Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2024-07-03 12:26:36
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31071.95 | 670.81 | 670.81 |
Net Site Energy | 31071.95 | 670.81 | 670.81 |
Total Source Energy | 95130.88 | 2053.76 | 2053.76 |
Net Source Energy | 95130.88 | 2053.76 | 2053.76 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1571.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1156.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1004.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2596.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 672.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 20.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2231.19 |
Humidification | 681.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.49 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 457.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 29500.18 | 1571.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4764.86 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1571.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1156.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 1004.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 56.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2596.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 672.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 20.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2231.19 |
Humidification | General | 681.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.49 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 457.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1571.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1156.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 1004.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2596.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 672.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 20.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2231.19 |
Humidification | Unassigned | 681.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.49 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 457.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 120.57 | 33.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 636.87 | 33.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 120.57 | 33.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 636.87 | 33.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 29500.185 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 29500.185 | 100.00 |
Total On-Site and Utility Electric Sources | 29500.185 | 100.00 |
Total Electricity End Uses | 29500.185 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 4764.86 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 4764.86 | 100.00 |
Total Water End Uses | 4764.86 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 5.83 |
Time Setpoint Not Met During Occupied Cooling | 64.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4814.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS SZVAV FAN | AIRLOOP DATACENTER BASEMENT SYS11 FAN | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 11.6510 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 11.6510 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 11.6510 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.6510 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 11.6510 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.6510 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 11.6510 | 18.58 | 484.4232 | |
Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.6100 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 25-AUG-14:00 | 26-DEC-05:19 | - | - | - | - | - | - | - | - | - | - | 21-JUL-16:30 |
Heating | 0.00 | 960582.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 265297.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235096.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 226410.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 73182.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 20919.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 27163.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2216341.48 | 960582.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 960582.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 265297.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 226410.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 73182.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 20919.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 27163.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1703.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3661.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17769.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3182.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8307.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8224.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2129.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 65.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 2158.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1448.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 93427.09 | 1703.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 36.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 79.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 177.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 45.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 46.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2016.98 | 36.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 36.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 79.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 177.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 45.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 46.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2016.98 | 36.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 7.03 | 0.301401 | 0.300000 | 2.11 |
DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | 31.70 | 0.018840 | 0.500000 | 15.85 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 7.39 | 0.257264 | 0.300000 | 2.22 | 0.686038 | 0.500000 | 0.001481 | 0.000191 | 2.22 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 70.02 | 0.271636 | 0.300000 | 21.01 | 0.724361 | 0.500000 | 0.001403 | 0.003762 | 21.01 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 7.37 | 0.257941 | 0.300000 | 2.21 | 0.687843 | 0.500000 | 0.001477 | 0.001217 | 5.91 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.07 | 0.222307 | 0.300000 | 0.322285 | 0.592818 | 0.500000 | 0.001714 | 0.000134 | 0.648982 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.61 | 0.095506 | 0.300000 | 0.483440 | 0.300000 | 0.500000 | 0.003989 | 0.000097 | 0.483440 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 2.31 | 0.103306 | 0.300000 | 0.693549 | 0.300000 | 0.500000 | 0.003688 | 0.000169 | 0.823335 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.97 | 0.078165 | 0.300000 | 0.590690 | 0.300000 | 0.500000 | 0.004874 | 0.000087 | 0.590690 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 11.75 | 0.203265 | 0.300000 | 3.52 | 0.542040 | 0.500000 | 0.001874 | 0.002415 | 11.75 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 16.69 | 0.300000 | 0.500000 | 0.004132 | 0.001626 | 7.91 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 23.61 | 0.101147 | 0.300000 | 7.08 | 0.300000 | 0.500000 | 0.003767 | 0.002444 | 11.89 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 18.12 | 0.084955 | 0.300000 | 5.43 | 0.300000 | 0.500000 | 0.004485 | 0.001503 | 7.31 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.64 | 0.145195 | 0.300000 | 0.493448 | 0.387187 | 0.500000 | 0.002624 | 0.000338 | 1.64 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.64 | 0.093708 | 0.300000 | 0.492715 | 0.300000 | 0.500000 | 0.004066 | 0.000224 | 1.09 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 2.55 | 0.093618 | 0.300000 | 0.765322 | 0.300000 | 0.500000 | 0.004070 | 0.000341 | 1.66 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.94 | 0.079426 | 0.300000 | 0.581314 | 0.300000 | 0.500000 | 0.004797 | 0.000215 | 1.05 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 21855.81 | 0.000191 | 440.92 | |
CORE_MID VAV BOX REHEAT COIL | 430024.39 | 0.003762 | 9702.77 | |
CORE_TOP VAV BOX REHEAT COIL | 139097.10 | 0.001217 | 3251.73 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 15285.69 | 0.000134 | 357.39 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11142.61 | 0.000097 | 258.98 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 19369.29 | 0.000169 | 452.72 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9990.83 | 0.000087 | 216.74 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 276020.99 | 0.002415 | 6448.94 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 185832.34 | 0.001626 | 4341.60 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 279405.91 | 0.002444 | 6527.95 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 171811.09 | 0.001503 | 4014.30 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 38606.26 | 0.000338 | 901.77 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 25654.64 | 0.000224 | 599.23 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 38951.16 | 0.000341 | 909.82 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 24581.95 | 0.000215 | 574.19 | |
VAV_BOT WITH REHEAT HEATING COIL | 44920.94 | 0.000393 | 766.36 | |
VAV_MID WITH REHEAT HEATING COIL | 324377.12 | 0.002838 | 5616.56 | |
VAV_TOP WITH REHEAT HEATING COIL | 28748.97 | 0.000252 | 505.29 | |
CAV_BAS HEATING COIL | 87214.40 | 0.000875 | 2622.63 | 100000.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 554035.36 | 0.000875 | 2622.63 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.776880 |
DATACENTER_MID_ZN_6 DIRECT AIR | 7.48 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.765306 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 7.18 | 4.31 | 14.36 | 4.31 | 12.01 | 12.01 | 0.300000 | 0.358756 | 12.01 |
VAV_MID WITH REHEAT | 70.10 | 42.06 | 140.19 | 54.76 | 110.50 | 110.50 | 0.300000 | 0.495608 | 110.50 |
VAV_TOP WITH REHEAT | 7.57 | 4.54 | 15.15 | 11.35 | 13.28 | 13.28 | 0.300000 | 0.854724 | 13.28 |
CAV_BAS | 2.11 | 2.11 | 7.03 | 2.11 | 7.03 | 7.03 | 1.00 | 0.300000 | 7.03 |
AIRLOOP DATACENTER BASEMENT | 15.85 | 15.85 | 31.70 | 15.85 | 31.70 | 31.70 | 1.00 | 0.499984 | 31.70 |
AIRLOOP DATACENTER BOT | 0.776880 | 0.776880 | 0.776880 | 0.776880 | 0.776880 | 0.776880 | 1.00 | 1.00 | 0.776880 |
AIRLOOP DATACENTER MID | 7.48 | 7.48 | 7.48 | 7.48 | 7.48 | 7.48 | 1.00 | 1.00 | 7.48 |
AIRLOOP DATACENTER TOP | 0.765306 | 0.765306 | 0.765306 | 0.765306 | 0.765306 | 0.765306 | 1.00 | 1.00 | 0.765306 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 12.01 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 110.50 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 13.28 | |
CAV_BAS_OA_CONTROLLER | 7.03 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 31.70 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.776880 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 7.48 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.765306 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 24.40 | 6.67 | 11.09 | 0.008734 | 0.008500 | 202926.68 | 0.007248 | 12.01 |
VAV_MID WITH REHEAT COOLING COIL | 24.44 | 6.67 | 11.09 | 0.008748 | 0.008500 | 1876700.07 | 0.067031 | 110.50 |
VAV_TOP WITH REHEAT COOLING COIL | 24.37 | 6.67 | 11.10 | 0.008715 | 0.008500 | 222943.35 | 0.007963 | 13.28 |
CAV_BAS COOLING COIL | 23.31 | 6.67 | 11.08 | 0.008826 | 0.008500 | 109044.59 | 0.003895 | 7.03 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 26.99 | 6.67 | 15.04 | 0.008532 | 0.008500 | 448153.54 | 0.016007 | 31.70 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 12.01 |
VAV_MID WITH REHEAT FAN | 110.50 |
VAV_TOP WITH REHEAT FAN | 13.28 |
CAV_BAS SZVAV FAN | 7.03 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | 31.70 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007248 | 0.000066 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000393 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.067031 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.002838 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.007963 | 0.000060 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000252 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | Design Size Minimum Supply Air Temperature [C] | User-Specified Minimum Supply Air Temperature [C] | User-Specified Maximum Supply Air Temperature [C] | User-Specified Nominal Cooling Capacity [W] | Design Size Maximum Supply Air Temperature [C] | |
CAV_BAS_UNITARY_PACKAGE_DX | 7.03 | 7.03 | 7.03 | 2.11 | 109044.59 | 100000.00 | 1.00 | 5.33 | 12.89 | 32.11 | ||
AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | 31.70 | 31.70 | 31.70 | 15.85 | 448153.54 | 100000.00 | 1.00 | 15.89 | 29.11 | |||
AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | 0.776880 | 0.776880 | 0.776880 | 0.776880 | 27154.21 | 1.00 | 12860.11 | 29.11 | ||||
AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | 7.48 | 7.48 | 7.48 | 7.48 | 261413.42 | 1.00 | 123789.99 | 29.11 | ||||
AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | 0.765306 | 0.765306 | 0.765306 | 0.765306 | 26750.89 | 1.00 | 12668.54 | 29.11 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000213 | 0.000037 | 96450.70 | 100000.00 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | 0.776880 | 1335.95 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | 7.48 | 12859.72 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | 0.765306 | 1316.05 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
AIRLOOP DATACENTER BOT COOLING COIL | 0.776880 | 0.388440 | 0.517920 | 12860.11 | 6430.06 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER MID COOLING COIL | 7.48 | 3.74 | 4.99 | 123789.99 | 61895.00 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.765310 | 0.382653 | 0.510207 | 12668.54 | 6334.27 | 0.800660 | 0.800660 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BOT HEATING COIL | 27154.21 |
AIRLOOP DATACENTER MID HEATING COIL | 261413.42 |
AIRLOOP DATACENTER TOP HEATING COIL | 26750.89 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.102144 | 21048.17 | |
HEATSYS1 PUMP | 0.019996 | 6021.95 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.102144 | 12.26 |
HEATSYS1 | 0.019996 | 2.40 |
COOLSYS1_SUPPLY | 0.102144 | 12.26 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.102144 | 0.102144 | 428750.86 | 6.67 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2285677.07 | 2285677.07 | 0.019996 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.051072 | 9714.70 |
COOLSYS1 CHILLER2 PUMP | 0.051072 | 9714.70 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.102144 | 0.051590 | 1444382.62 | 1444351.52 | 0.072386 |
COOLSYS1 CHILLER2 | 0.102144 | 0.051590 | 1444382.62 | 1444351.52 | 0.072386 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.144772 | 17.37 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.144772 | 50482.03 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 58.97 | 1731258.43 | 11.79 | 216407.30 |
TOWERWATERSYS COOLTOWER 2 | 58.97 | 1731258.43 | 11.79 | 216407.30 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 11.651 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 16.493 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 11.651 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 496.074 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 32383.100 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 32383.100 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 9130.649 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 9130.649 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
26 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
27 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
35 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
47 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
48 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
49 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
50 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
51 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
52 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
53 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
54 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
55 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
56 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
57 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
58 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
59 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
60 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
61 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
62 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
63 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
64 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
65 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
66 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
67 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
68 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
69 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
70 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
71 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
72 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
73 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
74 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
75 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
76 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
77 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
78 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
79 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
80 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
81 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
82 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
83 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
84 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
85 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
86 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
87 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
88 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
89 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
90 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
91 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
92 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
93 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
94 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
95 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
96 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
97 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
98 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
99 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
100 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
101 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
102 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
103 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
104 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
105 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
106 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
107 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
108 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
109 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
110 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
111 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
112 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
113 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
114 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
115 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
116 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
117 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
118 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
119 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
120 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
121 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone BASEMENT | 1.2500 |
3 | Zone CORE_BOTTOM | 1.2500 |
4 | Zone CORE_MID | 1.2500 |
5 | Zone CORE_TOP | 1.2500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.2500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.2500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.2500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone BASEMENT | 1.1500 |
3 | Zone CORE_BOTTOM | 1.1500 |
4 | Zone CORE_MID | 1.1500 |
5 | Zone CORE_TOP | 1.1500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.1500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.1500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.1500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 83284.46098 | 95777.13013 | 6.11037 | 7.02693 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | -4.30000 | 2.65759E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 87632.61642 | 100777.50888 | 6.42900 | 7.39335 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | -4.30000 | 2.65759E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 830143.00349 | 954664.45402 | 60.88861 | 70.02190 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 178423.57308 | 223029.46635 | 12.71627 | 15.89534 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 86622.57284 | 99615.95876 | 6.41213 | 7.37395 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.40000 | 8.40708E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 64699.57695 | 80874.47119 | 4.72691 | 5.90864 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12619.88896 | 14512.87231 | 0.93416 | 1.07428 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 26.40000 | 8.40708E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 7114.47958 | 8893.09947 | 0.51919 | 0.64898 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 18930.49860 | 21770.07339 | 1.40127 | 1.61147 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 21.10683 | 8.39884E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 5104.21834 | 6380.27292 | 0.37291 | 0.46614 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 27157.90332 | 31231.58882 | 2.01029 | 2.31183 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 26.09667 | 8.40660E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 9006.37794 | 11257.97243 | 0.65867 | 0.82334 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 23130.24975 | 26599.78721 | 1.71214 | 1.96897 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.12600 | 8.40508E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 3339.69767 | 4174.62209 | 0.24267 | 0.30334 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 115016.74567 | 132269.25752 | 8.51385 | 9.79093 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40000 | 8.40708E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 128220.45345 | 160275.56681 | 9.39938 | 11.74923 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 196096.65159 | 225511.14933 | 14.51545 | 16.69277 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 21.65283 | 8.39969E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 86315.76395 | 107894.70494 | 6.32908 | 7.91135 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 277375.13618 | 318981.40660 | 20.53187 | 23.61165 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 129788.68633 | 162235.85792 | 9.51504 | 11.89380 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 212815.65098 | 244737.99863 | 15.75301 | 18.11597 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.97433 | 8.40484E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 79818.80597 | 99773.50746 | 5.85011 | 7.31264 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13834.88211 | 15910.11442 | 1.02409 | 1.17771 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.40000 | 8.40708E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 17921.67656 | 22402.09570 | 1.31586 | 1.64483 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 19293.74808 | 22187.81029 | 1.42816 | 1.64238 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 22.16850 | 8.40048E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 11908.70856 | 14885.88570 | 0.87448 | 1.09310 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 29968.47823 | 34463.74996 | 2.21832 | 2.55107 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 26.24833 | 8.40684E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 18081.48705 | 22601.85881 | 1.32764 | 1.65956 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 22763.15872 | 26177.63253 | 1.68497 | 1.93771 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.97433 | 8.40484E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 11411.55928 | 14264.44910 | 0.83784 | 1.04730 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 9126.16673 | 10495.09174 | 0.67555 | 0.77688 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 23.07850 | 8.40189E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | -4.30000 | 2.65759E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 87847.12094 | 101024.18908 | 6.50274 | 7.47815 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 23.07850 | 8.40189E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -4.30000 | 2.65759E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8990.20741 | 10338.73852 | 0.66548 | 0.76531 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 23.07850 | 8.40189E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -4.30000 | 2.65759E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372346.50966 | 428198.48611 | 27.56179 | 31.69606 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 18.11900 | 8.39428E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -4.30000 | 2.65759E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 165548.92 | 12.00808 | 12.00808 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 42716.36 | 3.31962 | 3.31962 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1528001.93 | 110.49538 | 110.49538 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 414452.16 | 54.76235 | 54.76235 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 182425.72 | 13.28315 | 13.28315 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 41753.46 | 11.35342 | 11.35342 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 03:40:00 |
7 | CAV_BAS | Cooling | Sensible | 87671.17 | 7.02693 | 7.02693 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 52313.15 | 1.20016 | 1.20016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 420952.09 | 31.69708 | 31.69708 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 13534.74 | 0.33839 | 0.33839 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 10259.44 | 0.77688 | 0.77688 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 625.25 | 1.56323E-002 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 98728.36 | 7.47815 | 7.47815 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6252.49 | 0.15632 | 0.15632 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 10108.85 | 0.76531 | 0.76531 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 625.25 | 1.56323E-002 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 7.02693 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.30140 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 2.10808 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.39335 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25726 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.21800 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68604 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.48097E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.91204E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.21800 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21855.80906 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.91204E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 440.91998 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 70.02190 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27164 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 21.00657 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72436 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.40261E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.76204E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 21.00657 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 430024.38671 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.76204E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 9702.77336 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.37395 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25794 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.21218 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68784 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.47708E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21688E-003 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.90864 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 139097.09822 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21688E-003 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3251.72534 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07428 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22231 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32229 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59282 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.71385E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.33726E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.64898 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15285.69446 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.33726E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 357.39034 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.61147 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.55063E-002 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.48344 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.98927E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.74804E-005 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.48344 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11142.61034 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.74804E-005 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 258.97600 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.31183 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10331 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.69355 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.68807E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.69451E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.82334 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19369.28607 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69451E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 452.71780 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.96897 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.81654E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.59069 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.87428E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.74041E-005 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.59069 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9990.82543 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74041E-005 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 216.73843 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.74923 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20326 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.52477 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54204 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.87440E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.41475E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 11.74923 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 276020.98931 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.41475E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6448.93583 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 16.69277 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.13238E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.62574E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.91135 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 185832.34160 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.62574E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4341.60138 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 23.61165 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10115 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 7.08349 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.76678E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.44436E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 11.89380 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 279405.90835 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.44436E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6527.94684 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.11597 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.49555E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.43479 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.48470E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.50308E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.31264 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 171811.09112 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.50308E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4014.29700 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.64483 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14519 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.49345 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38719 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.62406E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.37744E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.64483 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 38606.26087 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.37744E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 901.76621 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.64238 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.37084E-002 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.49271 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.06580E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.24438E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.09310 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25654.64155 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.24438E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 599.22988 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.55107 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.36178E-002 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76532 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.06974E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.40762E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.65956 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 38951.15608 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.40762E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 909.81699 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.93771 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.94261E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.58131 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.79691E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.15054E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.04730 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24581.94613 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.15054E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 574.18821 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.77688 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.47815 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.76531 |
215 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 31.69606 |
216 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 1.88403E-002 |
217 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
218 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 15.84803 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.17995 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.30797 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 14.35989 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.30797 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 12.00808 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 12.00808 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.35876 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 70.09576 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 42.05745 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 140.19151 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 54.76235 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 110.49538 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 110.49538 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.49561 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.57497 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.54498 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 15.14994 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.35342 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 13.28315 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 13.28315 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.85472 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.10808 |
244 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.10808 |
245 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.02693 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.10808 |
247 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.02693 |
248 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 7.02693 |
249 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.30000 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 15.84803 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 15.84803 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 31.69606 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 15.84803 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 31.69708 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 31.69708 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.49998 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.77688 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.77688 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.77688 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.77688 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.77688 |
264 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.77688 |
265 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.47815 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.47815 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.47815 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 7.47815 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.47815 |
272 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 7.47815 |
273 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
274 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.76531 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.76531 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.76531 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.76531 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.76531 |
280 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.76531 |
281 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
282 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
283 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 12.00808 |
284 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 110.49538 |
285 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 13.28315 |
286 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 7.02693 |
287 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 31.69708 |
288 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.77688 |
289 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 7.47815 |
290 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.76531 |
291 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 12.00808 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.40487 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.09183 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.73438E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 202926.68029 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.24807E-003 |
299 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 12.00808 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 44920.93841 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.92988E-004 |
302 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 766.36296 |
303 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 12.00808 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.24807E-003 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.56989E-005 |
306 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.92988E-004 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 110.49538 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.44011 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.09188 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.74837E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1876700.06934 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.70314E-002 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 110.49538 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 324377.12076 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.83779E-003 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5616.56196 |
319 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 110.49538 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.70314E-002 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.10399E-006 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.83779E-003 |
323 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 13.28315 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.36608 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.09937 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.71496E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 222943.34614 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.96302E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 13.28315 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 28748.96718 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.51509E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 505.28700 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 13.28315 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.96302E-003 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.98002E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.51509E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.02693 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.02693 |
342 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.02693 |
343 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.02693 |
344 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.10808 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 23.31061 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.08253 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.82637E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 109044.58899 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.89482E-003 |
352 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.02693 |
353 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 109044.58899 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 87214.40406 |
355 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
356 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
357 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.62541 |
358 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
359 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
360 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Minimum Supply Air Temperature [C] | 5.33072 |
361 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 12.88890 |
362 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 32.11110 |
363 | Fan:VariableVolume | CAV_BAS SZVAV FAN | Design Size Maximum Flow Rate [m3/s] | 7.02693 |
364 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 31.69708 |
365 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
366 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 31.69708 |
367 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 31.69708 |
368 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 31.69708 |
369 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 15.84854 |
370 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.99157 |
371 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
372 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 15.03517 |
373 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.53167E-003 |
374 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
375 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Coil Load [W] | 448153.53867 |
376 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.60070E-002 |
377 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 31.69708 |
378 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 448153.53867 |
379 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Capacity [W] | 554035.35843 |
380 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
381 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
382 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.62541 |
383 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
384 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
385 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 15.88890 |
386 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 29.11110 |
387 | Fan:VariableVolume | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Design Size Maximum Flow Rate [m3/s] | 31.69708 |
388 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.12576E-004 |
389 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
390 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
391 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.77688 |
393 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
394 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.77688 |
395 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1335.95232 |
396 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.77688 |
397 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.77688 |
398 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.77688 |
399 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77688 |
400 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.77688 |
401 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.38844 |
402 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.51792 |
403 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 12860.11000 |
404 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6430.05500 |
405 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
406 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
407 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 12860.11000 |
408 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27154.21074 |
409 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
410 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
411 | Coil:Heating:Fuel | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Nominal Capacity [W] | 27154.21074 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.47815 |
413 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
414 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.47815 |
415 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 12859.72368 |
416 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.47815 |
417 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.47815 |
418 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.47815 |
419 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 7.47815 |
420 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.47815 |
421 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.73908 |
422 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.98543 |
423 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 123789.99000 |
424 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 61894.99500 |
425 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
426 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
427 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 123789.99000 |
428 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 261413.42089 |
429 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
430 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
431 | Coil:Heating:Fuel | AIRLOOP DATACENTER MID HEATING COIL | Design Size Nominal Capacity [W] | 261413.42089 |
432 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.76531 |
433 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
434 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.76531 |
435 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1316.05062 |
436 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.76531 |
437 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.76531 |
438 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.76531 |
439 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76531 |
440 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.76531 |
441 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.38265 |
442 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.51021 |
443 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 12668.54000 |
444 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6334.27000 |
445 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
446 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
447 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 12668.54000 |
448 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26750.89286 |
449 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
450 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
451 | Coil:Heating:Fuel | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Nominal Capacity [W] | 26750.89286 |
452 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.10214 |
453 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 21048.17052 |
454 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.10214 |
455 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 12.25732 |
456 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.10214 |
457 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.10214 |
458 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 428750.85809 |
459 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 6.67000 |
460 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.99961E-002 |
461 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.39953 |
462 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.99961E-002 |
463 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 6021.94723 |
464 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
465 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2285677.07164 |
466 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2285677.07000 |
467 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.99961E-002 |
468 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.10214 |
469 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 12.25732 |
470 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 5.10721E-002 |
471 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 9714.69591 |
472 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 5.10721E-002 |
473 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 9714.69591 |
474 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.10214 |
475 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.15900E-002 |
476 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1444382.61997 |
477 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1444351.52000 |
478 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 7.23858E-002 |
479 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.10214 |
480 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.15900E-002 |
481 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1444382.61997 |
482 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1444351.52000 |
483 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 7.23858E-002 |
484 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
485 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
486 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
487 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
488 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
489 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.14477 |
490 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 17.37259 |
491 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.14477 |
492 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 50482.03203 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 58.96936 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1731258.42538 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.79387 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 216407.30317 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 58.96936 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1731258.42538 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.79387 |
500 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 216407.30317 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 20750.53 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 408039.29 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 131956.39 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 14500.98 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10570.87 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 18374.96 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9481.71 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 261851.82 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 176292.92 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 265062.99 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 162991.38 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 36624.50 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 24337.72 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 36951.69 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 23320.09 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 37076.70 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 275485.25 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 25113.68 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94837.48 |
20 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | 94837.48 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 267123.04 | 194584.34 | 72538.70 | 0.73 | 32572.70 | 330.37 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2464031.69 | 1793203.76 | 670827.92 | 0.73 | 300334.52 | 3046.16 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 294405.85 | 214752.34 | 79653.50 | 0.73 | 35896.55 | 364.08 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 151985.83 | 112261.77 | 39724.06 | 0.74 | 19317.08 | 195.92 |
5 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | 559537.75 | 429855.93 | 129681.82 | 0.77 | 54212.36 | 549.85 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | 12251.3 | 9.16 | 9.16 | |||
2 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | 117929.3 | 10.40 | 10.40 | |||
3 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | 12068.8 | 9.16 | 9.16 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 6.37 | 21.74 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 6.37 | 21.74 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.1088923721 | 0.1487845872 | Pass | Pass | 5.5537908793 | 57.6575263027 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 6.2488924235E-003 | 7.8106993351E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 7.1681052982E-003 | 7.5958326994E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 2.7482902713E-002 | 2.5168737130E-002 | Pass | Pass | 0.5796832953 | 0.6882808468 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.0833115976E-002 | 1.7470214510E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.1248542134E-002 | 9.6177956152E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 9.2828477259E-002 | 0.1227504828 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.7656585744E-002 | 6.0614748174E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.5423444618E-002 | 2.0423019735E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.3795218665E-002 | 8.9048061440E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1020427961 | 0.1232665026 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 5.2710776731E-002 | 5.8444306044E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2935870864 | 0.2964611436 | Pass | Pass | 12.8771468192 | 39.3501923522 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2361771611 | 0.2661601847 | Pass | Pass | 7.0242356444 | 20.7588049212 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2291376748 | 0.2043750803 | Pass | Pass | 3.4540917951 | 12.7958102051 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1406805120 | 0.1488536455 | Pass | Pass | 4.0535518186 | 13.1193046105 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.5556091994E-003 | 6.7945301646E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.8863288134E-003 | 9.1650368435E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1361896031 | 0.1021106488 | Pass | Pass | 0.5398640314 | 0.5227647218 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.2633802369E-006 | 1.7998180927E-006 | Pass | Pass | 5.4731185413E-003 | 5.6986699367E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.9548721445E-006 | 2.8447158740E-006 | Pass | Pass | 0.4216295888 | 3.0353355340 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.7428923587E-002 | 2.4794598868E-002 | Pass | Pass | 3.5051639775E-003 | 3.9364660900E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.2909808344E-002 | 1.1914057930E-002 | Pass | Pass | 9.6877714976E-004 | 9.6455156658E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5879.08 | 124.23 | 0.00 | 36987.64 | 7705.90 | 50696.87 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
North Total or Average | 1390.74 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 3.241 | 0.391 | 0.431 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 11.6510 | 2779.43 | 32383.10 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 333.79 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.6510 | 24961.20 | 290822.99 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 2997.66 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.6510 | 3134.13 | 36515.73 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.6510 | 3134.20 | 36516.53 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 11.6510 | 783.68 | 9130.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 94.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 22.3674 | 362.03 | 8097.60 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 83.47 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
Interior Lighting Total | 11.7515 | 46320.38 | 544334.28 | 1723.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 64082.80 | AstronomicalClock | - | 83.54 | 83.54 | 1004.92 | |
Exterior Lighting Total | 64082.80 | 1004.92 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2852316.90 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2285677.07 | 0.79 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1444351.52 | 6.11 | 1437303.87 | 6.08 | 6.37 | 21.74 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1444351.52 | 6.11 | 1437303.87 | 6.08 | 6.37 | 21.74 |
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1731258.43 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1731258.43 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 202926.68 | 267123.04 | 194584.34 | 72538.70 | 0.73 | - | 32572.70 | 330.37 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1876700.07 | 2464031.69 | 1793203.76 | 670827.92 | 0.73 | - | 300334.52 | 3046.16 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 222943.35 | 294405.85 | 214752.34 | 79653.50 | 0.73 | - | 35896.55 | 364.08 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 109044.59 | 151985.83 | 112261.77 | 39724.06 | 0.74 | - | 19317.08 | 195.92 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | 448153.54 | 559537.75 | 429855.93 | 129681.82 | 0.77 | - | 54212.36 | 549.85 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | 12860.11 | 10296.58 | 2563.53 | 0.80 | 3.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | 123789.99 | 99113.69 | 24676.30 | 0.80 | 3.50 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 12668.54 | 10143.19 | 2525.35 | 0.80 | 3.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
AIRLOOP DATACENTER BOT COOLING COIL | 12251.3 | 9.16 | 9.16 | ||||
AIRLOOP DATACENTER MID COOLING COIL | 117929.3 | 10.40 | 10.40 | ||||
AIRLOOP DATACENTER TOP COOLING COIL | 12068.8 | 9.16 | 9.16 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 21855.81 | 20750.53 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 430024.39 | 408039.29 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 139097.10 | 131956.39 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 15285.69 | 14500.98 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11142.61 | 10570.87 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 19369.29 | 18374.96 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 9990.83 | 9481.71 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 276020.99 | 261851.82 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 185832.34 | 176292.92 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 279405.91 | 265062.99 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 171811.09 | 162991.38 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 38606.26 | 36624.50 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 25654.64 | 24337.72 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 38951.16 | 36951.69 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 24581.95 | 23320.09 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 44920.94 | 37076.70 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 324377.12 | 275485.25 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 28748.97 | 25113.68 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94837.48 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | 100000.00 | 94837.48 | - |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | 27154.21 | 0.80 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | 261413.42 | 0.79 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | 26750.89 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 12.01 | 26250.91 | 2186.10 | 1.00 | 1.12 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 110.50 | 241554.30 | 2186.10 | 1.00 | 1.08 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 13.28 | 28915.42 | 2176.85 | 1.00 | 1.12 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
CAV_BAS SZVAV FAN | Fan:VariableVolume | 0.61 | 1337.13 | 7.03 | 15443.65 | 2197.78 | 1.00 | 1.13 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 0.61 | 637.69 | 31.70 | 32906.60 | 1038.16 | 1.00 | 1.19 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:20:00 |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.78 | 1335.95 | 1719.64 | 1.00 | 1.35 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 7.48 | 12859.72 | 1719.64 | 1.00 | 1.08 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.77 | 1316.05 | 1719.64 | 1.00 | 1.36 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.83 | 0.102144 | 21048.17 | 206063.11 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.019996 | 6021.95 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.051072 | 9714.70 | 190215.15 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.051072 | 9714.70 | 190215.15 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 209234.68 | 0.144772 | 50482.03 | 348701.22 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 83284.46 | 95777.13 | 34.46 | 6.110 | 7.027 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 19.67 | 0.00840 | 1.200 | 0.00 |
CORE_BOTTOM | 87632.62 | 100777.51 | 40.37 | 6.429 | 7.393 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00885 | 19.67 | 0.00840 | 1.078 | 0.00 |
CORE_MID | 830143.00 | 954664.45 | 382.46 | 60.889 | 70.022 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00887 | 19.67 | 0.00840 | 10.778 | 0.00 |
CORE_TOP | 86622.57 | 99615.96 | 39.91 | 6.412 | 7.374 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00885 | 26.40 | 0.00841 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12619.89 | 14512.87 | 46.31 | 0.934 | 1.074 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00880 | 26.40 | 0.00841 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 18930.50 | 21770.07 | 107.79 | 1.401 | 1.611 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00863 | 21.11 | 0.00840 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 27157.90 | 31231.59 | 99.65 | 2.010 | 2.312 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00864 | 26.10 | 0.00841 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 23130.25 | 26599.79 | 131.70 | 1.712 | 1.969 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00860 | 25.13 | 0.00841 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 115016.75 | 132269.26 | 422.03 | 8.514 | 9.791 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00882 | 26.40 | 0.00841 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 196096.65 | 225511.15 | 1116.53 | 14.515 | 16.693 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00862 | 21.65 | 0.00840 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 277375.14 | 318981.41 | 1017.75 | 20.532 | 23.612 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00863 | 26.17 | 0.00841 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 212815.65 | 244738.00 | 1211.72 | 15.753 | 18.116 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00861 | 24.97 | 0.00840 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13834.88 | 15910.11 | 50.76 | 1.024 | 1.178 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00876 | 26.40 | 0.00841 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 19293.75 | 22187.81 | 109.85 | 1.428 | 1.642 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 24.00 | 24.00 | 0.00862 | 22.17 | 0.00840 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 29968.48 | 34463.75 | 109.96 | 2.218 | 2.551 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00862 | 26.25 | 0.00841 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 22763.16 | 26177.63 | 129.61 | 1.685 | 1.938 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00860 | 24.97 | 0.00840 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 9126.17 | 10495.09 | 289.90 | 0.676 | 0.777 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00856 | 23.08 | 0.00840 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 87847.12 | 101024.19 | 2790.51 | 6.503 | 7.478 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00856 | 23.08 | 0.00840 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8990.21 | 10338.74 | 285.58 | 0.665 | 0.765 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00856 | 23.08 | 0.00840 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372346.51 | 428198.49 | 546.39 | 27.562 | 31.696 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00853 | 18.12 | 0.00839 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | 21.00 | 23.65 | 0.00266 | -4.30 | 0.00266 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | 19.60 | 21.88 | 0.00266 | -4.30 | 0.00266 | 1.078 | 0.00 |
CORE_MID | 178423.57 | 223029.47 | 89.35 | 12.716 | 15.895 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 10.778 | 0.00 |
CORE_TOP | 64699.58 | 80874.47 | 32.40 | 4.727 | 5.909 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 7114.48 | 8893.10 | 28.38 | 0.519 | 0.649 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 5104.22 | 6380.27 | 31.59 | 0.373 | 0.466 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -4.30 | 0.00266 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 9006.38 | 11257.97 | 35.92 | 0.659 | 0.823 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 3339.70 | 4174.62 | 20.67 | 0.243 | 0.303 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -4.30 | 0.00266 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 128220.45 | 160275.57 | 511.39 | 9.399 | 11.749 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -4.30 | 0.00266 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 86315.76 | 107894.70 | 534.20 | 6.329 | 7.911 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -4.30 | 0.00266 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 129788.69 | 162235.86 | 517.63 | 9.515 | 11.894 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -4.30 | 0.00266 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 79818.81 | 99773.51 | 493.99 | 5.850 | 7.313 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -4.30 | 0.00266 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 17921.68 | 22402.10 | 71.48 | 1.316 | 1.645 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 11908.71 | 14885.89 | 73.70 | 0.874 | 1.093 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -4.30 | 0.00266 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 18081.49 | 22601.86 | 72.11 | 1.328 | 1.660 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 11411.56 | 14264.45 | 70.62 | 0.838 | 1.047 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -4.30 | 0.00266 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | 18.00 | 26.30 | 0.00850 | -4.30 | 0.00266 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 23.53 | 0.00545 | -4.30 | 0.00266 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 20.90 | 0.00316 | -4.30 | 0.00266 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 27.00 | 0.00850 | -4.30 | 0.00266 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 12.01 | 12.01 | 3.32 | 3.32 | 12.0081 | 4.3080 | 12.0081 | 0.3588 | 0.3000 |
VAV_MID WITH REHEAT | 110.50 | 110.50 | 54.76 | 54.76 | 110.4954 | 54.7624 | 110.4954 | 0.4956 | 0.3000 |
VAV_TOP WITH REHEAT | 13.28 | 13.28 | 11.35 | 11.35 | 13.2831 | 11.3534 | 13.2831 | 0.8547 | 0.3000 |
CAV_BAS | 7.03 | 7.03 | 1.20 | 1.20 | 7.0269 | 2.1081 | 7.0269 | 0.3000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 31.70 | 31.70 | 0.34 | 0.34 | 31.6971 | 15.8480 | 31.6971 | 0.5000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.78 | 0.78 | 0.02 | 0.02 | 0.7769 | 0.7769 | 0.7769 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 7.48 | 7.48 | 0.16 | 0.16 | 7.4782 | 7.4782 | 7.4782 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.77 | 0.77 | 0.02 | 0.02 | 0.7653 | 0.7653 | 0.7653 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 21855.809 | 21855.809 | 2.218004 | 0.00019120 | 440.920 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | 21855.81 | 21855.81 | 2.218004 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 0.00 | 0.00 | 21964.71 | 21964.71 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 430024.387 | 430024.387 | 21.006571 | 0.00376204 | 9702.773 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 430024.39 | 430024.39 | 21.006571 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 223029.47 | 0.00 | 432049.88 | 432049.88 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 139097.098 | 139097.098 | 5.908637 | 0.00121688 | 3251.725 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 139097.10 | 139097.10 | 5.908637 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 80874.47 | 0.00 | 139734.61 | 139734.61 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 15285.694 | 15285.694 | 0.648982 | 0.00013373 | 357.390 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15285.69 | 15285.69 | 0.648982 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00782811 | 50.0835 | 8893.10 | 0.00 | 15355.75 | 15355.75 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 11142.610 | 11142.610 | 0.483440 | 0.00009748 | 258.976 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11142.61 | 11142.61 | 0.483440 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00786543 | 50.3190 | 6380.27 | 0.00 | 11193.80 | 11193.80 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 19369.286 | 19369.286 | 0.823335 | 0.00016945 | 452.718 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19369.29 | 19369.29 | 0.823335 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00790560 | 50.5725 | 11257.97 | 0.00 | 19458.07 | 19458.07 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 9990.825 | 9990.825 | 0.590690 | 0.00008740 | 216.738 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9990.83 | 9990.83 | 0.590690 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00763665 | 48.8741 | 4174.62 | 0.00 | 10038.56 | 10038.56 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 276020.989 | 276020.989 | 11.749227 | 0.00241475 | 6448.936 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 276020.99 | 274370.32 | 11.749227 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00788845 | 50.4646 | 160275.57 | 0.00 | 277286.35 | 277286.35 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 185832.342 | 185832.342 | 7.911353 | 0.00162574 | 4341.601 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 185832.34 | 185832.34 | 7.911353 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00789099 | 50.4806 | 107894.70 | 0.00 | 186684.26 | 186684.26 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 279405.908 | 279405.908 | 11.893796 | 0.00244436 | 6527.947 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 279405.91 | 279405.91 | 11.893796 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00789026 | 50.4760 | 162235.86 | 0.00 | 280686.79 | 280686.79 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 171811.091 | 171811.091 | 7.312635 | 0.00150308 | 4014.297 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 171811.09 | 171811.09 | 7.312635 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00787857 | 50.4022 | 99773.51 | 0.00 | 172598.71 | 172598.71 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 38606.261 | 38606.261 | 1.644827 | 0.00033774 | 901.766 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38606.26 | 38410.32 | 1.644827 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00790573 | 50.5738 | 22402.10 | 0.00 | 38783.26 | 38783.26 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 25654.642 | 25654.642 | 1.093099 | 0.00022444 | 599.230 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25654.64 | 25654.64 | 1.093099 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00790552 | 50.5725 | 14885.89 | 0.00 | 25772.26 | 25772.26 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 38951.156 | 38951.156 | 1.659556 | 0.00034076 | 909.817 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38951.16 | 38951.16 | 1.659556 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00790659 | 50.5792 | 22601.86 | 0.00 | 39129.74 | 39129.74 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 24581.946 | 24581.946 | 1.047303 | 0.00021505 | 574.188 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24581.95 | 24581.95 | 1.047303 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00790130 | 50.5459 | 14264.45 | 0.00 | 24694.65 | 24694.65 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 202926.680 | -999.000 | 12.008082 | 0.00724807 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 202926.68 | 194171.27 | 12.008082 | 24.40 | 16.62 | 0.00873438 | 11.09 | 11.09 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 16.9094 | 24.00 | 0.00880099 | 46.8540 | 141061.37 | 0.00 | 204753.17 | 185080.11 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 44920.938 | 44920.938 | 3.602425 | 0.00039299 | 766.363 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 44920.94 | 44920.94 | 3.602425 | 2.47 | 1.57 | 0.00391340 | 12.89 | 11.54 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 56.3648 | 21.22 | 0.00553652 | 35.0637 | 16952.59 | 0.00 | 44874.33 | 44874.33 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1876700.069 | -999.000 | 110.495380 | 0.06703138 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 1876700.07 | 1791336.38 | 110.495380 | 24.44 | 16.65 | 0.00874837 | 11.09 | 11.09 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 18.3772 | 24.00 | 0.00882521 | 46.9811 | 1298011.48 | 0.00 | 1893535.67 | 1708115.02 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 324377.121 | 324377.121 | 33.148614 | 0.00283779 | 5616.562 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 324377.12 | 324377.12 | 33.148614 | 4.71 | 3.74 | 0.00459663 | 12.89 | 11.54 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 61.2575 | 18.67 | 0.00770402 | 56.9681 | 148142.83 | 0.00 | 333470.27 | 333470.27 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 222943.346 | -999.000 | 13.283150 | 0.00796302 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 222943.35 | 214064.19 | 13.283150 | 24.37 | 16.59 | 0.00871496 | 11.10 | 11.10 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 15.2863 | 24.00 | 0.00877055 | 46.6941 | 155967.38 | 0.00 | 224957.73 | 203977.91 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 28748.967 | 28748.967 | 3.984945 | 0.00025151 | 505.287 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 03:40:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28748.97 | 28748.97 | 3.984945 | 6.86 | 5.57 | 0.00515558 | 12.89 | 11.54 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 50.9543 | 16.31 | 0.00786638 | 67.5132 | 15360.27 | 0.00 | 30402.39 | 30402.39 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 109044.589 | -999.000 | 7.026927 | 0.00389482 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 109044.59 | 102051.98 | 7.026927 | 23.31 | 16.32 | 0.00882637 | 11.08 | 11.08 | 0.00850000 | 19.67 | 0.00839663 | 14.61 | 17.0794 | 24.00 | 0.00891488 | 47.4522 | 83284.46 | 0.00 | 112479.14 | 99445.16 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.070992 | 0.00087484 | 2622.625 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.070992 | -0.73 | -2.19 | 0.00265759 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 39.0804 | 23.73 | 0.00265759 | 14.5229 | 0.00 | 0.00 | 100079.59 | 100079.59 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 448153.539 | -999.000 | 31.697081 | 0.01600701 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:20:00 | 448153.54 | 445884.59 | 31.697081 | 26.99 | 17.34 | 0.00853167 | 15.04 | 12.91 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 1.0676 | 27.00 | 0.00853301 | 38.0317 | 372008.42 | 0.00 | 467926.99 | 467926.99 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 100000.000 | 100000.000 | 3.070992 | 0.00087484 | 2622.625 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.070992 | -0.05 | -0.05 | 0.00843763 | 29.11 | 17.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 11.0190 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | 100079.59 | 100079.59 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER BOT | 12860.110 | 10296.576 | 0.776880 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 6430.06 | 6369.61 | 0.517920 | 26.92 | 17.34 | 0.00855878 | 14.47 | 12.69 | 0.00850000 | 23.08 | 0.00840189 | 15.87 | 3.0183 | 27.00 | 0.00856200 | 38.1571 | 9126.17 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER BOT | 27154.211 | 27154.211 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 27154.21 | 27154.21 | 0.776880 | -0.09 | -0.09 | 0.00838244 | 29.11 | 17.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 2.0122 | 26.71 | 0.00850000 | 38.5403 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER MID | 123789.990 | 99113.693 | 7.478150 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 61895.00 | 61291.20 | 4.985433 | 26.92 | 17.34 | 0.00856101 | 14.47 | 12.69 | 0.00850000 | 23.08 | 0.00840189 | 15.87 | 3.1356 | 27.00 | 0.00856441 | 38.1678 | 87847.12 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER MID | 261413.421 | 261413.421 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 261413.42 | 261413.42 | 7.478153 | -0.09 | -0.09 | 0.00539320 | 29.11 | 17.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 2.0904 | 24.66 | 0.00545161 | 28.0375 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER TOP | 12668.540 | 10143.193 | 0.765310 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 6334.27 | 6274.00 | 0.510207 | 26.92 | 17.34 | 0.00855952 | 14.47 | 12.69 | 0.00850000 | 23.31 | 0.00840224 | 15.95 | 3.0639 | 27.00 | 0.00856280 | 38.1606 | 8989.41 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER TOP | 26750.893 | 26750.893 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 26750.89 | 26750.89 | 0.765306 | -0.09 | -1.05 | 0.00315041 | 29.11 | 17.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 2.0426 | 22.89 | 0.00316069 | 18.1521 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 21855.809 | 21855.809 | 2.218004 | 0.00019120 | 440.920 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.99406031 | 54.44 | 82.22 | 27.78 | 2331677.23 | 0.9373 | 0.956207 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | Sensible | 21855.81 | 21855.81 | 1.0000 | 2.64246822 | 2.218004 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.19118465 | 60.00 | 32.22 | 27.78 | 0.000 | 21855.81 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 0.00 | 0.00 | 21964.71 | 21964.71 | 2.64246822 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 20.95 | 14.83 | 0.00800000 | 41372.0 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 430024.387 | 430024.387 | 21.006571 | 0.00376204 | 9702.773 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.99406031 | 54.44 | 82.22 | 27.78 | 2331677.23 | 18.4427 | 18.813873 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 430024.39 | 430024.39 | 1.0000 | 25.02664092 | 21.006571 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 3.76165716 | 60.00 | 32.22 | 27.78 | 0.000 | 430024.39 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.57 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 223029.47 | 0.00 | 432049.88 | 432049.88 | 25.02664092 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.73 | 17.95 | 0.00800000 | 50323.4 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 139097.098 | 139097.098 | 5.908637 | 0.00121688 | 3251.725 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.99406031 | 54.44 | 82.22 | 27.78 | 2331677.23 | 5.9655 | 6.085597 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 139097.10 | 139097.10 | 1.0000 | 7.03938440 | 5.908637 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 1.21675796 | 60.00 | 32.22 | 27.78 | 0.000 | 139097.10 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 80874.47 | 0.00 | 139734.61 | 139734.61 | 7.03938440 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.27 | 18.78 | 0.00800000 | 52910.2 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15285.694 | 15285.694 | 0.648982 | 0.00013373 | 357.390 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.99406031 | 54.44 | 82.22 | 27.78 | 2331677.23 | 0.6556 | 0.668760 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15285.69 | 15285.69 | 1.0000 | 0.77317867 | 0.648982 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.13371228 | 60.00 | 32.22 | 27.78 | 0.000 | 15285.69 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00782811 | 21.00 | 0.00782811 | 50.0835 | 8893.10 | 0.00 | 15355.75 | 15355.75 | 0.77317867 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.28 | 18.79 | 0.00800000 | 52920.4 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11142.610 | 11142.610 | 0.483440 | 0.00009748 | 258.976 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.99406031 | 54.44 | 82.22 | 27.78 | 2331677.23 | 0.4779 | 0.487497 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11142.61 | 11142.61 | 1.0000 | 0.57595652 | 0.483440 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.09747047 | 60.00 | 32.22 | 27.78 | 0.000 | 11142.61 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00786543 | 21.00 | 0.00786543 | 50.3190 | 6380.27 | 0.00 | 11193.80 | 11193.80 | 0.57595652 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.86 | 18.65 | 0.00800000 | 52495.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19369.286 | 19369.286 | 0.823335 | 0.00016945 | 452.718 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.99406031 | 54.44 | 82.22 | 27.78 | 2331677.23 | 0.8307 | 0.847420 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19369.29 | 19369.29 | 1.0000 | 0.98089846 | 0.823335 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.16943368 | 60.00 | 32.22 | 27.78 | 0.000 | 19369.29 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00790560 | 21.00 | 0.00790560 | 50.5725 | 11257.97 | 0.00 | 19458.07 | 19458.07 | 0.98089846 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.25 | 18.78 | 0.00800000 | 52896.8 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9990.825 | 9990.825 | 0.590690 | 0.00008740 | 216.738 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.99406031 | 54.44 | 82.22 | 27.78 | 2331677.23 | 0.4285 | 0.437106 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9990.83 | 9990.83 | 1.0000 | 0.70373138 | 0.590690 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.08739518 | 60.00 | 32.22 | 27.78 | 0.000 | 9990.83 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.86 | 0.00763665 | 21.00 | 0.00763665 | 48.8741 | 4174.62 | 0.00 | 10038.56 | 10038.56 | 0.70373138 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 26.79 | 16.94 | 0.00800000 | 47324.6 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 276020.989 | 276020.989 | 11.749227 | 0.00241475 | 6448.936 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.99406031 | 54.44 | 82.22 | 27.78 | 2331677.23 | 11.8379 | 12.076115 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 276020.99 | 274370.32 | 1.0000 | 13.99769997 | 11.749227 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 2.41450570 | 60.00 | 32.22 | 27.78 | 0.000 | 276020.99 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00788845 | 21.00 | 0.00788845 | 50.4646 | 160275.57 | 0.00 | 277286.35 | 277286.35 | 13.99769997 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52869.3 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 185832.342 | 185832.342 | 7.911353 | 0.00162574 | 4341.601 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.99406031 | 54.44 | 82.22 | 27.78 | 2331677.23 | 7.9699 | 8.130297 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 185832.34 | 185832.34 | 1.0000 | 9.42536428 | 7.911353 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 1.62557655 | 60.00 | 32.22 | 27.78 | 0.000 | 185832.34 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00789099 | 21.00 | 0.00789099 | 50.4806 | 107894.70 | 0.00 | 186684.26 | 186684.26 | 9.42536428 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52866.4 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 279405.908 | 279405.908 | 11.893796 | 0.00244436 | 6527.947 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.99406031 | 54.44 | 82.22 | 27.78 | 2331677.23 | 11.9830 | 12.224208 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 279405.91 | 279405.91 | 1.0000 | 14.16993574 | 11.893796 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 2.44411542 | 60.00 | 32.22 | 27.78 | 0.000 | 279405.91 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00789026 | 21.00 | 0.00789026 | 50.4760 | 162235.86 | 0.00 | 280686.79 | 280686.79 | 14.16993574 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52868.4 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 171811.091 | 171811.091 | 7.312635 | 0.00150308 | 4014.297 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.99406031 | 54.44 | 82.22 | 27.78 | 2331677.23 | 7.3686 | 7.516858 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 171811.09 | 171811.09 | 1.0000 | 8.71206873 | 7.312635 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 1.50292505 | 60.00 | 32.22 | 27.78 | 0.000 | 171811.09 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00787857 | 21.00 | 0.00787857 | 50.4022 | 99773.51 | 0.00 | 172598.71 | 172598.71 | 8.71206873 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52871.3 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 38606.261 | 38606.261 | 1.644827 | 0.00033774 | 901.766 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.99406031 | 54.44 | 82.22 | 27.78 | 2331677.23 | 1.6557 | 1.689051 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 38606.26 | 38410.32 | 1.0000 | 1.95960029 | 1.644827 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.33770996 | 60.00 | 32.22 | 27.78 | 0.000 | 38606.26 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00790573 | 21.00 | 0.00790573 | 50.5738 | 22402.10 | 0.00 | 38783.26 | 38783.26 | 1.95960029 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52851.2 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25654.642 | 25654.642 | 1.093099 | 0.00022444 | 599.230 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.99406031 | 54.44 | 82.22 | 27.78 | 2331677.23 | 1.1003 | 1.122409 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25654.64 | 25654.64 | 1.0000 | 1.30228813 | 1.093099 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.22441510 | 60.00 | 32.22 | 27.78 | 0.000 | 25654.64 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00790552 | 21.00 | 0.00790552 | 50.5725 | 14885.89 | 0.00 | 25772.26 | 25772.26 | 1.30228813 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.76 | 0.00800000 | 52849.8 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 38951.156 | 38951.156 | 1.659556 | 0.00034076 | 909.817 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.99406031 | 54.44 | 82.22 | 27.78 | 2331677.23 | 1.6705 | 1.704141 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 38951.16 | 38951.16 | 1.0000 | 1.97714818 | 1.659556 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.34072694 | 60.00 | 32.22 | 27.78 | 0.000 | 38951.16 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00790659 | 21.00 | 0.00790659 | 50.5792 | 22601.86 | 0.00 | 39129.74 | 39129.74 | 1.97714818 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52850.8 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24581.946 | 24581.946 | 1.047303 | 0.00021505 | 574.188 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 19.99406031 | 54.44 | 82.22 | 27.78 | 2331677.23 | 1.0543 | 1.075478 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24581.95 | 24581.95 | 1.0000 | 1.24772698 | 1.047303 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.21503165 | 60.00 | 32.22 | 27.78 | 0.000 | 24581.95 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00790130 | 21.00 | 0.00790130 | 50.5459 | 14264.45 | 0.00 | 24694.65 | 24694.65 | 1.24772698 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52851.5 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 202926.680 | -999.000 | 12.008082 | 0.00724807 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0768 | 1004.8586 | 1.1914 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 12.008082 | 14.30609322 | 4197.9300 | 999.8980 | 102.13387505 | 13.34 | 6.67 | 6.67 | 2859768.22 | 7.0959 | 7.095914 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 202926.68 | 194171.27 | 1.0000 | 14.30609322 | 12.008082 | 24.40 | 16.62 | 0.00873438 | 46763.4 | 11.09 | 11.09 | 0.00850000 | 32578.8 | 7.24733146 | 6.67 | 13.34 | 6.67 | 26250.907 | 176675.77 | 26.40 | 0.00840708 | 17.04 | 2.03050000 | 16.9094 | 24.00 | 0.00880099 | 24.00 | 0.00880099 | 46.8540 | 141061.37 | 0.00 | 204753.17 | 185080.11 | 14.30609322 | 24.40 | 16.73 | 0.00873438 | 46763.4 | 11.73 | 11.34 | 0.00818928 | 32451.1 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 44920.938 | 44920.938 | 3.602425 | 0.00039299 | 766.363 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 12.008082 | 14.30609322 | 4197.9300 | 999.8980 | 19.99406031 | 54.44 | 82.22 | 27.78 | 2331677.23 | 1.9266 | 1.965323 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 44920.94 | 44920.94 | 1.0000 | 4.29182797 | 3.602425 | 2.47 | 1.57 | 0.00391340 | 12290.0 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 0.39294788 | 60.00 | 32.22 | 27.78 | 0.000 | 44920.94 | -4.30 | 0.00265759 | -4.30 | 2.03050000 | 56.3648 | 11.22 | 0.00553556 | 21.22 | 0.00553652 | 35.0637 | 16952.59 | 0.00 | 44874.33 | 44874.33 | 4.29182797 | 2.80 | 1.82 | 0.00391340 | 12621.1 | 13.13 | 7.24 | 0.00391340 | 23076.9 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1876700.069 | -999.000 | 110.495380 | 0.06703138 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1028 | 1004.8586 | 1.1914 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 110.495380 | 131.64110286 | 4197.9300 | 999.8980 | 102.13387505 | 13.34 | 6.67 | 6.67 | 2859768.22 | 65.6242 | 65.624202 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 1876700.07 | 1791336.38 | 1.0000 | 131.64110286 | 110.495380 | 24.44 | 16.65 | 0.00874837 | 46835.0 | 11.09 | 11.09 | 0.00850000 | 32578.8 | 67.02454025 | 6.67 | 13.34 | 6.67 | 241554.299 | 1635145.77 | 26.40 | 0.00840708 | 17.04 | 20.30600000 | 18.3772 | 24.00 | 0.00882521 | 24.00 | 0.00882521 | 46.9811 | 1298011.48 | 0.00 | 1893535.67 | 1708115.02 | 131.64110286 | 24.44 | 16.76 | 0.00874837 | 46835.0 | 11.73 | 11.34 | 0.00819003 | 32450.9 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 324377.121 | 324377.121 | 33.148614 | 0.00283779 | 5616.562 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 110.495380 | 131.64110286 | 4197.9300 | 999.8980 | 19.99406031 | 54.44 | 82.22 | 27.78 | 2331677.23 | 13.9118 | 14.191730 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 324377.12 | 324377.12 | 1.0000 | 39.49233086 | 33.148614 | 4.71 | 3.74 | 0.00459663 | 16273.9 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 2.83750307 | 60.00 | 32.22 | 27.78 | 0.000 | 324377.12 | -4.30 | 0.00265759 | -4.30 | 20.30600000 | 61.2575 | 18.97 | 0.00766253 | 18.67 | 0.00770402 | 56.9681 | 148142.83 | 0.00 | 333470.27 | 333470.27 | 39.49233086 | 2.80 | 2.77 | 0.00459663 | 14333.4 | 11.13 | 7.09 | 0.00459663 | 22777.3 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 222943.346 | -999.000 | 13.283150 | 0.00796302 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0407 | 1004.8586 | 1.1914 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 13.283150 | 15.82517263 | 4197.9300 | 999.8980 | 102.13387505 | 13.34 | 6.67 | 6.67 | 2859768.22 | 7.7959 | 7.795854 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 222943.35 | 214064.19 | 1.0000 | 15.82517263 | 13.283150 | 24.37 | 16.59 | 0.00871496 | 46674.4 | 11.10 | 11.10 | 0.00850000 | 32586.5 | 7.96220745 | 6.67 | 13.34 | 6.67 | 28915.422 | 194027.92 | 26.40 | 0.00840708 | 17.04 | 2.03050000 | 15.2863 | 24.00 | 0.00877055 | 24.00 | 0.00877055 | 46.6941 | 155967.38 | 0.00 | 224957.73 | 203977.91 | 15.82517263 | 24.37 | 16.70 | 0.00871496 | 46674.4 | 11.74 | 11.34 | 0.00818946 | 32459.2 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 28748.967 | 28748.967 | 3.984945 | 0.00025151 | 505.287 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 13.283150 | 15.82517263 | 4197.9300 | 999.8980 | 19.99406031 | 54.44 | 82.22 | 27.78 | 2331677.23 | 1.2330 | 1.257788 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 03:40:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 28748.97 | 28748.97 | 1.0000 | 4.74755179 | 3.984945 | 6.86 | 5.57 | 0.00515558 | 19855.4 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 0.25148285 | 60.00 | 32.22 | 27.78 | 0.000 | 28748.97 | -4.30 | 0.00265759 | -4.30 | 2.03050000 | 50.9543 | 18.46 | 0.00775078 | 16.31 | 0.00786638 | 67.5132 | 15360.27 | 0.00 | 30402.39 | 30402.39 | 4.74755179 | 2.80 | 2.80 | 0.00515558 | 15734.2 | 9.11 | 6.77 | 0.00515558 | 22138.0 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 109044.589 | -999.000 | 7.026927 | 0.00389482 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2478 | 1004.8586 | 1.1914 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 7.026927 | 8.37168411 | 4197.9300 | 999.8980 | 102.13387505 | 13.34 | 6.67 | 6.67 | 2859768.22 | 3.8131 | 3.813057 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 109044.59 | 102051.98 | 1.0000 | 8.37168411 | 7.026927 | 23.31 | 16.32 | 0.00882637 | 45880.1 | 11.08 | 11.08 | 0.00850000 | 32569.3 | 3.89442275 | 6.67 | 13.34 | 6.67 | 15443.647 | 93600.94 | 19.67 | 0.00839663 | 14.61 | 1.20015641 | 17.0794 | 24.06 | 0.00891488 | 24.00 | 0.00891488 | 47.4522 | 83284.46 | 0.00 | 112479.14 | 99445.16 | 8.37168411 | 23.31 | 16.43 | 0.00882637 | 45880.1 | 11.68 | 11.34 | 0.00820919 | 32444.5 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.070992 | 0.00087484 | 2622.625 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 7.026927 | 8.37168411 | 4197.9300 | 999.8980 | 19.99406031 | 54.44 | 82.22 | 27.78 | 2331677.23 | 4.2888 | 4.375071 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.070992 | -0.73 | -2.19 | 0.00265759 | 5904.9 | 32.11 | 18.62 | 0.00800000 | 52750.5 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -4.30 | 0.00265759 | -4.30 | 1.20015641 | 39.0804 | 0.00 | 0.00265759 | 23.73 | 0.00265759 | 14.5229 | 0.00 | 0.00 | 100079.59 | 100079.59 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40241.1 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 448153.539 | -999.000 | 31.697081 | 0.01600701 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6999 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 31.697081 | 37.76301462 | 4197.9300 | 999.8980 | 102.13387505 | 13.34 | 6.67 | 6.67 | 2859768.22 | 15.6710 | 15.670974 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:20:00 | Sensible | 448153.54 | 445884.59 | 1.0000 | 37.76301462 | 31.697081 | 26.99 | 17.34 | 0.00853167 | 48887.5 | 15.04 | 12.91 | 0.00850000 | 36603.5 | 16.00537314 | 6.67 | 13.34 | 6.67 | 32906.601 | 415246.94 | 26.40 | 0.00840708 | 17.04 | 0.33839277 | 1.0676 | 27.00 | 0.00853301 | 27.00 | 0.00853301 | 38.0317 | 372008.42 | 0.00 | 467926.99 | 467926.99 | 37.76301462 | 26.99 | 17.46 | 0.00853167 | 48887.5 | 14.85 | 12.97 | 0.00853167 | 36496.3 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.070992 | 0.00087484 | 2622.625 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 31.697081 | 37.76301462 | 4197.9300 | 999.8980 | 19.99406031 | 54.44 | 82.22 | 27.78 | 2331677.23 | 4.2888 | 4.375071 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.070992 | -0.05 | -0.05 | 0.00843763 | 21055.2 | 29.11 | 17.62 | 0.00800000 | 49691.3 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -4.30 | 0.00265759 | -4.30 | 0.33839277 | 11.0190 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | 100079.59 | 100079.59 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40241.1 | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12860.110 | 10296.576 | 0.776880 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7503 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.776880 | 0.92555254 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 6430.06 | 6369.61 | 1.0000 | 0.61703539 | 0.517920 | 26.92 | 17.34 | 0.00855878 | 48883.6 | 14.47 | 12.69 | 0.00850000 | 36031.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6430.06 | 23.08 | 0.00840189 | 15.87 | 0.01563234 | 3.0183 | 27.00 | 0.00856200 | 27.00 | 0.00856200 | 38.1571 | 9126.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27154.211 | 27154.211 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.776880 | 0.92555254 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 27154.21 | 27154.21 | 1.0000 | 0.92555254 | 0.776880 | -0.09 | -0.09 | 0.00838244 | 20875.7 | 29.11 | 17.62 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27154.21 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 2.0122 | 0.00 | 0.00850000 | 26.71 | 0.00850000 | 38.5403 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 123789.990 | 99113.693 | 7.478150 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7545 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.478153 | 8.90926253 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 61895.00 | 61291.20 | 1.0000 | 5.93950574 | 4.985433 | 26.92 | 17.34 | 0.00856101 | 48886.1 | 14.47 | 12.69 | 0.00850000 | 36031.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61895.00 | 23.08 | 0.00840189 | 15.87 | 0.15632344 | 3.1356 | 27.00 | 0.00856441 | 27.00 | 0.00856441 | 38.1678 | 87847.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 261413.421 | 261413.421 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.478153 | 8.90926253 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 261413.42 | 261413.42 | 1.0000 | 8.90926253 | 7.478153 | -0.09 | -0.09 | 0.00539320 | 13396.8 | 29.11 | 17.62 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 261413.42 | -4.30 | 0.00265759 | -4.30 | 0.15632344 | 2.0904 | 0.00 | 0.00545161 | 24.66 | 0.00545161 | 28.0375 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12668.540 | 10143.193 | 0.765310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7517 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.765306 | 0.91176457 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 6334.27 | 6274.00 | 1.0000 | 0.60784594 | 0.510207 | 26.92 | 17.34 | 0.00855952 | 48889.0 | 14.47 | 12.69 | 0.00850000 | 36031.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6334.27 | 23.31 | 0.00840224 | 15.95 | 0.01563234 | 3.0639 | 27.00 | 0.00856280 | 27.00 | 0.00856280 | 38.1606 | 8989.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26750.893 | 26750.893 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.765306 | 0.91176457 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 26750.89 | 26750.89 | 1.0000 | 0.91176457 | 0.765306 | -0.09 | -1.05 | 0.00315041 | 7790.2 | 29.11 | 17.62 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26750.89 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 2.0426 | 0.00 | 0.00316069 | 22.89 | 0.00316069 | 18.1521 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 12.01 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 110.50 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 13.28 | - | |||
CAV_BAS_OA_CONTROLLER | FixedDryBulb | 1.20 | 7.03 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 31.70 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1826.83 | 1248.67 | 0.00 |
CORE_BOTTOM | 2179.00 | 872.00 | 12.67 |
CORE_MID | 1132.00 | 2528.33 | 12.00 |
CORE_TOP | 1350.00 | 4396.67 | 581.17 |
PERIMETER_BOT_ZN_3 | 1072.67 | 3926.17 | 78.50 |
PERIMETER_BOT_ZN_2 | 1334.17 | 4303.17 | 177.83 |
PERIMETER_BOT_ZN_1 | 1661.83 | 4054.50 | 266.67 |
PERIMETER_BOT_ZN_4 | 1650.17 | 3765.83 | 90.00 |
PERIMETER_MID_ZN_3 | 1492.67 | 4869.33 | 928.00 |
PERIMETER_MID_ZN_2 | 1570.50 | 3996.83 | 823.50 |
PERIMETER_MID_ZN_1 | 1887.33 | 4319.67 | 636.50 |
PERIMETER_MID_ZN_4 | 1502.00 | 4907.83 | 765.83 |
PERIMETER_TOP_ZN_3 | 2475.17 | 5251.83 | 2053.67 |
PERIMETER_TOP_ZN_2 | 2755.67 | 4675.00 | 1807.00 |
PERIMETER_TOP_ZN_1 | 2669.17 | 4588.67 | 1600.00 |
PERIMETER_TOP_ZN_4 | 2356.50 | 5036.33 | 1671.17 |
DATACENTER_BOT_ZN_6 | 5943.00 | 803.00 | 803.00 |
DATACENTER_MID_ZN_6 | 5924.83 | 276.50 | 276.50 |
DATACENTER_TOP_ZN_6 | 5380.50 | 489.00 | 373.17 |
DATACENTER_BASEMENT_ZN_6 | 5858.33 | 3274.17 | 3272.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5927.17 | 4814.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 4.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7.83 | 0.00 | 0.50 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 10.33 | 0.00 | 10.33 |
PERIMETER_BOT_ZN_1 | 0.00 | 12.50 | 0.00 | 12.50 |
PERIMETER_BOT_ZN_4 | 0.00 | 20.83 | 0.00 | 12.50 |
PERIMETER_MID_ZN_3 | 5.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7.50 | 8.67 | 0.00 | 8.67 |
PERIMETER_MID_ZN_1 | 4.50 | 12.83 | 0.00 | 12.83 |
PERIMETER_MID_ZN_4 | 4.17 | 13.67 | 0.00 | 7.67 |
PERIMETER_TOP_ZN_3 | 72.33 | 0.00 | 5.50 | 0.00 |
PERIMETER_TOP_ZN_2 | 66.50 | 4.17 | 3.00 | 4.17 |
PERIMETER_TOP_ZN_1 | 48.50 | 8.00 | 1.50 | 8.00 |
PERIMETER_TOP_ZN_4 | 31.33 | 13.67 | 0.00 | 7.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 1.33 | 0.00 | 0.83 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 80.00 | 83.83 | 5.83 | 64.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 1.065 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 1.062 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.851 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.751 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 1.026 | 0.025 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 2.086 | 0.026 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 2.110 | 0.025 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 2.612 | 0.026 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.935 | 0.059 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 1.929 | 0.064 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 2.072 | 0.059 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 2.242 | 0.061 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 1.146 | 0.072 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 1.902 | 0.075 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 2.045 | 0.073 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 2.250 | 0.075 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.425 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.425 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.425 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 23.124 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 60.99 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.86 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.79 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.20 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1010.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 42770147.39 | 0.00 | 42770147.39 | 0.00 | 42770147.39 | 37848132.68 | 4292.84 | 2323.40 | 2143.77 | 131.86 |
CORE_BOTTOM | 43587995.78 | 0.00 | 43587995.78 | 0.00 | 43587995.78 | 33990283.35 | 4345.21 | 46.32 | 4368.46 | 171.89 |
CORE_MID | 0.35E+09 | 0.00 | 0.35E+09 | 0.00 | 0.35E+09 | 0.34E+09 | 4962.58 | 72.72 | 3724.71 | 128.71 |
CORE_TOP | 30700984.94 | 0.00 | 30700984.94 | 0.00 | 30700984.94 | 33990283.35 | 5613.65 | 75.05 | 3071.30 | 296.07 |
PERIMETER_BOT_ZN_3 | 5306362.80 | 0.00 | 5306362.80 | 255127.48 | 5561490.28 | 4267819.30 | 4059.58 | 66.31 | 4634.12 | 171.89 |
PERIMETER_BOT_ZN_2 | 6999073.47 | 0.00 | 6999073.47 | 170084.87 | 7169158.34 | 2750345.05 | 3760.19 | 0.00 | 4999.81 | 171.89 |
PERIMETER_BOT_ZN_1 | 10945254.66 | 0.00 | 10945254.66 | 255127.48 | 11200382.14 | 4267912.63 | 3760.19 | 0.00 | 4999.81 | 171.89 |
PERIMETER_BOT_ZN_4 | 8758491.77 | 0.00 | 8758491.77 | 170084.87 | 8928576.64 | 2750345.05 | 3760.19 | 0.00 | 4999.81 | 171.89 |
PERIMETER_MID_ZN_3 | 48208484.84 | 0.00 | 48208484.84 | 598343.38 | 48806828.22 | 42678193.03 | 3936.32 | 19.36 | 4804.31 | 128.71 |
PERIMETER_MID_ZN_2 | 61311522.13 | 0.00 | 61311522.13 | 398895.31 | 61710417.44 | 27503450.52 | 4347.69 | 0.53 | 4411.79 | 590.16 |
PERIMETER_MID_ZN_1 | 0.11E+09 | 0.00 | 0.11E+09 | 598343.38 | 0.11E+09 | 42679126.28 | 3833.28 | 0.00 | 4926.72 | 128.71 |
PERIMETER_MID_ZN_4 | 74663982.85 | 0.00 | 74663982.85 | 398895.31 | 75062878.16 | 27503450.52 | 3833.28 | 0.00 | 4926.72 | 128.71 |
PERIMETER_TOP_ZN_3 | 5928211.74 | 0.00 | 5928211.74 | 742904.54 | 6671116.27 | 4267819.30 | 3990.67 | 6.85 | 4762.48 | 296.07 |
PERIMETER_TOP_ZN_2 | 6324210.94 | 0.00 | 6324210.94 | 495269.35 | 6819480.29 | 2750345.05 | 3874.39 | 2.86 | 4882.75 | 296.07 |
PERIMETER_TOP_ZN_1 | 10526972.51 | 0.00 | 10526972.51 | 742904.54 | 11269877.04 | 4267912.63 | 3874.83 | 3.09 | 4882.08 | 296.07 |
PERIMETER_TOP_ZN_4 | 7491676.72 | 0.00 | 7491676.72 | 495269.35 | 7986946.07 | 2750345.05 | 3853.31 | 3.00 | 4903.69 | 296.07 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.36E+09 | 0.00 | 0.36E+09 | 0.00 | 0.36E+09 | 10671554.30 | 301.60 | 268.26 | 8190.14 | 2632.94 |
Total Facility | 0.69E+10 | 0.00 | 0.69E+10 | 23271546.24 | 0.70E+10 | 0.50E+10 | 6199.28 | 4401.38 | 8504.64 | 3118.63 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.9747 | 0.0000 | 1.9747 | 0.0000 | 1.9747 | 1.2002 | 1505.15 | 2322.23 | 2115.62 |
CORE_BOTTOM | 1.9863 | 0.0000 | 1.9863 | 0.0000 | 1.9863 | 1.0778 | 1673.81 | 43.65 | 4225.54 |
CORE_MID | 15.9293 | 0.0000 | 15.9293 | 0.0000 | 15.9293 | 10.7782 | 2213.66 | 71.85 | 3657.50 |
CORE_TOP | 1.4079 | 0.0000 | 1.4079 | 0.0000 | 1.4079 | 1.0778 | 2833.77 | 74.37 | 3034.86 |
PERIMETER_BOT_ZN_3 | 0.2414 | 0.0000 | 0.2414 | 0.0059 | 0.2473 | 0.1353 | 1403.71 | 64.60 | 4474.69 |
PERIMETER_BOT_ZN_2 | 0.3172 | 0.0000 | 0.3172 | 0.0039 | 0.3211 | 0.0872 | 1115.08 | 0.00 | 4827.92 |
PERIMETER_BOT_ZN_1 | 0.4973 | 0.0000 | 0.4973 | 0.0059 | 0.5032 | 0.1353 | 1115.08 | 0.00 | 4827.92 |
PERIMETER_BOT_ZN_4 | 0.3968 | 0.0000 | 0.3968 | 0.0039 | 0.4008 | 0.0872 | 1115.08 | 0.00 | 4827.92 |
PERIMETER_MID_ZN_3 | 2.2050 | 0.0000 | 2.2050 | 0.0138 | 2.2188 | 1.3533 | 1219.13 | 15.79 | 4708.09 |
PERIMETER_MID_ZN_2 | 2.9365 | 0.0000 | 2.9365 | 0.0098 | 2.9463 | 0.8721 | 1144.99 | 0.00 | 3889.01 |
PERIMETER_MID_ZN_1 | 4.8884 | 0.0000 | 4.8884 | 0.0138 | 4.9022 | 1.3533 | 1144.99 | 0.00 | 4798.01 |
PERIMETER_MID_ZN_4 | 3.4133 | 0.0000 | 3.4133 | 0.0092 | 3.4225 | 0.8721 | 1144.99 | 0.00 | 4798.01 |
PERIMETER_TOP_ZN_3 | 0.2709 | 0.0000 | 0.2709 | 0.0172 | 0.2881 | 0.1353 | 1269.54 | 4.57 | 4668.89 |
PERIMETER_TOP_ZN_2 | 0.2895 | 0.0000 | 0.2895 | 0.0115 | 0.3009 | 0.0872 | 1195.38 | 1.44 | 4746.19 |
PERIMETER_TOP_ZN_1 | 0.4825 | 0.0000 | 0.4825 | 0.0172 | 0.4997 | 0.1353 | 1195.47 | 1.62 | 4745.92 |
PERIMETER_TOP_ZN_4 | 0.3427 | 0.0000 | 0.3427 | 0.0115 | 0.3542 | 0.0872 | 1185.42 | 1.20 | 4756.38 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 12.0157 | 0.0000 | 12.0157 | 0.0000 | 12.0157 | 0.3384 | 110.20 | 268.03 | 5564.77 |
Total Facility | 315.1131 | 0.0000 | 315.1131 | 0.5438 | 315.6569 | 158.4706 | 3382.28 | 4385.53 | 5864.07 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 0.11E+09 | 0.00 | 0.11E+09 | 48026705.38 | 3760.19 | 0.00 | 4999.81 | 171.89 |
VAV_MID WITH REHEAT | 0.91E+09 | 0.00 | 0.91E+09 | 0.48E+09 | 3833.40 | 0.03 | 4926.57 | 128.71 |
VAV_TOP WITH REHEAT | 86541735.07 | 0.00 | 86541735.07 | 48026705.38 | 3944.63 | 5.97 | 4809.40 | 296.07 |
CAV_BAS | 60541917.03 | 0.00 | 60541917.03 | 37848132.68 | 4240.51 | 1.89 | 4517.59 | 131.86 |
AIRLOOP DATACENTER BASEMENT | 0.51E+09 | 0.00 | 0.51E+09 | 10671554.30 | 296.10 | 0.03 | 8463.87 | 2632.94 |
AIRLOOP DATACENTER BOT | 346745.77 | 0.00 | 346745.77 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3467457.73 | 0.00 | 3467457.73 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 346745.77 | 0.00 | 346745.77 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 4.8814 | 0.0000 | 4.8814 | 1.5229 | 1115.08 | 0.00 | 4827.92 |
VAV_MID WITH REHEAT | 41.4931 | 0.0000 | 41.4931 | 15.2292 | 1144.99 | 0.00 | 4798.01 |
VAV_TOP WITH REHEAT | 3.9650 | 0.0000 | 3.9650 | 1.5229 | 1234.22 | 3.32 | 4705.46 |
CAV_BAS | 2.7951 | 0.0000 | 2.7951 | 1.2002 | 1469.18 | 0.96 | 4472.86 |
AIRLOOP DATACENTER BASEMENT | 17.0552 | 0.0000 | 17.0552 | 0.3384 | 109.09 | 0.00 | 5833.91 |
AIRLOOP DATACENTER BOT | 0.0162 | 0.0000 | 0.0162 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1621 | 0.0000 | 0.1621 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0162 | 0.0000 | 0.0162 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 3.61 | 4812.47 | 0.00 | 0.00 | 0.00 | 183.72 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 87.96 | 4504.87 | 0.00 | 0.00 | 0.00 | 333.89 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 3.36 | 4225.80 | 0.00 | 0.00 | 0.00 | 882.68 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 2347.89 | 2306.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 267.89 | 8199.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 3.0444 | 6.1517 | 0.0000 | 0.0000 | 0.0000 | 2.4958 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 29.7375 | 53.7685 | 0.0000 | 0.0000 | 0.0000 | 26.1721 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.9073 | 5.4213 | 0.0000 | 0.0000 | 0.0000 | 2.5569 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7041 | 5.8012 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4819 | 18.1873 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0222 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2219 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0222 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1343 |
Defaulted Fields | 1287 |
Fields with Defaults | 3878 |
Autosized Fields | 320 |
Autosizable Fields | 465 |
Autocalculated Fields | 223 |
Autocalculatable Fields | 468 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 29500.18 | 287881.76 | 14-MAY-05:00 | 2216341.48 | 25-AUG-15:00 |
Electricity:Building | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 758.19 | 15076.70 | 01-JAN-00:10 | 42602.33 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 589.38 | 5907.35 | 01-JAN-00:10 | 43380.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5893.79 | 59073.32 | 01-JAN-00:10 | 433806.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 589.38 | 5907.33 | 01-JAN-00:10 | 43380.63 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 740.04 | 7417.49 | 01-JAN-00:10 | 54469.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 476.91 | 4780.12 | 01-JAN-00:10 | 35102.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 740.05 | 7417.62 | 01-JAN-00:10 | 54470.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 476.91 | 4780.09 | 01-JAN-00:10 | 35102.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7588.97 | 95364.66 | 01-JAN-00:10 | 387850.11 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1622.27 | 19890.94 | 01-JAN-00:10 | 85232.07 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:HVAC | 3774.34 | 31177.90 | 29-JAN-01:30 | 384614.08 | 28-APR-16:00 |
ExteriorEquipment:Electricity | 2623.11 | 22123.82 | 01-JAN-00:10 | 235096.12 | 03-APR-07:20 |
Transformer:ExteriorEquipment:Electricity | 56.04 | 979.82 | 01-JAN-00:10 | 3543.78 | 03-APR-07:20 |
ElectricityPurchased:Facility | 29500.18 | 287881.76 | 14-MAY-05:00 | 2216341.48 | 25-AUG-15:00 |
ElectricityPurchased:Plant | 29500.18 | 287881.76 | 14-MAY-05:00 | 2216341.48 | 25-AUG-15:00 |
Cogeneration:ElectricityPurchased | 29500.18 | 287881.76 | 14-MAY-05:00 | 2216341.48 | 25-AUG-15:00 |
General:Cogeneration:ElectricityPurchased | 29500.18 | 287881.76 | 14-MAY-05:00 | 2216341.48 | 25-AUG-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 29500.18 | 287881.76 | 14-MAY-05:00 | 2216341.48 | 25-AUG-15:00 |
ElectricityNet:Plant | 29500.18 | 287881.76 | 14-MAY-05:00 | 2216341.48 | 25-AUG-15:00 |
Cogeneration:ElectricityNet | 29500.18 | 287881.76 | 14-MAY-05:00 | 2216341.48 | 25-AUG-15:00 |
General:Cogeneration:ElectricityNet | 29500.18 | 287881.76 | 14-MAY-05:00 | 2216341.48 | 25-AUG-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1156.00 | 2124.63 | 09-JAN-07:10 | 302213.76 | 14-AUG-16:00 |
General:Cooling:Electricity | 1156.00 | 2124.63 | 09-JAN-07:10 | 302213.76 | 14-AUG-16:00 |
Fans:Electricity | 2596.91 | 25382.88 | 01-JAN-03:20 | 261483.67 | 28-APR-15:20 |
General:Fans:Electricity | 2596.91 | 25382.88 | 01-JAN-03:20 | 261483.67 | 28-APR-15:20 |
ExteriorLights:Electricity | 1004.92 | 0.00 | 01-JAN-08:20 | 64082.80 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 1004.92 | 0.00 | 01-JAN-08:20 | 64082.80 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.31 | 1944.00 | 01-JAN-00:10 | 1944.00 | 01-JAN-00:10 |
Humidifier:Electricity | 681.44 | 0.00 | 17-JAN-11:30 | 100000.00 | 31-MAR-24:00 |
General:Humidifier:Electricity | 681.44 | 0.00 | 17-JAN-11:30 | 100000.00 | 31-MAR-24:00 |
Electricity:Plant | 1866.73 | 0.00 | 03-JAN-01:30 | 431063.39 | 14-AUG-13:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 457.47 | 0.00 | 01-JAN-00:10 | 52813.61 | 15-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 457.47 | 0.00 | 01-JAN-00:10 | 52813.61 | 15-FEB-13:00 |
HeatRejection:Electricity | 20.70 | 0.00 | 01-JAN-00:10 | 44335.29 | 12-JUN-14:30 |
General:HeatRejection:Electricity | 20.70 | 0.00 | 01-JAN-00:10 | 44335.29 | 12-JUN-14:30 |
Pumps:Electricity | 672.51 | 0.00 | 03-JAN-00:10 | 78697.07 | 28-AUG-14:00 |
General:Pumps:Electricity | 672.51 | 0.00 | 03-JAN-00:10 | 78697.07 | 28-AUG-14:00 |
WIRED_LTG_ELECTRICITY | 157.66 | 0.00 | 01-JAN-00:10 | 13766.21 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1571.77 | 0.00 | 01-JAN-00:40 | 960582.02 | 26-DEC-05:20 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 1571.77 | 0.00 | 01-JAN-00:40 | 960582.02 | 26-DEC-05:20 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 1571.77 | 0.00 | 01-JAN-00:40 | 960582.02 | 26-DEC-05:20 |
Boiler:Heating:NaturalGas | 1571.77 | 0.00 | 01-JAN-00:40 | 960582.02 | 26-DEC-05:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 3524.96 | 0.00 | 01-JAN-01:00 | 1902647.42 | 21-JUL-16:00 |
PlantLoopCoolingDemand:HVAC | 3524.96 | 0.00 | 01-JAN-01:00 | 1902647.42 | 21-JUL-16:00 |
CoolingCoils:PlantLoopCoolingDemand | 3524.96 | 0.00 | 01-JAN-01:00 | 1902647.42 | 21-JUL-16:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 4764.86 | 0.00 | 29-JAN-01:30 | 0.00 | 21-JUL-16:30 |
Water:HVAC | 253.49 | 0.00 | 17-JAN-11:30 | 0.00 | 09-APR-06:20 |
Humidifier:Water | 253.49 | 0.00 | 17-JAN-11:30 | 0.00 | 09-APR-06:20 |
General:Humidifier:Water | 253.49 | 0.00 | 17-JAN-11:30 | 0.00 | 09-APR-06:20 |
MainsWater:Facility | 4764.86 | 0.00 | 29-JAN-01:30 | 0.00 | 21-JUL-16:30 |
MainsWater:HVAC | 253.49 | 0.00 | 17-JAN-11:30 | 0.00 | 09-APR-06:20 |
Humidifier:MainsWater | 253.49 | 0.00 | 17-JAN-11:30 | 0.00 | 09-APR-06:20 |
General:Humidifier:MainsWater | 253.49 | 0.00 | 17-JAN-11:30 | 0.00 | 09-APR-06:20 |
Water:Plant | 4511.36 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:30 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 21-APR-11:40 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 21-APR-11:40 |
MainsWater:Plant | 4511.36 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:30 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 21-APR-11:40 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 21-APR-11:40 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 2231.19 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:30 |
General:HeatRejection:Water | 2231.19 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:30 |
HeatRejection:MainsWater | 2231.19 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:30 |
General:HeatRejection:MainsWater | 2231.19 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 38899.90 | 102317.83 | 09-JAN-04:00 | 9698534.69 | 21-JUL-16:00 |
EnergyTransfer:Building | 19288.26 | 87500.48 | 15-JAN-06:00 | 1718136.52 | 28-APR-15:20 |
EnergyTransfer:Zone:BASEMENT | 673.26 | 0.00 | 01-JAN-00:10 | 82244.43 | 21-AUG-08:00 |
Heating:EnergyTransfer | 277.43 | 0.00 | 06-JAN-13:20 | 574862.32 | 26-DEC-05:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.78 | 0.00 | 01-JAN-00:10 | 7724.71 | 22-JUL-16:10 |
General:Heating:EnergyTransfer | 277.43 | 0.00 | 06-JAN-13:20 | 574862.32 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.78 | 0.00 | 01-JAN-00:10 | 7724.71 | 22-JUL-16:10 |
Cooling:EnergyTransfer | 19010.83 | 86102.81 | 09-JAN-04:00 | 1718136.52 | 28-APR-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 672.48 | 0.00 | 01-JAN-00:10 | 82244.43 | 21-AUG-08:00 |
General:Cooling:EnergyTransfer | 19010.83 | 86102.81 | 09-JAN-04:00 | 1718136.52 | 28-APR-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 672.48 | 0.00 | 01-JAN-00:10 | 82244.43 | 21-AUG-08:00 |
EnergyTransfer:Zone:CORE_BOTTOM | 602.67 | 0.00 | 01-JAN-00:10 | 55314.08 | 24-JUL-14:00 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 602.67 | 0.00 | 01-JAN-00:10 | 55314.08 | 24-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 602.67 | 0.00 | 01-JAN-00:10 | 55314.08 | 24-JUL-14:00 |
EnergyTransfer:Zone:CORE_MID | 4749.00 | 0.00 | 01-JAN-00:10 | 470343.98 | 21-JUL-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.03 | 0.00 | 01-JAN-00:10 | 41839.67 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.03 | 0.00 | 01-JAN-00:10 | 41839.67 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4748.98 | 0.00 | 01-JAN-00:10 | 470343.98 | 21-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4748.98 | 0.00 | 01-JAN-00:10 | 470343.98 | 21-JUL-16:00 |
EnergyTransfer:Zone:CORE_TOP | 387.31 | 0.00 | 01-JAN-00:40 | 76126.49 | 26-DEC-05:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 11.20 | 0.00 | 01-JAN-00:20 | 76126.49 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 11.20 | 0.00 | 01-JAN-00:20 | 76126.49 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 376.11 | 0.00 | 01-JAN-00:10 | 58067.19 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 376.11 | 0.00 | 01-JAN-00:10 | 58067.19 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 64.12 | 0.00 | 01-JAN-00:10 | 10225.79 | 10-JUL-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.10 | 0.00 | 01-JAN-00:10 | 4331.14 | 10-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.10 | 0.00 | 01-JAN-00:10 | 4331.14 | 10-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 64.01 | 0.00 | 01-JAN-00:10 | 10225.79 | 10-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 64.01 | 0.00 | 01-JAN-00:10 | 10225.79 | 10-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 73.10 | 0.00 | 01-JAN-00:10 | 15074.67 | 13-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.17 | 0.00 | 01-JAN-00:10 | 2868.88 | 12-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.17 | 0.00 | 01-JAN-00:10 | 2868.88 | 12-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 72.93 | 0.00 | 01-JAN-00:10 | 15074.67 | 13-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 72.93 | 0.00 | 01-JAN-00:10 | 15074.67 | 13-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 118.09 | 0.00 | 01-JAN-00:10 | 23627.05 | 11-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.63 | 0.00 | 01-JAN-00:10 | 5956.19 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.63 | 0.00 | 01-JAN-00:10 | 5956.19 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 117.46 | 0.00 | 01-JAN-00:10 | 23627.05 | 11-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 117.46 | 0.00 | 01-JAN-00:10 | 23627.05 | 11-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 101.36 | 0.00 | 01-JAN-00:10 | 19716.12 | 21-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1814.03 | 10-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1814.03 | 10-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 101.35 | 0.00 | 01-JAN-00:10 | 19716.12 | 21-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 101.35 | 0.00 | 01-JAN-00:10 | 19716.12 | 21-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 513.12 | 0.00 | 01-JAN-00:10 | 122885.66 | 26-DEC-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 43.04 | 0.00 | 01-JAN-00:10 | 122885.66 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 43.04 | 0.00 | 01-JAN-00:10 | 122885.66 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 470.08 | 0.00 | 01-JAN-00:10 | 93248.99 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 470.08 | 0.00 | 01-JAN-00:10 | 93248.99 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 585.75 | 0.00 | 01-JAN-00:10 | 155322.75 | 13-JUN-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 27.94 | 0.00 | 01-JAN-00:10 | 86613.44 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 27.94 | 0.00 | 01-JAN-00:10 | 86613.44 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 557.81 | 0.00 | 01-JAN-00:10 | 155322.75 | 13-JUN-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 557.81 | 0.00 | 01-JAN-00:10 | 155322.75 | 13-JUN-08:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1090.26 | 0.00 | 01-JAN-00:10 | 254450.23 | 11-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 31.42 | 0.00 | 01-JAN-00:10 | 111538.72 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 31.42 | 0.00 | 01-JAN-00:10 | 111538.72 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1058.84 | 0.00 | 01-JAN-00:10 | 254450.23 | 11-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1058.84 | 0.00 | 01-JAN-00:10 | 254450.23 | 11-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 670.03 | 0.00 | 01-JAN-00:10 | 184534.84 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 20.22 | 0.00 | 01-JAN-00:10 | 73419.72 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 20.22 | 0.00 | 01-JAN-00:10 | 73419.72 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 649.82 | 0.00 | 01-JAN-00:10 | 184534.84 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 649.82 | 0.00 | 01-JAN-00:10 | 184534.84 | 13-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 65.60 | 0.00 | 01-JAN-00:40 | 19295.22 | 26-DEC-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 22.57 | 0.00 | 01-JAN-00:40 | 19295.22 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 22.57 | 0.00 | 01-JAN-00:40 | 19295.22 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 43.03 | 0.00 | 01-JAN-00:10 | 10794.82 | 13-JUN-15:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 43.03 | 0.00 | 01-JAN-00:10 | 10794.82 | 13-JUN-15:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 63.70 | 0.00 | 01-JAN-00:40 | 15496.18 | 13-JUN-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 13.26 | 0.00 | 01-JAN-00:40 | 13825.23 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 13.26 | 0.00 | 01-JAN-00:40 | 13825.23 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 50.44 | 0.00 | 01-JAN-00:10 | 15496.18 | 13-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 50.44 | 0.00 | 01-JAN-00:10 | 15496.18 | 13-JUN-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 108.61 | 0.00 | 01-JAN-00:40 | 25843.73 | 11-SEP-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 17.45 | 0.00 | 01-JAN-00:40 | 20304.17 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 17.45 | 0.00 | 01-JAN-00:40 | 20304.17 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 91.16 | 0.00 | 01-JAN-00:10 | 25843.73 | 11-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 91.16 | 0.00 | 01-JAN-00:10 | 25843.73 | 11-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 66.65 | 0.00 | 01-JAN-00:40 | 19493.48 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 9.53 | 0.00 | 01-JAN-00:40 | 12101.83 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 9.53 | 0.00 | 01-JAN-00:40 | 12101.83 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 57.12 | 0.00 | 01-JAN-00:10 | 19493.48 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 57.12 | 0.00 | 01-JAN-00:10 | 19493.48 | 13-JUN-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 80.30 | 0.00 | 01-JAN-00:10 | 8954.53 | 01-MAY-05:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.47 | 0.00 | 01-JAN-00:10 | 2972.79 | 07-MAY-12:10 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.47 | 0.00 | 01-JAN-00:10 | 2972.79 | 07-MAY-12:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 79.83 | 0.00 | 01-JAN-00:10 | 8954.53 | 01-MAY-05:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 79.83 | 0.00 | 01-JAN-00:10 | 8954.53 | 01-MAY-05:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 548.20 | 0.00 | 01-JAN-00:10 | 78834.49 | 29-APR-05:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 13.47 | 0.00 | 01-JAN-00:10 | 42827.63 | 26-DEC-14:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 13.47 | 0.00 | 01-JAN-00:10 | 42827.63 | 26-DEC-14:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 534.73 | 0.00 | 01-JAN-00:10 | 78834.49 | 29-APR-05:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 534.73 | 0.00 | 01-JAN-00:10 | 78834.49 | 29-APR-05:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 134.22 | 0.00 | 01-JAN-00:40 | 30882.44 | 26-DEC-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 61.94 | 0.00 | 01-JAN-00:40 | 30882.44 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 61.94 | 0.00 | 01-JAN-00:40 | 30882.44 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 72.28 | 0.00 | 01-JAN-00:10 | 30303.32 | 21-JUL-14:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 72.28 | 0.00 | 01-JAN-00:10 | 30303.32 | 21-JUL-14:20 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 133.48 | 590.42 | 09-JAN-07:00 | 8414.57 | 30-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 133.48 | 590.42 | 09-JAN-07:00 | 8414.57 | 30-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 133.48 | 590.42 | 09-JAN-07:00 | 8414.57 | 30-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1176.48 | 5.88 | 15-JAN-06:00 | 79072.03 | 30-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.79 | 0.00 | 01-JAN-15:30 | 6914.34 | 02-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.79 | 0.00 | 01-JAN-15:30 | 6914.34 | 02-JAN-05:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1175.70 | 0.00 | 01-JAN-00:10 | 79072.03 | 30-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1175.70 | 0.00 | 01-JAN-00:10 | 79072.03 | 30-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 102.31 | 0.79 | 21-JAN-11:50 | 8044.53 | 30-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.61 | 0.00 | 02-JAN-11:40 | 1375.75 | 01-JAN-17:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.61 | 0.00 | 02-JAN-11:40 | 1375.75 | 01-JAN-17:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 100.70 | 0.00 | 01-JAN-00:10 | 8044.53 | 30-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 100.70 | 0.00 | 01-JAN-00:10 | 8044.53 | 30-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7180.63 | 83299.74 | 30-APR-23:10 | 394928.78 | 23-AUG-17:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.82 | 0.00 | 01-JAN-00:10 | 3429.41 | 16-JUN-23:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.82 | 0.00 | 01-JAN-00:10 | 3429.41 | 16-JUN-23:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7179.81 | 83299.74 | 30-APR-23:10 | 394928.78 | 23-AUG-17:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7179.81 | 83299.74 | 30-APR-23:10 | 394928.78 | 23-AUG-17:20 |
PlantLoopHeatingDemand:Facility | 1501.01 | 0.00 | 01-JAN-00:40 | 711040.39 | 02-JAN-06:10 |
PlantLoopHeatingDemand:Plant | 452.04 | 0.00 | 01-JAN-00:10 | 52439.48 | 14-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 452.04 | 0.00 | 01-JAN-00:10 | 52439.48 | 14-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 452.04 | 0.00 | 01-JAN-00:10 | 52439.48 | 14-FEB-12:10 |
EnergyTransfer:HVAC | 6416.43 | 8564.41 | 02-JAN-04:40 | 1988949.05 | 21-JUL-16:00 |
HeatingCoils:EnergyTransfer | 1048.97 | 0.00 | 01-JAN-00:40 | 704689.05 | 02-JAN-06:10 |
PlantLoopHeatingDemand:HVAC | 1048.97 | 0.00 | 01-JAN-00:40 | 704689.05 | 02-JAN-06:10 |
HeatingCoils:PlantLoopHeatingDemand | 1048.97 | 0.00 | 01-JAN-00:40 | 704689.05 | 02-JAN-06:10 |
CoolingCoils:EnergyTransfer | 5367.46 | 7332.91 | 09-JAN-07:10 | 1988949.05 | 21-JUL-16:00 |
EnergyTransfer:Plant | 13195.21 | 0.00 | 03-JAN-00:10 | 6056070.11 | 21-JUL-16:00 |
LoopToLoop:EnergyTransfer | 3559.42 | 0.00 | 01-JAN-01:00 | 1904390.16 | 21-JUL-16:00 |
WaterSystems:EnergyTransfer | 452.04 | 0.00 | 01-JAN-00:10 | 52439.48 | 14-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 452.04 | 0.00 | 01-JAN-00:10 | 52439.48 | 14-FEB-12:10 |
Boilers:EnergyTransfer | 1044.60 | 0.00 | 01-JAN-00:40 | 740935.66 | 26-DEC-05:20 |
Chillers:EnergyTransfer | 3711.55 | 0.00 | 01-JAN-00:10 | 1918516.77 | 21-JUL-16:00 |
HeatRejection:EnergyTransfer | 4427.60 | 0.00 | 01-JAN-00:10 | 2196666.98 | 21-JUL-16:00 |
General:HeatRejection:EnergyTransfer | 4427.60 | 0.00 | 01-JAN-00:10 | 2196666.98 | 21-JUL-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.778 | -672.478 | 0.000 | 0.000 | 94.272 | 333.789 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -180.759 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -602.673 | 0.000 | 0.000 | 83.552 | 299.766 | 289.614 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -70.260 |
CORE_MID | 0.000 | 0.000 | 0.025 | -4748.962 | 0.000 | 0.000 | 842.865 | 2997.664 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1987.720 |
CORE_TOP | 0.000 | 0.000 | 11.197 | -376.112 | 0.000 | 0.000 | 89.104 | 299.766 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -313.568 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.104 | -64.014 | 0.000 | 0.000 | 10.981 | 37.639 | 36.365 | 17.161 | 0.000 | 0.002 | 62.889 | 0.000 | -97.041 | 0.000 | -4.087 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.171 | -72.927 | 0.000 | 0.000 | 7.335 | 24.256 | 23.435 | 49.470 | 0.000 | 0.001 | 30.086 | 0.000 | -59.181 | 0.000 | -2.645 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.635 | -117.455 | 0.000 | 0.000 | 11.308 | 37.639 | 36.366 | 102.024 | 0.000 | 0.002 | 22.217 | 0.000 | -88.754 | 0.000 | -3.982 | -0.002 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.008 | -101.354 | 0.000 | 0.000 | 7.286 | 24.256 | 23.435 | 47.321 | 0.000 | 0.001 | 69.159 | 0.000 | -67.219 | 0.000 | -2.894 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 43.038 | -470.080 | 0.000 | 0.000 | 114.987 | 376.387 | 363.654 | 182.115 | 0.000 | 0.039 | 359.938 | 0.000 | -884.012 | 0.000 | -86.065 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 27.941 | -557.811 | 0.000 | 0.000 | 54.730 | 242.558 | 234.352 | 492.391 | 0.000 | 0.030 | 122.901 | 0.000 | -559.118 | 0.000 | -57.975 | -0.002 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 31.422 | -1058.837 | 0.000 | 0.000 | 114.775 | 376.395 | 363.660 | 1016.200 | 0.000 | 0.045 | 111.279 | 0.000 | -865.681 | 0.000 | -89.256 | -0.026 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 20.217 | -649.816 | 0.000 | 0.000 | 76.506 | 242.558 | 234.351 | 487.945 | 0.000 | 0.027 | 244.265 | 0.000 | -596.764 | 0.000 | -59.289 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 22.566 | -43.031 | 0.000 | 0.000 | 11.916 | 37.639 | 36.365 | 19.802 | 0.000 | 0.005 | 3.383 | 0.000 | -79.018 | 0.000 | -9.627 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 13.262 | -50.439 | 0.000 | 0.000 | 7.563 | 24.256 | 23.435 | 50.469 | 0.000 | 0.003 | 0.000 | 0.000 | -50.531 | 0.000 | -6.584 | -11.434 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 17.445 | -91.164 | 0.000 | 0.000 | 11.699 | 37.639 | 36.366 | 103.158 | 0.000 | 0.005 | 0.000 | 0.000 | -78.495 | 0.000 | -10.139 | -26.515 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 9.525 | -57.124 | 0.000 | 0.000 | 7.739 | 24.256 | 23.435 | 49.143 | 0.000 | 0.003 | 4.807 | 0.000 | -54.942 | 0.000 | -6.843 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -133.482 | 0.000 | 0.000 | 0.950 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -29.696 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.788 | -1175.695 | 0.000 | 0.000 | 9.502 | 83.466 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -456.866 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 1.608 | -100.702 | 0.000 | 0.000 | 0.950 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -64.084 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.822 | -7179.764 | 0.000 | 0.000 | 23.134 | 94.114 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -433.163 |
GROUNDFLOOR_PLENUM | 0.473 | -79.826 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.003 | 88.330 | 0.000 | 0.000 | 0.000 | -8.979 | 0.000 |
MIDFLOOR_PLENUM | 13.470 | -534.723 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.050 | 675.700 | 0.000 | 0.000 | 0.000 | -154.497 | -0.008 |
TOPFLOOR_PLENUM | 61.938 | -72.278 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.002 | 25.329 | 0.000 | 0.000 | 0.000 | -14.990 | -0.000 |
Total Facility | 75.881 | -686.827 | 201.551 | -18323.919 | 0.000 | 0.000 | 1581.155 | 5610.736 | 14676.396 | 2617.199 | 0.000 | 0.217 | 1820.283 | 0.000 | -3480.755 | 0.000 | -517.852 | -3574.106 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 02-JAN-04:01 | 0.00 | 0.00 | 0.00 | -141746.73 | 0.00 | 0.00 | 0.00 | 1619.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 126670.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 24-JUL-04:11 | 0.00 | 0.00 | 0.00 | -117670.80 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.65 | 0.00 | 0.00 | 0.00 | 108824.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 24-JUL-05:01 | 0.00 | 0.00 | 0.00 | -1024958.15 | 0.00 | 0.00 | 8384.17 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 911018.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 27-JUN-05:01 | 0.00 | 0.00 | 0.00 | -99251.85 | 0.00 | 0.00 | 885.63 | 2908.23 | 7647.36 | 0.00 | 0.00 | 0.00 | 87810.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 13-JUN-05:01 | 0.00 | 0.00 | 0.00 | -14027.85 | 0.00 | 0.00 | 114.32 | 365.16 | 960.25 | 2126.40 | 0.00 | 0.00 | 10499.39 | 0.00 | -0.00 | 0.00 | -37.65 | 0.00 |
PERIMETER_BOT_ZN_2 | 23-JUL-08:31 | 0.00 | 0.00 | 0.00 | -30846.29 | 0.00 | 0.00 | 19.75 | 117.66 | 464.11 | 19550.97 | 0.00 | 0.00 | 10819.21 | 0.00 | -0.00 | 0.00 | -125.41 | 0.00 |
PERIMETER_BOT_ZN_1 | 30-APR-12:31 | 0.00 | 0.00 | 0.00 | -44456.61 | 0.00 | 0.00 | 30.45 | 182.58 | 720.19 | 29131.33 | 0.00 | 0.00 | 14517.05 | 0.00 | -0.00 | 0.00 | -125.01 | 0.00 |
PERIMETER_BOT_ZN_4 | 09-JUL-17:11 | 0.00 | 0.00 | 0.00 | -40318.04 | 0.00 | 0.00 | 0.00 | 117.66 | 360.35 | 20998.46 | 0.00 | 0.00 | 18978.46 | 0.00 | -0.00 | 0.00 | -136.90 | 0.00 |
PERIMETER_MID_ZN_3 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | -93248.53 | 0.00 | 0.00 | 11143.77 | 32864.16 | 21605.52 | 49412.75 | 0.00 | 402.45 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22180.12 |
PERIMETER_MID_ZN_2 | 16-JUL-09:11 | 0.00 | 0.00 | 0.00 | -317754.54 | 0.00 | 0.00 | 207.33 | 1176.61 | 4641.14 | 169109.42 | 0.00 | 0.00 | 146601.20 | 0.00 | -0.00 | 0.00 | -3981.16 | 0.00 |
PERIMETER_MID_ZN_1 | 10-SEP-12:51 | 0.00 | 0.00 | 0.00 | -448150.18 | 0.00 | 0.00 | 308.50 | 1825.83 | 7201.95 | 274831.53 | 0.00 | 0.00 | 168601.73 | 0.00 | -0.00 | 0.00 | -4619.35 | 0.00 |
PERIMETER_MID_ZN_4 | 09-JUL-17:11 | 0.00 | 0.00 | 0.00 | -364010.20 | 0.00 | 0.00 | 0.00 | 1176.61 | 3603.49 | 209743.32 | 0.00 | 0.00 | 152619.20 | 0.00 | -0.00 | 0.00 | -3132.41 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-JUN-15:50 | 0.00 | 0.00 | 0.00 | -10794.78 | 0.00 | 0.00 | 1114.38 | 3286.42 | 2160.55 | 4894.78 | 0.00 | 47.83 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -709.17 |
PERIMETER_TOP_ZN_2 | 23-JUL-09:51 | 0.00 | 0.00 | 0.00 | -31679.32 | 0.00 | 0.00 | 19.25 | 117.66 | 464.11 | 14494.43 | 0.00 | 0.00 | 16814.91 | 0.00 | -0.00 | 0.00 | -231.05 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-14:11 | 0.00 | 0.00 | 0.00 | -47225.90 | 0.00 | 0.00 | 32.01 | 182.58 | 720.19 | 21255.51 | 0.00 | 0.00 | 25685.68 | 0.00 | -0.00 | 0.00 | -650.09 | 0.00 |
PERIMETER_TOP_ZN_4 | 11-JUN-16:51 | 0.00 | 0.00 | 0.00 | -36659.77 | 0.00 | 0.00 | 19.17 | 117.66 | 464.11 | 18820.41 | 0.00 | 0.00 | 17886.54 | 0.00 | -0.00 | 0.00 | -648.12 | 0.00 |
DATACENTER_BOT_ZN_6 | 30-APR-18:03 | 0.00 | 0.00 | 0.00 | -8414.57 | 0.00 | 0.00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 579.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 30-APR-18:20 | 0.00 | 0.00 | 0.00 | -79072.03 | 0.00 | 0.00 | 0.00 | 404.88 | 77944.22 | 0.00 | 0.00 | 0.00 | 722.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 30-APR-18:07 | 0.00 | 0.00 | 0.00 | -8044.53 | 0.00 | 0.00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 209.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 23-MAR-15:42 | 0.00 | 0.00 | 0.00 | -519314.66 | 0.00 | 0.00 | 2698.73 | 8217.58 | 284724.39 | 0.00 | 0.00 | 0.00 | 223673.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 01-MAY-05:12 | 0.00 | -10918.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11252.98 | 0.00 | -0.00 | 0.00 | -334.54 | 0.00 |
MIDFLOOR_PLENUM | 17-FEB-05:01 | 0.00 | -136572.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149986.88 | 0.00 | -0.00 | 0.00 | -13414.13 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-14:20 | 0.00 | -30303.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.52 | 30296.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-05:01 | 0.00 | 54034.13 | 0.00 | -2129793.46 | 0.00 | 0.00 | 16453.96 | 54433.43 | 497997.76 | 0.00 | 0.00 | 0.00 | 1629928.62 | 0.00 | -115104.04 | 0.00 | -7950.41 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 22-JUL-16:02 | 0.00 | 0.00 | 8710.07 | 0.00 | 0.00 | 0.00 | 520.14 | 1619.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24306.91 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-06:01 | 0.00 | 0.00 | 247182.22 | 0.00 | 0.00 | 0.00 | 11162.08 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -363900.21 |
CORE_TOP | 09-JAN-04:01 | 0.00 | 0.00 | 93136.94 | 0.00 | 0.00 | 0.00 | 0.00 | 1454.11 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -100528.68 |
PERIMETER_BOT_ZN_3 | 10-JAN-06:02 | 0.00 | 0.00 | 9738.51 | 0.00 | 0.00 | 0.00 | 146.10 | 365.16 | 960.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7495.03 | 0.00 | -138.78 | -3576.20 |
PERIMETER_BOT_ZN_2 | 10-JAN-05:01 | 0.00 | 0.00 | 8770.50 | 0.00 | 0.00 | 0.00 | 0.00 | 235.32 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4876.50 | 0.00 | -217.09 | -4392.69 |
PERIMETER_BOT_ZN_1 | 10-JAN-05:01 | 0.00 | 0.00 | 15552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 365.17 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6993.26 | 0.00 | -319.92 | -9350.27 |
PERIMETER_BOT_ZN_4 | 10-JAN-06:02 | 0.00 | 0.00 | 5870.94 | 0.00 | 0.00 | 0.00 | 94.15 | 235.32 | 618.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4951.76 | 0.00 | -92.73 | -1774.74 |
PERIMETER_MID_ZN_3 | 11-JAN-05:01 | 0.00 | 0.00 | 154145.47 | 0.00 | 0.00 | 0.00 | 0.00 | 3651.57 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -62055.14 | 0.00 | -9827.66 | -93369.84 |
PERIMETER_MID_ZN_2 | 11-JAN-05:01 | 0.00 | 0.00 | 149386.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2353.21 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -42811.95 | 0.00 | -6617.80 | -107115.02 |
PERIMETER_MID_ZN_1 | 10-JAN-05:01 | 0.00 | 0.00 | 215967.95 | 0.00 | 0.00 | 0.00 | 0.00 | 3651.65 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -67642.75 | 0.00 | -7218.89 | -152213.68 |
PERIMETER_MID_ZN_4 | 11-JAN-05:01 | 0.00 | 0.00 | 144777.50 | 0.00 | 0.00 | 0.00 | 0.00 | 2353.21 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -41897.99 | 0.00 | -6679.06 | -103358.31 |
PERIMETER_TOP_ZN_3 | 09-JAN-04:01 | 0.00 | 0.00 | 23789.23 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4629.95 | 0.00 | 0.00 | -20087.41 |
PERIMETER_TOP_ZN_2 | 09-JAN-04:01 | 0.00 | 0.00 | 19644.81 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3079.41 | 0.00 | 0.00 | -17163.53 |
PERIMETER_TOP_ZN_1 | 11-JAN-04:01 | 0.00 | 0.00 | 30056.70 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5891.59 | 0.00 | -1095.50 | -23997.77 |
PERIMETER_TOP_ZN_4 | 11-JAN-04:01 | 0.00 | 0.00 | 20793.32 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3786.80 | 0.00 | -734.37 | -16870.27 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 02-JAN-04:55 | 0.00 | 0.00 | 6914.34 | 0.00 | 0.00 | 0.00 | 0.00 | 404.88 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26805.27 |
DATACENTER_TOP_ZN_6 | 01-JAN-17:25 | 0.00 | 0.00 | 1377.11 | 0.00 | 0.00 | 0.00 | 5.93 | 40.49 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3372.14 |
DATACENTER_BASEMENT_ZN_6 | 16-JUN-23:21 | 0.00 | 0.00 | 34120.16 | 0.00 | 0.00 | 0.00 | 0.00 | 456.53 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -224392.96 |
GROUNDFLOOR_PLENUM | 30-APR-15:11 | 14453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -25.36 | -14427.79 |
MIDFLOOR_PLENUM | 30-APR-15:22 | 136923.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -225.73 | -136698.20 |
TOPFLOOR_PLENUM | 13-FEB-05:11 | 36975.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1175.59 | -35800.00 |
Total Facility | 02-JAN-06:01 | -333616.74 | 317493.43 | 976177.21 | -317493.43 | 0.00 | 0.00 | 20694.08 | 54433.43 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -196600.32 | 0.00 | 0.00 | -782502.63 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 14.3599 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 12.0081 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 140.1915 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 110.4954 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 15.1499 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 13.2831 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 7.0269 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 7.0269 | 0.1708 | 1.0000 | Not calculated | 1.2002 | 0.1708 | ||
AIRLOOP DATACENTER BASEMENT | 31.6961 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 31.6971 | 0.0107 | 1.0000 | Not calculated | 0.3384 | 0.0107 | ||
AIRLOOP DATACENTER BOT | 0.7769 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7769 | 0.0201 | 1.0000 | Not calculated | 0.0156 | 0.0201 | ||
AIRLOOP DATACENTER MID | 7.4782 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 7.4782 | 0.0209 | 1.0000 | Not calculated | 0.1563 | 0.0209 | ||
AIRLOOP DATACENTER TOP | 0.7653 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7653 | 0.0204 | 1.0000 | Not calculated | 0.0156 | 0.0204 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 7.1799 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.3080 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 70.0958 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 42.0575 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 7.5750 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.5450 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 2.1081 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 2.1081 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.5693 | ||
AIRLOOP DATACENTER BASEMENT | 15.8480 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 15.8480 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0214 | ||
AIRLOOP DATACENTER BOT | 0.7769 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7769 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0201 | ||
AIRLOOP DATACENTER MID | 7.4782 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 7.4782 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0209 | ||
AIRLOOP DATACENTER TOP | 0.7653 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7653 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0204 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 7.0269 | 7.0269 | 2.1081 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.3933 | 7.3933 | 2.2180 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 70.0219 | 70.0219 | 21.0066 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.3739 | 7.3739 | 2.2122 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0743 | 1.0743 | 0.3223 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6115 | 1.6115 | 0.4834 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3118 | 2.3118 | 0.6935 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9690 | 1.9690 | 0.5907 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.7492 | 11.7492 | 3.5248 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 16.6928 | 16.6928 | 5.0078 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 23.6116 | 23.6116 | 7.0835 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.1160 | 18.1160 | 5.4348 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6448 | 1.6448 | 0.4934 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6424 | 1.6424 | 0.4927 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5511 | 2.5511 | 0.7653 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9377 | 1.9377 | 0.5813 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7769 | 0.7769 | 0.7769 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.4782 | 7.4782 | 7.4782 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7653 | 0.7653 | 0.7653 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 31.6961 | 31.6961 | 15.8480 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 14.3599 | 12.0081 | 14.3599 | 4.3080 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 140.1915 | 110.4954 | 140.1915 | 42.0575 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 15.1499 | 13.2831 | 15.1499 | 4.5450 | 0.0000 | 1.0000 |
CAV_BAS | 7.0269 | 7.0269 | 7.0269 | 2.1081 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 31.6961 | 31.6971 | 31.6961 | 15.8480 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.7769 | 0.7769 | 0.7769 | 0.7769 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 7.4782 | 7.4782 | 7.4782 | 7.4782 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.7653 | 0.7653 | 0.7653 | 0.7653 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 2.1081 | 2.1081 | 2.1081 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.6967 | 3.6967 | 2.2180 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 35.0110 | 35.0110 | 21.0066 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.6870 | 3.6870 | 2.2122 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5371 | 0.5371 | 0.3223 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8057 | 0.8057 | 0.4834 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1559 | 1.1559 | 0.6935 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9845 | 0.9845 | 0.5907 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8746 | 5.8746 | 3.5248 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.3464 | 8.3464 | 5.0078 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.8058 | 11.8058 | 7.0835 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.0580 | 9.0580 | 5.4348 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8224 | 0.8224 | 0.4934 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8212 | 0.8212 | 0.4927 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2755 | 1.2755 | 0.7653 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9689 | 0.9689 | 0.5813 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7769 | 0.7769 | 0.7769 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.4782 | 7.4782 | 7.4782 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7653 | 0.7653 | 0.7653 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 15.8480 | 15.8480 | 15.8480 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 7.1799 | 4.3080 | 4.3080 | 4.3080 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 70.0958 | 42.0575 | 42.0575 | 42.0575 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 7.5750 | 4.5450 | 4.5450 | 4.5450 | 0.0000 | 1.0000 |
CAV_BAS | 2.1081 | 2.1081 | 2.1081 | 2.1081 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 15.8480 | 15.8480 | 15.8480 | 15.8480 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.7769 | 0.7769 | 0.7769 | 0.7769 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 7.4782 | 7.4782 | 7.4782 | 7.4782 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.7653 | 0.7653 | 0.7653 | 0.7653 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 5.83 |
Number of hours cooling loads not met | 64.50 |
Number of hours not met | 70.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1571.77 | 960582.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1156.00 | 302213.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 5610.74 | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 1004.92 | 64082.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 56.04 | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.31 | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2596.91 | 261483.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 672.51 | 78697.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 20.70 | 44335.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 681.44 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 457.47 | 52813.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 29500.18 |
Natural Gas | 0.00 | 1571.77 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 31071.95 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 121.13 |
Space Heating | 0.00 |
Space Cooling | 24.96 |
Fans (All) | 56.06 |
Service Water Heating | 9.88 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 636.87 |
Subtotal | 636.87 |
Natural Gas [MJ/m2] | |
Space Heating | 33.93 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 33.93 |
Subtotal | 33.93 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 18.06 |
Space Heating | 5.06 |
Space Cooling | 3.72 |
Fans (All) | 8.36 |
Service Water Heating | 1.47 |
Receptacle Equipment | 47.23 |
Miscellaneous | 16.10 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
LTG_SCH_DATACENTER | 2939. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8676.50 | 83.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8729.50 | 30.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8746.67 | 13.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8746.33 | 13.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8717.50 | 42.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8747.00 | 13.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8742.83 | 17.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8750.33 | 9.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8749.17 | 10.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8742.83 | 17.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6380.17 | 2379.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6354.67 | 2405.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6312.33 | 2447.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8153.17 | 606.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8742.83 | 17.17 | 0.00 | 0.00 | 0.00 |
Min | 6312.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2447.67 | 0.00 | 0.00 | 0.00 |
Average | 8406.85 | 353.15 | 0.00 | 0.00 | 0.00 |
Sum | 193357.50 | 8122.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368494.67 | 121.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330741.00 | 72.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1376.17 | 891.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1373.50 | 894.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1373.00 | 895.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 92130.17 | 11264.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368494.67 | 11264.83 | 0.00 | 0.00 | 0.00 |
Average | 79720.15 | 614.76 | 0.00 | 0.00 | 0.00 |
Sum | 1833563.50 | 14139.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8597.17 | 162.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8637.33 | 114.83 | 7.83 | 0.00 | 0.00 |
CORE_MID | 8713.17 | 46.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8748.17 | 11.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8746.00 | 14.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8681.83 | 78.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8749.00 | 11.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8745.00 | 15.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8737.67 | 22.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8751.50 | 8.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8747.00 | 13.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8739.17 | 20.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7554.33 | 1205.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7505.00 | 1255.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7489.50 | 1270.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8298.33 | 461.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8667.33 | 92.67 | 0.00 | 0.00 | 0.00 |
Min | 7489.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1270.50 | 7.83 | 0.00 | 0.00 |
Average | 8550.72 | 208.94 | 0.34 | 0.00 | 0.00 |
Sum | 196666.50 | 4805.67 | 7.83 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 368201.83 | 414.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330654.33 | 112.67 | 46.00 | 0.00 | 0.00 |
CORE_MID | 330722.00 | 91.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330809.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1677.17 | 590.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1647.67 | 620.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1618.83 | 649.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 93910.67 | 9484.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368201.83 | 9484.33 | 46.00 | 0.00 | 0.00 |
Average | 79812.63 | 520.28 | 2.00 | 0.00 | 0.00 |
Sum | 1835690.50 | 11966.50 | 46.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:36
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.514266E+11 | 141753.25 | 02-JAN-04:01 | 1.17 | 0.70 | 0.541025E+10 | 7495.81 | 17-JAN-10:09 | 9.75 | 7.86 |
February | 0.451705E+11 | 131114.78 | 21-FEB-05:11 | 5.37 | 4.72 | 0.499307E+10 | 7498.38 | 24-FEB-10:30 | 5.50 | 4.13 |
March | 0.529937E+11 | 117630.18 | 13-MAR-04:11 | 2.17 | 1.63 | 0.602121E+10 | 7498.57 | 02-MAR-10:50 | 2.17 | 1.63 |
April | 0.551997E+11 | 118088.31 | 24-APR-04:11 | 7.00 | 5.73 | 0.530859E+10 | 7499.28 | 27-APR-13:50 | 17.00 | 10.39 |
May | 0.565642E+11 | 129409.81 | 03-MAY-05:01 | 3.50 | 2.98 | 0.567294E+10 | 7499.31 | 23-MAY-13:20 | 18.33 | 14.52 |
June | 0.586189E+11 | 132140.94 | 12-JUN-04:11 | 8.33 | 8.33 | 0.578647E+10 | 7499.34 | 09-JUN-13:20 | 8.33 | 8.33 |
July | 0.597314E+11 | 121238.32 | 01-JUL-04:12 | 10.67 | 8.74 | 0.543333E+10 | 7499.34 | 13-JUL-09:20 | 16.67 | 13.83 |
August | 0.669417E+11 | 124677.96 | 07-AUG-04:12 | 10.67 | 9.54 | 0.609576E+10 | 7499.34 | 11-AUG-13:50 | 16.33 | 14.83 |
September | 0.590589E+11 | 129654.47 | 05-SEP-04:11 | 6.67 | 6.14 | 0.534252E+10 | 7499.33 | 18-SEP-13:30 | 16.50 | 13.79 |
October | 0.578034E+11 | 136573.47 | 02-OCT-04:11 | 9.67 | 7.33 | 0.552989E+10 | 7499.21 | 04-OCT-13:50 | 14.00 | 10.28 |
November | 0.552203E+11 | 132901.59 | 01-NOV-04:11 | 5.67 | 4.58 | 0.552363E+10 | 7498.56 | 08-NOV-14:00 | 12.00 | 12.00 |
December | 0.537553E+11 | 120243.86 | 26-DEC-05:11 | 1.97 | 0.30 | 0.529718E+10 | 7498.23 | 13-DEC-10:09 | 1.97 | 0.30 |
Annual Sum or Average | 0.672484E+12 | 0.664148E+11 | ||||||||
Minimum of Months | 0.451705E+11 | 117630.18 | 1.17 | 0.30 | 0.499307E+10 | 7495.81 | 1.97 | 0.30 | ||
Maximum of Months | 0.669417E+11 | 141753.25 | 10.67 | 9.54 | 0.609576E+10 | 7499.34 | 18.33 | 14.83 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.410603E+11 | 111759.61 | 02-JAN-05:01 | 1.00 | 0.59 | 0.504233E+10 | 6734.87 | 05-JAN-10:09 | 4.17 | 3.75 |
February | 0.380138E+11 | 105326.30 | 22-FEB-06:01 | 6.83 | 6.83 | 0.457493E+10 | 6734.90 | 21-FEB-10:20 | 6.83 | 6.83 |
March | 0.482937E+11 | 106867.96 | 18-MAR-05:01 | 9.00 | 9.00 | 0.548232E+10 | 6734.90 | 06-MAR-10:09 | 9.00 | 9.00 |
April | 0.530437E+11 | 113680.99 | 24-APR-04:11 | 7.00 | 5.73 | 0.488277E+10 | 6735.02 | 14-APR-13:39 | 7.00 | 5.73 |
May | 0.521041E+11 | 113104.43 | 01-MAY-04:12 | 4.67 | 3.91 | 0.527573E+10 | 6734.85 | 16-MAY-13:30 | 9.50 | 8.21 |
June | 0.560659E+11 | 113959.70 | 27-JUN-04:11 | 14.00 | 14.00 | 0.526735E+10 | 6734.94 | 20-JUN-09:09 | 14.00 | 14.00 |
July | 0.597528E+11 | 117664.95 | 24-JUL-04:11 | 13.00 | 13.00 | 0.489523E+10 | 6734.89 | 06-JUL-09:09 | 13.00 | 13.00 |
August | 0.661962E+11 | 115456.22 | 17-AUG-04:11 | 13.07 | 12.82 | 0.549777E+10 | 6734.99 | 08-AUG-09:00 | 13.07 | 12.82 |
September | 0.524332E+11 | 111291.02 | 01-SEP-04:12 | 13.33 | 12.77 | 0.487337E+10 | 6734.96 | 06-SEP-09:09 | 13.33 | 11.45 |
October | 0.470204E+11 | 113924.47 | 10-OCT-04:11 | 10.33 | 10.33 | 0.506570E+10 | 6734.92 | 17-OCT-09:09 | 12.33 | 11.88 |
November | 0.449696E+11 | 109804.46 | 13-NOV-05:11 | 3.33 | 3.18 | 0.501761E+10 | 6734.90 | 01-NOV-09:00 | 3.33 | 3.18 |
December | 0.437207E+11 | 106032.36 | 06-DEC-06:01 | 3.17 | 2.31 | 0.488090E+10 | 6734.89 | 07-DEC-10:30 | 7.00 | 5.54 |
Annual Sum or Average | 0.602674E+12 | 0.607560E+11 | ||||||||
Minimum of Months | 0.380138E+11 | 105326.30 | 1.00 | 0.59 | 0.457493E+10 | 6734.85 | 3.33 | 3.18 | ||
Maximum of Months | 0.661962E+11 | 117664.95 | 14.00 | 14.00 | 0.549777E+10 | 6735.02 | 14.00 | 14.00 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319375E+11 | 85620.08 | 20-JAN-06:02 | 2.00 | 1.57 | 0.491203E+10 | 6734.86 | 23-JAN-10:50 | 10.67 | 9.62 |
February | 0.304491E+11 | 85138.55 | 10-FEB-06:02 | 5.00 | 4.51 | 0.449419E+10 | 6734.91 | 15-FEB-10:20 | 5.33 | 4.26 |
March | 0.375407E+11 | 92140.66 | 24-MAR-05:02 | 4.00 | 3.12 | 0.541476E+10 | 6734.90 | 29-MAR-09:20 | 7.33 | 6.23 |
April | 0.409498E+11 | 100685.67 | 27-APR-05:01 | 4.00 | 3.12 | 0.484700E+10 | 6734.98 | 14-APR-13:39 | 4.00 | 3.12 |
May | 0.439703E+11 | 99571.31 | 03-MAY-05:01 | 3.50 | 2.98 | 0.524820E+10 | 6734.86 | 04-MAY-09:50 | 9.00 | 8.35 |
June | 0.473666E+11 | 102181.21 | 24-JUN-05:01 | 12.00 | 10.35 | 0.524771E+10 | 6734.93 | 20-JUN-09:09 | 12.00 | 10.35 |
July | 0.468012E+11 | 102483.95 | 24-JUL-05:01 | 13.00 | 13.00 | 0.487333E+10 | 6734.90 | 17-JUL-09:30 | 13.00 | 13.00 |
August | 0.511775E+11 | 101436.62 | 17-AUG-04:11 | 13.07 | 12.82 | 0.547499E+10 | 6734.92 | 08-AUG-09:00 | 13.07 | 12.82 |
September | 0.438477E+11 | 99589.49 | 02-SEP-05:02 | 13.00 | 11.97 | 0.484754E+10 | 6734.93 | 06-SEP-09:09 | 13.33 | 11.45 |
October | 0.373835E+11 | 98299.94 | 12-OCT-05:01 | 4.83 | 4.43 | 0.501495E+10 | 6734.92 | 17-OCT-09:09 | 12.33 | 11.88 |
November | 0.330925E+11 | 94617.51 | 09-NOV-06:01 | 9.00 | 9.00 | 0.492742E+10 | 6734.90 | 13-NOV-10:20 | 8.33 | 7.62 |
December | 0.303813E+11 | 34656.01 | 21-DEC-16:55 | 6.00 | 5.49 | 0.471981E+10 | 6734.89 | 07-DEC-10:30 | 6.00 | 5.49 |
Annual Sum or Average | 0.474898E+12 | 0.600219E+11 | ||||||||
Minimum of Months | 0.303813E+11 | 34656.01 | 2.00 | 1.57 | 0.449419E+10 | 6734.86 | 4.00 | 3.12 | ||
Maximum of Months | 0.511775E+11 | 102483.95 | 13.07 | 13.00 | 0.547499E+10 | 6734.98 | 13.33 | 13.00 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202469E+11 | 24900.06 | 19-JAN-16:45 | 6.33 | 6.25 | 0.417576E+10 | 6632.91 | 19-JAN-14:00 | 6.33 | 6.25 |
February | 0.198892E+11 | 25157.00 | 09-FEB-16:52 | 6.00 | 4.60 | 0.388899E+10 | 6664.28 | 03-FEB-14:00 | 6.00 | 4.60 |
March | 0.255122E+11 | 30555.28 | 31-MAR-15:52 | 9.00 | 4.96 | 0.479930E+10 | 6734.88 | 31-MAR-13:00 | 9.00 | 4.96 |
April | 0.331067E+11 | 51787.85 | 28-APR-16:00 | 20.00 | 12.32 | 0.456842E+10 | 6734.96 | 14-APR-13:00 | 20.00 | 12.32 |
May | 0.378664E+11 | 53942.88 | 23-MAY-15:40 | 18.00 | 14.38 | 0.502115E+10 | 6734.86 | 12-MAY-09:50 | 18.00 | 14.38 |
June | 0.443482E+11 | 99258.21 | 27-JUN-05:01 | 14.17 | 14.17 | 0.515143E+10 | 6734.93 | 20-JUN-09:09 | 14.17 | 14.17 |
July | 0.452199E+11 | 99193.97 | 18-JUL-05:01 | 16.00 | 14.13 | 0.479710E+10 | 6734.89 | 06-JUL-09:09 | 16.00 | 14.13 |
August | 0.469839E+11 | 54545.18 | 17-AUG-15:40 | 21.33 | 16.29 | 0.537773E+10 | 6734.89 | 11-AUG-13:50 | 21.33 | 16.29 |
September | 0.364417E+11 | 50910.03 | 13-SEP-16:00 | 23.00 | 16.22 | 0.465662E+10 | 6734.88 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.256892E+11 | 37165.28 | 05-OCT-15:52 | 16.00 | 9.13 | 0.450152E+10 | 6734.87 | 13-OCT-13:39 | 11.33 | 11.16 |
November | 0.217566E+11 | 28434.65 | 10-NOV-16:12 | 9.67 | 7.83 | 0.426947E+10 | 6734.85 | 10-NOV-14:30 | 9.67 | 7.83 |
December | 0.190533E+11 | 21654.12 | 21-DEC-17:00 | 6.00 | 5.49 | 0.399732E+10 | 6443.51 | 21-DEC-14:00 | 6.00 | 5.49 |
Annual Sum or Average | 0.376114E+12 | 0.552048E+11 | ||||||||
Minimum of Months | 0.190533E+11 | 21654.12 | 6.00 | 4.60 | 0.388899E+10 | 6443.51 | 6.00 | 4.60 | ||
Maximum of Months | 0.469839E+11 | 99258.21 | 23.00 | 16.29 | 0.537773E+10 | 6734.96 | 21.33 | 16.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.306972E+10 | 3479.38 | 18-JAN-06:02 | 6.17 | 5.66 | 0.537976E+09 | 822.56 | 19-JAN-14:00 | 9.00 | 7.43 |
February | 0.300705E+10 | 3510.61 | 22-FEB-06:02 | 6.83 | 6.83 | 0.501724E+09 | 823.10 | 21-FEB-14:30 | 6.83 | 6.83 |
March | 0.420350E+10 | 4943.19 | 30-MAR-13:32 | 12.67 | 7.61 | 0.633299E+09 | 845.64 | 28-MAR-13:09 | 12.67 | 7.61 |
April | 0.571953E+10 | 8299.23 | 28-APR-14:00 | 20.00 | 12.76 | 0.593809E+09 | 845.66 | 14-APR-13:39 | 20.00 | 12.76 |
May | 0.604386E+10 | 8370.53 | 22-MAY-15:00 | 24.00 | 16.08 | 0.645584E+09 | 845.63 | 16-MAY-13:30 | 24.00 | 16.08 |
June | 0.767932E+10 | 14028.30 | 13-JUN-05:01 | 14.50 | 12.20 | 0.655603E+09 | 845.64 | 20-JUN-09:09 | 16.33 | 13.20 |
July | 0.847876E+10 | 10225.79 | 10-JUL-15:00 | 23.00 | 16.69 | 0.610726E+09 | 845.64 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.869706E+10 | 9674.67 | 14-AUG-16:00 | 26.00 | 15.86 | 0.684755E+09 | 845.65 | 08-AUG-09:00 | 26.00 | 15.86 |
September | 0.606931E+10 | 8015.93 | 13-SEP-15:10 | 23.00 | 16.22 | 0.595918E+09 | 845.64 | 18-SEP-09:00 | 16.00 | 12.60 |
October | 0.431171E+10 | 5732.76 | 10-OCT-13:22 | 13.00 | 11.87 | 0.594292E+09 | 845.63 | 02-OCT-09:50 | 13.00 | 11.87 |
November | 0.358508E+10 | 3886.46 | 09-NOV-06:02 | 9.00 | 9.00 | 0.563624E+09 | 845.63 | 08-NOV-14:00 | 9.00 | 9.00 |
December | 0.314883E+10 | 3372.68 | 02-DEC-06:02 | 6.00 | 5.49 | 0.521547E+09 | 802.18 | 20-DEC-14:39 | 9.00 | 7.93 |
Annual Sum or Average | 0.640137E+11 | 0.713886E+10 | ||||||||
Minimum of Months | 0.300705E+10 | 3372.68 | 6.00 | 5.49 | 0.501724E+09 | 802.18 | 6.83 | 6.83 | ||
Maximum of Months | 0.869706E+10 | 14028.30 | 26.00 | 16.69 | 0.684755E+09 | 845.66 | 26.00 | 16.08 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.314646E+10 | 4923.75 | 17-JAN-06:02 | 6.07 | 6.02 | 0.319073E+09 | 527.94 | 20-JAN-10:30 | 5.00 | 4.55 |
February | 0.319850E+10 | 5839.92 | 17-FEB-09:32 | 2.33 | 1.65 | 0.298012E+09 | 544.96 | 17-FEB-10:39 | 5.00 | 3.80 |
March | 0.444605E+10 | 5094.84 | 18-MAR-05:01 | 9.00 | 9.00 | 0.363466E+09 | 533.56 | 31-MAR-09:50 | 8.33 | 5.01 |
April | 0.737983E+10 | 29767.17 | 30-APR-08:31 | 17.80 | 12.19 | 0.374821E+09 | 544.98 | 14-APR-13:39 | 17.80 | 12.19 |
May | 0.782663E+10 | 14484.76 | 23-MAY-08:30 | 18.00 | 14.38 | 0.402134E+09 | 544.96 | 22-MAY-13:00 | 18.00 | 14.38 |
June | 0.865900E+10 | 29183.35 | 25-JUN-09:51 | 18.00 | 12.90 | 0.410092E+09 | 544.96 | 08-JUN-13:09 | 18.00 | 12.90 |
July | 0.920013E+10 | 30853.63 | 23-JUL-08:31 | 19.67 | 15.53 | 0.386900E+09 | 544.96 | 18-JUL-13:09 | 19.67 | 15.53 |
August | 0.967393E+10 | 22037.45 | 13-AUG-08:42 | 14.83 | 13.03 | 0.431293E+09 | 544.97 | 01-AUG-09:50 | 14.83 | 13.03 |
September | 0.785174E+10 | 23241.71 | 04-SEP-09:52 | 14.50 | 11.14 | 0.378200E+09 | 544.97 | 06-SEP-09:09 | 13.33 | 11.45 |
October | 0.503313E+10 | 10302.40 | 01-OCT-08:58 | 12.00 | 8.41 | 0.352091E+09 | 544.96 | 23-OCT-09:09 | 9.33 | 8.10 |
November | 0.373926E+10 | 5668.94 | 11-NOV-10:22 | 9.00 | 6.58 | 0.322656E+09 | 530.44 | 13-NOV-10:09 | 8.17 | 7.54 |
December | 0.277275E+10 | 4511.91 | 20-DEC-05:11 | 4.67 | 4.34 | 0.303507E+09 | 496.98 | 06-DEC-10:20 | 4.67 | 4.34 |
Annual Sum or Average | 0.729274E+11 | 0.434224E+10 | ||||||||
Minimum of Months | 0.277275E+10 | 4511.91 | 2.33 | 1.65 | 0.298012E+09 | 496.98 | 4.67 | 3.80 | ||
Maximum of Months | 0.967393E+10 | 30853.63 | 19.67 | 15.53 | 0.431293E+09 | 544.98 | 19.67 | 15.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.582028E+10 | 16940.85 | 20-JAN-12:00 | 8.00 | 6.08 | 0.527764E+09 | 845.65 | 20-JAN-10:50 | 8.00 | 6.08 |
February | 0.629638E+10 | 19383.92 | 17-FEB-13:21 | 6.00 | 3.38 | 0.491440E+09 | 845.65 | 17-FEB-10:39 | 6.00 | 3.38 |
March | 0.679337E+10 | 13135.63 | 28-MAR-12:01 | 11.67 | 7.18 | 0.579343E+09 | 845.65 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.118684E+11 | 44450.93 | 30-APR-12:31 | 22.00 | 13.38 | 0.570935E+09 | 845.69 | 14-APR-13:39 | 22.00 | 13.38 |
May | 0.108461E+11 | 18426.70 | 22-MAY-13:10 | 22.17 | 14.96 | 0.605803E+09 | 845.66 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.117999E+11 | 28850.70 | 11-JUN-13:01 | 18.00 | 14.39 | 0.622803E+09 | 845.67 | 13-JUN-13:09 | 24.18 | 17.12 |
July | 0.133787E+11 | 40559.25 | 30-JUL-13:41 | 17.00 | 12.42 | 0.589073E+09 | 845.66 | 18-JUL-13:09 | 17.00 | 12.42 |
August | 0.156023E+11 | 40063.51 | 13-AUG-12:42 | 20.50 | 15.30 | 0.663267E+09 | 845.68 | 14-AUG-13:09 | 24.00 | 16.98 |
September | 0.142265E+11 | 41752.20 | 24-SEP-13:22 | 20.00 | 15.13 | 0.581290E+09 | 845.68 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.945525E+10 | 40399.16 | 01-OCT-13:01 | 12.17 | 9.71 | 0.557779E+09 | 845.65 | 30-OCT-13:09 | 11.00 | 9.32 |
November | 0.654342E+10 | 20442.04 | 11-NOV-12:11 | 9.00 | 7.15 | 0.525500E+09 | 845.65 | 13-NOV-10:20 | 8.33 | 7.62 |
December | 0.482462E+10 | 17263.05 | 18-DEC-13:26 | 8.00 | 5.46 | 0.496807E+09 | 845.65 | 26-DEC-14:00 | 6.00 | 3.37 |
Annual Sum or Average | 0.117455E+12 | 0.681180E+10 | ||||||||
Minimum of Months | 0.482462E+10 | 13135.63 | 6.00 | 3.38 | 0.491440E+09 | 845.65 | 6.00 | 3.37 | ||
Maximum of Months | 0.156023E+11 | 44450.93 | 22.17 | 15.30 | 0.663267E+09 | 845.69 | 24.18 | 17.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.482662E+10 | 8178.68 | 30-JAN-16:36 | 7.37 | 6.68 | 0.326216E+09 | 543.83 | 19-JAN-14:00 | 7.37 | 6.68 |
February | 0.517452E+10 | 11275.24 | 20-FEB-15:17 | 9.00 | 4.82 | 0.307890E+09 | 544.96 | 13-FEB-14:50 | 9.00 | 4.82 |
March | 0.695499E+10 | 10707.17 | 23-MAR-15:51 | 10.00 | 6.65 | 0.381152E+09 | 544.96 | 10-MAR-14:30 | 10.00 | 6.65 |
April | 0.100071E+11 | 36213.62 | 30-APR-14:31 | 23.67 | 13.01 | 0.374357E+09 | 544.98 | 14-APR-13:39 | 23.67 | 13.01 |
May | 0.967359E+10 | 33740.48 | 28-MAY-17:02 | 12.00 | 7.59 | 0.388860E+09 | 544.96 | 22-MAY-13:00 | 12.00 | 7.59 |
June | 0.111852E+11 | 36960.02 | 11-JUN-15:41 | 16.17 | 13.66 | 0.405928E+09 | 544.96 | 08-JUN-13:09 | 16.17 | 13.66 |
July | 0.126439E+11 | 40317.47 | 09-JUL-17:11 | 21.00 | 15.03 | 0.387503E+09 | 544.96 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.130530E+11 | 34769.75 | 13-AUG-16:41 | 19.33 | 14.91 | 0.436638E+09 | 544.97 | 14-AUG-13:09 | 24.00 | 16.98 |
September | 0.925691E+10 | 32715.99 | 24-SEP-15:21 | 22.00 | 15.41 | 0.362596E+09 | 544.97 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.690989E+10 | 16173.81 | 01-OCT-15:41 | 12.17 | 9.38 | 0.353646E+09 | 544.96 | 11-OCT-13:20 | 16.00 | 10.47 |
November | 0.597408E+10 | 8071.63 | 10-NOV-15:22 | 11.50 | 8.42 | 0.340296E+09 | 544.96 | 15-NOV-14:00 | 12.00 | 8.90 |
December | 0.569425E+10 | 7095.28 | 11-DEC-06:01 | 3.17 | 3.09 | 0.325596E+09 | 544.96 | 18-DEC-14:00 | 8.00 | 5.66 |
Annual Sum or Average | 0.101354E+12 | 0.439068E+10 | ||||||||
Minimum of Months | 0.482662E+10 | 7095.28 | 3.17 | 3.09 | 0.307890E+09 | 543.83 | 7.37 | 4.82 | ||
Maximum of Months | 0.130530E+11 | 40317.47 | 23.67 | 15.41 | 0.436638E+09 | 544.98 | 24.00 | 16.98 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158100E+10 | 3420.17 | 06-JAN-10:50 | 4.67 | 4.19 | 0.486152E+09 | 745.85 | 19-JAN-14:00 | 9.00 | 7.43 |
February | 0.176590E+10 | 3725.57 | 24-FEB-12:19 | 6.00 | 4.60 | 0.447855E+09 | 728.09 | 22-FEB-14:00 | 6.00 | 4.60 |
March | 0.297757E+10 | 3728.64 | 10-MAR-14:17 | 8.33 | 4.86 | 0.563771E+09 | 814.57 | 30-MAR-13:00 | 13.00 | 7.37 |
April | 0.420616E+10 | 6956.50 | 28-APR-15:10 | 20.08 | 13.47 | 0.555668E+09 | 845.65 | 14-APR-13:39 | 20.08 | 13.47 |
May | 0.494814E+10 | 7346.07 | 31-MAY-16:00 | 21.00 | 15.01 | 0.611277E+09 | 845.63 | 24-MAY-13:09 | 21.00 | 15.01 |
June | 0.644412E+10 | 9324.90 | 13-JUN-16:00 | 26.50 | 17.70 | 0.639176E+09 | 845.64 | 08-JUN-13:09 | 26.50 | 17.70 |
July | 0.678853E+10 | 9090.07 | 21-JUL-15:50 | 27.83 | 16.07 | 0.597119E+09 | 845.64 | 18-JUL-13:09 | 27.83 | 16.07 |
August | 0.681256E+10 | 8031.93 | 14-AUG-16:00 | 26.00 | 15.86 | 0.664844E+09 | 845.63 | 11-AUG-13:50 | 26.00 | 15.86 |
September | 0.494452E+10 | 7243.39 | 13-SEP-15:30 | 23.00 | 16.22 | 0.569328E+09 | 845.64 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.318398E+10 | 4201.48 | 06-OCT-15:32 | 17.00 | 9.21 | 0.536791E+09 | 844.51 | 11-OCT-13:00 | 16.00 | 10.23 |
November | 0.212631E+10 | 3444.82 | 09-NOV-06:01 | 9.00 | 9.00 | 0.492368E+09 | 770.93 | 08-NOV-14:00 | 9.00 | 9.00 |
December | 0.122932E+10 | 2708.53 | 20-DEC-14:32 | 9.00 | 7.93 | 0.456298E+09 | 690.67 | 20-DEC-14:39 | 9.00 | 7.93 |
Annual Sum or Average | 0.470081E+11 | 0.662065E+10 | ||||||||
Minimum of Months | 0.122932E+10 | 2708.53 | 4.67 | 4.19 | 0.447855E+09 | 690.67 | 6.00 | 4.60 | ||
Maximum of Months | 0.681256E+10 | 9324.90 | 27.83 | 17.70 | 0.664844E+09 | 845.65 | 27.83 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134754E+10 | 6536.89 | 20-JAN-11:02 | 6.33 | 5.61 | 0.228101E+09 | 548.49 | 20-JAN-11:09 | 6.33 | 5.61 |
February | 0.159873E+10 | 12786.73 | 23-FEB-11:01 | 7.02 | 5.19 | 0.211268E+09 | 548.49 | 17-FEB-11:09 | 7.02 | 5.19 |
March | 0.245130E+10 | 13286.22 | 30-MAR-10:01 | 9.17 | 6.66 | 0.257651E+09 | 548.49 | 28-MAR-12:09 | 9.17 | 6.66 |
April | 0.619237E+10 | 22091.49 | 30-APR-09:22 | 19.00 | 12.37 | 0.269547E+09 | 548.50 | 28-APR-14:09 | 19.00 | 12.37 |
May | 0.669459E+10 | 28984.69 | 21-MAY-08:52 | 13.00 | 9.30 | 0.289375E+09 | 548.50 | 22-MAY-14:09 | 23.17 | 15.81 |
June | 0.781739E+10 | 30670.94 | 25-JUN-10:11 | 19.00 | 13.44 | 0.296101E+09 | 548.50 | 13-JUN-12:09 | 19.00 | 13.44 |
July | 0.825753E+10 | 31775.16 | 16-JUL-09:11 | 16.00 | 13.59 | 0.280068E+09 | 548.54 | 10-JUL-10:09 | 16.00 | 13.59 |
August | 0.876622E+10 | 21622.65 | 06-AUG-09:42 | 15.83 | 13.53 | 0.310432E+09 | 548.51 | 14-AUG-10:09 | 22.00 | 16.44 |
September | 0.681516E+10 | 19886.48 | 10-SEP-08:52 | 17.00 | 13.95 | 0.272626E+09 | 548.51 | 12-SEP-10:09 | 17.17 | 14.50 |
October | 0.325647E+10 | 17354.74 | 03-OCT-10:01 | 13.00 | 9.30 | 0.249901E+09 | 548.49 | 03-OCT-12:09 | 13.00 | 9.72 |
November | 0.166773E+10 | 13021.01 | 03-NOV-10:01 | 7.33 | 5.22 | 0.227838E+09 | 548.49 | 03-NOV-10:09 | 7.33 | 5.22 |
December | 0.915987E+09 | 5033.08 | 08-DEC-11:02 | 6.17 | 4.24 | 0.215825E+09 | 537.35 | 08-DEC-11:09 | 6.17 | 4.24 |
Annual Sum or Average | 0.557810E+11 | 0.310873E+10 | ||||||||
Minimum of Months | 0.915987E+09 | 5033.08 | 6.17 | 4.24 | 0.211268E+09 | 537.35 | 6.17 | 4.24 | ||
Maximum of Months | 0.876622E+10 | 31775.16 | 19.00 | 13.95 | 0.310432E+09 | 548.54 | 23.17 | 16.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.498866E+10 | 20878.51 | 15-JAN-13:02 | 9.83 | 6.75 | 0.517229E+09 | 845.65 | 20-JAN-10:50 | 5.67 | 5.18 |
February | 0.572341E+10 | 35799.85 | 19-FEB-14:41 | 6.00 | 4.14 | 0.482299E+09 | 845.65 | 17-FEB-10:20 | 6.00 | 4.14 |
March | 0.559238E+10 | 12511.37 | 28-MAR-12:01 | 11.67 | 7.18 | 0.560353E+09 | 845.66 | 20-MAR-13:39 | 11.67 | 7.18 |
April | 0.108473E+11 | 41503.51 | 30-APR-13:22 | 22.50 | 12.93 | 0.558075E+09 | 845.69 | 14-APR-13:39 | 22.50 | 12.93 |
May | 0.996137E+10 | 20636.86 | 21-MAY-12:52 | 17.00 | 10.30 | 0.590448E+09 | 845.67 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.108546E+11 | 23939.05 | 11-JUN-13:21 | 18.00 | 14.39 | 0.606077E+09 | 845.66 | 13-JUN-13:09 | 24.18 | 17.12 |
July | 0.120884E+11 | 40757.29 | 30-JUL-13:31 | 17.00 | 12.42 | 0.573116E+09 | 845.66 | 18-JUL-13:09 | 17.00 | 12.42 |
August | 0.145446E+11 | 41301.33 | 06-AUG-13:02 | 17.17 | 13.56 | 0.646418E+09 | 845.68 | 14-AUG-13:09 | 24.00 | 16.98 |
September | 0.140374E+11 | 44817.81 | 10-SEP-12:51 | 21.00 | 15.44 | 0.572983E+09 | 846.43 | 12-SEP-13:20 | 20.33 | 16.30 |
October | 0.879113E+10 | 31862.97 | 01-OCT-13:22 | 12.50 | 9.55 | 0.544579E+09 | 845.70 | 03-OCT-13:20 | 13.33 | 9.34 |
November | 0.519926E+10 | 42532.63 | 11-NOV-13:21 | 9.00 | 7.22 | 0.509331E+09 | 845.65 | 10-NOV-10:50 | 9.00 | 7.22 |
December | 0.325540E+10 | 16870.25 | 18-DEC-13:26 | 8.00 | 5.46 | 0.481330E+09 | 845.65 | 26-DEC-14:00 | 6.00 | 3.37 |
Annual Sum or Average | 0.105884E+12 | 0.664224E+10 | ||||||||
Minimum of Months | 0.325540E+10 | 12511.37 | 6.00 | 4.14 | 0.481330E+09 | 845.65 | 5.67 | 3.37 | ||
Maximum of Months | 0.145446E+11 | 44817.81 | 22.50 | 15.44 | 0.646418E+09 | 846.43 | 24.18 | 17.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201902E+10 | 5286.47 | 19-JAN-15:50 | 8.17 | 7.46 | 0.307575E+09 | 503.37 | 19-JAN-15:00 | 8.00 | 7.45 |
February | 0.259499E+10 | 8577.45 | 27-FEB-16:25 | 8.00 | 6.72 | 0.287359E+09 | 530.44 | 27-FEB-14:00 | 8.00 | 6.72 |
March | 0.358737E+10 | 7959.06 | 23-MAR-16:42 | 10.00 | 6.65 | 0.340873E+09 | 521.19 | 23-MAR-15:50 | 10.00 | 6.65 |
April | 0.656255E+10 | 31294.07 | 30-APR-17:22 | 24.00 | 12.86 | 0.333007E+09 | 544.95 | 27-APR-13:50 | 24.00 | 12.86 |
May | 0.740970E+10 | 34457.46 | 21-MAY-16:51 | 20.00 | 12.79 | 0.361828E+09 | 544.96 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.898211E+10 | 34107.95 | 11-JUN-16:41 | 14.33 | 12.47 | 0.378608E+09 | 544.96 | 09-JUN-13:50 | 14.33 | 12.47 |
July | 0.952179E+10 | 36400.29 | 09-JUL-17:11 | 21.00 | 15.03 | 0.359119E+09 | 544.96 | 05-JUL-13:00 | 21.00 | 15.03 |
August | 0.933213E+10 | 33247.96 | 13-AUG-17:31 | 18.33 | 14.20 | 0.398548E+09 | 544.96 | 21-AUG-13:00 | 21.00 | 15.01 |
September | 0.705684E+10 | 28322.47 | 24-SEP-16:32 | 21.33 | 15.15 | 0.338354E+09 | 544.94 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.409560E+10 | 10884.96 | 03-OCT-15:53 | 14.00 | 8.96 | 0.323272E+09 | 539.17 | 05-OCT-13:00 | 16.00 | 8.75 |
November | 0.249156E+10 | 6079.12 | 11-NOV-14:02 | 9.00 | 7.01 | 0.305861E+09 | 514.38 | 15-NOV-14:00 | 12.00 | 8.90 |
December | 0.132816E+10 | 4438.34 | 21-DEC-14:40 | 8.00 | 6.98 | 0.291777E+09 | 464.05 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.649818E+11 | 0.402618E+10 | ||||||||
Minimum of Months | 0.132816E+10 | 4438.34 | 8.00 | 6.65 | 0.287359E+09 | 464.05 | 8.00 | 6.65 | ||
Maximum of Months | 0.952179E+10 | 36400.29 | 24.00 | 15.15 | 0.398548E+09 | 544.96 | 24.00 | 15.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.745409E+09 | 3572.13 | 19-JAN-15:35 | 8.33 | 7.46 | 0.465658E+09 | 661.29 | 19-JAN-14:00 | 8.33 | 7.46 |
February | 0.101120E+10 | 3465.24 | 03-FEB-15:00 | 9.00 | 5.33 | 0.423038E+09 | 653.19 | 03-FEB-14:00 | 9.00 | 5.33 |
March | 0.206096E+10 | 4112.29 | 30-MAR-15:30 | 12.00 | 6.19 | 0.518111E+09 | 722.64 | 30-MAR-13:00 | 12.00 | 6.19 |
April | 0.419609E+10 | 7534.04 | 28-APR-15:30 | 20.05 | 13.01 | 0.509627E+09 | 845.63 | 21-APR-13:20 | 20.05 | 13.01 |
May | 0.510186E+10 | 8429.23 | 22-MAY-15:30 | 23.50 | 15.68 | 0.562077E+09 | 845.63 | 24-MAY-13:09 | 16.00 | 12.97 |
June | 0.683252E+10 | 10794.82 | 13-JUN-15:50 | 26.42 | 17.72 | 0.602957E+09 | 845.64 | 26-JUN-13:09 | 22.00 | 16.85 |
July | 0.726046E+10 | 10308.50 | 21-JUL-15:50 | 27.83 | 16.07 | 0.569729E+09 | 845.64 | 18-JUL-13:09 | 27.83 | 16.07 |
August | 0.710069E+10 | 8946.40 | 14-AUG-16:00 | 26.00 | 15.86 | 0.628763E+09 | 845.63 | 14-AUG-13:20 | 26.00 | 15.86 |
September | 0.489042E+10 | 7691.96 | 13-SEP-15:30 | 23.00 | 16.22 | 0.526169E+09 | 845.63 | 12-SEP-13:20 | 23.00 | 16.22 |
October | 0.238237E+10 | 4566.42 | 06-OCT-15:50 | 17.00 | 9.21 | 0.486084E+09 | 759.08 | 11-OCT-13:00 | 16.00 | 10.23 |
November | 0.107526E+10 | 3770.17 | 10-NOV-15:20 | 11.67 | 8.42 | 0.463427E+09 | 686.87 | 10-NOV-14:00 | 11.67 | 8.42 |
December | 0.373972E+09 | 3093.31 | 23-DEC-17:01 | 8.00 | 6.06 | 0.447690E+09 | 625.82 | 06-DEC-10:50 | 8.00 | 6.06 |
Annual Sum or Average | 0.430312E+11 | 0.620333E+10 | ||||||||
Minimum of Months | 0.373972E+09 | 3093.31 | 8.00 | 5.33 | 0.423038E+09 | 625.82 | 8.00 | 5.33 | ||
Maximum of Months | 0.726046E+10 | 10794.82 | 27.83 | 17.72 | 0.628763E+09 | 845.64 | 27.83 | 16.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.804451E+09 | 3677.96 | 20-JAN-10:30 | 5.00 | 4.55 | 0.300135E+09 | 437.88 | 20-JAN-10:39 | 5.33 | 4.86 |
February | 0.116662E+10 | 4057.41 | 24-FEB-10:30 | 5.50 | 4.13 | 0.274487E+09 | 467.53 | 24-FEB-10:39 | 5.67 | 4.28 |
March | 0.196488E+10 | 3963.68 | 30-MAR-10:30 | 9.50 | 6.81 | 0.331049E+09 | 448.61 | 31-MAR-09:50 | 8.33 | 5.01 |
April | 0.563575E+10 | 16794.36 | 30-APR-10:02 | 19.83 | 12.47 | 0.358440E+09 | 544.98 | 14-APR-13:39 | 19.83 | 12.47 |
May | 0.630676E+10 | 14360.26 | 23-MAY-09:20 | 19.33 | 14.73 | 0.383227E+09 | 544.96 | 22-MAY-13:00 | 19.33 | 14.73 |
June | 0.770588E+10 | 29521.53 | 25-JUN-09:51 | 18.00 | 12.90 | 0.396929E+09 | 544.96 | 13-JUN-13:09 | 18.00 | 12.90 |
July | 0.813141E+10 | 31685.16 | 23-JUL-09:51 | 21.00 | 15.99 | 0.377462E+09 | 544.96 | 18-JUL-13:09 | 21.00 | 15.99 |
August | 0.846356E+10 | 13725.86 | 17-AUG-09:30 | 19.50 | 16.05 | 0.419415E+09 | 544.97 | 01-AUG-09:00 | 19.50 | 16.05 |
September | 0.613040E+10 | 12058.98 | 12-SEP-09:30 | 17.50 | 14.46 | 0.365720E+09 | 544.97 | 06-SEP-09:09 | 17.50 | 14.46 |
October | 0.266715E+10 | 6072.59 | 04-OCT-09:52 | 13.00 | 9.81 | 0.320682E+09 | 544.96 | 04-OCT-09:50 | 13.00 | 9.81 |
November | 0.101234E+10 | 3619.79 | 03-NOV-10:00 | 7.00 | 5.17 | 0.297975E+09 | 432.82 | 03-NOV-09:00 | 7.00 | 5.17 |
December | 0.449574E+09 | 3113.04 | 06-DEC-10:10 | 4.50 | 3.47 | 0.288601E+09 | 403.32 | 15-DEC-14:09 | 6.00 | 5.05 |
Annual Sum or Average | 0.504388E+11 | 0.411412E+10 | ||||||||
Minimum of Months | 0.449574E+09 | 3113.04 | 4.50 | 3.47 | 0.274487E+09 | 403.32 | 5.33 | 4.28 | ||
Maximum of Months | 0.846356E+10 | 31685.16 | 21.00 | 16.05 | 0.419415E+09 | 544.98 | 21.00 | 16.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.331397E+10 | 14798.65 | 11-JAN-13:40 | -1.3 | -2.8 | 0.495732E+09 | 845.65 | 20-JAN-14:39 | 8.33 | 6.53 |
February | 0.405644E+10 | 19569.77 | 17-FEB-14:02 | 6.00 | 3.06 | 0.463079E+09 | 845.65 | 17-FEB-10:00 | 6.00 | 3.06 |
March | 0.391870E+10 | 10432.15 | 28-MAR-12:11 | 11.33 | 7.17 | 0.534567E+09 | 845.65 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.980807E+10 | 44289.19 | 30-APR-13:22 | 22.50 | 12.93 | 0.539905E+09 | 845.68 | 14-APR-13:39 | 22.50 | 12.93 |
May | 0.913269E+10 | 20164.42 | 22-MAY-13:30 | 22.50 | 15.28 | 0.570740E+09 | 845.67 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.104363E+11 | 24548.93 | 11-JUN-13:31 | 18.00 | 14.39 | 0.589023E+09 | 845.67 | 13-JUN-13:09 | 24.18 | 17.12 |
July | 0.117876E+11 | 43080.30 | 30-JUL-13:41 | 17.00 | 12.42 | 0.560178E+09 | 845.66 | 18-JUL-13:09 | 17.00 | 12.42 |
August | 0.139192E+11 | 44264.19 | 06-AUG-13:32 | 17.67 | 13.76 | 0.630938E+09 | 845.69 | 14-AUG-13:09 | 24.00 | 16.98 |
September | 0.126493E+11 | 47239.97 | 10-SEP-14:11 | 21.33 | 16.15 | 0.558527E+09 | 845.68 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.684999E+10 | 42526.60 | 01-OCT-13:11 | 12.33 | 9.63 | 0.523936E+09 | 845.65 | 30-OCT-13:09 | 11.00 | 9.32 |
November | 0.328442E+10 | 17746.58 | 11-NOV-12:20 | 9.00 | 7.15 | 0.488668E+09 | 845.65 | 03-NOV-13:00 | 9.00 | 7.15 |
December | 0.200718E+10 | 13619.66 | 18-DEC-13:26 | 8.00 | 5.46 | 0.465609E+09 | 845.65 | 18-DEC-14:00 | 8.00 | 5.66 |
Annual Sum or Average | 0.911639E+11 | 0.642090E+10 | ||||||||
Minimum of Months | 0.200718E+10 | 10432.15 | -1.3 | -2.8 | 0.463079E+09 | 845.65 | 6.00 | 3.06 | ||
Maximum of Months | 0.139192E+11 | 47239.97 | 22.50 | 16.15 | 0.630938E+09 | 845.69 | 24.18 | 17.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119725E+10 | 5335.04 | 19-JAN-15:45 | 8.17 | 7.46 | 0.302771E+09 | 481.79 | 19-JAN-15:00 | 8.00 | 7.45 |
February | 0.177040E+10 | 7750.06 | 27-FEB-16:25 | 8.00 | 6.72 | 0.282118E+09 | 521.20 | 17-FEB-16:49 | 8.00 | 6.72 |
March | 0.254236E+10 | 7385.73 | 23-MAR-16:42 | 10.00 | 6.65 | 0.333323E+09 | 521.19 | 23-MAR-15:00 | 10.00 | 6.65 |
April | 0.599801E+10 | 33397.28 | 30-APR-17:22 | 24.00 | 12.86 | 0.324001E+09 | 544.95 | 27-APR-13:50 | 24.00 | 12.86 |
May | 0.691054E+10 | 36651.29 | 21-MAY-16:51 | 20.00 | 12.79 | 0.352095E+09 | 544.96 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.874917E+10 | 36655.50 | 11-JUN-16:51 | 14.00 | 12.24 | 0.368831E+09 | 544.96 | 09-JUN-13:00 | 14.00 | 12.24 |
July | 0.937969E+10 | 35335.68 | 16-JUL-17:11 | 18.33 | 15.08 | 0.351102E+09 | 544.96 | 05-JUL-13:00 | 18.33 | 15.08 |
August | 0.902162E+10 | 34132.42 | 06-AUG-16:11 | 17.67 | 13.44 | 0.388113E+09 | 544.96 | 15-AUG-13:00 | 19.00 | 15.28 |
September | 0.635352E+10 | 17598.94 | 10-SEP-16:52 | 19.00 | 15.90 | 0.329389E+09 | 544.93 | 13-SEP-13:00 | 23.00 | 16.22 |
October | 0.306845E+10 | 10669.63 | 03-OCT-15:53 | 14.00 | 8.96 | 0.315388E+09 | 521.20 | 11-OCT-15:39 | 14.33 | 10.66 |
November | 0.146257E+10 | 5347.15 | 10-NOV-15:40 | 11.33 | 8.41 | 0.301120E+09 | 490.50 | 15-NOV-14:00 | 12.00 | 8.90 |
December | 0.670275E+09 | 4350.53 | 21-DEC-14:40 | 8.00 | 6.98 | 0.289297E+09 | 438.00 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.571239E+11 | 0.393755E+10 | ||||||||
Minimum of Months | 0.670275E+09 | 4350.53 | 8.00 | 6.65 | 0.282118E+09 | 438.00 | 8.00 | 6.65 | ||
Maximum of Months | 0.937969E+10 | 36655.50 | 24.00 | 15.90 | 0.388113E+09 | 544.96 | 24.00 | 16.22 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.467499E+10 | 9602.75 | 02-JAN-06:01 | 1.17 | 0.75 | 0.00 | 0.00 | 01-JAN-00:10 | 1.17 | 0.75 |
February | 0.418960E+10 | 7762.14 | 23-FEB-06:05 | 1.83 | 1.83 | 0.00 | 0.00 | 01-FEB-00:10 | 1.83 | 1.83 |
March | 0.572565E+10 | 8126.25 | 25-MAR-05:07 | 1.83 | 1.40 | 0.00 | 0.00 | 01-MAR-00:10 | 1.83 | 1.40 |
April | 0.712913E+10 | 10031.13 | 29-APR-05:11 | 6.33 | 5.82 | 0.00 | 0.00 | 01-APR-00:10 | 6.33 | 5.82 |
May | 0.700597E+10 | 10918.71 | 01-MAY-05:12 | 4.67 | 3.91 | 0.00 | 0.00 | 01-MAY-00:10 | 4.67 | 3.91 |
June | 0.811640E+10 | 9369.49 | 15-JUN-05:13 | 12.00 | 10.35 | 0.00 | 0.00 | 01-JUN-00:10 | 12.00 | 10.35 |
July | 0.908293E+10 | 9366.25 | 24-JUL-05:04 | 13.00 | 13.00 | 0.00 | 0.00 | 01-JUL-00:10 | 13.00 | 13.00 |
August | 0.995680E+10 | 10060.71 | 05-AUG-05:13 | 10.00 | 9.27 | 0.00 | 0.00 | 01-AUG-00:10 | 10.00 | 9.27 |
September | 0.767422E+10 | 9640.53 | 15-SEP-05:13 | 10.67 | 10.32 | 0.00 | 0.00 | 01-SEP-00:10 | 10.67 | 10.32 |
October | 0.611642E+10 | 9035.74 | 10-OCT-05:04 | 11.00 | 11.00 | 0.00 | 0.00 | 01-OCT-00:10 | 11.00 | 11.00 |
November | 0.534426E+10 | 8205.90 | 13-NOV-05:16 | 3.33 | 3.18 | 0.00 | 0.00 | 01-NOV-00:10 | 3.33 | 3.18 |
December | 0.480966E+10 | 9896.92 | 30-DEC-06:01 | -1.0 | -2.5 | 0.00 | 0.00 | 01-DEC-00:10 | -1.0 | -2.5 |
Annual Sum or Average | 0.798260E+11 | 0.00 | ||||||||
Minimum of Months | 0.418960E+10 | 7762.14 | -1.0 | -2.5 | 0.00 | 0.00 | -1.0 | -2.5 | ||
Maximum of Months | 0.995680E+10 | 10918.71 | 13.00 | 13.00 | 0.00 | 0.00 | 13.00 | 13.00 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231937E+10 | 13405.31 | 12-JAN-05:01 | -2.0 | -3.8 | 0.00 | 0.00 | 01-JAN-00:10 | -2.0 | -3.8 |
February | 0.246508E+10 | 13657.46 | 17-FEB-05:01 | -2.1 | -2.2 | 0.00 | 0.00 | 01-FEB-00:10 | -2.1 | -2.2 |
March | 0.361157E+10 | 12121.79 | 04-MAR-05:11 | 3.00 | 0.90 | 0.00 | 0.00 | 01-MAR-00:10 | 3.00 | 0.90 |
April | 0.488242E+10 | 9307.50 | 22-APR-05:05 | 6.17 | 5.51 | 0.00 | 0.00 | 01-APR-00:10 | 6.17 | 5.51 |
May | 0.513168E+10 | 11733.65 | 05-MAY-04:11 | 5.33 | 3.83 | 0.00 | 0.00 | 01-MAY-00:10 | 5.33 | 3.83 |
June | 0.634815E+10 | 8919.87 | 24-JUN-05:06 | 12.00 | 10.35 | 0.00 | 0.00 | 01-JUN-00:10 | 12.00 | 10.35 |
July | 0.669842E+10 | 8894.38 | 15-JUL-05:05 | 8.50 | 7.86 | 0.00 | 0.00 | 01-JUL-00:10 | 8.50 | 7.86 |
August | 0.714545E+10 | 9130.90 | 19-AUG-05:10 | 12.00 | 11.46 | 0.00 | 0.00 | 01-AUG-00:10 | 12.00 | 11.46 |
September | 0.588146E+10 | 9209.36 | 14-SEP-05:10 | 11.17 | 10.03 | 0.00 | 0.00 | 01-SEP-00:10 | 11.17 | 10.03 |
October | 0.407881E+10 | 11466.08 | 21-OCT-04:11 | 7.00 | 4.67 | 0.00 | 0.00 | 01-OCT-00:10 | 7.00 | 4.67 |
November | 0.291736E+10 | 13255.29 | 17-NOV-05:11 | 3.00 | 1.77 | 0.00 | 0.00 | 01-NOV-00:10 | 3.00 | 1.77 |
December | 0.199278E+10 | 12966.26 | 26-DEC-05:11 | 1.97 | 0.30 | 0.00 | 0.00 | 01-DEC-00:10 | 1.97 | 0.30 |
Annual Sum or Average | 0.534726E+11 | 0.00 | ||||||||
Minimum of Months | 0.199278E+10 | 8894.38 | -2.1 | -3.8 | 0.00 | 0.00 | -2.1 | -3.8 | ||
Maximum of Months | 0.714545E+10 | 13657.46 | 12.00 | 11.46 | 0.00 | 0.00 | 12.00 | 11.46 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177942E+09 | 3311.51 | 15-JAN-13:20 | 9.67 | 6.81 | 0.00 | 0.00 | 01-JAN-00:10 | 9.67 | 6.81 |
February | 0.472125E+09 | 4418.21 | 22-FEB-12:30 | 9.50 | 7.93 | 0.00 | 0.00 | 01-FEB-00:10 | 9.50 | 7.93 |
March | 0.146132E+10 | 8430.05 | 25-MAR-12:30 | 13.00 | 10.05 | 0.00 | 0.00 | 01-MAR-00:10 | 13.00 | 10.05 |
April | 0.809348E+10 | 24897.93 | 28-APR-14:30 | 20.05 | 13.23 | 0.00 | 0.00 | 01-APR-00:10 | 20.05 | 13.23 |
May | 0.954491E+10 | 26915.36 | 22-MAY-14:20 | 23.33 | 15.87 | 0.00 | 0.00 | 01-MAY-00:10 | 23.33 | 15.87 |
June | 0.131078E+11 | 30189.22 | 13-JUN-14:00 | 25.10 | 17.45 | 0.00 | 0.00 | 01-JUN-00:10 | 25.10 | 17.45 |
July | 0.146515E+11 | 30303.32 | 21-JUL-14:20 | 27.00 | 16.08 | 0.00 | 0.00 | 01-JUL-00:10 | 27.00 | 16.08 |
August | 0.136966E+11 | 25619.96 | 14-AUG-14:50 | 24.83 | 16.12 | 0.00 | 0.00 | 01-AUG-00:10 | 24.83 | 16.12 |
September | 0.848749E+10 | 21467.74 | 13-SEP-14:20 | 23.00 | 16.22 | 0.00 | 0.00 | 01-SEP-00:10 | 23.00 | 16.22 |
October | 0.231075E+10 | 10592.30 | 03-OCT-13:51 | 14.00 | 9.41 | 0.00 | 0.00 | 01-OCT-00:10 | 14.00 | 9.41 |
November | 0.266520E+09 | 3935.97 | 11-NOV-13:47 | 9.00 | 7.08 | 0.00 | 0.00 | 01-NOV-00:10 | 9.00 | 7.08 |
December | 8166158.47 | 1001.63 | 06-DEC-13:00 | 7.00 | 5.14 | 0.00 | 0.00 | 01-DEC-00:10 | 7.00 | 5.14 |
Annual Sum or Average | 0.722787E+11 | 0.00 | ||||||||
Minimum of Months | 8166158.47 | 1001.63 | 7.00 | 5.14 | 0.00 | 0.00 | 7.00 | 5.14 | ||
Maximum of Months | 0.146515E+11 | 30303.32 | 27.00 | 17.45 | 0.00 | 0.00 | 27.00 | 17.45 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.300011E+10 | 2195.78 | 19-JAN-16:20 | 7.33 | 6.98 | 95230000.04 | 126.82 | 02-JAN-14:00 | 7.33 | 6.98 |
February | 0.728092E+10 | 4351.00 | 27-FEB-16:52 | 8.00 | 6.97 | 86396486.19 | 126.82 | 22-FEB-14:09 | 8.00 | 6.97 |
March | 0.134447E+11 | 6782.16 | 31-MAR-23:57 | 4.30 | 1.71 | 0.103236E+09 | 126.82 | 20-MAR-09:09 | 4.30 | 1.71 |
April | 0.186046E+11 | 8414.57 | 30-APR-18:03 | 24.00 | 13.14 | 91605100.71 | 126.82 | 28-APR-09:00 | 24.00 | 13.14 |
May | 0.408237E+10 | 3273.66 | 31-MAY-23:52 | 9.40 | 7.45 | 99233377.31 | 126.83 | 23-MAY-13:00 | 9.40 | 7.45 |
June | 0.906831E+10 | 5015.94 | 30-JUN-23:52 | 11.00 | 9.86 | 98957813.31 | 126.82 | 13-JUN-09:09 | 11.00 | 9.86 |
July | 0.145971E+11 | 7108.37 | 31-JUL-23:53 | 11.40 | 9.79 | 91880935.61 | 126.82 | 21-JUL-09:09 | 11.40 | 9.79 |
August | 0.196284E+11 | 8088.67 | 13-AUG-18:10 | 17.83 | 13.92 | 0.103238E+09 | 126.83 | 17-AUG-09:09 | 19.17 | 15.95 |
September | 0.401456E+10 | 3047.89 | 30-SEP-23:53 | 7.60 | 5.71 | 91606166.65 | 126.83 | 12-SEP-13:00 | 7.60 | 5.71 |
October | 0.858936E+10 | 4837.38 | 31-OCT-23:51 | 6.60 | 4.32 | 95230137.78 | 126.82 | 17-OCT-09:00 | 6.60 | 4.32 |
November | 0.129515E+11 | 5903.20 | 03-NOV-15:52 | 8.00 | 4.84 | 94300295.14 | 126.82 | 24-NOV-10:09 | 12.33 | 11.53 |
December | 0.182197E+11 | 7592.91 | 18-DEC-15:13 | 7.20 | 5.18 | 91880866.02 | 126.82 | 04-DEC-10:09 | 7.20 | 5.18 |
Annual Sum or Average | 0.133482E+12 | 0.114280E+10 | ||||||||
Minimum of Months | 0.300011E+10 | 2195.78 | 4.30 | 1.71 | 86396486.19 | 126.82 | 4.30 | 1.71 | ||
Maximum of Months | 0.196284E+11 | 8414.57 | 24.00 | 13.92 | 0.103238E+09 | 126.83 | 24.00 | 15.95 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148099E+10 | 1972.27 | 19-JAN-16:25 | 7.00 | 6.74 | 95230006.41 | 126.82 | 02-JAN-14:00 | 7.00 | 6.74 |
February | 0.599641E+10 | 4117.77 | 27-FEB-16:52 | 8.00 | 6.97 | 86396486.80 | 126.82 | 22-FEB-14:09 | 8.00 | 6.97 |
March | 0.119358E+11 | 6193.86 | 31-MAR-23:30 | 4.50 | 1.74 | 0.103236E+09 | 126.82 | 20-MAR-09:09 | 4.50 | 1.74 |
April | 0.172346E+11 | 7907.20 | 30-APR-18:17 | 24.00 | 13.14 | 91605105.36 | 126.82 | 28-APR-09:00 | 24.00 | 13.14 |
May | 0.320676E+10 | 2967.96 | 31-MAY-23:30 | 9.85 | 8.62 | 99233384.45 | 126.83 | 23-MAY-13:00 | 9.85 | 8.62 |
June | 0.828899E+10 | 4566.72 | 30-JUN-23:42 | 11.00 | 9.96 | 98957840.96 | 126.82 | 26-JUN-13:00 | 11.00 | 9.96 |
July | 0.135250E+11 | 6701.26 | 31-JUL-23:22 | 11.35 | 9.97 | 91880959.77 | 126.82 | 24-JUL-13:09 | 11.35 | 9.97 |
August | 0.183579E+11 | 7705.19 | 31-AUG-17:31 | 16.67 | 12.45 | 0.103239E+09 | 126.83 | 17-AUG-13:09 | 16.67 | 12.45 |
September | 0.314341E+10 | 2653.73 | 30-SEP-23:12 | 7.67 | 5.77 | 91606151.71 | 126.83 | 12-SEP-13:00 | 7.67 | 5.77 |
October | 0.732824E+10 | 4271.41 | 31-OCT-23:31 | 6.63 | 4.24 | 95230144.31 | 126.82 | 17-OCT-09:00 | 6.63 | 4.24 |
November | 0.112378E+11 | 5560.08 | 03-NOV-15:52 | 8.00 | 4.84 | 94300299.86 | 126.82 | 24-NOV-10:09 | 12.33 | 11.53 |
December | 0.158336E+11 | 7055.14 | 21-DEC-15:13 | 7.67 | 6.81 | 91880869.00 | 126.82 | 04-DEC-10:09 | 7.67 | 6.81 |
Annual Sum or Average | 0.117570E+12 | 0.114280E+10 | ||||||||
Minimum of Months | 0.148099E+10 | 1972.27 | 4.50 | 1.74 | 86396486.80 | 126.82 | 4.50 | 1.74 | ||
Maximum of Months | 0.183579E+11 | 7907.20 | 24.00 | 13.14 | 0.103239E+09 | 126.83 | 24.00 | 13.14 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.496060E+09 | 1835.56 | 19-JAN-16:25 | 7.00 | 6.74 | 94990439.36 | 128.39 | 12-JAN-10:09 | 7.00 | 6.74 |
February | 0.382178E+10 | 3909.21 | 27-FEB-16:52 | 8.00 | 6.97 | 86396718.61 | 126.82 | 22-FEB-14:09 | 8.00 | 6.97 |
March | 0.994662E+10 | 5671.46 | 23-MAR-17:32 | 8.67 | 6.29 | 0.103236E+09 | 126.82 | 20-MAR-09:09 | 8.67 | 6.29 |
April | 0.159867E+11 | 8044.53 | 30-APR-18:07 | 24.00 | 13.14 | 91605106.31 | 126.82 | 28-APR-09:00 | 24.00 | 13.14 |
May | 0.223302E+10 | 2677.74 | 31-MAY-23:10 | 10.15 | 9.40 | 99235221.21 | 126.83 | 23-MAY-13:00 | 10.15 | 9.40 |
June | 0.768368E+10 | 4249.33 | 13-JUN-18:40 | 21.77 | 15.84 | 98957842.95 | 126.82 | 13-JUN-09:00 | 21.77 | 15.84 |
July | 0.129903E+11 | 6399.56 | 31-JUL-23:01 | 11.32 | 10.09 | 91880989.98 | 126.82 | 10-JUL-09:09 | 11.32 | 10.09 |
August | 0.177722E+11 | 7805.84 | 17-AUG-18:10 | 20.50 | 15.86 | 0.103238E+09 | 126.83 | 16-AUG-13:09 | 20.50 | 15.86 |
September | 0.217355E+10 | 2396.67 | 12-SEP-17:00 | 19.00 | 15.28 | 91608712.28 | 126.83 | 12-SEP-13:00 | 19.00 | 15.28 |
October | 0.535568E+10 | 4070.87 | 03-OCT-16:42 | 13.17 | 8.54 | 95230156.27 | 126.82 | 17-OCT-09:00 | 9.00 | 9.00 |
November | 0.897729E+10 | 5426.89 | 10-NOV-16:01 | 10.33 | 8.12 | 94300308.43 | 126.82 | 24-NOV-10:09 | 12.33 | 11.53 |
December | 0.132652E+11 | 6811.08 | 21-DEC-15:13 | 7.67 | 6.81 | 91880869.57 | 126.82 | 04-DEC-10:09 | 7.67 | 6.81 |
Annual Sum or Average | 0.100702E+12 | 0.114256E+10 | ||||||||
Minimum of Months | 0.496060E+09 | 1835.56 | 7.00 | 6.29 | 86396718.61 | 126.82 | 7.00 | 6.29 | ||
Maximum of Months | 0.177722E+11 | 8044.53 | 24.00 | 15.86 | 0.103238E+09 | 128.39 | 24.00 | 15.86 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234888E+12 | 94212.26 | 21-JAN-05:11 | 2.00 | 1.57 | 0.207183E+10 | 2791.34 | 11-JAN-14:00 | 2.00 | 1.57 |
February | 0.435104E+12 | 486724.57 | 27-FEB-03:52 | 6.00 | 6.00 | 0.158084E+10 | 2762.55 | 22-FEB-14:09 | 6.00 | 6.00 |
March | 0.731329E+12 | 519310.22 | 23-MAR-15:42 | 10.17 | 6.74 | 0.186490E+10 | 2639.64 | 23-MAR-07:19 | 10.17 | 6.74 |
April | 0.948654E+12 | 504983.80 | 13-APR-13:32 | 10.73 | 6.15 | 0.158957E+10 | 2813.69 | 28-APR-13:50 | 19.67 | 12.54 |
May | 0.237547E+12 | 461025.58 | 31-MAY-23:57 | 9.40 | 7.45 | 0.215245E+10 | 2773.04 | 11-MAY-13:30 | 9.40 | 7.45 |
June | 0.469970E+12 | 517082.85 | 30-JUN-23:42 | 11.00 | 9.96 | 0.192843E+10 | 2745.22 | 01-JUN-09:50 | 11.00 | 9.96 |
July | 0.730927E+12 | 516944.24 | 01-JUL-01:22 | 11.00 | 9.91 | 0.179041E+10 | 2743.88 | 21-JUL-09:00 | 22.00 | 15.42 |
August | 0.982595E+12 | 490042.48 | 22-AUG-17:23 | 16.50 | 11.98 | 0.209963E+10 | 2843.12 | 24-AUG-13:00 | 19.00 | 11.57 |
September | 0.232752E+12 | 470855.29 | 30-SEP-23:45 | 7.62 | 5.73 | 0.198505E+10 | 2788.47 | 25-SEP-13:09 | 7.62 | 5.73 |
October | 0.486276E+12 | 516267.25 | 31-OCT-23:52 | 6.60 | 4.32 | 0.183088E+10 | 2751.46 | 11-OCT-09:00 | 6.60 | 4.32 |
November | 0.710048E+12 | 516719.23 | 01-NOV-03:22 | 6.05 | 4.43 | 0.169337E+10 | 2628.22 | 20-NOV-13:50 | 7.00 | 5.08 |
December | 0.979716E+12 | 497013.42 | 11-DEC-04:12 | 3.00 | 3.00 | 0.158604E+10 | 2755.02 | 27-DEC-10:00 | 2.00 | 1.57 |
Annual Sum or Average | 0.717981E+13 | 0.221734E+11 | ||||||||
Minimum of Months | 0.232752E+12 | 94212.26 | 2.00 | 1.57 | 0.158084E+10 | 2628.22 | 2.00 | 1.57 | ||
Maximum of Months | 0.982595E+12 | 519310.22 | 16.50 | 11.98 | 0.215245E+10 | 2843.12 | 22.00 | 15.42 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 67212521.35 | 3132.24 | 05-JAN-06:05 | 2.83 |
February | 64902307.03 | 3071.56 | 16-FEB-06:05 | 3.00 |
March | 67470448.80 | 2692.98 | 16-MAR-05:05 | 1.08 |
April | 66064581.83 | 2730.09 | 14-APR-05:11 | 3.67 |
May | 60881520.35 | 3106.89 | 06-MAY-05:05 | 2.17 |
June | 78035646.02 | 2602.46 | 03-JUN-05:12 | 8.33 |
July | 77551746.72 | 8710.09 | 22-JUL-16:02 | 29.00 |
August | 42927085.02 | 2269.90 | 24-AUG-05:23 | 8.50 |
September | 45870615.80 | 2766.74 | 30-SEP-05:05 | 8.83 |
October | 75042669.90 | 2604.75 | 28-OCT-05:03 | 7.00 |
November | 64662929.19 | 2564.63 | 02-NOV-05:04 | 8.00 |
December | 67076753.82 | 2648.02 | 20-DEC-06:06 | 4.33 |
Annual Sum or Average | 0.777699E+09 | |||
Minimum of Months | 42927085.02 | 2269.90 | 1.08 | |
Maximum of Months | 78035646.02 | 8710.09 | 29.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2510380.40 | 24721.55 | 02-JAN-06:01 | 1.17 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 4.00 |
Annual Sum or Average | 2510380.40 | |||
Minimum of Months | 0.00 | 0.00 | 1.17 | |
Maximum of Months | 2510380.40 | 24721.55 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316194E+10 | 93136.95 | 09-JAN-04:01 | -1.9 |
February | 0.177301E+10 | 82721.63 | 13-FEB-05:01 | -1.0 |
March | 0.105330E+10 | 75739.72 | 06-MAR-05:11 | 3.87 |
April | 69597276.46 | 62711.75 | 03-APR-05:01 | 3.83 |
May | 9690441.54 | 58230.08 | 15-MAY-05:01 | 7.12 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 11.43 |
September | 1787580.83 | 11917.21 | 18-SEP-05:03 | 12.00 |
October | 0.583904E+09 | 69459.46 | 23-OCT-04:51 | 3.00 |
November | 0.170763E+10 | 82549.47 | 20-NOV-05:11 | 0.33 |
December | 0.283652E+10 | 86624.92 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.111974E+11 | |||
Minimum of Months | 0.00 | 0.00 | -1.9 | |
Maximum of Months | 0.316194E+10 | 93136.95 | 12.00 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73729063.76 | 9738.50 | 10-JAN-06:02 | -4.0 |
February | 20402900.85 | 9070.73 | 13-FEB-06:02 | -1.0 |
March | 32191.66 | 536.53 | 04-MAR-06:03 | 3.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 7.57 |
November | 1310436.87 | 5421.40 | 28-NOV-06:01 | 1.00 |
December | 8483847.19 | 9189.59 | 30-DEC-06:01 | -1.0 |
Annual Sum or Average | 0.103958E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 73729063.76 | 9738.50 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 79798579.30 | 8770.41 | 10-JAN-05:01 | -4.0 |
February | 26298223.16 | 7725.53 | 13-FEB-06:02 | -1.0 |
March | 4140238.04 | 5274.33 | 08-MAR-06:01 | -0.2 |
April | 444775.84 | 1827.85 | 11-APR-05:03 | 5.83 |
May | 159493.28 | 1463.95 | 03-MAY-05:03 | 3.50 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 476305.19 | 2615.88 | 19-OCT-05:01 | 6.67 |
November | 11947040.57 | 5424.03 | 29-NOV-06:01 | -1.0 |
December | 47616723.77 | 7815.07 | 30-DEC-06:01 | -1.0 |
Annual Sum or Average | 0.170881E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 79798579.30 | 8770.41 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.216043E+09 | 15552.58 | 10-JAN-05:01 | -4.0 |
February | 0.116575E+09 | 15542.23 | 17-FEB-06:00 | -2.9 |
March | 45812312.02 | 10172.42 | 08-MAR-06:01 | -0.2 |
April | 1495630.94 | 7166.70 | 24-APR-05:01 | 7.00 |
May | 1556440.78 | 6577.94 | 05-MAY-05:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 11.43 |
September | 148351.26 | 989.01 | 20-SEP-05:05 | 6.00 |
October | 5871704.70 | 8718.12 | 23-OCT-05:01 | 3.17 |
November | 67358194.89 | 11913.16 | 20-NOV-06:03 | -0.7 |
December | 0.180134E+09 | 14609.77 | 30-DEC-05:01 | -1.8 |
Annual Sum or Average | 0.634994E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.216043E+09 | 15552.58 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6640989.75 | 5870.92 | 10-JAN-06:02 | -4.0 |
February | 567735.90 | 2556.83 | 24-FEB-06:03 | -0.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 7.57 |
November | 36965.38 | 616.09 | 28-NOV-06:04 | 1.00 |
December | 628050.88 | 5382.88 | 30-DEC-06:01 | -1.0 |
Annual Sum or Average | 7873741.92 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 6640989.75 | 5870.92 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105609E+10 | 15414.47 | 11-JAN-05:01 | -3.0 |
February | 0.696328E+09 | 14909.08 | 17-FEB-05:01 | -2.1 |
March | 0.346405E+09 | 13214.37 | 08-MAR-05:41 | 0.05 |
April | 39024245.28 | 11364.41 | 01-APR-05:02 | 2.17 |
May | 18892867.53 | 11546.81 | 05-MAY-04:11 | 5.33 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
July | 493817.11 | 5242.26 | 31-JUL-05:01 | 7.50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 11.43 |
September | 1164637.89 | 4035.59 | 18-SEP-05:03 | 12.00 |
October | 0.152803E+09 | 12817.10 | 23-OCT-04:59 | 3.00 |
November | 0.565333E+09 | 14493.25 | 29-NOV-05:01 | -0.2 |
December | 0.142723E+10 | 15027.09 | 30-DEC-05:01 | -1.8 |
Annual Sum or Average | 0.430376E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.0 | |
Maximum of Months | 0.142723E+10 | 15414.47 | 12.00 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.663474E+09 | 14938.56 | 11-JAN-05:01 | -3.0 |
February | 0.431964E+09 | 14247.89 | 17-FEB-05:01 | -2.1 |
March | 0.234797E+09 | 11998.34 | 08-MAR-05:41 | 0.05 |
April | 23528319.09 | 9662.56 | 01-APR-05:02 | 2.17 |
May | 12484238.87 | 10484.82 | 05-MAY-04:11 | 5.33 |
June | 405263.82 | 4607.59 | 07-JUN-05:01 | 6.33 |
July | 213672.23 | 2334.43 | 31-JUL-05:01 | 7.50 |
August | 294148.06 | 1011.90 | 28-AUG-05:04 | 9.17 |
September | 1803439.26 | 1555.39 | 20-SEP-05:03 | 6.00 |
October | 0.111687E+09 | 10922.83 | 23-OCT-05:01 | 3.17 |
November | 0.366293E+09 | 13787.37 | 20-NOV-05:01 | 0.67 |
December | 0.947207E+09 | 14666.83 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.279415E+10 | |||
Minimum of Months | 213672.23 | 1011.90 | -3.0 | |
Maximum of Months | 0.947207E+09 | 14938.56 | 9.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.677842E+09 | 21596.65 | 10-JAN-05:01 | -4.0 |
February | 0.456065E+09 | 20267.72 | 17-FEB-05:01 | -2.1 |
March | 0.300146E+09 | 17442.08 | 27-MAR-04:41 | 1.07 |
April | 24000534.20 | 12980.69 | 08-APR-05:01 | 0.00 |
May | 41120069.99 | 15449.14 | 05-MAY-04:11 | 5.33 |
June | 1660102.68 | 10668.27 | 08-JUN-05:01 | 6.17 |
July | 218431.18 | 1473.20 | 31-JUL-05:03 | 7.50 |
August | 187822.60 | 1158.43 | 23-AUG-05:05 | 9.33 |
September | 328217.20 | 956.01 | 09-SEP-05:05 | 10.67 |
October | 95363104.39 | 15728.52 | 23-OCT-05:01 | 3.17 |
November | 0.407086E+09 | 19734.69 | 29-NOV-05:01 | -0.2 |
December | 0.113819E+10 | 20854.61 | 30-DEC-05:01 | -1.8 |
Annual Sum or Average | 0.314221E+10 | |||
Minimum of Months | 187822.60 | 956.01 | -4.0 | |
Maximum of Months | 0.113819E+10 | 21596.65 | 10.67 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.489155E+09 | 14477.63 | 11-JAN-05:01 | -3.0 |
February | 0.309319E+09 | 13357.68 | 17-FEB-05:01 | -2.1 |
March | 0.161972E+09 | 11214.84 | 08-MAR-06:01 | -0.2 |
April | 7803425.14 | 6520.06 | 01-APR-05:02 | 2.17 |
May | 17109786.94 | 10004.21 | 05-MAY-04:11 | 5.33 |
June | 189477.34 | 868.94 | 29-JUN-05:05 | 11.33 |
July | 91426.50 | 1066.64 | 03-JUL-05:04 | 9.17 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 11.43 |
September | 1125721.44 | 1880.02 | 07-SEP-05:03 | 8.83 |
October | 59051735.49 | 10233.75 | 23-OCT-05:01 | 3.17 |
November | 0.275327E+09 | 13349.55 | 29-NOV-05:01 | -0.2 |
December | 0.700521E+09 | 13924.91 | 30-DEC-05:01 | -1.8 |
Annual Sum or Average | 0.202166E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.0 | |
Maximum of Months | 0.700521E+09 | 14477.63 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.463252E+10 | 23789.23 | 09-JAN-04:01 | -1.9 |
February | 0.351886E+10 | 23277.57 | 18-FEB-04:01 | -2.2 |
March | 0.231675E+10 | 20648.70 | 13-MAR-04:11 | 2.17 |
April | 0.864488E+09 | 17820.19 | 01-APR-04:11 | 2.53 |
May | 0.541929E+09 | 18270.83 | 05-MAY-04:11 | 5.33 |
June | 45636720.67 | 16057.61 | 08-JUN-04:11 | 6.00 |
July | 28829045.04 | 14583.08 | 31-JUL-04:12 | 8.33 |
August | 37510118.40 | 14413.27 | 28-AUG-05:01 | 9.17 |
September | 0.366609E+09 | 15881.49 | 21-SEP-04:12 | 6.00 |
October | 0.155878E+10 | 19267.46 | 23-OCT-04:11 | 3.00 |
November | 0.307138E+10 | 22725.75 | 20-NOV-04:31 | 1.33 |
December | 0.558268E+10 | 23219.05 | 30-DEC-04:11 | -2.0 |
Annual Sum or Average | 0.225660E+11 | |||
Minimum of Months | 28829045.04 | 14413.27 | -2.2 | |
Maximum of Months | 0.558268E+10 | 23789.23 | 9.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.270325E+10 | 19644.81 | 09-JAN-04:01 | -1.9 |
February | 0.203077E+10 | 19248.15 | 17-FEB-04:01 | -2.0 |
March | 0.142107E+10 | 16884.62 | 06-MAR-05:11 | 3.87 |
April | 0.383030E+09 | 14212.22 | 01-APR-04:11 | 2.53 |
May | 0.259562E+09 | 14816.34 | 05-MAY-04:11 | 5.33 |
June | 26209499.05 | 12850.38 | 08-JUN-04:11 | 6.00 |
July | 13402202.52 | 10954.29 | 31-JUL-05:01 | 7.50 |
August | 17316660.44 | 10838.22 | 28-AUG-05:01 | 9.17 |
September | 0.166910E+09 | 12148.87 | 21-SEP-04:12 | 6.00 |
October | 0.926496E+09 | 15763.83 | 23-OCT-04:11 | 3.00 |
November | 0.183687E+10 | 18844.93 | 20-NOV-04:31 | 1.33 |
December | 0.347693E+10 | 19094.05 | 30-DEC-04:11 | -2.0 |
Annual Sum or Average | 0.132618E+11 | |||
Minimum of Months | 13402202.52 | 10838.22 | -2.0 | |
Maximum of Months | 0.347693E+10 | 19644.81 | 9.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.322355E+10 | 30056.59 | 11-JAN-04:01 | -3.1 |
February | 0.242066E+10 | 28819.42 | 17-FEB-04:01 | -2.0 |
March | 0.200263E+10 | 25942.01 | 13-MAR-04:11 | 2.17 |
April | 0.735115E+09 | 21253.42 | 01-APR-04:11 | 2.53 |
May | 0.608843E+09 | 22626.65 | 05-MAY-04:11 | 5.33 |
June | 95972212.53 | 19621.22 | 08-JUN-04:11 | 6.00 |
July | 44198140.15 | 17250.50 | 05-JUL-05:01 | 7.33 |
August | 23922951.17 | 16118.13 | 28-AUG-05:01 | 9.17 |
September | 0.229747E+09 | 16537.34 | 08-SEP-05:02 | 8.00 |
October | 0.122311E+10 | 23006.84 | 23-OCT-04:11 | 3.00 |
November | 0.227681E+10 | 28643.50 | 20-NOV-04:31 | 1.33 |
December | 0.456048E+10 | 29185.74 | 30-DEC-04:11 | -2.0 |
Annual Sum or Average | 0.174450E+11 | |||
Minimum of Months | 23922951.17 | 16118.13 | -3.1 | |
Maximum of Months | 0.456048E+10 | 30056.59 | 9.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198859E+10 | 20793.24 | 11-JAN-04:01 | -3.1 |
February | 0.138293E+10 | 19372.96 | 17-FEB-04:01 | -2.0 |
March | 0.100700E+10 | 17589.51 | 13-MAR-04:11 | 2.17 |
April | 0.330760E+09 | 13969.79 | 01-APR-04:11 | 2.53 |
May | 0.256179E+09 | 15140.44 | 05-MAY-04:11 | 5.33 |
June | 20920920.51 | 12397.64 | 08-JUN-04:11 | 6.00 |
July | 11964503.47 | 11178.19 | 05-JUL-05:01 | 7.33 |
August | 3258045.80 | 3371.87 | 28-AUG-05:01 | 9.17 |
September | 0.122315E+09 | 10918.37 | 08-SEP-05:02 | 8.00 |
October | 0.669789E+09 | 15188.24 | 23-OCT-04:11 | 3.00 |
November | 0.127763E+10 | 19549.80 | 20-NOV-04:31 | 1.33 |
December | 0.245395E+10 | 20050.98 | 30-DEC-04:11 | -2.0 |
Annual Sum or Average | 0.952529E+10 | |||
Minimum of Months | 3258045.80 | 3371.87 | -3.1 | |
Maximum of Months | 0.245395E+10 | 20793.24 | 9.17 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16968555.64 | 6829.77 | 24-JAN-06:02 | 6.00 |
February | 20929408.63 | 8905.78 | 05-FEB-14:00 | 7.00 |
March | 16550449.88 | 8076.46 | 07-MAR-06:01 | 4.00 |
April | 55789421.39 | 14453.51 | 30-APR-15:11 | 24.00 |
May | 55708792.48 | 9061.71 | 21-MAY-16:22 | 19.00 |
June | 41724278.46 | 8449.62 | 11-JUN-16:22 | 15.00 |
July | 78964899.97 | 10966.87 | 30-JUL-15:01 | 16.83 |
August | 62939620.30 | 9601.52 | 20-AUG-15:22 | 23.50 |
September | 54935738.78 | 10313.42 | 24-SEP-15:21 | 22.00 |
October | 21042905.73 | 8198.29 | 27-OCT-04:11 | 9.00 |
November | 25057492.47 | 9159.55 | 05-NOV-12:26 | 10.50 |
December | 22479107.27 | 10190.90 | 12-DEC-05:16 | 4.00 |
Annual Sum or Average | 0.473091E+09 | |||
Minimum of Months | 16550449.88 | 6829.77 | 4.00 | |
Maximum of Months | 78964899.97 | 14453.51 | 24.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.419220E+09 | 6385.47 | 15-JAN-13:02 | 9.83 |
February | 0.168521E+09 | 11469.21 | 19-FEB-14:41 | 6.00 |
March | 29903171.21 | 3008.12 | 24-MAR-05:02 | 4.00 |
April | 24323946.74 | 13692.62 | 30-APR-15:22 | 24.00 |
May | 43041194.89 | 8992.23 | 21-MAY-16:51 | 20.00 |
June | 30711152.78 | 8284.78 | 18-JUN-15:37 | 14.37 |
July | 45359258.76 | 9405.60 | 02-JUL-13:15 | 16.67 |
August | 40868761.63 | 11298.27 | 13-AUG-15:31 | 21.00 |
September | 50832319.27 | 11361.53 | 24-SEP-15:51 | 22.00 |
October | 30333484.02 | 9515.21 | 01-OCT-13:22 | 12.50 |
November | 0.112562E+09 | 9016.35 | 11-NOV-13:21 | 9.00 |
December | 0.351348E+09 | 4420.76 | 26-DEC-12:03 | 6.00 |
Annual Sum or Average | 0.134702E+10 | |||
Minimum of Months | 24323946.74 | 3008.12 | 4.00 | |
Maximum of Months | 0.419220E+09 | 13692.62 | 24.00 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115265E+11 | 36912.98 | 09-JAN-06:13 | -2.0 |
February | 0.847148E+10 | 36975.66 | 13-FEB-05:11 | -1.0 |
March | 0.642998E+10 | 29956.81 | 06-MAR-05:22 | 3.90 |
April | 0.296857E+10 | 17784.60 | 03-APR-05:01 | 3.83 |
May | 0.216196E+10 | 15169.77 | 06-MAY-04:14 | 2.67 |
June | 0.765065E+09 | 28759.26 | 13-JUN-05:01 | 14.50 |
July | 0.551288E+09 | 27338.20 | 22-JUL-05:01 | 16.33 |
August | 0.938358E+09 | 21013.07 | 17-AUG-05:01 | 13.17 |
September | 0.199362E+10 | 13584.27 | 20-SEP-04:15 | 5.33 |
October | 0.486775E+10 | 33139.60 | 23-OCT-04:21 | 3.00 |
November | 0.798777E+10 | 32490.52 | 20-NOV-06:02 | -0.7 |
December | 0.132756E+11 | 35220.06 | 04-DEC-05:41 | 3.00 |
Annual Sum or Average | 0.619379E+11 | |||
Minimum of Months | 0.551288E+09 | 13584.27 | -2.0 | |
Maximum of Months | 0.132756E+11 | 36975.66 | 16.33 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 78757305.58 | 691.43 | 02-JAN-04:55 | 1.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 4.00 |
Annual Sum or Average | 78757305.58 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 78757305.58 | 691.43 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140979E+10 | 1377.11 | 01-JAN-17:25 | 3.00 |
February | 22604815.34 | 1081.57 | 19-FEB-06:14 | 1.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.111715E+09 | 1056.04 | 13-MAY-05:04 | 8.17 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 11.43 |
September | 64390055.06 | 945.98 | 08-SEP-04:18 | 7.33 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 4.00 |
Annual Sum or Average | 0.160850E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 0.140979E+10 | 1377.11 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.92 |
February | 0.165708E+09 | 27411.95 | 07-FEB-19:21 | 8.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 61361.77 | 1022.70 | 31-MAY-23:55 | 9.40 |
June | 0.380798E+09 | 34120.06 | 16-JUN-23:21 | 9.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 11.43 |
September | 260356.00 | 1615.45 | 30-SEP-23:04 | 7.68 |
October | 0.275313E+09 | 28180.56 | 26-OCT-19:41 | 9.83 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 4.00 |
Annual Sum or Average | 0.822140E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.380798E+09 | 34120.06 | 11.43 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.278508E+11 | 29144.79 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.252627E+11 | 29144.79 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.300191E+11 | 29144.79 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.268132E+11 | 29144.79 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.289349E+11 | 29144.79 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.287951E+11 | 29144.79 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.269531E+11 | 29144.79 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.300191E+11 | 29144.79 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.268132E+11 | 29144.79 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.278508E+11 | 29144.79 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.275243E+11 | 29144.79 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.269531E+11 | 29144.79 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.333789E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.252627E+11 | 29144.79 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.300191E+11 | 29144.79 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.785272E+10 | 8217.58 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.712300E+10 | 8217.58 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.846411E+10 | 8217.58 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.756018E+10 | 8217.58 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.815842E+10 | 8217.58 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.811897E+10 | 8217.58 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.759962E+10 | 8217.58 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.846411E+10 | 8217.58 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.756018E+10 | 8217.58 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.785272E+10 | 8217.58 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.776069E+10 | 8217.58 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.759962E+10 | 8217.58 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.941143E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.712300E+10 | 8217.58 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.846411E+10 | 8217.58 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.289349E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.287951E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.275243E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.333789E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214603E+09 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297993E+09 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178280E+09 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223472E+09 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 0.528695E+09 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 249710.68 | 0.408100E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1213271.96 | 0.394149E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 161932.52 | 0.286727E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295150E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320181E+09 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395622E+09 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543688E+09 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1624917.74 | 0.408666E+10 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178280E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1213271.96 | 0.543688E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141681E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195911E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114595E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28073.63 | 0.145824E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.64 | 0.344776E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 184154.51 | 0.261471E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1021535.70 | 0.250877E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 120345.69 | 0.180691E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194025E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207346E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256284E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351908E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1354111.17 | 0.264539E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114595E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1021535.70 | 0.351908E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213182E+09 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295437E+09 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171145E+09 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 286.32 | 0.221107E+09 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.04 | 0.511824E+09 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 255925.27 | 0.390523E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1486901.26 | 0.378071E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 163526.59 | 0.280555E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295861E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315529E+09 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384760E+09 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523803E+09 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1906641.49 | 0.398180E+10 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171145E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1486901.26 | 0.523803E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147600E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207398E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122385E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161148E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 | 0.368620E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 167350.73 | 0.288660E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 719937.61 | 0.288816E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107960.06 | 0.215504E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205785E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222713E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276985E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387890E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 995249.53 | 0.289351E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122385E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 719937.61 | 0.387890E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444641E+09 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630903E+09 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378981E+09 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33360.09 | 0.474129E+09 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114330E+10 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 548974.57 | 0.892685E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2898518.39 | 0.836636E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 371715.85 | 0.600260E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623033E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667057E+09 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.811266E+09 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110357E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3852568.89 | 0.860646E+10 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378981E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2898518.39 | 0.114330E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301230E+09 |
February | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426911E+09 |
March | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255377E+09 |
April | 0.688021E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90999.96 | 0.327649E+09 |
May | 0.744847E+09 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771906E+09 |
June | 0.742030E+09 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 395954.89 | 0.589534E+09 |
July | 0.690839E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2227546.66 | 0.560265E+09 |
August | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 284131.93 | 0.400560E+09 |
September | 0.688021E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430758E+09 |
October | 0.715730E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451536E+09 |
November | 0.708685E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544622E+09 |
December | 0.690839E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737139E+09 |
Annual Sum or Average | 0.858171E+10 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2998633.44 | 0.579749E+10 |
Minimum of Months | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255377E+09 |
Maximum of Months | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2227546.66 | 0.771906E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479702E+09 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673288E+09 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387062E+09 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502875E+09 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115914E+10 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 568407.64 | 0.877492E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3540332.31 | 0.838617E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 366863.86 | 0.620103E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673780E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715282E+09 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.852722E+09 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114554E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4475603.81 | 0.892560E+10 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387062E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3540332.31 | 0.115914E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304491E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434160E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252749E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 956.29 | 0.327354E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792732E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 439661.86 | 0.615612E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1985042.88 | 0.591720E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 259520.97 | 0.422055E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427943E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457231E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551262E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751600E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2685182.00 | 0.592891E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252749E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1985042.88 | 0.792732E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495472E+09 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701298E+09 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422154E+09 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 146452.88 | 0.527413E+09 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129331E+10 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 639291.30 | 0.102683E+10 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3732359.94 | 0.958994E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 607416.05 | 0.678014E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1969.96 | 0.678352E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715208E+09 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.889124E+09 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124077E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5127490.13 | 0.962693E+10 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422154E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3732359.94 | 0.129331E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332515E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472524E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284187E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46145.83 | 0.372887E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.891944E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 435886.02 | 0.693372E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2622443.34 | 0.663722E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 301540.25 | 0.470550E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490712E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488481E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596751E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826736E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3406015.44 | 0.658438E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284187E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2622443.34 | 0.891944E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524176E+09 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748609E+09 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436728E+09 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 302.64 | 0.575892E+09 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134233E+10 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 645242.52 | 0.103146E+10 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4226008.48 | 0.986457E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 425687.93 | 0.724726E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770005E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790366E+09 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938254E+09 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127023E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5297241.57 | 0.101392E+11 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436728E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4226008.48 | 0.134233E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342579E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491923E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292019E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3635.29 | 0.379221E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.928798E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 502358.42 | 0.729675E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2432646.81 | 0.703447E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 321872.34 | 0.497110E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.84 | 0.494132E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515244E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618770E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.850419E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3260599.69 | 0.684334E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292019E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2432646.81 | 0.928798E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.785272E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.712300E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.846411E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.756018E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.815842E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.811897E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.759962E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.846411E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.756018E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.785272E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.776069E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.759962E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.941143E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.712300E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.846411E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476909E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663283E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384990E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482944E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115052E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302384.53 | 0.876614E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2085234.48 | 0.847463E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200779.23 | 0.626587E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656345E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710356E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.887671E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121577E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2588398.24 | 0.897945E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384990E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2085234.48 | 0.121577E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803863E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114695E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665995E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.836720E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201416E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570944.56 | 0.153571E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4004803.65 | 0.145857E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404228.32 | 0.107241E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114042E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122843E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150937E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203704E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4979976.53 | 0.154497E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665995E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4004803.65 | 0.203704E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736538E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105779E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650345E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864277E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205220E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41203.17 | 0.162394E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1693150.16 | 0.154133E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111341.74 | 0.109529E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109589E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110894E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133740E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182656E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1845695.07 | 0.149905E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650345E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1693150.16 | 0.205220E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 29144.79 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 29144.79 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 29144.79 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 29144.79 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 29144.79 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 29144.79 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 29144.79 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 29144.79 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 29144.79 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 29144.79 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 29144.79 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 29144.79 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 697.98 | 08-JAN-08:00 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 626.76 | 14-FEB-22:51 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 656.99 | 27-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 704.21 | 23-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 1023.86 | 04-MAY-23:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 13-JUN-15:30 | 717.91 | 05-JUN-21:50 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.59 | 22-JUL-19:10 | 682.14 | 30-JUL-19:00 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.74 | 14-AUG-16:50 | 488.61 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 640.66 | 06-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 811.60 | 20-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 842.92 | 25-NOV-04:51 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 1225.97 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.61 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 59.59 | 1225.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 458.62 | 08-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 411.05 | 08-FEB-22:02 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 421.82 | 27-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.10 | 30-APR-18:40 | 456.32 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 658.92 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.09 | 13-JUN-15:30 | 549.21 | 18-JUN-11:00 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.39 | 22-JUL-19:10 | 417.32 | 11-JUL-01:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.41 | 14-AUG-18:00 | 296.29 | 22-AUG-01:53 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 419.17 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 514.97 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 540.61 | 25-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 781.49 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.29 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 71.39 | 781.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 706.26 | 01-JAN-14:55 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 695.55 | 05-FEB-13:59 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 623.33 | 27-MAR-21:40 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.11 | 30-APR-18:40 | 661.12 | 23-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 983.38 | 04-MAY-23:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 13-JUN-15:30 | 783.39 | 18-JUN-12:20 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.93 | 22-JUL-19:10 | 664.86 | 30-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.74 | 14-AUG-16:50 | 465.92 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 613.04 | 06-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 782.98 | 20-OCT-22:00 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 784.08 | 25-NOV-04:51 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 1179.58 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.92 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 99.93 | 1179.58 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 488.62 | 08-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 435.63 | 14-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 456.69 | 27-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 515.66 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 705.62 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.09 | 13-JUN-15:30 | 587.54 | 18-JUN-16:30 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.77 | 22-JUL-19:10 | 616.37 | 30-JUL-17:00 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.16 | 14-AUG-16:50 | 371.37 | 18-AUG-02:53 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 448.72 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 569.43 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 603.31 | 25-NOV-04:51 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 856.93 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.37 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 43.77 | 856.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1404.16 | 08-JAN-08:00 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1446.86 | 08-FEB-22:02 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1444.76 | 27-MAR-21:01 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.72 | 30-APR-17:30 | 1395.88 | 23-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2172.48 | 04-MAY-23:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.51 | 13-JUN-15:40 | 1573.47 | 05-JUN-21:10 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.19 | 22-JUL-19:10 | 1363.29 | 30-JUL-18:51 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.98 | 14-AUG-16:50 | 1032.65 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1294.08 | 06-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 1684.78 | 20-OCT-21:51 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1681.50 | 25-NOV-05:13 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 2570.44 | 02-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1032.65 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 155.19 | 2570.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 934.50 | 08-JAN-08:00 |
February | 1239.33 | 01-FEB-08:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 963.66 | 08-FEB-22:02 |
March | 1239.33 | 01-MAR-08:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 962.54 | 27-MAR-21:01 |
April | 1239.33 | 03-APR-07:10 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.29 | 30-APR-18:50 | 928.14 | 23-APR-22:00 |
May | 1239.33 | 01-MAY-07:10 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1417.95 | 04-MAY-23:00 |
June | 1239.33 | 01-JUN-07:10 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.01 | 13-JUN-15:40 | 1265.06 | 18-JUN-10:10 |
July | 1239.33 | 03-JUL-07:10 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.35 | 22-JUL-19:10 | 890.57 | 11-JUL-01:51 |
August | 1239.33 | 01-AUG-07:10 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.92 | 14-AUG-18:00 | 632.70 | 22-AUG-21:10 |
September | 1239.33 | 01-SEP-07:10 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 858.76 | 06-SEP-04:00 |
October | 1239.33 | 02-OCT-07:10 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 1106.77 | 20-OCT-21:51 |
November | 1239.33 | 01-NOV-07:10 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1117.39 | 25-NOV-05:13 |
December | 1239.33 | 01-DEC-08:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 1664.49 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 632.70 | |||||
Maximum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 167.35 | 1664.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1568.19 | 01-JAN-14:55 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1591.61 | 05-FEB-14:00 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1443.80 | 27-MAR-21:01 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1551.03 | 16-APR-12:10 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2135.15 | 04-MAY-23:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.51 | 13-JUN-15:40 | 1808.09 | 18-JUN-15:31 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.93 | 22-JUL-19:10 | 1508.73 | 30-JUL-16:51 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 14-AUG-18:00 | 1010.20 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1302.39 | 06-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 1705.26 | 20-OCT-21:51 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1673.95 | 25-NOV-05:13 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 2562.01 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1010.20 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 232.93 | 2562.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 959.94 | 08-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 966.13 | 08-FEB-22:02 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 963.29 | 27-MAR-21:01 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.36 | 30-APR-12:10 | 956.88 | 15-APR-17:40 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1435.00 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.42 | 25-JUN-13:00 | 1304.18 | 18-JUN-16:10 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.07 | 22-JUL-19:10 | 1359.43 | 30-JUL-17:30 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.15 | 20-AUG-13:10 | 724.46 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 865.62 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 1138.51 | 20-OCT-21:51 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1115.28 | 25-NOV-05:20 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 1705.33 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 724.46 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 92.07 | 1705.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1692.11 | 10-JAN-05:55 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1795.91 | 08-FEB-22:02 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1796.93 | 27-MAR-21:01 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.34 | 30-APR-14:50 | 1407.48 | 23-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2421.52 | 04-MAY-23:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.83 | 13-JUN-15:50 | 1827.36 | 05-JUN-21:10 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.03 | 22-JUL-19:10 | 1610.90 | 30-JUL-19:00 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.63 | 20-AUG-13:10 | 1172.41 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.60 | 24-SEP-15:00 | 1374.17 | 29-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 1902.66 | 20-OCT-21:51 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2095.25 | 25-NOV-05:18 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 2939.62 | 02-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1172.41 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 207.03 | 2939.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1128.02 | 10-JAN-05:57 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1196.57 | 08-FEB-22:02 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1197.64 | 27-MAR-21:01 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.64 | 30-APR-18:50 | 1008.93 | 16-APR-11:53 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1593.97 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.89 | 13-JUN-15:50 | 1558.10 | 18-JUN-10:41 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.02 | 22-JUL-19:10 | 1088.20 | 30-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.40 | 14-AUG-18:00 | 757.35 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 916.05 | 29-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 1258.98 | 20-OCT-21:01 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1396.81 | 25-NOV-05:18 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 1937.88 | 05-DEC-22:02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 757.35 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 187.02 | 1937.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1692.15 | 10-JAN-05:57 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1798.92 | 08-FEB-22:02 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1797.35 | 27-MAR-21:01 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 | 30-APR-18:50 | 1865.20 | 16-APR-12:00 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2413.99 | 04-MAY-23:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.83 | 13-JUN-15:50 | 2239.40 | 18-JUN-15:31 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 270.94 | 22-JUL-19:10 | 1869.73 | 30-JUL-17:00 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.93 | 14-AUG-16:50 | 1190.97 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1374.47 | 29-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 1948.88 | 20-OCT-21:51 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2095.24 | 25-NOV-05:20 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 2964.51 | 02-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1190.97 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 270.94 | 2964.51 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1128.08 | 10-JAN-05:57 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1200.78 | 08-FEB-22:02 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1199.95 | 27-MAR-21:01 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.58 | 30-APR-12:10 | 1175.83 | 15-APR-17:40 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1642.42 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.89 | 13-JUN-15:40 | 1630.88 | 18-JUN-16:10 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.29 | 22-JUL-19:10 | 1698.47 | 30-JUL-17:00 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.67 | 20-AUG-13:10 | 854.09 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 | 10-SEP-12:20 | 931.09 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 1319.40 | 20-OCT-21:51 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1396.82 | 25-NOV-05:16 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 1988.39 | 02-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 854.09 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 114.29 | 1988.39 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 8217.58 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 8217.58 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 8217.58 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 8217.58 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 8217.58 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 8217.58 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 8217.58 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 8217.58 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 8217.58 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 8217.58 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 8217.58 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 8217.58 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 8217.58 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 8217.58 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1612.59 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1428.36 | 08-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1437.34 | 27-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1566.79 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2340.79 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.01 | 13-JUN-16:00 | 1561.48 | 05-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.69 | 22-JUL-18:51 | 1398.67 | 30-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.25 | 14-AUG-17:00 | 1064.56 | 22-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1451.56 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 1793.50 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1933.64 | 25-NOV-04:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 2829.05 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1064.56 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.69 | 2829.05 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2762.52 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2500.73 | 08-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2462.73 | 27-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2644.82 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 4103.18 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.52 | 13-JUN-16:00 | 2727.88 | 05-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.46 | 22-JUL-18:51 | 2373.75 | 11-JUL-01:51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.08 | 14-AUG-17:00 | 1837.18 | 22-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 2471.17 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 3102.73 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 3221.67 | 25-NOV-04:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 4786.05 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1837.18 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.46 | 4786.05 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2227.20 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2556.38 | 08-FEB-22:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2548.20 | 27-MAR-21:01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2453.37 | 16-APR-12:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 3887.79 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.63 | 13-JUN-17:00 | 3571.78 | 18-JUN-15:31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.17 | 22-JUL-18:51 | 2885.00 | 30-JUL-17:01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 | 14-AUG-18:00 | 1792.63 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 2063.79 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 2870.95 | 20-OCT-21:51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2703.55 | 25-NOV-05:20 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 4810.51 | 02-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1792.63 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.17 | 4810.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 141753.25 | 02-JAN-04:01 | 0.00 | 14572.39 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 131114.78 | 21-FEB-05:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 117630.18 | 13-MAR-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 118088.31 | 24-APR-04:11 | 0.00 | 25906.48 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 129409.81 | 03-MAY-05:01 | 17952.25 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 132140.94 | 12-JUN-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 121238.32 | 01-JUL-04:12 | 0.00 | 8095.77 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 124677.96 | 07-AUG-04:12 | 0.00 | 19429.86 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 129654.47 | 05-SEP-04:11 | 0.00 | 22668.17 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 136573.47 | 02-OCT-04:11 | 0.00 | 29144.79 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 132901.59 | 01-NOV-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 120243.86 | 26-DEC-05:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 117630.18 | 0.00 | 8095.77 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 141753.25 | 17952.25 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 111759.61 | 02-JAN-05:01 | 0.00 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 105326.30 | 22-FEB-06:01 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 106867.96 | 18-MAR-05:01 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 113680.99 | 24-APR-04:11 | 0.00 | 23265.84 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 113104.43 | 01-MAY-04:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 113959.70 | 27-JUN-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 117664.95 | 24-JUL-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 115456.22 | 17-AUG-04:11 | 0.00 | 26174.07 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 111291.02 | 01-SEP-04:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 113924.47 | 10-OCT-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 109804.46 | 13-NOV-05:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 106032.36 | 06-DEC-06:01 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 105326.30 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 117664.95 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 85620.08 | 20-JAN-06:02 | 9673.43 | 17449.38 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 85138.55 | 10-FEB-06:02 | 9673.43 | 17449.38 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 92140.66 | 24-MAR-05:02 | 8061.19 | 14541.15 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 100685.67 | 27-APR-05:01 | 12897.91 | 23265.84 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 99571.31 | 03-MAY-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 102181.21 | 24-JUN-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 102483.95 | 24-JUL-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 101436.62 | 17-AUG-04:11 | 0.00 | 26174.07 | 53438.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 99589.49 | 02-SEP-05:02 | 8061.19 | 14541.15 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 98299.94 | 12-OCT-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 94617.51 | 09-NOV-06:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 34656.01 | 21-DEC-16:55 | 61265.06 | 104696.28 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 34656.01 | 0.00 | 14541.15 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 102483.95 | 61265.06 | 104696.28 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 24900.06 | 19-JAN-16:45 | 30632.53 | 52348.14 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25157.00 | 09-FEB-16:52 | 91897.59 | 157044.42 | 103239.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 30555.28 | 31-MAR-15:52 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 51787.85 | 28-APR-16:00 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 53942.88 | 23-MAY-15:40 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 99258.21 | 27-JUN-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 99193.97 | 18-JUL-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 54545.18 | 17-AUG-15:40 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 50910.03 | 13-SEP-16:00 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 37165.28 | 05-OCT-15:52 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28434.65 | 10-NOV-16:12 | 61265.06 | 104696.28 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21654.12 | 21-DEC-17:00 | 61265.06 | 104696.28 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 21654.12 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 99258.21 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3479.38 | 18-JAN-06:02 | 1012.16 | 1825.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3510.61 | 22-FEB-06:02 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.99 |
March | 4943.19 | 30-MAR-13:32 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.58 |
April | 8299.23 | 28-APR-14:00 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 |
May | 8370.53 | 22-MAY-15:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14028.30 | 13-JUN-05:01 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.65 |
July | 10225.79 | 10-JUL-15:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.28 |
August | 9674.67 | 14-AUG-16:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 0.00 |
September | 8015.93 | 13-SEP-15:10 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.22 |
October | 5732.76 | 10-OCT-13:22 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.16 |
November | 3886.46 | 09-NOV-06:02 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3372.68 | 02-DEC-06:02 | 1012.16 | 1825.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3372.68 | 1012.16 | 1825.79 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14028.30 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 54.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4923.75 | 17-JAN-06:02 | 1174.10 | 2117.89 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.75 |
February | 5839.92 | 17-FEB-09:32 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5094.84 | 18-MAR-05:01 | 1304.55 | 2353.21 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.79 |
April | 29767.17 | 30-APR-08:31 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.99 |
May | 14484.76 | 23-MAY-08:30 | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 |
June | 29183.35 | 25-JUN-09:51 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30853.63 | 23-JUL-08:31 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.41 |
August | 22037.45 | 13-AUG-08:42 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.00 |
September | 23241.71 | 04-SEP-09:52 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.99 |
October | 10302.40 | 01-OCT-08:58 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5668.94 | 11-NOV-10:22 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.64 |
December | 4511.91 | 20-DEC-05:11 | 0.00 | 2117.89 | 4324.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4511.91 | 0.00 | 588.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30853.63 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16940.85 | 20-JAN-12:00 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19383.92 | 17-FEB-13:21 | 13462.06 | 23005.41 | 15124.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.18 |
March | 13135.63 | 28-MAR-12:01 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.34 |
April | 44450.93 | 30-APR-12:31 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.01 |
May | 18426.70 | 22-MAY-13:10 | 4021.67 | 6572.98 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.11 |
June | 28850.70 | 11-JUN-13:01 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.31 |
July | 40559.25 | 30-JUL-13:41 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.10 |
August | 40063.51 | 13-AUG-12:42 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.14 |
September | 41752.20 | 24-SEP-13:22 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.46 |
October | 40399.16 | 01-OCT-13:01 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.49 |
November | 20442.04 | 11-NOV-12:11 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.29 |
December | 17263.05 | 18-DEC-13:26 | 9615.76 | 16432.44 | 10802.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13135.63 | 607.31 | 1095.50 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44450.93 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8178.68 | 30-JAN-16:36 | 6196.63 | 10589.46 | 6961.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11275.24 | 20-FEB-15:17 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.78 |
March | 10707.17 | 23-MAR-15:51 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.99 |
April | 36213.62 | 30-APR-14:31 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.50 |
May | 33740.48 | 28-MAY-17:02 | 0.00 | 705.96 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.04 |
June | 36960.02 | 11-JUN-15:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.85 |
July | 40317.47 | 09-JUL-17:11 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.90 |
August | 34769.75 | 13-AUG-16:41 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.63 |
September | 32715.99 | 24-SEP-15:21 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.49 |
October | 16173.81 | 01-OCT-15:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.89 |
November | 8071.63 | 10-NOV-15:22 | 6196.63 | 10589.46 | 6961.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.32 |
December | 7095.28 | 11-DEC-06:01 | 1043.64 | 1882.57 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7095.28 | 0.00 | 705.96 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40317.47 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3420.17 | 06-JAN-10:50 | 4021.58 | 6572.83 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3725.57 | 24-FEB-12:19 | 7408.18 | 23004.91 | 13443.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.62 |
March | 3728.64 | 10-MAR-14:17 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.39 |
April | 6956.50 | 28-APR-15:10 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.38 |
May | 7346.07 | 31-MAY-16:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.48 |
June | 9324.90 | 13-JUN-16:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 40.24 | 0.00 |
July | 9090.07 | 21-JUL-15:50 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 7.89 | 0.00 |
August | 8031.93 | 14-AUG-16:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 28.10 | 0.00 |
September | 7243.39 | 13-SEP-15:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.41 |
October | 4201.48 | 06-OCT-15:32 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.47 |
November | 3444.82 | 09-NOV-06:01 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2708.53 | 20-DEC-14:32 | 8043.16 | 13145.66 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2708.53 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9324.90 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 40.24 | 169.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6536.89 | 20-JAN-11:02 | 4957.30 | 8471.56 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12786.73 | 23-FEB-11:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.87 |
March | 13286.22 | 30-MAR-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.25 |
April | 22091.49 | 30-APR-09:22 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.98 |
May | 28984.69 | 21-MAY-08:52 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.34 |
June | 30670.94 | 25-JUN-10:11 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.77 |
July | 31775.16 | 16-JUL-09:11 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.12 |
August | 21622.65 | 06-AUG-09:42 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.91 |
September | 19886.48 | 10-SEP-08:52 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17354.74 | 03-OCT-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.61 |
November | 13021.01 | 03-NOV-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.97 |
December | 5033.08 | 08-DEC-11:02 | 6196.63 | 10589.46 | 6961.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5033.08 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31775.16 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20878.51 | 15-JAN-13:02 | 506.09 | 912.91 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.78 |
February | 35799.85 | 19-FEB-14:41 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 645.48 |
March | 12511.37 | 28-MAR-12:01 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.31 |
April | 41503.51 | 30-APR-13:22 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.49 |
May | 20636.86 | 21-MAY-12:52 | 506.09 | 912.91 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521.67 |
June | 23939.05 | 11-JUN-13:21 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.16 |
July | 40757.29 | 30-JUL-13:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1000.63 |
August | 41301.33 | 06-AUG-13:02 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.85 |
September | 44817.81 | 10-SEP-12:51 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.93 |
October | 31862.97 | 01-OCT-13:22 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 652.36 |
November | 42532.63 | 11-NOV-13:21 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 866.50 |
December | 16870.25 | 18-DEC-13:26 | 9615.76 | 16432.44 | 10802.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12511.37 | 506.09 | 912.91 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.78 | |
Maximum of Months | 44817.81 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1000.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5286.47 | 19-JAN-15:50 | 2478.65 | 4235.78 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8577.45 | 27-FEB-16:25 | 2478.65 | 4235.78 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7959.06 | 23-MAR-16:42 | 3913.66 | 11766.06 | 7735.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.53 |
April | 31294.07 | 30-APR-17:22 | 0.00 | 705.96 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.71 |
May | 34457.46 | 21-MAY-16:51 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.81 |
June | 34107.95 | 11-JUN-16:41 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.71 |
July | 36400.29 | 09-JUL-17:11 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.24 |
August | 33247.96 | 13-AUG-17:31 | 0.00 | 823.62 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.63 |
September | 28322.47 | 24-SEP-16:32 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.30 |
October | 10884.96 | 03-OCT-15:53 | 8675.28 | 14825.24 | 9746.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.70 |
November | 6079.12 | 11-NOV-14:02 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.69 |
December | 4438.34 | 21-DEC-14:40 | 5183.32 | 8471.56 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4438.34 | 0.00 | 705.96 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36400.29 | 8675.28 | 14825.24 | 9746.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3572.13 | 19-JAN-15:35 | 3846.22 | 6572.83 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3465.24 | 03-FEB-15:00 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.06 |
March | 4112.29 | 30-MAR-15:30 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.18 |
April | 7534.04 | 28-APR-15:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.48 |
May | 8429.23 | 22-MAY-15:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 |
June | 10794.82 | 13-JUN-15:50 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 47.83 | 0.00 |
July | 10308.50 | 21-JUL-15:50 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 | 0.00 |
August | 8946.40 | 14-AUG-16:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 32.88 | 0.00 |
September | 7691.96 | 13-SEP-15:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 |
October | 4566.42 | 06-OCT-15:50 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.65 |
November | 3770.17 | 10-NOV-15:20 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.97 |
December | 3093.31 | 23-DEC-17:01 | 910.95 | 1643.21 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3093.31 | 910.95 | 1643.21 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10794.82 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 47.83 | 266.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3677.96 | 20-JAN-10:30 | 5183.32 | 8471.56 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4057.41 | 24-FEB-10:30 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.93 |
March | 3963.68 | 30-MAR-10:30 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.03 |
April | 16794.36 | 30-APR-10:02 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.28 |
May | 14360.26 | 23-MAY-09:20 | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.61 |
June | 29521.53 | 25-JUN-09:51 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31685.16 | 23-JUL-09:51 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.05 |
August | 13725.86 | 17-AUG-09:30 | 2591.66 | 4235.78 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.88 |
September | 12058.98 | 12-SEP-09:30 | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.54 |
October | 6072.59 | 04-OCT-09:52 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3619.79 | 03-NOV-10:00 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.85 |
December | 3113.04 | 06-DEC-10:10 | 5183.32 | 8471.56 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3113.04 | 326.14 | 588.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31685.16 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14798.65 | 11-JAN-13:40 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.38 |
February | 19569.77 | 17-FEB-14:02 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.88 |
March | 10432.15 | 28-MAR-12:11 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.11 |
April | 44289.19 | 30-APR-13:22 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.79 |
May | 20164.42 | 22-MAY-13:30 | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.86 |
June | 24548.93 | 11-JUN-13:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 612.95 |
July | 43080.30 | 30-JUL-13:41 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1275.05 |
August | 44264.19 | 06-AUG-13:32 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.29 |
September | 47239.97 | 10-SEP-14:11 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.09 |
October | 42526.60 | 01-OCT-13:11 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 817.71 |
November | 17746.58 | 11-NOV-12:20 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1017.54 |
December | 13619.66 | 18-DEC-13:26 | 9615.76 | 16432.44 | 10802.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10432.15 | 607.31 | 1095.50 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.86 | |
Maximum of Months | 47239.97 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1275.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5335.04 | 19-JAN-15:45 | 2478.65 | 4235.78 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7750.06 | 27-FEB-16:25 | 2478.65 | 4235.78 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7385.73 | 23-MAR-16:42 | 3913.66 | 11766.06 | 7735.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.80 |
April | 33397.28 | 30-APR-17:22 | 0.00 | 705.96 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.41 |
May | 36651.29 | 21-MAY-16:51 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.47 |
June | 36655.50 | 11-JUN-16:51 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648.12 |
July | 35335.68 | 16-JUL-17:11 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 826.25 |
August | 34132.42 | 06-AUG-16:11 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.56 |
September | 17598.94 | 10-SEP-16:52 | 326.14 | 588.30 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.07 |
October | 10669.63 | 03-OCT-15:53 | 8675.28 | 14825.24 | 9746.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.00 |
November | 5347.15 | 10-NOV-15:40 | 3717.98 | 6353.67 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.92 |
December | 4350.53 | 21-DEC-14:40 | 5183.32 | 8471.56 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4350.53 | 0.00 | 588.30 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36655.50 | 8675.28 | 14825.24 | 9746.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 826.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9602.75 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7762.14 | 23-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.84 |
March | 8126.25 | 25-MAR-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10031.13 | 29-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10918.71 | 01-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.54 |
June | 9369.49 | 15-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.39 |
July | 9366.25 | 24-JUL-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.73 |
August | 10060.71 | 05-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.73 |
September | 9640.53 | 15-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.83 |
October | 9035.74 | 10-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8205.90 | 13-NOV-05:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9896.92 | 30-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7762.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10918.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13405.31 | 12-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1014.70 |
February | 13657.46 | 17-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1341.41 |
March | 12121.79 | 04-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1428.32 |
April | 9307.50 | 22-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11733.65 | 05-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2952.38 |
June | 8919.87 | 24-JUN-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.65 |
July | 8894.38 | 15-JUL-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.64 |
August | 9130.90 | 19-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.62 |
September | 9209.36 | 14-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11466.08 | 21-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1570.44 |
November | 13255.29 | 17-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2428.67 |
December | 12966.26 | 26-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2118.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8894.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13657.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2952.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3311.51 | 15-JAN-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.77 |
February | 4418.21 | 22-FEB-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.68 |
March | 8430.05 | 25-MAR-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.43 |
April | 24897.93 | 28-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.04 |
May | 26915.36 | 22-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.76 |
June | 30189.22 | 13-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.54 |
July | 30303.32 | 21-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.52 | 0.00 |
August | 25619.96 | 14-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.51 |
September | 21467.74 | 13-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.71 |
October | 10592.30 | 03-OCT-13:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.40 |
November | 3935.97 | 11-NOV-13:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1070.85 |
December | 1001.63 | 06-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1001.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30303.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.52 | 1070.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2195.78 | 19-JAN-16:20 | 444.28 | 1457.57 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4351.00 | 27-FEB-16:52 | 1110.71 | 3643.92 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6782.16 | 31-MAR-23:57 | 0.00 | 121.46 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8414.57 | 30-APR-18:03 | 0.00 | 242.93 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3273.66 | 31-MAY-23:52 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5015.94 | 30-JUN-23:52 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7108.37 | 31-JUL-23:53 | 0.00 | 161.95 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8088.67 | 13-AUG-18:10 | 0.00 | 202.44 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3047.89 | 30-SEP-23:53 | 0.00 | 242.93 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4837.38 | 31-OCT-23:51 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5903.20 | 03-NOV-15:52 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7592.91 | 18-DEC-15:13 | 888.56 | 2915.14 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2195.78 | 0.00 | 121.46 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8414.57 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1972.27 | 19-JAN-16:25 | 444.28 | 1457.57 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4117.77 | 27-FEB-16:52 | 1110.71 | 3643.92 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6193.86 | 31-MAR-23:30 | 0.00 | 80.98 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7907.20 | 30-APR-18:17 | 0.00 | 121.46 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2967.96 | 31-MAY-23:30 | 0.00 | 40.49 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4566.72 | 30-JUN-23:42 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6701.26 | 31-JUL-23:22 | 0.00 | 404.88 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7705.19 | 31-AUG-17:31 | 233.83 | 2429.28 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2653.73 | 30-SEP-23:12 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4271.41 | 31-OCT-23:31 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5560.08 | 03-NOV-15:52 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7055.14 | 21-DEC-15:13 | 888.56 | 2915.14 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1972.27 | 0.00 | 40.49 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7907.20 | 2221.41 | 7287.84 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1835.56 | 19-JAN-16:25 | 444.28 | 1457.57 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3909.21 | 27-FEB-16:52 | 1110.71 | 3643.92 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5671.46 | 23-MAR-17:32 | 233.83 | 2429.28 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8044.53 | 30-APR-18:07 | 0.00 | 242.93 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2677.74 | 31-MAY-23:10 | 0.00 | 40.49 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4249.33 | 13-JUN-18:40 | 23.38 | 242.93 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6399.56 | 31-JUL-23:01 | 0.00 | 404.88 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7805.84 | 17-AUG-18:10 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2396.67 | 12-SEP-17:00 | 70.15 | 404.88 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4070.87 | 03-OCT-16:42 | 350.75 | 2024.40 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5426.89 | 10-NOV-16:01 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6811.08 | 21-DEC-15:13 | 888.56 | 2915.14 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1835.56 | 0.00 | 40.49 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8044.53 | 2221.41 | 7287.84 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 94212.26 | 21-JAN-05:11 | 0.00 | 4565.32 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 486724.57 | 27-FEB-03:52 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 519310.22 | 23-MAR-15:42 | 48086.79 | 82175.84 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 504983.80 | 13-APR-13:32 | 50279.21 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 461025.58 | 31-MAY-23:57 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 517082.85 | 30-JUN-23:42 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 516944.24 | 01-JUL-01:22 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 490042.48 | 22-AUG-17:23 | 5061.77 | 27391.95 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 470855.29 | 30-SEP-23:45 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 516267.25 | 31-OCT-23:52 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 516719.23 | 01-NOV-03:22 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 497013.42 | 11-DEC-04:12 | 0.00 | 4565.32 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 94212.26 | 0.00 | 4565.32 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 519310.22 | 50279.21 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.185111E+13 | 1439722.42 | 20-JAN-11:30 | 0.328061E+12 | 919278.41 | 02-JAN-06:19 |
February | 0.205419E+13 | 1548221.53 | 09-FEB-16:10 | 0.226102E+12 | 766736.89 | 13-FEB-05:10 |
March | 0.278075E+13 | 1759961.05 | 30-MAR-14:09 | 0.175725E+12 | 637280.20 | 13-MAR-04:19 |
April | 0.301794E+13 | 2097470.51 | 28-APR-15:00 | 0.514353E+11 | 537182.11 | 01-APR-05:10 |
May | 0.188361E+13 | 1742700.27 | 22-MAY-15:20 | 0.456203E+11 | 543840.83 | 06-MAY-05:10 |
June | 0.225716E+13 | 1953143.16 | 13-JUN-15:50 | 0.129694E+11 | 273979.84 | 07-JUN-05:10 |
July | 0.269225E+13 | 2080617.97 | 21-JUL-15:00 | 0.758669E+10 | 263517.94 | 31-JUL-05:10 |
August | 0.318182E+13 | 2216341.48 | 25-AUG-14:00 | 0.920853E+10 | 213799.63 | 23-AUG-05:10 |
September | 0.185204E+13 | 1777079.83 | 13-SEP-15:30 | 0.290148E+11 | 317742.14 | 20-SEP-05:10 |
October | 0.223009E+13 | 1708034.45 | 06-OCT-15:20 | 0.114454E+12 | 583743.59 | 23-OCT-05:10 |
November | 0.261803E+13 | 1768484.43 | 10-NOV-15:09 | 0.212035E+12 | 798955.01 | 20-NOV-06:10 |
December | 0.308118E+13 | 1925443.71 | 29-DEC-16:30 | 0.359558E+12 | 960582.02 | 26-DEC-05:19 |
Annual Sum or Average | 0.295002E+14 | 0.157177E+13 | ||||
Minimum of Months | 0.185111E+13 | 1439722.42 | 0.758669E+10 | 213799.63 | ||
Maximum of Months | 0.318182E+13 | 2216341.48 | 0.359558E+12 | 960582.02 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.468149E+12 | 0.109851E+12 | 0.766053E+12 | 0.218140E+12 | 0.161556E+12 | 0.105321E+11 | 0.00 | 0.163481E+11 | 40003.53 | 0.605070E+11 | 0.00 | 0.399757E+11 | 0.00 |
February | 0.424646E+12 | 0.903952E+11 | 0.978954E+12 | 0.199667E+12 | 0.166521E+12 | 0.293979E+11 | 0.00 | 0.610757E+11 | 8006244.49 | 0.669628E+11 | 0.00 | 0.365585E+11 | 0.00 |
March | 0.504598E+12 | 0.879729E+11 | 0.141687E+13 | 0.230864E+12 | 0.210268E+12 | 0.818749E+11 | 0.00 | 0.974424E+11 | 6255293.57 | 0.108157E+12 | 0.00 | 0.426994E+11 | 0.00 |
April | 0.450709E+12 | 0.729006E+11 | 0.165903E+13 | 0.216144E+12 | 0.252888E+12 | 0.778755E+11 | 0.00 | 0.119236E+12 | 0.433611E+09 | 0.130697E+12 | 0.00 | 0.380291E+11 | 0.00 |
May | 0.486374E+12 | 0.645955E+11 | 0.774844E+12 | 0.224502E+12 | 0.199659E+12 | 0.214110E+11 | 0.00 | 0.405154E+11 | 0.634075E+09 | 0.315323E+11 | 0.00 | 0.395463E+11 | 0.00 |
June | 0.484022E+12 | 0.567902E+11 | 0.106252E+13 | 0.222585E+12 | 0.227919E+12 | 0.416820E+11 | 0.00 | 0.112995E+12 | 0.415193E+10 | 0.633039E+10 | 0.00 | 0.381652E+11 | 0.00 |
July | 0.453060E+12 | 0.612119E+11 | 0.139340E+13 | 0.218061E+12 | 0.257948E+12 | 0.945854E+11 | 0.00 | 0.167699E+12 | 0.607439E+10 | 0.462784E+10 | 0.00 | 0.355822E+11 | 0.00 |
August | 0.504598E+12 | 0.705552E+11 | 0.173200E+13 | 0.230864E+12 | 0.298038E+12 | 0.916263E+11 | 0.00 | 0.203038E+12 | 0.671380E+10 | 0.576478E+10 | 0.00 | 0.386230E+11 | 0.00 |
September | 0.450709E+12 | 0.798215E+11 | 0.740713E+12 | 0.216143E+12 | 0.207691E+12 | 0.349908E+11 | 0.00 | 0.724541E+11 | 0.251456E+10 | 0.116867E+11 | 0.00 | 0.353180E+11 | 0.00 |
October | 0.468149E+12 | 0.950476E+11 | 0.108340E+13 | 0.218140E+12 | 0.194835E+12 | 0.296302E+11 | 0.00 | 0.716868E+11 | 0.150749E+09 | 0.318619E+11 | 0.00 | 0.371867E+11 | 0.00 |
November | 0.462662E+12 | 0.102968E+12 | 0.135889E+13 | 0.209941E+12 | 0.198120E+12 | 0.830023E+11 | 0.00 | 0.939080E+11 | 8185613.87 | 0.710501E+11 | 0.00 | 0.374782E+11 | 0.00 |
December | 0.453060E+12 | 0.112811E+12 | 0.170972E+13 | 0.218060E+12 | 0.221471E+12 | 0.758980E+11 | 0.00 | 0.996000E+11 | 3024603.65 | 0.152258E+12 | 0.00 | 0.383034E+11 | 0.00 |
Annual Sum or Average | 0.561074E+13 | 0.100492E+13 | 0.146764E+14 | 0.262311E+13 | 0.259691E+13 | 0.672506E+12 | 0.00 | 0.115600E+13 | 0.206986E+11 | 0.681436E+12 | 0.00 | 0.457466E+12 | 0.00 |
Minimum of Months | 0.424646E+12 | 0.567902E+11 | 0.740713E+12 | 0.199667E+12 | 0.161556E+12 | 0.105321E+11 | 0.00 | 0.163481E+11 | 40003.53 | 0.462784E+10 | 0.00 | 0.353180E+11 | 0.00 |
Maximum of Months | 0.504598E+12 | 0.112811E+12 | 0.173200E+13 | 0.230864E+12 | 0.298038E+12 | 0.945854E+11 | 0.00 | 0.203038E+12 | 0.671380E+10 | 0.152258E+12 | 0.00 | 0.426994E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.328061E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.226102E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.175725E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.514353E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.456203E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.129694E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.758669E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.920853E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.290148E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.114454E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.212035E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.359558E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.157177E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.758669E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.359558E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 489900.85 | 02-JAN-08:09 | 64082.80 | 01-JAN-00:10 | 423497.50 | 02-JAN-08:09 | 235096.12 | 02-JAN-08:20 | 153458.60 | 20-JAN-11:00 | 35288.80 | 20-JAN-11:30 | 0.00 | 01-JAN-00:10 |
February | 489900.85 | 01-FEB-08:09 | 64082.80 | 01-FEB-00:10 | 541788.89 | 01-FEB-08:09 | 235096.12 | 01-FEB-08:20 | 161400.24 | 17-FEB-13:39 | 36477.08 | 24-FEB-13:09 | 0.00 | 01-FEB-00:10 |
March | 489900.85 | 01-MAR-08:09 | 64082.80 | 01-MAR-00:10 | 660080.29 | 01-MAR-08:09 | 235096.12 | 01-MAR-08:20 | 148857.14 | 23-MAR-15:00 | 37312.95 | 25-MAR-11:39 | 0.00 | 01-MAR-00:10 |
April | 489900.85 | 03-APR-07:10 | 64082.80 | 01-APR-00:10 | 778371.69 | 03-APR-07:10 | 235096.12 | 03-APR-07:19 | 261483.67 | 28-APR-15:20 | 40105.51 | 28-APR-15:39 | 0.00 | 01-APR-00:10 |
May | 489900.85 | 01-MAY-07:10 | 64082.80 | 01-MAY-00:10 | 423497.50 | 01-MAY-07:10 | 235096.12 | 01-MAY-07:19 | 221941.45 | 23-MAY-15:20 | 75735.97 | 22-MAY-15:39 | 0.00 | 01-MAY-00:10 |
June | 489900.85 | 01-JUN-07:10 | 64082.80 | 01-JUN-00:10 | 541788.89 | 01-JUN-07:10 | 235096.12 | 01-JUN-07:19 | 242013.78 | 13-JUN-15:00 | 75218.85 | 13-JUN-12:00 | 0.00 | 01-JUN-00:10 |
July | 489900.85 | 03-JUL-07:10 | 64082.80 | 01-JUL-00:10 | 660080.29 | 03-JUL-07:10 | 235096.12 | 03-JUL-07:19 | 251545.16 | 21-JUL-15:00 | 76765.61 | 22-JUL-15:50 | 0.00 | 01-JUL-00:10 |
August | 489900.85 | 01-AUG-07:10 | 64082.80 | 01-AUG-00:10 | 778371.69 | 01-AUG-07:10 | 235096.12 | 01-AUG-07:19 | 252290.53 | 17-AUG-15:20 | 78697.07 | 28-AUG-13:00 | 0.00 | 01-AUG-00:10 |
September | 489900.85 | 01-SEP-07:10 | 64082.80 | 01-SEP-00:10 | 423497.50 | 01-SEP-07:10 | 235096.12 | 01-SEP-07:19 | 233435.83 | 12-SEP-15:20 | 75161.48 | 13-SEP-14:50 | 0.00 | 01-SEP-00:10 |
October | 489900.85 | 02-OCT-07:10 | 64082.80 | 01-OCT-00:10 | 541788.89 | 02-OCT-07:10 | 235096.12 | 02-OCT-07:19 | 204350.53 | 06-OCT-15:30 | 37809.34 | 17-OCT-14:09 | 0.00 | 01-OCT-00:10 |
November | 489900.85 | 01-NOV-07:10 | 64082.80 | 01-NOV-00:10 | 660080.29 | 01-NOV-07:10 | 235096.12 | 01-NOV-07:19 | 171778.65 | 10-NOV-13:00 | 37603.34 | 10-NOV-11:09 | 0.00 | 01-NOV-00:10 |
December | 489900.85 | 01-DEC-08:09 | 64082.80 | 01-DEC-00:10 | 778371.69 | 01-DEC-08:09 | 235096.12 | 01-DEC-08:20 | 151929.13 | 21-DEC-13:50 | 37838.89 | 11-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 489900.85 | 64082.80 | 423497.50 | 235096.12 | 148857.14 | 35288.80 | 0.00 | |||||||
Maximum of Months | 489900.85 | 64082.80 | 778371.69 | 235096.12 | 261483.67 | 78697.07 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 48436.03 | 20-JAN-11:30 | 23.79 | 20-JAN-11:30 | 49339.74 | 10-JAN-17:10 | 0.00 | 52758.15 | 31-JAN-12:20 | 0.00 |
February | 75051.20 | 24-FEB-13:09 | 42.23 | 09-FEB-11:20 | 66666.67 | 17-FEB-17:10 | 0.00 | 52813.61 | 15-FEB-12:00 | 0.00 |
March | 109977.04 | 30-MAR-13:30 | 418.71 | 25-MAR-12:00 | 100000.00 | 31-MAR-23:00 | 0.00 | 52755.95 | 01-MAR-12:20 | 0.00 |
April | 191103.80 | 30-APR-16:19 | 9286.03 | 30-APR-15:09 | 100000.00 | 01-APR-00:00 | 0.00 | 52229.10 | 03-APR-11:30 | 0.00 |
May | 260335.80 | 22-MAY-15:20 | 40358.75 | 22-MAY-14:39 | 76184.28 | 21-MAY-14:00 | 0.00 | 51300.18 | 01-MAY-11:20 | 0.00 |
June | 287116.36 | 13-JUN-15:00 | 44335.29 | 12-JUN-14:30 | 56567.44 | 08-JUN-17:30 | 0.00 | 49554.71 | 01-JUN-11:00 | 0.00 |
July | 299726.55 | 21-JUL-15:00 | 44335.29 | 10-JUL-10:30 | 100000.00 | 10-JUL-16:00 | 0.00 | 47982.18 | 03-JUL-11:30 | 0.00 |
August | 302213.76 | 14-AUG-15:00 | 44335.29 | 14-AUG-12:30 | 100000.00 | 22-AUG-08:00 | 0.00 | 47400.04 | 01-AUG-11:00 | 0.00 |
September | 249559.12 | 13-SEP-14:50 | 44335.29 | 13-SEP-14:30 | 56592.80 | 29-SEP-16:00 | 0.00 | 47955.60 | 29-SEP-11:20 | 0.00 |
October | 127393.41 | 17-OCT-14:09 | 4489.02 | 17-OCT-14:09 | 81831.39 | 20-OCT-17:10 | 0.00 | 49564.58 | 31-OCT-11:30 | 0.00 |
November | 123365.26 | 10-NOV-15:09 | 1040.28 | 10-NOV-15:09 | 88716.53 | 04-NOV-05:49 | 0.00 | 51401.36 | 30-NOV-12:30 | 0.00 |
December | 95993.90 | 09-DEC-04:00 | 36.48 | 16-DEC-09:39 | 100000.00 | 03-DEC-00:49 | 0.00 | 52231.56 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 48436.03 | 23.79 | 49339.74 | 0.00 | 47400.04 | 0.00 | ||||
Maximum of Months | 302213.76 | 44335.29 | 100000.00 | 0.00 | 52813.61 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1439722.42 | 20-JAN-11:30 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 147774.72 | 35288.80 | 0.00 | 48436.03 | 23.79 |
February | 1548221.53 | 09-FEB-16:10 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 144324.40 | 12323.34 | 0.00 | 38813.68 | 15.15 |
March | 1759961.05 | 30-MAR-14:09 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 137176.47 | 36916.52 | 0.00 | 105793.90 | 109.09 |
April | 2097470.51 | 28-APR-15:00 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 256616.84 | 37248.63 | 0.00 | 155782.18 | 5382.38 |
May | 1742700.27 | 22-MAY-15:20 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 207830.46 | 74519.15 | 0.00 | 260335.80 | 13276.94 |
June | 1953143.16 | 13-JUN-15:50 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 241690.00 | 75138.02 | 0.00 | 287068.28 | 44335.29 |
July | 2080617.97 | 21-JUL-15:00 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 251545.16 | 76533.27 | 0.00 | 299726.55 | 31303.04 |
August | 2216341.48 | 25-AUG-14:00 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 226410.04 | 73182.01 | 0.00 | 265297.73 | 20919.65 |
September | 1777079.83 | 13-SEP-15:30 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 228143.99 | 73869.90 | 0.00 | 246123.88 | 44335.29 |
October | 1708034.45 | 06-OCT-15:20 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 202076.82 | 36460.51 | 0.00 | 100897.48 | 426.93 |
November | 1768484.43 | 10-NOV-15:09 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 151426.09 | 37124.05 | 0.00 | 123365.26 | 1040.28 |
December | 1925443.71 | 29-DEC-16:30 | 489900.85 | 778371.69 | 64082.80 | 235096.12 | 132596.20 | 36309.73 | 0.00 | 53999.69 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1439722.42 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 132596.20 | 12323.34 | 0.00 | 38813.68 | 0.00 | |
Maximum of Months | 2216341.48 | 489900.85 | 778371.69 | 64082.80 | 235096.12 | 256616.84 | 76533.27 | 0.00 | 299726.55 | 44335.29 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 919278.41 | 02-JAN-06:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 766736.89 | 13-FEB-05:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 637280.20 | 13-MAR-04:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 537182.11 | 01-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 543840.83 | 06-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 273979.84 | 07-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 263517.94 | 31-JUL-05:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 213799.63 | 23-AUG-05:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 317742.14 | 20-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 583743.59 | 23-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 798955.01 | 20-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 960582.02 | 26-DEC-05:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 213799.63 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 960582.02 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.93 | 0.00 | 25.93 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.59 | 0.00 | 25.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.66 | 0.00 | 25.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.73 | 0.00 | 25.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.68 | 0.00 | 25.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.83 | 0.00 | 25.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.68 | 0.00 | 25.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.61 | 0.00 | 25.61 |
Annual Sum or Average | 0.00 | 0.00 | 4.00 | 25.70 | 0.00 | 25.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.93 | 0.00 | 25.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 18.99 | 0.33 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
February | 1.17 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
March | 0.50 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.83 | 18.71 | 0.17 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
December | 1.83 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
Annual Sum or Average | 7.83 | 18.81 | 0.50 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 19.14 | 0.33 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.36 | 1.00 | 28.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.80 | 1.17 | 27.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.75 | 2.00 | 27.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.32 | 2.50 | 28.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.84 | 2.33 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.75 | 1.33 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.33 | 27.98 | 10.33 | 27.98 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.36 | 2.50 | 28.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.53 | 0.33 | 27.53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.37 | 0.33 | 27.37 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.55 | 1.50 | 28.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.65 | 1.33 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.90 | 3.67 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.96 | 4.00 | 27.96 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.59 | 0.67 | 27.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.64 | 0.50 | 27.64 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.50 | 27.91 | 12.50 | 27.91 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.55 | 4.00 | 28.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.83 | 1.33 | 28.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.25 | 1.83 | 28.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.46 | 1.50 | 28.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.69 | 3.17 | 28.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.75 | 3.00 | 28.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.75 | 1.67 | 27.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 20.83 | 28.55 | 12.50 | 28.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.83 | 3.17 | 28.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
February | 0.50 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
December | 2.50 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
Annual Sum or Average | 5.33 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
February | 0.50 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.37 | 1.00 | 28.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.91 | 0.83 | 27.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.76 | 1.67 | 27.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.47 | 2.33 | 28.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.76 | 2.00 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.48 | 0.83 | 27.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
December | 4.50 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
Annual Sum or Average | 7.50 | 19.24 | 0.00 | 19.24 | 8.67 | 23.94 | 8.67 | 25.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.50 | 19.37 | 0.00 | 19.37 | 2.33 | 28.47 | 2.33 | 28.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 19.07 | 0.00 | 19.07 | 0.50 | 21.40 | 0.50 | 22.73 |
February | 0.33 | 19.34 | 0.00 | 19.34 | 0.50 | 24.35 | 0.50 | 25.61 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.70 | 1.50 | 28.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.48 | 1.00 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.89 | 3.50 | 27.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.18 | 4.33 | 28.18 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.04 | 1.00 | 28.04 |
November | 0.83 | 19.31 | 0.00 | 19.31 | 0.50 | 22.54 | 0.50 | 24.01 |
December | 2.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
Annual Sum or Average | 4.50 | 19.16 | 0.00 | 19.16 | 12.83 | 25.74 | 12.83 | 26.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 19.34 | 0.00 | 19.34 | 4.33 | 28.70 | 4.33 | 28.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
February | 0.50 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.57 | 1.00 | 28.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.22 | 1.00 | 28.20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.54 | 1.00 | 28.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.51 | 1.83 | 28.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.30 | 2.00 | 28.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.59 | 0.83 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
December | 1.67 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
Annual Sum or Average | 4.17 | 19.13 | 0.00 | 19.13 | 13.67 | 26.22 | 7.67 | 26.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.33 | 0.00 | 19.33 | 4.50 | 28.57 | 2.00 | 28.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.33 | 16.67 | 2.17 | 16.57 | 0.00 | 16.57 | 0.00 | 16.57 |
February | 11.00 | 17.12 | 1.17 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
March | 5.83 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
April | 2.00 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
May | 1.50 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
October | 3.83 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
November | 10.17 | 17.37 | 0.17 | 17.41 | 0.00 | 17.41 | 0.00 | 17.41 |
December | 21.50 | 16.26 | 2.00 | 16.18 | 0.00 | 16.18 | 0.00 | 16.18 |
Annual Sum or Average | 72.33 | 17.14 | 5.50 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 21.50 | 19.42 | 2.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.83 | 16.64 | 0.67 | 16.56 | 0.00 | 16.56 | 0.00 | 16.56 |
February | 10.17 | 17.25 | 0.67 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
March | 5.67 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 |
April | 2.00 | 19.25 | 0.00 | 19.25 | 0.67 | 21.44 | 0.67 | 22.75 |
May | 1.00 | 19.17 | 0.00 | 19.17 | 0.33 | 21.20 | 0.33 | 22.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.67 | 0.67 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.36 | 2.00 | 28.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.56 | 0.50 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4.17 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
November | 9.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
December | 20.67 | 16.15 | 1.67 | 16.06 | 0.00 | 16.06 | 0.00 | 16.06 |
Annual Sum or Average | 66.50 | 17.09 | 3.00 | 17.01 | 4.17 | 17.63 | 4.17 | 18.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.67 | 19.25 | 1.67 | 19.25 | 2.00 | 28.36 | 2.00 | 28.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.67 | 17.62 | 0.00 | 17.62 | 0.00 | 17.62 | 0.00 | 17.62 |
February | 7.33 | 17.94 | 0.50 | 17.75 | 0.00 | 17.75 | 0.00 | 17.75 |
March | 5.17 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
April | 1.33 | 19.29 | 0.00 | 19.29 | 1.50 | 24.24 | 1.50 | 25.76 |
May | 1.33 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
June | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.68 | 0.83 | 27.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.83 | 2.67 | 27.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.11 | 3.00 | 28.11 |
October | 2.83 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
November | 6.67 | 17.69 | 0.00 | 17.69 | 0.00 | 17.69 | 0.00 | 17.69 |
December | 15.00 | 16.67 | 1.00 | 16.56 | 0.00 | 16.56 | 0.00 | 16.56 |
Annual Sum or Average | 48.50 | 17.69 | 1.50 | 17.61 | 8.00 | 19.05 | 8.00 | 20.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 0.00 | 16.56 |
Maximum of Months | 15.00 | 19.40 | 1.00 | 19.40 | 3.00 | 28.11 | 3.00 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.67 | 18.13 | 0.00 | 18.13 | 0.00 | 18.13 | 0.00 | 18.13 |
February | 6.00 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
March | 4.17 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
April | 0.33 | 19.37 | 0.00 | 19.37 | 1.33 | 26.94 | 0.83 | 27.50 |
May | 0.83 | 19.27 | 0.00 | 19.27 | 1.83 | 25.39 | 1.00 | 26.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.68 | 0.83 | 28.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.52 | 2.17 | 28.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.27 | 2.00 | 28.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.46 | 0.67 | 27.46 |
October | 2.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
November | 4.17 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 |
December | 7.17 | 17.87 | 0.00 | 17.87 | 0.00 | 17.87 | 0.00 | 17.87 |
Annual Sum or Average | 31.33 | 18.39 | 0.00 | 18.39 | 13.67 | 21.44 | 7.50 | 22.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.87 | 0.00 | 17.87 |
Maximum of Months | 7.17 | 19.37 | 0.00 | 19.37 | 4.83 | 28.68 | 2.17 | 28.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.72 | 0.83 | 27.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.33 | 27.72 | 0.83 | 27.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.72 | 0.83 | 27.71 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 291.50 | 23.55 | 55.83 | 23.92 | 0.00 | 23.92 |
February | 186.50 | 23.69 | 31.00 | 23.96 | 0.00 | 23.96 |
March | 169.67 | 23.80 | 50.00 | 24.21 | 0.00 | 24.21 |
April | 152.67 | 23.71 | 92.33 | 24.53 | 0.00 | 24.53 |
May | 134.33 | 23.46 | 121.83 | 24.38 | 0.00 | 24.38 |
June | 14.50 | 23.37 | 218.50 | 24.67 | 0.00 | 24.67 |
July | 0.17 | 23.53 | 344.17 | 24.70 | 0.00 | 24.70 |
August | 0.17 | 23.19 | 362.67 | 24.55 | 0.00 | 24.55 |
September | 35.50 | 23.28 | 221.83 | 24.70 | 0.00 | 24.70 |
October | 30.50 | 23.57 | 127.50 | 25.29 | 0.00 | 25.29 |
November | 52.00 | 23.78 | 124.00 | 25.15 | 0.00 | 25.15 |
December | 181.17 | 23.68 | 77.17 | 24.32 | 0.00 | 24.32 |
Annual Sum or Average | 1248.67 | 23.63 | 1826.83 | 24.49 | 0.00 | 24.49 |
Minimum of Months | 0.17 | 23.19 | 31.00 | 23.92 | 0.00 | 23.92 |
Maximum of Months | 291.50 | 23.80 | 362.67 | 25.29 | 0.00 | 25.29 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 205.00 | 23.75 | 37.50 | 23.99 | 12.67 | 24.10 |
February | 155.33 | 23.58 | 5.67 | 23.64 | 0.00 | 23.64 |
March | 130.00 | 23.69 | 50.17 | 24.19 | 0.00 | 24.19 |
April | 27.83 | 23.78 | 98.83 | 25.16 | 0.00 | 25.16 |
May | 66.50 | 23.65 | 151.50 | 24.38 | 0.00 | 24.38 |
June | 0.17 | 23.44 | 318.33 | 24.36 | 0.00 | 24.36 |
July | 1.00 | 23.57 | 413.83 | 24.34 | 0.00 | 24.34 |
August | 0.00 | 0.00 | 449.67 | 24.29 | 0.00 | 24.29 |
September | 10.83 | 23.62 | 284.83 | 24.33 | 0.00 | 24.33 |
October | 58.83 | 23.63 | 183.83 | 24.52 | 0.00 | 24.52 |
November | 75.17 | 23.70 | 131.50 | 24.50 | 0.00 | 24.50 |
December | 141.33 | 23.69 | 53.33 | 24.18 | 0.00 | 24.18 |
Annual Sum or Average | 872.00 | 23.68 | 2179.00 | 24.31 | 12.67 | 24.32 |
Minimum of Months | 0.00 | 0.00 | 5.67 | 23.64 | 0.00 | 23.64 |
Maximum of Months | 205.00 | 23.78 | 449.67 | 25.16 | 12.67 | 25.16 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 388.83 | 23.20 | 12.00 | 23.16 | 12.00 | 23.12 |
February | 315.83 | 23.27 | 0.00 | 23.27 | 0.00 | 23.27 |
March | 310.17 | 23.45 | 0.00 | 23.45 | 0.00 | 23.45 |
April | 175.67 | 23.58 | 16.17 | 23.71 | 0.00 | 23.71 |
May | 155.83 | 23.45 | 74.67 | 23.75 | 0.00 | 23.75 |
June | 63.17 | 23.41 | 242.00 | 24.13 | 0.00 | 24.13 |
July | 62.67 | 23.31 | 271.67 | 24.13 | 0.00 | 24.13 |
August | 47.17 | 23.40 | 285.67 | 24.12 | 0.00 | 24.12 |
September | 104.83 | 23.37 | 173.67 | 23.96 | 0.00 | 23.96 |
October | 210.50 | 23.40 | 45.17 | 23.54 | 0.00 | 23.54 |
November | 282.67 | 23.32 | 11.00 | 23.35 | 0.00 | 23.35 |
December | 411.00 | 23.11 | 0.00 | 23.11 | 0.00 | 23.11 |
Annual Sum or Average | 2528.33 | 23.32 | 1132.00 | 23.62 | 12.00 | 23.61 |
Minimum of Months | 47.17 | 23.11 | 0.00 | 23.11 | 0.00 | 23.11 |
Maximum of Months | 411.00 | 23.58 | 285.67 | 24.13 | 12.00 | 24.13 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.50 | 21.24 | 141.67 | 20.88 | 141.67 | 20.65 |
February | 452.83 | 21.51 | 100.83 | 21.15 | 100.83 | 20.91 |
March | 509.83 | 22.05 | 56.17 | 21.87 | 56.17 | 21.72 |
April | 359.83 | 22.60 | 14.83 | 22.55 | 11.33 | 22.48 |
May | 325.00 | 22.64 | 51.33 | 22.83 | 0.00 | 22.83 |
June | 185.67 | 22.89 | 180.00 | 23.48 | 0.00 | 23.48 |
July | 165.67 | 22.77 | 236.83 | 23.60 | 0.00 | 23.60 |
August | 178.17 | 22.89 | 210.83 | 23.53 | 0.00 | 23.53 |
September | 289.17 | 22.60 | 86.33 | 22.92 | 0.00 | 22.92 |
October | 455.00 | 22.02 | 36.50 | 21.88 | 36.50 | 21.75 |
November | 478.00 | 21.63 | 83.33 | 21.35 | 83.33 | 21.14 |
December | 497.00 | 21.12 | 151.33 | 20.75 | 151.33 | 20.51 |
Annual Sum or Average | 4396.67 | 21.97 | 1350.00 | 22.02 | 581.17 | 21.81 |
Minimum of Months | 165.67 | 21.12 | 14.83 | 20.75 | 0.00 | 20.51 |
Maximum of Months | 509.83 | 22.89 | 236.83 | 23.60 | 151.33 | 23.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.83 | 43.67 | 21.75 | 43.67 | 21.67 |
February | 454.00 | 21.95 | 16.00 | 21.90 | 16.00 | 21.85 |
March | 483.67 | 22.53 | 0.00 | 22.53 | 0.00 | 22.53 |
April | 289.83 | 22.96 | 11.00 | 23.02 | 0.00 | 23.02 |
May | 287.00 | 22.96 | 54.33 | 23.14 | 0.00 | 23.14 |
June | 124.83 | 23.23 | 219.33 | 23.81 | 0.00 | 23.81 |
July | 72.17 | 23.32 | 294.00 | 24.02 | 0.00 | 24.02 |
August | 90.83 | 23.20 | 304.33 | 23.89 | 0.00 | 23.89 |
September | 247.33 | 22.90 | 102.67 | 23.24 | 0.00 | 23.24 |
October | 409.00 | 22.57 | 8.50 | 22.60 | 0.00 | 22.60 |
November | 468.50 | 22.30 | 2.17 | 22.29 | 2.17 | 22.28 |
December | 497.00 | 21.81 | 16.67 | 21.77 | 16.67 | 21.74 |
Annual Sum or Average | 3926.17 | 22.40 | 1072.67 | 22.72 | 78.50 | 22.68 |
Minimum of Months | 72.17 | 21.81 | 0.00 | 21.75 | 0.00 | 21.67 |
Maximum of Months | 502.00 | 23.32 | 304.33 | 24.02 | 43.67 | 24.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.50 | 21.36 | 52.50 | 21.30 | 51.00 | 21.25 |
February | 443.17 | 21.45 | 21.50 | 21.40 | 20.83 | 21.36 |
March | 507.83 | 21.71 | 6.17 | 21.71 | 4.67 | 21.70 |
April | 295.00 | 22.32 | 99.17 | 22.85 | 3.83 | 22.89 |
May | 299.17 | 22.26 | 137.83 | 22.94 | 3.67 | 22.98 |
June | 228.83 | 22.53 | 210.50 | 23.34 | 7.67 | 23.39 |
July | 177.83 | 22.75 | 272.00 | 23.68 | 11.33 | 23.76 |
August | 197.83 | 22.67 | 255.67 | 23.51 | 11.00 | 23.58 |
September | 249.33 | 22.23 | 190.17 | 23.12 | 7.00 | 23.17 |
October | 426.17 | 21.84 | 30.67 | 22.00 | 0.00 | 22.00 |
November | 484.50 | 21.54 | 14.00 | 21.53 | 12.83 | 21.51 |
December | 497.00 | 21.21 | 44.00 | 21.15 | 44.00 | 21.10 |
Annual Sum or Average | 4303.17 | 21.82 | 1334.17 | 22.31 | 177.83 | 22.31 |
Minimum of Months | 177.83 | 21.21 | 6.17 | 21.15 | 0.00 | 21.10 |
Maximum of Months | 507.83 | 22.75 | 272.00 | 23.68 | 51.00 | 23.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 434.33 | 21.36 | 109.83 | 21.55 | 63.50 | 21.45 |
February | 372.67 | 21.43 | 87.00 | 21.69 | 35.17 | 21.60 |
March | 479.00 | 21.71 | 26.17 | 21.71 | 17.67 | 21.67 |
April | 281.00 | 22.27 | 140.33 | 22.96 | 5.50 | 23.01 |
May | 336.50 | 22.08 | 120.50 | 22.66 | 0.00 | 22.66 |
June | 252.17 | 22.31 | 187.83 | 23.09 | 0.33 | 23.09 |
July | 205.50 | 22.54 | 234.17 | 23.44 | 8.83 | 23.50 |
August | 195.33 | 22.73 | 266.83 | 23.58 | 16.00 | 23.68 |
September | 245.00 | 22.40 | 219.00 | 23.31 | 14.83 | 23.42 |
October | 374.17 | 21.82 | 100.17 | 22.34 | 1.50 | 22.35 |
November | 422.33 | 21.52 | 65.50 | 21.77 | 23.33 | 21.73 |
December | 456.50 | 21.22 | 104.50 | 21.25 | 80.00 | 21.14 |
Annual Sum or Average | 4054.50 | 21.82 | 1661.83 | 22.39 | 266.67 | 22.36 |
Minimum of Months | 195.33 | 21.22 | 26.17 | 21.25 | 0.00 | 21.14 |
Maximum of Months | 479.00 | 22.73 | 266.83 | 23.58 | 80.00 | 23.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 483.33 | 21.59 | 19.50 | 21.62 | 12.67 | 21.60 |
February | 407.17 | 21.69 | 26.67 | 21.86 | 0.50 | 21.85 |
March | 454.67 | 22.11 | 27.17 | 22.25 | 0.00 | 22.25 |
April | 194.17 | 22.65 | 174.33 | 23.59 | 6.83 | 23.65 |
May | 306.17 | 22.43 | 145.17 | 23.06 | 6.67 | 23.12 |
June | 155.50 | 22.64 | 265.67 | 23.69 | 13.50 | 23.74 |
July | 96.83 | 23.25 | 357.33 | 24.16 | 20.67 | 24.25 |
August | 84.33 | 23.49 | 395.17 | 24.18 | 20.83 | 24.27 |
September | 260.00 | 22.33 | 158.00 | 23.06 | 7.50 | 23.12 |
October | 398.50 | 22.05 | 60.33 | 22.38 | 0.00 | 22.38 |
November | 444.00 | 21.99 | 16.00 | 22.09 | 0.00 | 22.09 |
December | 481.17 | 21.90 | 4.83 | 21.93 | 0.83 | 21.92 |
Annual Sum or Average | 3765.83 | 22.10 | 1650.17 | 22.79 | 90.00 | 22.84 |
Minimum of Months | 84.33 | 21.59 | 4.83 | 21.62 | 0.00 | 21.60 |
Maximum of Months | 483.33 | 23.49 | 395.17 | 24.18 | 20.83 | 24.27 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.79 | 229.33 | 20.60 | 229.33 | 20.49 |
February | 454.00 | 20.89 | 165.50 | 20.68 | 165.50 | 20.55 |
March | 514.00 | 21.49 | 88.00 | 21.35 | 88.00 | 21.25 |
April | 424.50 | 22.27 | 16.17 | 22.21 | 14.83 | 22.15 |
May | 406.17 | 22.33 | 37.17 | 22.44 | 3.50 | 22.43 |
June | 243.00 | 22.71 | 131.67 | 23.19 | 0.00 | 23.19 |
July | 222.67 | 22.77 | 189.50 | 23.36 | 0.00 | 23.36 |
August | 270.67 | 22.73 | 154.67 | 23.19 | 0.00 | 23.19 |
September | 353.33 | 22.26 | 53.83 | 22.49 | 0.00 | 22.49 |
October | 493.00 | 21.67 | 29.83 | 21.58 | 29.83 | 21.50 |
November | 489.00 | 21.03 | 138.17 | 20.83 | 138.17 | 20.71 |
December | 497.00 | 20.52 | 258.83 | 20.33 | 258.83 | 20.24 |
Annual Sum or Average | 4869.33 | 21.62 | 1492.67 | 21.62 | 928.00 | 21.43 |
Minimum of Months | 222.67 | 20.52 | 16.17 | 20.33 | 0.00 | 20.24 |
Maximum of Months | 514.00 | 22.77 | 258.83 | 23.36 | 258.83 | 23.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.75 | 186.33 | 20.59 | 186.33 | 20.50 |
February | 384.83 | 20.91 | 131.50 | 20.74 | 131.50 | 20.64 |
March | 432.83 | 21.23 | 81.17 | 21.13 | 81.17 | 21.06 |
April | 295.33 | 22.00 | 67.67 | 22.37 | 11.17 | 22.38 |
May | 298.50 | 21.94 | 92.17 | 22.50 | 5.67 | 22.52 |
June | 236.17 | 22.16 | 144.00 | 22.98 | 6.50 | 23.04 |
July | 207.83 | 22.40 | 187.17 | 23.39 | 10.83 | 23.48 |
August | 227.67 | 22.27 | 169.33 | 23.10 | 9.00 | 23.18 |
September | 248.67 | 21.86 | 122.67 | 22.68 | 4.67 | 22.71 |
October | 399.00 | 21.41 | 36.00 | 21.42 | 24.17 | 21.36 |
November | 417.00 | 20.89 | 111.00 | 20.75 | 111.00 | 20.66 |
December | 422.00 | 20.45 | 241.50 | 20.28 | 241.50 | 20.21 |
Annual Sum or Average | 3996.83 | 21.37 | 1570.50 | 21.63 | 823.50 | 21.48 |
Minimum of Months | 207.83 | 20.45 | 36.00 | 20.28 | 4.67 | 20.21 |
Maximum of Months | 432.83 | 22.40 | 241.50 | 23.39 | 241.50 | 23.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 440.67 | 21.13 | 173.33 | 21.22 | 131.33 | 21.09 |
February | 376.33 | 21.21 | 136.67 | 21.42 | 83.83 | 21.27 |
March | 488.33 | 21.41 | 78.00 | 21.35 | 70.17 | 21.27 |
April | 300.50 | 21.93 | 145.67 | 22.64 | 15.83 | 22.65 |
May | 356.00 | 21.79 | 122.00 | 22.37 | 6.67 | 22.35 |
June | 290.83 | 21.99 | 157.33 | 22.75 | 0.33 | 22.75 |
July | 258.50 | 22.16 | 197.50 | 23.08 | 5.50 | 23.12 |
August | 262.00 | 22.39 | 226.67 | 23.23 | 14.50 | 23.33 |
September | 261.33 | 22.17 | 213.83 | 23.15 | 17.83 | 23.27 |
October | 383.00 | 21.55 | 110.33 | 22.04 | 18.17 | 22.03 |
November | 432.83 | 21.18 | 110.17 | 21.31 | 74.00 | 21.22 |
December | 469.33 | 20.86 | 215.83 | 20.75 | 198.33 | 20.62 |
Annual Sum or Average | 4319.67 | 21.55 | 1887.33 | 22.01 | 636.50 | 21.90 |
Minimum of Months | 258.50 | 20.86 | 78.00 | 20.75 | 0.33 | 20.62 |
Maximum of Months | 488.33 | 22.39 | 226.67 | 23.23 | 198.33 | 23.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.33 | 20.85 | 182.00 | 20.71 | 182.00 | 20.62 |
February | 435.67 | 20.97 | 119.33 | 20.85 | 113.83 | 20.74 |
March | 505.00 | 21.18 | 69.33 | 21.13 | 66.33 | 21.08 |
April | 393.50 | 21.90 | 75.83 | 22.22 | 10.83 | 22.23 |
May | 389.83 | 21.82 | 94.33 | 22.29 | 6.67 | 22.33 |
June | 298.83 | 22.12 | 149.33 | 22.83 | 8.17 | 22.89 |
July | 259.00 | 22.20 | 185.83 | 23.08 | 12.17 | 23.17 |
August | 308.17 | 22.26 | 158.00 | 22.90 | 10.67 | 22.98 |
September | 367.50 | 21.78 | 93.67 | 22.28 | 3.33 | 22.31 |
October | 467.33 | 21.34 | 40.33 | 21.42 | 17.83 | 21.37 |
November | 485.67 | 20.96 | 98.00 | 20.83 | 98.00 | 20.74 |
December | 497.00 | 20.61 | 236.00 | 20.46 | 236.00 | 20.38 |
Annual Sum or Average | 4907.83 | 21.40 | 1502.00 | 21.61 | 765.83 | 21.51 |
Minimum of Months | 259.00 | 20.61 | 40.33 | 20.46 | 3.33 | 20.38 |
Maximum of Months | 505.00 | 22.26 | 236.00 | 23.08 | 236.00 | 23.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.10 | 376.83 | 19.97 | 376.83 | 19.91 |
February | 454.00 | 20.16 | 295.00 | 19.97 | 295.00 | 19.89 |
March | 514.00 | 20.66 | 260.17 | 20.48 | 260.17 | 20.40 |
April | 461.83 | 21.47 | 114.50 | 21.25 | 112.33 | 21.09 |
May | 452.17 | 21.55 | 101.83 | 21.51 | 70.33 | 21.36 |
June | 330.00 | 22.07 | 106.17 | 22.51 | 3.17 | 22.50 |
July | 286.17 | 22.05 | 157.50 | 22.69 | 6.83 | 22.65 |
August | 342.17 | 22.06 | 112.67 | 22.51 | 2.50 | 22.50 |
September | 421.50 | 21.57 | 68.00 | 21.54 | 44.00 | 21.41 |
October | 502.00 | 20.69 | 184.83 | 20.42 | 184.83 | 20.27 |
November | 489.00 | 20.22 | 287.50 | 20.01 | 287.50 | 19.91 |
December | 497.00 | 19.95 | 410.17 | 19.85 | 410.17 | 19.81 |
Annual Sum or Average | 5251.83 | 20.94 | 2475.17 | 20.81 | 2053.67 | 20.60 |
Minimum of Months | 286.17 | 19.95 | 68.00 | 19.85 | 2.50 | 19.81 |
Maximum of Months | 514.00 | 22.07 | 410.17 | 22.69 | 410.17 | 22.65 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.17 | 352.67 | 20.02 | 352.67 | 19.96 |
February | 454.00 | 20.31 | 269.50 | 20.11 | 269.50 | 20.02 |
March | 514.00 | 20.67 | 242.33 | 20.51 | 242.33 | 20.43 |
April | 355.17 | 21.64 | 131.17 | 21.82 | 66.67 | 21.67 |
May | 356.33 | 21.60 | 138.83 | 22.04 | 36.67 | 21.92 |
June | 273.17 | 21.86 | 181.83 | 22.77 | 5.83 | 22.79 |
July | 222.83 | 22.11 | 245.83 | 23.24 | 14.00 | 23.28 |
August | 242.17 | 21.94 | 233.33 | 22.99 | 4.83 | 23.01 |
September | 283.00 | 21.53 | 162.33 | 22.34 | 19.67 | 22.25 |
October | 486.33 | 20.83 | 154.00 | 20.58 | 151.00 | 20.41 |
November | 489.00 | 20.29 | 255.67 | 20.07 | 255.67 | 19.96 |
December | 497.00 | 19.98 | 388.17 | 19.86 | 388.17 | 19.81 |
Annual Sum or Average | 4675.00 | 20.89 | 2755.67 | 21.06 | 1807.00 | 20.84 |
Minimum of Months | 222.83 | 19.98 | 131.17 | 19.86 | 4.83 | 19.81 |
Maximum of Months | 514.00 | 22.11 | 388.17 | 23.24 | 388.17 | 23.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 468.17 | 20.48 | 297.33 | 20.35 | 280.00 | 20.23 |
February | 406.00 | 20.68 | 238.83 | 20.62 | 205.83 | 20.45 |
March | 499.00 | 20.83 | 224.67 | 20.64 | 223.67 | 20.54 |
April | 337.00 | 21.53 | 190.67 | 21.93 | 84.50 | 21.78 |
May | 373.83 | 21.34 | 169.67 | 21.76 | 65.00 | 21.59 |
June | 313.83 | 21.69 | 152.17 | 22.42 | 7.33 | 22.40 |
July | 278.50 | 21.84 | 198.00 | 22.75 | 16.33 | 22.74 |
August | 283.17 | 22.01 | 213.17 | 22.94 | 13.67 | 23.02 |
September | 278.67 | 21.66 | 220.17 | 22.61 | 39.17 | 22.57 |
October | 410.33 | 20.91 | 197.67 | 21.10 | 123.83 | 20.89 |
November | 457.17 | 20.59 | 224.17 | 20.44 | 204.33 | 20.28 |
December | 483.00 | 20.26 | 342.67 | 20.11 | 336.33 | 20.02 |
Annual Sum or Average | 4588.67 | 21.04 | 2669.17 | 21.29 | 1600.00 | 21.08 |
Minimum of Months | 278.50 | 20.26 | 152.17 | 20.11 | 7.33 | 20.02 |
Maximum of Months | 499.00 | 22.01 | 342.67 | 22.94 | 336.33 | 23.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.33 | 315.00 | 20.15 | 315.00 | 20.08 |
February | 443.50 | 20.53 | 233.33 | 20.31 | 231.17 | 20.20 |
March | 507.83 | 20.79 | 205.17 | 20.66 | 203.17 | 20.58 |
April | 398.00 | 21.44 | 139.00 | 21.66 | 74.83 | 21.55 |
May | 395.33 | 21.41 | 136.00 | 21.80 | 51.50 | 21.71 |
June | 324.83 | 21.88 | 142.33 | 22.57 | 14.83 | 22.64 |
July | 291.83 | 22.02 | 176.00 | 22.84 | 18.00 | 22.92 |
August | 335.50 | 22.00 | 154.17 | 22.67 | 12.17 | 22.76 |
September | 377.50 | 21.45 | 114.67 | 21.87 | 28.67 | 21.81 |
October | 474.00 | 20.86 | 150.67 | 20.77 | 131.67 | 20.63 |
November | 489.00 | 20.50 | 226.50 | 20.28 | 226.50 | 20.16 |
December | 497.00 | 20.12 | 363.67 | 19.98 | 363.67 | 19.93 |
Annual Sum or Average | 5036.33 | 21.00 | 2356.50 | 21.09 | 1671.17 | 20.92 |
Minimum of Months | 291.83 | 20.12 | 114.67 | 19.98 | 12.17 | 19.93 |
Maximum of Months | 507.83 | 22.02 | 363.67 | 22.84 | 363.67 | 22.92 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 27.00 | 502.00 | 27.00 | 1.00 | 27.00 |
February | 9.83 | 27.00 | 454.00 | 27.00 | 9.83 | 27.00 |
March | 4.00 | 27.00 | 514.00 | 27.00 | 4.00 | 27.00 |
April | 90.50 | 27.00 | 485.00 | 27.00 | 90.50 | 27.00 |
May | 31.50 | 27.00 | 508.00 | 27.00 | 31.50 | 27.00 |
June | 105.83 | 27.00 | 496.00 | 27.00 | 105.83 | 27.00 |
July | 216.83 | 27.00 | 497.00 | 27.00 | 216.83 | 27.00 |
August | 268.17 | 27.00 | 514.00 | 27.00 | 268.17 | 27.00 |
September | 50.67 | 27.00 | 485.00 | 27.00 | 50.67 | 27.00 |
October | 16.67 | 27.00 | 502.00 | 27.00 | 16.67 | 27.00 |
November | 6.67 | 27.00 | 489.00 | 27.00 | 6.67 | 27.00 |
December | 1.33 | 27.00 | 497.00 | 27.00 | 1.33 | 27.00 |
Annual Sum or Average | 803.00 | 27.00 | 5943.00 | 27.00 | 803.00 | 27.00 |
Minimum of Months | 1.00 | 27.00 | 454.00 | 27.00 | 1.00 | 27.00 |
Maximum of Months | 268.17 | 27.00 | 514.00 | 27.00 | 268.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 493.17 | 27.00 | 0.00 | 27.00 |
February | 1.17 | 27.00 | 454.00 | 27.00 | 1.17 | 27.00 |
March | 0.67 | 27.00 | 514.00 | 27.00 | 0.67 | 27.00 |
April | 25.33 | 27.00 | 485.00 | 27.00 | 25.33 | 27.00 |
May | 18.00 | 27.00 | 508.00 | 27.00 | 18.00 | 27.00 |
June | 49.83 | 27.00 | 496.00 | 27.00 | 49.83 | 27.00 |
July | 78.00 | 27.00 | 497.00 | 27.00 | 78.00 | 27.00 |
August | 75.50 | 27.00 | 514.00 | 27.00 | 75.50 | 27.00 |
September | 22.17 | 27.00 | 485.00 | 27.00 | 22.17 | 27.00 |
October | 5.83 | 27.00 | 502.00 | 27.00 | 5.83 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 487.67 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 276.50 | 27.00 | 5924.83 | 27.00 | 276.50 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 78.00 | 27.00 | 514.00 | 27.00 | 78.00 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 61.33 | 25.78 | 355.33 | 26.82 | 0.00 | 26.82 |
February | 21.00 | 27.00 | 352.17 | 27.00 | 0.00 | 27.00 |
March | 3.17 | 27.00 | 461.50 | 27.00 | 0.00 | 27.00 |
April | 31.83 | 27.00 | 471.67 | 27.00 | 31.83 | 27.00 |
May | 28.50 | 27.00 | 505.00 | 27.00 | 28.50 | 27.00 |
June | 70.67 | 27.00 | 496.00 | 27.00 | 70.67 | 27.00 |
July | 106.67 | 27.00 | 497.00 | 27.00 | 106.67 | 27.00 |
August | 99.50 | 27.00 | 514.00 | 27.00 | 99.50 | 27.00 |
September | 32.33 | 27.00 | 485.00 | 27.00 | 32.33 | 27.00 |
October | 3.67 | 27.00 | 460.17 | 27.00 | 3.67 | 27.00 |
November | 5.17 | 27.00 | 411.50 | 27.00 | 0.00 | 27.00 |
December | 25.17 | 27.00 | 371.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 489.00 | 26.85 | 5380.50 | 26.99 | 373.17 | 26.99 |
Minimum of Months | 3.17 | 25.78 | 352.17 | 26.82 | 0.00 | 26.82 |
Maximum of Months | 106.67 | 27.00 | 514.00 | 27.00 | 106.67 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 252.83 | 27.08 | 502.00 | 27.08 | 252.83 | 27.08 |
February | 27.17 | 26.97 | 450.33 | 24.84 | 26.83 | 24.95 |
March | 222.17 | 25.84 | 477.17 | 25.55 | 221.17 | 25.62 |
April | 259.33 | 25.71 | 485.00 | 25.02 | 259.33 | 25.20 |
May | 332.17 | 27.03 | 508.00 | 27.03 | 332.17 | 27.03 |
June | 166.50 | 26.87 | 492.17 | 25.82 | 166.50 | 26.03 |
July | 461.50 | 26.11 | 494.83 | 26.04 | 461.50 | 26.06 |
August | 429.00 | 26.37 | 514.00 | 26.07 | 429.00 | 26.17 |
September | 459.50 | 27.01 | 485.00 | 27.01 | 459.50 | 27.01 |
October | 104.33 | 26.98 | 494.83 | 25.46 | 104.33 | 25.68 |
November | 300.00 | 25.84 | 458.00 | 25.54 | 299.83 | 25.62 |
December | 259.67 | 25.57 | 497.00 | 24.93 | 259.67 | 25.10 |
Annual Sum or Average | 3274.17 | 26.40 | 5858.33 | 25.95 | 3272.67 | 26.07 |
Minimum of Months | 27.17 | 25.57 | 450.33 | 24.84 | 26.83 | 24.95 |
Maximum of Months | 461.50 | 27.08 | 514.00 | 27.08 | 461.50 | 27.08 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 28.40459 | 0.79119 | 18.33216 |
February | 454.00000 | 27.00000 | 27.84087 | 0.81503 | 19.16517 |
March | 514.00000 | 27.00000 | 27.77352 | 0.85678 | 20.60846 |
April | 485.00000 | 27.00000 | 28.39590 | 0.95091 | 24.22969 |
May | 508.00000 | 27.00002 | 33.54333 | 0.23028 | 6.34699 |
June | 496.00000 | 27.00003 | 37.21587 | 0.32863 | 7.43706 |
July | 497.00000 | 27.00000 | 37.52474 | 0.39137 | 8.37427 |
August | 514.00000 | 27.00017 | 36.75947 | 0.42561 | 8.92843 |
September | 485.00000 | 27.00009 | 37.40823 | 0.26741 | 6.70305 |
October | 502.00000 | 27.00001 | 33.08657 | 0.88852 | 21.78271 |
November | 489.00000 | 27.00000 | 30.80493 | 0.87595 | 21.31922 |
December | 497.00000 | 27.00000 | 26.70345 | 0.85068 | 20.36729 |
Annual Sum or Average | 5943.00000 | 27.00003 | 32.15167 | 0.63754 | 15.25252 |
Minimum of Months | 454.00000 | 27.00000 | 26.70345 | 0.23028 | 6.34699 |
Maximum of Months | 514.00000 | 27.00017 | 37.52474 | 0.95091 | 24.22969 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 28.37995 | 0.70572 | 15.64567 |
February | 454.00000 | 27.00000 | 27.83403 | 0.73467 | 16.57907 |
March | 514.00000 | 27.00000 | 27.76807 | 0.76270 | 17.39805 |
April | 485.00000 | 27.00000 | 28.39141 | 0.84829 | 20.38329 |
May | 508.00000 | 27.00002 | 33.52533 | 0.14545 | 5.76854 |
June | 496.00000 | 27.00004 | 37.22704 | 0.24097 | 6.46964 |
July | 497.00000 | 27.00001 | 37.53997 | 0.27175 | 6.81926 |
August | 514.00000 | 27.00018 | 36.83418 | 0.28413 | 6.92829 |
September | 485.00000 | 27.00009 | 37.44575 | 0.17954 | 5.95446 |
October | 502.00000 | 27.00001 | 33.08338 | 0.81036 | 19.00089 |
November | 489.00000 | 27.00000 | 30.79691 | 0.76947 | 17.64805 |
December | 497.00000 | 27.00000 | 26.69504 | 0.71365 | 15.87184 |
Annual Sum or Average | 5943.00000 | 27.00003 | 32.15679 | 0.53687 | 12.82917 |
Minimum of Months | 454.00000 | 27.00000 | 26.69504 | 0.14545 | 5.76854 |
Maximum of Months | 514.00000 | 27.00018 | 37.53997 | 0.84829 | 20.38329 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.84951 | 28.67748 | 0.57357 | 12.59241 |
February | 454.00000 | 27.00020 | 27.83838 | 0.63539 | 13.88285 |
March | 514.00000 | 27.00000 | 27.77179 | 0.67565 | 14.87003 |
April | 485.00000 | 27.00000 | 28.39516 | 0.79214 | 18.66940 |
May | 508.00000 | 27.00051 | 33.53762 | 0.08555 | 5.86562 |
June | 496.00000 | 27.00004 | 37.23841 | 0.21120 | 6.49273 |
July | 497.00000 | 27.00001 | 37.54904 | 0.24841 | 6.88519 |
August | 514.00000 | 27.00016 | 36.94772 | 0.25358 | 6.86472 |
September | 485.00000 | 27.00132 | 37.48376 | 0.11758 | 5.89533 |
October | 502.00000 | 27.00001 | 33.10417 | 0.72345 | 16.34045 |
November | 489.00000 | 27.00000 | 30.80923 | 0.66921 | 14.73372 |
December | 497.00000 | 27.00000 | 26.70462 | 0.60736 | 13.03794 |
Annual Sum or Average | 5943.00000 | 26.98747 | 32.20213 | 0.46428 | 11.31068 |
Minimum of Months | 454.00000 | 26.84951 | 26.70462 | 0.08555 | 5.86562 |
Maximum of Months | 514.00000 | 27.00132 | 37.54904 | 0.79214 | 18.66940 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.08139 | 30.07076 | 1.02350 | 27.14025 |
February | 454.00000 | 24.68073 | 32.48998 | 0.70943 | 15.93288 |
March | 514.00000 | 25.11917 | 30.80599 | 0.88197 | 22.42089 |
April | 485.00000 | 24.65992 | 30.42646 | 0.96960 | 25.73581 |
May | 508.00000 | 27.03320 | 30.99637 | 0.44329 | 9.18512 |
June | 496.00000 | 25.43006 | 37.84979 | 0.27312 | 8.23128 |
July | 497.00000 | 25.95805 | 38.62970 | 0.60693 | 13.91429 |
August | 514.00000 | 25.81984 | 39.79876 | 0.75250 | 19.89645 |
September | 485.00000 | 27.01186 | 34.74830 | 0.52266 | 10.81473 |
October | 502.00000 | 25.07836 | 34.06828 | 0.83843 | 20.61630 |
November | 489.00000 | 25.06414 | 32.36696 | 0.91623 | 23.90025 |
December | 497.00000 | 24.59694 | 30.13414 | 0.95390 | 24.98142 |
Annual Sum or Average | 5943.00000 | 25.63706 | 33.54729 | 0.74122 | 18.58532 |
Minimum of Months | 454.00000 | 24.59694 | 30.07076 | 0.27312 | 8.23128 |
Maximum of Months | 514.00000 | 27.08139 | 39.79876 | 1.02350 | 27.14025 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.05265 | 28.83823 | 0.29610 | 7.28075 |
February | 454.00000 | 24.08505 | 29.60695 | 0.30590 | 7.13439 |
March | 514.00000 | 24.13889 | 28.83128 | 0.31981 | 7.34641 |
April | 485.00000 | 24.21046 | 28.85950 | 0.34673 | 7.87464 |
May | 508.00000 | 24.11371 | 35.34074 | -0.5226 | 11.43041 |
June | 496.00000 | 24.20510 | 41.78764 | -0.4328 | 9.55960 |
July | 497.00000 | 24.45089 | 43.36862 | -0.3388 | 8.22360 |
August | 514.00000 | 24.33302 | 44.11147 | -0.3551 | 8.43429 |
September | 485.00000 | 24.25556 | 41.58229 | -0.4101 | 9.64152 |
October | 502.00000 | 24.27591 | 35.07107 | 0.40733 | 8.86455 |
November | 489.00000 | 24.33345 | 32.30331 | 0.39989 | 8.77809 |
December | 497.00000 | 24.17850 | 27.75958 | 0.32419 | 7.53541 |
Annual Sum or Average | 5943.00000 | 24.22001 | 34.83218 | 0.02546 | 8.51817 |
Minimum of Months | 454.00000 | 24.05265 | 27.75958 | -0.5226 | 7.13439 |
Maximum of Months | 514.00000 | 24.45089 | 44.11147 | 0.40733 | 11.43041 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.06080 | 31.91675 | 0.31857 | 7.85165 |
February | 454.00000 | 24.02771 | 30.41441 | 0.30287 | 7.10548 |
March | 514.00000 | 24.15169 | 29.52242 | 0.33760 | 7.59551 |
April | 485.00000 | 24.32207 | 28.96398 | 0.39488 | 8.51099 |
May | 508.00000 | 24.17303 | 35.36679 | -0.4806 | 10.25174 |
June | 496.00000 | 24.21272 | 43.15747 | -0.3921 | 8.58360 |
July | 497.00000 | 24.27454 | 45.05731 | -0.3455 | 7.90523 |
August | 514.00000 | 24.25491 | 45.38377 | -0.3347 | 7.70801 |
September | 485.00000 | 24.17861 | 42.52309 | -0.4144 | 8.95575 |
October | 502.00000 | 24.25107 | 36.23070 | 0.40890 | 8.74842 |
November | 489.00000 | 24.26704 | 33.30278 | 0.38843 | 8.42064 |
December | 497.00000 | 24.18467 | 28.81399 | 0.33178 | 7.54239 |
Annual Sum or Average | 5943.00000 | 24.19741 | 35.93517 | 0.04025 | 8.27142 |
Minimum of Months | 454.00000 | 24.02771 | 28.81399 | -0.4806 | 7.10548 |
Maximum of Months | 514.00000 | 24.32207 | 45.38377 | 0.40890 | 10.25174 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.39432 | 33.55344 | 0.13606 | 5.97410 |
February | 454.00000 | 23.50481 | 31.97763 | 0.16069 | 6.05012 |
March | 514.00000 | 23.70321 | 31.24672 | 0.21233 | 6.27954 |
April | 485.00000 | 23.99107 | 30.17456 | 0.29490 | 7.03045 |
May | 508.00000 | 23.95091 | 36.26253 | -0.5781 | 12.54015 |
June | 496.00000 | 24.04442 | 44.01329 | -0.4745 | 10.11017 |
July | 497.00000 | 24.05137 | 46.13404 | -0.4593 | 9.90090 |
August | 514.00000 | 24.02715 | 46.45468 | -0.4553 | 9.68581 |
September | 485.00000 | 23.94868 | 43.53033 | -0.5172 | 11.05543 |
October | 502.00000 | 23.84783 | 37.65444 | 0.29555 | 7.14209 |
November | 489.00000 | 23.64815 | 35.41557 | 0.21844 | 6.50307 |
December | 497.00000 | 23.26777 | 31.57705 | 0.08934 | 5.83438 |
Annual Sum or Average | 5943.00000 | 23.78354 | 37.37879 | -0.0924 | 8.19357 |
Minimum of Months | 454.00000 | 23.26777 | 30.17456 | -0.5781 | 5.83438 |
Maximum of Months | 514.00000 | 24.05137 | 46.45468 | 0.29555 | 12.54015 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.25321 | 35.64206 | -0.4193 | 11.62863 |
February | 454.00000 | 21.51666 | 36.06659 | -0.3436 | 10.31896 |
March | 514.00000 | 22.06532 | 35.05520 | -0.2058 | 7.64864 |
April | 485.00000 | 22.96737 | 32.47870 | 0.03795 | 6.68978 |
May | 508.00000 | 23.13876 | 38.25588 | -0.8645 | 23.31065 |
June | 496.00000 | 23.62888 | 45.23545 | -0.6165 | 14.49782 |
July | 497.00000 | 23.66702 | 47.42384 | -0.5838 | 13.83456 |
August | 514.00000 | 23.64115 | 47.79584 | -0.5902 | 13.62175 |
September | 485.00000 | 23.15961 | 46.32968 | -0.7992 | 20.78982 |
October | 502.00000 | 22.20380 | 42.03996 | -0.1199 | 7.21831 |
November | 489.00000 | 21.67784 | 39.79012 | -0.2814 | 9.06230 |
December | 497.00000 | 21.12021 | 35.26204 | -0.4584 | 12.24911 |
Annual Sum or Average | 5943.00000 | 22.51099 | 40.14826 | -0.4384 | 12.59201 |
Minimum of Months | 454.00000 | 21.12021 | 32.47870 | -0.8645 | 6.68978 |
Maximum of Months | 514.00000 | 23.66702 | 47.79584 | 0.03795 | 23.31065 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.83046 | 32.61367 | -0.2543 | 7.42358 |
February | 454.00000 | 21.94552 | 33.18284 | -0.2172 | 7.02978 |
March | 514.00000 | 22.61442 | 31.47837 | -0.0582 | 6.18600 |
April | 485.00000 | 23.41360 | 29.87882 | 0.15476 | 6.43372 |
May | 508.00000 | 23.42987 | 36.00299 | -0.7516 | 18.43664 |
June | 496.00000 | 23.85676 | 43.17422 | -0.5180 | 11.52121 |
July | 497.00000 | 23.99923 | 44.95402 | -0.4403 | 9.72922 |
August | 514.00000 | 23.90846 | 45.53938 | -0.4706 | 10.31286 |
September | 485.00000 | 23.43726 | 43.38088 | -0.6937 | 16.63973 |
October | 502.00000 | 22.83549 | 38.69344 | 0.04635 | 6.08568 |
November | 489.00000 | 22.36432 | 35.95156 | -0.0954 | 6.23429 |
December | 497.00000 | 21.81070 | 31.62620 | -0.2618 | 7.16364 |
Annual Sum or Average | 5943.00000 | 22.96147 | 37.24110 | -0.2979 | 9.45126 |
Minimum of Months | 454.00000 | 21.81070 | 29.87882 | -0.7516 | 6.08568 |
Maximum of Months | 514.00000 | 23.99923 | 45.53938 | 0.15476 | 18.43664 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.39397 | 32.53104 | -0.3307 | 8.16444 |
February | 454.00000 | 21.51101 | 33.06028 | -0.2872 | 7.67103 |
March | 514.00000 | 21.73978 | 32.01111 | -0.2214 | 6.92840 |
April | 485.00000 | 23.02565 | 29.96180 | 0.15161 | 7.79901 |
May | 508.00000 | 23.03179 | 36.23784 | -0.7575 | 21.46260 |
June | 496.00000 | 23.30663 | 44.18674 | -0.5790 | 15.68367 |
July | 497.00000 | 23.58422 | 45.86699 | -0.4580 | 12.90035 |
August | 514.00000 | 23.42842 | 46.51488 | -0.5005 | 13.73822 |
September | 485.00000 | 23.11354 | 43.70898 | -0.6662 | 18.95165 |
October | 502.00000 | 22.16638 | 39.43652 | -0.0559 | 6.60448 |
November | 489.00000 | 21.56760 | 36.67191 | -0.2467 | 6.96522 |
December | 497.00000 | 21.20681 | 31.72704 | -0.3866 | 8.58279 |
Annual Sum or Average | 5943.00000 | 22.42894 | 37.70015 | -0.3630 | 11.31728 |
Minimum of Months | 454.00000 | 21.20681 | 29.96180 | -0.7575 | 6.60448 |
Maximum of Months | 514.00000 | 23.58422 | 46.51488 | 0.15161 | 21.46260 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.77368 | 31.93412 | -0.2330 | 8.93593 |
February | 454.00000 | 21.94301 | 32.30031 | -0.1709 | 8.62593 |
March | 514.00000 | 21.85941 | 31.87315 | -0.1979 | 7.30421 |
April | 485.00000 | 23.04679 | 29.88412 | 0.15978 | 8.45788 |
May | 508.00000 | 22.77305 | 36.79054 | -0.8660 | 25.28136 |
June | 496.00000 | 23.13365 | 44.62798 | -0.6662 | 17.87872 |
July | 497.00000 | 23.41497 | 46.26356 | -0.5316 | 14.70439 |
August | 514.00000 | 23.49682 | 46.27612 | -0.4705 | 13.79977 |
September | 485.00000 | 23.22979 | 43.30559 | -0.5907 | 18.62151 |
October | 502.00000 | 22.41542 | 38.86693 | 0.02119 | 7.81204 |
November | 489.00000 | 21.91517 | 36.07133 | -0.1588 | 7.87259 |
December | 497.00000 | 21.48509 | 31.31876 | -0.3204 | 9.28459 |
Annual Sum or Average | 5943.00000 | 22.54369 | 37.50540 | -0.3379 | 12.41588 |
Minimum of Months | 454.00000 | 21.48509 | 29.88412 | -0.8660 | 7.30421 |
Maximum of Months | 514.00000 | 23.49682 | 46.27612 | 0.15978 | 25.28136 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.69064 | 31.83737 | -0.2235 | 7.09102 |
February | 454.00000 | 21.95053 | 32.09427 | -0.1376 | 6.86723 |
March | 514.00000 | 22.35837 | 30.72037 | -0.0295 | 6.28976 |
April | 485.00000 | 23.62483 | 28.78146 | 0.33440 | 9.23238 |
May | 508.00000 | 23.08399 | 35.99731 | -0.6937 | 19.43509 |
June | 496.00000 | 23.59878 | 43.27880 | -0.4197 | 12.15525 |
July | 497.00000 | 23.96128 | 44.68130 | -0.2527 | 9.58948 |
August | 514.00000 | 23.99677 | 44.85372 | -0.2369 | 8.86476 |
September | 485.00000 | 23.07608 | 43.61694 | -0.6423 | 17.73251 |
October | 502.00000 | 22.50871 | 38.52193 | 0.05994 | 6.61772 |
November | 489.00000 | 22.20260 | 35.21058 | -0.0538 | 6.25111 |
December | 497.00000 | 21.99019 | 30.22704 | -0.1447 | 6.30765 |
Annual Sum or Average | 5943.00000 | 22.84313 | 36.69019 | -0.2045 | 9.71338 |
Minimum of Months | 454.00000 | 21.69064 | 28.78146 | -0.6937 | 6.25111 |
Maximum of Months | 514.00000 | 23.99677 | 44.85372 | 0.33440 | 19.43509 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.78779 | 34.46982 | -0.5409 | 12.61073 |
February | 454.00000 | 20.89439 | 35.01836 | -0.4966 | 11.44900 |
March | 514.00000 | 21.48637 | 33.66535 | -0.3417 | 8.49061 |
April | 485.00000 | 22.48075 | 31.83372 | -0.0770 | 6.74388 |
May | 508.00000 | 22.66128 | 37.69972 | -1.0147 | 29.14726 |
June | 496.00000 | 23.36205 | 44.60668 | -0.6969 | 17.11555 |
July | 497.00000 | 23.45477 | 46.53761 | -0.6460 | 15.57613 |
August | 514.00000 | 23.30220 | 47.39862 | -0.7007 | 17.19306 |
September | 485.00000 | 22.71647 | 45.21455 | -0.9479 | 26.47045 |
October | 502.00000 | 21.71083 | 41.42904 | -0.2288 | 7.40019 |
November | 489.00000 | 21.02783 | 38.69739 | -0.4361 | 10.23063 |
December | 497.00000 | 20.52041 | 34.02862 | -0.6174 | 14.30678 |
Annual Sum or Average | 5943.00000 | 22.04276 | 39.25217 | -0.5632 | 14.75759 |
Minimum of Months | 454.00000 | 20.52041 | 31.83372 | -1.0147 | 6.74388 |
Maximum of Months | 514.00000 | 23.45477 | 47.39862 | -0.0770 | 29.14726 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.74928 | 33.39695 | -0.5413 | 12.30862 |
February | 385.00000 | 20.91050 | 33.81960 | -0.4781 | 10.87338 |
March | 433.00000 | 21.23291 | 33.00633 | -0.3828 | 8.90200 |
April | 410.00000 | 22.57630 | 30.81214 | 0.02278 | 7.85748 |
May | 430.00000 | 22.62140 | 36.90228 | -0.9178 | 27.80398 |
June | 418.00000 | 22.96594 | 44.86300 | -0.7090 | 20.51635 |
July | 422.00000 | 23.29885 | 46.40590 | -0.5805 | 17.26977 |
August | 433.00000 | 23.04779 | 47.28109 | -0.6556 | 18.78294 |
September | 410.00000 | 22.73353 | 44.35334 | -0.8238 | 24.69696 |
October | 427.00000 | 21.57818 | 40.67590 | -0.2290 | 7.67477 |
November | 417.00000 | 20.89465 | 37.84979 | -0.4567 | 10.26468 |
December | 422.00000 | 20.44909 | 33.12383 | -0.6314 | 14.59094 |
Annual Sum or Average | 5034.00000 | 21.92622 | 38.57719 | -0.5332 | 15.15916 |
Minimum of Months | 385.00000 | 20.44909 | 30.81214 | -0.9178 | 7.67477 |
Maximum of Months | 433.00000 | 23.29885 | 47.28109 | 0.02278 | 27.80398 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.52082 | 32.42410 | -0.3121 | 10.25025 |
February | 454.00000 | 21.74331 | 32.75201 | -0.2312 | 9.84878 |
March | 514.00000 | 21.53610 | 32.78761 | -0.2903 | 8.34590 |
April | 485.00000 | 22.78154 | 30.52849 | 0.09108 | 8.82807 |
May | 508.00000 | 22.49739 | 37.46539 | -0.9645 | 29.79529 |
June | 496.00000 | 22.81326 | 45.55398 | -0.7808 | 22.23142 |
July | 497.00000 | 23.07446 | 47.23217 | -0.6597 | 19.19039 |
August | 514.00000 | 23.14782 | 47.28415 | -0.5974 | 18.05742 |
September | 485.00000 | 23.04826 | 43.70376 | -0.6493 | 21.64369 |
October | 502.00000 | 22.15900 | 39.74111 | -0.0436 | 8.51312 |
November | 489.00000 | 21.54865 | 37.03494 | -0.2647 | 9.28823 |
December | 497.00000 | 21.04781 | 32.40052 | -0.4585 | 12.00843 |
Annual Sum or Average | 5943.00000 | 22.24530 | 38.29221 | -0.4329 | 14.88326 |
Minimum of Months | 454.00000 | 21.04781 | 30.52849 | -0.9645 | 8.34590 |
Maximum of Months | 514.00000 | 23.14782 | 47.28415 | 0.09108 | 29.79529 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.85384 | 33.51851 | -0.4974 | 11.24040 |
February | 454.00000 | 21.08987 | 33.84429 | -0.4096 | 10.17151 |
March | 514.00000 | 21.22860 | 33.20583 | -0.3619 | 8.55380 |
April | 485.00000 | 22.29813 | 31.33327 | -0.0301 | 7.72967 |
May | 508.00000 | 22.32891 | 37.76686 | -0.9932 | 31.10932 |
June | 496.00000 | 22.83790 | 45.42109 | -0.7192 | 21.13129 |
July | 497.00000 | 23.04234 | 47.26254 | -0.6260 | 18.83868 |
August | 514.00000 | 22.88368 | 48.05585 | -0.6877 | 19.77825 |
September | 485.00000 | 22.31568 | 45.62683 | -0.9477 | 28.89531 |
October | 502.00000 | 21.51497 | 41.13379 | -0.2250 | 7.49011 |
November | 489.00000 | 20.97587 | 38.00525 | -0.4190 | 9.60684 |
December | 497.00000 | 20.60967 | 33.04347 | -0.5789 | 12.94166 |
Annual Sum or Average | 5943.00000 | 21.83717 | 39.06209 | -0.5431 | 15.66946 |
Minimum of Months | 454.00000 | 20.60967 | 31.33327 | -0.9932 | 7.49011 |
Maximum of Months | 514.00000 | 23.04234 | 48.05585 | -0.0301 | 31.10932 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.09819 | 35.83387 | -0.7773 | 20.47579 |
February | 454.00000 | 20.15885 | 36.71399 | -0.7342 | 19.08176 |
March | 514.00000 | 20.66133 | 35.20110 | -0.5861 | 13.83033 |
April | 485.00000 | 21.59174 | 33.25659 | -0.3001 | 9.45939 |
May | 508.00000 | 21.80291 | 39.31549 | -1.3035 | 42.50769 |
June | 496.00000 | 22.68152 | 46.20864 | -0.9070 | 25.83957 |
July | 497.00000 | 22.85232 | 48.13161 | -0.8277 | 23.16083 |
August | 514.00000 | 22.65821 | 49.12631 | -0.9014 | 25.43347 |
September | 485.00000 | 21.85990 | 47.30837 | -1.2400 | 39.54118 |
October | 502.00000 | 20.69342 | 43.78990 | -0.5091 | 12.51404 |
November | 489.00000 | 20.22216 | 40.61567 | -0.6891 | 17.62627 |
December | 497.00000 | 19.94956 | 35.47667 | -0.8299 | 22.44782 |
Annual Sum or Average | 5943.00000 | 21.27829 | 40.94964 | -0.8015 | 22.69358 |
Minimum of Months | 454.00000 | 19.94956 | 33.25659 | -1.3035 | 9.45939 |
Maximum of Months | 514.00000 | 22.85232 | 49.12631 | -0.3001 | 42.50769 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.17034 | 35.28015 | -0.7423 | 19.10990 |
February | 454.00000 | 20.30575 | 36.02330 | -0.6764 | 16.99354 |
March | 514.00000 | 20.67261 | 34.77426 | -0.5647 | 13.08004 |
April | 485.00000 | 22.26100 | 31.62108 | -0.0691 | 8.97537 |
May | 508.00000 | 22.32788 | 37.87144 | -1.0322 | 32.69854 |
June | 496.00000 | 22.81673 | 45.53669 | -0.7585 | 22.84854 |
July | 497.00000 | 23.20036 | 46.96071 | -0.6065 | 18.59173 |
August | 514.00000 | 22.99451 | 47.78495 | -0.6714 | 19.82845 |
September | 485.00000 | 22.56099 | 45.12640 | -0.9062 | 28.09064 |
October | 502.00000 | 20.92341 | 42.94735 | -0.4239 | 11.37121 |
November | 489.00000 | 20.29341 | 40.08312 | -0.6589 | 16.43091 |
December | 497.00000 | 19.98187 | 35.05847 | -0.8107 | 21.72320 |
Annual Sum or Average | 5943.00000 | 21.55076 | 39.95824 | -0.6609 | 19.16936 |
Minimum of Months | 454.00000 | 19.98187 | 31.62108 | -1.0322 | 8.97537 |
Maximum of Months | 514.00000 | 23.20036 | 47.78495 | -0.0691 | 32.69854 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.72969 | 34.16187 | -0.5642 | 16.08463 |
February | 454.00000 | 21.04466 | 34.58334 | -0.4581 | 14.30534 |
March | 514.00000 | 20.91462 | 34.33323 | -0.4921 | 12.37522 |
April | 485.00000 | 22.29273 | 31.54408 | -0.0530 | 10.20104 |
May | 508.00000 | 22.06991 | 38.44312 | -1.1362 | 37.72141 |
June | 496.00000 | 22.51074 | 46.34124 | -0.8890 | 27.32896 |
July | 497.00000 | 22.81062 | 47.99238 | -0.7503 | 23.55398 |
August | 514.00000 | 22.86933 | 48.12294 | -0.6990 | 22.46387 |
September | 485.00000 | 22.69002 | 44.68773 | -0.8055 | 27.97912 |
October | 502.00000 | 21.49076 | 41.59074 | -0.2530 | 11.18712 |
November | 489.00000 | 20.83663 | 38.96541 | -0.4955 | 14.15560 |
December | 497.00000 | 20.36196 | 34.27140 | -0.6893 | 18.59779 |
Annual Sum or Average | 5943.00000 | 21.72190 | 39.63269 | -0.6096 | 19.72049 |
Minimum of Months | 454.00000 | 20.36196 | 31.54408 | -1.1362 | 10.20104 |
Maximum of Months | 514.00000 | 22.86933 | 48.12294 | -0.0530 | 37.72141 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.33020 | 34.79839 | -0.6819 | 17.27497 |
February | 454.00000 | 20.59964 | 35.32518 | -0.5798 | 15.07360 |
March | 514.00000 | 20.82860 | 34.31394 | -0.5068 | 11.82841 |
April | 485.00000 | 21.89860 | 32.18716 | -0.1483 | 9.34790 |
May | 508.00000 | 21.98612 | 38.56566 | -1.1314 | 38.01068 |
June | 496.00000 | 22.56491 | 46.13092 | -0.8139 | 25.59230 |
July | 497.00000 | 22.80730 | 47.94406 | -0.7043 | 22.68111 |
August | 514.00000 | 22.61620 | 48.85708 | -0.7809 | 24.06878 |
September | 485.00000 | 22.00440 | 46.47757 | -1.0814 | 35.24390 |
October | 502.00000 | 21.02610 | 42.52938 | -0.3867 | 10.40467 |
November | 489.00000 | 20.49782 | 39.47704 | -0.5889 | 14.44215 |
December | 497.00000 | 20.12090 | 34.62012 | -0.7549 | 19.49211 |
Annual Sum or Average | 5943.00000 | 21.44650 | 40.14293 | -0.6814 | 20.33355 |
Minimum of Months | 454.00000 | 20.12090 | 32.18716 | -1.1314 | 9.34790 |
Maximum of Months | 514.00000 | 22.80730 | 48.85708 | -0.1483 | 38.01068 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.225783E+10 | 107128.82 | 20-JAN-11:20 | 82.07 | 0.101341E+11 | 0.00 | 0.123919E+11 | 0.49 | 6.18 | 20-JAN-11:20 | 0.00 | 0.00 |
February | 0.349278E+11 | 122230.20 | 10-FEB-13:42 | 221.98 | 0.157738E+12 | 0.00 | 0.192666E+12 | 1.49 | 6.69 | 10-FEB-13:42 | 0.00 | 0.00 |
March | 0.555406E+11 | 119079.52 | 24-MAR-05:14 | 631.28 | 0.267550E+12 | 0.00 | 0.323091E+12 | 4.05 | 6.61 | 28-MAR-13:42 | 0.00 | 0.00 |
April | 0.638599E+11 | 194835.67 | 30-APR-14:43 | 598.83 | 0.318104E+12 | 0.00 | 0.381964E+12 | 4.00 | 7.07 | 30-APR-13:22 | 0.00 | 0.00 |
May | 0.200524E+11 | 199389.84 | 22-MAY-14:20 | 164.63 | 0.103957E+12 | 0.00 | 0.124010E+12 | 1.05 | 7.02 | 22-MAY-16:00 | 0.00 | 0.00 |
June | 0.759281E+11 | 205733.19 | 12-JUN-14:00 | 305.08 | 0.412723E+12 | 0.00 | 0.488651E+12 | 2.14 | 7.07 | 25-JUN-17:33 | 0.00 | 0.00 |
July | 0.115476E+12 | 210234.77 | 10-JUL-09:40 | 709.98 | 0.629912E+12 | 0.00 | 0.745388E+12 | 4.77 | 7.03 | 23-JUL-10:03 | 0.00 | 0.00 |
August | 0.139366E+12 | 209846.12 | 28-AUG-13:20 | 685.43 | 0.760711E+12 | 0.00 | 0.900077E+12 | 4.67 | 7.02 | 13-AUG-12:53 | 0.00 | 0.00 |
September | 0.519443E+11 | 204766.73 | 13-SEP-13:50 | 266.43 | 0.285589E+12 | 0.00 | 0.337534E+12 | 1.85 | 7.00 | 13-SEP-15:40 | 0.00 | 0.00 |
October | 0.404429E+11 | 133276.25 | 23-OCT-13:42 | 223.09 | 0.185823E+12 | 0.00 | 0.226266E+12 | 1.36 | 6.83 | 23-OCT-13:42 | 0.00 | 0.00 |
November | 0.539112E+11 | 117498.27 | 13-NOV-23:04 | 640.45 | 0.257565E+12 | 0.00 | 0.311476E+12 | 4.24 | 6.56 | 02-NOV-23:14 | 0.00 | 0.00 |
December | 0.485984E+11 | 110989.01 | 29-DEC-16:47 | 584.44 | 0.231229E+12 | 0.00 | 0.279827E+12 | 3.75 | 6.37 | 29-DEC-16:47 | 0.00 | 0.00 |
Annual Sum or Average | 0.702306E+12 | 5113.70 | 0.362104E+13 | 0.00 | 0.432334E+13 | 2.83 | 0.00 | 0.00 | ||||
Minimum of Months | 0.225783E+10 | 107128.82 | 82.07 | 0.101341E+11 | 0.00 | 0.123919E+11 | 0.49 | 6.18 | 0.00 | 0.00 | ||
Maximum of Months | 0.139366E+12 | 210234.77 | 709.98 | 0.760711E+12 | 0.00 | 0.900077E+12 | 4.77 | 7.07 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.302596E+09 | 124832.77 | 22-MAY-15:20 | 1.00 | 0.192829E+10 | 0.00 | 0.223088E+10 | 0.01 | 6.48 | 22-MAY-15:20 | 0.00 | 0.00 |
June | 0.326351E+10 | 142054.40 | 13-JUN-13:05 | 7.50 | 0.214191E+11 | 0.00 | 0.246826E+11 | 0.07 | 6.91 | 13-JUN-13:05 | 0.00 | 0.00 |
July | 0.560780E+10 | 139075.11 | 21-JUL-16:00 | 13.00 | 0.368809E+11 | 0.00 | 0.424887E+11 | 0.11 | 6.90 | 21-JUL-16:00 | 0.00 | 0.00 |
August | 0.408019E+10 | 140188.77 | 28-AUG-14:05 | 9.00 | 0.271297E+11 | 0.00 | 0.312099E+11 | 0.08 | 6.88 | 14-AUG-16:00 | 0.00 | 0.00 |
September | 0.495206E+09 | 129836.62 | 13-SEP-14:05 | 1.58 | 0.315529E+10 | 0.00 | 0.365049E+10 | 0.01 | 6.77 | 13-SEP-14:05 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.137493E+11 | 32.08 | 0.905132E+11 | 0.00 | 0.104263E+12 | 0.02 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.560780E+10 | 142054.40 | 13.00 | 0.368809E+11 | 0.00 | 0.424887E+11 | 0.11 | 6.91 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 40003.53 | 0.66 | 35.00 | 20-JAN-11:20 | 376858.85 | 20-JAN-11:20 | 21.06 | 21.03 | 3.00 |
February | 8006244.49 | 136.13 | 79.58 | 03-FEB-11:20 | 752121.00 | 24-FEB-13:18 | 21.87 | 21.58 | 23.12 |
March | 6255293.57 | 84.64 | 1588.66 | 25-MAR-12:56 | 780150.63 | 28-MAR-13:45 | 21.39 | 20.93 | 47.26 |
April | 0.433611E+09 | 170.72 | 9750.17 | 30-APR-15:03 | 1357450.26 | 30-APR-15:03 | 21.53 | 20.98 | 49.01 |
May | 0.612440E+09 | 67.30 | 22167.64 | 22-MAY-14:05 | 1527266.57 | 22-MAY-14:20 | 21.30 | 21.13 | 11.66 |
June | 0.368924E+10 | 285.96 | 22167.64 | 12-JUN-12:50 | 1601026.95 | 12-JUN-14:00 | 22.39 | 21.72 | 30.23 |
July | 0.547904E+10 | 437.95 | 22167.64 | 10-JUL-09:00 | 1620624.51 | 22-JUL-10:40 | 22.07 | 21.07 | 66.76 |
August | 0.626468E+10 | 589.64 | 22167.64 | 14-AUG-10:00 | 1603139.74 | 28-AUG-13:20 | 22.34 | 21.14 | 65.91 |
September | 0.244566E+10 | 190.47 | 22167.64 | 13-SEP-13:40 | 1548602.20 | 13-SEP-13:50 | 21.70 | 21.24 | 24.00 |
October | 0.150749E+09 | 204.24 | 5270.47 | 17-OCT-14:08 | 912447.35 | 17-OCT-14:08 | 22.06 | 21.76 | 21.44 |
November | 8185613.87 | 93.95 | 1641.83 | 10-NOV-15:08 | 831984.06 | 10-NOV-15:08 | 21.37 | 20.90 | 51.01 |
December | 3024603.65 | 75.09 | 62.32 | 05-DEC-03:10 | 550984.13 | 29-DEC-16:50 | 21.30 | 20.88 | 41.01 |
Annual Sum or Average | 0.191009E+11 | 2336.75 | 21.70 | 21.19 | 36.28 | ||||
Minimum of Months | 40003.53 | 0.66 | 35.00 | 376858.85 | 21.06 | 20.88 | 3.00 | ||
Maximum of Months | 0.626468E+10 | 589.64 | 22167.64 | 1620624.51 | 22.39 | 21.76 | 66.76 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 21.06 | 21.06 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 21.87 | 21.87 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 21.39 | 21.39 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.53 | 21.53 | 0.00 |
May | 21635288.57 | 0.33 | 20179.37 | 22-MAY-14:40 | 1314382.04 | 22-MAY-14:40 | 21.30 | 21.30 | 0.03 |
June | 0.462693E+09 | 5.83 | 22167.64 | 12-JUN-14:05 | 1292769.28 | 12-JUN-16:00 | 22.39 | 22.36 | 0.58 |
July | 0.595344E+09 | 8.42 | 22167.64 | 10-JUL-10:30 | 1380634.04 | 21-JUL-11:00 | 22.07 | 22.03 | 0.82 |
August | 0.449123E+09 | 7.25 | 22167.64 | 14-AUG-12:30 | 1463257.93 | 28-AUG-15:00 | 22.34 | 22.30 | 0.70 |
September | 68896020.12 | 0.92 | 22167.64 | 13-SEP-14:05 | 1326652.02 | 13-SEP-14:05 | 21.70 | 21.69 | 0.09 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 01-OCT-00:03 | 22.06 | 22.06 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 21.37 | 21.37 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 21.30 | 21.30 | 0.00 |
Annual Sum or Average | 0.159769E+10 | 22.75 | 21.70 | 21.69 | 0.19 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.06 | 21.06 | 0.00 | ||
Maximum of Months | 0.595344E+09 | 8.42 | 22167.64 | 1463257.93 | 22.39 | 22.36 | 0.82 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.221693E+12 | 0.00 | 464.58 | 1881259.63 | 10-JAN-05:01 | 0.00 | 28.38 | 55.17 | 0.49 | 0.00 | 0.04 | 0.82 | 10-JAN-05:01 |
February | 0.150851E+12 | 0.00 | 405.22 | 1735247.82 | 06-FEB-05:11 | 0.00 | 27.75 | 53.93 | 0.37 | 0.00 | 0.03 | 0.76 | 06-FEB-05:11 |
March | 0.115060E+12 | 0.00 | 396.86 | 1835058.79 | 13-MAR-04:11 | 0.00 | 25.34 | 48.74 | 0.25 | 0.00 | 0.02 | 0.80 | 13-MAR-04:11 |
April | 0.324701E+11 | 0.00 | 190.18 | 1467566.17 | 11-APR-05:01 | 0.00 | 25.71 | 36.78 | 0.07 | 0.00 | 0.01 | 0.64 | 11-APR-05:01 |
May | 0.282608E+11 | 0.00 | 188.91 | 1502785.47 | 05-MAY-04:11 | 0.00 | 25.84 | 36.11 | 0.06 | 0.00 | 0.00 | 0.66 | 05-MAY-04:11 |
June | 0.782891E+10 | 0.00 | 99.78 | 589535.54 | 08-JUN-05:01 | 0.00 | 22.81 | 28.74 | 0.02 | 0.00 | 0.00 | 0.26 | 08-JUN-05:01 |
July | 0.454003E+10 | 0.00 | 82.88 | 508260.06 | 31-JUL-05:01 | 0.00 | 21.22 | 26.13 | 0.01 | 0.00 | 0.00 | 0.22 | 31-JUL-05:01 |
August | 0.548958E+10 | 0.00 | 83.32 | 201985.21 | 23-AUG-05:03 | 0.00 | 21.61 | 26.51 | 0.01 | 0.00 | 0.00 | 0.09 | 23-AUG-05:03 |
September | 0.174596E+11 | 0.00 | 167.36 | 417937.47 | 20-SEP-05:03 | 0.00 | 22.62 | 32.51 | 0.04 | 0.00 | 0.00 | 0.18 | 20-SEP-05:03 |
October | 0.724245E+11 | 0.00 | 320.33 | 1500385.17 | 24-OCT-05:01 | 0.00 | 24.24 | 42.17 | 0.16 | 0.00 | 0.01 | 0.66 | 24-OCT-05:01 |
November | 0.140338E+12 | 0.00 | 408.10 | 1633885.29 | 13-NOV-05:11 | 0.00 | 26.30 | 50.45 | 0.33 | 0.00 | 0.02 | 0.71 | 13-NOV-05:11 |
December | 0.248183E+12 | 0.00 | 485.44 | 1686098.77 | 30-DEC-05:01 | 0.00 | 29.07 | 56.84 | 0.57 | 0.00 | 0.04 | 0.74 | 30-DEC-05:01 |
Annual Sum or Average | 0.104460E+13 | 0.00 | 3292.96 | 0.00 | 25.06 | 41.11 | 0.20 | 0.00 | 0.01 | ||||
Minimum of Months | 0.454003E+10 | 0.00 | 82.88 | 201985.21 | 0.00 | 21.22 | 26.13 | 0.01 | 0.00 | 0.00 | 0.09 | ||
Maximum of Months | 0.248183E+12 | 0.00 | 485.44 | 1881259.63 | 0.00 | 29.07 | 56.84 | 0.57 | 0.00 | 0.04 | 0.82 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 489120.82 | 0.00 | 2.26 | 489120.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1613.85 | 09-JAN-17:05 | 1613.85 | 09-JAN-17:05 | 0.00 | 0.00 | 0.00 |
February | 745.66 | 0.00 | 0.46 | 745.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 17-FEB-10:41 | 0.67 | 17-FEB-10:41 | 0.00 | 0.00 | 0.00 |
March | 5033.00 | 0.00 | 2.95 | 5033.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.30 | 27-MAR-05:01 | 1.30 | 27-MAR-05:01 | 0.00 | 0.00 | 0.00 |
April | 0.535845E+10 | 0.00 | 58.18 | 0.535153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 122486.09 | 30-APR-15:11 | 122486.09 | 30-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.657405E+10 | 0.00 | 72.19 | 0.657405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113161.71 | 22-MAY-15:00 | 113161.71 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.210645E+11 | 0.00 | 181.82 | 0.205997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 136227.95 | 13-JUN-15:50 | 130217.68 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.358732E+11 | 0.00 | 311.11 | 0.358153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 137152.16 | 21-JUL-16:00 | 137152.16 | 21-JUL-16:00 | 0.00 | 0.00 | 0.00 |
August | 0.468549E+11 | 0.00 | 382.03 | 0.464643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 139284.01 | 14-AUG-14:20 | 137478.20 | 14-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.229010E+11 | 0.00 | 227.63 | 0.228925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 101803.20 | 13-SEP-14:20 | 101803.20 | 13-SEP-14:20 | 0.00 | 0.00 | 0.00 |
October | 0.129202E+10 | 0.00 | 26.96 | 0.129202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28541.09 | 11-OCT-14:53 | 28541.09 | 11-OCT-14:53 | 0.00 | 0.00 | 0.00 |
November | 24426849.15 | 0.00 | 1.75 | 24426849.15 | 0.00 | 0.00 | 0.00 | 0.00 | 11958.08 | 24-NOV-11:51 | 11958.08 | 24-NOV-11:51 | 0.00 | 0.00 | 0.00 |
December | 594.32 | 0.00 | 0.35 | 594.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 | 20-DEC-10:10 | 0.69 | 20-DEC-10:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139943E+12 | 0.00 | 1267.69 | 0.139014E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 594.32 | 0.00 | 0.35 | 594.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 0.67 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.468549E+11 | 0.00 | 382.03 | 0.464643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 139284.01 | 137478.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.552151E+09 | 0.00 | 55.14 | 0.552151E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 222669.84 | 20-JAN-11:02 | 222669.84 | 20-JAN-11:02 | 0.00 | 0.00 | 0.00 |
February | 0.161644E+10 | 0.00 | 67.70 | 0.161644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 175627.25 | 24-FEB-13:02 | 175627.25 | 24-FEB-13:02 | 0.00 | 0.00 | 0.00 |
March | 0.984359E+10 | 0.00 | 80.72 | 0.984359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 417693.10 | 30-MAR-14:01 | 417693.10 | 30-MAR-14:01 | 0.00 | 0.00 | 0.00 |
April | 0.549628E+11 | 0.00 | 81.94 | 0.549111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1050487.44 | 30-APR-16:02 | 1050487.44 | 30-APR-16:02 | 0.00 | 0.00 | 0.00 |
May | 0.727889E+11 | 0.00 | 94.68 | 0.727889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1009017.37 | 22-MAY-15:00 | 1009017.37 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.202436E+12 | 0.00 | 201.20 | 0.198411E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1265713.81 | 13-JUN-16:00 | 1208988.29 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.303396E+12 | 0.00 | 312.16 | 0.303072E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1254687.21 | 21-JUL-16:00 | 1254687.21 | 21-JUL-16:00 | 0.00 | 0.00 | 0.00 |
August | 0.388491E+12 | 0.00 | 383.57 | 0.386159E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1146597.19 | 14-AUG-16:00 | 1146597.19 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.212046E+12 | 0.00 | 242.90 | 0.211927E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 979415.88 | 13-SEP-14:05 | 979415.88 | 13-SEP-14:05 | 0.00 | 0.00 | 0.00 |
October | 0.199767E+11 | 0.00 | 48.62 | 0.199767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 639134.52 | 11-OCT-13:01 | 639134.52 | 11-OCT-13:01 | 0.00 | 0.00 | 0.00 |
November | 0.246218E+10 | 0.00 | 47.81 | 0.246218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 449245.85 | 10-NOV-15:01 | 449245.85 | 10-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 234925.59 | 0.00 | 86.09 | 234925.59 | 0.00 | 0.00 | 0.00 | 0.00 | 4.99 | 04-DEC-18:30 | 4.99 | 04-DEC-18:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126857E+13 | 0.00 | 1702.55 | 0.126172E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 234925.59 | 0.00 | 47.81 | 234925.59 | 0.00 | 0.00 | 0.00 | 0.00 | 4.99 | 4.99 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.388491E+12 | 0.00 | 383.57 | 0.386159E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1265713.81 | 1254687.21 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2220729.24 | 0.00 | 1.73 | 2220729.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2525.05 | 22-JAN-09:30 | 2525.05 | 22-JAN-09:30 | 0.00 | 0.00 | 0.00 |
February | 171750.72 | 0.00 | 0.65 | 171750.72 | 0.00 | 0.00 | 0.00 | 0.00 | 570.98 | 19-FEB-02:10 | 570.98 | 19-FEB-02:10 | 0.00 | 0.00 | 0.00 |
March | 2789.31 | 0.00 | 0.58 | 2789.31 | 0.00 | 0.00 | 0.00 | 0.00 | 23.30 | 04-MAR-15:51 | 23.30 | 04-MAR-15:51 | 0.00 | 0.00 | 0.00 |
April | 0.494577E+10 | 0.00 | 53.89 | 0.494365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 131928.50 | 30-APR-16:02 | 131928.50 | 30-APR-16:02 | 0.00 | 0.00 | 0.00 |
May | 0.635594E+10 | 0.00 | 70.10 | 0.635594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 135196.14 | 22-MAY-15:00 | 135196.14 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.207651E+11 | 0.00 | 173.11 | 0.203351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167000.05 | 13-JUN-14:40 | 159366.82 | 13-JUN-15:40 | 0.00 | 0.00 | 0.00 |
July | 0.327083E+11 | 0.00 | 293.69 | 0.326839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160593.54 | 21-JUL-16:00 | 160593.54 | 21-JUL-16:00 | 0.00 | 0.00 | 0.00 |
August | 0.384895E+11 | 0.00 | 373.02 | 0.383880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143072.46 | 14-AUG-15:50 | 143072.46 | 14-AUG-15:50 | 0.00 | 0.00 | 0.00 |
September | 0.193013E+11 | 0.00 | 213.95 | 0.192968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102429.28 | 13-SEP-15:20 | 102429.28 | 13-SEP-15:20 | 0.00 | 0.00 | 0.00 |
October | 0.944945E+09 | 0.00 | 24.91 | 0.944945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27627.21 | 07-OCT-15:00 | 27627.21 | 07-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 12373430.13 | 0.00 | 2.50 | 12373430.13 | 0.00 | 0.00 | 0.00 | 0.00 | 6799.98 | 24-NOV-11:54 | 6799.98 | 24-NOV-11:54 | 0.00 | 0.00 | 0.00 |
December | 3014966.06 | 0.00 | 4.33 | 3014966.06 | 0.00 | 0.00 | 0.00 | 0.00 | 3250.70 | 18-DEC-05:21 | 3250.70 | 18-DEC-05:21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123529E+12 | 0.00 | 1212.47 | 0.122966E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2789.31 | 0.00 | 0.58 | 2789.31 | 0.00 | 0.00 | 0.00 | 0.00 | 23.30 | 23.30 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.384895E+11 | 0.00 | 373.02 | 0.383880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167000.05 | 160593.54 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.685183E+10 | 0.00 | 72.23 | 0.675723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 116900.49 | 06-JAN-05:14 | 116900.49 | 06-JAN-05:14 | 0.00 | 0.00 | 0.00 |
February | 0.480931E+10 | 0.00 | 58.01 | 0.480146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 120548.13 | 16-FEB-05:16 | 120548.13 | 16-FEB-05:16 | 0.00 | 0.00 | 0.00 |
March | 0.488644E+10 | 0.00 | 92.15 | 0.488444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103421.59 | 30-MAR-04:55 | 103421.59 | 30-MAR-04:55 | 0.00 | 0.00 | 0.00 |
April | 0.980002E+10 | 0.00 | 156.68 | 0.976181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103554.50 | 08-APR-04:49 | 103554.50 | 08-APR-04:49 | 0.00 | 0.00 | 0.00 |
May | 0.141789E+11 | 0.00 | 154.25 | 0.137928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73881.06 | 31-MAY-04:55 | 64840.63 | 02-MAY-04:57 | 0.00 | 0.00 | 0.00 |
June | 0.237458E+11 | 0.00 | 225.40 | 0.199198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80737.20 | 27-JUN-05:43 | 70533.81 | 08-JUN-05:00 | 0.00 | 0.00 | 0.00 |
July | 0.262993E+11 | 0.00 | 274.73 | 0.231025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77326.05 | 24-JUL-18:11 | 60062.45 | 21-JUL-16:00 | 0.00 | 0.00 | 0.00 |
August | 0.318912E+11 | 0.00 | 357.41 | 0.286115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89111.62 | 11-AUG-16:20 | 63786.76 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.238568E+11 | 0.00 | 256.20 | 0.213188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77622.41 | 01-SEP-09:48 | 65817.45 | 30-SEP-04:57 | 0.00 | 0.00 | 0.00 |
October | 0.131886E+11 | 0.00 | 140.68 | 0.118905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 128461.93 | 10-OCT-01:53 | 128461.93 | 10-OCT-01:53 | 0.00 | 0.00 | 0.00 |
November | 0.662005E+10 | 0.00 | 116.11 | 0.648031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102918.34 | 30-NOV-05:57 | 102918.34 | 30-NOV-05:57 | 0.00 | 0.00 | 0.00 |
December | 0.527320E+10 | 0.00 | 92.34 | 0.527320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103541.74 | 30-DEC-05:54 | 103541.74 | 30-DEC-05:54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171401E+12 | 0.00 | 1996.20 | 0.156594E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.480931E+10 | 0.00 | 58.01 | 0.480146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73881.06 | 60062.45 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.318912E+11 | 0.00 | 357.41 | 0.286115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 128461.93 | 128461.93 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3008274.10 | 0.00 | 298.14 | 3008274.10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.53 | 17-JAN-11:53 | 122.53 | 17-JAN-11:53 | 0.00 | 0.00 | 0.00 |
February | 0.143785E+12 | 0.00 | 349.69 | 0.143785E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 282161.26 | 22-FEB-07:52 | 282161.26 | 22-FEB-07:52 | 0.00 | 0.00 | 0.00 |
March | 0.231589E+12 | 0.00 | 738.69 | 0.231540E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 271521.12 | 03-MAR-06:22 | 271521.12 | 03-MAR-06:22 | 0.00 | 0.00 | 0.00 |
April | 0.222375E+12 | 0.00 | 719.69 | 0.222241E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 431084.24 | 30-APR-18:21 | 431084.24 | 30-APR-18:21 | 0.00 | 0.00 | 0.00 |
May | 0.389885E+09 | 0.00 | 229.76 | 0.389885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 215571.30 | 31-MAY-23:54 | 215571.30 | 31-MAY-23:54 | 0.00 | 0.00 | 0.00 |
June | 0.152866E+12 | 0.00 | 331.65 | 0.138240E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 454208.73 | 25-JUN-18:38 | 303635.33 | 20-JUN-15:52 | 0.00 | 0.00 | 0.00 |
July | 0.237258E+12 | 0.00 | 736.80 | 0.221320E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 378265.51 | 24-JUL-13:42 | 306293.49 | 22-JUL-17:45 | 0.00 | 0.00 | 0.00 |
August | 0.257050E+12 | 0.00 | 743.25 | 0.251906E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 405502.61 | 20-AUG-16:00 | 405502.61 | 20-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.866741E+09 | 0.00 | 247.22 | 0.866741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 250301.90 | 30-SEP-24:00 | 250301.90 | 30-SEP-24:00 | 0.00 | 0.00 | 0.00 |
October | 0.142711E+12 | 0.00 | 327.35 | 0.138713E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 290324.05 | 08-OCT-16:31 | 288405.24 | 20-OCT-17:45 | 0.00 | 0.00 | 0.00 |
November | 0.226721E+12 | 0.00 | 716.23 | 0.226689E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 270574.31 | 10-NOV-15:22 | 270574.31 | 10-NOV-15:22 | 0.00 | 0.00 | 0.00 |
December | 0.205902E+12 | 0.00 | 744.00 | 0.205902E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 254865.49 | 28-DEC-05:19 | 254865.49 | 28-DEC-05:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182152E+13 | 0.00 | 6182.47 | 0.178160E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3008274.10 | 0.00 | 229.76 | 3008274.10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.53 | 122.53 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.257050E+12 | 0.00 | 744.00 | 0.251906E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 454208.73 | 431084.24 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.603482E+10 | 0.185172E+10 | 744.00 | 0.603439E+10 | 427780.80 | 0.00 | 0.51 | 19-JAN-16:15 | 0.25 | 10-JAN-07:10 | 3159.41 | 19-JAN-16:20 | 3159.41 | 19-JAN-16:20 | 25.74 | 18-JAN-17:00 | 935.30 | 19-JAN-16:15 | 0.00 | 01-JAN-00:03 |
February | 0.100294E+11 | 0.284929E+10 | 672.00 | 0.100293E+11 | 122894.70 | 0.00 | 0.80 | 27-FEB-16:52 | 0.56 | 17-FEB-07:01 | 5327.13 | 27-FEB-16:56 | 5327.13 | 27-FEB-16:56 | 21.66 | 08-FEB-16:42 | 1449.39 | 27-FEB-16:56 | 0.00 | 01-FEB-00:01 |
March | 0.164908E+11 | 0.434227E+10 | 744.00 | 0.164907E+11 | 101857.22 | 0.00 | 1.00 | 31-MAR-23:01 | 0.82 | 27-MAR-06:01 | 8118.11 | 31-MAR-23:57 | 8118.11 | 31-MAR-23:57 | 65.19 | 20-MAR-06:01 | 2104.00 | 31-MAR-23:57 | 0.00 | 01-MAR-00:01 |
April | 0.216731E+11 | 0.563869E+10 | 720.00 | 0.216726E+11 | 516753.90 | 0.00 | 1.00 | 01-APR-00:10 | 0.52 | 30-APR-24:00 | 9750.52 | 30-APR-18:03 | 9750.52 | 30-APR-18:03 | 41.62 | 28-APR-15:20 | 2684.14 | 30-APR-18:08 | 0.00 | 01-APR-00:10 |
May | 0.727453E+10 | 0.219115E+10 | 744.00 | 0.726357E+10 | 10955939.74 | 0.00 | 0.70 | 31-MAY-23:52 | 0.33 | 06-MAY-06:25 | 4609.61 | 31-MAY-23:52 | 4609.61 | 31-MAY-23:52 | 122.08 | 23-MAY-16:00 | 1288.18 | 31-MAY-23:52 | 0.00 | 01-MAY-00:10 |
June | 0.122801E+11 | 0.341903E+10 | 720.00 | 0.122175E+11 | 62604459.21 | 0.00 | 0.91 | 30-JUN-23:57 | 0.63 | 08-JUN-06:01 | 6351.89 | 30-JUN-23:52 | 6351.89 | 30-JUN-23:52 | 201.81 | 27-JUN-08:00 | 1664.60 | 30-JUN-23:52 | 0.00 | 01-JUN-00:03 |
July | 0.180081E+11 | 0.467247E+10 | 744.00 | 0.179274E+11 | 80695745.12 | 0.00 | 1.00 | 06-JUL-15:30 | 0.86 | 01-JUL-06:08 | 8444.32 | 31-JUL-23:53 | 8444.32 | 31-JUL-23:53 | 191.51 | 24-JUL-15:00 | 2206.04 | 22-JUL-18:40 | 0.00 | 01-JUL-00:01 |
August | 0.230617E+11 | 0.599609E+10 | 744.00 | 0.229545E+11 | 0.107221E+09 | 0.00 | 1.00 | 01-AUG-00:03 | 0.51 | 31-AUG-24:00 | 9426.56 | 13-AUG-18:02 | 9424.61 | 13-AUG-18:10 | 239.22 | 08-AUG-13:10 | 2639.69 | 14-AUG-16:00 | 0.00 | 01-AUG-00:03 |
September | 0.723925E+10 | 0.217215E+10 | 720.00 | 0.719303E+10 | 46221168.94 | 0.00 | 0.68 | 30-SEP-23:52 | 0.35 | 21-SEP-06:05 | 4383.84 | 30-SEP-23:53 | 4383.84 | 30-SEP-23:53 | 151.78 | 12-SEP-14:05 | 1236.20 | 30-SEP-23:53 | 0.00 | 01-SEP-00:10 |
October | 0.117835E+11 | 0.331855E+10 | 744.00 | 0.117669E+11 | 16638932.90 | 0.00 | 0.90 | 31-OCT-23:53 | 0.59 | 28-OCT-07:00 | 6173.33 | 31-OCT-23:53 | 6173.33 | 31-OCT-23:53 | 116.04 | 17-OCT-15:10 | 1625.82 | 31-OCT-23:53 | 0.00 | 01-OCT-00:03 |
November | 0.159610E+11 | 0.420687E+10 | 720.00 | 0.159511E+11 | 9919588.15 | 0.00 | 0.98 | 03-NOV-16:00 | 0.83 | 17-NOV-07:01 | 6909.06 | 10-NOV-15:52 | 6909.06 | 10-NOV-15:52 | 129.23 | 08-NOV-15:00 | 1774.87 | 10-NOV-16:00 | 0.00 | 01-NOV-00:01 |
December | 0.212644E+11 | 0.549942E+10 | 744.00 | 0.212643E+11 | 105698.50 | 0.00 | 1.00 | 01-DEC-00:02 | 1.00 | 01-DEC-00:02 | 8555.32 | 25-DEC-15:17 | 8555.32 | 25-DEC-15:17 | 26.58 | 20-DEC-17:12 | 2230.74 | 25-DEC-15:17 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.171101E+12 | 0.461577E+11 | 8760.00 | 0.170765E+12 | 0.335532E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.603482E+10 | 0.185172E+10 | 672.00 | 0.603439E+10 | 101857.22 | 0.00 | 0.51 | 0.25 | 3159.41 | 3159.41 | 21.66 | 935.30 | 0.00 | |||||||
Maximum of Months | 0.230617E+11 | 0.599609E+10 | 744.00 | 0.229545E+11 | 0.107221E+09 | 0.00 | 1.00 | 1.00 | 9750.52 | 9750.52 | 239.22 | 2684.14 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.430313E+11 | 0.115756E+11 | 744.00 | 0.430268E+11 | 4446108.21 | 0.00 | 0.49 | 19-JAN-16:15 | 0.08 | 02-JAN-07:10 | 28810.67 | 19-JAN-16:20 | 28810.67 | 19-JAN-16:20 | 255.93 | 18-JAN-17:00 | 7360.25 | 19-JAN-16:15 | 0.00 | 01-JAN-00:03 |
February | 0.862403E+11 | 0.213583E+11 | 672.00 | 0.862389E+11 | 1432919.18 | 0.00 | 0.79 | 27-FEB-16:52 | 0.46 | 13-FEB-07:01 | 50439.27 | 27-FEB-16:56 | 50439.27 | 27-FEB-16:56 | 223.81 | 07-FEB-17:00 | 11801.17 | 27-FEB-16:56 | 0.00 | 01-FEB-00:01 |
March | 0.148481E+12 | 0.339976E+11 | 744.00 | 0.148480E+12 | 1037125.69 | 0.00 | 1.00 | 31-MAR-23:01 | 0.75 | 27-MAR-06:01 | 74798.29 | 31-MAR-23:30 | 74798.29 | 31-MAR-23:30 | 593.36 | 20-MAR-06:01 | 16537.36 | 31-MAR-23:25 | 0.00 | 01-MAR-00:01 |
April | 0.201735E+12 | 0.448289E+11 | 720.00 | 0.201730E+12 | 5199786.64 | 0.00 | 1.00 | 01-APR-00:10 | 0.47 | 30-APR-24:00 | 91931.75 | 30-APR-18:17 | 91931.75 | 30-APR-18:17 | 408.96 | 28-APR-15:30 | 21652.08 | 30-APR-18:17 | 0.00 | 01-APR-00:10 |
May | 0.626505E+11 | 0.163493E+11 | 744.00 | 0.625411E+11 | 0.109371E+09 | 0.00 | 0.68 | 31-MAY-23:30 | 0.26 | 05-MAY-06:05 | 42539.30 | 31-MAY-23:30 | 42539.30 | 31-MAY-23:30 | 1219.90 | 23-MAY-16:00 | 10264.06 | 31-MAY-23:30 | 0.00 | 01-MAY-00:10 |
June | 0.113711E+12 | 0.273139E+11 | 720.00 | 0.113087E+12 | 0.623759E+09 | 0.00 | 0.88 | 30-JUN-23:42 | 0.59 | 08-JUN-06:01 | 58526.89 | 30-JUN-23:42 | 58526.89 | 30-JUN-23:42 | 2001.30 | 27-JUN-08:02 | 13398.64 | 13-JUN-16:00 | 0.00 | 01-JUN-00:03 |
July | 0.168019E+12 | 0.376262E+11 | 744.00 | 0.167215E+12 | 0.803940E+09 | 0.00 | 1.00 | 09-JUL-17:51 | 0.83 | 01-JUL-06:08 | 79872.36 | 31-JUL-23:22 | 79872.36 | 31-JUL-23:22 | 1875.23 | 24-JUL-15:40 | 17986.15 | 22-JUL-18:35 | 0.00 | 01-JUL-00:01 |
August | 0.216562E+12 | 0.481376E+11 | 744.00 | 0.215501E+12 | 0.106095E+10 | 0.00 | 1.00 | 01-AUG-00:03 | 0.44 | 31-AUG-24:00 | 89542.11 | 17-AUG-18:10 | 88747.45 | 13-AUG-18:10 | 2374.20 | 08-AUG-13:10 | 21633.58 | 14-AUG-17:50 | 0.00 | 01-AUG-00:03 |
September | 0.623795E+11 | 0.162205E+11 | 720.00 | 0.619236E+11 | 0.455913E+09 | 0.00 | 0.65 | 30-SEP-23:12 | 0.29 | 20-SEP-06:05 | 39397.04 | 30-SEP-23:12 | 39397.04 | 30-SEP-23:12 | 1511.74 | 12-SEP-14:05 | 9631.63 | 30-SEP-23:12 | 0.00 | 01-SEP-00:10 |
October | 0.103885E+12 | 0.254292E+11 | 744.00 | 0.103719E+12 | 0.165945E+09 | 0.00 | 0.86 | 31-OCT-23:33 | 0.51 | 23-OCT-06:02 | 55573.84 | 31-OCT-23:33 | 55573.84 | 31-OCT-23:33 | 1150.01 | 17-OCT-15:12 | 12730.72 | 31-OCT-23:39 | 0.00 | 01-OCT-00:03 |
November | 0.141178E+12 | 0.324752E+11 | 720.00 | 0.141078E+12 | 99299016.90 | 0.00 | 0.96 | 03-NOV-16:00 | 0.72 | 20-NOV-07:01 | 65070.62 | 10-NOV-16:01 | 65070.62 | 10-NOV-16:01 | 1286.92 | 08-NOV-15:00 | 14403.28 | 10-NOV-16:10 | 0.00 | 01-NOV-00:01 |
December | 0.187445E+12 | 0.412279E+11 | 744.00 | 0.187444E+12 | 981843.88 | 0.00 | 1.00 | 01-DEC-00:02 | 0.92 | 26-DEC-07:03 | 79747.77 | 21-DEC-15:18 | 79747.77 | 21-DEC-15:18 | 205.93 | 20-DEC-17:12 | 17726.16 | 21-DEC-15:13 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.153532E+13 | 0.356540E+12 | 8760.00 | 0.153198E+13 | 0.333228E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.430313E+11 | 0.115756E+11 | 672.00 | 0.430268E+11 | 981843.88 | 0.00 | 0.49 | 0.08 | 28810.67 | 28810.67 | 205.93 | 7360.25 | 0.00 | |||||||
Maximum of Months | 0.216562E+12 | 0.481376E+11 | 744.00 | 0.215501E+12 | 0.106095E+10 | 0.00 | 1.00 | 0.92 | 91931.75 | 91931.75 | 2374.20 | 21652.08 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.206927E+10 | 0.662969E+09 | 582.45 | 0.206915E+10 | 111501.64 | 0.00 | 0.46 | 19-JAN-16:30 | 0.00 | 01-JAN-00:03 | 2773.18 | 19-JAN-16:20 | 2773.18 | 19-JAN-16:20 | 22.64 | 18-JAN-17:00 | 832.60 | 19-JAN-16:15 | 0.00 | 01-JAN-00:03 |
February | 0.649944E+10 | 0.194029E+10 | 671.33 | 0.649932E+10 | 123881.14 | 0.00 | 0.75 | 27-FEB-16:52 | 0.00 | 06-FEB-02:41 | 4865.48 | 27-FEB-16:56 | 4865.48 | 27-FEB-16:56 | 21.20 | 08-FEB-16:42 | 1343.26 | 27-FEB-16:56 | 0.00 | 01-FEB-00:01 |
March | 0.129395E+11 | 0.356197E+10 | 744.00 | 0.129394E+11 | 94984.15 | 0.00 | 1.00 | 31-MAR-23:01 | 0.51 | 06-MAR-04:53 | 6841.64 | 31-MAR-23:03 | 6841.64 | 31-MAR-23:03 | 46.38 | 20-MAR-06:01 | 1744.27 | 31-MAR-23:03 | 0.00 | 01-MAR-00:01 |
April | 0.190036E+11 | 0.490885E+10 | 720.00 | 0.190031E+11 | 502768.72 | 0.00 | 1.00 | 01-APR-11:52 | 0.41 | 30-APR-24:00 | 9360.58 | 30-APR-18:07 | 9360.58 | 30-APR-18:07 | 41.24 | 28-APR-15:30 | 2570.89 | 30-APR-18:10 | 0.00 | 01-APR-00:10 |
May | 0.526051E+10 | 0.161991E+10 | 742.80 | 0.524959E+10 | 10924245.53 | 0.00 | 0.63 | 31-MAY-23:10 | 0.00 | 04-MAY-06:55 | 3993.79 | 31-MAY-23:10 | 3993.79 | 31-MAY-23:10 | 123.59 | 23-MAY-16:00 | 1140.23 | 31-MAY-23:10 | 0.00 | 01-MAY-00:10 |
June | 0.108436E+11 | 0.307048E+10 | 720.00 | 0.107813E+11 | 62269517.66 | 0.00 | 0.84 | 13-JUN-16:00 | 0.46 | 08-JUN-06:01 | 5634.87 | 13-JUN-16:00 | 5515.44 | 13-JUN-16:00 | 199.71 | 27-JUN-08:02 | 1625.77 | 13-JUN-16:00 | 0.00 | 01-JUN-00:03 |
July | 0.163477E+11 | 0.431673E+10 | 744.00 | 0.162674E+11 | 80324920.43 | 0.00 | 1.00 | 09-JUL-18:02 | 0.72 | 31-JUL-06:06 | 7715.59 | 31-JUL-23:03 | 7715.59 | 31-JUL-23:03 | 189.20 | 24-JUL-15:30 | 2187.51 | 22-JUL-18:40 | 0.00 | 01-JUL-00:01 |
August | 0.211499E+11 | 0.545800E+10 | 744.00 | 0.210450E+11 | 0.104928E+09 | 0.00 | 1.00 | 01-AUG-00:03 | 0.37 | 31-AUG-24:00 | 9149.84 | 14-AUG-16:00 | 9067.05 | 14-AUG-16:00 | 236.48 | 08-AUG-13:10 | 2570.27 | 14-AUG-17:50 | 0.00 | 01-AUG-00:03 |
September | 0.528177E+10 | 0.162192E+10 | 718.49 | 0.523651E+10 | 45252813.38 | 0.00 | 0.59 | 12-SEP-17:00 | 0.00 | 03-SEP-09:43 | 3678.54 | 12-SEP-17:00 | 3560.27 | 12-SEP-17:00 | 153.61 | 12-SEP-14:05 | 1067.00 | 13-SEP-17:00 | 0.00 | 01-SEP-00:10 |
October | 0.849623E+10 | 0.249614E+10 | 744.00 | 0.847992E+10 | 16307936.88 | 0.00 | 0.78 | 03-OCT-16:50 | 0.29 | 23-OCT-04:11 | 5125.27 | 03-OCT-16:42 | 5125.27 | 03-OCT-16:42 | 114.69 | 17-OCT-15:12 | 1401.33 | 03-OCT-16:48 | 0.00 | 01-OCT-00:03 |
November | 0.119351E+11 | 0.331468E+10 | 720.00 | 0.119253E+11 | 9788528.59 | 0.00 | 0.93 | 03-NOV-16:00 | 0.47 | 20-NOV-04:34 | 6427.18 | 10-NOV-16:01 | 6427.18 | 10-NOV-16:01 | 128.18 | 08-NOV-15:00 | 1673.69 | 10-NOV-16:10 | 0.00 | 01-NOV-00:01 |
December | 0.162566E+11 | 0.427423E+10 | 744.00 | 0.162566E+11 | 38208.67 | 0.00 | 1.00 | 01-DEC-12:43 | 0.69 | 26-DEC-04:30 | 7760.82 | 21-DEC-15:18 | 7760.82 | 21-DEC-15:18 | 9.21 | 20-DEC-17:00 | 2001.50 | 21-DEC-15:13 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.136083E+12 | 0.372462E+11 | 8595.07 | 0.135753E+12 | 0.330667E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.206927E+10 | 0.662969E+09 | 582.45 | 0.206915E+10 | 38208.67 | 0.00 | 0.46 | 0.00 | 2773.18 | 2773.18 | 9.21 | 832.60 | 0.00 | |||||||
Maximum of Months | 0.211499E+11 | 0.545800E+10 | 744.00 | 0.210450E+11 | 0.104928E+09 | 0.00 | 1.00 | 0.72 | 9360.58 | 9360.58 | 236.48 | 2570.89 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.18 | 0.00 | 95.18 | 0.06 | 905.75 | 0.00 | 0.00 | 0.00 |
February | 148.63 | 0.00 | 148.63 | 1.24 | 858.25 | 0.00 | 0.00 | 0.00 |
March | 205.68 | 0.00 | 205.68 | 17.22 | 713.78 | 0.00 | 0.00 | 0.00 |
April | 334.87 | 1.50 | 333.37 | 130.87 | 555.44 | 0.00 | 0.00 | 0.00 |
May | 418.68 | 20.20 | 398.48 | 164.10 | 439.66 | 0.00 | 0.00 | 0.00 |
June | 462.82 | 29.02 | 433.80 | 287.79 | 334.87 | 0.00 | 0.00 | 0.00 |
July | 439.01 | 25.03 | 413.98 | 302.45 | 311.26 | 0.00 | 0.00 | 0.00 |
August | 345.09 | 5.41 | 339.68 | 230.96 | 353.49 | 0.00 | 0.00 | 0.00 |
September | 262.66 | 0.06 | 262.60 | 139.27 | 462.81 | 0.00 | 0.00 | 0.00 |
October | 168.31 | 0.00 | 168.31 | 25.45 | 651.64 | 0.00 | 0.00 | 0.00 |
November | 101.13 | 0.00 | 101.13 | 0.19 | 827.47 | 0.00 | 0.00 | 0.00 |
December | 68.87 | 0.00 | 68.87 | 0.00 | 985.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 254.72 | 6.81 | 247.90 | 108.84 | 615.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.87 | 0.00 | 68.87 | 0.00 | 311.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 462.82 | 29.02 | 433.80 | 302.45 | 985.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.18 | 0.00 | 95.18 | 0.06 | 905.75 | 0.00 | 0.00 | 0.00 |
February | 148.63 | 0.00 | 148.63 | 1.24 | 858.25 | 0.00 | 0.00 | 0.00 |
March | 205.68 | 0.00 | 205.68 | 17.22 | 713.78 | 0.00 | 0.00 | 0.00 |
April | 334.87 | 1.50 | 333.37 | 130.87 | 555.44 | 0.00 | 0.00 | 0.00 |
May | 418.68 | 20.20 | 398.48 | 164.10 | 439.66 | 0.00 | 0.00 | 0.00 |
June | 462.82 | 29.02 | 433.80 | 287.79 | 334.87 | 0.00 | 0.00 | 0.00 |
July | 439.01 | 25.03 | 413.98 | 302.45 | 311.26 | 0.00 | 0.00 | 0.00 |
August | 345.09 | 5.41 | 339.68 | 230.96 | 353.49 | 0.00 | 0.00 | 0.00 |
September | 262.66 | 0.06 | 262.60 | 139.27 | 462.81 | 0.00 | 0.00 | 0.00 |
October | 168.31 | 0.00 | 168.31 | 25.45 | 651.64 | 0.00 | 0.00 | 0.00 |
November | 101.13 | 0.00 | 101.13 | 0.19 | 827.47 | 0.00 | 0.00 | 0.00 |
December | 68.87 | 0.00 | 68.87 | 0.00 | 985.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 254.72 | 6.81 | 247.90 | 108.84 | 615.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.87 | 0.00 | 68.87 | 0.00 | 311.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 462.82 | 29.02 | 433.80 | 302.45 | 985.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.18 | 0.00 | 95.18 | 0.06 | 905.75 | 0.00 | 0.00 | 0.00 |
February | 148.63 | 0.00 | 148.63 | 1.24 | 858.25 | 0.00 | 0.00 | 0.00 |
March | 205.68 | 0.00 | 205.68 | 17.22 | 713.78 | 0.00 | 0.00 | 0.00 |
April | 334.87 | 1.50 | 333.37 | 130.87 | 555.44 | 0.00 | 0.00 | 0.00 |
May | 418.68 | 20.20 | 398.48 | 164.10 | 439.66 | 0.00 | 0.00 | 0.00 |
June | 462.82 | 29.02 | 433.80 | 287.79 | 334.87 | 0.00 | 0.00 | 0.00 |
July | 439.01 | 25.03 | 413.98 | 302.45 | 311.26 | 0.00 | 0.00 | 0.00 |
August | 345.09 | 5.41 | 339.68 | 230.96 | 353.49 | 0.00 | 0.00 | 0.00 |
September | 262.66 | 0.06 | 262.60 | 139.27 | 462.81 | 0.00 | 0.00 | 0.00 |
October | 168.31 | 0.00 | 168.31 | 25.45 | 651.64 | 0.00 | 0.00 | 0.00 |
November | 101.13 | 0.00 | 101.13 | 0.19 | 827.47 | 0.00 | 0.00 | 0.00 |
December | 68.87 | 0.00 | 68.87 | 0.00 | 985.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 254.72 | 6.81 | 247.90 | 108.84 | 615.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.87 | 0.00 | 68.87 | 0.00 | 311.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 462.82 | 29.02 | 433.80 | 302.45 | 985.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.18 | 0.00 | 95.18 | 0.06 | 905.75 | 0.00 | 0.00 | 0.00 |
February | 148.63 | 0.00 | 148.63 | 1.24 | 858.25 | 0.00 | 0.00 | 0.00 |
March | 205.68 | 0.00 | 205.68 | 17.22 | 713.78 | 0.00 | 0.00 | 0.00 |
April | 334.87 | 1.50 | 333.37 | 130.87 | 555.44 | 0.00 | 0.00 | 0.00 |
May | 418.68 | 20.20 | 398.48 | 164.10 | 439.66 | 0.00 | 0.00 | 0.00 |
June | 462.82 | 29.02 | 433.80 | 287.79 | 334.87 | 0.00 | 0.00 | 0.00 |
July | 439.01 | 25.03 | 413.98 | 302.45 | 311.26 | 0.00 | 0.00 | 0.00 |
August | 345.09 | 5.41 | 339.68 | 230.96 | 353.49 | 0.00 | 0.00 | 0.00 |
September | 262.66 | 0.06 | 262.60 | 139.27 | 462.81 | 0.00 | 0.00 | 0.00 |
October | 168.31 | 0.00 | 168.31 | 25.45 | 651.64 | 0.00 | 0.00 | 0.00 |
November | 101.13 | 0.00 | 101.13 | 0.19 | 827.47 | 0.00 | 0.00 | 0.00 |
December | 68.87 | 0.00 | 68.87 | 0.00 | 985.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 254.72 | 6.81 | 247.90 | 108.84 | 615.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.87 | 0.00 | 68.87 | 0.00 | 311.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 462.82 | 29.02 | 433.80 | 302.45 | 985.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.18 | 0.00 | 95.18 | 0.06 | 905.71 | 0.00 | 0.00 | 0.00 |
February | 148.62 | 0.00 | 148.62 | 1.24 | 858.22 | 0.00 | 0.00 | 0.00 |
March | 205.67 | 0.00 | 205.67 | 17.22 | 713.75 | 0.00 | 0.00 | 0.00 |
April | 334.86 | 1.50 | 333.36 | 130.87 | 555.41 | 0.00 | 0.00 | 0.00 |
May | 418.66 | 20.20 | 398.46 | 164.09 | 439.64 | 0.00 | 0.00 | 0.00 |
June | 462.80 | 29.02 | 433.78 | 287.78 | 334.86 | 0.00 | 0.00 | 0.00 |
July | 438.99 | 25.03 | 413.96 | 302.44 | 311.25 | 0.00 | 0.00 | 0.00 |
August | 345.07 | 5.41 | 339.66 | 230.95 | 353.48 | 0.00 | 0.00 | 0.00 |
September | 262.65 | 0.06 | 262.59 | 139.26 | 462.79 | 0.00 | 0.00 | 0.00 |
October | 168.30 | 0.00 | 168.30 | 25.45 | 651.61 | 0.00 | 0.00 | 0.00 |
November | 101.12 | 0.00 | 101.12 | 0.19 | 827.43 | 0.00 | 0.00 | 0.00 |
December | 68.87 | 0.00 | 68.87 | 0.00 | 985.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 254.71 | 6.81 | 247.89 | 108.83 | 615.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.87 | 0.00 | 68.87 | 0.00 | 311.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 462.80 | 29.02 | 433.78 | 302.44 | 985.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 216.16 | 86.83 | 129.33 | 89.94 | 914.86 | 0.00 | 0.00 | 0.00 |
February | 322.33 | 119.07 | 203.26 | 158.11 | 868.54 | 0.00 | 0.00 | 0.00 |
March | 336.85 | 66.38 | 270.47 | 134.36 | 711.34 | 0.00 | 0.00 | 0.00 |
April | 904.46 | 425.01 | 479.45 | 837.53 | 546.73 | 0.00 | 0.00 | 0.00 |
May | 951.01 | 414.72 | 536.29 | 852.16 | 472.31 | 0.00 | 0.00 | 0.00 |
June | 941.33 | 375.96 | 565.37 | 926.85 | 362.58 | 0.00 | 0.00 | 0.00 |
July | 960.91 | 408.39 | 552.52 | 1002.31 | 334.16 | 0.00 | 0.00 | 0.00 |
August | 910.25 | 434.91 | 475.34 | 986.59 | 359.76 | 0.00 | 0.00 | 0.00 |
September | 819.71 | 435.89 | 383.83 | 847.12 | 460.77 | 0.00 | 0.00 | 0.00 |
October | 395.69 | 163.98 | 231.70 | 288.50 | 660.54 | 0.00 | 0.00 | 0.00 |
November | 206.28 | 70.30 | 135.98 | 84.39 | 829.67 | 0.00 | 0.00 | 0.00 |
December | 152.88 | 56.84 | 96.04 | 51.15 | 999.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 594.01 | 255.18 | 338.83 | 522.90 | 625.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 152.88 | 56.84 | 96.04 | 51.15 | 334.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 960.91 | 435.89 | 565.37 | 1002.31 | 999.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 216.16 | 86.83 | 129.33 | 89.94 | 914.86 | 0.00 | 0.00 | 0.00 |
February | 322.33 | 119.07 | 203.26 | 158.11 | 868.54 | 0.00 | 0.00 | 0.00 |
March | 336.85 | 66.38 | 270.47 | 134.36 | 711.34 | 0.00 | 0.00 | 0.00 |
April | 904.46 | 425.01 | 479.45 | 837.53 | 546.73 | 0.00 | 0.00 | 0.00 |
May | 951.01 | 414.72 | 536.29 | 852.16 | 472.31 | 0.00 | 0.00 | 0.00 |
June | 941.33 | 375.96 | 565.37 | 926.85 | 362.58 | 0.00 | 0.00 | 0.00 |
July | 960.91 | 408.39 | 552.52 | 1002.31 | 334.16 | 0.00 | 0.00 | 0.00 |
August | 910.25 | 434.91 | 475.34 | 986.59 | 359.76 | 0.00 | 0.00 | 0.00 |
September | 819.71 | 435.89 | 383.83 | 847.12 | 460.77 | 0.00 | 0.00 | 0.00 |
October | 395.69 | 163.98 | 231.70 | 288.50 | 660.54 | 0.00 | 0.00 | 0.00 |
November | 206.28 | 70.30 | 135.98 | 84.39 | 829.67 | 0.00 | 0.00 | 0.00 |
December | 152.88 | 56.84 | 96.04 | 51.15 | 999.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 594.01 | 255.18 | 338.83 | 522.90 | 625.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 152.88 | 56.84 | 96.04 | 51.15 | 334.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 960.91 | 435.89 | 565.37 | 1002.31 | 999.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 216.16 | 86.83 | 129.33 | 89.94 | 914.84 | 0.00 | 0.00 | 0.00 |
February | 322.33 | 119.07 | 203.26 | 158.11 | 868.52 | 0.00 | 0.00 | 0.00 |
March | 336.84 | 66.38 | 270.46 | 134.36 | 711.32 | 0.00 | 0.00 | 0.00 |
April | 904.44 | 425.00 | 479.44 | 837.51 | 546.72 | 0.00 | 0.00 | 0.00 |
May | 950.99 | 414.71 | 536.28 | 852.15 | 472.30 | 0.00 | 0.00 | 0.00 |
June | 941.31 | 375.95 | 565.36 | 926.83 | 362.57 | 0.00 | 0.00 | 0.00 |
July | 960.89 | 408.38 | 552.51 | 1002.29 | 334.15 | 0.00 | 0.00 | 0.00 |
August | 910.24 | 434.90 | 475.33 | 986.57 | 359.76 | 0.00 | 0.00 | 0.00 |
September | 819.70 | 435.88 | 383.82 | 847.11 | 460.76 | 0.00 | 0.00 | 0.00 |
October | 395.68 | 163.98 | 231.70 | 288.49 | 660.53 | 0.00 | 0.00 | 0.00 |
November | 206.28 | 70.30 | 135.98 | 84.39 | 829.65 | 0.00 | 0.00 | 0.00 |
December | 152.88 | 56.84 | 96.04 | 51.15 | 999.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 594.00 | 255.18 | 338.82 | 522.89 | 625.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 152.88 | 56.84 | 96.04 | 51.15 | 334.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 960.89 | 435.88 | 565.36 | 1002.29 | 999.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 540.37 | 349.81 | 190.57 | 470.04 | 748.90 | 0.00 | 0.00 | 0.00 |
February | 659.97 | 402.72 | 257.25 | 595.88 | 737.45 | 0.00 | 0.00 | 0.00 |
March | 408.04 | 118.80 | 289.23 | 262.56 | 630.31 | 0.00 | 0.00 | 0.00 |
April | 847.32 | 382.98 | 464.34 | 881.80 | 535.48 | 0.00 | 0.00 | 0.00 |
May | 700.81 | 228.16 | 472.65 | 656.64 | 466.08 | 0.00 | 0.00 | 0.00 |
June | 645.60 | 156.27 | 489.32 | 637.44 | 355.80 | 0.00 | 0.00 | 0.00 |
July | 699.49 | 219.05 | 480.44 | 763.08 | 332.12 | 0.00 | 0.00 | 0.00 |
August | 819.65 | 368.71 | 450.94 | 966.51 | 359.01 | 0.00 | 0.00 | 0.00 |
September | 968.61 | 567.43 | 401.18 | 1138.06 | 444.89 | 0.00 | 0.00 | 0.00 |
October | 665.48 | 388.94 | 276.54 | 674.73 | 588.11 | 0.00 | 0.00 | 0.00 |
November | 471.82 | 287.02 | 184.80 | 416.23 | 709.73 | 0.00 | 0.00 | 0.00 |
December | 373.96 | 239.60 | 134.36 | 312.17 | 856.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 649.10 | 307.92 | 341.18 | 647.04 | 562.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 373.96 | 118.80 | 134.36 | 262.56 | 332.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 968.61 | 567.43 | 489.32 | 1138.06 | 856.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 540.37 | 349.81 | 190.57 | 470.04 | 748.90 | 0.00 | 0.00 | 0.00 |
February | 659.97 | 402.72 | 257.25 | 595.88 | 737.45 | 0.00 | 0.00 | 0.00 |
March | 408.04 | 118.80 | 289.23 | 262.56 | 630.31 | 0.00 | 0.00 | 0.00 |
April | 847.32 | 382.98 | 464.34 | 881.80 | 535.48 | 0.00 | 0.00 | 0.00 |
May | 700.81 | 228.16 | 472.65 | 656.64 | 466.08 | 0.00 | 0.00 | 0.00 |
June | 645.60 | 156.27 | 489.32 | 637.44 | 355.80 | 0.00 | 0.00 | 0.00 |
July | 699.49 | 219.05 | 480.44 | 763.08 | 332.12 | 0.00 | 0.00 | 0.00 |
August | 819.65 | 368.71 | 450.94 | 966.51 | 359.01 | 0.00 | 0.00 | 0.00 |
September | 968.61 | 567.43 | 401.18 | 1138.06 | 444.89 | 0.00 | 0.00 | 0.00 |
October | 665.48 | 388.94 | 276.54 | 674.73 | 588.11 | 0.00 | 0.00 | 0.00 |
November | 471.82 | 287.02 | 184.80 | 416.23 | 709.73 | 0.00 | 0.00 | 0.00 |
December | 373.96 | 239.60 | 134.36 | 312.17 | 856.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 649.10 | 307.92 | 341.18 | 647.04 | 562.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 373.96 | 118.80 | 134.36 | 262.56 | 332.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 968.61 | 567.43 | 489.32 | 1138.06 | 856.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 540.37 | 349.81 | 190.57 | 470.04 | 748.90 | 0.00 | 0.00 | 0.00 |
February | 659.97 | 402.72 | 257.25 | 595.88 | 737.45 | 0.00 | 0.00 | 0.00 |
March | 408.04 | 118.80 | 289.23 | 262.56 | 630.31 | 0.00 | 0.00 | 0.00 |
April | 847.32 | 382.98 | 464.34 | 881.80 | 535.48 | 0.00 | 0.00 | 0.00 |
May | 700.81 | 228.16 | 472.65 | 656.64 | 466.08 | 0.00 | 0.00 | 0.00 |
June | 645.60 | 156.27 | 489.32 | 637.44 | 355.80 | 0.00 | 0.00 | 0.00 |
July | 699.49 | 219.05 | 480.44 | 763.08 | 332.12 | 0.00 | 0.00 | 0.00 |
August | 819.65 | 368.71 | 450.94 | 966.51 | 359.01 | 0.00 | 0.00 | 0.00 |
September | 968.61 | 567.43 | 401.18 | 1138.06 | 444.89 | 0.00 | 0.00 | 0.00 |
October | 665.48 | 388.94 | 276.54 | 674.73 | 588.11 | 0.00 | 0.00 | 0.00 |
November | 471.82 | 287.02 | 184.80 | 416.23 | 709.73 | 0.00 | 0.00 | 0.00 |
December | 373.96 | 239.60 | 134.36 | 312.17 | 856.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 649.10 | 307.92 | 341.18 | 647.04 | 562.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 373.96 | 118.80 | 134.36 | 262.56 | 332.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 968.61 | 567.43 | 489.32 | 1138.06 | 856.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 540.37 | 349.81 | 190.57 | 470.04 | 748.90 | 0.00 | 0.00 | 0.00 |
February | 659.97 | 402.72 | 257.25 | 595.88 | 737.45 | 0.00 | 0.00 | 0.00 |
March | 408.04 | 118.80 | 289.23 | 262.56 | 630.31 | 0.00 | 0.00 | 0.00 |
April | 847.32 | 382.98 | 464.34 | 881.80 | 535.48 | 0.00 | 0.00 | 0.00 |
May | 700.81 | 228.16 | 472.65 | 656.64 | 466.08 | 0.00 | 0.00 | 0.00 |
June | 645.60 | 156.27 | 489.32 | 637.44 | 355.80 | 0.00 | 0.00 | 0.00 |
July | 699.49 | 219.05 | 480.44 | 763.08 | 332.12 | 0.00 | 0.00 | 0.00 |
August | 819.65 | 368.71 | 450.94 | 966.51 | 359.01 | 0.00 | 0.00 | 0.00 |
September | 968.61 | 567.43 | 401.18 | 1138.06 | 444.89 | 0.00 | 0.00 | 0.00 |
October | 665.48 | 388.94 | 276.54 | 674.73 | 588.11 | 0.00 | 0.00 | 0.00 |
November | 471.82 | 287.02 | 184.80 | 416.23 | 709.73 | 0.00 | 0.00 | 0.00 |
December | 373.96 | 239.60 | 134.36 | 312.17 | 856.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 649.10 | 307.92 | 341.18 | 647.04 | 562.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 373.96 | 118.80 | 134.36 | 262.56 | 332.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 968.61 | 567.43 | 489.32 | 1138.06 | 856.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 540.35 | 349.79 | 190.56 | 470.02 | 748.86 | 0.00 | 0.00 | 0.00 |
February | 659.94 | 402.71 | 257.24 | 595.86 | 737.42 | 0.00 | 0.00 | 0.00 |
March | 408.02 | 118.80 | 289.22 | 262.55 | 630.28 | 0.00 | 0.00 | 0.00 |
April | 847.28 | 382.96 | 464.32 | 881.77 | 535.46 | 0.00 | 0.00 | 0.00 |
May | 700.78 | 228.15 | 472.63 | 656.61 | 466.07 | 0.00 | 0.00 | 0.00 |
June | 645.57 | 156.27 | 489.31 | 637.41 | 355.78 | 0.00 | 0.00 | 0.00 |
July | 699.46 | 219.04 | 480.42 | 763.05 | 332.11 | 0.00 | 0.00 | 0.00 |
August | 819.62 | 368.69 | 450.92 | 966.48 | 359.00 | 0.00 | 0.00 | 0.00 |
September | 968.58 | 567.41 | 401.17 | 1138.02 | 444.87 | 0.00 | 0.00 | 0.00 |
October | 665.45 | 388.93 | 276.52 | 674.71 | 588.08 | 0.00 | 0.00 | 0.00 |
November | 471.80 | 287.01 | 184.79 | 416.21 | 709.70 | 0.00 | 0.00 | 0.00 |
December | 373.95 | 239.59 | 134.36 | 312.16 | 856.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 649.07 | 307.91 | 341.16 | 647.01 | 562.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 373.95 | 118.80 | 134.36 | 262.55 | 332.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 968.58 | 567.41 | 489.31 | 1138.02 | 856.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 210.21 | 69.45 | 140.75 | 87.89 | 972.97 | 0.00 | 0.00 | 0.00 |
February | 372.18 | 157.15 | 215.03 | 233.52 | 938.29 | 0.00 | 0.00 | 0.00 |
March | 336.53 | 64.38 | 272.15 | 124.63 | 792.09 | 0.00 | 0.00 | 0.00 |
April | 794.06 | 315.41 | 478.65 | 689.72 | 657.37 | 0.00 | 0.00 | 0.00 |
May | 931.61 | 378.83 | 552.79 | 824.61 | 538.11 | 0.00 | 0.00 | 0.00 |
June | 1006.04 | 414.15 | 591.89 | 996.31 | 428.53 | 0.00 | 0.00 | 0.00 |
July | 1024.61 | 451.75 | 572.86 | 1069.86 | 413.34 | 0.00 | 0.00 | 0.00 |
August | 860.60 | 372.62 | 487.99 | 901.67 | 457.65 | 0.00 | 0.00 | 0.00 |
September | 690.43 | 309.61 | 380.83 | 697.75 | 533.65 | 0.00 | 0.00 | 0.00 |
October | 368.32 | 132.45 | 235.87 | 259.05 | 734.38 | 0.00 | 0.00 | 0.00 |
November | 199.32 | 58.18 | 141.14 | 84.04 | 927.53 | 0.00 | 0.00 | 0.00 |
December | 112.82 | 23.81 | 89.01 | 22.46 | 1144.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 576.17 | 229.07 | 347.10 | 500.19 | 710.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 112.82 | 23.81 | 89.01 | 22.46 | 413.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1024.61 | 451.75 | 591.89 | 1069.86 | 1144.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 210.21 | 69.45 | 140.75 | 87.89 | 972.97 | 0.00 | 0.00 | 0.00 |
February | 372.18 | 157.15 | 215.03 | 233.52 | 938.29 | 0.00 | 0.00 | 0.00 |
March | 336.53 | 64.38 | 272.15 | 124.63 | 792.09 | 0.00 | 0.00 | 0.00 |
April | 794.06 | 315.41 | 478.65 | 689.72 | 657.37 | 0.00 | 0.00 | 0.00 |
May | 931.61 | 378.83 | 552.79 | 824.61 | 538.11 | 0.00 | 0.00 | 0.00 |
June | 1006.04 | 414.15 | 591.89 | 996.31 | 428.53 | 0.00 | 0.00 | 0.00 |
July | 1024.61 | 451.75 | 572.86 | 1069.86 | 413.34 | 0.00 | 0.00 | 0.00 |
August | 860.60 | 372.62 | 487.99 | 901.67 | 457.65 | 0.00 | 0.00 | 0.00 |
September | 690.43 | 309.61 | 380.83 | 697.75 | 533.65 | 0.00 | 0.00 | 0.00 |
October | 368.32 | 132.45 | 235.87 | 259.05 | 734.38 | 0.00 | 0.00 | 0.00 |
November | 199.32 | 58.18 | 141.14 | 84.04 | 927.53 | 0.00 | 0.00 | 0.00 |
December | 112.82 | 23.81 | 89.01 | 22.46 | 1144.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 576.17 | 229.07 | 347.10 | 500.19 | 710.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 112.82 | 23.81 | 89.01 | 22.46 | 413.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1024.61 | 451.75 | 591.89 | 1069.86 | 1144.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 210.20 | 69.45 | 140.75 | 87.89 | 972.95 | 0.00 | 0.00 | 0.00 |
February | 372.17 | 157.14 | 215.03 | 233.51 | 938.28 | 0.00 | 0.00 | 0.00 |
March | 336.53 | 64.38 | 272.15 | 124.62 | 792.08 | 0.00 | 0.00 | 0.00 |
April | 794.04 | 315.40 | 478.64 | 689.71 | 657.36 | 0.00 | 0.00 | 0.00 |
May | 931.60 | 378.82 | 552.78 | 824.59 | 538.10 | 0.00 | 0.00 | 0.00 |
June | 1006.02 | 414.14 | 591.88 | 996.29 | 428.52 | 0.00 | 0.00 | 0.00 |
July | 1024.59 | 451.75 | 572.85 | 1069.84 | 413.33 | 0.00 | 0.00 | 0.00 |
August | 860.59 | 372.61 | 487.98 | 901.66 | 457.65 | 0.00 | 0.00 | 0.00 |
September | 690.42 | 309.60 | 380.82 | 697.74 | 533.64 | 0.00 | 0.00 | 0.00 |
October | 368.31 | 132.44 | 235.87 | 259.05 | 734.37 | 0.00 | 0.00 | 0.00 |
November | 199.32 | 58.18 | 141.13 | 84.03 | 927.51 | 0.00 | 0.00 | 0.00 |
December | 112.82 | 23.81 | 89.01 | 22.46 | 1144.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 576.16 | 229.07 | 347.09 | 500.18 | 710.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 112.82 | 23.81 | 89.01 | 22.46 | 413.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1024.59 | 451.75 | 591.88 | 1069.84 | 1144.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 475.90 | 0.00 | 475.90 | 3.24 | 4117.44 | 0.00 | 0.00 | 0.00 |
February | 743.14 | 0.00 | 743.14 | 16.20 | 3925.49 | 0.00 | 0.00 | 0.00 |
March | 1028.37 | 0.00 | 1028.37 | 122.30 | 3240.42 | 0.00 | 0.00 | 0.00 |
April | 1674.35 | 7.49 | 1666.85 | 712.68 | 2557.94 | 0.00 | 0.00 | 0.00 |
May | 2093.36 | 100.99 | 1992.37 | 870.55 | 2062.33 | 0.00 | 0.00 | 0.00 |
June | 2314.08 | 145.11 | 2168.97 | 1466.98 | 1589.46 | 0.00 | 0.00 | 0.00 |
July | 2195.03 | 125.15 | 2069.88 | 1570.70 | 1447.90 | 0.00 | 0.00 | 0.00 |
August | 1725.41 | 27.03 | 1698.37 | 1210.30 | 1612.51 | 0.00 | 0.00 | 0.00 |
September | 1313.27 | 0.29 | 1312.98 | 747.36 | 2149.31 | 0.00 | 0.00 | 0.00 |
October | 841.53 | 0.00 | 841.53 | 169.25 | 2945.51 | 0.00 | 0.00 | 0.00 |
November | 505.64 | 0.00 | 505.64 | 6.01 | 3669.84 | 0.00 | 0.00 | 0.00 |
December | 344.34 | 0.00 | 344.34 | 0.00 | 4388.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1273.56 | 34.07 | 1239.49 | 577.48 | 2803.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 344.34 | 0.00 | 344.34 | 0.00 | 1447.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2314.08 | 145.11 | 2168.97 | 1570.70 | 4388.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 648.48 | 260.49 | 387.98 | 283.42 | 2569.66 | 0.00 | 0.00 | 0.00 |
February | 966.99 | 357.21 | 609.78 | 488.51 | 2474.49 | 0.00 | 0.00 | 0.00 |
March | 1010.53 | 199.14 | 811.39 | 406.88 | 2018.67 | 0.00 | 0.00 | 0.00 |
April | 2713.35 | 1275.02 | 1438.33 | 2493.33 | 1577.93 | 0.00 | 0.00 | 0.00 |
May | 2853.01 | 1244.15 | 1608.86 | 2525.36 | 1364.78 | 0.00 | 0.00 | 0.00 |
June | 2823.95 | 1127.86 | 1696.09 | 2749.31 | 1047.41 | 0.00 | 0.00 | 0.00 |
July | 2882.70 | 1225.15 | 1657.55 | 2981.60 | 957.18 | 0.00 | 0.00 | 0.00 |
August | 2730.73 | 1304.72 | 1426.01 | 2940.26 | 1025.14 | 0.00 | 0.00 | 0.00 |
September | 2459.11 | 1307.64 | 1151.47 | 2520.02 | 1325.25 | 0.00 | 0.00 | 0.00 |
October | 1187.05 | 491.94 | 695.10 | 867.65 | 1867.18 | 0.00 | 0.00 | 0.00 |
November | 618.84 | 210.91 | 407.93 | 265.19 | 2314.40 | 0.00 | 0.00 | 0.00 |
December | 458.64 | 170.52 | 288.12 | 168.48 | 2774.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1782.02 | 765.55 | 1016.48 | 1561.36 | 1772.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 458.64 | 170.52 | 288.12 | 168.48 | 957.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2882.70 | 1307.64 | 1696.09 | 2981.60 | 2774.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2701.84 | 1749.01 | 952.83 | 2345.55 | 3670.90 | 0.00 | 0.00 | 0.00 |
February | 3299.80 | 2013.58 | 1286.22 | 2958.01 | 3651.99 | 0.00 | 0.00 | 0.00 |
March | 2040.15 | 594.00 | 1446.15 | 1315.35 | 3062.83 | 0.00 | 0.00 | 0.00 |
April | 4236.54 | 1914.87 | 2321.68 | 4382.43 | 2622.25 | 0.00 | 0.00 | 0.00 |
May | 3504.01 | 1140.79 | 2363.22 | 3256.44 | 2292.42 | 0.00 | 0.00 | 0.00 |
June | 3227.95 | 781.35 | 2446.60 | 3177.48 | 1730.09 | 0.00 | 0.00 | 0.00 |
July | 3497.42 | 1095.26 | 2402.16 | 3814.01 | 1593.28 | 0.00 | 0.00 | 0.00 |
August | 4098.21 | 1843.53 | 2254.68 | 4823.87 | 1716.11 | 0.00 | 0.00 | 0.00 |
September | 4843.01 | 2837.12 | 2005.89 | 5643.35 | 2199.47 | 0.00 | 0.00 | 0.00 |
October | 3327.35 | 1944.69 | 1382.66 | 3351.09 | 2890.36 | 0.00 | 0.00 | 0.00 |
November | 2359.09 | 1435.09 | 924.00 | 2078.18 | 3440.10 | 0.00 | 0.00 | 0.00 |
December | 1869.79 | 1197.99 | 671.81 | 1574.00 | 4126.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3245.46 | 1539.61 | 1705.86 | 3222.35 | 2745.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1869.79 | 594.00 | 671.81 | 1315.35 | 1593.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4843.01 | 2837.12 | 2446.60 | 5643.35 | 4126.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 630.61 | 208.36 | 422.26 | 286.45 | 2636.13 | 0.00 | 0.00 | 0.00 |
February | 1116.53 | 471.44 | 645.10 | 728.56 | 2554.92 | 0.00 | 0.00 | 0.00 |
March | 1009.58 | 193.13 | 816.45 | 421.76 | 2082.57 | 0.00 | 0.00 | 0.00 |
April | 2382.15 | 946.21 | 1435.94 | 2160.48 | 1731.47 | 0.00 | 0.00 | 0.00 |
May | 2794.81 | 1136.47 | 1658.34 | 2509.27 | 1501.59 | 0.00 | 0.00 | 0.00 |
June | 3018.10 | 1242.44 | 1775.66 | 3027.00 | 1180.44 | 0.00 | 0.00 | 0.00 |
July | 3073.80 | 1355.25 | 1718.55 | 3280.28 | 1097.29 | 0.00 | 0.00 | 0.00 |
August | 2581.79 | 1117.84 | 1463.94 | 2794.32 | 1172.92 | 0.00 | 0.00 | 0.00 |
September | 2071.28 | 928.81 | 1142.47 | 2140.52 | 1466.06 | 0.00 | 0.00 | 0.00 |
October | 1104.95 | 397.33 | 707.61 | 820.51 | 1963.87 | 0.00 | 0.00 | 0.00 |
November | 597.96 | 174.55 | 423.41 | 279.72 | 2414.87 | 0.00 | 0.00 | 0.00 |
December | 338.46 | 71.42 | 267.04 | 84.81 | 2944.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1728.50 | 687.22 | 1041.28 | 1547.26 | 1892.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 338.46 | 71.42 | 267.04 | 84.81 | 1097.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3073.80 | 1355.25 | 1775.66 | 3280.28 | 2944.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 475.90 | 0.00 | 475.90 | 13.71 | 3675.66 | 0.00 | 0.00 | 0.00 |
February | 743.14 | 0.00 | 743.14 | 44.03 | 3493.33 | 0.00 | 0.00 | 0.00 |
March | 1028.37 | 0.00 | 1028.37 | 180.11 | 2874.50 | 0.00 | 0.00 | 0.00 |
April | 1674.35 | 7.49 | 1666.85 | 793.94 | 2301.25 | 0.00 | 0.00 | 0.00 |
May | 2093.36 | 100.99 | 1992.37 | 963.65 | 1858.09 | 0.00 | 0.00 | 0.00 |
June | 2314.08 | 145.11 | 2168.97 | 1531.87 | 1465.68 | 0.00 | 0.00 | 0.00 |
July | 2195.03 | 125.15 | 2069.88 | 1625.38 | 1339.44 | 0.00 | 0.00 | 0.00 |
August | 1725.41 | 27.03 | 1698.37 | 1260.40 | 1476.35 | 0.00 | 0.00 | 0.00 |
September | 1313.27 | 0.29 | 1312.98 | 823.86 | 1925.85 | 0.00 | 0.00 | 0.00 |
October | 841.53 | 0.00 | 841.53 | 242.48 | 2550.41 | 0.00 | 0.00 | 0.00 |
November | 505.64 | 0.00 | 505.64 | 19.56 | 3210.35 | 0.00 | 0.00 | 0.00 |
December | 344.34 | 0.00 | 344.34 | 0.79 | 3956.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1273.56 | 34.07 | 1239.49 | 627.92 | 2505.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 344.34 | 0.00 | 344.34 | 0.79 | 1339.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2314.08 | 145.11 | 2168.97 | 1625.38 | 3956.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 648.48 | 260.49 | 387.98 | 314.13 | 2289.66 | 0.00 | 0.00 | 0.00 |
February | 966.99 | 357.21 | 609.78 | 533.94 | 2203.66 | 0.00 | 0.00 | 0.00 |
March | 1010.53 | 199.14 | 811.39 | 471.01 | 1801.48 | 0.00 | 0.00 | 0.00 |
April | 2713.35 | 1275.02 | 1438.33 | 2549.53 | 1450.12 | 0.00 | 0.00 | 0.00 |
May | 2853.01 | 1244.15 | 1608.86 | 2578.36 | 1263.66 | 0.00 | 0.00 | 0.00 |
June | 2823.95 | 1127.86 | 1696.09 | 2776.50 | 988.51 | 0.00 | 0.00 | 0.00 |
July | 2882.70 | 1225.15 | 1657.55 | 2996.50 | 907.00 | 0.00 | 0.00 | 0.00 |
August | 2730.73 | 1304.72 | 1426.01 | 2957.99 | 967.50 | 0.00 | 0.00 | 0.00 |
September | 2459.11 | 1307.64 | 1151.47 | 2560.57 | 1224.71 | 0.00 | 0.00 | 0.00 |
October | 1187.05 | 491.94 | 695.10 | 935.11 | 1635.17 | 0.00 | 0.00 | 0.00 |
November | 618.84 | 210.91 | 407.93 | 295.58 | 2029.50 | 0.00 | 0.00 | 0.00 |
December | 458.64 | 170.52 | 288.12 | 189.31 | 2501.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1782.02 | 765.55 | 1016.48 | 1600.36 | 1602.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 458.64 | 170.52 | 288.12 | 189.31 | 907.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2882.70 | 1307.64 | 1696.09 | 2996.50 | 2501.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2701.84 | 1749.01 | 952.83 | 2429.31 | 3273.92 | 0.00 | 0.00 | 0.00 |
February | 3299.80 | 2013.58 | 1286.22 | 3042.73 | 3279.84 | 0.00 | 0.00 | 0.00 |
March | 2040.15 | 594.00 | 1446.15 | 1390.59 | 2753.83 | 0.00 | 0.00 | 0.00 |
April | 4236.54 | 1914.87 | 2321.68 | 4430.94 | 2407.45 | 0.00 | 0.00 | 0.00 |
May | 3504.01 | 1140.79 | 2363.22 | 3294.93 | 2114.30 | 0.00 | 0.00 | 0.00 |
June | 3227.95 | 781.35 | 2446.60 | 3192.51 | 1623.62 | 0.00 | 0.00 | 0.00 |
July | 3497.42 | 1095.26 | 2402.16 | 3819.83 | 1496.84 | 0.00 | 0.00 | 0.00 |
August | 4098.21 | 1843.53 | 2254.68 | 4832.47 | 1607.75 | 0.00 | 0.00 | 0.00 |
September | 4843.01 | 2837.12 | 2005.89 | 5674.58 | 2028.18 | 0.00 | 0.00 | 0.00 |
October | 3327.35 | 1944.69 | 1382.66 | 3423.07 | 2560.94 | 0.00 | 0.00 | 0.00 |
November | 2359.09 | 1435.09 | 924.00 | 2142.76 | 3047.37 | 0.00 | 0.00 | 0.00 |
December | 1869.79 | 1197.99 | 671.81 | 1633.67 | 3723.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3245.46 | 1539.61 | 1705.86 | 3271.12 | 2489.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1869.79 | 594.00 | 671.81 | 1390.59 | 1496.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4843.01 | 2837.12 | 2446.60 | 5674.58 | 3723.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 630.61 | 208.36 | 422.26 | 303.44 | 2402.10 | 0.00 | 0.00 | 0.00 |
February | 1116.53 | 471.44 | 645.10 | 750.67 | 2335.82 | 0.00 | 0.00 | 0.00 |
March | 1009.58 | 193.13 | 816.45 | 442.96 | 1906.69 | 0.00 | 0.00 | 0.00 |
April | 2382.15 | 946.21 | 1435.94 | 2178.51 | 1605.82 | 0.00 | 0.00 | 0.00 |
May | 2794.81 | 1136.47 | 1658.34 | 2519.52 | 1398.47 | 0.00 | 0.00 | 0.00 |
June | 3018.10 | 1242.44 | 1775.66 | 3023.29 | 1114.71 | 0.00 | 0.00 | 0.00 |
July | 3073.80 | 1355.25 | 1718.55 | 3271.87 | 1037.06 | 0.00 | 0.00 | 0.00 |
August | 2581.79 | 1117.84 | 1463.94 | 2791.92 | 1105.60 | 0.00 | 0.00 | 0.00 |
September | 2071.28 | 928.81 | 1142.47 | 2152.07 | 1363.68 | 0.00 | 0.00 | 0.00 |
October | 1104.95 | 397.33 | 707.61 | 847.58 | 1777.53 | 0.00 | 0.00 | 0.00 |
November | 597.96 | 174.55 | 423.41 | 292.77 | 2188.77 | 0.00 | 0.00 | 0.00 |
December | 338.46 | 71.42 | 267.04 | 92.60 | 2704.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1728.50 | 687.22 | 1041.28 | 1558.31 | 1742.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 338.46 | 71.42 | 267.04 | 92.60 | 1037.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3073.80 | 1355.25 | 1775.66 | 3271.87 | 2704.96 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.254933E+09 | 0.00 | 0.254933E+09 | 151228.21 | 0.242595E+10 |
February | 0.359564E+09 | 0.00 | 0.359564E+09 | 3004581.18 | 0.207628E+10 |
March | 0.550885E+09 | 0.00 | 0.550885E+09 | 46118245.79 | 0.191179E+10 |
April | 0.867992E+09 | 3884768.92 | 0.864107E+09 | 0.339220E+09 | 0.143969E+10 |
May | 0.112139E+10 | 54101424.37 | 0.106728E+10 | 0.439521E+09 | 0.117759E+10 |
June | 0.119963E+10 | 75224754.64 | 0.112441E+10 | 0.745960E+09 | 0.867980E+09 |
July | 0.117585E+10 | 67041293.87 | 0.110881E+10 | 0.810080E+09 | 0.833692E+09 |
August | 0.924276E+09 | 14481121.60 | 0.909795E+09 | 0.618602E+09 | 0.946797E+09 |
September | 0.680808E+09 | 150649.08 | 0.680657E+09 | 0.360988E+09 | 0.119959E+10 |
October | 0.450799E+09 | 0.00 | 0.450799E+09 | 68178589.86 | 0.174535E+10 |
November | 0.262126E+09 | 0.00 | 0.262126E+09 | 499566.04 | 0.214480E+10 |
December | 0.184457E+09 | 0.00 | 0.184457E+09 | 0.00 | 0.263879E+10 |
Annual Sum or Average | 0.803271E+10 | 0.214884E+09 | 0.781782E+10 | 0.343232E+10 | 0.194083E+11 |
Minimum of Months | 0.184457E+09 | 0.00 | 0.184457E+09 | 0.00 | 0.833692E+09 |
Maximum of Months | 0.119963E+10 | 75224754.64 | 0.112441E+10 | 0.810080E+09 | 0.263879E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.254933E+09 | 0.00 | 0.254933E+09 | 151222.69 | 0.242595E+10 |
February | 0.359564E+09 | 0.00 | 0.359564E+09 | 3004557.59 | 0.207628E+10 |
March | 0.550884E+09 | 0.00 | 0.550884E+09 | 46118014.06 | 0.191179E+10 |
April | 0.867991E+09 | 3884764.26 | 0.864106E+09 | 0.339219E+09 | 0.143969E+10 |
May | 0.112138E+10 | 54101359.45 | 0.106728E+10 | 0.439520E+09 | 0.117759E+10 |
June | 0.119963E+10 | 75224664.38 | 0.112441E+10 | 0.745958E+09 | 0.867980E+09 |
July | 0.117585E+10 | 67041213.43 | 0.110881E+10 | 0.810079E+09 | 0.833692E+09 |
August | 0.924276E+09 | 14481104.22 | 0.909795E+09 | 0.618601E+09 | 0.946797E+09 |
September | 0.680807E+09 | 150648.89 | 0.680657E+09 | 0.360987E+09 | 0.119959E+10 |
October | 0.450798E+09 | 0.00 | 0.450798E+09 | 68178384.40 | 0.174535E+10 |
November | 0.262125E+09 | 0.00 | 0.262125E+09 | 499558.06 | 0.214480E+10 |
December | 0.184457E+09 | 0.00 | 0.184457E+09 | 0.00 | 0.263879E+10 |
Annual Sum or Average | 0.803270E+10 | 0.214884E+09 | 0.781781E+10 | 0.343232E+10 | 0.194083E+11 |
Minimum of Months | 0.184457E+09 | 0.00 | 0.184457E+09 | 0.00 | 0.833692E+09 |
Maximum of Months | 0.119963E+10 | 75224664.38 | 0.112441E+10 | 0.810079E+09 | 0.263879E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.254933E+09 | 0.00 | 0.254933E+09 | 151228.21 | 0.242595E+10 |
February | 0.359564E+09 | 0.00 | 0.359564E+09 | 3004581.18 | 0.207628E+10 |
March | 0.550885E+09 | 0.00 | 0.550885E+09 | 46118245.79 | 0.191179E+10 |
April | 0.867992E+09 | 3884768.92 | 0.864107E+09 | 0.339220E+09 | 0.143969E+10 |
May | 0.112139E+10 | 54101424.37 | 0.106728E+10 | 0.439521E+09 | 0.117759E+10 |
June | 0.119963E+10 | 75224754.64 | 0.112441E+10 | 0.745960E+09 | 0.867980E+09 |
July | 0.117585E+10 | 67041293.87 | 0.110881E+10 | 0.810080E+09 | 0.833692E+09 |
August | 0.924276E+09 | 14481121.60 | 0.909795E+09 | 0.618602E+09 | 0.946797E+09 |
September | 0.680808E+09 | 150649.08 | 0.680657E+09 | 0.360988E+09 | 0.119959E+10 |
October | 0.450799E+09 | 0.00 | 0.450799E+09 | 68178589.86 | 0.174535E+10 |
November | 0.262126E+09 | 0.00 | 0.262126E+09 | 499566.04 | 0.214480E+10 |
December | 0.184457E+09 | 0.00 | 0.184457E+09 | 0.00 | 0.263879E+10 |
Annual Sum or Average | 0.803271E+10 | 0.214884E+09 | 0.781782E+10 | 0.343232E+10 | 0.194083E+11 |
Minimum of Months | 0.184457E+09 | 0.00 | 0.184457E+09 | 0.00 | 0.833692E+09 |
Maximum of Months | 0.119963E+10 | 75224754.64 | 0.112441E+10 | 0.810080E+09 | 0.263879E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.254933E+09 | 0.00 | 0.254933E+09 | 151222.69 | 0.242595E+10 |
February | 0.359564E+09 | 0.00 | 0.359564E+09 | 3004557.59 | 0.207628E+10 |
March | 0.550884E+09 | 0.00 | 0.550884E+09 | 46118014.06 | 0.191179E+10 |
April | 0.867991E+09 | 3884764.26 | 0.864106E+09 | 0.339219E+09 | 0.143969E+10 |
May | 0.112138E+10 | 54101359.45 | 0.106728E+10 | 0.439520E+09 | 0.117759E+10 |
June | 0.119963E+10 | 75224664.38 | 0.112441E+10 | 0.745958E+09 | 0.867980E+09 |
July | 0.117585E+10 | 67041213.43 | 0.110881E+10 | 0.810079E+09 | 0.833692E+09 |
August | 0.924276E+09 | 14481104.22 | 0.909795E+09 | 0.618601E+09 | 0.946797E+09 |
September | 0.680807E+09 | 150648.89 | 0.680657E+09 | 0.360987E+09 | 0.119959E+10 |
October | 0.450798E+09 | 0.00 | 0.450798E+09 | 68178384.40 | 0.174535E+10 |
November | 0.262125E+09 | 0.00 | 0.262125E+09 | 499558.06 | 0.214480E+10 |
December | 0.184457E+09 | 0.00 | 0.184457E+09 | 0.00 | 0.263879E+10 |
Annual Sum or Average | 0.803270E+10 | 0.214884E+09 | 0.781781E+10 | 0.343232E+10 | 0.194083E+11 |
Minimum of Months | 0.184457E+09 | 0.00 | 0.184457E+09 | 0.00 | 0.833692E+09 |
Maximum of Months | 0.119963E+10 | 75224664.38 | 0.112441E+10 | 0.810079E+09 | 0.263879E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.254923E+09 | 0.00 | 0.254923E+09 | 151222.11 | 0.242585E+10 |
February | 0.359550E+09 | 0.00 | 0.359550E+09 | 3004460.08 | 0.207620E+10 |
March | 0.550863E+09 | 0.00 | 0.550863E+09 | 46116387.02 | 0.191171E+10 |
April | 0.867957E+09 | 3884612.35 | 0.864072E+09 | 0.339206E+09 | 0.143963E+10 |
May | 0.112134E+10 | 54099243.84 | 0.106724E+10 | 0.439503E+09 | 0.117754E+10 |
June | 0.119958E+10 | 75221722.76 | 0.112436E+10 | 0.745929E+09 | 0.867945E+09 |
July | 0.117580E+10 | 67038591.81 | 0.110876E+10 | 0.810047E+09 | 0.833658E+09 |
August | 0.924239E+09 | 14480537.94 | 0.909759E+09 | 0.618577E+09 | 0.946759E+09 |
September | 0.680780E+09 | 150643.00 | 0.680630E+09 | 0.360973E+09 | 0.119954E+10 |
October | 0.450780E+09 | 0.00 | 0.450780E+09 | 68175841.96 | 0.174527E+10 |
November | 0.262115E+09 | 0.00 | 0.262115E+09 | 499545.90 | 0.214471E+10 |
December | 0.184450E+09 | 0.00 | 0.184450E+09 | 0.00 | 0.263869E+10 |
Annual Sum or Average | 0.803238E+10 | 0.214875E+09 | 0.781751E+10 | 0.343218E+10 | 0.194075E+11 |
Minimum of Months | 0.184450E+09 | 0.00 | 0.184450E+09 | 0.00 | 0.833658E+09 |
Maximum of Months | 0.119958E+10 | 75221722.76 | 0.112436E+10 | 0.810047E+09 | 0.263869E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.578967E+09 | 0.232572E+09 | 0.346395E+09 | 0.240906E+09 | 0.245036E+10 |
February | 0.779791E+09 | 0.288061E+09 | 0.491731E+09 | 0.382505E+09 | 0.210117E+10 |
March | 0.902210E+09 | 0.177793E+09 | 0.724417E+09 | 0.359880E+09 | 0.190524E+10 |
April | 0.234436E+10 | 0.110163E+10 | 0.124273E+10 | 0.217088E+10 | 0.141711E+10 |
May | 0.254719E+10 | 0.111079E+10 | 0.143640E+10 | 0.228243E+10 | 0.126503E+10 |
June | 0.243992E+10 | 0.974480E+09 | 0.146544E+10 | 0.240239E+10 | 0.939806E+09 |
July | 0.257370E+10 | 0.109382E+10 | 0.147988E+10 | 0.268458E+10 | 0.895017E+09 |
August | 0.243802E+10 | 0.116486E+10 | 0.127316E+10 | 0.264249E+10 | 0.963586E+09 |
September | 0.212470E+10 | 0.112982E+10 | 0.994879E+09 | 0.219574E+10 | 0.119432E+10 |
October | 0.105981E+10 | 0.439211E+09 | 0.620595E+09 | 0.772708E+09 | 0.176919E+10 |
November | 0.534685E+09 | 0.182228E+09 | 0.352457E+09 | 0.218739E+09 | 0.215050E+10 |
December | 0.409476E+09 | 0.152237E+09 | 0.257238E+09 | 0.137006E+09 | 0.267594E+10 |
Annual Sum or Average | 0.187328E+11 | 0.804750E+10 | 0.106853E+11 | 0.164902E+11 | 0.197273E+11 |
Minimum of Months | 0.409476E+09 | 0.152237E+09 | 0.257238E+09 | 0.137006E+09 | 0.895017E+09 |
Maximum of Months | 0.257370E+10 | 0.116486E+10 | 0.147988E+10 | 0.268458E+10 | 0.267594E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.578967E+09 | 0.232572E+09 | 0.346395E+09 | 0.240906E+09 | 0.245036E+10 |
February | 0.779791E+09 | 0.288061E+09 | 0.491731E+09 | 0.382505E+09 | 0.210117E+10 |
March | 0.902210E+09 | 0.177793E+09 | 0.724417E+09 | 0.359880E+09 | 0.190524E+10 |
April | 0.234436E+10 | 0.110163E+10 | 0.124273E+10 | 0.217088E+10 | 0.141711E+10 |
May | 0.254719E+10 | 0.111079E+10 | 0.143640E+10 | 0.228243E+10 | 0.126503E+10 |
June | 0.243992E+10 | 0.974480E+09 | 0.146544E+10 | 0.240239E+10 | 0.939806E+09 |
July | 0.257370E+10 | 0.109382E+10 | 0.147988E+10 | 0.268458E+10 | 0.895017E+09 |
August | 0.243802E+10 | 0.116486E+10 | 0.127316E+10 | 0.264249E+10 | 0.963586E+09 |
September | 0.212470E+10 | 0.112982E+10 | 0.994879E+09 | 0.219574E+10 | 0.119432E+10 |
October | 0.105981E+10 | 0.439211E+09 | 0.620595E+09 | 0.772708E+09 | 0.176919E+10 |
November | 0.534685E+09 | 0.182228E+09 | 0.352457E+09 | 0.218739E+09 | 0.215050E+10 |
December | 0.409476E+09 | 0.152237E+09 | 0.257238E+09 | 0.137006E+09 | 0.267594E+10 |
Annual Sum or Average | 0.187328E+11 | 0.804750E+10 | 0.106853E+11 | 0.164902E+11 | 0.197273E+11 |
Minimum of Months | 0.409476E+09 | 0.152237E+09 | 0.257238E+09 | 0.137006E+09 | 0.895017E+09 |
Maximum of Months | 0.257370E+10 | 0.116486E+10 | 0.147988E+10 | 0.268458E+10 | 0.267594E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.578956E+09 | 0.232568E+09 | 0.346389E+09 | 0.240901E+09 | 0.245031E+10 |
February | 0.779777E+09 | 0.288055E+09 | 0.491722E+09 | 0.382498E+09 | 0.210114E+10 |
March | 0.902193E+09 | 0.177789E+09 | 0.724404E+09 | 0.359873E+09 | 0.190521E+10 |
April | 0.234432E+10 | 0.110161E+10 | 0.124271E+10 | 0.217084E+10 | 0.141709E+10 |
May | 0.254714E+10 | 0.111077E+10 | 0.143638E+10 | 0.228239E+10 | 0.126501E+10 |
June | 0.243988E+10 | 0.974463E+09 | 0.146541E+10 | 0.240235E+10 | 0.939789E+09 |
July | 0.257365E+10 | 0.109380E+10 | 0.147985E+10 | 0.268453E+10 | 0.895000E+09 |
August | 0.243797E+10 | 0.116484E+10 | 0.127313E+10 | 0.264244E+10 | 0.963568E+09 |
September | 0.212466E+10 | 0.112980E+10 | 0.994861E+09 | 0.219570E+10 | 0.119430E+10 |
October | 0.105979E+10 | 0.439203E+09 | 0.620583E+09 | 0.772694E+09 | 0.176916E+10 |
November | 0.534676E+09 | 0.182225E+09 | 0.352450E+09 | 0.218735E+09 | 0.215046E+10 |
December | 0.409468E+09 | 0.152235E+09 | 0.257234E+09 | 0.137003E+09 | 0.267589E+10 |
Annual Sum or Average | 0.187325E+11 | 0.804735E+10 | 0.106851E+11 | 0.164899E+11 | 0.197269E+11 |
Minimum of Months | 0.409468E+09 | 0.152235E+09 | 0.257234E+09 | 0.137003E+09 | 0.895000E+09 |
Maximum of Months | 0.257365E+10 | 0.116484E+10 | 0.147985E+10 | 0.268453E+10 | 0.267589E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144734E+10 | 0.936921E+09 | 0.510417E+09 | 0.125895E+10 | 0.200584E+10 |
February | 0.159659E+10 | 0.974263E+09 | 0.622330E+09 | 0.144156E+10 | 0.178403E+10 |
March | 0.109288E+10 | 0.318198E+09 | 0.774684E+09 | 0.703247E+09 | 0.168821E+10 |
April | 0.219625E+10 | 0.992680E+09 | 0.120357E+10 | 0.228563E+10 | 0.138797E+10 |
May | 0.187705E+10 | 0.611107E+09 | 0.126595E+10 | 0.175875E+10 | 0.124836E+10 |
June | 0.167339E+10 | 0.405057E+09 | 0.126833E+10 | 0.165224E+10 | 0.922229E+09 |
July | 0.187352E+10 | 0.586714E+09 | 0.128681E+10 | 0.204382E+10 | 0.889551E+09 |
August | 0.219535E+10 | 0.987552E+09 | 0.120780E+10 | 0.258871E+10 | 0.961573E+09 |
September | 0.251065E+10 | 0.147078E+10 | 0.103987E+10 | 0.294986E+10 | 0.115316E+10 |
October | 0.178242E+10 | 0.104174E+10 | 0.740674E+09 | 0.180721E+10 | 0.157519E+10 |
November | 0.122297E+10 | 0.743962E+09 | 0.479005E+09 | 0.107887E+10 | 0.183961E+10 |
December | 0.100162E+10 | 0.641745E+09 | 0.359879E+09 | 0.836128E+09 | 0.229520E+10 |
Annual Sum or Average | 0.204700E+11 | 0.971072E+10 | 0.107593E+11 | 0.204050E+11 | 0.177509E+11 |
Minimum of Months | 0.100162E+10 | 0.318198E+09 | 0.359879E+09 | 0.703247E+09 | 0.889551E+09 |
Maximum of Months | 0.251065E+10 | 0.147078E+10 | 0.128681E+10 | 0.294986E+10 | 0.229520E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144734E+10 | 0.936920E+09 | 0.510416E+09 | 0.125894E+10 | 0.200584E+10 |
February | 0.159659E+10 | 0.974262E+09 | 0.622330E+09 | 0.144156E+10 | 0.178403E+10 |
March | 0.109288E+10 | 0.318198E+09 | 0.774683E+09 | 0.703246E+09 | 0.168821E+10 |
April | 0.219625E+10 | 0.992678E+09 | 0.120357E+10 | 0.228563E+10 | 0.138797E+10 |
May | 0.187705E+10 | 0.611107E+09 | 0.126594E+10 | 0.175874E+10 | 0.124836E+10 |
June | 0.167339E+10 | 0.405057E+09 | 0.126833E+10 | 0.165224E+10 | 0.922229E+09 |
July | 0.187352E+10 | 0.586713E+09 | 0.128681E+10 | 0.204382E+10 | 0.889551E+09 |
August | 0.219535E+10 | 0.987551E+09 | 0.120780E+10 | 0.258871E+10 | 0.961573E+09 |
September | 0.251064E+10 | 0.147078E+10 | 0.103987E+10 | 0.294985E+10 | 0.115316E+10 |
October | 0.178241E+10 | 0.104174E+10 | 0.740673E+09 | 0.180721E+10 | 0.157519E+10 |
November | 0.122297E+10 | 0.743961E+09 | 0.479004E+09 | 0.107887E+10 | 0.183961E+10 |
December | 0.100162E+10 | 0.641744E+09 | 0.359878E+09 | 0.836127E+09 | 0.229520E+10 |
Annual Sum or Average | 0.204700E+11 | 0.971071E+10 | 0.107593E+11 | 0.204050E+11 | 0.177509E+11 |
Minimum of Months | 0.100162E+10 | 0.318198E+09 | 0.359878E+09 | 0.703246E+09 | 0.889551E+09 |
Maximum of Months | 0.251064E+10 | 0.147078E+10 | 0.128681E+10 | 0.294985E+10 | 0.229520E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144734E+10 | 0.936921E+09 | 0.510417E+09 | 0.125895E+10 | 0.200584E+10 |
February | 0.159659E+10 | 0.974263E+09 | 0.622330E+09 | 0.144156E+10 | 0.178403E+10 |
March | 0.109288E+10 | 0.318198E+09 | 0.774684E+09 | 0.703247E+09 | 0.168821E+10 |
April | 0.219625E+10 | 0.992680E+09 | 0.120357E+10 | 0.228563E+10 | 0.138797E+10 |
May | 0.187705E+10 | 0.611107E+09 | 0.126595E+10 | 0.175875E+10 | 0.124836E+10 |
June | 0.167339E+10 | 0.405057E+09 | 0.126833E+10 | 0.165224E+10 | 0.922229E+09 |
July | 0.187352E+10 | 0.586714E+09 | 0.128681E+10 | 0.204382E+10 | 0.889551E+09 |
August | 0.219535E+10 | 0.987552E+09 | 0.120780E+10 | 0.258871E+10 | 0.961573E+09 |
September | 0.251065E+10 | 0.147078E+10 | 0.103987E+10 | 0.294986E+10 | 0.115316E+10 |
October | 0.178242E+10 | 0.104174E+10 | 0.740674E+09 | 0.180721E+10 | 0.157519E+10 |
November | 0.122297E+10 | 0.743962E+09 | 0.479005E+09 | 0.107887E+10 | 0.183961E+10 |
December | 0.100162E+10 | 0.641745E+09 | 0.359879E+09 | 0.836128E+09 | 0.229520E+10 |
Annual Sum or Average | 0.204700E+11 | 0.971072E+10 | 0.107593E+11 | 0.204050E+11 | 0.177509E+11 |
Minimum of Months | 0.100162E+10 | 0.318198E+09 | 0.359879E+09 | 0.703247E+09 | 0.889551E+09 |
Maximum of Months | 0.251065E+10 | 0.147078E+10 | 0.128681E+10 | 0.294986E+10 | 0.229520E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144734E+10 | 0.936920E+09 | 0.510416E+09 | 0.125894E+10 | 0.200584E+10 |
February | 0.159659E+10 | 0.974262E+09 | 0.622330E+09 | 0.144156E+10 | 0.178403E+10 |
March | 0.109288E+10 | 0.318198E+09 | 0.774683E+09 | 0.703246E+09 | 0.168821E+10 |
April | 0.219625E+10 | 0.992678E+09 | 0.120357E+10 | 0.228563E+10 | 0.138797E+10 |
May | 0.187705E+10 | 0.611107E+09 | 0.126594E+10 | 0.175874E+10 | 0.124836E+10 |
June | 0.167339E+10 | 0.405057E+09 | 0.126833E+10 | 0.165224E+10 | 0.922229E+09 |
July | 0.187352E+10 | 0.586713E+09 | 0.128681E+10 | 0.204382E+10 | 0.889551E+09 |
August | 0.219535E+10 | 0.987551E+09 | 0.120780E+10 | 0.258871E+10 | 0.961573E+09 |
September | 0.251064E+10 | 0.147078E+10 | 0.103987E+10 | 0.294985E+10 | 0.115316E+10 |
October | 0.178241E+10 | 0.104174E+10 | 0.740673E+09 | 0.180721E+10 | 0.157519E+10 |
November | 0.122297E+10 | 0.743961E+09 | 0.479004E+09 | 0.107887E+10 | 0.183961E+10 |
December | 0.100162E+10 | 0.641744E+09 | 0.359878E+09 | 0.836127E+09 | 0.229520E+10 |
Annual Sum or Average | 0.204700E+11 | 0.971071E+10 | 0.107593E+11 | 0.204050E+11 | 0.177509E+11 |
Minimum of Months | 0.100162E+10 | 0.318198E+09 | 0.359878E+09 | 0.703246E+09 | 0.889551E+09 |
Maximum of Months | 0.251064E+10 | 0.147078E+10 | 0.128681E+10 | 0.294985E+10 | 0.229520E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144728E+10 | 0.936884E+09 | 0.510396E+09 | 0.125890E+10 | 0.200576E+10 |
February | 0.159653E+10 | 0.974224E+09 | 0.622305E+09 | 0.144151E+10 | 0.178396E+10 |
March | 0.109284E+10 | 0.318185E+09 | 0.774653E+09 | 0.703219E+09 | 0.168814E+10 |
April | 0.219616E+10 | 0.992640E+09 | 0.120352E+10 | 0.228554E+10 | 0.138792E+10 |
May | 0.187698E+10 | 0.611083E+09 | 0.126589E+10 | 0.175868E+10 | 0.124831E+10 |
June | 0.167332E+10 | 0.405041E+09 | 0.126828E+10 | 0.165218E+10 | 0.922192E+09 |
July | 0.187344E+10 | 0.586690E+09 | 0.128675E+10 | 0.204374E+10 | 0.889515E+09 |
August | 0.219527E+10 | 0.987512E+09 | 0.120775E+10 | 0.258861E+10 | 0.961535E+09 |
September | 0.251055E+10 | 0.147072E+10 | 0.103983E+10 | 0.294974E+10 | 0.115312E+10 |
October | 0.178234E+10 | 0.104170E+10 | 0.740644E+09 | 0.180714E+10 | 0.157513E+10 |
November | 0.122292E+10 | 0.743932E+09 | 0.478985E+09 | 0.107883E+10 | 0.183954E+10 |
December | 0.100158E+10 | 0.641719E+09 | 0.359864E+09 | 0.836095E+09 | 0.229510E+10 |
Annual Sum or Average | 0.204692E+11 | 0.971033E+10 | 0.107589E+11 | 0.204042E+11 | 0.177502E+11 |
Minimum of Months | 0.100158E+10 | 0.318185E+09 | 0.359864E+09 | 0.703219E+09 | 0.889515E+09 |
Maximum of Months | 0.251055E+10 | 0.147072E+10 | 0.128675E+10 | 0.294974E+10 | 0.229510E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.563017E+09 | 0.186023E+09 | 0.376994E+09 | 0.235399E+09 | 0.260600E+10 |
February | 0.900380E+09 | 0.380169E+09 | 0.520211E+09 | 0.564925E+09 | 0.226992E+10 |
March | 0.901366E+09 | 0.172431E+09 | 0.728935E+09 | 0.333796E+09 | 0.212154E+10 |
April | 0.205820E+10 | 0.817534E+09 | 0.124066E+10 | 0.178775E+10 | 0.170390E+10 |
May | 0.249523E+10 | 0.101465E+10 | 0.148058E+10 | 0.220862E+10 | 0.144128E+10 |
June | 0.260766E+10 | 0.107347E+10 | 0.153419E+10 | 0.258244E+10 | 0.111075E+10 |
July | 0.274431E+10 | 0.120998E+10 | 0.153434E+10 | 0.286552E+10 | 0.110710E+10 |
August | 0.230504E+10 | 0.998018E+09 | 0.130702E+10 | 0.241504E+10 | 0.122578E+10 |
September | 0.178960E+10 | 0.802498E+09 | 0.987104E+09 | 0.180858E+10 | 0.138323E+10 |
October | 0.986506E+09 | 0.354743E+09 | 0.631763E+09 | 0.693847E+09 | 0.196696E+10 |
November | 0.516642E+09 | 0.150814E+09 | 0.365828E+09 | 0.217822E+09 | 0.240415E+10 |
December | 0.302182E+09 | 63767053.22 | 0.238415E+09 | 60151606.15 | 0.306585E+10 |
Annual Sum or Average | 0.181701E+11 | 0.722410E+10 | 0.109460E+11 | 0.157739E+11 | 0.224065E+11 |
Minimum of Months | 0.302182E+09 | 63767053.22 | 0.238415E+09 | 60151606.15 | 0.110710E+10 |
Maximum of Months | 0.274431E+10 | 0.120998E+10 | 0.153434E+10 | 0.286552E+10 | 0.306585E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.563017E+09 | 0.186023E+09 | 0.376994E+09 | 0.235399E+09 | 0.260600E+10 |
February | 0.900380E+09 | 0.380169E+09 | 0.520211E+09 | 0.564925E+09 | 0.226992E+10 |
March | 0.901366E+09 | 0.172431E+09 | 0.728935E+09 | 0.333796E+09 | 0.212154E+10 |
April | 0.205820E+10 | 0.817534E+09 | 0.124066E+10 | 0.178775E+10 | 0.170390E+10 |
May | 0.249523E+10 | 0.101465E+10 | 0.148058E+10 | 0.220862E+10 | 0.144128E+10 |
June | 0.260766E+10 | 0.107347E+10 | 0.153419E+10 | 0.258244E+10 | 0.111075E+10 |
July | 0.274431E+10 | 0.120998E+10 | 0.153434E+10 | 0.286552E+10 | 0.110710E+10 |
August | 0.230504E+10 | 0.998018E+09 | 0.130702E+10 | 0.241504E+10 | 0.122578E+10 |
September | 0.178960E+10 | 0.802498E+09 | 0.987104E+09 | 0.180858E+10 | 0.138323E+10 |
October | 0.986506E+09 | 0.354743E+09 | 0.631763E+09 | 0.693847E+09 | 0.196696E+10 |
November | 0.516642E+09 | 0.150814E+09 | 0.365828E+09 | 0.217822E+09 | 0.240415E+10 |
December | 0.302182E+09 | 63767053.22 | 0.238415E+09 | 60151606.15 | 0.306585E+10 |
Annual Sum or Average | 0.181701E+11 | 0.722410E+10 | 0.109460E+11 | 0.157739E+11 | 0.224065E+11 |
Minimum of Months | 0.302182E+09 | 63767053.22 | 0.238415E+09 | 60151606.15 | 0.110710E+10 |
Maximum of Months | 0.274431E+10 | 0.120998E+10 | 0.153434E+10 | 0.286552E+10 | 0.306585E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.563007E+09 | 0.186020E+09 | 0.376987E+09 | 0.235394E+09 | 0.260595E+10 |
February | 0.900364E+09 | 0.380163E+09 | 0.520201E+09 | 0.564915E+09 | 0.226988E+10 |
March | 0.901350E+09 | 0.172428E+09 | 0.728921E+09 | 0.333790E+09 | 0.212150E+10 |
April | 0.205816E+10 | 0.817519E+09 | 0.124064E+10 | 0.178772E+10 | 0.170387E+10 |
May | 0.249519E+10 | 0.101463E+10 | 0.148056E+10 | 0.220858E+10 | 0.144126E+10 |
June | 0.260761E+10 | 0.107346E+10 | 0.153416E+10 | 0.258239E+10 | 0.111073E+10 |
July | 0.274426E+10 | 0.120995E+10 | 0.153431E+10 | 0.286547E+10 | 0.110708E+10 |
August | 0.230500E+10 | 0.998000E+09 | 0.130700E+10 | 0.241500E+10 | 0.122576E+10 |
September | 0.178957E+10 | 0.802483E+09 | 0.987086E+09 | 0.180855E+10 | 0.138321E+10 |
October | 0.986488E+09 | 0.354737E+09 | 0.631751E+09 | 0.693834E+09 | 0.196693E+10 |
November | 0.516632E+09 | 0.150811E+09 | 0.365821E+09 | 0.217818E+09 | 0.240411E+10 |
December | 0.302177E+09 | 63765888.05 | 0.238411E+09 | 60150507.05 | 0.306580E+10 |
Annual Sum or Average | 0.181698E+11 | 0.722396E+10 | 0.109458E+11 | 0.157736E+11 | 0.224061E+11 |
Minimum of Months | 0.302177E+09 | 63765888.05 | 0.238411E+09 | 60150507.05 | 0.110708E+10 |
Maximum of Months | 0.274426E+10 | 0.120995E+10 | 0.153431E+10 | 0.286547E+10 | 0.306580E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127465E+10 | 0.00 | 0.127465E+10 | 8678650.34 | 0.110281E+11 |
February | 0.179780E+10 | 0.00 | 0.179780E+10 | 39193325.97 | 0.949655E+10 |
March | 0.275439E+10 | 0.00 | 0.275439E+10 | 0.327559E+09 | 0.867913E+10 |
April | 0.433991E+10 | 19423609.73 | 0.432048E+10 | 0.184727E+10 | 0.663017E+10 |
May | 0.560686E+10 | 0.270504E+09 | 0.533635E+10 | 0.233167E+10 | 0.552374E+10 |
June | 0.599809E+10 | 0.376119E+09 | 0.562197E+10 | 0.380242E+10 | 0.411987E+10 |
July | 0.587917E+10 | 0.335202E+09 | 0.554396E+10 | 0.420696E+10 | 0.387805E+10 |
August | 0.462133E+10 | 72404732.46 | 0.454892E+10 | 0.324167E+10 | 0.431896E+10 |
September | 0.340400E+10 | 753236.27 | 0.340324E+10 | 0.193715E+10 | 0.557101E+10 |
October | 0.225397E+10 | 0.00 | 0.225397E+10 | 0.453307E+09 | 0.788925E+10 |
November | 0.131061E+10 | 0.00 | 0.131061E+10 | 15583391.57 | 0.951223E+10 |
December | 0.922274E+09 | 0.00 | 0.922274E+09 | 0.00 | 0.117541E+11 |
Annual Sum or Average | 0.401630E+11 | 0.107441E+10 | 0.390886E+11 | 0.182115E+11 | 0.884012E+11 |
Minimum of Months | 0.922274E+09 | 0.00 | 0.922274E+09 | 0.00 | 0.387805E+10 |
Maximum of Months | 0.599809E+10 | 0.376119E+09 | 0.562197E+10 | 0.420696E+10 | 0.117541E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173688E+10 | 0.697709E+09 | 0.103917E+10 | 0.759109E+09 | 0.688258E+10 |
February | 0.233935E+10 | 0.864173E+09 | 0.147518E+10 | 0.118179E+10 | 0.598629E+10 |
March | 0.270660E+10 | 0.533372E+09 | 0.217323E+10 | 0.108978E+10 | 0.540681E+10 |
April | 0.703301E+10 | 0.330486E+10 | 0.372815E+10 | 0.646270E+10 | 0.409001E+10 |
May | 0.764149E+10 | 0.333232E+10 | 0.430917E+10 | 0.676393E+10 | 0.365542E+10 |
June | 0.731969E+10 | 0.292341E+10 | 0.439628E+10 | 0.712622E+10 | 0.271488E+10 |
July | 0.772102E+10 | 0.328143E+10 | 0.443959E+10 | 0.798592E+10 | 0.256372E+10 |
August | 0.731398E+10 | 0.349455E+10 | 0.381943E+10 | 0.787520E+10 | 0.274573E+10 |
September | 0.637402E+10 | 0.338941E+10 | 0.298461E+10 | 0.653190E+10 | 0.343504E+10 |
October | 0.317938E+10 | 0.131762E+10 | 0.186177E+10 | 0.232392E+10 | 0.500105E+10 |
November | 0.160404E+10 | 0.546680E+09 | 0.105736E+10 | 0.687369E+09 | 0.599891E+10 |
December | 0.122841E+10 | 0.456707E+09 | 0.771708E+09 | 0.451259E+09 | 0.743134E+10 |
Annual Sum or Average | 0.561979E+11 | 0.241423E+11 | 0.320556E+11 | 0.492391E+11 | 0.559118E+11 |
Minimum of Months | 0.122841E+10 | 0.456707E+09 | 0.771708E+09 | 0.451259E+09 | 0.256372E+10 |
Maximum of Months | 0.772102E+10 | 0.349455E+10 | 0.443959E+10 | 0.798592E+10 | 0.743134E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723660E+10 | 0.468455E+10 | 0.255205E+10 | 0.628232E+10 | 0.983214E+10 |
February | 0.798287E+10 | 0.487126E+10 | 0.311161E+10 | 0.715602E+10 | 0.883489E+10 |
March | 0.546434E+10 | 0.159097E+10 | 0.387337E+10 | 0.352302E+10 | 0.820350E+10 |
April | 0.109811E+11 | 0.496334E+10 | 0.601778E+10 | 0.113593E+11 | 0.679686E+10 |
May | 0.938515E+10 | 0.305550E+10 | 0.632965E+10 | 0.872204E+10 | 0.614002E+10 |
June | 0.836684E+10 | 0.202526E+10 | 0.634157E+10 | 0.823602E+10 | 0.448439E+10 |
July | 0.936749E+10 | 0.293353E+10 | 0.643395E+10 | 0.102154E+11 | 0.426744E+10 |
August | 0.109766E+11 | 0.493770E+10 | 0.603894E+10 | 0.129203E+11 | 0.459642E+10 |
September | 0.125531E+11 | 0.735381E+10 | 0.519928E+10 | 0.146276E+11 | 0.570103E+10 |
October | 0.891197E+10 | 0.520865E+10 | 0.370333E+10 | 0.897557E+10 | 0.774155E+10 |
November | 0.611476E+10 | 0.371976E+10 | 0.239500E+10 | 0.538665E+10 | 0.891673E+10 |
December | 0.500806E+10 | 0.320869E+10 | 0.179937E+10 | 0.421581E+10 | 0.110532E+11 |
Annual Sum or Average | 0.102349E+12 | 0.485530E+11 | 0.537959E+11 | 0.101620E+12 | 0.865681E+11 |
Minimum of Months | 0.500806E+10 | 0.159097E+10 | 0.179937E+10 | 0.352302E+10 | 0.426744E+10 |
Maximum of Months | 0.125531E+11 | 0.735381E+10 | 0.643395E+10 | 0.146276E+11 | 0.110532E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168903E+10 | 0.558064E+09 | 0.113097E+10 | 0.767228E+09 | 0.706060E+10 |
February | 0.270111E+10 | 0.114050E+10 | 0.156062E+10 | 0.176254E+10 | 0.618086E+10 |
March | 0.270407E+10 | 0.517289E+09 | 0.218678E+10 | 0.112963E+10 | 0.557796E+10 |
April | 0.617453E+10 | 0.245258E+10 | 0.372195E+10 | 0.559995E+10 | 0.448798E+10 |
May | 0.748562E+10 | 0.304391E+10 | 0.444171E+10 | 0.672082E+10 | 0.402187E+10 |
June | 0.782290E+10 | 0.322039E+10 | 0.460251E+10 | 0.784599E+10 | 0.305969E+10 |
July | 0.823286E+10 | 0.362989E+10 | 0.460297E+10 | 0.878591E+10 | 0.293899E+10 |
August | 0.691505E+10 | 0.299402E+10 | 0.392103E+10 | 0.748431E+10 | 0.314154E+10 |
September | 0.536875E+10 | 0.240747E+10 | 0.296128E+10 | 0.554823E+10 | 0.380002E+10 |
October | 0.295949E+10 | 0.106422E+10 | 0.189527E+10 | 0.219765E+10 | 0.526003E+10 |
November | 0.154991E+10 | 0.452438E+09 | 0.109747E+10 | 0.725044E+09 | 0.625935E+10 |
December | 0.906538E+09 | 0.191299E+09 | 0.715238E+09 | 0.227158E+09 | 0.788750E+10 |
Annual Sum or Average | 0.545099E+11 | 0.216721E+11 | 0.328378E+11 | 0.487945E+11 | 0.596764E+11 |
Minimum of Months | 0.906538E+09 | 0.191299E+09 | 0.715238E+09 | 0.227158E+09 | 0.293899E+10 |
Maximum of Months | 0.823286E+10 | 0.362989E+10 | 0.460297E+10 | 0.878591E+10 | 0.788750E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127465E+10 | 0.00 | 0.127465E+10 | 36708580.21 | 0.984489E+10 |
February | 0.179780E+10 | 0.00 | 0.179780E+10 | 0.106516E+09 | 0.845108E+10 |
March | 0.275439E+10 | 0.00 | 0.275439E+10 | 0.482395E+09 | 0.769906E+10 |
April | 0.433991E+10 | 19423609.73 | 0.432048E+10 | 0.205788E+10 | 0.596484E+10 |
May | 0.560686E+10 | 0.270504E+09 | 0.533635E+10 | 0.258103E+10 | 0.497671E+10 |
June | 0.599809E+10 | 0.376119E+09 | 0.562197E+10 | 0.397061E+10 | 0.379903E+10 |
July | 0.587917E+10 | 0.335202E+09 | 0.554396E+10 | 0.435341E+10 | 0.358755E+10 |
August | 0.462133E+10 | 72404732.46 | 0.454892E+10 | 0.337585E+10 | 0.395425E+10 |
September | 0.340400E+10 | 753236.27 | 0.340324E+10 | 0.213544E+10 | 0.499180E+10 |
October | 0.225397E+10 | 0.00 | 0.225397E+10 | 0.649454E+09 | 0.683101E+10 |
November | 0.131061E+10 | 0.00 | 0.131061E+10 | 50699451.82 | 0.832124E+10 |
December | 0.922274E+09 | 0.00 | 0.922274E+09 | 2124561.62 | 0.105970E+11 |
Annual Sum or Average | 0.401630E+11 | 0.107441E+10 | 0.390886E+11 | 0.198021E+11 | 0.790185E+11 |
Minimum of Months | 0.922274E+09 | 0.00 | 0.922274E+09 | 2124561.62 | 0.358755E+10 |
Maximum of Months | 0.599809E+10 | 0.376119E+09 | 0.562197E+10 | 0.435341E+10 | 0.105970E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173688E+10 | 0.697709E+09 | 0.103917E+10 | 0.841363E+09 | 0.613264E+10 |
February | 0.233935E+10 | 0.864173E+09 | 0.147518E+10 | 0.129171E+10 | 0.533109E+10 |
March | 0.270660E+10 | 0.533372E+09 | 0.217323E+10 | 0.126154E+10 | 0.482508E+10 |
April | 0.703301E+10 | 0.330486E+10 | 0.372815E+10 | 0.660838E+10 | 0.375870E+10 |
May | 0.764149E+10 | 0.333232E+10 | 0.430917E+10 | 0.690587E+10 | 0.338459E+10 |
June | 0.731969E+10 | 0.292341E+10 | 0.439628E+10 | 0.719668E+10 | 0.256222E+10 |
July | 0.772102E+10 | 0.328143E+10 | 0.443959E+10 | 0.802583E+10 | 0.242930E+10 |
August | 0.731398E+10 | 0.349455E+10 | 0.381943E+10 | 0.792267E+10 | 0.259135E+10 |
September | 0.637402E+10 | 0.338941E+10 | 0.298461E+10 | 0.663700E+10 | 0.317445E+10 |
October | 0.317938E+10 | 0.131762E+10 | 0.186177E+10 | 0.250460E+10 | 0.437963E+10 |
November | 0.160404E+10 | 0.546680E+09 | 0.105736E+10 | 0.766134E+09 | 0.526046E+10 |
December | 0.122841E+10 | 0.456707E+09 | 0.771708E+09 | 0.507051E+09 | 0.670103E+10 |
Annual Sum or Average | 0.561979E+11 | 0.241423E+11 | 0.320556E+11 | 0.504688E+11 | 0.505305E+11 |
Minimum of Months | 0.122841E+10 | 0.456707E+09 | 0.771708E+09 | 0.507051E+09 | 0.242930E+10 |
Maximum of Months | 0.772102E+10 | 0.349455E+10 | 0.443959E+10 | 0.802583E+10 | 0.670103E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723660E+10 | 0.468455E+10 | 0.255205E+10 | 0.650665E+10 | 0.876887E+10 |
February | 0.798287E+10 | 0.487126E+10 | 0.311161E+10 | 0.736097E+10 | 0.793458E+10 |
March | 0.546434E+10 | 0.159097E+10 | 0.387337E+10 | 0.372456E+10 | 0.737585E+10 |
April | 0.109811E+11 | 0.496334E+10 | 0.601778E+10 | 0.114850E+11 | 0.624011E+10 |
May | 0.938515E+10 | 0.305550E+10 | 0.632965E+10 | 0.882514E+10 | 0.566293E+10 |
June | 0.836684E+10 | 0.202526E+10 | 0.634157E+10 | 0.827498E+10 | 0.420843E+10 |
July | 0.936749E+10 | 0.293353E+10 | 0.643395E+10 | 0.102310E+11 | 0.400914E+10 |
August | 0.109766E+11 | 0.493770E+10 | 0.603894E+10 | 0.129433E+11 | 0.430619E+10 |
September | 0.125531E+11 | 0.735381E+10 | 0.519928E+10 | 0.147085E+11 | 0.525705E+10 |
October | 0.891197E+10 | 0.520865E+10 | 0.370333E+10 | 0.916835E+10 | 0.685921E+10 |
November | 0.611476E+10 | 0.371976E+10 | 0.239500E+10 | 0.555404E+10 | 0.789878E+10 |
December | 0.500806E+10 | 0.320869E+10 | 0.179937E+10 | 0.437561E+10 | 0.997382E+10 |
Annual Sum or Average | 0.102349E+12 | 0.485530E+11 | 0.537959E+11 | 0.103158E+12 | 0.784950E+11 |
Minimum of Months | 0.500806E+10 | 0.159097E+10 | 0.179937E+10 | 0.372456E+10 | 0.400914E+10 |
Maximum of Months | 0.125531E+11 | 0.735381E+10 | 0.643395E+10 | 0.147085E+11 | 0.997382E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168903E+10 | 0.558064E+09 | 0.113097E+10 | 0.812733E+09 | 0.643378E+10 |
February | 0.270111E+10 | 0.114050E+10 | 0.156062E+10 | 0.181601E+10 | 0.565082E+10 |
March | 0.270407E+10 | 0.517289E+09 | 0.218678E+10 | 0.118643E+10 | 0.510689E+10 |
April | 0.617453E+10 | 0.245258E+10 | 0.372195E+10 | 0.564670E+10 | 0.416228E+10 |
May | 0.748562E+10 | 0.304391E+10 | 0.444171E+10 | 0.674828E+10 | 0.374565E+10 |
June | 0.782290E+10 | 0.322039E+10 | 0.460251E+10 | 0.783638E+10 | 0.288932E+10 |
July | 0.823286E+10 | 0.362989E+10 | 0.460297E+10 | 0.876336E+10 | 0.277766E+10 |
August | 0.691505E+10 | 0.299402E+10 | 0.392103E+10 | 0.747787E+10 | 0.296125E+10 |
September | 0.536875E+10 | 0.240747E+10 | 0.296128E+10 | 0.557816E+10 | 0.353466E+10 |
October | 0.295949E+10 | 0.106422E+10 | 0.189527E+10 | 0.227016E+10 | 0.476094E+10 |
November | 0.154991E+10 | 0.452438E+09 | 0.109747E+10 | 0.758872E+09 | 0.567330E+10 |
December | 0.906538E+09 | 0.191299E+09 | 0.715238E+09 | 0.248014E+09 | 0.724497E+10 |
Annual Sum or Average | 0.545099E+11 | 0.216721E+11 | 0.328378E+11 | 0.491430E+11 | 0.549415E+11 |
Minimum of Months | 0.906538E+09 | 0.191299E+09 | 0.715238E+09 | 0.248014E+09 | 0.277766E+10 |
Maximum of Months | 0.823286E+10 | 0.362989E+10 | 0.460297E+10 | 0.876336E+10 | 0.724497E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.28 | 4528.70 | 475.90 | 0.00 | 475.90 | 0.00 | 0.00 |
February | 6.21 | 4291.22 | 743.14 | 0.00 | 743.14 | 0.00 | 0.00 |
March | 86.09 | 3568.87 | 1028.38 | 0.00 | 1028.38 | 0.00 | 0.00 |
April | 654.35 | 2777.15 | 1674.35 | 7.49 | 1666.86 | 0.00 | 0.00 |
May | 820.48 | 2198.29 | 2093.37 | 100.99 | 1992.37 | 0.00 | 0.00 |
June | 1438.95 | 1674.33 | 2314.09 | 145.11 | 2168.98 | 0.00 | 0.00 |
July | 1512.23 | 1556.31 | 2195.04 | 125.15 | 2069.89 | 0.00 | 0.00 |
August | 1154.79 | 1767.45 | 1725.41 | 27.03 | 1698.38 | 0.00 | 0.00 |
September | 696.34 | 2314.01 | 1313.28 | 0.29 | 1312.98 | 0.00 | 0.00 |
October | 127.27 | 3258.16 | 841.54 | 0.00 | 841.54 | 0.00 | 0.00 |
November | 0.96 | 4137.31 | 505.64 | 0.00 | 505.64 | 0.00 | 0.00 |
December | 0.00 | 4926.02 | 344.34 | 0.00 | 344.34 | 0.00 | 0.00 |
Annual Sum or Average | 544.19 | 3077.14 | 1273.57 | 34.07 | 1239.50 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 1556.31 | 344.34 | 0.00 | 344.34 | 0.00 | 0.00 |
Maximum of Months | 1512.23 | 4926.02 | 2314.09 | 145.11 | 2168.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 269.83 | 2744.56 | 648.48 | 260.50 | 387.98 | 0.00 | 0.00 |
February | 474.33 | 2605.61 | 967.00 | 357.22 | 609.78 | 0.00 | 0.00 |
March | 403.09 | 2134.00 | 1010.53 | 199.14 | 811.39 | 0.00 | 0.00 |
April | 2512.57 | 1640.17 | 2713.36 | 1275.03 | 1438.34 | 0.00 | 0.00 |
May | 2556.47 | 1416.92 | 2853.02 | 1244.15 | 1608.87 | 0.00 | 0.00 |
June | 2780.53 | 1087.73 | 2823.97 | 1127.86 | 1696.10 | 0.00 | 0.00 |
July | 3006.90 | 1002.48 | 2882.71 | 1225.15 | 1657.56 | 0.00 | 0.00 |
August | 2959.76 | 1079.28 | 2730.74 | 1304.72 | 1426.02 | 0.00 | 0.00 |
September | 2541.35 | 1382.30 | 2459.12 | 1307.65 | 1151.47 | 0.00 | 0.00 |
October | 865.48 | 1981.61 | 1187.05 | 491.94 | 695.11 | 0.00 | 0.00 |
November | 253.17 | 2488.99 | 618.84 | 210.91 | 407.93 | 0.00 | 0.00 |
December | 153.46 | 2997.23 | 458.64 | 170.52 | 288.12 | 0.00 | 0.00 |
Annual Sum or Average | 1568.70 | 1876.63 | 1782.03 | 765.55 | 1016.48 | 0.00 | 0.00 |
Minimum of Months | 153.46 | 1002.48 | 458.64 | 170.52 | 288.12 | 0.00 | 0.00 |
Maximum of Months | 3006.90 | 2997.23 | 2882.71 | 1307.65 | 1696.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2350.16 | 3744.45 | 2701.85 | 1749.02 | 952.83 | 0.00 | 0.00 |
February | 2979.40 | 3687.21 | 3299.81 | 2013.59 | 1286.22 | 0.00 | 0.00 |
March | 1312.80 | 3151.50 | 2040.16 | 594.00 | 1446.16 | 0.00 | 0.00 |
April | 4408.98 | 2677.40 | 4236.56 | 1914.87 | 2321.68 | 0.00 | 0.00 |
May | 3283.18 | 2330.41 | 3504.03 | 1140.80 | 2363.23 | 0.00 | 0.00 |
June | 3187.17 | 1778.98 | 3227.96 | 781.35 | 2446.60 | 0.00 | 0.00 |
July | 3815.35 | 1660.59 | 3497.43 | 1095.26 | 2402.17 | 0.00 | 0.00 |
August | 4832.53 | 1795.04 | 4098.22 | 1843.53 | 2254.69 | 0.00 | 0.00 |
September | 5690.26 | 2224.45 | 4843.03 | 2837.13 | 2005.90 | 0.00 | 0.00 |
October | 3373.64 | 2940.52 | 3327.36 | 1944.69 | 1382.67 | 0.00 | 0.00 |
November | 2081.14 | 3548.60 | 2359.10 | 1435.10 | 924.00 | 0.00 | 0.00 |
December | 1560.86 | 4284.61 | 1869.80 | 1197.99 | 671.81 | 0.00 | 0.00 |
Annual Sum or Average | 3235.16 | 2814.37 | 3245.47 | 1539.61 | 1705.86 | 0.00 | 0.00 |
Minimum of Months | 1312.80 | 1660.59 | 1869.80 | 594.00 | 671.81 | 0.00 | 0.00 |
Maximum of Months | 5690.26 | 4284.61 | 4843.03 | 2837.13 | 2446.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 263.66 | 2918.89 | 630.62 | 208.36 | 422.26 | 0.00 | 0.00 |
February | 700.55 | 2814.86 | 1116.54 | 471.44 | 645.10 | 0.00 | 0.00 |
March | 373.87 | 2376.26 | 1009.59 | 193.13 | 816.45 | 0.00 | 0.00 |
April | 2069.15 | 1972.10 | 2382.16 | 946.21 | 1435.94 | 0.00 | 0.00 |
May | 2473.80 | 1614.33 | 2794.82 | 1136.47 | 1658.35 | 0.00 | 0.00 |
June | 2988.91 | 1285.58 | 3018.11 | 1242.44 | 1775.67 | 0.00 | 0.00 |
July | 3209.57 | 1240.02 | 3073.81 | 1355.25 | 1718.56 | 0.00 | 0.00 |
August | 2705.01 | 1372.95 | 2581.80 | 1117.85 | 1463.95 | 0.00 | 0.00 |
September | 2093.25 | 1600.95 | 2071.29 | 928.81 | 1142.47 | 0.00 | 0.00 |
October | 777.15 | 2203.13 | 1104.95 | 397.34 | 707.62 | 0.00 | 0.00 |
November | 252.11 | 2782.57 | 597.96 | 174.55 | 423.41 | 0.00 | 0.00 |
December | 67.37 | 3433.96 | 338.46 | 71.42 | 267.04 | 0.00 | 0.00 |
Annual Sum or Average | 1500.55 | 2131.50 | 1728.50 | 687.22 | 1041.28 | 0.00 | 0.00 |
Minimum of Months | 67.37 | 1240.02 | 338.46 | 71.42 | 267.04 | 0.00 | 0.00 |
Maximum of Months | 3209.57 | 3433.96 | 3073.81 | 1355.25 | 1775.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.24 | 4117.44 | 475.90 | 0.00 | 475.90 | 0.00 | 0.00 |
February | 16.20 | 3925.49 | 743.14 | 0.00 | 743.14 | 0.00 | 0.00 |
March | 122.30 | 3240.42 | 1028.37 | 0.00 | 1028.37 | 0.00 | 0.00 |
April | 712.68 | 2557.94 | 1674.35 | 7.49 | 1666.85 | 0.00 | 0.00 |
May | 870.55 | 2062.33 | 2093.36 | 100.99 | 1992.37 | 0.00 | 0.00 |
June | 1466.98 | 1589.46 | 2314.08 | 145.11 | 2168.97 | 0.00 | 0.00 |
July | 1570.70 | 1447.90 | 2195.03 | 125.15 | 2069.88 | 0.00 | 0.00 |
August | 1210.30 | 1612.51 | 1725.41 | 27.03 | 1698.37 | 0.00 | 0.00 |
September | 747.36 | 2149.31 | 1313.27 | 0.29 | 1312.98 | 0.00 | 0.00 |
October | 169.25 | 2945.51 | 841.53 | 0.00 | 841.53 | 0.00 | 0.00 |
November | 6.01 | 3669.84 | 505.64 | 0.00 | 505.64 | 0.00 | 0.00 |
December | 0.00 | 4388.47 | 344.34 | 0.00 | 344.34 | 0.00 | 0.00 |
Annual Sum or Average | 577.48 | 2803.18 | 1273.56 | 34.07 | 1239.49 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 1447.90 | 344.34 | 0.00 | 344.34 | 0.00 | 0.00 |
Maximum of Months | 1570.70 | 4388.47 | 2314.08 | 145.11 | 2168.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 283.42 | 2569.66 | 648.48 | 260.49 | 387.98 | 0.00 | 0.00 |
February | 488.51 | 2474.49 | 966.99 | 357.21 | 609.78 | 0.00 | 0.00 |
March | 406.88 | 2018.67 | 1010.53 | 199.14 | 811.39 | 0.00 | 0.00 |
April | 2493.33 | 1577.93 | 2713.35 | 1275.02 | 1438.33 | 0.00 | 0.00 |
May | 2525.36 | 1364.78 | 2853.01 | 1244.15 | 1608.86 | 0.00 | 0.00 |
June | 2749.31 | 1047.41 | 2823.95 | 1127.86 | 1696.09 | 0.00 | 0.00 |
July | 2981.60 | 957.18 | 2882.70 | 1225.15 | 1657.55 | 0.00 | 0.00 |
August | 2940.26 | 1025.14 | 2730.73 | 1304.72 | 1426.01 | 0.00 | 0.00 |
September | 2520.02 | 1325.25 | 2459.11 | 1307.64 | 1151.47 | 0.00 | 0.00 |
October | 867.65 | 1867.18 | 1187.05 | 491.94 | 695.10 | 0.00 | 0.00 |
November | 265.19 | 2314.40 | 618.84 | 210.91 | 407.93 | 0.00 | 0.00 |
December | 168.48 | 2774.54 | 458.64 | 170.52 | 288.12 | 0.00 | 0.00 |
Annual Sum or Average | 1561.36 | 1772.95 | 1782.02 | 765.55 | 1016.48 | 0.00 | 0.00 |
Minimum of Months | 168.48 | 957.18 | 458.64 | 170.52 | 288.12 | 0.00 | 0.00 |
Maximum of Months | 2981.60 | 2774.54 | 2882.70 | 1307.64 | 1696.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2345.55 | 3670.90 | 2701.84 | 1749.01 | 952.83 | 0.00 | 0.00 |
February | 2958.01 | 3651.99 | 3299.80 | 2013.58 | 1286.22 | 0.00 | 0.00 |
March | 1315.35 | 3062.83 | 2040.15 | 594.00 | 1446.15 | 0.00 | 0.00 |
April | 4382.43 | 2622.25 | 4236.54 | 1914.87 | 2321.68 | 0.00 | 0.00 |
May | 3256.44 | 2292.42 | 3504.01 | 1140.79 | 2363.22 | 0.00 | 0.00 |
June | 3177.48 | 1730.09 | 3227.95 | 781.35 | 2446.60 | 0.00 | 0.00 |
July | 3814.01 | 1593.28 | 3497.42 | 1095.26 | 2402.16 | 0.00 | 0.00 |
August | 4823.87 | 1716.11 | 4098.21 | 1843.53 | 2254.68 | 0.00 | 0.00 |
September | 5643.35 | 2199.47 | 4843.01 | 2837.12 | 2005.89 | 0.00 | 0.00 |
October | 3351.09 | 2890.36 | 3327.35 | 1944.69 | 1382.66 | 0.00 | 0.00 |
November | 2078.18 | 3440.10 | 2359.09 | 1435.09 | 924.00 | 0.00 | 0.00 |
December | 1574.00 | 4126.78 | 1869.79 | 1197.99 | 671.81 | 0.00 | 0.00 |
Annual Sum or Average | 3222.35 | 2745.06 | 3245.46 | 1539.61 | 1705.86 | 0.00 | 0.00 |
Minimum of Months | 1315.35 | 1593.28 | 1869.79 | 594.00 | 671.81 | 0.00 | 0.00 |
Maximum of Months | 5643.35 | 4126.78 | 4843.01 | 2837.12 | 2446.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 286.45 | 2636.13 | 630.61 | 208.36 | 422.26 | 0.00 | 0.00 |
February | 728.56 | 2554.92 | 1116.53 | 471.44 | 645.10 | 0.00 | 0.00 |
March | 421.76 | 2082.57 | 1009.58 | 193.13 | 816.45 | 0.00 | 0.00 |
April | 2160.48 | 1731.47 | 2382.15 | 946.21 | 1435.94 | 0.00 | 0.00 |
May | 2509.27 | 1501.59 | 2794.81 | 1136.47 | 1658.34 | 0.00 | 0.00 |
June | 3027.00 | 1180.44 | 3018.10 | 1242.44 | 1775.66 | 0.00 | 0.00 |
July | 3280.28 | 1097.29 | 3073.80 | 1355.25 | 1718.55 | 0.00 | 0.00 |
August | 2794.32 | 1172.92 | 2581.79 | 1117.84 | 1463.94 | 0.00 | 0.00 |
September | 2140.52 | 1466.06 | 2071.28 | 928.81 | 1142.47 | 0.00 | 0.00 |
October | 820.51 | 1963.87 | 1104.95 | 397.33 | 707.61 | 0.00 | 0.00 |
November | 279.72 | 2414.87 | 597.96 | 174.55 | 423.41 | 0.00 | 0.00 |
December | 84.81 | 2944.86 | 338.46 | 71.42 | 267.04 | 0.00 | 0.00 |
Annual Sum or Average | 1547.26 | 1892.33 | 1728.50 | 687.22 | 1041.28 | 0.00 | 0.00 |
Minimum of Months | 84.81 | 1097.29 | 338.46 | 71.42 | 267.04 | 0.00 | 0.00 |
Maximum of Months | 3280.28 | 2944.86 | 3073.80 | 1355.25 | 1775.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13.71 | 3675.66 | 475.90 | 0.00 | 475.90 | 0.00 | 0.00 |
February | 44.03 | 3493.33 | 743.14 | 0.00 | 743.14 | 0.00 | 0.00 |
March | 180.11 | 2874.50 | 1028.37 | 0.00 | 1028.37 | 0.00 | 0.00 |
April | 793.94 | 2301.25 | 1674.35 | 7.49 | 1666.85 | 0.00 | 0.00 |
May | 963.65 | 1858.09 | 2093.36 | 100.99 | 1992.37 | 0.00 | 0.00 |
June | 1531.87 | 1465.68 | 2314.08 | 145.11 | 2168.97 | 0.00 | 0.00 |
July | 1625.38 | 1339.44 | 2195.03 | 125.15 | 2069.88 | 0.00 | 0.00 |
August | 1260.40 | 1476.35 | 1725.41 | 27.03 | 1698.37 | 0.00 | 0.00 |
September | 823.86 | 1925.85 | 1313.27 | 0.29 | 1312.98 | 0.00 | 0.00 |
October | 242.48 | 2550.41 | 841.53 | 0.00 | 841.53 | 0.00 | 0.00 |
November | 19.56 | 3210.35 | 505.64 | 0.00 | 505.64 | 0.00 | 0.00 |
December | 0.79 | 3956.48 | 344.34 | 0.00 | 344.34 | 0.00 | 0.00 |
Annual Sum or Average | 627.92 | 2505.66 | 1273.56 | 34.07 | 1239.49 | 0.00 | 0.00 |
Minimum of Months | 0.79 | 1339.44 | 344.34 | 0.00 | 344.34 | 0.00 | 0.00 |
Maximum of Months | 1625.38 | 3956.48 | 2314.08 | 145.11 | 2168.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 314.13 | 2289.66 | 648.48 | 260.49 | 387.98 | 0.00 | 0.00 |
February | 533.94 | 2203.66 | 966.99 | 357.21 | 609.78 | 0.00 | 0.00 |
March | 471.01 | 1801.48 | 1010.53 | 199.14 | 811.39 | 0.00 | 0.00 |
April | 2549.53 | 1450.12 | 2713.35 | 1275.02 | 1438.33 | 0.00 | 0.00 |
May | 2578.36 | 1263.66 | 2853.01 | 1244.15 | 1608.86 | 0.00 | 0.00 |
June | 2776.50 | 988.51 | 2823.95 | 1127.86 | 1696.09 | 0.00 | 0.00 |
July | 2996.50 | 907.00 | 2882.70 | 1225.15 | 1657.55 | 0.00 | 0.00 |
August | 2957.99 | 967.50 | 2730.73 | 1304.72 | 1426.01 | 0.00 | 0.00 |
September | 2560.57 | 1224.71 | 2459.11 | 1307.64 | 1151.47 | 0.00 | 0.00 |
October | 935.11 | 1635.17 | 1187.05 | 491.94 | 695.10 | 0.00 | 0.00 |
November | 295.58 | 2029.50 | 618.84 | 210.91 | 407.93 | 0.00 | 0.00 |
December | 189.31 | 2501.88 | 458.64 | 170.52 | 288.12 | 0.00 | 0.00 |
Annual Sum or Average | 1600.36 | 1602.31 | 1782.02 | 765.55 | 1016.48 | 0.00 | 0.00 |
Minimum of Months | 189.31 | 907.00 | 458.64 | 170.52 | 288.12 | 0.00 | 0.00 |
Maximum of Months | 2996.50 | 2501.88 | 2882.70 | 1307.64 | 1696.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2429.31 | 3273.92 | 2701.84 | 1749.01 | 952.83 | 0.00 | 0.00 |
February | 3042.73 | 3279.84 | 3299.80 | 2013.58 | 1286.22 | 0.00 | 0.00 |
March | 1390.59 | 2753.83 | 2040.15 | 594.00 | 1446.15 | 0.00 | 0.00 |
April | 4430.94 | 2407.45 | 4236.54 | 1914.87 | 2321.68 | 0.00 | 0.00 |
May | 3294.93 | 2114.30 | 3504.01 | 1140.79 | 2363.22 | 0.00 | 0.00 |
June | 3192.51 | 1623.62 | 3227.95 | 781.35 | 2446.60 | 0.00 | 0.00 |
July | 3819.83 | 1496.84 | 3497.42 | 1095.26 | 2402.16 | 0.00 | 0.00 |
August | 4832.47 | 1607.75 | 4098.21 | 1843.53 | 2254.68 | 0.00 | 0.00 |
September | 5674.58 | 2028.18 | 4843.01 | 2837.12 | 2005.89 | 0.00 | 0.00 |
October | 3423.07 | 2560.94 | 3327.35 | 1944.69 | 1382.66 | 0.00 | 0.00 |
November | 2142.76 | 3047.37 | 2359.09 | 1435.09 | 924.00 | 0.00 | 0.00 |
December | 1633.67 | 3723.80 | 1869.79 | 1197.99 | 671.81 | 0.00 | 0.00 |
Annual Sum or Average | 3271.12 | 2489.06 | 3245.46 | 1539.61 | 1705.86 | 0.00 | 0.00 |
Minimum of Months | 1390.59 | 1496.84 | 1869.79 | 594.00 | 671.81 | 0.00 | 0.00 |
Maximum of Months | 5674.58 | 3723.80 | 4843.01 | 2837.12 | 2446.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 303.44 | 2402.10 | 630.61 | 208.36 | 422.26 | 0.00 | 0.00 |
February | 750.67 | 2335.82 | 1116.53 | 471.44 | 645.10 | 0.00 | 0.00 |
March | 442.96 | 1906.69 | 1009.58 | 193.13 | 816.45 | 0.00 | 0.00 |
April | 2178.51 | 1605.82 | 2382.15 | 946.21 | 1435.94 | 0.00 | 0.00 |
May | 2519.52 | 1398.47 | 2794.81 | 1136.47 | 1658.34 | 0.00 | 0.00 |
June | 3023.29 | 1114.71 | 3018.10 | 1242.44 | 1775.66 | 0.00 | 0.00 |
July | 3271.87 | 1037.06 | 3073.80 | 1355.25 | 1718.55 | 0.00 | 0.00 |
August | 2791.92 | 1105.60 | 2581.79 | 1117.84 | 1463.94 | 0.00 | 0.00 |
September | 2152.07 | 1363.68 | 2071.28 | 928.81 | 1142.47 | 0.00 | 0.00 |
October | 847.58 | 1777.53 | 1104.95 | 397.33 | 707.61 | 0.00 | 0.00 |
November | 292.77 | 2188.77 | 597.96 | 174.55 | 423.41 | 0.00 | 0.00 |
December | 92.60 | 2704.96 | 338.46 | 71.42 | 267.04 | 0.00 | 0.00 |
Annual Sum or Average | 1558.31 | 1742.18 | 1728.50 | 687.22 | 1041.28 | 0.00 | 0.00 |
Minimum of Months | 92.60 | 1037.06 | 338.46 | 71.42 | 267.04 | 0.00 | 0.00 |
Maximum of Months | 3271.87 | 2704.96 | 3073.80 | 1355.25 | 1775.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 756123.91 | 0.121297E+11 | 0.127466E+10 | 0.00 | 0.127466E+10 | 0.00 | 0.00 |
February | 15022737.61 | 0.103813E+11 | 0.179781E+10 | 0.00 | 0.179781E+10 | 0.00 | 0.00 |
March | 0.230589E+09 | 0.955886E+10 | 0.275440E+10 | 0.00 | 0.275440E+10 | 0.00 | 0.00 |
April | 0.169608E+10 | 0.719838E+10 | 0.433992E+10 | 19423678.70 | 0.432050E+10 | 0.00 | 0.00 |
May | 0.219759E+10 | 0.588791E+10 | 0.560688E+10 | 0.270505E+09 | 0.533637E+10 | 0.00 | 0.00 |
June | 0.372977E+10 | 0.433987E+10 | 0.599811E+10 | 0.376121E+09 | 0.562199E+10 | 0.00 | 0.00 |
July | 0.405037E+10 | 0.416842E+10 | 0.587919E+10 | 0.335204E+09 | 0.554398E+10 | 0.00 | 0.00 |
August | 0.309298E+10 | 0.473395E+10 | 0.462134E+10 | 72404989.57 | 0.454894E+10 | 0.00 | 0.00 |
September | 0.180492E+10 | 0.599791E+10 | 0.340401E+10 | 753238.95 | 0.340326E+10 | 0.00 | 0.00 |
October | 0.340890E+09 | 0.872666E+10 | 0.225397E+10 | 0.00 | 0.225397E+10 | 0.00 | 0.00 |
November | 2497794.09 | 0.107239E+11 | 0.131062E+10 | 0.00 | 0.131062E+10 | 0.00 | 0.00 |
December | 0.00 | 0.131939E+11 | 0.922278E+09 | 0.00 | 0.922278E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.171615E+11 | 0.970407E+11 | 0.401632E+11 | 0.107441E+10 | 0.390888E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.416842E+10 | 0.922278E+09 | 0.00 | 0.922278E+09 | 0.00 | 0.00 |
Maximum of Months | 0.405037E+10 | 0.131939E+11 | 0.599811E+10 | 0.376121E+09 | 0.562199E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.722713E+09 | 0.735103E+10 | 0.173689E+10 | 0.697712E+09 | 0.103918E+10 | 0.00 | 0.00 |
February | 0.114751E+10 | 0.630348E+10 | 0.233936E+10 | 0.864177E+09 | 0.147518E+10 | 0.00 | 0.00 |
March | 0.107963E+10 | 0.571570E+10 | 0.270661E+10 | 0.533374E+09 | 0.217324E+10 | 0.00 | 0.00 |
April | 0.651259E+10 | 0.425131E+10 | 0.703304E+10 | 0.330487E+10 | 0.372817E+10 | 0.00 | 0.00 |
May | 0.684724E+10 | 0.379508E+10 | 0.764152E+10 | 0.333234E+10 | 0.430919E+10 | 0.00 | 0.00 |
June | 0.720713E+10 | 0.281940E+10 | 0.731972E+10 | 0.292342E+10 | 0.439630E+10 | 0.00 | 0.00 |
July | 0.805369E+10 | 0.268503E+10 | 0.772105E+10 | 0.328145E+10 | 0.443961E+10 | 0.00 | 0.00 |
August | 0.792742E+10 | 0.289074E+10 | 0.731401E+10 | 0.349457E+10 | 0.381945E+10 | 0.00 | 0.00 |
September | 0.658717E+10 | 0.358293E+10 | 0.637405E+10 | 0.338943E+10 | 0.298462E+10 | 0.00 | 0.00 |
October | 0.231811E+10 | 0.530754E+10 | 0.317940E+10 | 0.131762E+10 | 0.186177E+10 | 0.00 | 0.00 |
November | 0.656212E+09 | 0.645147E+10 | 0.160405E+10 | 0.546682E+09 | 0.105736E+10 | 0.00 | 0.00 |
December | 0.411015E+09 | 0.802778E+10 | 0.122842E+10 | 0.456709E+09 | 0.771711E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.494704E+11 | 0.591815E+11 | 0.561981E+11 | 0.241423E+11 | 0.320558E+11 | 0.00 | 0.00 |
Minimum of Months | 0.411015E+09 | 0.268503E+10 | 0.122842E+10 | 0.456709E+09 | 0.771711E+09 | 0.00 | 0.00 |
Maximum of Months | 0.805369E+10 | 0.802778E+10 | 0.772105E+10 | 0.349457E+10 | 0.443961E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.629468E+10 | 0.100291E+11 | 0.723663E+10 | 0.468457E+10 | 0.255206E+10 | 0.00 | 0.00 |
February | 0.720776E+10 | 0.892009E+10 | 0.798290E+10 | 0.487128E+10 | 0.311163E+10 | 0.00 | 0.00 |
March | 0.351621E+10 | 0.844098E+10 | 0.546436E+10 | 0.159098E+10 | 0.387339E+10 | 0.00 | 0.00 |
April | 0.114281E+11 | 0.693982E+10 | 0.109812E+11 | 0.496336E+10 | 0.601781E+10 | 0.00 | 0.00 |
May | 0.879366E+10 | 0.624176E+10 | 0.938519E+10 | 0.305551E+10 | 0.632968E+10 | 0.00 | 0.00 |
June | 0.826115E+10 | 0.461111E+10 | 0.836687E+10 | 0.202527E+10 | 0.634160E+10 | 0.00 | 0.00 |
July | 0.102190E+11 | 0.444772E+10 | 0.936752E+10 | 0.293354E+10 | 0.643398E+10 | 0.00 | 0.00 |
August | 0.129435E+11 | 0.480783E+10 | 0.109767E+11 | 0.493772E+10 | 0.603896E+10 | 0.00 | 0.00 |
September | 0.147492E+11 | 0.576576E+10 | 0.125531E+11 | 0.735383E+10 | 0.519930E+10 | 0.00 | 0.00 |
October | 0.903597E+10 | 0.787589E+10 | 0.891200E+10 | 0.520866E+10 | 0.370334E+10 | 0.00 | 0.00 |
November | 0.539431E+10 | 0.919798E+10 | 0.611478E+10 | 0.371978E+10 | 0.239500E+10 | 0.00 | 0.00 |
December | 0.418060E+10 | 0.114759E+11 | 0.500808E+10 | 0.320870E+10 | 0.179938E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.102024E+12 | 0.887539E+11 | 0.102349E+12 | 0.485532E+11 | 0.537961E+11 | 0.00 | 0.00 |
Minimum of Months | 0.351621E+10 | 0.444772E+10 | 0.500808E+10 | 0.159098E+10 | 0.179938E+10 | 0.00 | 0.00 |
Maximum of Months | 0.147492E+11 | 0.114759E+11 | 0.125531E+11 | 0.735383E+10 | 0.643398E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.706192E+09 | 0.781795E+10 | 0.168904E+10 | 0.558066E+09 | 0.113098E+10 | 0.00 | 0.00 |
February | 0.169477E+10 | 0.680972E+10 | 0.270112E+10 | 0.114050E+10 | 0.156062E+10 | 0.00 | 0.00 |
March | 0.100138E+10 | 0.636458E+10 | 0.270408E+10 | 0.517291E+09 | 0.218679E+10 | 0.00 | 0.00 |
April | 0.536323E+10 | 0.511168E+10 | 0.617455E+10 | 0.245259E+10 | 0.372197E+10 | 0.00 | 0.00 |
May | 0.662583E+10 | 0.432382E+10 | 0.748565E+10 | 0.304392E+10 | 0.444173E+10 | 0.00 | 0.00 |
June | 0.774727E+10 | 0.333224E+10 | 0.782293E+10 | 0.322040E+10 | 0.460253E+10 | 0.00 | 0.00 |
July | 0.859651E+10 | 0.332127E+10 | 0.823289E+10 | 0.362991E+10 | 0.460299E+10 | 0.00 | 0.00 |
August | 0.724509E+10 | 0.367731E+10 | 0.691508E+10 | 0.299404E+10 | 0.392104E+10 | 0.00 | 0.00 |
September | 0.542571E+10 | 0.414967E+10 | 0.536877E+10 | 0.240748E+10 | 0.296129E+10 | 0.00 | 0.00 |
October | 0.208153E+10 | 0.590085E+10 | 0.295950E+10 | 0.106422E+10 | 0.189528E+10 | 0.00 | 0.00 |
November | 0.653461E+09 | 0.721242E+10 | 0.154992E+10 | 0.452440E+09 | 0.109748E+10 | 0.00 | 0.00 |
December | 0.180454E+09 | 0.919751E+10 | 0.906541E+09 | 0.191300E+09 | 0.715241E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.473214E+11 | 0.672190E+11 | 0.545101E+11 | 0.216722E+11 | 0.328379E+11 | 0.00 | 0.00 |
Minimum of Months | 0.180454E+09 | 0.332127E+10 | 0.906541E+09 | 0.191300E+09 | 0.715241E+09 | 0.00 | 0.00 |
Maximum of Months | 0.859651E+10 | 0.919751E+10 | 0.823289E+10 | 0.362991E+10 | 0.460299E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 8678650.34 | 0.110281E+11 | 0.127465E+10 | 0.00 | 0.127465E+10 | 0.00 | 0.00 |
February | 39193325.97 | 0.949655E+10 | 0.179780E+10 | 0.00 | 0.179780E+10 | 0.00 | 0.00 |
March | 0.327559E+09 | 0.867913E+10 | 0.275439E+10 | 0.00 | 0.275439E+10 | 0.00 | 0.00 |
April | 0.184727E+10 | 0.663017E+10 | 0.433991E+10 | 19423609.73 | 0.432048E+10 | 0.00 | 0.00 |
May | 0.233167E+10 | 0.552374E+10 | 0.560686E+10 | 0.270504E+09 | 0.533635E+10 | 0.00 | 0.00 |
June | 0.380242E+10 | 0.411987E+10 | 0.599809E+10 | 0.376119E+09 | 0.562197E+10 | 0.00 | 0.00 |
July | 0.420696E+10 | 0.387805E+10 | 0.587917E+10 | 0.335202E+09 | 0.554396E+10 | 0.00 | 0.00 |
August | 0.324167E+10 | 0.431896E+10 | 0.462133E+10 | 72404732.46 | 0.454892E+10 | 0.00 | 0.00 |
September | 0.193715E+10 | 0.557101E+10 | 0.340400E+10 | 753236.27 | 0.340324E+10 | 0.00 | 0.00 |
October | 0.453307E+09 | 0.788925E+10 | 0.225397E+10 | 0.00 | 0.225397E+10 | 0.00 | 0.00 |
November | 15583391.57 | 0.951223E+10 | 0.131061E+10 | 0.00 | 0.131061E+10 | 0.00 | 0.00 |
December | 0.00 | 0.117541E+11 | 0.922274E+09 | 0.00 | 0.922274E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.182115E+11 | 0.884012E+11 | 0.401630E+11 | 0.107441E+10 | 0.390886E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.387805E+10 | 0.922274E+09 | 0.00 | 0.922274E+09 | 0.00 | 0.00 |
Maximum of Months | 0.420696E+10 | 0.117541E+11 | 0.599809E+10 | 0.376119E+09 | 0.562197E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.759109E+09 | 0.688258E+10 | 0.173688E+10 | 0.697709E+09 | 0.103917E+10 | 0.00 | 0.00 |
February | 0.118179E+10 | 0.598629E+10 | 0.233935E+10 | 0.864173E+09 | 0.147518E+10 | 0.00 | 0.00 |
March | 0.108978E+10 | 0.540681E+10 | 0.270660E+10 | 0.533372E+09 | 0.217323E+10 | 0.00 | 0.00 |
April | 0.646270E+10 | 0.409001E+10 | 0.703301E+10 | 0.330486E+10 | 0.372815E+10 | 0.00 | 0.00 |
May | 0.676393E+10 | 0.365542E+10 | 0.764149E+10 | 0.333232E+10 | 0.430917E+10 | 0.00 | 0.00 |
June | 0.712622E+10 | 0.271488E+10 | 0.731969E+10 | 0.292341E+10 | 0.439628E+10 | 0.00 | 0.00 |
July | 0.798592E+10 | 0.256372E+10 | 0.772102E+10 | 0.328143E+10 | 0.443959E+10 | 0.00 | 0.00 |
August | 0.787520E+10 | 0.274573E+10 | 0.731398E+10 | 0.349455E+10 | 0.381943E+10 | 0.00 | 0.00 |
September | 0.653190E+10 | 0.343504E+10 | 0.637402E+10 | 0.338941E+10 | 0.298461E+10 | 0.00 | 0.00 |
October | 0.232392E+10 | 0.500105E+10 | 0.317938E+10 | 0.131762E+10 | 0.186177E+10 | 0.00 | 0.00 |
November | 0.687369E+09 | 0.599891E+10 | 0.160404E+10 | 0.546680E+09 | 0.105736E+10 | 0.00 | 0.00 |
December | 0.451259E+09 | 0.743134E+10 | 0.122841E+10 | 0.456707E+09 | 0.771708E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.492391E+11 | 0.559118E+11 | 0.561979E+11 | 0.241423E+11 | 0.320556E+11 | 0.00 | 0.00 |
Minimum of Months | 0.451259E+09 | 0.256372E+10 | 0.122841E+10 | 0.456707E+09 | 0.771708E+09 | 0.00 | 0.00 |
Maximum of Months | 0.798592E+10 | 0.743134E+10 | 0.772102E+10 | 0.349455E+10 | 0.443959E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.628232E+10 | 0.983214E+10 | 0.723660E+10 | 0.468455E+10 | 0.255205E+10 | 0.00 | 0.00 |
February | 0.715602E+10 | 0.883489E+10 | 0.798287E+10 | 0.487126E+10 | 0.311161E+10 | 0.00 | 0.00 |
March | 0.352302E+10 | 0.820350E+10 | 0.546434E+10 | 0.159097E+10 | 0.387337E+10 | 0.00 | 0.00 |
April | 0.113593E+11 | 0.679686E+10 | 0.109811E+11 | 0.496334E+10 | 0.601778E+10 | 0.00 | 0.00 |
May | 0.872204E+10 | 0.614002E+10 | 0.938515E+10 | 0.305550E+10 | 0.632965E+10 | 0.00 | 0.00 |
June | 0.823602E+10 | 0.448439E+10 | 0.836684E+10 | 0.202526E+10 | 0.634157E+10 | 0.00 | 0.00 |
July | 0.102154E+11 | 0.426744E+10 | 0.936749E+10 | 0.293353E+10 | 0.643395E+10 | 0.00 | 0.00 |
August | 0.129203E+11 | 0.459642E+10 | 0.109766E+11 | 0.493770E+10 | 0.603894E+10 | 0.00 | 0.00 |
September | 0.146276E+11 | 0.570103E+10 | 0.125531E+11 | 0.735381E+10 | 0.519928E+10 | 0.00 | 0.00 |
October | 0.897557E+10 | 0.774155E+10 | 0.891197E+10 | 0.520865E+10 | 0.370333E+10 | 0.00 | 0.00 |
November | 0.538665E+10 | 0.891673E+10 | 0.611476E+10 | 0.371976E+10 | 0.239500E+10 | 0.00 | 0.00 |
December | 0.421581E+10 | 0.110532E+11 | 0.500806E+10 | 0.320869E+10 | 0.179937E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.101620E+12 | 0.865681E+11 | 0.102349E+12 | 0.485530E+11 | 0.537959E+11 | 0.00 | 0.00 |
Minimum of Months | 0.352302E+10 | 0.426744E+10 | 0.500806E+10 | 0.159097E+10 | 0.179937E+10 | 0.00 | 0.00 |
Maximum of Months | 0.146276E+11 | 0.110532E+11 | 0.125531E+11 | 0.735381E+10 | 0.643395E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.767228E+09 | 0.706060E+10 | 0.168903E+10 | 0.558064E+09 | 0.113097E+10 | 0.00 | 0.00 |
February | 0.176254E+10 | 0.618086E+10 | 0.270111E+10 | 0.114050E+10 | 0.156062E+10 | 0.00 | 0.00 |
March | 0.112963E+10 | 0.557796E+10 | 0.270407E+10 | 0.517289E+09 | 0.218678E+10 | 0.00 | 0.00 |
April | 0.559995E+10 | 0.448798E+10 | 0.617453E+10 | 0.245258E+10 | 0.372195E+10 | 0.00 | 0.00 |
May | 0.672082E+10 | 0.402187E+10 | 0.748562E+10 | 0.304391E+10 | 0.444171E+10 | 0.00 | 0.00 |
June | 0.784599E+10 | 0.305969E+10 | 0.782290E+10 | 0.322039E+10 | 0.460251E+10 | 0.00 | 0.00 |
July | 0.878591E+10 | 0.293899E+10 | 0.823286E+10 | 0.362989E+10 | 0.460297E+10 | 0.00 | 0.00 |
August | 0.748431E+10 | 0.314154E+10 | 0.691505E+10 | 0.299402E+10 | 0.392103E+10 | 0.00 | 0.00 |
September | 0.554823E+10 | 0.380002E+10 | 0.536875E+10 | 0.240747E+10 | 0.296128E+10 | 0.00 | 0.00 |
October | 0.219765E+10 | 0.526003E+10 | 0.295949E+10 | 0.106422E+10 | 0.189527E+10 | 0.00 | 0.00 |
November | 0.725044E+09 | 0.625935E+10 | 0.154991E+10 | 0.452438E+09 | 0.109747E+10 | 0.00 | 0.00 |
December | 0.227158E+09 | 0.788750E+10 | 0.906538E+09 | 0.191299E+09 | 0.715238E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.487945E+11 | 0.596764E+11 | 0.545099E+11 | 0.216721E+11 | 0.328378E+11 | 0.00 | 0.00 |
Minimum of Months | 0.227158E+09 | 0.293899E+10 | 0.906538E+09 | 0.191299E+09 | 0.715238E+09 | 0.00 | 0.00 |
Maximum of Months | 0.878591E+10 | 0.788750E+10 | 0.823286E+10 | 0.362989E+10 | 0.460297E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 36708580.21 | 0.984489E+10 | 0.127465E+10 | 0.00 | 0.127465E+10 | 0.00 | 0.00 |
February | 0.106516E+09 | 0.845108E+10 | 0.179780E+10 | 0.00 | 0.179780E+10 | 0.00 | 0.00 |
March | 0.482395E+09 | 0.769906E+10 | 0.275439E+10 | 0.00 | 0.275439E+10 | 0.00 | 0.00 |
April | 0.205788E+10 | 0.596484E+10 | 0.433991E+10 | 19423609.73 | 0.432048E+10 | 0.00 | 0.00 |
May | 0.258103E+10 | 0.497671E+10 | 0.560686E+10 | 0.270504E+09 | 0.533635E+10 | 0.00 | 0.00 |
June | 0.397061E+10 | 0.379903E+10 | 0.599809E+10 | 0.376119E+09 | 0.562197E+10 | 0.00 | 0.00 |
July | 0.435341E+10 | 0.358755E+10 | 0.587917E+10 | 0.335202E+09 | 0.554396E+10 | 0.00 | 0.00 |
August | 0.337585E+10 | 0.395425E+10 | 0.462133E+10 | 72404732.46 | 0.454892E+10 | 0.00 | 0.00 |
September | 0.213544E+10 | 0.499180E+10 | 0.340400E+10 | 753236.27 | 0.340324E+10 | 0.00 | 0.00 |
October | 0.649454E+09 | 0.683101E+10 | 0.225397E+10 | 0.00 | 0.225397E+10 | 0.00 | 0.00 |
November | 50699451.82 | 0.832124E+10 | 0.131061E+10 | 0.00 | 0.131061E+10 | 0.00 | 0.00 |
December | 2124561.62 | 0.105970E+11 | 0.922274E+09 | 0.00 | 0.922274E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.198021E+11 | 0.790185E+11 | 0.401630E+11 | 0.107441E+10 | 0.390886E+11 | 0.00 | 0.00 |
Minimum of Months | 2124561.62 | 0.358755E+10 | 0.922274E+09 | 0.00 | 0.922274E+09 | 0.00 | 0.00 |
Maximum of Months | 0.435341E+10 | 0.105970E+11 | 0.599809E+10 | 0.376119E+09 | 0.562197E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.841363E+09 | 0.613264E+10 | 0.173688E+10 | 0.697709E+09 | 0.103917E+10 | 0.00 | 0.00 |
February | 0.129171E+10 | 0.533109E+10 | 0.233935E+10 | 0.864173E+09 | 0.147518E+10 | 0.00 | 0.00 |
March | 0.126154E+10 | 0.482508E+10 | 0.270660E+10 | 0.533372E+09 | 0.217323E+10 | 0.00 | 0.00 |
April | 0.660838E+10 | 0.375870E+10 | 0.703301E+10 | 0.330486E+10 | 0.372815E+10 | 0.00 | 0.00 |
May | 0.690587E+10 | 0.338459E+10 | 0.764149E+10 | 0.333232E+10 | 0.430917E+10 | 0.00 | 0.00 |
June | 0.719668E+10 | 0.256222E+10 | 0.731969E+10 | 0.292341E+10 | 0.439628E+10 | 0.00 | 0.00 |
July | 0.802583E+10 | 0.242930E+10 | 0.772102E+10 | 0.328143E+10 | 0.443959E+10 | 0.00 | 0.00 |
August | 0.792267E+10 | 0.259135E+10 | 0.731398E+10 | 0.349455E+10 | 0.381943E+10 | 0.00 | 0.00 |
September | 0.663700E+10 | 0.317445E+10 | 0.637402E+10 | 0.338941E+10 | 0.298461E+10 | 0.00 | 0.00 |
October | 0.250460E+10 | 0.437963E+10 | 0.317938E+10 | 0.131762E+10 | 0.186177E+10 | 0.00 | 0.00 |
November | 0.766134E+09 | 0.526046E+10 | 0.160404E+10 | 0.546680E+09 | 0.105736E+10 | 0.00 | 0.00 |
December | 0.507051E+09 | 0.670103E+10 | 0.122841E+10 | 0.456707E+09 | 0.771708E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.504688E+11 | 0.505305E+11 | 0.561979E+11 | 0.241423E+11 | 0.320556E+11 | 0.00 | 0.00 |
Minimum of Months | 0.507051E+09 | 0.242930E+10 | 0.122841E+10 | 0.456707E+09 | 0.771708E+09 | 0.00 | 0.00 |
Maximum of Months | 0.802583E+10 | 0.670103E+10 | 0.772102E+10 | 0.349455E+10 | 0.443959E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.650665E+10 | 0.876887E+10 | 0.723660E+10 | 0.468455E+10 | 0.255205E+10 | 0.00 | 0.00 |
February | 0.736097E+10 | 0.793458E+10 | 0.798287E+10 | 0.487126E+10 | 0.311161E+10 | 0.00 | 0.00 |
March | 0.372456E+10 | 0.737585E+10 | 0.546434E+10 | 0.159097E+10 | 0.387337E+10 | 0.00 | 0.00 |
April | 0.114850E+11 | 0.624011E+10 | 0.109811E+11 | 0.496334E+10 | 0.601778E+10 | 0.00 | 0.00 |
May | 0.882514E+10 | 0.566293E+10 | 0.938515E+10 | 0.305550E+10 | 0.632965E+10 | 0.00 | 0.00 |
June | 0.827498E+10 | 0.420843E+10 | 0.836684E+10 | 0.202526E+10 | 0.634157E+10 | 0.00 | 0.00 |
July | 0.102310E+11 | 0.400914E+10 | 0.936749E+10 | 0.293353E+10 | 0.643395E+10 | 0.00 | 0.00 |
August | 0.129433E+11 | 0.430619E+10 | 0.109766E+11 | 0.493770E+10 | 0.603894E+10 | 0.00 | 0.00 |
September | 0.147085E+11 | 0.525705E+10 | 0.125531E+11 | 0.735381E+10 | 0.519928E+10 | 0.00 | 0.00 |
October | 0.916835E+10 | 0.685921E+10 | 0.891197E+10 | 0.520865E+10 | 0.370333E+10 | 0.00 | 0.00 |
November | 0.555404E+10 | 0.789878E+10 | 0.611476E+10 | 0.371976E+10 | 0.239500E+10 | 0.00 | 0.00 |
December | 0.437561E+10 | 0.997382E+10 | 0.500806E+10 | 0.320869E+10 | 0.179937E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.103158E+12 | 0.784950E+11 | 0.102349E+12 | 0.485530E+11 | 0.537959E+11 | 0.00 | 0.00 |
Minimum of Months | 0.372456E+10 | 0.400914E+10 | 0.500806E+10 | 0.159097E+10 | 0.179937E+10 | 0.00 | 0.00 |
Maximum of Months | 0.147085E+11 | 0.997382E+10 | 0.125531E+11 | 0.735381E+10 | 0.643395E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.812733E+09 | 0.643378E+10 | 0.168903E+10 | 0.558064E+09 | 0.113097E+10 | 0.00 | 0.00 |
February | 0.181601E+10 | 0.565082E+10 | 0.270111E+10 | 0.114050E+10 | 0.156062E+10 | 0.00 | 0.00 |
March | 0.118643E+10 | 0.510689E+10 | 0.270407E+10 | 0.517289E+09 | 0.218678E+10 | 0.00 | 0.00 |
April | 0.564670E+10 | 0.416228E+10 | 0.617453E+10 | 0.245258E+10 | 0.372195E+10 | 0.00 | 0.00 |
May | 0.674828E+10 | 0.374565E+10 | 0.748562E+10 | 0.304391E+10 | 0.444171E+10 | 0.00 | 0.00 |
June | 0.783638E+10 | 0.288932E+10 | 0.782290E+10 | 0.322039E+10 | 0.460251E+10 | 0.00 | 0.00 |
July | 0.876336E+10 | 0.277766E+10 | 0.823286E+10 | 0.362989E+10 | 0.460297E+10 | 0.00 | 0.00 |
August | 0.747787E+10 | 0.296125E+10 | 0.691505E+10 | 0.299402E+10 | 0.392103E+10 | 0.00 | 0.00 |
September | 0.557816E+10 | 0.353466E+10 | 0.536875E+10 | 0.240747E+10 | 0.296128E+10 | 0.00 | 0.00 |
October | 0.227016E+10 | 0.476094E+10 | 0.295949E+10 | 0.106422E+10 | 0.189527E+10 | 0.00 | 0.00 |
November | 0.758872E+09 | 0.567330E+10 | 0.154991E+10 | 0.452438E+09 | 0.109747E+10 | 0.00 | 0.00 |
December | 0.248014E+09 | 0.724497E+10 | 0.906538E+09 | 0.191299E+09 | 0.715238E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.491430E+11 | 0.549415E+11 | 0.545099E+11 | 0.216721E+11 | 0.328378E+11 | 0.00 | 0.00 |
Minimum of Months | 0.248014E+09 | 0.277766E+10 | 0.906538E+09 | 0.191299E+09 | 0.715238E+09 | 0.00 | 0.00 |
Maximum of Months | 0.876336E+10 | 0.724497E+10 | 0.823286E+10 | 0.362989E+10 | 0.460297E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.399759E+11 | -0.395251E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -450819559.9 | 60.05 | 0.00 | 0.00 |
February | 0.365585E+11 | -0.361510E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -407474197.8 | 60.05 | 0.00 | 0.00 |
March | 0.426994E+11 | -0.422488E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -450680312.9 | 60.05 | 0.00 | 0.00 |
April | 0.380291E+11 | -0.375950E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -434084879.6 | 60.05 | 0.00 | 0.00 |
May | 0.395461E+11 | -0.390963E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -449730418.8 | 60.05 | 0.00 | 0.00 |
June | 0.381653E+11 | -0.377310E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -434318367.8 | 60.05 | 0.00 | 0.00 |
July | 0.355821E+11 | -0.351370E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -445092884.8 | 60.05 | 0.00 | 0.00 |
August | 0.386230E+11 | -0.381766E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -446480095.3 | 60.05 | 0.00 | 0.00 |
September | 0.353179E+11 | -0.348851E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -432861680.6 | 60.05 | 0.00 | 0.00 |
October | 0.371867E+11 | -0.367393E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -447470707.1 | 60.05 | 0.00 | 0.00 |
November | 0.374781E+11 | -0.370454E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -432706895.9 | 60.05 | 0.00 | 0.00 |
December | 0.383034E+11 | -0.378540E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -449386575.7 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.457466E+12 | -0.452184E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.528111E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.353179E+11 | -0.422488E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -450819559.9 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.426994E+11 | -0.348851E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -407474197.8 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 195.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 217.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 215.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 417.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 410.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 396.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 234.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 171.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120286E+10 | 19697.97 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.562672E+09 | 14678.07 | 17-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 86073723.31 | 6564.87 | 08-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5647625.12 | 3245.17 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191129E+09 | 8211.48 | 29-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.568097E+09 | 11883.84 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120286E+10 | 19697.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.435568E+09 | 12754.27 | 10-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246929E+09 | 12896.56 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 44229318.86 | 2907.00 | 04-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 107855.19 | 183.57 | 01-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4648056.32 | 594.59 | 28-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 89197581.41 | 8450.37 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270902E+09 | 12273.46 | 18-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.435568E+09 | 12896.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.159263E+10 | 12938.80 | 10-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121509E+10 | 13088.38 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.897157E+09 | 12437.03 | 08-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130560E+09 | 5649.20 | 08-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82852761.40 | 4997.44 | 03-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3904091.65 | 1881.92 | 07-JUN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 151692.93 | 779.73 | 31-JUL-05:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1128679.00 | 1067.88 | 23-AUG-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 52940739.87 | 3155.36 | 21-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.521139E+09 | 7077.75 | 19-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.973761E+09 | 12710.06 | 29-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181849E+10 | 12910.45 | 27-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.728980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 151692.93 | 779.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.181849E+10 | 13088.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.223976E+10 | 20979.45 | 10-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163893E+10 | 21219.65 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135971E+10 | 20170.39 | 08-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.356337E+09 | 17628.25 | 24-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.338311E+09 | 13189.43 | 05-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33567897.42 | 5050.50 | 08-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6670412.99 | 2263.23 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2066507.88 | 669.02 | 24-AUG-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125922E+09 | 6069.86 | 20-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.801598E+09 | 19099.43 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133500E+10 | 20750.96 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261587E+10 | 20932.88 | 27-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2066507.88 | 669.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.261587E+10 | 21219.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100676E+10 | 11465.13 | 10-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.581954E+09 | 7760.38 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160618E+09 | 2377.06 | 08-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1887381.75 | 932.83 | 01-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31929757.00 | 2990.31 | 16-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10344162.70 | 1748.73 | 21-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161518E+09 | 3067.38 | 23-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210576E+09 | 4588.78 | 28-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.292527E+09 | 10892.10 | 30-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100676E+10 | 11465.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.372122E+11 | 297292.54 | 06-JAN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144165E+11 | 299289.80 | 24-FEB-12:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.489197E+10 | 303738.18 | 31-MAR-13:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113907E+10 | 320109.90 | 12-APR-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.163715E+10 | 295686.44 | 01-MAY-13:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.286125E+09 | 281976.61 | 07-JUN-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1713065.83 | 24254.34 | 13-JUL-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 82055498.76 | 137423.10 | 08-SEP-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.373653E+09 | 263911.26 | 30-OCT-09:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.785303E+10 | 297594.81 | 03-NOV-11:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.257441E+11 | 162675.03 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.936376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.372122E+11 | 320109.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.473345E+09 | 452406.13 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.473345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.473345E+09 | 452406.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.288651E+11 | 173457.93 | 10-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.211287E+11 | 172081.34 | 17-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126844E+11 | 163558.57 | 08-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.327711E+10 | 160628.46 | 08-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.163433E+10 | 154031.21 | 06-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31992145.99 | 26923.95 | 07-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 42647450.44 | 84692.19 | 31-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28878787.03 | 13456.81 | 28-AUG-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115992E+10 | 61158.48 | 18-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.764533E+10 | 157022.40 | 04-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182360E+11 | 166291.87 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.350229E+11 | 168887.88 | 30-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129757E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 28878787.03 | 13456.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.350229E+11 | 173457.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.316580E+11 | 176283.90 | 10-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.245485E+11 | 172751.53 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203512E+11 | 163863.03 | 08-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453448E+10 | 161997.27 | 08-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.374346E+10 | 153900.19 | 02-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.898422E+09 | 93778.55 | 07-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.386796E+09 | 69236.46 | 31-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.850849E+09 | 46254.23 | 24-AUG-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.289342E+10 | 62953.31 | 20-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138526E+11 | 157134.37 | 06-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.246438E+11 | 166881.34 | 29-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379234E+11 | 170205.15 | 30-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.386796E+09 | 46254.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.379234E+11 | 176283.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.366726E+11 | 257001.51 | 10-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.280076E+11 | 251867.94 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261446E+11 | 238938.62 | 08-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.804217E+10 | 236222.77 | 08-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.829877E+10 | 226272.15 | 06-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.265551E+10 | 215961.59 | 08-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147471E+10 | 66664.43 | 31-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150506E+10 | 63552.94 | 23-AUG-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.377533E+10 | 62881.33 | 07-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156909E+11 | 225559.82 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.285836E+11 | 243328.15 | 29-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.509546E+11 | 248160.12 | 30-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211805E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.147471E+10 | 62881.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.509546E+11 | 257001.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.361495E+11 | 176022.58 | 10-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.265413E+11 | 172466.95 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.220163E+11 | 163540.10 | 08-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.627392E+10 | 110107.72 | 11-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.572823E+10 | 153355.05 | 10-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152466E+10 | 58189.77 | 08-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.929105E+09 | 50548.00 | 03-JUL-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.104962E+10 | 34424.50 | 24-AUG-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.438752E+10 | 70112.48 | 07-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159679E+11 | 154710.70 | 05-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279173E+11 | 166573.01 | 29-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.440724E+11 | 169916.35 | 30-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192558E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.929105E+09 | 34424.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.440724E+11 | 176022.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.830085E+10 | 29850.40 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.422813E+10 | 28710.27 | 17-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.259360E+10 | 21149.40 | 08-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.429095E+09 | 18157.89 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 61817209.48 | 10370.54 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20202808.68 | 5280.31 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.487975E+09 | 12073.25 | 06-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.254203E+10 | 22827.64 | 29-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.696036E+10 | 25435.61 | 27-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.256241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.830085E+10 | 29850.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.765360E+10 | 99274.43 | 10-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.532326E+10 | 97951.34 | 17-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.356963E+10 | 92410.79 | 08-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.575867E+09 | 84189.00 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109191E+09 | 78971.22 | 15-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 58748708.73 | 26139.03 | 18-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.203538E+10 | 87879.15 | 23-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.465921E+10 | 94673.82 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.836858E+10 | 96336.23 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.323535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.836858E+10 | 99274.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.855579E+10 | 24450.89 | 10-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.677925E+10 | 24088.10 | 17-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.538233E+10 | 22880.09 | 08-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.216877E+10 | 21690.77 | 08-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155588E+10 | 21295.43 | 06-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.401027E+09 | 19739.96 | 08-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.256629E+09 | 19051.14 | 31-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.433153E+09 | 18892.86 | 28-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124558E+10 | 20044.30 | 21-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.402308E+10 | 21609.80 | 23-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.651221E+10 | 23228.86 | 20-NOV-05:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.979682E+10 | 23670.32 | 30-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.471105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.256629E+09 | 18892.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.979682E+10 | 24450.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.653966E+10 | 20536.87 | 11-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.514903E+10 | 20014.29 | 17-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.452454E+10 | 18995.44 | 08-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133000E+10 | 17994.23 | 08-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110387E+10 | 17209.26 | 03-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.365685E+09 | 16354.25 | 08-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.222025E+09 | 15776.06 | 31-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.322233E+09 | 15644.65 | 28-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.889191E+09 | 16304.96 | 21-SEP-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.322301E+10 | 17894.08 | 23-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.530908E+10 | 19282.40 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.758239E+10 | 19623.96 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.365607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.222025E+09 | 15644.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.758239E+10 | 20536.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.791634E+10 | 31594.69 | 11-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.628243E+10 | 30789.52 | 17-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.632360E+10 | 29220.78 | 08-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.255928E+10 | 27679.18 | 08-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.245221E+10 | 27167.48 | 06-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.105744E+10 | 25154.25 | 08-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.767118E+09 | 24264.10 | 31-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.810534E+09 | 24061.52 | 28-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150435E+10 | 24287.11 | 27-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.434333E+10 | 27524.74 | 23-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.664653E+10 | 29559.94 | 20-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100145E+11 | 30188.55 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.506777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.767118E+09 | 24061.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100145E+11 | 31594.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.632645E+10 | 22090.25 | 11-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.484073E+10 | 21520.51 | 17-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.451949E+10 | 20416.31 | 08-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179036E+10 | 19331.03 | 08-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158612E+10 | 18479.84 | 03-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.613833E+09 | 17554.70 | 08-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.449892E+09 | 16928.72 | 31-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.514663E+09 | 7078.38 | 28-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130490E+10 | 16916.49 | 08-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.352389E+10 | 19094.12 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.516057E+10 | 20655.02 | 20-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.718311E+10 | 21048.83 | 30-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.449892E+09 | 7078.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.718311E+10 | 22090.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 489120.82 | 489120.82 | 1613.85 | 09-JAN-17:05 | 1613.85 | 0.00 |
February | 0.00 | 0.00 | 745.66 | 745.66 | 0.67 | 17-FEB-10:41 | 0.67 | 0.00 |
March | 0.00 | 0.00 | 5033.00 | 5033.00 | 1.30 | 27-MAR-05:01 | 1.30 | 0.00 |
April | 0.00 | 0.00 | 0.535845E+10 | 0.535153E+10 | 122486.09 | 30-APR-15:11 | 122486.09 | 0.01 |
May | 0.00 | 0.00 | 0.657405E+10 | 0.657405E+10 | 113161.71 | 22-MAY-15:00 | 113161.71 | 0.06 |
June | 0.00 | 0.00 | 0.210645E+11 | 0.205997E+11 | 136227.95 | 13-JUN-15:50 | 130046.82 | 0.21 |
July | 0.00 | 0.00 | 0.358732E+11 | 0.358153E+11 | 137152.16 | 21-JUL-16:00 | 137152.16 | 0.37 |
August | 0.00 | 0.00 | 0.468549E+11 | 0.464643E+11 | 139284.01 | 14-AUG-14:20 | 132986.30 | 0.45 |
September | 0.00 | 0.00 | 0.229010E+11 | 0.228925E+11 | 101803.20 | 13-SEP-14:20 | 101803.20 | 0.23 |
October | 0.00 | 0.00 | 0.129202E+10 | 0.129202E+10 | 28541.09 | 11-OCT-14:53 | 28541.09 | 0.00 |
November | 0.00 | 0.00 | 24426849.15 | 24426849.15 | 11958.08 | 24-NOV-11:51 | 11958.08 | 0.00 |
December | 0.00 | 0.00 | 594.32 | 594.32 | 0.69 | 20-DEC-10:10 | 0.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.139943E+12 | 0.139014E+12 | 0.11 | |||
Minimum of Months | 0.00 | 0.00 | 594.32 | 594.32 | 0.67 | 0.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.468549E+11 | 0.464643E+11 | 139284.01 | 137152.16 | 0.45 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.552151E+09 | 0.552151E+09 | 222669.84 | 20-JAN-11:02 | 222669.84 | 0.01 |
February | 0.00 | 0.00 | 0.161644E+10 | 0.161644E+10 | 175627.25 | 24-FEB-13:02 | 175627.25 | 0.01 |
March | 0.00 | 0.00 | 0.984359E+10 | 0.984359E+10 | 417693.10 | 30-MAR-14:01 | 417693.10 | 0.00 |
April | 0.00 | 0.00 | 0.549628E+11 | 0.549111E+11 | 1050487.44 | 30-APR-16:02 | 1050487.44 | 0.01 |
May | 0.00 | 0.00 | 0.727889E+11 | 0.727889E+11 | 1009017.37 | 22-MAY-15:00 | 1009017.37 | 0.06 |
June | 0.00 | 0.00 | 0.202436E+12 | 0.198411E+12 | 1265713.81 | 13-JUN-16:00 | 1208988.29 | 0.23 |
July | 0.00 | 0.00 | 0.303396E+12 | 0.303072E+12 | 1254687.21 | 21-JUL-16:00 | 1254687.21 | 0.36 |
August | 0.00 | 0.00 | 0.388491E+12 | 0.386159E+12 | 1146597.19 | 14-AUG-16:00 | 1146597.19 | 0.45 |
September | 0.00 | 0.00 | 0.212046E+12 | 0.211927E+12 | 979415.88 | 13-SEP-14:05 | 979415.88 | 0.25 |
October | 0.00 | 0.00 | 0.199767E+11 | 0.199767E+11 | 639134.52 | 11-OCT-13:01 | 639134.52 | 0.01 |
November | 0.00 | 0.00 | 0.246218E+10 | 0.246218E+10 | 449245.85 | 10-NOV-15:01 | 449245.85 | 0.00 |
December | 0.00 | 0.00 | 234925.59 | 234925.59 | 4.99 | 04-DEC-18:30 | 4.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.126857E+13 | 0.126172E+13 | 0.12 | |||
Minimum of Months | 0.00 | 0.00 | 234925.59 | 234925.59 | 4.99 | 4.99 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.388491E+12 | 0.386159E+12 | 1265713.81 | 1254687.21 | 0.45 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2220729.24 | 2220729.24 | 2525.05 | 22-JAN-09:30 | 2525.05 | 0.00 |
February | 0.00 | 0.00 | 171750.72 | 171750.72 | 570.98 | 19-FEB-02:10 | 570.98 | 0.00 |
March | 0.00 | 0.00 | 2789.31 | 2789.31 | 23.30 | 04-MAR-15:51 | 23.30 | 0.00 |
April | 0.00 | 0.00 | 0.494577E+10 | 0.494365E+10 | 131928.50 | 30-APR-16:02 | 131928.50 | 0.01 |
May | 0.00 | 0.00 | 0.635594E+10 | 0.635594E+10 | 135196.14 | 22-MAY-15:00 | 135196.14 | 0.06 |
June | 0.00 | 0.00 | 0.207651E+11 | 0.203351E+11 | 167000.05 | 13-JUN-14:40 | 156844.17 | 0.20 |
July | 0.00 | 0.00 | 0.327083E+11 | 0.326839E+11 | 160593.54 | 21-JUL-16:00 | 160593.54 | 0.35 |
August | 0.00 | 0.00 | 0.384895E+11 | 0.383880E+11 | 143072.46 | 14-AUG-15:50 | 143072.46 | 0.44 |
September | 0.00 | 0.00 | 0.193013E+11 | 0.192968E+11 | 102429.28 | 13-SEP-15:20 | 102429.28 | 0.22 |
October | 0.00 | 0.00 | 0.944945E+09 | 0.944945E+09 | 27627.21 | 07-OCT-15:00 | 27627.21 | 0.00 |
November | 0.00 | 0.00 | 12373430.13 | 12373430.13 | 6799.98 | 24-NOV-11:54 | 6799.98 | 0.00 |
December | 0.00 | 0.00 | 3014966.06 | 3014966.06 | 3250.70 | 18-DEC-05:21 | 3250.70 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.123529E+12 | 0.122966E+12 | 0.11 | |||
Minimum of Months | 0.00 | 0.00 | 2789.31 | 2789.31 | 23.30 | 23.30 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.384895E+11 | 0.383880E+11 | 167000.05 | 160593.54 | 0.44 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.685183E+10 | 0.675723E+10 | 116900.49 | 06-JAN-05:14 | 116900.49 | 0.02 |
February | 0.00 | 0.00 | 0.480931E+10 | 0.480146E+10 | 120548.13 | 16-FEB-05:16 | 120548.13 | 0.01 |
March | 0.00 | 0.00 | 0.488644E+10 | 0.488444E+10 | 103421.59 | 30-MAR-04:55 | 103421.59 | 0.00 |
April | 0.00 | 0.00 | 0.980002E+10 | 0.976181E+10 | 103554.50 | 08-APR-04:49 | 103554.50 | 0.00 |
May | 0.00 | 0.00 | 0.141789E+11 | 0.137928E+11 | 73881.06 | 31-MAY-04:55 | 57603.03 | 0.10 |
June | 0.00 | 0.00 | 0.237458E+11 | 0.199198E+11 | 80737.20 | 27-JUN-05:43 | 31900.89 | 0.26 |
July | 0.00 | 0.00 | 0.262993E+11 | 0.231025E+11 | 77326.05 | 24-JUL-18:11 | 52422.56 | 0.31 |
August | 0.00 | 0.00 | 0.318912E+11 | 0.286115E+11 | 89111.62 | 11-AUG-16:20 | 44766.26 | 0.40 |
September | 0.00 | 0.00 | 0.238568E+11 | 0.213188E+11 | 77622.41 | 01-SEP-09:48 | 51661.90 | 0.26 |
October | 0.00 | 0.00 | 0.131886E+11 | 0.118905E+11 | 128461.93 | 10-OCT-01:53 | 128461.93 | 0.09 |
November | 0.00 | 0.00 | 0.662005E+10 | 0.648031E+10 | 102918.34 | 30-NOV-05:57 | 102918.34 | 0.02 |
December | 0.00 | 0.00 | 0.527320E+10 | 0.527320E+10 | 103541.74 | 30-DEC-05:54 | 103541.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.171401E+12 | 0.156594E+12 | 0.12 | |||
Minimum of Months | 0.00 | 0.00 | 0.480931E+10 | 0.480146E+10 | 73881.06 | 31900.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.318912E+11 | 0.286115E+11 | 128461.93 | 128461.93 | 0.40 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3008274.10 | 3008274.10 | 122.53 | 17-JAN-11:53 | 122.53 | 0.24 |
February | 0.00 | 0.00 | 0.143785E+12 | 0.143785E+12 | 282161.26 | 22-FEB-07:52 | 282161.26 | 0.04 |
March | 0.00 | 0.00 | 0.231589E+12 | 0.231540E+12 | 271521.12 | 03-MAR-06:22 | 271521.12 | 0.02 |
April | 0.00 | 0.00 | 0.222375E+12 | 0.222241E+12 | 431084.24 | 30-APR-18:21 | 431084.24 | 0.01 |
May | 0.00 | 0.00 | 0.389885E+09 | 0.389885E+09 | 215571.30 | 31-MAY-23:54 | 215571.30 | 0.12 |
June | 0.00 | 0.00 | 0.152866E+12 | 0.138240E+12 | 454208.73 | 25-JUN-18:38 | 251275.78 | 0.39 |
July | 0.00 | 0.00 | 0.237258E+12 | 0.221320E+12 | 378265.51 | 24-JUL-13:42 | 251776.94 | 0.70 |
August | 0.00 | 0.00 | 0.257050E+12 | 0.251906E+12 | 405502.61 | 20-AUG-16:00 | 405502.61 | 0.77 |
September | 0.00 | 0.00 | 0.866741E+09 | 0.866741E+09 | 250301.90 | 30-SEP-24:00 | 250301.90 | 0.19 |
October | 0.00 | 0.00 | 0.142711E+12 | 0.138713E+12 | 290324.05 | 08-OCT-16:31 | 247935.77 | 0.20 |
November | 0.00 | 0.00 | 0.226721E+12 | 0.226689E+12 | 270574.31 | 10-NOV-15:22 | 270574.31 | 0.05 |
December | 0.00 | 0.00 | 0.205902E+12 | 0.205902E+12 | 254865.49 | 28-DEC-05:19 | 254865.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.182152E+13 | 0.178160E+13 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 3008274.10 | 3008274.10 | 122.53 | 122.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.257050E+12 | 0.251906E+12 | 454208.73 | 431084.24 | 0.77 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.603482E+10 | 0.603439E+10 | 3159.41 | 19-JAN-16:20 | 3159.41 | 0.00 |
February | 0.00 | 0.00 | 0.100294E+11 | 0.100293E+11 | 5327.13 | 27-FEB-16:56 | 5327.13 | 0.00 |
March | 0.00 | 0.00 | 0.164908E+11 | 0.164907E+11 | 8118.11 | 31-MAR-23:57 | 8118.11 | 0.00 |
April | 0.00 | 0.00 | 0.216731E+11 | 0.216726E+11 | 9750.52 | 30-APR-18:03 | 9750.52 | 0.00 |
May | 0.00 | 0.00 | 0.727453E+10 | 0.726357E+10 | 4609.61 | 31-MAY-23:52 | 4609.61 | 0.00 |
June | 0.00 | 0.00 | 0.122801E+11 | 0.122175E+11 | 6351.89 | 30-JUN-23:52 | 6351.89 | 0.00 |
July | 0.00 | 0.00 | 0.180081E+11 | 0.179274E+11 | 8444.32 | 31-JUL-23:53 | 8444.32 | 0.00 |
August | 0.00 | 0.00 | 0.230617E+11 | 0.229545E+11 | 9426.56 | 13-AUG-18:02 | 9424.61 | 0.00 |
September | 0.00 | 0.00 | 0.723925E+10 | 0.719303E+10 | 4383.84 | 30-SEP-23:53 | 4383.84 | 0.00 |
October | 0.00 | 0.00 | 0.117835E+11 | 0.117669E+11 | 6173.33 | 31-OCT-23:53 | 6173.33 | 0.00 |
November | 0.00 | 0.00 | 0.159610E+11 | 0.159511E+11 | 6909.06 | 10-NOV-15:52 | 6909.06 | 0.00 |
December | 0.00 | 0.00 | 0.212644E+11 | 0.212643E+11 | 8555.32 | 25-DEC-15:17 | 8555.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.171101E+12 | 0.170765E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.603482E+10 | 0.603439E+10 | 3159.41 | 3159.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.230617E+11 | 0.229545E+11 | 9750.52 | 9750.52 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.430313E+11 | 0.430268E+11 | 28810.67 | 19-JAN-16:20 | 28810.67 | 0.00 |
February | 0.00 | 0.00 | 0.862403E+11 | 0.862389E+11 | 50439.27 | 27-FEB-16:56 | 50439.27 | 0.00 |
March | 0.00 | 0.00 | 0.148481E+12 | 0.148480E+12 | 74798.29 | 31-MAR-23:30 | 74798.29 | 0.00 |
April | 0.00 | 0.00 | 0.201735E+12 | 0.201730E+12 | 91931.75 | 30-APR-18:17 | 91931.75 | 0.00 |
May | 0.00 | 0.00 | 0.626505E+11 | 0.625411E+11 | 42539.30 | 31-MAY-23:30 | 42539.30 | 0.00 |
June | 0.00 | 0.00 | 0.113711E+12 | 0.113087E+12 | 58526.89 | 30-JUN-23:42 | 58526.89 | 0.00 |
July | 0.00 | 0.00 | 0.168019E+12 | 0.167215E+12 | 79872.36 | 31-JUL-23:22 | 79872.36 | 0.00 |
August | 0.00 | 0.00 | 0.216562E+12 | 0.215501E+12 | 89542.11 | 17-AUG-18:10 | 88616.24 | 0.00 |
September | 0.00 | 0.00 | 0.623795E+11 | 0.619236E+11 | 39397.04 | 30-SEP-23:12 | 39397.04 | 0.00 |
October | 0.00 | 0.00 | 0.103885E+12 | 0.103719E+12 | 55573.84 | 31-OCT-23:33 | 55573.84 | 0.00 |
November | 0.00 | 0.00 | 0.141178E+12 | 0.141078E+12 | 65070.62 | 10-NOV-16:01 | 65070.62 | 0.00 |
December | 0.00 | 0.00 | 0.187445E+12 | 0.187444E+12 | 79747.77 | 21-DEC-15:18 | 79747.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.153532E+13 | 0.153198E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.430313E+11 | 0.430268E+11 | 28810.67 | 28810.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216562E+12 | 0.215501E+12 | 91931.75 | 91931.75 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.206927E+10 | 0.206915E+10 | 2773.18 | 19-JAN-16:20 | 2773.18 | 0.00 |
February | 0.00 | 0.00 | 0.649944E+10 | 0.649932E+10 | 4865.48 | 27-FEB-16:56 | 4865.48 | 0.00 |
March | 0.00 | 0.00 | 0.129395E+11 | 0.129394E+11 | 6841.64 | 31-MAR-23:03 | 6841.64 | 0.00 |
April | 0.00 | 0.00 | 0.190036E+11 | 0.190031E+11 | 9360.58 | 30-APR-18:07 | 9360.58 | 0.00 |
May | 0.00 | 0.00 | 0.526051E+10 | 0.524959E+10 | 3993.79 | 31-MAY-23:10 | 3993.79 | 0.00 |
June | 0.00 | 0.00 | 0.108436E+11 | 0.107813E+11 | 5634.87 | 13-JUN-16:00 | 5515.44 | 0.00 |
July | 0.00 | 0.00 | 0.163477E+11 | 0.162674E+11 | 7715.59 | 31-JUL-23:03 | 7715.59 | 0.00 |
August | 0.00 | 0.00 | 0.211499E+11 | 0.210450E+11 | 9149.84 | 14-AUG-16:00 | 9067.05 | 0.00 |
September | 0.00 | 0.00 | 0.528177E+10 | 0.523651E+10 | 3678.54 | 12-SEP-17:00 | 3560.27 | 0.00 |
October | 0.00 | 0.00 | 0.849623E+10 | 0.847992E+10 | 5125.27 | 03-OCT-16:42 | 5125.27 | 0.00 |
November | 0.00 | 0.00 | 0.119351E+11 | 0.119253E+11 | 6427.18 | 10-NOV-16:01 | 6427.18 | 0.00 |
December | 0.00 | 0.00 | 0.162566E+11 | 0.162566E+11 | 7760.82 | 21-DEC-15:18 | 7760.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.136083E+12 | 0.135753E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.206927E+10 | 0.206915E+10 | 2773.18 | 2773.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.211499E+11 | 0.210450E+11 | 9360.58 | 9360.58 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 82770.83 | 1881259.63 | 10-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 62355.85 | 1735247.82 | 06-FEB-05:11 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 42958.41 | 1835058.79 | 13-MAR-04:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12527.04 | 1467566.17 | 11-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10551.39 | 1502785.47 | 05-MAY-04:11 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 3020.41 | 589535.54 | 08-JUN-05:01 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 1695.05 | 508260.06 | 31-JUL-05:01 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 2049.57 | 201985.21 | 23-AUG-05:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 6735.97 | 417937.47 | 20-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27040.21 | 1500385.17 | 24-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 54142.81 | 1633885.29 | 13-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 92660.79 | 1686098.77 | 30-DEC-05:01 |
Annual Sum or Average | 0.00 | 33124.01 | ||||
Minimum of Months | 0.00 | 0.00 | 1695.05 | 201985.21 | ||
Maximum of Months | 0.00 | 0.00 | 92660.79 | 1881259.63 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3783.62 | 662113.05 | 20-JAN-11:20 | 300019.82 | 745655.54 | 15-JAN-14:10 |
February | 65202.57 | 817120.57 | 10-FEB-13:42 | 100254.80 | 738737.87 | 01-FEB-00:01 |
March | 99891.86 | 787583.71 | 24-MAR-05:14 | 12643.74 | 631733.11 | 01-MAR-00:01 |
April | 122725.55 | 1352871.49 | 30-APR-14:43 | 8741.15 | 724786.14 | 30-APR-24:00 |
May | 39878.74 | 1618067.11 | 22-MAY-15:20 | 198543.88 | 745642.95 | 07-MAY-11:40 |
June | 168665.14 | 1964476.48 | 13-JUN-13:05 | 80632.53 | 717593.19 | 02-JUN-07:35 |
July | 249835.16 | 1918516.77 | 21-JUL-16:00 | 2648.68 | 605207.55 | 01-JUL-03:44 |
August | 295912.04 | 1925709.27 | 28-AUG-14:05 | 4838.50 | 422760.99 | 11-AUG-16:43 |
September | 111743.39 | 1758929.50 | 13-SEP-14:05 | 184187.92 | 745594.58 | 23-SEP-01:10 |
October | 69378.51 | 910482.45 | 23-OCT-13:42 | 104127.04 | 718065.24 | 26-OCT-12:25 |
November | 99369.32 | 769970.80 | 13-NOV-23:04 | 6747.19 | 561840.88 | 01-NOV-04:11 |
December | 86334.23 | 707449.68 | 29-DEC-16:47 | 11917.16 | 423390.21 | 08-DEC-08:12 |
Annual Sum or Average | 118071.82 | 84639.18 | ||||
Minimum of Months | 3783.62 | 662113.05 | 2648.68 | 422760.99 | ||
Maximum of Months | 295912.04 | 1964476.48 | 300019.82 | 745655.54 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3001.27 | 339667.58 | 20-JAN-11:10 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 76143.07 | 646500.01 | 24-FEB-13:03 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 202899.76 | 898156.37 | 30-MAR-14:02 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 226876.37 | 1879399.76 | 30-APR-14:42 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46621.48 | 1600311.15 | 22-MAY-15:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 198414.91 | 2469506.70 | 25-JUN-17:32 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 347521.39 | 2709621.67 | 22-JUL-17:42 | 0.00 | 0.00 | 01-JUL-00:01 |
August | 404309.56 | 1881562.97 | 14-AUG-15:50 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 131761.38 | 1680330.78 | 10-SEP-14:51 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 82441.33 | 1062785.26 | 07-OCT-14:01 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 206548.16 | 964830.12 | 10-NOV-15:06 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 184173.33 | 510125.84 | 20-DEC-07:07 | 0.00 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 176548.06 | 0.00 | ||||
Minimum of Months | 3001.27 | 339667.58 | 0.00 | 0.00 | ||
Maximum of Months | 404309.56 | 2709621.67 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 14672.85 | 52249.04 | 31-JAN-12:52 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 14859.05 | 52332.16 | 14-FEB-12:17 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 15688.44 | 52246.88 | 01-MAR-12:32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 14420.48 | 51470.73 | 03-APR-11:32 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14512.95 | 50340.82 | 01-MAY-11:33 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 14472.79 | 48910.70 | 01-JUN-11:57 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 13036.64 | 47645.15 | 03-JUL-11:14 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 14169.95 | 46995.21 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 13376.28 | 47648.25 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 13634.04 | 48916.47 | 31-OCT-11:37 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14208.62 | 50302.49 | 30-NOV-12:52 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 14049.78 | 51474.56 | 29-DEC-12:43 |
Annual Sum or Average | 0.00 | 14255.08 | ||||
Minimum of Months | 0.00 | 0.00 | 13036.64 | 46995.21 | ||
Maximum of Months | 0.00 | 0.00 | 15688.44 | 52332.16 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 829.93 | 376858.85 | 20-JAN-11:20 | 2199.40 | 157129.86 | 09-JAN-02:20 |
February | 72075.83 | 752121.00 | 24-FEB-13:18 | 196.49 | 121746.74 | 01-FEB-00:03 |
March | 68462.39 | 780150.63 | 28-MAR-13:45 | 4044.42 | 119045.97 | 16-MAR-06:11 |
April | 111608.69 | 1357450.26 | 30-APR-15:03 | 3553.04 | 117405.33 | 15-APR-02:40 |
May | 44990.35 | 2628764.08 | 22-MAY-14:40 | 1407.07 | 103568.87 | 14-MAY-20:40 |
June | 214868.94 | 2853787.62 | 13-JUN-16:30 | 79.30 | 61006.62 | 19-JUN-15:40 |
July | 303504.39 | 2880955.00 | 10-JUL-10:30 | 313.40 | 42141.48 | 04-JUL-01:00 |
August | 368759.04 | 2948601.32 | 28-AUG-15:00 | 81.76 | 55664.16 | 23-AUG-04:45 |
September | 136062.63 | 2698658.27 | 13-SEP-14:05 | 919.25 | 92196.79 | 25-SEP-00:10 |
October | 89428.09 | 912447.35 | 17-OCT-14:08 | 39.52 | 45933.02 | 23-OCT-05:43 |
November | 70956.15 | 831984.06 | 10-NOV-15:08 | 3861.20 | 109621.46 | 03-NOV-19:01 |
December | 51613.86 | 550984.13 | 29-DEC-16:50 | 5184.33 | 152454.03 | 26-DEC-18:40 |
Annual Sum or Average | 128159.58 | 1833.57 | ||||
Minimum of Months | 829.93 | 376858.85 | 39.52 | 42141.48 | ||
Maximum of Months | 368759.04 | 2948601.32 | 5184.33 | 157129.86 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.843504E+10 | 0.51 | 19941.68 | 02-JAN-06:01 | 1.60 |
February | 0.791749E+10 | 0.52 | 20677.31 | 17-FEB-06:01 | 1.64 |
March | 0.976853E+10 | 0.56 | 19941.68 | 03-MAR-06:01 | 1.61 |
April | 0.124215E+11 | 0.63 | 19248.22 | 28-APR-15:00 | 1.58 |
May | 0.117628E+11 | 0.62 | 17355.00 | 01-MAY-04:12 | 1.51 |
June | 0.132217E+11 | 0.67 | 22192.74 | 13-JUN-05:01 | 1.67 |
July | 0.147037E+11 | 0.68 | 22002.28 | 18-JUL-04:11 | 1.67 |
August | 0.165827E+11 | 0.73 | 20711.64 | 17-AUG-04:11 | 1.62 |
September | 0.125844E+11 | 0.64 | 17571.27 | 12-SEP-15:00 | 1.51 |
October | 0.101192E+11 | 0.55 | 18860.13 | 14-OCT-05:01 | 1.57 |
November | 0.914280E+10 | 0.53 | 19941.68 | 03-NOV-05:01 | 1.61 |
December | 0.888858E+10 | 0.51 | 20677.31 | 18-DEC-06:01 | 1.63 |
Annual Sum or Average | 0.135548E+12 | 0.60 | |||
Minimum of Months | 0.791749E+10 | 0.51 | 17355.00 | 1.51 | |
Maximum of Months | 0.165827E+11 | 0.73 | 22192.74 | 1.67 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.719995E+11 | 0.50 | 221112.61 | 20-JAN-06:02 | 1.74 |
February | 0.686516E+11 | 0.52 | 221112.61 | 10-FEB-06:02 | 1.74 |
March | 0.802692E+11 | 0.54 | 221112.61 | 02-MAR-06:01 | 1.74 |
April | 0.991668E+11 | 0.58 | 207943.44 | 08-APR-05:01 | 1.70 |
May | 0.103331E+12 | 0.59 | 208965.38 | 10-MAY-05:01 | 1.70 |
June | 0.114714E+12 | 0.64 | 187977.86 | 08-JUN-05:01 | 1.62 |
July | 0.117435E+12 | 0.63 | 178801.81 | 20-JUL-14:01 | 1.58 |
August | 0.129232E+12 | 0.68 | 172074.36 | 01-AUG-05:02 | 1.55 |
September | 0.110845E+12 | 0.62 | 172074.36 | 01-SEP-04:12 | 1.55 |
October | 0.852053E+11 | 0.52 | 221112.61 | 14-OCT-05:01 | 1.74 |
November | 0.722435E+11 | 0.51 | 221112.61 | 02-NOV-05:01 | 1.74 |
December | 0.688721E+11 | 0.49 | 79957.14 | 21-DEC-13:58 | 1.13 |
Annual Sum or Average | 0.112197E+13 | 0.57 | |||
Minimum of Months | 0.686516E+11 | 0.49 | 79957.14 | 1.13 | |
Maximum of Months | 0.129232E+12 | 0.68 | 221112.61 | 1.74 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.793548E+10 | 0.53 | 10865.34 | 02-JAN-05:22 | 1.19 |
February | 0.705433E+10 | 0.52 | 10865.34 | 01-FEB-06:02 | 1.19 |
March | 0.741430E+10 | 0.50 | 10865.34 | 02-MAR-06:01 | 1.19 |
April | 0.845226E+10 | 0.51 | 17360.70 | 28-APR-15:30 | 1.44 |
May | 0.921370E+10 | 0.53 | 16566.01 | 23-MAY-15:20 | 1.41 |
June | 0.105151E+11 | 0.57 | 20056.92 | 13-JUN-16:00 | 1.53 |
July | 0.109737E+11 | 0.55 | 19635.84 | 21-JUL-16:00 | 1.52 |
August | 0.114428E+11 | 0.59 | 17322.31 | 14-AUG-15:40 | 1.43 |
September | 0.925386E+10 | 0.53 | 16565.14 | 12-SEP-15:20 | 1.41 |
October | 0.716822E+10 | 0.46 | 10865.34 | 02-OCT-05:01 | 1.19 |
November | 0.711668E+10 | 0.49 | 10865.34 | 20-NOV-05:51 | 1.19 |
December | 0.818351E+10 | 0.55 | 10865.34 | 01-DEC-06:01 | 1.19 |
Annual Sum or Average | 0.104724E+12 | 0.53 | |||
Minimum of Months | 0.705433E+10 | 0.46 | 10865.34 | 1.19 | |
Maximum of Months | 0.114428E+11 | 0.59 | 20056.92 | 1.53 |
Report: FanReportMonthly
For: CAV_BAS SZVAV FAN
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.520014E+10 | 0.48 | 15429.75 | 02-JAN-04:01 | 1.82 |
February | 0.474892E+10 | 0.48 | 15429.75 | 01-FEB-06:02 | 1.81 |
March | 0.631424E+10 | 0.54 | 15429.75 | 01-MAR-06:03 | 1.82 |
April | 0.773660E+10 | 0.57 | 15429.75 | 01-APR-04:11 | 1.82 |
May | 0.736176E+10 | 0.56 | 15429.75 | 01-MAY-04:12 | 1.82 |
June | 0.830835E+10 | 0.61 | 15429.75 | 01-JUN-04:11 | 1.81 |
July | 0.100200E+11 | 0.63 | 15429.75 | 01-JUL-05:01 | 1.81 |
August | 0.115723E+11 | 0.71 | 15429.75 | 01-AUG-04:12 | 1.81 |
September | 0.919028E+10 | 0.62 | 15429.75 | 01-SEP-04:12 | 1.81 |
October | 0.764811E+10 | 0.55 | 15429.75 | 02-OCT-04:11 | 1.82 |
November | 0.716179E+10 | 0.55 | 15429.75 | 01-NOV-04:11 | 1.82 |
December | 0.614567E+10 | 0.51 | 15429.75 | 01-DEC-05:11 | 1.82 |
Annual Sum or Average | 0.914081E+11 | 0.57 | |||
Minimum of Months | 0.474892E+10 | 0.48 | 15429.75 | 1.81 | |
Maximum of Months | 0.115723E+11 | 0.71 | 15429.75 | 1.82 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SYS11 FAN
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.264389E+11 | 0.51 | 9871.16 | 01-JAN-00:03 | 0.51 |
February | 0.406230E+11 | 0.62 | 32876.98 | 01-FEB-00:03 | 0.86 |
March | 0.649550E+11 | 0.73 | 32876.98 | 01-MAR-00:02 | 0.86 |
April | 0.849048E+11 | 0.86 | 32876.98 | 01-APR-00:10 | 0.86 |
May | 0.264430E+11 | 0.51 | 32876.98 | 31-MAY-23:54 | 0.86 |
June | 0.409532E+11 | 0.60 | 32876.98 | 01-JUN-00:10 | 0.86 |
July | 0.632688E+11 | 0.72 | 32876.98 | 01-JUL-00:02 | 0.86 |
August | 0.876608E+11 | 0.85 | 32876.98 | 01-AUG-00:03 | 0.86 |
September | 0.256111E+11 | 0.51 | 32876.98 | 30-SEP-23:03 | 0.86 |
October | 0.431479E+11 | 0.61 | 32876.98 | 01-OCT-00:08 | 0.86 |
November | 0.622486E+11 | 0.73 | 32876.98 | 01-NOV-00:02 | 0.86 |
December | 0.878346E+11 | 0.86 | 32876.98 | 01-DEC-00:02 | 0.86 |
Annual Sum or Average | 0.654090E+12 | 0.68 | |||
Minimum of Months | 0.256111E+11 | 0.51 | 9871.16 | 0.51 | |
Maximum of Months | 0.878346E+11 | 0.86 | 32876.98 | 0.86 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.357821E+10 | 1.42 | 1335.95 | 02-JAN-02:37 | 1.41 |
February | 0.323194E+10 | 1.42 | 1335.95 | 01-FEB-00:01 | 1.42 |
March | 0.357821E+10 | 1.42 | 1335.95 | 03-MAR-06:49 | 1.42 |
April | 0.346279E+10 | 1.42 | 1335.95 | 01-APR-05:35 | 1.42 |
May | 0.357821E+10 | 1.42 | 1335.95 | 08-MAY-16:50 | 1.42 |
June | 0.346279E+10 | 1.41 | 1335.95 | 01-JUN-00:10 | 1.41 |
July | 0.357821E+10 | 1.41 | 1335.95 | 01-JUL-06:26 | 1.42 |
August | 0.357821E+10 | 1.42 | 1335.95 | 02-AUG-06:03 | 1.42 |
September | 0.346279E+10 | 1.41 | 1335.95 | 02-SEP-07:24 | 1.41 |
October | 0.357821E+10 | 1.42 | 1335.95 | 01-OCT-00:03 | 1.42 |
November | 0.346279E+10 | 1.42 | 1335.95 | 02-NOV-15:01 | 1.42 |
December | 0.357821E+10 | 1.42 | 1335.95 | 01-DEC-13:15 | 1.42 |
Annual Sum or Average | 0.421306E+11 | 1.42 | |||
Minimum of Months | 0.323194E+10 | 1.41 | 1335.95 | 1.41 | |
Maximum of Months | 0.357821E+10 | 1.42 | 1335.95 | 1.42 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.344435E+11 | 1.42 | 12859.72 | 01-JAN-00:30 | 1.41 |
February | 0.311102E+11 | 1.42 | 12859.72 | 01-FEB-07:09 | 1.42 |
March | 0.344435E+11 | 1.42 | 12859.72 | 01-MAR-00:42 | 1.42 |
April | 0.333324E+11 | 1.42 | 12859.72 | 01-APR-05:20 | 1.42 |
May | 0.344435E+11 | 1.42 | 12859.72 | 01-MAY-00:30 | 1.42 |
June | 0.333324E+11 | 1.41 | 12859.72 | 01-JUN-00:14 | 1.41 |
July | 0.344435E+11 | 1.41 | 12859.72 | 01-JUL-08:22 | 1.42 |
August | 0.344435E+11 | 1.42 | 12859.72 | 01-AUG-04:00 | 1.42 |
September | 0.333324E+11 | 1.41 | 12859.72 | 01-SEP-00:10 | 1.42 |
October | 0.344435E+11 | 1.42 | 12859.72 | 01-OCT-04:42 | 1.42 |
November | 0.333324E+11 | 1.42 | 12859.72 | 01-NOV-00:53 | 1.42 |
December | 0.344435E+11 | 1.42 | 12859.72 | 08-DEC-06:26 | 1.42 |
Annual Sum or Average | 0.405544E+12 | 1.42 | |||
Minimum of Months | 0.311102E+11 | 1.41 | 12859.72 | 1.41 | |
Maximum of Months | 0.344435E+11 | 1.42 | 12859.72 | 1.42 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.352491E+10 | 1.42 | 1316.05 | 02-JAN-09:37 | 1.42 |
February | 0.318379E+10 | 1.42 | 1316.05 | 01-FEB-04:13 | 1.42 |
March | 0.352491E+10 | 1.42 | 1316.05 | 02-MAR-14:58 | 1.42 |
April | 0.341120E+10 | 1.42 | 1316.05 | 01-APR-00:49 | 1.42 |
May | 0.352491E+10 | 1.42 | 1316.05 | 01-MAY-05:03 | 1.42 |
June | 0.341120E+10 | 1.41 | 1316.05 | 01-JUN-00:03 | 1.41 |
July | 0.352491E+10 | 1.41 | 1316.05 | 01-JUL-13:28 | 1.42 |
August | 0.352491E+10 | 1.42 | 1316.05 | 01-AUG-05:53 | 1.42 |
September | 0.341120E+10 | 1.41 | 1316.05 | 03-SEP-07:00 | 1.41 |
October | 0.352491E+10 | 1.42 | 1316.05 | 01-OCT-06:23 | 1.42 |
November | 0.341120E+10 | 1.42 | 1316.05 | 02-NOV-15:03 | 1.42 |
December | 0.352491E+10 | 1.42 | 1316.05 | 01-DEC-10:50 | 1.42 |
Annual Sum or Average | 0.415030E+11 | 1.42 | |||
Minimum of Months | 0.318379E+10 | 1.41 | 1316.05 | 1.41 | |
Maximum of Months | 0.352491E+10 | 1.42 | 1316.05 | 1.42 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.221108E+09 | 0.198997E+09 | 3263.87 | 02-JAN-06:01 | 2937.48 | 2937.48 | 48.96 | 14.41 |
February | 0.149588E+09 | 0.134629E+09 | 2050.65 | 17-FEB-06:01 | 1845.58 | 1845.58 | 42.05 | 10.78 |
March | 0.112747E+09 | 0.101472E+09 | 1998.78 | 04-MAR-06:01 | 1798.91 | 1798.91 | 41.95 | 10.59 |
April | 31779035.11 | 28601131.60 | 1870.33 | 11-APR-05:01 | 1683.30 | 1683.30 | 35.06 | 10.12 |
May | 29310395.07 | 26379355.56 | 1659.12 | 05-MAY-05:01 | 1493.21 | 1493.21 | 38.51 | 9.24 |
June | 7600818.34 | 6840736.50 | 608.33 | 08-JUN-05:01 | 547.50 | 547.50 | 31.39 | 3.71 |
July | 4317648.66 | 3885883.80 | 471.32 | 31-JUL-05:01 | 424.19 | 424.19 | 25.64 | 2.87 |
August | 5211179.61 | 4690061.65 | 186.11 | 23-AUG-05:03 | 167.50 | 167.50 | 22.51 | 1.10 |
September | 17146689.94 | 15432020.95 | 426.42 | 07-SEP-05:03 | 383.78 | 383.78 | 28.72 | 2.58 |
October | 74587328.78 | 67128595.91 | 1983.66 | 23-OCT-05:01 | 1785.30 | 1785.30 | 44.23 | 10.52 |
November | 0.143748E+09 | 0.129373E+09 | 2027.92 | 28-NOV-06:01 | 1825.13 | 1825.13 | 42.87 | 10.69 |
December | 0.255336E+09 | 0.229802E+09 | 2062.02 | 30-DEC-06:01 | 1855.82 | 1855.82 | 44.86 | 10.81 |
Annual Sum or Average | 0.105248E+10 | 0.947231E+09 | ||||||
Minimum of Months | 4317648.66 | 3885883.80 | 186.11 | 167.50 | 167.50 | 22.51 | 1.10 | |
Maximum of Months | 0.255336E+09 | 0.229802E+09 | 3263.87 | 2937.48 | 2937.48 | 48.96 | 14.41 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 87328617.85 | 78595756.06 | 1178.57 | 20-JAN-11:10 | 1060.72 | 1060.72 | 8.56 | 10.40 |
February | 0.137073E+10 | 0.123365E+10 | 2676.01 | 03-FEB-11:08 | 2408.41 | 2408.41 | 9.07 | 23.94 |
March | 0.268584E+10 | 0.241725E+10 | 3359.43 | 30-MAR-13:22 | 3023.49 | 3023.49 | 9.61 | 29.78 |
April | 0.277770E+10 | 0.249993E+10 | 7702.32 | 30-APR-16:02 | 6932.08 | 6932.08 | 8.03 | 58.35 |
May | 0.532262E+09 | 0.479036E+09 | 6051.79 | 22-MAY-15:40 | 5446.61 | 5446.61 | 6.73 | 49.12 |
June | 0.237475E+10 | 0.213727E+10 | 10655.65 | 25-JUN-17:32 | 9590.09 | 9590.09 | 9.23 | 71.56 |
July | 0.392485E+10 | 0.353236E+10 | 20631.86 | 18-JUL-05:01 | 18568.67 | 18568.67 | 10.09 | 100.87 |
August | 0.442711E+10 | 0.398440E+10 | 11500.89 | 09-AUG-05:01 | 10350.80 | 10350.80 | 9.95 | 74.78 |
September | 0.130887E+10 | 0.117798E+10 | 5782.03 | 10-SEP-14:51 | 5203.82 | 5203.82 | 8.24 | 47.44 |
October | 0.151288E+10 | 0.136159E+10 | 3848.17 | 18-OCT-14:06 | 3463.35 | 3463.35 | 8.23 | 33.74 |
November | 0.267194E+10 | 0.240475E+10 | 4046.02 | 10-NOV-11:02 | 3641.42 | 3641.42 | 8.58 | 35.29 |
December | 0.248417E+10 | 0.223575E+10 | 2222.56 | 15-DEC-05:11 | 2000.31 | 2000.31 | 9.95 | 19.90 |
Annual Sum or Average | 0.261584E+11 | 0.235426E+11 | ||||||
Minimum of Months | 87328617.85 | 78595756.06 | 1178.57 | 1060.72 | 1060.72 | 6.73 | 10.40 | |
Maximum of Months | 0.442711E+10 | 0.398440E+10 | 20631.86 | 18568.67 | 18568.67 | 10.09 | 100.87 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.287035E+10 | 0.258332E+10 | 9714.70 | 01-JAN-00:20 | 8743.23 | 8743.23 | 6.84 | 51.07 |
February | 0.776403E+10 | 0.698763E+10 | 9714.70 | 01-FEB-00:03 | 8743.23 | 8743.23 | 6.93 | 51.07 |
March | 0.220836E+11 | 0.198752E+11 | 9714.70 | 01-MAR-00:04 | 8743.23 | 8743.23 | 7.64 | 51.07 |
April | 0.209507E+11 | 0.188557E+11 | 9714.70 | 01-APR-00:10 | 8743.23 | 8743.23 | 10.32 | 51.07 |
May | 0.575751E+10 | 0.518176E+10 | 9714.70 | 01-MAY-01:10 | 8743.23 | 8743.23 | 6.74 | 51.07 |
June | 0.106694E+11 | 0.960249E+10 | 9714.70 | 01-JUN-00:10 | 8743.23 | 8743.23 | 8.11 | 51.07 |
July | 0.248314E+11 | 0.223482E+11 | 9714.70 | 01-JUL-00:02 | 8743.23 | 8743.23 | 7.70 | 51.07 |
August | 0.239801E+11 | 0.215821E+11 | 9714.70 | 01-AUG-00:03 | 8743.23 | 8743.23 | 10.05 | 51.07 |
September | 0.931788E+10 | 0.838609E+10 | 9714.70 | 01-SEP-00:20 | 8743.23 | 8743.23 | 6.87 | 51.07 |
October | 0.780268E+10 | 0.702242E+10 | 9714.70 | 01-OCT-00:08 | 8743.23 | 8743.23 | 7.77 | 51.07 |
November | 0.223985E+11 | 0.201586E+11 | 9714.70 | 01-NOV-00:02 | 8743.23 | 8743.23 | 7.71 | 51.07 |
December | 0.204466E+11 | 0.184019E+11 | 9714.70 | 01-DEC-00:02 | 8743.23 | 8743.23 | 10.19 | 51.07 |
Annual Sum or Average | 0.178873E+12 | 0.160985E+12 | ||||||
Minimum of Months | 0.287035E+10 | 0.258332E+10 | 9714.70 | 8743.23 | 8743.23 | 6.74 | 51.07 | |
Maximum of Months | 0.248314E+11 | 0.223482E+11 | 9714.70 | 8743.23 | 8743.23 | 10.32 | 51.07 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 6.89 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 6.75 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 7.25 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 10.32 | 0.00 |
May | 40801722.83 | 36721550.55 | 9714.70 | 22-MAY-14:30 | 8743.23 | 8743.23 | 13.77 | 25.53 |
June | 0.308927E+09 | 0.278035E+09 | 9714.70 | 12-JUN-14:05 | 8743.23 | 8743.23 | 10.35 | 51.07 |
July | 0.483792E+09 | 0.435413E+09 | 9714.70 | 10-JUL-09:50 | 8743.23 | 8743.23 | 13.73 | 25.53 |
August | 0.402188E+09 | 0.361970E+09 | 9714.70 | 14-AUG-12:20 | 8743.23 | 8743.23 | 13.68 | 25.53 |
September | 55373766.70 | 49836390.03 | 9714.70 | 13-SEP-14:00 | 8743.23 | 8743.23 | 13.82 | 25.53 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 7.52 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 7.71 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 10.19 | 0.00 |
Annual Sum or Average | 0.129108E+10 | 0.116197E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.75 | 0.00 | |
Maximum of Months | 0.483792E+09 | 0.435413E+09 | 9714.70 | 8743.23 | 8743.23 | 13.82 | 51.07 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 56.90 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 57.05 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 56.93 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 57.04 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 57.22 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:01 | 16.86 | 16.86 | 57.37 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:01 | 16.86 | 16.86 | 57.39 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 57.30 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.17 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:01 | 16.86 | 16.86 | 57.44 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 57.32 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 57.24 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.90 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.44 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.724038E+10 | 0.651634E+10 | 25063.94 | 20-JAN-11:20 | 22557.55 | 22557.55 | 22.35 | 72.08 |
February | 0.200116E+11 | 0.180104E+11 | 25086.41 | 24-FEB-13:18 | 22577.77 | 22577.77 | 23.60 | 72.08 |
March | 0.568799E+11 | 0.511919E+11 | 25088.09 | 28-MAR-13:45 | 22579.28 | 22579.28 | 23.69 | 72.08 |
April | 0.540060E+11 | 0.486054E+11 | 25124.54 | 30-APR-15:03 | 22612.08 | 22612.08 | 25.61 | 72.08 |
May | 0.149382E+11 | 0.134444E+11 | 50243.24 | 22-MAY-14:40 | 45218.91 | 45218.91 | 25.46 | 144.16 |
June | 0.282121E+11 | 0.253909E+11 | 50258.96 | 13-JUN-16:30 | 45233.06 | 45233.06 | 25.84 | 144.16 |
July | 0.652282E+11 | 0.587054E+11 | 50260.86 | 10-JUL-10:30 | 45234.77 | 45234.77 | 25.88 | 144.16 |
August | 0.626988E+11 | 0.564289E+11 | 50265.59 | 28-AUG-15:00 | 45239.03 | 45239.03 | 25.99 | 144.16 |
September | 0.241823E+11 | 0.217640E+11 | 50248.12 | 13-SEP-14:05 | 45223.31 | 45223.31 | 25.58 | 144.16 |
October | 0.201272E+11 | 0.181144E+11 | 25096.02 | 17-OCT-14:08 | 22586.42 | 22586.42 | 24.13 | 72.08 |
November | 0.576789E+11 | 0.519110E+11 | 25091.19 | 10-NOV-15:08 | 22582.07 | 22582.07 | 23.86 | 72.08 |
December | 0.525990E+11 | 0.473391E+11 | 25074.36 | 29-DEC-16:50 | 22566.93 | 22566.93 | 22.93 | 72.08 |
Annual Sum or Average | 0.463802E+12 | 0.417422E+12 | ||||||
Minimum of Months | 0.724038E+10 | 0.651634E+10 | 25063.94 | 22557.55 | 22557.55 | 22.35 | 72.08 | |
Maximum of Months | 0.652282E+11 | 0.587054E+11 | 50265.59 | 45239.03 | 45239.03 | 25.99 | 144.16 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 44.00 | 44.00 | 82770.83 | 1881259.63 | 10-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 27.43 | 27.43 | 62355.85 | 1735247.82 | 06-FEB-05:11 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 26.20 | 26.20 | 42958.41 | 1835058.79 | 13-MAR-04:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 23.70 | 12527.04 | 1467566.17 | 11-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.95 | 22.95 | 10551.39 | 1502785.47 | 05-MAY-04:11 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.38 | 24.38 | 3020.41 | 589535.54 | 08-JUN-05:01 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 20.95 | 20.95 | 1695.05 | 508260.06 | 31-JUL-05:01 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.58 | 23.58 | 2049.57 | 201985.21 | 23-AUG-05:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.53 | 21.53 | 6735.97 | 417937.47 | 20-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 22.25 | 22.25 | 27040.21 | 1500385.17 | 24-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 24.39 | 24.39 | 54142.81 | 1633885.29 | 13-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 27.76 | 27.76 | 92660.79 | 1686098.77 | 30-DEC-05:01 |
Annual Sum or Average | 0.00 | 33124.01 | ||||||
Minimum of Months | 0.00 | 0.00 | 20.95 | 20.95 | 1695.05 | 201985.21 | ||
Maximum of Months | 0.00 | 0.00 | 44.00 | 44.00 | 92660.79 | 1881259.63 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3783.62 | 662113.05 | 20-JAN-11:20 | 9.79 | 6.70 | 300019.82 | 745655.54 | 15-JAN-14:10 |
February | 65202.57 | 817120.57 | 10-FEB-13:42 | 10.52 | 6.70 | 100254.80 | 738737.87 | 01-FEB-00:01 |
March | 99891.86 | 787583.71 | 24-MAR-05:14 | 10.38 | 6.70 | 12643.74 | 631733.11 | 01-MAR-00:01 |
April | 122725.55 | 1352871.49 | 30-APR-14:43 | 13.03 | 6.70 | 8741.15 | 724786.14 | 30-APR-24:00 |
May | 39878.74 | 1618067.11 | 22-MAY-15:20 | 10.48 | 6.70 | 198543.88 | 745642.95 | 07-MAY-11:40 |
June | 168665.14 | 1964476.48 | 13-JUN-13:05 | 11.29 | 6.70 | 80632.53 | 717593.19 | 02-JUN-07:35 |
July | 249835.16 | 1918516.77 | 21-JUL-16:00 | 11.18 | 6.70 | 2648.68 | 605207.55 | 01-JUL-03:44 |
August | 295912.04 | 1925709.27 | 28-AUG-14:05 | 11.20 | 6.70 | 4838.50 | 422760.99 | 11-AUG-16:43 |
September | 111743.39 | 1758929.50 | 13-SEP-14:05 | 10.81 | 6.70 | 184187.92 | 745594.58 | 23-SEP-01:10 |
October | 69378.51 | 910482.45 | 23-OCT-13:42 | 10.96 | 6.70 | 104127.04 | 718065.24 | 26-OCT-12:25 |
November | 99369.32 | 769970.80 | 13-NOV-23:04 | 10.30 | 6.70 | 6747.19 | 561840.88 | 01-NOV-04:11 |
December | 86334.23 | 707449.68 | 29-DEC-16:47 | 10.01 | 6.70 | 11917.16 | 423390.21 | 08-DEC-08:12 |
Annual Sum or Average | 118071.82 | 84639.18 | ||||||
Minimum of Months | 3783.62 | 662113.05 | 9.79 | 6.70 | 2648.68 | 422760.99 | ||
Maximum of Months | 295912.04 | 1964476.48 | 13.03 | 6.70 | 300019.82 | 745655.54 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3001.27 | 339667.58 | 20-JAN-11:10 | 14.50 | 10.06 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 76143.07 | 646500.01 | 24-FEB-13:03 | 13.71 | 9.57 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 202899.76 | 898156.37 | 30-MAR-14:02 | 14.05 | 7.67 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 226876.37 | 1879399.76 | 30-APR-14:42 | 17.76 | 8.86 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46621.48 | 1600311.15 | 22-MAY-15:10 | 14.91 | 8.80 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 198414.91 | 2469506.70 | 25-JUN-17:32 | 14.95 | 10.88 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 347521.39 | 2709621.67 | 22-JUL-17:42 | 13.29 | 10.95 | 0.00 | 0.00 | 01-JUL-00:01 |
August | 404309.56 | 1881562.97 | 14-AUG-15:50 | 15.84 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 131761.38 | 1680330.78 | 10-SEP-14:51 | 15.16 | 8.99 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 82441.33 | 1062785.26 | 07-OCT-14:01 | 15.66 | 7.98 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 206548.16 | 964830.12 | 10-NOV-15:06 | 14.27 | 7.26 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 184173.33 | 510125.84 | 20-DEC-07:07 | 12.82 | 8.67 | 0.00 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 176548.06 | 0.00 | ||||||
Minimum of Months | 3001.27 | 339667.58 | 12.82 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 404309.56 | 2709621.67 | 17.76 | 10.95 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 58.09 | 58.09 | 14672.85 | 52249.04 | 31-JAN-12:52 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 57.56 | 57.56 | 14859.05 | 52332.16 | 14-FEB-12:17 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 57.56 | 57.56 | 15688.44 | 52246.88 | 01-MAR-12:32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.59 | 57.59 | 14420.48 | 51470.73 | 03-APR-11:32 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.13 | 58.13 | 14512.95 | 50340.82 | 01-MAY-11:33 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 57.72 | 57.72 | 14472.79 | 48910.70 | 01-JUN-11:57 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 57.78 | 57.78 | 13036.64 | 47645.15 | 03-JUL-11:14 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.81 | 57.81 | 14169.95 | 46995.21 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.81 | 57.81 | 13376.28 | 47648.25 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 57.78 | 57.78 | 13634.04 | 48916.47 | 31-OCT-11:37 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 57.72 | 57.72 | 14208.62 | 50302.49 | 30-NOV-12:52 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 57.66 | 57.66 | 14049.78 | 51474.56 | 29-DEC-12:43 |
Annual Sum or Average | 0.00 | 14255.08 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.56 | 57.56 | 13036.64 | 46995.21 | ||
Maximum of Months | 0.00 | 0.00 | 58.13 | 58.13 | 15688.44 | 52332.16 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 829.93 | 376858.85 | 20-JAN-11:20 | 22.35 | 21.10 | 2199.40 | 157129.86 | 09-JAN-02:20 |
February | 72075.83 | 752121.00 | 24-FEB-13:18 | 23.60 | 21.10 | 196.49 | 121746.74 | 01-FEB-00:03 |
March | 68462.39 | 780150.63 | 28-MAR-13:45 | 23.69 | 21.10 | 4044.42 | 119045.97 | 16-MAR-06:11 |
April | 111608.69 | 1357450.26 | 30-APR-15:03 | 25.61 | 21.10 | 3553.04 | 117405.33 | 15-APR-02:40 |
May | 44990.35 | 2628764.08 | 22-MAY-14:40 | 25.46 | 21.10 | 1407.07 | 103568.87 | 14-MAY-20:40 |
June | 214868.94 | 2853787.62 | 13-JUN-16:30 | 25.84 | 21.85 | 79.30 | 61006.62 | 19-JUN-15:40 |
July | 303504.39 | 2880955.00 | 10-JUL-10:30 | 25.88 | 21.33 | 313.40 | 42141.48 | 04-JUL-01:00 |
August | 368759.04 | 2948601.32 | 28-AUG-15:00 | 25.99 | 21.14 | 81.76 | 55664.16 | 23-AUG-04:45 |
September | 136062.63 | 2698658.27 | 13-SEP-14:05 | 25.58 | 21.18 | 919.25 | 92196.79 | 25-SEP-00:10 |
October | 89428.09 | 912447.35 | 17-OCT-14:08 | 24.13 | 21.10 | 39.52 | 45933.02 | 23-OCT-05:43 |
November | 70956.15 | 831984.06 | 10-NOV-15:08 | 23.86 | 21.10 | 3861.20 | 109621.46 | 03-NOV-19:01 |
December | 51613.86 | 550984.13 | 29-DEC-16:50 | 22.93 | 21.10 | 5184.33 | 152454.03 | 26-DEC-18:40 |
Annual Sum or Average | 128159.58 | 1833.57 | ||||||
Minimum of Months | 829.93 | 376858.85 | 22.35 | 21.10 | 39.52 | 42141.48 | ||
Maximum of Months | 368759.04 | 2948601.32 | 25.99 | 21.85 | 5184.33 | 157129.86 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.647757E+10 | 0.00 | 489120.82 | 0.843504E+10 | 0.00 | 0.00 |
February | 0.424558E+10 | 0.00 | 745.66 | 0.791749E+10 | 0.00 | 0.00 |
March | 0.254779E+10 | 0.00 | 5033.00 | 0.976853E+10 | 0.00 | 0.00 |
April | 0.494540E+09 | 0.00 | 0.535845E+10 | 0.124215E+11 | 0.00 | 0.00 |
May | 0.453093E+09 | 0.00 | 0.657405E+10 | 0.117628E+11 | 0.00 | 0.00 |
June | 37471989.07 | 0.00 | 0.210645E+11 | 0.132217E+11 | 0.00 | 0.00 |
July | 6822105.92 | 0.00 | 0.358732E+11 | 0.147037E+11 | 0.00 | 0.00 |
August | 3195186.88 | 0.00 | 0.468549E+11 | 0.165827E+11 | 0.00 | 0.00 |
September | 0.189207E+09 | 0.00 | 0.229010E+11 | 0.125844E+11 | 0.00 | 0.00 |
October | 0.148890E+10 | 0.00 | 0.129202E+10 | 0.101192E+11 | 0.00 | 0.00 |
November | 0.279966E+10 | 0.00 | 24426849.15 | 0.914280E+10 | 0.00 | 0.00 |
December | 0.556589E+10 | 0.00 | 594.32 | 0.888858E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.243097E+11 | 0.00 | 0.139943E+12 | 0.135548E+12 | 0.00 | 0.00 |
Minimum of Months | 3195186.88 | 0.00 | 594.32 | 0.791749E+10 | 0.00 | 0.00 |
Maximum of Months | 0.647757E+10 | 0.00 | 0.468549E+11 | 0.165827E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.171031E+12 | 0.00 | 0.552151E+09 | 0.719995E+11 | 0.00 | 0.00 |
February | 0.114643E+12 | 0.00 | 0.161644E+10 | 0.686516E+11 | 0.00 | 0.00 |
March | 0.860885E+11 | 0.00 | 0.984359E+10 | 0.802692E+11 | 0.00 | 0.00 |
April | 0.232668E+11 | 0.00 | 0.549628E+11 | 0.991668E+11 | 0.00 | 0.00 |
May | 0.210419E+11 | 0.00 | 0.727889E+11 | 0.103331E+12 | 0.00 | 0.00 |
June | 0.539671E+10 | 0.00 | 0.202436E+12 | 0.114714E+12 | 0.00 | 0.00 |
July | 0.283497E+10 | 0.00 | 0.303396E+12 | 0.117435E+12 | 0.00 | 0.00 |
August | 0.343440E+10 | 0.00 | 0.388491E+12 | 0.129232E+12 | 0.00 | 0.00 |
September | 0.122983E+11 | 0.00 | 0.212046E+12 | 0.110845E+12 | 0.00 | 0.00 |
October | 0.535303E+11 | 0.00 | 0.199767E+11 | 0.852053E+11 | 0.00 | 0.00 |
November | 0.107234E+12 | 0.00 | 0.246218E+10 | 0.722435E+11 | 0.00 | 0.00 |
December | 0.193717E+12 | 0.00 | 234925.59 | 0.688721E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.794516E+12 | 0.00 | 0.126857E+13 | 0.112197E+13 | 0.00 | 0.00 |
Minimum of Months | 0.283497E+10 | 0.00 | 234925.59 | 0.686516E+11 | 0.00 | 0.00 |
Maximum of Months | 0.193717E+12 | 0.00 | 0.388491E+12 | 0.129232E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.452927E+11 | 0.00 | 2220729.24 | 0.793548E+10 | 0.00 | 0.00 |
February | 0.326028E+11 | 0.00 | 171750.72 | 0.705433E+10 | 0.00 | 0.00 |
March | 0.269132E+11 | 0.00 | 2789.31 | 0.741430E+10 | 0.00 | 0.00 |
April | 0.885338E+10 | 0.00 | 0.494577E+10 | 0.845226E+10 | 0.00 | 0.00 |
May | 0.686909E+10 | 0.00 | 0.635594E+10 | 0.921370E+10 | 0.00 | 0.00 |
June | 0.243798E+10 | 0.00 | 0.207651E+11 | 0.105151E+11 | 0.00 | 0.00 |
July | 0.169566E+10 | 0.00 | 0.327083E+11 | 0.109737E+11 | 0.00 | 0.00 |
August | 0.208058E+10 | 0.00 | 0.384895E+11 | 0.114428E+11 | 0.00 | 0.00 |
September | 0.502297E+10 | 0.00 | 0.193013E+11 | 0.925386E+10 | 0.00 | 0.00 |
October | 0.176367E+11 | 0.00 | 0.944945E+09 | 0.716822E+10 | 0.00 | 0.00 |
November | 0.308296E+11 | 0.00 | 12373430.13 | 0.711668E+10 | 0.00 | 0.00 |
December | 0.499058E+11 | 0.00 | 3014966.06 | 0.818351E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.230140E+12 | 0.00 | 0.123529E+12 | 0.104724E+12 | 0.00 | 0.00 |
Minimum of Months | 0.169566E+10 | 0.00 | 2789.31 | 0.705433E+10 | 0.00 | 0.00 |
Maximum of Months | 0.499058E+11 | 0.00 | 0.384895E+11 | 0.114428E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.685183E+10 | 0.520014E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.480931E+10 | 0.474892E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.488644E+10 | 0.631424E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.980002E+10 | 0.773660E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.141789E+11 | 0.736176E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.237458E+11 | 0.830835E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.262993E+11 | 0.100200E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.318912E+11 | 0.115723E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.238568E+11 | 0.919028E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.131886E+11 | 0.764811E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.662005E+10 | 0.716179E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.527320E+10 | 0.614567E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.171401E+12 | 0.914081E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.480931E+10 | 0.474892E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.318912E+11 | 0.115723E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 3008274.10 | 0.869459E+11 | 0.00 | 22.51 |
February | 0.00 | 0.00 | 0.143785E+12 | 0.107586E+12 | 0.00 | 24.91 |
March | 0.00 | 0.00 | 0.231589E+12 | 0.173112E+12 | 0.00 | 40.23 |
April | 0.00 | 0.00 | 0.222375E+12 | 0.215602E+12 | 0.00 | 48.62 |
May | 0.00 | 0.00 | 0.389885E+09 | 0.579754E+11 | 0.00 | 11.73 |
June | 0.00 | 0.00 | 0.152866E+12 | 0.472836E+11 | 0.00 | 2.35 |
July | 0.00 | 0.00 | 0.237258E+12 | 0.678966E+11 | 0.00 | 1.72 |
August | 0.00 | 0.00 | 0.257050E+12 | 0.934256E+11 | 0.00 | 2.14 |
September | 0.00 | 0.00 | 0.866741E+09 | 0.372979E+11 | 0.00 | 4.35 |
October | 0.00 | 0.00 | 0.142711E+12 | 0.750098E+11 | 0.00 | 11.85 |
November | 0.00 | 0.00 | 0.226721E+12 | 0.133299E+12 | 0.00 | 26.43 |
December | 0.00 | 0.00 | 0.205902E+12 | 0.240093E+12 | 0.00 | 56.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.182152E+13 | 0.133553E+13 | 0.00 | 253.49 |
Minimum of Months | 0.00 | 0.00 | 3008274.10 | 0.372979E+11 | 0.00 | 1.72 |
Maximum of Months | 0.00 | 0.00 | 0.257050E+12 | 0.240093E+12 | 0.00 | 56.64 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.542993E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.608123E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.792049E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.910147E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.576937E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.688182E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.825068E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.957431E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.563494E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.689676E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.766966E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.907764E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.882883E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.542993E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.957431E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.460191E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.524686E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.684411E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.781613E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.507928E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.606463E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.720697E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.825811E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.495529E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.598727E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.658076E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.756714E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.762085E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.460191E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.825811E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.418788E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.512407E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.708688E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.832005E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.514482E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.648168E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.784164E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.898291E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.503313E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.602105E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.672588E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.779914E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.787491E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.418788E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.898291E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.843504E+10 | 489120.82 | 0.647757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.791749E+10 | 745.66 | 0.424558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.976853E+10 | 5033.00 | 0.254779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124215E+11 | 0.535845E+10 | 0.494540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117628E+11 | 0.657405E+10 | 0.453093E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132217E+11 | 0.210645E+11 | 37471989.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147037E+11 | 0.358732E+11 | 6822105.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165827E+11 | 0.468549E+11 | 3195186.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125844E+11 | 0.229010E+11 | 0.189207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101192E+11 | 0.129202E+10 | 0.148890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.914280E+10 | 24426849.15 | 0.279966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.888858E+10 | 594.32 | 0.556589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135548E+12 | 0.139943E+12 | 0.243097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.791749E+10 | 594.32 | 3195186.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.165827E+11 | 0.468549E+11 | 0.647757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.719995E+11 | 0.552151E+09 | 0.171031E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.686516E+11 | 0.161644E+10 | 0.114643E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.802692E+11 | 0.984359E+10 | 0.860885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.991668E+11 | 0.549628E+11 | 0.232668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103331E+12 | 0.727889E+11 | 0.210419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114714E+12 | 0.202436E+12 | 0.539671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117435E+12 | 0.303396E+12 | 0.283497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129232E+12 | 0.388491E+12 | 0.343440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110845E+12 | 0.212046E+12 | 0.122983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.852053E+11 | 0.199767E+11 | 0.535303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.722435E+11 | 0.246218E+10 | 0.107234E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.688721E+11 | 234925.59 | 0.193717E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112197E+13 | 0.126857E+13 | 0.794516E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.686516E+11 | 234925.59 | 0.283497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129232E+12 | 0.388491E+12 | 0.193717E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.793548E+10 | 2220729.24 | 0.452927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.705433E+10 | 171750.72 | 0.326028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.741430E+10 | 2789.31 | 0.269132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.845226E+10 | 0.494577E+10 | 0.885338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.921370E+10 | 0.635594E+10 | 0.686909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.105151E+11 | 0.207651E+11 | 0.243798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109737E+11 | 0.327083E+11 | 0.169566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.114428E+11 | 0.384895E+11 | 0.208058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.925386E+10 | 0.193013E+11 | 0.502297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.716822E+10 | 0.944945E+09 | 0.176367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.711668E+10 | 12373430.13 | 0.308296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.818351E+10 | 3014966.06 | 0.499058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104724E+12 | 0.123529E+12 | 0.230140E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.705433E+10 | 2789.31 | 0.169566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114428E+11 | 0.384895E+11 | 0.499058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.520014E+10 | 0.685183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.474892E+10 | 0.480931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.631424E+10 | 0.488644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.773660E+10 | 0.980002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.736176E+10 | 0.141789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.830835E+10 | 0.237458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100200E+11 | 0.262993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115723E+11 | 0.318912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.919028E+10 | 0.238568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.764811E+10 | 0.131886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.716179E+10 | 0.662005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.614567E+10 | 0.527320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.914081E+11 | 0.171401E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.474892E+10 | 0.480931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115723E+11 | 0.318912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.264389E+11 | 3008274.10 | 0.00 | 0.00 | 0.00 | 0.602359E+11 | 0.00 | 0.00 |
February | 0.406230E+11 | 0.143785E+12 | 0.00 | 0.00 | 0.00 | 0.666627E+11 | 0.00 | 0.00 |
March | 0.649550E+11 | 0.231589E+12 | 0.00 | 0.00 | 0.00 | 0.107672E+12 | 0.00 | 0.00 |
April | 0.849048E+11 | 0.222375E+12 | 0.00 | 0.00 | 0.00 | 0.130111E+12 | 0.00 | 0.00 |
May | 0.264430E+11 | 0.389885E+09 | 0.00 | 0.00 | 0.00 | 0.313910E+11 | 0.00 | 0.00 |
June | 0.409532E+11 | 0.152866E+12 | 0.00 | 0.00 | 0.00 | 0.630202E+10 | 0.00 | 0.00 |
July | 0.632688E+11 | 0.237258E+12 | 0.00 | 0.00 | 0.00 | 0.460710E+10 | 0.00 | 0.00 |
August | 0.876608E+11 | 0.257050E+12 | 0.00 | 0.00 | 0.00 | 0.573895E+10 | 0.00 | 0.00 |
September | 0.256111E+11 | 0.866741E+09 | 0.00 | 0.00 | 0.00 | 0.116344E+11 | 0.00 | 0.00 |
October | 0.431479E+11 | 0.142711E+12 | 0.00 | 0.00 | 0.00 | 0.317191E+11 | 0.00 | 0.00 |
November | 0.622486E+11 | 0.226721E+12 | 0.00 | 0.00 | 0.00 | 0.707317E+11 | 0.00 | 0.00 |
December | 0.878346E+11 | 0.205902E+12 | 0.00 | 0.00 | 0.00 | 0.151576E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.654090E+12 | 0.182152E+13 | 0.00 | 0.00 | 0.00 | 0.678382E+12 | 0.00 | 0.00 |
Minimum of Months | 0.256111E+11 | 3008274.10 | 0.00 | 0.00 | 0.00 | 0.460710E+10 | 0.00 | 0.00 |
Maximum of Months | 0.878346E+11 | 0.257050E+12 | 0.00 | 0.00 | 0.00 | 0.151576E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.357821E+10 | 0.603482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.323194E+10 | 0.100294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.357821E+10 | 0.164908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.346279E+10 | 0.216731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.357821E+10 | 0.727453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.346279E+10 | 0.122801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.357821E+10 | 0.180081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.357821E+10 | 0.230617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.346279E+10 | 0.723925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.357821E+10 | 0.117835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.346279E+10 | 0.159610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357821E+10 | 0.212644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421306E+11 | 0.171101E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.323194E+10 | 0.603482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.357821E+10 | 0.230617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.344435E+11 | 0.430313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311102E+11 | 0.862403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.344435E+11 | 0.148481E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.333324E+11 | 0.201735E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.344435E+11 | 0.626505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.333324E+11 | 0.113711E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.344435E+11 | 0.168019E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.344435E+11 | 0.216562E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.333324E+11 | 0.623795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.344435E+11 | 0.103885E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.333324E+11 | 0.141178E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344435E+11 | 0.187445E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.405544E+12 | 0.153532E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.311102E+11 | 0.430313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.344435E+11 | 0.216562E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.352491E+10 | 0.206927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.318379E+10 | 0.649944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352491E+10 | 0.129395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.341120E+10 | 0.190036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.352491E+10 | 0.526051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.341120E+10 | 0.108436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.352491E+10 | 0.163477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.352491E+10 | 0.211499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.341120E+10 | 0.528177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.352491E+10 | 0.849623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.341120E+10 | 0.119351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.352491E+10 | 0.162566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.415030E+11 | 0.136083E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.318379E+10 | 0.206927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.352491E+10 | 0.211499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.843504E+10 | 0.647757E+10 | 489120.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.791749E+10 | 0.424558E+10 | 745.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.976853E+10 | 0.254779E+10 | 5033.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124215E+11 | 0.494540E+09 | 0.535845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117628E+11 | 0.453093E+09 | 0.657405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132217E+11 | 37471989.07 | 0.210645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147037E+11 | 6822105.92 | 0.358732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165827E+11 | 3195186.88 | 0.468549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125844E+11 | 0.189207E+09 | 0.229010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101192E+11 | 0.148890E+10 | 0.129202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.914280E+10 | 0.279966E+10 | 24426849.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.888858E+10 | 0.556589E+10 | 594.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135548E+12 | 0.243097E+11 | 0.139943E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.791749E+10 | 3195186.88 | 594.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.165827E+11 | 0.647757E+10 | 0.468549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.719995E+11 | 0.171031E+12 | 0.552151E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.686516E+11 | 0.114643E+12 | 0.161644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.802692E+11 | 0.860885E+11 | 0.984359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.991668E+11 | 0.232668E+11 | 0.549628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103331E+12 | 0.210419E+11 | 0.727889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114714E+12 | 0.539671E+10 | 0.202436E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117435E+12 | 0.283497E+10 | 0.303396E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129232E+12 | 0.343440E+10 | 0.388491E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110845E+12 | 0.122983E+11 | 0.212046E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.852053E+11 | 0.535303E+11 | 0.199767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.722435E+11 | 0.107234E+12 | 0.246218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.688721E+11 | 0.193717E+12 | 234925.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112197E+13 | 0.794516E+12 | 0.126857E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.686516E+11 | 0.283497E+10 | 234925.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129232E+12 | 0.193717E+12 | 0.388491E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.793548E+10 | 0.452927E+11 | 2220729.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.705433E+10 | 0.326028E+11 | 171750.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.741430E+10 | 0.269132E+11 | 2789.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.845226E+10 | 0.885338E+10 | 0.494577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.921370E+10 | 0.686909E+10 | 0.635594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.105151E+11 | 0.243798E+10 | 0.207651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109737E+11 | 0.169566E+10 | 0.327083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.114428E+11 | 0.208058E+10 | 0.384895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.925386E+10 | 0.502297E+10 | 0.193013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.716822E+10 | 0.176367E+11 | 0.944945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.711668E+10 | 0.308296E+11 | 12373430.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.818351E+10 | 0.499058E+11 | 3014966.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104724E+12 | 0.230140E+12 | 0.123529E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.705433E+10 | 0.169566E+10 | 2789.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114428E+11 | 0.499058E+11 | 0.384895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.520014E+10 | 0.00 | 0.685183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.474892E+10 | 0.00 | 0.480931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.631424E+10 | 0.00 | 0.488644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.773660E+10 | 0.00 | 0.980002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.736176E+10 | 0.00 | 0.141789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.830835E+10 | 0.00 | 0.237458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100200E+11 | 0.00 | 0.262993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115723E+11 | 0.00 | 0.318912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.919028E+10 | 0.00 | 0.238568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.764811E+10 | 0.00 | 0.131886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.716179E+10 | 0.00 | 0.662005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.614567E+10 | 0.00 | 0.527320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.914081E+11 | 0.00 | 0.171401E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.474892E+10 | 0.00 | 0.480931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115723E+11 | 0.00 | 0.318912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.264389E+11 | 0.00 | 3008274.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605070E+11 | 0.00 | 0.00 | 0.00 |
February | 0.406230E+11 | 0.00 | 0.143785E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669628E+11 | 0.00 | 0.00 | 0.00 |
March | 0.649550E+11 | 0.00 | 0.231589E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108157E+12 | 0.00 | 0.00 | 0.00 |
April | 0.849048E+11 | 0.00 | 0.222375E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130697E+12 | 0.00 | 0.00 | 0.00 |
May | 0.264430E+11 | 0.00 | 0.389885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315323E+11 | 0.00 | 0.00 | 0.00 |
June | 0.409532E+11 | 0.00 | 0.152866E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633039E+10 | 0.00 | 0.00 | 0.00 |
July | 0.632688E+11 | 0.00 | 0.237258E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462784E+10 | 0.00 | 0.00 | 0.00 |
August | 0.876608E+11 | 0.00 | 0.257050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576478E+10 | 0.00 | 0.00 | 0.00 |
September | 0.256111E+11 | 0.00 | 0.866741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116867E+11 | 0.00 | 0.00 | 0.00 |
October | 0.431479E+11 | 0.00 | 0.142711E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318619E+11 | 0.00 | 0.00 | 0.00 |
November | 0.622486E+11 | 0.00 | 0.226721E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710501E+11 | 0.00 | 0.00 | 0.00 |
December | 0.878346E+11 | 0.00 | 0.205902E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152258E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.654090E+12 | 0.00 | 0.182152E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681436E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.256111E+11 | 0.00 | 3008274.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462784E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.878346E+11 | 0.00 | 0.257050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152258E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.357821E+10 | 0.00 | 0.00 | 0.00 | 0.185172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.323194E+10 | 0.00 | 0.00 | 0.00 | 0.284929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.357821E+10 | 0.00 | 0.00 | 0.00 | 0.434227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.346279E+10 | 0.00 | 0.00 | 0.00 | 0.563869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.357821E+10 | 0.00 | 0.00 | 0.00 | 0.219115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.346279E+10 | 0.00 | 0.00 | 0.00 | 0.341903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.357821E+10 | 0.00 | 0.00 | 0.00 | 0.467247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.357821E+10 | 0.00 | 0.00 | 0.00 | 0.599609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.346279E+10 | 0.00 | 0.00 | 0.00 | 0.217215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.357821E+10 | 0.00 | 0.00 | 0.00 | 0.331855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.346279E+10 | 0.00 | 0.00 | 0.00 | 0.420687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357821E+10 | 0.00 | 0.00 | 0.00 | 0.549942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421306E+11 | 0.00 | 0.00 | 0.00 | 0.461577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.323194E+10 | 0.00 | 0.00 | 0.00 | 0.185172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.357821E+10 | 0.00 | 0.00 | 0.00 | 0.599609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.344435E+11 | 0.00 | 0.00 | 0.00 | 0.115756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311102E+11 | 0.00 | 0.00 | 0.00 | 0.213583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.344435E+11 | 0.00 | 0.00 | 0.00 | 0.339976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.333324E+11 | 0.00 | 0.00 | 0.00 | 0.448289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.344435E+11 | 0.00 | 0.00 | 0.00 | 0.163493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.333324E+11 | 0.00 | 0.00 | 0.00 | 0.273139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.344435E+11 | 0.00 | 0.00 | 0.00 | 0.376262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.344435E+11 | 0.00 | 0.00 | 0.00 | 0.481376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.333324E+11 | 0.00 | 0.00 | 0.00 | 0.162205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.344435E+11 | 0.00 | 0.00 | 0.00 | 0.254292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.333324E+11 | 0.00 | 0.00 | 0.00 | 0.324752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344435E+11 | 0.00 | 0.00 | 0.00 | 0.412279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.405544E+12 | 0.00 | 0.00 | 0.00 | 0.356540E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.311102E+11 | 0.00 | 0.00 | 0.00 | 0.115756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.344435E+11 | 0.00 | 0.00 | 0.00 | 0.481376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.352491E+10 | 0.00 | 0.00 | 0.00 | 0.662969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.318379E+10 | 0.00 | 0.00 | 0.00 | 0.194029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352491E+10 | 0.00 | 0.00 | 0.00 | 0.356197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.341120E+10 | 0.00 | 0.00 | 0.00 | 0.490885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.352491E+10 | 0.00 | 0.00 | 0.00 | 0.161991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.341120E+10 | 0.00 | 0.00 | 0.00 | 0.307048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.352491E+10 | 0.00 | 0.00 | 0.00 | 0.431673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.352491E+10 | 0.00 | 0.00 | 0.00 | 0.545800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.341120E+10 | 0.00 | 0.00 | 0.00 | 0.162192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.352491E+10 | 0.00 | 0.00 | 0.00 | 0.249614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.341120E+10 | 0.00 | 0.00 | 0.00 | 0.331468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.352491E+10 | 0.00 | 0.00 | 0.00 | 0.427423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.415030E+11 | 0.00 | 0.00 | 0.00 | 0.372462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.318379E+10 | 0.00 | 0.00 | 0.00 | 0.662969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.352491E+10 | 0.00 | 0.00 | 0.00 | 0.545800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.836023E+10 | 0.00 | 0.00 | 82625885.89 | 0.00 | 0.00 | 0.466376E+11 | 0.00 | 0.46 |
February | 0.200391E+11 | 0.00 | 0.00 | 0.145157E+09 | 0.00 | 0.00 | 0.299918E+11 | 0.00 | 0.46 |
March | 0.162643E+11 | 0.00 | 0.00 | 0.278518E+09 | 0.00 | 0.00 | 0.441074E+11 | 0.00 | 0.54 |
April | 0.847299E+10 | 0.00 | 0.00 | 0.197534E+09 | 0.00 | 0.00 | 0.503175E+11 | 0.00 | 0.72 |
May | 0.723952E+10 | 0.00 | 0.00 | 0.118654E+09 | 0.00 | 0.00 | 0.492267E+11 | 0.00 | 0.70 |
June | 0.726772E+10 | 0.199788E+09 | 0.00 | 0.342599E+09 | 0.00 | 0.00 | 0.421575E+11 | 0.00 | 0.88 |
July | 0.447029E+10 | 0.101800E+09 | 0.00 | 0.485355E+09 | 9959645.33 | 0.00 | 0.444462E+11 | 0.00 | 1.02 |
August | 0.219420E+10 | 11833282.21 | 0.00 | 0.198050E+09 | 0.00 | 0.00 | 0.506360E+11 | 0.00 | 1.22 |
September | 0.448393E+10 | 0.00 | 0.00 | 0.143039E+09 | 0.00 | 0.00 | 0.459752E+11 | 0.00 | 0.96 |
October | 0.108528E+11 | 0.00 | 0.00 | 0.295048E+09 | 0.00 | 0.00 | 0.473714E+11 | 0.00 | 0.70 |
November | 0.133130E+11 | 0.00 | 0.00 | 0.312847E+09 | 0.00 | 0.00 | 0.477241E+11 | 0.00 | 0.60 |
December | 0.131608E+11 | 0.00 | 0.00 | 0.164586E+09 | 0.00 | 0.00 | 0.464702E+11 | 0.00 | 0.50 |
Annual Sum or Average | 0.116119E+12 | 0.313421E+09 | 0.00 | 0.276401E+10 | 9959645.33 | 0.00 | 0.545062E+12 | 0.00 | 0.73 |
Minimum of Months | 0.219420E+10 | 0.00 | 0.00 | 82625885.89 | 0.00 | 0.00 | 0.299918E+11 | 0.00 | 0.46 |
Maximum of Months | 0.200391E+11 | 0.199788E+09 | 0.00 | 0.485355E+09 | 9959645.33 | 0.00 | 0.506360E+11 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.763634E+10 | 0.00 | 0.00 | 0.127930E+09 | 0.00 | 0.00 | 0.422518E+11 | 0.00 | 0.41 |
February | 0.128539E+11 | 0.00 | 0.00 | 0.310125E+09 | 0.00 | 0.00 | 0.327491E+11 | 0.00 | 0.43 |
March | 0.102340E+11 | 0.00 | 0.00 | 0.516547E+09 | 0.00 | 0.00 | 0.482591E+11 | 0.00 | 0.53 |
April | 0.453521E+10 | 0.00 | 0.00 | 0.349645E+09 | 0.00 | 0.00 | 0.596305E+11 | 0.00 | 0.78 |
May | 0.573583E+10 | 0.00 | 0.00 | 0.198777E+09 | 0.00 | 0.00 | 0.562047E+11 | 0.00 | 0.77 |
June | 0.585443E+10 | 34287.67 | 0.00 | 0.532059E+09 | 73156086.83 | 0.00 | 0.543945E+11 | 0.00 | 0.99 |
July | 0.702786E+10 | 21138083.88 | 0.00 | 0.635695E+09 | 6613696.43 | 0.00 | 0.500127E+11 | 0.00 | 1.07 |
August | 0.465907E+10 | 0.00 | 0.00 | 0.236247E+09 | 0.00 | 0.00 | 0.543786E+11 | 0.00 | 1.24 |
September | 0.547996E+10 | 0.00 | 0.00 | 0.181872E+09 | 0.00 | 0.00 | 0.486161E+11 | 0.00 | 0.98 |
October | 0.103051E+11 | 0.00 | 0.00 | 0.404496E+09 | 0.00 | 0.00 | 0.468632E+11 | 0.00 | 0.68 |
November | 0.863989E+10 | 0.00 | 0.00 | 0.489484E+09 | 0.00 | 0.00 | 0.455316E+11 | 0.00 | 0.53 |
December | 0.864982E+10 | 0.00 | 0.00 | 0.245835E+09 | 0.00 | 0.00 | 0.434187E+11 | 0.00 | 0.43 |
Annual Sum or Average | 0.916113E+11 | 21172371.55 | 0.00 | 0.422871E+10 | 79769783.25 | 0.00 | 0.582311E+12 | 0.00 | 0.74 |
Minimum of Months | 0.453521E+10 | 0.00 | 0.00 | 0.127930E+09 | 0.00 | 0.00 | 0.327491E+11 | 0.00 | 0.41 |
Maximum of Months | 0.128539E+11 | 21138083.88 | 0.00 | 0.635695E+09 | 73156086.83 | 0.00 | 0.596305E+11 | 0.00 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179983E+12 | 0.00 | 0.00 | 0.676773E+09 | 0.00 | 46304253.07 | 0.212465E+12 | 0.00 | 0.33 |
February | 0.171206E+12 | 0.00 | 0.00 | 0.180015E+10 | 0.00 | 0.00 | 0.190751E+12 | 0.00 | 0.34 |
March | 0.160957E+12 | 0.00 | 0.00 | 0.330438E+10 | 0.00 | 0.00 | 0.280099E+12 | 0.00 | 0.40 |
April | 0.107275E+12 | 1723264.97 | 0.00 | 0.210658E+10 | 0.00 | 0.00 | 0.375830E+12 | 0.00 | 0.60 |
May | 0.925834E+11 | 0.00 | 0.00 | 0.150605E+10 | 0.00 | 0.00 | 0.414795E+12 | 0.00 | 0.65 |
June | 0.103709E+12 | 2908682.67 | 0.00 | 0.376546E+10 | 0.774906E+09 | 0.00 | 0.389741E+12 | 0.00 | 0.83 |
July | 0.120198E+12 | 0.286502E+09 | 0.00 | 0.388446E+10 | 75875660.21 | 0.00 | 0.317522E+12 | 0.00 | 0.85 |
August | 0.916327E+11 | 0.00 | 0.00 | 0.128406E+10 | 0.00 | 0.00 | 0.349427E+12 | 0.00 | 0.96 |
September | 0.989086E+11 | 0.00 | 0.00 | 0.122645E+10 | 0.00 | 0.00 | 0.342092E+12 | 0.00 | 0.83 |
October | 0.139127E+12 | 0.00 | 0.00 | 0.268902E+10 | 0.00 | 0.00 | 0.303210E+12 | 0.00 | 0.54 |
November | 0.161200E+12 | 0.00 | 0.00 | 0.262284E+10 | 0.00 | 0.00 | 0.229740E+12 | 0.00 | 0.39 |
December | 0.203655E+12 | 0.00 | 0.00 | 0.942421E+09 | 0.00 | 0.00 | 0.158963E+12 | 0.00 | 0.30 |
Annual Sum or Average | 0.163044E+13 | 0.291134E+09 | 0.00 | 0.258086E+11 | 0.850781E+09 | 46304253.07 | 0.356463E+13 | 0.00 | 0.59 |
Minimum of Months | 0.916327E+11 | 0.00 | 0.00 | 0.676773E+09 | 0.00 | 0.00 | 0.158963E+12 | 0.00 | 0.30 |
Maximum of Months | 0.203655E+12 | 0.286502E+09 | 0.00 | 0.388446E+10 | 0.774906E+09 | 46304253.07 | 0.414795E+12 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.261626E+11 | 0.00 | 0.00 | 1304485.48 | 0.00 | 0.198200E+10 | 0.614665E+09 | 0.00 | 0.27 |
February | 0.243465E+11 | 0.00 | 0.00 | 4493139.37 | 0.00 | 0.129384E+10 | 0.703767E+09 | 0.00 | 0.27 |
March | 0.287165E+11 | 0.00 | 0.00 | 26034495.78 | 0.00 | 0.853674E+09 | 0.254906E+10 | 0.00 | 0.32 |
April | 0.186497E+11 | 0.00 | 0.00 | 0.104345E+09 | 5152526.13 | 0.100735E+09 | 0.216624E+11 | 0.00 | 0.52 |
May | 0.178326E+11 | 0.00 | 0.00 | 86468751.96 | 0.00 | 12850538.99 | 0.274668E+11 | 0.00 | 0.59 |
June | 0.135904E+11 | 0.00 | 0.00 | 0.294780E+09 | 55412099.60 | 0.00 | 0.347170E+11 | 0.00 | 0.80 |
July | 0.127869E+11 | 0.00 | 0.00 | 0.331618E+09 | 25850496.55 | 0.00 | 0.315824E+11 | 0.00 | 0.84 |
August | 0.119912E+11 | 0.00 | 0.00 | 88558347.61 | 0.00 | 0.00 | 0.305878E+11 | 0.00 | 0.91 |
September | 0.154433E+11 | 0.00 | 0.00 | 65645548.97 | 0.00 | 2081957.08 | 0.217135E+11 | 0.00 | 0.72 |
October | 0.243850E+11 | 0.00 | 0.00 | 51540716.48 | 0.00 | 0.473346E+09 | 0.607281E+10 | 0.00 | 0.41 |
November | 0.248410E+11 | 0.00 | 0.00 | 10010035.50 | 0.00 | 0.108058E+10 | 0.122281E+10 | 0.00 | 0.30 |
December | 0.244955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233833E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.243241E+12 | 0.00 | 0.00 | 0.106480E+10 | 86415122.28 | 0.813745E+10 | 0.178893E+12 | 0.00 | 0.52 |
Minimum of Months | 0.119912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.287165E+11 | 0.00 | 0.00 | 0.331618E+09 | 55412099.60 | 0.233833E+10 | 0.347170E+11 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.508404E+10 | 0.00 | 0.00 | 21558.40 | 0.00 | 0.292152E+09 | 73577310.07 | 0.00 | 0.35 |
February | 0.484071E+10 | 0.00 | 0.00 | 2164.69 | 0.00 | 97836875.87 | 6529832.39 | 0.00 | 0.36 |
March | 0.509490E+10 | 0.00 | 0.00 | 9339185.72 | 0.00 | 240167.04 | 0.957568E+09 | 0.00 | 0.43 |
April | 0.304867E+10 | 0.00 | 0.00 | 22327370.46 | 0.00 | 0.00 | 0.427137E+10 | 0.00 | 0.73 |
May | 0.293006E+10 | 0.00 | 0.00 | 15911174.44 | 0.00 | 0.00 | 0.454553E+10 | 0.00 | 0.76 |
June | 0.205043E+10 | 7836.62 | 0.00 | 58132427.51 | 10629878.02 | 0.00 | 0.604757E+10 | 0.00 | 1.10 |
July | 0.219949E+10 | 4556815.43 | 0.00 | 67625574.28 | 960997.09 | 0.00 | 0.566045E+10 | 0.00 | 1.22 |
August | 0.206924E+10 | 0.00 | 0.00 | 19121025.67 | 0.00 | 0.00 | 0.559132E+10 | 0.00 | 1.32 |
September | 0.309474E+10 | 0.00 | 0.00 | 11602427.80 | 0.00 | 0.00 | 0.343976E+10 | 0.00 | 0.96 |
October | 0.425602E+10 | 0.00 | 0.00 | 13990828.34 | 0.00 | 0.00 | 0.173808E+10 | 0.00 | 0.56 |
November | 0.519653E+10 | 0.00 | 0.00 | 1575722.67 | 0.00 | 13918992.02 | 0.214216E+09 | 0.00 | 0.42 |
December | 0.530461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41885636.05 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.451694E+11 | 4564652.06 | 0.00 | 0.219649E+09 | 11590875.11 | 0.446034E+09 | 0.325460E+11 | 0.00 | 0.71 |
Minimum of Months | 0.205043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.530461E+10 | 4556815.43 | 0.00 | 67625574.28 | 10629878.02 | 0.292152E+09 | 0.604757E+10 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.743962E+10 | 0.00 | 0.00 | 33538.38 | 0.00 | 0.698800E+09 | 37626621.18 | 0.00 | 0.82 |
February | 0.699527E+10 | 0.00 | 0.00 | 914288.63 | 0.00 | 0.300593E+09 | 0.126646E+09 | 0.00 | 0.84 |
March | 0.886665E+10 | 0.00 | 0.00 | 35158.55 | 0.00 | 39256028.28 | 26784929.60 | 0.00 | 0.98 |
April | 0.516486E+10 | 0.00 | 0.00 | 25104977.58 | 0.00 | 6102322.14 | 0.501714E+10 | 0.00 | 1.54 |
May | 0.570249E+10 | 0.00 | 0.00 | 15179941.68 | 0.00 | 1265657.40 | 0.482531E+10 | 0.00 | 1.63 |
June | 0.547391E+10 | 5401.52 | 0.00 | 42750896.19 | 15945215.45 | 0.00 | 0.457467E+10 | 0.00 | 2.07 |
July | 0.463334E+10 | 6331451.49 | 0.00 | 53264610.22 | 1441531.65 | 0.00 | 0.468850E+10 | 0.00 | 2.15 |
August | 0.395370E+10 | 0.00 | 0.00 | 18800848.33 | 0.00 | 0.00 | 0.557021E+10 | 0.00 | 2.42 |
September | 0.475476E+10 | 0.00 | 0.00 | 14343577.96 | 0.00 | 0.00 | 0.447060E+10 | 0.00 | 2.02 |
October | 0.773151E+10 | 0.00 | 0.00 | 7665639.80 | 0.00 | 5784004.49 | 0.999813E+09 | 0.00 | 1.25 |
November | 0.796285E+10 | 0.00 | 0.00 | 37100.06 | 0.00 | 0.146515E+09 | 21363411.02 | 0.00 | 0.97 |
December | 0.739249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632423E+09 | 0.00 | 0.00 | 0.80 |
Annual Sum or Average | 0.760714E+11 | 6336853.01 | 0.00 | 0.178131E+09 | 17386747.10 | 0.183074E+10 | 0.303587E+11 | 0.00 | 1.46 |
Minimum of Months | 0.395370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 |
Maximum of Months | 0.886665E+10 | 6331451.49 | 0.00 | 53264610.22 | 15945215.45 | 0.698800E+09 | 0.557021E+10 | 0.00 | 2.42 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.877851E+10 | 0.00 | 0.00 | 7348460.15 | 0.00 | 0.128254E+10 | 0.242487E+10 | 0.00 | 0.81 |
February | 0.784993E+10 | 0.00 | 0.00 | 30789493.22 | 0.00 | 0.889373E+09 | 0.312987E+10 | 0.00 | 0.88 |
March | 0.114560E+11 | 0.00 | 0.00 | 11470188.09 | 0.00 | 0.480500E+09 | 0.109125E+10 | 0.00 | 0.93 |
April | 0.717364E+10 | 0.00 | 0.00 | 48301057.74 | 0.00 | 12447365.77 | 0.902297E+10 | 0.00 | 1.64 |
May | 0.902606E+10 | 0.00 | 0.00 | 20134404.60 | 0.00 | 9779575.60 | 0.613274E+10 | 0.00 | 1.54 |
June | 0.838525E+10 | 9287.23 | 0.00 | 46431519.46 | 22875208.61 | 0.00 | 0.541888E+10 | 0.00 | 1.85 |
July | 0.731162E+10 | 4965032.06 | 0.00 | 64188872.59 | 4609515.95 | 0.00 | 0.604050E+10 | 0.00 | 2.04 |
August | 0.600033E+10 | 0.00 | 0.00 | 24862200.70 | 0.00 | 0.00 | 0.839936E+10 | 0.00 | 2.47 |
September | 0.666281E+10 | 0.00 | 0.00 | 30767594.63 | 0.00 | 1504984.41 | 0.879307E+10 | 0.00 | 2.33 |
October | 0.900511E+10 | 0.00 | 0.00 | 55109261.31 | 0.00 | 60521789.15 | 0.584795E+10 | 0.00 | 1.43 |
November | 0.981934E+10 | 0.00 | 0.00 | 21945176.39 | 0.00 | 0.440554E+09 | 0.216001E+10 | 0.00 | 0.96 |
December | 0.933500E+10 | 0.00 | 0.00 | 7046613.17 | 0.00 | 0.129620E+10 | 0.137550E+10 | 0.00 | 0.78 |
Annual Sum or Average | 0.100804E+12 | 4974319.29 | 0.00 | 0.368395E+09 | 27484724.56 | 0.447342E+10 | 0.598370E+11 | 0.00 | 1.47 |
Minimum of Months | 0.600033E+10 | 0.00 | 0.00 | 7046613.17 | 0.00 | 0.00 | 0.109125E+10 | 0.00 | 0.78 |
Maximum of Months | 0.114560E+11 | 4965032.06 | 0.00 | 64188872.59 | 22875208.61 | 0.129620E+10 | 0.902297E+10 | 0.00 | 2.47 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.956026E+10 | 0.00 | 0.00 | 524453.52 | 0.00 | 86329395.64 | 0.346897E+09 | 0.00 | 1.00 |
February | 0.828414E+10 | 0.00 | 0.00 | 8124743.60 | 0.00 | 2690924.49 | 0.944131E+09 | 0.00 | 1.05 |
March | 0.102954E+11 | 0.00 | 0.00 | 7414106.98 | 0.00 | 0.00 | 0.746801E+09 | 0.00 | 1.22 |
April | 0.555253E+10 | 0.00 | 0.00 | 34267250.73 | 0.00 | 0.00 | 0.719880E+10 | 0.00 | 1.98 |
May | 0.746355E+10 | 0.00 | 0.00 | 15314533.40 | 0.00 | 0.00 | 0.532484E+10 | 0.00 | 2.01 |
June | 0.604989E+10 | 17729711.54 | 0.00 | 49438840.03 | 6360673.67 | 0.00 | 0.623964E+10 | 0.00 | 2.57 |
July | 0.493327E+10 | 9033204.75 | 0.00 | 79712771.88 | 475338.41 | 0.00 | 0.698385E+10 | 0.00 | 2.86 |
August | 0.350200E+10 | 0.00 | 0.00 | 28257445.49 | 0.00 | 0.00 | 0.821920E+10 | 0.00 | 3.07 |
September | 0.659635E+10 | 0.00 | 0.00 | 11095666.70 | 0.00 | 0.00 | 0.414668E+10 | 0.00 | 2.41 |
October | 0.915466E+10 | 0.00 | 0.00 | 14118516.38 | 0.00 | 0.00 | 0.167322E+10 | 0.00 | 1.56 |
November | 0.956414E+10 | 0.00 | 0.00 | 2746696.53 | 0.00 | 426105.27 | 0.406549E+09 | 0.00 | 1.19 |
December | 0.963687E+10 | 0.00 | 0.00 | 558107.30 | 0.00 | 1469609.90 | 0.163126E+09 | 0.00 | 0.98 |
Annual Sum or Average | 0.905931E+11 | 26762916.30 | 0.00 | 0.251573E+09 | 6836012.07 | 90916035.30 | 0.423937E+11 | 0.00 | 1.83 |
Minimum of Months | 0.350200E+10 | 0.00 | 0.00 | 524453.52 | 0.00 | 0.00 | 0.163126E+09 | 0.00 | 0.98 |
Maximum of Months | 0.102954E+11 | 17729711.54 | 0.00 | 79712771.88 | 6360673.67 | 86329395.64 | 0.821920E+10 | 0.00 | 3.07 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.372346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215663E+11 | 0.00 | 0.00 | 0.39 |
February | 0.373508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155533E+11 | 0.00 | 0.00 | 0.39 |
March | 0.518496E+11 | 0.00 | 0.00 | 570.52 | 0.00 | 0.906871E+10 | 26944884.40 | 0.00 | 0.44 |
April | 0.429311E+11 | 0.00 | 0.00 | 73877684.82 | 169267.29 | 0.191123E+10 | 0.158561E+11 | 0.00 | 0.61 |
May | 0.444879E+11 | 0.00 | 0.00 | 66084241.77 | 0.00 | 0.546701E+09 | 0.206794E+11 | 0.00 | 0.68 |
June | 0.318550E+11 | 768733.02 | 0.00 | 0.342840E+09 | 0.130024E+09 | 0.00 | 0.362041E+11 | 0.00 | 0.95 |
July | 0.284415E+11 | 63350852.61 | 0.00 | 0.403894E+09 | 13953480.96 | 9587968.83 | 0.352920E+11 | 0.00 | 1.02 |
August | 0.292406E+11 | 0.00 | 0.00 | 91834014.20 | 0.00 | 0.00 | 0.326613E+11 | 0.00 | 1.08 |
September | 0.386737E+11 | 0.00 | 0.00 | 56977611.26 | 0.00 | 62838366.62 | 0.188848E+11 | 0.00 | 0.86 |
October | 0.501068E+11 | 0.00 | 0.00 | 12036723.65 | 0.00 | 0.596716E+10 | 0.158557E+10 | 0.00 | 0.54 |
November | 0.430736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126980E+11 | 0.00 | 0.00 | 0.44 |
December | 0.295911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265392E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.464836E+12 | 64119585.63 | 0.00 | 0.104755E+10 | 0.144147E+09 | 0.939232E+11 | 0.161190E+12 | 0.00 | 0.65 |
Minimum of Months | 0.284415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.518496E+11 | 63350852.61 | 0.00 | 0.403894E+09 | 0.130024E+09 | 0.265392E+11 | 0.362041E+11 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.412228E+11 | 0.00 | 0.00 | 660892.25 | 0.00 | 0.261544E+11 | 0.184923E+09 | 0.00 | 0.68 |
February | 0.408154E+11 | 0.00 | 0.00 | 4665571.76 | 0.00 | 0.199941E+11 | 0.436237E+09 | 0.00 | 0.69 |
March | 0.572208E+11 | 0.00 | 0.00 | 8610284.58 | 0.00 | 0.125367E+11 | 0.532904E+09 | 0.00 | 0.78 |
April | 0.428828E+11 | 523253.93 | 0.00 | 0.222341E+09 | 0.00 | 0.204422E+10 | 0.415040E+11 | 0.00 | 1.35 |
May | 0.503054E+11 | 0.00 | 0.00 | 0.137551E+09 | 0.00 | 0.773999E+09 | 0.399766E+11 | 0.00 | 1.46 |
June | 0.487310E+11 | 621495.56 | 0.00 | 0.399789E+09 | 0.184733E+09 | 24244924.29 | 0.398541E+11 | 0.00 | 1.89 |
July | 0.422249E+11 | 0.107665E+09 | 0.00 | 0.455882E+09 | 17283673.23 | 13660552.21 | 0.387604E+11 | 0.00 | 1.96 |
August | 0.382665E+11 | 0.00 | 0.00 | 0.161356E+09 | 0.00 | 27462213.70 | 0.461062E+11 | 0.00 | 2.24 |
September | 0.433200E+11 | 0.00 | 0.00 | 0.124217E+09 | 0.00 | 0.509481E+09 | 0.366652E+11 | 0.00 | 1.83 |
October | 0.546297E+11 | 0.00 | 0.00 | 65935567.77 | 0.00 | 0.823997E+10 | 0.717861E+10 | 0.00 | 1.02 |
November | 0.477881E+11 | 0.00 | 0.00 | 2144396.45 | 0.00 | 0.161161E+11 | 0.123148E+09 | 0.00 | 0.77 |
December | 0.309600E+11 | 0.00 | 0.00 | 68657.01 | 0.00 | 0.334549E+11 | 13248173.87 | 0.00 | 0.65 |
Annual Sum or Average | 0.538367E+12 | 0.108810E+09 | 0.00 | 0.158322E+10 | 0.202016E+09 | 0.119889E+12 | 0.251336E+12 | 0.00 | 1.28 |
Minimum of Months | 0.309600E+11 | 0.00 | 0.00 | 68657.01 | 0.00 | 13660552.21 | 13248173.87 | 0.00 | 0.65 |
Maximum of Months | 0.572208E+11 | 0.107665E+09 | 0.00 | 0.455882E+09 | 0.184733E+09 | 0.334549E+11 | 0.461062E+11 | 0.00 | 2.24 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.757900E+11 | 0.00 | 0.00 | 70945702.78 | 0.00 | 0.273241E+11 | 0.220530E+11 | 0.00 | 0.82 |
February | 0.697060E+11 | 0.00 | 0.00 | 0.314080E+09 | 0.00 | 0.191811E+11 | 0.299373E+11 | 0.00 | 0.89 |
March | 0.996507E+11 | 0.00 | 0.00 | 94003170.84 | 0.00 | 0.166807E+11 | 0.741564E+10 | 0.00 | 0.89 |
April | 0.653018E+11 | 0.00 | 0.00 | 0.446256E+09 | 340165.35 | 0.310989E+10 | 0.812298E+11 | 0.00 | 1.56 |
May | 0.849085E+11 | 0.00 | 0.00 | 0.186947E+09 | 0.00 | 0.294342E+10 | 0.547470E+11 | 0.00 | 1.49 |
June | 0.845249E+11 | 978906.83 | 0.00 | 0.366524E+09 | 0.261301E+09 | 99222962.83 | 0.434906E+11 | 0.00 | 1.77 |
July | 0.740102E+11 | 88663371.40 | 0.00 | 0.489789E+09 | 65857326.13 | 25640218.00 | 0.474442E+11 | 0.00 | 1.92 |
August | 0.617547E+11 | 0.00 | 0.00 | 0.211213E+09 | 0.00 | 14549155.61 | 0.713925E+11 | 0.00 | 2.38 |
September | 0.628985E+11 | 0.00 | 0.00 | 0.319961E+09 | 0.00 | 56470810.10 | 0.859472E+11 | 0.00 | 2.35 |
October | 0.770268E+11 | 0.00 | 0.00 | 0.578036E+09 | 0.00 | 0.849561E+10 | 0.577948E+11 | 0.00 | 1.42 |
November | 0.829123E+11 | 0.00 | 0.00 | 0.187563E+09 | 0.00 | 0.176815E+11 | 0.175101E+11 | 0.00 | 0.93 |
December | 0.644665E+11 | 0.00 | 0.00 | 54553493.62 | 0.00 | 0.417927E+11 | 0.947656E+10 | 0.00 | 0.77 |
Annual Sum or Average | 0.902951E+12 | 89642278.23 | 0.00 | 0.331987E+10 | 0.327499E+09 | 0.137405E+12 | 0.528439E+12 | 0.00 | 1.43 |
Minimum of Months | 0.617547E+11 | 0.00 | 0.00 | 54553493.62 | 0.00 | 14549155.61 | 0.741564E+10 | 0.00 | 0.77 |
Maximum of Months | 0.996507E+11 | 88663371.40 | 0.00 | 0.578036E+09 | 0.261301E+09 | 0.417927E+11 | 0.859472E+11 | 0.00 | 2.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.646062E+11 | 0.00 | 0.00 | 374322.94 | 0.00 | 0.255934E+11 | 0.325088E+09 | 0.00 | 0.92 |
February | 0.618901E+11 | 0.00 | 0.00 | 29464048.54 | 0.00 | 0.162993E+11 | 0.363133E+10 | 0.00 | 0.94 |
March | 0.809559E+11 | 0.00 | 0.00 | 18415133.13 | 0.00 | 0.113778E+11 | 0.174644E+10 | 0.00 | 1.05 |
April | 0.688825E+11 | 0.00 | 0.00 | 0.160170E+09 | 260990.83 | 0.126479E+10 | 0.299282E+11 | 0.00 | 1.58 |
May | 0.715847E+11 | 0.00 | 0.00 | 0.105992E+09 | 0.00 | 0.138369E+10 | 0.346884E+11 | 0.00 | 1.74 |
June | 0.672561E+11 | 0.209359E+09 | 0.00 | 0.302772E+09 | 48098836.84 | 24222897.28 | 0.358682E+11 | 0.00 | 2.21 |
July | 0.582389E+11 | 85076978.42 | 0.00 | 0.404949E+09 | 40357147.78 | 6998324.65 | 0.374173E+11 | 0.00 | 2.36 |
August | 0.521862E+11 | 0.00 | 0.00 | 0.118614E+09 | 0.00 | 0.00 | 0.394124E+11 | 0.00 | 2.46 |
September | 0.678041E+11 | 0.00 | 0.00 | 69432822.33 | 0.00 | 0.114147E+09 | 0.224117E+11 | 0.00 | 2.10 |
October | 0.753315E+11 | 0.00 | 0.00 | 83313694.36 | 0.00 | 0.708342E+10 | 0.841549E+10 | 0.00 | 1.33 |
November | 0.712612E+11 | 0.00 | 0.00 | 183235.56 | 0.00 | 0.144474E+11 | 0.182530E+09 | 0.00 | 1.04 |
December | 0.517537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345870E+11 | 0.00 | 0.00 | 0.89 |
Annual Sum or Average | 0.791751E+12 | 0.294436E+09 | 0.00 | 0.129368E+10 | 88716975.44 | 0.112182E+12 | 0.214027E+12 | 0.00 | 1.55 |
Minimum of Months | 0.517537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 |
Maximum of Months | 0.809559E+11 | 0.209359E+09 | 0.00 | 0.404949E+09 | 48098836.84 | 0.345870E+11 | 0.394124E+11 | 0.00 | 2.46 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.200643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442204E+10 | 0.00 | 0.00 | 0.48 |
February | 0.266432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322182E+10 | 0.00 | 0.00 | 0.49 |
March | 0.462335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250736E+10 | 0.00 | 0.00 | 0.56 |
April | 0.613472E+10 | 0.00 | 0.00 | 1780712.16 | 1149318.03 | 0.885169E+09 | 0.624565E+09 | 0.00 | 0.77 |
May | 0.643438E+10 | 0.00 | 0.00 | 2938155.46 | 0.00 | 0.664565E+09 | 0.133374E+10 | 0.00 | 0.87 |
June | 0.558143E+10 | 0.00 | 0.00 | 21310097.09 | 12360175.09 | 91185484.73 | 0.277381E+10 | 0.00 | 1.13 |
July | 0.478631E+10 | 0.00 | 0.00 | 23790151.66 | 5766189.44 | 55812621.06 | 0.296738E+10 | 0.00 | 1.18 |
August | 0.431628E+10 | 0.00 | 0.00 | 5611194.02 | 0.00 | 0.124007E+09 | 0.310212E+10 | 0.00 | 1.29 |
September | 0.522315E+10 | 0.00 | 0.00 | 1741766.97 | 0.00 | 0.604233E+09 | 0.109832E+10 | 0.00 | 1.06 |
October | 0.496288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172605E+10 | 0.00 | 0.00 | 0.70 |
November | 0.299267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306018E+10 | 0.00 | 0.00 | 0.54 |
December | 0.163015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437645E+10 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.513561E+11 | 0.00 | 0.00 | 57172077.35 | 19275682.56 | 0.217389E+11 | 0.118999E+11 | 0.00 | 0.80 |
Minimum of Months | 0.163015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55812621.06 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.643438E+10 | 0.00 | 0.00 | 23790151.66 | 12360175.09 | 0.442204E+10 | 0.310212E+10 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.264761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375599E+10 | 0.00 | 0.00 | 0.74 |
February | 0.305898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281013E+10 | 0.00 | 0.00 | 0.75 |
March | 0.484294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227218E+10 | 0.00 | 0.00 | 0.87 |
April | 0.438760E+10 | 1902217.80 | 0.00 | 16308266.67 | 0.00 | 0.529545E+09 | 0.339517E+10 | 0.00 | 1.32 |
May | 0.499017E+10 | 0.00 | 0.00 | 11760971.69 | 0.00 | 0.427767E+09 | 0.378241E+10 | 0.00 | 1.49 |
June | 0.514696E+10 | 0.00 | 0.00 | 35423145.01 | 12341812.48 | 65951478.08 | 0.411582E+10 | 0.00 | 1.95 |
July | 0.414298E+10 | 9501254.26 | 0.00 | 41976864.06 | 90978.96 | 33258805.90 | 0.422816E+10 | 0.00 | 1.98 |
August | 0.340194E+10 | 0.00 | 0.00 | 14279642.34 | 0.00 | 65674306.12 | 0.499619E+10 | 0.00 | 2.25 |
September | 0.371329E+10 | 0.00 | 0.00 | 9341017.51 | 0.00 | 0.398859E+09 | 0.337969E+10 | 0.00 | 1.80 |
October | 0.503381E+10 | 0.00 | 0.00 | 1372736.22 | 0.00 | 0.143809E+10 | 0.204736E+09 | 0.00 | 1.09 |
November | 0.330528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272754E+10 | 0.00 | 0.00 | 0.83 |
December | 0.210285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387716E+10 | 0.00 | 0.00 | 0.70 |
Annual Sum or Average | 0.467744E+11 | 11403472.06 | 0.00 | 0.130463E+09 | 12432791.45 | 0.184022E+11 | 0.241022E+11 | 0.00 | 1.32 |
Minimum of Months | 0.210285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33258805.90 | 0.00 | 0.00 | 0.70 |
Maximum of Months | 0.514696E+10 | 9501254.26 | 0.00 | 41976864.06 | 12341812.48 | 0.387716E+10 | 0.499619E+10 | 0.00 | 2.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.471134E+10 | 0.00 | 0.00 | 3514864.88 | 0.00 | 0.428461E+10 | 0.120541E+10 | 0.00 | 0.76 |
February | 0.460022E+10 | 0.00 | 0.00 | 21179360.13 | 0.00 | 0.329040E+10 | 0.192633E+10 | 0.00 | 0.81 |
March | 0.754336E+10 | 0.00 | 0.00 | 4377248.25 | 0.00 | 0.307930E+10 | 0.455355E+09 | 0.00 | 0.88 |
April | 0.582012E+10 | 0.00 | 0.00 | 38222702.46 | 1782554.76 | 0.120466E+10 | 0.787383E+10 | 0.00 | 1.54 |
May | 0.769483E+10 | 0.00 | 0.00 | 17267355.04 | 0.00 | 0.108194E+10 | 0.592813E+10 | 0.00 | 1.53 |
June | 0.853122E+10 | 0.00 | 0.00 | 34178124.44 | 19170228.20 | 0.347968E+09 | 0.491858E+10 | 0.00 | 1.84 |
July | 0.720628E+10 | 0.00 | 0.00 | 47820152.42 | 8943171.64 | 0.198005E+09 | 0.568732E+10 | 0.00 | 1.98 |
August | 0.572544E+10 | 0.00 | 0.00 | 19155146.50 | 0.00 | 0.159403E+09 | 0.825604E+10 | 0.00 | 2.42 |
September | 0.491463E+10 | 0.00 | 0.00 | 27981449.53 | 0.00 | 0.734396E+09 | 0.890171E+10 | 0.00 | 2.29 |
October | 0.582363E+10 | 0.00 | 0.00 | 45680285.95 | 0.00 | 0.189793E+10 | 0.468239E+10 | 0.00 | 1.33 |
November | 0.546419E+10 | 0.00 | 0.00 | 10214437.84 | 0.00 | 0.321142E+10 | 0.972974E+09 | 0.00 | 0.86 |
December | 0.358419E+10 | 0.00 | 0.00 | 2990607.17 | 0.00 | 0.532265E+10 | 0.459623E+09 | 0.00 | 0.71 |
Annual Sum or Average | 0.716195E+11 | 0.00 | 0.00 | 0.272582E+09 | 29895954.60 | 0.248127E+11 | 0.512677E+11 | 0.00 | 1.41 |
Minimum of Months | 0.358419E+10 | 0.00 | 0.00 | 2990607.17 | 0.00 | 0.159403E+09 | 0.455355E+09 | 0.00 | 0.71 |
Maximum of Months | 0.853122E+10 | 0.00 | 0.00 | 47820152.42 | 19170228.20 | 0.532265E+10 | 0.890171E+10 | 0.00 | 2.42 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.367235E+10 | 0.00 | 0.00 | 1809.40 | 0.00 | 0.387054E+10 | 8198225.19 | 0.00 | 0.87 |
February | 0.411413E+10 | 0.00 | 0.00 | 1195056.59 | 0.00 | 0.264630E+10 | 0.168066E+09 | 0.00 | 0.89 |
March | 0.627893E+10 | 0.00 | 0.00 | 920578.82 | 0.00 | 0.201910E+10 | 98952740.98 | 0.00 | 1.03 |
April | 0.599126E+10 | 0.00 | 0.00 | 15641342.35 | 1353972.32 | 0.811060E+09 | 0.322672E+10 | 0.00 | 1.60 |
May | 0.660328E+10 | 0.00 | 0.00 | 10428772.66 | 0.00 | 0.657914E+09 | 0.380742E+10 | 0.00 | 1.80 |
June | 0.683575E+10 | 15709392.93 | 0.00 | 30821766.20 | 3097012.35 | 0.113568E+09 | 0.408360E+10 | 0.00 | 2.30 |
July | 0.565664E+10 | 13078.04 | 0.00 | 41471442.07 | 6779872.84 | 80024537.55 | 0.451522E+10 | 0.00 | 2.43 |
August | 0.501317E+10 | 0.00 | 0.00 | 11736941.36 | 0.00 | 44551559.38 | 0.451120E+10 | 0.00 | 2.53 |
September | 0.583798E+10 | 0.00 | 0.00 | 6575655.03 | 0.00 | 0.525852E+09 | 0.242823E+10 | 0.00 | 2.12 |
October | 0.589301E+10 | 0.00 | 0.00 | 6627782.43 | 0.00 | 0.140849E+10 | 0.715442E+09 | 0.00 | 1.31 |
November | 0.453886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257372E+10 | 0.00 | 0.00 | 0.98 |
December | 0.271886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433082E+10 | 0.00 | 0.00 | 0.83 |
Annual Sum or Average | 0.631542E+11 | 15722470.97 | 0.00 | 0.125421E+09 | 11230857.51 | 0.190819E+11 | 0.235630E+11 | 0.00 | 1.56 |
Minimum of Months | 0.271886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44551559.38 | 0.00 | 0.00 | 0.83 |
Maximum of Months | 0.683575E+10 | 15709392.93 | 0.00 | 41471442.07 | 6779872.84 | 0.433082E+10 | 0.451522E+10 | 0.00 | 2.53 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 5974942.20 | 0.00 | 0.00 | 0.644546E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 46020539.64 | 0.00 | 0.00 | 0.523889E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 96619317.38 | 0.00 | 0.00 | 0.541138E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 67442022.01 | 0.00 | 0.00 | 0.416440E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 9286838.21 | 0.00 | 0.00 | 0.477838E+09 | 0.00 | 0.29 |
June | 0.00 | 61864.59 | 0.00 | 51625564.26 | 0.00 | 0.00 | 0.299548E+09 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.00 | 87721636.09 | 0.00 | 0.00 | 0.173383E+09 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 39434045.06 | 0.00 | 0.00 | 0.209888E+09 | 0.00 | 0.30 |
September | 0.00 | 0.00 | 0.00 | 8408632.57 | 0.00 | 0.00 | 0.323291E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 48916637.80 | 0.00 | 0.00 | 0.430182E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 85483462.93 | 0.00 | 0.00 | 0.464111E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 65394687.05 | 0.00 | 0.00 | 0.563529E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 61864.59 | 0.00 | 0.612328E+09 | 0.00 | 0.00 | 0.506778E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 5974942.20 | 0.00 | 0.00 | 0.173383E+09 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 61864.59 | 0.00 | 96619317.38 | 0.00 | 0.00 | 0.644546E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 75615221.57 | 0.00 | 0.00 | 41897171.02 | 0.00 | 0.00 | 0.638491E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 0.406138E+09 | 0.00 | 0.00 | 0.529266E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.885194E+09 | 0.00 | 0.00 | 0.549209E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.634570E+09 | 0.00 | 0.00 | 0.420460E+10 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 78856624.89 | 0.00 | 0.00 | 0.479175E+10 | 0.00 | 0.29 |
June | 0.00 | 570390.30 | 0.00 | 0.479609E+09 | 0.00 | 0.00 | 0.303458E+10 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.00 | 0.821710E+09 | 0.00 | 0.00 | 0.179224E+10 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 0.371899E+09 | 0.00 | 0.00 | 0.213467E+10 | 0.00 | 0.30 |
September | 0.00 | 0.00 | 0.00 | 70465315.62 | 0.00 | 0.00 | 0.325301E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 0.437178E+09 | 0.00 | 0.00 | 0.435439E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.772510E+09 | 0.00 | 0.00 | 0.472343E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.592857E+09 | 0.00 | 0.00 | 0.569596E+10 | 0.00 | 0.28 |
Annual Sum or Average | 75615221.57 | 570390.30 | 0.00 | 0.559288E+10 | 0.00 | 0.00 | 0.511543E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 41897171.02 | 0.00 | 0.00 | 0.179224E+10 | 0.00 | 0.28 |
Maximum of Months | 75615221.57 | 570390.30 | 0.00 | 0.885194E+09 | 0.00 | 0.00 | 0.638491E+10 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.204445E+09 | 0.00 | 0.00 | 1987319.16 | 0.00 | 0.00 | 0.443623E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 32676529.91 | 0.00 | 0.00 | 0.537227E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 79806166.79 | 0.00 | 0.00 | 0.557946E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 61019471.51 | 0.00 | 0.00 | 0.422895E+09 | 0.00 | 0.29 |
May | 22453474.50 | 0.00 | 0.00 | 6752600.15 | 0.00 | 0.00 | 0.457954E+09 | 0.00 | 0.29 |
June | 0.00 | 61482.47 | 0.00 | 46127801.94 | 0.00 | 0.00 | 0.305476E+09 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.00 | 80565491.34 | 0.00 | 0.00 | 0.180970E+09 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 36395883.72 | 0.00 | 0.00 | 0.215977E+09 | 0.00 | 0.30 |
September | 11141237.83 | 0.00 | 0.00 | 5770775.61 | 0.00 | 0.00 | 0.315988E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 37083155.30 | 0.00 | 0.00 | 0.442386E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 68268898.52 | 0.00 | 0.00 | 0.481458E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 53737027.36 | 0.00 | 0.00 | 0.575241E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.238040E+09 | 61482.47 | 0.00 | 0.510191E+09 | 0.00 | 0.00 | 0.493714E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1987319.16 | 0.00 | 0.00 | 0.180970E+09 | 0.00 | 0.28 |
Maximum of Months | 0.204445E+09 | 61482.47 | 0.00 | 80565491.34 | 0.00 | 0.00 | 0.575241E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.731328E+09 | 0.00 | 0.00 | 0.322758E+12 | 0.00 | 7.08 |
February | 0.318706E+10 | 0.00 | 0.00 | 0.266854E+10 | 0.00 | 0.00 | 0.442111E+12 | 0.00 | 11.74 |
March | 79516234.55 | 0.00 | 0.00 | 0.614637E+10 | 0.00 | 0.00 | 0.715935E+12 | 0.00 | 18.75 |
April | 0.00 | 0.00 | 0.00 | 0.545771E+10 | 0.00 | 0.00 | 0.934661E+12 | 0.00 | 33.57 |
May | 0.00 | 0.00 | 0.00 | 0.856995E+09 | 0.00 | 0.00 | 0.296253E+12 | 0.00 | 9.83 |
June | 0.108350E+10 | 98285.19 | 0.00 | 0.316864E+10 | 299732.57 | 0.00 | 0.398334E+12 | 0.00 | 20.35 |
July | 0.129550E+09 | 0.00 | 0.00 | 0.724878E+10 | 0.00 | 0.00 | 0.591286E+12 | 0.00 | 33.50 |
August | 0.00 | 0.00 | 0.00 | 0.395673E+10 | 0.00 | 0.00 | 0.815786E+12 | 0.00 | 51.82 |
September | 831586.89 | 0.00 | 0.00 | 0.835756E+09 | 0.00 | 0.00 | 0.270522E+12 | 0.00 | 13.00 |
October | 0.177010E+10 | 0.00 | 0.00 | 0.310822E+10 | 0.00 | 0.00 | 0.459409E+12 | 0.00 | 16.00 |
November | 14760929.34 | 0.00 | 0.00 | 0.601742E+10 | 0.00 | 0.00 | 0.659229E+12 | 0.00 | 19.45 |
December | 0.00 | 0.00 | 0.00 | 0.604457E+10 | 0.00 | 0.00 | 0.100494E+13 | 0.00 | 25.29 |
Annual Sum or Average | 0.626532E+10 | 98285.19 | 0.00 | 0.462411E+11 | 299732.57 | 0.00 | 0.691123E+13 | 0.00 | 21.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.731328E+09 | 0.00 | 0.00 | 0.270522E+12 | 0.00 | 7.08 |
Maximum of Months | 0.318706E+10 | 98285.19 | 0.00 | 0.724878E+10 | 299732.57 | 0.00 | 0.100494E+13 | 0.00 | 51.82 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:26:36
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.158384E+12 | 0.637074E+10 | 0.00 | 0.263533E+13 | 0.193233E+12 |
February | 0.243269E+12 | 0.908142E+10 | 0.00 | 0.257200E+13 | 0.415959E+12 |
March | 0.294141E+12 | 0.557732E+10 | 0.00 | 0.319792E+13 | 0.656045E+12 |
April | 0.744668E+12 | 0.683929E+10 | 0.00 | 0.366691E+13 | 0.749908E+12 |
May | 0.895199E+12 | 0.160825E+11 | 0.00 | 0.297990E+13 | 0.254459E+12 |
June | 0.899908E+12 | 0.126965E+11 | 0.00 | 0.306481E+13 | 0.720736E+12 |
July | 0.910092E+12 | 0.119801E+11 | 0.00 | 0.326188E+13 | 0.110739E+13 |
August | 0.745313E+12 | 0.880298E+10 | 0.00 | 0.338553E+13 | 0.132597E+13 |
September | 0.553164E+12 | 0.938617E+10 | 0.00 | 0.297169E+13 | 0.474326E+12 |
October | 0.257630E+12 | 0.946790E+10 | 0.00 | 0.302106E+13 | 0.442338E+12 |
November | 0.115707E+12 | 0.117262E+11 | 0.00 | 0.301006E+13 | 0.643555E+12 |
December | 0.616064E+11 | 0.162151E+11 | 0.00 | 0.322037E+13 | 0.721977E+12 |
Annual Sum or Average | 0.587908E+13 | 0.124226E+12 | 0.00 | 0.369875E+14 | 0.770590E+13 |
Minimum of Months | 0.616064E+11 | 0.557732E+10 | 0.00 | 0.257200E+13 | 0.193233E+12 |
Maximum of Months | 0.910092E+12 | 0.162151E+11 | 0.00 | 0.366691E+13 | 0.132597E+13 |