Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2024-07-03 12:21:51
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31702.77 | 684.42 | 684.42 |
Net Site Energy | 31702.77 | 684.42 | 684.42 |
Total Source Energy | 96671.98 | 2087.03 | 2087.03 |
Net Source Energy | 96671.98 | 2087.03 | 2087.03 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1791.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1005.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2648.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 788.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 55.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3811.30 |
Humidification | 613.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.10 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 438.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 29911.75 | 1791.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6319.57 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1791.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 1005.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 56.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2648.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 788.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 55.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3811.30 |
Humidification | General | 613.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.10 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 438.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1791.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 1005.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2648.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 788.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 55.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3811.30 |
Humidification | Unassigned | 613.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.10 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 438.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 129.46 | 38.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 645.76 | 38.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 129.46 | 38.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 645.76 | 38.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 29911.749 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 29911.749 | 100.00 |
Total On-Site and Utility Electric Sources | 29911.749 | 100.00 |
Total Electricity End Uses | 29911.749 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 6319.57 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 6319.57 | 100.00 |
Total Water End Uses | 6319.57 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 17.33 |
Time Setpoint Not Met During Occupied Cooling | 65.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4854.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS SZVAV FAN | AIRLOOP DATACENTER BASEMENT SYS11 FAN | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 11.6510 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 11.6510 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 11.6510 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.6510 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 11.6510 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.6510 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 11.6510 | 18.58 | 484.4232 | |
Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.6100 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-AUG-15:09 | 02-JAN-06:10 | - | - | - | - | - | - | - | - | - | - | 10-AUG-15:00 |
Heating | 0.00 | 1676942.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 385835.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235096.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 292322.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 83065.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 47672.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 33871.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2346135.99 | 1676942.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1676942.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 385835.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 292322.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 83065.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 47672.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 33871.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1941.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4599.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17769.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3182.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8307.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8386.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2498.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 176.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1941.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1388.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 94730.51 | 1941.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 41.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 99.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 181.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 53.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 41.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 29.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2045.12 | 41.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 41.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 99.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 181.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 53.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 41.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 29.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2045.12 | 41.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 7.16 | 0.295700 | 0.300000 | 2.15 |
DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | 31.85 | 0.018747 | 0.500000 | 15.93 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 7.48 | 0.254379 | 0.300000 | 2.24 | 0.678344 | 0.500000 | 0.001498 | 0.000193 | 2.24 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 70.72 | 0.268967 | 0.300000 | 21.21 | 0.717246 | 0.500000 | 0.001417 | 0.004317 | 21.21 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 7.58 | 0.251000 | 0.300000 | 2.27 | 0.669333 | 0.500000 | 0.001518 | 0.001263 | 6.16 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.16 | 0.205775 | 0.300000 | 0.348177 | 0.548734 | 0.500000 | 0.001852 | 0.000170 | 0.828049 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.70 | 0.090560 | 0.300000 | 0.509846 | 0.300000 | 0.500000 | 0.004207 | 0.000118 | 0.576728 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 2.43 | 0.098082 | 0.300000 | 0.730485 | 0.300000 | 0.500000 | 0.003884 | 0.000197 | 0.961963 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 2.05 | 0.074989 | 0.300000 | 0.615711 | 0.300000 | 0.500000 | 0.005081 | 0.000103 | 0.615711 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 14.40 | 0.165900 | 0.300000 | 4.32 | 0.442401 | 0.500000 | 0.002297 | 0.002945 | 14.40 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 17.63 | 0.300000 | 0.500000 | 0.004364 | 0.001957 | 9.56 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 25.01 | 0.095506 | 0.300000 | 7.50 | 0.300000 | 0.500000 | 0.003989 | 0.002900 | 14.17 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 19.01 | 0.080965 | 0.300000 | 5.70 | 0.300000 | 0.500000 | 0.004706 | 0.001831 | 8.95 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.91 | 0.125270 | 0.300000 | 0.571934 | 0.334053 | 0.500000 | 0.003041 | 0.000390 | 1.91 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.75 | 0.088085 | 0.300000 | 0.524171 | 0.300000 | 0.500000 | 0.004325 | 0.000257 | 1.26 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 2.71 | 0.088010 | 0.300000 | 0.814090 | 0.300000 | 0.500000 | 0.004329 | 0.000385 | 1.88 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 2.04 | 0.075546 | 0.300000 | 0.611174 | 0.300000 | 0.500000 | 0.005043 | 0.000247 | 1.21 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 22022.41 | 0.000193 | 444.28 | |
CORE_MID VAV BOX REHEAT COIL | 493494.35 | 0.004317 | 11510.21 | |
CORE_TOP VAV BOX REHEAT COIL | 144389.49 | 0.001263 | 3375.24 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 19404.72 | 0.000170 | 453.52 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 13510.88 | 0.000118 | 315.74 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 22530.71 | 0.000197 | 526.50 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11738.35 | 0.000103 | 260.92 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 336681.49 | 0.002945 | 7864.51 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 223647.13 | 0.001957 | 5224.03 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 331504.41 | 0.002900 | 7743.66 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 209337.31 | 0.001831 | 4889.99 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 44560.72 | 0.000390 | 1040.71 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 29380.21 | 0.000257 | 686.16 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 44034.54 | 0.000385 | 1028.43 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 28234.54 | 0.000247 | 659.42 | |
VAV_BOT WITH REHEAT HEATING COIL | 44661.47 | 0.000391 | 763.89 | |
VAV_MID WITH REHEAT HEATING COIL | 318641.32 | 0.002788 | 5534.35 | |
VAV_TOP WITH REHEAT HEATING COIL | 27051.18 | 0.000237 | 477.55 | |
CAV_BAS HEATING COIL | 88307.14 | 0.000875 | 2622.59 | 100000.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 554696.51 | 0.000875 | 2622.59 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.785813 |
DATACENTER_MID_ZN_6 DIRECT AIR | 7.57 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.776438 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 7.41 | 4.45 | 14.82 | 4.45 | 12.45 | 12.45 | 0.300000 | 0.357190 | 12.45 |
VAV_MID WITH REHEAT | 73.38 | 44.03 | 146.76 | 67.67 | 115.31 | 115.31 | 0.300000 | 0.586848 | 115.31 |
VAV_TOP WITH REHEAT | 7.99 | 4.79 | 15.98 | 12.41 | 13.96 | 13.96 | 0.300000 | 0.889347 | 13.96 |
CAV_BAS | 2.15 | 2.15 | 7.16 | 2.15 | 7.16 | 7.16 | 1.00 | 0.300000 | 7.16 |
AIRLOOP DATACENTER BASEMENT | 15.93 | 15.93 | 31.85 | 15.93 | 31.86 | 31.86 | 1.00 | 0.499964 | 31.86 |
AIRLOOP DATACENTER BOT | 0.785813 | 0.785813 | 0.785813 | 0.785813 | 0.785813 | 0.785813 | 1.00 | 1.00 | 0.785813 |
AIRLOOP DATACENTER MID | 7.57 | 7.57 | 7.57 | 7.57 | 7.57 | 7.57 | 1.00 | 1.00 | 7.57 |
AIRLOOP DATACENTER TOP | 0.776438 | 0.776438 | 0.776438 | 0.776438 | 0.776438 | 0.776438 | 1.00 | 1.000000 | 0.776438 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 12.45 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 115.31 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 13.96 | |
CAV_BAS_OA_CONTROLLER | 7.16 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 31.86 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.785813 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 7.57 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.776438 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 24.88 | 6.67 | 11.09 | 0.008798 | 0.008500 | 219294.26 | 0.007833 | 12.45 |
VAV_MID WITH REHEAT COOLING COIL | 24.95 | 6.67 | 11.09 | 0.008818 | 0.008500 | 2047854.70 | 0.073145 | 115.31 |
VAV_TOP WITH REHEAT COOLING COIL | 24.78 | 6.67 | 11.09 | 0.008772 | 0.008500 | 242996.28 | 0.008679 | 13.96 |
CAV_BAS COOLING COIL | 23.72 | 6.67 | 11.08 | 0.008892 | 0.008500 | 115532.61 | 0.004127 | 7.16 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 27.02 | 6.67 | 15.03 | 0.008536 | 0.008500 | 450413.74 | 0.016088 | 31.86 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 12.45 |
VAV_MID WITH REHEAT FAN | 115.31 |
VAV_TOP WITH REHEAT FAN | 13.96 |
CAV_BAS SZVAV FAN | 7.16 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | 31.86 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007833 | 0.000061 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000391 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.073145 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.002788 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.008679 | 0.000055 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000237 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | Design Size Minimum Supply Air Temperature [C] | User-Specified Minimum Supply Air Temperature [C] | User-Specified Maximum Supply Air Temperature [C] | User-Specified Nominal Cooling Capacity [W] | Design Size Maximum Supply Air Temperature [C] | |
CAV_BAS_UNITARY_PACKAGE_DX | 7.16 | 7.16 | 7.16 | 2.15 | 115532.61 | 100000.00 | 1.00 | 5.33 | 12.89 | 32.11 | ||
AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | 31.86 | 31.86 | 31.86 | 15.93 | 450413.74 | 100000.00 | 1.00 | 15.89 | 29.11 | |||
AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | 0.785813 | 0.785813 | 0.785813 | 0.785813 | 27362.66 | 1.00 | 13007.99 | 29.11 | ||||
AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | 7.57 | 7.57 | 7.57 | 7.57 | 263502.06 | 1.00 | 125252.98 | 29.11 | ||||
AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | 0.776438 | 0.776438 | 0.776438 | 0.776438 | 27037.16 | 1.00 | 12852.81 | 29.11 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000212 | 0.000037 | 96450.70 | 100000.00 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | 0.785813 | 1351.31 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | 7.57 | 13011.70 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | 0.776438 | 1335.19 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
AIRLOOP DATACENTER BOT COOLING COIL | 0.785810 | 0.392906 | 0.523873 | 13007.99 | 6503.99 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER MID COOLING COIL | 7.57 | 3.78 | 5.04 | 125252.98 | 62626.49 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.776440 | 0.388219 | 0.517627 | 12852.81 | 6426.40 | 0.800660 | 0.800660 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BOT HEATING COIL | 27362.66 |
AIRLOOP DATACENTER MID HEATING COIL | 263502.06 |
AIRLOOP DATACENTER TOP HEATING COIL | 27037.16 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.109871 | 22640.33 | |
HEATSYS1 PUMP | 0.022438 | 6757.40 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.109871 | 13.18 |
HEATSYS1 | 0.022438 | 2.69 |
COOLSYS1_SUPPLY | 0.109871 | 13.18 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.109871 | 0.109871 | 461183.15 | 6.67 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2564825.23 | 2564825.23 | 0.022438 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.054935 | 10449.55 |
COOLSYS1 CHILLER2 PUMP | 0.054935 | 10449.55 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.109871 | 0.055470 | 1553012.29 | 1553079.00 | 0.077835 |
COOLSYS1 CHILLER2 | 0.109871 | 0.055470 | 1553012.29 | 1553079.00 | 0.077835 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.155670 | 18.68 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.155670 | 54282.20 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 63.64 | 1861565.09 | 12.73 | 232695.64 |
TOWERWATERSYS COOLTOWER 2 | 63.64 | 1861565.09 | 12.73 | 232695.64 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 11.651 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 16.493 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 11.651 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 496.074 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 32383.100 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 32383.100 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 9130.649 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 9130.649 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
26 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
27 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
35 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
47 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
48 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
49 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
50 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
51 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
52 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
53 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
54 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
55 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
56 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
57 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
58 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
59 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
60 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
61 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
62 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
63 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
64 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
65 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
66 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
67 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
68 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
69 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
70 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
71 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
72 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
73 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
74 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
75 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
76 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
77 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
78 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
79 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
80 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
81 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
82 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
83 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
84 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
85 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
86 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
87 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
88 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
89 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
90 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
91 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
92 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
93 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
94 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
95 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
96 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
97 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
98 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
99 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
100 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
101 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
102 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
103 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
104 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
105 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
106 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
107 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
108 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
109 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
110 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
111 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
112 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
113 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
114 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
115 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
116 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
117 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
118 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
119 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
120 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
121 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone BASEMENT | 1.2500 |
3 | Zone CORE_BOTTOM | 1.2500 |
4 | Zone CORE_MID | 1.2500 |
5 | Zone CORE_TOP | 1.2500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.2500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.2500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.2500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone BASEMENT | 1.1500 |
3 | Zone CORE_BOTTOM | 1.1500 |
4 | Zone CORE_MID | 1.1500 |
5 | Zone CORE_TOP | 1.1500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.1500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.1500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.1500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 84573.01438 | 97258.96653 | 6.22818 | 7.16240 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | -4.20000 | 2.69032E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 88297.53191 | 101542.16170 | 6.50191 | 7.47720 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 835268.12837 | 960558.34763 | 61.49265 | 70.71655 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 228171.49624 | 285214.37030 | 16.47006 | 20.58757 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 88690.63193 | 101994.22672 | 6.58945 | 7.57786 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.82150E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 67150.69326 | 83938.36658 | 4.92595 | 6.15744 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 13583.58677 | 15621.12479 | 1.00921 | 1.16059 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 9023.83581 | 11279.79477 | 0.66244 | 0.82805 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 19891.08333 | 22874.74582 | 1.47782 | 1.69949 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 23.35067 | 8.81188E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 6281.34344 | 7851.67929 | 0.46138 | 0.57673 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 28499.02092 | 32773.87406 | 2.11735 | 2.43495 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.82094E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 10472.59947 | 13090.74934 | 0.76957 | 0.96196 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 24021.30288 | 27624.49832 | 1.78467 | 2.05237 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 4559.21527 | 5699.01909 | 0.33390 | 0.41737 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 126527.08643 | 145506.14939 | 9.40048 | 10.81055 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 156358.96099 | 195448.70124 | 11.51633 | 14.39541 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 206340.23385 | 237291.26893 | 15.33014 | 17.62966 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 23.97467 | 8.81286E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 103858.72471 | 129823.40589 | 7.65056 | 9.56321 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 292676.56047 | 336578.04454 | 21.74457 | 25.00626 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 153960.06421 | 192450.08026 | 11.33878 | 14.17348 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 222483.57530 | 255856.11159 | 16.52951 | 19.00894 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 27.77067 | 8.81889E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 97227.11616 | 121533.89521 | 7.15991 | 8.94989 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 15238.76265 | 17524.57705 | 1.13218 | 1.30201 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 20685.29172 | 25856.61465 | 1.52516 | 1.90645 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 20449.90942 | 23517.39583 | 1.51934 | 1.74724 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 24.26933 | 8.81333E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 13638.05978 | 17047.57472 | 1.00563 | 1.25704 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 31760.72623 | 36524.83517 | 2.35968 | 2.71363 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.82122E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 20441.46231 | 25551.82788 | 1.50711 | 1.88389 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 23844.22825 | 27420.86249 | 1.77152 | 2.03725 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 13107.03078 | 16383.78847 | 0.96635 | 1.20794 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 9197.16685 | 10576.74187 | 0.68332 | 0.78581 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 25.60400 | 8.81543E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 88558.52196 | 101842.30025 | 6.57959 | 7.56653 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 25.60400 | 8.81543E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 9087.43325 | 10450.54824 | 0.67516 | 0.77644 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 25.86400 | 8.81585E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372823.76671 | 428747.33171 | 27.69898 | 31.85383 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 19.93600 | 8.80655E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -4.20000 | 2.69032E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 178075.41 | 12.45103 | 12.45103 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 42514.05 | 3.86193 | 3.86193 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1658843.71 | 115.31014 | 115.31014 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 410448.25 | 67.66956 | 67.66956 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:10:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 197993.71 | 13.95716 | 13.95716 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 41372.43 | 12.41276 | 12.41276 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:40:00 |
7 | CAV_BAS | Cooling | Sensible | 92082.99 | 7.16240 | 7.16240 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 51977.62 | 1.20016 | 1.20016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 422714.23 | 31.85613 | 31.85613 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 13444.60 | 0.33839 | 0.33839 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 10387.66 | 0.78581 | 0.78581 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 621.08 | 1.56323E-002 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 100007.41 | 7.56653 | 7.56653 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6210.85 | 0.15632 | 0.15632 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 10267.79 | 0.77644 | 0.77644 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 621.08 | 1.56323E-002 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 7.16240 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.29570 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 2.14872 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.47720 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25438 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.24316 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67834 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49776E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.92662E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.24316 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22022.40881 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.92662E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 444.28097 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 70.71655 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26897 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 21.21496 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71725 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.41653E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.31730E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 21.21496 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 493494.34598 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.31730E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 11510.20509 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.57786 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25100 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.27336 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66933 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.51793E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.26318E-003 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.15744 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 144389.49496 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.26318E-003 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3375.24183 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.16059 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20578 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34818 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54873 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.85153E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.69761E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.82805 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19404.71842 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69761E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 453.52104 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.69949 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.05597E-002 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.50985 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.20717E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.18199E-004 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.57673 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13510.87565 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.18199E-004 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 315.74398 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.43495 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.80824E-002 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.73049 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.88449E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.97108E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.96196 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22530.70813 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.97108E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 526.50159 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.05237 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.49890E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.61571 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.08074E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02692E-004 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.61571 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11738.34593 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02692E-004 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 260.91533 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.39541 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16590 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.31862 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44240 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.29656E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.94544E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 14.39541 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 336681.49495 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.94544E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7864.50597 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 17.62966 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.36431E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.95656E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.56321 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 223647.13364 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.95656E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5224.03082 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 25.00626 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.55064E-002 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 7.50188 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.98926E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.90015E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 14.17348 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 331504.40523 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.90015E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7743.66209 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 19.00894 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.09646E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.70268 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.70576E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.83137E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.94989 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 209337.30868 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.83137E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4889.99232 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.90645 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12527 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.57193 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33405 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.04143E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.89837E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.90645 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 44560.71941 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.89837E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1040.71097 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.74724 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.80848E-002 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.52417 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.32538E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.57031E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.25704 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29380.21333 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.57031E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 686.16277 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.71363 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.80096E-002 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81409 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.32907E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.85233E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.88389 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 44034.54492 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.85233E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1028.42877 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.03725 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.55457E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.61117 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.04331E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.47008E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20794 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 28234.54255 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.47008E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 659.41761 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.78581 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.56653 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.77644 |
215 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 31.85383 |
216 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 1.87470E-002 |
217 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
218 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 15.92691 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.41230 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.44738 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 14.82460 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.44738 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 12.45103 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 12.45103 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.35719 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 73.37841 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 44.02705 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 146.75682 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 67.66956 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 115.31014 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 115.31014 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.58685 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.99121 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.79473 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 15.98242 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 12.41276 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 13.95716 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 13.95716 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.88935 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.14872 |
244 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.14872 |
245 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.16240 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.14872 |
247 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.16240 |
248 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 7.16240 |
249 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.30000 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 15.92691 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 15.92691 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 31.85383 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 15.92691 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 31.85613 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 31.85613 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.49996 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.78581 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.78581 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.78581 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.78581 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.78581 |
264 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.78581 |
265 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.56653 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.56653 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.56653 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 7.56653 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.56653 |
272 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 7.56653 |
273 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
274 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.77644 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.77644 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.77644 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.77644 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.77644 |
280 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.77644 |
281 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
282 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
283 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 12.45103 |
284 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 115.31014 |
285 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 13.95716 |
286 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 7.16240 |
287 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 31.85613 |
288 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.78581 |
289 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 7.56653 |
290 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.77644 |
291 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 12.45103 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.87965 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.08541 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.79798E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 219294.25778 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.83268E-003 |
299 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 12.45103 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 44661.46531 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.90718E-004 |
302 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 763.88623 |
303 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 12.45103 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.83268E-003 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.07953E-005 |
306 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.90718E-004 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 115.31014 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.94997 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.08547 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.81843E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2047854.70061 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.31446E-002 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 115.31014 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 318641.31999 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.78761E-003 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5534.34539 |
319 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 115.31014 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.31446E-002 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.51026E-006 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.78761E-003 |
323 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 13.95716 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.78478 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.09296 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.77210E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 242996.28084 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.67926E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 13.95716 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 27051.18022 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.36656E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 477.54867 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 13.95716 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.67926E-003 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.48653E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.36656E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.16240 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.16240 |
342 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.16240 |
343 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.16240 |
344 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.14872 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 23.72311 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.07608 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.89244E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 115532.60968 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.12656E-003 |
352 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.16240 |
353 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 115532.60968 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 88307.14154 |
355 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
356 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
357 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.58834 |
358 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
359 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
360 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Minimum Supply Air Temperature [C] | 5.33160 |
361 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 12.88890 |
362 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 32.11110 |
363 | Fan:VariableVolume | CAV_BAS SZVAV FAN | Design Size Maximum Flow Rate [m3/s] | 7.16240 |
364 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 31.85613 |
365 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
366 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 31.85613 |
367 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 31.85613 |
368 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 31.85613 |
369 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 15.92807 |
370 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.02350 |
371 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
372 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 15.03203 |
373 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.53604E-003 |
374 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
375 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Coil Load [W] | 450413.74390 |
376 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.60877E-002 |
377 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 31.85613 |
378 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 450413.74390 |
379 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Capacity [W] | 554696.50764 |
380 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
381 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
382 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.58834 |
383 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
384 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
385 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 15.88890 |
386 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 29.11110 |
387 | Fan:VariableVolume | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Design Size Maximum Flow Rate [m3/s] | 31.85613 |
388 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.11640E-004 |
389 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
390 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
391 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.78581 |
393 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
394 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.78581 |
395 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1351.31437 |
396 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.78581 |
397 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.78581 |
398 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.78581 |
399 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.78581 |
400 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.78581 |
401 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.39291 |
402 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.52387 |
403 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 13007.99000 |
404 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6503.99500 |
405 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
406 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
407 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 13007.99000 |
408 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27362.66216 |
409 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
410 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
411 | Coil:Heating:Fuel | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Nominal Capacity [W] | 27362.66216 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.56653 |
413 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
414 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.56653 |
415 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 13011.70354 |
416 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.56653 |
417 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.56653 |
418 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.56653 |
419 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 7.56653 |
420 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.56653 |
421 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.78327 |
422 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.04435 |
423 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 125252.98000 |
424 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 62626.49000 |
425 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
426 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
427 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 125252.98000 |
428 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 263502.05787 |
429 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
430 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
431 | Coil:Heating:Fuel | AIRLOOP DATACENTER MID HEATING COIL | Design Size Nominal Capacity [W] | 263502.05787 |
432 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.77644 |
433 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
434 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.77644 |
435 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1335.19323 |
436 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.77644 |
437 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.77644 |
438 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.77644 |
439 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77644 |
440 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.77644 |
441 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.38822 |
442 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.51763 |
443 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 12852.81000 |
444 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6426.40500 |
445 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
446 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
447 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 12852.81000 |
448 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27037.16067 |
449 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
450 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
451 | Coil:Heating:Fuel | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Nominal Capacity [W] | 27037.16067 |
452 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.10987 |
453 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 22640.33142 |
454 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.10987 |
455 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 13.18450 |
456 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.10987 |
457 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.10987 |
458 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 461183.14735 |
459 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 6.67000 |
460 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.24382E-002 |
461 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.69259 |
462 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.24382E-002 |
463 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 6757.40347 |
464 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
465 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2564825.22612 |
466 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2564825.23000 |
467 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.24382E-002 |
468 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.10987 |
469 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 13.18450 |
470 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 5.49354E-002 |
471 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 10449.55118 |
472 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 5.49354E-002 |
473 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 10449.55118 |
474 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.10987 |
475 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.54700E-002 |
476 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1553012.28784 |
477 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1553078.99500 |
478 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 7.78348E-002 |
479 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.10987 |
480 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.54700E-002 |
481 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1553012.28784 |
482 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1553078.99500 |
483 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 7.78348E-002 |
484 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
485 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
486 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
487 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
488 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
489 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.15567 |
490 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 18.68036 |
491 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.15567 |
492 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 54282.20380 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 63.64185 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1861565.09258 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 12.72837 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 232695.63657 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 63.64185 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1861565.09258 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 12.72837 |
500 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 232695.63657 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 20908.76 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 468168.43 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 136978.11 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 18408.71 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12817.39 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 21374.26 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11139.00 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 319400.99 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 212168.25 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 314489.60 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 198592.85 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 42273.63 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 27872.27 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 41774.46 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 26785.40 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 37045.27 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 272206.31 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 23824.59 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94837.70 |
20 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | 94837.70 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 282945.12 | 203924.05 | 79021.07 | 0.72 | 34501.67 | 349.94 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2630603.78 | 1893092.94 | 737510.84 | 0.72 | 320561.99 | 3251.32 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 315361.62 | 227779.30 | 87582.31 | 0.72 | 38468.98 | 390.17 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 158289.07 | 115632.18 | 42656.89 | 0.73 | 20109.75 | 203.96 |
5 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | 563679.67 | 431898.55 | 131781.12 | 0.77 | 54781.20 | 555.62 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | 12392.1 | 9.16 | 9.16 | |||
2 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | 119323.0 | 10.40 | 10.40 | |||
3 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | 12244.3 | 9.16 | 9.16 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 6.37 | 21.74 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 6.37 | 21.74 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 8.0535112359E-004 | 1.3568316946E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.2363089314E-003 | 5.9379959727E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.7540601819E-002 | 4.0045490814E-002 | Pass | Pass | 0.4106424758 | 0.5050379640 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.5405732980E-002 | 1.5001811219E-002 | Pass | Pass | 19.6793222131 | 138.9229992618 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.8346131472E-002 | 1.7833863423E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.0689222875E-002 | 1.9426898356E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 1.9240967127E-002 | 2.0556697933E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.9147068071E-002 | 1.8551183878E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1924979337 | 0.2063558485 | Pass | Pass | 4.8826902967 | 29.2642484430 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2035246125 | 0.2178360401 | Pass | Pass | 2.6750744915 | 12.9350928571 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1862816838 | 0.2046819185 | Pass | Pass | 2.4370735415 | 10.9479708401 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.2813690675E-002 | 9.7006016682E-002 | Pass | Pass | 10.3752469496 | 81.5934619724 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3398103252 | 0.3420719024 | Pass | Pass | 8.4473211430 | 27.7793366850 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3472120309 | 0.3530363402 | Pass | Pass | 4.5611203664 | 12.5229124144 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3325824974 | 0.3425111789 | Pass | Pass | 4.8416975220 | 12.9273634381 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2054336898 | 0.2344184753 | Pass | Pass | 5.0128198141 | 19.0131918535 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.7620742401E-003 | 4.9483900383E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.1536514364E-002 | 1.5105747026E-002 | Pass | Pass | 0.5884600568 | 1.0436975770 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1457705745 | 9.8718543623E-002 | Pass | Pass | 0.5027238183 | 0.4669842495 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.4160503807E-006 | 2.0516740971E-006 | Pass | Pass | 3.0786411496E-003 | 2.4291701138E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.3728211871E-003 | 4.9976246239E-003 | Pass | Pass | 8.2238447216E-004 | 6.7686754263E-004 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.7076120712E-003 | 6.1353057686E-003 | Pass | Pass | 1.2763846559E-003 | 1.1111412555E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.1406535246E-002 | 8.5907520383E-003 | Pass | Pass | 7.5511755811E-004 | 6.1675281488E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5791.77 | 179.71 | 0.00 | 34583.68 | 10147.10 | 50702.27 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.57_SHGC_EAST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
North Total or Average | 1390.74 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 3.241 | 0.391 | 0.431 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 11.6510 | 2779.43 | 32383.10 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 333.79 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.6510 | 24961.20 | 290822.99 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 2997.66 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.6510 | 3134.13 | 36515.73 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.6510 | 3134.20 | 36516.53 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 11.6510 | 783.68 | 9130.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 94.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 22.3674 | 362.03 | 8097.60 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 83.47 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
Interior Lighting Total | 11.7515 | 46320.38 | 544334.28 | 1723.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 64082.80 | AstronomicalClock | - | 83.55 | 83.55 | 1005.00 | |
Exterior Lighting Total | 64082.80 | 1005.00 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3068076.62 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2564825.23 | 0.79 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1553079.00 | 6.11 | 1545500.81 | 6.08 | 6.37 | 21.74 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1553079.00 | 6.11 | 1545500.81 | 6.08 | 6.37 | 21.74 |
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1861565.09 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1861565.09 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 219294.26 | 282945.12 | 203924.05 | 79021.07 | 0.72 | - | 34501.67 | 349.94 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2047854.70 | 2630603.78 | 1893092.94 | 737510.84 | 0.72 | - | 320561.99 | 3251.32 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 242996.28 | 315361.62 | 227779.30 | 87582.31 | 0.72 | - | 38468.98 | 390.17 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 115532.61 | 158289.07 | 115632.18 | 42656.89 | 0.73 | - | 20109.75 | 203.96 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | 450413.74 | 563679.67 | 431898.55 | 131781.12 | 0.77 | - | 54781.20 | 555.62 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | 13007.99 | 10414.98 | 2593.01 | 0.80 | 3.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | 125252.98 | 100285.05 | 24967.93 | 0.80 | 3.50 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 12852.81 | 10290.73 | 2562.08 | 0.80 | 3.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
AIRLOOP DATACENTER BOT COOLING COIL | 12392.1 | 9.16 | 9.16 | ||||
AIRLOOP DATACENTER MID COOLING COIL | 119323.0 | 10.40 | 10.40 | ||||
AIRLOOP DATACENTER TOP COOLING COIL | 12244.3 | 9.16 | 9.16 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 22022.41 | 20908.76 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 493494.35 | 468168.43 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 144389.49 | 136978.11 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 19404.72 | 18408.71 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 13510.88 | 12817.39 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 22530.71 | 21374.26 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11738.35 | 11139.00 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 336681.49 | 319400.99 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 223647.13 | 212168.25 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 331504.41 | 314489.60 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 209337.31 | 198592.85 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 44560.72 | 42273.63 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 29380.21 | 27872.27 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 44034.54 | 41774.46 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 28234.54 | 26785.40 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 44661.47 | 37045.27 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 318641.32 | 272206.31 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 27051.18 | 23824.59 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94837.70 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | 100000.00 | 94837.70 | - |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | 27362.66 | 0.80 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | 263502.06 | 0.79 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | 27037.16 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 12.45 | 27219.23 | 2186.10 | 1.00 | 1.12 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 115.31 | 252079.86 | 2186.10 | 1.00 | 1.08 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 13.96 | 30382.64 | 2176.85 | 1.00 | 1.12 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
CAV_BAS SZVAV FAN | Fan:VariableVolume | 0.61 | 1337.13 | 7.16 | 15741.40 | 2197.78 | 1.00 | 1.13 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 0.61 | 637.69 | 31.86 | 33071.72 | 1038.16 | 1.00 | 1.19 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:20:00 |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.79 | 1351.31 | 1719.64 | 1.00 | 1.35 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 7.57 | 13011.70 | 1719.64 | 1.00 | 1.08 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.78 | 1335.19 | 1719.64 | 1.00 | 1.35 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.83 | 0.109871 | 22640.33 | 206063.11 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.022438 | 6757.40 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.054935 | 10449.55 | 190215.15 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.054935 | 10449.55 | 190215.15 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 209234.68 | 0.155670 | 54282.20 | 348701.22 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 84573.01 | 97258.97 | 34.99 | 6.228 | 7.162 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 21.70 | 0.00881 | 1.200 | 0.00 |
CORE_BOTTOM | 88297.53 | 101542.16 | 40.68 | 6.502 | 7.477 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00885 | 21.70 | 0.00881 | 1.078 | 0.00 |
CORE_MID | 835268.13 | 960558.35 | 384.82 | 61.493 | 70.717 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00887 | 21.70 | 0.00881 | 10.778 | 0.00 |
CORE_TOP | 88690.63 | 101994.23 | 40.86 | 6.589 | 7.578 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00884 | 29.40 | 0.00882 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13583.59 | 15621.12 | 49.84 | 1.009 | 1.161 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00878 | 29.40 | 0.00882 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 19891.08 | 22874.75 | 113.26 | 1.478 | 1.699 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00862 | 23.35 | 0.00881 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 28499.02 | 32773.87 | 104.57 | 2.117 | 2.435 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00863 | 29.05 | 0.00882 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 24021.30 | 27624.50 | 136.77 | 1.785 | 2.052 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00860 | 27.94 | 0.00882 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 126527.09 | 145506.15 | 464.26 | 9.400 | 10.811 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00880 | 29.40 | 0.00882 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 206340.23 | 237291.27 | 1174.85 | 15.330 | 17.630 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00862 | 23.97 | 0.00881 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 292676.56 | 336578.04 | 1073.89 | 21.745 | 25.006 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00863 | 29.14 | 0.00882 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 222483.58 | 255856.11 | 1266.77 | 16.530 | 19.009 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00861 | 27.77 | 0.00882 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 15238.76 | 17524.58 | 55.92 | 1.132 | 1.302 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00875 | 29.40 | 0.00882 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 20449.91 | 23517.40 | 116.44 | 1.519 | 1.747 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 24.00 | 24.00 | 0.00863 | 24.27 | 0.00881 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 31760.73 | 36524.84 | 116.54 | 2.360 | 2.714 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00863 | 29.23 | 0.00882 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 23844.23 | 27420.86 | 135.76 | 1.772 | 2.037 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00861 | 27.94 | 0.00882 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 9197.17 | 10576.74 | 292.15 | 0.683 | 0.786 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00856 | 25.60 | 0.00882 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 88558.52 | 101842.30 | 2813.11 | 6.580 | 7.567 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00856 | 25.60 | 0.00882 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 9087.43 | 10450.55 | 288.67 | 0.675 | 0.776 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00856 | 25.86 | 0.00882 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372823.77 | 428747.33 | 547.10 | 27.699 | 31.854 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00853 | 19.94 | 0.00881 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | 21.00 | 23.70 | 0.00269 | -4.20 | 0.00269 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 17.60 | 21.56 | 0.00269 | -4.20 | 0.00269 | 1.078 | 0.00 |
CORE_MID | 228171.50 | 285214.37 | 114.26 | 16.470 | 20.588 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 10.778 | 0.00 |
CORE_TOP | 67150.69 | 83938.37 | 33.63 | 4.926 | 6.157 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 9023.84 | 11279.79 | 35.99 | 0.662 | 0.828 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 6281.34 | 7851.68 | 38.87 | 0.461 | 0.577 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 10472.60 | 13090.75 | 41.77 | 0.770 | 0.962 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 4559.22 | 5699.02 | 28.22 | 0.334 | 0.417 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00758 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 156358.96 | 195448.70 | 623.61 | 11.516 | 14.395 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -4.20 | 0.00269 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 103858.72 | 129823.41 | 642.77 | 7.651 | 9.563 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -4.20 | 0.00269 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 153960.06 | 192450.08 | 614.03 | 11.339 | 14.173 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -4.20 | 0.00269 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 97227.12 | 121533.90 | 601.73 | 7.160 | 8.950 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -4.20 | 0.00269 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 20685.29 | 25856.61 | 82.50 | 1.525 | 1.906 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 13638.06 | 17047.57 | 84.40 | 1.006 | 1.257 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 20441.46 | 25551.83 | 81.53 | 1.507 | 1.884 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 13107.03 | 16383.79 | 81.12 | 0.966 | 1.208 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -4.20 | 0.00269 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | 18.00 | 25.86 | 0.00849 | -4.20 | 0.00269 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 23.16 | 0.00366 | -4.20 | 0.00269 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 20.74 | 0.00321 | -4.20 | 0.00269 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 18.00 | 27.00 | 0.00850 | -4.20 | 0.00269 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 12.45 | 12.45 | 3.86 | 3.86 | 12.4510 | 4.4474 | 12.4510 | 0.3572 | 0.3000 |
VAV_MID WITH REHEAT | 115.31 | 115.31 | 67.67 | 67.67 | 115.3101 | 67.6696 | 115.3101 | 0.5868 | 0.3000 |
VAV_TOP WITH REHEAT | 13.96 | 13.96 | 12.41 | 12.41 | 13.9572 | 12.4128 | 13.9572 | 0.8893 | 0.3000 |
CAV_BAS | 7.16 | 7.16 | 1.20 | 1.20 | 7.1624 | 2.1487 | 7.1624 | 0.3000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 31.86 | 31.86 | 0.34 | 0.34 | 31.8561 | 15.9269 | 31.8561 | 0.5000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.79 | 0.79 | 0.02 | 0.02 | 0.7858 | 0.7858 | 0.7858 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 7.57 | 7.57 | 0.16 | 0.16 | 7.5665 | 7.5665 | 7.5665 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.78 | 0.78 | 0.02 | 0.02 | 0.7764 | 0.7764 | 0.7764 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 22022.409 | 22022.409 | 2.243161 | 0.00019266 | 444.281 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 22022.41 | 22022.41 | 2.243161 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 22132.14 | 22132.14 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 493494.346 | 493494.346 | 21.214964 | 0.00431730 | 11510.205 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 493494.35 | 493494.35 | 21.214964 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9796 | 285214.37 | 0.00 | 495758.24 | 495758.24 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 144389.495 | 144389.495 | 6.157437 | 0.00126318 | 3375.242 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 144389.49 | 144389.49 | 6.157437 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 83938.37 | 0.00 | 145051.28 | 145051.28 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 19404.718 | 19404.718 | 0.828049 | 0.00016976 | 453.521 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19404.72 | 19404.72 | 0.828049 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00774679 | 49.3883 | 11279.79 | 0.00 | 19493.66 | 19493.66 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 13510.876 | 13510.876 | 0.576728 | 0.00011820 | 315.744 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13510.88 | 13510.88 | 0.576728 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00777019 | 49.5355 | 7851.68 | 0.00 | 13572.81 | 13572.81 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 22530.708 | 22530.708 | 0.961963 | 0.00019711 | 526.502 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22530.71 | 22530.71 | 0.961963 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00780009 | 49.7235 | 13090.75 | 0.00 | 22633.99 | 22633.99 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 11738.346 | 11738.346 | 0.615711 | 0.00010269 | 260.915 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11738.35 | 11738.35 | 0.615711 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00757687 | 48.3189 | 5699.02 | 0.00 | 11793.91 | 11793.91 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 336681.495 | 336681.495 | 14.395411 | 0.00294544 | 7864.506 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 336681.49 | 334928.32 | 14.395411 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00771166 | 49.1684 | 195448.70 | 0.00 | 338225.07 | 338225.07 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 223647.134 | 223647.134 | 9.563205 | 0.00195656 | 5224.031 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 223647.13 | 223647.13 | 9.563205 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00771068 | 49.1623 | 129823.41 | 0.00 | 224672.50 | 224672.50 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 331504.405 | 331504.405 | 14.173480 | 0.00290015 | 7743.662 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 331504.41 | 331504.41 | 14.173480 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00770735 | 49.1413 | 192450.08 | 0.00 | 333024.24 | 333024.24 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 209337.309 | 209337.309 | 8.949892 | 0.00183137 | 4889.992 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 209337.31 | 209337.31 | 8.949892 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00769209 | 49.0453 | 121533.90 | 0.00 | 210297.05 | 210297.05 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 44560.719 | 44560.719 | 1.906447 | 0.00038984 | 1040.711 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 44560.72 | 44356.01 | 1.906447 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00772731 | 49.2676 | 25856.61 | 0.00 | 44765.03 | 44765.03 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 29380.213 | 29380.213 | 1.257037 | 0.00025703 | 686.163 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 29380.21 | 29380.21 | 1.257037 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00772431 | 49.2488 | 17047.57 | 0.00 | 29514.92 | 29514.92 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 44034.545 | 44034.545 | 1.883892 | 0.00038523 | 1028.429 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 44034.54 | 44034.54 | 1.883892 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00772422 | 49.2482 | 25551.83 | 0.00 | 44236.44 | 44236.44 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 28234.543 | 28234.543 | 1.207943 | 0.00024701 | 659.418 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 28234.54 | 28234.54 | 1.207943 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00771415 | 49.1849 | 16383.79 | 0.00 | 28364.00 | 28364.00 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 219294.258 | -999.000 | 12.451027 | 0.00783268 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 219294.26 | 207843.56 | 12.451027 | 24.88 | 16.80 | 0.00879798 | 11.09 | 11.09 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 16.3079 | 24.00 | 0.00879339 | 46.6419 | 145726.78 | 0.00 | 221829.73 | 198962.22 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 44661.465 | 44661.465 | 3.735308 | 0.00039072 | 763.886 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 44661.47 | 44661.47 | 3.735308 | 2.86 | 1.77 | 0.00391335 | 12.89 | 11.51 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 54.3596 | 20.42 | 0.00533565 | 35.3771 | 19345.39 | 0.00 | 44836.63 | 44836.63 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2047854.701 | -999.000 | 115.310141 | 0.07314462 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 2047854.70 | 1934543.53 | 115.310141 | 24.95 | 16.84 | 0.00881843 | 11.09 | 11.09 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 17.6099 | 24.00 | 0.00881777 | 46.7695 | 1349587.77 | 0.00 | 2071403.15 | 1852892.20 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 318641.320 | 318641.320 | 34.593042 | 0.00278761 | 5534.345 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 318641.32 | 318641.32 | 34.593042 | 5.17 | 3.99 | 0.00462803 | 12.89 | 11.51 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 58.6997 | 18.44 | 0.00752277 | 56.2263 | 157911.43 | 0.00 | 329504.24 | 329504.24 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 242996.281 | -999.000 | 13.957160 | 0.00867926 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 242996.28 | 231279.50 | 13.957160 | 24.78 | 16.75 | 0.00877210 | 11.09 | 11.09 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 14.5481 | 24.00 | 0.00876368 | 46.4865 | 163319.08 | 0.00 | 245825.79 | 221278.36 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 27051.180 | 27051.180 | 4.187148 | 0.00023666 | 477.549 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 27051.18 | 27051.18 | 4.187148 | 7.47 | 5.75 | 0.00507873 | 12.89 | 11.51 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 48.4936 | 17.02 | 0.00766310 | 62.6348 | 15269.69 | 0.00 | 28841.78 | 28841.78 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 115532.610 | -999.000 | 7.162405 | 0.00412656 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 115532.61 | 107045.00 | 7.162405 | 23.72 | 16.48 | 0.00889244 | 11.08 | 11.08 | 0.00850000 | 22.36 | 0.00881033 | 15.93 | 16.7563 | 24.00 | 0.00890907 | 47.2472 | 84573.01 | 0.00 | 119658.64 | 104898.49 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.082328 | 0.00087484 | 2622.588 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 100000.00 | 100000.00 | 3.082328 | -0.70 | -2.14 | 0.00269032 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 38.9367 | 23.78 | 0.00269032 | 14.5985 | 0.00 | 0.00 | 100078.78 | 100078.78 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 450413.744 | -999.000 | 31.856135 | 0.01608774 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:20:00 | 450413.74 | 447834.83 | 31.856135 | 27.02 | 17.32 | 0.00853604 | 15.03 | 12.87 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 1.0623 | 27.00 | 0.00853297 | 37.8916 | 372494.53 | 0.00 | 471610.51 | 471610.51 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 100000.000 | 100000.000 | 3.082328 | 0.00087484 | 2622.588 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 100000.00 | 100000.00 | 3.082328 | -0.04 | -0.04 | 0.00843829 | 29.11 | 17.59 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 10.9785 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | 100078.78 | 100078.78 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER BOT | 13007.990 | 10414.977 | 0.785810 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 6503.99 | 6435.45 | 0.523873 | 26.98 | 17.33 | 0.00856645 | 14.47 | 12.65 | 0.00850000 | 25.86 | 0.00881585 | 17.16 | 2.9840 | 27.00 | 0.00856139 | 38.0141 | 9197.17 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER BOT | 27362.662 | 27362.662 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 27362.66 | 27362.66 | 0.785813 | -0.08 | -0.08 | 0.00837203 | 29.11 | 17.59 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.9893 | 26.37 | 0.00848735 | 39.1200 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER MID | 125252.980 | 100285.051 | 7.566530 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 62626.49 | 61939.26 | 5.044353 | 26.97 | 17.33 | 0.00856920 | 14.47 | 12.65 | 0.00850000 | 25.60 | 0.00881543 | 17.07 | 3.0990 | 27.00 | 0.00856400 | 38.0256 | 88558.52 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER MID | 263502.058 | 263502.058 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 263502.06 | 263502.06 | 7.566532 | -0.09 | -0.33 | 0.00364245 | 29.11 | 17.59 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 2.0660 | 24.26 | 0.00366254 | 19.2783 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER TOP | 12852.810 | 10290.731 | 0.776440 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 6426.40 | 6357.81 | 0.517627 | 26.98 | 17.33 | 0.00856731 | 14.47 | 12.65 | 0.00850000 | 25.86 | 0.00881585 | 17.16 | 3.0200 | 27.00 | 0.00856220 | 38.0177 | 9087.43 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER TOP | 27037.161 | 27037.161 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 27037.16 | 27037.16 | 0.776438 | -0.08 | -1.00 | 0.00319526 | 29.11 | 17.59 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 2.0133 | 22.72 | 0.00320564 | 18.5294 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 22022.409 | 22022.409 | 2.243161 | 0.00019266 | 444.281 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.43592102 | 54.44 | 82.22 | 27.78 | 2616443.35 | 0.8417 | 0.858632 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 22022.41 | 22022.41 | 1.0000 | 2.66261090 | 2.243161 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.19264199 | 60.00 | 32.22 | 27.78 | 0.000 | 22022.41 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 22132.14 | 22132.14 | 2.66261090 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 20.95 | 14.83 | 0.00800000 | 41372.0 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 493494.346 | 493494.346 | 21.214964 | 0.00431730 | 11510.205 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.43592102 | 54.44 | 82.22 | 27.78 | 2616443.35 | 18.8613 | 19.240857 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 493494.35 | 493494.35 | 1.0000 | 25.18196710 | 21.214964 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 4.31686341 | 60.00 | 32.22 | 27.78 | 0.000 | 493494.35 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 50.9796 | 285214.37 | 0.00 | 495758.24 | 495758.24 | 25.18196710 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52746.9 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 144389.495 | 144389.495 | 6.157437 | 0.00126318 | 3375.242 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.43592102 | 54.44 | 82.22 | 27.78 | 2616443.35 | 5.5185 | 5.629604 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 144389.49 | 144389.49 | 1.0000 | 7.30882051 | 6.157437 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 1.26305343 | 60.00 | 32.22 | 27.78 | 0.000 | 144389.49 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 83938.37 | 0.00 | 145051.28 | 145051.28 | 7.30882051 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.26 | 18.78 | 0.00800000 | 52905.9 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19404.718 | 19404.718 | 0.828049 | 0.00016976 | 453.521 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.43592102 | 54.44 | 82.22 | 27.78 | 2616443.35 | 0.7416 | 0.756571 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19404.72 | 19404.72 | 1.0000 | 0.98288682 | 0.828049 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.16974362 | 60.00 | 32.22 | 27.78 | 0.000 | 19404.72 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00774679 | 21.00 | 0.00774679 | 49.3883 | 11279.79 | 0.00 | 19493.66 | 19493.66 | 0.98288682 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.25 | 18.78 | 0.00800000 | 52892.9 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13510.876 | 13510.876 | 0.576728 | 0.00011820 | 315.744 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.43592102 | 54.44 | 82.22 | 27.78 | 2616443.35 | 0.5164 | 0.526776 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13510.88 | 13510.88 | 1.0000 | 0.68457037 | 0.576728 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.11818698 | 60.00 | 32.22 | 27.78 | 0.000 | 13510.88 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00777019 | 21.00 | 0.00777019 | 49.5355 | 7851.68 | 0.00 | 13572.81 | 13572.81 | 0.68457037 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.24 | 18.78 | 0.00800000 | 52886.6 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22530.708 | 22530.708 | 0.961963 | 0.00019711 | 526.502 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.43592102 | 54.44 | 82.22 | 27.78 | 2616443.35 | 0.8611 | 0.878450 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 22530.71 | 22530.71 | 1.0000 | 1.14184081 | 0.961963 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.19708836 | 60.00 | 32.22 | 27.78 | 0.000 | 22530.71 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00780009 | 21.00 | 0.00780009 | 49.7235 | 13090.75 | 0.00 | 22633.99 | 22633.99 | 1.14184081 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.24 | 18.78 | 0.00800000 | 52882.2 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11738.346 | 11738.346 | 0.615711 | 0.00010269 | 260.915 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.43592102 | 54.44 | 82.22 | 27.78 | 2616443.35 | 0.4486 | 0.457667 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11738.35 | 11738.35 | 1.0000 | 0.73084272 | 0.615711 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.10268170 | 60.00 | 32.22 | 27.78 | 0.000 | 11738.35 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00757687 | 21.00 | 0.00757687 | 48.3189 | 5699.02 | 0.00 | 11793.91 | 11793.91 | 0.73084272 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.63 | 17.57 | 0.00800000 | 49197.2 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 336681.495 | 336681.495 | 14.395411 | 0.00294544 | 7864.506 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.43592102 | 54.44 | 82.22 | 27.78 | 2616443.35 | 12.8679 | 13.126879 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 336681.49 | 334928.32 | 1.0000 | 17.08722015 | 14.395411 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 2.94513613 | 60.00 | 32.22 | 27.78 | 0.000 | 336681.49 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00771166 | 21.00 | 0.00771166 | 49.1684 | 195448.70 | 0.00 | 338225.07 | 338225.07 | 17.08722015 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52853.9 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 223647.134 | 223647.134 | 9.563205 | 0.00195656 | 5224.031 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.43592102 | 54.44 | 82.22 | 27.78 | 2616443.35 | 8.5478 | 8.719781 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 223647.13 | 223647.13 | 1.0000 | 11.35143678 | 9.563205 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 1.95636310 | 60.00 | 32.22 | 27.78 | 0.000 | 223647.13 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00771068 | 21.00 | 0.00771068 | 49.1623 | 129823.41 | 0.00 | 224672.50 | 224672.50 | 11.35143678 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52852.3 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 331504.405 | 331504.405 | 14.173480 | 0.00290015 | 7743.662 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.43592102 | 54.44 | 82.22 | 27.78 | 2616443.35 | 12.6700 | 12.925029 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 331504.41 | 331504.41 | 1.0000 | 16.82379059 | 14.173480 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 2.89984931 | 60.00 | 32.22 | 27.78 | 0.000 | 331504.41 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00770735 | 21.00 | 0.00770735 | 49.1413 | 192450.08 | 0.00 | 333024.24 | 333024.24 | 16.82379059 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52854.7 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 209337.309 | 209337.309 | 8.949892 | 0.00183137 | 4889.992 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.43592102 | 54.44 | 82.22 | 27.78 | 2616443.35 | 8.0008 | 8.161855 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 209337.31 | 209337.31 | 1.0000 | 10.62343954 | 8.949892 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 1.83118728 | 60.00 | 32.22 | 27.78 | 0.000 | 209337.31 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00769209 | 21.00 | 0.00769209 | 49.0453 | 121533.90 | 0.00 | 210297.05 | 210297.05 | 10.62343954 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52855.4 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 44560.719 | 44560.719 | 1.906447 | 0.00038984 | 1040.711 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.43592102 | 54.44 | 82.22 | 27.78 | 2616443.35 | 1.7031 | 1.737378 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 44560.72 | 44356.01 | 1.0000 | 2.26293474 | 1.906447 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.38979685 | 60.00 | 32.22 | 27.78 | 0.000 | 44560.72 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.94 | 0.00772731 | 21.00 | 0.00772731 | 49.2676 | 25856.61 | 0.00 | 44765.03 | 44765.03 | 2.26293474 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52841.7 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29380.213 | 29380.213 | 1.257037 | 0.00025703 | 686.163 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.43592102 | 54.44 | 82.22 | 27.78 | 2616443.35 | 1.1229 | 1.145505 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 29380.21 | 29380.21 | 1.0000 | 1.49209148 | 1.257037 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.25700470 | 60.00 | 32.22 | 27.78 | 0.000 | 29380.21 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.94 | 0.00772431 | 21.00 | 0.00772431 | 49.2488 | 17047.57 | 0.00 | 29514.92 | 29514.92 | 1.49209148 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52840.7 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 44034.545 | 44034.545 | 1.883892 | 0.00038523 | 1028.429 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.43592102 | 54.44 | 82.22 | 27.78 | 2616443.35 | 1.6830 | 1.716863 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 44034.54 | 44034.54 | 1.0000 | 2.23616257 | 1.883892 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.38519411 | 60.00 | 32.22 | 27.78 | 0.000 | 44034.54 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.94 | 0.00772422 | 21.00 | 0.00772422 | 49.2482 | 25551.83 | 0.00 | 44236.44 | 44236.44 | 2.23616257 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52842.1 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 28234.543 | 28234.543 | 1.207943 | 0.00024701 | 659.418 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 22.43592102 | 54.44 | 82.22 | 27.78 | 2616443.35 | 1.0791 | 1.100837 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 28234.54 | 28234.54 | 1.0000 | 1.43381774 | 1.207943 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.24698290 | 60.00 | 32.22 | 27.78 | 0.000 | 28234.54 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.94 | 0.00771415 | 21.00 | 0.00771415 | 49.1849 | 16383.79 | 0.00 | 28364.00 | 28364.00 | 1.43381774 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52842.0 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 219294.258 | -999.000 | 12.451027 | 0.00783268 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1950 | 1004.8586 | 1.1870 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 12.451027 | 14.77925465 | 4197.9300 | 999.8980 | 109.85965639 | 13.34 | 6.67 | 6.67 | 3076091.59 | 7.1290 | 7.128990 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 219294.26 | 207843.56 | 1.0000 | 14.77925465 | 12.451027 | 24.88 | 16.80 | 0.00879798 | 47410.2 | 11.09 | 11.09 | 0.00850000 | 32572.2 | 7.83188377 | 6.67 | 13.34 | 6.67 | 27219.230 | 192075.03 | 29.40 | 0.00882150 | 18.34 | 2.03050000 | 16.3079 | 24.00 | 0.00879339 | 24.00 | 0.00879339 | 46.6419 | 145726.78 | 0.00 | 221829.73 | 198962.22 | 14.77925465 | 24.88 | 16.95 | 0.00879798 | 47410.2 | 11.70 | 11.32 | 0.00818463 | 32400.7 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 44661.465 | 44661.465 | 3.735308 | 0.00039072 | 763.886 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 12.451027 | 14.77925465 | 4197.9300 | 999.8980 | 22.43592102 | 54.44 | 82.22 | 27.78 | 2616443.35 | 1.7070 | 1.741306 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 44661.47 | 44661.47 | 1.0000 | 4.43377640 | 3.735308 | 2.86 | 1.77 | 0.00391335 | 12686.4 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 0.39067812 | 60.00 | 32.22 | 27.78 | 0.000 | 44661.47 | -4.20 | 0.00269032 | -4.20 | 2.03050000 | 54.3596 | 11.28 | 0.00537004 | 20.42 | 0.00533565 | 35.3771 | 19345.39 | 0.00 | 44836.63 | 44836.63 | 4.43377640 | 2.80 | 1.82 | 0.00391335 | 12621.0 | 12.79 | 7.08 | 0.00391335 | 22733.5 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2047854.701 | -999.000 | 115.310141 | 0.07314462 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2330 | 1004.8586 | 1.1870 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 115.310141 | 136.87207444 | 4197.9300 | 999.8980 | 109.85965639 | 13.34 | 6.67 | 6.67 | 3076091.59 | 66.5733 | 66.573268 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 2047854.70 | 1934543.53 | 1.0000 | 136.87207444 | 115.310141 | 24.95 | 16.84 | 0.00881843 | 47534.1 | 11.09 | 11.09 | 0.00850000 | 32572.3 | 73.13716349 | 6.67 | 13.34 | 6.67 | 252079.864 | 1795774.84 | 29.40 | 0.00882150 | 18.34 | 20.30600000 | 17.6099 | 24.00 | 0.00881777 | 24.00 | 0.00881777 | 46.7695 | 1349587.77 | 0.00 | 2071403.15 | 1852892.20 | 136.87207444 | 24.95 | 16.99 | 0.00881843 | 47534.1 | 11.69 | 11.32 | 0.00818559 | 32400.2 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 318641.320 | 318641.320 | 34.593042 | 0.00278761 | 5534.345 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 115.310141 | 136.87207444 | 4197.9300 | 999.8980 | 22.43592102 | 54.44 | 82.22 | 27.78 | 2616443.35 | 12.1784 | 12.423510 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 318641.32 | 318641.32 | 1.0000 | 41.06162233 | 34.593042 | 5.17 | 3.99 | 0.00462803 | 16810.2 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 2.78732891 | 60.00 | 32.22 | 27.78 | 0.000 | 318641.32 | -4.20 | 0.00269032 | -4.20 | 20.30600000 | 58.6997 | 18.48 | 0.00738207 | 18.44 | 0.00752277 | 56.2263 | 157911.43 | 0.00 | 329504.24 | 329504.24 | 41.06162233 | 2.80 | 2.80 | 0.00462803 | 14412.1 | 10.72 | 6.92 | 0.00462803 | 22436.7 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 242996.281 | -999.000 | 13.957160 | 0.00867926 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1469 | 1004.8586 | 1.1870 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 13.957160 | 16.56702036 | 4197.9300 | 999.8980 | 109.85965639 | 13.34 | 6.67 | 6.67 | 3076091.59 | 7.8995 | 7.899514 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 242996.28 | 231279.50 | 1.0000 | 16.56702036 | 13.957160 | 24.78 | 16.75 | 0.00877210 | 47247.4 | 11.09 | 11.09 | 0.00850000 | 32579.9 | 8.67837875 | 6.67 | 13.34 | 6.67 | 30382.641 | 212613.64 | 29.40 | 0.00882150 | 18.34 | 2.03050000 | 14.5481 | 24.00 | 0.00876368 | 24.00 | 0.00876368 | 46.4865 | 163319.08 | 0.00 | 245825.79 | 221278.36 | 16.56702036 | 24.78 | 16.90 | 0.00877210 | 47247.4 | 11.70 | 11.32 | 0.00818475 | 32409.1 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 27051.180 | 27051.180 | 4.187148 | 0.00023666 | 477.549 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 13.957160 | 16.56702036 | 4197.9300 | 999.8980 | 22.43592102 | 54.44 | 82.22 | 27.78 | 2616443.35 | 1.0339 | 1.054699 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 27051.18 | 27051.18 | 1.0000 | 4.97010611 | 4.187148 | 7.47 | 5.75 | 0.00507873 | 20280.7 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 0.23663138 | 60.00 | 32.22 | 27.78 | 0.000 | 27051.18 | -4.20 | 0.00269032 | -4.20 | 2.03050000 | 48.4936 | 18.46 | 0.00732743 | 17.02 | 0.00766310 | 62.6348 | 15269.69 | 0.00 | 28841.78 | 28841.78 | 4.97010611 | 2.80 | 2.80 | 0.00507873 | 15541.6 | 8.52 | 6.38 | 0.00507873 | 21344.6 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 115532.610 | -999.000 | 7.162405 | 0.00412656 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3706 | 1004.8586 | 1.1870 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 7.162405 | 8.50170814 | 4197.9300 | 999.8980 | 109.85965639 | 13.34 | 6.67 | 6.67 | 3076091.59 | 3.7558 | 3.755825 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 115532.61 | 107045.00 | 1.0000 | 8.50170814 | 7.162405 | 23.72 | 16.48 | 0.00889244 | 46469.5 | 11.08 | 11.08 | 0.00850000 | 32562.7 | 4.12613618 | 6.67 | 13.34 | 6.67 | 15741.397 | 99791.21 | 22.36 | 0.00881033 | 15.93 | 1.20015641 | 16.7563 | 24.00 | 0.00890907 | 24.00 | 0.00890907 | 47.2472 | 84573.01 | 0.00 | 119658.64 | 104898.49 | 8.50170814 | 23.72 | 16.63 | 0.00889244 | 46469.5 | 11.64 | 11.32 | 0.00820420 | 32394.9 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.082328 | 0.00087484 | 2622.588 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 7.162405 | 8.50170814 | 4197.9300 | 999.8980 | 22.43592102 | 54.44 | 82.22 | 27.78 | 2616443.35 | 3.8220 | 3.898901 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.082328 | -0.70 | -2.14 | 0.00269032 | 6017.6 | 32.11 | 18.58 | 0.00800000 | 52750.5 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -4.20 | 0.00269032 | -4.20 | 1.20015641 | 38.9367 | 0.00 | 0.00269032 | 23.78 | 0.00269032 | 14.5985 | 0.00 | 0.00 | 100078.78 | 100078.78 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40240.9 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 450413.744 | -999.000 | 31.856135 | 0.01608774 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7081 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 31.856135 | 37.81293863 | 4197.9300 | 999.8980 | 109.85965639 | 13.34 | 6.67 | 6.67 | 3076091.59 | 14.6424 | 14.642404 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:20:00 | Sensible | 450413.74 | 447834.83 | 1.0000 | 37.81293863 | 31.856135 | 27.02 | 17.32 | 0.00853604 | 48931.2 | 15.03 | 12.87 | 0.00850000 | 36600.3 | 16.08609420 | 6.67 | 13.34 | 6.67 | 33071.725 | 417342.02 | 29.40 | 0.00882150 | 18.34 | 0.33839277 | 1.0623 | 27.00 | 0.00853297 | 27.00 | 0.00853297 | 37.8916 | 372494.53 | 0.00 | 471610.51 | 471610.51 | 37.81293863 | 27.02 | 17.47 | 0.00853604 | 48931.2 | 14.80 | 12.95 | 0.00853604 | 36459.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.082328 | 0.00087484 | 2622.588 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 31.856135 | 37.81293863 | 4197.9300 | 999.8980 | 22.43592102 | 54.44 | 82.22 | 27.78 | 2616443.35 | 3.8220 | 3.898901 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.082328 | -0.04 | -0.04 | 0.00843829 | 21058.1 | 29.11 | 17.59 | 0.00800000 | 49691.3 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -4.20 | 0.00269032 | -4.20 | 0.33839277 | 10.9785 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | 100078.78 | 100078.78 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40240.9 | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13007.990 | 10414.977 | 0.785810 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7646 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.785813 | 0.93275260 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 6503.99 | 6435.45 | 1.0000 | 0.62183282 | 0.523873 | 26.98 | 17.33 | 0.00856645 | 48960.6 | 14.47 | 12.65 | 0.00850000 | 36026.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6503.99 | 25.86 | 0.00881585 | 17.16 | 0.01563234 | 2.9840 | 27.00 | 0.00856139 | 27.00 | 0.00856139 | 38.0141 | 9197.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27362.662 | 27362.662 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.785813 | 0.93275260 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 27362.66 | 27362.66 | 1.0000 | 0.93275260 | 0.785813 | -0.08 | -0.08 | 0.00837203 | 20852.7 | 29.11 | 17.59 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27362.66 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 1.9893 | 0.00 | 0.00848735 | 26.37 | 0.00848735 | 39.1200 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 125252.980 | 100285.051 | 7.566530 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7697 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.566532 | 8.98140401 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 62626.49 | 61939.26 | 1.0000 | 5.98760091 | 5.044353 | 26.97 | 17.33 | 0.00856920 | 48961.2 | 14.47 | 12.65 | 0.00850000 | 36026.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 62626.49 | 25.60 | 0.00881543 | 17.07 | 0.15632344 | 3.0990 | 27.00 | 0.00856400 | 27.00 | 0.00856400 | 38.0256 | 88558.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 263502.058 | 263502.058 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.566532 | 8.98140401 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 263502.06 | 263502.06 | 1.0000 | 8.98140401 | 7.566532 | -0.09 | -0.33 | 0.00364245 | 9021.8 | 29.11 | 17.59 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 263502.06 | -4.20 | 0.00269032 | -4.20 | 0.15632344 | 2.0660 | 0.00 | 0.00366254 | 24.26 | 0.00366254 | 19.2783 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12852.810 | 10290.731 | 0.776440 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7662 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.776438 | 0.92162489 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 6426.40 | 6357.81 | 1.0000 | 0.61441808 | 0.517627 | 26.98 | 17.33 | 0.00856731 | 48962.5 | 14.47 | 12.65 | 0.00850000 | 36026.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6426.40 | 25.86 | 0.00881585 | 17.16 | 0.01563234 | 3.0200 | 27.00 | 0.00856220 | 27.00 | 0.00856220 | 38.0177 | 9087.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27037.161 | 27037.161 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.776438 | 0.92162489 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 27037.16 | 27037.16 | 1.0000 | 0.92162489 | 0.776438 | -0.08 | -1.00 | 0.00319526 | 7905.7 | 29.11 | 17.59 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27037.16 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 2.0133 | 0.00 | 0.00320564 | 22.72 | 0.00320564 | 18.5294 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 12.45 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 115.31 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 13.96 | - | |||
CAV_BAS_OA_CONTROLLER | FixedDryBulb | 1.20 | 7.16 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 31.86 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2082.00 | 1061.67 | 12.67 |
CORE_BOTTOM | 2393.67 | 932.50 | 12.50 |
CORE_MID | 1368.67 | 2614.83 | 37.00 |
CORE_TOP | 1499.83 | 4126.83 | 568.67 |
PERIMETER_BOT_ZN_3 | 1416.33 | 3674.83 | 150.50 |
PERIMETER_BOT_ZN_2 | 1363.33 | 4268.33 | 225.17 |
PERIMETER_BOT_ZN_1 | 1856.00 | 3884.33 | 332.83 |
PERIMETER_BOT_ZN_4 | 1828.83 | 3694.00 | 182.67 |
PERIMETER_MID_ZN_3 | 1737.33 | 4750.67 | 1068.67 |
PERIMETER_MID_ZN_2 | 1686.67 | 3987.67 | 962.83 |
PERIMETER_MID_ZN_1 | 2107.50 | 4214.33 | 791.00 |
PERIMETER_MID_ZN_4 | 1756.33 | 4772.50 | 899.33 |
PERIMETER_TOP_ZN_3 | 2393.50 | 5100.33 | 1863.17 |
PERIMETER_TOP_ZN_2 | 2628.67 | 4711.50 | 1696.17 |
PERIMETER_TOP_ZN_1 | 2590.00 | 4471.67 | 1438.67 |
PERIMETER_TOP_ZN_4 | 2316.83 | 4903.33 | 1544.00 |
DATACENTER_BOT_ZN_6 | 5943.00 | 905.33 | 905.33 |
DATACENTER_MID_ZN_6 | 5829.17 | 317.17 | 304.17 |
DATACENTER_TOP_ZN_6 | 5406.33 | 549.50 | 429.17 |
DATACENTER_BASEMENT_ZN_6 | 5877.83 | 3421.50 | 3415.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5929.67 | 4854.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 6.50 | 0.00 | 0.17 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 1.83 | 0.00 | 1.17 | 0.00 |
CORE_TOP | 7.67 | 0.00 | 0.67 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 7.50 | 0.00 | 7.50 |
PERIMETER_BOT_ZN_1 | 0.33 | 9.67 | 0.00 | 9.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 23.67 | 0.00 | 14.50 |
PERIMETER_MID_ZN_3 | 10.67 | 0.00 | 0.17 | 0.00 |
PERIMETER_MID_ZN_2 | 19.00 | 7.33 | 0.00 | 7.33 |
PERIMETER_MID_ZN_1 | 7.83 | 9.50 | 0.00 | 9.50 |
PERIMETER_MID_ZN_4 | 7.50 | 14.67 | 0.00 | 7.33 |
PERIMETER_TOP_ZN_3 | 91.33 | 0.00 | 14.83 | 0.00 |
PERIMETER_TOP_ZN_2 | 87.17 | 6.33 | 11.83 | 6.33 |
PERIMETER_TOP_ZN_1 | 65.50 | 7.83 | 7.17 | 7.83 |
PERIMETER_TOP_ZN_4 | 49.67 | 14.17 | 5.67 | 7.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 8.00 | 0.00 | 7.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 108.33 | 90.33 | 17.33 | 65.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.09 | 149.60 | 6779.02 | 1.097 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.86 | 134.35 | 6849.35 | 1.088 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.86 | 134.35 | 6849.35 | 0.855 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.86 | 134.35 | 6849.35 | 0.787 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.89 | 16.87 | 860.00 | 1.111 | 0.041 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.44 | 10.87 | 554.22 | 2.220 | 0.042 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.89 | 16.87 | 860.02 | 2.222 | 0.041 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.44 | 10.87 | 554.22 | 2.718 | 0.042 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.89 | 16.87 | 860.00 | 1.115 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.87 | 10.87 | 554.22 | 2.053 | 0.104 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.89 | 16.87 | 860.02 | 2.160 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.44 | 10.87 | 554.22 | 2.336 | 0.098 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.89 | 16.87 | 860.00 | 1.352 | 0.117 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.44 | 10.87 | 554.22 | 2.064 | 0.121 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.89 | 16.87 | 860.02 | 2.180 | 0.118 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.44 | 10.87 | 554.22 | 2.377 | 0.122 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.22 | 42.18 | 1911.37 | 24.320 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.09 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.86 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.86 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.86 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.89 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.44 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.89 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.44 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.89 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.87 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.89 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.44 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.89 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.44 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.89 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.44 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.22 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.09 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.86 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.86 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.86 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.89 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.44 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.89 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.44 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.89 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.87 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.89 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.44 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.89 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.44 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.89 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.44 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.80 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.22 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1012.40 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 44032134.23 | 0.00 | 44032134.23 | 0.00 | 44032134.23 | 37848132.68 | 4265.80 | 2110.13 | 2384.07 | 138.44 |
CORE_BOTTOM | 44792212.42 | 0.00 | 44792212.42 | 0.00 | 44792212.42 | 33990283.35 | 4370.41 | 49.92 | 4339.67 | 191.50 |
CORE_MID | 0.35E+09 | 0.00 | 0.35E+09 | 0.00 | 0.35E+09 | 0.34E+09 | 5035.77 | 60.55 | 3663.68 | 165.87 |
CORE_TOP | 32083695.65 | 0.00 | 32083695.65 | 0.00 | 32083695.65 | 33990283.35 | 5419.14 | 51.49 | 3289.37 | 263.93 |
PERIMETER_BOT_ZN_3 | 5773871.66 | 0.00 | 5773871.66 | 420131.66 | 6194003.32 | 4267819.30 | 3814.37 | 16.30 | 4929.34 | 191.50 |
PERIMETER_BOT_ZN_2 | 7488190.85 | 0.00 | 7488190.85 | 280087.58 | 7768278.43 | 2750345.05 | 3748.83 | 0.50 | 5010.67 | 191.50 |
PERIMETER_BOT_ZN_1 | 11588418.68 | 0.00 | 11588418.68 | 420131.66 | 12008550.34 | 4267912.63 | 3748.83 | 0.00 | 5011.17 | 191.50 |
PERIMETER_BOT_ZN_4 | 9162365.36 | 0.00 | 9162365.36 | 280087.58 | 9442452.94 | 2750345.05 | 3748.83 | 0.00 | 5011.17 | 191.50 |
PERIMETER_MID_ZN_3 | 57736182.70 | 0.00 | 57736182.70 | 985321.86 | 58721504.55 | 42678193.03 | 3890.91 | 7.70 | 4861.38 | 165.87 |
PERIMETER_MID_ZN_2 | 64689177.98 | 0.00 | 64689177.98 | 656880.79 | 65346058.77 | 27503450.52 | 4356.77 | 1.35 | 4401.88 | 620.31 |
PERIMETER_MID_ZN_1 | 0.11E+09 | 0.00 | 0.11E+09 | 985321.86 | 0.11E+09 | 42679126.28 | 3837.15 | 0.17 | 4922.68 | 165.87 |
PERIMETER_MID_ZN_4 | 78035292.82 | 0.00 | 78035292.82 | 656880.79 | 78692173.61 | 27503450.52 | 3831.71 | 1.78 | 4926.52 | 165.87 |
PERIMETER_TOP_ZN_3 | 6977556.93 | 0.00 | 6977556.93 | 1223376.39 | 8200933.32 | 4267819.30 | 3984.52 | 12.11 | 4763.37 | 263.93 |
PERIMETER_TOP_ZN_2 | 6847929.33 | 0.00 | 6847929.33 | 815583.70 | 7663513.03 | 2750345.05 | 3890.85 | 2.74 | 4866.41 | 263.93 |
PERIMETER_TOP_ZN_1 | 11204850.71 | 0.00 | 11204850.71 | 1223376.39 | 12428227.10 | 4267912.63 | 3890.97 | 2.88 | 4866.14 | 263.93 |
PERIMETER_TOP_ZN_4 | 7901277.35 | 0.00 | 7901277.35 | 815583.70 | 8716861.05 | 2750345.05 | 3872.13 | 2.07 | 4885.80 | 263.93 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.39E+09 | 0.00 | 0.39E+09 | 0.00 | 0.39E+09 | 10671554.30 | 328.32 | 423.21 | 8008.46 | 2622.30 |
Total Facility | 0.72E+10 | 0.00 | 0.72E+10 | 38322411.53 | 0.72E+10 | 0.50E+10 | 6073.67 | 4383.93 | 8484.85 | 3103.02 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.0277 | 0.0000 | 2.0277 | 0.0000 | 2.0277 | 1.2002 | 1490.68 | 2108.10 | 2344.23 |
CORE_BOTTOM | 2.0301 | 0.0000 | 2.0301 | 0.0000 | 2.0301 | 1.0778 | 1721.89 | 48.19 | 4172.92 |
CORE_MID | 15.9627 | 0.0000 | 15.9627 | 0.0000 | 15.9627 | 10.7782 | 2293.04 | 60.01 | 3589.95 |
CORE_TOP | 1.4716 | 0.0000 | 1.4716 | 0.0000 | 1.4716 | 1.0778 | 2647.36 | 50.13 | 3245.51 |
PERIMETER_BOT_ZN_3 | 0.2610 | 0.0000 | 0.2610 | 0.0095 | 0.2705 | 0.1353 | 1178.76 | 15.42 | 4748.82 |
PERIMETER_BOT_ZN_2 | 0.3369 | 0.0000 | 0.3369 | 0.0064 | 0.3433 | 0.0872 | 1123.33 | 0.50 | 4819.17 |
PERIMETER_BOT_ZN_1 | 0.5229 | 0.0000 | 0.5229 | 0.0095 | 0.5325 | 0.1353 | 1123.33 | 0.00 | 4819.67 |
PERIMETER_BOT_ZN_4 | 0.4120 | 0.0000 | 0.4120 | 0.0064 | 0.4184 | 0.0872 | 1123.33 | 0.00 | 4819.67 |
PERIMETER_MID_ZN_3 | 2.6268 | 0.0000 | 2.6268 | 0.0224 | 2.6492 | 1.3533 | 1210.20 | 6.83 | 4725.97 |
PERIMETER_MID_ZN_2 | 3.1196 | 0.0000 | 3.1196 | 0.0159 | 3.1355 | 0.8721 | 1171.88 | 0.42 | 3861.70 |
PERIMETER_MID_ZN_1 | 5.0867 | 0.0000 | 5.0867 | 0.0224 | 5.1091 | 1.3533 | 1173.38 | 0.17 | 4769.45 |
PERIMETER_MID_ZN_4 | 3.5502 | 0.0000 | 3.5502 | 0.0149 | 3.5651 | 0.8721 | 1168.63 | 1.50 | 4772.87 |
PERIMETER_TOP_ZN_3 | 0.3189 | 0.0000 | 0.3189 | 0.0278 | 0.3467 | 0.1353 | 1273.68 | 10.24 | 4659.08 |
PERIMETER_TOP_ZN_2 | 0.3135 | 0.0000 | 0.3135 | 0.0185 | 0.3320 | 0.0872 | 1203.62 | 1.56 | 4737.82 |
PERIMETER_TOP_ZN_1 | 0.5135 | 0.0000 | 0.5135 | 0.0278 | 0.5413 | 0.1353 | 1203.57 | 1.67 | 4737.76 |
PERIMETER_TOP_ZN_4 | 0.3614 | 0.0000 | 0.3614 | 0.0185 | 0.3799 | 0.0872 | 1192.95 | 0.76 | 4749.29 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 12.6122 | 0.0000 | 12.6122 | 0.0000 | 12.6122 | 0.3384 | 126.01 | 423.08 | 5393.91 |
Total Facility | 325.8067 | 0.0000 | 325.8067 | 0.8803 | 326.6870 | 158.4706 | 3256.67 | 4371.77 | 5852.67 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 0.11E+09 | 0.00 | 0.11E+09 | 48026705.38 | 3748.83 | 0.00 | 5011.17 | 191.50 |
VAV_MID WITH REHEAT | 0.93E+09 | 0.00 | 0.93E+09 | 0.48E+09 | 3849.38 | 0.65 | 4909.96 | 165.87 |
VAV_TOP WITH REHEAT | 91603130.82 | 0.00 | 91603130.82 | 48026705.38 | 3945.62 | 4.33 | 4810.05 | 263.90 |
CAV_BAS | 61944668.49 | 0.00 | 61944668.49 | 37848132.68 | 4214.65 | 2.44 | 4542.91 | 138.44 |
AIRLOOP DATACENTER BASEMENT | 0.54E+09 | 0.00 | 0.54E+09 | 10671554.30 | 325.14 | 0.07 | 8434.80 | 2622.30 |
AIRLOOP DATACENTER BOT | 344200.17 | 0.00 | 344200.17 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3442001.72 | 0.00 | 3442001.72 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 344200.17 | 0.00 | 344200.17 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 5.0199 | 0.0000 | 5.0199 | 1.5229 | 1123.33 | 0.00 | 4819.67 |
VAV_MID WITH REHEAT | 42.4976 | 0.0000 | 42.4976 | 15.2292 | 1178.83 | 0.05 | 4764.12 |
VAV_TOP WITH REHEAT | 4.1971 | 0.0000 | 4.1971 | 1.5229 | 1236.53 | 2.26 | 4704.21 |
CAV_BAS | 2.8525 | 0.0000 | 2.8525 | 1.2002 | 1459.15 | 0.85 | 4483.00 |
AIRLOOP DATACENTER BASEMENT | 17.7709 | 0.0000 | 17.7709 | 0.3384 | 125.42 | 0.00 | 5817.58 |
AIRLOOP DATACENTER BOT | 0.0161 | 0.0000 | 0.0161 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1609 | 0.0000 | 0.1609 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0161 | 0.0000 | 0.0161 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 18.76 | 4705.13 | 0.00 | 0.00 | 0.00 | 287.27 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 99.66 | 4399.75 | 0.00 | 0.00 | 0.00 | 441.58 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 17.49 | 4242.95 | 0.00 | 0.00 | 0.00 | 808.65 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 2121.54 | 2545.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 422.96 | 8018.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.6588 | 6.4467 | 0.0000 | 0.0000 | 0.0000 | 2.3877 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 28.7793 | 56.3381 | 0.0000 | 0.0000 | 0.0000 | 25.3481 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.6795 | 5.7495 | 0.0000 | 0.0000 | 0.0000 | 2.5005 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6914 | 5.5524 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4779 | 19.5387 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2203 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1343 |
Defaulted Fields | 1287 |
Fields with Defaults | 3878 |
Autosized Fields | 320 |
Autosizable Fields | 465 |
Autocalculated Fields | 223 |
Autocalculatable Fields | 468 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 29911.75 | 288163.70 | 29-MAY-05:00 | 2346135.99 | 29-AUG-15:10 |
Electricity:Building | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 758.19 | 15076.70 | 01-JAN-00:10 | 42602.33 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 589.38 | 5907.35 | 01-JAN-00:10 | 43380.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5893.79 | 59073.32 | 01-JAN-00:10 | 433806.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 589.38 | 5907.33 | 01-JAN-00:10 | 43380.63 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 740.04 | 7417.49 | 01-JAN-00:10 | 54469.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 476.91 | 4780.12 | 01-JAN-00:10 | 35102.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 740.05 | 7417.62 | 01-JAN-00:10 | 54470.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 476.91 | 4780.09 | 01-JAN-00:10 | 35102.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7588.97 | 95364.66 | 01-JAN-00:10 | 387850.11 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1622.27 | 19890.94 | 01-JAN-00:10 | 85232.07 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:HVAC | 3760.73 | 32449.11 | 12-JAN-02:20 | 363858.38 | 18-JUL-15:00 |
ExteriorEquipment:Electricity | 2623.11 | 22123.82 | 01-JAN-00:10 | 235096.12 | 03-APR-07:20 |
Transformer:ExteriorEquipment:Electricity | 56.04 | 979.82 | 01-JAN-00:10 | 3543.78 | 03-APR-07:20 |
ElectricityPurchased:Facility | 29911.75 | 288163.70 | 29-MAY-05:00 | 2346135.99 | 29-AUG-15:10 |
ElectricityPurchased:Plant | 29911.75 | 288163.70 | 29-MAY-05:00 | 2346135.99 | 29-AUG-15:10 |
Cogeneration:ElectricityPurchased | 29911.75 | 288163.70 | 29-MAY-05:00 | 2346135.99 | 29-AUG-15:10 |
General:Cogeneration:ElectricityPurchased | 29911.75 | 288163.70 | 29-MAY-05:00 | 2346135.99 | 29-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 29911.75 | 288163.70 | 29-MAY-05:00 | 2346135.99 | 29-AUG-15:10 |
ElectricityNet:Plant | 29911.75 | 288163.70 | 29-MAY-05:00 | 2346135.99 | 29-AUG-15:10 |
Cogeneration:ElectricityNet | 29911.75 | 288163.70 | 29-MAY-05:00 | 2346135.99 | 29-AUG-15:10 |
General:Cogeneration:ElectricityNet | 29911.75 | 288163.70 | 29-MAY-05:00 | 2346135.99 | 29-AUG-15:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1452.23 | 534.52 | 02-JAN-07:10 | 387764.96 | 29-AUG-14:30 |
General:Cooling:Electricity | 1452.23 | 534.52 | 02-JAN-07:10 | 387764.96 | 29-AUG-14:30 |
Fans:Electricity | 2648.06 | 25618.90 | 14-JAN-05:50 | 294234.68 | 10-AUG-15:30 |
General:Fans:Electricity | 2648.06 | 25618.90 | 14-JAN-05:50 | 294234.68 | 10-AUG-15:30 |
ExteriorLights:Electricity | 1005.00 | 0.00 | 01-JAN-08:10 | 64082.80 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 1005.00 | 0.00 | 01-JAN-08:10 | 64082.80 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.31 | 1944.00 | 01-JAN-00:10 | 1944.00 | 01-JAN-00:10 |
Humidifier:Electricity | 613.17 | 0.00 | 11-JAN-20:10 | 100000.00 | 18-MAR-14:10 |
General:Humidifier:Electricity | 613.17 | 0.00 | 11-JAN-20:10 | 100000.00 | 18-MAR-14:10 |
Electricity:Plant | 2291.82 | 0.00 | 03-JAN-00:10 | 520719.48 | 29-AUG-15:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 438.50 | 0.00 | 01-JAN-00:10 | 52007.19 | 10-FEB-12:20 |
Water Heater:WaterSystems:Electricity | 438.50 | 0.00 | 01-JAN-00:10 | 52007.19 | 10-FEB-12:20 |
HeatRejection:Electricity | 55.59 | 0.00 | 01-JAN-00:10 | 47672.27 | 27-APR-12:30 |
General:HeatRejection:Electricity | 55.59 | 0.00 | 01-JAN-00:10 | 47672.27 | 27-APR-12:30 |
Pumps:Electricity | 788.95 | 0.00 | 03-JAN-00:10 | 91145.00 | 20-JUN-15:00 |
General:Pumps:Electricity | 788.95 | 0.00 | 03-JAN-00:10 | 91145.00 | 20-JUN-15:00 |
WIRED_LTG_ELECTRICITY | 157.66 | 0.00 | 01-JAN-00:10 | 13766.21 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1791.02 | 0.00 | 01-JAN-00:40 | 1676942.45 | 02-JAN-06:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 1791.02 | 0.00 | 01-JAN-00:40 | 1676942.45 | 02-JAN-06:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 1791.02 | 0.00 | 01-JAN-00:40 | 1676942.45 | 02-JAN-06:10 |
Boiler:Heating:NaturalGas | 1791.02 | 0.00 | 01-JAN-00:40 | 1676942.45 | 02-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 5339.16 | 0.00 | 01-JAN-06:10 | 2391825.20 | 29-AUG-14:30 |
PlantLoopCoolingDemand:HVAC | 5339.16 | 0.00 | 01-JAN-06:10 | 2391825.20 | 29-AUG-14:30 |
CoolingCoils:PlantLoopCoolingDemand | 5339.16 | 0.00 | 01-JAN-06:10 | 2391825.20 | 29-AUG-14:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 6319.57 | 0.00 | 12-JAN-01:20 | 0.00 | 10-AUG-16:00 |
Water:HVAC | 228.10 | 0.00 | 11-JAN-20:10 | 0.00 | 18-MAR-17:00 |
Humidifier:Water | 228.10 | 0.00 | 11-JAN-20:10 | 0.00 | 18-MAR-17:00 |
General:Humidifier:Water | 228.10 | 0.00 | 11-JAN-20:10 | 0.00 | 18-MAR-17:00 |
MainsWater:Facility | 6319.57 | 0.00 | 12-JAN-01:20 | 0.00 | 10-AUG-16:00 |
MainsWater:HVAC | 228.10 | 0.00 | 11-JAN-20:10 | 0.00 | 18-MAR-17:00 |
Humidifier:MainsWater | 228.10 | 0.00 | 11-JAN-20:10 | 0.00 | 18-MAR-17:00 |
General:Humidifier:MainsWater | 228.10 | 0.00 | 11-JAN-20:10 | 0.00 | 18-MAR-17:00 |
Water:Plant | 6091.47 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 28-FEB-12:30 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 28-FEB-12:30 |
MainsWater:Plant | 6091.47 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 28-FEB-12:30 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 28-FEB-12:30 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 3811.30 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
General:HeatRejection:Water | 3811.30 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
HeatRejection:MainsWater | 3811.30 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
General:HeatRejection:MainsWater | 3811.30 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 47141.24 | 101326.36 | 17-JAN-03:50 | 11971695.69 | 29-AUG-14:30 |
EnergyTransfer:Building | 19525.67 | 87227.72 | 14-JAN-19:00 | 1915503.39 | 10-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 683.54 | 0.00 | 01-JAN-00:10 | 86868.84 | 10-OCT-07:40 |
Heating:EnergyTransfer | 368.54 | 0.00 | 11-JAN-15:50 | 1114254.67 | 02-JAN-05:50 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.77 | 0.00 | 01-JAN-00:10 | 5342.90 | 01-APR-16:10 |
General:Heating:EnergyTransfer | 368.54 | 0.00 | 11-JAN-15:50 | 1114254.67 | 02-JAN-05:50 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.77 | 0.00 | 01-JAN-00:10 | 5342.90 | 01-APR-16:10 |
Cooling:EnergyTransfer | 19157.13 | 84719.09 | 17-JAN-04:10 | 1915503.39 | 10-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 682.77 | 0.00 | 01-JAN-00:10 | 86868.84 | 10-OCT-07:40 |
General:Cooling:EnergyTransfer | 19157.13 | 84719.09 | 17-JAN-04:10 | 1915503.39 | 10-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 682.77 | 0.00 | 01-JAN-00:10 | 86868.84 | 10-OCT-07:40 |
EnergyTransfer:Zone:CORE_BOTTOM | 607.41 | 0.00 | 01-JAN-00:10 | 57555.67 | 28-AUG-13:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 607.41 | 0.00 | 01-JAN-00:10 | 57555.67 | 28-AUG-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 607.41 | 0.00 | 01-JAN-00:10 | 57555.67 | 28-AUG-13:10 |
EnergyTransfer:Zone:CORE_MID | 4688.22 | 0.00 | 01-JAN-00:40 | 491252.63 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 3.37 | 0.00 | 01-JAN-00:10 | 361856.32 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 3.37 | 0.00 | 01-JAN-00:10 | 361856.32 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4684.85 | 0.00 | 01-JAN-00:40 | 491252.63 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4684.85 | 0.00 | 01-JAN-00:40 | 491252.63 | 10-AUG-16:00 |
EnergyTransfer:Zone:CORE_TOP | 407.49 | 0.00 | 01-JAN-00:40 | 80958.80 | 26-DEC-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 10.86 | 0.00 | 01-JAN-00:40 | 80958.80 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 10.86 | 0.00 | 01-JAN-00:40 | 80958.80 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 396.63 | 0.00 | 01-JAN-00:10 | 60556.45 | 10-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 396.63 | 0.00 | 01-JAN-00:10 | 60556.45 | 10-AUG-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 69.67 | 0.00 | 01-JAN-00:10 | 11905.15 | 24-JUL-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.18 | 0.00 | 01-JAN-00:10 | 4283.71 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.18 | 0.00 | 01-JAN-00:10 | 4283.71 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 69.49 | 0.00 | 01-JAN-00:10 | 11905.15 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 69.49 | 0.00 | 01-JAN-00:10 | 11905.15 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 75.21 | 0.00 | 01-JAN-00:10 | 16801.17 | 10-AUG-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.26 | 0.00 | 01-JAN-00:10 | 3059.88 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.26 | 0.00 | 01-JAN-00:10 | 3059.88 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 74.95 | 0.00 | 01-JAN-00:10 | 16801.17 | 10-AUG-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 74.95 | 0.00 | 01-JAN-00:10 | 16801.17 | 10-AUG-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 124.92 | 0.00 | 01-JAN-00:10 | 27163.94 | 04-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.85 | 0.00 | 01-JAN-00:10 | 7158.19 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.85 | 0.00 | 01-JAN-00:10 | 7158.19 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 124.07 | 0.00 | 01-JAN-00:10 | 27163.94 | 04-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 124.07 | 0.00 | 01-JAN-00:10 | 27163.94 | 04-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 105.87 | 0.00 | 01-JAN-00:10 | 22336.19 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 2008.41 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 2008.41 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 105.85 | 0.00 | 01-JAN-00:10 | 22336.19 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 105.85 | 0.00 | 01-JAN-00:10 | 22336.19 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 595.90 | 0.00 | 01-JAN-00:40 | 145319.24 | 02-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 63.54 | 0.00 | 01-JAN-00:40 | 145319.24 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 63.54 | 0.00 | 01-JAN-00:40 | 145319.24 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 532.36 | 0.00 | 01-JAN-00:10 | 106653.62 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 532.36 | 0.00 | 01-JAN-00:10 | 106653.62 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 600.27 | 0.00 | 01-JAN-00:40 | 177056.38 | 10-AUG-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 40.97 | 0.00 | 01-JAN-00:40 | 103089.46 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 40.97 | 0.00 | 01-JAN-00:40 | 103089.46 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 559.30 | 0.00 | 01-JAN-00:10 | 177056.38 | 10-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 559.30 | 0.00 | 01-JAN-00:10 | 177056.38 | 10-AUG-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1138.90 | 0.00 | 01-JAN-00:40 | 297095.46 | 04-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 48.38 | 0.00 | 01-JAN-00:40 | 155717.91 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 48.38 | 0.00 | 01-JAN-00:40 | 155717.91 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1090.51 | 0.00 | 01-JAN-00:10 | 297095.46 | 04-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1090.51 | 0.00 | 01-JAN-00:10 | 297095.46 | 04-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 701.13 | 0.00 | 01-JAN-00:40 | 199504.26 | 10-AUG-16:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 28.53 | 0.00 | 01-JAN-00:40 | 86172.90 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 28.53 | 0.00 | 01-JAN-00:40 | 86172.90 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 672.61 | 0.00 | 01-JAN-00:10 | 199504.26 | 10-AUG-16:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 672.61 | 0.00 | 01-JAN-00:10 | 199504.26 | 10-AUG-16:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 73.33 | 0.00 | 01-JAN-00:40 | 21117.00 | 21-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.23 | 0.00 | 01-JAN-00:40 | 21117.00 | 21-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.23 | 0.00 | 01-JAN-00:40 | 21117.00 | 21-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 50.10 | 0.00 | 01-JAN-00:10 | 12268.85 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 50.10 | 0.00 | 01-JAN-00:10 | 12268.85 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 67.32 | 0.00 | 01-JAN-00:40 | 17600.08 | 10-AUG-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 14.15 | 0.00 | 01-JAN-00:40 | 14416.55 | 21-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 14.15 | 0.00 | 01-JAN-00:40 | 14416.55 | 21-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 53.17 | 0.00 | 01-JAN-00:10 | 17600.08 | 10-AUG-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 53.17 | 0.00 | 01-JAN-00:10 | 17600.08 | 10-AUG-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 116.06 | 0.00 | 01-JAN-00:40 | 29690.31 | 04-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 18.22 | 0.00 | 01-JAN-00:40 | 21009.52 | 21-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 18.22 | 0.00 | 01-JAN-00:40 | 21009.52 | 21-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 97.84 | 0.00 | 01-JAN-00:10 | 29690.31 | 04-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 97.84 | 0.00 | 01-JAN-00:10 | 29690.31 | 04-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 71.45 | 0.00 | 01-JAN-00:40 | 20962.22 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 10.04 | 0.00 | 01-JAN-00:40 | 12381.76 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 10.04 | 0.00 | 01-JAN-00:40 | 12381.76 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 61.41 | 0.00 | 01-JAN-00:10 | 20962.22 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 61.41 | 0.00 | 01-JAN-00:10 | 20962.22 | 10-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 80.70 | 0.00 | 01-JAN-00:10 | 10355.57 | 29-AUG-15:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.59 | 0.00 | 01-JAN-00:10 | 3124.35 | 21-MAY-12:00 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.59 | 0.00 | 01-JAN-00:10 | 3124.35 | 21-MAY-12:00 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 80.11 | 0.00 | 01-JAN-00:10 | 10355.57 | 29-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 80.11 | 0.00 | 01-JAN-00:10 | 10355.57 | 29-AUG-15:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 571.10 | 0.00 | 01-JAN-00:40 | 175923.67 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 38.30 | 0.00 | 01-JAN-00:40 | 175923.67 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 38.30 | 0.00 | 01-JAN-00:40 | 175923.67 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 532.80 | 0.00 | 01-JAN-00:10 | 88255.78 | 19-FEB-05:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 532.80 | 0.00 | 01-JAN-00:10 | 88255.78 | 19-FEB-05:50 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 141.42 | 0.00 | 01-JAN-00:40 | 33746.29 | 10-AUG-14:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 58.65 | 0.00 | 01-JAN-00:40 | 33227.19 | 17-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 58.65 | 0.00 | 01-JAN-00:40 | 33227.19 | 17-JAN-05:30 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 82.77 | 0.00 | 01-JAN-00:10 | 33746.29 | 10-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 82.77 | 0.00 | 01-JAN-00:10 | 33746.29 | 10-AUG-14:30 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 133.66 | 367.60 | 16-JAN-06:00 | 8647.60 | 06-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 133.66 | 367.60 | 16-JAN-06:00 | 8647.60 | 06-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 133.66 | 367.60 | 16-JAN-06:00 | 8647.60 | 06-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1177.45 | 6.70 | 07-JAN-07:50 | 82609.02 | 10-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 4.78 | 0.00 | 02-JAN-12:00 | 13079.12 | 01-JAN-19:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 4.78 | 0.00 | 02-JAN-12:00 | 13079.12 | 01-JAN-19:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1172.67 | 0.00 | 01-JAN-00:10 | 82609.02 | 10-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1172.67 | 0.00 | 01-JAN-00:10 | 82609.02 | 10-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 105.28 | 5.29 | 29-MAY-11:00 | 8413.84 | 10-AUG-18:30 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.75 | 0.00 | 02-JAN-11:30 | 1404.22 | 08-JAN-18:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.75 | 0.00 | 02-JAN-11:30 | 1404.22 | 08-JAN-18:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 103.54 | 0.00 | 01-JAN-00:10 | 8413.84 | 10-AUG-18:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 103.54 | 0.00 | 01-JAN-00:10 | 8413.84 | 10-AUG-18:30 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7189.36 | 79108.79 | 30-APR-23:10 | 392033.62 | 21-APR-13:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 1.10 | 0.00 | 01-JAN-00:10 | 4059.78 | 23-OCT-00:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 1.10 | 0.00 | 01-JAN-00:10 | 4059.78 | 23-OCT-00:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7188.26 | 79108.79 | 30-APR-23:10 | 392033.62 | 21-APR-13:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7188.26 | 79108.79 | 30-APR-23:10 | 392033.62 | 21-APR-13:40 |
PlantLoopHeatingDemand:Facility | 1621.61 | 0.00 | 01-JAN-00:40 | 1316547.74 | 02-JAN-06:10 |
PlantLoopHeatingDemand:Plant | 433.10 | 0.00 | 01-JAN-00:10 | 51259.06 | 10-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 433.10 | 0.00 | 01-JAN-00:10 | 51259.06 | 10-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 433.10 | 0.00 | 01-JAN-00:10 | 51259.06 | 10-FEB-12:10 |
EnergyTransfer:HVAC | 8379.61 | 2107.11 | 01-JAN-04:00 | 2500427.25 | 29-AUG-14:30 |
HeatingCoils:EnergyTransfer | 1188.50 | 0.00 | 01-JAN-00:40 | 1310352.81 | 02-JAN-06:10 |
PlantLoopHeatingDemand:HVAC | 1188.50 | 0.00 | 01-JAN-00:40 | 1310352.81 | 02-JAN-06:10 |
HeatingCoils:PlantLoopHeatingDemand | 1188.50 | 0.00 | 01-JAN-00:40 | 1310352.81 | 02-JAN-06:10 |
CoolingCoils:EnergyTransfer | 7191.11 | 1714.31 | 02-JAN-07:30 | 2500427.25 | 29-AUG-14:30 |
EnergyTransfer:Plant | 19235.96 | 0.00 | 03-JAN-00:10 | 7589761.82 | 29-AUG-14:30 |
LoopToLoop:EnergyTransfer | 5426.38 | 0.00 | 01-JAN-06:10 | 2394681.17 | 29-AUG-14:30 |
WaterSystems:EnergyTransfer | 433.10 | 0.00 | 01-JAN-00:10 | 51259.06 | 10-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 433.10 | 0.00 | 01-JAN-00:10 | 51259.06 | 10-FEB-12:10 |
Boilers:EnergyTransfer | 1183.79 | 0.00 | 01-JAN-00:40 | 1310654.18 | 02-JAN-06:10 |
Chillers:EnergyTransfer | 5591.95 | 0.00 | 01-JAN-00:10 | 2405353.34 | 29-AUG-14:30 |
HeatRejection:EnergyTransfer | 6600.73 | 0.00 | 01-JAN-00:10 | 2764148.22 | 29-AUG-14:30 |
General:HeatRejection:EnergyTransfer | 6600.73 | 0.00 | 01-JAN-00:10 | 2764148.22 | 29-AUG-14:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.769 | -682.768 | 0.000 | 0.000 | 94.115 | 333.789 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -170.302 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -607.404 | 0.000 | 0.000 | 83.575 | 299.766 | 289.614 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -65.551 |
CORE_MID | 0.000 | 0.000 | 3.374 | -4684.826 | 0.000 | 0.000 | 846.423 | 2997.664 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -2058.762 |
CORE_TOP | 0.000 | 0.000 | 10.863 | -396.627 | 0.000 | 0.000 | 88.729 | 299.766 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -292.344 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.180 | -69.491 | 0.000 | 0.000 | 11.011 | 37.639 | 36.365 | 20.479 | 0.000 | 0.016 | 56.244 | 0.000 | -86.276 | 0.000 | -6.167 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.258 | -74.952 | 0.000 | 0.000 | 7.373 | 24.256 | 23.435 | 46.125 | 0.000 | 0.014 | 29.976 | 0.000 | -52.544 | 0.000 | -3.942 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.847 | -124.068 | 0.000 | 0.000 | 11.330 | 37.639 | 36.366 | 101.990 | 0.000 | 0.015 | 19.943 | 0.000 | -78.104 | 0.000 | -5.958 | 0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.017 | -105.850 | 0.000 | 0.000 | 7.306 | 24.256 | 23.435 | 49.322 | 0.000 | 0.009 | 65.768 | 0.000 | -59.890 | 0.000 | -4.373 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 63.541 | -532.353 | 0.000 | 0.000 | 116.026 | 376.387 | 363.654 | 219.578 | 0.000 | 0.482 | 289.658 | 0.000 | -770.543 | 0.000 | -126.428 | -0.005 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 40.974 | -559.295 | 0.000 | 0.000 | 55.042 | 242.558 | 234.352 | 459.088 | 0.000 | 0.312 | 102.052 | 0.000 | -490.378 | 0.000 | -84.706 | -0.003 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 48.381 | -1090.510 | 0.000 | 0.000 | 115.219 | 376.395 | 363.660 | 1014.039 | 0.000 | 0.345 | 57.406 | 0.000 | -753.400 | 0.000 | -131.535 | -0.013 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 28.527 | -672.601 | 0.000 | 0.000 | 76.529 | 242.558 | 234.351 | 507.070 | 0.000 | 0.251 | 193.705 | 0.000 | -522.646 | 0.000 | -87.743 | -0.004 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 23.229 | -50.100 | 0.000 | 0.000 | 11.913 | 37.639 | 36.365 | 23.124 | 0.000 | 0.060 | 1.828 | 0.000 | -69.786 | 0.000 | -14.272 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 14.148 | -53.174 | 0.000 | 0.000 | 7.587 | 24.256 | 23.435 | 46.886 | 0.000 | 0.033 | 0.000 | 0.000 | -44.754 | 0.000 | -9.627 | -8.789 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 18.221 | -97.835 | 0.000 | 0.000 | 11.698 | 37.639 | 36.366 | 102.455 | 0.000 | 0.040 | 0.000 | 0.000 | -68.925 | 0.000 | -14.971 | -24.688 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 10.039 | -61.413 | 0.000 | 0.000 | 7.724 | 24.256 | 23.435 | 50.849 | 0.000 | 0.030 | 3.720 | 0.000 | -48.486 | 0.000 | -10.154 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -133.664 | 0.000 | 0.000 | 0.950 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -29.514 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 4.783 | -1172.667 | 0.000 | 0.000 | 9.502 | 83.466 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -463.891 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 1.748 | -103.536 | 0.000 | 0.000 | 0.951 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -61.389 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 1.103 | -7188.179 | 0.000 | 0.000 | 23.047 | 94.114 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -424.942 |
GROUNDFLOOR_PLENUM | 0.586 | -80.110 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.024 | 93.072 | 0.000 | 0.000 | 0.000 | -13.572 | 0.000 |
MIDFLOOR_PLENUM | 38.303 | -532.798 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.513 | 723.353 | 0.000 | 0.000 | 0.000 | -229.371 | -0.013 |
TOPFLOOR_PLENUM | 58.649 | -82.773 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.019 | 46.229 | 0.000 | 0.000 | 0.000 | -22.123 | -0.001 |
Total Facility | 97.537 | -695.681 | 271.002 | -18461.312 | 0.000 | 0.000 | 1586.048 | 5610.736 | 14676.396 | 2641.004 | 0.000 | 2.164 | 1682.955 | 0.000 | -3045.732 | 0.000 | -764.943 | -3600.212 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 02-OCT-04:11 | 0.00 | 0.00 | 0.00 | -140074.04 | 0.00 | 0.00 | 0.00 | 3238.31 | 13457.54 | 0.00 | 0.00 | 0.00 | 123378.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 17-JUL-04:11 | 0.00 | 0.00 | 0.00 | -120513.03 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.65 | 0.00 | 0.00 | 0.00 | 111667.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 11-AUG-04:12 | 0.00 | 0.00 | 0.00 | -1045364.65 | 0.00 | 0.00 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 956906.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 11-AUG-05:01 | 0.00 | 0.00 | 0.00 | -102680.10 | 0.00 | 0.00 | 871.54 | 2908.23 | 7647.36 | 0.00 | 0.00 | 0.00 | 91252.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -11904.96 | 0.00 | 0.00 | 1114.38 | 3286.42 | 2160.55 | 7139.46 | 0.00 | 35.14 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1830.99 |
PERIMETER_BOT_ZN_2 | 30-JUL-07:51 | 0.00 | 0.00 | 0.00 | -32745.77 | 0.00 | 0.00 | 19.89 | 117.66 | 464.11 | 21484.07 | 0.00 | 0.00 | 10766.13 | 0.00 | -0.00 | 0.00 | -106.09 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-SEP-12:41 | 0.00 | 0.00 | 0.00 | -46690.90 | 0.00 | 0.00 | 30.09 | 182.58 | 720.19 | 29398.26 | 0.00 | 0.00 | 16534.90 | 0.00 | -0.00 | 0.00 | -175.12 | 0.00 |
PERIMETER_BOT_ZN_4 | 07-MAY-16:01 | 0.00 | 0.00 | 0.00 | -39899.33 | 0.00 | 0.00 | 17.80 | 117.66 | 464.11 | 21689.53 | 0.00 | 0.00 | 17742.96 | 0.00 | -0.00 | 0.00 | -132.74 | 0.00 |
PERIMETER_MID_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -106653.02 | 0.00 | 0.00 | 11143.77 | 32864.16 | 21605.52 | 71985.32 | 0.00 | 810.54 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -31756.28 |
PERIMETER_MID_ZN_2 | 23-JUL-08:61 | 0.00 | 0.00 | 0.00 | -337673.22 | 0.00 | 0.00 | 199.60 | 1176.61 | 4641.14 | 211863.55 | 0.00 | 0.00 | 124916.46 | 0.00 | -0.00 | 0.00 | -5124.13 | 0.00 |
PERIMETER_MID_ZN_1 | 08-OCT-13:31 | 0.00 | 0.00 | 0.00 | -479453.26 | 0.00 | 0.00 | 311.64 | 1825.83 | 7201.95 | 250669.47 | 0.00 | 0.00 | 224993.39 | 0.00 | -0.00 | 0.00 | -5549.02 | 0.00 |
PERIMETER_MID_ZN_4 | 06-AUG-16:41 | 0.00 | 0.00 | 0.00 | -377468.50 | 0.00 | 0.00 | 167.01 | 1176.61 | 4641.11 | 224772.24 | 0.00 | 0.00 | 149934.81 | 0.00 | -0.00 | 0.00 | -3223.28 | 0.00 |
PERIMETER_TOP_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -12268.84 | 0.00 | 0.00 | 1114.38 | 3286.42 | 2160.55 | 7079.22 | 0.00 | 98.94 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1470.67 |
PERIMETER_TOP_ZN_2 | 13-AUG-09:21 | 0.00 | 0.00 | 0.00 | -33344.05 | 0.00 | 0.00 | 19.35 | 117.66 | 464.11 | 17478.15 | 0.00 | 0.00 | 15691.66 | 0.00 | -0.00 | 0.00 | -426.89 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-14:11 | 0.00 | 0.00 | 0.00 | -53292.19 | 0.00 | 0.00 | 27.87 | 182.58 | 720.19 | 23296.20 | 0.00 | 0.00 | 29487.42 | 0.00 | -0.00 | 0.00 | -422.07 | 0.00 |
PERIMETER_TOP_ZN_4 | 06-AUG-17:11 | 0.00 | 0.00 | 0.00 | -41222.97 | 0.00 | 0.00 | 0.00 | 117.66 | 360.35 | 21333.65 | 0.00 | 0.00 | 19810.12 | 0.00 | -0.00 | 0.00 | -398.80 | 0.00 |
DATACENTER_BOT_ZN_6 | 06-AUG-18:40 | 0.00 | 0.00 | 0.00 | -8647.59 | 0.00 | 0.00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 812.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 10-AUG-18:40 | 0.00 | 0.00 | 0.00 | -82607.01 | 0.00 | 0.00 | 106.16 | 2429.28 | 77944.22 | 0.00 | 0.00 | 0.00 | 2127.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 10-AUG-18:30 | 0.00 | 0.00 | 0.00 | -8413.66 | 0.00 | 0.00 | 10.62 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 365.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 24-MAR-15:52 | 0.00 | 0.00 | 0.00 | -520676.87 | 0.00 | 0.00 | 2687.33 | 8217.58 | 284724.39 | 0.00 | 0.00 | 0.00 | 225047.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 12-AUG-05:12 | 0.00 | -10899.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11016.46 | 0.00 | -0.00 | 0.00 | -116.52 | 0.00 |
MIDFLOOR_PLENUM | 26-DEC-04:01 | 0.00 | -149091.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164322.88 | 0.00 | -0.00 | 0.00 | -15231.57 | 0.00 |
TOPFLOOR_PLENUM | 10-AUG-14:30 | 0.00 | -33745.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.21 | 33690.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-JUL-05:01 | 0.00 | 31410.40 | 0.00 | -2143463.82 | 0.00 | 0.00 | 16612.76 | 54433.43 | 497997.76 | 0.00 | 0.00 | 0.00 | 1664038.93 | 0.00 | -109343.17 | 0.00 | -11686.28 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 01-APR-16:02 | 0.00 | 0.00 | 6102.48 | 0.00 | 0.00 | 0.00 | 520.13 | 1619.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -21699.31 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-05:11 | 0.00 | 0.00 | 409474.34 | 0.00 | 0.00 | 0.00 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -497932.87 |
CORE_TOP | 26-DEC-04:11 | 0.00 | 0.00 | 96881.23 | 0.00 | 0.00 | 0.00 | 0.00 | 1454.11 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -104272.97 |
PERIMETER_BOT_ZN_3 | 06-JAN-06:01 | 0.00 | 0.00 | 11041.43 | 0.00 | 0.00 | 0.00 | 146.10 | 365.16 | 960.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6580.92 | 0.00 | -107.99 | -5824.01 |
PERIMETER_BOT_ZN_2 | 05-JAN-06:01 | 0.00 | 0.00 | 9828.88 | 0.00 | 0.00 | 0.00 | 94.73 | 235.32 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4311.74 | 0.00 | -70.51 | -6395.49 |
PERIMETER_BOT_ZN_1 | 26-DEC-05:01 | 0.00 | 0.00 | 16826.23 | 0.00 | 0.00 | 0.00 | 0.00 | 365.17 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5453.72 | 0.00 | 0.00 | -12483.25 |
PERIMETER_BOT_ZN_4 | 18-FEB-06:01 | 0.00 | 0.00 | 7274.03 | 0.00 | 0.00 | 0.00 | 94.15 | 235.32 | 618.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4537.53 | 0.00 | -44.86 | -3639.92 |
PERIMETER_MID_ZN_3 | 19-FEB-07:41 | 0.00 | 0.00 | 211897.27 | 0.00 | 0.00 | 0.00 | 872.84 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -58516.00 | 0.00 | -19403.86 | -143877.88 |
PERIMETER_MID_ZN_2 | 19-FEB-07:01 | 0.00 | 0.00 | 188208.56 | 0.00 | 0.00 | 0.00 | 564.07 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44184.61 | 0.00 | -13003.16 | -137402.61 |
PERIMETER_MID_ZN_1 | 26-DEC-04:01 | 0.00 | 0.00 | 255589.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1825.83 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -50706.53 | 0.00 | -8429.50 | -205734.78 |
PERIMETER_MID_ZN_4 | 26-DEC-04:01 | 0.00 | 0.00 | 171284.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.61 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -34664.82 | 0.00 | -5768.26 | -136832.64 |
PERIMETER_TOP_ZN_3 | 19-FEB-07:01 | 0.00 | 0.00 | 29670.67 | 0.00 | 0.00 | 0.00 | 90.71 | 182.58 | 720.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6092.06 | 0.00 | -2253.38 | -22318.71 |
PERIMETER_TOP_ZN_2 | 19-FEB-07:01 | 0.00 | 0.00 | 24310.81 | 0.00 | 0.00 | 0.00 | 58.55 | 117.66 | 464.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4053.79 | 0.00 | -1515.09 | -19382.25 |
PERIMETER_TOP_ZN_1 | 19-FEB-07:01 | 0.00 | 0.00 | 36893.42 | 0.00 | 0.00 | 0.00 | 90.49 | 182.58 | 720.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5887.20 | 0.00 | -2292.04 | -29707.44 |
PERIMETER_TOP_ZN_4 | 19-FEB-07:01 | 0.00 | 0.00 | 25436.38 | 0.00 | 0.00 | 0.00 | 57.83 | 117.66 | 464.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4017.55 | 0.00 | -1564.10 | -20494.33 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 01-JAN-17:05 | 0.00 | 0.00 | 13092.50 | 0.00 | 0.00 | 0.00 | 60.37 | 404.88 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -33043.81 |
DATACENTER_TOP_ZN_6 | 08-JAN-18:50 | 0.00 | 0.00 | 1404.22 | 0.00 | 0.00 | 0.00 | 0.00 | 40.49 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3393.31 |
DATACENTER_BASEMENT_ZN_6 | 23-OCT-00:41 | 0.00 | 0.00 | 39802.24 | 0.00 | 0.00 | 0.00 | 0.00 | 456.53 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -230075.03 |
GROUNDFLOOR_PLENUM | 10-SEP-15:21 | 13697.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -131.42 | -13566.05 |
MIDFLOOR_PLENUM | 02-JAN-06:12 | 193441.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5002.44 | -188438.75 |
TOPFLOOR_PLENUM | 09-JAN-05:13 | 39354.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1819.02 | -37535.04 |
Total Facility | 02-JAN-05:32 | 608.55 | 132870.64 | 1135654.96 | -132870.64 | 0.00 | 0.00 | 0.00 | 54433.43 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -130697.51 | 0.00 | -74514.45 | -1217910.22 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 14.8246 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 12.4510 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 146.7568 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 115.3101 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 15.9824 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 13.9572 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 7.1624 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 7.1624 | 0.1676 | 1.0000 | Not calculated | 1.2002 | 0.1676 | ||
AIRLOOP DATACENTER BASEMENT | 31.8538 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 31.8561 | 0.0106 | 1.0000 | Not calculated | 0.3384 | 0.0106 | ||
AIRLOOP DATACENTER BOT | 0.7858 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7858 | 0.0199 | 1.0000 | Not calculated | 0.0156 | 0.0199 | ||
AIRLOOP DATACENTER MID | 7.5665 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 7.5665 | 0.0207 | 1.0000 | Not calculated | 0.1563 | 0.0207 | ||
AIRLOOP DATACENTER TOP | 0.7764 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7764 | 0.0201 | 1.0000 | Not calculated | 0.0156 | 0.0201 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 7.4123 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.4474 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 73.3784 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 44.0270 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 7.9912 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7947 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 2.1487 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 2.1487 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.5585 | ||
AIRLOOP DATACENTER BASEMENT | 15.9269 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 15.9269 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0212 | ||
AIRLOOP DATACENTER BOT | 0.7858 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7858 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0199 | ||
AIRLOOP DATACENTER MID | 7.5665 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 7.5665 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0207 | ||
AIRLOOP DATACENTER TOP | 0.7764 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7764 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0201 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 7.1624 | 7.1624 | 2.1487 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.4772 | 7.4772 | 2.2432 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 70.7165 | 70.7165 | 21.2150 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.5779 | 7.5779 | 2.2734 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1606 | 1.1606 | 0.3482 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6995 | 1.6995 | 0.5098 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4350 | 2.4350 | 0.7305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0524 | 2.0524 | 0.6157 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.3954 | 14.3954 | 4.3186 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 17.6297 | 17.6297 | 5.2889 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 25.0063 | 25.0063 | 7.5019 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 19.0089 | 19.0089 | 5.7027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9064 | 1.9064 | 0.5719 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7472 | 1.7472 | 0.5242 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7136 | 2.7136 | 0.8141 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0372 | 2.0372 | 0.6112 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7858 | 0.7858 | 0.7858 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.5665 | 7.5665 | 7.5665 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7764 | 0.7764 | 0.7764 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 31.8538 | 31.8538 | 15.9269 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 14.8246 | 12.4510 | 14.8246 | 4.4474 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 146.7568 | 115.3101 | 146.7568 | 44.0270 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 15.9824 | 13.9572 | 15.9824 | 4.7947 | 0.0000 | 1.0000 |
CAV_BAS | 7.1624 | 7.1624 | 7.1624 | 2.1487 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 31.8538 | 31.8561 | 31.8538 | 15.9269 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.7858 | 0.7858 | 0.7858 | 0.7858 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 7.5665 | 7.5665 | 7.5665 | 7.5665 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.7764 | 0.7764 | 0.7764 | 0.7764 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 2.1487 | 2.1487 | 2.1487 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7386 | 3.7386 | 2.2432 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 35.3583 | 35.3583 | 21.2150 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7889 | 3.7889 | 2.2734 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5803 | 0.5803 | 0.3482 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8497 | 0.8497 | 0.5098 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2175 | 1.2175 | 0.7305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0262 | 1.0262 | 0.6157 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.1977 | 7.1977 | 4.3186 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.8148 | 8.8148 | 5.2889 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.5031 | 12.5031 | 7.5019 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.5045 | 9.5045 | 5.7027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9532 | 0.9532 | 0.5719 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8736 | 0.8736 | 0.5242 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3568 | 1.3568 | 0.8141 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0186 | 1.0186 | 0.6112 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7858 | 0.7858 | 0.7858 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.5665 | 7.5665 | 7.5665 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7764 | 0.7764 | 0.7764 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 15.9269 | 15.9269 | 15.9269 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 7.4123 | 4.4474 | 4.4474 | 4.4474 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 73.3784 | 44.0270 | 44.0270 | 44.0270 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 7.9912 | 4.7947 | 4.7947 | 4.7947 | 0.0000 | 1.0000 |
CAV_BAS | 2.1487 | 2.1487 | 2.1487 | 2.1487 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 15.9269 | 15.9269 | 15.9269 | 15.9269 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.7858 | 0.7858 | 0.7858 | 0.7858 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 7.5665 | 7.5665 | 7.5665 | 7.5665 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.7764 | 0.7764 | 0.7764 | 0.7764 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 17.33 |
Number of hours cooling loads not met | 65.83 |
Number of hours not met | 83.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1791.02 | 1676942.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1452.23 | 387764.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 5610.74 | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 1005.00 | 64082.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 56.04 | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.31 | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2648.06 | 294234.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 788.95 | 91145.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 55.59 | 47672.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 613.17 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 438.50 | 52007.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 29911.75 |
Natural Gas | 0.00 | 1791.02 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 31702.77 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 121.13 |
Space Heating | 0.00 |
Space Cooling | 31.35 |
Fans (All) | 57.17 |
Service Water Heating | 9.47 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 645.76 |
Subtotal | 645.76 |
Natural Gas [MJ/m2] | |
Space Heating | 38.67 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 38.67 |
Subtotal | 38.67 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 17.70 |
Space Heating | 5.65 |
Space Cooling | 4.58 |
Fans (All) | 8.35 |
Service Water Heating | 1.38 |
Receptacle Equipment | 46.29 |
Miscellaneous | 16.04 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
LTG_SCH_DATACENTER | 2939. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8569.00 | 191.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8739.17 | 20.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8747.50 | 12.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8745.50 | 14.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8622.17 | 137.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8747.17 | 12.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8732.67 | 27.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8749.83 | 10.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8746.83 | 13.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6036.50 | 2723.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6027.17 | 2732.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 5938.50 | 2821.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7811.33 | 948.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8727.50 | 32.50 | 0.00 | 0.00 | 0.00 |
Min | 5938.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2821.50 | 0.00 | 0.00 | 0.00 |
Average | 8336.48 | 423.52 | 0.00 | 0.00 | 0.00 |
Sum | 191739.00 | 9741.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368221.67 | 394.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1232.67 | 1035.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1223.83 | 1044.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1220.33 | 1047.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 89066.67 | 14328.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368221.67 | 14328.33 | 0.00 | 0.00 | 0.00 |
Average | 79558.83 | 776.08 | 0.00 | 0.00 | 0.00 |
Sum | 1829853.17 | 17849.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8460.67 | 277.67 | 21.67 | 0.00 | 0.00 |
CORE_BOTTOM | 8464.50 | 295.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8613.67 | 146.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8713.83 | 46.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8741.00 | 19.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8559.67 | 200.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8746.33 | 13.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8736.83 | 23.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8710.50 | 49.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8748.67 | 11.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8740.67 | 19.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8724.00 | 36.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7402.50 | 1357.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7357.33 | 1402.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7302.33 | 1457.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7973.33 | 786.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8753.67 | 6.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8561.00 | 199.00 | 0.00 | 0.00 | 0.00 |
Min | 7302.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1457.67 | 21.67 | 0.00 | 0.00 |
Average | 8482.26 | 276.80 | 0.94 | 0.00 | 0.00 |
Sum | 195092.00 | 6366.33 | 21.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 367710.50 | 835.50 | 70.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330369.67 | 443.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330544.00 | 269.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330722.00 | 91.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1553.83 | 714.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1525.17 | 742.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1503.83 | 764.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 91419.17 | 11975.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367710.50 | 11975.83 | 70.00 | 0.00 | 0.00 |
Average | 79643.36 | 688.51 | 3.04 | 0.00 | 0.00 |
Sum | 1831797.17 | 15835.83 | 70.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:51
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.486685E+11 | 132504.95 | 30-JAN-05:11 | 6.10 | 5.49 | 0.538199E+10 | 7495.04 | 02-JAN-10:09 | 6.10 | 5.49 |
February | 0.447477E+11 | 134631.62 | 27-FEB-05:11 | 6.50 | 5.53 | 0.501099E+10 | 7499.25 | 27-FEB-14:39 | 19.43 | 11.93 |
March | 0.553291E+11 | 133280.16 | 01-MAR-05:01 | 0.00 | -1.6 | 0.603653E+10 | 7498.48 | 07-MAR-10:00 | 8.90 | 7.50 |
April | 0.535621E+11 | 119369.07 | 03-APR-04:12 | 10.60 | 9.99 | 0.531568E+10 | 7499.34 | 27-APR-09:09 | 17.98 | 12.34 |
May | 0.571351E+11 | 131264.55 | 24-MAY-05:01 | 7.80 | 6.94 | 0.572572E+10 | 7499.32 | 16-MAY-13:00 | 7.80 | 6.94 |
June | 0.602496E+11 | 137756.67 | 19-JUN-04:11 | 10.77 | 9.45 | 0.579997E+10 | 7499.34 | 05-JUN-13:20 | 10.77 | 9.45 |
July | 0.613823E+11 | 127180.70 | 01-JUL-04:11 | 13.70 | 10.48 | 0.545215E+10 | 7499.34 | 11-JUL-09:30 | 16.40 | 15.57 |
August | 0.696987E+11 | 121924.59 | 21-AUG-04:12 | 11.47 | 11.08 | 0.610623E+10 | 7499.33 | 16-AUG-09:20 | 11.47 | 11.08 |
September | 0.607147E+11 | 133746.53 | 05-SEP-04:12 | 11.33 | 9.63 | 0.536412E+10 | 7499.34 | 08-SEP-09:00 | 17.20 | 13.55 |
October | 0.607864E+11 | 140101.37 | 02-OCT-04:11 | 9.40 | 8.23 | 0.553620E+10 | 7499.33 | 06-OCT-13:50 | 17.12 | 11.98 |
November | 0.569220E+11 | 125450.88 | 06-NOV-05:11 | 10.77 | 8.10 | 0.553247E+10 | 7499.02 | 02-NOV-13:50 | 10.77 | 8.10 |
December | 0.535783E+11 | 120196.61 | 11-DEC-05:11 | 4.13 | 3.14 | 0.531055E+10 | 7498.25 | 20-DEC-14:09 | 6.70 | 5.56 |
Annual Sum or Average | 0.682775E+12 | 0.665726E+11 | ||||||||
Minimum of Months | 0.447477E+11 | 119369.07 | 0.00 | -1.6 | 0.501099E+10 | 7495.04 | 6.10 | 5.49 | ||
Maximum of Months | 0.696987E+11 | 140101.37 | 13.70 | 11.08 | 0.610623E+10 | 7499.34 | 19.43 | 15.57 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.382014E+11 | 101562.11 | 26-JAN-06:01 | 4.60 | 4.18 | 0.502001E+10 | 6734.87 | 18-JAN-10:20 | 4.60 | 4.18 |
February | 0.376226E+11 | 107403.87 | 27-FEB-06:01 | 6.28 | 5.43 | 0.456802E+10 | 6734.90 | 23-FEB-10:50 | 6.28 | 5.43 |
March | 0.500036E+11 | 107592.00 | 10-MAR-05:11 | 11.10 | 10.93 | 0.548463E+10 | 6734.90 | 31-MAR-13:09 | 8.98 | 7.53 |
April | 0.507670E+11 | 113627.04 | 28-APR-04:12 | 11.50 | 10.06 | 0.487869E+10 | 6734.89 | 20-APR-09:00 | 11.50 | 10.06 |
May | 0.534035E+11 | 114342.93 | 01-MAY-04:12 | 12.20 | 10.35 | 0.527756E+10 | 6734.89 | 12-MAY-09:09 | 12.62 | 10.40 |
June | 0.572246E+11 | 117800.06 | 12-JUN-04:11 | 14.80 | 13.61 | 0.526828E+10 | 6734.91 | 05-JUN-09:00 | 14.80 | 13.61 |
July | 0.614266E+11 | 120435.66 | 17-JUL-04:11 | 14.23 | 12.63 | 0.489844E+10 | 6734.89 | 12-JUL-13:09 | 14.23 | 12.63 |
August | 0.698760E+11 | 117608.19 | 14-AUG-04:11 | 15.20 | 13.41 | 0.549865E+10 | 6735.30 | 09-AUG-09:00 | 15.20 | 13.41 |
September | 0.522477E+11 | 116701.18 | 05-SEP-04:12 | 11.33 | 9.63 | 0.487989E+10 | 6734.88 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.484736E+11 | 119017.04 | 10-OCT-04:11 | 12.20 | 11.04 | 0.506690E+10 | 6734.89 | 12-OCT-09:20 | 9.47 | 7.95 |
November | 0.450060E+11 | 114240.12 | 06-NOV-05:11 | 10.77 | 8.10 | 0.501542E+10 | 6734.89 | 17-NOV-10:39 | 8.30 | 7.18 |
December | 0.431537E+11 | 106656.44 | 28-DEC-06:01 | 9.40 | 8.02 | 0.487704E+10 | 6734.91 | 13-DEC-14:09 | 9.40 | 8.02 |
Annual Sum or Average | 0.607406E+12 | 0.607335E+11 | ||||||||
Minimum of Months | 0.376226E+11 | 101562.11 | 4.60 | 4.18 | 0.456802E+10 | 6734.87 | 4.60 | 4.18 | ||
Maximum of Months | 0.698760E+11 | 120435.66 | 15.20 | 13.61 | 0.549865E+10 | 6735.30 | 15.20 | 14.31 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.278935E+11 | 32038.50 | 12-JAN-16:55 | 7.20 | 5.41 | 0.470137E+10 | 6734.84 | 06-JAN-14:50 | 7.20 | 5.41 |
February | 0.288927E+11 | 92359.30 | 28-FEB-06:01 | 10.60 | 9.74 | 0.441404E+10 | 6734.90 | 02-FEB-10:09 | 10.60 | 9.74 |
March | 0.382349E+11 | 94509.30 | 03-MAR-06:01 | 6.60 | 6.18 | 0.540741E+10 | 6734.90 | 31-MAR-13:09 | 8.98 | 7.53 |
April | 0.380824E+11 | 99494.69 | 28-APR-04:12 | 11.50 | 10.06 | 0.482671E+10 | 6734.89 | 20-APR-09:00 | 11.50 | 10.06 |
May | 0.448372E+11 | 101978.73 | 16-MAY-05:01 | 11.70 | 10.43 | 0.525068E+10 | 6734.89 | 12-MAY-09:09 | 11.70 | 10.43 |
June | 0.474582E+11 | 103820.03 | 29-JUN-04:11 | 13.13 | 11.68 | 0.524844E+10 | 6734.90 | 05-JUN-13:39 | 13.13 | 11.68 |
July | 0.476570E+11 | 104319.64 | 25-JUL-04:11 | 13.90 | 13.04 | 0.488008E+10 | 6734.90 | 26-JUL-09:30 | 15.30 | 13.21 |
August | 0.524824E+11 | 104553.11 | 11-AUG-04:12 | 12.73 | 11.87 | 0.548367E+10 | 6735.18 | 09-AUG-09:00 | 12.73 | 11.87 |
September | 0.432222E+11 | 102202.76 | 09-SEP-05:01 | 12.12 | 10.94 | 0.485530E+10 | 6734.88 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.377946E+11 | 101591.25 | 05-OCT-05:01 | 8.30 | 5.23 | 0.500962E+10 | 6734.90 | 12-OCT-09:20 | 9.47 | 7.95 |
November | 0.319621E+11 | 94319.12 | 03-NOV-05:01 | 10.60 | 9.38 | 0.490373E+10 | 6734.90 | 17-NOV-10:39 | 8.30 | 7.18 |
December | 0.299679E+11 | 34566.63 | 06-DEC-16:14 | 2.57 | 2.27 | 0.468511E+10 | 6734.88 | 05-DEC-14:50 | 2.57 | 2.27 |
Annual Sum or Average | 0.468485E+12 | 0.596662E+11 | ||||||||
Minimum of Months | 0.278935E+11 | 32038.50 | 2.57 | 2.27 | 0.441404E+10 | 6734.84 | 2.57 | 2.27 | ||
Maximum of Months | 0.524824E+11 | 104553.11 | 13.90 | 13.04 | 0.548367E+10 | 6735.18 | 15.30 | 14.31 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.196485E+11 | 22288.38 | 11-JAN-17:00 | 12.20 | 9.27 | 0.412941E+10 | 6409.48 | 11-JAN-14:00 | 12.20 | 9.27 |
February | 0.207601E+11 | 30663.85 | 28-FEB-16:53 | 14.40 | 10.82 | 0.389340E+10 | 6734.86 | 24-FEB-14:50 | 14.40 | 10.82 |
March | 0.288256E+11 | 35848.38 | 15-MAR-15:53 | 11.10 | 7.72 | 0.491560E+10 | 6734.89 | 09-MAR-14:09 | 11.10 | 7.72 |
April | 0.322736E+11 | 54179.11 | 27-APR-15:30 | 27.20 | 17.10 | 0.454237E+10 | 6734.85 | 28-APR-09:09 | 11.70 | 11.07 |
May | 0.409315E+11 | 55273.43 | 04-MAY-15:30 | 24.15 | 14.75 | 0.507793E+10 | 6734.88 | 05-MAY-09:20 | 16.33 | 13.64 |
June | 0.459907E+11 | 102686.84 | 12-JUN-05:01 | 14.40 | 13.42 | 0.516892E+10 | 6734.90 | 05-JUN-09:00 | 14.40 | 13.42 |
July | 0.482922E+11 | 102631.05 | 28-JUL-05:01 | 14.50 | 12.30 | 0.483039E+10 | 6734.89 | 07-JUL-09:09 | 14.50 | 12.30 |
August | 0.515328E+11 | 102693.26 | 11-AUG-05:01 | 13.30 | 12.27 | 0.542637E+10 | 6735.10 | 09-AUG-09:00 | 13.30 | 12.27 |
September | 0.372728E+11 | 72028.25 | 01-SEP-05:01 | 15.50 | 13.57 | 0.468263E+10 | 6734.87 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.285864E+11 | 44588.97 | 04-OCT-16:00 | 21.10 | 11.40 | 0.460067E+10 | 6734.88 | 19-OCT-13:09 | 13.40 | 10.09 |
November | 0.228062E+11 | 29412.71 | 02-NOV-15:52 | 13.30 | 10.88 | 0.430142E+10 | 6734.87 | 02-NOV-13:20 | 13.30 | 10.88 |
December | 0.197097E+11 | 22075.67 | 29-DEC-17:00 | 9.40 | 7.98 | 0.401050E+10 | 6375.91 | 29-DEC-14:00 | 9.40 | 7.98 |
Annual Sum or Average | 0.396630E+12 | 0.555796E+11 | ||||||||
Minimum of Months | 0.196485E+11 | 22075.67 | 9.40 | 7.72 | 0.389340E+10 | 6375.91 | 9.40 | 7.72 | ||
Maximum of Months | 0.515328E+11 | 102693.26 | 27.20 | 17.10 | 0.542637E+10 | 6735.10 | 17.38 | 15.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.281923E+10 | 3582.23 | 11-JAN-06:03 | 9.90 | 7.47 | 0.520192E+09 | 804.10 | 11-JAN-14:39 | 14.40 | 10.49 |
February | 0.314659E+10 | 5140.86 | 27-FEB-15:37 | 19.60 | 12.34 | 0.494069E+09 | 845.63 | 24-FEB-14:20 | 19.60 | 12.34 |
March | 0.467724E+10 | 5886.17 | 10-MAR-14:22 | 16.40 | 11.76 | 0.634664E+09 | 845.63 | 09-MAR-14:09 | 16.40 | 11.76 |
April | 0.563471E+10 | 9440.15 | 27-APR-15:20 | 27.20 | 17.16 | 0.586972E+09 | 845.63 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.708809E+10 | 9256.84 | 05-MAY-13:30 | 23.85 | 16.52 | 0.647168E+09 | 845.64 | 05-MAY-13:50 | 24.22 | 16.54 |
June | 0.817969E+10 | 9923.85 | 21-JUN-15:30 | 24.70 | 15.68 | 0.655361E+09 | 845.65 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.937960E+10 | 11905.15 | 24-JUL-15:00 | 30.60 | 18.78 | 0.611744E+09 | 845.64 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.101773E+11 | 11371.77 | 25-AUG-14:00 | 27.40 | 18.74 | 0.686441E+09 | 845.71 | 09-AUG-09:00 | 27.40 | 18.74 |
September | 0.636513E+10 | 8552.60 | 12-SEP-14:30 | 24.40 | 16.63 | 0.597431E+09 | 845.64 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.477660E+10 | 6288.92 | 04-OCT-15:00 | 21.70 | 11.49 | 0.596100E+09 | 845.63 | 19-OCT-13:09 | 13.40 | 10.09 |
November | 0.388966E+10 | 4494.87 | 02-NOV-13:52 | 14.40 | 11.37 | 0.561283E+09 | 845.63 | 01-NOV-13:09 | 14.40 | 11.37 |
December | 0.335730E+10 | 3810.12 | 29-DEC-06:02 | 9.90 | 8.72 | 0.516815E+09 | 801.56 | 29-DEC-14:20 | 10.93 | 8.95 |
Annual Sum or Average | 0.694911E+11 | 0.710824E+10 | ||||||||
Minimum of Months | 0.281923E+10 | 3582.23 | 9.90 | 7.47 | 0.494069E+09 | 801.56 | 10.93 | 8.95 | ||
Maximum of Months | 0.101773E+11 | 11905.15 | 30.60 | 18.78 | 0.686441E+09 | 845.71 | 27.40 | 18.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262160E+10 | 4852.84 | 11-JAN-06:03 | 9.90 | 7.47 | 0.307460E+09 | 472.43 | 20-JAN-10:39 | 5.03 | 3.09 |
February | 0.326230E+10 | 5589.40 | 12-FEB-12:11 | 5.77 | 0.75 | 0.294700E+09 | 527.44 | 08-FEB-10:09 | 5.77 | 0.75 |
March | 0.533326E+10 | 9856.03 | 14-MAR-09:13 | 8.53 | 6.52 | 0.377009E+09 | 544.96 | 02-MAR-10:09 | 8.53 | 6.52 |
April | 0.671621E+10 | 14023.54 | 27-APR-08:50 | 17.52 | 12.20 | 0.361862E+09 | 544.96 | 20-APR-09:00 | 17.52 | 12.20 |
May | 0.786095E+10 | 14816.79 | 14-MAY-09:02 | 17.07 | 11.66 | 0.397964E+09 | 544.98 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.912296E+10 | 31269.95 | 25-JUN-09:31 | 17.43 | 12.65 | 0.409317E+09 | 544.97 | 09-JUN-13:09 | 17.43 | 12.65 |
July | 0.969430E+10 | 32748.20 | 30-JUL-07:51 | 18.30 | 14.65 | 0.384152E+09 | 544.99 | 24-JUL-09:09 | 18.30 | 14.65 |
August | 0.105641E+11 | 32671.38 | 13-AUG-08:51 | 20.90 | 15.90 | 0.430792E+09 | 545.05 | 09-AUG-09:00 | 20.90 | 15.90 |
September | 0.747283E+10 | 30119.94 | 10-SEP-09:22 | 16.65 | 13.51 | 0.365464E+09 | 544.96 | 15-SEP-09:39 | 17.80 | 14.95 |
October | 0.552624E+10 | 11581.45 | 09-OCT-08:29 | 12.80 | 11.20 | 0.354560E+09 | 544.96 | 05-OCT-09:00 | 12.80 | 11.20 |
November | 0.386004E+10 | 5673.92 | 06-NOV-05:11 | 10.77 | 8.10 | 0.320208E+09 | 516.90 | 15-NOV-10:09 | 7.30 | 5.72 |
December | 0.291692E+10 | 5089.53 | 29-DEC-06:02 | 9.90 | 8.72 | 0.300533E+09 | 498.12 | 05-DEC-10:20 | 9.90 | 8.72 |
Annual Sum or Average | 0.749517E+11 | 0.430402E+10 | ||||||||
Minimum of Months | 0.262160E+10 | 4852.84 | 5.77 | 0.75 | 0.294700E+09 | 472.43 | 5.03 | 0.75 | ||
Maximum of Months | 0.105641E+11 | 32748.20 | 20.90 | 15.90 | 0.430792E+09 | 545.05 | 20.90 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.466953E+10 | 19510.37 | 20-JAN-13:08 | 6.70 | 4.72 | 0.502669E+09 | 845.65 | 11-JAN-14:09 | 6.70 | 4.72 |
February | 0.641362E+10 | 42360.63 | 12-FEB-13:31 | 6.50 | 1.20 | 0.485483E+09 | 845.65 | 08-FEB-10:20 | 6.50 | 1.20 |
March | 0.990676E+10 | 23204.07 | 14-MAR-12:52 | 14.40 | 9.50 | 0.603543E+09 | 845.65 | 02-MAR-10:09 | 14.40 | 9.50 |
April | 0.109809E+11 | 41264.78 | 02-APR-13:22 | 18.90 | 11.09 | 0.558966E+09 | 845.66 | 27-APR-13:09 | 26.10 | 16.37 |
May | 0.117883E+11 | 25293.81 | 07-MAY-12:42 | 20.40 | 16.03 | 0.611319E+09 | 845.68 | 05-MAY-13:50 | 20.40 | 16.03 |
June | 0.122989E+11 | 20018.27 | 18-JUN-13:12 | 17.97 | 11.74 | 0.622734E+09 | 845.68 | 09-JUN-13:09 | 17.97 | 11.74 |
July | 0.145417E+11 | 33453.73 | 30-JUL-13:12 | 26.30 | 17.73 | 0.589279E+09 | 845.67 | 28-JUL-13:39 | 26.30 | 17.73 |
August | 0.168815E+11 | 45480.09 | 13-AUG-12:51 | 26.50 | 18.40 | 0.663984E+09 | 846.69 | 29-AUG-13:09 | 29.03 | 20.11 |
September | 0.137099E+11 | 46690.66 | 10-SEP-12:41 | 20.40 | 13.99 | 0.568939E+09 | 845.68 | 12-SEP-13:00 | 24.40 | 16.54 |
October | 0.106253E+11 | 45707.53 | 08-OCT-13:11 | 18.53 | 13.81 | 0.565632E+09 | 846.08 | 04-OCT-13:00 | 18.53 | 13.81 |
November | 0.659776E+10 | 26963.60 | 11-NOV-12:31 | 6.13 | 4.87 | 0.519762E+09 | 845.65 | 13-NOV-10:00 | 2.80 | 2.80 |
December | 0.565461E+10 | 20308.85 | 05-DEC-12:25 | 10.30 | 6.13 | 0.497656E+09 | 845.65 | 05-DEC-14:50 | 10.10 | 6.91 |
Annual Sum or Average | 0.124069E+12 | 0.678997E+10 | ||||||||
Minimum of Months | 0.466953E+10 | 19510.37 | 6.13 | 1.20 | 0.485483E+09 | 845.65 | 2.80 | 1.20 | ||
Maximum of Months | 0.168815E+11 | 46690.66 | 26.50 | 18.40 | 0.663984E+09 | 846.69 | 29.03 | 20.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.434149E+10 | 6545.47 | 11-JAN-06:03 | 9.90 | 7.47 | 0.315127E+09 | 512.69 | 05-JAN-14:00 | 9.90 | 7.47 |
February | 0.508046E+10 | 12514.26 | 26-FEB-15:03 | 14.40 | 10.47 | 0.302386E+09 | 544.96 | 27-FEB-14:50 | 19.72 | 12.05 |
March | 0.780382E+10 | 15732.35 | 18-MAR-17:07 | 19.22 | 9.55 | 0.385511E+09 | 544.96 | 14-MAR-13:39 | 19.22 | 9.55 |
April | 0.942907E+10 | 35586.27 | 23-APR-17:41 | 15.97 | 9.55 | 0.364916E+09 | 544.96 | 27-APR-13:39 | 26.10 | 16.65 |
May | 0.102054E+11 | 39904.48 | 07-MAY-16:01 | 22.12 | 16.29 | 0.392815E+09 | 544.97 | 05-MAY-13:50 | 22.12 | 16.29 |
June | 0.110286E+11 | 39147.33 | 18-JUN-16:31 | 17.57 | 12.19 | 0.404280E+09 | 544.97 | 09-JUN-13:09 | 17.57 | 12.19 |
July | 0.138570E+11 | 37821.16 | 23-JUL-17:01 | 26.60 | 15.64 | 0.387850E+09 | 544.97 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.149227E+11 | 37310.20 | 06-AUG-16:51 | 23.40 | 15.11 | 0.438033E+09 | 545.03 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.967631E+10 | 38437.42 | 10-SEP-16:01 | 22.20 | 14.43 | 0.362034E+09 | 544.97 | 12-SEP-13:00 | 24.40 | 16.54 |
October | 0.746755E+10 | 21089.90 | 01-OCT-15:41 | 16.70 | 13.63 | 0.355376E+09 | 544.96 | 03-OCT-13:20 | 18.30 | 10.45 |
November | 0.614568E+10 | 10031.26 | 05-NOV-14:38 | 15.33 | 13.14 | 0.337473E+09 | 544.96 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.589267E+10 | 8138.04 | 10-DEC-15:21 | 10.30 | 8.67 | 0.324598E+09 | 544.96 | 05-DEC-14:50 | 10.30 | 8.67 |
Annual Sum or Average | 0.105851E+12 | 0.437040E+10 | ||||||||
Minimum of Months | 0.434149E+10 | 6545.47 | 9.90 | 7.47 | 0.302386E+09 | 512.69 | 8.90 | 6.49 | ||
Maximum of Months | 0.149227E+11 | 39904.48 | 26.60 | 16.29 | 0.438033E+09 | 545.03 | 26.10 | 16.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110317E+10 | 3345.59 | 11-JAN-15:02 | 14.40 | 10.49 | 0.468155E+09 | 696.24 | 11-JAN-14:00 | 14.40 | 10.49 |
February | 0.180124E+10 | 3981.31 | 28-FEB-15:04 | 13.90 | 10.77 | 0.437990E+09 | 783.10 | 28-FEB-14:00 | 13.90 | 10.77 |
March | 0.349008E+10 | 4268.16 | 10-MAR-15:02 | 16.02 | 11.51 | 0.555697E+09 | 820.84 | 10-MAR-14:50 | 16.02 | 11.51 |
April | 0.436586E+10 | 8146.75 | 27-APR-15:50 | 27.20 | 16.97 | 0.528877E+09 | 845.63 | 27-APR-13:20 | 27.20 | 16.97 |
May | 0.619147E+10 | 8557.30 | 05-MAY-15:30 | 24.70 | 17.20 | 0.611702E+09 | 845.64 | 05-MAY-13:50 | 24.70 | 17.20 |
June | 0.714228E+10 | 9250.68 | 21-JUN-15:40 | 24.80 | 15.84 | 0.631176E+09 | 845.64 | 09-JUN-13:09 | 24.80 | 15.84 |
July | 0.783531E+10 | 10665.36 | 24-JUL-15:00 | 30.60 | 18.78 | 0.594634E+09 | 845.64 | 28-JUL-13:00 | 20.00 | 15.26 |
August | 0.823198E+10 | 10240.99 | 25-AUG-14:00 | 27.40 | 18.74 | 0.665858E+09 | 845.68 | 09-AUG-09:00 | 27.40 | 18.74 |
September | 0.566960E+10 | 7549.64 | 12-SEP-15:00 | 24.40 | 16.71 | 0.560780E+09 | 845.63 | 01-SEP-13:20 | 24.40 | 16.71 |
October | 0.380357E+10 | 4916.38 | 04-OCT-13:15 | 20.77 | 11.28 | 0.527747E+09 | 832.83 | 05-OCT-13:00 | 16.10 | 10.65 |
November | 0.230691E+10 | 4031.87 | 04-NOV-05:01 | 12.80 | 11.49 | 0.481615E+09 | 758.75 | 02-NOV-13:00 | 12.80 | 11.49 |
December | 0.129406E+10 | 3151.84 | 29-DEC-15:02 | 10.60 | 8.76 | 0.452563E+09 | 669.63 | 29-DEC-14:00 | 10.60 | 8.76 |
Annual Sum or Average | 0.532355E+11 | 0.651679E+10 | ||||||||
Minimum of Months | 0.110317E+10 | 3151.84 | 10.60 | 8.76 | 0.437990E+09 | 669.63 | 10.60 | 8.76 | ||
Maximum of Months | 0.823198E+10 | 10665.36 | 30.60 | 18.78 | 0.665858E+09 | 845.68 | 27.40 | 18.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.726920E+09 | 4958.92 | 20-JAN-11:02 | 5.60 | 3.32 | 0.221531E+09 | 516.91 | 20-JAN-11:09 | 5.60 | 3.32 |
February | 0.147429E+10 | 12606.38 | 03-FEB-11:01 | 10.10 | 7.33 | 0.208790E+09 | 548.49 | 27-FEB-15:09 | 19.90 | 12.22 |
March | 0.325637E+10 | 18734.21 | 14-MAR-10:01 | 10.28 | 7.92 | 0.266061E+09 | 548.49 | 14-MAR-10:09 | 10.28 | 7.92 |
April | 0.509522E+10 | 19019.18 | 26-APR-10:01 | 16.47 | 11.04 | 0.257664E+09 | 548.50 | 27-APR-14:09 | 26.28 | 16.91 |
May | 0.665402E+10 | 30885.30 | 14-MAY-09:32 | 18.17 | 11.98 | 0.284728E+09 | 548.52 | 15-MAY-10:09 | 19.18 | 13.24 |
June | 0.825724E+10 | 32783.61 | 25-JUN-09:51 | 17.80 | 12.97 | 0.295177E+09 | 548.51 | 27-JUN-14:09 | 23.98 | 14.78 |
July | 0.869898E+10 | 33768.51 | 23-JUL-08:61 | 17.98 | 13.63 | 0.277772E+09 | 548.51 | 07-JUL-12:09 | 17.98 | 13.63 |
August | 0.938098E+10 | 32565.83 | 06-AUG-08:41 | 15.12 | 12.79 | 0.311494E+09 | 548.59 | 09-AUG-10:09 | 23.92 | 16.01 |
September | 0.627319E+10 | 20666.42 | 10-SEP-09:42 | 17.02 | 13.53 | 0.262167E+09 | 548.50 | 12-SEP-14:09 | 24.40 | 16.57 |
October | 0.360173E+10 | 19143.11 | 03-OCT-10:01 | 15.18 | 9.09 | 0.250966E+09 | 548.49 | 05-OCT-10:09 | 14.08 | 9.36 |
November | 0.159470E+10 | 12774.16 | 02-NOV-10:01 | 11.88 | 10.24 | 0.226015E+09 | 548.49 | 02-NOV-14:09 | 14.22 | 11.35 |
December | 0.915909E+09 | 5338.71 | 05-DEC-11:01 | 8.58 | 5.53 | 0.215177E+09 | 536.93 | 05-DEC-11:09 | 8.58 | 5.53 |
Annual Sum or Average | 0.559295E+11 | 0.307754E+10 | ||||||||
Minimum of Months | 0.726920E+09 | 4958.92 | 5.60 | 3.32 | 0.208790E+09 | 516.91 | 5.60 | 3.32 | ||
Maximum of Months | 0.938098E+10 | 33768.51 | 18.17 | 13.63 | 0.311494E+09 | 548.59 | 26.28 | 16.91 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.320331E+10 | 20469.03 | 20-JAN-13:13 | 6.70 | 4.72 | 0.490149E+09 | 845.65 | 06-JAN-14:50 | 6.70 | 4.72 |
February | 0.542908E+10 | 44774.46 | 12-FEB-13:51 | 6.70 | 1.36 | 0.473082E+09 | 845.67 | 27-FEB-14:39 | 19.43 | 11.93 |
March | 0.868090E+10 | 25221.86 | 14-MAR-13:23 | 15.00 | 10.00 | 0.586490E+09 | 845.66 | 17-MAR-13:30 | 11.95 | 8.17 |
April | 0.953975E+10 | 24732.56 | 27-APR-13:20 | 26.10 | 16.46 | 0.541830E+09 | 845.67 | 04-APR-13:20 | 26.10 | 16.46 |
May | 0.107973E+11 | 41396.07 | 14-MAY-12:52 | 22.20 | 12.20 | 0.594898E+09 | 845.68 | 05-MAY-13:50 | 22.20 | 12.20 |
June | 0.112452E+11 | 26972.92 | 11-JUN-12:42 | 21.70 | 15.34 | 0.602806E+09 | 845.68 | 09-JUN-13:09 | 21.70 | 15.34 |
July | 0.131192E+11 | 35827.36 | 30-JUL-13:32 | 26.50 | 17.71 | 0.573329E+09 | 845.67 | 28-JUL-13:39 | 26.50 | 17.71 |
August | 0.151750E+11 | 43107.22 | 06-AUG-12:42 | 21.33 | 15.15 | 0.646510E+09 | 846.48 | 29-AUG-13:09 | 29.03 | 20.11 |
September | 0.132755E+11 | 43878.04 | 10-SEP-14:22 | 22.50 | 14.48 | 0.555678E+09 | 846.40 | 08-SEP-13:20 | 22.50 | 14.48 |
October | 0.972188E+10 | 47942.54 | 08-OCT-13:31 | 19.27 | 14.01 | 0.550247E+09 | 846.01 | 04-OCT-13:00 | 19.27 | 14.01 |
November | 0.485562E+10 | 36253.64 | 11-NOV-13:41 | 7.62 | 5.43 | 0.499426E+09 | 845.66 | 02-NOV-13:30 | 7.62 | 5.43 |
December | 0.400881E+10 | 19910.19 | 05-DEC-12:25 | 10.30 | 6.13 | 0.483383E+09 | 845.65 | 05-DEC-14:50 | 10.10 | 6.91 |
Annual Sum or Average | 0.109051E+12 | 0.659783E+10 | ||||||||
Minimum of Months | 0.320331E+10 | 19910.19 | 6.70 | 1.36 | 0.473082E+09 | 845.65 | 6.70 | 4.72 | ||
Maximum of Months | 0.151750E+11 | 47942.54 | 26.50 | 17.71 | 0.646510E+09 | 846.48 | 29.03 | 20.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125955E+10 | 4800.09 | 05-JAN-15:45 | 6.20 | 4.71 | 0.301933E+09 | 454.66 | 05-JAN-15:50 | 6.20 | 4.71 |
February | 0.220527E+10 | 9488.65 | 27-FEB-15:25 | 19.70 | 12.30 | 0.283340E+09 | 544.96 | 27-FEB-14:39 | 19.70 | 12.30 |
March | 0.422965E+10 | 12703.17 | 14-MAR-16:00 | 17.20 | 10.94 | 0.347759E+09 | 544.96 | 02-MAR-14:50 | 17.20 | 10.94 |
April | 0.579962E+10 | 19262.16 | 01-APR-17:06 | 26.52 | 12.40 | 0.325216E+09 | 544.96 | 27-APR-13:50 | 26.10 | 16.74 |
May | 0.795934E+10 | 36953.23 | 14-MAY-16:11 | 23.13 | 11.97 | 0.366532E+09 | 544.97 | 05-MAY-13:50 | 23.13 | 11.97 |
June | 0.869353E+10 | 33477.24 | 25-JUN-16:41 | 21.70 | 13.39 | 0.375478E+09 | 544.96 | 01-JUN-13:50 | 21.70 | 13.39 |
July | 0.106038E+11 | 34743.45 | 30-JUL-17:31 | 26.70 | 17.74 | 0.361217E+09 | 544.96 | 28-JUL-13:00 | 26.70 | 17.74 |
August | 0.105415E+11 | 37741.82 | 06-AUG-16:41 | 23.47 | 15.19 | 0.403531E+09 | 544.96 | 09-AUG-13:20 | 27.77 | 17.73 |
September | 0.753696E+10 | 30583.09 | 10-SEP-16:22 | 22.20 | 14.33 | 0.337326E+09 | 544.96 | 12-SEP-13:00 | 24.40 | 16.54 |
October | 0.450907E+10 | 13925.29 | 04-OCT-16:00 | 21.10 | 11.40 | 0.324751E+09 | 544.96 | 03-OCT-13:00 | 21.10 | 11.40 |
November | 0.237443E+10 | 6253.20 | 04-NOV-15:30 | 20.55 | 15.94 | 0.303355E+09 | 505.18 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.154785E+10 | 5076.71 | 05-DEC-15:30 | 8.05 | 5.82 | 0.293499E+09 | 479.68 | 05-DEC-14:00 | 8.05 | 5.82 |
Annual Sum or Average | 0.672606E+11 | 0.402394E+10 | ||||||||
Minimum of Months | 0.125955E+10 | 4800.09 | 6.20 | 4.71 | 0.283340E+09 | 454.66 | 6.20 | 4.71 | ||
Maximum of Months | 0.106038E+11 | 37741.82 | 26.70 | 17.74 | 0.403531E+09 | 544.97 | 27.77 | 17.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.453866E+09 | 3804.59 | 11-JAN-15:00 | 14.40 | 10.49 | 0.464229E+09 | 633.03 | 11-JAN-14:00 | 14.40 | 10.49 |
February | 0.112367E+10 | 4679.18 | 27-FEB-16:08 | 19.32 | 12.38 | 0.425658E+09 | 716.34 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.268010E+10 | 5077.08 | 10-MAR-14:50 | 16.20 | 11.59 | 0.523049E+09 | 764.55 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.418436E+10 | 9171.75 | 27-APR-15:20 | 27.20 | 17.16 | 0.495297E+09 | 845.63 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.640905E+10 | 9120.66 | 31-MAY-15:00 | 22.20 | 15.72 | 0.573424E+09 | 845.64 | 05-MAY-13:50 | 22.20 | 15.72 |
June | 0.769591E+10 | 10325.43 | 21-JUN-15:40 | 24.80 | 15.84 | 0.597936E+09 | 845.64 | 09-JUN-13:09 | 24.80 | 15.84 |
July | 0.855845E+10 | 12268.85 | 24-JUL-15:00 | 30.60 | 18.78 | 0.570034E+09 | 845.64 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.880463E+10 | 11378.12 | 09-AUG-15:30 | 28.70 | 18.83 | 0.637090E+09 | 845.63 | 15-AUG-13:09 | 24.25 | 15.86 |
September | 0.553958E+10 | 8113.65 | 12-SEP-15:10 | 24.40 | 16.76 | 0.520076E+09 | 845.63 | 12-SEP-13:00 | 24.40 | 16.76 |
October | 0.298397E+10 | 5573.51 | 04-OCT-13:30 | 20.85 | 11.31 | 0.488632E+09 | 777.87 | 04-OCT-13:00 | 21.10 | 11.41 |
November | 0.124212E+10 | 4452.74 | 02-NOV-14:31 | 13.67 | 11.26 | 0.463024E+09 | 693.15 | 02-NOV-13:00 | 13.67 | 11.26 |
December | 0.424357E+09 | 3455.94 | 30-DEC-17:02 | 5.60 | 4.81 | 0.447852E+09 | 625.85 | 14-DEC-10:20 | 5.60 | 4.81 |
Annual Sum or Average | 0.501001E+11 | 0.620630E+10 | ||||||||
Minimum of Months | 0.424357E+09 | 3455.94 | 5.60 | 4.81 | 0.425658E+09 | 625.85 | 5.60 | 4.81 | ||
Maximum of Months | 0.880463E+10 | 12268.85 | 30.60 | 18.83 | 0.637090E+09 | 845.64 | 27.20 | 17.16 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.422743E+09 | 3526.20 | 20-JAN-06:04 | -0.1 | -0.6 | 0.299126E+09 | 403.43 | 17-JAN-10:39 | -0.1 | -0.6 |
February | 0.123713E+10 | 4115.94 | 27-FEB-15:40 | 19.60 | 12.34 | 0.274297E+09 | 448.29 | 27-FEB-14:00 | 19.60 | 12.34 |
March | 0.294509E+10 | 6919.42 | 14-MAR-10:01 | 10.28 | 7.92 | 0.345418E+09 | 544.96 | 14-MAR-09:20 | 10.28 | 7.92 |
April | 0.484643E+10 | 13496.42 | 27-APR-09:25 | 18.35 | 12.60 | 0.340885E+09 | 544.96 | 20-APR-09:00 | 18.35 | 12.60 |
May | 0.654654E+10 | 27196.75 | 14-MAY-09:32 | 18.17 | 11.98 | 0.379158E+09 | 544.98 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.826057E+10 | 31644.64 | 25-JUN-09:41 | 17.62 | 12.81 | 0.397441E+09 | 544.97 | 09-JUN-13:09 | 17.62 | 12.81 |
July | 0.884310E+10 | 31607.79 | 30-JUL-07:51 | 18.30 | 14.65 | 0.374939E+09 | 544.99 | 24-JUL-09:09 | 18.30 | 14.65 |
August | 0.948561E+10 | 33351.20 | 13-AUG-09:21 | 21.80 | 16.25 | 0.419193E+09 | 545.05 | 09-AUG-09:00 | 21.80 | 16.25 |
September | 0.590091E+10 | 27470.13 | 10-SEP-09:32 | 16.83 | 13.52 | 0.346725E+09 | 544.96 | 12-SEP-13:00 | 24.40 | 16.54 |
October | 0.311079E+10 | 8737.09 | 04-OCT-09:32 | 16.67 | 10.80 | 0.325968E+09 | 544.96 | 05-OCT-09:30 | 12.80 | 8.29 |
November | 0.110952E+10 | 4049.10 | 02-NOV-10:31 | 12.43 | 10.47 | 0.298254E+09 | 440.79 | 02-NOV-13:00 | 14.40 | 11.37 |
December | 0.466123E+09 | 3651.66 | 12-DEC-06:04 | 0.87 | 0.87 | 0.288676E+09 | 403.32 | 08-DEC-14:09 | 0.87 | 0.87 |
Annual Sum or Average | 0.531745E+11 | 0.409008E+10 | ||||||||
Minimum of Months | 0.422743E+09 | 3526.20 | -0.1 | -0.6 | 0.274297E+09 | 403.32 | -0.1 | -0.6 | ||
Maximum of Months | 0.948561E+10 | 33351.20 | 21.80 | 16.25 | 0.419193E+09 | 545.05 | 24.40 | 16.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227829E+10 | 18517.27 | 20-JAN-13:25 | 6.70 | 4.72 | 0.478586E+09 | 845.65 | 20-JAN-14:09 | 6.78 | 4.76 |
February | 0.417565E+10 | 21902.16 | 27-FEB-14:22 | 19.15 | 11.80 | 0.460882E+09 | 845.65 | 07-FEB-14:09 | 19.15 | 11.80 |
March | 0.713299E+10 | 25080.56 | 14-MAR-13:23 | 15.00 | 10.00 | 0.569888E+09 | 845.65 | 20-MAR-13:09 | 11.78 | 8.00 |
April | 0.865802E+10 | 36274.97 | 02-APR-13:12 | 18.90 | 11.02 | 0.526708E+09 | 845.66 | 27-APR-13:09 | 26.10 | 16.37 |
May | 0.102483E+11 | 37201.83 | 14-MAY-12:52 | 22.20 | 12.20 | 0.578087E+09 | 845.68 | 05-MAY-13:50 | 22.20 | 12.20 |
June | 0.110335E+11 | 29612.49 | 11-JUN-12:42 | 21.70 | 15.34 | 0.588169E+09 | 845.68 | 09-JUN-13:09 | 21.70 | 15.34 |
July | 0.131360E+11 | 37229.59 | 30-JUL-13:52 | 26.70 | 17.68 | 0.562649E+09 | 845.67 | 28-JUL-13:39 | 26.70 | 17.68 |
August | 0.150632E+11 | 51036.71 | 13-AUG-14:01 | 27.35 | 18.84 | 0.632620E+09 | 845.69 | 15-AUG-13:09 | 24.25 | 15.86 |
September | 0.122272E+11 | 53285.94 | 10-SEP-14:11 | 22.40 | 14.54 | 0.539002E+09 | 845.68 | 12-SEP-13:00 | 24.40 | 16.54 |
October | 0.802258E+10 | 48049.44 | 08-OCT-13:41 | 19.63 | 14.09 | 0.532549E+09 | 846.12 | 04-OCT-13:00 | 19.63 | 14.09 |
November | 0.327777E+10 | 20885.40 | 04-NOV-13:25 | 20.85 | 16.00 | 0.482033E+09 | 845.65 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.258166E+10 | 17062.18 | 05-DEC-12:25 | 10.30 | 6.13 | 0.470918E+09 | 845.65 | 05-DEC-14:50 | 10.10 | 6.91 |
Annual Sum or Average | 0.978352E+11 | 0.642209E+10 | ||||||||
Minimum of Months | 0.227829E+10 | 17062.18 | 6.70 | 4.72 | 0.460882E+09 | 845.65 | 6.78 | 4.76 | ||
Maximum of Months | 0.150632E+11 | 53285.94 | 27.35 | 18.84 | 0.632620E+09 | 846.12 | 26.70 | 17.68 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.787987E+09 | 4812.12 | 05-JAN-15:40 | 6.30 | 4.80 | 0.300052E+09 | 434.47 | 05-JAN-15:50 | 6.20 | 4.71 |
February | 0.161902E+10 | 9170.30 | 27-FEB-15:30 | 19.70 | 12.30 | 0.279543E+09 | 544.60 | 27-FEB-14:00 | 19.70 | 12.30 |
March | 0.338747E+10 | 13066.07 | 14-MAR-16:00 | 17.20 | 10.94 | 0.342315E+09 | 544.96 | 02-MAR-14:00 | 17.20 | 10.94 |
April | 0.528185E+10 | 20198.68 | 01-APR-17:06 | 26.52 | 12.40 | 0.319002E+09 | 544.96 | 27-APR-13:50 | 26.10 | 16.74 |
May | 0.765934E+10 | 39954.85 | 07-MAY-17:31 | 21.30 | 16.02 | 0.357931E+09 | 544.97 | 05-MAY-13:50 | 21.30 | 16.02 |
June | 0.857974E+10 | 36692.24 | 18-JUN-18:01 | 16.60 | 12.33 | 0.367732E+09 | 544.96 | 01-JUN-13:00 | 16.60 | 12.33 |
July | 0.106718E+11 | 37468.95 | 23-JUL-17:01 | 26.60 | 15.64 | 0.354556E+09 | 544.96 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.105110E+11 | 41221.18 | 06-AUG-17:11 | 23.53 | 15.16 | 0.394715E+09 | 544.96 | 09-AUG-13:20 | 27.77 | 17.73 |
September | 0.696882E+10 | 38112.65 | 10-SEP-16:51 | 22.20 | 14.17 | 0.328351E+09 | 544.96 | 12-SEP-13:00 | 24.40 | 16.54 |
October | 0.356673E+10 | 14093.85 | 04-OCT-16:00 | 21.10 | 11.40 | 0.318501E+09 | 544.96 | 03-OCT-13:00 | 21.10 | 11.40 |
November | 0.148817E+10 | 6152.58 | 04-NOV-15:40 | 20.37 | 15.93 | 0.300154E+09 | 485.59 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.891168E+09 | 5046.97 | 05-DEC-15:30 | 8.05 | 5.82 | 0.290428E+09 | 455.82 | 05-DEC-14:00 | 8.05 | 5.82 |
Annual Sum or Average | 0.614131E+11 | 0.395328E+10 | ||||||||
Minimum of Months | 0.787987E+09 | 4812.12 | 6.30 | 4.80 | 0.279543E+09 | 434.47 | 6.20 | 4.71 | ||
Maximum of Months | 0.106718E+11 | 41221.18 | 26.60 | 16.02 | 0.394715E+09 | 544.97 | 27.77 | 17.73 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328118E+10 | 8822.43 | 14-JAN-06:02 | 2.20 | 1.10 | 0.00 | 0.00 | 01-JAN-00:10 | 2.20 | 1.10 |
February | 0.371647E+10 | 8606.09 | 18-FEB-06:01 | -1.8 | -2.6 | 0.00 | 0.00 | 01-FEB-00:10 | -1.8 | -2.6 |
March | 0.580744E+10 | 7703.22 | 22-MAR-05:05 | 6.10 | 5.58 | 0.00 | 0.00 | 01-MAR-00:10 | 6.10 | 5.58 |
April | 0.651296E+10 | 9163.17 | 29-APR-05:10 | 8.40 | 8.40 | 0.00 | 0.00 | 01-APR-00:10 | 8.40 | 8.40 |
May | 0.746096E+10 | 9372.30 | 02-MAY-05:10 | 10.10 | 8.82 | 0.00 | 0.00 | 01-MAY-00:10 | 10.10 | 8.82 |
June | 0.844492E+10 | 8967.76 | 13-JUN-05:04 | 11.70 | 10.15 | 0.00 | 0.00 | 01-JUN-00:10 | 11.70 | 10.15 |
July | 0.987441E+10 | 9651.44 | 31-JUL-16:00 | 28.90 | 19.18 | 0.00 | 0.00 | 01-JUL-00:10 | 28.90 | 19.18 |
August | 0.112130E+11 | 10899.97 | 12-AUG-05:12 | 14.43 | 12.99 | 0.00 | 0.00 | 01-AUG-00:10 | 14.43 | 12.99 |
September | 0.805497E+10 | 10405.25 | 14-SEP-05:12 | 12.43 | 12.07 | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 | 12.07 |
October | 0.636657E+10 | 9084.67 | 10-OCT-05:06 | 12.20 | 11.22 | 0.00 | 0.00 | 01-OCT-00:10 | 12.20 | 11.22 |
November | 0.509004E+10 | 8629.25 | 06-NOV-06:04 | 11.28 | 8.36 | 0.00 | 0.00 | 01-NOV-00:10 | 11.28 | 8.36 |
December | 0.428741E+10 | 9231.28 | 26-DEC-06:01 | -0.8 | -0.8 | 0.00 | 0.00 | 01-DEC-00:10 | -0.8 | -0.8 |
Annual Sum or Average | 0.801103E+11 | 0.00 | ||||||||
Minimum of Months | 0.328118E+10 | 7703.22 | -1.8 | -2.6 | 0.00 | 0.00 | -1.8 | -2.6 | ||
Maximum of Months | 0.112130E+11 | 10899.97 | 28.90 | 19.18 | 0.00 | 0.00 | 28.90 | 19.18 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105309E+10 | 14731.16 | 14-JAN-05:11 | 2.20 | 1.37 | 0.00 | 0.00 | 01-JAN-00:10 | 2.20 | 1.37 |
February | 0.194204E+10 | 14439.56 | 18-FEB-05:01 | -1.2 | -2.4 | 0.00 | 0.00 | 01-FEB-00:10 | -1.2 | -2.4 |
March | 0.345901E+10 | 13236.48 | 01-MAR-05:01 | 0.00 | -1.6 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | -1.6 |
April | 0.411762E+10 | 12005.27 | 11-APR-04:11 | 5.20 | 4.35 | 0.00 | 0.00 | 01-APR-00:10 | 5.20 | 4.35 |
May | 0.559615E+10 | 9392.46 | 18-MAY-05:02 | 5.60 | 5.28 | 0.00 | 0.00 | 01-MAY-00:10 | 5.60 | 5.28 |
June | 0.659858E+10 | 9448.86 | 24-JUN-05:06 | 12.80 | 10.37 | 0.00 | 0.00 | 01-JUN-00:10 | 12.80 | 10.37 |
July | 0.740698E+10 | 8958.15 | 29-JUL-05:06 | 13.90 | 12.58 | 0.00 | 0.00 | 01-JUL-00:10 | 13.90 | 12.58 |
August | 0.839123E+10 | 9343.58 | 11-AUG-05:07 | 13.30 | 12.27 | 0.00 | 0.00 | 01-AUG-00:10 | 13.30 | 12.27 |
September | 0.635817E+10 | 9704.73 | 14-SEP-05:10 | 12.62 | 12.25 | 0.00 | 0.00 | 01-SEP-00:10 | 12.62 | 12.25 |
October | 0.423569E+10 | 10793.08 | 31-OCT-04:11 | 7.57 | 7.02 | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 | 7.02 |
November | 0.247340E+10 | 13544.11 | 24-NOV-05:11 | 2.60 | 1.97 | 0.00 | 0.00 | 01-NOV-00:10 | 2.60 | 1.97 |
December | 0.164806E+10 | 14907.89 | 26-DEC-04:01 | -1.0 | -1.0 | 0.00 | 0.00 | 01-DEC-00:10 | -1.0 | -1.0 |
Annual Sum or Average | 0.532800E+11 | 0.00 | ||||||||
Minimum of Months | 0.105309E+10 | 8958.15 | -1.2 | -2.4 | 0.00 | 0.00 | -1.2 | -2.4 | ||
Maximum of Months | 0.839123E+10 | 14907.89 | 13.90 | 12.58 | 0.00 | 0.00 | 13.90 | 12.58 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35491836.33 | 1788.38 | 11-JAN-14:30 | 14.40 | 10.49 | 0.00 | 0.00 | 01-JAN-00:10 | 14.40 | 10.49 |
February | 0.682243E+09 | 8303.44 | 27-FEB-15:00 | 20.00 | 12.17 | 0.00 | 0.00 | 01-FEB-00:10 | 20.00 | 12.17 |
March | 0.308964E+10 | 14260.78 | 14-MAR-14:32 | 15.93 | 10.38 | 0.00 | 0.00 | 01-MAR-00:10 | 15.93 | 10.38 |
April | 0.706619E+10 | 28829.30 | 27-APR-14:05 | 26.28 | 16.91 | 0.00 | 0.00 | 01-APR-00:10 | 26.28 | 16.91 |
May | 0.115170E+11 | 30185.69 | 04-MAY-14:05 | 23.98 | 15.25 | 0.00 | 0.00 | 01-MAY-00:10 | 23.98 | 15.25 |
June | 0.140520E+11 | 30429.41 | 28-JUN-14:05 | 25.18 | 15.64 | 0.00 | 0.00 | 01-JUN-00:10 | 25.18 | 15.64 |
July | 0.172648E+11 | 32619.70 | 24-JUL-13:50 | 29.22 | 18.16 | 0.00 | 0.00 | 01-JUL-00:10 | 29.22 | 18.16 |
August | 0.163730E+11 | 33746.29 | 10-AUG-14:30 | 29.80 | 19.03 | 0.00 | 0.00 | 01-AUG-00:10 | 29.80 | 19.03 |
September | 0.907351E+10 | 25062.82 | 14-SEP-14:20 | 23.90 | 17.07 | 0.00 | 0.00 | 01-SEP-00:10 | 23.90 | 17.07 |
October | 0.311047E+10 | 17102.69 | 04-OCT-14:20 | 21.30 | 11.44 | 0.00 | 0.00 | 01-OCT-00:10 | 21.30 | 11.44 |
November | 0.483204E+09 | 9355.50 | 04-NOV-13:50 | 21.02 | 15.96 | 0.00 | 0.00 | 01-NOV-00:10 | 21.02 | 15.96 |
December | 26587830.18 | 1849.54 | 05-DEC-13:02 | 10.60 | 6.22 | 0.00 | 0.00 | 01-DEC-00:10 | 10.60 | 6.22 |
Annual Sum or Average | 0.827741E+11 | 0.00 | ||||||||
Minimum of Months | 26587830.18 | 1788.38 | 10.60 | 6.22 | 0.00 | 0.00 | 10.60 | 6.22 | ||
Maximum of Months | 0.172648E+11 | 33746.29 | 29.80 | 19.03 | 0.00 | 0.00 | 29.80 | 19.03 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258774E+10 | 2114.23 | 05-JAN-16:03 | 5.73 | 4.38 | 95229991.95 | 126.82 | 13-JAN-10:09 | 3.40 | 2.26 |
February | 0.715751E+10 | 4210.71 | 07-FEB-16:43 | 7.30 | 3.84 | 86396528.92 | 126.82 | 24-FEB-14:09 | 12.88 | 11.55 |
March | 0.135749E+11 | 6743.36 | 31-MAR-24:00 | 8.00 | 7.45 | 0.103236E+09 | 126.82 | 10-MAR-10:00 | 8.00 | 7.45 |
April | 0.184037E+11 | 8362.71 | 26-APR-18:00 | 22.80 | 13.49 | 91605247.19 | 126.83 | 28-APR-13:00 | 18.30 | 12.88 |
May | 0.418628E+10 | 3394.89 | 31-MAY-23:52 | 13.00 | 10.11 | 99233665.63 | 126.83 | 31-MAY-13:00 | 13.00 | 10.11 |
June | 0.909494E+10 | 5250.09 | 30-JUN-23:52 | 15.50 | 12.58 | 98957634.27 | 126.82 | 21-JUN-09:30 | 15.50 | 12.58 |
July | 0.147749E+11 | 7272.59 | 31-JUL-24:00 | 17.40 | 14.08 | 91880996.91 | 126.82 | 24-JUL-13:00 | 17.40 | 14.08 |
August | 0.198338E+11 | 8647.60 | 06-AUG-18:32 | 22.47 | 15.07 | 0.103239E+09 | 126.83 | 30-AUG-09:09 | 19.33 | 17.24 |
September | 0.418960E+10 | 3146.13 | 30-SEP-23:55 | 14.30 | 12.32 | 91606716.65 | 126.83 | 14-SEP-13:09 | 14.30 | 12.32 |
October | 0.872246E+10 | 4739.14 | 31-OCT-23:53 | 9.10 | 7.85 | 95230102.72 | 126.82 | 26-OCT-09:39 | 9.10 | 7.85 |
November | 0.129704E+11 | 5861.43 | 10-NOV-15:51 | 8.90 | 6.48 | 94300300.44 | 126.82 | 01-NOV-13:50 | 8.90 | 6.48 |
December | 0.181677E+11 | 7881.73 | 05-DEC-15:55 | 6.10 | 4.53 | 91880888.77 | 126.82 | 28-DEC-14:00 | 11.10 | 9.78 |
Annual Sum or Average | 0.133664E+12 | 0.114280E+10 | ||||||||
Minimum of Months | 0.258774E+10 | 2114.23 | 5.73 | 3.84 | 86396528.92 | 126.82 | 3.40 | 2.26 | ||
Maximum of Months | 0.198338E+11 | 8647.60 | 22.80 | 15.07 | 0.103239E+09 | 126.83 | 19.33 | 17.24 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.962439E+09 | 1771.38 | 05-JAN-16:20 | 5.37 | 4.14 | 95180242.50 | 126.82 | 02-JAN-10:39 | 5.37 | 4.14 |
February | 0.559534E+10 | 3973.62 | 08-FEB-16:51 | 6.70 | 3.26 | 86396531.50 | 126.82 | 24-FEB-14:09 | 12.88 | 11.55 |
March | 0.120411E+11 | 6055.53 | 31-MAR-23:25 | 8.15 | 7.59 | 0.103236E+09 | 126.82 | 10-MAR-10:00 | 8.15 | 7.59 |
April | 0.169415E+11 | 8060.56 | 26-APR-18:00 | 22.80 | 13.49 | 91605256.18 | 126.83 | 28-APR-13:00 | 18.30 | 12.88 |
May | 0.333897E+10 | 3136.91 | 31-MAY-23:22 | 13.50 | 10.66 | 99233666.51 | 126.83 | 31-MAY-13:00 | 13.50 | 10.66 |
June | 0.826749E+10 | 4915.80 | 30-JUN-23:52 | 15.50 | 12.58 | 98957651.66 | 126.82 | 21-JUN-09:30 | 15.50 | 12.58 |
July | 0.137598E+11 | 6949.16 | 31-JUL-23:40 | 17.87 | 14.34 | 91881027.60 | 126.82 | 31-JUL-09:09 | 17.87 | 14.34 |
August | 0.185989E+11 | 8260.90 | 10-AUG-18:40 | 30.17 | 18.81 | 0.103239E+09 | 126.83 | 25-AUG-09:00 | 23.10 | 17.35 |
September | 0.335060E+10 | 2766.23 | 30-SEP-23:21 | 14.15 | 12.18 | 91606704.94 | 126.83 | 13-SEP-13:00 | 14.15 | 12.18 |
October | 0.742299E+10 | 4456.83 | 04-OCT-16:50 | 20.68 | 11.37 | 95230108.77 | 126.82 | 26-OCT-09:39 | 10.77 | 10.10 |
November | 0.111607E+11 | 5491.15 | 10-NOV-16:01 | 8.53 | 6.27 | 94300306.59 | 126.82 | 03-NOV-13:00 | 8.53 | 6.27 |
December | 0.158269E+11 | 7342.42 | 05-DEC-15:55 | 6.10 | 4.53 | 91880887.59 | 126.82 | 28-DEC-14:00 | 11.10 | 9.78 |
Annual Sum or Average | 0.117267E+12 | 0.114275E+10 | ||||||||
Minimum of Months | 0.962439E+09 | 1771.38 | 5.37 | 3.26 | 86396531.50 | 126.82 | 5.37 | 4.14 | ||
Maximum of Months | 0.185989E+11 | 8260.90 | 30.17 | 18.81 | 0.103239E+09 | 126.83 | 23.10 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.425019E+09 | 1585.24 | 05-JAN-16:20 | 5.37 | 4.14 | 94839361.26 | 126.98 | 18-JAN-10:09 | 3.98 | 3.51 |
February | 0.383190E+10 | 3818.48 | 27-FEB-16:11 | 19.23 | 12.34 | 86396580.92 | 126.82 | 24-FEB-14:09 | 19.23 | 12.34 |
March | 0.103836E+11 | 5973.99 | 02-MAR-16:51 | 12.80 | 8.57 | 0.103236E+09 | 126.82 | 10-MAR-10:00 | 13.30 | 11.77 |
April | 0.158343E+11 | 8184.92 | 26-APR-18:00 | 22.80 | 13.49 | 91605236.75 | 126.83 | 28-APR-13:00 | 18.30 | 12.88 |
May | 0.256445E+10 | 2944.29 | 31-MAY-23:02 | 13.83 | 11.03 | 99236456.70 | 126.83 | 31-MAY-13:00 | 13.83 | 11.03 |
June | 0.782897E+10 | 4721.76 | 30-JUN-23:12 | 15.77 | 13.04 | 98957657.79 | 126.82 | 21-JUN-09:30 | 15.77 | 13.04 |
July | 0.134421E+11 | 6855.21 | 31-JUL-23:20 | 18.33 | 14.60 | 91881068.73 | 126.82 | 31-JUL-09:09 | 18.33 | 14.60 |
August | 0.182405E+11 | 8413.84 | 10-AUG-18:30 | 30.30 | 18.97 | 0.103239E+09 | 126.83 | 30-AUG-13:09 | 23.50 | 18.10 |
September | 0.248757E+10 | 2634.63 | 08-SEP-17:40 | 21.10 | 14.32 | 91606762.32 | 126.83 | 13-SEP-13:00 | 22.80 | 17.40 |
October | 0.585263E+10 | 4502.48 | 04-OCT-16:49 | 20.68 | 11.37 | 95230115.82 | 126.82 | 26-OCT-09:39 | 10.77 | 10.10 |
November | 0.916072E+10 | 5318.28 | 10-NOV-16:01 | 8.53 | 6.27 | 94300315.36 | 126.82 | 01-NOV-13:39 | 8.53 | 6.27 |
December | 0.134844E+11 | 7126.51 | 05-DEC-15:55 | 6.10 | 4.53 | 91880877.51 | 126.82 | 29-DEC-14:00 | 10.60 | 8.76 |
Annual Sum or Average | 0.103536E+12 | 0.114241E+10 | ||||||||
Minimum of Months | 0.425019E+09 | 1585.24 | 5.37 | 4.14 | 86396580.92 | 126.82 | 3.98 | 3.51 | ||
Maximum of Months | 0.182405E+11 | 8413.84 | 30.30 | 18.97 | 0.103239E+09 | 126.98 | 23.50 | 18.10 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234244E+12 | 95536.04 | 10-JAN-05:11 | 5.40 | 3.34 | 0.207238E+10 | 2779.93 | 06-JAN-10:09 | 5.40 | 3.34 |
February | 0.435369E+12 | 497513.27 | 28-FEB-03:22 | 11.40 | 10.15 | 0.159725E+10 | 2746.43 | 22-FEB-14:00 | 11.40 | 10.15 |
March | 0.729219E+12 | 520962.05 | 24-MAR-15:52 | 8.90 | 2.71 | 0.187630E+10 | 2652.37 | 31-MAR-13:09 | 8.98 | 7.53 |
April | 0.950539E+12 | 500331.48 | 26-APR-21:04 | 15.13 | 10.76 | 0.153645E+10 | 2857.47 | 26-APR-14:39 | 15.13 | 10.76 |
May | 0.238205E+12 | 457020.49 | 31-MAY-23:58 | 13.00 | 10.11 | 0.215229E+10 | 2788.82 | 15-MAY-13:00 | 13.00 | 10.11 |
June | 0.470934E+12 | 502560.93 | 30-JUN-23:53 | 15.50 | 12.58 | 0.197914E+10 | 2796.53 | 09-JUN-09:39 | 15.50 | 12.58 |
July | 0.733874E+12 | 512503.56 | 03-JUL-10:10 | 14.68 | 10.44 | 0.184366E+10 | 2827.34 | 18-JUL-13:00 | 22.20 | 13.04 |
August | 0.981098E+12 | 484508.43 | 02-AUG-16:43 | 16.45 | 13.50 | 0.212040E+10 | 2814.90 | 09-AUG-09:09 | 22.97 | 13.49 |
September | 0.234074E+12 | 457715.06 | 30-SEP-23:46 | 14.25 | 12.27 | 0.198319E+10 | 2749.28 | 05-SEP-13:00 | 14.25 | 12.27 |
October | 0.487600E+12 | 513664.42 | 31-OCT-23:12 | 8.70 | 7.69 | 0.184679E+10 | 2822.04 | 04-OCT-13:00 | 8.70 | 7.69 |
November | 0.709471E+12 | 513659.03 | 02-NOV-13:32 | 14.40 | 11.44 | 0.169608E+10 | 2539.42 | 22-NOV-08:20 | 2.97 | 2.54 |
December | 0.983632E+12 | 500031.29 | 18-DEC-02:02 | 3.40 | 2.72 | 0.155609E+10 | 2751.73 | 26-DEC-10:09 | 0.02 | 0.01 |
Annual Sum or Average | 0.718826E+13 | 0.222600E+11 | ||||||||
Minimum of Months | 0.234074E+12 | 95536.04 | 3.40 | 2.71 | 0.153645E+10 | 2539.42 | 0.02 | 0.01 | ||
Maximum of Months | 0.983632E+12 | 520962.05 | 16.45 | 13.50 | 0.215229E+10 | 2857.47 | 22.97 | 13.49 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 62359859.98 | 3251.27 | 24-JAN-06:45 | 5.92 |
February | 77178560.42 | 2998.10 | 25-FEB-06:11 | 11.10 |
March | 80215076.77 | 2691.17 | 17-MAR-05:04 | 6.10 |
April | 75935804.95 | 6102.52 | 01-APR-16:02 | 27.12 |
May | 57415560.98 | 3008.00 | 18-MAY-05:45 | 5.60 |
June | 74481884.85 | 2539.03 | 15-JUN-05:03 | 8.98 |
July | 57826384.70 | 4377.09 | 22-JUL-16:01 | 25.92 |
August | 32101793.91 | 3113.62 | 12-AUG-16:01 | 25.02 |
September | 41350775.50 | 2834.69 | 28-SEP-05:05 | 8.30 |
October | 76598710.91 | 2665.38 | 18-OCT-05:55 | 9.40 |
November | 65232587.82 | 2586.90 | 13-NOV-06:06 | 1.70 |
December | 68192914.67 | 2809.71 | 26-DEC-06:04 | -0.8 |
Annual Sum or Average | 0.768890E+09 | |||
Minimum of Months | 32101793.91 | 2539.03 | -0.8 | |
Maximum of Months | 80215076.77 | 6102.52 | 27.12 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:03 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.323983E+09 | 40947.46 | 02-JAN-05:11 | 6.10 |
February | 10635158.84 | 33418.08 | 21-FEB-06:01 | 1.70 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:03 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9.22 |
December | 2808512.92 | 32765.98 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.337427E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.323983E+09 | 40947.46 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363593E+10 | 92166.70 | 17-JAN-04:51 | 1.70 |
February | 0.196298E+10 | 89774.50 | 21-FEB-04:51 | 1.70 |
March | 0.735868E+09 | 78278.82 | 06-MAR-05:11 | 6.70 |
April | 89579911.76 | 69200.54 | 18-APR-05:01 | 3.30 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.352761E+09 | 64003.77 | 16-OCT-04:11 | 7.20 |
November | 0.147506E+10 | 85757.62 | 13-NOV-04:11 | 1.50 |
December | 0.261116E+10 | 96881.43 | 26-DEC-04:11 | -0.9 |
Annual Sum or Average | 0.108633E+11 | |||
Minimum of Months | 0.00 | 0.00 | -0.9 | |
Maximum of Months | 0.363593E+10 | 96881.43 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115827E+09 | 11041.50 | 06-JAN-06:01 | -1.8 |
February | 53571222.09 | 10988.16 | 18-FEB-06:01 | -1.8 |
March | 498534.99 | 3273.86 | 25-MAR-05:01 | 2.20 |
April | 0.00 | 0.00 | 01-APR-00:03 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.35 |
November | 118440.01 | 835.86 | 22-NOV-06:03 | 3.22 |
December | 9550854.01 | 10601.49 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.179566E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.8 | |
Maximum of Months | 0.115827E+09 | 11041.50 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127879E+09 | 9829.07 | 05-JAN-06:01 | -0.8 |
February | 67812945.66 | 9588.85 | 18-FEB-06:01 | -1.8 |
March | 9151846.25 | 6738.39 | 01-MAR-06:01 | -0.1 |
April | 2508382.60 | 5848.91 | 18-APR-05:01 | 3.30 |
May | 274801.33 | 2082.93 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 85362.87 | 569.09 | 27-SEP-05:05 | 7.38 |
October | 805520.87 | 3863.25 | 27-OCT-05:01 | 8.98 |
November | 4592209.78 | 6061.93 | 24-NOV-06:01 | 2.02 |
December | 45035623.80 | 9153.18 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.258146E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.8 | |
Maximum of Months | 0.127879E+09 | 9829.07 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.382009E+09 | 16825.88 | 17-JAN-05:01 | 1.60 |
February | 0.197903E+09 | 16210.57 | 18-FEB-05:41 | -1.6 |
March | 37179516.19 | 11628.86 | 01-MAR-06:01 | -0.1 |
April | 6026010.24 | 10454.94 | 18-APR-05:01 | 3.30 |
May | 1360159.31 | 7986.21 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 242422.25 | 1115.82 | 28-SEP-05:05 | 8.30 |
October | 3118554.47 | 8632.73 | 16-OCT-05:01 | 7.12 |
November | 49863234.52 | 12402.72 | 24-NOV-06:03 | 2.02 |
December | 0.169543E+09 | 16826.58 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.847245E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.6 | |
Maximum of Months | 0.382009E+09 | 16826.58 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12302578.95 | 7128.29 | 09-JAN-06:01 | -1.5 |
February | 4524460.15 | 7274.06 | 18-FEB-06:01 | -1.8 |
March | 17159.27 | 285.99 | 01-MAR-06:04 | -0.1 |
April | 0.00 | 0.00 | 01-APR-00:03 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 17062.36 | 284.37 | 31-OCT-05:04 | 8.58 |
November | 57305.16 | 463.76 | 24-NOV-06:04 | 2.02 |
December | 546431.47 | 6375.03 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 17464997.36 | |||
Minimum of Months | 0.00 | 0.00 | -1.8 | |
Maximum of Months | 12302578.95 | 7274.06 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227096E+10 | 19085.55 | 17-JAN-04:51 | 1.70 |
February | 0.119954E+10 | 21189.66 | 19-FEB-07:41 | -5.0 |
March | 0.474091E+09 | 16394.82 | 01-MAR-05:41 | 0.00 |
April | 0.160738E+09 | 14892.24 | 19-APR-05:02 | 1.78 |
May | 11765023.49 | 13476.02 | 18-MAY-05:02 | 5.60 |
June | 29030.01 | 435.45 | 15-JUN-05:03 | 8.98 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 174640.77 | 1093.69 | 27-SEP-05:03 | 7.38 |
October | 0.147081E+09 | 13763.68 | 31-OCT-04:11 | 7.57 |
November | 0.600270E+09 | 17163.23 | 13-NOV-05:01 | 1.20 |
December | 0.148944E+10 | 19785.11 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.635408E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.227096E+10 | 21189.66 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144898E+10 | 17475.19 | 17-JAN-04:51 | 1.70 |
February | 0.725736E+09 | 18820.94 | 19-FEB-07:01 | -5.0 |
March | 0.289189E+09 | 14163.63 | 01-MAR-05:41 | 0.00 |
April | 95044505.05 | 12944.88 | 11-APR-04:11 | 5.20 |
May | 12006332.25 | 10448.19 | 18-MAY-05:02 | 5.60 |
June | 767078.97 | 6444.64 | 14-JUN-05:01 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 |
August | 59122.05 | 288.85 | 21-AUG-05:04 | 11.20 |
September | 2171463.15 | 2645.78 | 05-SEP-05:02 | 10.68 |
October | 0.108544E+09 | 11827.38 | 31-OCT-04:11 | 7.57 |
November | 0.415633E+09 | 15217.59 | 13-NOV-05:01 | 1.20 |
December | 0.999306E+09 | 18136.03 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.409744E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.144898E+10 | 18820.94 | 15.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172887E+10 | 24769.28 | 17-JAN-04:51 | 1.70 |
February | 0.791557E+09 | 23604.72 | 21-FEB-04:51 | 1.70 |
March | 0.352742E+09 | 20259.10 | 01-MAR-05:41 | 0.00 |
April | 0.149096E+09 | 18688.50 | 18-APR-04:11 | 2.97 |
May | 20311795.79 | 16141.77 | 18-MAY-05:02 | 5.60 |
June | 1063067.22 | 6749.08 | 27-JUN-05:01 | 13.40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 475453.30 | 1590.60 | 27-SEP-05:03 | 7.38 |
October | 0.106583E+09 | 16661.03 | 31-OCT-04:11 | 7.57 |
November | 0.485461E+09 | 20867.89 | 13-NOV-05:01 | 1.20 |
December | 0.120193E+10 | 25558.32 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.483809E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.172887E+10 | 25558.32 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105574E+10 | 16526.57 | 17-JAN-04:51 | 1.70 |
February | 0.506797E+09 | 15860.10 | 21-FEB-04:51 | 1.70 |
March | 0.212853E+09 | 13661.92 | 01-MAR-05:41 | 0.00 |
April | 70650254.39 | 12356.93 | 18-APR-04:11 | 2.97 |
May | 10656048.37 | 10342.03 | 18-MAY-05:02 | 5.60 |
June | 508506.97 | 4470.46 | 27-JUN-05:01 | 13.40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 179072.19 | 700.15 | 18-SEP-05:08 | 12.20 |
October | 60268927.50 | 11178.43 | 31-OCT-04:11 | 7.57 |
November | 0.270795E+09 | 13969.20 | 13-NOV-05:01 | 1.20 |
December | 0.664209E+09 | 17127.94 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.285266E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.105574E+10 | 17127.94 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.612646E+10 | 27578.68 | 16-JAN-05:53 | -2.2 |
February | 0.428811E+10 | 29670.93 | 19-FEB-07:01 | -5.0 |
March | 0.216852E+10 | 23890.44 | 06-MAR-01:31 | 6.10 |
April | 0.103565E+10 | 22255.92 | 11-APR-04:11 | 5.20 |
May | 0.315613E+09 | 20181.57 | 18-MAY-04:11 | 6.33 |
June | 40506636.56 | 17158.87 | 14-JUN-04:11 | 10.00 |
July | 227793.01 | 2535.20 | 05-JUL-05:01 | 11.78 |
August | 1957437.74 | 5782.76 | 05-AUG-05:02 | 12.68 |
September | 0.142714E+09 | 17141.14 | 27-SEP-04:12 | 7.20 |
October | 0.116469E+10 | 21614.94 | 30-OCT-04:11 | 7.20 |
November | 0.280374E+10 | 25605.08 | 13-NOV-04:11 | 1.50 |
December | 0.514035E+10 | 27421.47 | 26-DEC-04:11 | -0.9 |
Annual Sum or Average | 0.232286E+11 | |||
Minimum of Months | 227793.01 | 2535.20 | -5.0 | |
Maximum of Months | 0.612646E+10 | 29670.93 | 12.68 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.382761E+10 | 20206.59 | 16-JAN-03:13 | -1.9 |
February | 0.249131E+10 | 24311.08 | 19-FEB-07:01 | -5.0 |
March | 0.124602E+10 | 17848.99 | 06-MAR-05:11 | 6.70 |
April | 0.543202E+09 | 17386.17 | 11-APR-04:11 | 5.20 |
May | 0.203251E+09 | 15567.97 | 18-MAY-04:11 | 6.33 |
June | 30573398.17 | 13080.38 | 14-JUN-04:11 | 10.00 |
July | 365693.14 | 3059.82 | 05-JUL-05:01 | 11.78 |
August | 2452956.42 | 4922.93 | 05-AUG-05:02 | 12.68 |
September | 89171178.10 | 12887.98 | 27-SEP-04:12 | 7.20 |
October | 0.700236E+09 | 16727.56 | 16-OCT-04:11 | 7.20 |
November | 0.178519E+10 | 20148.08 | 13-NOV-04:11 | 1.50 |
December | 0.322841E+10 | 21590.38 | 26-DEC-04:11 | -0.9 |
Annual Sum or Average | 0.141478E+11 | |||
Minimum of Months | 365693.14 | 3059.82 | -5.0 | |
Maximum of Months | 0.382761E+10 | 24311.08 | 12.68 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.478830E+10 | 30585.24 | 14-JAN-05:11 | 2.20 |
February | 0.296559E+10 | 36893.81 | 19-FEB-07:01 | -5.0 |
March | 0.174428E+10 | 27252.86 | 06-MAR-05:11 | 6.70 |
April | 0.928835E+09 | 26240.23 | 18-APR-04:11 | 2.97 |
May | 0.346501E+09 | 23663.56 | 18-MAY-04:11 | 6.33 |
June | 60345370.76 | 19630.44 | 14-JUN-04:11 | 10.00 |
July | 436712.73 | 1537.45 | 13-JUL-05:03 | 12.80 |
August | 1709785.92 | 4433.77 | 05-AUG-05:02 | 12.68 |
September | 0.108197E+09 | 18792.74 | 27-SEP-04:12 | 7.20 |
October | 0.901422E+09 | 24939.96 | 16-OCT-04:11 | 7.20 |
November | 0.224878E+10 | 30384.74 | 13-NOV-04:11 | 1.50 |
December | 0.412656E+10 | 32865.69 | 26-DEC-04:11 | -0.9 |
Annual Sum or Average | 0.182210E+11 | |||
Minimum of Months | 436712.73 | 1537.45 | -5.0 | |
Maximum of Months | 0.478830E+10 | 36893.81 | 12.80 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286622E+10 | 21081.85 | 14-JAN-05:11 | 2.20 |
February | 0.175808E+10 | 25436.69 | 19-FEB-07:01 | -5.0 |
March | 0.928140E+09 | 18903.54 | 06-MAR-05:11 | 6.70 |
April | 0.453150E+09 | 17495.25 | 18-APR-04:11 | 2.97 |
May | 0.150185E+09 | 15918.57 | 18-MAY-04:11 | 6.33 |
June | 16393172.33 | 12390.66 | 15-JUN-05:01 | 8.98 |
July | 36046.48 | 506.62 | 18-JUL-05:03 | 12.80 |
August | 382368.42 | 552.54 | 19-AUG-05:05 | 12.18 |
September | 39088538.67 | 9012.61 | 27-SEP-05:03 | 7.38 |
October | 0.484185E+09 | 16138.50 | 16-OCT-04:11 | 7.20 |
November | 0.113916E+10 | 20587.69 | 13-NOV-04:11 | 1.50 |
December | 0.220436E+10 | 22562.24 | 26-DEC-04:11 | -0.9 |
Annual Sum or Average | 0.100394E+11 | |||
Minimum of Months | 36046.48 | 506.62 | -5.0 | |
Maximum of Months | 0.286622E+10 | 25436.69 | 12.80 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 37070286.22 | 9382.70 | 11-JAN-06:03 | 9.90 |
February | 29068634.50 | 11040.13 | 12-FEB-13:31 | 6.50 |
March | 29181666.19 | 9766.19 | 08-MAR-06:01 | 10.18 |
April | 64063919.48 | 9865.93 | 10-APR-04:12 | 9.63 |
May | 61412295.42 | 9607.78 | 14-MAY-16:22 | 23.05 |
June | 46564930.57 | 8909.36 | 26-JUN-04:11 | 12.80 |
July | 77693200.70 | 11824.78 | 30-JUL-15:12 | 27.40 |
August | 83529994.35 | 13020.08 | 13-AUG-14:51 | 28.10 |
September | 51934551.60 | 13696.83 | 10-SEP-15:21 | 22.50 |
October | 35899855.24 | 9861.51 | 08-OCT-13:12 | 18.53 |
November | 33561994.81 | 11276.49 | 29-NOV-06:01 | 8.22 |
December | 35848545.70 | 12826.84 | 28-DEC-06:01 | 9.40 |
Annual Sum or Average | 0.585830E+09 | |||
Minimum of Months | 29068634.50 | 8909.36 | 6.50 | |
Maximum of Months | 83529994.35 | 13696.83 | 28.10 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207643E+10 | 19344.13 | 02-JAN-06:12 | 6.10 |
February | 0.603562E+09 | 14541.19 | 12-FEB-13:51 | 6.70 |
March | 88851988.84 | 6517.56 | 09-MAR-06:01 | 10.68 |
April | 27626810.98 | 7189.47 | 02-APR-10:56 | 15.60 |
May | 49938832.55 | 12195.92 | 14-MAY-15:31 | 23.30 |
June | 35863396.90 | 8659.72 | 18-JUN-16:52 | 17.20 |
July | 55277529.54 | 11924.88 | 30-JUL-15:32 | 27.60 |
August | 45047290.33 | 14773.96 | 06-AUG-15:21 | 23.75 |
September | 38859409.05 | 12956.44 | 10-SEP-15:42 | 22.30 |
October | 53952499.66 | 11542.89 | 08-OCT-13:32 | 19.27 |
November | 0.159580E+09 | 10463.42 | 11-NOV-13:41 | 7.62 |
December | 0.595274E+09 | 4973.55 | 03-DEC-11:58 | 11.70 |
Annual Sum or Average | 0.383026E+10 | |||
Minimum of Months | 27626810.98 | 4973.55 | 6.10 | |
Maximum of Months | 0.207643E+10 | 19344.13 | 27.60 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138494E+11 | 39354.19 | 09-JAN-05:13 | -0.2 |
February | 0.914485E+10 | 37422.71 | 21-FEB-05:11 | 1.70 |
March | 0.557881E+10 | 29825.39 | 06-MAR-05:41 | 6.70 |
April | 0.292677E+10 | 21911.51 | 18-APR-05:01 | 3.30 |
May | 0.151199E+10 | 15592.14 | 11-MAY-05:01 | 5.10 |
June | 0.592761E+09 | 31048.78 | 22-JUN-05:01 | 11.20 |
July | 0.257189E+09 | 29492.28 | 25-JUL-05:01 | 13.90 |
August | 0.400670E+09 | 28205.83 | 01-AUG-05:01 | 11.30 |
September | 0.131589E+10 | 19743.93 | 01-SEP-05:01 | 15.50 |
October | 0.365829E+10 | 23396.65 | 16-OCT-05:01 | 7.12 |
November | 0.742293E+10 | 33830.72 | 13-NOV-05:11 | 1.30 |
December | 0.119891E+11 | 34421.00 | 11-DEC-05:22 | 4.55 |
Annual Sum or Average | 0.586486E+11 | |||
Minimum of Months | 0.257189E+09 | 15592.14 | -0.2 | |
Maximum of Months | 0.138494E+11 | 39354.19 | 15.50 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:03 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.478283E+09 | 1309.25 | 01-JAN-17:05 | 6.10 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:03 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.478283E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.478283E+09 | 1309.25 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159578E+10 | 1404.22 | 08-JAN-18:50 | 3.30 |
February | 85084124.73 | 1091.89 | 12-FEB-03:26 | 1.40 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:03 | 7.93 |
May | 49290014.24 | 911.32 | 02-MAY-05:10 | 10.10 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 17494036.66 | 845.76 | 27-SEP-02:13 | 8.30 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.174764E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.40 | |
Maximum of Months | 0.159578E+10 | 1404.22 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 |
February | 0.515099E+09 | 30736.39 | 25-FEB-19:21 | 10.30 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:03 | 7.93 |
May | 1918565.39 | 31976.09 | 31-MAY-23:51 | 13.00 |
June | 0.324203E+09 | 38997.90 | 26-JUN-00:51 | 13.30 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 1061871.76 | 17086.66 | 30-SEP-23:41 | 14.25 |
October | 0.260597E+09 | 39800.62 | 23-OCT-00:41 | 10.50 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.110288E+10 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.515099E+09 | 39800.62 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.278508E+11 | 29144.79 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.252627E+11 | 29144.79 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.300191E+11 | 29144.79 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.268132E+11 | 29144.79 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.289349E+11 | 29144.79 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.287951E+11 | 29144.79 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.269531E+11 | 29144.79 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.300191E+11 | 29144.79 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.268132E+11 | 29144.79 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.278508E+11 | 29144.79 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.275243E+11 | 29144.79 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.269531E+11 | 29144.79 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.333789E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.252627E+11 | 29144.79 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.300191E+11 | 29144.79 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.785272E+10 | 8217.58 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.712300E+10 | 8217.58 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.846411E+10 | 8217.58 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.756018E+10 | 8217.58 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.815842E+10 | 8217.58 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.811897E+10 | 8217.58 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.759962E+10 | 8217.58 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.846411E+10 | 8217.58 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.756018E+10 | 8217.58 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.785272E+10 | 8217.58 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.776069E+10 | 8217.58 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.759962E+10 | 8217.58 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.941143E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.712300E+10 | 8217.58 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.846411E+10 | 8217.58 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.289349E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.287951E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.275243E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.333789E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761658E+09 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672980E+09 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648288E+09 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1088026.80 | 0.616329E+09 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38424.66 | 0.471821E+09 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 386330.27 | 0.392502E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6085872.29 | 0.332230E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8586328.54 | 0.271308E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38305.65 | 0.220840E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518721E+09 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604281E+09 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656279E+09 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16223288.20 | 0.616724E+10 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220840E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8586328.54 | 0.761658E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496500E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442078E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416484E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1130473.70 | 0.393117E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55226.87 | 0.300598E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 347525.69 | 0.248726E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5547973.33 | 0.204530E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6937171.22 | 0.163144E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47568.38 | 0.139424E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330338E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384550E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422223E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14065939.18 | 0.394171E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139424E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6937171.22 | 0.496500E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733649E+09 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674005E+09 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630928E+09 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1142693.33 | 0.595205E+09 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38651.57 | 0.453149E+09 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 419805.27 | 0.372426E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5242146.53 | 0.313642E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8500872.56 | 0.254839E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38295.97 | 0.216288E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506282E+09 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575089E+09 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632588E+09 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15382465.22 | 0.595809E+10 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216288E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8500872.56 | 0.733649E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523524E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471669E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457127E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 362564.97 | 0.445042E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30098.15 | 0.330937E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 257595.45 | 0.276681E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2880215.00 | 0.249811E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5517396.68 | 0.208202E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25530.99 | 0.157173E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361398E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422765E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469014E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9073401.23 | 0.437334E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157173E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5517396.68 | 0.523524E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153654E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137315E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133315E+10 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3644112.56 | 0.126504E+10 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80437.92 | 0.100296E+10 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 795734.95 | 0.834573E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20284340.61 | 0.697340E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23301425.88 | 0.564535E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84346.84 | 0.457739E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104977E+10 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121080E+10 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131721E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48190398.75 | 0.126428E+11 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457739E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23301425.88 | 0.153654E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102306E+10 |
February | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932767E+09 |
March | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.899576E+09 |
April | 0.688021E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2467017.11 | 0.858167E+09 |
May | 0.744847E+09 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83179.81 | 0.668265E+09 |
June | 0.742030E+09 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 730816.60 | 0.556686E+09 |
July | 0.690839E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12509850.04 | 0.457906E+09 |
August | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15322221.55 | 0.374045E+09 |
September | 0.688021E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86094.65 | 0.306575E+09 |
October | 0.715730E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708575E+09 |
November | 0.708685E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.807235E+09 |
December | 0.690839E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877785E+09 |
Annual Sum or Average | 0.858171E+10 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31199179.76 | 0.847064E+10 |
Minimum of Months | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306575E+09 |
Maximum of Months | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15322221.55 | 0.102306E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159092E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149591E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140232E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2368473.40 | 0.131614E+10 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65160.83 | 0.101677E+10 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 915728.25 | 0.824959E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11757836.60 | 0.693648E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19366585.24 | 0.570020E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67085.99 | 0.487618E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113079E+10 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125305E+10 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137139E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34540870.29 | 0.131535E+11 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487618E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19366585.24 | 0.159092E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104691E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.956245E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921396E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 992630.15 | 0.881149E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 132693.04 | 0.702900E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 590465.37 | 0.571292E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8804940.75 | 0.505785E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14582620.24 | 0.404413E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44810.03 | 0.326315E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727218E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826108E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904580E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25148159.57 | 0.877431E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326315E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14582620.24 | 0.104691E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178854E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157923E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148797E+10 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4775265.11 | 0.142182E+10 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 163984.23 | 0.113930E+10 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 867322.27 | 0.962142E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24569470.67 | 0.806350E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29179993.90 | 0.640400E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 153948.19 | 0.504212E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113904E+10 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133482E+10 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146794E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59709984.37 | 0.142718E+11 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504212E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29179993.90 | 0.178854E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118871E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105997E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100085E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3043670.84 | 0.971237E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44230.99 | 0.774756E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 678742.31 | 0.660033E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12153543.26 | 0.544246E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17322023.11 | 0.438149E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59477.19 | 0.346689E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.773772E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.889713E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.978405E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33301687.70 | 0.962652E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346689E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17322023.11 | 0.118871E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182039E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168877E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158157E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2818658.48 | 0.150253E+10 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53234.98 | 0.118110E+10 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 939013.51 | 0.975051E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12824398.71 | 0.822610E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22981886.76 | 0.666159E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57835.69 | 0.557140E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125869E+10 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138899E+10 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152788E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39675028.12 | 0.149709E+11 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557140E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22981886.76 | 0.182039E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121938E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110327E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105647E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1154559.97 | 0.102258E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 118634.47 | 0.826501E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 612065.73 | 0.680273E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10136442.28 | 0.604735E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17555725.61 | 0.477695E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38629.88 | 0.378027E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826850E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934413E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102351E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29616057.93 | 0.101537E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378027E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17555725.61 | 0.121938E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.785272E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.712300E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.846411E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.756018E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.815842E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.811897E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.759962E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.846411E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.756018E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.785272E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.776069E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.759962E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.941143E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.712300E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.846411E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170049E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150082E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143013E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1554182.44 | 0.134016E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4747.69 | 0.102452E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303568.80 | 0.844096E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9048030.19 | 0.710669E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13324127.16 | 0.590860E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2838.95 | 0.484974E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114584E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133407E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146572E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24237495.23 | 0.135723E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484974E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13324127.16 | 0.170049E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276218E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252122E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244236E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3695312.32 | 0.228237E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8199.49 | 0.178193E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563974.54 | 0.146168E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20770929.99 | 0.121606E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26281387.49 | 0.100937E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4797.74 | 0.837190E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195115E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223369E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243794E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51324601.56 | 0.229371E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837190E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26281387.49 | 0.276218E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260883E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238152E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230586E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1906038.90 | 0.225575E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184465E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16975.02 | 0.155957E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3602468.65 | 0.130398E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13089463.99 | 0.102576E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812136E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179946E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203001E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219571E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18614946.57 | 0.221232E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812136E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13089463.99 | 0.260883E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 29144.79 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 29144.79 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 29144.79 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 29144.79 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 29144.79 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 29144.79 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 29144.79 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 29144.79 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 29144.79 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 29144.79 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 29144.79 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 29144.79 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1238.60 | 28-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1160.76 | 16-FEB-03:51 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1086.47 | 28-MAR-23:51 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.09 | 01-APR-17:01 | 1114.71 | 07-APR-23:53 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 | 05-MAY-16:00 | 796.52 | 17-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.91 | 28-JUN-16:00 | 1082.51 | 13-JUN-02:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.47 | 23-JUL-15:50 | 554.48 | 02-JUL-03:51 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.10 | 13-AUG-15:00 | 756.79 | 11-AUG-03:52 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 14-SEP-17:00 | 533.56 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 975.24 | 31-OCT-21:10 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1180.86 | 29-NOV-22:51 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 952.16 | 17-DEC-20:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.56 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 164.47 | 1238.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 803.38 | 28-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 768.68 | 19-FEB-10:00 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 705.21 | 28-MAR-23:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.13 | 01-APR-17:10 | 723.29 | 07-APR-23:53 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 14-MAY-15:50 | 514.20 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 | 28-JUN-16:00 | 697.96 | 13-JUN-02:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.79 | 23-JUL-15:50 | 352.16 | 02-JUL-03:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.00 | 13-AUG-17:40 | 480.36 | 11-AUG-03:52 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.19 | 14-SEP-17:00 | 336.45 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 628.55 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 764.22 | 29-NOV-22:51 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 613.96 | 17-DEC-20:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.45 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 163.79 | 803.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1179.02 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1240.87 | 19-FEB-12:00 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1069.78 | 28-MAR-23:51 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.35 | 01-APR-17:10 | 1088.36 | 07-APR-23:53 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 | 05-MAY-16:00 | 769.06 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.91 | 28-JUN-16:00 | 1028.76 | 13-JUN-02:51 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.43 | 23-JUL-15:50 | 530.75 | 02-JUL-03:51 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.39 | 13-AUG-17:40 | 747.82 | 11-AUG-03:52 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 14-SEP-17:00 | 500.84 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 936.87 | 31-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1134.87 | 29-NOV-22:51 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 891.76 | 22-DEC-22:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.84 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 178.43 | 1240.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 858.87 | 28-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 804.78 | 16-FEB-03:51 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 781.38 | 28-MAR-23:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.63 | 01-APR-16:00 | 800.89 | 07-APR-23:53 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 | 05-MAY-16:00 | 556.67 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 | 28-JUN-16:00 | 760.37 | 13-JUN-02:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.52 | 23-JUL-13:10 | 418.99 | 02-JUL-03:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.23 | 13-AUG-12:20 | 590.59 | 11-AUG-03:52 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.63 | 14-SEP-17:00 | 369.79 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 661.00 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 827.22 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 694.12 | 17-DEC-20:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.79 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 90.52 | 858.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2518.24 | 12-JAN-24:00 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2359.68 | 16-FEB-22:01 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2258.04 | 29-MAR-04:52 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 449.95 | 01-APR-17:01 | 2344.61 | 10-APR-21:03 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.00 | 14-MAY-15:00 | 1705.09 | 18-MAY-04:57 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.60 | 28-JUN-16:00 | 2180.18 | 13-JUN-02:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 540.03 | 23-JUL-16:10 | 1103.84 | 02-JUL-03:51 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.74 | 13-AUG-15:10 | 1616.21 | 11-AUG-03:52 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.39 | 14-SEP-17:00 | 1096.66 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2171.98 | 31-OCT-21:01 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2417.17 | 29-NOV-22:51 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1947.90 | 22-DEC-22:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1096.66 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 540.03 | 2518.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1664.61 | 12-JAN-24:00 |
February | 1239.33 | 01-FEB-08:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1572.54 | 16-FEB-22:01 |
March | 1239.33 | 01-MAR-08:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1508.71 | 29-MAR-04:52 |
April | 1239.33 | 03-APR-07:10 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 316.28 | 01-APR-17:01 | 1560.33 | 10-APR-21:03 |
May | 1239.33 | 01-MAY-07:10 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.69 | 14-MAY-17:00 | 1136.74 | 18-MAY-04:57 |
June | 1239.33 | 01-JUN-07:10 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.07 | 28-JUN-16:00 | 1419.75 | 13-JUN-02:51 |
July | 1239.33 | 03-JUL-07:10 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.74 | 23-JUL-16:10 | 821.62 | 02-JUL-09:59 |
August | 1239.33 | 01-AUG-07:10 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.94 | 13-AUG-17:50 | 1070.11 | 11-AUG-03:52 |
September | 1239.33 | 01-SEP-07:10 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.58 | 14-SEP-17:00 | 704.95 | 18-SEP-23:00 |
October | 1239.33 | 02-OCT-07:10 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 1446.75 | 31-OCT-21:01 |
November | 1239.33 | 01-NOV-07:10 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1599.77 | 29-NOV-22:51 |
December | 1239.33 | 01-DEC-08:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1290.95 | 22-DEC-22:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 704.95 | |||||
Maximum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 352.74 | 1664.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2511.21 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2800.90 | 19-FEB-12:30 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2268.39 | 28-MAR-23:51 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 294.60 | 01-APR-17:30 | 2345.07 | 10-APR-21:03 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 | 05-MAY-16:00 | 1705.19 | 18-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.60 | 28-JUN-16:00 | 2116.55 | 13-JUN-02:51 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 409.56 | 23-JUL-16:10 | 1114.32 | 02-JUL-03:51 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.45 | 13-AUG-17:50 | 1635.89 | 11-AUG-03:52 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.39 | 14-SEP-17:00 | 1067.81 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2170.28 | 31-OCT-21:01 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2409.08 | 29-NOV-22:51 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1962.04 | 22-DEC-22:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1067.81 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 409.56 | 2800.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1680.96 | 12-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1573.28 | 16-FEB-22:01 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1505.60 | 29-MAR-04:52 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.32 | 01-APR-16:00 | 1570.14 | 10-APR-21:03 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.86 | 06-MAY-13:00 | 1175.12 | 27-MAY-17:10 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.06 | 28-JUN-16:00 | 1416.93 | 13-JUN-02:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.48 | 23-JUL-13:30 | 779.24 | 02-JUL-03:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.96 | 13-AUG-12:30 | 1151.44 | 11-AUG-03:52 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 | 14-SEP-17:00 | 712.50 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 1447.79 | 31-OCT-21:01 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1623.75 | 29-NOV-22:51 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1315.69 | 22-DEC-22:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 712.50 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 322.48 | 1680.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3093.27 | 12-JAN-22:03 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2933.26 | 16-FEB-22:01 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2822.60 | 29-MAR-04:53 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 587.17 | 01-APR-17:01 | 2896.17 | 10-APR-21:03 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.26 | 14-MAY-15:00 | 2132.79 | 18-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.13 | 28-JUN-16:00 | 2367.86 | 13-JUN-02:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 649.61 | 23-JUL-15:50 | 1188.20 | 27-JUL-23:51 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 365.86 | 13-AUG-14:50 | 1862.80 | 11-AUG-03:52 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.25 | 10-SEP-15:00 | 1183.55 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2700.56 | 31-OCT-21:01 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2934.97 | 29-NOV-22:01 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2398.09 | 22-DEC-22:02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1183.55 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 649.61 | 3093.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2059.82 | 12-JAN-22:03 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1954.72 | 16-FEB-22:01 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1881.50 | 29-MAR-04:58 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 384.16 | 01-APR-17:01 | 1928.52 | 10-APR-21:03 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 | 05-MAY-16:00 | 1421.77 | 18-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.42 | 28-JUN-16:00 | 1553.87 | 13-JUN-02:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 375.93 | 23-JUL-15:50 | 907.47 | 02-JUL-10:00 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.72 | 13-AUG-17:30 | 1239.05 | 11-AUG-03:52 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.99 | 14-SEP-17:00 | 777.28 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 1799.09 | 31-OCT-21:01 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1955.71 | 29-NOV-22:01 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1597.28 | 22-DEC-22:02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 777.28 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 384.16 | 2059.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3092.49 | 12-JAN-22:03 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2972.12 | 19-FEB-12:20 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2822.30 | 29-MAR-04:57 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.80 | 01-APR-17:50 | 2899.37 | 10-APR-21:03 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 | 05-MAY-16:00 | 2132.76 | 18-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.13 | 28-JUN-16:00 | 2309.34 | 13-JUN-02:51 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 440.83 | 23-JUL-15:50 | 1276.96 | 04-JUL-15:10 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.33 | 13-AUG-17:30 | 1890.82 | 11-AUG-03:52 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 | 14-SEP-17:00 | 1186.46 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2699.62 | 31-OCT-21:01 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2934.51 | 29-NOV-22:01 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2400.18 | 22-DEC-22:02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1186.46 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 440.83 | 3092.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2065.21 | 12-JAN-22:03 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1956.68 | 16-FEB-22:01 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1881.54 | 29-MAR-04:55 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.26 | 01-APR-16:00 | 1943.18 | 10-APR-21:03 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.34 | 06-MAY-13:00 | 1461.29 | 27-MAY-17:20 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.42 | 28-JUN-16:00 | 1566.28 | 13-JUN-02:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.97 | 23-JUL-13:10 | 926.02 | 04-JUL-16:30 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.78 | 13-AUG-12:50 | 1337.25 | 11-AUG-03:52 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.28 | 14-SEP-17:00 | 810.73 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 1802.14 | 31-OCT-21:01 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1958.23 | 29-NOV-22:01 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1602.41 | 22-DEC-22:02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 810.73 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 369.97 | 2065.21 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 8217.58 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 8217.58 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 8217.58 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 8217.58 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 8217.58 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 8217.58 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 8217.58 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 8217.58 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 8217.58 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 8217.58 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 8217.58 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 8217.58 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 8217.58 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 8217.58 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2810.51 | 28-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2604.49 | 16-FEB-03:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2428.14 | 28-MAR-23:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.61 | 01-APR-17:01 | 2467.91 | 07-APR-23:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 | 05-MAY-16:00 | 1801.23 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.56 | 28-JUN-15:00 | 2428.08 | 13-JUN-02:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.38 | 23-JUL-16:00 | 1225.27 | 02-JUL-03:51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.16 | 13-AUG-15:00 | 1638.50 | 11-AUG-03:52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.54 | 14-SEP-17:00 | 1145.51 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2159.18 | 31-OCT-21:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2645.65 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2145.83 | 17-DEC-20:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1145.51 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.38 | 2810.51 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4785.43 | 28-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 4418.25 | 16-FEB-03:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 4122.41 | 28-MAR-23:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.25 | 01-APR-17:01 | 4265.00 | 07-APR-23:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 05-MAY-16:00 | 3127.27 | 18-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.96 | 28-JUN-15:00 | 4154.51 | 13-JUN-02:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 586.88 | 23-JUL-13:52 | 2079.02 | 02-JUL-03:51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.03 | 13-AUG-14:51 | 2884.59 | 11-AUG-03:52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.40 | 14-SEP-17:00 | 1956.51 | 30-SEP-04:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 3699.45 | 31-OCT-21:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 4466.55 | 29-NOV-22:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3594.29 | 22-DEC-22:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1956.51 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 586.88 | 4785.43 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4424.01 | 12-JAN-22:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 4042.91 | 16-FEB-22:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 3891.41 | 29-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.63 | 01-APR-17:01 | 4230.31 | 10-APR-21:03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2951.75 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.84 | 28-JUN-17:00 | 3672.26 | 13-JUN-02:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.78 | 24-JUL-14:30 | 1982.51 | 02-JUL-12:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.38 | 08-AUG-17:00 | 2775.29 | 11-AUG-03:52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1817.04 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 3896.44 | 31-OCT-21:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 4232.83 | 29-NOV-22:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3570.27 | 22-DEC-22:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1817.04 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.63 | 4424.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 132504.95 | 30-JAN-05:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 134631.62 | 27-FEB-05:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 133280.16 | 01-MAR-05:01 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 119369.07 | 03-APR-04:12 | 0.00 | 19429.86 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 131264.55 | 24-MAY-05:01 | 17952.25 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 137756.67 | 19-JUN-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 127180.70 | 01-JUL-04:11 | 0.00 | 16191.55 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 121924.59 | 21-AUG-04:12 | 0.00 | 19429.86 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 133746.53 | 05-SEP-04:12 | 0.00 | 19429.86 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 140101.37 | 02-OCT-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 125450.88 | 06-NOV-05:11 | 0.00 | 22668.17 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 120196.61 | 11-DEC-05:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 119369.07 | 0.00 | 16191.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 140101.37 | 17952.25 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 101562.11 | 26-JAN-06:01 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 107403.87 | 27-FEB-06:01 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 107592.00 | 10-MAR-05:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 113627.04 | 28-APR-04:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 114342.93 | 01-MAY-04:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 117800.06 | 12-JUN-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 120435.66 | 17-JUL-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 117608.19 | 14-AUG-04:11 | 0.00 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 116701.18 | 05-SEP-04:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 119017.04 | 10-OCT-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 114240.12 | 06-NOV-05:11 | 0.00 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 106656.44 | 28-DEC-06:01 | 12897.91 | 23265.84 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 101562.11 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 120435.66 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 32038.50 | 12-JAN-16:55 | 30632.53 | 52348.14 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 92359.30 | 28-FEB-06:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 94509.30 | 03-MAR-06:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 99494.69 | 28-APR-04:12 | 0.00 | 17449.38 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 101978.73 | 16-MAY-05:01 | 12897.91 | 23265.84 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 103820.03 | 29-JUN-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 104319.64 | 25-JUL-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 104553.11 | 11-AUG-04:12 | 0.00 | 17449.38 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 102202.76 | 09-SEP-05:01 | 12897.91 | 23265.84 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 101591.25 | 05-OCT-05:01 | 12897.91 | 23265.84 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 94319.12 | 03-NOV-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 34566.63 | 06-DEC-16:14 | 76581.32 | 130870.35 | 86032.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 32038.50 | 0.00 | 17449.38 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 104553.11 | 76581.32 | 130870.35 | 86032.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 22288.38 | 11-JAN-17:00 | 30632.53 | 52348.14 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30663.85 | 28-FEB-16:53 | 45948.79 | 78522.21 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 35848.38 | 15-MAR-15:53 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 54179.11 | 27-APR-15:30 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 55273.43 | 04-MAY-15:30 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 102686.84 | 12-JUN-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 102631.05 | 28-JUL-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 102693.26 | 11-AUG-05:01 | 11285.67 | 20357.61 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 72028.25 | 01-SEP-05:01 | 11285.67 | 20357.61 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44588.97 | 04-OCT-16:00 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 29412.71 | 02-NOV-15:52 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22075.67 | 29-DEC-17:00 | 61265.06 | 104696.28 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 22075.67 | 11285.67 | 20357.61 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 102693.26 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3582.23 | 11-JAN-06:03 | 809.73 | 1460.63 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.39 |
February | 5140.86 | 27-FEB-15:37 | 5769.33 | 9859.25 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.43 |
March | 5886.17 | 10-MAR-14:22 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.63 |
April | 9440.15 | 27-APR-15:20 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 22.77 | 0.00 |
May | 9256.84 | 05-MAY-13:30 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 |
June | 9923.85 | 21-JUN-15:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 4.13 | 0.00 |
July | 11905.15 | 24-JUL-15:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 35.14 | 0.00 |
August | 11371.77 | 25-AUG-14:00 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 15.29 | 0.00 |
September | 8552.60 | 12-SEP-14:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2.18 | 0.00 |
October | 6288.92 | 04-OCT-15:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.06 |
November | 4494.87 | 02-NOV-13:52 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.39 |
December | 3810.12 | 29-DEC-06:02 | 1012.16 | 1825.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3582.23 | 809.73 | 1460.63 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11905.15 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 35.14 | 103.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4852.84 | 11-JAN-06:03 | 521.82 | 941.28 | 2475.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.88 |
February | 5589.40 | 12-FEB-12:11 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.29 |
March | 9856.03 | 14-MAR-09:13 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.87 |
April | 14023.54 | 27-APR-08:50 | 2478.65 | 4235.78 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.57 |
May | 14816.79 | 14-MAY-09:02 | 260.91 | 470.64 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.44 |
June | 31269.95 | 25-JUN-09:31 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.28 |
July | 32748.20 | 30-JUL-07:51 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.09 |
August | 32671.38 | 13-AUG-08:51 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.67 |
September | 30119.94 | 10-SEP-09:22 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.28 |
October | 11581.45 | 09-OCT-08:29 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.00 |
November | 5673.92 | 06-NOV-05:11 | 0.00 | 1647.25 | 3363.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.30 |
December | 5089.53 | 29-DEC-06:02 | 652.28 | 1176.61 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4852.84 | 0.00 | 470.64 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.57 | |
Maximum of Months | 32748.20 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19510.37 | 20-JAN-13:08 | 7692.61 | 13145.95 | 8642.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 |
February | 42360.63 | 12-FEB-13:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 911.09 |
March | 23204.07 | 14-MAR-12:52 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41264.78 | 02-APR-13:22 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.13 |
May | 25293.81 | 07-MAY-12:42 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.61 |
June | 20018.27 | 18-JUN-13:12 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.15 |
July | 33453.73 | 30-JUL-13:12 | 506.09 | 912.91 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.75 |
August | 45480.09 | 13-AUG-12:51 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.80 |
September | 46690.66 | 10-SEP-12:41 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.12 |
October | 45707.53 | 08-OCT-13:11 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.60 |
November | 26963.60 | 11-NOV-12:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.77 |
December | 20308.85 | 05-DEC-12:25 | 4233.34 | 13145.95 | 7682.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19510.37 | 506.09 | 912.91 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46690.66 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 911.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6545.47 | 11-JAN-06:03 | 521.82 | 941.28 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.32 |
February | 12514.26 | 26-FEB-15:03 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.11 |
March | 15732.35 | 18-MAR-17:07 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.00 |
April | 35586.27 | 23-APR-17:41 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.51 |
May | 39904.48 | 07-MAY-16:01 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.74 |
June | 39147.33 | 18-JUN-16:31 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.47 |
July | 37821.16 | 23-JUL-17:01 | 0.00 | 823.62 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.74 |
August | 37310.20 | 06-AUG-16:51 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.31 |
September | 38437.42 | 10-SEP-16:01 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.71 |
October | 21089.90 | 01-OCT-15:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.85 |
November | 10031.26 | 05-NOV-14:38 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.58 |
December | 8138.04 | 10-DEC-15:21 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6545.47 | 0.00 | 823.62 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.74 | |
Maximum of Months | 39904.48 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3345.59 | 11-JAN-15:02 | 7692.44 | 13145.66 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.58 |
February | 3981.31 | 28-FEB-15:04 | 9615.55 | 16432.08 | 10802.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.41 |
March | 4268.16 | 10-MAR-15:02 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.38 |
April | 8146.75 | 27-APR-15:50 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 51.57 | 0.00 |
May | 8557.30 | 05-MAY-15:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 6.94 | 0.00 |
June | 9250.68 | 21-JUN-15:40 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 10.26 | 0.00 |
July | 10665.36 | 24-JUL-15:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 81.05 | 0.00 |
August | 10240.99 | 25-AUG-14:00 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 34.71 | 0.00 |
September | 7549.64 | 12-SEP-15:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 3.73 | 0.00 |
October | 4916.38 | 04-OCT-13:15 | 12064.74 | 19718.49 | 12963.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.87 |
November | 4031.87 | 04-NOV-05:01 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.70 |
December | 3151.84 | 29-DEC-15:02 | 7692.44 | 13145.66 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3151.84 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10665.36 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 81.05 | 274.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4958.92 | 20-JAN-11:02 | 4957.30 | 8471.56 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.35 |
February | 12606.38 | 03-FEB-11:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.55 |
March | 18734.21 | 14-MAR-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.48 |
April | 19019.18 | 26-APR-10:01 | 8675.28 | 14825.24 | 9746.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.58 |
May | 30885.30 | 14-MAY-09:32 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.49 |
June | 32783.61 | 25-JUN-09:51 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.10 |
July | 33768.51 | 23-JUL-08:61 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.41 |
August | 32565.83 | 06-AUG-08:41 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.10 |
September | 20666.42 | 10-SEP-09:42 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.18 |
October | 19143.11 | 03-OCT-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.65 |
November | 12774.16 | 02-NOV-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.19 |
December | 5338.71 | 05-DEC-11:01 | 8675.28 | 14825.24 | 9746.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4958.92 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.55 | |
Maximum of Months | 33768.51 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20469.03 | 20-JAN-13:13 | 5769.46 | 9859.46 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.53 |
February | 44774.46 | 12-FEB-13:51 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2106.32 |
March | 25221.86 | 14-MAR-13:23 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.34 |
April | 24732.56 | 27-APR-13:20 | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 26.59 | 0.00 |
May | 41396.07 | 14-MAY-12:52 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 646.81 |
June | 26972.92 | 11-JUN-12:42 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.54 |
July | 35827.36 | 30-JUL-13:32 | 506.09 | 912.91 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.28 |
August | 43107.22 | 06-AUG-12:42 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.72 |
September | 43878.04 | 10-SEP-14:22 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.20 |
October | 47942.54 | 08-OCT-13:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.90 |
November | 36253.64 | 11-NOV-13:41 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 738.30 |
December | 19910.19 | 05-DEC-12:25 | 4233.34 | 13145.95 | 7682.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19910.19 | 506.09 | 912.91 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47942.54 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 26.59 | 2106.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4800.09 | 05-JAN-15:45 | 2478.65 | 4235.78 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.24 |
February | 9488.65 | 27-FEB-15:25 | 2478.65 | 4235.78 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.99 |
March | 12703.17 | 14-MAR-16:00 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.92 |
April | 19262.16 | 01-APR-17:06 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.49 |
May | 36953.23 | 14-MAY-16:11 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.63 |
June | 33477.24 | 25-JUN-16:41 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.73 |
July | 34743.45 | 30-JUL-17:31 | 0.00 | 823.62 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.01 |
August | 37741.82 | 06-AUG-16:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.33 |
September | 30583.09 | 10-SEP-16:22 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.15 |
October | 13925.29 | 04-OCT-16:00 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.13 |
November | 6253.20 | 04-NOV-15:30 | 130.46 | 352.98 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.41 |
December | 5076.71 | 05-DEC-15:30 | 3717.98 | 6353.67 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4800.09 | 0.00 | 352.98 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.41 | |
Maximum of Months | 37741.82 | 3717.98 | 6353.67 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3804.59 | 11-JAN-15:00 | 10053.95 | 16432.08 | 10802.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.75 |
February | 4679.18 | 27-FEB-16:08 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.26 |
March | 5077.08 | 10-MAR-14:50 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.44 |
April | 9171.75 | 27-APR-15:20 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 61.78 | 0.00 |
May | 9120.66 | 31-MAY-15:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.41 |
June | 10325.43 | 21-JUN-15:40 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 10.73 | 0.00 |
July | 12268.85 | 24-JUL-15:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 98.94 | 0.00 |
August | 11378.12 | 09-AUG-15:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 116.49 | 0.00 |
September | 8113.65 | 12-SEP-15:10 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2.90 | 0.00 |
October | 5573.51 | 04-OCT-13:30 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.63 |
November | 4452.74 | 02-NOV-14:31 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.84 |
December | 3455.94 | 30-DEC-17:02 | 506.08 | 912.89 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3455.94 | 506.08 | 912.89 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12268.85 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 116.49 | 321.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3526.20 | 20-JAN-06:04 | 913.19 | 1647.25 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.03 |
February | 4115.94 | 27-FEB-15:40 | 3717.98 | 6353.67 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.58 |
March | 6919.42 | 14-MAR-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.83 |
April | 13496.42 | 27-APR-09:25 | 2591.66 | 4235.78 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.09 |
May | 27196.75 | 14-MAY-09:32 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549.56 |
June | 31644.64 | 25-JUN-09:41 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.15 |
July | 31607.79 | 30-JUL-07:51 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.04 |
August | 33351.20 | 13-AUG-09:21 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.89 |
September | 27470.13 | 10-SEP-09:32 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.45 |
October | 8737.09 | 04-OCT-09:32 | 7774.98 | 12707.35 | 8354.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.09 |
November | 4049.10 | 02-NOV-10:31 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.96 |
December | 3651.66 | 12-DEC-06:04 | 913.19 | 1647.25 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3526.20 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.03 | |
Maximum of Months | 33351.20 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18517.27 | 20-JAN-13:25 | 3846.30 | 6572.98 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.20 |
February | 21902.16 | 27-FEB-14:22 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.61 |
March | 25080.56 | 14-MAR-13:23 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.81 |
April | 36274.97 | 02-APR-13:12 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 816.90 |
May | 37201.83 | 14-MAY-12:52 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 818.15 |
June | 29612.49 | 11-JUN-12:42 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.00 |
July | 37229.59 | 30-JUL-13:52 | 506.09 | 912.91 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.91 |
August | 51036.71 | 13-AUG-14:01 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.42 |
September | 53285.94 | 10-SEP-14:11 | 910.97 | 1643.24 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.07 |
October | 48049.44 | 08-OCT-13:41 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 600.41 |
November | 20885.40 | 04-NOV-13:25 | 423.33 | 1095.50 | 1680.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17062.18 | 05-DEC-12:25 | 4233.34 | 13145.95 | 7682.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17062.18 | 423.33 | 912.91 | 1680.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53285.94 | 20108.34 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 818.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4812.12 | 05-JAN-15:40 | 2478.65 | 4235.78 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.60 |
February | 9170.30 | 27-FEB-15:30 | 2478.65 | 4235.78 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.70 |
March | 13066.07 | 14-MAR-16:00 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
April | 20198.68 | 01-APR-17:06 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.68 |
May | 39954.85 | 07-MAY-17:31 | 0.00 | 1058.95 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.18 |
June | 36692.24 | 18-JUN-18:01 | 0.00 | 823.62 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 690.49 |
July | 37468.95 | 23-JUL-17:01 | 0.00 | 823.62 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.02 |
August | 41221.18 | 06-AUG-17:11 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.80 |
September | 38112.65 | 10-SEP-16:51 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.86 |
October | 14093.85 | 04-OCT-16:00 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.49 |
November | 6152.58 | 04-NOV-15:40 | 130.46 | 352.98 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.05 |
December | 5046.97 | 05-DEC-15:30 | 3717.98 | 6353.67 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4812.12 | 0.00 | 352.98 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.05 | |
Maximum of Months | 41221.18 | 3717.98 | 6353.67 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 690.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8822.43 | 14-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.06 |
February | 8606.09 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.76 |
March | 7703.22 | 22-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9163.17 | 29-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.67 |
May | 9372.30 | 02-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.95 |
June | 8967.76 | 13-JUN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.89 |
July | 9651.44 | 31-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.66 | 0.00 |
August | 10899.97 | 12-AUG-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.52 |
September | 10405.25 | 14-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9084.67 | 10-OCT-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.22 |
November | 8629.25 | 06-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.62 |
December | 9231.28 | 26-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7703.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10899.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.66 | 264.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14731.16 | 14-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2796.45 |
February | 14439.56 | 18-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 947.86 |
March | 13236.48 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1543.17 |
April | 12005.27 | 11-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3536.81 |
May | 9392.46 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 726.63 |
June | 9448.86 | 24-JUN-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.00 |
July | 8958.15 | 29-JUL-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.29 |
August | 9343.58 | 11-AUG-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.49 |
September | 9704.73 | 14-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10793.08 | 31-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1746.58 |
November | 13544.11 | 24-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1391.05 |
December | 14907.89 | 26-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1523.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8958.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14907.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3536.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1788.38 | 11-JAN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.51 |
February | 8303.44 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.14 |
March | 14260.78 | 14-MAR-14:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.04 |
April | 28829.30 | 27-APR-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.87 |
May | 30185.69 | 04-MAY-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.64 |
June | 30429.41 | 28-JUN-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.92 |
July | 32619.70 | 24-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.61 | 0.00 |
August | 33746.29 | 10-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.21 | 0.00 |
September | 25062.82 | 14-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.07 |
October | 17102.69 | 04-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.10 |
November | 9355.50 | 04-NOV-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1849.54 | 05-DEC-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1788.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33746.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.61 | 577.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2114.23 | 05-JAN-16:03 | 666.42 | 2186.35 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4210.71 | 07-FEB-16:43 | 1554.99 | 5101.49 | 27280.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6743.36 | 31-MAR-24:00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8362.71 | 26-APR-18:00 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3394.89 | 31-MAY-23:52 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5250.09 | 30-JUN-23:52 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7272.59 | 31-JUL-24:00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8647.60 | 06-AUG-18:32 | 0.00 | 323.90 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3146.13 | 30-SEP-23:55 | 0.00 | 80.98 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4739.14 | 31-OCT-23:53 | 0.00 | 242.93 | 35074.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5861.43 | 10-NOV-15:51 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7881.73 | 05-DEC-15:55 | 888.56 | 2915.14 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2114.23 | 0.00 | 40.49 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8647.60 | 2221.41 | 7287.84 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1771.38 | 05-JAN-16:20 | 444.28 | 1457.57 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3973.62 | 08-FEB-16:51 | 2221.41 | 7287.84 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6055.53 | 31-MAR-23:25 | 0.00 | 161.95 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8060.56 | 26-APR-18:00 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3136.91 | 31-MAY-23:22 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4915.80 | 30-JUN-23:52 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6949.16 | 31-JUL-23:40 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8260.90 | 10-AUG-18:40 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2766.23 | 30-SEP-23:21 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4456.83 | 04-OCT-16:50 | 701.50 | 4048.80 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5491.15 | 10-NOV-16:01 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7342.42 | 05-DEC-15:55 | 888.56 | 2915.14 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1771.38 | 0.00 | 40.49 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8260.90 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1585.24 | 05-JAN-16:20 | 444.28 | 1457.57 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3818.48 | 27-FEB-16:11 | 2221.41 | 7287.84 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5973.99 | 02-MAR-16:51 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8184.92 | 26-APR-18:00 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2944.29 | 31-MAY-23:02 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4721.76 | 30-JUN-23:12 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6855.21 | 31-JUL-23:20 | 0.00 | 80.98 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8413.84 | 10-AUG-18:30 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2634.63 | 08-SEP-17:40 | 23.38 | 242.93 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4502.48 | 04-OCT-16:49 | 701.50 | 4048.80 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5318.28 | 10-NOV-16:01 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7126.51 | 05-DEC-15:55 | 888.56 | 2915.14 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1585.24 | 0.00 | 80.98 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8413.84 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 95536.04 | 10-JAN-05:11 | 0.00 | 9130.65 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 497513.27 | 28-FEB-03:22 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 520962.05 | 24-MAR-15:52 | 48086.79 | 82175.84 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 500331.48 | 26-APR-21:04 | 2530.88 | 9130.65 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 457020.49 | 31-MAY-23:58 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 502560.93 | 30-JUN-23:53 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 512503.56 | 03-JUL-10:10 | 48086.79 | 82175.84 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 484508.43 | 02-AUG-16:43 | 15185.30 | 45653.24 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 457715.06 | 30-SEP-23:46 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 513664.42 | 31-OCT-23:12 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 513659.03 | 02-NOV-13:32 | 50279.21 | 82175.84 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 500031.29 | 18-DEC-02:02 | 0.00 | 4565.32 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 95536.04 | 0.00 | 4565.32 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 520962.05 | 50279.21 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.186251E+13 | 1406390.79 | 20-JAN-16:49 | 0.456307E+12 | 1676942.45 | 02-JAN-06:10 |
February | 0.206463E+13 | 1690304.87 | 27-FEB-15:09 | 0.286832E+12 | 1267672.46 | 21-FEB-06:10 |
March | 0.280958E+13 | 1869271.61 | 14-MAR-15:00 | 0.169501E+12 | 852133.13 | 06-MAR-05:19 |
April | 0.300111E+13 | 2243447.26 | 27-APR-15:09 | 0.825759E+11 | 642030.03 | 11-APR-04:19 |
May | 0.192835E+13 | 1793699.30 | 04-MAY-15:30 | 0.413114E+11 | 563010.37 | 18-MAY-05:10 |
June | 0.230850E+13 | 1942178.57 | 28-JUN-15:39 | 0.141804E+11 | 298665.09 | 14-JUN-05:10 |
July | 0.278899E+13 | 2143518.36 | 31-JUL-15:00 | 0.386846E+10 | 81158.63 | 13-JUL-05:40 |
August | 0.331812E+13 | 2346135.99 | 29-AUG-15:09 | 0.602343E+10 | 144905.73 | 03-AUG-05:10 |
September | 0.187122E+13 | 1834916.08 | 14-SEP-15:09 | 0.286524E+11 | 360975.14 | 27-SEP-05:10 |
October | 0.224760E+13 | 1847598.15 | 04-OCT-15:09 | 0.112404E+12 | 619781.40 | 30-OCT-04:19 |
November | 0.262199E+13 | 1750558.52 | 29-NOV-16:40 | 0.232718E+12 | 845097.14 | 13-NOV-05:10 |
December | 0.308916E+13 | 1935323.04 | 13-DEC-16:00 | 0.356647E+12 | 1055807.45 | 26-DEC-06:10 |
Annual Sum or Average | 0.299117E+14 | 0.179102E+13 | ||||
Minimum of Months | 0.186251E+13 | 1406390.79 | 0.386846E+10 | 81158.63 | ||
Maximum of Months | 0.331812E+13 | 2346135.99 | 0.456307E+12 | 1676942.45 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.468149E+12 | 0.109274E+12 | 0.766053E+12 | 0.218140E+12 | 0.165208E+12 | 0.114729E+11 | 0.00 | 0.137426E+11 | 16412.45 | 0.714092E+11 | 0.00 | 0.390641E+11 | 0.00 |
February | 0.424646E+12 | 0.900876E+11 | 0.978954E+12 | 0.199667E+12 | 0.170969E+12 | 0.307254E+11 | 0.00 | 0.630551E+11 | 0.106089E+09 | 0.706877E+11 | 0.00 | 0.357335E+11 | 0.00 |
March | 0.504598E+12 | 0.879344E+11 | 0.141687E+13 | 0.230864E+12 | 0.221047E+12 | 0.910202E+11 | 0.00 | 0.105692E+12 | 0.107343E+09 | 0.109899E+12 | 0.00 | 0.415465E+11 | 0.00 |
April | 0.450709E+12 | 0.732466E+11 | 0.165903E+13 | 0.216144E+12 | 0.245181E+12 | 0.929944E+11 | 0.00 | 0.141833E+12 | 0.197994E+10 | 0.833012E+11 | 0.00 | 0.366919E+11 | 0.00 |
May | 0.486374E+12 | 0.650569E+11 | 0.774844E+12 | 0.224502E+12 | 0.205574E+12 | 0.333985E+11 | 0.00 | 0.703371E+11 | 0.233263E+10 | 0.281739E+11 | 0.00 | 0.377547E+11 | 0.00 |
June | 0.484022E+12 | 0.572516E+11 | 0.106252E+13 | 0.222585E+12 | 0.229224E+12 | 0.547651E+11 | 0.00 | 0.146048E+12 | 0.529522E+10 | 0.107430E+11 | 0.00 | 0.360518E+11 | 0.00 |
July | 0.453060E+12 | 0.617886E+11 | 0.139340E+13 | 0.218061E+12 | 0.268924E+12 | 0.103118E+12 | 0.00 | 0.231037E+12 | 0.148249E+11 | 0.113828E+11 | 0.00 | 0.333893E+11 | 0.00 |
August | 0.504598E+12 | 0.709397E+11 | 0.173200E+13 | 0.230864E+12 | 0.307372E+12 | 0.111528E+12 | 0.00 | 0.298504E+12 | 0.249393E+11 | 0.115342E+10 | 0.00 | 0.362176E+11 | 0.00 |
September | 0.450709E+12 | 0.799369E+11 | 0.740713E+12 | 0.216143E+12 | 0.207034E+12 | 0.424685E+11 | 0.00 | 0.943773E+11 | 0.533762E+10 | 0.118682E+10 | 0.00 | 0.333099E+11 | 0.00 |
October | 0.468149E+12 | 0.948554E+11 | 0.108340E+13 | 0.218140E+12 | 0.201961E+12 | 0.359876E+11 | 0.00 | 0.806779E+11 | 0.440404E+09 | 0.285619E+11 | 0.00 | 0.354212E+11 | 0.00 |
November | 0.462662E+12 | 0.102545E+12 | 0.135889E+13 | 0.209941E+12 | 0.199465E+12 | 0.897029E+11 | 0.00 | 0.958015E+11 | 0.224934E+09 | 0.666654E+11 | 0.00 | 0.360931E+11 | 0.00 |
December | 0.453060E+12 | 0.112081E+12 | 0.170972E+13 | 0.218060E+12 | 0.226097E+12 | 0.917675E+11 | 0.00 | 0.111129E+12 | 5384422.75 | 0.130009E+12 | 0.00 | 0.372273E+11 | 0.00 |
Annual Sum or Average | 0.561074E+13 | 0.100500E+13 | 0.146764E+14 | 0.262311E+13 | 0.264806E+13 | 0.788949E+12 | 0.00 | 0.145223E+13 | 0.555938E+11 | 0.613173E+12 | 0.00 | 0.438501E+12 | 0.00 |
Minimum of Months | 0.424646E+12 | 0.572516E+11 | 0.740713E+12 | 0.199667E+12 | 0.165208E+12 | 0.114729E+11 | 0.00 | 0.137426E+11 | 16412.45 | 0.115342E+10 | 0.00 | 0.333099E+11 | 0.00 |
Maximum of Months | 0.504598E+12 | 0.112081E+12 | 0.173200E+13 | 0.230864E+12 | 0.307372E+12 | 0.111528E+12 | 0.00 | 0.298504E+12 | 0.249393E+11 | 0.130009E+12 | 0.00 | 0.415465E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.456307E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.286832E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.169501E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.825759E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.413114E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.141804E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.386846E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.602343E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.286524E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.112404E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.232718E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.356647E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.179102E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.386846E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.456307E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 489900.85 | 02-JAN-08:09 | 64082.80 | 01-JAN-00:10 | 423497.50 | 02-JAN-08:09 | 235096.12 | 02-JAN-08:20 | 146076.50 | 02-JAN-06:10 | 37885.13 | 19-JAN-07:30 | 0.00 | 01-JAN-00:10 |
February | 489900.85 | 01-FEB-08:09 | 64082.80 | 01-FEB-00:10 | 541788.89 | 01-FEB-08:09 | 235096.12 | 01-FEB-08:20 | 171585.62 | 27-FEB-15:30 | 42099.92 | 27-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 489900.85 | 01-MAR-08:09 | 64082.80 | 01-MAR-00:10 | 660080.29 | 01-MAR-08:09 | 235096.12 | 01-MAR-08:20 | 213077.09 | 14-MAR-15:00 | 40914.26 | 10-MAR-15:09 | 0.00 | 01-MAR-00:10 |
April | 489900.85 | 03-APR-07:10 | 64082.80 | 01-APR-00:10 | 778371.69 | 03-APR-07:10 | 235096.12 | 03-APR-07:19 | 260941.73 | 27-APR-14:30 | 84825.14 | 26-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 489900.85 | 01-MAY-07:10 | 64082.80 | 01-MAY-00:10 | 423497.50 | 01-MAY-07:10 | 235096.12 | 01-MAY-07:19 | 227007.73 | 04-MAY-14:00 | 81942.27 | 04-MAY-13:50 | 0.00 | 01-MAY-00:10 |
June | 489900.85 | 01-JUN-07:10 | 64082.80 | 01-JUN-00:10 | 541788.89 | 01-JUN-07:10 | 235096.12 | 01-JUN-07:19 | 233610.43 | 28-JUN-15:30 | 91145.00 | 20-JUN-14:00 | 0.00 | 01-JUN-00:10 |
July | 489900.85 | 03-JUL-07:10 | 64082.80 | 01-JUL-00:10 | 660080.29 | 03-JUL-07:10 | 235096.12 | 03-JUL-07:19 | 258071.29 | 31-JUL-15:20 | 82961.36 | 19-JUL-16:19 | 0.00 | 01-JUL-00:10 |
August | 489900.85 | 01-AUG-07:10 | 64082.80 | 01-AUG-00:10 | 778371.69 | 01-AUG-07:10 | 235096.12 | 01-AUG-07:19 | 294234.68 | 10-AUG-15:30 | 84448.31 | 21-AUG-13:50 | 0.00 | 01-AUG-00:10 |
September | 489900.85 | 01-SEP-07:10 | 64082.80 | 01-SEP-00:10 | 423497.50 | 01-SEP-07:10 | 235096.12 | 01-SEP-07:19 | 248037.99 | 14-SEP-14:30 | 81310.31 | 11-SEP-15:30 | 0.00 | 01-SEP-00:10 |
October | 489900.85 | 02-OCT-07:10 | 64082.80 | 01-OCT-00:10 | 541788.89 | 02-OCT-07:10 | 235096.12 | 02-OCT-07:19 | 229277.59 | 03-OCT-15:30 | 40984.30 | 08-OCT-13:39 | 0.00 | 01-OCT-00:10 |
November | 489900.85 | 01-NOV-07:10 | 64082.80 | 01-NOV-00:10 | 660080.29 | 01-NOV-07:10 | 235096.12 | 01-NOV-07:19 | 160327.72 | 15-NOV-13:20 | 40854.85 | 02-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 489900.85 | 01-DEC-08:09 | 64082.80 | 01-DEC-00:10 | 778371.69 | 01-DEC-08:09 | 235096.12 | 01-DEC-08:20 | 161878.59 | 05-DEC-13:09 | 40451.84 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 489900.85 | 64082.80 | 423497.50 | 235096.12 | 146076.50 | 37885.13 | 0.00 | |||||||
Maximum of Months | 489900.85 | 64082.80 | 778371.69 | 235096.12 | 294234.68 | 91145.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 43430.32 | 13-JAN-18:19 | 11.40 | 12-JAN-14:50 | 49841.19 | 09-JAN-21:00 | 0.00 | 51963.88 | 31-JAN-12:00 | 0.00 |
February | 176967.75 | 27-FEB-14:00 | 6808.12 | 27-FEB-15:09 | 68194.16 | 11-FEB-20:19 | 0.00 | 52007.19 | 10-FEB-12:20 | 0.00 |
March | 145201.61 | 18-MAR-12:09 | 4635.74 | 10-MAR-13:09 | 100000.00 | 18-MAR-14:09 | 0.00 | 51884.58 | 01-MAR-12:00 | 0.00 |
April | 320142.10 | 27-APR-15:50 | 47672.27 | 27-APR-12:30 | 100000.00 | 01-APR-18:00 | 0.00 | 50774.37 | 03-APR-11:39 | 0.00 |
May | 271507.92 | 04-MAY-14:50 | 47672.27 | 05-MAY-13:50 | 100000.00 | 14-MAY-13:30 | 0.00 | 48767.84 | 01-MAY-11:20 | 0.00 |
June | 302866.25 | 27-JUN-14:09 | 47672.27 | 28-JUN-15:30 | 100000.00 | 08-JUN-14:50 | 0.00 | 46870.50 | 01-JUN-11:50 | 0.00 |
July | 338058.90 | 31-JUL-15:00 | 47672.27 | 07-JUL-12:30 | 100000.00 | 07-JUL-20:49 | 0.00 | 45393.47 | 03-JUL-11:50 | 0.00 |
August | 387764.96 | 29-AUG-14:30 | 47672.27 | 07-AUG-10:50 | 100000.00 | 09-AUG-08:39 | 0.00 | 44767.27 | 31-AUG-11:30 | 0.00 |
September | 292077.84 | 12-SEP-14:09 | 47672.27 | 12-SEP-13:39 | 23737.84 | 28-SEP-16:10 | 0.00 | 45685.60 | 29-SEP-11:50 | 0.00 |
October | 175422.09 | 04-OCT-14:00 | 6443.78 | 04-OCT-14:00 | 100000.00 | 04-OCT-13:20 | 0.00 | 47251.95 | 31-OCT-11:50 | 0.00 |
November | 142016.02 | 04-NOV-12:09 | 7964.41 | 04-NOV-14:09 | 87133.25 | 13-NOV-19:00 | 0.00 | 49236.97 | 30-NOV-12:20 | 0.00 |
December | 95562.48 | 23-DEC-05:00 | 80.35 | 16-DEC-09:50 | 100000.00 | 02-DEC-07:30 | 0.00 | 51162.31 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 43430.32 | 11.40 | 23737.84 | 0.00 | 44767.27 | 0.00 | ||||
Maximum of Months | 387764.96 | 47672.27 | 100000.00 | 0.00 | 52007.19 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1406390.79 | 20-JAN-16:49 | 489900.85 | 423497.50 | 64082.80 | 235096.12 | 112945.89 | 317.02 | 0.00 | 8138.57 | 0.00 |
February | 1690304.87 | 27-FEB-15:09 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 171467.91 | 41733.62 | 0.00 | 161061.11 | 6808.12 |
March | 1869271.61 | 14-MAR-15:00 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 213077.09 | 38580.29 | 0.00 | 115446.54 | 1698.54 |
April | 2243447.26 | 27-APR-15:09 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 255362.86 | 82439.20 | 0.00 | 317421.33 | 47672.27 |
May | 1793699.30 | 04-MAY-15:30 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 224491.90 | 80328.35 | 0.00 | 270519.88 | 32137.09 |
June | 1942178.57 | 28-JUN-15:39 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 233489.93 | 80843.18 | 0.00 | 278294.68 | 47672.27 |
July | 2143518.36 | 31-JUL-15:00 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 256702.41 | 81562.37 | 0.00 | 338058.90 | 47672.27 |
August | 2346135.99 | 29-AUG-15:09 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 292322.66 | 83065.44 | 0.00 | 385835.86 | 47672.27 |
September | 1834916.08 | 14-SEP-15:09 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 246782.16 | 79888.61 | 0.00 | 278681.37 | 47362.64 |
October | 1847598.15 | 04-OCT-15:09 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 225173.69 | 40165.66 | 0.00 | 174537.34 | 6407.73 |
November | 1750558.52 | 29-NOV-16:40 | 489900.85 | 660080.29 | 64082.80 | 235096.12 | 136895.15 | 39037.77 | 0.00 | 42779.57 | 0.00 |
December | 1935323.04 | 13-DEC-16:00 | 489900.85 | 778371.69 | 64082.80 | 235096.12 | 135979.21 | 38866.68 | 0.00 | 57664.64 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1406390.79 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 112945.89 | 317.02 | 0.00 | 8138.57 | 0.00 | |
Maximum of Months | 2346135.99 | 489900.85 | 778371.69 | 64082.80 | 235096.12 | 292322.66 | 83065.44 | 0.00 | 385835.86 | 47672.27 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1676942.45 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1267672.46 | 21-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 852133.13 | 06-MAR-05:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 642030.03 | 11-APR-04:19 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 563010.37 | 18-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 298665.09 | 14-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 81158.63 | 13-JUL-05:40 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 144905.73 | 03-AUG-05:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 360975.14 | 27-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 619781.40 | 30-OCT-04:19 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 845097.14 | 13-NOV-05:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 1055807.45 | 26-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 81158.63 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 1676942.45 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.58 | 0.00 | 25.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.63 | 0.00 | 25.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.73 | 0.00 | 25.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.68 | 0.00 | 25.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.26 | 0.17 | 26.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.01 | 0.00 | 26.01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.68 | 0.00 | 25.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.50 | 25.80 | 0.17 | 25.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.26 | 0.17 | 26.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 19.63 | 1.17 | 19.81 | 0.00 | 19.81 | 0.00 | 19.81 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.83 | 19.63 | 1.17 | 19.81 | 0.00 | 19.81 | 0.00 | 19.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 19.63 | 1.17 | 19.81 | 0.00 | 19.81 | 0.00 | 19.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 18.74 | 0.67 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
February | 1.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
March | 0.33 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
December | 1.67 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 |
Annual Sum or Average | 7.67 | 18.75 | 0.67 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 19.06 | 0.67 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.05 | 0.83 | 28.05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.22 | 1.00 | 28.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.65 | 2.33 | 28.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.52 | 2.33 | 28.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.14 | 1.00 | 28.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.50 | 28.42 | 7.50 | 28.42 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.65 | 2.33 | 28.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.66 | 0.50 | 27.66 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.72 | 0.83 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.77 | 0.67 | 27.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.07 | 2.17 | 28.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.24 | 2.67 | 28.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.60 | 1.50 | 28.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 28.17 | 0.67 | 28.17 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.56 | 0.50 | 27.56 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 19.31 | 0.00 | 19.31 | 9.67 | 27.80 | 9.67 | 27.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.31 | 0.00 | 19.31 | 2.67 | 28.60 | 2.67 | 28.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.85 | 1.50 | 27.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.61 | 2.67 | 28.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.20 | 1.50 | 28.13 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.98 | 3.17 | 28.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.25 | 4.17 | 28.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.26 | 1.50 | 28.23 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 23.67 | 28.46 | 14.50 | 28.43 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.98 | 4.17 | 28.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 |
February | 2.67 | 18.91 | 0.17 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
March | 0.67 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
December | 3.17 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
Annual Sum or Average | 10.67 | 18.97 | 0.17 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 19.33 | 0.17 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.50 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
February | 2.67 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
March | 1.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
April | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.19 | 0.83 | 28.19 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.31 | 1.00 | 28.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.74 | 2.33 | 28.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.56 | 2.33 | 28.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.23 | 0.83 | 28.23 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
December | 6.67 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Annual Sum or Average | 19.00 | 19.11 | 0.00 | 19.11 | 7.33 | 21.72 | 7.33 | 23.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.50 | 19.43 | 0.00 | 19.43 | 2.33 | 28.74 | 2.33 | 28.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
February | 1.67 | 18.98 | 0.00 | 18.98 | 0.83 | 21.93 | 0.83 | 23.40 |
March | 0.17 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.78 | 0.67 | 27.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.77 | 0.83 | 27.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.16 | 1.83 | 28.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.34 | 2.33 | 28.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.94 | 1.50 | 28.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.07 | 1.00 | 28.07 |
November | 0.50 | 19.26 | 0.00 | 19.26 | 0.50 | 23.50 | 0.50 | 24.91 |
December | 2.17 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
Annual Sum or Average | 7.83 | 19.01 | 0.00 | 19.01 | 9.50 | 24.05 | 9.50 | 25.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 19.26 | 0.00 | 19.26 | 2.33 | 28.94 | 2.33 | 28.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
February | 1.67 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
March | 0.33 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.52 | 2.33 | 28.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.21 | 0.67 | 28.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.98 | 1.67 | 29.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.60 | 1.50 | 28.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.27 | 1.00 | 28.23 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
December | 1.67 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
Annual Sum or Average | 7.50 | 19.10 | 0.00 | 19.10 | 14.67 | 25.39 | 7.33 | 26.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 19.41 | 0.00 | 19.41 | 4.33 | 28.98 | 2.33 | 29.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 33.17 | 15.66 | 8.17 | 15.51 | 0.00 | 15.51 | 0.00 | 15.51 |
February | 22.00 | 15.91 | 4.50 | 15.77 | 0.00 | 15.77 | 0.00 | 15.77 |
March | 5.50 | 18.62 | 0.17 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 |
April | 2.83 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
May | 0.33 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.33 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
November | 7.83 | 17.69 | 0.17 | 17.63 | 0.00 | 17.63 | 0.00 | 17.63 |
December | 17.33 | 16.45 | 1.83 | 16.30 | 0.00 | 16.30 | 0.00 | 16.30 |
Annual Sum or Average | 91.33 | 16.43 | 14.83 | 16.22 | 0.00 | 16.22 | 0.00 | 16.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.17 | 19.16 | 8.17 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.83 | 15.62 | 7.50 | 15.49 | 0.00 | 15.49 | 0.00 | 15.49 |
February | 18.33 | 15.89 | 2.00 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 |
March | 5.50 | 18.41 | 0.33 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 |
April | 3.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
May | 0.33 | 19.15 | 0.00 | 19.15 | 0.67 | 24.75 | 0.67 | 25.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.93 | 0.83 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.53 | 2.33 | 28.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.40 | 2.00 | 28.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.59 | 0.50 | 27.59 |
October | 2.67 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
November | 7.50 | 17.50 | 0.17 | 17.45 | 0.00 | 17.45 | 0.00 | 17.45 |
December | 17.00 | 16.34 | 1.83 | 16.20 | 0.00 | 16.20 | 0.00 | 16.20 |
Annual Sum or Average | 87.17 | 16.39 | 11.83 | 16.21 | 6.33 | 16.93 | 6.33 | 17.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.49 | 0.00 | 15.49 |
Maximum of Months | 32.83 | 19.15 | 7.50 | 19.15 | 2.33 | 28.53 | 2.33 | 28.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.50 | 15.90 | 4.50 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 |
February | 12.00 | 16.36 | 1.83 | 16.13 | 0.00 | 16.13 | 0.00 | 16.13 |
March | 4.33 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
April | 2.33 | 19.10 | 0.00 | 19.10 | 0.50 | 20.59 | 0.50 | 21.64 |
May | 0.33 | 19.09 | 0.00 | 19.09 | 0.83 | 25.22 | 0.83 | 26.24 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.17 | 27.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.27 | 2.00 | 28.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.30 | 2.50 | 28.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.76 | 1.50 | 28.76 |
October | 1.67 | 19.09 | 0.00 | 19.09 | 0.33 | 20.53 | 0.33 | 21.56 |
November | 4.33 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
December | 15.00 | 16.58 | 0.83 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
Annual Sum or Average | 65.50 | 16.73 | 7.17 | 16.55 | 7.83 | 17.68 | 7.83 | 18.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.76 | 0.00 | 15.76 |
Maximum of Months | 25.50 | 19.10 | 4.50 | 19.10 | 2.50 | 28.76 | 2.50 | 28.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.33 | 16.03 | 3.50 | 15.86 | 0.00 | 15.86 | 0.00 | 15.86 |
February | 10.83 | 16.58 | 2.17 | 16.27 | 0.00 | 16.27 | 0.00 | 16.27 |
March | 3.83 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
April | 1.67 | 19.15 | 0.00 | 19.15 | 0.17 | 19.90 | 0.17 | 20.52 |
May | 0.33 | 19.21 | 0.00 | 19.21 | 4.00 | 27.89 | 2.17 | 28.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.26 | 0.67 | 28.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 29.11 | 2.00 | 29.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.76 | 1.50 | 28.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.64 | 0.50 | 28.74 |
October | 1.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
November | 3.00 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 |
December | 7.67 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 |
Annual Sum or Average | 49.67 | 16.94 | 5.67 | 16.72 | 14.17 | 19.17 | 7.00 | 20.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.86 | 0.00 | 15.86 |
Maximum of Months | 21.33 | 19.21 | 3.50 | 19.21 | 4.33 | 29.11 | 2.17 | 29.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.84 | 5.50 | 27.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.68 | 2.17 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.00 | 27.80 | 7.67 | 27.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.84 | 5.50 | 27.84 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 336.67 | 23.63 | 27.33 | 23.79 | 12.50 | 23.87 |
February | 191.67 | 23.75 | 36.67 | 24.03 | 0.00 | 24.03 |
March | 126.67 | 23.81 | 65.17 | 24.43 | 0.00 | 24.43 |
April | 98.00 | 23.64 | 105.17 | 24.67 | 0.00 | 24.67 |
May | 85.17 | 23.42 | 153.67 | 24.56 | 0.00 | 24.56 |
June | 3.17 | 23.14 | 204.33 | 24.91 | 0.00 | 24.91 |
July | 0.00 | 0.00 | 391.67 | 24.68 | 0.00 | 24.68 |
August | 0.17 | 24.00 | 440.67 | 24.49 | 0.17 | 24.49 |
September | 17.00 | 23.24 | 284.33 | 24.71 | 0.00 | 24.71 |
October | 13.17 | 23.40 | 123.00 | 25.66 | 0.00 | 25.66 |
November | 32.33 | 23.68 | 156.50 | 25.15 | 0.00 | 25.15 |
December | 157.67 | 23.73 | 93.50 | 24.52 | 0.00 | 24.52 |
Annual Sum or Average | 1061.67 | 23.66 | 2082.00 | 24.55 | 12.67 | 24.56 |
Minimum of Months | 0.00 | 0.00 | 27.33 | 23.79 | 0.00 | 23.87 |
Maximum of Months | 336.67 | 24.00 | 440.67 | 25.66 | 12.50 | 25.66 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 275.83 | 23.64 | 13.83 | 23.70 | 12.50 | 23.75 |
February | 190.50 | 23.64 | 42.83 | 23.81 | 0.00 | 23.81 |
March | 115.00 | 23.72 | 70.67 | 24.19 | 0.00 | 24.19 |
April | 41.50 | 23.73 | 145.67 | 24.68 | 0.00 | 24.68 |
May | 43.83 | 23.62 | 212.50 | 24.38 | 0.00 | 24.38 |
June | 2.50 | 23.66 | 278.33 | 24.40 | 0.00 | 24.40 |
July | 0.00 | 0.00 | 420.67 | 24.38 | 0.00 | 24.38 |
August | 0.00 | 0.00 | 482.83 | 24.29 | 0.00 | 24.29 |
September | 2.83 | 23.44 | 356.50 | 24.42 | 0.00 | 24.42 |
October | 39.00 | 23.57 | 168.17 | 24.62 | 0.00 | 24.62 |
November | 74.17 | 23.65 | 150.50 | 24.43 | 0.00 | 24.43 |
December | 147.33 | 23.66 | 51.17 | 24.06 | 0.00 | 24.06 |
Annual Sum or Average | 932.50 | 23.65 | 2393.67 | 24.28 | 12.50 | 24.28 |
Minimum of Months | 0.00 | 0.00 | 13.83 | 23.70 | 0.00 | 23.75 |
Maximum of Months | 275.83 | 23.73 | 482.83 | 24.68 | 12.50 | 24.68 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 450.67 | 22.56 | 24.83 | 22.38 | 24.83 | 22.22 |
February | 365.67 | 22.99 | 12.83 | 22.92 | 12.17 | 22.86 |
March | 315.50 | 23.44 | 10.00 | 23.46 | 0.00 | 23.46 |
April | 218.50 | 23.48 | 44.33 | 23.66 | 0.00 | 23.66 |
May | 128.67 | 23.48 | 116.67 | 23.89 | 0.00 | 23.89 |
June | 61.83 | 23.46 | 172.33 | 24.16 | 0.00 | 24.16 |
July | 37.83 | 23.43 | 283.50 | 24.25 | 0.00 | 24.25 |
August | 25.83 | 23.34 | 386.50 | 24.19 | 0.00 | 24.19 |
September | 60.00 | 23.37 | 247.83 | 24.17 | 0.00 | 24.17 |
October | 211.33 | 23.34 | 42.17 | 23.56 | 0.00 | 23.56 |
November | 316.83 | 23.27 | 27.67 | 23.35 | 0.00 | 23.35 |
December | 422.17 | 23.03 | 0.00 | 23.03 | 0.00 | 23.03 |
Annual Sum or Average | 2614.83 | 23.13 | 1368.67 | 23.51 | 37.00 | 23.47 |
Minimum of Months | 25.83 | 22.56 | 0.00 | 22.38 | 0.00 | 22.22 |
Maximum of Months | 450.67 | 23.48 | 386.50 | 24.25 | 24.83 | 24.25 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.00 | 159.00 | 20.56 | 159.00 | 20.29 |
February | 442.50 | 21.44 | 106.17 | 21.06 | 106.17 | 20.80 |
March | 473.50 | 22.19 | 50.83 | 21.98 | 50.50 | 21.81 |
April | 358.00 | 22.49 | 35.67 | 22.55 | 9.33 | 22.50 |
May | 275.83 | 22.80 | 71.83 | 23.07 | 0.00 | 23.07 |
June | 170.00 | 23.08 | 143.00 | 23.58 | 0.00 | 23.58 |
July | 121.17 | 23.08 | 264.00 | 23.84 | 0.00 | 23.84 |
August | 123.33 | 23.05 | 302.00 | 23.83 | 0.00 | 23.83 |
September | 257.83 | 22.79 | 122.50 | 23.20 | 0.00 | 23.20 |
October | 431.33 | 22.25 | 30.17 | 22.12 | 30.17 | 22.01 |
November | 474.33 | 21.71 | 79.00 | 21.44 | 77.83 | 21.23 |
December | 497.00 | 21.19 | 135.67 | 20.84 | 135.67 | 20.61 |
Annual Sum or Average | 4126.83 | 21.99 | 1499.83 | 22.10 | 568.67 | 21.86 |
Minimum of Months | 121.17 | 21.00 | 30.17 | 20.56 | 0.00 | 20.29 |
Maximum of Months | 502.00 | 23.08 | 302.00 | 23.84 | 159.00 | 23.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.43 | 84.33 | 21.26 | 84.33 | 21.14 |
February | 435.33 | 21.75 | 55.83 | 21.59 | 55.83 | 21.46 |
March | 460.33 | 22.50 | 5.00 | 22.48 | 5.00 | 22.46 |
April | 298.00 | 22.79 | 42.00 | 22.97 | 0.00 | 22.97 |
May | 233.17 | 22.97 | 111.83 | 23.35 | 0.00 | 23.35 |
June | 110.83 | 23.23 | 191.50 | 23.83 | 0.00 | 23.83 |
July | 50.67 | 23.32 | 353.17 | 24.12 | 0.00 | 24.12 |
August | 49.83 | 23.19 | 374.67 | 24.06 | 0.00 | 24.06 |
September | 194.83 | 22.95 | 173.67 | 23.53 | 0.00 | 23.53 |
October | 392.50 | 22.63 | 12.33 | 22.71 | 0.00 | 22.71 |
November | 450.33 | 22.22 | 6.67 | 22.25 | 0.00 | 22.25 |
December | 497.00 | 21.76 | 5.33 | 21.75 | 5.33 | 21.74 |
Annual Sum or Average | 3674.83 | 22.26 | 1416.33 | 22.69 | 150.50 | 22.62 |
Minimum of Months | 49.83 | 21.43 | 5.00 | 21.26 | 0.00 | 21.14 |
Maximum of Months | 502.00 | 23.32 | 374.67 | 24.12 | 84.33 | 24.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.97 | 94.67 | 20.86 | 94.67 | 20.78 |
February | 447.33 | 21.36 | 47.83 | 21.27 | 47.83 | 21.19 |
March | 480.67 | 21.79 | 15.00 | 21.80 | 8.83 | 21.78 |
April | 325.50 | 22.04 | 79.83 | 22.47 | 0.00 | 22.47 |
May | 296.00 | 22.25 | 136.67 | 22.88 | 3.83 | 22.91 |
June | 206.50 | 22.53 | 208.17 | 23.37 | 4.83 | 23.41 |
July | 168.67 | 22.76 | 264.33 | 23.64 | 10.83 | 23.72 |
August | 167.67 | 22.65 | 284.00 | 23.56 | 10.00 | 23.63 |
September | 278.50 | 22.19 | 148.33 | 22.90 | 4.50 | 22.94 |
October | 421.17 | 21.86 | 42.17 | 22.10 | 0.00 | 22.10 |
November | 477.33 | 21.46 | 7.83 | 21.46 | 5.33 | 21.45 |
December | 497.00 | 21.15 | 34.50 | 21.11 | 34.50 | 21.07 |
Annual Sum or Average | 4268.33 | 21.73 | 1363.33 | 22.20 | 225.17 | 22.17 |
Minimum of Months | 167.67 | 20.97 | 7.83 | 20.86 | 0.00 | 20.78 |
Maximum of Months | 502.00 | 22.76 | 284.00 | 23.64 | 94.67 | 23.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 471.83 | 21.03 | 123.67 | 20.94 | 111.00 | 20.81 |
February | 374.50 | 21.32 | 116.83 | 21.57 | 61.67 | 21.44 |
March | 394.00 | 21.66 | 95.67 | 22.01 | 20.33 | 21.95 |
April | 310.50 | 22.04 | 123.67 | 22.67 | 2.17 | 22.69 |
May | 301.50 | 22.19 | 151.33 | 22.87 | 3.67 | 22.90 |
June | 233.67 | 22.34 | 181.33 | 23.15 | 1.67 | 23.17 |
July | 167.33 | 22.64 | 269.33 | 23.62 | 9.33 | 23.68 |
August | 159.00 | 22.65 | 294.50 | 23.63 | 11.17 | 23.70 |
September | 250.00 | 22.29 | 199.50 | 23.16 | 6.00 | 23.22 |
October | 349.00 | 21.89 | 120.50 | 22.54 | 2.83 | 22.57 |
November | 427.17 | 21.46 | 69.33 | 21.67 | 28.17 | 21.62 |
December | 445.83 | 21.20 | 110.33 | 21.30 | 74.83 | 21.19 |
Annual Sum or Average | 3884.33 | 21.73 | 1856.00 | 22.35 | 332.83 | 22.28 |
Minimum of Months | 159.00 | 21.03 | 69.33 | 20.94 | 1.67 | 20.81 |
Maximum of Months | 471.83 | 22.65 | 294.50 | 23.63 | 111.00 | 23.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.67 | 21.30 | 32.67 | 21.25 | 32.67 | 21.20 |
February | 414.17 | 21.54 | 40.00 | 21.63 | 20.33 | 21.58 |
March | 416.17 | 22.11 | 46.83 | 22.34 | 0.00 | 22.34 |
April | 256.83 | 22.47 | 155.33 | 23.31 | 8.67 | 23.36 |
May | 258.00 | 22.48 | 179.83 | 23.27 | 13.33 | 23.38 |
June | 157.50 | 22.51 | 245.33 | 23.62 | 7.00 | 23.66 |
July | 102.00 | 23.69 | 383.17 | 24.33 | 40.00 | 24.42 |
August | 84.33 | 24.06 | 421.00 | 24.31 | 51.00 | 24.38 |
September | 217.67 | 22.32 | 206.17 | 23.34 | 9.33 | 23.41 |
October | 378.17 | 22.06 | 74.50 | 22.49 | 0.33 | 22.49 |
November | 438.33 | 21.90 | 36.00 | 22.14 | 0.00 | 22.14 |
December | 472.17 | 21.84 | 8.00 | 21.89 | 0.00 | 21.89 |
Annual Sum or Average | 3694.00 | 22.04 | 1828.83 | 22.80 | 182.67 | 22.85 |
Minimum of Months | 84.33 | 21.30 | 8.00 | 21.25 | 0.00 | 21.20 |
Maximum of Months | 498.67 | 24.06 | 421.00 | 24.33 | 51.00 | 24.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.26 | 302.67 | 20.07 | 302.67 | 19.98 |
February | 454.00 | 20.63 | 204.50 | 20.39 | 204.50 | 20.26 |
March | 513.17 | 21.33 | 101.00 | 21.17 | 101.00 | 21.05 |
April | 443.50 | 21.90 | 41.00 | 21.87 | 29.50 | 21.79 |
May | 354.33 | 22.27 | 54.83 | 22.50 | 0.67 | 22.50 |
June | 261.83 | 22.68 | 92.17 | 23.04 | 0.00 | 23.04 |
July | 190.50 | 22.78 | 203.50 | 23.44 | 0.00 | 23.44 |
August | 196.33 | 22.60 | 244.00 | 23.42 | 0.00 | 23.42 |
September | 354.00 | 22.32 | 63.33 | 22.58 | 0.00 | 22.58 |
October | 495.00 | 21.63 | 32.67 | 21.53 | 32.67 | 21.45 |
November | 489.00 | 20.91 | 130.67 | 20.69 | 130.67 | 20.55 |
December | 497.00 | 20.48 | 267.00 | 20.31 | 267.00 | 20.22 |
Annual Sum or Average | 4750.67 | 21.43 | 1737.33 | 21.45 | 1068.67 | 21.24 |
Minimum of Months | 190.50 | 20.26 | 32.67 | 20.07 | 0.00 | 19.98 |
Maximum of Months | 513.17 | 22.78 | 302.67 | 23.44 | 302.67 | 23.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.14 | 271.50 | 19.94 | 271.50 | 19.86 |
February | 385.00 | 20.67 | 171.67 | 20.45 | 171.67 | 20.34 |
March | 420.33 | 21.23 | 80.33 | 21.08 | 78.33 | 20.96 |
April | 322.33 | 21.64 | 62.33 | 21.84 | 23.17 | 21.77 |
May | 297.67 | 21.88 | 86.00 | 22.43 | 4.17 | 22.47 |
June | 226.83 | 22.24 | 142.00 | 23.04 | 5.33 | 23.10 |
July | 204.83 | 22.49 | 181.67 | 23.35 | 10.17 | 23.45 |
August | 194.00 | 22.39 | 200.83 | 23.32 | 11.17 | 23.41 |
September | 283.50 | 21.92 | 88.33 | 22.48 | 4.00 | 22.52 |
October | 387.33 | 21.38 | 44.33 | 21.44 | 25.67 | 21.36 |
November | 416.83 | 20.81 | 120.50 | 20.60 | 120.50 | 20.46 |
December | 422.00 | 20.39 | 237.17 | 20.21 | 237.17 | 20.13 |
Annual Sum or Average | 3987.67 | 21.25 | 1686.67 | 21.43 | 962.83 | 21.24 |
Minimum of Months | 194.00 | 20.14 | 44.33 | 19.94 | 4.00 | 19.86 |
Maximum of Months | 427.00 | 22.49 | 271.50 | 23.35 | 271.50 | 23.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 477.00 | 20.57 | 239.00 | 20.39 | 228.67 | 20.25 |
February | 383.00 | 20.98 | 171.33 | 21.12 | 122.00 | 20.96 |
March | 401.67 | 21.26 | 141.00 | 21.55 | 66.83 | 21.41 |
April | 334.50 | 21.62 | 134.67 | 22.20 | 27.00 | 22.13 |
May | 332.33 | 21.89 | 136.00 | 22.58 | 5.00 | 22.61 |
June | 291.00 | 22.07 | 142.50 | 22.78 | 1.33 | 22.80 |
July | 228.00 | 22.28 | 225.83 | 23.25 | 7.67 | 23.31 |
August | 231.00 | 22.30 | 245.33 | 23.29 | 11.67 | 23.37 |
September | 276.50 | 22.02 | 179.67 | 22.90 | 7.00 | 22.96 |
October | 363.83 | 21.55 | 132.33 | 22.19 | 19.00 | 22.16 |
November | 442.33 | 21.08 | 132.83 | 21.14 | 97.83 | 21.01 |
December | 453.17 | 20.73 | 227.00 | 20.69 | 197.00 | 20.55 |
Annual Sum or Average | 4214.33 | 21.40 | 2107.50 | 21.86 | 791.00 | 21.70 |
Minimum of Months | 228.00 | 20.57 | 132.33 | 20.39 | 1.33 | 20.25 |
Maximum of Months | 477.00 | 22.30 | 245.33 | 23.29 | 228.67 | 23.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.39 | 258.83 | 20.18 | 258.83 | 20.08 |
February | 442.67 | 20.77 | 153.83 | 20.58 | 150.67 | 20.45 |
March | 482.33 | 21.20 | 86.33 | 21.19 | 70.00 | 21.10 |
April | 390.00 | 21.53 | 83.17 | 21.88 | 18.33 | 21.84 |
May | 375.00 | 21.99 | 101.67 | 22.50 | 11.17 | 22.60 |
June | 316.17 | 22.05 | 133.00 | 22.70 | 2.67 | 22.72 |
July | 229.67 | 22.36 | 231.33 | 23.37 | 19.17 | 23.46 |
August | 261.50 | 22.29 | 218.17 | 23.18 | 24.67 | 23.27 |
September | 339.50 | 21.90 | 117.50 | 22.52 | 5.83 | 22.57 |
October | 454.50 | 21.36 | 50.33 | 21.50 | 19.67 | 21.46 |
November | 482.17 | 20.92 | 109.33 | 20.79 | 105.50 | 20.68 |
December | 497.00 | 20.65 | 212.83 | 20.47 | 212.83 | 20.38 |
Annual Sum or Average | 4772.50 | 21.32 | 1756.33 | 21.57 | 899.33 | 21.43 |
Minimum of Months | 229.67 | 20.39 | 50.33 | 20.18 | 2.67 | 20.08 |
Maximum of Months | 502.00 | 22.36 | 258.83 | 23.37 | 258.83 | 23.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.96 | 398.17 | 19.84 | 398.17 | 19.79 |
February | 454.00 | 20.19 | 286.17 | 19.98 | 286.17 | 19.89 |
March | 514.00 | 20.70 | 216.33 | 20.47 | 216.33 | 20.35 |
April | 464.00 | 21.30 | 120.67 | 21.13 | 109.83 | 20.98 |
May | 407.83 | 21.69 | 79.33 | 21.75 | 38.17 | 21.62 |
June | 332.50 | 22.14 | 81.17 | 22.50 | 0.67 | 22.50 |
July | 254.00 | 22.20 | 175.50 | 22.93 | 1.00 | 22.92 |
August | 274.17 | 22.08 | 183.17 | 22.86 | 0.00 | 22.86 |
September | 409.83 | 21.67 | 52.83 | 21.82 | 12.67 | 21.78 |
October | 502.00 | 20.88 | 139.17 | 20.64 | 139.17 | 20.48 |
November | 489.00 | 20.26 | 261.67 | 20.03 | 261.67 | 19.91 |
December | 497.00 | 19.99 | 399.33 | 19.87 | 399.33 | 19.83 |
Annual Sum or Average | 5100.33 | 20.94 | 2393.50 | 20.86 | 1863.17 | 20.64 |
Minimum of Months | 254.00 | 19.96 | 52.83 | 19.84 | 0.00 | 19.79 |
Maximum of Months | 514.00 | 22.20 | 399.33 | 22.93 | 399.33 | 22.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.96 | 381.83 | 19.81 | 381.83 | 19.76 |
February | 454.00 | 20.26 | 262.00 | 20.04 | 262.00 | 19.94 |
March | 509.00 | 20.83 | 174.00 | 20.58 | 172.00 | 20.42 |
April | 395.50 | 21.38 | 114.67 | 21.41 | 73.67 | 21.24 |
May | 341.17 | 21.56 | 141.17 | 22.06 | 32.33 | 21.96 |
June | 250.00 | 21.99 | 201.00 | 22.97 | 4.33 | 23.00 |
July | 223.00 | 22.26 | 242.33 | 23.27 | 11.17 | 23.35 |
August | 232.33 | 22.19 | 240.33 | 23.18 | 11.33 | 23.25 |
September | 338.83 | 21.57 | 129.33 | 22.19 | 13.00 | 22.16 |
October | 479.67 | 21.02 | 126.50 | 20.82 | 119.00 | 20.65 |
November | 489.00 | 20.31 | 244.33 | 20.07 | 244.33 | 19.94 |
December | 497.00 | 20.01 | 371.17 | 19.86 | 371.17 | 19.81 |
Annual Sum or Average | 4711.50 | 20.91 | 2628.67 | 21.06 | 1696.17 | 20.83 |
Minimum of Months | 223.00 | 19.96 | 114.67 | 19.81 | 4.33 | 19.76 |
Maximum of Months | 509.00 | 22.26 | 381.83 | 23.27 | 381.83 | 23.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.83 | 20.20 | 322.67 | 19.98 | 318.67 | 19.87 |
February | 406.67 | 20.59 | 234.50 | 20.56 | 200.00 | 20.39 |
March | 425.83 | 20.85 | 209.00 | 20.88 | 154.33 | 20.68 |
April | 357.67 | 21.24 | 177.50 | 21.61 | 82.83 | 21.43 |
May | 349.33 | 21.50 | 160.17 | 22.06 | 41.67 | 21.95 |
June | 306.50 | 21.81 | 141.50 | 22.56 | 3.67 | 22.57 |
July | 247.00 | 22.02 | 223.00 | 23.05 | 9.17 | 23.12 |
August | 258.67 | 21.99 | 227.17 | 23.02 | 11.50 | 23.09 |
September | 311.33 | 21.68 | 170.83 | 22.50 | 19.83 | 22.52 |
October | 389.17 | 21.04 | 177.33 | 21.37 | 92.50 | 21.19 |
November | 455.83 | 20.52 | 226.17 | 20.43 | 199.50 | 20.26 |
December | 468.83 | 20.23 | 320.17 | 20.08 | 305.00 | 19.96 |
Annual Sum or Average | 4471.67 | 21.01 | 2590.00 | 21.30 | 1438.67 | 21.07 |
Minimum of Months | 247.00 | 20.20 | 141.50 | 19.98 | 3.67 | 19.87 |
Maximum of Months | 494.83 | 22.02 | 322.67 | 23.05 | 318.67 | 23.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.07 | 342.17 | 19.89 | 342.17 | 19.81 |
February | 447.00 | 20.44 | 237.33 | 20.23 | 235.33 | 20.12 |
March | 490.83 | 20.88 | 176.67 | 20.75 | 162.17 | 20.61 |
April | 403.33 | 21.26 | 129.83 | 21.45 | 73.50 | 21.32 |
May | 384.67 | 21.67 | 122.33 | 22.13 | 35.33 | 22.15 |
June | 324.00 | 21.80 | 127.83 | 22.49 | 6.00 | 22.52 |
July | 251.33 | 22.16 | 220.33 | 23.16 | 27.00 | 23.28 |
August | 296.33 | 22.09 | 202.83 | 22.96 | 31.33 | 23.07 |
September | 358.33 | 21.60 | 109.00 | 22.18 | 10.00 | 22.20 |
October | 463.33 | 21.01 | 116.33 | 20.99 | 91.17 | 20.86 |
November | 485.17 | 20.51 | 207.17 | 20.29 | 205.00 | 20.16 |
December | 497.00 | 20.20 | 325.00 | 20.02 | 325.00 | 19.95 |
Annual Sum or Average | 4903.33 | 21.01 | 2316.83 | 21.15 | 1544.00 | 20.97 |
Minimum of Months | 251.33 | 20.07 | 109.00 | 19.89 | 6.00 | 19.81 |
Maximum of Months | 502.00 | 22.16 | 342.17 | 23.16 | 342.17 | 23.28 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 4.33 | 27.00 | 454.00 | 27.00 | 4.33 | 27.00 |
March | 16.00 | 27.00 | 514.00 | 27.00 | 16.00 | 27.00 |
April | 89.17 | 27.00 | 485.00 | 27.00 | 89.17 | 27.00 |
May | 36.33 | 27.00 | 508.00 | 27.00 | 36.33 | 27.00 |
June | 92.00 | 27.00 | 496.00 | 27.00 | 92.00 | 27.00 |
July | 235.50 | 27.00 | 497.00 | 27.00 | 235.50 | 27.00 |
August | 332.67 | 27.00 | 514.00 | 27.00 | 332.67 | 27.00 |
September | 64.17 | 27.00 | 485.00 | 27.00 | 64.17 | 27.00 |
October | 21.17 | 27.00 | 502.00 | 27.00 | 21.17 | 27.00 |
November | 6.83 | 27.00 | 489.00 | 27.00 | 6.83 | 27.00 |
December | 7.17 | 27.00 | 497.00 | 27.00 | 7.17 | 27.00 |
Annual Sum or Average | 905.33 | 27.00 | 5943.00 | 27.00 | 905.33 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 332.67 | 27.00 | 514.00 | 27.00 | 332.67 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.00 | 25.45 | 436.83 | 26.96 | 0.00 | 26.96 |
February | 0.17 | 27.00 | 411.83 | 27.00 | 0.17 | 27.00 |
March | 5.83 | 27.00 | 507.50 | 27.00 | 5.83 | 27.00 |
April | 15.17 | 27.00 | 485.00 | 27.00 | 15.17 | 27.00 |
May | 15.50 | 27.00 | 508.00 | 27.00 | 15.50 | 27.00 |
June | 30.33 | 27.00 | 496.00 | 27.00 | 30.33 | 27.00 |
July | 92.33 | 27.00 | 497.00 | 27.00 | 92.33 | 27.00 |
August | 105.17 | 27.00 | 514.00 | 27.00 | 105.17 | 27.00 |
September | 33.33 | 27.00 | 485.00 | 27.00 | 33.33 | 27.00 |
October | 6.33 | 27.00 | 502.00 | 27.00 | 6.33 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 317.17 | 26.94 | 5829.17 | 27.00 | 304.17 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 411.83 | 26.96 | 0.00 | 26.96 |
Maximum of Months | 105.17 | 27.00 | 514.00 | 27.00 | 105.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 77.17 | 25.12 | 335.83 | 26.65 | 0.00 | 26.65 |
February | 28.50 | 27.00 | 332.83 | 27.00 | 0.00 | 27.00 |
March | 8.33 | 27.00 | 459.83 | 27.00 | 5.67 | 27.00 |
April | 21.83 | 27.00 | 480.00 | 27.00 | 21.83 | 27.00 |
May | 33.17 | 27.00 | 508.00 | 27.00 | 33.17 | 27.00 |
June | 54.17 | 27.00 | 496.00 | 27.00 | 54.17 | 27.00 |
July | 131.00 | 27.00 | 497.00 | 27.00 | 131.00 | 27.00 |
August | 132.00 | 27.00 | 514.00 | 27.00 | 132.00 | 27.00 |
September | 45.00 | 27.00 | 485.00 | 27.00 | 45.00 | 27.00 |
October | 6.33 | 27.00 | 483.17 | 27.00 | 6.33 | 27.00 |
November | 0.00 | 0.00 | 428.33 | 27.00 | 0.00 | 27.00 |
December | 12.00 | 27.00 | 386.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 549.50 | 26.74 | 5406.33 | 26.98 | 429.17 | 26.98 |
Minimum of Months | 0.00 | 0.00 | 332.83 | 26.65 | 0.00 | 26.65 |
Maximum of Months | 132.00 | 27.00 | 514.00 | 27.00 | 132.00 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 235.67 | 27.08 | 502.00 | 27.09 | 235.67 | 27.09 |
February | 35.83 | 27.01 | 450.83 | 24.95 | 35.83 | 25.09 |
March | 283.33 | 25.79 | 483.50 | 25.63 | 279.67 | 25.69 |
April | 173.50 | 25.92 | 485.00 | 24.65 | 173.50 | 24.91 |
May | 399.67 | 27.03 | 508.00 | 27.03 | 399.67 | 27.03 |
June | 219.17 | 26.89 | 495.67 | 26.07 | 219.17 | 26.26 |
July | 453.83 | 26.42 | 491.50 | 26.30 | 453.83 | 26.34 |
August | 467.83 | 26.55 | 514.00 | 26.39 | 467.83 | 26.44 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 124.67 | 26.99 | 499.67 | 25.56 | 124.67 | 25.80 |
November | 358.17 | 25.81 | 465.67 | 25.62 | 355.50 | 25.69 |
December | 184.83 | 25.36 | 497.00 | 24.50 | 184.83 | 24.69 |
Annual Sum or Average | 3421.50 | 26.50 | 5877.83 | 26.01 | 3415.17 | 26.15 |
Minimum of Months | 35.83 | 25.36 | 450.83 | 24.50 | 35.83 | 24.69 |
Maximum of Months | 485.00 | 27.08 | 514.00 | 27.09 | 485.00 | 27.09 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 27.62190 | 0.76242 | 17.36753 |
February | 454.00000 | 27.00000 | 27.12417 | 0.80005 | 18.71881 |
March | 514.00000 | 27.00000 | 28.08629 | 0.87036 | 21.15071 |
April | 485.00000 | 27.00001 | 30.96980 | 0.95418 | 24.35967 |
May | 508.00000 | 27.00004 | 34.71784 | 0.24741 | 6.49816 |
June | 496.00000 | 27.00002 | 36.01586 | 0.31803 | 7.29722 |
July | 497.00000 | 27.00001 | 37.52320 | 0.41212 | 8.71615 |
August | 514.00000 | 27.00021 | 37.32643 | 0.45310 | 9.45879 |
September | 485.00000 | 27.00014 | 38.19936 | 0.29047 | 6.96408 |
October | 502.00000 | 27.00001 | 33.88940 | 0.90461 | 22.38538 |
November | 489.00000 | 27.00000 | 31.77947 | 0.88422 | 21.62635 |
December | 497.00000 | 27.00000 | 27.39293 | 0.85496 | 20.51540 |
Annual Sum or Average | 5943.00000 | 27.00004 | 32.58729 | 0.64438 | 15.38002 |
Minimum of Months | 454.00000 | 27.00000 | 27.12417 | 0.24741 | 6.49816 |
Maximum of Months | 514.00000 | 27.00021 | 38.19936 | 0.95418 | 24.35967 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.95835 | 27.86778 | 0.64974 | 14.16490 |
February | 454.00000 | 27.00000 | 27.12503 | 0.70637 | 15.80784 |
March | 514.00000 | 27.00000 | 28.07405 | 0.77431 | 17.84938 |
April | 485.00000 | 27.00001 | 30.97350 | 0.84903 | 20.39775 |
May | 508.00000 | 27.00004 | 34.71517 | 0.16278 | 5.84827 |
June | 496.00000 | 27.00002 | 36.01532 | 0.22415 | 6.30657 |
July | 497.00000 | 27.00001 | 37.53934 | 0.29373 | 7.08044 |
August | 514.00000 | 27.00023 | 37.41032 | 0.31256 | 7.33004 |
September | 485.00000 | 27.00014 | 38.26188 | 0.20216 | 6.12648 |
October | 502.00000 | 27.00001 | 33.88524 | 0.82254 | 19.41469 |
November | 489.00000 | 27.00000 | 31.77356 | 0.77216 | 17.72183 |
December | 497.00000 | 27.00000 | 27.39758 | 0.72063 | 16.07961 |
Annual Sum or Average | 5943.00000 | 26.99652 | 32.62035 | 0.53910 | 12.80762 |
Minimum of Months | 454.00000 | 26.95835 | 27.12503 | 0.16278 | 5.84827 |
Maximum of Months | 514.00000 | 27.00023 | 38.26188 | 0.84903 | 20.39775 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.71146 | 28.10646 | 0.52451 | 12.07219 |
February | 454.00000 | 27.00005 | 27.13120 | 0.62638 | 13.73463 |
March | 514.00000 | 27.00000 | 28.08489 | 0.70407 | 15.82585 |
April | 485.00000 | 27.00001 | 31.03573 | 0.80068 | 18.89751 |
May | 508.00000 | 27.00052 | 34.73686 | 0.11994 | 5.93955 |
June | 496.00000 | 27.00002 | 36.02615 | 0.20621 | 6.39758 |
July | 497.00000 | 27.00002 | 37.54573 | 0.28458 | 7.24618 |
August | 514.00000 | 27.00020 | 37.52047 | 0.29529 | 7.37211 |
September | 485.00000 | 27.00025 | 38.31197 | 0.14722 | 6.02487 |
October | 502.00000 | 27.00001 | 33.90095 | 0.75280 | 17.22266 |
November | 489.00000 | 27.00000 | 31.78747 | 0.68410 | 15.14165 |
December | 497.00000 | 27.00000 | 27.42747 | 0.62378 | 13.45432 |
Annual Sum or Average | 5943.00000 | 26.97572 | 32.66888 | 0.47925 | 11.58263 |
Minimum of Months | 454.00000 | 26.71146 | 27.13120 | 0.11994 | 5.93955 |
Maximum of Months | 514.00000 | 27.00052 | 38.31197 | 0.80068 | 18.89751 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.09236 | 30.00737 | 1.01744 | 26.88526 |
February | 454.00000 | 24.76417 | 32.13702 | 0.73055 | 16.64660 |
March | 514.00000 | 25.26716 | 30.75972 | 0.91345 | 23.57303 |
April | 485.00000 | 24.19342 | 33.36417 | 0.88261 | 22.77785 |
May | 508.00000 | 27.03256 | 32.28561 | 0.46558 | 9.59550 |
June | 496.00000 | 25.70580 | 35.17606 | 0.33967 | 8.89384 |
July | 497.00000 | 26.13022 | 38.30718 | 0.68297 | 16.86564 |
August | 514.00000 | 26.24557 | 41.33338 | 0.93299 | 25.87235 |
September | 485.00000 | 27.00115 | 36.97352 | 0.55934 | 11.65294 |
October | 502.00000 | 25.18748 | 33.80370 | 0.87290 | 21.83679 |
November | 489.00000 | 25.24758 | 33.09674 | 0.96296 | 25.63415 |
December | 497.00000 | 24.18071 | 30.83294 | 0.86981 | 21.73097 |
Annual Sum or Average | 5943.00000 | 25.68190 | 34.02126 | 0.77009 | 19.37294 |
Minimum of Months | 454.00000 | 24.18071 | 30.00737 | 0.33967 | 8.89384 |
Maximum of Months | 514.00000 | 27.09236 | 41.33338 | 1.01744 | 26.88526 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.96488 | 29.80621 | 0.27819 | 7.33314 |
February | 454.00000 | 24.11744 | 29.09611 | 0.30918 | 7.24054 |
March | 514.00000 | 24.17952 | 28.79479 | 0.33299 | 7.52995 |
April | 485.00000 | 24.20812 | 32.46475 | 0.36877 | 8.22781 |
May | 508.00000 | 24.17570 | 37.14734 | -0.4852 | 10.73544 |
June | 496.00000 | 24.29764 | 39.05175 | -0.4179 | 9.32307 |
July | 497.00000 | 24.51764 | 42.80196 | -0.3136 | 8.03046 |
August | 514.00000 | 24.38957 | 45.24759 | -0.3208 | 7.96079 |
September | 485.00000 | 24.34124 | 43.22640 | -0.3656 | 8.97824 |
October | 502.00000 | 24.29575 | 35.47074 | 0.42262 | 9.26664 |
November | 489.00000 | 24.36273 | 33.57263 | 0.41961 | 9.21045 |
December | 497.00000 | 24.22623 | 28.61298 | 0.34121 | 7.77155 |
Annual Sum or Average | 5943.00000 | 24.25695 | 35.48669 | 0.04461 | 8.47431 |
Minimum of Months | 454.00000 | 23.96488 | 28.61298 | -0.4852 | 7.24054 |
Maximum of Months | 514.00000 | 24.51764 | 45.24759 | 0.42262 | 10.73544 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.86989 | 31.17786 | 0.25710 | 6.88098 |
February | 454.00000 | 23.96313 | 30.00047 | 0.28213 | 6.99041 |
March | 514.00000 | 24.16548 | 29.33933 | 0.34352 | 7.66855 |
April | 485.00000 | 24.28001 | 32.64604 | 0.40495 | 8.73143 |
May | 508.00000 | 24.19223 | 37.71897 | -0.4535 | 9.74359 |
June | 496.00000 | 24.22493 | 39.83508 | -0.4061 | 8.81120 |
July | 497.00000 | 24.32443 | 44.72661 | -0.3257 | 7.70106 |
August | 514.00000 | 24.27062 | 48.29244 | -0.3011 | 7.28042 |
September | 485.00000 | 24.29170 | 45.33811 | -0.3592 | 8.24631 |
October | 502.00000 | 24.25044 | 36.37900 | 0.41498 | 8.89449 |
November | 489.00000 | 24.24505 | 34.74183 | 0.39355 | 8.54057 |
December | 497.00000 | 24.14782 | 29.88090 | 0.32937 | 7.47366 |
Annual Sum or Average | 5943.00000 | 24.18658 | 36.72336 | 0.04576 | 8.08501 |
Minimum of Months | 454.00000 | 23.86989 | 29.33933 | -0.4535 | 6.88098 |
Maximum of Months | 514.00000 | 24.32443 | 48.29244 | 0.41498 | 9.74359 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.71040 | 31.86790 | -0.0561 | 7.12673 |
February | 454.00000 | 23.18892 | 31.53232 | 0.07458 | 6.29828 |
March | 514.00000 | 23.69080 | 30.94792 | 0.20806 | 6.33020 |
April | 485.00000 | 23.85893 | 34.23796 | 0.28146 | 7.01955 |
May | 508.00000 | 23.97128 | 38.58065 | -0.5524 | 11.89129 |
June | 496.00000 | 24.05128 | 40.54228 | -0.4950 | 10.50008 |
July | 497.00000 | 24.12265 | 45.82138 | -0.4338 | 9.38826 |
August | 514.00000 | 24.11391 | 49.25889 | -0.4022 | 8.79300 |
September | 485.00000 | 24.05840 | 46.34048 | -0.4646 | 9.95745 |
October | 502.00000 | 23.81831 | 37.94876 | 0.29187 | 7.15793 |
November | 489.00000 | 23.54901 | 37.40832 | 0.20347 | 6.44018 |
December | 497.00000 | 23.17406 | 32.80655 | 0.07260 | 5.79462 |
Annual Sum or Average | 5943.00000 | 23.69603 | 38.15399 | -0.1081 | 8.07361 |
Minimum of Months | 454.00000 | 22.71040 | 30.94792 | -0.5524 | 5.79462 |
Maximum of Months | 514.00000 | 24.12265 | 49.25889 | 0.29187 | 11.89129 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.00368 | 34.17324 | -0.4906 | 14.07522 |
February | 454.00000 | 21.50774 | 34.42988 | -0.3500 | 11.26194 |
March | 514.00000 | 22.32651 | 33.69177 | -0.1370 | 7.55168 |
April | 485.00000 | 22.89733 | 36.47404 | 0.04300 | 6.73464 |
May | 508.00000 | 23.35442 | 40.08923 | -0.7660 | 19.55725 |
June | 496.00000 | 23.74868 | 41.33585 | -0.5943 | 13.54930 |
July | 497.00000 | 23.87198 | 46.56465 | -0.5053 | 11.34561 |
August | 514.00000 | 23.83971 | 50.20294 | -0.4887 | 11.05794 |
September | 485.00000 | 23.36122 | 48.64867 | -0.7130 | 17.52079 |
October | 502.00000 | 22.48974 | 41.56407 | -0.0425 | 6.77403 |
November | 489.00000 | 21.77486 | 41.47657 | -0.2431 | 8.70061 |
December | 497.00000 | 21.19458 | 36.11113 | -0.4312 | 11.53132 |
Annual Sum or Average | 5943.00000 | 22.62366 | 40.43370 | -0.3940 | 11.64201 |
Minimum of Months | 454.00000 | 21.00368 | 33.69177 | -0.7660 | 6.73464 |
Maximum of Months | 514.00000 | 23.87198 | 50.20294 | 0.04300 | 19.55725 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.42559 | 31.58540 | -0.3607 | 8.80604 |
February | 454.00000 | 21.83715 | 31.83727 | -0.2460 | 8.04263 |
March | 514.00000 | 22.65120 | 31.18541 | -0.0411 | 6.23315 |
April | 485.00000 | 23.29447 | 33.65337 | 0.15198 | 6.63228 |
May | 508.00000 | 23.56451 | 38.09010 | -0.6698 | 16.10032 |
June | 496.00000 | 23.90186 | 39.80679 | -0.5143 | 11.30765 |
July | 497.00000 | 24.09889 | 44.36919 | -0.3913 | 8.78279 |
August | 514.00000 | 24.03805 | 48.19058 | -0.3809 | 8.70606 |
September | 485.00000 | 23.62195 | 46.25474 | -0.6078 | 14.15130 |
October | 502.00000 | 22.95722 | 38.52323 | 0.08315 | 6.15744 |
November | 489.00000 | 22.36009 | 37.41647 | -0.0808 | 6.38563 |
December | 497.00000 | 21.76119 | 32.59906 | -0.2644 | 7.11793 |
Annual Sum or Average | 5943.00000 | 22.96813 | 37.83395 | -0.2776 | 9.04166 |
Minimum of Months | 454.00000 | 21.42559 | 31.18541 | -0.6698 | 6.15744 |
Maximum of Months | 514.00000 | 24.09889 | 48.19058 | 0.15198 | 16.10032 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.97140 | 31.68141 | -0.4494 | 9.77795 |
February | 454.00000 | 21.39776 | 32.09517 | -0.3170 | 8.28892 |
March | 514.00000 | 21.93184 | 31.75705 | -0.1541 | 6.77904 |
April | 485.00000 | 22.68771 | 34.30076 | 0.08546 | 7.23866 |
May | 508.00000 | 22.96276 | 39.04227 | -0.7614 | 21.17755 |
June | 496.00000 | 23.37731 | 40.71130 | -0.5626 | 15.01069 |
July | 497.00000 | 23.55370 | 45.55860 | -0.4577 | 12.66305 |
August | 514.00000 | 23.46594 | 49.58305 | -0.4486 | 12.60371 |
September | 485.00000 | 22.94558 | 47.65731 | -0.7143 | 19.90150 |
October | 502.00000 | 22.22598 | 39.44588 | -0.0281 | 6.72535 |
November | 489.00000 | 21.51863 | 38.40507 | -0.2431 | 7.13129 |
December | 497.00000 | 21.15115 | 32.85686 | -0.3893 | 8.51064 |
Annual Sum or Average | 5943.00000 | 22.35696 | 38.63611 | -0.3709 | 11.33898 |
Minimum of Months | 454.00000 | 20.97140 | 31.68141 | -0.7614 | 6.72535 |
Maximum of Months | 514.00000 | 23.55370 | 49.58305 | 0.08546 | 21.17755 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.22293 | 31.36489 | -0.3875 | 10.31684 |
February | 454.00000 | 21.85891 | 31.39251 | -0.1943 | 9.24260 |
March | 514.00000 | 22.22849 | 31.23404 | -0.0671 | 7.88353 |
April | 485.00000 | 22.78645 | 34.06613 | 0.11332 | 8.08356 |
May | 508.00000 | 22.93504 | 39.07986 | -0.7785 | 22.33545 |
June | 496.00000 | 23.22724 | 41.14628 | -0.6469 | 17.18815 |
July | 497.00000 | 23.56381 | 45.49799 | -0.4650 | 12.99861 |
August | 514.00000 | 23.53288 | 49.37493 | -0.4218 | 12.47567 |
September | 485.00000 | 23.14323 | 47.03608 | -0.6114 | 18.37637 |
October | 502.00000 | 22.60199 | 38.59270 | 0.08370 | 8.25687 |
November | 489.00000 | 21.82925 | 37.80880 | -0.1662 | 8.08704 |
December | 497.00000 | 21.51196 | 32.30804 | -0.2945 | 9.11971 |
Annual Sum or Average | 5943.00000 | 22.54252 | 38.29004 | -0.3212 | 12.05400 |
Minimum of Months | 454.00000 | 21.22293 | 31.23404 | -0.7785 | 7.88353 |
Maximum of Months | 514.00000 | 23.56381 | 49.37493 | 0.11332 | 22.33545 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.31421 | 30.99585 | -0.3293 | 7.84642 |
February | 454.00000 | 21.78683 | 31.26499 | -0.1827 | 7.42891 |
March | 514.00000 | 22.49112 | 30.58661 | 0.02151 | 6.59213 |
April | 485.00000 | 23.33764 | 32.89364 | 0.28380 | 8.95555 |
May | 508.00000 | 23.22500 | 38.34702 | -0.6176 | 17.64554 |
June | 496.00000 | 23.55413 | 40.23503 | -0.4586 | 12.48941 |
July | 497.00000 | 24.12385 | 43.93196 | -0.1726 | 8.94734 |
August | 514.00000 | 24.09552 | 47.68729 | -0.1460 | 8.20311 |
September | 485.00000 | 23.29212 | 46.57240 | -0.5421 | 15.46724 |
October | 502.00000 | 22.62060 | 38.41869 | 0.10076 | 6.99765 |
November | 489.00000 | 22.18690 | 36.81988 | -0.0421 | 6.52401 |
December | 497.00000 | 21.96785 | 31.25221 | -0.1378 | 6.31283 |
Annual Sum or Average | 5943.00000 | 22.84126 | 37.45962 | -0.1856 | 9.45776 |
Minimum of Months | 454.00000 | 21.31421 | 30.58661 | -0.6176 | 6.31283 |
Maximum of Months | 514.00000 | 24.12385 | 47.68729 | 0.28380 | 17.64554 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.26228 | 33.46407 | -0.6949 | 17.59260 |
February | 454.00000 | 20.62914 | 33.78983 | -0.5678 | 14.27000 |
March | 514.00000 | 21.33789 | 33.54476 | -0.3635 | 9.08703 |
April | 485.00000 | 22.07570 | 36.14756 | -0.1426 | 7.12668 |
May | 508.00000 | 22.77331 | 39.92268 | -0.9363 | 26.25385 |
June | 496.00000 | 23.28834 | 41.42527 | -0.7277 | 18.00459 |
July | 497.00000 | 23.52374 | 45.91049 | -0.6034 | 14.29495 |
August | 514.00000 | 23.45913 | 50.08034 | -0.5985 | 14.46951 |
September | 485.00000 | 22.74919 | 48.71128 | -0.8998 | 24.40199 |
October | 502.00000 | 21.66112 | 41.42419 | -0.2273 | 7.26740 |
November | 489.00000 | 20.90617 | 40.50125 | -0.4497 | 10.59455 |
December | 497.00000 | 20.47684 | 34.96554 | -0.6209 | 14.33444 |
Annual Sum or Average | 5943.00000 | 21.93979 | 40.03071 | -0.5697 | 14.81315 |
Minimum of Months | 454.00000 | 20.26228 | 33.46407 | -0.9363 | 7.12668 |
Maximum of Months | 514.00000 | 23.52374 | 50.08034 | -0.1426 | 26.25385 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.14120 | 32.78710 | -0.7223 | 18.46842 |
February | 385.00000 | 20.67274 | 32.88063 | -0.5446 | 13.24783 |
March | 433.00000 | 21.30133 | 32.86418 | -0.3419 | 9.09186 |
April | 410.00000 | 22.14440 | 35.22990 | -0.0723 | 7.67414 |
May | 430.00000 | 22.53150 | 39.80240 | -0.9327 | 28.15348 |
June | 418.00000 | 23.05760 | 41.47004 | -0.6909 | 19.71928 |
July | 422.00000 | 23.26623 | 45.99840 | -0.5818 | 16.90503 |
August | 433.00000 | 23.23082 | 50.08633 | -0.5583 | 16.28402 |
September | 410.00000 | 22.54043 | 48.61077 | -0.8803 | 26.08998 |
October | 427.00000 | 21.62352 | 40.86401 | -0.2048 | 7.65730 |
November | 417.00000 | 20.81025 | 39.80193 | -0.4665 | 10.92373 |
December | 422.00000 | 20.39468 | 34.28549 | -0.6375 | 14.89199 |
Annual Sum or Average | 5034.00000 | 21.81667 | 39.59615 | -0.5532 | 15.77460 |
Minimum of Months | 385.00000 | 20.14120 | 32.78710 | -0.9327 | 7.65730 |
Maximum of Months | 433.00000 | 23.26623 | 50.08633 | -0.0723 | 28.15348 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.75189 | 32.29796 | -0.5362 | 14.51948 |
February | 454.00000 | 21.50270 | 32.06763 | -0.2991 | 11.34067 |
March | 514.00000 | 21.88495 | 32.17261 | -0.1615 | 9.23389 |
April | 485.00000 | 22.40617 | 35.02896 | 0.01140 | 8.63114 |
May | 508.00000 | 22.63704 | 39.84805 | -0.8866 | 27.02028 |
June | 496.00000 | 22.87197 | 42.07934 | -0.7759 | 21.94746 |
July | 497.00000 | 23.22563 | 46.40272 | -0.5939 | 17.32359 |
August | 514.00000 | 23.22934 | 50.40130 | -0.5411 | 16.51170 |
September | 485.00000 | 22.89269 | 47.78875 | -0.6969 | 22.04303 |
October | 502.00000 | 22.29342 | 39.45012 | 0.00351 | 8.93584 |
November | 489.00000 | 21.39791 | 38.98514 | -0.2942 | 9.89216 |
December | 497.00000 | 21.04422 | 33.47255 | -0.4402 | 12.34526 |
Annual Sum or Average | 5943.00000 | 22.18399 | 39.21617 | -0.4358 | 15.01403 |
Minimum of Months | 454.00000 | 20.75189 | 32.06763 | -0.8866 | 8.63114 |
Maximum of Months | 514.00000 | 23.22934 | 50.40130 | 0.01140 | 27.02028 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.38790 | 32.73056 | -0.6412 | 15.71196 |
February | 454.00000 | 20.84804 | 32.99089 | -0.4820 | 12.18816 |
March | 514.00000 | 21.37267 | 32.96946 | -0.3078 | 8.75082 |
April | 485.00000 | 22.03959 | 35.75004 | -0.0804 | 7.95449 |
May | 508.00000 | 22.49408 | 40.15848 | -0.9095 | 28.14499 |
June | 496.00000 | 22.75255 | 42.32533 | -0.7763 | 22.28874 |
July | 497.00000 | 23.28194 | 46.21096 | -0.5225 | 16.57495 |
August | 514.00000 | 23.10706 | 50.78723 | -0.5648 | 17.12376 |
September | 485.00000 | 22.53682 | 48.80986 | -0.8427 | 25.32805 |
October | 502.00000 | 21.61331 | 40.94210 | -0.1893 | 7.47074 |
November | 489.00000 | 20.96437 | 39.80610 | -0.4119 | 9.72922 |
December | 497.00000 | 20.65215 | 34.02397 | -0.5543 | 12.56558 |
Annual Sum or Average | 5943.00000 | 21.84601 | 39.83844 | -0.5242 | 15.34680 |
Minimum of Months | 454.00000 | 20.38790 | 32.73056 | -0.9095 | 7.47074 |
Maximum of Months | 514.00000 | 23.28194 | 50.78723 | -0.0804 | 28.14499 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.95829 | 34.05417 | -0.8325 | 22.76637 |
February | 454.00000 | 20.18724 | 34.65666 | -0.7312 | 19.48973 |
March | 514.00000 | 20.69688 | 34.66252 | -0.5548 | 13.58480 |
April | 485.00000 | 21.40527 | 37.41958 | -0.3168 | 9.49105 |
May | 508.00000 | 22.09995 | 41.34023 | -1.1584 | 36.24878 |
June | 496.00000 | 22.71493 | 42.67815 | -0.8983 | 25.19766 |
July | 497.00000 | 23.02395 | 47.15263 | -0.7430 | 20.01566 |
August | 514.00000 | 22.92930 | 51.62491 | -0.7526 | 20.47445 |
September | 485.00000 | 21.99449 | 50.73006 | -1.1554 | 35.78735 |
October | 502.00000 | 20.87881 | 43.22395 | -0.4454 | 10.91028 |
November | 489.00000 | 20.26165 | 42.19243 | -0.6587 | 16.89727 |
December | 497.00000 | 19.98510 | 36.37711 | -0.8081 | 21.56397 |
Annual Sum or Average | 5943.00000 | 21.35534 | 41.38442 | -0.7549 | 21.04337 |
Minimum of Months | 454.00000 | 19.95829 | 34.05417 | -1.1584 | 9.49105 |
Maximum of Months | 514.00000 | 23.02395 | 51.62491 | -0.3168 | 36.24878 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.95552 | 33.84142 | -0.8227 | 22.46573 |
February | 454.00000 | 20.25999 | 34.32689 | -0.6880 | 17.88736 |
March | 514.00000 | 20.86195 | 34.18602 | -0.4799 | 12.43344 |
April | 485.00000 | 21.83863 | 36.33477 | -0.1590 | 9.10227 |
May | 508.00000 | 22.33616 | 40.59578 | -1.0058 | 31.72365 |
June | 496.00000 | 23.00534 | 41.67207 | -0.7020 | 20.79962 |
July | 497.00000 | 23.20735 | 46.44769 | -0.5832 | 17.76388 |
August | 514.00000 | 23.12290 | 50.74623 | -0.5775 | 17.53948 |
September | 485.00000 | 22.28619 | 49.62530 | -0.9827 | 31.06047 |
October | 502.00000 | 21.13752 | 42.35513 | -0.3533 | 10.09632 |
November | 489.00000 | 20.30941 | 41.80944 | -0.6370 | 16.22316 |
December | 497.00000 | 20.00685 | 36.10405 | -0.7918 | 21.01169 |
Annual Sum or Average | 5943.00000 | 21.53823 | 40.71108 | -0.6485 | 19.01209 |
Minimum of Months | 454.00000 | 19.95552 | 33.84142 | -1.0058 | 9.10227 |
Maximum of Months | 514.00000 | 23.20735 | 50.74623 | -0.1590 | 31.72365 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.24843 | 33.31478 | -0.7096 | 19.67653 |
February | 454.00000 | 20.96065 | 33.11806 | -0.4791 | 14.92451 |
March | 514.00000 | 21.38910 | 33.23740 | -0.3223 | 12.31309 |
April | 485.00000 | 21.98179 | 36.00238 | -0.1144 | 10.17871 |
May | 508.00000 | 22.28147 | 40.69465 | -1.0235 | 33.38544 |
June | 496.00000 | 22.63735 | 42.63942 | -0.8558 | 25.91773 |
July | 497.00000 | 23.01481 | 46.96052 | -0.6559 | 20.55389 |
August | 514.00000 | 22.96484 | 51.25538 | -0.6240 | 20.16950 |
September | 485.00000 | 22.51310 | 48.90735 | -0.8501 | 28.77707 |
October | 502.00000 | 21.75428 | 40.86407 | -0.1654 | 10.62806 |
November | 489.00000 | 20.78159 | 40.68820 | -0.4953 | 14.49819 |
December | 497.00000 | 20.44628 | 35.27642 | -0.6440 | 18.42294 |
Annual Sum or Average | 5943.00000 | 21.75482 | 40.29517 | -0.5794 | 19.15772 |
Minimum of Months | 454.00000 | 20.24843 | 33.11806 | -1.0235 | 10.17871 |
Maximum of Months | 514.00000 | 23.01481 | 51.25538 | -0.1144 | 33.38544 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.06878 | 33.51291 | -0.7674 | 20.46763 |
February | 454.00000 | 20.49417 | 33.78052 | -0.6126 | 16.10351 |
March | 514.00000 | 21.02221 | 33.74468 | -0.4298 | 11.63391 |
April | 485.00000 | 21.72838 | 36.47225 | -0.1766 | 9.39089 |
May | 508.00000 | 22.20640 | 40.83290 | -1.0198 | 33.67338 |
June | 496.00000 | 22.55071 | 42.80677 | -0.8431 | 25.72745 |
July | 497.00000 | 23.07811 | 46.75213 | -0.5800 | 19.47503 |
August | 514.00000 | 22.86176 | 51.58342 | -0.6393 | 20.45643 |
September | 485.00000 | 22.22001 | 49.73894 | -0.9702 | 31.20872 |
October | 502.00000 | 21.23875 | 41.96658 | -0.3159 | 9.47654 |
November | 489.00000 | 20.53740 | 41.12131 | -0.5621 | 14.04729 |
December | 497.00000 | 20.20176 | 35.54804 | -0.7146 | 18.26052 |
Annual Sum or Average | 5943.00000 | 21.52632 | 40.70081 | -0.6364 | 19.18539 |
Minimum of Months | 454.00000 | 20.06878 | 33.51291 | -1.0198 | 9.39089 |
Maximum of Months | 514.00000 | 23.07811 | 51.58342 | -0.1766 | 33.67338 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.202886E+10 | 84937.55 | 26-JAN-15:44 | 81.53 | 0.906694E+10 | 0.00 | 0.110958E+11 | 0.49 | 4.51 | 20-JAN-21:20 | 0.00 | 0.00 |
February | 0.376059E+11 | 176136.83 | 27-FEB-15:00 | 215.37 | 0.171703E+12 | 0.00 | 0.209309E+12 | 1.45 | 7.01 | 27-FEB-15:00 | 0.00 | 0.00 |
March | 0.631470E+11 | 150002.10 | 18-MAR-12:04 | 653.14 | 0.305750E+12 | 0.00 | 0.368897E+12 | 4.20 | 6.93 | 18-MAR-12:04 | 0.00 | 0.00 |
April | 0.832068E+11 | 221683.67 | 26-APR-16:20 | 654.18 | 0.425708E+12 | 0.00 | 0.508915E+12 | 4.40 | 7.01 | 01-APR-14:55 | 0.00 | 0.00 |
May | 0.483384E+11 | 220150.73 | 05-MAY-15:10 | 236.17 | 0.265764E+12 | 0.00 | 0.314103E+12 | 1.58 | 7.02 | 04-MAY-14:05 | 0.00 | 0.00 |
June | 0.107122E+12 | 224521.09 | 20-JUN-16:20 | 370.49 | 0.600233E+12 | 0.00 | 0.707355E+12 | 2.68 | 7.16 | 28-JUN-13:00 | 0.00 | 0.00 |
July | 0.166179E+12 | 225086.00 | 21-JUL-15:30 | 691.50 | 0.975807E+12 | 0.00 | 0.114199E+13 | 4.90 | 7.10 | 07-JUL-11:05 | 0.00 | 0.00 |
August | 0.189663E+12 | 228046.33 | 28-AUG-12:20 | 688.72 | 0.114699E+13 | 0.00 | 0.133665E+13 | 5.02 | 7.05 | 13-AUG-09:42 | 0.00 | 0.00 |
September | 0.696202E+11 | 221295.38 | 15-SEP-15:40 | 292.24 | 0.390542E+12 | 0.00 | 0.460162E+12 | 2.07 | 7.11 | 13-SEP-16:20 | 0.00 | 0.00 |
October | 0.488215E+11 | 163200.96 | 04-OCT-12:45 | 253.47 | 0.235384E+12 | 0.00 | 0.284205E+12 | 1.59 | 6.98 | 04-OCT-12:45 | 0.00 | 0.00 |
November | 0.556268E+11 | 145082.68 | 02-NOV-13:23 | 644.82 | 0.268005E+12 | 0.00 | 0.323632E+12 | 4.28 | 6.86 | 02-NOV-13:23 | 0.00 | 0.00 |
December | 0.598770E+11 | 117974.28 | 21-DEC-08:47 | 656.56 | 0.284569E+12 | 0.00 | 0.344446E+12 | 4.21 | 6.25 | 21-DEC-08:47 | 0.00 | 0.00 |
Annual Sum or Average | 0.931236E+12 | 5438.20 | 0.507952E+13 | 0.00 | 0.601076E+13 | 3.08 | 0.00 | 0.00 | ||||
Minimum of Months | 0.202886E+10 | 84937.55 | 81.53 | 0.906694E+10 | 0.00 | 0.110958E+11 | 0.49 | 4.51 | 0.00 | 0.00 | ||
Maximum of Months | 0.189663E+12 | 228046.33 | 691.50 | 0.114699E+13 | 0.00 | 0.133665E+13 | 5.02 | 7.16 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.383727E+10 | 150572.73 | 26-APR-13:55 | 7.92 | 0.255888E+11 | 0.00 | 0.294260E+11 | 0.07 | 6.91 | 26-APR-13:55 | 0.00 | 0.00 |
May | 0.958253E+09 | 130364.80 | 04-MAY-14:50 | 2.25 | 0.615708E+10 | 0.00 | 0.711534E+10 | 0.02 | 6.59 | 04-MAY-14:00 | 0.00 | 0.00 |
June | 0.482985E+10 | 160933.66 | 27-JUN-14:05 | 11.75 | 0.313188E+11 | 0.00 | 0.361486E+11 | 0.10 | 6.97 | 27-JUN-14:05 | 0.00 | 0.00 |
July | 0.170428E+11 | 162242.26 | 27-JUL-14:05 | 35.75 | 0.112055E+12 | 0.00 | 0.129097E+12 | 0.31 | 6.91 | 27-JUL-14:05 | 0.00 | 0.00 |
August | 0.470774E+11 | 179397.44 | 29-AUG-14:30 | 92.75 | 0.312778E+12 | 0.00 | 0.359856E+12 | 0.82 | 6.89 | 14-AUG-16:00 | 0.00 | 0.00 |
September | 0.379600E+10 | 155042.45 | 12-SEP-14:05 | 9.00 | 0.245343E+11 | 0.00 | 0.283303E+11 | 0.08 | 6.91 | 12-SEP-14:05 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.775416E+11 | 159.42 | 0.512432E+12 | 0.00 | 0.589973E+12 | 0.12 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.470774E+11 | 179397.44 | 92.75 | 0.312778E+12 | 0.00 | 0.359856E+12 | 0.82 | 6.97 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 16412.45 | 0.27 | 25.16 | 26-JAN-16:04 | 326202.97 | 26-JAN-16:04 | 21.05 | 21.03 | 2.67 |
February | 0.106089E+09 | 148.52 | 7674.65 | 27-FEB-15:02 | 1349956.32 | 27-FEB-15:02 | 21.93 | 21.63 | 24.12 |
March | 0.107343E+09 | 112.99 | 5053.56 | 10-MAR-13:04 | 1040306.35 | 18-MAR-12:06 | 21.42 | 20.92 | 54.00 |
April | 0.147769E+10 | 313.97 | 23836.14 | 27-APR-11:45 | 1772922.84 | 26-APR-16:30 | 21.70 | 21.01 | 62.19 |
May | 0.225853E+10 | 156.57 | 23836.14 | 04-MAY-14:30 | 1706231.51 | 05-MAY-15:10 | 21.60 | 21.20 | 21.36 |
June | 0.474731E+10 | 356.00 | 23836.14 | 20-JUN-12:50 | 1730824.12 | 22-JUN-15:30 | 22.48 | 21.59 | 39.82 |
July | 0.122973E+11 | 522.35 | 23836.14 | 07-JUL-11:50 | 1729673.12 | 25-JUL-15:10 | 22.57 | 21.17 | 70.68 |
August | 0.180294E+11 | 586.39 | 23836.14 | 07-AUG-10:00 | 1737384.30 | 12-AUG-14:30 | 22.93 | 21.29 | 70.26 |
September | 0.475222E+10 | 228.71 | 23836.14 | 11-SEP-14:20 | 1695821.60 | 22-SEP-15:00 | 21.86 | 21.28 | 29.18 |
October | 0.440404E+09 | 223.98 | 6443.78 | 04-OCT-15:00 | 1302168.80 | 04-OCT-15:00 | 22.04 | 21.69 | 26.03 |
November | 0.224934E+09 | 92.28 | 9979.88 | 04-NOV-12:08 | 1050760.43 | 04-NOV-12:08 | 21.35 | 20.90 | 55.66 |
December | 5384422.75 | 103.38 | 85.94 | 16-DEC-07:40 | 691310.19 | 21-DEC-08:48 | 21.35 | 20.87 | 52.37 |
Annual Sum or Average | 0.444466E+11 | 2845.41 | 21.86 | 21.21 | 42.46 | ||||
Minimum of Months | 16412.45 | 0.27 | 25.16 | 326202.97 | 21.05 | 20.87 | 2.67 | ||
Maximum of Months | 0.180294E+11 | 586.39 | 23836.14 | 1772922.84 | 22.93 | 21.69 | 70.68 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 21.05 | 21.05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 21.93 | 21.93 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 21.42 | 21.42 | 0.00 |
April | 0.502241E+09 | 6.83 | 23836.14 | 27-APR-12:30 | 1547020.24 | 26-APR-15:20 | 21.70 | 21.66 | 0.74 |
May | 74100053.73 | 1.17 | 23836.14 | 05-MAY-13:50 | 1461591.10 | 04-MAY-14:50 | 21.60 | 21.59 | 0.12 |
June | 0.547910E+09 | 8.42 | 23836.14 | 28-JUN-15:30 | 1557794.22 | 22-JUN-15:50 | 22.48 | 22.43 | 0.91 |
July | 0.252758E+10 | 30.17 | 23836.14 | 07-JUL-12:30 | 1548564.76 | 07-JUL-15:00 | 22.57 | 22.42 | 3.13 |
August | 0.690989E+10 | 81.92 | 23836.14 | 07-AUG-10:50 | 1567084.95 | 15-AUG-13:00 | 22.93 | 22.51 | 8.53 |
September | 0.585400E+09 | 6.92 | 23836.14 | 12-SEP-13:40 | 1421341.56 | 12-SEP-13:40 | 21.86 | 21.83 | 0.74 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 22.04 | 22.04 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 21.35 | 21.35 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.35 | 21.35 | 0.00 |
Annual Sum or Average | 0.111471E+11 | 135.42 | 21.86 | 21.80 | 1.20 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.05 | 21.05 | 0.00 | ||
Maximum of Months | 0.690989E+10 | 81.92 | 23836.14 | 1567084.95 | 22.93 | 22.51 | 8.53 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.310644E+12 | 0.00 | 518.92 | 2172348.17 | 02-JAN-05:11 | 0.00 | 29.69 | 58.62 | 0.74 | 0.00 | 0.05 | 0.85 | 02-JAN-05:11 |
February | 0.191065E+12 | 0.00 | 416.95 | 1976867.79 | 18-FEB-05:01 | 0.00 | 28.14 | 54.17 | 0.48 | 0.00 | 0.03 | 0.77 | 18-FEB-05:01 |
March | 0.109816E+12 | 0.00 | 365.50 | 2164032.92 | 27-MAR-04:11 | 0.00 | 24.54 | 45.45 | 0.25 | 0.00 | 0.02 | 0.84 | 27-MAR-04:11 |
April | 0.526254E+11 | 0.00 | 227.59 | 2000289.46 | 19-APR-04:11 | 0.00 | 23.70 | 37.01 | 0.12 | 0.00 | 0.01 | 0.78 | 19-APR-04:11 |
May | 0.251407E+11 | 0.00 | 158.76 | 1644999.79 | 11-MAY-05:01 | 0.00 | 22.59 | 31.67 | 0.05 | 0.00 | 0.00 | 0.64 | 11-MAY-05:01 |
June | 0.854067E+10 | 0.00 | 99.27 | 718990.88 | 14-JUN-05:01 | 0.00 | 21.37 | 27.39 | 0.02 | 0.00 | 0.00 | 0.28 | 14-JUN-05:01 |
July | 0.230274E+10 | 0.00 | 63.68 | 158606.72 | 12-JUL-09:53 | 0.00 | 19.92 | 23.82 | 0.00 | 0.00 | 0.00 | 0.06 | 12-JUL-09:53 |
August | 0.359620E+10 | 0.00 | 73.16 | 231301.91 | 01-AUG-09:03 | 0.00 | 20.83 | 25.22 | 0.01 | 0.00 | 0.00 | 0.09 | 01-AUG-09:03 |
September | 0.171789E+11 | 0.00 | 161.80 | 492847.06 | 27-SEP-05:03 | 0.00 | 21.61 | 31.37 | 0.04 | 0.00 | 0.00 | 0.19 | 27-SEP-05:03 |
October | 0.702771E+11 | 0.00 | 310.79 | 1735296.99 | 24-OCT-05:01 | 0.00 | 23.30 | 40.79 | 0.16 | 0.00 | 0.01 | 0.68 | 24-OCT-05:01 |
November | 0.151510E+12 | 0.00 | 416.07 | 1853465.60 | 14-NOV-05:11 | 0.00 | 25.82 | 50.46 | 0.36 | 0.00 | 0.02 | 0.72 | 14-NOV-05:11 |
December | 0.241097E+12 | 0.00 | 461.01 | 2040328.33 | 04-DEC-05:11 | 0.00 | 28.47 | 54.46 | 0.56 | 0.00 | 0.04 | 0.80 | 04-DEC-05:11 |
Annual Sum or Average | 0.118379E+13 | 0.00 | 3273.49 | 0.00 | 24.14 | 39.96 | 0.23 | 0.00 | 0.01 | ||||
Minimum of Months | 0.230274E+10 | 0.00 | 63.68 | 158606.72 | 0.00 | 19.92 | 23.82 | 0.00 | 0.00 | 0.00 | 0.06 | ||
Maximum of Months | 0.310644E+12 | 0.00 | 518.92 | 2172348.17 | 0.00 | 29.69 | 58.62 | 0.74 | 0.00 | 0.05 | 0.85 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2878.24 | 0.00 | 1.69 | 2878.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 11-JAN-14:20 | 0.50 | 11-JAN-14:20 | 0.00 | 0.00 | 0.00 |
February | 0.907003E+09 | 0.00 | 10.87 | 0.907003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59022.03 | 27-FEB-15:00 | 59022.03 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.139777E+10 | 0.00 | 32.12 | 0.139777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35722.09 | 18-MAR-16:00 | 35722.09 | 18-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.118424E+11 | 0.00 | 96.05 | 0.118424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138912.63 | 27-APR-14:40 | 138912.63 | 27-APR-14:40 | 0.00 | 0.00 | 0.00 |
May | 0.203770E+11 | 0.00 | 191.81 | 0.203724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118710.39 | 04-MAY-15:00 | 118710.39 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.381580E+11 | 0.00 | 300.09 | 0.381528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 127872.94 | 28-JUN-15:30 | 127872.94 | 28-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.688980E+11 | 0.00 | 394.12 | 0.679914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158863.06 | 31-JUL-14:40 | 148469.35 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.936130E+11 | 0.00 | 431.13 | 0.910588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 173405.15 | 29-AUG-14:30 | 161592.88 | 29-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.317552E+11 | 0.00 | 255.35 | 0.312821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135886.27 | 14-SEP-14:00 | 126640.49 | 12-SEP-15:00 | 0.00 | 0.00 | 0.00 |
October | 0.546546E+10 | 0.00 | 79.40 | 0.546546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88056.91 | 04-OCT-15:00 | 88056.91 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.874412E+09 | 0.00 | 12.72 | 0.874412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45340.58 | 04-NOV-14:00 | 45340.58 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 1232.84 | 0.00 | 0.84 | 1232.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 | 07-DEC-12:45 | 0.58 | 07-DEC-12:45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.273288E+12 | 0.00 | 1806.18 | 0.269345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1232.84 | 0.00 | 0.84 | 1232.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 0.50 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.936130E+11 | 0.00 | 431.13 | 0.910588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 173405.15 | 161592.88 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 193866.98 | 0.00 | 79.68 | 193866.98 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 | 31-JAN-06:03 | 5.32 | 31-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.109231E+11 | 0.00 | 52.02 | 0.109231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 715360.02 | 27-FEB-15:02 | 715360.02 | 27-FEB-15:02 | 0.00 | 0.00 | 0.00 |
March | 0.343017E+11 | 0.00 | 72.49 | 0.343017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 668377.02 | 01-MAR-15:01 | 668377.02 | 01-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.107256E+12 | 0.00 | 114.36 | 0.107256E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1233172.33 | 27-APR-14:50 | 1233172.33 | 27-APR-14:50 | 0.00 | 0.00 | 0.00 |
May | 0.195048E+12 | 0.00 | 203.57 | 0.195013E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1125571.91 | 04-MAY-15:00 | 1125571.91 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.345768E+12 | 0.00 | 300.95 | 0.345729E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1185527.94 | 28-JUN-15:40 | 1185527.94 | 28-JUN-15:40 | 0.00 | 0.00 | 0.00 |
July | 0.585647E+12 | 0.00 | 381.90 | 0.578571E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1401435.68 | 31-JUL-14:05 | 1298179.85 | 31-JUL-16:00 | 0.00 | 0.00 | 0.00 |
August | 0.766382E+12 | 0.00 | 402.69 | 0.746480E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1551499.42 | 29-AUG-14:30 | 1450961.34 | 10-AUG-15:50 | 0.00 | 0.00 | 0.00 |
September | 0.303243E+12 | 0.00 | 259.72 | 0.298720E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1291909.73 | 14-SEP-14:05 | 1218230.40 | 14-SEP-14:05 | 0.00 | 0.00 | 0.00 |
October | 0.592120E+11 | 0.00 | 91.49 | 0.592120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 946642.76 | 04-OCT-13:13 | 946642.76 | 04-OCT-13:13 | 0.00 | 0.00 | 0.00 |
November | 0.123937E+11 | 0.00 | 91.91 | 0.123937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 497670.83 | 02-NOV-14:01 | 497670.83 | 02-NOV-14:01 | 0.00 | 0.00 | 0.00 |
December | 5545840.15 | 0.00 | 92.39 | 5545840.15 | 0.00 | 0.00 | 0.00 | 0.00 | 35342.90 | 06-DEC-17:03 | 35342.90 | 06-DEC-17:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242018E+13 | 0.00 | 2143.15 | 0.238860E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 193866.98 | 0.00 | 52.02 | 193866.98 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 | 5.32 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.766382E+12 | 0.00 | 402.69 | 0.746480E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1551499.42 | 1450961.34 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 4133138.14 | 0.00 | 4.04 | 4133138.14 | 0.00 | 0.00 | 0.00 | 0.00 | 1695.32 | 07-JAN-22:20 | 1695.32 | 07-JAN-22:20 | 0.00 | 0.00 | 0.00 |
February | 0.648557E+09 | 0.00 | 12.97 | 0.648557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40576.83 | 27-FEB-15:00 | 40576.83 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.110534E+10 | 0.00 | 28.45 | 0.110534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36791.48 | 18-MAR-14:00 | 36791.48 | 18-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.110401E+11 | 0.00 | 86.49 | 0.110401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 156835.28 | 27-APR-14:40 | 156835.28 | 27-APR-14:40 | 0.00 | 0.00 | 0.00 |
May | 0.202657E+11 | 0.00 | 181.45 | 0.202617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149472.21 | 04-MAY-15:00 | 149472.21 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.378000E+11 | 0.00 | 285.25 | 0.377990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 156654.53 | 28-JUN-15:20 | 156654.53 | 28-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.660235E+11 | 0.00 | 368.56 | 0.653333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 181212.51 | 31-JUL-14:40 | 171684.67 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.857102E+11 | 0.00 | 387.92 | 0.837903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 191275.08 | 10-AUG-14:40 | 184242.39 | 10-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.297430E+11 | 0.00 | 242.69 | 0.294009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153254.37 | 14-SEP-14:00 | 144885.20 | 14-SEP-14:50 | 0.00 | 0.00 | 0.00 |
October | 0.428511E+10 | 0.00 | 70.85 | 0.428511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81994.98 | 04-OCT-15:00 | 81994.98 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.847179E+09 | 0.00 | 11.73 | 0.847179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46770.39 | 04-NOV-14:00 | 46770.39 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 701859.22 | 0.00 | 2.20 | 701859.22 | 0.00 | 0.00 | 0.00 | 0.00 | 1358.07 | 11-DEC-05:11 | 1358.07 | 11-DEC-05:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.257474E+12 | 0.00 | 1682.59 | 0.254516E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 701859.22 | 0.00 | 2.20 | 701859.22 | 0.00 | 0.00 | 0.00 | 0.00 | 1358.07 | 1358.07 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.857102E+11 | 0.00 | 387.92 | 0.837903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 191275.08 | 184242.39 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.630730E+10 | 0.00 | 56.75 | 0.623053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119171.61 | 05-JAN-05:05 | 119171.61 | 05-JAN-05:05 | 0.00 | 0.00 | 0.00 |
February | 0.665979E+10 | 0.00 | 71.95 | 0.624601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 124026.46 | 15-FEB-05:47 | 124026.46 | 15-FEB-05:47 | 0.00 | 0.00 | 0.00 |
March | 0.731741E+10 | 0.00 | 119.01 | 0.724497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 117423.86 | 01-MAR-05:44 | 117423.86 | 01-MAR-05:44 | 0.00 | 0.00 | 0.00 |
April | 0.125529E+11 | 0.00 | 162.74 | 0.123445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106213.73 | 01-APR-05:00 | 106213.73 | 01-APR-05:00 | 0.00 | 0.00 | 0.00 |
May | 0.211410E+11 | 0.00 | 225.22 | 0.201567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74846.14 | 25-MAY-04:55 | 65147.07 | 25-MAY-04:55 | 0.00 | 0.00 | 0.00 |
June | 0.286139E+11 | 0.00 | 305.48 | 0.275897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75278.46 | 12-JUN-04:11 | 65011.48 | 07-JUN-09:01 | 0.00 | 0.00 | 0.00 |
July | 0.416940E+11 | 0.00 | 333.28 | 0.374608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 101521.70 | 11-JUL-09:32 | 72123.91 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.564131E+11 | 0.00 | 388.28 | 0.487751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106104.14 | 14-AUG-02:39 | 106104.14 | 14-AUG-02:39 | 0.00 | 0.00 | 0.00 |
September | 0.303734E+11 | 0.00 | 295.88 | 0.252842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110203.88 | 04-SEP-15:30 | 109805.02 | 04-SEP-15:30 | 0.00 | 0.00 | 0.00 |
October | 0.162320E+11 | 0.00 | 179.51 | 0.153641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122029.13 | 09-OCT-11:09 | 122029.13 | 09-OCT-11:09 | 0.00 | 0.00 | 0.00 |
November | 0.788016E+10 | 0.00 | 132.23 | 0.750640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67432.68 | 04-NOV-10:34 | 51566.30 | 02-NOV-11:41 | 0.00 | 0.00 | 0.00 |
December | 0.572481E+10 | 0.00 | 97.51 | 0.572481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107444.39 | 30-DEC-05:58 | 107444.39 | 30-DEC-05:58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.240910E+12 | 0.00 | 2367.84 | 0.219928E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.572481E+10 | 0.00 | 56.75 | 0.572481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67432.68 | 51566.30 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.564131E+11 | 0.00 | 388.28 | 0.487751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124026.46 | 124026.46 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3898644.71 | 0.00 | 296.89 | 3898644.71 | 0.00 | 0.00 | 0.00 | 0.00 | 37.95 | 18-JAN-05:02 | 37.95 | 18-JAN-05:02 | 0.00 | 0.00 | 0.00 |
February | 0.144747E+12 | 0.00 | 372.85 | 0.143477E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 319051.86 | 27-FEB-15:00 | 319051.86 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.237788E+12 | 0.00 | 722.73 | 0.237706E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 300383.92 | 14-MAR-16:01 | 300383.92 | 14-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.281601E+12 | 0.00 | 719.89 | 0.280927E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 424017.51 | 01-APR-17:01 | 424017.51 | 01-APR-17:01 | 0.00 | 0.00 | 0.00 |
May | 0.472313E+10 | 0.00 | 239.26 | 0.472313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 210884.78 | 31-MAY-23:55 | 210884.78 | 31-MAY-23:55 | 0.00 | 0.00 | 0.00 |
June | 0.160505E+12 | 0.00 | 360.16 | 0.154550E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 322791.89 | 21-JUN-11:50 | 321748.97 | 09-JUN-12:00 | 0.00 | 0.00 | 0.00 |
July | 0.284671E+12 | 0.00 | 735.93 | 0.273930E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 400586.28 | 11-JUL-09:46 | 300245.50 | 23-JUL-18:04 | 0.00 | 0.00 | 0.00 |
August | 0.409190E+12 | 0.00 | 743.17 | 0.400521E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 496926.38 | 25-AUG-11:20 | 407206.67 | 12-AUG-16:01 | 0.00 | 0.00 | 0.00 |
September | 0.574634E+10 | 0.00 | 262.01 | 0.572910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 234906.15 | 30-SEP-23:55 | 228549.03 | 30-SEP-23:31 | 0.00 | 0.00 | 0.00 |
October | 0.141361E+12 | 0.00 | 320.91 | 0.137824E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 348892.00 | 01-OCT-11:41 | 337252.42 | 04-OCT-16:41 | 0.00 | 0.00 | 0.00 |
November | 0.222483E+12 | 0.00 | 718.13 | 0.219632E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 322955.42 | 04-NOV-11:47 | 256747.28 | 04-NOV-11:42 | 0.00 | 0.00 | 0.00 |
December | 0.254490E+12 | 0.00 | 744.00 | 0.254490E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 251842.73 | 11-DEC-05:20 | 251842.73 | 11-DEC-05:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214731E+13 | 0.00 | 6235.93 | 0.211351E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3898644.71 | 0.00 | 239.26 | 3898644.71 | 0.00 | 0.00 | 0.00 | 0.00 | 37.95 | 37.95 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.409190E+12 | 0.00 | 744.00 | 0.400521E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 496926.38 | 424017.51 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.568079E+10 | 0.175488E+10 | 744.00 | 0.568046E+10 | 327681.14 | 0.00 | 0.50 | 05-JAN-16:03 | 0.24 | 17-JAN-07:10 | 3065.38 | 05-JAN-16:10 | 3065.38 | 05-JAN-16:10 | 21.04 | 02-JAN-07:03 | 912.53 | 05-JAN-16:10 | 0.00 | 01-JAN-00:03 |
February | 0.998741E+10 | 0.283972E+10 | 672.00 | 0.998133E+10 | 6081287.20 | 0.00 | 0.78 | 27-FEB-16:11 | 0.54 | 18-FEB-18:00 | 5293.51 | 27-FEB-16:13 | 5293.51 | 27-FEB-16:13 | 109.62 | 24-FEB-10:51 | 1445.10 | 27-FEB-16:13 | 0.00 | 01-FEB-00:01 |
March | 0.167394E+11 | 0.440080E+10 | 744.00 | 0.167345E+11 | 4896062.39 | 0.00 | 1.00 | 01-MAR-16:11 | 0.81 | 01-MAR-07:01 | 8094.67 | 31-MAR-24:00 | 8094.67 | 31-MAR-24:00 | 117.67 | 09-MAR-17:00 | 2091.81 | 31-MAR-24:00 | 0.00 | 01-MAR-00:01 |
April | 0.215568E+11 | 0.560201E+10 | 720.00 | 0.215467E+11 | 10120322.97 | 0.00 | 1.00 | 01-APR-00:03 | 0.49 | 30-APR-24:00 | 9634.38 | 26-APR-18:00 | 9634.38 | 26-APR-18:00 | 152.08 | 28-APR-13:00 | 2693.85 | 27-APR-16:00 | 0.00 | 01-APR-00:03 |
May | 0.751112E+10 | 0.225933E+10 | 744.00 | 0.748755E+10 | 23565166.36 | 0.00 | 0.71 | 31-MAY-23:51 | 0.33 | 18-MAY-06:05 | 4746.21 | 31-MAY-23:51 | 4746.20 | 31-MAY-23:52 | 118.10 | 05-MAY-16:10 | 1322.14 | 31-MAY-23:51 | 0.00 | 01-MAY-00:10 |
June | 0.123772E+11 | 0.345309E+10 | 720.00 | 0.123457E+11 | 31480341.36 | 0.00 | 0.93 | 30-JUN-23:51 | 0.63 | 15-JUN-06:02 | 6601.64 | 30-JUN-23:51 | 6601.40 | 30-JUN-23:52 | 180.29 | 12-JUN-14:00 | 1719.36 | 30-JUN-23:51 | 0.00 | 01-JUN-00:02 |
July | 0.182962E+11 | 0.477247E+10 | 744.00 | 0.182160E+11 | 80172281.54 | 0.00 | 1.00 | 06-JUL-15:40 | 0.88 | 01-JUL-06:53 | 8680.76 | 31-JUL-24:00 | 8623.61 | 31-JUL-24:00 | 218.96 | 11-JUL-09:30 | 2284.39 | 30-JUL-18:11 | 0.00 | 01-JUL-00:01 |
August | 0.234246E+11 | 0.619070E+10 | 744.00 | 0.232884E+11 | 0.136148E+09 | 0.00 | 1.00 | 01-AUG-00:10 | 0.52 | 31-AUG-24:00 | 10061.58 | 10-AUG-18:30 | 9998.91 | 06-AUG-18:40 | 263.74 | 30-AUG-09:10 | 3075.81 | 10-AUG-18:30 | 0.00 | 01-AUG-00:10 |
September | 0.750547E+10 | 0.224824E+10 | 720.00 | 0.743612E+10 | 69349321.72 | 0.00 | 0.68 | 30-SEP-23:55 | 0.35 | 28-SEP-06:05 | 4497.44 | 30-SEP-23:55 | 4497.44 | 30-SEP-23:55 | 181.81 | 14-SEP-11:00 | 1264.63 | 30-SEP-23:55 | 0.00 | 01-SEP-00:10 |
October | 0.119938E+11 | 0.337471E+10 | 744.00 | 0.119833E+11 | 10487673.64 | 0.00 | 0.88 | 31-OCT-23:53 | 0.59 | 28-OCT-06:51 | 6090.46 | 31-OCT-23:53 | 6090.46 | 31-OCT-23:53 | 123.46 | 26-OCT-13:51 | 1615.56 | 31-OCT-23:53 | 0.00 | 01-OCT-00:01 |
November | 0.160540E+11 | 0.423764E+10 | 720.00 | 0.160387E+11 | 15287108.31 | 0.00 | 0.97 | 04-NOV-16:00 | 0.82 | 25-NOV-17:51 | 7017.21 | 04-NOV-16:00 | 6955.98 | 04-NOV-16:00 | 147.05 | 03-NOV-16:00 | 1801.35 | 04-NOV-16:00 | 0.00 | 01-NOV-00:01 |
December | 0.212849E+11 | 0.549797E+10 | 744.00 | 0.212833E+11 | 1526940.73 | 0.00 | 1.00 | 01-DEC-00:10 | 1.00 | 01-DEC-00:10 | 8848.37 | 05-DEC-15:47 | 8848.37 | 05-DEC-15:47 | 60.38 | 28-DEC-16:12 | 2312.45 | 05-DEC-15:43 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.172412E+12 | 0.466316E+11 | 8760.00 | 0.172022E+12 | 0.389443E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.568079E+10 | 0.175488E+10 | 672.00 | 0.568046E+10 | 327681.14 | 0.00 | 0.50 | 0.24 | 3065.38 | 3065.38 | 21.04 | 912.53 | 0.00 | |||||||
Maximum of Months | 0.234246E+11 | 0.619070E+10 | 744.00 | 0.232884E+11 | 0.136148E+09 | 0.00 | 1.00 | 1.00 | 10061.58 | 9998.91 | 263.74 | 3075.81 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.344254E+11 | 0.935496E+10 | 711.41 | 0.344240E+11 | 1402203.17 | 0.00 | 0.46 | 05-JAN-16:03 | 0.00 | 01-JAN-00:03 | 26661.63 | 05-JAN-16:10 | 26661.63 | 05-JAN-16:10 | 203.58 | 02-JAN-09:43 | 6886.11 | 05-JAN-16:10 | 0.00 | 01-JAN-00:03 |
February | 0.830390E+11 | 0.206618E+11 | 672.00 | 0.829787E+11 | 60265862.27 | 0.00 | 0.77 | 27-FEB-16:11 | 0.37 | 20-FEB-07:50 | 50115.55 | 27-FEB-16:13 | 50115.55 | 27-FEB-16:13 | 1081.17 | 24-FEB-10:51 | 11765.35 | 27-FEB-16:13 | 0.00 | 01-FEB-00:01 |
March | 0.150714E+12 | 0.344515E+11 | 744.00 | 0.150665E+12 | 49100119.91 | 0.00 | 1.00 | 01-MAR-16:21 | 0.73 | 06-MAR-07:10 | 73566.95 | 31-MAR-23:25 | 73566.95 | 31-MAR-23:25 | 1169.90 | 09-MAR-17:00 | 16188.33 | 31-MAR-23:25 | 0.00 | 01-MAR-00:01 |
April | 0.199646E+12 | 0.442861E+11 | 720.00 | 0.199546E+12 | 99715584.92 | 0.00 | 1.00 | 01-APR-00:03 | 0.39 | 30-APR-24:00 | 92820.82 | 26-APR-18:00 | 92820.82 | 26-APR-18:00 | 1512.92 | 28-APR-13:00 | 22067.31 | 27-APR-16:00 | 0.00 | 01-APR-00:03 |
May | 0.652925E+11 | 0.170042E+11 | 744.00 | 0.650595E+11 | 0.233051E+09 | 0.00 | 0.70 | 31-MAY-23:21 | 0.25 | 18-MAY-06:05 | 44382.98 | 31-MAY-23:21 | 44380.79 | 31-MAY-23:22 | 1176.15 | 05-MAY-16:10 | 10652.08 | 31-MAY-23:21 | 0.00 | 01-MAY-00:10 |
June | 0.114197E+12 | 0.275065E+11 | 720.00 | 0.113883E+12 | 0.314051E+09 | 0.00 | 0.91 | 30-JUN-23:51 | 0.59 | 14-JUN-06:02 | 62172.28 | 30-JUN-23:51 | 62169.73 | 30-JUN-23:52 | 1793.98 | 12-JUN-14:00 | 13950.06 | 30-JUN-23:51 | 0.00 | 01-JUN-00:02 |
July | 0.171465E+12 | 0.385641E+11 | 744.00 | 0.170666E+12 | 0.799031E+09 | 0.00 | 1.00 | 06-JUL-16:00 | 0.85 | 01-JUL-06:53 | 83300.86 | 31-JUL-23:05 | 82499.96 | 31-JUL-23:40 | 2180.05 | 11-JUL-09:40 | 18538.73 | 30-JUL-18:21 | 0.00 | 01-JUL-00:01 |
August | 0.220541E+12 | 0.498481E+11 | 744.00 | 0.219192E+12 | 0.134843E+10 | 0.00 | 1.00 | 01-AUG-00:10 | 0.45 | 31-AUG-24:00 | 96979.54 | 10-AUG-18:30 | 96229.01 | 10-AUG-18:30 | 2621.91 | 30-AUG-09:10 | 25411.00 | 10-AUG-18:30 | 0.00 | 01-AUG-00:10 |
September | 0.653550E+11 | 0.169549E+11 | 720.00 | 0.646716E+11 | 0.683400E+09 | 0.00 | 0.65 | 30-SEP-23:23 | 0.29 | 27-SEP-06:05 | 40674.05 | 30-SEP-23:21 | 40674.05 | 30-SEP-23:21 | 1785.13 | 14-SEP-11:00 | 9905.69 | 30-SEP-23:23 | 0.00 | 01-SEP-00:10 |
October | 0.105600E+12 | 0.258305E+11 | 744.00 | 0.105495E+12 | 0.104904E+09 | 0.00 | 0.85 | 04-OCT-16:50 | 0.51 | 30-OCT-06:02 | 56388.24 | 04-OCT-16:50 | 56388.24 | 04-OCT-16:50 | 1219.52 | 26-OCT-13:51 | 12927.19 | 04-OCT-16:41 | 0.00 | 01-OCT-00:01 |
November | 0.141143E+12 | 0.325527E+11 | 720.00 | 0.140990E+12 | 0.152691E+09 | 0.00 | 0.95 | 10-NOV-15:51 | 0.72 | 13-NOV-07:01 | 65335.58 | 04-NOV-16:00 | 64722.67 | 04-NOV-16:00 | 1461.41 | 03-NOV-16:00 | 14492.11 | 04-NOV-16:00 | 0.00 | 01-NOV-00:01 |
December | 0.188096E+12 | 0.414014E+11 | 744.00 | 0.188082E+12 | 13714017.17 | 0.00 | 1.00 | 01-DEC-00:10 | 0.88 | 26-DEC-07:03 | 82499.95 | 05-DEC-15:53 | 82499.95 | 05-DEC-15:53 | 592.63 | 28-DEC-15:43 | 18420.92 | 05-DEC-15:53 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.153951E+13 | 0.358417E+12 | 8727.41 | 0.153565E+13 | 0.385975E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.344254E+11 | 0.935496E+10 | 672.00 | 0.344240E+11 | 1402203.17 | 0.00 | 0.46 | 0.00 | 26661.63 | 26661.63 | 203.58 | 6886.11 | 0.00 | |||||||
Maximum of Months | 0.220541E+12 | 0.498481E+11 | 744.00 | 0.219192E+12 | 0.134843E+10 | 0.00 | 1.00 | 0.88 | 96979.54 | 96229.01 | 2621.91 | 25411.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.188048E+10 | 0.603946E+09 | 540.42 | 0.188047E+10 | 3364.36 | 0.00 | 0.42 | 05-JAN-16:03 | 0.00 | 01-JAN-00:03 | 2514.75 | 05-JAN-16:10 | 2514.75 | 05-JAN-16:10 | 1.58 | 02-JAN-08:54 | 764.82 | 05-JAN-16:10 | 0.00 | 01-JAN-00:03 |
February | 0.653763E+10 | 0.194765E+10 | 671.74 | 0.653168E+10 | 5952031.07 | 0.00 | 0.75 | 27-FEB-16:11 | 0.00 | 12-FEB-03:21 | 5006.84 | 27-FEB-16:13 | 5006.84 | 27-FEB-16:13 | 107.77 | 24-FEB-10:51 | 1378.35 | 27-FEB-16:13 | 0.00 | 01-FEB-00:01 |
March | 0.135050E+11 | 0.369260E+10 | 744.00 | 0.135001E+11 | 4858911.81 | 0.00 | 1.00 | 01-MAR-16:51 | 0.49 | 06-MAR-04:53 | 7104.93 | 14-MAR-17:00 | 7104.93 | 14-MAR-17:00 | 116.57 | 09-MAR-17:00 | 1812.73 | 14-MAR-16:53 | 0.00 | 01-MAR-00:01 |
April | 0.189448E+11 | 0.490099E+10 | 720.00 | 0.189356E+11 | 9111394.05 | 0.00 | 1.00 | 01-APR-10:35 | 0.27 | 30-APR-24:00 | 9440.47 | 26-APR-18:00 | 9440.47 | 26-APR-18:00 | 151.74 | 28-APR-13:00 | 2634.40 | 27-APR-16:00 | 0.00 | 01-APR-00:03 |
May | 0.579683E+10 | 0.177691E+10 | 743.04 | 0.577361E+10 | 23223189.96 | 0.00 | 0.66 | 31-MAY-23:01 | 0.00 | 01-MAY-02:53 | 4279.64 | 31-MAY-23:01 | 4279.49 | 31-MAY-23:02 | 118.33 | 05-MAY-16:10 | 1211.01 | 31-MAY-23:01 | 0.00 | 01-MAY-00:10 |
June | 0.110693E+11 | 0.313720E+10 | 720.00 | 0.110380E+11 | 31325351.43 | 0.00 | 0.87 | 30-JUN-23:11 | 0.48 | 15-JUN-06:02 | 6059.79 | 30-JUN-23:11 | 6056.95 | 30-JUN-23:12 | 179.49 | 12-JUN-14:00 | 1604.78 | 28-JUN-16:00 | 0.00 | 01-JUN-00:02 |
July | 0.169199E+11 | 0.447833E+10 | 744.00 | 0.168401E+11 | 79850177.94 | 0.00 | 1.00 | 06-JUL-15:50 | 0.78 | 18-JUL-06:02 | 8263.09 | 31-JUL-23:05 | 8190.17 | 31-JUL-23:20 | 217.80 | 11-JUL-09:40 | 2254.60 | 30-JUL-18:11 | 0.00 | 01-JUL-00:01 |
August | 0.217856E+11 | 0.572481E+10 | 744.00 | 0.216519E+11 | 0.133695E+09 | 0.00 | 1.00 | 01-AUG-00:10 | 0.40 | 31-AUG-24:00 | 9885.99 | 10-AUG-18:30 | 9811.32 | 10-AUG-18:30 | 263.75 | 30-AUG-09:02 | 3021.99 | 10-AUG-18:20 | 0.00 | 01-AUG-00:10 |
September | 0.574269E+10 | 0.175802E+10 | 719.72 | 0.567495E+10 | 67742700.85 | 0.00 | 0.61 | 08-SEP-17:30 | 0.00 | 17-SEP-01:13 | 3860.70 | 08-SEP-17:30 | 3860.70 | 08-SEP-17:30 | 183.41 | 14-SEP-11:00 | 1134.29 | 14-SEP-17:00 | 0.00 | 01-SEP-00:10 |
October | 0.908061E+10 | 0.265110E+10 | 744.00 | 0.907032E+10 | 10292228.04 | 0.00 | 0.85 | 04-OCT-16:50 | 0.31 | 16-OCT-04:11 | 5718.50 | 04-OCT-16:50 | 5718.50 | 04-OCT-16:50 | 121.09 | 26-OCT-13:51 | 1533.33 | 04-OCT-16:41 | 0.00 | 01-OCT-00:01 |
November | 0.122023E+11 | 0.338432E+10 | 720.00 | 0.121872E+11 | 15123755.46 | 0.00 | 0.92 | 04-NOV-16:00 | 0.46 | 13-NOV-04:11 | 6462.81 | 04-NOV-16:00 | 6401.90 | 04-NOV-16:00 | 145.64 | 03-NOV-16:00 | 1686.81 | 04-NOV-16:00 | 0.00 | 01-NOV-00:01 |
December | 0.165579E+11 | 0.435231E+10 | 744.00 | 0.165569E+11 | 959108.15 | 0.00 | 1.00 | 01-DEC-12:13 | 0.66 | 26-DEC-04:11 | 8068.71 | 05-DEC-15:47 | 8068.71 | 05-DEC-15:47 | 58.79 | 28-DEC-15:43 | 2091.29 | 05-DEC-15:43 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.140023E+12 | 0.384082E+11 | 8554.92 | 0.139641E+12 | 0.382137E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.188048E+10 | 0.603946E+09 | 540.42 | 0.188047E+10 | 3364.36 | 0.00 | 0.42 | 0.00 | 2514.75 | 2514.75 | 1.58 | 764.82 | 0.00 | |||||||
Maximum of Months | 0.217856E+11 | 0.572481E+10 | 744.00 | 0.216519E+11 | 0.133695E+09 | 0.00 | 1.00 | 0.78 | 9885.99 | 9811.32 | 263.75 | 3021.99 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.31 | 0.00 | 95.31 | 0.02 | 885.31 | 0.00 | 0.00 | 0.00 |
February | 148.31 | 0.00 | 148.31 | 9.33 | 785.80 | 0.00 | 0.00 | 0.00 |
March | 218.51 | 0.00 | 218.51 | 39.87 | 636.73 | 0.00 | 0.00 | 0.00 |
April | 309.21 | 1.10 | 308.12 | 132.03 | 496.26 | 0.00 | 0.00 | 0.00 |
May | 397.88 | 11.82 | 386.06 | 250.29 | 380.44 | 0.00 | 0.00 | 0.00 |
June | 418.36 | 27.63 | 390.74 | 302.24 | 292.49 | 0.00 | 0.00 | 0.00 |
July | 397.63 | 31.18 | 366.45 | 344.10 | 264.23 | 0.00 | 0.00 | 0.00 |
August | 321.88 | 8.70 | 313.18 | 285.28 | 264.15 | 0.00 | 0.00 | 0.00 |
September | 250.03 | 0.07 | 249.95 | 145.12 | 387.90 | 0.00 | 0.00 | 0.00 |
October | 171.31 | 0.00 | 171.31 | 37.10 | 554.88 | 0.00 | 0.00 | 0.00 |
November | 107.91 | 0.00 | 107.91 | 3.49 | 733.00 | 0.00 | 0.00 | 0.00 |
December | 80.99 | 0.00 | 80.99 | 0.00 | 898.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 243.58 | 6.76 | 236.82 | 129.88 | 547.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.99 | 0.00 | 80.99 | 0.00 | 264.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.36 | 31.18 | 390.74 | 344.10 | 898.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.31 | 0.00 | 95.31 | 0.02 | 885.31 | 0.00 | 0.00 | 0.00 |
February | 148.31 | 0.00 | 148.31 | 9.33 | 785.80 | 0.00 | 0.00 | 0.00 |
March | 218.51 | 0.00 | 218.51 | 39.87 | 636.73 | 0.00 | 0.00 | 0.00 |
April | 309.21 | 1.10 | 308.12 | 132.03 | 496.26 | 0.00 | 0.00 | 0.00 |
May | 397.88 | 11.82 | 386.06 | 250.29 | 380.44 | 0.00 | 0.00 | 0.00 |
June | 418.36 | 27.63 | 390.74 | 302.24 | 292.49 | 0.00 | 0.00 | 0.00 |
July | 397.63 | 31.18 | 366.45 | 344.10 | 264.23 | 0.00 | 0.00 | 0.00 |
August | 321.88 | 8.70 | 313.18 | 285.28 | 264.15 | 0.00 | 0.00 | 0.00 |
September | 250.03 | 0.07 | 249.95 | 145.12 | 387.90 | 0.00 | 0.00 | 0.00 |
October | 171.31 | 0.00 | 171.31 | 37.10 | 554.88 | 0.00 | 0.00 | 0.00 |
November | 107.91 | 0.00 | 107.91 | 3.49 | 733.00 | 0.00 | 0.00 | 0.00 |
December | 80.99 | 0.00 | 80.99 | 0.00 | 898.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 243.58 | 6.76 | 236.82 | 129.88 | 547.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.99 | 0.00 | 80.99 | 0.00 | 264.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.36 | 31.18 | 390.74 | 344.10 | 898.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.31 | 0.00 | 95.31 | 0.02 | 885.31 | 0.00 | 0.00 | 0.00 |
February | 148.31 | 0.00 | 148.31 | 9.33 | 785.80 | 0.00 | 0.00 | 0.00 |
March | 218.51 | 0.00 | 218.51 | 39.87 | 636.73 | 0.00 | 0.00 | 0.00 |
April | 309.21 | 1.10 | 308.12 | 132.03 | 496.26 | 0.00 | 0.00 | 0.00 |
May | 397.88 | 11.82 | 386.06 | 250.29 | 380.44 | 0.00 | 0.00 | 0.00 |
June | 418.36 | 27.63 | 390.74 | 302.24 | 292.49 | 0.00 | 0.00 | 0.00 |
July | 397.63 | 31.18 | 366.45 | 344.10 | 264.23 | 0.00 | 0.00 | 0.00 |
August | 321.88 | 8.70 | 313.18 | 285.28 | 264.15 | 0.00 | 0.00 | 0.00 |
September | 250.03 | 0.07 | 249.95 | 145.12 | 387.90 | 0.00 | 0.00 | 0.00 |
October | 171.31 | 0.00 | 171.31 | 37.10 | 554.88 | 0.00 | 0.00 | 0.00 |
November | 107.91 | 0.00 | 107.91 | 3.49 | 733.00 | 0.00 | 0.00 | 0.00 |
December | 80.99 | 0.00 | 80.99 | 0.00 | 898.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 243.58 | 6.76 | 236.82 | 129.88 | 547.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.99 | 0.00 | 80.99 | 0.00 | 264.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.36 | 31.18 | 390.74 | 344.10 | 898.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.31 | 0.00 | 95.31 | 0.02 | 885.31 | 0.00 | 0.00 | 0.00 |
February | 148.31 | 0.00 | 148.31 | 9.33 | 785.80 | 0.00 | 0.00 | 0.00 |
March | 218.51 | 0.00 | 218.51 | 39.87 | 636.73 | 0.00 | 0.00 | 0.00 |
April | 309.21 | 1.10 | 308.12 | 132.03 | 496.26 | 0.00 | 0.00 | 0.00 |
May | 397.88 | 11.82 | 386.06 | 250.29 | 380.44 | 0.00 | 0.00 | 0.00 |
June | 418.36 | 27.63 | 390.74 | 302.24 | 292.49 | 0.00 | 0.00 | 0.00 |
July | 397.63 | 31.18 | 366.45 | 344.10 | 264.23 | 0.00 | 0.00 | 0.00 |
August | 321.88 | 8.70 | 313.18 | 285.28 | 264.15 | 0.00 | 0.00 | 0.00 |
September | 250.03 | 0.07 | 249.95 | 145.12 | 387.90 | 0.00 | 0.00 | 0.00 |
October | 171.31 | 0.00 | 171.31 | 37.10 | 554.88 | 0.00 | 0.00 | 0.00 |
November | 107.91 | 0.00 | 107.91 | 3.49 | 733.00 | 0.00 | 0.00 | 0.00 |
December | 80.99 | 0.00 | 80.99 | 0.00 | 898.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 243.58 | 6.76 | 236.82 | 129.88 | 547.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.99 | 0.00 | 80.99 | 0.00 | 264.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.36 | 31.18 | 390.74 | 344.10 | 898.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.31 | 0.00 | 95.31 | 0.02 | 885.27 | 0.00 | 0.00 | 0.00 |
February | 148.30 | 0.00 | 148.30 | 9.33 | 785.77 | 0.00 | 0.00 | 0.00 |
March | 218.50 | 0.00 | 218.50 | 39.87 | 636.71 | 0.00 | 0.00 | 0.00 |
April | 309.20 | 1.10 | 308.11 | 132.03 | 496.24 | 0.00 | 0.00 | 0.00 |
May | 397.87 | 11.82 | 386.05 | 250.28 | 380.42 | 0.00 | 0.00 | 0.00 |
June | 418.35 | 27.63 | 390.72 | 302.23 | 292.48 | 0.00 | 0.00 | 0.00 |
July | 397.61 | 31.17 | 366.44 | 344.09 | 264.22 | 0.00 | 0.00 | 0.00 |
August | 321.87 | 8.70 | 313.17 | 285.27 | 264.14 | 0.00 | 0.00 | 0.00 |
September | 250.02 | 0.07 | 249.94 | 145.11 | 387.88 | 0.00 | 0.00 | 0.00 |
October | 171.30 | 0.00 | 171.30 | 37.10 | 554.85 | 0.00 | 0.00 | 0.00 |
November | 107.90 | 0.00 | 107.90 | 3.49 | 732.97 | 0.00 | 0.00 | 0.00 |
December | 80.99 | 0.00 | 80.99 | 0.00 | 898.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 243.57 | 6.76 | 236.81 | 129.87 | 547.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.99 | 0.00 | 80.99 | 0.00 | 264.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.35 | 31.17 | 390.72 | 344.09 | 898.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.17 | 43.14 | 127.03 | 36.35 | 912.15 | 0.00 | 0.00 | 0.00 |
February | 312.25 | 110.82 | 201.42 | 147.85 | 786.36 | 0.00 | 0.00 | 0.00 |
March | 466.21 | 168.77 | 297.44 | 310.57 | 635.57 | 0.00 | 0.00 | 0.00 |
April | 722.70 | 300.29 | 422.41 | 638.24 | 490.34 | 0.00 | 0.00 | 0.00 |
May | 769.02 | 267.37 | 501.65 | 732.75 | 400.29 | 0.00 | 0.00 | 0.00 |
June | 920.98 | 400.73 | 520.26 | 968.11 | 313.38 | 0.00 | 0.00 | 0.00 |
July | 857.65 | 384.96 | 472.69 | 957.48 | 272.46 | 0.00 | 0.00 | 0.00 |
August | 842.95 | 421.69 | 421.26 | 981.62 | 262.21 | 0.00 | 0.00 | 0.00 |
September | 623.24 | 287.44 | 335.80 | 622.18 | 387.55 | 0.00 | 0.00 | 0.00 |
October | 406.23 | 172.61 | 233.62 | 308.42 | 555.78 | 0.00 | 0.00 | 0.00 |
November | 199.11 | 56.21 | 142.90 | 73.47 | 741.80 | 0.00 | 0.00 | 0.00 |
December | 163.31 | 52.58 | 110.74 | 51.89 | 919.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 538.81 | 222.71 | 316.10 | 487.54 | 555.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 163.31 | 43.14 | 110.74 | 36.35 | 262.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 920.98 | 421.69 | 520.26 | 981.62 | 919.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.17 | 43.14 | 127.03 | 36.35 | 912.15 | 0.00 | 0.00 | 0.00 |
February | 312.25 | 110.82 | 201.42 | 147.85 | 786.36 | 0.00 | 0.00 | 0.00 |
March | 466.21 | 168.77 | 297.44 | 310.57 | 635.57 | 0.00 | 0.00 | 0.00 |
April | 722.70 | 300.29 | 422.41 | 638.24 | 490.34 | 0.00 | 0.00 | 0.00 |
May | 769.02 | 267.37 | 501.65 | 732.75 | 400.29 | 0.00 | 0.00 | 0.00 |
June | 920.98 | 400.73 | 520.26 | 968.11 | 313.38 | 0.00 | 0.00 | 0.00 |
July | 857.65 | 384.96 | 472.69 | 957.48 | 272.46 | 0.00 | 0.00 | 0.00 |
August | 842.95 | 421.69 | 421.26 | 981.62 | 262.21 | 0.00 | 0.00 | 0.00 |
September | 623.24 | 287.44 | 335.80 | 622.18 | 387.55 | 0.00 | 0.00 | 0.00 |
October | 406.23 | 172.61 | 233.62 | 308.42 | 555.78 | 0.00 | 0.00 | 0.00 |
November | 199.11 | 56.21 | 142.90 | 73.47 | 741.80 | 0.00 | 0.00 | 0.00 |
December | 163.31 | 52.58 | 110.74 | 51.89 | 919.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 538.81 | 222.71 | 316.10 | 487.54 | 555.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 163.31 | 43.14 | 110.74 | 36.35 | 262.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 920.98 | 421.69 | 520.26 | 981.62 | 919.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.17 | 43.14 | 127.02 | 36.35 | 912.14 | 0.00 | 0.00 | 0.00 |
February | 312.24 | 110.82 | 201.42 | 147.84 | 786.35 | 0.00 | 0.00 | 0.00 |
March | 466.20 | 168.77 | 297.43 | 310.57 | 635.55 | 0.00 | 0.00 | 0.00 |
April | 722.69 | 300.29 | 422.40 | 638.23 | 490.33 | 0.00 | 0.00 | 0.00 |
May | 769.00 | 267.36 | 501.64 | 732.74 | 400.29 | 0.00 | 0.00 | 0.00 |
June | 920.97 | 400.72 | 520.25 | 968.09 | 313.37 | 0.00 | 0.00 | 0.00 |
July | 857.64 | 384.96 | 472.68 | 957.46 | 272.45 | 0.00 | 0.00 | 0.00 |
August | 842.94 | 421.68 | 421.25 | 981.60 | 262.21 | 0.00 | 0.00 | 0.00 |
September | 623.23 | 287.44 | 335.79 | 622.17 | 387.55 | 0.00 | 0.00 | 0.00 |
October | 406.22 | 172.60 | 233.61 | 308.42 | 555.76 | 0.00 | 0.00 | 0.00 |
November | 199.11 | 56.21 | 142.90 | 73.47 | 741.78 | 0.00 | 0.00 | 0.00 |
December | 163.31 | 52.57 | 110.74 | 51.89 | 919.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 538.80 | 222.70 | 316.10 | 487.53 | 555.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 163.31 | 43.14 | 110.74 | 36.35 | 262.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 920.97 | 421.68 | 520.25 | 981.60 | 919.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 421.12 | 250.06 | 171.06 | 313.78 | 742.15 | 0.00 | 0.00 | 0.00 |
February | 647.62 | 400.89 | 246.73 | 572.76 | 658.66 | 0.00 | 0.00 | 0.00 |
March | 696.65 | 371.52 | 325.14 | 659.43 | 575.72 | 0.00 | 0.00 | 0.00 |
April | 735.53 | 319.36 | 416.17 | 745.22 | 479.53 | 0.00 | 0.00 | 0.00 |
May | 672.55 | 200.36 | 472.19 | 693.22 | 387.33 | 0.00 | 0.00 | 0.00 |
June | 615.32 | 165.21 | 450.11 | 650.14 | 308.75 | 0.00 | 0.00 | 0.00 |
July | 671.03 | 245.77 | 425.26 | 804.99 | 278.16 | 0.00 | 0.00 | 0.00 |
August | 720.94 | 336.19 | 384.75 | 905.21 | 268.73 | 0.00 | 0.00 | 0.00 |
September | 798.77 | 441.11 | 357.66 | 931.49 | 366.80 | 0.00 | 0.00 | 0.00 |
October | 723.55 | 446.74 | 276.81 | 750.27 | 499.76 | 0.00 | 0.00 | 0.00 |
November | 427.79 | 245.16 | 182.63 | 350.68 | 621.70 | 0.00 | 0.00 | 0.00 |
December | 447.59 | 289.65 | 157.94 | 380.43 | 765.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 631.27 | 308.76 | 322.50 | 646.82 | 495.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 421.12 | 165.21 | 157.94 | 313.78 | 268.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 798.77 | 446.74 | 472.19 | 931.49 | 765.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 421.12 | 250.06 | 171.06 | 313.78 | 742.15 | 0.00 | 0.00 | 0.00 |
February | 647.62 | 400.89 | 246.73 | 572.76 | 658.66 | 0.00 | 0.00 | 0.00 |
March | 696.65 | 371.52 | 325.14 | 659.43 | 575.72 | 0.00 | 0.00 | 0.00 |
April | 735.53 | 319.36 | 416.17 | 745.22 | 479.53 | 0.00 | 0.00 | 0.00 |
May | 672.55 | 200.36 | 472.19 | 693.21 | 387.33 | 0.00 | 0.00 | 0.00 |
June | 615.32 | 165.20 | 450.11 | 650.14 | 308.75 | 0.00 | 0.00 | 0.00 |
July | 671.03 | 245.77 | 425.26 | 804.99 | 278.16 | 0.00 | 0.00 | 0.00 |
August | 720.94 | 336.19 | 384.75 | 905.21 | 268.73 | 0.00 | 0.00 | 0.00 |
September | 798.77 | 441.11 | 357.66 | 931.49 | 366.80 | 0.00 | 0.00 | 0.00 |
October | 723.55 | 446.74 | 276.81 | 750.27 | 499.76 | 0.00 | 0.00 | 0.00 |
November | 427.79 | 245.16 | 182.63 | 350.67 | 621.70 | 0.00 | 0.00 | 0.00 |
December | 447.59 | 289.65 | 157.94 | 380.43 | 765.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 631.27 | 308.76 | 322.50 | 646.82 | 495.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 421.12 | 165.20 | 157.94 | 313.78 | 268.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 798.77 | 446.74 | 472.19 | 931.49 | 765.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 421.12 | 250.06 | 171.06 | 313.78 | 742.15 | 0.00 | 0.00 | 0.00 |
February | 647.62 | 400.89 | 246.73 | 572.76 | 658.66 | 0.00 | 0.00 | 0.00 |
March | 696.65 | 371.52 | 325.14 | 659.43 | 575.72 | 0.00 | 0.00 | 0.00 |
April | 735.53 | 319.36 | 416.17 | 745.22 | 479.53 | 0.00 | 0.00 | 0.00 |
May | 672.55 | 200.36 | 472.19 | 693.22 | 387.33 | 0.00 | 0.00 | 0.00 |
June | 615.32 | 165.21 | 450.11 | 650.14 | 308.75 | 0.00 | 0.00 | 0.00 |
July | 671.03 | 245.77 | 425.26 | 804.99 | 278.16 | 0.00 | 0.00 | 0.00 |
August | 720.94 | 336.19 | 384.75 | 905.21 | 268.73 | 0.00 | 0.00 | 0.00 |
September | 798.77 | 441.11 | 357.66 | 931.49 | 366.80 | 0.00 | 0.00 | 0.00 |
October | 723.55 | 446.74 | 276.81 | 750.27 | 499.76 | 0.00 | 0.00 | 0.00 |
November | 427.79 | 245.16 | 182.63 | 350.68 | 621.70 | 0.00 | 0.00 | 0.00 |
December | 447.59 | 289.65 | 157.94 | 380.43 | 765.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 631.27 | 308.76 | 322.50 | 646.82 | 495.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 421.12 | 165.21 | 157.94 | 313.78 | 268.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 798.77 | 446.74 | 472.19 | 931.49 | 765.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 421.12 | 250.06 | 171.06 | 313.78 | 742.15 | 0.00 | 0.00 | 0.00 |
February | 647.62 | 400.89 | 246.73 | 572.76 | 658.66 | 0.00 | 0.00 | 0.00 |
March | 696.65 | 371.52 | 325.14 | 659.43 | 575.72 | 0.00 | 0.00 | 0.00 |
April | 735.53 | 319.36 | 416.17 | 745.22 | 479.53 | 0.00 | 0.00 | 0.00 |
May | 672.55 | 200.36 | 472.19 | 693.21 | 387.33 | 0.00 | 0.00 | 0.00 |
June | 615.32 | 165.20 | 450.11 | 650.14 | 308.75 | 0.00 | 0.00 | 0.00 |
July | 671.03 | 245.77 | 425.26 | 804.99 | 278.16 | 0.00 | 0.00 | 0.00 |
August | 720.94 | 336.19 | 384.75 | 905.21 | 268.73 | 0.00 | 0.00 | 0.00 |
September | 798.77 | 441.11 | 357.66 | 931.49 | 366.80 | 0.00 | 0.00 | 0.00 |
October | 723.55 | 446.74 | 276.81 | 750.27 | 499.76 | 0.00 | 0.00 | 0.00 |
November | 427.79 | 245.16 | 182.63 | 350.67 | 621.70 | 0.00 | 0.00 | 0.00 |
December | 447.59 | 289.65 | 157.94 | 380.43 | 765.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 631.27 | 308.76 | 322.50 | 646.82 | 495.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 421.12 | 165.20 | 157.94 | 313.78 | 268.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 798.77 | 446.74 | 472.19 | 931.49 | 765.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 421.10 | 250.05 | 171.05 | 313.77 | 742.12 | 0.00 | 0.00 | 0.00 |
February | 647.59 | 400.87 | 246.72 | 572.74 | 658.64 | 0.00 | 0.00 | 0.00 |
March | 696.62 | 371.50 | 325.12 | 659.41 | 575.70 | 0.00 | 0.00 | 0.00 |
April | 735.50 | 319.35 | 416.15 | 745.19 | 479.51 | 0.00 | 0.00 | 0.00 |
May | 672.52 | 200.35 | 472.17 | 693.19 | 387.31 | 0.00 | 0.00 | 0.00 |
June | 615.29 | 165.20 | 450.09 | 650.11 | 308.74 | 0.00 | 0.00 | 0.00 |
July | 671.00 | 245.76 | 425.25 | 804.96 | 278.15 | 0.00 | 0.00 | 0.00 |
August | 720.91 | 336.17 | 384.74 | 905.18 | 268.72 | 0.00 | 0.00 | 0.00 |
September | 798.74 | 441.09 | 357.65 | 931.46 | 366.79 | 0.00 | 0.00 | 0.00 |
October | 723.52 | 446.72 | 276.80 | 750.24 | 499.74 | 0.00 | 0.00 | 0.00 |
November | 427.77 | 245.15 | 182.62 | 350.66 | 621.68 | 0.00 | 0.00 | 0.00 |
December | 447.57 | 289.64 | 157.93 | 380.42 | 765.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 631.24 | 308.75 | 322.49 | 646.80 | 495.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 421.10 | 165.20 | 157.93 | 313.77 | 268.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 798.74 | 446.72 | 472.17 | 931.46 | 765.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 179.49 | 52.93 | 126.56 | 50.71 | 969.56 | 0.00 | 0.00 | 0.00 |
February | 321.81 | 120.94 | 200.86 | 168.93 | 851.62 | 0.00 | 0.00 | 0.00 |
March | 450.94 | 152.20 | 298.73 | 295.23 | 719.18 | 0.00 | 0.00 | 0.00 |
April | 686.05 | 262.30 | 423.75 | 579.13 | 596.93 | 0.00 | 0.00 | 0.00 |
May | 882.79 | 358.63 | 524.16 | 873.47 | 461.51 | 0.00 | 0.00 | 0.00 |
June | 849.00 | 329.64 | 519.36 | 862.38 | 374.14 | 0.00 | 0.00 | 0.00 |
July | 1048.83 | 551.32 | 497.51 | 1202.18 | 356.62 | 0.00 | 0.00 | 0.00 |
August | 867.63 | 443.04 | 424.59 | 1004.47 | 358.76 | 0.00 | 0.00 | 0.00 |
September | 706.55 | 339.02 | 367.53 | 745.97 | 450.49 | 0.00 | 0.00 | 0.00 |
October | 402.24 | 163.89 | 238.35 | 307.04 | 627.98 | 0.00 | 0.00 | 0.00 |
November | 200.31 | 56.50 | 143.82 | 74.95 | 818.47 | 0.00 | 0.00 | 0.00 |
December | 168.40 | 57.71 | 110.70 | 63.16 | 1022.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 565.15 | 241.59 | 323.55 | 521.33 | 633.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 168.40 | 52.93 | 110.70 | 50.71 | 356.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1048.83 | 551.32 | 524.16 | 1202.18 | 1022.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 179.49 | 52.93 | 126.56 | 50.71 | 969.56 | 0.00 | 0.00 | 0.00 |
February | 321.81 | 120.94 | 200.86 | 168.93 | 851.62 | 0.00 | 0.00 | 0.00 |
March | 450.94 | 152.20 | 298.73 | 295.23 | 719.18 | 0.00 | 0.00 | 0.00 |
April | 686.05 | 262.30 | 423.75 | 579.13 | 596.93 | 0.00 | 0.00 | 0.00 |
May | 882.79 | 358.63 | 524.16 | 873.47 | 461.51 | 0.00 | 0.00 | 0.00 |
June | 849.00 | 329.64 | 519.36 | 862.38 | 374.14 | 0.00 | 0.00 | 0.00 |
July | 1048.83 | 551.32 | 497.51 | 1202.18 | 356.62 | 0.00 | 0.00 | 0.00 |
August | 867.63 | 443.04 | 424.59 | 1004.47 | 358.76 | 0.00 | 0.00 | 0.00 |
September | 706.55 | 339.02 | 367.53 | 745.97 | 450.49 | 0.00 | 0.00 | 0.00 |
October | 402.24 | 163.89 | 238.35 | 307.04 | 627.98 | 0.00 | 0.00 | 0.00 |
November | 200.31 | 56.50 | 143.82 | 74.95 | 818.47 | 0.00 | 0.00 | 0.00 |
December | 168.40 | 57.71 | 110.70 | 63.16 | 1022.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 565.15 | 241.59 | 323.55 | 521.33 | 633.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 168.40 | 52.93 | 110.70 | 50.71 | 356.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1048.83 | 551.32 | 524.16 | 1202.18 | 1022.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 179.49 | 52.93 | 126.56 | 50.71 | 969.54 | 0.00 | 0.00 | 0.00 |
February | 321.80 | 120.94 | 200.86 | 168.93 | 851.60 | 0.00 | 0.00 | 0.00 |
March | 450.93 | 152.20 | 298.73 | 295.23 | 719.16 | 0.00 | 0.00 | 0.00 |
April | 686.04 | 262.30 | 423.74 | 579.12 | 596.92 | 0.00 | 0.00 | 0.00 |
May | 882.77 | 358.62 | 524.15 | 873.46 | 461.50 | 0.00 | 0.00 | 0.00 |
June | 848.99 | 329.63 | 519.35 | 862.36 | 374.13 | 0.00 | 0.00 | 0.00 |
July | 1048.81 | 551.31 | 497.50 | 1202.16 | 356.61 | 0.00 | 0.00 | 0.00 |
August | 867.61 | 443.03 | 424.59 | 1004.46 | 358.75 | 0.00 | 0.00 | 0.00 |
September | 706.54 | 339.01 | 367.53 | 745.95 | 450.48 | 0.00 | 0.00 | 0.00 |
October | 402.24 | 163.89 | 238.34 | 307.03 | 627.96 | 0.00 | 0.00 | 0.00 |
November | 200.31 | 56.50 | 143.81 | 74.94 | 818.46 | 0.00 | 0.00 | 0.00 |
December | 168.40 | 57.71 | 110.69 | 63.16 | 1022.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 565.14 | 241.59 | 323.55 | 521.32 | 633.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 168.40 | 52.93 | 110.69 | 50.71 | 356.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1048.81 | 551.31 | 524.15 | 1202.16 | 1022.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 476.56 | 0.00 | 476.56 | 1.51 | 3927.17 | 0.00 | 0.00 | 0.00 |
February | 741.54 | 0.00 | 741.54 | 73.09 | 3520.07 | 0.00 | 0.00 | 0.00 |
March | 1092.54 | 0.00 | 1092.54 | 260.10 | 2843.88 | 0.00 | 0.00 | 0.00 |
April | 1546.05 | 5.48 | 1540.57 | 752.60 | 2220.76 | 0.00 | 0.00 | 0.00 |
May | 1989.38 | 59.10 | 1930.28 | 1310.97 | 1763.20 | 0.00 | 0.00 | 0.00 |
June | 2091.79 | 138.13 | 1953.65 | 1566.89 | 1358.62 | 0.00 | 0.00 | 0.00 |
July | 1988.13 | 155.88 | 1832.25 | 1786.77 | 1208.70 | 0.00 | 0.00 | 0.00 |
August | 1609.40 | 43.51 | 1565.90 | 1493.84 | 1188.87 | 0.00 | 0.00 | 0.00 |
September | 1250.13 | 0.37 | 1249.76 | 782.25 | 1758.71 | 0.00 | 0.00 | 0.00 |
October | 856.55 | 0.00 | 856.55 | 245.81 | 2446.51 | 0.00 | 0.00 | 0.00 |
November | 539.54 | 0.00 | 539.54 | 31.51 | 3189.89 | 0.00 | 0.00 | 0.00 |
December | 404.95 | 0.00 | 404.95 | 0.90 | 3958.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1217.89 | 33.79 | 1184.10 | 696.28 | 2443.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 404.95 | 0.00 | 404.95 | 0.90 | 1188.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2091.79 | 155.88 | 1953.65 | 1786.77 | 3958.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 510.51 | 129.43 | 381.08 | 117.05 | 2490.78 | 0.00 | 0.00 | 0.00 |
February | 936.73 | 332.47 | 604.27 | 462.78 | 2202.51 | 0.00 | 0.00 | 0.00 |
March | 1398.61 | 506.31 | 892.30 | 928.44 | 1796.21 | 0.00 | 0.00 | 0.00 |
April | 2168.08 | 900.87 | 1267.21 | 1904.50 | 1390.08 | 0.00 | 0.00 | 0.00 |
May | 2307.03 | 802.10 | 1504.93 | 2178.93 | 1146.03 | 0.00 | 0.00 | 0.00 |
June | 2762.93 | 1202.17 | 1560.76 | 2870.39 | 899.64 | 0.00 | 0.00 | 0.00 |
July | 2572.93 | 1154.88 | 1418.05 | 2850.51 | 777.98 | 0.00 | 0.00 | 0.00 |
August | 2528.83 | 1265.06 | 1263.76 | 2919.15 | 757.39 | 0.00 | 0.00 | 0.00 |
September | 1869.70 | 862.32 | 1007.38 | 1854.66 | 1099.89 | 0.00 | 0.00 | 0.00 |
October | 1218.67 | 517.82 | 700.85 | 926.92 | 1553.24 | 0.00 | 0.00 | 0.00 |
November | 597.32 | 168.63 | 428.69 | 229.34 | 2049.92 | 0.00 | 0.00 | 0.00 |
December | 489.94 | 157.73 | 332.21 | 163.76 | 2533.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1616.41 | 668.11 | 948.30 | 1455.76 | 1554.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 489.94 | 129.43 | 332.21 | 117.05 | 757.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2762.93 | 1265.06 | 1560.76 | 2919.15 | 2533.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2105.58 | 1250.30 | 855.28 | 1567.77 | 3547.18 | 0.00 | 0.00 | 0.00 |
February | 3238.06 | 2004.41 | 1233.66 | 2846.44 | 3204.64 | 0.00 | 0.00 | 0.00 |
March | 3483.22 | 1857.56 | 1625.66 | 3265.31 | 2796.93 | 0.00 | 0.00 | 0.00 |
April | 3677.62 | 1596.80 | 2080.82 | 3696.48 | 2319.95 | 0.00 | 0.00 | 0.00 |
May | 3362.71 | 1001.79 | 2360.93 | 3429.64 | 1889.11 | 0.00 | 0.00 | 0.00 |
June | 3076.55 | 826.02 | 2250.54 | 3232.87 | 1484.12 | 0.00 | 0.00 | 0.00 |
July | 3355.12 | 1228.82 | 2126.29 | 4009.87 | 1322.28 | 0.00 | 0.00 | 0.00 |
August | 3604.65 | 1680.91 | 1923.74 | 4513.93 | 1280.67 | 0.00 | 0.00 | 0.00 |
September | 3993.80 | 2205.51 | 1788.29 | 4630.37 | 1789.65 | 0.00 | 0.00 | 0.00 |
October | 3617.71 | 2233.67 | 1384.04 | 3712.03 | 2432.24 | 0.00 | 0.00 | 0.00 |
November | 2138.91 | 1225.78 | 913.13 | 1754.06 | 2987.32 | 0.00 | 0.00 | 0.00 |
December | 2237.91 | 1448.24 | 789.67 | 1906.05 | 3661.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3156.29 | 1543.80 | 1612.49 | 3215.50 | 2389.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2105.58 | 826.02 | 789.67 | 1567.77 | 1280.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3993.80 | 2233.67 | 2360.93 | 4630.37 | 3661.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 538.46 | 158.78 | 379.68 | 162.36 | 2566.04 | 0.00 | 0.00 | 0.00 |
February | 965.42 | 362.83 | 602.59 | 541.11 | 2273.09 | 0.00 | 0.00 | 0.00 |
March | 1352.80 | 456.61 | 896.19 | 935.15 | 1879.74 | 0.00 | 0.00 | 0.00 |
April | 2058.14 | 786.90 | 1271.23 | 1819.56 | 1541.27 | 0.00 | 0.00 | 0.00 |
May | 2648.34 | 1075.88 | 1572.46 | 2648.73 | 1272.80 | 0.00 | 0.00 | 0.00 |
June | 2546.98 | 988.91 | 1558.07 | 2636.14 | 1001.12 | 0.00 | 0.00 | 0.00 |
July | 3146.44 | 1653.93 | 1492.51 | 3661.83 | 930.25 | 0.00 | 0.00 | 0.00 |
August | 2602.86 | 1329.10 | 1273.77 | 3098.80 | 894.71 | 0.00 | 0.00 | 0.00 |
September | 2119.63 | 1017.05 | 1102.59 | 2276.90 | 1215.11 | 0.00 | 0.00 | 0.00 |
October | 1206.71 | 491.68 | 715.04 | 965.28 | 1648.09 | 0.00 | 0.00 | 0.00 |
November | 600.94 | 169.49 | 431.45 | 251.53 | 2091.29 | 0.00 | 0.00 | 0.00 |
December | 505.20 | 173.12 | 332.08 | 212.09 | 2608.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1695.42 | 724.77 | 970.65 | 1607.91 | 1657.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 505.20 | 158.78 | 332.08 | 162.36 | 894.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3146.44 | 1653.93 | 1572.46 | 3661.83 | 2608.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 476.56 | 0.00 | 476.56 | 6.80 | 3645.67 | 0.00 | 0.00 | 0.00 |
February | 741.54 | 0.00 | 741.54 | 95.21 | 3218.44 | 0.00 | 0.00 | 0.00 |
March | 1092.54 | 0.00 | 1092.54 | 308.13 | 2549.28 | 0.00 | 0.00 | 0.00 |
April | 1546.05 | 5.48 | 1540.57 | 813.41 | 2010.06 | 0.00 | 0.00 | 0.00 |
May | 1989.38 | 59.10 | 1930.28 | 1371.27 | 1605.33 | 0.00 | 0.00 | 0.00 |
June | 2091.79 | 138.13 | 1953.65 | 1610.62 | 1261.35 | 0.00 | 0.00 | 0.00 |
July | 1988.13 | 155.88 | 1832.25 | 1813.85 | 1130.82 | 0.00 | 0.00 | 0.00 |
August | 1609.40 | 43.51 | 1565.90 | 1527.83 | 1096.26 | 0.00 | 0.00 | 0.00 |
September | 1250.13 | 0.37 | 1249.76 | 841.63 | 1565.40 | 0.00 | 0.00 | 0.00 |
October | 856.55 | 0.00 | 856.55 | 307.92 | 2143.54 | 0.00 | 0.00 | 0.00 |
November | 539.54 | 0.00 | 539.54 | 47.04 | 2815.57 | 0.00 | 0.00 | 0.00 |
December | 404.95 | 0.00 | 404.95 | 5.96 | 3571.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1217.89 | 33.79 | 1184.10 | 733.26 | 2212.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 404.95 | 0.00 | 404.95 | 5.96 | 1096.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2091.79 | 155.88 | 1953.65 | 1813.85 | 3645.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 510.51 | 129.43 | 381.08 | 130.81 | 2308.36 | 0.00 | 0.00 | 0.00 |
February | 936.73 | 332.47 | 604.27 | 503.87 | 2005.35 | 0.00 | 0.00 | 0.00 |
March | 1398.61 | 506.31 | 892.30 | 987.12 | 1613.40 | 0.00 | 0.00 | 0.00 |
April | 2168.08 | 900.87 | 1267.21 | 1956.07 | 1273.90 | 0.00 | 0.00 | 0.00 |
May | 2307.03 | 802.10 | 1504.93 | 2214.87 | 1066.70 | 0.00 | 0.00 | 0.00 |
June | 2762.93 | 1202.17 | 1560.76 | 2880.43 | 855.71 | 0.00 | 0.00 | 0.00 |
July | 2572.93 | 1154.88 | 1418.05 | 2854.34 | 747.00 | 0.00 | 0.00 | 0.00 |
August | 2528.83 | 1265.06 | 1263.76 | 2932.62 | 719.81 | 0.00 | 0.00 | 0.00 |
September | 1869.70 | 862.32 | 1007.38 | 1891.49 | 1002.62 | 0.00 | 0.00 | 0.00 |
October | 1218.67 | 517.82 | 700.85 | 987.27 | 1375.33 | 0.00 | 0.00 | 0.00 |
November | 597.32 | 168.63 | 428.69 | 257.15 | 1809.54 | 0.00 | 0.00 | 0.00 |
December | 489.94 | 157.73 | 332.21 | 183.16 | 2285.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1616.41 | 668.11 | 948.30 | 1486.74 | 1419.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 489.94 | 129.43 | 332.21 | 130.81 | 719.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2762.93 | 1265.06 | 1560.76 | 2932.62 | 2308.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2105.58 | 1250.30 | 855.28 | 1617.81 | 3263.12 | 0.00 | 0.00 | 0.00 |
February | 3238.06 | 2004.41 | 1233.66 | 2917.40 | 2923.41 | 0.00 | 0.00 | 0.00 |
March | 3483.22 | 1857.56 | 1625.66 | 3310.73 | 2535.96 | 0.00 | 0.00 | 0.00 |
April | 3677.62 | 1596.80 | 2080.82 | 3733.05 | 2135.88 | 0.00 | 0.00 | 0.00 |
May | 3362.71 | 1001.79 | 2360.93 | 3449.18 | 1753.73 | 0.00 | 0.00 | 0.00 |
June | 3076.55 | 826.02 | 2250.54 | 3227.38 | 1402.77 | 0.00 | 0.00 | 0.00 |
July | 3355.12 | 1228.82 | 2126.29 | 3995.20 | 1260.94 | 0.00 | 0.00 | 0.00 |
August | 3604.65 | 1680.91 | 1923.74 | 4511.93 | 1208.86 | 0.00 | 0.00 | 0.00 |
September | 3993.80 | 2205.51 | 1788.29 | 4657.50 | 1637.47 | 0.00 | 0.00 | 0.00 |
October | 3617.71 | 2233.67 | 1384.04 | 3770.02 | 2177.07 | 0.00 | 0.00 | 0.00 |
November | 2138.91 | 1225.78 | 913.13 | 1815.65 | 2661.20 | 0.00 | 0.00 | 0.00 |
December | 2237.91 | 1448.24 | 789.67 | 1962.16 | 3308.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3156.29 | 1543.80 | 1612.49 | 3248.83 | 2185.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2105.58 | 826.02 | 789.67 | 1617.81 | 1208.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3993.80 | 2233.67 | 2360.93 | 4657.50 | 3308.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 538.46 | 158.78 | 379.68 | 169.79 | 2400.52 | 0.00 | 0.00 | 0.00 |
February | 965.42 | 362.83 | 602.59 | 557.93 | 2109.35 | 0.00 | 0.00 | 0.00 |
March | 1352.80 | 456.61 | 896.19 | 947.66 | 1729.54 | 0.00 | 0.00 | 0.00 |
April | 2058.14 | 786.90 | 1271.23 | 1828.85 | 1435.78 | 0.00 | 0.00 | 0.00 |
May | 2648.34 | 1075.88 | 1572.46 | 2648.55 | 1191.85 | 0.00 | 0.00 | 0.00 |
June | 2546.98 | 988.91 | 1558.07 | 2623.53 | 950.42 | 0.00 | 0.00 | 0.00 |
July | 3146.44 | 1653.93 | 1492.51 | 3643.76 | 889.56 | 0.00 | 0.00 | 0.00 |
August | 2602.86 | 1329.10 | 1273.77 | 3091.59 | 850.20 | 0.00 | 0.00 | 0.00 |
September | 2119.63 | 1017.05 | 1102.59 | 2284.67 | 1125.05 | 0.00 | 0.00 | 0.00 |
October | 1206.71 | 491.68 | 715.04 | 984.19 | 1503.68 | 0.00 | 0.00 | 0.00 |
November | 600.94 | 169.49 | 431.45 | 262.98 | 1899.40 | 0.00 | 0.00 | 0.00 |
December | 505.20 | 173.12 | 332.08 | 221.25 | 2395.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1695.42 | 724.77 | 970.65 | 1612.42 | 1537.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 505.20 | 158.78 | 332.08 | 169.79 | 850.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3146.44 | 1653.93 | 1572.46 | 3643.76 | 2400.52 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.255286E+09 | 0.00 | 0.255286E+09 | 57019.37 | 0.237121E+10 |
February | 0.358790E+09 | 0.00 | 0.358790E+09 | 22562192.67 | 0.190102E+10 |
March | 0.585258E+09 | 0.00 | 0.585258E+09 | 0.106783E+09 | 0.170542E+10 |
April | 0.801484E+09 | 2843106.81 | 0.798641E+09 | 0.342232E+09 | 0.128630E+10 |
May | 0.106568E+10 | 31659948.67 | 0.103403E+10 | 0.670382E+09 | 0.101897E+10 |
June | 0.108439E+10 | 71608902.18 | 0.101279E+10 | 0.783405E+09 | 0.758127E+09 |
July | 0.106501E+10 | 83502072.51 | 0.981511E+09 | 0.921640E+09 | 0.707724E+09 |
August | 0.862136E+09 | 23306118.95 | 0.838830E+09 | 0.764095E+09 | 0.707488E+09 |
September | 0.648074E+09 | 191107.15 | 0.647883E+09 | 0.376152E+09 | 0.100544E+10 |
October | 0.458840E+09 | 0.00 | 0.458840E+09 | 99376987.86 | 0.148618E+10 |
November | 0.279701E+09 | 0.00 | 0.279701E+09 | 9053318.98 | 0.189992E+10 |
December | 0.216927E+09 | 0.00 | 0.216927E+09 | 7690.44 | 0.240752E+10 |
Annual Sum or Average | 0.768159E+10 | 0.213111E+09 | 0.746848E+10 | 0.409575E+10 | 0.172553E+11 |
Minimum of Months | 0.216927E+09 | 0.00 | 0.216927E+09 | 7690.44 | 0.707488E+09 |
Maximum of Months | 0.108439E+10 | 83502072.51 | 0.103403E+10 | 0.921640E+09 | 0.240752E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.255286E+09 | 0.00 | 0.255286E+09 | 57017.97 | 0.237121E+10 |
February | 0.358789E+09 | 0.00 | 0.358789E+09 | 22562123.92 | 0.190102E+10 |
March | 0.585258E+09 | 0.00 | 0.585258E+09 | 0.106782E+09 | 0.170542E+10 |
April | 0.801483E+09 | 2843103.40 | 0.798640E+09 | 0.342232E+09 | 0.128630E+10 |
May | 0.106568E+10 | 31659910.68 | 0.103402E+10 | 0.670381E+09 | 0.101897E+10 |
June | 0.108439E+10 | 71608816.26 | 0.101279E+10 | 0.783404E+09 | 0.758127E+09 |
July | 0.106501E+10 | 83501972.32 | 0.981510E+09 | 0.921639E+09 | 0.707724E+09 |
August | 0.862135E+09 | 23306090.98 | 0.838829E+09 | 0.764095E+09 | 0.707488E+09 |
September | 0.648073E+09 | 191106.92 | 0.647882E+09 | 0.376151E+09 | 0.100544E+10 |
October | 0.458839E+09 | 0.00 | 0.458839E+09 | 99376746.97 | 0.148618E+10 |
November | 0.279700E+09 | 0.00 | 0.279700E+09 | 9053289.78 | 0.189992E+10 |
December | 0.216927E+09 | 0.00 | 0.216927E+09 | 7690.02 | 0.240752E+10 |
Annual Sum or Average | 0.768158E+10 | 0.213111E+09 | 0.746847E+10 | 0.409574E+10 | 0.172553E+11 |
Minimum of Months | 0.216927E+09 | 0.00 | 0.216927E+09 | 7690.02 | 0.707488E+09 |
Maximum of Months | 0.108439E+10 | 83501972.32 | 0.103402E+10 | 0.921639E+09 | 0.240752E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.255286E+09 | 0.00 | 0.255286E+09 | 57019.37 | 0.237121E+10 |
February | 0.358790E+09 | 0.00 | 0.358790E+09 | 22562192.67 | 0.190102E+10 |
March | 0.585258E+09 | 0.00 | 0.585258E+09 | 0.106783E+09 | 0.170542E+10 |
April | 0.801484E+09 | 2843106.81 | 0.798641E+09 | 0.342232E+09 | 0.128630E+10 |
May | 0.106568E+10 | 31659948.67 | 0.103403E+10 | 0.670382E+09 | 0.101897E+10 |
June | 0.108439E+10 | 71608902.18 | 0.101279E+10 | 0.783405E+09 | 0.758127E+09 |
July | 0.106501E+10 | 83502072.51 | 0.981511E+09 | 0.921640E+09 | 0.707724E+09 |
August | 0.862136E+09 | 23306118.95 | 0.838830E+09 | 0.764095E+09 | 0.707488E+09 |
September | 0.648074E+09 | 191107.15 | 0.647883E+09 | 0.376152E+09 | 0.100544E+10 |
October | 0.458840E+09 | 0.00 | 0.458840E+09 | 99376987.86 | 0.148618E+10 |
November | 0.279701E+09 | 0.00 | 0.279701E+09 | 9053318.98 | 0.189992E+10 |
December | 0.216927E+09 | 0.00 | 0.216927E+09 | 7690.44 | 0.240752E+10 |
Annual Sum or Average | 0.768159E+10 | 0.213111E+09 | 0.746848E+10 | 0.409575E+10 | 0.172553E+11 |
Minimum of Months | 0.216927E+09 | 0.00 | 0.216927E+09 | 7690.44 | 0.707488E+09 |
Maximum of Months | 0.108439E+10 | 83502072.51 | 0.103403E+10 | 0.921640E+09 | 0.240752E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.255286E+09 | 0.00 | 0.255286E+09 | 57017.97 | 0.237121E+10 |
February | 0.358789E+09 | 0.00 | 0.358789E+09 | 22562123.92 | 0.190102E+10 |
March | 0.585258E+09 | 0.00 | 0.585258E+09 | 0.106782E+09 | 0.170542E+10 |
April | 0.801483E+09 | 2843103.40 | 0.798640E+09 | 0.342232E+09 | 0.128630E+10 |
May | 0.106568E+10 | 31659910.68 | 0.103402E+10 | 0.670381E+09 | 0.101897E+10 |
June | 0.108439E+10 | 71608816.26 | 0.101279E+10 | 0.783404E+09 | 0.758127E+09 |
July | 0.106501E+10 | 83501972.32 | 0.981510E+09 | 0.921639E+09 | 0.707724E+09 |
August | 0.862135E+09 | 23306090.98 | 0.838829E+09 | 0.764095E+09 | 0.707488E+09 |
September | 0.648073E+09 | 191106.92 | 0.647882E+09 | 0.376151E+09 | 0.100544E+10 |
October | 0.458839E+09 | 0.00 | 0.458839E+09 | 99376746.97 | 0.148618E+10 |
November | 0.279700E+09 | 0.00 | 0.279700E+09 | 9053289.78 | 0.189992E+10 |
December | 0.216927E+09 | 0.00 | 0.216927E+09 | 7690.02 | 0.240752E+10 |
Annual Sum or Average | 0.768158E+10 | 0.213111E+09 | 0.746847E+10 | 0.409574E+10 | 0.172553E+11 |
Minimum of Months | 0.216927E+09 | 0.00 | 0.216927E+09 | 7690.02 | 0.707488E+09 |
Maximum of Months | 0.108439E+10 | 83501972.32 | 0.103402E+10 | 0.921639E+09 | 0.240752E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.255276E+09 | 0.00 | 0.255276E+09 | 57017.08 | 0.237111E+10 |
February | 0.358775E+09 | 0.00 | 0.358775E+09 | 22561283.31 | 0.190094E+10 |
March | 0.585235E+09 | 0.00 | 0.585235E+09 | 0.106778E+09 | 0.170535E+10 |
April | 0.801451E+09 | 2842992.22 | 0.798608E+09 | 0.342219E+09 | 0.128624E+10 |
May | 0.106564E+10 | 31658672.63 | 0.103398E+10 | 0.670355E+09 | 0.101893E+10 |
June | 0.108435E+10 | 71606016.03 | 0.101275E+10 | 0.783373E+09 | 0.758097E+09 |
July | 0.106497E+10 | 83498707.01 | 0.981471E+09 | 0.921603E+09 | 0.707696E+09 |
August | 0.862101E+09 | 23305179.61 | 0.838796E+09 | 0.764065E+09 | 0.707460E+09 |
September | 0.648048E+09 | 191099.45 | 0.647857E+09 | 0.376137E+09 | 0.100540E+10 |
October | 0.458821E+09 | 0.00 | 0.458821E+09 | 99372982.53 | 0.148612E+10 |
November | 0.279689E+09 | 0.00 | 0.279689E+09 | 9052954.09 | 0.189985E+10 |
December | 0.216918E+09 | 0.00 | 0.216918E+09 | 7690.13 | 0.240742E+10 |
Annual Sum or Average | 0.768128E+10 | 0.213103E+09 | 0.746818E+10 | 0.409558E+10 | 0.172546E+11 |
Minimum of Months | 0.216918E+09 | 0.00 | 0.216918E+09 | 7690.13 | 0.707460E+09 |
Maximum of Months | 0.108435E+10 | 83498707.01 | 0.103398E+10 | 0.921603E+09 | 0.240742E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.455786E+09 | 0.115557E+09 | 0.340229E+09 | 97356114.56 | 0.244311E+10 |
February | 0.755388E+09 | 0.268103E+09 | 0.487285E+09 | 0.357673E+09 | 0.190236E+10 |
March | 0.124869E+10 | 0.452036E+09 | 0.796652E+09 | 0.831842E+09 | 0.170230E+10 |
April | 0.187324E+10 | 0.778358E+09 | 0.109488E+10 | 0.165433E+10 | 0.127095E+10 |
May | 0.205974E+10 | 0.716123E+09 | 0.134361E+10 | 0.196261E+10 | 0.107215E+10 |
June | 0.238719E+10 | 0.103868E+10 | 0.134851E+10 | 0.250935E+10 | 0.812269E+09 |
July | 0.229713E+10 | 0.103109E+10 | 0.126605E+10 | 0.256451E+10 | 0.729747E+09 |
August | 0.225776E+10 | 0.112946E+10 | 0.112830E+10 | 0.262916E+10 | 0.702308E+09 |
September | 0.161543E+10 | 0.745052E+09 | 0.870382E+09 | 0.161269E+10 | 0.100454E+10 |
October | 0.108804E+10 | 0.462313E+09 | 0.625723E+09 | 0.826081E+09 | 0.148859E+10 |
November | 0.516092E+09 | 0.145698E+09 | 0.370394E+09 | 0.190429E+09 | 0.192273E+10 |
December | 0.437422E+09 | 0.140819E+09 | 0.296603E+09 | 0.138984E+09 | 0.246370E+10 |
Annual Sum or Average | 0.169919E+11 | 0.702329E+10 | 0.996861E+10 | 0.153750E+11 | 0.175148E+11 |
Minimum of Months | 0.437422E+09 | 0.115557E+09 | 0.296603E+09 | 97356114.56 | 0.702308E+09 |
Maximum of Months | 0.238719E+10 | 0.112946E+10 | 0.134851E+10 | 0.262916E+10 | 0.246370E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.455786E+09 | 0.115557E+09 | 0.340229E+09 | 97356114.56 | 0.244311E+10 |
February | 0.755388E+09 | 0.268103E+09 | 0.487285E+09 | 0.357673E+09 | 0.190236E+10 |
March | 0.124869E+10 | 0.452036E+09 | 0.796652E+09 | 0.831842E+09 | 0.170230E+10 |
April | 0.187324E+10 | 0.778358E+09 | 0.109488E+10 | 0.165433E+10 | 0.127095E+10 |
May | 0.205974E+10 | 0.716123E+09 | 0.134361E+10 | 0.196261E+10 | 0.107215E+10 |
June | 0.238719E+10 | 0.103868E+10 | 0.134851E+10 | 0.250935E+10 | 0.812269E+09 |
July | 0.229713E+10 | 0.103109E+10 | 0.126605E+10 | 0.256451E+10 | 0.729747E+09 |
August | 0.225776E+10 | 0.112946E+10 | 0.112830E+10 | 0.262916E+10 | 0.702308E+09 |
September | 0.161543E+10 | 0.745052E+09 | 0.870382E+09 | 0.161269E+10 | 0.100454E+10 |
October | 0.108804E+10 | 0.462313E+09 | 0.625723E+09 | 0.826081E+09 | 0.148859E+10 |
November | 0.516092E+09 | 0.145698E+09 | 0.370394E+09 | 0.190429E+09 | 0.192273E+10 |
December | 0.437422E+09 | 0.140819E+09 | 0.296603E+09 | 0.138984E+09 | 0.246370E+10 |
Annual Sum or Average | 0.169919E+11 | 0.702329E+10 | 0.996861E+10 | 0.153750E+11 | 0.175148E+11 |
Minimum of Months | 0.437422E+09 | 0.115557E+09 | 0.296603E+09 | 97356114.56 | 0.702308E+09 |
Maximum of Months | 0.238719E+10 | 0.112946E+10 | 0.134851E+10 | 0.262916E+10 | 0.246370E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.455777E+09 | 0.115555E+09 | 0.340223E+09 | 97354335.66 | 0.244307E+10 |
February | 0.755374E+09 | 0.268098E+09 | 0.487276E+09 | 0.357667E+09 | 0.190233E+10 |
March | 0.124866E+10 | 0.452027E+09 | 0.796637E+09 | 0.831827E+09 | 0.170227E+10 |
April | 0.187320E+10 | 0.778344E+09 | 0.109486E+10 | 0.165430E+10 | 0.127093E+10 |
May | 0.205970E+10 | 0.716110E+09 | 0.134359E+10 | 0.196257E+10 | 0.107213E+10 |
June | 0.238715E+10 | 0.103867E+10 | 0.134848E+10 | 0.250930E+10 | 0.812254E+09 |
July | 0.229709E+10 | 0.103107E+10 | 0.126602E+10 | 0.256446E+10 | 0.729734E+09 |
August | 0.225772E+10 | 0.112944E+10 | 0.112828E+10 | 0.262912E+10 | 0.702295E+09 |
September | 0.161540E+10 | 0.745039E+09 | 0.870366E+09 | 0.161266E+10 | 0.100452E+10 |
October | 0.108802E+10 | 0.462305E+09 | 0.625711E+09 | 0.826066E+09 | 0.148856E+10 |
November | 0.516082E+09 | 0.145695E+09 | 0.370387E+09 | 0.190425E+09 | 0.192270E+10 |
December | 0.437414E+09 | 0.140816E+09 | 0.296597E+09 | 0.138981E+09 | 0.246366E+10 |
Annual Sum or Average | 0.169916E+11 | 0.702316E+10 | 0.996843E+10 | 0.153747E+11 | 0.175144E+11 |
Minimum of Months | 0.437414E+09 | 0.115555E+09 | 0.296597E+09 | 97354335.66 | 0.702295E+09 |
Maximum of Months | 0.238715E+10 | 0.112944E+10 | 0.134848E+10 | 0.262912E+10 | 0.246366E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112793E+10 | 0.669771E+09 | 0.458161E+09 | 0.840439E+09 | 0.198778E+10 |
February | 0.156672E+10 | 0.969823E+09 | 0.596900E+09 | 0.138563E+10 | 0.159344E+10 |
March | 0.186591E+10 | 0.995072E+09 | 0.870843E+09 | 0.176622E+10 | 0.154201E+10 |
April | 0.190650E+10 | 0.827792E+09 | 0.107871E+10 | 0.193161E+10 | 0.124295E+10 |
May | 0.180136E+10 | 0.536643E+09 | 0.126472E+10 | 0.185671E+10 | 0.103742E+10 |
June | 0.159490E+10 | 0.428212E+09 | 0.116669E+10 | 0.168515E+10 | 0.800283E+09 |
July | 0.179729E+10 | 0.658263E+09 | 0.113903E+10 | 0.215610E+10 | 0.745016E+09 |
August | 0.193096E+10 | 0.900439E+09 | 0.103052E+10 | 0.242452E+10 | 0.719763E+09 |
September | 0.207041E+10 | 0.114335E+10 | 0.927062E+09 | 0.241443E+10 | 0.950750E+09 |
October | 0.193796E+10 | 0.119655E+10 | 0.741412E+09 | 0.200953E+10 | 0.133856E+10 |
November | 0.110882E+10 | 0.635450E+09 | 0.473375E+09 | 0.908950E+09 | 0.161145E+10 |
December | 0.119882E+10 | 0.775803E+09 | 0.423016E+09 | 0.101895E+10 | 0.205160E+10 |
Annual Sum or Average | 0.199076E+11 | 0.973717E+10 | 0.101704E+11 | 0.203982E+11 | 0.156210E+11 |
Minimum of Months | 0.110882E+10 | 0.428212E+09 | 0.423016E+09 | 0.840439E+09 | 0.719763E+09 |
Maximum of Months | 0.207041E+10 | 0.119655E+10 | 0.126472E+10 | 0.242452E+10 | 0.205160E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112793E+10 | 0.669771E+09 | 0.458161E+09 | 0.840437E+09 | 0.198778E+10 |
February | 0.156672E+10 | 0.969822E+09 | 0.596900E+09 | 0.138563E+10 | 0.159344E+10 |
March | 0.186591E+10 | 0.995070E+09 | 0.870842E+09 | 0.176622E+10 | 0.154201E+10 |
April | 0.190650E+10 | 0.827791E+09 | 0.107871E+10 | 0.193160E+10 | 0.124295E+10 |
May | 0.180136E+10 | 0.536643E+09 | 0.126471E+10 | 0.185671E+10 | 0.103742E+10 |
June | 0.159490E+10 | 0.428211E+09 | 0.116669E+10 | 0.168515E+10 | 0.800283E+09 |
July | 0.179729E+10 | 0.658262E+09 | 0.113903E+10 | 0.215609E+10 | 0.745016E+09 |
August | 0.193096E+10 | 0.900438E+09 | 0.103052E+10 | 0.242452E+10 | 0.719762E+09 |
September | 0.207041E+10 | 0.114335E+10 | 0.927061E+09 | 0.241443E+10 | 0.950750E+09 |
October | 0.193796E+10 | 0.119654E+10 | 0.741411E+09 | 0.200953E+10 | 0.133856E+10 |
November | 0.110882E+10 | 0.635449E+09 | 0.473374E+09 | 0.908949E+09 | 0.161145E+10 |
December | 0.119882E+10 | 0.775802E+09 | 0.423016E+09 | 0.101895E+10 | 0.205160E+10 |
Annual Sum or Average | 0.199076E+11 | 0.973715E+10 | 0.101704E+11 | 0.203982E+11 | 0.156210E+11 |
Minimum of Months | 0.110882E+10 | 0.428211E+09 | 0.423016E+09 | 0.840437E+09 | 0.719762E+09 |
Maximum of Months | 0.207041E+10 | 0.119654E+10 | 0.126471E+10 | 0.242452E+10 | 0.205160E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112793E+10 | 0.669771E+09 | 0.458161E+09 | 0.840439E+09 | 0.198778E+10 |
February | 0.156672E+10 | 0.969823E+09 | 0.596900E+09 | 0.138563E+10 | 0.159344E+10 |
March | 0.186591E+10 | 0.995072E+09 | 0.870843E+09 | 0.176622E+10 | 0.154201E+10 |
April | 0.190650E+10 | 0.827792E+09 | 0.107871E+10 | 0.193161E+10 | 0.124295E+10 |
May | 0.180136E+10 | 0.536643E+09 | 0.126472E+10 | 0.185671E+10 | 0.103742E+10 |
June | 0.159490E+10 | 0.428212E+09 | 0.116669E+10 | 0.168515E+10 | 0.800283E+09 |
July | 0.179729E+10 | 0.658263E+09 | 0.113903E+10 | 0.215610E+10 | 0.745016E+09 |
August | 0.193096E+10 | 0.900439E+09 | 0.103052E+10 | 0.242452E+10 | 0.719763E+09 |
September | 0.207041E+10 | 0.114335E+10 | 0.927062E+09 | 0.241443E+10 | 0.950750E+09 |
October | 0.193796E+10 | 0.119655E+10 | 0.741412E+09 | 0.200953E+10 | 0.133856E+10 |
November | 0.110882E+10 | 0.635450E+09 | 0.473375E+09 | 0.908950E+09 | 0.161145E+10 |
December | 0.119882E+10 | 0.775803E+09 | 0.423016E+09 | 0.101895E+10 | 0.205160E+10 |
Annual Sum or Average | 0.199076E+11 | 0.973717E+10 | 0.101704E+11 | 0.203982E+11 | 0.156210E+11 |
Minimum of Months | 0.110882E+10 | 0.428212E+09 | 0.423016E+09 | 0.840439E+09 | 0.719763E+09 |
Maximum of Months | 0.207041E+10 | 0.119655E+10 | 0.126472E+10 | 0.242452E+10 | 0.205160E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112793E+10 | 0.669771E+09 | 0.458161E+09 | 0.840437E+09 | 0.198778E+10 |
February | 0.156672E+10 | 0.969822E+09 | 0.596900E+09 | 0.138563E+10 | 0.159344E+10 |
March | 0.186591E+10 | 0.995070E+09 | 0.870842E+09 | 0.176622E+10 | 0.154201E+10 |
April | 0.190650E+10 | 0.827791E+09 | 0.107871E+10 | 0.193160E+10 | 0.124295E+10 |
May | 0.180136E+10 | 0.536643E+09 | 0.126471E+10 | 0.185671E+10 | 0.103742E+10 |
June | 0.159490E+10 | 0.428211E+09 | 0.116669E+10 | 0.168515E+10 | 0.800283E+09 |
July | 0.179729E+10 | 0.658262E+09 | 0.113903E+10 | 0.215609E+10 | 0.745016E+09 |
August | 0.193096E+10 | 0.900438E+09 | 0.103052E+10 | 0.242452E+10 | 0.719762E+09 |
September | 0.207041E+10 | 0.114335E+10 | 0.927061E+09 | 0.241443E+10 | 0.950750E+09 |
October | 0.193796E+10 | 0.119654E+10 | 0.741411E+09 | 0.200953E+10 | 0.133856E+10 |
November | 0.110882E+10 | 0.635449E+09 | 0.473374E+09 | 0.908949E+09 | 0.161145E+10 |
December | 0.119882E+10 | 0.775802E+09 | 0.423016E+09 | 0.101895E+10 | 0.205160E+10 |
Annual Sum or Average | 0.199076E+11 | 0.973715E+10 | 0.101704E+11 | 0.203982E+11 | 0.156210E+11 |
Minimum of Months | 0.110882E+10 | 0.428211E+09 | 0.423016E+09 | 0.840437E+09 | 0.719762E+09 |
Maximum of Months | 0.207041E+10 | 0.119654E+10 | 0.126471E+10 | 0.242452E+10 | 0.205160E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112789E+10 | 0.669744E+09 | 0.458143E+09 | 0.840405E+09 | 0.198770E+10 |
February | 0.156666E+10 | 0.969784E+09 | 0.596876E+09 | 0.138557E+10 | 0.159337E+10 |
March | 0.186584E+10 | 0.995032E+09 | 0.870807E+09 | 0.176615E+10 | 0.154195E+10 |
April | 0.190642E+10 | 0.827759E+09 | 0.107867E+10 | 0.193153E+10 | 0.124290E+10 |
May | 0.180129E+10 | 0.536622E+09 | 0.126467E+10 | 0.185663E+10 | 0.103738E+10 |
June | 0.159484E+10 | 0.428194E+09 | 0.116665E+10 | 0.168509E+10 | 0.800251E+09 |
July | 0.179722E+10 | 0.658237E+09 | 0.113898E+10 | 0.215601E+10 | 0.744986E+09 |
August | 0.193088E+10 | 0.900403E+09 | 0.103048E+10 | 0.242442E+10 | 0.719734E+09 |
September | 0.207033E+10 | 0.114330E+10 | 0.927025E+09 | 0.241433E+10 | 0.950712E+09 |
October | 0.193788E+10 | 0.119650E+10 | 0.741382E+09 | 0.200945E+10 | 0.133850E+10 |
November | 0.110878E+10 | 0.635424E+09 | 0.473356E+09 | 0.908914E+09 | 0.161138E+10 |
December | 0.119877E+10 | 0.775772E+09 | 0.422999E+09 | 0.101891E+10 | 0.205151E+10 |
Annual Sum or Average | 0.199068E+11 | 0.973677E+10 | 0.101700E+11 | 0.203974E+11 | 0.156204E+11 |
Minimum of Months | 0.110878E+10 | 0.428194E+09 | 0.422999E+09 | 0.840405E+09 | 0.719734E+09 |
Maximum of Months | 0.207033E+10 | 0.119650E+10 | 0.126467E+10 | 0.242442E+10 | 0.205151E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.480743E+09 | 0.141762E+09 | 0.338980E+09 | 0.135821E+09 | 0.259687E+10 |
February | 0.778521E+09 | 0.292590E+09 | 0.485931E+09 | 0.408677E+09 | 0.206023E+10 |
March | 0.120779E+10 | 0.407661E+09 | 0.800128E+09 | 0.790753E+09 | 0.192624E+10 |
April | 0.177825E+10 | 0.679892E+09 | 0.109835E+10 | 0.150110E+10 | 0.154724E+10 |
May | 0.236446E+10 | 0.960553E+09 | 0.140391E+10 | 0.233951E+10 | 0.123612E+10 |
June | 0.220061E+10 | 0.854425E+09 | 0.134619E+10 | 0.223529E+10 | 0.969771E+09 |
July | 0.280917E+10 | 0.147665E+10 | 0.133253E+10 | 0.321993E+10 | 0.955172E+09 |
August | 0.232386E+10 | 0.118663E+10 | 0.113723E+10 | 0.269038E+10 | 0.960898E+09 |
September | 0.183138E+10 | 0.878738E+09 | 0.952646E+09 | 0.193354E+10 | 0.116768E+10 |
October | 0.107737E+10 | 0.438975E+09 | 0.638391E+09 | 0.822371E+09 | 0.168197E+10 |
November | 0.519214E+09 | 0.146440E+09 | 0.372774E+09 | 0.194259E+09 | 0.212148E+10 |
December | 0.451050E+09 | 0.154563E+09 | 0.296487E+09 | 0.169173E+09 | 0.273982E+10 |
Annual Sum or Average | 0.178224E+11 | 0.761888E+10 | 0.102035E+11 | 0.164408E+11 | 0.199635E+11 |
Minimum of Months | 0.451050E+09 | 0.141762E+09 | 0.296487E+09 | 0.135821E+09 | 0.955172E+09 |
Maximum of Months | 0.280917E+10 | 0.147665E+10 | 0.140391E+10 | 0.321993E+10 | 0.273982E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.480743E+09 | 0.141762E+09 | 0.338980E+09 | 0.135821E+09 | 0.259687E+10 |
February | 0.778521E+09 | 0.292590E+09 | 0.485931E+09 | 0.408677E+09 | 0.206023E+10 |
March | 0.120779E+10 | 0.407661E+09 | 0.800128E+09 | 0.790753E+09 | 0.192624E+10 |
April | 0.177825E+10 | 0.679892E+09 | 0.109835E+10 | 0.150110E+10 | 0.154724E+10 |
May | 0.236446E+10 | 0.960553E+09 | 0.140391E+10 | 0.233951E+10 | 0.123612E+10 |
June | 0.220061E+10 | 0.854425E+09 | 0.134619E+10 | 0.223529E+10 | 0.969771E+09 |
July | 0.280917E+10 | 0.147665E+10 | 0.133253E+10 | 0.321993E+10 | 0.955172E+09 |
August | 0.232386E+10 | 0.118663E+10 | 0.113723E+10 | 0.269038E+10 | 0.960898E+09 |
September | 0.183138E+10 | 0.878738E+09 | 0.952646E+09 | 0.193354E+10 | 0.116768E+10 |
October | 0.107737E+10 | 0.438975E+09 | 0.638391E+09 | 0.822371E+09 | 0.168197E+10 |
November | 0.519214E+09 | 0.146440E+09 | 0.372774E+09 | 0.194259E+09 | 0.212148E+10 |
December | 0.451050E+09 | 0.154563E+09 | 0.296487E+09 | 0.169173E+09 | 0.273982E+10 |
Annual Sum or Average | 0.178224E+11 | 0.761888E+10 | 0.102035E+11 | 0.164408E+11 | 0.199635E+11 |
Minimum of Months | 0.451050E+09 | 0.141762E+09 | 0.296487E+09 | 0.135821E+09 | 0.955172E+09 |
Maximum of Months | 0.280917E+10 | 0.147665E+10 | 0.140391E+10 | 0.321993E+10 | 0.273982E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.480734E+09 | 0.141760E+09 | 0.338974E+09 | 0.135818E+09 | 0.259682E+10 |
February | 0.778507E+09 | 0.292585E+09 | 0.485922E+09 | 0.408669E+09 | 0.206020E+10 |
March | 0.120777E+10 | 0.407654E+09 | 0.800114E+09 | 0.790739E+09 | 0.192620E+10 |
April | 0.177821E+10 | 0.679880E+09 | 0.109833E+10 | 0.150107E+10 | 0.154721E+10 |
May | 0.236442E+10 | 0.960536E+09 | 0.140388E+10 | 0.233947E+10 | 0.123609E+10 |
June | 0.220057E+10 | 0.854409E+09 | 0.134616E+10 | 0.223525E+10 | 0.969754E+09 |
July | 0.280912E+10 | 0.147662E+10 | 0.133250E+10 | 0.321987E+10 | 0.955154E+09 |
August | 0.232382E+10 | 0.118661E+10 | 0.113721E+10 | 0.269033E+10 | 0.960881E+09 |
September | 0.183135E+10 | 0.878722E+09 | 0.952628E+09 | 0.193351E+10 | 0.116765E+10 |
October | 0.107735E+10 | 0.438967E+09 | 0.638379E+09 | 0.822356E+09 | 0.168194E+10 |
November | 0.519205E+09 | 0.146437E+09 | 0.372768E+09 | 0.194255E+09 | 0.212144E+10 |
December | 0.451042E+09 | 0.154561E+09 | 0.296481E+09 | 0.169169E+09 | 0.273977E+10 |
Annual Sum or Average | 0.178221E+11 | 0.761874E+10 | 0.102034E+11 | 0.164405E+11 | 0.199631E+11 |
Minimum of Months | 0.451042E+09 | 0.141760E+09 | 0.296481E+09 | 0.135818E+09 | 0.955154E+09 |
Maximum of Months | 0.280912E+10 | 0.147662E+10 | 0.140388E+10 | 0.321987E+10 | 0.273977E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127641E+10 | 0.00 | 0.127641E+10 | 4036850.79 | 0.105185E+11 |
February | 0.179393E+10 | 0.00 | 0.179393E+10 | 0.176827E+09 | 0.851575E+10 |
March | 0.292626E+10 | 0.00 | 0.292626E+10 | 0.696640E+09 | 0.761705E+10 |
April | 0.400737E+10 | 14215362.16 | 0.399315E+10 | 0.195075E+10 | 0.575621E+10 |
May | 0.532836E+10 | 0.158298E+09 | 0.517006E+10 | 0.351131E+10 | 0.472255E+10 |
June | 0.542191E+10 | 0.358040E+09 | 0.506387E+10 | 0.406137E+10 | 0.352155E+10 |
July | 0.532500E+10 | 0.417505E+09 | 0.490750E+10 | 0.478570E+10 | 0.323738E+10 |
August | 0.431063E+10 | 0.116529E+09 | 0.419410E+10 | 0.400110E+10 | 0.318426E+10 |
September | 0.324033E+10 | 955524.19 | 0.323937E+10 | 0.202759E+10 | 0.455856E+10 |
October | 0.229417E+10 | 0.00 | 0.229417E+10 | 0.658379E+09 | 0.655274E+10 |
November | 0.139849E+10 | 0.00 | 0.139849E+10 | 81661005.06 | 0.826821E+10 |
December | 0.108462E+10 | 0.00 | 0.108462E+10 | 2398717.01 | 0.106015E+11 |
Annual Sum or Average | 0.384075E+11 | 0.106554E+10 | 0.373419E+11 | 0.219578E+11 | 0.770543E+11 |
Minimum of Months | 0.108462E+10 | 0.00 | 0.108462E+10 | 2398717.01 | 0.318426E+10 |
Maximum of Months | 0.542191E+10 | 0.417505E+09 | 0.517006E+10 | 0.478570E+10 | 0.106015E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136734E+10 | 0.346667E+09 | 0.102068E+10 | 0.313504E+09 | 0.667131E+10 |
February | 0.226614E+10 | 0.804301E+09 | 0.146184E+10 | 0.111957E+10 | 0.532832E+10 |
March | 0.374602E+10 | 0.135609E+10 | 0.238993E+10 | 0.248672E+10 | 0.481097E+10 |
April | 0.561966E+10 | 0.233505E+10 | 0.328461E+10 | 0.493647E+10 | 0.360309E+10 |
May | 0.617914E+10 | 0.214835E+10 | 0.403080E+10 | 0.583605E+10 | 0.306954E+10 |
June | 0.716151E+10 | 0.311602E+10 | 0.404548E+10 | 0.744006E+10 | 0.233187E+10 |
July | 0.689132E+10 | 0.309322E+10 | 0.379810E+10 | 0.763481E+10 | 0.208374E+10 |
August | 0.677321E+10 | 0.338835E+10 | 0.338486E+10 | 0.781865E+10 | 0.202859E+10 |
September | 0.484625E+10 | 0.223513E+10 | 0.261112E+10 | 0.480727E+10 | 0.285091E+10 |
October | 0.326407E+10 | 0.138692E+10 | 0.187715E+10 | 0.248265E+10 | 0.416020E+10 |
November | 0.154826E+10 | 0.437089E+09 | 0.111117E+10 | 0.594455E+09 | 0.531339E+10 |
December | 0.131225E+10 | 0.422453E+09 | 0.889799E+09 | 0.438604E+09 | 0.678583E+10 |
Annual Sum or Average | 0.509752E+11 | 0.210697E+11 | 0.299055E+11 | 0.459088E+11 | 0.490378E+11 |
Minimum of Months | 0.131225E+10 | 0.346667E+09 | 0.889799E+09 | 0.313504E+09 | 0.202859E+10 |
Maximum of Months | 0.716151E+10 | 0.338835E+10 | 0.404548E+10 | 0.781865E+10 | 0.678583E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.563959E+10 | 0.334882E+10 | 0.229078E+10 | 0.419913E+10 | 0.950077E+10 |
February | 0.783352E+10 | 0.484906E+10 | 0.298447E+10 | 0.688612E+10 | 0.775266E+10 |
March | 0.932946E+10 | 0.497530E+10 | 0.435416E+10 | 0.874580E+10 | 0.749129E+10 |
April | 0.953239E+10 | 0.413891E+10 | 0.539348E+10 | 0.958127E+10 | 0.601332E+10 |
May | 0.900669E+10 | 0.268318E+10 | 0.632350E+10 | 0.918594E+10 | 0.505980E+10 |
June | 0.797443E+10 | 0.214103E+10 | 0.583339E+10 | 0.837960E+10 | 0.384683E+10 |
July | 0.898634E+10 | 0.329128E+10 | 0.569506E+10 | 0.107400E+11 | 0.354159E+10 |
August | 0.965469E+10 | 0.450214E+10 | 0.515255E+10 | 0.120901E+11 | 0.343015E+10 |
September | 0.103519E+11 | 0.571668E+10 | 0.463525E+10 | 0.120019E+11 | 0.463878E+10 |
October | 0.968967E+10 | 0.598266E+10 | 0.370701E+10 | 0.994230E+10 | 0.651450E+10 |
November | 0.554405E+10 | 0.317721E+10 | 0.236684E+10 | 0.454652E+10 | 0.774313E+10 |
December | 0.599402E+10 | 0.387897E+10 | 0.211505E+10 | 0.510518E+10 | 0.980715E+10 |
Annual Sum or Average | 0.995368E+11 | 0.486852E+11 | 0.508516E+11 | 0.101404E+12 | 0.753400E+11 |
Minimum of Months | 0.554405E+10 | 0.214103E+10 | 0.211505E+10 | 0.419913E+10 | 0.343015E+10 |
Maximum of Months | 0.103519E+11 | 0.598266E+10 | 0.632350E+10 | 0.120901E+11 | 0.980715E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144221E+10 | 0.425283E+09 | 0.101693E+10 | 0.434857E+09 | 0.687288E+10 |
February | 0.233554E+10 | 0.877761E+09 | 0.145778E+10 | 0.130904E+10 | 0.549907E+10 |
March | 0.362333E+10 | 0.122297E+10 | 0.240036E+10 | 0.250471E+10 | 0.503470E+10 |
April | 0.533469E+10 | 0.203966E+10 | 0.329503E+10 | 0.471631E+10 | 0.399496E+10 |
May | 0.709332E+10 | 0.288163E+10 | 0.421169E+10 | 0.709436E+10 | 0.340906E+10 |
June | 0.660177E+10 | 0.256325E+10 | 0.403852E+10 | 0.683286E+10 | 0.259490E+10 |
July | 0.842744E+10 | 0.442989E+10 | 0.399755E+10 | 0.980784E+10 | 0.249157E+10 |
August | 0.697151E+10 | 0.355985E+10 | 0.341165E+10 | 0.829983E+10 | 0.239638E+10 |
September | 0.549409E+10 | 0.263619E+10 | 0.285791E+10 | 0.590172E+10 | 0.314955E+10 |
October | 0.323206E+10 | 0.131691E+10 | 0.191515E+10 | 0.258541E+10 | 0.441425E+10 |
November | 0.155763E+10 | 0.439316E+09 | 0.111831E+10 | 0.651962E+09 | 0.542063E+10 |
December | 0.135314E+10 | 0.463686E+09 | 0.889451E+09 | 0.568065E+09 | 0.698662E+10 |
Annual Sum or Average | 0.534667E+11 | 0.228564E+11 | 0.306103E+11 | 0.507070E+11 | 0.522646E+11 |
Minimum of Months | 0.135314E+10 | 0.425283E+09 | 0.889451E+09 | 0.434857E+09 | 0.239638E+10 |
Maximum of Months | 0.842744E+10 | 0.442989E+10 | 0.421169E+10 | 0.980784E+10 | 0.698662E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127641E+10 | 0.00 | 0.127641E+10 | 18214039.73 | 0.976457E+10 |
February | 0.179393E+10 | 0.00 | 0.179393E+10 | 0.230320E+09 | 0.778606E+10 |
March | 0.292626E+10 | 0.00 | 0.292626E+10 | 0.825301E+09 | 0.682799E+10 |
April | 0.400737E+10 | 14215362.16 | 0.399315E+10 | 0.210836E+10 | 0.521008E+10 |
May | 0.532836E+10 | 0.158298E+09 | 0.517006E+10 | 0.367281E+10 | 0.429972E+10 |
June | 0.542191E+10 | 0.358040E+09 | 0.506387E+10 | 0.417472E+10 | 0.326941E+10 |
July | 0.532500E+10 | 0.417505E+09 | 0.490750E+10 | 0.485821E+10 | 0.302880E+10 |
August | 0.431063E+10 | 0.116529E+09 | 0.419410E+10 | 0.409214E+10 | 0.293624E+10 |
September | 0.324033E+10 | 955524.19 | 0.323937E+10 | 0.218149E+10 | 0.405752E+10 |
October | 0.229417E+10 | 0.00 | 0.229417E+10 | 0.824731E+09 | 0.574125E+10 |
November | 0.139849E+10 | 0.00 | 0.139849E+10 | 0.121926E+09 | 0.729796E+10 |
December | 0.108462E+10 | 0.00 | 0.108462E+10 | 15960248.92 | 0.956638E+10 |
Annual Sum or Average | 0.384075E+11 | 0.106554E+10 | 0.373419E+11 | 0.231242E+11 | 0.697860E+11 |
Minimum of Months | 0.108462E+10 | 0.00 | 0.108462E+10 | 15960248.92 | 0.293624E+10 |
Maximum of Months | 0.542191E+10 | 0.417505E+09 | 0.517006E+10 | 0.485821E+10 | 0.976457E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136734E+10 | 0.346667E+09 | 0.102068E+10 | 0.350365E+09 | 0.618272E+10 |
February | 0.226614E+10 | 0.804301E+09 | 0.146184E+10 | 0.121895E+10 | 0.485133E+10 |
March | 0.374602E+10 | 0.135609E+10 | 0.238993E+10 | 0.264390E+10 | 0.432132E+10 |
April | 0.561966E+10 | 0.233505E+10 | 0.328461E+10 | 0.507013E+10 | 0.330195E+10 |
May | 0.617914E+10 | 0.214835E+10 | 0.403080E+10 | 0.593230E+10 | 0.285705E+10 |
June | 0.716151E+10 | 0.311602E+10 | 0.404548E+10 | 0.746609E+10 | 0.221800E+10 |
July | 0.689132E+10 | 0.309322E+10 | 0.379810E+10 | 0.764508E+10 | 0.200077E+10 |
August | 0.677321E+10 | 0.338835E+10 | 0.338486E+10 | 0.785472E+10 | 0.192793E+10 |
September | 0.484625E+10 | 0.223513E+10 | 0.261112E+10 | 0.490275E+10 | 0.259878E+10 |
October | 0.326407E+10 | 0.138692E+10 | 0.187715E+10 | 0.264430E+10 | 0.368369E+10 |
November | 0.154826E+10 | 0.437089E+09 | 0.111117E+10 | 0.666535E+09 | 0.469034E+10 |
December | 0.131225E+10 | 0.422453E+09 | 0.889799E+09 | 0.490570E+09 | 0.612045E+10 |
Annual Sum or Average | 0.509752E+11 | 0.210697E+11 | 0.299055E+11 | 0.468857E+11 | 0.447543E+11 |
Minimum of Months | 0.131225E+10 | 0.346667E+09 | 0.889799E+09 | 0.350365E+09 | 0.192793E+10 |
Maximum of Months | 0.716151E+10 | 0.338835E+10 | 0.404548E+10 | 0.785472E+10 | 0.618272E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.563959E+10 | 0.334882E+10 | 0.229078E+10 | 0.433314E+10 | 0.873993E+10 |
February | 0.783352E+10 | 0.484906E+10 | 0.298447E+10 | 0.705778E+10 | 0.707231E+10 |
March | 0.932946E+10 | 0.497530E+10 | 0.435416E+10 | 0.886746E+10 | 0.679231E+10 |
April | 0.953239E+10 | 0.413891E+10 | 0.539348E+10 | 0.967607E+10 | 0.553619E+10 |
May | 0.900669E+10 | 0.268318E+10 | 0.632350E+10 | 0.923827E+10 | 0.469719E+10 |
June | 0.797443E+10 | 0.214103E+10 | 0.583339E+10 | 0.836538E+10 | 0.363599E+10 |
July | 0.898634E+10 | 0.329128E+10 | 0.569506E+10 | 0.107008E+11 | 0.337730E+10 |
August | 0.965469E+10 | 0.450214E+10 | 0.515255E+10 | 0.120848E+11 | 0.323781E+10 |
September | 0.103519E+11 | 0.571668E+10 | 0.463525E+10 | 0.120722E+11 | 0.424433E+10 |
October | 0.968967E+10 | 0.598266E+10 | 0.370701E+10 | 0.100976E+11 | 0.583106E+10 |
November | 0.554405E+10 | 0.317721E+10 | 0.236684E+10 | 0.470617E+10 | 0.689782E+10 |
December | 0.599402E+10 | 0.387897E+10 | 0.211505E+10 | 0.525544E+10 | 0.886276E+10 |
Annual Sum or Average | 0.995368E+11 | 0.486852E+11 | 0.508516E+11 | 0.102455E+12 | 0.689250E+11 |
Minimum of Months | 0.554405E+10 | 0.214103E+10 | 0.211505E+10 | 0.433314E+10 | 0.323781E+10 |
Maximum of Months | 0.103519E+11 | 0.598266E+10 | 0.632350E+10 | 0.120848E+11 | 0.886276E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144221E+10 | 0.425283E+09 | 0.101693E+10 | 0.454775E+09 | 0.642955E+10 |
February | 0.233554E+10 | 0.877761E+09 | 0.145778E+10 | 0.134974E+10 | 0.510295E+10 |
March | 0.362333E+10 | 0.122297E+10 | 0.240036E+10 | 0.253822E+10 | 0.463239E+10 |
April | 0.533469E+10 | 0.203966E+10 | 0.329503E+10 | 0.474039E+10 | 0.372154E+10 |
May | 0.709332E+10 | 0.288163E+10 | 0.421169E+10 | 0.709387E+10 | 0.319225E+10 |
June | 0.660177E+10 | 0.256325E+10 | 0.403852E+10 | 0.680018E+10 | 0.246349E+10 |
July | 0.842744E+10 | 0.442989E+10 | 0.399755E+10 | 0.975943E+10 | 0.238259E+10 |
August | 0.697151E+10 | 0.355985E+10 | 0.341165E+10 | 0.828051E+10 | 0.227719E+10 |
September | 0.549409E+10 | 0.263619E+10 | 0.285791E+10 | 0.592187E+10 | 0.291612E+10 |
October | 0.323206E+10 | 0.131691E+10 | 0.191515E+10 | 0.263604E+10 | 0.402745E+10 |
November | 0.155763E+10 | 0.439316E+09 | 0.111831E+10 | 0.681647E+09 | 0.492323E+10 |
December | 0.135314E+10 | 0.463686E+09 | 0.889451E+09 | 0.592598E+09 | 0.641717E+10 |
Annual Sum or Average | 0.534667E+11 | 0.228564E+11 | 0.306103E+11 | 0.508493E+11 | 0.484859E+11 |
Minimum of Months | 0.135314E+10 | 0.425283E+09 | 0.889451E+09 | 0.454775E+09 | 0.227719E+10 |
Maximum of Months | 0.842744E+10 | 0.442989E+10 | 0.421169E+10 | 0.975943E+10 | 0.642955E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.11 | 4426.50 | 476.56 | 0.00 | 476.56 | 0.00 | 0.00 |
February | 46.63 | 3928.99 | 741.54 | 0.00 | 741.54 | 0.00 | 0.00 |
March | 199.34 | 3183.63 | 1092.54 | 0.00 | 1092.54 | 0.00 | 0.00 |
April | 660.16 | 2481.26 | 1546.06 | 5.48 | 1540.57 | 0.00 | 0.00 |
May | 1251.45 | 1902.18 | 1989.39 | 59.10 | 1930.29 | 0.00 | 0.00 |
June | 1511.18 | 1462.43 | 2091.79 | 138.13 | 1953.66 | 0.00 | 0.00 |
July | 1720.49 | 1321.16 | 1988.14 | 155.88 | 1832.26 | 0.00 | 0.00 |
August | 1426.39 | 1320.72 | 1609.41 | 43.51 | 1565.90 | 0.00 | 0.00 |
September | 725.60 | 1939.49 | 1250.13 | 0.37 | 1249.76 | 0.00 | 0.00 |
October | 185.51 | 2774.36 | 856.55 | 0.00 | 856.55 | 0.00 | 0.00 |
November | 17.46 | 3664.95 | 539.54 | 0.00 | 539.54 | 0.00 | 0.00 |
December | 0.01 | 4494.29 | 404.95 | 0.00 | 404.95 | 0.00 | 0.00 |
Annual Sum or Average | 649.37 | 2735.79 | 1217.90 | 33.79 | 1184.11 | 0.00 | 0.00 |
Minimum of Months | 0.01 | 1320.72 | 404.95 | 0.00 | 404.95 | 0.00 | 0.00 |
Maximum of Months | 1720.49 | 4494.29 | 2091.79 | 155.88 | 1953.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 109.05 | 2736.44 | 510.51 | 129.43 | 381.08 | 0.00 | 0.00 |
February | 443.54 | 2359.06 | 936.74 | 332.47 | 604.27 | 0.00 | 0.00 |
March | 931.72 | 1906.68 | 1398.61 | 506.31 | 892.30 | 0.00 | 0.00 |
April | 1914.72 | 1471.00 | 2168.09 | 900.87 | 1267.21 | 0.00 | 0.00 |
May | 2198.25 | 1200.87 | 2307.04 | 802.10 | 1504.93 | 0.00 | 0.00 |
June | 2904.32 | 940.12 | 2762.94 | 1202.17 | 1560.76 | 0.00 | 0.00 |
July | 2872.42 | 817.36 | 2572.94 | 1154.88 | 1418.05 | 0.00 | 0.00 |
August | 2944.83 | 786.63 | 2528.84 | 1265.07 | 1263.77 | 0.00 | 0.00 |
September | 1866.53 | 1162.65 | 1869.70 | 862.32 | 1007.38 | 0.00 | 0.00 |
October | 925.26 | 1667.32 | 1218.67 | 517.82 | 700.85 | 0.00 | 0.00 |
November | 220.40 | 2225.37 | 597.32 | 168.63 | 428.69 | 0.00 | 0.00 |
December | 155.67 | 2759.50 | 489.94 | 157.73 | 332.21 | 0.00 | 0.00 |
Annual Sum or Average | 1462.61 | 1666.16 | 1616.42 | 668.12 | 948.30 | 0.00 | 0.00 |
Minimum of Months | 109.05 | 786.63 | 489.94 | 129.43 | 332.21 | 0.00 | 0.00 |
Maximum of Months | 2944.83 | 2759.50 | 2762.94 | 1265.07 | 1560.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1568.91 | 3710.73 | 2105.59 | 1250.31 | 855.28 | 0.00 | 0.00 |
February | 2863.79 | 3293.29 | 3238.08 | 2004.41 | 1233.66 | 0.00 | 0.00 |
March | 3297.13 | 2878.58 | 3483.23 | 1857.57 | 1625.66 | 0.00 | 0.00 |
April | 3726.06 | 2397.64 | 3677.63 | 1596.81 | 2080.83 | 0.00 | 0.00 |
May | 3466.05 | 1936.63 | 3362.72 | 1001.79 | 2360.93 | 0.00 | 0.00 |
June | 3250.66 | 1543.74 | 3076.56 | 826.02 | 2250.55 | 0.00 | 0.00 |
July | 4024.94 | 1390.77 | 3355.13 | 1228.83 | 2126.30 | 0.00 | 0.00 |
August | 4526.02 | 1343.63 | 3604.66 | 1680.91 | 1923.75 | 0.00 | 0.00 |
September | 4657.42 | 1833.99 | 3993.82 | 2205.52 | 1788.30 | 0.00 | 0.00 |
October | 3751.34 | 2498.78 | 3617.72 | 2233.68 | 1384.05 | 0.00 | 0.00 |
November | 1753.36 | 3108.48 | 2138.92 | 1225.78 | 913.14 | 0.00 | 0.00 |
December | 1902.15 | 3829.86 | 2237.92 | 1448.25 | 789.67 | 0.00 | 0.00 |
Annual Sum or Average | 3234.09 | 2476.68 | 3156.30 | 1543.80 | 1612.50 | 0.00 | 0.00 |
Minimum of Months | 1568.91 | 1343.63 | 2105.59 | 826.02 | 789.67 | 0.00 | 0.00 |
Maximum of Months | 4657.42 | 3829.86 | 3993.82 | 2233.68 | 2360.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 152.13 | 2908.66 | 538.46 | 158.78 | 379.68 | 0.00 | 0.00 |
February | 506.79 | 2554.84 | 965.42 | 362.83 | 602.59 | 0.00 | 0.00 |
March | 885.69 | 2157.51 | 1352.80 | 456.61 | 896.20 | 0.00 | 0.00 |
April | 1737.37 | 1790.77 | 2058.14 | 786.91 | 1271.24 | 0.00 | 0.00 |
May | 2620.40 | 1384.53 | 2648.35 | 1075.88 | 1572.47 | 0.00 | 0.00 |
June | 2587.13 | 1122.41 | 2546.99 | 988.91 | 1558.08 | 0.00 | 0.00 |
July | 3606.53 | 1069.85 | 3146.46 | 1653.94 | 1492.52 | 0.00 | 0.00 |
August | 3013.40 | 1076.27 | 2602.87 | 1329.10 | 1273.77 | 0.00 | 0.00 |
September | 2237.88 | 1351.47 | 2119.64 | 1017.05 | 1102.59 | 0.00 | 0.00 |
October | 921.11 | 1883.91 | 1206.72 | 491.68 | 715.04 | 0.00 | 0.00 |
November | 224.84 | 2455.40 | 600.94 | 169.49 | 431.45 | 0.00 | 0.00 |
December | 189.48 | 3068.78 | 505.21 | 173.12 | 332.08 | 0.00 | 0.00 |
Annual Sum or Average | 1563.99 | 1899.10 | 1695.43 | 724.77 | 970.65 | 0.00 | 0.00 |
Minimum of Months | 152.13 | 1069.85 | 505.21 | 158.78 | 332.08 | 0.00 | 0.00 |
Maximum of Months | 3606.53 | 3068.78 | 3146.46 | 1653.94 | 1572.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.51 | 3927.17 | 476.56 | 0.00 | 476.56 | 0.00 | 0.00 |
February | 73.09 | 3520.07 | 741.54 | 0.00 | 741.54 | 0.00 | 0.00 |
March | 260.10 | 2843.88 | 1092.54 | 0.00 | 1092.54 | 0.00 | 0.00 |
April | 752.60 | 2220.76 | 1546.05 | 5.48 | 1540.57 | 0.00 | 0.00 |
May | 1310.97 | 1763.20 | 1989.38 | 59.10 | 1930.28 | 0.00 | 0.00 |
June | 1566.89 | 1358.62 | 2091.79 | 138.13 | 1953.65 | 0.00 | 0.00 |
July | 1786.77 | 1208.70 | 1988.13 | 155.88 | 1832.25 | 0.00 | 0.00 |
August | 1493.84 | 1188.87 | 1609.40 | 43.51 | 1565.90 | 0.00 | 0.00 |
September | 782.25 | 1758.71 | 1250.13 | 0.37 | 1249.76 | 0.00 | 0.00 |
October | 245.81 | 2446.51 | 856.55 | 0.00 | 856.55 | 0.00 | 0.00 |
November | 31.51 | 3189.89 | 539.54 | 0.00 | 539.54 | 0.00 | 0.00 |
December | 0.90 | 3958.16 | 404.95 | 0.00 | 404.95 | 0.00 | 0.00 |
Annual Sum or Average | 696.28 | 2443.38 | 1217.89 | 33.79 | 1184.10 | 0.00 | 0.00 |
Minimum of Months | 0.90 | 1188.87 | 404.95 | 0.00 | 404.95 | 0.00 | 0.00 |
Maximum of Months | 1786.77 | 3958.16 | 2091.79 | 155.88 | 1953.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 117.05 | 2490.78 | 510.51 | 129.43 | 381.08 | 0.00 | 0.00 |
February | 462.78 | 2202.51 | 936.73 | 332.47 | 604.27 | 0.00 | 0.00 |
March | 928.44 | 1796.21 | 1398.61 | 506.31 | 892.30 | 0.00 | 0.00 |
April | 1904.50 | 1390.08 | 2168.08 | 900.87 | 1267.21 | 0.00 | 0.00 |
May | 2178.93 | 1146.03 | 2307.03 | 802.10 | 1504.93 | 0.00 | 0.00 |
June | 2870.39 | 899.64 | 2762.93 | 1202.17 | 1560.76 | 0.00 | 0.00 |
July | 2850.51 | 777.98 | 2572.93 | 1154.88 | 1418.05 | 0.00 | 0.00 |
August | 2919.15 | 757.39 | 2528.83 | 1265.06 | 1263.76 | 0.00 | 0.00 |
September | 1854.66 | 1099.89 | 1869.70 | 862.32 | 1007.38 | 0.00 | 0.00 |
October | 926.92 | 1553.24 | 1218.67 | 517.82 | 700.85 | 0.00 | 0.00 |
November | 229.34 | 2049.92 | 597.32 | 168.63 | 428.69 | 0.00 | 0.00 |
December | 163.76 | 2533.54 | 489.94 | 157.73 | 332.21 | 0.00 | 0.00 |
Annual Sum or Average | 1455.76 | 1554.98 | 1616.41 | 668.11 | 948.30 | 0.00 | 0.00 |
Minimum of Months | 117.05 | 757.39 | 489.94 | 129.43 | 332.21 | 0.00 | 0.00 |
Maximum of Months | 2919.15 | 2533.54 | 2762.93 | 1265.06 | 1560.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1567.77 | 3547.18 | 2105.58 | 1250.30 | 855.28 | 0.00 | 0.00 |
February | 2846.44 | 3204.64 | 3238.06 | 2004.41 | 1233.66 | 0.00 | 0.00 |
March | 3265.31 | 2796.93 | 3483.22 | 1857.56 | 1625.66 | 0.00 | 0.00 |
April | 3696.48 | 2319.95 | 3677.62 | 1596.80 | 2080.82 | 0.00 | 0.00 |
May | 3429.64 | 1889.11 | 3362.71 | 1001.79 | 2360.93 | 0.00 | 0.00 |
June | 3232.87 | 1484.12 | 3076.55 | 826.02 | 2250.54 | 0.00 | 0.00 |
July | 4009.87 | 1322.28 | 3355.12 | 1228.82 | 2126.29 | 0.00 | 0.00 |
August | 4513.93 | 1280.67 | 3604.65 | 1680.91 | 1923.74 | 0.00 | 0.00 |
September | 4630.37 | 1789.65 | 3993.80 | 2205.51 | 1788.29 | 0.00 | 0.00 |
October | 3712.03 | 2432.24 | 3617.71 | 2233.67 | 1384.04 | 0.00 | 0.00 |
November | 1754.06 | 2987.32 | 2138.91 | 1225.78 | 913.13 | 0.00 | 0.00 |
December | 1906.05 | 3661.57 | 2237.91 | 1448.24 | 789.67 | 0.00 | 0.00 |
Annual Sum or Average | 3215.50 | 2389.01 | 3156.29 | 1543.80 | 1612.49 | 0.00 | 0.00 |
Minimum of Months | 1567.77 | 1280.67 | 2105.58 | 826.02 | 789.67 | 0.00 | 0.00 |
Maximum of Months | 4630.37 | 3661.57 | 3993.80 | 2233.67 | 2360.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 162.36 | 2566.04 | 538.46 | 158.78 | 379.68 | 0.00 | 0.00 |
February | 541.11 | 2273.09 | 965.42 | 362.83 | 602.59 | 0.00 | 0.00 |
March | 935.15 | 1879.74 | 1352.80 | 456.61 | 896.19 | 0.00 | 0.00 |
April | 1819.56 | 1541.27 | 2058.14 | 786.90 | 1271.23 | 0.00 | 0.00 |
May | 2648.73 | 1272.80 | 2648.34 | 1075.88 | 1572.46 | 0.00 | 0.00 |
June | 2636.14 | 1001.12 | 2546.98 | 988.91 | 1558.07 | 0.00 | 0.00 |
July | 3661.83 | 930.25 | 3146.44 | 1653.93 | 1492.51 | 0.00 | 0.00 |
August | 3098.80 | 894.71 | 2602.86 | 1329.10 | 1273.77 | 0.00 | 0.00 |
September | 2276.90 | 1215.11 | 2119.63 | 1017.05 | 1102.59 | 0.00 | 0.00 |
October | 965.28 | 1648.09 | 1206.71 | 491.68 | 715.04 | 0.00 | 0.00 |
November | 251.53 | 2091.29 | 600.94 | 169.49 | 431.45 | 0.00 | 0.00 |
December | 212.09 | 2608.50 | 505.20 | 173.12 | 332.08 | 0.00 | 0.00 |
Annual Sum or Average | 1607.91 | 1657.30 | 1695.42 | 724.77 | 970.65 | 0.00 | 0.00 |
Minimum of Months | 162.36 | 894.71 | 505.20 | 158.78 | 332.08 | 0.00 | 0.00 |
Maximum of Months | 3661.83 | 2608.50 | 3146.44 | 1653.93 | 1572.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.80 | 3645.67 | 476.56 | 0.00 | 476.56 | 0.00 | 0.00 |
February | 95.21 | 3218.44 | 741.54 | 0.00 | 741.54 | 0.00 | 0.00 |
March | 308.13 | 2549.28 | 1092.54 | 0.00 | 1092.54 | 0.00 | 0.00 |
April | 813.41 | 2010.06 | 1546.05 | 5.48 | 1540.57 | 0.00 | 0.00 |
May | 1371.27 | 1605.33 | 1989.38 | 59.10 | 1930.28 | 0.00 | 0.00 |
June | 1610.62 | 1261.35 | 2091.79 | 138.13 | 1953.65 | 0.00 | 0.00 |
July | 1813.85 | 1130.82 | 1988.13 | 155.88 | 1832.25 | 0.00 | 0.00 |
August | 1527.83 | 1096.26 | 1609.40 | 43.51 | 1565.90 | 0.00 | 0.00 |
September | 841.63 | 1565.40 | 1250.13 | 0.37 | 1249.76 | 0.00 | 0.00 |
October | 307.92 | 2143.54 | 856.55 | 0.00 | 856.55 | 0.00 | 0.00 |
November | 47.04 | 2815.57 | 539.54 | 0.00 | 539.54 | 0.00 | 0.00 |
December | 5.96 | 3571.68 | 404.95 | 0.00 | 404.95 | 0.00 | 0.00 |
Annual Sum or Average | 733.26 | 2212.90 | 1217.89 | 33.79 | 1184.10 | 0.00 | 0.00 |
Minimum of Months | 5.96 | 1096.26 | 404.95 | 0.00 | 404.95 | 0.00 | 0.00 |
Maximum of Months | 1813.85 | 3645.67 | 2091.79 | 155.88 | 1953.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 130.81 | 2308.36 | 510.51 | 129.43 | 381.08 | 0.00 | 0.00 |
February | 503.87 | 2005.35 | 936.73 | 332.47 | 604.27 | 0.00 | 0.00 |
March | 987.12 | 1613.40 | 1398.61 | 506.31 | 892.30 | 0.00 | 0.00 |
April | 1956.07 | 1273.90 | 2168.08 | 900.87 | 1267.21 | 0.00 | 0.00 |
May | 2214.87 | 1066.70 | 2307.03 | 802.10 | 1504.93 | 0.00 | 0.00 |
June | 2880.43 | 855.71 | 2762.93 | 1202.17 | 1560.76 | 0.00 | 0.00 |
July | 2854.34 | 747.00 | 2572.93 | 1154.88 | 1418.05 | 0.00 | 0.00 |
August | 2932.62 | 719.81 | 2528.83 | 1265.06 | 1263.76 | 0.00 | 0.00 |
September | 1891.49 | 1002.62 | 1869.70 | 862.32 | 1007.38 | 0.00 | 0.00 |
October | 987.27 | 1375.33 | 1218.67 | 517.82 | 700.85 | 0.00 | 0.00 |
November | 257.15 | 1809.54 | 597.32 | 168.63 | 428.69 | 0.00 | 0.00 |
December | 183.16 | 2285.11 | 489.94 | 157.73 | 332.21 | 0.00 | 0.00 |
Annual Sum or Average | 1486.74 | 1419.15 | 1616.41 | 668.11 | 948.30 | 0.00 | 0.00 |
Minimum of Months | 130.81 | 719.81 | 489.94 | 129.43 | 332.21 | 0.00 | 0.00 |
Maximum of Months | 2932.62 | 2308.36 | 2762.93 | 1265.06 | 1560.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1617.81 | 3263.12 | 2105.58 | 1250.30 | 855.28 | 0.00 | 0.00 |
February | 2917.40 | 2923.41 | 3238.06 | 2004.41 | 1233.66 | 0.00 | 0.00 |
March | 3310.73 | 2535.96 | 3483.22 | 1857.56 | 1625.66 | 0.00 | 0.00 |
April | 3733.05 | 2135.88 | 3677.62 | 1596.80 | 2080.82 | 0.00 | 0.00 |
May | 3449.18 | 1753.73 | 3362.71 | 1001.79 | 2360.93 | 0.00 | 0.00 |
June | 3227.38 | 1402.77 | 3076.55 | 826.02 | 2250.54 | 0.00 | 0.00 |
July | 3995.20 | 1260.94 | 3355.12 | 1228.82 | 2126.29 | 0.00 | 0.00 |
August | 4511.93 | 1208.86 | 3604.65 | 1680.91 | 1923.74 | 0.00 | 0.00 |
September | 4657.50 | 1637.47 | 3993.80 | 2205.51 | 1788.29 | 0.00 | 0.00 |
October | 3770.02 | 2177.07 | 3617.71 | 2233.67 | 1384.04 | 0.00 | 0.00 |
November | 1815.65 | 2661.20 | 2138.91 | 1225.78 | 913.13 | 0.00 | 0.00 |
December | 1962.16 | 3308.98 | 2237.91 | 1448.24 | 789.67 | 0.00 | 0.00 |
Annual Sum or Average | 3248.83 | 2185.60 | 3156.29 | 1543.80 | 1612.49 | 0.00 | 0.00 |
Minimum of Months | 1617.81 | 1208.86 | 2105.58 | 826.02 | 789.67 | 0.00 | 0.00 |
Maximum of Months | 4657.50 | 3308.98 | 3993.80 | 2233.67 | 2360.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 169.79 | 2400.52 | 538.46 | 158.78 | 379.68 | 0.00 | 0.00 |
February | 557.93 | 2109.35 | 965.42 | 362.83 | 602.59 | 0.00 | 0.00 |
March | 947.66 | 1729.54 | 1352.80 | 456.61 | 896.19 | 0.00 | 0.00 |
April | 1828.85 | 1435.78 | 2058.14 | 786.90 | 1271.23 | 0.00 | 0.00 |
May | 2648.55 | 1191.85 | 2648.34 | 1075.88 | 1572.46 | 0.00 | 0.00 |
June | 2623.53 | 950.42 | 2546.98 | 988.91 | 1558.07 | 0.00 | 0.00 |
July | 3643.76 | 889.56 | 3146.44 | 1653.93 | 1492.51 | 0.00 | 0.00 |
August | 3091.59 | 850.20 | 2602.86 | 1329.10 | 1273.77 | 0.00 | 0.00 |
September | 2284.67 | 1125.05 | 2119.63 | 1017.05 | 1102.59 | 0.00 | 0.00 |
October | 984.19 | 1503.68 | 1206.71 | 491.68 | 715.04 | 0.00 | 0.00 |
November | 262.98 | 1899.40 | 600.94 | 169.49 | 431.45 | 0.00 | 0.00 |
December | 221.25 | 2395.90 | 505.20 | 173.12 | 332.08 | 0.00 | 0.00 |
Annual Sum or Average | 1612.42 | 1537.48 | 1695.42 | 724.77 | 970.65 | 0.00 | 0.00 |
Minimum of Months | 169.79 | 850.20 | 505.20 | 158.78 | 332.08 | 0.00 | 0.00 |
Maximum of Months | 3643.76 | 2400.52 | 3146.44 | 1653.93 | 1572.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 285091.77 | 0.118559E+11 | 0.127642E+10 | 0.00 | 0.127642E+10 | 0.00 | 0.00 |
February | 0.112810E+09 | 0.950500E+10 | 0.179393E+10 | 0.00 | 0.179393E+10 | 0.00 | 0.00 |
March | 0.533908E+09 | 0.852703E+10 | 0.292627E+10 | 0.00 | 0.292627E+10 | 0.00 | 0.00 |
April | 0.171115E+10 | 0.643143E+10 | 0.400738E+10 | 14215412.64 | 0.399317E+10 | 0.00 | 0.00 |
May | 0.335188E+10 | 0.509480E+10 | 0.532838E+10 | 0.158298E+09 | 0.517008E+10 | 0.00 | 0.00 |
June | 0.391699E+10 | 0.379061E+10 | 0.542193E+10 | 0.358041E+09 | 0.506389E+10 | 0.00 | 0.00 |
July | 0.460816E+10 | 0.353859E+10 | 0.532502E+10 | 0.417507E+09 | 0.490751E+10 | 0.00 | 0.00 |
August | 0.382044E+10 | 0.353741E+10 | 0.431064E+10 | 0.116530E+09 | 0.419411E+10 | 0.00 | 0.00 |
September | 0.188074E+10 | 0.502715E+10 | 0.324034E+10 | 955527.58 | 0.323939E+10 | 0.00 | 0.00 |
October | 0.496880E+09 | 0.743085E+10 | 0.229418E+10 | 0.00 | 0.229418E+10 | 0.00 | 0.00 |
November | 45266171.62 | 0.949954E+10 | 0.139849E+10 | 0.00 | 0.139849E+10 | 0.00 | 0.00 |
December | 38451.07 | 0.120375E+11 | 0.108463E+10 | 0.00 | 0.108463E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.204786E+11 | 0.862758E+11 | 0.384076E+11 | 0.106555E+10 | 0.373421E+11 | 0.00 | 0.00 |
Minimum of Months | 38451.07 | 0.353741E+10 | 0.108463E+10 | 0.00 | 0.108463E+10 | 0.00 | 0.00 |
Maximum of Months | 0.460816E+10 | 0.120375E+11 | 0.542193E+10 | 0.417507E+09 | 0.517008E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.292067E+09 | 0.732929E+10 | 0.136735E+10 | 0.346668E+09 | 0.102068E+10 | 0.00 | 0.00 |
February | 0.107301E+10 | 0.570705E+10 | 0.226615E+10 | 0.804304E+09 | 0.146185E+10 | 0.00 | 0.00 |
March | 0.249551E+10 | 0.510686E+10 | 0.374604E+10 | 0.135610E+10 | 0.238994E+10 | 0.00 | 0.00 |
April | 0.496296E+10 | 0.381284E+10 | 0.561968E+10 | 0.233506E+10 | 0.328462E+10 | 0.00 | 0.00 |
May | 0.588778E+10 | 0.321642E+10 | 0.617917E+10 | 0.214836E+10 | 0.403081E+10 | 0.00 | 0.00 |
June | 0.752799E+10 | 0.243679E+10 | 0.716153E+10 | 0.311603E+10 | 0.404550E+10 | 0.00 | 0.00 |
July | 0.769348E+10 | 0.218923E+10 | 0.689135E+10 | 0.309324E+10 | 0.379812E+10 | 0.00 | 0.00 |
August | 0.788745E+10 | 0.210691E+10 | 0.677324E+10 | 0.338836E+10 | 0.338488E+10 | 0.00 | 0.00 |
September | 0.483803E+10 | 0.301360E+10 | 0.484627E+10 | 0.223514E+10 | 0.261113E+10 | 0.00 | 0.00 |
October | 0.247823E+10 | 0.446574E+10 | 0.326409E+10 | 0.138693E+10 | 0.187716E+10 | 0.00 | 0.00 |
November | 0.571283E+09 | 0.576817E+10 | 0.154827E+10 | 0.437091E+09 | 0.111118E+10 | 0.00 | 0.00 |
December | 0.416949E+09 | 0.739106E+10 | 0.131226E+10 | 0.422454E+09 | 0.889803E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.461248E+11 | 0.525440E+11 | 0.509754E+11 | 0.210697E+11 | 0.299057E+11 | 0.00 | 0.00 |
Minimum of Months | 0.292067E+09 | 0.210691E+10 | 0.131226E+10 | 0.346668E+09 | 0.889803E+09 | 0.00 | 0.00 |
Maximum of Months | 0.788745E+10 | 0.739106E+10 | 0.716153E+10 | 0.338836E+10 | 0.404550E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.420216E+10 | 0.993882E+10 | 0.563961E+10 | 0.334883E+10 | 0.229079E+10 | 0.00 | 0.00 |
February | 0.692809E+10 | 0.796713E+10 | 0.783355E+10 | 0.484907E+10 | 0.298448E+10 | 0.00 | 0.00 |
March | 0.883103E+10 | 0.770999E+10 | 0.932949E+10 | 0.497532E+10 | 0.435418E+10 | 0.00 | 0.00 |
April | 0.965795E+10 | 0.621469E+10 | 0.953243E+10 | 0.413893E+10 | 0.539350E+10 | 0.00 | 0.00 |
May | 0.928347E+10 | 0.518707E+10 | 0.900672E+10 | 0.268319E+10 | 0.632353E+10 | 0.00 | 0.00 |
June | 0.842570E+10 | 0.400138E+10 | 0.797446E+10 | 0.214104E+10 | 0.583341E+10 | 0.00 | 0.00 |
July | 0.107804E+11 | 0.372505E+10 | 0.898637E+10 | 0.329129E+10 | 0.569509E+10 | 0.00 | 0.00 |
August | 0.121225E+11 | 0.359878E+10 | 0.965473E+10 | 0.450216E+10 | 0.515257E+10 | 0.00 | 0.00 |
September | 0.120720E+11 | 0.475371E+10 | 0.103520E+11 | 0.571670E+10 | 0.463527E+10 | 0.00 | 0.00 |
October | 0.100476E+11 | 0.669274E+10 | 0.968971E+10 | 0.598268E+10 | 0.370703E+10 | 0.00 | 0.00 |
November | 0.454471E+10 | 0.805717E+10 | 0.554407E+10 | 0.317722E+10 | 0.236685E+10 | 0.00 | 0.00 |
December | 0.509471E+10 | 0.102579E+11 | 0.599405E+10 | 0.387898E+10 | 0.211506E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.101990E+12 | 0.781044E+11 | 0.995372E+11 | 0.486854E+11 | 0.508517E+11 | 0.00 | 0.00 |
Minimum of Months | 0.420216E+10 | 0.359878E+10 | 0.554407E+10 | 0.214104E+10 | 0.211506E+10 | 0.00 | 0.00 |
Maximum of Months | 0.121225E+11 | 0.102579E+11 | 0.103520E+11 | 0.598268E+10 | 0.632353E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.407459E+09 | 0.779057E+10 | 0.144222E+10 | 0.425284E+09 | 0.101694E+10 | 0.00 | 0.00 |
February | 0.122602E+10 | 0.618067E+10 | 0.233555E+10 | 0.877765E+09 | 0.145778E+10 | 0.00 | 0.00 |
March | 0.237224E+10 | 0.577868E+10 | 0.362335E+10 | 0.122298E+10 | 0.240037E+10 | 0.00 | 0.00 |
April | 0.450327E+10 | 0.464168E+10 | 0.533471E+10 | 0.203966E+10 | 0.329504E+10 | 0.00 | 0.00 |
May | 0.701848E+10 | 0.370832E+10 | 0.709335E+10 | 0.288164E+10 | 0.421170E+10 | 0.00 | 0.00 |
June | 0.670583E+10 | 0.290930E+10 | 0.660179E+10 | 0.256326E+10 | 0.403854E+10 | 0.00 | 0.00 |
July | 0.965973E+10 | 0.286550E+10 | 0.842747E+10 | 0.442991E+10 | 0.399756E+10 | 0.00 | 0.00 |
August | 0.807110E+10 | 0.288268E+10 | 0.697154E+10 | 0.355987E+10 | 0.341167E+10 | 0.00 | 0.00 |
September | 0.580060E+10 | 0.350301E+10 | 0.549412E+10 | 0.263620E+10 | 0.285792E+10 | 0.00 | 0.00 |
October | 0.246710E+10 | 0.504588E+10 | 0.323208E+10 | 0.131692E+10 | 0.191516E+10 | 0.00 | 0.00 |
November | 0.582773E+09 | 0.636439E+10 | 0.155763E+10 | 0.439318E+09 | 0.111832E+10 | 0.00 | 0.00 |
December | 0.507514E+09 | 0.821941E+10 | 0.135314E+10 | 0.463687E+09 | 0.889455E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.493221E+11 | 0.598901E+11 | 0.534669E+11 | 0.228565E+11 | 0.306105E+11 | 0.00 | 0.00 |
Minimum of Months | 0.407459E+09 | 0.286550E+10 | 0.135314E+10 | 0.425284E+09 | 0.889455E+09 | 0.00 | 0.00 |
Maximum of Months | 0.965973E+10 | 0.821941E+10 | 0.842747E+10 | 0.442991E+10 | 0.421170E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 4036850.79 | 0.105185E+11 | 0.127641E+10 | 0.00 | 0.127641E+10 | 0.00 | 0.00 |
February | 0.176827E+09 | 0.851575E+10 | 0.179393E+10 | 0.00 | 0.179393E+10 | 0.00 | 0.00 |
March | 0.696640E+09 | 0.761705E+10 | 0.292626E+10 | 0.00 | 0.292626E+10 | 0.00 | 0.00 |
April | 0.195075E+10 | 0.575621E+10 | 0.400737E+10 | 14215362.16 | 0.399315E+10 | 0.00 | 0.00 |
May | 0.351131E+10 | 0.472255E+10 | 0.532836E+10 | 0.158298E+09 | 0.517006E+10 | 0.00 | 0.00 |
June | 0.406137E+10 | 0.352155E+10 | 0.542191E+10 | 0.358040E+09 | 0.506387E+10 | 0.00 | 0.00 |
July | 0.478570E+10 | 0.323738E+10 | 0.532500E+10 | 0.417505E+09 | 0.490750E+10 | 0.00 | 0.00 |
August | 0.400110E+10 | 0.318426E+10 | 0.431063E+10 | 0.116529E+09 | 0.419410E+10 | 0.00 | 0.00 |
September | 0.202759E+10 | 0.455856E+10 | 0.324033E+10 | 955524.19 | 0.323937E+10 | 0.00 | 0.00 |
October | 0.658379E+09 | 0.655274E+10 | 0.229417E+10 | 0.00 | 0.229417E+10 | 0.00 | 0.00 |
November | 81661005.06 | 0.826821E+10 | 0.139849E+10 | 0.00 | 0.139849E+10 | 0.00 | 0.00 |
December | 2398717.01 | 0.106015E+11 | 0.108462E+10 | 0.00 | 0.108462E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.219578E+11 | 0.770543E+11 | 0.384075E+11 | 0.106554E+10 | 0.373419E+11 | 0.00 | 0.00 |
Minimum of Months | 2398717.01 | 0.318426E+10 | 0.108462E+10 | 0.00 | 0.108462E+10 | 0.00 | 0.00 |
Maximum of Months | 0.478570E+10 | 0.106015E+11 | 0.542191E+10 | 0.417505E+09 | 0.517006E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.313504E+09 | 0.667131E+10 | 0.136734E+10 | 0.346667E+09 | 0.102068E+10 | 0.00 | 0.00 |
February | 0.111957E+10 | 0.532832E+10 | 0.226614E+10 | 0.804301E+09 | 0.146184E+10 | 0.00 | 0.00 |
March | 0.248672E+10 | 0.481097E+10 | 0.374602E+10 | 0.135609E+10 | 0.238993E+10 | 0.00 | 0.00 |
April | 0.493647E+10 | 0.360309E+10 | 0.561966E+10 | 0.233505E+10 | 0.328461E+10 | 0.00 | 0.00 |
May | 0.583605E+10 | 0.306954E+10 | 0.617914E+10 | 0.214835E+10 | 0.403080E+10 | 0.00 | 0.00 |
June | 0.744006E+10 | 0.233187E+10 | 0.716151E+10 | 0.311602E+10 | 0.404548E+10 | 0.00 | 0.00 |
July | 0.763481E+10 | 0.208374E+10 | 0.689132E+10 | 0.309322E+10 | 0.379810E+10 | 0.00 | 0.00 |
August | 0.781865E+10 | 0.202859E+10 | 0.677321E+10 | 0.338835E+10 | 0.338486E+10 | 0.00 | 0.00 |
September | 0.480727E+10 | 0.285091E+10 | 0.484625E+10 | 0.223513E+10 | 0.261112E+10 | 0.00 | 0.00 |
October | 0.248265E+10 | 0.416020E+10 | 0.326407E+10 | 0.138692E+10 | 0.187715E+10 | 0.00 | 0.00 |
November | 0.594455E+09 | 0.531339E+10 | 0.154826E+10 | 0.437089E+09 | 0.111117E+10 | 0.00 | 0.00 |
December | 0.438604E+09 | 0.678583E+10 | 0.131225E+10 | 0.422453E+09 | 0.889799E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.459088E+11 | 0.490378E+11 | 0.509752E+11 | 0.210697E+11 | 0.299055E+11 | 0.00 | 0.00 |
Minimum of Months | 0.313504E+09 | 0.202859E+10 | 0.131225E+10 | 0.346667E+09 | 0.889799E+09 | 0.00 | 0.00 |
Maximum of Months | 0.781865E+10 | 0.678583E+10 | 0.716151E+10 | 0.338835E+10 | 0.404548E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.419913E+10 | 0.950077E+10 | 0.563959E+10 | 0.334882E+10 | 0.229078E+10 | 0.00 | 0.00 |
February | 0.688612E+10 | 0.775266E+10 | 0.783352E+10 | 0.484906E+10 | 0.298447E+10 | 0.00 | 0.00 |
March | 0.874580E+10 | 0.749129E+10 | 0.932946E+10 | 0.497530E+10 | 0.435416E+10 | 0.00 | 0.00 |
April | 0.958127E+10 | 0.601332E+10 | 0.953239E+10 | 0.413891E+10 | 0.539348E+10 | 0.00 | 0.00 |
May | 0.918594E+10 | 0.505980E+10 | 0.900669E+10 | 0.268318E+10 | 0.632350E+10 | 0.00 | 0.00 |
June | 0.837960E+10 | 0.384683E+10 | 0.797443E+10 | 0.214103E+10 | 0.583339E+10 | 0.00 | 0.00 |
July | 0.107400E+11 | 0.354159E+10 | 0.898634E+10 | 0.329128E+10 | 0.569506E+10 | 0.00 | 0.00 |
August | 0.120901E+11 | 0.343015E+10 | 0.965469E+10 | 0.450214E+10 | 0.515255E+10 | 0.00 | 0.00 |
September | 0.120019E+11 | 0.463878E+10 | 0.103519E+11 | 0.571668E+10 | 0.463525E+10 | 0.00 | 0.00 |
October | 0.994230E+10 | 0.651450E+10 | 0.968967E+10 | 0.598266E+10 | 0.370701E+10 | 0.00 | 0.00 |
November | 0.454652E+10 | 0.774313E+10 | 0.554405E+10 | 0.317721E+10 | 0.236684E+10 | 0.00 | 0.00 |
December | 0.510518E+10 | 0.980715E+10 | 0.599402E+10 | 0.387897E+10 | 0.211505E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.101404E+12 | 0.753400E+11 | 0.995368E+11 | 0.486852E+11 | 0.508516E+11 | 0.00 | 0.00 |
Minimum of Months | 0.419913E+10 | 0.343015E+10 | 0.554405E+10 | 0.214103E+10 | 0.211505E+10 | 0.00 | 0.00 |
Maximum of Months | 0.120901E+11 | 0.980715E+10 | 0.103519E+11 | 0.598266E+10 | 0.632350E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.434857E+09 | 0.687288E+10 | 0.144221E+10 | 0.425283E+09 | 0.101693E+10 | 0.00 | 0.00 |
February | 0.130904E+10 | 0.549907E+10 | 0.233554E+10 | 0.877761E+09 | 0.145778E+10 | 0.00 | 0.00 |
March | 0.250471E+10 | 0.503470E+10 | 0.362333E+10 | 0.122297E+10 | 0.240036E+10 | 0.00 | 0.00 |
April | 0.471631E+10 | 0.399496E+10 | 0.533469E+10 | 0.203966E+10 | 0.329503E+10 | 0.00 | 0.00 |
May | 0.709436E+10 | 0.340906E+10 | 0.709332E+10 | 0.288163E+10 | 0.421169E+10 | 0.00 | 0.00 |
June | 0.683286E+10 | 0.259490E+10 | 0.660177E+10 | 0.256325E+10 | 0.403852E+10 | 0.00 | 0.00 |
July | 0.980784E+10 | 0.249157E+10 | 0.842744E+10 | 0.442989E+10 | 0.399755E+10 | 0.00 | 0.00 |
August | 0.829983E+10 | 0.239638E+10 | 0.697151E+10 | 0.355985E+10 | 0.341165E+10 | 0.00 | 0.00 |
September | 0.590172E+10 | 0.314955E+10 | 0.549409E+10 | 0.263619E+10 | 0.285791E+10 | 0.00 | 0.00 |
October | 0.258541E+10 | 0.441425E+10 | 0.323206E+10 | 0.131691E+10 | 0.191515E+10 | 0.00 | 0.00 |
November | 0.651962E+09 | 0.542063E+10 | 0.155763E+10 | 0.439316E+09 | 0.111831E+10 | 0.00 | 0.00 |
December | 0.568065E+09 | 0.698662E+10 | 0.135314E+10 | 0.463686E+09 | 0.889451E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.507070E+11 | 0.522646E+11 | 0.534667E+11 | 0.228564E+11 | 0.306103E+11 | 0.00 | 0.00 |
Minimum of Months | 0.434857E+09 | 0.239638E+10 | 0.135314E+10 | 0.425283E+09 | 0.889451E+09 | 0.00 | 0.00 |
Maximum of Months | 0.980784E+10 | 0.698662E+10 | 0.842744E+10 | 0.442989E+10 | 0.421169E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 18214039.73 | 0.976457E+10 | 0.127641E+10 | 0.00 | 0.127641E+10 | 0.00 | 0.00 |
February | 0.230320E+09 | 0.778606E+10 | 0.179393E+10 | 0.00 | 0.179393E+10 | 0.00 | 0.00 |
March | 0.825301E+09 | 0.682799E+10 | 0.292626E+10 | 0.00 | 0.292626E+10 | 0.00 | 0.00 |
April | 0.210836E+10 | 0.521008E+10 | 0.400737E+10 | 14215362.16 | 0.399315E+10 | 0.00 | 0.00 |
May | 0.367281E+10 | 0.429972E+10 | 0.532836E+10 | 0.158298E+09 | 0.517006E+10 | 0.00 | 0.00 |
June | 0.417472E+10 | 0.326941E+10 | 0.542191E+10 | 0.358040E+09 | 0.506387E+10 | 0.00 | 0.00 |
July | 0.485821E+10 | 0.302880E+10 | 0.532500E+10 | 0.417505E+09 | 0.490750E+10 | 0.00 | 0.00 |
August | 0.409214E+10 | 0.293624E+10 | 0.431063E+10 | 0.116529E+09 | 0.419410E+10 | 0.00 | 0.00 |
September | 0.218149E+10 | 0.405752E+10 | 0.324033E+10 | 955524.19 | 0.323937E+10 | 0.00 | 0.00 |
October | 0.824731E+09 | 0.574125E+10 | 0.229417E+10 | 0.00 | 0.229417E+10 | 0.00 | 0.00 |
November | 0.121926E+09 | 0.729796E+10 | 0.139849E+10 | 0.00 | 0.139849E+10 | 0.00 | 0.00 |
December | 15960248.92 | 0.956638E+10 | 0.108462E+10 | 0.00 | 0.108462E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.231242E+11 | 0.697860E+11 | 0.384075E+11 | 0.106554E+10 | 0.373419E+11 | 0.00 | 0.00 |
Minimum of Months | 15960248.92 | 0.293624E+10 | 0.108462E+10 | 0.00 | 0.108462E+10 | 0.00 | 0.00 |
Maximum of Months | 0.485821E+10 | 0.976457E+10 | 0.542191E+10 | 0.417505E+09 | 0.517006E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.350365E+09 | 0.618272E+10 | 0.136734E+10 | 0.346667E+09 | 0.102068E+10 | 0.00 | 0.00 |
February | 0.121895E+10 | 0.485133E+10 | 0.226614E+10 | 0.804301E+09 | 0.146184E+10 | 0.00 | 0.00 |
March | 0.264390E+10 | 0.432132E+10 | 0.374602E+10 | 0.135609E+10 | 0.238993E+10 | 0.00 | 0.00 |
April | 0.507013E+10 | 0.330195E+10 | 0.561966E+10 | 0.233505E+10 | 0.328461E+10 | 0.00 | 0.00 |
May | 0.593230E+10 | 0.285705E+10 | 0.617914E+10 | 0.214835E+10 | 0.403080E+10 | 0.00 | 0.00 |
June | 0.746609E+10 | 0.221800E+10 | 0.716151E+10 | 0.311602E+10 | 0.404548E+10 | 0.00 | 0.00 |
July | 0.764508E+10 | 0.200077E+10 | 0.689132E+10 | 0.309322E+10 | 0.379810E+10 | 0.00 | 0.00 |
August | 0.785472E+10 | 0.192793E+10 | 0.677321E+10 | 0.338835E+10 | 0.338486E+10 | 0.00 | 0.00 |
September | 0.490275E+10 | 0.259878E+10 | 0.484625E+10 | 0.223513E+10 | 0.261112E+10 | 0.00 | 0.00 |
October | 0.264430E+10 | 0.368369E+10 | 0.326407E+10 | 0.138692E+10 | 0.187715E+10 | 0.00 | 0.00 |
November | 0.666535E+09 | 0.469034E+10 | 0.154826E+10 | 0.437089E+09 | 0.111117E+10 | 0.00 | 0.00 |
December | 0.490570E+09 | 0.612045E+10 | 0.131225E+10 | 0.422453E+09 | 0.889799E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.468857E+11 | 0.447543E+11 | 0.509752E+11 | 0.210697E+11 | 0.299055E+11 | 0.00 | 0.00 |
Minimum of Months | 0.350365E+09 | 0.192793E+10 | 0.131225E+10 | 0.346667E+09 | 0.889799E+09 | 0.00 | 0.00 |
Maximum of Months | 0.785472E+10 | 0.618272E+10 | 0.716151E+10 | 0.338835E+10 | 0.404548E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.433314E+10 | 0.873993E+10 | 0.563959E+10 | 0.334882E+10 | 0.229078E+10 | 0.00 | 0.00 |
February | 0.705778E+10 | 0.707231E+10 | 0.783352E+10 | 0.484906E+10 | 0.298447E+10 | 0.00 | 0.00 |
March | 0.886746E+10 | 0.679231E+10 | 0.932946E+10 | 0.497530E+10 | 0.435416E+10 | 0.00 | 0.00 |
April | 0.967607E+10 | 0.553619E+10 | 0.953239E+10 | 0.413891E+10 | 0.539348E+10 | 0.00 | 0.00 |
May | 0.923827E+10 | 0.469719E+10 | 0.900669E+10 | 0.268318E+10 | 0.632350E+10 | 0.00 | 0.00 |
June | 0.836538E+10 | 0.363599E+10 | 0.797443E+10 | 0.214103E+10 | 0.583339E+10 | 0.00 | 0.00 |
July | 0.107008E+11 | 0.337730E+10 | 0.898634E+10 | 0.329128E+10 | 0.569506E+10 | 0.00 | 0.00 |
August | 0.120848E+11 | 0.323781E+10 | 0.965469E+10 | 0.450214E+10 | 0.515255E+10 | 0.00 | 0.00 |
September | 0.120722E+11 | 0.424433E+10 | 0.103519E+11 | 0.571668E+10 | 0.463525E+10 | 0.00 | 0.00 |
October | 0.100976E+11 | 0.583106E+10 | 0.968967E+10 | 0.598266E+10 | 0.370701E+10 | 0.00 | 0.00 |
November | 0.470617E+10 | 0.689782E+10 | 0.554405E+10 | 0.317721E+10 | 0.236684E+10 | 0.00 | 0.00 |
December | 0.525544E+10 | 0.886276E+10 | 0.599402E+10 | 0.387897E+10 | 0.211505E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.102455E+12 | 0.689250E+11 | 0.995368E+11 | 0.486852E+11 | 0.508516E+11 | 0.00 | 0.00 |
Minimum of Months | 0.433314E+10 | 0.323781E+10 | 0.554405E+10 | 0.214103E+10 | 0.211505E+10 | 0.00 | 0.00 |
Maximum of Months | 0.120848E+11 | 0.886276E+10 | 0.103519E+11 | 0.598266E+10 | 0.632350E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.454775E+09 | 0.642955E+10 | 0.144221E+10 | 0.425283E+09 | 0.101693E+10 | 0.00 | 0.00 |
February | 0.134974E+10 | 0.510295E+10 | 0.233554E+10 | 0.877761E+09 | 0.145778E+10 | 0.00 | 0.00 |
March | 0.253822E+10 | 0.463239E+10 | 0.362333E+10 | 0.122297E+10 | 0.240036E+10 | 0.00 | 0.00 |
April | 0.474039E+10 | 0.372154E+10 | 0.533469E+10 | 0.203966E+10 | 0.329503E+10 | 0.00 | 0.00 |
May | 0.709387E+10 | 0.319225E+10 | 0.709332E+10 | 0.288163E+10 | 0.421169E+10 | 0.00 | 0.00 |
June | 0.680018E+10 | 0.246349E+10 | 0.660177E+10 | 0.256325E+10 | 0.403852E+10 | 0.00 | 0.00 |
July | 0.975943E+10 | 0.238259E+10 | 0.842744E+10 | 0.442989E+10 | 0.399755E+10 | 0.00 | 0.00 |
August | 0.828051E+10 | 0.227719E+10 | 0.697151E+10 | 0.355985E+10 | 0.341165E+10 | 0.00 | 0.00 |
September | 0.592187E+10 | 0.291612E+10 | 0.549409E+10 | 0.263619E+10 | 0.285791E+10 | 0.00 | 0.00 |
October | 0.263604E+10 | 0.402745E+10 | 0.323206E+10 | 0.131691E+10 | 0.191515E+10 | 0.00 | 0.00 |
November | 0.681647E+09 | 0.492323E+10 | 0.155763E+10 | 0.439316E+09 | 0.111831E+10 | 0.00 | 0.00 |
December | 0.592598E+09 | 0.641717E+10 | 0.135314E+10 | 0.463686E+09 | 0.889451E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.508493E+11 | 0.484859E+11 | 0.534667E+11 | 0.228564E+11 | 0.306103E+11 | 0.00 | 0.00 |
Minimum of Months | 0.454775E+09 | 0.227719E+10 | 0.135314E+10 | 0.425283E+09 | 0.889451E+09 | 0.00 | 0.00 |
Maximum of Months | 0.975943E+10 | 0.642955E+10 | 0.842744E+10 | 0.442989E+10 | 0.421169E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.390644E+11 | -0.386122E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -452280219.3 | 60.05 | 0.00 | 0.00 |
February | 0.357334E+11 | -0.353262E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -407227804.9 | 60.05 | 0.00 | 0.00 |
March | 0.415463E+11 | -0.410963E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -449953652.3 | 60.05 | 0.00 | 0.00 |
April | 0.366919E+11 | -0.362576E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -434327936.2 | 60.05 | 0.00 | 0.00 |
May | 0.377549E+11 | -0.373060E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -448928162.1 | 60.05 | 0.00 | 0.00 |
June | 0.360515E+11 | -0.356186E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -432877419.0 | 60.05 | 0.00 | 0.00 |
July | 0.333894E+11 | -0.329455E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443848733.2 | 60.05 | 0.00 | 0.00 |
August | 0.362177E+11 | -0.357723E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -445428114.8 | 60.05 | 0.00 | 0.00 |
September | 0.333097E+11 | -0.328780E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -431678897.7 | 60.05 | 0.00 | 0.00 |
October | 0.354215E+11 | -0.349745E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -446952552.8 | 60.05 | 0.00 | 0.00 |
November | 0.360928E+11 | -0.356606E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -432222335.1 | 60.05 | 0.00 | 0.00 |
December | 0.372272E+11 | -0.367784E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -448777299.7 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.438501E+12 | -0.433226E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.527450E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.333097E+11 | -0.410963E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -452280219.3 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.415463E+11 | -0.328780E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -407227804.9 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.778945E+09 | 14911.15 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.343403E+09 | 10417.51 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17680575.80 | 4775.74 | 01-MAR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14980549.63 | 3088.87 | 13-NOV-07:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106930E+09 | 9336.69 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.778945E+09 | 14911.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.840443E+09 | 14298.46 | 07-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.429055E+09 | 14333.43 | 08-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 77704123.16 | 6514.10 | 25-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2491551.76 | 2142.50 | 19-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5619236.84 | 1475.71 | 31-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 68350648.59 | 3656.24 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.292607E+09 | 13924.19 | 26-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.840443E+09 | 14333.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.222880E+10 | 14474.92 | 07-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141574E+10 | 14514.52 | 08-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.747254E+09 | 14399.71 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.247110E+09 | 13582.42 | 18-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104376E+09 | 5051.25 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11335388.07 | 2189.05 | 15-JUN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 148384.80 | 140.97 | 18-AUG-05:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 61545056.05 | 4285.59 | 27-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.442169E+09 | 8561.45 | 27-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106253E+10 | 13879.91 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187849E+10 | 14501.07 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.819950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.222880E+10 | 14514.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.313792E+10 | 22589.78 | 07-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.189892E+10 | 22649.07 | 08-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.106184E+10 | 22471.58 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.505762E+09 | 21203.58 | 18-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.242707E+09 | 12231.26 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27039010.27 | 3874.53 | 15-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 93919823.17 | 6436.88 | 28-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.651809E+09 | 19659.02 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151009E+10 | 21900.48 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.250684E+10 | 22628.68 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.313792E+10 | 22649.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151084E+10 | 13104.25 | 07-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.754089E+09 | 12975.23 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161072E+09 | 4284.08 | 01-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9705761.36 | 1419.39 | 19-APR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31061909.28 | 2664.14 | 18-MAY-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7273521.71 | 1917.19 | 28-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115593E+09 | 4297.39 | 31-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.244737E+09 | 4510.06 | 24-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.347182E+09 | 12747.72 | 26-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.151084E+10 | 13104.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.290430E+11 | 195404.16 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169160E+11 | 308237.87 | 08-FEB-10:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131913E+10 | 309137.55 | 24-MAR-13:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.510643E+09 | 277492.90 | 18-APR-11:28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.383837E+09 | 276946.57 | 17-MAY-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.182671E+09 | 174514.42 | 13-JUN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9162280.09 | 119781.01 | 12-JUL-09:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 51801772.53 | 163010.20 | 01-AUG-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126962E+09 | 252740.92 | 27-SEP-09:46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.204995E+09 | 274387.97 | 11-OCT-09:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207470E+10 | 183714.36 | 02-NOV-09:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122151E+11 | 177784.42 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.630381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9162280.09 | 119781.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.290430E+11 | 309137.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.965439E+10 | 524707.78 | 17-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.801550E+09 | 519314.34 | 21-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.463756E+09 | 539068.36 | 26-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.965439E+10 | 539068.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.522358E+11 | 206404.79 | 07-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.321666E+11 | 210351.13 | 19-FEB-07:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172846E+11 | 198187.11 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.733335E+10 | 191929.96 | 19-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.175351E+10 | 182534.89 | 11-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152270E+09 | 35857.62 | 15-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 513936.46 | 1040.05 | 03-AUG-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.764996E+09 | 51238.91 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.918280E+10 | 180034.88 | 13-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.233135E+11 | 194535.56 | 13-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.420710E+11 | 202361.20 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186259E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.522358E+11 | 210351.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.472817E+11 | 191893.39 | 07-JAN-05:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.304694E+11 | 189950.91 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197979E+11 | 184111.70 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.857826E+10 | 173525.51 | 18-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.449999E+10 | 165852.36 | 11-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134215E+10 | 114368.16 | 14-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.377336E+09 | 29937.62 | 05-JUL-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.577677E+09 | 40993.12 | 03-AUG-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.364939E+10 | 75412.65 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136621E+11 | 166864.83 | 13-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.276245E+11 | 180214.05 | 13-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.405413E+11 | 188079.88 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198402E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.377336E+09 | 29937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.472817E+11 | 191893.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.610761E+11 | 275168.05 | 06-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.368685E+11 | 275029.50 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.247661E+11 | 266593.11 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133479E+11 | 251819.57 | 19-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.710915E+10 | 245092.04 | 11-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.274159E+10 | 125579.38 | 14-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.639766E+09 | 31747.93 | 18-JUL-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.103046E+10 | 50074.33 | 03-AUG-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.400642E+10 | 85870.57 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155746E+11 | 234633.32 | 24-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.352612E+11 | 259156.43 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.516517E+11 | 272330.35 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.254073E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.639766E+09 | 31747.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.610761E+11 | 275168.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.513682E+11 | 191257.57 | 06-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.337729E+11 | 191169.96 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227508E+11 | 185253.08 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110134E+11 | 174541.05 | 18-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.532697E+10 | 170203.97 | 11-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173875E+10 | 81897.99 | 27-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.224586E+09 | 19742.38 | 18-JUL-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.720041E+09 | 34152.96 | 04-AUG-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.373489E+10 | 44902.50 | 27-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156466E+11 | 162879.12 | 24-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.310595E+11 | 179426.80 | 13-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.443171E+11 | 187954.97 | 26-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221674E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.224586E+09 | 19742.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.513682E+11 | 191257.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.592672E+10 | 26991.93 | 07-JAN-08:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.391444E+10 | 24386.64 | 18-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.802095E+09 | 19355.54 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.206772E+09 | 12575.06 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7869106.60 | 2750.49 | 18-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33541637.27 | 3399.77 | 16-OCT-06:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108571E+10 | 17479.32 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.382720E+10 | 23773.80 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.592672E+10 | 26991.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.921952E+10 | 99187.59 | 07-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.545316E+10 | 98796.78 | 18-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.246407E+10 | 92170.49 | 25-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.679379E+09 | 90504.57 | 18-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24977520.40 | 10946.40 | 30-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 49942000.29 | 13554.00 | 18-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110258E+10 | 83819.05 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.420378E+10 | 93909.60 | 13-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.767542E+10 | 97648.06 | 26-DEC-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.308728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.921952E+10 | 99187.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110267E+11 | 27346.67 | 07-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.810671E+10 | 28057.33 | 19-FEB-07:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.544011E+10 | 26391.32 | 01-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.289234E+10 | 25395.46 | 19-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129448E+10 | 23604.02 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.388689E+09 | 21839.13 | 15-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114822E+09 | 6256.93 | 05-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.206501E+09 | 9510.26 | 05-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111167E+10 | 21811.73 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.378639E+10 | 23061.00 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.675014E+10 | 25813.70 | 13-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.999776E+10 | 26832.80 | 26-DEC-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.511164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.114822E+09 | 6256.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110267E+11 | 28057.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.829442E+10 | 21579.28 | 07-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.579243E+10 | 22647.10 | 19-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.390028E+10 | 20779.91 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.190099E+10 | 20023.80 | 19-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108866E+10 | 18592.63 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.375566E+09 | 17184.84 | 15-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.171530E+09 | 6468.51 | 05-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.190994E+09 | 8331.47 | 05-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100163E+10 | 17126.44 | 27-SEP-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.295795E+10 | 18159.44 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.542436E+10 | 20287.34 | 13-NOV-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.758913E+10 | 21126.89 | 26-DEC-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.386879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.171530E+09 | 6468.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.829442E+10 | 22647.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105549E+11 | 32954.70 | 07-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.725296E+10 | 34578.76 | 19-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.542111E+10 | 31735.32 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.324446E+10 | 30579.72 | 19-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.200921E+10 | 28397.52 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100389E+10 | 26249.99 | 15-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.510962E+09 | 6861.00 | 13-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.509037E+09 | 9737.39 | 05-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150374E+10 | 25127.10 | 27-SEP-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.386484E+10 | 27732.74 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.708697E+10 | 30983.99 | 13-NOV-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.963299E+10 | 32265.81 | 26-DEC-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.525951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.509037E+09 | 6861.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105549E+11 | 34578.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.780810E+10 | 23114.36 | 07-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.555576E+10 | 24262.52 | 19-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.420871E+10 | 22253.30 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.236723E+10 | 21437.99 | 19-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135107E+10 | 19898.10 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.609701E+09 | 18383.85 | 15-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.264725E+09 | 4487.87 | 18-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.317034E+09 | 4547.62 | 19-AUG-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111334E+10 | 12896.27 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.321975E+10 | 19296.46 | 30-OCT-04:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.525958E+10 | 21722.88 | 13-NOV-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.698866E+10 | 22627.62 | 26-DEC-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.390637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.264725E+09 | 4487.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.780810E+10 | 24262.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2878.24 | 2878.24 | 0.50 | 11-JAN-14:20 | 0.50 | 0.00 |
February | 0.00 | 0.00 | 0.907003E+09 | 0.907003E+09 | 59022.03 | 27-FEB-15:00 | 59022.03 | 0.00 |
March | 0.00 | 0.00 | 0.139777E+10 | 0.139777E+10 | 35722.09 | 18-MAR-16:00 | 35722.09 | 0.01 |
April | 0.00 | 0.00 | 0.118424E+11 | 0.118424E+11 | 138912.63 | 27-APR-14:40 | 138912.63 | 0.04 |
May | 0.00 | 0.00 | 0.203770E+11 | 0.203724E+11 | 118710.39 | 04-MAY-15:00 | 118710.39 | 0.13 |
June | 0.00 | 0.00 | 0.381580E+11 | 0.381528E+11 | 127872.94 | 28-JUN-15:30 | 127872.94 | 0.25 |
July | 0.00 | 0.00 | 0.688980E+11 | 0.679914E+11 | 158863.06 | 31-JUL-14:40 | 147381.64 | 0.44 |
August | 0.00 | 0.00 | 0.936130E+11 | 0.910588E+11 | 173405.15 | 29-AUG-14:30 | 159599.54 | 0.57 |
September | 0.00 | 0.00 | 0.317552E+11 | 0.312821E+11 | 135886.27 | 14-SEP-14:00 | 125907.09 | 0.30 |
October | 0.00 | 0.00 | 0.546546E+10 | 0.546546E+10 | 88056.91 | 04-OCT-15:00 | 88056.91 | 0.02 |
November | 0.00 | 0.00 | 0.874412E+09 | 0.874412E+09 | 45340.58 | 04-NOV-14:00 | 45340.58 | 0.02 |
December | 0.00 | 0.00 | 1232.84 | 1232.84 | 0.58 | 07-DEC-12:45 | 0.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.273288E+12 | 0.269345E+12 | 0.15 | |||
Minimum of Months | 0.00 | 0.00 | 1232.84 | 1232.84 | 0.50 | 0.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.936130E+11 | 0.910588E+11 | 173405.15 | 159599.54 | 0.57 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 193866.98 | 193866.98 | 5.32 | 31-JAN-06:03 | 5.32 | 0.00 |
February | 0.00 | 0.00 | 0.109231E+11 | 0.109231E+11 | 715360.02 | 27-FEB-15:02 | 715360.02 | 0.01 |
March | 0.00 | 0.00 | 0.343017E+11 | 0.343017E+11 | 668377.02 | 01-MAR-15:01 | 668377.02 | 0.01 |
April | 0.00 | 0.00 | 0.107256E+12 | 0.107256E+12 | 1233172.33 | 27-APR-14:50 | 1233172.33 | 0.05 |
May | 0.00 | 0.00 | 0.195048E+12 | 0.195013E+12 | 1125571.91 | 04-MAY-15:00 | 1125571.91 | 0.14 |
June | 0.00 | 0.00 | 0.345768E+12 | 0.345729E+12 | 1185527.94 | 28-JUN-15:40 | 1185527.94 | 0.25 |
July | 0.00 | 0.00 | 0.585647E+12 | 0.578571E+12 | 1401435.68 | 31-JUL-14:05 | 1281602.09 | 0.43 |
August | 0.00 | 0.00 | 0.766382E+12 | 0.746480E+12 | 1551499.42 | 29-AUG-14:30 | 1417524.75 | 0.53 |
September | 0.00 | 0.00 | 0.303243E+12 | 0.298720E+12 | 1291909.73 | 14-SEP-14:05 | 1218230.40 | 0.31 |
October | 0.00 | 0.00 | 0.592120E+11 | 0.592120E+11 | 946642.76 | 04-OCT-13:13 | 946642.76 | 0.02 |
November | 0.00 | 0.00 | 0.123937E+11 | 0.123937E+11 | 497670.83 | 02-NOV-14:01 | 497670.83 | 0.02 |
December | 0.00 | 0.00 | 5545840.15 | 5545840.15 | 35342.90 | 06-DEC-17:03 | 35342.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.242018E+13 | 0.238860E+13 | 0.15 | |||
Minimum of Months | 0.00 | 0.00 | 193866.98 | 193866.98 | 5.32 | 5.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.766382E+12 | 0.746480E+12 | 1551499.42 | 1417524.75 | 0.53 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4133138.14 | 4133138.14 | 1695.32 | 07-JAN-22:20 | 1695.32 | 0.00 |
February | 0.00 | 0.00 | 0.648557E+09 | 0.648557E+09 | 40576.83 | 27-FEB-15:00 | 40576.83 | 0.00 |
March | 0.00 | 0.00 | 0.110534E+10 | 0.110534E+10 | 36791.48 | 18-MAR-14:00 | 36791.48 | 0.01 |
April | 0.00 | 0.00 | 0.110401E+11 | 0.110401E+11 | 156835.28 | 27-APR-14:40 | 156835.28 | 0.04 |
May | 0.00 | 0.00 | 0.202657E+11 | 0.202617E+11 | 149472.21 | 04-MAY-15:00 | 149472.21 | 0.12 |
June | 0.00 | 0.00 | 0.378000E+11 | 0.377990E+11 | 156654.53 | 28-JUN-15:20 | 156654.53 | 0.24 |
July | 0.00 | 0.00 | 0.660235E+11 | 0.653333E+11 | 181212.51 | 31-JUL-14:40 | 169374.44 | 0.41 |
August | 0.00 | 0.00 | 0.857102E+11 | 0.837903E+11 | 191275.08 | 10-AUG-14:40 | 182336.15 | 0.51 |
September | 0.00 | 0.00 | 0.297430E+11 | 0.294009E+11 | 153254.37 | 14-SEP-14:00 | 142110.40 | 0.29 |
October | 0.00 | 0.00 | 0.428511E+10 | 0.428511E+10 | 81994.98 | 04-OCT-15:00 | 81994.98 | 0.01 |
November | 0.00 | 0.00 | 0.847179E+09 | 0.847179E+09 | 46770.39 | 04-NOV-14:00 | 46770.39 | 0.01 |
December | 0.00 | 0.00 | 701859.22 | 701859.22 | 1358.07 | 11-DEC-05:11 | 1358.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.257474E+12 | 0.254516E+12 | 0.14 | |||
Minimum of Months | 0.00 | 0.00 | 701859.22 | 701859.22 | 1358.07 | 1358.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.857102E+11 | 0.837903E+11 | 191275.08 | 182336.15 | 0.51 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.630730E+10 | 0.623053E+10 | 119171.61 | 05-JAN-05:05 | 119171.61 | 0.01 |
February | 0.00 | 0.00 | 0.665979E+10 | 0.624601E+10 | 124026.46 | 15-FEB-05:47 | 124026.46 | 0.03 |
March | 0.00 | 0.00 | 0.731741E+10 | 0.724497E+10 | 117423.86 | 01-MAR-05:44 | 117423.86 | 0.01 |
April | 0.00 | 0.00 | 0.125529E+11 | 0.123445E+11 | 106213.73 | 01-APR-05:00 | 106213.73 | 0.05 |
May | 0.00 | 0.00 | 0.211410E+11 | 0.201567E+11 | 74846.14 | 25-MAY-04:55 | 65147.07 | 0.17 |
June | 0.00 | 0.00 | 0.286139E+11 | 0.275897E+11 | 75278.46 | 12-JUN-04:11 | 40688.73 | 0.29 |
July | 0.00 | 0.00 | 0.416940E+11 | 0.374608E+11 | 101521.70 | 11-JUL-09:32 | 47826.88 | 0.38 |
August | 0.00 | 0.00 | 0.564131E+11 | 0.487751E+11 | 106104.14 | 14-AUG-02:39 | 106104.14 | 0.52 |
September | 0.00 | 0.00 | 0.303734E+11 | 0.252842E+11 | 110203.88 | 04-SEP-15:30 | 109805.02 | 0.37 |
October | 0.00 | 0.00 | 0.162320E+11 | 0.153641E+11 | 122029.13 | 09-OCT-11:09 | 122029.13 | 0.10 |
November | 0.00 | 0.00 | 0.788016E+10 | 0.750640E+10 | 67432.68 | 04-NOV-10:34 | 48861.92 | 0.03 |
December | 0.00 | 0.00 | 0.572481E+10 | 0.572481E+10 | 107444.39 | 30-DEC-05:58 | 107444.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.240910E+12 | 0.219928E+12 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 0.572481E+10 | 0.572481E+10 | 67432.68 | 40688.73 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.564131E+11 | 0.487751E+11 | 124026.46 | 124026.46 | 0.52 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3898644.71 | 3898644.71 | 37.95 | 18-JAN-05:02 | 37.95 | 0.11 |
February | 0.00 | 0.00 | 0.144747E+12 | 0.143477E+12 | 319051.86 | 27-FEB-15:00 | 319051.86 | 0.08 |
March | 0.00 | 0.00 | 0.237788E+12 | 0.237706E+12 | 300383.92 | 14-MAR-16:01 | 300383.92 | 0.05 |
April | 0.00 | 0.00 | 0.281601E+12 | 0.280927E+12 | 424017.51 | 01-APR-17:01 | 424017.51 | 0.11 |
May | 0.00 | 0.00 | 0.472313E+10 | 0.472313E+10 | 210884.78 | 31-MAY-23:55 | 210884.78 | 0.18 |
June | 0.00 | 0.00 | 0.160505E+12 | 0.154550E+12 | 322791.89 | 21-JUN-11:50 | 307631.40 | 0.38 |
July | 0.00 | 0.00 | 0.284671E+12 | 0.273930E+12 | 400586.28 | 11-JUL-09:46 | 235769.88 | 0.73 |
August | 0.00 | 0.00 | 0.409190E+12 | 0.400521E+12 | 496926.38 | 25-AUG-11:20 | 391128.59 | 0.94 |
September | 0.00 | 0.00 | 0.574634E+10 | 0.572910E+10 | 234906.15 | 30-SEP-23:55 | 210451.81 | 0.33 |
October | 0.00 | 0.00 | 0.141361E+12 | 0.137824E+12 | 348892.00 | 01-OCT-11:41 | 241851.26 | 0.20 |
November | 0.00 | 0.00 | 0.222483E+12 | 0.219632E+12 | 322955.42 | 04-NOV-11:47 | 252498.19 | 0.13 |
December | 0.00 | 0.00 | 0.254490E+12 | 0.254490E+12 | 251842.73 | 11-DEC-05:20 | 251842.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.214731E+13 | 0.211351E+13 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 3898644.71 | 3898644.71 | 37.95 | 37.95 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.409190E+12 | 0.400521E+12 | 496926.38 | 424017.51 | 0.94 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.568079E+10 | 0.568046E+10 | 3065.38 | 05-JAN-16:10 | 3065.38 | 0.00 |
February | 0.00 | 0.00 | 0.998741E+10 | 0.998133E+10 | 5293.51 | 27-FEB-16:13 | 5293.51 | 0.00 |
March | 0.00 | 0.00 | 0.167394E+11 | 0.167345E+11 | 8094.67 | 31-MAR-24:00 | 8094.67 | 0.00 |
April | 0.00 | 0.00 | 0.215568E+11 | 0.215467E+11 | 9634.38 | 26-APR-18:00 | 9634.38 | 0.00 |
May | 0.00 | 0.00 | 0.751112E+10 | 0.748755E+10 | 4746.21 | 31-MAY-23:51 | 4746.20 | 0.00 |
June | 0.00 | 0.00 | 0.123772E+11 | 0.123457E+11 | 6601.64 | 30-JUN-23:51 | 6601.40 | 0.00 |
July | 0.00 | 0.00 | 0.182962E+11 | 0.182160E+11 | 8680.76 | 31-JUL-24:00 | 8623.61 | 0.00 |
August | 0.00 | 0.00 | 0.234246E+11 | 0.232884E+11 | 10061.58 | 10-AUG-18:30 | 9986.88 | 0.00 |
September | 0.00 | 0.00 | 0.750547E+10 | 0.743612E+10 | 4497.44 | 30-SEP-23:55 | 4497.44 | 0.00 |
October | 0.00 | 0.00 | 0.119938E+11 | 0.119833E+11 | 6090.46 | 31-OCT-23:53 | 6090.46 | 0.00 |
November | 0.00 | 0.00 | 0.160540E+11 | 0.160387E+11 | 7017.21 | 04-NOV-16:00 | 6955.98 | 0.00 |
December | 0.00 | 0.00 | 0.212849E+11 | 0.212833E+11 | 8848.37 | 05-DEC-15:47 | 8848.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.172412E+12 | 0.172022E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.568079E+10 | 0.568046E+10 | 3065.38 | 3065.38 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.234246E+11 | 0.232884E+11 | 10061.58 | 9986.88 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.344254E+11 | 0.344240E+11 | 26661.63 | 05-JAN-16:10 | 26661.63 | 0.00 |
February | 0.00 | 0.00 | 0.830390E+11 | 0.829787E+11 | 50115.55 | 27-FEB-16:13 | 50115.55 | 0.00 |
March | 0.00 | 0.00 | 0.150714E+12 | 0.150665E+12 | 73566.95 | 31-MAR-23:25 | 73566.95 | 0.00 |
April | 0.00 | 0.00 | 0.199646E+12 | 0.199546E+12 | 92820.82 | 26-APR-18:00 | 92820.82 | 0.00 |
May | 0.00 | 0.00 | 0.652925E+11 | 0.650595E+11 | 44382.98 | 31-MAY-23:21 | 44380.78 | 0.00 |
June | 0.00 | 0.00 | 0.114197E+12 | 0.113883E+12 | 62172.28 | 30-JUN-23:51 | 62169.70 | 0.00 |
July | 0.00 | 0.00 | 0.171465E+12 | 0.170666E+12 | 83300.86 | 31-JUL-23:05 | 82373.62 | 0.00 |
August | 0.00 | 0.00 | 0.220541E+12 | 0.219192E+12 | 96979.54 | 10-AUG-18:30 | 96229.01 | 0.00 |
September | 0.00 | 0.00 | 0.653550E+11 | 0.646716E+11 | 40674.05 | 30-SEP-23:21 | 40674.05 | 0.00 |
October | 0.00 | 0.00 | 0.105600E+12 | 0.105495E+12 | 56388.24 | 04-OCT-16:50 | 56388.24 | 0.00 |
November | 0.00 | 0.00 | 0.141143E+12 | 0.140990E+12 | 65335.58 | 04-NOV-16:00 | 64722.67 | 0.00 |
December | 0.00 | 0.00 | 0.188096E+12 | 0.188082E+12 | 82499.95 | 05-DEC-15:53 | 82499.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.153951E+13 | 0.153565E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.344254E+11 | 0.344240E+11 | 26661.63 | 26661.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.220541E+12 | 0.219192E+12 | 96979.54 | 96229.01 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.188048E+10 | 0.188047E+10 | 2514.75 | 05-JAN-16:10 | 2514.75 | 0.00 |
February | 0.00 | 0.00 | 0.653763E+10 | 0.653168E+10 | 5006.84 | 27-FEB-16:13 | 5006.84 | 0.00 |
March | 0.00 | 0.00 | 0.135050E+11 | 0.135001E+11 | 7104.93 | 14-MAR-17:00 | 7104.93 | 0.00 |
April | 0.00 | 0.00 | 0.189448E+11 | 0.189356E+11 | 9440.47 | 26-APR-18:00 | 9440.47 | 0.00 |
May | 0.00 | 0.00 | 0.579683E+10 | 0.577361E+10 | 4279.64 | 31-MAY-23:01 | 4279.49 | 0.00 |
June | 0.00 | 0.00 | 0.110693E+11 | 0.110380E+11 | 6059.79 | 30-JUN-23:11 | 6056.92 | 0.00 |
July | 0.00 | 0.00 | 0.169199E+11 | 0.168401E+11 | 8263.09 | 31-JUL-23:05 | 8186.16 | 0.00 |
August | 0.00 | 0.00 | 0.217856E+11 | 0.216519E+11 | 9885.99 | 10-AUG-18:30 | 9811.32 | 0.00 |
September | 0.00 | 0.00 | 0.574269E+10 | 0.567495E+10 | 3860.70 | 08-SEP-17:30 | 3860.70 | 0.00 |
October | 0.00 | 0.00 | 0.908061E+10 | 0.907032E+10 | 5718.50 | 04-OCT-16:50 | 5718.50 | 0.00 |
November | 0.00 | 0.00 | 0.122023E+11 | 0.121872E+11 | 6462.81 | 04-NOV-16:00 | 6401.90 | 0.00 |
December | 0.00 | 0.00 | 0.165579E+11 | 0.165569E+11 | 8068.71 | 05-DEC-15:47 | 8068.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.140023E+12 | 0.139641E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.188048E+10 | 0.188047E+10 | 2514.75 | 2514.75 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.217856E+11 | 0.216519E+11 | 9885.99 | 9811.32 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 115981.31 | 2172348.17 | 02-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 78978.76 | 1976867.79 | 18-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 41000.43 | 2164032.92 | 27-MAR-04:11 |
April | 0.00 | 0.00 | 01-APR-00:03 | 20303.00 | 2000289.46 | 19-APR-04:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 9386.48 | 1644999.79 | 11-MAY-05:01 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 3295.01 | 718990.88 | 14-JUN-05:01 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 859.74 | 158606.72 | 12-JUL-09:53 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1342.67 | 231301.91 | 01-AUG-09:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 6627.68 | 492847.06 | 27-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 26238.47 | 1735296.99 | 24-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 58452.74 | 1853465.60 | 14-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 90015.26 | 2040328.33 | 04-DEC-05:11 |
Annual Sum or Average | 0.00 | 37537.84 | ||||
Minimum of Months | 0.00 | 0.00 | 859.74 | 158606.72 | ||
Maximum of Months | 0.00 | 0.00 | 115981.31 | 2172348.17 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3385.21 | 378039.35 | 26-JAN-15:44 | 321406.70 | 802092.69 | 01-JAN-17:10 |
February | 70975.03 | 1234294.89 | 27-FEB-15:00 | 125128.17 | 758744.82 | 24-FEB-16:35 |
March | 114154.07 | 1040110.93 | 18-MAR-12:04 | 8237.54 | 692392.10 | 01-MAR-00:01 |
April | 174231.17 | 2079823.42 | 26-APR-13:55 | 5033.67 | 527625.28 | 27-APR-21:45 |
May | 102643.49 | 1718518.49 | 04-MAY-14:50 | 195708.03 | 802080.63 | 27-MAY-15:20 |
June | 245584.23 | 2244100.79 | 27-JUN-14:05 | 81056.83 | 786772.98 | 30-JUN-06:02 |
July | 409587.88 | 2241610.61 | 27-JUL-14:05 | 5271.52 | 573235.64 | 01-JUL-00:32 |
August | 549990.19 | 2405353.34 | 29-AUG-14:30 | 7056.25 | 589712.30 | 09-AUG-02:25 |
September | 162205.12 | 2141795.36 | 12-SEP-14:05 | 171900.54 | 802061.55 | 17-SEP-20:33 |
October | 87882.22 | 1139370.97 | 04-OCT-12:45 | 109905.86 | 785424.57 | 06-OCT-20:22 |
November | 103397.08 | 995389.36 | 02-NOV-13:23 | 6190.40 | 569153.77 | 01-NOV-00:24 |
December | 106246.31 | 737460.76 | 21-DEC-08:47 | 5081.01 | 434594.41 | 26-DEC-11:51 |
Annual Sum or Average | 178466.85 | 86744.40 | ||||
Minimum of Months | 3385.21 | 378039.35 | 5033.67 | 434594.41 | ||
Maximum of Months | 549990.19 | 2405353.34 | 321406.70 | 802092.69 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 2684.78 | 56731.30 | 05-JAN-12:08 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 83013.17 | 1356873.91 | 27-FEB-14:33 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 221777.38 | 1175781.17 | 10-MAR-13:01 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 300256.27 | 2178937.08 | 26-APR-13:55 | 0.00 | 0.00 | 01-APR-00:03 |
May | 117847.76 | 1794364.01 | 14-MAY-15:31 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 282625.04 | 2656088.13 | 20-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:02 |
July | 491396.14 | 2982947.82 | 15-JUL-17:41 | 0.00 | 0.00 | 01-JUL-00:01 |
August | 620027.44 | 2926436.49 | 30-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 186018.40 | 2003152.81 | 10-SEP-13:42 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 105169.64 | 1823035.04 | 08-OCT-13:32 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 213387.04 | 1192046.10 | 04-NOV-12:06 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 227683.72 | 514926.88 | 30-DEC-05:58 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 238841.54 | 0.00 | ||||
Minimum of Months | 2684.78 | 56731.30 | 0.00 | 0.00 | ||
Maximum of Months | 620027.44 | 2982947.82 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 14332.44 | 51088.56 | 31-JAN-12:38 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 14518.51 | 51151.61 | 10-FEB-12:53 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 15258.70 | 50976.10 | 01-MAR-12:38 |
April | 0.00 | 0.00 | 01-APR-00:03 | 13905.15 | 49838.17 | 03-APR-11:15 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 13845.36 | 48285.37 | 01-MAY-11:23 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 13658.88 | 46385.37 | 01-JUN-11:13 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 12219.49 | 44765.03 | 03-JUL-11:17 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 13273.49 | 44111.29 | 31-AUG-11:13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12602.96 | 45074.25 | 29-SEP-11:53 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 12975.98 | 46820.12 | 31-OCT-11:35 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 13675.01 | 48661.94 | 30-NOV-12:51 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 13648.71 | 50167.92 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 13654.68 | ||||
Minimum of Months | 0.00 | 0.00 | 12219.49 | 44111.29 | ||
Maximum of Months | 0.00 | 0.00 | 15258.70 | 51151.61 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 685.67 | 326202.97 | 26-JAN-16:04 | 2655.13 | 168410.25 | 09-JAN-00:40 |
February | 83134.25 | 1349956.32 | 27-FEB-15:02 | 132.18 | 65418.73 | 16-FEB-14:10 |
March | 84951.59 | 1040306.35 | 18-MAR-12:06 | 3192.20 | 139866.70 | 30-MAR-05:41 |
April | 193663.62 | 3235228.62 | 27-APR-14:20 | 2355.60 | 116679.55 | 18-APR-18:00 |
May | 124241.91 | 2923182.20 | 04-MAY-14:50 | 1063.37 | 120374.12 | 20-MAY-03:20 |
June | 311466.07 | 3115588.44 | 22-JUN-15:50 | 20.60 | 50157.99 | 15-JUN-20:50 |
July | 525213.64 | 3695329.18 | 31-JUL-16:00 | 268.24 | 63418.48 | 05-JUL-02:20 |
August | 753241.74 | 4634282.85 | 29-AUG-14:30 | 277.57 | 60339.92 | 09-AUG-02:00 |
September | 205964.60 | 3014824.96 | 14-SEP-14:05 | 755.77 | 78557.99 | 07-SEP-24:00 |
October | 111555.15 | 1302168.80 | 04-OCT-15:00 | 87.82 | 52811.50 | 27-OCT-16:50 |
November | 72880.88 | 1050760.43 | 04-NOV-12:08 | 3599.81 | 120975.55 | 22-NOV-07:08 |
December | 68354.46 | 691310.19 | 21-DEC-08:48 | 4976.72 | 126234.64 | 07-DEC-00:20 |
Annual Sum or Average | 212500.23 | 1626.87 | ||||
Minimum of Months | 685.67 | 326202.97 | 20.60 | 50157.99 | ||
Maximum of Months | 753241.74 | 4634282.85 | 4976.72 | 168410.25 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.798306E+10 | 0.49 | 20996.61 | 05-JAN-06:01 | 1.63 |
February | 0.800371E+10 | 0.52 | 20996.61 | 08-FEB-06:01 | 1.63 |
March | 0.107859E+11 | 0.58 | 20209.44 | 01-MAR-06:01 | 1.60 |
April | 0.115710E+11 | 0.60 | 20209.44 | 18-APR-05:01 | 1.60 |
May | 0.121919E+11 | 0.62 | 17513.30 | 01-MAY-04:12 | 1.50 |
June | 0.134776E+11 | 0.67 | 18624.55 | 23-JUN-04:11 | 1.53 |
July | 0.155771E+11 | 0.69 | 22305.27 | 24-JUL-04:11 | 1.66 |
August | 0.180657E+11 | 0.76 | 23096.07 | 29-AUG-15:00 | 1.68 |
September | 0.124931E+11 | 0.62 | 19882.74 | 01-SEP-04:11 | 1.58 |
October | 0.106580E+11 | 0.56 | 19080.62 | 16-OCT-05:01 | 1.56 |
November | 0.926462E+10 | 0.53 | 20209.44 | 22-NOV-06:01 | 1.60 |
December | 0.895321E+10 | 0.51 | 20996.61 | 05-DEC-06:01 | 1.63 |
Annual Sum or Average | 0.139025E+12 | 0.60 | |||
Minimum of Months | 0.798306E+10 | 0.49 | 17513.30 | 1.50 | |
Maximum of Months | 0.180657E+11 | 0.76 | 23096.07 | 1.68 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.742778E+11 | 0.52 | 114462.50 | 02-JAN-05:11 | 1.29 |
February | 0.708553E+11 | 0.53 | 227260.41 | 04-FEB-06:01 | 1.73 |
March | 0.897417E+11 | 0.56 | 227260.41 | 16-MAR-05:01 | 1.74 |
April | 0.918093E+11 | 0.55 | 227260.41 | 01-APR-05:01 | 1.73 |
May | 0.107220E+12 | 0.60 | 227260.41 | 24-MAY-05:01 | 1.73 |
June | 0.115506E+12 | 0.64 | 174607.84 | 01-JUN-04:12 | 1.55 |
July | 0.124211E+12 | 0.63 | 214957.56 | 24-JUL-05:01 | 1.68 |
August | 0.139611E+12 | 0.68 | 202676.64 | 10-AUG-15:30 | 1.64 |
September | 0.109561E+12 | 0.60 | 183014.34 | 14-SEP-14:05 | 1.57 |
October | 0.896447E+11 | 0.53 | 227260.41 | 14-OCT-05:01 | 1.73 |
November | 0.732654E+11 | 0.50 | 227260.41 | 02-NOV-05:01 | 1.73 |
December | 0.719629E+11 | 0.49 | 114462.50 | 26-DEC-06:01 | 1.30 |
Annual Sum or Average | 0.115767E+13 | 0.57 | |||
Minimum of Months | 0.708553E+11 | 0.49 | 114462.50 | 1.29 | |
Maximum of Months | 0.139611E+12 | 0.68 | 227260.41 | 1.74 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.914163E+10 | 0.59 | 11495.46 | 02-JAN-05:21 | 1.19 |
February | 0.787756E+10 | 0.55 | 11495.46 | 01-FEB-06:02 | 1.19 |
March | 0.834572E+10 | 0.52 | 11495.46 | 04-MAR-06:01 | 1.19 |
April | 0.838327E+10 | 0.50 | 18831.84 | 27-APR-14:40 | 1.46 |
May | 0.984955E+10 | 0.54 | 18112.33 | 04-MAY-15:00 | 1.44 |
June | 0.108629E+11 | 0.57 | 18975.59 | 28-JUN-15:30 | 1.47 |
July | 0.120428E+11 | 0.56 | 20598.10 | 31-JUL-15:20 | 1.52 |
August | 0.131528E+11 | 0.60 | 22616.19 | 10-AUG-15:20 | 1.58 |
September | 0.955240E+10 | 0.52 | 18117.72 | 14-SEP-15:00 | 1.44 |
October | 0.779495E+10 | 0.47 | 14628.38 | 04-OCT-14:50 | 1.32 |
November | 0.757679E+10 | 0.50 | 11495.46 | 01-NOV-05:01 | 1.19 |
December | 0.823890E+10 | 0.53 | 11495.46 | 01-DEC-06:01 | 1.19 |
Annual Sum or Average | 0.112819E+12 | 0.54 | |||
Minimum of Months | 0.757679E+10 | 0.47 | 11495.46 | 1.19 | |
Maximum of Months | 0.131528E+11 | 0.60 | 22616.19 | 1.58 |
Report: FanReportMonthly
For: CAV_BAS SZVAV FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.518782E+10 | 0.47 | 15727.23 | 02-JAN-05:11 | 1.82 |
February | 0.494132E+10 | 0.49 | 15727.23 | 01-FEB-06:02 | 1.82 |
March | 0.738646E+10 | 0.57 | 15727.23 | 01-MAR-05:01 | 1.83 |
April | 0.761240E+10 | 0.56 | 15727.23 | 01-APR-04:11 | 1.82 |
May | 0.768925E+10 | 0.57 | 15727.23 | 01-MAY-04:12 | 1.82 |
June | 0.845098E+10 | 0.62 | 15727.23 | 01-JUN-04:12 | 1.82 |
July | 0.868344E+10 | 0.60 | 15727.23 | 01-JUL-04:11 | 1.82 |
August | 0.945722E+10 | 0.66 | 15727.23 | 01-AUG-04:11 | 1.81 |
September | 0.900233E+10 | 0.62 | 15727.23 | 01-SEP-04:11 | 1.81 |
October | 0.876608E+10 | 0.59 | 15727.23 | 02-OCT-04:11 | 1.82 |
November | 0.777220E+10 | 0.56 | 15727.23 | 01-NOV-04:11 | 1.82 |
December | 0.648139E+10 | 0.51 | 15727.23 | 01-DEC-05:11 | 1.82 |
Annual Sum or Average | 0.914309E+11 | 0.57 | |||
Minimum of Months | 0.494132E+10 | 0.47 | 15727.23 | 1.81 | |
Maximum of Months | 0.945722E+10 | 0.66 | 15727.23 | 1.83 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SYS11 FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.265716E+11 | 0.52 | 9920.69 | 01-JAN-00:03 | 0.52 |
February | 0.413138E+11 | 0.62 | 33041.96 | 01-FEB-00:03 | 0.86 |
March | 0.627412E+11 | 0.72 | 33041.96 | 01-MAR-00:02 | 0.86 |
April | 0.851152E+11 | 0.86 | 33041.96 | 01-APR-00:03 | 0.86 |
May | 0.265771E+11 | 0.52 | 33041.96 | 31-MAY-23:47 | 0.86 |
June | 0.402369E+11 | 0.60 | 33041.96 | 01-JUN-00:02 | 0.86 |
July | 0.663645E+11 | 0.74 | 33041.96 | 01-JUL-00:01 | 0.86 |
August | 0.850387E+11 | 0.84 | 33041.96 | 01-AUG-00:10 | 0.86 |
September | 0.257352E+11 | 0.51 | 33041.96 | 30-SEP-23:22 | 0.86 |
October | 0.430510E+11 | 0.61 | 33041.96 | 01-OCT-00:03 | 0.86 |
November | 0.608964E+11 | 0.72 | 33041.96 | 01-NOV-00:02 | 0.86 |
December | 0.884150E+11 | 0.86 | 33041.96 | 01-DEC-00:10 | 0.86 |
Annual Sum or Average | 0.652057E+12 | 0.68 | |||
Minimum of Months | 0.257352E+11 | 0.51 | 9920.69 | 0.52 | |
Maximum of Months | 0.884150E+11 | 0.86 | 33041.96 | 0.86 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.361936E+10 | 1.43 | 1351.31 | 01-JAN-00:20 | 1.42 |
February | 0.326910E+10 | 1.43 | 1351.31 | 01-FEB-00:04 | 1.42 |
March | 0.361936E+10 | 1.43 | 1351.31 | 01-MAR-00:18 | 1.42 |
April | 0.350261E+10 | 1.42 | 1351.31 | 01-APR-00:20 | 1.42 |
May | 0.361936E+10 | 1.42 | 1351.31 | 01-MAY-00:20 | 1.42 |
June | 0.350261E+10 | 1.42 | 1351.31 | 01-JUN-00:25 | 1.42 |
July | 0.361936E+10 | 1.42 | 1351.31 | 01-JUL-00:01 | 1.42 |
August | 0.361936E+10 | 1.42 | 1351.31 | 01-AUG-00:20 | 1.42 |
September | 0.350261E+10 | 1.42 | 1351.31 | 01-SEP-00:10 | 1.42 |
October | 0.361936E+10 | 1.42 | 1351.31 | 01-OCT-00:01 | 1.42 |
November | 0.350261E+10 | 1.42 | 1351.31 | 01-NOV-00:31 | 1.42 |
December | 0.361936E+10 | 1.43 | 1351.31 | 01-DEC-00:16 | 1.43 |
Annual Sum or Average | 0.426150E+11 | 1.42 | |||
Minimum of Months | 0.326910E+10 | 1.42 | 1351.31 | 1.42 | |
Maximum of Months | 0.361936E+10 | 1.43 | 1351.31 | 1.43 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.348505E+11 | 1.43 | 13011.70 | 09-JAN-16:13 | 1.43 |
February | 0.314779E+11 | 1.43 | 13011.70 | 01-FEB-00:01 | 1.42 |
March | 0.348505E+11 | 1.43 | 13011.70 | 17-MAR-17:38 | 1.42 |
April | 0.337263E+11 | 1.42 | 13011.70 | 01-APR-02:40 | 1.42 |
May | 0.348505E+11 | 1.42 | 13011.70 | 01-MAY-00:10 | 1.42 |
June | 0.337263E+11 | 1.42 | 13011.70 | 01-JUN-00:04 | 1.42 |
July | 0.348505E+11 | 1.42 | 13011.70 | 03-JUL-14:10 | 1.42 |
August | 0.348505E+11 | 1.42 | 13011.70 | 03-AUG-20:55 | 1.42 |
September | 0.337263E+11 | 1.42 | 13011.70 | 01-SEP-01:00 | 1.42 |
October | 0.348505E+11 | 1.42 | 13011.70 | 01-OCT-00:24 | 1.42 |
November | 0.337263E+11 | 1.42 | 13011.70 | 01-NOV-00:08 | 1.42 |
December | 0.348505E+11 | 1.43 | 13011.70 | 01-DEC-02:26 | 1.43 |
Annual Sum or Average | 0.410337E+12 | 1.42 | |||
Minimum of Months | 0.314779E+11 | 1.42 | 13011.70 | 1.42 | |
Maximum of Months | 0.348505E+11 | 1.43 | 13011.70 | 1.43 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.357618E+10 | 1.43 | 1335.19 | 02-JAN-08:48 | 1.42 |
February | 0.323010E+10 | 1.43 | 1335.19 | 01-FEB-00:07 | 1.42 |
March | 0.357618E+10 | 1.43 | 1335.19 | 01-MAR-00:04 | 1.42 |
April | 0.346082E+10 | 1.42 | 1335.19 | 01-APR-00:03 | 1.42 |
May | 0.357618E+10 | 1.42 | 1335.19 | 01-MAY-00:20 | 1.42 |
June | 0.346082E+10 | 1.42 | 1335.19 | 01-JUN-00:13 | 1.42 |
July | 0.357618E+10 | 1.42 | 1335.19 | 01-JUL-00:02 | 1.42 |
August | 0.357618E+10 | 1.42 | 1335.19 | 01-AUG-00:10 | 1.42 |
September | 0.346082E+10 | 1.42 | 1335.19 | 01-SEP-01:10 | 1.42 |
October | 0.357618E+10 | 1.42 | 1335.19 | 01-OCT-00:12 | 1.42 |
November | 0.346082E+10 | 1.42 | 1335.19 | 01-NOV-00:31 | 1.42 |
December | 0.357618E+10 | 1.43 | 1335.19 | 01-DEC-00:16 | 1.43 |
Annual Sum or Average | 0.421067E+11 | 1.42 | |||
Minimum of Months | 0.323010E+10 | 1.42 | 1335.19 | 1.42 | |
Maximum of Months | 0.357618E+10 | 1.43 | 1335.19 | 1.43 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.341465E+09 | 0.307318E+09 | 4043.70 | 17-JAN-06:02 | 3639.33 | 3639.33 | 49.96 | 17.08 |
February | 0.196520E+09 | 0.176868E+09 | 4039.42 | 21-FEB-06:01 | 3635.48 | 3635.48 | 48.65 | 17.08 |
March | 0.112987E+09 | 0.101689E+09 | 2424.99 | 25-MAR-05:01 | 2182.49 | 2182.49 | 42.78 | 12.54 |
April | 53995925.20 | 48596332.68 | 2406.54 | 18-APR-05:01 | 2165.89 | 2165.89 | 39.53 | 12.49 |
May | 24815071.74 | 22333564.57 | 2027.91 | 18-MAY-05:02 | 1825.12 | 1825.12 | 38.24 | 11.06 |
June | 8225381.50 | 7402843.35 | 744.71 | 14-JUN-05:01 | 670.24 | 670.24 | 27.77 | 4.55 |
July | 2082024.08 | 1873821.68 | 141.19 | 12-JUL-09:53 | 127.07 | 127.07 | 20.01 | 0.83 |
August | 3343067.43 | 3008760.69 | 208.72 | 01-AUG-09:03 | 187.85 | 187.85 | 20.95 | 1.24 |
September | 16515906.44 | 14864315.80 | 488.20 | 27-SEP-05:03 | 439.38 | 439.38 | 28.36 | 2.96 |
October | 73274187.76 | 65946768.98 | 2383.62 | 31-OCT-05:01 | 2145.26 | 2145.26 | 38.36 | 12.41 |
November | 0.156822E+09 | 0.141139E+09 | 2422.99 | 24-NOV-06:01 | 2180.69 | 2180.69 | 47.03 | 12.51 |
December | 0.252643E+09 | 0.227379E+09 | 4048.91 | 26-DEC-06:01 | 3644.02 | 3644.02 | 51.47 | 17.08 |
Annual Sum or Average | 0.124269E+10 | 0.111842E+10 | ||||||
Minimum of Months | 2082024.08 | 1873821.68 | 141.19 | 127.07 | 127.07 | 20.01 | 0.83 | |
Maximum of Months | 0.341465E+09 | 0.307318E+09 | 4048.91 | 3644.02 | 3644.02 | 51.47 | 17.08 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 84582838.41 | 76124554.57 | 478.26 | 11-JAN-21:13 | 430.43 | 430.43 | 6.81 | 4.13 |
February | 0.143632E+10 | 0.129268E+10 | 5812.21 | 27-FEB-15:05 | 5230.99 | 5230.99 | 6.73 | 48.40 |
March | 0.294508E+10 | 0.265057E+10 | 5371.09 | 10-MAR-13:01 | 4833.98 | 4833.98 | 8.11 | 45.42 |
April | 0.368256E+10 | 0.331431E+10 | 9993.57 | 26-APR-14:05 | 8994.22 | 8994.22 | 6.73 | 70.87 |
May | 0.111058E+10 | 0.999524E+09 | 7012.49 | 04-MAY-13:50 | 6311.24 | 6311.24 | 6.81 | 55.83 |
June | 0.311711E+10 | 0.280540E+10 | 16175.59 | 20-JUN-15:00 | 14558.03 | 14558.03 | 9.81 | 92.96 |
July | 0.491385E+10 | 0.442247E+10 | 16869.97 | 24-JUL-05:02 | 15182.97 | 15182.97 | 10.25 | 94.98 |
August | 0.589682E+10 | 0.530714E+10 | 19372.64 | 23-AUG-05:02 | 17435.38 | 17435.38 | 10.22 | 101.72 |
September | 0.170862E+10 | 0.153776E+10 | 11840.98 | 10-SEP-13:42 | 10656.88 | 10656.88 | 9.23 | 78.44 |
October | 0.168266E+10 | 0.151440E+10 | 11190.80 | 08-OCT-13:32 | 10071.72 | 10071.72 | 9.62 | 75.89 |
November | 0.275311E+10 | 0.247780E+10 | 5109.22 | 02-NOV-13:20 | 4598.30 | 4598.30 | 9.79 | 43.58 |
December | 0.308193E+10 | 0.277373E+10 | 2258.49 | 14-DEC-09:45 | 2032.64 | 2032.64 | 9.80 | 20.21 |
Annual Sum or Average | 0.324132E+11 | 0.291719E+11 | ||||||
Minimum of Months | 84582838.41 | 76124554.57 | 478.26 | 430.43 | 430.43 | 6.73 | 4.13 | |
Maximum of Months | 0.589682E+10 | 0.530714E+10 | 19372.64 | 17435.38 | 17435.38 | 10.25 | 101.72 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.306716E+10 | 0.276044E+10 | 10449.55 | 01-JAN-01:00 | 9404.60 | 9404.60 | 6.74 | 54.93 |
February | 0.810180E+10 | 0.729162E+10 | 10449.55 | 01-FEB-00:03 | 9404.60 | 9404.60 | 7.04 | 54.93 |
March | 0.245702E+11 | 0.221132E+11 | 10449.55 | 01-MAR-00:04 | 9404.60 | 9404.60 | 7.55 | 54.93 |
April | 0.246211E+11 | 0.221590E+11 | 10449.55 | 01-APR-00:03 | 9404.60 | 9404.60 | 10.57 | 54.93 |
May | 0.888430E+10 | 0.799587E+10 | 10449.55 | 01-MAY-02:40 | 9404.60 | 9404.60 | 7.23 | 54.93 |
June | 0.139372E+11 | 0.125435E+11 | 10449.55 | 01-JUN-00:02 | 9404.60 | 9404.60 | 8.04 | 54.93 |
July | 0.260166E+11 | 0.234149E+11 | 10449.55 | 01-JUL-00:03 | 9404.60 | 9404.60 | 8.02 | 54.93 |
August | 0.259190E+11 | 0.233271E+11 | 10449.55 | 01-AUG-00:10 | 9404.60 | 9404.60 | 10.15 | 54.93 |
September | 0.109936E+11 | 0.989427E+10 | 10449.55 | 01-SEP-00:20 | 9404.60 | 9404.60 | 7.67 | 54.93 |
October | 0.953502E+10 | 0.858151E+10 | 10449.55 | 01-OCT-00:03 | 9404.60 | 9404.60 | 7.65 | 54.93 |
November | 0.242585E+11 | 0.218327E+11 | 10449.55 | 01-NOV-00:04 | 9404.60 | 9404.60 | 9.02 | 54.93 |
December | 0.247082E+11 | 0.222374E+11 | 10449.55 | 01-DEC-00:11 | 9404.60 | 9404.60 | 10.24 | 54.93 |
Annual Sum or Average | 0.204613E+12 | 0.184152E+12 | ||||||
Minimum of Months | 0.306716E+10 | 0.276044E+10 | 10449.55 | 9404.60 | 9404.60 | 6.74 | 54.93 | |
Maximum of Months | 0.260166E+11 | 0.234149E+11 | 10449.55 | 9404.60 | 9404.60 | 10.57 | 54.93 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 6.72 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 6.91 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 7.20 | 0.00 |
April | 0.297812E+09 | 0.268031E+09 | 10449.55 | 26-APR-13:40 | 9404.60 | 9404.60 | 14.04 | 27.46 |
May | 0.134799E+09 | 0.121319E+09 | 10449.55 | 04-MAY-13:50 | 9404.60 | 9404.60 | 13.62 | 27.46 |
June | 0.492174E+09 | 0.442956E+09 | 10449.55 | 09-JUN-15:50 | 9404.60 | 9404.60 | 13.12 | 27.46 |
July | 0.148279E+10 | 0.133451E+10 | 10449.55 | 07-JUL-11:00 | 9404.60 | 9404.60 | 13.64 | 27.46 |
August | 0.367720E+10 | 0.330948E+10 | 10449.55 | 07-AUG-10:40 | 9404.60 | 9404.60 | 13.56 | 27.46 |
September | 0.407532E+09 | 0.366779E+09 | 10449.55 | 11-SEP-14:30 | 9404.60 | 9404.60 | 13.75 | 27.46 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 7.41 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 8.76 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 10.13 | 0.00 |
Annual Sum or Average | 0.649231E+10 | 0.584308E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 0.00 | |
Maximum of Months | 0.367720E+10 | 0.330948E+10 | 10449.55 | 9404.60 | 9404.60 | 14.04 | 27.46 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 56.98 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 57.12 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 57.27 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:01 | 16.86 | 16.86 | 57.26 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:01 | 16.86 | 16.86 | 57.56 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:01 | 16.86 | 16.86 | 57.46 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:01 | 16.86 | 16.86 | 57.59 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:01 | 16.86 | 16.86 | 57.56 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:01 | 16.86 | 16.86 | 57.55 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:01 | 16.86 | 16.86 | 57.58 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 57.49 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 57.33 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.98 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.59 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.786680E+10 | 0.708012E+10 | 26945.97 | 26-JAN-16:04 | 24251.37 | 24251.37 | 22.11 | 77.50 |
February | 0.208888E+11 | 0.187999E+11 | 27008.18 | 27-FEB-15:02 | 24307.36 | 24307.36 | 25.27 | 77.50 |
March | 0.632790E+11 | 0.569511E+11 | 26988.74 | 18-MAR-12:06 | 24289.86 | 24289.86 | 24.31 | 77.50 |
April | 0.642296E+11 | 0.578067E+11 | 54053.99 | 27-APR-14:20 | 48648.59 | 48648.59 | 26.09 | 155.01 |
May | 0.231311E+11 | 0.208180E+11 | 54032.18 | 04-MAY-14:50 | 48628.96 | 48628.96 | 25.61 | 155.01 |
June | 0.371011E+11 | 0.333910E+11 | 54045.62 | 22-JUN-15:50 | 48641.06 | 48641.06 | 25.91 | 155.01 |
July | 0.705902E+11 | 0.635312E+11 | 54086.17 | 31-JUL-16:00 | 48677.56 | 48677.56 | 26.80 | 155.01 |
August | 0.759183E+11 | 0.683265E+11 | 54151.98 | 29-AUG-14:30 | 48736.78 | 48736.78 | 28.25 | 155.01 |
September | 0.292329E+11 | 0.263097E+11 | 54038.58 | 14-SEP-14:05 | 48634.72 | 48634.72 | 25.75 | 155.01 |
October | 0.245837E+11 | 0.221253E+11 | 27004.83 | 04-OCT-15:00 | 24304.35 | 24304.35 | 25.12 | 77.50 |
November | 0.624252E+11 | 0.561827E+11 | 26989.36 | 04-NOV-12:08 | 24290.43 | 24290.43 | 24.34 | 77.50 |
December | 0.636119E+11 | 0.572507E+11 | 26967.82 | 21-DEC-08:48 | 24271.04 | 24271.04 | 23.23 | 77.50 |
Annual Sum or Average | 0.542859E+12 | 0.488573E+12 | ||||||
Minimum of Months | 0.786680E+10 | 0.708012E+10 | 26945.97 | 24251.37 | 24251.37 | 22.11 | 77.50 | |
Maximum of Months | 0.759183E+11 | 0.683265E+11 | 54151.98 | 48736.78 | 48736.78 | 28.25 | 155.01 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 34.05 | 34.05 | 115981.31 | 2172348.17 | 02-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 28.56 | 28.56 | 78978.76 | 1976867.79 | 18-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 23.79 | 23.79 | 41000.43 | 2164032.92 | 27-MAR-04:11 |
April | 0.00 | 0.00 | 01-APR-00:03 | 25.43 | 25.43 | 20303.00 | 2000289.46 | 19-APR-04:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 21.91 | 21.91 | 9386.48 | 1644999.79 | 11-MAY-05:01 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 21.82 | 21.82 | 3295.01 | 718990.88 | 14-JUN-05:01 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 20.43 | 20.43 | 859.74 | 158606.72 | 12-JUL-09:53 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 19.69 | 19.69 | 1342.67 | 231301.91 | 01-AUG-09:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 20.03 | 20.03 | 6627.68 | 492847.06 | 27-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 20.80 | 20.80 | 26238.47 | 1735296.99 | 24-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 27.51 | 27.51 | 58452.74 | 1853465.60 | 14-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 29.30 | 29.30 | 90015.26 | 2040328.33 | 04-DEC-05:11 |
Annual Sum or Average | 0.00 | 37537.84 | ||||||
Minimum of Months | 0.00 | 0.00 | 19.69 | 19.69 | 859.74 | 158606.72 | ||
Maximum of Months | 0.00 | 0.00 | 34.05 | 34.05 | 115981.31 | 2172348.17 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3385.21 | 378039.35 | 26-JAN-15:44 | 8.34 | 6.70 | 321406.70 | 802092.69 | 01-JAN-17:10 |
February | 70975.03 | 1234294.89 | 27-FEB-15:00 | 12.06 | 6.70 | 125128.17 | 758744.82 | 24-FEB-16:35 |
March | 114154.07 | 1040110.93 | 18-MAR-12:04 | 11.41 | 6.89 | 8237.54 | 692392.10 | 01-MAR-00:01 |
April | 174231.17 | 2079823.42 | 26-APR-13:55 | 11.22 | 6.70 | 5033.67 | 527625.28 | 27-APR-21:45 |
May | 102643.49 | 1718518.49 | 04-MAY-14:50 | 10.43 | 6.70 | 195708.03 | 802080.63 | 27-MAY-15:20 |
June | 245584.23 | 2244100.79 | 27-JUN-14:05 | 11.58 | 6.70 | 81056.83 | 786772.98 | 30-JUN-06:02 |
July | 409587.88 | 2241610.61 | 27-JUL-14:05 | 11.57 | 6.70 | 5271.52 | 573235.64 | 01-JUL-00:32 |
August | 549990.19 | 2405353.34 | 29-AUG-14:30 | 11.93 | 6.70 | 7056.25 | 589712.30 | 09-AUG-02:25 |
September | 162205.12 | 2141795.36 | 12-SEP-14:05 | 11.35 | 6.70 | 171900.54 | 802061.55 | 17-SEP-20:33 |
October | 87882.22 | 1139370.97 | 04-OCT-12:45 | 11.65 | 6.70 | 109905.86 | 785424.57 | 06-OCT-20:22 |
November | 103397.08 | 995389.36 | 02-NOV-13:23 | 11.03 | 6.70 | 6190.40 | 569153.77 | 01-NOV-00:24 |
December | 106246.31 | 737460.76 | 21-DEC-08:47 | 9.90 | 6.70 | 5081.01 | 434594.41 | 26-DEC-11:51 |
Annual Sum or Average | 178466.85 | 86744.40 | ||||||
Minimum of Months | 3385.21 | 378039.35 | 8.34 | 6.70 | 5033.67 | 434594.41 | ||
Maximum of Months | 549990.19 | 2405353.34 | 12.06 | 6.89 | 321406.70 | 802092.69 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 2684.78 | 56731.30 | 05-JAN-12:08 | 9.98 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 83013.17 | 1356873.91 | 27-FEB-14:33 | 16.45 | 7.00 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 221777.38 | 1175781.17 | 10-MAR-13:01 | 12.88 | 7.40 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 300256.27 | 2178937.08 | 26-APR-13:55 | 14.22 | 6.70 | 0.00 | 0.00 | 01-APR-00:03 |
May | 117847.76 | 1794364.01 | 14-MAY-15:31 | 18.70 | 9.15 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 282625.04 | 2656088.13 | 20-JUN-15:00 | 13.52 | 9.78 | 0.00 | 0.00 | 01-JUN-00:02 |
July | 491396.14 | 2982947.82 | 15-JUL-17:41 | 15.32 | 11.43 | 0.00 | 0.00 | 01-JUL-00:01 |
August | 620027.44 | 2926436.49 | 30-AUG-05:02 | 14.11 | 11.67 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 186018.40 | 2003152.81 | 10-SEP-13:42 | 12.80 | 10.47 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 105169.64 | 1823035.04 | 08-OCT-13:32 | 12.44 | 10.18 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 213387.04 | 1192046.10 | 04-NOV-12:06 | 15.16 | 7.40 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 227683.72 | 514926.88 | 30-DEC-05:58 | 12.78 | 8.90 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 238841.54 | 0.00 | ||||||
Minimum of Months | 2684.78 | 56731.30 | 9.98 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 620027.44 | 2982947.82 | 18.70 | 11.67 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 58.14 | 58.14 | 14332.44 | 51088.56 | 31-JAN-12:38 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 57.62 | 57.62 | 14518.51 | 51151.61 | 10-FEB-12:53 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 57.62 | 57.62 | 15258.70 | 50976.10 | 01-MAR-12:38 |
April | 0.00 | 0.00 | 01-APR-00:03 | 57.67 | 57.67 | 13905.15 | 49838.17 | 03-APR-11:15 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.21 | 58.21 | 13845.36 | 48285.37 | 01-MAY-11:23 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 57.84 | 57.84 | 13658.88 | 46385.37 | 01-JUN-11:13 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 57.91 | 57.91 | 12219.49 | 44765.03 | 03-JUL-11:17 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.96 | 57.96 | 13273.49 | 44111.29 | 31-AUG-11:13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.95 | 57.95 | 12602.96 | 45074.25 | 29-SEP-11:53 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 57.90 | 57.90 | 12975.98 | 46820.12 | 31-OCT-11:35 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 57.82 | 57.82 | 13675.01 | 48661.94 | 30-NOV-12:51 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.73 | 57.73 | 13648.71 | 50167.92 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 13654.68 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.62 | 57.62 | 12219.49 | 44111.29 | ||
Maximum of Months | 0.00 | 0.00 | 58.21 | 58.21 | 15258.70 | 51151.61 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 685.67 | 326202.97 | 26-JAN-16:04 | 22.11 | 21.10 | 2655.13 | 168410.25 | 09-JAN-00:40 |
February | 83134.25 | 1349956.32 | 27-FEB-15:02 | 25.27 | 21.10 | 132.18 | 65418.73 | 16-FEB-14:10 |
March | 84951.59 | 1040306.35 | 18-MAR-12:06 | 24.31 | 21.10 | 3192.20 | 139866.70 | 30-MAR-05:41 |
April | 193663.62 | 3235228.62 | 27-APR-14:20 | 26.09 | 21.72 | 2355.60 | 116679.55 | 18-APR-18:00 |
May | 124241.91 | 2923182.20 | 04-MAY-14:50 | 25.61 | 21.10 | 1063.37 | 120374.12 | 20-MAY-03:20 |
June | 311466.07 | 3115588.44 | 22-JUN-15:50 | 25.91 | 21.10 | 20.60 | 50157.99 | 15-JUN-20:50 |
July | 525213.64 | 3695329.18 | 31-JUL-16:00 | 26.80 | 22.96 | 268.24 | 63418.48 | 05-JUL-02:20 |
August | 753241.74 | 4634282.85 | 29-AUG-14:30 | 28.25 | 23.91 | 277.57 | 60339.92 | 09-AUG-02:00 |
September | 205964.60 | 3014824.96 | 14-SEP-14:05 | 25.75 | 21.60 | 755.77 | 78557.99 | 07-SEP-24:00 |
October | 111555.15 | 1302168.80 | 04-OCT-15:00 | 25.12 | 21.10 | 87.82 | 52811.50 | 27-OCT-16:50 |
November | 72880.88 | 1050760.43 | 04-NOV-12:08 | 24.34 | 21.10 | 3599.81 | 120975.55 | 22-NOV-07:08 |
December | 68354.46 | 691310.19 | 21-DEC-08:48 | 23.23 | 21.10 | 4976.72 | 126234.64 | 07-DEC-00:20 |
Annual Sum or Average | 212500.23 | 1626.87 | ||||||
Minimum of Months | 685.67 | 326202.97 | 22.11 | 21.10 | 20.60 | 50157.99 | ||
Maximum of Months | 753241.74 | 4634282.85 | 28.25 | 23.91 | 4976.72 | 168410.25 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.849695E+10 | 0.00 | 2878.24 | 0.798306E+10 | 0.00 | 0.00 |
February | 0.484121E+10 | 0.00 | 0.907003E+09 | 0.800371E+10 | 0.00 | 0.00 |
March | 0.206555E+10 | 0.00 | 0.139777E+10 | 0.107859E+11 | 0.00 | 0.00 |
April | 0.765069E+09 | 0.00 | 0.118424E+11 | 0.115710E+11 | 0.00 | 0.00 |
May | 0.378145E+09 | 0.00 | 0.203770E+11 | 0.121919E+11 | 0.00 | 0.00 |
June | 38374398.33 | 0.00 | 0.381580E+11 | 0.134776E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.688980E+11 | 0.155771E+11 | 0.00 | 0.00 |
August | 148384.80 | 0.00 | 0.936130E+11 | 0.180657E+11 | 0.00 | 0.00 |
September | 0.162738E+09 | 0.00 | 0.317552E+11 | 0.124931E+11 | 0.00 | 0.00 |
October | 0.121519E+10 | 0.00 | 0.546546E+10 | 0.106580E+11 | 0.00 | 0.00 |
November | 0.290068E+10 | 0.00 | 0.874412E+09 | 0.926462E+10 | 0.00 | 0.00 |
December | 0.513205E+10 | 0.00 | 1232.84 | 0.895321E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.259961E+11 | 0.00 | 0.273288E+12 | 0.139025E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 1232.84 | 0.798306E+10 | 0.00 | 0.00 |
Maximum of Months | 0.849695E+10 | 0.00 | 0.936130E+11 | 0.180657E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.250659E+12 | 0.00 | 193866.98 | 0.742778E+11 | 0.00 | 0.00 |
February | 0.150995E+12 | 0.00 | 0.109231E+11 | 0.708553E+11 | 0.00 | 0.00 |
March | 0.859186E+11 | 0.00 | 0.343017E+11 | 0.897417E+11 | 0.00 | 0.00 |
April | 0.407835E+11 | 0.00 | 0.107256E+12 | 0.918093E+11 | 0.00 | 0.00 |
May | 0.190735E+11 | 0.00 | 0.195048E+12 | 0.107220E+12 | 0.00 | 0.00 |
June | 0.615743E+10 | 0.00 | 0.345768E+12 | 0.115506E+12 | 0.00 | 0.00 |
July | 0.125085E+10 | 0.00 | 0.585647E+12 | 0.124211E+12 | 0.00 | 0.00 |
August | 0.238049E+10 | 0.00 | 0.766382E+12 | 0.139611E+12 | 0.00 | 0.00 |
September | 0.122827E+11 | 0.00 | 0.303243E+12 | 0.109561E+12 | 0.00 | 0.00 |
October | 0.542711E+11 | 0.00 | 0.592120E+11 | 0.896447E+11 | 0.00 | 0.00 |
November | 0.119333E+12 | 0.00 | 0.123937E+11 | 0.732654E+11 | 0.00 | 0.00 |
December | 0.191260E+12 | 0.00 | 5545840.15 | 0.719629E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.934366E+12 | 0.00 | 0.242018E+13 | 0.115767E+13 | 0.00 | 0.00 |
Minimum of Months | 0.125085E+10 | 0.00 | 193866.98 | 0.708553E+11 | 0.00 | 0.00 |
Maximum of Months | 0.250659E+12 | 0.00 | 0.766382E+12 | 0.139611E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.528304E+11 | 0.00 | 4133138.14 | 0.914163E+10 | 0.00 | 0.00 |
February | 0.360755E+11 | 0.00 | 0.648557E+09 | 0.787756E+10 | 0.00 | 0.00 |
March | 0.222364E+11 | 0.00 | 0.110534E+10 | 0.834572E+10 | 0.00 | 0.00 |
April | 0.112912E+11 | 0.00 | 0.110401E+11 | 0.838327E+10 | 0.00 | 0.00 |
May | 0.577626E+10 | 0.00 | 0.202657E+11 | 0.984955E+10 | 0.00 | 0.00 |
June | 0.237784E+10 | 0.00 | 0.378000E+11 | 0.108629E+11 | 0.00 | 0.00 |
July | 0.106204E+10 | 0.00 | 0.660235E+11 | 0.120428E+11 | 0.00 | 0.00 |
August | 0.122357E+10 | 0.00 | 0.857102E+11 | 0.131528E+11 | 0.00 | 0.00 |
September | 0.478033E+10 | 0.00 | 0.297430E+11 | 0.955240E+10 | 0.00 | 0.00 |
October | 0.149651E+11 | 0.00 | 0.428511E+10 | 0.779495E+10 | 0.00 | 0.00 |
November | 0.298105E+11 | 0.00 | 0.847179E+09 | 0.757679E+10 | 0.00 | 0.00 |
December | 0.457111E+11 | 0.00 | 701859.22 | 0.823890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228140E+12 | 0.00 | 0.257474E+12 | 0.112819E+12 | 0.00 | 0.00 |
Minimum of Months | 0.106204E+10 | 0.00 | 701859.22 | 0.757679E+10 | 0.00 | 0.00 |
Maximum of Months | 0.528304E+11 | 0.00 | 0.857102E+11 | 0.131528E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.630730E+10 | 0.518782E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.665979E+10 | 0.494132E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.731741E+10 | 0.738646E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.125529E+11 | 0.761240E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.211410E+11 | 0.768925E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.286139E+11 | 0.845098E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.416940E+11 | 0.868344E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.564131E+11 | 0.945722E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.303734E+11 | 0.900233E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.162320E+11 | 0.876608E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.788016E+10 | 0.777220E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.572481E+10 | 0.648139E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.240910E+12 | 0.914309E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.572481E+10 | 0.494132E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.564131E+11 | 0.945722E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 3898644.71 | 0.979808E+11 | 0.00 | 26.56 |
February | 0.00 | 0.00 | 0.144747E+12 | 0.112002E+12 | 0.00 | 26.30 |
March | 0.00 | 0.00 | 0.237788E+12 | 0.172640E+12 | 0.00 | 40.88 |
April | 0.00 | 0.00 | 0.281601E+12 | 0.168416E+12 | 0.00 | 30.99 |
May | 0.00 | 0.00 | 0.472313E+10 | 0.547510E+11 | 0.00 | 10.48 |
June | 0.00 | 0.00 | 0.160505E+12 | 0.509799E+11 | 0.00 | 4.00 |
July | 0.00 | 0.00 | 0.284671E+12 | 0.777473E+11 | 0.00 | 4.23 |
August | 0.00 | 0.00 | 0.409190E+12 | 0.861921E+11 | 0.00 | 0.43 |
September | 0.00 | 0.00 | 0.574634E+10 | 0.269221E+11 | 0.00 | 0.44 |
October | 0.00 | 0.00 | 0.141361E+12 | 0.716129E+11 | 0.00 | 10.63 |
November | 0.00 | 0.00 | 0.222483E+12 | 0.127562E+12 | 0.00 | 24.80 |
December | 0.00 | 0.00 | 0.254490E+12 | 0.218424E+12 | 0.00 | 48.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.214731E+13 | 0.126523E+13 | 0.00 | 228.10 |
Minimum of Months | 0.00 | 0.00 | 3898644.71 | 0.269221E+11 | 0.00 | 0.43 |
Maximum of Months | 0.00 | 0.00 | 0.409190E+12 | 0.218424E+12 | 0.00 | 48.36 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.537424E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.610882E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.802016E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.910462E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.587869E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.695570E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.839183E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.981006E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.575084E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.699407E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.774025E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.911733E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.892466E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.537424E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.981006E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.442055E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.521397E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.693020E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.780124E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.518547E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.612329E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.734146E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.846986E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.506812E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.606811E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.662791E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.762520E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.768754E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.442055E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.846986E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.418013E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.517775E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.726879E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.836181E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.535309E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.659802E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.805451E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.930099E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.521884E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.622728E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.684514E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.792849E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.805148E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.418013E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.930099E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.798306E+10 | 2878.24 | 0.849695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.800371E+10 | 0.907003E+09 | 0.484121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107859E+11 | 0.139777E+10 | 0.206555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115710E+11 | 0.118424E+11 | 0.765069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121919E+11 | 0.203770E+11 | 0.378145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134776E+11 | 0.381580E+11 | 38374398.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155771E+11 | 0.688980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180657E+11 | 0.936130E+11 | 148384.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124931E+11 | 0.317552E+11 | 0.162738E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106580E+11 | 0.546546E+10 | 0.121519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.926462E+10 | 0.874412E+09 | 0.290068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.895321E+10 | 1232.84 | 0.513205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139025E+12 | 0.273288E+12 | 0.259961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.798306E+10 | 1232.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180657E+11 | 0.936130E+11 | 0.849695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.742778E+11 | 193866.98 | 0.250659E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.708553E+11 | 0.109231E+11 | 0.150995E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.897417E+11 | 0.343017E+11 | 0.859186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.918093E+11 | 0.107256E+12 | 0.407835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107220E+12 | 0.195048E+12 | 0.190735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.115506E+12 | 0.345768E+12 | 0.615743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.124211E+12 | 0.585647E+12 | 0.125085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139611E+12 | 0.766382E+12 | 0.238049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109561E+12 | 0.303243E+12 | 0.122827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.896447E+11 | 0.592120E+11 | 0.542711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.732654E+11 | 0.123937E+11 | 0.119333E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.719629E+11 | 5545840.15 | 0.191260E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115767E+13 | 0.242018E+13 | 0.934366E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.708553E+11 | 193866.98 | 0.125085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139611E+12 | 0.766382E+12 | 0.250659E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.914163E+10 | 4133138.14 | 0.528304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.787756E+10 | 0.648557E+09 | 0.360755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.834572E+10 | 0.110534E+10 | 0.222364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.838327E+10 | 0.110401E+11 | 0.112912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.984955E+10 | 0.202657E+11 | 0.577626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108629E+11 | 0.378000E+11 | 0.237784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120428E+11 | 0.660235E+11 | 0.106204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131528E+11 | 0.857102E+11 | 0.122357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.955240E+10 | 0.297430E+11 | 0.478033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.779495E+10 | 0.428511E+10 | 0.149651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.757679E+10 | 0.847179E+09 | 0.298105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.823890E+10 | 701859.22 | 0.457111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112819E+12 | 0.257474E+12 | 0.228140E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.757679E+10 | 701859.22 | 0.106204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131528E+11 | 0.857102E+11 | 0.528304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.518782E+10 | 0.630730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.494132E+10 | 0.665979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.738646E+10 | 0.731741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.761240E+10 | 0.125529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.768925E+10 | 0.211410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.845098E+10 | 0.286139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.868344E+10 | 0.416940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.945722E+10 | 0.564131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.900233E+10 | 0.303734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.876608E+10 | 0.162320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.777220E+10 | 0.788016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.648139E+10 | 0.572481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.914309E+11 | 0.240910E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.494132E+10 | 0.572481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.945722E+10 | 0.564131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.265716E+11 | 3898644.71 | 0.00 | 0.00 | 0.00 | 0.710892E+11 | 0.00 | 0.00 |
February | 0.413138E+11 | 0.144747E+12 | 0.00 | 0.00 | 0.00 | 0.703710E+11 | 0.00 | 0.00 |
March | 0.627412E+11 | 0.237788E+12 | 0.00 | 0.00 | 0.00 | 0.109406E+12 | 0.00 | 0.00 |
April | 0.851152E+11 | 0.281601E+12 | 0.00 | 0.00 | 0.00 | 0.829279E+11 | 0.00 | 0.00 |
May | 0.265771E+11 | 0.472313E+10 | 0.00 | 0.00 | 0.00 | 0.280476E+11 | 0.00 | 0.00 |
June | 0.402369E+11 | 0.160505E+12 | 0.00 | 0.00 | 0.00 | 0.106949E+11 | 0.00 | 0.00 |
July | 0.663645E+11 | 0.284671E+12 | 0.00 | 0.00 | 0.00 | 0.113318E+11 | 0.00 | 0.00 |
August | 0.850387E+11 | 0.409190E+12 | 0.00 | 0.00 | 0.00 | 0.114825E+10 | 0.00 | 0.00 |
September | 0.257352E+11 | 0.574634E+10 | 0.00 | 0.00 | 0.00 | 0.118150E+10 | 0.00 | 0.00 |
October | 0.430510E+11 | 0.141361E+12 | 0.00 | 0.00 | 0.00 | 0.284339E+11 | 0.00 | 0.00 |
November | 0.608964E+11 | 0.222483E+12 | 0.00 | 0.00 | 0.00 | 0.663666E+11 | 0.00 | 0.00 |
December | 0.884150E+11 | 0.254490E+12 | 0.00 | 0.00 | 0.00 | 0.129427E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.652057E+12 | 0.214731E+13 | 0.00 | 0.00 | 0.00 | 0.610425E+12 | 0.00 | 0.00 |
Minimum of Months | 0.257352E+11 | 3898644.71 | 0.00 | 0.00 | 0.00 | 0.114825E+10 | 0.00 | 0.00 |
Maximum of Months | 0.884150E+11 | 0.409190E+12 | 0.00 | 0.00 | 0.00 | 0.129427E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.361936E+10 | 0.568079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.326910E+10 | 0.998741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.361936E+10 | 0.167394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.350261E+10 | 0.215568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.361936E+10 | 0.751112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.350261E+10 | 0.123772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.361936E+10 | 0.182962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.361936E+10 | 0.234246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.350261E+10 | 0.750547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.361936E+10 | 0.119938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.350261E+10 | 0.160540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.361936E+10 | 0.212849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.426150E+11 | 0.172412E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.326910E+10 | 0.568079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.361936E+10 | 0.234246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.348505E+11 | 0.344254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.314779E+11 | 0.830390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.348505E+11 | 0.150714E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.337263E+11 | 0.199646E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.348505E+11 | 0.652925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.337263E+11 | 0.114197E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.348505E+11 | 0.171465E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.348505E+11 | 0.220541E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.337263E+11 | 0.653550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.348505E+11 | 0.105600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.337263E+11 | 0.141143E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.348505E+11 | 0.188096E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.410337E+12 | 0.153951E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.314779E+11 | 0.344254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.348505E+11 | 0.220541E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.357618E+10 | 0.188048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.323010E+10 | 0.653763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.357618E+10 | 0.135050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.346082E+10 | 0.189448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.357618E+10 | 0.579683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.346082E+10 | 0.110693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.357618E+10 | 0.169199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.357618E+10 | 0.217856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.346082E+10 | 0.574269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.357618E+10 | 0.908061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.346082E+10 | 0.122023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357618E+10 | 0.165579E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421067E+11 | 0.140023E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.323010E+10 | 0.188048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.357618E+10 | 0.217856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.798306E+10 | 0.849695E+10 | 2878.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.800371E+10 | 0.484121E+10 | 0.907003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107859E+11 | 0.206555E+10 | 0.139777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115710E+11 | 0.765069E+09 | 0.118424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121919E+11 | 0.378145E+09 | 0.203770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134776E+11 | 38374398.33 | 0.381580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155771E+11 | 0.00 | 0.688980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180657E+11 | 148384.80 | 0.936130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124931E+11 | 0.162738E+09 | 0.317552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106580E+11 | 0.121519E+10 | 0.546546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.926462E+10 | 0.290068E+10 | 0.874412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.895321E+10 | 0.513205E+10 | 1232.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139025E+12 | 0.259961E+11 | 0.273288E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.798306E+10 | 0.00 | 1232.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180657E+11 | 0.849695E+10 | 0.936130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.742778E+11 | 0.250659E+12 | 193866.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.708553E+11 | 0.150995E+12 | 0.109231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.897417E+11 | 0.859186E+11 | 0.343017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.918093E+11 | 0.407835E+11 | 0.107256E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107220E+12 | 0.190735E+11 | 0.195048E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.115506E+12 | 0.615743E+10 | 0.345768E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.124211E+12 | 0.125085E+10 | 0.585647E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139611E+12 | 0.238049E+10 | 0.766382E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109561E+12 | 0.122827E+11 | 0.303243E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.896447E+11 | 0.542711E+11 | 0.592120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.732654E+11 | 0.119333E+12 | 0.123937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.719629E+11 | 0.191260E+12 | 5545840.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115767E+13 | 0.934366E+12 | 0.242018E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.708553E+11 | 0.125085E+10 | 193866.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139611E+12 | 0.250659E+12 | 0.766382E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.914163E+10 | 0.528304E+11 | 4133138.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.787756E+10 | 0.360755E+11 | 0.648557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.834572E+10 | 0.222364E+11 | 0.110534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.838327E+10 | 0.112912E+11 | 0.110401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.984955E+10 | 0.577626E+10 | 0.202657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108629E+11 | 0.237784E+10 | 0.378000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120428E+11 | 0.106204E+10 | 0.660235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131528E+11 | 0.122357E+10 | 0.857102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.955240E+10 | 0.478033E+10 | 0.297430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.779495E+10 | 0.149651E+11 | 0.428511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.757679E+10 | 0.298105E+11 | 0.847179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.823890E+10 | 0.457111E+11 | 701859.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112819E+12 | 0.228140E+12 | 0.257474E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.757679E+10 | 0.106204E+10 | 701859.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131528E+11 | 0.528304E+11 | 0.857102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.518782E+10 | 0.00 | 0.630730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.494132E+10 | 0.00 | 0.665979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.738646E+10 | 0.00 | 0.731741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.761240E+10 | 0.00 | 0.125529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.768925E+10 | 0.00 | 0.211410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.845098E+10 | 0.00 | 0.286139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.868344E+10 | 0.00 | 0.416940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.945722E+10 | 0.00 | 0.564131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.900233E+10 | 0.00 | 0.303734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.876608E+10 | 0.00 | 0.162320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.777220E+10 | 0.00 | 0.788016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.648139E+10 | 0.00 | 0.572481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.914309E+11 | 0.00 | 0.240910E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.494132E+10 | 0.00 | 0.572481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.945722E+10 | 0.00 | 0.564131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.265716E+11 | 0.00 | 3898644.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714092E+11 | 0.00 | 0.00 | 0.00 |
February | 0.413138E+11 | 0.00 | 0.144747E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706877E+11 | 0.00 | 0.00 | 0.00 |
March | 0.627412E+11 | 0.00 | 0.237788E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109899E+12 | 0.00 | 0.00 | 0.00 |
April | 0.851152E+11 | 0.00 | 0.281601E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.833012E+11 | 0.00 | 0.00 | 0.00 |
May | 0.265771E+11 | 0.00 | 0.472313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281739E+11 | 0.00 | 0.00 | 0.00 |
June | 0.402369E+11 | 0.00 | 0.160505E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107430E+11 | 0.00 | 0.00 | 0.00 |
July | 0.663645E+11 | 0.00 | 0.284671E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113828E+11 | 0.00 | 0.00 | 0.00 |
August | 0.850387E+11 | 0.00 | 0.409190E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115342E+10 | 0.00 | 0.00 | 0.00 |
September | 0.257352E+11 | 0.00 | 0.574634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118682E+10 | 0.00 | 0.00 | 0.00 |
October | 0.430510E+11 | 0.00 | 0.141361E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285619E+11 | 0.00 | 0.00 | 0.00 |
November | 0.608964E+11 | 0.00 | 0.222483E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666654E+11 | 0.00 | 0.00 | 0.00 |
December | 0.884150E+11 | 0.00 | 0.254490E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130009E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.652057E+12 | 0.00 | 0.214731E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613173E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.257352E+11 | 0.00 | 3898644.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115342E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.884150E+11 | 0.00 | 0.409190E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130009E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.361936E+10 | 0.00 | 0.00 | 0.00 | 0.175488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.326910E+10 | 0.00 | 0.00 | 0.00 | 0.283972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.361936E+10 | 0.00 | 0.00 | 0.00 | 0.440080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.350261E+10 | 0.00 | 0.00 | 0.00 | 0.560201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.361936E+10 | 0.00 | 0.00 | 0.00 | 0.225933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.350261E+10 | 0.00 | 0.00 | 0.00 | 0.345309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.361936E+10 | 0.00 | 0.00 | 0.00 | 0.477247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.361936E+10 | 0.00 | 0.00 | 0.00 | 0.619070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.350261E+10 | 0.00 | 0.00 | 0.00 | 0.224824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.361936E+10 | 0.00 | 0.00 | 0.00 | 0.337471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.350261E+10 | 0.00 | 0.00 | 0.00 | 0.423764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.361936E+10 | 0.00 | 0.00 | 0.00 | 0.549797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.426150E+11 | 0.00 | 0.00 | 0.00 | 0.466316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.326910E+10 | 0.00 | 0.00 | 0.00 | 0.175488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.361936E+10 | 0.00 | 0.00 | 0.00 | 0.619070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.348505E+11 | 0.00 | 0.00 | 0.00 | 0.935496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.314779E+11 | 0.00 | 0.00 | 0.00 | 0.206618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.348505E+11 | 0.00 | 0.00 | 0.00 | 0.344515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.337263E+11 | 0.00 | 0.00 | 0.00 | 0.442861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.348505E+11 | 0.00 | 0.00 | 0.00 | 0.170042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.337263E+11 | 0.00 | 0.00 | 0.00 | 0.275065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.348505E+11 | 0.00 | 0.00 | 0.00 | 0.385641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.348505E+11 | 0.00 | 0.00 | 0.00 | 0.498481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.337263E+11 | 0.00 | 0.00 | 0.00 | 0.169549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.348505E+11 | 0.00 | 0.00 | 0.00 | 0.258305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.337263E+11 | 0.00 | 0.00 | 0.00 | 0.325527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.348505E+11 | 0.00 | 0.00 | 0.00 | 0.414014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.410337E+12 | 0.00 | 0.00 | 0.00 | 0.358417E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.314779E+11 | 0.00 | 0.00 | 0.00 | 0.935496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.348505E+11 | 0.00 | 0.00 | 0.00 | 0.498481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.357618E+10 | 0.00 | 0.00 | 0.00 | 0.603946E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.323010E+10 | 0.00 | 0.00 | 0.00 | 0.194765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.357618E+10 | 0.00 | 0.00 | 0.00 | 0.369260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.346082E+10 | 0.00 | 0.00 | 0.00 | 0.490099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.357618E+10 | 0.00 | 0.00 | 0.00 | 0.177691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.346082E+10 | 0.00 | 0.00 | 0.00 | 0.313720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.357618E+10 | 0.00 | 0.00 | 0.00 | 0.447833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.357618E+10 | 0.00 | 0.00 | 0.00 | 0.572481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.346082E+10 | 0.00 | 0.00 | 0.00 | 0.175802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.357618E+10 | 0.00 | 0.00 | 0.00 | 0.265110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.346082E+10 | 0.00 | 0.00 | 0.00 | 0.338432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357618E+10 | 0.00 | 0.00 | 0.00 | 0.435231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421067E+11 | 0.00 | 0.00 | 0.00 | 0.384082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.323010E+10 | 0.00 | 0.00 | 0.00 | 0.603946E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.357618E+10 | 0.00 | 0.00 | 0.00 | 0.572481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108647E+11 | 0.00 | 0.00 | 72628639.94 | 0.00 | 0.00 | 0.429287E+11 | 0.00 | 0.45 |
February | 0.167858E+11 | 0.00 | 0.00 | 0.204282E+09 | 0.00 | 0.00 | 0.309900E+11 | 0.00 | 0.52 |
March | 0.136628E+11 | 0.00 | 0.00 | 0.370453E+09 | 0.00 | 0.00 | 0.476573E+11 | 0.00 | 0.67 |
April | 0.768585E+10 | 22243227.28 | 0.00 | 0.183937E+09 | 0.00 | 0.00 | 0.466446E+11 | 0.00 | 0.73 |
May | 0.550894E+10 | 43157739.54 | 0.00 | 0.132871E+09 | 0.00 | 0.00 | 0.446911E+11 | 0.00 | 0.81 |
June | 0.374108E+10 | 9326078.71 | 0.00 | 0.410510E+09 | 460560.64 | 0.00 | 0.421090E+11 | 0.00 | 0.96 |
July | 0.176587E+10 | 0.109898E+10 | 0.00 | 0.368260E+09 | 4399053.21 | 0.00 | 0.328951E+11 | 0.00 | 0.95 |
August | 0.117697E+10 | 0.251909E+10 | 0.00 | 0.152695E+09 | 1711828.62 | 0.00 | 0.302124E+11 | 0.00 | 0.97 |
September | 0.342945E+10 | 0.246847E+09 | 0.00 | 0.151384E+09 | 0.00 | 0.00 | 0.419678E+11 | 0.00 | 0.98 |
October | 0.947468E+10 | 0.00 | 0.00 | 0.318442E+09 | 0.00 | 0.00 | 0.498896E+11 | 0.00 | 0.82 |
November | 0.126019E+11 | 0.00 | 0.00 | 0.370385E+09 | 0.00 | 0.00 | 0.497696E+11 | 0.00 | 0.67 |
December | 0.110356E+11 | 0.00 | 0.00 | 0.188474E+09 | 0.00 | 0.00 | 0.485680E+11 | 0.00 | 0.52 |
Annual Sum or Average | 0.977335E+11 | 0.393965E+10 | 0.00 | 0.292432E+10 | 6571442.48 | 0.00 | 0.508323E+12 | 0.00 | 0.76 |
Minimum of Months | 0.117697E+10 | 0.00 | 0.00 | 72628639.94 | 0.00 | 0.00 | 0.302124E+11 | 0.00 | 0.45 |
Maximum of Months | 0.167858E+11 | 0.251909E+10 | 0.00 | 0.410510E+09 | 4399053.21 | 0.00 | 0.498896E+11 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.115319E+11 | 0.00 | 0.00 | 0.111796E+09 | 0.00 | 0.00 | 0.330936E+11 | 0.00 | 0.39 |
February | 0.134431E+11 | 0.00 | 0.00 | 0.326183E+09 | 0.00 | 0.00 | 0.303031E+11 | 0.00 | 0.49 |
March | 0.106261E+11 | 0.00 | 0.00 | 0.595816E+09 | 0.00 | 0.00 | 0.491053E+11 | 0.00 | 0.66 |
April | 0.519574E+10 | 17974350.43 | 0.00 | 0.288126E+09 | 0.00 | 0.00 | 0.518843E+11 | 0.00 | 0.77 |
May | 0.504328E+10 | 328894.48 | 0.00 | 0.200382E+09 | 0.00 | 0.00 | 0.514207E+11 | 0.00 | 0.90 |
June | 0.408517E+10 | 3265408.23 | 0.00 | 0.476003E+09 | 6392921.93 | 0.00 | 0.481055E+11 | 0.00 | 1.06 |
July | 0.457717E+10 | 0.138197E+09 | 0.00 | 0.424243E+09 | 4126782.85 | 0.00 | 0.376566E+11 | 0.00 | 1.04 |
August | 0.367529E+10 | 0.556236E+09 | 0.00 | 0.182704E+09 | 0.00 | 0.00 | 0.367004E+11 | 0.00 | 1.04 |
September | 0.399169E+10 | 0.00 | 0.00 | 0.182008E+09 | 0.00 | 0.00 | 0.455840E+11 | 0.00 | 0.97 |
October | 0.916701E+10 | 0.00 | 0.00 | 0.401551E+09 | 0.00 | 0.00 | 0.474702E+11 | 0.00 | 0.77 |
November | 0.868640E+10 | 0.00 | 0.00 | 0.521877E+09 | 0.00 | 0.00 | 0.446003E+11 | 0.00 | 0.58 |
December | 0.991385E+10 | 0.00 | 0.00 | 0.237742E+09 | 0.00 | 0.00 | 0.407429E+11 | 0.00 | 0.45 |
Annual Sum or Average | 0.899367E+11 | 0.716002E+09 | 0.00 | 0.394843E+10 | 10519704.78 | 0.00 | 0.516667E+12 | 0.00 | 0.76 |
Minimum of Months | 0.367529E+10 | 0.00 | 0.00 | 0.111796E+09 | 0.00 | 0.00 | 0.303031E+11 | 0.00 | 0.39 |
Maximum of Months | 0.134431E+11 | 0.556236E+09 | 0.00 | 0.595816E+09 | 6392921.93 | 0.00 | 0.518843E+11 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.221931E+12 | 0.00 | 0.00 | 0.325964E+09 | 0.00 | 0.243398E+10 | 0.107549E+12 | 0.00 | 0.30 |
February | 0.196562E+12 | 0.00 | 0.00 | 0.142876E+10 | 0.00 | 90068335.88 | 0.135892E+12 | 0.00 | 0.38 |
March | 0.166979E+12 | 0.00 | 0.00 | 0.362356E+10 | 0.00 | 0.00 | 0.265433E+12 | 0.00 | 0.49 |
April | 0.120494E+12 | 0.171733E+09 | 0.00 | 0.159747E+10 | 85163612.10 | 0.00 | 0.290829E+12 | 0.00 | 0.58 |
May | 0.875448E+11 | 4771475.75 | 0.00 | 0.148170E+10 | 5492728.82 | 0.00 | 0.370291E+12 | 0.00 | 0.76 |
June | 0.956105E+11 | 38078790.98 | 0.00 | 0.306665E+10 | 75592819.40 | 0.00 | 0.321326E+12 | 0.00 | 0.88 |
July | 0.831224E+11 | 0.128867E+10 | 0.00 | 0.233205E+10 | 97200853.46 | 0.00 | 0.226302E+12 | 0.00 | 0.81 |
August | 0.487737E+11 | 0.522130E+10 | 0.00 | 0.106374E+10 | 1061271.71 | 0.00 | 0.236523E+12 | 0.00 | 0.78 |
September | 0.817508E+11 | 0.00 | 0.00 | 0.117770E+10 | 3737867.52 | 0.00 | 0.306987E+12 | 0.00 | 0.80 |
October | 0.140203E+12 | 0.00 | 0.00 | 0.248008E+10 | 0.00 | 0.00 | 0.284779E+12 | 0.00 | 0.60 |
November | 0.170135E+12 | 0.00 | 0.00 | 0.243134E+10 | 0.00 | 0.00 | 0.194555E+12 | 0.00 | 0.41 |
December | 0.208533E+12 | 0.00 | 0.00 | 0.810231E+09 | 0.00 | 24325655.91 | 0.139684E+12 | 0.00 | 0.32 |
Annual Sum or Average | 0.162164E+13 | 0.672456E+10 | 0.00 | 0.218193E+11 | 0.268249E+09 | 0.254837E+10 | 0.288015E+13 | 0.00 | 0.59 |
Minimum of Months | 0.487737E+11 | 0.00 | 0.00 | 0.325964E+09 | 0.00 | 0.00 | 0.107549E+12 | 0.00 | 0.30 |
Maximum of Months | 0.221931E+12 | 0.522130E+10 | 0.00 | 0.362356E+10 | 97200853.46 | 0.243398E+10 | 0.370291E+12 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.244321E+11 | 0.00 | 0.00 | 16572.96 | 0.00 | 0.238682E+10 | 30332454.61 | 0.00 | 0.27 |
February | 0.235414E+11 | 0.00 | 0.00 | 7922831.43 | 0.00 | 0.147858E+10 | 0.141711E+10 | 0.00 | 0.33 |
March | 0.271733E+11 | 0.00 | 0.00 | 79481949.71 | 0.00 | 0.460315E+09 | 0.680497E+10 | 0.00 | 0.42 |
April | 0.191624E+11 | 250704.34 | 0.00 | 76041751.88 | 31939.68 | 0.102166E+09 | 0.161541E+11 | 0.00 | 0.51 |
May | 0.155263E+11 | 0.00 | 0.00 | 91647700.45 | 0.00 | 0.00 | 0.273836E+11 | 0.00 | 0.72 |
June | 0.125867E+11 | 0.00 | 0.00 | 0.251423E+09 | 4278276.89 | 0.00 | 0.286765E+11 | 0.00 | 0.86 |
July | 0.884396E+10 | 40610715.51 | 0.00 | 0.182166E+09 | 151986.53 | 0.00 | 0.232389E+11 | 0.00 | 0.81 |
August | 0.755952E+10 | 0.267979E+09 | 0.00 | 78506053.91 | 0.00 | 0.00 | 0.182294E+11 | 0.00 | 0.74 |
September | 0.144623E+11 | 0.00 | 0.00 | 55532902.30 | 0.00 | 0.00 | 0.186158E+11 | 0.00 | 0.72 |
October | 0.233894E+11 | 0.00 | 0.00 | 68746638.38 | 0.00 | 0.325928E+09 | 0.845121E+10 | 0.00 | 0.50 |
November | 0.252170E+11 | 0.00 | 0.00 | 10557382.36 | 56287.50 | 0.102359E+10 | 0.934792E+09 | 0.00 | 0.35 |
December | 0.242139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204805E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.226108E+12 | 0.308840E+09 | 0.00 | 0.902043E+09 | 4518490.59 | 0.782546E+10 | 0.149937E+12 | 0.00 | 0.54 |
Minimum of Months | 0.755952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.271733E+11 | 0.267979E+09 | 0.00 | 0.251423E+09 | 4278276.89 | 0.238682E+10 | 0.286765E+11 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.515791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424836E+09 | 0.00 | 0.00 | 0.38 |
February | 0.470867E+10 | 0.00 | 0.00 | 2401803.52 | 0.00 | 0.213197E+09 | 0.307095E+09 | 0.00 | 0.46 |
March | 0.528395E+10 | 0.00 | 0.00 | 15320331.63 | 0.00 | 1550296.70 | 0.133207E+10 | 0.00 | 0.58 |
April | 0.348066E+10 | 3098033.72 | 0.00 | 15755307.04 | 0.00 | 0.00 | 0.319969E+10 | 0.00 | 0.74 |
May | 0.275266E+10 | 82412.53 | 0.00 | 18233061.31 | 0.00 | 0.00 | 0.480975E+10 | 0.00 | 1.01 |
June | 0.201381E+10 | 667766.56 | 0.00 | 49446540.72 | 992290.19 | 0.00 | 0.513328E+10 | 0.00 | 1.22 |
July | 0.170769E+10 | 26913111.39 | 0.00 | 40220933.65 | 640546.87 | 0.00 | 0.424552E+10 | 0.00 | 1.25 |
August | 0.159465E+10 | 0.105030E+09 | 0.00 | 15506131.79 | 0.00 | 0.00 | 0.366865E+10 | 0.00 | 1.15 |
September | 0.272073E+10 | 0.00 | 0.00 | 11640889.92 | 0.00 | 0.00 | 0.338761E+10 | 0.00 | 0.99 |
October | 0.454606E+10 | 0.00 | 0.00 | 12407293.68 | 0.00 | 0.00 | 0.175422E+10 | 0.00 | 0.68 |
November | 0.537480E+10 | 0.00 | 0.00 | 3740875.10 | 0.00 | 1297493.18 | 0.345847E+09 | 0.00 | 0.49 |
December | 0.560901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49659581.27 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.449506E+11 | 0.135791E+09 | 0.00 | 0.184673E+09 | 1632837.07 | 0.690540E+09 | 0.281837E+11 | 0.00 | 0.78 |
Minimum of Months | 0.159465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.560901E+10 | 0.105030E+09 | 0.00 | 49446540.72 | 992290.19 | 0.424836E+09 | 0.513328E+10 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.720301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972220E+09 | 0.00 | 0.00 | 0.86 |
February | 0.696966E+10 | 0.00 | 0.00 | 3705.32 | 0.00 | 0.625598E+09 | 10122397.61 | 0.00 | 1.02 |
March | 0.870739E+10 | 0.00 | 0.00 | 8535036.80 | 0.00 | 0.121280E+09 | 0.728481E+09 | 0.00 | 1.29 |
April | 0.615471E+10 | 2095585.14 | 0.00 | 13527299.70 | 435205.34 | 18416510.36 | 0.305956E+10 | 0.00 | 1.53 |
May | 0.555924E+10 | 74754.18 | 0.00 | 13023677.76 | 0.00 | 1066689.31 | 0.399629E+10 | 0.00 | 1.90 |
June | 0.432953E+10 | 441335.96 | 0.00 | 42850882.72 | 1571152.62 | 0.00 | 0.480097E+10 | 0.00 | 2.28 |
July | 0.361794E+10 | 21369941.58 | 0.00 | 35126520.31 | 937973.43 | 0.00 | 0.362441E+10 | 0.00 | 2.19 |
August | 0.324976E+10 | 80367375.35 | 0.00 | 13988493.16 | 0.00 | 0.00 | 0.339145E+10 | 0.00 | 2.17 |
September | 0.515219E+10 | 0.00 | 0.00 | 10189588.85 | 0.00 | 1126481.38 | 0.317317E+10 | 0.00 | 2.01 |
October | 0.775758E+10 | 0.00 | 0.00 | 8911474.42 | 0.00 | 5568147.29 | 0.123863E+10 | 0.00 | 1.49 |
November | 0.829324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62065737.29 | 0.00 | 0.00 | 1.11 |
December | 0.774396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545667E+09 | 0.00 | 0.00 | 0.90 |
Annual Sum or Average | 0.747382E+11 | 0.104349E+09 | 0.00 | 0.146157E+09 | 2944331.39 | 0.235301E+10 | 0.240231E+11 | 0.00 | 1.56 |
Minimum of Months | 0.324976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 |
Maximum of Months | 0.870739E+10 | 80367375.35 | 0.00 | 42850882.72 | 1571152.62 | 0.972220E+09 | 0.480097E+10 | 0.00 | 2.28 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.897328E+10 | 0.00 | 0.00 | 3672433.83 | 0.00 | 0.175383E+10 | 0.124007E+10 | 0.00 | 0.81 |
February | 0.810694E+10 | 0.00 | 0.00 | 29456342.12 | 0.00 | 0.107685E+10 | 0.287619E+10 | 0.00 | 1.06 |
March | 0.978084E+10 | 0.00 | 0.00 | 69043486.32 | 0.00 | 0.352431E+09 | 0.570481E+10 | 0.00 | 1.41 |
April | 0.831819E+10 | 7793239.95 | 0.00 | 29819687.00 | 0.00 | 63550290.61 | 0.589950E+10 | 0.00 | 1.60 |
May | 0.813615E+10 | 151396.64 | 0.00 | 20139078.77 | 0.00 | 6608722.37 | 0.586710E+10 | 0.00 | 1.85 |
June | 0.724342E+10 | 803991.55 | 0.00 | 40545942.24 | 2081855.11 | 0.00 | 0.468624E+10 | 0.00 | 2.00 |
July | 0.586626E+10 | 45382557.48 | 0.00 | 27289525.55 | 1343886.89 | 0.00 | 0.409918E+10 | 0.00 | 2.05 |
August | 0.512822E+10 | 0.190342E+09 | 0.00 | 15508437.44 | 0.00 | 0.00 | 0.390212E+10 | 0.00 | 1.98 |
September | 0.717938E+10 | 0.00 | 0.00 | 22345582.94 | 0.00 | 3031056.68 | 0.605747E+10 | 0.00 | 2.26 |
October | 0.907489E+10 | 0.00 | 0.00 | 52364907.10 | 0.00 | 49201594.19 | 0.607320E+10 | 0.00 | 1.71 |
November | 0.105020E+11 | 0.00 | 0.00 | 19740824.70 | 0.00 | 0.428018E+09 | 0.161578E+10 | 0.00 | 1.10 |
December | 0.925877E+10 | 0.00 | 0.00 | 11370039.90 | 0.00 | 0.123638E+10 | 0.214076E+10 | 0.00 | 0.89 |
Annual Sum or Average | 0.975684E+11 | 0.244473E+09 | 0.00 | 0.341296E+09 | 3425742.00 | 0.496990E+10 | 0.501624E+11 | 0.00 | 1.56 |
Minimum of Months | 0.512822E+10 | 0.00 | 0.00 | 3672433.83 | 0.00 | 0.00 | 0.124007E+10 | 0.00 | 0.81 |
Maximum of Months | 0.105020E+11 | 0.190342E+09 | 0.00 | 69043486.32 | 2081855.11 | 0.175383E+10 | 0.607320E+10 | 0.00 | 2.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.963929E+10 | 0.00 | 0.00 | 72569.59 | 0.00 | 0.157165E+09 | 73416236.10 | 0.00 | 1.04 |
February | 0.866521E+10 | 0.00 | 0.00 | 4776448.96 | 0.00 | 15348177.63 | 0.572766E+09 | 0.00 | 1.25 |
March | 0.982169E+10 | 0.00 | 0.00 | 21737767.53 | 0.00 | 511788.08 | 0.197501E+10 | 0.00 | 1.61 |
April | 0.701982E+10 | 5304537.55 | 0.00 | 20134497.85 | 0.00 | 0.00 | 0.432966E+10 | 0.00 | 1.94 |
May | 0.675123E+10 | 90276.10 | 0.00 | 16007951.24 | 0.00 | 0.00 | 0.471978E+10 | 0.00 | 2.37 |
June | 0.579530E+10 | 1627510.37 | 0.00 | 33879785.44 | 1713431.33 | 0.00 | 0.418803E+10 | 0.00 | 2.63 |
July | 0.412833E+10 | 52840288.77 | 0.00 | 34222309.25 | 164654.03 | 0.00 | 0.442348E+10 | 0.00 | 2.82 |
August | 0.307754E+10 | 0.165134E+09 | 0.00 | 20744510.15 | 0.00 | 0.00 | 0.455953E+10 | 0.00 | 2.57 |
September | 0.618741E+10 | 0.00 | 0.00 | 10150477.95 | 0.00 | 0.00 | 0.358740E+10 | 0.00 | 2.46 |
October | 0.926903E+10 | 0.00 | 0.00 | 13932406.43 | 0.00 | 366494.62 | 0.167515E+10 | 0.00 | 1.84 |
November | 0.986812E+10 | 0.00 | 0.00 | 2326570.68 | 0.00 | 1535493.27 | 0.239012E+09 | 0.00 | 1.35 |
December | 0.966087E+10 | 0.00 | 0.00 | 1294408.07 | 0.00 | 1045846.52 | 0.352391E+09 | 0.00 | 1.09 |
Annual Sum or Average | 0.898839E+11 | 0.224996E+09 | 0.00 | 0.179280E+09 | 1878085.36 | 0.175972E+09 | 0.306956E+11 | 0.00 | 1.92 |
Minimum of Months | 0.307754E+10 | 0.00 | 0.00 | 72569.59 | 0.00 | 0.00 | 73416236.10 | 0.00 | 1.04 |
Maximum of Months | 0.986812E+10 | 0.165134E+09 | 0.00 | 34222309.25 | 1713431.33 | 0.157165E+09 | 0.471978E+10 | 0.00 | 2.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.298949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351299E+11 | 0.00 | 0.00 | 0.47 |
February | 0.399129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220210E+11 | 0.00 | 0.00 | 0.55 |
March | 0.629666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.980807E+10 | 0.00 | 0.00 | 0.65 |
April | 0.540576E+11 | 29350753.81 | 0.00 | 21629823.75 | 17336327.02 | 0.477244E+10 | 0.616367E+10 | 0.00 | 0.72 |
May | 0.475065E+11 | 2092112.05 | 0.00 | 80342793.06 | 0.00 | 0.467978E+09 | 0.233870E+11 | 0.00 | 0.96 |
June | 0.380451E+11 | 8173091.14 | 0.00 | 0.251280E+09 | 15388049.01 | 3629761.09 | 0.265399E+11 | 0.00 | 1.12 |
July | 0.282423E+11 | 0.271307E+09 | 0.00 | 0.165486E+09 | 16347647.86 | 0.00 | 0.224749E+11 | 0.00 | 1.09 |
August | 0.254486E+11 | 0.102943E+10 | 0.00 | 71204767.79 | 136542.80 | 0.00 | 0.190833E+11 | 0.00 | 1.00 |
September | 0.454033E+11 | 0.00 | 0.00 | 39590418.40 | 760898.84 | 27334467.80 | 0.139006E+11 | 0.00 | 0.97 |
October | 0.611257E+11 | 0.00 | 0.00 | 6854354.23 | 0.00 | 0.536082E+10 | 0.127585E+10 | 0.00 | 0.75 |
November | 0.486071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162996E+11 | 0.00 | 0.00 | 0.57 |
December | 0.342408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316586E+11 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.515451E+12 | 0.134035E+10 | 0.00 | 0.636389E+09 | 49969465.53 | 0.125549E+12 | 0.112825E+12 | 0.00 | 0.78 |
Minimum of Months | 0.254486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.629666E+11 | 0.102943E+10 | 0.00 | 0.251280E+09 | 17336327.02 | 0.351299E+11 | 0.265399E+11 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.272720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368991E+11 | 0.00 | 0.00 | 0.71 |
February | 0.385750E+11 | 0.00 | 0.00 | 3410219.90 | 0.00 | 0.226819E+11 | 0.215757E+09 | 0.00 | 0.84 |
March | 0.601663E+11 | 0.00 | 0.00 | 70859754.63 | 0.00 | 0.102059E+11 | 0.517971E+10 | 0.00 | 1.04 |
April | 0.472525E+11 | 26419843.82 | 0.00 | 0.114638E+09 | 16975482.66 | 0.411181E+10 | 0.228536E+11 | 0.00 | 1.29 |
May | 0.474280E+11 | 2462279.97 | 0.00 | 0.119385E+09 | 0.00 | 0.934481E+09 | 0.330834E+11 | 0.00 | 1.71 |
June | 0.392972E+11 | 5138189.35 | 0.00 | 0.388204E+09 | 21850875.74 | 32250676.24 | 0.405879E+11 | 0.00 | 2.10 |
July | 0.313837E+11 | 0.255156E+09 | 0.00 | 0.300784E+09 | 13259696.63 | 0.00 | 0.295699E+11 | 0.00 | 1.97 |
August | 0.275221E+11 | 0.909505E+09 | 0.00 | 0.121467E+09 | 726616.38 | 16060095.61 | 0.269102E+11 | 0.00 | 1.91 |
September | 0.435168E+11 | 392475.77 | 0.00 | 89587051.55 | 0.00 | 0.433311E+09 | 0.255628E+11 | 0.00 | 1.78 |
October | 0.555633E+11 | 0.00 | 0.00 | 71754079.53 | 0.00 | 0.667751E+10 | 0.904896E+10 | 0.00 | 1.23 |
November | 0.453029E+11 | 0.00 | 0.00 | 2393201.32 | 0.00 | 0.188747E+11 | 99590548.51 | 0.00 | 0.88 |
December | 0.314099E+11 | 0.00 | 0.00 | 49846.01 | 0.00 | 0.334844E+11 | 5440063.77 | 0.00 | 0.72 |
Annual Sum or Average | 0.494690E+12 | 0.119907E+10 | 0.00 | 0.128253E+10 | 52812671.41 | 0.134351E+12 | 0.193117E+12 | 0.00 | 1.35 |
Minimum of Months | 0.272720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 |
Maximum of Months | 0.601663E+11 | 0.909505E+09 | 0.00 | 0.388204E+09 | 21850875.74 | 0.368991E+11 | 0.405879E+11 | 0.00 | 2.10 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.611442E+11 | 0.00 | 0.00 | 28862305.15 | 0.00 | 0.439648E+11 | 0.942324E+10 | 0.00 | 0.82 |
February | 0.676960E+11 | 0.00 | 0.00 | 0.299878E+09 | 0.00 | 0.244010E+11 | 0.268852E+11 | 0.00 | 1.07 |
March | 0.841148E+11 | 0.00 | 0.00 | 0.665870E+09 | 0.00 | 0.139126E+11 | 0.488102E+11 | 0.00 | 1.34 |
April | 0.722544E+11 | 0.145284E+09 | 0.00 | 0.254402E+09 | 0.00 | 0.757736E+10 | 0.489627E+11 | 0.00 | 1.49 |
May | 0.786859E+11 | 4708326.75 | 0.00 | 0.176815E+09 | 0.00 | 0.145828E+10 | 0.504306E+11 | 0.00 | 1.79 |
June | 0.786639E+11 | 11555190.91 | 0.00 | 0.286491E+09 | 26730569.46 | 46172953.05 | 0.322803E+11 | 0.00 | 1.93 |
July | 0.556166E+11 | 0.537220E+09 | 0.00 | 0.195903E+09 | 18807813.65 | 0.00 | 0.321658E+11 | 0.00 | 1.90 |
August | 0.500440E+11 | 0.218385E+10 | 0.00 | 0.121126E+09 | 164197.63 | 0.00 | 0.281073E+11 | 0.00 | 1.81 |
September | 0.691721E+11 | 3354486.08 | 0.00 | 0.216707E+09 | 0.00 | 76764288.55 | 0.552236E+11 | 0.00 | 2.24 |
October | 0.804072E+11 | 0.00 | 0.00 | 0.527675E+09 | 0.00 | 0.747363E+10 | 0.555170E+11 | 0.00 | 1.67 |
November | 0.844860E+11 | 0.00 | 0.00 | 0.169915E+09 | 0.00 | 0.203568E+11 | 0.122334E+11 | 0.00 | 1.06 |
December | 0.633470E+11 | 0.00 | 0.00 | 96093924.44 | 0.00 | 0.396622E+11 | 0.167674E+11 | 0.00 | 0.87 |
Annual Sum or Average | 0.845632E+12 | 0.288597E+10 | 0.00 | 0.303974E+10 | 45702580.73 | 0.158930E+12 | 0.416807E+12 | 0.00 | 1.50 |
Minimum of Months | 0.500440E+11 | 0.00 | 0.00 | 28862305.15 | 0.00 | 0.00 | 0.942324E+10 | 0.00 | 0.82 |
Maximum of Months | 0.844860E+11 | 0.218385E+10 | 0.00 | 0.665870E+09 | 26730569.46 | 0.439648E+11 | 0.555170E+11 | 0.00 | 2.24 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.476403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379884E+11 | 0.00 | 0.00 | 0.95 |
February | 0.607782E+11 | 0.00 | 0.00 | 16529238.52 | 0.00 | 0.193781E+11 | 0.155958E+10 | 0.00 | 1.13 |
March | 0.810235E+11 | 0.00 | 0.00 | 69183157.26 | 0.00 | 0.106483E+11 | 0.600473E+10 | 0.00 | 1.35 |
April | 0.683591E+11 | 62326993.60 | 0.00 | 82493146.11 | 7198626.45 | 0.469321E+10 | 0.164128E+11 | 0.00 | 1.56 |
May | 0.682851E+11 | 1281463.37 | 0.00 | 0.105230E+09 | 1477603.10 | 0.948588E+09 | 0.273555E+11 | 0.00 | 2.08 |
June | 0.645391E+11 | 20713407.09 | 0.00 | 0.184570E+09 | 20319705.43 | 25072488.82 | 0.187172E+11 | 0.00 | 2.27 |
July | 0.425881E+11 | 0.552068E+09 | 0.00 | 0.163908E+09 | 2387424.91 | 0.00 | 0.245086E+11 | 0.00 | 2.31 |
August | 0.396731E+11 | 0.153488E+10 | 0.00 | 89354913.26 | 1375367.13 | 0.00 | 0.181335E+11 | 0.00 | 2.02 |
September | 0.618561E+11 | 1004756.37 | 0.00 | 64093849.54 | 0.00 | 32926191.51 | 0.195737E+11 | 0.00 | 2.13 |
October | 0.779937E+11 | 0.00 | 0.00 | 74618243.77 | 0.00 | 0.555059E+10 | 0.763323E+10 | 0.00 | 1.58 |
November | 0.700569E+11 | 0.00 | 0.00 | 532813.23 | 0.00 | 0.154516E+11 | 0.130568E+09 | 0.00 | 1.17 |
December | 0.552162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316692E+11 | 0.00 | 0.00 | 0.98 |
Annual Sum or Average | 0.738010E+12 | 0.217227E+10 | 0.00 | 0.850513E+09 | 32758727.01 | 0.126386E+12 | 0.140029E+12 | 0.00 | 1.63 |
Minimum of Months | 0.396731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 |
Maximum of Months | 0.810235E+11 | 0.153488E+10 | 0.00 | 0.184570E+09 | 20319705.43 | 0.379884E+11 | 0.273555E+11 | 0.00 | 2.31 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.205044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470975E+10 | 0.00 | 0.00 | 0.54 |
February | 0.313984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349184E+10 | 0.00 | 0.00 | 0.66 |
March | 0.601997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236106E+10 | 0.00 | 0.00 | 0.81 |
April | 0.648718E+10 | 42068.21 | 0.00 | 795693.53 | 8035.42 | 0.112366E+10 | 0.269012E+09 | 0.00 | 0.90 |
May | 0.639445E+10 | 0.00 | 0.00 | 4355528.78 | 0.00 | 0.616772E+09 | 0.190321E+10 | 0.00 | 1.18 |
June | 0.603685E+10 | 0.00 | 0.00 | 14021279.75 | 1076333.47 | 0.122485E+09 | 0.193147E+10 | 0.00 | 1.34 |
July | 0.391932E+10 | 7615476.61 | 0.00 | 10232729.43 | 42137.23 | 1190142.59 | 0.237368E+10 | 0.00 | 1.27 |
August | 0.346506E+10 | 49794265.03 | 0.00 | 5932848.98 | 561896.43 | 5349860.03 | 0.163809E+10 | 0.00 | 1.15 |
September | 0.549452E+10 | 0.00 | 0.00 | 2148468.93 | 0.00 | 0.427428E+09 | 0.114589E+10 | 0.00 | 1.20 |
October | 0.605113E+10 | 0.00 | 0.00 | 30842.24 | 0.00 | 0.160287E+10 | 30164291.93 | 0.00 | 0.93 |
November | 0.362640E+10 | 0.00 | 1493.93 | 0.00 | 8701.83 | 0.320505E+10 | 0.00 | 3965.10 | 0.69 |
December | 0.210759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451077E+10 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.547928E+11 | 57451809.85 | 1493.93 | 37517391.65 | 1697104.38 | 0.221782E+11 | 0.929150E+10 | 3965.10 | 0.94 |
Minimum of Months | 0.205044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1190142.59 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.648718E+10 | 49794265.03 | 1493.93 | 14021279.75 | 1076333.47 | 0.470975E+10 | 0.237368E+10 | 3965.10 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.224563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394135E+10 | 0.00 | 0.00 | 0.76 |
February | 0.338304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268867E+10 | 0.00 | 0.00 | 0.94 |
March | 0.592315E+10 | 0.00 | 0.00 | 563390.81 | 0.00 | 0.169355E+10 | 69346647.57 | 0.00 | 1.16 |
April | 0.487452E+10 | 36022.93 | 0.00 | 7928539.87 | 7364.37 | 0.761214E+09 | 0.188672E+10 | 0.00 | 1.35 |
May | 0.486331E+10 | 0.00 | 0.00 | 9869130.10 | 0.00 | 0.495186E+09 | 0.333613E+10 | 0.00 | 1.81 |
June | 0.402412E+10 | 0.00 | 0.00 | 36021606.55 | 986447.49 | 99203128.18 | 0.437362E+10 | 0.00 | 2.17 |
July | 0.298355E+10 | 6155496.28 | 0.00 | 27875464.08 | 35043.72 | 1991797.94 | 0.351387E+10 | 0.00 | 2.03 |
August | 0.270975E+10 | 42697326.00 | 0.00 | 11618735.15 | 514971.74 | 11362189.76 | 0.263781E+10 | 0.00 | 1.93 |
September | 0.426003E+10 | 0.00 | 0.00 | 6975388.77 | 0.00 | 0.321874E+09 | 0.241872E+10 | 0.00 | 1.87 |
October | 0.549132E+10 | 0.00 | 0.00 | 3024917.33 | 0.00 | 0.122205E+10 | 0.376194E+09 | 0.00 | 1.34 |
November | 0.350997E+10 | 0.00 | 1482.60 | 0.00 | 7975.13 | 0.274636E+10 | 0.00 | 3520.55 | 0.99 |
December | 0.228642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377173E+10 | 0.00 | 0.00 | 0.77 |
Annual Sum or Average | 0.465548E+11 | 48888845.21 | 1482.60 | 0.103877E+09 | 1551802.46 | 0.177545E+11 | 0.186124E+11 | 3520.55 | 1.43 |
Minimum of Months | 0.224563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1991797.94 | 0.00 | 0.00 | 0.76 |
Maximum of Months | 0.592315E+10 | 42697326.00 | 1482.60 | 36021606.55 | 986447.49 | 0.394135E+10 | 0.437362E+10 | 3520.55 | 2.17 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.438125E+10 | 0.00 | 0.00 | 1458913.06 | 0.00 | 0.491332E+10 | 0.406582E+09 | 0.00 | 0.77 |
February | 0.496725E+10 | 0.00 | 0.00 | 22017652.61 | 0.00 | 0.328526E+10 | 0.191089E+10 | 0.00 | 1.03 |
March | 0.697460E+10 | 0.00 | 0.00 | 51645311.89 | 0.00 | 0.227676E+10 | 0.441586E+10 | 0.00 | 1.34 |
April | 0.653132E+10 | 125303.86 | 0.00 | 23227806.29 | 0.00 | 0.134872E+10 | 0.491144E+10 | 0.00 | 1.50 |
May | 0.744932E+10 | 0.00 | 0.00 | 16333299.61 | 0.00 | 0.928811E+09 | 0.553563E+10 | 0.00 | 1.87 |
June | 0.799900E+10 | 0.00 | 0.00 | 27591404.91 | 1532050.72 | 0.280604E+09 | 0.384295E+10 | 0.00 | 2.03 |
July | 0.533151E+10 | 13446445.93 | 0.00 | 20193179.11 | 54426.37 | 3796824.63 | 0.437393E+10 | 0.00 | 1.97 |
August | 0.469445E+10 | 98633596.93 | 0.00 | 14106668.24 | 799802.15 | 7803169.27 | 0.318956E+10 | 0.00 | 1.83 |
September | 0.614525E+10 | 0.00 | 0.00 | 20131974.85 | 0.00 | 0.434386E+09 | 0.608137E+10 | 0.00 | 2.28 |
October | 0.645332E+10 | 0.00 | 0.00 | 42532391.25 | 0.00 | 0.178348E+10 | 0.488818E+10 | 0.00 | 1.64 |
November | 0.565479E+10 | 0.00 | 2581.02 | 10749814.69 | 12386.17 | 0.353183E+10 | 0.795183E+09 | 5189.36 | 1.03 |
December | 0.409258E+10 | 0.00 | 0.00 | 5422562.77 | 0.00 | 0.459938E+10 | 0.900982E+09 | 0.00 | 0.79 |
Annual Sum or Average | 0.706746E+11 | 0.112205E+09 | 2581.02 | 0.255411E+09 | 2398665.41 | 0.233941E+11 | 0.412525E+11 | 5189.36 | 1.51 |
Minimum of Months | 0.409258E+10 | 0.00 | 0.00 | 1458913.06 | 0.00 | 3796824.63 | 0.406582E+09 | 0.00 | 0.77 |
Maximum of Months | 0.799900E+10 | 98633596.93 | 2581.02 | 51645311.89 | 1532050.72 | 0.491332E+10 | 0.608137E+10 | 5189.36 | 2.28 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.309515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411402E+10 | 0.00 | 0.00 | 0.89 |
February | 0.426379E+10 | 0.00 | 0.00 | 523302.35 | 0.00 | 0.277214E+10 | 46754744.28 | 0.00 | 1.10 |
March | 0.685975E+10 | 0.00 | 0.00 | 6215156.49 | 0.00 | 0.165333E+10 | 0.589660E+09 | 0.00 | 1.38 |
April | 0.619561E+10 | 79942.52 | 0.00 | 8465830.96 | 0.00 | 0.887417E+09 | 0.176681E+10 | 0.00 | 1.59 |
May | 0.652089E+10 | 0.00 | 0.00 | 10627596.20 | 0.00 | 0.503902E+09 | 0.323528E+10 | 0.00 | 2.17 |
June | 0.654369E+10 | 0.00 | 0.00 | 18863195.76 | 1150178.98 | 0.120354E+09 | 0.230448E+10 | 0.00 | 2.36 |
July | 0.412016E+10 | 14871990.10 | 0.00 | 17719423.08 | 23524.78 | 767202.53 | 0.322271E+10 | 0.00 | 2.38 |
August | 0.375242E+10 | 72832005.60 | 0.00 | 10098725.89 | 0.00 | 4971468.59 | 0.198765E+10 | 0.00 | 2.04 |
September | 0.573558E+10 | 0.00 | 0.00 | 6272668.30 | 0.00 | 0.212369E+09 | 0.217091E+10 | 0.00 | 2.20 |
October | 0.639522E+10 | 0.00 | 0.00 | 6482195.28 | 0.00 | 0.126071E+10 | 0.701486E+09 | 0.00 | 1.59 |
November | 0.470643E+10 | 0.00 | 0.00 | 44104.12 | 15132.42 | 0.257119E+10 | 12379347.69 | 0.00 | 1.15 |
December | 0.322370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383448E+10 | 0.00 | 0.00 | 0.90 |
Annual Sum or Average | 0.614124E+11 | 87783938.22 | 0.00 | 85312198.42 | 1188836.18 | 0.179356E+11 | 0.160381E+11 | 0.00 | 1.65 |
Minimum of Months | 0.309515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 767202.53 | 0.00 | 0.00 | 0.89 |
Maximum of Months | 0.685975E+10 | 72832005.60 | 0.00 | 18863195.76 | 1150178.98 | 0.411402E+10 | 0.323528E+10 | 0.00 | 2.38 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 5705585.67 | 0.00 | 0.00 | 0.627625E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 49503349.99 | 0.00 | 0.00 | 0.473477E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.107566E+09 | 0.00 | 0.00 | 0.452507E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 60255469.20 | 0.00 | 0.00 | 0.381010E+09 | 0.00 | 0.29 |
May | 0.00 | 2062.56 | 0.00 | 9255144.65 | 0.00 | 0.00 | 0.388007E+09 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 43989867.98 | 0.00 | 0.00 | 0.275920E+09 | 0.00 | 0.30 |
July | 0.00 | 3521466.70 | 0.00 | 51309014.38 | 0.00 | 0.00 | 0.144529E+09 | 0.00 | 0.28 |
August | 0.00 | 14374071.59 | 0.00 | 26632362.87 | 0.00 | 0.00 | 0.122477E+09 | 0.00 | 0.31 |
September | 0.00 | 36715.83 | 0.00 | 7962907.07 | 0.00 | 0.00 | 0.272308E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 47209013.19 | 0.00 | 0.00 | 0.396342E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 90900011.20 | 0.00 | 0.00 | 0.425643E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 65390298.76 | 0.00 | 0.00 | 0.530507E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 17934316.68 | 0.00 | 0.565679E+09 | 0.00 | 0.00 | 0.449035E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 5705585.67 | 0.00 | 0.00 | 0.122477E+09 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 14374071.59 | 0.00 | 0.107566E+09 | 0.00 | 0.00 | 0.627625E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.364837E+09 | 0.00 | 0.00 | 32813473.84 | 0.00 | 0.00 | 0.594304E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 0.424961E+09 | 0.00 | 0.00 | 0.480550E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.986092E+09 | 0.00 | 0.00 | 0.461394E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.564406E+09 | 0.00 | 0.00 | 0.385011E+10 | 0.00 | 0.29 |
May | 0.00 | 13015.27 | 0.00 | 78323611.73 | 0.00 | 0.00 | 0.389602E+10 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 0.406895E+09 | 0.00 | 0.00 | 0.279321E+10 | 0.00 | 0.30 |
July | 0.00 | 34545363.49 | 0.00 | 0.478501E+09 | 0.00 | 0.00 | 0.148243E+10 | 0.00 | 0.28 |
August | 0.00 | 0.141003E+09 | 0.00 | 0.250769E+09 | 0.00 | 0.00 | 0.125236E+10 | 0.00 | 0.31 |
September | 0.00 | 294282.89 | 0.00 | 65812082.49 | 0.00 | 0.00 | 0.274795E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 0.420681E+09 | 0.00 | 0.00 | 0.401496E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.815687E+09 | 0.00 | 0.00 | 0.434974E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.593036E+09 | 0.00 | 0.00 | 0.536785E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.364837E+09 | 0.175855E+09 | 0.00 | 0.511798E+10 | 0.00 | 0.00 | 0.451171E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 32813473.84 | 0.00 | 0.00 | 0.125236E+10 | 0.00 | 0.28 |
Maximum of Months | 0.364837E+09 | 0.141003E+09 | 0.00 | 0.986092E+09 | 0.00 | 0.00 | 0.594304E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.226323E+09 | 0.00 | 0.00 | 1782179.28 | 0.00 | 0.00 | 0.404858E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 35288889.75 | 0.00 | 0.00 | 0.487820E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 91259736.87 | 0.00 | 0.00 | 0.468837E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 54261803.73 | 0.00 | 0.00 | 0.387981E+09 | 0.00 | 0.29 |
May | 9566177.25 | 1300.42 | 0.00 | 6897691.49 | 0.00 | 0.00 | 0.381236E+09 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 39582773.54 | 0.00 | 0.00 | 0.280553E+09 | 0.00 | 0.30 |
July | 0.00 | 3485105.64 | 0.00 | 46597324.54 | 0.00 | 0.00 | 0.149608E+09 | 0.00 | 0.28 |
August | 0.00 | 14058779.55 | 0.00 | 24589488.33 | 0.00 | 0.00 | 0.127330E+09 | 0.00 | 0.31 |
September | 3921561.57 | 28233.16 | 0.00 | 5319000.45 | 0.00 | 0.00 | 0.272947E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 36973264.21 | 0.00 | 0.00 | 0.406805E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 73278966.95 | 0.00 | 0.00 | 0.443439E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 54329954.13 | 0.00 | 0.00 | 0.542162E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.239811E+09 | 17573418.77 | 0.00 | 0.470161E+09 | 0.00 | 0.00 | 0.435358E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1782179.28 | 0.00 | 0.00 | 0.127330E+09 | 0.00 | 0.28 |
Maximum of Months | 0.226323E+09 | 14058779.55 | 0.00 | 91259736.87 | 0.00 | 0.00 | 0.542162E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.779877E+09 | 0.00 | 0.00 | 0.332992E+12 | 0.00 | 7.21 |
February | 0.314486E+10 | 0.00 | 0.00 | 0.297953E+10 | 0.00 | 0.00 | 0.442626E+12 | 0.00 | 13.19 |
March | 0.549331E+09 | 0.00 | 0.00 | 0.670395E+10 | 0.00 | 0.00 | 0.714928E+12 | 0.00 | 21.74 |
April | 393222.32 | 3634129.11 | 0.00 | 0.483586E+10 | 0.00 | 0.00 | 0.830986E+12 | 0.00 | 36.58 |
May | 0.00 | 0.00 | 0.00 | 0.884478E+09 | 0.00 | 0.00 | 0.289400E+12 | 0.00 | 12.45 |
June | 0.818254E+09 | 0.00 | 0.00 | 0.309308E+10 | 0.00 | 0.00 | 0.390853E+12 | 0.00 | 23.74 |
July | 0.190111E+09 | 18002597.10 | 0.00 | 0.555932E+10 | 0.00 | 0.00 | 0.549478E+12 | 0.00 | 38.14 |
August | 0.00 | 0.147146E+09 | 0.00 | 0.338315E+10 | 0.00 | 0.00 | 0.655100E+12 | 0.00 | 48.30 |
September | 0.00 | 0.00 | 0.00 | 0.804588E+09 | 0.00 | 0.00 | 0.256606E+12 | 0.00 | 14.49 |
October | 0.153623E+10 | 0.00 | 0.00 | 0.314993E+10 | 0.00 | 0.00 | 0.457014E+12 | 0.00 | 18.56 |
November | 7561753.88 | 0.00 | 0.00 | 0.655146E+10 | 0.00 | 0.00 | 0.659282E+12 | 0.00 | 21.69 |
December | 0.00 | 0.00 | 0.00 | 0.543404E+10 | 0.00 | 0.00 | 0.940562E+12 | 0.00 | 26.54 |
Annual Sum or Average | 0.624674E+10 | 0.168782E+09 | 0.00 | 0.441593E+11 | 0.00 | 0.00 | 0.651983E+13 | 0.00 | 23.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.779877E+09 | 0.00 | 0.00 | 0.256606E+12 | 0.00 | 7.21 |
Maximum of Months | 0.314486E+10 | 0.147146E+09 | 0.00 | 0.670395E+10 | 0.00 | 0.00 | 0.940562E+12 | 0.00 | 48.30 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:51
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.129570E+12 | 0.221487E+11 | 0.00 | 0.228342E+13 | 0.219448E+12 |
February | 0.239917E+12 | 0.199960E+11 | 0.00 | 0.243942E+13 | 0.449602E+12 |
March | 0.418409E+12 | 0.185328E+11 | 0.00 | 0.314030E+13 | 0.713449E+12 |
April | 0.647153E+12 | 0.177744E+11 | 0.00 | 0.333450E+13 | 0.935957E+12 |
May | 0.848795E+12 | 0.139920E+11 | 0.00 | 0.288433E+13 | 0.463401E+12 |
June | 0.853845E+12 | 0.115260E+11 | 0.00 | 0.277778E+13 | 0.978043E+12 |
July | 0.902312E+12 | 0.100330E+11 | 0.00 | 0.295017E+13 | 0.162237E+13 |
August | 0.702157E+12 | 0.780414E+10 | 0.00 | 0.265516E+13 | 0.213919E+13 |
September | 0.494050E+12 | 0.659001E+10 | 0.00 | 0.283907E+13 | 0.642314E+12 |
October | 0.314493E+12 | 0.148438E+11 | 0.00 | 0.309301E+13 | 0.507903E+12 |
November | 0.140690E+12 | 0.174708E+11 | 0.00 | 0.304248E+13 | 0.671054E+12 |
December | 0.100380E+12 | 0.190022E+11 | 0.00 | 0.314398E+13 | 0.804368E+12 |
Annual Sum or Average | 0.579177E+13 | 0.179714E+12 | 0.00 | 0.345836E+14 | 0.101471E+14 |
Minimum of Months | 0.100380E+12 | 0.659001E+10 | 0.00 | 0.228342E+13 | 0.219448E+12 |
Maximum of Months | 0.902312E+12 | 0.221487E+11 | 0.00 | 0.333450E+13 | 0.213919E+13 |