Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2024-07-03 12:26:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 41455.81 | 894.98 | 894.98 |
Net Site Energy | 41455.81 | 894.98 | 894.98 |
Total Source Energy | 108850.43 | 2349.95 | 2349.95 |
Net Source Energy | 108850.43 | 2349.95 | 2349.95 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 10772.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1211.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 999.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2789.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 724.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 24.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2665.75 |
Humidification | 1469.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 546.84 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 553.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 30682.83 | 10772.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5492.75 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 10772.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1211.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 999.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 56.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2789.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 724.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 24.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2665.75 |
Humidification | General | 1469.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 546.84 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 553.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 10772.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1211.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 999.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2789.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 724.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 24.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2665.75 |
Humidification | Unassigned | 1469.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 546.84 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 553.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 146.23 | 232.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 662.40 | 232.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 146.23 | 232.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 662.40 | 232.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 30682.828 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 30682.828 | 100.00 |
Total On-Site and Utility Electric Sources | 30682.828 | 100.00 |
Total Electricity End Uses | 30682.828 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5492.75 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5492.75 | 100.00 |
Total Water End Uses | 5492.75 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 156.83 |
Time Setpoint Not Met During Occupied Cooling | 358.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5442.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS SZVAV FAN | AIRLOOP DATACENTER BASEMENT SYS11 FAN | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 11.6510 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 11.6510 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 11.6510 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.6510 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 11.6510 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.6510 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 11.6510 | 18.58 | 484.4232 | |
Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.6100 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:30 | 27-FEB-07:19 | - | - | - | - | - | - | - | - | - | - | 21-JUL-15:00 |
Heating | 0.00 | 3075343.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 280623.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235096.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 277543.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 77778.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 16485.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 43594.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2299393.13 | 3075343.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3075343.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 280623.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 277543.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 77778.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 16485.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 43594.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 11677.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3838.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17769.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3164.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8307.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8834.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2292.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 76.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 4655.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1754.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 97172.52 | 11677.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 252.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 82.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 190.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 49.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 100.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 37.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2097.84 | 252.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 252.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 82.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 190.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 49.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 100.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 37.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2097.84 | 252.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 7.30 | 0.290125 | 0.300000 | 2.19 |
DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | 32.07 | 0.018619 | 0.500000 | 16.04 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 7.60 | 0.250277 | 0.300000 | 2.28 | 0.667405 | 0.500000 | 0.001522 | 0.000271 | 2.28 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 71.95 | 0.264357 | 0.300000 | 21.58 | 0.704952 | 0.500000 | 0.001441 | 0.005175 | 25.06 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 8.94 | 0.212724 | 0.300000 | 2.68 | 0.567263 | 0.500000 | 0.001791 | 0.001829 | 8.94 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.59 | 0.150178 | 0.300000 | 0.477076 | 0.400473 | 0.500000 | 0.002537 | 0.000325 | 1.59 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.68 | 0.091508 | 0.300000 | 0.504565 | 0.300000 | 0.500000 | 0.004164 | 0.000221 | 1.08 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 2.62 | 0.091024 | 0.300000 | 0.787131 | 0.300000 | 0.500000 | 0.004186 | 0.000349 | 1.71 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.99 | 0.077493 | 0.300000 | 0.595817 | 0.300000 | 0.500000 | 0.004917 | 0.000184 | 0.902616 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 20.05 | 0.119088 | 0.300000 | 6.02 | 0.317569 | 0.500000 | 0.003199 | 0.004096 | 20.05 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 17.80 | 0.300000 | 0.500000 | 0.004406 | 0.002722 | 13.33 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 27.44 | 0.087041 | 0.300000 | 8.23 | 0.300000 | 0.500000 | 0.004377 | 0.004056 | 19.86 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 18.42 | 0.083553 | 0.300000 | 5.53 | 0.300000 | 0.500000 | 0.004560 | 0.002622 | 12.84 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 2.68 | 0.089109 | 0.300000 | 0.804027 | 0.300000 | 0.500000 | 0.004276 | 0.000547 | 2.68 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.77 | 0.086824 | 0.300000 | 0.531781 | 0.300000 | 0.500000 | 0.004388 | 0.000361 | 1.77 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 2.88 | 0.082825 | 0.300000 | 0.865053 | 0.300000 | 0.500000 | 0.004600 | 0.000543 | 2.66 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.93 | 0.079794 | 0.300000 | 0.578632 | 0.300000 | 0.500000 | 0.004775 | 0.000355 | 1.74 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 30973.89 | 0.000271 | 649.28 | |
CORE_MID VAV BOX REHEAT COIL | 591577.09 | 0.005175 | 13859.28 | |
CORE_TOP VAV BOX REHEAT COIL | 209074.28 | 0.001829 | 4885.21 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 37142.30 | 0.000325 | 867.59 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 25245.43 | 0.000221 | 589.68 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 39865.67 | 0.000349 | 931.17 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 21088.77 | 0.000184 | 492.65 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 468164.44 | 0.004096 | 10934.19 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 311126.45 | 0.002722 | 7266.38 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 463673.35 | 0.004056 | 10829.35 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 299677.88 | 0.002622 | 6999.12 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 62540.22 | 0.000547 | 1460.48 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 41210.12 | 0.000361 | 962.36 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 62059.36 | 0.000543 | 1449.26 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 40606.35 | 0.000355 | 948.26 | |
VAV_BOT WITH REHEAT HEATING COIL | 121035.41 | 0.001059 | 1884.32 | |
VAV_MID WITH REHEAT HEATING COIL | 1229953.31 | 0.010760 | 18792.50 | |
VAV_TOP WITH REHEAT HEATING COIL | 109864.08 | 0.000961 | 1797.37 | |
CAV_BAS HEATING COIL | 143667.76 | 0.000875 | 2622.58 | 100000.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 572979.15 | 0.000875 | 2622.58 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.776884 |
DATACENTER_MID_ZN_6 DIRECT AIR | 7.48 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.758587 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 7.74 | 4.64 | 15.48 | 6.36 | 12.54 | 12.54 | 0.300000 | 0.507274 | 12.54 |
VAV_MID WITH REHEAT | 77.83 | 46.70 | 155.66 | 91.14 | 116.44 | 116.44 | 0.300000 | 0.782715 | 116.44 |
VAV_TOP WITH REHEAT | 9.10 | 5.46 | 18.21 | 17.79 | 13.23 | 17.79 | 0.300000 | 1.00 | 17.79 |
CAV_BAS | 2.19 | 2.19 | 7.30 | 2.19 | 7.30 | 7.30 | 1.00 | 0.300000 | 7.30 |
AIRLOOP DATACENTER BASEMENT | 16.04 | 16.04 | 32.07 | 16.04 | 32.07 | 32.07 | 1.00 | 0.500000 | 32.07 |
AIRLOOP DATACENTER BOT | 0.776884 | 0.776884 | 0.776884 | 0.776884 | 0.776884 | 0.776884 | 1.00 | 1.000000 | 0.776884 |
AIRLOOP DATACENTER MID | 7.48 | 7.48 | 7.48 | 7.48 | 7.48 | 7.48 | 1.00 | 1.000000 | 7.48 |
AIRLOOP DATACENTER TOP | 0.758587 | 0.758587 | 0.758587 | 0.758587 | 0.758587 | 0.758587 | 1.00 | 1.00 | 0.758587 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 12.54 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 116.44 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 17.79 | |
CAV_BAS_OA_CONTROLLER | 7.30 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 32.07 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.776884 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 7.48 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.758587 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 24.55 | 6.67 | 11.08 | 0.007244 | 0.007000 | 213002.64 | 0.007608 | 12.54 |
VAV_MID WITH REHEAT COOLING COIL | 24.59 | 6.67 | 11.08 | 0.007258 | 0.007000 | 1989293.27 | 0.071053 | 116.44 |
VAV_TOP WITH REHEAT COOLING COIL | 24.51 | 6.67 | 11.10 | 0.007233 | 0.007000 | 300317.09 | 0.010727 | 17.79 |
CAV_BAS COOLING COIL | 23.37 | 6.67 | 11.07 | 0.007334 | 0.007000 | 113439.88 | 0.004052 | 7.30 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 27.00 | 6.67 | 15.03 | 0.007033 | 0.007000 | 451708.90 | 0.016134 | 32.07 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 12.54 |
VAV_MID WITH REHEAT FAN | 116.44 |
VAV_TOP WITH REHEAT FAN | 17.79 |
CAV_BAS SZVAV FAN | 7.30 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | 32.07 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007608 | 0.000063 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.001059 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.071053 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.010760 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.010727 | 0.000044 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000961 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | Design Size Minimum Supply Air Temperature [C] | User-Specified Minimum Supply Air Temperature [C] | User-Specified Maximum Supply Air Temperature [C] | User-Specified Nominal Cooling Capacity [W] | Design Size Maximum Supply Air Temperature [C] | |
CAV_BAS_UNITARY_PACKAGE_DX | 7.30 | 7.30 | 7.30 | 2.19 | 113439.88 | 100000.00 | 1.00 | 5.33 | 12.89 | 32.11 | ||
AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | 32.07 | 32.07 | 32.07 | 16.04 | 451708.90 | 100000.00 | 1.00 | 15.89 | 29.11 | |||
AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | 0.776884 | 0.776884 | 0.776884 | 0.776884 | 27719.31 | 1.00 | 12860.19 | 29.11 | ||||
AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | 7.48 | 7.48 | 7.48 | 7.48 | 267284.88 | 1.00 | 123871.93 | 29.11 | ||||
AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | 0.758587 | 0.758587 | 0.758587 | 0.758587 | 27084.82 | 1.00 | 12557.30 | 29.11 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000291 | 0.000037 | 96450.70 | 100000.00 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | 0.776884 | 1335.96 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | 7.48 | 12868.24 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | 0.758587 | 1304.49 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
AIRLOOP DATACENTER BOT COOLING COIL | 0.776880 | 0.388442 | 0.517920 | 12860.19 | 6430.10 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER MID COOLING COIL | 7.48 | 3.74 | 4.99 | 123871.93 | 61935.96 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.758590 | 0.379293 | 0.505727 | 12557.30 | 6278.65 | 0.800660 | 0.800660 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BOT HEATING COIL | 27719.31 |
AIRLOOP DATACENTER MID HEATING COIL | 267284.88 |
AIRLOOP DATACENTER TOP HEATING COIL | 27084.82 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.109573 | 22579.02 | |
HEATSYS1 PUMP | 0.038186 | 11499.90 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.109573 | 13.15 |
HEATSYS1 | 0.038186 | 4.58 |
COOLSYS1_SUPPLY | 0.109573 | 13.15 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.109573 | 0.109573 | 459934.30 | 6.67 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 4364878.40 | 4364878.40 | 0.038186 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.054787 | 10421.25 |
COOLSYS1 CHILLER2 PUMP | 0.054787 | 10421.25 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.109573 | 0.055345 | 1549512.62 | 1549520.52 | 0.077656 |
COOLSYS1 CHILLER2 | 0.109573 | 0.055345 | 1549512.62 | 1549520.52 | 0.077656 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.155313 | 18.64 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.155313 | 54157.83 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 63.58 | 1857288.95 | 12.72 | 232161.12 |
TOWERWATERSYS COOLTOWER 2 | 63.58 | 1857288.95 | 12.72 | 232161.12 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 11.651 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 16.493 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 11.651 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 496.074 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 32383.100 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 32383.100 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 9130.649 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 9130.649 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 4.938 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2025 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
26 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
27 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
35 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 4.9377744 | 4.9377744 | 4.9377744 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
47 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
48 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
49 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
50 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
51 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
52 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
53 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
54 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
55 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
56 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
57 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
58 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
59 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
60 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
61 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
62 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
63 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
64 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
65 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
66 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
67 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
68 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
69 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
70 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
71 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
72 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
73 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
74 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
75 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
76 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
77 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
78 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
79 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
80 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
81 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
82 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
83 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
84 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
85 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
86 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
87 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
88 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
89 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
90 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
91 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
92 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
93 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
94 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
95 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
96 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
97 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
98 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
99 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
100 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
101 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
102 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
103 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
104 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
105 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
106 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
107 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
108 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
109 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
110 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
111 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
112 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
113 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
114 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
115 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
116 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
117 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
118 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
119 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
120 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
121 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.46_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.615 | 2.615 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.46_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.615 | 2.615 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.46_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.615 | 2.615 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.46_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.615 | 2.615 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.53892E-002 | 0.31435 | 0.47035 | 0.47035 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.53892E-002 | 0.31435 | 0.47035 | 0.47035 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.53892E-002 | 0.31435 | 0.47035 | 0.47035 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.53892E-002 | 0.31435 | 0.47035 | 0.47035 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone BASEMENT | 1.2500 |
3 | Zone CORE_BOTTOM | 1.2500 |
4 | Zone CORE_MID | 1.2500 |
5 | Zone CORE_TOP | 1.2500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.2500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.2500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.2500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone BASEMENT | 1.1500 |
3 | Zone CORE_BOTTOM | 1.1500 |
4 | Zone CORE_MID | 1.1500 |
5 | Zone CORE_TOP | 1.1500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.1500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.1500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.1500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 85845.62618 | 98722.47011 | 6.34785 | 7.30003 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 89379.23847 | 102786.12424 | 6.60849 | 7.59976 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 6895.81803 | 8619.77254 | 0.50233 | 1.07782 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 846367.83601 | 973323.01141 | 62.56505 | 71.94981 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 276680.65819 | 345850.82274 | 20.04957 | 25.06197 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 82116.17740 | 94433.60401 | 6.12571 | 7.04457 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 27.09400 | 7.00668E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 97125.04964 | 121406.31205 | 7.15310 | 8.94138 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 14392.75551 | 16551.66883 | 1.07366 | 1.23471 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38200 | 6.99811E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 17240.63392 | 21550.79240 | 1.27220 | 1.59025 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 19605.62498 | 22546.46873 | 1.46251 | 1.68188 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 22.07900 | 6.99914E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 11717.33439 | 14646.66799 | 0.86482 | 1.08102 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 30585.16342 | 35172.93793 | 2.28154 | 2.62377 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 27.40000 | 7.00714E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 18502.81010 | 23128.51262 | 1.36568 | 1.70710 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 23151.42903 | 26624.14338 | 1.72701 | 1.98606 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.69700 | 7.00305E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 9791.35538 | 12239.19422 | 0.72209 | 0.90262 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 133039.43386 | 152995.34894 | 9.92434 | 11.41299 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38200 | 6.99811E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 217242.07076 | 271552.58845 | 16.04325 | 20.05406 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 207480.11340 | 238602.13041 | 15.47721 | 17.79879 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 22.65700 | 7.00000E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 144366.05443 | 180457.56804 | 10.66240 | 13.32800 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 319848.56691 | 367825.85194 | 23.85948 | 27.43840 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 27.40000 | 7.00714E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 215161.01666 | 268951.27082 | 15.88906 | 19.86132 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 214722.21042 | 246930.54198 | 16.01744 | 18.42006 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.44200 | 7.00266E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 139060.34728 | 173825.43410 | 10.26941 | 12.83676 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13999.43799 | 16099.35368 | 1.04431 | 1.20096 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 27.29800 | 7.00699E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 29011.50851 | 36264.38564 | 2.14407 | 2.68009 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 20663.22683 | 23762.71086 | 1.54140 | 1.77260 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 22.94600 | 7.00043E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 19116.40067 | 23895.50084 | 1.41285 | 1.76606 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 33612.99523 | 38654.94451 | 2.50740 | 2.88351 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 27.40000 | 7.00714E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 28788.66863 | 35985.83579 | 2.12756 | 2.65945 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 22483.68572 | 25856.23858 | 1.67719 | 1.92877 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.69700 | 7.00305E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 18836.49705 | 23545.62131 | 1.39213 | 1.74017 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 9055.96679 | 10414.36181 | 0.67555 | 0.77688 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 21.84100 | 6.99878E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -41.90000 | 6.45023E-005 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 87228.58948 | 100312.87790 | 6.50705 | 7.48310 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 21.84100 | 6.99878E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -41.90000 | 6.45023E-005 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8842.65805 | 10169.05675 | 0.65964 | 0.75859 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | 21.99400 | 6.99901E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -41.90000 | 6.45023E-005 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 373881.62096 | 429963.86410 | 27.89012 | 32.07364 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 18.11800 | 6.99333E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -41.90000 | 6.45023E-005 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 174071.87 | 12.53528 | 12.53528 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 132495.95 | 6.35882 | 6.35882 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:30:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1622741.47 | 116.44362 | 116.44362 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 1319807.56 | 91.14212 | 91.14212 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 182744.79 | 13.22950 | 13.22950 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 130847.20 | 17.78715 | 17.78715 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 |
7 | CAV_BAS | Cooling | Sensible | 91135.86 | 7.30003 | 7.30003 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 105806.54 | 1.20016 | 1.20016 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 424071.79 | 32.07366 | 32.07366 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 28623.64 | 0.33839 | 0.33839 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 10185.36 | 0.77688 | 0.77688 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1322.29 | 1.56323E-002 | 1.56323E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 98071.82 | 7.48310 | 7.48310 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 13222.94 | 0.15632 | 0.15632 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 9946.04 | 0.75859 | 0.75859 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1322.29 | 1.56323E-002 | 1.56323E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 7.30003 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.29013 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 2.19001 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.59976 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25028 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.27993 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66740 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.52231E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.70973E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.27993 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30973.89092 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.70973E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 649.28483 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 71.94981 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26436 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 21.58494 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70495 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44123E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.17537E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 25.06197 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 591577.09102 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.17537E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 13859.28265 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.94138 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21272 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.68241 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56726 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.79106E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.82907E-003 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.94138 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 209074.28027 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.82907E-003 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4885.20802 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.59025 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15018 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.47708 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40047 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.53700E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.24937E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.59025 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 37142.30433 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.24937E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 867.58910 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.68188 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.15076E-002 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.50456 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.16359E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.20858E-004 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.08102 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25245.42893 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.20858E-004 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 589.67586 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.62377 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.10239E-002 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78713 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.18571E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.48762E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.70710 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 39865.67248 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.48762E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 931.16579 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.98606 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.74927E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.59582 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.91659E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.84494E-004 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.90262 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21088.76916 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.84494E-004 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 492.64828 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 20.05406 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11909 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.01622 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31757 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.19930E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.09571E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 20.05406 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 468164.44451 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.09571E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 10934.18725 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 17.79879 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.40618E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.72187E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 13.32800 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 311126.45344 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.72187E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7266.38314 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 27.43840 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.70407E-002 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.23152 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.37726E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.05642E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.86132 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 463673.35321 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.05642E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 10829.35115 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.42006 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.35530E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.52602 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.55998E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.62171E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 12.83676 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 299677.88495 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.62171E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6999.12345 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.68009 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.91092E-002 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80403 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.27565E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.47129E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.68009 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 62540.21950 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.47129E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1460.48107 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.77260 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.68242E-002 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.53178 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.38818E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.60524E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.76606 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 41210.12145 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.60524E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 962.35868 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.88351 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.28247E-002 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.86505 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.60008E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.42922E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.65945 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 62059.35752 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.42922E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1449.25585 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.92877 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.97943E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.57863 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.77478E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.55242E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.74017 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 40606.34609 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.55242E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 948.26219 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.77688 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.48310 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.75859 |
215 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 32.07364 |
216 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 1.86185E-002 |
217 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
218 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 16.03682 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.74086 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.64452 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 15.48173 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 6.35882 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 12.53528 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 12.53528 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.50727 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 77.83056 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 46.69834 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 155.66112 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 91.14212 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 116.44362 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 116.44362 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.78271 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 9.10318 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.46191 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 18.20635 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 17.78715 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 13.22950 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 17.78715 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 1.00000 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.19001 |
244 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.19001 |
245 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.30003 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.19001 |
247 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.30003 |
248 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 7.30003 |
249 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.30000 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 16.03682 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 16.03682 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 32.07364 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 16.03682 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 32.07366 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 32.07366 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.50000 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.77688 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.77688 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.77688 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.77688 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.77688 |
264 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.77688 |
265 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.48310 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.48310 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.48310 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 7.48310 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.48310 |
272 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 7.48310 |
273 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
274 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.75859 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.75859 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.75859 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.75859 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.75859 |
280 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.75859 |
281 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
282 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
283 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 12.53528 |
284 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 116.44362 |
285 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 17.78715 |
286 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 7.30003 |
287 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 32.07366 |
288 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.77688 |
289 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 7.48310 |
290 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.75859 |
291 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 12.53528 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.54994 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.07792 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.24410E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 213002.64138 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.60796E-003 |
299 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 12.53528 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 121035.40588 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.05887E-003 |
302 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1884.32243 |
303 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 12.53528 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.60796E-003 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.25911E-005 |
306 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.05887E-003 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 116.44362 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.59217 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.07797 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.25753E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1989293.26649 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.10529E-002 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 116.44362 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 1229953.30519 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07602E-002 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 18792.50425 |
319 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 116.44362 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.10529E-002 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.70191E-006 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.07602E-002 |
323 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 17.78715 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.50614 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.09504 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.23257E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 300317.08722 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.07266E-002 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 17.78715 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 109864.07543 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.61139E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1797.37233 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 17.78715 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.07266E-002 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.43933E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.61139E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.30003 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.30003 |
342 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.30003 |
343 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.30003 |
344 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.19001 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 23.36937 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.06855 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.33432E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 113439.88440 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.05181E-003 |
352 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.30003 |
353 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 113439.88440 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 143667.76234 |
355 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
356 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
357 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.57515 |
358 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
359 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
360 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Minimum Supply Air Temperature [C] | 5.33238 |
361 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 12.88890 |
362 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 32.11110 |
363 | Fan:VariableVolume | CAV_BAS SZVAV FAN | Design Size Maximum Flow Rate [m3/s] | 7.30003 |
364 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 32.07366 |
365 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
366 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 32.07366 |
367 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 32.07366 |
368 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 32.07366 |
369 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 16.03683 |
370 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.00221 |
371 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
372 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 15.02855 |
373 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.03253E-003 |
374 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
375 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Coil Load [W] | 451708.89657 |
376 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.61340E-002 |
377 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 32.07366 |
378 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 451708.89657 |
379 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Capacity [W] | 572979.14609 |
380 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
381 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
382 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.57515 |
383 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
384 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
385 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 15.88890 |
386 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 29.11110 |
387 | Fan:VariableVolume | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Design Size Maximum Flow Rate [m3/s] | 32.07366 |
388 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.91389E-004 |
389 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
390 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
391 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.77688 |
393 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
394 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.77688 |
395 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1335.96014 |
396 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.77688 |
397 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.77688 |
398 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.77688 |
399 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77688 |
400 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.77688 |
401 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.38844 |
402 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.51792 |
403 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 12860.19000 |
404 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6430.09500 |
405 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
406 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
407 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 12860.19000 |
408 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27719.30584 |
409 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
410 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
411 | Coil:Heating:Fuel | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Nominal Capacity [W] | 27719.30584 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.48310 |
413 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
414 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.48310 |
415 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 12868.23582 |
416 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.48310 |
417 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.48310 |
418 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.48310 |
419 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 7.48310 |
420 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.48310 |
421 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.74155 |
422 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.98873 |
423 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 123871.93000 |
424 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 61935.96500 |
425 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
426 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
427 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 123871.93000 |
428 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 267284.87758 |
429 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
430 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
431 | Coil:Heating:Fuel | AIRLOOP DATACENTER MID HEATING COIL | Design Size Nominal Capacity [W] | 267284.87758 |
432 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.75859 |
433 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
434 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.75859 |
435 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1304.49494 |
436 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.75859 |
437 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.75859 |
438 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.75859 |
439 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75859 |
440 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.75859 |
441 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.37929 |
442 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.50573 |
443 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 12557.30000 |
444 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6278.65000 |
445 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
446 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
447 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 12557.30000 |
448 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27084.82324 |
449 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
450 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
451 | Coil:Heating:Fuel | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Nominal Capacity [W] | 27084.82324 |
452 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.10957 |
453 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 22579.02317 |
454 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.10957 |
455 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 13.14880 |
456 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.10957 |
457 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.10957 |
458 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 459934.29926 |
459 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 6.67000 |
460 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.81859E-002 |
461 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 4.58230 |
462 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.81859E-002 |
463 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 11499.90423 |
464 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
465 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 4364878.40430 |
466 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 4364878.40000 |
467 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.81859E-002 |
468 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.10957 |
469 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 13.14880 |
470 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 5.47867E-002 |
471 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 10421.25461 |
472 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 5.47867E-002 |
473 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 10421.25461 |
474 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.10957 |
475 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.53450E-002 |
476 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1549512.62071 |
477 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1549520.52000 |
478 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 7.76565E-002 |
479 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.10957 |
480 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.53450E-002 |
481 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1549512.62071 |
482 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1549520.52000 |
483 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 7.76565E-002 |
484 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
485 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
486 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
487 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
488 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
489 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.15531 |
490 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 18.63756 |
491 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.15531 |
492 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 54157.83030 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 63.57876 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1857288.95361 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 12.71575 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 232161.11920 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 63.57876 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1857288.95361 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 12.71575 |
500 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 232161.11920 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 29402.48 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 561207.87 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 198343.58 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 35236.03 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 23949.75 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 37819.63 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 20006.41 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 444136.87 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 295158.55 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 439876.26 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 284297.53 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 59330.50 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 39095.12 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 58874.32 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 38522.33 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 82638.41 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 819087.74 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 83446.50 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94837.77 |
20 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | 94837.77 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 322423.52 | 224573.62 | 97849.89 | 0.70 | 59096.09 | 599.39 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 3001693.14 | 2088808.12 | 912885.02 | 0.70 | 548413.76 | 5562.32 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 455964.16 | 318019.71 | 137944.45 | 0.70 | 83648.98 | 848.41 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 182892.31 | 128926.40 | 53965.91 | 0.70 | 37643.86 | 381.80 |
5 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | 641512.29 | 484614.82 | 156897.47 | 0.76 | 77842.82 | 789.53 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | 12251.3 | 9.16 | 9.16 | |||
2 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | 118007.4 | 10.40 | 10.40 | |||
3 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | 11962.8 | 9.16 | 9.16 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 6.37 | 21.74 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 6.37 | 21.74 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_NORTH_0.4 | N/A | 2.615 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_NORTH_0.4 | N/A | 2.615 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_NORTH_0.4 | N/A | 2.615 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_NORTH_0.4 | N/A | 2.615 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_NORTH_0.4 | N/A | 2.615 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 4.938 | 4.938 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 4.938 | 4.938 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 4.938 | 4.938 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 4.938 | 4.938 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_EAST_0.4 | N/A | 2.615 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_EAST_0.4 | N/A | 2.615 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_EAST_0.4 | N/A | 2.615 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 4.938 | 4.938 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 4.938 | 4.938 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_SOUTH_0.4 | N/A | 2.615 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_SOUTH_0.4 | N/A | 2.615 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_SOUTH_0.4 | N/A | 2.615 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_SOUTH_0.4 | N/A | 2.615 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_SOUTH_0.4 | N/A | 2.615 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 4.938 | 4.938 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 4.938 | 4.938 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 4.938 | 4.938 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 4.938 | 4.938 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_WEST_0.4 | N/A | 2.615 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_WEST_0.4 | N/A | 2.615 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_WEST_0.4 | N/A | 2.615 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 4.938 | 4.938 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 4.938 | 4.938 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_NORTH_0.4 | N/A | 2.615 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_EAST_0.4 | N/A | 2.615 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_SOUTH_0.4 | N/A | 2.615 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_WEST_0.4 | N/A | 2.615 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_NORTH_0.4 | N/A | 2.615 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_EAST_0.4 | N/A | 2.615 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_SOUTH_0.4 | N/A | 2.615 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_WEST_0.4 | N/A | 2.615 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 6.5845733697E-004 | 1.8008059570E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1197592410 | 8.2610020605E-002 | Pass | Pass | 0.4869298653 | 0.4980500659 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 2.1389268186E-002 | 1.3487904839E-002 | Pass | Pass | 0.4878099407 | 0.4960373253 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1728520632 | 0.1686710598 | Pass | Pass | 0.6541653001 | 0.6594590280 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2277203916 | 0.2327240149 | Pass | Pass | 0.6823601736 | 0.6007904017 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3009201757 | 0.3051255289 | Pass | Pass | 0.6799672572 | 0.5950451839 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3294665819 | 0.3335018631 | Pass | Pass | 0.6697899416 | 0.5975134710 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.6515261006E-002 | 3.8207754085E-002 | Pass | Pass | 0.4968649280 | 0.4967813598 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.7462614460 | 0.7504349750 | Pass | Pass | 0.6287569646 | 0.5900827611 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.7774294108 | 0.7887844113 | Pass | Pass | 0.6252033397 | 0.5908551321 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.7246019977 | 0.7347918399 | Pass | Pass | 0.6289141329 | 0.5928293999 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6459564248 | 0.6572549355 | Pass | Pass | 0.6365557168 | 0.5888360789 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.9711455587 | 0.9819359549 | Pass | Pass | 0.6098073637 | 0.6164052284 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.9938236717 | 1.0047016693 | Pass | Pass | 0.6072423476 | 0.6113364139 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.9467723727 | 0.9596427800 | Pass | Pass | 0.6100030651 | 0.6163163858 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.8918103660 | 0.9068997591 | Pass | Pass | 0.6152251568 | 0.5979656228 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.1227546720E-002 | 9.5148191228E-003 | Pass | Pass | 0.7339175171 | 0.7362566764 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.7046691705E-002 | 4.9041236509E-002 | Pass | Pass | 0.4828706306 | 0.4829792567 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.3450272428 | 0.2398678507 | Pass | Pass | 0.4859111928 | 0.4956706205 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.9737323326E-004 | 9.2056871004E-004 | Pass | Pass | 1.1806259734E-003 | 1.0539727256E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.7036625365E-003 | 2.2965496849E-003 | Pass | Pass | 1.1732537372E-003 | 1.0377700715E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.3524006113E-003 | 4.1831471968E-003 | Pass | Pass | 2.2524593213E-003 | 1.5388285413E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.9170886474E-002 | 2.6769743165E-002 | Pass | Pass | 2.3281874665E-003 | 1.6241344335E-003 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4363.07 | 212.82 | 0.00 | 35909.96 | 10890.17 | 51376.02 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.273 | 0.283 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.46_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.46_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.46_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.46_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.46_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.46_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.46_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.46_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.46_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.46_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.46_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.46_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.46_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.46_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.46_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.46_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.46_SHGC_NORTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.615 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.46_SHGC_EAST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.615 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.46_SHGC_SOUTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.615 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.46_SHGC_WEST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.615 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.46_SHGC_NORTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.615 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.46_SHGC_EAST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.615 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.46_SHGC_SOUTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.615 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.46_SHGC_WEST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.615 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.615 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 1390.74 | 2.615 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.615 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 11.6510 | 2779.43 | 32383.10 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 333.79 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.6510 | 24961.20 | 290822.99 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 2997.66 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.6510 | 3134.13 | 36515.73 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.6510 | 3134.20 | 36516.53 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 11.6510 | 783.68 | 9130.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 94.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 22.3674 | 362.03 | 8097.60 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 83.47 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
Interior Lighting Total | 11.7515 | 46320.38 | 544334.28 | 1723.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 64082.80 | AstronomicalClock | - | 83.06 | 83.06 | 999.11 | |
Exterior Lighting Total | 64082.80 | 999.11 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3059768.51 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 4364878.40 | 0.79 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1549520.52 | 6.11 | 1541959.70 | 6.08 | 6.37 | 21.74 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1549520.52 | 6.11 | 1541959.70 | 6.08 | 6.37 | 21.74 |
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1857288.95 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1857288.95 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 213002.64 | 322423.52 | 224573.62 | 97849.89 | 0.70 | - | 59096.09 | 599.39 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1989293.27 | 3001693.14 | 2088808.12 | 912885.02 | 0.70 | - | 548413.76 | 5562.32 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 300317.09 | 455964.16 | 318019.71 | 137944.45 | 0.70 | - | 83648.98 | 848.41 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 113439.88 | 182892.31 | 128926.40 | 53965.91 | 0.70 | - | 37643.86 | 381.80 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | 451708.90 | 641512.29 | 484614.82 | 156897.47 | 0.76 | - | 77842.82 | 789.53 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | 12860.19 | 10296.64 | 2563.55 | 0.80 | 3.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | 123871.93 | 99179.30 | 24692.63 | 0.80 | 3.50 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 12557.30 | 10054.13 | 2503.17 | 0.80 | 3.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
AIRLOOP DATACENTER BOT COOLING COIL | 12251.3 | 9.16 | 9.16 | ||||
AIRLOOP DATACENTER MID COOLING COIL | 118007.4 | 10.40 | 10.40 | ||||
AIRLOOP DATACENTER TOP COOLING COIL | 11962.8 | 9.16 | 9.16 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 30973.89 | 29402.48 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 591577.09 | 561207.87 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 209074.28 | 198343.58 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 37142.30 | 35236.03 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 25245.43 | 23949.75 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 39865.67 | 37819.63 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 21088.77 | 20006.41 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 468164.44 | 444136.87 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 311126.45 | 295158.55 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 463673.35 | 439876.26 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 299677.88 | 284297.53 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 62540.22 | 59330.50 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 41210.12 | 39095.12 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 62059.36 | 58874.32 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 40606.35 | 38522.33 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 121035.41 | 82638.41 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 1229953.31 | 819087.74 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 109864.08 | 83446.50 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94837.77 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | 100000.00 | 94837.77 | - |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | 27719.31 | 0.80 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | 267284.88 | 0.79 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | 27084.82 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 12.54 | 27403.41 | 2186.10 | 1.00 | 1.12 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 116.44 | 254557.76 | 2186.10 | 1.00 | 1.08 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1337.13 | 17.79 | 38516.17 | 2165.39 | 1.00 | 1.12 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
CAV_BAS SZVAV FAN | Fan:VariableVolume | 0.61 | 1337.13 | 7.30 | 16043.86 | 2197.78 | 1.00 | 1.13 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 0.61 | 637.69 | 32.07 | 33297.55 | 1038.16 | 1.00 | 1.19 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.78 | 1335.96 | 1719.64 | 1.00 | 1.35 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 7.48 | 12868.24 | 1719.64 | 1.00 | 1.08 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.76 | 1304.49 | 1719.64 | 1.00 | 1.36 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.83 | 0.109573 | 22579.02 | 206063.11 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.038186 | 11499.90 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.054787 | 10421.25 | 190215.15 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.054787 | 10421.25 | 190215.15 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 209234.68 | 0.155313 | 54157.83 | 348701.22 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 85845.63 | 98722.47 | 35.52 | 6.348 | 7.300 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00740 | 19.85 | 0.00700 | 1.200 | 0.00 |
CORE_BOTTOM | 89379.24 | 102786.12 | 41.18 | 6.608 | 7.600 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00735 | 19.85 | 0.00700 | 1.078 | 0.00 |
CORE_MID | 846367.84 | 973323.01 | 389.93 | 62.565 | 71.950 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00736 | 19.85 | 0.00700 | 10.778 | 0.00 |
CORE_TOP | 82116.18 | 94433.60 | 37.83 | 6.126 | 7.045 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00737 | 27.09 | 0.00701 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 14392.76 | 16551.67 | 52.81 | 1.074 | 1.235 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00726 | 21.38 | 0.00700 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 19605.62 | 22546.47 | 111.63 | 1.463 | 1.682 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00712 | 22.08 | 0.00700 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 30585.16 | 35172.94 | 112.22 | 2.282 | 2.624 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00712 | 27.40 | 0.00701 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 23151.43 | 26624.14 | 131.82 | 1.727 | 1.986 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00710 | 24.70 | 0.00700 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 133039.43 | 152995.35 | 488.16 | 9.924 | 11.413 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00727 | 21.38 | 0.00700 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 207480.11 | 238602.13 | 1181.34 | 15.477 | 17.799 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00712 | 22.66 | 0.00700 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 319848.57 | 367825.85 | 1173.59 | 23.859 | 27.438 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00712 | 27.40 | 0.00701 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 214722.21 | 246930.54 | 1222.58 | 16.017 | 18.420 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00711 | 24.44 | 0.00700 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13999.44 | 16099.35 | 51.37 | 1.044 | 1.201 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00726 | 27.30 | 0.00701 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 20663.23 | 23762.71 | 117.65 | 1.541 | 1.773 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00712 | 22.95 | 0.00700 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 33613.00 | 38654.94 | 123.33 | 2.507 | 2.884 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00711 | 27.40 | 0.00701 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 22483.69 | 25856.24 | 128.02 | 1.677 | 1.929 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00711 | 24.70 | 0.00700 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 9055.97 | 10414.36 | 287.67 | 0.676 | 0.777 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 27.00 | 27.00 | 0.00706 | 21.84 | 0.00700 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 87228.59 | 100312.88 | 2770.86 | 6.507 | 7.483 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 27.00 | 27.00 | 0.00706 | 21.84 | 0.00700 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8842.66 | 10169.06 | 280.89 | 0.660 | 0.759 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | 27.00 | 27.00 | 0.00706 | 21.99 | 0.00700 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 373881.62 | 429963.86 | 548.65 | 27.890 | 32.074 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00703 | 18.12 | 0.00699 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 22.24 | 0.00006 | -41.90 | 0.00006 | 1.200 | 0.00 |
CORE_BOTTOM | 6895.82 | 8619.77 | 3.45 | 0.502 | 1.078 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 1.078 | 0.00 |
CORE_MID | 276680.66 | 345850.82 | 138.56 | 20.050 | 25.062 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 10.778 | 0.00 |
CORE_TOP | 97125.05 | 121406.31 | 48.64 | 7.153 | 8.941 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 17240.63 | 21550.79 | 68.76 | 1.272 | 1.590 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 11717.33 | 14646.67 | 72.52 | 0.865 | 1.081 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 18502.81 | 23128.51 | 73.79 | 1.366 | 1.707 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 9791.36 | 12239.19 | 60.60 | 0.722 | 0.903 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 217242.07 | 271552.59 | 866.44 | 16.043 | 20.054 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 144366.05 | 180457.57 | 893.46 | 10.662 | 13.328 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 215161.02 | 268951.27 | 858.12 | 15.889 | 19.861 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 139060.35 | 173825.43 | 860.63 | 10.269 | 12.837 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 29011.51 | 36264.39 | 115.71 | 2.144 | 2.680 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 19116.40 | 23895.50 | 118.31 | 1.413 | 1.766 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 28788.67 | 35985.84 | 114.82 | 2.128 | 2.659 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 18836.50 | 23545.62 | 116.58 | 1.392 | 1.740 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.14 | 0.00069 | -41.90 | 0.00006 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.38 | 0.00069 | -41.90 | 0.00006 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 18.76 | 0.00069 | -41.90 | 0.00006 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 18.00 | 27.00 | 0.00700 | -41.90 | 0.00006 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 12.54 | 12.54 | 6.36 | 6.36 | 12.5353 | 6.3588 | 12.5353 | 0.5073 | 0.3000 |
VAV_MID WITH REHEAT | 116.44 | 116.44 | 91.14 | 91.14 | 116.4436 | 91.1421 | 116.4436 | 0.7827 | 0.3000 |
VAV_TOP WITH REHEAT | 13.23 | 13.23 | 17.79 | 17.79 | 13.2295 | 17.7872 | 17.7872 | 1.0000 | 0.3000 |
CAV_BAS | 7.30 | 7.30 | 1.20 | 1.20 | 7.3000 | 2.1900 | 7.3000 | 0.3000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 32.07 | 32.07 | 0.34 | 0.34 | 32.0737 | 16.0368 | 32.0737 | 0.5000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.78 | 0.78 | 0.02 | 0.02 | 0.7769 | 0.7769 | 0.7769 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 7.48 | 7.48 | 0.16 | 0.16 | 7.4831 | 7.4831 | 7.4831 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.76 | 0.76 | 0.02 | 0.02 | 0.7586 | 0.7586 | 0.7586 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 30973.891 | 30973.891 | 2.279928 | 0.00027097 | 649.285 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30973.89 | 30973.89 | 2.279928 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00799998 | 50.9129 | 8619.77 | 0.00 | 31126.13 | 31126.13 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 591577.091 | 591577.091 | 25.061967 | 0.00517537 | 13859.283 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 591577.09 | 591577.09 | 25.061967 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 345850.82 | 0.00 | 594286.09 | 594286.09 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 209074.280 | 209074.280 | 8.941379 | 0.00182907 | 4885.208 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 209074.28 | 207761.12 | 8.941379 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 121406.31 | 0.00 | 210032.70 | 210032.70 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 37142.304 | 37142.304 | 1.590255 | 0.00032494 | 867.589 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 37142.30 | 36951.03 | 1.590255 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798568 | 50.8233 | 21550.79 | 0.00 | 37312.59 | 37312.59 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 25245.429 | 25245.429 | 1.081019 | 0.00022086 | 589.676 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25245.43 | 25245.43 | 1.081019 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798596 | 50.8250 | 14646.67 | 0.00 | 25361.17 | 25361.17 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 39865.672 | 39865.672 | 1.707102 | 0.00034876 | 931.166 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39865.67 | 39865.67 | 1.707102 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798665 | 50.8294 | 23128.51 | 0.00 | 40048.45 | 40048.45 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 21088.769 | 21088.769 | 0.902616 | 0.00018449 | 492.648 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21088.77 | 21088.77 | 0.902616 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798311 | 50.8071 | 12239.19 | 0.00 | 21185.45 | 21185.45 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 468164.445 | 468164.445 | 20.054063 | 0.00409571 | 10934.187 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 468164.44 | 465974.50 | 20.054063 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797333 | 50.7459 | 271552.59 | 0.00 | 470310.96 | 470310.96 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 311126.453 | 311126.453 | 13.328005 | 0.00272187 | 7266.383 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 311126.45 | 311126.45 | 13.328005 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797323 | 50.7453 | 180457.57 | 0.00 | 312552.97 | 312552.97 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 463673.353 | 463673.353 | 19.861319 | 0.00405642 | 10829.351 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 463673.35 | 463673.35 | 19.861319 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797307 | 50.7443 | 268951.27 | 0.00 | 465799.27 | 465799.27 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 299677.885 | 299677.885 | 12.836762 | 0.00262171 | 6999.123 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 299677.88 | 299677.88 | 12.836762 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797224 | 50.7391 | 173825.43 | 0.00 | 301051.90 | 301051.90 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 62540.220 | 62540.220 | 2.680089 | 0.00054713 | 1460.481 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 62540.22 | 62274.33 | 2.680089 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797506 | 50.7569 | 36264.39 | 0.00 | 62826.98 | 62826.98 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 41210.121 | 41210.121 | 1.766063 | 0.00036052 | 962.359 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 41210.12 | 41188.09 | 1.766063 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797476 | 50.7550 | 23895.50 | 0.00 | 41399.08 | 41399.08 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 62059.358 | 62059.358 | 2.659455 | 0.00054292 | 1449.256 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 62059.36 | 62059.36 | 2.659455 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797486 | 50.7557 | 35985.84 | 0.00 | 62343.91 | 62343.91 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 40606.346 | 40606.346 | 1.740167 | 0.00035524 | 948.262 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40606.35 | 40606.35 | 1.740167 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797441 | 50.7528 | 23545.62 | 0.00 | 40792.53 | 40792.53 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 213002.641 | -999.000 | 12.535278 | 0.00760796 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 213002.64 | 205194.30 | 12.535278 | 24.55 | 15.33 | 0.00724410 | 11.08 | 9.67 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 16.1983 | 24.00 | 0.00728992 | 38.7089 | 146078.25 | 0.00 | 216149.47 | 216149.47 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 121035.406 | 121035.406 | 3.760583 | 0.00105887 | 1884.322 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:30:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 121035.41 | 121035.41 | 3.760583 | -14.13 | -14.13 | 0.00369786 | 12.89 | 11.49 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 53.9943 | 18.61 | 0.00796973 | 58.8191 | 15268.14 | 0.00 | 99967.70 | 99967.70 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1989293.266 | -999.000 | 116.443616 | 0.07105295 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 1989293.27 | 1912701.77 | 116.443616 | 24.59 | 15.36 | 0.00725753 | 11.08 | 9.67 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 17.4385 | 24.00 | 0.00731044 | 38.8166 | 1356863.50 | 0.00 | 2018540.84 | 2018540.84 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1229953.305 | 1229953.305 | 34.933085 | 0.01076017 | 18792.504 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 1229953.31 | 1229953.31 | 34.933085 | -16.67 | -16.67 | 0.00336282 | 12.89 | 11.49 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 58.1283 | 18.34 | 0.00796282 | 59.7960 | 165472.33 | 0.00 | 991061.56 | 991061.56 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 300317.087 | -999.000 | 17.787154 | 0.01072663 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 300317.09 | 289782.24 | 17.787154 | 24.51 | 15.30 | 0.00723257 | 11.10 | 9.67 | 0.00700000 | 27.30 | 0.00700699 | 16.11 | 11.4155 | 24.00 | 0.00727356 | 38.6230 | 153934.78 | 0.00 | 304772.74 | 304772.74 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 109864.075 | 109864.075 | 5.336146 | 0.00096114 | 1797.372 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 109864.08 | 109864.08 | 5.336146 | -4.40 | -4.40 | 0.00495128 | 12.89 | 11.49 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 38.0518 | 17.09 | 0.00798106 | 64.8482 | 19093.69 | 0.00 | 101002.33 | 101002.33 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 113439.884 | -999.000 | 7.300026 | 0.00405181 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 113439.88 | 107402.99 | 7.300026 | 23.37 | 14.98 | 0.00733432 | 11.07 | 9.66 | 0.00700000 | 19.85 | 0.00699585 | 13.32 | 16.4404 | 24.00 | 0.00740091 | 39.2918 | 85845.63 | 0.00 | 117535.99 | 117535.99 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.086362 | 0.00087484 | 2622.575 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.086362 | -6.89 | -10.92 | 0.00006450 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 38.8858 | 22.35 | 0.00006450 | 0.3828 | 0.00 | 0.00 | 100078.50 | 100078.50 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 451708.897 | -999.000 | 32.073662 | 0.01613400 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 451708.90 | 449726.94 | 32.073662 | 27.00 | 16.03 | 0.00703253 | 15.03 | 11.37 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 1.0550 | 27.00 | 0.00703280 | 31.2635 | 373383.83 | 0.00 | 472954.17 | 472954.17 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 100000.000 | 100000.000 | 3.086362 | 0.00087484 | 2622.575 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.086362 | -0.44 | -0.44 | 0.00692683 | 29.11 | 17.57 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 10.9641 | 27.00 | 0.00700000 | 31.1156 | 0.00 | 0.00 | 100078.50 | 100078.50 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER BOT | 12860.190 | 10296.640 | 0.776880 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 6430.10 | 6376.96 | 0.517920 | 26.90 | 16.01 | 0.00706115 | 14.46 | 11.13 | 0.00700000 | 21.84 | 0.00699878 | 14.10 | 3.0183 | 27.00 | 0.00706243 | 31.3921 | 9055.97 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER BOT | 27719.306 | 27719.306 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 27719.31 | 27719.31 | 0.776884 | -0.84 | -5.64 | 0.00067427 | 29.11 | 17.57 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 2.0122 | 24.85 | 0.00068679 | 3.5033 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER MID | 123871.930 | 99179.299 | 7.483100 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 61935.96 | 61405.35 | 4.988733 | 26.89 | 16.02 | 0.00706341 | 14.46 | 11.13 | 0.00700000 | 21.84 | 0.00699878 | 14.10 | 3.1335 | 27.00 | 0.00706479 | 31.4025 | 87228.59 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER MID | 267284.878 | 267284.878 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 267284.88 | 267284.88 | 7.483103 | -0.88 | -5.66 | 0.00067382 | 29.11 | 17.57 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 2.0890 | 23.57 | 0.00068682 | 3.7826 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER TOP | 12557.300 | 10054.128 | 0.758590 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | 6278.65 | 6225.58 | 0.505727 | 26.90 | 16.02 | 0.00706257 | 14.46 | 11.13 | 0.00700000 | 21.99 | 0.00699901 | 14.15 | 3.0911 | 27.00 | 0.00706390 | 31.3986 | 8842.66 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER TOP | 27084.823 | 27084.823 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 27084.82 | 27084.82 | 0.758587 | -0.86 | -5.66 | 0.00067306 | 29.11 | 17.57 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 2.0607 | 21.08 | 0.00068587 | 4.3932 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 30973.891 | 30973.891 | 2.279928 | 0.00027097 | 649.285 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.18196506 | 54.44 | 82.22 | 27.78 | 4452723.32 | 0.6956 | 0.709616 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30973.89 | 30973.89 | 1.0000 | 2.70271604 | 2.279928 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.27094547 | 60.00 | 32.22 | 27.78 | 0.000 | 30973.89 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.83 | 0.00799998 | 21.00 | 0.00799998 | 50.9129 | 8619.77 | 0.00 | 31126.13 | 31126.13 | 2.70271604 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 24.09 | 15.99 | 0.00800000 | 44576.4 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 591577.091 | 591577.091 | 25.061967 | 0.00517537 | 13859.283 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.18196506 | 54.44 | 82.22 | 27.78 | 4452723.32 | 13.2857 | 13.553117 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 591577.09 | 591577.09 | 1.0000 | 29.70944027 | 25.061967 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 5.17484652 | 60.00 | 32.22 | 27.78 | 0.000 | 591577.09 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 345850.82 | 0.00 | 594286.09 | 594286.09 | 29.70944027 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.42 | 18.83 | 0.00800000 | 53063.1 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 209074.280 | 209074.280 | 8.941379 | 0.00182907 | 4885.208 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.18196506 | 54.44 | 82.22 | 27.78 | 4452723.32 | 4.6954 | 4.789922 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 209074.28 | 207761.12 | 1.0000 | 10.59946209 | 8.941379 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 1.82888643 | 60.00 | 32.22 | 27.78 | 0.000 | 209074.28 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 121406.31 | 0.00 | 210032.70 | 210032.70 | 10.59946209 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52875.2 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 37142.304 | 37142.304 | 1.590255 | 0.00032494 | 867.589 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.18196506 | 54.44 | 82.22 | 27.78 | 4452723.32 | 0.8341 | 0.850936 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 37142.30 | 36951.03 | 1.0000 | 1.88515070 | 1.590255 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.32490393 | 60.00 | 32.22 | 27.78 | 0.000 | 37142.30 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798568 | 21.00 | 0.00798568 | 50.8233 | 21550.79 | 0.00 | 37312.59 | 37312.59 | 1.88515070 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52852.7 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25245.429 | 25245.429 | 1.081019 | 0.00022086 | 589.676 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.18196506 | 54.44 | 82.22 | 27.78 | 4452723.32 | 0.5670 | 0.578376 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25245.43 | 25245.43 | 1.0000 | 1.28148278 | 1.081019 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.22083550 | 60.00 | 32.22 | 27.78 | 0.000 | 25245.43 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798596 | 21.00 | 0.00798596 | 50.8250 | 14646.67 | 0.00 | 25361.17 | 25361.17 | 1.28148278 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.76 | 0.00800000 | 52850.3 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 39865.672 | 39865.672 | 1.707102 | 0.00034876 | 931.166 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.18196506 | 54.44 | 82.22 | 27.78 | 4452723.32 | 0.8953 | 0.913328 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39865.67 | 39865.67 | 1.0000 | 2.02366562 | 1.707102 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.34872672 | 60.00 | 32.22 | 27.78 | 0.000 | 39865.67 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798665 | 21.00 | 0.00798665 | 50.8294 | 23128.51 | 0.00 | 40048.45 | 40048.45 | 2.02366562 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.76 | 0.00800000 | 52849.9 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21088.769 | 21088.769 | 0.902616 | 0.00018449 | 492.648 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.18196506 | 54.44 | 82.22 | 27.78 | 4452723.32 | 0.4736 | 0.483147 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21088.77 | 21088.77 | 1.0000 | 1.06999704 | 0.902616 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.18447493 | 60.00 | 32.22 | 27.78 | 0.000 | 21088.77 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798311 | 21.00 | 0.00798311 | 50.8071 | 12239.19 | 0.00 | 21185.45 | 21185.45 | 1.06999704 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52859.4 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 468164.445 | 468164.445 | 20.054063 | 0.00409571 | 10934.187 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.18196506 | 54.44 | 82.22 | 27.78 | 4452723.32 | 10.5141 | 10.725716 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 468164.44 | 465974.50 | 1.0000 | 23.77287469 | 20.054063 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 4.09528899 | 60.00 | 32.22 | 27.78 | 0.000 | 468164.44 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797333 | 21.00 | 0.00797333 | 50.7459 | 271552.59 | 0.00 | 470310.96 | 470310.96 | 23.77287469 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52843.3 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 311126.453 | 311126.453 | 13.328005 | 0.00272187 | 7266.383 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.18196506 | 54.44 | 82.22 | 27.78 | 4452723.32 | 6.9873 | 7.127952 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 311126.45 | 311126.45 | 1.0000 | 15.79954061 | 13.328005 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 2.72159228 | 60.00 | 32.22 | 27.78 | 0.000 | 311126.45 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797323 | 21.00 | 0.00797323 | 50.7453 | 180457.57 | 0.00 | 312552.97 | 312552.97 | 15.79954061 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52842.2 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 463673.353 | 463673.353 | 19.861319 | 0.00405642 | 10829.351 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.18196506 | 54.44 | 82.22 | 27.78 | 4452723.32 | 10.4133 | 10.622824 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 463673.35 | 463673.35 | 1.0000 | 23.54438835 | 19.861319 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 4.05600297 | 60.00 | 32.22 | 27.78 | 0.000 | 463673.35 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797307 | 21.00 | 0.00797307 | 50.7443 | 268951.27 | 0.00 | 465799.27 | 465799.27 | 23.54438835 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52843.7 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 299677.885 | 299677.885 | 12.836762 | 0.00262171 | 6999.123 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.18196506 | 54.44 | 82.22 | 27.78 | 4452723.32 | 6.7302 | 6.865664 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 299677.88 | 299677.88 | 1.0000 | 15.21720179 | 12.836762 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 2.62144543 | 60.00 | 32.22 | 27.78 | 0.000 | 299677.88 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797224 | 21.00 | 0.00797224 | 50.7391 | 173825.43 | 0.00 | 301051.90 | 301051.90 | 15.21720179 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52843.5 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 62540.220 | 62540.220 | 2.680089 | 0.00054713 | 1460.481 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.18196506 | 54.44 | 82.22 | 27.78 | 4452723.32 | 1.4045 | 1.432806 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 62540.22 | 62274.33 | 1.0000 | 3.17708323 | 2.680089 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.54707331 | 60.00 | 32.22 | 27.78 | 0.000 | 62540.22 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.94 | 0.00797506 | 21.00 | 0.00797506 | 50.7569 | 36264.39 | 0.00 | 62826.98 | 62826.98 | 3.17708323 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52834.9 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 41210.121 | 41210.121 | 1.766063 | 0.00036052 | 962.359 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.18196506 | 54.44 | 82.22 | 27.78 | 4452723.32 | 0.9255 | 0.944130 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 41210.12 | 41188.09 | 1.0000 | 2.09356068 | 1.766063 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.36048734 | 60.00 | 32.22 | 27.78 | 0.000 | 41210.12 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.94 | 0.00797476 | 21.00 | 0.00797476 | 50.7550 | 23895.50 | 0.00 | 41399.08 | 41399.08 | 2.09356068 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52834.3 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 62059.358 | 62059.358 | 2.659455 | 0.00054292 | 1449.256 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.18196506 | 54.44 | 82.22 | 27.78 | 4452723.32 | 1.3937 | 1.421789 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 62059.36 | 62059.36 | 1.0000 | 3.15262225 | 2.659455 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.54286695 | 60.00 | 32.22 | 27.78 | 0.000 | 62059.36 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.94 | 0.00797486 | 21.00 | 0.00797486 | 50.7557 | 35985.84 | 0.00 | 62343.91 | 62343.91 | 3.15262225 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52835.1 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 40606.346 | 40606.346 | 1.740167 | 0.00035524 | 948.262 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.18196506 | 54.44 | 82.22 | 27.78 | 4452723.32 | 0.9119 | 0.930297 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 40606.35 | 40606.35 | 1.0000 | 2.06286285 | 1.740167 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.35520579 | 60.00 | 32.22 | 27.78 | 0.000 | 40606.35 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.94 | 0.00797441 | 21.00 | 0.00797441 | 50.7528 | 23545.62 | 0.00 | 40792.53 | 40792.53 | 2.06286285 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52834.5 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 213002.641 | -999.000 | 12.535278 | 0.00760796 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3064 | 1004.8586 | 1.1854 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 12.535278 | 14.85981064 | 4197.9300 | 999.8980 | 109.56216499 | 13.34 | 6.67 | 6.67 | 3067761.78 | 6.9433 | 6.943259 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 213002.64 | 205194.30 | 1.0000 | 14.85981064 | 12.535278 | 24.55 | 15.33 | 0.00724410 | 43116.4 | 11.08 | 9.67 | 0.00700000 | 28782.3 | 7.60718473 | 6.67 | 13.34 | 6.67 | 27403.410 | 185599.23 | 27.40 | 0.00700714 | 16.15 | 2.03050000 | 16.1983 | 24.00 | 0.00728992 | 24.00 | 0.00728992 | 38.7089 | 146078.25 | 0.00 | 216149.47 | 216149.47 | 14.85981064 | 24.55 | 15.49 | 0.00724410 | 43116.4 | 10.27 | 9.70 | 0.00724410 | 28570.5 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 121035.406 | 121035.406 | 3.760583 | 0.00105887 | 1884.322 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 12.535278 | 14.85981064 | 4197.9300 | 999.8980 | 38.18196506 | 54.44 | 82.22 | 27.78 | 4452723.32 | 2.7182 | 2.772939 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:30:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 121035.41 | 121035.41 | 1.0000 | 4.45794319 | 3.760583 | -14.13 | -14.13 | 0.00369786 | -5047.7 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 1.05876252 | 60.00 | 32.22 | 27.78 | 0.000 | 121035.41 | -41.90 | 0.00006450 | -41.90 | 2.03050000 | 53.9943 | 18.46 | 0.00796212 | 18.61 | 0.00796973 | 58.8191 | 15268.14 | 0.00 | 99967.70 | 99967.70 | 4.45794319 | 2.80 | 1.52 | 0.00369786 | 12080.9 | 24.96 | 12.28 | 0.00369786 | 34505.5 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1989293.266 | -999.000 | 116.443616 | 0.07105295 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3314 | 1004.8586 | 1.1854 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 116.443616 | 138.03683819 | 4197.9300 | 999.8980 | 109.56216499 | 13.34 | 6.67 | 6.67 | 3067761.78 | 64.8451 | 64.845102 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 1989293.27 | 1912701.77 | 1.0000 | 138.03683819 | 116.443616 | 24.59 | 15.36 | 0.00725753 | 43193.6 | 11.08 | 9.67 | 0.00700000 | 28782.3 | 71.04569813 | 6.67 | 13.34 | 6.67 | 254557.758 | 1734735.51 | 27.40 | 0.00700714 | 16.15 | 20.30600000 | 17.4385 | 24.00 | 0.00731044 | 24.00 | 0.00731044 | 38.8166 | 1356863.50 | 0.00 | 2018540.84 | 2018540.84 | 138.03683819 | 24.59 | 15.51 | 0.00725753 | 43193.6 | 10.23 | 9.70 | 0.00725753 | 28570.4 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1229953.305 | 1229953.305 | 34.933085 | 0.01076017 | 18792.504 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 116.443616 | 138.03683819 | 4197.9300 | 999.8980 | 38.18196506 | 54.44 | 82.22 | 27.78 | 4452723.32 | 27.6225 | 28.178409 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 1229953.31 | 1229953.31 | 1.0000 | 41.41105146 | 34.933085 | -16.67 | -16.67 | 0.00336282 | -8443.2 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 10.75907042 | 60.00 | 32.22 | 27.78 | 0.000 | 1229953.31 | -41.90 | 0.00006450 | -41.90 | 20.30600000 | 58.1283 | 18.36 | 0.00794170 | 18.34 | 0.00796282 | 59.7960 | 165472.33 | 0.00 | 991061.56 | 991061.56 | 41.41105146 | 2.80 | 1.05 | 0.00336282 | 11241.3 | 26.47 | 12.56 | 0.00336282 | 35173.6 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 300317.087 | -999.000 | 17.787154 | 0.01072663 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.2850 | 1004.8586 | 1.1854 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 17.787154 | 21.08559110 | 4197.9300 | 999.8980 | 109.56216499 | 13.34 | 6.67 | 6.67 | 3067761.78 | 9.7895 | 9.789453 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 300317.09 | 289782.24 | 1.0000 | 21.08559110 | 17.787154 | 24.51 | 15.30 | 0.00723257 | 43042.5 | 11.10 | 9.67 | 0.00700000 | 28799.7 | 10.72553629 | 6.67 | 13.34 | 6.67 | 38516.173 | 261800.91 | 27.30 | 0.00700699 | 16.11 | 2.03050000 | 11.4155 | 24.00 | 0.00727356 | 24.00 | 0.00727356 | 38.6230 | 153934.78 | 0.00 | 304772.74 | 304772.74 | 21.08559110 | 24.51 | 15.46 | 0.00723257 | 43042.5 | 10.31 | 9.71 | 0.00723257 | 28588.4 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 109864.075 | 109864.075 | 5.336146 | 0.00096114 | 1797.372 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 17.787154 | 21.08559110 | 4197.9300 | 999.8980 | 38.18196506 | 54.44 | 82.22 | 27.78 | 4452723.32 | 2.4673 | 2.517002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 109864.08 | 109864.08 | 1.0000 | 6.32567733 | 5.336146 | -4.40 | -4.40 | 0.00495128 | 7926.1 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 0.96104081 | 60.00 | 32.22 | 27.78 | 0.000 | 109864.08 | -41.90 | 0.00006450 | -41.90 | 2.03050000 | 38.0518 | 18.64 | 0.00795299 | 17.09 | 0.00798106 | 64.8482 | 19093.69 | 0.00 | 101002.33 | 101002.33 | 6.32567733 | 2.80 | 2.80 | 0.00495128 | 15222.2 | 18.55 | 10.88 | 0.00495128 | 31189.2 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 113439.884 | -999.000 | 7.300026 | 0.00405181 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4741 | 1004.8586 | 1.1854 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 7.300026 | 8.65373797 | 4197.9300 | 999.8980 | 109.56216499 | 13.34 | 6.67 | 6.67 | 3067761.78 | 3.6978 | 3.697806 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 113439.88 | 107402.99 | 1.0000 | 8.65373797 | 7.300026 | 23.37 | 14.98 | 0.00733432 | 42143.8 | 11.07 | 9.66 | 0.00700000 | 28772.7 | 4.05139650 | 6.67 | 13.34 | 6.67 | 16043.859 | 97396.02 | 19.85 | 0.00699585 | 13.32 | 1.20015641 | 16.4404 | 24.06 | 0.00740091 | 24.00 | 0.00740091 | 39.2918 | 85845.63 | 0.00 | 117535.99 | 117535.99 | 8.65373797 | 23.37 | 15.13 | 0.00733432 | 42143.8 | 10.03 | 9.69 | 0.00733432 | 28561.7 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.086362 | 0.00087484 | 2622.575 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 7.300026 | 8.65373797 | 4197.9300 | 999.8980 | 38.18196506 | 54.44 | 82.22 | 27.78 | 4452723.32 | 2.2458 | 2.291015 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.086362 | -6.89 | -10.92 | 0.00006450 | -6761.4 | 32.11 | 18.56 | 0.00800000 | 52750.5 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -41.90 | 0.00006450 | -41.90 | 1.20015641 | 38.8858 | 0.00 | 0.00006450 | 22.35 | 0.00006450 | 0.3828 | 0.00 | 0.00 | 100078.50 | 100078.50 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40240.8 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 451708.897 | -999.000 | 32.073662 | 0.01613400 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9131 | 1004.8586 | 1.1854 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 32.073662 | 38.02137889 | 4197.9300 | 999.8980 | 109.56216499 | 13.34 | 6.67 | 6.67 | 3067761.78 | 14.7244 | 14.724380 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 451708.90 | 449726.94 | 1.0000 | 38.02137889 | 32.073662 | 27.00 | 16.03 | 0.00703253 | 45073.8 | 15.03 | 11.37 | 0.00700000 | 32803.4 | 16.13234934 | 6.67 | 13.34 | 6.67 | 33297.552 | 418411.34 | 27.40 | 0.00700714 | 16.15 | 0.33839277 | 1.0550 | 27.00 | 0.00703280 | 27.00 | 0.00703280 | 31.2635 | 373383.83 | 0.00 | 472954.17 | 472954.17 | 38.02137889 | 27.00 | 16.19 | 0.00703253 | 45073.8 | 14.78 | 11.44 | 0.00703253 | 32634.7 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.086362 | 0.00087484 | 2622.575 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 32.073662 | 38.02137889 | 4197.9300 | 999.8980 | 38.18196506 | 54.44 | 82.22 | 27.78 | 4452723.32 | 2.2458 | 2.291015 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.086362 | -0.44 | -0.44 | 0.00692683 | 16873.7 | 29.11 | 17.57 | 0.00800000 | 49691.3 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -41.90 | 0.00006450 | -41.90 | 0.33839277 | 10.9641 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.1156 | 0.00 | 0.00 | 100078.50 | 100078.50 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40240.8 | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12860.190 | 10296.640 | 0.776880 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9663 | 1004.8586 | 1.1854 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.776884 | 0.92094893 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | Sensible | 6430.10 | 6376.96 | 1.0000 | 0.61396272 | 0.517920 | 26.90 | 16.01 | 0.00706115 | 45037.8 | 14.46 | 11.13 | 0.00700000 | 32228.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6430.10 | 21.84 | 0.00699878 | 14.10 | 0.01563234 | 3.0183 | 27.00 | 0.00706243 | 27.00 | 0.00706243 | 31.3921 | 9055.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27719.306 | 27719.306 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.776884 | 0.92094893 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 27719.31 | 27719.31 | 1.0000 | 0.92094893 | 0.776884 | -0.84 | -5.64 | 0.00067427 | 838.1 | 29.11 | 17.57 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27719.31 | -41.90 | 0.00006450 | -41.90 | 0.01563234 | 2.0122 | 0.00 | 0.00068679 | 24.85 | 0.00068679 | 3.5033 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 123871.930 | 99179.299 | 7.483100 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9705 | 1004.8586 | 1.1854 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.483103 | 8.87076463 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | Sensible | 61935.96 | 61405.35 | 1.0000 | 5.91384052 | 4.988733 | 26.89 | 16.02 | 0.00706341 | 45039.5 | 14.46 | 11.13 | 0.00700000 | 32228.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61935.96 | 21.84 | 0.00699878 | 14.10 | 0.15632344 | 3.1335 | 27.00 | 0.00706479 | 27.00 | 0.00706479 | 31.4025 | 87228.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 267284.878 | 267284.878 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.483103 | 8.87076463 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 267284.88 | 267284.88 | 1.0000 | 8.87076463 | 7.483103 | -0.88 | -5.66 | 0.00067382 | 804.6 | 29.11 | 17.57 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 267284.88 | -41.90 | 0.00006450 | -41.90 | 0.15632344 | 2.0890 | 0.00 | 0.00068682 | 23.57 | 0.00068682 | 3.7826 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12557.300 | 10054.128 | 0.758590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9690 | 1004.8586 | 1.1854 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.758587 | 0.89925828 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | Sensible | 6278.65 | 6225.58 | 1.0000 | 0.59950826 | 0.505727 | 26.90 | 16.02 | 0.00706257 | 45042.0 | 14.46 | 11.13 | 0.00700000 | 32228.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6278.65 | 21.99 | 0.00699901 | 14.15 | 0.01563234 | 3.0911 | 27.00 | 0.00706390 | 27.00 | 0.00706390 | 31.3986 | 8842.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27084.823 | 27084.823 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.758587 | 0.89925828 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 27084.82 | 27084.82 | 1.0000 | 0.89925828 | 0.758587 | -0.86 | -5.66 | 0.00067306 | 814.6 | 29.11 | 17.57 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27084.82 | -41.90 | 0.00006450 | -41.90 | 0.01563234 | 2.0607 | 0.00 | 0.00068587 | 21.08 | 0.00068587 | 4.3932 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 12.54 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 116.44 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 17.79 | - | |||
CAV_BAS_OA_CONTROLLER | FixedDryBulb | 1.20 | 7.30 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 32.07 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1052.17 | 3744.33 | 70.50 |
CORE_BOTTOM | 1172.83 | 3235.67 | 82.33 |
CORE_MID | 1335.83 | 4017.17 | 715.33 |
CORE_TOP | 2933.17 | 4879.83 | 2530.50 |
PERIMETER_BOT_ZN_3 | 3375.83 | 4413.50 | 2554.17 |
PERIMETER_BOT_ZN_2 | 3430.33 | 4378.67 | 2432.50 |
PERIMETER_BOT_ZN_1 | 3427.33 | 4298.33 | 2330.67 |
PERIMETER_BOT_ZN_4 | 3218.17 | 4106.00 | 1914.67 |
PERIMETER_MID_ZN_3 | 3505.00 | 5118.67 | 3133.83 |
PERIMETER_MID_ZN_2 | 3112.17 | 4018.67 | 2464.67 |
PERIMETER_MID_ZN_1 | 3573.83 | 4515.33 | 2578.33 |
PERIMETER_MID_ZN_4 | 3546.50 | 4973.33 | 2907.33 |
PERIMETER_TOP_ZN_3 | 3738.17 | 5510.17 | 3560.17 |
PERIMETER_TOP_ZN_2 | 3967.67 | 4841.33 | 3205.00 |
PERIMETER_TOP_ZN_1 | 3937.50 | 4724.83 | 3055.83 |
PERIMETER_TOP_ZN_4 | 3858.67 | 5088.17 | 3275.67 |
DATACENTER_BOT_ZN_6 | 5370.00 | 873.67 | 869.67 |
DATACENTER_MID_ZN_6 | 4265.17 | 642.50 | 363.17 |
DATACENTER_TOP_ZN_6 | 3469.00 | 1176.83 | 435.83 |
DATACENTER_BASEMENT_ZN_6 | 5931.83 | 3316.50 | 3315.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5893.00 | 5442.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 7.83 | 8.17 | 7.83 | 0.67 |
CORE_BOTTOM | 0.17 | 0.33 | 0.17 | 0.00 |
CORE_MID | 2.33 | 0.00 | 0.67 | 0.00 |
CORE_TOP | 35.00 | 0.00 | 1.83 | 0.00 |
PERIMETER_BOT_ZN_3 | 41.50 | 3.50 | 3.17 | 0.00 |
PERIMETER_BOT_ZN_2 | 56.00 | 7.33 | 6.17 | 6.17 |
PERIMETER_BOT_ZN_1 | 61.00 | 9.17 | 7.00 | 9.17 |
PERIMETER_BOT_ZN_4 | 12.83 | 17.50 | 0.00 | 6.83 |
PERIMETER_MID_ZN_3 | 229.67 | 0.50 | 54.00 | 0.00 |
PERIMETER_MID_ZN_2 | 482.00 | 5.50 | 56.67 | 5.33 |
PERIMETER_MID_ZN_1 | 182.33 | 10.17 | 36.17 | 10.17 |
PERIMETER_MID_ZN_4 | 155.00 | 6.50 | 31.17 | 1.33 |
PERIMETER_TOP_ZN_3 | 432.50 | 0.00 | 104.67 | 0.00 |
PERIMETER_TOP_ZN_2 | 423.17 | 3.83 | 94.00 | 3.83 |
PERIMETER_TOP_ZN_1 | 376.83 | 5.83 | 78.83 | 5.83 |
PERIMETER_TOP_ZN_4 | 340.33 | 4.83 | 80.50 | 0.83 |
DATACENTER_BOT_ZN_6 | 0.00 | 501.00 | 0.00 | 319.50 |
DATACENTER_MID_ZN_6 | 0.00 | 435.00 | 0.00 | 282.33 |
DATACENTER_TOP_ZN_6 | 0.00 | 370.50 | 0.00 | 236.17 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.67 | 0.00 | 0.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 872.50 | 566.00 | 156.83 | 358.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.91 | 149.60 | 6779.02 | 0.852 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.60 | 134.35 | 6849.35 | 0.831 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.60 | 134.35 | 6849.35 | 0.699 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.60 | 134.35 | 6849.35 | 0.665 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.98 | 16.87 | 860.00 | 1.087 | 0.028 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.50 | 10.87 | 554.22 | 1.861 | 0.029 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.98 | 16.87 | 860.02 | 1.930 | 0.028 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.50 | 10.87 | 554.22 | 2.068 | 0.029 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.98 | 16.87 | 860.00 | 1.227 | 0.065 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.93 | 10.87 | 554.22 | 1.797 | 0.072 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.98 | 16.87 | 860.02 | 1.996 | 0.065 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.50 | 10.87 | 554.22 | 1.828 | 0.067 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.98 | 16.87 | 860.00 | 1.426 | 0.080 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.50 | 10.87 | 554.22 | 1.720 | 0.083 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.98 | 16.87 | 860.02 | 1.842 | 0.080 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.50 | 10.87 | 554.22 | 1.704 | 0.083 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.429 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.46 | 42.18 | 1911.37 | 17.179 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.91 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.60 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.60 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.60 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.98 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.50 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.98 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.50 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.98 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.93 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.98 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.50 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.98 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.50 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.98 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.50 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.46 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.91 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.60 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.60 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.60 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.98 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.50 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.98 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.50 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.98 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.93 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.98 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.50 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.98 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.50 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.98 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.50 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.46 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1026.00 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 34040980.06 | 0.00 | 34040980.06 | 0.00 | 34040980.06 | 37848132.68 | 4327.30 | 3090.72 | 1341.97 | 102.21 |
CORE_BOTTOM | 34499766.20 | 0.00 | 34499766.20 | 0.00 | 34499766.20 | 33990283.35 | 6234.35 | 17.44 | 2508.21 | 413.92 |
CORE_MID | 0.29E+09 | 0.00 | 0.29E+09 | 0.00 | 0.29E+09 | 0.34E+09 | 6609.67 | 24.91 | 2125.42 | 754.55 |
CORE_TOP | 27214398.06 | 0.00 | 27214398.06 | 0.00 | 27214398.06 | 33990283.35 | 6710.04 | 17.46 | 2032.50 | 443.96 |
PERIMETER_BOT_ZN_3 | 5737027.29 | 0.00 | 5737027.29 | 288582.77 | 6025610.06 | 4267819.30 | 3955.92 | 26.14 | 4777.93 | 413.92 |
PERIMETER_BOT_ZN_2 | 6316123.42 | 0.00 | 6316123.42 | 192388.38 | 6508511.80 | 2750345.05 | 3791.76 | 7.00 | 4961.24 | 413.92 |
PERIMETER_BOT_ZN_1 | 10146301.13 | 0.00 | 10146301.13 | 288582.77 | 10434883.90 | 4267912.63 | 3789.92 | 6.29 | 4963.79 | 413.92 |
PERIMETER_BOT_ZN_4 | 7044179.60 | 0.00 | 7044179.60 | 192388.38 | 7236567.98 | 2750345.05 | 3703.55 | 11.56 | 5044.89 | 413.92 |
PERIMETER_MID_ZN_3 | 65162120.61 | 0.00 | 65162120.61 | 676813.33 | 65838933.94 | 42678193.03 | 3993.23 | 7.60 | 4759.17 | 754.55 |
PERIMETER_MID_ZN_2 | 59245422.75 | 0.00 | 59245422.75 | 451208.58 | 59696631.33 | 27503450.52 | 4430.61 | 11.40 | 4317.99 | 1154.52 |
PERIMETER_MID_ZN_1 | 0.10E+09 | 0.00 | 0.10E+09 | 676813.33 | 0.11E+09 | 42679126.27 | 3875.39 | 11.07 | 4873.53 | 754.55 |
PERIMETER_MID_ZN_4 | 62382988.97 | 0.00 | 62382988.97 | 451208.58 | 62834197.55 | 27503450.52 | 3854.53 | 12.45 | 4893.02 | 754.55 |
PERIMETER_TOP_ZN_3 | 7372437.52 | 0.00 | 7372437.52 | 840343.21 | 8212780.73 | 4267819.30 | 4108.81 | 4.80 | 4646.39 | 443.91 |
PERIMETER_TOP_ZN_2 | 5693505.10 | 0.00 | 5693505.10 | 560228.43 | 6253733.52 | 2750345.05 | 4102.09 | 3.18 | 4654.73 | 443.91 |
PERIMETER_TOP_ZN_1 | 9455634.96 | 0.00 | 9455634.96 | 840343.21 | 10295978.18 | 4267912.63 | 4094.17 | 3.43 | 4662.41 | 443.91 |
PERIMETER_TOP_ZN_4 | 5663686.27 | 0.00 | 5663686.27 | 560228.43 | 6223914.69 | 2750345.05 | 4087.87 | 3.34 | 4668.78 | 443.91 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.27E+09 | 0.00 | 0.27E+09 | 0.00 | 0.27E+09 | 10671554.30 | 573.08 | 647.09 | 7539.83 | 2498.12 |
Total Facility | 0.63E+10 | 0.00 | 0.63E+10 | 26323523.88 | 0.63E+10 | 0.50E+10 | 7053.56 | 4422.83 | 8282.21 | 3060.42 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.5723 | 0.0000 | 1.5723 | 0.0000 | 1.5723 | 1.2002 | 1535.51 | 3090.05 | 1317.44 |
CORE_BOTTOM | 1.5460 | 0.0000 | 1.5460 | 0.0000 | 1.5460 | 1.0778 | 3555.57 | 15.87 | 2371.56 |
CORE_MID | 13.0201 | 0.0000 | 13.0201 | 0.0000 | 13.0201 | 10.7782 | 3870.35 | 24.80 | 2047.85 |
CORE_TOP | 1.2421 | 0.0000 | 1.2421 | 0.0000 | 1.2421 | 1.0778 | 3937.58 | 17.42 | 1988.00 |
PERIMETER_BOT_ZN_3 | 0.2547 | 0.0000 | 0.2547 | 0.0065 | 0.2612 | 0.1353 | 1305.55 | 24.70 | 4612.75 |
PERIMETER_BOT_ZN_2 | 0.2813 | 0.0000 | 0.2813 | 0.0043 | 0.2856 | 0.0872 | 1205.44 | 3.77 | 4733.79 |
PERIMETER_BOT_ZN_1 | 0.4526 | 0.0000 | 0.4526 | 0.0065 | 0.4591 | 0.1353 | 1205.14 | 2.90 | 4734.96 |
PERIMETER_BOT_ZN_4 | 0.3125 | 0.0000 | 0.3125 | 0.0043 | 0.3168 | 0.0872 | 1165.79 | 4.17 | 4773.04 |
PERIMETER_MID_ZN_3 | 2.8846 | 0.0000 | 2.8846 | 0.0152 | 2.8999 | 1.3533 | 1313.72 | 3.36 | 4625.92 |
PERIMETER_MID_ZN_2 | 2.7198 | 0.0000 | 2.7198 | 0.0109 | 2.7306 | 0.8721 | 1255.15 | 5.77 | 3773.08 |
PERIMETER_MID_ZN_1 | 4.6845 | 0.0000 | 4.6845 | 0.0152 | 4.6997 | 1.3533 | 1257.79 | 5.92 | 4679.29 |
PERIMETER_MID_ZN_4 | 2.7687 | 0.0000 | 2.7687 | 0.0101 | 2.7789 | 0.8721 | 1249.35 | 4.70 | 4688.95 |
PERIMETER_TOP_ZN_3 | 0.3356 | 0.0000 | 0.3356 | 0.0189 | 0.3545 | 0.1353 | 1371.83 | 4.05 | 4567.12 |
PERIMETER_TOP_ZN_2 | 0.2602 | 0.0000 | 0.2602 | 0.0126 | 0.2728 | 0.0872 | 1366.29 | 2.12 | 4574.59 |
PERIMETER_TOP_ZN_1 | 0.4323 | 0.0000 | 0.4323 | 0.0189 | 0.4512 | 0.1353 | 1361.73 | 1.54 | 4579.72 |
PERIMETER_TOP_ZN_4 | 0.2581 | 0.0000 | 0.2581 | 0.0126 | 0.2707 | 0.0872 | 1358.41 | 1.86 | 4582.73 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8.8636 | 0.0000 | 8.8636 | 0.0000 | 8.8636 | 0.3384 | 208.21 | 646.12 | 5088.67 |
Total Facility | 277.7527 | 0.0000 | 277.7527 | 0.5991 | 278.3518 | 158.4706 | 4236.56 | 4382.84 | 5780.68 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 89576434.20 | 0.00 | 89576434.20 | 48026705.38 | 3887.00 | 7.06 | 4865.93 | 413.92 |
VAV_MID WITH REHEAT | 0.82E+09 | 0.00 | 0.82E+09 | 0.48E+09 | 4003.28 | 5.19 | 4751.54 | 754.55 |
VAV_TOP WITH REHEAT | 77851271.78 | 0.00 | 77851271.78 | 48026705.38 | 4130.38 | 2.31 | 4627.31 | 443.70 |
CAV_BAS | 47642146.74 | 0.00 | 47642146.74 | 37848132.68 | 4302.03 | 0.54 | 4457.43 | 102.21 |
AIRLOOP DATACENTER BASEMENT | 0.37E+09 | 0.00 | 0.37E+09 | 10671554.30 | 555.03 | 1.47 | 8203.50 | 2498.07 |
AIRLOOP DATACENTER BOT | 343300.97 | 0.00 | 343300.97 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3433009.67 | 0.00 | 3433009.67 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 343300.97 | 0.00 | 343300.97 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 4.0010 | 0.0000 | 4.0010 | 1.5229 | 1253.37 | 2.95 | 4686.68 |
VAV_MID WITH REHEAT | 36.5166 | 0.0000 | 36.5166 | 15.2292 | 1312.60 | 2.66 | 4627.73 |
VAV_TOP WITH REHEAT | 3.5530 | 0.0000 | 3.5530 | 1.5229 | 1384.33 | 1.01 | 4557.66 |
CAV_BAS | 2.2005 | 0.0000 | 2.2005 | 1.2002 | 1524.55 | 0.16 | 4418.30 |
AIRLOOP DATACENTER BASEMENT | 12.4558 | 0.0000 | 12.4558 | 0.3384 | 201.62 | 0.52 | 5740.86 |
AIRLOOP DATACENTER BOT | 0.0160 | 0.0000 | 0.0160 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1605 | 0.0000 | 0.1605 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0160 | 0.0000 | 0.0160 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 11.24 | 3245.19 | 0.00 | 0.00 | 0.00 | 2003.93 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 67.79 | 3839.59 | 0.00 | 0.00 | 0.00 | 1825.13 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 10.04 | 2936.99 | 0.00 | 0.00 | 0.00 | 2303.06 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 3112.98 | 1498.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 645.59 | 7610.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.6571 | 6.6347 | 0.0000 | 0.0000 | 0.0000 | 2.4793 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 28.9361 | 54.4669 | 0.0000 | 0.0000 | 0.0000 | 25.7804 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.6627 | 6.2119 | 0.0000 | 0.0000 | 0.0000 | 2.4327 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6871 | 5.6109 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4760 | 14.4205 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2197 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1343 |
Defaulted Fields | 1287 |
Fields with Defaults | 3878 |
Autosized Fields | 320 |
Autosizable Fields | 465 |
Autocalculated Fields | 223 |
Autocalculatable Fields | 468 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 30682.83 | 293299.73 | 04-SEP-18:10 | 2299393.13 | 10-AUG-15:30 |
Electricity:Building | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 758.19 | 15076.70 | 01-JAN-00:10 | 42602.33 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 589.38 | 5907.35 | 01-JAN-00:10 | 43380.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5893.79 | 59073.32 | 01-JAN-00:10 | 433806.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 589.38 | 5907.33 | 01-JAN-00:10 | 43380.63 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 740.04 | 7417.49 | 01-JAN-00:10 | 54469.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 476.91 | 4780.12 | 01-JAN-00:10 | 35102.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 740.05 | 7417.62 | 01-JAN-00:10 | 54470.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 476.91 | 4780.09 | 01-JAN-00:10 | 35102.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7588.97 | 95364.66 | 01-JAN-00:10 | 387850.11 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1622.27 | 19890.94 | 01-JAN-00:10 | 85232.07 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:HVAC | 4692.76 | 33335.30 | 04-SEP-08:20 | 405559.63 | 10-AUG-15:30 |
ExteriorEquipment:Electricity | 2623.11 | 22123.82 | 01-JAN-00:10 | 235096.12 | 03-APR-07:20 |
Transformer:ExteriorEquipment:Electricity | 56.04 | 979.82 | 01-JAN-00:10 | 3543.78 | 03-APR-14:20 |
ElectricityPurchased:Facility | 30682.83 | 293299.73 | 04-SEP-18:10 | 2299393.13 | 10-AUG-15:30 |
ElectricityPurchased:Plant | 30682.83 | 293299.73 | 04-SEP-18:10 | 2299393.13 | 10-AUG-15:30 |
Cogeneration:ElectricityPurchased | 30682.83 | 293299.73 | 04-SEP-18:10 | 2299393.13 | 10-AUG-15:30 |
General:Cogeneration:ElectricityPurchased | 30682.83 | 293299.73 | 04-SEP-18:10 | 2299393.13 | 10-AUG-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 30682.83 | 293299.73 | 04-SEP-18:10 | 2299393.13 | 10-AUG-15:30 |
ElectricityNet:Plant | 30682.83 | 293299.73 | 04-SEP-18:10 | 2299393.13 | 10-AUG-15:30 |
Cogeneration:ElectricityNet | 30682.83 | 293299.73 | 04-SEP-18:10 | 2299393.13 | 10-AUG-15:30 |
General:Cogeneration:ElectricityNet | 30682.83 | 293299.73 | 04-SEP-18:10 | 2299393.13 | 10-AUG-15:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1211.92 | 0.00 | 01-JAN-00:20 | 344180.58 | 21-JUL-12:10 |
General:Cooling:Electricity | 1211.92 | 0.00 | 01-JAN-00:20 | 344180.58 | 21-JUL-12:10 |
Fans:Electricity | 2789.43 | 25497.12 | 01-JAN-00:40 | 277543.21 | 10-AUG-15:30 |
General:Fans:Electricity | 2789.43 | 25497.12 | 01-JAN-00:40 | 277543.21 | 10-AUG-15:30 |
ExteriorLights:Electricity | 999.11 | 0.00 | 01-JAN-11:20 | 64082.80 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 999.11 | 0.00 | 01-JAN-11:20 | 64082.80 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.31 | 1944.00 | 01-JAN-00:10 | 1944.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1469.99 | 0.00 | 02-JUN-20:50 | 100000.00 | 01-APR-01:30 |
General:Humidifier:Electricity | 1469.99 | 0.00 | 02-JUN-20:50 | 100000.00 | 01-APR-01:30 |
Electricity:Plant | 2136.75 | 0.00 | 05-JAN-00:10 | 487136.39 | 21-JUL-12:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 553.91 | 0.00 | 01-JAN-00:10 | 63566.02 | 13-JAN-12:30 |
Water Heater:WaterSystems:Electricity | 553.91 | 0.00 | 01-JAN-00:10 | 63566.02 | 13-JAN-12:30 |
HeatRejection:Electricity | 24.21 | 0.00 | 01-JAN-00:10 | 47562.77 | 29-JUN-13:40 |
General:HeatRejection:Electricity | 24.21 | 0.00 | 01-JAN-00:10 | 47562.77 | 29-JUN-13:40 |
Pumps:Electricity | 724.00 | 0.00 | 05-JAN-00:10 | 83900.94 | 11-AUG-14:50 |
General:Pumps:Electricity | 724.00 | 0.00 | 05-JAN-00:10 | 83900.94 | 11-AUG-14:50 |
WIRED_LTG_ELECTRICITY | 157.66 | 0.00 | 01-JAN-00:10 | 13766.21 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 10772.98 | 0.00 | 01-JAN-00:40 | 3075343.59 | 27-FEB-07:20 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 10772.98 | 0.00 | 01-JAN-00:40 | 3075343.59 | 27-FEB-07:20 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 10772.98 | 0.00 | 01-JAN-00:40 | 3075343.59 | 27-FEB-07:20 |
Boiler:Heating:NaturalGas | 10772.98 | 0.00 | 01-JAN-00:40 | 3075343.59 | 27-FEB-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 4247.25 | 0.00 | 01-JAN-00:20 | 1985907.40 | 11-AUG-15:40 |
PlantLoopCoolingDemand:HVAC | 4247.25 | 0.00 | 01-JAN-00:20 | 1985907.40 | 11-AUG-15:40 |
CoolingCoils:PlantLoopCoolingDemand | 4247.25 | 0.00 | 01-JAN-00:20 | 1985907.40 | 11-AUG-15:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 5492.75 | 0.00 | 02-JUN-23:40 | 0.00 | 21-JUL-16:00 |
Water:HVAC | 546.84 | 0.00 | 02-JUN-20:50 | 0.00 | 01-APR-01:30 |
Humidifier:Water | 546.84 | 0.00 | 02-JUN-20:50 | 0.00 | 01-APR-01:30 |
General:Humidifier:Water | 546.84 | 0.00 | 02-JUN-20:50 | 0.00 | 01-APR-01:30 |
MainsWater:Facility | 5492.75 | 0.00 | 02-JUN-23:40 | 0.00 | 21-JUL-16:00 |
MainsWater:HVAC | 546.84 | 0.00 | 02-JUN-20:50 | 0.00 | 01-APR-01:30 |
Humidifier:MainsWater | 546.84 | 0.00 | 02-JUN-20:50 | 0.00 | 01-APR-01:30 |
General:Humidifier:MainsWater | 546.84 | 0.00 | 02-JUN-20:50 | 0.00 | 01-APR-01:30 |
Water:Plant | 4945.91 | 0.00 | 01-JAN-00:20 | 0.00 | 21-JUL-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
MainsWater:Plant | 4945.91 | 0.00 | 01-JAN-00:20 | 0.00 | 21-JUL-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 2665.75 | 0.00 | 01-JAN-00:20 | 0.00 | 21-JUL-16:00 |
General:HeatRejection:Water | 2665.75 | 0.00 | 01-JAN-00:20 | 0.00 | 21-JUL-16:00 |
HeatRejection:MainsWater | 2665.75 | 0.00 | 01-JAN-00:20 | 0.00 | 21-JUL-16:00 |
General:HeatRejection:MainsWater | 2665.75 | 0.00 | 01-JAN-00:20 | 0.00 | 21-JUL-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 56845.62 | 97419.60 | 01-JAN-00:40 | 10611108.55 | 11-AUG-14:40 |
EnergyTransfer:Building | 20842.32 | 87056.73 | 06-JAN-22:50 | 1841535.20 | 02-JAN-05:10 |
EnergyTransfer:Zone:BASEMENT | 727.90 | 0.00 | 01-JAN-00:10 | 83429.01 | 12-JAN-13:50 |
Heating:EnergyTransfer | 2746.41 | 0.00 | 01-MAR-22:10 | 1760678.57 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 1.99 | 0.00 | 01-JAN-00:10 | 28875.51 | 12-JAN-12:10 |
General:Heating:EnergyTransfer | 2746.41 | 0.00 | 01-MAR-22:10 | 1760678.57 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 1.99 | 0.00 | 01-JAN-00:10 | 28875.51 | 12-JAN-12:10 |
Cooling:EnergyTransfer | 18095.91 | 79125.39 | 02-JAN-05:50 | 1812411.31 | 11-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 725.91 | 0.00 | 01-JAN-00:10 | 79395.07 | 05-SEP-08:40 |
General:Cooling:EnergyTransfer | 18095.91 | 79125.39 | 02-JAN-05:50 | 1812411.31 | 11-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 725.91 | 0.00 | 01-JAN-00:10 | 79395.07 | 05-SEP-08:40 |
EnergyTransfer:Zone:CORE_BOTTOM | 552.99 | 0.00 | 01-JAN-00:40 | 57148.40 | 24-JUL-13:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.09 | 0.00 | 01-JAN-00:10 | 15114.56 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.09 | 0.00 | 01-JAN-00:10 | 15114.56 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 552.90 | 0.00 | 01-JAN-00:40 | 57148.40 | 24-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 552.90 | 0.00 | 01-JAN-00:40 | 57148.40 | 24-JUL-13:10 |
EnergyTransfer:Zone:CORE_MID | 4523.75 | 0.00 | 01-JAN-00:40 | 538214.26 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 34.49 | 0.00 | 01-JAN-00:20 | 538214.26 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 34.49 | 0.00 | 01-JAN-00:20 | 538214.26 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4489.26 | 0.00 | 01-JAN-00:40 | 490177.59 | 12-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4489.26 | 0.00 | 01-JAN-00:40 | 490177.59 | 12-JUL-16:00 |
EnergyTransfer:Zone:CORE_TOP | 407.03 | 0.00 | 01-JAN-00:40 | 104229.41 | 27-FEB-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 68.92 | 0.00 | 01-JAN-00:40 | 104229.41 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 68.92 | 0.00 | 01-JAN-00:40 | 104229.41 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 338.11 | 0.00 | 01-JAN-00:20 | 55280.22 | 21-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 338.11 | 0.00 | 01-JAN-00:20 | 55280.22 | 21-JUL-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 78.19 | 0.00 | 01-JAN-00:40 | 17463.82 | 27-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 22.26 | 0.00 | 01-JAN-00:40 | 17463.82 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 22.26 | 0.00 | 01-JAN-00:40 | 17463.82 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 55.92 | 0.00 | 01-JAN-00:20 | 12714.17 | 11-JUL-05:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 55.92 | 0.00 | 01-JAN-00:20 | 12714.17 | 11-JUL-05:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 77.59 | 0.00 | 01-JAN-00:40 | 18250.13 | 07-JUL-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 17.08 | 0.00 | 01-JAN-00:40 | 12364.04 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 17.08 | 0.00 | 01-JAN-00:40 | 12364.04 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 60.50 | 0.00 | 01-JAN-00:20 | 18250.13 | 07-JUL-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 60.50 | 0.00 | 01-JAN-00:20 | 18250.13 | 07-JUL-08:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 127.59 | 0.00 | 01-JAN-00:40 | 27339.33 | 10-AUG-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 25.22 | 0.00 | 01-JAN-00:40 | 19268.24 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 25.22 | 0.00 | 01-JAN-00:40 | 19268.24 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 102.36 | 0.00 | 01-JAN-00:20 | 27339.33 | 10-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 102.36 | 0.00 | 01-JAN-00:20 | 27339.33 | 10-AUG-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 80.91 | 0.00 | 01-JAN-00:40 | 17671.73 | 10-AUG-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 3.99 | 0.00 | 01-JAN-00:20 | 9737.90 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 3.99 | 0.00 | 01-JAN-00:20 | 9737.90 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 76.91 | 0.00 | 01-JAN-00:40 | 17671.73 | 10-AUG-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 76.91 | 0.00 | 01-JAN-00:40 | 17671.73 | 10-AUG-17:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1057.69 | 0.00 | 01-JAN-00:40 | 247639.08 | 24-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 603.82 | 0.00 | 01-JAN-00:40 | 247639.08 | 24-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 603.82 | 0.00 | 01-JAN-00:40 | 247639.08 | 24-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 453.87 | 0.00 | 01-JAN-00:20 | 109697.02 | 11-JUL-05:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 453.87 | 0.00 | 01-JAN-00:20 | 109697.02 | 11-JUL-05:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 877.72 | 0.00 | 01-JAN-00:40 | 193855.55 | 07-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 366.62 | 0.00 | 01-JAN-00:40 | 170872.56 | 24-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 366.62 | 0.00 | 01-JAN-00:40 | 170872.56 | 24-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 511.10 | 0.00 | 01-JAN-00:20 | 193855.55 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 511.10 | 0.00 | 01-JAN-00:20 | 193855.55 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1438.16 | 0.00 | 01-JAN-00:40 | 291862.00 | 10-AUG-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 474.03 | 0.00 | 01-JAN-00:40 | 254568.51 | 24-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 474.03 | 0.00 | 01-JAN-00:40 | 254568.51 | 24-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 964.13 | 0.00 | 01-JAN-00:20 | 291862.00 | 10-AUG-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 964.13 | 0.00 | 01-JAN-00:20 | 291862.00 | 10-AUG-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 774.40 | 0.00 | 01-JAN-00:40 | 161545.86 | 06-JUL-17:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 305.50 | 0.00 | 01-JAN-00:40 | 160862.11 | 24-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 305.50 | 0.00 | 01-JAN-00:40 | 160862.11 | 24-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 468.90 | 0.00 | 01-JAN-00:20 | 161545.86 | 06-JUL-17:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 468.90 | 0.00 | 01-JAN-00:20 | 161545.86 | 06-JUL-17:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 153.53 | 0.00 | 01-JAN-00:40 | 31976.40 | 24-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 109.92 | 0.00 | 01-JAN-00:40 | 31976.40 | 24-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 109.92 | 0.00 | 01-JAN-00:40 | 31976.40 | 24-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 43.61 | 0.00 | 01-JAN-00:20 | 11025.04 | 30-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 43.61 | 0.00 | 01-JAN-00:20 | 11025.04 | 30-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 114.62 | 0.00 | 01-JAN-00:40 | 20936.15 | 24-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 67.31 | 0.00 | 01-JAN-00:40 | 20936.15 | 24-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 67.31 | 0.00 | 01-JAN-00:40 | 20936.15 | 24-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 47.31 | 0.00 | 01-JAN-00:20 | 19057.10 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 47.31 | 0.00 | 01-JAN-00:20 | 19057.10 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 175.25 | 0.00 | 01-JAN-00:40 | 31770.65 | 24-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 90.26 | 0.00 | 01-JAN-00:40 | 31770.65 | 24-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 90.26 | 0.00 | 01-JAN-00:40 | 31770.65 | 24-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 84.99 | 0.00 | 01-JAN-00:20 | 29620.99 | 10-AUG-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 84.99 | 0.00 | 01-JAN-00:20 | 29620.99 | 10-AUG-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 98.55 | 0.00 | 01-JAN-00:40 | 20682.18 | 24-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 56.22 | 0.00 | 01-JAN-00:40 | 20682.18 | 24-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 56.22 | 0.00 | 01-JAN-00:40 | 20682.18 | 24-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 42.34 | 0.00 | 01-JAN-00:20 | 16627.76 | 11-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 42.34 | 0.00 | 01-JAN-00:20 | 16627.76 | 11-JUL-17:40 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 72.41 | 0.00 | 01-JAN-00:40 | 14448.61 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 5.85 | 0.00 | 01-JAN-00:20 | 14448.61 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 5.85 | 0.00 | 01-JAN-00:20 | 14448.61 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 66.57 | 0.00 | 01-JAN-00:40 | 10259.30 | 05-JUL-05:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 66.57 | 0.00 | 01-JAN-00:40 | 10259.30 | 05-JUL-05:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 823.07 | 0.00 | 01-JAN-00:40 | 239948.15 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 240.67 | 0.00 | 01-JAN-00:40 | 239948.15 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 240.67 | 0.00 | 01-JAN-00:40 | 239948.15 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 582.41 | 0.00 | 01-JAN-00:10 | 111124.19 | 18-FEB-03:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 582.41 | 0.00 | 01-JAN-00:10 | 111124.19 | 18-FEB-03:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 268.21 | 0.00 | 01-JAN-00:40 | 55823.77 | 27-FEB-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 217.52 | 0.00 | 01-JAN-00:40 | 55823.77 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 217.52 | 0.00 | 01-JAN-00:40 | 55823.77 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 50.70 | 0.00 | 01-JAN-00:10 | 22844.60 | 21-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 50.70 | 0.00 | 01-JAN-00:10 | 22844.60 | 21-JUL-14:30 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 120.53 | 4.58 | 15-DEC-17:10 | 11579.24 | 14-DEC-14:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 1.77 | 0.00 | 02-JAN-09:10 | 1359.28 | 12-JAN-01:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 1.77 | 0.00 | 02-JAN-09:10 | 1359.28 | 12-JAN-01:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 118.76 | 0.00 | 01-JAN-00:10 | 11579.24 | 14-DEC-14:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 118.76 | 0.00 | 01-JAN-00:10 | 11579.24 | 14-DEC-14:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1032.39 | 6.54 | 20-FEB-23:00 | 110120.20 | 14-DEC-14:10 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 25.05 | 0.00 | 03-JAN-12:20 | 13208.98 | 13-JAN-00:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 25.05 | 0.00 | 03-JAN-12:20 | 13208.98 | 13-JAN-00:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1007.35 | 0.00 | 01-JAN-00:10 | 110120.20 | 14-DEC-14:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1007.35 | 0.00 | 01-JAN-00:10 | 110120.20 | 14-DEC-14:10 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 89.49 | 1.69 | 15-DEC-14:40 | 10173.06 | 14-DEC-14:10 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 4.31 | 0.00 | 04-JAN-14:40 | 1372.55 | 26-JAN-00:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 4.31 | 0.00 | 04-JAN-14:40 | 1372.55 | 26-JAN-00:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 85.18 | 0.00 | 01-JAN-00:10 | 10173.06 | 14-DEC-14:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 85.18 | 0.00 | 01-JAN-00:10 | 10173.06 | 14-DEC-14:10 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7170.35 | 78478.65 | 01-JAN-00:20 | 401185.41 | 10-AUG-22:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 3.52 | 0.00 | 01-JAN-00:10 | 4266.15 | 04-FEB-18:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 3.52 | 0.00 | 01-JAN-00:10 | 4266.15 | 04-FEB-18:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7166.83 | 78478.65 | 01-JAN-00:20 | 401185.41 | 10-AUG-22:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7166.83 | 78478.65 | 01-JAN-00:20 | 401185.41 | 10-AUG-22:10 |
PlantLoopHeatingDemand:Facility | 8360.81 | 0.00 | 01-JAN-00:40 | 2496412.69 | 27-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 548.24 | 0.00 | 01-JAN-00:10 | 62900.66 | 03-JAN-12:20 |
WaterSystems:PlantLoopHeatingDemand | 548.24 | 0.00 | 01-JAN-00:10 | 62900.66 | 03-JAN-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 548.24 | 0.00 | 01-JAN-00:10 | 62900.66 | 03-JAN-12:20 |
EnergyTransfer:HVAC | 13634.12 | 0.22 | 12-JAN-23:20 | 2531253.36 | 27-FEB-07:10 |
HeatingCoils:EnergyTransfer | 7812.57 | 0.00 | 01-JAN-00:40 | 2475445.80 | 27-FEB-07:10 |
PlantLoopHeatingDemand:HVAC | 7812.57 | 0.00 | 01-JAN-00:40 | 2475445.80 | 27-FEB-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 7812.57 | 0.00 | 01-JAN-00:40 | 2475445.80 | 27-FEB-07:10 |
CoolingCoils:EnergyTransfer | 5821.55 | 0.00 | 01-JAN-00:20 | 2091300.28 | 11-AUG-15:40 |
EnergyTransfer:Plant | 22369.17 | 0.00 | 05-JAN-00:10 | 6909107.16 | 21-JUL-12:10 |
LoopToLoop:EnergyTransfer | 4309.74 | 0.00 | 01-JAN-00:20 | 2144737.94 | 11-AUG-14:40 |
WaterSystems:EnergyTransfer | 548.24 | 0.00 | 01-JAN-00:10 | 62900.66 | 03-JAN-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 548.24 | 0.00 | 01-JAN-00:10 | 62900.66 | 03-JAN-12:20 |
Boilers:EnergyTransfer | 7767.43 | 0.00 | 01-JAN-00:40 | 2403275.13 | 27-FEB-07:20 |
Chillers:EnergyTransfer | 4454.57 | 0.00 | 01-JAN-00:20 | 2248874.13 | 21-JUL-12:10 |
HeatRejection:EnergyTransfer | 5289.19 | 0.00 | 01-JAN-00:20 | 2574121.09 | 21-JUL-12:10 |
General:HeatRejection:EnergyTransfer | 5289.19 | 0.00 | 01-JAN-00:20 | 2574121.09 | 21-JUL-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 1.991 | -725.906 | 0.000 | 0.000 | 99.455 | 333.789 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -133.727 |
CORE_BOTTOM | 0.000 | 0.000 | 0.087 | -552.901 | 0.000 | 0.000 | 84.639 | 299.766 | 289.614 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -121.207 |
CORE_MID | 0.000 | 0.000 | 34.490 | -4489.249 | 0.000 | 0.000 | 871.219 | 2997.664 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -2310.252 |
CORE_TOP | 0.000 | 0.000 | 68.922 | -338.109 | 0.000 | 0.000 | 92.821 | 299.766 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -413.013 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 22.263 | -55.923 | 0.000 | 0.000 | 11.628 | 37.639 | 36.365 | 18.581 | 0.000 | 0.004 | 89.133 | 0.000 | -152.743 | 0.000 | -6.947 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 17.085 | -60.503 | 0.000 | 0.000 | 7.489 | 24.256 | 23.435 | 52.356 | 0.000 | 0.004 | 35.227 | 0.000 | -94.764 | 0.000 | -4.585 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 25.225 | -102.361 | 0.000 | 0.000 | 11.620 | 37.639 | 36.366 | 104.707 | 0.000 | 0.005 | 28.332 | 0.000 | -134.624 | 0.000 | -6.910 | 0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 3.992 | -76.914 | 0.000 | 0.000 | 7.512 | 24.256 | 23.435 | 35.360 | 0.000 | 0.002 | 91.537 | 0.000 | -104.285 | 0.000 | -4.895 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 603.820 | -453.867 | 0.000 | 0.000 | 119.460 | 376.387 | 363.654 | 196.799 | 0.000 | 0.124 | 410.185 | 0.000 | -1464.333 | 0.000 | -152.228 | -0.024 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 366.621 | -511.098 | 0.000 | 0.000 | 55.801 | 242.558 | 234.352 | 521.142 | 0.000 | 0.081 | 112.278 | 0.000 | -918.778 | 0.000 | -102.959 | -0.017 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 474.031 | -964.125 | 0.000 | 0.000 | 117.324 | 376.395 | 363.660 | 1041.684 | 0.000 | 0.098 | 75.024 | 0.000 | -1326.413 | 0.000 | -157.677 | -0.001 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 305.502 | -468.897 | 0.000 | 0.000 | 77.468 | 242.558 | 234.351 | 364.311 | 0.000 | 0.063 | 319.981 | 0.000 | -970.475 | 0.000 | -104.863 | -0.002 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 109.917 | -43.610 | 0.000 | 0.000 | 12.184 | 37.639 | 36.365 | 20.945 | 0.000 | 0.018 | 0.001 | 0.000 | -141.112 | 0.000 | -18.112 | -14.233 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 67.306 | -47.310 | 0.000 | 0.000 | 7.643 | 24.256 | 23.435 | 52.964 | 0.000 | 0.009 | 0.001 | 0.000 | -89.000 | 0.000 | -12.317 | -26.986 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 90.261 | -84.989 | 0.000 | 0.000 | 11.856 | 37.639 | 36.366 | 105.104 | 0.000 | 0.011 | 0.001 | 0.000 | -127.495 | 0.000 | -18.815 | -49.939 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 56.217 | -42.338 | 0.000 | 0.000 | 7.806 | 24.256 | 23.435 | 36.667 | 0.000 | 0.007 | 0.518 | 0.000 | -93.965 | 0.000 | -12.603 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 1.768 | -118.760 | 0.000 | 0.000 | 0.907 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -46.142 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 25.045 | -1007.347 | 0.000 | 0.000 | 9.113 | 83.466 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -649.083 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 4.313 | -85.176 | 0.000 | 0.000 | 0.919 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -82.282 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 3.524 | -7166.550 | 0.000 | 0.000 | 22.870 | 94.114 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -448.816 |
GROUNDFLOOR_PLENUM | 5.845 | -66.566 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.005 | 75.791 | 0.000 | 0.000 | 0.000 | -15.075 | -0.000 |
MIDFLOOR_PLENUM | 240.666 | -582.406 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.104 | 602.335 | 0.000 | 0.000 | 0.000 | -260.699 | -0.000 |
TOPFLOOR_PLENUM | 217.519 | -50.695 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.007 | 0.000 | 0.000 | 0.000 | 0.000 | -27.218 | -139.613 |
Total Facility | 464.030 | -699.667 | 2282.380 | -17395.933 | 0.000 | 0.000 | 1629.734 | 5610.736 | 14676.396 | 2550.621 | 0.000 | 0.543 | 1840.347 | 0.000 | -5617.987 | 0.000 | -905.903 | -4435.337 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 05-SEP-04:11 | 0.00 | 0.00 | 0.00 | -147041.28 | 0.00 | 0.00 | 0.00 | 3238.31 | 13457.54 | 0.00 | 0.00 | 0.00 | 130345.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 24-JUL-04:12 | 0.00 | 0.00 | 0.00 | -122696.14 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.65 | 0.00 | 0.00 | 0.00 | 113850.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 22-JUN-04:12 | 0.00 | 0.00 | 0.00 | -1087525.85 | 0.00 | 0.00 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 999067.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 25-JUL-05:01 | 0.00 | 0.00 | 0.00 | -126594.21 | 0.00 | 0.00 | 846.27 | 2908.23 | 7647.36 | 0.00 | 0.00 | 0.00 | 115192.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 11-JUL-04:22 | 0.00 | 0.00 | 0.00 | -25942.35 | 0.00 | 0.00 | 0.00 | 365.16 | 745.56 | 15240.26 | 0.00 | 0.00 | 9821.71 | 0.00 | -0.00 | 0.00 | -230.34 | 0.00 |
PERIMETER_BOT_ZN_2 | 23-JUL-07:11 | 0.00 | 0.00 | 0.00 | -29850.70 | 0.00 | 0.00 | 24.10 | 117.66 | 464.11 | 18816.82 | 0.00 | 0.00 | 10428.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-JUN-14:41 | 0.00 | 0.00 | 0.00 | -46691.03 | 0.00 | 0.00 | 35.75 | 182.58 | 720.19 | 21764.45 | 0.00 | 0.00 | 24257.38 | 0.00 | -0.00 | 0.00 | -269.33 | 0.00 |
PERIMETER_BOT_ZN_4 | 11-JUN-17:01 | 0.00 | 0.00 | 0.00 | -37165.16 | 0.00 | 0.00 | 0.00 | 117.66 | 360.35 | 16510.56 | 0.00 | 0.00 | 20527.28 | 0.00 | -0.00 | 0.00 | -350.69 | 0.00 |
PERIMETER_MID_ZN_3 | 07-JUL-04:51 | 0.00 | 0.00 | 0.00 | -301344.02 | 0.00 | 0.00 | 0.00 | 3651.57 | 7455.61 | 131518.18 | 0.00 | 0.00 | 161419.57 | 0.00 | -0.00 | 0.00 | -2700.91 | 0.00 |
PERIMETER_MID_ZN_2 | 14-MAY-08:51 | 0.00 | 0.00 | 0.00 | -326518.90 | 0.00 | 0.00 | 200.08 | 1176.61 | 4641.14 | 201783.73 | 0.00 | 0.00 | 124841.61 | 0.00 | -0.00 | 0.00 | -6124.27 | 0.00 |
PERIMETER_MID_ZN_1 | 21-MAY-13:21 | 0.00 | 0.00 | 0.00 | -501266.19 | 0.00 | 0.00 | 312.81 | 1825.83 | 7201.95 | 303812.34 | 0.00 | 0.00 | 199822.24 | 0.00 | -0.00 | 0.00 | -11708.97 | 0.00 |
PERIMETER_MID_ZN_4 | 11-JUN-17:21 | 0.00 | 0.00 | 0.00 | -333982.38 | 0.00 | 0.00 | 0.00 | 1176.61 | 3603.49 | 138129.48 | 0.00 | 0.00 | 198982.12 | 0.00 | -0.00 | 0.00 | -7909.31 | 0.00 |
PERIMETER_TOP_ZN_3 | 28-JUN-05:01 | 0.00 | 0.00 | 0.00 | -33008.06 | 0.00 | 0.00 | 108.35 | 365.16 | 960.25 | 4536.57 | 0.00 | 0.00 | 27068.48 | 0.00 | -0.00 | 0.00 | -30.74 | 0.00 |
PERIMETER_TOP_ZN_2 | 23-JUL-11:01 | 0.00 | 0.00 | 0.00 | -33439.09 | 0.00 | 0.00 | 19.10 | 117.66 | 464.11 | 11561.68 | 0.00 | 0.00 | 21276.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 23-JUL-13:41 | 0.00 | 0.00 | 0.00 | -58880.84 | 0.00 | 0.00 | 24.24 | 182.58 | 720.19 | 28730.32 | 0.00 | 0.00 | 29439.57 | 0.00 | -0.00 | 0.00 | -216.07 | 0.00 |
PERIMETER_TOP_ZN_4 | 11-JUN-16:41 | 0.00 | 0.00 | 0.00 | -34788.79 | 0.00 | 0.00 | 22.16 | 117.66 | 464.11 | 18147.28 | 0.00 | 0.00 | 17000.91 | 0.00 | -0.00 | 0.00 | -963.33 | 0.00 |
DATACENTER_BOT_ZN_6 | 07-DEC-10:01 | 0.00 | 0.00 | 0.00 | -13551.90 | 0.00 | 0.00 | 0.00 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 5028.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 07-DEC-10:01 | 0.00 | 0.00 | 0.00 | -123887.76 | 0.00 | 0.00 | 0.00 | 7287.84 | 77944.22 | 0.00 | 0.00 | 0.00 | 38655.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 11-DEC-19:01 | 0.00 | 0.00 | 0.00 | -11992.11 | 0.00 | 0.00 | 1.45 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 3953.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | -535567.34 | 0.00 | 0.00 | 0.00 | 456.53 | 284724.39 | 0.00 | 0.00 | 0.00 | 250386.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 31-MAR-04:11 | 0.00 | -17738.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19490.20 | 0.00 | -0.00 | 0.00 | -1751.77 | 0.00 |
MIDFLOOR_PLENUM | 18-FEB-04:01 | 0.00 | -240174.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243473.04 | 0.00 | -0.00 | 0.00 | -3298.63 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-14:30 | 0.00 | -22845.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.18 | 22830.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-JUN-04:11 | 0.00 | 125278.11 | 0.00 | -2470005.99 | 0.00 | 0.00 | 0.00 | 54433.43 | 350716.63 | 162600.69 | 0.00 | 0.00 | 1829617.98 | 0.00 | -28195.23 | 0.00 | -24445.61 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 27-FEB-07:06 | 0.00 | 0.00 | 96415.73 | 0.00 | 0.00 | 0.00 | 2257.53 | 9714.93 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -121845.74 |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 21676.27 | 0.00 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -30522.15 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 654499.64 | 0.00 | 0.00 | 0.00 | 0.00 | 14541.15 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -728417.02 |
CORE_TOP | 27-FEB-04:01 | 0.00 | 0.00 | 131677.39 | 0.00 | 0.00 | 0.00 | 0.00 | 1454.11 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -139069.13 |
PERIMETER_BOT_ZN_3 | 27-FEB-04:01 | 0.00 | 0.00 | 23531.46 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11587.18 | 0.00 | 0.00 | -12872.42 |
PERIMETER_BOT_ZN_2 | 27-FEB-04:01 | 0.00 | 0.00 | 21741.22 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7692.31 | 0.00 | 0.00 | -14647.03 |
PERIMETER_BOT_ZN_1 | 26-FEB-05:01 | 0.00 | 0.00 | 34246.35 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 | 559.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9896.72 | 0.00 | -1512.67 | -23578.73 |
PERIMETER_BOT_ZN_4 | 30-JAN-04:01 | 0.00 | 0.00 | 20476.46 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6926.98 | 0.00 | -710.99 | -13436.62 |
PERIMETER_MID_ZN_3 | 26-FEB-10:01 | 0.00 | 0.00 | 319173.72 | 0.00 | 0.00 | 0.00 | 923.01 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -79527.48 | 0.00 | -38309.23 | -211287.65 |
PERIMETER_MID_ZN_2 | 26-FEB-04:01 | 0.00 | 0.00 | 264559.62 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.61 | 3603.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -64967.16 | 0.00 | -23211.12 | -181161.46 |
PERIMETER_MID_ZN_1 | 26-FEB-05:21 | 0.00 | 0.00 | 399268.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1825.83 | 5591.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -96982.06 | 0.00 | -33056.91 | -276647.60 |
PERIMETER_MID_ZN_4 | 26-FEB-10:01 | 0.00 | 0.00 | 261066.12 | 0.00 | 0.00 | 0.00 | 590.02 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -57030.05 | 0.00 | -25962.13 | -184481.68 |
PERIMETER_TOP_ZN_3 | 26-FEB-10:01 | 0.00 | 0.00 | 44126.93 | 0.00 | 0.00 | 0.00 | 94.38 | 182.58 | 720.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7642.60 | 0.00 | -4664.45 | -32817.03 |
PERIMETER_TOP_ZN_2 | 26-FEB-04:41 | 0.00 | 0.00 | 29075.16 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6291.08 | 0.00 | -2813.10 | -20448.99 |
PERIMETER_TOP_ZN_1 | 26-FEB-05:21 | 0.00 | 0.00 | 46855.32 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 | 559.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9385.13 | 0.00 | -4012.27 | -34199.68 |
PERIMETER_TOP_ZN_4 | 26-FEB-10:01 | 0.00 | 0.00 | 31269.00 | 0.00 | 0.00 | 0.00 | 60.51 | 117.66 | 464.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5502.46 | 0.00 | -3144.19 | -23264.64 |
DATACENTER_BOT_ZN_6 | 22-DEC-00:22 | 0.00 | 0.00 | 2013.99 | 0.00 | 0.00 | 0.00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9848.90 |
DATACENTER_MID_ZN_6 | 20-FEB-09:02 | 0.00 | 0.00 | 18991.89 | 0.00 | 0.00 | 0.00 | 37.83 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -58406.71 |
DATACENTER_TOP_ZN_6 | 26-NOV-05:02 | 0.00 | 0.00 | 1968.45 | 0.00 | 0.00 | 0.00 | 0.00 | 40.49 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7854.76 |
DATACENTER_BASEMENT_ZN_6 | 17-JUN-20:51 | 0.00 | 0.00 | 33711.31 | 0.00 | 0.00 | 0.00 | 0.00 | 456.53 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -223984.10 |
GROUNDFLOOR_PLENUM | 02-JAN-06:12 | 16021.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -114.82 | -15906.36 |
MIDFLOOR_PLENUM | 02-JAN-06:12 | 271465.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1975.96 | -269489.46 |
TOPFLOOR_PLENUM | 12-JAN-05:22 | 63841.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -63841.55 |
Total Facility | 02-JAN-05:21 | 119332.91 | 79279.44 | 2074948.90 | -79279.44 | 0.00 | 0.00 | 0.00 | 54433.43 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -299845.93 | 0.00 | -25155.10 | -2156139.43 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 15.4817 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 12.5353 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 155.6611 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 116.4436 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 18.2064 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 13.2295 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 7.3000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 7.3000 | 0.1644 | 1.0000 | Not calculated | 1.2002 | 0.1644 | ||
AIRLOOP DATACENTER BASEMENT | 32.0736 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 32.0737 | 0.0106 | 1.0000 | Not calculated | 0.3384 | 0.0106 | ||
AIRLOOP DATACENTER BOT | 0.7769 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7769 | 0.0201 | 1.0000 | Not calculated | 0.0156 | 0.0201 | ||
AIRLOOP DATACENTER MID | 7.4831 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 7.4831 | 0.0209 | 1.0000 | Not calculated | 0.1563 | 0.0209 | ||
AIRLOOP DATACENTER TOP | 0.7586 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7586 | 0.0206 | 1.0000 | Not calculated | 0.0156 | 0.0206 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 7.7409 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6445 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 77.8306 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 46.6983 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 9.1032 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.4619 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 2.1900 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 2.1900 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.5480 | ||
AIRLOOP DATACENTER BASEMENT | 16.0368 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 16.0368 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0211 | ||
AIRLOOP DATACENTER BOT | 0.7769 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7769 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0201 | ||
AIRLOOP DATACENTER MID | 7.4831 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 7.4831 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0209 | ||
AIRLOOP DATACENTER TOP | 0.7586 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7586 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0206 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 7.3000 | 7.3000 | 2.1900 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.5998 | 7.5998 | 2.2799 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 71.9498 | 71.9498 | 21.5849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.9414 | 8.9414 | 2.6824 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5903 | 1.5903 | 0.4771 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6819 | 1.6819 | 0.5046 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6238 | 2.6238 | 0.7871 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9861 | 1.9861 | 0.5958 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 20.0541 | 20.0541 | 6.0162 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 17.7988 | 17.7988 | 5.3396 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 27.4384 | 27.4384 | 8.2315 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.4201 | 18.4201 | 5.5260 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6801 | 2.6801 | 0.8040 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7726 | 1.7726 | 0.5318 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8835 | 2.8835 | 0.8651 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9288 | 1.9288 | 0.5786 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7769 | 0.7769 | 0.7769 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.4831 | 7.4831 | 7.4831 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7586 | 0.7586 | 0.7586 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 32.0736 | 32.0736 | 16.0368 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 15.4817 | 12.5353 | 15.4817 | 4.6445 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 155.6611 | 116.4436 | 155.6611 | 46.6983 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 18.2064 | 13.2295 | 18.2064 | 5.4619 | 0.0000 | 1.0000 |
CAV_BAS | 7.3000 | 7.3000 | 7.3000 | 2.1900 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 32.0736 | 32.0737 | 32.0736 | 16.0368 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.7769 | 0.7769 | 0.7769 | 0.7769 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 7.4831 | 7.4831 | 7.4831 | 7.4831 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.7586 | 0.7586 | 0.7586 | 0.7586 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 2.1900 | 2.1900 | 2.1900 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7999 | 3.7999 | 2.2799 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 35.9749 | 35.9749 | 21.5849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.4707 | 4.4707 | 2.6824 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7951 | 0.7951 | 0.4771 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8409 | 0.8409 | 0.5046 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3119 | 1.3119 | 0.7871 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9930 | 0.9930 | 0.5958 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.0270 | 10.0270 | 6.0162 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.8994 | 8.8994 | 5.3396 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.7192 | 13.7192 | 8.2315 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.2100 | 9.2100 | 5.5260 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3400 | 1.3400 | 0.8040 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8863 | 0.8863 | 0.5318 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4418 | 1.4418 | 0.8651 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9644 | 0.9644 | 0.5786 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7769 | 0.7769 | 0.7769 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.4831 | 7.4831 | 7.4831 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7586 | 0.7586 | 0.7586 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 16.0368 | 16.0368 | 16.0368 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 7.7409 | 4.6445 | 4.6445 | 4.6445 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 77.8306 | 46.6983 | 46.6983 | 46.6983 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 9.1032 | 5.4619 | 5.4619 | 5.4619 | 0.0000 | 1.0000 |
CAV_BAS | 2.1900 | 2.1900 | 2.1900 | 2.1900 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 16.0368 | 16.0368 | 16.0368 | 16.0368 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.7769 | 0.7769 | 0.7769 | 0.7769 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 7.4831 | 7.4831 | 7.4831 | 7.4831 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.7586 | 0.7586 | 0.7586 | 0.7586 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 156.83 |
Number of hours cooling loads not met | 358.33 |
Number of hours not met | 486.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 10772.98 | 3075343.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1211.92 | 344180.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 5610.74 | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 999.11 | 64082.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 56.04 | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.31 | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2789.43 | 277543.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 724.00 | 83900.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 24.21 | 47562.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1469.99 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 553.91 | 63566.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 30682.83 |
Natural Gas | 0.00 | 10772.98 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 41455.81 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 121.13 |
Space Heating | 0.00 |
Space Cooling | 26.16 |
Fans (All) | 60.22 |
Service Water Heating | 11.96 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 662.40 |
Subtotal | 662.40 |
Natural Gas [MJ/m2] | |
Space Heating | 232.58 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 232.58 |
Subtotal | 232.58 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.53 |
Space Heating | 25.99 |
Space Cooling | 2.92 |
Fans (All) | 6.73 |
Service Water Heating | 1.34 |
Receptacle Equipment | 35.40 |
Miscellaneous | 14.09 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
LTG_SCH_DATACENTER | 2939. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8653.33 | 106.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8741.33 | 18.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8754.00 | 6.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8754.67 | 5.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8672.33 | 87.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8752.50 | 7.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8753.67 | 6.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8754.67 | 5.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7408.83 | 1077.33 | 273.83 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7464.17 | 1094.83 | 201.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7492.83 | 1131.83 | 135.33 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8577.83 | 182.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
Min | 7408.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1131.83 | 273.83 | 0.00 | 0.00 |
Average | 8570.25 | 163.22 | 26.53 | 0.00 | 0.00 |
Sum | 197115.67 | 3754.17 | 610.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368348.83 | 267.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330812.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1803.83 | 379.00 | 85.17 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1821.83 | 371.67 | 74.50 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1824.50 | 388.33 | 55.17 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 101022.00 | 2373.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368348.83 | 2373.00 | 85.17 | 0.00 | 0.00 |
Average | 80161.22 | 164.36 | 9.34 | 0.00 | 0.00 |
Sum | 1843708.00 | 3780.17 | 214.83 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8628.17 | 131.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8653.17 | 106.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8713.33 | 46.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8755.83 | 4.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8754.17 | 5.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8622.17 | 137.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8755.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8751.50 | 8.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7943.33 | 799.83 | 16.83 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7972.17 | 787.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8008.00 | 752.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8634.50 | 125.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
Min | 7943.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 799.83 | 16.83 | 0.00 | 0.00 |
Average | 8630.90 | 128.37 | 0.73 | 0.00 | 0.00 |
Sum | 198510.67 | 2952.50 | 16.83 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 368224.00 | 392.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330685.00 | 128.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330746.00 | 67.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330797.00 | 16.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1988.83 | 264.00 | 15.17 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1992.50 | 275.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1995.67 | 272.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 101698.00 | 1697.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368224.00 | 1697.00 | 15.17 | 0.00 | 0.00 |
Average | 80198.96 | 135.30 | 0.66 | 0.00 | 0.00 |
Sum | 1844576.00 | 3111.83 | 15.17 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:42
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.545652E+11 | 84733.51 | 12-JAN-07:01 | -38.3 | -38.4 | 0.426188E+10 | 6219.63 | 20-JAN-10:20 | -6.5 | -6.8 |
February | 0.484547E+11 | 127551.85 | 11-FEB-06:01 | -5.8 | -6.3 | 0.411213E+10 | 7126.08 | 10-FEB-14:00 | -5.8 | -6.3 |
March | 0.587050E+11 | 127610.05 | 13-MAR-05:01 | -24.0 | -24.5 | 0.525598E+10 | 7496.50 | 22-MAR-13:09 | 4.60 | 1.63 |
April | 0.532206E+11 | 120149.45 | 29-APR-04:01 | -1.7 | -2.2 | 0.523616E+10 | 7498.34 | 20-APR-13:20 | -1.7 | -2.2 |
May | 0.597801E+11 | 138415.93 | 02-MAY-04:12 | 3.50 | 0.89 | 0.569624E+10 | 7499.33 | 30-MAY-13:20 | 17.80 | 9.05 |
June | 0.627296E+11 | 144349.76 | 19-JUN-04:12 | 7.07 | 6.43 | 0.583139E+10 | 7499.34 | 28-JUN-13:09 | 17.30 | 14.04 |
July | 0.647946E+11 | 143675.60 | 10-JUL-04:11 | 9.40 | 8.48 | 0.545353E+10 | 7499.37 | 07-JUL-09:00 | 9.40 | 8.48 |
August | 0.736210E+11 | 131004.73 | 21-AUG-04:11 | 4.23 | 3.90 | 0.604245E+10 | 7499.38 | 25-AUG-13:39 | 22.07 | 15.01 |
September | 0.616127E+11 | 147055.71 | 05-SEP-04:11 | 5.00 | 4.48 | 0.520419E+10 | 7499.18 | 07-SEP-13:30 | 15.00 | 8.00 |
October | 0.590197E+11 | 145868.01 | 10-OCT-03:01 | -0.6 | -0.9 | 0.539556E+10 | 7499.09 | 24-OCT-13:39 | -2.1 | -2.8 |
November | 0.649013E+11 | 129172.51 | 02-NOV-05:01 | -11.0 | -11.4 | 0.454640E+10 | 6754.52 | 02-NOV-13:00 | -8.9 | -9.5 |
December | 0.645063E+11 | 112059.57 | 26-DEC-06:01 | -12.1 | -12.4 | 0.419602E+10 | 6850.45 | 26-DEC-10:20 | -8.9 | -9.7 |
Annual Sum or Average | 0.725911E+12 | 0.612320E+11 | ||||||||
Minimum of Months | 0.484547E+11 | 84733.51 | -38.3 | -38.4 | 0.411213E+10 | 6219.63 | -8.9 | -9.7 | ||
Maximum of Months | 0.736210E+11 | 147055.71 | 9.40 | 8.48 | 0.604245E+10 | 7499.38 | 22.07 | 15.01 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.315139E+11 | 24978.85 | 20-JAN-17:00 | -11.1 | -11.2 | 0.459717E+10 | 6734.75 | 25-JAN-14:30 | -18.9 | -19.2 |
February | 0.296517E+11 | 69588.19 | 09-FEB-06:01 | 0.00 | -0.5 | 0.434311E+10 | 6734.89 | 10-FEB-10:09 | -6.2 | -7.1 |
March | 0.391274E+11 | 108971.23 | 23-MAR-05:01 | -2.8 | -4.2 | 0.537857E+10 | 6734.89 | 17-MAR-09:09 | -2.8 | -4.2 |
April | 0.491927E+11 | 112159.06 | 29-APR-04:01 | -1.7 | -2.2 | 0.486360E+10 | 6734.88 | 03-APR-09:09 | -1.7 | -2.2 |
May | 0.559968E+11 | 113178.15 | 01-MAY-04:12 | 6.87 | 2.54 | 0.527791E+10 | 6734.88 | 16-MAY-09:39 | 7.07 | 5.43 |
June | 0.610623E+11 | 117466.34 | 30-JUN-04:12 | 14.40 | 12.81 | 0.526978E+10 | 6734.89 | 30-JUN-09:09 | 17.57 | 14.96 |
July | 0.641637E+11 | 122703.66 | 24-JUL-04:12 | 12.80 | 12.43 | 0.489759E+10 | 6735.18 | 19-JUL-09:09 | 12.80 | 12.43 |
August | 0.676938E+11 | 122547.52 | 14-AUG-04:12 | 11.50 | 10.36 | 0.550025E+10 | 6734.89 | 25-AUG-09:50 | 15.22 | 11.63 |
September | 0.467182E+11 | 116977.21 | 05-SEP-04:11 | 5.00 | 4.48 | 0.486892E+10 | 6734.91 | 08-SEP-13:09 | 11.28 | 7.64 |
October | 0.404649E+11 | 108477.68 | 03-OCT-05:01 | -1.1 | -1.4 | 0.502519E+10 | 6734.90 | 02-OCT-09:09 | -1.1 | -1.4 |
November | 0.337033E+11 | 33973.81 | 03-NOV-15:51 | -11.1 | -11.5 | 0.490865E+10 | 6734.89 | 10-NOV-10:09 | -13.8 | -14.8 |
December | 0.336132E+11 | 32355.15 | 26-DEC-16:53 | -15.6 | -15.9 | 0.473838E+10 | 6734.89 | 29-DEC-10:09 | -11.6 | -12.1 |
Annual Sum or Average | 0.552902E+12 | 0.596691E+11 | ||||||||
Minimum of Months | 0.296517E+11 | 24978.85 | -15.6 | -15.9 | 0.434311E+10 | 6734.75 | -18.9 | -19.2 | ||
Maximum of Months | 0.676938E+11 | 122703.66 | 14.40 | 12.81 | 0.550025E+10 | 6735.18 | 17.57 | 14.96 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.264341E+11 | 22853.42 | 27-JAN-17:00 | -12.2 | -12.5 | 0.428613E+10 | 6643.48 | 27-JAN-14:00 | -12.2 | -12.5 |
February | 0.272657E+11 | 28158.28 | 16-FEB-16:51 | -5.6 | -7.7 | 0.405922E+10 | 6734.88 | 16-FEB-14:09 | -5.6 | -7.7 |
March | 0.337770E+11 | 35194.29 | 22-MAR-15:53 | 5.60 | 2.61 | 0.512251E+10 | 6734.89 | 22-MAR-09:09 | 5.60 | 2.61 |
April | 0.358947E+11 | 99799.34 | 21-APR-05:01 | -2.0 | -3.0 | 0.471996E+10 | 6734.89 | 18-APR-09:09 | -2.0 | -3.0 |
May | 0.470062E+11 | 102752.95 | 09-MAY-05:01 | 5.78 | 2.19 | 0.525270E+10 | 6734.88 | 16-MAY-09:39 | 7.07 | 5.43 |
June | 0.520962E+11 | 108740.41 | 22-JUN-04:12 | 13.90 | 11.43 | 0.525988E+10 | 6734.90 | 27-JUN-09:30 | 13.90 | 13.08 |
July | 0.499870E+11 | 107648.74 | 25-JUL-04:11 | 14.40 | 13.72 | 0.488716E+10 | 6735.13 | 19-JUL-09:09 | 14.40 | 13.72 |
August | 0.504511E+11 | 105830.59 | 03-AUG-04:11 | 15.00 | 13.08 | 0.547975E+10 | 6734.89 | 15-AUG-09:30 | 12.50 | 10.09 |
September | 0.373450E+11 | 100611.42 | 01-SEP-05:01 | 7.12 | 5.68 | 0.481749E+10 | 6734.90 | 08-SEP-13:09 | 11.28 | 7.64 |
October | 0.315512E+11 | 93582.77 | 06-OCT-05:01 | 6.60 | 2.71 | 0.476664E+10 | 6734.89 | 20-OCT-09:50 | -1.3 | -1.3 |
November | 0.285236E+11 | 24174.61 | 03-NOV-15:51 | -11.1 | -11.5 | 0.436734E+10 | 6714.07 | 03-NOV-13:00 | -11.1 | -11.5 |
December | 0.285947E+11 | 21089.97 | 15-DEC-17:00 | -30.0 | -30.2 | 0.416774E+10 | 6466.98 | 22-DEC-14:00 | -22.8 | -23.1 |
Annual Sum or Average | 0.448926E+12 | 0.571865E+11 | ||||||||
Minimum of Months | 0.264341E+11 | 21089.97 | -30.0 | -30.2 | 0.405922E+10 | 6466.98 | -22.8 | -23.1 | ||
Maximum of Months | 0.520962E+11 | 108740.41 | 15.00 | 13.72 | 0.547975E+10 | 6735.13 | 14.40 | 13.72 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113638E+11 | 19932.81 | 19-JAN-17:00 | -6.7 | -6.9 | 0.372835E+10 | 5322.89 | 20-JAN-14:00 | -11.1 | -11.3 |
February | 0.140372E+11 | 22902.04 | 09-FEB-17:00 | -2.2 | -2.6 | 0.346059E+10 | 5883.60 | 09-FEB-14:00 | -2.2 | -2.6 |
March | 0.232539E+11 | 25803.45 | 22-MAR-16:00 | 5.60 | 2.61 | 0.430162E+10 | 6233.22 | 22-MAR-13:00 | 5.60 | 2.61 |
April | 0.288127E+11 | 39576.32 | 20-APR-15:54 | 13.30 | 5.81 | 0.417125E+10 | 6734.86 | 20-APR-13:09 | 13.30 | 5.81 |
May | 0.414168E+11 | 54777.17 | 31-MAY-05:01 | 12.07 | 7.63 | 0.500190E+10 | 6734.86 | 02-MAY-13:39 | 12.07 | 7.63 |
June | 0.514062E+11 | 126479.89 | 21-JUN-04:11 | 13.70 | 11.45 | 0.518544E+10 | 6734.89 | 28-JUN-13:00 | 17.80 | 14.79 |
July | 0.489971E+11 | 126595.74 | 25-JUL-05:01 | 14.40 | 13.72 | 0.481503E+10 | 6735.07 | 19-JUL-09:09 | 14.40 | 13.72 |
August | 0.454996E+11 | 124089.09 | 03-AUG-05:01 | 14.90 | 13.04 | 0.531379E+10 | 6734.88 | 25-AUG-09:50 | 15.22 | 11.63 |
September | 0.284738E+11 | 35911.22 | 01-SEP-15:57 | 15.60 | 10.82 | 0.423811E+10 | 6734.86 | 08-SEP-13:00 | 12.20 | 8.27 |
October | 0.210415E+11 | 25756.67 | 04-OCT-16:00 | 10.00 | 4.57 | 0.398277E+10 | 6340.48 | 04-OCT-13:00 | 10.00 | 4.57 |
November | 0.126068E+11 | 20373.22 | 02-NOV-16:00 | -8.9 | -9.4 | 0.370867E+10 | 5364.46 | 02-NOV-13:00 | -8.9 | -9.4 |
December | 0.112008E+11 | 18807.47 | 29-DEC-17:00 | -14.4 | -14.8 | 0.358040E+10 | 5133.01 | 29-DEC-14:00 | -14.4 | -14.8 |
Annual Sum or Average | 0.338110E+12 | 0.514879E+11 | ||||||||
Minimum of Months | 0.112008E+11 | 18807.47 | -14.4 | -14.8 | 0.346059E+10 | 5133.01 | -14.4 | -14.8 | ||
Maximum of Months | 0.514062E+11 | 126595.74 | 15.60 | 13.72 | 0.531379E+10 | 6735.07 | 17.80 | 14.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 75914293.69 | 2948.93 | 21-JAN-17:01 | -5.5 | -5.8 | 0.464666E+09 | 625.99 | 02-JAN-10:09 | -5.5 | -5.8 |
February | 0.527197E+09 | 3619.49 | 09-FEB-06:02 | 0.00 | -0.5 | 0.422666E+09 | 642.18 | 09-FEB-14:00 | 0.00 | -1.0 |
March | 0.201203E+10 | 4725.40 | 21-MAR-05:02 | -4.3 | -5.7 | 0.521481E+09 | 783.34 | 22-MAR-13:00 | 5.60 | 1.90 |
April | 0.523412E+10 | 6408.94 | 30-APR-13:41 | 8.80 | 4.61 | 0.534560E+09 | 845.63 | 26-APR-13:50 | 8.80 | 4.61 |
May | 0.812914E+10 | 22845.06 | 31-MAY-04:12 | 12.03 | 7.57 | 0.645776E+09 | 845.63 | 02-MAY-13:39 | 12.03 | 7.57 |
June | 0.108484E+11 | 24930.37 | 09-JUN-04:11 | 10.00 | 7.12 | 0.659228E+09 | 845.63 | 28-JUN-13:00 | 17.80 | 14.79 |
July | 0.110335E+11 | 25943.94 | 11-JUL-04:22 | 13.35 | 11.22 | 0.612522E+09 | 845.67 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.945565E+10 | 9606.63 | 02-AUG-14:00 | 22.80 | 15.29 | 0.677699E+09 | 845.63 | 09-AUG-09:20 | 13.73 | 11.46 |
September | 0.539202E+10 | 6316.66 | 01-SEP-13:40 | 14.63 | 10.60 | 0.543799E+09 | 845.63 | 01-SEP-13:00 | 15.00 | 10.77 |
October | 0.286038E+10 | 5153.08 | 04-OCT-05:02 | 7.70 | 2.90 | 0.497911E+09 | 789.88 | 04-OCT-13:00 | 11.10 | 4.80 |
November | 0.265869E+09 | 3089.81 | 06-NOV-06:04 | -16.6 | -17.0 | 0.461527E+09 | 625.77 | 28-NOV-10:20 | -28.9 | -29.1 |
December | 88787641.92 | 3128.72 | 29-DEC-06:04 | -14.8 | -15.2 | 0.449276E+09 | 625.81 | 15-DEC-10:09 | -14.8 | -15.2 |
Annual Sum or Average | 0.559230E+11 | 0.649111E+10 | ||||||||
Minimum of Months | 75914293.69 | 2948.93 | -16.6 | -17.0 | 0.422666E+09 | 625.77 | -28.9 | -29.1 | ||
Maximum of Months | 0.110335E+11 | 25943.94 | 22.80 | 15.29 | 0.677699E+09 | 845.67 | 17.80 | 14.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 48353777.61 | 3420.79 | 23-JAN-06:03 | -11.2 | -11.4 | 0.299251E+09 | 403.43 | 20-JAN-14:50 | -11.2 | -11.4 |
February | 0.611394E+09 | 3781.46 | 15-FEB-10:41 | -16.0 | -16.2 | 0.272845E+09 | 442.21 | 15-FEB-10:50 | -16.0 | -16.2 |
March | 0.299243E+10 | 7753.83 | 22-MAR-09:51 | 1.70 | 0.21 | 0.352318E+09 | 544.96 | 20-MAR-09:09 | 1.70 | 0.21 |
April | 0.591390E+10 | 11604.36 | 22-APR-09:23 | 9.15 | 3.96 | 0.354451E+09 | 544.96 | 13-APR-09:09 | 9.15 | 3.96 |
May | 0.103632E+11 | 23257.61 | 14-MAY-09:12 | 15.37 | 8.02 | 0.417613E+09 | 544.96 | 16-MAY-09:20 | 6.33 | 4.90 |
June | 0.110544E+11 | 28908.99 | 18-JUN-10:11 | 14.23 | 11.41 | 0.420503E+09 | 544.96 | 13-JUN-13:09 | 14.23 | 11.41 |
July | 0.113533E+11 | 29846.86 | 23-JUL-07:11 | 17.07 | 14.04 | 0.389786E+09 | 545.40 | 11-JUL-09:30 | 17.07 | 14.04 |
August | 0.980806E+10 | 28213.84 | 27-AUG-10:21 | 12.80 | 10.67 | 0.431848E+09 | 544.96 | 10-AUG-09:09 | 12.80 | 10.67 |
September | 0.550435E+10 | 12926.76 | 10-SEP-11:02 | 14.60 | 7.89 | 0.344637E+09 | 544.96 | 01-SEP-09:20 | 14.60 | 7.89 |
October | 0.270402E+10 | 7571.81 | 03-OCT-09:43 | 3.43 | 2.35 | 0.318864E+09 | 544.96 | 03-OCT-09:09 | 3.43 | 2.35 |
November | 0.112270E+09 | 3347.83 | 20-NOV-06:04 | -18.4 | -18.8 | 0.297041E+09 | 403.28 | 27-NOV-14:30 | -23.9 | -24.2 |
December | 37318547.34 | 3370.62 | 18-DEC-06:04 | -16.7 | -17.1 | 0.288990E+09 | 403.30 | 26-DEC-14:00 | -14.4 | -14.9 |
Annual Sum or Average | 0.605029E+11 | 0.418815E+10 | ||||||||
Minimum of Months | 37318547.34 | 3347.83 | -18.4 | -18.8 | 0.272845E+09 | 403.28 | -23.9 | -24.2 | ||
Maximum of Months | 0.113533E+11 | 29846.86 | 17.07 | 14.04 | 0.431848E+09 | 545.40 | 17.07 | 14.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.417132E+09 | 5967.13 | 25-JAN-13:30 | -19.8 | -20.0 | 0.465069E+09 | 676.49 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.216929E+10 | 12168.28 | 15-FEB-13:21 | -8.9 | -9.7 | 0.441346E+09 | 845.65 | 15-FEB-14:09 | -8.1 | -9.1 |
March | 0.669057E+10 | 20149.36 | 26-MAR-14:35 | -8.9 | -10.6 | 0.574255E+09 | 845.65 | 06-MAR-14:09 | -8.9 | -10.6 |
April | 0.123148E+11 | 43805.00 | 09-APR-14:01 | 2.48 | -2.4 | 0.553360E+09 | 845.65 | 03-APR-13:09 | 2.48 | -2.4 |
May | 0.147137E+11 | 32297.80 | 14-MAY-12:32 | 18.53 | 9.40 | 0.623463E+09 | 845.65 | 19-MAY-13:00 | 13.30 | 8.13 |
June | 0.162364E+11 | 46686.93 | 04-JUN-14:41 | 19.32 | 11.73 | 0.637404E+09 | 845.67 | 13-JUN-13:09 | 23.98 | 13.48 |
July | 0.169222E+11 | 45743.08 | 23-JUL-13:12 | 25.00 | 15.26 | 0.593408E+09 | 845.69 | 07-JUL-13:09 | 25.00 | 15.26 |
August | 0.168986E+11 | 46063.66 | 27-AUG-11:41 | 16.23 | 12.39 | 0.655631E+09 | 845.88 | 10-AUG-13:00 | 16.23 | 12.39 |
September | 0.981178E+10 | 29689.37 | 10-SEP-11:02 | 14.60 | 7.89 | 0.533619E+09 | 845.66 | 08-SEP-13:20 | 14.60 | 7.89 |
October | 0.506334E+10 | 21114.44 | 03-OCT-13:22 | 10.85 | 6.24 | 0.507719E+09 | 845.65 | 30-OCT-13:09 | -12.0 | -13.0 |
November | 0.103794E+10 | 8851.54 | 08-NOV-13:21 | -13.6 | -14.4 | 0.466000E+09 | 845.65 | 08-NOV-14:09 | -13.4 | -14.2 |
December | 85361395.36 | 5224.36 | 14-DEC-06:04 | -25.7 | -25.9 | 0.448072E+09 | 625.85 | 21-DEC-14:30 | -13.9 | -14.5 |
Annual Sum or Average | 0.102361E+12 | 0.649935E+10 | ||||||||
Minimum of Months | 85361395.36 | 5224.36 | -25.7 | -25.9 | 0.441346E+09 | 625.85 | -18.9 | -19.2 | ||
Maximum of Months | 0.169222E+11 | 46686.93 | 25.00 | 15.26 | 0.655631E+09 | 845.88 | 25.00 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.504661E+09 | 4096.63 | 19-JAN-06:03 | -2.5 | -4.0 | 0.300316E+09 | 403.44 | 12-JAN-14:09 | -2.5 | -4.0 |
February | 0.148594E+10 | 4564.09 | 09-FEB-06:02 | 0.00 | -0.5 | 0.274384E+09 | 444.85 | 09-FEB-14:00 | 0.00 | -1.0 |
March | 0.425394E+10 | 10809.12 | 26-MAR-16:36 | -7.8 | -9.7 | 0.345352E+09 | 521.20 | 22-MAR-15:00 | -7.8 | -9.7 |
April | 0.929120E+10 | 33384.91 | 09-APR-16:41 | 4.32 | -1.6 | 0.356888E+09 | 544.96 | 26-APR-13:50 | 10.68 | 4.22 |
May | 0.995280E+10 | 21749.09 | 28-MAY-17:52 | 16.70 | 8.41 | 0.398433E+09 | 544.95 | 01-MAY-13:20 | 16.70 | 8.41 |
June | 0.119462E+11 | 37164.81 | 11-JUN-17:01 | 18.80 | 10.99 | 0.416293E+09 | 544.96 | 13-JUN-13:09 | 23.98 | 13.48 |
July | 0.125393E+11 | 34251.41 | 30-JUL-18:21 | 17.75 | 11.99 | 0.391302E+09 | 544.99 | 19-JUL-09:09 | 17.75 | 11.99 |
August | 0.122089E+11 | 32116.71 | 27-AUG-17:02 | 21.02 | 12.75 | 0.435793E+09 | 544.96 | 28-AUG-09:00 | 12.20 | 8.79 |
September | 0.676520E+10 | 20885.13 | 02-SEP-17:42 | 16.70 | 10.38 | 0.337955E+09 | 544.95 | 01-SEP-13:39 | 16.70 | 10.38 |
October | 0.391073E+10 | 6889.75 | 04-OCT-04:11 | 7.80 | 2.80 | 0.316930E+09 | 521.19 | 03-OCT-15:30 | 7.80 | 2.80 |
November | 0.210188E+10 | 4771.41 | 08-NOV-15:30 | -15.0 | -15.5 | 0.299869E+09 | 449.44 | 08-NOV-14:00 | -15.0 | -15.5 |
December | 0.195381E+10 | 4259.37 | 14-DEC-04:01 | -25.7 | -25.9 | 0.291681E+09 | 403.36 | 21-DEC-14:50 | -14.2 | -14.8 |
Annual Sum or Average | 0.769146E+11 | 0.416519E+10 | ||||||||
Minimum of Months | 0.504661E+09 | 4096.63 | -25.7 | -25.9 | 0.274384E+09 | 403.36 | -15.0 | -15.5 | ||
Maximum of Months | 0.125393E+11 | 37164.81 | 21.02 | 12.75 | 0.435793E+09 | 544.99 | 23.98 | 13.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31888616.81 | 4004.23 | 19-JAN-06:04 | -2.5 | -4.0 | 0.463418E+09 | 625.99 | 26-JAN-10:00 | -22.8 | -23.0 |
February | 0.100562E+09 | 4019.47 | 07-FEB-06:04 | -5.1 | -6.4 | 0.420888E+09 | 625.80 | 27-FEB-14:20 | -28.7 | -28.9 |
March | 0.687931E+09 | 4509.61 | 22-MAR-14:02 | 5.60 | 1.96 | 0.505806E+09 | 674.49 | 22-MAR-13:00 | 5.60 | 1.96 |
April | 0.346378E+10 | 5969.98 | 28-APR-05:02 | -1.5 | -2.2 | 0.470871E+09 | 771.33 | 28-APR-13:00 | 11.70 | 4.88 |
May | 0.765639E+10 | 24388.41 | 31-MAY-05:01 | 12.07 | 7.63 | 0.592370E+09 | 845.61 | 31-MAY-13:20 | 19.60 | 10.29 |
June | 0.102171E+11 | 29711.02 | 29-JUN-04:51 | 12.20 | 10.91 | 0.646398E+09 | 845.63 | 28-JUN-13:00 | 12.20 | 10.91 |
July | 0.974129E+10 | 30134.29 | 07-JUL-04:51 | 15.00 | 11.56 | 0.594737E+09 | 845.66 | 07-JUL-13:09 | 22.88 | 16.17 |
August | 0.815409E+10 | 8307.08 | 02-AUG-15:40 | 22.93 | 14.75 | 0.624234E+09 | 845.62 | 03-AUG-13:20 | 19.40 | 15.63 |
September | 0.415347E+10 | 5767.44 | 02-SEP-05:03 | 6.70 | 5.73 | 0.480010E+09 | 781.72 | 01-SEP-13:00 | 6.70 | 5.73 |
October | 0.111444E+10 | 4519.47 | 04-OCT-15:01 | 10.92 | 4.77 | 0.468781E+09 | 678.59 | 04-OCT-13:00 | 10.92 | 4.77 |
November | 30511551.41 | 4035.58 | 18-NOV-06:04 | -8.2 | -8.7 | 0.459061E+09 | 625.78 | 27-NOV-14:00 | -23.9 | -24.2 |
December | 35428743.80 | 3706.71 | 23-DEC-17:01 | -2.6 | -3.4 | 0.446804E+09 | 625.82 | 21-DEC-14:39 | -2.6 | -3.4 |
Annual Sum or Average | 0.453869E+11 | 0.617338E+10 | ||||||||
Minimum of Months | 30511551.41 | 3706.71 | -8.2 | -8.7 | 0.420888E+09 | 625.78 | -28.7 | -28.9 | ||
Maximum of Months | 0.102171E+11 | 30134.29 | 22.93 | 14.75 | 0.646398E+09 | 845.66 | 22.88 | 16.17 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 48257900.32 | 3716.29 | 19-JAN-11:04 | -7.1 | -7.8 | 0.213814E+09 | 385.87 | 18-JAN-16:30 | -7.1 | -7.8 |
February | 0.187193E+09 | 4678.24 | 15-FEB-11:01 | -14.9 | -15.2 | 0.197251E+09 | 479.45 | 15-FEB-11:09 | -14.9 | -15.2 |
March | 0.167123E+10 | 16581.23 | 22-MAR-10:01 | 1.88 | 0.29 | 0.250514E+09 | 548.49 | 22-MAR-10:09 | 1.88 | 0.29 |
April | 0.433219E+10 | 20908.22 | 22-APR-10:01 | 10.47 | 4.84 | 0.249037E+09 | 548.49 | 06-APR-10:09 | 10.47 | 4.84 |
May | 0.972657E+10 | 32652.60 | 14-MAY-08:51 | 15.00 | 7.79 | 0.302561E+09 | 548.49 | 12-MAY-12:09 | 15.00 | 7.79 |
June | 0.107469E+11 | 29813.21 | 18-JUN-10:21 | 14.15 | 11.34 | 0.306581E+09 | 548.51 | 20-JUN-14:09 | 24.08 | 14.17 |
July | 0.106773E+11 | 31334.41 | 23-JUL-07:11 | 17.07 | 14.04 | 0.284555E+09 | 548.51 | 19-JUL-12:09 | 17.07 | 14.04 |
August | 0.864055E+10 | 28628.65 | 27-AUG-10:21 | 12.80 | 10.67 | 0.310135E+09 | 548.52 | 24-AUG-12:09 | 12.80 | 10.67 |
September | 0.386603E+10 | 19862.79 | 10-SEP-09:32 | 12.23 | 6.85 | 0.242987E+09 | 548.49 | 01-SEP-10:09 | 12.23 | 6.85 |
October | 0.112457E+10 | 13518.55 | 13-OCT-10:01 | -6.1 | -7.3 | 0.226461E+09 | 548.49 | 03-OCT-10:09 | -6.1 | -7.3 |
November | 47393572.41 | 3682.41 | 24-NOV-11:03 | -17.0 | -17.3 | 0.212443E+09 | 385.70 | 27-NOV-09:00 | -27.2 | -27.4 |
December | 41666781.25 | 3676.88 | 21-DEC-11:03 | -13.3 | -13.6 | 0.205267E+09 | 385.85 | 21-DEC-16:40 | -16.5 | -17.0 |
Annual Sum or Average | 0.511099E+11 | 0.300161E+10 | ||||||||
Minimum of Months | 41666781.25 | 3676.88 | -17.0 | -17.3 | 0.197251E+09 | 385.70 | -27.2 | -27.4 | ||
Maximum of Months | 0.107469E+11 | 32652.60 | 17.07 | 14.04 | 0.310135E+09 | 548.52 | 24.08 | 14.17 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.307217E+09 | 5942.34 | 25-JAN-13:40 | -19.5 | -19.7 | 0.463864E+09 | 662.17 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.202384E+10 | 12657.03 | 15-FEB-13:31 | -8.7 | -9.6 | 0.437459E+09 | 845.65 | 15-FEB-14:09 | -8.1 | -9.1 |
March | 0.647643E+10 | 22056.81 | 26-MAR-14:13 | -9.4 | -10.9 | 0.567290E+09 | 845.66 | 22-MAR-13:20 | -9.4 | -10.9 |
April | 0.115100E+11 | 46559.01 | 09-APR-14:31 | 3.33 | -2.0 | 0.541695E+09 | 845.66 | 11-APR-13:30 | 6.65 | 1.21 |
May | 0.144183E+11 | 50126.78 | 21-MAY-13:21 | 15.00 | 7.02 | 0.611867E+09 | 845.65 | 19-MAY-13:00 | 15.00 | 7.02 |
June | 0.159652E+11 | 49048.43 | 04-JUN-14:51 | 19.40 | 11.69 | 0.624616E+09 | 845.67 | 13-JUN-13:09 | 23.98 | 13.48 |
July | 0.159166E+11 | 48647.93 | 23-JUL-13:52 | 25.00 | 15.26 | 0.579635E+09 | 845.69 | 07-JUL-13:09 | 25.00 | 15.26 |
August | 0.157570E+11 | 47298.92 | 27-AUG-13:42 | 19.13 | 14.11 | 0.635855E+09 | 846.45 | 25-AUG-13:20 | 19.13 | 14.11 |
September | 0.920510E+10 | 22574.78 | 07-SEP-14:25 | 15.85 | 8.58 | 0.519630E+09 | 845.66 | 18-SEP-13:30 | 13.05 | 8.01 |
October | 0.409330E+10 | 21865.35 | 03-OCT-13:29 | 10.85 | 6.24 | 0.496497E+09 | 845.67 | 03-OCT-13:39 | 11.13 | 6.36 |
November | 0.684309E+09 | 8032.92 | 08-NOV-13:50 | -13.4 | -14.2 | 0.462135E+09 | 826.25 | 08-NOV-14:09 | -13.4 | -14.2 |
December | 55582137.48 | 5547.87 | 16-DEC-06:04 | -19.1 | -19.4 | 0.446849E+09 | 625.90 | 21-DEC-14:50 | -14.2 | -14.8 |
Annual Sum or Average | 0.964129E+11 | 0.638739E+10 | ||||||||
Minimum of Months | 55582137.48 | 5547.87 | -19.5 | -19.7 | 0.437459E+09 | 625.90 | -18.9 | -19.2 | ||
Maximum of Months | 0.159652E+11 | 50126.78 | 25.00 | 15.26 | 0.635855E+09 | 846.45 | 25.00 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32042589.07 | 3752.96 | 05-JAN-06:04 | -13.3 | -13.4 | 0.298783E+09 | 403.45 | 05-JAN-10:09 | -17.3 | -17.6 |
February | 0.237935E+09 | 3752.46 | 02-FEB-06:03 | -6.5 | -7.0 | 0.271448E+09 | 403.31 | 27-FEB-10:09 | -33.8 | -33.9 |
March | 0.137071E+10 | 5097.92 | 27-MAR-17:00 | -5.0 | -8.2 | 0.329290E+09 | 475.79 | 31-MAR-15:00 | -9.4 | -11.8 |
April | 0.505746E+10 | 15478.60 | 22-APR-17:06 | 14.13 | 6.18 | 0.315009E+09 | 521.19 | 19-APR-14:00 | 14.13 | 6.18 |
May | 0.763382E+10 | 32489.64 | 28-MAY-17:41 | 16.70 | 8.41 | 0.367640E+09 | 544.78 | 31-MAY-13:00 | 20.00 | 10.15 |
June | 0.986584E+10 | 33398.55 | 11-JUN-17:21 | 18.60 | 10.93 | 0.396359E+09 | 544.96 | 23-JUN-13:30 | 20.00 | 11.59 |
July | 0.916331E+10 | 16154.59 | 06-JUL-17:50 | 24.32 | 15.19 | 0.365727E+09 | 544.97 | 07-JUL-13:09 | 22.88 | 16.17 |
August | 0.814665E+10 | 23348.81 | 27-AUG-17:42 | 20.68 | 12.29 | 0.390426E+09 | 544.93 | 02-AUG-13:00 | 20.68 | 12.29 |
September | 0.405867E+10 | 9041.16 | 07-SEP-15:55 | 17.20 | 8.91 | 0.308485E+09 | 521.19 | 07-SEP-14:00 | 17.20 | 8.91 |
October | 0.117668E+10 | 4899.54 | 03-OCT-15:10 | 12.62 | 6.83 | 0.302620E+09 | 473.05 | 03-OCT-15:20 | 12.43 | 6.74 |
November | 77677499.91 | 3832.31 | 24-NOV-06:04 | -11.2 | -11.6 | 0.296040E+09 | 403.28 | 27-NOV-10:30 | -27.2 | -27.4 |
December | 69112358.08 | 3696.08 | 30-DEC-06:04 | -16.7 | -17.0 | 0.288179E+09 | 403.32 | 21-DEC-14:50 | -16.7 | -17.0 |
Annual Sum or Average | 0.468899E+11 | 0.393001E+10 | ||||||||
Minimum of Months | 32042589.07 | 3696.08 | -16.7 | -17.0 | 0.271448E+09 | 403.28 | -33.8 | -33.9 | ||
Maximum of Months | 0.986584E+10 | 33398.55 | 24.32 | 15.19 | 0.396359E+09 | 544.97 | 22.88 | 16.17 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33522004.12 | 5286.93 | 17-JAN-06:04 | -7.2 | -7.4 | 0.462891E+09 | 626.09 | 10-JAN-14:09 | -7.2 | -7.4 |
February | 35240930.85 | 4905.36 | 11-FEB-17:01 | -1.2 | -2.7 | 0.420342E+09 | 625.86 | 24-FEB-10:39 | -24.8 | -25.3 |
March | 0.259339E+09 | 4999.30 | 18-MAR-16:01 | 1.10 | -1.2 | 0.504111E+09 | 625.79 | 02-MAR-10:50 | 1.10 | -1.2 |
April | 0.272656E+10 | 6386.61 | 28-APR-15:20 | 12.20 | 4.90 | 0.453459E+09 | 698.09 | 28-APR-13:00 | 12.20 | 4.90 |
May | 0.752474E+10 | 19137.49 | 31-MAY-05:01 | 12.07 | 7.63 | 0.535553E+09 | 840.34 | 31-MAY-13:00 | 20.00 | 10.15 |
June | 0.109687E+11 | 33007.85 | 28-JUN-05:01 | 13.12 | 11.99 | 0.608510E+09 | 845.63 | 13-JUN-13:09 | 13.12 | 11.99 |
July | 0.104862E+11 | 30649.28 | 11-JUL-04:11 | 12.80 | 10.97 | 0.557195E+09 | 845.66 | 07-JUL-13:09 | 12.80 | 10.97 |
August | 0.833586E+10 | 9742.51 | 03-AUG-05:01 | 14.90 | 13.04 | 0.570867E+09 | 833.84 | 02-AUG-13:00 | 14.90 | 13.04 |
September | 0.274739E+10 | 6411.19 | 01-SEP-16:00 | 15.60 | 10.82 | 0.454255E+09 | 699.31 | 01-SEP-13:00 | 15.60 | 10.82 |
October | 0.421023E+09 | 5606.60 | 20-OCT-05:03 | -1.8 | -1.8 | 0.463895E+09 | 625.79 | 27-OCT-09:09 | -19.5 | -19.9 |
November | 33362100.76 | 5440.51 | 02-NOV-05:04 | -11.0 | -11.4 | 0.458456E+09 | 625.80 | 27-NOV-10:20 | -27.2 | -27.4 |
December | 38614721.72 | 5482.62 | 21-DEC-06:04 | -13.9 | -14.2 | 0.446238E+09 | 625.95 | 15-DEC-10:00 | -13.9 | -14.2 |
Annual Sum or Average | 0.436105E+11 | 0.593577E+10 | ||||||||
Minimum of Months | 33362100.76 | 4905.36 | -13.9 | -14.2 | 0.420342E+09 | 625.79 | -27.2 | -27.4 | ||
Maximum of Months | 0.109687E+11 | 33007.85 | 15.60 | 13.04 | 0.608510E+09 | 845.66 | 20.00 | 13.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21337548.33 | 3482.72 | 17-JAN-06:04 | -7.2 | -7.4 | 0.298280E+09 | 403.46 | 10-JAN-14:50 | -7.2 | -7.4 |
February | 52183237.21 | 3242.06 | 11-FEB-17:01 | -1.2 | -2.7 | 0.270913E+09 | 403.31 | 24-FEB-10:39 | -24.8 | -25.3 |
March | 0.126748E+10 | 5080.72 | 22-MAR-10:31 | 2.43 | 0.50 | 0.331115E+09 | 511.03 | 22-MAR-09:00 | 2.43 | 0.50 |
April | 0.378038E+10 | 9191.91 | 21-APR-10:13 | 8.53 | 3.66 | 0.326371E+09 | 544.96 | 13-APR-09:09 | 8.53 | 3.66 |
May | 0.889507E+10 | 32394.37 | 14-MAY-09:41 | 15.92 | 8.37 | 0.404500E+09 | 544.96 | 19-MAY-09:09 | 12.15 | 6.94 |
June | 0.106069E+11 | 29618.21 | 04-JUN-10:31 | 18.13 | 12.03 | 0.414260E+09 | 544.97 | 13-JUN-13:09 | 23.98 | 13.48 |
July | 0.105408E+11 | 33438.45 | 23-JUL-11:01 | 22.98 | 15.48 | 0.382371E+09 | 545.39 | 11-JUL-09:00 | 22.98 | 15.48 |
August | 0.824482E+10 | 16858.82 | 10-AUG-09:03 | 14.97 | 10.30 | 0.412449E+09 | 544.96 | 25-AUG-09:50 | 15.22 | 11.63 |
September | 0.312801E+10 | 7039.73 | 10-SEP-09:35 | 12.23 | 6.85 | 0.309905E+09 | 544.95 | 08-SEP-09:50 | 12.23 | 6.85 |
October | 0.726561E+09 | 4707.13 | 03-OCT-10:30 | 5.00 | 3.43 | 0.300635E+09 | 487.77 | 03-OCT-09:00 | 5.00 | 3.43 |
November | 21817025.54 | 3581.87 | 02-NOV-05:04 | -11.0 | -11.4 | 0.295428E+09 | 403.29 | 29-NOV-10:09 | -29.7 | -29.9 |
December | 24620951.72 | 3653.34 | 21-DEC-06:04 | -13.9 | -14.2 | 0.287551E+09 | 403.38 | 19-DEC-14:50 | -13.9 | -14.2 |
Annual Sum or Average | 0.473099E+11 | 0.403378E+10 | ||||||||
Minimum of Months | 21337548.33 | 3242.06 | -13.9 | -14.2 | 0.270913E+09 | 403.29 | -29.7 | -29.9 | ||
Maximum of Months | 0.106069E+11 | 33438.45 | 22.98 | 15.48 | 0.414260E+09 | 545.39 | 23.98 | 15.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136463E+09 | 6036.96 | 25-JAN-06:04 | -22.1 | -22.4 | 0.462964E+09 | 626.10 | 03-JAN-10:50 | -22.1 | -22.4 |
February | 0.124703E+10 | 9107.42 | 15-FEB-13:51 | -8.3 | -9.2 | 0.428682E+09 | 845.65 | 15-FEB-14:09 | -8.1 | -9.1 |
March | 0.495443E+10 | 18535.44 | 31-MAR-13:51 | -11.1 | -13.1 | 0.554829E+09 | 845.65 | 06-MAR-14:09 | -11.1 | -13.1 |
April | 0.994504E+10 | 27883.82 | 20-APR-13:53 | 14.40 | 6.23 | 0.528678E+09 | 845.65 | 26-APR-13:50 | 10.68 | 4.22 |
May | 0.129846E+11 | 50381.56 | 14-MAY-12:21 | 18.35 | 9.42 | 0.595764E+09 | 845.65 | 19-MAY-13:00 | 13.30 | 8.13 |
June | 0.155001E+11 | 51119.78 | 04-JUN-14:41 | 19.32 | 11.73 | 0.614331E+09 | 845.67 | 13-JUN-13:09 | 23.98 | 13.48 |
July | 0.154736E+11 | 58881.78 | 23-JUL-13:41 | 25.00 | 15.26 | 0.568685E+09 | 845.69 | 07-JUL-13:09 | 25.00 | 15.26 |
August | 0.146056E+11 | 54459.95 | 27-AUG-13:31 | 18.87 | 14.02 | 0.620364E+09 | 845.67 | 25-AUG-13:00 | 18.87 | 14.02 |
September | 0.708938E+10 | 21756.80 | 07-SEP-14:25 | 15.85 | 8.58 | 0.499449E+09 | 845.66 | 08-SEP-13:20 | 11.47 | 7.77 |
October | 0.266434E+10 | 19492.49 | 03-OCT-13:22 | 10.85 | 6.24 | 0.483961E+09 | 845.65 | 13-OCT-13:09 | 0.18 | -2.9 |
November | 0.344082E+09 | 7312.24 | 08-NOV-13:50 | -13.4 | -14.2 | 0.459729E+09 | 743.24 | 08-NOV-14:09 | -13.4 | -14.2 |
December | 44635633.82 | 6009.48 | 21-DEC-06:04 | -13.9 | -14.2 | 0.446260E+09 | 626.05 | 21-DEC-14:50 | -14.2 | -14.8 |
Annual Sum or Average | 0.849893E+11 | 0.626370E+10 | ||||||||
Minimum of Months | 44635633.82 | 6009.48 | -22.1 | -22.4 | 0.428682E+09 | 626.05 | -22.1 | -22.4 | ||
Maximum of Months | 0.155001E+11 | 58881.78 | 25.00 | 15.26 | 0.620364E+09 | 845.69 | 25.00 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28014334.51 | 3943.73 | 25-JAN-06:04 | -22.1 | -22.4 | 0.298408E+09 | 403.47 | 09-JAN-10:50 | -22.1 | -22.4 |
February | 0.111237E+09 | 3994.35 | 04-FEB-06:04 | -18.9 | -19.1 | 0.271046E+09 | 403.28 | 28-FEB-10:00 | -25.6 | -25.8 |
March | 0.941038E+09 | 5030.01 | 27-MAR-16:53 | -5.0 | -8.2 | 0.327260E+09 | 458.49 | 22-MAR-15:00 | -5.0 | -8.2 |
April | 0.437398E+10 | 14032.60 | 20-APR-17:44 | 12.30 | 5.27 | 0.309227E+09 | 521.19 | 19-APR-15:09 | 12.30 | 5.27 |
May | 0.693164E+10 | 32376.80 | 28-MAY-17:41 | 16.70 | 8.41 | 0.355809E+09 | 544.88 | 31-MAY-13:00 | 20.00 | 10.15 |
June | 0.966819E+10 | 34788.61 | 11-JUN-16:41 | 18.90 | 11.02 | 0.388292E+09 | 544.96 | 23-JUN-13:20 | 19.80 | 11.49 |
July | 0.897841E+10 | 18601.75 | 30-JUL-19:01 | 17.20 | 11.77 | 0.357486E+09 | 544.97 | 07-JUL-13:09 | 17.20 | 11.77 |
August | 0.756648E+10 | 28568.42 | 27-AUG-17:31 | 20.77 | 12.41 | 0.378991E+09 | 544.89 | 02-AUG-13:00 | 20.77 | 12.41 |
September | 0.300864E+10 | 9138.10 | 02-SEP-17:22 | 16.70 | 10.30 | 0.300980E+09 | 521.19 | 18-SEP-15:00 | 16.10 | 9.39 |
October | 0.642912E+09 | 4816.25 | 03-OCT-15:10 | 12.62 | 6.83 | 0.300145E+09 | 452.38 | 03-OCT-15:20 | 12.43 | 6.74 |
November | 43980658.76 | 4007.96 | 14-NOV-06:04 | -15.6 | -15.9 | 0.295638E+09 | 403.29 | 29-NOV-10:20 | -29.4 | -29.6 |
December | 43469610.38 | 4006.48 | 07-DEC-06:04 | -22.8 | -23.1 | 0.287730E+09 | 403.42 | 21-DEC-14:50 | -14.2 | -14.8 |
Annual Sum or Average | 0.423380E+11 | 0.387101E+10 | ||||||||
Minimum of Months | 28014334.51 | 3943.73 | -22.8 | -23.1 | 0.271046E+09 | 403.28 | -29.4 | -29.6 | ||
Maximum of Months | 0.966819E+10 | 34788.61 | 20.77 | 12.41 | 0.388292E+09 | 544.97 | 20.77 | 12.41 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179412E+10 | 15774.11 | 13-JAN-04:01 | -33.2 | -33.3 | 0.00 | 0.00 | 01-JAN-00:10 | -33.2 | -33.3 |
February | 0.198344E+10 | 16071.77 | 25-FEB-04:01 | -25.4 | -25.8 | 0.00 | 0.00 | 01-FEB-00:10 | -25.4 | -25.8 |
March | 0.303564E+10 | 17738.35 | 31-MAR-04:11 | -24.6 | -25.1 | 0.00 | 0.00 | 01-MAR-00:10 | -24.6 | -25.1 |
April | 0.577738E+10 | 11709.37 | 03-APR-04:01 | -21.1 | -21.6 | 0.00 | 0.00 | 01-APR-00:10 | -21.1 | -21.6 |
May | 0.817448E+10 | 9759.88 | 16-MAY-05:10 | 3.30 | 1.49 | 0.00 | 0.00 | 01-MAY-00:10 | 3.30 | 1.49 |
June | 0.100846E+11 | 10338.99 | 17-JUN-05:11 | 8.17 | 6.80 | 0.00 | 0.00 | 01-JUN-00:10 | 8.17 | 6.80 |
July | 0.107847E+11 | 12228.22 | 05-JUL-05:11 | 8.30 | 7.82 | 0.00 | 0.00 | 01-JUL-00:10 | 8.30 | 7.82 |
August | 0.105788E+11 | 11551.66 | 07-AUG-05:02 | 10.60 | 10.26 | 0.00 | 0.00 | 01-AUG-00:10 | 10.60 | 10.26 |
September | 0.665526E+10 | 10772.73 | 05-SEP-04:17 | 5.00 | 4.48 | 0.00 | 0.00 | 01-SEP-00:10 | 5.00 | 4.48 |
October | 0.428794E+10 | 16139.71 | 27-OCT-04:01 | -17.7 | -18.2 | 0.00 | 0.00 | 01-OCT-00:10 | -17.7 | -18.2 |
November | 0.183670E+10 | 14666.51 | 30-NOV-04:01 | -28.2 | -28.4 | 0.00 | 0.00 | 01-NOV-00:10 | -28.2 | -28.4 |
December | 0.157328E+10 | 15966.92 | 15-DEC-04:01 | -32.4 | -32.5 | 0.00 | 0.00 | 01-DEC-00:10 | -32.4 | -32.5 |
Annual Sum or Average | 0.665663E+11 | 0.00 | ||||||||
Minimum of Months | 0.157328E+10 | 9759.88 | -33.2 | -33.3 | 0.00 | 0.00 | -33.2 | -33.3 | ||
Maximum of Months | 0.107847E+11 | 17738.35 | 10.60 | 10.26 | 0.00 | 0.00 | 10.60 | 10.26 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231640E+10 | 20771.79 | 26-JAN-04:11 | -24.2 | -24.5 | 0.00 | 0.00 | 01-JAN-00:10 | -24.2 | -24.5 |
February | 0.298142E+10 | 24017.33 | 18-FEB-04:01 | -22.6 | -23.0 | 0.00 | 0.00 | 01-FEB-00:10 | -22.6 | -23.0 |
March | 0.287282E+10 | 22288.27 | 25-MAR-03:01 | -11.8 | -12.4 | 0.00 | 0.00 | 01-MAR-00:10 | -11.8 | -12.4 |
April | 0.362858E+10 | 18309.13 | 01-APR-03:01 | -10.3 | -12.0 | 0.00 | 0.00 | 01-APR-00:10 | -10.3 | -12.0 |
May | 0.637179E+10 | 9230.20 | 20-MAY-05:10 | 6.28 | 4.90 | 0.00 | 0.00 | 01-MAY-00:10 | 6.28 | 4.90 |
June | 0.841592E+10 | 9385.45 | 24-JUN-05:12 | 12.80 | 12.28 | 0.00 | 0.00 | 01-JUN-00:10 | 12.80 | 12.28 |
July | 0.849376E+10 | 10423.57 | 05-JUL-05:07 | 8.30 | 7.78 | 0.00 | 0.00 | 01-JUL-00:10 | 8.30 | 7.78 |
August | 0.798455E+10 | 12097.40 | 31-AUG-05:01 | -1.2 | -3.1 | 0.00 | 0.00 | 01-AUG-00:10 | -1.2 | -3.1 |
September | 0.488636E+10 | 16216.51 | 30-SEP-04:01 | -4.0 | -4.5 | 0.00 | 0.00 | 01-SEP-00:10 | -4.0 | -4.5 |
October | 0.297387E+10 | 22969.98 | 22-OCT-05:31 | -20.4 | -20.6 | 0.00 | 0.00 | 01-OCT-00:10 | -20.4 | -20.6 |
November | 0.360330E+10 | 21038.48 | 09-NOV-04:11 | -26.1 | -26.4 | 0.00 | 0.00 | 01-NOV-00:10 | -26.1 | -26.4 |
December | 0.371191E+10 | 20976.34 | 15-DEC-04:01 | -32.4 | -32.5 | 0.00 | 0.00 | 01-DEC-00:10 | -32.4 | -32.5 |
Annual Sum or Average | 0.582407E+11 | 0.00 | ||||||||
Minimum of Months | 0.231640E+10 | 9230.20 | -32.4 | -32.5 | 0.00 | 0.00 | -32.4 | -32.5 | ||
Maximum of Months | 0.849376E+10 | 24017.33 | 12.80 | 12.28 | 0.00 | 0.00 | 12.80 | 12.28 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 0.100930E+09 | 4237.12 | 22-MAR-16:13 | 5.60 | 2.33 | 0.00 | 0.00 | 01-MAR-00:10 | 5.60 | 2.33 |
April | 0.329400E+10 | 12455.47 | 20-APR-15:12 | 13.70 | 6.18 | 0.00 | 0.00 | 01-APR-00:10 | 13.70 | 6.18 |
May | 0.870992E+10 | 19840.15 | 31-MAY-14:40 | 20.73 | 10.55 | 0.00 | 0.00 | 01-MAY-00:10 | 20.73 | 10.55 |
June | 0.136470E+11 | 22548.29 | 29-JUN-14:40 | 25.93 | 16.13 | 0.00 | 0.00 | 01-JUN-00:10 | 25.93 | 16.13 |
July | 0.134602E+11 | 22844.60 | 21-JUL-14:30 | 26.95 | 14.56 | 0.00 | 0.00 | 01-JUL-00:10 | 26.95 | 14.56 |
August | 0.940544E+10 | 18739.73 | 10-AUG-14:30 | 22.20 | 12.05 | 0.00 | 0.00 | 01-AUG-00:10 | 22.20 | 12.05 |
September | 0.197298E+10 | 8562.67 | 07-SEP-15:30 | 16.65 | 8.91 | 0.00 | 0.00 | 01-SEP-00:10 | 16.65 | 8.91 |
October | 0.104959E+09 | 3374.86 | 03-OCT-16:13 | 11.50 | 5.96 | 0.00 | 0.00 | 01-OCT-00:10 | 11.50 | 5.96 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -10.0 | -10.9 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.506954E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.00 | 0.00 | -25.8 | -26.0 | ||
Maximum of Months | 0.136470E+11 | 22844.60 | 26.95 | 16.13 | 0.00 | 0.00 | 26.95 | 16.13 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.818862E+09 | 4919.04 | 30-JAN-11:01 | -24.9 | -25.3 | 97815300.48 | 156.79 | 13-JAN-14:00 | -24.9 | -25.3 |
February | 0.491536E+10 | 10585.12 | 22-FEB-11:01 | -24.5 | -24.8 | 91515069.94 | 204.37 | 24-FEB-10:39 | -24.8 | -25.3 |
March | 0.118521E+11 | 11023.88 | 01-MAR-09:31 | -24.6 | -25.1 | 0.104891E+09 | 222.14 | 01-MAR-08:09 | -24.6 | -25.1 |
April | 0.183665E+11 | 8633.62 | 20-APR-18:51 | 11.10 | 4.63 | 91605096.15 | 126.82 | 21-APR-13:09 | 12.98 | 5.28 |
May | 0.429808E+10 | 3433.67 | 31-MAY-23:51 | 12.40 | 8.53 | 99233107.85 | 126.82 | 17-MAY-13:50 | 12.40 | 8.53 |
June | 0.930168E+10 | 5322.13 | 30-JUN-23:52 | 15.10 | 14.10 | 98957486.29 | 126.82 | 30-JUN-13:09 | 15.10 | 14.10 |
July | 0.147460E+11 | 7215.54 | 31-JUL-24:00 | 16.60 | 11.46 | 91880924.76 | 126.82 | 28-JUL-09:00 | 16.60 | 11.46 |
August | 0.196607E+11 | 8217.88 | 27-AUG-18:42 | 19.60 | 11.80 | 0.103237E+09 | 126.83 | 03-AUG-13:09 | 19.60 | 11.80 |
September | 0.364461E+10 | 2727.68 | 30-SEP-23:51 | 1.30 | -0.1 | 91605091.05 | 126.82 | 07-SEP-09:09 | 1.30 | -0.1 |
October | 0.761388E+10 | 4162.39 | 31-OCT-23:42 | -10.1 | -11.0 | 95230018.31 | 126.82 | 02-OCT-13:30 | -10.1 | -11.0 |
November | 0.983218E+10 | 11487.47 | 08-NOV-22:01 | -24.9 | -25.1 | 0.108923E+09 | 232.27 | 09-NOV-10:09 | -25.7 | -26.0 |
December | 0.137106E+11 | 13552.77 | 07-DEC-10:01 | -24.8 | -25.1 | 0.110814E+09 | 232.27 | 05-DEC-10:09 | -24.8 | -25.1 |
Annual Sum or Average | 0.118761E+12 | 0.118571E+10 | ||||||||
Minimum of Months | 0.818862E+09 | 2727.68 | -24.9 | -25.3 | 91515069.94 | 126.82 | -25.7 | -26.0 | ||
Maximum of Months | 0.196607E+11 | 13552.77 | 19.60 | 14.10 | 0.110814E+09 | 232.27 | 19.60 | 14.10 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259081E+09 | 2872.30 | 13-JAN-15:22 | -24.8 | -24.9 | 95638418.69 | 145.55 | 13-JAN-14:00 | -24.8 | -24.9 |
February | 0.349664E+10 | 10150.42 | 28-FEB-11:21 | -24.8 | -25.1 | 90213960.83 | 188.92 | 24-FEB-10:39 | -24.8 | -25.1 |
March | 0.100359E+11 | 10621.10 | 01-MAR-09:31 | -24.6 | -25.1 | 0.104814E+09 | 222.14 | 01-MAR-09:09 | -24.6 | -25.1 |
April | 0.163937E+11 | 8333.52 | 20-APR-18:51 | 11.10 | 4.63 | 91605096.92 | 126.82 | 21-APR-13:09 | 12.98 | 5.28 |
May | 0.343418E+10 | 3137.09 | 31-MAY-23:41 | 12.63 | 8.49 | 99233110.27 | 126.82 | 17-MAY-13:50 | 12.63 | 8.49 |
June | 0.866713E+10 | 5102.40 | 30-JUN-23:32 | 15.53 | 12.93 | 98957499.10 | 126.82 | 30-JUN-13:09 | 15.53 | 12.93 |
July | 0.137749E+11 | 7010.41 | 31-JUL-23:15 | 17.60 | 12.30 | 91880949.09 | 126.82 | 26-JUL-13:00 | 17.60 | 12.30 |
August | 0.183249E+11 | 7877.56 | 10-AUG-19:00 | 21.70 | 11.86 | 0.103237E+09 | 126.83 | 03-AUG-13:09 | 21.70 | 11.86 |
September | 0.242575E+10 | 2070.90 | 06-SEP-17:55 | 12.20 | 9.07 | 91605093.96 | 126.82 | 07-SEP-09:09 | 5.47 | 3.11 |
October | 0.559916E+10 | 3569.95 | 03-OCT-15:51 | 11.70 | 6.37 | 95230018.31 | 126.82 | 02-OCT-13:30 | 11.70 | 6.37 |
November | 0.732900E+10 | 10770.29 | 29-NOV-13:31 | -25.0 | -25.2 | 0.108524E+09 | 232.27 | 09-NOV-10:09 | -25.0 | -25.2 |
December | 0.109946E+11 | 12389.60 | 07-DEC-10:01 | -24.8 | -25.1 | 0.110797E+09 | 232.27 | 05-DEC-10:09 | -24.8 | -25.1 |
Annual Sum or Average | 0.100735E+12 | 0.118174E+10 | ||||||||
Minimum of Months | 0.259081E+09 | 2070.90 | -25.0 | -25.2 | 90213960.83 | 126.82 | -25.0 | -25.2 | ||
Maximum of Months | 0.183249E+11 | 12389.60 | 21.70 | 12.93 | 0.110797E+09 | 232.27 | 21.70 | 12.93 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15239187.19 | 446.99 | 19-JAN-11:04 | -7.1 | -7.8 | 91634058.07 | 129.77 | 05-JAN-14:00 | -7.1 | -7.8 |
February | 0.205912E+10 | 10112.68 | 28-FEB-11:21 | -24.8 | -25.1 | 88999479.02 | 175.55 | 27-FEB-14:00 | -24.8 | -25.1 |
March | 0.789480E+10 | 10540.97 | 01-MAR-09:31 | -24.6 | -25.1 | 0.104444E+09 | 205.72 | 01-MAR-09:39 | -24.6 | -25.1 |
April | 0.146562E+11 | 8272.28 | 20-APR-18:51 | 11.10 | 4.63 | 91605097.41 | 126.82 | 21-APR-13:09 | 12.98 | 5.28 |
May | 0.245271E+10 | 2987.58 | 31-MAY-23:12 | 13.33 | 8.32 | 99237069.79 | 126.82 | 17-MAY-13:50 | 13.33 | 8.32 |
June | 0.825366E+10 | 4984.83 | 30-JUN-23:12 | 15.97 | 11.62 | 98957500.01 | 126.82 | 30-JUN-13:09 | 15.97 | 11.62 |
July | 0.133616E+11 | 6906.44 | 31-JUL-23:04 | 17.85 | 12.51 | 91880970.67 | 126.82 | 26-JUL-13:00 | 17.85 | 12.51 |
August | 0.176490E+11 | 7926.37 | 10-AUG-19:00 | 21.70 | 11.86 | 0.103237E+09 | 126.83 | 03-AUG-13:09 | 21.70 | 11.86 |
September | 0.109443E+10 | 1917.55 | 08-SEP-17:27 | 13.85 | 8.80 | 91600695.72 | 126.82 | 28-SEP-09:09 | -0.9 | -1.9 |
October | 0.331469E+10 | 3372.60 | 03-OCT-15:51 | 11.70 | 6.37 | 95230033.62 | 126.82 | 03-OCT-09:09 | 11.70 | 6.37 |
November | 0.536075E+10 | 10689.20 | 29-NOV-13:31 | -25.0 | -25.2 | 0.106693E+09 | 231.10 | 30-NOV-14:00 | -26.1 | -26.4 |
December | 0.906432E+10 | 11991.77 | 11-DEC-19:01 | -24.7 | -25.0 | 0.110759E+09 | 232.27 | 05-DEC-10:09 | -24.7 | -25.0 |
Annual Sum or Average | 0.851766E+11 | 0.117428E+10 | ||||||||
Minimum of Months | 15239187.19 | 446.99 | -25.0 | -25.2 | 88999479.02 | 126.82 | -26.1 | -26.4 | ||
Maximum of Months | 0.176490E+11 | 11991.77 | 21.70 | 12.51 | 0.110759E+09 | 232.27 | 21.70 | 12.51 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227760E+12 | 94965.25 | 06-JAN-13:01 | -13.3 | -13.6 | 0.208194E+10 | 2789.40 | 23-JAN-10:09 | -12.1 | -12.5 |
February | 0.432848E+12 | 502580.94 | 09-FEB-11:42 | -2.0 | -2.3 | 0.154071E+10 | 2685.66 | 22-FEB-14:50 | -16.9 | -17.6 |
March | 0.720508E+12 | 535621.53 | 01-MAR-00:02 | -28.9 | -29.2 | 0.173224E+10 | 2308.95 | 23-MAR-13:00 | -1.7 | -4.1 |
April | 0.945014E+12 | 515516.49 | 13-APR-14:10 | 5.00 | 0.59 | 0.170599E+10 | 2731.03 | 03-APR-13:00 | 5.00 | 0.59 |
May | 0.238800E+12 | 486853.60 | 31-MAY-23:38 | 12.87 | 8.44 | 0.217671E+10 | 2861.95 | 12-MAY-13:09 | 12.87 | 8.44 |
June | 0.475076E+12 | 507784.17 | 30-JUN-23:09 | 16.18 | 10.91 | 0.188518E+10 | 2837.76 | 22-JUN-13:09 | 16.18 | 10.91 |
July | 0.736306E+12 | 534364.36 | 04-JUL-13:16 | 11.70 | 9.10 | 0.185319E+10 | 2830.72 | 12-JUL-09:00 | 21.70 | 13.13 |
August | 0.985649E+12 | 518456.26 | 20-AUG-12:11 | 12.43 | 9.96 | 0.191188E+10 | 2844.34 | 10-AUG-13:09 | 12.43 | 9.96 |
September | 0.233990E+12 | 499574.67 | 30-SEP-23:12 | 0.77 | -0.8 | 0.199365E+10 | 2774.07 | 19-SEP-09:09 | 0.77 | -0.8 |
October | 0.489859E+12 | 532479.70 | 31-OCT-23:01 | -10.4 | -11.2 | 0.171108E+10 | 2683.46 | 30-OCT-09:09 | -10.4 | -11.2 |
November | 0.708848E+12 | 525097.40 | 02-NOV-21:53 | -8.9 | -9.2 | 0.195786E+10 | 2654.97 | 06-NOV-14:00 | -10.6 | -11.8 |
December | 0.972169E+12 | 497171.99 | 15-DEC-12:08 | -33.2 | -33.4 | 0.188641E+10 | 2730.81 | 29-DEC-14:20 | -10.8 | -11.4 |
Annual Sum or Average | 0.716683E+13 | 0.224368E+11 | ||||||||
Minimum of Months | 0.227760E+12 | 94965.25 | -33.2 | -33.4 | 0.154071E+10 | 2308.95 | -16.9 | -17.6 | ||
Maximum of Months | 0.985649E+12 | 535621.53 | 16.18 | 10.91 | 0.217671E+10 | 2861.95 | 21.70 | 13.13 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.687034E+09 | 96025.43 | 12-JAN-11:03 | -37.2 |
February | 0.599846E+09 | 96419.05 | 27-FEB-07:06 | -34.9 |
March | 76079804.02 | 95531.41 | 01-MAR-08:61 | -28.1 |
April | 74774815.33 | 2722.48 | 24-APR-05:04 | -3.4 |
May | 62940578.52 | 3209.26 | 27-MAY-05:55 | 0.60 |
June | 71155516.70 | 2559.10 | 14-JUN-05:51 | 16.70 |
July | 80223243.67 | 9879.77 | 29-JUL-16:03 | 30.00 |
August | 47130884.09 | 2606.79 | 31-AUG-05:04 | -1.2 |
September | 61015865.52 | 3358.48 | 22-SEP-05:13 | 3.13 |
October | 76674263.17 | 3105.59 | 10-OCT-05:04 | -0.6 |
November | 34377027.24 | 2715.89 | 13-NOV-06:03 | -18.1 |
December | 0.119812E+09 | 82637.87 | 15-DEC-11:01 | -33.3 |
Annual Sum or Average | 0.199106E+10 | |||
Minimum of Months | 34377027.24 | 2559.10 | -37.2 | |
Maximum of Months | 0.687034E+09 | 96419.05 | 30.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 86564175.77 | 21676.30 | 02-JAN-05:01 | -15.6 |
February | 844255.21 | 14070.92 | 27-FEB-06:01 | -35.9 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:01 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -25.8 |
Annual Sum or Average | 87408430.97 | |||
Minimum of Months | 0.00 | 0.00 | -35.9 | |
Maximum of Months | 86564175.77 | 21676.30 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138310E+10 | 65450.02 | 02-JAN-04:01 | -15.1 |
February | 0.526876E+09 | 56182.89 | 27-FEB-05:01 | -36.1 |
March | 60806131.76 | 52315.68 | 06-MAR-05:01 | -20.2 |
April | 14648281.23 | 49315.43 | 03-APR-05:01 | -21.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.112659E+09 | 53764.28 | 30-OCT-04:01 | -14.4 |
November | 0.623158E+09 | 55685.70 | 13-NOV-05:11 | -19.8 |
December | 0.727708E+09 | 56562.52 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.344896E+10 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.138310E+10 | 65450.02 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157611E+11 | 130268.55 | 09-JAN-04:11 | -18.7 |
February | 0.112170E+11 | 131677.39 | 27-FEB-04:01 | -34.7 |
March | 0.696510E+10 | 128042.74 | 13-MAR-03:01 | -22.1 |
April | 0.205354E+10 | 127411.21 | 03-APR-03:01 | -21.1 |
May | 14359247.06 | 86036.58 | 01-MAY-05:01 | 7.30 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 13097793.45 | 93375.40 | 31-AUG-05:01 | -1.2 |
September | 0.444479E+09 | 107254.59 | 25-SEP-04:11 | -1.1 |
October | 0.497040E+10 | 128044.86 | 30-OCT-03:01 | -13.5 |
November | 0.127926E+11 | 131213.67 | 27-NOV-04:01 | -26.0 |
December | 0.146901E+11 | 130786.38 | 04-DEC-00:01 | -22.1 |
Annual Sum or Average | 0.689217E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.7 | |
Maximum of Months | 0.157611E+11 | 131677.39 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.673926E+10 | 22941.89 | 02-JAN-04:01 | -15.1 |
February | 0.399049E+10 | 23531.33 | 27-FEB-04:01 | -34.7 |
March | 0.215038E+10 | 22345.00 | 01-MAR-04:01 | -27.9 |
April | 0.191956E+09 | 20540.09 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 212880.57 | 3548.01 | 31-AUG-05:01 | -1.2 |
September | 3360566.12 | 13584.04 | 30-SEP-05:01 | -4.5 |
October | 0.701777E+09 | 20619.96 | 27-OCT-04:01 | -17.7 |
November | 0.338405E+10 | 22477.03 | 27-NOV-04:01 | -26.0 |
December | 0.510156E+10 | 22453.11 | 04-DEC-04:01 | -20.0 |
Annual Sum or Average | 0.222630E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.7 | |
Maximum of Months | 0.673926E+10 | 23531.33 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.499680E+10 | 21055.43 | 02-JAN-04:01 | -15.1 |
February | 0.267993E+10 | 21741.15 | 27-FEB-04:01 | -34.7 |
March | 0.132339E+10 | 20712.17 | 01-MAR-04:01 | -27.9 |
April | 0.154515E+09 | 18618.95 | 03-APR-03:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 780301.95 | 12710.01 | 31-AUG-05:01 | -1.2 |
September | 9262713.01 | 13470.17 | 30-SEP-05:01 | -4.5 |
October | 0.530893E+09 | 18679.36 | 27-OCT-04:01 | -17.7 |
November | 0.288748E+10 | 20501.92 | 27-NOV-04:01 | -26.0 |
December | 0.450192E+10 | 20862.68 | 04-DEC-04:01 | -20.0 |
Annual Sum or Average | 0.170850E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.7 | |
Maximum of Months | 0.499680E+10 | 21741.15 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.751720E+10 | 33106.96 | 02-JAN-04:01 | -15.1 |
February | 0.375946E+10 | 34246.30 | 26-FEB-05:01 | -25.6 |
March | 0.191402E+10 | 32540.73 | 01-MAR-04:01 | -27.9 |
April | 0.264455E+09 | 29472.56 | 03-APR-03:01 | -21.1 |
May | 126899.88 | 748.76 | 27-MAY-05:02 | 0.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 1213114.39 | 19783.84 | 31-AUG-05:01 | -1.2 |
September | 40203881.24 | 21869.68 | 30-SEP-05:01 | -4.5 |
October | 0.945668E+09 | 31542.93 | 30-OCT-03:01 | -13.5 |
November | 0.406795E+10 | 32251.91 | 13-NOV-04:01 | -20.1 |
December | 0.671445E+10 | 33022.15 | 04-DEC-04:01 | -20.0 |
Annual Sum or Average | 0.252248E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.9 | |
Maximum of Months | 0.751720E+10 | 34246.30 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207416E+10 | 20476.47 | 30-JAN-04:01 | -25.1 |
February | 0.963825E+09 | 19802.80 | 27-FEB-04:01 | -34.7 |
March | 0.319245E+09 | 17946.21 | 06-MAR-05:01 | -20.2 |
April | 6698561.12 | 16184.87 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 |
September | 85670.11 | 1112.11 | 28-SEP-05:03 | -2.3 |
October | 0.131158E+09 | 17941.10 | 30-OCT-04:01 | -14.4 |
November | 0.228158E+09 | 17666.86 | 13-NOV-05:01 | -20.2 |
December | 0.268605E+09 | 17911.91 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.399193E+10 | |||
Minimum of Months | 0.00 | 0.00 | -34.7 | |
Maximum of Months | 0.207416E+10 | 20476.47 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136578E+11 | 31089.65 | 29-JAN-00:01 | -25.0 |
February | 0.970369E+10 | 31917.49 | 26-FEB-10:01 | -27.2 |
March | 0.632176E+10 | 30391.56 | 13-MAR-01:31 | -20.8 |
April | 0.188908E+10 | 30703.12 | 03-APR-02:41 | -20.7 |
May | 15504299.89 | 19075.86 | 27-MAY-05:02 | 0.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 28963019.03 | 21770.15 | 31-AUG-05:01 | -1.2 |
September | 0.311365E+09 | 23746.24 | 30-SEP-04:01 | -4.0 |
October | 0.399406E+10 | 30602.32 | 22-OCT-22:51 | -15.6 |
November | 0.107882E+11 | 30847.92 | 26-NOV-05:01 | -24.9 |
December | 0.136716E+11 | 30970.22 | 03-DEC-23:31 | -22.2 |
Annual Sum or Average | 0.603821E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.136716E+11 | 31917.49 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.873332E+10 | 25803.86 | 29-JAN-00:01 | -25.0 |
February | 0.564238E+10 | 26455.96 | 26-FEB-04:01 | -25.6 |
March | 0.301884E+10 | 25128.24 | 01-MAR-04:01 | -27.9 |
April | 0.879278E+09 | 25289.04 | 03-APR-02:41 | -20.7 |
May | 5853984.02 | 11924.80 | 27-MAY-05:02 | 0.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 14910883.90 | 16216.97 | 31-AUG-05:01 | -1.2 |
September | 0.164193E+09 | 17890.05 | 30-SEP-04:01 | -4.0 |
October | 0.226799E+10 | 25197.02 | 30-OCT-03:11 | -13.7 |
November | 0.696000E+10 | 25650.68 | 26-NOV-05:01 | -24.9 |
December | 0.897542E+10 | 25737.97 | 04-DEC-00:11 | -22.0 |
Annual Sum or Average | 0.366622E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.9 | |
Maximum of Months | 0.897542E+10 | 26455.96 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119716E+11 | 38837.28 | 29-JAN-00:01 | -25.0 |
February | 0.654097E+10 | 39926.96 | 26-FEB-05:21 | -25.6 |
March | 0.353984E+10 | 37551.15 | 06-MAR-04:01 | -20.0 |
April | 0.102310E+10 | 37024.91 | 03-APR-02:41 | -20.7 |
May | 18401880.39 | 19406.93 | 27-MAY-05:02 | 0.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 15149227.60 | 24435.38 | 31-AUG-05:01 | -1.2 |
September | 0.189253E+09 | 26858.25 | 30-SEP-05:01 | -4.5 |
October | 0.265051E+10 | 38011.98 | 30-OCT-03:11 | -13.7 |
November | 0.843567E+10 | 38641.42 | 26-NOV-09:01 | -25.6 |
December | 0.130187E+11 | 38903.20 | 03-DEC-12:51 | -22.8 |
Annual Sum or Average | 0.474032E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.6 | |
Maximum of Months | 0.130187E+11 | 39926.96 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.787279E+10 | 25545.25 | 29-JAN-00:01 | -25.0 |
February | 0.491828E+10 | 26106.73 | 26-FEB-10:01 | -27.2 |
March | 0.280673E+10 | 24456.03 | 06-MAR-04:01 | -20.0 |
April | 0.661546E+09 | 23494.87 | 03-APR-03:21 | -21.1 |
May | 13742371.35 | 12920.13 | 27-MAY-04:01 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 8878556.28 | 15983.87 | 31-AUG-05:01 | -1.2 |
September | 0.139474E+09 | 17642.70 | 30-SEP-04:01 | -4.0 |
October | 0.201455E+10 | 24850.72 | 22-OCT-22:51 | -15.6 |
November | 0.526339E+10 | 25195.89 | 26-NOV-05:01 | -24.9 |
December | 0.685089E+10 | 25254.45 | 03-DEC-12:51 | -22.8 |
Annual Sum or Average | 0.305503E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.787279E+10 | 26106.73 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214564E+11 | 42533.15 | 29-JAN-00:01 | -25.0 |
February | 0.170182E+11 | 44127.22 | 26-FEB-10:01 | -27.2 |
March | 0.131421E+11 | 42424.97 | 13-MAR-01:01 | -21.0 |
April | 0.515334E+10 | 42623.70 | 03-APR-02:41 | -20.7 |
May | 0.248357E+09 | 29795.63 | 27-MAY-04:01 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 150813.51 | 1759.49 | 05-JUL-05:04 | 8.30 |
August | 0.173804E+09 | 30794.08 | 31-AUG-04:31 | -0.9 |
September | 0.178675E+10 | 33512.84 | 30-SEP-03:02 | -3.4 |
October | 0.946639E+10 | 42523.92 | 22-OCT-22:41 | -15.7 |
November | 0.189653E+11 | 42576.16 | 13-NOV-04:01 | -20.1 |
December | 0.225059E+11 | 42953.51 | 04-DEC-00:01 | -22.1 |
Annual Sum or Average | 0.109917E+12 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.225059E+11 | 44127.22 | 12.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141286E+11 | 28160.97 | 29-JAN-00:01 | -25.0 |
February | 0.102135E+11 | 29075.31 | 26-FEB-04:41 | -25.6 |
March | 0.649690E+10 | 27994.37 | 13-MAR-01:01 | -21.0 |
April | 0.249659E+10 | 28175.46 | 03-APR-02:41 | -20.7 |
May | 86356137.51 | 19634.89 | 27-MAY-04:01 | 0.00 |
June | 19755.43 | 329.26 | 26-JUN-05:03 | 12.38 |
July | 64147.06 | 748.38 | 05-JUL-05:04 | 8.30 |
August | 77379573.39 | 20187.78 | 31-AUG-04:31 | -0.9 |
September | 0.857242E+09 | 22143.26 | 30-SEP-03:02 | -3.4 |
October | 0.543381E+10 | 28098.89 | 22-OCT-22:41 | -15.7 |
November | 0.124362E+11 | 28249.33 | 13-NOV-04:01 | -20.1 |
December | 0.150794E+11 | 28430.46 | 04-DEC-00:01 | -22.1 |
Annual Sum or Average | 0.673061E+11 | |||
Minimum of Months | 19755.43 | 329.26 | -25.6 | |
Maximum of Months | 0.150794E+11 | 29075.31 | 12.38 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194543E+11 | 45357.64 | 29-JAN-00:01 | -25.0 |
February | 0.125714E+11 | 46855.55 | 26-FEB-05:21 | -25.6 |
March | 0.840472E+10 | 44737.54 | 06-MAR-03:41 | -19.8 |
April | 0.335505E+10 | 44825.41 | 03-APR-02:41 | -20.7 |
May | 0.321650E+09 | 30690.97 | 27-MAY-04:01 | 0.00 |
June | 1916672.76 | 14824.71 | 19-JUN-05:01 | 8.27 |
July | 781387.31 | 11247.44 | 06-JUL-05:01 | 8.77 |
August | 0.133146E+09 | 31064.05 | 31-AUG-04:31 | -0.9 |
September | 0.124321E+10 | 34953.85 | 30-SEP-05:01 | -4.5 |
October | 0.694380E+10 | 45142.16 | 30-OCT-02:51 | -13.3 |
November | 0.160531E+11 | 45471.33 | 13-NOV-04:01 | -20.1 |
December | 0.217783E+11 | 45962.10 | 04-DEC-00:01 | -22.1 |
Annual Sum or Average | 0.902614E+11 | |||
Minimum of Months | 781387.31 | 11247.44 | -25.6 | |
Maximum of Months | 0.217783E+11 | 46855.55 | 8.77 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124961E+11 | 30292.74 | 29-JAN-00:01 | -25.0 |
February | 0.881794E+10 | 31269.17 | 26-FEB-10:01 | -27.2 |
March | 0.602109E+10 | 29528.68 | 13-MAR-01:01 | -21.0 |
April | 0.196899E+10 | 29577.99 | 03-APR-00:01 | -16.8 |
May | 0.141251E+09 | 20254.57 | 27-MAY-04:01 | 0.00 |
June | 58438.79 | 776.13 | 26-JUN-05:03 | 12.38 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 67773557.70 | 20320.42 | 31-AUG-04:31 | -0.9 |
September | 0.751495E+09 | 23008.81 | 30-SEP-05:01 | -4.5 |
October | 0.455624E+10 | 29722.85 | 22-OCT-22:41 | -15.7 |
November | 0.969151E+10 | 29834.58 | 13-NOV-04:01 | -20.1 |
December | 0.117044E+11 | 30131.65 | 03-DEC-12:41 | -22.8 |
Annual Sum or Average | 0.562168E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.124961E+11 | 31269.17 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.271330E+10 | 16021.18 | 02-JAN-06:12 | -15.2 |
February | 0.103693E+10 | 7205.29 | 27-FEB-06:07 | -35.9 |
March | 0.421995E+09 | 9571.18 | 12-MAR-12:22 | -8.9 |
April | 72653500.19 | 10231.70 | 07-APR-04:01 | -3.9 |
May | 69471217.07 | 11273.97 | 31-MAY-04:12 | 12.03 |
June | 48797138.70 | 12620.48 | 14-JUN-04:11 | 16.10 |
July | 72677441.08 | 13181.58 | 12-JUL-04:11 | 15.00 |
August | 70376535.04 | 11065.35 | 27-AUG-16:22 | 20.85 |
September | 32994592.11 | 7993.32 | 01-SEP-04:12 | 7.60 |
October | 71478352.58 | 9078.42 | 04-OCT-04:11 | 7.80 |
November | 0.392060E+09 | 3569.98 | 27-NOV-10:20 | -27.2 |
December | 0.842465E+09 | 6218.17 | 04-DEC-06:05 | -19.4 |
Annual Sum or Average | 0.584520E+10 | |||
Minimum of Months | 32994592.11 | 3569.98 | -35.9 | |
Maximum of Months | 0.271330E+10 | 16021.18 | 20.85 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.644053E+10 | 27146.56 | 02-JAN-06:12 | -15.2 |
February | 0.361574E+10 | 16376.05 | 27-FEB-06:06 | -35.9 |
March | 0.228061E+10 | 10485.83 | 27-MAR-12:01 | -7.0 |
April | 0.630656E+09 | 13287.51 | 09-APR-14:31 | 3.33 |
May | 65590208.95 | 15811.01 | 28-MAY-16:21 | 16.40 |
June | 39655289.50 | 11326.64 | 29-JUN-04:11 | 11.87 |
July | 44167586.81 | 13491.67 | 23-JUL-11:52 | 23.90 |
August | 34250631.51 | 11649.84 | 27-AUG-15:02 | 21.02 |
September | 17482932.43 | 5164.20 | 17-SEP-11:10 | 12.88 |
October | 0.127624E+10 | 10379.46 | 30-OCT-05:03 | -14.5 |
November | 0.435254E+10 | 14427.57 | 13-NOV-06:05 | -18.1 |
December | 0.526905E+10 | 14501.76 | 04-DEC-06:04 | -19.4 |
Annual Sum or Average | 0.240665E+11 | |||
Minimum of Months | 17482932.43 | 5164.20 | -35.9 | |
Maximum of Months | 0.644053E+10 | 27146.56 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.419791E+11 | 63841.53 | 12-JAN-05:22 | -38.0 |
February | 0.325626E+11 | 63213.12 | 27-FEB-06:12 | -35.7 |
March | 0.245656E+11 | 52704.18 | 06-MAR-05:04 | -20.2 |
April | 0.955216E+10 | 53310.42 | 03-APR-04:04 | -21.1 |
May | 0.136723E+10 | 19196.33 | 31-MAY-05:01 | 12.07 |
June | 0.143913E+09 | 30220.42 | 28-JUN-05:01 | 13.12 |
July | 0.120196E+09 | 29994.15 | 28-JUL-05:01 | 11.75 |
August | 0.849614E+09 | 29796.17 | 02-AUG-05:01 | 11.10 |
September | 0.478578E+10 | 31730.64 | 25-SEP-05:01 | -1.2 |
October | 0.188259E+11 | 48301.38 | 30-OCT-04:14 | -14.4 |
November | 0.388852E+11 | 53617.51 | 27-NOV-06:12 | -26.7 |
December | 0.438814E+11 | 52551.66 | 15-DEC-06:01 | -32.9 |
Annual Sum or Average | 0.217519E+12 | |||
Minimum of Months | 0.120196E+09 | 19196.33 | -38.0 | |
Maximum of Months | 0.438814E+11 | 63841.53 | 13.12 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.679367E+09 | 1542.20 | 29-JAN-11:13 | -24.8 |
February | 0.369865E+09 | 1514.62 | 26-FEB-18:02 | -25.4 |
March | 0.135151E+09 | 1828.69 | 31-MAR-05:02 | -25.2 |
April | 0.00 | 0.00 | 01-APR-00:01 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 1.42 |
November | 0.270598E+09 | 1836.28 | 08-NOV-23:32 | -25.2 |
December | 0.312978E+09 | 2013.99 | 22-DEC-00:22 | -25.5 |
Annual Sum or Average | 0.176796E+10 | |||
Minimum of Months | 0.00 | 0.00 | -25.5 | |
Maximum of Months | 0.679367E+09 | 2013.99 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146088E+10 | 1326.99 | 12-JAN-22:12 | -36.3 |
February | 0.357053E+09 | 1899.19 | 20-FEB-09:02 | -24.7 |
March | 0.130104E+09 | 1587.63 | 01-MAR-23:42 | -25.3 |
April | 0.00 | 0.00 | 01-APR-00:01 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 1.42 |
November | 0.258164E+09 | 1622.63 | 08-NOV-23:32 | -25.2 |
December | 0.298311E+09 | 1736.68 | 22-DEC-00:22 | -25.5 |
Annual Sum or Average | 0.250451E+10 | |||
Minimum of Months | 0.00 | 0.00 | -36.3 | |
Maximum of Months | 0.146088E+10 | 1899.19 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.216031E+10 | 1381.09 | 12-JAN-23:45 | -35.6 |
February | 0.719347E+09 | 1743.74 | 25-FEB-04:32 | -24.8 |
March | 0.133982E+09 | 1501.70 | 01-MAR-23:42 | -25.3 |
April | 0.00 | 0.00 | 01-APR-00:01 | -11.7 |
May | 68150494.62 | 1035.82 | 28-MAY-05:00 | 2.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 |
September | 0.435122E+09 | 1336.64 | 25-SEP-02:55 | -0.6 |
October | 0.209481E+09 | 1118.84 | 28-OCT-03:21 | -10.8 |
November | 0.272393E+09 | 1968.45 | 26-NOV-05:02 | -24.9 |
December | 0.313820E+09 | 1591.89 | 22-DEC-00:22 | -25.5 |
Annual Sum or Average | 0.431261E+10 | |||
Minimum of Months | 0.00 | 0.00 | -35.6 | |
Maximum of Months | 0.216031E+10 | 1968.45 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 |
February | 0.163953E+10 | 32437.62 | 04-FEB-18:01 | -17.6 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:01 | -11.7 |
May | 304729.50 | 1627.13 | 31-MAY-23:04 | 13.57 |
June | 0.485354E+09 | 33709.93 | 17-JUN-20:51 | 15.60 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 |
September | 2309034.93 | 6490.25 | 30-SEP-23:04 | 0.63 |
October | 0.139662E+10 | 19717.14 | 14-OCT-17:51 | 1.10 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -25.8 |
Annual Sum or Average | 0.352412E+10 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.163953E+10 | 33709.93 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.278508E+11 | 29144.79 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.252627E+11 | 29144.79 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.300191E+11 | 29144.79 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.268132E+11 | 29144.79 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.289349E+11 | 29144.79 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.287951E+11 | 29144.79 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.269531E+11 | 29144.79 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.300191E+11 | 29144.79 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.268132E+11 | 29144.79 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.278508E+11 | 29144.79 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.275243E+11 | 29144.79 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.269531E+11 | 29144.79 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.333789E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.252627E+11 | 29144.79 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.300191E+11 | 29144.79 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.785272E+10 | 8217.58 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.712300E+10 | 8217.58 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.846411E+10 | 8217.58 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.756018E+10 | 8217.58 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.815842E+10 | 8217.58 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.811897E+10 | 8217.58 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.759962E+10 | 8217.58 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.846411E+10 | 8217.58 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.756018E+10 | 8217.58 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.785272E+10 | 8217.58 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.776069E+10 | 8217.58 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.759962E+10 | 8217.58 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.941143E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.712300E+10 | 8217.58 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.846411E+10 | 8217.58 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.289349E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.287951E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.275243E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.333789E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.755277E+09 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611089E+09 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.923799E+09 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104498E+10 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607647E+09 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 813617.70 | 0.360261E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3203088.81 | 0.264723E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 383403.65 | 0.319352E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383731E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826593E+09 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286906E+09 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563001E+09 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4400110.17 | 0.694736E+10 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264723E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3203088.81 | 0.104498E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501242E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406124E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617094E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695404E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402980E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 637325.70 | 0.230192E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2711888.44 | 0.166662E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 378164.06 | 0.201786E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255562E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549086E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189010E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370231E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3727378.21 | 0.458537E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166662E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2711888.44 | 0.695404E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750272E+09 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612245E+09 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934602E+09 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106727E+10 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601896E+09 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 868764.50 | 0.343936E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3297160.28 | 0.253866E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 411016.77 | 0.312251E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382598E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817049E+09 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282140E+09 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551686E+09 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4576941.55 | 0.690981E+10 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253866E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3297160.28 | 0.106727E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513356E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419088E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642978E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769943E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430800E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 542408.72 | 0.254866E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1693574.71 | 0.194205E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 253803.35 | 0.237125E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268294E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.569757E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199650E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394884E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2489786.78 | 0.489495E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194205E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1693574.71 | 0.769943E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174091E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139968E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205738E+10 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222208E+10 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129351E+10 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1790073.05 | 0.772055E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9410927.68 | 0.572166E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1184323.32 | 0.664982E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812885E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178318E+10 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641390E+09 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126261E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12385324.05 | 0.152228E+11 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572166E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9410927.68 | 0.222208E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115488E+10 |
February | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.931337E+09 |
March | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138871E+10 |
April | 0.688021E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153200E+10 |
May | 0.744847E+09 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903022E+09 |
June | 0.742030E+09 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1398383.05 | 0.514810E+09 |
July | 0.690839E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5818392.34 | 0.387197E+09 |
August | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 891591.21 | 0.456041E+09 |
September | 0.688021E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566459E+09 |
October | 0.715730E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119997E+10 |
November | 0.708685E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425705E+09 |
December | 0.690839E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835744E+09 |
Annual Sum or Average | 0.858171E+10 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8108366.59 | 0.102959E+11 |
Minimum of Months | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387197E+09 |
Maximum of Months | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5818392.34 | 0.153200E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174354E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141318E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213386E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241628E+10 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137479E+10 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1938998.30 | 0.773375E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6948855.76 | 0.585662E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 892460.79 | 0.707184E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874313E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183807E+10 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643597E+09 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126386E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9780314.85 | 0.157677E+11 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585662E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6948855.76 | 0.241628E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116395E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937518E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139264E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160168E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.928628E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1179386.27 | 0.538121E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4630379.39 | 0.404632E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 522925.91 | 0.472187E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564788E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120531E+10 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429561E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.847286E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6332691.57 | 0.104863E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404632E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4630379.39 | 0.160168E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215041E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172014E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250766E+10 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263106E+10 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145464E+10 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2410210.99 | 0.877595E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13473333.77 | 0.654402E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2396527.84 | 0.752931E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912880E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210152E+10 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789586E+09 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155923E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18280072.60 | 0.181121E+11 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654402E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13473333.77 | 0.263106E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143296E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114661E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167824E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180421E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104496E+10 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1573775.79 | 0.608338E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6434627.13 | 0.461621E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 928155.98 | 0.531213E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636769E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140719E+10 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526102E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103898E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8936558.89 | 0.123172E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461621E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6434627.13 | 0.180421E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215219E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172711E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256168E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283773E+10 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159727E+10 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2221830.17 | 0.914025E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8133137.14 | 0.698424E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 988892.96 | 0.833774E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.995461E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214730E+10 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790686E+09 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155967E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11343860.27 | 0.188153E+11 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698424E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8133137.14 | 0.283773E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143653E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115172E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168927E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189715E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108945E+10 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1354236.33 | 0.641759E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5257258.78 | 0.485983E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 563059.74 | 0.560572E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653108E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142634E+10 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528237E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104275E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7174554.85 | 0.126029E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485983E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5257258.78 | 0.189715E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.785272E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.712300E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.846411E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.756018E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.815842E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.811897E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.759962E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.846411E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.756018E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.785272E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.776069E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.759962E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.941143E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.712300E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.846411E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161460E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132057E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201823E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230147E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131660E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 937737.54 | 0.756515E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4074625.81 | 0.558517E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239923.79 | 0.692110E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841832E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181533E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625204E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121408E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5252287.14 | 0.150751E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558517E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4074625.81 | 0.230147E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282026E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230640E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351129E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394382E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229835E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1653526.06 | 0.131935E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8187449.80 | 0.969690E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512307.91 | 0.119118E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146118E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310180E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106933E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207722E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10353283.77 | 0.260699E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969690E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8187449.80 | 0.394382E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304136E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246715E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368839E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405956E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237117E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676869.68 | 0.141954E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6143209.56 | 0.106348E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22743.07 | 0.124334E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142038E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309587E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112814E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221942E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6842822.31 | 0.272178E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106348E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6143209.56 | 0.405956E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 29144.79 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 29144.79 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 29144.79 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 29144.79 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 29144.79 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 29144.79 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 29144.79 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 29144.79 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 29144.79 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 29144.79 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 29144.79 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 29144.79 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3308.39 | 28-JAN-23:51 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1980.04 | 25-FEB-00:51 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1479.69 | 14-MAR-21:01 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 2179.56 | 01-APR-18:51 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1027.73 | 26-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.86 | 30-JUN-15:00 | 1029.41 | 25-JUN-05:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.96 | 29-JUL-19:50 | 756.03 | 04-JUL-16:51 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.23 | 11-AUG-16:00 | 808.92 | 30-AUG-01:00 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 692.30 | 04-SEP-14:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 1328.62 | 21-OCT-04:42 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1096.10 | 10-NOV-01:51 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1162.64 | 28-DEC-02:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 692.30 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 142.96 | 3308.39 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2205.58 | 28-JAN-23:51 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1311.83 | 25-FEB-00:51 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 986.40 | 14-MAR-21:01 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 1424.34 | 01-APR-18:51 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 676.14 | 26-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 | 30-JUN-15:00 | 671.00 | 25-JUN-06:00 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.91 | 29-JUL-19:50 | 490.43 | 04-JUL-16:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.42 | 23-AUG-18:00 | 524.04 | 30-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 460.07 | 04-SEP-14:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 887.44 | 21-OCT-04:02 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 719.37 | 10-NOV-01:51 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 761.69 | 28-DEC-02:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.07 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 138.91 | 2205.58 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3308.43 | 28-JAN-23:51 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1966.73 | 25-FEB-00:51 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1586.58 | 12-MAR-14:33 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 2307.45 | 01-APR-18:51 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1010.68 | 26-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.86 | 30-JUN-15:00 | 951.36 | 25-JUN-06:00 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.56 | 29-JUL-19:50 | 744.06 | 04-JUL-16:51 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.23 | 11-AUG-16:00 | 785.72 | 30-AUG-01:00 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 647.72 | 04-SEP-14:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 1338.54 | 21-OCT-04:42 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1080.78 | 10-NOV-01:51 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1140.03 | 28-DEC-02:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 647.72 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 187.56 | 3308.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2208.01 | 28-JAN-23:51 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1379.11 | 25-FEB-00:51 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 989.06 | 14-MAR-21:01 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 1874.22 | 01-APR-18:51 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 722.62 | 26-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 | 30-JUN-15:00 | 723.06 | 25-JUN-06:00 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.76 | 21-JUL-16:00 | 553.65 | 04-JUL-16:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.49 | 11-AUG-16:00 | 580.03 | 30-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 480.04 | 04-SEP-14:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 911.16 | 21-OCT-03:51 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 772.71 | 10-NOV-01:51 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 844.78 | 28-DEC-02:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.04 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 75.76 | 2208.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 7710.67 | 28-JAN-23:51 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 4604.36 | 24-FEB-05:54 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 3469.13 | 14-MAR-21:01 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 4627.30 | 01-APR-18:51 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2169.61 | 27-MAY-04:03 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.82 | 30-JUN-15:00 | 2013.36 | 25-JUN-05:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 390.57 | 29-JUL-20:10 | 1628.93 | 04-JUL-16:51 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.68 | 23-AUG-18:00 | 1692.27 | 30-AUG-01:00 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1385.41 | 30-SEP-04:55 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 3125.64 | 21-OCT-04:44 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2533.77 | 10-NOV-05:09 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 2667.01 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1385.41 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 390.57 | 7710.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5137.27 | 28-JAN-23:51 |
February | 1239.33 | 01-FEB-08:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3069.58 | 24-FEB-05:10 |
March | 1239.33 | 01-MAR-08:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2313.70 | 14-MAR-21:01 |
April | 1239.33 | 03-APR-07:10 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 3093.06 | 01-APR-18:51 |
May | 1239.33 | 01-MAY-07:10 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1453.71 | 26-MAY-22:00 |
June | 1239.33 | 01-JUN-07:10 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.88 | 30-JUN-15:00 | 1338.74 | 25-JUN-05:51 |
July | 1239.33 | 03-JUL-07:10 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 299.70 | 29-JUL-20:10 | 1094.87 | 04-JUL-16:51 |
August | 1239.33 | 01-AUG-07:10 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.06 | 23-AUG-18:00 | 1128.21 | 30-AUG-01:00 |
September | 1239.33 | 01-SEP-07:10 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 933.42 | 04-SEP-14:00 |
October | 1239.33 | 02-OCT-07:10 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2093.49 | 21-OCT-04:03 |
November | 1239.33 | 01-NOV-07:10 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1689.16 | 10-NOV-05:09 |
December | 1239.33 | 01-DEC-08:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1777.74 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 933.42 | |||||
Maximum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 299.70 | 5137.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 7714.83 | 28-JAN-23:51 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 4604.37 | 24-FEB-05:08 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 3785.23 | 12-MAR-14:46 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 5298.31 | 01-APR-18:51 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2201.20 | 26-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.82 | 30-JUN-15:00 | 2099.99 | 18-JUN-14:30 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 377.74 | 29-JUL-20:10 | 1678.70 | 04-JUL-16:51 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.66 | 11-AUG-16:00 | 1703.21 | 30-AUG-01:00 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1442.93 | 30-SEP-21:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 3143.82 | 21-OCT-04:23 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2533.77 | 10-NOV-05:08 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 2652.37 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1442.93 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 377.74 | 7714.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5143.42 | 28-JAN-23:51 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3069.58 | 24-FEB-05:16 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2315.25 | 14-MAR-21:01 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 4070.70 | 01-APR-18:51 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1496.07 | 27-MAY-20:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.88 | 30-JUN-15:00 | 1329.13 | 25-JUN-05:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.08 | 21-JUL-16:00 | 1140.68 | 04-JUL-16:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.11 | 11-AUG-16:00 | 1136.91 | 30-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 926.81 | 04-SEP-14:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2094.08 | 21-OCT-04:03 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1689.18 | 10-NOV-05:08 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1773.54 | 28-DEC-02:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 926.81 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 174.08 | 5143.42 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 9554.07 | 28-JAN-23:51 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 5730.80 | 24-FEB-05:09 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 4308.57 | 14-MAR-21:01 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 5567.66 | 01-APR-18:51 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2682.47 | 27-MAY-04:10 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.76 | 30-JUN-15:00 | 2171.34 | 24-JUN-20:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 586.79 | 29-JUL-20:10 | 1887.70 | 04-JUL-16:51 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.89 | 23-AUG-18:00 | 2092.54 | 30-AUG-04:52 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1697.59 | 30-SEP-04:52 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 3897.38 | 21-OCT-04:50 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 3131.78 | 10-NOV-04:56 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 3278.95 | 28-DEC-02:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1697.59 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 586.79 | 9554.07 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6365.96 | 28-JAN-23:51 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3820.49 | 24-FEB-05:56 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2873.09 | 14-MAR-21:01 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 3707.05 | 01-APR-18:51 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1788.28 | 27-MAY-04:07 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.51 | 30-JUN-15:00 | 1463.49 | 18-JUN-14:20 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 348.38 | 29-JUL-20:10 | 1274.59 | 04-JUL-16:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.88 | 23-AUG-18:00 | 1395.02 | 30-AUG-04:52 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1130.95 | 30-SEP-04:52 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2598.24 | 21-OCT-04:48 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2087.83 | 10-NOV-04:56 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 2185.13 | 28-DEC-02:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1130.95 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 348.38 | 6365.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 9560.06 | 28-JAN-23:51 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 5730.78 | 24-FEB-05:09 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 4346.09 | 12-MAR-15:00 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 6133.82 | 01-APR-18:51 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2682.42 | 27-MAY-04:07 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.76 | 30-JUN-15:00 | 2612.70 | 18-JUN-14:20 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 472.52 | 29-JUL-20:10 | 1956.40 | 04-JUL-16:51 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.34 | 11-AUG-16:00 | 2092.55 | 30-AUG-04:58 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1698.80 | 30-SEP-04:52 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 3897.40 | 21-OCT-04:47 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 3131.74 | 10-NOV-04:51 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 3279.83 | 28-DEC-02:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.80 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 472.52 | 9560.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6373.50 | 28-JAN-23:51 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3820.47 | 24-FEB-05:46 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2876.32 | 14-MAR-21:01 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 4734.13 | 01-APR-18:51 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1788.32 | 27-MAY-04:06 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.51 | 30-JUN-15:00 | 1492.91 | 24-JUN-20:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.68 | 21-JUL-16:00 | 1343.16 | 04-JUL-16:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.90 | 11-AUG-16:00 | 1395.05 | 30-AUG-04:53 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1133.68 | 30-SEP-04:52 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2598.27 | 21-OCT-04:46 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2087.82 | 10-NOV-04:51 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 2191.44 | 28-DEC-02:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1133.68 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 211.68 | 6373.50 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 8217.58 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 8217.58 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 8217.58 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 8217.58 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 8217.58 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 8217.58 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 8217.58 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 8217.58 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 8217.58 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 8217.58 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 8217.58 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 8217.58 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 8217.58 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 8217.58 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 7221.65 | 28-JAN-23:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 4416.30 | 25-FEB-00:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 3167.70 | 25-MAR-03:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 4869.22 | 01-APR-18:51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2266.94 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.68 | 30-JUN-15:00 | 2205.01 | 25-JUN-05:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.27 | 29-JUL-17:01 | 1480.37 | 04-JUL-16:52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.11 | 11-AUG-16:00 | 1781.91 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1406.00 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2957.14 | 21-OCT-03:51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2454.36 | 10-NOV-01:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 2585.06 | 28-DEC-02:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1406.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.27 | 7221.65 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 12712.79 | 28-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 7720.35 | 25-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 5488.70 | 25-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 8479.85 | 01-APR-18:51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 3969.59 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.72 | 30-JUN-15:00 | 3761.85 | 25-JUN-05:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.99 | 29-JUL-17:01 | 2559.29 | 04-JUL-16:51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.60 | 11-AUG-16:00 | 3095.01 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 2362.63 | 30-SEP-21:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 5074.28 | 21-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 4204.81 | 10-NOV-01:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 4402.60 | 28-DEC-02:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2362.63 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.99 | 12712.79 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 13329.67 | 28-JAN-23:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 8307.43 | 25-FEB-00:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 6092.52 | 14-MAR-21:01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 9161.71 | 01-APR-18:57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 3954.28 | 26-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.50 | 30-JUN-15:00 | 3531.81 | 18-JUN-13:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.40 | 29-JUL-19:32 | 3060.65 | 04-JUL-16:51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.08 | 11-AUG-18:00 | 2965.42 | 30-AUG-04:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 2332.97 | 30-SEP-04:52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 5248.47 | 21-OCT-04:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 4413.94 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 4731.38 | 28-DEC-02:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2332.97 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.40 | 13329.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 84733.51 | 12-JAN-07:01 | 25133.15 | 68004.51 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 127551.85 | 11-FEB-06:01 | 17952.25 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 127610.05 | 13-MAR-05:01 | 17952.25 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 120149.45 | 29-APR-04:01 | 0.00 | 16191.55 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 138415.93 | 02-MAY-04:12 | 0.00 | 19429.86 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 144349.76 | 19-JUN-04:12 | 0.00 | 19429.86 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 143675.60 | 10-JUL-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 131004.73 | 21-AUG-04:11 | 0.00 | 22668.17 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 147055.71 | 05-SEP-04:11 | 0.00 | 22668.17 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 145868.01 | 10-OCT-03:01 | 0.00 | 12953.24 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 129172.51 | 02-NOV-05:01 | 17952.25 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 112059.57 | 26-DEC-06:01 | 17952.25 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 84733.51 | 0.00 | 12953.24 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 147055.71 | 25133.15 | 68004.51 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 24978.85 | 20-JAN-17:00 | 15316.26 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 69588.19 | 09-FEB-06:01 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 108971.23 | 23-MAR-05:01 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 112159.06 | 29-APR-04:01 | 0.00 | 14541.15 | 44532.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 113178.15 | 01-MAY-04:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 117466.34 | 30-JUN-04:12 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 122703.66 | 24-JUL-04:12 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 122547.52 | 14-AUG-04:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 116977.21 | 05-SEP-04:11 | 0.00 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 108477.68 | 03-OCT-05:01 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33973.81 | 03-NOV-15:51 | 153162.65 | 261740.70 | 172066.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 32355.15 | 26-DEC-16:53 | 45948.79 | 78522.21 | 51619.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 24978.85 | 0.00 | 14541.15 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 122703.66 | 153162.65 | 261740.70 | 172066.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 22853.42 | 27-JAN-17:00 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28158.28 | 16-FEB-16:51 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 35194.29 | 22-MAR-15:53 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 99799.34 | 21-APR-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 102752.95 | 09-MAY-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 108740.41 | 22-JUN-04:12 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 107648.74 | 25-JUL-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 105830.59 | 03-AUG-04:11 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 100611.42 | 01-SEP-05:01 | 12897.91 | 23265.84 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 93582.77 | 06-OCT-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24174.61 | 03-NOV-15:51 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21089.97 | 15-DEC-17:00 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 21089.97 | 0.00 | 20357.61 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 108740.41 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19932.81 | 19-JAN-17:00 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22902.04 | 09-FEB-17:00 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 25803.45 | 22-MAR-16:00 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39576.32 | 20-APR-15:54 | 76581.32 | 130870.35 | 86032.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 54777.17 | 31-MAY-05:01 | 14510.15 | 26174.07 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 126479.89 | 21-JUN-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 126595.74 | 25-JUL-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 124089.09 | 03-AUG-05:01 | 11285.67 | 20357.61 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35911.22 | 01-SEP-15:57 | 45948.79 | 78522.21 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25756.67 | 04-OCT-16:00 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20373.22 | 02-NOV-16:00 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18807.47 | 29-DEC-17:00 | 61265.06 | 104696.28 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 18807.47 | 0.00 | 20357.61 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 126595.74 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2948.93 | 21-JAN-17:01 | 708.51 | 1278.05 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.57 |
February | 3619.49 | 09-FEB-06:02 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.93 |
March | 4725.40 | 21-MAR-05:02 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6408.94 | 30-APR-13:41 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 738.77 |
May | 22845.06 | 31-MAY-04:12 | 0.00 | 2190.94 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24930.37 | 09-JUN-04:11 | 0.00 | 3651.57 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.52 |
July | 25943.94 | 11-JUL-04:22 | 0.00 | 3651.57 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.34 |
August | 9606.63 | 02-AUG-14:00 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.47 |
September | 6316.66 | 01-SEP-13:40 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.03 |
October | 5153.08 | 04-OCT-05:02 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.40 |
November | 3089.81 | 06-NOV-06:04 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3128.72 | 29-DEC-06:04 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2948.93 | 0.00 | 1278.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25943.94 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 738.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3420.79 | 23-JAN-06:03 | 1304.55 | 2353.21 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3781.46 | 15-FEB-10:41 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.14 |
March | 7753.83 | 22-MAR-09:51 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11604.36 | 22-APR-09:23 | 4092.09 | 7059.64 | 7735.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.55 |
May | 23257.61 | 14-MAY-09:12 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.48 |
June | 28908.99 | 18-JUN-10:11 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.75 |
July | 29846.86 | 23-JUL-07:11 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28213.84 | 27-AUG-10:21 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.47 |
September | 12926.76 | 10-SEP-11:02 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.68 |
October | 7571.81 | 03-OCT-09:43 | 10366.64 | 16943.13 | 11138.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.75 |
November | 3347.83 | 20-NOV-06:04 | 1304.55 | 2353.21 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.90 |
December | 3370.62 | 18-DEC-06:04 | 1304.55 | 2353.21 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3347.83 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29846.86 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5967.13 | 25-JAN-13:30 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.22 |
February | 12168.28 | 15-FEB-13:21 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20149.36 | 26-MAR-14:35 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43805.00 | 09-APR-14:01 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 560.26 |
May | 32297.80 | 14-MAY-12:32 | 506.09 | 912.91 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.05 |
June | 46686.93 | 04-JUN-14:41 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.33 |
July | 45743.08 | 23-JUL-13:12 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.23 |
August | 46063.66 | 27-AUG-11:41 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.99 |
September | 29689.37 | 10-SEP-11:02 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.08 |
October | 21114.44 | 03-OCT-13:22 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.75 |
November | 8851.54 | 08-NOV-13:21 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.39 |
December | 5224.36 | 14-DEC-06:04 | 2024.37 | 3651.65 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5224.36 | 506.09 | 912.91 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46686.93 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 560.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4096.63 | 19-JAN-06:03 | 913.19 | 1647.25 | 4331.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.08 |
February | 4564.09 | 09-FEB-06:02 | 1304.55 | 2353.21 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.11 |
March | 10809.12 | 26-MAR-16:36 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33384.91 | 09-APR-16:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.60 |
May | 21749.09 | 28-MAY-17:52 | 0.00 | 588.30 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.38 |
June | 37164.81 | 11-JUN-17:01 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.69 |
July | 34251.41 | 30-JUL-18:21 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.41 |
August | 32116.71 | 27-AUG-17:02 | 0.00 | 705.96 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.34 |
September | 20885.13 | 02-SEP-17:42 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.94 |
October | 6889.75 | 04-OCT-04:11 | 0.00 | 2353.21 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.29 |
November | 4771.41 | 08-NOV-15:30 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.07 |
December | 4259.37 | 14-DEC-04:01 | 0.00 | 1176.61 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4096.63 | 0.00 | 588.30 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37164.81 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4004.23 | 19-JAN-06:04 | 1417.03 | 2556.10 | 6721.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.15 |
February | 4019.47 | 07-FEB-06:04 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.48 |
March | 4509.61 | 22-MAR-14:02 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5969.98 | 28-APR-05:02 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.32 |
May | 24388.41 | 31-MAY-05:01 | 1821.89 | 3286.42 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.32 |
June | 29711.02 | 29-JUN-04:51 | 0.00 | 3651.57 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.49 |
July | 30134.29 | 07-JUL-04:51 | 0.00 | 3651.57 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.09 |
August | 8307.08 | 02-AUG-15:40 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 |
September | 5767.44 | 02-SEP-05:03 | 809.73 | 1460.63 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.88 |
October | 4519.47 | 04-OCT-15:01 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.46 |
November | 4035.58 | 18-NOV-06:04 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.71 |
December | 3706.71 | 23-DEC-17:01 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3706.71 | 0.00 | 1460.63 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30134.29 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3716.29 | 19-JAN-11:04 | 6196.63 | 10589.46 | 6961.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.28 |
February | 4678.24 | 15-FEB-11:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.77 |
March | 16581.23 | 22-MAR-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.06 |
April | 20908.22 | 22-APR-10:01 | 3913.66 | 7059.64 | 7735.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.40 |
May | 32652.60 | 14-MAY-08:51 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 612.43 |
June | 29813.21 | 18-JUN-10:21 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 627.98 |
July | 31334.41 | 23-JUL-07:11 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28628.65 | 27-AUG-10:21 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.77 |
September | 19862.79 | 10-SEP-09:32 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.90 |
October | 13518.55 | 13-OCT-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.55 |
November | 3682.41 | 24-NOV-11:03 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3676.88 | 21-DEC-11:03 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3676.88 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32652.60 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 627.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5942.34 | 25-JAN-13:40 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.75 |
February | 12657.03 | 15-FEB-13:31 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22056.81 | 26-MAR-14:13 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46559.01 | 09-APR-14:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 513.00 |
May | 50126.78 | 21-MAY-13:21 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1170.90 |
June | 49048.43 | 04-JUN-14:51 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 658.38 |
July | 48647.93 | 23-JUL-13:52 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.40 |
August | 47298.92 | 27-AUG-13:42 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.62 |
September | 22574.78 | 07-SEP-14:25 | 7692.61 | 13145.95 | 8642.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.14 |
October | 21865.35 | 03-OCT-13:29 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.18 |
November | 8032.92 | 08-NOV-13:50 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.90 |
December | 5547.87 | 16-DEC-06:04 | 2024.37 | 3651.65 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5547.87 | 607.31 | 1095.50 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50126.78 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1170.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3752.96 | 05-JAN-06:04 | 1043.64 | 1882.57 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.89 |
February | 3752.46 | 02-FEB-06:03 | 1304.55 | 2353.21 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.51 |
March | 5097.92 | 27-MAR-17:00 | 3913.66 | 11766.06 | 7735.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.60 |
April | 15478.60 | 22-APR-17:06 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1046.38 |
May | 32489.64 | 28-MAY-17:41 | 0.00 | 823.62 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.84 |
June | 33398.55 | 11-JUN-17:21 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 790.93 |
July | 16154.59 | 06-JUL-17:50 | 130.46 | 705.96 | 618.81 | 0.00 | 0.00 | 0.00 | 0.00 | 1.76 | 0.00 |
August | 23348.81 | 27-AUG-17:42 | 0.00 | 705.96 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.16 |
September | 9041.16 | 07-SEP-15:55 | 4957.30 | 8471.56 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.98 |
October | 4899.54 | 03-OCT-15:10 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.43 |
November | 3832.31 | 24-NOV-06:04 | 1304.55 | 2353.21 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.84 |
December | 3696.08 | 30-DEC-06:04 | 1304.55 | 2353.21 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3696.08 | 0.00 | 705.96 | 618.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33398.55 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1.76 | 1046.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5286.93 | 17-JAN-06:04 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.01 |
February | 4905.36 | 11-FEB-17:01 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.70 |
March | 4999.30 | 18-MAR-16:01 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6386.61 | 28-APR-15:20 | 7692.44 | 13145.66 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.58 |
May | 19137.49 | 31-MAY-05:01 | 1821.89 | 3286.42 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.72 |
June | 33007.85 | 28-JUN-05:01 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.74 |
July | 30649.28 | 11-JUL-04:11 | 0.00 | 3651.57 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 689.73 |
August | 9742.51 | 03-AUG-05:01 | 1417.03 | 2556.10 | 6721.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.16 |
September | 6411.19 | 01-SEP-16:00 | 5769.33 | 9859.25 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.42 |
October | 5606.60 | 20-OCT-05:03 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.80 |
November | 5440.51 | 02-NOV-05:04 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.48 |
December | 5482.62 | 21-DEC-06:04 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4905.36 | 0.00 | 1825.79 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33007.85 | 7692.44 | 13145.66 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 689.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3482.72 | 17-JAN-06:04 | 1304.55 | 2353.21 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.90 |
February | 3242.06 | 11-FEB-17:01 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.11 |
March | 5080.72 | 22-MAR-10:31 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.54 |
April | 9191.91 | 21-APR-10:13 | 7435.95 | 12707.35 | 8354.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.84 |
May | 32394.37 | 14-MAY-09:41 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.87 |
June | 29618.21 | 04-JUN-10:31 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 659.40 |
July | 33438.45 | 23-JUL-11:01 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16858.82 | 10-AUG-09:03 | 7774.98 | 12707.35 | 8354.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.90 |
September | 7039.73 | 10-SEP-09:35 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 637.56 |
October | 4707.13 | 03-OCT-10:30 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.15 |
November | 3581.87 | 02-NOV-05:04 | 1304.55 | 2353.21 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.20 |
December | 3653.34 | 21-DEC-06:04 | 1304.55 | 2353.21 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3242.06 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33438.45 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 659.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6036.96 | 25-JAN-06:04 | 1821.93 | 3286.49 | 8642.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9107.42 | 15-FEB-13:51 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18535.44 | 31-MAR-13:51 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 531.74 |
April | 27883.82 | 20-APR-13:53 | 8043.34 | 13145.95 | 8642.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.35 |
May | 50381.56 | 14-MAY-12:21 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 743.90 |
June | 51119.78 | 04-JUN-14:41 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.93 |
July | 58881.78 | 23-JUL-13:41 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.07 |
August | 54459.95 | 27-AUG-13:31 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.95 |
September | 21756.80 | 07-SEP-14:25 | 7692.61 | 13145.95 | 8642.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.01 |
October | 19492.49 | 03-OCT-13:22 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.04 |
November | 7312.24 | 08-NOV-13:50 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.36 |
December | 6009.48 | 21-DEC-06:04 | 2024.37 | 3651.65 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6009.48 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 58881.78 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3943.73 | 25-JAN-06:04 | 1174.10 | 2117.89 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3994.35 | 04-FEB-06:04 | 1304.55 | 2353.21 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5030.01 | 27-MAR-16:53 | 3913.66 | 11766.06 | 7735.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 546.70 |
April | 14032.60 | 20-APR-17:44 | 652.28 | 3529.82 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.65 |
May | 32376.80 | 28-MAY-17:41 | 0.00 | 823.62 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.36 |
June | 34788.61 | 11-JUN-16:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 963.33 |
July | 18601.75 | 30-JUL-19:01 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.17 |
August | 28568.42 | 27-AUG-17:31 | 0.00 | 1058.95 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 589.96 |
September | 9138.10 | 02-SEP-17:22 | 326.14 | 588.30 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.17 |
October | 4816.25 | 03-OCT-15:10 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.84 |
November | 4007.96 | 14-NOV-06:04 | 1304.55 | 2353.21 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.88 |
December | 4006.48 | 07-DEC-06:04 | 1304.55 | 2353.21 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3943.73 | 0.00 | 588.30 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34788.61 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 963.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15774.11 | 13-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16071.77 | 25-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1470.81 |
March | 17738.35 | 31-MAR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1751.77 |
April | 11709.37 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1811.11 |
May | 9759.88 | 16-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.66 |
June | 10338.99 | 17-JUN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.89 |
July | 12228.22 | 05-JUL-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.83 |
August | 11551.66 | 07-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.14 |
September | 10772.73 | 05-SEP-04:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.39 |
October | 16139.71 | 27-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2589.32 |
November | 14666.51 | 30-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15966.92 | 15-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9759.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17738.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2589.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20771.79 | 26-JAN-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24017.33 | 18-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.86 |
March | 22288.27 | 25-MAR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5442.54 |
April | 18309.13 | 01-APR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4630.74 |
May | 9230.20 | 20-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.76 |
June | 9385.45 | 24-JUN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.05 |
July | 10423.57 | 05-JUL-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.85 |
August | 12097.40 | 31-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.67 |
September | 16216.51 | 30-SEP-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1688.13 |
October | 22969.98 | 22-OCT-05:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2928.13 |
November | 21038.48 | 09-NOV-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20976.34 | 15-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9230.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24017.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5442.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2706.80 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2238.44 |
March | 4237.12 | 22-MAR-16:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12455.47 | 20-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.51 |
May | 19840.15 | 31-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.46 |
June | 22548.29 | 29-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
July | 22844.60 | 21-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.18 | 0.00 |
August | 18739.73 | 10-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.16 |
September | 8562.67 | 07-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.08 |
October | 3374.86 | 03-OCT-16:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.74 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2524.92 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22844.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.18 | 2706.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 4919.04 | 30-JAN-11:01 | 2221.41 | 7287.84 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10585.12 | 22-FEB-11:01 | 2221.41 | 7287.84 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11023.88 | 01-MAR-09:31 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8633.62 | 20-APR-18:51 | 163.68 | 1700.50 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3433.67 | 31-MAY-23:51 | 0.00 | 323.90 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5322.13 | 30-JUN-23:52 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7215.54 | 31-JUL-24:00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8217.88 | 27-AUG-18:42 | 0.00 | 202.44 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2727.68 | 30-SEP-23:51 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4162.39 | 31-OCT-23:42 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11487.47 | 08-NOV-22:01 | 116.92 | 809.76 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13552.77 | 07-DEC-10:01 | 2322.69 | 7287.84 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2727.68 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13552.77 | 2322.69 | 7287.84 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2872.30 | 13-JAN-15:22 | 1110.71 | 3643.92 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10150.42 | 28-FEB-11:21 | 2221.41 | 7287.84 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10621.10 | 01-MAR-09:31 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8333.52 | 20-APR-18:51 | 163.68 | 1700.50 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3137.09 | 31-MAY-23:41 | 0.00 | 283.42 | 27280.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5102.40 | 30-JUN-23:32 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7010.41 | 31-JUL-23:15 | 0.00 | 161.95 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7877.56 | 10-AUG-19:00 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2070.90 | 06-SEP-17:55 | 46.77 | 485.86 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3569.95 | 03-OCT-15:51 | 2221.41 | 7287.84 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10770.29 | 29-NOV-13:31 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12389.60 | 07-DEC-10:01 | 2322.69 | 7287.84 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2070.90 | 0.00 | 161.95 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12389.60 | 2322.69 | 7287.84 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 446.99 | 19-JAN-11:04 | 1110.71 | 3643.92 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10112.68 | 28-FEB-11:21 | 2221.41 | 7287.84 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10540.97 | 01-MAR-09:31 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8272.28 | 20-APR-18:51 | 163.68 | 1700.50 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2987.58 | 31-MAY-23:12 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4984.83 | 30-JUN-23:12 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6906.44 | 31-JUL-23:04 | 0.00 | 202.44 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7926.37 | 10-AUG-19:00 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1917.55 | 08-SEP-17:27 | 140.30 | 1457.57 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3372.60 | 03-OCT-15:51 | 2221.41 | 7287.84 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10689.20 | 29-NOV-13:31 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11991.77 | 11-DEC-19:01 | 233.83 | 2429.28 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 446.99 | 0.00 | 202.44 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11991.77 | 2221.41 | 7287.84 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 94965.25 | 06-JAN-13:01 | 43278.11 | 73958.25 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 502580.94 | 09-FEB-11:42 | 48086.79 | 82175.84 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 535621.53 | 01-MAR-00:02 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 515516.49 | 13-APR-14:10 | 48086.79 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 486853.60 | 31-MAY-23:38 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 507784.17 | 30-JUN-23:09 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 534364.36 | 04-JUL-13:16 | 2530.88 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 518456.26 | 20-AUG-12:11 | 2530.88 | 4565.32 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 499574.67 | 30-SEP-23:12 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 532479.70 | 31-OCT-23:01 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 525097.40 | 02-NOV-21:53 | 2530.88 | 9130.65 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 497171.99 | 15-DEC-12:08 | 26462.74 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 94965.25 | 0.00 | 4565.32 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 535621.53 | 48086.79 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.194749E+13 | 1395093.28 | 27-JAN-16:00 | 0.227024E+13 | 2841718.54 | 12-JAN-07:30 |
February | 0.212433E+13 | 1622510.46 | 09-FEB-16:00 | 0.161130E+13 | 3075343.59 | 27-FEB-07:19 |
March | 0.286444E+13 | 1775386.69 | 22-MAR-14:09 | 0.125292E+13 | 2351813.98 | 01-MAR-07:40 |
April | 0.313320E+13 | 2019842.23 | 21-APR-15:50 | 0.357682E+12 | 1986841.06 | 03-APR-06:19 |
May | 0.204287E+13 | 1731192.36 | 31-MAY-15:00 | 0.341373E+11 | 715735.91 | 27-MAY-04:10 |
June | 0.241242E+13 | 2004297.60 | 22-JUN-15:00 | 0.116156E+10 | 43652.29 | 02-JUN-05:49 |
July | 0.277717E+13 | 2118639.59 | 31-JUL-14:39 | 0.139917E+10 | 65882.64 | 06-JUL-05:10 |
August | 0.321429E+13 | 2299393.13 | 10-AUG-15:30 | 0.200956E+11 | 755956.24 | 30-AUG-05:10 |
September | 0.182863E+13 | 1596888.83 | 07-SEP-15:00 | 0.169168E+12 | 870656.03 | 30-SEP-04:10 |
October | 0.233268E+13 | 1674537.91 | 03-OCT-14:09 | 0.869836E+12 | 1933773.04 | 30-OCT-06:19 |
November | 0.276685E+13 | 1741747.54 | 06-NOV-16:30 | 0.190585E+13 | 2578002.51 | 27-NOV-07:19 |
December | 0.323847E+13 | 1924829.13 | 29-DEC-16:00 | 0.227920E+13 | 2460543.98 | 15-DEC-07:00 |
Annual Sum or Average | 0.306828E+14 | 0.107730E+14 | ||||
Minimum of Months | 0.182863E+13 | 1395093.28 | 0.116156E+10 | 43652.29 | ||
Maximum of Months | 0.323847E+13 | 2299393.13 | 0.227920E+13 | 3075343.59 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.468149E+12 | 0.137881E+12 | 0.766053E+12 | 0.218140E+12 | 0.197457E+12 | 0.151393E+11 | 0.00 | 0.488663E+10 | 0.00 | 0.915464E+11 | 0.00 | 0.482337E+11 | 0.00 |
February | 0.424646E+12 | 0.103160E+12 | 0.978954E+12 | 0.199667E+12 | 0.196082E+12 | 0.246951E+11 | 0.00 | 0.560367E+11 | 7226212.83 | 0.972632E+11 | 0.00 | 0.438221E+11 | 0.00 |
March | 0.504598E+12 | 0.900107E+11 | 0.141687E+13 | 0.230864E+12 | 0.222983E+12 | 0.744033E+11 | 0.00 | 0.990569E+11 | 4206936.49 | 0.174129E+12 | 0.00 | 0.515215E+11 | 0.00 |
April | 0.450709E+12 | 0.633651E+11 | 0.165903E+13 | 0.216144E+12 | 0.245589E+12 | 0.884819E+11 | 0.00 | 0.115217E+12 | 1383454.78 | 0.247945E+12 | 0.00 | 0.467227E+11 | 0.00 |
May | 0.486374E+12 | 0.414103E+11 | 0.774844E+12 | 0.224502E+12 | 0.227510E+12 | 0.317384E+11 | 0.00 | 0.538069E+11 | 0.195278E+09 | 0.152972E+12 | 0.00 | 0.495131E+11 | 0.00 |
June | 0.484022E+12 | 0.230698E+11 | 0.106252E+13 | 0.222585E+12 | 0.265070E+12 | 0.634524E+11 | 0.00 | 0.180718E+12 | 0.629606E+10 | 0.573674E+11 | 0.00 | 0.473195E+11 | 0.00 |
July | 0.453060E+12 | 0.320670E+11 | 0.139340E+13 | 0.218061E+12 | 0.285440E+12 | 0.940990E+11 | 0.00 | 0.232729E+12 | 0.120822E+11 | 0.128589E+11 | 0.00 | 0.433689E+11 | 0.00 |
August | 0.504598E+12 | 0.553291E+11 | 0.173200E+13 | 0.230864E+12 | 0.300645E+12 | 0.936698E+11 | 0.00 | 0.195830E+12 | 0.560808E+10 | 0.494169E+11 | 0.00 | 0.463252E+11 | 0.00 |
September | 0.450709E+12 | 0.769378E+11 | 0.740713E+12 | 0.216143E+12 | 0.184073E+12 | 0.155823E+11 | 0.00 | 0.269550E+11 | 9400105.32 | 0.756023E+11 | 0.00 | 0.419030E+11 | 0.00 |
October | 0.468149E+12 | 0.103776E+12 | 0.108340E+13 | 0.218140E+12 | 0.201289E+12 | 0.320849E+11 | 0.00 | 0.716014E+11 | 8695336.95 | 0.110164E+12 | 0.00 | 0.440645E+11 | 0.00 |
November | 0.462662E+12 | 0.124462E+12 | 0.135889E+13 | 0.209941E+12 | 0.219797E+12 | 0.961106E+11 | 0.00 | 0.802005E+11 | 1005838.39 | 0.170025E+12 | 0.00 | 0.447580E+11 | 0.00 |
December | 0.453060E+12 | 0.147647E+12 | 0.170972E+13 | 0.218060E+12 | 0.243498E+12 | 0.945426E+11 | 0.00 | 0.948817E+11 | 120968.43 | 0.230699E+12 | 0.00 | 0.463597E+11 | 0.00 |
Annual Sum or Average | 0.561074E+13 | 0.999115E+12 | 0.146764E+14 | 0.262311E+13 | 0.278943E+13 | 0.724000E+12 | 0.00 | 0.121192E+13 | 0.242137E+11 | 0.146999E+13 | 0.00 | 0.553912E+12 | 0.00 |
Minimum of Months | 0.424646E+12 | 0.230698E+11 | 0.740713E+12 | 0.199667E+12 | 0.184073E+12 | 0.151393E+11 | 0.00 | 0.488663E+10 | 0.00 | 0.128589E+11 | 0.00 | 0.419030E+11 | 0.00 |
Maximum of Months | 0.504598E+12 | 0.147647E+12 | 0.173200E+13 | 0.230864E+12 | 0.300645E+12 | 0.961106E+11 | 0.00 | 0.232729E+12 | 0.120822E+11 | 0.247945E+12 | 0.00 | 0.515215E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.227024E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.161130E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.125292E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.357682E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.341373E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.116156E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.139917E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.200956E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.169168E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.869836E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.190585E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.227920E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.107730E+14 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.116156E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.227920E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 489900.85 | 02-JAN-08:09 | 64082.80 | 01-JAN-00:10 | 423497.50 | 02-JAN-08:09 | 235096.12 | 02-JAN-08:20 | 146583.94 | 02-JAN-06:19 | 37551.20 | 15-JAN-09:50 | 0.00 | 01-JAN-00:10 |
February | 489900.85 | 01-FEB-08:09 | 64082.80 | 01-FEB-00:10 | 541788.89 | 01-FEB-08:09 | 235096.12 | 01-FEB-08:20 | 141843.92 | 27-FEB-06:10 | 38171.05 | 10-FEB-16:49 | 0.00 | 01-FEB-00:10 |
March | 489900.85 | 01-MAR-08:09 | 64082.80 | 01-MAR-00:10 | 660080.29 | 01-MAR-08:09 | 235096.12 | 01-MAR-08:20 | 158321.78 | 31-MAR-14:20 | 39837.14 | 27-MAR-04:10 | 0.00 | 01-MAR-00:10 |
April | 489900.85 | 03-APR-07:10 | 64082.80 | 01-APR-00:10 | 778371.69 | 03-APR-07:10 | 235096.12 | 03-APR-07:19 | 246261.26 | 21-APR-15:00 | 39751.55 | 03-APR-04:10 | 0.00 | 01-APR-00:10 |
May | 489900.85 | 01-MAY-07:10 | 64082.80 | 01-MAY-00:10 | 423497.50 | 01-MAY-07:10 | 235096.12 | 01-MAY-07:19 | 228560.41 | 31-MAY-15:20 | 39612.55 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 489900.85 | 01-JUN-07:10 | 64082.80 | 01-JUN-00:10 | 541788.89 | 01-JUN-07:10 | 235096.12 | 01-JUN-07:19 | 250276.38 | 29-JUN-14:30 | 82447.63 | 20-JUN-13:20 | 0.00 | 01-JUN-00:10 |
July | 489900.85 | 03-JUL-07:10 | 64082.80 | 01-JUL-00:10 | 660080.29 | 03-JUL-07:10 | 235096.12 | 03-JUL-07:19 | 265920.14 | 21-JUL-14:30 | 83447.20 | 19-JUL-15:39 | 0.00 | 01-JUL-00:10 |
August | 489900.85 | 01-AUG-07:10 | 64082.80 | 01-AUG-00:10 | 778371.69 | 01-AUG-07:10 | 235096.12 | 01-AUG-07:19 | 277543.21 | 10-AUG-15:30 | 83900.94 | 11-AUG-14:50 | 0.00 | 01-AUG-00:10 |
September | 489900.85 | 01-SEP-07:10 | 64082.80 | 01-SEP-00:10 | 423497.50 | 01-SEP-07:10 | 235096.12 | 01-SEP-07:19 | 198537.90 | 07-SEP-15:30 | 38953.27 | 18-SEP-14:09 | 0.00 | 01-SEP-00:10 |
October | 489900.85 | 02-OCT-07:10 | 64082.80 | 01-OCT-00:10 | 541788.89 | 02-OCT-07:10 | 235096.12 | 02-OCT-07:19 | 173918.47 | 03-OCT-14:09 | 39451.19 | 03-OCT-14:09 | 0.00 | 01-OCT-00:10 |
November | 489900.85 | 01-NOV-07:10 | 64082.80 | 01-NOV-00:10 | 660080.29 | 01-NOV-07:10 | 235096.12 | 01-NOV-07:19 | 136888.63 | 13-NOV-06:10 | 41020.19 | 27-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 489900.85 | 01-DEC-08:09 | 64082.80 | 01-DEC-00:10 | 778371.69 | 01-DEC-08:09 | 235096.12 | 01-DEC-08:20 | 140308.68 | 04-DEC-05:10 | 40712.84 | 04-DEC-05:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 489900.85 | 64082.80 | 423497.50 | 235096.12 | 136888.63 | 37551.20 | 0.00 | |||||||
Maximum of Months | 489900.85 | 64082.80 | 778371.69 | 235096.12 | 277543.21 | 83900.94 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 5888.01 | 07-JAN-00:20 | 0.00 | 01-JAN-00:10 | 41068.80 | 19-JAN-05:40 | 0.00 | 63566.02 | 13-JAN-12:30 | 0.00 |
February | 67059.94 | 09-FEB-16:00 | 16.50 | 09-FEB-07:10 | 63345.45 | 27-FEB-21:10 | 0.00 | 63561.19 | 01-FEB-12:30 | 0.00 |
March | 91553.12 | 22-MAR-13:50 | 28.83 | 22-MAR-14:09 | 99614.55 | 31-MAR-23:00 | 0.00 | 63561.08 | 01-MAR-12:20 | 0.00 |
April | 133408.33 | 06-APR-13:39 | 71.76 | 06-APR-14:09 | 100000.00 | 01-APR-01:30 | 0.00 | 63540.84 | 03-APR-11:30 | 0.00 |
May | 168280.72 | 31-MAY-15:00 | 5594.89 | 31-MAY-15:00 | 100000.00 | 06-MAY-17:10 | 0.00 | 63531.91 | 03-MAY-11:39 | 0.00 |
June | 330946.17 | 20-JUN-13:00 | 47562.77 | 29-JUN-13:39 | 100000.00 | 03-JUN-16:10 | 0.00 | 62144.72 | 02-JUN-11:20 | 0.00 |
July | 344180.58 | 21-JUL-12:09 | 47562.77 | 03-JUL-14:00 | 100000.00 | 12-JUL-22:40 | 0.00 | 59209.91 | 03-JUL-11:30 | 0.00 |
August | 333442.42 | 11-AUG-14:39 | 47562.77 | 23-AUG-14:00 | 100000.00 | 10-AUG-21:10 | 0.00 | 57952.32 | 01-AUG-11:50 | 0.00 |
September | 125840.79 | 18-SEP-13:39 | 1371.38 | 18-SEP-13:00 | 83519.06 | 07-SEP-15:00 | 0.00 | 57319.53 | 29-SEP-11:30 | 0.00 |
October | 124321.06 | 03-OCT-13:50 | 523.34 | 03-OCT-13:50 | 70756.51 | 04-OCT-11:39 | 0.00 | 58686.66 | 31-OCT-11:20 | 0.00 |
November | 56825.24 | 03-NOV-03:39 | 14.36 | 03-NOV-03:39 | 76939.89 | 04-NOV-02:00 | 0.00 | 60923.90 | 30-NOV-12:20 | 0.00 |
December | 87640.92 | 21-DEC-22:40 | 14.23 | 15-DEC-08:20 | 100000.00 | 05-DEC-22:40 | 0.00 | 63550.52 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 5888.01 | 0.00 | 41068.80 | 0.00 | 57319.53 | 0.00 | ||||
Maximum of Months | 344180.58 | 47562.77 | 100000.00 | 0.00 | 63566.02 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1395093.28 | 27-JAN-16:00 | 489900.85 | 423497.50 | 64082.80 | 235096.12 | 92583.10 | 535.16 | 0.00 | 4638.02 | 0.00 |
February | 1622510.46 | 09-FEB-16:00 | 489900.85 | 541788.89 | 64082.80 | 235096.12 | 110350.80 | 26785.71 | 0.00 | 67059.94 | 7.53 |
March | 1775386.69 | 22-MAR-14:09 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 155294.93 | 39166.85 | 0.00 | 89169.82 | 28.83 |
April | 2019842.23 | 21-APR-15:50 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 245031.01 | 39139.42 | 0.00 | 83672.13 | 21.53 |
May | 1731192.36 | 31-MAY-15:00 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 221546.74 | 39612.55 | 0.00 | 168280.72 | 5594.89 |
June | 2004297.60 | 22-JUN-15:00 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 228824.06 | 77658.92 | 0.00 | 268083.71 | 16706.84 |
July | 2118639.59 | 31-JUL-14:39 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 245081.27 | 77890.20 | 0.00 | 284832.53 | 26793.34 |
August | 2299393.13 | 10-AUG-15:30 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 277543.21 | 77778.37 | 0.00 | 280623.02 | 16485.62 |
September | 1596888.83 | 07-SEP-15:00 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 187492.98 | 38536.65 | 0.00 | 95375.01 | 183.21 |
October | 1674537.91 | 03-OCT-14:09 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 173918.47 | 39451.19 | 0.00 | 117633.88 | 385.25 |
November | 1741747.54 | 06-NOV-16:30 | 489900.85 | 660080.29 | 64082.80 | 235096.12 | 103458.82 | 38757.56 | 0.00 | 34332.42 | 0.00 |
December | 1924829.13 | 29-DEC-16:00 | 489900.85 | 778371.69 | 64082.80 | 235096.12 | 115044.81 | 39755.50 | 0.00 | 73596.03 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1395093.28 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 92583.10 | 535.16 | 0.00 | 4638.02 | 0.00 | |
Maximum of Months | 2299393.13 | 489900.85 | 778371.69 | 64082.80 | 235096.12 | 277543.21 | 77890.20 | 0.00 | 284832.53 | 26793.34 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 2841718.54 | 12-JAN-07:30 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 3075343.59 | 27-FEB-07:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 2351813.98 | 01-MAR-07:40 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 1986841.06 | 03-APR-06:19 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 715735.91 | 27-MAY-04:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 43652.29 | 02-JUN-05:49 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 65882.64 | 06-JUL-05:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 755956.24 | 30-AUG-05:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 870656.03 | 30-SEP-04:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 1933773.04 | 30-OCT-06:19 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 2578002.51 | 27-NOV-07:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 2460543.98 | 15-DEC-07:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 43652.29 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 3075343.59 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.33 | 20.06 | 7.33 | 20.06 | 0.00 | 20.06 | 0.00 | 20.06 |
February | 0.50 | 20.34 | 0.50 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 25.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.65 | 0.00 | 25.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.73 | 0.00 | 25.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 25.73 | 0.00 | 25.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 26.86 | 0.67 | 26.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.70 | 0.00 | 25.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7.83 | 20.08 | 7.83 | 20.08 | 8.17 | 22.10 | 0.67 | 22.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.33 | 20.34 | 7.33 | 20.34 | 3.17 | 26.86 | 0.67 | 26.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.44 | 0.17 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 20.44 | 0.17 | 20.44 | 0.33 | 23.00 | 0.00 | 23.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.44 | 0.17 | 20.44 | 0.17 | 25.57 | 0.00 | 25.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 19.26 | 0.67 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
November | 0.17 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 |
December | 0.17 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 |
Annual Sum or Average | 2.33 | 19.14 | 0.67 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 19.42 | 0.67 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.33 | 18.55 | 0.33 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
February | 6.17 | 18.50 | 0.33 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
March | 3.83 | 18.64 | 0.33 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
April | 1.17 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.17 | 17.98 | 0.00 | 17.98 | 0.00 | 17.98 | 0.00 | 17.98 |
October | 2.33 | 17.94 | 0.00 | 17.94 | 0.00 | 17.94 | 0.00 | 17.94 |
November | 6.67 | 18.67 | 0.67 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 |
December | 7.33 | 18.67 | 0.17 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
Annual Sum or Average | 35.00 | 18.55 | 1.83 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.33 | 18.67 | 0.67 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.50 | 17.43 | 0.83 | 17.35 | 0.00 | 17.35 | 0.00 | 17.35 |
February | 7.67 | 18.20 | 1.00 | 18.43 | 0.00 | 18.43 | 0.00 | 18.43 |
March | 5.83 | 18.83 | 0.83 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
April | 0.50 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 26.09 | 0.00 | 26.09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.00 | 0.00 | 26.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.17 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
November | 5.50 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
December | 8.33 | 18.79 | 0.50 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
Annual Sum or Average | 41.50 | 18.29 | 3.17 | 18.36 | 3.50 | 18.92 | 0.00 | 18.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.50 | 19.02 | 1.00 | 19.02 | 2.00 | 26.09 | 0.00 | 26.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.83 | 16.39 | 4.67 | 16.17 | 0.00 | 16.17 | 0.00 | 16.17 |
February | 9.83 | 17.36 | 1.33 | 17.31 | 0.00 | 17.31 | 0.00 | 17.31 |
March | 5.67 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
April | 0.67 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.34 | 2.67 | 28.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.83 | 0.83 | 27.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.74 | 2.17 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.69 | 0.50 | 27.69 |
October | 1.33 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
November | 6.83 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
December | 9.83 | 18.31 | 0.17 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 |
Annual Sum or Average | 56.00 | 17.46 | 6.17 | 17.28 | 7.33 | 18.39 | 6.17 | 19.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 21.83 | 19.00 | 4.67 | 19.00 | 2.67 | 28.34 | 2.67 | 28.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 23.50 | 16.24 | 5.00 | 16.04 | 0.00 | 16.04 | 0.00 | 16.04 |
February | 11.00 | 17.28 | 1.83 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
March | 6.00 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 |
April | 0.67 | 19.02 | 0.00 | 19.02 | 1.33 | 24.63 | 1.33 | 25.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.93 | 2.67 | 27.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.69 | 1.17 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.38 | 2.17 | 28.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.40 | 1.67 | 28.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.68 | 0.17 | 27.68 |
October | 1.67 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
November | 7.50 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 |
December | 10.67 | 18.15 | 0.17 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 |
Annual Sum or Average | 61.00 | 17.34 | 7.00 | 17.16 | 9.17 | 18.45 | 9.17 | 19.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.04 | 0.00 | 16.04 |
Maximum of Months | 23.50 | 19.02 | 5.00 | 19.02 | 2.67 | 28.40 | 2.67 | 28.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.17 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
February | 3.67 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
March | 2.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.87 | 0.83 | 27.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.15 | 1.17 | 28.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.97 | 1.17 | 28.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.75 | 1.83 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.04 | 1.83 | 28.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.67 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
Annual Sum or Average | 12.83 | 18.87 | 0.00 | 18.87 | 17.50 | 24.11 | 6.83 | 24.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.17 | 19.34 | 0.00 | 19.34 | 4.50 | 28.15 | 1.83 | 28.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 52.50 | 15.19 | 15.83 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 |
February | 43.17 | 15.55 | 11.67 | 15.46 | 0.00 | 15.46 | 0.00 | 15.46 |
March | 21.67 | 16.79 | 1.33 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 |
April | 8.33 | 16.80 | 1.00 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.84 | 0.00 | 25.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.33 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
October | 14.33 | 16.42 | 2.17 | 16.26 | 0.00 | 16.26 | 0.00 | 16.26 |
November | 38.67 | 15.83 | 9.17 | 15.72 | 0.00 | 15.72 | 0.00 | 15.72 |
December | 50.67 | 15.65 | 12.83 | 15.52 | 0.00 | 15.52 | 0.00 | 15.52 |
Annual Sum or Average | 229.67 | 15.76 | 54.00 | 15.63 | 0.50 | 15.65 | 0.00 | 15.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.50 | 19.36 | 15.83 | 19.36 | 0.33 | 25.84 | 0.00 | 25.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 128.00 | 16.92 | 18.00 | 16.71 | 0.00 | 16.71 | 0.00 | 16.71 |
February | 68.50 | 16.86 | 8.00 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 |
March | 19.17 | 16.94 | 0.83 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
April | 7.50 | 17.20 | 0.33 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.68 | 2.33 | 28.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.70 | 0.50 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.02 | 2.50 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.50 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
October | 23.33 | 17.65 | 1.33 | 17.49 | 0.00 | 17.49 | 0.00 | 17.49 |
November | 104.33 | 17.37 | 11.17 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
December | 130.67 | 16.86 | 17.00 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
Annual Sum or Average | 482.00 | 17.03 | 56.67 | 16.87 | 5.50 | 16.99 | 5.33 | 17.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.67 | 19.37 | 18.00 | 19.37 | 2.67 | 28.68 | 2.50 | 28.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 50.17 | 15.21 | 14.17 | 15.08 | 0.00 | 15.08 | 0.00 | 15.08 |
February | 30.50 | 15.90 | 3.67 | 15.80 | 0.00 | 15.80 | 0.00 | 15.80 |
March | 12.33 | 17.42 | 0.50 | 17.47 | 0.00 | 17.47 | 0.00 | 17.47 |
April | 3.50 | 18.06 | 0.17 | 17.92 | 1.33 | 20.50 | 1.33 | 21.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.13 | 3.50 | 28.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.81 | 1.00 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.56 | 2.17 | 28.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.42 | 1.83 | 28.42 |
September | 0.17 | 19.35 | 0.00 | 19.35 | 0.33 | 24.77 | 0.33 | 25.85 |
October | 9.17 | 17.10 | 0.83 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 |
November | 29.50 | 16.06 | 4.67 | 15.99 | 0.00 | 15.99 | 0.00 | 15.99 |
December | 47.00 | 15.52 | 12.17 | 15.40 | 0.00 | 15.40 | 0.00 | 15.40 |
Annual Sum or Average | 182.33 | 15.84 | 36.17 | 15.70 | 10.17 | 16.25 | 10.17 | 16.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.08 | 0.00 | 15.08 |
Maximum of Months | 50.17 | 19.35 | 14.17 | 19.35 | 3.50 | 28.56 | 3.50 | 28.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 46.67 | 15.29 | 14.00 | 15.15 | 0.00 | 15.15 | 0.00 | 15.15 |
February | 30.50 | 15.85 | 5.17 | 15.73 | 0.00 | 15.73 | 0.00 | 15.73 |
March | 12.17 | 17.46 | 0.17 | 17.49 | 0.00 | 17.49 | 0.00 | 17.49 |
April | 3.50 | 18.18 | 0.00 | 18.18 | 0.33 | 19.01 | 0.17 | 19.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.95 | 0.50 | 27.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.16 | 0.33 | 28.25 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.85 | 0.00 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.09 | 0.33 | 28.02 |
September | 0.17 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
October | 10.50 | 16.76 | 1.17 | 16.57 | 0.00 | 16.57 | 0.00 | 16.57 |
November | 23.17 | 16.36 | 4.33 | 16.20 | 0.00 | 16.20 | 0.00 | 16.20 |
December | 28.33 | 15.94 | 6.33 | 15.72 | 0.00 | 15.72 | 0.00 | 15.72 |
Annual Sum or Average | 155.00 | 16.02 | 31.17 | 15.83 | 6.50 | 16.24 | 1.33 | 16.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.15 | 0.00 | 15.15 |
Maximum of Months | 46.67 | 19.33 | 14.00 | 19.33 | 3.00 | 28.16 | 0.50 | 28.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 75.50 | 14.52 | 21.00 | 14.43 | 0.00 | 14.43 | 0.00 | 14.43 |
February | 67.17 | 14.84 | 18.00 | 14.74 | 0.00 | 14.74 | 0.00 | 14.74 |
March | 57.17 | 15.40 | 10.00 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 |
April | 27.00 | 15.67 | 5.17 | 15.49 | 0.00 | 15.49 | 0.00 | 15.49 |
May | 0.33 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.50 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
September | 4.33 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 |
October | 39.50 | 15.42 | 8.17 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
November | 74.67 | 14.95 | 20.00 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
December | 86.33 | 14.92 | 22.33 | 14.83 | 0.00 | 14.83 | 0.00 | 14.83 |
Annual Sum or Average | 432.50 | 15.04 | 104.67 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 86.33 | 19.04 | 22.33 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 78.67 | 14.50 | 21.67 | 14.42 | 0.00 | 14.42 | 0.00 | 14.42 |
February | 65.67 | 14.88 | 15.67 | 14.80 | 0.00 | 14.80 | 0.00 | 14.80 |
March | 49.67 | 15.48 | 4.17 | 15.52 | 0.00 | 15.52 | 0.00 | 15.52 |
April | 23.17 | 15.86 | 2.33 | 15.78 | 0.00 | 15.78 | 0.00 | 15.78 |
May | 0.33 | 18.76 | 0.00 | 18.76 | 2.00 | 26.76 | 2.00 | 27.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.51 | 0.33 | 27.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.39 | 1.50 | 28.39 |
August | 0.50 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
September | 4.00 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
October | 37.50 | 15.45 | 6.67 | 15.35 | 0.00 | 15.35 | 0.00 | 15.35 |
November | 75.67 | 14.92 | 20.50 | 14.85 | 0.00 | 14.85 | 0.00 | 14.85 |
December | 88.00 | 14.87 | 23.00 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 |
Annual Sum or Average | 423.17 | 15.03 | 94.00 | 14.94 | 3.83 | 15.03 | 3.83 | 15.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.42 | 0.00 | 14.42 |
Maximum of Months | 88.00 | 19.07 | 23.00 | 19.07 | 2.00 | 28.39 | 2.00 | 28.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 72.00 | 14.55 | 18.50 | 14.47 | 0.00 | 14.47 | 0.00 | 14.47 |
February | 55.33 | 15.00 | 9.67 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
March | 41.17 | 15.71 | 4.17 | 15.74 | 0.00 | 15.74 | 0.00 | 15.74 |
April | 17.17 | 16.20 | 2.50 | 15.98 | 0.00 | 15.98 | 0.00 | 15.98 |
May | 0.50 | 18.92 | 0.00 | 18.92 | 1.67 | 25.90 | 1.67 | 26.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.69 | 0.83 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.64 | 2.00 | 28.64 |
August | 0.33 | 19.02 | 0.00 | 19.02 | 1.33 | 26.65 | 1.33 | 27.50 |
September | 3.33 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
October | 32.50 | 15.61 | 4.17 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
November | 69.33 | 14.96 | 17.67 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
December | 85.17 | 14.90 | 22.17 | 14.82 | 0.00 | 14.82 | 0.00 | 14.82 |
Annual Sum or Average | 376.83 | 15.11 | 78.83 | 15.02 | 5.83 | 15.19 | 5.83 | 15.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.47 | 0.00 | 14.47 |
Maximum of Months | 85.17 | 19.02 | 22.17 | 19.02 | 2.00 | 28.64 | 2.00 | 28.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 66.67 | 14.62 | 18.00 | 14.52 | 0.00 | 14.52 | 0.00 | 14.52 |
February | 57.50 | 15.00 | 14.50 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 |
March | 40.50 | 15.68 | 5.17 | 15.69 | 0.00 | 15.69 | 0.00 | 15.69 |
April | 15.50 | 16.43 | 3.00 | 16.13 | 0.17 | 16.23 | 0.17 | 16.33 |
May | 0.50 | 18.95 | 0.00 | 18.95 | 2.17 | 25.92 | 0.17 | 26.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.39 | 0.33 | 28.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.61 | 0.00 | 27.61 |
August | 0.33 | 19.11 | 0.00 | 19.11 | 0.67 | 25.05 | 0.17 | 25.46 |
September | 3.17 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
October | 28.00 | 15.75 | 5.00 | 15.60 | 0.00 | 15.60 | 0.00 | 15.60 |
November | 60.67 | 15.07 | 18.67 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 |
December | 67.50 | 15.04 | 16.17 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
Annual Sum or Average | 340.33 | 15.20 | 80.50 | 15.09 | 4.83 | 15.24 | 0.83 | 15.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.52 | 0.00 | 14.52 |
Maximum of Months | 67.50 | 19.11 | 18.67 | 19.11 | 2.17 | 28.39 | 0.33 | 28.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 102.67 | 28.83 | 68.83 | 28.83 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 104.67 | 32.83 | 59.50 | 32.80 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 36.67 | 15.17 | 36.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 113.67 | 37.83 | 79.17 | 37.74 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 143.67 | 41.49 | 96.83 | 41.36 |
Annual Sum or Average | 0.00 | 0.00 | 501.00 | 35.91 | 319.50 | 35.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 143.67 | 41.49 | 96.83 | 41.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 28.11 | 32.00 | 28.13 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 104.50 | 31.04 | 59.33 | 31.11 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 35.11 | 15.17 | 35.02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 113.33 | 35.79 | 79.00 | 35.85 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 143.67 | 39.44 | 96.83 | 39.47 |
Annual Sum or Average | 0.00 | 0.00 | 435.00 | 35.14 | 282.33 | 35.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 143.67 | 39.44 | 96.83 | 39.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 78.17 | 29.60 | 46.00 | 29.80 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 | 32.91 | 14.50 | 32.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 113.17 | 33.82 | 78.83 | 34.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 143.50 | 37.60 | 96.83 | 37.74 |
Annual Sum or Average | 0.00 | 0.00 | 370.50 | 34.31 | 236.17 | 34.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 143.50 | 37.60 | 96.83 | 37.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.56 | 0.17 | 27.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.56 | 0.50 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 27.56 | 0.67 | 27.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.56 | 0.50 | 27.56 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.58 | 41.33 | 21.51 | 41.33 | 21.45 |
February | 454.00 | 22.05 | 22.00 | 21.99 | 22.00 | 21.94 |
March | 506.50 | 22.60 | 2.00 | 22.60 | 2.00 | 22.59 |
April | 402.00 | 23.61 | 22.67 | 23.75 | 0.00 | 23.75 |
May | 292.33 | 23.61 | 55.83 | 24.00 | 0.00 | 24.00 |
June | 14.33 | 23.73 | 168.17 | 25.02 | 0.00 | 25.02 |
July | 0.00 | 0.00 | 365.33 | 24.77 | 0.00 | 24.77 |
August | 32.17 | 23.72 | 246.50 | 24.75 | 0.00 | 24.75 |
September | 236.00 | 23.52 | 84.33 | 24.23 | 0.00 | 24.23 |
October | 322.33 | 23.39 | 38.83 | 23.69 | 0.00 | 23.69 |
November | 489.00 | 22.36 | 1.50 | 22.35 | 1.50 | 22.34 |
December | 493.67 | 21.91 | 3.67 | 21.89 | 3.67 | 21.88 |
Annual Sum or Average | 3744.33 | 22.60 | 1052.17 | 23.09 | 70.50 | 23.06 |
Minimum of Months | 0.00 | 0.00 | 1.50 | 21.51 | 0.00 | 21.45 |
Maximum of Months | 506.50 | 23.73 | 365.33 | 25.02 | 41.33 | 25.02 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.44 | 66.17 | 22.23 | 66.17 | 22.06 |
February | 450.50 | 22.98 | 14.50 | 22.91 | 14.50 | 22.85 |
March | 474.17 | 23.52 | 0.00 | 23.52 | 0.00 | 23.52 |
April | 250.00 | 23.85 | 20.00 | 24.01 | 0.00 | 24.01 |
May | 131.83 | 23.84 | 33.67 | 24.25 | 0.00 | 24.25 |
June | 7.33 | 23.82 | 198.17 | 24.58 | 0.00 | 24.58 |
July | 0.00 | 0.00 | 425.00 | 24.37 | 0.00 | 24.37 |
August | 10.50 | 23.96 | 330.67 | 24.44 | 0.00 | 24.44 |
September | 119.17 | 23.69 | 65.67 | 24.34 | 0.00 | 24.34 |
October | 304.17 | 23.65 | 17.33 | 23.74 | 0.00 | 23.74 |
November | 489.00 | 23.54 | 0.00 | 23.54 | 0.00 | 23.54 |
December | 497.00 | 23.33 | 1.67 | 23.32 | 1.67 | 23.31 |
Annual Sum or Average | 3235.67 | 23.31 | 1172.83 | 23.58 | 82.33 | 23.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.23 | 0.00 | 22.06 |
Maximum of Months | 502.00 | 23.96 | 425.00 | 24.58 | 66.17 | 24.58 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.56 | 170.50 | 21.19 | 170.50 | 20.96 |
February | 454.00 | 22.06 | 111.50 | 21.72 | 111.50 | 21.48 |
March | 510.67 | 22.81 | 50.50 | 22.65 | 50.50 | 22.52 |
April | 429.00 | 23.31 | 15.33 | 23.23 | 15.33 | 23.15 |
May | 249.83 | 23.68 | 2.83 | 23.70 | 0.00 | 23.70 |
June | 49.17 | 23.63 | 140.67 | 24.31 | 0.00 | 24.31 |
July | 18.33 | 23.47 | 275.50 | 24.36 | 0.00 | 24.36 |
August | 72.67 | 23.55 | 192.00 | 24.20 | 0.00 | 24.20 |
September | 273.00 | 23.50 | 9.50 | 23.55 | 0.00 | 23.55 |
October | 472.50 | 22.90 | 34.00 | 22.75 | 34.00 | 22.61 |
November | 489.00 | 21.91 | 148.67 | 21.57 | 148.67 | 21.36 |
December | 497.00 | 21.68 | 184.83 | 21.35 | 184.83 | 21.17 |
Annual Sum or Average | 4017.17 | 22.51 | 1335.83 | 22.46 | 715.33 | 22.22 |
Minimum of Months | 18.33 | 21.56 | 2.83 | 21.19 | 0.00 | 20.96 |
Maximum of Months | 510.67 | 23.68 | 275.50 | 24.36 | 184.83 | 24.36 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.18 | 475.50 | 20.15 | 475.50 | 20.14 |
February | 454.00 | 20.37 | 357.33 | 20.23 | 357.33 | 20.17 |
March | 514.00 | 20.95 | 309.33 | 20.73 | 309.33 | 20.63 |
April | 479.00 | 21.81 | 144.00 | 21.44 | 144.00 | 21.21 |
May | 394.33 | 22.77 | 8.67 | 22.72 | 8.67 | 22.68 |
June | 184.17 | 23.14 | 92.00 | 23.51 | 0.00 | 23.51 |
July | 142.50 | 22.99 | 202.50 | 23.74 | 0.00 | 23.74 |
August | 254.67 | 22.89 | 109.50 | 23.27 | 1.33 | 23.27 |
September | 467.17 | 22.06 | 42.50 | 21.94 | 42.50 | 21.84 |
October | 502.00 | 20.87 | 253.50 | 20.58 | 253.50 | 20.43 |
November | 489.00 | 20.23 | 448.67 | 20.18 | 448.67 | 20.16 |
December | 497.00 | 20.14 | 489.67 | 20.13 | 489.67 | 20.13 |
Annual Sum or Average | 4879.83 | 21.23 | 2933.17 | 21.04 | 2530.50 | 20.82 |
Minimum of Months | 142.50 | 20.14 | 8.67 | 20.13 | 0.00 | 20.13 |
Maximum of Months | 514.00 | 23.14 | 489.67 | 23.74 | 489.67 | 23.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.07 | 502.00 | 20.07 | 502.00 | 20.07 |
February | 454.00 | 20.21 | 418.17 | 20.18 | 418.17 | 20.16 |
March | 514.00 | 20.83 | 359.67 | 20.72 | 359.67 | 20.67 |
April | 472.33 | 22.12 | 86.33 | 21.86 | 86.33 | 21.68 |
May | 334.17 | 23.16 | 0.17 | 23.16 | 0.00 | 23.16 |
June | 44.00 | 23.39 | 216.17 | 24.11 | 0.00 | 24.11 |
July | 18.67 | 23.16 | 398.67 | 24.20 | 0.00 | 24.20 |
August | 143.00 | 23.03 | 204.83 | 23.72 | 0.00 | 23.72 |
September | 443.33 | 22.32 | 9.33 | 22.31 | 7.50 | 22.28 |
October | 502.00 | 21.21 | 198.00 | 21.01 | 198.00 | 20.90 |
November | 489.00 | 20.34 | 485.50 | 20.34 | 485.50 | 20.34 |
December | 497.00 | 20.30 | 497.00 | 20.30 | 497.00 | 20.30 |
Annual Sum or Average | 4413.50 | 21.18 | 3375.83 | 21.21 | 2554.17 | 20.99 |
Minimum of Months | 18.67 | 20.07 | 0.17 | 20.07 | 0.00 | 20.07 |
Maximum of Months | 514.00 | 23.39 | 502.00 | 24.20 | 502.00 | 24.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.01 | 502.00 | 20.01 | 502.00 | 20.01 |
February | 454.00 | 20.28 | 403.00 | 20.23 | 403.00 | 20.21 |
March | 495.33 | 21.05 | 259.33 | 20.86 | 258.33 | 20.77 |
April | 387.00 | 21.87 | 98.83 | 21.88 | 67.50 | 21.72 |
May | 240.17 | 22.74 | 139.67 | 23.38 | 8.33 | 23.46 |
June | 123.67 | 22.89 | 255.67 | 23.76 | 2.50 | 23.78 |
July | 103.00 | 23.00 | 324.67 | 23.95 | 10.50 | 24.02 |
August | 196.17 | 22.56 | 220.17 | 23.38 | 0.83 | 23.38 |
September | 395.00 | 21.95 | 54.67 | 22.25 | 8.83 | 22.24 |
October | 496.33 | 21.18 | 186.33 | 21.01 | 184.67 | 20.90 |
November | 489.00 | 20.22 | 489.00 | 20.22 | 489.00 | 20.22 |
December | 497.00 | 20.14 | 497.00 | 20.14 | 497.00 | 20.14 |
Annual Sum or Average | 4378.67 | 21.08 | 3430.33 | 21.23 | 2432.50 | 21.01 |
Minimum of Months | 103.00 | 20.01 | 54.67 | 20.01 | 0.83 | 20.01 |
Maximum of Months | 502.00 | 23.00 | 502.00 | 23.95 | 502.00 | 24.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.00 | 489.00 | 19.99 | 489.00 | 19.98 |
February | 444.33 | 20.57 | 341.83 | 20.42 | 341.83 | 20.36 |
March | 430.17 | 21.02 | 274.00 | 20.98 | 244.83 | 20.86 |
April | 308.33 | 21.78 | 175.50 | 22.17 | 71.17 | 21.98 |
May | 283.67 | 22.35 | 141.33 | 23.02 | 7.67 | 23.07 |
June | 173.67 | 22.61 | 225.00 | 23.50 | 4.00 | 23.54 |
July | 141.50 | 22.65 | 295.33 | 23.76 | 8.83 | 23.82 |
August | 210.00 | 22.48 | 228.50 | 23.41 | 6.33 | 23.45 |
September | 353.83 | 21.84 | 100.33 | 22.29 | 15.00 | 22.25 |
October | 466.83 | 21.11 | 211.50 | 20.99 | 197.00 | 20.87 |
November | 487.00 | 20.27 | 448.00 | 20.22 | 448.00 | 20.20 |
December | 497.00 | 20.06 | 497.00 | 20.06 | 497.00 | 20.06 |
Annual Sum or Average | 4298.33 | 21.07 | 3427.33 | 21.28 | 2330.67 | 21.04 |
Minimum of Months | 141.50 | 20.00 | 100.33 | 19.99 | 4.00 | 19.98 |
Maximum of Months | 502.00 | 22.65 | 497.00 | 23.76 | 497.00 | 23.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.33 | 487.50 | 20.32 | 487.50 | 20.31 |
February | 454.00 | 20.59 | 335.33 | 20.51 | 335.33 | 20.48 |
March | 495.00 | 21.25 | 187.17 | 21.14 | 186.50 | 21.07 |
April | 291.50 | 22.32 | 108.00 | 22.83 | 15.00 | 22.79 |
May | 270.17 | 22.62 | 102.83 | 23.16 | 3.33 | 23.19 |
June | 96.33 | 22.81 | 309.33 | 24.06 | 4.00 | 24.09 |
July | 40.17 | 23.49 | 408.83 | 24.32 | 8.83 | 24.36 |
August | 85.17 | 23.04 | 360.17 | 24.17 | 7.17 | 24.21 |
September | 389.83 | 22.09 | 50.33 | 22.38 | 0.17 | 22.38 |
October | 495.83 | 21.36 | 116.50 | 21.24 | 114.67 | 21.14 |
November | 489.00 | 20.87 | 362.33 | 20.83 | 362.33 | 20.82 |
December | 497.00 | 20.88 | 389.83 | 20.84 | 389.83 | 20.82 |
Annual Sum or Average | 4106.00 | 21.33 | 3218.17 | 21.71 | 1914.67 | 21.49 |
Minimum of Months | 40.17 | 20.33 | 50.33 | 20.32 | 0.17 | 20.31 |
Maximum of Months | 502.00 | 23.49 | 487.50 | 24.32 | 487.50 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 502.00 | 19.83 | 502.00 | 19.83 |
February | 454.00 | 19.92 | 451.00 | 19.91 | 451.00 | 19.91 |
March | 514.00 | 20.27 | 470.50 | 20.24 | 470.50 | 20.22 |
April | 485.00 | 20.85 | 237.50 | 20.62 | 237.50 | 20.50 |
May | 477.50 | 22.34 | 7.83 | 22.31 | 7.83 | 22.28 |
June | 182.50 | 22.90 | 117.00 | 23.37 | 0.00 | 23.37 |
July | 154.50 | 22.78 | 202.17 | 23.54 | 0.00 | 23.54 |
August | 376.17 | 22.33 | 57.83 | 22.53 | 5.83 | 22.51 |
September | 485.00 | 21.32 | 91.50 | 21.22 | 91.50 | 21.14 |
October | 502.00 | 20.35 | 381.67 | 20.24 | 381.67 | 20.20 |
November | 489.00 | 19.84 | 489.00 | 19.84 | 489.00 | 19.84 |
December | 497.00 | 19.78 | 497.00 | 19.78 | 497.00 | 19.78 |
Annual Sum or Average | 5118.67 | 20.78 | 3505.00 | 20.63 | 3133.83 | 20.46 |
Minimum of Months | 154.50 | 19.78 | 7.83 | 19.78 | 0.00 | 19.78 |
Maximum of Months | 514.00 | 22.90 | 502.00 | 23.54 | 502.00 | 23.54 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.59 | 427.00 | 19.59 | 427.00 | 19.59 |
February | 385.00 | 19.77 | 378.00 | 19.76 | 378.00 | 19.75 |
March | 430.33 | 20.50 | 314.33 | 20.34 | 314.33 | 20.28 |
April | 366.33 | 21.27 | 149.67 | 21.08 | 135.00 | 20.89 |
May | 256.83 | 22.42 | 96.33 | 23.00 | 10.17 | 23.08 |
June | 156.33 | 22.67 | 181.00 | 23.49 | 2.00 | 23.51 |
July | 134.33 | 22.79 | 232.33 | 23.79 | 13.17 | 23.87 |
August | 235.33 | 22.24 | 129.67 | 22.94 | 2.67 | 22.93 |
September | 362.17 | 21.51 | 66.17 | 21.61 | 44.67 | 21.53 |
October | 426.00 | 20.40 | 298.67 | 20.25 | 298.67 | 20.18 |
November | 417.00 | 19.61 | 417.00 | 19.61 | 417.00 | 19.61 |
December | 422.00 | 19.51 | 422.00 | 19.51 | 422.00 | 19.51 |
Annual Sum or Average | 4018.67 | 20.67 | 3112.17 | 20.72 | 2464.67 | 20.49 |
Minimum of Months | 134.33 | 19.51 | 66.17 | 19.51 | 2.00 | 19.51 |
Maximum of Months | 430.33 | 22.79 | 427.00 | 23.79 | 427.00 | 23.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.87 | 495.50 | 19.86 | 495.50 | 19.85 |
February | 447.50 | 20.31 | 369.83 | 20.17 | 369.83 | 20.12 |
March | 431.33 | 20.75 | 308.83 | 20.71 | 278.00 | 20.58 |
April | 320.00 | 21.37 | 218.33 | 21.72 | 116.33 | 21.48 |
May | 304.67 | 22.15 | 147.33 | 22.83 | 16.33 | 22.88 |
June | 221.17 | 22.37 | 206.00 | 23.24 | 4.17 | 23.28 |
July | 190.67 | 22.33 | 250.67 | 23.46 | 8.83 | 23.53 |
August | 271.50 | 22.17 | 202.67 | 23.06 | 10.50 | 23.10 |
September | 364.67 | 21.57 | 120.17 | 21.99 | 36.67 | 21.91 |
October | 475.83 | 20.74 | 287.83 | 20.60 | 275.50 | 20.49 |
November | 489.00 | 19.94 | 469.67 | 19.91 | 469.67 | 19.89 |
December | 497.00 | 19.79 | 497.00 | 19.79 | 497.00 | 19.79 |
Annual Sum or Average | 4515.33 | 20.85 | 3573.83 | 21.02 | 2578.33 | 20.79 |
Minimum of Months | 190.67 | 19.79 | 120.17 | 19.79 | 4.17 | 19.79 |
Maximum of Months | 502.00 | 22.37 | 497.00 | 23.46 | 497.00 | 23.53 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.87 | 502.00 | 19.87 | 502.00 | 19.87 |
February | 454.00 | 19.99 | 438.33 | 19.97 | 438.33 | 19.97 |
March | 514.00 | 20.49 | 407.83 | 20.39 | 407.83 | 20.35 |
April | 414.00 | 21.21 | 189.83 | 21.15 | 151.50 | 20.96 |
May | 389.33 | 22.05 | 63.33 | 22.32 | 8.17 | 22.30 |
June | 225.83 | 22.39 | 184.17 | 23.28 | 2.50 | 23.30 |
July | 203.67 | 22.24 | 220.67 | 23.32 | 1.00 | 23.33 |
August | 324.83 | 22.06 | 133.17 | 22.68 | 4.83 | 22.68 |
September | 457.67 | 21.41 | 70.00 | 21.43 | 54.00 | 21.37 |
October | 502.00 | 20.46 | 351.33 | 20.34 | 351.33 | 20.29 |
November | 489.00 | 19.90 | 488.83 | 19.90 | 488.83 | 19.90 |
December | 497.00 | 19.86 | 497.00 | 19.86 | 497.00 | 19.86 |
Annual Sum or Average | 4973.33 | 20.79 | 3546.50 | 20.79 | 2907.33 | 20.60 |
Minimum of Months | 203.67 | 19.86 | 63.33 | 19.86 | 1.00 | 19.86 |
Maximum of Months | 514.00 | 22.39 | 502.00 | 23.32 | 502.00 | 23.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.70 | 502.00 | 19.70 | 502.00 | 19.70 |
February | 454.00 | 19.78 | 454.00 | 19.78 | 454.00 | 19.78 |
March | 514.00 | 20.06 | 500.17 | 20.05 | 500.17 | 20.05 |
April | 485.00 | 20.37 | 314.50 | 20.20 | 314.50 | 20.13 |
May | 502.67 | 21.46 | 73.67 | 21.31 | 73.67 | 21.20 |
June | 319.00 | 22.36 | 70.50 | 22.59 | 6.17 | 22.55 |
July | 299.00 | 22.26 | 96.00 | 22.69 | 0.00 | 22.69 |
August | 461.50 | 21.72 | 45.00 | 21.73 | 27.33 | 21.67 |
September | 485.00 | 20.68 | 231.67 | 20.55 | 231.67 | 20.48 |
October | 502.00 | 19.91 | 464.67 | 19.87 | 464.67 | 19.85 |
November | 489.00 | 19.71 | 489.00 | 19.71 | 489.00 | 19.71 |
December | 497.00 | 19.66 | 497.00 | 19.66 | 497.00 | 19.66 |
Annual Sum or Average | 5510.17 | 20.52 | 3738.17 | 20.33 | 3560.17 | 20.20 |
Minimum of Months | 299.00 | 19.66 | 45.00 | 19.66 | 0.00 | 19.66 |
Maximum of Months | 514.00 | 22.36 | 502.00 | 22.69 | 502.00 | 22.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.70 | 502.00 | 19.70 | 502.00 | 19.70 |
February | 454.00 | 19.79 | 452.50 | 19.79 | 452.50 | 19.79 |
March | 514.00 | 20.22 | 432.83 | 20.11 | 432.83 | 20.07 |
April | 448.50 | 20.96 | 220.67 | 20.68 | 212.33 | 20.51 |
May | 315.83 | 22.08 | 127.50 | 22.49 | 31.17 | 22.42 |
June | 176.17 | 22.36 | 240.67 | 23.32 | 6.50 | 23.28 |
July | 168.67 | 22.49 | 280.00 | 23.58 | 9.50 | 23.64 |
August | 309.83 | 22.03 | 160.33 | 22.66 | 11.33 | 22.61 |
September | 464.33 | 21.13 | 145.67 | 20.95 | 141.33 | 20.82 |
October | 502.00 | 19.99 | 419.50 | 19.89 | 419.50 | 19.85 |
November | 489.00 | 19.70 | 489.00 | 19.70 | 489.00 | 19.70 |
December | 497.00 | 19.66 | 497.00 | 19.66 | 497.00 | 19.66 |
Annual Sum or Average | 4841.33 | 20.54 | 3967.67 | 20.60 | 3205.00 | 20.39 |
Minimum of Months | 168.67 | 19.66 | 127.50 | 19.66 | 6.50 | 19.66 |
Maximum of Months | 514.00 | 22.49 | 502.00 | 23.58 | 502.00 | 23.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.72 | 501.67 | 19.72 | 501.67 | 19.72 |
February | 451.33 | 19.97 | 414.33 | 19.89 | 414.33 | 19.87 |
March | 460.50 | 20.46 | 362.50 | 20.33 | 347.33 | 20.24 |
April | 354.33 | 21.02 | 265.83 | 21.20 | 181.00 | 20.95 |
May | 331.33 | 21.71 | 192.17 | 22.20 | 71.17 | 22.05 |
June | 241.83 | 22.06 | 206.00 | 22.97 | 9.83 | 22.96 |
July | 217.17 | 22.05 | 230.00 | 23.19 | 7.50 | 23.25 |
August | 296.83 | 21.84 | 193.17 | 22.68 | 20.67 | 22.66 |
September | 398.50 | 21.10 | 203.50 | 21.25 | 142.33 | 21.07 |
October | 485.00 | 20.18 | 387.83 | 20.07 | 379.50 | 20.00 |
November | 489.00 | 19.76 | 483.50 | 19.74 | 483.50 | 19.74 |
December | 497.00 | 19.67 | 497.00 | 19.67 | 497.00 | 19.67 |
Annual Sum or Average | 4724.83 | 20.57 | 3937.50 | 20.70 | 3055.83 | 20.49 |
Minimum of Months | 217.17 | 19.67 | 192.17 | 19.67 | 7.50 | 19.67 |
Maximum of Months | 502.00 | 22.06 | 501.67 | 23.19 | 501.67 | 23.25 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.74 | 502.00 | 19.74 | 502.00 | 19.74 |
February | 454.00 | 19.84 | 450.83 | 19.84 | 450.83 | 19.84 |
March | 514.00 | 20.23 | 448.17 | 20.16 | 448.17 | 20.13 |
April | 425.17 | 20.87 | 256.00 | 20.77 | 221.33 | 20.59 |
May | 409.67 | 21.70 | 104.50 | 21.85 | 52.17 | 21.73 |
June | 247.83 | 22.08 | 183.33 | 23.01 | 7.00 | 23.00 |
July | 236.83 | 22.02 | 196.83 | 23.04 | 1.83 | 23.05 |
August | 348.50 | 21.77 | 127.33 | 22.33 | 14.33 | 22.29 |
September | 462.17 | 21.00 | 172.83 | 20.92 | 161.17 | 20.82 |
October | 502.00 | 20.06 | 430.83 | 19.98 | 430.83 | 19.95 |
November | 489.00 | 19.77 | 489.00 | 19.77 | 489.00 | 19.77 |
December | 497.00 | 19.72 | 497.00 | 19.72 | 497.00 | 19.72 |
Annual Sum or Average | 5088.17 | 20.56 | 3858.67 | 20.56 | 3275.67 | 20.38 |
Minimum of Months | 236.83 | 19.72 | 104.50 | 19.72 | 1.83 | 19.72 |
Maximum of Months | 514.00 | 22.08 | 502.00 | 23.04 | 502.00 | 23.05 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 27.00 | 252.17 | 27.44 | 0.00 | 27.44 |
February | 57.50 | 32.84 | 329.83 | 28.75 | 57.50 | 29.28 |
March | 15.17 | 36.07 | 463.33 | 27.58 | 15.17 | 27.84 |
April | 22.17 | 27.00 | 485.00 | 27.00 | 22.17 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 94.17 | 27.00 | 496.00 | 27.00 | 94.17 | 27.00 |
July | 240.33 | 27.00 | 497.00 | 27.00 | 240.33 | 27.00 |
August | 259.33 | 27.00 | 514.00 | 27.00 | 259.33 | 27.00 |
September | 2.00 | 27.00 | 485.00 | 27.00 | 2.00 | 27.00 |
October | 0.00 | 0.00 | 458.50 | 27.00 | 0.00 | 27.00 |
November | 79.67 | 37.54 | 447.67 | 30.18 | 79.67 | 31.15 |
December | 99.33 | 40.82 | 433.50 | 32.15 | 99.33 | 33.51 |
Annual Sum or Average | 873.67 | 30.07 | 5370.00 | 27.88 | 869.67 | 28.15 |
Minimum of Months | 0.00 | 0.00 | 252.17 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 259.33 | 40.82 | 514.00 | 32.15 | 259.33 | 33.51 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 89.33 | 25.90 | 83.17 | 26.63 | 0.00 | 26.63 |
February | 72.33 | 29.42 | 211.67 | 28.49 | 36.33 | 28.87 |
March | 25.67 | 31.53 | 312.00 | 27.70 | 14.17 | 28.00 |
April | 8.33 | 27.00 | 422.00 | 27.00 | 8.33 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 25.33 | 27.00 | 496.00 | 27.00 | 25.33 | 27.00 |
July | 60.17 | 27.00 | 497.00 | 27.00 | 60.17 | 27.00 |
August | 44.17 | 27.00 | 514.00 | 27.00 | 44.17 | 27.00 |
September | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
October | 20.50 | 27.00 | 342.17 | 27.00 | 0.00 | 27.00 |
November | 138.50 | 32.05 | 201.17 | 31.14 | 77.67 | 32.04 |
December | 158.17 | 34.67 | 193.00 | 33.91 | 97.00 | 35.12 |
Annual Sum or Average | 642.50 | 30.28 | 4265.17 | 27.90 | 363.17 | 28.26 |
Minimum of Months | 0.00 | 0.00 | 83.17 | 26.63 | 0.00 | 26.63 |
Maximum of Months | 158.17 | 34.67 | 514.00 | 33.91 | 97.00 | 35.12 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 265.83 | 25.26 | 55.00 | 24.86 | 55.00 | 24.57 |
February | 117.67 | 27.35 | 101.17 | 27.82 | 8.50 | 27.95 |
March | 80.00 | 27.98 | 180.33 | 27.64 | 12.00 | 27.90 |
April | 38.83 | 27.00 | 322.17 | 27.00 | 6.00 | 27.00 |
May | 0.00 | 0.00 | 486.83 | 27.00 | 0.00 | 27.00 |
June | 48.50 | 27.00 | 496.00 | 27.00 | 48.50 | 27.00 |
July | 83.67 | 27.00 | 497.00 | 27.00 | 83.67 | 27.00 |
August | 52.67 | 27.00 | 511.83 | 27.00 | 52.67 | 27.00 |
September | 0.83 | 26.60 | 415.33 | 27.00 | 0.00 | 27.00 |
October | 73.00 | 27.00 | 193.67 | 27.00 | 0.00 | 27.00 |
November | 194.83 | 29.86 | 99.17 | 30.84 | 74.00 | 31.58 |
December | 221.00 | 31.77 | 110.50 | 33.38 | 95.50 | 34.42 |
Annual Sum or Average | 1176.83 | 28.08 | 3469.00 | 27.63 | 435.83 | 27.87 |
Minimum of Months | 0.00 | 0.00 | 55.00 | 24.86 | 0.00 | 24.57 |
Maximum of Months | 265.83 | 31.77 | 511.83 | 33.38 | 95.50 | 34.42 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 27.19 | 502.00 | 27.12 | 6.50 | 27.12 |
February | 0.17 | 21.01 | 447.50 | 24.39 | 0.00 | 24.39 |
March | 84.00 | 25.76 | 513.50 | 25.11 | 83.83 | 25.19 |
April | 339.67 | 25.65 | 485.00 | 25.30 | 339.67 | 25.40 |
May | 468.33 | 27.19 | 508.00 | 27.19 | 468.33 | 27.19 |
June | 127.17 | 27.00 | 492.50 | 25.59 | 126.50 | 25.84 |
July | 469.17 | 26.37 | 496.33 | 26.28 | 469.17 | 26.31 |
August | 417.33 | 26.14 | 514.00 | 25.81 | 417.33 | 25.91 |
September | 485.00 | 27.09 | 485.00 | 27.09 | 485.00 | 27.09 |
October | 0.00 | 0.00 | 502.00 | 24.53 | 0.00 | 24.53 |
November | 453.83 | 25.75 | 489.00 | 25.71 | 453.83 | 25.73 |
December | 465.33 | 26.13 | 497.00 | 26.05 | 465.33 | 26.08 |
Annual Sum or Average | 3316.50 | 26.38 | 5931.83 | 25.98 | 3315.50 | 26.09 |
Minimum of Months | 0.00 | 0.00 | 447.50 | 24.39 | 0.00 | 24.39 |
Maximum of Months | 485.00 | 27.19 | 514.00 | 27.19 | 485.00 | 27.19 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.25404 | 10.90591 | 0.56448 | 12.04758 |
February | 454.00000 | 27.75508 | 11.11277 | 0.70836 | 17.41597 |
March | 514.00000 | 27.26769 | 11.81253 | 0.71173 | 16.51627 |
April | 485.00000 | 27.00000 | 15.31012 | 0.82300 | 19.53071 |
May | 508.00000 | 27.00000 | 22.80039 | 0.15965 | 5.71723 |
June | 496.00000 | 27.00001 | 31.70118 | 0.30997 | 7.20596 |
July | 497.00000 | 27.00000 | 37.42194 | 0.40911 | 8.59278 |
August | 514.00000 | 27.00006 | 34.21314 | 0.40633 | 8.59851 |
September | 485.00000 | 27.00000 | 26.59301 | 0.13177 | 5.59080 |
October | 502.00000 | 27.00000 | 17.15828 | 0.69621 | 15.38644 |
November | 489.00000 | 28.71746 | 9.44389 | 0.92869 | 26.04734 |
December | 497.00000 | 29.76276 | 8.70464 | 1.12448 | 29.94462 |
Annual Sum or Average | 5943.00000 | 27.47466 | 19.84907 | 0.57940 | 14.32617 |
Minimum of Months | 454.00000 | 27.00000 | 8.70464 | 0.13177 | 5.59080 |
Maximum of Months | 514.00000 | 29.76276 | 37.42194 | 1.12448 | 29.94462 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.88353 | 10.84827 | 0.41299 | 9.33897 |
February | 454.00000 | 27.55466 | 11.08838 | 0.58638 | 13.46970 |
March | 514.00000 | 27.23046 | 11.81113 | 0.60640 | 13.68347 |
April | 485.00000 | 27.00000 | 15.30974 | 0.69146 | 15.46232 |
May | 508.00000 | 27.00000 | 22.78142 | 0.06918 | 5.35980 |
June | 496.00000 | 27.00001 | 31.69494 | 0.23271 | 6.40393 |
July | 497.00000 | 27.00001 | 37.42521 | 0.29129 | 6.93870 |
August | 514.00000 | 27.00007 | 34.24626 | 0.25332 | 6.59343 |
September | 485.00000 | 27.00000 | 26.57762 | 0.01863 | 5.28579 |
October | 502.00000 | 27.00000 | 17.15304 | 0.59222 | 12.63034 |
November | 489.00000 | 28.44224 | 9.51898 | 0.73797 | 21.18257 |
December | 497.00000 | 29.44061 | 8.79441 | 0.91698 | 26.36690 |
Annual Sum or Average | 5943.00000 | 27.37525 | 19.85516 | 0.44911 | 11.85248 |
Minimum of Months | 454.00000 | 26.88353 | 8.79441 | 0.01863 | 5.28579 |
Maximum of Months | 514.00000 | 29.44061 | 37.42521 | 0.91698 | 26.36690 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.07048 | 10.91790 | 0.18037 | 8.18980 |
February | 454.00000 | 27.32414 | 11.06816 | 0.45521 | 10.26842 |
March | 514.00000 | 27.17198 | 11.80657 | 0.50539 | 11.15544 |
April | 485.00000 | 27.00000 | 15.30987 | 0.61452 | 13.57225 |
May | 508.00000 | 27.00126 | 22.78714 | 0.00312 | 5.54880 |
June | 496.00000 | 27.00001 | 31.70173 | 0.20940 | 6.39735 |
July | 497.00000 | 27.00001 | 37.43345 | 0.26495 | 6.80805 |
August | 514.00000 | 27.00007 | 34.30887 | 0.20342 | 6.36107 |
September | 485.00000 | 26.99984 | 26.58287 | -0.1009 | 5.71663 |
October | 502.00000 | 27.00008 | 17.15486 | 0.49305 | 10.45166 |
November | 489.00000 | 28.17286 | 9.55323 | 0.59780 | 17.06009 |
December | 497.00000 | 29.13221 | 8.89450 | 0.77220 | 23.94396 |
Annual Sum or Average | 5943.00000 | 27.23605 | 19.87805 | 0.34854 | 10.43185 |
Minimum of Months | 454.00000 | 26.07048 | 8.89450 | -0.1009 | 5.54880 |
Maximum of Months | 514.00000 | 29.13221 | 37.43345 | 0.77220 | 23.94396 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.12306 | 29.97589 | 0.94130 | 23.78628 |
February | 454.00000 | 24.38426 | 28.87157 | 0.56781 | 11.84386 |
March | 514.00000 | 25.00245 | 27.14785 | 0.77786 | 18.35330 |
April | 485.00000 | 25.06464 | 24.29858 | 1.03770 | 28.31077 |
May | 508.00000 | 27.18471 | 29.73840 | 0.50771 | 10.48541 |
June | 496.00000 | 25.20230 | 33.63052 | 0.20985 | 7.93114 |
July | 497.00000 | 26.19694 | 36.69889 | 0.70524 | 16.88281 |
August | 514.00000 | 25.53772 | 34.57852 | 0.69927 | 18.53239 |
September | 485.00000 | 27.08538 | 30.01141 | 0.52644 | 10.84702 |
October | 502.00000 | 24.52679 | 28.93519 | 0.69367 | 15.19697 |
November | 489.00000 | 25.67884 | 27.04303 | 1.06108 | 28.83894 |
December | 497.00000 | 25.97508 | 26.32739 | 1.20719 | 35.83305 |
Annual Sum or Average | 5943.00000 | 25.75563 | 29.79719 | 0.74503 | 18.92309 |
Minimum of Months | 454.00000 | 24.38426 | 24.29858 | 0.20985 | 7.93114 |
Maximum of Months | 514.00000 | 27.18471 | 36.69889 | 1.20719 | 35.83305 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.58135 | 11.00008 | -0.4010 | 8.78580 |
February | 454.00000 | 22.05311 | 11.63813 | -0.2873 | 7.57661 |
March | 514.00000 | 22.64338 | 12.32964 | -0.1339 | 6.42501 |
April | 485.00000 | 23.95446 | 14.83507 | 0.18525 | 6.28947 |
May | 508.00000 | 24.12117 | 21.42533 | -0.6062 | 13.43200 |
June | 496.00000 | 24.33239 | 33.09461 | -0.4398 | 9.73214 |
July | 497.00000 | 24.54955 | 41.70935 | -0.3004 | 8.09774 |
August | 514.00000 | 24.34279 | 36.89721 | -0.3862 | 9.22466 |
September | 485.00000 | 24.12494 | 26.84233 | -0.5539 | 12.68495 |
October | 502.00000 | 23.88975 | 17.89800 | 0.19887 | 6.77489 |
November | 489.00000 | 22.35652 | 9.58925 | -0.2010 | 6.67718 |
December | 497.00000 | 21.92575 | 8.98497 | -0.3078 | 7.81299 |
Annual Sum or Average | 5943.00000 | 23.33182 | 20.61079 | -0.2700 | 8.63556 |
Minimum of Months | 454.00000 | 21.58135 | 8.98497 | -0.6062 | 6.28947 |
Maximum of Months | 514.00000 | 24.54955 | 41.70935 | 0.19887 | 13.43200 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.44392 | 11.59270 | -0.2465 | 7.59763 |
February | 454.00000 | 22.98601 | 12.90879 | -0.1018 | 6.26466 |
March | 514.00000 | 23.57976 | 13.42394 | 0.05995 | 5.67388 |
April | 485.00000 | 24.13558 | 14.90235 | 0.23986 | 6.55768 |
May | 508.00000 | 24.16949 | 21.39697 | -0.5662 | 12.07275 |
June | 496.00000 | 24.25303 | 34.19163 | -0.4248 | 9.19527 |
July | 497.00000 | 24.31398 | 42.77191 | -0.3326 | 7.79211 |
August | 514.00000 | 24.29708 | 37.50731 | -0.3740 | 8.44964 |
September | 485.00000 | 24.20276 | 27.27916 | -0.5382 | 11.72896 |
October | 502.00000 | 23.95839 | 19.20106 | 0.19948 | 6.33933 |
November | 489.00000 | 23.53519 | 11.34899 | 0.02004 | 5.46078 |
December | 497.00000 | 23.32690 | 10.82305 | -0.0357 | 5.65534 |
Annual Sum or Average | 5943.00000 | 23.77187 | 21.53303 | -0.1763 | 7.74298 |
Minimum of Months | 454.00000 | 22.44392 | 10.82305 | -0.5662 | 5.46078 |
Maximum of Months | 514.00000 | 24.31398 | 42.77191 | 0.23986 | 12.07275 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.56013 | 11.62638 | -0.4729 | 12.29523 |
February | 454.00000 | 22.06142 | 12.73189 | -0.3350 | 9.69957 |
March | 514.00000 | 22.81965 | 13.50916 | -0.1407 | 6.78114 |
April | 485.00000 | 23.42349 | 16.07085 | 0.04345 | 6.15859 |
May | 508.00000 | 23.95641 | 22.02446 | -0.6634 | 14.71494 |
June | 496.00000 | 24.13893 | 34.61484 | -0.4919 | 10.40303 |
July | 497.00000 | 24.18056 | 43.63174 | -0.4202 | 9.11564 |
August | 514.00000 | 24.09897 | 38.40743 | -0.4912 | 10.55381 |
September | 485.00000 | 23.81319 | 28.51611 | -0.6970 | 15.98641 |
October | 502.00000 | 22.97377 | 20.04488 | -0.0590 | 6.64576 |
November | 489.00000 | 21.91210 | 10.72200 | -0.3872 | 10.01468 |
December | 497.00000 | 21.67829 | 10.35197 | -0.4481 | 10.92668 |
Annual Sum or Average | 5943.00000 | 23.06032 | 21.94504 | -0.3807 | 10.27356 |
Minimum of Months | 454.00000 | 21.56013 | 10.35197 | -0.6970 | 6.15859 |
Maximum of Months | 514.00000 | 24.18056 | 43.63174 | 0.04345 | 15.98641 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.18198 | 12.43691 | -0.8668 | 23.40660 |
February | 454.00000 | 20.36707 | 13.95386 | -0.7922 | 21.23796 |
March | 514.00000 | 20.95022 | 14.44671 | -0.6234 | 15.46125 |
April | 485.00000 | 21.83798 | 17.08518 | -0.3539 | 10.83641 |
May | 508.00000 | 23.05228 | 23.32566 | -0.9764 | 27.32449 |
June | 496.00000 | 23.76399 | 35.42893 | -0.6119 | 13.94137 |
July | 497.00000 | 23.78661 | 44.83588 | -0.5462 | 12.19668 |
August | 514.00000 | 23.49247 | 39.98008 | -0.7030 | 17.26581 |
September | 485.00000 | 22.12843 | 31.52939 | -1.2906 | 41.14744 |
October | 502.00000 | 20.86551 | 21.84822 | -0.5967 | 15.34109 |
November | 489.00000 | 20.22883 | 12.03313 | -0.8476 | 22.66207 |
December | 497.00000 | 20.14120 | 11.38094 | -0.8825 | 23.72319 |
Annual Sum or Average | 5943.00000 | 21.74680 | 23.27878 | -0.7568 | 20.33601 |
Minimum of Months | 454.00000 | 20.14120 | 11.38094 | -1.2906 | 10.83641 |
Maximum of Months | 514.00000 | 23.78661 | 44.83588 | -0.3539 | 41.14744 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.06679 | 10.79862 | -0.9440 | 25.65936 |
February | 454.00000 | 20.21147 | 12.44913 | -0.8537 | 22.44276 |
March | 514.00000 | 20.83367 | 13.16299 | -0.6467 | 15.06464 |
April | 485.00000 | 22.16753 | 15.11525 | -0.2400 | 8.32477 |
May | 508.00000 | 23.47314 | 21.26958 | -0.7924 | 19.39983 |
June | 496.00000 | 24.06630 | 33.74436 | -0.4469 | 9.56252 |
July | 497.00000 | 24.14426 | 42.29666 | -0.3583 | 8.09233 |
August | 514.00000 | 23.78910 | 37.85578 | -0.5514 | 12.65771 |
September | 485.00000 | 22.47655 | 28.79830 | -1.1290 | 33.63651 |
October | 502.00000 | 21.21079 | 19.77055 | -0.4860 | 11.50792 |
November | 489.00000 | 20.34011 | 10.59875 | -0.8321 | 20.83132 |
December | 497.00000 | 20.29731 | 9.83476 | -0.8737 | 22.26382 |
Annual Sum or Average | 5943.00000 | 21.93856 | 21.39552 | -0.6779 | 17.38502 |
Minimum of Months | 454.00000 | 20.06679 | 9.83476 | -1.1290 | 8.09233 |
Maximum of Months | 514.00000 | 24.14426 | 42.29666 | -0.2400 | 33.63651 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.00941 | 10.38905 | -0.9717 | 26.81433 |
February | 454.00000 | 20.27665 | 11.97342 | -0.8336 | 21.61734 |
March | 514.00000 | 21.15697 | 12.53943 | -0.5287 | 13.19486 |
April | 485.00000 | 22.34892 | 14.56916 | -0.1392 | 8.53676 |
May | 508.00000 | 23.47876 | 20.85114 | -0.6362 | 17.61544 |
June | 496.00000 | 23.75328 | 34.17988 | -0.4285 | 10.93169 |
July | 497.00000 | 23.82263 | 42.88311 | -0.3385 | 9.88633 |
August | 514.00000 | 23.42480 | 38.42378 | -0.5568 | 14.19867 |
September | 485.00000 | 22.41910 | 28.54962 | -1.0779 | 33.03807 |
October | 502.00000 | 21.21226 | 19.39710 | -0.4679 | 11.35291 |
November | 489.00000 | 20.22288 | 10.15416 | -0.8785 | 22.75659 |
December | 497.00000 | 20.13506 | 9.46762 | -0.9395 | 25.03829 |
Annual Sum or Average | 5943.00000 | 21.86963 | 21.20572 | -0.6478 | 17.84866 |
Minimum of Months | 454.00000 | 20.00941 | 9.46762 | -1.0779 | 8.53676 |
Maximum of Months | 514.00000 | 23.82263 | 42.88311 | -0.1392 | 33.03807 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.00375 | 10.40371 | -0.9630 | 26.69270 |
February | 454.00000 | 20.64424 | 11.76625 | -0.7213 | 19.09977 |
March | 514.00000 | 21.54756 | 12.23723 | -0.4103 | 13.13079 |
April | 485.00000 | 22.67549 | 14.18733 | -0.0260 | 9.72797 |
May | 508.00000 | 23.14896 | 21.22279 | -0.7675 | 22.68490 |
June | 496.00000 | 23.55212 | 34.60370 | -0.5080 | 13.48929 |
July | 497.00000 | 23.66354 | 43.30720 | -0.4027 | 11.70409 |
August | 514.00000 | 23.40556 | 38.40318 | -0.5375 | 15.41799 |
September | 485.00000 | 22.47420 | 28.41273 | -1.0379 | 32.51207 |
October | 502.00000 | 21.33232 | 19.32951 | -0.4322 | 11.90192 |
November | 489.00000 | 20.28649 | 10.11448 | -0.8445 | 22.12792 |
December | 497.00000 | 20.05857 | 9.52930 | -0.9563 | 25.96501 |
Annual Sum or Average | 5943.00000 | 21.91119 | 21.21967 | -0.6329 | 18.67121 |
Minimum of Months | 454.00000 | 20.00375 | 9.52930 | -1.0379 | 9.72797 |
Maximum of Months | 514.00000 | 23.66354 | 43.30720 | -0.0260 | 32.51207 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.32538 | 10.08399 | -0.8236 | 20.87511 |
February | 454.00000 | 20.59072 | 11.69567 | -0.6981 | 16.60283 |
March | 514.00000 | 21.35869 | 12.27282 | -0.4397 | 10.53242 |
April | 485.00000 | 23.12494 | 13.81082 | 0.10436 | 8.07980 |
May | 508.00000 | 23.35928 | 20.98754 | -0.6945 | 18.30270 |
June | 496.00000 | 23.94493 | 33.81189 | -0.3479 | 9.73863 |
July | 497.00000 | 24.15893 | 42.00220 | -0.2074 | 7.71207 |
August | 514.00000 | 24.03683 | 36.95537 | -0.3077 | 9.35954 |
September | 485.00000 | 22.52046 | 28.21782 | -1.0106 | 29.65682 |
October | 502.00000 | 21.40194 | 19.10248 | -0.3901 | 9.51534 |
November | 489.00000 | 20.86818 | 9.79146 | -0.6211 | 13.46052 |
December | 497.00000 | 20.88412 | 8.99062 | -0.6276 | 13.74591 |
Annual Sum or Average | 5943.00000 | 22.22796 | 20.73237 | -0.5038 | 13.91475 |
Minimum of Months | 454.00000 | 20.32538 | 8.99062 | -1.0106 | 7.71207 |
Maximum of Months | 514.00000 | 24.15893 | 42.00220 | 0.10436 | 29.65682 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.82541 | 10.25282 | -1.0836 | 31.56247 |
February | 454.00000 | 19.91849 | 11.71895 | -1.0087 | 28.72182 |
March | 514.00000 | 20.27198 | 12.68617 | -0.8524 | 22.32630 |
April | 485.00000 | 20.84688 | 16.02973 | -0.5856 | 14.58855 |
May | 508.00000 | 22.43016 | 22.43165 | -1.1286 | 33.28090 |
June | 496.00000 | 23.59661 | 34.80687 | -0.6044 | 13.87108 |
July | 497.00000 | 23.58697 | 43.83550 | -0.5570 | 12.59115 |
August | 514.00000 | 22.75152 | 40.20428 | -0.9042 | 24.64419 |
September | 485.00000 | 21.32476 | 30.70313 | -1.5329 | 52.84115 |
October | 502.00000 | 20.34684 | 20.13277 | -0.7628 | 19.30830 |
November | 489.00000 | 19.83743 | 9.45847 | -1.0632 | 30.77692 |
December | 497.00000 | 19.77874 | 8.98139 | -1.1049 | 32.42980 |
Annual Sum or Average | 5943.00000 | 21.22303 | 21.86770 | -0.9312 | 26.35624 |
Minimum of Months | 454.00000 | 19.77874 | 8.98139 | -1.5329 | 12.59115 |
Maximum of Months | 514.00000 | 23.59661 | 43.83550 | -0.5570 | 52.84115 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.58634 | 9.90588 | -1.1501 | 34.56261 |
February | 385.00000 | 19.76716 | 11.18283 | -1.0295 | 29.76035 |
March | 433.00000 | 20.52305 | 11.89569 | -0.7340 | 19.06353 |
April | 410.00000 | 21.58974 | 14.84652 | -0.3559 | 11.76607 |
May | 430.00000 | 23.11079 | 21.07279 | -0.7766 | 23.16682 |
June | 418.00000 | 23.51928 | 34.61275 | -0.5191 | 13.66261 |
July | 422.00000 | 23.68513 | 43.31098 | -0.4102 | 12.14305 |
August | 433.00000 | 23.04959 | 39.16185 | -0.7119 | 19.56565 |
September | 410.00000 | 21.86872 | 29.38407 | -1.3039 | 43.30447 |
October | 427.00000 | 20.41210 | 19.49858 | -0.7269 | 18.64451 |
November | 417.00000 | 19.60875 | 8.98809 | -1.1258 | 33.59444 |
December | 422.00000 | 19.51220 | 8.64789 | -1.1818 | 35.92570 |
Annual Sum or Average | 5034.00000 | 21.36461 | 21.11793 | -0.8336 | 24.52307 |
Minimum of Months | 385.00000 | 19.51220 | 8.64789 | -1.3039 | 11.76607 |
Maximum of Months | 433.00000 | 23.68513 | 43.31098 | -0.3559 | 43.30447 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.86549 | 9.98684 | -1.0446 | 30.10046 |
February | 454.00000 | 20.36155 | 11.19795 | -0.8190 | 22.62122 |
March | 514.00000 | 21.30558 | 11.77998 | -0.4863 | 15.67175 |
April | 485.00000 | 22.34994 | 14.44227 | -0.1128 | 11.61253 |
May | 508.00000 | 22.93835 | 21.46096 | -0.8329 | 26.10449 |
June | 496.00000 | 23.29111 | 35.21648 | -0.5918 | 16.62143 |
July | 497.00000 | 23.41875 | 44.04779 | -0.4936 | 14.89282 |
August | 514.00000 | 23.08750 | 39.22182 | -0.6538 | 20.08519 |
September | 485.00000 | 22.22231 | 28.97900 | -1.1279 | 37.07438 |
October | 502.00000 | 20.91500 | 19.32283 | -0.5622 | 15.25147 |
November | 489.00000 | 19.93876 | 9.15859 | -0.9913 | 28.19307 |
December | 497.00000 | 19.78823 | 8.73996 | -1.0943 | 32.01362 |
Annual Sum or Average | 5943.00000 | 21.63563 | 21.22752 | -0.7331 | 22.48580 |
Minimum of Months | 454.00000 | 19.78823 | 8.73996 | -1.1279 | 11.61253 |
Maximum of Months | 514.00000 | 23.41875 | 44.04779 | -0.1128 | 37.07438 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.87200 | 9.95470 | -1.0531 | 30.26996 |
February | 454.00000 | 19.99268 | 11.40811 | -0.9561 | 26.62060 |
March | 514.00000 | 20.49159 | 12.27863 | -0.7526 | 19.14767 |
April | 485.00000 | 21.62835 | 15.08305 | -0.3285 | 11.95371 |
May | 508.00000 | 22.53717 | 22.04887 | -1.0147 | 30.57049 |
June | 496.00000 | 23.34435 | 35.17716 | -0.5922 | 16.23756 |
July | 497.00000 | 23.32838 | 44.35104 | -0.5575 | 14.87106 |
August | 514.00000 | 22.79188 | 39.96570 | -0.8069 | 22.73921 |
September | 485.00000 | 21.55975 | 30.07974 | -1.4050 | 47.29812 |
October | 502.00000 | 20.46007 | 19.75285 | -0.7116 | 17.65612 |
November | 489.00000 | 19.90210 | 9.15376 | -1.0118 | 28.66190 |
December | 497.00000 | 19.85891 | 8.66982 | -1.0497 | 30.06529 |
Annual Sum or Average | 5943.00000 | 21.32613 | 21.59284 | -0.8523 | 24.62465 |
Minimum of Months | 454.00000 | 19.85891 | 8.66982 | -1.4050 | 11.95371 |
Maximum of Months | 514.00000 | 23.34435 | 44.35104 | -0.3285 | 47.29812 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.70280 | 10.87046 | -1.1839 | 35.76463 |
February | 454.00000 | 19.78163 | 12.48855 | -1.1185 | 33.18066 |
March | 514.00000 | 20.06246 | 13.09087 | -0.9764 | 27.34526 |
April | 485.00000 | 20.36908 | 16.43297 | -0.7465 | 19.43103 |
May | 508.00000 | 21.48262 | 23.48315 | -1.4438 | 48.26899 |
June | 496.00000 | 22.86914 | 36.29896 | -0.8182 | 21.39545 |
July | 497.00000 | 22.84707 | 45.77117 | -0.7753 | 19.75100 |
August | 514.00000 | 21.91463 | 42.17635 | -1.1727 | 35.89265 |
September | 485.00000 | 20.68282 | 31.89581 | -1.8233 | 66.28629 |
October | 502.00000 | 19.90799 | 21.05816 | -0.9424 | 26.44481 |
November | 489.00000 | 19.70551 | 10.44121 | -1.1734 | 35.41251 |
December | 497.00000 | 19.66427 | 9.79868 | -1.2102 | 36.93643 |
Annual Sum or Average | 5943.00000 | 20.75926 | 22.91813 | -1.1149 | 33.82021 |
Minimum of Months | 454.00000 | 19.66427 | 9.79868 | -1.8233 | 19.43103 |
Maximum of Months | 514.00000 | 22.86914 | 45.77117 | -0.7465 | 66.28629 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.69563 | 10.85715 | -1.1852 | 35.83652 |
February | 454.00000 | 19.79168 | 12.46281 | -1.0895 | 32.14068 |
March | 514.00000 | 20.22477 | 12.93067 | -0.8536 | 23.49447 |
April | 485.00000 | 21.19383 | 15.60602 | -0.4794 | 14.60924 |
May | 508.00000 | 22.82185 | 21.67392 | -0.8842 | 27.19997 |
June | 496.00000 | 23.41609 | 35.01542 | -0.5395 | 14.98178 |
July | 497.00000 | 23.52398 | 43.81528 | -0.4484 | 13.55957 |
August | 514.00000 | 22.80839 | 40.03215 | -0.7944 | 22.95817 |
September | 485.00000 | 21.25967 | 30.87551 | -1.5670 | 54.61716 |
October | 502.00000 | 19.99298 | 20.89955 | -0.8873 | 24.60645 |
November | 489.00000 | 19.69948 | 10.42593 | -1.1732 | 35.42739 |
December | 497.00000 | 19.65660 | 9.78557 | -1.2166 | 37.20842 |
Annual Sum or Average | 5943.00000 | 21.18791 | 22.12390 | -0.9242 | 27.96398 |
Minimum of Months | 454.00000 | 19.65660 | 9.78557 | -1.5670 | 13.55957 |
Maximum of Months | 514.00000 | 23.52398 | 43.81528 | -0.4484 | 54.61716 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.71786 | 10.81613 | -1.1514 | 34.55604 |
February | 454.00000 | 19.99045 | 12.27177 | -0.9762 | 28.34248 |
March | 514.00000 | 20.82819 | 12.48489 | -0.6601 | 20.28470 |
April | 485.00000 | 21.86680 | 14.94701 | -0.2740 | 14.19180 |
May | 508.00000 | 22.55100 | 21.98082 | -0.9955 | 32.75655 |
June | 496.00000 | 23.07119 | 35.77389 | -0.6669 | 20.02733 |
July | 497.00000 | 23.17309 | 44.78675 | -0.5768 | 18.15634 |
August | 514.00000 | 22.78674 | 40.06203 | -0.7741 | 24.91990 |
September | 485.00000 | 21.65555 | 30.15188 | -1.3935 | 48.52566 |
October | 502.00000 | 20.31102 | 20.52327 | -0.7723 | 21.93200 |
November | 489.00000 | 19.75501 | 10.35575 | -1.1145 | 33.26156 |
December | 497.00000 | 19.66749 | 9.75329 | -1.2005 | 36.55227 |
Annual Sum or Average | 5943.00000 | 21.29358 | 22.08755 | -0.8783 | 27.74803 |
Minimum of Months | 454.00000 | 19.66749 | 9.75329 | -1.3935 | 14.19180 |
Maximum of Months | 514.00000 | 23.17309 | 44.78675 | -0.2740 | 48.52566 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.73834 | 10.77523 | -1.1494 | 34.34859 |
February | 454.00000 | 19.84068 | 12.37271 | -1.0573 | 30.79756 |
March | 514.00000 | 20.23360 | 12.88161 | -0.8703 | 23.64175 |
April | 485.00000 | 21.26267 | 15.50572 | -0.4559 | 15.16015 |
May | 508.00000 | 22.16361 | 22.53606 | -1.1626 | 37.38732 |
June | 496.00000 | 23.11182 | 35.73003 | -0.6673 | 19.58590 |
July | 497.00000 | 23.07974 | 45.07658 | -0.6379 | 17.99687 |
August | 514.00000 | 22.49037 | 40.79847 | -0.9213 | 27.64364 |
September | 485.00000 | 21.14926 | 30.96845 | -1.6093 | 57.00017 |
October | 502.00000 | 20.06025 | 20.75407 | -0.8653 | 23.52354 |
November | 489.00000 | 19.77142 | 10.32567 | -1.1111 | 32.85467 |
December | 497.00000 | 19.71597 | 9.69788 | -1.1506 | 34.43554 |
Annual Sum or Average | 5943.00000 | 21.06289 | 22.38247 | -0.9705 | 29.48419 |
Minimum of Months | 454.00000 | 19.71597 | 9.69788 | -1.6093 | 15.16015 |
Maximum of Months | 514.00000 | 23.11182 | 45.07658 | -0.4559 | 57.00017 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.760135E+09 | 2498.46 | 28-JAN-11:04 | 100.49 | 0.339322E+10 | 0.00 | 0.415335E+10 | 0.60 | 4.50 | 26-JAN-02:00 | 0.00 | 0.00 |
February | 0.393198E+11 | 123250.10 | 17-FEB-07:06 | 165.51 | 0.175960E+12 | 0.00 | 0.215279E+12 | 1.10 | 6.47 | 17-FEB-07:06 | 0.00 | 0.00 |
March | 0.635370E+11 | 123875.94 | 23-MAR-14:06 | 529.79 | 0.290478E+12 | 0.00 | 0.354015E+12 | 3.31 | 6.49 | 23-MAR-14:06 | 0.00 | 0.00 |
April | 0.628629E+11 | 151186.10 | 11-APR-13:44 | 639.94 | 0.300511E+12 | 0.00 | 0.363374E+12 | 4.24 | 6.91 | 11-APR-13:44 | 0.00 | 0.00 |
May | 0.329636E+11 | 157993.19 | 31-MAY-16:00 | 231.07 | 0.165480E+12 | 0.00 | 0.198443E+12 | 1.47 | 6.96 | 31-MAY-16:00 | 0.00 | 0.00 |
June | 0.136979E+12 | 218021.69 | 21-JUN-13:40 | 427.93 | 0.789335E+12 | 0.00 | 0.926314E+12 | 3.20 | 7.01 | 13-JUN-16:10 | 0.00 | 0.00 |
July | 0.167684E+12 | 223657.33 | 19-JUL-14:20 | 622.85 | 0.100570E+13 | 0.00 | 0.117339E+13 | 4.51 | 7.17 | 11-JUL-11:20 | 0.00 | 0.00 |
August | 0.128260E+12 | 225106.99 | 04-AUG-12:50 | 647.68 | 0.710699E+12 | 0.00 | 0.838959E+12 | 4.40 | 7.12 | 10-AUG-16:20 | 0.00 | 0.00 |
September | 0.984290E+10 | 123804.72 | 18-SEP-13:37 | 113.28 | 0.462925E+11 | 0.00 | 0.561354E+11 | 0.72 | 6.51 | 18-SEP-13:37 | 0.00 | 0.00 |
October | 0.459955E+11 | 146019.69 | 03-OCT-13:41 | 222.66 | 0.206825E+12 | 0.00 | 0.252820E+12 | 1.34 | 6.87 | 03-OCT-13:41 | 0.00 | 0.00 |
November | 0.527337E+11 | 115842.11 | 03-NOV-03:33 | 687.98 | 0.250266E+12 | 0.00 | 0.302999E+12 | 4.56 | 6.18 | 03-NOV-03:33 | 0.00 | 0.00 |
December | 0.590547E+11 | 118966.23 | 05-DEC-20:08 | 677.64 | 0.281455E+12 | 0.00 | 0.340510E+12 | 4.35 | 6.39 | 05-DEC-20:08 | 0.00 | 0.00 |
Annual Sum or Average | 0.799994E+12 | 5066.83 | 0.422640E+13 | 0.00 | 0.502639E+13 | 2.83 | 0.00 | 0.00 | ||||
Minimum of Months | 0.760135E+09 | 2498.46 | 100.49 | 0.339322E+10 | 0.00 | 0.415335E+10 | 0.60 | 4.50 | 0.00 | 0.00 | ||
Maximum of Months | 0.167684E+12 | 225106.99 | 687.98 | 0.100570E+13 | 0.00 | 0.117339E+13 | 4.56 | 7.17 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.881531E+10 | 157997.70 | 20-JUN-14:00 | 19.00 | 0.579501E+11 | 0.00 | 0.667654E+11 | 0.17 | 6.94 | 20-JUN-14:00 | 0.00 | 0.00 |
July | 0.175709E+11 | 185020.98 | 21-JUL-12:05 | 38.42 | 0.116047E+12 | 0.00 | 0.133618E+12 | 0.34 | 7.00 | 21-JUL-12:05 | 0.00 | 0.00 |
August | 0.824621E+10 | 154467.29 | 24-AUG-14:05 | 18.67 | 0.541738E+11 | 0.00 | 0.624200E+11 | 0.16 | 6.94 | 24-AUG-14:05 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.346324E+11 | 76.08 | 0.228171E+12 | 0.00 | 0.262803E+12 | 0.06 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.175709E+11 | 185020.98 | 38.42 | 0.116047E+12 | 0.00 | 0.133618E+12 | 0.34 | 7.00 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 267687.41 | 27-JAN-02:70 | 21.02 | 21.00 | 1.84 |
February | 7226212.83 | 161.95 | 39.07 | 12-FEB-23:18 | 653586.38 | 12-FEB-23:18 | 22.29 | 22.00 | 18.91 |
March | 4206936.49 | 197.61 | 51.41 | 08-MAR-05:16 | 789683.75 | 08-MAR-05:16 | 21.66 | 21.19 | 38.71 |
April | 1383454.78 | 18.28 | 90.20 | 06-APR-14:06 | 1025244.84 | 11-APR-13:46 | 21.24 | 20.73 | 49.29 |
May | 0.195278E+09 | 102.31 | 5594.89 | 31-MAY-16:00 | 1276864.24 | 31-MAY-16:00 | 21.33 | 21.07 | 18.62 |
June | 0.528743E+10 | 415.60 | 23781.38 | 29-JUN-11:30 | 1681236.10 | 29-JUN-12:00 | 22.75 | 21.57 | 45.92 |
July | 0.104115E+11 | 506.26 | 23781.38 | 03-JUL-15:00 | 1773503.30 | 19-JUL-16:30 | 22.74 | 21.27 | 63.89 |
August | 0.479720E+10 | 420.62 | 23781.38 | 23-AUG-13:00 | 1773402.79 | 04-AUG-12:50 | 22.16 | 21.10 | 64.37 |
September | 9400105.32 | 30.51 | 1732.40 | 19-SEP-14:06 | 889874.50 | 18-SEP-13:58 | 21.22 | 21.14 | 8.22 |
October | 8695336.95 | 198.45 | 1108.72 | 03-OCT-13:44 | 951894.62 | 03-OCT-13:44 | 22.15 | 21.83 | 22.78 |
November | 1005838.39 | 20.42 | 42.20 | 03-NOV-03:39 | 687162.73 | 03-NOV-03:39 | 21.20 | 20.74 | 41.65 |
December | 120968.43 | 2.75 | 45.54 | 15-DEC-08:30 | 723694.10 | 15-DEC-08:30 | 21.15 | 20.68 | 44.15 |
Annual Sum or Average | 0.207234E+11 | 2074.74 | 21.74 | 21.19 | 34.98 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 267687.41 | 21.02 | 20.68 | 1.84 | ||
Maximum of Months | 0.104115E+11 | 506.26 | 23781.38 | 1773503.30 | 22.75 | 22.00 | 64.37 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 21.02 | 21.02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 22.29 | 22.29 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 21.66 | 21.66 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 21.24 | 21.24 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 21.33 | 21.33 | 0.00 |
June | 0.100864E+10 | 16.08 | 23781.38 | 29-JUN-13:40 | 1535462.38 | 21-JUN-16:00 | 22.75 | 22.65 | 1.73 |
July | 0.167076E+10 | 29.50 | 23781.38 | 03-JUL-15:00 | 1606341.38 | 21-JUL-15:00 | 22.74 | 22.56 | 3.07 |
August | 0.810884E+09 | 13.83 | 23781.38 | 23-AUG-15:00 | 1578616.81 | 23-AUG-15:50 | 22.16 | 22.08 | 1.44 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 21.22 | 21.22 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 22.15 | 22.15 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 21.20 | 21.20 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 21.15 | 21.15 | 0.00 |
Annual Sum or Average | 0.349028E+10 | 59.42 | 21.74 | 21.71 | 0.52 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 | 21.02 | 0.00 | ||
Maximum of Months | 0.167076E+10 | 29.50 | 23781.38 | 1606341.38 | 22.75 | 22.65 | 3.07 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.166521E+13 | 0.00 | 653.77 | 4274307.30 | 17-JAN-04:01 | 0.00 | 36.74 | 76.25 | 3.51 | 0.00 | 0.14 | 0.98 | 17-JAN-04:01 |
February | 0.116086E+13 | 0.00 | 585.97 | 3096685.42 | 06-FEB-05:01 | 0.00 | 36.06 | 75.22 | 2.65 | 0.00 | 0.11 | 0.71 | 06-FEB-05:01 |
March | 0.858846E+12 | 0.00 | 614.02 | 3293902.64 | 21-MAR-04:01 | 0.00 | 32.25 | 72.06 | 1.67 | 0.00 | 0.07 | 0.75 | 21-MAR-04:01 |
April | 0.238938E+12 | 0.00 | 423.38 | 3271084.28 | 24-APR-04:01 | 0.00 | 26.69 | 54.66 | 0.47 | 0.00 | 0.02 | 0.75 | 24-APR-04:01 |
May | 0.205793E+11 | 0.00 | 165.51 | 2559246.50 | 27-MAY-04:01 | 0.00 | 21.99 | 32.07 | 0.04 | 0.00 | 0.00 | 0.59 | 27-MAY-04:01 |
June | 0.697885E+09 | 0.00 | 52.68 | 143488.53 | 15-JUN-09:22 | 0.00 | 21.13 | 24.40 | 0.00 | 0.00 | 0.00 | 0.03 | 15-JUN-09:22 |
July | 0.838987E+09 | 0.00 | 44.85 | 412610.17 | 05-JUL-09:17 | 0.00 | 20.39 | 23.13 | 0.00 | 0.00 | 0.00 | 0.09 | 05-JUL-09:17 |
August | 0.122166E+11 | 0.00 | 124.35 | 3056717.07 | 31-AUG-05:01 | 0.00 | 20.70 | 28.31 | 0.02 | 0.00 | 0.00 | 0.70 | 31-AUG-05:01 |
September | 0.104583E+12 | 0.00 | 346.77 | 3098514.29 | 30-SEP-04:01 | 0.00 | 23.58 | 45.67 | 0.21 | 0.00 | 0.01 | 0.71 | 30-SEP-04:01 |
October | 0.579405E+12 | 0.00 | 542.21 | 3257233.42 | 11-OCT-04:01 | 0.00 | 29.44 | 63.87 | 1.10 | 0.00 | 0.05 | 0.75 | 11-OCT-04:01 |
November | 0.142054E+13 | 0.00 | 631.55 | 3460182.84 | 24-NOV-05:01 | 0.00 | 37.53 | 76.45 | 2.98 | 0.00 | 0.13 | 0.79 | 24-NOV-05:01 |
December | 0.170471E+13 | 0.00 | 676.79 | 3306327.14 | 05-DEC-05:01 | 0.00 | 39.02 | 77.87 | 3.59 | 0.00 | 0.15 | 0.76 | 05-DEC-05:01 |
Annual Sum or Average | 0.776743E+13 | 0.00 | 4861.82 | 0.00 | 28.75 | 54.03 | 1.35 | 0.00 | 0.06 | ||||
Minimum of Months | 0.697885E+09 | 0.00 | 44.85 | 143488.53 | 0.00 | 20.39 | 23.13 | 0.00 | 0.00 | 0.00 | 0.03 | ||
Maximum of Months | 0.170471E+13 | 0.00 | 676.79 | 4274307.30 | 0.00 | 39.02 | 77.87 | 3.59 | 0.00 | 0.15 | 0.98 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 325.92 | 0.00 | 0.17 | 325.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 | 01-JAN-05:00 | 0.54 | 01-JAN-05:00 | 0.00 | 0.00 | 0.00 |
February | 1760.06 | 0.00 | 1.22 | 1760.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 | 13-FEB-05:01 | 0.97 | 13-FEB-05:01 | 0.00 | 0.00 | 0.00 |
March | 133421.78 | 0.00 | 0.05 | 133421.78 | 0.00 | 0.00 | 0.00 | 0.00 | 1026.94 | 27-MAR-16:01 | 1026.94 | 27-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 52487753.29 | 0.00 | 7.12 | 52487753.29 | 0.00 | 0.00 | 0.00 | 0.00 | 7283.71 | 22-APR-14:00 | 7283.71 | 22-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.119302E+11 | 0.00 | 166.04 | 0.119302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91647.73 | 31-MAY-16:00 | 91647.73 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.515281E+11 | 0.00 | 339.21 | 0.514218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135747.33 | 30-JUN-12:05 | 135268.10 | 30-JUN-14:30 | 0.00 | 0.00 | 0.00 |
July | 0.701952E+11 | 0.00 | 371.53 | 0.699128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140769.00 | 21-JUL-14:40 | 140769.00 | 21-JUL-14:40 | 0.00 | 0.00 | 0.00 |
August | 0.401043E+11 | 0.00 | 280.07 | 0.401033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140802.88 | 11-AUG-15:30 | 140802.88 | 11-AUG-15:30 | 0.00 | 0.00 | 0.00 |
September | 0.927286E+09 | 0.00 | 37.47 | 0.927286E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29521.52 | 07-SEP-15:55 | 29521.52 | 07-SEP-15:55 | 0.00 | 0.00 | 0.00 |
October | 128.09 | 0.00 | 0.08 | 128.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 | 07-OCT-05:39 | 0.49 | 07-OCT-05:39 | 0.00 | 0.00 | 0.00 |
November | 47.16 | 0.00 | 0.03 | 47.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 | 18-NOV-06:38 | 0.39 | 18-NOV-06:38 | 0.00 | 0.00 | 0.00 |
December | 2074.00 | 0.00 | 1.30 | 2074.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 | 26-DEC-05:01 | 0.98 | 26-DEC-05:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174738E+12 | 0.00 | 1204.27 | 0.174348E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 47.16 | 0.00 | 0.03 | 47.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 | 0.39 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.701952E+11 | 0.00 | 371.53 | 0.699128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140802.88 | 140802.88 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 77554.42 | 0.00 | 37.75 | 77554.42 | 0.00 | 0.00 | 0.00 | 0.00 | 5.02 | 15-JAN-17:50 | 5.02 | 15-JAN-17:50 | 0.00 | 0.00 | 0.00 |
February | 90971.66 | 0.00 | 27.32 | 90971.66 | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 07-FEB-04:04 | 5.50 | 07-FEB-04:04 | 0.00 | 0.00 | 0.00 |
March | 0.111519E+10 | 0.00 | 35.83 | 0.111519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 286475.93 | 22-MAR-14:01 | 286475.93 | 22-MAR-14:01 | 0.00 | 0.00 | 0.00 |
April | 0.818761E+10 | 0.00 | 56.62 | 0.818761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 553729.14 | 26-APR-13:04 | 553729.14 | 26-APR-13:04 | 0.00 | 0.00 | 0.00 |
May | 0.115678E+12 | 0.00 | 174.74 | 0.115678E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 870727.69 | 31-MAY-16:00 | 870727.69 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.478928E+12 | 0.00 | 337.60 | 0.477932E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1319163.65 | 30-JUN-12:05 | 1304526.01 | 30-JUN-14:30 | 0.00 | 0.00 | 0.00 |
July | 0.612641E+12 | 0.00 | 359.55 | 0.610309E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1324758.08 | 21-JUL-14:30 | 1324758.08 | 21-JUL-14:30 | 0.00 | 0.00 | 0.00 |
August | 0.343767E+12 | 0.00 | 285.54 | 0.343759E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1253749.92 | 11-AUG-15:40 | 1253749.92 | 11-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.264986E+11 | 0.00 | 117.04 | 0.264986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 600705.30 | 18-SEP-14:02 | 600705.30 | 18-SEP-14:02 | 0.00 | 0.00 | 0.00 |
October | 0.306294E+10 | 0.00 | 41.17 | 0.306294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 556105.98 | 03-OCT-14:01 | 556105.98 | 03-OCT-14:01 | 0.00 | 0.00 | 0.00 |
November | 48081.74 | 0.00 | 11.55 | 48081.74 | 0.00 | 0.00 | 0.00 | 0.00 | 5.99 | 24-NOV-02:61 | 5.99 | 24-NOV-02:61 | 0.00 | 0.00 | 0.00 |
December | 41663.64 | 0.00 | 16.48 | 41663.64 | 0.00 | 0.00 | 0.00 | 0.00 | 4.61 | 31-DEC-07:59 | 4.61 | 31-DEC-07:59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158988E+13 | 0.00 | 1501.19 | 0.158654E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 41663.64 | 0.00 | 11.55 | 41663.64 | 0.00 | 0.00 | 0.00 | 0.00 | 4.61 | 4.61 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.612641E+12 | 0.00 | 359.55 | 0.610309E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1324758.08 | 1324758.08 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 7126521.86 | 0.00 | 5.00 | 7126521.86 | 0.00 | 0.00 | 0.00 | 0.00 | 2656.61 | 28-JAN-05:13 | 2656.61 | 28-JAN-05:13 | 0.00 | 0.00 | 0.00 |
February | 4645360.88 | 0.00 | 3.30 | 4645360.88 | 0.00 | 0.00 | 0.00 | 0.00 | 7224.65 | 22-FEB-06:02 | 7224.65 | 22-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 6402110.68 | 0.00 | 5.32 | 6402110.68 | 0.00 | 0.00 | 0.00 | 0.00 | 4282.49 | 08-MAR-05:01 | 4282.49 | 08-MAR-05:01 | 0.00 | 0.00 | 0.00 |
April | 32669151.98 | 0.00 | 9.16 | 32669151.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7108.41 | 22-APR-14:00 | 7108.41 | 22-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.106423E+11 | 0.00 | 152.24 | 0.106423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91882.31 | 31-MAY-16:00 | 91882.31 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.487244E+11 | 0.00 | 321.00 | 0.486596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 146599.19 | 30-JUN-14:30 | 146599.19 | 30-JUN-14:30 | 0.00 | 0.00 | 0.00 |
July | 0.635362E+11 | 0.00 | 339.36 | 0.633752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160160.65 | 23-JUL-13:01 | 160160.65 | 23-JUL-13:01 | 0.00 | 0.00 | 0.00 |
August | 0.340497E+11 | 0.00 | 249.22 | 0.340497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135984.02 | 11-AUG-15:40 | 135984.02 | 11-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.648081E+09 | 0.00 | 28.90 | 0.648081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22415.72 | 07-SEP-16:00 | 22415.72 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 2365680.27 | 0.00 | 3.60 | 2365680.27 | 0.00 | 0.00 | 0.00 | 0.00 | 3489.79 | 27-OCT-04:22 | 3489.79 | 27-OCT-04:22 | 0.00 | 0.00 | 0.00 |
November | 9296501.02 | 0.00 | 5.55 | 9296501.02 | 0.00 | 0.00 | 0.00 | 0.00 | 6981.30 | 27-NOV-06:12 | 6981.30 | 27-NOV-06:12 | 0.00 | 0.00 | 0.00 |
December | 9246515.71 | 0.00 | 9.70 | 9246515.71 | 0.00 | 0.00 | 0.00 | 0.00 | 4373.78 | 16-DEC-05:12 | 4373.78 | 16-DEC-05:12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157672E+12 | 0.00 | 1132.33 | 0.157447E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2365680.27 | 0.00 | 3.30 | 2365680.27 | 0.00 | 0.00 | 0.00 | 0.00 | 2656.61 | 2656.61 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.635362E+11 | 0.00 | 339.36 | 0.633752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160160.65 | 160160.65 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 |
February | 9206227.45 | 0.00 | 1.27 | 9206227.45 | 0.00 | 0.00 | 0.00 | 0.00 | 37944.75 | 10-FEB-06:01 | 37944.75 | 10-FEB-06:01 | 0.00 | 0.00 | 0.00 |
March | 0.301199E+09 | 0.00 | 6.27 | 0.301199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 121853.43 | 23-MAR-04:47 | 121853.43 | 23-MAR-04:47 | 0.00 | 0.00 | 0.00 |
April | 0.490969E+10 | 0.00 | 78.36 | 0.490969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 126438.59 | 24-APR-03:43 | 126438.59 | 24-APR-03:43 | 0.00 | 0.00 | 0.00 |
May | 0.191617E+11 | 0.00 | 195.60 | 0.191617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81736.02 | 15-MAY-12:06 | 81736.02 | 15-MAY-12:06 | 0.00 | 0.00 | 0.00 |
June | 0.344442E+11 | 0.00 | 319.30 | 0.328913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85781.84 | 27-JUN-17:50 | 75301.10 | 02-JUN-09:01 | 0.00 | 0.00 | 0.00 |
July | 0.418349E+11 | 0.00 | 338.43 | 0.391783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 162237.86 | 31-JUL-01:57 | 140479.80 | 31-JUL-01:57 | 0.00 | 0.00 | 0.00 |
August | 0.314813E+11 | 0.00 | 326.90 | 0.306859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 136305.97 | 28-AUG-00:13 | 136305.97 | 28-AUG-00:13 | 0.00 | 0.00 | 0.00 |
September | 0.139766E+11 | 0.00 | 131.80 | 0.138903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75897.04 | 07-SEP-13:22 | 75897.04 | 07-SEP-13:22 | 0.00 | 0.00 | 0.00 |
October | 0.450937E+10 | 0.00 | 54.01 | 0.450777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 144962.78 | 16-OCT-03:59 | 144962.78 | 16-OCT-03:59 | 0.00 | 0.00 | 0.00 |
November | 40529581.07 | 0.00 | 2.37 | 40529581.07 | 0.00 | 0.00 | 0.00 | 0.00 | 54923.39 | 07-NOV-06:02 | 54923.39 | 07-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 6818662.70 | 0.00 | 0.82 | 6818662.70 | 0.00 | 0.00 | 0.00 | 0.00 | 22325.01 | 26-DEC-06:02 | 22325.01 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.150675E+12 | 0.00 | 1455.11 | 0.145583E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.418349E+11 | 0.00 | 338.43 | 0.391783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 162237.86 | 144962.78 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2468241.59 | 0.00 | 177.56 | 2468241.59 | 0.00 | 0.00 | 0.00 | 0.00 | 49.57 | 01-JAN-00:33 | 49.57 | 01-JAN-00:33 | 0.00 | 0.00 | 0.00 |
February | 0.171933E+12 | 0.00 | 286.68 | 0.171933E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 346636.64 | 22-FEB-14:41 | 346636.64 | 22-FEB-14:41 | 0.00 | 0.00 | 0.00 |
March | 0.269607E+12 | 0.00 | 545.42 | 0.269607E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 340273.74 | 01-MAR-07:12 | 340273.74 | 01-MAR-07:12 | 0.00 | 0.00 | 0.00 |
April | 0.263906E+12 | 0.00 | 719.67 | 0.263906E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 305136.23 | 11-APR-14:19 | 305136.23 | 11-APR-14:19 | 0.00 | 0.00 | 0.00 |
May | 0.256760E+09 | 0.00 | 256.80 | 0.256760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 265474.84 | 31-MAY-23:30 | 265474.84 | 31-MAY-23:30 | 0.00 | 0.00 | 0.00 |
June | 0.212735E+12 | 0.00 | 443.01 | 0.206262E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 479731.85 | 30-JUN-18:39 | 398580.90 | 09-JUN-12:51 | 0.00 | 0.00 | 0.00 |
July | 0.297245E+12 | 0.00 | 713.19 | 0.281307E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 461585.22 | 26-JUL-14:57 | 354707.37 | 31-JUL-10:22 | 0.00 | 0.00 | 0.00 |
August | 0.285042E+12 | 0.00 | 743.67 | 0.282858E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 396766.89 | 11-AUG-14:05 | 396766.89 | 11-AUG-14:05 | 0.00 | 0.00 | 0.00 |
September | 0.281399E+09 | 0.00 | 284.27 | 0.281399E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 289962.10 | 30-SEP-23:51 | 289962.10 | 30-SEP-23:51 | 0.00 | 0.00 | 0.00 |
October | 0.190748E+12 | 0.00 | 411.30 | 0.190748E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 314586.31 | 28-OCT-11:31 | 314586.31 | 28-OCT-11:31 | 0.00 | 0.00 | 0.00 |
November | 0.225321E+12 | 0.00 | 694.00 | 0.225321E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 277389.84 | 01-NOV-06:11 | 277389.84 | 01-NOV-06:11 | 0.00 | 0.00 | 0.00 |
December | 0.257203E+12 | 0.00 | 744.00 | 0.257203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 292314.25 | 14-DEC-16:06 | 292314.25 | 14-DEC-16:06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217428E+13 | 0.00 | 6019.56 | 0.214969E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2468241.59 | 0.00 | 177.56 | 2468241.59 | 0.00 | 0.00 | 0.00 | 0.00 | 49.57 | 49.57 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.297245E+12 | 0.00 | 744.00 | 0.282858E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 479731.85 | 398580.90 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.262081E+10 | 0.832699E+09 | 626.95 | 0.262081E+10 | -0.0 | 0.00 | 0.96 | 13-JAN-15:22 | 0.00 | 01-JAN-00:01 | 6612.07 | 13-JAN-15:22 | 6612.07 | 13-JAN-15:22 | 0.00 | 28-JAN-05:52 | 1699.12 | 13-JAN-15:22 | 0.00 | 01-JAN-00:01 |
February | 0.687134E+10 | 0.199333E+10 | 567.50 | 0.687134E+10 | -0.0 | 0.00 | 1.00 | 19-FEB-10:31 | 0.00 | 19-FEB-00:51 | 13268.77 | 28-FEB-11:21 | 13268.77 | 28-FEB-11:21 | 0.00 | 25-FEB-04:32 | 3576.39 | 28-FEB-11:21 | 0.00 | 01-FEB-00:01 |
March | 0.143553E+11 | 0.380792E+10 | 708.83 | 0.143553E+11 | -0.0 | 0.00 | 1.00 | 01-MAR-09:31 | 0.00 | 01-MAR-00:01 | 13626.29 | 01-MAR-09:31 | 13626.29 | 01-MAR-09:31 | 0.00 | 09-MAR-17:18 | 3674.40 | 01-MAR-09:31 | 0.00 | 01-MAR-00:01 |
April | 0.212653E+11 | 0.550953E+10 | 720.00 | 0.212653E+11 | -0.0 | 0.00 | 1.00 | 01-APR-00:01 | 0.53 | 30-APR-24:00 | 9671.47 | 20-APR-19:00 | 9671.47 | 20-APR-19:00 | 0.00 | 14-APR-10:22 | 2547.98 | 20-APR-18:51 | 0.00 | 01-APR-00:01 |
May | 0.751632E+10 | 0.224911E+10 | 744.00 | 0.751632E+10 | -0.0 | 0.00 | 0.74 | 31-MAY-23:59 | 0.32 | 27-MAY-07:00 | 4769.63 | 31-MAY-23:51 | 4769.63 | 31-MAY-23:51 | 0.00 | 09-MAY-18:40 | 1323.56 | 31-MAY-23:51 | 0.00 | 01-MAY-00:10 |
June | 0.125583E+11 | 0.348987E+10 | 720.00 | 0.125360E+11 | 22335701.96 | 0.00 | 0.94 | 30-JUN-23:51 | 0.64 | 24-JUN-16:57 | 6658.54 | 30-JUN-23:51 | 6658.08 | 30-JUN-23:52 | 162.24 | 27-JUN-15:51 | 1726.08 | 30-JUN-23:51 | 0.00 | 01-JUN-00:05 |
July | 0.181936E+11 | 0.473322E+10 | 744.00 | 0.181387E+11 | 54880690.36 | 0.00 | 1.00 | 06-JUL-15:40 | 0.89 | 01-JUL-17:00 | 8551.50 | 31-JUL-24:00 | 8551.50 | 31-JUL-24:00 | 221.33 | 26-JUL-15:00 | 2222.07 | 31-JUL-24:00 | 0.00 | 01-JUL-00:01 |
August | 0.229879E+11 | 0.599049E+10 | 744.00 | 0.229451E+11 | 42873643.05 | 0.00 | 1.00 | 01-AUG-00:01 | 0.52 | 31-AUG-24:00 | 9553.84 | 27-AUG-18:42 | 9553.84 | 27-AUG-18:42 | 177.49 | 03-AUG-14:00 | 2599.45 | 11-AUG-16:00 | 0.00 | 01-AUG-00:01 |
September | 0.664015E+10 | 0.200976E+10 | 720.00 | 0.664015E+10 | -0.0 | 0.00 | 0.66 | 30-SEP-23:51 | 0.27 | 30-SEP-07:00 | 4063.64 | 30-SEP-23:51 | 4063.64 | 30-SEP-23:51 | 0.00 | 21-SEP-14:58 | 1148.85 | 30-SEP-23:51 | 0.00 | 01-SEP-00:10 |
October | 0.104765E+11 | 0.298174E+10 | 744.00 | 0.104765E+11 | -0.0 | 0.00 | 0.85 | 31-OCT-23:48 | 0.45 | 30-OCT-06:01 | 5498.35 | 31-OCT-23:42 | 5498.35 | 31-OCT-23:42 | 0.00 | 06-OCT-16:17 | 1464.94 | 31-OCT-23:42 | 0.00 | 01-OCT-00:01 |
November | 0.119363E+11 | 0.318329E+10 | 607.50 | 0.119363E+11 | -0.0 | 0.00 | 1.00 | 08-NOV-22:01 | 0.00 | 08-NOV-21:51 | 13876.10 | 29-NOV-13:31 | 13876.10 | 29-NOV-13:31 | 0.00 | 17-NOV-12:03 | 3733.89 | 29-NOV-13:31 | 0.00 | 01-NOV-00:01 |
December | 0.157662E+11 | 0.403627E+10 | 603.00 | 0.157662E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-01:01 | 0.00 | 01-DEC-00:01 | 14327.47 | 14-DEC-14:01 | 14327.47 | 14-DEC-14:01 | 0.00 | 11-DEC-14:14 | 3843.24 | 22-DEC-06:41 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.151188E+12 | 0.408172E+11 | 8249.79 | 0.151068E+12 | 0.120090E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.262081E+10 | 0.832699E+09 | 567.50 | 0.262081E+10 | -0.0 | 0.00 | 0.66 | 0.00 | 4063.64 | 4063.64 | 0.00 | 1148.85 | 0.00 | |||||||
Maximum of Months | 0.229879E+11 | 0.599049E+10 | 744.00 | 0.229451E+11 | 54880690.36 | 0.00 | 1.00 | 0.89 | 14327.47 | 14327.47 | 221.33 | 3843.24 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.115267E+11 | 0.320549E+10 | 487.71 | 0.115267E+11 | -0.0 | 0.00 | 0.72 | 13-JAN-15:22 | 0.00 | 01-JAN-00:01 | 43538.58 | 13-JAN-15:22 | 43538.58 | 13-JAN-15:22 | 0.00 | 13-JAN-15:22 | 10357.26 | 13-JAN-15:22 | 0.00 | 01-JAN-00:01 |
February | 0.534969E+11 | 0.136246E+11 | 567.48 | 0.534969E+11 | -0.0 | 0.00 | 1.00 | 19-FEB-10:31 | 0.00 | 19-FEB-00:51 | 126140.53 | 28-FEB-11:21 | 126140.53 | 28-FEB-11:21 | 0.00 | 24-FEB-10:32 | 29102.97 | 28-FEB-11:21 | 0.00 | 01-FEB-00:01 |
March | 0.124132E+12 | 0.288252E+11 | 708.83 | 0.124132E+12 | -0.0 | 0.00 | 1.00 | 01-MAR-09:31 | 0.00 | 01-MAR-00:01 | 130060.95 | 01-MAR-09:31 | 130060.95 | 01-MAR-09:31 | 0.00 | 22-MAR-15:11 | 30060.77 | 01-MAR-09:31 | 0.00 | 01-MAR-00:01 |
April | 0.191651E+12 | 0.423247E+11 | 720.00 | 0.191651E+12 | -0.0 | 0.00 | 1.00 | 01-APR-00:01 | 0.42 | 30-APR-24:00 | 93222.36 | 20-APR-19:00 | 93222.36 | 20-APR-19:00 | 0.00 | 26-APR-21:16 | 21051.89 | 20-APR-18:51 | 0.00 | 01-APR-00:01 |
May | 0.652083E+11 | 0.169042E+11 | 744.00 | 0.652083E+11 | -0.0 | 0.00 | 0.71 | 31-MAY-23:41 | 0.24 | 27-MAY-06:10 | 44239.15 | 31-MAY-23:41 | 44239.15 | 31-MAY-23:41 | 0.00 | 17-MAY-17:10 | 10594.64 | 31-MAY-23:41 | 0.00 | 01-MAY-00:10 |
June | 0.117963E+12 | 0.282206E+11 | 720.00 | 0.117741E+12 | 0.222588E+09 | 0.00 | 0.94 | 30-JUN-23:21 | 0.60 | 24-JUN-16:57 | 63915.16 | 30-JUN-23:21 | 63892.24 | 30-JUN-23:32 | 1615.31 | 27-JUN-15:51 | 14213.25 | 30-JUN-23:21 | 0.00 | 01-JUN-00:05 |
July | 0.170907E+12 | 0.383300E+11 | 744.00 | 0.170360E+12 | 0.546757E+09 | 0.00 | 1.00 | 06-JUL-18:20 | 0.85 | 01-JUL-17:00 | 82972.31 | 31-JUL-23:15 | 82972.31 | 31-JUL-23:15 | 2201.66 | 26-JUL-15:00 | 18494.57 | 31-JUL-23:12 | 0.00 | 01-JUL-00:01 |
August | 0.215198E+12 | 0.479270E+11 | 744.00 | 0.214776E+12 | 0.421769E+09 | 0.00 | 1.00 | 01-AUG-00:01 | 0.42 | 31-AUG-24:00 | 90641.65 | 10-AUG-19:00 | 90641.65 | 10-AUG-19:00 | 1771.95 | 03-AUG-14:00 | 21123.89 | 11-AUG-16:00 | 0.00 | 01-AUG-00:01 |
September | 0.529395E+11 | 0.139776E+11 | 720.00 | 0.529395E+11 | -0.0 | 0.00 | 0.56 | 30-SEP-23:32 | 0.17 | 30-SEP-06:10 | 32648.44 | 30-SEP-23:32 | 32648.44 | 30-SEP-23:32 | 0.00 | 19-SEP-16:26 | 8143.64 | 02-SEP-18:06 | 0.00 | 01-SEP-00:10 |
October | 0.833020E+11 | 0.208492E+11 | 744.00 | 0.833020E+11 | -0.0 | 0.00 | 0.76 | 31-OCT-23:01 | 0.27 | 30-OCT-06:01 | 45717.70 | 31-OCT-23:03 | 45717.70 | 31-OCT-23:03 | 0.00 | 02-OCT-17:07 | 10883.62 | 03-OCT-16:00 | 0.00 | 01-OCT-00:01 |
November | 0.932514E+11 | 0.221599E+11 | 607.50 | 0.932514E+11 | -0.0 | 0.00 | 1.00 | 08-NOV-22:01 | 0.00 | 08-NOV-21:51 | 132057.41 | 29-NOV-13:31 | 132057.41 | 29-NOV-13:31 | 0.00 | 17-NOV-12:12 | 30495.41 | 29-NOV-13:31 | 0.00 | 01-NOV-00:01 |
December | 0.129418E+12 | 0.288222E+11 | 603.00 | 0.129418E+12 | -0.0 | 0.00 | 1.00 | 01-DEC-01:01 | 0.00 | 01-DEC-00:01 | 136651.00 | 14-DEC-14:01 | 136651.00 | 14-DEC-14:01 | 0.00 | 06-DEC-15:11 | 31379.82 | 14-DEC-14:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.130899E+13 | 0.305171E+12 | 8110.53 | 0.130780E+13 | 0.119111E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.115267E+11 | 0.320549E+10 | 487.71 | 0.115267E+11 | -0.0 | 0.00 | 0.56 | 0.00 | 32648.44 | 32648.44 | 0.00 | 8143.64 | 0.00 | |||||||
Maximum of Months | 0.215198E+12 | 0.479270E+11 | 744.00 | 0.214776E+12 | 0.546757E+09 | 0.00 | 1.00 | 0.85 | 136651.00 | 136651.00 | 2201.66 | 31379.82 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.267739E+09 | 88300783.76 | 211.29 | 0.267739E+09 | 0.00 | 0.00 | 0.23 | 19-JAN-11:04 | 0.00 | 01-JAN-00:01 | 1244.85 | 19-JAN-11:04 | 1244.85 | 19-JAN-11:04 | 0.00 | 20-JAN-10:50 | 396.39 | 19-JAN-11:04 | 0.00 | 01-JAN-00:01 |
February | 0.359569E+10 | 0.109898E+10 | 563.02 | 0.359569E+10 | -0.0 | 0.00 | 1.00 | 22-FEB-11:01 | 0.00 | 04-FEB-04:01 | 12634.60 | 28-FEB-11:21 | 12634.60 | 28-FEB-11:21 | 0.00 | 07-FEB-13:40 | 3394.01 | 28-FEB-11:21 | 0.00 | 01-FEB-00:01 |
March | 0.103165E+11 | 0.288674E+10 | 708.83 | 0.103165E+11 | -0.0 | 0.00 | 1.00 | 01-MAR-09:31 | 0.00 | 01-MAR-00:01 | 12986.18 | 01-MAR-09:31 | 12986.18 | 01-MAR-09:31 | 0.00 | 02-MAR-08:41 | 3498.59 | 01-MAR-09:31 | 0.00 | 01-MAR-00:01 |
April | 0.174735E+11 | 0.452009E+10 | 720.00 | 0.174735E+11 | -0.0 | 0.00 | 1.00 | 01-APR-15:51 | 0.26 | 30-APR-24:00 | 9278.68 | 20-APR-19:00 | 9278.68 | 20-APR-19:00 | 0.00 | 07-APR-12:30 | 2440.68 | 20-APR-18:51 | 0.00 | 01-APR-00:01 |
May | 0.551920E+10 | 0.168997E+10 | 742.84 | 0.551920E+10 | -0.0 | 0.00 | 0.69 | 31-MAY-23:12 | 0.00 | 02-MAY-06:41 | 4292.08 | 31-MAY-23:12 | 4292.08 | 31-MAY-23:12 | 0.00 | 16-MAY-15:07 | 1208.49 | 31-MAY-23:12 | 0.00 | 01-MAY-00:10 |
June | 0.114286E+11 | 0.321280E+10 | 720.00 | 0.114064E+11 | 22229696.54 | 0.00 | 0.92 | 30-JUN-23:11 | 0.50 | 25-JUN-04:52 | 6295.13 | 30-JUN-23:11 | 6289.32 | 30-JUN-23:12 | 161.57 | 27-JUN-15:51 | 1644.17 | 30-JUN-23:11 | 0.00 | 01-JUN-00:05 |
July | 0.167247E+11 | 0.441079E+10 | 744.00 | 0.166701E+11 | 54635543.26 | 0.00 | 1.00 | 06-JUL-16:00 | 0.79 | 31-JUL-06:17 | 8210.93 | 31-JUL-23:04 | 8210.93 | 31-JUL-23:04 | 220.05 | 26-JUL-15:00 | 2129.90 | 31-JUL-23:04 | 0.00 | 01-JUL-00:01 |
August | 0.208905E+11 | 0.540657E+10 | 744.00 | 0.208491E+11 | 41394491.45 | 0.00 | 1.00 | 01-AUG-00:01 | 0.32 | 31-AUG-24:00 | 9130.65 | 10-AUG-19:00 | 9130.65 | 10-AUG-19:00 | 177.49 | 03-AUG-14:00 | 2490.86 | 11-AUG-16:00 | 0.00 | 01-AUG-00:01 |
September | 0.357416E+10 | 0.112476E+10 | 708.76 | 0.357416E+10 | -0.0 | 0.00 | 0.50 | 02-SEP-18:16 | 0.00 | 03-SEP-10:23 | 2999.05 | 02-SEP-18:16 | 2999.05 | 02-SEP-18:16 | 0.00 | 12-SEP-14:40 | 891.47 | 02-SEP-18:16 | 0.00 | 01-SEP-00:10 |
October | 0.588367E+10 | 0.177502E+10 | 743.61 | 0.588367E+10 | -0.0 | 0.00 | 0.70 | 03-OCT-15:51 | 0.00 | 15-OCT-05:11 | 4389.80 | 03-OCT-15:53 | 4389.80 | 03-OCT-15:53 | 0.00 | 12-OCT-16:04 | 1231.65 | 03-OCT-16:00 | 0.00 | 01-OCT-00:01 |
November | 0.739534E+10 | 0.212362E+10 | 607.48 | 0.739534E+10 | -0.0 | 0.00 | 1.00 | 08-NOV-22:01 | 0.00 | 08-NOV-21:51 | 13190.84 | 29-NOV-13:31 | 13190.84 | 29-NOV-13:31 | 0.00 | 09-NOV-10:33 | 3556.85 | 29-NOV-13:31 | 0.00 | 01-NOV-00:01 |
December | 0.110515E+11 | 0.296842E+10 | 603.00 | 0.110515E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-01:01 | 0.00 | 01-DEC-00:01 | 13680.80 | 14-DEC-14:01 | 13680.80 | 14-DEC-14:01 | 0.00 | 22-DEC-06:42 | 3674.13 | 14-DEC-14:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.114121E+12 | 0.313061E+11 | 7816.83 | 0.114003E+12 | 0.118260E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.267739E+09 | 88300783.76 | 211.29 | 0.267739E+09 | -0.0 | 0.00 | 0.23 | 0.00 | 1244.85 | 1244.85 | 0.00 | 396.39 | 0.00 | |||||||
Maximum of Months | 0.208905E+11 | 0.540657E+10 | 744.00 | 0.208491E+11 | 54635543.26 | 0.00 | 1.00 | 0.79 | 13680.80 | 13680.80 | 220.05 | 3674.13 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.33 | 0.00 | 14.33 | 0.00 | 1754.52 | 0.00 | 0.00 | 0.00 |
February | 63.36 | 0.00 | 63.36 | 0.00 | 1620.92 | 0.00 | 0.00 | 0.00 |
March | 169.47 | 0.00 | 169.47 | 0.47 | 1301.66 | 0.00 | 0.00 | 0.00 |
April | 306.49 | 6.63 | 299.87 | 42.87 | 749.94 | 0.00 | 0.00 | 0.00 |
May | 469.40 | 74.17 | 395.22 | 231.06 | 301.80 | 0.00 | 0.00 | 0.00 |
June | 612.70 | 135.92 | 476.78 | 491.28 | 138.89 | 0.00 | 0.00 | 0.00 |
July | 514.19 | 83.24 | 430.95 | 431.85 | 170.74 | 0.00 | 0.00 | 0.00 |
August | 328.38 | 18.15 | 310.23 | 185.16 | 288.81 | 0.00 | 0.00 | 0.00 |
September | 183.31 | 0.18 | 183.13 | 22.73 | 613.08 | 0.00 | 0.00 | 0.00 |
October | 89.20 | 0.00 | 89.20 | 0.00 | 1104.55 | 0.00 | 0.00 | 0.00 |
November | 27.68 | 0.00 | 27.68 | 0.00 | 1756.30 | 0.00 | 0.00 | 0.00 |
December | 4.35 | 0.00 | 4.35 | 0.00 | 1866.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 232.74 | 26.64 | 206.09 | 117.84 | 968.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.35 | 0.00 | 4.35 | 0.00 | 138.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 612.70 | 135.92 | 476.78 | 491.28 | 1866.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.33 | 0.00 | 14.33 | 0.00 | 1754.52 | 0.00 | 0.00 | 0.00 |
February | 63.36 | 0.00 | 63.36 | 0.00 | 1620.92 | 0.00 | 0.00 | 0.00 |
March | 169.47 | 0.00 | 169.47 | 0.47 | 1301.66 | 0.00 | 0.00 | 0.00 |
April | 306.49 | 6.63 | 299.87 | 42.87 | 749.94 | 0.00 | 0.00 | 0.00 |
May | 469.40 | 74.17 | 395.22 | 231.06 | 301.80 | 0.00 | 0.00 | 0.00 |
June | 612.70 | 135.92 | 476.78 | 491.28 | 138.89 | 0.00 | 0.00 | 0.00 |
July | 514.19 | 83.24 | 430.95 | 431.85 | 170.74 | 0.00 | 0.00 | 0.00 |
August | 328.38 | 18.15 | 310.23 | 185.16 | 288.81 | 0.00 | 0.00 | 0.00 |
September | 183.31 | 0.18 | 183.13 | 22.73 | 613.08 | 0.00 | 0.00 | 0.00 |
October | 89.20 | 0.00 | 89.20 | 0.00 | 1104.55 | 0.00 | 0.00 | 0.00 |
November | 27.68 | 0.00 | 27.68 | 0.00 | 1756.30 | 0.00 | 0.00 | 0.00 |
December | 4.35 | 0.00 | 4.35 | 0.00 | 1866.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 232.74 | 26.64 | 206.09 | 117.84 | 968.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.35 | 0.00 | 4.35 | 0.00 | 138.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 612.70 | 135.92 | 476.78 | 491.28 | 1866.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.33 | 0.00 | 14.33 | 0.00 | 1754.52 | 0.00 | 0.00 | 0.00 |
February | 63.36 | 0.00 | 63.36 | 0.00 | 1620.92 | 0.00 | 0.00 | 0.00 |
March | 169.47 | 0.00 | 169.47 | 0.47 | 1301.66 | 0.00 | 0.00 | 0.00 |
April | 306.49 | 6.63 | 299.87 | 42.87 | 749.94 | 0.00 | 0.00 | 0.00 |
May | 469.40 | 74.17 | 395.22 | 231.06 | 301.80 | 0.00 | 0.00 | 0.00 |
June | 612.70 | 135.92 | 476.78 | 491.28 | 138.89 | 0.00 | 0.00 | 0.00 |
July | 514.19 | 83.24 | 430.95 | 431.85 | 170.74 | 0.00 | 0.00 | 0.00 |
August | 328.38 | 18.15 | 310.23 | 185.16 | 288.81 | 0.00 | 0.00 | 0.00 |
September | 183.31 | 0.18 | 183.13 | 22.73 | 613.08 | 0.00 | 0.00 | 0.00 |
October | 89.20 | 0.00 | 89.20 | 0.00 | 1104.55 | 0.00 | 0.00 | 0.00 |
November | 27.68 | 0.00 | 27.68 | 0.00 | 1756.30 | 0.00 | 0.00 | 0.00 |
December | 4.35 | 0.00 | 4.35 | 0.00 | 1866.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 232.74 | 26.64 | 206.09 | 117.84 | 968.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.35 | 0.00 | 4.35 | 0.00 | 138.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 612.70 | 135.92 | 476.78 | 491.28 | 1866.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.33 | 0.00 | 14.33 | 0.00 | 1754.52 | 0.00 | 0.00 | 0.00 |
February | 63.36 | 0.00 | 63.36 | 0.00 | 1620.92 | 0.00 | 0.00 | 0.00 |
March | 169.47 | 0.00 | 169.47 | 0.47 | 1301.66 | 0.00 | 0.00 | 0.00 |
April | 306.49 | 6.63 | 299.87 | 42.87 | 749.94 | 0.00 | 0.00 | 0.00 |
May | 469.40 | 74.17 | 395.22 | 231.06 | 301.80 | 0.00 | 0.00 | 0.00 |
June | 612.70 | 135.92 | 476.78 | 491.28 | 138.89 | 0.00 | 0.00 | 0.00 |
July | 514.19 | 83.24 | 430.95 | 431.85 | 170.74 | 0.00 | 0.00 | 0.00 |
August | 328.38 | 18.15 | 310.23 | 185.16 | 288.81 | 0.00 | 0.00 | 0.00 |
September | 183.31 | 0.18 | 183.13 | 22.73 | 613.08 | 0.00 | 0.00 | 0.00 |
October | 89.20 | 0.00 | 89.20 | 0.00 | 1104.55 | 0.00 | 0.00 | 0.00 |
November | 27.68 | 0.00 | 27.68 | 0.00 | 1756.30 | 0.00 | 0.00 | 0.00 |
December | 4.35 | 0.00 | 4.35 | 0.00 | 1866.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 232.74 | 26.64 | 206.09 | 117.84 | 968.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.35 | 0.00 | 4.35 | 0.00 | 138.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 612.70 | 135.92 | 476.78 | 491.28 | 1866.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.33 | 0.00 | 14.33 | 0.00 | 1754.45 | 0.00 | 0.00 | 0.00 |
February | 63.36 | 0.00 | 63.36 | 0.00 | 1620.85 | 0.00 | 0.00 | 0.00 |
March | 169.46 | 0.00 | 169.46 | 0.47 | 1301.61 | 0.00 | 0.00 | 0.00 |
April | 306.48 | 6.63 | 299.85 | 42.87 | 749.91 | 0.00 | 0.00 | 0.00 |
May | 469.38 | 74.17 | 395.21 | 231.05 | 301.79 | 0.00 | 0.00 | 0.00 |
June | 612.68 | 135.91 | 476.76 | 491.26 | 138.88 | 0.00 | 0.00 | 0.00 |
July | 514.17 | 83.23 | 430.94 | 431.84 | 170.73 | 0.00 | 0.00 | 0.00 |
August | 328.36 | 18.15 | 310.22 | 185.16 | 288.80 | 0.00 | 0.00 | 0.00 |
September | 183.30 | 0.18 | 183.13 | 22.73 | 613.06 | 0.00 | 0.00 | 0.00 |
October | 89.20 | 0.00 | 89.20 | 0.00 | 1104.51 | 0.00 | 0.00 | 0.00 |
November | 27.68 | 0.00 | 27.68 | 0.00 | 1756.23 | 0.00 | 0.00 | 0.00 |
December | 4.35 | 0.00 | 4.35 | 0.00 | 1866.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 232.73 | 26.64 | 206.09 | 117.84 | 968.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.35 | 0.00 | 4.35 | 0.00 | 138.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 612.68 | 135.91 | 476.76 | 491.26 | 1866.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 41.82 | 13.07 | 28.75 | 0.40 | 1897.30 | 0.00 | 0.00 | 0.00 |
February | 231.49 | 110.30 | 121.19 | 68.24 | 1630.16 | 0.00 | 0.00 | 0.00 |
March | 661.58 | 335.23 | 326.36 | 438.14 | 1236.94 | 0.00 | 0.00 | 0.00 |
April | 909.71 | 460.65 | 449.06 | 689.42 | 700.15 | 0.00 | 0.00 | 0.00 |
May | 1322.16 | 745.13 | 577.03 | 1321.37 | 338.96 | 0.00 | 0.00 | 0.00 |
June | 1215.64 | 566.84 | 648.80 | 1286.30 | 167.21 | 0.00 | 0.00 | 0.00 |
July | 1154.95 | 559.89 | 595.06 | 1277.86 | 189.90 | 0.00 | 0.00 | 0.00 |
August | 914.99 | 445.55 | 469.44 | 933.79 | 291.78 | 0.00 | 0.00 | 0.00 |
September | 565.75 | 247.88 | 317.87 | 432.34 | 590.68 | 0.00 | 0.00 | 0.00 |
October | 298.52 | 119.72 | 178.80 | 151.41 | 1092.30 | 0.00 | 0.00 | 0.00 |
November | 63.34 | 22.02 | 41.32 | 0.98 | 1883.15 | 0.00 | 0.00 | 0.00 |
December | 9.04 | 2.14 | 6.90 | 0.00 | 2040.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 618.11 | 303.70 | 314.41 | 553.41 | 1001.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.04 | 2.14 | 6.90 | 0.00 | 167.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1322.16 | 745.13 | 648.80 | 1321.37 | 2040.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 41.82 | 13.07 | 28.75 | 0.40 | 1897.30 | 0.00 | 0.00 | 0.00 |
February | 231.49 | 110.30 | 121.19 | 68.24 | 1630.16 | 0.00 | 0.00 | 0.00 |
March | 661.58 | 335.23 | 326.36 | 438.14 | 1236.94 | 0.00 | 0.00 | 0.00 |
April | 909.71 | 460.65 | 449.06 | 689.42 | 700.15 | 0.00 | 0.00 | 0.00 |
May | 1322.16 | 745.13 | 577.03 | 1321.37 | 338.96 | 0.00 | 0.00 | 0.00 |
June | 1215.64 | 566.84 | 648.80 | 1286.30 | 167.21 | 0.00 | 0.00 | 0.00 |
July | 1154.95 | 559.89 | 595.06 | 1277.86 | 189.90 | 0.00 | 0.00 | 0.00 |
August | 914.99 | 445.55 | 469.44 | 933.79 | 291.78 | 0.00 | 0.00 | 0.00 |
September | 565.75 | 247.88 | 317.87 | 432.34 | 590.68 | 0.00 | 0.00 | 0.00 |
October | 298.52 | 119.72 | 178.80 | 151.41 | 1092.30 | 0.00 | 0.00 | 0.00 |
November | 63.34 | 22.02 | 41.32 | 0.98 | 1883.15 | 0.00 | 0.00 | 0.00 |
December | 9.04 | 2.14 | 6.90 | 0.00 | 2040.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 618.11 | 303.70 | 314.41 | 553.41 | 1001.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.04 | 2.14 | 6.90 | 0.00 | 167.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1322.16 | 745.13 | 648.80 | 1321.37 | 2040.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 41.82 | 13.07 | 28.75 | 0.40 | 1897.27 | 0.00 | 0.00 | 0.00 |
February | 231.49 | 110.29 | 121.19 | 68.24 | 1630.13 | 0.00 | 0.00 | 0.00 |
March | 661.57 | 335.22 | 326.35 | 438.13 | 1236.92 | 0.00 | 0.00 | 0.00 |
April | 909.70 | 460.64 | 449.06 | 689.41 | 700.13 | 0.00 | 0.00 | 0.00 |
May | 1322.14 | 745.12 | 577.02 | 1321.35 | 338.95 | 0.00 | 0.00 | 0.00 |
June | 1215.62 | 566.83 | 648.79 | 1286.27 | 167.20 | 0.00 | 0.00 | 0.00 |
July | 1154.93 | 559.88 | 595.05 | 1277.84 | 189.90 | 0.00 | 0.00 | 0.00 |
August | 914.98 | 445.54 | 469.43 | 933.77 | 291.78 | 0.00 | 0.00 | 0.00 |
September | 565.74 | 247.87 | 317.87 | 432.33 | 590.67 | 0.00 | 0.00 | 0.00 |
October | 298.52 | 119.72 | 178.79 | 151.40 | 1092.28 | 0.00 | 0.00 | 0.00 |
November | 63.34 | 22.02 | 41.32 | 0.98 | 1883.12 | 0.00 | 0.00 | 0.00 |
December | 9.04 | 2.14 | 6.90 | 0.00 | 2040.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 618.10 | 303.70 | 314.40 | 553.40 | 1001.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.04 | 2.14 | 6.90 | 0.00 | 167.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1322.14 | 745.12 | 648.79 | 1321.35 | 2040.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 172.67 | 114.00 | 58.67 | 62.23 | 1576.62 | 0.00 | 0.00 | 0.00 |
February | 593.62 | 413.50 | 180.12 | 385.28 | 1280.58 | 0.00 | 0.00 | 0.00 |
March | 1017.70 | 690.31 | 327.38 | 843.35 | 1002.53 | 0.00 | 0.00 | 0.00 |
April | 1239.50 | 771.04 | 468.46 | 1238.13 | 669.66 | 0.00 | 0.00 | 0.00 |
May | 1020.74 | 528.20 | 492.54 | 1080.63 | 367.16 | 0.00 | 0.00 | 0.00 |
June | 931.78 | 381.02 | 550.76 | 1027.63 | 202.95 | 0.00 | 0.00 | 0.00 |
July | 897.95 | 390.35 | 507.60 | 1030.63 | 211.79 | 0.00 | 0.00 | 0.00 |
August | 930.76 | 512.75 | 418.01 | 1038.80 | 301.93 | 0.00 | 0.00 | 0.00 |
September | 753.17 | 453.82 | 299.34 | 720.30 | 523.80 | 0.00 | 0.00 | 0.00 |
October | 543.15 | 345.08 | 198.07 | 402.05 | 872.93 | 0.00 | 0.00 | 0.00 |
November | 291.69 | 204.03 | 87.67 | 124.74 | 1495.06 | 0.00 | 0.00 | 0.00 |
December | 51.82 | 36.60 | 15.22 | 2.56 | 1764.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 703.52 | 402.77 | 300.75 | 664.05 | 853.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.82 | 36.60 | 15.22 | 2.56 | 202.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1239.50 | 771.04 | 550.76 | 1238.13 | 1764.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 172.67 | 114.00 | 58.67 | 62.23 | 1576.62 | 0.00 | 0.00 | 0.00 |
February | 593.62 | 413.50 | 180.12 | 385.28 | 1280.58 | 0.00 | 0.00 | 0.00 |
March | 1017.69 | 690.31 | 327.38 | 843.35 | 1002.53 | 0.00 | 0.00 | 0.00 |
April | 1239.50 | 771.04 | 468.46 | 1238.13 | 669.66 | 0.00 | 0.00 | 0.00 |
May | 1020.74 | 528.20 | 492.54 | 1080.63 | 367.16 | 0.00 | 0.00 | 0.00 |
June | 931.78 | 381.02 | 550.76 | 1027.63 | 202.95 | 0.00 | 0.00 | 0.00 |
July | 897.95 | 390.35 | 507.60 | 1030.63 | 211.79 | 0.00 | 0.00 | 0.00 |
August | 930.76 | 512.75 | 418.01 | 1038.79 | 301.93 | 0.00 | 0.00 | 0.00 |
September | 753.17 | 453.82 | 299.34 | 720.30 | 523.80 | 0.00 | 0.00 | 0.00 |
October | 543.15 | 345.08 | 198.07 | 402.05 | 872.93 | 0.00 | 0.00 | 0.00 |
November | 291.69 | 204.03 | 87.67 | 124.74 | 1495.06 | 0.00 | 0.00 | 0.00 |
December | 51.82 | 36.60 | 15.22 | 2.56 | 1764.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 703.52 | 402.77 | 300.75 | 664.05 | 853.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.82 | 36.60 | 15.22 | 2.56 | 202.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1239.50 | 771.04 | 550.76 | 1238.13 | 1764.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 172.67 | 114.00 | 58.67 | 62.23 | 1576.62 | 0.00 | 0.00 | 0.00 |
February | 593.62 | 413.50 | 180.12 | 385.28 | 1280.58 | 0.00 | 0.00 | 0.00 |
March | 1017.70 | 690.31 | 327.38 | 843.35 | 1002.53 | 0.00 | 0.00 | 0.00 |
April | 1239.50 | 771.04 | 468.46 | 1238.13 | 669.66 | 0.00 | 0.00 | 0.00 |
May | 1020.74 | 528.20 | 492.54 | 1080.63 | 367.16 | 0.00 | 0.00 | 0.00 |
June | 931.78 | 381.02 | 550.76 | 1027.63 | 202.95 | 0.00 | 0.00 | 0.00 |
July | 897.95 | 390.35 | 507.60 | 1030.63 | 211.79 | 0.00 | 0.00 | 0.00 |
August | 930.76 | 512.75 | 418.01 | 1038.80 | 301.93 | 0.00 | 0.00 | 0.00 |
September | 753.17 | 453.82 | 299.34 | 720.30 | 523.80 | 0.00 | 0.00 | 0.00 |
October | 543.15 | 345.08 | 198.07 | 402.05 | 872.93 | 0.00 | 0.00 | 0.00 |
November | 291.69 | 204.03 | 87.67 | 124.74 | 1495.06 | 0.00 | 0.00 | 0.00 |
December | 51.82 | 36.60 | 15.22 | 2.56 | 1764.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 703.52 | 402.77 | 300.75 | 664.05 | 853.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.82 | 36.60 | 15.22 | 2.56 | 202.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1239.50 | 771.04 | 550.76 | 1238.13 | 1764.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 172.67 | 114.00 | 58.67 | 62.23 | 1576.62 | 0.00 | 0.00 | 0.00 |
February | 593.62 | 413.50 | 180.12 | 385.28 | 1280.58 | 0.00 | 0.00 | 0.00 |
March | 1017.69 | 690.31 | 327.38 | 843.35 | 1002.53 | 0.00 | 0.00 | 0.00 |
April | 1239.50 | 771.04 | 468.46 | 1238.13 | 669.66 | 0.00 | 0.00 | 0.00 |
May | 1020.74 | 528.20 | 492.54 | 1080.63 | 367.16 | 0.00 | 0.00 | 0.00 |
June | 931.78 | 381.02 | 550.76 | 1027.63 | 202.95 | 0.00 | 0.00 | 0.00 |
July | 897.95 | 390.35 | 507.60 | 1030.63 | 211.79 | 0.00 | 0.00 | 0.00 |
August | 930.76 | 512.75 | 418.01 | 1038.79 | 301.93 | 0.00 | 0.00 | 0.00 |
September | 753.17 | 453.82 | 299.34 | 720.30 | 523.80 | 0.00 | 0.00 | 0.00 |
October | 543.15 | 345.08 | 198.07 | 402.05 | 872.93 | 0.00 | 0.00 | 0.00 |
November | 291.69 | 204.03 | 87.67 | 124.74 | 1495.06 | 0.00 | 0.00 | 0.00 |
December | 51.82 | 36.60 | 15.22 | 2.56 | 1764.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 703.52 | 402.77 | 300.75 | 664.05 | 853.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.82 | 36.60 | 15.22 | 2.56 | 202.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1239.50 | 771.04 | 550.76 | 1238.13 | 1764.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 172.66 | 114.00 | 58.66 | 62.23 | 1576.56 | 0.00 | 0.00 | 0.00 |
February | 593.60 | 413.48 | 180.11 | 385.27 | 1280.52 | 0.00 | 0.00 | 0.00 |
March | 1017.65 | 690.28 | 327.37 | 843.32 | 1002.49 | 0.00 | 0.00 | 0.00 |
April | 1239.45 | 771.01 | 468.44 | 1238.08 | 669.64 | 0.00 | 0.00 | 0.00 |
May | 1020.70 | 528.18 | 492.52 | 1080.59 | 367.15 | 0.00 | 0.00 | 0.00 |
June | 931.74 | 381.00 | 550.74 | 1027.59 | 202.94 | 0.00 | 0.00 | 0.00 |
July | 897.92 | 390.34 | 507.58 | 1030.59 | 211.78 | 0.00 | 0.00 | 0.00 |
August | 930.72 | 512.73 | 417.99 | 1038.75 | 301.92 | 0.00 | 0.00 | 0.00 |
September | 753.14 | 453.81 | 299.33 | 720.27 | 523.78 | 0.00 | 0.00 | 0.00 |
October | 543.13 | 345.07 | 198.06 | 402.03 | 872.89 | 0.00 | 0.00 | 0.00 |
November | 291.68 | 204.02 | 87.66 | 124.74 | 1495.00 | 0.00 | 0.00 | 0.00 |
December | 51.81 | 36.59 | 15.22 | 2.56 | 1764.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 703.49 | 402.76 | 300.73 | 664.03 | 853.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.81 | 36.59 | 15.22 | 2.56 | 202.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1239.45 | 771.01 | 550.74 | 1238.08 | 1764.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.02 | 3.88 | 18.13 | 0.00 | 1982.37 | 0.00 | 0.00 | 0.00 |
February | 130.02 | 45.04 | 84.98 | 6.39 | 1766.49 | 0.00 | 0.00 | 0.00 |
March | 390.84 | 167.91 | 222.94 | 148.60 | 1377.57 | 0.00 | 0.00 | 0.00 |
April | 928.81 | 481.76 | 447.06 | 737.87 | 833.79 | 0.00 | 0.00 | 0.00 |
May | 903.05 | 411.69 | 491.36 | 802.17 | 412.12 | 0.00 | 0.00 | 0.00 |
June | 989.44 | 422.24 | 567.21 | 1004.77 | 237.34 | 0.00 | 0.00 | 0.00 |
July | 827.80 | 313.41 | 514.38 | 843.56 | 259.57 | 0.00 | 0.00 | 0.00 |
August | 680.39 | 288.35 | 392.05 | 625.62 | 382.00 | 0.00 | 0.00 | 0.00 |
September | 411.58 | 172.38 | 239.20 | 264.18 | 667.02 | 0.00 | 0.00 | 0.00 |
October | 160.96 | 48.24 | 112.71 | 31.43 | 1203.90 | 0.00 | 0.00 | 0.00 |
November | 64.31 | 23.25 | 41.05 | 1.48 | 1976.11 | 0.00 | 0.00 | 0.00 |
December | 5.78 | 0.60 | 5.18 | 0.00 | 2171.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 460.77 | 198.65 | 262.12 | 373.75 | 1102.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.78 | 0.60 | 5.18 | 0.00 | 237.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 989.44 | 481.76 | 567.21 | 1004.77 | 2171.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.02 | 3.88 | 18.13 | 0.00 | 1982.37 | 0.00 | 0.00 | 0.00 |
February | 130.02 | 45.04 | 84.98 | 6.39 | 1766.49 | 0.00 | 0.00 | 0.00 |
March | 390.84 | 167.91 | 222.94 | 148.60 | 1377.57 | 0.00 | 0.00 | 0.00 |
April | 928.81 | 481.76 | 447.06 | 737.87 | 833.79 | 0.00 | 0.00 | 0.00 |
May | 903.05 | 411.69 | 491.36 | 802.17 | 412.12 | 0.00 | 0.00 | 0.00 |
June | 989.44 | 422.24 | 567.21 | 1004.77 | 237.34 | 0.00 | 0.00 | 0.00 |
July | 827.80 | 313.41 | 514.38 | 843.56 | 259.57 | 0.00 | 0.00 | 0.00 |
August | 680.39 | 288.35 | 392.05 | 625.62 | 382.00 | 0.00 | 0.00 | 0.00 |
September | 411.58 | 172.38 | 239.20 | 264.18 | 667.02 | 0.00 | 0.00 | 0.00 |
October | 160.96 | 48.24 | 112.71 | 31.43 | 1203.90 | 0.00 | 0.00 | 0.00 |
November | 64.31 | 23.25 | 41.05 | 1.48 | 1976.11 | 0.00 | 0.00 | 0.00 |
December | 5.78 | 0.60 | 5.18 | 0.00 | 2171.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 460.77 | 198.65 | 262.12 | 373.75 | 1102.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.78 | 0.60 | 5.18 | 0.00 | 237.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 989.44 | 481.76 | 567.21 | 1004.77 | 2171.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.02 | 3.88 | 18.13 | 0.00 | 1982.33 | 0.00 | 0.00 | 0.00 |
February | 130.02 | 45.04 | 84.98 | 6.39 | 1766.46 | 0.00 | 0.00 | 0.00 |
March | 390.84 | 167.90 | 222.93 | 148.60 | 1377.55 | 0.00 | 0.00 | 0.00 |
April | 928.80 | 481.75 | 447.05 | 737.86 | 833.78 | 0.00 | 0.00 | 0.00 |
May | 903.03 | 411.68 | 491.35 | 802.15 | 412.11 | 0.00 | 0.00 | 0.00 |
June | 989.42 | 422.23 | 567.20 | 1004.75 | 237.34 | 0.00 | 0.00 | 0.00 |
July | 827.78 | 313.41 | 514.37 | 843.54 | 259.57 | 0.00 | 0.00 | 0.00 |
August | 680.38 | 288.34 | 392.04 | 625.61 | 381.99 | 0.00 | 0.00 | 0.00 |
September | 411.57 | 172.38 | 239.19 | 264.17 | 667.00 | 0.00 | 0.00 | 0.00 |
October | 160.96 | 48.24 | 112.71 | 31.42 | 1203.88 | 0.00 | 0.00 | 0.00 |
November | 64.31 | 23.25 | 41.05 | 1.48 | 1976.08 | 0.00 | 0.00 | 0.00 |
December | 5.78 | 0.60 | 5.18 | 0.00 | 2171.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 460.76 | 198.64 | 262.12 | 373.75 | 1102.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.78 | 0.60 | 5.18 | 0.00 | 237.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 989.42 | 481.75 | 567.20 | 1004.75 | 2171.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 71.67 | 0.00 | 71.67 | 0.00 | 8632.27 | 0.00 | 0.00 | 0.00 |
February | 316.81 | 0.00 | 316.81 | 0.00 | 7945.19 | 0.00 | 0.00 | 0.00 |
March | 847.33 | 0.00 | 847.33 | 7.38 | 6293.06 | 0.00 | 0.00 | 0.00 |
April | 1532.45 | 33.14 | 1499.31 | 278.09 | 3443.47 | 0.00 | 0.00 | 0.00 |
May | 2346.96 | 370.87 | 1976.10 | 1252.32 | 1400.37 | 0.00 | 0.00 | 0.00 |
June | 3063.48 | 679.59 | 2383.89 | 2501.36 | 649.89 | 0.00 | 0.00 | 0.00 |
July | 2570.93 | 416.19 | 2154.75 | 2228.09 | 790.44 | 0.00 | 0.00 | 0.00 |
August | 1641.87 | 90.75 | 1551.12 | 1018.36 | 1290.24 | 0.00 | 0.00 | 0.00 |
September | 916.55 | 0.89 | 915.66 | 154.66 | 2813.17 | 0.00 | 0.00 | 0.00 |
October | 446.00 | 0.00 | 446.00 | 2.02 | 5191.88 | 0.00 | 0.00 | 0.00 |
November | 138.41 | 0.00 | 138.41 | 0.00 | 8443.14 | 0.00 | 0.00 | 0.00 |
December | 21.74 | 0.00 | 21.74 | 0.00 | 9042.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1163.67 | 133.21 | 1030.46 | 624.05 | 4643.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.74 | 0.00 | 21.74 | 0.00 | 649.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3063.48 | 679.59 | 2383.89 | 2501.36 | 9042.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 125.47 | 39.22 | 86.25 | 1.51 | 5582.68 | 0.00 | 0.00 | 0.00 |
February | 694.47 | 330.89 | 363.58 | 209.99 | 4795.29 | 0.00 | 0.00 | 0.00 |
March | 1984.73 | 1005.67 | 979.06 | 1318.03 | 3638.81 | 0.00 | 0.00 | 0.00 |
April | 2729.11 | 1381.93 | 1347.18 | 2068.40 | 2009.68 | 0.00 | 0.00 | 0.00 |
May | 3966.44 | 2235.36 | 1731.08 | 3928.48 | 981.78 | 0.00 | 0.00 | 0.00 |
June | 3646.89 | 1700.51 | 1946.38 | 3828.84 | 482.30 | 0.00 | 0.00 | 0.00 |
July | 3464.81 | 1679.64 | 1785.17 | 3804.39 | 552.80 | 0.00 | 0.00 | 0.00 |
August | 2744.95 | 1336.64 | 1408.31 | 2788.49 | 839.14 | 0.00 | 0.00 | 0.00 |
September | 1697.23 | 743.62 | 953.61 | 1294.43 | 1696.72 | 0.00 | 0.00 | 0.00 |
October | 895.55 | 359.17 | 536.39 | 464.16 | 3118.67 | 0.00 | 0.00 | 0.00 |
November | 190.03 | 66.05 | 123.97 | 2.92 | 5439.04 | 0.00 | 0.00 | 0.00 |
December | 27.12 | 6.41 | 20.71 | 0.00 | 5940.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1854.31 | 911.11 | 943.21 | 1652.53 | 2913.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.12 | 6.41 | 20.71 | 0.00 | 482.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3966.44 | 2235.36 | 1946.38 | 3928.48 | 5940.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 863.34 | 570.01 | 293.33 | 310.42 | 7839.08 | 0.00 | 0.00 | 0.00 |
February | 2968.08 | 2067.48 | 900.60 | 1929.48 | 6358.34 | 0.00 | 0.00 | 0.00 |
March | 5088.42 | 3451.51 | 1636.90 | 4183.60 | 4977.71 | 0.00 | 0.00 | 0.00 |
April | 6197.42 | 3855.15 | 2342.26 | 6143.04 | 3284.90 | 0.00 | 0.00 | 0.00 |
May | 5103.62 | 2640.97 | 2462.65 | 5350.15 | 1811.71 | 0.00 | 0.00 | 0.00 |
June | 4658.85 | 1905.07 | 2753.78 | 5106.09 | 985.55 | 0.00 | 0.00 | 0.00 |
July | 4489.72 | 1951.74 | 2537.97 | 5133.81 | 1025.35 | 0.00 | 0.00 | 0.00 |
August | 4653.75 | 2563.72 | 2090.02 | 5177.14 | 1456.78 | 0.00 | 0.00 | 0.00 |
September | 3765.79 | 2269.10 | 1496.70 | 3580.82 | 2585.96 | 0.00 | 0.00 | 0.00 |
October | 2715.70 | 1725.38 | 990.33 | 2013.54 | 4270.89 | 0.00 | 0.00 | 0.00 |
November | 1458.46 | 1020.13 | 438.32 | 636.49 | 7305.25 | 0.00 | 0.00 | 0.00 |
December | 259.08 | 182.98 | 76.10 | 13.09 | 8693.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3517.54 | 2013.83 | 1503.71 | 3303.16 | 4206.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 259.08 | 182.98 | 76.10 | 13.09 | 985.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6197.42 | 3855.15 | 2753.78 | 6143.04 | 8693.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.05 | 11.65 | 54.39 | 0.00 | 5734.69 | 0.00 | 0.00 | 0.00 |
February | 390.05 | 135.12 | 254.93 | 23.10 | 5061.83 | 0.00 | 0.00 | 0.00 |
March | 1172.52 | 503.71 | 668.81 | 466.38 | 3875.11 | 0.00 | 0.00 | 0.00 |
April | 2786.41 | 1445.26 | 1341.16 | 2285.09 | 2227.70 | 0.00 | 0.00 | 0.00 |
May | 2709.12 | 1235.06 | 1474.05 | 2454.10 | 1144.02 | 0.00 | 0.00 | 0.00 |
June | 2968.29 | 1266.69 | 1701.60 | 3053.93 | 645.92 | 0.00 | 0.00 | 0.00 |
July | 2483.36 | 940.23 | 1543.13 | 2609.03 | 673.35 | 0.00 | 0.00 | 0.00 |
August | 2041.16 | 865.04 | 1176.12 | 1970.21 | 962.55 | 0.00 | 0.00 | 0.00 |
September | 1234.73 | 517.15 | 717.58 | 831.40 | 1816.51 | 0.00 | 0.00 | 0.00 |
October | 482.87 | 144.73 | 338.14 | 104.89 | 3329.18 | 0.00 | 0.00 | 0.00 |
November | 192.93 | 69.76 | 123.16 | 5.14 | 5505.64 | 0.00 | 0.00 | 0.00 |
December | 17.33 | 1.79 | 15.54 | 0.00 | 6075.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1382.29 | 595.94 | 786.35 | 1155.22 | 3077.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.33 | 1.79 | 15.54 | 0.00 | 645.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2968.29 | 1445.26 | 1701.60 | 3053.93 | 6075.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 71.67 | 0.00 | 71.67 | 0.00 | 8475.51 | 0.00 | 0.00 | 0.00 |
February | 316.81 | 0.00 | 316.81 | 0.00 | 7760.27 | 0.00 | 0.00 | 0.00 |
March | 847.33 | 0.00 | 847.33 | 12.51 | 6093.40 | 0.00 | 0.00 | 0.00 |
April | 1532.45 | 33.14 | 1499.31 | 319.91 | 3235.97 | 0.00 | 0.00 | 0.00 |
May | 2346.96 | 370.87 | 1976.10 | 1384.46 | 1273.25 | 0.00 | 0.00 | 0.00 |
June | 3063.48 | 679.59 | 2383.89 | 2589.72 | 598.06 | 0.00 | 0.00 | 0.00 |
July | 2570.93 | 416.19 | 2154.75 | 2308.87 | 729.28 | 0.00 | 0.00 | 0.00 |
August | 1641.87 | 90.75 | 1551.12 | 1099.11 | 1174.08 | 0.00 | 0.00 | 0.00 |
September | 916.55 | 0.89 | 915.66 | 196.66 | 2541.28 | 0.00 | 0.00 | 0.00 |
October | 446.00 | 0.00 | 446.00 | 8.84 | 4900.39 | 0.00 | 0.00 | 0.00 |
November | 138.41 | 0.00 | 138.41 | 0.00 | 8250.15 | 0.00 | 0.00 | 0.00 |
December | 21.74 | 0.00 | 21.74 | 0.00 | 8876.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1163.67 | 133.21 | 1030.46 | 664.15 | 4474.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.74 | 0.00 | 21.74 | 0.00 | 598.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3063.48 | 679.59 | 2383.89 | 2589.72 | 8876.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 125.47 | 39.22 | 86.25 | 1.04 | 5518.70 | 0.00 | 0.00 | 0.00 |
February | 694.47 | 330.89 | 363.58 | 218.85 | 4690.81 | 0.00 | 0.00 | 0.00 |
March | 1984.73 | 1005.67 | 979.06 | 1355.70 | 3499.13 | 0.00 | 0.00 | 0.00 |
April | 2729.11 | 1381.93 | 1347.18 | 2130.19 | 1887.82 | 0.00 | 0.00 | 0.00 |
May | 3966.44 | 2235.36 | 1731.08 | 3982.78 | 919.08 | 0.00 | 0.00 | 0.00 |
June | 3646.89 | 1700.51 | 1946.38 | 3846.26 | 459.75 | 0.00 | 0.00 | 0.00 |
July | 3464.81 | 1679.64 | 1785.17 | 3821.08 | 525.98 | 0.00 | 0.00 | 0.00 |
August | 2744.95 | 1336.64 | 1408.31 | 2824.28 | 787.40 | 0.00 | 0.00 | 0.00 |
September | 1697.23 | 743.62 | 953.61 | 1357.54 | 1533.41 | 0.00 | 0.00 | 0.00 |
October | 895.55 | 359.17 | 536.39 | 491.67 | 2930.91 | 0.00 | 0.00 | 0.00 |
November | 190.03 | 66.05 | 123.97 | 3.05 | 5346.13 | 0.00 | 0.00 | 0.00 |
December | 27.12 | 6.41 | 20.71 | 0.00 | 5881.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1854.31 | 911.11 | 943.21 | 1679.48 | 2822.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.12 | 6.41 | 20.71 | 0.00 | 459.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3966.44 | 2235.36 | 1946.38 | 3982.78 | 5881.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 863.34 | 570.01 | 293.33 | 318.09 | 7676.83 | 0.00 | 0.00 | 0.00 |
February | 2968.08 | 2067.48 | 900.60 | 1973.62 | 6164.10 | 0.00 | 0.00 | 0.00 |
March | 5088.42 | 3451.51 | 1636.90 | 4238.52 | 4767.76 | 0.00 | 0.00 | 0.00 |
April | 6197.42 | 3855.15 | 2342.26 | 6196.28 | 3085.60 | 0.00 | 0.00 | 0.00 |
May | 5103.62 | 2640.97 | 2462.65 | 5381.71 | 1678.07 | 0.00 | 0.00 | 0.00 |
June | 4658.85 | 1905.07 | 2753.78 | 5107.82 | 932.21 | 0.00 | 0.00 | 0.00 |
July | 4489.72 | 1951.74 | 2537.97 | 5139.64 | 971.07 | 0.00 | 0.00 | 0.00 |
August | 4653.75 | 2563.72 | 2090.02 | 5194.98 | 1368.47 | 0.00 | 0.00 | 0.00 |
September | 3765.79 | 2269.10 | 1496.70 | 3642.32 | 2356.72 | 0.00 | 0.00 | 0.00 |
October | 2715.70 | 1725.38 | 990.33 | 2075.42 | 4002.11 | 0.00 | 0.00 | 0.00 |
November | 1458.46 | 1020.13 | 438.32 | 653.50 | 7108.25 | 0.00 | 0.00 | 0.00 |
December | 259.08 | 182.98 | 76.10 | 13.59 | 8521.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3517.54 | 2013.83 | 1503.71 | 3332.82 | 4042.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 259.08 | 182.98 | 76.10 | 13.59 | 932.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6197.42 | 3855.15 | 2753.78 | 6196.28 | 8521.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.05 | 11.65 | 54.39 | 0.00 | 5632.37 | 0.00 | 0.00 | 0.00 |
February | 390.05 | 135.12 | 254.93 | 24.66 | 4949.20 | 0.00 | 0.00 | 0.00 |
March | 1172.52 | 503.71 | 668.81 | 473.52 | 3754.74 | 0.00 | 0.00 | 0.00 |
April | 2786.41 | 1445.26 | 1341.16 | 2302.27 | 2105.35 | 0.00 | 0.00 | 0.00 |
May | 2709.12 | 1235.06 | 1474.05 | 2473.86 | 1067.35 | 0.00 | 0.00 | 0.00 |
June | 2968.29 | 1266.69 | 1701.60 | 3055.17 | 614.44 | 0.00 | 0.00 | 0.00 |
July | 2483.36 | 940.23 | 1543.13 | 2612.74 | 641.06 | 0.00 | 0.00 | 0.00 |
August | 2041.16 | 865.04 | 1176.12 | 1981.11 | 909.42 | 0.00 | 0.00 | 0.00 |
September | 1234.73 | 517.15 | 717.58 | 850.84 | 1681.30 | 0.00 | 0.00 | 0.00 |
October | 482.87 | 144.73 | 338.14 | 113.24 | 3167.76 | 0.00 | 0.00 | 0.00 |
November | 192.93 | 69.76 | 123.16 | 5.48 | 5385.46 | 0.00 | 0.00 | 0.00 |
December | 17.33 | 1.79 | 15.54 | 0.00 | 5968.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1382.29 | 595.94 | 786.35 | 1162.72 | 2979.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.33 | 1.79 | 15.54 | 0.00 | 614.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2968.29 | 1445.26 | 1701.60 | 3055.17 | 5968.82 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38392015.88 | 0.00 | 38392015.88 | 0.00 | 0.469931E+10 |
February | 0.153287E+09 | 0.00 | 0.153287E+09 | 0.00 | 0.392132E+10 |
March | 0.453904E+09 | 0.00 | 0.453904E+09 | 1247162.18 | 0.348637E+10 |
April | 0.794433E+09 | 17182439.81 | 0.777251E+09 | 0.111130E+09 | 0.194385E+10 |
May | 0.125724E+10 | 0.198669E+09 | 0.105857E+10 | 0.618883E+09 | 0.808342E+09 |
June | 0.158813E+10 | 0.352305E+09 | 0.123582E+10 | 0.127341E+10 | 0.359992E+09 |
July | 0.137721E+10 | 0.222945E+09 | 0.115427E+10 | 0.115667E+10 | 0.457300E+09 |
August | 0.879528E+09 | 48612644.47 | 0.830915E+09 | 0.495942E+09 | 0.773561E+09 |
September | 0.475144E+09 | 462949.17 | 0.474681E+09 | 58923754.61 | 0.158910E+10 |
October | 0.238914E+09 | 0.00 | 0.238914E+09 | 0.00 | 0.295843E+10 |
November | 71751941.49 | 0.00 | 71751941.49 | 0.00 | 0.455233E+10 |
December | 11646133.21 | 0.00 | 11646133.21 | 0.00 | 0.499901E+10 |
Annual Sum or Average | 0.733958E+10 | 0.840178E+09 | 0.649940E+10 | 0.371621E+10 | 0.305489E+11 |
Minimum of Months | 11646133.21 | 0.00 | 11646133.21 | 0.00 | 0.359992E+09 |
Maximum of Months | 0.158813E+10 | 0.352305E+09 | 0.123582E+10 | 0.127341E+10 | 0.499901E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38391980.36 | 0.00 | 38391980.36 | 0.00 | 0.469931E+10 |
February | 0.153287E+09 | 0.00 | 0.153287E+09 | 0.00 | 0.392132E+10 |
March | 0.453904E+09 | 0.00 | 0.453904E+09 | 1247147.90 | 0.348637E+10 |
April | 0.794433E+09 | 17182419.19 | 0.777250E+09 | 0.111129E+09 | 0.194385E+10 |
May | 0.125724E+10 | 0.198669E+09 | 0.105857E+10 | 0.618881E+09 | 0.808343E+09 |
June | 0.158813E+10 | 0.352305E+09 | 0.123582E+10 | 0.127340E+10 | 0.359992E+09 |
July | 0.137721E+10 | 0.222945E+09 | 0.115427E+10 | 0.115667E+10 | 0.457300E+09 |
August | 0.879527E+09 | 48612586.14 | 0.830914E+09 | 0.495942E+09 | 0.773561E+09 |
September | 0.475144E+09 | 462948.61 | 0.474681E+09 | 58923568.52 | 0.158911E+10 |
October | 0.238914E+09 | 0.00 | 0.238914E+09 | 0.00 | 0.295843E+10 |
November | 71751875.10 | 0.00 | 71751875.10 | 0.00 | 0.455233E+10 |
December | 11646121.96 | 0.00 | 11646121.96 | 0.00 | 0.499901E+10 |
Annual Sum or Average | 0.733957E+10 | 0.840177E+09 | 0.649940E+10 | 0.371620E+10 | 0.305489E+11 |
Minimum of Months | 11646121.96 | 0.00 | 11646121.96 | 0.00 | 0.359992E+09 |
Maximum of Months | 0.158813E+10 | 0.352305E+09 | 0.123582E+10 | 0.127340E+10 | 0.499901E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38392015.88 | 0.00 | 38392015.88 | 0.00 | 0.469931E+10 |
February | 0.153287E+09 | 0.00 | 0.153287E+09 | 0.00 | 0.392132E+10 |
March | 0.453904E+09 | 0.00 | 0.453904E+09 | 1247162.18 | 0.348637E+10 |
April | 0.794433E+09 | 17182439.81 | 0.777251E+09 | 0.111130E+09 | 0.194385E+10 |
May | 0.125724E+10 | 0.198669E+09 | 0.105857E+10 | 0.618883E+09 | 0.808342E+09 |
June | 0.158813E+10 | 0.352305E+09 | 0.123582E+10 | 0.127341E+10 | 0.359992E+09 |
July | 0.137721E+10 | 0.222945E+09 | 0.115427E+10 | 0.115667E+10 | 0.457300E+09 |
August | 0.879528E+09 | 48612644.47 | 0.830915E+09 | 0.495942E+09 | 0.773561E+09 |
September | 0.475144E+09 | 462949.17 | 0.474681E+09 | 58923754.61 | 0.158910E+10 |
October | 0.238914E+09 | 0.00 | 0.238914E+09 | 0.00 | 0.295843E+10 |
November | 71751941.49 | 0.00 | 71751941.49 | 0.00 | 0.455233E+10 |
December | 11646133.21 | 0.00 | 11646133.21 | 0.00 | 0.499901E+10 |
Annual Sum or Average | 0.733958E+10 | 0.840178E+09 | 0.649940E+10 | 0.371621E+10 | 0.305489E+11 |
Minimum of Months | 11646133.21 | 0.00 | 11646133.21 | 0.00 | 0.359992E+09 |
Maximum of Months | 0.158813E+10 | 0.352305E+09 | 0.123582E+10 | 0.127341E+10 | 0.499901E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38391980.36 | 0.00 | 38391980.36 | 0.00 | 0.469931E+10 |
February | 0.153287E+09 | 0.00 | 0.153287E+09 | 0.00 | 0.392132E+10 |
March | 0.453904E+09 | 0.00 | 0.453904E+09 | 1247147.90 | 0.348637E+10 |
April | 0.794433E+09 | 17182419.19 | 0.777250E+09 | 0.111129E+09 | 0.194385E+10 |
May | 0.125724E+10 | 0.198669E+09 | 0.105857E+10 | 0.618881E+09 | 0.808343E+09 |
June | 0.158813E+10 | 0.352305E+09 | 0.123582E+10 | 0.127340E+10 | 0.359992E+09 |
July | 0.137721E+10 | 0.222945E+09 | 0.115427E+10 | 0.115667E+10 | 0.457300E+09 |
August | 0.879527E+09 | 48612586.14 | 0.830914E+09 | 0.495942E+09 | 0.773561E+09 |
September | 0.475144E+09 | 462948.61 | 0.474681E+09 | 58923568.52 | 0.158911E+10 |
October | 0.238914E+09 | 0.00 | 0.238914E+09 | 0.00 | 0.295843E+10 |
November | 71751875.10 | 0.00 | 71751875.10 | 0.00 | 0.455233E+10 |
December | 11646121.96 | 0.00 | 11646121.96 | 0.00 | 0.499901E+10 |
Annual Sum or Average | 0.733957E+10 | 0.840177E+09 | 0.649940E+10 | 0.371620E+10 | 0.305489E+11 |
Minimum of Months | 11646121.96 | 0.00 | 11646121.96 | 0.00 | 0.359992E+09 |
Maximum of Months | 0.158813E+10 | 0.352305E+09 | 0.123582E+10 | 0.127340E+10 | 0.499901E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38390468.51 | 0.00 | 38390468.51 | 0.00 | 0.469912E+10 |
February | 0.153281E+09 | 0.00 | 0.153281E+09 | 0.00 | 0.392116E+10 |
March | 0.453886E+09 | 0.00 | 0.453886E+09 | 1247111.91 | 0.348623E+10 |
April | 0.794401E+09 | 17181747.28 | 0.777220E+09 | 0.111125E+09 | 0.194377E+10 |
May | 0.125719E+10 | 0.198661E+09 | 0.105853E+10 | 0.618858E+09 | 0.808310E+09 |
June | 0.158806E+10 | 0.352291E+09 | 0.123577E+10 | 0.127335E+10 | 0.359977E+09 |
July | 0.137716E+10 | 0.222937E+09 | 0.115422E+10 | 0.115663E+10 | 0.457282E+09 |
August | 0.879492E+09 | 48610685.16 | 0.830882E+09 | 0.495922E+09 | 0.773529E+09 |
September | 0.475125E+09 | 462930.51 | 0.474662E+09 | 58921379.72 | 0.158904E+10 |
October | 0.238905E+09 | 0.00 | 0.238905E+09 | 0.00 | 0.295831E+10 |
November | 71749049.57 | 0.00 | 71749049.57 | 0.00 | 0.455215E+10 |
December | 11645663.82 | 0.00 | 11645663.82 | 0.00 | 0.499880E+10 |
Annual Sum or Average | 0.733928E+10 | 0.840144E+09 | 0.649914E+10 | 0.371606E+10 | 0.305477E+11 |
Minimum of Months | 11645663.82 | 0.00 | 11645663.82 | 0.00 | 0.359977E+09 |
Maximum of Months | 0.158806E+10 | 0.352291E+09 | 0.123577E+10 | 0.127335E+10 | 0.499880E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112020E+09 | 35012326.08 | 77007183.42 | 1058839.08 | 0.508174E+10 |
February | 0.560024E+09 | 0.266830E+09 | 0.293193E+09 | 0.165085E+09 | 0.394368E+10 |
March | 0.177199E+10 | 0.897873E+09 | 0.874114E+09 | 0.117350E+10 | 0.331302E+10 |
April | 0.235798E+10 | 0.119400E+10 | 0.116397E+10 | 0.178699E+10 | 0.181478E+10 |
May | 0.354128E+10 | 0.199575E+10 | 0.154552E+10 | 0.353916E+10 | 0.907869E+09 |
June | 0.315094E+10 | 0.146925E+10 | 0.168169E+10 | 0.333408E+10 | 0.433402E+09 |
July | 0.309342E+10 | 0.149960E+10 | 0.159382E+10 | 0.342263E+10 | 0.508631E+09 |
August | 0.245072E+10 | 0.119336E+10 | 0.125735E+10 | 0.250105E+10 | 0.781515E+09 |
September | 0.146642E+10 | 0.642495E+09 | 0.823924E+09 | 0.112063E+10 | 0.153104E+10 |
October | 0.799558E+09 | 0.320666E+09 | 0.478891E+09 | 0.405529E+09 | 0.292563E+10 |
November | 0.164184E+09 | 57070418.04 | 0.107113E+09 | 2532135.58 | 0.488113E+10 |
December | 24213294.95 | 5724922.53 | 18488372.41 | 0.00 | 0.546565E+10 |
Annual Sum or Average | 0.194927E+11 | 0.957764E+10 | 0.991509E+10 | 0.174522E+11 | 0.315881E+11 |
Minimum of Months | 24213294.95 | 5724922.53 | 18488372.41 | 0.00 | 0.433402E+09 |
Maximum of Months | 0.354128E+10 | 0.199575E+10 | 0.168169E+10 | 0.353916E+10 | 0.546565E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112020E+09 | 35012326.08 | 77007183.42 | 1058839.08 | 0.508174E+10 |
February | 0.560024E+09 | 0.266830E+09 | 0.293193E+09 | 0.165085E+09 | 0.394368E+10 |
March | 0.177199E+10 | 0.897873E+09 | 0.874114E+09 | 0.117350E+10 | 0.331302E+10 |
April | 0.235798E+10 | 0.119400E+10 | 0.116397E+10 | 0.178699E+10 | 0.181478E+10 |
May | 0.354128E+10 | 0.199575E+10 | 0.154552E+10 | 0.353916E+10 | 0.907869E+09 |
June | 0.315094E+10 | 0.146925E+10 | 0.168169E+10 | 0.333408E+10 | 0.433402E+09 |
July | 0.309342E+10 | 0.149960E+10 | 0.159382E+10 | 0.342263E+10 | 0.508631E+09 |
August | 0.245072E+10 | 0.119336E+10 | 0.125735E+10 | 0.250105E+10 | 0.781515E+09 |
September | 0.146642E+10 | 0.642495E+09 | 0.823924E+09 | 0.112063E+10 | 0.153104E+10 |
October | 0.799558E+09 | 0.320666E+09 | 0.478891E+09 | 0.405529E+09 | 0.292563E+10 |
November | 0.164184E+09 | 57070418.04 | 0.107113E+09 | 2532135.58 | 0.488113E+10 |
December | 24213294.95 | 5724922.53 | 18488372.41 | 0.00 | 0.546565E+10 |
Annual Sum or Average | 0.194927E+11 | 0.957764E+10 | 0.991509E+10 | 0.174522E+11 | 0.315881E+11 |
Minimum of Months | 24213294.95 | 5724922.53 | 18488372.41 | 0.00 | 0.433402E+09 |
Maximum of Months | 0.354128E+10 | 0.199575E+10 | 0.168169E+10 | 0.353916E+10 | 0.546565E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112017E+09 | 35011686.33 | 77005776.33 | 1058819.74 | 0.508165E+10 |
February | 0.560013E+09 | 0.266826E+09 | 0.293188E+09 | 0.165082E+09 | 0.394361E+10 |
March | 0.177196E+10 | 0.897857E+09 | 0.874098E+09 | 0.117348E+10 | 0.331296E+10 |
April | 0.235793E+10 | 0.119398E+10 | 0.116395E+10 | 0.178696E+10 | 0.181475E+10 |
May | 0.354121E+10 | 0.199572E+10 | 0.154550E+10 | 0.353910E+10 | 0.907852E+09 |
June | 0.315089E+10 | 0.146923E+10 | 0.168166E+10 | 0.333402E+10 | 0.433394E+09 |
July | 0.309336E+10 | 0.149957E+10 | 0.159379E+10 | 0.342256E+10 | 0.508622E+09 |
August | 0.245067E+10 | 0.119334E+10 | 0.125733E+10 | 0.250101E+10 | 0.781501E+09 |
September | 0.146639E+10 | 0.642484E+09 | 0.823909E+09 | 0.112061E+10 | 0.153101E+10 |
October | 0.799543E+09 | 0.320661E+09 | 0.478883E+09 | 0.405522E+09 | 0.292557E+10 |
November | 0.164181E+09 | 57069375.24 | 0.107111E+09 | 2532089.32 | 0.488104E+10 |
December | 24212852.52 | 5724817.93 | 18488034.59 | 0.00 | 0.546555E+10 |
Annual Sum or Average | 0.194924E+11 | 0.957746E+10 | 0.991491E+10 | 0.174519E+11 | 0.315875E+11 |
Minimum of Months | 24212852.52 | 5724817.93 | 18488034.59 | 0.00 | 0.433394E+09 |
Maximum of Months | 0.354121E+10 | 0.199572E+10 | 0.168166E+10 | 0.353910E+10 | 0.546555E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.462480E+09 | 0.305345E+09 | 0.157134E+09 | 0.166688E+09 | 0.422283E+10 |
February | 0.143609E+10 | 0.100034E+10 | 0.435749E+09 | 0.932079E+09 | 0.309797E+10 |
March | 0.272580E+10 | 0.184893E+10 | 0.876865E+09 | 0.225883E+10 | 0.268518E+10 |
April | 0.321278E+10 | 0.199853E+10 | 0.121424E+10 | 0.320923E+10 | 0.173577E+10 |
May | 0.273394E+10 | 0.141473E+10 | 0.131921E+10 | 0.289437E+10 | 0.983414E+09 |
June | 0.241518E+10 | 0.987600E+09 | 0.142758E+10 | 0.266362E+10 | 0.526055E+09 |
July | 0.240508E+10 | 0.104552E+10 | 0.135956E+10 | 0.276044E+10 | 0.567260E+09 |
August | 0.249295E+10 | 0.137335E+10 | 0.111960E+10 | 0.278231E+10 | 0.808697E+09 |
September | 0.195221E+10 | 0.117631E+10 | 0.775896E+09 | 0.186702E+10 | 0.135770E+10 |
October | 0.145477E+10 | 0.924261E+09 | 0.530505E+09 | 0.107684E+10 | 0.233805E+10 |
November | 0.756073E+09 | 0.528844E+09 | 0.227229E+09 | 0.323327E+09 | 0.387518E+10 |
December | 0.138785E+09 | 98017837.42 | 40767286.65 | 6850205.83 | 0.472691E+10 |
Annual Sum or Average | 0.221861E+11 | 0.127018E+11 | 0.948433E+10 | 0.209416E+11 | 0.269250E+11 |
Minimum of Months | 0.138785E+09 | 98017837.42 | 40767286.65 | 6850205.83 | 0.526055E+09 |
Maximum of Months | 0.321278E+10 | 0.199853E+10 | 0.142758E+10 | 0.320923E+10 | 0.472691E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.462479E+09 | 0.305345E+09 | 0.157134E+09 | 0.166688E+09 | 0.422283E+10 |
February | 0.143609E+10 | 0.100034E+10 | 0.435749E+09 | 0.932077E+09 | 0.309797E+10 |
March | 0.272579E+10 | 0.184893E+10 | 0.876864E+09 | 0.225883E+10 | 0.268518E+10 |
April | 0.321278E+10 | 0.199853E+10 | 0.121424E+10 | 0.320923E+10 | 0.173577E+10 |
May | 0.273394E+10 | 0.141473E+10 | 0.131921E+10 | 0.289437E+10 | 0.983414E+09 |
June | 0.241517E+10 | 0.987599E+09 | 0.142758E+10 | 0.266362E+10 | 0.526055E+09 |
July | 0.240508E+10 | 0.104552E+10 | 0.135956E+10 | 0.276044E+10 | 0.567260E+09 |
August | 0.249295E+10 | 0.137335E+10 | 0.111960E+10 | 0.278231E+10 | 0.808697E+09 |
September | 0.195221E+10 | 0.117631E+10 | 0.775896E+09 | 0.186702E+10 | 0.135770E+10 |
October | 0.145476E+10 | 0.924260E+09 | 0.530505E+09 | 0.107684E+10 | 0.233805E+10 |
November | 0.756072E+09 | 0.528844E+09 | 0.227228E+09 | 0.323326E+09 | 0.387518E+10 |
December | 0.138785E+09 | 98017719.81 | 40767240.46 | 6850164.47 | 0.472691E+10 |
Annual Sum or Average | 0.221861E+11 | 0.127018E+11 | 0.948432E+10 | 0.209416E+11 | 0.269250E+11 |
Minimum of Months | 0.138785E+09 | 98017719.81 | 40767240.46 | 6850164.47 | 0.526055E+09 |
Maximum of Months | 0.321278E+10 | 0.199853E+10 | 0.142758E+10 | 0.320923E+10 | 0.472691E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.462480E+09 | 0.305345E+09 | 0.157134E+09 | 0.166688E+09 | 0.422283E+10 |
February | 0.143609E+10 | 0.100034E+10 | 0.435749E+09 | 0.932079E+09 | 0.309797E+10 |
March | 0.272580E+10 | 0.184893E+10 | 0.876865E+09 | 0.225883E+10 | 0.268518E+10 |
April | 0.321278E+10 | 0.199853E+10 | 0.121424E+10 | 0.320923E+10 | 0.173577E+10 |
May | 0.273394E+10 | 0.141473E+10 | 0.131921E+10 | 0.289437E+10 | 0.983414E+09 |
June | 0.241518E+10 | 0.987600E+09 | 0.142758E+10 | 0.266362E+10 | 0.526055E+09 |
July | 0.240508E+10 | 0.104552E+10 | 0.135956E+10 | 0.276044E+10 | 0.567260E+09 |
August | 0.249295E+10 | 0.137335E+10 | 0.111960E+10 | 0.278231E+10 | 0.808697E+09 |
September | 0.195221E+10 | 0.117631E+10 | 0.775896E+09 | 0.186702E+10 | 0.135770E+10 |
October | 0.145477E+10 | 0.924261E+09 | 0.530505E+09 | 0.107684E+10 | 0.233805E+10 |
November | 0.756073E+09 | 0.528844E+09 | 0.227229E+09 | 0.323327E+09 | 0.387518E+10 |
December | 0.138785E+09 | 98017837.42 | 40767286.65 | 6850205.83 | 0.472691E+10 |
Annual Sum or Average | 0.221861E+11 | 0.127018E+11 | 0.948433E+10 | 0.209416E+11 | 0.269250E+11 |
Minimum of Months | 0.138785E+09 | 98017837.42 | 40767286.65 | 6850205.83 | 0.526055E+09 |
Maximum of Months | 0.321278E+10 | 0.199853E+10 | 0.142758E+10 | 0.320923E+10 | 0.472691E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.462479E+09 | 0.305345E+09 | 0.157134E+09 | 0.166688E+09 | 0.422283E+10 |
February | 0.143609E+10 | 0.100034E+10 | 0.435749E+09 | 0.932077E+09 | 0.309797E+10 |
March | 0.272579E+10 | 0.184893E+10 | 0.876864E+09 | 0.225883E+10 | 0.268518E+10 |
April | 0.321278E+10 | 0.199853E+10 | 0.121424E+10 | 0.320923E+10 | 0.173577E+10 |
May | 0.273394E+10 | 0.141473E+10 | 0.131921E+10 | 0.289437E+10 | 0.983414E+09 |
June | 0.241517E+10 | 0.987599E+09 | 0.142758E+10 | 0.266362E+10 | 0.526055E+09 |
July | 0.240508E+10 | 0.104552E+10 | 0.135956E+10 | 0.276044E+10 | 0.567260E+09 |
August | 0.249295E+10 | 0.137335E+10 | 0.111960E+10 | 0.278231E+10 | 0.808697E+09 |
September | 0.195221E+10 | 0.117631E+10 | 0.775896E+09 | 0.186702E+10 | 0.135770E+10 |
October | 0.145476E+10 | 0.924260E+09 | 0.530505E+09 | 0.107684E+10 | 0.233805E+10 |
November | 0.756072E+09 | 0.528844E+09 | 0.227228E+09 | 0.323326E+09 | 0.387518E+10 |
December | 0.138785E+09 | 98017719.81 | 40767240.46 | 6850164.47 | 0.472691E+10 |
Annual Sum or Average | 0.221861E+11 | 0.127018E+11 | 0.948432E+10 | 0.209416E+11 | 0.269250E+11 |
Minimum of Months | 0.138785E+09 | 98017719.81 | 40767240.46 | 6850164.47 | 0.526055E+09 |
Maximum of Months | 0.321278E+10 | 0.199853E+10 | 0.142758E+10 | 0.320923E+10 | 0.472691E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.462461E+09 | 0.305333E+09 | 0.157128E+09 | 0.166682E+09 | 0.422266E+10 |
February | 0.143603E+10 | 0.100030E+10 | 0.435732E+09 | 0.932041E+09 | 0.309784E+10 |
March | 0.272569E+10 | 0.184886E+10 | 0.876830E+09 | 0.225874E+10 | 0.268507E+10 |
April | 0.321265E+10 | 0.199845E+10 | 0.121420E+10 | 0.320911E+10 | 0.173570E+10 |
May | 0.273383E+10 | 0.141468E+10 | 0.131915E+10 | 0.289425E+10 | 0.983374E+09 |
June | 0.241508E+10 | 0.987560E+09 | 0.142752E+10 | 0.266351E+10 | 0.526033E+09 |
July | 0.240498E+10 | 0.104548E+10 | 0.135950E+10 | 0.276033E+10 | 0.567237E+09 |
August | 0.249285E+10 | 0.137330E+10 | 0.111955E+10 | 0.278220E+10 | 0.808664E+09 |
September | 0.195213E+10 | 0.117627E+10 | 0.775865E+09 | 0.186694E+10 | 0.135765E+10 |
October | 0.145471E+10 | 0.924223E+09 | 0.530484E+09 | 0.107680E+10 | 0.233796E+10 |
November | 0.756043E+09 | 0.528823E+09 | 0.227220E+09 | 0.323314E+09 | 0.387503E+10 |
December | 0.138780E+09 | 98013886.87 | 40765643.55 | 6849929.73 | 0.472672E+10 |
Annual Sum or Average | 0.221852E+11 | 0.127013E+11 | 0.948395E+10 | 0.209408E+11 | 0.269239E+11 |
Minimum of Months | 0.138780E+09 | 98013886.87 | 40765643.55 | 6849929.73 | 0.526033E+09 |
Maximum of Months | 0.321265E+10 | 0.199845E+10 | 0.142752E+10 | 0.320911E+10 | 0.472672E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58967118.18 | 10404562.00 | 48562556.17 | 0.00 | 0.530957E+10 |
February | 0.314540E+09 | 0.108960E+09 | 0.205581E+09 | 15453364.42 | 0.427349E+10 |
March | 0.104683E+10 | 0.449717E+09 | 0.597115E+09 | 0.398022E+09 | 0.368969E+10 |
April | 0.240749E+10 | 0.124871E+10 | 0.115877E+10 | 0.191257E+10 | 0.216119E+10 |
May | 0.241872E+10 | 0.110268E+10 | 0.131605E+10 | 0.214852E+10 | 0.110382E+10 |
June | 0.256463E+10 | 0.109443E+10 | 0.147020E+10 | 0.260437E+10 | 0.615184E+09 |
July | 0.221717E+10 | 0.839446E+09 | 0.137772E+10 | 0.225938E+10 | 0.695239E+09 |
August | 0.182237E+10 | 0.772314E+09 | 0.105005E+10 | 0.167566E+10 | 0.102315E+10 |
September | 0.106681E+10 | 0.446820E+09 | 0.619995E+09 | 0.684750E+09 | 0.172890E+10 |
October | 0.431110E+09 | 0.129216E+09 | 0.301895E+09 | 84170247.95 | 0.322452E+10 |
November | 0.166689E+09 | 60276375.60 | 0.106413E+09 | 3829882.25 | 0.512208E+10 |
December | 15473576.35 | 1597987.93 | 13875588.42 | 0.00 | 0.581497E+10 |
Annual Sum or Average | 0.145308E+11 | 0.626457E+10 | 0.826623E+10 | 0.117867E+11 | 0.347618E+11 |
Minimum of Months | 15473576.35 | 1597987.93 | 13875588.42 | 0.00 | 0.615184E+09 |
Maximum of Months | 0.256463E+10 | 0.124871E+10 | 0.147020E+10 | 0.260437E+10 | 0.581497E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58967118.18 | 10404562.00 | 48562556.17 | 0.00 | 0.530957E+10 |
February | 0.314540E+09 | 0.108960E+09 | 0.205581E+09 | 15453364.42 | 0.427349E+10 |
March | 0.104683E+10 | 0.449717E+09 | 0.597115E+09 | 0.398022E+09 | 0.368969E+10 |
April | 0.240749E+10 | 0.124871E+10 | 0.115877E+10 | 0.191257E+10 | 0.216119E+10 |
May | 0.241872E+10 | 0.110268E+10 | 0.131605E+10 | 0.214852E+10 | 0.110382E+10 |
June | 0.256463E+10 | 0.109443E+10 | 0.147020E+10 | 0.260437E+10 | 0.615184E+09 |
July | 0.221717E+10 | 0.839446E+09 | 0.137772E+10 | 0.225938E+10 | 0.695239E+09 |
August | 0.182237E+10 | 0.772314E+09 | 0.105005E+10 | 0.167566E+10 | 0.102315E+10 |
September | 0.106681E+10 | 0.446820E+09 | 0.619995E+09 | 0.684750E+09 | 0.172890E+10 |
October | 0.431110E+09 | 0.129216E+09 | 0.301895E+09 | 84170247.95 | 0.322452E+10 |
November | 0.166689E+09 | 60276375.60 | 0.106413E+09 | 3829882.25 | 0.512208E+10 |
December | 15473576.35 | 1597987.93 | 13875588.42 | 0.00 | 0.581497E+10 |
Annual Sum or Average | 0.145308E+11 | 0.626457E+10 | 0.826623E+10 | 0.117867E+11 | 0.347618E+11 |
Minimum of Months | 15473576.35 | 1597987.93 | 13875588.42 | 0.00 | 0.615184E+09 |
Maximum of Months | 0.256463E+10 | 0.124871E+10 | 0.147020E+10 | 0.260437E+10 | 0.581497E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58966040.72 | 10404371.89 | 48561668.83 | 0.00 | 0.530948E+10 |
February | 0.314535E+09 | 0.108958E+09 | 0.205577E+09 | 15453082.05 | 0.427341E+10 |
March | 0.104681E+10 | 0.449709E+09 | 0.597104E+09 | 0.398015E+09 | 0.368963E+10 |
April | 0.240744E+10 | 0.124869E+10 | 0.115875E+10 | 0.191253E+10 | 0.216115E+10 |
May | 0.241868E+10 | 0.110266E+10 | 0.131602E+10 | 0.214848E+10 | 0.110380E+10 |
June | 0.256458E+10 | 0.109441E+10 | 0.147017E+10 | 0.260432E+10 | 0.615173E+09 |
July | 0.221713E+10 | 0.839431E+09 | 0.137770E+10 | 0.225934E+10 | 0.695226E+09 |
August | 0.182234E+10 | 0.772300E+09 | 0.105004E+10 | 0.167562E+10 | 0.102313E+10 |
September | 0.106680E+10 | 0.446812E+09 | 0.619984E+09 | 0.684738E+09 | 0.172887E+10 |
October | 0.431102E+09 | 0.129213E+09 | 0.301889E+09 | 84168709.98 | 0.322446E+10 |
November | 0.166686E+09 | 60275274.22 | 0.106411E+09 | 3829812.27 | 0.512199E+10 |
December | 15473293.61 | 1597958.73 | 13875334.88 | 0.00 | 0.581487E+10 |
Annual Sum or Average | 0.145305E+11 | 0.626446E+10 | 0.826608E+10 | 0.117865E+11 | 0.347612E+11 |
Minimum of Months | 15473293.61 | 1597958.73 | 13875334.88 | 0.00 | 0.615173E+09 |
Maximum of Months | 0.256458E+10 | 0.124869E+10 | 0.147017E+10 | 0.260432E+10 | 0.581487E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.191958E+09 | 0.00 | 0.191958E+09 | 0.00 | 0.231207E+11 |
February | 0.766428E+09 | 0.00 | 0.766428E+09 | 0.00 | 0.192210E+11 |
March | 0.226949E+10 | 0.00 | 0.226949E+10 | 19765078.05 | 0.168553E+11 |
April | 0.397212E+10 | 85911160.21 | 0.388621E+10 | 0.720816E+09 | 0.892548E+10 |
May | 0.628611E+10 | 0.993333E+09 | 0.529277E+10 | 0.335423E+10 | 0.375076E+10 |
June | 0.794054E+10 | 0.176151E+10 | 0.617904E+10 | 0.648353E+10 | 0.168452E+10 |
July | 0.688599E+10 | 0.111471E+10 | 0.577127E+10 | 0.596773E+10 | 0.211712E+10 |
August | 0.439759E+10 | 0.243060E+09 | 0.415453E+10 | 0.272756E+10 | 0.345578E+10 |
September | 0.237569E+10 | 2314717.84 | 0.237338E+10 | 0.400868E+09 | 0.729173E+10 |
October | 0.119456E+10 | 0.00 | 0.119456E+10 | 5405162.73 | 0.139059E+11 |
November | 0.358755E+09 | 0.00 | 0.358755E+09 | 0.00 | 0.218846E+11 |
December | 58229961.93 | 0.00 | 58229961.93 | 0.00 | 0.242204E+11 |
Annual Sum or Average | 0.366975E+11 | 0.420084E+10 | 0.324966E+11 | 0.196799E+11 | 0.146433E+12 |
Minimum of Months | 58229961.93 | 0.00 | 58229961.93 | 0.00 | 0.168452E+10 |
Maximum of Months | 0.794054E+10 | 0.176151E+10 | 0.617904E+10 | 0.648353E+10 | 0.242204E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.336055E+09 | 0.105036E+09 | 0.231019E+09 | 4041061.50 | 0.149527E+11 |
February | 0.168005E+10 | 0.800483E+09 | 0.879571E+09 | 0.508013E+09 | 0.116008E+11 |
March | 0.531591E+10 | 0.269359E+10 | 0.262232E+10 | 0.353021E+10 | 0.974618E+10 |
April | 0.707385E+10 | 0.358197E+10 | 0.349189E+10 | 0.536129E+10 | 0.520908E+10 |
May | 0.106237E+11 | 0.598720E+10 | 0.463653E+10 | 0.105220E+11 | 0.262959E+10 |
June | 0.945274E+10 | 0.440771E+10 | 0.504502E+10 | 0.992434E+10 | 0.125012E+10 |
July | 0.928015E+10 | 0.449875E+10 | 0.478140E+10 | 0.101897E+11 | 0.148063E+10 |
August | 0.735207E+10 | 0.358004E+10 | 0.377203E+10 | 0.746868E+10 | 0.224755E+10 |
September | 0.439921E+10 | 0.192747E+10 | 0.247175E+10 | 0.335515E+10 | 0.439791E+10 |
October | 0.239865E+10 | 0.961989E+09 | 0.143666E+10 | 0.124321E+10 | 0.835305E+10 |
November | 0.492546E+09 | 0.171210E+09 | 0.321336E+09 | 7567488.72 | 0.140980E+11 |
December | 72639144.43 | 17174592.54 | 55464551.89 | 0.00 | 0.159122E+11 |
Annual Sum or Average | 0.584776E+11 | 0.287326E+11 | 0.297450E+11 | 0.521142E+11 | 0.918778E+11 |
Minimum of Months | 72639144.43 | 17174592.54 | 55464551.89 | 0.00 | 0.125012E+10 |
Maximum of Months | 0.106237E+11 | 0.598720E+10 | 0.504502E+10 | 0.105220E+11 | 0.159122E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231237E+10 | 0.152671E+10 | 0.785662E+09 | 0.831427E+09 | 0.209962E+11 |
February | 0.718037E+10 | 0.500165E+10 | 0.217872E+10 | 0.466781E+10 | 0.153821E+11 |
March | 0.136288E+11 | 0.924454E+10 | 0.438427E+10 | 0.112054E+11 | 0.133323E+11 |
April | 0.160637E+11 | 0.999255E+10 | 0.607115E+10 | 0.159228E+11 | 0.851445E+10 |
May | 0.136695E+11 | 0.707358E+10 | 0.659596E+10 | 0.143298E+11 | 0.485248E+10 |
June | 0.120757E+11 | 0.493794E+10 | 0.713780E+10 | 0.132350E+11 | 0.255454E+10 |
July | 0.120253E+11 | 0.522755E+10 | 0.679770E+10 | 0.137504E+11 | 0.274631E+10 |
August | 0.124646E+11 | 0.686667E+10 | 0.559792E+10 | 0.138665E+11 | 0.390185E+10 |
September | 0.976093E+10 | 0.588150E+10 | 0.387944E+10 | 0.928148E+10 | 0.670281E+10 |
October | 0.727374E+10 | 0.462125E+10 | 0.265249E+10 | 0.539306E+10 | 0.114392E+11 |
November | 0.378032E+10 | 0.264419E+10 | 0.113613E+10 | 0.164977E+10 | 0.189352E+11 |
December | 0.693917E+09 | 0.490083E+09 | 0.203834E+09 | 35064172.52 | 0.232840E+11 |
Annual Sum or Average | 0.110929E+12 | 0.635082E+11 | 0.474211E+11 | 0.104168E+12 | 0.132641E+12 |
Minimum of Months | 0.693917E+09 | 0.490083E+09 | 0.203834E+09 | 35064172.52 | 0.255454E+10 |
Maximum of Months | 0.160637E+11 | 0.999255E+10 | 0.713780E+10 | 0.159228E+11 | 0.232840E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.176900E+09 | 31213367.85 | 0.145686E+09 | 0.00 | 0.153598E+11 |
February | 0.943611E+09 | 0.326876E+09 | 0.616736E+09 | 55878286.56 | 0.122456E+11 |
March | 0.314046E+10 | 0.134914E+10 | 0.179133E+10 | 0.124916E+10 | 0.103791E+11 |
April | 0.722239E+10 | 0.374610E+10 | 0.347628E+10 | 0.592295E+10 | 0.577419E+10 |
May | 0.725610E+10 | 0.330799E+10 | 0.394810E+10 | 0.657307E+10 | 0.306415E+10 |
June | 0.769381E+10 | 0.328327E+10 | 0.441055E+10 | 0.791579E+10 | 0.167423E+10 |
July | 0.665143E+10 | 0.251831E+10 | 0.413312E+10 | 0.698802E+10 | 0.180349E+10 |
August | 0.546705E+10 | 0.231692E+10 | 0.315013E+10 | 0.527701E+10 | 0.257809E+10 |
September | 0.320041E+10 | 0.134045E+10 | 0.185997E+10 | 0.215498E+10 | 0.470839E+10 |
October | 0.129332E+10 | 0.387643E+09 | 0.905674E+09 | 0.280945E+09 | 0.891687E+10 |
November | 0.500062E+09 | 0.180827E+09 | 0.319235E+09 | 13316934.28 | 0.142706E+11 |
December | 46420255.89 | 4793914.93 | 41626340.96 | 0.00 | 0.162730E+11 |
Annual Sum or Average | 0.435920E+11 | 0.187935E+11 | 0.247984E+11 | 0.364311E+11 | 0.970475E+11 |
Minimum of Months | 46420255.89 | 4793914.93 | 41626340.96 | 0.00 | 0.167423E+10 |
Maximum of Months | 0.769381E+10 | 0.374610E+10 | 0.441055E+10 | 0.791579E+10 | 0.162730E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.191958E+09 | 0.00 | 0.191958E+09 | 0.00 | 0.227008E+11 |
February | 0.766428E+09 | 0.00 | 0.766428E+09 | 0.00 | 0.187736E+11 |
March | 0.226949E+10 | 0.00 | 0.226949E+10 | 33494527.15 | 0.163206E+11 |
April | 0.397212E+10 | 85911160.21 | 0.388621E+10 | 0.829206E+09 | 0.838763E+10 |
May | 0.628611E+10 | 0.993333E+09 | 0.529277E+10 | 0.370815E+10 | 0.341028E+10 |
June | 0.794054E+10 | 0.176151E+10 | 0.617904E+10 | 0.671255E+10 | 0.155018E+10 |
July | 0.688599E+10 | 0.111471E+10 | 0.577127E+10 | 0.618407E+10 | 0.195330E+10 |
August | 0.439759E+10 | 0.243060E+09 | 0.415453E+10 | 0.294386E+10 | 0.314465E+10 |
September | 0.237569E+10 | 2314717.84 | 0.237338E+10 | 0.509751E+09 | 0.658701E+10 |
October | 0.119456E+10 | 0.00 | 0.119456E+10 | 23665039.94 | 0.131252E+11 |
November | 0.358755E+09 | 0.00 | 0.358755E+09 | 0.00 | 0.213844E+11 |
December | 58229961.93 | 0.00 | 58229961.93 | 0.00 | 0.237743E+11 |
Annual Sum or Average | 0.366975E+11 | 0.420084E+10 | 0.324966E+11 | 0.209447E+11 | 0.141112E+12 |
Minimum of Months | 58229961.93 | 0.00 | 58229961.93 | 0.00 | 0.155018E+10 |
Maximum of Months | 0.794054E+10 | 0.176151E+10 | 0.617904E+10 | 0.671255E+10 | 0.237743E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.336055E+09 | 0.105036E+09 | 0.231019E+09 | 2789649.95 | 0.147813E+11 |
February | 0.168005E+10 | 0.800483E+09 | 0.879571E+09 | 0.529432E+09 | 0.113480E+11 |
March | 0.531591E+10 | 0.269359E+10 | 0.262232E+10 | 0.363110E+10 | 0.937207E+10 |
April | 0.707385E+10 | 0.358197E+10 | 0.349189E+10 | 0.552144E+10 | 0.489323E+10 |
May | 0.106237E+11 | 0.598720E+10 | 0.463653E+10 | 0.106675E+11 | 0.246166E+10 |
June | 0.945274E+10 | 0.440771E+10 | 0.504502E+10 | 0.996951E+10 | 0.119168E+10 |
July | 0.928015E+10 | 0.449875E+10 | 0.478140E+10 | 0.102344E+11 | 0.140878E+10 |
August | 0.735207E+10 | 0.358004E+10 | 0.377203E+10 | 0.756456E+10 | 0.210898E+10 |
September | 0.439921E+10 | 0.192747E+10 | 0.247175E+10 | 0.351874E+10 | 0.397459E+10 |
October | 0.239865E+10 | 0.961989E+09 | 0.143666E+10 | 0.131690E+10 | 0.785015E+10 |
November | 0.492546E+09 | 0.171210E+09 | 0.321336E+09 | 7895625.40 | 0.138572E+11 |
December | 72639144.43 | 17174592.54 | 55464551.89 | 0.00 | 0.157527E+11 |
Annual Sum or Average | 0.584776E+11 | 0.287326E+11 | 0.297450E+11 | 0.529642E+11 | 0.890003E+11 |
Minimum of Months | 72639144.43 | 17174592.54 | 55464551.89 | 0.00 | 0.119168E+10 |
Maximum of Months | 0.106237E+11 | 0.598720E+10 | 0.504502E+10 | 0.106675E+11 | 0.157527E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231237E+10 | 0.152671E+10 | 0.785662E+09 | 0.851964E+09 | 0.205616E+11 |
February | 0.718037E+10 | 0.500165E+10 | 0.217872E+10 | 0.477458E+10 | 0.149122E+11 |
March | 0.136288E+11 | 0.924454E+10 | 0.438427E+10 | 0.113524E+11 | 0.127700E+11 |
April | 0.160637E+11 | 0.999255E+10 | 0.607115E+10 | 0.160608E+11 | 0.799787E+10 |
May | 0.136695E+11 | 0.707358E+10 | 0.659596E+10 | 0.144144E+11 | 0.449453E+10 |
June | 0.120757E+11 | 0.493794E+10 | 0.713780E+10 | 0.132395E+11 | 0.241628E+10 |
July | 0.120253E+11 | 0.522755E+10 | 0.679770E+10 | 0.137660E+11 | 0.260092E+10 |
August | 0.124646E+11 | 0.686667E+10 | 0.559792E+10 | 0.139142E+11 | 0.366531E+10 |
September | 0.976093E+10 | 0.588150E+10 | 0.387944E+10 | 0.944090E+10 | 0.610861E+10 |
October | 0.727374E+10 | 0.462125E+10 | 0.265249E+10 | 0.555880E+10 | 0.107192E+11 |
November | 0.378032E+10 | 0.264419E+10 | 0.113613E+10 | 0.169387E+10 | 0.184246E+11 |
December | 0.693917E+09 | 0.490083E+09 | 0.203834E+09 | 36396908.05 | 0.228235E+11 |
Annual Sum or Average | 0.110929E+12 | 0.635082E+11 | 0.474211E+11 | 0.105104E+12 | 0.127495E+12 |
Minimum of Months | 0.693917E+09 | 0.490083E+09 | 0.203834E+09 | 36396908.05 | 0.241628E+10 |
Maximum of Months | 0.160637E+11 | 0.999255E+10 | 0.713780E+10 | 0.160608E+11 | 0.228235E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.176900E+09 | 31213367.85 | 0.145686E+09 | 0.00 | 0.150857E+11 |
February | 0.943611E+09 | 0.326876E+09 | 0.616736E+09 | 59665480.42 | 0.119731E+11 |
March | 0.314046E+10 | 0.134914E+10 | 0.179133E+10 | 0.126828E+10 | 0.100567E+11 |
April | 0.722239E+10 | 0.374610E+10 | 0.347628E+10 | 0.596749E+10 | 0.545707E+10 |
May | 0.725610E+10 | 0.330799E+10 | 0.394810E+10 | 0.662598E+10 | 0.285880E+10 |
June | 0.769381E+10 | 0.328327E+10 | 0.441055E+10 | 0.791899E+10 | 0.159263E+10 |
July | 0.665143E+10 | 0.251831E+10 | 0.413312E+10 | 0.699795E+10 | 0.171700E+10 |
August | 0.546705E+10 | 0.231692E+10 | 0.315013E+10 | 0.530620E+10 | 0.243579E+10 |
September | 0.320041E+10 | 0.134045E+10 | 0.185997E+10 | 0.220536E+10 | 0.435793E+10 |
October | 0.129332E+10 | 0.387643E+09 | 0.905674E+09 | 0.303289E+09 | 0.848454E+10 |
November | 0.500062E+09 | 0.180827E+09 | 0.319235E+09 | 14205443.51 | 0.139591E+11 |
December | 46420255.89 | 4793914.93 | 41626340.96 | 0.00 | 0.159869E+11 |
Annual Sum or Average | 0.435920E+11 | 0.187935E+11 | 0.247984E+11 | 0.366674E+11 | 0.939653E+11 |
Minimum of Months | 46420255.89 | 4793914.93 | 41626340.96 | 0.00 | 0.159263E+10 |
Maximum of Months | 0.769381E+10 | 0.374610E+10 | 0.441055E+10 | 0.791899E+10 | 0.159869E+11 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 8772.54 | 71.67 | 0.00 | 71.67 | 0.00 | 0.00 |
February | 0.00 | 8104.51 | 316.81 | 0.00 | 316.81 | 0.00 | 0.00 |
March | 2.33 | 6508.25 | 847.33 | 0.00 | 847.33 | 0.00 | 0.00 |
April | 214.37 | 3749.68 | 1532.46 | 33.14 | 1499.31 | 0.00 | 0.00 |
May | 1155.31 | 1508.99 | 2346.97 | 370.87 | 1976.10 | 0.00 | 0.00 |
June | 2456.40 | 694.42 | 3063.49 | 679.60 | 2383.90 | 0.00 | 0.00 |
July | 2159.24 | 853.68 | 2570.94 | 416.19 | 2154.75 | 0.00 | 0.00 |
August | 925.81 | 1444.06 | 1641.88 | 90.75 | 1551.13 | 0.00 | 0.00 |
September | 113.66 | 3065.38 | 916.55 | 0.89 | 915.66 | 0.00 | 0.00 |
October | 0.00 | 5522.71 | 446.00 | 0.00 | 446.00 | 0.00 | 0.00 |
November | 0.00 | 8781.43 | 138.41 | 0.00 | 138.41 | 0.00 | 0.00 |
December | 0.00 | 9332.00 | 21.74 | 0.00 | 21.74 | 0.00 | 0.00 |
Annual Sum or Average | 589.20 | 4843.46 | 1163.67 | 133.21 | 1030.46 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 694.42 | 21.74 | 0.00 | 21.74 | 0.00 | 0.00 |
Maximum of Months | 2456.40 | 9332.00 | 3063.49 | 679.60 | 2383.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.19 | 5691.88 | 125.47 | 39.22 | 86.25 | 0.00 | 0.00 |
February | 204.72 | 4890.45 | 694.47 | 330.89 | 363.58 | 0.00 | 0.00 |
March | 1314.40 | 3710.80 | 1984.74 | 1005.68 | 979.06 | 0.00 | 0.00 |
April | 2068.26 | 2100.43 | 2729.12 | 1381.94 | 1347.18 | 0.00 | 0.00 |
May | 3964.09 | 1016.87 | 3966.46 | 2235.37 | 1731.09 | 0.00 | 0.00 |
June | 3858.87 | 501.62 | 3646.90 | 1700.51 | 1946.39 | 0.00 | 0.00 |
July | 3833.56 | 569.70 | 3464.83 | 1679.65 | 1785.18 | 0.00 | 0.00 |
August | 2801.34 | 875.35 | 2744.96 | 1336.64 | 1408.32 | 0.00 | 0.00 |
September | 1297.02 | 1772.03 | 1697.23 | 743.62 | 953.61 | 0.00 | 0.00 |
October | 454.22 | 3276.89 | 895.56 | 359.17 | 536.39 | 0.00 | 0.00 |
November | 2.93 | 5649.42 | 190.03 | 66.05 | 123.97 | 0.00 | 0.00 |
December | 0.00 | 6121.88 | 27.12 | 6.41 | 20.71 | 0.00 | 0.00 |
Annual Sum or Average | 1660.21 | 3004.94 | 1854.32 | 911.11 | 943.21 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 501.62 | 27.12 | 6.41 | 20.71 | 0.00 | 0.00 |
Maximum of Months | 3964.09 | 6121.88 | 3966.46 | 2235.37 | 1946.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 311.17 | 7883.06 | 863.34 | 570.01 | 293.33 | 0.00 | 0.00 |
February | 1926.40 | 6402.83 | 2968.09 | 2067.49 | 900.60 | 0.00 | 0.00 |
March | 4216.72 | 5012.62 | 5088.43 | 3451.53 | 1636.91 | 0.00 | 0.00 |
April | 6190.60 | 3348.29 | 6197.44 | 3855.16 | 2342.27 | 0.00 | 0.00 |
May | 5403.13 | 1835.81 | 5103.64 | 2640.98 | 2462.66 | 0.00 | 0.00 |
June | 5138.11 | 1014.76 | 4658.87 | 1905.08 | 2753.79 | 0.00 | 0.00 |
July | 5153.11 | 1058.94 | 4489.73 | 1951.75 | 2537.98 | 0.00 | 0.00 |
August | 5193.93 | 1509.65 | 4653.76 | 2563.73 | 2090.03 | 0.00 | 0.00 |
September | 3601.47 | 2619.00 | 3765.81 | 2269.10 | 1496.70 | 0.00 | 0.00 |
October | 2010.21 | 4364.61 | 2715.71 | 1725.38 | 990.33 | 0.00 | 0.00 |
November | 623.70 | 7475.22 | 1458.46 | 1020.14 | 438.32 | 0.00 | 0.00 |
December | 12.79 | 8824.06 | 259.08 | 182.98 | 76.10 | 0.00 | 0.00 |
Annual Sum or Average | 3320.24 | 4268.90 | 3517.56 | 2013.84 | 1503.72 | 0.00 | 0.00 |
Minimum of Months | 12.79 | 1014.76 | 259.08 | 182.98 | 76.10 | 0.00 | 0.00 |
Maximum of Months | 6190.60 | 8824.06 | 6197.44 | 3855.16 | 2753.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 5947.07 | 66.05 | 11.65 | 54.39 | 0.00 | 0.00 |
February | 19.16 | 5299.43 | 390.05 | 135.12 | 254.93 | 0.00 | 0.00 |
March | 445.81 | 4132.70 | 1172.52 | 503.71 | 668.81 | 0.00 | 0.00 |
April | 2213.60 | 2501.37 | 2786.43 | 1445.26 | 1341.16 | 0.00 | 0.00 |
May | 2406.48 | 1236.35 | 2709.13 | 1235.07 | 1474.06 | 0.00 | 0.00 |
June | 3014.30 | 712.01 | 2968.30 | 1266.70 | 1701.61 | 0.00 | 0.00 |
July | 2530.65 | 778.71 | 2483.37 | 940.23 | 1543.14 | 0.00 | 0.00 |
August | 1876.84 | 1145.99 | 2041.17 | 865.04 | 1176.13 | 0.00 | 0.00 |
September | 792.53 | 2001.03 | 1234.73 | 517.15 | 717.58 | 0.00 | 0.00 |
October | 94.28 | 3611.67 | 482.87 | 144.73 | 338.14 | 0.00 | 0.00 |
November | 4.43 | 5928.30 | 192.93 | 69.76 | 123.16 | 0.00 | 0.00 |
December | 0.00 | 6513.15 | 17.33 | 1.79 | 15.54 | 0.00 | 0.00 |
Annual Sum or Average | 1121.26 | 3306.85 | 1382.30 | 595.94 | 786.36 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 712.01 | 17.33 | 1.79 | 15.54 | 0.00 | 0.00 |
Maximum of Months | 3014.30 | 6513.15 | 2968.30 | 1445.26 | 1701.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 8632.27 | 71.67 | 0.00 | 71.67 | 0.00 | 0.00 |
February | 0.00 | 7945.19 | 316.81 | 0.00 | 316.81 | 0.00 | 0.00 |
March | 7.38 | 6293.06 | 847.33 | 0.00 | 847.33 | 0.00 | 0.00 |
April | 278.09 | 3443.47 | 1532.45 | 33.14 | 1499.31 | 0.00 | 0.00 |
May | 1252.32 | 1400.37 | 2346.96 | 370.87 | 1976.10 | 0.00 | 0.00 |
June | 2501.36 | 649.89 | 3063.48 | 679.59 | 2383.89 | 0.00 | 0.00 |
July | 2228.09 | 790.44 | 2570.93 | 416.19 | 2154.75 | 0.00 | 0.00 |
August | 1018.36 | 1290.24 | 1641.87 | 90.75 | 1551.12 | 0.00 | 0.00 |
September | 154.66 | 2813.17 | 916.55 | 0.89 | 915.66 | 0.00 | 0.00 |
October | 2.02 | 5191.88 | 446.00 | 0.00 | 446.00 | 0.00 | 0.00 |
November | 0.00 | 8443.14 | 138.41 | 0.00 | 138.41 | 0.00 | 0.00 |
December | 0.00 | 9042.86 | 21.74 | 0.00 | 21.74 | 0.00 | 0.00 |
Annual Sum or Average | 624.05 | 4643.37 | 1163.67 | 133.21 | 1030.46 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 649.89 | 21.74 | 0.00 | 21.74 | 0.00 | 0.00 |
Maximum of Months | 2501.36 | 9042.86 | 3063.48 | 679.59 | 2383.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.51 | 5582.68 | 125.47 | 39.22 | 86.25 | 0.00 | 0.00 |
February | 209.99 | 4795.29 | 694.47 | 330.89 | 363.58 | 0.00 | 0.00 |
March | 1318.03 | 3638.81 | 1984.73 | 1005.67 | 979.06 | 0.00 | 0.00 |
April | 2068.40 | 2009.68 | 2729.11 | 1381.93 | 1347.18 | 0.00 | 0.00 |
May | 3928.48 | 981.78 | 3966.44 | 2235.36 | 1731.08 | 0.00 | 0.00 |
June | 3828.84 | 482.30 | 3646.89 | 1700.51 | 1946.38 | 0.00 | 0.00 |
July | 3804.39 | 552.80 | 3464.81 | 1679.64 | 1785.17 | 0.00 | 0.00 |
August | 2788.49 | 839.14 | 2744.95 | 1336.64 | 1408.31 | 0.00 | 0.00 |
September | 1294.43 | 1696.72 | 1697.23 | 743.62 | 953.61 | 0.00 | 0.00 |
October | 464.16 | 3118.67 | 895.55 | 359.17 | 536.39 | 0.00 | 0.00 |
November | 2.92 | 5439.04 | 190.03 | 66.05 | 123.97 | 0.00 | 0.00 |
December | 0.00 | 5940.95 | 27.12 | 6.41 | 20.71 | 0.00 | 0.00 |
Annual Sum or Average | 1652.53 | 2913.42 | 1854.31 | 911.11 | 943.21 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 482.30 | 27.12 | 6.41 | 20.71 | 0.00 | 0.00 |
Maximum of Months | 3928.48 | 5940.95 | 3966.44 | 2235.36 | 1946.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 310.42 | 7839.08 | 863.34 | 570.01 | 293.33 | 0.00 | 0.00 |
February | 1929.48 | 6358.34 | 2968.08 | 2067.48 | 900.60 | 0.00 | 0.00 |
March | 4183.60 | 4977.71 | 5088.42 | 3451.51 | 1636.90 | 0.00 | 0.00 |
April | 6143.04 | 3284.90 | 6197.42 | 3855.15 | 2342.26 | 0.00 | 0.00 |
May | 5350.15 | 1811.71 | 5103.62 | 2640.97 | 2462.65 | 0.00 | 0.00 |
June | 5106.09 | 985.55 | 4658.85 | 1905.07 | 2753.78 | 0.00 | 0.00 |
July | 5133.81 | 1025.35 | 4489.72 | 1951.74 | 2537.97 | 0.00 | 0.00 |
August | 5177.14 | 1456.78 | 4653.75 | 2563.72 | 2090.02 | 0.00 | 0.00 |
September | 3580.82 | 2585.96 | 3765.79 | 2269.10 | 1496.70 | 0.00 | 0.00 |
October | 2013.54 | 4270.89 | 2715.70 | 1725.38 | 990.33 | 0.00 | 0.00 |
November | 636.49 | 7305.25 | 1458.46 | 1020.13 | 438.32 | 0.00 | 0.00 |
December | 13.09 | 8693.25 | 259.08 | 182.98 | 76.10 | 0.00 | 0.00 |
Annual Sum or Average | 3303.16 | 4206.03 | 3517.54 | 2013.83 | 1503.71 | 0.00 | 0.00 |
Minimum of Months | 13.09 | 985.55 | 259.08 | 182.98 | 76.10 | 0.00 | 0.00 |
Maximum of Months | 6143.04 | 8693.25 | 6197.42 | 3855.15 | 2753.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 5734.69 | 66.05 | 11.65 | 54.39 | 0.00 | 0.00 |
February | 23.10 | 5061.83 | 390.05 | 135.12 | 254.93 | 0.00 | 0.00 |
March | 466.38 | 3875.11 | 1172.52 | 503.71 | 668.81 | 0.00 | 0.00 |
April | 2285.09 | 2227.70 | 2786.41 | 1445.26 | 1341.16 | 0.00 | 0.00 |
May | 2454.10 | 1144.02 | 2709.12 | 1235.06 | 1474.05 | 0.00 | 0.00 |
June | 3053.93 | 645.92 | 2968.29 | 1266.69 | 1701.60 | 0.00 | 0.00 |
July | 2609.03 | 673.35 | 2483.36 | 940.23 | 1543.13 | 0.00 | 0.00 |
August | 1970.21 | 962.55 | 2041.16 | 865.04 | 1176.12 | 0.00 | 0.00 |
September | 831.40 | 1816.51 | 1234.73 | 517.15 | 717.58 | 0.00 | 0.00 |
October | 104.89 | 3329.18 | 482.87 | 144.73 | 338.14 | 0.00 | 0.00 |
November | 5.14 | 5505.64 | 192.93 | 69.76 | 123.16 | 0.00 | 0.00 |
December | 0.00 | 6075.65 | 17.33 | 1.79 | 15.54 | 0.00 | 0.00 |
Annual Sum or Average | 1155.22 | 3077.36 | 1382.29 | 595.94 | 786.35 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 645.92 | 17.33 | 1.79 | 15.54 | 0.00 | 0.00 |
Maximum of Months | 3053.93 | 6075.65 | 2968.29 | 1445.26 | 1701.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 8475.51 | 71.67 | 0.00 | 71.67 | 0.00 | 0.00 |
February | 0.00 | 7760.27 | 316.81 | 0.00 | 316.81 | 0.00 | 0.00 |
March | 12.51 | 6093.40 | 847.33 | 0.00 | 847.33 | 0.00 | 0.00 |
April | 319.91 | 3235.97 | 1532.45 | 33.14 | 1499.31 | 0.00 | 0.00 |
May | 1384.46 | 1273.25 | 2346.96 | 370.87 | 1976.10 | 0.00 | 0.00 |
June | 2589.72 | 598.06 | 3063.48 | 679.59 | 2383.89 | 0.00 | 0.00 |
July | 2308.87 | 729.28 | 2570.93 | 416.19 | 2154.75 | 0.00 | 0.00 |
August | 1099.11 | 1174.08 | 1641.87 | 90.75 | 1551.12 | 0.00 | 0.00 |
September | 196.66 | 2541.28 | 916.55 | 0.89 | 915.66 | 0.00 | 0.00 |
October | 8.84 | 4900.39 | 446.00 | 0.00 | 446.00 | 0.00 | 0.00 |
November | 0.00 | 8250.15 | 138.41 | 0.00 | 138.41 | 0.00 | 0.00 |
December | 0.00 | 8876.30 | 21.74 | 0.00 | 21.74 | 0.00 | 0.00 |
Annual Sum or Average | 664.15 | 4474.63 | 1163.67 | 133.21 | 1030.46 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 598.06 | 21.74 | 0.00 | 21.74 | 0.00 | 0.00 |
Maximum of Months | 2589.72 | 8876.30 | 3063.48 | 679.59 | 2383.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.04 | 5518.70 | 125.47 | 39.22 | 86.25 | 0.00 | 0.00 |
February | 218.85 | 4690.81 | 694.47 | 330.89 | 363.58 | 0.00 | 0.00 |
March | 1355.70 | 3499.13 | 1984.73 | 1005.67 | 979.06 | 0.00 | 0.00 |
April | 2130.19 | 1887.82 | 2729.11 | 1381.93 | 1347.18 | 0.00 | 0.00 |
May | 3982.78 | 919.08 | 3966.44 | 2235.36 | 1731.08 | 0.00 | 0.00 |
June | 3846.26 | 459.75 | 3646.89 | 1700.51 | 1946.38 | 0.00 | 0.00 |
July | 3821.08 | 525.98 | 3464.81 | 1679.64 | 1785.17 | 0.00 | 0.00 |
August | 2824.28 | 787.40 | 2744.95 | 1336.64 | 1408.31 | 0.00 | 0.00 |
September | 1357.54 | 1533.41 | 1697.23 | 743.62 | 953.61 | 0.00 | 0.00 |
October | 491.67 | 2930.91 | 895.55 | 359.17 | 536.39 | 0.00 | 0.00 |
November | 3.05 | 5346.13 | 190.03 | 66.05 | 123.97 | 0.00 | 0.00 |
December | 0.00 | 5881.38 | 27.12 | 6.41 | 20.71 | 0.00 | 0.00 |
Annual Sum or Average | 1679.48 | 2822.18 | 1854.31 | 911.11 | 943.21 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 459.75 | 27.12 | 6.41 | 20.71 | 0.00 | 0.00 |
Maximum of Months | 3982.78 | 5881.38 | 3966.44 | 2235.36 | 1946.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 318.09 | 7676.83 | 863.34 | 570.01 | 293.33 | 0.00 | 0.00 |
February | 1973.62 | 6164.10 | 2968.08 | 2067.48 | 900.60 | 0.00 | 0.00 |
March | 4238.52 | 4767.76 | 5088.42 | 3451.51 | 1636.90 | 0.00 | 0.00 |
April | 6196.28 | 3085.60 | 6197.42 | 3855.15 | 2342.26 | 0.00 | 0.00 |
May | 5381.71 | 1678.07 | 5103.62 | 2640.97 | 2462.65 | 0.00 | 0.00 |
June | 5107.82 | 932.21 | 4658.85 | 1905.07 | 2753.78 | 0.00 | 0.00 |
July | 5139.64 | 971.07 | 4489.72 | 1951.74 | 2537.97 | 0.00 | 0.00 |
August | 5194.98 | 1368.47 | 4653.75 | 2563.72 | 2090.02 | 0.00 | 0.00 |
September | 3642.32 | 2356.72 | 3765.79 | 2269.10 | 1496.70 | 0.00 | 0.00 |
October | 2075.42 | 4002.11 | 2715.70 | 1725.38 | 990.33 | 0.00 | 0.00 |
November | 653.50 | 7108.25 | 1458.46 | 1020.13 | 438.32 | 0.00 | 0.00 |
December | 13.59 | 8521.34 | 259.08 | 182.98 | 76.10 | 0.00 | 0.00 |
Annual Sum or Average | 3332.82 | 4042.83 | 3517.54 | 2013.83 | 1503.71 | 0.00 | 0.00 |
Minimum of Months | 13.59 | 932.21 | 259.08 | 182.98 | 76.10 | 0.00 | 0.00 |
Maximum of Months | 6196.28 | 8521.34 | 6197.42 | 3855.15 | 2753.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 5632.37 | 66.05 | 11.65 | 54.39 | 0.00 | 0.00 |
February | 24.66 | 4949.20 | 390.05 | 135.12 | 254.93 | 0.00 | 0.00 |
March | 473.52 | 3754.74 | 1172.52 | 503.71 | 668.81 | 0.00 | 0.00 |
April | 2302.27 | 2105.35 | 2786.41 | 1445.26 | 1341.16 | 0.00 | 0.00 |
May | 2473.86 | 1067.35 | 2709.12 | 1235.06 | 1474.05 | 0.00 | 0.00 |
June | 3055.17 | 614.44 | 2968.29 | 1266.69 | 1701.60 | 0.00 | 0.00 |
July | 2612.74 | 641.06 | 2483.36 | 940.23 | 1543.13 | 0.00 | 0.00 |
August | 1981.11 | 909.42 | 2041.16 | 865.04 | 1176.12 | 0.00 | 0.00 |
September | 850.84 | 1681.30 | 1234.73 | 517.15 | 717.58 | 0.00 | 0.00 |
October | 113.24 | 3167.76 | 482.87 | 144.73 | 338.14 | 0.00 | 0.00 |
November | 5.48 | 5385.46 | 192.93 | 69.76 | 123.16 | 0.00 | 0.00 |
December | 0.00 | 5968.82 | 17.33 | 1.79 | 15.54 | 0.00 | 0.00 |
Annual Sum or Average | 1162.72 | 2979.62 | 1382.29 | 595.94 | 786.35 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 614.44 | 17.33 | 1.79 | 15.54 | 0.00 | 0.00 |
Maximum of Months | 3055.17 | 5968.82 | 2968.29 | 1445.26 | 1701.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.234964E+11 | 0.191958E+09 | 0.00 | 0.191958E+09 | 0.00 | 0.00 |
February | 0.00 | 0.196064E+11 | 0.766431E+09 | 0.00 | 0.766431E+09 | 0.00 | 0.00 |
March | 6235732.07 | 0.174317E+11 | 0.226950E+10 | 0.00 | 0.226950E+10 | 0.00 | 0.00 |
April | 0.555643E+09 | 0.971916E+10 | 0.397213E+10 | 85911465.29 | 0.388622E+10 | 0.00 | 0.00 |
May | 0.309439E+10 | 0.404168E+10 | 0.628613E+10 | 0.993337E+09 | 0.529279E+10 | 0.00 | 0.00 |
June | 0.636698E+10 | 0.179995E+10 | 0.794057E+10 | 0.176151E+10 | 0.617906E+10 | 0.00 | 0.00 |
July | 0.578332E+10 | 0.228648E+10 | 0.688601E+10 | 0.111472E+10 | 0.577129E+10 | 0.00 | 0.00 |
August | 0.247969E+10 | 0.386777E+10 | 0.439760E+10 | 0.243061E+09 | 0.415454E+10 | 0.00 | 0.00 |
September | 0.294616E+09 | 0.794546E+10 | 0.237570E+10 | 2314726.06 | 0.237339E+10 | 0.00 | 0.00 |
October | 0.00 | 0.147920E+11 | 0.119456E+10 | 0.00 | 0.119456E+10 | 0.00 | 0.00 |
November | 0.00 | 0.227615E+11 | 0.358757E+09 | 0.00 | 0.358757E+09 | 0.00 | 0.00 |
December | 0.00 | 0.249948E+11 | 58230174.16 | 0.00 | 58230174.16 | 0.00 | 0.00 |
Annual Sum or Average | 0.185809E+11 | 0.152743E+12 | 0.366976E+11 | 0.420085E+10 | 0.324967E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.179995E+10 | 58230174.16 | 0.00 | 58230174.16 | 0.00 | 0.00 |
Maximum of Months | 0.636698E+10 | 0.249948E+11 | 0.794057E+10 | 0.176151E+10 | 0.617906E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 3176497.91 | 0.152451E+11 | 0.336056E+09 | 0.105036E+09 | 0.231020E+09 | 0.00 | 0.00 |
February | 0.495251E+09 | 0.118310E+11 | 0.168006E+10 | 0.800486E+09 | 0.879574E+09 | 0.00 | 0.00 |
March | 0.352048E+10 | 0.993901E+10 | 0.531593E+10 | 0.269360E+10 | 0.262233E+10 | 0.00 | 0.00 |
April | 0.536094E+10 | 0.544431E+10 | 0.707388E+10 | 0.358198E+10 | 0.349190E+10 | 0.00 | 0.00 |
May | 0.106174E+11 | 0.272359E+10 | 0.106238E+11 | 0.598722E+10 | 0.463655E+10 | 0.00 | 0.00 |
June | 0.100022E+11 | 0.130020E+10 | 0.945277E+10 | 0.440773E+10 | 0.504504E+10 | 0.00 | 0.00 |
July | 0.102678E+11 | 0.152588E+10 | 0.928019E+10 | 0.449877E+10 | 0.478142E+10 | 0.00 | 0.00 |
August | 0.750311E+10 | 0.234453E+10 | 0.735210E+10 | 0.358006E+10 | 0.377204E+10 | 0.00 | 0.00 |
September | 0.336187E+10 | 0.459309E+10 | 0.439923E+10 | 0.192747E+10 | 0.247176E+10 | 0.00 | 0.00 |
October | 0.121658E+10 | 0.877683E+10 | 0.239866E+10 | 0.961993E+09 | 0.143667E+10 | 0.00 | 0.00 |
November | 7596360.48 | 0.146433E+11 | 0.492548E+09 | 0.171210E+09 | 0.321337E+09 | 0.00 | 0.00 |
December | 0.00 | 0.163969E+11 | 72639442.41 | 17174663.00 | 55464779.41 | 0.00 | 0.00 |
Annual Sum or Average | 0.523564E+11 | 0.947637E+11 | 0.584778E+11 | 0.287327E+11 | 0.297451E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.130020E+10 | 72639442.41 | 17174663.00 | 55464779.41 | 0.00 | 0.00 |
Maximum of Months | 0.106174E+11 | 0.163969E+11 | 0.106238E+11 | 0.598722E+10 | 0.504504E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.833434E+09 | 0.211140E+11 | 0.231238E+10 | 0.152671E+10 | 0.785665E+09 | 0.00 | 0.00 |
February | 0.466035E+10 | 0.154897E+11 | 0.718040E+10 | 0.500167E+10 | 0.217873E+10 | 0.00 | 0.00 |
March | 0.112941E+11 | 0.134258E+11 | 0.136289E+11 | 0.924457E+10 | 0.438429E+10 | 0.00 | 0.00 |
April | 0.160460E+11 | 0.867878E+10 | 0.160638E+11 | 0.999259E+10 | 0.607117E+10 | 0.00 | 0.00 |
May | 0.144717E+11 | 0.491703E+10 | 0.136696E+11 | 0.707361E+10 | 0.659598E+10 | 0.00 | 0.00 |
June | 0.133180E+11 | 0.263025E+10 | 0.120758E+11 | 0.493796E+10 | 0.713783E+10 | 0.00 | 0.00 |
July | 0.138021E+11 | 0.283628E+10 | 0.120253E+11 | 0.522757E+10 | 0.679773E+10 | 0.00 | 0.00 |
August | 0.139114E+11 | 0.404345E+10 | 0.124646E+11 | 0.686670E+10 | 0.559794E+10 | 0.00 | 0.00 |
September | 0.933501E+10 | 0.678845E+10 | 0.976097E+10 | 0.588152E+10 | 0.387945E+10 | 0.00 | 0.00 |
October | 0.538416E+10 | 0.116902E+11 | 0.727377E+10 | 0.462126E+10 | 0.265250E+10 | 0.00 | 0.00 |
November | 0.161662E+10 | 0.193758E+11 | 0.378033E+10 | 0.264420E+10 | 0.113613E+10 | 0.00 | 0.00 |
December | 34250670.32 | 0.236344E+11 | 0.693920E+09 | 0.490085E+09 | 0.203835E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104707E+12 | 0.134624E+12 | 0.110930E+12 | 0.635084E+11 | 0.474213E+11 | 0.00 | 0.00 |
Minimum of Months | 34250670.32 | 0.263025E+10 | 0.693920E+09 | 0.490085E+09 | 0.203835E+09 | 0.00 | 0.00 |
Maximum of Months | 0.160460E+11 | 0.236344E+11 | 0.160638E+11 | 0.999259E+10 | 0.713783E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.159286E+11 | 0.176900E+09 | 31213495.90 | 0.145687E+09 | 0.00 | 0.00 |
February | 46359810.88 | 0.128204E+11 | 0.943615E+09 | 0.326877E+09 | 0.616738E+09 | 0.00 | 0.00 |
March | 0.119406E+10 | 0.110690E+11 | 0.314048E+10 | 0.134914E+10 | 0.179133E+10 | 0.00 | 0.00 |
April | 0.573766E+10 | 0.648354E+10 | 0.722242E+10 | 0.374612E+10 | 0.347630E+10 | 0.00 | 0.00 |
May | 0.644553E+10 | 0.331145E+10 | 0.725613E+10 | 0.330801E+10 | 0.394812E+10 | 0.00 | 0.00 |
June | 0.781307E+10 | 0.184554E+10 | 0.769384E+10 | 0.328328E+10 | 0.441056E+10 | 0.00 | 0.00 |
July | 0.677809E+10 | 0.208570E+10 | 0.665146E+10 | 0.251832E+10 | 0.413314E+10 | 0.00 | 0.00 |
August | 0.502694E+10 | 0.306943E+10 | 0.546707E+10 | 0.231693E+10 | 0.315014E+10 | 0.00 | 0.00 |
September | 0.205424E+10 | 0.518668E+10 | 0.320042E+10 | 0.134045E+10 | 0.185997E+10 | 0.00 | 0.00 |
October | 0.252509E+09 | 0.967351E+10 | 0.129332E+10 | 0.387645E+09 | 0.905678E+09 | 0.00 | 0.00 |
November | 11489576.76 | 0.153662E+11 | 0.500064E+09 | 0.180828E+09 | 0.319236E+09 | 0.00 | 0.00 |
December | 0.00 | 0.174448E+11 | 46420446.31 | 4793934.59 | 41626511.72 | 0.00 | 0.00 |
Annual Sum or Average | 0.353599E+11 | 0.104285E+12 | 0.435921E+11 | 0.187936E+11 | 0.247985E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.184554E+10 | 46420446.31 | 4793934.59 | 41626511.72 | 0.00 | 0.00 |
Maximum of Months | 0.781307E+10 | 0.174448E+11 | 0.769384E+10 | 0.374612E+10 | 0.441056E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.231207E+11 | 0.191958E+09 | 0.00 | 0.191958E+09 | 0.00 | 0.00 |
February | 0.00 | 0.192210E+11 | 0.766428E+09 | 0.00 | 0.766428E+09 | 0.00 | 0.00 |
March | 19765078.05 | 0.168553E+11 | 0.226949E+10 | 0.00 | 0.226949E+10 | 0.00 | 0.00 |
April | 0.720816E+09 | 0.892548E+10 | 0.397212E+10 | 85911160.21 | 0.388621E+10 | 0.00 | 0.00 |
May | 0.335423E+10 | 0.375076E+10 | 0.628611E+10 | 0.993333E+09 | 0.529277E+10 | 0.00 | 0.00 |
June | 0.648353E+10 | 0.168452E+10 | 0.794054E+10 | 0.176151E+10 | 0.617904E+10 | 0.00 | 0.00 |
July | 0.596773E+10 | 0.211712E+10 | 0.688599E+10 | 0.111471E+10 | 0.577127E+10 | 0.00 | 0.00 |
August | 0.272756E+10 | 0.345578E+10 | 0.439759E+10 | 0.243060E+09 | 0.415453E+10 | 0.00 | 0.00 |
September | 0.400868E+09 | 0.729173E+10 | 0.237569E+10 | 2314717.84 | 0.237338E+10 | 0.00 | 0.00 |
October | 5405162.73 | 0.139059E+11 | 0.119456E+10 | 0.00 | 0.119456E+10 | 0.00 | 0.00 |
November | 0.00 | 0.218846E+11 | 0.358755E+09 | 0.00 | 0.358755E+09 | 0.00 | 0.00 |
December | 0.00 | 0.242204E+11 | 58229961.93 | 0.00 | 58229961.93 | 0.00 | 0.00 |
Annual Sum or Average | 0.196799E+11 | 0.146433E+12 | 0.366975E+11 | 0.420084E+10 | 0.324966E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.168452E+10 | 58229961.93 | 0.00 | 58229961.93 | 0.00 | 0.00 |
Maximum of Months | 0.648353E+10 | 0.242204E+11 | 0.794054E+10 | 0.176151E+10 | 0.617904E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 4041061.50 | 0.149527E+11 | 0.336055E+09 | 0.105036E+09 | 0.231019E+09 | 0.00 | 0.00 |
February | 0.508013E+09 | 0.116008E+11 | 0.168005E+10 | 0.800483E+09 | 0.879571E+09 | 0.00 | 0.00 |
March | 0.353021E+10 | 0.974618E+10 | 0.531591E+10 | 0.269359E+10 | 0.262232E+10 | 0.00 | 0.00 |
April | 0.536129E+10 | 0.520908E+10 | 0.707385E+10 | 0.358197E+10 | 0.349189E+10 | 0.00 | 0.00 |
May | 0.105220E+11 | 0.262959E+10 | 0.106237E+11 | 0.598720E+10 | 0.463653E+10 | 0.00 | 0.00 |
June | 0.992434E+10 | 0.125012E+10 | 0.945274E+10 | 0.440771E+10 | 0.504502E+10 | 0.00 | 0.00 |
July | 0.101897E+11 | 0.148063E+10 | 0.928015E+10 | 0.449875E+10 | 0.478140E+10 | 0.00 | 0.00 |
August | 0.746868E+10 | 0.224755E+10 | 0.735207E+10 | 0.358004E+10 | 0.377203E+10 | 0.00 | 0.00 |
September | 0.335515E+10 | 0.439791E+10 | 0.439921E+10 | 0.192747E+10 | 0.247175E+10 | 0.00 | 0.00 |
October | 0.124321E+10 | 0.835305E+10 | 0.239865E+10 | 0.961989E+09 | 0.143666E+10 | 0.00 | 0.00 |
November | 7567488.72 | 0.140980E+11 | 0.492546E+09 | 0.171210E+09 | 0.321336E+09 | 0.00 | 0.00 |
December | 0.00 | 0.159122E+11 | 72639144.43 | 17174592.54 | 55464551.89 | 0.00 | 0.00 |
Annual Sum or Average | 0.521142E+11 | 0.918778E+11 | 0.584776E+11 | 0.287326E+11 | 0.297450E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.125012E+10 | 72639144.43 | 17174592.54 | 55464551.89 | 0.00 | 0.00 |
Maximum of Months | 0.105220E+11 | 0.159122E+11 | 0.106237E+11 | 0.598720E+10 | 0.504502E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.831427E+09 | 0.209962E+11 | 0.231237E+10 | 0.152671E+10 | 0.785662E+09 | 0.00 | 0.00 |
February | 0.466781E+10 | 0.153821E+11 | 0.718037E+10 | 0.500165E+10 | 0.217872E+10 | 0.00 | 0.00 |
March | 0.112054E+11 | 0.133323E+11 | 0.136288E+11 | 0.924454E+10 | 0.438427E+10 | 0.00 | 0.00 |
April | 0.159228E+11 | 0.851445E+10 | 0.160637E+11 | 0.999255E+10 | 0.607115E+10 | 0.00 | 0.00 |
May | 0.143298E+11 | 0.485248E+10 | 0.136695E+11 | 0.707358E+10 | 0.659596E+10 | 0.00 | 0.00 |
June | 0.132350E+11 | 0.255454E+10 | 0.120757E+11 | 0.493794E+10 | 0.713780E+10 | 0.00 | 0.00 |
July | 0.137504E+11 | 0.274631E+10 | 0.120253E+11 | 0.522755E+10 | 0.679770E+10 | 0.00 | 0.00 |
August | 0.138665E+11 | 0.390185E+10 | 0.124646E+11 | 0.686667E+10 | 0.559792E+10 | 0.00 | 0.00 |
September | 0.928148E+10 | 0.670281E+10 | 0.976093E+10 | 0.588150E+10 | 0.387944E+10 | 0.00 | 0.00 |
October | 0.539306E+10 | 0.114392E+11 | 0.727374E+10 | 0.462125E+10 | 0.265249E+10 | 0.00 | 0.00 |
November | 0.164977E+10 | 0.189352E+11 | 0.378032E+10 | 0.264419E+10 | 0.113613E+10 | 0.00 | 0.00 |
December | 35064172.52 | 0.232840E+11 | 0.693917E+09 | 0.490083E+09 | 0.203834E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104168E+12 | 0.132641E+12 | 0.110929E+12 | 0.635082E+11 | 0.474211E+11 | 0.00 | 0.00 |
Minimum of Months | 35064172.52 | 0.255454E+10 | 0.693917E+09 | 0.490083E+09 | 0.203834E+09 | 0.00 | 0.00 |
Maximum of Months | 0.159228E+11 | 0.232840E+11 | 0.160637E+11 | 0.999255E+10 | 0.713780E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.153598E+11 | 0.176900E+09 | 31213367.85 | 0.145686E+09 | 0.00 | 0.00 |
February | 55878286.56 | 0.122456E+11 | 0.943611E+09 | 0.326876E+09 | 0.616736E+09 | 0.00 | 0.00 |
March | 0.124916E+10 | 0.103791E+11 | 0.314046E+10 | 0.134914E+10 | 0.179133E+10 | 0.00 | 0.00 |
April | 0.592295E+10 | 0.577419E+10 | 0.722239E+10 | 0.374610E+10 | 0.347628E+10 | 0.00 | 0.00 |
May | 0.657307E+10 | 0.306415E+10 | 0.725610E+10 | 0.330799E+10 | 0.394810E+10 | 0.00 | 0.00 |
June | 0.791579E+10 | 0.167423E+10 | 0.769381E+10 | 0.328327E+10 | 0.441055E+10 | 0.00 | 0.00 |
July | 0.698802E+10 | 0.180349E+10 | 0.665143E+10 | 0.251831E+10 | 0.413312E+10 | 0.00 | 0.00 |
August | 0.527701E+10 | 0.257809E+10 | 0.546705E+10 | 0.231692E+10 | 0.315013E+10 | 0.00 | 0.00 |
September | 0.215498E+10 | 0.470839E+10 | 0.320041E+10 | 0.134045E+10 | 0.185997E+10 | 0.00 | 0.00 |
October | 0.280945E+09 | 0.891687E+10 | 0.129332E+10 | 0.387643E+09 | 0.905674E+09 | 0.00 | 0.00 |
November | 13316934.28 | 0.142706E+11 | 0.500062E+09 | 0.180827E+09 | 0.319235E+09 | 0.00 | 0.00 |
December | 0.00 | 0.162730E+11 | 46420255.89 | 4793914.93 | 41626340.96 | 0.00 | 0.00 |
Annual Sum or Average | 0.364311E+11 | 0.970475E+11 | 0.435920E+11 | 0.187935E+11 | 0.247984E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.167423E+10 | 46420255.89 | 4793914.93 | 41626340.96 | 0.00 | 0.00 |
Maximum of Months | 0.791579E+10 | 0.162730E+11 | 0.769381E+10 | 0.374610E+10 | 0.441055E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.227008E+11 | 0.191958E+09 | 0.00 | 0.191958E+09 | 0.00 | 0.00 |
February | 0.00 | 0.187736E+11 | 0.766428E+09 | 0.00 | 0.766428E+09 | 0.00 | 0.00 |
March | 33494527.15 | 0.163206E+11 | 0.226949E+10 | 0.00 | 0.226949E+10 | 0.00 | 0.00 |
April | 0.829206E+09 | 0.838763E+10 | 0.397212E+10 | 85911160.21 | 0.388621E+10 | 0.00 | 0.00 |
May | 0.370815E+10 | 0.341028E+10 | 0.628611E+10 | 0.993333E+09 | 0.529277E+10 | 0.00 | 0.00 |
June | 0.671255E+10 | 0.155018E+10 | 0.794054E+10 | 0.176151E+10 | 0.617904E+10 | 0.00 | 0.00 |
July | 0.618407E+10 | 0.195330E+10 | 0.688599E+10 | 0.111471E+10 | 0.577127E+10 | 0.00 | 0.00 |
August | 0.294386E+10 | 0.314465E+10 | 0.439759E+10 | 0.243060E+09 | 0.415453E+10 | 0.00 | 0.00 |
September | 0.509751E+09 | 0.658701E+10 | 0.237569E+10 | 2314717.84 | 0.237338E+10 | 0.00 | 0.00 |
October | 23665039.94 | 0.131252E+11 | 0.119456E+10 | 0.00 | 0.119456E+10 | 0.00 | 0.00 |
November | 0.00 | 0.213844E+11 | 0.358755E+09 | 0.00 | 0.358755E+09 | 0.00 | 0.00 |
December | 0.00 | 0.237743E+11 | 58229961.93 | 0.00 | 58229961.93 | 0.00 | 0.00 |
Annual Sum or Average | 0.209447E+11 | 0.141112E+12 | 0.366975E+11 | 0.420084E+10 | 0.324966E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.155018E+10 | 58229961.93 | 0.00 | 58229961.93 | 0.00 | 0.00 |
Maximum of Months | 0.671255E+10 | 0.237743E+11 | 0.794054E+10 | 0.176151E+10 | 0.617904E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 2789649.95 | 0.147813E+11 | 0.336055E+09 | 0.105036E+09 | 0.231019E+09 | 0.00 | 0.00 |
February | 0.529432E+09 | 0.113480E+11 | 0.168005E+10 | 0.800483E+09 | 0.879571E+09 | 0.00 | 0.00 |
March | 0.363110E+10 | 0.937207E+10 | 0.531591E+10 | 0.269359E+10 | 0.262232E+10 | 0.00 | 0.00 |
April | 0.552144E+10 | 0.489323E+10 | 0.707385E+10 | 0.358197E+10 | 0.349189E+10 | 0.00 | 0.00 |
May | 0.106675E+11 | 0.246166E+10 | 0.106237E+11 | 0.598720E+10 | 0.463653E+10 | 0.00 | 0.00 |
June | 0.996951E+10 | 0.119168E+10 | 0.945274E+10 | 0.440771E+10 | 0.504502E+10 | 0.00 | 0.00 |
July | 0.102344E+11 | 0.140878E+10 | 0.928015E+10 | 0.449875E+10 | 0.478140E+10 | 0.00 | 0.00 |
August | 0.756456E+10 | 0.210898E+10 | 0.735207E+10 | 0.358004E+10 | 0.377203E+10 | 0.00 | 0.00 |
September | 0.351874E+10 | 0.397459E+10 | 0.439921E+10 | 0.192747E+10 | 0.247175E+10 | 0.00 | 0.00 |
October | 0.131690E+10 | 0.785015E+10 | 0.239865E+10 | 0.961989E+09 | 0.143666E+10 | 0.00 | 0.00 |
November | 7895625.40 | 0.138572E+11 | 0.492546E+09 | 0.171210E+09 | 0.321336E+09 | 0.00 | 0.00 |
December | 0.00 | 0.157527E+11 | 72639144.43 | 17174592.54 | 55464551.89 | 0.00 | 0.00 |
Annual Sum or Average | 0.529642E+11 | 0.890003E+11 | 0.584776E+11 | 0.287326E+11 | 0.297450E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.119168E+10 | 72639144.43 | 17174592.54 | 55464551.89 | 0.00 | 0.00 |
Maximum of Months | 0.106675E+11 | 0.157527E+11 | 0.106237E+11 | 0.598720E+10 | 0.504502E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.851964E+09 | 0.205616E+11 | 0.231237E+10 | 0.152671E+10 | 0.785662E+09 | 0.00 | 0.00 |
February | 0.477458E+10 | 0.149122E+11 | 0.718037E+10 | 0.500165E+10 | 0.217872E+10 | 0.00 | 0.00 |
March | 0.113524E+11 | 0.127700E+11 | 0.136288E+11 | 0.924454E+10 | 0.438427E+10 | 0.00 | 0.00 |
April | 0.160608E+11 | 0.799787E+10 | 0.160637E+11 | 0.999255E+10 | 0.607115E+10 | 0.00 | 0.00 |
May | 0.144144E+11 | 0.449453E+10 | 0.136695E+11 | 0.707358E+10 | 0.659596E+10 | 0.00 | 0.00 |
June | 0.132395E+11 | 0.241628E+10 | 0.120757E+11 | 0.493794E+10 | 0.713780E+10 | 0.00 | 0.00 |
July | 0.137660E+11 | 0.260092E+10 | 0.120253E+11 | 0.522755E+10 | 0.679770E+10 | 0.00 | 0.00 |
August | 0.139142E+11 | 0.366531E+10 | 0.124646E+11 | 0.686667E+10 | 0.559792E+10 | 0.00 | 0.00 |
September | 0.944090E+10 | 0.610861E+10 | 0.976093E+10 | 0.588150E+10 | 0.387944E+10 | 0.00 | 0.00 |
October | 0.555880E+10 | 0.107192E+11 | 0.727374E+10 | 0.462125E+10 | 0.265249E+10 | 0.00 | 0.00 |
November | 0.169387E+10 | 0.184246E+11 | 0.378032E+10 | 0.264419E+10 | 0.113613E+10 | 0.00 | 0.00 |
December | 36396908.05 | 0.228235E+11 | 0.693917E+09 | 0.490083E+09 | 0.203834E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105104E+12 | 0.127495E+12 | 0.110929E+12 | 0.635082E+11 | 0.474211E+11 | 0.00 | 0.00 |
Minimum of Months | 36396908.05 | 0.241628E+10 | 0.693917E+09 | 0.490083E+09 | 0.203834E+09 | 0.00 | 0.00 |
Maximum of Months | 0.160608E+11 | 0.228235E+11 | 0.160637E+11 | 0.999255E+10 | 0.713780E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.150857E+11 | 0.176900E+09 | 31213367.85 | 0.145686E+09 | 0.00 | 0.00 |
February | 59665480.42 | 0.119731E+11 | 0.943611E+09 | 0.326876E+09 | 0.616736E+09 | 0.00 | 0.00 |
March | 0.126828E+10 | 0.100567E+11 | 0.314046E+10 | 0.134914E+10 | 0.179133E+10 | 0.00 | 0.00 |
April | 0.596749E+10 | 0.545707E+10 | 0.722239E+10 | 0.374610E+10 | 0.347628E+10 | 0.00 | 0.00 |
May | 0.662598E+10 | 0.285880E+10 | 0.725610E+10 | 0.330799E+10 | 0.394810E+10 | 0.00 | 0.00 |
June | 0.791899E+10 | 0.159263E+10 | 0.769381E+10 | 0.328327E+10 | 0.441055E+10 | 0.00 | 0.00 |
July | 0.699795E+10 | 0.171700E+10 | 0.665143E+10 | 0.251831E+10 | 0.413312E+10 | 0.00 | 0.00 |
August | 0.530620E+10 | 0.243579E+10 | 0.546705E+10 | 0.231692E+10 | 0.315013E+10 | 0.00 | 0.00 |
September | 0.220536E+10 | 0.435793E+10 | 0.320041E+10 | 0.134045E+10 | 0.185997E+10 | 0.00 | 0.00 |
October | 0.303289E+09 | 0.848454E+10 | 0.129332E+10 | 0.387643E+09 | 0.905674E+09 | 0.00 | 0.00 |
November | 14205443.51 | 0.139591E+11 | 0.500062E+09 | 0.180827E+09 | 0.319235E+09 | 0.00 | 0.00 |
December | 0.00 | 0.159869E+11 | 46420255.89 | 4793914.93 | 41626340.96 | 0.00 | 0.00 |
Annual Sum or Average | 0.366674E+11 | 0.939653E+11 | 0.435920E+11 | 0.187935E+11 | 0.247984E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.159263E+10 | 46420255.89 | 4793914.93 | 41626340.96 | 0.00 | 0.00 |
Maximum of Months | 0.791899E+10 | 0.159869E+11 | 0.769381E+10 | 0.374610E+10 | 0.441055E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.482340E+11 | -0.477512E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -482857654.6 | 60.05 | 0.00 | 0.00 |
February | 0.438220E+11 | -0.433912E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -430718886.0 | 60.05 | 0.00 | 0.00 |
March | 0.515216E+11 | -0.510525E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -469055937.8 | 60.05 | 0.00 | 0.00 |
April | 0.467224E+11 | -0.462847E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -437698467.7 | 60.05 | 0.00 | 0.00 |
May | 0.495133E+11 | -0.490639E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -449463577.0 | 60.05 | 0.00 | 0.00 |
June | 0.473193E+11 | -0.468870E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -432280420.7 | 60.05 | 0.00 | 0.00 |
July | 0.433689E+11 | -0.429257E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443183267.3 | 60.05 | 0.00 | 0.00 |
August | 0.463253E+11 | -0.458795E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -445763646.0 | 60.05 | 0.00 | 0.00 |
September | 0.419031E+11 | -0.414691E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -433959557.4 | 60.05 | 0.00 | 0.00 |
October | 0.440641E+11 | -0.436116E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -452514053.0 | 60.05 | 0.00 | 0.00 |
November | 0.447583E+11 | -0.443026E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -455680717.5 | 60.05 | 0.00 | 0.00 |
December | 0.463596E+11 | -0.458833E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -476357330.5 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.553912E+12 | -0.548502E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.540953E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.419031E+11 | -0.510525E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -482857654.6 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.515216E+11 | -0.414691E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -430718886.0 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 108.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 205.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 329.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 421.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 545.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 583.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 562.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 467.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 356.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 265.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 135.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 583.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.602289E+11 | 92535.45 | 12-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.400030E+11 | 86681.95 | 27-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.269709E+11 | 71780.97 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.340123E+10 | 52598.56 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7366958.41 | 1701.73 | 27-MAY-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3801560.85 | 4664.85 | 31-AUG-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.376459E+09 | 14248.72 | 30-SEP-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113861E+11 | 49174.26 | 31-OCT-06:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.483643E+11 | 70158.78 | 29-NOV-09:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.601228E+11 | 79863.51 | 15-DEC-07:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250865E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.602289E+11 | 92535.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.420915E+09 | 37132.23 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 50473952.32 | 36922.61 | 27-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.471389E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.420915E+09 | 37132.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.111642E+11 | 23518.06 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.755816E+10 | 23321.52 | 27-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.510641E+10 | 23319.45 | 06-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.743322E+09 | 25249.76 | 08-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 200250.16 | 196.16 | 27-MAY-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4782499.57 | 7532.70 | 31-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.207999E+09 | 19018.50 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.251282E+10 | 24308.72 | 14-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.745035E+10 | 23235.11 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.945108E+10 | 23314.09 | 04-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.441993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.111642E+11 | 25249.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.968054E+10 | 21359.82 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.639124E+10 | 21341.73 | 27-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388421E+10 | 21319.42 | 15-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.888233E+09 | 21922.91 | 08-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18317261.44 | 2599.08 | 27-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23502229.02 | 19426.68 | 31-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.454647E+09 | 21022.14 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.272012E+10 | 21316.25 | 30-OCT-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.734674E+10 | 21317.50 | 13-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.913779E+10 | 21313.10 | 18-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.405453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.968054E+10 | 21922.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144950E+11 | 33494.18 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.865459E+10 | 33465.75 | 27-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.552668E+10 | 33421.11 | 08-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151894E+10 | 34376.75 | 08-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.194012E+09 | 8177.63 | 27-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29200.74 | 486.68 | 06-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 62677329.68 | 30464.41 | 31-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.939433E+09 | 32965.14 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.424963E+10 | 33991.69 | 11-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102445E+11 | 33430.24 | 16-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139210E+11 | 33454.67 | 26-DEC-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.598064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.144950E+11 | 34376.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.728896E+10 | 21396.65 | 09-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.467577E+10 | 21441.09 | 27-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.255729E+10 | 21395.24 | 13-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172838E+09 | 21338.44 | 04-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12449525.31 | 1702.45 | 27-MAY-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.230788E+09 | 5430.12 | 28-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195928E+10 | 21398.74 | 30-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.362389E+10 | 21347.38 | 20-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.401019E+10 | 21389.95 | 04-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.728896E+10 | 21441.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.667587E+12 | 982367.83 | 12-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.467186E+12 | 918834.14 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.369103E+12 | 772942.19 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.715049E+11 | 890477.88 | 13-APR-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.996652E+09 | 499370.56 | 26-MAY-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18648992.26 | 134628.68 | 15-JUN-09:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 57350504.51 | 335832.87 | 05-JUL-09:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.662101E+09 | 481284.50 | 30-AUG-13:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126590E+11 | 862018.69 | 28-SEP-09:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.199341E+12 | 736267.61 | 05-OCT-09:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.621313E+12 | 780809.95 | 28-NOV-08:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.726797E+12 | 876232.27 | 15-DEC-07:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.313723E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 18648992.26 | 134628.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.726797E+12 | 982367.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.372646E+11 | 680070.01 | 18-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168353E+11 | 679819.60 | 06-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.449153E+10 | 679665.52 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132842E+10 | 679595.04 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.446409E+10 | 679779.53 | 31-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197352E+11 | 679971.81 | 14-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.235470E+11 | 679892.79 | 26-DEC-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107666E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.372646E+11 | 680070.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.193124E+12 | 296440.86 | 04-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147957E+12 | 295385.09 | 24-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117697E+12 | 296426.05 | 06-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.437602E+11 | 294780.99 | 08-APR-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.226729E+10 | 244025.57 | 27-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181237E+10 | 275480.16 | 31-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.204370E+11 | 290769.70 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.851017E+11 | 294943.70 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162479E+12 | 296474.14 | 24-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192329E+12 | 296415.70 | 09-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.966964E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.193124E+12 | 296474.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.127749E+12 | 241913.88 | 09-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.920094E+11 | 241936.66 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.610994E+11 | 242151.75 | 06-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.226484E+11 | 241625.14 | 03-APR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121494E+10 | 153317.39 | 27-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17676106.46 | 8241.60 | 05-JUL-05:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.105806E+10 | 214619.11 | 31-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124849E+11 | 230577.65 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.531196E+11 | 241904.00 | 23-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108873E+12 | 242044.50 | 13-NOV-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129563E+12 | 242009.24 | 05-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.609837E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.129563E+12 | 242151.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.194049E+12 | 366918.76 | 09-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120657E+12 | 366952.19 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.805182E+11 | 366352.00 | 27-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.314019E+11 | 366182.08 | 04-APR-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.623619E+10 | 248477.75 | 27-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.194776E+09 | 26569.70 | 26-JUN-05:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.210965E+09 | 37584.40 | 06-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.304013E+10 | 325463.30 | 31-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.184208E+11 | 349695.03 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.729801E+11 | 366904.29 | 23-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153503E+12 | 367118.20 | 13-NOV-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205977E+12 | 367065.51 | 05-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.887189E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.194776E+09 | 26569.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.205977E+12 | 367118.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.130312E+12 | 241779.36 | 09-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.943906E+11 | 241800.54 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.719814E+11 | 241406.56 | 27-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.239778E+11 | 241195.32 | 04-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.391850E+10 | 162331.60 | 27-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34470723.02 | 13398.80 | 02-JUN-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 66077322.44 | 15282.44 | 06-JUL-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.197713E+10 | 214454.58 | 31-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.168689E+11 | 230458.68 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.601976E+11 | 241770.19 | 23-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102400E+12 | 241762.49 | 20-NOV-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119422E+12 | 241761.99 | 18-DEC-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.625546E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 34470723.02 | 13398.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.130312E+12 | 241800.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.754450E+11 | 104042.83 | 12-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.533104E+11 | 94516.94 | 27-FEB-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.386432E+11 | 81847.15 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.755836E+10 | 64608.24 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82857582.24 | 7694.23 | 27-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118532E+09 | 14584.37 | 31-AUG-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.178350E+10 | 24153.01 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.221943E+11 | 58085.14 | 31-OCT-06:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.699139E+11 | 81690.71 | 29-NOV-09:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.813595E+11 | 92217.27 | 15-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.350409E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.813595E+11 | 104042.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.326875E+11 | 131310.51 | 23-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235685E+11 | 131355.82 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167356E+11 | 131404.46 | 20-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.607408E+10 | 131142.11 | 10-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.346072E+09 | 112900.86 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139104E+09 | 119247.74 | 31-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262243E+10 | 129194.96 | 29-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134685E+11 | 131618.67 | 24-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279139E+11 | 131293.28 | 20-NOV-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.321148E+11 | 131307.44 | 20-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155670E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.326875E+11 | 131618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.290094E+11 | 39420.98 | 05-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.238908E+11 | 39454.46 | 08-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.210845E+11 | 39423.98 | 13-MAR-03:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100599E+11 | 39423.62 | 10-APR-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180619E+10 | 36622.79 | 27-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 63672433.54 | 4872.99 | 26-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.106453E+09 | 6995.65 | 05-JUL-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123668E+10 | 36760.30 | 31-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.653428E+10 | 39388.40 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165903E+11 | 39419.20 | 30-OCT-03:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262350E+11 | 39422.48 | 13-NOV-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.299058E+11 | 39415.16 | 28-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166523E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 63672433.54 | 4872.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.299058E+11 | 39454.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.191237E+11 | 26099.82 | 05-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147323E+11 | 26111.02 | 20-FEB-23:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107808E+11 | 26068.00 | 24-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.458005E+10 | 26014.72 | 03-APR-03:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.527541E+09 | 24183.96 | 27-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26998561.28 | 3799.44 | 26-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 39443904.23 | 4211.43 | 05-JUL-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.361596E+09 | 24274.80 | 31-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.303902E+10 | 26009.87 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.972841E+10 | 26067.25 | 24-OCT-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172441E+11 | 26110.11 | 12-NOV-22:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199728E+11 | 26025.00 | 28-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100157E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 26998561.28 | 3799.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.199728E+11 | 26111.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.274593E+11 | 42293.92 | 26-JAN-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.189757E+11 | 42323.09 | 08-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141546E+11 | 42300.93 | 08-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.639405E+10 | 42375.60 | 08-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.189929E+10 | 38061.64 | 27-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.305528E+09 | 20431.43 | 19-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.258806E+09 | 16784.84 | 06-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.103678E+10 | 38205.88 | 31-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.451283E+10 | 41336.48 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130754E+11 | 42376.50 | 21-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.236005E+11 | 42428.30 | 13-NOV-02:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.297216E+11 | 42416.48 | 20-DEC-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141394E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.258806E+09 | 16784.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.297216E+11 | 42428.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.179075E+11 | 28235.03 | 28-JAN-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136781E+11 | 28321.32 | 08-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110925E+11 | 28313.11 | 08-MAR-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.443710E+10 | 28289.92 | 08-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115252E+10 | 25213.69 | 27-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 97882590.74 | 4552.48 | 26-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 95113830.30 | 3489.72 | 06-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.642175E+09 | 25309.49 | 31-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.345643E+10 | 27175.69 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.937382E+10 | 28310.54 | 26-OCT-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149154E+11 | 28313.95 | 02-NOV-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170222E+11 | 28317.20 | 20-DEC-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.938707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 95113830.30 | 3489.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.179075E+11 | 28321.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.200554E+11 | 191777.12 | 12-JAN-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130667E+11 | 187303.57 | 27-FEB-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.250800E+10 | 181555.85 | 01-MAR-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.368733E+10 | 180568.97 | 29-NOV-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.103805E+11 | 186576.45 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.496980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.200554E+11 | 191777.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 325.92 | 325.92 | 0.54 | 01-JAN-05:00 | 0.54 | 0.00 |
February | 0.00 | 0.00 | 1760.06 | 1760.06 | 0.97 | 13-FEB-05:01 | 0.97 | 0.00 |
March | 0.00 | 0.00 | 133421.78 | 133421.78 | 1026.94 | 27-MAR-16:01 | 1026.94 | 0.00 |
April | 0.00 | 0.00 | 52487753.29 | 52487753.29 | 7283.71 | 22-APR-14:00 | 7283.71 | 0.00 |
May | 0.00 | 0.00 | 0.119302E+11 | 0.119302E+11 | 91647.73 | 31-MAY-16:00 | 91647.73 | 0.00 |
June | 0.00 | 0.00 | 0.515281E+11 | 0.514218E+11 | 135747.33 | 30-JUN-12:05 | 128841.01 | 0.12 |
July | 0.00 | 0.00 | 0.701952E+11 | 0.699128E+11 | 140769.00 | 21-JUL-14:40 | 140769.00 | 0.38 |
August | 0.00 | 0.00 | 0.401043E+11 | 0.401033E+11 | 140802.88 | 11-AUG-15:30 | 140802.88 | 0.23 |
September | 0.00 | 0.00 | 0.927286E+09 | 0.927286E+09 | 29521.52 | 07-SEP-15:55 | 29521.52 | 0.00 |
October | 0.00 | 0.00 | 128.09 | 128.09 | 0.49 | 07-OCT-05:39 | 0.49 | 0.00 |
November | 0.00 | 0.00 | 47.16 | 47.16 | 0.39 | 18-NOV-06:38 | 0.39 | 0.00 |
December | 0.00 | 0.00 | 2074.00 | 2074.00 | 0.98 | 26-DEC-05:01 | 0.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.174738E+12 | 0.174348E+12 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 47.16 | 47.16 | 0.39 | 0.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.701952E+11 | 0.699128E+11 | 140802.88 | 140802.88 | 0.38 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 77554.42 | 77554.42 | 5.02 | 15-JAN-17:50 | 5.02 | 0.00 |
February | 0.00 | 0.00 | 90971.66 | 90971.66 | 5.50 | 07-FEB-04:04 | 5.50 | 0.00 |
March | 0.00 | 0.00 | 0.111519E+10 | 0.111519E+10 | 286475.93 | 22-MAR-14:01 | 286475.93 | 0.00 |
April | 0.00 | 0.00 | 0.818761E+10 | 0.818761E+10 | 553729.14 | 26-APR-13:04 | 553729.14 | 0.00 |
May | 0.00 | 0.00 | 0.115678E+12 | 0.115678E+12 | 870727.69 | 31-MAY-16:00 | 870727.69 | 0.00 |
June | 0.00 | 0.00 | 0.478928E+12 | 0.477932E+12 | 1319163.65 | 30-JUN-12:05 | 1247989.66 | 0.12 |
July | 0.00 | 0.00 | 0.612641E+12 | 0.610309E+12 | 1324758.08 | 21-JUL-14:30 | 1324758.08 | 0.37 |
August | 0.00 | 0.00 | 0.343767E+12 | 0.343759E+12 | 1253749.92 | 11-AUG-15:40 | 1253749.92 | 0.22 |
September | 0.00 | 0.00 | 0.264986E+11 | 0.264986E+11 | 600705.30 | 18-SEP-14:02 | 600705.30 | 0.00 |
October | 0.00 | 0.00 | 0.306294E+10 | 0.306294E+10 | 556105.98 | 03-OCT-14:01 | 556105.98 | 0.00 |
November | 0.00 | 0.00 | 48081.74 | 48081.74 | 5.99 | 24-NOV-02:61 | 5.99 | 0.00 |
December | 0.00 | 0.00 | 41663.64 | 41663.64 | 4.61 | 31-DEC-07:59 | 4.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.158988E+13 | 0.158654E+13 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 41663.64 | 41663.64 | 4.61 | 4.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.612641E+12 | 0.610309E+12 | 1324758.08 | 1324758.08 | 0.37 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7126521.86 | 7126521.86 | 2656.61 | 28-JAN-05:13 | 2656.61 | 0.00 |
February | 0.00 | 0.00 | 4645360.88 | 4645360.88 | 7224.65 | 22-FEB-06:02 | 7224.65 | 0.00 |
March | 0.00 | 0.00 | 6402110.68 | 6402110.68 | 4282.49 | 08-MAR-05:01 | 4282.49 | 0.00 |
April | 0.00 | 0.00 | 32669151.98 | 32669151.98 | 7108.41 | 22-APR-14:00 | 7108.41 | 0.00 |
May | 0.00 | 0.00 | 0.106423E+11 | 0.106423E+11 | 91882.31 | 31-MAY-16:00 | 91882.31 | 0.00 |
June | 0.00 | 0.00 | 0.487244E+11 | 0.486596E+11 | 146599.19 | 30-JUN-14:30 | 146599.19 | 0.12 |
July | 0.00 | 0.00 | 0.635362E+11 | 0.633752E+11 | 160160.65 | 23-JUL-13:01 | 160160.65 | 0.35 |
August | 0.00 | 0.00 | 0.340497E+11 | 0.340497E+11 | 135984.02 | 11-AUG-15:40 | 135984.02 | 0.20 |
September | 0.00 | 0.00 | 0.648081E+09 | 0.648081E+09 | 22415.72 | 07-SEP-16:00 | 22415.72 | 0.00 |
October | 0.00 | 0.00 | 2365680.27 | 2365680.27 | 3489.79 | 27-OCT-04:22 | 3489.79 | 0.00 |
November | 0.00 | 0.00 | 9296501.02 | 9296501.02 | 6981.30 | 27-NOV-06:12 | 6981.30 | 0.00 |
December | 0.00 | 0.00 | 9246515.71 | 9246515.71 | 4373.78 | 16-DEC-05:12 | 4373.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.157672E+12 | 0.157447E+12 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 2365680.27 | 2365680.27 | 2656.61 | 2656.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.635362E+11 | 0.633752E+11 | 160160.65 | 160160.65 | 0.35 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 9206227.45 | 9206227.45 | 37944.75 | 10-FEB-06:01 | 37944.75 | 0.00 |
March | 0.00 | 0.00 | 0.301199E+09 | 0.301199E+09 | 121853.43 | 23-MAR-04:47 | 121853.43 | 0.00 |
April | 0.00 | 0.00 | 0.490969E+10 | 0.490969E+10 | 126438.59 | 24-APR-03:43 | 126438.59 | 0.00 |
May | 0.00 | 0.00 | 0.191617E+11 | 0.191617E+11 | 81736.02 | 15-MAY-12:06 | 81736.02 | 0.00 |
June | 0.00 | 0.00 | 0.344442E+11 | 0.328913E+11 | 85781.84 | 27-JUN-17:50 | 55395.54 | 0.13 |
July | 0.00 | 0.00 | 0.418349E+11 | 0.391783E+11 | 162237.86 | 31-JUL-01:57 | 140479.80 | 0.34 |
August | 0.00 | 0.00 | 0.314813E+11 | 0.306859E+11 | 136305.97 | 28-AUG-00:13 | 136305.97 | 0.24 |
September | 0.00 | 0.00 | 0.139766E+11 | 0.138903E+11 | 75897.04 | 07-SEP-13:22 | 75897.04 | 0.01 |
October | 0.00 | 0.00 | 0.450937E+10 | 0.450777E+10 | 144962.78 | 16-OCT-03:59 | 144962.78 | 0.00 |
November | 0.00 | 0.00 | 40529581.07 | 40529581.07 | 54923.39 | 07-NOV-06:02 | 54923.39 | 0.00 |
December | 0.00 | 0.00 | 6818662.70 | 6818662.70 | 22325.01 | 26-DEC-06:02 | 22325.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150675E+12 | 0.145583E+12 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.418349E+11 | 0.391783E+11 | 162237.86 | 144962.78 | 0.34 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2468241.59 | 2468241.59 | 49.57 | 01-JAN-00:33 | 49.57 | 0.01 |
February | 0.00 | 0.00 | 0.171933E+12 | 0.171933E+12 | 346636.64 | 22-FEB-14:41 | 346636.64 | 0.00 |
March | 0.00 | 0.00 | 0.269607E+12 | 0.269607E+12 | 340273.74 | 01-MAR-07:12 | 340273.74 | 0.00 |
April | 0.00 | 0.00 | 0.263906E+12 | 0.263906E+12 | 305136.23 | 11-APR-14:19 | 305136.23 | 0.00 |
May | 0.00 | 0.00 | 0.256760E+09 | 0.256760E+09 | 265474.84 | 31-MAY-23:30 | 265474.84 | 0.01 |
June | 0.00 | 0.00 | 0.212735E+12 | 0.206262E+12 | 479731.85 | 30-JUN-18:39 | 270952.85 | 0.22 |
July | 0.00 | 0.00 | 0.297245E+12 | 0.281307E+12 | 461585.22 | 26-JUL-14:57 | 254624.83 | 0.71 |
August | 0.00 | 0.00 | 0.285042E+12 | 0.282858E+12 | 396766.89 | 11-AUG-14:05 | 396766.89 | 0.44 |
September | 0.00 | 0.00 | 0.281399E+09 | 0.281399E+09 | 289962.10 | 30-SEP-23:51 | 289962.10 | 0.06 |
October | 0.00 | 0.00 | 0.190748E+12 | 0.190748E+12 | 314586.31 | 28-OCT-11:31 | 314586.31 | 0.00 |
November | 0.00 | 0.00 | 0.225321E+12 | 0.225321E+12 | 277389.84 | 01-NOV-06:11 | 277389.84 | 0.00 |
December | 0.00 | 0.00 | 0.257203E+12 | 0.257203E+12 | 292314.25 | 14-DEC-16:06 | 292314.25 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.217428E+13 | 0.214969E+13 | 0.12 | |||
Minimum of Months | 0.00 | 0.00 | 2468241.59 | 2468241.59 | 49.57 | 49.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.297245E+12 | 0.282858E+12 | 479731.85 | 396766.89 | 0.71 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.262081E+10 | 0.262081E+10 | 6612.07 | 13-JAN-15:22 | 6612.07 | 0.00 |
February | 0.00 | 0.00 | 0.687134E+10 | 0.687134E+10 | 13268.77 | 28-FEB-11:21 | 13268.77 | 0.00 |
March | 0.00 | 0.00 | 0.143553E+11 | 0.143553E+11 | 13626.29 | 01-MAR-09:31 | 13626.29 | 0.00 |
April | 0.00 | 0.00 | 0.212653E+11 | 0.212653E+11 | 9671.47 | 20-APR-19:00 | 9671.47 | 0.00 |
May | 0.00 | 0.00 | 0.751632E+10 | 0.751632E+10 | 4769.63 | 31-MAY-23:51 | 4769.63 | 0.00 |
June | 0.00 | 0.00 | 0.125583E+11 | 0.125360E+11 | 6658.54 | 30-JUN-23:51 | 6658.08 | 0.00 |
July | 0.00 | 0.00 | 0.181936E+11 | 0.181387E+11 | 8551.50 | 31-JUL-24:00 | 8551.50 | 0.00 |
August | 0.00 | 0.00 | 0.229879E+11 | 0.229451E+11 | 9553.84 | 27-AUG-18:42 | 9553.84 | 0.00 |
September | 0.00 | 0.00 | 0.664015E+10 | 0.664015E+10 | 4063.64 | 30-SEP-23:51 | 4063.64 | 0.00 |
October | 0.00 | 0.00 | 0.104765E+11 | 0.104765E+11 | 5498.35 | 31-OCT-23:42 | 5498.35 | 0.00 |
November | 0.00 | 0.00 | 0.119363E+11 | 0.119363E+11 | 13876.10 | 29-NOV-13:31 | 13876.10 | 0.00 |
December | 0.00 | 0.00 | 0.157662E+11 | 0.157662E+11 | 14327.47 | 14-DEC-14:01 | 14327.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.151188E+12 | 0.151068E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.262081E+10 | 0.262081E+10 | 4063.64 | 4063.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.229879E+11 | 0.229451E+11 | 14327.47 | 14327.47 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.115267E+11 | 0.115267E+11 | 43538.58 | 13-JAN-15:22 | 43538.58 | 0.00 |
February | 0.00 | 0.00 | 0.534969E+11 | 0.534969E+11 | 126140.53 | 28-FEB-11:21 | 126140.53 | 0.00 |
March | 0.00 | 0.00 | 0.124132E+12 | 0.124132E+12 | 130060.95 | 01-MAR-09:31 | 130060.95 | 0.00 |
April | 0.00 | 0.00 | 0.191651E+12 | 0.191651E+12 | 93222.36 | 20-APR-19:00 | 93222.36 | 0.00 |
May | 0.00 | 0.00 | 0.652083E+11 | 0.652083E+11 | 44239.15 | 31-MAY-23:41 | 44239.15 | 0.00 |
June | 0.00 | 0.00 | 0.117963E+12 | 0.117741E+12 | 63915.16 | 30-JUN-23:21 | 63883.79 | 0.00 |
July | 0.00 | 0.00 | 0.170907E+12 | 0.170360E+12 | 82972.31 | 31-JUL-23:15 | 82972.31 | 0.00 |
August | 0.00 | 0.00 | 0.215198E+12 | 0.214776E+12 | 90641.65 | 10-AUG-19:00 | 90641.65 | 0.00 |
September | 0.00 | 0.00 | 0.529395E+11 | 0.529395E+11 | 32648.44 | 30-SEP-23:32 | 32648.44 | 0.00 |
October | 0.00 | 0.00 | 0.833020E+11 | 0.833020E+11 | 45717.70 | 31-OCT-23:03 | 45717.70 | 0.00 |
November | 0.00 | 0.00 | 0.932514E+11 | 0.932514E+11 | 132057.41 | 29-NOV-13:31 | 132057.41 | 0.00 |
December | 0.00 | 0.00 | 0.129418E+12 | 0.129418E+12 | 136651.00 | 14-DEC-14:01 | 136651.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.130899E+13 | 0.130780E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.115267E+11 | 0.115267E+11 | 32648.44 | 32648.44 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.215198E+12 | 0.214776E+12 | 136651.00 | 136651.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.267739E+09 | 0.267739E+09 | 1244.85 | 19-JAN-11:04 | 1244.85 | 0.00 |
February | 0.00 | 0.00 | 0.359569E+10 | 0.359569E+10 | 12634.60 | 28-FEB-11:21 | 12634.60 | 0.00 |
March | 0.00 | 0.00 | 0.103165E+11 | 0.103165E+11 | 12986.18 | 01-MAR-09:31 | 12986.18 | 0.00 |
April | 0.00 | 0.00 | 0.174735E+11 | 0.174735E+11 | 9278.68 | 20-APR-19:00 | 9278.68 | 0.00 |
May | 0.00 | 0.00 | 0.551920E+10 | 0.551920E+10 | 4292.08 | 31-MAY-23:12 | 4292.08 | 0.00 |
June | 0.00 | 0.00 | 0.114286E+11 | 0.114064E+11 | 6295.13 | 30-JUN-23:11 | 6289.25 | 0.00 |
July | 0.00 | 0.00 | 0.167247E+11 | 0.166701E+11 | 8210.93 | 31-JUL-23:04 | 8210.93 | 0.00 |
August | 0.00 | 0.00 | 0.208905E+11 | 0.208491E+11 | 9130.65 | 10-AUG-19:00 | 9130.65 | 0.00 |
September | 0.00 | 0.00 | 0.357416E+10 | 0.357416E+10 | 2999.05 | 02-SEP-18:16 | 2999.05 | 0.00 |
October | 0.00 | 0.00 | 0.588367E+10 | 0.588367E+10 | 4389.80 | 03-OCT-15:53 | 4389.80 | 0.00 |
November | 0.00 | 0.00 | 0.739534E+10 | 0.739534E+10 | 13190.84 | 29-NOV-13:31 | 13190.84 | 0.00 |
December | 0.00 | 0.00 | 0.110515E+11 | 0.110515E+11 | 13680.80 | 14-DEC-14:01 | 13680.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.114121E+12 | 0.114003E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.267739E+09 | 0.267739E+09 | 1244.85 | 1244.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.208905E+11 | 0.208491E+11 | 13680.80 | 13680.80 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 621719.38 | 4274307.30 | 17-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 479854.04 | 3096685.42 | 06-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 320656.45 | 3293902.64 | 21-MAR-04:01 |
April | 0.00 | 0.00 | 01-APR-00:01 | 92183.05 | 3271084.28 | 24-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 7683.42 | 2559246.50 | 27-MAY-04:01 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 269.25 | 143488.53 | 15-JUN-09:22 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 313.24 | 412610.17 | 05-JUL-09:17 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4561.15 | 3056717.07 | 31-AUG-05:01 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 40348.49 | 3098514.29 | 30-SEP-04:01 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 216325.17 | 3257233.42 | 11-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 548047.61 | 3460182.84 | 24-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 636465.57 | 3306327.14 | 05-DEC-05:01 |
Annual Sum or Average | 0.00 | 246303.62 | ||||
Minimum of Months | 0.00 | 0.00 | 269.25 | 143488.53 | ||
Maximum of Months | 0.00 | 0.00 | 636465.57 | 4274307.30 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1266.88 | 11120.24 | 18-JAN-22:01 | 95076.56 | 800010.27 | 22-JAN-23:12 |
February | 72734.58 | 797390.28 | 17-FEB-07:06 | 70662.79 | 686048.99 | 12-FEB-21:32 |
March | 108452.02 | 803390.25 | 23-MAR-14:06 | 2961.94 | 605604.61 | 12-MAR-02:30 |
April | 115937.99 | 1045348.26 | 11-APR-13:44 | 4231.40 | 466893.22 | 14-APR-09:02 |
May | 61783.06 | 1099561.63 | 31-MAY-16:00 | 215849.97 | 799900.56 | 21-MAY-06:02 |
June | 330146.95 | 2193146.70 | 20-JUN-14:00 | 61176.15 | 746371.29 | 23-JUN-22:01 |
July | 427846.15 | 2592003.22 | 21-JUL-12:05 | 23867.24 | 683122.48 | 31-JUL-01:31 |
August | 289568.88 | 2143521.39 | 24-AUG-14:05 | 9734.09 | 721010.45 | 31-AUG-24:00 |
September | 17861.72 | 805956.23 | 18-SEP-13:37 | 331494.16 | 799875.62 | 03-SEP-10:00 |
October | 77219.57 | 1002617.05 | 03-OCT-13:41 | 109192.07 | 706657.32 | 19-OCT-09:32 |
November | 96553.18 | 715413.39 | 03-NOV-03:33 | 2094.52 | 543870.07 | 01-NOV-02:27 |
December | 105083.31 | 759778.63 | 05-DEC-20:08 | 3254.59 | 696268.94 | 05-DEC-21:31 |
Annual Sum or Average | 142628.44 | 77278.01 | ||||
Minimum of Months | 1266.88 | 11120.24 | 2094.52 | 466893.22 | ||
Maximum of Months | 427846.15 | 2592003.22 | 331494.16 | 800010.27 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.10 | 126.19 | 28-JAN-05:13 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 79342.44 | 369567.76 | 10-FEB-17:13 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 150951.94 | 818485.86 | 22-MAR-14:10 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 207184.44 | 1103539.60 | 13-APR-14:07 | 0.00 | 0.00 | 01-APR-00:01 |
May | 71360.41 | 1095901.29 | 31-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 361890.62 | 2008312.57 | 20-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 494550.01 | 2271931.87 | 21-JUL-12:05 | 0.00 | 0.00 | 01-JUL-00:01 |
August | 375874.56 | 2144737.94 | 11-AUG-14:40 | 0.00 | 0.00 | 01-AUG-00:01 |
September | 20870.46 | 774248.66 | 18-SEP-14:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 88359.73 | 1124558.94 | 03-OCT-13:58 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 185103.71 | 467342.77 | 10-NOV-06:01 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 174745.04 | 559146.29 | 26-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 184942.91 | 0.00 | ||||
Minimum of Months | 0.10 | 126.19 | 0.00 | 0.00 | ||
Maximum of Months | 494550.01 | 2271931.87 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 17739.75 | 62780.95 | 09-JAN-12:18 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 17847.57 | 62781.16 | 28-FEB-12:59 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 18970.66 | 62780.31 | 06-MAR-12:36 |
April | 0.00 | 0.00 | 01-APR-00:01 | 17768.27 | 62781.22 | 06-APR-11:54 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 18229.21 | 62780.51 | 11-MAY-11:32 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18000.47 | 61218.34 | 01-JUN-11:21 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15940.88 | 58673.33 | 03-JUL-11:58 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17042.25 | 56912.78 | 01-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 15913.23 | 56529.28 | 29-SEP-11:32 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16196.61 | 58205.24 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17004.75 | 60510.85 | 30-NOV-12:37 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 17043.40 | 62780.28 | 29-DEC-12:22 |
Annual Sum or Average | 0.00 | 17305.15 | ||||
Minimum of Months | 0.00 | 0.00 | 15913.23 | 56529.28 | ||
Maximum of Months | 0.00 | 0.00 | 18970.66 | 62781.22 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 159.77 | 27877.09 | 27-JAN-02:70 | 3759.63 | 168140.25 | 22-JAN-18:20 |
February | 94316.58 | 653586.38 | 12-FEB-23:18 | 30.10 | 46838.92 | 17-FEB-06:56 |
March | 95675.43 | 789683.75 | 08-MAR-05:16 | 4628.79 | 70114.94 | 23-MAR-13:40 |
April | 46324.68 | 1025244.84 | 11-APR-13:46 | 6236.49 | 158600.96 | 06-APR-23:01 |
May | 68150.70 | 1276864.24 | 31-MAY-16:00 | 1879.38 | 142923.10 | 28-MAY-05:10 |
June | 415924.57 | 3115758.41 | 29-JUN-15:10 | 8.05 | 33919.33 | 17-JUN-12:35 |
July | 538763.01 | 3212682.76 | 21-JUL-15:00 | 228.65 | 87040.68 | 04-JUL-07:10 |
August | 352210.68 | 3162222.10 | 23-AUG-15:40 | 693.64 | 91302.40 | 30-AUG-23:40 |
September | 16738.30 | 889874.50 | 18-SEP-13:58 | 1515.82 | 157170.64 | 23-SEP-03:40 |
October | 98674.30 | 951894.62 | 03-OCT-13:44 | 81.25 | 65151.49 | 05-OCT-09:50 |
November | 19353.79 | 687162.73 | 03-NOV-03:39 | 4418.40 | 56774.60 | 06-NOV-06:08 |
December | 22651.41 | 723694.10 | 15-DEC-08:30 | 6661.50 | 154826.71 | 29-DEC-16:30 |
Annual Sum or Average | 148098.49 | 2526.37 | ||||
Minimum of Months | 159.77 | 27877.09 | 8.05 | 33919.33 | ||
Maximum of Months | 538763.01 | 3212682.76 | 6661.50 | 168140.25 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.887556E+10 | 0.60 | 11812.93 | 02-JAN-05:01 | 1.28 |
February | 0.750078E+10 | 0.55 | 22281.74 | 09-FEB-06:01 | 1.67 |
March | 0.920401E+10 | 0.57 | 21987.00 | 18-MAR-05:01 | 1.66 |
April | 0.119532E+11 | 0.62 | 22281.74 | 08-APR-05:01 | 1.67 |
May | 0.138664E+11 | 0.67 | 25847.61 | 30-MAY-05:01 | 1.77 |
June | 0.160798E+11 | 0.73 | 27378.75 | 14-JUN-04:11 | 1.81 |
July | 0.169554E+11 | 0.72 | 27378.75 | 08-JUL-04:11 | 1.80 |
August | 0.170078E+11 | 0.74 | 23025.51 | 28-AUG-04:11 | 1.68 |
September | 0.104123E+11 | 0.57 | 21587.39 | 30-SEP-05:01 | 1.65 |
October | 0.896904E+10 | 0.52 | 22281.74 | 14-OCT-05:01 | 1.67 |
November | 0.783503E+10 | 0.52 | 8116.17 | 01-NOV-05:01 | 1.09 |
December | 0.808392E+10 | 0.53 | 8116.17 | 01-DEC-05:01 | 1.09 |
Annual Sum or Average | 0.136743E+12 | 0.61 | |||
Minimum of Months | 0.750078E+10 | 0.52 | 8116.17 | 1.09 | |
Maximum of Months | 0.170078E+11 | 0.74 | 27378.75 | 1.81 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.105224E+12 | 0.71 | 125863.03 | 02-JAN-04:01 | 1.35 |
February | 0.944746E+11 | 0.70 | 125863.03 | 01-FEB-06:01 | 1.36 |
March | 0.997610E+11 | 0.65 | 125863.03 | 06-MAR-05:01 | 1.36 |
April | 0.102289E+12 | 0.61 | 213944.70 | 27-APR-05:01 | 1.69 |
May | 0.127546E+12 | 0.65 | 254328.66 | 31-MAY-05:01 | 1.82 |
June | 0.145857E+12 | 0.71 | 254328.66 | 03-JUN-05:01 | 1.81 |
July | 0.139991E+12 | 0.66 | 254328.66 | 01-JUL-05:01 | 1.81 |
August | 0.134673E+12 | 0.67 | 187343.05 | 11-AUG-15:30 | 1.59 |
September | 0.926343E+11 | 0.56 | 222829.86 | 15-SEP-05:01 | 1.72 |
October | 0.885697E+11 | 0.58 | 244328.24 | 05-OCT-05:01 | 1.79 |
November | 0.101663E+12 | 0.71 | 125863.03 | 06-NOV-05:01 | 1.35 |
December | 0.107384E+12 | 0.72 | 125863.03 | 02-DEC-06:01 | 1.36 |
Annual Sum or Average | 0.134007E+13 | 0.66 | |||
Minimum of Months | 0.885697E+11 | 0.56 | 125863.03 | 1.35 | |
Maximum of Months | 0.145857E+12 | 0.72 | 254328.66 | 1.82 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116626E+11 | 0.66 | 12022.36 | 11-JAN-06:01 | 1.11 |
February | 0.103833E+11 | 0.65 | 12022.36 | 01-FEB-05:01 | 1.11 |
March | 0.112596E+11 | 0.63 | 12022.36 | 09-MAR-06:01 | 1.10 |
April | 0.955258E+10 | 0.54 | 12022.36 | 18-APR-05:01 | 1.10 |
May | 0.980921E+10 | 0.50 | 14194.65 | 31-MAY-15:20 | 1.18 |
June | 0.115104E+11 | 0.53 | 27731.73 | 28-JUN-05:01 | 1.55 |
July | 0.110573E+11 | 0.50 | 25107.30 | 08-JUL-05:01 | 1.49 |
August | 0.102354E+11 | 0.49 | 18579.32 | 01-AUG-05:01 | 1.31 |
September | 0.768243E+10 | 0.44 | 12022.36 | 05-SEP-05:01 | 1.10 |
October | 0.991660E+10 | 0.56 | 12022.36 | 02-OCT-04:12 | 1.10 |
November | 0.112602E+11 | 0.66 | 12022.36 | 01-NOV-04:01 | 1.11 |
December | 0.119376E+11 | 0.67 | 12022.36 | 01-DEC-05:01 | 1.11 |
Annual Sum or Average | 0.126267E+12 | 0.57 | |||
Minimum of Months | 0.768243E+10 | 0.44 | 12022.36 | 1.10 | |
Maximum of Months | 0.119376E+11 | 0.67 | 27731.73 | 1.55 |
Report: FanReportMonthly
For: CAV_BAS SZVAV FAN
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.340365E+10 | 0.42 | 16029.42 | 03-JAN-07:55 | 1.84 |
February | 0.307177E+10 | 0.43 | 16029.42 | 09-FEB-06:01 | 1.83 |
March | 0.326866E+10 | 0.45 | 16029.42 | 01-MAR-07:10 | 1.84 |
April | 0.558551E+10 | 0.50 | 16029.42 | 01-APR-05:01 | 1.84 |
May | 0.797088E+10 | 0.57 | 16029.42 | 01-MAY-04:12 | 1.83 |
June | 0.875636E+10 | 0.63 | 16029.42 | 01-JUN-04:12 | 1.83 |
July | 0.891436E+10 | 0.61 | 16029.42 | 01-JUL-04:11 | 1.82 |
August | 0.108155E+11 | 0.68 | 16029.42 | 01-AUG-04:12 | 1.82 |
September | 0.722809E+10 | 0.56 | 16029.42 | 01-SEP-04:12 | 1.83 |
October | 0.439618E+10 | 0.46 | 16029.42 | 02-OCT-04:11 | 1.83 |
November | 0.278010E+10 | 0.41 | 16029.42 | 01-NOV-05:01 | 1.84 |
December | 0.292438E+10 | 0.41 | 16029.42 | 05-DEC-19:52 | 1.84 |
Annual Sum or Average | 0.691155E+11 | 0.51 | |||
Minimum of Months | 0.278010E+10 | 0.41 | 16029.42 | 1.82 | |
Maximum of Months | 0.108155E+11 | 0.68 | 16029.42 | 1.84 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SYS11 FAN
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.267530E+11 | 0.52 | 9988.43 | 01-JAN-00:01 | 0.52 |
February | 0.431333E+11 | 0.63 | 33267.58 | 01-FEB-00:03 | 0.86 |
March | 0.579508E+11 | 0.69 | 33267.58 | 01-MAR-00:02 | 0.86 |
April | 0.760102E+11 | 0.81 | 33267.58 | 01-APR-00:02 | 0.86 |
May | 0.267795E+11 | 0.52 | 33267.58 | 31-MAY-23:03 | 0.86 |
June | 0.426683E+11 | 0.61 | 33267.58 | 01-JUN-00:13 | 0.86 |
July | 0.669830E+11 | 0.74 | 33267.58 | 01-JUL-00:01 | 0.86 |
August | 0.863751E+11 | 0.85 | 33267.58 | 01-AUG-00:01 | 0.86 |
September | 0.259174E+11 | 0.52 | 33267.58 | 30-SEP-23:03 | 0.86 |
October | 0.478989E+11 | 0.63 | 33267.58 | 01-OCT-00:03 | 0.86 |
November | 0.560598E+11 | 0.69 | 33267.58 | 01-NOV-00:01 | 0.86 |
December | 0.716301E+11 | 0.77 | 33267.58 | 01-DEC-00:01 | 0.86 |
Annual Sum or Average | 0.628159E+12 | 0.66 | |||
Minimum of Months | 0.259174E+11 | 0.52 | 9988.43 | 0.52 | |
Maximum of Months | 0.863751E+11 | 0.85 | 33267.58 | 0.86 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.357824E+10 | 1.44 | 1335.96 | 01-JAN-11:40 | 1.43 |
February | 0.323195E+10 | 1.44 | 1335.96 | 01-FEB-05:01 | 1.44 |
March | 0.357824E+10 | 1.44 | 1335.96 | 01-MAR-12:07 | 1.44 |
April | 0.346281E+10 | 1.43 | 1335.96 | 01-APR-06:42 | 1.44 |
May | 0.357824E+10 | 1.43 | 1335.96 | 01-MAY-01:00 | 1.43 |
June | 0.346281E+10 | 1.43 | 1335.96 | 01-JUN-17:36 | 1.43 |
July | 0.357824E+10 | 1.42 | 1335.96 | 01-JUL-10:45 | 1.42 |
August | 0.357824E+10 | 1.42 | 1335.96 | 01-AUG-10:43 | 1.42 |
September | 0.346281E+10 | 1.43 | 1335.96 | 01-SEP-02:40 | 1.43 |
October | 0.357824E+10 | 1.43 | 1335.96 | 01-OCT-00:33 | 1.43 |
November | 0.346281E+10 | 1.44 | 1335.96 | 01-NOV-00:23 | 1.44 |
December | 0.357824E+10 | 1.44 | 1335.96 | 01-DEC-01:39 | 1.44 |
Annual Sum or Average | 0.421308E+11 | 1.43 | |||
Minimum of Months | 0.323195E+10 | 1.42 | 1335.96 | 1.42 | |
Maximum of Months | 0.357824E+10 | 1.44 | 1335.96 | 1.44 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.344663E+11 | 1.44 | 12868.24 | 02-JAN-12:17 | 1.43 |
February | 0.311308E+11 | 1.44 | 12868.24 | 01-FEB-00:02 | 1.44 |
March | 0.344663E+11 | 1.44 | 12868.24 | 01-MAR-10:26 | 1.44 |
April | 0.333545E+11 | 1.43 | 12868.24 | 17-APR-05:03 | 1.43 |
May | 0.344663E+11 | 1.43 | 12868.24 | 01-MAY-00:50 | 1.43 |
June | 0.333545E+11 | 1.43 | 12868.24 | 01-JUN-02:35 | 1.43 |
July | 0.344663E+11 | 1.42 | 12868.24 | 01-JUL-00:37 | 1.42 |
August | 0.344663E+11 | 1.42 | 12868.24 | 01-AUG-00:01 | 1.42 |
September | 0.333545E+11 | 1.43 | 12868.24 | 01-SEP-00:40 | 1.43 |
October | 0.344663E+11 | 1.43 | 12868.24 | 01-OCT-00:22 | 1.43 |
November | 0.333545E+11 | 1.44 | 12868.24 | 01-NOV-00:32 | 1.44 |
December | 0.344663E+11 | 1.44 | 12868.24 | 01-DEC-01:23 | 1.44 |
Annual Sum or Average | 0.405813E+12 | 1.43 | |||
Minimum of Months | 0.311308E+11 | 1.42 | 12868.24 | 1.42 | |
Maximum of Months | 0.344663E+11 | 1.44 | 12868.24 | 1.44 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.349396E+10 | 1.44 | 1304.49 | 02-JAN-22:16 | 1.44 |
February | 0.315583E+10 | 1.44 | 1304.49 | 01-FEB-03:23 | 1.44 |
March | 0.349396E+10 | 1.44 | 1304.49 | 05-MAR-02:54 | 1.44 |
April | 0.338125E+10 | 1.43 | 1304.49 | 01-APR-04:53 | 1.44 |
May | 0.349396E+10 | 1.43 | 1304.49 | 01-MAY-01:00 | 1.43 |
June | 0.338125E+10 | 1.43 | 1304.49 | 25-JUN-02:41 | 1.42 |
July | 0.349396E+10 | 1.42 | 1304.49 | 01-JUL-07:27 | 1.42 |
August | 0.349396E+10 | 1.42 | 1304.49 | 01-AUG-09:10 | 1.42 |
September | 0.338125E+10 | 1.43 | 1304.49 | 01-SEP-08:22 | 1.43 |
October | 0.349396E+10 | 1.43 | 1304.49 | 01-OCT-05:34 | 1.43 |
November | 0.338125E+10 | 1.44 | 1304.49 | 05-NOV-06:15 | 1.44 |
December | 0.349396E+10 | 1.44 | 1304.49 | 02-DEC-06:44 | 1.44 |
Annual Sum or Average | 0.411386E+11 | 1.43 | |||
Minimum of Months | 0.315583E+10 | 1.42 | 1304.49 | 1.42 | |
Maximum of Months | 0.349396E+10 | 1.44 | 1304.49 | 1.44 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.156651E+10 | 0.140986E+10 | 4500.12 | 02-JAN-05:22 | 4050.11 | 4050.11 | 57.70 | 22.46 |
February | 0.106999E+10 | 0.962989E+09 | 4471.25 | 27-FEB-06:01 | 4024.12 | 4024.12 | 56.28 | 22.38 |
March | 0.750819E+09 | 0.675737E+09 | 4407.55 | 06-MAR-05:02 | 3966.79 | 3966.79 | 51.90 | 22.21 |
April | 0.207187E+09 | 0.186469E+09 | 4336.46 | 03-APR-05:01 | 3902.82 | 3902.82 | 53.85 | 21.96 |
May | 18223705.57 | 16401335.01 | 2580.72 | 27-MAY-05:02 | 2322.65 | 2322.65 | 38.47 | 14.97 |
June | 640355.00 | 576319.50 | 131.16 | 15-JUN-09:22 | 118.05 | 118.05 | 20.84 | 0.77 |
July | 759250.22 | 683325.20 | 367.98 | 05-JUL-09:17 | 331.18 | 331.18 | 20.46 | 2.19 |
August | 10930303.57 | 9837273.21 | 3185.63 | 31-AUG-05:01 | 2867.07 | 2867.07 | 35.54 | 17.74 |
September | 91401474.19 | 82261326.77 | 3164.87 | 28-SEP-05:01 | 2848.38 | 2848.38 | 38.52 | 17.64 |
October | 0.498004E+09 | 0.448204E+09 | 4337.88 | 30-OCT-05:01 | 3904.10 | 3904.10 | 52.92 | 21.97 |
November | 0.128408E+10 | 0.115567E+10 | 4373.69 | 20-NOV-06:02 | 3936.32 | 3936.32 | 55.84 | 22.06 |
December | 0.159470E+10 | 0.143523E+10 | 4391.37 | 04-DEC-05:02 | 3952.23 | 3952.23 | 54.18 | 22.14 |
Annual Sum or Average | 0.709326E+10 | 0.638393E+10 | ||||||
Minimum of Months | 640355.00 | 576319.50 | 131.16 | 118.05 | 118.05 | 20.46 | 0.77 | |
Maximum of Months | 0.159470E+10 | 0.143523E+10 | 4500.12 | 4050.11 | 4050.11 | 57.70 | 22.46 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 29309.93 | 26378.94 | 8.89 | 28-JAN-05:13 | 8.00 | 8.00 | 6.70 | 0.08 |
February | 0.129336E+10 | 0.116403E+10 | 1832.73 | 22-FEB-06:02 | 1649.45 | 1649.45 | 7.08 | 16.34 |
March | 0.244064E+10 | 0.219658E+10 | 3045.01 | 22-MAR-14:10 | 2740.51 | 2740.51 | 8.61 | 27.20 |
April | 0.232882E+10 | 0.209594E+10 | 3406.29 | 13-APR-13:59 | 3065.66 | 3065.66 | 8.45 | 30.29 |
May | 0.580134E+09 | 0.522121E+09 | 2687.62 | 14-MAY-11:31 | 2418.86 | 2418.86 | 9.57 | 24.06 |
June | 0.312211E+10 | 0.280990E+10 | 7696.71 | 20-JUN-13:20 | 6927.04 | 6927.04 | 8.69 | 59.62 |
July | 0.469700E+10 | 0.422730E+10 | 15847.63 | 22-JUL-05:02 | 14262.86 | 14262.86 | 10.29 | 91.86 |
August | 0.385524E+10 | 0.346971E+10 | 9131.37 | 11-AUG-14:50 | 8218.23 | 8218.23 | 6.73 | 66.87 |
September | 0.245982E+09 | 0.221384E+09 | 2748.51 | 01-SEP-13:02 | 2473.66 | 2473.66 | 7.30 | 24.60 |
October | 0.157404E+10 | 0.141664E+10 | 3397.40 | 03-OCT-13:58 | 3057.66 | 3057.66 | 7.86 | 30.22 |
November | 0.237199E+10 | 0.213480E+10 | 2255.25 | 07-NOV-06:01 | 2029.73 | 2029.73 | 9.78 | 20.18 |
December | 0.189948E+10 | 0.170953E+10 | 2255.24 | 26-DEC-06:02 | 2029.71 | 2029.71 | 9.68 | 20.18 |
Annual Sum or Average | 0.244088E+11 | 0.219680E+11 | ||||||
Minimum of Months | 29309.93 | 26378.94 | 8.89 | 8.00 | 8.00 | 6.70 | 0.08 | |
Maximum of Months | 0.469700E+10 | 0.422730E+10 | 15847.63 | 14262.86 | 14262.86 | 10.29 | 91.86 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.377000E+10 | 0.339300E+10 | 10421.25 | 01-JAN-00:01 | 9379.13 | 9379.13 | 6.74 | 54.78 |
February | 0.620929E+10 | 0.558836E+10 | 10421.25 | 01-FEB-00:03 | 9379.13 | 9379.13 | 6.79 | 54.78 |
March | 0.198758E+11 | 0.178883E+11 | 10421.25 | 01-MAR-00:04 | 9379.13 | 9379.13 | 8.05 | 54.78 |
April | 0.240102E+11 | 0.216091E+11 | 10421.25 | 01-APR-00:01 | 9379.13 | 9379.13 | 10.35 | 54.78 |
May | 0.866897E+10 | 0.780208E+10 | 10421.25 | 01-MAY-04:18 | 9379.13 | 9379.13 | 7.39 | 54.78 |
June | 0.160557E+11 | 0.144501E+11 | 10421.25 | 01-JUN-00:13 | 9379.13 | 9379.13 | 7.96 | 54.78 |
July | 0.233735E+11 | 0.210362E+11 | 10421.25 | 01-JUL-00:03 | 9379.13 | 9379.13 | 8.50 | 54.78 |
August | 0.243184E+11 | 0.218865E+11 | 10421.25 | 01-AUG-00:01 | 9379.13 | 9379.13 | 10.16 | 54.78 |
September | 0.425625E+10 | 0.383063E+10 | 10421.25 | 01-SEP-01:10 | 9379.13 | 9379.13 | 6.86 | 54.78 |
October | 0.835338E+10 | 0.751804E+10 | 10421.25 | 01-OCT-00:02 | 9379.13 | 9379.13 | 7.74 | 54.78 |
November | 0.258107E+11 | 0.232297E+11 | 10421.25 | 01-NOV-00:03 | 9379.13 | 9379.13 | 8.05 | 54.78 |
December | 0.254233E+11 | 0.228810E+11 | 10421.25 | 01-DEC-00:01 | 9379.13 | 9379.13 | 10.10 | 54.78 |
Annual Sum or Average | 0.190126E+12 | 0.171113E+12 | ||||||
Minimum of Months | 0.377000E+10 | 0.339300E+10 | 10421.25 | 9379.13 | 9379.13 | 6.74 | 54.78 | |
Maximum of Months | 0.258107E+11 | 0.232297E+11 | 10421.25 | 9379.13 | 9379.13 | 10.35 | 54.78 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 6.74 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 7.86 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 10.35 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 7.06 | 0.00 |
June | 0.856627E+09 | 0.770964E+09 | 10421.25 | 13-JUN-12:20 | 9379.13 | 9379.13 | 13.99 | 27.39 |
July | 0.182580E+10 | 0.164322E+10 | 10421.25 | 03-JUL-15:00 | 9379.13 | 9379.13 | 13.55 | 27.39 |
August | 0.853501E+09 | 0.768151E+09 | 10421.25 | 02-AUG-13:00 | 9379.13 | 9379.13 | 13.82 | 27.39 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 7.07 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 7.97 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 8.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 10.10 | 0.00 |
Annual Sum or Average | 0.353593E+10 | 0.318234E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 0.00 | |
Maximum of Months | 0.182580E+10 | 0.164322E+10 | 10421.25 | 9379.13 | 9379.13 | 13.99 | 27.39 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:02 | 16.86 | 16.86 | 56.64 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 56.62 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 56.62 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:01 | 16.86 | 16.86 | 56.62 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:01 | 16.86 | 16.86 | 56.88 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:01 | 16.86 | 16.86 | 56.67 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:01 | 16.86 | 16.86 | 56.83 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:01 | 16.86 | 16.86 | 56.83 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:01 | 16.86 | 16.86 | 56.92 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:01 | 16.86 | 16.86 | 56.96 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 56.86 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 56.74 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.62 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 56.96 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.968983E+10 | 0.872085E+10 | 26866.44 | 27-JAN-02:70 | 24179.80 | 24179.80 | 21.19 | 77.33 |
February | 0.160205E+11 | 0.144184E+11 | 26903.87 | 12-FEB-23:18 | 24213.48 | 24213.48 | 23.12 | 77.33 |
March | 0.512231E+11 | 0.461008E+11 | 26912.02 | 08-MAR-05:16 | 24220.82 | 24220.82 | 23.54 | 77.33 |
April | 0.618265E+11 | 0.556438E+11 | 26926.14 | 11-APR-13:46 | 24233.52 | 24233.52 | 24.27 | 77.33 |
May | 0.223582E+11 | 0.201224E+11 | 26941.40 | 31-MAY-16:00 | 24247.26 | 24247.26 | 25.05 | 77.33 |
June | 0.433081E+11 | 0.389773E+11 | 53922.30 | 29-JUN-15:10 | 48530.07 | 48530.07 | 25.92 | 154.65 |
July | 0.640891E+11 | 0.576802E+11 | 53929.08 | 21-JUL-15:00 | 48536.17 | 48536.17 | 26.07 | 154.65 |
August | 0.645189E+11 | 0.580670E+11 | 53925.55 | 23-AUG-15:40 | 48532.99 | 48532.99 | 25.99 | 154.65 |
September | 0.108794E+11 | 0.979144E+10 | 26918.02 | 18-SEP-13:58 | 24226.22 | 24226.22 | 23.85 | 77.33 |
October | 0.215466E+11 | 0.193919E+11 | 26921.74 | 03-OCT-13:44 | 24229.57 | 24229.57 | 24.05 | 77.33 |
November | 0.665345E+11 | 0.598811E+11 | 26905.88 | 03-NOV-03:39 | 24215.29 | 24215.29 | 23.23 | 77.33 |
December | 0.655121E+11 | 0.589609E+11 | 26908.07 | 15-DEC-08:30 | 24217.26 | 24217.26 | 23.34 | 77.33 |
Annual Sum or Average | 0.497507E+12 | 0.447756E+12 | ||||||
Minimum of Months | 0.968983E+10 | 0.872085E+10 | 26866.44 | 24179.80 | 24179.80 | 21.19 | 77.33 | |
Maximum of Months | 0.665345E+11 | 0.598811E+11 | 53929.08 | 48536.17 | 48536.17 | 26.07 | 154.65 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 36.93 | 36.93 | 621719.38 | 4274307.30 | 17-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 36.01 | 82.20 | 479854.04 | 3096685.42 | 06-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 41.80 | 82.20 | 320656.45 | 3293902.64 | 21-MAR-04:01 |
April | 0.00 | 0.00 | 01-APR-00:01 | 30.91 | 30.91 | 92183.05 | 3271084.28 | 24-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 21.93 | 21.93 | 7683.42 | 2559246.50 | 27-MAY-04:01 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 23.53 | 23.53 | 269.25 | 143488.53 | 15-JUN-09:22 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 20.62 | 20.62 | 313.24 | 412610.17 | 05-JUL-09:17 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 19.98 | 19.98 | 4561.15 | 3056717.07 | 31-AUG-05:01 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.04 | 22.04 | 40348.49 | 3098514.29 | 30-SEP-04:01 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 24.00 | 24.00 | 216325.17 | 3257233.42 | 11-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 32.37 | 82.20 | 548047.61 | 3460182.84 | 24-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 39.48 | 39.48 | 636465.57 | 3306327.14 | 05-DEC-05:01 |
Annual Sum or Average | 0.00 | 246303.62 | ||||||
Minimum of Months | 0.00 | 0.00 | 19.98 | 19.98 | 269.25 | 143488.53 | ||
Maximum of Months | 0.00 | 0.00 | 41.80 | 82.20 | 636465.57 | 4274307.30 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1266.88 | 11120.24 | 18-JAN-22:01 | 6.75 | 6.70 | 95076.56 | 800010.27 | 22-JAN-23:12 |
February | 72734.58 | 797390.28 | 17-FEB-07:06 | 10.17 | 6.70 | 70662.79 | 686048.99 | 12-FEB-21:32 |
March | 108452.02 | 803390.25 | 23-MAR-14:06 | 10.20 | 6.70 | 2961.94 | 605604.61 | 12-MAR-02:30 |
April | 115937.99 | 1045348.26 | 11-APR-13:44 | 11.25 | 6.70 | 4231.40 | 466893.22 | 14-APR-09:02 |
May | 61783.06 | 1099561.63 | 31-MAY-16:00 | 11.49 | 6.70 | 215849.97 | 799900.56 | 21-MAY-06:02 |
June | 330146.95 | 2193146.70 | 20-JUN-14:00 | 11.48 | 6.70 | 61176.15 | 746371.29 | 23-JUN-22:01 |
July | 427846.15 | 2592003.22 | 21-JUL-12:05 | 12.35 | 6.70 | 23867.24 | 683122.48 | 31-JUL-01:31 |
August | 289568.88 | 2143521.39 | 24-AUG-14:05 | 11.37 | 6.70 | 9734.09 | 721010.45 | 31-AUG-24:00 |
September | 17861.72 | 805956.23 | 18-SEP-13:37 | 10.55 | 7.04 | 331494.16 | 799875.62 | 03-SEP-10:00 |
October | 77219.57 | 1002617.05 | 03-OCT-13:41 | 11.07 | 6.70 | 109192.07 | 706657.32 | 19-OCT-09:32 |
November | 96553.18 | 715413.39 | 03-NOV-03:33 | 9.82 | 6.70 | 2094.52 | 543870.07 | 01-NOV-02:27 |
December | 105083.31 | 759778.63 | 05-DEC-20:08 | 10.01 | 6.70 | 3254.59 | 696268.94 | 05-DEC-21:31 |
Annual Sum or Average | 142628.44 | 77278.01 | ||||||
Minimum of Months | 1266.88 | 11120.24 | 6.75 | 6.70 | 2094.52 | 466893.22 | ||
Maximum of Months | 427846.15 | 2592003.22 | 12.35 | 7.04 | 331494.16 | 800010.27 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.10 | 126.19 | 28-JAN-05:13 | 7.10 | 6.72 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 79342.44 | 369567.76 | 10-FEB-17:13 | 12.17 | 7.78 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 150951.94 | 818485.86 | 22-MAR-14:10 | 13.89 | 8.99 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 207184.44 | 1103539.60 | 13-APR-14:07 | 15.50 | 6.93 | 0.00 | 0.00 | 01-APR-00:01 |
May | 71360.41 | 1095901.29 | 31-MAY-16:00 | 20.05 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 361890.62 | 2008312.57 | 20-JUN-14:00 | 15.71 | 6.94 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 494550.01 | 2271931.87 | 21-JUL-12:05 | 15.42 | 6.70 | 0.00 | 0.00 | 01-JUL-00:01 |
August | 375874.56 | 2144737.94 | 11-AUG-14:40 | 14.61 | 6.70 | 0.00 | 0.00 | 01-AUG-00:01 |
September | 20870.46 | 774248.66 | 18-SEP-14:10 | 18.16 | 8.03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 88359.73 | 1124558.94 | 03-OCT-13:58 | 15.59 | 7.82 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 185103.71 | 467342.77 | 10-NOV-06:01 | 12.23 | 9.86 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 174745.04 | 559146.29 | 26-DEC-06:02 | 13.32 | 9.58 | 0.00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 184942.91 | 0.00 | ||||||
Minimum of Months | 0.10 | 126.19 | 7.10 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 494550.01 | 2271931.87 | 20.05 | 9.86 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 57.66 | 57.66 | 17739.75 | 62780.95 | 09-JAN-12:18 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 57.06 | 57.06 | 17847.57 | 62781.16 | 28-FEB-12:59 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 57.06 | 57.06 | 18970.66 | 62780.31 | 06-MAR-12:36 |
April | 0.00 | 0.00 | 01-APR-00:01 | 57.06 | 57.06 | 17768.27 | 62781.22 | 06-APR-11:54 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.66 | 57.66 | 18229.21 | 62780.51 | 11-MAY-11:32 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 57.13 | 57.13 | 18000.47 | 61218.34 | 01-JUN-11:21 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 57.24 | 57.24 | 15940.88 | 58673.33 | 03-JUL-11:58 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 57.34 | 57.34 | 17042.25 | 56912.78 | 01-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.38 | 57.38 | 15913.23 | 56529.28 | 29-SEP-11:32 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 57.36 | 57.36 | 16196.61 | 58205.24 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 57.28 | 57.28 | 17004.75 | 60510.85 | 30-NOV-12:37 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 57.17 | 57.17 | 17043.40 | 62780.28 | 29-DEC-12:22 |
Annual Sum or Average | 0.00 | 17305.15 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.06 | 57.06 | 15913.23 | 56529.28 | ||
Maximum of Months | 0.00 | 0.00 | 57.66 | 57.66 | 18970.66 | 62781.22 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 159.77 | 27877.09 | 27-JAN-02:70 | 21.19 | 20.36 | 3759.63 | 168140.25 | 22-JAN-18:20 |
February | 94316.58 | 653586.38 | 12-FEB-23:18 | 23.12 | 21.10 | 30.10 | 46838.92 | 17-FEB-06:56 |
March | 95675.43 | 789683.75 | 08-MAR-05:16 | 23.54 | 21.10 | 4628.79 | 70114.94 | 23-MAR-13:40 |
April | 46324.68 | 1025244.84 | 11-APR-13:46 | 24.27 | 21.10 | 6236.49 | 158600.96 | 06-APR-23:01 |
May | 68150.70 | 1276864.24 | 31-MAY-16:00 | 25.05 | 21.10 | 1879.38 | 142923.10 | 28-MAY-05:10 |
June | 415924.57 | 3115758.41 | 29-JUN-15:10 | 25.92 | 21.29 | 8.05 | 33919.33 | 17-JUN-12:35 |
July | 538763.01 | 3212682.76 | 21-JUL-15:00 | 26.07 | 21.10 | 228.65 | 87040.68 | 04-JUL-07:10 |
August | 352210.68 | 3162222.10 | 23-AUG-15:40 | 25.99 | 21.11 | 693.64 | 91302.40 | 30-AUG-23:40 |
September | 16738.30 | 889874.50 | 18-SEP-13:58 | 23.85 | 21.10 | 1515.82 | 157170.64 | 23-SEP-03:40 |
October | 98674.30 | 951894.62 | 03-OCT-13:44 | 24.05 | 21.10 | 81.25 | 65151.49 | 05-OCT-09:50 |
November | 19353.79 | 687162.73 | 03-NOV-03:39 | 23.23 | 21.10 | 4418.40 | 56774.60 | 06-NOV-06:08 |
December | 22651.41 | 723694.10 | 15-DEC-08:30 | 23.34 | 21.10 | 6661.50 | 154826.71 | 29-DEC-16:30 |
Annual Sum or Average | 148098.49 | 2526.37 | ||||||
Minimum of Months | 159.77 | 27877.09 | 21.19 | 20.36 | 8.05 | 33919.33 | ||
Maximum of Months | 538763.01 | 3212682.76 | 26.07 | 21.29 | 6661.50 | 168140.25 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.103278E+12 | 0.00 | 325.92 | 0.887556E+10 | 0.00 | 0.00 |
February | 0.673333E+11 | 0.00 | 1760.06 | 0.750078E+10 | 0.00 | 0.00 |
March | 0.440455E+11 | 0.00 | 133421.78 | 0.920401E+10 | 0.00 | 0.00 |
April | 0.672456E+10 | 0.00 | 52487753.29 | 0.119532E+11 | 0.00 | 0.00 |
May | 0.232346E+09 | 0.00 | 0.119302E+11 | 0.138664E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.515281E+11 | 0.160798E+11 | 0.00 | 0.00 |
July | 29200.74 | 0.00 | 0.701952E+11 | 0.169554E+11 | 0.00 | 0.00 |
August | 94763619.13 | 0.00 | 0.401043E+11 | 0.170078E+11 | 0.00 | 0.00 |
September | 0.220932E+10 | 0.00 | 0.927286E+09 | 0.104123E+11 | 0.00 | 0.00 |
October | 0.228279E+11 | 0.00 | 128.09 | 0.896904E+10 | 0.00 | 0.00 |
November | 0.770297E+11 | 0.00 | 47.16 | 0.783503E+10 | 0.00 | 0.00 |
December | 0.966429E+11 | 0.00 | 2074.00 | 0.808392E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.420419E+12 | 0.00 | 0.174738E+12 | 0.136743E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 47.16 | 0.750078E+10 | 0.00 | 0.00 |
Maximum of Months | 0.103278E+12 | 0.00 | 0.701952E+11 | 0.170078E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.135009E+13 | 0.00 | 77554.42 | 0.105224E+12 | 0.00 | 0.00 |
February | 0.939036E+12 | 0.00 | 90971.66 | 0.944746E+11 | 0.00 | 0.00 |
March | 0.704891E+12 | 0.00 | 0.111519E+10 | 0.997610E+11 | 0.00 | 0.00 |
April | 0.194622E+12 | 0.00 | 0.818761E+10 | 0.102289E+12 | 0.00 | 0.00 |
May | 0.146336E+11 | 0.00 | 0.115678E+12 | 0.127546E+12 | 0.00 | 0.00 |
June | 0.247896E+09 | 0.00 | 0.478928E+12 | 0.145857E+12 | 0.00 | 0.00 |
July | 0.352069E+09 | 0.00 | 0.612641E+12 | 0.139991E+12 | 0.00 | 0.00 |
August | 0.854979E+10 | 0.00 | 0.343767E+12 | 0.134673E+12 | 0.00 | 0.00 |
September | 0.808706E+11 | 0.00 | 0.264986E+11 | 0.926343E+11 | 0.00 | 0.00 |
October | 0.475204E+12 | 0.00 | 0.306294E+10 | 0.885697E+11 | 0.00 | 0.00 |
November | 0.116830E+13 | 0.00 | 48081.74 | 0.101663E+12 | 0.00 | 0.00 |
December | 0.139763E+13 | 0.00 | 41663.64 | 0.107384E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.633443E+13 | 0.00 | 0.158988E+13 | 0.134007E+13 | 0.00 | 0.00 |
Minimum of Months | 0.247896E+09 | 0.00 | 41663.64 | 0.885697E+11 | 0.00 | 0.00 |
Maximum of Months | 0.139763E+13 | 0.00 | 0.612641E+12 | 0.145857E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.201632E+12 | 0.00 | 7126521.86 | 0.116626E+11 | 0.00 | 0.00 |
February | 0.148156E+12 | 0.00 | 4645360.88 | 0.103833E+11 | 0.00 | 0.00 |
March | 0.112491E+12 | 0.00 | 6402110.68 | 0.112596E+11 | 0.00 | 0.00 |
April | 0.391036E+11 | 0.00 | 32669151.98 | 0.955258E+10 | 0.00 | 0.00 |
May | 0.581447E+10 | 0.00 | 0.106423E+11 | 0.980921E+10 | 0.00 | 0.00 |
June | 0.494082E+09 | 0.00 | 0.487244E+11 | 0.115104E+11 | 0.00 | 0.00 |
July | 0.499817E+09 | 0.00 | 0.635362E+11 | 0.110573E+11 | 0.00 | 0.00 |
August | 0.353487E+10 | 0.00 | 0.340497E+11 | 0.102354E+11 | 0.00 | 0.00 |
September | 0.219485E+11 | 0.00 | 0.648081E+09 | 0.768243E+10 | 0.00 | 0.00 |
October | 0.844307E+11 | 0.00 | 2365680.27 | 0.991660E+10 | 0.00 | 0.00 |
November | 0.179823E+12 | 0.00 | 9296501.02 | 0.112602E+11 | 0.00 | 0.00 |
December | 0.210097E+12 | 0.00 | 9246515.71 | 0.119376E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.100802E+13 | 0.00 | 0.157672E+12 | 0.126267E+12 | 0.00 | 0.00 |
Minimum of Months | 0.494082E+09 | 0.00 | 2365680.27 | 0.768243E+10 | 0.00 | 0.00 |
Maximum of Months | 0.210097E+12 | 0.00 | 0.635362E+11 | 0.119376E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.200554E+11 | 0.00 | 0.00 | 0.340365E+10 | 0.00 | 0.00 |
February | 0.130667E+11 | 0.00 | 9206227.45 | 0.307177E+10 | 0.00 | 0.00 |
March | 0.250800E+10 | 0.00 | 0.301199E+09 | 0.326866E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.490969E+10 | 0.558551E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.191617E+11 | 0.797088E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.344442E+11 | 0.875636E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.418349E+11 | 0.891436E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.314813E+11 | 0.108155E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.139766E+11 | 0.722809E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.450937E+10 | 0.439618E+10 | 0.00 | 0.00 |
November | 0.368733E+10 | 0.00 | 40529581.07 | 0.278010E+10 | 0.00 | 0.00 |
December | 0.103805E+11 | 0.00 | 6818662.70 | 0.292438E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.496980E+11 | 0.00 | 0.150675E+12 | 0.691155E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.278010E+10 | 0.00 | 0.00 |
Maximum of Months | 0.200554E+11 | 0.00 | 0.418349E+11 | 0.108155E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 2468241.59 | 0.118299E+12 | 0.00 | 34.06 |
February | 0.00 | 0.00 | 0.171933E+12 | 0.140396E+12 | 0.00 | 36.18 |
March | 0.00 | 0.00 | 0.269607E+12 | 0.232080E+12 | 0.00 | 64.78 |
April | 0.00 | 0.00 | 0.263906E+12 | 0.323956E+12 | 0.00 | 92.24 |
May | 0.00 | 0.00 | 0.256760E+09 | 0.179752E+12 | 0.00 | 56.91 |
June | 0.00 | 0.00 | 0.212735E+12 | 0.100036E+12 | 0.00 | 21.34 |
July | 0.00 | 0.00 | 0.297245E+12 | 0.798419E+11 | 0.00 | 4.78 |
August | 0.00 | 0.00 | 0.285042E+12 | 0.135792E+12 | 0.00 | 18.38 |
September | 0.00 | 0.00 | 0.281399E+09 | 0.101520E+12 | 0.00 | 28.12 |
October | 0.00 | 0.00 | 0.190748E+12 | 0.158063E+12 | 0.00 | 40.98 |
November | 0.00 | 0.00 | 0.225321E+12 | 0.226084E+12 | 0.00 | 63.25 |
December | 0.00 | 0.00 | 0.257203E+12 | 0.302329E+12 | 0.00 | 85.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.217428E+13 | 0.209815E+13 | 0.00 | 546.84 |
Minimum of Months | 0.00 | 0.00 | 2468241.59 | 0.798419E+11 | 0.00 | 4.78 |
Maximum of Months | 0.00 | 0.00 | 0.297245E+12 | 0.323956E+12 | 0.00 | 92.24 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.441093E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.522529E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.738616E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.897233E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.582735E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.695268E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.831145E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.956873E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.547257E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.655997E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.664610E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.761450E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.829481E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.441093E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.956873E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.376718E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.447554E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.632915E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.756791E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.513705E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.615751E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.727963E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.823933E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.473320E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.553155E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.555144E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.632885E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.710983E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.376718E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.823933E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.358226E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.425482E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.638070E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.790134E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.518393E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.659405E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.790474E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.890053E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.450602E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.526898E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.550487E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.646238E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.724446E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.358226E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.890053E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.887556E+10 | 325.92 | 0.103278E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.750078E+10 | 1760.06 | 0.673333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.920401E+10 | 133421.78 | 0.440455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119532E+11 | 52487753.29 | 0.672456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138664E+11 | 0.119302E+11 | 0.232346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160798E+11 | 0.515281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169554E+11 | 0.701952E+11 | 29200.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170078E+11 | 0.401043E+11 | 94763619.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104123E+11 | 0.927286E+09 | 0.220932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.896904E+10 | 128.09 | 0.228279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.783503E+10 | 47.16 | 0.770297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.808392E+10 | 2074.00 | 0.966429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136743E+12 | 0.174738E+12 | 0.420419E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.750078E+10 | 47.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170078E+11 | 0.701952E+11 | 0.103278E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.105224E+12 | 77554.42 | 0.135009E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.944746E+11 | 90971.66 | 0.939036E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.997610E+11 | 0.111519E+10 | 0.704891E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102289E+12 | 0.818761E+10 | 0.194622E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127546E+12 | 0.115678E+12 | 0.146336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145857E+12 | 0.478928E+12 | 0.247896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139991E+12 | 0.612641E+12 | 0.352069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134673E+12 | 0.343767E+12 | 0.854979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.926343E+11 | 0.264986E+11 | 0.808706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.885697E+11 | 0.306294E+10 | 0.475204E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101663E+12 | 48081.74 | 0.116830E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107384E+12 | 41663.64 | 0.139763E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134007E+13 | 0.158988E+13 | 0.633443E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.885697E+11 | 41663.64 | 0.247896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145857E+12 | 0.612641E+12 | 0.139763E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.116626E+11 | 7126521.86 | 0.201632E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103833E+11 | 4645360.88 | 0.148156E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112596E+11 | 6402110.68 | 0.112491E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.955258E+10 | 32669151.98 | 0.391036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.980921E+10 | 0.106423E+11 | 0.581447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.115104E+11 | 0.487244E+11 | 0.494082E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110573E+11 | 0.635362E+11 | 0.499817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.102354E+11 | 0.340497E+11 | 0.353487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.768243E+10 | 0.648081E+09 | 0.219485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.991660E+10 | 2365680.27 | 0.844307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112602E+11 | 9296501.02 | 0.179823E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119376E+11 | 9246515.71 | 0.210097E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126267E+12 | 0.157672E+12 | 0.100802E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.768243E+10 | 2365680.27 | 0.494082E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119376E+11 | 0.635362E+11 | 0.210097E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.340365E+10 | 0.00 | 0.200554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.307177E+10 | 9206227.45 | 0.130667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.326866E+10 | 0.301199E+09 | 0.250800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.558551E+10 | 0.490969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.797088E+10 | 0.191617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.875636E+10 | 0.344442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.891436E+10 | 0.418349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108155E+11 | 0.314813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.722809E+10 | 0.139766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.439618E+10 | 0.450937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.278010E+10 | 40529581.07 | 0.368733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.292438E+10 | 6818662.70 | 0.103805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.691155E+11 | 0.150675E+12 | 0.496980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.278010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108155E+11 | 0.418349E+11 | 0.200554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.267530E+11 | 2468241.59 | 0.00 | 0.00 | 0.00 | 0.911361E+11 | 0.00 | 0.00 |
February | 0.431333E+11 | 0.171933E+12 | 0.00 | 0.00 | 0.00 | 0.968273E+11 | 0.00 | 0.00 |
March | 0.579508E+11 | 0.269607E+12 | 0.00 | 0.00 | 0.00 | 0.173349E+12 | 0.00 | 0.00 |
April | 0.760102E+11 | 0.263906E+12 | 0.00 | 0.00 | 0.00 | 0.246834E+12 | 0.00 | 0.00 |
May | 0.267795E+11 | 0.256760E+09 | 0.00 | 0.00 | 0.00 | 0.152287E+12 | 0.00 | 0.00 |
June | 0.426683E+11 | 0.212735E+12 | 0.00 | 0.00 | 0.00 | 0.571103E+11 | 0.00 | 0.00 |
July | 0.669830E+11 | 0.297245E+12 | 0.00 | 0.00 | 0.00 | 0.128012E+11 | 0.00 | 0.00 |
August | 0.863751E+11 | 0.285042E+12 | 0.00 | 0.00 | 0.00 | 0.491954E+11 | 0.00 | 0.00 |
September | 0.259174E+11 | 0.281399E+09 | 0.00 | 0.00 | 0.00 | 0.752635E+11 | 0.00 | 0.00 |
October | 0.478989E+11 | 0.190748E+12 | 0.00 | 0.00 | 0.00 | 0.109671E+12 | 0.00 | 0.00 |
November | 0.560598E+11 | 0.225321E+12 | 0.00 | 0.00 | 0.00 | 0.169263E+12 | 0.00 | 0.00 |
December | 0.716301E+11 | 0.257203E+12 | 0.00 | 0.00 | 0.00 | 0.229665E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.628159E+12 | 0.217428E+13 | 0.00 | 0.00 | 0.00 | 0.146340E+13 | 0.00 | 0.00 |
Minimum of Months | 0.259174E+11 | 2468241.59 | 0.00 | 0.00 | 0.00 | 0.128012E+11 | 0.00 | 0.00 |
Maximum of Months | 0.863751E+11 | 0.297245E+12 | 0.00 | 0.00 | 0.00 | 0.246834E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.357824E+10 | 0.262081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.323195E+10 | 0.687134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.357824E+10 | 0.143553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.346281E+10 | 0.212653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.357824E+10 | 0.751632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.346281E+10 | 0.125583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.357824E+10 | 0.181936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.357824E+10 | 0.229879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.346281E+10 | 0.664015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.357824E+10 | 0.104765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.346281E+10 | 0.119363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357824E+10 | 0.157662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421308E+11 | 0.151188E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.323195E+10 | 0.262081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.357824E+10 | 0.229879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.344663E+11 | 0.115267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311308E+11 | 0.534969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.344663E+11 | 0.124132E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.333545E+11 | 0.191651E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.344663E+11 | 0.652083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.333545E+11 | 0.117963E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.344663E+11 | 0.170907E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.344663E+11 | 0.215198E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.333545E+11 | 0.529395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.344663E+11 | 0.833020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.333545E+11 | 0.932514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344663E+11 | 0.129418E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.405813E+12 | 0.130899E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.311308E+11 | 0.115267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.344663E+11 | 0.215198E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.349396E+10 | 0.267739E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.315583E+10 | 0.359569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.349396E+10 | 0.103165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.338125E+10 | 0.174735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.349396E+10 | 0.551920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.338125E+10 | 0.114286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.349396E+10 | 0.167247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.349396E+10 | 0.208905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.338125E+10 | 0.357416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.349396E+10 | 0.588367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.338125E+10 | 0.739534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.349396E+10 | 0.110515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.411386E+11 | 0.114121E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.315583E+10 | 0.267739E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.349396E+10 | 0.208905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.887556E+10 | 0.103278E+12 | 325.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.750078E+10 | 0.673333E+11 | 1760.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.920401E+10 | 0.440455E+11 | 133421.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119532E+11 | 0.672456E+10 | 52487753.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138664E+11 | 0.232346E+09 | 0.119302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160798E+11 | 0.00 | 0.515281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169554E+11 | 29200.74 | 0.701952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170078E+11 | 94763619.13 | 0.401043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104123E+11 | 0.220932E+10 | 0.927286E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.896904E+10 | 0.228279E+11 | 128.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.783503E+10 | 0.770297E+11 | 47.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.808392E+10 | 0.966429E+11 | 2074.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136743E+12 | 0.420419E+12 | 0.174738E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.750078E+10 | 0.00 | 47.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170078E+11 | 0.103278E+12 | 0.701952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.105224E+12 | 0.135009E+13 | 77554.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.944746E+11 | 0.939036E+12 | 90971.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.997610E+11 | 0.704891E+12 | 0.111519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102289E+12 | 0.194622E+12 | 0.818761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127546E+12 | 0.146336E+11 | 0.115678E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145857E+12 | 0.247896E+09 | 0.478928E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139991E+12 | 0.352069E+09 | 0.612641E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134673E+12 | 0.854979E+10 | 0.343767E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.926343E+11 | 0.808706E+11 | 0.264986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.885697E+11 | 0.475204E+12 | 0.306294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101663E+12 | 0.116830E+13 | 48081.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107384E+12 | 0.139763E+13 | 41663.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134007E+13 | 0.633443E+13 | 0.158988E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.885697E+11 | 0.247896E+09 | 41663.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145857E+12 | 0.139763E+13 | 0.612641E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.116626E+11 | 0.201632E+12 | 7126521.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103833E+11 | 0.148156E+12 | 4645360.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112596E+11 | 0.112491E+12 | 6402110.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.955258E+10 | 0.391036E+11 | 32669151.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.980921E+10 | 0.581447E+10 | 0.106423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.115104E+11 | 0.494082E+09 | 0.487244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110573E+11 | 0.499817E+09 | 0.635362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.102354E+11 | 0.353487E+10 | 0.340497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.768243E+10 | 0.219485E+11 | 0.648081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.991660E+10 | 0.844307E+11 | 2365680.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112602E+11 | 0.179823E+12 | 9296501.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119376E+11 | 0.210097E+12 | 9246515.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126267E+12 | 0.100802E+13 | 0.157672E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.768243E+10 | 0.494082E+09 | 2365680.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119376E+11 | 0.210097E+12 | 0.635362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.340365E+10 | 0.200554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.307177E+10 | 0.130667E+11 | 9206227.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.326866E+10 | 0.250800E+10 | 0.301199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.558551E+10 | 0.00 | 0.490969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.797088E+10 | 0.00 | 0.191617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.875636E+10 | 0.00 | 0.344442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.891436E+10 | 0.00 | 0.418349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108155E+11 | 0.00 | 0.314813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.722809E+10 | 0.00 | 0.139766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.439618E+10 | 0.00 | 0.450937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.278010E+10 | 0.368733E+10 | 40529581.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.292438E+10 | 0.103805E+11 | 6818662.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.691155E+11 | 0.496980E+11 | 0.150675E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.278010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108155E+11 | 0.200554E+11 | 0.418349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.267530E+11 | 0.00 | 2468241.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.915464E+11 | 0.00 | 0.00 | 0.00 |
February | 0.431333E+11 | 0.00 | 0.171933E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972632E+11 | 0.00 | 0.00 | 0.00 |
March | 0.579508E+11 | 0.00 | 0.269607E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174129E+12 | 0.00 | 0.00 | 0.00 |
April | 0.760102E+11 | 0.00 | 0.263906E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247945E+12 | 0.00 | 0.00 | 0.00 |
May | 0.267795E+11 | 0.00 | 0.256760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152972E+12 | 0.00 | 0.00 | 0.00 |
June | 0.426683E+11 | 0.00 | 0.212735E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573674E+11 | 0.00 | 0.00 | 0.00 |
July | 0.669830E+11 | 0.00 | 0.297245E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128589E+11 | 0.00 | 0.00 | 0.00 |
August | 0.863751E+11 | 0.00 | 0.285042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494169E+11 | 0.00 | 0.00 | 0.00 |
September | 0.259174E+11 | 0.00 | 0.281399E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.756023E+11 | 0.00 | 0.00 | 0.00 |
October | 0.478989E+11 | 0.00 | 0.190748E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110164E+12 | 0.00 | 0.00 | 0.00 |
November | 0.560598E+11 | 0.00 | 0.225321E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170025E+12 | 0.00 | 0.00 | 0.00 |
December | 0.716301E+11 | 0.00 | 0.257203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230699E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.628159E+12 | 0.00 | 0.217428E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146999E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.259174E+11 | 0.00 | 2468241.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128589E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.863751E+11 | 0.00 | 0.297245E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247945E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.357824E+10 | 0.00 | 0.00 | 0.00 | 0.832699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.323195E+10 | 0.00 | 0.00 | 0.00 | 0.199333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.357824E+10 | 0.00 | 0.00 | 0.00 | 0.380792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.346281E+10 | 0.00 | 0.00 | 0.00 | 0.550953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.357824E+10 | 0.00 | 0.00 | 0.00 | 0.224911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.346281E+10 | 0.00 | 0.00 | 0.00 | 0.348987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.357824E+10 | 0.00 | 0.00 | 0.00 | 0.473322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.357824E+10 | 0.00 | 0.00 | 0.00 | 0.599049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.346281E+10 | 0.00 | 0.00 | 0.00 | 0.200976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.357824E+10 | 0.00 | 0.00 | 0.00 | 0.298174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.346281E+10 | 0.00 | 0.00 | 0.00 | 0.318329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357824E+10 | 0.00 | 0.00 | 0.00 | 0.403627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421308E+11 | 0.00 | 0.00 | 0.00 | 0.408172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.323195E+10 | 0.00 | 0.00 | 0.00 | 0.832699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.357824E+10 | 0.00 | 0.00 | 0.00 | 0.599049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.344663E+11 | 0.00 | 0.00 | 0.00 | 0.320549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311308E+11 | 0.00 | 0.00 | 0.00 | 0.136246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.344663E+11 | 0.00 | 0.00 | 0.00 | 0.288252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.333545E+11 | 0.00 | 0.00 | 0.00 | 0.423247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.344663E+11 | 0.00 | 0.00 | 0.00 | 0.169042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.333545E+11 | 0.00 | 0.00 | 0.00 | 0.282206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.344663E+11 | 0.00 | 0.00 | 0.00 | 0.383300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.344663E+11 | 0.00 | 0.00 | 0.00 | 0.479270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.333545E+11 | 0.00 | 0.00 | 0.00 | 0.139776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.344663E+11 | 0.00 | 0.00 | 0.00 | 0.208492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.333545E+11 | 0.00 | 0.00 | 0.00 | 0.221599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344663E+11 | 0.00 | 0.00 | 0.00 | 0.288222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.405813E+12 | 0.00 | 0.00 | 0.00 | 0.305171E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.311308E+11 | 0.00 | 0.00 | 0.00 | 0.320549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.344663E+11 | 0.00 | 0.00 | 0.00 | 0.479270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.349396E+10 | 0.00 | 0.00 | 0.00 | 88300783.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.315583E+10 | 0.00 | 0.00 | 0.00 | 0.109898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.349396E+10 | 0.00 | 0.00 | 0.00 | 0.288674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.338125E+10 | 0.00 | 0.00 | 0.00 | 0.452009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.349396E+10 | 0.00 | 0.00 | 0.00 | 0.168997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.338125E+10 | 0.00 | 0.00 | 0.00 | 0.321280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.349396E+10 | 0.00 | 0.00 | 0.00 | 0.441079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.349396E+10 | 0.00 | 0.00 | 0.00 | 0.540657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.338125E+10 | 0.00 | 0.00 | 0.00 | 0.112476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.349396E+10 | 0.00 | 0.00 | 0.00 | 0.177502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.338125E+10 | 0.00 | 0.00 | 0.00 | 0.212362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.349396E+10 | 0.00 | 0.00 | 0.00 | 0.296842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.411386E+11 | 0.00 | 0.00 | 0.00 | 0.313061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.315583E+10 | 0.00 | 0.00 | 0.00 | 88300783.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.349396E+10 | 0.00 | 0.00 | 0.00 | 0.540657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.715896E+11 | 0.00 | 0.00 | 482.41 | 0.00 | 0.104569E+11 | 6934648.66 | 0.00 | 0.31 |
February | 0.603102E+11 | 0.00 | 0.00 | 2688151.96 | 0.00 | 0.784174E+10 | 0.254020E+09 | 0.00 | 0.32 |
March | 0.646019E+11 | 0.00 | 0.00 | 34497274.06 | 0.00 | 0.483630E+09 | 0.409521E+10 | 0.00 | 0.35 |
April | 0.239709E+11 | 0.00 | 0.00 | 0.178190E+09 | 0.00 | 0.00 | 0.350041E+11 | 0.00 | 0.51 |
May | 0.661908E+10 | 0.00 | 0.00 | 0.143316E+09 | 0.00 | 0.00 | 0.487188E+11 | 0.00 | 0.79 |
June | 0.335949E+10 | 85245023.55 | 0.00 | 0.490705E+09 | 0.00 | 0.00 | 0.390786E+11 | 0.00 | 0.99 |
July | 0.203504E+10 | 0.245627E+09 | 0.00 | 0.397260E+09 | 23787444.76 | 0.00 | 0.352274E+11 | 0.00 | 0.96 |
August | 0.458811E+10 | 3487987.73 | 0.00 | 0.274920E+09 | 0.00 | 0.00 | 0.549484E+11 | 0.00 | 1.09 |
September | 0.100106E+11 | 0.00 | 0.00 | 0.132064E+09 | 0.00 | 0.00 | 0.503873E+11 | 0.00 | 0.64 |
October | 0.399761E+11 | 0.00 | 0.00 | 0.186572E+09 | 0.00 | 0.00 | 0.230417E+11 | 0.00 | 0.41 |
November | 0.748479E+11 | 0.00 | 0.00 | 11721972.60 | 0.00 | 44563423.11 | 0.915699E+09 | 0.00 | 0.32 |
December | 0.797462E+11 | 0.00 | 0.00 | 2732473.99 | 0.00 | 0.182185E+10 | 0.293206E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.441655E+12 | 0.334360E+09 | 0.00 | 0.185467E+10 | 23787444.76 | 0.206486E+11 | 0.291971E+12 | 0.00 | 0.58 |
Minimum of Months | 0.203504E+10 | 0.00 | 0.00 | 482.41 | 0.00 | 0.00 | 6934648.66 | 0.00 | 0.31 |
Maximum of Months | 0.797462E+11 | 0.245627E+09 | 0.00 | 0.490705E+09 | 23787444.76 | 0.104569E+11 | 0.549484E+11 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.530792E+11 | 0.00 | 0.00 | 6001170.78 | 0.00 | 0.229560E+09 | 0.106416E+11 | 0.00 | 0.26 |
February | 0.436087E+11 | 0.00 | 0.00 | 0.101241E+09 | 0.00 | 1400878.84 | 0.897546E+10 | 0.00 | 0.25 |
March | 0.321630E+11 | 0.00 | 0.00 | 0.321227E+09 | 0.00 | 0.00 | 0.258731E+11 | 0.00 | 0.29 |
April | 0.113418E+11 | 0.00 | 0.00 | 0.413029E+09 | 0.00 | 0.00 | 0.502004E+11 | 0.00 | 0.54 |
May | 0.647128E+10 | 0.00 | 0.00 | 0.237746E+09 | 0.00 | 0.00 | 0.582562E+11 | 0.00 | 0.93 |
June | 0.501641E+10 | 1798224.94 | 0.00 | 0.592366E+09 | 0.00 | 0.00 | 0.463884E+11 | 0.00 | 1.11 |
July | 0.665131E+10 | 0.156236E+09 | 0.00 | 0.444234E+09 | 20765263.16 | 0.00 | 0.394103E+11 | 0.00 | 1.06 |
August | 0.550326E+10 | 0.00 | 0.00 | 0.357749E+09 | 0.00 | 0.00 | 0.602517E+11 | 0.00 | 1.15 |
September | 0.556094E+10 | 0.00 | 0.00 | 0.207396E+09 | 0.00 | 0.00 | 0.514574E+11 | 0.00 | 0.61 |
October | 0.200302E+11 | 0.00 | 0.00 | 0.410300E+09 | 0.00 | 0.00 | 0.323420E+11 | 0.00 | 0.34 |
November | 0.356405E+11 | 0.00 | 0.00 | 0.243369E+09 | 0.00 | 0.00 | 0.257056E+11 | 0.00 | 0.25 |
December | 0.426546E+11 | 0.00 | 0.00 | 0.177301E+09 | 0.00 | 0.00 | 0.238050E+11 | 0.00 | 0.25 |
Annual Sum or Average | 0.267721E+12 | 0.158034E+09 | 0.00 | 0.351196E+10 | 20765263.16 | 0.230961E+09 | 0.433307E+12 | 0.00 | 0.59 |
Minimum of Months | 0.501641E+10 | 0.00 | 0.00 | 6001170.78 | 0.00 | 0.00 | 0.897546E+10 | 0.00 | 0.25 |
Maximum of Months | 0.530792E+11 | 0.156236E+09 | 0.00 | 0.592366E+09 | 20765263.16 | 0.229560E+09 | 0.602517E+11 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.573657E+12 | 0.00 | 0.00 | 12924184.28 | 0.00 | 0.180154E+11 | 0.312507E+11 | 0.00 | 0.26 |
February | 0.492381E+12 | 0.00 | 0.00 | 0.336303E+09 | 0.00 | 0.790427E+10 | 0.292816E+11 | 0.00 | 0.26 |
March | 0.455296E+12 | 0.00 | 0.00 | 0.114423E+10 | 0.00 | 0.161454E+10 | 0.950315E+11 | 0.00 | 0.28 |
April | 0.230332E+12 | 0.00 | 0.00 | 0.170154E+10 | 0.00 | 0.536246E+09 | 0.224089E+12 | 0.00 | 0.40 |
May | 0.875327E+11 | 0.00 | 0.00 | 0.176716E+10 | 0.00 | 0.00 | 0.442935E+12 | 0.00 | 0.79 |
June | 0.695233E+11 | 32407462.77 | 0.00 | 0.454174E+10 | 0.00 | 0.00 | 0.356350E+12 | 0.00 | 0.95 |
July | 0.736150E+11 | 0.156658E+10 | 0.00 | 0.288080E+10 | 0.249100E+09 | 0.00 | 0.266212E+12 | 0.00 | 0.83 |
August | 0.796893E+11 | 0.00 | 0.00 | 0.207580E+10 | 0.00 | 0.00 | 0.387471E+12 | 0.00 | 0.86 |
September | 0.133593E+12 | 0.00 | 0.00 | 0.135607E+10 | 0.00 | 0.00 | 0.305744E+12 | 0.00 | 0.48 |
October | 0.326526E+12 | 0.00 | 0.00 | 0.154293E+10 | 0.00 | 0.339161E+10 | 0.120926E+12 | 0.00 | 0.29 |
November | 0.598735E+12 | 0.00 | 0.00 | 55204000.45 | 0.00 | 0.112089E+11 | 0.837560E+10 | 0.00 | 0.26 |
December | 0.657641E+12 | 0.00 | 0.00 | 354611.62 | 0.00 | 0.945610E+10 | 0.153097E+10 | 0.00 | 0.26 |
Annual Sum or Average | 0.377852E+13 | 0.159899E+10 | 0.00 | 0.174151E+11 | 0.249100E+09 | 0.521271E+11 | 0.226920E+13 | 0.00 | 0.50 |
Minimum of Months | 0.695233E+11 | 0.00 | 0.00 | 354611.62 | 0.00 | 0.00 | 0.153097E+10 | 0.00 | 0.26 |
Maximum of Months | 0.657641E+12 | 0.156658E+10 | 0.00 | 0.454174E+10 | 0.249100E+09 | 0.180154E+11 | 0.442935E+12 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.308442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209115E+11 | 0.00 | 0.00 | 0.22 |
February | 0.292558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136940E+11 | 0.00 | 0.00 | 0.23 |
March | 0.400343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674690E+10 | 0.00 | 0.00 | 0.25 |
April | 0.330452E+11 | 0.00 | 0.00 | 21701109.45 | 0.00 | 0.192861E+10 | 0.436444E+10 | 0.00 | 0.37 |
May | 0.238409E+11 | 0.00 | 0.00 | 77178338.31 | 0.00 | 7297239.29 | 0.232647E+11 | 0.00 | 0.73 |
June | 0.146103E+11 | 245663.93 | 0.00 | 0.329360E+09 | 0.00 | 0.00 | 0.274970E+11 | 0.00 | 0.96 |
July | 0.137752E+11 | 92329411.06 | 0.00 | 0.154611E+09 | 57285044.27 | 0.00 | 0.187409E+11 | 0.00 | 0.82 |
August | 0.178507E+11 | 2251.99 | 0.00 | 91132949.18 | 0.00 | 5403700.77 | 0.225420E+11 | 0.00 | 0.81 |
September | 0.308443E+11 | 0.00 | 0.00 | 11826341.00 | 0.00 | 0.579464E+09 | 0.378188E+10 | 0.00 | 0.42 |
October | 0.321723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513203E+10 | 0.00 | 0.00 | 0.27 |
November | 0.326486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173761E+11 | 0.00 | 0.00 | 0.22 |
December | 0.300560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239412E+11 | 0.00 | 0.00 | 0.22 |
Annual Sum or Average | 0.328978E+12 | 92577326.99 | 0.00 | 0.685809E+09 | 57285044.27 | 0.903226E+11 | 0.100191E+12 | 0.00 | 0.46 |
Minimum of Months | 0.137752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
Maximum of Months | 0.400343E+11 | 92329411.06 | 0.00 | 0.329360E+09 | 57285044.27 | 0.239412E+11 | 0.274970E+11 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.858258E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125571E+11 | 0.00 | 0.00 | 0.42 |
February | 0.221571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.858221E+10 | 0.00 | 0.00 | 0.41 |
March | 0.547123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547284E+10 | 0.00 | 0.00 | 0.42 |
April | 0.764045E+10 | 0.00 | 0.00 | 4481216.50 | 0.00 | 0.507119E+09 | 0.972682E+09 | 0.00 | 0.62 |
May | 0.445986E+10 | 0.00 | 0.00 | 19433854.60 | 0.00 | 0.00 | 0.544412E+10 | 0.00 | 1.14 |
June | 0.183570E+10 | 407776.36 | 0.00 | 86694663.42 | 0.00 | 0.00 | 0.714364E+10 | 0.00 | 1.57 |
July | 0.229620E+10 | 30608642.45 | 0.00 | 54526638.79 | 4345145.75 | 0.00 | 0.538995E+10 | 0.00 | 1.45 |
August | 0.376823E+10 | 0.00 | 0.00 | 24100039.07 | 0.00 | 416589.75 | 0.553837E+10 | 0.00 | 1.35 |
September | 0.717888E+10 | 0.00 | 0.00 | 2574283.69 | 0.00 | 49723862.93 | 0.113602E+10 | 0.00 | 0.70 |
October | 0.625671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251611E+10 | 0.00 | 0.00 | 0.44 |
November | 0.230316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973686E+10 | 0.00 | 0.00 | 0.38 |
December | 0.977503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123530E+11 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.452619E+11 | 31016418.81 | 0.00 | 0.191811E+09 | 4345145.75 | 0.517754E+11 | 0.256248E+11 | 0.00 | 0.78 |
Minimum of Months | 0.858258E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.764045E+10 | 30608642.45 | 0.00 | 86694663.42 | 4345145.75 | 0.125571E+11 | 0.714364E+10 | 0.00 | 1.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.678455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134838E+11 | 0.00 | 0.00 | 0.69 |
February | 0.304810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834953E+10 | 0.00 | 0.00 | 0.67 |
March | 0.696650E+10 | 0.00 | 0.00 | 6144114.36 | 0.00 | 0.415011E+10 | 0.538323E+09 | 0.00 | 0.70 |
April | 0.689476E+10 | 0.00 | 0.00 | 20220256.51 | 0.00 | 0.528152E+09 | 0.283039E+10 | 0.00 | 1.08 |
May | 0.399497E+10 | 0.00 | 0.00 | 35828028.44 | 0.00 | 0.00 | 0.882294E+10 | 0.00 | 2.22 |
June | 0.288490E+10 | 341838.07 | 0.00 | 82890250.98 | 0.00 | 0.00 | 0.721551E+10 | 0.00 | 2.60 |
July | 0.335578E+10 | 24998801.35 | 0.00 | 53382471.82 | 5171524.08 | 0.00 | 0.533154E+10 | 0.00 | 2.48 |
August | 0.435002E+10 | 0.00 | 0.00 | 30539466.27 | 0.00 | 1078374.37 | 0.621296E+10 | 0.00 | 2.24 |
September | 0.730072E+10 | 0.00 | 0.00 | 4939728.98 | 0.00 | 0.157631E+09 | 0.161443E+10 | 0.00 | 1.18 |
October | 0.664555E+10 | 0.00 | 0.00 | 1353939.65 | 0.00 | 0.251698E+10 | 0.133979E+09 | 0.00 | 0.72 |
November | 0.129225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114387E+11 | 0.00 | 0.00 | 0.63 |
December | 0.232422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138628E+11 | 0.00 | 0.00 | 0.64 |
Annual Sum or Average | 0.476444E+11 | 25340639.42 | 0.00 | 0.235298E+09 | 5171524.08 | 0.544889E+11 | 0.327001E+11 | 0.00 | 1.32 |
Minimum of Months | 0.232422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
Maximum of Months | 0.730072E+10 | 24998801.35 | 0.00 | 82890250.98 | 5171524.08 | 0.138628E+11 | 0.882294E+10 | 0.00 | 2.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.257351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195229E+11 | 0.00 | 0.00 | 0.70 |
February | 0.688436E+10 | 0.00 | 0.00 | 4451870.52 | 0.00 | 0.105693E+11 | 0.389808E+09 | 0.00 | 0.68 |
March | 0.950894E+10 | 0.00 | 0.00 | 51885843.50 | 0.00 | 0.570756E+10 | 0.427626E+10 | 0.00 | 0.76 |
April | 0.824155E+10 | 0.00 | 0.00 | 72770735.03 | 0.00 | 0.110114E+10 | 0.101562E+11 | 0.00 | 1.41 |
May | 0.810621E+10 | 0.00 | 0.00 | 39588930.58 | 0.00 | 2810434.20 | 0.105123E+11 | 0.00 | 2.21 |
June | 0.667189E+10 | 656910.18 | 0.00 | 90066232.18 | 0.00 | 0.00 | 0.709133E+10 | 0.00 | 2.48 |
July | 0.679814E+10 | 63895213.33 | 0.00 | 36404386.11 | 7169081.30 | 0.00 | 0.483569E+10 | 0.00 | 2.28 |
August | 0.804443E+10 | 0.00 | 0.00 | 37973378.75 | 0.00 | 2854474.89 | 0.867948E+10 | 0.00 | 2.49 |
September | 0.960308E+10 | 0.00 | 0.00 | 22081084.83 | 0.00 | 0.358509E+09 | 0.571380E+10 | 0.00 | 1.36 |
October | 0.940198E+10 | 0.00 | 0.00 | 20822462.33 | 0.00 | 0.404901E+10 | 0.164160E+10 | 0.00 | 0.76 |
November | 0.493164E+10 | 0.00 | 0.00 | 900412.74 | 0.00 | 0.148441E+11 | 91957221.39 | 0.00 | 0.63 |
December | 0.810147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211819E+11 | 0.00 | 0.00 | 0.64 |
Annual Sum or Average | 0.815759E+11 | 64552123.51 | 0.00 | 0.376945E+09 | 7169081.30 | 0.773400E+11 | 0.533884E+11 | 0.00 | 1.37 |
Minimum of Months | 0.810147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
Maximum of Months | 0.960308E+10 | 63895213.33 | 0.00 | 90066232.18 | 7169081.30 | 0.211819E+11 | 0.105123E+11 | 0.00 | 2.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.464223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120692E+11 | 0.00 | 0.00 | 0.82 |
February | 0.757399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586996E+10 | 0.00 | 0.00 | 0.79 |
March | 0.111659E+11 | 0.00 | 0.00 | 4454625.78 | 0.00 | 0.208221E+10 | 0.431999E+09 | 0.00 | 0.82 |
April | 0.727546E+10 | 0.00 | 0.00 | 37511773.09 | 0.00 | 41857704.59 | 0.588913E+10 | 0.00 | 1.46 |
May | 0.629168E+10 | 0.00 | 0.00 | 16053057.93 | 0.00 | 0.00 | 0.604002E+10 | 0.00 | 2.23 |
June | 0.442368E+10 | 497635.00 | 0.00 | 61496321.39 | 0.00 | 0.00 | 0.514373E+10 | 0.00 | 2.72 |
July | 0.417401E+10 | 49332950.18 | 0.00 | 35487218.34 | 1837484.25 | 0.00 | 0.412301E+10 | 0.00 | 2.47 |
August | 0.434912E+10 | 0.00 | 0.00 | 30304097.49 | 0.00 | 0.00 | 0.700801E+10 | 0.00 | 2.63 |
September | 0.878355E+10 | 0.00 | 0.00 | 5553789.15 | 0.00 | 1363562.74 | 0.186891E+10 | 0.00 | 1.40 |
October | 0.985491E+10 | 0.00 | 0.00 | 508334.75 | 0.00 | 0.104776E+10 | 50269882.91 | 0.00 | 0.85 |
November | 0.124275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258527E+10 | 0.00 | 0.00 | 0.74 |
December | 0.129759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363774E+10 | 0.00 | 0.00 | 0.75 |
Annual Sum or Average | 0.939380E+11 | 49830585.19 | 0.00 | 0.191369E+09 | 1837484.25 | 0.273354E+11 | 0.305551E+11 | 0.00 | 1.48 |
Minimum of Months | 0.417401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 |
Maximum of Months | 0.129759E+11 | 49332950.18 | 0.00 | 61496321.39 | 1837484.25 | 0.120692E+11 | 0.700801E+10 | 0.00 | 2.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.227522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172116E+12 | 0.00 | 0.00 | 0.57 |
February | 0.984051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137819E+12 | 0.00 | 0.00 | 0.58 |
March | 0.329368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117594E+12 | 0.00 | 0.00 | 0.59 |
April | 0.733759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355124E+11 | 0.00 | 0.00 | 0.74 |
May | 0.905036E+11 | 0.00 | 0.00 | 22336530.90 | 0.00 | 0.778755E+09 | 0.148904E+11 | 0.00 | 1.24 |
June | 0.421818E+11 | 8395723.42 | 0.00 | 0.499544E+09 | 0.00 | 0.00 | 0.440814E+11 | 0.00 | 1.55 |
July | 0.440906E+11 | 0.349508E+09 | 0.00 | 0.178065E+09 | 87258077.23 | 0.00 | 0.258721E+11 | 0.00 | 1.35 |
August | 0.723963E+11 | 0.00 | 0.00 | 36943641.28 | 0.00 | 0.125839E+10 | 0.170294E+11 | 0.00 | 1.32 |
September | 0.835396E+11 | 0.00 | 0.00 | 21757.75 | 0.00 | 0.135876E+11 | 0.141297E+09 | 0.00 | 0.83 |
October | 0.398198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792746E+11 | 0.00 | 0.00 | 0.60 |
November | 0.381109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169291E+12 | 0.00 | 0.00 | 0.58 |
December | 0.341761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183837E+12 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.498189E+12 | 0.357904E+09 | 0.00 | 0.736910E+09 | 87258077.23 | 0.911068E+12 | 0.102015E+12 | 0.00 | 0.88 |
Minimum of Months | 0.227522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.905036E+11 | 0.349508E+09 | 0.00 | 0.499544E+09 | 87258077.23 | 0.183837E+12 | 0.440814E+11 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.329277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121429E+12 | 0.00 | 0.00 | 0.63 |
February | 0.140638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.920775E+11 | 0.00 | 0.00 | 0.64 |
March | 0.482446E+11 | 0.00 | 0.00 | 34111845.68 | 0.00 | 0.589937E+11 | 0.332833E+10 | 0.00 | 0.67 |
April | 0.512464E+11 | 0.00 | 0.00 | 0.161941E+09 | 0.00 | 0.178405E+11 | 0.199101E+11 | 0.00 | 0.96 |
May | 0.394937E+11 | 0.00 | 0.00 | 0.330704E+09 | 0.00 | 0.190545E+09 | 0.774170E+11 | 0.00 | 2.12 |
June | 0.277418E+11 | 6825171.37 | 0.00 | 0.800123E+09 | 609288.32 | 0.00 | 0.664441E+11 | 0.00 | 2.53 |
July | 0.293546E+11 | 0.265207E+09 | 0.00 | 0.487609E+09 | 0.121051E+09 | 0.00 | 0.467836E+11 | 0.00 | 2.31 |
August | 0.402832E+11 | 0.00 | 0.00 | 0.256623E+09 | 0.00 | 0.736867E+09 | 0.483455E+11 | 0.00 | 2.01 |
September | 0.563141E+11 | 0.00 | 0.00 | 42314998.27 | 0.00 | 0.731572E+10 | 0.112291E+11 | 0.00 | 1.01 |
October | 0.326439E+11 | 0.00 | 0.00 | 9280547.05 | 0.00 | 0.521723E+11 | 0.712619E+09 | 0.00 | 0.67 |
November | 0.334028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121529E+12 | 0.00 | 0.00 | 0.65 |
December | 0.350960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131169E+12 | 0.00 | 0.00 | 0.64 |
Annual Sum or Average | 0.349529E+12 | 0.272032E+09 | 0.00 | 0.212271E+10 | 0.121660E+09 | 0.603454E+12 | 0.274170E+12 | 0.00 | 1.24 |
Minimum of Months | 0.329277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
Maximum of Months | 0.563141E+11 | 0.265207E+09 | 0.00 | 0.800123E+09 | 0.121051E+09 | 0.131169E+12 | 0.774170E+11 | 0.00 | 2.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.186274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219090E+12 | 0.00 | 0.00 | 0.77 |
February | 0.677336E+11 | 0.00 | 0.00 | 36141633.54 | 0.00 | 0.130480E+12 | 0.337340E+10 | 0.00 | 0.79 |
March | 0.933229E+11 | 0.00 | 0.00 | 0.555946E+09 | 0.00 | 0.807394E+11 | 0.489320E+11 | 0.00 | 0.88 |
April | 0.709379E+11 | 0.00 | 0.00 | 0.710331E+09 | 0.00 | 0.268259E+11 | 0.942741E+11 | 0.00 | 1.42 |
May | 0.791498E+11 | 0.00 | 0.00 | 0.398949E+09 | 0.00 | 0.112714E+10 | 0.101253E+12 | 0.00 | 2.25 |
June | 0.702163E+11 | 13185455.03 | 0.00 | 0.833746E+09 | 0.00 | 0.00 | 0.631764E+11 | 0.00 | 2.48 |
July | 0.653840E+11 | 0.826706E+09 | 0.00 | 0.287876E+09 | 85447470.65 | 0.00 | 0.399317E+11 | 0.00 | 2.17 |
August | 0.780721E+11 | 0.00 | 0.00 | 0.338938E+09 | 0.00 | 0.132491E+10 | 0.738666E+11 | 0.00 | 2.40 |
September | 0.908810E+11 | 0.00 | 0.00 | 0.219336E+09 | 0.00 | 0.879687E+10 | 0.525292E+11 | 0.00 | 1.36 |
October | 0.826687E+11 | 0.00 | 0.00 | 0.183765E+09 | 0.00 | 0.712685E+11 | 0.137620E+11 | 0.00 | 0.85 |
November | 0.411271E+11 | 0.00 | 0.00 | 12476.58 | 0.00 | 0.195017E+12 | 99093618.51 | 0.00 | 0.79 |
December | 0.527650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250354E+12 | 0.00 | 0.00 | 0.79 |
Annual Sum or Average | 0.763397E+12 | 0.839891E+09 | 0.00 | 0.356504E+10 | 85447470.65 | 0.985025E+12 | 0.491197E+12 | 0.00 | 1.42 |
Minimum of Months | 0.527650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 |
Maximum of Months | 0.933229E+11 | 0.826706E+09 | 0.00 | 0.833746E+09 | 85447470.65 | 0.250354E+12 | 0.101253E+12 | 0.00 | 2.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.261074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156937E+12 | 0.00 | 0.00 | 0.80 |
February | 0.193192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115614E+12 | 0.00 | 0.00 | 0.82 |
March | 0.549067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830136E+11 | 0.00 | 0.00 | 0.84 |
April | 0.642469E+11 | 0.00 | 0.00 | 0.154970E+09 | 0.00 | 0.204655E+11 | 0.232975E+11 | 0.00 | 1.18 |
May | 0.727168E+11 | 0.00 | 0.00 | 81690301.01 | 0.00 | 0.814193E+09 | 0.304968E+11 | 0.00 | 1.94 |
June | 0.546862E+11 | 11518445.20 | 0.00 | 0.328190E+09 | 0.00 | 0.00 | 0.263639E+11 | 0.00 | 2.36 |
July | 0.481627E+11 | 0.428558E+09 | 0.00 | 93774353.03 | 70526567.11 | 0.00 | 0.155542E+11 | 0.00 | 1.95 |
August | 0.649273E+11 | 0.00 | 0.00 | 68902464.65 | 0.00 | 0.812221E+09 | 0.205033E+11 | 0.00 | 2.03 |
September | 0.754069E+11 | 0.00 | 0.00 | 20073559.08 | 0.00 | 0.815720E+10 | 0.653283E+10 | 0.00 | 1.20 |
October | 0.467413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624882E+11 | 0.00 | 0.00 | 0.85 |
November | 0.108552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147669E+12 | 0.00 | 0.00 | 0.83 |
December | 0.648726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164964E+12 | 0.00 | 0.00 | 0.82 |
Annual Sum or Average | 0.521067E+12 | 0.440076E+09 | 0.00 | 0.747600E+09 | 70526567.11 | 0.760935E+12 | 0.122749E+12 | 0.00 | 1.31 |
Minimum of Months | 0.261074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 |
Maximum of Months | 0.754069E+11 | 0.428558E+09 | 0.00 | 0.328190E+09 | 70526567.11 | 0.164964E+12 | 0.304968E+11 | 0.00 | 2.36 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.115375E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154118E+11 | 0.00 | 0.00 | 0.53 |
February | 0.199421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126911E+11 | 0.00 | 0.00 | 0.55 |
March | 0.139121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126401E+11 | 0.00 | 0.00 | 0.60 |
April | 0.720165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444344E+10 | 0.00 | 0.00 | 0.86 |
May | 0.115762E+11 | 0.00 | 0.00 | 443448.12 | 0.00 | 0.617638E+09 | 0.647869E+09 | 0.00 | 1.56 |
June | 0.830887E+10 | 73635.32 | 0.00 | 12125319.97 | 0.00 | 0.00 | 0.190066E+10 | 0.00 | 1.82 |
July | 0.645960E+10 | 18141173.63 | 0.00 | 5598273.44 | 21691859.74 | 621709.31 | 0.176383E+10 | 0.00 | 1.61 |
August | 0.921504E+10 | 0.00 | 0.00 | 1288456.85 | 675.01 | 0.346005E+09 | 0.110282E+10 | 0.00 | 1.65 |
September | 0.748199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301047E+10 | 0.00 | 0.00 | 1.00 |
October | 0.186996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.931673E+10 | 0.00 | 0.00 | 0.63 |
November | 98022178.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148995E+11 | 0.00 | 0.00 | 0.53 |
December | 0.154410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160335E+11 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.540718E+11 | 18214808.95 | 0.00 | 19455498.39 | 21692534.75 | 0.894109E+11 | 0.541518E+10 | 0.00 | 0.99 |
Minimum of Months | 98022178.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.115762E+11 | 18141173.63 | 0.00 | 12125319.97 | 21691859.74 | 0.160335E+11 | 0.190066E+10 | 0.00 | 1.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 73820423.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101958E+11 | 0.00 | 0.00 | 0.55 |
February | 0.341752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818358E+10 | 0.00 | 0.00 | 0.56 |
March | 0.387420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540488E+10 | 0.00 | 0.00 | 0.62 |
April | 0.504411E+10 | 0.00 | 0.00 | 7988867.66 | 0.00 | 0.181859E+10 | 0.988181E+09 | 0.00 | 0.91 |
May | 0.413179E+10 | 0.00 | 0.00 | 26504181.62 | 0.00 | 0.196409E+09 | 0.631619E+10 | 0.00 | 2.02 |
June | 0.276772E+10 | 48702.22 | 0.00 | 76340587.15 | 0.00 | 204480.55 | 0.653567E+10 | 0.00 | 2.53 |
July | 0.276382E+10 | 20367202.83 | 0.00 | 43383880.72 | 7252720.02 | 411197.05 | 0.462073E+10 | 0.00 | 2.31 |
August | 0.420368E+10 | 0.00 | 0.00 | 19917310.94 | 446.45 | 83589881.17 | 0.405504E+10 | 0.00 | 2.00 |
September | 0.530599E+10 | 0.00 | 0.00 | 1455127.85 | 0.00 | 0.122740E+10 | 0.424493E+09 | 0.00 | 1.03 |
October | 0.219319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520534E+10 | 0.00 | 0.00 | 0.65 |
November | 64371703.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985497E+10 | 0.00 | 0.00 | 0.55 |
December | 97661297.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106091E+11 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.308621E+11 | 20415905.06 | 0.00 | 0.175590E+09 | 7253166.47 | 0.527803E+11 | 0.229403E+11 | 0.00 | 1.19 |
Minimum of Months | 64371703.56 | 0.00 | 0.00 | 0.00 | 0.00 | 204480.55 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.530599E+10 | 20367202.83 | 0.00 | 76340587.15 | 7252720.02 | 0.106091E+11 | 0.653567E+10 | 0.00 | 2.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.794154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158970E+11 | 0.00 | 0.00 | 0.57 |
February | 0.341557E+10 | 0.00 | 0.00 | 694845.80 | 0.00 | 0.103782E+11 | 61957487.21 | 0.00 | 0.59 |
March | 0.609265E+10 | 0.00 | 0.00 | 37662928.48 | 0.00 | 0.703421E+10 | 0.277883E+10 | 0.00 | 0.68 |
April | 0.536076E+10 | 0.00 | 0.00 | 57039791.33 | 0.00 | 0.279992E+10 | 0.783675E+10 | 0.00 | 1.26 |
May | 0.688373E+10 | 0.00 | 0.00 | 32983540.05 | 0.00 | 0.945979E+09 | 0.926866E+10 | 0.00 | 2.16 |
June | 0.669678E+10 | 79224.25 | 0.00 | 79976596.78 | 0.00 | 3878003.19 | 0.671066E+10 | 0.00 | 2.47 |
July | 0.595550E+10 | 58546978.89 | 0.00 | 26394002.21 | 6256158.96 | 1492995.72 | 0.442455E+10 | 0.00 | 2.15 |
August | 0.677194E+10 | 0.00 | 0.00 | 29736368.06 | 726.25 | 0.275015E+09 | 0.726825E+10 | 0.00 | 2.33 |
September | 0.662589E+10 | 0.00 | 0.00 | 16479614.36 | 0.00 | 0.216202E+10 | 0.377392E+10 | 0.00 | 1.23 |
October | 0.474804E+10 | 0.00 | 0.00 | 11074444.99 | 0.00 | 0.679309E+10 | 0.723875E+09 | 0.00 | 0.70 |
November | 0.146880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146610E+11 | 0.00 | 0.00 | 0.57 |
December | 0.165428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172457E+11 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 0.549792E+11 | 58626203.13 | 0.00 | 0.292042E+09 | 6256885.21 | 0.781976E+11 | 0.428474E+11 | 0.00 | 1.28 |
Minimum of Months | 0.165428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1492995.72 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.688373E+10 | 58546978.89 | 0.00 | 79976596.78 | 6256158.96 | 0.172457E+11 | 0.926866E+10 | 0.00 | 2.47 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 95193865.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110669E+11 | 0.00 | 0.00 | 0.60 |
February | 0.713651E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.854944E+10 | 0.00 | 0.00 | 0.61 |
March | 0.308321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700829E+10 | 0.00 | 0.00 | 0.67 |
April | 0.484716E+10 | 0.00 | 0.00 | 13872074.31 | 0.00 | 0.215054E+10 | 0.206597E+10 | 0.00 | 1.07 |
May | 0.660884E+10 | 0.00 | 0.00 | 6902724.41 | 0.00 | 0.458971E+09 | 0.281354E+10 | 0.00 | 1.92 |
June | 0.526077E+10 | 87893.24 | 0.00 | 31782097.39 | 0.00 | 783124.99 | 0.283769E+10 | 0.00 | 2.36 |
July | 0.444063E+10 | 32297963.88 | 0.00 | 9116144.24 | 4056038.16 | 0.00 | 0.174660E+10 | 0.00 | 1.95 |
August | 0.586423E+10 | 485.78 | 0.00 | 6266991.83 | 0.00 | 0.146047E+09 | 0.200585E+10 | 0.00 | 2.00 |
September | 0.545767E+10 | 0.00 | 0.00 | 1509925.15 | 0.00 | 0.162964E+10 | 0.502125E+09 | 0.00 | 1.13 |
October | 0.234629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570118E+10 | 0.00 | 0.00 | 0.71 |
November | 0.137066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106507E+11 | 0.00 | 0.00 | 0.60 |
December | 0.132760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115116E+11 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.389875E+11 | 32386342.90 | 0.00 | 69449957.34 | 4056038.16 | 0.588741E+11 | 0.119718E+11 | 0.00 | 1.19 |
Minimum of Months | 95193865.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.660884E+10 | 32297963.88 | 0.00 | 31782097.39 | 4056038.16 | 0.115116E+11 | 0.283769E+10 | 0.00 | 2.36 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 31144294.14 | 0.00 | 0.00 | 5206349.61 | 0.00 | 0.00 | 0.116352E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 84374895.60 | 0.00 | 0.00 | 0.911786E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.128292E+09 | 0.00 | 0.00 | 0.915847E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.103451E+09 | 0.00 | 0.00 | 0.551257E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 10422901.85 | 0.00 | 0.00 | 0.453798E+09 | 0.00 | 0.30 |
June | 0.00 | 94483.95 | 0.00 | 51604265.30 | 0.00 | 0.00 | 0.254685E+09 | 0.00 | 0.30 |
July | 0.00 | 548349.66 | 0.00 | 52697397.66 | 0.00 | 0.00 | 0.177261E+09 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 57545624.79 | 0.00 | 0.00 | 0.305095E+09 | 0.00 | 0.30 |
September | 0.00 | 0.00 | 0.00 | 9563240.11 | 0.00 | 0.00 | 0.553355E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 63420546.60 | 0.00 | 0.00 | 0.745185E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.244231E+09 | 0.00 | 0.00 | 0.950777E+09 | 0.00 | 0.29 |
December | 0.00 | 0.00 | 0.00 | 0.368547E+09 | 0.00 | 0.00 | 0.951245E+09 | 0.00 | 0.28 |
Annual Sum or Average | 31144294.14 | 642833.62 | 0.00 | 0.117936E+10 | 0.00 | 0.00 | 0.793382E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 5206349.61 | 0.00 | 0.00 | 0.177261E+09 | 0.00 | 0.28 |
Maximum of Months | 31144294.14 | 548349.66 | 0.00 | 0.368547E+09 | 0.00 | 0.00 | 0.116352E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.440927E+10 | 0.00 | 0.00 | 18888236.36 | 0.00 | 0.00 | 0.748553E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 0.678119E+09 | 0.00 | 0.00 | 0.924342E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.114893E+10 | 0.00 | 0.00 | 0.928534E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.945881E+09 | 0.00 | 0.00 | 0.560176E+10 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 87905356.98 | 0.00 | 0.00 | 0.455328E+10 | 0.00 | 0.30 |
June | 0.00 | 918346.72 | 0.00 | 0.485640E+09 | 0.00 | 0.00 | 0.257737E+10 | 0.00 | 0.30 |
July | 0.00 | 5477193.68 | 0.00 | 0.491911E+09 | 0.00 | 0.00 | 0.180874E+10 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 0.537892E+09 | 0.00 | 0.00 | 0.309532E+10 | 0.00 | 0.30 |
September | 0.00 | 0.00 | 0.00 | 73915628.67 | 0.00 | 0.00 | 0.555422E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 0.525213E+09 | 0.00 | 0.00 | 0.756074E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.206759E+10 | 0.00 | 0.00 | 0.981248E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.326164E+10 | 0.00 | 0.00 | 0.985259E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.440927E+10 | 6395540.40 | 0.00 | 0.103235E+11 | 0.00 | 0.00 | 0.764308E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 18888236.36 | 0.00 | 0.00 | 0.180874E+10 | 0.00 | 0.28 |
Maximum of Months | 0.440927E+10 | 5477193.68 | 0.00 | 0.326164E+10 | 0.00 | 0.00 | 0.985259E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.104684E+10 | 0.00 | 0.00 | 40556.57 | 0.00 | 0.00 | 0.127950E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 49521929.70 | 0.00 | 0.00 | 0.938790E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 99128638.05 | 0.00 | 0.00 | 0.942953E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 88461185.49 | 0.00 | 0.00 | 0.566282E+09 | 0.00 | 0.29 |
May | 11693721.88 | 0.00 | 0.00 | 7412887.01 | 0.00 | 0.00 | 0.445079E+09 | 0.00 | 0.30 |
June | 0.00 | 92058.75 | 0.00 | 47239897.17 | 0.00 | 0.00 | 0.259138E+09 | 0.00 | 0.30 |
July | 0.00 | 547756.23 | 0.00 | 47620490.10 | 0.00 | 0.00 | 0.182570E+09 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 51920050.26 | 0.00 | 0.00 | 0.312429E+09 | 0.00 | 0.30 |
September | 88732025.52 | 0.00 | 0.00 | 4773769.53 | 0.00 | 0.00 | 0.469332E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 40473614.21 | 0.00 | 0.00 | 0.768126E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.172946E+09 | 0.00 | 0.00 | 0.100674E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.288763E+09 | 0.00 | 0.00 | 0.101444E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.114727E+10 | 639814.98 | 0.00 | 0.898302E+09 | 0.00 | 0.00 | 0.703383E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 40556.57 | 0.00 | 0.00 | 0.127950E+09 | 0.00 | 0.28 |
Maximum of Months | 0.104684E+10 | 547756.23 | 0.00 | 0.288763E+09 | 0.00 | 0.00 | 0.101444E+10 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.104437E+10 | 0.00 | 0.00 | 0.346270E+12 | 0.00 | 3.67 |
February | 0.132165E+11 | 0.00 | 0.00 | 0.318293E+10 | 0.00 | 0.00 | 0.425011E+12 | 0.00 | 5.84 |
March | 0.694488E+10 | 0.00 | 0.00 | 0.675674E+10 | 0.00 | 0.00 | 0.725741E+12 | 0.00 | 9.94 |
April | 0.00 | 0.00 | 0.00 | 0.945120E+10 | 0.00 | 0.00 | 0.100768E+13 | 0.00 | 21.97 |
May | 990393.55 | 0.00 | 0.00 | 0.997126E+09 | 0.00 | 0.00 | 0.418584E+12 | 0.00 | 11.08 |
June | 0.120024E+10 | 9465290.03 | 0.00 | 0.296043E+10 | 166055.82 | 0.00 | 0.399844E+12 | 0.00 | 23.13 |
July | 0.549198E+09 | 18630021.24 | 0.00 | 0.541424E+10 | 0.00 | 0.00 | 0.543917E+12 | 0.00 | 36.38 |
August | 0.00 | 0.00 | 0.00 | 0.558676E+10 | 0.00 | 0.00 | 0.837636E+12 | 0.00 | 45.91 |
September | 2189904.23 | 0.00 | 0.00 | 0.901009E+09 | 0.00 | 0.00 | 0.335934E+12 | 0.00 | 8.65 |
October | 0.954734E+10 | 0.00 | 0.00 | 0.363896E+10 | 0.00 | 0.00 | 0.492236E+12 | 0.00 | 8.84 |
November | 0.957544E+09 | 0.00 | 0.00 | 0.782915E+10 | 0.00 | 0.00 | 0.739498E+12 | 0.00 | 8.44 |
December | 0.00 | 0.00 | 0.00 | 0.129630E+11 | 0.00 | 0.00 | 0.102571E+13 | 0.00 | 11.22 |
Annual Sum or Average | 0.324188E+11 | 28095311.28 | 0.00 | 0.607259E+11 | 166055.82 | 0.00 | 0.729807E+13 | 0.00 | 16.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.901009E+09 | 0.00 | 0.00 | 0.335934E+12 | 0.00 | 3.67 |
Maximum of Months | 0.132165E+11 | 18630021.24 | 0.00 | 0.129630E+11 | 166055.82 | 0.00 | 0.102571E+13 | 0.00 | 45.91 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:26:42
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.649700E+10 | 0.236914E+11 | 0.00 | 0.245479E+13 | 0.640561E+12 |
February | 0.830931E+11 | 0.192124E+11 | 0.00 | 0.235279E+13 | 0.760723E+12 |
March | 0.372039E+12 | 0.289045E+11 | 0.00 | 0.301847E+13 | 0.981112E+12 |
April | 0.644314E+12 | 0.318980E+11 | 0.00 | 0.348351E+13 | 0.829675E+12 |
May | 0.790587E+12 | 0.183477E+11 | 0.00 | 0.327129E+13 | 0.336491E+12 |
June | 0.813353E+12 | 0.101277E+11 | 0.00 | 0.277072E+13 | 0.124831E+13 |
July | 0.738232E+12 | 0.822701E+10 | 0.00 | 0.309567E+13 | 0.168699E+13 |
August | 0.551501E+12 | 0.969879E+10 | 0.00 | 0.351508E+13 | 0.131988E+13 |
September | 0.259330E+12 | 0.115195E+11 | 0.00 | 0.298714E+13 | 0.212651E+12 |
October | 0.116990E+12 | 0.249246E+11 | 0.00 | 0.279333E+13 | 0.687862E+12 |
November | 0.176769E+11 | 0.887522E+10 | 0.00 | 0.289995E+13 | 0.100814E+13 |
December | -0.175515E+11 | 0.173914E+11 | 0.00 | 0.326720E+13 | 0.117774E+13 |
Annual Sum or Average | 0.436307E+13 | 0.212818E+12 | 0.00 | 0.359099E+14 | 0.108901E+14 |
Minimum of Months | -0.175515E+11 | 0.822701E+10 | 0.00 | 0.235279E+13 | 0.212651E+12 |
Maximum of Months | 0.813353E+12 | 0.318980E+11 | 0.00 | 0.351508E+13 | 0.168699E+13 |