10 | 0.584203E+10 | 0.114562E+11 | 0.133144E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187112E+10 | 0.439265E+09 | 0.143185E+10 | 0.317995E+09 | 0.101260E+11 |
February | 0.273909E+10 | 0.703967E+09 | 0.203513E+10 | 0.742040E+09 | 0.871441E+10 |
March | 0.475301E+10 | 0.203513E+10 | 0.271788E+10 | 0.304538E+10 | 0.681825E+10 |
April | 0.563169E+10 | 0.230922E+10 | 0.332247E+10 | 0.452503E+10 | 0.483893E+10 |
May | 0.686493E+10 | 0.310250E+10 | 0.376242E+10 | 0.687707E+10 | 0.335957E+10 |
June | 0.801556E+10 | 0.377019E+10 | 0.424537E+10 | 0.938600E+10 | 0.215086E+10 |
July | 0.740509E+10 | 0.324665E+10 | 0.415844E+10 | 0.948163E+10 | 0.156868E+10 |
August | 0.669746E+10 | 0.284783E+10 | 0.384964E+10 | 0.840331E+10 | 0.195434E+10 |
September | 0.508992E+10 | 0.219812E+10 | 0.289181E+10 | 0.555286E+10 | 0.288276E+10 |
October | 0.340952E+10 | 0.120103E+10 | 0.220849E+10 | 0.251865E+10 | 0.478846E+10 |
November | 0.195531E+10 | 0.563452E+09 | 0.139186E+10 | 0.879321E+09 | 0.625907E+10 |
December | 0.175159E+10 | 0.381651E+09 | 0.136994E+10 | 0.303385E+09 | 0.976686E+10 |
Annual Sum or Average | 0.561843E+11 | 0.227990E+11 | 0.333853E+11 | 0.520327E+11 | 0.632282E+11 |
Minimum of Months | 0.175159E+10 | 0.381651E+09 | 0.136994E+10 | 0.303385E+09 | 0.156868E+10 |
Maximum of Months | 0.801556E+10 | 0.377019E+10 | 0.424537E+10 | 0.948163E+10 | 0.101260E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.178758E+10 | 0.00 | 0.178758E+10 | 2260606.19 | 0.151782E+11 |
February | 0.246003E+10 | 0.00 | 0.246003E+10 | 15931333.44 | 0.131008E+11 |
March | 0.330296E+10 | 0.00 | 0.330296E+10 | 0.667174E+09 | 0.101314E+11 |
April | 0.407289E+10 | 16252441.88 | 0.405664E+10 | 0.157304E+10 | 0.650497E+10 |
May | 0.489025E+10 | 0.207374E+09 | 0.468287E+10 | 0.324880E+10 | 0.408490E+10 |
June | 0.569220E+10 | 0.484549E+09 | 0.520765E+10 | 0.568272E+10 | 0.252477E+10 |
July | 0.545628E+10 | 0.352215E+09 | 0.510406E+10 | 0.663916E+10 | 0.182020E+10 |
August | 0.472120E+10 | 71822758.33 | 0.464937E+10 | 0.538651E+10 | 0.239834E+10 |
September | 0.347703E+10 | 722376.53 | 0.347631E+10 | 0.293534E+10 | 0.369590E+10 |
October | 0.268587E+10 | 0.00 | 0.268587E+10 | 0.100862E+10 | 0.635157E+10 |
November | 0.174662E+10 | 0.00 | 0.174662E+10 | 0.250656E+09 | 0.850522E+10 |
December | 0.167312E+10 | 0.00 | 0.167312E+10 | 6612822.92 | 0.142719E+11 |
Annual Sum or Average | 0.419660E+11 | 0.113294E+10 | 0.408331E+11 | 0.274168E+11 | 0.885683E+11 |
Minimum of Months | 0.167312E+10 | 0.00 | 0.167312E+10 | 2260606.19 | 0.182020E+10 |
Maximum of Months | 0.569220E+10 | 0.484549E+09 | 0.520765E+10 | 0.663916E+10 | 0.151782E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.218084E+10 | 0.703223E+09 | 0.147761E+10 | 0.569131E+09 | 0.913242E+10 |
February | 0.289028E+10 | 0.867301E+09 | 0.202298E+10 | 0.959098E+09 | 0.791544E+10 |
March | 0.459184E+10 | 0.192303E+10 | 0.266881E+10 | 0.297685E+10 | 0.607597E+10 |
April | 0.588154E+10 | 0.259878E+10 | 0.328276E+10 | 0.479968E+10 | 0.407152E+10 |
May | 0.680908E+10 | 0.301202E+10 | 0.379706E+10 | 0.673571E+10 | 0.280718E+10 |
June | 0.735928E+10 | 0.325244E+10 | 0.410684E+10 | 0.843794E+10 | 0.173672E+10 |
July | 0.730241E+10 | 0.321515E+10 | 0.408726E+10 | 0.924161E+10 | 0.124219E+10 |
August | 0.659487E+10 | 0.276817E+10 | 0.382671E+10 | 0.810436E+10 | 0.162207E+10 |
September | 0.531105E+10 | 0.235578E+10 | 0.295527E+10 | 0.574792E+10 | 0.241316E+10 |
October | 0.372412E+10 | 0.154040E+10 | 0.218372E+10 | 0.296081E+10 | 0.398979E+10 |
November | 0.204424E+10 | 0.655770E+09 | 0.138847E+10 | 0.105443E+10 | 0.537588E+10 |
December | 0.170058E+10 | 0.351376E+09 | 0.134920E+10 | 0.280103E+09 | 0.896543E+10 |
Annual Sum or Average | 0.563901E+11 | 0.232434E+11 | 0.331467E+11 | 0.518676E+11 | 0.553478E+11 |
Minimum of Months | 0.170058E+10 | 0.351376E+09 | 0.134920E+10 | 0.280103E+09 | 0.124219E+10 |
Maximum of Months | 0.735928E+10 | 0.325244E+10 | 0.410684E+10 | 0.924161E+10 | 0.913242E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.768663E+10 | 0.448691E+10 | 0.319972E+10 | 0.514426E+10 | 0.127279E+11 |
February | 0.792689E+10 | 0.382228E+10 | 0.410461E+10 | 0.496408E+10 | 0.113307E+11 |
March | 0.107119E+11 | 0.601897E+10 | 0.469297E+10 | 0.902649E+10 | 0.895013E+10 |
April | 0.858500E+10 | 0.343059E+10 | 0.515441E+10 | 0.772385E+10 | 0.674830E+10 |
May | 0.776306E+10 | 0.225472E+10 | 0.550834E+10 | 0.779543E+10 | 0.465231E+10 |
June | 0.729986E+10 | 0.154688E+10 | 0.575299E+10 | 0.849457E+10 | 0.284490E+10 |
July | 0.770038E+10 | 0.186836E+10 | 0.583201E+10 | 0.102720E+11 | 0.203215E+10 |
August | 0.864494E+10 | 0.280291E+10 | 0.584203E+10 | 0.113053E+11 | 0.262897E+10 |
September | 0.972725E+10 | 0.473789E+10 | 0.498936E+10 | 0.115360E+11 | 0.395991E+10 |
October | 0.961779E+10 | 0.549387E+10 | 0.412392E+10 | 0.951121E+10 | 0.618574E+10 |
November | 0.666587E+10 | 0.376311E+10 | 0.290276E+10 | 0.560808E+10 | 0.797575E+10 |
December | 0.642755E+10 | 0.332655E+10 | 0.310100E+10 | 0.401788E+10 | 0.124832E+11 |
Annual Sum or Average | 0.987572E+11 | 0.435530E+11 | 0.552041E+11 | 0.953992E+11 | 0.825200E+11 |
Minimum of Months | 0.642755E+10 | 0.154688E+10 | 0.290276E+10 | 0.401788E+10 | 0.203215E+10 |
Maximum of Months | 0.107119E+11 | 0.601897E+10 | 0.584203E+10 | 0.115360E+11 | 0.127279E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187112E+10 | 0.439265E+09 | 0.143185E+10 | 0.326154E+09 | 0.979508E+10 |
February | 0.273909E+10 | 0.703967E+09 | 0.203513E+10 | 0.744554E+09 | 0.843309E+10 |
March | 0.475301E+10 | 0.203513E+10 | 0.271788E+10 | 0.307088E+10 | 0.642037E+10 |
April | 0.563169E+10 | 0.230922E+10 | 0.332247E+10 | 0.455027E+10 | 0.451007E+10 |
May | 0.686493E+10 | 0.310250E+10 | 0.376242E+10 | 0.686761E+10 | 0.315006E+10 |
June | 0.801556E+10 | 0.377019E+10 | 0.424537E+10 | 0.933148E+10 | 0.205728E+10 |
July | 0.740509E+10 | 0.324665E+10 | 0.415844E+10 | 0.942406E+10 | 0.151678E+10 |
August | 0.669746E+10 | 0.284783E+10 | 0.384964E+10 | 0.837462E+10 | 0.186827E+10 |
September | 0.508992E+10 | 0.219812E+10 | 0.289181E+10 | 0.556750E+10 | 0.268263E+10 |
October | 0.340952E+10 | 0.120103E+10 | 0.220849E+10 | 0.258090E+10 | 0.435984E+10 |
November | 0.195531E+10 | 0.563452E+09 | 0.139186E+10 | 0.918991E+09 | 0.573735E+10 |
December | 0.175159E+10 | 0.381651E+09 | 0.136994E+10 | 0.311092E+09 | 0.938421E+10 |
Annual Sum or Average | 0.561843E+11 | 0.227990E+11 | 0.333853E+11 | 0.520681E+11 | 0.599150E+11 |
Minimum of Months | 0.175159E+10 | 0.381651E+09 | 0.136994E+10 | 0.311092E+09 | 0.151678E+10 |
Maximum of Months | 0.801556E+10 | 0.377019E+10 | 0.424537E+10 | 0.942406E+10 | 0.979508E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 6243.63 | 667.41 | 0.00 | 667.41 | 0.00 | 0.00 |
February | 1.78 | 5927.20 | 1016.88 | 0.00 | 1016.88 | 0.00 | 0.00 |
March | 194.87 | 4360.06 | 1233.19 | 0.00 | 1233.19 | 0.00 | 0.00 |
April | 463.73 | 3062.09 | 1571.34 | 6.27 | 1565.07 | 0.00 | 0.00 |
May | 1073.88 | 1828.85 | 1825.82 | 77.42 | 1748.39 | 0.00 | 0.00 |
June | 2089.16 | 1129.68 | 2196.07 | 186.94 | 2009.13 | 0.00 | 0.00 |
July | 2394.92 | 780.59 | 2037.15 | 131.50 | 1905.65 | 0.00 | 0.00 |
August | 1913.48 | 1065.14 | 1762.70 | 26.82 | 1735.88 | 0.00 | 0.00 |
September | 1001.20 | 1782.45 | 1341.45 | 0.28 | 1341.17 | 0.00 | 0.00 |
October | 247.62 | 3022.21 | 1002.79 | 0.00 | 1002.79 | 0.00 | 0.00 |
November | 46.97 | 4109.13 | 673.85 | 0.00 | 673.85 | 0.00 | 0.00 |
December | 0.53 | 6057.36 | 624.68 | 0.00 | 624.68 | 0.00 | 0.00 |
Annual Sum or Average | 790.87 | 3267.28 | 1330.74 | 35.93 | 1294.81 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 780.59 | 624.68 | 0.00 | 624.68 | 0.00 | 0.00 |
Maximum of Months | 2394.92 | 6243.63 | 2196.07 | 186.94 | 2009.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 196.26 | 3755.18 | 814.23 | 262.55 | 551.68 | 0.00 | 0.00 |
February | 373.25 | 3555.83 | 1194.73 | 358.51 | 836.22 | 0.00 | 0.00 |
March | 1071.53 | 2555.10 | 1714.40 | 717.98 | 996.42 | 0.00 | 0.00 |
April | 1806.81 | 1803.84 | 2269.12 | 1002.62 | 1266.50 | 0.00 | 0.00 |
May | 2519.29 | 1170.80 | 2542.23 | 1124.56 | 1417.66 | 0.00 | 0.00 |
June | 3293.71 | 725.80 | 2839.24 | 1254.81 | 1584.44 | 0.00 | 0.00 |
July | 3503.96 | 474.16 | 2726.42 | 1200.40 | 1526.01 | 0.00 | 0.00 |
August | 3062.69 | 631.88 | 2462.25 | 1033.52 | 1428.73 | 0.00 | 0.00 |
September | 2206.20 | 1072.91 | 2049.02 | 908.87 | 1140.16 | 0.00 | 0.00 |
October | 1030.23 | 1806.47 | 1390.43 | 575.12 | 815.31 | 0.00 | 0.00 |
November | 354.53 | 2504.10 | 788.68 | 253.00 | 535.68 | 0.00 | 0.00 |
December | 87.77 | 3745.20 | 634.93 | 131.19 | 503.74 | 0.00 | 0.00 |
Annual Sum or Average | 1632.64 | 1975.52 | 1788.13 | 737.05 | 1051.08 | 0.00 | 0.00 |
Minimum of Months | 87.77 | 474.16 | 634.93 | 131.19 | 503.74 | 0.00 | 0.00 |
Maximum of Months | 3503.96 | 3755.18 | 2839.24 | 1254.81 | 1584.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1897.79 | 5094.71 | 2869.87 | 1675.23 | 1194.64 | 0.00 | 0.00 |
February | 2053.52 | 4952.96 | 3276.67 | 1579.98 | 1696.69 | 0.00 | 0.00 |
March | 3365.28 | 3683.52 | 3999.39 | 2247.23 | 1752.16 | 0.00 | 0.00 |
April | 2950.49 | 2928.20 | 3312.13 | 1323.54 | 1988.59 | 0.00 | 0.00 |
May | 2919.01 | 1931.81 | 2898.41 | 841.82 | 2056.59 | 0.00 | 0.00 |
June | 3294.63 | 1219.37 | 2816.32 | 596.79 | 2219.52 | 0.00 | 0.00 |
July | 3856.16 | 827.98 | 2875.00 | 697.57 | 2177.43 | 0.00 | 0.00 |
August | 4237.88 | 1083.22 | 3227.66 | 1046.49 | 2181.17 | 0.00 | 0.00 |
September | 4461.89 | 1727.43 | 3752.81 | 1827.90 | 1924.91 | 0.00 | 0.00 |
October | 3511.29 | 2676.65 | 3590.88 | 2051.18 | 1539.70 | 0.00 | 0.00 |
November | 2103.42 | 3554.82 | 2571.72 | 1451.82 | 1119.90 | 0.00 | 0.00 |
December | 1461.67 | 5091.73 | 2399.78 | 1241.99 | 1157.78 | 0.00 | 0.00 |
Annual Sum or Average | 3015.16 | 2886.73 | 3131.58 | 1381.06 | 1750.52 | 0.00 | 0.00 |
Minimum of Months | 1461.67 | 827.98 | 2399.78 | 596.79 | 1119.90 | 0.00 | 0.00 |
Maximum of Months | 4461.89 | 5094.71 | 3999.39 | 2247.23 | 2219.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 111.76 | 4089.03 | 698.60 | 164.00 | 534.59 | 0.00 | 0.00 |
February | 301.16 | 3882.06 | 1132.24 | 290.99 | 841.24 | 0.00 | 0.00 |
March | 1095.89 | 2842.40 | 1774.58 | 759.83 | 1014.74 | 0.00 | 0.00 |
April | 1669.19 | 2160.86 | 2172.73 | 890.91 | 1281.82 | 0.00 | 0.00 |
May | 2543.29 | 1363.28 | 2563.08 | 1158.35 | 1404.73 | 0.00 | 0.00 |
June | 3597.53 | 915.88 | 3092.44 | 1454.55 | 1637.88 | 0.00 | 0.00 |
July | 3479.88 | 679.99 | 2764.75 | 1212.16 | 1552.59 | 0.00 | 0.00 |
August | 3057.93 | 874.80 | 2500.56 | 1063.26 | 1437.30 | 0.00 | 0.00 |
September | 2099.52 | 1249.27 | 1963.71 | 848.04 | 1115.67 | 0.00 | 0.00 |
October | 889.07 | 2032.47 | 1272.97 | 448.41 | 824.56 | 0.00 | 0.00 |
November | 303.97 | 2793.32 | 754.37 | 217.38 | 536.99 | 0.00 | 0.00 |
December | 99.97 | 4117.54 | 653.97 | 142.49 | 511.48 | 0.00 | 0.00 |
Annual Sum or Average | 1611.37 | 2241.81 | 1781.60 | 722.95 | 1058.65 | 0.00 | 0.00 |
Minimum of Months | 99.97 | 679.99 | 653.97 | 142.49 | 511.48 | 0.00 | 0.00 |
Maximum of Months | 3597.53 | 4117.54 | 3092.44 | 1454.55 | 1637.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 5867.28 | 667.41 | 0.00 | 667.41 | 0.00 | 0.00 |
February | 3.56 | 5614.74 | 1016.88 | 0.00 | 1016.88 | 0.00 | 0.00 |
March | 228.04 | 4026.18 | 1233.19 | 0.00 | 1233.19 | 0.00 | 0.00 |
April | 560.32 | 2736.86 | 1571.33 | 6.27 | 1565.06 | 0.00 | 0.00 |
May | 1159.69 | 1671.19 | 1825.81 | 77.42 | 1748.38 | 0.00 | 0.00 |
June | 2159.26 | 1041.33 | 2196.06 | 186.94 | 2009.12 | 0.00 | 0.00 |
July | 2462.51 | 717.29 | 2037.14 | 131.50 | 1905.64 | 0.00 | 0.00 |
August | 1984.04 | 962.62 | 1762.69 | 26.82 | 1735.88 | 0.00 | 0.00 |
September | 1079.16 | 1585.43 | 1341.45 | 0.28 | 1341.17 | 0.00 | 0.00 |
October | 319.67 | 2674.40 | 1002.79 | 0.00 | 1002.79 | 0.00 | 0.00 |
November | 72.92 | 3642.38 | 673.85 | 0.00 | 673.85 | 0.00 | 0.00 |
December | 1.34 | 5573.44 | 624.67 | 0.00 | 624.67 | 0.00 | 0.00 |
Annual Sum or Average | 841.27 | 2996.32 | 1330.73 | 35.93 | 1294.81 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 717.29 | 624.67 | 0.00 | 624.67 | 0.00 | 0.00 |
Maximum of Months | 2462.51 | 5867.28 | 2196.06 | 186.94 | 2009.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 202.92 | 3529.30 | 814.23 | 262.55 | 551.68 | 0.00 | 0.00 |
February | 382.06 | 3392.98 | 1194.72 | 358.51 | 836.22 | 0.00 | 0.00 |
March | 1072.31 | 2434.65 | 1714.40 | 717.98 | 996.42 | 0.00 | 0.00 |
April | 1797.99 | 1707.38 | 2269.11 | 1002.62 | 1266.50 | 0.00 | 0.00 |
May | 2487.40 | 1122.90 | 2542.22 | 1124.56 | 1417.66 | 0.00 | 0.00 |
June | 3258.57 | 695.64 | 2839.23 | 1254.80 | 1584.43 | 0.00 | 0.00 |
July | 3462.96 | 473.73 | 2726.41 | 1200.40 | 1526.01 | 0.00 | 0.00 |
August | 3028.44 | 629.78 | 2462.24 | 1033.52 | 1428.73 | 0.00 | 0.00 |
September | 2190.24 | 1009.48 | 2049.01 | 908.86 | 1140.15 | 0.00 | 0.00 |
October | 1038.09 | 1681.17 | 1390.43 | 575.12 | 815.31 | 0.00 | 0.00 |
November | 370.09 | 2318.04 | 788.67 | 253.00 | 535.68 | 0.00 | 0.00 |
December | 97.12 | 3493.50 | 634.92 | 131.19 | 503.73 | 0.00 | 0.00 |
Annual Sum or Average | 1622.66 | 1866.40 | 1788.12 | 737.04 | 1051.07 | 0.00 | 0.00 |
Minimum of Months | 97.12 | 473.73 | 634.92 | 131.19 | 503.73 | 0.00 | 0.00 |
Maximum of Months | 3462.96 | 3529.30 | 2839.23 | 1254.80 | 1584.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1881.90 | 4971.02 | 2869.86 | 1675.22 | 1194.64 | 0.00 | 0.00 |
February | 2017.31 | 4890.15 | 3276.66 | 1579.98 | 1696.68 | 0.00 | 0.00 |
March | 3314.33 | 3607.20 | 3999.38 | 2247.23 | 1752.15 | 0.00 | 0.00 |
April | 2927.63 | 2834.63 | 3312.12 | 1323.53 | 1988.58 | 0.00 | 0.00 |
May | 2881.65 | 1890.33 | 2898.40 | 841.82 | 2056.58 | 0.00 | 0.00 |
June | 3272.46 | 1173.16 | 2816.31 | 596.79 | 2219.52 | 0.00 | 0.00 |
July | 3839.01 | 802.23 | 2874.99 | 697.57 | 2177.42 | 0.00 | 0.00 |
August | 4217.90 | 1050.70 | 3227.65 | 1046.49 | 2181.17 | 0.00 | 0.00 |
September | 4419.83 | 1679.98 | 3752.80 | 1827.89 | 1924.91 | 0.00 | 0.00 |
October | 3471.33 | 2603.89 | 3590.87 | 2051.18 | 1539.70 | 0.00 | 0.00 |
November | 2092.02 | 3434.56 | 2571.71 | 1451.82 | 1119.89 | 0.00 | 0.00 |
December | 1462.62 | 4915.12 | 2399.77 | 1241.99 | 1157.78 | 0.00 | 0.00 |
Annual Sum or Average | 2988.97 | 2810.00 | 3131.57 | 1381.06 | 1750.51 | 0.00 | 0.00 |
Minimum of Months | 1462.62 | 802.23 | 2399.77 | 596.79 | 1119.89 | 0.00 | 0.00 |
Maximum of Months | 4419.83 | 4971.02 | 3999.38 | 2247.23 | 2219.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 118.73 | 3780.61 | 698.60 | 164.00 | 534.59 | 0.00 | 0.00 |
February | 306.73 | 3602.19 | 1132.23 | 290.99 | 841.24 | 0.00 | 0.00 |
March | 1137.02 | 2545.64 | 1774.57 | 759.83 | 1014.74 | 0.00 | 0.00 |
April | 1745.77 | 1866.87 | 2172.72 | 890.90 | 1281.82 | 0.00 | 0.00 |
May | 2567.60 | 1254.32 | 2563.07 | 1158.34 | 1404.73 | 0.00 | 0.00 |
June | 3621.14 | 829.81 | 3092.42 | 1454.55 | 1637.87 | 0.00 | 0.00 |
July | 3540.03 | 585.68 | 2764.74 | 1212.16 | 1552.58 | 0.00 | 0.00 |
August | 3137.44 | 729.67 | 2500.55 | 1063.26 | 1437.29 | 0.00 | 0.00 |
September | 2142.31 | 1112.18 | 1963.70 | 848.04 | 1115.67 | 0.00 | 0.00 |
October | 940.35 | 1787.81 | 1272.97 | 448.41 | 824.56 | 0.00 | 0.00 |
November | 339.24 | 2414.76 | 754.37 | 217.38 | 536.98 | 0.00 | 0.00 |
December | 113.27 | 3646.53 | 653.97 | 142.49 | 511.48 | 0.00 | 0.00 |
Annual Sum or Average | 1649.94 | 2004.95 | 1781.59 | 722.95 | 1058.64 | 0.00 | 0.00 |
Minimum of Months | 113.27 | 585.68 | 653.97 | 142.49 | 511.48 | 0.00 | 0.00 |
Maximum of Months | 3621.14 | 3780.61 | 3092.42 | 1454.55 | 1637.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.84 | 5666.90 | 667.41 | 0.00 | 667.41 | 0.00 | 0.00 |
February | 6.59 | 5415.36 | 1016.88 | 0.00 | 1016.88 | 0.00 | 0.00 |
March | 249.09 | 3782.62 | 1233.19 | 0.00 | 1233.19 | 0.00 | 0.00 |
April | 606.88 | 2509.64 | 1571.33 | 6.27 | 1565.06 | 0.00 | 0.00 |
May | 1212.96 | 1525.13 | 1825.81 | 77.42 | 1748.38 | 0.00 | 0.00 |
June | 2192.41 | 974.06 | 2196.06 | 186.94 | 2009.12 | 0.00 | 0.00 |
July | 2478.78 | 679.59 | 2037.14 | 131.50 | 1905.64 | 0.00 | 0.00 |
August | 2011.09 | 895.44 | 1762.69 | 26.82 | 1735.88 | 0.00 | 0.00 |
September | 1132.46 | 1425.89 | 1341.45 | 0.28 | 1341.17 | 0.00 | 0.00 |
October | 376.58 | 2371.41 | 1002.79 | 0.00 | 1002.79 | 0.00 | 0.00 |
November | 96.70 | 3281.34 | 673.85 | 0.00 | 673.85 | 0.00 | 0.00 |
December | 2.47 | 5328.52 | 624.67 | 0.00 | 624.67 | 0.00 | 0.00 |
Annual Sum or Average | 869.38 | 2808.48 | 1330.73 | 35.93 | 1294.81 | 0.00 | 0.00 |
Minimum of Months | 0.84 | 679.59 | 624.67 | 0.00 | 624.67 | 0.00 | 0.00 |
Maximum of Months | 2478.78 | 5666.90 | 2196.06 | 186.94 | 2009.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 212.49 | 3409.66 | 814.23 | 262.55 | 551.68 | 0.00 | 0.00 |
February | 396.45 | 3271.92 | 1194.72 | 358.51 | 836.22 | 0.00 | 0.00 |
March | 1111.43 | 2268.51 | 1714.40 | 717.98 | 996.42 | 0.00 | 0.00 |
April | 1851.73 | 1570.80 | 2269.11 | 1002.62 | 1266.50 | 0.00 | 0.00 |
May | 2514.83 | 1048.08 | 2542.22 | 1124.56 | 1417.66 | 0.00 | 0.00 |
June | 3255.38 | 670.03 | 2839.23 | 1254.80 | 1584.43 | 0.00 | 0.00 |
July | 3450.42 | 463.78 | 2726.41 | 1200.40 | 1526.01 | 0.00 | 0.00 |
August | 3025.82 | 605.61 | 2462.24 | 1033.52 | 1428.73 | 0.00 | 0.00 |
September | 2217.56 | 931.00 | 2049.01 | 908.86 | 1140.15 | 0.00 | 0.00 |
October | 1105.44 | 1489.62 | 1390.43 | 575.12 | 815.31 | 0.00 | 0.00 |
November | 406.80 | 2074.03 | 788.67 | 253.00 | 535.68 | 0.00 | 0.00 |
December | 104.58 | 3347.31 | 634.92 | 131.19 | 503.73 | 0.00 | 0.00 |
Annual Sum or Average | 1644.71 | 1755.07 | 1788.12 | 737.04 | 1051.07 | 0.00 | 0.00 |
Minimum of Months | 104.58 | 463.78 | 634.92 | 131.19 | 503.73 | 0.00 | 0.00 |
Maximum of Months | 3450.42 | 3409.66 | 2839.23 | 1254.80 | 1584.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1920.65 | 4752.06 | 2869.86 | 1675.22 | 1194.64 | 0.00 | 0.00 |
February | 2051.95 | 4683.66 | 3276.66 | 1579.98 | 1696.68 | 0.00 | 0.00 |
March | 3370.11 | 3341.60 | 3999.38 | 2247.23 | 1752.15 | 0.00 | 0.00 |
April | 2979.88 | 2603.51 | 3312.12 | 1323.53 | 1988.58 | 0.00 | 0.00 |
May | 2910.48 | 1736.97 | 2898.40 | 841.82 | 2056.58 | 0.00 | 0.00 |
June | 3277.23 | 1097.57 | 2816.31 | 596.79 | 2219.52 | 0.00 | 0.00 |
July | 3835.11 | 758.72 | 2874.99 | 697.57 | 2177.42 | 0.00 | 0.00 |
August | 4220.93 | 981.55 | 3227.65 | 1046.49 | 2181.17 | 0.00 | 0.00 |
September | 4450.62 | 1527.74 | 3752.80 | 1827.89 | 1924.91 | 0.00 | 0.00 |
October | 3551.08 | 2309.49 | 3590.87 | 2051.18 | 1539.70 | 0.00 | 0.00 |
November | 2163.61 | 3077.06 | 2571.71 | 1451.82 | 1119.89 | 0.00 | 0.00 |
December | 1500.11 | 4660.68 | 2399.77 | 1241.99 | 1157.78 | 0.00 | 0.00 |
Annual Sum or Average | 3025.09 | 2616.69 | 3131.57 | 1381.06 | 1750.51 | 0.00 | 0.00 |
Minimum of Months | 1500.11 | 758.72 | 2399.77 | 596.79 | 1119.89 | 0.00 | 0.00 |
Maximum of Months | 4450.62 | 4752.06 | 3999.38 | 2247.23 | 2219.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 121.77 | 3657.06 | 698.60 | 164.00 | 534.59 | 0.00 | 0.00 |
February | 307.77 | 3485.90 | 1132.23 | 290.99 | 841.24 | 0.00 | 0.00 |
March | 1146.53 | 2397.09 | 1774.57 | 759.83 | 1014.74 | 0.00 | 0.00 |
April | 1755.51 | 1740.00 | 2172.72 | 890.90 | 1281.82 | 0.00 | 0.00 |
May | 2564.07 | 1176.10 | 2563.07 | 1158.34 | 1404.73 | 0.00 | 0.00 |
June | 3600.11 | 793.70 | 3092.42 | 1454.55 | 1637.87 | 0.00 | 0.00 |
July | 3518.54 | 566.30 | 2764.74 | 1212.16 | 1552.58 | 0.00 | 0.00 |
August | 3126.73 | 697.53 | 2500.55 | 1063.26 | 1437.29 | 0.00 | 0.00 |
September | 2147.95 | 1034.97 | 1963.70 | 848.04 | 1115.67 | 0.00 | 0.00 |
October | 963.60 | 1627.78 | 1272.97 | 448.41 | 824.56 | 0.00 | 0.00 |
November | 354.55 | 2213.48 | 754.37 | 217.38 | 536.98 | 0.00 | 0.00 |
December | 116.15 | 3503.66 | 653.97 | 142.49 | 511.48 | 0.00 | 0.00 |
Annual Sum or Average | 1651.07 | 1899.89 | 1781.59 | 722.95 | 1058.64 | 0.00 | 0.00 |
Minimum of Months | 116.15 | 566.30 | 653.97 | 142.49 | 511.48 | 0.00 | 0.00 |
Maximum of Months | 3600.11 | 3657.06 | 3092.42 | 1454.55 | 1637.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.167229E+11 | 0.178759E+10 | 0.00 | 0.178759E+10 | 0.00 | 0.00 |
February | 4297838.62 | 0.143391E+11 | 0.246004E+10 | 0.00 | 0.246004E+10 | 0.00 | 0.00 |
March | 0.521951E+09 | 0.116780E+11 | 0.330298E+10 | 0.00 | 0.330298E+10 | 0.00 | 0.00 |
April | 0.120199E+10 | 0.793694E+10 | 0.407290E+10 | 16252499.60 | 0.405665E+10 | 0.00 | 0.00 |
May | 0.287627E+10 | 0.489839E+10 | 0.489026E+10 | 0.207375E+09 | 0.468289E+10 | 0.00 | 0.00 |
June | 0.541511E+10 | 0.292814E+10 | 0.569222E+10 | 0.484551E+09 | 0.520767E+10 | 0.00 | 0.00 |
July | 0.641455E+10 | 0.209072E+10 | 0.545630E+10 | 0.352216E+09 | 0.510408E+10 | 0.00 | 0.00 |
August | 0.512506E+10 | 0.285288E+10 | 0.472121E+10 | 71823013.38 | 0.464939E+10 | 0.00 | 0.00 |
September | 0.259511E+10 | 0.462011E+10 | 0.347704E+10 | 722379.10 | 0.347632E+10 | 0.00 | 0.00 |
October | 0.663220E+09 | 0.809468E+10 | 0.268588E+10 | 0.00 | 0.268588E+10 | 0.00 | 0.00 |
November | 0.121757E+09 | 0.106509E+11 | 0.174662E+10 | 0.00 | 0.174662E+10 | 0.00 | 0.00 |
December | 1407450.01 | 0.162240E+11 | 0.167313E+10 | 0.00 | 0.167313E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.249407E+11 | 0.103037E+12 | 0.419662E+11 | 0.113294E+10 | 0.408332E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.209072E+10 | 0.167313E+10 | 0.00 | 0.167313E+10 | 0.00 | 0.00 |
Maximum of Months | 0.641455E+10 | 0.167229E+11 | 0.569222E+10 | 0.484551E+09 | 0.520767E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.525671E+09 | 0.100579E+11 | 0.218084E+10 | 0.703226E+09 | 0.147762E+10 | 0.00 | 0.00 |
February | 0.902954E+09 | 0.860226E+10 | 0.289029E+10 | 0.867305E+09 | 0.202298E+10 | 0.00 | 0.00 |
March | 0.286998E+10 | 0.684359E+10 | 0.459186E+10 | 0.192304E+10 | 0.266882E+10 | 0.00 | 0.00 |
April | 0.468326E+10 | 0.467554E+10 | 0.588156E+10 | 0.259879E+10 | 0.328277E+10 | 0.00 | 0.00 |
May | 0.674766E+10 | 0.313586E+10 | 0.680911E+10 | 0.301203E+10 | 0.379707E+10 | 0.00 | 0.00 |
June | 0.853730E+10 | 0.188127E+10 | 0.735931E+10 | 0.325246E+10 | 0.410686E+10 | 0.00 | 0.00 |
July | 0.938501E+10 | 0.127000E+10 | 0.730244E+10 | 0.321516E+10 | 0.408727E+10 | 0.00 | 0.00 |
August | 0.820310E+10 | 0.169242E+10 | 0.659490E+10 | 0.276818E+10 | 0.382672E+10 | 0.00 | 0.00 |
September | 0.571846E+10 | 0.278098E+10 | 0.531107E+10 | 0.235579E+10 | 0.295528E+10 | 0.00 | 0.00 |
October | 0.275937E+10 | 0.483844E+10 | 0.372413E+10 | 0.154040E+10 | 0.218373E+10 | 0.00 | 0.00 |
November | 0.918939E+09 | 0.649062E+10 | 0.204425E+10 | 0.655773E+09 | 0.138848E+10 | 0.00 | 0.00 |
December | 0.235082E+09 | 0.100311E+11 | 0.170059E+10 | 0.351378E+09 | 0.134921E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.514868E+11 | 0.623000E+11 | 0.563904E+11 | 0.232435E+11 | 0.331468E+11 | 0.00 | 0.00 |
Minimum of Months | 0.235082E+09 | 0.127000E+10 | 0.170059E+10 | 0.351378E+09 | 0.134921E+10 | 0.00 | 0.00 |
Maximum of Months | 0.938501E+10 | 0.100579E+11 | 0.735931E+10 | 0.325246E+10 | 0.410686E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.508303E+10 | 0.136457E+11 | 0.768666E+10 | 0.448693E+10 | 0.319973E+10 | 0.00 | 0.00 |
February | 0.496788E+10 | 0.119822E+11 | 0.792692E+10 | 0.382229E+10 | 0.410463E+10 | 0.00 | 0.00 |
March | 0.901357E+10 | 0.986594E+10 | 0.107120E+11 | 0.601899E+10 | 0.469298E+10 | 0.00 | 0.00 |
April | 0.764767E+10 | 0.758990E+10 | 0.858503E+10 | 0.343061E+10 | 0.515443E+10 | 0.00 | 0.00 |
May | 0.781826E+10 | 0.517417E+10 | 0.776309E+10 | 0.225473E+10 | 0.550836E+10 | 0.00 | 0.00 |
June | 0.853969E+10 | 0.316061E+10 | 0.729989E+10 | 0.154688E+10 | 0.575301E+10 | 0.00 | 0.00 |
July | 0.103283E+11 | 0.221767E+10 | 0.770040E+10 | 0.186837E+10 | 0.583203E+10 | 0.00 | 0.00 |
August | 0.113507E+11 | 0.290131E+10 | 0.864497E+10 | 0.280292E+10 | 0.584205E+10 | 0.00 | 0.00 |
September | 0.115652E+11 | 0.447750E+10 | 0.972729E+10 | 0.473791E+10 | 0.498938E+10 | 0.00 | 0.00 |
October | 0.940463E+10 | 0.716913E+10 | 0.961783E+10 | 0.549389E+10 | 0.412394E+10 | 0.00 | 0.00 |
November | 0.545206E+10 | 0.921410E+10 | 0.666589E+10 | 0.376312E+10 | 0.290277E+10 | 0.00 | 0.00 |
December | 0.391494E+10 | 0.136377E+11 | 0.642757E+10 | 0.332656E+10 | 0.310101E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.950860E+11 | 0.910359E+11 | 0.987575E+11 | 0.435532E+11 | 0.552043E+11 | 0.00 | 0.00 |
Minimum of Months | 0.391494E+10 | 0.221767E+10 | 0.642757E+10 | 0.154688E+10 | 0.290277E+10 | 0.00 | 0.00 |
Maximum of Months | 0.115652E+11 | 0.136457E+11 | 0.107120E+11 | 0.601899E+10 | 0.584205E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.299327E+09 | 0.109521E+11 | 0.187113E+10 | 0.439267E+09 | 0.143186E+10 | 0.00 | 0.00 |
February | 0.728558E+09 | 0.939149E+10 | 0.273910E+10 | 0.703970E+09 | 0.203513E+10 | 0.00 | 0.00 |
March | 0.293522E+10 | 0.761309E+10 | 0.475303E+10 | 0.203514E+10 | 0.271789E+10 | 0.00 | 0.00 |
April | 0.432653E+10 | 0.560096E+10 | 0.563172E+10 | 0.230923E+10 | 0.332249E+10 | 0.00 | 0.00 |
May | 0.681193E+10 | 0.365141E+10 | 0.686496E+10 | 0.310252E+10 | 0.376244E+10 | 0.00 | 0.00 |
June | 0.932480E+10 | 0.237395E+10 | 0.801559E+10 | 0.377020E+10 | 0.424539E+10 | 0.00 | 0.00 |
July | 0.932051E+10 | 0.182127E+10 | 0.740512E+10 | 0.324666E+10 | 0.415846E+10 | 0.00 | 0.00 |
August | 0.819035E+10 | 0.234305E+10 | 0.669749E+10 | 0.284784E+10 | 0.384965E+10 | 0.00 | 0.00 |
September | 0.544196E+10 | 0.323810E+10 | 0.508994E+10 | 0.219812E+10 | 0.289182E+10 | 0.00 | 0.00 |
October | 0.238128E+10 | 0.544377E+10 | 0.340953E+10 | 0.120103E+10 | 0.220850E+10 | 0.00 | 0.00 |
November | 0.787884E+09 | 0.724030E+10 | 0.195532E+10 | 0.563454E+09 | 0.139187E+10 | 0.00 | 0.00 |
December | 0.267749E+09 | 0.110284E+11 | 0.175159E+10 | 0.381653E+09 | 0.136994E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.508161E+11 | 0.706979E+11 | 0.561845E+11 | 0.227991E+11 | 0.333854E+11 | 0.00 | 0.00 |
Minimum of Months | 0.267749E+09 | 0.182127E+10 | 0.175159E+10 | 0.381653E+09 | 0.136994E+10 | 0.00 | 0.00 |
Maximum of Months | 0.932480E+10 | 0.110284E+11 | 0.801559E+10 | 0.377020E+10 | 0.424539E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.157149E+11 | 0.178758E+10 | 0.00 | 0.178758E+10 | 0.00 | 0.00 |
February | 8611162.58 | 0.135832E+11 | 0.246003E+10 | 0.00 | 0.246003E+10 | 0.00 | 0.00 |
March | 0.610789E+09 | 0.107837E+11 | 0.330296E+10 | 0.00 | 0.330296E+10 | 0.00 | 0.00 |
April | 0.145235E+10 | 0.709394E+10 | 0.407289E+10 | 16252441.88 | 0.405664E+10 | 0.00 | 0.00 |
May | 0.310611E+10 | 0.447611E+10 | 0.489025E+10 | 0.207374E+09 | 0.468287E+10 | 0.00 | 0.00 |
June | 0.559679E+10 | 0.269913E+10 | 0.569220E+10 | 0.484549E+09 | 0.520765E+10 | 0.00 | 0.00 |
July | 0.659560E+10 | 0.192120E+10 | 0.545628E+10 | 0.352215E+09 | 0.510406E+10 | 0.00 | 0.00 |
August | 0.531406E+10 | 0.257827E+10 | 0.472120E+10 | 71822758.33 | 0.464937E+10 | 0.00 | 0.00 |
September | 0.279717E+10 | 0.410944E+10 | 0.347703E+10 | 722376.53 | 0.347631E+10 | 0.00 | 0.00 |
October | 0.856193E+09 | 0.716310E+10 | 0.268587E+10 | 0.00 | 0.268587E+10 | 0.00 | 0.00 |
November | 0.189003E+09 | 0.944105E+10 | 0.174662E+10 | 0.00 | 0.174662E+10 | 0.00 | 0.00 |
December | 3601448.41 | 0.149279E+11 | 0.167312E+10 | 0.00 | 0.167312E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.265303E+11 | 0.944920E+11 | 0.419660E+11 | 0.113294E+10 | 0.408331E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.192120E+10 | 0.167312E+10 | 0.00 | 0.167312E+10 | 0.00 | 0.00 |
Maximum of Months | 0.659560E+10 | 0.157149E+11 | 0.569220E+10 | 0.484549E+09 | 0.520765E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.543502E+09 | 0.945288E+10 | 0.218084E+10 | 0.703223E+09 | 0.147761E+10 | 0.00 | 0.00 |
February | 0.924270E+09 | 0.820831E+10 | 0.289028E+10 | 0.867301E+09 | 0.202298E+10 | 0.00 | 0.00 |
March | 0.287208E+10 | 0.652098E+10 | 0.459184E+10 | 0.192303E+10 | 0.266881E+10 | 0.00 | 0.00 |
April | 0.466040E+10 | 0.442552E+10 | 0.588154E+10 | 0.259878E+10 | 0.328276E+10 | 0.00 | 0.00 |
May | 0.666226E+10 | 0.300757E+10 | 0.680908E+10 | 0.301202E+10 | 0.379706E+10 | 0.00 | 0.00 |
June | 0.844621E+10 | 0.180309E+10 | 0.735928E+10 | 0.325244E+10 | 0.410684E+10 | 0.00 | 0.00 |
July | 0.927520E+10 | 0.126883E+10 | 0.730241E+10 | 0.321515E+10 | 0.408726E+10 | 0.00 | 0.00 |
August | 0.811136E+10 | 0.168681E+10 | 0.659487E+10 | 0.276817E+10 | 0.382671E+10 | 0.00 | 0.00 |
September | 0.567710E+10 | 0.261657E+10 | 0.531105E+10 | 0.235578E+10 | 0.295527E+10 | 0.00 | 0.00 |
October | 0.278042E+10 | 0.450286E+10 | 0.372412E+10 | 0.154040E+10 | 0.218372E+10 | 0.00 | 0.00 |
November | 0.959277E+09 | 0.600836E+10 | 0.204424E+10 | 0.655770E+09 | 0.138847E+10 | 0.00 | 0.00 |
December | 0.260129E+09 | 0.935700E+10 | 0.170058E+10 | 0.351376E+09 | 0.134920E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.511722E+11 | 0.588588E+11 | 0.563901E+11 | 0.232434E+11 | 0.331467E+11 | 0.00 | 0.00 |
Minimum of Months | 0.260129E+09 | 0.126883E+10 | 0.170058E+10 | 0.351376E+09 | 0.134920E+10 | 0.00 | 0.00 |
Maximum of Months | 0.927520E+10 | 0.945288E+10 | 0.735928E+10 | 0.325244E+10 | 0.410684E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.504048E+10 | 0.133144E+11 | 0.768663E+10 | 0.448691E+10 | 0.319972E+10 | 0.00 | 0.00 |
February | 0.488028E+10 | 0.118302E+11 | 0.792689E+10 | 0.382228E+10 | 0.410461E+10 | 0.00 | 0.00 |
March | 0.887709E+10 | 0.966153E+10 | 0.107119E+11 | 0.601897E+10 | 0.469297E+10 | 0.00 | 0.00 |
April | 0.758842E+10 | 0.734736E+10 | 0.858500E+10 | 0.343059E+10 | 0.515441E+10 | 0.00 | 0.00 |
May | 0.771820E+10 | 0.506305E+10 | 0.776306E+10 | 0.225472E+10 | 0.550834E+10 | 0.00 | 0.00 |
June | 0.848221E+10 | 0.304083E+10 | 0.729986E+10 | 0.154688E+10 | 0.575299E+10 | 0.00 | 0.00 |
July | 0.102824E+11 | 0.214869E+10 | 0.770038E+10 | 0.186836E+10 | 0.583201E+10 | 0.00 | 0.00 |
August | 0.112972E+11 | 0.281419E+10 | 0.864494E+10 | 0.280291E+10 | 0.584203E+10 | 0.00 | 0.00 |
September | 0.114562E+11 | 0.435450E+10 | 0.972725E+10 | 0.473789E+10 | 0.498936E+10 | 0.00 | 0.00 |
October | 0.929760E+10 | 0.697425E+10 | 0.961779E+10 | 0.549387E+10 | 0.412392E+10 | 0.00 | 0.00 |
November | 0.542251E+10 | 0.890238E+10 | 0.666587E+10 | 0.376311E+10 | 0.290276E+10 | 0.00 | 0.00 |
December | 0.391748E+10 | 0.131647E+11 | 0.642755E+10 | 0.332655E+10 | 0.310100E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.942601E+11 | 0.886161E+11 | 0.987572E+11 | 0.435530E+11 | 0.552041E+11 | 0.00 | 0.00 |
Minimum of Months | 0.391748E+10 | 0.214869E+10 | 0.642755E+10 | 0.154688E+10 | 0.290276E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114562E+11 | 0.133144E+11 | 0.107119E+11 | 0.601897E+10 | 0.584203E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.317995E+09 | 0.101260E+11 | 0.187112E+10 | 0.439265E+09 | 0.143185E+10 | 0.00 | 0.00 |
February | 0.742040E+09 | 0.871441E+10 | 0.273909E+10 | 0.703967E+09 | 0.203513E+10 | 0.00 | 0.00 |
March | 0.304538E+10 | 0.681825E+10 | 0.475301E+10 | 0.203513E+10 | 0.271788E+10 | 0.00 | 0.00 |
April | 0.452503E+10 | 0.483893E+10 | 0.563169E+10 | 0.230922E+10 | 0.332247E+10 | 0.00 | 0.00 |
May | 0.687707E+10 | 0.335957E+10 | 0.686493E+10 | 0.310250E+10 | 0.376242E+10 | 0.00 | 0.00 |
June | 0.938600E+10 | 0.215086E+10 | 0.801556E+10 | 0.377019E+10 | 0.424537E+10 | 0.00 | 0.00 |
July | 0.948163E+10 | 0.156868E+10 | 0.740509E+10 | 0.324665E+10 | 0.415844E+10 | 0.00 | 0.00 |
August | 0.840331E+10 | 0.195434E+10 | 0.669746E+10 | 0.284783E+10 | 0.384964E+10 | 0.00 | 0.00 |
September | 0.555286E+10 | 0.288276E+10 | 0.508992E+10 | 0.219812E+10 | 0.289181E+10 | 0.00 | 0.00 |
October | 0.251865E+10 | 0.478846E+10 | 0.340952E+10 | 0.120103E+10 | 0.220849E+10 | 0.00 | 0.00 |
November | 0.879321E+09 | 0.625907E+10 | 0.195531E+10 | 0.563452E+09 | 0.139186E+10 | 0.00 | 0.00 |
December | 0.303385E+09 | 0.976686E+10 | 0.175159E+10 | 0.381651E+09 | 0.136994E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.520327E+11 | 0.632282E+11 | 0.561843E+11 | 0.227990E+11 | 0.333853E+11 | 0.00 | 0.00 |
Minimum of Months | 0.303385E+09 | 0.156868E+10 | 0.175159E+10 | 0.381651E+09 | 0.136994E+10 | 0.00 | 0.00 |
Maximum of Months | 0.948163E+10 | 0.101260E+11 | 0.801556E+10 | 0.377019E+10 | 0.424537E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 2260606.19 | 0.151782E+11 | 0.178758E+10 | 0.00 | 0.178758E+10 | 0.00 | 0.00 |
February | 15931333.44 | 0.131008E+11 | 0.246003E+10 | 0.00 | 0.246003E+10 | 0.00 | 0.00 |
March | 0.667174E+09 | 0.101314E+11 | 0.330296E+10 | 0.00 | 0.330296E+10 | 0.00 | 0.00 |
April | 0.157304E+10 | 0.650497E+10 | 0.407289E+10 | 16252441.88 | 0.405664E+10 | 0.00 | 0.00 |
May | 0.324880E+10 | 0.408490E+10 | 0.489025E+10 | 0.207374E+09 | 0.468287E+10 | 0.00 | 0.00 |
June | 0.568272E+10 | 0.252477E+10 | 0.569220E+10 | 0.484549E+09 | 0.520765E+10 | 0.00 | 0.00 |
July | 0.663916E+10 | 0.182020E+10 | 0.545628E+10 | 0.352215E+09 | 0.510406E+10 | 0.00 | 0.00 |
August | 0.538651E+10 | 0.239834E+10 | 0.472120E+10 | 71822758.33 | 0.464937E+10 | 0.00 | 0.00 |
September | 0.293534E+10 | 0.369590E+10 | 0.347703E+10 | 722376.53 | 0.347631E+10 | 0.00 | 0.00 |
October | 0.100862E+10 | 0.635157E+10 | 0.268587E+10 | 0.00 | 0.268587E+10 | 0.00 | 0.00 |
November | 0.250656E+09 | 0.850522E+10 | 0.174662E+10 | 0.00 | 0.174662E+10 | 0.00 | 0.00 |
December | 6612822.92 | 0.142719E+11 | 0.167312E+10 | 0.00 | 0.167312E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.274168E+11 | 0.885683E+11 | 0.419660E+11 | 0.113294E+10 | 0.408331E+11 | 0.00 | 0.00 |
Minimum of Months | 2260606.19 | 0.182020E+10 | 0.167312E+10 | 0.00 | 0.167312E+10 | 0.00 | 0.00 |
Maximum of Months | 0.663916E+10 | 0.151782E+11 | 0.569220E+10 | 0.484549E+09 | 0.520765E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.569131E+09 | 0.913242E+10 | 0.218084E+10 | 0.703223E+09 | 0.147761E+10 | 0.00 | 0.00 |
February | 0.959098E+09 | 0.791544E+10 | 0.289028E+10 | 0.867301E+09 | 0.202298E+10 | 0.00 | 0.00 |
March | 0.297685E+10 | 0.607597E+10 | 0.459184E+10 | 0.192303E+10 | 0.266881E+10 | 0.00 | 0.00 |
April | 0.479968E+10 | 0.407152E+10 | 0.588154E+10 | 0.259878E+10 | 0.328276E+10 | 0.00 | 0.00 |
May | 0.673571E+10 | 0.280718E+10 | 0.680908E+10 | 0.301202E+10 | 0.379706E+10 | 0.00 | 0.00 |
June | 0.843794E+10 | 0.173672E+10 | 0.735928E+10 | 0.325244E+10 | 0.410684E+10 | 0.00 | 0.00 |
July | 0.924161E+10 | 0.124219E+10 | 0.730241E+10 | 0.321515E+10 | 0.408726E+10 | 0.00 | 0.00 |
August | 0.810436E+10 | 0.162207E+10 | 0.659487E+10 | 0.276817E+10 | 0.382671E+10 | 0.00 | 0.00 |
September | 0.574792E+10 | 0.241316E+10 | 0.531105E+10 | 0.235578E+10 | 0.295527E+10 | 0.00 | 0.00 |
October | 0.296081E+10 | 0.398979E+10 | 0.372412E+10 | 0.154040E+10 | 0.218372E+10 | 0.00 | 0.00 |
November | 0.105443E+10 | 0.537588E+10 | 0.204424E+10 | 0.655770E+09 | 0.138847E+10 | 0.00 | 0.00 |
December | 0.280103E+09 | 0.896543E+10 | 0.170058E+10 | 0.351376E+09 | 0.134920E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.518676E+11 | 0.553478E+11 | 0.563901E+11 | 0.232434E+11 | 0.331467E+11 | 0.00 | 0.00 |
Minimum of Months | 0.280103E+09 | 0.124219E+10 | 0.170058E+10 | 0.351376E+09 | 0.134920E+10 | 0.00 | 0.00 |
Maximum of Months | 0.924161E+10 | 0.913242E+10 | 0.735928E+10 | 0.325244E+10 | 0.410684E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.514426E+10 | 0.127279E+11 | 0.768663E+10 | 0.448691E+10 | 0.319972E+10 | 0.00 | 0.00 |
February | 0.496408E+10 | 0.113307E+11 | 0.792689E+10 | 0.382228E+10 | 0.410461E+10 | 0.00 | 0.00 |
March | 0.902649E+10 | 0.895013E+10 | 0.107119E+11 | 0.601897E+10 | 0.469297E+10 | 0.00 | 0.00 |
April | 0.772385E+10 | 0.674830E+10 | 0.858500E+10 | 0.343059E+10 | 0.515441E+10 | 0.00 | 0.00 |
May | 0.779543E+10 | 0.465231E+10 | 0.776306E+10 | 0.225472E+10 | 0.550834E+10 | 0.00 | 0.00 |
June | 0.849457E+10 | 0.284490E+10 | 0.729986E+10 | 0.154688E+10 | 0.575299E+10 | 0.00 | 0.00 |
July | 0.102720E+11 | 0.203215E+10 | 0.770038E+10 | 0.186836E+10 | 0.583201E+10 | 0.00 | 0.00 |
August | 0.113053E+11 | 0.262897E+10 | 0.864494E+10 | 0.280291E+10 | 0.584203E+10 | 0.00 | 0.00 |
September | 0.115360E+11 | 0.395991E+10 | 0.972725E+10 | 0.473789E+10 | 0.498936E+10 | 0.00 | 0.00 |
October | 0.951121E+10 | 0.618574E+10 | 0.961779E+10 | 0.549387E+10 | 0.412392E+10 | 0.00 | 0.00 |
November | 0.560808E+10 | 0.797575E+10 | 0.666587E+10 | 0.376311E+10 | 0.290276E+10 | 0.00 | 0.00 |
December | 0.401788E+10 | 0.124832E+11 | 0.642755E+10 | 0.332655E+10 | 0.310100E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.953992E+11 | 0.825200E+11 | 0.987572E+11 | 0.435530E+11 | 0.552041E+11 | 0.00 | 0.00 |
Minimum of Months | 0.401788E+10 | 0.203215E+10 | 0.642755E+10 | 0.154688E+10 | 0.290276E+10 | 0.00 | 0.00 |
Maximum of Months | 0.115360E+11 | 0.127279E+11 | 0.107119E+11 | 0.601897E+10 | 0.584203E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.326154E+09 | 0.979508E+10 | 0.187112E+10 | 0.439265E+09 | 0.143185E+10 | 0.00 | 0.00 |
February | 0.744554E+09 | 0.843309E+10 | 0.273909E+10 | 0.703967E+09 | 0.203513E+10 | 0.00 | 0.00 |
March | 0.307088E+10 | 0.642037E+10 | 0.475301E+10 | 0.203513E+10 | 0.271788E+10 | 0.00 | 0.00 |
April | 0.455027E+10 | 0.451007E+10 | 0.563169E+10 | 0.230922E+10 | 0.332247E+10 | 0.00 | 0.00 |
May | 0.686761E+10 | 0.315006E+10 | 0.686493E+10 | 0.310250E+10 | 0.376242E+10 | 0.00 | 0.00 |
June | 0.933148E+10 | 0.205728E+10 | 0.801556E+10 | 0.377019E+10 | 0.424537E+10 | 0.00 | 0.00 |
July | 0.942406E+10 | 0.151678E+10 | 0.740509E+10 | 0.324665E+10 | 0.415844E+10 | 0.00 | 0.00 |
August | 0.837462E+10 | 0.186827E+10 | 0.669746E+10 | 0.284783E+10 | 0.384964E+10 | 0.00 | 0.00 |
September | 0.556750E+10 | 0.268263E+10 | 0.508992E+10 | 0.219812E+10 | 0.289181E+10 | 0.00 | 0.00 |
October | 0.258090E+10 | 0.435984E+10 | 0.340952E+10 | 0.120103E+10 | 0.220849E+10 | 0.00 | 0.00 |
November | 0.918991E+09 | 0.573735E+10 | 0.195531E+10 | 0.563452E+09 | 0.139186E+10 | 0.00 | 0.00 |
December | 0.311092E+09 | 0.938421E+10 | 0.175159E+10 | 0.381651E+09 | 0.136994E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.520681E+11 | 0.599150E+11 | 0.561843E+11 | 0.227990E+11 | 0.333853E+11 | 0.00 | 0.00 |
Minimum of Months | 0.311092E+09 | 0.151678E+10 | 0.175159E+10 | 0.381651E+09 | 0.136994E+10 | 0.00 | 0.00 |
Maximum of Months | 0.942406E+10 | 0.979508E+10 | 0.801556E+10 | 0.377019E+10 | 0.424537E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.423782E+11 | -0.419189E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -459297346.4 | 60.05 | 0.00 | 0.00 |
February | 0.390503E+11 | -0.386325E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -417752408.6 | 60.05 | 0.00 | 0.00 |
March | 0.452903E+11 | -0.448357E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -454629840.7 | 60.05 | 0.00 | 0.00 |
April | 0.395165E+11 | -0.390803E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -436224476.1 | 60.05 | 0.00 | 0.00 |
May | 0.398649E+11 | -0.394149E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -450018806.9 | 60.05 | 0.00 | 0.00 |
June | 0.371342E+11 | -0.367014E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -432786089.1 | 60.05 | 0.00 | 0.00 |
July | 0.336767E+11 | -0.332332E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443529308.4 | 60.05 | 0.00 | 0.00 |
August | 0.361623E+11 | -0.357176E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444660368.9 | 60.05 | 0.00 | 0.00 |
September | 0.334061E+11 | -0.329757E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -430398505.7 | 60.05 | 0.00 | 0.00 |
October | 0.361265E+11 | -0.356802E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -446290215.9 | 60.05 | 0.00 | 0.00 |
November | 0.376561E+11 | -0.372240E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -432039880.4 | 60.05 | 0.00 | 0.00 |
December | 0.397053E+11 | -0.392532E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -452049790.6 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.459967E+12 | -0.454668E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.529968E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.334061E+11 | -0.448357E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -459297346.4 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.452903E+11 | -0.329757E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -417752408.6 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 255.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 262.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 339.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 371.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 332.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 430.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 289.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 314.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 258.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3928.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.152177E+11 | 35964.33 | 04-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153741E+11 | 45582.63 | 07-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384630E+10 | 35475.47 | 07-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125423E+09 | 15078.26 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 81450472.57 | 10838.79 | 17-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.319457E+09 | 12079.45 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.795409E+10 | 43603.25 | 11-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.429185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.153741E+11 | 45582.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.436546E+10 | 20053.05 | 23-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.396536E+10 | 20056.93 | 22-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138256E+10 | 20784.06 | 03-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119353E+09 | 19837.19 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 116272.63 | 775.15 | 08-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 711334.97 | 278.57 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104449E+09 | 20429.93 | 17-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.321327E+09 | 19865.01 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.267063E+10 | 20037.23 | 26-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.436546E+10 | 20784.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.445411E+10 | 19412.39 | 10-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.395799E+10 | 19417.57 | 08-FEB-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166738E+10 | 19416.33 | 06-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.476895E+09 | 18667.29 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 59556266.25 | 3899.47 | 01-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 36710364.72 | 3392.64 | 30-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.466135E+09 | 18771.91 | 17-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112997E+10 | 18419.07 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.381606E+10 | 19420.41 | 26-DEC-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.445411E+10 | 19420.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.520843E+10 | 26571.90 | 12-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.466483E+10 | 26570.90 | 21-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.178875E+10 | 26551.60 | 06-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.624403E+09 | 25534.79 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120592E+09 | 4747.95 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5346371.36 | 3830.01 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 28465475.67 | 3866.22 | 30-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.468030E+09 | 25856.19 | 17-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118808E+10 | 25201.80 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.416223E+10 | 26570.80 | 26-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.520843E+10 | 26571.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.377957E+10 | 19734.34 | 12-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.301643E+10 | 19733.93 | 21-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.682121E+09 | 19691.10 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 42336293.76 | 12754.83 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15512556.39 | 2437.43 | 12-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8934324.19 | 1767.49 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166447E+09 | 17570.05 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.344525E+09 | 18712.90 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159360E+10 | 19733.84 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.964947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.377957E+10 | 19734.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.252450E+12 | 432815.65 | 04-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.231339E+12 | 512034.62 | 07-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.850466E+11 | 424669.47 | 07-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.538533E+10 | 515415.37 | 13-APR-13:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.314274E+09 | 225522.19 | 18-MAY-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108183E+09 | 345673.63 | 13-JUN-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2017.09 | 6.72 | 29-JUL-17:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3373924.16 | 33739.24 | 31-AUG-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12521961.74 | 33025.42 | 29-SEP-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.326237E+10 | 385086.86 | 16-OCT-09:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129397E+11 | 552233.18 | 03-NOV-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.194925E+12 | 514863.93 | 11-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.785786E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2017.09 | 6.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.252450E+12 | 552233.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.201780E+11 | 694703.15 | 31-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109026E+11 | 694118.58 | 08-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141123E+10 | 694020.99 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.778454E+10 | 693836.98 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.402763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.201780E+11 | 694703.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131892E+12 | 289974.32 | 24-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119284E+12 | 289754.17 | 21-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.636821E+11 | 290028.00 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.232262E+11 | 289782.33 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.364862E+10 | 230971.31 | 08-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 78574979.89 | 35132.18 | 14-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 65550502.35 | 23280.44 | 31-AUG-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.257866E+10 | 154022.73 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202157E+11 | 284287.05 | 17-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.439542E+11 | 288887.87 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117171E+12 | 289940.08 | 26-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.525796E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131892E+12 | 290028.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.819423E+11 | 233288.75 | 04-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.733320E+11 | 233366.15 | 21-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.356494E+11 | 232869.06 | 08-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142209E+11 | 221617.93 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.306897E+10 | 132811.35 | 08-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.227198E+09 | 32065.16 | 14-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.192317E+09 | 39255.50 | 31-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.250493E+10 | 112072.57 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142650E+11 | 217571.04 | 17-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316112E+11 | 221786.02 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.772990E+11 | 233274.86 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.334313E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.819423E+11 | 233366.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.959249E+11 | 289975.74 | 24-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.870726E+11 | 289755.59 | 21-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.362441E+11 | 288519.59 | 25-MAR-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172606E+11 | 285592.57 | 17-APR-04:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.369640E+10 | 175110.78 | 08-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.514305E+09 | 150179.74 | 14-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 54557491.27 | 16192.82 | 31-AUG-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129758E+10 | 112843.74 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122321E+11 | 284288.44 | 17-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.308127E+11 | 288889.28 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.906533E+11 | 289941.50 | 26-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.375763E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.959249E+11 | 289975.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.891128E+11 | 240192.09 | 04-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.781976E+11 | 240197.43 | 14-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388136E+11 | 239641.63 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164177E+11 | 228196.04 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.428052E+10 | 93465.93 | 03-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.584642E+09 | 56899.26 | 14-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2069202.49 | 4115.42 | 06-JUL-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123802E+09 | 31597.67 | 31-AUG-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.292649E+10 | 85149.64 | 29-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164606E+11 | 224026.08 | 17-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.349207E+11 | 228372.51 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.797796E+11 | 240170.19 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.361620E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2069202.49 | 4115.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.891128E+11 | 240197.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.307148E+11 | 49765.33 | 04-JAN-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.274015E+11 | 51079.53 | 21-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110109E+11 | 49846.97 | 07-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132101E+10 | 29951.24 | 17-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40987202.58 | 11025.00 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37.19 | 0.62 | 21-JUN-05:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 200538.86 | 454.86 | 05-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.866681E+09 | 25564.47 | 17-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.301544E+10 | 27337.41 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.252720E+11 | 52136.95 | 11-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.996435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.307148E+11 | 52136.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.176735E+11 | 115126.52 | 23-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149722E+11 | 115256.07 | 16-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.783670E+10 | 114957.63 | 24-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214291E+10 | 115061.98 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.188022E+09 | 89974.17 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 64973637.20 | 8751.99 | 05-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.244842E+10 | 113470.39 | 17-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.566541E+10 | 115057.85 | 24-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154364E+11 | 114839.37 | 12-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.664285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.176735E+11 | 115256.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.214651E+11 | 37999.48 | 09-JAN-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.199899E+11 | 38006.38 | 28-FEB-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127768E+11 | 38046.09 | 03-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.620483E+10 | 37746.34 | 17-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197327E+10 | 31694.73 | 02-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.360255E+09 | 30350.29 | 15-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24205830.33 | 4576.27 | 07-JUL-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.238499E+09 | 10954.08 | 31-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151772E+10 | 29775.90 | 11-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.600595E+10 | 37513.15 | 17-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103055E+11 | 37861.01 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205767E+11 | 38070.85 | 06-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101439E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 24205830.33 | 4576.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.214651E+11 | 38070.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.133221E+11 | 25658.17 | 04-JAN-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122137E+11 | 25663.83 | 28-FEB-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.681833E+10 | 25679.66 | 25-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.304699E+10 | 25215.00 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.888584E+09 | 20448.63 | 08-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140079E+09 | 20062.17 | 14-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2554494.85 | 2001.42 | 07-JUL-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 96731242.49 | 8535.47 | 31-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.722278E+09 | 19536.86 | 30-SEP-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.323007E+10 | 24915.60 | 17-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.636157E+10 | 25265.26 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132861E+11 | 25661.61 | 06-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.601291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2554494.85 | 2001.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.133221E+11 | 25679.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.169128E+11 | 37996.77 | 04-JAN-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159843E+11 | 38006.67 | 28-FEB-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.868330E+10 | 37996.51 | 06-MAR-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.492358E+10 | 37444.03 | 17-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183089E+10 | 30796.43 | 08-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.479886E+09 | 30350.53 | 15-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105297E+09 | 5102.39 | 06-JUL-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.218458E+09 | 8903.89 | 31-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106213E+10 | 29426.07 | 30-SEP-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.408453E+10 | 37412.94 | 17-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.792804E+10 | 37861.30 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171469E+11 | 38071.15 | 06-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.793600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.105297E+09 | 5102.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171469E+11 | 38071.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.129708E+11 | 28659.97 | 12-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116019E+11 | 28661.64 | 03-FEB-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.656836E+10 | 28661.47 | 01-MAR-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.334097E+10 | 27234.24 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122424E+10 | 21058.90 | 18-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.277621E+09 | 21642.73 | 14-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 48197207.49 | 3287.75 | 06-JUL-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139903E+09 | 4204.51 | 31-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.897294E+09 | 19339.14 | 30-SEP-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.339182E+10 | 26835.80 | 17-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.600888E+10 | 27267.50 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120775E+11 | 28657.75 | 29-DEC-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.585475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 48197207.49 | 3287.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.129708E+11 | 28661.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 50484106.80 | 7168.44 | 06-FEB-21:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50484106.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50484106.80 | 7168.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 728034.12 | 728034.12 | 2416.54 | 19-JAN-17:05 | 2416.54 | 0.00 |
February | 0.00 | 0.00 | 118407.09 | 118407.09 | 957.39 | 28-FEB-17:01 | 957.39 | 0.00 |
March | 0.00 | 0.00 | 0.709597E+10 | 0.692450E+10 | 120191.35 | 15-MAR-13:50 | 120191.35 | 0.04 |
April | 0.00 | 0.00 | 0.293594E+10 | 0.293594E+10 | 58183.21 | 07-APR-14:00 | 58183.21 | 0.01 |
May | 0.00 | 0.00 | 0.244533E+11 | 0.240573E+11 | 115313.92 | 10-MAY-14:30 | 106997.01 | 0.12 |
June | 0.00 | 0.00 | 0.934731E+11 | 0.793829E+11 | 195230.94 | 29-JUN-04:11 | 98639.10 | 0.44 |
July | 0.00 | 0.00 | 0.158252E+12 | 0.132262E+12 | 219620.97 | 17-JUL-04:12 | 171230.86 | 0.65 |
August | 0.00 | 0.00 | 0.141971E+12 | 0.123936E+12 | 204948.03 | 08-AUG-04:11 | 88846.97 | 0.65 |
September | 0.00 | 0.00 | 0.595005E+11 | 0.523716E+11 | 205904.71 | 14-SEP-05:02 | 88818.20 | 0.33 |
October | 0.00 | 0.00 | 0.873537E+10 | 0.872877E+10 | 112380.57 | 11-OCT-15:10 | 112380.57 | 0.07 |
November | 0.00 | 0.00 | 0.138038E+10 | 0.138038E+10 | 78134.91 | 27-NOV-06:03 | 78134.91 | 0.02 |
December | 0.00 | 0.00 | 8382228.71 | 8382228.71 | 3645.53 | 01-DEC-10:53 | 3645.53 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.497807E+12 | 0.431989E+12 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 118407.09 | 118407.09 | 957.39 | 957.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.158252E+12 | 0.132262E+12 | 219620.97 | 171230.86 | 0.65 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 82960.50 | 82960.50 | 4.24 | 29-JAN-19:20 | 4.24 | 0.00 |
February | 0.00 | 0.00 | 63452.91 | 63452.91 | 5.89 | 05-FEB-16:31 | 5.89 | 0.00 |
March | 0.00 | 0.00 | 0.643912E+11 | 0.630859E+11 | 1030212.76 | 15-MAR-14:05 | 1030212.76 | 0.05 |
April | 0.00 | 0.00 | 0.286261E+11 | 0.286261E+11 | 629122.75 | 26-APR-13:03 | 629122.75 | 0.01 |
May | 0.00 | 0.00 | 0.231662E+12 | 0.228152E+12 | 1108872.33 | 24-MAY-05:02 | 754367.33 | 0.12 |
June | 0.00 | 0.00 | 0.835483E+12 | 0.703289E+12 | 1782589.41 | 29-JUN-04:11 | 893567.61 | 0.44 |
July | 0.00 | 0.00 | 0.132680E+13 | 0.108551E+13 | 2329149.32 | 21-JUL-04:02 | 1439804.17 | 0.58 |
August | 0.00 | 0.00 | 0.113584E+13 | 0.982873E+12 | 2372225.42 | 15-AUG-05:02 | 1573168.43 | 0.58 |
September | 0.00 | 0.00 | 0.529400E+12 | 0.462964E+12 | 1957574.46 | 14-SEP-05:02 | 843876.31 | 0.33 |
October | 0.00 | 0.00 | 0.964522E+11 | 0.964291E+11 | 944162.66 | 11-OCT-15:20 | 944162.66 | 0.09 |
November | 0.00 | 0.00 | 0.159446E+11 | 0.159446E+11 | 526910.50 | 16-NOV-15:01 | 526910.50 | 0.02 |
December | 0.00 | 0.00 | 23839953.82 | 23839953.82 | 14899.60 | 01-DEC-10:53 | 14899.60 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.426462E+13 | 0.366690E+13 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 63452.91 | 63452.91 | 4.24 | 4.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.132680E+13 | 0.108551E+13 | 2372225.42 | 1573168.43 | 0.58 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6777671.26 | 6777671.26 | 4626.88 | 23-JAN-06:01 | 4626.88 | 0.00 |
February | 0.00 | 0.00 | 5000413.77 | 5000413.77 | 5228.09 | 24-FEB-05:41 | 5228.09 | 0.00 |
March | 0.00 | 0.00 | 0.630187E+10 | 0.620231E+10 | 120708.94 | 15-MAR-14:00 | 120708.94 | 0.04 |
April | 0.00 | 0.00 | 0.232517E+10 | 0.232517E+10 | 44326.09 | 07-APR-14:00 | 44326.09 | 0.01 |
May | 0.00 | 0.00 | 0.245202E+11 | 0.242568E+11 | 133661.13 | 10-MAY-14:40 | 125810.41 | 0.11 |
June | 0.00 | 0.00 | 0.951468E+11 | 0.823311E+11 | 213134.64 | 27-JUN-05:02 | 129493.12 | 0.42 |
July | 0.00 | 0.00 | 0.152692E+12 | 0.128671E+12 | 345211.32 | 21-JUL-03:01 | 216142.60 | 0.57 |
August | 0.00 | 0.00 | 0.127072E+12 | 0.112174E+12 | 274181.72 | 14-AUG-04:11 | 156660.87 | 0.56 |
September | 0.00 | 0.00 | 0.543672E+11 | 0.481608E+11 | 241169.68 | 14-SEP-05:02 | 103301.24 | 0.31 |
October | 0.00 | 0.00 | 0.663799E+10 | 0.663799E+10 | 103871.76 | 11-OCT-15:20 | 103871.76 | 0.07 |
November | 0.00 | 0.00 | 0.110255E+10 | 0.110255E+10 | 27701.05 | 27-NOV-06:03 | 27701.05 | 0.02 |
December | 0.00 | 0.00 | 12406924.68 | 12406924.68 | 3602.33 | 08-DEC-06:01 | 3602.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.470189E+12 | 0.411886E+12 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 5000413.77 | 5000413.77 | 3602.33 | 3602.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.152692E+12 | 0.128671E+12 | 345211.32 | 216142.60 | 0.57 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.108477E+10 | 0.102989E+10 | 74873.30 | 02-JAN-06:13 | 50038.84 | 0.00 |
February | 0.00 | 0.00 | 0.252618E+09 | 0.252618E+09 | 55096.75 | 13-FEB-06:01 | 55096.75 | 0.00 |
March | 0.00 | 0.00 | 0.607925E+10 | 0.562742E+10 | 108266.34 | 18-MAR-04:58 | 108266.34 | 0.05 |
April | 0.00 | 0.00 | 0.690275E+10 | 0.690166E+10 | 107149.83 | 06-APR-04:36 | 107149.83 | 0.00 |
May | 0.00 | 0.00 | 0.205594E+11 | 0.188720E+11 | 96145.06 | 17-MAY-14:20 | 42190.48 | 0.12 |
June | 0.00 | 0.00 | 0.529069E+11 | 0.400045E+11 | 146168.54 | 27-JUN-04:53 | 58584.35 | 0.39 |
July | 0.00 | 0.00 | 0.814381E+11 | 0.591585E+11 | 155453.67 | 17-JUL-03:01 | 109238.32 | 0.50 |
August | 0.00 | 0.00 | 0.774254E+11 | 0.603662E+11 | 148951.92 | 28-AUG-04:32 | 66126.44 | 0.55 |
September | 0.00 | 0.00 | 0.455623E+11 | 0.358524E+11 | 152645.39 | 16-SEP-04:53 | 69259.33 | 0.36 |
October | 0.00 | 0.00 | 0.164038E+11 | 0.155542E+11 | 130046.18 | 17-OCT-03:59 | 130046.18 | 0.11 |
November | 0.00 | 0.00 | 0.790609E+10 | 0.789911E+10 | 120592.41 | 13-NOV-01:17 | 120592.41 | 0.02 |
December | 0.00 | 0.00 | 0.251648E+10 | 0.251521E+10 | 109851.62 | 06-DEC-06:00 | 109851.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.319038E+12 | 0.254034E+12 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 0.252618E+09 | 0.252618E+09 | 55096.75 | 42190.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.814381E+11 | 0.603662E+11 | 155453.67 | 130046.18 | 0.55 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2990644.88 | 2990644.88 | 71.65 | 17-JAN-05:22 | 71.65 | 0.03 |
February | 0.00 | 0.00 | 0.156290E+12 | 0.156290E+12 | 267551.81 | 01-FEB-00:21 | 267551.81 | 0.00 |
March | 0.00 | 0.00 | 0.228962E+12 | 0.227826E+12 | 340288.64 | 16-MAR-15:06 | 240963.08 | 0.11 |
April | 0.00 | 0.00 | 0.203353E+12 | 0.203353E+12 | 271578.56 | 25-APR-14:00 | 271578.56 | 0.02 |
May | 0.00 | 0.00 | 0.159683E+11 | 0.159180E+11 | 284967.52 | 31-MAY-23:41 | 249059.01 | 0.17 |
June | 0.00 | 0.00 | 0.315577E+12 | 0.276079E+12 | 530116.82 | 21-JUN-10:34 | 194047.17 | 0.58 |
July | 0.00 | 0.00 | 0.537874E+12 | 0.515224E+12 | 520630.36 | 17-JUL-17:10 | 286371.24 | 0.98 |
August | 0.00 | 0.00 | 0.637019E+12 | 0.595695E+12 | 538604.23 | 07-AUG-07:05 | 389396.95 | 0.96 |
September | 0.00 | 0.00 | 0.439237E+11 | 0.439111E+11 | 219034.67 | 30-SEP-23:34 | 219034.67 | 0.33 |
October | 0.00 | 0.00 | 0.162603E+12 | 0.156855E+12 | 353040.77 | 01-OCT-07:21 | 239172.60 | 0.14 |
November | 0.00 | 0.00 | 0.210075E+12 | 0.210060E+12 | 290222.26 | 26-NOV-16:22 | 290222.26 | 0.04 |
December | 0.00 | 0.00 | 0.226767E+12 | 0.226767E+12 | 257222.99 | 19-DEC-12:10 | 257222.99 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.273842E+13 | 0.262798E+13 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 2990644.88 | 2990644.88 | 71.65 | 71.65 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.637019E+12 | 0.595695E+12 | 538604.23 | 389396.95 | 0.98 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.470831E+10 | 0.470831E+10 | 2823.64 | 15-JAN-16:35 | 2823.64 | 0.00 |
February | 0.00 | 0.00 | 0.873912E+10 | 0.873912E+10 | 5074.15 | 28-FEB-16:53 | 5074.15 | 0.00 |
March | 0.00 | 0.00 | 0.162489E+11 | 0.162351E+11 | 8000.55 | 31-MAR-23:57 | 8000.55 | 0.00 |
April | 0.00 | 0.00 | 0.212421E+11 | 0.212407E+11 | 9233.37 | 02-APR-17:50 | 9233.37 | 0.00 |
May | 0.00 | 0.00 | 0.740049E+10 | 0.737941E+10 | 4739.61 | 31-MAY-23:53 | 4739.61 | 0.00 |
June | 0.00 | 0.00 | 0.126878E+11 | 0.125391E+11 | 6659.84 | 30-JUN-23:53 | 6659.84 | 0.00 |
July | 0.00 | 0.00 | 0.186362E+11 | 0.183594E+11 | 8650.09 | 31-JUL-23:02 | 8532.80 | 0.00 |
August | 0.00 | 0.00 | 0.235399E+11 | 0.233283E+11 | 9705.38 | 14-AUG-16:00 | 9356.39 | 0.00 |
September | 0.00 | 0.00 | 0.755055E+10 | 0.744636E+10 | 4382.40 | 30-SEP-23:51 | 4382.40 | 0.00 |
October | 0.00 | 0.00 | 0.117972E+11 | 0.117805E+11 | 6211.61 | 31-OCT-23:52 | 6211.61 | 0.00 |
November | 0.00 | 0.00 | 0.159095E+11 | 0.159084E+11 | 6984.38 | 15-NOV-16:13 | 6984.38 | 0.00 |
December | 0.00 | 0.00 | 0.205011E+11 | 0.205011E+11 | 8539.02 | 04-DEC-16:17 | 8539.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.168961E+12 | 0.168166E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.470831E+10 | 0.470831E+10 | 2823.64 | 2823.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.235399E+11 | 0.233283E+11 | 9705.38 | 9356.39 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.223573E+11 | 0.223573E+11 | 23648.92 | 12-JAN-16:40 | 23648.92 | 0.00 |
February | 0.00 | 0.00 | 0.662931E+11 | 0.662931E+11 | 47036.30 | 28-FEB-16:53 | 47036.30 | 0.00 |
March | 0.00 | 0.00 | 0.142234E+12 | 0.142096E+12 | 73315.63 | 31-MAR-23:27 | 73315.63 | 0.00 |
April | 0.00 | 0.00 | 0.194112E+12 | 0.194099E+12 | 87807.67 | 24-APR-17:55 | 87807.67 | 0.00 |
May | 0.00 | 0.00 | 0.649464E+11 | 0.647369E+11 | 44724.15 | 31-MAY-23:33 | 44724.15 | 0.00 |
June | 0.00 | 0.00 | 0.118870E+12 | 0.117388E+12 | 63672.23 | 30-JUN-23:33 | 63672.23 | 0.00 |
July | 0.00 | 0.00 | 0.176061E+12 | 0.173305E+12 | 83338.66 | 31-JUL-23:02 | 82183.79 | 0.00 |
August | 0.00 | 0.00 | 0.222458E+12 | 0.220355E+12 | 93135.68 | 04-AUG-18:40 | 93135.68 | 0.00 |
September | 0.00 | 0.00 | 0.656522E+11 | 0.646233E+11 | 37680.67 | 30-SEP-23:52 | 37680.67 | 0.00 |
October | 0.00 | 0.00 | 0.102249E+12 | 0.102082E+12 | 55627.39 | 31-OCT-23:22 | 55627.39 | 0.00 |
November | 0.00 | 0.00 | 0.138060E+12 | 0.138048E+12 | 65618.84 | 15-NOV-16:13 | 65618.84 | 0.00 |
December | 0.00 | 0.00 | 0.173960E+12 | 0.173959E+12 | 77992.22 | 04-DEC-16:17 | 77992.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.148725E+13 | 0.147934E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.223573E+11 | 0.223573E+11 | 23648.92 | 23648.92 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.222458E+12 | 0.220355E+12 | 93135.68 | 93135.68 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.100599E+10 | 0.100599E+10 | 2106.97 | 12-JAN-16:40 | 2106.97 | 0.00 |
February | 0.00 | 0.00 | 0.482452E+10 | 0.482452E+10 | 4678.29 | 28-FEB-16:53 | 4678.29 | 0.00 |
March | 0.00 | 0.00 | 0.124367E+11 | 0.124229E+11 | 6980.22 | 15-MAR-15:20 | 6901.15 | 0.00 |
April | 0.00 | 0.00 | 0.181238E+11 | 0.181227E+11 | 8839.54 | 24-APR-17:55 | 8839.54 | 0.00 |
May | 0.00 | 0.00 | 0.582349E+10 | 0.580276E+10 | 4301.18 | 31-MAY-23:12 | 4301.18 | 0.00 |
June | 0.00 | 0.00 | 0.117175E+11 | 0.115692E+11 | 6225.08 | 30-JUN-23:12 | 6225.08 | 0.00 |
July | 0.00 | 0.00 | 0.176261E+11 | 0.173506E+11 | 8308.90 | 31-JUL-23:02 | 8207.44 | 0.00 |
August | 0.00 | 0.00 | 0.221314E+11 | 0.219222E+11 | 9475.50 | 04-AUG-18:30 | 9475.24 | 0.00 |
September | 0.00 | 0.00 | 0.591995E+10 | 0.581725E+10 | 3758.10 | 21-SEP-17:30 | 3685.48 | 0.00 |
October | 0.00 | 0.00 | 0.854664E+10 | 0.853015E+10 | 5517.77 | 11-OCT-17:00 | 5494.40 | 0.00 |
November | 0.00 | 0.00 | 0.117171E+11 | 0.117159E+11 | 6439.29 | 15-NOV-16:13 | 6439.29 | 0.00 |
December | 0.00 | 0.00 | 0.152433E+11 | 0.152432E+11 | 7547.12 | 04-DEC-16:17 | 7547.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.135116E+12 | 0.134327E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.100599E+10 | 0.100599E+10 | 2106.97 | 2106.97 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.221314E+11 | 0.219222E+11 | 9475.50 | 9475.24 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 303607.81 | 3552217.06 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 301400.08 | 2694990.96 | 18-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 120256.46 | 2938011.79 | 03-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 37973.82 | 2703693.73 | 06-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 7939.76 | 1736157.88 | 08-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 1072.20 | 725659.79 | 14-JUN-05:01 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 64.70 | 11520.18 | 06-JUL-05:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 420.34 | 84763.07 | 31-AUG-05:24 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 5259.21 | 1145092.20 | 30-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 32640.00 | 2901026.02 | 17-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 75651.22 | 2861353.16 | 15-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 256874.77 | 2840983.49 | 30-DEC-05:01 |
Annual Sum or Average | 0.00 | 94284.42 | ||||
Minimum of Months | 0.00 | 0.00 | 64.70 | 11520.18 | ||
Maximum of Months | 0.00 | 0.00 | 303607.81 | 3552217.06 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1683.12 | 118641.66 | 03-JAN-22:02 | 128154.20 | 915902.57 | 15-JAN-13:40 |
February | 68407.43 | 900292.69 | 28-FEB-07:02 | 175380.50 | 806318.59 | 06-FEB-12:12 |
March | 130732.62 | 2115927.20 | 14-MAR-13:10 | 6365.85 | 681511.14 | 01-MAR-04:02 |
April | 103215.55 | 1170703.81 | 25-APR-13:54 | 13755.69 | 891455.24 | 30-APR-24:00 |
May | 125181.05 | 1842524.73 | 10-MAY-15:40 | 230979.28 | 915573.77 | 07-MAY-08:07 |
June | 564252.68 | 2869668.46 | 21-JUN-09:11 | 51601.45 | 881935.19 | 30-JUN-23:11 |
July | 892689.89 | 3367889.57 | 29-JUL-05:05 | 9290.67 | 622622.33 | 01-JUL-00:08 |
August | 837246.80 | 3775322.70 | 15-AUG-05:02 | 4178.93 | 421479.92 | 16-AUG-06:05 |
September | 303609.92 | 2493289.42 | 15-SEP-12:05 | 153271.72 | 915541.74 | 29-SEP-01:40 |
October | 113813.69 | 1689457.95 | 11-OCT-15:10 | 145718.77 | 860378.74 | 13-OCT-07:33 |
November | 101404.73 | 1152828.43 | 16-NOV-14:41 | 7980.39 | 725997.10 | 01-NOV-04:11 |
December | 95095.34 | 866467.50 | 22-DEC-11:20 | 12235.57 | 629603.69 | 19-DEC-09:15 |
Annual Sum or Average | 279944.14 | 77680.97 | ||||
Minimum of Months | 1683.12 | 118641.66 | 4178.93 | 421479.92 | ||
Maximum of Months | 892689.89 | 3775322.70 | 230979.28 | 915902.57 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 386.91 | 85792.89 | 21-JAN-06:01 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 75593.91 | 438349.25 | 17-FEB-16:53 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 231559.47 | 1925773.85 | 15-MAR-13:50 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 205828.93 | 1059465.75 | 08-APR-13:15 | 0.00 | 0.00 | 01-APR-00:10 |
May | 144164.77 | 5177349.72 | 24-MAY-04:12 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 599369.86 | 4694987.74 | 27-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:01 |
July | 925330.04 | 4906462.82 | 29-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:01 |
August | 881869.29 | 4806104.92 | 08-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 327240.63 | 4868692.97 | 14-SEP-04:11 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 142130.92 | 1682105.61 | 11-OCT-15:10 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 207016.15 | 1311590.58 | 16-NOV-13:04 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 200237.32 | 552006.47 | 11-DEC-06:11 | 0.00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 330400.92 | 0.00 | ||||
Minimum of Months | 386.91 | 85792.89 | 0.00 | 0.00 | ||
Maximum of Months | 925330.04 | 5177349.72 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 15565.49 | 55761.35 | 31-JAN-12:25 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 15883.48 | 55959.12 | 15-FEB-12:48 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 16653.06 | 55779.99 | 01-MAR-12:47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 14992.81 | 54072.28 | 03-APR-11:56 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14631.74 | 51559.82 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14076.10 | 48364.99 | 01-JUN-11:18 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 12326.76 | 45521.93 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 13253.11 | 44047.86 | 01-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12640.60 | 45463.01 | 29-SEP-11:42 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 13239.12 | 48281.29 | 31-OCT-11:54 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14277.44 | 51375.77 | 30-NOV-12:35 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 14571.55 | 54008.96 | 29-DEC-12:18 |
Annual Sum or Average | 0.00 | 14333.73 | ||||
Minimum of Months | 0.00 | 0.00 | 12326.76 | 44047.86 | ||
Maximum of Months | 0.00 | 0.00 | 16653.06 | 55959.12 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 219.59 | 62377.80 | 18-JAN-07:30 | 3827.93 | 201604.51 | 25-JAN-04:05 |
February | 40221.47 | 693943.63 | 17-FEB-12:06 | 48.60 | 69294.50 | 02-FEB-06:47 |
March | 81764.48 | 3447539.85 | 15-MAR-13:05 | 5843.69 | 137657.16 | 30-MAR-04:11 |
April | 72211.54 | 1172630.45 | 25-APR-13:56 | 5471.40 | 164300.17 | 14-APR-09:00 |
May | 150839.15 | 3241674.73 | 10-MAY-15:40 | 1440.97 | 149187.01 | 02-MAY-03:10 |
June | 852050.44 | 6897566.68 | 27-JUN-13:00 | 18.32 | 61917.10 | 13-JUN-08:43 |
July | 1623656.15 | 7308848.52 | 20-JUL-14:05 | 37.66 | 37800.25 | 06-JUL-06:20 |
August | 1334747.67 | 6328286.43 | 15-AUG-13:00 | 270.81 | 51275.04 | 18-AUG-01:30 |
September | 424357.19 | 5266624.70 | 15-SEP-12:05 | 697.31 | 104402.98 | 03-SEP-22:20 |
October | 136400.94 | 1960373.89 | 11-OCT-15:10 | 167.91 | 84981.81 | 16-OCT-05:47 |
November | 49327.63 | 1164346.75 | 16-NOV-13:06 | 6508.04 | 146159.06 | 21-NOV-03:57 |
December | 24243.53 | 828165.36 | 19-DEC-11:58 | 9993.91 | 169911.06 | 09-DEC-16:50 |
Annual Sum or Average | 402664.72 | 2880.22 | ||||
Minimum of Months | 219.59 | 62377.80 | 18.32 | 37800.25 | ||
Maximum of Months | 1623656.15 | 7308848.52 | 9993.91 | 201604.51 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.745857E+10 | 0.51 | 8284.31 | 12-JAN-13:40 | 1.12 |
February | 0.686623E+10 | 0.52 | 20887.42 | 23-FEB-06:01 | 1.65 |
March | 0.101221E+11 | 0.58 | 20887.42 | 03-MAR-06:01 | 1.66 |
April | 0.107315E+11 | 0.60 | 19947.74 | 03-APR-05:01 | 1.62 |
May | 0.117924E+11 | 0.62 | 17847.45 | 24-MAY-05:02 | 1.53 |
June | 0.150972E+11 | 0.72 | 26711.41 | 17-JUN-05:01 | 1.82 |
July | 0.177725E+11 | 0.78 | 26711.41 | 22-JUL-04:11 | 1.82 |
August | 0.194391E+11 | 0.83 | 26711.41 | 14-AUG-04:11 | 1.82 |
September | 0.130727E+11 | 0.65 | 20823.52 | 14-SEP-04:11 | 1.63 |
October | 0.106125E+11 | 0.57 | 20887.42 | 17-OCT-05:01 | 1.66 |
November | 0.934814E+10 | 0.54 | 20451.94 | 03-NOV-05:01 | 1.64 |
December | 0.825584E+10 | 0.51 | 20887.42 | 18-DEC-06:01 | 1.65 |
Annual Sum or Average | 0.140569E+12 | 0.62 | |||
Minimum of Months | 0.686623E+10 | 0.51 | 8284.31 | 1.12 | |
Maximum of Months | 0.194391E+11 | 0.83 | 26711.41 | 1.82 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.878283E+11 | 0.63 | 115649.07 | 02-JAN-04:01 | 1.32 |
February | 0.802218E+11 | 0.63 | 115649.07 | 06-FEB-05:11 | 1.33 |
March | 0.901053E+11 | 0.59 | 223533.32 | 31-MAR-05:01 | 1.75 |
April | 0.869761E+11 | 0.56 | 217239.18 | 26-APR-05:02 | 1.73 |
May | 0.107914E+12 | 0.61 | 177822.36 | 02-MAY-05:02 | 1.59 |
June | 0.132954E+12 | 0.70 | 181346.27 | 19-JUN-05:01 | 1.59 |
July | 0.142967E+12 | 0.69 | 250364.47 | 21-JUL-03:01 | 1.82 |
August | 0.148337E+12 | 0.71 | 250364.47 | 14-AUG-04:11 | 1.82 |
September | 0.113093E+12 | 0.62 | 177822.36 | 01-SEP-04:12 | 1.57 |
October | 0.879304E+11 | 0.53 | 230760.06 | 03-OCT-05:01 | 1.77 |
November | 0.745993E+11 | 0.51 | 230760.06 | 01-NOV-05:01 | 1.77 |
December | 0.830808E+11 | 0.59 | 115649.07 | 04-DEC-06:01 | 1.32 |
Annual Sum or Average | 0.123601E+13 | 0.62 | |||
Minimum of Months | 0.745993E+11 | 0.51 | 115649.07 | 1.32 | |
Maximum of Months | 0.148337E+12 | 0.71 | 250364.47 | 1.82 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.104390E+11 | 0.64 | 11160.52 | 14-JAN-05:11 | 1.11 |
February | 0.954822E+10 | 0.65 | 11160.52 | 01-FEB-05:12 | 1.11 |
March | 0.946409E+10 | 0.57 | 16483.56 | 16-MAR-05:01 | 1.30 |
April | 0.780147E+10 | 0.47 | 11160.52 | 03-APR-04:11 | 1.11 |
May | 0.913835E+10 | 0.49 | 16483.56 | 24-MAY-05:02 | 1.30 |
June | 0.119119E+11 | 0.56 | 18063.01 | 26-JUN-05:02 | 1.35 |
July | 0.130777E+11 | 0.56 | 35713.72 | 21-JUL-03:01 | 1.80 |
August | 0.128751E+11 | 0.57 | 19659.27 | 14-AUG-04:11 | 1.39 |
September | 0.924022E+10 | 0.49 | 16483.56 | 14-SEP-05:02 | 1.30 |
October | 0.777757E+10 | 0.46 | 11290.07 | 11-OCT-15:20 | 1.11 |
November | 0.778491E+10 | 0.49 | 11160.52 | 03-NOV-05:01 | 1.11 |
December | 0.101876E+11 | 0.63 | 11160.52 | 21-DEC-06:01 | 1.11 |
Annual Sum or Average | 0.119246E+12 | 0.55 | |||
Minimum of Months | 0.777757E+10 | 0.46 | 11160.52 | 1.11 | |
Maximum of Months | 0.130777E+11 | 0.65 | 35713.72 | 1.80 |
Report: FanReportMonthly
For: CAV_BAS SZVAV FAN
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.307170E+10 | 0.42 | 15571.05 | 02-JAN-06:01 | 1.84 |
February | 0.262486E+10 | 0.42 | 15571.05 | 02-FEB-06:01 | 1.85 |
March | 0.464644E+10 | 0.49 | 15571.05 | 01-MAR-06:01 | 1.85 |
April | 0.615798E+10 | 0.53 | 15571.05 | 01-APR-05:02 | 1.84 |
May | 0.677876E+10 | 0.55 | 15571.05 | 01-MAY-04:11 | 1.84 |
June | 0.707620E+10 | 0.60 | 15571.05 | 01-JUN-04:11 | 1.83 |
July | 0.674721E+10 | 0.57 | 15571.05 | 01-JUL-04:11 | 1.83 |
August | 0.885227E+10 | 0.67 | 15571.05 | 01-AUG-04:11 | 1.83 |
September | 0.897046E+10 | 0.64 | 15571.05 | 01-SEP-04:12 | 1.83 |
October | 0.910626E+10 | 0.61 | 15571.05 | 02-OCT-04:11 | 1.84 |
November | 0.757396E+10 | 0.57 | 15571.05 | 01-NOV-04:11 | 1.85 |
December | 0.418106E+10 | 0.45 | 15571.05 | 01-DEC-05:11 | 1.84 |
Annual Sum or Average | 0.757872E+11 | 0.54 | |||
Minimum of Months | 0.262486E+10 | 0.42 | 15571.05 | 1.83 | |
Maximum of Months | 0.910626E+10 | 0.67 | 15571.05 | 1.85 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SYS11 FAN
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.268133E+11 | 0.52 | 10010.95 | 01-JAN-00:02 | 0.52 |
February | 0.432732E+11 | 0.64 | 33342.59 | 01-FEB-00:03 | 0.87 |
March | 0.611863E+11 | 0.71 | 33342.59 | 01-MAR-00:01 | 0.87 |
April | 0.859728E+11 | 0.87 | 33342.59 | 01-APR-00:10 | 0.87 |
May | 0.268413E+11 | 0.52 | 33342.59 | 31-MAY-23:02 | 0.87 |
June | 0.391576E+11 | 0.60 | 33342.59 | 01-JUN-00:02 | 0.87 |
July | 0.563124E+11 | 0.69 | 33342.59 | 01-JUL-00:01 | 0.87 |
August | 0.795736E+11 | 0.82 | 33342.59 | 01-AUG-00:05 | 0.86 |
September | 0.259764E+11 | 0.52 | 33342.59 | 30-SEP-23:02 | 0.87 |
October | 0.448492E+11 | 0.62 | 33342.59 | 01-OCT-00:01 | 0.87 |
November | 0.615455E+11 | 0.73 | 33342.59 | 01-NOV-00:02 | 0.87 |
December | 0.890116E+11 | 0.87 | 33342.59 | 01-DEC-00:02 | 0.87 |
Annual Sum or Average | 0.640513E+12 | 0.68 | |||
Minimum of Months | 0.259764E+11 | 0.52 | 10010.95 | 0.52 | |
Maximum of Months | 0.890116E+11 | 0.87 | 33342.59 | 0.87 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.350594E+10 | 1.45 | 1308.97 | 01-JAN-01:12 | 1.44 |
February | 0.316665E+10 | 1.45 | 1308.97 | 21-FEB-07:11 | 1.45 |
March | 0.350594E+10 | 1.45 | 1308.97 | 01-MAR-10:28 | 1.45 |
April | 0.339284E+10 | 1.44 | 1308.97 | 01-APR-01:08 | 1.44 |
May | 0.350594E+10 | 1.44 | 1308.97 | 01-MAY-04:40 | 1.44 |
June | 0.339284E+10 | 1.44 | 1308.97 | 10-JUN-19:17 | 1.44 |
July | 0.350594E+10 | 1.43 | 1308.97 | 01-JUL-05:09 | 1.44 |
August | 0.350594E+10 | 1.44 | 1308.97 | 01-AUG-06:08 | 1.44 |
September | 0.339284E+10 | 1.44 | 1308.97 | 04-SEP-09:02 | 1.44 |
October | 0.350594E+10 | 1.44 | 1308.97 | 01-OCT-00:01 | 1.44 |
November | 0.339284E+10 | 1.44 | 1308.97 | 01-NOV-06:56 | 1.44 |
December | 0.350594E+10 | 1.45 | 1308.97 | 01-DEC-08:06 | 1.44 |
Annual Sum or Average | 0.412796E+11 | 1.44 | |||
Minimum of Months | 0.316665E+10 | 1.43 | 1308.97 | 1.44 | |
Maximum of Months | 0.350594E+10 | 1.45 | 1308.97 | 1.45 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.336840E+11 | 1.45 | 12576.16 | 06-JAN-16:30 | 1.45 |
February | 0.304243E+11 | 1.45 | 12576.16 | 01-FEB-06:26 | 1.45 |
March | 0.336840E+11 | 1.45 | 12576.16 | 01-MAR-17:40 | 1.45 |
April | 0.325974E+11 | 1.44 | 12576.16 | 01-APR-06:40 | 1.44 |
May | 0.336840E+11 | 1.44 | 12576.16 | 01-MAY-10:42 | 1.44 |
June | 0.325974E+11 | 1.44 | 12576.16 | 01-JUN-02:21 | 1.44 |
July | 0.336840E+11 | 1.43 | 12576.16 | 01-JUL-14:05 | 1.43 |
August | 0.336840E+11 | 1.44 | 12576.16 | 01-AUG-01:27 | 1.44 |
September | 0.325974E+11 | 1.44 | 12576.16 | 01-SEP-18:03 | 1.44 |
October | 0.336840E+11 | 1.44 | 12576.16 | 03-OCT-06:13 | 1.44 |
November | 0.325974E+11 | 1.44 | 12576.16 | 01-NOV-03:41 | 1.44 |
December | 0.336840E+11 | 1.45 | 12576.16 | 02-DEC-01:28 | 1.44 |
Annual Sum or Average | 0.396602E+12 | 1.44 | |||
Minimum of Months | 0.304243E+11 | 1.43 | 12576.16 | 1.43 | |
Maximum of Months | 0.336840E+11 | 1.45 | 12576.16 | 1.45 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.346891E+10 | 1.45 | 1295.14 | 02-JAN-13:00 | 1.44 |
February | 0.313321E+10 | 1.45 | 1295.14 | 01-FEB-00:03 | 1.45 |
March | 0.346891E+10 | 1.45 | 1295.14 | 01-MAR-00:24 | 1.45 |
April | 0.335701E+10 | 1.44 | 1295.14 | 01-APR-03:51 | 1.44 |
May | 0.346891E+10 | 1.44 | 1295.14 | 01-MAY-04:47 | 1.44 |
June | 0.335701E+10 | 1.44 | 1295.14 | 01-JUN-05:05 | 1.44 |
July | 0.346891E+10 | 1.43 | 1295.14 | 01-JUL-00:41 | 1.44 |
August | 0.346891E+10 | 1.44 | 1295.14 | 01-AUG-01:50 | 1.44 |
September | 0.335701E+10 | 1.44 | 1295.14 | 01-SEP-00:30 | 1.44 |
October | 0.346891E+10 | 1.44 | 1295.14 | 01-OCT-05:01 | 1.44 |
November | 0.335701E+10 | 1.44 | 1295.14 | 01-NOV-10:19 | 1.44 |
December | 0.346891E+10 | 1.45 | 1295.14 | 01-DEC-03:33 | 1.45 |
Annual Sum or Average | 0.408436E+11 | 1.44 | |||
Minimum of Months | 0.313321E+10 | 1.43 | 1295.14 | 1.44 | |
Maximum of Months | 0.346891E+10 | 1.45 | 1295.14 | 1.45 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.795622E+09 | 0.716060E+09 | 5306.17 | 02-JAN-06:01 | 4775.55 | 4775.55 | 54.46 | 22.96 |
February | 0.726510E+09 | 0.653859E+09 | 5286.84 | 27-FEB-06:01 | 4758.15 | 4758.15 | 50.07 | 22.96 |
March | 0.305309E+09 | 0.274778E+09 | 4513.26 | 06-MAR-06:01 | 4061.94 | 4061.94 | 54.84 | 20.90 |
April | 97369768.95 | 87632792.05 | 3307.45 | 05-APR-05:02 | 2976.71 | 2976.71 | 49.75 | 17.16 |
May | 20628649.90 | 18565784.91 | 2209.00 | 08-MAY-05:03 | 1988.10 | 1988.10 | 39.50 | 12.71 |
June | 2623182.11 | 2360863.90 | 701.78 | 14-JUN-05:01 | 631.60 | 631.60 | 28.03 | 4.26 |
July | 161588.22 | 145429.40 | 10.79 | 06-JUL-05:10 | 9.71 | 9.71 | 21.53 | 0.06 |
August | 1028949.48 | 926054.53 | 77.01 | 31-AUG-05:24 | 69.31 | 69.31 | 20.44 | 0.45 |
September | 13112544.45 | 11801290.01 | 1286.80 | 30-SEP-05:03 | 1158.12 | 1158.12 | 33.36 | 7.82 |
October | 87407850.80 | 78667065.72 | 3401.83 | 30-OCT-05:01 | 3061.64 | 3061.64 | 46.73 | 17.52 |
November | 0.194568E+09 | 0.175111E+09 | 3397.55 | 29-NOV-06:01 | 3057.79 | 3057.79 | 44.78 | 17.52 |
December | 0.675736E+09 | 0.608163E+09 | 5299.11 | 04-DEC-06:01 | 4769.20 | 4769.20 | 52.86 | 22.96 |
Annual Sum or Average | 0.292008E+10 | 0.262807E+10 | ||||||
Minimum of Months | 161588.22 | 145429.40 | 10.79 | 9.71 | 9.71 | 20.44 | 0.06 | |
Maximum of Months | 0.795622E+09 | 0.716060E+09 | 5306.17 | 4775.55 | 4775.55 | 54.84 | 22.96 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12609880.59 | 11348892.53 | 557.50 | 23-JAN-06:01 | 501.75 | 501.75 | 6.82 | 4.81 |
February | 0.140636E+10 | 0.126573E+10 | 2340.08 | 17-FEB-14:42 | 2106.07 | 2106.07 | 9.88 | 20.91 |
March | 0.290354E+10 | 0.261318E+10 | 9539.94 | 16-MAR-04:11 | 8585.95 | 8585.95 | 9.97 | 72.06 |
April | 0.255851E+10 | 0.230266E+10 | 3768.74 | 27-APR-13:23 | 3391.87 | 3391.87 | 9.80 | 33.57 |
May | 0.128764E+10 | 0.115888E+10 | 19221.98 | 24-MAY-05:02 | 17299.79 | 17299.79 | 10.09 | 108.32 |
June | 0.499440E+10 | 0.449496E+10 | 24127.06 | 30-JUN-05:01 | 21714.35 | 21714.35 | 9.45 | 121.07 |
July | 0.718575E+10 | 0.646718E+10 | 25582.44 | 22-JUL-04:11 | 23024.20 | 23024.20 | 10.43 | 124.43 |
August | 0.752009E+10 | 0.676808E+10 | 26008.62 | 14-AUG-04:11 | 23407.76 | 23407.76 | 10.16 | 125.41 |
September | 0.257421E+10 | 0.231679E+10 | 19756.42 | 16-SEP-05:02 | 17780.78 | 17780.78 | 9.50 | 109.84 |
October | 0.209830E+10 | 0.188847E+10 | 6733.42 | 11-OCT-14:40 | 6060.08 | 6060.08 | 6.73 | 55.90 |
November | 0.265794E+10 | 0.239215E+10 | 4641.09 | 16-NOV-14:40 | 4176.98 | 4176.98 | 9.34 | 40.76 |
December | 0.263160E+10 | 0.236844E+10 | 2532.60 | 01-DEC-11:00 | 2279.34 | 2279.34 | 9.79 | 22.66 |
Annual Sum or Average | 0.378310E+11 | 0.340479E+11 | ||||||
Minimum of Months | 12609880.59 | 11348892.53 | 557.50 | 501.75 | 501.75 | 6.73 | 4.81 | |
Maximum of Months | 0.752009E+10 | 0.676808E+10 | 26008.62 | 23407.76 | 23407.76 | 10.43 | 125.41 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.388273E+10 | 0.349446E+10 | 11929.02 | 01-JAN-00:08 | 10736.12 | 10736.12 | 6.73 | 62.71 |
February | 0.882003E+10 | 0.793803E+10 | 11929.02 | 01-FEB-00:03 | 10736.12 | 10736.12 | 6.93 | 62.71 |
March | 0.294115E+11 | 0.264703E+11 | 11929.02 | 01-MAR-00:03 | 10736.12 | 10736.12 | 7.77 | 62.71 |
April | 0.239158E+11 | 0.215242E+11 | 11929.02 | 01-APR-00:10 | 10736.12 | 10736.12 | 9.73 | 62.71 |
May | 0.114225E+11 | 0.102803E+11 | 11929.02 | 01-MAY-07:04 | 10736.12 | 10736.12 | 8.36 | 62.71 |
June | 0.219688E+11 | 0.197720E+11 | 11929.02 | 01-JUN-00:05 | 10736.12 | 10736.12 | 8.33 | 62.71 |
July | 0.294558E+11 | 0.265102E+11 | 11929.02 | 01-JUL-00:41 | 10736.12 | 10736.12 | 9.97 | 62.71 |
August | 0.302647E+11 | 0.272382E+11 | 11929.02 | 01-AUG-00:05 | 10736.12 | 10736.12 | 10.18 | 62.71 |
September | 0.160584E+11 | 0.144526E+11 | 11929.02 | 01-SEP-00:20 | 10736.12 | 10736.12 | 6.76 | 62.71 |
October | 0.118574E+11 | 0.106716E+11 | 11929.02 | 01-OCT-00:06 | 10736.12 | 10736.12 | 8.28 | 62.71 |
November | 0.275373E+11 | 0.247836E+11 | 11929.02 | 01-NOV-00:02 | 10736.12 | 10736.12 | 7.56 | 62.71 |
December | 0.259957E+11 | 0.233962E+11 | 11929.02 | 01-DEC-00:01 | 10736.12 | 10736.12 | 10.27 | 62.71 |
Annual Sum or Average | 0.240591E+12 | 0.216532E+12 | ||||||
Minimum of Months | 0.388273E+10 | 0.349446E+10 | 11929.02 | 10736.12 | 10736.12 | 6.73 | 62.71 | |
Maximum of Months | 0.302647E+11 | 0.272382E+11 | 11929.02 | 10736.12 | 10736.12 | 10.27 | 62.71 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 6.73 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 6.74 | 0.00 |
March | 0.146727E+09 | 0.132054E+09 | 11929.02 | 14-MAR-12:50 | 10736.12 | 10736.12 | 13.32 | 31.35 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 9.73 | 0.00 |
May | 57259296.81 | 51533367.13 | 11929.02 | 10-MAY-14:30 | 10736.12 | 10736.12 | 13.20 | 31.35 |
June | 0.254531E+10 | 0.229078E+10 | 11929.02 | 01-JUN-14:30 | 10736.12 | 10736.12 | 13.24 | 31.35 |
July | 0.705295E+10 | 0.634765E+10 | 11929.02 | 03-JUL-10:30 | 10736.12 | 10736.12 | 13.46 | 31.35 |
August | 0.629029E+10 | 0.566126E+10 | 11929.02 | 01-AUG-11:30 | 10736.12 | 10736.12 | 13.54 | 31.35 |
September | 0.922113E+09 | 0.829902E+09 | 11929.02 | 08-SEP-13:00 | 10736.12 | 10736.12 | 13.22 | 31.35 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 8.11 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 7.56 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 10.27 | 0.00 |
Annual Sum or Average | 0.170147E+11 | 0.153132E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.73 | 0.00 | |
Maximum of Months | 0.705295E+10 | 0.634765E+10 | 11929.02 | 10736.12 | 10736.12 | 13.54 | 31.35 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 56.88 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 56.84 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 57.00 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 56.88 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 57.15 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:01 | 16.86 | 16.86 | 57.40 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:01 | 16.86 | 16.86 | 57.55 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:01 | 16.86 | 16.86 | 57.55 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.35 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:01 | 16.86 | 16.86 | 57.56 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 57.41 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 57.18 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.84 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.56 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.979117E+10 | 0.881205E+10 | 30709.80 | 18-JAN-07:30 | 27638.82 | 27638.82 | 21.27 | 88.38 |
February | 0.227068E+11 | 0.204361E+11 | 30747.57 | 17-FEB-12:06 | 27672.82 | 27672.82 | 22.98 | 88.38 |
March | 0.758741E+11 | 0.682867E+11 | 61624.51 | 15-MAR-13:05 | 55462.06 | 55462.06 | 25.77 | 176.77 |
April | 0.615379E+11 | 0.553841E+11 | 30776.26 | 25-APR-13:56 | 27698.63 | 27698.63 | 24.27 | 88.38 |
May | 0.294633E+11 | 0.265170E+11 | 61610.12 | 10-MAY-15:40 | 55449.11 | 55449.11 | 25.49 | 176.77 |
June | 0.618579E+11 | 0.556721E+11 | 61815.00 | 27-JUN-12:20 | 55633.50 | 55633.50 | 29.60 | 176.77 |
July | 0.916470E+11 | 0.824823E+11 | 61815.00 | 15-JUL-14:05 | 55633.50 | 55633.50 | 29.92 | 176.77 |
August | 0.927459E+11 | 0.834713E+11 | 61815.00 | 14-AUG-14:05 | 55633.50 | 55633.50 | 29.53 | 176.77 |
September | 0.425912E+11 | 0.383320E+11 | 61751.88 | 15-SEP-12:05 | 55576.69 | 55576.69 | 28.23 | 176.77 |
October | 0.305260E+11 | 0.274734E+11 | 30828.73 | 11-OCT-15:10 | 27745.86 | 27745.86 | 26.41 | 88.38 |
November | 0.705866E+11 | 0.635280E+11 | 30775.76 | 16-NOV-13:06 | 27698.18 | 27698.18 | 24.25 | 88.38 |
December | 0.668161E+11 | 0.601345E+11 | 30755.61 | 19-DEC-11:58 | 27680.05 | 27680.05 | 23.34 | 88.38 |
Annual Sum or Average | 0.656144E+12 | 0.590530E+12 | ||||||
Minimum of Months | 0.979117E+10 | 0.881205E+10 | 30709.80 | 27638.82 | 27638.82 | 21.27 | 88.38 | |
Maximum of Months | 0.927459E+11 | 0.834713E+11 | 61815.00 | 55633.50 | 55633.50 | 29.92 | 176.77 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 31.62 | 31.62 | 303607.81 | 3552217.06 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 37.96 | 37.96 | 301400.08 | 2694990.96 | 18-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 30.26 | 30.26 | 120256.46 | 2938011.79 | 03-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.03 | 23.03 | 37973.82 | 2703693.73 | 06-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 21.20 | 21.20 | 7939.76 | 1736157.88 | 08-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 20.67 | 20.67 | 1072.20 | 725659.79 | 14-JUN-05:01 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 21.75 | 21.75 | 64.70 | 11520.18 | 06-JUL-05:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.84 | 20.84 | 420.34 | 84763.07 | 31-AUG-05:24 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 20.54 | 20.54 | 5259.21 | 1145092.20 | 30-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 21.91 | 21.91 | 32640.00 | 2901026.02 | 17-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 22.56 | 22.56 | 75651.22 | 2861353.16 | 15-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 27.37 | 27.37 | 256874.77 | 2840983.49 | 30-DEC-05:01 |
Annual Sum or Average | 0.00 | 94284.42 | ||||||
Minimum of Months | 0.00 | 0.00 | 20.54 | 20.54 | 64.70 | 11520.18 | ||
Maximum of Months | 0.00 | 0.00 | 37.96 | 37.96 | 303607.81 | 3552217.06 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1683.12 | 118641.66 | 03-JAN-22:02 | 7.15 | 6.70 | 128154.20 | 915902.57 | 15-JAN-13:40 |
February | 68407.43 | 900292.69 | 28-FEB-07:02 | 10.13 | 6.70 | 175380.50 | 806318.59 | 06-FEB-12:12 |
March | 130732.62 | 2115927.20 | 14-MAR-13:10 | 10.73 | 6.70 | 6365.85 | 681511.14 | 01-MAR-04:02 |
April | 103215.55 | 1170703.81 | 25-APR-13:54 | 11.16 | 6.70 | 13755.69 | 891455.24 | 30-APR-24:00 |
May | 125181.05 | 1842524.73 | 10-MAY-15:40 | 10.27 | 6.76 | 230979.28 | 915573.77 | 07-MAY-08:07 |
June | 564252.68 | 2869668.46 | 21-JUN-09:11 | 12.16 | 6.70 | 51601.45 | 881935.19 | 30-JUN-23:11 |
July | 892689.89 | 3367889.57 | 29-JUL-05:05 | 13.11 | 6.70 | 9290.67 | 622622.33 | 01-JUL-00:08 |
August | 837246.80 | 3775322.70 | 15-AUG-05:02 | 13.89 | 7.14 | 4178.93 | 421479.92 | 16-AUG-06:05 |
September | 303609.92 | 2493289.42 | 15-SEP-12:05 | 11.45 | 6.70 | 153271.72 | 915541.74 | 29-SEP-01:40 |
October | 113813.69 | 1689457.95 | 11-OCT-15:10 | 13.13 | 6.70 | 145718.77 | 860378.74 | 13-OCT-07:33 |
November | 101404.73 | 1152828.43 | 16-NOV-14:41 | 11.11 | 6.73 | 7980.39 | 725997.10 | 01-NOV-04:11 |
December | 95095.34 | 866467.50 | 22-DEC-11:20 | 10.00 | 6.70 | 12235.57 | 629603.69 | 19-DEC-09:15 |
Annual Sum or Average | 279944.14 | 77680.97 | ||||||
Minimum of Months | 1683.12 | 118641.66 | 7.15 | 6.70 | 4178.93 | 421479.92 | ||
Maximum of Months | 892689.89 | 3775322.70 | 13.89 | 7.14 | 230979.28 | 915902.57 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 386.91 | 85792.89 | 21-JAN-06:01 | 11.08 | 6.74 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 75593.91 | 438349.25 | 17-FEB-16:53 | 11.70 | 9.99 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 231559.47 | 1925773.85 | 15-MAR-13:50 | 14.86 | 8.66 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 205828.93 | 1059465.75 | 08-APR-13:15 | 16.36 | 7.48 | 0.00 | 0.00 | 01-APR-00:10 |
May | 144164.77 | 5177349.72 | 24-MAY-04:12 | 19.38 | 11.95 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 599369.86 | 4694987.74 | 27-JUN-05:02 | 16.36 | 12.07 | 0.00 | 0.00 | 01-JUN-00:01 |
July | 925330.04 | 4906462.82 | 29-JUL-05:02 | 17.09 | 12.48 | 0.00 | 0.00 | 01-JUL-00:01 |
August | 881869.29 | 4806104.92 | 08-AUG-05:02 | 16.24 | 11.83 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 327240.63 | 4868692.97 | 14-SEP-04:11 | 18.63 | 11.12 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 142130.92 | 1682105.61 | 11-OCT-15:10 | 14.25 | 6.70 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 207016.15 | 1311590.58 | 16-NOV-13:04 | 15.04 | 7.19 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 200237.32 | 552006.47 | 11-DEC-06:11 | 13.00 | 9.57 | 0.00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 330400.92 | 0.00 | ||||||
Minimum of Months | 386.91 | 85792.89 | 11.08 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 925330.04 | 5177349.72 | 19.38 | 12.48 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 57.98 | 57.98 | 15565.49 | 55761.35 | 31-JAN-12:25 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 57.39 | 57.39 | 15883.48 | 55959.12 | 15-FEB-12:48 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 57.39 | 57.39 | 16653.06 | 55779.99 | 01-MAR-12:47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.46 | 57.46 | 14992.81 | 54072.28 | 03-APR-11:56 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.08 | 58.08 | 14631.74 | 51559.82 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 57.74 | 57.74 | 14076.10 | 48364.99 | 01-JUN-11:18 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 57.87 | 57.87 | 12326.76 | 45521.93 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 57.95 | 57.95 | 13253.11 | 44047.86 | 01-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.95 | 57.95 | 12640.60 | 45463.01 | 29-SEP-11:42 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 57.88 | 57.88 | 13239.12 | 48281.29 | 31-OCT-11:54 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 57.75 | 57.75 | 14277.44 | 51375.77 | 30-NOV-12:35 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 57.60 | 57.60 | 14571.55 | 54008.96 | 29-DEC-12:18 |
Annual Sum or Average | 0.00 | 14333.73 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.39 | 57.39 | 12326.76 | 44047.86 | ||
Maximum of Months | 0.00 | 0.00 | 58.08 | 58.08 | 16653.06 | 55959.12 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 219.59 | 62377.80 | 18-JAN-07:30 | 21.27 | 20.52 | 3827.93 | 201604.51 | 25-JAN-04:05 |
February | 40221.47 | 693943.63 | 17-FEB-12:06 | 22.98 | 21.10 | 48.60 | 69294.50 | 02-FEB-06:47 |
March | 81764.48 | 3447539.85 | 15-MAR-13:05 | 25.77 | 21.10 | 5843.69 | 137657.16 | 30-MAR-04:11 |
April | 72211.54 | 1172630.45 | 25-APR-13:56 | 24.27 | 21.10 | 5471.40 | 164300.17 | 14-APR-09:00 |
May | 150839.15 | 3241674.73 | 10-MAY-15:40 | 25.49 | 21.70 | 1440.97 | 149187.01 | 02-MAY-03:10 |
June | 852050.44 | 6897566.68 | 27-JUN-13:00 | 30.44 | 26.66 | 18.32 | 61917.10 | 13-JUN-08:43 |
July | 1623656.15 | 7308848.52 | 20-JUL-14:05 | 30.99 | 26.97 | 37.66 | 37800.25 | 06-JUL-06:20 |
August | 1334747.67 | 6328286.43 | 15-AUG-13:00 | 29.66 | 25.83 | 270.81 | 51275.04 | 18-AUG-01:30 |
September | 424357.19 | 5266624.70 | 15-SEP-12:05 | 28.23 | 24.48 | 697.31 | 104402.98 | 03-SEP-22:20 |
October | 136400.94 | 1960373.89 | 11-OCT-15:10 | 26.41 | 21.10 | 167.91 | 84981.81 | 16-OCT-05:47 |
November | 49327.63 | 1164346.75 | 16-NOV-13:06 | 24.25 | 21.10 | 6508.04 | 146159.06 | 21-NOV-03:57 |
December | 24243.53 | 828165.36 | 19-DEC-11:58 | 23.34 | 21.10 | 9993.91 | 169911.06 | 09-DEC-16:50 |
Annual Sum or Average | 402664.72 | 2880.22 | ||||||
Minimum of Months | 219.59 | 62377.80 | 21.27 | 20.52 | 18.32 | 37800.25 | ||
Maximum of Months | 1623656.15 | 7308848.52 | 30.99 | 26.97 | 9993.91 | 201604.51 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.330253E+11 | 0.00 | 728034.12 | 0.745857E+10 | 0.00 | 0.00 |
February | 0.309787E+11 | 0.00 | 118407.09 | 0.686623E+10 | 0.00 | 0.00 |
March | 0.936711E+10 | 0.00 | 0.709597E+10 | 0.101221E+11 | 0.00 | 0.00 |
April | 0.138841E+10 | 0.00 | 0.293594E+10 | 0.107315E+11 | 0.00 | 0.00 |
May | 0.195777E+09 | 0.00 | 0.244533E+11 | 0.117924E+11 | 0.00 | 0.00 |
June | 5346371.36 | 0.00 | 0.934731E+11 | 0.150972E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.158252E+12 | 0.177725E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.141971E+12 | 0.194391E+11 | 0.00 | 0.00 |
September | 74821499.55 | 0.00 | 0.595005E+11 | 0.130727E+11 | 0.00 | 0.00 |
October | 0.128651E+10 | 0.00 | 0.873537E+10 | 0.106125E+11 | 0.00 | 0.00 |
November | 0.330336E+10 | 0.00 | 0.138038E+10 | 0.934814E+10 | 0.00 | 0.00 |
December | 0.201966E+11 | 0.00 | 8382228.71 | 0.825584E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.998219E+11 | 0.00 | 0.497807E+12 | 0.140569E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 118407.09 | 0.686623E+10 | 0.00 | 0.00 |
Maximum of Months | 0.330253E+11 | 0.00 | 0.158252E+12 | 0.194391E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.671500E+12 | 0.00 | 82960.50 | 0.878283E+11 | 0.00 | 0.00 |
February | 0.600127E+12 | 0.00 | 63452.91 | 0.802218E+11 | 0.00 | 0.00 |
March | 0.260847E+12 | 0.00 | 0.643912E+11 | 0.901053E+11 | 0.00 | 0.00 |
April | 0.765107E+11 | 0.00 | 0.286261E+11 | 0.869761E+11 | 0.00 | 0.00 |
May | 0.150088E+11 | 0.00 | 0.231662E+12 | 0.107914E+12 | 0.00 | 0.00 |
June | 0.151290E+10 | 0.00 | 0.835483E+12 | 0.132954E+12 | 0.00 | 0.00 |
July | 2071219.57 | 0.00 | 0.132680E+13 | 0.142967E+12 | 0.00 | 0.00 |
August | 0.439600E+09 | 0.00 | 0.113584E+13 | 0.148337E+12 | 0.00 | 0.00 |
September | 0.932018E+10 | 0.00 | 0.529400E+12 | 0.113093E+12 | 0.00 | 0.00 |
October | 0.664357E+11 | 0.00 | 0.964522E+11 | 0.879304E+11 | 0.00 | 0.00 |
November | 0.154238E+12 | 0.00 | 0.159446E+11 | 0.745993E+11 | 0.00 | 0.00 |
December | 0.567612E+12 | 0.00 | 23839953.82 | 0.830808E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.242355E+13 | 0.00 | 0.426462E+13 | 0.123601E+13 | 0.00 | 0.00 |
Minimum of Months | 2071219.57 | 0.00 | 63452.91 | 0.745993E+11 | 0.00 | 0.00 |
Maximum of Months | 0.671500E+12 | 0.00 | 0.132680E+13 | 0.148337E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.113059E+12 | 0.00 | 6777671.26 | 0.104390E+11 | 0.00 | 0.00 |
February | 0.102164E+12 | 0.00 | 5000413.77 | 0.954822E+10 | 0.00 | 0.00 |
March | 0.536944E+11 | 0.00 | 0.630187E+10 | 0.946409E+10 | 0.00 | 0.00 |
April | 0.209803E+11 | 0.00 | 0.232517E+10 | 0.780147E+10 | 0.00 | 0.00 |
May | 0.614600E+10 | 0.00 | 0.245202E+11 | 0.913835E+10 | 0.00 | 0.00 |
June | 0.125784E+10 | 0.00 | 0.951468E+11 | 0.119119E+11 | 0.00 | 0.00 |
July | 0.180255E+09 | 0.00 | 0.152692E+12 | 0.130777E+11 | 0.00 | 0.00 |
August | 0.693592E+09 | 0.00 | 0.127072E+12 | 0.128751E+11 | 0.00 | 0.00 |
September | 0.426460E+10 | 0.00 | 0.543672E+11 | 0.924022E+10 | 0.00 | 0.00 |
October | 0.200275E+11 | 0.00 | 0.663799E+10 | 0.777757E+10 | 0.00 | 0.00 |
November | 0.392848E+11 | 0.00 | 0.110255E+10 | 0.778491E+10 | 0.00 | 0.00 |
December | 0.103795E+12 | 0.00 | 12406924.68 | 0.101876E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.465547E+12 | 0.00 | 0.470189E+12 | 0.119246E+12 | 0.00 | 0.00 |
Minimum of Months | 0.180255E+09 | 0.00 | 5000413.77 | 0.777757E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113059E+12 | 0.00 | 0.152692E+12 | 0.130777E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.108477E+10 | 0.307170E+10 | 0.00 | 0.00 |
February | 50484106.80 | 0.00 | 0.252618E+09 | 0.262486E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.607925E+10 | 0.464644E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.690275E+10 | 0.615798E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.205594E+11 | 0.677876E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.529069E+11 | 0.707620E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.814381E+11 | 0.674721E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.774254E+11 | 0.885227E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.455623E+11 | 0.897046E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.164038E+11 | 0.910626E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.790609E+10 | 0.757396E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.251648E+10 | 0.418106E+10 | 0.00 | 0.00 |
Annual Sum or Average | 50484106.80 | 0.00 | 0.319038E+12 | 0.757872E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.252618E+09 | 0.262486E+10 | 0.00 | 0.00 |
Maximum of Months | 50484106.80 | 0.00 | 0.814381E+11 | 0.910626E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 2990644.88 | 0.130399E+12 | 0.00 | 38.53 |
February | 0.00 | 0.00 | 0.156290E+12 | 0.149023E+12 | 0.00 | 39.34 |
March | 0.00 | 0.00 | 0.228962E+12 | 0.202416E+12 | 0.00 | 52.54 |
April | 0.00 | 0.00 | 0.203353E+12 | 0.243216E+12 | 0.00 | 58.49 |
May | 0.00 | 0.00 | 0.159683E+11 | 0.851412E+11 | 0.00 | 21.69 |
June | 0.00 | 0.00 | 0.315577E+12 | 0.573122E+11 | 0.00 | 6.75 |
July | 0.00 | 0.00 | 0.537874E+12 | 0.575977E+11 | 0.00 | 0.48 |
August | 0.00 | 0.00 | 0.637019E+12 | 0.807688E+11 | 0.00 | 0.44 |
September | 0.00 | 0.00 | 0.439237E+11 | 0.338479E+11 | 0.00 | 2.93 |
October | 0.00 | 0.00 | 0.162603E+12 | 0.994947E+11 | 0.00 | 20.33 |
November | 0.00 | 0.00 | 0.210075E+12 | 0.194116E+12 | 0.00 | 49.32 |
December | 0.00 | 0.00 | 0.226767E+12 | 0.314449E+12 | 0.00 | 83.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.273842E+13 | 0.164778E+13 | 0.00 | 374.70 |
Minimum of Months | 0.00 | 0.00 | 2990644.88 | 0.338479E+11 | 0.00 | 0.44 |
Maximum of Months | 0.00 | 0.00 | 0.637019E+12 | 0.314449E+12 | 0.00 | 83.86 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.497059E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.567347E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.775739E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.891720E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.572723E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.693389E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.843401E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.980149E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.565171E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.681364E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.755366E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.879251E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.870268E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.497059E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.980149E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.398125E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.472029E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.662018E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.756492E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.505474E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.611602E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.737098E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.846008E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.496122E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.586611E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.642360E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.719896E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.743384E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.398125E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.846008E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.379399E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.459240E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.688030E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.804453E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.524945E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.666580E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.817362E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.936083E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.516507E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.596371E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.660028E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.748628E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.779763E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.379399E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.936083E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.745857E+10 | 728034.12 | 0.330253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.686623E+10 | 118407.09 | 0.309787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101221E+11 | 0.709597E+10 | 0.936711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107315E+11 | 0.293594E+10 | 0.138841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117924E+11 | 0.244533E+11 | 0.195777E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150972E+11 | 0.934731E+11 | 5346371.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.177725E+11 | 0.158252E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.194391E+11 | 0.141971E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130727E+11 | 0.595005E+11 | 74821499.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106125E+11 | 0.873537E+10 | 0.128651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.934814E+10 | 0.138038E+10 | 0.330336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.825584E+10 | 8382228.71 | 0.201966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140569E+12 | 0.497807E+12 | 0.998219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.686623E+10 | 118407.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.194391E+11 | 0.158252E+12 | 0.330253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.878283E+11 | 82960.50 | 0.671500E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.802218E+11 | 63452.91 | 0.600127E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.901053E+11 | 0.643912E+11 | 0.260847E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.869761E+11 | 0.286261E+11 | 0.765107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107914E+12 | 0.231662E+12 | 0.150088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132954E+12 | 0.835483E+12 | 0.151290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142967E+12 | 0.132680E+13 | 2071219.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148337E+12 | 0.113584E+13 | 0.439600E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113093E+12 | 0.529400E+12 | 0.932018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.879304E+11 | 0.964522E+11 | 0.664357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.745993E+11 | 0.159446E+11 | 0.154238E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.830808E+11 | 23839953.82 | 0.567612E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123601E+13 | 0.426462E+13 | 0.242355E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.745993E+11 | 63452.91 | 2071219.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.148337E+12 | 0.132680E+13 | 0.671500E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.104390E+11 | 6777671.26 | 0.113059E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.954822E+10 | 5000413.77 | 0.102164E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.946409E+10 | 0.630187E+10 | 0.536944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.780147E+10 | 0.232517E+10 | 0.209803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.913835E+10 | 0.245202E+11 | 0.614600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119119E+11 | 0.951468E+11 | 0.125784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.130777E+11 | 0.152692E+12 | 0.180255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.128751E+11 | 0.127072E+12 | 0.693592E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.924022E+10 | 0.543672E+11 | 0.426460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.777757E+10 | 0.663799E+10 | 0.200275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.778491E+10 | 0.110255E+10 | 0.392848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101876E+11 | 12406924.68 | 0.103795E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119246E+12 | 0.470189E+12 | 0.465547E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.777757E+10 | 5000413.77 | 0.180255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130777E+11 | 0.152692E+12 | 0.113059E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.307170E+10 | 0.108477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.262486E+10 | 0.252618E+09 | 50484106.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.464644E+10 | 0.607925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.615798E+10 | 0.690275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.677876E+10 | 0.205594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.707620E+10 | 0.529069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.674721E+10 | 0.814381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.885227E+10 | 0.774254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.897046E+10 | 0.455623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.910626E+10 | 0.164038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.757396E+10 | 0.790609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.418106E+10 | 0.251648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.757872E+11 | 0.319038E+12 | 50484106.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.262486E+10 | 0.252618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.910626E+10 | 0.814381E+11 | 50484106.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.268133E+11 | 2990644.88 | 0.00 | 0.00 | 0.00 | 0.103122E+12 | 0.00 | 0.00 |
February | 0.432732E+11 | 0.156290E+12 | 0.00 | 0.00 | 0.00 | 0.105276E+12 | 0.00 | 0.00 |
March | 0.611863E+11 | 0.228962E+12 | 0.00 | 0.00 | 0.00 | 0.140597E+12 | 0.00 | 0.00 |
April | 0.859728E+11 | 0.203353E+12 | 0.00 | 0.00 | 0.00 | 0.156539E+12 | 0.00 | 0.00 |
May | 0.268413E+11 | 0.159683E+11 | 0.00 | 0.00 | 0.00 | 0.580386E+11 | 0.00 | 0.00 |
June | 0.391576E+11 | 0.315577E+12 | 0.00 | 0.00 | 0.00 | 0.180732E+11 | 0.00 | 0.00 |
July | 0.563124E+11 | 0.537874E+12 | 0.00 | 0.00 | 0.00 | 0.127951E+10 | 0.00 | 0.00 |
August | 0.795736E+11 | 0.637019E+12 | 0.00 | 0.00 | 0.00 | 0.118992E+10 | 0.00 | 0.00 |
September | 0.259764E+11 | 0.439237E+11 | 0.00 | 0.00 | 0.00 | 0.783621E+10 | 0.00 | 0.00 |
October | 0.448492E+11 | 0.162603E+12 | 0.00 | 0.00 | 0.00 | 0.544006E+11 | 0.00 | 0.00 |
November | 0.615455E+11 | 0.210075E+12 | 0.00 | 0.00 | 0.00 | 0.131976E+12 | 0.00 | 0.00 |
December | 0.890116E+11 | 0.226767E+12 | 0.00 | 0.00 | 0.00 | 0.224427E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.640513E+12 | 0.273842E+13 | 0.00 | 0.00 | 0.00 | 0.100275E+13 | 0.00 | 0.00 |
Minimum of Months | 0.259764E+11 | 2990644.88 | 0.00 | 0.00 | 0.00 | 0.118992E+10 | 0.00 | 0.00 |
Maximum of Months | 0.890116E+11 | 0.637019E+12 | 0.00 | 0.00 | 0.00 | 0.224427E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.350594E+10 | 0.470831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.316665E+10 | 0.873912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.350594E+10 | 0.162489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.339284E+10 | 0.212421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.350594E+10 | 0.740049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.339284E+10 | 0.126878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.350594E+10 | 0.186362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.350594E+10 | 0.235399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.339284E+10 | 0.755055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.350594E+10 | 0.117972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.339284E+10 | 0.159095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.350594E+10 | 0.205011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.412796E+11 | 0.168961E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.316665E+10 | 0.470831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.350594E+10 | 0.235399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.336840E+11 | 0.223573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.304243E+11 | 0.662931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.336840E+11 | 0.142234E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.325974E+11 | 0.194112E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.336840E+11 | 0.649464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.325974E+11 | 0.118870E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.336840E+11 | 0.176061E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.336840E+11 | 0.222458E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.325974E+11 | 0.656522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336840E+11 | 0.102249E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.325974E+11 | 0.138060E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.336840E+11 | 0.173960E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.396602E+12 | 0.148725E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.304243E+11 | 0.223573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.336840E+11 | 0.222458E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.346891E+10 | 0.100599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.313321E+10 | 0.482452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.346891E+10 | 0.124367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.335701E+10 | 0.181238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.346891E+10 | 0.582349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.335701E+10 | 0.117175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.346891E+10 | 0.176261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.346891E+10 | 0.221314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.335701E+10 | 0.591995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.346891E+10 | 0.854664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.335701E+10 | 0.117171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.346891E+10 | 0.152433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.408436E+11 | 0.135116E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.313321E+10 | 0.100599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.346891E+10 | 0.221314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.745857E+10 | 0.330253E+11 | 728034.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.686623E+10 | 0.309787E+11 | 118407.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101221E+11 | 0.936711E+10 | 0.709597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107315E+11 | 0.138841E+10 | 0.293594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117924E+11 | 0.195777E+09 | 0.244533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150972E+11 | 5346371.36 | 0.934731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.177725E+11 | 0.00 | 0.158252E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.194391E+11 | 0.00 | 0.141971E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130727E+11 | 74821499.55 | 0.595005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106125E+11 | 0.128651E+10 | 0.873537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.934814E+10 | 0.330336E+10 | 0.138038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.825584E+10 | 0.201966E+11 | 8382228.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140569E+12 | 0.998219E+11 | 0.497807E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.686623E+10 | 0.00 | 118407.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.194391E+11 | 0.330253E+11 | 0.158252E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.878283E+11 | 0.671500E+12 | 82960.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.802218E+11 | 0.600127E+12 | 63452.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.901053E+11 | 0.260847E+12 | 0.643912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.869761E+11 | 0.765107E+11 | 0.286261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107914E+12 | 0.150088E+11 | 0.231662E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132954E+12 | 0.151290E+10 | 0.835483E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142967E+12 | 2071219.57 | 0.132680E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148337E+12 | 0.439600E+09 | 0.113584E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113093E+12 | 0.932018E+10 | 0.529400E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.879304E+11 | 0.664357E+11 | 0.964522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.745993E+11 | 0.154238E+12 | 0.159446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.830808E+11 | 0.567612E+12 | 23839953.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123601E+13 | 0.242355E+13 | 0.426462E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.745993E+11 | 2071219.57 | 63452.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.148337E+12 | 0.671500E+12 | 0.132680E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.104390E+11 | 0.113059E+12 | 6777671.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.954822E+10 | 0.102164E+12 | 5000413.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.946409E+10 | 0.536944E+11 | 0.630187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.780147E+10 | 0.209803E+11 | 0.232517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.913835E+10 | 0.614600E+10 | 0.245202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119119E+11 | 0.125784E+10 | 0.951468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.130777E+11 | 0.180255E+09 | 0.152692E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.128751E+11 | 0.693592E+09 | 0.127072E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.924022E+10 | 0.426460E+10 | 0.543672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.777757E+10 | 0.200275E+11 | 0.663799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.778491E+10 | 0.392848E+11 | 0.110255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101876E+11 | 0.103795E+12 | 12406924.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119246E+12 | 0.465547E+12 | 0.470189E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.777757E+10 | 0.180255E+09 | 5000413.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130777E+11 | 0.113059E+12 | 0.152692E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.307170E+10 | 0.00 | 0.108477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.262486E+10 | 50484106.80 | 0.252618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.464644E+10 | 0.00 | 0.607925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.615798E+10 | 0.00 | 0.690275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.677876E+10 | 0.00 | 0.205594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.707620E+10 | 0.00 | 0.529069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.674721E+10 | 0.00 | 0.814381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.885227E+10 | 0.00 | 0.774254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.897046E+10 | 0.00 | 0.455623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.910626E+10 | 0.00 | 0.164038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.757396E+10 | 0.00 | 0.790609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.418106E+10 | 0.00 | 0.251648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.757872E+11 | 50484106.80 | 0.319038E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.262486E+10 | 0.00 | 0.252618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.910626E+10 | 50484106.80 | 0.814381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.268133E+11 | 0.00 | 2990644.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103586E+12 | 0.00 | 0.00 | 0.00 |
February | 0.432732E+11 | 0.00 | 0.156290E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105750E+12 | 0.00 | 0.00 | 0.00 |
March | 0.611863E+11 | 0.00 | 0.228962E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141230E+12 | 0.00 | 0.00 | 0.00 |
April | 0.859728E+11 | 0.00 | 0.203353E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157243E+12 | 0.00 | 0.00 | 0.00 |
May | 0.268413E+11 | 0.00 | 0.159683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582998E+11 | 0.00 | 0.00 | 0.00 |
June | 0.391576E+11 | 0.00 | 0.315577E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181545E+11 | 0.00 | 0.00 | 0.00 |
July | 0.563124E+11 | 0.00 | 0.537874E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128527E+10 | 0.00 | 0.00 | 0.00 |
August | 0.795736E+11 | 0.00 | 0.637019E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119527E+10 | 0.00 | 0.00 | 0.00 |
September | 0.259764E+11 | 0.00 | 0.439237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787148E+10 | 0.00 | 0.00 | 0.00 |
October | 0.448492E+11 | 0.00 | 0.162603E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546455E+11 | 0.00 | 0.00 | 0.00 |
November | 0.615455E+11 | 0.00 | 0.210075E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132570E+12 | 0.00 | 0.00 | 0.00 |
December | 0.890116E+11 | 0.00 | 0.226767E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225437E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.640513E+12 | 0.00 | 0.273842E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100727E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.259764E+11 | 0.00 | 2990644.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119527E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.890116E+11 | 0.00 | 0.637019E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225437E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.350594E+10 | 0.00 | 0.00 | 0.00 | 0.146465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.316665E+10 | 0.00 | 0.00 | 0.00 | 0.250682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.350594E+10 | 0.00 | 0.00 | 0.00 | 0.425145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.339284E+10 | 0.00 | 0.00 | 0.00 | 0.552436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.350594E+10 | 0.00 | 0.00 | 0.00 | 0.222129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.339284E+10 | 0.00 | 0.00 | 0.00 | 0.354105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.350594E+10 | 0.00 | 0.00 | 0.00 | 0.492808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.350594E+10 | 0.00 | 0.00 | 0.00 | 0.629555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.339284E+10 | 0.00 | 0.00 | 0.00 | 0.225887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.350594E+10 | 0.00 | 0.00 | 0.00 | 0.330771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.339284E+10 | 0.00 | 0.00 | 0.00 | 0.416081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.350594E+10 | 0.00 | 0.00 | 0.00 | 0.528658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.412796E+11 | 0.00 | 0.00 | 0.00 | 0.457472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.316665E+10 | 0.00 | 0.00 | 0.00 | 0.146465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.350594E+10 | 0.00 | 0.00 | 0.00 | 0.629555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.336840E+11 | 0.00 | 0.00 | 0.00 | 0.612855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.304243E+11 | 0.00 | 0.00 | 0.00 | 0.167786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.336840E+11 | 0.00 | 0.00 | 0.00 | 0.325178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.325974E+11 | 0.00 | 0.00 | 0.00 | 0.430518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.336840E+11 | 0.00 | 0.00 | 0.00 | 0.168634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.325974E+11 | 0.00 | 0.00 | 0.00 | 0.285628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.336840E+11 | 0.00 | 0.00 | 0.00 | 0.400258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.336840E+11 | 0.00 | 0.00 | 0.00 | 0.509168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.325974E+11 | 0.00 | 0.00 | 0.00 | 0.170148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336840E+11 | 0.00 | 0.00 | 0.00 | 0.249771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.325974E+11 | 0.00 | 0.00 | 0.00 | 0.316386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.336840E+11 | 0.00 | 0.00 | 0.00 | 0.383056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.396602E+12 | 0.00 | 0.00 | 0.00 | 0.346782E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.304243E+11 | 0.00 | 0.00 | 0.00 | 0.612855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.336840E+11 | 0.00 | 0.00 | 0.00 | 0.509168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.346891E+10 | 0.00 | 0.00 | 0.00 | 0.325080E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.313321E+10 | 0.00 | 0.00 | 0.00 | 0.145919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.346891E+10 | 0.00 | 0.00 | 0.00 | 0.341139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.335701E+10 | 0.00 | 0.00 | 0.00 | 0.468752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.346891E+10 | 0.00 | 0.00 | 0.00 | 0.178055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.335701E+10 | 0.00 | 0.00 | 0.00 | 0.330880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.346891E+10 | 0.00 | 0.00 | 0.00 | 0.470471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.346891E+10 | 0.00 | 0.00 | 0.00 | 0.589192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.335701E+10 | 0.00 | 0.00 | 0.00 | 0.180806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.346891E+10 | 0.00 | 0.00 | 0.00 | 0.249480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.335701E+10 | 0.00 | 0.00 | 0.00 | 0.324327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.346891E+10 | 0.00 | 0.00 | 0.00 | 0.401738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.408436E+11 | 0.00 | 0.00 | 0.00 | 0.371326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.313321E+10 | 0.00 | 0.00 | 0.00 | 0.325080E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.346891E+10 | 0.00 | 0.00 | 0.00 | 0.589192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.341030E+11 | 0.00 | 0.00 | 26209558.56 | 0.00 | 0.00 | 0.225980E+11 | 0.00 | 0.34 |
February | 0.462950E+11 | 0.00 | 0.00 | 35820032.34 | 0.00 | 0.00 | 0.410338E+10 | 0.00 | 0.33 |
March | 0.313140E+11 | 30770050.86 | 0.00 | 0.165248E+09 | 0.00 | 0.00 | 0.229013E+11 | 0.00 | 0.46 |
April | 0.105022E+11 | 0.00 | 0.00 | 0.145887E+09 | 0.00 | 0.00 | 0.425434E+11 | 0.00 | 0.59 |
May | 0.442812E+10 | 56649221.26 | 0.00 | 0.106560E+09 | 0.00 | 0.00 | 0.386564E+11 | 0.00 | 0.72 |
June | 0.215511E+10 | 0.661402E+10 | 0.00 | 0.302078E+09 | 74852290.04 | 0.00 | 0.221764E+11 | 0.00 | 0.75 |
July | 0.176196E+09 | 0.164750E+11 | 0.00 | 0.109491E+09 | 0.193921E+09 | 0.00 | 0.774996E+10 | 0.00 | 0.52 |
August | 0.493075E+09 | 0.981258E+10 | 0.00 | 0.113685E+09 | 63519898.19 | 0.00 | 0.176029E+11 | 0.00 | 0.74 |
September | 0.193752E+10 | 0.374254E+10 | 0.00 | 0.126087E+09 | 39809164.71 | 0.00 | 0.340515E+11 | 0.00 | 0.91 |
October | 0.105167E+11 | 0.00 | 0.00 | 0.393984E+09 | 0.00 | 0.00 | 0.507453E+11 | 0.00 | 0.81 |
November | 0.148130E+11 | 0.00 | 0.00 | 0.348539E+09 | 0.00 | 0.00 | 0.483754E+11 | 0.00 | 0.63 |
December | 0.288710E+11 | 0.00 | 0.00 | 96057202.76 | 0.00 | 0.00 | 0.313179E+11 | 0.00 | 0.39 |
Annual Sum or Average | 0.185605E+12 | 0.367316E+11 | 0.00 | 0.196965E+10 | 0.372103E+09 | 0.00 | 0.342822E+12 | 0.00 | 0.60 |
Minimum of Months | 0.176196E+09 | 0.00 | 0.00 | 26209558.56 | 0.00 | 0.00 | 0.410338E+10 | 0.00 | 0.33 |
Maximum of Months | 0.462950E+11 | 0.164750E+11 | 0.00 | 0.393984E+09 | 0.193921E+09 | 0.00 | 0.507453E+11 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.204856E+11 | 0.00 | 0.00 | 48745028.24 | 0.00 | 0.00 | 0.268219E+11 | 0.00 | 0.28 |
February | 0.260823E+11 | 0.00 | 0.00 | 0.211673E+09 | 0.00 | 0.00 | 0.168600E+11 | 0.00 | 0.28 |
March | 0.155987E+11 | 0.00 | 0.00 | 0.472315E+09 | 0.00 | 0.00 | 0.383664E+11 | 0.00 | 0.47 |
April | 0.733121E+10 | 0.00 | 0.00 | 0.277010E+09 | 0.00 | 0.00 | 0.512388E+11 | 0.00 | 0.68 |
May | 0.463863E+10 | 5024903.79 | 0.00 | 0.171577E+09 | 3344940.76 | 0.00 | 0.478677E+11 | 0.00 | 0.85 |
June | 0.223511E+10 | 0.244235E+10 | 0.00 | 0.395303E+09 | 68821627.28 | 0.00 | 0.274494E+11 | 0.00 | 0.78 |
July | 0.157171E+10 | 0.792674E+10 | 0.00 | 0.116828E+09 | 0.257594E+09 | 0.00 | 0.843479E+10 | 0.00 | 0.48 |
August | 0.241943E+10 | 0.382782E+10 | 0.00 | 0.131656E+09 | 0.119514E+09 | 0.00 | 0.198770E+11 | 0.00 | 0.73 |
September | 0.369893E+10 | 0.129381E+10 | 0.00 | 0.136515E+09 | 25451550.52 | 0.00 | 0.348202E+11 | 0.00 | 0.85 |
October | 0.795918E+10 | 0.00 | 0.00 | 0.481467E+09 | 0.00 | 0.00 | 0.477305E+11 | 0.00 | 0.71 |
November | 0.894356E+10 | 0.00 | 0.00 | 0.495569E+09 | 797509.20 | 0.00 | 0.445182E+11 | 0.00 | 0.53 |
December | 0.161407E+11 | 0.00 | 0.00 | 0.179214E+09 | 0.00 | 0.00 | 0.336301E+11 | 0.00 | 0.32 |
Annual Sum or Average | 0.117105E+12 | 0.154957E+11 | 0.00 | 0.311787E+10 | 0.475524E+09 | 0.00 | 0.397615E+12 | 0.00 | 0.58 |
Minimum of Months | 0.157171E+10 | 0.00 | 0.00 | 48745028.24 | 0.00 | 0.00 | 0.843479E+10 | 0.00 | 0.28 |
Maximum of Months | 0.260823E+11 | 0.792674E+10 | 0.00 | 0.495569E+09 | 0.257594E+09 | 0.00 | 0.512388E+11 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.367615E+12 | 0.00 | 0.00 | 70663577.16 | 0.00 | 0.740129E+10 | 0.607810E+11 | 0.00 | 0.27 |
February | 0.372902E+12 | 0.00 | 0.00 | 0.301469E+09 | 0.00 | 0.644841E+10 | 0.261903E+11 | 0.00 | 0.28 |
March | 0.258540E+12 | 0.00 | 0.00 | 0.199968E+10 | 0.00 | 0.520730E+09 | 0.161645E+12 | 0.00 | 0.37 |
April | 0.156448E+12 | 0.00 | 0.00 | 0.145682E+10 | 0.00 | 0.00 | 0.260242E+12 | 0.00 | 0.50 |
May | 0.753349E+11 | 17841599.24 | 0.00 | 0.131865E+10 | 38711742.59 | 0.00 | 0.356859E+12 | 0.00 | 0.73 |
June | 0.537173E+11 | 0.220924E+11 | 0.00 | 0.272383E+10 | 0.205406E+10 | 0.00 | 0.191039E+12 | 0.00 | 0.68 |
July | 0.164551E+11 | 0.729741E+11 | 0.00 | 0.692362E+09 | 0.271871E+10 | 0.00 | 0.558090E+11 | 0.00 | 0.39 |
August | 0.178355E+11 | 0.345483E+11 | 0.00 | 0.891931E+09 | 0.955963E+09 | 0.00 | 0.139718E+12 | 0.00 | 0.55 |
September | 0.719098E+11 | 0.121564E+11 | 0.00 | 0.842675E+09 | 0.356582E+09 | 0.00 | 0.226890E+12 | 0.00 | 0.71 |
October | 0.144849E+12 | 0.00 | 0.00 | 0.262917E+10 | 0.00 | 0.00 | 0.250506E+12 | 0.00 | 0.52 |
November | 0.176051E+12 | 0.00 | 0.00 | 0.219179E+10 | 24658419.70 | 0.00 | 0.185198E+12 | 0.00 | 0.37 |
December | 0.358071E+12 | 0.00 | 0.00 | 0.230135E+09 | 0.00 | 0.410902E+10 | 0.544016E+11 | 0.00 | 0.28 |
Annual Sum or Average | 0.206973E+13 | 0.141789E+12 | 0.00 | 0.153492E+11 | 0.614869E+10 | 0.184794E+11 | 0.196928E+13 | 0.00 | 0.47 |
Minimum of Months | 0.164551E+11 | 0.00 | 0.00 | 70663577.16 | 0.00 | 0.00 | 0.261903E+11 | 0.00 | 0.27 |
Maximum of Months | 0.372902E+12 | 0.729741E+11 | 0.00 | 0.272383E+10 | 0.271871E+10 | 0.740129E+10 | 0.356859E+12 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.281593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601991E+10 | 0.00 | 0.00 | 0.23 |
February | 0.264485E+11 | 0.00 | 0.00 | 0.00 | 51261.82 | 0.563813E+10 | 0.00 | 118832.92 | 0.24 |
March | 0.291273E+11 | 0.00 | 0.00 | 31936009.48 | 0.00 | 0.235112E+10 | 0.293415E+10 | 0.00 | 0.33 |
April | 0.239341E+11 | 0.00 | 0.00 | 47993637.12 | 0.00 | 0.421953E+09 | 0.106626E+11 | 0.00 | 0.44 |
May | 0.153128E+11 | 6107656.38 | 0.00 | 81441479.05 | 4005523.67 | 29499688.90 | 0.240894E+11 | 0.00 | 0.67 |
June | 0.728037E+10 | 0.174152E+10 | 0.00 | 0.224142E+09 | 0.244377E+09 | 0.00 | 0.168273E+11 | 0.00 | 0.65 |
July | 0.213889E+10 | 0.614903E+10 | 0.00 | 41929534.97 | 0.688171E+09 | 0.00 | 0.401175E+10 | 0.00 | 0.37 |
August | 0.392375E+10 | 0.289111E+10 | 0.00 | 66076639.70 | 0.253815E+09 | 0.00 | 0.938833E+10 | 0.00 | 0.50 |
September | 0.115406E+11 | 0.894393E+09 | 0.00 | 43210420.18 | 0.182699E+09 | 0.00 | 0.134883E+11 | 0.00 | 0.63 |
October | 0.229964E+11 | 0.00 | 0.00 | 63333976.19 | 0.00 | 0.557549E+09 | 0.752711E+10 | 0.00 | 0.45 |
November | 0.250930E+11 | 0.00 | 5492087.87 | 5321947.49 | 23114401.95 | 0.147965E+10 | 0.532062E+09 | 179580.14 | 0.32 |
December | 0.271813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507544E+10 | 0.00 | 0.00 | 0.24 |
Annual Sum or Average | 0.223136E+12 | 0.116822E+11 | 5492087.87 | 0.605386E+09 | 0.139623E+10 | 0.215733E+11 | 0.894611E+11 | 298413.06 | 0.42 |
Minimum of Months | 0.213889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Maximum of Months | 0.291273E+11 | 0.614903E+10 | 5492087.87 | 0.224142E+09 | 0.688171E+09 | 0.601991E+10 | 0.240894E+11 | 179580.14 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.379411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411215E+10 | 0.00 | 0.00 | 0.37 |
February | 0.351338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379082E+10 | 0.00 | 0.00 | 0.38 |
March | 0.581271E+10 | 0.00 | 0.00 | 6328995.25 | 0.00 | 0.116766E+10 | 0.577059E+09 | 0.00 | 0.51 |
April | 0.570056E+10 | 0.00 | 0.00 | 8400883.69 | 0.00 | 40713479.25 | 0.186677E+10 | 0.00 | 0.70 |
May | 0.357233E+10 | 155531.95 | 0.00 | 12955709.34 | 1135354.72 | 0.00 | 0.382566E+10 | 0.00 | 0.97 |
June | 0.152844E+10 | 0.506441E+09 | 0.00 | 39881367.83 | 14417454.21 | 0.00 | 0.284018E+10 | 0.00 | 0.97 |
July | 0.596629E+09 | 0.152994E+10 | 0.00 | 9925229.93 | 57122391.89 | 0.00 | 0.877911E+09 | 0.00 | 0.64 |
August | 0.127327E+10 | 0.681819E+09 | 0.00 | 12376103.29 | 26178408.61 | 0.00 | 0.184564E+10 | 0.00 | 0.86 |
September | 0.282521E+10 | 0.205206E+09 | 0.00 | 7832589.88 | 10711742.98 | 0.00 | 0.242127E+10 | 0.00 | 0.95 |
October | 0.566336E+10 | 0.00 | 0.00 | 12097700.90 | 0.00 | 69941513.46 | 0.135539E+10 | 0.00 | 0.71 |
November | 0.641602E+10 | 0.00 | 0.00 | 1646452.11 | 146033.16 | 79063046.08 | 0.170840E+09 | 0.00 | 0.52 |
December | 0.485138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239193E+10 | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.455474E+11 | 0.292356E+10 | 0.00 | 0.111445E+09 | 0.109711E+09 | 0.116523E+11 | 0.157807E+11 | 0.00 | 0.66 |
Minimum of Months | 0.596629E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.641602E+10 | 0.152994E+10 | 0.00 | 39881367.83 | 57122391.89 | 0.411215E+10 | 0.382566E+10 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.503898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438234E+10 | 0.00 | 0.00 | 0.68 |
February | 0.463769E+10 | 0.00 | 0.00 | 275637.49 | 0.00 | 0.403742E+10 | 28395741.44 | 0.00 | 0.70 |
March | 0.729118E+10 | 0.00 | 0.00 | 6407237.48 | 0.00 | 0.118547E+10 | 0.527897E+09 | 0.00 | 0.93 |
April | 0.651677E+10 | 0.00 | 0.00 | 13421310.00 | 0.00 | 0.124941E+09 | 0.285843E+10 | 0.00 | 1.33 |
May | 0.476594E+10 | 93379.60 | 0.00 | 14206807.62 | 1372646.33 | 2167983.15 | 0.443637E+10 | 0.00 | 1.83 |
June | 0.232062E+10 | 0.396220E+09 | 0.00 | 37035547.39 | 43300620.85 | 0.00 | 0.319008E+10 | 0.00 | 1.69 |
July | 0.745234E+09 | 0.105938E+10 | 0.00 | 16501645.44 | 0.308843E+09 | 0.00 | 0.133903E+10 | 0.00 | 1.15 |
August | 0.178941E+10 | 0.433771E+09 | 0.00 | 10587246.44 | 0.147843E+09 | 0.00 | 0.178756E+10 | 0.00 | 1.43 |
September | 0.352346E+10 | 0.119643E+09 | 0.00 | 9661434.27 | 86478564.95 | 0.00 | 0.287616E+10 | 0.00 | 1.71 |
October | 0.728433E+10 | 0.00 | 0.00 | 9098823.06 | 0.00 | 95417850.45 | 0.102778E+10 | 0.00 | 1.29 |
November | 0.751350E+10 | 0.00 | 0.00 | 1061577.25 | 174194.13 | 0.328574E+09 | 0.110472E+09 | 0.00 | 0.96 |
December | 0.531236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332568E+10 | 0.00 | 0.00 | 0.67 |
Annual Sum or Average | 0.567395E+11 | 0.200911E+10 | 0.00 | 0.118257E+09 | 0.588013E+09 | 0.134820E+11 | 0.181822E+11 | 0.00 | 1.20 |
Minimum of Months | 0.745234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
Maximum of Months | 0.751350E+10 | 0.105938E+10 | 0.00 | 37035547.39 | 0.308843E+09 | 0.438234E+10 | 0.443637E+10 | 0.00 | 1.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.526493E+10 | 0.00 | 0.00 | 1926923.70 | 0.00 | 0.486836E+10 | 0.135851E+10 | 0.00 | 0.54 |
February | 0.520139E+10 | 0.00 | 0.00 | 17934834.05 | 0.00 | 0.423168E+10 | 0.138053E+10 | 0.00 | 0.56 |
March | 0.701310E+10 | 0.00 | 0.00 | 51393522.13 | 0.00 | 0.130908E+10 | 0.386237E+10 | 0.00 | 0.81 |
April | 0.701041E+10 | 0.00 | 0.00 | 26212015.67 | 0.00 | 0.353841E+09 | 0.506360E+10 | 0.00 | 1.18 |
May | 0.594907E+10 | 211277.82 | 0.00 | 17774060.79 | 1601734.55 | 1668956.50 | 0.491859E+10 | 0.00 | 1.43 |
June | 0.316492E+10 | 0.566263E+09 | 0.00 | 37437758.66 | 37516300.66 | 0.00 | 0.268801E+10 | 0.00 | 1.26 |
July | 0.119682E+10 | 0.176592E+10 | 0.00 | 6844897.43 | 0.206722E+09 | 0.00 | 0.699870E+09 | 0.00 | 0.80 |
August | 0.220783E+10 | 0.840540E+09 | 0.00 | 14902882.93 | 67211660.90 | 0.00 | 0.191078E+10 | 0.00 | 1.13 |
September | 0.388192E+10 | 0.263249E+09 | 0.00 | 18061579.74 | 56500650.29 | 0.00 | 0.476179E+10 | 0.00 | 1.58 |
October | 0.669125E+10 | 0.00 | 0.00 | 62674667.48 | 0.00 | 0.229545E+09 | 0.525060E+10 | 0.00 | 1.30 |
November | 0.726198E+10 | 74090.56 | 0.00 | 32054479.92 | 143528.38 | 0.591499E+09 | 0.265669E+10 | 0.00 | 0.83 |
December | 0.595445E+10 | 0.00 | 0.00 | 4156344.26 | 0.00 | 0.371574E+10 | 0.834593E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.607981E+11 | 0.343626E+10 | 0.00 | 0.291374E+09 | 0.369696E+09 | 0.153014E+11 | 0.353859E+11 | 0.00 | 1.00 |
Minimum of Months | 0.119682E+10 | 0.00 | 0.00 | 1926923.70 | 0.00 | 0.00 | 0.699870E+09 | 0.00 | 0.53 |
Maximum of Months | 0.726198E+10 | 0.176592E+10 | 0.00 | 62674667.48 | 0.206722E+09 | 0.486836E+10 | 0.525060E+10 | 0.00 | 1.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.830650E+10 | 0.00 | 0.00 | 11826.42 | 0.00 | 0.313229E+10 | 56275683.15 | 0.00 | 0.83 |
February | 0.810437E+10 | 0.00 | 0.00 | 1403360.62 | 0.00 | 0.240714E+10 | 0.121589E+09 | 0.00 | 0.85 |
March | 0.944996E+10 | 0.00 | 0.00 | 18453307.72 | 0.00 | 0.266396E+09 | 0.154316E+10 | 0.00 | 1.16 |
April | 0.739842E+10 | 0.00 | 0.00 | 22163927.72 | 0.00 | 555850.07 | 0.460568E+10 | 0.00 | 1.74 |
May | 0.622984E+10 | 337247.09 | 0.00 | 14362710.86 | 1508764.24 | 0.00 | 0.467981E+10 | 0.00 | 2.19 |
June | 0.314911E+10 | 0.570095E+09 | 0.00 | 38319594.53 | 13821742.22 | 0.00 | 0.292633E+10 | 0.00 | 2.00 |
July | 0.109155E+10 | 0.184522E+10 | 0.00 | 8049014.71 | 66610460.04 | 0.00 | 0.797556E+09 | 0.00 | 1.24 |
August | 0.171054E+10 | 0.843706E+09 | 0.00 | 16473503.24 | 24251937.82 | 0.00 | 0.238091E+10 | 0.00 | 1.74 |
September | 0.449507E+10 | 0.195187E+09 | 0.00 | 8234125.44 | 58525292.78 | 0.00 | 0.286957E+10 | 0.00 | 2.03 |
October | 0.876456E+10 | 0.00 | 0.00 | 15845984.54 | 0.00 | 2811474.37 | 0.155806E+10 | 0.00 | 1.61 |
November | 0.927721E+10 | 64502.79 | 0.00 | 4916630.91 | 148146.37 | 3159192.60 | 0.492524E+09 | 0.00 | 1.18 |
December | 0.987769E+10 | 0.00 | 0.00 | 194573.74 | 0.00 | 0.590296E+09 | 65853984.71 | 0.00 | 0.82 |
Annual Sum or Average | 0.778548E+11 | 0.345461E+10 | 0.00 | 0.148429E+09 | 0.164866E+09 | 0.640265E+10 | 0.220973E+11 | 0.00 | 1.45 |
Minimum of Months | 0.109155E+10 | 0.00 | 0.00 | 11826.42 | 0.00 | 0.00 | 56275683.15 | 0.00 | 0.82 |
Maximum of Months | 0.987769E+10 | 0.184522E+10 | 0.00 | 38319594.53 | 66610460.04 | 0.313229E+10 | 0.467981E+10 | 0.00 | 2.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.136332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107538E+12 | 0.00 | 0.00 | 0.60 |
February | 0.212694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.917927E+11 | 0.00 | 0.00 | 0.61 |
March | 0.566477E+11 | 0.00 | 0.00 | 3837691.24 | 0.00 | 0.497151E+11 | 0.394440E+09 | 0.00 | 0.71 |
April | 0.781068E+11 | 0.00 | 0.00 | 867304.28 | 0.00 | 0.155302E+11 | 0.834346E+09 | 0.00 | 0.88 |
May | 0.769839E+11 | 1579786.68 | 0.00 | 19903567.32 | 11549180.74 | 0.935375E+09 | 0.106322E+11 | 0.00 | 1.17 |
June | 0.402743E+11 | 0.487070E+10 | 0.00 | 97653686.97 | 0.712619E+09 | 0.00 | 0.838043E+10 | 0.00 | 1.07 |
July | 0.108730E+11 | 0.141466E+11 | 0.00 | 35609055.68 | 0.337294E+10 | 0.00 | 0.430303E+10 | 0.00 | 0.67 |
August | 0.229301E+11 | 0.592902E+10 | 0.00 | 57549497.79 | 0.193635E+10 | 0.00 | 0.868780E+10 | 0.00 | 0.88 |
September | 0.518156E+11 | 0.137039E+10 | 0.00 | 21296495.62 | 0.131329E+10 | 0.703539E+09 | 0.941643E+10 | 0.00 | 1.14 |
October | 0.768817E+11 | 0.00 | 0.00 | 97211.31 | 0.00 | 0.116326E+11 | 58685811.88 | 0.00 | 0.90 |
November | 0.568834E+11 | 0.00 | 0.00 | 0.00 | 6853989.57 | 0.320021E+11 | 0.00 | 0.00 | 0.71 |
December | 0.171940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.979009E+11 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.523493E+12 | 0.263183E+11 | 0.00 | 0.236815E+09 | 0.735360E+10 | 0.407751E+12 | 0.427074E+11 | 0.00 | 0.83 |
Minimum of Months | 0.108730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.781068E+11 | 0.141466E+11 | 0.00 | 97653686.97 | 0.337294E+10 | 0.107538E+12 | 0.106322E+11 | 0.00 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714875E+11 | 0.00 | 0.00 | 0.66 |
February | 0.201068E+11 | 0.00 | 0.00 | 933661.31 | 0.00 | 0.597314E+11 | 75067371.95 | 0.00 | 0.67 |
March | 0.467050E+11 | 0.00 | 0.00 | 43534707.74 | 0.00 | 0.280501E+11 | 0.290330E+10 | 0.00 | 0.82 |
April | 0.470060E+11 | 0.00 | 0.00 | 0.108633E+09 | 0.00 | 0.870223E+10 | 0.208981E+11 | 0.00 | 1.12 |
May | 0.432572E+11 | 1815553.39 | 0.00 | 0.127240E+09 | 9512973.98 | 0.551834E+09 | 0.365648E+11 | 0.00 | 1.68 |
June | 0.225213E+11 | 0.409017E+10 | 0.00 | 0.339766E+09 | 0.695499E+09 | 0.00 | 0.280466E+11 | 0.00 | 1.64 |
July | 0.664675E+10 | 0.114010E+11 | 0.00 | 0.143947E+09 | 0.321558E+10 | 0.00 | 0.116726E+11 | 0.00 | 1.10 |
August | 0.157402E+11 | 0.457454E+10 | 0.00 | 94264300.18 | 0.188100E+10 | 6858362.51 | 0.143929E+11 | 0.00 | 1.30 |
September | 0.324392E+11 | 0.110486E+10 | 0.00 | 76858669.91 | 0.114866E+10 | 0.337619E+09 | 0.221726E+11 | 0.00 | 1.58 |
October | 0.524185E+11 | 0.00 | 0.00 | 64624342.59 | 0.00 | 0.819667E+10 | 0.554755E+10 | 0.00 | 1.07 |
November | 0.391627E+11 | 0.00 | 838279.94 | 4035579.57 | 5146554.37 | 0.235869E+11 | 0.217657E+09 | 2510.14 | 0.77 |
December | 0.123320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691755E+11 | 0.00 | 0.00 | 0.66 |
Annual Sum or Average | 0.352910E+12 | 0.211724E+11 | 838279.94 | 0.100384E+10 | 0.695540E+10 | 0.269827E+12 | 0.142491E+12 | 2510.14 | 1.09 |
Minimum of Months | 0.664675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.524185E+11 | 0.114010E+11 | 838279.94 | 0.339766E+09 | 0.321558E+10 | 0.714875E+11 | 0.365648E+11 | 2510.14 | 1.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.379045E+11 | 0.00 | 0.00 | 15559716.50 | 0.00 | 0.738332E+11 | 0.126455E+11 | 0.00 | 0.62 |
February | 0.435157E+11 | 0.00 | 0.00 | 0.168933E+09 | 0.00 | 0.614256E+11 | 0.129527E+11 | 0.00 | 0.64 |
March | 0.622227E+11 | 0.00 | 0.00 | 0.458681E+09 | 0.00 | 0.259663E+11 | 0.332804E+11 | 0.00 | 0.82 |
April | 0.586158E+11 | 0.00 | 0.00 | 0.220964E+09 | 0.00 | 0.123445E+11 | 0.403259E+11 | 0.00 | 1.09 |
May | 0.578017E+11 | 3436765.47 | 0.00 | 0.156240E+09 | 10889993.31 | 0.114518E+10 | 0.414741E+11 | 0.00 | 1.37 |
June | 0.334172E+11 | 0.573394E+10 | 0.00 | 0.290853E+09 | 0.721084E+09 | 19870132.00 | 0.209407E+11 | 0.00 | 1.22 |
July | 0.109506E+11 | 0.179710E+11 | 0.00 | 55370107.35 | 0.299945E+10 | 0.00 | 0.551031E+10 | 0.00 | 0.76 |
August | 0.210636E+11 | 0.829873E+10 | 0.00 | 0.123058E+09 | 0.151571E+10 | 0.00 | 0.142053E+11 | 0.00 | 1.03 |
September | 0.374874E+11 | 0.260344E+10 | 0.00 | 0.167664E+09 | 0.975749E+09 | 0.384155E+09 | 0.419124E+11 | 0.00 | 1.56 |
October | 0.592580E+11 | 0.00 | 0.00 | 0.599762E+09 | 0.00 | 0.763298E+10 | 0.422084E+11 | 0.00 | 1.21 |
November | 0.555764E+11 | 0.00 | 0.00 | 0.274804E+09 | 6854022.84 | 0.219470E+11 | 0.200179E+11 | 0.00 | 0.79 |
December | 0.399931E+11 | 0.00 | 0.00 | 28724256.44 | 0.00 | 0.712697E+11 | 0.556094E+10 | 0.00 | 0.61 |
Annual Sum or Average | 0.517807E+12 | 0.346105E+11 | 0.00 | 0.256061E+10 | 0.622973E+10 | 0.275969E+12 | 0.291034E+12 | 0.00 | 0.98 |
Minimum of Months | 0.109506E+11 | 0.00 | 0.00 | 15559716.50 | 0.00 | 0.00 | 0.551031E+10 | 0.00 | 0.61 |
Maximum of Months | 0.622227E+11 | 0.179710E+11 | 0.00 | 0.599762E+09 | 0.299945E+10 | 0.738332E+11 | 0.422084E+11 | 0.00 | 1.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.228575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897989E+11 | 0.00 | 0.00 | 0.87 |
February | 0.314699E+11 | 0.00 | 0.00 | 4170662.69 | 0.00 | 0.731340E+11 | 0.338117E+09 | 0.00 | 0.88 |
March | 0.641762E+11 | 0.00 | 0.00 | 63451969.76 | 0.00 | 0.310052E+11 | 0.503737E+10 | 0.00 | 1.04 |
April | 0.649739E+11 | 0.00 | 0.00 | 98277349.27 | 0.00 | 0.960547E+10 | 0.188257E+11 | 0.00 | 1.39 |
May | 0.624844E+11 | 1850794.69 | 0.00 | 0.101660E+09 | 10769621.31 | 0.328023E+09 | 0.293843E+11 | 0.00 | 1.92 |
June | 0.336451E+11 | 0.492772E+10 | 0.00 | 0.252704E+09 | 0.801049E+09 | 5265681.85 | 0.184970E+11 | 0.00 | 1.79 |
July | 0.104938E+11 | 0.131278E+11 | 0.00 | 39334689.48 | 0.432186E+10 | 0.00 | 0.416245E+10 | 0.00 | 1.05 |
August | 0.214700E+11 | 0.594577E+10 | 0.00 | 68141771.71 | 0.183765E+10 | 0.00 | 0.899878E+10 | 0.00 | 1.35 |
September | 0.460982E+11 | 0.115044E+10 | 0.00 | 45635445.79 | 0.135009E+10 | 0.415474E+09 | 0.146241E+11 | 0.00 | 1.79 |
October | 0.697093E+11 | 0.00 | 0.00 | 70754412.65 | 0.00 | 0.803975E+10 | 0.589849E+10 | 0.00 | 1.33 |
November | 0.599471E+11 | 0.00 | 0.00 | 1646065.57 | 6391351.37 | 0.225663E+11 | 0.322666E+09 | 0.00 | 1.02 |
December | 0.274323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795068E+11 | 0.00 | 0.00 | 0.87 |
Annual Sum or Average | 0.514758E+12 | 0.251536E+11 | 0.00 | 0.745777E+09 | 0.832780E+10 | 0.314405E+12 | 0.106089E+12 | 0.00 | 1.28 |
Minimum of Months | 0.104938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Maximum of Months | 0.697093E+11 | 0.131278E+11 | 0.00 | 0.252704E+09 | 0.432186E+10 | 0.897989E+11 | 0.293843E+11 | 0.00 | 1.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.330557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109635E+11 | 0.00 | 0.00 | 0.61 |
February | 0.101990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959599E+10 | 0.00 | 64678.95 | 0.62 |
March | 0.475715E+10 | 0.00 | 0.00 | 246107.45 | 0.00 | 0.641472E+10 | 32653319.63 | 0.00 | 0.83 |
April | 0.804679E+10 | 0.00 | 0.00 | 23415.70 | 0.00 | 0.271813E+10 | 71967045.01 | 0.00 | 1.07 |
May | 0.942894E+10 | 0.00 | 0.00 | 1192383.19 | 2812950.03 | 0.722561E+09 | 0.750510E+09 | 0.00 | 1.46 |
June | 0.536382E+10 | 0.342551E+09 | 0.00 | 4213911.29 | 0.156936E+09 | 46527332.25 | 0.606689E+09 | 0.00 | 1.28 |
July | 0.119427E+10 | 0.993573E+09 | 0.00 | 3532116.65 | 0.737598E+09 | 0.00 | 0.407768E+09 | 0.00 | 0.76 |
August | 0.261739E+10 | 0.407053E+09 | 0.00 | 5217195.17 | 0.373495E+09 | 24095683.87 | 0.808073E+09 | 0.00 | 1.02 |
September | 0.591263E+10 | 78056971.82 | 0.00 | 1137033.33 | 0.210804E+09 | 0.526408E+09 | 0.684689E+09 | 0.00 | 1.41 |
October | 0.719628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268010E+10 | 0.00 | 0.00 | 1.13 |
November | 0.367142E+10 | 0.00 | 8077548.11 | 0.00 | 1148190.16 | 0.528837E+10 | 0.00 | 176442.88 | 0.83 |
December | 0.750887E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.991689E+10 | 0.00 | 0.00 | 0.62 |
Annual Sum or Average | 0.502900E+11 | 0.182123E+10 | 8077548.11 | 15562162.78 | 0.148279E+10 | 0.488973E+11 | 0.336235E+10 | 241121.83 | 0.97 |
Minimum of Months | 0.330557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
Maximum of Months | 0.942894E+10 | 0.993573E+09 | 8077548.11 | 5217195.17 | 0.737598E+09 | 0.109635E+11 | 0.808073E+09 | 176442.88 | 1.46 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.419280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720750E+10 | 0.00 | 0.00 | 0.64 |
February | 0.151521E+10 | 0.00 | 563.82 | 0.00 | 0.00 | 0.565077E+10 | 0.00 | 43119.51 | 0.65 |
March | 0.444569E+10 | 0.00 | 0.00 | 871709.06 | 0.00 | 0.304326E+10 | 79637643.51 | 0.00 | 0.87 |
April | 0.462271E+10 | 0.00 | 0.00 | 6870514.29 | 0.00 | 0.127059E+10 | 0.164492E+10 | 0.00 | 1.16 |
May | 0.424527E+10 | 0.00 | 0.00 | 10961630.66 | 1899830.45 | 0.324667E+09 | 0.355528E+10 | 0.00 | 1.72 |
June | 0.217827E+10 | 0.322912E+09 | 0.00 | 32616564.47 | 70885116.22 | 14126128.91 | 0.290225E+10 | 0.00 | 1.63 |
July | 0.458133E+09 | 0.920990E+09 | 0.00 | 13361694.97 | 0.398449E+09 | 0.00 | 0.113576E+10 | 0.00 | 1.04 |
August | 0.135647E+10 | 0.372300E+09 | 0.00 | 9534554.82 | 0.202350E+09 | 16156263.09 | 0.134640E+10 | 0.00 | 1.26 |
September | 0.280984E+10 | 82687584.95 | 0.00 | 6488301.57 | 0.121149E+09 | 0.231900E+09 | 0.211901E+10 | 0.00 | 1.59 |
October | 0.520714E+10 | 0.00 | 0.00 | 1205375.08 | 0.00 | 0.135568E+10 | 0.124317E+09 | 0.00 | 1.19 |
November | 0.291275E+10 | 0.00 | 5470080.20 | 0.00 | 775472.94 | 0.313842E+10 | 0.00 | 104559.67 | 0.87 |
December | 0.549043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665424E+10 | 0.00 | 0.00 | 0.65 |
Annual Sum or Average | 0.307198E+11 | 0.169889E+10 | 5470644.03 | 81910344.93 | 0.795508E+09 | 0.289073E+11 | 0.129076E+11 | 147679.18 | 1.11 |
Minimum of Months | 0.419280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
Maximum of Months | 0.520714E+10 | 0.920990E+09 | 5470080.20 | 32616564.47 | 0.398449E+09 | 0.720750E+10 | 0.355528E+10 | 104559.67 | 1.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.272828E+10 | 0.00 | 0.00 | 685983.46 | 0.00 | 0.796121E+10 | 0.656115E+09 | 0.00 | 0.61 |
February | 0.380981E+10 | 0.00 | 1765.68 | 8874564.88 | 0.00 | 0.637170E+10 | 0.639562E+09 | 62913.78 | 0.63 |
March | 0.601547E+10 | 0.00 | 0.00 | 31681620.61 | 0.00 | 0.357904E+10 | 0.233629E+10 | 0.00 | 0.89 |
April | 0.611419E+10 | 0.00 | 0.00 | 17361479.15 | 0.00 | 0.209223E+10 | 0.375408E+10 | 0.00 | 1.20 |
May | 0.689439E+10 | 0.00 | 0.00 | 12103397.43 | 2812972.07 | 0.747040E+09 | 0.403319E+10 | 0.00 | 1.58 |
June | 0.423488E+10 | 0.399765E+09 | 0.00 | 23077596.65 | 0.150800E+09 | 0.148272E+09 | 0.207403E+10 | 0.00 | 1.38 |
July | 0.112226E+10 | 0.128779E+10 | 0.00 | 6202846.68 | 0.646084E+09 | 650254.52 | 0.610750E+09 | 0.00 | 0.82 |
August | 0.235695E+10 | 0.591445E+09 | 0.00 | 12629560.82 | 0.297936E+09 | 11601192.56 | 0.139448E+10 | 0.00 | 1.12 |
September | 0.420373E+10 | 0.154330E+09 | 0.00 | 12905782.67 | 0.177953E+09 | 0.312923E+09 | 0.399890E+10 | 0.00 | 1.70 |
October | 0.610750E+10 | 0.00 | 0.00 | 44611608.14 | 0.00 | 0.173229E+10 | 0.348951E+10 | 0.00 | 1.34 |
November | 0.456937E+10 | 0.00 | 8031135.95 | 14745002.00 | 1148199.16 | 0.363330E+10 | 0.108501E+10 | 80402.77 | 0.86 |
December | 0.248139E+10 | 0.00 | 0.00 | 1389386.43 | 0.00 | 0.793260E+10 | 0.268299E+09 | 0.00 | 0.63 |
Annual Sum or Average | 0.506382E+11 | 0.243333E+10 | 8032901.63 | 0.186269E+09 | 0.127673E+10 | 0.345228E+11 | 0.243402E+11 | 143316.55 | 1.06 |
Minimum of Months | 0.112226E+10 | 0.00 | 0.00 | 685983.46 | 0.00 | 650254.52 | 0.268299E+09 | 0.00 | 0.61 |
Maximum of Months | 0.689439E+10 | 0.128779E+10 | 8031135.95 | 44611608.14 | 0.646084E+09 | 0.796121E+10 | 0.403319E+10 | 80402.77 | 1.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.129616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742451E+10 | 0.00 | 0.00 | 0.73 |
February | 0.207599E+10 | 0.00 | 534.77 | 228873.58 | 4873.37 | 0.608968E+10 | 23554784.10 | 38360.87 | 0.74 |
March | 0.505894E+10 | 0.00 | 0.00 | 4661020.01 | 0.00 | 0.324136E+10 | 0.407175E+09 | 0.00 | 1.00 |
April | 0.553540E+10 | 0.00 | 0.00 | 9186731.89 | 0.00 | 0.141086E+10 | 0.195074E+10 | 0.00 | 1.38 |
May | 0.580034E+10 | 0.00 | 0.00 | 10232162.63 | 2173333.25 | 0.430720E+09 | 0.322197E+10 | 0.00 | 1.98 |
June | 0.327712E+10 | 0.347725E+09 | 0.00 | 26338087.83 | 0.101203E+09 | 41894405.59 | 0.210919E+10 | 0.00 | 1.79 |
July | 0.873938E+09 | 0.985792E+09 | 0.00 | 4636213.92 | 0.513855E+09 | 0.00 | 0.448880E+09 | 0.00 | 1.01 |
August | 0.189025E+10 | 0.436524E+09 | 0.00 | 7803813.43 | 0.233642E+09 | 497769.45 | 0.946747E+09 | 0.00 | 1.33 |
September | 0.414583E+10 | 77630886.73 | 0.00 | 4299803.72 | 0.151329E+09 | 0.193704E+09 | 0.154363E+10 | 0.00 | 1.82 |
October | 0.578785E+10 | 0.00 | 0.00 | 5957381.99 | 0.00 | 0.138386E+10 | 0.539044E+09 | 0.00 | 1.37 |
November | 0.390721E+10 | 0.00 | 1935141.16 | 0.00 | 5194995.10 | 0.301325E+10 | 0.00 | 24039.36 | 1.00 |
December | 0.141380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681931E+10 | 0.00 | 0.00 | 0.75 |
Annual Sum or Average | 0.410628E+11 | 0.184767E+10 | 1935675.93 | 73344089.00 | 0.100740E+10 | 0.300496E+11 | 0.111909E+11 | 62400.23 | 1.24 |
Minimum of Months | 0.873938E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
Maximum of Months | 0.580034E+10 | 0.985792E+09 | 1935141.16 | 26338087.83 | 0.513855E+09 | 0.742451E+10 | 0.322197E+10 | 38360.87 | 1.98 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3224389.39 | 0.00 | 0.00 | 0.831972E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 55570903.23 | 0.00 | 0.00 | 0.701848E+09 | 0.00 | 0.28 |
March | 0.00 | 97049.70 | 0.00 | 0.104265E+09 | 0.00 | 0.00 | 0.578344E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 63976387.72 | 0.00 | 0.00 | 0.459746E+09 | 0.00 | 0.29 |
May | 0.00 | 173678.38 | 0.00 | 8292153.24 | 0.00 | 0.00 | 0.370887E+09 | 0.00 | 0.29 |
June | 0.00 | 49906420.56 | 0.00 | 32123773.41 | 0.00 | 0.00 | 0.147492E+09 | 0.00 | 0.30 |
July | 0.00 | 0.148233E+09 | 0.00 | 9124025.45 | 0.00 | 0.00 | 30028210.47 | 0.00 | 0.28 |
August | 0.00 | 78605775.06 | 0.00 | 17044654.83 | 0.00 | 0.00 | 75050003.28 | 0.00 | 0.31 |
September | 0.00 | 20179635.17 | 0.00 | 5589044.97 | 0.00 | 0.00 | 0.215955E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 53390401.87 | 0.00 | 0.00 | 0.410902E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 90871867.52 | 0.00 | 0.00 | 0.481018E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 61047121.72 | 0.00 | 0.00 | 0.716439E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.297195E+09 | 0.00 | 0.504519E+09 | 0.00 | 0.00 | 0.501968E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3224389.39 | 0.00 | 0.00 | 30028210.47 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.148233E+09 | 0.00 | 0.104265E+09 | 0.00 | 0.00 | 0.831972E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.152916E+10 | 0.00 | 0.00 | 14465838.10 | 0.00 | 0.00 | 0.679873E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 0.448689E+09 | 0.00 | 0.00 | 0.712562E+10 | 0.00 | 0.28 |
March | 0.00 | 861969.71 | 0.00 | 0.933673E+09 | 0.00 | 0.00 | 0.589350E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.594214E+09 | 0.00 | 0.00 | 0.464321E+10 | 0.00 | 0.29 |
May | 0.00 | 1513728.21 | 0.00 | 71214627.45 | 0.00 | 0.00 | 0.372157E+10 | 0.00 | 0.29 |
June | 0.00 | 0.493585E+09 | 0.00 | 0.301918E+09 | 0.00 | 0.00 | 0.149561E+10 | 0.00 | 0.30 |
July | 0.00 | 0.147158E+10 | 0.00 | 85385770.39 | 0.00 | 0.00 | 0.307674E+09 | 0.00 | 0.28 |
August | 0.00 | 0.779257E+09 | 0.00 | 0.160693E+09 | 0.00 | 0.00 | 0.766714E+09 | 0.00 | 0.31 |
September | 0.00 | 0.194772E+09 | 0.00 | 45816612.86 | 0.00 | 0.00 | 0.217656E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 0.471850E+09 | 0.00 | 0.00 | 0.417181E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.811939E+09 | 0.00 | 0.00 | 0.490713E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.539793E+09 | 0.00 | 0.00 | 0.723495E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.152916E+10 | 0.294157E+10 | 0.00 | 0.447965E+10 | 0.00 | 0.00 | 0.492431E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 14465838.10 | 0.00 | 0.00 | 0.307674E+09 | 0.00 | 0.28 |
Maximum of Months | 0.152916E+10 | 0.147158E+10 | 0.00 | 0.933673E+09 | 0.00 | 0.00 | 0.723495E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.468066E+09 | 0.00 | 0.00 | 588051.00 | 0.00 | 0.00 | 0.361406E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 36763826.29 | 0.00 | 0.00 | 0.720646E+09 | 0.00 | 0.28 |
March | 0.00 | 83183.11 | 0.00 | 85132193.62 | 0.00 | 0.00 | 0.597602E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 56728225.44 | 0.00 | 0.00 | 0.467234E+09 | 0.00 | 0.29 |
May | 13132746.50 | 167866.66 | 0.00 | 6281738.68 | 0.00 | 0.00 | 0.360194E+09 | 0.00 | 0.29 |
June | 0.00 | 49499051.12 | 0.00 | 29378342.25 | 0.00 | 0.00 | 0.150474E+09 | 0.00 | 0.30 |
July | 0.00 | 0.147132E+09 | 0.00 | 8244603.03 | 0.00 | 0.00 | 31125587.90 | 0.00 | 0.28 |
August | 0.00 | 77489516.22 | 0.00 | 15832392.17 | 0.00 | 0.00 | 77829937.37 | 0.00 | 0.31 |
September | 6591116.95 | 19491474.83 | 0.00 | 3724262.49 | 0.00 | 0.00 | 0.212398E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 41088633.63 | 0.00 | 0.00 | 0.423445E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 72023724.98 | 0.00 | 0.00 | 0.499895E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 49510128.47 | 0.00 | 0.00 | 0.728015E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.487790E+09 | 0.293863E+09 | 0.00 | 0.405296E+09 | 0.00 | 0.00 | 0.463026E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 588051.00 | 0.00 | 0.00 | 31125587.90 | 0.00 | 0.28 |
Maximum of Months | 0.468066E+09 | 0.147132E+09 | 0.00 | 85132193.62 | 0.00 | 0.00 | 0.728015E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.846516E+09 | 0.00 | 0.00 | 0.362479E+12 | 0.00 | 5.44 |
February | 0.631686E+10 | 0.00 | 0.00 | 0.335908E+10 | 0.00 | 0.00 | 0.460142E+12 | 0.00 | 8.35 |
March | 33473066.04 | 0.00 | 0.00 | 0.733040E+10 | 0.00 | 0.00 | 0.736368E+12 | 0.00 | 17.23 |
April | 0.00 | 0.00 | 0.00 | 0.539882E+10 | 0.00 | 0.00 | 0.975618E+12 | 0.00 | 32.75 |
May | 0.00 | 0.00 | 0.00 | 0.788112E+09 | 0.00 | 0.00 | 0.304969E+12 | 0.00 | 11.88 |
June | 0.679888E+09 | 0.190810E+10 | 0.00 | 0.234503E+10 | 13709629.38 | 0.00 | 0.241946E+12 | 0.00 | 18.29 |
July | 2627042.01 | 0.346617E+10 | 0.00 | 0.222936E+10 | 0.00 | 0.00 | 0.256852E+12 | 0.00 | 21.47 |
August | 0.00 | 0.203811E+10 | 0.00 | 0.262686E+10 | 0.00 | 0.00 | 0.424355E+12 | 0.00 | 32.42 |
September | 0.00 | 396283.40 | 0.00 | 0.693441E+09 | 0.00 | 0.00 | 0.226348E+12 | 0.00 | 12.85 |
October | 0.216592E+10 | 0.00 | 0.00 | 0.332496E+10 | 0.00 | 0.00 | 0.468987E+12 | 0.00 | 17.15 |
November | 61055547.44 | 0.00 | 0.00 | 0.686985E+10 | 0.00 | 0.00 | 0.729255E+12 | 0.00 | 20.82 |
December | 0.00 | 0.00 | 0.00 | 0.555482E+10 | 0.00 | 0.00 | 0.105887E+13 | 0.00 | 20.22 |
Annual Sum or Average | 0.925982E+10 | 0.741277E+10 | 0.00 | 0.413672E+11 | 13709629.38 | 0.00 | 0.624619E+13 | 0.00 | 18.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.693441E+09 | 0.00 | 0.00 | 0.226348E+12 | 0.00 | 5.44 |
Maximum of Months | 0.631686E+10 | 0.346617E+10 | 0.00 | 0.733040E+10 | 13709629.38 | 0.00 | 0.105887E+13 | 0.00 | 32.75 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:22:25
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.264390E+12 | 0.497960E+11 | 0.00 | 0.215467E+13 | 0.423544E+12 |
February | 0.404753E+12 | 0.521490E+11 | 0.00 | 0.211148E+13 | 0.635773E+12 |
March | 0.592507E+12 | 0.327817E+11 | 0.00 | 0.287416E+13 | 0.854188E+12 |
April | 0.705944E+12 | 0.266000E+11 | 0.00 | 0.343845E+13 | 0.730198E+12 |
May | 0.862793E+12 | 0.145474E+11 | 0.00 | 0.271170E+13 | 0.537979E+12 |
June | 0.929572E+12 | 0.547364E+10 | 0.00 | 0.165339E+13 | 0.193515E+13 |
July | 0.861961E+12 | -0.141539E+10 | 0.00 | 0.780056E+12 | 0.312354E+13 |
August | 0.732098E+12 | 0.198366E+10 | 0.00 | 0.151753E+13 | 0.309655E+13 |
September | 0.554683E+12 | 0.813946E+10 | 0.00 | 0.218530E+13 | 0.104535E+13 |
October | 0.376234E+12 | 0.201707E+11 | 0.00 | 0.298342E+13 | 0.602420E+12 |
November | 0.203683E+12 | 0.279207E+11 | 0.00 | 0.293027E+13 | 0.701074E+12 |
December | 0.239040E+12 | 0.532686E+11 | 0.00 | 0.296138E+13 | 0.924864E+12 |
Annual Sum or Average | 0.672766E+13 | 0.291416E+12 | 0.00 | 0.283018E+14 | 0.146106E+14 |
Minimum of Months | 0.203683E+12 | -0.141539E+10 | 0.00 | 0.780056E+12 | 0.423544E+12 |
Maximum of Months | 0.929572E+12 | 0.532686E+11 | 0.00 | 0.343845E+13 | 0.312354E+13 |