Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:22
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2024-07-03 12:22:34
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 36537.90 | 788.81 | 788.81 |
Net Site Energy | 36537.90 | 788.81 | 788.81 |
Total Source Energy | 105783.97 | 2283.75 | 2283.75 |
Net Source Energy | 105783.97 | 2283.75 | 2283.75 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 4767.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1730.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1005.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3103.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 788.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 58.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5670.72 |
Humidification | 1695.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.89 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 478.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 31769.99 | 4767.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8581.77 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 4767.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1730.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 1005.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 56.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 3103.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 788.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 58.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5670.72 |
Humidification | General | 1695.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.89 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 478.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 4767.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1730.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 1005.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 3103.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 788.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 58.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5670.72 |
Humidification | Unassigned | 1695.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.89 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 478.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 169.57 | 102.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 685.87 | 102.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 169.57 | 102.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 685.87 | 102.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 31769.985 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 31769.985 | 100.00 |
Total On-Site and Utility Electric Sources | 31769.985 | 100.00 |
Total Electricity End Uses | 31769.985 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 8581.77 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 8581.77 | 100.00 |
Total Water End Uses | 8581.77 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 79.50 |
Time Setpoint Not Met During Occupied Cooling | 180.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5097.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS SZVAV FAN | AIRLOOP DATACENTER BASEMENT SYS11 FAN | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:22 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 11.6510 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 11.6510 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 11.6510 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.6510 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 11.6510 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.6510 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 11.6510 | 18.58 | 484.4232 | |
Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.6100 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 07-AUG-15:20 | 09-JAN-07:19 | - | - | - | - | - | - | - | - | - | - | 17-JUL-15:00 |
Heating | 0.00 | 2729835.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 371987.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235096.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 340147.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 87549.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 40289.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35991.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2379332.99 | 2729835.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2729835.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 371987.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 340147.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 87549.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 40289.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 35991.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 5168.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5479.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17769.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3183.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8307.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9827.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2496.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 184.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 5371.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1515.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 100615.54 | 5168.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 111.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 118.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 212.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 53.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 115.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 32.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2172.17 | 111.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 111.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 118.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 212.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 53.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 115.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 32.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2172.17 | 111.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 7.91 | 0.267858 | 0.300000 | 2.37 |
DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | 35.92 | 0.016623 | 0.500000 | 17.96 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 8.43 | 0.225694 | 0.300000 | 2.53 | 0.601850 | 0.500000 | 0.001688 | 0.000288 | 2.53 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 80.06 | 0.237563 | 0.300000 | 24.02 | 0.633501 | 0.500000 | 0.001604 | 0.005804 | 31.73 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 10.09 | 0.188556 | 0.300000 | 3.03 | 0.502816 | 0.500000 | 0.002021 | 0.001832 | 10.09 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.79 | 0.133351 | 0.300000 | 0.537273 | 0.355604 | 0.500000 | 0.002857 | 0.000325 | 1.79 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.91 | 0.080601 | 0.300000 | 0.572841 | 0.300000 | 0.500000 | 0.004727 | 0.000221 | 1.22 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 2.44 | 0.097713 | 0.300000 | 0.733247 | 0.300000 | 0.500000 | 0.003899 | 0.000358 | 1.97 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 2.38 | 0.064725 | 0.300000 | 0.713353 | 0.300000 | 0.500000 | 0.005886 | 0.000191 | 1.05 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 23.72 | 0.100686 | 0.300000 | 7.12 | 0.300000 | 0.500000 | 0.003784 | 0.004302 | 23.72 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 20.22 | 0.300000 | 0.500000 | 0.005005 | 0.002858 | 15.76 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 24.64 | 0.096921 | 0.300000 | 7.39 | 0.300000 | 0.500000 | 0.003931 | 0.004394 | 24.23 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 22.24 | 0.069190 | 0.300000 | 6.67 | 0.300000 | 0.500000 | 0.005507 | 0.002847 | 15.70 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 3.15 | 0.075867 | 0.300000 | 0.944369 | 0.300000 | 0.500000 | 0.005022 | 0.000571 | 3.15 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 2.08 | 0.074162 | 0.300000 | 0.622577 | 0.300000 | 0.500000 | 0.005137 | 0.000376 | 2.08 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 3.20 | 0.074609 | 0.300000 | 0.960310 | 0.300000 | 0.500000 | 0.005107 | 0.000580 | 3.20 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 2.42 | 0.063707 | 0.300000 | 0.724747 | 0.300000 | 0.500000 | 0.005980 | 0.000380 | 2.10 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 32905.70 | 0.000288 | 697.43 | |
CORE_MID VAV BOX REHEAT COIL | 663454.26 | 0.005804 | 15529.98 | |
CORE_TOP VAV BOX REHEAT COIL | 209462.70 | 0.001832 | 4893.73 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 37147.51 | 0.000325 | 867.63 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 25222.84 | 0.000221 | 589.09 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 40879.80 | 0.000358 | 954.75 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 21807.28 | 0.000191 | 509.36 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 491724.02 | 0.004302 | 11483.09 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 326648.87 | 0.002858 | 7628.04 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 502240.11 | 0.004394 | 11728.57 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 325423.97 | 0.002847 | 7599.43 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 65237.59 | 0.000571 | 1523.34 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 43006.94 | 0.000376 | 1004.23 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 66337.74 | 0.000580 | 1549.02 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 43465.02 | 0.000380 | 1014.92 | |
VAV_BOT WITH REHEAT HEATING COIL | 70344.26 | 0.000615 | 1161.21 | |
VAV_MID WITH REHEAT HEATING COIL | 763257.46 | 0.006677 | 12411.54 | |
VAV_TOP WITH REHEAT HEATING COIL | 64169.54 | 0.000561 | 1098.84 | |
CAV_BAS HEATING COIL | 115658.17 | 0.000875 | 2621.31 | 100000.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 563211.79 | 0.000875 | 2621.31 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.869090 |
DATACENTER_MID_ZN_6 DIRECT AIR | 8.37 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.862278 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 8.47 | 5.08 | 16.95 | 7.11 | 14.06 | 14.06 | 0.300000 | 0.505468 | 14.06 |
VAV_MID WITH REHEAT | 85.44 | 51.27 | 170.89 | 111.14 | 130.55 | 130.55 | 0.300000 | 0.851323 | 130.55 |
VAV_TOP WITH REHEAT | 10.46 | 6.28 | 20.93 | 20.61 | 16.37 | 20.61 | 0.300000 | 1.00 | 20.61 |
CAV_BAS | 2.37 | 2.37 | 7.91 | 2.37 | 7.91 | 7.91 | 1.00 | 0.300000 | 7.91 |
AIRLOOP DATACENTER BASEMENT | 17.96 | 17.96 | 35.92 | 17.96 | 35.92 | 35.92 | 1.00 | 0.499998 | 35.92 |
AIRLOOP DATACENTER BOT | 0.869090 | 0.869090 | 0.869090 | 0.869090 | 0.869090 | 0.869090 | 1.00 | 1.000000 | 0.869090 |
AIRLOOP DATACENTER MID | 8.37 | 8.37 | 8.37 | 8.37 | 8.37 | 8.37 | 1.00 | 1.000000 | 8.37 |
AIRLOOP DATACENTER TOP | 0.862278 | 0.862278 | 0.862278 | 0.862278 | 0.862278 | 0.862278 | 1.00 | 1.00 | 0.862278 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 14.06 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 130.55 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 20.61 | |
CAV_BAS_OA_CONTROLLER | 7.91 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 35.92 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.869090 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 8.37 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.862278 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.36 | 6.67 | 10.86 | 0.007144 | 0.007000 | 223960.04 | 0.007999 | 14.06 |
VAV_MID WITH REHEAT COOLING COIL | 25.46 | 6.67 | 10.85 | 0.007144 | 0.007000 | 2095275.81 | 0.074838 | 130.55 |
VAV_TOP WITH REHEAT COOLING COIL | 25.15 | 6.67 | 10.88 | 0.007120 | 0.007000 | 321884.44 | 0.011497 | 20.61 |
CAV_BAS COOLING COIL | 25.47 | 6.67 | 10.84 | 0.007263 | 0.007000 | 126247.17 | 0.004509 | 7.91 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 27.06 | 6.67 | 14.93 | 0.007026 | 0.007000 | 454842.35 | 0.016246 | 35.92 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 14.06 |
VAV_MID WITH REHEAT FAN | 130.55 |
VAV_TOP WITH REHEAT FAN | 20.61 |
CAV_BAS SZVAV FAN | 7.91 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | 35.92 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007999 | 0.000060 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000615 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.074838 | 0.000006 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.006677 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.011497 | 0.000041 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000561 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | Design Size Minimum Supply Air Temperature [C] | User-Specified Minimum Supply Air Temperature [C] | User-Specified Maximum Supply Air Temperature [C] | User-Specified Nominal Cooling Capacity [W] | Design Size Maximum Supply Air Temperature [C] | |
CAV_BAS_UNITARY_PACKAGE_DX | 7.91 | 7.91 | 7.91 | 2.37 | 126247.17 | 100000.00 | 1.00 | 5.34 | 12.89 | 32.11 | ||
AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | 35.92 | 35.92 | 35.92 | 17.96 | 454842.35 | 100000.00 | 1.00 | 15.89 | 29.11 | |||
AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | 0.869090 | 0.869090 | 0.869090 | 0.869090 | 27229.65 | 1.00 | 14386.53 | 29.11 | ||||
AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | 8.37 | 8.37 | 8.37 | 8.37 | 262439.59 | 1.00 | 138568.66 | 29.11 | ||||
AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | 0.862278 | 0.862278 | 0.862278 | 0.862278 | 27019.80 | 1.00 | 14273.76 | 29.11 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000280 | 0.000037 | 96450.70 | 100000.00 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | 0.869090 | 1494.52 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | 8.37 | 14394.98 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | 0.862278 | 1482.81 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
AIRLOOP DATACENTER BOT COOLING COIL | 0.869090 | 0.434545 | 0.579393 | 14386.53 | 7193.27 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER MID COOLING COIL | 8.37 | 4.19 | 5.58 | 138568.66 | 69284.33 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.862280 | 0.431139 | 0.574853 | 14273.76 | 7136.88 | 0.800660 | 0.800660 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BOT HEATING COIL | 27229.65 |
AIRLOOP DATACENTER MID HEATING COIL | 262439.59 |
AIRLOOP DATACENTER TOP HEATING COIL | 27019.80 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.115090 | 23715.78 | |
HEATSYS1 PUMP | 0.034930 | 10519.44 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.115090 | 13.81 |
HEATSYS1 | 0.034930 | 4.19 |
COOLSYS1_SUPPLY | 0.115090 | 13.81 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.115090 | 0.115090 | 483089.93 | 6.67 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3992735.62 | 3992735.62 | 0.034930 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.057545 | 10945.92 |
COOLSYS1 CHILLER2 PUMP | 0.057545 | 10945.92 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.115090 | 0.058180 | 1628885.07 | 1628942.16 | 0.081637 |
COOLSYS1 CHILLER2 | 0.115090 | 0.058180 | 1628885.07 | 1628942.16 | 0.081637 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.163274 | 19.59 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.163274 | 56933.72 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 75.24 | 1952519.72 | 15.05 | 244064.97 |
TOWERWATERSYS COOLTOWER 2 | 75.24 | 1952519.72 | 15.05 | 244064.97 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 11.651 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 16.493 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 11.651 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 496.074 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 32383.100 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 32383.100 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 9130.649 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 9130.649 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
26 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
27 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
35 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
47 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
48 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
49 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
50 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
51 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
52 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
53 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
54 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
55 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
56 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
57 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
58 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
59 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
60 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
61 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
62 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
63 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
64 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
65 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
66 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
67 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
68 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
69 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
70 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
71 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
72 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
73 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
74 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
75 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
76 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
77 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
78 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
79 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
80 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
81 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
82 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
83 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
84 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
85 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
86 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
87 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
88 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
89 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
90 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
91 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
92 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
93 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
94 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
95 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
96 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
97 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
98 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
99 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
100 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
101 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
102 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
103 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
104 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
105 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
106 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
107 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
108 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
109 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
110 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
111 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
112 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
113 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
114 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
115 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
116 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
117 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
118 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
119 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
120 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
121 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone BASEMENT | 1.2500 |
3 | Zone CORE_BOTTOM | 1.2500 |
4 | Zone CORE_MID | 1.2500 |
5 | Zone CORE_TOP | 1.2500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.2500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.2500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.2500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone BASEMENT | 1.1500 |
3 | Zone CORE_BOTTOM | 1.1500 |
4 | Zone CORE_MID | 1.1500 |
5 | Zone CORE_TOP | 1.1500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.1500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.1500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.1500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 82582.17793 | 94969.50462 | 6.87554 | 7.90687 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 88023.52343 | 101227.05195 | 7.32829 | 8.42754 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 8706.61981 | 10883.27476 | 0.71344 | 1.07782 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 836409.26807 | 961870.65828 | 69.62158 | 80.06482 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 309628.75853 | 387035.94816 | 25.38713 | 31.73391 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 92558.17193 | 106441.89772 | 7.77210 | 8.93791 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 32.92000 | 6.30608E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 97276.95630 | 121596.19538 | 8.06994 | 10.08742 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 15080.16386 | 17342.18843 | 1.26625 | 1.45619 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.40000 | 6.30683E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 17241.34471 | 21551.68088 | 1.43273 | 1.79091 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 19774.51542 | 22740.69274 | 1.66041 | 1.90947 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 25.05333 | 6.29402E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 11705.83777 | 14632.29721 | 0.97291 | 1.21614 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 25311.64207 | 29108.38838 | 2.12535 | 2.44416 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.13333 | 6.30642E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 18971.09305 | 23713.86632 | 1.57694 | 1.97117 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 24625.00768 | 28318.75884 | 2.06769 | 2.37784 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 30.62667 | 6.30253E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 10123.10088 | 12653.87610 | 0.84091 | 1.05114 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 144006.48620 | 165607.45913 | 12.09181 | 13.90558 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.40000 | 6.30683E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 228170.79444 | 285213.49304 | 18.97546 | 23.71932 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 209394.85848 | 240804.08726 | 17.58211 | 20.21943 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.96000 | 6.29539E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 151567.81311 | 189459.76639 | 12.60584 | 15.75730 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 255186.40312 | 293464.36358 | 21.42715 | 24.64123 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.30663E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 233044.28222 | 291305.35278 | 19.38185 | 24.22731 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 230358.94244 | 264912.78380 | 19.34240 | 22.24376 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 150999.38308 | 188749.22885 | 12.55859 | 15.69824 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 17576.59657 | 20213.08606 | 1.47585 | 1.69722 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.24000 | 6.30658E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 30264.66053 | 37830.82567 | 2.51832 | 3.14790 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 21063.30409 | 24222.79970 | 1.76860 | 2.03389 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 26.86667 | 6.29676E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 19951.29288 | 24939.11610 | 1.66021 | 2.07526 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 28521.40030 | 32799.61034 | 2.39483 | 2.75406 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40000 | 6.30683E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 30774.57078 | 38468.21348 | 2.56083 | 3.20103 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 25018.68540 | 28771.48821 | 2.10072 | 2.41582 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 20163.50946 | 25204.38682 | 1.67792 | 2.09740 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 9000.10478 | 10350.12050 | 0.75573 | 0.86909 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 86687.18769 | 99690.26584 | 7.27907 | 8.37093 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8929.55578 | 10268.98915 | 0.74981 | 0.86228 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 26.57333 | 6.29632E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372023.17111 | 427826.64677 | 31.23789 | 35.92357 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 18.84000 | 6.28481E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 14:30:00 | -27.60000 | 3.41898E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 185440.66 | 14.06059 | 14.06059 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 86925.99 | 7.10719 | 7.10719 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:50:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1735419.75 | 130.54521 | 130.54521 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 858425.16 | 111.13608 | 111.13608 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:10:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 211963.37 | 16.36952 | 16.36952 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 82706.16 | 20.60900 | 20.60900 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 |
7 | CAV_BAS | Cooling | Sensible | 93568.43 | 7.90687 | 7.90687 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 75836.09 | 1.20016 | 1.20016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 424173.77 | 35.92372 | 35.92372 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 20308.21 | 0.33839 | 0.33839 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 10206.10 | 0.86909 | 0.86909 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 938.16 | 1.56323E-002 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 98298.70 | 8.37093 | 8.37093 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 9381.55 | 0.15632 | 0.15632 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 10130.86 | 0.86228 | 0.86228 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 938.16 | 1.56323E-002 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 7.90687 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.26786 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 2.37206 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.42754 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22569 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.52826 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60185 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.68813E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.87873E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.52826 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 32905.70252 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.87873E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 697.43272 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 80.06482 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23756 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 24.01945 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63350 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.60379E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.80419E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 31.73391 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 663454.26104 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.80419E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 15529.97553 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.08742 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18856 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.02623 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50282 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.02062E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.83247E-003 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 10.08742 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 209462.69912 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.83247E-003 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4893.73166 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.79091 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13335 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.53727 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35560 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.85711E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.24983E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.79091 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 37147.51454 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.24983E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 867.62603 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.90947 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.06009E-002 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.57284 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.72700E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.20660E-004 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.21614 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25222.83836 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.20660E-004 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 589.09378 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.44416 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.77129E-002 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.73325 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.89918E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.57634E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.97117 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 40879.80312 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.57634E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 954.75422 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.37784 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.47247E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.71335 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.88647E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.90780E-004 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.05114 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21807.27587 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.90780E-004 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 509.36361 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 23.71932 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10069 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 7.11580 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.78404E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.30182E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 23.71932 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 491724.02162 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.30182E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 11483.08556 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 20.21943 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.00542E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.85767E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 15.75730 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 326648.87103 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.85767E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7628.03824 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 24.64123 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.69212E-002 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 7.39237 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.93103E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.39382E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 24.22731 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 502240.10590 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.39382E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 11728.56736 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 22.24376 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.91902E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.67313 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.50656E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.84695E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 15.69824 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 325423.97244 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.84695E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7599.42936 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.14790 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.58667E-002 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.94437 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.02197E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.70727E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.14790 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 65237.58953 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.70727E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1523.33627 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.07526 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.41619E-002 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.62258 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.13741E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.76243E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.07526 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 43006.94358 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.76243E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1004.23059 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.20103 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.46090E-002 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.96031 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.10662E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.80351E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.20103 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 66337.73734 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.80351E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1549.01868 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.41582 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.37070E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.72475 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.98050E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.80251E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.09740 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 43465.01971 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.80251E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1014.92226 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.86909 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 8.37093 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.86228 |
215 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 35.92357 |
216 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 1.66232E-002 |
217 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
218 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 17.96178 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 8.47496 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.08498 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 16.94992 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 7.10719 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 14.06059 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 14.06059 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.50547 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 85.44428 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 51.26657 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 170.88855 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 111.13608 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 130.54521 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 130.54521 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.85132 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 10.46372 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.27823 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 20.92743 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 20.60900 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 16.36952 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 20.60900 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 1.00000 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.37206 |
244 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.37206 |
245 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.90687 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.37206 |
247 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.90687 |
248 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 7.90687 |
249 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.30000 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 17.96178 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 17.96178 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 35.92357 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 17.96178 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 35.92372 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 35.92372 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.50000 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.86909 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.86909 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.86909 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.86909 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.86909 |
264 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.86909 |
265 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 8.37093 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 8.37093 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.37093 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 8.37093 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.37093 |
272 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 8.37093 |
273 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
274 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.86228 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.86228 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.86228 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.86228 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.86228 |
280 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.86228 |
281 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
282 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
283 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 14.06059 |
284 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 130.54521 |
285 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 20.60900 |
286 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 7.90687 |
287 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 35.92372 |
288 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.86909 |
289 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 8.37093 |
290 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.86228 |
291 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 14.06059 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.35704 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.85868 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.14415E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 223960.04207 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.99933E-003 |
299 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 14.06059 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 70344.26031 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.15402E-004 |
302 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1161.20700 |
303 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 14.06059 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.99933E-003 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.95288E-005 |
306 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.15402E-004 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 130.54521 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.46256 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.85005 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.14400E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2095275.80550 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.48384E-002 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 130.54521 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 763257.46269 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.67731E-003 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 12411.54353 |
319 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 130.54521 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.48384E-002 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.36292E-006 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.67731E-003 |
323 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 20.60900 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.14728 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.87774 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.12021E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 321884.44179 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.14970E-002 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 20.60900 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 64169.53895 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.61383E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1098.83881 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 20.60900 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.14970E-002 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.14188E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.61383E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.90687 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.90687 |
342 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.90687 |
343 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.90687 |
344 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.37206 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.46716 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.83960 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.26313E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 126247.16694 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.50926E-003 |
352 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.90687 |
353 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 126247.16694 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 115658.16782 |
355 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
356 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
357 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2621.30818 |
358 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
359 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
360 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Minimum Supply Air Temperature [C] | 5.33790 |
361 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 12.88890 |
362 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 32.11110 |
363 | Fan:VariableVolume | CAV_BAS SZVAV FAN | Design Size Maximum Flow Rate [m3/s] | 7.90687 |
364 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 35.92372 |
365 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
366 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 35.92372 |
367 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 35.92372 |
368 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 35.92372 |
369 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 17.96186 |
370 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.05817 |
371 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
372 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 14.92556 |
373 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.02611E-003 |
374 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
375 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Coil Load [W] | 454842.34972 |
376 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.62459E-002 |
377 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 35.92372 |
378 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 454842.34972 |
379 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Capacity [W] | 563211.78524 |
380 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
381 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
382 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2621.30818 |
383 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
384 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
385 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 15.88890 |
386 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 29.11110 |
387 | Fan:VariableVolume | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Design Size Maximum Flow Rate [m3/s] | 35.92372 |
388 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.79758E-004 |
389 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
390 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
391 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.86909 |
393 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
394 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.86909 |
395 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1494.52113 |
396 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.86909 |
397 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.86909 |
398 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.86909 |
399 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.86909 |
400 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.86909 |
401 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.43455 |
402 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.57939 |
403 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 14386.53000 |
404 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7193.26500 |
405 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
406 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
407 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 14386.53000 |
408 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27229.64694 |
409 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
410 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
411 | Coil:Heating:Fuel | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Nominal Capacity [W] | 27229.64694 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.37093 |
413 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
414 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 8.37093 |
415 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 14394.98218 |
416 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 8.37093 |
417 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 8.37093 |
418 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.37093 |
419 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 8.37093 |
420 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 8.37093 |
421 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 4.18547 |
422 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.58062 |
423 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 138568.66000 |
424 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 69284.33000 |
425 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
426 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
427 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 138568.66000 |
428 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 262439.58862 |
429 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
430 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
431 | Coil:Heating:Fuel | AIRLOOP DATACENTER MID HEATING COIL | Design Size Nominal Capacity [W] | 262439.58862 |
432 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.86228 |
433 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
434 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.86228 |
435 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1482.80704 |
436 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.86228 |
437 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.86228 |
438 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.86228 |
439 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.86228 |
440 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.86228 |
441 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.43114 |
442 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.57485 |
443 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 14273.76000 |
444 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7136.88000 |
445 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
446 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
447 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 14273.76000 |
448 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27019.79919 |
449 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
450 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
451 | Coil:Heating:Fuel | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Nominal Capacity [W] | 27019.79919 |
452 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.11509 |
453 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 23715.77560 |
454 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.11509 |
455 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 13.81078 |
456 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.11509 |
457 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.11509 |
458 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 483089.92594 |
459 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 6.67000 |
460 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.49302E-002 |
461 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 4.19162 |
462 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.49302E-002 |
463 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 10519.44017 |
464 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
465 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3992735.61768 |
466 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 3992735.62000 |
467 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.49302E-002 |
468 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.11509 |
469 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 13.81078 |
470 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 5.75449E-002 |
471 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 10945.91799 |
472 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 5.75449E-002 |
473 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 10945.91799 |
474 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.11509 |
475 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.81800E-002 |
476 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1628885.07133 |
477 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1628942.15500 |
478 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 8.16368E-002 |
479 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.11509 |
480 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.81800E-002 |
481 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1628885.07133 |
482 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1628942.15500 |
483 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 8.16368E-002 |
484 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
485 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
486 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
487 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
488 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
489 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.16327 |
490 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 19.59284 |
491 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.16327 |
492 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 56933.72347 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 75.23523 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1952519.72414 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 15.04705 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 244064.96552 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 75.23523 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1952519.72414 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 15.04705 |
500 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 244064.96552 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 31237.21 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 629552.46 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 198760.70 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 35249.59 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 23934.17 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 38791.19 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 20693.10 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 466601.30 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 309960.04 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 476580.12 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 308797.72 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 61904.55 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 40809.69 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 62948.49 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 41244.36 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 54408.81 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 572441.56 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 53368.65 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94845.12 |
20 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | 94845.12 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 379250.73 | 236790.03 | 142460.70 | 0.62 | 123483.58 | 1252.44 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 3533042.35 | 2203127.75 | 1329914.60 | 0.62 | 1136212.56 | 11524.10 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 551021.66 | 345168.18 | 205853.48 | 0.63 | 185562.38 | 1882.08 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 215091.26 | 133872.10 | 81219.16 | 0.62 | 74605.96 | 756.70 |
5 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | 735705.55 | 512377.89 | 223327.66 | 0.70 | 116770.90 | 1184.36 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | 13705.4 | 9.16 | 9.16 | |||
2 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | 132008.3 | 10.40 | 10.40 | |||
3 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | 13598.0 | 9.16 | 9.16 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 6.37 | 21.74 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 6.37 | 21.74 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6691073485E-003 | 1.4567967192E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 6.2301045392E-002 | 0.1476592594 | Pass | Pass | 6.4013064609E-002 | 0.2448303388 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 8.5694021811E-002 | 7.0010630627E-002 | Pass | Pass | 0.3594486246 | 0.4842169748 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.4539542139E-002 | 3.1268140664E-002 | Pass | Pass | 2.7517353905 | 23.7915073962 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.5909973972E-002 | 0.1261882145 | Pass | Pass | 6.4133737132E-002 | 0.2443275652 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1322593856 | 0.2424422100 | Pass | Pass | 6.6439899310E-002 | 0.2493656337 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2104828760 | 0.3308859088 | Pass | Pass | 6.4521180969E-002 | 0.2456750620 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1233280486 | 0.2758661607 | Pass | Pass | 6.5333580718E-002 | 0.2413126285 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2034601160 | 0.2630935458 | Pass | Pass | 0.8120435654 | 1.3206127593 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1680564493 | 0.2307211527 | Pass | Pass | 0.9676608758 | 2.5145503235 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2208185467 | 0.2047657184 | Pass | Pass | 0.7978511218 | 3.5262553253 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1292364762 | 0.1331134460 | Pass | Pass | 0.5543307146 | 0.7611554670 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4229931271 | 0.4741176530 | Pass | Pass | 3.8252148413 | 16.8669465541 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3262263760 | 0.4491269676 | Pass | Pass | 14.7686845335 | 105.4031395887 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3576906777 | 0.4022107683 | Pass | Pass | 1.2466504452 | 6.1190771563 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2801059033 | 0.3464414076 | Pass | Pass | 3.8674342300 | 36.9978140503 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.0599959949E-002 | 3.2186187842E-002 | Pass | Pass | 7.4284584740E-002 | 0.2670681335 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.3573122164E-002 | 2.5366882339E-002 | Pass | Pass | 0.4555851070 | 0.9161412388 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1995037660 | 0.1569464909 | Pass | Pass | 0.6164790305 | 0.7261555247 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.7985036680E-006 | 2.1498466077E-006 | Pass | Pass | 7.7866198458E-003 | 6.3271661497E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.3213666789E-002 | 1.3426321607E-002 | Pass | Pass | 9.3197635290E-003 | 1.4842348471E-002 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.5243626796E-002 | 2.7555253555E-002 | Pass | Pass | 4.1441456030E-003 | 3.9108508568E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.2930290305E-002 | 2.7569619093E-002 | Pass | Pass | 1.7320829875E-003 | 1.6386532496E-003 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6768.51 | 290.28 | 0.00 | 31941.83 | 13498.35 | 52498.97 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
North Total or Average | 1390.74 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 3.241 | 0.391 | 0.431 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 11.6510 | 2779.43 | 32383.10 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 333.79 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.6510 | 24961.20 | 290822.99 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 2997.66 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.6510 | 3134.13 | 36515.73 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.6510 | 3134.20 | 36516.53 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 11.6510 | 783.68 | 9130.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 94.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 22.3674 | 362.03 | 8097.60 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 83.47 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
Interior Lighting Total | 11.7515 | 46320.38 | 544334.28 | 1723.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 64082.80 | AstronomicalClock | - | 83.57 | 83.57 | 1005.27 | |
Exterior Lighting Total | 64082.80 | 1005.27 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3213814.11 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 3992735.62 | 0.79 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1628942.16 | 6.11 | 1620993.80 | 6.08 | 6.37 | 21.74 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1628942.16 | 6.11 | 1620993.80 | 6.08 | 6.37 | 21.74 |
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1952519.72 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1952519.72 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 223960.04 | 379250.73 | 236790.03 | 142460.70 | 0.62 | - | 123483.58 | 1252.44 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2095275.81 | 3533042.35 | 2203127.75 | 1329914.60 | 0.62 | - | 1136212.56 | 11524.10 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 321884.44 | 551021.66 | 345168.18 | 205853.48 | 0.63 | - | 185562.38 | 1882.08 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 126247.17 | 215091.26 | 133872.10 | 81219.16 | 0.62 | - | 74605.96 | 756.70 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | 454842.35 | 735705.55 | 512377.89 | 223327.66 | 0.70 | - | 116770.90 | 1184.36 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | 14386.53 | 11518.72 | 2867.81 | 0.80 | 3.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | 138568.66 | 110946.38 | 27622.28 | 0.80 | 3.50 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 14273.76 | 11428.43 | 2845.33 | 0.80 | 3.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
AIRLOOP DATACENTER BOT COOLING COIL | 13705.4 | 9.16 | 9.16 | ||||
AIRLOOP DATACENTER MID COOLING COIL | 132008.3 | 10.40 | 10.40 | ||||
AIRLOOP DATACENTER TOP COOLING COIL | 13598.0 | 9.16 | 9.16 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 32905.70 | 31237.21 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 663454.26 | 629552.46 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 209462.70 | 198760.70 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 37147.51 | 35249.59 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 25222.84 | 23934.17 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 40879.80 | 38791.19 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 21807.28 | 20693.10 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 491724.02 | 466601.30 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 326648.87 | 309960.04 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 502240.11 | 476580.12 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 325423.97 | 308797.72 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 65237.59 | 61904.55 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 43006.94 | 40809.69 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 66337.74 | 62948.49 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 43465.02 | 41244.36 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 70344.26 | 54408.81 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 763257.46 | 572441.56 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 64169.54 | 53368.65 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94845.12 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | 100000.00 | 94845.12 | - |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | 27229.65 | 0.80 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | 262439.59 | 0.79 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | 27019.80 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 14.06 | 30607.80 | 2176.85 | 1.00 | 1.12 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 130.55 | 285385.29 | 2186.10 | 1.00 | 1.08 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1337.13 | 20.61 | 44439.48 | 2156.31 | 1.00 | 1.12 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
CAV_BAS SZVAV FAN | Fan:VariableVolume | 0.61 | 1337.13 | 7.91 | 17377.58 | 2197.78 | 1.00 | 1.12 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 0.62 | 637.69 | 35.92 | 37098.23 | 1032.69 | 1.00 | 1.20 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.87 | 1494.52 | 1719.64 | 1.00 | 1.32 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 8.37 | 14394.98 | 1719.64 | 1.00 | 1.08 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.86 | 1482.81 | 1719.64 | 1.00 | 1.33 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.83 | 0.115090 | 23715.78 | 206063.11 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.034930 | 10519.44 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.057545 | 10945.92 | 190215.15 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.057545 | 10945.92 | 190215.15 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 209234.68 | 0.163274 | 56933.72 | 348701.22 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 82582.18 | 94969.50 | 34.17 | 6.876 | 7.907 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00742 | 21.56 | 0.00629 | 1.200 | 0.00 |
CORE_BOTTOM | 88023.52 | 101227.05 | 40.55 | 7.328 | 8.428 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00735 | 21.56 | 0.00629 | 1.078 | 0.00 |
CORE_MID | 836409.27 | 961870.66 | 385.35 | 69.622 | 80.065 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00737 | 21.56 | 0.00629 | 10.778 | 0.00 |
CORE_TOP | 92558.17 | 106441.90 | 42.64 | 7.772 | 8.938 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00733 | 32.92 | 0.00631 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 15080.16 | 17342.19 | 55.33 | 1.266 | 1.456 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00723 | 33.40 | 0.00631 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 19774.52 | 22740.69 | 112.59 | 1.660 | 1.909 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00711 | 25.05 | 0.00629 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 25311.64 | 29108.39 | 92.87 | 2.125 | 2.444 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00714 | 33.13 | 0.00631 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 24625.01 | 28318.76 | 140.21 | 2.068 | 2.378 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00709 | 30.63 | 0.00630 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 144006.49 | 165607.46 | 528.40 | 12.092 | 13.906 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00721 | 33.40 | 0.00631 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 209394.86 | 240804.09 | 1192.25 | 17.582 | 20.219 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00710 | 25.96 | 0.00630 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 255186.40 | 293464.36 | 936.33 | 21.427 | 24.641 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00712 | 33.27 | 0.00631 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 230358.94 | 264912.78 | 1311.61 | 19.342 | 22.244 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00709 | 30.36 | 0.00630 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 17576.60 | 20213.09 | 64.49 | 1.476 | 1.697 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00717 | 33.24 | 0.00631 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 21063.30 | 24222.80 | 119.93 | 1.769 | 2.034 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00709 | 26.87 | 0.00630 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 28521.40 | 32799.61 | 104.65 | 2.395 | 2.754 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00711 | 33.40 | 0.00631 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 25018.69 | 28771.49 | 142.45 | 2.101 | 2.416 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00708 | 30.36 | 0.00630 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 9000.10 | 10350.12 | 285.89 | 0.756 | 0.869 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00706 | 26.28 | 0.00630 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 86687.19 | 99690.27 | 2753.67 | 7.279 | 8.371 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00707 | 26.28 | 0.00630 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8929.56 | 10268.99 | 283.65 | 0.750 | 0.862 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 27.00 | 27.00 | 0.00706 | 26.57 | 0.00630 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372023.17 | 427826.65 | 545.92 | 31.238 | 35.924 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00703 | 18.84 | 0.00628 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 22.10 | 0.00034 | -27.60 | 0.00034 | 1.200 | 0.00 |
CORE_BOTTOM | 8706.62 | 10883.27 | 4.36 | 0.713 | 1.078 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 1.078 | 0.00 |
CORE_MID | 309628.76 | 387035.95 | 155.05 | 25.387 | 31.734 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 10.778 | 0.00 |
CORE_TOP | 97276.96 | 121596.20 | 48.71 | 8.070 | 10.087 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 17241.34 | 21551.68 | 68.76 | 1.433 | 1.791 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 11705.84 | 14632.30 | 72.45 | 0.973 | 1.216 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 18971.09 | 23713.87 | 75.66 | 1.577 | 1.971 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 10123.10 | 12653.88 | 62.65 | 0.841 | 1.051 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 228170.79 | 285213.49 | 910.02 | 18.975 | 23.719 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -27.60 | 0.00034 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 151567.81 | 189459.77 | 938.04 | 12.606 | 15.757 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -27.60 | 0.00034 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 233044.28 | 291305.35 | 929.44 | 19.382 | 24.227 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -27.60 | 0.00034 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 150999.38 | 188749.23 | 934.52 | 12.559 | 15.698 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -27.60 | 0.00034 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 30264.66 | 37830.83 | 120.71 | 2.518 | 3.148 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 19951.29 | 24939.12 | 123.48 | 1.660 | 2.075 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 30774.57 | 38468.21 | 122.74 | 2.561 | 3.201 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 20163.51 | 25204.39 | 124.79 | 1.678 | 2.097 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.04 | 0.00113 | -27.60 | 0.00034 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.22 | 0.00113 | -27.60 | 0.00034 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 18.75 | 0.00113 | -27.60 | 0.00034 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 14:30:00 | 18.00 | 27.00 | 0.00700 | -27.60 | 0.00034 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 14.06 | 14.06 | 7.11 | 7.11 | 14.0606 | 7.1072 | 14.0606 | 0.5055 | 0.3000 |
VAV_MID WITH REHEAT | 130.55 | 130.55 | 111.14 | 111.14 | 130.5452 | 111.1361 | 130.5452 | 0.8513 | 0.3000 |
VAV_TOP WITH REHEAT | 16.37 | 16.37 | 20.61 | 20.61 | 16.3695 | 20.6090 | 20.6090 | 1.0000 | 0.3000 |
CAV_BAS | 7.91 | 7.91 | 1.20 | 1.20 | 7.9069 | 2.3721 | 7.9069 | 0.3000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 35.92 | 35.92 | 0.34 | 0.34 | 35.9237 | 17.9618 | 35.9237 | 0.5000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.87 | 0.87 | 0.02 | 0.02 | 0.8691 | 0.8691 | 0.8691 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 8.37 | 8.37 | 0.16 | 0.16 | 8.3709 | 8.3709 | 8.3709 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.86 | 0.86 | 0.02 | 0.02 | 0.8623 | 0.8623 | 0.8623 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 32905.703 | 32905.703 | 2.528261 | 0.00028787 | 697.433 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 32905.70 | 32905.70 | 2.528261 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 10883.27 | 0.00 | 33064.55 | 33064.55 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 663454.261 | 663454.261 | 31.733914 | 0.00580419 | 15529.976 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 663454.26 | 663454.26 | 31.733914 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 387035.95 | 0.00 | 666493.43 | 666493.43 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 209462.699 | 209462.699 | 10.087422 | 0.00183247 | 4893.732 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 209462.70 | 208231.62 | 10.087422 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 121596.20 | 0.00 | 210422.95 | 210422.95 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 37147.515 | 37147.515 | 1.790910 | 0.00032498 | 867.626 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 37147.51 | 36969.23 | 1.790910 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00789746 | 44.6599 | 21551.68 | 0.00 | 37317.83 | 37317.83 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 25222.838 | 25222.838 | 1.216137 | 0.00022066 | 589.094 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25222.84 | 25222.84 | 1.216137 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00789920 | 44.6696 | 14632.30 | 0.00 | 25338.48 | 25338.48 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 40879.803 | 40879.803 | 1.971175 | 0.00035763 | 954.754 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40879.80 | 40879.80 | 1.971175 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00790643 | 44.7100 | 23713.87 | 0.00 | 41067.24 | 41067.24 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 21807.276 | 21807.276 | 1.051139 | 0.00019078 | 509.364 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21807.28 | 21807.28 | 1.051139 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00788387 | 44.5841 | 12653.88 | 0.00 | 21907.26 | 21907.26 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 491724.022 | 491724.022 | 23.719320 | 0.00430182 | 11483.086 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 491724.02 | 489630.81 | 23.719320 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00781906 | 44.2237 | 285213.49 | 0.00 | 493978.66 | 493978.66 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 326648.871 | 326648.871 | 15.757297 | 0.00285767 | 7628.038 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 326648.87 | 326648.87 | 15.757297 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00781832 | 44.2197 | 189459.77 | 0.00 | 328146.62 | 328146.62 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 502240.106 | 502240.106 | 24.227309 | 0.00439382 | 11728.567 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 502240.11 | 502240.11 | 24.227309 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00782273 | 44.2442 | 291305.35 | 0.00 | 504542.97 | 504542.97 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 325423.972 | 325423.972 | 15.698243 | 0.00284695 | 7599.429 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 325423.97 | 325423.97 | 15.698243 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00781785 | 44.2170 | 188749.23 | 0.00 | 326916.11 | 326916.11 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 65237.590 | 65237.590 | 3.147897 | 0.00057073 | 1523.336 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 65237.59 | 64981.10 | 3.147897 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00782950 | 44.2826 | 37830.83 | 0.00 | 65536.73 | 65536.73 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 43006.944 | 43006.944 | 2.075258 | 0.00037624 | 1004.231 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 43006.94 | 42838.92 | 2.075258 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00782759 | 44.2720 | 24939.12 | 0.00 | 43204.15 | 43204.15 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 66337.737 | 66337.737 | 3.201032 | 0.00058035 | 1549.019 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 66337.74 | 66077.95 | 3.201032 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00783228 | 44.2981 | 38468.21 | 0.00 | 66641.92 | 66641.92 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 43465.020 | 43465.020 | 2.097396 | 0.00038025 | 1014.922 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 43465.02 | 43465.02 | 2.097396 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00782956 | 44.2830 | 25204.39 | 0.00 | 43664.32 | 43664.32 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 223960.042 | -999.000 | 14.060594 | 0.00799933 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 223960.04 | 219695.24 | 14.060594 | 25.36 | 14.35 | 0.00714415 | 10.86 | 8.58 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 14.4411 | 24.00 | 0.00728555 | 34.3686 | 145544.54 | 0.00 | 254142.27 | 249662.19 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 70344.260 | 70344.260 | 4.218178 | 0.00061540 | 1161.207 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:50:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 70344.26 | 70344.26 | 4.218178 | -2.87 | -2.87 | 0.00423834 | 12.89 | 10.44 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 48.1369 | 16.08 | 0.00771513 | 59.3795 | 10655.58 | 0.00 | 65835.71 | 65835.71 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2095275.805 | -999.000 | 130.545209 | 0.07483840 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 2095275.81 | 2055634.89 | 130.545209 | 25.46 | 14.38 | 0.00714400 | 10.85 | 8.58 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 15.5548 | 24.00 | 0.00729837 | 34.4283 | 1350632.72 | 0.00 | 2375763.53 | 2333420.01 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 763257.463 | 763257.463 | 39.163563 | 0.00667731 | 12411.544 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 763257.46 | 763257.46 | 39.163563 | -5.53 | -5.53 | 0.00385962 | 12.89 | 10.44 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 51.8492 | 18.39 | 0.00779980 | 51.8864 | 164114.07 | 0.00 | 692541.32 | 692541.32 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 321884.442 | -999.000 | 20.609005 | 0.01149697 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 321884.44 | 316699.92 | 20.609005 | 25.15 | 14.25 | 0.00712021 | 10.88 | 8.59 | 0.00700000 | 33.24 | 0.00630658 | 16.31 | 9.8525 | 24.00 | 0.00723566 | 34.1358 | 169208.99 | 0.00 | 366145.40 | 361104.68 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 64169.539 | 64169.539 | 6.182701 | 0.00056138 | 1098.839 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 64169.54 | 64169.54 | 6.182701 | 3.08 | 2.89 | 0.00524508 | 12.89 | 10.44 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 32.8416 | 16.88 | 0.00785416 | 57.4515 | 24585.16 | 0.00 | 64598.74 | 64598.74 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 126247.167 | -999.000 | 7.906873 | 0.00450926 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 126247.17 | 121950.82 | 7.906873 | 25.47 | 14.49 | 0.00726313 | 10.84 | 8.57 | 0.00700000 | 32.60 | 0.00630558 | 16.10 | 15.1786 | 24.00 | 0.00746028 | 35.1835 | 72793.67 | 0.00 | 146681.15 | 141501.71 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.474082 | 0.00087484 | 2621.308 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.474082 | -4.19 | -8.90 | 0.00034190 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 34.5460 | 22.21 | 0.00034190 | 1.8175 | 0.00 | 0.00 | 100050.95 | 100050.95 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 454842.350 | -999.000 | 35.923717 | 0.01624591 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 454842.35 | 453379.96 | 35.923717 | 27.06 | 14.84 | 0.00702611 | 14.93 | 10.28 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 0.9420 | 27.00 | 0.00703296 | 27.7753 | 371596.99 | 0.00 | 531304.92 | 531304.92 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 100000.000 | 100000.000 | 3.474082 | 0.00087484 | 2621.308 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.474082 | -0.26 | -0.26 | 0.00693728 | 29.11 | 16.32 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 9.7405 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | 100050.95 | 100050.95 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER BOT | 14386.530 | 11518.719 | 0.869090 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 7193.27 | 7149.90 | 0.579393 | 26.99 | 14.83 | 0.00704893 | 14.28 | 10.02 | 0.00700000 | 26.28 | 0.00629588 | 13.94 | 2.6981 | 27.00 | 0.00706272 | 27.8899 | 9000.10 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER BOT | 27229.647 | 27229.647 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 27229.65 | 27229.65 | 0.869090 | -0.50 | -5.18 | 0.00111985 | 29.11 | 16.32 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 1.7987 | 24.73 | 0.00113410 | 5.1700 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER MID | 138568.660 | 110946.383 | 8.370930 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 69284.33 | 68851.37 | 5.580620 | 26.99 | 14.83 | 0.00705072 | 14.28 | 10.02 | 0.00700000 | 26.28 | 0.00629588 | 13.94 | 2.8012 | 27.00 | 0.00706509 | 27.8992 | 86687.19 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER MID | 262439.589 | 262439.589 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 262439.59 | 262439.59 | 8.370933 | -0.52 | -5.20 | 0.00111933 | 29.11 | 16.32 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 1.8675 | 23.42 | 0.00113413 | 5.5933 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER TOP | 14273.760 | 11428.429 | 0.862280 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 7136.88 | 7093.59 | 0.574853 | 26.99 | 14.83 | 0.00704924 | 14.28 | 10.02 | 0.00700000 | 26.57 | 0.00629632 | 14.04 | 2.7194 | 27.00 | 0.00706314 | 27.8915 | 8929.56 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER TOP | 27019.799 | 27019.799 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 27019.80 | 27019.80 | 0.862278 | -0.50 | -5.19 | 0.00111868 | 29.11 | 16.32 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 1.8129 | 21.02 | 0.00113302 | 6.4692 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 32905.703 | 32905.703 | 2.528261 | 0.00028787 | 697.433 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 34.92662973 | 54.44 | 82.22 | 27.78 | 4073091.01 | 0.8079 | 0.824139 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 32905.70 | 32905.70 | 1.0000 | 2.66261248 | 2.528261 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.28784407 | 60.00 | 32.22 | 27.78 | 0.000 | 32905.70 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.77 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 10883.27 | 0.00 | 33064.55 | 33064.55 | 2.66261248 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 24.98 | 16.31 | 0.00800000 | 45477.9 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 663454.261 | 663454.261 | 31.733914 | 0.00580419 | 15529.976 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 34.92662973 | 54.44 | 82.22 | 27.78 | 4073091.01 | 16.2887 | 16.616534 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 663454.26 | 663454.26 | 1.0000 | 33.42025016 | 31.733914 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 5.80359521 | 60.00 | 32.22 | 27.78 | 0.000 | 663454.26 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 387035.95 | 0.00 | 666493.43 | 666493.43 | 33.42025016 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.36 | 18.81 | 0.00800000 | 53002.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 209462.699 | 209462.699 | 10.087422 | 0.00183247 | 4893.732 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 34.92662973 | 54.44 | 82.22 | 27.78 | 4073091.01 | 5.1426 | 5.246095 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 209462.70 | 208231.62 | 1.0000 | 10.62346596 | 10.087422 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 1.83228414 | 60.00 | 32.22 | 27.78 | 0.000 | 209462.70 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 121596.20 | 0.00 | 210422.95 | 210422.95 | 10.62346596 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52867.2 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 37147.515 | 37147.515 | 1.790910 | 0.00032498 | 867.626 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 34.92662973 | 54.44 | 82.22 | 27.78 | 4073091.01 | 0.9120 | 0.930378 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 37147.51 | 36969.23 | 1.0000 | 1.88607919 | 1.790910 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.32494951 | 60.00 | 32.22 | 27.78 | 0.000 | 37147.51 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00789746 | 21.00 | 0.00789746 | 44.6599 | 21551.68 | 0.00 | 37317.83 | 37317.83 | 1.88607919 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52845.8 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25222.838 | 25222.838 | 1.216137 | 0.00022066 | 589.094 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 34.92662973 | 54.44 | 82.22 | 27.78 | 4073091.01 | 0.6193 | 0.631718 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25222.84 | 25222.84 | 1.0000 | 1.28076241 | 1.216137 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.22063788 | 60.00 | 32.22 | 27.78 | 0.000 | 25222.84 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00789920 | 21.00 | 0.00789920 | 44.6696 | 14632.30 | 0.00 | 25338.48 | 25338.48 | 1.28076241 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52843.7 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 40879.803 | 40879.803 | 1.971175 | 0.00035763 | 954.754 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 34.92662973 | 54.44 | 82.22 | 27.78 | 4073091.01 | 1.0037 | 1.023854 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 40879.80 | 40879.80 | 1.0000 | 2.07592250 | 1.971175 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.35759787 | 60.00 | 32.22 | 27.78 | 0.000 | 40879.80 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00790643 | 21.00 | 0.00790643 | 44.7100 | 23713.87 | 0.00 | 41067.24 | 41067.24 | 2.07592250 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52842.5 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21807.276 | 21807.276 | 1.051139 | 0.00019078 | 509.364 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 34.92662973 | 54.44 | 82.22 | 27.78 | 4073091.01 | 0.5354 | 0.546174 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21807.28 | 21807.28 | 1.0000 | 1.10699639 | 1.051139 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.19076010 | 60.00 | 32.22 | 27.78 | 0.000 | 21807.28 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00788387 | 21.00 | 0.00788387 | 44.5841 | 12653.88 | 0.00 | 21907.26 | 21907.26 | 1.10699639 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.76 | 0.00800000 | 52849.6 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 491724.022 | 491724.022 | 23.719320 | 0.00430182 | 11483.086 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 34.92662973 | 54.44 | 82.22 | 27.78 | 4073091.01 | 12.0725 | 12.315467 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 491724.02 | 489630.81 | 1.0000 | 24.97976153 | 23.719320 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 4.30137742 | 60.00 | 32.22 | 27.78 | 0.000 | 491724.02 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.94 | 0.00781906 | 21.00 | 0.00781906 | 44.2237 | 285213.49 | 0.00 | 493978.66 | 493978.66 | 24.97976153 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52835.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 326648.871 | 326648.871 | 15.757297 | 0.00285767 | 7628.038 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 34.92662973 | 54.44 | 82.22 | 27.78 | 4073091.01 | 8.0197 | 8.181079 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 326648.87 | 326648.87 | 1.0000 | 16.59463789 | 15.757297 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 2.85737531 | 60.00 | 32.22 | 27.78 | 0.000 | 326648.87 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.94 | 0.00781832 | 21.00 | 0.00781832 | 44.2197 | 189459.77 | 0.00 | 328146.62 | 328146.62 | 16.59463789 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52834.1 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 502240.106 | 502240.106 | 24.227309 | 0.00439382 | 11728.567 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 34.92662973 | 54.44 | 82.22 | 27.78 | 4073091.01 | 12.3307 | 12.578847 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 502240.11 | 502240.11 | 1.0000 | 25.51474543 | 24.227309 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 4.39336733 | 60.00 | 32.22 | 27.78 | 0.000 | 502240.11 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.94 | 0.00782273 | 21.00 | 0.00782273 | 44.2442 | 291305.35 | 0.00 | 504542.97 | 504542.97 | 25.51474543 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52834.4 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 325423.972 | 325423.972 | 15.698243 | 0.00284695 | 7599.429 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 34.92662973 | 54.44 | 82.22 | 27.78 | 4073091.01 | 7.9896 | 8.150401 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 325423.97 | 325423.97 | 1.0000 | 16.53244547 | 15.698243 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 2.84666045 | 60.00 | 32.22 | 27.78 | 0.000 | 325423.97 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.94 | 0.00781785 | 21.00 | 0.00781785 | 44.2170 | 188749.23 | 0.00 | 326916.11 | 326916.11 | 16.53244547 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52834.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 65237.590 | 65237.590 | 3.147897 | 0.00057073 | 1523.336 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 34.92662973 | 54.44 | 82.22 | 27.78 | 4073091.01 | 1.6017 | 1.633907 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 65237.59 | 64981.10 | 1.0000 | 3.31517592 | 3.147897 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.57066867 | 60.00 | 32.22 | 27.78 | 0.000 | 65237.59 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.94 | 0.00782950 | 21.00 | 0.00782950 | 44.2826 | 37830.83 | 0.00 | 65536.73 | 65536.73 | 3.31517592 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52828.5 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 43006.944 | 43006.944 | 2.075258 | 0.00037624 | 1004.231 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 34.92662973 | 54.44 | 82.22 | 27.78 | 4073091.01 | 1.0559 | 1.077130 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 43006.94 | 42838.92 | 1.0000 | 2.18553673 | 2.075258 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.37620512 | 60.00 | 32.22 | 27.78 | 0.000 | 43006.94 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.94 | 0.00782759 | 21.00 | 0.00782759 | 44.2720 | 24939.12 | 0.00 | 43204.15 | 43204.15 | 2.18553673 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52828.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 66337.737 | 66337.737 | 3.201032 | 0.00058035 | 1549.019 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 34.92662973 | 54.44 | 82.22 | 27.78 | 4073091.01 | 1.6287 | 1.661461 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 66337.74 | 66077.95 | 1.0000 | 3.37113462 | 3.201032 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.58029226 | 60.00 | 32.22 | 27.78 | 0.000 | 66337.74 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.94 | 0.00783228 | 21.00 | 0.00783228 | 44.2981 | 38468.21 | 0.00 | 66641.92 | 66641.92 | 3.37113462 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52828.2 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 43465.020 | 43465.020 | 2.097396 | 0.00038025 | 1014.922 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 34.92662973 | 54.44 | 82.22 | 27.78 | 4073091.01 | 1.0671 | 1.088602 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 43465.02 | 43465.02 | 1.0000 | 2.20885154 | 2.097396 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.38021216 | 60.00 | 32.22 | 27.78 | 0.000 | 43465.02 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.94 | 0.00782956 | 21.00 | 0.00782956 | 44.2830 | 25204.39 | 0.00 | 43664.32 | 43664.32 | 2.20885154 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52827.7 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 223960.042 | -999.000 | 14.060594 | 0.00799933 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.1206 | 1004.8586 | 1.0531 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 14.060594 | 14.80777193 | 4197.9300 | 999.8980 | 115.07812802 | 13.34 | 6.67 | 6.67 | 3222209.81 | 6.9505 | 6.950511 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 223960.04 | 219695.24 | 1.0000 | 14.80777193 | 14.060594 | 25.36 | 14.35 | 0.00714415 | 43683.6 | 10.86 | 8.58 | 0.00700000 | 28559.1 | 7.99851777 | 6.67 | 13.34 | 6.67 | 30607.801 | 193352.24 | 33.40 | 0.00630683 | 16.37 | 2.03050000 | 14.4411 | 24.00 | 0.00728555 | 24.00 | 0.00728555 | 34.3686 | 145544.54 | 0.00 | 254142.27 | 249662.19 | 14.80777193 | 25.36 | 15.69 | 0.00714415 | 43683.6 | 8.80 | 8.79 | 0.00702396 | 26520.8 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 70344.260 | 70344.260 | 4.218178 | 0.00061540 | 1161.207 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 14.060594 | 14.80777193 | 4197.9300 | 999.8980 | 34.92662973 | 54.44 | 82.22 | 27.78 | 4073091.01 | 1.7270 | 1.761806 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:50:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 70344.26 | 70344.26 | 1.0000 | 4.44233158 | 4.218178 | -2.87 | -2.87 | 0.00423834 | 7693.8 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 0.61533950 | 60.00 | 32.22 | 27.78 | 0.000 | 70344.26 | -27.60 | 0.00034190 | -27.60 | 2.03050000 | 48.1369 | 20.08 | 0.00785483 | 16.08 | 0.00771513 | 59.3795 | 10655.58 | 0.00 | 65835.71 | 65835.71 | 4.44233158 | 2.80 | 2.28 | 0.00423834 | 13435.4 | 17.43 | 9.62 | 0.00423834 | 28255.5 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2095275.805 | -999.000 | 130.545209 | 0.07483840 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.1203 | 1004.8586 | 1.0531 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 130.545209 | 137.48236575 | 4197.9300 | 999.8980 | 115.07812802 | 13.34 | 6.67 | 6.67 | 3222209.81 | 65.0261 | 65.026051 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 2095275.81 | 2055634.89 | 1.0000 | 137.48236575 | 130.545209 | 25.46 | 14.38 | 0.00714400 | 43790.7 | 10.85 | 8.58 | 0.00700000 | 28550.3 | 74.83076270 | 6.67 | 13.34 | 6.67 | 285385.294 | 1809890.51 | 33.40 | 0.00630683 | 16.37 | 20.30600000 | 15.5548 | 24.00 | 0.00729837 | 24.00 | 0.00729837 | 34.4283 | 1350632.72 | 0.00 | 2375763.53 | 2333420.01 | 137.48236575 | 25.46 | 15.73 | 0.00714400 | 43790.7 | 8.79 | 8.79 | 0.00702165 | 26510.2 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 763257.463 | 763257.463 | 39.163563 | 0.00667731 | 12411.544 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 130.545209 | 137.48236575 | 4197.9300 | 999.8980 | 34.92662973 | 54.44 | 82.22 | 27.78 | 4073091.01 | 18.7390 | 19.116153 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 763257.46 | 763257.46 | 1.0000 | 41.24470973 | 39.163563 | -5.53 | -5.53 | 0.00385962 | 4059.1 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 6.67662809 | 60.00 | 32.22 | 27.78 | 0.000 | 763257.46 | -27.60 | 0.00034190 | -27.60 | 20.30600000 | 51.8492 | 18.24 | 0.00764754 | 18.39 | 0.00779980 | 51.8864 | 164114.07 | 0.00 | 692541.32 | 692541.32 | 41.24470973 | 2.80 | 1.75 | 0.00385962 | 12486.3 | 19.39 | 10.08 | 0.00385962 | 29277.4 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 321884.442 | -999.000 | 20.609005 | 0.01149697 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0761 | 1004.8586 | 1.0531 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 20.609005 | 21.70416476 | 4197.9300 | 999.8980 | 115.07812802 | 13.34 | 6.67 | 6.67 | 3222209.81 | 9.9896 | 9.989556 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 321884.44 | 316699.92 | 1.0000 | 21.70416476 | 20.609005 | 25.15 | 14.25 | 0.00712021 | 43409.1 | 10.88 | 8.59 | 0.00700000 | 28578.5 | 11.49579364 | 6.67 | 13.34 | 6.67 | 44439.475 | 277444.97 | 33.24 | 0.00630658 | 16.31 | 2.03050000 | 9.8525 | 24.00 | 0.00723566 | 24.00 | 0.00723566 | 34.1358 | 169208.99 | 0.00 | 366145.40 | 361104.68 | 21.70416476 | 25.15 | 15.59 | 0.00712021 | 43409.1 | 8.81 | 8.80 | 0.00702795 | 26539.2 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 64169.539 | 64169.539 | 6.182701 | 0.00056138 | 1098.839 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 20.609005 | 21.70416476 | 4197.9300 | 999.8980 | 34.92662973 | 54.44 | 82.22 | 27.78 | 4073091.01 | 1.5755 | 1.607157 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 64169.54 | 64169.54 | 1.0000 | 6.51124943 | 6.182701 | 3.08 | 2.89 | 0.00524508 | 16243.9 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 0.56132585 | 60.00 | 32.22 | 27.78 | 0.000 | 64169.54 | -27.60 | 0.00034190 | -27.60 | 2.03050000 | 32.8416 | 18.09 | 0.00764282 | 16.88 | 0.00785416 | 57.4515 | 24585.16 | 0.00 | 64598.74 | 64598.74 | 6.51124943 | 2.80 | 2.80 | 0.00524508 | 15958.5 | 12.58 | 8.53 | 0.00524508 | 25879.6 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 126247.167 | -999.000 | 7.906873 | 0.00450926 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3418 | 1004.8586 | 1.0531 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 7.906873 | 8.32704350 | 4197.9300 | 999.8980 | 115.07812802 | 13.34 | 6.67 | 6.67 | 3222209.81 | 3.9180 | 3.918031 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 126247.17 | 121950.82 | 1.0000 | 8.32704350 | 7.906873 | 25.47 | 14.49 | 0.00726313 | 44098.9 | 10.84 | 8.57 | 0.00700000 | 28539.7 | 4.50879630 | 6.67 | 13.34 | 6.67 | 17377.576 | 108869.59 | 32.60 | 0.00630558 | 16.10 | 1.20015641 | 15.1786 | 24.00 | 0.00746028 | 24.00 | 0.00746028 | 35.1835 | 72793.67 | 0.00 | 146681.15 | 141501.71 | 8.32704350 | 25.47 | 15.84 | 0.00726313 | 44098.9 | 8.78 | 8.77 | 0.00701604 | 26483.9 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.474082 | 0.00087484 | 2621.308 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 7.906873 | 8.32704350 | 4197.9300 | 999.8980 | 34.92662973 | 54.44 | 82.22 | 27.78 | 4073091.01 | 2.4551 | 2.504548 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.474082 | -4.19 | -8.90 | 0.00034190 | -3357.2 | 32.11 | 17.27 | 0.00800000 | 52750.5 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -27.60 | 0.00034190 | -27.60 | 1.20015641 | 34.5460 | 0.00 | 0.00034190 | 22.21 | 0.00034190 | 1.8175 | 0.00 | 0.00 | 100050.95 | 100050.95 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.01 | 14.59 | 0.00000000 | 40233.3 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 454842.350 | -999.000 | 35.923717 | 0.01624591 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9012 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 35.923717 | 37.83269940 | 4197.9300 | 999.8980 | 115.07812802 | 13.34 | 6.67 | 6.67 | 3222209.81 | 14.1159 | 14.115851 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 454842.35 | 453379.96 | 1.0000 | 37.83269940 | 35.923717 | 27.06 | 14.84 | 0.00702611 | 45114.4 | 14.93 | 10.28 | 0.00700000 | 32698.6 | 16.24425761 | 6.67 | 13.34 | 6.67 | 37098.234 | 417744.12 | 33.40 | 0.00630683 | 16.37 | 0.33839277 | 0.9420 | 27.00 | 0.00703296 | 27.00 | 0.00703296 | 27.7753 | 371596.99 | 0.00 | 531304.92 | 531304.92 | 37.83269940 | 27.06 | 16.20 | 0.00702611 | 45114.4 | 13.26 | 10.78 | 0.00702611 | 31070.9 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.474082 | 0.00087484 | 2621.308 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 35.923717 | 37.83269940 | 4197.9300 | 999.8980 | 34.92662973 | 54.44 | 82.22 | 27.78 | 4073091.01 | 2.4551 | 2.504548 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.474082 | -0.26 | -0.26 | 0.00693728 | 17085.1 | 29.11 | 16.32 | 0.00800000 | 49691.3 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -27.60 | 0.00034190 | -27.60 | 0.33839277 | 9.7405 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | 100050.95 | 100050.95 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.01 | 14.59 | 0.00000000 | 40233.3 | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 14386.530 | 11518.719 | 0.869090 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9436 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.869090 | 0.91527341 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 7193.27 | 7149.90 | 1.0000 | 0.61018223 | 0.579393 | 26.99 | 14.83 | 0.00704893 | 45099.0 | 14.28 | 10.02 | 0.00700000 | 32046.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7193.27 | 26.28 | 0.00629588 | 13.94 | 0.01563234 | 2.6981 | 27.00 | 0.00706272 | 27.00 | 0.00706272 | 27.8899 | 9000.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27229.647 | 27229.647 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.869090 | 0.91527341 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 27229.65 | 27229.65 | 1.0000 | 0.91527341 | 0.869090 | -0.50 | -5.18 | 0.00111985 | 2300.8 | 29.11 | 16.32 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27229.65 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 1.7987 | 0.00 | 0.00113410 | 24.73 | 0.00113410 | 5.1700 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 138568.660 | 110946.383 | 8.370930 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9469 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 8.370933 | 8.81576321 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 69284.33 | 68851.37 | 1.0000 | 5.87717348 | 5.580620 | 26.99 | 14.83 | 0.00705072 | 45103.1 | 14.28 | 10.02 | 0.00700000 | 32046.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 69284.33 | 26.28 | 0.00629588 | 13.94 | 0.15632344 | 2.8012 | 27.00 | 0.00706509 | 27.00 | 0.00706509 | 27.8992 | 86687.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 262439.589 | 262439.589 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 8.370933 | 8.81576321 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 262439.59 | 262439.59 | 1.0000 | 8.81576321 | 8.370933 | -0.52 | -5.20 | 0.00111933 | 2280.4 | 29.11 | 16.32 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 262439.59 | -27.60 | 0.00034190 | -27.60 | 0.15632344 | 1.8675 | 0.00 | 0.00113413 | 23.42 | 0.00113413 | 5.5933 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 14273.760 | 11428.429 | 0.862280 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9442 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.862278 | 0.90809948 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 7136.88 | 7093.59 | 1.0000 | 0.60540097 | 0.574853 | 26.99 | 14.83 | 0.00704924 | 45105.1 | 14.28 | 10.02 | 0.00700000 | 32046.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7136.88 | 26.57 | 0.00629632 | 14.04 | 0.01563234 | 2.7194 | 27.00 | 0.00706314 | 27.00 | 0.00706314 | 27.8915 | 8929.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27019.799 | 27019.799 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.862278 | 0.90809948 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 27019.80 | 27019.80 | 1.0000 | 0.90809948 | 0.862278 | -0.50 | -5.19 | 0.00111868 | 2293.9 | 29.11 | 16.32 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27019.80 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 1.8129 | 0.00 | 0.00113302 | 21.02 | 0.00113302 | 6.4692 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 14.06 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 130.55 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 20.61 | - | |||
CAV_BAS_OA_CONTROLLER | FixedDryBulb | 1.20 | 7.91 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 35.92 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1214.67 | 2881.33 | 20.67 |
CORE_BOTTOM | 1252.67 | 2341.33 | 46.33 |
CORE_MID | 1016.67 | 3729.17 | 304.17 |
CORE_TOP | 2138.33 | 4743.50 | 1574.67 |
PERIMETER_BOT_ZN_3 | 2144.83 | 4371.50 | 1230.50 |
PERIMETER_BOT_ZN_2 | 2422.83 | 4264.50 | 1251.67 |
PERIMETER_BOT_ZN_1 | 2617.50 | 3782.67 | 1163.17 |
PERIMETER_BOT_ZN_4 | 2221.67 | 4013.17 | 807.50 |
PERIMETER_MID_ZN_3 | 2854.33 | 5122.17 | 2376.17 |
PERIMETER_MID_ZN_2 | 2630.67 | 3919.00 | 1840.00 |
PERIMETER_MID_ZN_1 | 2913.67 | 4008.17 | 1567.00 |
PERIMETER_MID_ZN_4 | 2828.33 | 4774.67 | 1993.00 |
PERIMETER_TOP_ZN_3 | 3372.17 | 5348.83 | 3012.83 |
PERIMETER_TOP_ZN_2 | 3571.00 | 4637.50 | 2586.67 |
PERIMETER_TOP_ZN_1 | 3304.67 | 4404.67 | 2189.33 |
PERIMETER_TOP_ZN_4 | 3333.33 | 4907.33 | 2565.83 |
DATACENTER_BOT_ZN_6 | 5771.50 | 754.50 | 754.50 |
DATACENTER_MID_ZN_6 | 5167.50 | 395.83 | 311.17 |
DATACENTER_TOP_ZN_6 | 4312.33 | 870.67 | 453.50 |
DATACENTER_BASEMENT_ZN_6 | 5832.83 | 2667.83 | 2664.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5933.00 | 5097.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 8.17 | 0.00 | 0.17 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 23.00 | 0.00 | 0.83 | 0.00 |
PERIMETER_BOT_ZN_3 | 26.33 | 0.00 | 3.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 30.17 | 14.33 | 3.17 | 14.33 |
PERIMETER_BOT_ZN_1 | 35.33 | 19.67 | 3.67 | 19.33 |
PERIMETER_BOT_ZN_4 | 9.50 | 30.50 | 0.00 | 16.00 |
PERIMETER_MID_ZN_3 | 132.00 | 0.00 | 25.33 | 0.00 |
PERIMETER_MID_ZN_2 | 197.83 | 14.50 | 19.17 | 14.50 |
PERIMETER_MID_ZN_1 | 97.83 | 19.50 | 10.67 | 18.67 |
PERIMETER_MID_ZN_4 | 101.00 | 19.17 | 15.50 | 9.33 |
PERIMETER_TOP_ZN_3 | 274.67 | 0.00 | 59.50 | 0.00 |
PERIMETER_TOP_ZN_2 | 261.00 | 12.50 | 47.33 | 12.50 |
PERIMETER_TOP_ZN_1 | 214.67 | 9.83 | 30.67 | 9.33 |
PERIMETER_TOP_ZN_4 | 206.67 | 18.67 | 38.17 | 8.83 |
DATACENTER_BOT_ZN_6 | 0.00 | 131.67 | 0.00 | 70.33 |
DATACENTER_MID_ZN_6 | 0.00 | 57.83 | 0.00 | 38.67 |
DATACENTER_TOP_ZN_6 | 0.00 | 20.67 | 0.00 | 15.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 28.67 | 0.00 | 25.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 453.00 | 278.00 | 79.50 | 180.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.943 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.956 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.764 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.744 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 1.194 | 0.059 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 2.121 | 0.061 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 1.958 | 0.059 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 2.525 | 0.061 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 1.425 | 0.137 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 2.002 | 0.150 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 1.913 | 0.138 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 2.225 | 0.142 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 1.704 | 0.170 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 1.963 | 0.176 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 2.013 | 0.170 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 2.180 | 0.176 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.425 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.425 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.425 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 20.938 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 60.99 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.86 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.79 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.20 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1010.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 37870603.62 | 0.00 | 37870603.62 | 0.00 | 37870603.62 | 37848132.68 | 4285.98 | 2756.18 | 1717.84 | 115.49 |
CORE_BOTTOM | 39844548.75 | 0.00 | 39844548.75 | 0.00 | 39844548.75 | 33990283.35 | 5342.06 | 40.65 | 3377.29 | 313.69 |
CORE_MID | 0.32E+09 | 0.00 | 0.32E+09 | 0.00 | 0.32E+09 | 0.34E+09 | 5976.07 | 54.29 | 2729.64 | 467.48 |
CORE_TOP | 30668322.41 | 0.00 | 30668322.41 | 0.00 | 30668322.41 | 33990283.35 | 6076.58 | 36.79 | 2646.63 | 419.70 |
PERIMETER_BOT_ZN_3 | 6341188.92 | 0.00 | 6341188.92 | 591585.02 | 6932773.93 | 4267819.30 | 3801.47 | 23.15 | 4935.39 | 313.69 |
PERIMETER_BOT_ZN_2 | 7235788.03 | 0.00 | 7235788.03 | 394389.74 | 7630177.77 | 2750345.05 | 3716.06 | 4.42 | 5039.52 | 313.69 |
PERIMETER_BOT_ZN_1 | 10307098.36 | 0.00 | 10307098.36 | 591585.02 | 10898683.38 | 4267912.63 | 3745.54 | 3.25 | 5011.21 | 313.69 |
PERIMETER_BOT_ZN_4 | 8640185.71 | 0.00 | 8640185.71 | 394389.74 | 9034575.45 | 2750345.05 | 3671.67 | 5.11 | 5083.22 | 313.69 |
PERIMETER_MID_ZN_3 | 75842868.53 | 0.00 | 75842868.53 | 1387434.57 | 77230303.10 | 42678193.03 | 3795.71 | 14.72 | 4949.57 | 467.48 |
PERIMETER_MID_ZN_2 | 65444627.35 | 0.00 | 65444627.35 | 924955.75 | 66369583.10 | 27503450.52 | 4146.62 | 8.03 | 4605.35 | 944.29 |
PERIMETER_MID_ZN_1 | 0.10E+09 | 0.00 | 0.10E+09 | 1387434.57 | 0.10E+09 | 42679126.28 | 3744.48 | 8.25 | 5007.27 | 467.48 |
PERIMETER_MID_ZN_4 | 76012114.28 | 0.00 | 76012114.28 | 924955.75 | 76937070.02 | 27503450.52 | 3619.83 | 9.26 | 5130.91 | 467.48 |
PERIMETER_TOP_ZN_3 | 8885868.46 | 0.00 | 8885868.46 | 1722650.34 | 10608518.81 | 4267819.30 | 3971.11 | 11.75 | 4777.13 | 419.70 |
PERIMETER_TOP_ZN_2 | 6554155.77 | 0.00 | 6554155.77 | 1148432.78 | 7702588.55 | 2750345.05 | 3953.57 | 5.59 | 4800.83 | 419.68 |
PERIMETER_TOP_ZN_1 | 10418908.41 | 0.00 | 10418908.41 | 1722650.34 | 12141558.76 | 4267912.63 | 3955.91 | 5.87 | 4798.22 | 419.70 |
PERIMETER_TOP_ZN_4 | 7299254.98 | 0.00 | 7299254.98 | 1148432.78 | 8447687.76 | 2750345.05 | 3916.56 | 4.44 | 4839.00 | 419.68 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.34E+09 | 0.00 | 0.34E+09 | 0.00 | 0.34E+09 | 10671554.30 | 839.53 | 1044.72 | 6875.74 | 2342.64 |
Total Facility | 0.69E+10 | 0.00 | 0.69E+10 | 53961922.12 | 0.70E+10 | 0.50E+10 | 6640.51 | 4416.03 | 8073.76 | 2962.82 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.7477 | 0.0000 | 1.7477 | 0.0000 | 1.7477 | 1.2002 | 1499.97 | 2755.51 | 1687.52 |
CORE_BOTTOM | 1.7885 | 0.0000 | 1.7885 | 0.0000 | 1.7885 | 1.0778 | 2675.18 | 39.64 | 3228.18 |
CORE_MID | 14.3113 | 0.0000 | 14.3113 | 0.0000 | 14.3113 | 10.7782 | 3234.96 | 52.46 | 2655.58 |
CORE_TOP | 1.3972 | 0.0000 | 1.3972 | 0.0000 | 1.3972 | 1.0778 | 3304.11 | 36.61 | 2602.28 |
PERIMETER_BOT_ZN_3 | 0.2816 | 0.0000 | 0.2816 | 0.0139 | 0.2955 | 0.1353 | 1191.97 | 20.94 | 4730.10 |
PERIMETER_BOT_ZN_2 | 0.3225 | 0.0000 | 0.3225 | 0.0092 | 0.3317 | 0.0872 | 1137.87 | 2.40 | 4802.73 |
PERIMETER_BOT_ZN_1 | 0.4616 | 0.0000 | 0.4616 | 0.0139 | 0.4755 | 0.1353 | 1153.78 | 2.23 | 4786.99 |
PERIMETER_BOT_ZN_4 | 0.3839 | 0.0000 | 0.3839 | 0.0092 | 0.3931 | 0.0872 | 1127.99 | 1.27 | 4813.74 |
PERIMETER_MID_ZN_3 | 3.3734 | 0.0000 | 3.3734 | 0.0325 | 3.4059 | 1.3533 | 1230.19 | 9.82 | 4702.99 |
PERIMETER_MID_ZN_2 | 3.0492 | 0.0000 | 3.0492 | 0.0230 | 3.0722 | 0.8721 | 1159.70 | 2.48 | 3871.83 |
PERIMETER_MID_ZN_1 | 4.5115 | 0.0000 | 4.5115 | 0.0325 | 4.5440 | 1.3533 | 1185.12 | 4.31 | 4753.56 |
PERIMETER_MID_ZN_4 | 3.3914 | 0.0000 | 3.3914 | 0.0217 | 3.4130 | 0.8721 | 1142.31 | 3.77 | 4796.93 |
PERIMETER_TOP_ZN_3 | 0.4039 | 0.0000 | 0.4039 | 0.0404 | 0.4443 | 0.1353 | 1274.02 | 8.32 | 4660.66 |
PERIMETER_TOP_ZN_2 | 0.2988 | 0.0000 | 0.2988 | 0.0269 | 0.3257 | 0.0872 | 1260.00 | 2.64 | 4680.35 |
PERIMETER_TOP_ZN_1 | 0.4754 | 0.0000 | 0.4754 | 0.0404 | 0.5158 | 0.1353 | 1260.90 | 2.70 | 4679.40 |
PERIMETER_TOP_ZN_4 | 0.3323 | 0.0000 | 0.3323 | 0.0269 | 0.3592 | 0.0872 | 1241.47 | 2.26 | 4699.27 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 10.8700 | 0.0000 | 10.8700 | 0.0000 | 10.8700 | 0.3384 | 336.65 | 1044.12 | 4562.23 |
Total Facility | 306.2956 | 0.0000 | 306.2956 | 1.2778 | 307.5734 | 158.4706 | 3823.51 | 4374.96 | 5681.86 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 80264507.99 | 0.00 | 80264507.99 | 48026705.38 | 3786.50 | 4.29 | 4969.21 | 313.69 |
VAV_MID WITH REHEAT | 0.71E+09 | 0.00 | 0.71E+09 | 0.48E+09 | 3891.20 | 4.44 | 4864.36 | 467.48 |
VAV_TOP WITH REHEAT | 70790209.84 | 0.00 | 70790209.84 | 48026705.38 | 4080.27 | 6.39 | 4673.34 | 419.60 |
CAV_BAS | 41850269.20 | 0.00 | 41850269.20 | 37848132.68 | 4273.32 | 0.87 | 4485.81 | 115.49 |
AIRLOOP DATACENTER BASEMENT | 0.38E+09 | 0.00 | 0.38E+09 | 10671554.30 | 835.29 | 0.77 | 7923.94 | 2342.58 |
AIRLOOP DATACENTER BOT | 270949.60 | 0.00 | 270949.60 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 2709495.95 | 0.00 | 2709495.95 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 270949.60 | 0.00 | 270949.60 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.5914 | 0.0000 | 3.5914 | 1.5229 | 1170.45 | 1.39 | 4771.16 |
VAV_MID WITH REHEAT | 31.6105 | 0.0000 | 31.6105 | 15.2292 | 1238.72 | 2.36 | 4701.92 |
VAV_TOP WITH REHEAT | 3.2248 | 0.0000 | 3.2248 | 1.5229 | 1336.89 | 3.80 | 4602.31 |
CAV_BAS | 1.9313 | 0.0000 | 1.9313 | 1.2002 | 1491.58 | 0.26 | 4451.15 |
AIRLOOP DATACENTER BASEMENT | 12.0560 | 0.0000 | 12.0560 | 0.3384 | 334.92 | 0.38 | 5607.70 |
AIRLOOP DATACENTER BOT | 0.0127 | 0.0000 | 0.0127 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1266 | 0.0000 | 0.1266 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0127 | 0.0000 | 0.0127 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 26.46 | 4058.97 | 0.00 | 0.00 | 0.00 | 1060.59 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 85.44 | 4187.49 | 0.00 | 0.00 | 0.00 | 1051.77 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 19.30 | 3788.38 | 0.00 | 0.00 | 0.00 | 1453.64 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 2770.49 | 1869.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 1043.79 | 6920.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.1011 | 5.1481 | 0.0000 | 0.0000 | 0.0000 | 1.8901 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 22.3819 | 44.4642 | 0.0000 | 0.0000 | 0.0000 | 19.5761 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.1683 | 4.8636 | 0.0000 | 0.0000 | 0.0000 | 1.8862 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.3313 | 4.4438 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3756 | 15.5651 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1734 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1343 |
Defaulted Fields | 1287 |
Fields with Defaults | 3878 |
Autosized Fields | 320 |
Autosizable Fields | 465 |
Autocalculated Fields | 223 |
Autocalculatable Fields | 468 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 31769.99 | 297700.92 | 10-SEP-18:20 | 2379332.99 | 07-AUG-15:20 |
Electricity:Building | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 758.19 | 15076.70 | 01-JAN-00:10 | 42602.33 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 589.38 | 5907.35 | 01-JAN-00:10 | 43380.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5893.79 | 59073.32 | 01-JAN-00:10 | 433806.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 589.38 | 5907.33 | 01-JAN-00:10 | 43380.63 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 740.04 | 7417.49 | 01-JAN-00:10 | 54469.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 476.91 | 4780.12 | 01-JAN-00:10 | 35102.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 740.05 | 7417.62 | 01-JAN-00:10 | 54470.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 476.91 | 4780.09 | 01-JAN-00:10 | 35102.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7588.97 | 95364.66 | 01-JAN-00:10 | 387850.11 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1622.27 | 19890.94 | 01-JAN-00:10 | 85232.07 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:HVAC | 5299.19 | 36901.09 | 11-SEP-22:50 | 403607.81 | 14-AUG-15:30 |
ExteriorEquipment:Electricity | 2623.11 | 22123.82 | 01-JAN-00:10 | 235096.12 | 03-APR-07:20 |
Transformer:ExteriorEquipment:Electricity | 56.04 | 979.82 | 01-JAN-00:10 | 3543.78 | 03-APR-07:20 |
ElectricityPurchased:Facility | 31769.99 | 297700.92 | 10-SEP-18:20 | 2379332.99 | 07-AUG-15:20 |
ElectricityPurchased:Plant | 31769.99 | 297700.92 | 10-SEP-18:20 | 2379332.99 | 07-AUG-15:20 |
Cogeneration:ElectricityPurchased | 31769.99 | 297700.92 | 10-SEP-18:20 | 2379332.99 | 07-AUG-15:20 |
General:Cogeneration:ElectricityPurchased | 31769.99 | 297700.92 | 10-SEP-18:20 | 2379332.99 | 07-AUG-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 31769.99 | 297700.92 | 10-SEP-18:20 | 2379332.99 | 07-AUG-15:20 |
ElectricityNet:Plant | 31769.99 | 297700.92 | 10-SEP-18:20 | 2379332.99 | 07-AUG-15:20 |
Cogeneration:ElectricityNet | 31769.99 | 297700.92 | 10-SEP-18:20 | 2379332.99 | 07-AUG-15:20 |
General:Cogeneration:ElectricityNet | 31769.99 | 297700.92 | 10-SEP-18:20 | 2379332.99 | 07-AUG-15:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1730.34 | 0.00 | 06-JAN-01:10 | 393837.46 | 07-SEP-14:50 |
General:Cooling:Electricity | 1730.34 | 0.00 | 06-JAN-01:10 | 393837.46 | 07-SEP-14:50 |
Fans:Electricity | 3103.16 | 28500.85 | 01-JAN-04:40 | 347887.24 | 10-AUG-15:10 |
General:Fans:Electricity | 3103.16 | 28500.85 | 01-JAN-04:40 | 347887.24 | 10-AUG-15:10 |
ExteriorLights:Electricity | 1005.27 | 0.00 | 01-JAN-08:20 | 64082.80 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 1005.27 | 0.00 | 01-JAN-08:20 | 64082.80 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.31 | 1944.00 | 01-JAN-00:10 | 1944.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1695.94 | 0.00 | 17-APR-15:00 | 100000.00 | 31-MAR-23:20 |
General:Humidifier:Electricity | 1695.94 | 0.00 | 17-APR-15:00 | 100000.00 | 31-MAR-23:20 |
Electricity:Plant | 2611.32 | 0.00 | 03-JAN-00:10 | 543464.31 | 07-SEP-14:50 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 478.45 | 0.00 | 01-JAN-00:10 | 58671.58 | 17-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 478.45 | 0.00 | 01-JAN-00:10 | 58671.58 | 17-FEB-12:50 |
HeatRejection:Electricity | 58.28 | 0.00 | 01-JAN-00:10 | 50001.50 | 06-JUN-15:10 |
General:HeatRejection:Electricity | 58.28 | 0.00 | 01-JAN-00:10 | 50001.50 | 06-JUN-15:10 |
Pumps:Electricity | 788.30 | 0.00 | 03-JAN-00:10 | 87619.82 | 07-AUG-14:30 |
General:Pumps:Electricity | 788.30 | 0.00 | 03-JAN-00:10 | 87619.82 | 07-AUG-14:30 |
WIRED_LTG_ELECTRICITY | 157.66 | 0.00 | 01-JAN-00:10 | 13766.21 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4767.92 | 0.00 | 01-JAN-00:40 | 2729835.69 | 09-JAN-07:20 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 4767.92 | 0.00 | 01-JAN-00:40 | 2729835.69 | 09-JAN-07:20 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 4767.92 | 0.00 | 01-JAN-00:40 | 2729835.69 | 09-JAN-07:20 |
Boiler:Heating:NaturalGas | 4767.92 | 0.00 | 01-JAN-00:40 | 2729835.69 | 09-JAN-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 7151.37 | 0.00 | 01-JAN-00:20 | 2578597.25 | 07-SEP-14:50 |
PlantLoopCoolingDemand:HVAC | 7151.37 | 0.00 | 01-JAN-00:20 | 2578597.25 | 07-SEP-14:50 |
CoolingCoils:PlantLoopCoolingDemand | 7151.37 | 0.00 | 01-JAN-00:20 | 2578597.25 | 07-SEP-14:50 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 8581.77 | 0.00 | 20-MAY-23:10 | 0.00 | 17-JUL-16:00 |
Water:HVAC | 630.89 | 0.00 | 17-APR-15:00 | 0.00 | 01-APR-01:10 |
Humidifier:Water | 630.89 | 0.00 | 17-APR-15:00 | 0.00 | 01-APR-01:10 |
General:Humidifier:Water | 630.89 | 0.00 | 17-APR-15:00 | 0.00 | 01-APR-01:10 |
MainsWater:Facility | 8581.77 | 0.00 | 20-MAY-23:10 | 0.00 | 17-JUL-16:00 |
MainsWater:HVAC | 630.89 | 0.00 | 17-APR-15:00 | 0.00 | 01-APR-01:10 |
Humidifier:MainsWater | 630.89 | 0.00 | 17-APR-15:00 | 0.00 | 01-APR-01:10 |
General:Humidifier:MainsWater | 630.89 | 0.00 | 17-APR-15:00 | 0.00 | 01-APR-01:10 |
Water:Plant | 7950.88 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-11:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-11:10 |
MainsWater:Plant | 7950.88 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-11:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-11:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 5670.72 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-18:00 |
General:HeatRejection:Water | 5670.72 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-18:00 |
HeatRejection:MainsWater | 5670.72 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-18:00 |
General:HeatRejection:MainsWater | 5670.72 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-18:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 59822.53 | 102147.63 | 12-JAN-02:50 | 12111866.92 | 10-AUG-15:10 |
EnergyTransfer:Building | 20612.92 | 86548.65 | 21-JAN-19:00 | 1974464.39 | 10-AUG-15:00 |
EnergyTransfer:Zone:BASEMENT | 650.41 | 0.00 | 01-JAN-00:10 | 77917.03 | 02-JAN-06:20 |
Heating:EnergyTransfer | 1464.46 | 0.00 | 14-JAN-17:20 | 1700257.76 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 1.10 | 0.00 | 01-JAN-00:10 | 14881.79 | 05-AUG-16:10 |
General:Heating:EnergyTransfer | 1464.46 | 0.00 | 14-JAN-17:20 | 1700257.76 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 1.10 | 0.00 | 01-JAN-00:10 | 14881.79 | 05-AUG-16:10 |
Cooling:EnergyTransfer | 19148.45 | 80672.53 | 09-JAN-05:40 | 1974464.39 | 10-AUG-15:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 649.31 | 0.00 | 01-JAN-00:10 | 77397.42 | 02-JAN-06:20 |
General:Cooling:EnergyTransfer | 19148.45 | 80672.53 | 09-JAN-05:40 | 1974464.39 | 10-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 649.31 | 0.00 | 01-JAN-00:10 | 77397.42 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 590.70 | 0.00 | 01-JAN-00:10 | 58021.80 | 07-AUG-14:00 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.01 | 0.00 | 01-JAN-00:10 | 6763.79 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.01 | 0.00 | 01-JAN-00:10 | 6763.79 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 590.70 | 0.00 | 01-JAN-00:10 | 58021.80 | 07-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 590.70 | 0.00 | 01-JAN-00:10 | 58021.80 | 07-AUG-14:00 |
EnergyTransfer:Zone:CORE_MID | 4671.47 | 0.00 | 01-JAN-00:40 | 499583.31 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 12.79 | 0.00 | 01-JAN-00:10 | 375023.52 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 12.79 | 0.00 | 01-JAN-00:10 | 375023.52 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4658.68 | 0.00 | 01-JAN-00:40 | 499583.31 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4658.68 | 0.00 | 01-JAN-00:40 | 499583.31 | 10-AUG-16:00 |
EnergyTransfer:Zone:CORE_TOP | 435.94 | 0.00 | 01-JAN-00:40 | 107394.22 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 39.07 | 0.00 | 01-JAN-00:20 | 107394.22 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 39.07 | 0.00 | 01-JAN-00:20 | 107394.22 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 396.87 | 0.00 | 01-JAN-00:40 | 63100.77 | 17-JUL-15:40 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 396.87 | 0.00 | 01-JAN-00:40 | 63100.77 | 17-JUL-15:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 80.36 | 0.00 | 01-JAN-00:10 | 18905.61 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 9.24 | 0.00 | 01-JAN-00:10 | 18905.61 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 9.24 | 0.00 | 01-JAN-00:10 | 18905.61 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 71.13 | 0.00 | 01-JAN-00:10 | 12784.61 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 71.13 | 0.00 | 01-JAN-00:10 | 12784.61 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 81.18 | 0.00 | 01-JAN-00:10 | 17942.45 | 07-AUG-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 6.42 | 0.00 | 01-JAN-00:10 | 13535.14 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 6.42 | 0.00 | 01-JAN-00:10 | 13535.14 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 74.75 | 0.00 | 01-JAN-00:10 | 17942.45 | 07-AUG-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 74.75 | 0.00 | 01-JAN-00:10 | 17942.45 | 07-AUG-08:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 132.12 | 0.00 | 01-JAN-00:10 | 27111.76 | 18-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 10.13 | 0.00 | 01-JAN-00:10 | 20640.96 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 10.13 | 0.00 | 01-JAN-00:10 | 20640.96 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 122.00 | 0.00 | 01-JAN-00:10 | 27111.76 | 18-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 122.00 | 0.00 | 01-JAN-00:10 | 27111.76 | 18-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 103.99 | 0.00 | 01-JAN-00:10 | 21799.67 | 07-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.63 | 0.00 | 01-JAN-00:10 | 10765.43 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.63 | 0.00 | 01-JAN-00:10 | 10765.43 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 101.36 | 0.00 | 01-JAN-00:10 | 21799.67 | 07-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 101.36 | 0.00 | 01-JAN-00:10 | 21799.67 | 07-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 886.66 | 0.00 | 01-JAN-00:40 | 257118.81 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 323.12 | 0.00 | 01-JAN-00:40 | 257118.81 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 323.12 | 0.00 | 01-JAN-00:40 | 257118.81 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 563.54 | 0.00 | 01-JAN-00:20 | 119205.86 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 563.54 | 0.00 | 01-JAN-00:20 | 119205.86 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 787.66 | 0.00 | 01-JAN-00:40 | 186225.21 | 07-AUG-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 186.35 | 0.00 | 01-JAN-00:40 | 176975.81 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 186.35 | 0.00 | 01-JAN-00:40 | 176975.81 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 601.31 | 0.00 | 01-JAN-00:20 | 186225.21 | 07-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 601.31 | 0.00 | 01-JAN-00:20 | 186225.21 | 07-AUG-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1346.01 | 0.00 | 01-JAN-00:40 | 295607.43 | 18-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 221.37 | 0.00 | 01-JAN-00:10 | 253687.15 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 221.37 | 0.00 | 01-JAN-00:10 | 253687.15 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1124.64 | 0.00 | 01-JAN-00:40 | 295607.43 | 18-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1124.64 | 0.00 | 01-JAN-00:40 | 295607.43 | 18-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 826.66 | 0.00 | 01-JAN-00:40 | 206162.57 | 17-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 165.79 | 0.00 | 01-JAN-00:20 | 164620.87 | 27-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 165.79 | 0.00 | 01-JAN-00:20 | 164620.87 | 27-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 660.88 | 0.00 | 01-JAN-00:40 | 206162.57 | 17-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 660.88 | 0.00 | 01-JAN-00:40 | 206162.57 | 17-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 122.85 | 0.00 | 01-JAN-00:40 | 33856.16 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 68.81 | 0.00 | 01-JAN-00:40 | 33856.16 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 68.81 | 0.00 | 01-JAN-00:40 | 33856.16 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 54.04 | 0.00 | 01-JAN-00:20 | 13840.80 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 54.04 | 0.00 | 01-JAN-00:20 | 13840.80 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 97.67 | 0.00 | 01-JAN-00:40 | 22344.89 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 40.03 | 0.00 | 01-JAN-00:40 | 22344.89 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 40.03 | 0.00 | 01-JAN-00:40 | 22344.89 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 57.63 | 0.00 | 01-JAN-00:20 | 18843.31 | 17-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 57.63 | 0.00 | 01-JAN-00:20 | 18843.31 | 17-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 156.72 | 0.00 | 01-JAN-00:40 | 33384.46 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 51.22 | 0.00 | 01-JAN-00:40 | 33384.46 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 51.22 | 0.00 | 01-JAN-00:40 | 33384.46 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 105.50 | 0.00 | 01-JAN-00:20 | 29418.59 | 18-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 105.50 | 0.00 | 01-JAN-00:20 | 29418.59 | 18-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 95.93 | 0.00 | 01-JAN-00:40 | 21888.02 | 17-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 34.12 | 0.00 | 01-JAN-00:40 | 21427.87 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 34.12 | 0.00 | 01-JAN-00:40 | 21427.87 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 61.81 | 0.00 | 01-JAN-00:20 | 21888.02 | 17-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 61.81 | 0.00 | 01-JAN-00:20 | 21888.02 | 17-JUL-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 78.86 | 0.00 | 01-JAN-00:10 | 11054.81 | 07-AUG-15:00 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 2.64 | 0.00 | 01-JAN-00:10 | 7096.01 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 2.64 | 0.00 | 01-JAN-00:10 | 7096.01 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 76.23 | 0.00 | 01-JAN-00:10 | 11054.81 | 07-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 76.23 | 0.00 | 01-JAN-00:10 | 11054.81 | 07-AUG-15:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 693.40 | 0.00 | 01-JAN-00:40 | 156254.22 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 125.20 | 0.00 | 01-JAN-00:10 | 156254.22 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 125.20 | 0.00 | 01-JAN-00:10 | 156254.22 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 568.20 | 0.00 | 01-JAN-00:40 | 114681.47 | 12-NOV-05:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 568.20 | 0.00 | 01-JAN-00:40 | 114681.47 | 12-NOV-05:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 236.45 | 0.00 | 01-JAN-00:40 | 63513.43 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 141.66 | 0.00 | 01-JAN-00:40 | 63513.43 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 141.66 | 0.00 | 01-JAN-00:40 | 63513.43 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 94.78 | 0.00 | 01-JAN-00:10 | 39801.40 | 17-JUL-14:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 94.78 | 0.00 | 01-JAN-00:10 | 39801.40 | 17-JUL-14:20 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 130.21 | 5.55 | 28-JAN-19:20 | 11626.11 | 29-DEC-09:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.62 | 0.00 | 01-JAN-00:10 | 1531.21 | 10-JAN-24:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.62 | 0.00 | 01-JAN-00:10 | 1531.21 | 10-JAN-24:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 129.59 | 0.00 | 06-JAN-00:30 | 11626.11 | 29-DEC-09:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 129.59 | 0.00 | 06-JAN-00:30 | 11626.11 | 29-DEC-09:50 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1141.78 | 5.04 | 07-MAY-04:40 | 105645.84 | 29-DEC-09:50 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 13.71 | 0.00 | 02-JAN-10:30 | 14834.86 | 10-JAN-23:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 13.71 | 0.00 | 02-JAN-10:30 | 14834.86 | 10-JAN-23:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1128.06 | 0.00 | 01-JAN-00:10 | 105645.84 | 29-DEC-09:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1128.06 | 0.00 | 01-JAN-00:10 | 105645.84 | 29-DEC-09:50 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 100.24 | 5.10 | 30-SEP-08:00 | 9353.09 | 29-DEC-09:50 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 3.07 | 0.00 | 02-JAN-11:40 | 1599.74 | 29-JAN-17:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 3.07 | 0.00 | 02-JAN-11:40 | 1599.74 | 29-JAN-17:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 97.17 | 0.00 | 01-JAN-00:10 | 9353.09 | 29-DEC-09:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 97.17 | 0.00 | 01-JAN-00:10 | 9353.09 | 29-DEC-09:50 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7165.65 | 80448.27 | 09-JAN-06:50 | 401395.25 | 18-AUG-09:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 5.37 | 0.00 | 01-JAN-00:10 | 5661.21 | 25-JUN-07:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 5.37 | 0.00 | 01-JAN-00:10 | 5661.21 | 25-JUN-07:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7160.29 | 80448.27 | 09-JAN-06:50 | 401395.25 | 18-AUG-09:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7160.29 | 80448.27 | 09-JAN-06:50 | 401395.25 | 18-AUG-09:20 |
PlantLoopHeatingDemand:Facility | 3727.38 | 0.00 | 01-JAN-00:40 | 2199135.91 | 09-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 472.97 | 0.00 | 01-JAN-00:10 | 58297.13 | 17-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 472.97 | 0.00 | 01-JAN-00:10 | 58297.13 | 17-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 472.97 | 0.00 | 01-JAN-00:10 | 58297.13 | 17-FEB-12:10 |
EnergyTransfer:HVAC | 12235.86 | 0.72 | 10-JAN-22:10 | 2622283.16 | 07-SEP-14:50 |
HeatingCoils:EnergyTransfer | 3254.41 | 0.00 | 01-JAN-00:40 | 2180186.38 | 09-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 3254.41 | 0.00 | 01-JAN-00:40 | 2180186.38 | 09-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 3254.41 | 0.00 | 01-JAN-00:40 | 2180186.38 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 8981.45 | 0.00 | 06-JAN-01:10 | 2622283.16 | 07-SEP-14:50 |
EnergyTransfer:Plant | 26973.75 | 0.00 | 03-JAN-00:10 | 8101638.71 | 07-SEP-14:50 |
LoopToLoop:EnergyTransfer | 7258.63 | 0.00 | 01-JAN-00:20 | 2564657.92 | 07-SEP-14:50 |
WaterSystems:EnergyTransfer | 472.97 | 0.00 | 01-JAN-00:10 | 58297.13 | 17-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 472.97 | 0.00 | 01-JAN-00:10 | 58297.13 | 17-FEB-12:10 |
Boilers:EnergyTransfer | 3237.39 | 0.00 | 01-JAN-00:40 | 2128690.36 | 09-JAN-07:20 |
Chillers:EnergyTransfer | 7359.24 | 0.00 | 01-JAN-00:20 | 2564097.79 | 07-SEP-14:50 |
HeatRejection:EnergyTransfer | 8645.53 | 0.00 | 01-JAN-00:20 | 2946211.76 | 07-SEP-14:50 |
General:HeatRejection:EnergyTransfer | 8645.53 | 0.00 | 01-JAN-00:20 | 2946211.76 | 07-SEP-14:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 1.103 | -649.300 | 0.000 | 0.000 | 95.037 | 333.789 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -205.027 |
CORE_BOTTOM | 0.000 | 0.000 | 0.010 | -590.694 | 0.000 | 0.000 | 83.946 | 299.766 | 289.614 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -82.642 |
CORE_MID | 0.000 | 0.000 | 12.789 | -4658.663 | 0.000 | 0.000 | 856.062 | 2997.664 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -2103.980 |
CORE_TOP | 0.000 | 0.000 | 39.070 | -396.864 | 0.000 | 0.000 | 91.317 | 299.766 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -322.903 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 9.238 | -71.125 | 0.000 | 0.000 | 11.433 | 37.639 | 36.365 | 24.166 | 0.000 | 0.097 | 81.077 | 0.000 | -119.188 | 0.000 | -9.702 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 6.421 | -74.755 | 0.000 | 0.000 | 7.384 | 24.256 | 23.435 | 62.424 | 0.000 | 0.069 | 29.652 | 0.000 | -72.462 | 0.000 | -6.423 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 10.127 | -121.996 | 0.000 | 0.000 | 11.264 | 37.639 | 36.366 | 136.216 | 0.000 | 0.091 | 6.016 | 0.000 | -105.961 | 0.000 | -9.763 | -0.002 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 2.627 | -101.360 | 0.000 | 0.000 | 7.406 | 24.256 | 23.435 | 58.960 | 0.000 | 0.061 | 73.500 | 0.000 | -82.019 | 0.000 | -6.866 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 323.119 | -563.538 | 0.000 | 0.000 | 119.302 | 376.387 | 363.654 | 260.504 | 0.000 | 2.688 | 434.087 | 0.000 | -1111.888 | 0.000 | -204.315 | -0.009 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 186.347 | -601.309 | 0.000 | 0.000 | 55.122 | 242.558 | 234.352 | 621.746 | 0.000 | 1.536 | 91.426 | 0.000 | -691.876 | 0.000 | -139.902 | -0.027 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 221.367 | -1124.641 | 0.000 | 0.000 | 114.044 | 376.395 | 363.660 | 1347.607 | 0.000 | 2.055 | 0.002 | 0.000 | -1044.126 | 0.000 | -218.872 | -37.488 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 165.786 | -660.869 | 0.000 | 0.000 | 76.808 | 242.558 | 234.351 | 603.184 | 0.000 | 1.562 | 230.955 | 0.000 | -752.018 | 0.000 | -142.316 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 68.806 | -54.043 | 0.000 | 0.000 | 12.144 | 37.639 | 36.365 | 27.200 | 0.000 | 0.364 | 0.000 | 0.000 | -104.439 | 0.000 | -23.811 | -0.225 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 40.035 | -57.632 | 0.000 | 0.000 | 7.585 | 24.256 | 23.435 | 63.244 | 0.000 | 0.187 | 0.002 | 0.000 | -65.147 | 0.000 | -16.284 | -19.677 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 51.221 | -105.497 | 0.000 | 0.000 | 11.659 | 37.639 | 36.366 | 136.263 | 0.000 | 0.266 | 0.001 | 0.000 | -97.440 | 0.000 | -25.265 | -45.212 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 34.118 | -61.807 | 0.000 | 0.000 | 7.743 | 24.256 | 23.435 | 60.491 | 0.000 | 0.193 | 0.000 | 0.000 | -71.377 | 0.000 | -16.756 | -0.297 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.622 | -129.591 | 0.000 | 0.000 | 0.948 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -34.205 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 13.714 | -1128.062 | 0.000 | 0.000 | 9.488 | 83.466 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -517.412 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 3.074 | -97.167 | 0.000 | 0.000 | 0.951 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -69.085 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 5.368 | -7159.809 | 0.000 | 0.000 | 23.378 | 94.114 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -457.909 |
GROUNDFLOOR_PLENUM | 2.636 | -76.228 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.166 | 95.064 | 0.000 | 0.000 | 0.000 | -21.639 | 0.000 |
MIDFLOOR_PLENUM | 125.204 | -568.194 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.180 | 806.692 | 0.000 | 0.000 | 0.000 | -366.882 | -0.004 |
TOPFLOOR_PLENUM | 141.665 | -94.784 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.256 | 0.001 | 0.000 | 0.000 | 0.000 | -35.812 | -11.325 |
Total Facility | 269.505 | -739.206 | 1194.959 | -18408.723 | 0.000 | 0.000 | 1603.022 | 5610.736 | 14676.396 | 3402.006 | 0.000 | 12.771 | 1848.476 | 0.000 | -4317.941 | 0.000 | -1244.609 | -3907.427 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-NOV-04:01 | 0.00 | 0.00 | 0.00 | -144657.59 | 0.00 | 0.00 | 0.00 | 1619.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 129580.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 14-AUG-04:11 | 0.00 | 0.00 | 0.00 | -118808.16 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.65 | 0.00 | 0.00 | 0.00 | 109962.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 09-AUG-04:11 | 0.00 | 0.00 | 0.00 | -1071181.10 | 0.00 | 0.00 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 982722.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 21-JUN-04:11 | 0.00 | 0.00 | 0.00 | -130286.03 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.62 | 0.00 | 0.00 | 0.00 | 121440.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 06-AUG-16:01 | 0.00 | 0.00 | 0.00 | -26062.59 | 0.00 | 0.00 | 42.64 | 182.58 | 720.18 | 5853.51 | 0.00 | 273.64 | 18990.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 06-AUG-08:41 | 0.00 | 0.00 | 0.00 | -34611.13 | 0.00 | 0.00 | 15.73 | 117.66 | 464.11 | 23782.80 | 0.00 | 0.00 | 10281.66 | 0.00 | -0.00 | 0.00 | -50.83 | 0.00 |
PERIMETER_BOT_ZN_1 | 03-SEP-12:41 | 0.00 | 0.00 | 0.00 | -44579.89 | 0.00 | 0.00 | 25.10 | 182.58 | 720.19 | 32011.50 | 0.00 | 158.12 | 11482.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 16-JUL-17:01 | 0.00 | 0.00 | 0.00 | -45325.24 | 0.00 | 0.00 | 0.00 | 117.66 | 360.35 | 24603.97 | 0.00 | 24.56 | 20218.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 17-JUL-16:00 | 0.00 | 0.00 | 0.00 | -119200.81 | 0.00 | 0.00 | 11143.82 | 32864.16 | 21605.52 | 74431.00 | 0.00 | 2127.30 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22970.98 |
PERIMETER_MID_ZN_2 | 06-AUG-09:31 | 0.00 | 0.00 | 0.00 | -373448.20 | 0.00 | 0.00 | 142.22 | 1176.61 | 4641.14 | 204647.29 | 0.00 | 0.00 | 163337.12 | 0.00 | -0.00 | 0.00 | -496.17 | 0.00 |
PERIMETER_MID_ZN_1 | 26-FEB-14:11 | 0.00 | 0.00 | 0.00 | -442254.79 | 0.00 | 0.00 | 262.68 | 1825.83 | 7201.95 | 329639.55 | 0.00 | 0.00 | 115633.24 | 0.00 | -0.00 | 0.00 | -12308.47 | 0.00 |
PERIMETER_MID_ZN_4 | 04-SEP-16:31 | 0.00 | 0.00 | 0.00 | -402430.64 | 0.00 | 0.00 | 141.63 | 1176.61 | 4641.11 | 217633.54 | 0.00 | 717.69 | 178120.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 17-JUL-16:00 | 0.00 | 0.00 | 0.00 | -13840.17 | 0.00 | 0.00 | 1114.38 | 3286.42 | 2160.55 | 7327.37 | 0.00 | 261.92 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -310.47 |
PERIMETER_TOP_ZN_2 | 16-JUL-08:51 | 0.00 | 0.00 | 0.00 | -36299.07 | 0.00 | 0.00 | 17.23 | 117.66 | 464.11 | 20358.74 | 0.00 | 0.00 | 15744.56 | 0.00 | -0.00 | 0.00 | -403.23 | 0.00 |
PERIMETER_TOP_ZN_1 | 03-SEP-13:21 | 0.00 | 0.00 | 0.00 | -58933.50 | 0.00 | 0.00 | 21.53 | 182.58 | 720.19 | 28894.76 | 0.00 | 394.21 | 28720.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 16-JUL-17:31 | 0.00 | 0.00 | 0.00 | -46487.07 | 0.00 | 0.00 | 0.00 | 117.66 | 360.35 | 23551.93 | 0.00 | 48.03 | 22409.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 29-DEC-01:01 | 0.00 | 0.00 | 0.00 | -13251.44 | 0.00 | 0.00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 5416.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 29-DEC-01:01 | 0.00 | 0.00 | 0.00 | -118786.24 | 0.00 | 0.00 | 0.00 | 404.88 | 77944.22 | 0.00 | 0.00 | 0.00 | 40437.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 29-DEC-09:41 | 0.00 | 0.00 | 0.00 | -11612.40 | 0.00 | 0.00 | 0.00 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 3089.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | -538317.49 | 0.00 | 0.00 | 0.00 | 456.53 | 284724.39 | 0.00 | 0.00 | 0.00 | 253136.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 28-JAN-04:11 | 0.00 | -20587.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23063.67 | 0.00 | -0.00 | 0.00 | -2476.46 | 0.00 |
MIDFLOOR_PLENUM | 05-MAR-00:01 | 0.00 | -236030.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277387.11 | 0.00 | -0.00 | 0.00 | -41356.20 | 0.00 |
TOPFLOOR_PLENUM | 17-JUL-14:20 | 0.00 | -39799.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.48 | 39736.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-AUG-04:11 | 0.00 | 58725.78 | 0.00 | -2244944.23 | 0.00 | 0.00 | 0.00 | 54433.43 | 587299.42 | 0.00 | 0.00 | 0.00 | 1708606.37 | 0.00 | -135008.93 | 0.00 | -29111.84 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 05-AUG-16:01 | 0.00 | 0.00 | 16085.87 | 0.00 | 0.00 | 0.00 | 520.14 | 1619.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -31682.70 |
CORE_BOTTOM | 09-JAN-06:01 | 0.00 | 0.00 | 19419.61 | 0.00 | 0.00 | 0.00 | 1151.01 | 2908.23 | 7647.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -31126.24 |
CORE_MID | 09-JAN-05:01 | 0.00 | 0.00 | 609862.84 | 0.00 | 0.00 | 0.00 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -698321.37 |
CORE_TOP | 09-JAN-04:01 | 0.00 | 0.00 | 133443.75 | 0.00 | 0.00 | 0.00 | 0.00 | 1454.11 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -140835.49 |
PERIMETER_BOT_ZN_3 | 31-DEC-08:11 | 0.00 | 0.00 | 23399.80 | 0.00 | 0.00 | 0.00 | 87.87 | 182.58 | 720.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11957.51 | 0.00 | -1266.13 | -11166.79 |
PERIMETER_BOT_ZN_2 | 31-DEC-07:31 | 0.00 | 0.00 | 22015.12 | 0.00 | 0.00 | 0.00 | 57.45 | 117.66 | 464.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8199.70 | 0.00 | -887.29 | -13567.36 |
PERIMETER_BOT_ZN_1 | 31-DEC-07:31 | 0.00 | 0.00 | 31669.03 | 0.00 | 0.00 | 0.00 | 89.57 | 182.58 | 720.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -12613.50 | 0.00 | -1321.69 | -18726.19 |
PERIMETER_BOT_ZN_4 | 11-JAN-04:11 | 0.00 | 0.00 | 21342.71 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8600.53 | 0.00 | -588.23 | -12752.07 |
PERIMETER_MID_ZN_3 | 09-JAN-04:01 | 0.00 | 0.00 | 339110.16 | 0.00 | 0.00 | 0.00 | 0.00 | 1825.79 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -117745.41 | 0.00 | -18443.27 | -212202.88 |
PERIMETER_MID_ZN_2 | 31-DEC-07:51 | 0.00 | 0.00 | 275487.38 | 0.00 | 0.00 | 0.00 | 600.49 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -79073.78 | 0.00 | -19856.90 | -182974.93 |
PERIMETER_MID_ZN_1 | 31-DEC-07:51 | 0.00 | 0.00 | 351776.56 | 0.00 | 0.00 | 0.00 | 930.09 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -124386.28 | 0.00 | -29682.58 | -207665.57 |
PERIMETER_MID_ZN_4 | 09-JAN-04:01 | 0.00 | 0.00 | 283410.23 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.61 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -76240.64 | 0.00 | -12496.99 | -200653.85 |
PERIMETER_TOP_ZN_3 | 09-JAN-04:01 | 0.00 | 0.00 | 46592.78 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11413.34 | 0.00 | -2238.81 | -33868.77 |
PERIMETER_TOP_ZN_2 | 31-DEC-08:61 | 0.00 | 0.00 | 30798.07 | 0.00 | 0.00 | 0.00 | 61.45 | 117.66 | 464.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7595.95 | 0.00 | -2338.19 | -21507.16 |
PERIMETER_TOP_ZN_1 | 31-DEC-08:61 | 0.00 | 0.00 | 47449.60 | 0.00 | 0.00 | 0.00 | 95.30 | 182.58 | 720.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11955.29 | 0.00 | -3510.21 | -32982.17 |
PERIMETER_TOP_ZN_4 | 09-JAN-04:01 | 0.00 | 0.00 | 35098.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7365.46 | 0.00 | -1513.79 | -26816.88 |
DATACENTER_BOT_ZN_6 | 29-DEC-05:02 | 0.00 | 0.00 | 2389.30 | 0.00 | 0.00 | 0.00 | 0.00 | 80.98 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10264.70 |
DATACENTER_MID_ZN_6 | 29-DEC-05:02 | 0.00 | 0.00 | 19380.04 | 0.00 | 0.00 | 0.00 | 0.00 | 809.76 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -98134.02 |
DATACENTER_TOP_ZN_6 | 29-DEC-05:02 | 0.00 | 0.00 | 1753.52 | 0.00 | 0.00 | 0.00 | 0.00 | 80.98 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9628.92 |
DATACENTER_BASEMENT_ZN_6 | 25-JUN-07:41 | 0.00 | 0.00 | 39626.72 | 0.00 | 0.00 | 0.00 | 170.40 | 456.53 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -230069.92 |
GROUNDFLOOR_PLENUM | 06-AUG-16:01 | 17291.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.62 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17875.06 |
MIDFLOOR_PLENUM | 09-JAN-06:05 | 184820.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -8135.36 | -176684.87 |
TOPFLOOR_PLENUM | 28-JAN-05:11 | 70527.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3745.38 | -66782.01 |
Total Facility | 09-JAN-06:01 | 3294.70 | 80714.49 | 2075783.42 | -80714.49 | 0.00 | 0.00 | 22812.60 | 54433.43 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -491747.06 | 0.00 | -29022.02 | -1896970.04 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 16.9499 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 14.0606 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 170.8886 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 130.5452 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 20.9274 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 16.3695 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 7.9069 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 7.9069 | 0.1518 | 1.0000 | Not calculated | 1.2002 | 0.1518 | ||
AIRLOOP DATACENTER BASEMENT | 35.9236 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 35.9237 | 0.0094 | 1.0000 | Not calculated | 0.3384 | 0.0094 | ||
AIRLOOP DATACENTER BOT | 0.8691 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.8691 | 0.0180 | 1.0000 | Not calculated | 0.0156 | 0.0180 | ||
AIRLOOP DATACENTER MID | 8.3709 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 8.3709 | 0.0187 | 1.0000 | Not calculated | 0.1563 | 0.0187 | ||
AIRLOOP DATACENTER TOP | 0.8623 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.8623 | 0.0181 | 1.0000 | Not calculated | 0.0156 | 0.0181 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 8.4750 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0850 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 85.4443 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 51.2666 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.4637 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.2782 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 2.3721 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 2.3721 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.5060 | ||
AIRLOOP DATACENTER BASEMENT | 17.9618 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 17.9618 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0188 | ||
AIRLOOP DATACENTER BOT | 0.8691 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.8691 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0180 | ||
AIRLOOP DATACENTER MID | 8.3709 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 8.3709 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0187 | ||
AIRLOOP DATACENTER TOP | 0.8623 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.8623 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0181 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 7.9069 | 7.9069 | 2.3721 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.4275 | 8.4275 | 2.5283 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 80.0648 | 80.0648 | 24.0194 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.0874 | 10.0874 | 3.0262 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7909 | 1.7909 | 0.5373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9095 | 1.9095 | 0.5728 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4442 | 2.4442 | 0.7332 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3778 | 2.3778 | 0.7134 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 23.7193 | 23.7193 | 7.1158 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 20.2194 | 20.2194 | 6.0658 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 24.6412 | 24.6412 | 7.3924 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 22.2438 | 22.2438 | 6.6731 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1479 | 3.1479 | 0.9444 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0753 | 2.0753 | 0.6226 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2010 | 3.2010 | 0.9603 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4158 | 2.4158 | 0.7247 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8691 | 0.8691 | 0.8691 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 8.3709 | 8.3709 | 8.3709 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8623 | 0.8623 | 0.8623 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 35.9236 | 35.9236 | 17.9618 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 16.9499 | 14.0606 | 16.9499 | 5.0850 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 170.8886 | 130.5452 | 170.8886 | 51.2666 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 20.9274 | 16.3695 | 20.9274 | 6.2782 | 0.0000 | 1.0000 |
CAV_BAS | 7.9069 | 7.9069 | 7.9069 | 2.3721 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 35.9236 | 35.9237 | 35.9236 | 17.9618 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.8691 | 0.8691 | 0.8691 | 0.8691 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 8.3709 | 8.3709 | 8.3709 | 8.3709 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.8623 | 0.8623 | 0.8623 | 0.8623 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 2.3721 | 2.3721 | 2.3721 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.2138 | 4.2138 | 2.5283 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 40.0324 | 40.0324 | 24.0194 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.0437 | 5.0437 | 3.0262 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8955 | 0.8955 | 0.5373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9547 | 0.9547 | 0.5728 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2221 | 1.2221 | 0.7332 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1889 | 1.1889 | 0.7134 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.8597 | 11.8597 | 7.1158 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.1097 | 10.1097 | 6.0658 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.3206 | 12.3206 | 7.3924 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.1219 | 11.1219 | 6.6731 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5739 | 1.5739 | 0.9444 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0376 | 1.0376 | 0.6226 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6005 | 1.6005 | 0.9603 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2079 | 1.2079 | 0.7247 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8691 | 0.8691 | 0.8691 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 8.3709 | 8.3709 | 8.3709 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8623 | 0.8623 | 0.8623 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 17.9618 | 17.9618 | 17.9618 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 8.4750 | 5.0850 | 5.0850 | 5.0850 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 85.4443 | 51.2666 | 51.2666 | 51.2666 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.4637 | 6.2782 | 6.2782 | 6.2782 | 0.0000 | 1.0000 |
CAV_BAS | 2.3721 | 2.3721 | 2.3721 | 2.3721 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 17.9618 | 17.9618 | 17.9618 | 17.9618 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.8691 | 0.8691 | 0.8691 | 0.8691 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 8.3709 | 8.3709 | 8.3709 | 8.3709 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.8623 | 0.8623 | 0.8623 | 0.8623 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 79.50 |
Number of hours cooling loads not met | 180.17 |
Number of hours not met | 246.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 4767.92 | 2729835.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1730.34 | 393837.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 5610.74 | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 1005.27 | 64082.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 56.04 | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.31 | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 3103.16 | 347887.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 788.30 | 87619.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 58.28 | 50001.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1695.94 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 478.45 | 58671.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 31769.99 |
Natural Gas | 0.00 | 4767.92 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 36537.90 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 121.13 |
Space Heating | 0.00 |
Space Cooling | 37.36 |
Fans (All) | 66.99 |
Service Water Heating | 10.33 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 685.87 |
Subtotal | 685.87 |
Natural Gas [MJ/m2] | |
Space Heating | 102.93 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 102.93 |
Subtotal | 102.93 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.36 |
Space Heating | 13.05 |
Space Cooling | 4.74 |
Fans (All) | 8.49 |
Service Water Heating | 1.31 |
Receptacle Equipment | 40.17 |
Miscellaneous | 16.89 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
LTG_SCH_DATACENTER | 2939. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8694.50 | 65.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8745.33 | 14.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8746.17 | 13.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8719.33 | 40.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8745.33 | 14.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8745.17 | 14.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8739.17 | 20.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8746.83 | 13.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8750.33 | 9.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8741.33 | 18.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8640.33 | 110.17 | 9.50 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8692.83 | 59.50 | 7.67 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8707.67 | 49.17 | 3.17 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8528.00 | 232.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8734.83 | 25.17 | 0.00 | 0.00 | 0.00 |
Min | 8528.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 232.00 | 9.50 | 0.00 | 0.00 |
Average | 8728.55 | 30.57 | 0.88 | 0.00 | 0.00 |
Sum | 200756.67 | 703.00 | 20.33 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368495.83 | 120.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330812.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2228.50 | 37.83 | 1.67 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2234.33 | 32.00 | 1.67 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2239.00 | 27.33 | 1.67 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 100399.17 | 2995.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368495.83 | 2995.83 | 1.67 | 0.00 | 0.00 |
Average | 80194.95 | 139.75 | 0.22 | 0.00 | 0.00 |
Sum | 1844483.83 | 3214.17 | 5.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8679.50 | 80.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8715.17 | 44.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8724.83 | 35.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8744.50 | 15.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8752.17 | 7.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8749.00 | 11.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8746.50 | 13.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8719.67 | 40.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8755.17 | 4.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8749.17 | 10.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8746.83 | 13.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8740.00 | 20.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8750.33 | 9.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8744.83 | 15.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8740.33 | 19.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8740.83 | 19.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8743.33 | 16.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8609.83 | 150.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8751.00 | 9.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8710.67 | 49.33 | 0.00 | 0.00 | 0.00 |
Min | 8609.83 | 0.83 | 0.00 | 0.00 | 0.00 |
Max | 8759.17 | 150.17 | 0.00 | 0.00 | 0.00 |
Average | 8734.08 | 25.92 | 0.00 | 0.00 | 0.00 |
Sum | 200883.83 | 596.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 368411.83 | 204.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330723.00 | 90.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330726.00 | 87.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330782.00 | 31.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2261.67 | 6.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2260.67 | 7.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2260.50 | 7.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 101230.50 | 2164.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368411.83 | 2164.50 | 0.00 | 0.00 | 0.00 |
Average | 80221.96 | 112.95 | 0.00 | 0.00 | 0.00 |
Sum | 1845105.17 | 2597.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:34
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.503323E+11 | 136092.48 | 02-JAN-04:01 | -0.5 | -3.0 | 0.502222E+10 | 7498.90 | 13-JAN-14:09 | 8.17 | 3.83 |
February | 0.414776E+11 | 132516.08 | 28-FEB-05:01 | -3.4 | -4.0 | 0.475475E+10 | 7499.30 | 27-FEB-14:20 | -3.4 | -4.0 |
March | 0.468258E+11 | 134012.38 | 23-MAR-05:01 | 3.40 | 0.10 | 0.589227E+10 | 7499.26 | 10-MAR-10:09 | 3.40 | 0.10 |
April | 0.442730E+11 | 113931.32 | 03-APR-13:40 | 12.93 | 5.08 | 0.529562E+10 | 7499.25 | 07-APR-09:20 | 18.30 | 7.54 |
May | 0.490785E+11 | 131627.68 | 11-MAY-05:01 | 1.47 | -0.3 | 0.566800E+10 | 7499.34 | 30-MAY-09:30 | 17.80 | 12.14 |
June | 0.551848E+11 | 137838.57 | 05-JUN-04:11 | 8.33 | 5.29 | 0.583030E+10 | 7499.43 | 21-JUN-09:39 | 22.23 | 14.94 |
July | 0.597921E+11 | 142361.52 | 05-JUL-04:11 | 9.40 | 8.79 | 0.545947E+10 | 7499.36 | 18-JUL-09:00 | 28.90 | 16.00 |
August | 0.686130E+11 | 125248.53 | 28-AUG-04:11 | 8.67 | 4.95 | 0.610254E+10 | 7499.36 | 01-AUG-13:39 | 8.67 | 4.95 |
September | 0.614376E+11 | 139462.10 | 12-SEP-04:11 | 4.80 | 4.80 | 0.532565E+10 | 7499.69 | 07-SEP-13:50 | 4.80 | 4.80 |
October | 0.614006E+11 | 142831.22 | 30-OCT-04:11 | 4.40 | 1.75 | 0.558721E+10 | 7499.34 | 18-OCT-09:20 | 4.40 | 1.75 |
November | 0.561975E+11 | 144670.35 | 06-NOV-04:01 | -2.8 | -3.9 | 0.551686E+10 | 7499.25 | 08-NOV-14:30 | 13.55 | 7.81 |
December | 0.546930E+11 | 113927.24 | 11-DEC-05:01 | -1.6 | -4.2 | 0.519499E+10 | 7496.49 | 01-DEC-10:39 | -1.6 | -4.2 |
Annual Sum or Average | 0.649306E+12 | 0.656499E+11 | ||||||||
Minimum of Months | 0.414776E+11 | 113927.24 | -3.4 | -4.2 | 0.475475E+10 | 7496.49 | -3.4 | -4.2 | ||
Maximum of Months | 0.686130E+11 | 144670.35 | 12.93 | 8.79 | 0.610254E+10 | 7499.69 | 28.90 | 16.00 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366360E+11 | 105454.13 | 02-JAN-06:01 | -1.3 | -3.4 | 0.486489E+10 | 6734.84 | 20-JAN-14:30 | 0.30 | -3.3 |
February | 0.338340E+11 | 102985.59 | 28-FEB-06:02 | -3.9 | -4.3 | 0.448506E+10 | 6734.88 | 22-FEB-10:09 | -3.9 | -4.3 |
March | 0.443277E+11 | 105331.50 | 30-MAR-05:01 | 0.00 | -2.1 | 0.542738E+10 | 6734.89 | 10-MAR-10:09 | 0.00 | -2.1 |
April | 0.483153E+11 | 109652.26 | 24-APR-04:11 | 3.33 | 2.42 | 0.486594E+10 | 6734.89 | 04-APR-09:09 | 3.33 | 2.42 |
May | 0.482813E+11 | 110172.17 | 30-MAY-04:12 | 15.60 | 10.93 | 0.527045E+10 | 6735.27 | 02-MAY-13:09 | 15.60 | 10.93 |
June | 0.575040E+11 | 114441.93 | 22-JUN-04:11 | 16.10 | 12.27 | 0.526284E+10 | 6734.89 | 20-JUN-09:50 | 16.10 | 12.27 |
July | 0.644214E+11 | 117142.29 | 05-JUL-04:11 | 9.40 | 8.79 | 0.489514E+10 | 6734.90 | 03-JUL-13:09 | 9.40 | 8.79 |
August | 0.710125E+11 | 118805.05 | 14-AUG-04:11 | 12.20 | 9.88 | 0.549767E+10 | 6734.88 | 18-AUG-09:09 | 15.28 | 9.62 |
September | 0.526538E+11 | 117203.52 | 05-SEP-04:11 | 18.30 | 11.92 | 0.487354E+10 | 6735.20 | 07-SEP-09:50 | 16.52 | 15.26 |
October | 0.481070E+11 | 109496.22 | 19-OCT-04:11 | 12.60 | 5.60 | 0.506426E+10 | 6734.89 | 06-OCT-09:09 | 12.60 | 5.60 |
November | 0.438843E+11 | 106964.10 | 24-NOV-05:11 | 12.20 | 4.58 | 0.500694E+10 | 6734.89 | 16-NOV-14:09 | 12.20 | 4.58 |
December | 0.417178E+11 | 106690.06 | 06-DEC-06:01 | 7.02 | 3.93 | 0.484829E+10 | 6734.89 | 07-DEC-10:09 | 3.35 | 1.22 |
Annual Sum or Average | 0.590695E+12 | 0.603624E+11 | ||||||||
Minimum of Months | 0.338340E+11 | 102985.59 | -3.9 | -4.3 | 0.448506E+10 | 6734.84 | -3.9 | -4.3 | ||
Maximum of Months | 0.710125E+11 | 118805.05 | 18.30 | 12.27 | 0.549767E+10 | 6735.27 | 16.52 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.282881E+11 | 26155.26 | 13-JAN-16:53 | 7.80 | 3.93 | 0.443707E+10 | 6734.81 | 20-JAN-14:00 | 0.00 | -3.4 |
February | 0.277871E+11 | 36528.75 | 28-FEB-16:52 | 10.00 | 4.31 | 0.426935E+10 | 6734.88 | 28-FEB-10:09 | 10.00 | 4.31 |
March | 0.358902E+11 | 37635.60 | 01-MAR-16:53 | 7.80 | 3.22 | 0.528069E+10 | 6734.89 | 01-MAR-10:09 | 7.80 | 3.22 |
April | 0.363695E+11 | 97734.91 | 07-APR-05:01 | 12.20 | 5.15 | 0.479432E+10 | 6734.89 | 04-APR-09:09 | 12.20 | 5.15 |
May | 0.405369E+11 | 97000.21 | 13-MAY-05:01 | 7.30 | 3.28 | 0.520967E+10 | 6735.30 | 02-MAY-13:09 | 7.30 | 3.28 |
June | 0.491983E+11 | 105513.85 | 23-JUN-04:11 | 18.13 | 11.74 | 0.524472E+10 | 6734.90 | 01-JUN-09:50 | 18.13 | 11.74 |
July | 0.509557E+11 | 105979.64 | 18-JUL-04:11 | 16.47 | 11.17 | 0.488191E+10 | 6734.90 | 03-JUL-13:09 | 16.47 | 11.17 |
August | 0.532208E+11 | 107092.24 | 09-AUG-04:11 | 15.57 | 10.59 | 0.548443E+10 | 6734.88 | 18-AUG-09:09 | 15.28 | 9.62 |
September | 0.430654E+11 | 102458.39 | 07-SEP-04:11 | 15.20 | 13.06 | 0.484061E+10 | 6735.19 | 07-SEP-09:50 | 16.52 | 15.26 |
October | 0.371667E+11 | 99602.22 | 19-OCT-05:01 | 12.20 | 5.54 | 0.499460E+10 | 6734.90 | 13-OCT-09:00 | 12.20 | 5.54 |
November | 0.325431E+11 | 91492.75 | 08-NOV-06:01 | 10.13 | 4.88 | 0.479286E+10 | 6734.88 | 16-NOV-14:09 | 10.63 | 6.46 |
December | 0.308459E+11 | 33054.18 | 07-DEC-16:23 | 5.55 | 1.71 | 0.447202E+10 | 6734.89 | 07-DEC-10:39 | 5.55 | 1.71 |
Annual Sum or Average | 0.465868E+12 | 0.587023E+11 | ||||||||
Minimum of Months | 0.277871E+11 | 26155.26 | 5.55 | 1.71 | 0.426935E+10 | 6734.81 | 0.00 | -3.4 | ||
Maximum of Months | 0.532208E+11 | 107092.24 | 18.13 | 13.06 | 0.548443E+10 | 6735.30 | 18.13 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161010E+11 | 23579.62 | 13-JAN-17:00 | 7.80 | 3.93 | 0.382850E+10 | 5822.39 | 13-JAN-14:00 | 7.80 | 3.93 |
February | 0.196369E+11 | 26117.11 | 28-FEB-17:00 | 10.00 | 4.31 | 0.360824E+10 | 6299.21 | 28-FEB-14:00 | 10.00 | 4.31 |
March | 0.271695E+11 | 29070.54 | 28-MAR-15:51 | 10.60 | 3.09 | 0.453341E+10 | 6701.77 | 23-MAR-13:00 | 10.60 | 3.09 |
April | 0.297525E+11 | 45103.19 | 25-APR-16:00 | 17.80 | 7.70 | 0.425740E+10 | 6734.88 | 13-APR-13:09 | 17.80 | 7.70 |
May | 0.375220E+11 | 55339.34 | 19-MAY-16:00 | 27.80 | 14.54 | 0.479047E+10 | 6734.87 | 04-MAY-13:30 | 27.80 | 14.54 |
June | 0.500841E+11 | 130333.83 | 21-JUN-04:11 | 17.40 | 12.31 | 0.509900E+10 | 6734.89 | 01-JUN-09:39 | 17.40 | 12.31 |
July | 0.545067E+11 | 123686.69 | 14-JUL-05:01 | 14.97 | 11.72 | 0.480210E+10 | 6734.90 | 03-JUL-13:09 | 14.97 | 11.72 |
August | 0.533843E+11 | 123209.02 | 09-AUG-05:01 | 16.42 | 10.97 | 0.535892E+10 | 6734.86 | 02-AUG-13:50 | 16.42 | 10.97 |
September | 0.389648E+11 | 120651.92 | 05-SEP-05:02 | 18.40 | 11.40 | 0.451794E+10 | 6735.12 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.286660E+11 | 40382.03 | 18-OCT-16:00 | 24.40 | 11.02 | 0.437010E+10 | 6734.87 | 20-OCT-13:00 | 13.30 | 6.77 |
November | 0.228031E+11 | 26683.90 | 03-NOV-16:00 | 14.30 | 7.69 | 0.405244E+10 | 6403.83 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.182753E+11 | 24960.36 | 06-DEC-16:30 | 8.05 | 3.45 | 0.377254E+10 | 6183.25 | 06-DEC-14:00 | 8.05 | 3.45 |
Annual Sum or Average | 0.396866E+12 | 0.529911E+11 | ||||||||
Minimum of Months | 0.161010E+11 | 23579.62 | 7.80 | 3.09 | 0.360824E+10 | 5822.39 | 7.80 | 3.09 | ||
Maximum of Months | 0.545067E+11 | 130333.83 | 27.80 | 14.54 | 0.535892E+10 | 6735.12 | 27.80 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121795E+10 | 3771.50 | 02-JAN-14:40 | 6.30 | 1.27 | 0.472063E+09 | 709.03 | 02-JAN-14:50 | 6.20 | 1.19 |
February | 0.204403E+10 | 5324.97 | 26-FEB-14:51 | 16.70 | 6.48 | 0.443579E+09 | 805.75 | 27-FEB-14:00 | 18.90 | 7.23 |
March | 0.399178E+10 | 5062.65 | 26-MAR-14:01 | 10.00 | 2.16 | 0.562815E+09 | 826.02 | 29-MAR-13:00 | 12.80 | 4.50 |
April | 0.561883E+10 | 8258.30 | 07-APR-14:30 | 22.50 | 9.29 | 0.545084E+09 | 845.63 | 13-APR-13:50 | 13.22 | 7.45 |
May | 0.675448E+10 | 9600.02 | 19-MAY-16:00 | 27.80 | 14.54 | 0.607504E+09 | 845.69 | 02-MAY-13:09 | 27.80 | 14.54 |
June | 0.975436E+10 | 15843.92 | 21-JUN-05:01 | 15.87 | 11.84 | 0.646620E+09 | 845.65 | 27-JUN-13:50 | 24.53 | 13.02 |
July | 0.116919E+11 | 25549.13 | 16-JUL-18:21 | 32.50 | 17.04 | 0.610299E+09 | 845.65 | 13-JUL-09:00 | 32.50 | 17.04 |
August | 0.113272E+11 | 26062.77 | 06-AUG-16:01 | 35.50 | 16.24 | 0.679445E+09 | 845.64 | 01-AUG-13:09 | 35.50 | 16.24 |
September | 0.733232E+10 | 17842.42 | 05-SEP-04:11 | 18.30 | 11.92 | 0.573109E+09 | 845.68 | 07-SEP-09:50 | 16.52 | 15.26 |
October | 0.541190E+10 | 6815.88 | 19-OCT-14:30 | 21.40 | 10.24 | 0.562574E+09 | 845.63 | 13-OCT-13:50 | 21.40 | 10.24 |
November | 0.378195E+10 | 5349.73 | 24-NOV-06:02 | 12.20 | 4.55 | 0.513481E+09 | 820.04 | 24-NOV-14:39 | 14.87 | 6.43 |
December | 0.219894E+10 | 4860.78 | 06-DEC-06:02 | 7.02 | 3.93 | 0.469653E+09 | 761.65 | 06-DEC-14:20 | 11.50 | 5.51 |
Annual Sum or Average | 0.711256E+11 | 0.668623E+10 | ||||||||
Minimum of Months | 0.121795E+10 | 3771.50 | 6.30 | 1.27 | 0.443579E+09 | 709.03 | 6.20 | 1.19 | ||
Maximum of Months | 0.116919E+11 | 26062.77 | 35.50 | 17.04 | 0.679445E+09 | 845.69 | 35.50 | 17.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126625E+10 | 4769.35 | 15-JAN-11:32 | 4.03 | -1.0 | 0.304292E+09 | 484.27 | 17-JAN-10:30 | 5.25 | 1.27 |
February | 0.231084E+10 | 10071.11 | 26-FEB-09:26 | 8.90 | 2.67 | 0.291209E+09 | 544.96 | 28-FEB-10:09 | 1.57 | -0.3 |
March | 0.422202E+10 | 11075.01 | 28-MAR-09:11 | 5.73 | 0.86 | 0.366752E+09 | 544.96 | 01-MAR-10:20 | 5.73 | 0.86 |
April | 0.606763E+10 | 19467.24 | 16-APR-08:31 | 11.47 | 4.88 | 0.347482E+09 | 544.96 | 04-APR-09:09 | 11.47 | 4.88 |
May | 0.741092E+10 | 14759.89 | 19-MAY-08:40 | 17.23 | 11.19 | 0.392720E+09 | 544.99 | 02-MAY-13:09 | 17.23 | 11.19 |
June | 0.105255E+11 | 30644.57 | 04-JUN-07:51 | 16.10 | 13.33 | 0.414729E+09 | 545.05 | 23-JUN-09:09 | 25.97 | 15.51 |
July | 0.125436E+11 | 33057.04 | 16-JUL-08:21 | 20.80 | 15.47 | 0.390635E+09 | 545.31 | 17-JUL-09:30 | 30.30 | 17.33 |
August | 0.119240E+11 | 34610.61 | 06-AUG-08:41 | 26.55 | 14.17 | 0.434961E+09 | 545.64 | 07-AUG-09:50 | 30.13 | 15.30 |
September | 0.773083E+10 | 29392.47 | 03-SEP-09:21 | 26.40 | 14.26 | 0.365692E+09 | 544.96 | 05-SEP-13:50 | 24.22 | 15.03 |
October | 0.549347E+10 | 22049.49 | 15-OCT-09:41 | 16.05 | 8.05 | 0.361430E+09 | 544.96 | 16-OCT-09:09 | 17.70 | 9.16 |
November | 0.338912E+10 | 6923.83 | 03-NOV-09:31 | 7.90 | 4.84 | 0.325632E+09 | 544.96 | 03-NOV-09:09 | 7.90 | 4.84 |
December | 0.187077E+10 | 5035.98 | 08-DEC-06:02 | -0.7 | -3.0 | 0.297248E+09 | 492.31 | 20-DEC-10:30 | 3.85 | -0.4 |
Annual Sum or Average | 0.747549E+11 | 0.429278E+10 | ||||||||
Minimum of Months | 0.126625E+10 | 4769.35 | -0.7 | -3.0 | 0.291209E+09 | 484.27 | 1.57 | -0.4 | ||
Maximum of Months | 0.125436E+11 | 34610.61 | 26.55 | 15.47 | 0.434961E+09 | 545.64 | 30.30 | 17.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366478E+10 | 33846.05 | 15-JAN-13:32 | 5.40 | -0.5 | 0.510071E+09 | 845.65 | 27-JAN-14:20 | -22.0 | -22.7 |
February | 0.605700E+10 | 42262.30 | 26-FEB-13:31 | 15.40 | 5.68 | 0.496338E+09 | 845.65 | 01-FEB-14:09 | 15.40 | 5.68 |
March | 0.834289E+10 | 37781.11 | 26-MAR-13:21 | 9.45 | 1.83 | 0.593740E+09 | 845.65 | 01-MAR-10:20 | 9.45 | 1.83 |
April | 0.905518E+10 | 37240.47 | 16-APR-13:12 | 18.67 | 7.93 | 0.539746E+09 | 845.65 | 13-APR-13:09 | 18.67 | 7.93 |
May | 0.977375E+10 | 19307.91 | 19-MAY-13:30 | 26.65 | 14.96 | 0.598185E+09 | 845.72 | 02-MAY-13:09 | 26.65 | 14.96 |
June | 0.128792E+11 | 23343.86 | 11-JUN-13:51 | 24.40 | 12.87 | 0.628366E+09 | 845.67 | 27-JUN-13:50 | 24.53 | 13.02 |
July | 0.161609E+11 | 39624.32 | 16-JUL-14:21 | 32.50 | 18.75 | 0.599118E+09 | 846.03 | 31-JUL-13:50 | 30.50 | 14.60 |
August | 0.182524E+11 | 40411.28 | 06-AUG-12:41 | 33.72 | 14.74 | 0.668184E+09 | 846.25 | 09-AUG-13:00 | 33.90 | 16.31 |
September | 0.138736E+11 | 44580.11 | 03-SEP-12:41 | 33.22 | 15.94 | 0.570902E+09 | 846.57 | 05-SEP-13:00 | 24.40 | 15.14 |
October | 0.113141E+11 | 39532.02 | 15-OCT-11:01 | 18.77 | 9.82 | 0.583172E+09 | 846.06 | 18-OCT-13:00 | 25.00 | 11.40 |
November | 0.767990E+10 | 37965.88 | 12-NOV-13:31 | -0.6 | -3.6 | 0.554802E+09 | 845.65 | 03-NOV-09:20 | -0.6 | -3.6 |
December | 0.494260E+10 | 17473.96 | 12-DEC-12:24 | -2.8 | -5.7 | 0.513352E+09 | 845.65 | 19-DEC-14:09 | 10.97 | 6.81 |
Annual Sum or Average | 0.121996E+12 | 0.685597E+10 | ||||||||
Minimum of Months | 0.366478E+10 | 17473.96 | -2.8 | -5.7 | 0.496338E+09 | 845.65 | -22.0 | -22.7 | ||
Maximum of Months | 0.182524E+11 | 44580.11 | 33.72 | 18.75 | 0.668184E+09 | 846.57 | 33.90 | 16.31 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217474E+10 | 6187.02 | 13-JAN-15:40 | 9.27 | 4.85 | 0.306611E+09 | 507.83 | 13-JAN-15:50 | 9.08 | 4.76 |
February | 0.362481E+10 | 31136.52 | 26-FEB-16:51 | 15.60 | 5.90 | 0.291424E+09 | 544.96 | 27-FEB-14:39 | 18.70 | 7.17 |
March | 0.623108E+10 | 14034.64 | 28-MAR-15:53 | 10.60 | 3.09 | 0.362003E+09 | 544.96 | 02-MAR-14:00 | 10.60 | 3.09 |
April | 0.911998E+10 | 37439.78 | 16-APR-17:11 | 19.80 | 8.90 | 0.352141E+09 | 544.96 | 13-APR-13:50 | 19.80 | 8.90 |
May | 0.961910E+10 | 36271.85 | 28-MAY-17:31 | 20.37 | 10.36 | 0.377076E+09 | 544.96 | 15-MAY-13:00 | 20.37 | 10.36 |
June | 0.123461E+11 | 36354.69 | 18-JUN-17:31 | 25.20 | 14.48 | 0.401923E+09 | 544.97 | 27-JUN-13:50 | 24.53 | 13.02 |
July | 0.152730E+11 | 45331.86 | 16-JUL-17:01 | 33.22 | 17.33 | 0.388580E+09 | 544.97 | 13-JUL-09:00 | 33.22 | 17.33 |
August | 0.157898E+11 | 43724.35 | 06-AUG-16:41 | 35.10 | 15.80 | 0.436286E+09 | 544.97 | 01-AUG-13:09 | 35.10 | 15.80 |
September | 0.981140E+10 | 38844.16 | 03-SEP-15:21 | 33.30 | 15.93 | 0.354099E+09 | 544.96 | 05-SEP-13:50 | 24.22 | 15.03 |
October | 0.740315E+10 | 28168.94 | 15-OCT-17:01 | 20.45 | 10.12 | 0.350910E+09 | 544.96 | 20-OCT-13:00 | 13.30 | 6.77 |
November | 0.562487E+10 | 10269.30 | 03-NOV-15:23 | 14.45 | 7.69 | 0.336227E+09 | 544.96 | 06-NOV-14:20 | 8.13 | 3.18 |
December | 0.434305E+10 | 8984.25 | 06-DEC-15:24 | 10.25 | 4.94 | 0.313092E+09 | 544.95 | 06-DEC-14:00 | 10.25 | 4.94 |
Annual Sum or Average | 0.101361E+12 | 0.427037E+10 | ||||||||
Minimum of Months | 0.217474E+10 | 6187.02 | 9.27 | 3.09 | 0.291424E+09 | 507.83 | 8.13 | 3.09 | ||
Maximum of Months | 0.157898E+11 | 45331.86 | 35.10 | 17.33 | 0.436286E+09 | 544.97 | 35.10 | 17.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140163E+09 | 4148.23 | 04-JAN-06:04 | -5.6 | -7.7 | 0.463711E+09 | 626.00 | 18-JAN-14:50 | -8.9 | -10.0 |
February | 0.871753E+09 | 5493.51 | 27-FEB-13:21 | 17.75 | 6.76 | 0.423054E+09 | 676.63 | 27-FEB-14:00 | 18.90 | 7.23 |
March | 0.240872E+10 | 5213.93 | 23-MAR-13:30 | 9.70 | 2.18 | 0.513518E+09 | 708.64 | 29-MAR-13:00 | 12.80 | 4.50 |
April | 0.412175E+10 | 6280.66 | 07-APR-14:40 | 22.23 | 9.16 | 0.479052E+09 | 826.76 | 07-APR-13:00 | 22.23 | 9.16 |
May | 0.613969E+10 | 9099.93 | 19-MAY-16:00 | 27.80 | 14.54 | 0.548494E+09 | 845.62 | 30-MAY-13:20 | 18.90 | 10.13 |
June | 0.932310E+10 | 11059.61 | 29-JUN-15:10 | 32.02 | 14.63 | 0.610652E+09 | 845.64 | 20-JUN-13:39 | 32.02 | 14.63 |
July | 0.106566E+11 | 11920.59 | 17-JUL-16:00 | 37.20 | 17.28 | 0.587160E+09 | 845.63 | 20-JUL-09:20 | 24.63 | 15.40 |
August | 0.972271E+10 | 11874.50 | 09-AUG-14:50 | 33.40 | 16.01 | 0.638628E+09 | 845.64 | 01-AUG-13:09 | 33.40 | 16.01 |
September | 0.664928E+10 | 9880.66 | 04-SEP-12:32 | 31.47 | 15.75 | 0.517102E+09 | 845.63 | 05-SEP-13:50 | 24.22 | 15.03 |
October | 0.403275E+10 | 7178.06 | 18-OCT-13:50 | 24.90 | 11.31 | 0.493868E+09 | 789.66 | 19-OCT-13:00 | 21.10 | 10.22 |
November | 0.182398E+10 | 5360.10 | 03-NOV-13:30 | 14.35 | 7.74 | 0.466326E+09 | 692.80 | 08-NOV-14:20 | 13.67 | 7.87 |
December | 0.463573E+09 | 4167.44 | 22-DEC-06:03 | -6.1 | -6.5 | 0.447622E+09 | 625.97 | 27-DEC-10:50 | -12.0 | -12.5 |
Annual Sum or Average | 0.563541E+11 | 0.618919E+10 | ||||||||
Minimum of Months | 0.140163E+09 | 4148.23 | -6.1 | -7.7 | 0.423054E+09 | 625.97 | -12.0 | -12.5 | ||
Maximum of Months | 0.106566E+11 | 11920.59 | 37.20 | 17.28 | 0.638628E+09 | 845.64 | 33.40 | 16.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285889E+09 | 4705.18 | 14-JAN-11:02 | 8.58 | 4.13 | 0.217614E+09 | 489.26 | 20-JAN-11:09 | -1.9 | -4.9 |
February | 0.117591E+10 | 13938.13 | 27-FEB-11:01 | 14.68 | 5.50 | 0.206307E+09 | 548.49 | 27-FEB-15:09 | 18.90 | 7.20 |
March | 0.261008E+10 | 18410.18 | 28-MAR-10:01 | 7.38 | 1.58 | 0.259764E+09 | 548.49 | 13-MAR-10:09 | 7.38 | 1.58 |
April | 0.449879E+10 | 20381.87 | 06-APR-10:01 | 15.78 | 6.97 | 0.248117E+09 | 548.49 | 13-APR-14:09 | 13.22 | 7.55 |
May | 0.629600E+10 | 15713.30 | 19-MAY-10:05 | 20.37 | 12.65 | 0.281538E+09 | 548.56 | 02-MAY-12:09 | 20.37 | 12.65 |
June | 0.100513E+11 | 33824.71 | 25-JUN-09:31 | 18.50 | 12.34 | 0.301088E+09 | 548.52 | 28-JUN-10:09 | 24.78 | 12.68 |
July | 0.120447E+11 | 32709.63 | 02-JUL-07:11 | 18.33 | 13.65 | 0.286119E+09 | 548.54 | 13-JUL-10:09 | 23.48 | 13.97 |
August | 0.109017E+11 | 37345.39 | 06-AUG-09:31 | 29.07 | 14.77 | 0.316335E+09 | 548.52 | 08-AUG-10:09 | 24.18 | 14.57 |
September | 0.650865E+10 | 29382.61 | 04-SEP-09:52 | 27.80 | 14.99 | 0.260593E+09 | 548.51 | 07-SEP-10:09 | 16.88 | 15.79 |
October | 0.368413E+10 | 17344.81 | 12-OCT-10:01 | 16.97 | 8.85 | 0.252668E+09 | 548.50 | 18-OCT-14:09 | 25.00 | 11.44 |
November | 0.159485E+10 | 14234.25 | 03-NOV-10:01 | 9.10 | 5.57 | 0.227596E+09 | 548.49 | 09-NOV-11:09 | 5.25 | 2.44 |
December | 0.478951E+09 | 5220.64 | 06-DEC-11:01 | 10.47 | 5.80 | 0.211755E+09 | 516.70 | 06-DEC-11:09 | 10.47 | 5.80 |
Annual Sum or Average | 0.601309E+11 | 0.306949E+10 | ||||||||
Minimum of Months | 0.285889E+09 | 4705.18 | 7.38 | 1.58 | 0.206307E+09 | 489.26 | -1.9 | -4.9 | ||
Maximum of Months | 0.120447E+11 | 37345.39 | 29.07 | 14.99 | 0.316335E+09 | 548.56 | 25.00 | 15.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.301989E+10 | 16920.62 | 19-JAN-13:40 | -6.0 | -7.8 | 0.500762E+09 | 845.65 | 02-JAN-14:50 | -6.0 | -7.8 |
February | 0.594804E+10 | 44226.58 | 26-FEB-14:11 | 15.97 | 6.00 | 0.489641E+09 | 845.75 | 27-FEB-14:50 | 18.80 | 7.20 |
March | 0.787293E+10 | 38955.49 | 26-MAR-13:41 | 9.82 | 2.05 | 0.582711E+09 | 845.68 | 01-MAR-14:50 | 9.82 | 2.05 |
April | 0.784917E+10 | 36925.73 | 16-APR-13:02 | 18.48 | 7.81 | 0.525278E+09 | 846.40 | 24-APR-13:20 | 17.80 | 9.82 |
May | 0.898665E+10 | 19961.60 | 19-MAY-13:40 | 26.83 | 14.98 | 0.585874E+09 | 845.72 | 02-MAY-13:09 | 26.83 | 14.98 |
June | 0.120555E+11 | 19808.64 | 18-JUN-13:12 | 22.57 | 15.14 | 0.616756E+09 | 845.68 | 19-JUN-13:09 | 24.50 | 12.52 |
July | 0.148858E+11 | 31805.19 | 16-JUL-15:51 | 32.80 | 18.18 | 0.589936E+09 | 846.32 | 31-JUL-13:20 | 30.20 | 14.55 |
August | 0.166394E+11 | 42958.74 | 06-AUG-13:31 | 34.23 | 15.17 | 0.656162E+09 | 846.33 | 25-AUG-13:20 | 30.20 | 14.53 |
September | 0.135123E+11 | 42866.99 | 04-SEP-15:11 | 32.40 | 16.61 | 0.559691E+09 | 846.49 | 05-SEP-13:00 | 24.40 | 15.14 |
October | 0.109451E+11 | 40608.63 | 22-OCT-14:11 | 18.90 | 9.12 | 0.571653E+09 | 849.09 | 18-OCT-13:30 | 18.90 | 9.12 |
November | 0.685772E+10 | 38915.80 | 12-NOV-14:01 | -0.1 | -3.3 | 0.540721E+09 | 845.68 | 03-NOV-13:30 | -0.1 | -3.3 |
December | 0.389186E+10 | 16758.95 | 12-DEC-12:33 | -2.8 | -5.7 | 0.496210E+09 | 845.65 | 13-DEC-14:20 | -5.6 | -7.0 |
Annual Sum or Average | 0.112464E+12 | 0.671539E+10 | ||||||||
Minimum of Months | 0.301989E+10 | 16758.95 | -6.0 | -7.8 | 0.489641E+09 | 845.65 | -6.0 | -7.8 | ||
Maximum of Months | 0.166394E+11 | 44226.58 | 34.23 | 18.18 | 0.656162E+09 | 849.09 | 30.20 | 15.14 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.533928E+09 | 5055.96 | 13-JAN-15:40 | 9.27 | 4.85 | 0.300162E+09 | 459.80 | 13-JAN-15:50 | 9.08 | 4.76 |
February | 0.167766E+10 | 9600.70 | 28-FEB-16:32 | 10.37 | 4.49 | 0.280584E+09 | 521.20 | 27-FEB-16:30 | 10.37 | 4.49 |
March | 0.318160E+10 | 11885.27 | 28-MAR-16:52 | 10.60 | 2.97 | 0.340913E+09 | 544.96 | 02-MAR-14:50 | 10.60 | 2.97 |
April | 0.513415E+10 | 34385.10 | 16-APR-17:01 | 19.90 | 8.94 | 0.313409E+09 | 526.81 | 24-APR-13:00 | 17.80 | 9.82 |
May | 0.727146E+10 | 38530.47 | 28-MAY-18:01 | 19.82 | 10.31 | 0.354268E+09 | 544.94 | 19-MAY-13:00 | 19.82 | 10.31 |
June | 0.101294E+11 | 34416.06 | 18-JUN-17:11 | 25.40 | 14.50 | 0.380272E+09 | 544.96 | 20-JUN-13:00 | 28.90 | 18.82 |
July | 0.118930E+11 | 39977.07 | 09-JUL-16:51 | 28.30 | 12.98 | 0.367428E+09 | 544.95 | 13-JUL-13:20 | 28.53 | 15.68 |
August | 0.110324E+11 | 39836.56 | 06-AUG-16:11 | 35.40 | 16.13 | 0.401838E+09 | 544.95 | 01-AUG-13:30 | 35.40 | 16.13 |
September | 0.730944E+10 | 40243.19 | 04-SEP-16:31 | 32.80 | 16.68 | 0.330419E+09 | 544.95 | 05-SEP-13:00 | 24.40 | 15.14 |
October | 0.458726E+10 | 19309.61 | 15-OCT-17:21 | 19.15 | 9.49 | 0.324736E+09 | 521.20 | 10-OCT-15:00 | 19.15 | 9.49 |
November | 0.239026E+10 | 7506.60 | 03-NOV-15:33 | 14.40 | 7.69 | 0.310604E+09 | 521.19 | 03-NOV-15:00 | 14.30 | 7.69 |
December | 0.947136E+09 | 5358.53 | 06-DEC-15:40 | 9.97 | 4.80 | 0.291370E+09 | 479.57 | 06-DEC-15:50 | 9.68 | 4.65 |
Annual Sum or Average | 0.660877E+11 | 0.399600E+10 | ||||||||
Minimum of Months | 0.533928E+09 | 5055.96 | 9.27 | 2.97 | 0.280584E+09 | 459.80 | 9.08 | 2.97 | ||
Maximum of Months | 0.118930E+11 | 40243.19 | 35.40 | 16.68 | 0.401838E+09 | 544.96 | 35.40 | 18.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 65179595.39 | 4961.18 | 14-JAN-17:02 | 8.90 | 4.06 | 0.463029E+09 | 626.03 | 11-JAN-14:00 | 8.90 | 4.06 |
February | 0.421604E+09 | 5561.48 | 27-FEB-16:00 | 18.90 | 7.06 | 0.420979E+09 | 625.80 | 02-FEB-10:39 | 18.90 | 7.06 |
March | 0.155440E+10 | 6021.22 | 29-MAR-16:00 | 12.20 | 4.07 | 0.505865E+09 | 652.42 | 14-MAR-13:00 | 12.20 | 4.07 |
April | 0.333588E+10 | 7511.93 | 07-APR-14:40 | 22.23 | 9.16 | 0.459806E+09 | 762.94 | 07-APR-13:00 | 22.23 | 9.16 |
May | 0.610157E+10 | 11312.16 | 28-MAY-16:41 | 20.92 | 10.55 | 0.521474E+09 | 845.60 | 19-MAY-13:00 | 20.92 | 10.55 |
June | 0.100128E+11 | 12410.27 | 29-JUN-15:10 | 32.02 | 14.63 | 0.574726E+09 | 845.64 | 20-JUN-13:00 | 32.02 | 14.63 |
July | 0.118321E+11 | 13840.80 | 17-JUL-16:00 | 37.20 | 17.28 | 0.558141E+09 | 845.63 | 13-JUL-13:20 | 37.20 | 17.28 |
August | 0.103926E+11 | 13274.04 | 09-AUG-14:50 | 33.40 | 16.01 | 0.603515E+09 | 845.62 | 11-AUG-13:20 | 31.47 | 13.57 |
September | 0.635427E+10 | 13128.36 | 03-SEP-15:21 | 33.30 | 15.93 | 0.487929E+09 | 845.42 | 05-SEP-13:00 | 24.40 | 15.14 |
October | 0.287497E+10 | 7041.36 | 18-OCT-15:50 | 24.50 | 11.12 | 0.472920E+09 | 717.53 | 19-OCT-13:00 | 21.10 | 10.22 |
November | 0.903390E+09 | 5327.90 | 17-NOV-15:40 | 16.70 | 8.38 | 0.459807E+09 | 625.79 | 27-NOV-10:39 | -10.3 | -11.7 |
December | 0.195071E+09 | 5511.14 | 07-DEC-06:04 | -1.2 | -2.6 | 0.446700E+09 | 626.07 | 15-DEC-10:00 | -11.1 | -11.4 |
Annual Sum or Average | 0.540439E+11 | 0.597489E+10 | ||||||||
Minimum of Months | 65179595.39 | 4961.18 | -1.2 | -2.6 | 0.420979E+09 | 625.79 | -11.1 | -11.7 | ||
Maximum of Months | 0.118321E+11 | 13840.80 | 37.20 | 17.28 | 0.603515E+09 | 845.64 | 37.20 | 17.28 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171771E+09 | 3284.32 | 14-JAN-17:02 | 8.90 | 4.06 | 0.298510E+09 | 403.47 | 09-JAN-10:50 | 8.90 | 4.06 |
February | 0.968300E+09 | 4945.81 | 26-FEB-12:31 | 14.43 | 5.31 | 0.274240E+09 | 478.24 | 27-FEB-10:00 | 14.40 | 5.37 |
March | 0.233686E+10 | 7667.87 | 23-MAR-10:22 | 8.60 | 1.66 | 0.342030E+09 | 544.96 | 28-MAR-09:09 | 5.37 | 0.68 |
April | 0.399451E+10 | 11907.39 | 25-APR-09:33 | 11.27 | 5.45 | 0.327343E+09 | 544.96 | 24-APR-09:09 | 11.27 | 5.45 |
May | 0.611074E+10 | 14577.17 | 19-MAY-09:30 | 18.90 | 11.91 | 0.374407E+09 | 544.99 | 02-MAY-13:09 | 18.90 | 11.91 |
June | 0.100303E+11 | 31723.36 | 25-JUN-09:51 | 19.40 | 12.54 | 0.405711E+09 | 545.00 | 28-JUN-09:00 | 24.40 | 12.69 |
July | 0.122948E+11 | 36306.60 | 16-JUL-08:51 | 22.20 | 16.07 | 0.385705E+09 | 545.38 | 17-JUL-09:39 | 30.77 | 17.46 |
August | 0.108468E+11 | 33505.01 | 06-AUG-09:41 | 29.53 | 14.91 | 0.428524E+09 | 545.50 | 07-AUG-09:00 | 30.60 | 15.43 |
September | 0.611899E+10 | 31095.50 | 03-SEP-10:01 | 28.07 | 14.84 | 0.346300E+09 | 544.96 | 05-SEP-13:50 | 24.22 | 15.03 |
October | 0.327141E+10 | 8131.60 | 18-OCT-09:55 | 20.00 | 8.80 | 0.323759E+09 | 544.96 | 18-OCT-09:09 | 20.00 | 8.80 |
November | 0.120461E+10 | 4645.79 | 03-NOV-10:11 | 9.50 | 5.81 | 0.297808E+09 | 473.94 | 03-NOV-09:00 | 9.50 | 5.81 |
December | 0.283045E+09 | 3621.28 | 07-DEC-06:04 | -1.2 | -2.6 | 0.287952E+09 | 403.39 | 15-DEC-14:50 | -10.6 | -10.9 |
Annual Sum or Average | 0.576321E+11 | 0.409229E+10 | ||||||||
Minimum of Months | 0.171771E+09 | 3284.32 | -1.2 | -2.6 | 0.274240E+09 | 403.39 | -10.6 | -10.9 | ||
Maximum of Months | 0.122948E+11 | 36306.60 | 29.53 | 16.07 | 0.428524E+09 | 545.50 | 30.77 | 17.46 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258421E+10 | 15534.20 | 31-JAN-13:30 | -0.9 | -4.5 | 0.487044E+09 | 845.65 | 27-JAN-14:20 | -0.9 | -4.5 |
February | 0.497852E+10 | 52694.63 | 26-FEB-14:31 | 16.33 | 6.24 | 0.467967E+09 | 845.65 | 01-FEB-14:09 | 16.33 | 6.24 |
March | 0.662361E+10 | 24246.77 | 01-MAR-14:01 | 6.97 | 2.89 | 0.564009E+09 | 845.65 | 06-MAR-14:09 | 0.68 | -2.2 |
April | 0.693999E+10 | 22503.21 | 25-APR-13:34 | 16.30 | 6.98 | 0.504018E+09 | 845.65 | 13-APR-13:09 | 16.30 | 6.98 |
May | 0.874559E+10 | 20990.07 | 19-MAY-13:50 | 27.02 | 15.00 | 0.565394E+09 | 845.72 | 02-MAY-13:09 | 27.02 | 15.00 |
June | 0.124647E+11 | 20638.07 | 30-JUN-13:50 | 28.62 | 14.17 | 0.594046E+09 | 845.68 | 27-JUN-13:50 | 28.62 | 14.17 |
July | 0.157136E+11 | 52291.48 | 16-JUL-14:51 | 33.30 | 19.05 | 0.571335E+09 | 845.68 | 12-JUL-13:09 | 33.30 | 19.05 |
August | 0.168292E+11 | 48226.49 | 06-AUG-13:42 | 34.32 | 15.27 | 0.636261E+09 | 845.67 | 01-AUG-13:09 | 34.32 | 15.27 |
September | 0.128022E+11 | 58935.48 | 03-SEP-13:21 | 33.60 | 16.11 | 0.537075E+09 | 846.00 | 01-SEP-13:00 | 33.60 | 16.11 |
October | 0.928075E+10 | 49129.78 | 15-OCT-14:01 | 23.22 | 11.15 | 0.543887E+09 | 845.93 | 18-OCT-13:00 | 25.00 | 11.40 |
November | 0.549834E+10 | 24334.81 | 03-NOV-13:22 | 14.35 | 7.74 | 0.512958E+09 | 845.65 | 15-NOV-14:09 | 10.28 | 4.16 |
December | 0.303704E+10 | 13805.86 | 12-DEC-14:24 | -2.2 | -5.4 | 0.477164E+09 | 845.65 | 12-DEC-14:20 | -2.2 | -5.4 |
Annual Sum or Average | 0.105498E+12 | 0.646116E+10 | ||||||||
Minimum of Months | 0.258421E+10 | 13805.86 | -2.2 | -5.4 | 0.467967E+09 | 845.65 | -2.2 | -5.4 | ||
Maximum of Months | 0.168292E+11 | 58935.48 | 34.32 | 19.05 | 0.636261E+09 | 846.00 | 34.32 | 19.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.397206E+09 | 5107.18 | 13-JAN-15:40 | 9.27 | 4.85 | 0.299071E+09 | 437.50 | 13-JAN-15:50 | 9.08 | 4.76 |
February | 0.130188E+10 | 9157.61 | 28-FEB-16:33 | 10.37 | 4.49 | 0.278013E+09 | 521.19 | 24-FEB-16:00 | 10.37 | 4.49 |
March | 0.255008E+10 | 11858.36 | 28-MAR-16:52 | 10.60 | 2.97 | 0.337783E+09 | 539.22 | 02-MAR-14:00 | 10.60 | 2.97 |
April | 0.447185E+10 | 29140.78 | 22-APR-17:41 | 16.10 | 8.34 | 0.307732E+09 | 524.19 | 24-APR-13:00 | 17.80 | 9.82 |
May | 0.695913E+10 | 41362.40 | 28-MAY-18:01 | 19.82 | 10.31 | 0.348431E+09 | 544.95 | 19-MAY-13:00 | 19.82 | 10.31 |
June | 0.101237E+11 | 37329.50 | 18-JUN-17:11 | 25.40 | 14.50 | 0.372588E+09 | 544.96 | 20-JUN-13:00 | 28.90 | 18.82 |
July | 0.121772E+11 | 46493.26 | 16-JUL-17:31 | 32.97 | 17.02 | 0.360143E+09 | 544.95 | 13-JUL-13:20 | 32.97 | 17.02 |
August | 0.109630E+11 | 39376.16 | 06-AUG-16:21 | 35.30 | 16.02 | 0.393646E+09 | 544.95 | 11-AUG-13:20 | 31.47 | 13.57 |
September | 0.674883E+10 | 43952.60 | 04-SEP-16:41 | 32.80 | 16.72 | 0.324302E+09 | 544.96 | 05-SEP-13:00 | 24.40 | 15.14 |
October | 0.371069E+10 | 13812.69 | 18-OCT-16:00 | 24.40 | 11.02 | 0.318183E+09 | 532.00 | 18-OCT-13:00 | 24.40 | 11.02 |
November | 0.175458E+10 | 7001.52 | 03-NOV-15:23 | 14.45 | 7.69 | 0.304531E+09 | 521.19 | 03-NOV-15:00 | 14.30 | 7.69 |
December | 0.649226E+09 | 5453.00 | 06-DEC-15:40 | 9.97 | 4.80 | 0.289102E+09 | 457.77 | 06-DEC-15:50 | 9.68 | 4.65 |
Annual Sum or Average | 0.618075E+11 | 0.393353E+10 | ||||||||
Minimum of Months | 0.397206E+09 | 5107.18 | 9.27 | 2.97 | 0.278013E+09 | 437.50 | 9.08 | 2.97 | ||
Maximum of Months | 0.121772E+11 | 46493.26 | 35.30 | 17.02 | 0.393646E+09 | 544.96 | 32.97 | 18.82 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.295106E+10 | 20587.05 | 28-JAN-04:11 | -29.3 | -29.6 | 0.00 | 0.00 | 01-JAN-00:10 | -29.3 | -29.6 |
February | 0.251353E+10 | 19090.38 | 04-FEB-04:11 | -21.7 | -22.0 | 0.00 | 0.00 | 01-FEB-00:10 | -21.7 | -22.0 |
March | 0.461534E+10 | 16993.64 | 04-MAR-04:01 | -18.4 | -18.9 | 0.00 | 0.00 | 01-MAR-00:10 | -18.4 | -18.9 |
April | 0.599574E+10 | 10041.67 | 29-APR-05:01 | -7.7 | -8.6 | 0.00 | 0.00 | 01-APR-00:10 | -7.7 | -8.6 |
May | 0.602810E+10 | 11659.57 | 22-MAY-05:01 | -0.6 | -0.6 | 0.00 | 0.00 | 01-MAY-00:10 | -0.6 | -0.6 |
June | 0.897300E+10 | 9628.50 | 26-JUN-05:12 | 10.33 | 9.12 | 0.00 | 0.00 | 01-JUN-00:10 | 10.33 | 9.12 |
July | 0.110523E+11 | 10891.97 | 17-JUL-15:50 | 37.02 | 17.24 | 0.00 | 0.00 | 01-JUL-00:10 | 37.02 | 17.24 |
August | 0.116688E+11 | 11054.81 | 07-AUG-15:00 | 32.80 | 15.97 | 0.00 | 0.00 | 01-AUG-00:10 | 32.80 | 15.97 |
September | 0.796195E+10 | 11953.29 | 05-SEP-05:02 | 18.40 | 11.40 | 0.00 | 0.00 | 01-SEP-00:10 | 18.40 | 11.40 |
October | 0.623339E+10 | 10116.90 | 10-OCT-05:01 | -6.1 | -6.6 | 0.00 | 0.00 | 01-OCT-00:10 | -6.1 | -6.6 |
November | 0.464452E+10 | 15709.60 | 27-NOV-04:01 | -15.8 | -16.7 | 0.00 | 0.00 | 01-NOV-00:10 | -15.8 | -16.7 |
December | 0.359001E+10 | 16043.47 | 28-DEC-04:01 | -22.7 | -23.1 | 0.00 | 0.00 | 01-DEC-00:10 | -22.7 | -23.1 |
Annual Sum or Average | 0.762278E+11 | 0.00 | ||||||||
Minimum of Months | 0.251353E+10 | 9628.50 | -29.3 | -29.6 | 0.00 | 0.00 | -29.3 | -29.6 | ||
Maximum of Months | 0.116688E+11 | 20587.05 | 37.02 | 17.24 | 0.00 | 0.00 | 37.02 | 17.24 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214786E+10 | 21681.73 | 06-JAN-03:21 | -25.2 | -25.7 | 0.00 | 0.00 | 01-JAN-00:10 | -25.2 | -25.7 |
February | 0.172581E+10 | 21958.39 | 04-FEB-03:41 | -22.1 | -22.4 | 0.00 | 0.00 | 01-FEB-00:10 | -22.1 | -22.4 |
March | 0.305618E+10 | 23602.99 | 05-MAR-00:01 | -23.1 | -23.6 | 0.00 | 0.00 | 01-MAR-00:10 | -23.1 | -23.6 |
April | 0.381828E+10 | 18006.95 | 15-APR-04:01 | -0.1 | -3.1 | 0.00 | 0.00 | 01-APR-00:10 | -0.1 | -3.1 |
May | 0.438723E+10 | 18691.91 | 08-MAY-03:01 | -2.7 | -3.0 | 0.00 | 0.00 | 01-MAY-00:10 | -2.7 | -3.0 |
June | 0.743346E+10 | 12756.95 | 17-JUN-05:01 | 2.35 | 1.74 | 0.00 | 0.00 | 01-JUN-00:10 | 2.35 | 1.74 |
July | 0.884113E+10 | 10260.52 | 22-JUL-05:05 | 8.77 | 7.17 | 0.00 | 0.00 | 01-JUL-00:10 | 8.77 | 7.17 |
August | 0.896730E+10 | 10693.49 | 14-AUG-05:12 | 12.03 | 9.76 | 0.00 | 0.00 | 01-AUG-00:10 | 12.03 | 9.76 |
September | 0.629562E+10 | 14320.84 | 19-SEP-04:11 | 2.20 | 1.67 | 0.00 | 0.00 | 01-SEP-00:10 | 2.20 | 1.67 |
October | 0.409657E+10 | 17195.65 | 10-OCT-03:01 | -4.1 | -4.8 | 0.00 | 0.00 | 01-OCT-00:10 | -4.1 | -4.8 |
November | 0.316437E+10 | 22881.42 | 26-NOV-07:41 | -16.3 | -16.9 | 0.00 | 0.00 | 01-NOV-00:10 | -16.3 | -16.9 |
December | 0.288580E+10 | 20899.18 | 16-DEC-04:01 | -9.9 | -10.1 | 0.00 | 0.00 | 01-DEC-00:10 | -9.9 | -10.1 |
Annual Sum or Average | 0.568196E+11 | 0.00 | ||||||||
Minimum of Months | 0.172581E+10 | 10260.52 | -25.2 | -25.7 | 0.00 | 0.00 | -25.2 | -25.7 | ||
Maximum of Months | 0.896730E+10 | 23602.99 | 12.03 | 9.76 | 0.00 | 0.00 | 12.03 | 9.76 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9390169.86 | 1758.30 | 14-JAN-17:10 | 8.90 | 4.06 | 0.00 | 0.00 | 01-JAN-00:10 | 8.90 | 4.06 |
February | 0.585522E+09 | 9636.82 | 26-FEB-14:34 | 16.33 | 6.24 | 0.00 | 0.00 | 01-FEB-00:10 | 16.33 | 6.24 |
March | 0.265928E+10 | 11840.98 | 22-MAR-14:31 | 11.10 | 4.12 | 0.00 | 0.00 | 01-MAR-00:10 | 11.10 | 4.12 |
April | 0.586249E+10 | 20792.52 | 25-APR-14:42 | 16.85 | 7.33 | 0.00 | 0.00 | 01-APR-00:10 | 16.85 | 7.33 |
May | 0.107734E+11 | 30281.68 | 19-MAY-14:50 | 28.12 | 14.91 | 0.00 | 0.00 | 01-MAY-00:10 | 28.12 | 14.91 |
June | 0.181705E+11 | 34454.83 | 23-JUN-13:30 | 31.40 | 15.21 | 0.00 | 0.00 | 01-JUN-00:10 | 31.40 | 15.21 |
July | 0.227936E+11 | 39801.40 | 17-JUL-14:20 | 36.50 | 17.01 | 0.00 | 0.00 | 01-JUL-00:10 | 36.50 | 17.01 |
August | 0.193722E+11 | 36663.86 | 07-AUG-14:00 | 32.80 | 15.97 | 0.00 | 0.00 | 01-AUG-00:10 | 32.80 | 15.97 |
September | 0.102310E+11 | 27453.91 | 01-SEP-14:05 | 27.88 | 14.54 | 0.00 | 0.00 | 01-SEP-00:10 | 27.88 | 14.54 |
October | 0.370984E+10 | 17326.71 | 18-OCT-14:30 | 25.00 | 11.51 | 0.00 | 0.00 | 01-OCT-00:10 | 25.00 | 11.51 |
November | 0.606915E+09 | 6730.78 | 03-NOV-13:51 | 15.00 | 7.85 | 0.00 | 0.00 | 01-NOV-00:10 | 15.00 | 7.85 |
December | 10449164.53 | 1018.89 | 06-DEC-13:50 | 11.88 | 5.75 | 0.00 | 0.00 | 01-DEC-00:10 | 11.88 | 5.75 |
Annual Sum or Average | 0.947847E+11 | 0.00 | ||||||||
Minimum of Months | 9390169.86 | 1018.89 | 8.90 | 4.06 | 0.00 | 0.00 | 8.90 | 4.06 | ||
Maximum of Months | 0.227936E+11 | 39801.40 | 36.50 | 17.01 | 0.00 | 0.00 | 36.50 | 17.01 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173407E+10 | 5335.21 | 06-JAN-03:31 | -25.0 | -25.4 | 96931357.40 | 162.40 | 27-JAN-10:39 | -24.8 | -25.3 |
February | 0.640323E+10 | 11084.72 | 01-FEB-07:01 | -24.9 | -25.2 | 86436441.03 | 126.82 | 27-FEB-14:00 | 18.90 | 7.23 |
March | 0.127322E+11 | 6415.61 | 31-MAR-23:57 | 2.50 | 0.99 | 0.103236E+09 | 126.82 | 03-MAR-10:09 | 2.50 | 0.99 |
April | 0.182381E+11 | 8379.19 | 24-APR-18:10 | 17.33 | 7.36 | 91605084.98 | 126.82 | 07-APR-13:09 | 17.33 | 7.36 |
May | 0.396978E+10 | 3439.69 | 31-MAY-23:51 | 15.50 | 10.27 | 99233096.94 | 126.82 | 22-MAY-13:20 | 15.50 | 10.27 |
June | 0.908595E+10 | 5371.40 | 30-JUN-24:00 | 19.60 | 12.23 | 98957700.98 | 126.83 | 22-JUN-09:09 | 19.60 | 12.23 |
July | 0.148100E+11 | 7234.37 | 31-JUL-23:05 | 20.62 | 12.81 | 91880973.22 | 126.82 | 19-JUL-09:09 | 20.62 | 12.81 |
August | 0.198758E+11 | 8767.50 | 04-AUG-19:00 | 29.40 | 13.38 | 0.103237E+09 | 126.83 | 22-AUG-13:00 | 24.40 | 15.66 |
September | 0.409407E+10 | 3173.66 | 30-SEP-23:31 | 12.27 | 6.64 | 91605825.35 | 126.84 | 07-SEP-13:09 | 12.27 | 6.64 |
October | 0.857335E+10 | 4619.25 | 31-OCT-23:52 | 4.70 | 1.47 | 95230018.23 | 126.82 | 26-OCT-13:00 | 4.70 | 1.47 |
November | 0.126956E+11 | 6256.41 | 13-NOV-16:21 | 3.15 | -2.5 | 94300283.24 | 126.82 | 17-NOV-10:00 | 13.90 | 5.94 |
December | 0.173795E+11 | 13251.44 | 29-DEC-01:01 | -24.9 | -25.2 | 92731205.31 | 222.14 | 29-DEC-08:09 | -27.9 | -28.1 |
Annual Sum or Average | 0.129592E+12 | 0.114538E+10 | ||||||||
Minimum of Months | 0.173407E+10 | 3173.66 | -25.0 | -25.4 | 86436441.03 | 126.82 | -27.9 | -28.1 | ||
Maximum of Months | 0.198758E+11 | 13251.44 | 29.40 | 13.38 | 0.103237E+09 | 222.14 | 24.40 | 15.66 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.543664E+09 | 2577.57 | 27-JAN-10:32 | -24.8 | -25.3 | 95747740.72 | 144.87 | 27-JAN-10:39 | -24.8 | -25.3 |
February | 0.492249E+10 | 10603.72 | 01-FEB-07:01 | -24.9 | -25.2 | 86425077.49 | 126.82 | 27-FEB-14:00 | 18.90 | 7.23 |
March | 0.111998E+11 | 6219.18 | 28-MAR-17:42 | 9.18 | 2.32 | 0.103236E+09 | 126.82 | 03-MAR-10:09 | 9.18 | 2.32 |
April | 0.165410E+11 | 8075.58 | 25-APR-18:02 | 16.73 | 7.64 | 91605086.89 | 126.82 | 07-APR-13:09 | 16.73 | 7.64 |
May | 0.302456E+10 | 3220.69 | 31-MAY-23:31 | 15.70 | 10.35 | 99233103.56 | 126.82 | 22-MAY-13:20 | 15.70 | 10.35 |
June | 0.841354E+10 | 5231.65 | 30-JUN-23:40 | 19.90 | 12.27 | 98957727.84 | 126.83 | 21-JUN-13:00 | 19.90 | 12.27 |
July | 0.138917E+11 | 7020.06 | 31-JUL-23:50 | 19.48 | 11.61 | 91881000.61 | 126.82 | 19-JUL-09:09 | 19.48 | 11.61 |
August | 0.186259E+11 | 8449.46 | 04-AUG-19:00 | 29.40 | 13.38 | 0.103237E+09 | 126.83 | 22-AUG-13:09 | 23.07 | 14.90 |
September | 0.317961E+10 | 2702.09 | 30-SEP-23:11 | 12.73 | 7.02 | 91605836.93 | 126.84 | 07-SEP-13:00 | 12.73 | 7.02 |
October | 0.722755E+10 | 4333.56 | 18-OCT-17:00 | 21.70 | 10.27 | 95230018.25 | 126.82 | 26-OCT-13:00 | 11.70 | 4.93 |
November | 0.106937E+11 | 5829.17 | 03-NOV-15:51 | 14.30 | 7.69 | 94300283.24 | 126.82 | 17-NOV-10:00 | 13.90 | 5.94 |
December | 0.145428E+11 | 11878.62 | 29-DEC-01:01 | -24.9 | -25.2 | 92730812.11 | 222.14 | 29-DEC-08:09 | -27.9 | -28.1 |
Annual Sum or Average | 0.112806E+12 | 0.114419E+10 | ||||||||
Minimum of Months | 0.543664E+09 | 2577.57 | -24.9 | -25.3 | 86425077.49 | 126.82 | -27.9 | -28.1 | ||
Maximum of Months | 0.186259E+11 | 11878.62 | 29.40 | 13.38 | 0.103237E+09 | 222.14 | 23.07 | 14.90 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197278E+09 | 1600.97 | 13-JAN-16:25 | 8.35 | 4.30 | 93864729.01 | 134.95 | 09-JAN-14:00 | 8.35 | 4.30 |
February | 0.303402E+10 | 9246.42 | 01-FEB-07:01 | -24.9 | -25.2 | 86412534.02 | 126.82 | 27-FEB-14:00 | 18.90 | 7.23 |
March | 0.907628E+10 | 6159.83 | 28-MAR-17:42 | 9.18 | 2.32 | 0.103236E+09 | 126.82 | 03-MAR-10:09 | 9.18 | 2.32 |
April | 0.148798E+11 | 8152.30 | 25-APR-18:02 | 16.73 | 7.64 | 91605088.35 | 126.82 | 07-APR-13:09 | 16.73 | 7.64 |
May | 0.223192E+10 | 3017.07 | 31-MAY-23:12 | 15.90 | 10.43 | 99198514.81 | 127.42 | 01-MAY-09:09 | 15.90 | 10.43 |
June | 0.787733E+10 | 5170.32 | 30-JUN-23:20 | 20.20 | 12.29 | 98957713.39 | 126.83 | 21-JUN-09:00 | 20.20 | 12.29 |
July | 0.135611E+11 | 6947.92 | 31-JUL-23:20 | 20.33 | 12.51 | 91881033.89 | 126.82 | 19-JUL-09:09 | 20.33 | 12.51 |
August | 0.181854E+11 | 8592.92 | 04-AUG-19:00 | 29.40 | 13.38 | 0.103237E+09 | 126.83 | 22-AUG-13:00 | 24.40 | 15.66 |
September | 0.235374E+10 | 2844.26 | 04-SEP-17:42 | 31.88 | 16.41 | 91605702.51 | 126.84 | 07-SEP-13:00 | 21.10 | 18.47 |
October | 0.521191E+10 | 4385.58 | 18-OCT-17:00 | 21.70 | 10.27 | 95230022.15 | 126.82 | 26-OCT-13:00 | 11.70 | 4.93 |
November | 0.834607E+10 | 5706.40 | 03-NOV-15:51 | 14.30 | 7.69 | 94300283.24 | 126.82 | 17-NOV-10:00 | 13.90 | 5.94 |
December | 0.122122E+11 | 11612.20 | 29-DEC-09:41 | -24.6 | -24.9 | 92717303.60 | 222.14 | 29-DEC-08:09 | -24.6 | -24.9 |
Annual Sum or Average | 0.971671E+11 | 0.114225E+10 | ||||||||
Minimum of Months | 0.197278E+09 | 1600.97 | -24.9 | -25.2 | 86412534.02 | 126.82 | -24.6 | -24.9 | ||
Maximum of Months | 0.181854E+11 | 11612.20 | 31.88 | 16.41 | 0.103237E+09 | 222.14 | 24.40 | 18.47 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230331E+12 | 102591.70 | 24-JAN-05:11 | 9.03 | 3.15 | 0.209079E+10 | 2817.53 | 31-JAN-14:00 | -1.1 | -4.4 |
February | 0.437403E+12 | 505033.77 | 23-FEB-22:03 | -7.9 | -8.4 | 0.145586E+10 | 2616.13 | 16-FEB-14:39 | -7.9 | -8.4 |
March | 0.721212E+12 | 538422.54 | 01-MAR-00:02 | -3.0 | -4.1 | 0.165249E+10 | 2234.37 | 16-MAR-13:09 | 5.10 | -1.2 |
April | 0.941890E+12 | 514260.54 | 03-APR-13:40 | 12.93 | 5.08 | 0.166161E+10 | 2856.31 | 06-APR-13:00 | 20.60 | 9.94 |
May | 0.234399E+12 | 496036.94 | 31-MAY-23:55 | 15.50 | 10.27 | 0.217977E+10 | 2871.65 | 31-MAY-13:09 | 15.50 | 10.27 |
June | 0.471669E+12 | 506617.36 | 20-JUN-02:32 | 8.33 | 5.15 | 0.190613E+10 | 2875.10 | 05-JUN-13:09 | 8.33 | 5.15 |
July | 0.732328E+12 | 536603.76 | 15-JUL-04:02 | 13.22 | 9.95 | 0.191866E+10 | 2857.29 | 21-JUL-09:00 | 23.30 | 11.57 |
August | 0.978083E+12 | 534275.47 | 16-AUG-15:22 | 15.80 | 9.93 | 0.216621E+10 | 2856.81 | 15-AUG-09:09 | 15.80 | 9.93 |
September | 0.233691E+12 | 493960.53 | 30-SEP-23:12 | 12.73 | 7.02 | 0.199878E+10 | 2871.07 | 21-SEP-13:09 | 12.73 | 7.02 |
October | 0.494336E+12 | 520849.93 | 31-OCT-23:32 | 4.10 | 0.90 | 0.170881E+10 | 2864.48 | 16-OCT-13:09 | 4.10 | 0.90 |
November | 0.703474E+12 | 535368.15 | 03-NOV-13:32 | 14.57 | 7.78 | 0.159357E+10 | 2541.40 | 17-NOV-16:00 | 17.20 | 8.89 |
December | 0.981471E+12 | 498729.46 | 19-DEC-09:32 | 5.20 | 2.35 | 0.159596E+10 | 2718.94 | 07-DEC-10:09 | 5.20 | 2.35 |
Annual Sum or Average | 0.716029E+13 | 0.219286E+11 | ||||||||
Minimum of Months | 0.230331E+12 | 102591.70 | -7.9 | -8.4 | 0.145586E+10 | 2234.37 | -7.9 | -8.4 | ||
Maximum of Months | 0.981471E+12 | 538422.54 | 15.80 | 10.27 | 0.217977E+10 | 2875.10 | 23.30 | 11.57 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 84743546.66 | 3549.03 | 18-JAN-06:55 | -10.0 |
February | 79536839.50 | 3168.23 | 22-FEB-06:11 | -4.2 |
March | 93704980.37 | 3059.95 | 31-MAR-05:03 | -2.8 |
April | 68676692.46 | 3313.78 | 21-APR-05:05 | 2.20 |
May | 95056824.21 | 8811.95 | 20-MAY-16:03 | 29.82 |
June | 0.107013E+09 | 7180.87 | 24-JUN-16:01 | 28.22 |
July | 0.101808E+09 | 13070.85 | 15-JUL-16:01 | 32.80 |
August | 0.116904E+09 | 16085.90 | 05-AUG-16:01 | 35.22 |
September | 0.112306E+09 | 14321.09 | 02-SEP-16:02 | 33.98 |
October | 86969068.68 | 2906.20 | 10-OCT-05:04 | -6.1 |
November | 88637164.23 | 3030.82 | 28-NOV-06:03 | -5.1 |
December | 67420300.58 | 2970.66 | 16-DEC-06:04 | -9.3 |
Annual Sum or Average | 0.110278E+10 | |||
Minimum of Months | 67420300.58 | 2906.20 | -10.0 | |
Maximum of Months | 0.116904E+09 | 16085.90 | 35.22 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9599135.14 | 19419.80 | 09-JAN-06:01 | -27.2 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:02 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -2.1 |
Annual Sum or Average | 9599135.14 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 9599135.14 | 19419.80 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.700105E+09 | 60986.34 | 09-JAN-05:01 | -27.2 |
February | 0.158394E+09 | 53013.27 | 06-FEB-05:01 | -0.4 |
March | 0.107523E+09 | 58790.62 | 06-MAR-05:01 | -18.4 |
April | 0.00 | 0.00 | 01-APR-00:02 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 |
November | 61413175.97 | 55386.48 | 27-NOV-05:01 | -15.4 |
December | 0.251437E+09 | 60186.04 | 26-DEC-05:01 | -7.3 |
Annual Sum or Average | 0.127887E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.700105E+09 | 60986.34 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130581E+11 | 133442.67 | 09-JAN-04:01 | -27.2 |
February | 0.593516E+10 | 130742.96 | 06-FEB-00:01 | -4.8 |
March | 0.415721E+10 | 131071.46 | 06-MAR-04:11 | -18.5 |
April | 0.784707E+09 | 110249.70 | 29-APR-04:01 | -7.8 |
May | 0.116605E+10 | 120371.34 | 08-MAY-03:01 | -2.7 |
June | 8479872.61 | 91612.07 | 17-JUN-05:01 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 2055858.71 | 27411.45 | 18-AUG-05:01 | 7.30 |
September | 0.110039E+09 | 94391.69 | 19-SEP-05:01 | 2.20 |
October | 0.116662E+10 | 121372.17 | 10-OCT-03:01 | -4.1 |
November | 0.429960E+10 | 130753.67 | 27-NOV-03:51 | -15.8 |
December | 0.838178E+10 | 130051.49 | 26-DEC-04:11 | -6.5 |
Annual Sum or Average | 0.390698E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.130581E+11 | 133442.67 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.477300E+10 | 23372.29 | 29-JAN-06:01 | -30.5 |
February | 0.183192E+10 | 22346.10 | 04-FEB-04:11 | -21.7 |
March | 0.702945E+09 | 22539.80 | 06-MAR-04:01 | -18.4 |
April | 26466431.21 | 18447.89 | 29-APR-05:01 | -7.7 |
May | 41897536.61 | 18261.73 | 08-MAY-05:01 | -2.8 |
June | 29449.88 | 490.83 | 16-JUN-05:02 | 3.22 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 74529.17 | 809.89 | 18-SEP-05:01 | 3.80 |
October | 18387281.55 | 18494.14 | 10-OCT-05:01 | -6.1 |
November | 0.305782E+09 | 21567.18 | 27-NOV-04:01 | -15.8 |
December | 0.153757E+10 | 23399.77 | 31-DEC-08:11 | -27.4 |
Annual Sum or Average | 0.923808E+10 | |||
Minimum of Months | 0.00 | 0.00 | -30.5 | |
Maximum of Months | 0.477300E+10 | 23399.77 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.307507E+10 | 21602.98 | 28-JAN-04:11 | -29.3 |
February | 0.121126E+10 | 20578.93 | 04-FEB-04:11 | -21.7 |
March | 0.514046E+09 | 20691.34 | 06-MAR-04:31 | -18.7 |
April | 38608677.54 | 16277.80 | 29-APR-05:01 | -7.7 |
May | 37816033.67 | 14787.02 | 08-MAY-05:01 | -2.8 |
June | 325501.16 | 4562.36 | 16-JUN-05:01 | 3.22 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 1065842.63 | 5101.98 | 18-SEP-05:01 | 3.80 |
October | 24580379.21 | 15997.35 | 10-OCT-05:01 | -6.1 |
November | 0.264888E+09 | 19795.88 | 27-NOV-04:01 | -15.8 |
December | 0.125348E+10 | 22015.12 | 31-DEC-07:31 | -28.0 |
Annual Sum or Average | 0.642113E+10 | |||
Minimum of Months | 0.00 | 0.00 | -29.3 | |
Maximum of Months | 0.307507E+10 | 22015.12 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.451188E+10 | 31020.87 | 28-JAN-04:11 | -29.3 |
February | 0.177035E+10 | 30959.03 | 05-FEB-05:41 | -20.0 |
March | 0.997964E+09 | 30931.70 | 06-MAR-03:51 | -18.3 |
April | 0.127940E+09 | 25140.45 | 29-APR-04:01 | -7.8 |
May | 0.165233E+09 | 24105.00 | 08-MAY-04:01 | -2.3 |
June | 2162124.71 | 12817.77 | 17-JUN-05:01 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 135063.34 | 1800.84 | 18-AUG-05:01 | 7.30 |
September | 11897166.14 | 17358.75 | 19-SEP-05:01 | 2.20 |
October | 0.104980E+09 | 24822.98 | 10-OCT-04:41 | -5.9 |
November | 0.567223E+09 | 29915.40 | 27-NOV-04:01 | -15.8 |
December | 0.186693E+10 | 31668.99 | 31-DEC-07:31 | -28.0 |
Annual Sum or Average | 0.101267E+11 | |||
Minimum of Months | 0.00 | 0.00 | -29.3 | |
Maximum of Months | 0.451188E+10 | 31668.99 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166504E+10 | 21342.74 | 11-JAN-04:11 | -28.9 |
February | 0.514178E+09 | 18958.83 | 04-FEB-04:11 | -21.7 |
March | 0.169110E+09 | 20640.79 | 06-MAR-04:01 | -18.4 |
April | 2039229.62 | 15915.00 | 29-APR-05:01 | -7.7 |
May | 8665482.66 | 14135.41 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 138790.43 | 2313.17 | 19-SEP-05:03 | 2.20 |
October | 3240609.39 | 15710.78 | 10-OCT-05:01 | -6.1 |
November | 65908737.48 | 18688.36 | 27-NOV-05:01 | -15.4 |
December | 0.198320E+09 | 18597.63 | 30-DEC-05:01 | -20.6 |
Annual Sum or Average | 0.262664E+10 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.166504E+10 | 21342.74 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114442E+11 | 33911.30 | 09-JAN-04:01 | -27.2 |
February | 0.536703E+10 | 32558.26 | 05-FEB-06:01 | -20.0 |
March | 0.315214E+10 | 33128.97 | 06-MAR-04:11 | -18.5 |
April | 0.716884E+09 | 26832.29 | 29-APR-04:21 | -7.8 |
May | 0.529590E+09 | 28057.66 | 08-MAY-03:01 | -2.7 |
June | 15886532.75 | 21126.83 | 17-JUN-05:01 | 2.35 |
July | 110350.15 | 1471.21 | 05-JUL-05:03 | 9.40 |
August | 4140495.26 | 16863.41 | 18-AUG-05:01 | 7.30 |
September | 0.163786E+09 | 23394.50 | 19-SEP-04:11 | 2.20 |
October | 0.616477E+09 | 28527.86 | 10-OCT-03:41 | -4.8 |
November | 0.298846E+10 | 32928.98 | 27-NOV-03:01 | -15.9 |
December | 0.731322E+10 | 33768.36 | 31-DEC-07:51 | -27.8 |
Annual Sum or Average | 0.323119E+11 | |||
Minimum of Months | 110350.15 | 1471.21 | -27.8 | |
Maximum of Months | 0.114442E+11 | 33911.30 | 9.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.664390E+10 | 27447.61 | 09-JAN-04:01 | -27.2 |
February | 0.302649E+10 | 26540.03 | 05-FEB-04:41 | -20.0 |
March | 0.178104E+10 | 26869.64 | 06-MAR-03:31 | -18.5 |
April | 0.381713E+09 | 21375.94 | 29-APR-04:21 | -7.8 |
May | 0.311685E+09 | 21066.66 | 08-MAY-03:01 | -2.7 |
June | 11211637.40 | 14791.12 | 17-JUN-05:01 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 2741350.67 | 12074.50 | 18-AUG-05:01 | 7.30 |
September | 87649464.38 | 17285.07 | 19-SEP-04:11 | 2.20 |
October | 0.349890E+09 | 21759.23 | 10-OCT-03:41 | -4.8 |
November | 0.174268E+10 | 26740.63 | 27-NOV-02:21 | -16.0 |
December | 0.429574E+10 | 27548.96 | 31-DEC-07:51 | -27.8 |
Annual Sum or Average | 0.186347E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.8 | |
Maximum of Months | 0.664390E+10 | 27548.96 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.800359E+10 | 34911.46 | 09-JAN-04:01 | -27.2 |
February | 0.334036E+10 | 33858.17 | 05-FEB-06:01 | -20.0 |
March | 0.228988E+10 | 34322.06 | 06-MAR-04:11 | -18.5 |
April | 0.590367E+09 | 27807.75 | 29-APR-04:21 | -7.8 |
May | 0.537144E+09 | 28601.08 | 08-MAY-03:01 | -2.7 |
June | 23996782.78 | 22044.07 | 17-JUN-05:01 | 2.35 |
July | 302825.34 | 3960.81 | 08-JUL-05:01 | 6.23 |
August | 5957332.43 | 17354.05 | 18-AUG-05:01 | 7.30 |
September | 0.106404E+09 | 23744.63 | 19-SEP-04:11 | 2.20 |
October | 0.389692E+09 | 29500.38 | 10-OCT-03:41 | -4.8 |
November | 0.194005E+10 | 34067.84 | 27-NOV-03:41 | -15.8 |
December | 0.490894E+10 | 35177.91 | 31-DEC-07:51 | -27.8 |
Annual Sum or Average | 0.221367E+11 | |||
Minimum of Months | 302825.34 | 3960.81 | -27.8 | |
Maximum of Months | 0.800359E+10 | 35177.91 | 7.30 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.625533E+10 | 28341.19 | 09-JAN-04:01 | -27.2 |
February | 0.266114E+10 | 27243.12 | 05-FEB-00:01 | -19.9 |
March | 0.159999E+10 | 27835.49 | 06-MAR-03:31 | -18.5 |
April | 0.317314E+09 | 21858.81 | 29-APR-04:21 | -7.8 |
May | 0.268247E+09 | 21021.89 | 08-MAY-05:01 | -2.8 |
June | 7729021.25 | 16040.77 | 17-JUN-05:01 | 2.35 |
July | 21841.32 | 219.52 | 08-JUL-05:03 | 6.23 |
August | 3415113.26 | 12059.87 | 18-AUG-05:01 | 7.30 |
September | 72368356.41 | 17757.93 | 19-SEP-04:11 | 2.20 |
October | 0.293976E+09 | 22358.67 | 10-OCT-03:41 | -4.8 |
November | 0.145085E+10 | 27656.18 | 27-NOV-03:41 | -15.8 |
December | 0.364821E+10 | 28161.66 | 31-DEC-07:11 | -28.1 |
Annual Sum or Average | 0.165786E+11 | |||
Minimum of Months | 21841.32 | 219.52 | -28.1 | |
Maximum of Months | 0.625533E+10 | 28341.19 | 7.30 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.192315E+11 | 46593.40 | 09-JAN-04:01 | -27.2 |
February | 0.107073E+11 | 44705.15 | 05-FEB-06:01 | -20.0 |
March | 0.766745E+10 | 45659.95 | 06-MAR-04:11 | -18.5 |
April | 0.271211E+10 | 39382.39 | 29-APR-03:01 | -6.9 |
May | 0.201695E+10 | 38507.39 | 08-MAY-04:11 | -2.4 |
June | 0.195771E+09 | 30733.95 | 17-JUN-04:11 | 2.03 |
July | 20016428.59 | 25180.32 | 08-JUL-04:11 | 5.60 |
August | 94992534.31 | 27754.76 | 18-AUG-04:11 | 7.20 |
September | 0.908988E+09 | 34976.76 | 19-SEP-04:11 | 2.20 |
October | 0.279399E+10 | 40915.15 | 10-OCT-03:21 | -4.5 |
November | 0.782046E+10 | 45498.32 | 27-NOV-03:51 | -15.8 |
December | 0.146368E+11 | 46582.18 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.688063E+11 | |||
Minimum of Months | 20016428.59 | 25180.32 | -27.6 | |
Maximum of Months | 0.192315E+11 | 46593.40 | 7.20 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115128E+11 | 30788.58 | 09-JAN-04:01 | -27.2 |
February | 0.611462E+10 | 29633.45 | 05-FEB-06:01 | -20.0 |
March | 0.436569E+10 | 30146.76 | 06-MAR-04:11 | -18.5 |
April | 0.142302E+10 | 25987.68 | 29-APR-03:01 | -6.9 |
May | 0.113706E+10 | 25370.50 | 08-MAY-04:11 | -2.4 |
June | 0.100153E+09 | 20416.79 | 17-JUN-04:11 | 2.03 |
July | 10787501.17 | 16801.09 | 08-JUL-04:11 | 5.60 |
August | 46623653.10 | 18392.01 | 18-AUG-04:11 | 7.20 |
September | 0.473113E+09 | 23009.09 | 19-SEP-04:11 | 2.20 |
October | 0.153331E+10 | 26993.65 | 10-OCT-03:21 | -4.5 |
November | 0.449201E+10 | 30033.67 | 27-NOV-03:51 | -15.8 |
December | 0.882546E+10 | 30798.60 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.400346E+11 | |||
Minimum of Months | 10787501.17 | 16801.09 | -27.6 | |
Maximum of Months | 0.115128E+11 | 30798.60 | 7.20 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144720E+11 | 47077.03 | 09-JAN-04:01 | -27.2 |
February | 0.733656E+10 | 45476.40 | 05-FEB-06:01 | -20.0 |
March | 0.590841E+10 | 46331.30 | 06-MAR-04:11 | -18.5 |
April | 0.231173E+10 | 40010.18 | 29-APR-03:01 | -6.9 |
May | 0.198978E+10 | 39038.71 | 08-MAY-04:11 | -2.4 |
June | 0.280366E+09 | 31350.19 | 17-JUN-04:11 | 2.03 |
July | 29263084.54 | 25876.57 | 08-JUL-04:51 | 5.60 |
August | 92120985.93 | 28251.06 | 18-AUG-04:11 | 7.20 |
September | 0.688612E+09 | 35172.02 | 19-SEP-04:11 | 2.20 |
October | 0.198552E+10 | 41481.81 | 10-OCT-03:21 | -4.5 |
November | 0.536902E+10 | 46121.75 | 27-NOV-03:51 | -15.8 |
December | 0.107580E+11 | 47450.35 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.512214E+11 | |||
Minimum of Months | 29263084.54 | 25876.57 | -27.6 | |
Maximum of Months | 0.144720E+11 | 47450.35 | 7.20 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105787E+11 | 35098.38 | 09-JAN-04:01 | -27.2 |
February | 0.514357E+10 | 33426.38 | 05-FEB-06:01 | -20.0 |
March | 0.365481E+10 | 34191.95 | 06-MAR-04:11 | -18.5 |
April | 0.112814E+10 | 28339.53 | 29-APR-03:01 | -6.9 |
May | 0.956855E+09 | 27298.13 | 08-MAY-04:11 | -2.4 |
June | 0.112769E+09 | 21277.13 | 17-JUN-04:11 | 2.03 |
July | 4677232.08 | 16860.62 | 08-JUL-05:01 | 6.23 |
August | 40819505.54 | 19144.06 | 18-AUG-04:11 | 7.20 |
September | 0.386264E+09 | 24213.62 | 19-SEP-04:11 | 2.20 |
October | 0.120141E+10 | 29410.84 | 10-OCT-04:01 | -5.2 |
November | 0.361345E+10 | 34093.70 | 27-NOV-03:51 | -15.8 |
December | 0.729644E+10 | 34692.87 | 31-DEC-07:21 | -28.1 |
Annual Sum or Average | 0.341179E+11 | |||
Minimum of Months | 4677232.08 | 16860.62 | -28.1 | |
Maximum of Months | 0.105787E+11 | 35098.38 | 7.20 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139855E+10 | 9162.81 | 15-JAN-13:32 | 5.40 |
February | 0.483355E+09 | 13439.44 | 26-FEB-16:11 | 15.93 |
March | 0.255671E+09 | 10438.29 | 26-MAR-11:24 | 6.95 |
April | 57453926.20 | 12804.54 | 16-APR-16:31 | 20.00 |
May | 38480093.17 | 10071.05 | 28-MAY-16:52 | 21.10 |
June | 45040641.15 | 10463.24 | 18-JUN-16:52 | 25.60 |
July | 92220978.85 | 14259.65 | 16-JUL-15:01 | 33.22 |
August | 79789259.13 | 17291.66 | 06-AUG-16:01 | 35.50 |
September | 59603580.75 | 14176.45 | 04-SEP-15:31 | 32.60 |
October | 40271790.32 | 10935.59 | 15-OCT-14:22 | 23.05 |
November | 27080082.73 | 11838.25 | 24-NOV-05:11 | 12.20 |
December | 58767899.69 | 11359.14 | 06-DEC-06:01 | 7.02 |
Annual Sum or Average | 0.263629E+10 | |||
Minimum of Months | 27080082.73 | 9162.81 | 5.40 | |
Maximum of Months | 0.139855E+10 | 17291.66 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.507018E+10 | 18482.03 | 09-JAN-06:05 | -27.2 |
February | 0.204981E+10 | 16084.67 | 06-FEB-06:05 | 0.60 |
March | 0.103452E+10 | 12611.65 | 06-MAR-11:01 | -4.0 |
April | 51039013.69 | 12654.50 | 16-APR-17:01 | 19.90 |
May | 0.222258E+09 | 10204.73 | 28-MAY-17:21 | 20.55 |
June | 35716130.81 | 10814.04 | 18-JUN-17:11 | 25.40 |
July | 62714783.19 | 13636.04 | 16-JUL-15:51 | 32.80 |
August | 40877357.72 | 16996.33 | 06-AUG-16:11 | 35.40 |
September | 50287662.30 | 14966.78 | 04-SEP-15:51 | 32.80 |
October | 0.162361E+09 | 12619.68 | 15-OCT-14:01 | 23.22 |
November | 0.118053E+10 | 11035.10 | 27-NOV-06:03 | -14.5 |
December | 0.255996E+10 | 15628.75 | 26-DEC-06:04 | -7.9 |
Annual Sum or Average | 0.125203E+11 | |||
Minimum of Months | 35716130.81 | 10204.73 | -27.2 | |
Maximum of Months | 0.507018E+10 | 18482.03 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362150E+11 | 70527.39 | 28-JAN-05:11 | -27.2 |
February | 0.205988E+11 | 58011.70 | 01-FEB-05:21 | -25.0 |
March | 0.158287E+11 | 61017.60 | 06-MAR-05:05 | -18.4 |
April | 0.676593E+10 | 38875.87 | 29-APR-05:02 | -7.7 |
May | 0.492114E+10 | 44275.27 | 08-MAY-04:22 | -2.5 |
June | 0.117487E+10 | 40256.29 | 29-JUN-05:01 | 8.35 |
July | 0.457599E+09 | 37027.25 | 21-JUL-05:01 | 11.75 |
August | 0.885361E+09 | 31614.81 | 01-AUG-05:01 | 12.30 |
September | 0.276932E+10 | 27676.17 | 20-SEP-05:01 | 3.30 |
October | 0.704766E+10 | 40477.60 | 10-OCT-05:01 | -6.1 |
November | 0.161376E+11 | 60888.83 | 27-NOV-05:15 | -15.3 |
December | 0.288625E+11 | 61334.97 | 29-DEC-06:04 | -25.1 |
Annual Sum or Average | 0.141665E+12 | |||
Minimum of Months | 0.457599E+09 | 27676.17 | -27.2 | |
Maximum of Months | 0.362150E+11 | 70527.39 | 12.30 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.563938E+09 | 1691.38 | 06-JAN-03:33 | -25.0 |
February | 16501041.63 | 1720.21 | 01-FEB-04:02 | -25.0 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:02 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4.98 |
December | 41498492.96 | 2389.30 | 29-DEC-05:02 | -25.0 |
Annual Sum or Average | 0.621938E+09 | |||
Minimum of Months | 0.00 | 0.00 | -25.0 | |
Maximum of Months | 0.563938E+09 | 2389.30 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128763E+10 | 1544.73 | 06-JAN-03:33 | -25.0 |
February | 16026000.70 | 1546.00 | 01-FEB-04:02 | -25.0 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:02 | 2.68 |
May | 27302948.68 | 582.22 | 08-MAY-03:55 | -2.2 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4.98 |
December | 40415125.40 | 1938.00 | 29-DEC-05:02 | -25.0 |
Annual Sum or Average | 0.137137E+10 | |||
Minimum of Months | 0.00 | 0.00 | -25.0 | |
Maximum of Months | 0.128763E+10 | 1938.00 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225075E+10 | 1609.32 | 29-JAN-17:50 | -21.9 |
February | 0.185671E+09 | 1533.10 | 01-FEB-04:02 | -25.0 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -3.0 |
April | 5507588.93 | 1550.58 | 30-APR-23:40 | -1.2 |
May | 0.389743E+09 | 1534.03 | 01-MAY-00:20 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.184248E+09 | 1492.71 | 17-SEP-06:53 | 2.20 |
October | 15010921.11 | 1195.51 | 09-OCT-09:53 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4.98 |
December | 42929716.13 | 1753.52 | 29-DEC-05:02 | -25.0 |
Annual Sum or Average | 0.307386E+10 | |||
Minimum of Months | 0.00 | 0.00 | -25.0 | |
Maximum of Months | 0.225075E+10 | 1753.52 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.38 |
February | 0.270438E+10 | 23387.33 | 05-FEB-22:31 | -12.2 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:02 | 2.68 |
May | 653322.34 | 3379.75 | 31-MAY-23:04 | 16.00 |
June | 0.870269E+09 | 39628.50 | 25-JUN-07:41 | 15.32 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 3632322.67 | 19663.22 | 30-SEP-23:31 | 12.27 |
October | 0.178878E+10 | 29021.35 | 01-OCT-14:21 | 9.45 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -2.1 |
Annual Sum or Average | 0.536772E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.270438E+10 | 39628.50 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.278508E+11 | 29144.79 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.252627E+11 | 29144.79 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.300191E+11 | 29144.79 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.268132E+11 | 29144.79 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.289349E+11 | 29144.79 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.287951E+11 | 29144.79 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.269531E+11 | 29144.79 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.300191E+11 | 29144.79 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.268132E+11 | 29144.79 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.278508E+11 | 29144.79 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.275243E+11 | 29144.79 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.269531E+11 | 29144.79 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.333789E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.252627E+11 | 29144.79 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.300191E+11 | 29144.79 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.785272E+10 | 8217.58 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.712300E+10 | 8217.58 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.846411E+10 | 8217.58 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.756018E+10 | 8217.58 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.815842E+10 | 8217.58 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.811897E+10 | 8217.58 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.759962E+10 | 8217.58 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.846411E+10 | 8217.58 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.756018E+10 | 8217.58 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.785272E+10 | 8217.58 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.776069E+10 | 8217.58 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.759962E+10 | 8217.58 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.941143E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.712300E+10 | 8217.58 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.846411E+10 | 8217.58 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.289349E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.287951E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.275243E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.333789E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148502E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115442E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104774E+10 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758168E+09 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2069981.69 | 0.742485E+09 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10026324.11 | 0.368203E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36147527.17 | 0.244147E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28871836.67 | 0.272222E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19907856.79 | 0.490073E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 307564.55 | 0.733424E+09 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105624E+10 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134972E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97331090.97 | 0.970186E+10 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244147E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36147527.17 | 0.148502E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.989921E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776359E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700233E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500722E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1816221.21 | 0.485735E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7390783.02 | 0.240404E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25677294.23 | 0.156897E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20279823.59 | 0.170298E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13494378.40 | 0.324206E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 251775.74 | 0.489368E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697306E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.891817E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68910276.20 | 0.642327E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156897E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25677294.23 | 0.989921E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149614E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119369E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106300E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.756378E+09 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2084492.87 | 0.725488E+09 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10015247.97 | 0.355696E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34415038.11 | 0.235196E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27955846.31 | 0.266130E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16303904.15 | 0.492889E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107814.71 | 0.751505E+09 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106293E+10 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136350E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90882344.13 | 0.976255E+10 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235196E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34415038.11 | 0.149614E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101523E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808941E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733031E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558273E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1378599.69 | 0.527268E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6282491.68 | 0.262890E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22153795.63 | 0.188011E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18139479.72 | 0.207233E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13189332.93 | 0.344870E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 124506.83 | 0.516093E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743913E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.960459E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61268206.48 | 0.686621E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188011E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22153795.63 | 0.101523E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322728E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245148E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226006E+10 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156909E+10 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5816408.71 | 0.156246E+10 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27169167.65 | 0.781873E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99597011.29 | 0.512798E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72568225.04 | 0.565489E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58427422.32 | 0.101393E+10 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5215091.02 | 0.147832E+10 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218992E+10 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281883E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268793E+09 | 0.204315E+11 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512798E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99597011.29 | 0.322728E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216293E+10 |
February | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168094E+10 |
March | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155170E+10 |
April | 0.688021E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109985E+10 |
May | 0.744847E+09 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3663313.56 | 0.106241E+10 |
June | 0.742030E+09 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16394618.01 | 0.541994E+09 |
July | 0.690839E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56580772.19 | 0.363197E+09 |
August | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44555271.42 | 0.395033E+09 |
September | 0.688021E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31349163.81 | 0.715892E+09 |
October | 0.715730E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1090121.71 | 0.104051E+10 |
November | 0.708685E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148365E+10 |
December | 0.690839E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189209E+10 |
Annual Sum or Average | 0.858171E+10 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153633E+09 | 0.139902E+11 |
Minimum of Months | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363197E+09 |
Maximum of Months | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56580772.19 | 0.216293E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336418E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270076E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241514E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169593E+10 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4252141.24 | 0.162435E+10 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22715408.73 | 0.802330E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78298173.81 | 0.535841E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63488662.01 | 0.606580E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36487924.94 | 0.111369E+10 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 212461.40 | 0.168829E+10 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235589E+10 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298417E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205455E+09 | 0.218872E+11 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535841E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78298173.81 | 0.336418E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217878E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170225E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156380E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112807E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3218505.64 | 0.111864E+10 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15907862.91 | 0.560753E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57441538.86 | 0.388588E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44794945.19 | 0.408186E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33604907.68 | 0.719060E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1231088.91 | 0.104442E+10 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150356E+10 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191550E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156199E+09 | 0.142316E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388588E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57441538.86 | 0.217878E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394257E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287667E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265752E+10 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22805.05 | 0.176883E+10 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8512609.86 | 0.179615E+10 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36577393.31 | 0.891815E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133001E+09 | 0.578836E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95610785.29 | 0.640658E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78499473.92 | 0.113970E+10 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11439924.19 | 0.159870E+10 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252282E+10 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339690E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363664E+09 | 0.238112E+11 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578836E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133001E+09 | 0.394257E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263270E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195021E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180536E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124437E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4349614.37 | 0.122970E+10 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19447505.51 | 0.637871E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68543341.61 | 0.426931E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53682085.24 | 0.463421E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37960013.04 | 0.811288E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2653496.84 | 0.111994E+10 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169259E+10 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226968E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186636E+09 | 0.162841E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426931E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68543341.61 | 0.263270E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403001E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310809E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281548E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191588E+10 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5507081.59 | 0.187188E+10 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28588468.09 | 0.924232E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104268E+09 | 0.609924E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80395410.81 | 0.697717E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47146867.06 | 0.126163E+10 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 222946.58 | 0.185126E+10 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266814E+10 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351074E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266129E+09 | 0.252650E+11 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609924E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104268E+09 | 0.403001E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264907E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199492E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184685E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130004E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3883833.90 | 0.130996E+10 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19285981.54 | 0.663777E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71145431.37 | 0.458740E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55165719.08 | 0.482729E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41157840.28 | 0.834534E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2324140.95 | 0.117071E+10 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174434E+10 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230031E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192963E+09 | 0.167560E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458740E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71145431.37 | 0.264907E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.785272E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.712300E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.846411E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.756018E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.815842E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.811897E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.759962E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.846411E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.756018E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.785272E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.776069E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.759962E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.941143E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.712300E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.846411E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326636E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258584E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233072E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169151E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3115654.02 | 0.164149E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15718378.69 | 0.806115E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61517982.78 | 0.539988E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51194416.70 | 0.606125E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34757181.94 | 0.110417E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80297.28 | 0.165762E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237828E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303127E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166384E+09 | 0.216395E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539988E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61517982.78 | 0.326636E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548545E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440276E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402044E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288755E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5954197.86 | 0.283062E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29812687.85 | 0.140595E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118691E+09 | 0.931260E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94638445.74 | 0.104442E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68682535.01 | 0.190767E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245709.95 | 0.280972E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397915E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498321E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318025E+09 | 0.366882E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.931260E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118691E+09 | 0.548545E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560323E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427155E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399998E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279711E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2632828.32 | 0.283259E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18506551.35 | 0.144160E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93448324.94 | 0.919999E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83375914.51 | 0.102804E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58211344.93 | 0.181092E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251285E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372050E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487402E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256175E+09 | 0.358124E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.919999E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93448324.94 | 0.560323E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 29144.79 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 29144.79 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 29144.79 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 29144.79 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 29144.79 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 29144.79 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 29144.79 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 29144.79 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 29144.79 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 29144.79 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 29144.79 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 29144.79 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2506.17 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1475.09 | 17-FEB-03:51 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1820.87 | 02-MAR-22:51 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 1291.60 | 27-APR-01:55 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.80 | 20-MAY-17:01 | 2430.48 | 22-MAY-03:51 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.66 | 24-JUN-17:10 | 1025.05 | 14-JUN-01:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 324.08 | 30-JUL-12:10 | 611.66 | 05-JUL-00:51 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.14 | 06-AUG-17:31 | 784.83 | 23-AUG-02:53 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 434.34 | 03-SEP-13:00 | 1372.89 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.17 | 15-OCT-13:50 | 1177.13 | 30-OCT-21:51 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1505.89 | 28-NOV-05:59 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2200.76 | 01-DEC-04:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 611.66 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 434.34 | 2506.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1670.47 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 970.54 | 17-FEB-03:51 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1204.49 | 02-MAR-22:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 842.81 | 27-APR-01:55 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.21 | 20-MAY-17:30 | 1609.38 | 22-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.32 | 24-JUN-17:10 | 662.35 | 14-JUN-01:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.03 | 30-JUL-12:10 | 397.50 | 05-JUL-00:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.90 | 06-AUG-17:31 | 500.32 | 23-AUG-02:53 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.21 | 03-SEP-13:00 | 897.51 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.01 | 15-OCT-13:50 | 779.53 | 08-OCT-08:40 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1003.94 | 28-NOV-05:59 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1438.09 | 01-DEC-05:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.50 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 295.21 | 1670.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2505.28 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1522.44 | 19-FEB-12:22 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1840.13 | 02-MAR-22:51 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 1261.79 | 27-APR-01:55 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.23 | 20-MAY-17:30 | 2423.81 | 22-MAY-04:02 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.21 | 24-JUN-17:10 | 986.79 | 14-JUN-01:51 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 308.42 | 30-JUL-14:10 | 592.91 | 05-JUL-00:51 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 362.02 | 06-AUG-17:31 | 760.84 | 23-AUG-02:53 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.66 | 03-SEP-16:50 | 1318.47 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.98 | 18-OCT-14:10 | 1223.10 | 08-OCT-14:51 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1505.91 | 28-NOV-05:56 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2137.96 | 01-DEC-05:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.91 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 362.02 | 2505.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1672.62 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1024.99 | 17-FEB-03:51 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1267.26 | 02-MAR-22:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 928.40 | 27-APR-01:55 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.18 | 20-MAY-17:01 | 1660.96 | 22-MAY-03:51 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.13 | 29-JUN-15:00 | 724.14 | 14-JUN-01:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 30-JUL-12:10 | 451.58 | 05-JUL-00:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.11 | 06-AUG-12:10 | 600.61 | 23-AUG-02:53 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.50 | 03-SEP-13:00 | 944.10 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 15-OCT-12:30 | 819.64 | 30-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1003.94 | 28-NOV-05:58 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1561.67 | 01-DEC-04:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.58 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 314.50 | 1672.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5865.00 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3242.56 | 08-FEB-22:01 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 3984.75 | 02-MAR-22:01 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 2692.12 | 27-APR-01:55 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.26 | 20-MAY-17:01 | 5690.16 | 22-MAY-04:47 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 387.77 | 24-JUN-17:10 | 2126.22 | 14-JUN-01:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 903.82 | 30-JUL-11:53 | 1266.55 | 05-JUL-00:51 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 960.77 | 06-AUG-18:00 | 1542.31 | 23-AUG-02:53 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1192.81 | 03-SEP-13:00 | 2745.15 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 398.09 | 15-OCT-14:10 | 2572.15 | 30-OCT-21:01 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 3547.11 | 28-NOV-05:56 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 5043.46 | 01-DEC-05:06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1266.55 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1192.81 | 5865.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3909.51 | 05-JAN-22:01 |
February | 1239.33 | 01-FEB-08:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2160.88 | 08-FEB-22:01 |
March | 1239.33 | 01-MAR-08:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2657.19 | 02-MAR-22:01 |
April | 1239.33 | 03-APR-07:10 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 1807.56 | 27-APR-01:55 |
May | 1239.33 | 01-MAY-07:10 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.21 | 29-MAY-15:00 | 3793.55 | 22-MAY-04:46 |
June | 1239.33 | 01-JUN-07:10 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.76 | 24-JUN-17:10 | 1525.92 | 04-JUN-13:51 |
July | 1239.33 | 03-JUL-07:10 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 490.26 | 30-JUL-14:30 | 844.50 | 05-JUL-00:51 |
August | 1239.33 | 01-AUG-07:10 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 642.22 | 06-AUG-17:40 | 1025.02 | 23-AUG-02:53 |
September | 1239.33 | 01-SEP-07:10 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 723.25 | 03-SEP-13:00 | 1829.39 | 12-SEP-03:00 |
October | 1239.33 | 02-OCT-07:10 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.29 | 15-OCT-14:10 | 1716.04 | 30-OCT-21:01 |
November | 1239.33 | 01-NOV-07:10 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2364.74 | 28-NOV-05:59 |
December | 1239.33 | 01-DEC-08:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3362.28 | 01-DEC-05:09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844.50 | |||||
Maximum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 723.25 | 3909.51 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5868.44 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3586.48 | 19-FEB-12:25 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 4139.80 | 12-MAR-15:00 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 2737.79 | 27-APR-01:55 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 313.06 | 20-MAY-17:01 | 5690.33 | 22-MAY-04:41 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 324.25 | 24-JUN-17:10 | 2192.32 | 04-JUN-13:51 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 694.30 | 30-JUL-12:00 | 1290.82 | 05-JUL-00:51 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 844.16 | 06-AUG-17:40 | 1580.38 | 23-AUG-02:53 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 817.13 | 03-SEP-12:54 | 2768.00 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.04 | 18-OCT-14:10 | 2802.34 | 08-OCT-14:51 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 3547.08 | 28-NOV-05:59 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 5043.30 | 01-DEC-05:09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1290.82 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 844.16 | 5868.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3910.12 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2164.10 | 08-FEB-22:01 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2711.42 | 02-MAR-22:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 1826.44 | 27-APR-01:55 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.42 | 20-MAY-17:01 | 3794.73 | 22-MAY-04:03 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.99 | 29-JUN-15:00 | 1441.38 | 14-JUN-01:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 676.10 | 30-JUL-11:50 | 917.97 | 05-JUL-00:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 634.79 | 06-AUG-12:00 | 1068.84 | 23-AUG-02:53 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 822.53 | 03-SEP-13:00 | 1822.32 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.30 | 15-OCT-12:50 | 1718.25 | 30-OCT-21:01 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2364.74 | 28-NOV-05:57 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3362.18 | 01-DEC-05:06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 917.97 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 822.53 | 3910.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 7272.54 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 4035.82 | 17-FEB-05:56 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 4958.14 | 17-MAR-04:44 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.19 | 16-APR-16:50 | 3172.42 | 15-APR-04:50 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 530.96 | 20-MAY-17:40 | 7103.98 | 22-MAY-04:54 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 509.25 | 24-JUN-17:10 | 2324.11 | 14-JUN-01:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1239.68 | 30-JUL-12:00 | 1399.45 | 05-JUL-00:51 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1260.90 | 06-AUG-17:50 | 1795.50 | 17-AUG-04:52 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1469.00 | 03-SEP-13:00 | 2915.50 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 678.03 | 15-OCT-14:10 | 3197.17 | 30-OCT-21:01 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 4400.60 | 28-NOV-05:46 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6297.71 | 01-DEC-05:09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1399.45 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1469.00 | 7272.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4848.02 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2690.58 | 17-FEB-05:54 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 3305.42 | 17-MAR-04:48 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 2114.84 | 15-APR-04:47 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 305.48 | 20-MAY-17:40 | 4736.21 | 22-MAY-04:56 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.97 | 24-JUN-17:10 | 1903.57 | 04-JUN-13:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 703.41 | 30-JUL-15:00 | 939.23 | 05-JUL-00:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 795.99 | 06-AUG-17:50 | 1196.87 | 17-AUG-05:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 844.60 | 03-SEP-16:50 | 1940.07 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 286.32 | 15-OCT-14:10 | 2131.59 | 30-OCT-21:01 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2933.78 | 28-NOV-05:47 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4198.74 | 01-DEC-05:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 939.23 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 844.60 | 4848.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 7275.79 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 4035.82 | 17-FEB-05:58 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 4961.86 | 02-MAR-22:01 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 3172.36 | 15-APR-04:42 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 414.27 | 20-MAY-17:01 | 7104.25 | 22-MAY-04:57 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 418.27 | 24-JUN-17:10 | 2695.95 | 04-JUN-13:51 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1005.62 | 30-JUL-12:00 | 1430.81 | 05-JUL-00:51 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1169.24 | 06-AUG-17:50 | 1817.07 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.80 | 03-SEP-16:47 | 2942.56 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.28 | 18-OCT-14:20 | 3209.01 | 30-OCT-21:01 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 4400.71 | 28-NOV-05:47 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6298.23 | 01-DEC-05:09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1430.81 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1169.24 | 7275.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4849.48 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2690.55 | 17-FEB-05:56 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 3306.79 | 02-MAR-22:01 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 2114.75 | 15-APR-04:50 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 275.26 | 20-MAY-17:01 | 4736.19 | 22-MAY-04:59 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.28 | 29-JUN-15:00 | 1611.02 | 14-JUN-01:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 821.65 | 30-JUL-12:00 | 1045.00 | 05-JUL-00:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 769.45 | 06-AUG-11:51 | 1248.64 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 936.91 | 03-SEP-13:00 | 1985.15 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.55 | 15-OCT-12:50 | 2136.08 | 30-OCT-21:01 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2933.80 | 28-NOV-05:50 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4198.79 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1045.00 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 936.91 | 4849.48 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 8217.58 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 8217.58 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 8217.58 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 8217.58 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 8217.58 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 8217.58 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 8217.58 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 8217.58 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 8217.58 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 8217.58 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 8217.58 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 8217.58 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 8217.58 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 8217.58 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5175.91 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3424.72 | 17-FEB-03:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 4066.35 | 02-MAR-22:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 2899.96 | 27-APR-01:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.80 | 20-MAY-17:01 | 5723.02 | 22-MAY-04:01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.93 | 29-JUN-15:00 | 2291.91 | 14-JUN-01:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 642.08 | 30-JUL-11:51 | 1341.14 | 05-JUL-00:51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 701.87 | 06-AUG-17:51 | 1760.71 | 23-AUG-02:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 800.78 | 03-SEP-13:00 | 3148.73 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.92 | 18-OCT-13:55 | 2653.36 | 30-OCT-22:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 3237.77 | 26-NOV-19:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 5110.40 | 01-DEC-04:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1341.14 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 800.78 | 5723.02 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9141.18 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 5892.68 | 17-FEB-03:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 7138.76 | 02-MAR-22:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 5048.50 | 27-APR-01:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467.35 | 20-MAY-17:01 | 9679.98 | 22-MAY-04:20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.52 | 29-JUN-15:00 | 3982.37 | 14-JUN-01:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1227.56 | 30-JUL-12:00 | 2311.42 | 05-JUL-00:51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1327.01 | 06-AUG-18:00 | 2993.72 | 23-AUG-02:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1509.99 | 03-SEP-13:00 | 5423.35 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.41 | 18-OCT-13:55 | 4529.56 | 30-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 5307.73 | 28-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 8305.68 | 01-DEC-04:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2311.42 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1509.99 | 9679.98 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10100.85 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 5641.14 | 08-FEB-22:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 7192.06 | 02-MAR-22:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 4744.42 | 27-APR-01:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.47 | 20-MAY-17:01 | 9478.60 | 22-MAY-04:51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.73 | 29-JUN-15:00 | 4558.60 | 04-JUN-13:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.89 | 30-JUL-12:00 | 2155.19 | 05-JUL-00:51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1259.37 | 06-AUG-17:50 | 2820.62 | 22-AUG-21:02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1325.37 | 03-SEP-13:00 | 4771.46 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 4513.69 | 30-OCT-21:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 5689.06 | 28-NOV-05:50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 7908.81 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2155.19 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1325.37 | 10100.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 136092.48 | 02-JAN-04:01 | 0.00 | 14572.39 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 132516.08 | 28-FEB-05:01 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 134012.38 | 23-MAR-05:01 | 17952.25 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 113931.32 | 03-APR-13:40 | 178322.13 | 291447.90 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 131627.68 | 11-MAY-05:01 | 12566.58 | 22668.17 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 137838.57 | 05-JUN-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 142361.52 | 05-JUL-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 125248.53 | 28-AUG-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 139462.10 | 12-SEP-04:11 | 0.00 | 29144.79 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 142831.22 | 30-OCT-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 144670.35 | 06-NOV-04:01 | 0.00 | 16191.55 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 113927.24 | 11-DEC-05:01 | 0.00 | 22668.17 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 113927.24 | 0.00 | 14572.39 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 144670.35 | 178322.13 | 291447.90 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 105454.13 | 02-JAN-06:01 | 14510.15 | 26174.07 | 68826.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 102985.59 | 28-FEB-06:02 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 105331.50 | 30-MAR-05:01 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 109652.26 | 24-APR-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 110172.17 | 30-MAY-04:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 114441.93 | 22-JUN-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 117142.29 | 05-JUL-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 118805.05 | 14-AUG-04:11 | 0.00 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 117203.52 | 05-SEP-04:11 | 0.00 | 23265.84 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 109496.22 | 19-OCT-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 106964.10 | 24-NOV-05:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 106690.06 | 06-DEC-06:01 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 102985.59 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 118805.05 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 26155.26 | 13-JAN-16:53 | 107213.85 | 183218.49 | 120445.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 36528.75 | 28-FEB-16:52 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 37635.60 | 01-MAR-16:53 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97734.91 | 07-APR-05:01 | 12897.91 | 23265.84 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97000.21 | 13-MAY-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 105513.85 | 23-JUN-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 105979.64 | 18-JUL-04:11 | 0.00 | 26174.07 | 53438.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 107092.24 | 09-AUG-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 102458.39 | 07-SEP-04:11 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 99602.22 | 19-OCT-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 91492.75 | 08-NOV-06:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33054.18 | 07-DEC-16:23 | 45948.79 | 78522.21 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 26155.26 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 107092.24 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 23579.62 | 13-JAN-17:00 | 107213.85 | 183218.49 | 120445.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26117.11 | 28-FEB-17:00 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29070.54 | 28-MAR-15:51 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 45103.19 | 25-APR-16:00 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 55339.34 | 19-MAY-16:00 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 130333.83 | 21-JUN-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 123686.69 | 14-JUL-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 123209.02 | 09-AUG-05:01 | 12897.91 | 23265.84 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 120651.92 | 05-SEP-05:02 | 9673.43 | 17449.38 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40382.03 | 18-OCT-16:00 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 26683.90 | 03-NOV-16:00 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24960.36 | 06-DEC-16:30 | 76581.32 | 130870.35 | 86032.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 23579.62 | 0.00 | 17449.38 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 130333.83 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3771.50 | 02-JAN-14:40 | 10053.95 | 16432.08 | 10802.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.56 |
February | 5324.97 | 26-FEB-14:51 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.14 |
March | 5062.65 | 26-MAR-14:01 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.05 |
April | 8258.30 | 07-APR-14:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.97 |
May | 9600.02 | 19-MAY-16:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 78.51 | 0.00 |
June | 15843.92 | 21-JUN-05:01 | 1821.89 | 3286.42 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.32 |
July | 25549.13 | 16-JUL-18:21 | 0.00 | 1825.79 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 92.20 | 0.00 |
August | 26062.77 | 06-AUG-16:01 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 273.64 | 0.00 |
September | 17842.42 | 05-SEP-04:11 | 0.00 | 2921.26 | 5964.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.42 |
October | 6815.88 | 19-OCT-14:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.32 |
November | 5349.73 | 24-NOV-06:02 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.13 |
December | 4860.78 | 06-DEC-06:02 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3771.50 | 0.00 | 1825.79 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26062.77 | 10053.95 | 16432.08 | 10802.76 | 0.00 | 0.00 | 0.00 | 0.00 | 273.64 | 510.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4769.35 | 15-JAN-11:32 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551.58 |
February | 10071.11 | 26-FEB-09:26 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 585.80 |
March | 11075.01 | 28-MAR-09:11 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.10 |
April | 19467.24 | 16-APR-08:31 | 587.05 | 1058.95 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.85 |
May | 14759.89 | 19-MAY-08:40 | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.98 |
June | 30644.57 | 04-JUN-07:51 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.10 |
July | 33057.04 | 16-JUL-08:21 | 587.05 | 1058.95 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.75 |
August | 34610.61 | 06-AUG-08:41 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.83 |
September | 29392.47 | 03-SEP-09:21 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.55 |
October | 22049.49 | 15-OCT-09:41 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.63 |
November | 6923.83 | 03-NOV-09:31 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.92 |
December | 5035.98 | 08-DEC-06:02 | 1043.64 | 1882.57 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4769.35 | 391.37 | 705.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.79 | |
Maximum of Months | 34610.61 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 585.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33846.05 | 15-JAN-13:32 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 765.53 |
February | 42262.30 | 26-FEB-13:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.80 |
March | 37781.11 | 26-MAR-13:21 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 817.54 |
April | 37240.47 | 16-APR-13:12 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.03 |
May | 19307.91 | 19-MAY-13:30 | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 33.90 | 0.00 |
June | 23343.86 | 11-JUN-13:51 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.86 |
July | 39624.32 | 16-JUL-14:21 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 88.61 | 0.00 |
August | 40411.28 | 06-AUG-12:41 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 168.68 | 0.00 |
September | 44580.11 | 03-SEP-12:41 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 158.12 | 0.00 |
October | 39532.02 | 15-OCT-11:01 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.53 |
November | 37965.88 | 12-NOV-13:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.07 |
December | 17473.96 | 12-DEC-12:24 | 5291.67 | 16432.44 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17473.96 | 607.31 | 1095.50 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44580.11 | 5291.67 | 16432.44 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 168.68 | 817.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6187.02 | 13-JAN-15:40 | 3717.98 | 6353.67 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.06 |
February | 31136.52 | 26-FEB-16:51 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.68 |
March | 14034.64 | 28-MAR-15:53 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.13 |
April | 37439.78 | 16-APR-17:11 | 0.00 | 941.28 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.22 |
May | 36271.85 | 28-MAY-17:31 | 0.00 | 823.62 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.14 |
June | 36354.69 | 18-JUN-17:31 | 0.00 | 823.62 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.92 |
July | 45331.86 | 16-JUL-17:01 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 24.56 | 0.00 |
August | 43724.35 | 06-AUG-16:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 104.47 | 0.00 |
September | 38844.16 | 03-SEP-15:21 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.01 | 0.00 |
October | 28168.94 | 15-OCT-17:01 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.68 |
November | 10269.30 | 03-NOV-15:23 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.79 |
December | 8984.25 | 06-DEC-15:24 | 6196.63 | 10589.46 | 6961.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6187.02 | 0.00 | 823.62 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45331.86 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 142.01 | 274.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4148.23 | 04-JAN-06:04 | 1417.03 | 2556.10 | 6721.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.43 |
February | 5493.51 | 27-FEB-13:21 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.47 |
March | 5213.93 | 23-MAR-13:30 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.92 |
April | 6280.66 | 07-APR-14:40 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.17 |
May | 9099.93 | 19-MAY-16:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 178.84 | 0.00 |
June | 11059.61 | 29-JUN-15:10 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 286.63 | 0.00 |
July | 11920.59 | 17-JUL-16:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 212.73 | 0.00 |
August | 11874.50 | 09-AUG-14:50 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 129.85 | 0.00 |
September | 9880.66 | 04-SEP-12:32 | 607.30 | 1095.47 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 559.99 | 0.00 |
October | 7178.06 | 18-OCT-13:50 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 70.49 | 0.00 |
November | 5360.10 | 03-NOV-13:30 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.64 |
December | 4167.44 | 22-DEC-06:03 | 1821.89 | 3286.42 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4148.23 | 607.30 | 1095.47 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11920.59 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 559.99 | 504.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4705.18 | 14-JAN-11:02 | 1956.83 | 3529.82 | 3867.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.46 |
February | 13938.13 | 27-FEB-11:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.47 |
March | 18410.18 | 28-MAR-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.33 |
April | 20381.87 | 06-APR-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.50 |
May | 15713.30 | 19-MAY-10:05 | 2478.65 | 4235.78 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.95 |
June | 33824.71 | 25-JUN-09:31 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.59 |
July | 32709.63 | 02-JUL-07:11 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.56 |
August | 37345.39 | 06-AUG-09:31 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.62 |
September | 29382.61 | 04-SEP-09:52 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 28.05 | 0.00 |
October | 17344.81 | 12-OCT-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.86 |
November | 14234.25 | 03-NOV-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.13 |
December | 5220.64 | 06-DEC-11:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4705.18 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37345.39 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 28.05 | 419.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16920.62 | 19-JAN-13:40 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.70 |
February | 44226.58 | 26-FEB-14:11 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.85 |
March | 38955.49 | 26-MAR-13:41 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1876.19 |
April | 36925.73 | 16-APR-13:02 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 935.00 |
May | 19961.60 | 19-MAY-13:40 | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 85.14 | 0.00 |
June | 19808.64 | 18-JUN-13:12 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.58 |
July | 31805.19 | 16-JUL-15:51 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 175.88 | 0.00 |
August | 42958.74 | 06-AUG-13:31 | 910.97 | 1643.24 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 351.72 | 0.00 |
September | 42866.99 | 04-SEP-15:11 | 910.97 | 1643.24 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 160.50 | 0.00 |
October | 40608.63 | 22-OCT-14:11 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1380.02 |
November | 38915.80 | 12-NOV-14:01 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1221.47 |
December | 16758.95 | 12-DEC-12:33 | 3175.00 | 9859.46 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16758.95 | 607.31 | 1095.50 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44226.58 | 3175.00 | 9859.46 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 351.72 | 1876.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5055.96 | 13-JAN-15:40 | 3717.98 | 6353.67 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.96 |
February | 9600.70 | 28-FEB-16:32 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.78 |
March | 11885.27 | 28-MAR-16:52 | 3913.66 | 11766.06 | 7735.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.46 |
April | 34385.10 | 16-APR-17:01 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.68 |
May | 38530.47 | 28-MAY-18:01 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 822.00 |
June | 34416.06 | 18-JUN-17:11 | 0.00 | 823.62 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.84 |
July | 39977.07 | 09-JUL-16:51 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.82 |
August | 39836.56 | 06-AUG-16:11 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 271.15 | 0.00 |
September | 40243.19 | 04-SEP-16:31 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 71.77 | 0.00 |
October | 19309.61 | 15-OCT-17:21 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 568.78 |
November | 7506.60 | 03-NOV-15:33 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.91 |
December | 5358.53 | 06-DEC-15:40 | 4957.30 | 8471.56 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5055.96 | 0.00 | 823.62 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40243.19 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 271.15 | 822.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4961.18 | 14-JAN-17:02 | 506.08 | 912.89 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.44 |
February | 5561.48 | 27-FEB-16:00 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.82 |
March | 6021.22 | 29-MAR-16:00 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.98 |
April | 7511.93 | 07-APR-14:40 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.77 |
May | 11312.16 | 28-MAY-16:41 | 910.95 | 1643.21 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.85 |
June | 12410.27 | 29-JUN-15:10 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 350.96 | 0.00 |
July | 13840.80 | 17-JUL-16:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 261.92 | 0.00 |
August | 13274.04 | 09-AUG-14:50 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 159.33 | 0.00 |
September | 13128.36 | 03-SEP-15:21 | 910.95 | 1643.21 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 886.63 | 0.00 |
October | 7041.36 | 18-OCT-15:50 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 59.61 | 0.00 |
November | 5327.90 | 17-NOV-15:40 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.24 |
December | 5511.14 | 07-DEC-06:04 | 1619.46 | 2921.26 | 7681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 513.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4961.18 | 506.08 | 912.89 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13840.80 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 886.63 | 594.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3284.32 | 14-JAN-17:02 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.47 |
February | 4945.81 | 26-FEB-12:31 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 513.46 |
March | 7667.87 | 23-MAR-10:22 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675.23 |
April | 11907.39 | 25-APR-09:33 | 10366.64 | 16943.13 | 11138.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.71 |
May | 14577.17 | 19-MAY-09:30 | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.00 |
June | 31723.36 | 25-JUN-09:51 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.05 |
July | 36306.60 | 16-JUL-08:51 | 587.05 | 1058.95 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.23 |
August | 33505.01 | 06-AUG-09:41 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 75.05 | 0.00 |
September | 31095.50 | 03-SEP-10:01 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 43.43 | 0.00 |
October | 8131.60 | 18-OCT-09:55 | 2591.66 | 4235.78 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.47 |
November | 4645.79 | 03-NOV-10:11 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.29 |
December | 3621.28 | 07-DEC-06:04 | 1043.64 | 1882.57 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3284.32 | 326.14 | 588.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36306.60 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 75.05 | 675.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15534.20 | 31-JAN-13:30 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 836.36 |
February | 52694.63 | 26-FEB-14:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1275.53 |
March | 24246.77 | 01-MAR-14:01 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.85 |
April | 22503.21 | 25-APR-13:34 | 10054.17 | 16432.44 | 10802.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.42 |
May | 20990.07 | 19-MAY-13:50 | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 112.92 | 0.00 |
June | 20638.07 | 30-JUN-13:50 | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 46.23 | 0.00 |
July | 52291.48 | 16-JUL-14:51 | 910.97 | 1643.24 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 346.27 | 0.00 |
August | 48226.49 | 06-AUG-13:42 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 635.31 | 0.00 |
September | 58935.48 | 03-SEP-13:21 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 394.21 | 0.00 |
October | 49129.78 | 15-OCT-14:01 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 733.59 |
November | 24334.81 | 03-NOV-13:22 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.01 |
December | 13805.86 | 12-DEC-14:24 | 10054.17 | 16432.44 | 10802.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 580.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13805.86 | 607.31 | 1095.50 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 58935.48 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 635.31 | 1275.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5107.18 | 13-JAN-15:40 | 3717.98 | 6353.67 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.09 |
February | 9157.61 | 28-FEB-16:33 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.20 |
March | 11858.36 | 28-MAR-16:52 | 3913.66 | 11766.06 | 7735.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.15 |
April | 29140.78 | 22-APR-17:41 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 717.39 |
May | 41362.40 | 28-MAY-18:01 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1008.57 |
June | 37329.50 | 18-JUN-17:11 | 0.00 | 823.62 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.00 |
July | 46493.26 | 16-JUL-17:31 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 48.03 | 0.00 |
August | 39376.16 | 06-AUG-16:21 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 433.58 | 0.00 |
September | 43952.60 | 04-SEP-16:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 80.14 | 0.00 |
October | 13812.69 | 18-OCT-16:00 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 4.26 | 0.00 |
November | 7001.52 | 03-NOV-15:23 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.02 |
December | 5453.00 | 06-DEC-15:40 | 4957.30 | 8471.56 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5107.18 | 0.00 | 823.62 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46493.26 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 433.58 | 1008.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20587.05 | 28-JAN-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2476.46 |
February | 19090.38 | 04-FEB-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1658.00 |
March | 16993.64 | 04-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1788.37 |
April | 10041.67 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.63 |
May | 11659.57 | 22-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1366.46 |
June | 9628.50 | 26-JUN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.19 |
July | 10891.97 | 17-JUL-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.42 | 0.00 |
August | 11054.81 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.43 | 0.00 |
September | 11953.29 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.09 |
October | 10116.90 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.79 |
November | 15709.60 | 27-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3013.51 |
December | 16043.47 | 28-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2087.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9628.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20587.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.42 | 3013.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21681.73 | 06-JAN-03:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5954.39 |
February | 21958.39 | 04-FEB-03:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3141.73 |
March | 23602.99 | 05-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4135.62 |
April | 18006.95 | 15-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4270.80 |
May | 18691.91 | 08-MAY-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2464.91 |
June | 12756.95 | 17-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.07 |
July | 10260.52 | 22-JUL-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10693.49 | 14-AUG-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.72 |
September | 14320.84 | 19-SEP-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.95 |
October | 17195.65 | 10-OCT-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1811.72 |
November | 22881.42 | 26-NOV-07:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4375.82 |
December | 20899.18 | 16-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2066.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 10260.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23602.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5954.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1758.30 | 14-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 655.34 |
February | 9636.82 | 26-FEB-14:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 925.93 |
March | 11840.98 | 22-MAR-14:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.32 |
April | 20792.52 | 25-APR-14:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.54 |
May | 30281.68 | 19-MAY-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.32 | 0.00 |
June | 34454.83 | 23-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.89 | 0.00 |
July | 39801.40 | 17-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.48 | 0.00 |
August | 36663.86 | 07-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.51 | 0.00 |
September | 27453.91 | 01-SEP-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.92 | 0.00 |
October | 17326.71 | 18-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.44 |
November | 6730.78 | 03-NOV-13:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.04 |
December | 1018.89 | 06-DEC-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1333.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1018.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39801.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.51 | 1333.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5335.21 | 06-JAN-03:31 | 0.00 | 283.42 | 13640.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11084.72 | 01-FEB-07:01 | 467.67 | 2429.28 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6415.61 | 31-MAR-23:57 | 0.00 | 121.46 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8379.19 | 24-APR-18:10 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3439.69 | 31-MAY-23:51 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5371.40 | 30-JUN-24:00 | 0.00 | 40.49 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7234.37 | 31-JUL-23:05 | 0.00 | 161.95 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8767.50 | 04-AUG-19:00 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3173.66 | 30-SEP-23:31 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4619.25 | 31-OCT-23:52 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6256.41 | 13-NOV-16:21 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13251.44 | 29-DEC-01:01 | 0.00 | 404.88 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 3173.66 | 0.00 | 40.49 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13251.44 | 2221.41 | 7287.84 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2577.57 | 27-JAN-10:32 | 1393.61 | 4372.71 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10603.72 | 01-FEB-07:01 | 467.67 | 2429.28 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6219.18 | 28-MAR-17:42 | 233.83 | 2429.28 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8075.58 | 25-APR-18:02 | 233.83 | 2429.28 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3220.69 | 31-MAY-23:31 | 0.00 | 323.90 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5231.65 | 30-JUN-23:40 | 0.00 | 40.49 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7020.06 | 31-JUL-23:50 | 0.00 | 80.98 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8449.46 | 04-AUG-19:00 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2702.09 | 30-SEP-23:11 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4333.56 | 18-OCT-17:00 | 70.15 | 404.88 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5829.17 | 03-NOV-15:51 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11878.62 | 29-DEC-01:01 | 0.00 | 404.88 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2577.57 | 0.00 | 40.49 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11878.62 | 2221.41 | 7287.84 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1600.97 | 13-JAN-16:25 | 444.28 | 1457.57 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9246.42 | 01-FEB-07:01 | 467.67 | 2429.28 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6159.83 | 28-MAR-17:42 | 233.83 | 2429.28 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8152.30 | 25-APR-18:02 | 233.83 | 2429.28 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3017.07 | 31-MAY-23:12 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5170.32 | 30-JUN-23:20 | 0.00 | 80.98 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6947.92 | 31-JUL-23:20 | 0.00 | 80.98 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8592.92 | 04-AUG-19:00 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2844.26 | 04-SEP-17:42 | 0.00 | 364.39 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4385.58 | 18-OCT-17:00 | 70.15 | 404.88 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5706.40 | 03-NOV-15:51 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11612.20 | 29-DEC-09:41 | 2221.41 | 7287.84 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1600.97 | 0.00 | 80.98 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11612.20 | 2221.41 | 7287.84 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 102591.70 | 24-JAN-05:11 | 0.00 | 9130.65 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 505033.77 | 23-FEB-22:03 | 2530.88 | 9130.65 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 538422.54 | 01-MAR-00:02 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 514260.54 | 03-APR-13:40 | 50279.21 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 496036.94 | 31-MAY-23:55 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 506617.36 | 20-JUN-02:32 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 536603.76 | 15-JUL-04:02 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 534275.47 | 16-AUG-15:22 | 48086.79 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 493960.53 | 30-SEP-23:12 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 520849.93 | 31-OCT-23:32 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 535368.15 | 03-NOV-13:32 | 50279.21 | 82175.84 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 498729.46 | 19-DEC-09:32 | 48086.79 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 102591.70 | 0.00 | 4565.32 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 538422.54 | 50279.21 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.196686E+13 | 1467095.35 | 02-JAN-16:40 | 0.144233E+13 | 2729835.69 | 09-JAN-07:19 |
February | 0.216310E+13 | 1760197.35 | 27-FEB-15:09 | 0.768125E+12 | 1924870.60 | 06-FEB-05:10 |
March | 0.289650E+13 | 1868500.39 | 02-MAR-15:09 | 0.512212E+12 | 2078691.54 | 06-MAR-05:10 |
April | 0.315436E+13 | 2154687.46 | 06-APR-15:00 | 0.193588E+12 | 1075687.89 | 29-APR-04:10 |
May | 0.205264E+13 | 1847107.21 | 19-MAY-15:30 | 0.135021E+12 | 1172117.83 | 22-MAY-04:10 |
June | 0.250979E+13 | 2015587.45 | 29-JUN-15:20 | 0.231641E+11 | 643186.02 | 17-JUN-04:19 |
July | 0.300653E+13 | 2259029.27 | 17-JUL-15:00 | 0.428891E+10 | 272127.14 | 08-JUL-05:10 |
August | 0.351318E+13 | 2379332.99 | 07-AUG-15:20 | 0.147814E+11 | 661521.95 | 18-AUG-05:10 |
September | 0.201842E+13 | 1943329.95 | 07-SEP-14:50 | 0.795976E+11 | 779421.41 | 19-SEP-04:19 |
October | 0.242513E+13 | 1931038.43 | 18-OCT-15:39 | 0.186820E+12 | 1139662.86 | 10-OCT-05:10 |
November | 0.278853E+13 | 1876191.55 | 17-NOV-16:49 | 0.465582E+12 | 1869090.75 | 27-NOV-06:10 |
December | 0.327494E+13 | 1982412.30 | 06-DEC-16:40 | 0.942409E+12 | 2020511.49 | 26-DEC-05:10 |
Annual Sum or Average | 0.317700E+14 | 0.476792E+13 | ||||
Minimum of Months | 0.196686E+13 | 1467095.35 | 0.428891E+10 | 272127.14 | ||
Maximum of Months | 0.351318E+13 | 2379332.99 | 0.144233E+13 | 2729835.69 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.468149E+12 | 0.109043E+12 | 0.766053E+12 | 0.218140E+12 | 0.211907E+12 | 0.163197E+11 | 0.00 | 0.950794E+10 | 392.00 | 0.123835E+12 | 0.00 | 0.439094E+11 | 0.00 |
February | 0.424646E+12 | 0.900876E+11 | 0.978954E+12 | 0.199667E+12 | 0.206131E+12 | 0.322990E+11 | 0.00 | 0.728140E+11 | 17207741.08 | 0.117905E+12 | 0.00 | 0.405763E+11 | 0.00 |
March | 0.504598E+12 | 0.879729E+11 | 0.141687E+13 | 0.230864E+12 | 0.249504E+12 | 0.593615E+11 | 0.00 | 0.120628E+12 | 14299914.47 | 0.179464E+12 | 0.00 | 0.472187E+11 | 0.00 |
April | 0.450709E+12 | 0.732466E+11 | 0.165903E+13 | 0.216144E+12 | 0.268663E+12 | 0.836820E+11 | 0.00 | 0.126608E+12 | 0.179457E+09 | 0.234782E+12 | 0.00 | 0.413166E+11 | 0.00 |
May | 0.486374E+12 | 0.651338E+11 | 0.774844E+12 | 0.224502E+12 | 0.222959E+12 | 0.338981E+11 | 0.00 | 0.736286E+11 | 0.144370E+10 | 0.128103E+12 | 0.00 | 0.417543E+11 | 0.00 |
June | 0.484022E+12 | 0.575207E+11 | 0.106252E+13 | 0.222585E+12 | 0.276425E+12 | 0.723510E+11 | 0.00 | 0.216304E+12 | 0.108651E+11 | 0.683023E+11 | 0.00 | 0.388965E+11 | 0.00 |
July | 0.453060E+12 | 0.619809E+11 | 0.139340E+13 | 0.218061E+12 | 0.324980E+12 | 0.108445E+12 | 0.00 | 0.331241E+12 | 0.224456E+11 | 0.577147E+11 | 0.00 | 0.351987E+11 | 0.00 |
August | 0.504598E+12 | 0.709397E+11 | 0.173200E+13 | 0.230864E+12 | 0.355326E+12 | 0.110504E+12 | 0.00 | 0.323410E+12 | 0.165646E+11 | 0.131317E+12 | 0.00 | 0.376564E+11 | 0.00 |
September | 0.450709E+12 | 0.799369E+11 | 0.740713E+12 | 0.216143E+12 | 0.236083E+12 | 0.489586E+11 | 0.00 | 0.122210E+12 | 0.619856E+10 | 0.828304E+11 | 0.00 | 0.346413E+11 | 0.00 |
October | 0.468149E+12 | 0.948169E+11 | 0.108340E+13 | 0.218140E+12 | 0.238475E+12 | 0.455583E+11 | 0.00 | 0.110916E+12 | 0.532130E+09 | 0.127787E+12 | 0.00 | 0.373498E+11 | 0.00 |
November | 0.462662E+12 | 0.102507E+12 | 0.135889E+13 | 0.209941E+12 | 0.235988E+12 | 0.816603E+11 | 0.00 | 0.105600E+12 | 17305181.33 | 0.192375E+12 | 0.00 | 0.388911E+11 | 0.00 |
December | 0.453060E+12 | 0.112081E+12 | 0.170972E+13 | 0.218060E+12 | 0.276723E+12 | 0.952666E+11 | 0.00 | 0.117469E+12 | 351372.95 | 0.251524E+12 | 0.00 | 0.410409E+11 | 0.00 |
Annual Sum or Average | 0.561074E+13 | 0.100527E+13 | 0.146764E+14 | 0.262311E+13 | 0.310316E+13 | 0.788304E+12 | 0.00 | 0.173034E+13 | 0.582784E+11 | 0.169594E+13 | 0.00 | 0.478450E+12 | 0.00 |
Minimum of Months | 0.424646E+12 | 0.575207E+11 | 0.740713E+12 | 0.199667E+12 | 0.206131E+12 | 0.163197E+11 | 0.00 | 0.950794E+10 | 392.00 | 0.577147E+11 | 0.00 | 0.346413E+11 | 0.00 |
Maximum of Months | 0.504598E+12 | 0.112081E+12 | 0.173200E+13 | 0.230864E+12 | 0.355326E+12 | 0.110504E+12 | 0.00 | 0.331241E+12 | 0.224456E+11 | 0.251524E+12 | 0.00 | 0.472187E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.144233E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.768125E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.512212E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.193588E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.135021E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.231641E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.428891E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.147814E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.795976E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.186820E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.465582E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.942409E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.476792E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.428891E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.144233E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 489900.85 | 02-JAN-08:09 | 64082.80 | 01-JAN-00:10 | 423497.50 | 02-JAN-08:09 | 235096.12 | 02-JAN-08:20 | 150692.11 | 09-JAN-06:10 | 40115.35 | 19-JAN-06:40 | 0.00 | 01-JAN-00:10 |
February | 489900.85 | 01-FEB-08:09 | 64082.80 | 01-FEB-00:10 | 541788.89 | 01-FEB-08:09 | 235096.12 | 01-FEB-08:20 | 199803.90 | 28-FEB-15:00 | 41342.85 | 28-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 489900.85 | 01-MAR-08:09 | 64082.80 | 01-MAR-00:10 | 660080.29 | 01-MAR-08:09 | 235096.12 | 01-MAR-08:20 | 210690.97 | 28-MAR-15:50 | 41552.49 | 01-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 489900.85 | 03-APR-07:10 | 64082.80 | 01-APR-00:10 | 778371.69 | 03-APR-07:10 | 235096.12 | 03-APR-07:19 | 270647.56 | 25-APR-15:39 | 41835.77 | 04-APR-05:10 | 0.00 | 01-APR-00:10 |
May | 489900.85 | 01-MAY-07:10 | 64082.80 | 01-MAY-00:10 | 423497.50 | 01-MAY-07:10 | 235096.12 | 01-MAY-07:19 | 265300.79 | 19-MAY-15:30 | 84743.82 | 19-MAY-12:50 | 0.00 | 01-MAY-00:10 |
June | 489900.85 | 01-JUN-07:10 | 64082.80 | 01-JUN-00:10 | 541788.89 | 01-JUN-07:10 | 235096.12 | 01-JUN-07:19 | 285984.42 | 29-JUN-14:30 | 85347.19 | 30-JUN-15:39 | 0.00 | 01-JUN-00:10 |
July | 489900.85 | 03-JUL-07:10 | 64082.80 | 01-JUL-00:10 | 660080.29 | 03-JUL-07:10 | 235096.12 | 03-JUL-07:19 | 328570.57 | 17-JUL-15:00 | 86828.46 | 25-JUL-13:50 | 0.00 | 01-JUL-00:10 |
August | 489900.85 | 01-AUG-07:10 | 64082.80 | 01-AUG-00:10 | 778371.69 | 01-AUG-07:10 | 235096.12 | 01-AUG-07:19 | 347887.24 | 10-AUG-15:09 | 87619.82 | 07-AUG-14:30 | 0.00 | 01-AUG-00:10 |
September | 489900.85 | 01-SEP-07:10 | 64082.80 | 01-SEP-00:10 | 423497.50 | 01-SEP-07:10 | 235096.12 | 01-SEP-07:19 | 297953.51 | 01-SEP-15:50 | 85297.02 | 01-SEP-10:50 | 0.00 | 01-SEP-00:10 |
October | 489900.85 | 02-OCT-07:10 | 64082.80 | 01-OCT-00:10 | 541788.89 | 02-OCT-07:10 | 235096.12 | 02-OCT-07:19 | 241716.60 | 18-OCT-15:50 | 81871.85 | 18-OCT-14:50 | 0.00 | 01-OCT-00:10 |
November | 489900.85 | 01-NOV-07:10 | 64082.80 | 01-NOV-00:10 | 660080.29 | 01-NOV-07:10 | 235096.12 | 01-NOV-07:19 | 213844.02 | 03-NOV-14:50 | 41946.35 | 03-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 489900.85 | 01-DEC-08:09 | 64082.80 | 01-DEC-00:10 | 778371.69 | 01-DEC-08:09 | 235096.12 | 01-DEC-08:20 | 179776.54 | 07-DEC-13:50 | 42717.92 | 26-DEC-05:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 489900.85 | 64082.80 | 423497.50 | 235096.12 | 150692.11 | 40115.35 | 0.00 | |||||||
Maximum of Months | 489900.85 | 64082.80 | 778371.69 | 235096.12 | 347887.24 | 87619.82 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 31123.64 | 03-JAN-16:19 | 0.65 | 02-JAN-16:40 | 77221.41 | 03-JAN-14:00 | 0.00 | 58519.82 | 31-JAN-12:20 | 0.00 |
February | 146770.72 | 27-FEB-15:09 | 1591.48 | 27-FEB-15:09 | 100000.00 | 27-FEB-14:39 | 0.00 | 58671.58 | 17-FEB-12:50 | 0.00 |
March | 143485.75 | 02-MAR-14:50 | 288.04 | 02-MAR-14:50 | 100000.00 | 31-MAR-23:19 | 0.00 | 58619.91 | 01-MAR-12:20 | 0.00 |
April | 209338.65 | 06-APR-15:00 | 7120.41 | 06-APR-15:00 | 100000.00 | 01-APR-00:49 | 0.00 | 57266.29 | 03-APR-11:50 | 0.00 |
May | 287027.18 | 19-MAY-13:39 | 36545.54 | 19-MAY-13:39 | 100000.00 | 02-MAY-20:10 | 0.00 | 54734.28 | 02-MAY-11:00 | 0.00 |
June | 319490.69 | 29-JUN-15:09 | 50001.50 | 06-JUN-15:09 | 100000.00 | 05-JUN-10:20 | 0.00 | 51571.30 | 02-JUN-11:20 | 0.00 |
July | 372775.27 | 17-JUL-15:00 | 50001.50 | 13-JUL-13:30 | 100000.00 | 08-JUL-10:50 | 0.00 | 48010.73 | 03-JUL-11:30 | 0.00 |
August | 378553.45 | 10-AUG-15:09 | 50001.50 | 05-AUG-12:30 | 100000.00 | 02-AUG-18:40 | 0.00 | 46517.70 | 01-AUG-11:00 | 0.00 |
September | 393837.46 | 07-SEP-14:50 | 50001.50 | 06-SEP-12:50 | 100000.00 | 16-SEP-15:00 | 0.00 | 47429.93 | 28-SEP-11:50 | 0.00 |
October | 295978.74 | 18-OCT-14:20 | 16704.79 | 18-OCT-14:00 | 100000.00 | 15-OCT-12:09 | 0.00 | 50712.33 | 30-OCT-11:50 | 0.00 |
November | 161891.05 | 03-NOV-13:30 | 2100.88 | 03-NOV-13:30 | 100000.00 | 14-NOV-13:50 | 0.00 | 53574.00 | 30-NOV-12:20 | 0.00 |
December | 97733.76 | 07-DEC-10:00 | 42.50 | 06-DEC-11:39 | 100000.00 | 01-DEC-01:10 | 0.00 | 56261.71 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 31123.64 | 0.65 | 77221.41 | 0.00 | 46517.70 | 0.00 | ||||
Maximum of Months | 393837.46 | 50001.50 | 100000.00 | 0.00 | 58671.58 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1467095.35 | 02-JAN-16:40 | 489900.85 | 423497.50 | 64082.80 | 235096.12 | 109461.18 | 16066.14 | 0.00 | 26980.30 | 0.65 |
February | 1760197.35 | 27-FEB-15:09 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 179843.23 | 41167.56 | 0.00 | 146770.72 | 1591.48 |
March | 1868500.39 | 02-MAR-15:09 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 197507.37 | 41545.62 | 0.00 | 137288.36 | 123.85 |
April | 2154687.46 | 06-APR-15:00 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 249719.45 | 41755.12 | 0.00 | 209338.65 | 7120.41 |
May | 1847107.21 | 19-MAY-15:30 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 265300.79 | 83823.26 | 0.00 | 277179.38 | 31877.88 |
June | 2015587.45 | 29-JUN-15:20 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 281958.92 | 82010.87 | 0.00 | 311364.53 | 35570.09 |
July | 2259029.27 | 17-JUL-15:00 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 328570.57 | 86238.25 | 0.00 | 372775.27 | 50001.50 |
August | 2379332.99 | 07-AUG-15:20 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 340147.06 | 87549.07 | 0.00 | 371987.00 | 40289.89 |
September | 1943329.95 | 07-SEP-14:50 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 239647.69 | 84437.31 | 0.00 | 393837.46 | 50001.50 |
October | 1931038.43 | 18-OCT-15:39 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 238070.07 | 81597.07 | 0.00 | 289930.28 | 15710.95 |
November | 1876191.55 | 17-NOV-16:49 | 489900.85 | 660080.29 | 64082.80 | 235096.12 | 168711.49 | 40608.29 | 0.00 | 106139.96 | 123.07 |
December | 1982412.30 | 06-DEC-16:40 | 489900.85 | 778371.69 | 64082.80 | 235096.12 | 157123.01 | 40459.01 | 0.00 | 75369.78 | 6.23 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1467095.35 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 109461.18 | 16066.14 | 0.00 | 26980.30 | 0.65 | |
Maximum of Months | 2379332.99 | 489900.85 | 778371.69 | 64082.80 | 235096.12 | 340147.06 | 87549.07 | 0.00 | 393837.46 | 50001.50 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 2729835.69 | 09-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1924870.60 | 06-FEB-05:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 2078691.54 | 06-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 1075687.89 | 29-APR-04:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 1172117.83 | 22-MAY-04:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 643186.02 | 17-JUN-04:19 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 272127.14 | 08-JUL-05:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 661521.95 | 18-AUG-05:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 779421.41 | 19-SEP-04:19 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 1139662.86 | 10-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 1869090.75 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 2020511.49 | 26-DEC-05:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 272127.14 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 2729835.69 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.72 | 0.00 | 25.72 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.60 | 0.00 | 25.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.71 | 0.00 | 25.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 25.67 | 0.00 | 25.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 26.20 | 0.17 | 26.30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.70 | 0.00 | 25.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.67 | 0.00 | 25.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.17 | 25.79 | 0.17 | 25.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 26.20 | 0.17 | 26.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Annual Sum or Average | 0.50 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.83 | 17.28 | 0.33 | 17.37 | 0.00 | 17.37 | 0.00 | 17.37 |
February | 3.67 | 18.72 | 0.33 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
March | 1.83 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 |
April | 0.33 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
May | 0.67 | 18.03 | 0.00 | 18.03 | 0.00 | 18.03 | 0.00 | 18.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
November | 2.00 | 18.43 | 0.17 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
December | 4.50 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 |
Annual Sum or Average | 23.00 | 17.90 | 0.83 | 17.98 | 0.00 | 17.98 | 0.00 | 17.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.83 | 18.87 | 0.33 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.67 | 15.90 | 1.83 | 15.84 | 0.00 | 15.84 | 0.00 | 15.84 |
February | 3.50 | 18.44 | 0.33 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
March | 1.50 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
December | 4.00 | 17.26 | 0.83 | 17.25 | 0.00 | 17.25 | 0.00 | 17.25 |
Annual Sum or Average | 26.33 | 16.65 | 3.00 | 16.62 | 0.00 | 16.62 | 0.00 | 16.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.67 | 18.44 | 1.83 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.67 | 15.72 | 1.83 | 15.67 | 0.00 | 15.67 | 0.00 | 15.67 |
February | 4.50 | 17.51 | 0.50 | 17.26 | 0.00 | 17.26 | 0.00 | 17.26 |
March | 1.67 | 18.15 | 0.00 | 18.15 | 0.00 | 18.15 | 0.00 | 18.15 |
April | 0.17 | 19.40 | 0.00 | 19.40 | 0.67 | 26.11 | 0.67 | 26.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.15 | 3.67 | 28.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.71 | 5.00 | 28.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.67 | 2.00 | 28.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.99 | 3.00 | 27.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 |
December | 5.50 | 16.68 | 0.83 | 16.43 | 0.00 | 16.43 | 0.00 | 16.43 |
Annual Sum or Average | 30.17 | 16.37 | 3.17 | 16.25 | 14.33 | 19.89 | 14.33 | 21.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.67 | 19.40 | 1.83 | 19.40 | 5.00 | 28.71 | 5.00 | 28.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.17 | 15.81 | 2.17 | 15.73 | 0.33 | 15.92 | 0.33 | 16.11 |
February | 5.67 | 17.37 | 0.50 | 17.17 | 1.33 | 19.21 | 1.33 | 20.63 |
March | 3.00 | 16.91 | 0.00 | 16.91 | 0.50 | 18.44 | 0.50 | 19.59 |
April | 0.17 | 19.23 | 0.00 | 19.23 | 1.00 | 26.64 | 1.00 | 27.21 |
May | 0.33 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.85 | 4.17 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.22 | 3.00 | 28.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.36 | 5.50 | 28.38 |
October | 0.17 | 19.28 | 0.00 | 19.28 | 2.50 | 27.93 | 2.50 | 28.21 |
November | 1.50 | 18.79 | 0.17 | 18.95 | 1.00 | 22.21 | 1.00 | 23.69 |
December | 6.33 | 16.56 | 0.83 | 16.33 | 0.00 | 16.33 | 0.00 | 16.33 |
Annual Sum or Average | 35.33 | 16.48 | 3.67 | 16.36 | 19.67 | 20.32 | 19.33 | 22.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 18.17 | 19.28 | 2.17 | 19.28 | 5.67 | 28.36 | 5.50 | 28.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.17 | 17.68 | 0.00 | 17.68 | 0.00 | 17.68 | 0.00 | 17.68 |
February | 2.33 | 18.89 | 0.00 | 18.89 | 0.17 | 19.45 | 0.17 | 19.94 |
March | 0.83 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.87 | 0.83 | 28.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.46 | 1.33 | 28.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.45 | 1.67 | 28.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.89 | 5.50 | 28.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.27 | 3.50 | 28.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.60 | 2.33 | 28.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 28.21 | 0.67 | 28.21 |
November | 0.33 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
December | 0.83 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Annual Sum or Average | 9.50 | 18.19 | 0.00 | 18.19 | 30.50 | 26.11 | 16.00 | 26.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 | 0.00 | 17.68 |
Maximum of Months | 5.17 | 19.14 | 0.00 | 19.14 | 10.00 | 28.89 | 5.50 | 28.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.83 | 15.18 | 9.83 | 15.10 | 0.00 | 15.10 | 0.00 | 15.10 |
February | 20.83 | 16.12 | 3.67 | 16.01 | 0.00 | 16.01 | 0.00 | 16.01 |
March | 14.67 | 16.46 | 1.50 | 16.35 | 0.00 | 16.35 | 0.00 | 16.35 |
April | 2.17 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
May | 2.00 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.33 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
October | 1.50 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 |
November | 13.50 | 16.14 | 3.17 | 15.89 | 0.00 | 15.89 | 0.00 | 15.89 |
December | 33.17 | 15.45 | 7.17 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
Annual Sum or Average | 132.00 | 15.80 | 25.33 | 15.64 | 0.00 | 15.64 | 0.00 | 15.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.83 | 19.35 | 9.83 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 74.33 | 16.61 | 9.17 | 16.45 | 0.00 | 16.45 | 0.00 | 16.45 |
February | 31.67 | 17.16 | 2.33 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
March | 17.33 | 16.95 | 0.67 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 |
April | 2.00 | 19.08 | 0.00 | 19.08 | 0.33 | 20.25 | 0.33 | 21.13 |
May | 2.50 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.20 | 3.67 | 28.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.69 | 5.67 | 28.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.73 | 2.33 | 28.73 |
September | 0.33 | 19.33 | 0.00 | 19.33 | 2.50 | 26.94 | 2.50 | 27.42 |
October | 1.50 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
November | 19.00 | 17.39 | 1.83 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
December | 49.17 | 16.56 | 5.17 | 16.35 | 0.00 | 16.35 | 0.00 | 16.35 |
Annual Sum or Average | 197.83 | 16.86 | 19.17 | 16.69 | 14.50 | 17.43 | 14.50 | 18.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.35 | 0.00 | 16.35 |
Maximum of Months | 74.33 | 19.33 | 9.17 | 19.33 | 5.67 | 28.73 | 5.67 | 28.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.17 | 15.34 | 4.67 | 15.30 | 0.17 | 15.36 | 0.17 | 15.41 |
February | 15.17 | 16.57 | 1.17 | 16.59 | 1.50 | 17.63 | 1.50 | 18.51 |
March | 12.17 | 16.53 | 0.83 | 16.42 | 0.50 | 16.84 | 0.50 | 17.24 |
April | 1.50 | 19.08 | 0.00 | 19.08 | 0.83 | 22.31 | 0.83 | 23.83 |
May | 1.83 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.86 | 4.00 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.28 | 2.67 | 28.32 |
September | 0.33 | 19.40 | 0.00 | 19.40 | 5.67 | 28.13 | 5.17 | 28.41 |
October | 1.33 | 18.77 | 0.00 | 18.77 | 2.67 | 25.46 | 2.67 | 26.80 |
November | 8.67 | 16.73 | 0.67 | 16.59 | 1.17 | 17.85 | 1.17 | 18.86 |
December | 24.67 | 15.77 | 3.33 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 |
Annual Sum or Average | 97.83 | 16.08 | 10.67 | 15.98 | 19.50 | 17.86 | 18.67 | 19.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.17 | 19.40 | 4.67 | 19.40 | 5.67 | 28.28 | 5.17 | 28.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.67 | 15.26 | 6.50 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 |
February | 16.83 | 16.28 | 2.00 | 16.15 | 0.00 | 16.15 | 0.00 | 16.15 |
March | 11.83 | 16.46 | 0.83 | 16.35 | 0.00 | 16.35 | 0.00 | 16.35 |
April | 1.17 | 19.07 | 0.00 | 19.07 | 1.00 | 23.47 | 0.50 | 24.49 |
May | 1.83 | 18.51 | 0.00 | 18.51 | 2.67 | 24.26 | 1.17 | 24.99 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.44 | 1.33 | 28.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 29.02 | 3.33 | 28.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.87 | 1.00 | 28.96 |
September | 0.17 | 19.40 | 0.00 | 19.40 | 2.67 | 28.22 | 1.67 | 28.42 |
October | 1.17 | 18.66 | 0.00 | 18.66 | 0.33 | 20.63 | 0.33 | 21.88 |
November | 9.83 | 16.51 | 1.83 | 16.24 | 0.00 | 16.24 | 0.00 | 16.24 |
December | 23.50 | 15.80 | 4.33 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 |
Annual Sum or Average | 101.00 | 15.97 | 15.50 | 15.81 | 19.17 | 17.63 | 9.33 | 18.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.21 | 0.00 | 15.21 |
Maximum of Months | 34.67 | 19.40 | 6.50 | 19.40 | 6.67 | 29.02 | 3.33 | 28.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 70.83 | 14.41 | 16.67 | 14.35 | 0.00 | 14.35 | 0.00 | 14.35 |
February | 43.00 | 15.19 | 8.17 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
March | 31.33 | 15.48 | 6.00 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 |
April | 9.17 | 17.19 | 0.83 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
May | 10.00 | 16.12 | 1.67 | 15.92 | 0.00 | 15.92 | 0.00 | 15.92 |
June | 0.83 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.33 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
September | 2.00 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
October | 8.83 | 17.29 | 0.33 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
November | 35.50 | 15.09 | 9.17 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
December | 62.83 | 14.62 | 16.67 | 14.53 | 0.00 | 14.53 | 0.00 | 14.53 |
Annual Sum or Average | 274.67 | 15.09 | 59.50 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.83 | 19.27 | 16.67 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 67.50 | 14.40 | 13.50 | 14.35 | 0.00 | 14.35 | 0.00 | 14.35 |
February | 40.33 | 15.23 | 6.17 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
March | 29.17 | 15.51 | 4.67 | 15.43 | 0.00 | 15.43 | 0.00 | 15.43 |
April | 9.17 | 17.18 | 0.67 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
May | 10.17 | 16.08 | 1.50 | 15.90 | 0.00 | 15.90 | 0.00 | 15.90 |
June | 0.67 | 19.25 | 0.00 | 19.25 | 2.17 | 25.84 | 2.17 | 26.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.41 | 5.67 | 28.41 |
August | 0.33 | 19.15 | 0.00 | 19.15 | 2.50 | 27.62 | 2.50 | 28.15 |
September | 1.67 | 18.81 | 0.00 | 18.81 | 2.17 | 23.90 | 2.17 | 25.32 |
October | 9.00 | 17.16 | 0.67 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
November | 31.83 | 15.18 | 5.50 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 |
December | 61.17 | 14.64 | 14.67 | 14.57 | 0.00 | 14.57 | 0.00 | 14.57 |
Annual Sum or Average | 261.00 | 15.11 | 47.33 | 15.01 | 12.50 | 15.53 | 12.50 | 16.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 | 0.00 | 14.35 |
Maximum of Months | 67.50 | 19.25 | 14.67 | 19.25 | 5.67 | 28.41 | 5.67 | 28.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 58.67 | 14.54 | 10.00 | 14.50 | 0.00 | 14.50 | 0.00 | 14.50 |
February | 30.17 | 15.49 | 4.00 | 15.51 | 0.83 | 15.82 | 0.83 | 16.11 |
March | 23.50 | 15.68 | 2.83 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 |
April | 7.67 | 17.59 | 0.33 | 17.48 | 0.33 | 17.87 | 0.33 | 18.24 |
May | 9.33 | 16.18 | 1.33 | 15.99 | 0.00 | 15.99 | 0.00 | 15.99 |
June | 1.17 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
July | 0.17 | 19.42 | 0.00 | 19.42 | 2.00 | 27.54 | 2.00 | 27.87 |
August | 0.33 | 19.20 | 0.00 | 19.20 | 2.00 | 27.31 | 1.83 | 27.94 |
September | 1.50 | 18.86 | 0.00 | 18.86 | 3.50 | 25.93 | 3.17 | 27.15 |
October | 7.33 | 17.41 | 0.00 | 17.41 | 1.17 | 18.98 | 1.17 | 20.17 |
November | 24.17 | 15.45 | 3.17 | 15.39 | 0.00 | 15.39 | 0.00 | 15.39 |
December | 50.67 | 14.78 | 9.00 | 14.70 | 0.00 | 14.70 | 0.00 | 14.70 |
Annual Sum or Average | 214.67 | 15.30 | 30.67 | 15.21 | 9.83 | 15.73 | 9.33 | 16.18 |
Minimum of Months | 0.17 | 14.54 | 0.00 | 14.50 | 0.00 | 14.50 | 0.00 | 14.50 |
Maximum of Months | 58.67 | 19.42 | 10.00 | 19.42 | 3.50 | 27.54 | 3.17 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 59.50 | 14.52 | 12.50 | 14.46 | 0.00 | 14.46 | 0.00 | 14.46 |
February | 29.83 | 15.33 | 5.50 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 |
March | 21.83 | 15.84 | 2.83 | 15.68 | 0.00 | 15.68 | 0.00 | 15.68 |
April | 5.33 | 18.29 | 0.00 | 18.29 | 1.00 | 19.89 | 0.50 | 20.50 |
May | 6.00 | 16.94 | 0.00 | 16.94 | 2.33 | 20.10 | 1.00 | 20.93 |
June | 0.50 | 19.25 | 0.00 | 19.25 | 3.33 | 27.33 | 1.17 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.98 | 3.33 | 28.96 |
August | 0.17 | 19.14 | 0.00 | 19.14 | 2.17 | 28.52 | 1.17 | 28.77 |
September | 1.33 | 18.92 | 0.00 | 18.92 | 2.50 | 25.53 | 1.67 | 26.59 |
October | 6.00 | 17.56 | 0.00 | 17.56 | 0.00 | 17.56 | 0.00 | 17.56 |
November | 24.17 | 15.41 | 5.17 | 15.28 | 0.00 | 15.28 | 0.00 | 15.28 |
December | 52.00 | 14.84 | 12.17 | 14.76 | 0.00 | 14.76 | 0.00 | 14.76 |
Annual Sum or Average | 206.67 | 15.26 | 38.17 | 15.13 | 18.67 | 16.10 | 8.83 | 16.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.46 | 0.00 | 14.46 |
Maximum of Months | 59.50 | 19.25 | 12.50 | 19.25 | 7.33 | 28.98 | 3.33 | 28.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 117.17 | 29.11 | 61.83 | 29.15 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 33.12 | 1.00 | 33.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 38.81 | 7.50 | 39.30 |
Annual Sum or Average | 0.00 | 0.00 | 131.67 | 30.04 | 70.33 | 30.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 117.17 | 38.81 | 61.83 | 39.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 43.50 | 28.34 | 30.17 | 28.38 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 31.28 | 1.00 | 31.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 36.64 | 7.50 | 37.06 |
Annual Sum or Average | 0.00 | 0.00 | 57.83 | 30.10 | 38.67 | 30.19 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 43.50 | 36.64 | 30.17 | 37.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.86 | 6.50 | 27.86 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 29.28 | 1.00 | 29.45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 34.50 | 7.50 | 34.82 |
Annual Sum or Average | 0.00 | 0.00 | 20.67 | 31.61 | 15.00 | 31.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 34.50 | 7.50 | 34.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.58 | 13.83 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.58 | 5.17 | 27.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.57 | 4.83 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.58 | 1.33 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 28.67 | 27.58 | 25.17 | 27.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.58 | 13.83 | 27.58 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 461.83 | 22.93 | 23.67 | 23.05 | 16.50 | 23.12 |
February | 402.33 | 23.17 | 1.17 | 23.17 | 1.17 | 23.16 |
March | 449.67 | 23.58 | 0.83 | 23.57 | 0.83 | 23.56 |
April | 353.17 | 23.79 | 10.50 | 23.84 | 0.00 | 23.84 |
May | 296.17 | 23.63 | 63.00 | 23.97 | 0.00 | 23.97 |
June | 61.00 | 23.79 | 191.17 | 24.59 | 0.00 | 24.59 |
July | 7.50 | 23.81 | 326.00 | 24.78 | 0.00 | 24.78 |
August | 6.00 | 23.50 | 217.33 | 24.98 | 0.00 | 24.98 |
September | 92.33 | 23.45 | 190.67 | 24.60 | 1.83 | 24.60 |
October | 108.33 | 23.78 | 105.33 | 24.98 | 0.00 | 24.98 |
November | 247.33 | 23.78 | 73.00 | 24.34 | 0.00 | 24.34 |
December | 395.67 | 23.44 | 12.00 | 23.51 | 0.33 | 23.50 |
Annual Sum or Average | 2881.33 | 23.46 | 1214.67 | 23.96 | 20.67 | 23.97 |
Minimum of Months | 6.00 | 22.93 | 0.83 | 23.05 | 0.00 | 23.12 |
Maximum of Months | 461.83 | 23.81 | 326.00 | 24.98 | 16.50 | 24.98 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 466.50 | 23.24 | 24.17 | 23.14 | 22.50 | 23.05 |
February | 408.50 | 23.42 | 5.00 | 23.39 | 5.00 | 23.36 |
March | 335.67 | 23.57 | 2.00 | 23.56 | 2.00 | 23.54 |
April | 152.00 | 23.78 | 33.17 | 24.13 | 0.00 | 24.13 |
May | 154.67 | 23.78 | 66.00 | 24.22 | 0.00 | 24.22 |
June | 32.33 | 23.79 | 204.00 | 24.33 | 4.33 | 24.34 |
July | 4.17 | 23.85 | 361.33 | 24.36 | 0.67 | 24.36 |
August | 0.00 | 0.00 | 289.17 | 24.44 | 0.00 | 24.44 |
September | 74.83 | 23.78 | 189.67 | 24.37 | 11.83 | 24.36 |
October | 141.17 | 23.77 | 53.83 | 24.29 | 0.00 | 24.29 |
November | 227.33 | 23.81 | 23.50 | 23.99 | 0.00 | 23.99 |
December | 344.17 | 23.68 | 0.83 | 23.69 | 0.00 | 23.69 |
Annual Sum or Average | 2341.33 | 23.57 | 1252.67 | 23.90 | 46.33 | 23.88 |
Minimum of Months | 0.00 | 0.00 | 0.83 | 23.14 | 0.00 | 23.05 |
Maximum of Months | 466.50 | 23.85 | 361.33 | 24.44 | 22.50 | 24.44 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.02 | 121.33 | 21.70 | 121.33 | 21.48 |
February | 449.67 | 22.73 | 38.33 | 22.55 | 38.33 | 22.40 |
March | 489.17 | 23.19 | 18.33 | 23.08 | 18.33 | 22.98 |
April | 359.50 | 23.44 | 0.00 | 23.44 | 0.00 | 23.44 |
May | 268.17 | 23.50 | 42.50 | 23.70 | 0.00 | 23.70 |
June | 123.83 | 23.52 | 149.50 | 23.96 | 5.00 | 23.97 |
July | 57.00 | 23.72 | 257.50 | 24.23 | 7.17 | 24.25 |
August | 59.83 | 23.55 | 163.67 | 24.27 | 0.00 | 24.27 |
September | 172.00 | 23.48 | 124.17 | 23.88 | 12.67 | 23.89 |
October | 320.33 | 23.46 | 0.00 | 23.46 | 0.00 | 23.46 |
November | 432.50 | 23.12 | 19.33 | 23.02 | 19.33 | 22.92 |
December | 495.17 | 22.42 | 82.00 | 22.10 | 82.00 | 21.87 |
Annual Sum or Average | 3729.17 | 22.97 | 1016.67 | 23.05 | 304.17 | 22.90 |
Minimum of Months | 57.00 | 22.02 | 0.00 | 21.70 | 0.00 | 21.48 |
Maximum of Months | 502.00 | 23.72 | 257.50 | 24.27 | 121.33 | 24.27 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.41 | 370.33 | 20.24 | 370.33 | 20.17 |
February | 454.00 | 20.88 | 250.50 | 20.62 | 250.50 | 20.50 |
March | 514.00 | 21.43 | 169.17 | 21.10 | 169.17 | 20.90 |
April | 459.67 | 21.95 | 86.67 | 21.67 | 86.67 | 21.47 |
May | 406.00 | 22.47 | 50.33 | 22.32 | 36.67 | 22.15 |
June | 236.83 | 22.82 | 131.17 | 23.30 | 5.50 | 23.32 |
July | 163.50 | 23.01 | 234.67 | 23.69 | 11.50 | 23.71 |
August | 196.00 | 22.95 | 147.67 | 23.50 | 0.00 | 23.50 |
September | 341.50 | 22.49 | 88.33 | 22.68 | 34.83 | 22.65 |
October | 484.00 | 21.81 | 85.50 | 21.54 | 85.50 | 21.34 |
November | 489.00 | 21.13 | 201.83 | 20.80 | 201.83 | 20.62 |
December | 497.00 | 20.58 | 322.17 | 20.34 | 322.17 | 20.23 |
Annual Sum or Average | 4743.50 | 21.59 | 2138.33 | 21.47 | 1574.67 | 21.22 |
Minimum of Months | 163.50 | 20.41 | 50.33 | 20.24 | 0.00 | 20.17 |
Maximum of Months | 514.00 | 23.01 | 370.33 | 23.69 | 370.33 | 23.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.49 | 373.67 | 20.38 | 373.67 | 20.34 |
February | 454.00 | 20.91 | 244.83 | 20.73 | 244.83 | 20.65 |
March | 514.00 | 21.43 | 138.17 | 21.22 | 138.17 | 21.08 |
April | 444.33 | 22.22 | 22.17 | 22.15 | 22.17 | 22.09 |
May | 367.00 | 22.47 | 59.33 | 22.63 | 13.67 | 22.57 |
June | 164.00 | 22.94 | 193.00 | 23.57 | 0.00 | 23.57 |
July | 62.00 | 23.19 | 337.00 | 24.06 | 1.00 | 24.06 |
August | 126.17 | 23.01 | 231.50 | 23.78 | 0.00 | 23.78 |
September | 287.33 | 22.41 | 112.17 | 22.96 | 4.00 | 22.95 |
October | 464.67 | 22.18 | 15.33 | 22.14 | 15.33 | 22.10 |
November | 489.00 | 21.49 | 131.67 | 21.26 | 131.67 | 21.10 |
December | 497.00 | 20.79 | 286.00 | 20.62 | 286.00 | 20.54 |
Annual Sum or Average | 4371.50 | 21.64 | 2144.83 | 21.76 | 1230.50 | 21.54 |
Minimum of Months | 62.00 | 20.49 | 15.33 | 20.38 | 0.00 | 20.34 |
Maximum of Months | 514.00 | 23.19 | 373.67 | 24.06 | 373.67 | 24.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.33 | 20.56 | 354.00 | 20.43 | 354.00 | 20.37 |
February | 436.33 | 21.00 | 221.00 | 20.82 | 219.17 | 20.72 |
March | 479.00 | 21.31 | 152.33 | 21.19 | 138.83 | 21.06 |
April | 382.33 | 21.78 | 75.67 | 22.01 | 27.33 | 21.95 |
May | 317.00 | 22.01 | 115.83 | 22.48 | 17.00 | 22.41 |
June | 173.17 | 22.76 | 253.67 | 23.65 | 14.33 | 23.75 |
July | 118.83 | 23.48 | 342.67 | 24.11 | 25.33 | 24.24 |
August | 175.50 | 22.67 | 282.67 | 23.60 | 6.83 | 23.66 |
September | 276.00 | 22.18 | 163.17 | 23.01 | 12.00 | 23.08 |
October | 426.83 | 21.93 | 38.33 | 22.03 | 14.50 | 21.99 |
November | 481.17 | 21.39 | 137.50 | 21.20 | 136.33 | 21.07 |
December | 497.00 | 20.72 | 286.00 | 20.57 | 286.00 | 20.50 |
Annual Sum or Average | 4264.50 | 21.52 | 2422.83 | 21.83 | 1251.67 | 21.64 |
Minimum of Months | 118.83 | 20.56 | 38.33 | 20.43 | 6.83 | 20.37 |
Maximum of Months | 501.33 | 23.48 | 354.00 | 24.11 | 354.00 | 24.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 446.00 | 20.78 | 315.67 | 20.66 | 297.67 | 20.54 |
February | 362.00 | 21.26 | 230.33 | 21.30 | 187.67 | 21.13 |
March | 405.83 | 21.30 | 207.67 | 21.41 | 147.33 | 21.23 |
April | 357.33 | 21.79 | 120.50 | 22.04 | 55.17 | 21.92 |
May | 323.33 | 21.93 | 135.17 | 22.32 | 37.00 | 22.18 |
June | 210.00 | 22.31 | 202.83 | 23.25 | 0.83 | 23.26 |
July | 134.67 | 22.97 | 309.67 | 23.91 | 14.67 | 24.00 |
August | 166.83 | 22.79 | 278.50 | 23.70 | 9.67 | 23.78 |
September | 242.00 | 22.39 | 207.00 | 23.33 | 23.00 | 23.44 |
October | 335.67 | 22.04 | 154.50 | 22.55 | 39.17 | 22.52 |
November | 371.00 | 21.49 | 180.50 | 21.68 | 112.00 | 21.48 |
December | 428.00 | 20.96 | 275.17 | 20.91 | 239.00 | 20.75 |
Annual Sum or Average | 3782.67 | 21.63 | 2617.50 | 22.06 | 1163.17 | 21.86 |
Minimum of Months | 134.67 | 20.78 | 120.50 | 20.66 | 0.83 | 20.54 |
Maximum of Months | 446.00 | 22.97 | 315.67 | 23.91 | 297.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.67 | 20.77 | 292.17 | 20.62 | 292.17 | 20.55 |
February | 427.00 | 21.13 | 159.00 | 21.06 | 146.17 | 20.94 |
March | 459.33 | 21.47 | 91.67 | 21.49 | 64.83 | 21.39 |
April | 331.50 | 22.36 | 87.83 | 22.82 | 5.17 | 22.86 |
May | 302.67 | 22.14 | 142.67 | 22.90 | 8.67 | 22.94 |
June | 184.17 | 22.54 | 251.83 | 23.56 | 14.50 | 23.63 |
July | 103.50 | 23.87 | 382.50 | 24.33 | 47.33 | 24.43 |
August | 103.83 | 23.40 | 379.83 | 24.21 | 31.17 | 24.26 |
September | 279.67 | 22.24 | 170.67 | 23.10 | 13.83 | 23.19 |
October | 404.00 | 22.00 | 59.67 | 22.29 | 4.00 | 22.31 |
November | 433.17 | 21.61 | 70.67 | 21.64 | 50.00 | 21.54 |
December | 483.67 | 21.29 | 133.17 | 21.14 | 129.67 | 21.02 |
Annual Sum or Average | 4013.17 | 21.73 | 2221.67 | 22.26 | 807.50 | 22.14 |
Minimum of Months | 103.50 | 20.77 | 59.67 | 20.62 | 4.00 | 20.55 |
Maximum of Months | 500.67 | 23.87 | 382.50 | 24.33 | 292.17 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.88 | 486.17 | 19.86 | 486.17 | 19.85 |
February | 454.00 | 20.23 | 387.17 | 20.16 | 387.17 | 20.14 |
March | 514.00 | 20.54 | 314.83 | 20.39 | 314.83 | 20.32 |
April | 484.17 | 21.09 | 155.83 | 20.89 | 155.83 | 20.76 |
May | 456.00 | 21.66 | 86.33 | 21.56 | 70.00 | 21.40 |
June | 304.50 | 22.29 | 107.83 | 22.75 | 0.17 | 22.74 |
July | 212.67 | 22.60 | 190.83 | 23.30 | 1.33 | 23.31 |
August | 298.33 | 22.37 | 116.67 | 22.88 | 0.17 | 22.88 |
September | 408.50 | 21.71 | 85.50 | 21.87 | 37.33 | 21.78 |
October | 502.00 | 21.06 | 148.50 | 20.88 | 148.50 | 20.77 |
November | 489.00 | 20.39 | 320.17 | 20.23 | 320.17 | 20.17 |
December | 497.00 | 19.96 | 454.50 | 19.91 | 454.50 | 19.90 |
Annual Sum or Average | 5122.17 | 20.97 | 2854.33 | 20.88 | 2376.17 | 20.68 |
Minimum of Months | 212.67 | 19.88 | 85.50 | 19.86 | 0.17 | 19.85 |
Maximum of Months | 514.00 | 22.60 | 486.17 | 23.30 | 486.17 | 23.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.81 | 395.83 | 19.76 | 395.83 | 19.74 |
February | 382.50 | 20.41 | 279.67 | 20.25 | 279.67 | 20.18 |
March | 421.17 | 20.75 | 227.17 | 20.53 | 224.17 | 20.42 |
April | 348.00 | 21.27 | 125.50 | 21.23 | 98.00 | 21.05 |
May | 313.50 | 21.60 | 111.83 | 21.80 | 50.50 | 21.60 |
June | 186.83 | 22.46 | 187.17 | 23.42 | 15.67 | 23.54 |
July | 138.33 | 23.25 | 256.00 | 24.05 | 28.17 | 24.22 |
August | 186.50 | 22.44 | 201.83 | 23.44 | 7.83 | 23.51 |
September | 273.83 | 21.85 | 124.00 | 22.53 | 25.33 | 22.53 |
October | 403.33 | 21.33 | 101.50 | 21.18 | 94.67 | 21.04 |
November | 416.00 | 20.54 | 249.17 | 20.35 | 249.17 | 20.26 |
December | 422.00 | 19.86 | 371.00 | 19.79 | 371.00 | 19.76 |
Annual Sum or Average | 3919.00 | 21.00 | 2630.67 | 21.15 | 1840.00 | 20.93 |
Minimum of Months | 138.33 | 19.81 | 101.50 | 19.76 | 7.83 | 19.74 |
Maximum of Months | 427.00 | 23.25 | 395.83 | 24.05 | 395.83 | 24.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 459.33 | 20.46 | 358.83 | 20.34 | 345.83 | 20.24 |
February | 363.67 | 20.95 | 264.33 | 21.00 | 220.17 | 20.83 |
March | 408.83 | 20.96 | 265.83 | 21.08 | 199.83 | 20.89 |
April | 367.33 | 21.38 | 173.00 | 21.56 | 109.67 | 21.37 |
May | 346.50 | 21.66 | 157.00 | 21.97 | 64.33 | 21.77 |
June | 238.83 | 22.09 | 186.50 | 23.03 | 1.83 | 23.03 |
July | 175.83 | 22.66 | 275.83 | 23.69 | 13.00 | 23.78 |
August | 202.00 | 22.43 | 257.67 | 23.49 | 8.33 | 23.55 |
September | 261.50 | 22.21 | 214.83 | 23.11 | 40.83 | 23.18 |
October | 345.83 | 21.70 | 192.67 | 22.16 | 79.33 | 22.04 |
November | 392.00 | 21.14 | 241.17 | 21.21 | 180.17 | 21.00 |
December | 446.50 | 20.48 | 326.00 | 20.35 | 303.67 | 20.22 |
Annual Sum or Average | 4008.17 | 21.33 | 2913.67 | 21.69 | 1567.00 | 21.45 |
Minimum of Months | 175.83 | 20.46 | 157.00 | 20.34 | 1.83 | 20.22 |
Maximum of Months | 459.33 | 22.66 | 358.83 | 23.69 | 345.83 | 23.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.03 | 455.17 | 19.97 | 455.17 | 19.95 |
February | 440.00 | 20.49 | 312.17 | 20.35 | 309.17 | 20.28 |
March | 488.33 | 20.76 | 254.17 | 20.63 | 241.17 | 20.52 |
April | 425.17 | 21.25 | 142.50 | 21.30 | 107.50 | 21.17 |
May | 381.83 | 21.69 | 143.67 | 22.01 | 57.83 | 21.88 |
June | 273.33 | 22.05 | 182.00 | 22.96 | 8.17 | 23.01 |
July | 223.33 | 22.54 | 242.17 | 23.51 | 27.33 | 23.62 |
August | 258.67 | 22.17 | 198.33 | 23.11 | 10.00 | 23.16 |
September | 348.67 | 21.68 | 130.17 | 22.24 | 32.50 | 22.24 |
October | 455.83 | 21.21 | 120.67 | 21.18 | 98.00 | 21.06 |
November | 480.50 | 20.69 | 250.00 | 20.48 | 248.83 | 20.37 |
December | 497.00 | 20.12 | 397.33 | 20.00 | 397.33 | 19.96 |
Annual Sum or Average | 4774.67 | 21.05 | 2828.33 | 21.18 | 1993.00 | 20.99 |
Minimum of Months | 223.33 | 20.03 | 120.67 | 19.97 | 8.17 | 19.95 |
Maximum of Months | 502.00 | 22.54 | 455.17 | 23.51 | 455.17 | 23.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.73 | 495.00 | 19.72 | 495.00 | 19.71 |
February | 454.00 | 19.93 | 431.17 | 19.90 | 431.17 | 19.89 |
March | 514.00 | 20.21 | 386.83 | 20.10 | 386.83 | 20.05 |
April | 485.00 | 20.54 | 253.33 | 20.31 | 253.33 | 20.20 |
May | 478.33 | 21.21 | 148.17 | 21.07 | 134.83 | 20.91 |
June | 356.83 | 21.76 | 105.33 | 22.12 | 24.33 | 22.07 |
July | 276.33 | 21.99 | 154.33 | 22.66 | 8.00 | 22.64 |
August | 353.00 | 21.87 | 106.33 | 22.29 | 11.83 | 22.25 |
September | 441.33 | 21.28 | 127.67 | 21.26 | 103.50 | 21.14 |
October | 502.00 | 20.42 | 277.50 | 20.21 | 277.50 | 20.11 |
November | 489.00 | 19.98 | 406.33 | 19.89 | 406.33 | 19.85 |
December | 497.00 | 19.76 | 480.17 | 19.74 | 480.17 | 19.73 |
Annual Sum or Average | 5348.83 | 20.61 | 3372.17 | 20.49 | 3012.83 | 20.33 |
Minimum of Months | 276.33 | 19.73 | 105.33 | 19.72 | 8.00 | 19.71 |
Maximum of Months | 514.00 | 21.99 | 495.00 | 22.66 | 495.00 | 22.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.76 | 480.50 | 19.74 | 480.50 | 19.73 |
February | 454.00 | 20.12 | 357.83 | 19.99 | 357.83 | 19.94 |
March | 504.33 | 20.47 | 311.17 | 20.24 | 311.17 | 20.13 |
April | 421.83 | 20.91 | 199.33 | 20.75 | 172.00 | 20.54 |
May | 369.17 | 21.34 | 164.83 | 21.45 | 97.17 | 21.22 |
June | 209.50 | 22.10 | 251.00 | 23.17 | 24.50 | 23.17 |
July | 160.17 | 22.92 | 322.00 | 23.86 | 30.67 | 23.98 |
August | 206.00 | 22.21 | 278.67 | 23.33 | 15.67 | 23.36 |
September | 337.17 | 21.64 | 180.83 | 22.16 | 74.17 | 22.08 |
October | 487.33 | 20.79 | 202.67 | 20.51 | 200.83 | 20.35 |
November | 489.00 | 20.07 | 357.00 | 19.92 | 357.00 | 19.86 |
December | 497.00 | 19.79 | 465.17 | 19.75 | 465.17 | 19.73 |
Annual Sum or Average | 4637.50 | 20.71 | 3571.00 | 20.88 | 2586.67 | 20.66 |
Minimum of Months | 160.17 | 19.76 | 164.83 | 19.74 | 15.67 | 19.73 |
Maximum of Months | 504.33 | 22.92 | 480.50 | 23.86 | 480.50 | 23.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 481.50 | 20.13 | 399.17 | 19.98 | 396.50 | 19.92 |
February | 393.67 | 20.53 | 298.00 | 20.46 | 269.83 | 20.32 |
March | 432.17 | 20.52 | 324.00 | 20.54 | 273.67 | 20.37 |
April | 392.50 | 20.77 | 242.50 | 20.82 | 188.17 | 20.59 |
May | 374.83 | 21.23 | 199.50 | 21.45 | 117.33 | 21.23 |
June | 277.67 | 21.66 | 194.17 | 22.49 | 31.67 | 22.40 |
July | 218.17 | 22.11 | 253.50 | 23.20 | 18.83 | 23.24 |
August | 244.83 | 21.99 | 244.67 | 23.04 | 18.00 | 23.05 |
September | 312.00 | 21.74 | 226.33 | 22.43 | 83.17 | 22.35 |
October | 376.00 | 20.90 | 254.17 | 21.15 | 163.00 | 20.92 |
November | 432.33 | 20.56 | 299.50 | 20.47 | 265.17 | 20.32 |
December | 469.00 | 20.09 | 369.17 | 19.92 | 364.00 | 19.84 |
Annual Sum or Average | 4404.67 | 20.87 | 3304.67 | 21.11 | 2189.33 | 20.87 |
Minimum of Months | 218.17 | 20.09 | 194.17 | 19.92 | 18.00 | 19.84 |
Maximum of Months | 481.50 | 22.11 | 399.17 | 23.20 | 396.50 | 23.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.82 | 468.50 | 19.77 | 468.50 | 19.76 |
February | 445.83 | 20.23 | 352.83 | 20.09 | 350.67 | 20.03 |
March | 492.50 | 20.48 | 326.17 | 20.33 | 314.67 | 20.23 |
April | 428.50 | 20.82 | 217.17 | 20.78 | 183.00 | 20.62 |
May | 390.50 | 21.38 | 184.67 | 21.65 | 100.33 | 21.48 |
June | 292.17 | 21.83 | 192.50 | 22.71 | 33.00 | 22.75 |
July | 248.17 | 22.30 | 235.50 | 23.27 | 40.17 | 23.38 |
August | 287.50 | 22.01 | 198.50 | 22.90 | 21.67 | 22.94 |
September | 372.00 | 21.49 | 164.67 | 21.89 | 82.00 | 21.82 |
October | 465.50 | 20.76 | 219.33 | 20.61 | 199.00 | 20.46 |
November | 485.67 | 20.29 | 335.33 | 20.11 | 334.67 | 20.03 |
December | 497.00 | 19.88 | 438.17 | 19.81 | 438.17 | 19.78 |
Annual Sum or Average | 4907.33 | 20.78 | 3333.33 | 20.88 | 2565.83 | 20.69 |
Minimum of Months | 248.17 | 19.82 | 164.67 | 19.77 | 21.67 | 19.76 |
Maximum of Months | 502.00 | 22.30 | 468.50 | 23.27 | 468.50 | 23.38 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.17 | 30.31 | 422.50 | 27.35 | 7.17 | 27.40 |
February | 3.67 | 28.91 | 398.50 | 27.04 | 3.67 | 27.05 |
March | 6.00 | 27.00 | 487.17 | 27.00 | 6.00 | 27.00 |
April | 29.00 | 27.00 | 485.00 | 27.00 | 29.00 | 27.00 |
May | 13.33 | 27.00 | 508.00 | 27.00 | 13.33 | 27.00 |
June | 102.17 | 27.00 | 496.00 | 27.00 | 102.17 | 27.00 |
July | 230.67 | 27.00 | 497.00 | 27.00 | 230.67 | 27.00 |
August | 273.33 | 27.00 | 514.00 | 27.00 | 273.33 | 27.00 |
September | 54.50 | 27.00 | 485.00 | 27.00 | 54.50 | 27.00 |
October | 12.67 | 27.00 | 502.00 | 27.00 | 12.67 | 27.00 |
November | 10.67 | 27.00 | 489.00 | 27.00 | 10.67 | 27.00 |
December | 11.33 | 35.63 | 487.33 | 27.39 | 11.33 | 27.58 |
Annual Sum or Average | 754.50 | 27.17 | 5771.50 | 27.06 | 754.50 | 27.07 |
Minimum of Months | 3.67 | 27.00 | 398.50 | 27.00 | 3.67 | 27.00 |
Maximum of Months | 273.33 | 35.63 | 514.00 | 27.39 | 273.33 | 27.58 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 44.00 | 26.47 | 241.67 | 27.06 | 0.00 | 27.06 |
February | 15.83 | 27.33 | 296.67 | 27.03 | 2.17 | 27.05 |
March | 14.17 | 27.00 | 431.50 | 27.00 | 2.83 | 27.00 |
April | 7.00 | 27.00 | 472.17 | 27.00 | 7.00 | 27.00 |
May | 6.67 | 27.00 | 490.33 | 27.00 | 6.67 | 27.00 |
June | 45.50 | 27.00 | 496.00 | 27.00 | 45.50 | 27.00 |
July | 102.33 | 27.00 | 497.00 | 27.00 | 102.33 | 27.00 |
August | 106.83 | 27.00 | 514.00 | 27.00 | 106.83 | 27.00 |
September | 23.50 | 27.00 | 485.00 | 27.00 | 23.50 | 27.00 |
October | 5.83 | 27.00 | 501.67 | 27.00 | 5.83 | 27.00 |
November | 1.00 | 27.00 | 402.83 | 27.00 | 1.00 | 27.00 |
December | 23.17 | 30.46 | 338.67 | 27.44 | 7.50 | 27.65 |
Annual Sum or Average | 395.83 | 27.16 | 5167.50 | 27.03 | 311.17 | 27.05 |
Minimum of Months | 1.00 | 26.47 | 241.67 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 106.83 | 30.46 | 514.00 | 27.44 | 106.83 | 27.65 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 164.67 | 25.47 | 132.00 | 25.88 | 21.33 | 25.68 |
February | 68.50 | 27.00 | 177.33 | 27.01 | 0.50 | 27.01 |
March | 45.67 | 27.00 | 305.17 | 27.00 | 1.50 | 27.00 |
April | 23.17 | 27.00 | 396.67 | 27.00 | 9.67 | 27.00 |
May | 30.17 | 26.69 | 459.50 | 26.98 | 13.83 | 26.98 |
June | 80.67 | 27.00 | 495.00 | 27.00 | 80.67 | 27.00 |
July | 142.33 | 27.00 | 497.00 | 27.00 | 142.33 | 27.00 |
August | 135.67 | 27.00 | 514.00 | 27.00 | 135.67 | 27.00 |
September | 38.00 | 27.00 | 469.67 | 27.00 | 35.83 | 27.00 |
October | 14.67 | 27.00 | 397.33 | 27.00 | 5.17 | 27.00 |
November | 47.83 | 27.00 | 270.83 | 27.00 | 0.00 | 27.00 |
December | 79.33 | 27.76 | 197.83 | 27.44 | 7.00 | 27.64 |
Annual Sum or Average | 870.67 | 26.77 | 4312.33 | 26.96 | 453.50 | 26.96 |
Minimum of Months | 14.67 | 25.47 | 132.00 | 25.88 | 0.00 | 25.68 |
Maximum of Months | 164.67 | 27.76 | 514.00 | 27.44 | 142.33 | 27.64 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 207.33 | 27.22 | 502.00 | 27.19 | 207.33 | 27.20 |
February | 0.33 | 23.38 | 371.83 | 24.09 | 0.00 | 24.09 |
March | 0.00 | 0.00 | 496.33 | 24.43 | 0.00 | 24.43 |
April | 218.83 | 26.24 | 484.83 | 25.30 | 218.83 | 25.52 |
May | 384.17 | 27.22 | 508.00 | 27.21 | 384.17 | 27.21 |
June | 191.33 | 26.98 | 491.00 | 25.84 | 189.17 | 26.11 |
July | 445.00 | 26.73 | 494.00 | 26.60 | 444.83 | 26.64 |
August | 484.33 | 26.77 | 514.00 | 26.65 | 484.33 | 26.69 |
September | 485.00 | 27.11 | 485.00 | 27.11 | 485.00 | 27.11 |
October | 23.33 | 27.00 | 500.33 | 24.58 | 22.50 | 24.69 |
November | 140.67 | 25.59 | 488.50 | 25.27 | 140.67 | 25.33 |
December | 87.50 | 25.56 | 497.00 | 24.30 | 87.50 | 24.47 |
Annual Sum or Average | 2667.83 | 26.80 | 5832.83 | 25.99 | 2664.33 | 26.18 |
Minimum of Months | 0.00 | 0.00 | 371.83 | 24.09 | 0.00 | 24.09 |
Maximum of Months | 485.00 | 27.22 | 514.00 | 27.21 | 485.00 | 27.21 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.27690 | 14.37983 | 0.65646 | 14.40110 |
February | 454.00000 | 27.01560 | 14.67021 | 0.65955 | 14.44739 |
March | 514.00000 | 27.00000 | 16.37073 | 0.72596 | 16.34110 |
April | 485.00000 | 27.00000 | 20.27490 | 0.85074 | 20.45591 |
May | 508.00000 | 27.00000 | 24.11211 | 0.14402 | 5.74978 |
June | 496.00000 | 27.00003 | 29.41597 | 0.26517 | 6.76503 |
July | 497.00000 | 27.00001 | 31.90953 | 0.36935 | 8.06073 |
August | 514.00000 | 27.00002 | 30.04630 | 0.39985 | 8.53127 |
September | 485.00000 | 27.00007 | 29.51064 | 0.20760 | 6.22280 |
October | 502.00000 | 27.00000 | 22.36984 | 0.80234 | 18.73134 |
November | 489.00000 | 27.00000 | 18.00361 | 0.76121 | 17.41084 |
December | 497.00000 | 27.19676 | 14.73970 | 0.75842 | 17.52223 |
Annual Sum or Average | 5943.00000 | 27.04105 | 22.20102 | 0.54874 | 12.85885 |
Minimum of Months | 454.00000 | 27.00000 | 14.37983 | 0.14402 | 5.74978 |
Maximum of Months | 514.00000 | 27.27690 | 31.90953 | 0.85074 | 20.45591 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.04968 | 14.42984 | 0.50976 | 10.83917 |
February | 454.00000 | 27.01148 | 14.67000 | 0.57678 | 12.32200 |
March | 514.00000 | 27.00000 | 16.36475 | 0.64106 | 13.96084 |
April | 485.00000 | 27.00000 | 20.26660 | 0.73518 | 16.63962 |
May | 508.00000 | 27.00000 | 24.09501 | 0.05483 | 5.52645 |
June | 496.00000 | 27.00003 | 29.40779 | 0.18867 | 6.12127 |
July | 497.00000 | 27.00001 | 31.89993 | 0.26032 | 6.73322 |
August | 514.00000 | 27.00002 | 30.04447 | 0.25779 | 6.72247 |
September | 485.00000 | 27.00007 | 29.50579 | 0.11285 | 5.68988 |
October | 502.00000 | 27.00000 | 22.36253 | 0.72146 | 16.17029 |
November | 489.00000 | 27.00000 | 17.99515 | 0.64527 | 14.06079 |
December | 497.00000 | 27.16133 | 14.73580 | 0.60127 | 13.35380 |
Annual Sum or Average | 5943.00000 | 27.01858 | 22.19889 | 0.44059 | 10.65397 |
Minimum of Months | 454.00000 | 27.00000 | 14.42984 | 0.05483 | 5.52645 |
Maximum of Months | 514.00000 | 27.16133 | 31.89993 | 0.73518 | 16.63962 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.51607 | 14.55959 | 0.32724 | 9.13192 |
February | 454.00000 | 27.00669 | 14.67242 | 0.48848 | 10.44694 |
March | 514.00000 | 27.00000 | 16.36946 | 0.55798 | 12.04167 |
April | 485.00000 | 27.00000 | 20.27314 | 0.66106 | 14.70148 |
May | 508.00000 | 26.98199 | 24.12328 | -0.0147 | 6.08986 |
June | 496.00000 | 27.00003 | 29.41979 | 0.16427 | 6.33898 |
July | 497.00000 | 27.00001 | 31.91500 | 0.24967 | 6.95621 |
August | 514.00000 | 27.00002 | 30.08445 | 0.23442 | 6.82753 |
September | 485.00000 | 26.99996 | 29.53460 | 0.04926 | 5.89709 |
October | 502.00000 | 27.00007 | 22.36819 | 0.63451 | 13.87902 |
November | 489.00000 | 27.00000 | 18.00180 | 0.54649 | 11.72200 |
December | 497.00000 | 27.12509 | 14.75030 | 0.50162 | 11.06711 |
Annual Sum or Average | 5943.00000 | 26.96856 | 22.22370 | 0.36530 | 9.57612 |
Minimum of Months | 454.00000 | 26.51607 | 14.55959 | -0.0147 | 5.89709 |
Maximum of Months | 514.00000 | 27.12509 | 31.91500 | 0.66106 | 14.70148 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.18193 | 29.97599 | 0.98628 | 25.61577 |
February | 454.00000 | 24.00527 | 27.45092 | 0.48653 | 10.13677 |
March | 514.00000 | 24.39872 | 26.17964 | 0.62267 | 13.58009 |
April | 485.00000 | 24.87400 | 24.77956 | 0.94227 | 24.92346 |
May | 508.00000 | 27.19446 | 29.67616 | 0.43265 | 8.98843 |
June | 496.00000 | 25.35425 | 32.58413 | 0.17446 | 8.42236 |
July | 497.00000 | 26.44434 | 33.18023 | 0.70818 | 17.46442 |
August | 514.00000 | 26.53492 | 29.53775 | 0.93857 | 25.52201 |
September | 485.00000 | 27.10998 | 31.57211 | 0.54443 | 11.33338 |
October | 502.00000 | 24.45594 | 28.62202 | 0.69106 | 15.35198 |
November | 489.00000 | 25.16931 | 25.75980 | 0.85836 | 20.93635 |
December | 497.00000 | 24.08215 | 25.73067 | 0.82048 | 19.61770 |
Annual Sum or Average | 5943.00000 | 25.58012 | 28.76673 | 0.68521 | 16.87065 |
Minimum of Months | 454.00000 | 24.00527 | 24.77956 | 0.17446 | 8.42236 |
Maximum of Months | 514.00000 | 27.19446 | 33.18023 | 0.98628 | 25.61577 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.11465 | 14.76986 | -0.0211 | 7.40475 |
February | 454.00000 | 23.41686 | 15.28075 | 0.04000 | 6.14522 |
March | 514.00000 | 23.77723 | 16.50988 | 0.13485 | 5.93853 |
April | 485.00000 | 24.07667 | 19.84336 | 0.22979 | 6.29648 |
May | 508.00000 | 24.10409 | 23.55649 | -0.6306 | 14.17407 |
June | 496.00000 | 24.27448 | 31.29651 | -0.4953 | 10.68605 |
July | 497.00000 | 24.51648 | 35.46201 | -0.3719 | 8.86736 |
August | 514.00000 | 24.38846 | 31.12035 | -0.4257 | 9.62505 |
September | 485.00000 | 24.30065 | 30.43238 | -0.4718 | 10.96082 |
October | 502.00000 | 24.37332 | 21.59980 | 0.34324 | 7.93054 |
November | 489.00000 | 24.32590 | 17.17180 | 0.29170 | 7.22569 |
December | 497.00000 | 23.79232 | 14.21639 | 0.14269 | 6.18506 |
Annual Sum or Average | 5943.00000 | 24.04177 | 22.65483 | -0.1050 | 8.47600 |
Minimum of Months | 454.00000 | 23.11465 | 14.21639 | -0.6306 | 5.93853 |
Maximum of Months | 514.00000 | 24.51648 | 35.46201 | 0.34324 | 14.17407 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.33000 | 13.82807 | -0.0040 | 6.27499 |
February | 454.00000 | 23.52168 | 15.79810 | 0.06242 | 5.87112 |
March | 514.00000 | 23.82846 | 16.51165 | 0.15708 | 6.05762 |
April | 485.00000 | 24.14342 | 19.69453 | 0.27490 | 6.82091 |
May | 508.00000 | 24.17772 | 23.60036 | -0.5775 | 12.64646 |
June | 496.00000 | 24.15460 | 32.66379 | -0.4793 | 10.20901 |
July | 497.00000 | 24.27026 | 36.91347 | -0.3902 | 8.66912 |
August | 514.00000 | 24.25493 | 31.82539 | -0.4187 | 9.01401 |
September | 485.00000 | 24.21282 | 31.52605 | -0.4811 | 10.50191 |
October | 502.00000 | 24.21322 | 22.32528 | 0.30627 | 7.18625 |
November | 489.00000 | 24.17846 | 17.79460 | 0.25369 | 6.61911 |
December | 497.00000 | 23.89441 | 15.02949 | 0.15829 | 6.04033 |
Annual Sum or Average | 5943.00000 | 24.01771 | 23.17280 | -0.0970 | 8.01057 |
Minimum of Months | 454.00000 | 23.33000 | 13.82807 | -0.5775 | 5.87112 |
Maximum of Months | 514.00000 | 24.27026 | 36.91347 | 0.30627 | 12.64646 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.01862 | 14.68649 | -0.3395 | 9.48171 |
February | 454.00000 | 22.74192 | 16.82060 | -0.1407 | 6.93972 |
March | 514.00000 | 23.22971 | 17.56893 | -0.0041 | 6.32092 |
April | 485.00000 | 23.62144 | 20.92436 | 0.12672 | 5.87658 |
May | 508.00000 | 23.87320 | 24.32952 | -0.7056 | 16.52230 |
June | 496.00000 | 23.99669 | 33.14624 | -0.5586 | 12.11456 |
July | 497.00000 | 24.10551 | 37.49162 | -0.4841 | 10.46561 |
August | 514.00000 | 24.12292 | 32.33506 | -0.5142 | 10.96892 |
September | 485.00000 | 23.94468 | 32.26086 | -0.6026 | 13.46051 |
October | 502.00000 | 23.72458 | 23.72317 | 0.16826 | 5.98666 |
November | 489.00000 | 23.23325 | 18.98296 | 0.00123 | 6.27984 |
December | 497.00000 | 22.42296 | 16.28113 | -0.2191 | 8.26997 |
Annual Sum or Average | 5943.00000 | 23.42460 | 24.09075 | -0.2745 | 9.41710 |
Minimum of Months | 454.00000 | 22.01862 | 14.68649 | -0.7056 | 5.87658 |
Maximum of Months | 514.00000 | 24.12292 | 37.49162 | 0.16826 | 16.52230 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.40892 | 15.41477 | -0.7731 | 20.47590 |
February | 454.00000 | 20.87764 | 17.77756 | -0.6207 | 15.55795 |
March | 514.00000 | 21.43319 | 18.75655 | -0.4583 | 12.20527 |
April | 485.00000 | 22.05220 | 22.86471 | -0.2585 | 8.85690 |
May | 508.00000 | 22.79369 | 25.67204 | -1.0722 | 31.59306 |
June | 496.00000 | 23.47860 | 34.11347 | -0.7197 | 18.23536 |
July | 497.00000 | 23.73210 | 38.38579 | -0.5849 | 13.78417 |
August | 514.00000 | 23.68443 | 33.15783 | -0.6507 | 15.55695 |
September | 485.00000 | 22.95598 | 34.05126 | -0.9402 | 26.76567 |
October | 502.00000 | 21.88483 | 25.91864 | -0.2879 | 9.05486 |
November | 489.00000 | 21.12724 | 20.89685 | -0.5273 | 13.83195 |
December | 497.00000 | 20.57550 | 17.63362 | -0.7060 | 18.70650 |
Annual Sum or Average | 5943.00000 | 22.09423 | 25.43000 | -0.6339 | 17.06885 |
Minimum of Months | 454.00000 | 20.40892 | 15.41477 | -1.0722 | 8.85690 |
Maximum of Months | 514.00000 | 23.73210 | 38.38579 | -0.2585 | 31.59306 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.48855 | 13.85709 | -0.7618 | 19.29932 |
February | 454.00000 | 20.90840 | 16.24690 | -0.6041 | 14.39782 |
March | 514.00000 | 21.42985 | 17.20637 | -0.4308 | 10.64716 |
April | 485.00000 | 22.36954 | 20.82698 | -0.1503 | 6.92092 |
May | 508.00000 | 22.95050 | 24.30589 | -0.9720 | 28.04537 |
June | 496.00000 | 23.68363 | 32.69638 | -0.6014 | 14.27236 |
July | 497.00000 | 24.03716 | 36.53671 | -0.4214 | 9.64709 |
August | 514.00000 | 23.85260 | 31.85955 | -0.5348 | 12.30372 |
September | 485.00000 | 23.13648 | 32.57420 | -0.8365 | 23.28458 |
October | 502.00000 | 22.31338 | 23.70869 | -0.1522 | 6.73482 |
November | 489.00000 | 21.49272 | 18.75261 | -0.4022 | 10.09759 |
December | 497.00000 | 20.79406 | 15.82030 | -0.6242 | 14.92284 |
Annual Sum or Average | 5943.00000 | 22.29877 | 23.74387 | -0.5412 | 14.22300 |
Minimum of Months | 454.00000 | 20.48855 | 13.85709 | -0.9720 | 6.73482 |
Maximum of Months | 514.00000 | 24.03716 | 36.53671 | -0.1503 | 28.04537 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.56462 | 13.43944 | -0.7309 | 18.61290 |
February | 454.00000 | 21.12659 | 15.69866 | -0.5273 | 13.45330 |
March | 514.00000 | 21.51325 | 16.75445 | -0.3745 | 10.64796 |
April | 485.00000 | 22.28599 | 20.55689 | -0.1118 | 8.08868 |
May | 508.00000 | 22.79512 | 24.18658 | -0.9266 | 27.83493 |
June | 496.00000 | 23.57422 | 32.60198 | -0.5073 | 14.77672 |
July | 497.00000 | 23.92789 | 36.60461 | -0.3111 | 10.61131 |
August | 514.00000 | 23.56713 | 32.11783 | -0.4930 | 14.00958 |
September | 485.00000 | 23.02611 | 32.61077 | -0.7730 | 23.18334 |
October | 502.00000 | 22.25062 | 23.43580 | -0.1202 | 7.25440 |
November | 489.00000 | 21.42754 | 18.48498 | -0.3964 | 9.97189 |
December | 497.00000 | 20.72480 | 15.53172 | -0.6347 | 15.16720 |
Annual Sum or Average | 5943.00000 | 22.24055 | 23.54930 | -0.4927 | 14.48623 |
Minimum of Months | 454.00000 | 20.56462 | 13.43944 | -0.9266 | 7.25440 |
Maximum of Months | 514.00000 | 23.92789 | 36.60461 | -0.1118 | 27.83493 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.18763 | 13.12026 | -0.5573 | 16.95252 |
February | 454.00000 | 21.88984 | 15.11425 | -0.3123 | 12.92714 |
March | 514.00000 | 21.90541 | 16.42505 | -0.2657 | 11.10287 |
April | 485.00000 | 22.42388 | 20.45395 | -0.0904 | 8.72379 |
May | 508.00000 | 22.73976 | 24.32838 | -0.9821 | 30.40775 |
June | 496.00000 | 23.34781 | 33.13590 | -0.6483 | 18.07533 |
July | 497.00000 | 23.81046 | 36.90883 | -0.4115 | 12.05512 |
August | 514.00000 | 23.67417 | 31.92972 | -0.4668 | 13.78701 |
September | 485.00000 | 23.29180 | 32.07761 | -0.6546 | 21.54620 |
October | 502.00000 | 22.74108 | 22.77718 | 0.02589 | 9.05444 |
November | 489.00000 | 22.18838 | 17.78536 | -0.1906 | 10.37518 |
December | 497.00000 | 21.43408 | 14.98982 | -0.4401 | 14.21860 |
Annual Sum or Average | 5943.00000 | 22.55749 | 23.30463 | -0.4178 | 14.96597 |
Minimum of Months | 454.00000 | 21.18763 | 13.12026 | -0.9821 | 8.72379 |
Maximum of Months | 514.00000 | 23.81046 | 36.90883 | 0.02589 | 30.40775 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.77448 | 13.19637 | -0.6362 | 15.54626 |
February | 454.00000 | 21.32853 | 15.38862 | -0.4326 | 11.55134 |
March | 514.00000 | 21.75247 | 16.42699 | -0.2732 | 8.94582 |
April | 485.00000 | 22.94367 | 19.69554 | 0.09694 | 7.61712 |
May | 508.00000 | 22.99592 | 23.84755 | -0.8041 | 24.29127 |
June | 496.00000 | 23.51592 | 32.73835 | -0.4849 | 14.54823 |
July | 497.00000 | 24.08997 | 36.26839 | -0.2052 | 9.53714 |
August | 514.00000 | 24.05577 | 31.17821 | -0.2516 | 9.37918 |
September | 485.00000 | 23.05165 | 32.39047 | -0.7099 | 21.68695 |
October | 502.00000 | 22.42206 | 23.06390 | -0.0424 | 7.15386 |
November | 489.00000 | 21.93224 | 17.86808 | -0.2284 | 8.36188 |
December | 497.00000 | 21.36936 | 14.87558 | -0.4118 | 10.41079 |
Annual Sum or Average | 5943.00000 | 22.52818 | 23.12447 | -0.3654 | 12.42306 |
Minimum of Months | 454.00000 | 20.77448 | 13.19637 | -0.8041 | 7.15386 |
Maximum of Months | 514.00000 | 24.08997 | 36.26839 | 0.09694 | 24.29127 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.87560 | 13.78901 | -0.9993 | 28.40022 |
February | 454.00000 | 20.22660 | 16.50820 | -0.8294 | 21.42696 |
March | 514.00000 | 20.54200 | 17.83781 | -0.6845 | 16.69244 |
April | 485.00000 | 21.09649 | 22.30333 | -0.4702 | 11.17416 |
May | 508.00000 | 21.90658 | 25.69962 | -1.3238 | 42.95985 |
June | 496.00000 | 22.92723 | 34.04567 | -0.8497 | 23.20791 |
July | 497.00000 | 23.37387 | 37.82027 | -0.6503 | 16.03357 |
August | 514.00000 | 23.06024 | 33.20410 | -0.8138 | 21.78500 |
September | 485.00000 | 22.07362 | 34.40311 | -1.1938 | 37.78772 |
October | 502.00000 | 21.06114 | 25.35255 | -0.4661 | 10.71175 |
November | 489.00000 | 20.38841 | 19.62062 | -0.7216 | 18.27378 |
December | 497.00000 | 19.95817 | 16.23510 | -0.9208 | 25.42036 |
Annual Sum or Average | 5943.00000 | 21.38458 | 24.78277 | -0.8273 | 22.84354 |
Minimum of Months | 454.00000 | 19.87560 | 13.78901 | -1.3238 | 10.71175 |
Maximum of Months | 514.00000 | 23.37387 | 37.82027 | -0.4661 | 42.95985 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.80711 | 13.31087 | -0.9976 | 28.44040 |
February | 385.00000 | 20.43338 | 15.83341 | -0.7482 | 19.57352 |
March | 433.00000 | 20.84498 | 16.93686 | -0.5810 | 15.30059 |
April | 410.00000 | 21.70895 | 21.21524 | -0.2829 | 10.39091 |
May | 430.00000 | 22.28180 | 24.89169 | -1.1313 | 36.08589 |
June | 418.00000 | 23.33714 | 32.79646 | -0.6071 | 18.78852 |
July | 422.00000 | 23.82228 | 36.44839 | -0.3753 | 13.07846 |
August | 433.00000 | 23.40979 | 32.00266 | -0.5860 | 17.61770 |
September | 410.00000 | 22.62618 | 33.21647 | -0.9435 | 30.18656 |
October | 427.00000 | 21.48661 | 24.34009 | -0.3352 | 9.61887 |
November | 417.00000 | 20.55054 | 18.82459 | -0.6641 | 16.73109 |
December | 422.00000 | 19.86351 | 15.81962 | -0.9272 | 25.82482 |
Annual Sum or Average | 5034.00000 | 21.68853 | 23.83789 | -0.6818 | 20.15139 |
Minimum of Months | 385.00000 | 19.80711 | 13.31087 | -1.1313 | 9.61887 |
Maximum of Months | 433.00000 | 23.82228 | 36.44839 | -0.2829 | 36.08589 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.79286 | 12.99570 | -0.6868 | 20.70290 |
February | 454.00000 | 21.63216 | 15.14794 | -0.3829 | 15.39252 |
March | 514.00000 | 21.61781 | 16.70716 | -0.3445 | 13.39276 |
April | 485.00000 | 22.07894 | 21.04306 | -0.1856 | 10.40062 |
May | 508.00000 | 22.46312 | 24.83432 | -1.0850 | 34.84309 |
June | 496.00000 | 23.13780 | 33.52100 | -0.7285 | 21.28736 |
July | 497.00000 | 23.62110 | 37.16088 | -0.4902 | 14.64446 |
August | 514.00000 | 23.48645 | 32.18196 | -0.5487 | 16.99945 |
September | 485.00000 | 23.10771 | 32.43071 | -0.7193 | 24.88806 |
October | 502.00000 | 22.46668 | 23.28724 | -0.0395 | 10.31293 |
November | 489.00000 | 21.76624 | 18.13276 | -0.3083 | 13.04172 |
December | 497.00000 | 20.85168 | 15.34589 | -0.6155 | 18.83391 |
Annual Sum or Average | 5943.00000 | 22.25655 | 23.61771 | -0.5131 | 17.93198 |
Minimum of Months | 454.00000 | 20.79286 | 12.99570 | -1.0850 | 10.31293 |
Maximum of Months | 514.00000 | 23.62110 | 37.16088 | -0.0395 | 34.84309 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.02678 | 13.44028 | -0.9256 | 25.55958 |
February | 454.00000 | 20.59813 | 15.93700 | -0.6894 | 18.23045 |
March | 514.00000 | 20.92143 | 17.26058 | -0.5482 | 14.45401 |
April | 485.00000 | 21.60855 | 21.50553 | -0.2909 | 10.15552 |
May | 508.00000 | 22.30175 | 25.01238 | -1.0956 | 35.76388 |
June | 496.00000 | 22.95532 | 33.87296 | -0.7238 | 22.28103 |
July | 497.00000 | 23.38163 | 37.73563 | -0.5132 | 16.39050 |
August | 514.00000 | 23.13825 | 32.85056 | -0.6570 | 19.91994 |
September | 485.00000 | 22.34939 | 33.76318 | -1.0089 | 33.08206 |
October | 502.00000 | 21.46403 | 24.57504 | -0.3232 | 9.63838 |
November | 489.00000 | 20.74740 | 19.02883 | -0.5953 | 15.31622 |
December | 497.00000 | 20.12129 | 15.87054 | -0.8393 | 22.63955 |
Annual Sum or Average | 5943.00000 | 21.64358 | 24.28675 | -0.6846 | 20.30817 |
Minimum of Months | 454.00000 | 20.02678 | 13.44028 | -1.0956 | 9.63838 |
Maximum of Months | 514.00000 | 23.38163 | 37.73563 | -0.2909 | 35.76388 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.72502 | 14.18091 | -1.1057 | 32.86499 |
February | 454.00000 | 19.92625 | 16.82094 | -0.9681 | 27.19982 |
March | 514.00000 | 20.21174 | 18.09086 | -0.8259 | 21.93862 |
April | 485.00000 | 20.54158 | 22.96799 | -0.6438 | 16.49543 |
May | 508.00000 | 21.37271 | 26.38331 | -1.5261 | 51.72098 |
June | 496.00000 | 22.33374 | 35.14969 | -1.0292 | 31.24903 |
July | 497.00000 | 22.80256 | 39.18057 | -0.8066 | 22.45307 |
August | 514.00000 | 22.48491 | 34.31634 | -0.9850 | 29.18299 |
September | 485.00000 | 21.50723 | 35.55098 | -1.4060 | 47.02943 |
October | 502.00000 | 20.41746 | 26.35765 | -0.6703 | 16.78262 |
November | 489.00000 | 19.98069 | 20.24042 | -0.8920 | 24.61022 |
December | 497.00000 | 19.76177 | 16.61986 | -1.0469 | 30.55928 |
Annual Sum or Average | 5943.00000 | 20.93180 | 25.53818 | -0.9926 | 29.36450 |
Minimum of Months | 454.00000 | 19.72502 | 14.18091 | -1.5261 | 16.49543 |
Maximum of Months | 514.00000 | 22.80256 | 39.18057 | -0.6438 | 51.72098 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.76243 | 14.11580 | -1.0638 | 31.26355 |
February | 454.00000 | 20.12252 | 16.57826 | -0.8723 | 23.85806 |
March | 514.00000 | 20.53305 | 17.76086 | -0.6980 | 19.05389 |
April | 485.00000 | 21.32136 | 21.95973 | -0.4068 | 13.84027 |
May | 508.00000 | 22.06693 | 25.36705 | -1.2215 | 39.57104 |
June | 496.00000 | 23.23734 | 33.23616 | -0.6287 | 19.95716 |
July | 497.00000 | 23.69681 | 37.05560 | -0.3831 | 13.71511 |
August | 514.00000 | 23.33741 | 32.53298 | -0.5884 | 18.56593 |
September | 485.00000 | 22.39127 | 33.91039 | -1.0437 | 34.25143 |
October | 502.00000 | 20.87641 | 25.66839 | -0.5162 | 13.88072 |
November | 489.00000 | 20.07462 | 20.10232 | -0.8322 | 22.54849 |
December | 497.00000 | 19.78841 | 16.56828 | -1.0131 | 29.32059 |
Annual Sum or Average | 5943.00000 | 21.44552 | 24.61702 | -0.7718 | 23.31665 |
Minimum of Months | 454.00000 | 19.76243 | 14.11580 | -1.2215 | 13.71511 |
Maximum of Months | 514.00000 | 23.69681 | 37.05560 | -0.3831 | 39.57104 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.29170 | 13.66637 | -0.8621 | 25.78307 |
February | 454.00000 | 21.02310 | 15.74485 | -0.5820 | 19.59268 |
March | 514.00000 | 21.08441 | 17.21861 | -0.5242 | 17.79451 |
April | 485.00000 | 21.43846 | 21.86342 | -0.3748 | 14.70683 |
May | 508.00000 | 21.98216 | 25.48886 | -1.2729 | 42.56617 |
June | 496.00000 | 22.69937 | 34.40520 | -0.8665 | 27.44064 |
July | 497.00000 | 23.19618 | 38.24551 | -0.6076 | 19.38031 |
August | 514.00000 | 23.09135 | 33.02423 | -0.6715 | 22.26583 |
September | 485.00000 | 22.60286 | 33.45293 | -0.9145 | 32.33073 |
October | 502.00000 | 21.70914 | 24.47085 | -0.2629 | 13.77329 |
November | 489.00000 | 20.95242 | 19.11933 | -0.5533 | 17.53884 |
December | 497.00000 | 20.30218 | 16.04879 | -0.8091 | 24.24292 |
Annual Sum or Average | 5943.00000 | 21.70378 | 24.44779 | -0.6933 | 23.16137 |
Minimum of Months | 454.00000 | 20.29170 | 13.66637 | -1.2729 | 13.77329 |
Maximum of Months | 514.00000 | 23.19618 | 38.24551 | -0.2629 | 42.56617 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.81695 | 14.00612 | -1.0340 | 30.12882 |
February | 454.00000 | 20.29542 | 16.35333 | -0.8142 | 22.71489 |
March | 514.00000 | 20.61938 | 17.59959 | -0.6692 | 18.53303 |
April | 485.00000 | 21.20740 | 22.07875 | -0.4220 | 13.91436 |
May | 508.00000 | 22.01216 | 25.43606 | -1.2195 | 40.98485 |
June | 496.00000 | 22.74192 | 34.35092 | -0.7951 | 26.18025 |
July | 497.00000 | 23.15871 | 38.38576 | -0.5725 | 19.57903 |
August | 514.00000 | 22.91785 | 33.38563 | -0.7275 | 23.48314 |
September | 485.00000 | 22.08765 | 34.37357 | -1.1261 | 38.38694 |
October | 502.00000 | 20.98962 | 25.39947 | -0.4784 | 13.66871 |
November | 489.00000 | 20.31400 | 19.75633 | -0.7518 | 20.34526 |
December | 497.00000 | 19.88428 | 16.39822 | -0.9584 | 27.28389 |
Annual Sum or Average | 5943.00000 | 21.34668 | 24.84265 | -0.7976 | 24.61834 |
Minimum of Months | 454.00000 | 19.81695 | 14.00612 | -1.2195 | 13.66871 |
Maximum of Months | 514.00000 | 23.15871 | 38.38576 | -0.4220 | 40.98485 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.132146E+10 | 90354.16 | 02-JAN-16:25 | 107.95 | 0.590582E+10 | 0.00 | 0.722728E+10 | 0.65 | 4.51 | 02-JAN-17:25 | 0.00 | 0.00 |
February | 0.486805E+11 | 148622.63 | 27-FEB-14:46 | 214.20 | 0.221450E+12 | 0.00 | 0.270130E+12 | 1.45 | 6.81 | 27-FEB-14:46 | 0.00 | 0.00 |
March | 0.792261E+11 | 152677.19 | 01-MAR-14:50 | 399.86 | 0.360244E+12 | 0.00 | 0.439470E+12 | 2.45 | 6.86 | 01-MAR-14:50 | 0.00 | 0.00 |
April | 0.726340E+11 | 184519.10 | 06-APR-16:00 | 575.75 | 0.359070E+12 | 0.00 | 0.431704E+12 | 3.85 | 7.01 | 06-APR-16:00 | 0.00 | 0.00 |
May | 0.509336E+11 | 224378.19 | 19-MAY-13:10 | 229.66 | 0.281620E+12 | 0.00 | 0.332554E+12 | 1.55 | 7.01 | 31-MAY-15:10 | 0.00 | 0.00 |
June | 0.158129E+12 | 233151.80 | 26-JUN-10:20 | 436.55 | 0.936353E+12 | 0.00 | 0.109448E+13 | 3.34 | 7.14 | 06-JUN-14:20 | 0.00 | 0.00 |
July | 0.222022E+12 | 234836.04 | 18-JUL-07:50 | 607.96 | 0.139215E+13 | 0.00 | 0.161417E+13 | 4.71 | 7.10 | 10-JUL-15:20 | 0.00 | 0.00 |
August | 0.202238E+12 | 234288.22 | 01-AUG-12:30 | 628.23 | 0.124996E+13 | 0.00 | 0.145220E+13 | 4.72 | 7.20 | 12-AUG-14:30 | 0.00 | 0.00 |
September | 0.915835E+11 | 235605.74 | 25-SEP-12:20 | 313.55 | 0.544946E+12 | 0.00 | 0.636529E+12 | 2.34 | 7.03 | 03-SEP-15:32 | 0.00 | 0.00 |
October | 0.776795E+11 | 212623.05 | 18-OCT-15:10 | 304.32 | 0.393936E+12 | 0.00 | 0.471615E+12 | 1.98 | 7.02 | 15-OCT-14:03 | 0.00 | 0.00 |
November | 0.655536E+11 | 156159.79 | 03-NOV-13:22 | 558.61 | 0.306950E+12 | 0.00 | 0.372504E+12 | 3.66 | 6.89 | 03-NOV-13:22 | 0.00 | 0.00 |
December | 0.686961E+11 | 106628.02 | 06-DEC-11:30 | 652.42 | 0.327150E+12 | 0.00 | 0.395847E+12 | 4.18 | 5.57 | 06-DEC-11:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.113870E+13 | 5029.07 | 0.637974E+13 | 0.00 | 0.751844E+13 | 2.91 | 0.00 | 0.00 | ||||
Minimum of Months | 0.132146E+10 | 90354.16 | 107.95 | 0.590582E+10 | 0.00 | 0.722728E+10 | 0.65 | 4.51 | 0.00 | 0.00 | ||
Maximum of Months | 0.222022E+12 | 235605.74 | 652.42 | 0.139215E+13 | 0.00 | 0.161417E+13 | 4.72 | 7.20 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 |
May | 0.160319E+10 | 146399.03 | 19-MAY-14:05 | 3.50 | 0.103658E+11 | 0.00 | 0.119690E+11 | 0.03 | 6.74 | 19-MAY-14:05 | 0.00 | 0.00 |
June | 0.216449E+11 | 162709.05 | 21-JUN-12:05 | 45.25 | 0.141418E+12 | 0.00 | 0.163063E+12 | 0.41 | 6.92 | 21-JUN-12:05 | 0.00 | 0.00 |
July | 0.574561E+11 | 192537.69 | 10-JUL-12:05 | 114.60 | 0.380981E+12 | 0.00 | 0.438437E+12 | 1.02 | 7.01 | 10-JUL-12:05 | 0.00 | 0.00 |
August | 0.574314E+11 | 191449.71 | 05-AUG-17:06 | 112.13 | 0.385063E+12 | 0.00 | 0.442494E+12 | 1.00 | 7.00 | 05-AUG-17:06 | 0.00 | 0.00 |
September | 0.865254E+10 | 191056.98 | 07-SEP-14:50 | 17.75 | 0.564139E+11 | 0.00 | 0.650665E+11 | 0.16 | 7.01 | 27-SEP-14:05 | 0.00 | 0.00 |
October | 0.806886E+09 | 178849.26 | 18-OCT-13:04 | 1.77 | 0.525787E+10 | 0.00 | 0.606476E+10 | 0.02 | 7.00 | 18-OCT-13:04 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.147595E+12 | 295.00 | 0.979500E+12 | 0.00 | 0.112709E+13 | 0.22 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.574561E+11 | 192537.69 | 114.60 | 0.385063E+12 | 0.00 | 0.442494E+12 | 1.02 | 7.01 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 392.00 | 0.03 | 3.27 | 02-JAN-16:34 | 322167.08 | 02-JAN-16:34 | 21.01 | 20.99 | 2.40 |
February | 17207741.08 | 173.53 | 1976.22 | 27-FEB-14:49 | 1090405.09 | 27-FEB-14:49 | 22.24 | 21.89 | 23.83 |
March | 14299914.47 | 298.15 | 612.77 | 02-MAR-14:44 | 1052166.93 | 02-MAR-14:44 | 22.09 | 21.56 | 39.28 |
April | 0.179457E+09 | 93.89 | 7120.41 | 06-APR-16:00 | 1478953.83 | 06-APR-16:00 | 21.42 | 20.86 | 50.93 |
May | 0.129314E+10 | 137.65 | 22248.01 | 19-MAY-13:50 | 1791623.29 | 19-MAY-16:30 | 21.47 | 21.08 | 19.95 |
June | 0.826954E+10 | 419.98 | 25000.75 | 06-JUN-14:20 | 1815620.34 | 30-JUN-11:20 | 22.95 | 21.59 | 49.26 |
July | 0.161536E+11 | 525.96 | 25000.75 | 01-JUL-12:30 | 1840622.69 | 18-JUL-07:50 | 23.33 | 21.37 | 64.99 |
August | 0.112514E+11 | 487.40 | 25000.75 | 05-AUG-10:45 | 1863776.17 | 01-AUG-12:30 | 22.92 | 21.14 | 66.20 |
September | 0.525523E+10 | 228.66 | 25000.75 | 02-SEP-11:00 | 1852400.47 | 05-SEP-13:00 | 21.94 | 21.16 | 31.71 |
October | 0.505917E+09 | 264.33 | 9752.29 | 18-OCT-15:20 | 1714178.32 | 18-OCT-15:20 | 22.31 | 21.76 | 32.21 |
November | 17305181.33 | 121.78 | 2509.36 | 03-NOV-13:25 | 1137221.20 | 03-NOV-13:25 | 21.57 | 21.08 | 44.41 |
December | 351372.95 | 11.03 | 59.81 | 06-DEC-11:32 | 518268.26 | 06-DEC-11:32 | 21.23 | 20.71 | 51.72 |
Annual Sum or Average | 0.429574E+11 | 2762.40 | 22.04 | 21.26 | 39.82 | ||||
Minimum of Months | 392.00 | 0.03 | 3.27 | 322167.08 | 21.01 | 20.71 | 2.40 | ||
Maximum of Months | 0.161536E+11 | 525.96 | 25000.75 | 1863776.17 | 23.33 | 21.89 | 66.20 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 21.01 | 21.01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 22.24 | 22.24 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 22.09 | 22.09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 01-APR-00:02 | 21.42 | 21.42 | 0.00 |
May | 0.150562E+09 | 2.67 | 18910.02 | 19-MAY-14:05 | 1572610.35 | 19-MAY-14:05 | 21.47 | 21.46 | 0.29 |
June | 0.259559E+10 | 38.25 | 25000.75 | 06-JUN-15:10 | 1674581.36 | 29-JUN-15:30 | 22.95 | 22.72 | 4.32 |
July | 0.629199E+10 | 98.74 | 25000.75 | 13-JUL-13:30 | 1689720.66 | 31-JUL-14:30 | 23.33 | 22.77 | 10.79 |
August | 0.531324E+10 | 99.47 | 25000.75 | 05-AUG-12:30 | 1690000.44 | 24-AUG-14:30 | 22.92 | 22.35 | 10.87 |
September | 0.943327E+09 | 13.75 | 25000.75 | 06-SEP-12:50 | 1609620.85 | 01-SEP-11:00 | 21.94 | 21.86 | 1.55 |
October | 26212828.06 | 1.02 | 8352.39 | 18-OCT-15:00 | 1565575.70 | 18-OCT-12:40 | 22.31 | 22.31 | 0.11 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 21.57 | 21.57 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 21.23 | 21.23 | 0.00 |
Annual Sum or Average | 0.153209E+11 | 253.90 | 22.04 | 21.92 | 2.36 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.01 | 21.01 | 0.00 | ||
Maximum of Months | 0.629199E+10 | 99.47 | 25000.75 | 1690000.44 | 23.33 | 22.77 | 10.87 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.101126E+13 | 0.00 | 642.80 | 3350463.25 | 02-JAN-05:01 | 0.00 | 34.65 | 71.91 | 2.33 | 0.00 | 0.09 | 0.84 | 02-JAN-05:01 |
February | 0.520827E+12 | 0.00 | 504.02 | 3329789.19 | 28-FEB-05:01 | 0.00 | 31.46 | 64.75 | 1.22 | 0.00 | 0.05 | 0.83 | 28-FEB-05:01 |
March | 0.335888E+12 | 0.00 | 518.10 | 3560797.79 | 01-MAR-05:01 | 0.00 | 27.80 | 59.88 | 0.71 | 0.00 | 0.03 | 0.89 | 01-MAR-05:01 |
April | 0.122202E+12 | 0.00 | 337.68 | 3278903.32 | 22-APR-04:01 | 0.00 | 23.92 | 45.37 | 0.26 | 0.00 | 0.01 | 0.82 | 22-APR-04:01 |
May | 0.856620E+11 | 0.00 | 260.56 | 3220045.99 | 09-MAY-04:01 | 0.00 | 23.71 | 39.52 | 0.18 | 0.00 | 0.01 | 0.81 | 09-MAY-04:01 |
June | 0.140462E+11 | 0.00 | 107.52 | 2788322.64 | 17-JUN-04:11 | 0.00 | 22.06 | 28.61 | 0.03 | 0.00 | 0.00 | 0.70 | 17-JUN-04:11 |
July | 0.256516E+10 | 0.00 | 50.94 | 517010.18 | 08-JUL-05:01 | 0.00 | 21.28 | 24.31 | 0.01 | 0.00 | 0.00 | 0.13 | 08-JUL-05:01 |
August | 0.888500E+10 | 0.00 | 89.54 | 2452347.83 | 18-AUG-05:01 | 0.00 | 21.15 | 26.48 | 0.02 | 0.00 | 0.00 | 0.61 | 18-AUG-05:01 |
September | 0.487154E+11 | 0.00 | 217.04 | 2871111.05 | 20-SEP-04:11 | 0.00 | 22.05 | 35.23 | 0.11 | 0.00 | 0.00 | 0.72 | 20-SEP-04:11 |
October | 0.117075E+12 | 0.00 | 363.73 | 3222882.63 | 05-OCT-04:01 | 0.00 | 24.15 | 45.65 | 0.25 | 0.00 | 0.01 | 0.81 | 05-OCT-04:01 |
November | 0.306852E+12 | 0.00 | 501.30 | 3343425.15 | 06-NOV-05:01 | 0.00 | 28.36 | 59.25 | 0.67 | 0.00 | 0.03 | 0.84 | 06-NOV-05:01 |
December | 0.663403E+12 | 0.00 | 608.09 | 3388782.67 | 18-DEC-05:11 | 0.00 | 31.47 | 68.68 | 1.40 | 0.00 | 0.06 | 0.85 | 18-DEC-05:11 |
Annual Sum or Average | 0.323739E+13 | 0.00 | 4201.32 | 0.00 | 25.98 | 47.39 | 0.60 | 0.00 | 0.03 | ||||
Minimum of Months | 0.256516E+10 | 0.00 | 50.94 | 517010.18 | 0.00 | 21.15 | 24.31 | 0.01 | 0.00 | 0.00 | 0.13 | ||
Maximum of Months | 0.101126E+13 | 0.00 | 642.80 | 3560797.79 | 0.00 | 34.65 | 71.91 | 2.33 | 0.00 | 0.09 | 0.89 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 0.731142E+09 | 0.00 | 12.77 | 0.731142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45528.09 | 27-FEB-15:21 | 45528.09 | 27-FEB-15:21 | 0.00 | 0.00 | 0.00 |
March | 46009654.44 | 0.00 | 3.70 | 46009654.44 | 0.00 | 0.00 | 0.00 | 0.00 | 7492.37 | 14-MAR-13:21 | 7492.37 | 14-MAR-13:21 | 0.00 | 0.00 | 0.00 |
April | 0.763361E+10 | 0.00 | 79.73 | 0.763361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92485.94 | 06-APR-16:00 | 92485.94 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.220150E+11 | 0.00 | 170.61 | 0.220150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 129600.19 | 19-MAY-15:30 | 129600.19 | 19-MAY-15:30 | 0.00 | 0.00 | 0.00 |
June | 0.679616E+11 | 0.00 | 334.29 | 0.679102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 145707.80 | 29-JUN-14:40 | 145707.80 | 29-JUN-14:40 | 0.00 | 0.00 | 0.00 |
July | 0.117065E+12 | 0.00 | 439.25 | 0.116863E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 174405.86 | 17-JUL-15:50 | 174405.86 | 17-JUL-15:50 | 0.00 | 0.00 | 0.00 |
August | 0.107083E+12 | 0.00 | 419.71 | 0.107083E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 170365.17 | 07-AUG-15:00 | 170365.17 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.463970E+11 | 0.00 | 252.37 | 0.450390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 218179.06 | 07-SEP-14:50 | 148193.35 | 01-SEP-15:20 | 0.00 | 0.00 | 0.00 |
October | 0.125692E+11 | 0.00 | 113.87 | 0.125692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122112.64 | 18-OCT-15:20 | 122112.64 | 18-OCT-15:20 | 0.00 | 0.00 | 0.00 |
November | 0.765204E+09 | 0.00 | 25.71 | 0.765204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23277.81 | 17-NOV-16:51 | 23277.81 | 17-NOV-16:51 | 0.00 | 0.00 | 0.00 |
December | 102335.07 | 0.00 | 0.54 | 102335.07 | 0.00 | 0.00 | 0.00 | 0.00 | 507.75 | 26-DEC-17:03 | 507.75 | 26-DEC-17:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.382267E+12 | 0.00 | 1852.54 | 0.380656E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.117065E+12 | 0.00 | 439.25 | 0.116863E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 218179.06 | 174405.86 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 96972.77 | 0.00 | 40.85 | 96972.77 | 0.00 | 0.00 | 0.00 | 0.00 | 5.97 | 03-JAN-05:12 | 5.97 | 03-JAN-05:12 | 0.00 | 0.00 | 0.00 |
February | 0.106124E+11 | 0.00 | 87.97 | 0.106124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 719262.50 | 27-FEB-15:01 | 719262.50 | 27-FEB-15:01 | 0.00 | 0.00 | 0.00 |
March | 0.111127E+11 | 0.00 | 113.93 | 0.111127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 594821.34 | 02-MAR-15:01 | 594821.34 | 02-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.702122E+11 | 0.00 | 162.26 | 0.702122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 821613.97 | 06-APR-16:00 | 821613.97 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.209437E+12 | 0.00 | 216.37 | 0.209437E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1262989.04 | 19-MAY-15:30 | 1262989.04 | 19-MAY-15:30 | 0.00 | 0.00 | 0.00 |
June | 0.622458E+12 | 0.00 | 336.33 | 0.621902E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1406876.51 | 29-JUN-15:00 | 1406876.51 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.101660E+13 | 0.00 | 416.06 | 0.101498E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1608029.92 | 17-JUL-16:00 | 1608029.92 | 17-JUL-16:00 | 0.00 | 0.00 | 0.00 |
August | 0.891082E+12 | 0.00 | 384.96 | 0.891082E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1576479.38 | 10-AUG-15:10 | 1576479.38 | 10-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.426758E+12 | 0.00 | 271.64 | 0.414281E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2007414.84 | 07-SEP-14:50 | 1380731.29 | 01-SEP-15:40 | 0.00 | 0.00 | 0.00 |
October | 0.133795E+12 | 0.00 | 158.44 | 0.133795E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1102844.75 | 18-OCT-15:20 | 1102844.75 | 18-OCT-15:20 | 0.00 | 0.00 | 0.00 |
November | 0.116953E+11 | 0.00 | 88.26 | 0.116953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 764669.18 | 03-NOV-14:01 | 764669.18 | 03-NOV-14:01 | 0.00 | 0.00 | 0.00 |
December | 262511.42 | 0.00 | 90.91 | 262511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 02-DEC-13:17 | 5.58 | 02-DEC-13:17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.340377E+13 | 0.00 | 2367.98 | 0.338911E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 96972.77 | 0.00 | 40.85 | 96972.77 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 5.58 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.101660E+13 | 0.00 | 416.06 | 0.101498E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2007414.84 | 1608029.92 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 4108511.06 | 0.00 | 5.70 | 4108511.06 | 0.00 | 0.00 | 0.00 | 0.00 | 5555.10 | 18-JAN-06:01 | 5555.10 | 18-JAN-06:01 | 0.00 | 0.00 | 0.00 |
February | 0.573729E+09 | 0.00 | 20.18 | 0.573729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41801.33 | 26-FEB-15:11 | 41801.33 | 26-FEB-15:11 | 0.00 | 0.00 | 0.00 |
March | 17457434.51 | 0.00 | 6.93 | 17457434.51 | 0.00 | 0.00 | 0.00 | 0.00 | 4760.60 | 20-MAR-04:31 | 4760.60 | 20-MAR-04:31 | 0.00 | 0.00 | 0.00 |
April | 0.620092E+10 | 0.00 | 72.18 | 0.620092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83213.80 | 06-APR-16:00 | 83213.80 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.225257E+11 | 0.00 | 159.58 | 0.225257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159464.47 | 19-MAY-15:30 | 159464.47 | 19-MAY-15:30 | 0.00 | 0.00 | 0.00 |
June | 0.722633E+11 | 0.00 | 322.32 | 0.722388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 176601.32 | 29-JUN-15:00 | 176601.32 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.119541E+12 | 0.00 | 407.29 | 0.119416E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 236621.58 | 16-JUL-15:31 | 220068.86 | 16-JUL-15:31 | 0.00 | 0.00 | 0.00 |
August | 0.100582E+12 | 0.00 | 370.23 | 0.100582E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 193889.23 | 10-AUG-15:00 | 193889.23 | 10-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.454381E+11 | 0.00 | 238.69 | 0.443677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 194924.16 | 07-SEP-14:50 | 191281.48 | 03-SEP-15:21 | 0.00 | 0.00 | 0.00 |
October | 0.102207E+11 | 0.00 | 105.30 | 0.102207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118223.12 | 18-OCT-15:00 | 118223.12 | 18-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.577939E+09 | 0.00 | 23.76 | 0.577939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18183.01 | 04-NOV-13:54 | 18183.01 | 04-NOV-13:54 | 0.00 | 0.00 | 0.00 |
December | 10539264.19 | 0.00 | 6.81 | 10539264.19 | 0.00 | 0.00 | 0.00 | 0.00 | 4469.19 | 04-DEC-05:12 | 4469.19 | 04-DEC-05:12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377956E+12 | 0.00 | 1738.97 | 0.376736E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4108511.06 | 0.00 | 5.70 | 4108511.06 | 0.00 | 0.00 | 0.00 | 0.00 | 4469.19 | 4469.19 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.119541E+12 | 0.00 | 407.29 | 0.119416E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 236621.58 | 220068.86 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.214667E+10 | 0.00 | 17.84 | 0.205747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115206.37 | 02-JAN-05:04 | 107753.21 | 03-JAN-05:57 | 0.00 | 0.00 | 0.00 |
February | 0.226954E+10 | 0.00 | 24.62 | 0.226954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 138147.60 | 28-FEB-05:45 | 138147.60 | 28-FEB-05:45 | 0.00 | 0.00 | 0.00 |
March | 0.381141E+10 | 0.00 | 37.75 | 0.381141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 129189.99 | 01-MAR-05:48 | 129189.99 | 01-MAR-05:48 | 0.00 | 0.00 | 0.00 |
April | 0.794048E+10 | 0.00 | 108.13 | 0.794048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91446.63 | 13-APR-04:06 | 91446.63 | 13-APR-04:06 | 0.00 | 0.00 | 0.00 |
May | 0.171542E+11 | 0.00 | 181.02 | 0.171508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78408.32 | 22-MAY-05:02 | 78408.32 | 22-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.367914E+11 | 0.00 | 296.31 | 0.357962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 139861.94 | 15-JUN-04:42 | 139861.94 | 15-JUN-04:42 | 0.00 | 0.00 | 0.00 |
July | 0.544491E+11 | 0.00 | 358.53 | 0.535766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100778.69 | 25-JUL-05:02 | 100778.69 | 25-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.533960E+11 | 0.00 | 378.17 | 0.533903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81711.44 | 07-AUG-04:13 | 81711.44 | 07-AUG-04:13 | 0.00 | 0.00 | 0.00 |
September | 0.334159E+11 | 0.00 | 278.73 | 0.313800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114679.41 | 07-SEP-14:50 | 98168.21 | 04-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.182928E+11 | 0.00 | 174.02 | 0.182928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133631.17 | 11-OCT-03:48 | 133631.17 | 11-OCT-03:48 | 0.00 | 0.00 | 0.00 |
November | 0.890418E+10 | 0.00 | 113.49 | 0.890418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140702.29 | 27-NOV-05:43 | 140702.29 | 27-NOV-05:43 | 0.00 | 0.00 | 0.00 |
December | 0.374433E+10 | 0.00 | 63.80 | 0.374433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 128081.82 | 26-DEC-05:50 | 128081.82 | 26-DEC-05:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242316E+12 | 0.00 | 2032.41 | 0.238314E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.214667E+10 | 0.00 | 17.84 | 0.205747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78408.32 | 78408.32 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.544491E+11 | 0.00 | 378.17 | 0.535766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140702.29 | 140702.29 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3103156.31 | 0.00 | 182.24 | 3103156.31 | 0.00 | 0.00 | 0.00 | 0.00 | 68.66 | 02-JAN-19:53 | 68.66 | 02-JAN-19:53 | 0.00 | 0.00 | 0.00 |
February | 0.198821E+12 | 0.00 | 290.22 | 0.198821E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 371343.27 | 27-FEB-15:13 | 371343.27 | 27-FEB-15:13 | 0.00 | 0.00 | 0.00 |
March | 0.329608E+12 | 0.00 | 420.15 | 0.329608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 297266.35 | 31-MAR-23:24 | 297266.35 | 31-MAR-23:24 | 0.00 | 0.00 | 0.00 |
April | 0.244862E+12 | 0.00 | 719.75 | 0.244862E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 334800.56 | 03-APR-13:59 | 334800.56 | 03-APR-13:59 | 0.00 | 0.00 | 0.00 |
May | 0.934275E+10 | 0.00 | 231.11 | 0.934275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 299590.35 | 31-MAY-23:50 | 299590.35 | 31-MAY-23:50 | 0.00 | 0.00 | 0.00 |
June | 0.261857E+12 | 0.00 | 491.66 | 0.258696E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 447540.39 | 21-JUN-23:52 | 431900.76 | 19-JUN-19:41 | 0.00 | 0.00 | 0.00 |
July | 0.432051E+12 | 0.00 | 696.70 | 0.429499E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 484040.84 | 01-JUL-01:01 | 374892.99 | 23-JUL-21:32 | 0.00 | 0.00 | 0.00 |
August | 0.459329E+12 | 0.00 | 743.17 | 0.459327E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 400028.30 | 05-AUG-09:02 | 400028.30 | 05-AUG-09:02 | 0.00 | 0.00 | 0.00 |
September | 0.335645E+11 | 0.00 | 316.72 | 0.335645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 308405.00 | 30-SEP-23:21 | 308405.00 | 30-SEP-23:21 | 0.00 | 0.00 | 0.00 |
October | 0.213671E+12 | 0.00 | 453.92 | 0.213670E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 443483.24 | 23-OCT-13:51 | 443483.24 | 23-OCT-13:51 | 0.00 | 0.00 | 0.00 |
November | 0.263558E+12 | 0.00 | 594.02 | 0.263558E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 355842.34 | 16-NOV-22:22 | 355842.34 | 16-NOV-22:22 | 0.00 | 0.00 | 0.00 |
December | 0.298394E+12 | 0.00 | 744.00 | 0.298394E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 316901.25 | 19-DEC-13:49 | 316901.25 | 19-DEC-13:49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274506E+13 | 0.00 | 5883.64 | 0.273935E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3103156.31 | 0.00 | 182.24 | 3103156.31 | 0.00 | 0.00 | 0.00 | 0.00 | 68.66 | 68.66 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.459329E+12 | 0.00 | 744.00 | 0.459327E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 484040.84 | 443483.24 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.441468E+10 | 0.137059E+10 | 625.40 | 0.441435E+10 | 328398.08 | 0.00 | 1.00 | 06-JAN-03:31 | 0.00 | 06-JAN-00:23 | 9061.77 | 06-JAN-03:31 | 9061.77 | 06-JAN-03:31 | 20.36 | 02-JAN-07:03 | 2340.51 | 06-JAN-03:31 | 0.00 | 01-JAN-00:03 |
February | 0.943480E+10 | 0.271512E+10 | 668.83 | 0.943480E+10 | -0.0 | 0.00 | 1.00 | 01-FEB-07:01 | 0.00 | 01-FEB-03:51 | 14590.53 | 01-FEB-07:01 | 14590.53 | 01-FEB-07:01 | 0.00 | 27-FEB-16:31 | 3923.92 | 01-FEB-07:01 | 0.00 | 01-FEB-00:01 |
March | 0.161653E+11 | 0.431642E+10 | 744.00 | 0.161653E+11 | -0.0 | 0.00 | 1.00 | 28-MAR-17:41 | 0.64 | 06-MAR-07:02 | 7910.13 | 31-MAR-23:57 | 7910.13 | 31-MAR-23:57 | 0.00 | 28-MAR-17:42 | 2016.66 | 31-MAR-23:57 | 0.00 | 01-MAR-00:01 |
April | 0.217185E+11 | 0.558322E+10 | 720.00 | 0.217185E+11 | -0.0 | 0.00 | 1.00 | 01-APR-00:02 | 0.43 | 30-APR-23:53 | 9823.14 | 22-APR-18:07 | 9823.14 | 22-APR-18:07 | 0.00 | 14-APR-10:46 | 2567.91 | 22-APR-18:03 | 0.00 | 01-APR-00:02 |
May | 0.763678E+10 | 0.231237E+10 | 744.00 | 0.763678E+10 | 8334.37 | 0.00 | 0.70 | 31-MAY-24:00 | 0.26 | 08-MAY-06:10 | 4934.21 | 31-MAY-23:51 | 4934.21 | 31-MAY-23:51 | 6.16 | 19-MAY-16:10 | 1380.67 | 31-MAY-23:51 | 0.00 | 01-MAY-00:10 |
June | 0.128085E+11 | 0.365987E+10 | 720.00 | 0.127813E+11 | 27208488.66 | 0.00 | 0.90 | 30-JUN-24:00 | 0.57 | 17-JUN-06:02 | 6865.93 | 30-JUN-24:00 | 6865.93 | 30-JUN-24:00 | 190.06 | 20-JUN-16:00 | 1891.95 | 29-JUN-15:00 | 0.00 | 01-JUN-00:01 |
July | 0.187747E+11 | 0.514126E+10 | 744.00 | 0.187445E+11 | 30240101.96 | 0.00 | 1.00 | 02-JUL-18:11 | 0.84 | 05-JUL-06:41 | 8728.89 | 31-JUL-23:05 | 8728.89 | 31-JUL-23:05 | 196.04 | 19-JUL-09:10 | 2756.88 | 17-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 0.237657E+11 | 0.639021E+10 | 744.00 | 0.237558E+11 | 9992654.06 | 0.00 | 1.00 | 01-AUG-00:10 | 0.51 | 31-AUG-24:00 | 10301.28 | 04-AUG-19:00 | 10301.28 | 04-AUG-19:00 | 162.41 | 22-AUG-15:40 | 3335.89 | 05-AUG-18:50 | 0.00 | 01-AUG-00:10 |
September | 0.775648E+10 | 0.237505E+10 | 720.00 | 0.772905E+10 | 27421147.61 | 0.00 | 0.67 | 30-SEP-23:31 | 0.32 | 19-SEP-06:10 | 4668.19 | 30-SEP-23:31 | 4668.19 | 30-SEP-23:31 | 297.65 | 07-SEP-15:20 | 1506.99 | 04-SEP-17:42 | 0.00 | 01-SEP-00:10 |
October | 0.122166E+11 | 0.345757E+10 | 744.00 | 0.122166E+11 | -0.0 | 0.00 | 0.85 | 31-OCT-23:52 | 0.53 | 10-OCT-06:01 | 6113.77 | 31-OCT-23:52 | 6113.77 | 31-OCT-23:52 | 0.00 | 05-OCT-15:09 | 1637.43 | 18-OCT-16:00 | 0.00 | 01-OCT-00:01 |
November | 0.161069E+11 | 0.428278E+10 | 720.00 | 0.161069E+11 | -0.0 | 0.00 | 0.98 | 13-NOV-16:21 | 0.70 | 27-NOV-07:01 | 7403.04 | 03-NOV-15:53 | 7403.04 | 03-NOV-15:53 | 0.00 | 01-NOV-15:03 | 1913.02 | 03-NOV-16:00 | 0.00 | 01-NOV-00:01 |
December | 0.206996E+11 | 0.528822E+10 | 733.50 | 0.206996E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-00:05 | 0.00 | 29-DEC-00:51 | 15441.45 | 29-DEC-09:41 | 15441.45 | 29-DEC-09:41 | 0.00 | 19-DEC-12:42 | 4163.03 | 29-DEC-09:41 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.171499E+12 | 0.468927E+11 | 8627.74 | 0.171404E+12 | 95199124.74 | 0.00 | ||||||||||||||
Minimum of Months | 0.441468E+10 | 0.137059E+10 | 625.40 | 0.441435E+10 | -0.0 | 0.00 | 0.67 | 0.00 | 4668.19 | 4668.19 | 0.00 | 1380.67 | 0.00 | |||||||
Maximum of Months | 0.237657E+11 | 0.639021E+10 | 744.00 | 0.237558E+11 | 30240101.96 | 0.00 | 1.00 | 0.84 | 15441.45 | 15441.45 | 297.65 | 4163.03 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.235673E+11 | 0.644100E+10 | 586.52 | 0.235658E+11 | 1464652.06 | 0.00 | 0.65 | 27-JAN-10:32 | 0.00 | 01-JAN-00:03 | 42177.70 | 27-JAN-10:32 | 42177.70 | 27-JAN-10:32 | 121.83 | 01-JAN-15:55 | 10242.75 | 27-JAN-10:32 | 0.00 | 01-JAN-00:03 |
February | 0.782147E+11 | 0.196512E+11 | 668.83 | 0.782147E+11 | 0.00 | 0.00 | 1.00 | 01-FEB-07:01 | 0.00 | 01-FEB-03:51 | 138286.89 | 01-FEB-07:01 | 138286.89 | 01-FEB-07:01 | 0.00 | 01-FEB-07:01 | 31797.15 | 01-FEB-07:01 | 0.00 | 01-FEB-00:01 |
March | 0.144855E+12 | 0.336086E+11 | 744.00 | 0.144855E+12 | -0.0 | 0.00 | 1.00 | 28-MAR-17:31 | 0.54 | 06-MAR-07:02 | 73624.15 | 28-MAR-17:42 | 73624.15 | 28-MAR-17:42 | 0.00 | 28-MAR-17:38 | 16027.94 | 28-MAR-17:42 | 0.00 | 01-MAR-00:01 |
April | 0.198788E+12 | 0.436296E+11 | 720.00 | 0.198788E+12 | -0.0 | 0.00 | 1.00 | 01-APR-10:52 | 0.26 | 30-APR-24:00 | 93435.38 | 25-APR-18:10 | 93435.38 | 25-APR-18:10 | 0.00 | 21-APR-15:02 | 20916.65 | 25-APR-18:01 | 0.00 | 01-APR-00:02 |
May | 0.651692E+11 | 0.170888E+11 | 744.00 | 0.651689E+11 | 281928.29 | 0.00 | 0.69 | 31-MAY-23:31 | 0.12 | 08-MAY-06:10 | 46601.89 | 31-MAY-23:31 | 46601.89 | 31-MAY-23:31 | 104.96 | 19-MAY-16:10 | 11213.66 | 31-MAY-23:31 | 0.00 | 01-MAY-00:10 |
June | 0.119935E+12 | 0.295144E+11 | 720.00 | 0.119663E+12 | 0.272232E+09 | 0.00 | 0.91 | 30-JUN-23:40 | 0.53 | 17-JUN-06:02 | 66711.51 | 30-JUN-23:40 | 66711.51 | 30-JUN-23:40 | 1901.75 | 20-JUN-16:00 | 15581.95 | 29-JUN-15:00 | 0.00 | 01-JUN-00:01 |
July | 0.177091E+12 | 0.417611E+11 | 744.00 | 0.176789E+12 | 0.302029E+09 | 0.00 | 1.00 | 02-JUL-18:21 | 0.81 | 05-JUL-06:35 | 84595.61 | 31-JUL-23:50 | 84595.61 | 31-JUL-23:50 | 1956.49 | 19-JUL-09:20 | 22557.20 | 17-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 0.223684E+12 | 0.514422E+11 | 744.00 | 0.223585E+12 | 98534098.18 | 0.00 | 1.00 | 01-AUG-00:10 | 0.45 | 31-AUG-24:00 | 99282.23 | 04-AUG-19:00 | 99282.23 | 04-AUG-19:00 | 1619.24 | 22-AUG-15:40 | 27169.07 | 05-AUG-18:50 | 0.00 | 01-AUG-00:10 |
September | 0.669921E+11 | 0.177801E+11 | 720.00 | 0.667200E+11 | 0.272109E+09 | 0.00 | 0.64 | 04-SEP-17:31 | 0.22 | 19-SEP-06:10 | 41415.93 | 30-SEP-23:11 | 41415.93 | 30-SEP-23:11 | 2972.23 | 07-SEP-15:30 | 12152.41 | 04-SEP-17:31 | 0.00 | 01-SEP-00:10 |
October | 0.107235E+12 | 0.263777E+11 | 744.00 | 0.107235E+12 | -0.0 | 0.00 | 0.81 | 18-OCT-17:00 | 0.40 | 10-OCT-06:01 | 56844.45 | 18-OCT-17:00 | 56844.45 | 18-OCT-17:00 | 0.00 | 06-OCT-15:37 | 13368.71 | 18-OCT-16:50 | 0.00 | 01-OCT-00:01 |
November | 0.139624E+12 | 0.324749E+11 | 720.00 | 0.139624E+12 | -0.0 | 0.00 | 0.95 | 03-NOV-15:51 | 0.55 | 27-NOV-04:04 | 70561.90 | 03-NOV-15:53 | 70561.90 | 03-NOV-15:53 | 0.00 | 03-NOV-14:56 | 15668.23 | 03-NOV-16:00 | 0.00 | 01-NOV-00:01 |
December | 0.177171E+12 | 0.393425E+11 | 733.50 | 0.177171E+12 | -0.0 | 0.00 | 1.00 | 01-DEC-09:52 | 0.00 | 29-DEC-00:51 | 146773.66 | 29-DEC-09:41 | 146773.66 | 29-DEC-09:41 | 0.00 | 19-DEC-14:54 | 33925.03 | 29-DEC-09:41 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.152233E+13 | 0.359112E+12 | 8588.86 | 0.152138E+13 | 0.946651E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.235673E+11 | 0.644100E+10 | 586.52 | 0.235658E+11 | -0.0 | 0.00 | 0.64 | 0.00 | 41415.93 | 41415.93 | 0.00 | 10242.75 | 0.00 | |||||||
Maximum of Months | 0.223684E+12 | 0.514422E+11 | 744.00 | 0.223585E+12 | 0.302029E+09 | 0.00 | 1.00 | 0.81 | 146773.66 | 146773.66 | 2972.23 | 33925.03 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.116568E+10 | 0.374890E+09 | 366.93 | 0.116568E+10 | -0.0 | 0.00 | 0.43 | 13-JAN-16:25 | 0.00 | 01-JAN-00:03 | 2772.64 | 13-JAN-16:25 | 2772.64 | 13-JAN-16:25 | 0.00 | 13-JAN-16:33 | 838.68 | 13-JAN-16:30 | 0.00 | 01-JAN-00:03 |
February | 0.586825E+10 | 0.176723E+10 | 668.35 | 0.586825E+10 | -0.0 | 0.00 | 1.00 | 01-FEB-07:01 | 0.00 | 01-FEB-03:51 | 12290.30 | 01-FEB-07:01 | 12290.30 | 01-FEB-07:01 | 0.00 | 24-FEB-16:45 | 3265.66 | 01-FEB-07:01 | 0.00 | 01-FEB-00:01 |
March | 0.124780E+11 | 0.347656E+10 | 744.00 | 0.124780E+11 | -0.0 | 0.00 | 0.98 | 28-MAR-17:50 | 0.32 | 06-MAR-04:24 | 7346.38 | 28-MAR-17:42 | 7346.38 | 28-MAR-17:42 | 0.00 | 22-MAR-14:25 | 1873.99 | 28-MAR-17:41 | 0.00 | 01-MAR-00:01 |
April | 0.183246E+11 | 0.476156E+10 | 719.00 | 0.183246E+11 | -0.0 | 0.00 | 1.00 | 01-APR-14:45 | 0.00 | 30-APR-23:03 | 9463.57 | 25-APR-18:10 | 9463.57 | 25-APR-18:10 | 0.00 | 20-APR-16:10 | 2467.60 | 25-APR-18:01 | 0.00 | 01-APR-00:02 |
May | 0.547827E+10 | 0.169060E+10 | 708.00 | 0.547826E+10 | 11970.28 | 0.00 | 0.66 | 31-MAY-23:12 | 0.00 | 01-MAY-00:10 | 4499.87 | 31-MAY-23:12 | 4499.87 | 31-MAY-23:12 | 7.44 | 19-MAY-16:10 | 1277.25 | 31-MAY-23:12 | 0.00 | 01-MAY-00:10 |
June | 0.115695E+11 | 0.335555E+10 | 720.00 | 0.115423E+11 | 27170601.59 | 0.00 | 0.89 | 30-JUN-23:20 | 0.38 | 17-JUN-06:02 | 6653.13 | 30-JUN-23:20 | 6653.13 | 30-JUN-23:20 | 191.14 | 20-JUN-16:00 | 1892.73 | 29-JUN-15:00 | 0.00 | 01-JUN-00:01 |
July | 0.174944E+11 | 0.486107E+10 | 744.00 | 0.174643E+11 | 30147705.77 | 0.00 | 1.00 | 02-JUL-18:21 | 0.70 | 08-JUL-06:02 | 8430.72 | 31-JUL-23:20 | 8430.72 | 31-JUL-23:20 | 196.71 | 19-JUL-09:20 | 2742.75 | 17-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 0.220435E+11 | 0.590817E+10 | 744.00 | 0.220341E+11 | 9405151.52 | 0.00 | 1.00 | 01-AUG-00:10 | 0.41 | 31-AUG-24:00 | 10115.00 | 04-AUG-19:00 | 10115.00 | 04-AUG-19:00 | 160.29 | 22-AUG-15:40 | 3246.84 | 05-AUG-18:50 | 0.00 | 01-AUG-00:10 |
September | 0.580154E+10 | 0.181911E+10 | 717.69 | 0.577442E+10 | 27117783.33 | 0.00 | 0.66 | 04-SEP-17:42 | 0.00 | 11-SEP-23:33 | 4327.06 | 04-SEP-17:42 | 4327.06 | 04-SEP-17:42 | 301.48 | 07-SEP-15:30 | 1506.32 | 04-SEP-17:31 | 0.00 | 01-SEP-00:10 |
October | 0.880886E+10 | 0.259432E+10 | 743.92 | 0.880886E+10 | -0.0 | 0.00 | 0.81 | 18-OCT-17:00 | 0.00 | 09-OCT-06:21 | 5779.78 | 18-OCT-17:00 | 5779.78 | 18-OCT-17:00 | 0.00 | 12-OCT-12:15 | 1592.66 | 18-OCT-16:00 | 0.00 | 01-OCT-00:01 |
November | 0.117271E+11 | 0.328831E+10 | 720.00 | 0.117271E+11 | -0.0 | 0.00 | 0.92 | 03-NOV-15:51 | 0.32 | 27-NOV-04:02 | 6976.76 | 03-NOV-15:53 | 6976.76 | 03-NOV-15:53 | 0.00 | 03-NOV-16:37 | 1824.86 | 03-NOV-16:00 | 0.00 | 01-NOV-00:01 |
December | 0.155004E+11 | 0.414254E+10 | 733.50 | 0.155004E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-14:32 | 0.00 | 29-DEC-00:51 | 14914.23 | 29-DEC-09:41 | 14914.23 | 29-DEC-09:41 | 0.00 | 07-DEC-14:58 | 4020.12 | 29-DEC-09:41 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.136260E+12 | 0.380399E+11 | 8329.39 | 0.136166E+12 | 93853212.50 | 0.00 | ||||||||||||||
Minimum of Months | 0.116568E+10 | 0.374890E+09 | 366.93 | 0.116568E+10 | -0.0 | 0.00 | 0.43 | 0.00 | 2772.64 | 2772.64 | 0.00 | 838.68 | 0.00 | |||||||
Maximum of Months | 0.220435E+11 | 0.590817E+10 | 744.00 | 0.220341E+11 | 30147705.77 | 0.00 | 1.00 | 0.70 | 14914.23 | 14914.23 | 301.48 | 4020.12 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.58 | 0.00 | 116.58 | 0.00 | 1537.54 | 0.00 | 0.00 | 0.00 |
February | 164.61 | 0.00 | 164.61 | 5.51 | 1157.18 | 0.00 | 0.00 | 0.00 |
March | 267.40 | 0.00 | 267.40 | 32.50 | 938.55 | 0.00 | 0.00 | 0.00 |
April | 304.89 | 1.78 | 303.11 | 90.80 | 676.20 | 0.00 | 0.00 | 0.00 |
May | 400.40 | 23.73 | 376.67 | 219.69 | 490.47 | 0.00 | 0.00 | 0.00 |
June | 466.24 | 53.59 | 412.65 | 415.32 | 298.22 | 0.00 | 0.00 | 0.00 |
July | 425.94 | 39.89 | 386.04 | 488.29 | 241.76 | 0.00 | 0.00 | 0.00 |
August | 341.31 | 9.15 | 332.16 | 345.35 | 289.10 | 0.00 | 0.00 | 0.00 |
September | 255.61 | 0.09 | 255.52 | 184.56 | 442.20 | 0.00 | 0.00 | 0.00 |
October | 186.46 | 0.00 | 186.46 | 41.82 | 679.01 | 0.00 | 0.00 | 0.00 |
November | 126.75 | 0.00 | 126.75 | 3.56 | 994.21 | 0.00 | 0.00 | 0.00 |
December | 97.76 | 0.00 | 97.76 | 0.01 | 1345.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 263.36 | 10.74 | 252.62 | 153.26 | 755.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 97.76 | 0.00 | 97.76 | 0.00 | 241.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 466.24 | 53.59 | 412.65 | 488.29 | 1537.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.58 | 0.00 | 116.58 | 0.00 | 1537.54 | 0.00 | 0.00 | 0.00 |
February | 164.61 | 0.00 | 164.61 | 5.51 | 1157.18 | 0.00 | 0.00 | 0.00 |
March | 267.40 | 0.00 | 267.40 | 32.50 | 938.55 | 0.00 | 0.00 | 0.00 |
April | 304.89 | 1.78 | 303.11 | 90.80 | 676.20 | 0.00 | 0.00 | 0.00 |
May | 400.40 | 23.73 | 376.67 | 219.69 | 490.47 | 0.00 | 0.00 | 0.00 |
June | 466.24 | 53.59 | 412.65 | 415.32 | 298.22 | 0.00 | 0.00 | 0.00 |
July | 425.94 | 39.89 | 386.04 | 488.29 | 241.76 | 0.00 | 0.00 | 0.00 |
August | 341.31 | 9.15 | 332.16 | 345.35 | 289.10 | 0.00 | 0.00 | 0.00 |
September | 255.61 | 0.09 | 255.52 | 184.56 | 442.20 | 0.00 | 0.00 | 0.00 |
October | 186.46 | 0.00 | 186.46 | 41.82 | 679.01 | 0.00 | 0.00 | 0.00 |
November | 126.75 | 0.00 | 126.75 | 3.56 | 994.21 | 0.00 | 0.00 | 0.00 |
December | 97.76 | 0.00 | 97.76 | 0.01 | 1345.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 263.36 | 10.74 | 252.62 | 153.26 | 755.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 97.76 | 0.00 | 97.76 | 0.00 | 241.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 466.24 | 53.59 | 412.65 | 488.29 | 1537.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.58 | 0.00 | 116.58 | 0.00 | 1537.54 | 0.00 | 0.00 | 0.00 |
February | 164.61 | 0.00 | 164.61 | 5.51 | 1157.18 | 0.00 | 0.00 | 0.00 |
March | 267.40 | 0.00 | 267.40 | 32.50 | 938.55 | 0.00 | 0.00 | 0.00 |
April | 304.89 | 1.78 | 303.11 | 90.80 | 676.20 | 0.00 | 0.00 | 0.00 |
May | 400.40 | 23.73 | 376.67 | 219.69 | 490.47 | 0.00 | 0.00 | 0.00 |
June | 466.24 | 53.59 | 412.65 | 415.32 | 298.22 | 0.00 | 0.00 | 0.00 |
July | 425.94 | 39.89 | 386.04 | 488.29 | 241.76 | 0.00 | 0.00 | 0.00 |
August | 341.31 | 9.15 | 332.16 | 345.35 | 289.10 | 0.00 | 0.00 | 0.00 |
September | 255.61 | 0.09 | 255.52 | 184.56 | 442.20 | 0.00 | 0.00 | 0.00 |
October | 186.46 | 0.00 | 186.46 | 41.82 | 679.01 | 0.00 | 0.00 | 0.00 |
November | 126.75 | 0.00 | 126.75 | 3.56 | 994.21 | 0.00 | 0.00 | 0.00 |
December | 97.76 | 0.00 | 97.76 | 0.01 | 1345.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 263.36 | 10.74 | 252.62 | 153.26 | 755.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 97.76 | 0.00 | 97.76 | 0.00 | 241.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 466.24 | 53.59 | 412.65 | 488.29 | 1537.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.58 | 0.00 | 116.58 | 0.00 | 1537.54 | 0.00 | 0.00 | 0.00 |
February | 164.61 | 0.00 | 164.61 | 5.51 | 1157.18 | 0.00 | 0.00 | 0.00 |
March | 267.40 | 0.00 | 267.40 | 32.50 | 938.55 | 0.00 | 0.00 | 0.00 |
April | 304.89 | 1.78 | 303.11 | 90.80 | 676.20 | 0.00 | 0.00 | 0.00 |
May | 400.40 | 23.73 | 376.67 | 219.69 | 490.47 | 0.00 | 0.00 | 0.00 |
June | 466.24 | 53.59 | 412.65 | 415.32 | 298.22 | 0.00 | 0.00 | 0.00 |
July | 425.94 | 39.89 | 386.04 | 488.29 | 241.76 | 0.00 | 0.00 | 0.00 |
August | 341.31 | 9.15 | 332.16 | 345.35 | 289.10 | 0.00 | 0.00 | 0.00 |
September | 255.61 | 0.09 | 255.52 | 184.56 | 442.20 | 0.00 | 0.00 | 0.00 |
October | 186.46 | 0.00 | 186.46 | 41.82 | 679.01 | 0.00 | 0.00 | 0.00 |
November | 126.75 | 0.00 | 126.75 | 3.56 | 994.21 | 0.00 | 0.00 | 0.00 |
December | 97.76 | 0.00 | 97.76 | 0.01 | 1345.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 263.36 | 10.74 | 252.62 | 153.26 | 755.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 97.76 | 0.00 | 97.76 | 0.00 | 241.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 466.24 | 53.59 | 412.65 | 488.29 | 1537.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.58 | 0.00 | 116.58 | 0.00 | 1537.47 | 0.00 | 0.00 | 0.00 |
February | 164.60 | 0.00 | 164.60 | 5.51 | 1157.13 | 0.00 | 0.00 | 0.00 |
March | 267.39 | 0.00 | 267.39 | 32.50 | 938.51 | 0.00 | 0.00 | 0.00 |
April | 304.88 | 1.78 | 303.10 | 90.80 | 676.17 | 0.00 | 0.00 | 0.00 |
May | 400.38 | 23.73 | 376.66 | 219.68 | 490.45 | 0.00 | 0.00 | 0.00 |
June | 466.22 | 53.59 | 412.63 | 415.31 | 298.20 | 0.00 | 0.00 | 0.00 |
July | 425.92 | 39.89 | 386.03 | 488.27 | 241.75 | 0.00 | 0.00 | 0.00 |
August | 341.29 | 9.15 | 332.14 | 345.34 | 289.09 | 0.00 | 0.00 | 0.00 |
September | 255.60 | 0.09 | 255.51 | 184.56 | 442.19 | 0.00 | 0.00 | 0.00 |
October | 186.45 | 0.00 | 186.45 | 41.82 | 678.98 | 0.00 | 0.00 | 0.00 |
November | 126.75 | 0.00 | 126.75 | 3.56 | 994.17 | 0.00 | 0.00 | 0.00 |
December | 97.76 | 0.00 | 97.76 | 0.01 | 1345.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 263.35 | 10.74 | 252.61 | 153.25 | 755.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 97.76 | 0.00 | 97.76 | 0.00 | 241.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 466.22 | 53.59 | 412.63 | 488.27 | 1537.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 297.45 | 136.37 | 161.08 | 108.90 | 1558.94 | 0.00 | 0.00 | 0.00 |
February | 465.24 | 230.98 | 234.26 | 276.45 | 1160.58 | 0.00 | 0.00 | 0.00 |
March | 625.56 | 258.84 | 366.72 | 409.56 | 950.66 | 0.00 | 0.00 | 0.00 |
April | 798.15 | 395.56 | 402.59 | 676.56 | 680.58 | 0.00 | 0.00 | 0.00 |
May | 881.66 | 392.28 | 489.38 | 828.66 | 525.96 | 0.00 | 0.00 | 0.00 |
June | 1141.19 | 587.26 | 553.94 | 1308.90 | 328.72 | 0.00 | 0.00 | 0.00 |
July | 1197.71 | 677.10 | 520.61 | 1528.43 | 255.55 | 0.00 | 0.00 | 0.00 |
August | 1040.87 | 579.94 | 460.93 | 1285.89 | 291.58 | 0.00 | 0.00 | 0.00 |
September | 736.31 | 380.08 | 356.23 | 791.88 | 442.23 | 0.00 | 0.00 | 0.00 |
October | 528.26 | 268.24 | 260.02 | 426.05 | 679.50 | 0.00 | 0.00 | 0.00 |
November | 334.80 | 156.31 | 178.49 | 170.87 | 982.36 | 0.00 | 0.00 | 0.00 |
December | 246.94 | 106.06 | 140.88 | 78.51 | 1352.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 692.36 | 348.02 | 344.34 | 659.82 | 765.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.94 | 106.06 | 140.88 | 78.51 | 255.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1197.71 | 677.10 | 553.94 | 1528.43 | 1558.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 297.45 | 136.37 | 161.08 | 108.90 | 1558.94 | 0.00 | 0.00 | 0.00 |
February | 465.24 | 230.98 | 234.26 | 276.45 | 1160.58 | 0.00 | 0.00 | 0.00 |
March | 625.56 | 258.84 | 366.72 | 409.56 | 950.66 | 0.00 | 0.00 | 0.00 |
April | 798.15 | 395.56 | 402.59 | 676.56 | 680.58 | 0.00 | 0.00 | 0.00 |
May | 881.66 | 392.28 | 489.38 | 828.66 | 525.96 | 0.00 | 0.00 | 0.00 |
June | 1141.19 | 587.26 | 553.94 | 1308.90 | 328.72 | 0.00 | 0.00 | 0.00 |
July | 1197.71 | 677.10 | 520.61 | 1528.43 | 255.55 | 0.00 | 0.00 | 0.00 |
August | 1040.87 | 579.94 | 460.93 | 1285.89 | 291.58 | 0.00 | 0.00 | 0.00 |
September | 736.31 | 380.08 | 356.23 | 791.88 | 442.23 | 0.00 | 0.00 | 0.00 |
October | 528.26 | 268.24 | 260.02 | 426.05 | 679.50 | 0.00 | 0.00 | 0.00 |
November | 334.80 | 156.31 | 178.49 | 170.87 | 982.36 | 0.00 | 0.00 | 0.00 |
December | 246.94 | 106.06 | 140.88 | 78.51 | 1352.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 692.36 | 348.02 | 344.34 | 659.82 | 765.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.94 | 106.06 | 140.88 | 78.51 | 255.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1197.71 | 677.10 | 553.94 | 1528.43 | 1558.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 297.45 | 136.37 | 161.08 | 108.90 | 1558.91 | 0.00 | 0.00 | 0.00 |
February | 465.23 | 230.98 | 234.25 | 276.45 | 1160.56 | 0.00 | 0.00 | 0.00 |
March | 625.54 | 258.83 | 366.71 | 409.56 | 950.65 | 0.00 | 0.00 | 0.00 |
April | 798.13 | 395.55 | 402.58 | 676.55 | 680.56 | 0.00 | 0.00 | 0.00 |
May | 881.64 | 392.28 | 489.37 | 828.65 | 525.95 | 0.00 | 0.00 | 0.00 |
June | 1141.17 | 587.25 | 553.93 | 1308.87 | 328.71 | 0.00 | 0.00 | 0.00 |
July | 1197.69 | 677.09 | 520.60 | 1528.40 | 255.55 | 0.00 | 0.00 | 0.00 |
August | 1040.85 | 579.93 | 460.92 | 1285.87 | 291.58 | 0.00 | 0.00 | 0.00 |
September | 736.30 | 380.07 | 356.22 | 791.87 | 442.22 | 0.00 | 0.00 | 0.00 |
October | 528.26 | 268.24 | 260.02 | 426.04 | 679.49 | 0.00 | 0.00 | 0.00 |
November | 334.80 | 156.31 | 178.49 | 170.86 | 982.34 | 0.00 | 0.00 | 0.00 |
December | 246.93 | 106.06 | 140.87 | 78.51 | 1352.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 692.35 | 348.01 | 344.34 | 659.80 | 765.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.93 | 106.06 | 140.87 | 78.51 | 255.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1197.69 | 677.09 | 553.93 | 1528.40 | 1558.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 821.79 | 586.94 | 234.85 | 654.56 | 1271.63 | 0.00 | 0.00 | 0.00 |
February | 1046.54 | 752.71 | 293.83 | 955.33 | 954.06 | 0.00 | 0.00 | 0.00 |
March | 935.47 | 525.31 | 410.15 | 850.53 | 856.94 | 0.00 | 0.00 | 0.00 |
April | 751.96 | 359.67 | 392.29 | 721.79 | 649.27 | 0.00 | 0.00 | 0.00 |
May | 668.10 | 221.89 | 446.20 | 657.16 | 506.80 | 0.00 | 0.00 | 0.00 |
June | 663.82 | 193.60 | 470.22 | 784.67 | 339.02 | 0.00 | 0.00 | 0.00 |
July | 715.66 | 264.36 | 451.30 | 979.30 | 261.50 | 0.00 | 0.00 | 0.00 |
August | 850.52 | 428.82 | 421.70 | 1124.30 | 299.95 | 0.00 | 0.00 | 0.00 |
September | 943.33 | 578.01 | 365.32 | 1131.74 | 427.65 | 0.00 | 0.00 | 0.00 |
October | 986.20 | 681.94 | 304.26 | 1046.70 | 609.52 | 0.00 | 0.00 | 0.00 |
November | 899.12 | 651.29 | 247.83 | 830.28 | 805.08 | 0.00 | 0.00 | 0.00 |
December | 781.47 | 564.30 | 217.17 | 639.52 | 1094.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 837.22 | 482.28 | 354.94 | 863.89 | 672.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 663.82 | 193.60 | 217.17 | 639.52 | 261.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1046.54 | 752.71 | 470.22 | 1131.74 | 1271.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 821.79 | 586.94 | 234.85 | 654.56 | 1271.63 | 0.00 | 0.00 | 0.00 |
February | 1046.53 | 752.71 | 293.83 | 955.33 | 954.06 | 0.00 | 0.00 | 0.00 |
March | 935.46 | 525.31 | 410.15 | 850.53 | 856.94 | 0.00 | 0.00 | 0.00 |
April | 751.96 | 359.67 | 392.29 | 721.79 | 649.27 | 0.00 | 0.00 | 0.00 |
May | 668.09 | 221.89 | 446.20 | 657.16 | 506.80 | 0.00 | 0.00 | 0.00 |
June | 663.82 | 193.60 | 470.22 | 784.67 | 339.02 | 0.00 | 0.00 | 0.00 |
July | 715.66 | 264.36 | 451.30 | 979.30 | 261.50 | 0.00 | 0.00 | 0.00 |
August | 850.52 | 428.82 | 421.70 | 1124.30 | 299.95 | 0.00 | 0.00 | 0.00 |
September | 943.33 | 578.01 | 365.32 | 1131.74 | 427.65 | 0.00 | 0.00 | 0.00 |
October | 986.20 | 681.94 | 304.26 | 1046.70 | 609.52 | 0.00 | 0.00 | 0.00 |
November | 899.12 | 651.29 | 247.83 | 830.28 | 805.08 | 0.00 | 0.00 | 0.00 |
December | 781.47 | 564.30 | 217.17 | 639.52 | 1094.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 837.22 | 482.28 | 354.94 | 863.88 | 672.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 663.82 | 193.60 | 217.17 | 639.52 | 261.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1046.53 | 752.71 | 470.22 | 1131.74 | 1271.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 821.79 | 586.94 | 234.85 | 654.56 | 1271.63 | 0.00 | 0.00 | 0.00 |
February | 1046.54 | 752.71 | 293.83 | 955.33 | 954.06 | 0.00 | 0.00 | 0.00 |
March | 935.47 | 525.31 | 410.15 | 850.53 | 856.94 | 0.00 | 0.00 | 0.00 |
April | 751.96 | 359.67 | 392.29 | 721.79 | 649.27 | 0.00 | 0.00 | 0.00 |
May | 668.10 | 221.89 | 446.20 | 657.16 | 506.80 | 0.00 | 0.00 | 0.00 |
June | 663.82 | 193.60 | 470.22 | 784.67 | 339.02 | 0.00 | 0.00 | 0.00 |
July | 715.66 | 264.36 | 451.30 | 979.30 | 261.50 | 0.00 | 0.00 | 0.00 |
August | 850.52 | 428.82 | 421.70 | 1124.30 | 299.95 | 0.00 | 0.00 | 0.00 |
September | 943.33 | 578.01 | 365.32 | 1131.74 | 427.65 | 0.00 | 0.00 | 0.00 |
October | 986.20 | 681.94 | 304.26 | 1046.70 | 609.52 | 0.00 | 0.00 | 0.00 |
November | 899.12 | 651.29 | 247.83 | 830.28 | 805.08 | 0.00 | 0.00 | 0.00 |
December | 781.47 | 564.30 | 217.17 | 639.52 | 1094.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 837.22 | 482.28 | 354.94 | 863.89 | 672.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 663.82 | 193.60 | 217.17 | 639.52 | 261.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1046.54 | 752.71 | 470.22 | 1131.74 | 1271.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 821.79 | 586.94 | 234.85 | 654.56 | 1271.63 | 0.00 | 0.00 | 0.00 |
February | 1046.53 | 752.71 | 293.83 | 955.33 | 954.06 | 0.00 | 0.00 | 0.00 |
March | 935.46 | 525.31 | 410.15 | 850.53 | 856.94 | 0.00 | 0.00 | 0.00 |
April | 751.96 | 359.67 | 392.29 | 721.79 | 649.27 | 0.00 | 0.00 | 0.00 |
May | 668.09 | 221.89 | 446.20 | 657.16 | 506.80 | 0.00 | 0.00 | 0.00 |
June | 663.82 | 193.60 | 470.22 | 784.67 | 339.02 | 0.00 | 0.00 | 0.00 |
July | 715.66 | 264.36 | 451.30 | 979.30 | 261.50 | 0.00 | 0.00 | 0.00 |
August | 850.52 | 428.82 | 421.70 | 1124.30 | 299.95 | 0.00 | 0.00 | 0.00 |
September | 943.33 | 578.01 | 365.32 | 1131.74 | 427.65 | 0.00 | 0.00 | 0.00 |
October | 986.20 | 681.94 | 304.26 | 1046.70 | 609.52 | 0.00 | 0.00 | 0.00 |
November | 899.12 | 651.29 | 247.83 | 830.28 | 805.08 | 0.00 | 0.00 | 0.00 |
December | 781.47 | 564.30 | 217.17 | 639.52 | 1094.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 837.22 | 482.28 | 354.94 | 863.88 | 672.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 663.82 | 193.60 | 217.17 | 639.52 | 261.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1046.53 | 752.71 | 470.22 | 1131.74 | 1271.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 821.76 | 586.91 | 234.84 | 654.53 | 1271.58 | 0.00 | 0.00 | 0.00 |
February | 1046.49 | 752.68 | 293.82 | 955.29 | 954.02 | 0.00 | 0.00 | 0.00 |
March | 935.43 | 525.29 | 410.13 | 850.50 | 856.91 | 0.00 | 0.00 | 0.00 |
April | 751.93 | 359.65 | 392.28 | 721.76 | 649.24 | 0.00 | 0.00 | 0.00 |
May | 668.07 | 221.88 | 446.18 | 657.13 | 506.78 | 0.00 | 0.00 | 0.00 |
June | 663.79 | 193.59 | 470.20 | 784.64 | 339.00 | 0.00 | 0.00 | 0.00 |
July | 715.64 | 264.35 | 451.28 | 979.26 | 261.49 | 0.00 | 0.00 | 0.00 |
August | 850.49 | 428.80 | 421.69 | 1124.26 | 299.94 | 0.00 | 0.00 | 0.00 |
September | 943.29 | 577.99 | 365.31 | 1131.69 | 427.64 | 0.00 | 0.00 | 0.00 |
October | 986.16 | 681.92 | 304.24 | 1046.66 | 609.49 | 0.00 | 0.00 | 0.00 |
November | 899.09 | 651.26 | 247.82 | 830.25 | 805.05 | 0.00 | 0.00 | 0.00 |
December | 781.44 | 564.28 | 217.16 | 639.50 | 1094.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 837.19 | 482.26 | 354.92 | 863.85 | 671.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 663.79 | 193.59 | 217.16 | 639.50 | 261.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1046.49 | 752.68 | 470.20 | 1131.69 | 1271.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 269.43 | 108.58 | 160.85 | 96.00 | 1684.01 | 0.00 | 0.00 | 0.00 |
February | 459.87 | 226.05 | 233.82 | 278.82 | 1248.60 | 0.00 | 0.00 | 0.00 |
March | 588.52 | 215.64 | 372.88 | 367.32 | 1060.33 | 0.00 | 0.00 | 0.00 |
April | 768.32 | 340.40 | 427.92 | 636.48 | 808.13 | 0.00 | 0.00 | 0.00 |
May | 950.36 | 433.41 | 516.94 | 925.67 | 603.09 | 0.00 | 0.00 | 0.00 |
June | 1033.95 | 474.93 | 559.02 | 1180.63 | 404.36 | 0.00 | 0.00 | 0.00 |
July | 1059.17 | 535.21 | 523.96 | 1351.13 | 342.95 | 0.00 | 0.00 | 0.00 |
August | 899.38 | 441.40 | 457.98 | 1093.41 | 390.13 | 0.00 | 0.00 | 0.00 |
September | 723.49 | 365.77 | 357.72 | 792.31 | 520.99 | 0.00 | 0.00 | 0.00 |
October | 517.10 | 256.92 | 260.18 | 430.93 | 769.05 | 0.00 | 0.00 | 0.00 |
November | 366.06 | 181.60 | 184.46 | 219.37 | 1090.35 | 0.00 | 0.00 | 0.00 |
December | 246.06 | 103.85 | 142.20 | 83.96 | 1497.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 657.70 | 307.28 | 350.43 | 623.21 | 866.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.06 | 103.85 | 142.20 | 83.96 | 342.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1059.17 | 535.21 | 559.02 | 1351.13 | 1684.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 269.43 | 108.58 | 160.85 | 96.00 | 1684.01 | 0.00 | 0.00 | 0.00 |
February | 459.87 | 226.05 | 233.82 | 278.82 | 1248.60 | 0.00 | 0.00 | 0.00 |
March | 588.52 | 215.64 | 372.88 | 367.32 | 1060.33 | 0.00 | 0.00 | 0.00 |
April | 768.32 | 340.40 | 427.92 | 636.48 | 808.13 | 0.00 | 0.00 | 0.00 |
May | 950.36 | 433.41 | 516.94 | 925.67 | 603.09 | 0.00 | 0.00 | 0.00 |
June | 1033.95 | 474.93 | 559.02 | 1180.63 | 404.36 | 0.00 | 0.00 | 0.00 |
July | 1059.17 | 535.21 | 523.96 | 1351.13 | 342.95 | 0.00 | 0.00 | 0.00 |
August | 899.38 | 441.40 | 457.98 | 1093.41 | 390.13 | 0.00 | 0.00 | 0.00 |
September | 723.49 | 365.77 | 357.72 | 792.31 | 520.99 | 0.00 | 0.00 | 0.00 |
October | 517.10 | 256.92 | 260.18 | 430.93 | 769.05 | 0.00 | 0.00 | 0.00 |
November | 366.06 | 181.60 | 184.46 | 219.37 | 1090.35 | 0.00 | 0.00 | 0.00 |
December | 246.06 | 103.85 | 142.20 | 83.96 | 1497.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 657.70 | 307.28 | 350.43 | 623.21 | 866.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.06 | 103.85 | 142.20 | 83.96 | 342.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1059.17 | 535.21 | 559.02 | 1351.13 | 1684.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 269.42 | 108.58 | 160.84 | 95.99 | 1683.98 | 0.00 | 0.00 | 0.00 |
February | 459.86 | 226.05 | 233.82 | 278.82 | 1248.58 | 0.00 | 0.00 | 0.00 |
March | 588.51 | 215.64 | 372.87 | 367.32 | 1060.31 | 0.00 | 0.00 | 0.00 |
April | 768.31 | 340.40 | 427.91 | 636.47 | 808.11 | 0.00 | 0.00 | 0.00 |
May | 950.34 | 433.41 | 516.93 | 925.65 | 603.08 | 0.00 | 0.00 | 0.00 |
June | 1033.93 | 474.92 | 559.01 | 1180.60 | 404.35 | 0.00 | 0.00 | 0.00 |
July | 1059.15 | 535.20 | 523.95 | 1351.10 | 342.95 | 0.00 | 0.00 | 0.00 |
August | 899.36 | 441.39 | 457.97 | 1093.39 | 390.13 | 0.00 | 0.00 | 0.00 |
September | 723.48 | 365.76 | 357.72 | 792.29 | 520.98 | 0.00 | 0.00 | 0.00 |
October | 517.09 | 256.91 | 260.18 | 430.93 | 769.03 | 0.00 | 0.00 | 0.00 |
November | 366.05 | 181.59 | 184.46 | 219.36 | 1090.33 | 0.00 | 0.00 | 0.00 |
December | 246.05 | 103.85 | 142.20 | 83.96 | 1497.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 657.69 | 307.27 | 350.42 | 623.20 | 866.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.05 | 103.85 | 142.20 | 83.96 | 342.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1059.15 | 535.20 | 559.01 | 1351.10 | 1683.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 582.91 | 0.00 | 582.91 | 2.40 | 7384.57 | 0.00 | 0.00 | 0.00 |
February | 823.04 | 0.00 | 823.04 | 55.00 | 5526.33 | 0.00 | 0.00 | 0.00 |
March | 1336.99 | 0.00 | 1336.99 | 207.79 | 4433.96 | 0.00 | 0.00 | 0.00 |
April | 1524.45 | 8.90 | 1515.55 | 544.85 | 3081.77 | 0.00 | 0.00 | 0.00 |
May | 2001.97 | 118.63 | 1883.34 | 1182.20 | 2269.92 | 0.00 | 0.00 | 0.00 |
June | 2331.18 | 267.95 | 2063.23 | 2162.91 | 1399.01 | 0.00 | 0.00 | 0.00 |
July | 2129.66 | 199.47 | 1930.19 | 2541.70 | 1120.69 | 0.00 | 0.00 | 0.00 |
August | 1706.51 | 45.74 | 1660.77 | 1821.44 | 1310.00 | 0.00 | 0.00 | 0.00 |
September | 1278.06 | 0.46 | 1277.60 | 1012.58 | 2012.77 | 0.00 | 0.00 | 0.00 |
October | 932.27 | 0.00 | 932.27 | 280.81 | 3065.10 | 0.00 | 0.00 | 0.00 |
November | 633.76 | 0.00 | 633.76 | 40.25 | 4535.17 | 0.00 | 0.00 | 0.00 |
December | 488.81 | 0.00 | 488.81 | 0.80 | 6264.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1316.77 | 53.69 | 1263.08 | 826.05 | 3525.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 488.81 | 0.00 | 488.81 | 0.80 | 1120.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2331.18 | 267.95 | 2063.23 | 2541.70 | 7384.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 892.34 | 409.10 | 483.24 | 342.45 | 4495.89 | 0.00 | 0.00 | 0.00 |
February | 1395.70 | 692.93 | 702.77 | 843.69 | 3367.98 | 0.00 | 0.00 | 0.00 |
March | 1876.65 | 776.51 | 1100.14 | 1223.81 | 2747.84 | 0.00 | 0.00 | 0.00 |
April | 2394.42 | 1186.66 | 1207.76 | 2016.48 | 1946.49 | 0.00 | 0.00 | 0.00 |
May | 2644.95 | 1176.84 | 1468.11 | 2462.02 | 1502.30 | 0.00 | 0.00 | 0.00 |
June | 3423.54 | 1761.75 | 1661.79 | 3888.45 | 955.88 | 0.00 | 0.00 | 0.00 |
July | 3593.11 | 2031.28 | 1561.83 | 4548.55 | 749.28 | 0.00 | 0.00 | 0.00 |
August | 3122.57 | 1739.80 | 1382.77 | 3823.42 | 857.54 | 0.00 | 0.00 | 0.00 |
September | 2208.91 | 1140.23 | 1068.68 | 2358.61 | 1264.63 | 0.00 | 0.00 | 0.00 |
October | 1584.78 | 804.73 | 780.05 | 1284.01 | 1911.36 | 0.00 | 0.00 | 0.00 |
November | 1004.40 | 468.92 | 535.48 | 535.20 | 2757.73 | 0.00 | 0.00 | 0.00 |
December | 740.80 | 318.18 | 422.63 | 252.12 | 3824.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2077.07 | 1044.05 | 1033.02 | 1971.54 | 2193.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 740.80 | 318.18 | 422.63 | 252.12 | 749.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3593.11 | 2031.28 | 1661.79 | 4548.55 | 4495.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4108.89 | 2934.65 | 1174.24 | 3235.77 | 6307.62 | 0.00 | 0.00 | 0.00 |
February | 5232.61 | 3763.49 | 1469.12 | 4690.38 | 4764.19 | 0.00 | 0.00 | 0.00 |
March | 4677.27 | 2626.54 | 2050.73 | 4175.48 | 4262.85 | 0.00 | 0.00 | 0.00 |
April | 3759.74 | 1798.31 | 1961.43 | 3569.57 | 3173.62 | 0.00 | 0.00 | 0.00 |
May | 3340.44 | 1109.45 | 2230.99 | 3244.41 | 2486.15 | 0.00 | 0.00 | 0.00 |
June | 3319.06 | 968.00 | 2351.06 | 3893.03 | 1665.72 | 0.00 | 0.00 | 0.00 |
July | 3578.28 | 1321.81 | 2256.47 | 4881.24 | 1274.82 | 0.00 | 0.00 | 0.00 |
August | 4252.55 | 2144.06 | 2108.49 | 5588.81 | 1461.97 | 0.00 | 0.00 | 0.00 |
September | 4716.59 | 2890.01 | 1826.58 | 5581.33 | 2113.49 | 0.00 | 0.00 | 0.00 |
October | 4930.94 | 3409.68 | 1521.26 | 5158.32 | 3008.03 | 0.00 | 0.00 | 0.00 |
November | 4495.56 | 3256.40 | 1239.16 | 4115.68 | 3945.92 | 0.00 | 0.00 | 0.00 |
December | 3907.33 | 2821.48 | 1085.84 | 3187.31 | 5331.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4186.05 | 2411.39 | 1774.66 | 4273.23 | 3310.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3319.06 | 968.00 | 1085.84 | 3187.31 | 1274.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5232.61 | 3763.49 | 2351.06 | 5588.81 | 6307.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 808.27 | 325.74 | 482.53 | 302.20 | 4805.99 | 0.00 | 0.00 | 0.00 |
February | 1379.60 | 678.14 | 701.46 | 858.93 | 3532.66 | 0.00 | 0.00 | 0.00 |
March | 1765.55 | 646.93 | 1118.63 | 1130.83 | 2968.41 | 0.00 | 0.00 | 0.00 |
April | 2304.94 | 1021.19 | 1283.74 | 1982.59 | 2133.61 | 0.00 | 0.00 | 0.00 |
May | 2851.04 | 1300.23 | 1550.82 | 2801.26 | 1677.91 | 0.00 | 0.00 | 0.00 |
June | 3101.83 | 1424.78 | 1677.04 | 3575.24 | 1128.27 | 0.00 | 0.00 | 0.00 |
July | 3177.48 | 1605.63 | 1571.85 | 4122.30 | 919.63 | 0.00 | 0.00 | 0.00 |
August | 2698.11 | 1324.17 | 1373.93 | 3372.85 | 997.08 | 0.00 | 0.00 | 0.00 |
September | 2170.46 | 1097.29 | 1073.16 | 2414.50 | 1430.52 | 0.00 | 0.00 | 0.00 |
October | 1551.28 | 770.75 | 780.53 | 1337.71 | 2087.97 | 0.00 | 0.00 | 0.00 |
November | 1098.16 | 544.78 | 553.38 | 704.54 | 2940.70 | 0.00 | 0.00 | 0.00 |
December | 738.16 | 311.56 | 426.61 | 280.39 | 4042.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1973.09 | 921.82 | 1051.27 | 1912.68 | 2384.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 738.16 | 311.56 | 426.61 | 280.39 | 919.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3177.48 | 1605.63 | 1677.04 | 4122.30 | 4805.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 582.91 | 0.00 | 582.91 | 5.52 | 7189.60 | 0.00 | 0.00 | 0.00 |
February | 823.04 | 0.00 | 823.04 | 78.80 | 5269.75 | 0.00 | 0.00 | 0.00 |
March | 1336.99 | 0.00 | 1336.99 | 235.58 | 4164.58 | 0.00 | 0.00 | 0.00 |
April | 1524.45 | 8.90 | 1515.55 | 594.26 | 2803.97 | 0.00 | 0.00 | 0.00 |
May | 2001.97 | 118.63 | 1883.34 | 1230.27 | 2081.07 | 0.00 | 0.00 | 0.00 |
June | 2331.18 | 267.95 | 2063.23 | 2223.95 | 1297.32 | 0.00 | 0.00 | 0.00 |
July | 2129.66 | 199.47 | 1930.19 | 2591.26 | 1044.33 | 0.00 | 0.00 | 0.00 |
August | 1706.51 | 45.74 | 1660.77 | 1865.92 | 1204.90 | 0.00 | 0.00 | 0.00 |
September | 1278.06 | 0.46 | 1277.60 | 1063.51 | 1829.08 | 0.00 | 0.00 | 0.00 |
October | 932.27 | 0.00 | 932.27 | 338.37 | 2733.96 | 0.00 | 0.00 | 0.00 |
November | 633.76 | 0.00 | 633.76 | 61.59 | 4204.08 | 0.00 | 0.00 | 0.00 |
December | 488.81 | 0.00 | 488.81 | 1.02 | 6007.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1316.77 | 53.69 | 1263.08 | 862.50 | 3311.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 488.81 | 0.00 | 488.81 | 1.02 | 1044.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2331.18 | 267.95 | 2063.23 | 2591.26 | 7189.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 892.34 | 409.10 | 483.24 | 357.13 | 4384.16 | 0.00 | 0.00 | 0.00 |
February | 1395.70 | 692.93 | 702.77 | 889.19 | 3205.73 | 0.00 | 0.00 | 0.00 |
March | 1876.65 | 776.51 | 1100.14 | 1277.61 | 2570.67 | 0.00 | 0.00 | 0.00 |
April | 2394.42 | 1186.66 | 1207.76 | 2072.64 | 1777.31 | 0.00 | 0.00 | 0.00 |
May | 2644.95 | 1176.84 | 1468.11 | 2496.59 | 1391.71 | 0.00 | 0.00 | 0.00 |
June | 3423.54 | 1761.75 | 1661.79 | 3903.32 | 907.56 | 0.00 | 0.00 | 0.00 |
July | 3593.11 | 2031.28 | 1561.83 | 4550.43 | 715.79 | 0.00 | 0.00 | 0.00 |
August | 3122.57 | 1739.80 | 1382.77 | 3829.44 | 811.50 | 0.00 | 0.00 | 0.00 |
September | 2208.91 | 1140.23 | 1068.68 | 2396.13 | 1165.26 | 0.00 | 0.00 | 0.00 |
October | 1584.78 | 804.73 | 780.05 | 1361.67 | 1701.03 | 0.00 | 0.00 | 0.00 |
November | 1004.40 | 468.92 | 535.48 | 586.01 | 2540.72 | 0.00 | 0.00 | 0.00 |
December | 740.80 | 318.18 | 422.63 | 267.43 | 3668.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2077.07 | 1044.05 | 1033.02 | 2005.45 | 2065.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 740.80 | 318.18 | 422.63 | 267.43 | 715.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3593.11 | 2031.28 | 1661.79 | 4550.43 | 4384.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4108.89 | 2934.65 | 1174.24 | 3286.96 | 6081.14 | 0.00 | 0.00 | 0.00 |
February | 5232.61 | 3763.49 | 1469.12 | 4761.87 | 4485.87 | 0.00 | 0.00 | 0.00 |
March | 4677.27 | 2626.54 | 2050.73 | 4226.56 | 3981.39 | 0.00 | 0.00 | 0.00 |
April | 3759.74 | 1798.31 | 1961.43 | 3625.63 | 2892.76 | 0.00 | 0.00 | 0.00 |
May | 3340.44 | 1109.45 | 2230.99 | 3271.34 | 2289.02 | 0.00 | 0.00 | 0.00 |
June | 3319.06 | 968.00 | 2351.06 | 3912.28 | 1552.03 | 0.00 | 0.00 | 0.00 |
July | 3578.28 | 1321.81 | 2256.47 | 4893.53 | 1188.75 | 0.00 | 0.00 | 0.00 |
August | 4252.55 | 2144.06 | 2108.49 | 5595.12 | 1358.80 | 0.00 | 0.00 | 0.00 |
September | 4716.59 | 2890.01 | 1826.58 | 5613.35 | 1934.44 | 0.00 | 0.00 | 0.00 |
October | 4930.94 | 3409.68 | 1521.26 | 5238.28 | 2691.15 | 0.00 | 0.00 | 0.00 |
November | 4495.56 | 3256.40 | 1239.16 | 4220.65 | 3616.80 | 0.00 | 0.00 | 0.00 |
December | 3907.33 | 2821.48 | 1085.84 | 3250.51 | 5064.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4186.05 | 2411.39 | 1774.66 | 4320.88 | 3089.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3319.06 | 968.00 | 1085.84 | 3250.51 | 1188.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5232.61 | 3763.49 | 2351.06 | 5613.35 | 6081.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 808.27 | 325.74 | 482.53 | 307.83 | 4685.28 | 0.00 | 0.00 | 0.00 |
February | 1379.60 | 678.14 | 701.46 | 871.54 | 3377.72 | 0.00 | 0.00 | 0.00 |
March | 1765.55 | 646.93 | 1118.63 | 1140.09 | 2811.89 | 0.00 | 0.00 | 0.00 |
April | 2304.94 | 1021.19 | 1283.74 | 1996.56 | 1978.03 | 0.00 | 0.00 | 0.00 |
May | 2851.04 | 1300.23 | 1550.82 | 2798.35 | 1567.49 | 0.00 | 0.00 | 0.00 |
June | 3101.83 | 1424.78 | 1677.04 | 3565.47 | 1069.70 | 0.00 | 0.00 | 0.00 |
July | 3177.48 | 1605.63 | 1571.85 | 4112.05 | 876.76 | 0.00 | 0.00 | 0.00 |
August | 2698.11 | 1324.17 | 1373.93 | 3366.28 | 946.04 | 0.00 | 0.00 | 0.00 |
September | 2170.46 | 1097.29 | 1073.16 | 2417.24 | 1336.55 | 0.00 | 0.00 | 0.00 |
October | 1551.28 | 770.75 | 780.53 | 1361.99 | 1908.33 | 0.00 | 0.00 | 0.00 |
November | 1098.16 | 544.78 | 553.38 | 725.73 | 2753.86 | 0.00 | 0.00 | 0.00 |
December | 738.16 | 311.56 | 426.61 | 286.95 | 3894.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1973.09 | 921.82 | 1051.27 | 1918.17 | 2263.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 738.16 | 311.56 | 426.61 | 286.95 | 876.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3177.48 | 1605.63 | 1677.04 | 4112.05 | 4685.28 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.312259E+09 | 0.00 | 0.312259E+09 | 9331.83 | 0.411814E+10 |
February | 0.398223E+09 | 0.00 | 0.398223E+09 | 13340663.75 | 0.279944E+10 |
March | 0.716207E+09 | 0.00 | 0.716207E+09 | 87054118.54 | 0.251380E+10 |
April | 0.790284E+09 | 4611923.39 | 0.785673E+09 | 0.235359E+09 | 0.175271E+10 |
May | 0.107243E+10 | 63547929.39 | 0.100888E+10 | 0.588409E+09 | 0.131369E+10 |
June | 0.120850E+10 | 0.138907E+09 | 0.106959E+10 | 0.107652E+10 | 0.772976E+09 |
July | 0.114083E+10 | 0.106852E+09 | 0.103398E+10 | 0.130783E+10 | 0.647540E+09 |
August | 0.914153E+09 | 24503575.52 | 0.889650E+09 | 0.924991E+09 | 0.774324E+09 |
September | 0.662552E+09 | 237759.72 | 0.662315E+09 | 0.478386E+09 | 0.114619E+10 |
October | 0.499403E+09 | 0.00 | 0.499403E+09 | 0.112005E+09 | 0.181865E+10 |
November | 0.328548E+09 | 0.00 | 0.328548E+09 | 9238670.24 | 0.257700E+10 |
December | 0.261847E+09 | 0.00 | 0.261847E+09 | 32185.37 | 0.360338E+10 |
Annual Sum or Average | 0.830523E+10 | 0.338660E+09 | 0.796657E+10 | 0.483317E+10 | 0.238378E+11 |
Minimum of Months | 0.261847E+09 | 0.00 | 0.261847E+09 | 9331.83 | 0.647540E+09 |
Maximum of Months | 0.120850E+10 | 0.138907E+09 | 0.106959E+10 | 0.130783E+10 | 0.411814E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.312259E+09 | 0.00 | 0.312259E+09 | 9331.42 | 0.411814E+10 |
February | 0.398223E+09 | 0.00 | 0.398223E+09 | 13340629.29 | 0.279944E+10 |
March | 0.716206E+09 | 0.00 | 0.716206E+09 | 87053848.58 | 0.251380E+10 |
April | 0.790284E+09 | 4611917.85 | 0.785672E+09 | 0.235359E+09 | 0.175271E+10 |
May | 0.107243E+10 | 63547853.14 | 0.100888E+10 | 0.588408E+09 | 0.131369E+10 |
June | 0.120850E+10 | 0.138906E+09 | 0.106959E+10 | 0.107651E+10 | 0.772976E+09 |
July | 0.114083E+10 | 0.106852E+09 | 0.103398E+10 | 0.130783E+10 | 0.647540E+09 |
August | 0.914153E+09 | 24503546.12 | 0.889649E+09 | 0.924990E+09 | 0.774324E+09 |
September | 0.662552E+09 | 237759.44 | 0.662314E+09 | 0.478386E+09 | 0.114619E+10 |
October | 0.499403E+09 | 0.00 | 0.499403E+09 | 0.112005E+09 | 0.181865E+10 |
November | 0.328547E+09 | 0.00 | 0.328547E+09 | 9238619.42 | 0.257700E+10 |
December | 0.261847E+09 | 0.00 | 0.261847E+09 | 32184.30 | 0.360338E+10 |
Annual Sum or Average | 0.830523E+10 | 0.338660E+09 | 0.796657E+10 | 0.483317E+10 | 0.238378E+11 |
Minimum of Months | 0.261847E+09 | 0.00 | 0.261847E+09 | 9331.42 | 0.647540E+09 |
Maximum of Months | 0.120850E+10 | 0.138906E+09 | 0.106959E+10 | 0.130783E+10 | 0.411814E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.312259E+09 | 0.00 | 0.312259E+09 | 9331.83 | 0.411814E+10 |
February | 0.398223E+09 | 0.00 | 0.398223E+09 | 13340663.75 | 0.279944E+10 |
March | 0.716207E+09 | 0.00 | 0.716207E+09 | 87054118.54 | 0.251380E+10 |
April | 0.790284E+09 | 4611923.39 | 0.785673E+09 | 0.235359E+09 | 0.175271E+10 |
May | 0.107243E+10 | 63547929.39 | 0.100888E+10 | 0.588409E+09 | 0.131369E+10 |
June | 0.120850E+10 | 0.138907E+09 | 0.106959E+10 | 0.107652E+10 | 0.772976E+09 |
July | 0.114083E+10 | 0.106852E+09 | 0.103398E+10 | 0.130783E+10 | 0.647540E+09 |
August | 0.914153E+09 | 24503575.52 | 0.889650E+09 | 0.924991E+09 | 0.774324E+09 |
September | 0.662552E+09 | 237759.72 | 0.662315E+09 | 0.478386E+09 | 0.114619E+10 |
October | 0.499403E+09 | 0.00 | 0.499403E+09 | 0.112005E+09 | 0.181865E+10 |
November | 0.328548E+09 | 0.00 | 0.328548E+09 | 9238670.24 | 0.257700E+10 |
December | 0.261847E+09 | 0.00 | 0.261847E+09 | 32185.37 | 0.360338E+10 |
Annual Sum or Average | 0.830523E+10 | 0.338660E+09 | 0.796657E+10 | 0.483317E+10 | 0.238378E+11 |
Minimum of Months | 0.261847E+09 | 0.00 | 0.261847E+09 | 9331.83 | 0.647540E+09 |
Maximum of Months | 0.120850E+10 | 0.138907E+09 | 0.106959E+10 | 0.130783E+10 | 0.411814E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.312259E+09 | 0.00 | 0.312259E+09 | 9331.42 | 0.411814E+10 |
February | 0.398223E+09 | 0.00 | 0.398223E+09 | 13340629.29 | 0.279944E+10 |
March | 0.716206E+09 | 0.00 | 0.716206E+09 | 87053848.58 | 0.251380E+10 |
April | 0.790284E+09 | 4611917.85 | 0.785672E+09 | 0.235359E+09 | 0.175271E+10 |
May | 0.107243E+10 | 63547853.14 | 0.100888E+10 | 0.588408E+09 | 0.131369E+10 |
June | 0.120850E+10 | 0.138906E+09 | 0.106959E+10 | 0.107651E+10 | 0.772976E+09 |
July | 0.114083E+10 | 0.106852E+09 | 0.103398E+10 | 0.130783E+10 | 0.647540E+09 |
August | 0.914153E+09 | 24503546.12 | 0.889649E+09 | 0.924990E+09 | 0.774324E+09 |
September | 0.662552E+09 | 237759.44 | 0.662314E+09 | 0.478386E+09 | 0.114619E+10 |
October | 0.499403E+09 | 0.00 | 0.499403E+09 | 0.112005E+09 | 0.181865E+10 |
November | 0.328547E+09 | 0.00 | 0.328547E+09 | 9238619.42 | 0.257700E+10 |
December | 0.261847E+09 | 0.00 | 0.261847E+09 | 32184.30 | 0.360338E+10 |
Annual Sum or Average | 0.830523E+10 | 0.338660E+09 | 0.796657E+10 | 0.483317E+10 | 0.238378E+11 |
Minimum of Months | 0.261847E+09 | 0.00 | 0.261847E+09 | 9331.42 | 0.647540E+09 |
Maximum of Months | 0.120850E+10 | 0.138906E+09 | 0.106959E+10 | 0.130783E+10 | 0.411814E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.312247E+09 | 0.00 | 0.312247E+09 | 9331.45 | 0.411797E+10 |
February | 0.398207E+09 | 0.00 | 0.398207E+09 | 13340126.06 | 0.279933E+10 |
March | 0.716178E+09 | 0.00 | 0.716178E+09 | 87050609.88 | 0.251370E+10 |
April | 0.790253E+09 | 4611737.51 | 0.785641E+09 | 0.235350E+09 | 0.175264E+10 |
May | 0.107238E+10 | 63545368.13 | 0.100884E+10 | 0.588385E+09 | 0.131363E+10 |
June | 0.120845E+10 | 0.138901E+09 | 0.106955E+10 | 0.107647E+10 | 0.772945E+09 |
July | 0.114078E+10 | 0.106848E+09 | 0.103394E+10 | 0.130778E+10 | 0.647514E+09 |
August | 0.914116E+09 | 24502587.92 | 0.889614E+09 | 0.924953E+09 | 0.774293E+09 |
September | 0.662526E+09 | 237750.14 | 0.662288E+09 | 0.478367E+09 | 0.114615E+10 |
October | 0.499383E+09 | 0.00 | 0.499383E+09 | 0.112000E+09 | 0.181858E+10 |
November | 0.328534E+09 | 0.00 | 0.328534E+09 | 9238297.88 | 0.257690E+10 |
December | 0.261836E+09 | 0.00 | 0.261836E+09 | 32184.07 | 0.360323E+10 |
Annual Sum or Average | 0.830490E+10 | 0.338647E+09 | 0.796625E+10 | 0.483298E+10 | 0.238369E+11 |
Minimum of Months | 0.261836E+09 | 0.00 | 0.261836E+09 | 9331.45 | 0.647514E+09 |
Maximum of Months | 0.120845E+10 | 0.138901E+09 | 0.106955E+10 | 0.130778E+10 | 0.411797E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.796692E+09 | 0.365251E+09 | 0.431441E+09 | 0.291687E+09 | 0.417546E+10 |
February | 0.112551E+10 | 0.558787E+09 | 0.566719E+09 | 0.668794E+09 | 0.280768E+10 |
March | 0.167549E+10 | 0.693271E+09 | 0.982219E+09 | 0.109698E+10 | 0.254625E+10 |
April | 0.206880E+10 | 0.102528E+10 | 0.104352E+10 | 0.175365E+10 | 0.176406E+10 |
May | 0.236143E+10 | 0.105069E+10 | 0.131074E+10 | 0.221950E+10 | 0.140872E+10 |
June | 0.295797E+10 | 0.152217E+10 | 0.143580E+10 | 0.339267E+10 | 0.852045E+09 |
July | 0.320796E+10 | 0.181354E+10 | 0.139441E+10 | 0.409374E+10 | 0.684478E+09 |
August | 0.278786E+10 | 0.155331E+10 | 0.123455E+10 | 0.344413E+10 | 0.780978E+09 |
September | 0.190852E+10 | 0.985170E+09 | 0.923348E+09 | 0.205256E+10 | 0.114627E+10 |
October | 0.141490E+10 | 0.718466E+09 | 0.696438E+09 | 0.114112E+10 | 0.181997E+10 |
November | 0.867812E+09 | 0.405154E+09 | 0.462658E+09 | 0.442884E+09 | 0.254628E+10 |
December | 0.661397E+09 | 0.284071E+09 | 0.377325E+09 | 0.210273E+09 | 0.362196E+10 |
Annual Sum or Average | 0.218343E+11 | 0.109752E+11 | 0.108592E+11 | 0.208080E+11 | 0.241541E+11 |
Minimum of Months | 0.661397E+09 | 0.284071E+09 | 0.377325E+09 | 0.210273E+09 | 0.684478E+09 |
Maximum of Months | 0.320796E+10 | 0.181354E+10 | 0.143580E+10 | 0.409374E+10 | 0.417546E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.796692E+09 | 0.365251E+09 | 0.431441E+09 | 0.291687E+09 | 0.417546E+10 |
February | 0.112551E+10 | 0.558787E+09 | 0.566719E+09 | 0.668794E+09 | 0.280768E+10 |
March | 0.167549E+10 | 0.693271E+09 | 0.982219E+09 | 0.109698E+10 | 0.254625E+10 |
April | 0.206880E+10 | 0.102528E+10 | 0.104352E+10 | 0.175365E+10 | 0.176406E+10 |
May | 0.236143E+10 | 0.105069E+10 | 0.131074E+10 | 0.221950E+10 | 0.140872E+10 |
June | 0.295797E+10 | 0.152217E+10 | 0.143580E+10 | 0.339267E+10 | 0.852045E+09 |
July | 0.320796E+10 | 0.181354E+10 | 0.139441E+10 | 0.409374E+10 | 0.684478E+09 |
August | 0.278786E+10 | 0.155331E+10 | 0.123455E+10 | 0.344413E+10 | 0.780978E+09 |
September | 0.190852E+10 | 0.985170E+09 | 0.923348E+09 | 0.205256E+10 | 0.114627E+10 |
October | 0.141490E+10 | 0.718466E+09 | 0.696438E+09 | 0.114112E+10 | 0.181997E+10 |
November | 0.867812E+09 | 0.405154E+09 | 0.462658E+09 | 0.442884E+09 | 0.254628E+10 |
December | 0.661397E+09 | 0.284071E+09 | 0.377325E+09 | 0.210273E+09 | 0.362196E+10 |
Annual Sum or Average | 0.218343E+11 | 0.109752E+11 | 0.108592E+11 | 0.208080E+11 | 0.241541E+11 |
Minimum of Months | 0.661397E+09 | 0.284071E+09 | 0.377325E+09 | 0.210273E+09 | 0.684478E+09 |
Maximum of Months | 0.320796E+10 | 0.181354E+10 | 0.143580E+10 | 0.409374E+10 | 0.417546E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.796677E+09 | 0.365244E+09 | 0.431433E+09 | 0.291682E+09 | 0.417539E+10 |
February | 0.112549E+10 | 0.558777E+09 | 0.566709E+09 | 0.668782E+09 | 0.280763E+10 |
March | 0.167546E+10 | 0.693258E+09 | 0.982201E+09 | 0.109696E+10 | 0.254621E+10 |
April | 0.206876E+10 | 0.102526E+10 | 0.104350E+10 | 0.175362E+10 | 0.176402E+10 |
May | 0.236139E+10 | 0.105067E+10 | 0.131072E+10 | 0.221945E+10 | 0.140869E+10 |
June | 0.295792E+10 | 0.152214E+10 | 0.143578E+10 | 0.339260E+10 | 0.852029E+09 |
July | 0.320790E+10 | 0.181351E+10 | 0.139439E+10 | 0.409366E+10 | 0.684465E+09 |
August | 0.278781E+10 | 0.155328E+10 | 0.123453E+10 | 0.344407E+10 | 0.780963E+09 |
September | 0.190848E+10 | 0.985152E+09 | 0.923331E+09 | 0.205252E+10 | 0.114625E+10 |
October | 0.141488E+10 | 0.718453E+09 | 0.696425E+09 | 0.114110E+10 | 0.181994E+10 |
November | 0.867796E+09 | 0.405147E+09 | 0.462649E+09 | 0.442876E+09 | 0.254623E+10 |
December | 0.661385E+09 | 0.284066E+09 | 0.377319E+09 | 0.210270E+09 | 0.362189E+10 |
Annual Sum or Average | 0.218339E+11 | 0.109750E+11 | 0.108590E+11 | 0.208076E+11 | 0.241537E+11 |
Minimum of Months | 0.661385E+09 | 0.284066E+09 | 0.377319E+09 | 0.210270E+09 | 0.684465E+09 |
Maximum of Months | 0.320790E+10 | 0.181351E+10 | 0.143578E+10 | 0.409366E+10 | 0.417539E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.220108E+10 | 0.157205E+10 | 0.629024E+09 | 0.175316E+10 | 0.340592E+10 |
February | 0.253178E+10 | 0.182095E+10 | 0.710829E+09 | 0.231113E+10 | 0.230805E+10 |
March | 0.250555E+10 | 0.140700E+10 | 0.109855E+10 | 0.227807E+10 | 0.229523E+10 |
April | 0.194907E+10 | 0.932255E+09 | 0.101682E+10 | 0.187088E+10 | 0.168290E+10 |
May | 0.178943E+10 | 0.594318E+09 | 0.119511E+10 | 0.176013E+10 | 0.135742E+10 |
June | 0.172062E+10 | 0.501815E+09 | 0.121881E+10 | 0.203386E+10 | 0.878733E+09 |
July | 0.191684E+10 | 0.708073E+09 | 0.120876E+10 | 0.262296E+10 | 0.700411E+09 |
August | 0.227803E+10 | 0.114854E+10 | 0.112949E+10 | 0.301134E+10 | 0.803386E+09 |
September | 0.244511E+10 | 0.149820E+10 | 0.946912E+09 | 0.293347E+10 | 0.110848E+10 |
October | 0.264144E+10 | 0.182652E+10 | 0.814917E+09 | 0.280349E+10 | 0.163253E+10 |
November | 0.233053E+10 | 0.168814E+10 | 0.642387E+09 | 0.215209E+10 | 0.208677E+10 |
December | 0.209310E+10 | 0.151143E+10 | 0.581671E+09 | 0.171289E+10 | 0.293249E+10 |
Annual Sum or Average | 0.264026E+11 | 0.152093E+11 | 0.111933E+11 | 0.272435E+11 | 0.211923E+11 |
Minimum of Months | 0.172062E+10 | 0.501815E+09 | 0.581671E+09 | 0.171289E+10 | 0.700411E+09 |
Maximum of Months | 0.264144E+10 | 0.182652E+10 | 0.121881E+10 | 0.301134E+10 | 0.340592E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.220108E+10 | 0.157205E+10 | 0.629023E+09 | 0.175316E+10 | 0.340592E+10 |
February | 0.253178E+10 | 0.182095E+10 | 0.710828E+09 | 0.231113E+10 | 0.230805E+10 |
March | 0.250555E+10 | 0.140700E+10 | 0.109855E+10 | 0.227807E+10 | 0.229523E+10 |
April | 0.194907E+10 | 0.932254E+09 | 0.101682E+10 | 0.187088E+10 | 0.168290E+10 |
May | 0.178943E+10 | 0.594317E+09 | 0.119511E+10 | 0.176013E+10 | 0.135742E+10 |
June | 0.172062E+10 | 0.501815E+09 | 0.121880E+10 | 0.203386E+10 | 0.878733E+09 |
July | 0.191683E+10 | 0.708072E+09 | 0.120876E+10 | 0.262295E+10 | 0.700411E+09 |
August | 0.227803E+10 | 0.114854E+10 | 0.112949E+10 | 0.301133E+10 | 0.803386E+09 |
September | 0.244511E+10 | 0.149820E+10 | 0.946911E+09 | 0.293347E+10 | 0.110848E+10 |
October | 0.264144E+10 | 0.182652E+10 | 0.814917E+09 | 0.280348E+10 | 0.163253E+10 |
November | 0.233052E+10 | 0.168814E+10 | 0.642386E+09 | 0.215209E+10 | 0.208677E+10 |
December | 0.209310E+10 | 0.151143E+10 | 0.581670E+09 | 0.171289E+10 | 0.293249E+10 |
Annual Sum or Average | 0.264025E+11 | 0.152093E+11 | 0.111933E+11 | 0.272434E+11 | 0.211923E+11 |
Minimum of Months | 0.172062E+10 | 0.501815E+09 | 0.581670E+09 | 0.171289E+10 | 0.700411E+09 |
Maximum of Months | 0.264144E+10 | 0.182652E+10 | 0.121880E+10 | 0.301133E+10 | 0.340592E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.220108E+10 | 0.157205E+10 | 0.629024E+09 | 0.175316E+10 | 0.340592E+10 |
February | 0.253178E+10 | 0.182095E+10 | 0.710829E+09 | 0.231113E+10 | 0.230805E+10 |
March | 0.250555E+10 | 0.140700E+10 | 0.109855E+10 | 0.227807E+10 | 0.229523E+10 |
April | 0.194907E+10 | 0.932255E+09 | 0.101682E+10 | 0.187088E+10 | 0.168290E+10 |
May | 0.178943E+10 | 0.594318E+09 | 0.119511E+10 | 0.176013E+10 | 0.135742E+10 |
June | 0.172062E+10 | 0.501815E+09 | 0.121881E+10 | 0.203386E+10 | 0.878733E+09 |
July | 0.191684E+10 | 0.708073E+09 | 0.120876E+10 | 0.262296E+10 | 0.700411E+09 |
August | 0.227803E+10 | 0.114854E+10 | 0.112949E+10 | 0.301134E+10 | 0.803386E+09 |
September | 0.244511E+10 | 0.149820E+10 | 0.946912E+09 | 0.293347E+10 | 0.110848E+10 |
October | 0.264144E+10 | 0.182652E+10 | 0.814917E+09 | 0.280349E+10 | 0.163253E+10 |
November | 0.233053E+10 | 0.168814E+10 | 0.642387E+09 | 0.215209E+10 | 0.208677E+10 |
December | 0.209310E+10 | 0.151143E+10 | 0.581671E+09 | 0.171289E+10 | 0.293249E+10 |
Annual Sum or Average | 0.264026E+11 | 0.152093E+11 | 0.111933E+11 | 0.272435E+11 | 0.211923E+11 |
Minimum of Months | 0.172062E+10 | 0.501815E+09 | 0.581671E+09 | 0.171289E+10 | 0.700411E+09 |
Maximum of Months | 0.264144E+10 | 0.182652E+10 | 0.121881E+10 | 0.301134E+10 | 0.340592E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.220108E+10 | 0.157205E+10 | 0.629023E+09 | 0.175316E+10 | 0.340592E+10 |
February | 0.253178E+10 | 0.182095E+10 | 0.710828E+09 | 0.231113E+10 | 0.230805E+10 |
March | 0.250555E+10 | 0.140700E+10 | 0.109855E+10 | 0.227807E+10 | 0.229523E+10 |
April | 0.194907E+10 | 0.932254E+09 | 0.101682E+10 | 0.187088E+10 | 0.168290E+10 |
May | 0.178943E+10 | 0.594317E+09 | 0.119511E+10 | 0.176013E+10 | 0.135742E+10 |
June | 0.172062E+10 | 0.501815E+09 | 0.121880E+10 | 0.203386E+10 | 0.878733E+09 |
July | 0.191683E+10 | 0.708072E+09 | 0.120876E+10 | 0.262295E+10 | 0.700411E+09 |
August | 0.227803E+10 | 0.114854E+10 | 0.112949E+10 | 0.301133E+10 | 0.803386E+09 |
September | 0.244511E+10 | 0.149820E+10 | 0.946911E+09 | 0.293347E+10 | 0.110848E+10 |
October | 0.264144E+10 | 0.182652E+10 | 0.814917E+09 | 0.280348E+10 | 0.163253E+10 |
November | 0.233052E+10 | 0.168814E+10 | 0.642386E+09 | 0.215209E+10 | 0.208677E+10 |
December | 0.209310E+10 | 0.151143E+10 | 0.581670E+09 | 0.171289E+10 | 0.293249E+10 |
Annual Sum or Average | 0.264025E+11 | 0.152093E+11 | 0.111933E+11 | 0.272434E+11 | 0.211923E+11 |
Minimum of Months | 0.172062E+10 | 0.501815E+09 | 0.581670E+09 | 0.171289E+10 | 0.700411E+09 |
Maximum of Months | 0.264144E+10 | 0.182652E+10 | 0.121880E+10 | 0.301133E+10 | 0.340592E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.220099E+10 | 0.157199E+10 | 0.628999E+09 | 0.175309E+10 | 0.340579E+10 |
February | 0.253168E+10 | 0.182088E+10 | 0.710800E+09 | 0.231104E+10 | 0.230796E+10 |
March | 0.250545E+10 | 0.140695E+10 | 0.109850E+10 | 0.227798E+10 | 0.229514E+10 |
April | 0.194900E+10 | 0.932217E+09 | 0.101678E+10 | 0.187080E+10 | 0.168283E+10 |
May | 0.178935E+10 | 0.594294E+09 | 0.119506E+10 | 0.176006E+10 | 0.135737E+10 |
June | 0.172055E+10 | 0.501795E+09 | 0.121876E+10 | 0.203378E+10 | 0.878697E+09 |
July | 0.191676E+10 | 0.708045E+09 | 0.120871E+10 | 0.262285E+10 | 0.700383E+09 |
August | 0.227794E+10 | 0.114850E+10 | 0.112944E+10 | 0.301122E+10 | 0.803354E+09 |
September | 0.244501E+10 | 0.149814E+10 | 0.946874E+09 | 0.293335E+10 | 0.110843E+10 |
October | 0.264133E+10 | 0.182645E+10 | 0.814885E+09 | 0.280337E+10 | 0.163246E+10 |
November | 0.233043E+10 | 0.168807E+10 | 0.642361E+09 | 0.215201E+10 | 0.208668E+10 |
December | 0.209302E+10 | 0.151137E+10 | 0.581647E+09 | 0.171283E+10 | 0.293237E+10 |
Annual Sum or Average | 0.264015E+11 | 0.152087E+11 | 0.111928E+11 | 0.272424E+11 | 0.211915E+11 |
Minimum of Months | 0.172055E+10 | 0.501795E+09 | 0.581647E+09 | 0.171283E+10 | 0.700383E+09 |
Maximum of Months | 0.264133E+10 | 0.182645E+10 | 0.121876E+10 | 0.301122E+10 | 0.340579E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.721633E+09 | 0.290824E+09 | 0.430810E+09 | 0.257113E+09 | 0.451045E+10 |
February | 0.111252E+10 | 0.546860E+09 | 0.565660E+09 | 0.674531E+09 | 0.302062E+10 |
March | 0.157630E+10 | 0.577581E+09 | 0.998720E+09 | 0.983836E+09 | 0.283998E+10 |
April | 0.199149E+10 | 0.882321E+09 | 0.110917E+10 | 0.164977E+10 | 0.209467E+10 |
May | 0.254544E+10 | 0.116086E+10 | 0.138458E+10 | 0.247931E+10 | 0.161533E+10 |
June | 0.268000E+10 | 0.123103E+10 | 0.144898E+10 | 0.306018E+10 | 0.104809E+10 |
July | 0.283688E+10 | 0.143352E+10 | 0.140336E+10 | 0.361887E+10 | 0.918568E+09 |
August | 0.240889E+10 | 0.118223E+10 | 0.122666E+10 | 0.292859E+10 | 0.104493E+10 |
September | 0.187529E+10 | 0.948072E+09 | 0.927221E+09 | 0.205366E+10 | 0.135041E+10 |
October | 0.138500E+10 | 0.688130E+09 | 0.696867E+09 | 0.115421E+10 | 0.205982E+10 |
November | 0.948819E+09 | 0.470695E+09 | 0.478124E+09 | 0.568598E+09 | 0.282619E+10 |
December | 0.659039E+09 | 0.278162E+09 | 0.380877E+09 | 0.224890E+09 | 0.401088E+10 |
Annual Sum or Average | 0.207413E+11 | 0.969028E+10 | 0.110510E+11 | 0.196536E+11 | 0.273399E+11 |
Minimum of Months | 0.659039E+09 | 0.278162E+09 | 0.380877E+09 | 0.224890E+09 | 0.918568E+09 |
Maximum of Months | 0.283688E+10 | 0.143352E+10 | 0.144898E+10 | 0.361887E+10 | 0.451045E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.721633E+09 | 0.290824E+09 | 0.430810E+09 | 0.257113E+09 | 0.451045E+10 |
February | 0.111252E+10 | 0.546860E+09 | 0.565660E+09 | 0.674531E+09 | 0.302062E+10 |
March | 0.157630E+10 | 0.577581E+09 | 0.998720E+09 | 0.983836E+09 | 0.283998E+10 |
April | 0.199149E+10 | 0.882321E+09 | 0.110917E+10 | 0.164977E+10 | 0.209467E+10 |
May | 0.254544E+10 | 0.116086E+10 | 0.138458E+10 | 0.247931E+10 | 0.161533E+10 |
June | 0.268000E+10 | 0.123103E+10 | 0.144898E+10 | 0.306018E+10 | 0.104809E+10 |
July | 0.283688E+10 | 0.143352E+10 | 0.140336E+10 | 0.361887E+10 | 0.918568E+09 |
August | 0.240889E+10 | 0.118223E+10 | 0.122666E+10 | 0.292859E+10 | 0.104493E+10 |
September | 0.187529E+10 | 0.948072E+09 | 0.927221E+09 | 0.205366E+10 | 0.135041E+10 |
October | 0.138500E+10 | 0.688130E+09 | 0.696867E+09 | 0.115421E+10 | 0.205982E+10 |
November | 0.948819E+09 | 0.470695E+09 | 0.478124E+09 | 0.568598E+09 | 0.282619E+10 |
December | 0.659039E+09 | 0.278162E+09 | 0.380877E+09 | 0.224890E+09 | 0.401088E+10 |
Annual Sum or Average | 0.207413E+11 | 0.969028E+10 | 0.110510E+11 | 0.196536E+11 | 0.273399E+11 |
Minimum of Months | 0.659039E+09 | 0.278162E+09 | 0.380877E+09 | 0.224890E+09 | 0.918568E+09 |
Maximum of Months | 0.283688E+10 | 0.143352E+10 | 0.144898E+10 | 0.361887E+10 | 0.451045E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.721620E+09 | 0.290818E+09 | 0.430802E+09 | 0.257108E+09 | 0.451037E+10 |
February | 0.111250E+10 | 0.546850E+09 | 0.565650E+09 | 0.674518E+09 | 0.302057E+10 |
March | 0.157627E+10 | 0.577570E+09 | 0.998702E+09 | 0.983818E+09 | 0.283993E+10 |
April | 0.199145E+10 | 0.882305E+09 | 0.110915E+10 | 0.164974E+10 | 0.209463E+10 |
May | 0.254539E+10 | 0.116083E+10 | 0.138456E+10 | 0.247927E+10 | 0.161530E+10 |
June | 0.267996E+10 | 0.123100E+10 | 0.144895E+10 | 0.306013E+10 | 0.104807E+10 |
July | 0.283683E+10 | 0.143349E+10 | 0.140334E+10 | 0.361880E+10 | 0.918552E+09 |
August | 0.240885E+10 | 0.118221E+10 | 0.122664E+10 | 0.292854E+10 | 0.104491E+10 |
September | 0.187526E+10 | 0.948055E+09 | 0.927204E+09 | 0.205362E+10 | 0.135038E+10 |
October | 0.138497E+10 | 0.688118E+09 | 0.696854E+09 | 0.115419E+10 | 0.205978E+10 |
November | 0.948802E+09 | 0.470687E+09 | 0.478115E+09 | 0.568587E+09 | 0.282614E+10 |
December | 0.659027E+09 | 0.278157E+09 | 0.380870E+09 | 0.224886E+09 | 0.401081E+10 |
Annual Sum or Average | 0.207409E+11 | 0.969010E+10 | 0.110508E+11 | 0.196532E+11 | 0.273394E+11 |
Minimum of Months | 0.659027E+09 | 0.278157E+09 | 0.380870E+09 | 0.224886E+09 | 0.918552E+09 |
Maximum of Months | 0.283683E+10 | 0.143349E+10 | 0.144895E+10 | 0.361880E+10 | 0.451037E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.156128E+10 | 0.00 | 0.156128E+10 | 6435986.61 | 0.197788E+11 |
February | 0.199109E+10 | 0.00 | 0.199109E+10 | 0.133067E+09 | 0.133693E+11 |
March | 0.358099E+10 | 0.00 | 0.358099E+10 | 0.556553E+09 | 0.118759E+11 |
April | 0.395137E+10 | 23059338.10 | 0.392832E+10 | 0.141226E+10 | 0.798794E+10 |
May | 0.536207E+10 | 0.317736E+09 | 0.504433E+10 | 0.316642E+10 | 0.607975E+10 |
June | 0.604242E+10 | 0.694525E+09 | 0.534789E+10 | 0.560626E+10 | 0.362624E+10 |
July | 0.570408E+10 | 0.534256E+09 | 0.516983E+10 | 0.680769E+10 | 0.300166E+10 |
August | 0.457071E+10 | 0.122516E+09 | 0.444819E+10 | 0.487855E+10 | 0.350869E+10 |
September | 0.331272E+10 | 1188784.23 | 0.331153E+10 | 0.262461E+10 | 0.521709E+10 |
October | 0.249699E+10 | 0.00 | 0.249699E+10 | 0.752122E+09 | 0.820955E+10 |
November | 0.164272E+10 | 0.00 | 0.164272E+10 | 0.104324E+09 | 0.117552E+11 |
December | 0.130922E+10 | 0.00 | 0.130922E+10 | 2143204.73 | 0.167786E+11 |
Annual Sum or Average | 0.415257E+11 | 0.169328E+10 | 0.398324E+11 | 0.260504E+11 | 0.111189E+12 |
Minimum of Months | 0.130922E+10 | 0.00 | 0.130922E+10 | 2143204.73 | 0.300166E+10 |
Maximum of Months | 0.604242E+10 | 0.694525E+09 | 0.534789E+10 | 0.680769E+10 | 0.197788E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239005E+10 | 0.109574E+10 | 0.129431E+10 | 0.917210E+09 | 0.120418E+11 |
February | 0.337649E+10 | 0.167634E+10 | 0.170014E+10 | 0.204106E+10 | 0.814782E+10 |
March | 0.502642E+10 | 0.207979E+10 | 0.294663E+10 | 0.327786E+10 | 0.735982E+10 |
April | 0.620634E+10 | 0.307582E+10 | 0.313052E+10 | 0.522672E+10 | 0.504529E+10 |
May | 0.708423E+10 | 0.315204E+10 | 0.393219E+10 | 0.659426E+10 | 0.402377E+10 |
June | 0.887383E+10 | 0.456646E+10 | 0.430736E+10 | 0.100789E+11 | 0.247764E+10 |
July | 0.962377E+10 | 0.544058E+10 | 0.418320E+10 | 0.121828E+11 | 0.200688E+10 |
August | 0.836349E+10 | 0.465988E+10 | 0.370361E+10 | 0.102407E+11 | 0.229683E+10 |
September | 0.572550E+10 | 0.295548E+10 | 0.277002E+10 | 0.611351E+10 | 0.327791E+10 |
October | 0.424467E+10 | 0.215538E+10 | 0.208929E+10 | 0.343909E+10 | 0.511938E+10 |
November | 0.260341E+10 | 0.121545E+10 | 0.138796E+10 | 0.138724E+10 | 0.714805E+10 |
December | 0.198417E+10 | 0.852206E+09 | 0.113196E+10 | 0.675290E+09 | 0.102424E+11 |
Annual Sum or Average | 0.655024E+11 | 0.329252E+11 | 0.325772E+11 | 0.621746E+11 | 0.691876E+11 |
Minimum of Months | 0.198417E+10 | 0.852206E+09 | 0.113196E+10 | 0.675290E+09 | 0.200688E+10 |
Maximum of Months | 0.962377E+10 | 0.544058E+10 | 0.430736E+10 | 0.121828E+11 | 0.120418E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110053E+11 | 0.786017E+10 | 0.314508E+10 | 0.866668E+10 | 0.168943E+11 |
February | 0.126587E+11 | 0.910464E+10 | 0.355410E+10 | 0.113470E+11 | 0.115255E+11 |
March | 0.125276E+11 | 0.703493E+10 | 0.549268E+10 | 0.111836E+11 | 0.114176E+11 |
April | 0.974526E+10 | 0.466122E+10 | 0.508404E+10 | 0.925233E+10 | 0.822602E+10 |
May | 0.894703E+10 | 0.297155E+10 | 0.597547E+10 | 0.868982E+10 | 0.665891E+10 |
June | 0.860300E+10 | 0.250905E+10 | 0.609396E+10 | 0.100907E+11 | 0.431754E+10 |
July | 0.958406E+10 | 0.354032E+10 | 0.604374E+10 | 0.130739E+11 | 0.341448E+10 |
August | 0.113900E+11 | 0.574265E+10 | 0.564738E+10 | 0.149691E+11 | 0.391574E+10 |
September | 0.122254E+11 | 0.749090E+10 | 0.473450E+10 | 0.144668E+11 | 0.547816E+10 |
October | 0.132070E+11 | 0.913249E+10 | 0.407454E+10 | 0.138161E+11 | 0.805672E+10 |
November | 0.116525E+11 | 0.844059E+10 | 0.321189E+10 | 0.106678E+11 | 0.102278E+11 |
December | 0.104654E+11 | 0.755706E+10 | 0.290832E+10 | 0.853690E+10 | 0.142797E+11 |
Annual Sum or Average | 0.132011E+12 | 0.760456E+11 | 0.559657E+11 | 0.134761E+12 | 0.104413E+12 |
Minimum of Months | 0.860300E+10 | 0.250905E+10 | 0.290832E+10 | 0.853690E+10 | 0.341448E+10 |
Maximum of Months | 0.132070E+11 | 0.913249E+10 | 0.609396E+10 | 0.149691E+11 | 0.168943E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216488E+10 | 0.872462E+09 | 0.129242E+10 | 0.809405E+09 | 0.128724E+11 |
February | 0.333753E+10 | 0.164056E+10 | 0.169696E+10 | 0.207793E+10 | 0.854622E+10 |
March | 0.472885E+10 | 0.173272E+10 | 0.299613E+10 | 0.302883E+10 | 0.795060E+10 |
April | 0.597440E+10 | 0.264694E+10 | 0.332746E+10 | 0.513888E+10 | 0.553031E+10 |
May | 0.763623E+10 | 0.348253E+10 | 0.415370E+10 | 0.750289E+10 | 0.449412E+10 |
June | 0.803993E+10 | 0.369304E+10 | 0.434689E+10 | 0.926701E+10 | 0.292447E+10 |
July | 0.851055E+10 | 0.430051E+10 | 0.421004E+10 | 0.110412E+11 | 0.246313E+10 |
August | 0.722660E+10 | 0.354667E+10 | 0.367994E+10 | 0.903385E+10 | 0.267059E+10 |
September | 0.562582E+10 | 0.284419E+10 | 0.278164E+10 | 0.625838E+10 | 0.370791E+10 |
October | 0.415495E+10 | 0.206437E+10 | 0.209058E+10 | 0.358291E+10 | 0.559242E+10 |
November | 0.284643E+10 | 0.141207E+10 | 0.143436E+10 | 0.182617E+10 | 0.762230E+10 |
December | 0.197710E+10 | 0.834477E+09 | 0.114262E+10 | 0.750997E+09 | 0.108274E+11 |
Annual Sum or Average | 0.622233E+11 | 0.290705E+11 | 0.331527E+11 | 0.603184E+11 | 0.752018E+11 |
Minimum of Months | 0.197710E+10 | 0.834477E+09 | 0.114262E+10 | 0.750997E+09 | 0.246313E+10 |
Maximum of Months | 0.851055E+10 | 0.430051E+10 | 0.434689E+10 | 0.110412E+11 | 0.128724E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.156128E+10 | 0.00 | 0.156128E+10 | 14777338.63 | 0.192566E+11 |
February | 0.199109E+10 | 0.00 | 0.199109E+10 | 0.190630E+09 | 0.127486E+11 |
March | 0.358099E+10 | 0.00 | 0.358099E+10 | 0.630987E+09 | 0.111544E+11 |
April | 0.395137E+10 | 23059338.10 | 0.392832E+10 | 0.154031E+10 | 0.726788E+10 |
May | 0.536207E+10 | 0.317736E+09 | 0.504433E+10 | 0.329516E+10 | 0.557395E+10 |
June | 0.604242E+10 | 0.694525E+09 | 0.534789E+10 | 0.576448E+10 | 0.336265E+10 |
July | 0.570408E+10 | 0.534256E+09 | 0.516983E+10 | 0.694043E+10 | 0.279715E+10 |
August | 0.457071E+10 | 0.122516E+09 | 0.444819E+10 | 0.499768E+10 | 0.322719E+10 |
September | 0.331272E+10 | 1188784.23 | 0.331153E+10 | 0.275662E+10 | 0.474098E+10 |
October | 0.249699E+10 | 0.00 | 0.249699E+10 | 0.906289E+09 | 0.732264E+10 |
November | 0.164272E+10 | 0.00 | 0.164272E+10 | 0.159646E+09 | 0.108970E+11 |
December | 0.130922E+10 | 0.00 | 0.130922E+10 | 2744071.20 | 0.160896E+11 |
Annual Sum or Average | 0.415257E+11 | 0.169328E+10 | 0.398324E+11 | 0.271997E+11 | 0.104439E+12 |
Minimum of Months | 0.130922E+10 | 0.00 | 0.130922E+10 | 2744071.20 | 0.279715E+10 |
Maximum of Months | 0.604242E+10 | 0.694525E+09 | 0.534789E+10 | 0.694043E+10 | 0.192566E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239005E+10 | 0.109574E+10 | 0.129431E+10 | 0.956544E+09 | 0.117425E+11 |
February | 0.337649E+10 | 0.167634E+10 | 0.170014E+10 | 0.215113E+10 | 0.775531E+10 |
March | 0.502642E+10 | 0.207979E+10 | 0.294663E+10 | 0.342194E+10 | 0.688529E+10 |
April | 0.620634E+10 | 0.307582E+10 | 0.313052E+10 | 0.537227E+10 | 0.460679E+10 |
May | 0.708423E+10 | 0.315204E+10 | 0.393219E+10 | 0.668688E+10 | 0.372756E+10 |
June | 0.887383E+10 | 0.456646E+10 | 0.430736E+10 | 0.101174E+11 | 0.235238E+10 |
July | 0.962377E+10 | 0.544058E+10 | 0.418320E+10 | 0.121879E+11 | 0.191717E+10 |
August | 0.836349E+10 | 0.465988E+10 | 0.370361E+10 | 0.102568E+11 | 0.217351E+10 |
September | 0.572550E+10 | 0.295548E+10 | 0.277002E+10 | 0.621077E+10 | 0.302035E+10 |
October | 0.424467E+10 | 0.215538E+10 | 0.208929E+10 | 0.364710E+10 | 0.455603E+10 |
November | 0.260341E+10 | 0.121545E+10 | 0.138796E+10 | 0.151895E+10 | 0.658555E+10 |
December | 0.198417E+10 | 0.852206E+09 | 0.113196E+10 | 0.716277E+09 | 0.982496E+10 |
Annual Sum or Average | 0.655024E+11 | 0.329252E+11 | 0.325772E+11 | 0.632439E+11 | 0.651474E+11 |
Minimum of Months | 0.198417E+10 | 0.852206E+09 | 0.113196E+10 | 0.716277E+09 | 0.191717E+10 |
Maximum of Months | 0.962377E+10 | 0.544058E+10 | 0.430736E+10 | 0.121879E+11 | 0.117425E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110053E+11 | 0.786017E+10 | 0.314508E+10 | 0.880380E+10 | 0.162877E+11 |
February | 0.126587E+11 | 0.910464E+10 | 0.355410E+10 | 0.115199E+11 | 0.108522E+11 |
March | 0.125276E+11 | 0.703493E+10 | 0.549268E+10 | 0.113204E+11 | 0.106638E+11 |
April | 0.974526E+10 | 0.466122E+10 | 0.508404E+10 | 0.939762E+10 | 0.749802E+10 |
May | 0.894703E+10 | 0.297155E+10 | 0.597547E+10 | 0.876196E+10 | 0.613091E+10 |
June | 0.860300E+10 | 0.250905E+10 | 0.609396E+10 | 0.101406E+11 | 0.402286E+10 |
July | 0.958406E+10 | 0.354032E+10 | 0.604374E+10 | 0.131068E+11 | 0.318394E+10 |
August | 0.113900E+11 | 0.574265E+10 | 0.564738E+10 | 0.149860E+11 | 0.363940E+10 |
September | 0.122254E+11 | 0.749090E+10 | 0.473450E+10 | 0.145498E+11 | 0.501406E+10 |
October | 0.132070E+11 | 0.913249E+10 | 0.407454E+10 | 0.140302E+11 | 0.720798E+10 |
November | 0.116525E+11 | 0.844059E+10 | 0.321189E+10 | 0.109399E+11 | 0.937475E+10 |
December | 0.104654E+11 | 0.755706E+10 | 0.290832E+10 | 0.870616E+10 | 0.135645E+11 |
Annual Sum or Average | 0.132011E+12 | 0.760456E+11 | 0.559657E+11 | 0.136263E+12 | 0.974402E+11 |
Minimum of Months | 0.860300E+10 | 0.250905E+10 | 0.290832E+10 | 0.870616E+10 | 0.318394E+10 |
Maximum of Months | 0.132070E+11 | 0.913249E+10 | 0.609396E+10 | 0.149860E+11 | 0.162877E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216488E+10 | 0.872462E+09 | 0.129242E+10 | 0.824482E+09 | 0.125490E+11 |
February | 0.333753E+10 | 0.164056E+10 | 0.169696E+10 | 0.210844E+10 | 0.817138E+10 |
March | 0.472885E+10 | 0.173272E+10 | 0.299613E+10 | 0.305361E+10 | 0.753136E+10 |
April | 0.597440E+10 | 0.264694E+10 | 0.332746E+10 | 0.517509E+10 | 0.512706E+10 |
May | 0.763623E+10 | 0.348253E+10 | 0.415370E+10 | 0.749509E+10 | 0.419837E+10 |
June | 0.803993E+10 | 0.369304E+10 | 0.434689E+10 | 0.924169E+10 | 0.277265E+10 |
July | 0.851055E+10 | 0.430051E+10 | 0.421004E+10 | 0.110137E+11 | 0.234830E+10 |
August | 0.722660E+10 | 0.354667E+10 | 0.367994E+10 | 0.901624E+10 | 0.253388E+10 |
September | 0.562582E+10 | 0.284419E+10 | 0.278164E+10 | 0.626550E+10 | 0.346435E+10 |
October | 0.415495E+10 | 0.206437E+10 | 0.209058E+10 | 0.364795E+10 | 0.511126E+10 |
November | 0.284643E+10 | 0.141207E+10 | 0.143436E+10 | 0.188110E+10 | 0.713801E+10 |
December | 0.197710E+10 | 0.834477E+09 | 0.114262E+10 | 0.768562E+09 | 0.104316E+11 |
Annual Sum or Average | 0.622233E+11 | 0.290705E+11 | 0.331527E+11 | 0.604915E+11 | 0.713773E+11 |
Minimum of Months | 0.197710E+10 | 0.834477E+09 | 0.114262E+10 | 0.768562E+09 | 0.234830E+10 |
Maximum of Months | 0.851055E+10 | 0.430051E+10 | 0.434689E+10 | 0.110137E+11 | 0.125490E+11 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.02 | 7687.62 | 582.92 | 0.00 | 582.92 | 0.00 | 0.00 |
February | 27.57 | 5785.84 | 823.04 | 0.00 | 823.04 | 0.00 | 0.00 |
March | 162.51 | 4692.70 | 1336.99 | 0.00 | 1336.99 | 0.00 | 0.00 |
April | 454.01 | 3380.98 | 1524.46 | 8.90 | 1515.56 | 0.00 | 0.00 |
May | 1098.42 | 2452.35 | 2001.97 | 118.63 | 1883.35 | 0.00 | 0.00 |
June | 2076.59 | 1491.07 | 2331.19 | 267.95 | 2063.24 | 0.00 | 0.00 |
July | 2441.43 | 1208.81 | 2129.67 | 199.47 | 1930.20 | 0.00 | 0.00 |
August | 1726.75 | 1445.49 | 1706.51 | 45.74 | 1660.77 | 0.00 | 0.00 |
September | 922.80 | 2211.00 | 1278.06 | 0.46 | 1277.60 | 0.00 | 0.00 |
October | 209.09 | 3395.00 | 932.27 | 0.00 | 932.27 | 0.00 | 0.00 |
November | 17.82 | 4971.02 | 633.77 | 0.00 | 633.77 | 0.00 | 0.00 |
December | 0.06 | 6726.68 | 488.81 | 0.00 | 488.81 | 0.00 | 0.00 |
Annual Sum or Average | 766.29 | 3779.43 | 1316.77 | 53.69 | 1263.08 | 0.00 | 0.00 |
Minimum of Months | 0.02 | 1208.81 | 488.81 | 0.00 | 488.81 | 0.00 | 0.00 |
Maximum of Months | 2441.43 | 7687.62 | 2331.19 | 267.95 | 2063.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 326.71 | 4676.79 | 892.35 | 409.10 | 483.24 | 0.00 | 0.00 |
February | 829.35 | 3481.73 | 1395.71 | 692.94 | 702.77 | 0.00 | 0.00 |
March | 1228.69 | 2851.97 | 1876.66 | 776.51 | 1100.15 | 0.00 | 0.00 |
April | 2029.67 | 2041.72 | 2394.43 | 1186.66 | 1207.77 | 0.00 | 0.00 |
May | 2485.98 | 1577.86 | 2644.96 | 1176.84 | 1468.12 | 0.00 | 0.00 |
June | 3926.67 | 986.16 | 3423.56 | 1761.76 | 1661.80 | 0.00 | 0.00 |
July | 4585.25 | 766.66 | 3593.12 | 2031.29 | 1561.83 | 0.00 | 0.00 |
August | 3857.65 | 874.75 | 3122.58 | 1739.81 | 1382.78 | 0.00 | 0.00 |
September | 2375.63 | 1326.69 | 2208.92 | 1140.24 | 1068.68 | 0.00 | 0.00 |
October | 1278.13 | 2038.48 | 1584.78 | 804.73 | 780.06 | 0.00 | 0.00 |
November | 512.59 | 2947.06 | 1004.41 | 468.93 | 535.48 | 0.00 | 0.00 |
December | 235.52 | 4056.83 | 740.81 | 318.18 | 422.63 | 0.00 | 0.00 |
Annual Sum or Average | 1979.44 | 2297.75 | 2077.07 | 1044.05 | 1033.02 | 0.00 | 0.00 |
Minimum of Months | 235.52 | 766.66 | 740.81 | 318.18 | 422.63 | 0.00 | 0.00 |
Maximum of Months | 4585.25 | 4676.79 | 3593.12 | 2031.29 | 1661.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3272.75 | 6358.08 | 4108.91 | 2934.66 | 1174.24 | 0.00 | 0.00 |
February | 4776.60 | 4770.25 | 5232.63 | 3763.50 | 1469.13 | 0.00 | 0.00 |
March | 4252.64 | 4284.67 | 4677.29 | 2626.55 | 2050.74 | 0.00 | 0.00 |
April | 3608.92 | 3246.30 | 3759.76 | 1798.32 | 1961.44 | 0.00 | 0.00 |
May | 3285.76 | 2534.00 | 3340.45 | 1109.45 | 2230.99 | 0.00 | 0.00 |
June | 3923.32 | 1695.07 | 3319.07 | 968.00 | 2351.07 | 0.00 | 0.00 |
July | 4896.46 | 1307.51 | 3578.29 | 1321.81 | 2256.48 | 0.00 | 0.00 |
August | 5621.48 | 1499.74 | 4252.57 | 2144.07 | 2108.50 | 0.00 | 0.00 |
September | 5658.65 | 2138.25 | 4716.61 | 2890.02 | 1826.59 | 0.00 | 0.00 |
October | 5233.47 | 3047.55 | 4930.96 | 3409.70 | 1521.26 | 0.00 | 0.00 |
November | 4151.38 | 4025.37 | 4495.57 | 3256.41 | 1239.16 | 0.00 | 0.00 |
December | 3197.58 | 5474.29 | 3907.34 | 2821.49 | 1085.85 | 0.00 | 0.00 |
Annual Sum or Average | 4319.39 | 3359.99 | 4186.07 | 2411.40 | 1774.67 | 0.00 | 0.00 |
Minimum of Months | 3197.58 | 1307.51 | 3319.07 | 968.00 | 1085.85 | 0.00 | 0.00 |
Maximum of Months | 5658.65 | 6358.08 | 5232.63 | 3763.50 | 2351.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 287.98 | 5051.99 | 808.28 | 325.74 | 482.53 | 0.00 | 0.00 |
February | 836.47 | 3745.79 | 1379.61 | 678.15 | 701.46 | 0.00 | 0.00 |
March | 1101.96 | 3180.96 | 1765.56 | 646.93 | 1118.63 | 0.00 | 0.00 |
April | 1909.44 | 2424.37 | 2304.95 | 1021.20 | 1283.75 | 0.00 | 0.00 |
May | 2776.99 | 1809.27 | 2851.06 | 1300.23 | 1550.82 | 0.00 | 0.00 |
June | 3541.86 | 1213.06 | 3101.84 | 1424.79 | 1677.05 | 0.00 | 0.00 |
July | 4053.36 | 1028.86 | 3177.49 | 1605.63 | 1571.86 | 0.00 | 0.00 |
August | 3280.21 | 1170.39 | 2698.12 | 1324.18 | 1373.94 | 0.00 | 0.00 |
September | 2376.90 | 1562.96 | 2170.47 | 1097.30 | 1073.17 | 0.00 | 0.00 |
October | 1292.79 | 2307.13 | 1551.29 | 770.75 | 780.54 | 0.00 | 0.00 |
November | 658.09 | 3271.03 | 1098.16 | 544.78 | 553.38 | 0.00 | 0.00 |
December | 251.89 | 4492.45 | 738.17 | 311.56 | 426.61 | 0.00 | 0.00 |
Annual Sum or Average | 1869.62 | 2600.81 | 1973.10 | 921.82 | 1051.27 | 0.00 | 0.00 |
Minimum of Months | 251.89 | 1028.86 | 738.17 | 311.56 | 426.61 | 0.00 | 0.00 |
Maximum of Months | 4053.36 | 5051.99 | 3177.49 | 1605.63 | 1677.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.40 | 7384.57 | 582.91 | 0.00 | 582.91 | 0.00 | 0.00 |
February | 55.00 | 5526.33 | 823.04 | 0.00 | 823.04 | 0.00 | 0.00 |
March | 207.79 | 4433.96 | 1336.99 | 0.00 | 1336.99 | 0.00 | 0.00 |
April | 544.85 | 3081.77 | 1524.45 | 8.90 | 1515.55 | 0.00 | 0.00 |
May | 1182.20 | 2269.92 | 2001.97 | 118.63 | 1883.34 | 0.00 | 0.00 |
June | 2162.91 | 1399.01 | 2331.18 | 267.95 | 2063.23 | 0.00 | 0.00 |
July | 2541.70 | 1120.69 | 2129.66 | 199.47 | 1930.19 | 0.00 | 0.00 |
August | 1821.44 | 1310.00 | 1706.51 | 45.74 | 1660.77 | 0.00 | 0.00 |
September | 1012.58 | 2012.77 | 1278.06 | 0.46 | 1277.60 | 0.00 | 0.00 |
October | 280.81 | 3065.10 | 932.27 | 0.00 | 932.27 | 0.00 | 0.00 |
November | 40.25 | 4535.17 | 633.76 | 0.00 | 633.76 | 0.00 | 0.00 |
December | 0.80 | 6264.42 | 488.81 | 0.00 | 488.81 | 0.00 | 0.00 |
Annual Sum or Average | 826.05 | 3525.77 | 1316.77 | 53.69 | 1263.08 | 0.00 | 0.00 |
Minimum of Months | 0.80 | 1120.69 | 488.81 | 0.00 | 488.81 | 0.00 | 0.00 |
Maximum of Months | 2541.70 | 7384.57 | 2331.18 | 267.95 | 2063.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 342.45 | 4495.89 | 892.34 | 409.10 | 483.24 | 0.00 | 0.00 |
February | 843.69 | 3367.98 | 1395.70 | 692.93 | 702.77 | 0.00 | 0.00 |
March | 1223.81 | 2747.84 | 1876.65 | 776.51 | 1100.14 | 0.00 | 0.00 |
April | 2016.48 | 1946.49 | 2394.42 | 1186.66 | 1207.76 | 0.00 | 0.00 |
May | 2462.02 | 1502.30 | 2644.95 | 1176.84 | 1468.11 | 0.00 | 0.00 |
June | 3888.45 | 955.88 | 3423.54 | 1761.75 | 1661.79 | 0.00 | 0.00 |
July | 4548.55 | 749.28 | 3593.11 | 2031.28 | 1561.83 | 0.00 | 0.00 |
August | 3823.42 | 857.54 | 3122.57 | 1739.80 | 1382.77 | 0.00 | 0.00 |
September | 2358.61 | 1264.63 | 2208.91 | 1140.23 | 1068.68 | 0.00 | 0.00 |
October | 1284.01 | 1911.36 | 1584.78 | 804.73 | 780.05 | 0.00 | 0.00 |
November | 535.20 | 2757.73 | 1004.40 | 468.92 | 535.48 | 0.00 | 0.00 |
December | 252.12 | 3824.08 | 740.80 | 318.18 | 422.63 | 0.00 | 0.00 |
Annual Sum or Average | 1971.54 | 2193.92 | 2077.07 | 1044.05 | 1033.02 | 0.00 | 0.00 |
Minimum of Months | 252.12 | 749.28 | 740.80 | 318.18 | 422.63 | 0.00 | 0.00 |
Maximum of Months | 4548.55 | 4495.89 | 3593.11 | 2031.28 | 1661.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3235.77 | 6307.62 | 4108.89 | 2934.65 | 1174.24 | 0.00 | 0.00 |
February | 4690.38 | 4764.19 | 5232.61 | 3763.49 | 1469.12 | 0.00 | 0.00 |
March | 4175.48 | 4262.85 | 4677.27 | 2626.54 | 2050.73 | 0.00 | 0.00 |
April | 3569.57 | 3173.62 | 3759.74 | 1798.31 | 1961.43 | 0.00 | 0.00 |
May | 3244.41 | 2486.15 | 3340.44 | 1109.45 | 2230.99 | 0.00 | 0.00 |
June | 3893.03 | 1665.72 | 3319.06 | 968.00 | 2351.06 | 0.00 | 0.00 |
July | 4881.24 | 1274.82 | 3578.28 | 1321.81 | 2256.47 | 0.00 | 0.00 |
August | 5588.81 | 1461.97 | 4252.55 | 2144.06 | 2108.49 | 0.00 | 0.00 |
September | 5581.33 | 2113.49 | 4716.59 | 2890.01 | 1826.58 | 0.00 | 0.00 |
October | 5158.32 | 3008.03 | 4930.94 | 3409.68 | 1521.26 | 0.00 | 0.00 |
November | 4115.68 | 3945.92 | 4495.56 | 3256.40 | 1239.16 | 0.00 | 0.00 |
December | 3187.31 | 5331.42 | 3907.33 | 2821.48 | 1085.84 | 0.00 | 0.00 |
Annual Sum or Average | 4273.23 | 3310.90 | 4186.05 | 2411.39 | 1774.66 | 0.00 | 0.00 |
Minimum of Months | 3187.31 | 1274.82 | 3319.06 | 968.00 | 1085.84 | 0.00 | 0.00 |
Maximum of Months | 5588.81 | 6307.62 | 5232.61 | 3763.49 | 2351.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 302.20 | 4805.99 | 808.27 | 325.74 | 482.53 | 0.00 | 0.00 |
February | 858.93 | 3532.66 | 1379.60 | 678.14 | 701.46 | 0.00 | 0.00 |
March | 1130.83 | 2968.41 | 1765.55 | 646.93 | 1118.63 | 0.00 | 0.00 |
April | 1982.59 | 2133.61 | 2304.94 | 1021.19 | 1283.74 | 0.00 | 0.00 |
May | 2801.26 | 1677.91 | 2851.04 | 1300.23 | 1550.82 | 0.00 | 0.00 |
June | 3575.24 | 1128.27 | 3101.83 | 1424.78 | 1677.04 | 0.00 | 0.00 |
July | 4122.30 | 919.63 | 3177.48 | 1605.63 | 1571.85 | 0.00 | 0.00 |
August | 3372.85 | 997.08 | 2698.11 | 1324.17 | 1373.93 | 0.00 | 0.00 |
September | 2414.50 | 1430.52 | 2170.46 | 1097.29 | 1073.16 | 0.00 | 0.00 |
October | 1337.71 | 2087.97 | 1551.28 | 770.75 | 780.53 | 0.00 | 0.00 |
November | 704.54 | 2940.70 | 1098.16 | 544.78 | 553.38 | 0.00 | 0.00 |
December | 280.39 | 4042.48 | 738.16 | 311.56 | 426.61 | 0.00 | 0.00 |
Annual Sum or Average | 1912.68 | 2384.63 | 1973.09 | 921.82 | 1051.27 | 0.00 | 0.00 |
Minimum of Months | 280.39 | 919.63 | 738.16 | 311.56 | 426.61 | 0.00 | 0.00 |
Maximum of Months | 4122.30 | 4805.99 | 3177.48 | 1605.63 | 1677.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.52 | 7189.60 | 582.91 | 0.00 | 582.91 | 0.00 | 0.00 |
February | 78.80 | 5269.75 | 823.04 | 0.00 | 823.04 | 0.00 | 0.00 |
March | 235.58 | 4164.58 | 1336.99 | 0.00 | 1336.99 | 0.00 | 0.00 |
April | 594.26 | 2803.97 | 1524.45 | 8.90 | 1515.55 | 0.00 | 0.00 |
May | 1230.27 | 2081.07 | 2001.97 | 118.63 | 1883.34 | 0.00 | 0.00 |
June | 2223.95 | 1297.32 | 2331.18 | 267.95 | 2063.23 | 0.00 | 0.00 |
July | 2591.26 | 1044.33 | 2129.66 | 199.47 | 1930.19 | 0.00 | 0.00 |
August | 1865.92 | 1204.90 | 1706.51 | 45.74 | 1660.77 | 0.00 | 0.00 |
September | 1063.51 | 1829.08 | 1278.06 | 0.46 | 1277.60 | 0.00 | 0.00 |
October | 338.37 | 2733.96 | 932.27 | 0.00 | 932.27 | 0.00 | 0.00 |
November | 61.59 | 4204.08 | 633.76 | 0.00 | 633.76 | 0.00 | 0.00 |
December | 1.02 | 6007.18 | 488.81 | 0.00 | 488.81 | 0.00 | 0.00 |
Annual Sum or Average | 862.50 | 3311.73 | 1316.77 | 53.69 | 1263.08 | 0.00 | 0.00 |
Minimum of Months | 1.02 | 1044.33 | 488.81 | 0.00 | 488.81 | 0.00 | 0.00 |
Maximum of Months | 2591.26 | 7189.60 | 2331.18 | 267.95 | 2063.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 357.13 | 4384.16 | 892.34 | 409.10 | 483.24 | 0.00 | 0.00 |
February | 889.19 | 3205.73 | 1395.70 | 692.93 | 702.77 | 0.00 | 0.00 |
March | 1277.61 | 2570.67 | 1876.65 | 776.51 | 1100.14 | 0.00 | 0.00 |
April | 2072.64 | 1777.31 | 2394.42 | 1186.66 | 1207.76 | 0.00 | 0.00 |
May | 2496.59 | 1391.71 | 2644.95 | 1176.84 | 1468.11 | 0.00 | 0.00 |
June | 3903.32 | 907.56 | 3423.54 | 1761.75 | 1661.79 | 0.00 | 0.00 |
July | 4550.43 | 715.79 | 3593.11 | 2031.28 | 1561.83 | 0.00 | 0.00 |
August | 3829.44 | 811.50 | 3122.57 | 1739.80 | 1382.77 | 0.00 | 0.00 |
September | 2396.13 | 1165.26 | 2208.91 | 1140.23 | 1068.68 | 0.00 | 0.00 |
October | 1361.67 | 1701.03 | 1584.78 | 804.73 | 780.05 | 0.00 | 0.00 |
November | 586.01 | 2540.72 | 1004.40 | 468.92 | 535.48 | 0.00 | 0.00 |
December | 267.43 | 3668.22 | 740.80 | 318.18 | 422.63 | 0.00 | 0.00 |
Annual Sum or Average | 2005.45 | 2065.81 | 2077.07 | 1044.05 | 1033.02 | 0.00 | 0.00 |
Minimum of Months | 267.43 | 715.79 | 740.80 | 318.18 | 422.63 | 0.00 | 0.00 |
Maximum of Months | 4550.43 | 4384.16 | 3593.11 | 2031.28 | 1661.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3286.96 | 6081.14 | 4108.89 | 2934.65 | 1174.24 | 0.00 | 0.00 |
February | 4761.87 | 4485.87 | 5232.61 | 3763.49 | 1469.12 | 0.00 | 0.00 |
March | 4226.56 | 3981.39 | 4677.27 | 2626.54 | 2050.73 | 0.00 | 0.00 |
April | 3625.63 | 2892.76 | 3759.74 | 1798.31 | 1961.43 | 0.00 | 0.00 |
May | 3271.34 | 2289.02 | 3340.44 | 1109.45 | 2230.99 | 0.00 | 0.00 |
June | 3912.28 | 1552.03 | 3319.06 | 968.00 | 2351.06 | 0.00 | 0.00 |
July | 4893.53 | 1188.75 | 3578.28 | 1321.81 | 2256.47 | 0.00 | 0.00 |
August | 5595.12 | 1358.80 | 4252.55 | 2144.06 | 2108.49 | 0.00 | 0.00 |
September | 5613.35 | 1934.44 | 4716.59 | 2890.01 | 1826.58 | 0.00 | 0.00 |
October | 5238.28 | 2691.15 | 4930.94 | 3409.68 | 1521.26 | 0.00 | 0.00 |
November | 4220.65 | 3616.80 | 4495.56 | 3256.40 | 1239.16 | 0.00 | 0.00 |
December | 3250.51 | 5064.42 | 3907.33 | 2821.48 | 1085.84 | 0.00 | 0.00 |
Annual Sum or Average | 4320.88 | 3089.81 | 4186.05 | 2411.39 | 1774.66 | 0.00 | 0.00 |
Minimum of Months | 3250.51 | 1188.75 | 3319.06 | 968.00 | 1085.84 | 0.00 | 0.00 |
Maximum of Months | 5613.35 | 6081.14 | 5232.61 | 3763.49 | 2351.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 307.83 | 4685.28 | 808.27 | 325.74 | 482.53 | 0.00 | 0.00 |
February | 871.54 | 3377.72 | 1379.60 | 678.14 | 701.46 | 0.00 | 0.00 |
March | 1140.09 | 2811.89 | 1765.55 | 646.93 | 1118.63 | 0.00 | 0.00 |
April | 1996.56 | 1978.03 | 2304.94 | 1021.19 | 1283.74 | 0.00 | 0.00 |
May | 2798.35 | 1567.49 | 2851.04 | 1300.23 | 1550.82 | 0.00 | 0.00 |
June | 3565.47 | 1069.70 | 3101.83 | 1424.78 | 1677.04 | 0.00 | 0.00 |
July | 4112.05 | 876.76 | 3177.48 | 1605.63 | 1571.85 | 0.00 | 0.00 |
August | 3366.28 | 946.04 | 2698.11 | 1324.17 | 1373.93 | 0.00 | 0.00 |
September | 2417.24 | 1336.55 | 2170.46 | 1097.29 | 1073.16 | 0.00 | 0.00 |
October | 1361.99 | 1908.33 | 1551.28 | 770.75 | 780.53 | 0.00 | 0.00 |
November | 725.73 | 2753.86 | 1098.16 | 544.78 | 553.38 | 0.00 | 0.00 |
December | 286.95 | 3894.72 | 738.16 | 311.56 | 426.61 | 0.00 | 0.00 |
Annual Sum or Average | 1918.17 | 2263.36 | 1973.09 | 921.82 | 1051.27 | 0.00 | 0.00 |
Minimum of Months | 286.95 | 876.76 | 738.16 | 311.56 | 426.61 | 0.00 | 0.00 |
Maximum of Months | 4112.05 | 4685.28 | 3177.48 | 1605.63 | 1677.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 46657.95 | 0.205905E+11 | 0.156128E+10 | 0.00 | 0.156128E+10 | 0.00 | 0.00 |
February | 66702712.13 | 0.139971E+11 | 0.199110E+10 | 0.00 | 0.199110E+10 | 0.00 | 0.00 |
March | 0.435267E+09 | 0.125689E+11 | 0.358100E+10 | 0.00 | 0.358100E+10 | 0.00 | 0.00 |
April | 0.117679E+10 | 0.876350E+10 | 0.395139E+10 | 23059419.99 | 0.392833E+10 | 0.00 | 0.00 |
May | 0.294202E+10 | 0.656838E+10 | 0.536209E+10 | 0.317737E+09 | 0.504435E+10 | 0.00 | 0.00 |
June | 0.538253E+10 | 0.386485E+10 | 0.604244E+10 | 0.694527E+09 | 0.534791E+10 | 0.00 | 0.00 |
July | 0.653912E+10 | 0.323767E+10 | 0.570410E+10 | 0.534258E+09 | 0.516985E+10 | 0.00 | 0.00 |
August | 0.462492E+10 | 0.387159E+10 | 0.457073E+10 | 0.122517E+09 | 0.444821E+10 | 0.00 | 0.00 |
September | 0.239191E+10 | 0.573091E+10 | 0.331273E+10 | 1188788.45 | 0.331155E+10 | 0.00 | 0.00 |
October | 0.560019E+09 | 0.909318E+10 | 0.249700E+10 | 0.00 | 0.249700E+10 | 0.00 | 0.00 |
November | 46192877.21 | 0.128849E+11 | 0.164272E+10 | 0.00 | 0.164272E+10 | 0.00 | 0.00 |
December | 160923.40 | 0.180167E+11 | 0.130922E+10 | 0.00 | 0.130922E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241657E+11 | 0.119188E+12 | 0.415258E+11 | 0.169329E+10 | 0.398325E+11 | 0.00 | 0.00 |
Minimum of Months | 46657.95 | 0.323767E+10 | 0.130922E+10 | 0.00 | 0.130922E+10 | 0.00 | 0.00 |
Maximum of Months | 0.653912E+10 | 0.205905E+11 | 0.604244E+10 | 0.694527E+09 | 0.534791E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.875056E+09 | 0.125263E+11 | 0.239006E+10 | 0.109575E+10 | 0.129431E+10 | 0.00 | 0.00 |
February | 0.200637E+10 | 0.842299E+10 | 0.337650E+10 | 0.167635E+10 | 0.170015E+10 | 0.00 | 0.00 |
March | 0.329092E+10 | 0.763872E+10 | 0.502644E+10 | 0.207980E+10 | 0.294664E+10 | 0.00 | 0.00 |
April | 0.526092E+10 | 0.529214E+10 | 0.620636E+10 | 0.307583E+10 | 0.313054E+10 | 0.00 | 0.00 |
May | 0.665845E+10 | 0.422613E+10 | 0.708426E+10 | 0.315205E+10 | 0.393221E+10 | 0.00 | 0.00 |
June | 0.101779E+11 | 0.255612E+10 | 0.887386E+10 | 0.456648E+10 | 0.430738E+10 | 0.00 | 0.00 |
July | 0.122811E+11 | 0.205342E+10 | 0.962381E+10 | 0.544060E+10 | 0.418321E+10 | 0.00 | 0.00 |
August | 0.103323E+11 | 0.234292E+10 | 0.836352E+10 | 0.465989E+10 | 0.370363E+10 | 0.00 | 0.00 |
September | 0.615764E+10 | 0.343878E+10 | 0.572552E+10 | 0.295549E+10 | 0.277003E+10 | 0.00 | 0.00 |
October | 0.342335E+10 | 0.545987E+10 | 0.424469E+10 | 0.215539E+10 | 0.208930E+10 | 0.00 | 0.00 |
November | 0.132864E+10 | 0.763879E+10 | 0.260342E+10 | 0.121545E+10 | 0.138796E+10 | 0.00 | 0.00 |
December | 0.630816E+09 | 0.108658E+11 | 0.198418E+10 | 0.852209E+09 | 0.113197E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.624236E+11 | 0.724620E+11 | 0.655026E+11 | 0.329253E+11 | 0.325773E+11 | 0.00 | 0.00 |
Minimum of Months | 0.630816E+09 | 0.205342E+10 | 0.198418E+10 | 0.852209E+09 | 0.113197E+10 | 0.00 | 0.00 |
Maximum of Months | 0.122811E+11 | 0.125263E+11 | 0.962381E+10 | 0.544060E+10 | 0.430738E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.876574E+10 | 0.170295E+11 | 0.110053E+11 | 0.786020E+10 | 0.314509E+10 | 0.00 | 0.00 |
February | 0.115556E+11 | 0.115402E+11 | 0.126588E+11 | 0.910467E+10 | 0.355411E+10 | 0.00 | 0.00 |
March | 0.113903E+11 | 0.114761E+11 | 0.125277E+11 | 0.703495E+10 | 0.549270E+10 | 0.00 | 0.00 |
April | 0.935431E+10 | 0.841441E+10 | 0.974529E+10 | 0.466123E+10 | 0.508406E+10 | 0.00 | 0.00 |
May | 0.880057E+10 | 0.678706E+10 | 0.894706E+10 | 0.297156E+10 | 0.597550E+10 | 0.00 | 0.00 |
June | 0.101692E+11 | 0.439363E+10 | 0.860303E+10 | 0.250905E+10 | 0.609398E+10 | 0.00 | 0.00 |
July | 0.131147E+11 | 0.350203E+10 | 0.958410E+10 | 0.354034E+10 | 0.604376E+10 | 0.00 | 0.00 |
August | 0.150566E+11 | 0.401690E+10 | 0.113901E+11 | 0.574267E+10 | 0.564740E+10 | 0.00 | 0.00 |
September | 0.146672E+11 | 0.554235E+10 | 0.122254E+11 | 0.749092E+10 | 0.473452E+10 | 0.00 | 0.00 |
October | 0.140173E+11 | 0.816256E+10 | 0.132071E+11 | 0.913253E+10 | 0.407455E+10 | 0.00 | 0.00 |
November | 0.107604E+11 | 0.104338E+11 | 0.116525E+11 | 0.844062E+10 | 0.321191E+10 | 0.00 | 0.00 |
December | 0.856440E+10 | 0.146623E+11 | 0.104654E+11 | 0.755709E+10 | 0.290833E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.136216E+12 | 0.105961E+12 | 0.132012E+12 | 0.760458E+11 | 0.559659E+11 | 0.00 | 0.00 |
Minimum of Months | 0.856440E+10 | 0.350203E+10 | 0.860303E+10 | 0.250905E+10 | 0.290833E+10 | 0.00 | 0.00 |
Maximum of Months | 0.150566E+11 | 0.170295E+11 | 0.132071E+11 | 0.913253E+10 | 0.609398E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.771335E+09 | 0.135313E+11 | 0.216489E+10 | 0.872466E+09 | 0.129242E+10 | 0.00 | 0.00 |
February | 0.202358E+10 | 0.906181E+10 | 0.333754E+10 | 0.164057E+10 | 0.169697E+10 | 0.00 | 0.00 |
March | 0.295149E+10 | 0.851988E+10 | 0.472887E+10 | 0.173273E+10 | 0.299614E+10 | 0.00 | 0.00 |
April | 0.494927E+10 | 0.628396E+10 | 0.597442E+10 | 0.264695E+10 | 0.332748E+10 | 0.00 | 0.00 |
May | 0.743789E+10 | 0.484596E+10 | 0.763627E+10 | 0.348255E+10 | 0.415372E+10 | 0.00 | 0.00 |
June | 0.918049E+10 | 0.314425E+10 | 0.803997E+10 | 0.369306E+10 | 0.434691E+10 | 0.00 | 0.00 |
July | 0.108565E+11 | 0.275569E+10 | 0.851059E+10 | 0.430052E+10 | 0.421006E+10 | 0.00 | 0.00 |
August | 0.878572E+10 | 0.313478E+10 | 0.722663E+10 | 0.354668E+10 | 0.367995E+10 | 0.00 | 0.00 |
September | 0.616094E+10 | 0.405119E+10 | 0.562585E+10 | 0.284420E+10 | 0.278165E+10 | 0.00 | 0.00 |
October | 0.346261E+10 | 0.617941E+10 | 0.415497E+10 | 0.206438E+10 | 0.209059E+10 | 0.00 | 0.00 |
November | 0.170578E+10 | 0.847852E+10 | 0.284644E+10 | 0.141208E+10 | 0.143436E+10 | 0.00 | 0.00 |
December | 0.674667E+09 | 0.120326E+11 | 0.197710E+10 | 0.834480E+09 | 0.114262E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.589603E+11 | 0.820193E+11 | 0.622235E+11 | 0.290707E+11 | 0.331529E+11 | 0.00 | 0.00 |
Minimum of Months | 0.674667E+09 | 0.275569E+10 | 0.197710E+10 | 0.834480E+09 | 0.114262E+10 | 0.00 | 0.00 |
Maximum of Months | 0.108565E+11 | 0.135313E+11 | 0.851059E+10 | 0.430052E+10 | 0.434691E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 6435986.61 | 0.197788E+11 | 0.156128E+10 | 0.00 | 0.156128E+10 | 0.00 | 0.00 |
February | 0.133067E+09 | 0.133693E+11 | 0.199109E+10 | 0.00 | 0.199109E+10 | 0.00 | 0.00 |
March | 0.556553E+09 | 0.118759E+11 | 0.358099E+10 | 0.00 | 0.358099E+10 | 0.00 | 0.00 |
April | 0.141226E+10 | 0.798794E+10 | 0.395137E+10 | 23059338.10 | 0.392832E+10 | 0.00 | 0.00 |
May | 0.316642E+10 | 0.607975E+10 | 0.536207E+10 | 0.317736E+09 | 0.504433E+10 | 0.00 | 0.00 |
June | 0.560626E+10 | 0.362624E+10 | 0.604242E+10 | 0.694525E+09 | 0.534789E+10 | 0.00 | 0.00 |
July | 0.680769E+10 | 0.300166E+10 | 0.570408E+10 | 0.534256E+09 | 0.516983E+10 | 0.00 | 0.00 |
August | 0.487855E+10 | 0.350869E+10 | 0.457071E+10 | 0.122516E+09 | 0.444819E+10 | 0.00 | 0.00 |
September | 0.262461E+10 | 0.521709E+10 | 0.331272E+10 | 1188784.23 | 0.331153E+10 | 0.00 | 0.00 |
October | 0.752122E+09 | 0.820955E+10 | 0.249699E+10 | 0.00 | 0.249699E+10 | 0.00 | 0.00 |
November | 0.104324E+09 | 0.117552E+11 | 0.164272E+10 | 0.00 | 0.164272E+10 | 0.00 | 0.00 |
December | 2143204.73 | 0.167786E+11 | 0.130922E+10 | 0.00 | 0.130922E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.260504E+11 | 0.111189E+12 | 0.415257E+11 | 0.169328E+10 | 0.398324E+11 | 0.00 | 0.00 |
Minimum of Months | 2143204.73 | 0.300166E+10 | 0.130922E+10 | 0.00 | 0.130922E+10 | 0.00 | 0.00 |
Maximum of Months | 0.680769E+10 | 0.197788E+11 | 0.604242E+10 | 0.694525E+09 | 0.534789E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.917210E+09 | 0.120418E+11 | 0.239005E+10 | 0.109574E+10 | 0.129431E+10 | 0.00 | 0.00 |
February | 0.204106E+10 | 0.814782E+10 | 0.337649E+10 | 0.167634E+10 | 0.170014E+10 | 0.00 | 0.00 |
March | 0.327786E+10 | 0.735982E+10 | 0.502642E+10 | 0.207979E+10 | 0.294663E+10 | 0.00 | 0.00 |
April | 0.522672E+10 | 0.504529E+10 | 0.620634E+10 | 0.307582E+10 | 0.313052E+10 | 0.00 | 0.00 |
May | 0.659426E+10 | 0.402377E+10 | 0.708423E+10 | 0.315204E+10 | 0.393219E+10 | 0.00 | 0.00 |
June | 0.100789E+11 | 0.247764E+10 | 0.887383E+10 | 0.456646E+10 | 0.430736E+10 | 0.00 | 0.00 |
July | 0.121828E+11 | 0.200688E+10 | 0.962377E+10 | 0.544058E+10 | 0.418320E+10 | 0.00 | 0.00 |
August | 0.102407E+11 | 0.229683E+10 | 0.836349E+10 | 0.465988E+10 | 0.370361E+10 | 0.00 | 0.00 |
September | 0.611351E+10 | 0.327791E+10 | 0.572550E+10 | 0.295548E+10 | 0.277002E+10 | 0.00 | 0.00 |
October | 0.343909E+10 | 0.511938E+10 | 0.424467E+10 | 0.215538E+10 | 0.208929E+10 | 0.00 | 0.00 |
November | 0.138724E+10 | 0.714805E+10 | 0.260341E+10 | 0.121545E+10 | 0.138796E+10 | 0.00 | 0.00 |
December | 0.675290E+09 | 0.102424E+11 | 0.198417E+10 | 0.852206E+09 | 0.113196E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.621746E+11 | 0.691876E+11 | 0.655024E+11 | 0.329252E+11 | 0.325772E+11 | 0.00 | 0.00 |
Minimum of Months | 0.675290E+09 | 0.200688E+10 | 0.198417E+10 | 0.852206E+09 | 0.113196E+10 | 0.00 | 0.00 |
Maximum of Months | 0.121828E+11 | 0.120418E+11 | 0.962377E+10 | 0.544058E+10 | 0.430736E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.866668E+10 | 0.168943E+11 | 0.110053E+11 | 0.786017E+10 | 0.314508E+10 | 0.00 | 0.00 |
February | 0.113470E+11 | 0.115255E+11 | 0.126587E+11 | 0.910464E+10 | 0.355410E+10 | 0.00 | 0.00 |
March | 0.111836E+11 | 0.114176E+11 | 0.125276E+11 | 0.703493E+10 | 0.549268E+10 | 0.00 | 0.00 |
April | 0.925233E+10 | 0.822602E+10 | 0.974526E+10 | 0.466122E+10 | 0.508404E+10 | 0.00 | 0.00 |
May | 0.868982E+10 | 0.665891E+10 | 0.894703E+10 | 0.297155E+10 | 0.597547E+10 | 0.00 | 0.00 |
June | 0.100907E+11 | 0.431754E+10 | 0.860300E+10 | 0.250905E+10 | 0.609396E+10 | 0.00 | 0.00 |
July | 0.130739E+11 | 0.341448E+10 | 0.958406E+10 | 0.354032E+10 | 0.604374E+10 | 0.00 | 0.00 |
August | 0.149691E+11 | 0.391574E+10 | 0.113900E+11 | 0.574265E+10 | 0.564738E+10 | 0.00 | 0.00 |
September | 0.144668E+11 | 0.547816E+10 | 0.122254E+11 | 0.749090E+10 | 0.473450E+10 | 0.00 | 0.00 |
October | 0.138161E+11 | 0.805672E+10 | 0.132070E+11 | 0.913249E+10 | 0.407454E+10 | 0.00 | 0.00 |
November | 0.106678E+11 | 0.102278E+11 | 0.116525E+11 | 0.844059E+10 | 0.321189E+10 | 0.00 | 0.00 |
December | 0.853690E+10 | 0.142797E+11 | 0.104654E+11 | 0.755706E+10 | 0.290832E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.134761E+12 | 0.104413E+12 | 0.132011E+12 | 0.760456E+11 | 0.559657E+11 | 0.00 | 0.00 |
Minimum of Months | 0.853690E+10 | 0.341448E+10 | 0.860300E+10 | 0.250905E+10 | 0.290832E+10 | 0.00 | 0.00 |
Maximum of Months | 0.149691E+11 | 0.168943E+11 | 0.132070E+11 | 0.913249E+10 | 0.609396E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.809405E+09 | 0.128724E+11 | 0.216488E+10 | 0.872462E+09 | 0.129242E+10 | 0.00 | 0.00 |
February | 0.207793E+10 | 0.854622E+10 | 0.333753E+10 | 0.164056E+10 | 0.169696E+10 | 0.00 | 0.00 |
March | 0.302883E+10 | 0.795060E+10 | 0.472885E+10 | 0.173272E+10 | 0.299613E+10 | 0.00 | 0.00 |
April | 0.513888E+10 | 0.553031E+10 | 0.597440E+10 | 0.264694E+10 | 0.332746E+10 | 0.00 | 0.00 |
May | 0.750289E+10 | 0.449412E+10 | 0.763623E+10 | 0.348253E+10 | 0.415370E+10 | 0.00 | 0.00 |
June | 0.926701E+10 | 0.292447E+10 | 0.803993E+10 | 0.369304E+10 | 0.434689E+10 | 0.00 | 0.00 |
July | 0.110412E+11 | 0.246313E+10 | 0.851055E+10 | 0.430051E+10 | 0.421004E+10 | 0.00 | 0.00 |
August | 0.903385E+10 | 0.267059E+10 | 0.722660E+10 | 0.354667E+10 | 0.367994E+10 | 0.00 | 0.00 |
September | 0.625838E+10 | 0.370791E+10 | 0.562582E+10 | 0.284419E+10 | 0.278164E+10 | 0.00 | 0.00 |
October | 0.358291E+10 | 0.559242E+10 | 0.415495E+10 | 0.206437E+10 | 0.209058E+10 | 0.00 | 0.00 |
November | 0.182617E+10 | 0.762230E+10 | 0.284643E+10 | 0.141207E+10 | 0.143436E+10 | 0.00 | 0.00 |
December | 0.750997E+09 | 0.108274E+11 | 0.197710E+10 | 0.834477E+09 | 0.114262E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.603184E+11 | 0.752018E+11 | 0.622233E+11 | 0.290705E+11 | 0.331527E+11 | 0.00 | 0.00 |
Minimum of Months | 0.750997E+09 | 0.246313E+10 | 0.197710E+10 | 0.834477E+09 | 0.114262E+10 | 0.00 | 0.00 |
Maximum of Months | 0.110412E+11 | 0.128724E+11 | 0.851055E+10 | 0.430051E+10 | 0.434689E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 14777338.63 | 0.192566E+11 | 0.156128E+10 | 0.00 | 0.156128E+10 | 0.00 | 0.00 |
February | 0.190630E+09 | 0.127486E+11 | 0.199109E+10 | 0.00 | 0.199109E+10 | 0.00 | 0.00 |
March | 0.630987E+09 | 0.111544E+11 | 0.358099E+10 | 0.00 | 0.358099E+10 | 0.00 | 0.00 |
April | 0.154031E+10 | 0.726788E+10 | 0.395137E+10 | 23059338.10 | 0.392832E+10 | 0.00 | 0.00 |
May | 0.329516E+10 | 0.557395E+10 | 0.536207E+10 | 0.317736E+09 | 0.504433E+10 | 0.00 | 0.00 |
June | 0.576448E+10 | 0.336265E+10 | 0.604242E+10 | 0.694525E+09 | 0.534789E+10 | 0.00 | 0.00 |
July | 0.694043E+10 | 0.279715E+10 | 0.570408E+10 | 0.534256E+09 | 0.516983E+10 | 0.00 | 0.00 |
August | 0.499768E+10 | 0.322719E+10 | 0.457071E+10 | 0.122516E+09 | 0.444819E+10 | 0.00 | 0.00 |
September | 0.275662E+10 | 0.474098E+10 | 0.331272E+10 | 1188784.23 | 0.331153E+10 | 0.00 | 0.00 |
October | 0.906289E+09 | 0.732264E+10 | 0.249699E+10 | 0.00 | 0.249699E+10 | 0.00 | 0.00 |
November | 0.159646E+09 | 0.108970E+11 | 0.164272E+10 | 0.00 | 0.164272E+10 | 0.00 | 0.00 |
December | 2744071.20 | 0.160896E+11 | 0.130922E+10 | 0.00 | 0.130922E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.271997E+11 | 0.104439E+12 | 0.415257E+11 | 0.169328E+10 | 0.398324E+11 | 0.00 | 0.00 |
Minimum of Months | 2744071.20 | 0.279715E+10 | 0.130922E+10 | 0.00 | 0.130922E+10 | 0.00 | 0.00 |
Maximum of Months | 0.694043E+10 | 0.192566E+11 | 0.604242E+10 | 0.694525E+09 | 0.534789E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.956544E+09 | 0.117425E+11 | 0.239005E+10 | 0.109574E+10 | 0.129431E+10 | 0.00 | 0.00 |
February | 0.215113E+10 | 0.775531E+10 | 0.337649E+10 | 0.167634E+10 | 0.170014E+10 | 0.00 | 0.00 |
March | 0.342194E+10 | 0.688529E+10 | 0.502642E+10 | 0.207979E+10 | 0.294663E+10 | 0.00 | 0.00 |
April | 0.537227E+10 | 0.460679E+10 | 0.620634E+10 | 0.307582E+10 | 0.313052E+10 | 0.00 | 0.00 |
May | 0.668688E+10 | 0.372756E+10 | 0.708423E+10 | 0.315204E+10 | 0.393219E+10 | 0.00 | 0.00 |
June | 0.101174E+11 | 0.235238E+10 | 0.887383E+10 | 0.456646E+10 | 0.430736E+10 | 0.00 | 0.00 |
July | 0.121879E+11 | 0.191717E+10 | 0.962377E+10 | 0.544058E+10 | 0.418320E+10 | 0.00 | 0.00 |
August | 0.102568E+11 | 0.217351E+10 | 0.836349E+10 | 0.465988E+10 | 0.370361E+10 | 0.00 | 0.00 |
September | 0.621077E+10 | 0.302035E+10 | 0.572550E+10 | 0.295548E+10 | 0.277002E+10 | 0.00 | 0.00 |
October | 0.364710E+10 | 0.455603E+10 | 0.424467E+10 | 0.215538E+10 | 0.208929E+10 | 0.00 | 0.00 |
November | 0.151895E+10 | 0.658555E+10 | 0.260341E+10 | 0.121545E+10 | 0.138796E+10 | 0.00 | 0.00 |
December | 0.716277E+09 | 0.982496E+10 | 0.198417E+10 | 0.852206E+09 | 0.113196E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.632439E+11 | 0.651474E+11 | 0.655024E+11 | 0.329252E+11 | 0.325772E+11 | 0.00 | 0.00 |
Minimum of Months | 0.716277E+09 | 0.191717E+10 | 0.198417E+10 | 0.852206E+09 | 0.113196E+10 | 0.00 | 0.00 |
Maximum of Months | 0.121879E+11 | 0.117425E+11 | 0.962377E+10 | 0.544058E+10 | 0.430736E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.880380E+10 | 0.162877E+11 | 0.110053E+11 | 0.786017E+10 | 0.314508E+10 | 0.00 | 0.00 |
February | 0.115199E+11 | 0.108522E+11 | 0.126587E+11 | 0.910464E+10 | 0.355410E+10 | 0.00 | 0.00 |
March | 0.113204E+11 | 0.106638E+11 | 0.125276E+11 | 0.703493E+10 | 0.549268E+10 | 0.00 | 0.00 |
April | 0.939762E+10 | 0.749802E+10 | 0.974526E+10 | 0.466122E+10 | 0.508404E+10 | 0.00 | 0.00 |
May | 0.876196E+10 | 0.613091E+10 | 0.894703E+10 | 0.297155E+10 | 0.597547E+10 | 0.00 | 0.00 |
June | 0.101406E+11 | 0.402286E+10 | 0.860300E+10 | 0.250905E+10 | 0.609396E+10 | 0.00 | 0.00 |
July | 0.131068E+11 | 0.318394E+10 | 0.958406E+10 | 0.354032E+10 | 0.604374E+10 | 0.00 | 0.00 |
August | 0.149860E+11 | 0.363940E+10 | 0.113900E+11 | 0.574265E+10 | 0.564738E+10 | 0.00 | 0.00 |
September | 0.145498E+11 | 0.501406E+10 | 0.122254E+11 | 0.749090E+10 | 0.473450E+10 | 0.00 | 0.00 |
October | 0.140302E+11 | 0.720798E+10 | 0.132070E+11 | 0.913249E+10 | 0.407454E+10 | 0.00 | 0.00 |
November | 0.109399E+11 | 0.937475E+10 | 0.116525E+11 | 0.844059E+10 | 0.321189E+10 | 0.00 | 0.00 |
December | 0.870616E+10 | 0.135645E+11 | 0.104654E+11 | 0.755706E+10 | 0.290832E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.136263E+12 | 0.974402E+11 | 0.132011E+12 | 0.760456E+11 | 0.559657E+11 | 0.00 | 0.00 |
Minimum of Months | 0.870616E+10 | 0.318394E+10 | 0.860300E+10 | 0.250905E+10 | 0.290832E+10 | 0.00 | 0.00 |
Maximum of Months | 0.149860E+11 | 0.162877E+11 | 0.132070E+11 | 0.913249E+10 | 0.609396E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.824482E+09 | 0.125490E+11 | 0.216488E+10 | 0.872462E+09 | 0.129242E+10 | 0.00 | 0.00 |
February | 0.210844E+10 | 0.817138E+10 | 0.333753E+10 | 0.164056E+10 | 0.169696E+10 | 0.00 | 0.00 |
March | 0.305361E+10 | 0.753136E+10 | 0.472885E+10 | 0.173272E+10 | 0.299613E+10 | 0.00 | 0.00 |
April | 0.517509E+10 | 0.512706E+10 | 0.597440E+10 | 0.264694E+10 | 0.332746E+10 | 0.00 | 0.00 |
May | 0.749509E+10 | 0.419837E+10 | 0.763623E+10 | 0.348253E+10 | 0.415370E+10 | 0.00 | 0.00 |
June | 0.924169E+10 | 0.277265E+10 | 0.803993E+10 | 0.369304E+10 | 0.434689E+10 | 0.00 | 0.00 |
July | 0.110137E+11 | 0.234830E+10 | 0.851055E+10 | 0.430051E+10 | 0.421004E+10 | 0.00 | 0.00 |
August | 0.901624E+10 | 0.253388E+10 | 0.722660E+10 | 0.354667E+10 | 0.367994E+10 | 0.00 | 0.00 |
September | 0.626550E+10 | 0.346435E+10 | 0.562582E+10 | 0.284419E+10 | 0.278164E+10 | 0.00 | 0.00 |
October | 0.364795E+10 | 0.511126E+10 | 0.415495E+10 | 0.206437E+10 | 0.209058E+10 | 0.00 | 0.00 |
November | 0.188110E+10 | 0.713801E+10 | 0.284643E+10 | 0.141207E+10 | 0.143436E+10 | 0.00 | 0.00 |
December | 0.768562E+09 | 0.104316E+11 | 0.197710E+10 | 0.834477E+09 | 0.114262E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.604915E+11 | 0.713773E+11 | 0.622233E+11 | 0.290705E+11 | 0.331527E+11 | 0.00 | 0.00 |
Minimum of Months | 0.768562E+09 | 0.234830E+10 | 0.197710E+10 | 0.834477E+09 | 0.114262E+10 | 0.00 | 0.00 |
Maximum of Months | 0.110137E+11 | 0.125490E+11 | 0.851055E+10 | 0.430051E+10 | 0.434689E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.439097E+11 | -0.434465E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -463123594.1 | 60.05 | 0.00 | 0.00 |
February | 0.405762E+11 | -0.401603E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -415902686.2 | 60.05 | 0.00 | 0.00 |
March | 0.472189E+11 | -0.467627E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -456232665.3 | 60.05 | 0.00 | 0.00 |
April | 0.413165E+11 | -0.408794E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -437025851.9 | 60.05 | 0.00 | 0.00 |
May | 0.417541E+11 | -0.413036E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -450440648.6 | 60.05 | 0.00 | 0.00 |
June | 0.388965E+11 | -0.384626E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -433911657.5 | 60.05 | 0.00 | 0.00 |
July | 0.351986E+11 | -0.347545E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444086320.8 | 60.05 | 0.00 | 0.00 |
August | 0.376568E+11 | -0.372113E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -445457467.1 | 60.05 | 0.00 | 0.00 |
September | 0.346409E+11 | -0.342090E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -431983540.7 | 60.05 | 0.00 | 0.00 |
October | 0.373498E+11 | -0.369037E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -446157960.6 | 60.05 | 0.00 | 0.00 |
November | 0.388909E+11 | -0.384580E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -432976032.4 | 60.05 | 0.00 | 0.00 |
December | 0.410410E+11 | -0.405868E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -454194872.1 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.478450E+12 | -0.473138E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.531149E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.346409E+11 | -0.467627E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -463123594.1 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.472189E+11 | -0.342090E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -415902686.2 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 304.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 385.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 417.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 421.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 352.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 317.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 269.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 236.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3965.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.213339E+11 | 67710.49 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.973143E+10 | 49663.02 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.294168E+10 | 42283.22 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96211305.13 | 10962.57 | 29-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19811687.63 | 4724.62 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 45789258.07 | 9224.39 | 10-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107076E+10 | 26779.06 | 27-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.851203E+10 | 53131.68 | 29-DEC-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.437516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.213339E+11 | 67710.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.101484E+09 | 39499.55 | 30-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10603108.27 | 6339.57 | 06-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112088E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.101484E+09 | 39499.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.811190E+10 | 23402.37 | 25-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.415425E+10 | 24066.30 | 28-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208694E+10 | 23307.94 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.356783E+09 | 23101.83 | 28-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.246024E+09 | 22964.52 | 08-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12953791.31 | 3852.39 | 16-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74711160.85 | 5093.48 | 18-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.323564E+09 | 23094.42 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137255E+10 | 24093.25 | 10-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.389071E+10 | 23318.72 | 28-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.811190E+10 | 24093.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.664543E+10 | 21405.20 | 07-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.367307E+10 | 21410.11 | 09-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227374E+10 | 21405.45 | 04-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.725409E+09 | 21336.99 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.425113E+09 | 19991.05 | 08-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 42484933.05 | 9244.48 | 16-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 106063.98 | 1767.73 | 05-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15816584.75 | 3935.00 | 28-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.234688E+09 | 9661.95 | 18-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.687449E+09 | 21096.32 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190430E+10 | 21412.89 | 27-NOV-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.413737E+10 | 21407.17 | 28-DEC-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 106063.98 | 1767.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.664543E+10 | 21412.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.822802E+10 | 30532.44 | 25-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.420337E+10 | 30525.30 | 04-FEB-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.298649E+10 | 30524.10 | 06-MAR-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109300E+10 | 30408.82 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.891558E+09 | 28683.86 | 06-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130725E+09 | 18862.85 | 17-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3706158.41 | 2756.46 | 08-JUL-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22650052.15 | 7896.68 | 18-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.330890E+09 | 27089.70 | 19-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.838296E+09 | 30063.84 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.219639E+10 | 30523.69 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.469196E+10 | 30535.37 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.256170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3706158.41 | 2756.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.822802E+10 | 30535.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.559179E+10 | 22423.00 | 07-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.298667E+10 | 22426.14 | 09-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156682E+10 | 22422.43 | 04-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144156E+09 | 22365.14 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.317541E+09 | 20146.56 | 08-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29863003.80 | 3737.26 | 17-JUN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139826E+09 | 6969.19 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.434037E+09 | 22105.55 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110046E+10 | 22428.36 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.214188E+10 | 22423.88 | 28-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.559179E+10 | 22428.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.285636E+12 | 727990.85 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130171E+12 | 547463.60 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.464640E+11 | 724281.05 | 01-MAR-12:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.284794E+10 | 359526.93 | 03-APR-09:28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.239146E+10 | 541354.32 | 23-MAY-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32987894.35 | 325978.45 | 15-JUN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12142345.69 | 202372.43 | 05-JUL-09:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12239843.05 | 81598.95 | 02-AUG-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.465123E+09 | 478745.54 | 19-SEP-09:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.292800E+10 | 753669.43 | 10-OCT-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.367917E+11 | 775589.67 | 10-NOV-10:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153500E+12 | 605323.80 | 29-DEC-08:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.661253E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 12142345.69 | 81598.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.285636E+12 | 775589.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.198489E+11 | 720493.41 | 31-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.484460E+10 | 714226.25 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.279186E+10 | 719222.31 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.306103E+10 | 719370.87 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.898790E+10 | 719852.25 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.395343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.198489E+11 | 720493.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.172734E+12 | 310214.07 | 30-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100068E+12 | 311268.75 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.728532E+11 | 310114.23 | 01-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.296137E+11 | 308335.65 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.184665E+11 | 305003.91 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.177122E+10 | 274537.35 | 17-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.179526E+09 | 65951.19 | 08-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142469E+10 | 257897.02 | 18-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111216E+11 | 278437.53 | 19-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.292764E+11 | 310277.50 | 10-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.694737E+11 | 309386.99 | 13-NOV-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127100E+12 | 311345.18 | 26-DEC-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.634082E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.179526E+09 | 65951.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172734E+12 | 311345.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104877E+12 | 248734.31 | 10-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.586234E+11 | 248296.76 | 09-FEB-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.433391E+11 | 248736.83 | 06-MAR-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.175732E+11 | 248296.60 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.118997E+11 | 232722.61 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141721E+10 | 207619.07 | 16-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.221029E+09 | 46590.40 | 08-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.128580E+10 | 196432.21 | 18-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.757415E+10 | 212248.85 | 19-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180190E+11 | 245592.03 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.430288E+11 | 248740.71 | 27-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.788483E+11 | 248309.01 | 14-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.386707E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.221029E+09 | 46590.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104877E+12 | 248740.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123819E+12 | 322558.50 | 10-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.618419E+11 | 321054.10 | 23-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.504059E+11 | 321329.57 | 06-MAR-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.233245E+11 | 319815.06 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178583E+11 | 314606.75 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.326947E+10 | 283160.03 | 17-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.434117E+09 | 101031.08 | 08-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135484E+10 | 265985.24 | 18-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.787370E+10 | 287185.77 | 19-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167309E+11 | 321844.69 | 10-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.438772E+11 | 321340.91 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.860167E+11 | 322707.62 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.436806E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.434117E+09 | 101031.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123819E+12 | 322707.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113210E+12 | 260917.89 | 10-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.639822E+11 | 260315.88 | 23-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.503197E+11 | 260920.28 | 06-MAR-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214470E+11 | 259501.21 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148783E+11 | 244038.08 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.314225E+10 | 219315.51 | 17-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.489501E+09 | 45828.04 | 08-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180513E+10 | 205836.85 | 18-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100447E+11 | 222481.41 | 19-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.220356E+11 | 257586.75 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.471125E+11 | 260923.98 | 27-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.825490E+11 | 260294.61 | 26-DEC-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.431016E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.489501E+09 | 45828.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113210E+12 | 260923.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.367210E+11 | 66339.46 | 09-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159211E+11 | 63585.29 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.730295E+10 | 54436.44 | 04-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.657308E+09 | 24811.16 | 29-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.461008E+09 | 15812.31 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7968797.57 | 2711.53 | 19-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.761425E+09 | 23885.05 | 10-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.606348E+10 | 43202.00 | 27-NOV-03:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219764E+11 | 64094.35 | 29-DEC-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.898727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.367210E+11 | 66339.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.263066E+11 | 131493.27 | 18-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143116E+11 | 131514.37 | 01-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105572E+11 | 131139.72 | 08-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.388382E+10 | 130872.36 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.294207E+10 | 130243.07 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.115811E+09 | 116734.25 | 17-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 46166384.26 | 44245.75 | 18-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.813482E+09 | 118412.02 | 19-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.424449E+10 | 132162.69 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107246E+11 | 131746.80 | 06-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195098E+11 | 131594.13 | 14-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.934557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.263066E+11 | 132162.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.271020E+11 | 41114.85 | 19-JAN-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174986E+11 | 41193.18 | 14-FEB-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146678E+11 | 41153.56 | 07-MAR-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.745454E+10 | 41262.62 | 28-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.515780E+10 | 40507.90 | 08-MAY-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124937E+10 | 36357.47 | 17-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.353596E+09 | 32531.81 | 08-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101062E+10 | 32980.36 | 18-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.367243E+10 | 36880.06 | 19-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.791928E+10 | 41015.08 | 10-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145117E+11 | 41142.31 | 28-NOV-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.222210E+11 | 41123.11 | 09-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122819E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.353596E+09 | 32531.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.271020E+11 | 41262.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.165865E+11 | 27104.37 | 19-JAN-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.998672E+10 | 27156.01 | 14-FEB-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.798080E+10 | 27129.89 | 07-MAR-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.366711E+10 | 27201.78 | 28-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.254594E+10 | 26531.14 | 08-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.514367E+09 | 23968.14 | 17-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108320E+09 | 21446.13 | 08-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.400245E+09 | 21741.83 | 18-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.171533E+10 | 24312.65 | 19-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.391178E+10 | 27038.60 | 10-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.833803E+10 | 27122.48 | 28-NOV-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136752E+11 | 27109.82 | 09-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.694303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.108320E+09 | 21446.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.165865E+11 | 27201.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.207995E+11 | 41808.19 | 19-JAN-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117807E+11 | 41887.85 | 14-FEB-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108208E+11 | 41847.56 | 07-MAR-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.590804E+10 | 41958.45 | 28-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.473450E+10 | 40923.99 | 08-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147536E+10 | 36970.59 | 17-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.498936E+09 | 33080.42 | 08-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.919960E+09 | 33536.53 | 18-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.266826E+10 | 37502.00 | 19-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.499075E+10 | 41706.75 | 10-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.981171E+10 | 41836.12 | 28-NOV-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164753E+11 | 41816.60 | 09-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.908838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.498936E+09 | 33080.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.207995E+11 | 41958.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.162635E+11 | 31210.12 | 18-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.960829E+10 | 31210.19 | 23-FEB-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.816469E+10 | 31147.20 | 03-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.397470E+10 | 31141.39 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.293263E+10 | 29052.25 | 08-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.900342E+09 | 26229.50 | 17-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.278145E+09 | 23456.81 | 08-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.610171E+09 | 23781.19 | 18-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.214964E+10 | 26609.10 | 19-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.428941E+10 | 30671.35 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.790502E+10 | 31201.48 | 21-NOV-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126506E+11 | 31201.88 | 28-DEC-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.697271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.278145E+09 | 23456.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.162635E+11 | 31210.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.298840E+10 | 180102.06 | 10-JAN-21:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.402996E+09 | 17821.62 | 04-FEB-16:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 80675034.81 | 30705.99 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20871873.34 | 4302.43 | 29-DEC-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.298840E+10 | 180102.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.731142E+09 | 0.731142E+09 | 45528.09 | 27-FEB-15:21 | 45528.09 | 0.00 |
March | 0.00 | 0.00 | 46009654.44 | 46009654.44 | 7492.37 | 14-MAR-13:21 | 7492.37 | 0.00 |
April | 0.00 | 0.00 | 0.763361E+10 | 0.763361E+10 | 92485.94 | 06-APR-16:00 | 92485.94 | 0.00 |
May | 0.00 | 0.00 | 0.220150E+11 | 0.220150E+11 | 129600.19 | 19-MAY-15:30 | 129600.19 | 0.02 |
June | 0.00 | 0.00 | 0.679616E+11 | 0.679102E+11 | 145707.80 | 29-JUN-14:40 | 145707.80 | 0.17 |
July | 0.00 | 0.00 | 0.117065E+12 | 0.116863E+12 | 174405.86 | 17-JUL-15:50 | 174405.86 | 0.31 |
August | 0.00 | 0.00 | 0.107083E+12 | 0.107083E+12 | 170365.17 | 07-AUG-15:00 | 170365.17 | 0.15 |
September | 0.00 | 0.00 | 0.463970E+11 | 0.450390E+11 | 218179.06 | 07-SEP-14:50 | 114612.82 | 0.12 |
October | 0.00 | 0.00 | 0.125692E+11 | 0.125692E+11 | 122112.64 | 18-OCT-15:20 | 122112.64 | 0.00 |
November | 0.00 | 0.00 | 0.765204E+09 | 0.765204E+09 | 23277.81 | 17-NOV-16:51 | 23277.81 | 0.00 |
December | 0.00 | 0.00 | 102335.07 | 102335.07 | 507.75 | 26-DEC-17:03 | 507.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.382267E+12 | 0.380656E+12 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.117065E+12 | 0.116863E+12 | 218179.06 | 174405.86 | 0.31 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 96972.77 | 96972.77 | 5.97 | 03-JAN-05:12 | 5.97 | 0.00 |
February | 0.00 | 0.00 | 0.106124E+11 | 0.106124E+11 | 719262.50 | 27-FEB-15:01 | 719262.50 | 0.00 |
March | 0.00 | 0.00 | 0.111127E+11 | 0.111127E+11 | 594821.34 | 02-MAR-15:01 | 594821.34 | 0.00 |
April | 0.00 | 0.00 | 0.702122E+11 | 0.702122E+11 | 821613.97 | 06-APR-16:00 | 821613.97 | 0.00 |
May | 0.00 | 0.00 | 0.209437E+12 | 0.209437E+12 | 1262989.04 | 19-MAY-15:30 | 1262989.04 | 0.02 |
June | 0.00 | 0.00 | 0.622458E+12 | 0.621902E+12 | 1406876.51 | 29-JUN-15:00 | 1406876.51 | 0.17 |
July | 0.00 | 0.00 | 0.101660E+13 | 0.101498E+13 | 1608029.92 | 17-JUL-16:00 | 1608029.92 | 0.29 |
August | 0.00 | 0.00 | 0.891082E+12 | 0.891082E+12 | 1576479.38 | 10-AUG-15:10 | 1576479.38 | 0.14 |
September | 0.00 | 0.00 | 0.426758E+12 | 0.414281E+12 | 2007414.84 | 07-SEP-14:50 | 1054942.76 | 0.11 |
October | 0.00 | 0.00 | 0.133795E+12 | 0.133795E+12 | 1102844.75 | 18-OCT-15:20 | 1102844.75 | 0.00 |
November | 0.00 | 0.00 | 0.116953E+11 | 0.116953E+11 | 764669.18 | 03-NOV-14:01 | 764669.18 | 0.00 |
December | 0.00 | 0.00 | 262511.42 | 262511.42 | 5.58 | 02-DEC-13:17 | 5.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.340377E+13 | 0.338911E+13 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 96972.77 | 96972.77 | 5.58 | 5.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101660E+13 | 0.101498E+13 | 2007414.84 | 1608029.92 | 0.29 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4108511.06 | 4108511.06 | 5555.10 | 18-JAN-06:01 | 5555.10 | 0.00 |
February | 0.00 | 0.00 | 0.573729E+09 | 0.573729E+09 | 41801.33 | 26-FEB-15:11 | 41801.33 | 0.00 |
March | 0.00 | 0.00 | 17457434.51 | 17457434.51 | 4760.60 | 20-MAR-04:31 | 4760.60 | 0.00 |
April | 0.00 | 0.00 | 0.620092E+10 | 0.620092E+10 | 83213.80 | 06-APR-16:00 | 83213.80 | 0.00 |
May | 0.00 | 0.00 | 0.225257E+11 | 0.225257E+11 | 159464.47 | 19-MAY-15:30 | 159464.47 | 0.02 |
June | 0.00 | 0.00 | 0.722633E+11 | 0.722388E+11 | 176601.32 | 29-JUN-15:00 | 176601.32 | 0.16 |
July | 0.00 | 0.00 | 0.119541E+12 | 0.119416E+12 | 236621.58 | 16-JUL-15:31 | 220068.86 | 0.30 |
August | 0.00 | 0.00 | 0.100582E+12 | 0.100582E+12 | 193889.23 | 10-AUG-15:00 | 193889.23 | 0.14 |
September | 0.00 | 0.00 | 0.454381E+11 | 0.443677E+11 | 194924.16 | 07-SEP-14:50 | 104965.71 | 0.11 |
October | 0.00 | 0.00 | 0.102207E+11 | 0.102207E+11 | 118223.12 | 18-OCT-15:00 | 118223.12 | 0.00 |
November | 0.00 | 0.00 | 0.577939E+09 | 0.577939E+09 | 18183.01 | 04-NOV-13:54 | 18183.01 | 0.00 |
December | 0.00 | 0.00 | 10539264.19 | 10539264.19 | 4469.19 | 04-DEC-05:12 | 4469.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.377956E+12 | 0.376736E+12 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 4108511.06 | 4108511.06 | 4469.19 | 4469.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.119541E+12 | 0.119416E+12 | 236621.58 | 220068.86 | 0.30 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.214667E+10 | 0.205747E+10 | 115206.37 | 02-JAN-05:04 | 23259.91 | 0.00 |
February | 0.00 | 0.00 | 0.226954E+10 | 0.226954E+10 | 138147.60 | 28-FEB-05:45 | 138147.60 | 0.00 |
March | 0.00 | 0.00 | 0.381141E+10 | 0.381141E+10 | 129189.99 | 01-MAR-05:48 | 129189.99 | 0.00 |
April | 0.00 | 0.00 | 0.794048E+10 | 0.794048E+10 | 91446.63 | 13-APR-04:06 | 91446.63 | 0.00 |
May | 0.00 | 0.00 | 0.171542E+11 | 0.171508E+11 | 78408.32 | 22-MAY-05:02 | 78408.32 | 0.02 |
June | 0.00 | 0.00 | 0.367914E+11 | 0.357962E+11 | 139861.94 | 15-JUN-04:42 | 139861.94 | 0.15 |
July | 0.00 | 0.00 | 0.544491E+11 | 0.535766E+11 | 100778.69 | 25-JUL-05:02 | 100778.69 | 0.24 |
August | 0.00 | 0.00 | 0.533960E+11 | 0.533903E+11 | 81711.44 | 07-AUG-04:13 | 81711.44 | 0.13 |
September | 0.00 | 0.00 | 0.334159E+11 | 0.313800E+11 | 114679.41 | 07-SEP-14:50 | 55640.01 | 0.12 |
October | 0.00 | 0.00 | 0.182928E+11 | 0.182928E+11 | 133631.17 | 11-OCT-03:48 | 133631.17 | 0.00 |
November | 0.00 | 0.00 | 0.890418E+10 | 0.890418E+10 | 140702.29 | 27-NOV-05:43 | 140702.29 | 0.00 |
December | 0.00 | 0.00 | 0.374433E+10 | 0.374433E+10 | 128081.82 | 26-DEC-05:50 | 128081.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.242316E+12 | 0.238314E+12 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 0.214667E+10 | 0.205747E+10 | 78408.32 | 23259.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.544491E+11 | 0.535766E+11 | 140702.29 | 140702.29 | 0.24 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3103156.31 | 3103156.31 | 68.66 | 02-JAN-19:53 | 68.66 | 0.00 |
February | 0.00 | 0.00 | 0.198821E+12 | 0.198821E+12 | 371343.27 | 27-FEB-15:13 | 371343.27 | 0.00 |
March | 0.00 | 0.00 | 0.329608E+12 | 0.329608E+12 | 297266.35 | 31-MAR-23:24 | 297266.35 | 0.00 |
April | 0.00 | 0.00 | 0.244862E+12 | 0.244862E+12 | 334800.56 | 03-APR-13:59 | 334800.56 | 0.00 |
May | 0.00 | 0.00 | 0.934275E+10 | 0.934275E+10 | 299590.35 | 31-MAY-23:50 | 299590.35 | 0.03 |
June | 0.00 | 0.00 | 0.261857E+12 | 0.258696E+12 | 447540.39 | 21-JUN-23:52 | 283308.07 | 0.27 |
July | 0.00 | 0.00 | 0.432051E+12 | 0.429499E+12 | 484040.84 | 01-JUL-01:01 | 218930.45 | 0.54 |
August | 0.00 | 0.00 | 0.459329E+12 | 0.459327E+12 | 400028.30 | 05-AUG-09:02 | 400028.30 | 0.26 |
September | 0.00 | 0.00 | 0.335645E+11 | 0.335645E+11 | 308405.00 | 30-SEP-23:21 | 308405.00 | 0.17 |
October | 0.00 | 0.00 | 0.213671E+12 | 0.213670E+12 | 443483.24 | 23-OCT-13:51 | 443483.24 | 0.01 |
November | 0.00 | 0.00 | 0.263558E+12 | 0.263558E+12 | 355842.34 | 16-NOV-22:22 | 355842.34 | 0.00 |
December | 0.00 | 0.00 | 0.298394E+12 | 0.298394E+12 | 316901.25 | 19-DEC-13:49 | 316901.25 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.274506E+13 | 0.273935E+13 | 0.11 | |||
Minimum of Months | 0.00 | 0.00 | 3103156.31 | 3103156.31 | 68.66 | 68.66 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.459329E+12 | 0.459327E+12 | 484040.84 | 443483.24 | 0.54 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.441468E+10 | 0.441435E+10 | 9061.77 | 06-JAN-03:31 | 9061.77 | 0.00 |
February | 0.00 | 0.00 | 0.943480E+10 | 0.943480E+10 | 14590.53 | 01-FEB-07:01 | 14590.53 | 0.00 |
March | 0.00 | 0.00 | 0.161653E+11 | 0.161653E+11 | 7910.13 | 31-MAR-23:57 | 7910.13 | 0.00 |
April | 0.00 | 0.00 | 0.217185E+11 | 0.217185E+11 | 9823.14 | 22-APR-18:07 | 9823.14 | 0.00 |
May | 0.00 | 0.00 | 0.763678E+10 | 0.763678E+10 | 4934.21 | 31-MAY-23:51 | 4934.21 | 0.00 |
June | 0.00 | 0.00 | 0.128085E+11 | 0.127813E+11 | 6865.93 | 30-JUN-24:00 | 6865.93 | 0.00 |
July | 0.00 | 0.00 | 0.187747E+11 | 0.187445E+11 | 8728.89 | 31-JUL-23:05 | 8728.89 | 0.00 |
August | 0.00 | 0.00 | 0.237657E+11 | 0.237558E+11 | 10301.28 | 04-AUG-19:00 | 10301.28 | 0.00 |
September | 0.00 | 0.00 | 0.775648E+10 | 0.772905E+10 | 4668.19 | 30-SEP-23:31 | 4668.19 | 0.00 |
October | 0.00 | 0.00 | 0.122166E+11 | 0.122166E+11 | 6113.77 | 31-OCT-23:52 | 6113.77 | 0.00 |
November | 0.00 | 0.00 | 0.161069E+11 | 0.161069E+11 | 7403.04 | 03-NOV-15:53 | 7403.04 | 0.00 |
December | 0.00 | 0.00 | 0.206996E+11 | 0.206996E+11 | 15441.45 | 29-DEC-09:41 | 15441.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.171499E+12 | 0.171404E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.441468E+10 | 0.441435E+10 | 4668.19 | 4668.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.237657E+11 | 0.237558E+11 | 15441.45 | 15441.45 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.235673E+11 | 0.235658E+11 | 42177.70 | 27-JAN-10:32 | 42177.70 | 0.00 |
February | 0.00 | 0.00 | 0.782147E+11 | 0.782147E+11 | 138286.89 | 01-FEB-07:01 | 138286.89 | 0.00 |
March | 0.00 | 0.00 | 0.144855E+12 | 0.144855E+12 | 73624.15 | 28-MAR-17:42 | 73624.15 | 0.00 |
April | 0.00 | 0.00 | 0.198788E+12 | 0.198788E+12 | 93435.38 | 25-APR-18:10 | 93435.38 | 0.00 |
May | 0.00 | 0.00 | 0.651692E+11 | 0.651689E+11 | 46601.89 | 31-MAY-23:31 | 46601.89 | 0.00 |
June | 0.00 | 0.00 | 0.119935E+12 | 0.119663E+12 | 66711.51 | 30-JUN-23:40 | 66711.51 | 0.00 |
July | 0.00 | 0.00 | 0.177091E+12 | 0.176789E+12 | 84595.61 | 31-JUL-23:50 | 84595.61 | 0.00 |
August | 0.00 | 0.00 | 0.223684E+12 | 0.223585E+12 | 99282.23 | 04-AUG-19:00 | 99282.23 | 0.00 |
September | 0.00 | 0.00 | 0.669921E+11 | 0.667200E+11 | 41415.93 | 30-SEP-23:11 | 41415.93 | 0.00 |
October | 0.00 | 0.00 | 0.107235E+12 | 0.107235E+12 | 56844.45 | 18-OCT-17:00 | 56844.45 | 0.00 |
November | 0.00 | 0.00 | 0.139624E+12 | 0.139624E+12 | 70561.90 | 03-NOV-15:53 | 70561.90 | 0.00 |
December | 0.00 | 0.00 | 0.177171E+12 | 0.177171E+12 | 146773.66 | 29-DEC-09:41 | 146773.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.152233E+13 | 0.152138E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.235673E+11 | 0.235658E+11 | 41415.93 | 41415.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.223684E+12 | 0.223585E+12 | 146773.66 | 146773.66 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.116568E+10 | 0.116568E+10 | 2772.64 | 13-JAN-16:25 | 2772.64 | 0.00 |
February | 0.00 | 0.00 | 0.586825E+10 | 0.586825E+10 | 12290.30 | 01-FEB-07:01 | 12290.30 | 0.00 |
March | 0.00 | 0.00 | 0.124780E+11 | 0.124780E+11 | 7346.38 | 28-MAR-17:42 | 7346.38 | 0.00 |
April | 0.00 | 0.00 | 0.183246E+11 | 0.183246E+11 | 9463.57 | 25-APR-18:10 | 9463.57 | 0.00 |
May | 0.00 | 0.00 | 0.547827E+10 | 0.547826E+10 | 4499.87 | 31-MAY-23:12 | 4499.87 | 0.00 |
June | 0.00 | 0.00 | 0.115695E+11 | 0.115423E+11 | 6653.13 | 30-JUN-23:20 | 6653.13 | 0.00 |
July | 0.00 | 0.00 | 0.174944E+11 | 0.174643E+11 | 8430.72 | 31-JUL-23:20 | 8430.72 | 0.00 |
August | 0.00 | 0.00 | 0.220435E+11 | 0.220341E+11 | 10115.00 | 04-AUG-19:00 | 10115.00 | 0.00 |
September | 0.00 | 0.00 | 0.580154E+10 | 0.577442E+10 | 4327.06 | 04-SEP-17:42 | 4327.06 | 0.00 |
October | 0.00 | 0.00 | 0.880886E+10 | 0.880886E+10 | 5779.78 | 18-OCT-17:00 | 5779.78 | 0.00 |
November | 0.00 | 0.00 | 0.117271E+11 | 0.117271E+11 | 6976.76 | 03-NOV-15:53 | 6976.76 | 0.00 |
December | 0.00 | 0.00 | 0.155004E+11 | 0.155004E+11 | 14914.23 | 29-DEC-09:41 | 14914.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.136260E+12 | 0.136166E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.116568E+10 | 0.116568E+10 | 2772.64 | 2772.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.220435E+11 | 0.220341E+11 | 14914.23 | 14914.23 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 377563.06 | 3350463.25 | 02-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 215289.02 | 3329789.19 | 28-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 125406.04 | 3560797.79 | 01-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:02 | 47145.81 | 3278903.32 | 22-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 31982.51 | 3220045.99 | 09-MAY-04:01 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5419.04 | 2788322.64 | 17-JUN-04:11 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 957.72 | 517010.18 | 08-JUL-05:01 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 3317.28 | 2452347.83 | 18-AUG-05:01 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18794.52 | 2871111.05 | 20-SEP-04:11 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 43710.78 | 3222882.63 | 05-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 118384.31 | 3343425.15 | 06-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 247686.38 | 3388782.67 | 18-DEC-05:11 |
Annual Sum or Average | 0.00 | 102656.82 | ||||
Minimum of Months | 0.00 | 0.00 | 957.72 | 517010.18 | ||
Maximum of Months | 0.00 | 0.00 | 377563.06 | 3560797.79 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 2204.98 | 402979.66 | 02-JAN-16:25 | 117638.19 | 840339.53 | 22-JAN-15:10 |
February | 91538.38 | 1012268.10 | 27-FEB-14:46 | 53434.60 | 695107.65 | 28-FEB-23:12 |
March | 134499.59 | 1047031.63 | 01-MAR-14:50 | 23069.49 | 649873.36 | 31-MAR-23:13 |
April | 138531.62 | 1293012.84 | 06-APR-16:00 | 13763.28 | 822308.08 | 30-APR-23:43 |
May | 109515.74 | 1973554.42 | 19-MAY-14:05 | 182254.55 | 840127.61 | 07-MAY-03:20 |
June | 428554.99 | 2252744.63 | 21-JUN-12:05 | 56720.45 | 808575.27 | 25-JUN-22:21 |
July | 676573.35 | 2697991.40 | 10-JUL-12:05 | 31201.61 | 727076.32 | 23-JUL-06:10 |
August | 625802.20 | 2680594.69 | 05-AUG-17:06 | 15048.64 | 486545.19 | 10-AUG-02:20 |
September | 237820.48 | 2570792.28 | 27-SEP-14:05 | 212523.04 | 840116.72 | 17-SEP-12:47 |
October | 150316.35 | 2504335.33 | 18-OCT-13:04 | 91573.82 | 704805.26 | 29-OCT-20:32 |
November | 118422.16 | 1076162.88 | 03-NOV-13:22 | 15403.00 | 623278.47 | 28-NOV-01:30 |
December | 122144.00 | 593788.27 | 06-DEC-11:30 | 5716.83 | 276020.40 | 06-DEC-01:37 |
Annual Sum or Average | 237577.25 | 68246.74 | ||||
Minimum of Months | 2204.98 | 402979.66 | 5716.83 | 276020.40 | ||
Maximum of Months | 676573.35 | 2697991.40 | 212523.04 | 840339.53 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 863.54 | 69459.03 | 18-JAN-06:01 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 104527.20 | 1518302.74 | 27-FEB-15:08 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 152465.11 | 1172268.81 | 02-MAR-15:02 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 220697.24 | 1309487.83 | 06-APR-16:00 | 0.00 | 0.00 | 01-APR-00:02 |
May | 118386.06 | 1812041.43 | 19-MAY-12:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 454544.07 | 1979819.31 | 29-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:01 |
July | 713078.62 | 3684616.50 | 19-JUL-04:11 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 661744.30 | 2445229.10 | 05-AUG-17:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 248082.26 | 2564657.92 | 07-SEP-14:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 176628.30 | 1759649.14 | 18-OCT-13:06 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 189445.56 | 1325762.57 | 03-NOV-14:04 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 221197.75 | 601206.66 | 26-DEC-05:50 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 273109.89 | 0.00 | ||||
Minimum of Months | 863.54 | 69459.03 | 0.00 | 0.00 | ||
Maximum of Months | 713078.62 | 3684616.50 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 16135.05 | 57876.86 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 16514.11 | 58183.80 | 17-FEB-12:38 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 17371.52 | 58080.53 | 01-MAR-12:44 |
April | 0.00 | 0.00 | 01-APR-00:02 | 15686.02 | 56502.29 | 03-APR-11:46 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15336.03 | 53999.83 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14754.70 | 50705.40 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 12894.00 | 47668.69 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 13810.05 | 45986.73 | 01-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 13115.78 | 47092.14 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 13695.34 | 49894.98 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14752.91 | 53085.37 | 30-NOV-12:58 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 15068.81 | 55890.46 | 29-DEC-12:18 |
Annual Sum or Average | 0.00 | 14918.66 | ||||
Minimum of Months | 0.00 | 0.00 | 12894.00 | 45986.73 | ||
Maximum of Months | 0.00 | 0.00 | 17371.52 | 58183.80 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 339.43 | 322167.08 | 02-JAN-16:34 | 3964.85 | 199240.26 | 07-JAN-19:56 |
February | 112517.46 | 1090405.09 | 27-FEB-14:49 | 474.29 | 81129.14 | 16-FEB-17:20 |
March | 160044.62 | 1052166.93 | 02-MAR-14:44 | 1219.35 | 84717.99 | 30-MAR-15:00 |
April | 97225.24 | 1478953.83 | 06-APR-16:00 | 4251.48 | 148123.56 | 09-APR-07:11 |
May | 131147.07 | 3145220.70 | 19-MAY-14:05 | 2105.07 | 153602.99 | 07-MAY-09:40 |
June | 555540.65 | 3349162.73 | 29-JUN-15:30 | 10.00 | 37562.80 | 14-JUN-17:00 |
July | 887016.46 | 3393160.53 | 18-JUL-15:20 | 330.58 | 58653.91 | 08-JUL-04:00 |
August | 807206.44 | 3380000.89 | 24-AUG-14:30 | 559.23 | 83221.61 | 29-AUG-23:20 |
September | 296266.06 | 4820253.89 | 07-SEP-14:50 | 1183.08 | 135998.90 | 30-SEP-03:30 |
October | 184871.02 | 3131151.40 | 18-OCT-12:40 | 226.65 | 65252.45 | 03-OCT-12:59 |
November | 86344.97 | 1137221.20 | 03-NOV-13:25 | 5048.75 | 80085.23 | 15-NOV-19:30 |
December | 43522.08 | 518268.26 | 06-DEC-11:32 | 6301.80 | 133167.82 | 23-DEC-01:04 |
Annual Sum or Average | 281781.80 | 2147.98 | ||||
Minimum of Months | 339.43 | 322167.08 | 10.00 | 37562.80 | ||
Maximum of Months | 887016.46 | 4820253.89 | 6301.80 | 199240.26 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.983726E+10 | 0.64 | 23898.32 | 03-JAN-06:01 | 1.84 |
February | 0.893267E+10 | 0.61 | 23898.32 | 16-FEB-06:01 | 1.84 |
March | 0.114499E+11 | 0.66 | 23898.32 | 27-MAR-05:01 | 1.84 |
April | 0.123835E+11 | 0.67 | 23898.32 | 14-APR-05:01 | 1.83 |
May | 0.125180E+11 | 0.66 | 21423.96 | 06-MAY-05:01 | 1.75 |
June | 0.162569E+11 | 0.78 | 24899.84 | 21-JUN-04:11 | 1.85 |
July | 0.197387E+11 | 0.84 | 26880.50 | 19-JUL-04:11 | 1.91 |
August | 0.215319E+11 | 0.89 | 27136.90 | 07-AUG-15:10 | 1.93 |
September | 0.142372E+11 | 0.72 | 30369.57 | 05-SEP-04:11 | 2.02 |
October | 0.123616E+11 | 0.64 | 23898.32 | 11-OCT-05:01 | 1.84 |
November | 0.108740E+11 | 0.61 | 23898.32 | 10-NOV-06:01 | 1.84 |
December | 0.102747E+11 | 0.60 | 23281.86 | 21-DEC-06:01 | 1.82 |
Annual Sum or Average | 0.160396E+12 | 0.69 | |||
Minimum of Months | 0.893267E+10 | 0.60 | 21423.96 | 1.75 | |
Maximum of Months | 0.215319E+11 | 0.89 | 30369.57 | 2.02 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.108883E+12 | 0.75 | 136061.17 | 02-JAN-05:01 | 1.50 |
February | 0.923241E+11 | 0.68 | 137772.46 | 28-FEB-15:01 | 1.50 |
March | 0.110220E+12 | 0.69 | 154383.49 | 23-MAR-12:01 | 1.58 |
April | 0.104578E+12 | 0.64 | 234918.47 | 25-APR-05:01 | 1.89 |
May | 0.116646E+12 | 0.67 | 234300.64 | 16-MAY-05:02 | 1.88 |
June | 0.148879E+12 | 0.77 | 249742.15 | 16-JUN-05:01 | 1.93 |
July | 0.167084E+12 | 0.78 | 238277.23 | 17-JUL-16:00 | 1.88 |
August | 0.171310E+12 | 0.80 | 266033.01 | 18-AUG-05:01 | 1.98 |
September | 0.128094E+12 | 0.71 | 266033.01 | 21-SEP-05:01 | 1.99 |
October | 0.107597E+12 | 0.63 | 266033.01 | 17-OCT-05:01 | 1.99 |
November | 0.991752E+11 | 0.65 | 248012.81 | 04-NOV-05:01 | 1.93 |
December | 0.106805E+12 | 0.72 | 136061.17 | 04-DEC-06:01 | 1.50 |
Annual Sum or Average | 0.146160E+13 | 0.71 | |||
Minimum of Months | 0.923241E+11 | 0.63 | 136061.17 | 1.50 | |
Maximum of Months | 0.171310E+12 | 0.80 | 266033.01 | 1.99 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.130650E+11 | 0.72 | 13683.98 | 02-JAN-04:01 | 1.23 |
February | 0.109278E+11 | 0.66 | 13683.98 | 01-FEB-05:01 | 1.23 |
March | 0.116485E+11 | 0.64 | 13683.98 | 01-MAR-05:01 | 1.23 |
April | 0.962690E+10 | 0.53 | 13683.98 | 10-APR-04:21 | 1.23 |
May | 0.107863E+11 | 0.56 | 17496.88 | 19-MAY-15:40 | 1.35 |
June | 0.127522E+11 | 0.60 | 20781.54 | 01-JUN-05:01 | 1.45 |
July | 0.143939E+11 | 0.60 | 23099.32 | 17-JUL-16:00 | 1.52 |
August | 0.142561E+11 | 0.60 | 22053.32 | 10-AUG-15:00 | 1.49 |
September | 0.107210E+11 | 0.54 | 21209.68 | 05-SEP-05:02 | 1.47 |
October | 0.971328E+10 | 0.52 | 13683.98 | 02-OCT-04:11 | 1.22 |
November | 0.107041E+11 | 0.61 | 13683.98 | 01-NOV-05:01 | 1.23 |
December | 0.123718E+11 | 0.69 | 13683.98 | 01-DEC-05:01 | 1.23 |
Annual Sum or Average | 0.140967E+12 | 0.61 | |||
Minimum of Months | 0.962690E+10 | 0.52 | 13683.98 | 1.22 | |
Maximum of Months | 0.143939E+11 | 0.72 | 23099.32 | 1.52 |
Report: FanReportMonthly
For: CAV_BAS SZVAV FAN
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.378516E+10 | 0.48 | 17361.94 | 02-JAN-04:01 | 2.05 |
February | 0.374959E+10 | 0.49 | 17361.94 | 08-FEB-06:01 | 2.06 |
March | 0.507182E+10 | 0.55 | 17361.94 | 01-MAR-05:48 | 2.06 |
April | 0.615878E+10 | 0.56 | 17361.94 | 01-APR-05:03 | 2.06 |
May | 0.664193E+10 | 0.58 | 17361.94 | 01-MAY-05:02 | 2.06 |
June | 0.761123E+10 | 0.65 | 17361.94 | 01-JUN-04:11 | 2.05 |
July | 0.808921E+10 | 0.64 | 17361.94 | 01-JUL-04:11 | 2.04 |
August | 0.986680E+10 | 0.73 | 17361.94 | 01-AUG-04:11 | 2.05 |
September | 0.912486E+10 | 0.68 | 17361.94 | 01-SEP-04:11 | 2.05 |
October | 0.921229E+10 | 0.65 | 17361.94 | 02-OCT-04:11 | 2.06 |
November | 0.751409E+10 | 0.61 | 17361.94 | 01-NOV-04:11 | 2.06 |
December | 0.545586E+10 | 0.53 | 17361.94 | 01-DEC-06:01 | 2.07 |
Annual Sum or Average | 0.822816E+11 | 0.60 | |||
Minimum of Months | 0.374959E+10 | 0.48 | 17361.94 | 2.04 | |
Maximum of Months | 0.986680E+10 | 0.73 | 17361.94 | 2.07 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SYS11 FAN
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.298067E+11 | 0.58 | 11128.54 | 01-JAN-00:03 | 0.58 |
February | 0.481702E+11 | 0.71 | 37064.85 | 01-FEB-00:03 | 0.96 |
March | 0.645838E+11 | 0.77 | 37064.85 | 01-MAR-00:02 | 0.97 |
April | 0.908868E+11 | 0.94 | 37064.85 | 01-APR-00:02 | 0.97 |
May | 0.298362E+11 | 0.58 | 37064.85 | 31-MAY-23:03 | 0.96 |
June | 0.458967E+11 | 0.68 | 37064.85 | 01-JUN-00:03 | 0.96 |
July | 0.691438E+11 | 0.80 | 37064.85 | 01-JUL-00:10 | 0.96 |
August | 0.918309E+11 | 0.93 | 37064.85 | 01-AUG-00:10 | 0.96 |
September | 0.288763E+11 | 0.58 | 37064.85 | 30-SEP-23:03 | 0.96 |
October | 0.530607E+11 | 0.71 | 37064.85 | 01-OCT-00:02 | 0.97 |
November | 0.626920E+11 | 0.77 | 37064.85 | 01-NOV-00:02 | 0.97 |
December | 0.952857E+11 | 0.94 | 37064.85 | 01-DEC-00:05 | 0.97 |
Annual Sum or Average | 0.710070E+12 | 0.75 | |||
Minimum of Months | 0.288763E+11 | 0.58 | 11128.54 | 0.58 | |
Maximum of Months | 0.952857E+11 | 0.94 | 37064.85 | 0.97 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.400293E+10 | 1.61 | 1494.52 | 01-JAN-01:12 | 1.60 |
February | 0.361555E+10 | 1.61 | 1494.52 | 01-FEB-00:02 | 1.62 |
March | 0.400293E+10 | 1.61 | 1494.52 | 01-MAR-00:01 | 1.61 |
April | 0.387380E+10 | 1.61 | 1494.52 | 04-APR-23:45 | 1.61 |
May | 0.400293E+10 | 1.61 | 1494.52 | 22-MAY-03:50 | 1.60 |
June | 0.387380E+10 | 1.60 | 1494.52 | 01-JUN-00:03 | 1.61 |
July | 0.400293E+10 | 1.60 | 1494.52 | 01-JUL-00:21 | 1.60 |
August | 0.400293E+10 | 1.60 | 1494.52 | 01-AUG-19:10 | 1.60 |
September | 0.387380E+10 | 1.60 | 1494.52 | 12-SEP-07:36 | 1.60 |
October | 0.400293E+10 | 1.61 | 1494.52 | 01-OCT-00:01 | 1.61 |
November | 0.387380E+10 | 1.61 | 1494.52 | 01-NOV-00:05 | 1.62 |
December | 0.400293E+10 | 1.61 | 1494.52 | 02-DEC-03:34 | 1.61 |
Annual Sum or Average | 0.471312E+11 | 1.61 | |||
Minimum of Months | 0.361555E+10 | 1.60 | 1494.52 | 1.60 | |
Maximum of Months | 0.400293E+10 | 1.61 | 1494.52 | 1.62 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.385555E+11 | 1.61 | 14394.98 | 01-JAN-14:30 | 1.60 |
February | 0.348243E+11 | 1.61 | 14394.98 | 02-FEB-07:56 | 1.62 |
March | 0.385555E+11 | 1.61 | 14394.98 | 22-MAR-17:49 | 1.61 |
April | 0.373118E+11 | 1.61 | 14394.98 | 02-APR-10:56 | 1.62 |
May | 0.385555E+11 | 1.61 | 14394.98 | 04-MAY-10:02 | 1.61 |
June | 0.373118E+11 | 1.60 | 14394.98 | 01-JUN-02:12 | 1.61 |
July | 0.385555E+11 | 1.60 | 14394.98 | 16-JUL-19:08 | 1.60 |
August | 0.385555E+11 | 1.60 | 14394.98 | 02-AUG-01:03 | 1.60 |
September | 0.373118E+11 | 1.60 | 14394.98 | 03-SEP-10:37 | 1.60 |
October | 0.385555E+11 | 1.61 | 14394.98 | 03-OCT-06:38 | 1.61 |
November | 0.373118E+11 | 1.61 | 14394.98 | 01-NOV-00:06 | 1.62 |
December | 0.385555E+11 | 1.61 | 14394.98 | 01-DEC-19:00 | 1.61 |
Annual Sum or Average | 0.453960E+12 | 1.61 | |||
Minimum of Months | 0.348243E+11 | 1.60 | 14394.98 | 1.60 | |
Maximum of Months | 0.385555E+11 | 1.61 | 14394.98 | 1.62 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.397155E+10 | 1.61 | 1482.81 | 02-JAN-09:30 | 1.60 |
February | 0.358721E+10 | 1.61 | 1482.81 | 01-FEB-00:25 | 1.62 |
March | 0.397155E+10 | 1.61 | 1482.81 | 01-MAR-00:02 | 1.61 |
April | 0.384344E+10 | 1.61 | 1482.81 | 01-APR-00:17 | 1.61 |
May | 0.397155E+10 | 1.61 | 1482.81 | 01-MAY-07:20 | 1.62 |
June | 0.384344E+10 | 1.60 | 1482.81 | 01-JUN-01:45 | 1.61 |
July | 0.397155E+10 | 1.60 | 1482.81 | 01-JUL-00:29 | 1.60 |
August | 0.397155E+10 | 1.60 | 1482.81 | 01-AUG-00:50 | 1.60 |
September | 0.384344E+10 | 1.60 | 1482.81 | 01-SEP-00:20 | 1.60 |
October | 0.397155E+10 | 1.61 | 1482.81 | 01-OCT-01:01 | 1.61 |
November | 0.384344E+10 | 1.61 | 1482.81 | 01-NOV-00:31 | 1.62 |
December | 0.397155E+10 | 1.61 | 1482.81 | 01-DEC-00:16 | 1.62 |
Annual Sum or Average | 0.467618E+11 | 1.61 | |||
Minimum of Months | 0.358721E+10 | 1.60 | 1482.81 | 1.60 | |
Maximum of Months | 0.397155E+10 | 1.61 | 1482.81 | 1.62 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.105186E+10 | 0.946670E+09 | 5670.54 | 23-JAN-06:01 | 5103.49 | 5103.49 | 53.58 | 25.04 |
February | 0.498524E+09 | 0.448671E+09 | 5673.74 | 06-FEB-06:02 | 5106.36 | 5106.36 | 54.27 | 25.04 |
March | 0.322095E+09 | 0.289886E+09 | 4847.98 | 06-MAR-06:01 | 4363.19 | 4363.19 | 56.68 | 22.79 |
April | 0.114922E+09 | 0.103430E+09 | 3644.08 | 15-APR-05:01 | 3279.67 | 3279.67 | 44.11 | 19.04 |
May | 84334728.54 | 75901255.69 | 3712.03 | 08-MAY-05:01 | 3340.82 | 3340.82 | 50.41 | 19.23 |
June | 13349935.26 | 12014941.73 | 3466.48 | 17-JUN-05:01 | 3119.83 | 3119.83 | 37.39 | 18.43 |
July | 2400956.75 | 2160861.07 | 465.72 | 08-JUL-05:01 | 419.14 | 419.14 | 24.96 | 2.79 |
August | 8523104.45 | 7670794.01 | 3034.93 | 18-AUG-05:01 | 2731.44 | 2731.44 | 33.27 | 16.75 |
September | 47542565.83 | 42788309.25 | 3507.40 | 20-SEP-05:01 | 3156.66 | 3156.66 | 40.38 | 18.57 |
October | 0.112808E+09 | 0.101527E+09 | 3640.83 | 11-OCT-05:01 | 3276.75 | 3276.75 | 42.58 | 19.04 |
November | 0.296122E+09 | 0.266510E+09 | 5083.89 | 28-NOV-06:01 | 4575.50 | 4575.50 | 53.33 | 23.49 |
December | 0.632164E+09 | 0.568947E+09 | 5655.61 | 04-DEC-06:01 | 5090.05 | 5090.05 | 50.35 | 25.04 |
Annual Sum or Average | 0.318464E+10 | 0.286618E+10 | ||||||
Minimum of Months | 2400956.75 | 2160861.07 | 465.72 | 419.14 | 419.14 | 24.96 | 2.79 | |
Maximum of Months | 0.105186E+10 | 0.946670E+09 | 5673.74 | 5106.36 | 5106.36 | 56.68 | 25.04 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 24319747.21 | 21887772.49 | 540.19 | 18-JAN-06:01 | 486.17 | 486.17 | 6.82 | 4.67 |
February | 0.149271E+10 | 0.134344E+10 | 3639.74 | 26-FEB-14:51 | 3275.77 | 3275.77 | 9.43 | 32.34 |
March | 0.253164E+10 | 0.227847E+10 | 3548.84 | 02-MAR-14:42 | 3193.96 | 3193.96 | 8.60 | 31.57 |
April | 0.223763E+10 | 0.201387E+10 | 3352.32 | 11-APR-13:37 | 3017.09 | 3017.09 | 9.51 | 29.90 |
May | 0.814825E+09 | 0.733343E+09 | 6180.28 | 19-MAY-12:50 | 5562.25 | 5562.25 | 8.33 | 51.30 |
June | 0.352192E+10 | 0.316973E+10 | 12419.60 | 22-JUN-05:01 | 11177.64 | 11177.64 | 9.47 | 82.23 |
July | 0.549284E+10 | 0.494356E+10 | 15316.88 | 19-JUL-04:11 | 13785.19 | 13785.19 | 10.71 | 92.36 |
August | 0.496797E+10 | 0.447117E+10 | 9104.70 | 07-AUG-14:05 | 8194.23 | 8194.23 | 6.73 | 67.89 |
September | 0.170732E+10 | 0.153658E+10 | 7166.28 | 01-SEP-12:05 | 6449.66 | 6449.66 | 7.67 | 57.43 |
October | 0.207161E+10 | 0.186445E+10 | 3827.86 | 02-OCT-13:14 | 3445.07 | 3445.07 | 9.01 | 33.91 |
November | 0.255853E+10 | 0.230268E+10 | 3960.74 | 03-NOV-13:24 | 3564.67 | 3564.67 | 8.24 | 35.00 |
December | 0.257134E+10 | 0.231421E+10 | 2320.06 | 12-DEC-05:01 | 2088.05 | 2088.05 | 9.63 | 20.76 |
Annual Sum or Average | 0.299926E+11 | 0.269934E+11 | ||||||
Minimum of Months | 24319747.21 | 21887772.49 | 540.19 | 486.17 | 486.17 | 6.73 | 4.67 | |
Maximum of Months | 0.549284E+10 | 0.494356E+10 | 15316.88 | 13785.19 | 13785.19 | 10.71 | 92.36 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.425396E+10 | 0.382856E+10 | 10945.92 | 01-JAN-00:03 | 9851.33 | 9851.33 | 6.74 | 57.54 |
February | 0.844062E+10 | 0.759655E+10 | 10945.92 | 01-FEB-00:03 | 9851.33 | 9851.33 | 6.96 | 57.54 |
March | 0.157565E+11 | 0.141809E+11 | 10945.92 | 01-MAR-00:04 | 9851.33 | 9851.33 | 8.16 | 57.54 |
April | 0.226927E+11 | 0.204234E+11 | 10945.92 | 01-APR-00:02 | 9851.33 | 9851.33 | 10.68 | 57.54 |
May | 0.904971E+10 | 0.814474E+10 | 10945.92 | 01-MAY-00:37 | 9851.33 | 9851.33 | 6.79 | 57.54 |
June | 0.172026E+11 | 0.154823E+11 | 10945.92 | 01-JUN-00:03 | 9851.33 | 9851.33 | 8.18 | 57.54 |
July | 0.239612E+11 | 0.215651E+11 | 10945.92 | 01-JUL-00:10 | 9851.33 | 9851.33 | 10.28 | 57.54 |
August | 0.247642E+11 | 0.222878E+11 | 10945.92 | 01-AUG-00:10 | 9851.33 | 9851.33 | 10.14 | 57.54 |
September | 0.123636E+11 | 0.111272E+11 | 10945.92 | 01-SEP-00:10 | 9851.33 | 9851.33 | 7.89 | 57.54 |
October | 0.119919E+11 | 0.107927E+11 | 10945.92 | 01-OCT-00:02 | 9851.33 | 9851.33 | 8.29 | 57.54 |
November | 0.220130E+11 | 0.198117E+11 | 10945.92 | 01-NOV-00:02 | 9851.33 | 9851.33 | 7.85 | 57.54 |
December | 0.257106E+11 | 0.231395E+11 | 10945.92 | 01-DEC-00:05 | 9851.33 | 9851.33 | 10.61 | 57.54 |
Annual Sum or Average | 0.198201E+12 | 0.178381E+12 | ||||||
Minimum of Months | 0.425396E+10 | 0.382856E+10 | 10945.92 | 9851.33 | 9851.33 | 6.74 | 57.54 | |
Maximum of Months | 0.257106E+11 | 0.231395E+11 | 10945.92 | 9851.33 | 9851.33 | 10.68 | 57.54 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 6.74 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 6.74 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 7.97 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 10.68 | 0.00 |
May | 0.157621E+09 | 0.141859E+09 | 10945.92 | 19-MAY-12:20 | 9851.33 | 9851.33 | 13.82 | 28.77 |
June | 0.238074E+10 | 0.214266E+10 | 10945.92 | 05-JUN-14:00 | 9851.33 | 9851.33 | 12.69 | 28.77 |
July | 0.517257E+10 | 0.465531E+10 | 10945.92 | 03-JUL-10:05 | 9851.33 | 9851.33 | 10.28 | 57.54 |
August | 0.510561E+10 | 0.459505E+10 | 10945.92 | 01-AUG-12:05 | 9851.33 | 9851.33 | 10.26 | 57.54 |
September | 0.971998E+09 | 0.874798E+09 | 10945.92 | 01-SEP-10:40 | 9851.33 | 9851.33 | 13.19 | 28.77 |
October | 0.127848E+09 | 0.115063E+09 | 10945.92 | 18-OCT-12:30 | 9851.33 | 9851.33 | 13.82 | 28.77 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 7.85 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 10.61 | 0.00 |
Annual Sum or Average | 0.139164E+11 | 0.125248E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.74 | 0.00 | |
Maximum of Months | 0.517257E+10 | 0.465531E+10 | 10945.92 | 9851.33 | 9851.33 | 13.82 | 57.54 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 56.89 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 56.88 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 56.88 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 56.67 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 57.20 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:01 | 16.86 | 16.86 | 57.27 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:01 | 16.86 | 16.86 | 57.43 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:01 | 16.86 | 16.86 | 57.48 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:01 | 16.86 | 16.86 | 57.49 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:01 | 16.86 | 16.86 | 57.47 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 57.32 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 57.14 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.67 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.49 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.108767E+11 | 0.978902E+10 | 28261.00 | 02-JAN-16:34 | 25434.90 | 25434.90 | 22.05 | 81.29 |
February | 0.217652E+11 | 0.195887E+11 | 28307.01 | 27-FEB-14:49 | 25476.31 | 25476.31 | 24.31 | 81.29 |
March | 0.406384E+11 | 0.365745E+11 | 28304.72 | 02-MAR-14:44 | 25474.25 | 25474.25 | 24.20 | 81.29 |
April | 0.585275E+11 | 0.526747E+11 | 28331.86 | 06-APR-16:00 | 25498.67 | 25498.67 | 25.45 | 81.29 |
May | 0.236787E+11 | 0.213109E+11 | 56677.02 | 19-MAY-14:05 | 51009.32 | 51009.32 | 25.73 | 162.58 |
June | 0.491231E+11 | 0.442108E+11 | 56691.27 | 29-JUN-15:30 | 51022.15 | 51022.15 | 26.03 | 162.58 |
July | 0.737026E+11 | 0.663324E+11 | 56694.35 | 18-JUL-15:20 | 51024.92 | 51024.92 | 26.09 | 162.58 |
August | 0.755448E+11 | 0.679903E+11 | 56693.43 | 24-AUG-14:30 | 51024.09 | 51024.09 | 26.07 | 162.58 |
September | 0.337589E+11 | 0.303830E+11 | 56794.30 | 07-SEP-14:50 | 51114.87 | 51114.87 | 28.19 | 162.58 |
October | 0.311413E+11 | 0.280272E+11 | 56676.04 | 18-OCT-12:40 | 51008.43 | 51008.43 | 25.71 | 162.58 |
November | 0.566834E+11 | 0.510150E+11 | 28309.82 | 03-NOV-13:25 | 25478.84 | 25478.84 | 24.45 | 81.29 |
December | 0.662396E+11 | 0.596157E+11 | 28272.74 | 06-DEC-11:32 | 25445.46 | 25445.46 | 22.63 | 81.29 |
Annual Sum or Average | 0.541680E+12 | 0.487512E+12 | ||||||
Minimum of Months | 0.108767E+11 | 0.978902E+10 | 28261.00 | 25434.90 | 25434.90 | 22.05 | 81.29 | |
Maximum of Months | 0.755448E+11 | 0.679903E+11 | 56794.30 | 51114.87 | 51114.87 | 28.19 | 162.58 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 24.89 | 24.89 | 377563.06 | 3350463.25 | 02-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 30.88 | 82.20 | 215289.02 | 3329789.19 | 28-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 25.11 | 25.11 | 125406.04 | 3560797.79 | 01-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:02 | 26.64 | 26.64 | 47145.81 | 3278903.32 | 22-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.24 | 76.64 | 31982.51 | 3220045.99 | 09-MAY-04:01 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 22.16 | 22.16 | 5419.04 | 2788322.64 | 17-JUN-04:11 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.22 | 21.22 | 957.72 | 517010.18 | 08-JUL-05:01 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.42 | 20.42 | 3317.28 | 2452347.83 | 18-AUG-05:01 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 20.48 | 20.48 | 18794.52 | 2871111.05 | 20-SEP-04:11 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 21.79 | 21.79 | 43710.78 | 3222882.63 | 05-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 26.78 | 26.78 | 118384.31 | 3343425.15 | 06-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 29.41 | 77.60 | 247686.38 | 3388782.67 | 18-DEC-05:11 |
Annual Sum or Average | 0.00 | 102656.82 | ||||||
Minimum of Months | 0.00 | 0.00 | 20.42 | 20.42 | 957.72 | 517010.18 | ||
Maximum of Months | 0.00 | 0.00 | 30.88 | 82.20 | 377563.06 | 3560797.79 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 2204.98 | 402979.66 | 02-JAN-16:25 | 8.37 | 6.70 | 117638.19 | 840339.53 | 22-JAN-15:10 |
February | 91538.38 | 1012268.10 | 27-FEB-14:46 | 10.90 | 6.70 | 53434.60 | 695107.65 | 28-FEB-23:12 |
March | 134499.59 | 1047031.63 | 01-MAR-14:50 | 11.04 | 6.70 | 23069.49 | 649873.36 | 31-MAR-23:13 |
April | 138531.62 | 1293012.84 | 06-APR-16:00 | 12.07 | 6.70 | 13763.28 | 822308.08 | 30-APR-23:43 |
May | 109515.74 | 1973554.42 | 19-MAY-14:05 | 10.79 | 6.70 | 182254.55 | 840127.61 | 07-MAY-03:20 |
June | 428554.99 | 2252744.63 | 21-JUN-12:05 | 11.37 | 6.70 | 56720.45 | 808575.27 | 25-JUN-22:21 |
July | 676573.35 | 2697991.40 | 10-JUL-12:05 | 12.30 | 6.70 | 31201.61 | 727076.32 | 23-JUL-06:10 |
August | 625802.20 | 2680594.69 | 05-AUG-17:06 | 12.26 | 6.70 | 15048.64 | 486545.19 | 10-AUG-02:20 |
September | 237820.48 | 2570792.28 | 27-SEP-14:05 | 12.03 | 6.70 | 212523.04 | 840116.72 | 17-SEP-12:47 |
October | 150316.35 | 2504335.33 | 18-OCT-13:04 | 11.90 | 6.70 | 91573.82 | 704805.26 | 29-OCT-20:32 |
November | 118422.16 | 1076162.88 | 03-NOV-13:22 | 11.16 | 6.70 | 15403.00 | 623278.47 | 28-NOV-01:30 |
December | 122144.00 | 593788.27 | 06-DEC-11:30 | 10.51 | 8.05 | 5716.83 | 276020.40 | 06-DEC-01:37 |
Annual Sum or Average | 237577.25 | 68246.74 | ||||||
Minimum of Months | 2204.98 | 402979.66 | 8.37 | 6.70 | 5716.83 | 276020.40 | ||
Maximum of Months | 676573.35 | 2697991.40 | 12.30 | 8.05 | 212523.04 | 840339.53 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 863.54 | 69459.03 | 18-JAN-06:01 | 10.25 | 6.74 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 104527.20 | 1518302.74 | 27-FEB-15:08 | 19.16 | 6.85 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 152465.11 | 1172268.81 | 02-MAR-15:02 | 15.61 | 7.15 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 220697.24 | 1309487.83 | 06-APR-16:00 | 21.15 | 6.70 | 0.00 | 0.00 | 01-APR-00:02 |
May | 118386.06 | 1812041.43 | 19-MAY-12:50 | 15.14 | 8.60 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 454544.07 | 1979819.31 | 29-JUN-15:00 | 22.29 | 6.70 | 0.00 | 0.00 | 01-JUN-00:01 |
July | 713078.62 | 3684616.50 | 19-JUL-04:11 | 16.23 | 12.07 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 661744.30 | 2445229.10 | 05-AUG-17:03 | 20.12 | 6.75 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 248082.26 | 2564657.92 | 07-SEP-14:50 | 19.46 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 176628.30 | 1759649.14 | 18-OCT-13:06 | 21.04 | 6.75 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 189445.56 | 1325762.57 | 03-NOV-14:04 | 16.14 | 6.70 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 221197.75 | 601206.66 | 26-DEC-05:50 | 13.62 | 10.07 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 273109.89 | 0.00 | ||||||
Minimum of Months | 863.54 | 69459.03 | 10.25 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 713078.62 | 3684616.50 | 22.29 | 12.07 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.91 | 57.91 | 16135.05 | 57876.86 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 57.29 | 57.29 | 16514.11 | 58183.80 | 17-FEB-12:38 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 57.28 | 57.28 | 17371.52 | 58080.53 | 01-MAR-12:44 |
April | 0.00 | 0.00 | 01-APR-00:02 | 57.35 | 57.35 | 15686.02 | 56502.29 | 03-APR-11:46 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.99 | 57.99 | 15336.03 | 53999.83 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 57.63 | 57.63 | 14754.70 | 50705.40 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.77 | 57.77 | 12894.00 | 47668.69 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.86 | 57.86 | 13810.05 | 45986.73 | 01-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.87 | 57.87 | 13115.78 | 47092.14 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 57.80 | 57.80 | 13695.34 | 49894.98 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 57.67 | 57.67 | 14752.91 | 53085.37 | 30-NOV-12:58 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 57.52 | 57.52 | 15068.81 | 55890.46 | 29-DEC-12:18 |
Annual Sum or Average | 0.00 | 14918.66 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.28 | 57.28 | 12894.00 | 45986.73 | ||
Maximum of Months | 0.00 | 0.00 | 57.99 | 57.99 | 17371.52 | 58183.80 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 339.43 | 322167.08 | 02-JAN-16:34 | 22.05 | 21.10 | 3964.85 | 199240.26 | 07-JAN-19:56 |
February | 112517.46 | 1090405.09 | 27-FEB-14:49 | 24.31 | 21.10 | 474.29 | 81129.14 | 16-FEB-17:20 |
March | 160044.62 | 1052166.93 | 02-MAR-14:44 | 24.20 | 21.10 | 1219.35 | 84717.99 | 30-MAR-15:00 |
April | 97225.24 | 1478953.83 | 06-APR-16:00 | 25.45 | 21.10 | 4251.48 | 148123.56 | 09-APR-07:11 |
May | 131147.07 | 3145220.70 | 19-MAY-14:05 | 25.73 | 21.10 | 2105.07 | 153602.99 | 07-MAY-09:40 |
June | 555540.65 | 3349162.73 | 29-JUN-15:30 | 26.03 | 21.10 | 10.00 | 37562.80 | 14-JUN-17:00 |
July | 887016.46 | 3393160.53 | 18-JUL-15:20 | 26.09 | 21.72 | 330.58 | 58653.91 | 08-JUL-04:00 |
August | 807206.44 | 3380000.89 | 24-AUG-14:30 | 26.07 | 21.10 | 559.23 | 83221.61 | 29-AUG-23:20 |
September | 296266.06 | 4820253.89 | 07-SEP-14:50 | 28.19 | 23.89 | 1183.08 | 135998.90 | 30-SEP-03:30 |
October | 184871.02 | 3131151.40 | 18-OCT-12:40 | 25.71 | 21.10 | 226.65 | 65252.45 | 03-OCT-12:59 |
November | 86344.97 | 1137221.20 | 03-NOV-13:25 | 24.45 | 21.10 | 5048.75 | 80085.23 | 15-NOV-19:30 |
December | 43522.08 | 518268.26 | 06-DEC-11:32 | 22.63 | 21.10 | 6301.80 | 133167.82 | 23-DEC-01:04 |
Annual Sum or Average | 281781.80 | 2147.98 | ||||||
Minimum of Months | 339.43 | 322167.08 | 22.05 | 21.10 | 10.00 | 37562.80 | ||
Maximum of Months | 887016.46 | 4820253.89 | 28.19 | 23.89 | 6301.80 | 199240.26 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.500125E+11 | 0.00 | 0.00 | 0.983726E+10 | 0.00 | 0.00 |
February | 0.247594E+11 | 0.00 | 0.731142E+09 | 0.893267E+10 | 0.00 | 0.00 |
March | 0.118557E+11 | 0.00 | 46009654.44 | 0.114499E+11 | 0.00 | 0.00 |
April | 0.241556E+10 | 0.00 | 0.763361E+10 | 0.123835E+11 | 0.00 | 0.00 |
May | 0.190005E+10 | 0.00 | 0.220150E+11 | 0.125180E+11 | 0.00 | 0.00 |
June | 0.216027E+09 | 0.00 | 0.679616E+11 | 0.162569E+11 | 0.00 | 0.00 |
July | 3812222.39 | 0.00 | 0.117065E+12 | 0.197387E+11 | 0.00 | 0.00 |
August | 38466636.91 | 0.00 | 0.107083E+12 | 0.215319E+11 | 0.00 | 0.00 |
September | 0.780115E+09 | 0.00 | 0.463970E+11 | 0.142372E+11 | 0.00 | 0.00 |
October | 0.232914E+10 | 0.00 | 0.125692E+11 | 0.123616E+11 | 0.00 | 0.00 |
November | 0.764446E+10 | 0.00 | 0.765204E+09 | 0.108740E+11 | 0.00 | 0.00 |
December | 0.233739E+11 | 0.00 | 102335.07 | 0.102747E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.125329E+12 | 0.00 | 0.382267E+12 | 0.160396E+12 | 0.00 | 0.00 |
Minimum of Months | 3812222.39 | 0.00 | 0.00 | 0.893267E+10 | 0.00 | 0.00 |
Maximum of Months | 0.500125E+11 | 0.00 | 0.117065E+12 | 0.215319E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.820125E+12 | 0.00 | 96972.77 | 0.108883E+12 | 0.00 | 0.00 |
February | 0.419531E+12 | 0.00 | 0.106124E+11 | 0.923241E+11 | 0.00 | 0.00 |
March | 0.266174E+12 | 0.00 | 0.111127E+11 | 0.110220E+12 | 0.00 | 0.00 |
April | 0.948063E+11 | 0.00 | 0.702122E+11 | 0.104578E+12 | 0.00 | 0.00 |
May | 0.654943E+11 | 0.00 | 0.209437E+12 | 0.116646E+12 | 0.00 | 0.00 |
June | 0.963315E+10 | 0.00 | 0.622458E+12 | 0.148879E+12 | 0.00 | 0.00 |
July | 0.133632E+10 | 0.00 | 0.101660E+13 | 0.167084E+12 | 0.00 | 0.00 |
August | 0.588270E+10 | 0.00 | 0.891082E+12 | 0.171310E+12 | 0.00 | 0.00 |
September | 0.370793E+11 | 0.00 | 0.426758E+12 | 0.128094E+12 | 0.00 | 0.00 |
October | 0.889899E+11 | 0.00 | 0.133795E+12 | 0.107597E+12 | 0.00 | 0.00 |
November | 0.243345E+12 | 0.00 | 0.116953E+11 | 0.991752E+11 | 0.00 | 0.00 |
December | 0.537002E+12 | 0.00 | 262511.42 | 0.106805E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.258940E+13 | 0.00 | 0.340377E+13 | 0.146160E+13 | 0.00 | 0.00 |
Minimum of Months | 0.133632E+10 | 0.00 | 96972.77 | 0.923241E+11 | 0.00 | 0.00 |
Maximum of Months | 0.820125E+12 | 0.00 | 0.101660E+13 | 0.171310E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.143779E+12 | 0.00 | 4108511.06 | 0.130650E+11 | 0.00 | 0.00 |
February | 0.791070E+11 | 0.00 | 0.573729E+09 | 0.109278E+11 | 0.00 | 0.00 |
March | 0.594943E+11 | 0.00 | 17457434.51 | 0.116485E+11 | 0.00 | 0.00 |
April | 0.255455E+11 | 0.00 | 0.620092E+10 | 0.962690E+10 | 0.00 | 0.00 |
May | 0.187739E+11 | 0.00 | 0.225257E+11 | 0.107863E+11 | 0.00 | 0.00 |
June | 0.425524E+10 | 0.00 | 0.722633E+11 | 0.127522E+11 | 0.00 | 0.00 |
July | 0.123900E+10 | 0.00 | 0.119541E+12 | 0.143939E+11 | 0.00 | 0.00 |
August | 0.298716E+10 | 0.00 | 0.100582E+12 | 0.142561E+11 | 0.00 | 0.00 |
September | 0.110271E+11 | 0.00 | 0.454381E+11 | 0.107210E+11 | 0.00 | 0.00 |
October | 0.261171E+11 | 0.00 | 0.102207E+11 | 0.971328E+10 | 0.00 | 0.00 |
November | 0.573546E+11 | 0.00 | 0.577939E+09 | 0.107041E+11 | 0.00 | 0.00 |
December | 0.106508E+12 | 0.00 | 10539264.19 | 0.123718E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.536188E+12 | 0.00 | 0.377956E+12 | 0.140967E+12 | 0.00 | 0.00 |
Minimum of Months | 0.123900E+10 | 0.00 | 4108511.06 | 0.962690E+10 | 0.00 | 0.00 |
Maximum of Months | 0.143779E+12 | 0.00 | 0.119541E+12 | 0.143939E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.298840E+10 | 0.00 | 0.214667E+10 | 0.378516E+10 | 0.00 | 0.00 |
February | 0.402996E+09 | 0.00 | 0.226954E+10 | 0.374959E+10 | 0.00 | 0.00 |
March | 80675034.81 | 0.00 | 0.381141E+10 | 0.507182E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.794048E+10 | 0.615878E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.171542E+11 | 0.664193E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.367914E+11 | 0.761123E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.544491E+11 | 0.808921E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.533960E+11 | 0.986680E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.334159E+11 | 0.912486E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.182928E+11 | 0.921229E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.890418E+10 | 0.751409E+10 | 0.00 | 0.00 |
December | 20871873.34 | 0.00 | 0.374433E+10 | 0.545586E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.349294E+10 | 0.00 | 0.242316E+12 | 0.822816E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.214667E+10 | 0.374959E+10 | 0.00 | 0.00 |
Maximum of Months | 0.298840E+10 | 0.00 | 0.544491E+11 | 0.986680E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 3103156.31 | 0.153641E+12 | 0.00 | 46.07 |
February | 0.00 | 0.00 | 0.198821E+12 | 0.166075E+12 | 0.00 | 43.86 |
March | 0.00 | 0.00 | 0.329608E+12 | 0.244048E+12 | 0.00 | 66.76 |
April | 0.00 | 0.00 | 0.244862E+12 | 0.325669E+12 | 0.00 | 87.34 |
May | 0.00 | 0.00 | 0.934275E+10 | 0.157940E+12 | 0.00 | 47.65 |
June | 0.00 | 0.00 | 0.261857E+12 | 0.114199E+12 | 0.00 | 25.41 |
July | 0.00 | 0.00 | 0.432051E+12 | 0.126859E+12 | 0.00 | 21.47 |
August | 0.00 | 0.00 | 0.459329E+12 | 0.223148E+12 | 0.00 | 48.85 |
September | 0.00 | 0.00 | 0.335645E+11 | 0.111707E+12 | 0.00 | 30.81 |
October | 0.00 | 0.00 | 0.213671E+12 | 0.180848E+12 | 0.00 | 47.54 |
November | 0.00 | 0.00 | 0.263558E+12 | 0.255067E+12 | 0.00 | 71.56 |
December | 0.00 | 0.00 | 0.298394E+12 | 0.346810E+12 | 0.00 | 93.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.274506E+13 | 0.240601E+13 | 0.00 | 630.89 |
Minimum of Months | 0.00 | 0.00 | 3103156.31 | 0.111707E+12 | 0.00 | 21.47 |
Maximum of Months | 0.00 | 0.00 | 0.459329E+12 | 0.346810E+12 | 0.00 | 93.57 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.537352E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.633066E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.831935E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.945702E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.631530E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.753367E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.914418E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.103931E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.624884E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.746050E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.815658E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.929115E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.940239E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.537352E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.103931E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.449965E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.544755E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.721641E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.809414E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.556443E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.668262E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.803166E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.899977E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.550919E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.649332E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.697867E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.778980E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.813072E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.449965E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.899977E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.434644E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.535444E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.744811E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.860500E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.566215E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.719899E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.883262E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.987972E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.566255E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.656587E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.713174E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.811409E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.848017E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.434644E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.987972E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.983726E+10 | 0.00 | 0.500125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.893267E+10 | 0.731142E+09 | 0.247594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114499E+11 | 46009654.44 | 0.118557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123835E+11 | 0.763361E+10 | 0.241556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125180E+11 | 0.220150E+11 | 0.190005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162569E+11 | 0.679616E+11 | 0.216027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.197387E+11 | 0.117065E+12 | 3812222.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.215319E+11 | 0.107083E+12 | 38466636.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142372E+11 | 0.463970E+11 | 0.780115E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123616E+11 | 0.125692E+11 | 0.232914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108740E+11 | 0.765204E+09 | 0.764446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102747E+11 | 102335.07 | 0.233739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160396E+12 | 0.382267E+12 | 0.125329E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.893267E+10 | 0.00 | 3812222.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.215319E+11 | 0.117065E+12 | 0.500125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.108883E+12 | 96972.77 | 0.820125E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.923241E+11 | 0.106124E+11 | 0.419531E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110220E+12 | 0.111127E+11 | 0.266174E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104578E+12 | 0.702122E+11 | 0.948063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116646E+12 | 0.209437E+12 | 0.654943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148879E+12 | 0.622458E+12 | 0.963315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167084E+12 | 0.101660E+13 | 0.133632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171310E+12 | 0.891082E+12 | 0.588270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128094E+12 | 0.426758E+12 | 0.370793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107597E+12 | 0.133795E+12 | 0.889899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.991752E+11 | 0.116953E+11 | 0.243345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106805E+12 | 262511.42 | 0.537002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146160E+13 | 0.340377E+13 | 0.258940E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.923241E+11 | 96972.77 | 0.133632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171310E+12 | 0.101660E+13 | 0.820125E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.130650E+11 | 4108511.06 | 0.143779E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109278E+11 | 0.573729E+09 | 0.791070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116485E+11 | 17457434.51 | 0.594943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.962690E+10 | 0.620092E+10 | 0.255455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107863E+11 | 0.225257E+11 | 0.187739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127522E+11 | 0.722633E+11 | 0.425524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143939E+11 | 0.119541E+12 | 0.123900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142561E+11 | 0.100582E+12 | 0.298716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107210E+11 | 0.454381E+11 | 0.110271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.971328E+10 | 0.102207E+11 | 0.261171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107041E+11 | 0.577939E+09 | 0.573546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123718E+11 | 10539264.19 | 0.106508E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140967E+12 | 0.377956E+12 | 0.536188E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.962690E+10 | 4108511.06 | 0.123900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143939E+11 | 0.119541E+12 | 0.143779E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.378516E+10 | 0.214667E+10 | 0.298840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.374959E+10 | 0.226954E+10 | 0.402996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.507182E+10 | 0.381141E+10 | 80675034.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.615878E+10 | 0.794048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.664193E+10 | 0.171542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.761123E+10 | 0.367914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.808921E+10 | 0.544491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.986680E+10 | 0.533960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.912486E+10 | 0.334159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.921229E+10 | 0.182928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.751409E+10 | 0.890418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.545586E+10 | 0.374433E+10 | 20871873.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.822816E+11 | 0.242316E+12 | 0.349294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.374959E+10 | 0.214667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.986680E+10 | 0.544491E+11 | 0.298840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.298067E+11 | 3103156.31 | 0.00 | 0.00 | 0.00 | 0.123280E+12 | 0.00 | 0.00 |
February | 0.481702E+11 | 0.198821E+12 | 0.00 | 0.00 | 0.00 | 0.117376E+12 | 0.00 | 0.00 |
March | 0.645838E+11 | 0.329608E+12 | 0.00 | 0.00 | 0.00 | 0.178660E+12 | 0.00 | 0.00 |
April | 0.908868E+11 | 0.244862E+12 | 0.00 | 0.00 | 0.00 | 0.233730E+12 | 0.00 | 0.00 |
May | 0.298362E+11 | 0.934275E+10 | 0.00 | 0.00 | 0.00 | 0.127529E+12 | 0.00 | 0.00 |
June | 0.458967E+11 | 0.261857E+12 | 0.00 | 0.00 | 0.00 | 0.679962E+11 | 0.00 | 0.00 |
July | 0.691438E+11 | 0.432051E+12 | 0.00 | 0.00 | 0.00 | 0.574560E+11 | 0.00 | 0.00 |
August | 0.918309E+11 | 0.459329E+12 | 0.00 | 0.00 | 0.00 | 0.130729E+12 | 0.00 | 0.00 |
September | 0.288763E+11 | 0.335645E+11 | 0.00 | 0.00 | 0.00 | 0.824593E+11 | 0.00 | 0.00 |
October | 0.530607E+11 | 0.213671E+12 | 0.00 | 0.00 | 0.00 | 0.127215E+12 | 0.00 | 0.00 |
November | 0.626920E+11 | 0.263558E+12 | 0.00 | 0.00 | 0.00 | 0.191513E+12 | 0.00 | 0.00 |
December | 0.952857E+11 | 0.298394E+12 | 0.00 | 0.00 | 0.00 | 0.250397E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.710070E+12 | 0.274506E+13 | 0.00 | 0.00 | 0.00 | 0.168834E+13 | 0.00 | 0.00 |
Minimum of Months | 0.288763E+11 | 3103156.31 | 0.00 | 0.00 | 0.00 | 0.574560E+11 | 0.00 | 0.00 |
Maximum of Months | 0.952857E+11 | 0.459329E+12 | 0.00 | 0.00 | 0.00 | 0.250397E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.400293E+10 | 0.441468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.361555E+10 | 0.943480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.400293E+10 | 0.161653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.387380E+10 | 0.217185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.400293E+10 | 0.763678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.387380E+10 | 0.128085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.400293E+10 | 0.187747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.400293E+10 | 0.237657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.387380E+10 | 0.775648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.400293E+10 | 0.122166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.387380E+10 | 0.161069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.400293E+10 | 0.206996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.471312E+11 | 0.171499E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.361555E+10 | 0.441468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.400293E+10 | 0.237657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.385555E+11 | 0.235673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.348243E+11 | 0.782147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.385555E+11 | 0.144855E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.373118E+11 | 0.198788E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.385555E+11 | 0.651692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.373118E+11 | 0.119935E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.385555E+11 | 0.177091E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.385555E+11 | 0.223684E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.373118E+11 | 0.669921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.385555E+11 | 0.107235E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373118E+11 | 0.139624E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.385555E+11 | 0.177171E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453960E+12 | 0.152233E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.348243E+11 | 0.235673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.385555E+11 | 0.223684E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.397155E+10 | 0.116568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.358721E+10 | 0.586825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.397155E+10 | 0.124780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.384344E+10 | 0.183246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.397155E+10 | 0.547827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.384344E+10 | 0.115695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.397155E+10 | 0.174944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.397155E+10 | 0.220435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.384344E+10 | 0.580154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.397155E+10 | 0.880886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.384344E+10 | 0.117271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.397155E+10 | 0.155004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.467618E+11 | 0.136260E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.358721E+10 | 0.116568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.397155E+10 | 0.220435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.983726E+10 | 0.500125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.893267E+10 | 0.247594E+11 | 0.731142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114499E+11 | 0.118557E+11 | 46009654.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123835E+11 | 0.241556E+10 | 0.763361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125180E+11 | 0.190005E+10 | 0.220150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162569E+11 | 0.216027E+09 | 0.679616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.197387E+11 | 3812222.39 | 0.117065E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.215319E+11 | 38466636.91 | 0.107083E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142372E+11 | 0.780115E+09 | 0.463970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123616E+11 | 0.232914E+10 | 0.125692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108740E+11 | 0.764446E+10 | 0.765204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102747E+11 | 0.233739E+11 | 102335.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160396E+12 | 0.125329E+12 | 0.382267E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.893267E+10 | 3812222.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.215319E+11 | 0.500125E+11 | 0.117065E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.108883E+12 | 0.820125E+12 | 96972.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.923241E+11 | 0.419531E+12 | 0.106124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110220E+12 | 0.266174E+12 | 0.111127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104578E+12 | 0.948063E+11 | 0.702122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116646E+12 | 0.654943E+11 | 0.209437E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148879E+12 | 0.963315E+10 | 0.622458E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167084E+12 | 0.133632E+10 | 0.101660E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171310E+12 | 0.588270E+10 | 0.891082E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128094E+12 | 0.370793E+11 | 0.426758E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107597E+12 | 0.889899E+11 | 0.133795E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.991752E+11 | 0.243345E+12 | 0.116953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106805E+12 | 0.537002E+12 | 262511.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146160E+13 | 0.258940E+13 | 0.340377E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.923241E+11 | 0.133632E+10 | 96972.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171310E+12 | 0.820125E+12 | 0.101660E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.130650E+11 | 0.143779E+12 | 4108511.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109278E+11 | 0.791070E+11 | 0.573729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116485E+11 | 0.594943E+11 | 17457434.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.962690E+10 | 0.255455E+11 | 0.620092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107863E+11 | 0.187739E+11 | 0.225257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127522E+11 | 0.425524E+10 | 0.722633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143939E+11 | 0.123900E+10 | 0.119541E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142561E+11 | 0.298716E+10 | 0.100582E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107210E+11 | 0.110271E+11 | 0.454381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.971328E+10 | 0.261171E+11 | 0.102207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107041E+11 | 0.573546E+11 | 0.577939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123718E+11 | 0.106508E+12 | 10539264.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140967E+12 | 0.536188E+12 | 0.377956E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.962690E+10 | 0.123900E+10 | 4108511.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143939E+11 | 0.143779E+12 | 0.119541E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.378516E+10 | 0.298840E+10 | 0.214667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.374959E+10 | 0.402996E+09 | 0.226954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.507182E+10 | 80675034.81 | 0.381141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.615878E+10 | 0.00 | 0.794048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.664193E+10 | 0.00 | 0.171542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.761123E+10 | 0.00 | 0.367914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.808921E+10 | 0.00 | 0.544491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.986680E+10 | 0.00 | 0.533960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.912486E+10 | 0.00 | 0.334159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.921229E+10 | 0.00 | 0.182928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.751409E+10 | 0.00 | 0.890418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.545586E+10 | 20871873.34 | 0.374433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.822816E+11 | 0.349294E+10 | 0.242316E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.374959E+10 | 0.00 | 0.214667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.986680E+10 | 0.298840E+10 | 0.544491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.298067E+11 | 0.00 | 3103156.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123835E+12 | 0.00 | 0.00 | 0.00 |
February | 0.481702E+11 | 0.00 | 0.198821E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117905E+12 | 0.00 | 0.00 | 0.00 |
March | 0.645838E+11 | 0.00 | 0.329608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179464E+12 | 0.00 | 0.00 | 0.00 |
April | 0.908868E+11 | 0.00 | 0.244862E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234782E+12 | 0.00 | 0.00 | 0.00 |
May | 0.298362E+11 | 0.00 | 0.934275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128103E+12 | 0.00 | 0.00 | 0.00 |
June | 0.458967E+11 | 0.00 | 0.261857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683023E+11 | 0.00 | 0.00 | 0.00 |
July | 0.691438E+11 | 0.00 | 0.432051E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577147E+11 | 0.00 | 0.00 | 0.00 |
August | 0.918309E+11 | 0.00 | 0.459329E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131317E+12 | 0.00 | 0.00 | 0.00 |
September | 0.288763E+11 | 0.00 | 0.335645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.828304E+11 | 0.00 | 0.00 | 0.00 |
October | 0.530607E+11 | 0.00 | 0.213671E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127787E+12 | 0.00 | 0.00 | 0.00 |
November | 0.626920E+11 | 0.00 | 0.263558E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192375E+12 | 0.00 | 0.00 | 0.00 |
December | 0.952857E+11 | 0.00 | 0.298394E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251524E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.710070E+12 | 0.00 | 0.274506E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169594E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.288763E+11 | 0.00 | 3103156.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577147E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.952857E+11 | 0.00 | 0.459329E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251524E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.400293E+10 | 0.00 | 0.00 | 0.00 | 0.137059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.361555E+10 | 0.00 | 0.00 | 0.00 | 0.271512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.400293E+10 | 0.00 | 0.00 | 0.00 | 0.431642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.387380E+10 | 0.00 | 0.00 | 0.00 | 0.558322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.400293E+10 | 0.00 | 0.00 | 0.00 | 0.231237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.387380E+10 | 0.00 | 0.00 | 0.00 | 0.365987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.400293E+10 | 0.00 | 0.00 | 0.00 | 0.514126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.400293E+10 | 0.00 | 0.00 | 0.00 | 0.639021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.387380E+10 | 0.00 | 0.00 | 0.00 | 0.237505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.400293E+10 | 0.00 | 0.00 | 0.00 | 0.345757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.387380E+10 | 0.00 | 0.00 | 0.00 | 0.428278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.400293E+10 | 0.00 | 0.00 | 0.00 | 0.528822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.471312E+11 | 0.00 | 0.00 | 0.00 | 0.468927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.361555E+10 | 0.00 | 0.00 | 0.00 | 0.137059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.400293E+10 | 0.00 | 0.00 | 0.00 | 0.639021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.385555E+11 | 0.00 | 0.00 | 0.00 | 0.644100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.348243E+11 | 0.00 | 0.00 | 0.00 | 0.196512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.385555E+11 | 0.00 | 0.00 | 0.00 | 0.336086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.373118E+11 | 0.00 | 0.00 | 0.00 | 0.436296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.385555E+11 | 0.00 | 0.00 | 0.00 | 0.170888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.373118E+11 | 0.00 | 0.00 | 0.00 | 0.295144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.385555E+11 | 0.00 | 0.00 | 0.00 | 0.417611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.385555E+11 | 0.00 | 0.00 | 0.00 | 0.514422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.373118E+11 | 0.00 | 0.00 | 0.00 | 0.177801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.385555E+11 | 0.00 | 0.00 | 0.00 | 0.263777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373118E+11 | 0.00 | 0.00 | 0.00 | 0.324749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.385555E+11 | 0.00 | 0.00 | 0.00 | 0.393425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453960E+12 | 0.00 | 0.00 | 0.00 | 0.359112E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.348243E+11 | 0.00 | 0.00 | 0.00 | 0.644100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.385555E+11 | 0.00 | 0.00 | 0.00 | 0.514422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.397155E+10 | 0.00 | 0.00 | 0.00 | 0.374890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.358721E+10 | 0.00 | 0.00 | 0.00 | 0.176723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.397155E+10 | 0.00 | 0.00 | 0.00 | 0.347656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.384344E+10 | 0.00 | 0.00 | 0.00 | 0.476156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.397155E+10 | 0.00 | 0.00 | 0.00 | 0.169060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.384344E+10 | 0.00 | 0.00 | 0.00 | 0.335555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.397155E+10 | 0.00 | 0.00 | 0.00 | 0.486107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.397155E+10 | 0.00 | 0.00 | 0.00 | 0.590817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.384344E+10 | 0.00 | 0.00 | 0.00 | 0.181911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.397155E+10 | 0.00 | 0.00 | 0.00 | 0.259432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.384344E+10 | 0.00 | 0.00 | 0.00 | 0.328831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.397155E+10 | 0.00 | 0.00 | 0.00 | 0.414254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.467618E+11 | 0.00 | 0.00 | 0.00 | 0.380399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.358721E+10 | 0.00 | 0.00 | 0.00 | 0.374890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.397155E+10 | 0.00 | 0.00 | 0.00 | 0.590817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.374659E+11 | 0.00 | 0.00 | 33310195.39 | 0.00 | 0.196697E+09 | 0.227350E+11 | 0.00 | 0.35 |
February | 0.346895E+11 | 0.00 | 0.00 | 0.118419E+09 | 0.00 | 0.00 | 0.131077E+11 | 0.00 | 0.39 |
March | 0.292303E+11 | 0.00 | 0.00 | 0.200769E+09 | 0.00 | 0.00 | 0.244262E+11 | 0.00 | 0.46 |
April | 0.112102E+11 | 0.00 | 0.00 | 0.162485E+09 | 0.00 | 0.00 | 0.368770E+11 | 0.00 | 0.60 |
May | 0.553395E+10 | 37124853.53 | 0.00 | 94075033.98 | 9563901.64 | 0.00 | 0.393624E+11 | 0.00 | 0.68 |
June | 0.395452E+10 | 0.643313E+09 | 0.00 | 0.331872E+09 | 460211.99 | 0.00 | 0.281303E+11 | 0.00 | 0.82 |
July | 0.833804E+09 | 0.156207E+10 | 0.00 | 0.218941E+09 | 32852397.03 | 0.00 | 0.193128E+11 | 0.00 | 0.73 |
August | 0.166498E+10 | 0.952300E+09 | 0.00 | 0.194059E+09 | 53928318.11 | 0.00 | 0.303559E+11 | 0.00 | 0.93 |
September | 0.438277E+10 | 0.951334E+09 | 0.00 | 0.146674E+09 | 41640876.17 | 0.00 | 0.397201E+11 | 0.00 | 0.91 |
October | 0.113435E+11 | 0.00 | 0.00 | 0.465223E+09 | 0.00 | 0.00 | 0.461604E+11 | 0.00 | 0.82 |
November | 0.181520E+11 | 0.00 | 0.00 | 0.363888E+09 | 0.00 | 0.00 | 0.413971E+11 | 0.00 | 0.63 |
December | 0.279679E+11 | 0.00 | 0.00 | 0.132114E+09 | 0.00 | 0.00 | 0.335206E+11 | 0.00 | 0.45 |
Annual Sum or Average | 0.186429E+12 | 0.414615E+10 | 0.00 | 0.246183E+10 | 0.138446E+09 | 0.196697E+09 | 0.375105E+12 | 0.00 | 0.65 |
Minimum of Months | 0.833804E+09 | 0.00 | 0.00 | 33310195.39 | 0.00 | 0.00 | 0.131077E+11 | 0.00 | 0.35 |
Maximum of Months | 0.374659E+11 | 0.156207E+10 | 0.00 | 0.465223E+09 | 53928318.11 | 0.196697E+09 | 0.461604E+11 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.276516E+11 | 0.00 | 0.00 | 58129278.52 | 0.00 | 13554666.35 | 0.241484E+11 | 0.00 | 0.31 |
February | 0.234232E+11 | 0.00 | 0.00 | 0.264963E+09 | 0.00 | 0.00 | 0.202674E+11 | 0.00 | 0.39 |
March | 0.195550E+11 | 0.00 | 0.00 | 0.461249E+09 | 0.00 | 0.00 | 0.345558E+11 | 0.00 | 0.49 |
April | 0.902338E+10 | 0.00 | 0.00 | 0.318330E+09 | 0.00 | 0.00 | 0.468383E+11 | 0.00 | 0.75 |
May | 0.503417E+10 | 15678585.22 | 0.00 | 0.149131E+09 | 7555977.39 | 0.00 | 0.443548E+11 | 0.00 | 0.79 |
June | 0.509640E+10 | 0.224340E+09 | 0.00 | 0.448453E+09 | 439086.08 | 0.00 | 0.338279E+11 | 0.00 | 0.95 |
July | 0.366134E+10 | 0.529947E+09 | 0.00 | 0.238760E+09 | 24274650.00 | 0.00 | 0.205282E+11 | 0.00 | 0.78 |
August | 0.410940E+10 | 0.404700E+09 | 0.00 | 0.236617E+09 | 42151788.48 | 0.00 | 0.331512E+11 | 0.00 | 1.02 |
September | 0.341627E+10 | 0.346862E+09 | 0.00 | 0.180881E+09 | 32709946.57 | 0.00 | 0.400980E+11 | 0.00 | 0.88 |
October | 0.995056E+10 | 0.00 | 0.00 | 0.553828E+09 | 0.00 | 0.00 | 0.427419E+11 | 0.00 | 0.78 |
November | 0.127052E+11 | 0.00 | 0.00 | 0.531606E+09 | 0.00 | 0.00 | 0.398287E+11 | 0.00 | 0.57 |
December | 0.170786E+11 | 0.00 | 0.00 | 0.232390E+09 | 0.00 | 0.00 | 0.355596E+11 | 0.00 | 0.39 |
Annual Sum or Average | 0.140705E+12 | 0.152153E+10 | 0.00 | 0.367434E+10 | 0.107131E+09 | 13554666.35 | 0.415900E+12 | 0.00 | 0.68 |
Minimum of Months | 0.341627E+10 | 0.00 | 0.00 | 58129278.52 | 0.00 | 0.00 | 0.202674E+11 | 0.00 | 0.31 |
Maximum of Months | 0.276516E+11 | 0.529947E+09 | 0.00 | 0.553828E+09 | 42151788.48 | 13554666.35 | 0.468383E+11 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.400735E+12 | 0.00 | 0.00 | 48257317.62 | 0.00 | 0.762190E+10 | 0.484727E+11 | 0.00 | 0.28 |
February | 0.307073E+12 | 0.00 | 0.00 | 0.902324E+09 | 0.00 | 0.132967E+10 | 0.671835E+11 | 0.00 | 0.33 |
March | 0.245308E+12 | 0.00 | 0.00 | 0.257186E+10 | 0.00 | 0.202698E+10 | 0.186372E+12 | 0.00 | 0.39 |
April | 0.154021E+12 | 0.00 | 0.00 | 0.170103E+10 | 0.00 | 0.00 | 0.251304E+12 | 0.00 | 0.56 |
May | 0.101950E+12 | 72154118.87 | 0.00 | 0.101028E+10 | 0.218861E+09 | 0.00 | 0.295458E+12 | 0.00 | 0.67 |
June | 0.816555E+11 | 0.238357E+10 | 0.00 | 0.320824E+10 | 0.141970E+09 | 0.00 | 0.238794E+12 | 0.00 | 0.82 |
July | 0.483586E+11 | 0.587882E+10 | 0.00 | 0.137112E+10 | 0.271648E+09 | 0.00 | 0.124202E+12 | 0.00 | 0.61 |
August | 0.464463E+11 | 0.435903E+10 | 0.00 | 0.135263E+10 | 0.442053E+09 | 0.00 | 0.210499E+12 | 0.00 | 0.76 |
September | 0.826250E+11 | 0.326287E+10 | 0.00 | 0.116924E+10 | 0.557738E+09 | 0.00 | 0.256122E+12 | 0.00 | 0.72 |
October | 0.160186E+12 | 0.00 | 0.00 | 0.317398E+10 | 0.00 | 0.00 | 0.223723E+12 | 0.00 | 0.59 |
November | 0.231049E+12 | 0.00 | 0.00 | 0.217823E+10 | 0.00 | 0.178773E+10 | 0.157244E+12 | 0.00 | 0.43 |
December | 0.337287E+12 | 0.00 | 0.00 | 0.466656E+09 | 0.00 | 0.325871E+10 | 0.833436E+11 | 0.00 | 0.31 |
Annual Sum or Average | 0.219669E+13 | 0.159564E+11 | 0.00 | 0.191539E+11 | 0.163227E+10 | 0.160250E+11 | 0.214272E+13 | 0.00 | 0.54 |
Minimum of Months | 0.464463E+11 | 0.00 | 0.00 | 48257317.62 | 0.00 | 0.00 | 0.484727E+11 | 0.00 | 0.28 |
Maximum of Months | 0.400735E+12 | 0.587882E+10 | 0.00 | 0.320824E+10 | 0.557738E+09 | 0.762190E+10 | 0.295458E+12 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.252421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116017E+11 | 0.00 | 0.00 | 0.25 |
February | 0.269878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499676E+10 | 0.00 | 0.00 | 0.32 |
March | 0.326366E+11 | 0.00 | 0.00 | 7211454.41 | 0.00 | 0.396994E+10 | 0.766042E+09 | 0.00 | 0.37 |
April | 0.287418E+11 | 0.00 | 0.00 | 23103856.59 | 0.00 | 0.958219E+09 | 0.604664E+10 | 0.00 | 0.53 |
May | 0.231245E+11 | 0.00 | 0.00 | 37307777.57 | 10828177.46 | 0.555365E+09 | 0.145712E+11 | 0.00 | 0.67 |
June | 0.155473E+11 | 0.103767E+09 | 0.00 | 0.184745E+09 | 1126393.61 | 4827476.09 | 0.154819E+11 | 0.00 | 0.82 |
July | 0.793573E+10 | 0.298371E+09 | 0.00 | 79351837.79 | 20060554.29 | 0.00 | 0.853629E+10 | 0.00 | 0.62 |
August | 0.102534E+11 | 0.193665E+09 | 0.00 | 73084659.26 | 89354406.70 | 1047216.31 | 0.127391E+11 | 0.00 | 0.73 |
September | 0.180931E+11 | 0.153835E+09 | 0.00 | 36910361.49 | 97748008.77 | 0.209322E+09 | 0.106577E+11 | 0.00 | 0.69 |
October | 0.289178E+11 | 0.00 | 0.00 | 19465028.86 | 0.00 | 0.118734E+10 | 0.209968E+10 | 0.00 | 0.56 |
November | 0.281128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277973E+10 | 0.00 | 0.00 | 0.39 |
December | 0.252515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764568E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.270845E+12 | 0.749638E+09 | 0.00 | 0.461180E+09 | 0.219118E+09 | 0.339099E+11 | 0.708984E+11 | 0.00 | 0.52 |
Minimum of Months | 0.793573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.326366E+11 | 0.298371E+09 | 0.00 | 0.184745E+09 | 97748008.77 | 0.116017E+11 | 0.154819E+11 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.315556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693277E+10 | 0.00 | 0.00 | 0.47 |
February | 0.448121E+10 | 0.00 | 0.00 | 4371.09 | 0.00 | 0.369866E+10 | 4561559.48 | 0.00 | 0.56 |
March | 0.734363E+10 | 0.00 | 0.00 | 20197.54 | 0.00 | 0.165780E+10 | 22556496.10 | 0.00 | 0.62 |
April | 0.687960E+10 | 0.00 | 0.00 | 5357798.99 | 0.00 | 0.111009E+09 | 0.133016E+10 | 0.00 | 0.88 |
May | 0.511717E+10 | 4450368.53 | 0.00 | 7032119.99 | 1605697.99 | 0.133893E+09 | 0.251352E+10 | 0.00 | 1.01 |
June | 0.331148E+10 | 46353187.69 | 0.00 | 37874946.00 | 93308.86 | 354731.51 | 0.294899E+10 | 0.00 | 1.27 |
July | 0.199023E+10 | 0.125259E+09 | 0.00 | 18001830.36 | 5158532.73 | 0.00 | 0.189801E+10 | 0.00 | 1.05 |
August | 0.290913E+10 | 95422950.25 | 0.00 | 13776555.93 | 8957549.57 | 0.00 | 0.258976E+10 | 0.00 | 1.26 |
September | 0.474729E+10 | 67510710.02 | 0.00 | 6148760.92 | 6951092.19 | 1334425.56 | 0.175593E+10 | 0.00 | 1.06 |
October | 0.720232E+10 | 0.00 | 0.00 | 5480248.37 | 0.00 | 0.117221E+09 | 0.514229E+09 | 0.00 | 0.89 |
November | 0.710405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894577E+09 | 0.00 | 0.00 | 0.66 |
December | 0.490623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381771E+10 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 0.591479E+11 | 0.338996E+09 | 0.00 | 93696829.20 | 22766181.34 | 0.173653E+11 | 0.135777E+11 | 0.00 | 0.85 |
Minimum of Months | 0.199023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.734363E+10 | 0.125259E+09 | 0.00 | 37874946.00 | 8957549.57 | 0.693277E+10 | 0.294899E+10 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.376863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694110E+10 | 0.00 | 0.00 | 0.77 |
February | 0.491150E+10 | 0.00 | 0.00 | 3198444.08 | 0.00 | 0.355840E+10 | 0.283039E+09 | 0.00 | 0.93 |
March | 0.701350E+10 | 0.00 | 0.00 | 12009750.04 | 0.00 | 0.193293E+10 | 0.959088E+09 | 0.00 | 1.07 |
April | 0.653153E+10 | 0.00 | 0.00 | 17008584.35 | 0.00 | 0.266440E+09 | 0.282413E+10 | 0.00 | 1.56 |
May | 0.469132E+10 | 3557622.68 | 0.00 | 12588343.10 | 1707170.06 | 0.200215E+09 | 0.420288E+10 | 0.00 | 1.79 |
June | 0.321795E+10 | 38814769.76 | 0.00 | 53318711.32 | 382020.44 | 1260056.56 | 0.421732E+10 | 0.00 | 2.31 |
July | 0.194082E+10 | 92718429.13 | 0.00 | 32480681.07 | 9477419.76 | 0.00 | 0.314118E+10 | 0.00 | 2.07 |
August | 0.311504E+10 | 82592701.56 | 0.00 | 20809459.71 | 9550553.04 | 0.00 | 0.361378E+10 | 0.00 | 2.31 |
September | 0.471804E+10 | 57141889.33 | 0.00 | 10831383.23 | 7610981.26 | 8580654.63 | 0.270691E+10 | 0.00 | 1.85 |
October | 0.708311E+10 | 0.00 | 0.00 | 14412517.78 | 0.00 | 0.283660E+09 | 0.119939E+10 | 0.00 | 1.52 |
November | 0.720507E+10 | 0.00 | 0.00 | 1477181.30 | 0.00 | 0.120968E+10 | 0.127616E+09 | 0.00 | 1.10 |
December | 0.499530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430574E+10 | 0.00 | 0.00 | 0.80 |
Annual Sum or Average | 0.591918E+11 | 0.274825E+09 | 0.00 | 0.178135E+09 | 28728144.55 | 0.187080E+11 | 0.232753E+11 | 0.00 | 1.51 |
Minimum of Months | 0.194082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 |
Maximum of Months | 0.720507E+10 | 92718429.13 | 0.00 | 53318711.32 | 9550553.04 | 0.694110E+10 | 0.421732E+10 | 0.00 | 2.31 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.443873E+10 | 0.00 | 0.00 | 5975926.47 | 0.00 | 0.751829E+10 | 0.245991E+10 | 0.00 | 0.68 |
February | 0.508608E+10 | 0.00 | 0.00 | 57620064.44 | 0.00 | 0.384782E+10 | 0.411681E+10 | 0.00 | 0.99 |
March | 0.689354E+10 | 0.00 | 0.00 | 77047734.28 | 0.00 | 0.256734E+10 | 0.591703E+10 | 0.00 | 1.13 |
April | 0.747305E+10 | 0.00 | 0.00 | 32058083.85 | 0.00 | 0.610842E+09 | 0.529944E+10 | 0.00 | 1.50 |
May | 0.618655E+10 | 6179259.08 | 0.00 | 16774638.64 | 2191388.01 | 0.507133E+09 | 0.498811E+10 | 0.00 | 1.56 |
June | 0.531927E+10 | 68516776.28 | 0.00 | 41026101.78 | 127343.94 | 12425740.48 | 0.322164E+10 | 0.00 | 1.73 |
July | 0.333559E+10 | 0.181755E+09 | 0.00 | 19809030.85 | 7040145.06 | 0.00 | 0.202431E+10 | 0.00 | 1.46 |
August | 0.441374E+10 | 0.184165E+09 | 0.00 | 21234815.70 | 12348457.76 | 814365.78 | 0.369554E+10 | 0.00 | 1.96 |
September | 0.545205E+10 | 0.174351E+09 | 0.00 | 22107712.74 | 6806978.99 | 93966170.44 | 0.536951E+10 | 0.00 | 1.95 |
October | 0.671121E+10 | 0.00 | 0.00 | 95662630.68 | 0.00 | 0.484041E+09 | 0.691755E+10 | 0.00 | 1.76 |
November | 0.652369E+10 | 0.00 | 0.00 | 68034065.80 | 0.00 | 0.168688E+10 | 0.527345E+10 | 0.00 | 1.15 |
December | 0.555143E+10 | 0.00 | 0.00 | 19047381.51 | 0.00 | 0.448989E+10 | 0.303931E+10 | 0.00 | 0.75 |
Annual Sum or Average | 0.673849E+11 | 0.614968E+09 | 0.00 | 0.476398E+09 | 28514313.76 | 0.218194E+11 | 0.523226E+11 | 0.00 | 1.39 |
Minimum of Months | 0.333559E+10 | 0.00 | 0.00 | 5975926.47 | 0.00 | 0.00 | 0.202431E+10 | 0.00 | 0.68 |
Maximum of Months | 0.747305E+10 | 0.184165E+09 | 0.00 | 95662630.68 | 12348457.76 | 0.751829E+10 | 0.691755E+10 | 0.00 | 1.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.693867E+10 | 0.00 | 0.00 | 93704.45 | 0.00 | 0.627366E+10 | 0.113450E+09 | 0.00 | 0.96 |
February | 0.771860E+10 | 0.00 | 0.00 | 7388907.41 | 0.00 | 0.269729E+10 | 0.562207E+09 | 0.00 | 1.17 |
March | 0.100131E+11 | 0.00 | 0.00 | 19848500.72 | 0.00 | 0.826279E+09 | 0.159266E+10 | 0.00 | 1.35 |
April | 0.790537E+10 | 0.00 | 0.00 | 22211875.79 | 0.00 | 3423206.68 | 0.416165E+10 | 0.00 | 2.07 |
May | 0.643890E+10 | 4748209.96 | 0.00 | 12146726.31 | 2125918.42 | 82651075.43 | 0.454452E+10 | 0.00 | 2.24 |
June | 0.523047E+10 | 58071423.41 | 0.00 | 37483931.57 | 123888.78 | 0.00 | 0.290657E+10 | 0.00 | 2.53 |
July | 0.294736E+10 | 0.189206E+09 | 0.00 | 18410885.77 | 826214.69 | 0.00 | 0.210995E+10 | 0.00 | 2.10 |
August | 0.343338E+10 | 0.143464E+09 | 0.00 | 21301283.03 | 2970627.64 | 0.00 | 0.382349E+10 | 0.00 | 2.60 |
September | 0.632348E+10 | 0.113932E+09 | 0.00 | 7672233.06 | 1269451.33 | 478152.96 | 0.251771E+10 | 0.00 | 2.24 |
October | 0.899970E+10 | 0.00 | 0.00 | 20604973.93 | 0.00 | 56364972.57 | 0.167501E+10 | 0.00 | 1.93 |
November | 0.929053E+10 | 0.00 | 0.00 | 11648377.64 | 0.00 | 0.417258E+09 | 0.104294E+10 | 0.00 | 1.39 |
December | 0.956686E+10 | 0.00 | 0.00 | 1243040.77 | 0.00 | 0.159184E+10 | 0.431910E+09 | 0.00 | 1.01 |
Annual Sum or Average | 0.848064E+11 | 0.509422E+09 | 0.00 | 0.180054E+09 | 7316100.86 | 0.119493E+11 | 0.254821E+11 | 0.00 | 1.80 |
Minimum of Months | 0.294736E+10 | 0.00 | 0.00 | 93704.45 | 0.00 | 0.00 | 0.113450E+09 | 0.00 | 0.96 |
Maximum of Months | 0.100131E+11 | 0.189206E+09 | 0.00 | 37483931.57 | 2970627.64 | 0.627366E+10 | 0.454452E+10 | 0.00 | 2.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.950792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126954E+12 | 0.00 | 0.00 | 0.65 |
February | 0.300908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784451E+11 | 0.00 | 0.00 | 0.74 |
March | 0.648462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514874E+11 | 0.00 | 0.00 | 0.81 |
April | 0.786184E+11 | 0.00 | 0.00 | 1709132.32 | 0.00 | 0.188028E+11 | 0.162925E+10 | 0.00 | 1.06 |
May | 0.748744E+11 | 54764113.30 | 0.00 | 14633659.94 | 30436959.21 | 0.116313E+11 | 0.703295E+10 | 0.00 | 1.22 |
June | 0.595381E+11 | 0.517710E+09 | 0.00 | 88476909.39 | 46896207.77 | 0.747876E+09 | 0.882189E+10 | 0.00 | 1.40 |
July | 0.302255E+11 | 0.155314E+10 | 0.00 | 63253416.35 | 96852448.02 | 11324814.46 | 0.868972E+10 | 0.00 | 1.09 |
August | 0.446027E+11 | 0.105208E+10 | 0.00 | 48255122.58 | 0.175726E+09 | 0.195815E+09 | 0.104755E+11 | 0.00 | 1.27 |
September | 0.652945E+11 | 0.603546E+09 | 0.00 | 13952820.72 | 0.254270E+09 | 0.599459E+10 | 0.570441E+10 | 0.00 | 1.26 |
October | 0.746639E+11 | 0.00 | 0.00 | 468910.72 | 0.00 | 0.190824E+11 | 0.384353E+09 | 0.00 | 1.10 |
November | 0.550806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492223E+11 | 0.00 | 0.00 | 0.88 |
December | 0.216873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100747E+12 | 0.00 | 0.00 | 0.70 |
Annual Sum or Average | 0.609030E+12 | 0.378124E+10 | 0.00 | 0.230750E+09 | 0.604182E+09 | 0.463322E+12 | 0.427381E+11 | 0.00 | 1.02 |
Minimum of Months | 0.950792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11324814.46 | 0.00 | 0.00 | 0.65 |
Maximum of Months | 0.786184E+11 | 0.155314E+10 | 0.00 | 88476909.39 | 0.254270E+09 | 0.126954E+12 | 0.104755E+11 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819906E+11 | 0.00 | 0.00 | 0.70 |
February | 0.261196E+11 | 0.00 | 0.00 | 10666464.04 | 0.00 | 0.491819E+11 | 0.711667E+09 | 0.00 | 0.80 |
March | 0.456847E+11 | 0.00 | 0.00 | 94908441.60 | 0.00 | 0.327842E+11 | 0.652818E+10 | 0.00 | 0.92 |
April | 0.452457E+11 | 0.00 | 0.00 | 0.146027E+09 | 0.00 | 0.119910E+11 | 0.220889E+11 | 0.00 | 1.35 |
May | 0.391079E+11 | 47040143.00 | 0.00 | 0.112158E+09 | 21751116.92 | 0.760346E+10 | 0.331436E+11 | 0.00 | 1.67 |
June | 0.313204E+11 | 0.488717E+09 | 0.00 | 0.468621E+09 | 32584587.54 | 0.569285E+09 | 0.348486E+11 | 0.00 | 2.22 |
July | 0.165812E+11 | 0.125853E+10 | 0.00 | 0.286577E+09 | 0.126311E+09 | 0.00 | 0.264086E+11 | 0.00 | 1.94 |
August | 0.265711E+11 | 0.108761E+10 | 0.00 | 0.175090E+09 | 0.111140E+09 | 0.122954E+09 | 0.291092E+11 | 0.00 | 2.07 |
September | 0.392688E+11 | 0.638369E+09 | 0.00 | 89119552.80 | 0.106451E+09 | 0.402878E+10 | 0.204782E+11 | 0.00 | 1.67 |
October | 0.507825E+11 | 0.00 | 0.00 | 95177837.82 | 0.00 | 0.123407E+11 | 0.661253E+10 | 0.00 | 1.29 |
November | 0.391566E+11 | 0.00 | 0.00 | 8294070.38 | 0.00 | 0.330491E+11 | 0.607044E+09 | 0.00 | 0.94 |
December | 0.188846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671155E+11 | 0.00 | 0.00 | 0.75 |
Annual Sum or Average | 0.391736E+12 | 0.352027E+10 | 0.00 | 0.148664E+10 | 0.398237E+09 | 0.300777E+12 | 0.180537E+12 | 0.00 | 1.36 |
Minimum of Months | 0.130125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 |
Maximum of Months | 0.507825E+11 | 0.125853E+10 | 0.00 | 0.468621E+09 | 0.126311E+09 | 0.819906E+11 | 0.348486E+11 | 0.00 | 2.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.348621E+11 | 0.00 | 0.00 | 45692097.17 | 0.00 | 0.919228E+11 | 0.205179E+11 | 0.00 | 0.71 |
February | 0.428290E+11 | 0.00 | 0.00 | 0.618977E+09 | 0.00 | 0.495100E+11 | 0.396557E+11 | 0.00 | 1.01 |
March | 0.579202E+11 | 0.00 | 0.00 | 0.804655E+09 | 0.00 | 0.371002E+11 | 0.556741E+11 | 0.00 | 1.13 |
April | 0.600974E+11 | 0.00 | 0.00 | 0.290319E+09 | 0.00 | 0.169476E+11 | 0.453451E+11 | 0.00 | 1.43 |
May | 0.539958E+11 | 90014326.07 | 0.00 | 0.154088E+09 | 26507879.71 | 0.123606E+11 | 0.437254E+11 | 0.00 | 1.53 |
June | 0.506169E+11 | 0.837615E+09 | 0.00 | 0.351204E+09 | 25367262.71 | 0.135774E+10 | 0.265348E+11 | 0.00 | 1.67 |
July | 0.287428E+11 | 0.236133E+10 | 0.00 | 0.165616E+09 | 83603934.34 | 11089362.40 | 0.163673E+11 | 0.00 | 1.35 |
August | 0.381753E+11 | 0.237694E+10 | 0.00 | 0.182350E+09 | 0.132707E+09 | 0.407383E+09 | 0.294210E+11 | 0.00 | 1.78 |
September | 0.477609E+11 | 0.208210E+10 | 0.00 | 0.212962E+09 | 42118180.90 | 0.481564E+10 | 0.497244E+11 | 0.00 | 1.94 |
October | 0.565014E+11 | 0.00 | 0.00 | 0.985304E+09 | 0.00 | 0.116419E+11 | 0.622063E+11 | 0.00 | 1.71 |
November | 0.548404E+11 | 0.00 | 0.00 | 0.641569E+09 | 0.00 | 0.314656E+11 | 0.450719E+11 | 0.00 | 1.14 |
December | 0.441674E+11 | 0.00 | 0.00 | 0.136268E+09 | 0.00 | 0.694407E+11 | 0.214278E+11 | 0.00 | 0.79 |
Annual Sum or Average | 0.570510E+12 | 0.774799E+10 | 0.00 | 0.458901E+10 | 0.310304E+09 | 0.326981E+12 | 0.455672E+12 | 0.00 | 1.35 |
Minimum of Months | 0.287428E+11 | 0.00 | 0.00 | 45692097.17 | 0.00 | 11089362.40 | 0.163673E+11 | 0.00 | 0.71 |
Maximum of Months | 0.600974E+11 | 0.237694E+10 | 0.00 | 0.985304E+09 | 0.132707E+09 | 0.919228E+11 | 0.622063E+11 | 0.00 | 1.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.224311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104596E+12 | 0.00 | 0.00 | 0.94 |
February | 0.397001E+11 | 0.00 | 0.00 | 33611526.52 | 0.00 | 0.597015E+11 | 0.261759E+10 | 0.00 | 1.08 |
March | 0.651670E+11 | 0.00 | 0.00 | 0.101489E+09 | 0.00 | 0.383120E+11 | 0.761533E+10 | 0.00 | 1.21 |
April | 0.680578E+11 | 0.00 | 0.00 | 94552527.01 | 0.00 | 0.135567E+11 | 0.167210E+11 | 0.00 | 1.71 |
May | 0.581905E+11 | 51357278.63 | 0.00 | 84271974.54 | 28543498.67 | 0.871260E+10 | 0.285623E+11 | 0.00 | 2.00 |
June | 0.495456E+11 | 0.647154E+09 | 0.00 | 0.255845E+09 | 25348514.68 | 0.100231E+10 | 0.185590E+11 | 0.00 | 2.25 |
July | 0.286763E+11 | 0.214578E+10 | 0.00 | 95472672.78 | 56588556.05 | 8783514.28 | 0.106426E+11 | 0.00 | 1.77 |
August | 0.402717E+11 | 0.137197E+10 | 0.00 | 80219815.69 | 0.135357E+09 | 0.310553E+09 | 0.138349E+11 | 0.00 | 2.04 |
September | 0.566445E+11 | 0.983273E+09 | 0.00 | 46298500.97 | 0.135344E+09 | 0.467170E+10 | 0.140177E+11 | 0.00 | 1.98 |
October | 0.691060E+11 | 0.00 | 0.00 | 91330078.44 | 0.00 | 0.130600E+11 | 0.760792E+10 | 0.00 | 1.66 |
November | 0.590644E+11 | 0.00 | 0.00 | 14427695.09 | 0.00 | 0.370219E+11 | 0.161028E+10 | 0.00 | 1.28 |
December | 0.330577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815278E+11 | 0.00 | 0.00 | 1.02 |
Annual Sum or Average | 0.589913E+12 | 0.519954E+10 | 0.00 | 0.897520E+09 | 0.381181E+09 | 0.362482E+12 | 0.121789E+12 | 0.00 | 1.58 |
Minimum of Months | 0.224311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8783514.28 | 0.00 | 0.00 | 0.94 |
Maximum of Months | 0.691060E+11 | 0.214578E+10 | 0.00 | 0.255845E+09 | 0.135357E+09 | 0.104596E+12 | 0.285623E+11 | 0.00 | 2.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.428249E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110946E+11 | 0.00 | 0.00 | 0.62 |
February | 0.209222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789138E+10 | 0.00 | 0.00 | 0.79 |
March | 0.561309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605335E+10 | 0.00 | 0.00 | 0.91 |
April | 0.746899E+10 | 0.00 | 0.00 | 35689.50 | 0.00 | 0.332392E+10 | 90362658.37 | 0.00 | 1.27 |
May | 0.860239E+10 | 1686698.63 | 0.00 | 937493.41 | 1692359.89 | 0.188756E+10 | 0.706253E+09 | 0.00 | 1.52 |
June | 0.734213E+10 | 20662456.30 | 0.00 | 4588541.67 | 1570841.38 | 0.431468E+09 | 0.708892E+09 | 0.00 | 1.74 |
July | 0.358175E+10 | 65958636.03 | 0.00 | 6309880.09 | 17930760.14 | 79552316.98 | 0.814543E+09 | 0.00 | 1.31 |
August | 0.499083E+10 | 48005757.24 | 0.00 | 5058773.54 | 32595722.53 | 0.278573E+09 | 0.970362E+09 | 0.00 | 1.54 |
September | 0.662189E+10 | 33454487.45 | 0.00 | 806790.03 | 31513534.89 | 0.150238E+10 | 0.348630E+09 | 0.00 | 1.55 |
October | 0.658079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340885E+10 | 0.00 | 0.00 | 1.36 |
November | 0.350214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614362E+10 | 0.00 | 0.00 | 0.98 |
December | 0.123840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903048E+10 | 0.00 | 0.00 | 0.67 |
Annual Sum or Average | 0.580629E+11 | 0.169768E+09 | 0.00 | 17737168.24 | 85303218.82 | 0.511258E+11 | 0.363904E+10 | 0.00 | 1.19 |
Minimum of Months | 0.428249E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79552316.98 | 0.00 | 0.00 | 0.62 |
Maximum of Months | 0.860239E+10 | 65958636.03 | 0.00 | 6309880.09 | 32595722.53 | 0.110946E+11 | 0.970362E+09 | 0.00 | 1.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.872693E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672514E+10 | 0.00 | 0.00 | 0.63 |
February | 0.239799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418353E+10 | 0.00 | 0.00 | 0.81 |
March | 0.448668E+10 | 0.00 | 0.00 | 2704159.76 | 0.00 | 0.302363E+10 | 0.203942E+09 | 0.00 | 0.94 |
April | 0.433868E+10 | 0.00 | 0.00 | 9580889.91 | 0.00 | 0.150609E+10 | 0.163342E+10 | 0.00 | 1.37 |
May | 0.387431E+10 | 1142051.65 | 0.00 | 8814018.73 | 1085599.82 | 0.948961E+09 | 0.313205E+10 | 0.00 | 1.71 |
June | 0.310678E+10 | 18086549.05 | 0.00 | 38960754.85 | 498577.37 | 0.184340E+09 | 0.323949E+10 | 0.00 | 2.21 |
July | 0.143547E+10 | 54871962.70 | 0.00 | 25888892.50 | 10080154.91 | 36451468.74 | 0.247735E+10 | 0.00 | 1.89 |
August | 0.208122E+10 | 60749621.65 | 0.00 | 17176388.55 | 8453936.94 | 0.120000E+09 | 0.286133E+10 | 0.00 | 2.03 |
September | 0.336422E+10 | 43968615.88 | 0.00 | 6853073.93 | 7015650.93 | 0.728243E+09 | 0.174294E+10 | 0.00 | 1.69 |
October | 0.481186E+10 | 0.00 | 0.00 | 1877263.20 | 0.00 | 0.159770E+10 | 0.186702E+09 | 0.00 | 1.40 |
November | 0.311621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324208E+10 | 0.00 | 0.00 | 1.00 |
December | 0.127050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549944E+10 | 0.00 | 0.00 | 0.68 |
Annual Sum or Average | 0.351566E+11 | 0.178819E+09 | 0.00 | 0.111855E+09 | 27133919.98 | 0.277956E+11 | 0.154772E+11 | 0.00 | 1.36 |
Minimum of Months | 0.872693E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36451468.74 | 0.00 | 0.00 | 0.63 |
Maximum of Months | 0.481186E+10 | 60749621.65 | 0.00 | 38960754.85 | 10080154.91 | 0.672514E+10 | 0.323949E+10 | 0.00 | 2.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.259236E+10 | 0.00 | 0.00 | 2180721.66 | 0.00 | 0.815204E+10 | 0.108509E+10 | 0.00 | 0.64 |
February | 0.383082E+10 | 0.00 | 0.00 | 39861990.69 | 0.00 | 0.479924E+10 | 0.249391E+10 | 0.00 | 0.94 |
March | 0.516783E+10 | 0.00 | 0.00 | 62891222.89 | 0.00 | 0.404735E+10 | 0.465032E+10 | 0.00 | 1.12 |
April | 0.586220E+10 | 0.00 | 0.00 | 20702470.52 | 0.00 | 0.251512E+10 | 0.401306E+10 | 0.00 | 1.50 |
May | 0.599815E+10 | 1878596.22 | 0.00 | 12654313.91 | 1674510.01 | 0.179286E+10 | 0.443290E+10 | 0.00 | 1.70 |
June | 0.592014E+10 | 31511691.85 | 0.00 | 26983025.83 | 1016515.96 | 0.597575E+09 | 0.252950E+10 | 0.00 | 1.89 |
July | 0.299272E+10 | 94252839.50 | 0.00 | 17310633.11 | 14402346.02 | 0.101603E+09 | 0.187500E+10 | 0.00 | 1.49 |
August | 0.380874E+10 | 0.114199E+09 | 0.00 | 20010616.85 | 16669987.34 | 0.266922E+09 | 0.325606E+10 | 0.00 | 1.91 |
September | 0.476698E+10 | 0.119888E+09 | 0.00 | 16722571.19 | 6745692.17 | 0.115609E+10 | 0.453143E+10 | 0.00 | 2.04 |
October | 0.518568E+10 | 0.00 | 0.00 | 72043528.79 | 0.00 | 0.199574E+10 | 0.493859E+10 | 0.00 | 1.75 |
November | 0.451975E+10 | 0.00 | 0.00 | 41490625.67 | 0.00 | 0.359237E+10 | 0.278968E+10 | 0.00 | 1.11 |
December | 0.334513E+10 | 0.00 | 0.00 | 7049885.76 | 0.00 | 0.620734E+10 | 0.104459E+10 | 0.00 | 0.69 |
Annual Sum or Average | 0.539905E+11 | 0.361731E+09 | 0.00 | 0.339902E+09 | 40509051.50 | 0.352243E+11 | 0.376401E+11 | 0.00 | 1.40 |
Minimum of Months | 0.259236E+10 | 0.00 | 0.00 | 2180721.66 | 0.00 | 0.101603E+09 | 0.104459E+10 | 0.00 | 0.64 |
Maximum of Months | 0.599815E+10 | 0.119888E+09 | 0.00 | 72043528.79 | 16669987.34 | 0.815204E+10 | 0.493859E+10 | 0.00 | 2.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.121782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760175E+10 | 0.00 | 0.00 | 0.74 |
February | 0.275117E+10 | 0.00 | 0.00 | 2060462.30 | 0.00 | 0.476195E+10 | 0.164762E+09 | 0.00 | 0.94 |
March | 0.499924E+10 | 0.00 | 0.00 | 8854017.89 | 0.00 | 0.342288E+10 | 0.693794E+09 | 0.00 | 1.11 |
April | 0.552639E+10 | 0.00 | 0.00 | 8458439.64 | 0.00 | 0.161491E+10 | 0.176650E+10 | 0.00 | 1.66 |
May | 0.515626E+10 | 1329471.76 | 0.00 | 8238935.29 | 1263755.72 | 0.108533E+10 | 0.317733E+10 | 0.00 | 2.03 |
June | 0.460752E+10 | 23746885.80 | 0.00 | 25808493.52 | 289694.97 | 0.300673E+09 | 0.210606E+10 | 0.00 | 2.29 |
July | 0.250088E+10 | 89114437.11 | 0.00 | 11397815.06 | 7618976.35 | 27964914.59 | 0.128307E+10 | 0.00 | 1.77 |
August | 0.346946E+10 | 60278549.42 | 0.00 | 10196478.79 | 18060430.78 | 98218587.99 | 0.156209E+10 | 0.00 | 2.03 |
September | 0.455471E+10 | 57363722.43 | 0.00 | 4560348.59 | 11100421.38 | 0.813043E+09 | 0.147168E+10 | 0.00 | 1.99 |
October | 0.539616E+10 | 0.00 | 0.00 | 6951264.33 | 0.00 | 0.176515E+10 | 0.630072E+09 | 0.00 | 1.66 |
November | 0.398517E+10 | 0.00 | 0.00 | 355214.03 | 0.00 | 0.337977E+10 | 34355199.49 | 0.00 | 1.16 |
December | 0.195946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591777E+10 | 0.00 | 0.00 | 0.79 |
Annual Sum or Average | 0.461242E+11 | 0.231833E+09 | 0.00 | 86881469.43 | 38333279.21 | 0.307894E+11 | 0.128897E+11 | 0.00 | 1.52 |
Minimum of Months | 0.121782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27964914.59 | 0.00 | 0.00 | 0.74 |
Maximum of Months | 0.552639E+10 | 89114437.11 | 0.00 | 25808493.52 | 18060430.78 | 0.760175E+10 | 0.317733E+10 | 0.00 | 2.29 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 6314772.09 | 0.00 | 0.00 | 4840184.22 | 0.00 | 0.00 | 0.854460E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 58237306.53 | 0.00 | 0.00 | 0.594668E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.116857E+09 | 0.00 | 0.00 | 0.555947E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 79899317.21 | 0.00 | 0.00 | 0.405753E+09 | 0.00 | 0.29 |
May | 0.00 | 35714.39 | 0.00 | 7555626.75 | 0.00 | 0.00 | 0.430495E+09 | 0.00 | 0.29 |
June | 0.00 | 4953094.23 | 0.00 | 44482470.07 | 0.00 | 0.00 | 0.212734E+09 | 0.00 | 0.30 |
July | 0.00 | 6337419.57 | 0.00 | 28906571.18 | 0.00 | 0.00 | 0.113807E+09 | 0.00 | 0.28 |
August | 0.00 | 3442560.72 | 0.00 | 36902398.71 | 0.00 | 0.00 | 0.185427E+09 | 0.00 | 0.31 |
September | 0.00 | 6010699.85 | 0.00 | 7836455.23 | 0.00 | 0.00 | 0.308635E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 65937819.00 | 0.00 | 0.00 | 0.386747E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.105826E+09 | 0.00 | 0.00 | 0.450703E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 76945625.54 | 0.00 | 0.00 | 0.659432E+09 | 0.00 | 0.28 |
Annual Sum or Average | 6314772.09 | 20779488.76 | 0.00 | 0.634228E+09 | 0.00 | 0.00 | 0.515881E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 4840184.22 | 0.00 | 0.00 | 0.113807E+09 | 0.00 | 0.28 |
Maximum of Months | 6314772.09 | 6337419.57 | 0.00 | 0.116857E+09 | 0.00 | 0.00 | 0.854460E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.182130E+10 | 0.00 | 0.00 | 20177703.04 | 0.00 | 0.00 | 0.677417E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 0.498934E+09 | 0.00 | 0.00 | 0.603012E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.107402E+10 | 0.00 | 0.00 | 0.565399E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.740742E+09 | 0.00 | 0.00 | 0.411570E+10 | 0.00 | 0.29 |
May | 28998658.19 | 318010.31 | 0.00 | 61799666.93 | 0.00 | 0.00 | 0.428929E+10 | 0.00 | 0.29 |
June | 0.00 | 49089723.99 | 0.00 | 0.416066E+09 | 0.00 | 0.00 | 0.215574E+10 | 0.00 | 0.30 |
July | 0.00 | 62732593.48 | 0.00 | 0.270825E+09 | 0.00 | 0.00 | 0.115550E+10 | 0.00 | 0.28 |
August | 0.00 | 34306976.82 | 0.00 | 0.345517E+09 | 0.00 | 0.00 | 0.187913E+10 | 0.00 | 0.31 |
September | 0.00 | 58961479.96 | 0.00 | 62811799.85 | 0.00 | 0.00 | 0.310239E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 0.588179E+09 | 0.00 | 0.00 | 0.393878E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.945728E+09 | 0.00 | 0.00 | 0.461957E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.683949E+09 | 0.00 | 0.00 | 0.667582E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.185030E+10 | 0.205409E+09 | 0.00 | 0.570875E+10 | 0.00 | 0.00 | 0.503902E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 20177703.04 | 0.00 | 0.00 | 0.115550E+10 | 0.00 | 0.28 |
Maximum of Months | 0.182130E+10 | 62732593.48 | 0.00 | 0.107402E+10 | 0.00 | 0.00 | 0.677417E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.539474E+09 | 0.00 | 0.00 | 736423.54 | 0.00 | 0.00 | 0.313682E+09 | 0.00 | 0.28 |
February | 59007.54 | 0.00 | 0.00 | 39626661.24 | 0.00 | 0.00 | 0.613183E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 96664389.57 | 0.00 | 0.00 | 0.576140E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 69657472.01 | 0.00 | 0.00 | 0.415993E+09 | 0.00 | 0.29 |
May | 47461939.44 | 34917.78 | 0.00 | 4987925.69 | 0.00 | 0.00 | 0.385484E+09 | 0.00 | 0.29 |
June | 0.00 | 4943068.26 | 0.00 | 39357186.39 | 0.00 | 0.00 | 0.217946E+09 | 0.00 | 0.30 |
July | 0.00 | 6298176.64 | 0.00 | 26110825.98 | 0.00 | 0.00 | 0.116689E+09 | 0.00 | 0.28 |
August | 0.00 | 3429323.89 | 0.00 | 33520179.37 | 0.00 | 0.00 | 0.189500E+09 | 0.00 | 0.31 |
September | 27425396.20 | 5899406.12 | 0.00 | 4670647.71 | 0.00 | 0.00 | 0.284715E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 49568901.86 | 0.00 | 0.00 | 0.403118E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 83511412.24 | 0.00 | 0.00 | 0.473018E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 61986800.01 | 0.00 | 0.00 | 0.673727E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.614421E+09 | 20604892.69 | 0.00 | 0.510399E+09 | 0.00 | 0.00 | 0.466319E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 736423.54 | 0.00 | 0.00 | 0.116689E+09 | 0.00 | 0.28 |
Maximum of Months | 0.539474E+09 | 6298176.64 | 0.00 | 96664389.57 | 0.00 | 0.00 | 0.673727E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.107021E+10 | 0.00 | 0.00 | 0.383963E+12 | 0.00 | 5.70 |
February | 0.904997E+10 | 0.00 | 0.00 | 0.304342E+10 | 0.00 | 0.00 | 0.441412E+12 | 0.00 | 10.20 |
March | 0.553717E+10 | 0.00 | 0.00 | 0.594358E+10 | 0.00 | 0.00 | 0.690547E+12 | 0.00 | 15.29 |
April | 0.00 | 0.00 | 0.00 | 0.681842E+10 | 0.00 | 0.00 | 0.102396E+13 | 0.00 | 34.47 |
May | 1076822.80 | 0.00 | 0.00 | 0.805964E+09 | 0.00 | 0.00 | 0.383560E+12 | 0.00 | 12.49 |
June | 0.188993E+10 | 47194035.57 | 0.00 | 0.274583E+10 | 29196.63 | 0.00 | 0.359163E+12 | 0.00 | 21.23 |
July | 0.912779E+09 | 86585263.11 | 0.00 | 0.365416E+10 | 0.00 | 0.00 | 0.447233E+12 | 0.00 | 33.13 |
August | 0.00 | 52738536.71 | 0.00 | 0.492839E+10 | 0.00 | 0.00 | 0.739362E+12 | 0.00 | 45.48 |
September | 1518016.18 | 18347346.70 | 0.00 | 0.802852E+09 | 0.00 | 0.00 | 0.312523E+12 | 0.00 | 14.02 |
October | 0.475712E+10 | 0.00 | 0.00 | 0.364478E+10 | 0.00 | 0.00 | 0.506983E+12 | 0.00 | 17.20 |
November | 0.232016E+10 | 0.00 | 0.00 | 0.705603E+10 | 0.00 | 0.00 | 0.747636E+12 | 0.00 | 18.98 |
December | 0.00 | 0.00 | 0.00 | 0.645791E+10 | 0.00 | 0.00 | 0.102911E+13 | 0.00 | 21.03 |
Annual Sum or Average | 0.244697E+11 | 0.204865E+09 | 0.00 | 0.469716E+11 | 29196.63 | 0.00 | 0.706545E+13 | 0.00 | 20.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.802852E+09 | 0.00 | 0.00 | 0.312523E+12 | 0.00 | 5.70 |
Maximum of Months | 0.904997E+10 | 86585263.11 | 0.00 | 0.705603E+10 | 29196.63 | 0.00 | 0.102911E+13 | 0.00 | 45.48 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:22:34
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.282005E+12 | 0.454748E+11 | 0.00 | 0.220032E+13 | 0.490146E+12 |
February | 0.368885E+12 | 0.348672E+11 | 0.00 | 0.227502E+13 | 0.654480E+12 |
March | 0.615778E+12 | 0.322729E+11 | 0.00 | 0.289391E+13 | 0.868212E+12 |
April | 0.654665E+12 | 0.226341E+11 | 0.00 | 0.343570E+13 | 0.854326E+12 |
May | 0.866108E+12 | 0.219718E+11 | 0.00 | 0.273289E+13 | 0.523931E+12 |
June | 0.934020E+12 | 0.111097E+11 | 0.00 | 0.238423E+13 | 0.159077E+13 |
July | 0.926939E+12 | 0.726992E+10 | 0.00 | 0.214160E+13 | 0.258285E+13 |
August | 0.770027E+12 | 0.783487E+10 | 0.00 | 0.262778E+13 | 0.250211E+13 |
September | 0.579749E+12 | 0.142370E+11 | 0.00 | 0.240789E+13 | 0.887977E+12 |
October | 0.378336E+12 | 0.211962E+11 | 0.00 | 0.299841E+13 | 0.737495E+12 |
November | 0.212717E+12 | 0.309243E+11 | 0.00 | 0.291114E+13 | 0.793279E+12 |
December | 0.179278E+12 | 0.404852E+11 | 0.00 | 0.293285E+13 | 0.101277E+13 |
Annual Sum or Average | 0.676851E+13 | 0.290278E+12 | 0.00 | 0.319418E+14 | 0.134983E+14 |
Minimum of Months | 0.179278E+12 | 0.726992E+10 | 0.00 | 0.214160E+13 | 0.490146E+12 |
Maximum of Months | 0.934020E+12 | 0.454748E+11 | 0.00 | 0.343570E+13 | 0.258285E+13 |