Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440

Simulation Timestamp: 2024-07-03 12:26:25


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 38690.25 835.28 835.28
Net Site Energy 38690.25 835.28 835.28
Total Source Energy 107589.58 2322.73 2322.73
Net Source Energy 107589.58 2322.73 2322.73


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 7173.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1965.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 5610.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1006.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2623.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2912.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1008.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 176.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6305.85
Humidification 1053.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 391.74
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 484.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 31516.73 7173.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8977.76
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 7173.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 1965.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 5610.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 1006.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5334.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 56.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 2505.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 61.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2912.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 1008.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 176.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6305.85
Humidification General 1053.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 391.74
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 484.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 7173.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 1965.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 5610.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 1006.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 2623.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2912.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 1008.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 176.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6305.85
Humidification Unassigned 1053.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 391.74
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 484.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 142.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 164.09 154.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.19
Other 373.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 680.41 154.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.19


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 142.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 164.09 154.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.19
Other 373.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 680.41 154.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.19


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 31516.729 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 31516.729 100.00
     
Total On-Site and Utility Electric Sources 31516.729 100.00
Total Electricity End Uses 31516.729 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 8977.76 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 8977.76 100.00
Total Water End Uses 8977.76 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 118.33
Time Setpoint Not Met During Occupied Cooling 173.17
Time Not Comfortable Based on Simple ASHRAE 55-2004 5281.83


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| Environment |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS SZVAV FAN | AIRLOOP DATACENTER BASEMENT SYS11 FAN | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26
RunPeriod RUNPERIOD 1
Weather File Rochester International Arpt MN USA TMY3 WMO#=726440
Latitude [deg] 43.90
Longitude [deg] -92.5
Elevation [m] 398.00
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 11.6510 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 11.6510 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 11.6510 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 11.6510 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 11.6510 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 11.6510 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 11.6510 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 11.6510 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 115.90 115.90 11.6510 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 11.6510 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 115.90 115.90 11.6510 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 11.6510 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 11.6510 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 11.6510 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 11.6510 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 11.6510 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 22.3674 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 22.3674 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 22.3674 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 11.6510 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 11.7515 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 11.7515 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 11.6510 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 11.6510 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 11.6510 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 11.6510 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 11.6510 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 11.6510 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 11.6510 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 11.6510 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 11.6510 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 11.6510 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 11.6510 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 11.6510 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 11.6510 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 11.6510 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 11.6510 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 11.6510 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 22.3674 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 22.3674 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 22.3674 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 11.6510 18.58 484.4232  
Total 46320.38             11.7515 9.29 17.8789  
Conditioned Total 46320.38             11.7515 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 3.6100 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 04-AUG-15:30 30-JAN-07:30 - - - - - - - - - - 07-SEP-14:20
Heating 0.00 3142160.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 515044.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 489900.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 778371.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 235096.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 305773.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 102278.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 58522.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 35451.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 2520439.57 3142160.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 3142160.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 515044.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 489900.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 3543.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 229608.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 1944.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 305773.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 102278.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 58522.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 35451.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 7776.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 6224.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 17769.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 3185.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 46480.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 8307.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 9222.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 3193.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 559.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 3335.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 1535.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 99813.48 7776.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 167.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 134.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 383.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 68.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 179.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 199.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 68.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 12.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 72.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 33.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2154.85 167.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 167.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 134.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 383.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 68.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 179.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 199.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 68.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 12.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 72.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 33.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2154.85 167.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

AirTerminal:SingleDuct:VAV:NoReheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s]
BASEMENT PSZ-VAV DIFFUSER 7.24 0.292441 0.300000 2.17
DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER 32.85 0.018177 0.500000 16.43
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 7.72 0.246427 0.300000 2.32 0.657138 0.500000 0.001546 0.000314 2.32 12.89 0.008000
CORE_MID VAV BOX COMPONENT 73.32 0.259431 0.300000 21.99 0.691816 0.500000 0.001469 0.006670 33.45 12.89 0.008000
CORE_TOP VAV BOX COMPONENT 9.32 0.204083 0.300000 2.80 0.544221 0.500000 0.001867 0.001847 9.32 12.89 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 1.82 0.131035 0.300000 0.546772 0.349426 0.500000 0.002908 0.000361 1.82 12.89 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.74 0.088265 0.300000 0.523101 0.300000 0.500000 0.004317 0.000238 1.20 12.89 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 2.03 0.117465 0.300000 0.609951 0.313240 0.500000 0.003244 0.000376 1.90 12.89 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 2.13 0.072411 0.300000 0.637629 0.300000 0.500000 0.005262 0.000209 1.06 12.89 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 25.42 0.093963 0.300000 7.62 0.300000 0.500000 0.004055 0.005026 25.42 12.89 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 18.41       0.300000 0.500000 0.004556 0.003262 16.50 12.89 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 24.84 0.096156 0.300000 7.45 0.300000 0.500000 0.003962 0.004912 24.84 12.89 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 19.83 0.077607 0.300000 5.95 0.300000 0.500000 0.004909 0.003268 16.53 12.89 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 3.29 0.072585 0.300000 0.987072 0.300000 0.500000 0.005249 0.000650 3.29 12.89 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 2.13 0.072188 0.300000 0.639603 0.300000 0.500000 0.005278 0.000421 2.13 12.89 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 3.23 0.073932 0.300000 0.969098 0.300000 0.500000 0.005153 0.000639 3.23 12.89 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 2.16 0.071255 0.300000 0.647980 0.300000 0.500000 0.005347 0.000427 2.16 12.89 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K] User-Specified Rated Capacity [W]
CORE_BOTTOM VAV BOX REHEAT COIL 35943.51 0.000314 772.99  
CORE_MID VAV BOX REHEAT COIL 762425.37 0.006670 17844.44  
CORE_TOP VAV BOX REHEAT COIL 211115.18 0.001847 4932.69  
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 41224.38 0.000361 962.81  
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 27239.17 0.000238 636.17  
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 42991.00 0.000376 1004.06  
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 23917.28 0.000209 558.63  
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 574504.89 0.005026 13415.34  
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 372878.55 0.003262 8707.10  
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 561430.16 0.004912 13110.13  
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 373526.03 0.003268 8722.19  
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 74351.27 0.000650 1736.05  
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 48177.52 0.000421 1124.91  
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 72998.39 0.000639 1704.47  
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 48807.77 0.000427 1139.62  
VAV_BOT WITH REHEAT HEATING COIL 80348.33 0.000703 1306.68  
VAV_MID WITH REHEAT HEATING COIL 817832.28 0.007155 13190.66  
VAV_TOP WITH REHEAT HEATING COIL 69215.72 0.000606 1184.36  
CAV_BAS HEATING COIL 116808.39 0.000875 2622.25 100000.00
AIRLOOP DATACENTER BASEMENT HEATING COIL 562104.91 0.000875 2622.25 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
DATACENTER_BOT_ZN_6 DIRECT AIR 0.790752
DATACENTER_MID_ZN_6 DIRECT AIR 7.61
DATACENTER_TOP_ZN_6 DIRECT AIR 0.783349
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 7.72 4.63 15.44 7.06 12.60 12.60 0.300000 0.560338 12.60
VAV_MID WITH REHEAT 80.90 48.54 161.81 116.73 118.36 118.36 0.300000 0.986216 118.36
VAV_TOP WITH REHEAT 10.07 6.04 20.13 20.13 14.60 20.13 0.300000 1.00 20.13
CAV_BAS 2.17 2.17 7.24 2.17 7.24 7.24 1.00 0.300000 7.24
AIRLOOP DATACENTER BASEMENT 16.43 16.43 32.85 16.43 32.85 32.85 1.00 0.499997 32.85
AIRLOOP DATACENTER BOT 0.790752 0.790752 0.790752 0.790752 0.790752 0.790752 1.00 1.00 0.790752
AIRLOOP DATACENTER MID 7.61 7.61 7.61 7.61 7.61 7.61 1.00 1.00 7.61
AIRLOOP DATACENTER TOP 0.783349 0.783349 0.783349 0.783349 0.783349 0.783349 1.00 1.00 0.783349
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 12.60  
VAV_MID WITH REHEAT_OA_CONTROLLER 118.36  
VAV_TOP WITH REHEAT_OA_CONTROLLER 20.13  
CAV_BAS_OA_CONTROLLER 7.24 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 32.85 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.790752 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 7.61 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.783349 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 25.16 6.67 11.03 0.009921 0.008500 261222.41 0.009330 12.60
VAV_MID WITH REHEAT COOLING COIL 25.26 6.67 11.03 0.010115 0.008500 2533061.11 0.090475 118.36
VAV_TOP WITH REHEAT COOLING COIL 25.00 6.67 11.05 0.009833 0.008500 407681.49 0.014561 20.13
CAV_BAS COOLING COIL 23.94 6.67 11.02 0.009983 0.008500 137571.78 0.004914 7.24
AIRLOOP DATACENTER BASEMENT COOLING COIL 27.04 6.67 15.00 0.008603 0.008500 457412.79 0.016338 32.85
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 12.60
VAV_MID WITH REHEAT FAN 118.36
VAV_TOP WITH REHEAT FAN 20.13
CAV_BAS SZVAV FAN 7.24
AIRLOOP DATACENTER BASEMENT SYS11 FAN 32.85
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.009330 0.000051
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000703  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.090475 0.000005
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.007155  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.014561 0.000033
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000606  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitarySystem

Design Size Supply Air Flow Rate [m3/s] Design Size Heating Supply Air Flow Rate [m3/s] Design Size Cooling Supply Air Flow Rate [m3/s] Design Size No Load Supply Air Flow Rate [m3/s] Design Size Nominal Cooling Capacity [W] Design Size Nominal Heating Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone Design Size Minimum Supply Air Temperature [C] User-Specified Minimum Supply Air Temperature [C] User-Specified Maximum Supply Air Temperature [C] User-Specified Nominal Cooling Capacity [W] Design Size Maximum Supply Air Temperature [C]
CAV_BAS_UNITARY_PACKAGE_DX 7.24 7.24 7.24 2.17 137571.78 100000.00 1.00 5.33 12.89 32.11    
AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX 32.85 32.85 32.85 16.43 457412.79 100000.00 1.00   15.89 29.11    
AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX 0.790752 0.790752 0.790752 0.790752   27039.51 1.00       13089.75 29.11
AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX 7.61 7.61 7.61 7.61   260351.50 1.00       125948.91 29.11
AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX 0.783349 0.783349 0.783349 0.783349   26790.80 1.00       12967.21 29.11
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000296 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:SystemModel

Design Size Design Maximum Air Flow Rate [m3/s] Design Electric Power Consumption [W]
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN 0.790752 1359.81
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN 7.61 13084.00
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN 0.783349 1347.08
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:MultiSpeed

User-Specified Speed 2 Rated Air Flow Rate [m3/s] Design Size Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] User-Specified Speed 2 Rated Sensible Heat Ratio User-Specified Speed 1 Rated Sensible Heat Ratio
AIRLOOP DATACENTER BOT COOLING COIL 0.790750 0.395376 0.527167 13089.75 6544.88 0.800660 0.800660
AIRLOOP DATACENTER MID COOLING COIL 7.61 3.80 5.07 125948.91 62974.46 0.800660 0.800660
AIRLOOP DATACENTER TOP COOLING COIL 0.783350 0.391674 0.522233 12967.21 6483.60 0.800660 0.800660
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BOT HEATING COIL 27039.51
AIRLOOP DATACENTER MID HEATING COIL 260351.50
AIRLOOP DATACENTER TOP HEATING COIL 26790.80
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.135618 27945.92  
HEATSYS1 PUMP 0.038834 11695.00 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.135618 16.27
HEATSYS1 0.038834 4.66
COOLSYS1_SUPPLY 0.135618 16.27
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.135618 0.135618 569257.81 6.67
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 4438926.80 4438926.80 0.038834
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 CHILLER1 PUMP 0.067809 12898.32
COOLSYS1 CHILLER2 PUMP 0.067809 12898.32
SWHSYS1 PUMP 0.000440 56.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.135618 0.068385 1914597.90 1914622.11 0.095954
COOLSYS1 CHILLER2 0.135618 0.068385 1914597.90 1914622.11 0.095954
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.191908 23.03
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.191908 66918.62
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 80.74 2292209.93 16.15 286526.24
TOWERWATERSYS COOLTOWER 2 80.74 2292209.93 16.15 286526.24
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 7.40 -0.00 -7.60 -12.60 -7.70 0.30 7.00 14.20 19.20 20.90 20.00 15.40


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Rochester International Arpt MN USA TMY3 WMO#=726440 43.90 -92.50 -6.00 398.00 96634 1.1486


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 6.38 33.50 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 76.91 115.90 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 76.91 115.90 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 11.651 4.842 0.000 0.000 0.000 0.000 16.493 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 11.651 8.070 0.000 0.000 0.000 0.000 19.721 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 22.367 215.299 0.000 0.000 0.000 0.000 237.667 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 22.367 215.299 0.000 0.000 0.000 0.000 237.667 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 22.367 215.299 0.000 0.000 0.000 0.000 237.667 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 11.651 484.423 0.000 0.000 0.000 0.000 496.074 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 32383.100 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 32383.100
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 29082.299 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 29082.299
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 29082.299 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 29082.299
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 29082.299 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 29082.299
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 3651.573 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3651.573
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 2353.212 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2353.212
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 3651.653 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3651.653
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 2353.212 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2353.212
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 3651.573 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3651.573
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 2353.212 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2353.212
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 3651.653 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3651.653
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 2353.212 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2353.212
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 3651.573 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3651.573
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 2353.212 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2353.212
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 3651.653 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3651.653
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 2353.212 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2353.212
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 9130.649 11.651 216.462 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 9130.649
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 809.760 22.367 415.559 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 809.760
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 809.760 22.367 415.559 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 809.760
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 809.760 22.367 415.559 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 809.760


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 9.815 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.3762 0.900 0.900 0.700 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 4 7 0.167 0.5136 0.900 0.900 0.700 0.700 Smooth
10 NONRES_EXT_WALL_MID 21 4 7 0.167 0.5136 0.900 0.900 0.700 0.700 Smooth
11 NONRES_EXT_WALL_TOP 22 4 7 0.167 0.5136 0.900 0.900 0.700 0.700 Smooth
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.1019
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 2.599
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
16 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
17 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.713
18 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
19 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
20 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
21 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 1.713
22 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
23 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
24 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
25 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 1.713
26 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
27 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
28 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
29 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
30 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
31 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
32 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
33 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
34 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
35 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 0.9868
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 0.9868
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 9.8148919 9.8148919 9.8148919  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.61039648E-06 0.16815647E-08 -0.37447326E-05 0.10149002E-16
47 2 0.76989337 0.22941655E-02 1.0458372 -0.71793422E-06
48 1 -21.843031 0.15409339 -6.3407615 0.20050303
49 0 21.373924 0.14439780 5.5957134  
50 7 -0.33207909E-12 0.79542070E-15 -0.11586622E-12 0.10783435E-15
51 6 0.31762832E-07 0.14865645E-09 0.72503568E-08 -0.15188138E-12
52 5 -0.20568023E-03 0.12486053E-05 -0.10556626E-03 0.71569697E-08
53 4 0.31018727 0.59758545E-03 0.10618022 -0.36135240E-04
54 3 -7.6231853 0.18239075E-01 -2.4448349 0.30759039E-01
55 2 42.047589 0.63983780E-01 15.698525 -0.34644559
56 1 -81.446794 0.28535822E-01 -29.529986 1.0978209
57 0 46.824333 0.56745654E-03 16.282146  
58 7 -0.33207909E-12 0.79542070E-15 -0.11586622E-12 0.10783435E-15
59 6 0.31762832E-07 0.14865645E-09 0.72503568E-08 -0.15188138E-12
60 5 -0.20568023E-03 0.12486053E-05 -0.10556626E-03 0.71569697E-08
61 4 0.31018727 0.59758545E-03 0.10618022 -0.36135240E-04
62 3 -7.6231853 0.18239075E-01 -2.4448349 0.30759039E-01
63 2 42.047589 0.63983780E-01 15.698525 -0.34644559
64 1 -81.446794 0.28535822E-01 -29.529986 1.0978209
65 0 46.824333 0.56745654E-03 16.282146  
66 7 -0.33207909E-12 0.79542070E-15 -0.11586622E-12 0.10783435E-15
67 6 0.31762832E-07 0.14865645E-09 0.72503568E-08 -0.15188138E-12
68 5 -0.20568023E-03 0.12486053E-05 -0.10556626E-03 0.71569697E-08
69 4 0.31018727 0.59758545E-03 0.10618022 -0.36135240E-04
70 3 -7.6231853 0.18239075E-01 -2.4448349 0.30759039E-01
71 2 42.047589 0.63983780E-01 15.698525 -0.34644559
72 1 -81.446794 0.28535822E-01 -29.529986 1.0978209
73 0 46.824333 0.56745654E-03 16.282146  
74 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
75 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
76 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
77 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
78 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
79 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
80 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
81 0 1.0055995 0.48413807E-04 60.838472  
82 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
83 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
84 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
85 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
86 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
87 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
88 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
89 0 1.0055995 0.48413807E-04 60.838472  
90 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
91 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
92 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
93 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
94 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
95 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
96 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
97 0 1.0055995 0.48413807E-04 60.838472  
98 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
99 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
100 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
101 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
102 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
103 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
104 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
105 0 1.0055995 0.48413807E-04 60.838472  
106 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
107 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
108 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
109 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
110 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
111 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
112 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
113 0 1.0055995 0.48413807E-04 60.838472  
114 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
115 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
116 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
117 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
118 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
119 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
120 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
121 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.57_SHGC_EAST_0.39 35 1 VerySmooth 3.241 3.241 1.000 0.391    
2 WINDOW_U_0.57_SHGC_SOUTH_0.39 36 1 VerySmooth 3.241 3.241 1.000 0.391    
3 WINDOW_U_0.57_SHGC_WEST_0.39 37 1 VerySmooth 3.241 3.241 1.000 0.391    
4 WINDOW_U_0.57_SHGC_NORTH_0.39 38 1 VerySmooth 3.241 3.241 1.000 0.391    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   2.00000E-003 0.30403 0.46623 0.46623 0.42900 0.13485 0.17261 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   2.00000E-003 0.30403 0.46623 0.46623 0.42900 0.13485 0.17261 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   2.00000E-003 0.30403 0.46623 0.46623 0.42900 0.13485 0.17261 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   2.00000E-003 0.30403 0.46623 0.46623 0.42900 0.13485 0.17261 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 13.342 0.7435


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2500
2 Zone BASEMENT 1.2500
3 Zone CORE_BOTTOM 1.2500
4 Zone CORE_MID 1.2500
5 Zone CORE_TOP 1.2500
6 Zone PERIMETER_BOT_ZN_3 1.2500
7 Zone PERIMETER_BOT_ZN_2 1.2500
8 Zone PERIMETER_BOT_ZN_1 1.2500
9 Zone PERIMETER_BOT_ZN_4 1.2500
10 Zone PERIMETER_MID_ZN_3 1.2500
11 Zone PERIMETER_MID_ZN_2 1.2500
12 Zone PERIMETER_MID_ZN_1 1.2500
13 Zone PERIMETER_MID_ZN_4 1.2500
14 Zone PERIMETER_TOP_ZN_3 1.2500
15 Zone PERIMETER_TOP_ZN_2 1.2500
16 Zone PERIMETER_TOP_ZN_1 1.2500
17 Zone PERIMETER_TOP_ZN_4 1.2500
18 Zone DATACENTER_BOT_ZN_6 1.2500
19 Zone DATACENTER_MID_ZN_6 1.2500
20 Zone DATACENTER_TOP_ZN_6 1.2500
21 Zone DATACENTER_BASEMENT_ZN_6 1.2500


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.1500
2 Zone BASEMENT 1.1500
3 Zone CORE_BOTTOM 1.1500
4 Zone CORE_MID 1.1500
5 Zone CORE_TOP 1.1500
6 Zone PERIMETER_BOT_ZN_3 1.1500
7 Zone PERIMETER_BOT_ZN_2 1.1500
8 Zone PERIMETER_BOT_ZN_1 1.1500
9 Zone PERIMETER_BOT_ZN_4 1.1500
10 Zone PERIMETER_MID_ZN_3 1.1500
11 Zone PERIMETER_MID_ZN_2 1.1500
12 Zone PERIMETER_MID_ZN_1 1.1500
13 Zone PERIMETER_MID_ZN_4 1.1500
14 Zone PERIMETER_TOP_ZN_3 1.1500
15 Zone PERIMETER_TOP_ZN_2 1.1500
16 Zone PERIMETER_TOP_ZN_1 1.1500
17 Zone PERIMETER_TOP_ZN_4 1.1500
18 Zone DATACENTER_BOT_ZN_6 1.1500
19 Zone DATACENTER_MID_ZN_6 1.1500
20 Zone DATACENTER_TOP_ZN_6 1.1500
21 Zone DATACENTER_BASEMENT_ZN_6 1.1500


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 82743.46439 95154.98405 6.29759 7.24223 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 23.35600 1.53506E-002 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -26.20000 3.61342E-004 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 88186.72540 101414.73421 6.71173 7.71849 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 23.35600 1.53506E-002 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 11157.21920 13946.52401 0.83332 1.07782 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -26.20000 3.61342E-004 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 837830.45162 963505.01936 63.75306 73.31602 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 23.35600 1.53506E-002 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 355704.54839 444630.68548 26.76254 33.45318 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -26.20000 3.61342E-004 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 91963.97358 105758.56961 7.06130 8.12050 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 31.20000 1.53651E-002 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 98062.78115 122578.47644 7.45597 9.31996 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -26.20000 3.61342E-004 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 14811.80246 17033.57283 1.13738 1.30799 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 31.20000 1.53651E-002 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 19135.52228 23919.40285 1.45806 1.82257 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -26.20000 3.61342E-004 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 19745.79952 22707.66945 1.51624 1.74367 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:50:00 25.03433 1.53537E-002 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 12643.48519 15804.35649 0.96347 1.20433 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -26.20000 3.61342E-004 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 23024.05507 26477.66333 1.76797 2.03317 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 30.84667 1.53644E-002 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 19954.44421 24943.05526 1.52063 1.90079 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -26.20000 3.61342E-004 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 24069.07256 27679.43344 1.84820 2.12543 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 29.53933 1.53620E-002 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 11104.04964 13880.06205 0.84576 1.05719 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -26.20000 3.61342E-004 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 141648.12652 162895.34549 10.87809 12.50981 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 31.20000 1.53651E-002 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 266623.93016 333279.91271 20.33313 25.41641 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -26.20000 3.61342E-004 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 208413.06402 239675.02362 16.00520 18.40598 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:10:00 25.67033 1.53549E-002 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 173051.50622 216314.38277 13.19729 16.49662 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -26.20000 3.61342E-004 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 229285.37490 263678.18114 17.60816 20.24938 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 30.93500 1.53646E-002 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 260563.93719 325704.92148 19.86984 24.83729 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -26.20000 3.61342E-004 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 224552.04804 258234.85524 17.24454 19.83122 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 29.36267 1.53617E-002 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 173350.83032 216688.53790 13.22033 16.52541 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -26.20000 3.61342E-004 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 17274.28287 19865.42531 1.32665 1.52565 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 31.20000 1.53651E-002 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 34499.91421 43124.89277 2.63219 3.29024 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -26.20000 3.61342E-004 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 21112.86600 24279.79590 1.62144 1.86466 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 26.27100 1.53560E-002 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 22355.19203 27943.99004 1.70561 2.13201 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -26.20000 3.61342E-004 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 25859.99384 29738.99292 1.98601 2.28391 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 31.02333 1.53648E-002 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 33872.78222 42340.97777 2.58426 3.23033 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -26.20000 3.61342E-004 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 24356.22070 28009.65380 1.87051 2.15109 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 29.53933 1.53620E-002 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 22647.24943 28309.06179 1.72795 2.15993 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -26.20000 3.61342E-004 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8955.26543 10298.55525 0.68761 0.79075 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 26.87167 1.53571E-002 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 -26.20000 3.61342E-004 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 86166.78277 99091.80019 6.61615 7.60857 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 26.87167 1.53571E-002 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -26.20000 3.61342E-004 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 8871.42180 10202.13508 0.68117 0.78335 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.06600 1.53574E-002 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 -26.20000 3.61342E-004 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 372062.20038 427871.53043 28.56746 32.85258 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 21.55400 1.53473E-002 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -26.20000 3.61342E-004 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 178170.59 12.60438 12.60438 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 91570.85 7.06272 7.06272 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:50:00
3 VAV_MID WITH REHEAT Cooling Sensible 1660228.11 118.36041 118.36041 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 891479.61 116.72891 116.72891 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:00:00
5 VAV_TOP WITH REHEAT Cooling Sensible 203773.68 14.59770 14.59770 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 84417.07 20.13247 20.13247 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:00:00
7 CAV_BAS Cooling Sensible 92408.00 7.24223 7.24223 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CAV_BAS Heating Sensible 80767.74 1.20016 1.20016 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 422416.69 32.85278 32.85278 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 21601.39 0.33839 0.33839 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 10137.01 0.79075 0.79075 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 997.89 1.56323E-002 1.56323E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 97536.58 7.60857 7.60857 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 9978.95 0.15632 0.15632 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 10045.59 0.78335 0.78335 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 997.89 1.56323E-002 1.56323E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:NoReheat BASEMENT PSZ-VAV DIFFUSER Design Size Maximum Air Flow Rate [m3/s] 7.24223
2 AirTerminal:SingleDuct:VAV:NoReheat BASEMENT PSZ-VAV DIFFUSER Design Size Constant Minimum Air Flow Fraction 0.29244
3 AirTerminal:SingleDuct:VAV:NoReheat BASEMENT PSZ-VAV DIFFUSER User-Specified Constant Minimum Air Flow Fraction 0.30000
4 AirTerminal:SingleDuct:VAV:NoReheat BASEMENT PSZ-VAV DIFFUSER Design Size Minimum Air Flow Rate [m3/s] 2.17267
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 7.71849
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24643
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.31555
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.65714
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.54610E-003
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.14450E-004
13 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.31555
14 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
15 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
16 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 35943.51052
17 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.14450E-004
18 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 772.98791
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 73.31602
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.25943
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 21.99481
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.69182
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.46860E-003
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.67003E-003
27 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 33.45318
28 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
29 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
30 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 762425.37185
31 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.67003E-003
32 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 17844.43890
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.31996
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20408
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.79599
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54422
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.86689E-003
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.84693E-003
41 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.31996
42 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
43 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
44 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 211115.18056
45 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.84693E-003
46 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4932.69485
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.82257
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13103
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.54677
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34943
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.90763E-003
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.60649E-004
55 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.82257
56 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
57 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
58 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 41224.37628
59 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.60649E-004
60 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 962.81352
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.74367
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 8.82650E-002
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.52310
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.31655E-003
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.38300E-004
69 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.20433
70 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
71 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
72 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 27239.16875
73 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.38300E-004
74 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 636.17426
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.03317
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11746
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.60995
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.31324
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.24352E-003
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.76104E-004
83 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.90079
84 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
85 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
86 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 42990.99880
87 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.76104E-004
88 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1004.05702
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.12543
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.24112E-002
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.63763
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.26162E-003
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.09239E-004
97 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.05719
98 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
99 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
100 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 23917.27751
101 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.09239E-004
102 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 558.62998
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 25.41641
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.39631E-002
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 7.62492
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.05478E-003
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.02602E-003
111 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 25.41641
112 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
113 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
114 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 574504.89433
115 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.02602E-003
116 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 13415.33736
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 18.40598
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.55650E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.26210E-003
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 16.49662
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 372878.55302
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.26210E-003
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 8707.09620
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 24.83729
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.61561E-002
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 7.45119
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.96231E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.91164E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 24.83729
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 561430.15870
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.91164E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 13110.12770
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 19.83122
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.76075E-002
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.94937
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.90932E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.26777E-003
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 16.52541
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 373526.03494
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.26777E-003
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 8722.19427
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.29024
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.25845E-002
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.98707
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.24905E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.50457E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.29024
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 74351.27467
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.50457E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1736.05461
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.13201
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.21878E-002
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.63960
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.27790E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.21478E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.13201
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 48177.52180
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.21478E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1124.91041
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.23033
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.39324E-002
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.96910
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.15336E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.38622E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.23033
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 72998.38842
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.38622E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1704.47231
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.15993
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.12545E-002
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.64798
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.34703E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.26992E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.15993
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 48807.76870
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.26992E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1139.62129
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.79075
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 7.60857
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.78335
215 AirTerminal:SingleDuct:VAV:NoReheat DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER Design Size Maximum Air Flow Rate [m3/s] 32.85258
216 AirTerminal:SingleDuct:VAV:NoReheat DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER Design Size Constant Minimum Air Flow Fraction 1.81771E-002
217 AirTerminal:SingleDuct:VAV:NoReheat DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER User-Specified Constant Minimum Air Flow Fraction 0.50000
218 AirTerminal:SingleDuct:VAV:NoReheat DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER Design Size Minimum Air Flow Rate [m3/s] 16.42629
219 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 7.72167
220 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.63300
221 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 15.44334
222 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 7.06272
223 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 12.60438
224 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 12.60438
225 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
226 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.56034
227 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 80.90346
228 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 48.54208
229 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 161.80693
230 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 116.72891
231 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 118.36041
232 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 118.36041
233 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
234 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.98622
235 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 10.06624
236 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 6.03974
237 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 20.13247
238 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 20.13247
239 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 14.59770
240 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 20.13247
241 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
242 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 1.00000
243 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.17267
244 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.17267
245 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 7.24223
246 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 2.17267
247 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 7.24223
248 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 7.24223
249 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
250 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 0.30000
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 16.42629
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 16.42629
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 32.85258
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 16.42629
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 32.85278
256 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 32.85278
257 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
258 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.50000
259 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.79075
260 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.79075
261 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.79075
262 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.79075
263 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.79075
264 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.79075
265 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
266 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
267 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 7.60857
268 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 7.60857
269 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 7.60857
270 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 7.60857
271 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 7.60857
272 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 7.60857
273 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
274 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
275 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.78335
276 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.78335
277 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.78335
278 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.78335
279 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.78335
280 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.78335
281 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
282 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
283 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 12.60438
284 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 118.36041
285 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 20.13247
286 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 7.24223
287 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 32.85278
288 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.79075
289 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 7.60857
290 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.78335
291 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 12.60438
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.16083
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.02886
295 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 9.92108E-003
296 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
297 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 261222.41150
298 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.33026E-003
299 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 12.60438
300 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 80348.32589
301 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 7.02922E-004
302 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1306.68012
303 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 12.60438
304 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 9.33026E-003
305 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 5.10372E-005
306 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 7.02922E-004
307 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 118.36041
308 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.25505
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.02951
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.01147E-002
312 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
313 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 2533061.11232
314 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.04751E-002
315 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 118.36041
316 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 817832.27959
317 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 7.15475E-003
318 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 13190.66037
319 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 118.36041
320 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 9.04751E-002
321 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 5.26322E-006
322 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 7.15475E-003
323 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 20.13247
324 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.00096
325 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
326 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.05391
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 9.83306E-003
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
329 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 407681.49438
330 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.45614E-002
331 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 20.13247
332 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 69215.71663
333 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.05529E-004
334 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1184.35574
335 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 20.13247
336 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.45614E-002
337 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 3.27022E-005
338 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 6.05529E-004
339 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 7.24223
340 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
341 AirLoopHVAC:UnitarySystem CAV_BAS_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 7.24223
342 AirLoopHVAC:UnitarySystem CAV_BAS_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 7.24223
343 AirLoopHVAC:UnitarySystem CAV_BAS_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 7.24223
344 AirLoopHVAC:UnitarySystem CAV_BAS_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 2.17267
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 23.94445
346 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
347 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.01913
348 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 9.98344E-003
349 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
350 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 137571.77760
351 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.91375E-003
352 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 7.24223
353 AirLoopHVAC:UnitarySystem CAV_BAS_UNITARY_PACKAGE_DX Design Size Nominal Cooling Capacity [W] 137571.77760
354 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 116808.39385
355 Coil:Heating:Water CAV_BAS HEATING COIL User-Specified Rated Capacity [W] 100000.00000
356 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.74844E-004
357 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 2622.25111
358 AirLoopHVAC:UnitarySystem CAV_BAS_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 100000.00000
359 AirLoopHVAC:UnitarySystem CAV_BAS_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
360 AirLoopHVAC:UnitarySystem CAV_BAS_UNITARY_PACKAGE_DX Design Size Minimum Supply Air Temperature [C] 5.33258
361 AirLoopHVAC:UnitarySystem CAV_BAS_UNITARY_PACKAGE_DX User-Specified Minimum Supply Air Temperature [C] 12.88890
362 AirLoopHVAC:UnitarySystem CAV_BAS_UNITARY_PACKAGE_DX User-Specified Maximum Supply Air Temperature [C] 32.11110
363 Fan:VariableVolume CAV_BAS SZVAV FAN Design Size Maximum Flow Rate [m3/s] 7.24223
364 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 32.85278
365 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
366 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 32.85278
367 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 32.85278
368 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 32.85278
369 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 16.42639
370 Coil:Cooling:Water AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.04124
371 Coil:Cooling:Water AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
372 Coil:Cooling:Water AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Design Outlet Air Temperature [C] 15.00346
373 Coil:Cooling:Water AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.60349E-003
374 Coil:Cooling:Water AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
375 Coil:Cooling:Water AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Design Coil Load [W] 457412.79274
376 Coil:Cooling:Water AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.63377E-002
377 Coil:Cooling:Water AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Design Air Flow Rate [m3/s] 32.85278
378 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX Design Size Nominal Cooling Capacity [W] 457412.79274
379 Coil:Heating:Water AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Capacity [W] 562104.90989
380 Coil:Heating:Water AIRLOOP DATACENTER BASEMENT HEATING COIL User-Specified Rated Capacity [W] 100000.00000
381 Coil:Heating:Water AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.74844E-004
382 Coil:Heating:Water AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size U-Factor Times Area Value [W/K] 2622.25111
383 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 100000.00000
384 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
385 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX User-Specified Minimum Supply Air Temperature [C] 15.88890
386 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX User-Specified Maximum Supply Air Temperature [C] 29.11110
387 Fan:VariableVolume AIRLOOP DATACENTER BASEMENT SYS11 FAN Design Size Maximum Flow Rate [m3/s] 32.85278
388 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 2.95807E-004
389 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
390 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
391 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
392 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.79075
393 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
394 Fan:SystemModel AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 0.79075
395 Fan:SystemModel AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 1359.80750
396 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 0.79075
397 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 0.79075
398 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 0.79075
399 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.79075
400 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER BOT COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 0.79075
401 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER BOT COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.39538
402 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER BOT COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.52717
403 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER BOT COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 13089.75000
404 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER BOT COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 6544.87500
405 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER BOT COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.80066
406 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER BOT COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.80066
407 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 13089.75000
408 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 27039.50747
409 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 29.11000
410 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
411 Coil:Heating:Fuel AIRLOOP DATACENTER BOT HEATING COIL Design Size Nominal Capacity [W] 27039.50747
412 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 7.60857
413 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
414 Fan:SystemModel AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 7.60857
415 Fan:SystemModel AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 13083.99998
416 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 7.60857
417 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 7.60857
418 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 7.60857
419 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 7.60857
420 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER MID COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 7.60857
421 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER MID COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 3.80429
422 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER MID COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 5.07238
423 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER MID COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 125948.91000
424 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER MID COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 62974.45500
425 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER MID COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.80066
426 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER MID COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.80066
427 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 125948.91000
428 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 260351.49502
429 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 29.11000
430 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
431 Coil:Heating:Fuel AIRLOOP DATACENTER MID HEATING COIL Design Size Nominal Capacity [W] 260351.49502
432 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.78335
433 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
434 Fan:SystemModel AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 0.78335
435 Fan:SystemModel AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 1347.07742
436 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 0.78335
437 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 0.78335
438 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 0.78335
439 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.78335
440 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER TOP COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 0.78335
441 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER TOP COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.39167
442 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER TOP COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.52223
443 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER TOP COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 12967.21000
444 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER TOP COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 6483.60500
445 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER TOP COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.80066
446 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER TOP COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.80066
447 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 12967.21000
448 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 26790.79739
449 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 29.11000
450 AirLoopHVAC:UnitarySystem AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
451 Coil:Heating:Fuel AIRLOOP DATACENTER TOP HEATING COIL Design Size Nominal Capacity [W] 26790.79739
452 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 0.13562
453 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 27945.91594
454 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 0.13562
455 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 16.27419
456 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 0.13562
457 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 0.13562
458 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 569257.80938
459 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 6.67000
460 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 3.88337E-002
461 PlantLoop HEATSYS1 Plant Loop Volume [m3] 4.66004
462 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 3.88337E-002
463 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 11694.99545
464 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
465 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 4438926.80098
466 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 4438926.80000
467 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 3.88337E-002
468 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 0.13562
469 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 16.27419
470 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Flow Rate [m3/s] 6.78091E-002
471 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Power Consumption [W] 12898.32174
472 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Flow Rate [m3/s] 6.78091E-002
473 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Power Consumption [W] 12898.32174
474 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 0.13562
475 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 6.83850E-002
476 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1914597.89624
477 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1914622.11500
478 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 9.59541E-002
479 Chiller:Electric:EIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 0.13562
480 Chiller:Electric:EIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 6.83850E-002
481 Chiller:Electric:EIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1914597.89624
482 Chiller:Electric:EIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1914622.11500
483 Chiller:Electric:EIR COOLSYS1 CHILLER2 Design Size Reference Condenser Fluid Flow Rate [m3/s] 9.59541E-002
484 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
485 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
486 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
487 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 56.20530
488 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
489 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.19191
490 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 23.02898
491 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.19191
492 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 66918.62306
493 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 80.74065
494 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 2292209.92710
495 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 16.14813
496 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 286526.24089
497 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 80.74065
498 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 2292209.92710
499 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 16.14813
500 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 286526.24089


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 34114.94
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 723334.11
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 200292.27
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 39111.06
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 25842.79
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 40787.12
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 22691.18
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 545054.03
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 353763.68
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 532649.53
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 354377.97
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 70539.83
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 45707.81
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 69256.29
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 46305.75
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 60258.63
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 602756.27
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 57474.08
19 Coil:Heating:Water CAV_BAS HEATING COIL 94839.65
20 Coil:Heating:Water AIRLOOP DATACENTER BASEMENT HEATING COIL 94839.65


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 314812.92 214234.54 100578.38 0.68 39575.03 401.39
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2998609.73 2029802.55 968807.18 0.68 375521.47 3808.75
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 497455.53 339890.64 157564.88 0.68 62681.76 635.75
4 Coil:Cooling:Water CAV_BAS COOLING COIL 177077.39 121739.76 55337.63 0.69 23475.87 238.11
5 Coil:Cooling:Water AIRLOOP DATACENTER BASEMENT COOLING COIL 588527.44 441537.86 146989.58 0.75 58894.90 597.34


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER BOT COOLING COIL 12470.0     9.16 9.16  
2 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER MID COOLING COIL 119986.0     10.40 10.40  
3 Coil:Cooling:DX:MultiSpeed AIRLOOP DATACENTER TOP COOLING COIL 12353.3     9.16 9.16  


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 6.37 21.74
2 Chiller:Electric:EIR COOLSYS1 CHILLER2 6.37 21.74


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.514 0.477   76.91 200.61 76.91 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.39 N/A 3.241 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.39 N/A 3.241 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.39 N/A 3.241 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.39 N/A 3.241 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.39 N/A 3.241 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.514 0.477   52.57 133.74 52.57 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_EAST_0.39 N/A 3.241 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_EAST_0.39 N/A 3.241 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_EAST_0.39 N/A 3.241 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.514 0.477   76.91 200.61 76.91 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.39 N/A 3.241 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.39 N/A 3.241 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.39 N/A 3.241 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.39 N/A 3.241 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.39 N/A 3.241 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.514 0.477   52.57 133.74 52.57 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_WEST_0.39 N/A 3.241 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_WEST_0.39 N/A 3.241 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_WEST_0.39 N/A 3.241 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.514 0.477   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.39 N/A 3.241 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.514 0.477   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_EAST_0.39 N/A 3.241 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.514 0.477   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.39 N/A 3.241 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.514 0.477   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_WEST_0.39 N/A 3.241 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.514 0.477   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.39 N/A 3.241 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.514 0.477   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_EAST_0.39 N/A 3.241 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.514 0.477   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.39 N/A 3.241 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.514 0.477   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_WEST_0.39 N/A 3.241 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.514 0.477   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.514 0.477   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.514 0.477   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.514 0.477   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.514 0.477   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.514 0.477   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.514 0.477   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.514 0.477   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.514 0.477   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.514 0.477   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.514 0.477   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.514 0.477   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.940 0.824   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.0624874014E-003 1.5566294810E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 3.5310375774E-003 6.2391289845E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 4.1283950404E-002 2.5762289177E-002 Pass Pass 0.4888341982 0.4916354852 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 7.1436026040E-002 8.5724459318E-002 Pass Pass 2.9350625499 18.9587987305 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 2.2854155281E-002 1.8992038013E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 2.7074374368E-002 3.9078251055E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 3.8144908437E-002 6.3231414960E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 2.3753028381E-002 1.9942148041E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 0.4300065884 0.4482956145 Pass Pass 0.7773750587 0.7645519621 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.4360698968 0.4606252543 Pass Pass 0.7557524609 0.6832660721 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.3759596978 0.4219069832 Pass Pass 0.7843514012 0.7251525756 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.2985389362 0.3239898391 Pass Pass 0.7873250274 0.7515070535 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.6178655210 0.6365186999 Pass Pass 0.7895179309 1.2048084396 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.6219260044 0.6481067301 Pass Pass 0.7172295278 0.7302084203 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.5620588899 0.6055378526 Pass Pass 0.7083499027 0.6697400285 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.4883433067 0.5149225098 Pass Pass 0.7393888010 0.8054660891 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.2912116418E-003 5.3795975743E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 3.9937787015E-002 2.7819822792E-002 Pass Pass 0.4869152097 0.4671638918 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 0.2495841730 0.1796756271 Pass Pass 0.4927374382 0.4846512897 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 3.2735763369E-002 6.5732499087E-002 Pass Pass 21.4365744191 211.6536879243 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 5.4344046207E-003 4.7770741507E-003 Pass Pass 1.2932498548E-003 1.1945108784E-003 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 9.9296382607E-003 8.8644142614E-003 Pass Pass 2.5571210890E-003 2.0370184040E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 3.1364768138E-002 2.1809378117E-002 Pass Pass 1.6572625453E-003 1.2827898246E-003 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 6902.28 373.33 0.00 27950.73 15804.19 51030.53



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB -26.20 0.00 -26.20 Wetbulb [C] 5.70 310.00
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 31.20 10.60 23.10 Wetbulb [C] 6.70 200.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 26.00 35      
Feb 0.00 0      
Mar 0.00 0      
Apr 29.00 23      
May 0.00 0      
Jun 107.00 45      
Jul 72.00 29      
Aug 0.00 0      
Sep 20.00 11      
Oct 0.00 0      
Nov 0.00 0      
Dec 4.00 8      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.477 0.514 200.61 76.91 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.477 0.514 133.74 52.57 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.477 0.514 200.61 76.91 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.477 0.514 133.74 52.57 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.477 0.514 2006.06 847.11 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.477 0.514 1337.37 564.74 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.477 0.514 2006.06 847.11 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.477 0.514 1337.37 564.74 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.477 0.514 200.61 84.71 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.477 0.514 133.74 56.47 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.477 0.514 200.61 84.71 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.477 0.514 133.74 56.47 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.477 0.514 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 0.477 0.514 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.477 0.514 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.477 0.514 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.477 0.514 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.477 0.514 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.477 0.514 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.477 0.514 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.477 0.514 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.477 0.514 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.477 0.514 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.477 0.514 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.30 0.358 0.376 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.845 0.940 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.57_SHGC_NORTH_0.39   23.18 0.00 0.00 23.18 23.18 3.241 0.391 0.431             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.57_SHGC_NORTH_0.39   23.18 0.00 0.00 23.18 23.18 3.241 0.391 0.431             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.57_SHGC_NORTH_0.39   23.18 0.00 0.00 23.18 23.18 3.241 0.391 0.431             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.57_SHGC_NORTH_0.39   23.18 0.00 0.00 23.18 23.18 3.241 0.391 0.431             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.57_SHGC_NORTH_0.39   23.18 0.00 0.00 23.18 23.18 3.241 0.391 0.431             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.57_SHGC_EAST_0.39   25.75 0.00 0.00 25.75 25.75 3.241 0.391 0.431             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.57_SHGC_EAST_0.39   25.75 0.00 0.00 25.75 25.75 3.241 0.391 0.431             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.57_SHGC_EAST_0.39   25.75 0.00 0.00 25.75 25.75 3.241 0.391 0.431             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.57_SHGC_SOUTH_0.39   23.18 0.00 0.00 23.18 23.18 3.241 0.391 0.431             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.57_SHGC_SOUTH_0.39   23.18 0.00 0.00 23.18 23.18 3.241 0.391 0.431             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.57_SHGC_SOUTH_0.39   23.18 0.00 0.00 23.18 23.18 3.241 0.391 0.431             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.57_SHGC_SOUTH_0.39   23.18 0.00 0.00 23.18 23.18 3.241 0.391 0.431             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.57_SHGC_SOUTH_0.39   23.18 0.00 0.00 23.18 23.18 3.241 0.391 0.431             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.57_SHGC_WEST_0.39   25.75 0.00 0.00 25.75 25.75 3.241 0.391 0.431             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.57_SHGC_WEST_0.39   25.75 0.00 0.00 25.75 25.75 3.241 0.391 0.431             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.57_SHGC_WEST_0.39   25.75 0.00 0.00 25.75 25.75 3.241 0.391 0.431             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.57_SHGC_NORTH_0.39   115.90 0.00 0.00 115.90 1158.95 3.241 0.391 0.431             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.57_SHGC_EAST_0.39   77.26 0.00 0.00 77.26 772.63 3.241 0.391 0.431             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.57_SHGC_SOUTH_0.39   115.90 0.00 0.00 115.90 1158.95 3.241 0.391 0.431             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.57_SHGC_WEST_0.39   77.26 0.00 0.00 77.26 772.63 3.241 0.391 0.431             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.57_SHGC_NORTH_0.39   115.90 0.00 0.00 115.90 115.90 3.241 0.391 0.431             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.57_SHGC_EAST_0.39   77.26 0.00 0.00 77.26 77.26 3.241 0.391 0.431             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.57_SHGC_SOUTH_0.39   115.90 0.00 0.00 115.90 115.90 3.241 0.391 0.431             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.57_SHGC_WEST_0.39   77.26 0.00 0.00 77.26 77.26 3.241 0.391 0.431             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             4635.80 3.241 0.391 0.431                      
North Total or Average             1390.74 3.241 0.391 0.431                      
Non-North Total or Average             3245.06 3.241 0.391 0.431                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 11.6510 2779.43 32383.10 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 333.79
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 11.6510 2496.12 29082.30 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 299.77
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 11.6510 24961.20 290822.99 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 2997.66
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 11.6510 2496.12 29082.30 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 299.77
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 11.6510 313.41 3651.57 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 37.64
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 11.6510 201.98 2353.21 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 24.26
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 11.6510 313.42 3651.65 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 37.64
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 11.6510 201.98 2353.21 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 24.26
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 11.6510 3134.13 36515.73 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 376.39
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 11.6510 2019.75 23532.12 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 242.56
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 11.6510 3134.20 36516.53 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 376.39
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 11.6510 2019.75 23532.12 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 242.56
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 11.6510 313.41 3651.57 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 37.64
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 11.6510 201.98 2353.21 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 24.26
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 11.6510 313.42 3651.65 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 37.64
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 11.6510 201.98 2353.21 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 24.26
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 11.6510 783.68 9130.65 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 94.11
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 22.3674 36.20 809.76 LightsWired LTG_SCH_DATACENTER 56.37 168.00 54.91 0.0000 Y 8.35
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 22.3674 362.03 8097.60 LightsWired LTG_SCH_DATACENTER 56.37 168.00 54.91 0.0000 Y 83.47
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 22.3674 36.20 809.76 LightsWired LTG_SCH_DATACENTER 56.37 168.00 54.91 0.0000 Y 8.35
Interior Lighting Total       11.7515 46320.38 544334.28               1723.61


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS 64082.80 AstronomicalClock -   83.63 83.63 1006.00
Exterior Lighting Total 64082.80           1006.00



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 3787056.37          
HEATSYS1 BOILER Boiler:HotWater 4438926.80 0.79        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 1914622.11 6.11 1905279.80 6.08 6.37 21.74
COOLSYS1 CHILLER2 Chiller:Electric:EIR 1914622.11 6.11 1905279.80 6.08 6.37 21.74
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 2292209.93          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 2292209.93          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 261222.41 314812.92 214234.54 100578.38 0.68 - 39575.03 401.39
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 2533061.11 2998609.73 2029802.55 968807.18 0.68 - 375521.47 3808.75
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 407681.49 497455.53 339890.64 157564.88 0.68 - 62681.76 635.75
CAV_BAS COOLING COIL Coil:Cooling:Water 137571.78 177077.39 121739.76 55337.63 0.69 - 23475.87 238.11
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:Water 457412.79 588527.44 441537.86 146989.58 0.75 - 58894.90 597.34
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:DX:MultiSpeed   13089.75 10480.44 2609.31 0.80 3.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:DX:MultiSpeed   125948.91 100842.25 25106.66 0.80 3.50    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:DX:MultiSpeed   12967.21 10382.33 2584.88 0.80 3.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
AIRLOOP DATACENTER BOT COOLING COIL   12470.0     9.16 9.16  
AIRLOOP DATACENTER MID COOLING COIL   119986.0     10.40 10.40  
AIRLOOP DATACENTER TOP COOLING COIL   12353.3     9.16 9.16  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:DX:MultiSpeed                
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:DX:MultiSpeed                
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:DX:MultiSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 35943.51 34114.94 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 762425.37 723334.11 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 211115.18 200292.27 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 41224.38 39111.06 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 27239.17 25842.79 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 42991.00 40787.12 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 23917.28 22691.18 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 574504.89 545054.03 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 372878.55 353763.68 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 561430.16 532649.53 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 373526.03 354377.97 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 74351.27 70539.83 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 48177.52 45707.81 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 72998.39 69256.29 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 48807.77 46305.75 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 80348.33 60258.63 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 817832.28 602756.27 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 69215.72 57474.08 -
CAV_BAS HEATING COIL Coil:Heating:Water 100000.00 94839.65 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:Water 100000.00 94839.65 -
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:Fuel   27039.51 0.80
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:Fuel   260351.50 0.79
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:Fuel   26790.80 0.80
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1337.13 12.60 27554.47 2186.10 1.00 1.11 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1337.13 118.36 258748.06 2186.10 1.00 1.08 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.62 1337.13 20.13 43411.92 2156.31 1.00 1.12 General ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00
CAV_BAS SZVAV FAN Fan:VariableVolume 0.61 1337.13 7.24 15916.84 2197.78 1.00 1.13 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
AIRLOOP DATACENTER BASEMENT SYS11 FAN Fan:VariableVolume 0.61 637.69 32.85 34106.41 1038.16 1.00 1.19 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.56 966.87 0.79 1359.81 1719.64 1.00 1.35 General ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.56 966.87 7.61 13084.00 1719.64 1.00 1.08 General ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.56 966.87 0.78 1347.08 1719.64 1.00 1.35 General ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.83 0.135618 27945.92 206063.11 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.038834 11695.00 301156.09 0.90 General
COOLSYS1 CHILLER1 PUMP Pump:ConstantSpeed Intermittent 123258.43 0.067809 12898.32 190215.15 0.90 General
COOLSYS1 CHILLER2 PUMP Pump:ConstantSpeed Intermittent 123258.43 0.067809 12898.32 190215.15 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000440 56.21 127739.32 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 209234.68 0.191908 66918.62 348701.22 0.90 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 1.00 13.34 0.74



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 82743.46 95154.98 34.24 6.298 7.242 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00892 23.36 0.01535 1.200 0.00
CORE_BOTTOM 88186.73 101414.73 40.63 6.712 7.718 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00885 23.36 0.01535 1.078 0.00
CORE_MID 837830.45 963505.02 386.00 63.753 73.316 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00887 23.36 0.01535 10.778 0.00
CORE_TOP 91963.97 105758.57 42.37 7.061 8.120 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 24.00 0.00883 31.20 0.01537 1.078 0.00
PERIMETER_BOT_ZN_3 14811.80 17033.57 54.35 1.137 1.308 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 24.00 24.00 0.00897 31.20 0.01537 0.135 0.00
PERIMETER_BOT_ZN_2 19745.80 22707.67 112.43 1.516 1.744 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:50:00 24.00 24.00 0.00874 25.03 0.01535 0.087 0.00
PERIMETER_BOT_ZN_1 23024.06 26477.66 84.48 1.768 2.033 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 24.00 24.00 0.00880 30.85 0.01536 0.135 0.00
PERIMETER_BOT_ZN_4 24069.07 27679.43 137.04 1.848 2.125 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 24.00 24.00 0.00869 29.54 0.01536 0.087 0.00
PERIMETER_MID_ZN_3 141648.13 162895.35 519.75 10.878 12.510 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00926 31.20 0.01537 1.353 0.00
PERIMETER_MID_ZN_2 208413.06 239675.02 1186.66 16.005 18.406 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:10:00 24.00 24.00 0.00886 25.67 0.01535 0.872 0.00
PERIMETER_MID_ZN_1 229285.37 263678.18 841.29 17.608 20.249 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 24.00 24.00 0.00898 30.93 0.01536 1.353 0.00
PERIMETER_MID_ZN_4 224552.05 258234.86 1278.55 17.245 19.831 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 24.00 24.00 0.00883 29.36 0.01536 0.872 0.00
PERIMETER_TOP_ZN_3 17274.28 19865.43 63.38 1.327 1.526 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 24.00 0.00922 31.20 0.01537 0.135 0.00
PERIMETER_TOP_ZN_2 21112.87 24279.80 120.21 1.621 1.865 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 24.00 24.00 0.00891 26.27 0.01536 0.087 0.00
PERIMETER_TOP_ZN_1 25859.99 29738.99 94.89 1.986 2.284 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 24.00 24.00 0.00900 31.02 0.01536 0.135 0.00
PERIMETER_TOP_ZN_4 24356.22 28009.65 138.68 1.871 2.151 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 24.00 24.00 0.00885 29.54 0.01536 0.087 0.00
DATACENTER_BOT_ZN_6 8955.27 10298.56 284.47 0.688 0.791 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 27.00 27.00 0.00856 26.87 0.01536 0.016 0.00
DATACENTER_MID_ZN_6 86166.78 99091.80 2737.14 6.616 7.609 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 27.00 27.00 0.00857 26.87 0.01536 0.156 0.00
DATACENTER_TOP_ZN_6 8871.42 10202.14 281.81 0.681 0.783 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.00 27.00 0.00856 27.07 0.01536 0.016 0.00
DATACENTER_BASEMENT_ZN_6 372062.20 427871.53 545.98 28.567 32.853 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 27.00 27.00 0.00853 21.55 0.01535 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.96 0.00036 -26.20 0.00036 1.200 0.00
CORE_BOTTOM 11157.22 13946.52 5.59 0.833 1.078 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -26.20 0.00036 1.078 0.00
CORE_MID 355704.55 444630.69 178.13 26.763 33.453 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -26.20 0.00036 10.778 0.00
CORE_TOP 98062.78 122578.48 49.11 7.456 9.320 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -26.20 0.00036 1.078 0.00
PERIMETER_BOT_ZN_3 19135.52 23919.40 76.32 1.458 1.823 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00779 -26.20 0.00036 0.135 0.00
PERIMETER_BOT_ZN_2 12643.49 15804.36 78.25 0.963 1.204 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00779 -26.20 0.00036 0.087 0.00
PERIMETER_BOT_ZN_1 19954.44 24943.06 79.58 1.521 1.901 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00780 -26.20 0.00036 0.135 0.00
PERIMETER_BOT_ZN_4 11104.05 13880.06 68.72 0.846 1.057 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00776 -26.20 0.00036 0.087 0.00
PERIMETER_MID_ZN_3 266623.93 333279.91 1063.39 20.333 25.416 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00765 -26.20 0.00036 1.353 0.00
PERIMETER_MID_ZN_2 173051.51 216314.38 1071.00 13.197 16.497 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00765 -26.20 0.00036 0.872 0.00
PERIMETER_MID_ZN_1 260563.94 325704.92 1039.20 19.870 24.837 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00765 -26.20 0.00036 1.353 0.00
PERIMETER_MID_ZN_4 173350.83 216688.54 1072.85 13.220 16.525 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00765 -26.20 0.00036 0.872 0.00
PERIMETER_TOP_ZN_3 34499.91 43124.89 137.60 2.632 3.290 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00767 -26.20 0.00036 0.135 0.00
PERIMETER_TOP_ZN_2 22355.19 27943.99 138.35 1.706 2.132 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00766 -26.20 0.00036 0.087 0.00
PERIMETER_TOP_ZN_1 33872.78 42340.98 135.09 2.584 3.230 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00766 -26.20 0.00036 0.135 0.00
PERIMETER_TOP_ZN_4 22647.25 28309.06 140.16 1.728 2.160 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00766 -26.20 0.00036 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 18.00 23.93 0.00116 -26.20 0.00036 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 22.00 0.00116 -26.20 0.00036 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 18.00 18.73 0.00116 -26.20 0.00036 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 18.00 27.00 0.00850 -26.20 0.00036 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 12.60 12.60 7.06 7.06 12.6044 7.0627 12.6044 0.5603 0.3000
VAV_MID WITH REHEAT 118.36 118.36 116.73 116.73 118.3604 116.7289 118.3604 0.9862 0.3000
VAV_TOP WITH REHEAT 14.60 14.60 20.13 20.13 14.5977 20.1325 20.1325 1.0000 0.3000
CAV_BAS 7.24 7.24 1.20 1.20 7.2422 2.1727 7.2422 0.3000 1.0000
AIRLOOP DATACENTER BASEMENT 32.85 32.85 0.34 0.34 32.8528 16.4263 32.8528 0.5000 1.0000
AIRLOOP DATACENTER BOT 0.79 0.79 0.02 0.02 0.7908 0.7908 0.7908 1.0000 1.0000
AIRLOOP DATACENTER MID 7.61 7.61 0.16 0.16 7.6086 7.6086 7.6086 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.78 0.78 0.02 0.02 0.7833 0.7833 0.7833 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 35943.511 35943.511 2.315548 0.00031445 772.988 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 35943.51 35943.51 2.315548 12.89 11.21 0.00800000 32.11 18.22 0.00800000 -26.20 0.00036134 -26.20 0.0000 21.00 0.00800000 49.3289 13946.52 0.00 36115.90 36115.90
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 762425.372 762425.372 33.453180 0.00667003 17844.439 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 762425.37 762425.37 33.453180 12.89 11.21 0.00800000 32.11 18.22 0.00800000 -26.20 0.00036134 -26.20 0.0000 21.00 0.00800000 49.3289 444630.69 0.00 765918.09 765918.09
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 211115.181 211115.181 9.319962 0.00184693 4932.695 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 211115.18 209819.91 9.319962 12.89 11.21 0.00800000 32.11 18.22 0.00800000 -26.20 0.00036134 -26.20 0.0000 21.00 0.00800000 49.3290 122578.48 0.00 212082.98 212082.98
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 41224.376 41224.376 1.822574 0.00036065 962.814 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 41224.38 41031.54 1.822574 12.89 11.21 0.00800000 32.11 18.22 0.00800000 -26.20 0.00036134 -26.20 0.0000 21.00 0.00779187 48.0647 23919.40 0.00 41413.39 41413.39
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 27239.169 27239.169 1.204332 0.00023830 636.174 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 27239.17 27239.17 1.204332 12.89 11.21 0.00800000 32.11 18.22 0.00800000 -26.20 0.00036134 -26.20 0.0000 21.00 0.00778992 48.0529 15804.36 0.00 27364.06 27364.06
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 42990.999 42990.999 1.900793 0.00037610 1004.057 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 42991.00 42991.00 1.900793 12.89 11.21 0.00800000 32.11 18.22 0.00800000 -26.20 0.00036134 -26.20 0.0000 21.00 0.00779979 48.1129 24943.06 0.00 43188.11 43188.11
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 23917.278 23917.278 1.057194 0.00020924 558.630 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 23917.28 23917.28 1.057194 12.89 11.21 0.00800000 32.11 18.22 0.00800000 -26.20 0.00036134 -26.20 0.0000 21.00 0.00776198 47.8828 13880.06 0.00 24026.93 24026.93
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 574504.894 574504.894 25.416412 0.00502602 13415.337 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 574504.89 572198.62 25.416412 12.89 11.21 0.00800000 32.11 18.22 0.00800000 -26.20 0.00036134 -26.20 0.0000 21.00 0.00765445 47.2310 333279.91 0.00 577139.17 577139.17
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 372878.553 372878.553 16.496616 0.00326210 8707.096 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 372878.55 372878.55 16.496616 12.89 11.21 0.00800000 32.11 18.22 0.00800000 -26.20 0.00036134 -26.20 0.0000 21.00 0.00764537 47.1759 216314.38 0.00 374588.32 374588.32
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 561430.159 561430.159 24.837294 0.00491164 13110.128 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 561430.16 559160.95 24.837294 12.89 11.21 0.00800000 32.11 18.22 0.00800000 -26.20 0.00036134 -26.20 0.0000 21.00 0.00764679 47.1844 325704.92 0.00 564004.48 564004.48
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 373526.035 373526.035 16.525407 0.00326777 8722.194 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 373526.03 373526.03 16.525407 12.89 11.21 0.00800000 32.11 18.22 0.00800000 -26.20 0.00036134 -26.20 0.0000 21.00 0.00764632 47.1817 216688.54 0.00 375238.77 375238.77
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 74351.275 74351.275 3.290241 0.00065046 1736.055 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 74351.27 74073.05 3.290241 12.89 11.21 0.00800000 32.11 18.22 0.00800000 -26.20 0.00036134 -26.20 0.0000 21.00 0.00766664 47.3067 43124.89 0.00 74692.21 74692.21
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 48177.522 48177.522 2.132009 0.00042148 1124.910 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 48177.52 47997.84 2.132009 12.89 11.21 0.00800000 32.11 18.22 0.00800000 -26.20 0.00036134 -26.20 0.0000 21.00 0.00765735 47.2502 27943.99 0.00 48398.44 48398.44
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 72998.388 72998.388 3.230326 0.00063862 1704.472 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 72998.39 72724.19 3.230326 12.89 11.21 0.00800000 32.11 18.22 0.00800000 -26.20 0.00036134 -26.20 0.0000 21.00 0.00766068 47.2704 42340.98 0.00 73333.12 73333.12
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 48807.769 48807.769 2.159933 0.00042699 1139.621 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 48807.77 48626.49 2.159933 12.89 11.21 0.00800000 32.11 18.22 0.00800000 -26.20 0.00036134 -26.20 0.0000 21.00 0.00766196 47.2784 28309.06 0.00 49031.57 49031.57
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 261222.411 -999.000 12.604378 0.00933026 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 261222.41 209229.94 12.604378 25.16 17.47 0.00992108 11.03 10.95 0.00850000 31.20 0.01536508 23.13 16.1095 24.00 0.00887321 45.5368 142458.39 0.00 270206.29 205224.97
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 80348.326 80348.326 3.781313 0.00070292 1306.680 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:50:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 80348.33 80348.33 3.781313 -5.52 -5.52 0.00369333 12.89 11.21 0.00800000 -26.20 0.00036134 -26.20 53.6983 18.65 0.00766933 54.7503 14817.79 0.00 72908.28 72908.28
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 2533061.112 -999.000 118.360409 0.09047507 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 2533061.11 1978157.00 118.360409 25.26 17.66 0.01011468 11.03 10.95 0.00850000 31.20 0.01536508 23.13 17.1561 24.00 0.00900434 46.2017 1317272.71 0.00 2618503.46 1942916.94
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 817832.280 817832.280 35.508123 0.00715475 13190.660 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 817832.28 817832.28 35.508123 -7.07 -7.07 0.00337843 12.89 11.21 0.00800000 -26.20 0.00036134 -26.20 57.1869 18.34 0.00766451 55.7817 206216.20 0.00 729191.40 729191.40
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 407681.494 -999.000 20.132471 0.01456144 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 407681.49 329915.18 20.132471 25.00 17.35 0.00983306 11.05 10.96 0.00850000 31.20 0.01536508 23.13 10.0857 24.00 0.00893778 45.8653 165070.23 0.00 421890.32 323516.49
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 69215.717 69215.717 6.039741 0.00060553 1184.356 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 69215.72 69215.72 6.039741 2.96 2.96 0.00497777 12.89 11.21 0.00800000 -26.20 0.00036134 -26.20 33.6190 16.82 0.00768789 61.5817 34622.82 0.00 69570.77 69570.77
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 137571.778 -999.000 7.242230 0.00491375 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 137571.78 107200.72 7.242230 23.94 17.12 0.00998344 11.02 10.94 0.00850000 23.36 0.01535063 20.94 16.5716 24.00 0.00891734 45.7594 82743.46 0.00 146243.54 107938.81
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 100000.000 100000.000 3.185474 0.00087484 2622.251 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 100000.00 100000.00 3.185474 -4.34 -8.65 0.00036134 32.11 18.22 0.00800000 -26.20 0.00036134 -26.20 37.6759 22.08 0.00036134 2.1110 0.00 0.00 100071.45 100071.45
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:Water AirLoopHVAC AIRLOOP DATACENTER BASEMENT 457412.793 -999.000 32.852785 0.01633772 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 457412.79 450204.00 32.852785 27.04 17.04 0.00860349 15.00 12.56 0.00850000 31.20 0.01536508 23.13 1.0300 27.00 0.00853305 36.6651 371638.55 0.00 490747.74 490747.74
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:Water AirLoopHVAC AIRLOOP DATACENTER BASEMENT 100000.000 100000.000 3.185474 0.00087484 2622.251 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 100000.00 100000.00 3.185474 -0.27 -0.27 0.00841617 29.11 17.24 0.00800000 -26.20 0.00036134 -26.20 10.6230 27.00 0.00850000 36.5206 0.00 0.00 100071.45 100071.45
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC AIRLOOP DATACENTER BOT 13089.750 10480.439 0.790750 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 6544.88 6350.28 0.527167 27.00 17.10 0.00869751 14.42 12.33 0.00850000 26.87 0.01535708 21.94 2.9654 27.00 0.00856320 36.7909 8955.27 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:Fuel AirLoopHVAC AIRLOOP DATACENTER BOT 27039.507 27039.507 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 27039.51 27039.51 0.790752 -0.52 -4.75 0.00114674 29.11 17.24 0.00800000 -26.20 0.00036134 -26.20 1.9769 24.62 0.00116258 5.8178 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC AIRLOOP DATACENTER MID 125948.910 100842.254 7.608570 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 62974.46 61031.44 5.072380 27.00 17.10 0.00870520 14.42 12.33 0.00850000 26.87 0.01535708 21.94 3.0819 27.00 0.00856566 36.8014 86166.78 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:Fuel AirLoopHVAC AIRLOOP DATACENTER MID 260351.495 260351.495 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 260351.50 260351.50 7.608574 -0.54 -4.76 0.00114614 29.11 17.24 0.00800000 -26.20 0.00036134 -26.20 2.0546 23.26 0.00116261 6.3151 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC AIRLOOP DATACENTER TOP 12967.210 10382.326 0.783350 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 6483.60 6289.20 0.522233 27.00 17.10 0.00869928 14.42 12.33 0.00850000 27.07 0.01535744 22.00 2.9934 27.00 0.00856371 36.7931 8871.42 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:Fuel AirLoopHVAC AIRLOOP DATACENTER TOP 26790.797 26790.797 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 26790.80 26790.80 0.783349 -0.52 -4.75 0.00114519 29.11 17.24 0.00800000 -26.20 0.00036134 -26.20 1.9956 21.00 0.00116115 7.2364 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 35943.511 35943.511 2.315548 0.00031445 772.988 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.82970665 54.44 82.22 27.78 4528261.97 0.7938 0.809734 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 35943.51 35943.51 1.0000 2.65953587 2.315548 12.89 11.21 0.00800000 33150.5 32.11 18.22 0.00800000 52751.6 0.31441743 60.00 32.22 27.78 0.000 35943.51 -26.20 0.00036134 -26.20 0.00000000 0.0000 20.72 0.00800000 21.00 0.00800000 49.3289 13946.52 0.00 36115.90 36115.90 2.65953587 12.80 11.60 0.00800000 33059.8 26.12 16.71 0.00800000 46639.6
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 762425.372 762425.372 33.453180 0.00667003 17844.439 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.82970665 54.44 82.22 27.78 4528261.97 16.8370 17.175894 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 762425.37 762425.37 1.0000 38.42284473 33.453180 12.89 11.21 0.00800000 33150.5 32.11 18.22 0.00800000 52751.6 6.66934934 60.00 32.22 27.78 0.000 762425.37 -26.20 0.00036134 -26.20 0.00000000 0.0000 20.86 0.00800000 21.00 0.00800000 49.3289 444630.69 0.00 765918.09 765918.09 38.42284473 12.80 11.60 0.00800000 33059.8 32.35 18.81 0.00800000 52993.8
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 211115.181 211115.181 9.319962 0.00184693 4932.695 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.82970665 54.44 82.22 27.78 4528261.97 4.6622 4.755996 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 211115.18 209819.91 1.0000 10.70449627 9.319962 12.89 11.21 0.00800000 33150.5 32.11 18.22 0.00800000 52751.6 1.84673929 60.00 32.22 27.78 0.000 211115.18 -26.20 0.00036134 -26.20 0.00000000 0.0000 20.95 0.00800000 21.00 0.00800000 49.3290 122578.48 0.00 212082.98 212082.98 10.70449627 12.80 11.60 0.00800000 33059.8 32.23 18.77 0.00800000 52872.3
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 41224.376 41224.376 1.822574 0.00036065 962.814 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.82970665 54.44 82.22 27.78 4528261.97 0.9104 0.928701 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 41224.38 41031.54 1.0000 2.09332827 1.822574 12.89 11.21 0.00800000 33150.5 32.11 18.22 0.00800000 52751.6 0.36061204 60.00 32.22 27.78 0.000 41224.38 -26.20 0.00036134 -26.20 0.00000000 0.0000 20.94 0.00779187 21.00 0.00779187 48.0647 23919.40 0.00 41413.39 41413.39 2.09332827 12.80 11.60 0.00800000 33059.8 32.20 18.76 0.00800000 52843.3
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 27239.169 27239.169 1.204332 0.00023830 636.174 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.82970665 54.44 82.22 27.78 4528261.97 0.6015 0.613643 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 27239.17 27239.17 1.0000 1.38324198 1.204332 12.89 11.21 0.00800000 33150.5 32.11 18.22 0.00800000 52751.6 0.23827582 60.00 32.22 27.78 0.000 27239.17 -26.20 0.00036134 -26.20 0.00000000 0.0000 20.94 0.00778992 21.00 0.00778992 48.0529 15804.36 0.00 27364.06 27364.06 1.38324198 12.80 11.60 0.00800000 33059.8 32.20 18.76 0.00800000 52842.4
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 42990.999 42990.999 1.900793 0.00037610 1004.057 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.82970665 54.44 82.22 27.78 4528261.97 0.9494 0.968500 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 42991.00 42991.00 1.0000 2.18316671 1.900793 12.89 11.21 0.00800000 33150.5 32.11 18.22 0.00800000 52751.6 0.37606565 60.00 32.22 27.78 0.000 42991.00 -26.20 0.00036134 -26.20 0.00000000 0.0000 20.94 0.00779979 21.00 0.00779979 48.1129 24943.06 0.00 43188.11 43188.11 2.18316671 12.80 11.60 0.00800000 33059.8 32.20 18.76 0.00800000 52842.2
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 23917.278 23917.278 1.057194 0.00020924 558.630 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.82970665 54.44 82.22 27.78 4528261.97 0.5282 0.538808 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 23917.28 23917.28 1.0000 1.21424689 1.057194 12.89 11.21 0.00800000 33150.5 32.11 18.22 0.00800000 52751.6 0.20921743 60.00 32.22 27.78 0.000 23917.28 -26.20 0.00036134 -26.20 0.00000000 0.0000 20.95 0.00776198 21.00 0.00776198 47.8828 13880.06 0.00 24026.93 24026.93 1.21424689 12.80 11.60 0.00800000 33059.8 32.21 18.76 0.00800000 52847.3
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 574504.894 574504.894 25.416412 0.00502602 13415.337 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.82970665 54.44 82.22 27.78 4528261.97 12.6871 12.942428 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 574504.89 572198.62 1.0000 29.19216836 25.416412 12.89 11.21 0.00800000 33150.5 32.11 18.22 0.00800000 52751.6 5.02550673 60.00 32.22 27.78 0.000 574504.89 -26.20 0.00036134 -26.20 0.00000000 0.0000 20.94 0.00765445 21.00 0.00765445 47.2310 333279.91 0.00 577139.17 577139.17 29.19216836 12.80 11.60 0.00800000 33059.8 32.19 18.76 0.00800000 52830.2
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 372878.553 372878.553 16.496616 0.00326210 8707.096 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.82970665 54.44 82.22 27.78 4528261.97 8.2345 8.400196 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 372878.55 372878.55 1.0000 18.94728475 16.496616 12.89 11.21 0.00800000 33150.5 32.11 18.22 0.00800000 52751.6 3.26177148 60.00 32.22 27.78 0.000 372878.55 -26.20 0.00036134 -26.20 0.00000000 0.0000 20.94 0.00764537 21.00 0.00764537 47.1759 216314.38 0.00 374588.32 374588.32 18.94728475 12.80 11.60 0.00800000 33059.8 32.19 18.76 0.00800000 52829.9
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 561430.159 561430.159 24.837294 0.00491164 13110.128 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.82970665 54.44 82.22 27.78 4528261.97 12.3984 12.647881 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 561430.16 559160.95 1.0000 28.52701864 24.837294 12.89 11.21 0.00800000 33150.5 32.11 18.22 0.00800000 52751.6 4.91113491 60.00 32.22 27.78 0.000 561430.16 -26.20 0.00036134 -26.20 0.00000000 0.0000 20.94 0.00764679 21.00 0.00764679 47.1844 325704.92 0.00 564004.48 564004.48 28.52701864 12.80 11.60 0.00800000 33059.8 32.19 18.76 0.00800000 52830.7
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 373526.035 373526.035 16.525407 0.00326777 8722.194 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.82970665 54.44 82.22 27.78 4528261.97 8.2488 8.414782 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 373526.03 373526.03 1.0000 18.98035288 16.525407 12.89 11.21 0.00800000 33150.5 32.11 18.22 0.00800000 52751.6 3.26743535 60.00 32.22 27.78 0.000 373526.03 -26.20 0.00036134 -26.20 0.00000000 0.0000 20.94 0.00764632 21.00 0.00764632 47.1817 216688.54 0.00 375238.77 375238.77 18.98035288 12.80 11.60 0.00800000 33059.8 32.19 18.76 0.00800000 52829.7
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 74351.275 74351.275 3.290241 0.00065046 1736.055 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.82970665 54.44 82.22 27.78 4528261.97 1.6419 1.674983 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 74351.27 74073.05 1.0000 3.77902526 3.290241 12.89 11.21 0.00800000 33150.5 32.11 18.22 0.00800000 52751.6 0.65039103 60.00 32.22 27.78 0.000 74351.27 -26.20 0.00036134 -26.20 0.00000000 0.0000 20.94 0.00766664 21.00 0.00766664 47.3067 43124.89 0.00 74692.21 74692.21 3.77902526 12.80 11.60 0.00800000 33059.8 32.18 18.76 0.00800000 52824.8
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 48177.522 48177.522 2.132009 0.00042148 1124.910 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.82970665 54.44 82.22 27.78 4528261.97 1.0639 1.085342 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 48177.52 47997.84 1.0000 2.44873168 2.132009 12.89 11.21 0.00800000 33150.5 32.11 18.22 0.00800000 52751.6 0.42143498 60.00 32.22 27.78 0.000 48177.52 -26.20 0.00036134 -26.20 0.00000000 0.0000 20.94 0.00765735 21.00 0.00765735 47.2502 27943.99 0.00 48398.44 48398.44 2.44873168 12.80 11.60 0.00800000 33059.8 32.18 18.76 0.00800000 52824.5
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 72998.388 72998.388 3.230326 0.00063862 1704.472 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.82970665 54.44 82.22 27.78 4528261.97 1.6121 1.644505 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 72998.39 72724.19 1.0000 3.71020975 3.230326 12.89 11.21 0.00800000 33150.5 32.11 18.22 0.00800000 52751.6 0.63855660 60.00 32.22 27.78 0.000 72998.39 -26.20 0.00036134 -26.20 0.00000000 0.0000 20.94 0.00766068 21.00 0.00766068 47.2704 42340.98 0.00 73333.12 73333.12 3.71020975 12.80 11.60 0.00800000 33059.8 32.18 18.76 0.00800000 52825.1
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 48807.769 48807.769 2.159933 0.00042699 1139.621 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 unknown unknown -999.0 -999.0   4197.9300 999.8980 38.82970665 54.44 82.22 27.78 4528261.97 1.0778 1.099540 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 48807.77 48626.49 1.0000 2.48080417 2.159933 12.89 11.21 0.00800000 33150.5 32.11 18.22 0.00800000 52751.6 0.42694809 60.00 32.22 27.78 0.000 48807.77 -26.20 0.00036134 -26.20 0.00000000 0.0000 20.94 0.00766196 21.00 0.00766196 47.2784 28309.06 0.00 49031.57 49031.57 2.48080417 12.80 11.60 0.00800000 33059.8 32.18 18.76 0.00800000 52824.2
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 261222.411 -999.000 12.604378 0.00933026 -999.000 -999.0000 1.00000 1.00000 1023.2828 1004.8586 1.1486 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 12.604378 14.47683153   4197.9300 999.8980 135.60440726 13.34 6.67 6.67 3796949.59 6.8798 6.879797 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 261222.41 209229.94 1.0000 14.47683153 12.604378 25.16 17.47 0.00992108 50558.7 11.03 10.95 0.00850000 32514.5 9.32930750 6.67 13.34 6.67 27554.470 233667.94 31.20 0.01536508 23.13 2.03050000 16.1095 24.00 0.00887321 24.00 0.00887321 45.5368 142458.39 0.00 270206.29 205224.97 14.47683153 25.16 17.98 0.00992108 50558.7 11.31 11.11 0.00814126 31893.9
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 80348.326 80348.326 3.781313 0.00070292 1306.680 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 12.604378 14.47683153   4197.9300 999.8980 38.82970665 54.44 82.22 27.78 4528261.97 1.7744 1.810084 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:50:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 80348.33 80348.33 1.0000 4.34304946 3.781313 -5.52 -5.52 0.00369333 3650.1 12.89 11.21 0.00800000 33150.5 0.70285050 60.00 32.22 27.78 0.000 80348.33 -26.20 0.00036134 -26.20 2.03050000 53.6983 18.46 0.00755760 18.65 0.00766933 54.7503 14817.79 0.00 72908.28 72908.28 4.34304946 2.80 1.52 0.00369333 12069.6 19.39 9.89 0.00369333 28856.9
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 2533061.112 -999.000 118.360409 0.09047507 -999.000 -999.0000 1.00000 1.00000 1023.6427 1004.8586 1.1486 VAV_MID WITH REHEAT FAN Fan:VariableVolume 118.360409 135.94353720   4197.9300 999.8980 135.60440726 13.34 6.67 6.67 3796949.59 66.7131 66.713056 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 2533061.11 1978157.00 1.0000 135.94353720 118.360409 25.26 17.66 0.01011468 51148.3 11.03 10.95 0.00850000 32515.2 90.46584441 6.67 13.34 6.67 258748.064 2274313.05 31.20 0.01536508 23.13 20.30600000 17.1561 24.00 0.00900434 24.00 0.00900434 46.2017 1317272.71 0.00 2618503.46 1942916.94 135.94353720 25.26 18.16 0.01011468 51148.3 11.29 11.10 0.00814412 31886.6
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 817832.280 817832.280 35.508123 0.00715475 13190.660 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 VAV_MID WITH REHEAT FAN Fan:VariableVolume 118.360409 135.94353720   4197.9300 999.8980 38.82970665 54.44 82.22 27.78 4528261.97 18.0606 18.424099 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 817832.28 817832.28 1.0000 40.78306116 35.508123 -7.07 -7.07 0.00337843 1303.3 12.89 11.21 0.00800000 33150.5 7.15402369 60.00 32.22 27.78 0.000 817832.28 -26.20 0.00036134 -26.20 20.30600000 57.1869 18.49 0.00740845 18.34 0.00766451 55.7817 206216.20 0.00 729191.40 729191.40 40.78306116 2.80 1.07 0.00337843 11280.4 20.48 10.03 0.00337843 29160.1
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 407681.494 -999.000 20.132471 0.01456144 -999.000 -999.0000 1.00000 1.00000 1023.1192 1004.8586 1.1486 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 20.132471 23.12326713   4197.9300 999.8980 135.60440726 13.34 6.67 6.67 3796949.59 10.7371 10.737079 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 Sensible 407681.49 329915.18 1.0000 23.12326713 20.132471 25.00 17.35 0.00983306 50170.9 11.05 10.96 0.00850000 32540.1 14.55995296 6.67 13.34 6.67 43411.919 364269.57 31.20 0.01536508 23.13 2.03050000 10.0857 24.00 0.00893778 24.00 0.00893778 45.8653 165070.23 0.00 421890.32 323516.49 23.12326713 25.00 17.85 0.00983306 50170.9 11.33 11.12 0.00814617 31925.6
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 69215.717 69215.717 6.039741 0.00060553 1184.356 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 20.132471 23.12326713   4197.9300 999.8980 38.82970665 54.44 82.22 27.78 4528261.97 1.5285 1.559289 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 69215.72 69215.72 1.0000 6.93698014 6.039741 2.96 2.96 0.00497777 15450.2 12.89 11.21 0.00800000 33150.5 0.60546751 60.00 32.22 27.78 0.000 69215.72 -26.20 0.00036134 -26.20 2.03050000 33.6190 17.73 0.00731578 16.82 0.00768789 61.5817 34622.82 0.00 69570.77 69570.77 6.93698014 2.80 2.80 0.00497777 15288.6 12.69 8.28 0.00497777 25317.5
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 137571.778 -999.000 7.242230 0.00491375 -999.000 -999.0000 1.00000 1.00000 1023.3987 1004.8586 1.1486 CAV_BAS SZVAV FAN Fan:VariableVolume 7.242230 8.31810566   4197.9300 999.8980 135.60440726 13.34 6.67 6.67 3796949.59 3.6232 3.623218 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 137571.78 107200.72 1.0000 8.31810566 7.242230 23.94 17.12 0.00998344 49472.7 11.02 10.94 0.00850000 32504.6 4.91324389 6.67 13.34 6.67 15916.836 121654.94 23.36 0.01535063 20.94 1.20015641 16.5716 24.06 0.00891734 24.00 0.00891734 45.7594 82743.46 0.00 146243.54 107938.81 8.31810566 23.94 17.62 0.00998344 49472.7 11.26 11.11 0.00815743 31891.4
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 100000.000 100000.000 3.185474 0.00087484 2622.251 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 CAV_BAS SZVAV FAN Fan:VariableVolume 7.242230 8.31810566   4197.9300 999.8980 38.82970665 54.44 82.22 27.78 4528261.97 2.2084 2.252797 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 100000.00 100000.00 1.0000 3.65869449 3.185474 -4.34 -8.65 0.00036134 -3462.0 32.11 18.22 0.00800000 52750.5 0.87475438 60.00 32.22 27.78 0.000 100000.00 -26.20 0.00036134 -26.20 1.20015641 37.6759 0.00 0.00036134 22.08 0.00036134 2.1110 0.00 0.00 100071.45 100071.45 3.65869449 12.80 1.98 0.00000000 12887.2 40.02 14.59 0.00000000 40238.9
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes Yes Yes No 457412.793 -999.000 32.852785 0.01633772 -999.000 -999.0000 1.00000 1.00000 1020.8335 1004.8586 1.1486 AIRLOOP DATACENTER BASEMENT SYS11 FAN Fan:VariableVolume 32.852785 37.73325713   4197.9300 999.8980 135.60440726 13.34 6.67 6.67 3796949.59 12.0468 12.046849 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 Sensible 457412.79 450204.00 1.0000 37.73325713 32.852785 27.04 17.04 0.00860349 49121.4 15.00 12.56 0.00850000 36571.1 16.33605851 6.67 13.34 6.67 34106.405 423306.39 31.20 0.01536508 23.13 0.33839277 1.0300 27.00 0.00853305 27.00 0.00853305 36.6651 371638.55 0.00 490747.74 490747.74 37.73325713 27.04 17.53 0.00860349 49121.4 14.30 12.81 0.00860349 36115.7
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes Yes Yes No 100000.000 100000.000 3.185474 0.00087484 2622.251 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 AIRLOOP DATACENTER BASEMENT SYS11 FAN Fan:VariableVolume 32.852785 37.73325713   4197.9300 999.8980 38.82970665 54.44 82.22 27.78 4528261.97 2.2084 2.252797 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 100000.00 100000.00 1.0000 3.65869449 3.185474 -0.27 -0.27 0.00841617 20772.9 29.11 17.24 0.00800000 49691.3 0.87475438 60.00 32.22 27.78 0.000 100000.00 -26.20 0.00036134 -26.20 0.33839277 10.6230 0.00 0.00850000 27.00 0.00850000 36.5206 0.00 0.00 100071.45 100071.45 3.65869449 12.80 1.98 0.00000000 12887.2 40.02 14.59 0.00000000 40238.9
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A No No unknown No 13089.750 10480.439 0.790750 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.0082 1004.8586 1.1486 AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.790752 0.90822253   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 Sensible 6544.88 6350.28 1.0000 0.60548035 0.527167 27.00 17.10 0.00869751 49315.4 14.42 12.33 0.00850000 35978.2 -999.0 -999.00 -999.00 -999.00 0.000 6544.88 26.87 0.01535708 21.94 0.01563234 2.9654 27.00 0.00856320 27.00 0.00856320 36.7909 8955.27 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 27039.507 27039.507 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.790752 0.90822253   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 27039.51 27039.51 1.0000 0.90822253 0.790752 -0.52 -4.75 0.00114674 2346.4 29.11 17.24 0.00800000 49691.3 -999.0 -999.00 -999.00 -999.00 0.000 27039.51 -26.20 0.00036134 -26.20 0.01563234 1.9769 0.00 0.00116258 24.62 0.00116258 5.8178 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A No No unknown No 125948.910 100842.254 7.608570 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.0225 1004.8586 1.1486 AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 7.608574 8.73887186   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 Sensible 62974.46 61031.44 1.0000 5.82591161 5.072380 27.00 17.10 0.00870520 49334.9 14.42 12.33 0.00850000 35978.2 -999.0 -999.00 -999.00 -999.00 0.000 62974.46 26.87 0.01535708 21.94 0.15632344 3.0819 27.00 0.00856566 27.00 0.00856566 36.8014 86166.78 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 260351.495 260351.495 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 7.608574 8.73887186   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 260351.50 260351.50 1.0000 8.73887186 7.608574 -0.54 -4.76 0.00114614 2324.4 29.11 17.24 0.00800000 49691.3 -999.0 -999.00 -999.00 -999.00 0.000 260351.50 -26.20 0.00036134 -26.20 0.15632344 2.0546 0.00 0.00116261 23.26 0.00116261 6.3151 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A No No unknown No 12967.210 10382.326 0.783350 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.0115 1004.8586 1.1486 AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.783349 0.89972004   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 6483.60 6289.20 1.0000 0.59981414 0.522233 27.00 17.10 0.00869928 49323.9 14.42 12.33 0.00850000 35978.2 -999.0 -999.00 -999.00 -999.00 0.000 6483.60 27.07 0.01535744 22.00 0.01563234 2.9934 27.00 0.00856371 27.00 0.00856371 36.7931 8871.42 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 26790.797 26790.797 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.783349 0.89972004   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 26790.80 26790.80 1.0000 0.89972004 0.783349 -0.52 -4.75 0.00114519 2337.6 29.11 17.24 0.00800000 49691.3 -999.0 -999.00 -999.00 -999.00 0.000 26790.80 -26.20 0.00036134 -26.20 0.01563234 1.9956 0.00 0.00116115 21.00 0.00116115 7.2364 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER FixedDryBulb 0.00 12.60 -      
VAV_MID WITH REHEAT_OA_CONTROLLER FixedDryBulb 0.00 118.36 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER FixedDryBulb 0.00 20.13 -      
CAV_BAS_OA_CONTROLLER FixedDryBulb 1.20 7.24 -      
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER DifferentialDryBulb 0.34 32.85 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 2189.83 2655.00 40.67
CORE_BOTTOM 2308.50 2425.50 54.17
CORE_MID 2219.17 3283.33 483.83
CORE_TOP 2949.33 4328.50 1692.00
PERIMETER_BOT_ZN_3 3253.67 4045.50 1689.17
PERIMETER_BOT_ZN_2 3173.33 4111.83 1697.17
PERIMETER_BOT_ZN_1 3218.00 3693.67 1475.83
PERIMETER_BOT_ZN_4 2916.67 3885.50 1196.17
PERIMETER_MID_ZN_3 3257.33 4894.83 2482.50
PERIMETER_MID_ZN_2 3011.83 3821.67 2036.00
PERIMETER_MID_ZN_1 3231.17 4151.67 1841.67
PERIMETER_MID_ZN_4 3351.33 4541.17 2233.50
PERIMETER_TOP_ZN_3 3487.33 5200.17 2921.67
PERIMETER_TOP_ZN_2 3758.00 4660.50 2664.33
PERIMETER_TOP_ZN_1 3406.17 4577.33 2306.50
PERIMETER_TOP_ZN_4 3619.50 4764.00 2664.67
DATACENTER_BOT_ZN_6 5635.50 1133.83 1129.83
DATACENTER_MID_ZN_6 4860.00 692.00 508.50
DATACENTER_TOP_ZN_6 4245.67 1125.83 609.67
DATACENTER_BASEMENT_ZN_6 5917.83 2856.50 2854.83
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5941.67 5281.83
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.83 7.83 0.83 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 1.67 0.00 0.33 0.00
CORE_TOP 26.33 0.00 1.50 0.00
PERIMETER_BOT_ZN_3 49.00 0.00 5.83 0.00
PERIMETER_BOT_ZN_2 50.83 14.00 3.67 14.00
PERIMETER_BOT_ZN_1 55.33 16.17 3.83 16.17
PERIMETER_BOT_ZN_4 17.33 37.83 0.17 21.50
PERIMETER_MID_ZN_3 213.67 0.00 48.00 0.00
PERIMETER_MID_ZN_2 343.50 13.33 41.17 13.33
PERIMETER_MID_ZN_1 167.00 11.83 25.33 11.83
PERIMETER_MID_ZN_4 168.00 21.83 32.17 11.83
PERIMETER_TOP_ZN_3 354.17 0.00 89.33 0.00
PERIMETER_TOP_ZN_2 343.33 9.00 77.17 9.00
PERIMETER_TOP_ZN_1 304.33 8.17 57.50 8.17
PERIMETER_TOP_ZN_4 289.17 21.67 62.50 11.50
DATACENTER_BOT_ZN_6 0.00 136.17 0.00 90.67
DATACENTER_MID_ZN_6 0.00 97.67 0.00 68.50
DATACENTER_TOP_ZN_6 0.00 89.00 0.00 62.50
DATACENTER_BASEMENT_ZN_6 0.00 2.83 0.00 2.83
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 648.00 252.67 118.33 173.17
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.43 149.60 6779.02 0.795 0.000 0.000 0.000
CORE_BOTTOM 56.07 134.35 6849.35 0.755 0.000 0.000 0.000
CORE_MID 56.07 134.35 6849.35 0.617 0.000 0.000 0.000
CORE_TOP 56.07 134.35 6849.35 0.602 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.04 16.87 860.00 1.056 0.063 0.000 0.000
PERIMETER_BOT_ZN_2 4.54 10.87 554.22 1.642 0.065 0.000 0.000
PERIMETER_BOT_ZN_1 7.04 16.87 860.02 1.351 0.063 0.000 0.000
PERIMETER_BOT_ZN_4 4.54 10.87 554.22 1.988 0.066 0.000 0.000
PERIMETER_MID_ZN_3 7.04 16.87 860.00 1.385 0.148 0.000 0.000
PERIMETER_MID_ZN_2 3.97 10.87 554.22 1.622 0.162 0.000 0.000
PERIMETER_MID_ZN_1 7.04 16.87 860.02 1.516 0.148 0.000 0.000
PERIMETER_MID_ZN_4 4.54 10.87 554.22 1.788 0.153 0.000 0.000
PERIMETER_TOP_ZN_3 7.04 16.87 860.00 1.582 0.183 0.000 0.000
PERIMETER_TOP_ZN_2 4.54 10.87 554.22 1.676 0.190 0.000 0.000
PERIMETER_TOP_ZN_1 7.04 16.87 860.02 1.643 0.184 0.000 0.000
PERIMETER_TOP_ZN_4 4.54 10.87 554.22 1.712 0.190 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.60 42.18 1911.37 16.549 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.43 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 56.07 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 56.07 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 56.07 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.04 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.54 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 7.04 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.54 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 7.04 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.97 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 7.04 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.54 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 7.04 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.54 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 7.04 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.54 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.60 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 62.43 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 56.07 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 56.07 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 56.07 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 7.04 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.54 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 7.04 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.54 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 7.04 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.97 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 7.04 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.54 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 7.04 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.54 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 7.04 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.54 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.81 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.60 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1034.72 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 31930320.69 0.00 31930320.69 0.00 31930320.69 37848132.68 4282.16 3227.77 1250.06 93.91
CORE_BOTTOM 31553764.01 0.00 31553764.01 0.00 31553764.01 33990283.35 6315.02 28.11 2416.86 355.13
CORE_MID 0.26E+09 0.00 0.26E+09 0.00 0.26E+09 0.34E+09 6796.38 25.99 1937.63 624.60
CORE_TOP 24604523.61 0.00 24604523.61 0.00 24604523.61 33990283.35 6836.36 21.08 1902.56 380.76
PERIMETER_BOT_ZN_3 5627795.96 0.00 5627795.96 650322.70 6278118.65 4267819.30 3908.66 20.02 4831.32 355.13
PERIMETER_BOT_ZN_2 5626839.55 0.00 5626839.55 433548.17 6060387.71 2750345.05 3790.34 3.99 4965.67 355.13
PERIMETER_BOT_ZN_1 7142969.11 0.00 7142969.11 650322.70 7793291.81 4267912.63 3854.70 5.44 4899.86 355.13
PERIMETER_BOT_ZN_4 6815662.07 0.00 6815662.07 433548.17 7249210.24 2750345.05 3737.66 6.90 5015.44 355.13
PERIMETER_MID_ZN_3 74028932.57 0.00 74028932.57 1525195.93 75554128.50 42678193.03 3801.83 17.03 4941.14 624.60
PERIMETER_MID_ZN_2 51164551.81 0.00 51164551.81 1016796.59 52181348.40 27503450.52 4260.97 18.26 4480.78 1043.82
PERIMETER_MID_ZN_1 80321668.68 0.00 80321668.68 1525195.93 81846864.61 42679126.28 3811.66 11.29 4937.05 624.60
PERIMETER_MID_ZN_4 61252358.51 0.00 61252358.51 1016796.59 62269155.10 27503450.52 3653.99 11.59 5094.43 624.60
PERIMETER_TOP_ZN_3 8166907.85 0.00 8166907.85 1893702.01 10060609.86 4267819.30 4058.57 4.36 4697.07 380.76
PERIMETER_TOP_ZN_2 5559030.15 0.00 5559030.15 1262467.14 6821497.29 2750345.05 4057.58 4.13 4698.30 380.74
PERIMETER_TOP_ZN_1 8454121.78 0.00 8454121.78 1893702.01 10347823.79 4267912.63 4062.60 4.49 4692.92 380.76
PERIMETER_TOP_ZN_4 5678017.03 0.00 5678017.03 1262467.14 6940484.18 2750345.05 4054.75 4.72 4700.53 380.74
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.29E+09 0.00 0.29E+09 0.00 0.29E+09 10671554.30 681.22 1172.00 6906.79 2480.18
Total Facility 0.57E+10 0.00 0.57E+10 59319930.40 0.58E+10 0.50E+10 7312.27 4430.89 8162.47 2973.15


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.4688 0.0000 1.4688 0.0000 1.4688 1.2002 1503.96 3226.84 1212.19
CORE_BOTTOM 1.4081 0.0000 1.4081 0.0000 1.4081 1.0778 3629.41 27.85 2285.74
CORE_MID 11.5258 0.0000 11.5258 0.0000 11.5258 10.7782 4035.86 25.59 1881.54
CORE_TOP 1.1272 0.0000 1.1272 0.0000 1.1272 1.0778 4049.31 20.49 1873.20
PERIMETER_BOT_ZN_3 0.2484 0.0000 0.2484 0.0149 0.2633 0.1353 1278.61 17.86 4646.53
PERIMETER_BOT_ZN_2 0.2490 0.0000 0.2490 0.0100 0.2590 0.0872 1201.54 2.85 4738.61
PERIMETER_BOT_ZN_1 0.3175 0.0000 0.3175 0.0149 0.3324 0.1353 1240.15 4.26 4698.59
PERIMETER_BOT_ZN_4 0.3013 0.0000 0.3013 0.0100 0.3113 0.0872 1183.74 1.67 4757.59
PERIMETER_MID_ZN_3 3.2712 0.0000 3.2712 0.0351 3.3063 1.3533 1251.40 8.10 4683.51
PERIMETER_MID_ZN_2 2.4628 0.0000 2.4628 0.0248 2.4876 0.8721 1214.82 7.52 3811.67
PERIMETER_MID_ZN_1 3.5702 0.0000 3.5702 0.0351 3.6052 1.3533 1250.54 2.62 4689.84
PERIMETER_MID_ZN_4 2.7162 0.0000 2.7162 0.0234 2.7396 0.8721 1192.37 5.46 4745.17
PERIMETER_TOP_ZN_3 0.3736 0.0000 0.3736 0.0435 0.4172 0.1353 1318.89 3.04 4621.08
PERIMETER_TOP_ZN_2 0.2546 0.0000 0.2546 0.0290 0.2836 0.0872 1318.23 2.92 4621.85
PERIMETER_TOP_ZN_1 0.3872 0.0000 0.3872 0.0435 0.4307 0.1353 1321.59 2.77 4618.64
PERIMETER_TOP_ZN_4 0.2601 0.0000 0.2601 0.0290 0.2891 0.0872 1315.98 3.39 4623.63
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 8.5619 0.0000 8.5619 0.0000 8.5619 0.3384 307.64 1171.45 4463.92
Total Facility 251.5845 0.0000 251.5845 1.3774 252.9619 158.4706 4495.27 4382.23 5674.55


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 74885963.70 0.00 74885963.70 48026705.38 3863.10 6.66 4890.24 355.13
VAV_MID WITH REHEAT 0.69E+09 0.00 0.69E+09 0.48E+09 3966.01 9.75 4784.23 624.60
VAV_TOP WITH REHEAT 69207638.33 0.00 69207638.33 48026705.38 4123.02 3.94 4633.03 380.72
CAV_BAS 42012504.48 0.00 42012504.48 37848132.68 4260.85 1.01 4498.14 93.91
AIRLOOP DATACENTER BASEMENT 0.38E+09 0.00 0.38E+09 10671554.30 670.85 0.70 8088.45 2480.06
AIRLOOP DATACENTER BOT 322270.54 0.00 322270.54 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 3222705.41 0.00 3222705.41 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 322270.54 0.00 322270.54 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 3.3301 0.0000 3.3301 1.5229 1230.63 4.06 4708.32
VAV_MID WITH REHEAT 30.7877 0.0000 30.7877 15.2292 1289.29 4.29 4649.42
VAV_TOP WITH REHEAT 3.1696 0.0000 3.1696 1.5229 1363.92 3.13 4575.95
CAV_BAS 1.9326 0.0000 1.9326 1.2002 1490.68 0.55 4451.77
AIRLOOP DATACENTER BASEMENT 11.2948 0.0000 11.2948 0.3384 304.37 0.18 5638.45
AIRLOOP DATACENTER BOT 0.0151 0.0000 0.0151 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1506 0.0000 0.1506 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0151 0.0000 0.0151 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 34.56 3171.72 0.00 0.00 0.00 1938.85 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 98.74 3540.60 0.00 0.00 0.00 1869.16 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 22.67 2916.02 0.00 0.00 0.00 2262.29 0.00 0.00 0.00
CAV_BAS 0.00 3241.49 1391.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 1170.96 6963.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 2.4710 5.4364 0.0000 0.0000 0.0000 2.2661 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 26.6014 46.6823 0.0000 0.0000 0.0000 23.6591 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 2.7100 5.3698 0.0000 0.0000 0.0000 2.2822 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.5835 4.8984 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4468 14.8566 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0206 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2062 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0206 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1343
Defaulted Fields 1287
Fields with Defaults 3878
Autosized Fields 320
Autosizable Fields 465
Autocalculated Fields 223
Autocalculatable Fields 468



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 31516.73 290095.75 28-MAY-05:00 2520439.57 04-AUG-15:30
Electricity:Building 20287.13 234472.87 01-JAN-00:10 1268272.53 03-APR-07:10
Electricity:Zone:BASEMENT 758.19 15076.70 01-JAN-00:10 42602.33 02-JAN-08:10
Electricity:SpaceType:GENERAL 20287.13 234472.87 01-JAN-00:10 1268272.53 03-APR-07:10
InteriorLights:Electricity 5610.74 27216.71 01-JAN-00:10 489900.85 02-JAN-08:10
InteriorLights:Electricity:Zone:BASEMENT 333.79 1619.15 01-JAN-00:10 29144.79 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 5610.74 27216.71 01-JAN-00:10 489900.85 02-JAN-08:10
LightsWired:InteriorLights:Electricity 5610.74 27216.71 01-JAN-00:10 489900.85 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 333.79 1619.15 01-JAN-00:10 29144.79 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 5610.74 27216.71 01-JAN-00:10 489900.85 02-JAN-08:10
Electricity:Zone:CORE_BOTTOM 589.38 5907.35 01-JAN-00:10 43380.70 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 299.77 1454.11 01-JAN-00:10 26174.07 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 299.77 1454.11 01-JAN-00:10 26174.07 02-JAN-08:10
Electricity:Zone:CORE_MID 5893.79 59073.32 01-JAN-00:10 433806.32 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 2997.66 14541.15 01-JAN-00:10 261740.70 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 2997.66 14541.15 01-JAN-00:10 261740.70 02-JAN-08:10
Electricity:Zone:CORE_TOP 589.38 5907.33 01-JAN-00:10 43380.63 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 299.77 1454.11 01-JAN-00:10 26174.07 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 299.77 1454.11 01-JAN-00:10 26174.07 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 74.00 741.75 01-JAN-00:10 5446.97 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 37.64 182.58 01-JAN-00:10 3286.42 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 37.64 182.58 01-JAN-00:10 3286.42 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_2 47.69 478.01 01-JAN-00:10 3510.23 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 24.26 117.66 01-JAN-00:10 2117.89 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 24.26 117.66 01-JAN-00:10 2117.89 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_1 74.01 741.76 01-JAN-00:10 5447.07 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 37.64 182.58 01-JAN-00:10 3286.49 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 37.64 182.58 01-JAN-00:10 3286.49 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_4 47.69 478.01 01-JAN-00:10 3510.22 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 24.26 117.66 01-JAN-00:10 2117.89 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 24.26 117.66 01-JAN-00:10 2117.89 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_3 740.04 7417.49 01-JAN-00:10 54469.67 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 376.39 1825.79 01-JAN-00:10 32864.16 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 376.39 1825.79 01-JAN-00:10 32864.16 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_2 476.91 4780.12 01-JAN-00:10 35102.33 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 242.56 1176.61 01-JAN-00:10 21178.91 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 242.56 1176.61 01-JAN-00:10 21178.91 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_1 740.05 7417.62 01-JAN-00:10 54470.72 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 376.39 1825.83 01-JAN-00:10 32864.88 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 376.39 1825.83 01-JAN-00:10 32864.88 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_4 476.91 4780.09 01-JAN-00:10 35102.24 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 242.56 1176.61 01-JAN-00:10 21178.91 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 242.56 1176.61 01-JAN-00:10 21178.91 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_3 74.00 741.75 01-JAN-00:10 5446.97 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 37.64 182.58 01-JAN-00:10 3286.42 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 37.64 182.58 01-JAN-00:10 3286.42 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_2 47.69 478.01 01-JAN-00:10 3510.23 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 24.26 117.66 01-JAN-00:10 2117.89 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 24.26 117.66 01-JAN-00:10 2117.89 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_1 74.01 741.76 01-JAN-00:10 5447.07 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 37.64 182.58 01-JAN-00:10 3286.49 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 37.64 182.58 01-JAN-00:10 3286.49 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_4 47.69 478.01 01-JAN-00:10 3510.22 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 24.26 117.66 01-JAN-00:10 2117.89 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 24.26 117.66 01-JAN-00:10 2117.89 02-JAN-08:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7588.97 95364.66 01-JAN-00:10 387850.11 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 94.11 456.53 01-JAN-00:10 8217.58 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 94.11 456.53 01-JAN-00:10 8217.58 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 162.23 1989.09 01-JAN-00:10 8523.21 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 8.35 40.49 01-JAN-00:10 728.78 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 8.35 40.49 01-JAN-00:10 728.78 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1622.27 19890.94 01-JAN-00:10 85232.07 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 83.47 404.88 01-JAN-00:10 7287.84 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 83.47 404.88 01-JAN-00:10 7287.84 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 162.23 1989.09 01-JAN-00:10 8523.21 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 8.35 40.49 01-JAN-00:10 728.78 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 8.35 40.49 01-JAN-00:10 728.78 02-JAN-08:10
InteriorEquipment:Electricity 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:HVAC 4441.73 33075.97 14-MAY-05:50 374397.01 17-APR-15:30
ExteriorEquipment:Electricity 2623.11 22123.82 01-JAN-00:10 235096.12 03-APR-07:20
Transformer:ExteriorEquipment:Electricity 56.04 979.82 01-JAN-00:10 3543.78 03-APR-07:20
ElectricityPurchased:Facility 31516.73 290095.75 28-MAY-05:00 2520439.57 04-AUG-15:30
ElectricityPurchased:Plant 31516.73 290095.75 28-MAY-05:00 2520439.57 04-AUG-15:30
Cogeneration:ElectricityPurchased 31516.73 290095.75 28-MAY-05:00 2520439.57 04-AUG-15:30
General:Cogeneration:ElectricityPurchased 31516.73 290095.75 28-MAY-05:00 2520439.57 04-AUG-15:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 31516.73 290095.75 28-MAY-05:00 2520439.57 04-AUG-15:30
ElectricityNet:Plant 31516.73 290095.75 28-MAY-05:00 2520439.57 04-AUG-15:30
Cogeneration:ElectricityNet 31516.73 290095.75 28-MAY-05:00 2520439.57 04-AUG-15:30
General:Cogeneration:ElectricityNet 31516.73 290095.75 28-MAY-05:00 2520439.57 04-AUG-15:30
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 1965.43 0.00 06-JAN-00:30 515044.72 04-AUG-15:30
General:Cooling:Electricity 1965.43 0.00 06-JAN-00:30 515044.72 04-AUG-15:30
Fans:Electricity 2912.16 26021.95 01-JAN-10:40 305773.99 04-AUG-15:30
General:Fans:Electricity 2912.16 26021.95 01-JAN-10:40 305773.99 04-AUG-15:30
ExteriorLights:Electricity 1006.00 0.00 01-JAN-08:00 64082.80 01-JAN-00:10
General:ExteriorLights:Electricity 1006.00 0.00 01-JAN-08:00 64082.80 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 2505.76 19200.00 01-JAN-00:10 229608.34 02-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 61.31 1944.00 01-JAN-00:10 1944.00 01-JAN-00:10
Humidifier:Electricity 1053.07 0.00 18-MAR-13:40 100000.00 25-MAR-15:20
General:Humidifier:Electricity 1053.07 0.00 18-MAR-13:40 100000.00 25-MAR-15:20
Electricity:Plant 3214.80 0.00 12-JAN-00:10 686412.04 04-AUG-13:00
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:Electricity 484.77 0.00 01-JAN-00:10 60480.04 21-FEB-12:30
Water Heater:WaterSystems:Electricity 484.77 0.00 01-JAN-00:10 60480.04 21-FEB-12:30
HeatRejection:Electricity 176.75 0.00 01-JAN-00:10 58522.13 11-JUN-15:10
General:HeatRejection:Electricity 176.75 0.00 01-JAN-00:10 58522.13 11-JUN-15:10
Pumps:Electricity 1008.31 0.00 12-JAN-00:10 102278.78 04-AUG-15:30
General:Pumps:Electricity 1008.31 0.00 12-JAN-00:10 102278.78 04-AUG-15:30
WIRED_LTG_ELECTRICITY 157.66 0.00 01-JAN-00:10 13766.21 02-JAN-08:20
WIRED_INT_EQUIP 5334.97 88964.76 31-MAR-23:10 305206.10 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 7173.53 0.00 01-JAN-00:40 3142160.44 30-JAN-07:30
NaturalGas:HVAC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:NaturalGas 7173.53 0.00 01-JAN-00:40 3142160.44 30-JAN-07:30
General:Heating:NaturalGas 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
NaturalGas:Plant 7173.53 0.00 01-JAN-00:40 3142160.44 30-JAN-07:30
Boiler:Heating:NaturalGas 7173.53 0.00 01-JAN-00:40 3142160.44 30-JAN-07:30


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 8725.08 0.00 01-JAN-00:20 3035141.26 04-AUG-15:30
PlantLoopCoolingDemand:HVAC 8725.08 0.00 01-JAN-00:20 3035141.26 04-AUG-15:30
CoolingCoils:PlantLoopCoolingDemand 8725.08 0.00 01-JAN-00:20 3035141.26 04-AUG-15:30


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 8977.76 0.00 20-MAR-00:40 0.00 07-SEP-14:20
Water:HVAC 391.74 0.00 18-MAR-13:40 0.00 06-APR-14:30
Humidifier:Water 391.74 0.00 18-MAR-13:40 0.00 06-APR-14:30
General:Humidifier:Water 391.74 0.00 18-MAR-13:40 0.00 06-APR-14:30
MainsWater:Facility 8977.76 0.00 20-MAR-00:40 0.00 07-SEP-14:20
MainsWater:HVAC 391.74 0.00 18-MAR-13:40 0.00 06-APR-14:30
Humidifier:MainsWater 391.74 0.00 18-MAR-13:40 0.00 06-APR-14:30
General:Humidifier:MainsWater 391.74 0.00 18-MAR-13:40 0.00 06-APR-14:30
Water:Plant 8586.02 0.00 01-JAN-00:10 0.00 07-SEP-14:20
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 19-APR-11:30
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 19-APR-11:30
MainsWater:Plant 8586.02 0.00 01-JAN-00:10 0.00 07-SEP-14:20
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 19-APR-11:30
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 19-APR-11:30
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 6305.85 0.00 01-JAN-00:10 0.00 07-SEP-14:20
General:HeatRejection:Water 6305.85 0.00 01-JAN-00:10 0.00 07-SEP-14:20
HeatRejection:MainsWater 6305.85 0.00 01-JAN-00:10 0.00 07-SEP-14:20
General:HeatRejection:MainsWater 6305.85 0.00 01-JAN-00:10 0.00 07-SEP-14:20


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 70819.02 100530.63 10-JAN-00:50 14746100.91 04-AUG-15:30
EnergyTransfer:Building 21112.43 87381.63 11-JAN-22:30 2156948.42 11-DEC-05:10
EnergyTransfer:Zone:BASEMENT 651.33 0.00 01-JAN-00:10 82894.31 05-SEP-05:10
Heating:EnergyTransfer 2277.14 0.00 07-FEB-22:10 1927492.62 30-JAN-05:10
Heating:EnergyTransfer:Zone:BASEMENT 1.31 0.00 01-JAN-00:10 27625.22 02-FEB-07:40
General:Heating:EnergyTransfer 2277.14 0.00 07-FEB-22:10 1927492.62 30-JAN-05:10
General:Heating:EnergyTransfer:Zone:BASEMENT 1.31 0.00 01-JAN-00:10 27625.22 02-FEB-07:40
Cooling:EnergyTransfer 18835.29 80561.81 30-JAN-05:10 1938973.38 04-AUG-15:30
Cooling:EnergyTransfer:Zone:BASEMENT 650.02 0.00 01-JAN-00:10 82564.03 05-SEP-05:10
General:Cooling:EnergyTransfer 18835.29 80561.81 30-JAN-05:10 1938973.38 04-AUG-15:30
General:Cooling:EnergyTransfer:Zone:BASEMENT 650.02 0.00 01-JAN-00:10 82564.03 05-SEP-05:10
EnergyTransfer:Zone:CORE_BOTTOM 582.40 0.00 01-JAN-00:10 57063.05 14-AUG-15:50
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.01 0.00 01-JAN-00:10 10533.46 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.01 0.00 01-JAN-00:10 10533.46 06-FEB-06:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 582.39 0.00 01-JAN-00:10 57063.05 14-AUG-15:50
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 582.39 0.00 01-JAN-00:10 57063.05 14-AUG-15:50
EnergyTransfer:Zone:CORE_MID 4623.92 0.00 01-JAN-00:40 567759.46 02-JAN-06:10
Heating:EnergyTransfer:Zone:CORE_MID 29.95 0.00 01-JAN-00:20 567759.46 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:CORE_MID 29.95 0.00 01-JAN-00:20 567759.46 02-JAN-06:10
Cooling:EnergyTransfer:Zone:CORE_MID 4593.97 0.00 01-JAN-00:40 495605.76 30-JUN-16:00
General:Cooling:EnergyTransfer:Zone:CORE_MID 4593.97 0.00 01-JAN-00:40 495605.76 30-JUN-16:00
EnergyTransfer:Zone:CORE_TOP 447.03 0.00 01-JAN-00:40 109071.36 30-JAN-05:10
Heating:EnergyTransfer:Zone:CORE_TOP 48.95 0.00 01-JAN-00:40 109071.36 30-JAN-05:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 48.95 0.00 01-JAN-00:40 109071.36 30-JAN-05:10
Cooling:EnergyTransfer:Zone:CORE_TOP 398.08 0.00 01-JAN-00:20 61703.34 04-AUG-15:20
General:Cooling:EnergyTransfer:Zone:CORE_TOP 398.08 0.00 01-JAN-00:20 61703.34 04-AUG-15:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 89.59 0.00 01-JAN-00:10 22287.57 30-JAN-05:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 17.23 0.00 01-JAN-00:10 22287.57 30-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 17.23 0.00 01-JAN-00:10 22287.57 30-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 72.37 0.00 01-JAN-00:10 12627.97 26-JUN-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 72.37 0.00 01-JAN-00:10 12627.97 26-JUN-14:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 79.56 0.00 01-JAN-00:10 16154.49 02-AUG-08:40
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 11.21 0.00 01-JAN-00:10 15539.50 30-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 11.21 0.00 01-JAN-00:10 15539.50 30-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 68.35 0.00 01-JAN-00:10 16154.49 02-AUG-08:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 68.35 0.00 01-JAN-00:10 16154.49 02-AUG-08:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 120.92 0.00 01-JAN-00:10 25742.76 07-SEP-12:50
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 15.57 0.00 01-JAN-00:10 23109.21 30-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 15.57 0.00 01-JAN-00:10 23109.21 30-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 105.35 0.00 01-JAN-00:10 25742.76 07-SEP-12:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 105.35 0.00 01-JAN-00:10 25742.76 07-SEP-12:50
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 102.75 0.00 01-JAN-00:10 21213.67 02-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 4.62 0.00 01-JAN-00:10 13430.14 30-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 4.62 0.00 01-JAN-00:10 13430.14 30-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 98.13 0.00 01-JAN-00:10 21213.67 02-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 98.13 0.00 01-JAN-00:10 21213.67 02-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 1131.24 0.00 01-JAN-00:40 320203.07 19-JAN-04:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 529.73 0.00 01-JAN-00:40 320203.07 19-JAN-04:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 529.73 0.00 01-JAN-00:40 320203.07 19-JAN-04:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 601.51 0.00 01-JAN-00:20 118501.11 26-JUN-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 601.51 0.00 01-JAN-00:20 118501.11 26-JUN-14:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 847.46 0.00 01-JAN-00:40 218354.00 09-DEC-05:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 301.83 0.00 01-JAN-00:40 218354.00 09-DEC-05:40
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 301.83 0.00 01-JAN-00:40 218354.00 09-DEC-05:40
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 545.64 0.00 01-JAN-00:20 166816.57 02-AUG-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 545.64 0.00 01-JAN-00:20 166816.57 02-AUG-09:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1351.15 0.00 01-JAN-00:40 311886.38 19-JAN-04:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 359.45 0.00 01-JAN-00:40 311886.38 19-JAN-04:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 359.45 0.00 01-JAN-00:40 311886.38 19-JAN-04:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 991.70 0.00 01-JAN-00:20 269526.32 07-SEP-13:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 991.70 0.00 01-JAN-00:20 269526.32 07-SEP-13:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 905.48 0.00 01-JAN-00:40 219612.71 09-DEC-05:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 268.91 0.00 01-JAN-00:40 219612.71 09-DEC-05:40
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 268.91 0.00 01-JAN-00:40 219612.71 09-DEC-05:40
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 636.57 0.00 01-JAN-00:20 187316.45 02-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 636.57 0.00 01-JAN-00:20 187316.45 02-AUG-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 151.99 0.00 01-JAN-00:40 43135.23 09-DEC-05:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 92.76 0.00 01-JAN-00:40 43135.23 09-DEC-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 92.76 0.00 01-JAN-00:40 43135.23 09-DEC-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 59.23 0.00 01-JAN-00:20 13569.14 26-JUN-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 59.23 0.00 01-JAN-00:20 13569.14 26-JUN-14:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 109.93 0.00 01-JAN-00:40 27988.71 09-DEC-05:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 54.88 0.00 01-JAN-00:40 27988.71 09-DEC-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 54.88 0.00 01-JAN-00:40 27988.71 09-DEC-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 55.05 0.00 01-JAN-00:20 16640.09 26-JUN-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 55.05 0.00 01-JAN-00:20 16640.09 26-JUN-09:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 165.23 0.00 01-JAN-00:40 42269.05 09-DEC-05:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 69.76 0.00 01-JAN-00:40 42269.05 09-DEC-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 69.76 0.00 01-JAN-00:40 42269.05 09-DEC-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 95.47 0.00 01-JAN-00:20 28182.79 07-SEP-13:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 95.47 0.00 01-JAN-00:20 28182.79 07-SEP-13:10
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 107.57 0.00 01-JAN-00:40 27993.10 09-DEC-05:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 47.05 0.00 01-JAN-00:40 27993.10 09-DEC-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 47.05 0.00 01-JAN-00:40 27993.10 09-DEC-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 60.52 0.00 01-JAN-00:20 19675.32 02-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 60.52 0.00 01-JAN-00:20 19675.32 02-AUG-16:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 77.43 0.00 01-JAN-00:10 10098.00 04-AUG-15:30
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 5.53 0.00 01-JAN-00:10 9503.70 30-JAN-06:10
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 5.53 0.00 01-JAN-00:10 9503.70 30-JAN-06:10
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 71.90 0.00 01-JAN-00:10 10098.00 04-AUG-15:30
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 71.90 0.00 01-JAN-00:10 10098.00 04-AUG-15:30
EnergyTransfer:Zone:MIDFLOOR_PLENUM 820.44 0.00 01-JAN-00:40 233188.19 02-JAN-06:20
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 227.02 0.00 01-JAN-00:40 233188.19 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 227.02 0.00 01-JAN-00:40 233188.19 02-JAN-06:20
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 593.43 0.00 01-JAN-00:10 107759.34 11-NOV-05:30
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 593.43 0.00 01-JAN-00:10 107759.34 11-NOV-05:30
EnergyTransfer:Zone:TOPFLOOR_PLENUM 263.86 0.00 01-JAN-00:40 71051.08 30-JAN-05:10
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 168.04 0.00 01-JAN-00:40 71051.08 30-JAN-05:10
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 168.04 0.00 01-JAN-00:40 71051.08 30-JAN-05:10
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 95.82 0.00 01-JAN-00:10 35257.58 30-JUN-13:50
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 95.82 0.00 01-JAN-00:10 35257.58 30-JUN-13:50
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 128.20 3.59 01-JAN-02:20 8484.50 29-AUG-17:40
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.62 0.00 01-JAN-01:50 1390.59 31-JAN-00:40
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.62 0.00 01-JAN-01:50 1390.59 31-JAN-00:40
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 127.58 0.00 01-JAN-00:20 8484.50 29-AUG-17:40
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 127.58 0.00 01-JAN-00:20 8484.50 29-AUG-17:40
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1116.20 5.20 19-JAN-19:10 81274.07 29-AUG-17:40
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 18.12 0.00 02-JAN-13:10 13571.40 16-JAN-18:00
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 18.12 0.00 02-JAN-13:10 13571.40 16-JAN-18:00
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1098.08 0.00 01-JAN-00:10 81274.07 29-AUG-17:40
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1098.08 0.00 01-JAN-00:10 81274.07 29-AUG-17:40
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 98.92 0.22 24-JAN-12:50 8229.25 29-AUG-17:40
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 2.97 0.00 02-JAN-12:50 1429.23 30-JAN-23:20
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 2.97 0.00 02-JAN-12:50 1429.23 30-JAN-23:20
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 95.95 0.00 01-JAN-00:10 8229.25 29-AUG-17:40
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 95.95 0.00 01-JAN-00:10 8229.25 29-AUG-17:40
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7139.83 80390.90 30-JAN-06:50 389863.52 12-APR-14:00
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 1.64 0.00 01-JAN-00:10 4042.32 05-JUN-01:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 1.64 0.00 01-JAN-00:10 4042.32 05-JUN-01:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7138.18 80390.90 30-JAN-06:50 389863.52 12-APR-14:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7138.18 80390.90 30-JAN-06:50 389863.52 12-APR-14:00
PlantLoopHeatingDemand:Facility 5539.79 0.00 01-JAN-00:40 2524409.38 30-JAN-07:30
PlantLoopHeatingDemand:Plant 479.24 0.00 01-JAN-00:10 59652.47 21-FEB-12:10
WaterSystems:PlantLoopHeatingDemand 479.24 0.00 01-JAN-00:10 59652.47 21-FEB-12:10
General:WaterSystems:PlantLoopHeatingDemand 479.24 0.00 01-JAN-00:10 59652.47 21-FEB-12:10
EnergyTransfer:HVAC 15530.18 2.97 30-JAN-22:10 3151635.41 04-AUG-15:30
HeatingCoils:EnergyTransfer 5060.55 0.00 01-JAN-00:40 2504667.12 30-JAN-07:30
PlantLoopHeatingDemand:HVAC 5060.55 0.00 01-JAN-00:40 2504667.12 30-JAN-07:30
HeatingCoils:PlantLoopHeatingDemand 5060.55 0.00 01-JAN-00:40 2504667.12 30-JAN-07:30
CoolingCoils:EnergyTransfer 10469.63 0.00 06-JAN-00:30 3151635.41 04-AUG-15:30
EnergyTransfer:Plant 34176.41 0.00 12-JAN-00:10 9655492.13 04-AUG-15:30
LoopToLoop:EnergyTransfer 8984.32 0.00 01-JAN-00:20 3035264.83 04-AUG-15:30
WaterSystems:EnergyTransfer 479.24 0.00 01-JAN-00:10 59652.47 21-FEB-12:10
WaterUse:WaterSystems:EnergyTransfer 479.24 0.00 01-JAN-00:10 59652.47 21-FEB-12:10
Boilers:EnergyTransfer 5032.59 0.00 01-JAN-00:40 2459808.16 30-JAN-07:30
Chillers:EnergyTransfer 9067.64 0.00 01-JAN-00:20 3051598.03 04-AUG-15:30
HeatRejection:EnergyTransfer 10612.61 0.00 01-JAN-00:20 3533052.13 04-AUG-15:30
General:HeatRejection:EnergyTransfer 10612.61 0.00 01-JAN-00:20 3533052.13 04-AUG-15:30
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 1.311 -650.016 0.000 0.000 96.186 333.789 424.397 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -205.668
CORE_BOTTOM 0.000 0.000 0.015 -582.386 0.000 0.000 84.261 299.766 289.614 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -91.270
CORE_MID 0.000 0.000 29.952 -4593.957 0.000 0.000 864.951 2997.664 2896.128 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -2194.737
CORE_TOP 0.000 0.000 48.951 -398.076 0.000 0.000 91.424 299.766 289.613 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -331.678
PERIMETER_BOT_ZN_3 0.000 0.000 17.225 -72.369 0.000 0.000 11.517 37.639 36.365 25.850 0.000 0.108 81.686 0.000 -125.235 0.000 -12.788 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 11.209 -68.352 0.000 0.000 7.440 24.256 23.435 53.553 0.000 0.081 32.377 0.000 -75.528 0.000 -8.469 0.000
PERIMETER_BOT_ZN_1 0.000 0.000 15.569 -105.349 0.000 0.000 11.289 37.639 36.366 110.320 0.000 0.095 14.655 0.000 -107.736 0.000 -12.849 -0.001
PERIMETER_BOT_ZN_4 0.000 0.000 4.616 -98.134 0.000 0.000 7.399 24.256 23.435 55.407 0.000 0.060 76.358 0.000 -84.346 0.000 -9.052 0.000
PERIMETER_MID_ZN_3 0.000 0.000 529.729 -601.508 0.000 0.000 119.652 376.387 363.654 277.576 0.000 3.353 387.556 0.000 -1181.060 0.000 -275.339 -0.017
PERIMETER_MID_ZN_2 0.000 0.000 301.825 -545.634 0.000 0.000 55.449 242.558 234.352 532.164 0.000 1.773 88.386 0.000 -723.866 0.000 -187.006 -0.003
PERIMETER_MID_ZN_1 0.000 0.000 359.445 -991.698 0.000 0.000 115.333 376.395 363.660 1097.180 0.000 2.333 18.421 0.000 -1053.544 0.000 -287.525 -0.000
PERIMETER_MID_ZN_4 0.000 0.000 268.907 -636.571 0.000 0.000 76.587 242.558 234.351 566.868 0.000 1.572 209.861 0.000 -773.776 0.000 -190.355 -0.001
PERIMETER_TOP_ZN_3 0.000 0.000 92.763 -59.232 0.000 0.000 12.157 37.639 36.365 28.704 0.000 0.454 0.000 0.000 -112.828 0.000 -32.948 -3.073
PERIMETER_TOP_ZN_2 0.000 0.000 54.881 -55.045 0.000 0.000 7.648 24.256 23.435 54.177 0.000 0.226 0.000 0.000 -69.168 0.000 -22.339 -18.070
PERIMETER_TOP_ZN_1 0.000 0.000 69.755 -95.472 0.000 0.000 11.788 37.639 36.366 110.958 0.000 0.316 0.000 0.000 -99.696 0.000 -34.113 -37.541
PERIMETER_TOP_ZN_4 0.000 0.000 47.055 -60.516 0.000 0.000 7.722 24.256 23.435 56.755 0.000 0.192 0.000 0.000 -74.370 0.000 -22.884 -1.645
DATACENTER_BOT_ZN_6 0.000 0.000 0.617 -127.581 0.000 0.000 0.941 8.347 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -36.204
DATACENTER_MID_ZN_6 0.000 0.000 18.115 -1098.081 0.000 0.000 9.437 83.466 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -551.743
DATACENTER_TOP_ZN_6 0.000 0.000 2.970 -95.948 0.000 0.000 0.948 8.347 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -70.197
DATACENTER_BASEMENT_ZN_6 0.000 0.000 1.641 -7138.003 0.000 0.000 22.796 94.114 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -475.405
GROUNDFLOOR_PLENUM 5.532 -71.901 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.171 94.588 0.000 0.000 0.000 -28.390 0.000
MIDFLOOR_PLENUM 227.016 -593.424 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 3.518 842.419 0.000 0.000 0.000 -479.529 -0.009
TOPFLOOR_PLENUM 168.039 -95.817 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.217 0.000 0.000 0.000 0.000 -48.652 -23.786
Total Facility 400.587 -761.142 1876.551 -18073.928 0.000 0.000 1614.923 5610.736 14676.396 2969.512 0.000 14.468 1846.308 0.000 -4481.154 0.000 -1652.241 -4041.049


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 23-OCT-03:01 0.00 0.00 0.00 -137632.77 0.00 0.00 0.00 1619.15 13457.54 0.00 0.00 0.00 122556.07 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 15-AUG-04:11 0.00 0.00 0.00 -117377.90 0.00 0.00 0.00 2908.23 5937.65 0.00 0.00 0.00 108532.03 0.00 -0.00 0.00 0.00 0.00
CORE_MID 29-JUN-04:11 0.00 0.00 0.00 -1075687.10 0.00 0.00 0.00 29082.30 59376.23 0.00 0.00 0.00 987228.57 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 03-AUG-04:01 0.00 0.00 0.00 -129386.33 0.00 0.00 0.00 2908.23 5937.62 0.00 0.00 0.00 120540.47 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 25-JUN-18:31 0.00 0.00 0.00 -19430.23 0.00 0.00 0.00 182.58 559.17 7387.65 0.00 180.65 11120.18 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 02-JUL-08:41 0.00 0.00 0.00 -33122.56 0.00 0.00 18.36 117.66 464.11 20374.18 0.00 0.00 12248.04 0.00 -0.00 0.00 -99.80 0.00
PERIMETER_BOT_ZN_1 29-OCT-13:21 0.00 0.00 0.00 -35981.78 0.00 0.00 35.82 182.58 720.19 28730.03 0.00 0.00 7417.36 0.00 -0.00 0.00 -1104.20 0.00
PERIMETER_BOT_ZN_4 02-JUL-16:41 0.00 0.00 0.00 -43243.12 0.00 0.00 13.15 117.66 464.11 21173.10 0.00 0.00 21511.34 0.00 -0.00 0.00 -36.23 0.00
PERIMETER_MID_ZN_3 26-JUN-14:30 0.00 0.00 0.00 -118499.07 0.00 0.00 11143.82 32864.16 21605.52 86401.05 0.00 1491.13 0.00 0.00 -0.00 0.00 0.00 -35006.61
PERIMETER_MID_ZN_2 30-JUL-09:21 0.00 0.00 0.00 -341983.15 0.00 0.00 187.09 1176.61 4641.14 176159.60 0.00 0.00 161482.54 0.00 -0.00 0.00 -1663.82 0.00
PERIMETER_MID_ZN_1 01-OCT-13:41 0.00 0.00 0.00 -456686.07 0.00 0.00 318.72 1825.83 7201.95 276167.83 0.00 0.00 183832.36 0.00 -0.00 0.00 -12660.61 0.00
PERIMETER_MID_ZN_4 14-MAY-17:01 0.00 0.00 0.00 -370229.66 0.00 0.00 0.00 1176.61 3603.49 193229.23 0.00 0.00 174658.18 0.00 -0.00 0.00 -2437.83 0.00
PERIMETER_TOP_ZN_3 25-JUN-17:41 0.00 0.00 0.00 -15667.15 0.00 0.00 0.00 182.58 559.17 7188.22 0.00 854.67 6882.52 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 25-JUN-08:21 0.00 0.00 0.00 -38717.30 0.00 0.00 19.19 117.66 464.11 20832.77 0.00 0.00 17669.19 0.00 -0.00 0.00 -385.63 0.00
PERIMETER_TOP_ZN_1 17-SEP-13:31 0.00 0.00 0.00 -57709.87 0.00 0.00 30.76 182.58 720.19 23815.72 0.00 0.00 33336.27 0.00 -0.00 0.00 -375.67 0.00
PERIMETER_TOP_ZN_4 25-JUN-17:01 0.00 0.00 0.00 -44605.34 0.00 0.00 0.00 117.66 360.35 21311.39 0.00 116.03 22699.92 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 04-FEB-10:31 0.00 0.00 0.00 -10396.54 0.00 0.00 14.32 242.93 3897.21 0.00 0.00 0.00 6242.08 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 04-FEB-10:31 0.00 0.00 0.00 -99824.88 0.00 0.00 185.52 2429.28 38972.11 0.00 0.00 0.00 58237.97 0.00 -0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 26-NOV-08:11 0.00 0.00 0.00 -9246.38 0.00 0.00 3.16 40.49 5845.82 0.00 0.00 0.00 3356.91 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 24-MAR-15:52 0.00 0.00 0.00 -521569.93 0.00 0.00 2733.21 8217.58 284724.39 0.00 0.00 0.00 225894.74 0.00 -0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 06-JAN-04:11 0.00 -19776.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22587.00 0.00 -0.00 0.00 -2810.51 0.00
MIDFLOOR_PLENUM 09-DEC-02:12 0.00 -267151.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 441353.67 0.00 -0.00 0.00 -174201.67 0.00
TOPFLOOR_PLENUM 30-JUN-13:50 0.00 -35256.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 68.78 35187.92 0.00 -0.00 0.00 0.00 0.00
Total Facility 18-JUL-05:01 0.00 23075.58 0.00 -2177088.91 0.00 0.00 16533.22 54433.43 497997.76 16673.32 0.00 0.00 1626080.81 0.00 -48790.04 0.00 -8915.16 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 03-FEB-07:08 0.00 0.00 92597.73 0.00 0.00 0.00 2208.58 9714.93 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -117978.78
CORE_BOTTOM 06-FEB-06:01 0.00 0.00 23948.39 0.00 0.00 0.00 1161.27 2908.23 7647.39 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -35665.28
CORE_MID 02-JAN-04:01 0.00 0.00 695322.54 0.00 0.00 0.00 0.00 14541.15 59376.23 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -769239.92
CORE_TOP 30-JAN-03:21 0.00 0.00 134329.20 0.00 0.00 0.00 0.00 1454.11 5937.62 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -141720.94
PERIMETER_BOT_ZN_3 02-FEB-04:11 0.00 0.00 27298.27 0.00 0.00 0.00 0.00 182.58 745.56 0.00 0.00 0.00 0.00 0.00 -14951.66 0.00 -2202.11 -11072.64
PERIMETER_BOT_ZN_2 02-FEB-04:11 0.00 0.00 23520.65 0.00 0.00 0.00 0.00 117.66 480.47 0.00 0.00 0.00 0.00 0.00 -9581.74 0.00 -1472.71 -13064.34
PERIMETER_BOT_ZN_1 02-FEB-04:11 0.00 0.00 30318.86 0.00 0.00 0.00 0.00 182.58 745.57 0.00 0.00 0.00 0.00 0.00 -14385.48 0.00 -2207.07 -14654.47
PERIMETER_BOT_ZN_4 02-FEB-04:11 0.00 0.00 22875.88 0.00 0.00 0.00 0.00 117.66 480.46 0.00 0.00 0.00 0.00 0.00 -10303.78 0.00 -1524.25 -11645.98
PERIMETER_MID_ZN_3 09-DEC-02:11 0.00 0.00 423704.60 0.00 0.00 0.00 0.00 1825.79 5591.71 0.00 0.00 0.00 0.00 0.00 -115113.95 0.00 -93654.50 -222353.64
PERIMETER_MID_ZN_2 09-DEC-02:11 0.00 0.00 304282.33 0.00 0.00 0.00 0.00 1176.61 3603.51 0.00 0.00 0.00 0.00 0.00 -72260.38 0.00 -62901.49 -173900.57
PERIMETER_MID_ZN_1 09-DEC-02:11 0.00 0.00 407781.31 0.00 0.00 0.00 0.00 1825.83 5591.79 0.00 0.00 0.00 0.00 0.00 -109212.05 0.00 -94865.50 -211121.39
PERIMETER_MID_ZN_4 09-DEC-02:11 0.00 0.00 319705.24 0.00 0.00 0.00 0.00 1176.61 3603.49 0.00 0.00 0.00 0.00 0.00 -77411.02 0.00 -63459.95 -183614.36
PERIMETER_TOP_ZN_3 09-DEC-02:61 0.00 0.00 56190.33 0.00 0.00 0.00 0.00 182.58 559.17 0.00 0.00 0.00 0.00 0.00 -11186.74 0.00 -12213.69 -33531.65
PERIMETER_TOP_ZN_2 09-DEC-02:61 0.00 0.00 36444.86 0.00 0.00 0.00 0.00 117.66 360.35 0.00 0.00 0.00 0.00 0.00 -6999.37 0.00 -8135.43 -21788.07
PERIMETER_TOP_ZN_1 09-DEC-02:61 0.00 0.00 55003.51 0.00 0.00 0.00 0.00 182.58 559.18 0.00 0.00 0.00 0.00 0.00 -10532.15 0.00 -12245.88 -32967.24
PERIMETER_TOP_ZN_4 09-DEC-02:61 0.00 0.00 36636.07 0.00 0.00 0.00 0.00 117.66 360.35 0.00 0.00 0.00 0.00 0.00 -7540.52 0.00 -8191.33 -21382.22
DATACENTER_BOT_ZN_6 26-NOV-03:02 0.00 0.00 1673.39 0.00 0.00 0.00 0.00 40.49 5845.82 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -7559.69
DATACENTER_MID_ZN_6 26-NOV-03:02 0.00 0.00 14576.39 0.00 0.00 0.00 0.00 404.88 58458.17 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -73439.43
DATACENTER_TOP_ZN_6 29-JAN-17:21 0.00 0.00 1446.71 0.00 0.00 0.00 6.23 40.49 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -3442.04
DATACENTER_BASEMENT_ZN_6 05-JUN-01:01 0.00 0.00 39816.80 0.00 0.00 0.00 0.00 456.53 189816.26 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -230089.59
GROUNDFLOOR_PLENUM 16-APR-15:31 14387.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 548.87 0.00 0.00 -0.00 0.00 0.00 -14936.21
MIDFLOOR_PLENUM 02-JAN-06:12 266296.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -11019.71 -255276.50
TOPFLOOR_PLENUM 02-FEB-05:31 77369.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -6416.40 -70953.59
Total Facility 11-DEC-05:21 -415139.41 521003.64 2267868.41 -521003.64 0.00 0.00 0.00 54433.43 587299.42 0.00 0.00 0.00 0.00 0.00 -446133.91 0.00 -169264.46 -1879063.47



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 15.4433 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 12.6044 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 161.8069 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 118.3604 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 20.1325 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 14.5977 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 7.2422 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 7.2422 0.1657 1.0000 Not calculated 1.2002 0.1657    
AIRLOOP DATACENTER BASEMENT 32.8526 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 32.8528 0.0103 1.0000 Not calculated 0.3384 0.0103    
AIRLOOP DATACENTER BOT 0.7908 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.7908 0.0198 1.0000 Not calculated 0.0156 0.0198    
AIRLOOP DATACENTER MID 7.6086 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 7.6086 0.0205 1.0000 Not calculated 0.1563 0.0205    
AIRLOOP DATACENTER TOP 0.7833 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.7833 0.0200 1.0000 Not calculated 0.0156 0.0200    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 7.7217 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.6330 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 80.9035 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 48.5421 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 10.0662 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 6.0397 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 2.1727 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 2.1727 1.0000 1.0000 Not calculated 1.2002 0.5524    
AIRLOOP DATACENTER BASEMENT 16.4263 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 16.4263 1.0000 1.0000 Not calculated 0.3384 0.0206    
AIRLOOP DATACENTER BOT 0.7908 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.7908 1.0000 1.0000 Not calculated 0.0156 0.0198    
AIRLOOP DATACENTER MID 7.6086 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 7.6086 1.0000 1.0000 Not calculated 0.1563 0.0205    
AIRLOOP DATACENTER TOP 0.7833 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.7833 1.0000 1.0000 Not calculated 0.0156 0.0200    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT 7.2422 7.2422 2.1727 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.7185 7.7185 2.3155 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 73.3160 73.3160 21.9948 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.3200 9.3200 2.7960 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.8226 1.8226 0.5468 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7437 1.7437 0.5231 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.0332 2.0332 0.6100 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1254 2.1254 0.6376 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 25.4164 25.4164 7.6249 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 18.4060 18.4060 5.5218 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 24.8373 24.8373 7.4512 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 19.8312 19.8312 5.9494 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.2902 3.2902 0.9871 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1320 2.1320 0.6396 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.2303 3.2303 0.9691 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1599 2.1599 0.6480 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.7908 0.7908 0.7908 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 7.6086 7.6086 7.6086 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.7833 0.7833 0.7833 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT 32.8526 32.8526 16.4263 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 15.4433 12.6044 15.4433 4.6330 0.0000 1.0000
VAV_MID WITH REHEAT 161.8069 118.3604 161.8069 48.5421 0.0000 1.0000
VAV_TOP WITH REHEAT 20.1325 14.5977 20.1325 6.0397 0.0000 1.0000
CAV_BAS 7.2422 7.2422 7.2422 2.1727 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 32.8526 32.8528 32.8526 16.4263 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.7908 0.7908 0.7908 0.7908 0.0156 1.0000
AIRLOOP DATACENTER MID 7.6086 7.6086 7.6086 7.6086 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.7833 0.7833 0.7833 0.7833 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT 2.1727 2.1727 2.1727 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.8592 3.8592 2.3155 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 36.6580 36.6580 21.9948 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.6600 4.6600 2.7960 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9113 0.9113 0.5468 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8718 0.8718 0.5231 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0166 1.0166 0.6100 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0627 1.0627 0.6376 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 12.7082 12.7082 7.6249 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.2030 9.2030 5.5218 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 12.4186 12.4186 7.4512 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.9156 9.9156 5.9494 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6451 1.6451 0.9871 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0660 1.0660 0.6396 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6152 1.6152 0.9691 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0800 1.0800 0.6480 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.7908 0.7908 0.7908 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 7.6086 7.6086 7.6086 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.7833 0.7833 0.7833 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT 16.4263 16.4263 16.4263 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 7.7217 4.6330 4.6330 4.6330 0.0000 1.0000
VAV_MID WITH REHEAT 80.9035 48.5421 48.5421 48.5421 0.0000 1.0000
VAV_TOP WITH REHEAT 10.0662 6.0397 6.0397 6.0397 0.0000 1.0000
CAV_BAS 2.1727 2.1727 2.1727 2.1727 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 16.4263 16.4263 16.4263 16.4263 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.7908 0.7908 0.7908 0.7908 0.0156 1.0000
AIRLOOP DATACENTER MID 7.6086 7.6086 7.6086 7.6086 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.7833 0.7833 0.7833 0.7833 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 118.33
Number of hours cooling loads not met 173.17
Number of hours not met 286.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 7173.53 3142160.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 1965.43 515044.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 5610.74 489900.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 1006.00 64082.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5334.97 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 56.04 3543.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 2505.76 229608.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 61.31 1944.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2912.16 305773.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 1008.31 102278.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 176.75 58522.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 1053.07 100000.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 484.77 60480.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 14676.40 31516.73
Natural Gas 0.00 7173.53
Additional 0.00 0.00
Total 14676.40 38690.25


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 121.13
Space Heating 0.00
Space Cooling 42.43
Fans (All) 62.87
Service Water Heating 10.47
Receptacle Equipment 316.85
Miscellaneous (All) 680.41
Subtotal 680.41


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 154.87
Service Water Heating 0.00
Miscellaneous (All) 154.87
Subtotal 154.87


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 14.50
Space Heating 18.54
Space Cooling 5.08
Fans (All) 7.53
Service Water Heating 1.25
Receptacle Equipment 37.93
Miscellaneous 15.16


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
ELEVATOR_RUNNING_SCH 675. 3744.
ELEVATOR_STANDBY_SCH 7740. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2939. 8760.
LTG_SCH_DATACENTER 2939. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4049. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 2347. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365
HTGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL January 20.44 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8568.17 191.83 0.00 0.00 0.00
CORE_BOTTOM 8739.67 20.33 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8726.17 33.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8729.83 30.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8378.00 382.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8719.50 40.50 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8736.67 23.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8685.17 74.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8729.33 30.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8745.00 15.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8690.83 69.17 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 6028.00 2725.00 7.00 0.00 0.00
DATACENTER_MID_ZN_6 6034.50 2724.50 1.00 0.00 0.00
DATACENTER_TOP_ZN_6 6024.67 2735.33 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 6742.67 2017.33 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8705.33 54.67 0.00 0.00 0.00
Min 6024.67 0.00 0.00 0.00 0.00
Max 8760.00 2735.33 7.00 0.00 0.00
Average 8274.07 485.59 0.35 0.00 0.00
Sum 190303.50 11168.50 8.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 368126.00 490.00 0.00 0.00 0.00
CORE_BOTTOM 330811.00 2.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330813.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1371.67 893.50 2.83 0.00 0.00
DATACENTER_MID_ZN_6 1376.67 890.83 0.50 0.00 0.00
DATACENTER_TOP_ZN_6 1371.50 896.50 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 74629.50 28765.50 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 368126.00 28765.50 2.83 0.00 0.00
Average 78946.14 1388.62 0.14 0.00 0.00
Sum 1815761.33 31938.33 3.33 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8217.83 542.17 0.00 0.00 0.00
CORE_BOTTOM 8087.83 672.17 0.00 0.00 0.00
CORE_MID 8249.50 510.50 0.00 0.00 0.00
CORE_TOP 8500.00 260.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8432.67 327.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8556.67 203.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8444.67 315.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8033.17 726.83 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8563.83 196.17 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8468.50 291.50 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8464.83 295.17 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8286.00 474.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8578.67 181.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8491.00 269.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8510.50 249.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8343.83 416.17 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 7763.83 996.17 0.00 0.00 0.00
DATACENTER_MID_ZN_6 7756.67 1003.33 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 7748.50 1011.50 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 6689.00 2071.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8146.83 613.17 0.00 0.00 0.00
MIDFLOOR_PLENUM 8486.50 273.50 0.00 0.00 0.00
TOPFLOOR_PLENUM 8015.33 744.67 0.00 0.00 0.00
Min 6689.00 181.33 0.00 0.00 0.00
Max 8578.67 2071.00 0.00 0.00 0.00
Average 8210.27 549.73 0.00 0.00 0.00
Sum 188836.17 12643.83 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 367099.17 1516.83 0.00 0.00 0.00
CORE_BOTTOM 329937.00 876.00 0.00 0.00 0.00
CORE_MID 330069.00 744.00 0.00 0.00 0.00
CORE_TOP 330453.00 360.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1669.50 598.50 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1658.50 609.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1656.00 612.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 74980.00 28415.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 367099.17 28415.00 0.00 0.00 0.00
Average 78868.31 1466.60 0.00 0.00 0.00
Sum 1813971.17 33731.83 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:25

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A

For: Environment

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -12.56
February -7.67
March 0.331
April 7.021
May 14.194
June 19.161
July 20.915
August 20.049
September 15.390
October 7.428
November -0.02
December -7.58
   
Annual Sum or Average 6.460
Minimum of Months -12.56
Maximum of Months 20.915



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -12.56
February -7.67
March 0.331
April 7.021
May 14.194
June 19.161
July 20.915
August 20.049
September 15.390
October 7.428
November -0.02
December -7.58
   
Annual Sum or Average 6.460
Minimum of Months -12.56
Maximum of Months 20.915



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -12.56
February -7.67
March 0.331
April 7.021
May 14.194
June 19.161
July 20.915
August 20.049
September 15.390
October 7.428
November -0.02
December -7.58
   
Annual Sum or Average 6.460
Minimum of Months -12.56
Maximum of Months 20.915



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

For: Environment

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -12.56
February -7.67
March 0.331
April 7.021
May 14.194
June 19.161
July 20.915
August 20.049
September 15.390
October 7.428
November -0.02
December -7.58
   
Annual Sum or Average 6.460
Minimum of Months -12.56
Maximum of Months 20.915



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -12.56
February -7.67
March 0.331
April 7.021
May 14.194
June 19.161
July 20.915
August 20.049
September 15.390
October 7.428
November -0.02
December -7.58
   
Annual Sum or Average 6.460
Minimum of Months -12.56
Maximum of Months 20.915



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER

For: Environment

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -12.56
February -7.67
March 0.331
April 7.021
May 14.194
June 19.161
July 20.915
August 20.049
September 15.390
October 7.428
November -0.02
December -7.58
   
Annual Sum or Average 6.460
Minimum of Months -12.56
Maximum of Months 20.915



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -12.56
February -7.67
March 0.331
April 7.021
May 14.194
June 19.161
July 20.915
August 20.049
September 15.390
October 7.428
November -0.02
December -7.58
   
Annual Sum or Average 6.460
Minimum of Months -12.56
Maximum of Months 20.915



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE

For: Environment

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -12.56
February -7.67
March 0.331
April 7.021
May 14.194
June 19.161
July 20.915
August 20.049
September 15.390
October 7.428
November -0.02
December -7.58
   
Annual Sum or Average 6.460
Minimum of Months -12.56
Maximum of Months 20.915



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -12.56
February -7.67
March 0.331
April 7.021
May 14.194
June 19.161
July 20.915
August 20.049
September 15.390
October 7.428
November -0.02
December -7.58
   
Annual Sum or Average 6.460
Minimum of Months -12.56
Maximum of Months 20.915



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.532822E+11 124702.25 14-JAN-06:01 -3.4 -4.1 0.453413E+10 7368.72 13-JAN-14:09 -3.4 -4.1
February 0.423157E+11 123244.69 24-FEB-06:01 0.40 -1.6 0.445969E+10 7499.22 24-FEB-10:09 4.60 1.53
March 0.465823E+11 120310.84 25-MAR-05:01 -1.5 -2.5 0.571312E+10 7498.89 31-MAR-09:50 3.72 1.12
April 0.418739E+11 113138.40 19-APR-13:24 10.60 7.03 0.523468E+10 7499.23 10-APR-09:30 10.60 7.03
May 0.471684E+11 125089.30 18-MAY-05:02 5.28 4.19 0.574943E+10 7499.36 30-MAY-13:09 26.70 19.86
June 0.559556E+11 133453.03 19-JUN-04:11 12.03 10.64 0.584082E+10 7499.32 22-JUN-09:50 17.52 12.29
July 0.598227E+11 121305.34 24-JUL-04:11 10.00 9.40 0.546742E+10 7499.33 11-JUL-09:20 10.00 9.40
August 0.704961E+11 122927.14 07-AUG-04:12 8.50 7.60 0.612966E+10 7499.39 16-AUG-13:09 22.88 15.15
September 0.628687E+11 133566.64 27-SEP-04:11 5.93 5.19 0.535052E+10 7499.34 13-SEP-09:50 5.93 5.19
October 0.601119E+11 137659.95 23-OCT-03:01 -1.2 -2.2 0.557035E+10 7499.34 02-OCT-13:50 -1.2 -2.2
November 0.560387E+11 135351.93 01-NOV-04:11 5.00 4.07 0.542066E+10 7499.24 08-NOV-14:09 13.90 12.22
December 0.535050E+11 112070.72 04-DEC-05:01 -9.6 -9.9 0.503058E+10 7485.88 19-DEC-14:09 -1.7 -3.4
                     
Annual Sum or Average 0.650021E+12         0.645011E+11        
Minimum of Months 0.418739E+11 112070.72   -9.6 -9.9 0.445969E+10 7368.72   -3.4 -4.1
Maximum of Months 0.704961E+11 137659.95   12.03 10.64 0.612966E+10 7499.39   26.70 19.86



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.320379E+11 35261.86 13-JAN-16:55 2.20 0.77 0.474266E+10 6734.80 12-JAN-10:30 2.20 0.77
February 0.310777E+11 97582.52 25-FEB-06:01 0.00 -0.6 0.440247E+10 6734.90 22-FEB-10:09 0.00 -0.6
March 0.420149E+11 106365.89 30-MAR-05:01 1.10 0.61 0.542843E+10 6734.89 28-MAR-13:09 1.10 0.61
April 0.470455E+11 112600.27 17-APR-04:11 12.43 10.73 0.485241E+10 6734.91 11-APR-13:09 12.43 10.73
May 0.519316E+11 111408.00 30-MAY-04:12 14.40 14.40 0.526906E+10 6734.94 09-MAY-09:09 14.40 14.40
June 0.594040E+11 115990.49 28-JUN-04:11 17.60 16.08 0.526704E+10 6734.90 15-JUN-09:20 17.60 16.08
July 0.658032E+11 116389.55 19-JUL-04:11 11.87 11.14 0.489535E+10 6734.88 11-JUL-13:00 11.87 11.14
August 0.718855E+11 117402.96 15-AUG-04:11 15.40 14.38 0.549933E+10 6735.25 08-AUG-09:09 15.40 14.38
September 0.534742E+11 115726.76 01-SEP-04:11 13.30 11.05 0.487448E+10 6734.89 21-SEP-13:09 12.80 11.83
October 0.467935E+11 109575.37 11-OCT-04:11 10.87 9.98 0.505896E+10 6734.90 20-OCT-09:09 12.70 8.99
November 0.427289E+11 109538.13 08-NOV-05:11 12.20 11.27 0.497358E+10 6734.91 01-NOV-09:20 12.20 11.27
December 0.381893E+11 42223.81 05-DEC-16:15 -5.2 -8.3 0.478416E+10 6734.88 18-DEC-10:09 -2.3 -3.2
                     
Annual Sum or Average 0.582386E+12         0.600479E+11        
Minimum of Months 0.310777E+11 35261.86   -5.2 -8.3 0.440247E+10 6734.80   -2.3 -3.2
Maximum of Months 0.718855E+11 117402.96   17.60 16.08 0.549933E+10 6735.25   17.60 16.08



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.277499E+11 28456.77 13-JAN-16:55 2.20 0.77 0.425903E+10 6734.68 13-JAN-14:20 2.20 0.77
February 0.268889E+11 29143.87 24-FEB-16:52 7.20 5.13 0.405939E+10 6734.89 24-FEB-14:20 7.20 5.13
March 0.337370E+11 89702.57 24-MAR-05:01 7.12 4.33 0.518108E+10 6734.89 23-MAR-13:30 7.12 4.33
April 0.359467E+11 98619.05 17-APR-05:01 11.42 9.68 0.473406E+10 6734.91 07-APR-09:20 11.42 9.68
May 0.440838E+11 102298.75 13-MAY-05:01 13.22 12.93 0.523995E+10 6734.92 09-MAY-09:09 13.22 12.93
June 0.501474E+11 107596.43 29-JUN-04:11 17.60 16.30 0.524994E+10 6734.90 15-JUN-09:20 17.60 16.30
July 0.504905E+11 105790.21 01-JUL-04:11 15.20 13.63 0.488231E+10 6734.88 11-JUL-13:00 17.80 16.71
August 0.528691E+11 102745.07 11-AUG-04:11 13.50 12.44 0.548228E+10 6735.18 08-AUG-09:09 13.50 12.44
September 0.432799E+11 103697.97 08-SEP-04:11 17.40 14.82 0.484221E+10 6734.89 21-SEP-13:09 12.80 11.83
October 0.345954E+11 94961.42 21-OCT-05:01 10.33 8.13 0.496345E+10 6734.91 20-OCT-09:30 10.33 8.13
November 0.309327E+11 94464.67 09-NOV-06:01 14.82 12.81 0.464205E+10 6734.91 01-NOV-09:20 14.82 12.81
December 0.286754E+11 25689.96 07-DEC-16:53 -7.2 -9.8 0.427767E+10 6734.80 07-DEC-14:20 -7.2 -9.8
                     
Annual Sum or Average 0.459397E+12         0.578134E+11        
Minimum of Months 0.268889E+11 25689.96   -7.2 -9.8 0.405939E+10 6734.68   -7.2 -9.8
Maximum of Months 0.528691E+11 107596.43   17.60 16.30 0.548228E+10 6735.18   17.80 16.71



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.143185E+11 23505.48 13-JAN-17:00 2.20 0.77 0.379128E+10 5916.58 13-JAN-14:00 2.20 0.77
February 0.171362E+11 25549.76 24-FEB-17:00 7.20 5.13 0.353684E+10 6181.32 24-FEB-14:00 7.20 5.13
March 0.266649E+11 32688.99 24-MAR-15:53 10.60 5.50 0.447715E+10 6734.85 24-MAR-13:00 10.60 5.50
April 0.312694E+11 53703.53 18-APR-15:50 25.55 19.61 0.425348E+10 6734.83 19-APR-13:00 10.60 7.03
May 0.426577E+11 91174.43 31-MAY-05:02 16.38 14.96 0.498150E+10 6734.86 05-MAY-09:20 16.38 14.96
June 0.524491E+11 129304.36 14-JUN-05:01 17.80 17.37 0.512584E+10 6734.90 15-JUN-09:20 15.97 13.78
July 0.535778E+11 122374.22 28-JUL-05:01 17.80 16.77 0.481289E+10 6734.88 11-JUL-13:00 17.80 16.77
August 0.540510E+11 129417.28 03-AUG-04:01 23.80 22.62 0.538360E+10 6734.80 23-AUG-09:20 19.60 18.34
September 0.391631E+11 121041.59 12-SEP-05:02 16.02 15.69 0.453359E+10 6734.82 12-SEP-13:20 21.67 16.01
October 0.274293E+11 36144.59 20-OCT-16:00 21.30 12.72 0.428994E+10 6734.72 20-OCT-13:00 21.30 12.72
November 0.224083E+11 32269.58 03-NOV-15:53 15.00 9.33 0.400832E+10 6706.95 03-NOV-13:00 15.00 9.33
December 0.169528E+11 23143.19 01-DEC-16:30 -2.8 -4.8 0.368980E+10 5872.22 01-DEC-14:00 -2.8 -4.8
                     
Annual Sum or Average 0.398078E+12         0.528842E+11        
Minimum of Months 0.143185E+11 23143.19   -2.8 -4.8 0.353684E+10 5872.22   -2.8 -4.8
Maximum of Months 0.540510E+11 129417.28   25.55 22.62 0.538360E+10 6734.90   21.67 18.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.303710E+09 3826.02 13-JAN-14:20 3.90 1.72 0.465574E+09 667.98 13-JAN-14:30 3.90 1.72
February 0.116796E+10 4241.87 24-FEB-15:30 8.30 5.75 0.425618E+09 712.38 24-FEB-14:00 8.30 5.75
March 0.359650E+10 6411.26 19-MAR-13:21 17.50 13.24 0.543366E+09 828.03 28-MAR-13:00 16.70 10.30
April 0.591878E+10 10964.84 18-APR-15:00 28.30 20.65 0.525164E+09 845.63 13-APR-13:09 28.30 20.65
May 0.842678E+10 10904.01 31-MAY-14:50 29.90 19.65 0.628338E+09 845.64 08-MAY-13:00 29.90 19.65
June 0.108262E+11 19433.48 25-JUN-18:31 29.97 21.56 0.648573E+09 845.64 15-JUN-09:20 29.97 21.56
July 0.120444E+11 12187.37 03-JUL-13:40 29.23 24.20 0.610199E+09 845.64 18-JUL-09:30 21.40 14.62
August 0.122517E+11 12610.50 04-AUG-15:20 33.90 25.66 0.682257E+09 845.68 08-AUG-09:09 20.28 15.58
September 0.803471E+10 14441.78 11-SEP-04:11 20.40 17.35 0.573440E+09 845.63 18-SEP-09:20 21.30 16.23
October 0.545892E+10 6453.39 01-OCT-14:51 19.40 12.33 0.546365E+09 845.63 02-OCT-13:09 16.65 14.10
November 0.339793E+10 6335.99 09-NOV-06:02 14.82 12.81 0.503077E+09 820.94 07-NOV-14:20 14.82 12.81
December 0.941590E+09 3577.10 01-DEC-06:03 -2.3 -3.2 0.450104E+09 631.37 01-DEC-14:00 -1.1 -3.6
                     
Annual Sum or Average 0.723692E+11         0.660207E+10        
Minimum of Months 0.303710E+09 3577.10   -2.3 -3.2 0.425618E+09 631.37   -1.1 -3.6
Maximum of Months 0.122517E+11 19433.48   33.90 25.66 0.682257E+09 845.68   29.97 21.56



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.466717E+09 3999.50 12-JAN-10:13 -1.9 -2.6 0.300426E+09 456.57 12-JAN-10:20 -1.9 -2.6
February 0.131464E+10 6236.30 24-FEB-09:31 3.87 1.06 0.278128E+09 544.96 24-FEB-10:50 5.40 2.22
March 0.350182E+10 9382.68 28-MAR-09:03 7.67 4.71 0.359059E+09 544.96 17-MAR-09:39 7.67 4.71
April 0.558910E+10 26246.06 30-APR-08:32 9.43 4.96 0.335991E+09 544.96 13-APR-09:09 9.43 4.96
May 0.837043E+10 28737.87 29-MAY-09:01 22.48 18.29 0.403853E+09 544.98 05-MAY-09:09 22.48 18.29
June 0.104306E+11 32153.56 25-JUN-07:51 23.90 20.49 0.411799E+09 544.96 01-JUN-09:39 23.90 20.49
July 0.113789E+11 33138.61 02-JUL-08:41 25.32 20.92 0.389092E+09 544.99 18-JUL-09:30 21.40 14.62
August 0.109423E+11 30598.39 27-AUG-09:11 23.33 19.50 0.435701E+09 545.02 08-AUG-09:09 23.33 19.50
September 0.795389E+10 21256.85 04-SEP-08:52 16.10 13.09 0.369221E+09 544.97 05-SEP-09:30 21.95 14.90
October 0.488035E+10 10541.53 01-OCT-08:48 12.78 9.88 0.350095E+09 544.96 20-OCT-09:09 12.70 8.99
November 0.267795E+10 5650.48 09-NOV-05:11 15.00 13.04 0.312320E+09 498.65 03-NOV-10:39 15.00 13.04
December 0.845592E+09 4242.75 05-DEC-09:40 -6.3 -8.4 0.291391E+09 473.04 05-DEC-10:09 -5.9 -8.1
                     
Annual Sum or Average 0.683523E+11         0.423708E+10        
Minimum of Months 0.466717E+09 3999.50   -6.3 -8.4 0.278128E+09 456.57   -5.9 -8.1
Maximum of Months 0.113789E+11 33138.61   25.32 20.92 0.435701E+09 545.02   23.90 20.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.280413E+10 15112.47 12-JAN-12:30 1.95 0.38 0.511497E+09 845.65 30-JAN-14:20 -24.2 -24.6
February 0.370104E+10 19931.08 24-FEB-13:23 7.25 4.63 0.476482E+09 845.65 16-FEB-14:20 7.25 4.63
March 0.619794E+10 33268.89 19-MAR-12:41 16.42 12.53 0.587765E+09 845.65 28-MAR-13:09 15.78 9.88
April 0.862874E+10 34708.58 16-APR-11:32 24.63 19.46 0.537196E+09 846.14 18-APR-13:39 27.93 20.65
May 0.102811E+11 23478.78 29-MAY-12:22 24.45 18.92 0.623132E+09 845.66 08-MAY-13:00 24.45 18.92
June 0.126564E+11 34592.98 25-JUN-13:51 32.20 22.49 0.638184E+09 845.66 21-JUN-13:30 32.20 22.49
July 0.145190E+11 34307.85 02-JUL-12:42 28.40 22.40 0.604715E+09 845.66 18-JUL-09:30 21.40 14.62
August 0.161113E+11 25063.17 13-AUG-11:21 21.10 18.55 0.677549E+09 846.10 02-AUG-13:00 21.10 18.55
September 0.127676E+11 34678.20 10-SEP-14:31 27.43 17.62 0.577960E+09 846.10 05-SEP-13:00 27.43 17.62
October 0.930077E+10 35982.21 29-OCT-13:21 13.35 7.41 0.576781E+09 845.85 20-OCT-13:39 13.35 7.41
November 0.511875E+10 32885.93 12-NOV-12:31 -0.4 -3.0 0.523845E+09 845.65 14-NOV-10:50 5.95 3.65
December 0.326233E+10 25795.94 03-DEC-13:12 5.60 2.35 0.495655E+09 845.65 28-DEC-14:09 -4.9 -6.1
                     
Annual Sum or Average 0.105349E+12         0.683076E+10        
Minimum of Months 0.280413E+10 15112.47   -0.4 -3.0 0.476482E+09 845.65   -24.2 -24.6
Maximum of Months 0.161113E+11 35982.21   32.20 22.49 0.677549E+09 846.14   32.20 22.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.127132E+10 5895.14 12-JAN-15:40 2.80 1.13 0.304615E+09 498.95 12-JAN-15:50 2.80 1.13
February 0.264502E+10 10002.01 24-FEB-16:21 7.75 5.51 0.284934E+09 544.96 24-FEB-14:50 7.75 5.51
March 0.589587E+10 11733.17 19-MAR-16:03 18.80 13.89 0.361196E+09 544.96 28-MAR-13:50 16.52 10.22
April 0.938546E+10 42036.42 16-APR-16:11 28.70 20.49 0.350323E+09 544.96 12-APR-13:00 28.70 20.49
May 0.100943E+11 38508.26 21-MAY-16:21 18.35 10.29 0.391960E+09 544.97 08-MAY-13:00 18.35 10.29
June 0.128159E+11 42746.18 25-JUN-17:11 31.50 21.73 0.409661E+09 544.96 21-JUN-13:30 31.50 21.73
July 0.152645E+11 43262.52 02-JUL-16:41 28.98 21.21 0.392887E+09 544.97 18-JUL-09:30 21.40 14.62
August 0.158942E+11 36780.93 13-AUG-16:01 25.50 20.53 0.441348E+09 544.97 07-AUG-13:09 25.50 20.53
September 0.985144E+10 33277.80 10-SEP-14:31 27.43 17.62 0.359531E+09 544.96 07-SEP-13:00 27.43 17.62
October 0.708701E+10 33610.45 01-OCT-16:11 17.70 11.56 0.351329E+09 544.96 19-OCT-13:39 17.67 10.18
November 0.492410E+10 10982.92 03-NOV-15:23 15.55 9.47 0.327729E+09 544.95 03-NOV-13:39 15.55 9.47
December 0.300479E+10 6675.82 01-DEC-15:23 -1.4 -3.8 0.302136E+09 537.17 01-DEC-14:00 -1.4 -3.8
                     
Annual Sum or Average 0.981339E+11         0.427765E+10        
Minimum of Months 0.127132E+10 5895.14   -1.4 -3.8 0.284934E+09 498.95   -1.4 -3.8
Maximum of Months 0.158942E+11 43262.52   31.50 21.73 0.441348E+09 544.97   31.50 21.73



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 87796233.93 5030.61 11-JAN-06:04 -4.4 -4.6 0.462951E+09 626.10 18-JAN-10:00 -13.9 -14.4
February 0.215244E+09 4846.95 14-FEB-06:04 -3.3 -4.4 0.420787E+09 625.80 02-FEB-14:00 -3.3 -4.4
March 0.177554E+10 5865.50 28-MAR-15:30 16.40 10.50 0.509555E+09 695.44 28-MAR-13:00 16.40 10.50
April 0.420428E+10 10094.88 16-APR-16:21 28.60 20.44 0.470051E+09 845.61 18-APR-13:20 27.57 20.63
May 0.836113E+10 10423.22 31-MAY-15:00 30.00 19.70 0.562655E+09 845.61 31-MAY-13:20 30.00 19.70
June 0.107072E+11 11850.11 26-JUN-14:30 31.40 21.97 0.608539E+09 845.63 21-JUN-13:30 31.40 21.97
July 0.111773E+11 10956.37 26-JUL-15:20 30.00 25.67 0.578052E+09 845.62 21-JUL-13:20 30.00 25.67
August 0.109021E+11 11834.59 04-AUG-15:30 33.90 25.83 0.637153E+09 845.62 09-AUG-13:20 26.50 16.73
September 0.744346E+10 10265.69 11-SEP-14:30 28.60 20.18 0.515091E+09 845.62 07-SEP-13:20 28.60 20.18
October 0.361088E+10 7136.14 01-OCT-15:01 19.18 12.23 0.478219E+09 716.08 02-OCT-13:00 17.40 14.50
November 0.161568E+10 6805.14 08-NOV-06:01 12.20 11.27 0.464235E+09 691.14 03-NOV-13:00 12.20 11.27
December 50701590.82 5075.71 30-DEC-06:03 -1.7 -2.2 0.446857E+09 626.03 11-DEC-14:09 -1.7 -2.2
                     
Annual Sum or Average 0.601512E+11         0.615414E+10        
Minimum of Months 50701590.82 4846.95   -4.4 -4.6 0.420787E+09 625.80   -13.9 -14.4
Maximum of Months 0.111773E+11 11850.11   33.90 25.83 0.637153E+09 845.63   31.40 25.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.137894E+09 4631.78 12-JAN-11:02 0.28 -1.0 0.215198E+09 486.21 12-JAN-11:09 0.28 -1.0
February 0.439527E+09 13105.47 24-FEB-11:01 5.68 2.52 0.199268E+09 548.49 24-FEB-11:09 5.68 2.52
March 0.193552E+10 17504.61 28-MAR-10:01 10.47 6.54 0.253311E+09 548.49 28-MAR-10:09 10.47 6.54
April 0.391703E+10 21095.39 30-APR-09:02 10.18 5.26 0.240955E+09 548.49 14-APR-12:09 10.18 5.26
May 0.732481E+10 29725.76 14-MAY-08:52 15.60 12.96 0.290342E+09 548.52 04-MAY-10:09 15.60 12.96
June 0.983540E+10 31266.32 25-JUN-09:22 26.95 21.50 0.299301E+09 548.49 08-JUN-12:09 26.95 21.50
July 0.105211E+11 34218.91 30-JUL-09:21 23.35 19.20 0.284999E+09 548.50 18-JUL-10:09 23.35 19.20
August 0.970747E+10 32132.56 20-AUG-09:01 20.97 18.46 0.315627E+09 548.50 30-AUG-10:09 18.68 15.67
September 0.676295E+10 30732.21 04-SEP-08:41 15.63 12.89 0.264267E+09 548.50 18-SEP-10:09 21.97 16.57
October 0.281315E+10 14534.15 20-OCT-10:01 15.68 10.42 0.243429E+09 548.49 20-OCT-14:09 22.72 13.08
November 0.103027E+10 12878.08 04-NOV-10:01 9.60 5.18 0.221570E+09 548.49 03-NOV-10:09 9.60 5.18
December 0.138421E+09 4175.53 01-DEC-11:02 -2.1 -4.0 0.208553E+09 452.41 01-DEC-11:09 -2.1 -4.0
                     
Annual Sum or Average 0.545636E+11         0.303682E+10        
Minimum of Months 0.137894E+09 4175.53   -2.1 -4.0 0.199268E+09 452.41   -2.1 -4.0
Maximum of Months 0.105211E+11 34218.91   26.95 21.50 0.315627E+09 548.52   26.95 21.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.268406E+10 15509.83 12-JAN-12:40 2.03 0.42 0.500221E+09 845.65 30-JAN-14:30 -24.1 -24.5
February 0.359138E+10 22012.65 24-FEB-13:32 7.43 4.81 0.464521E+09 845.65 24-FEB-14:20 7.97 5.32
March 0.569974E+10 31658.92 19-MAR-13:11 17.23 13.08 0.566192E+09 845.66 24-MAR-13:30 12.75 6.50
April 0.762549E+10 31983.54 16-APR-13:42 27.62 20.47 0.515775E+09 845.66 19-APR-13:20 10.60 7.03
May 0.101669E+11 18089.69 30-MAY-13:30 26.70 19.86 0.594228E+09 845.66 22-MAY-13:00 26.70 19.86
June 0.124112E+11 18772.75 30-JUN-13:10 29.40 21.96 0.615997E+09 845.65 21-JUN-13:20 29.40 21.96
July 0.135402E+11 41232.62 30-JUL-14:01 27.20 19.47 0.585839E+09 845.65 11-JUL-13:00 27.20 19.47
August 0.148569E+11 41695.74 13-AUG-13:11 25.37 19.81 0.655998E+09 845.68 07-AUG-13:09 25.37 19.81
September 0.127105E+11 45539.79 17-SEP-14:21 27.20 18.12 0.557058E+09 846.63 05-SEP-13:20 27.20 18.12
October 0.890064E+10 45667.80 01-OCT-13:41 18.95 12.28 0.552333E+09 846.32 20-OCT-13:30 22.20 12.82
November 0.417340E+10 23460.94 03-NOV-13:30 15.85 10.76 0.495975E+09 845.68 03-NOV-13:39 15.93 10.67
December 0.280971E+10 17778.94 01-DEC-13:23 -0.9 -3.3 0.482297E+09 845.65 14-DEC-14:09 1.20 0.19
                     
Annual Sum or Average 0.991701E+11         0.658643E+10        
Minimum of Months 0.268406E+10 15509.83   -0.9 -3.3 0.464521E+09 845.65   -24.1 -24.5
Maximum of Months 0.148569E+11 45667.80   29.40 21.96 0.655998E+09 846.63   29.40 21.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.363678E+09 4800.69 12-JAN-15:50 2.80 1.13 0.299255E+09 451.99 12-JAN-15:00 2.80 1.13
February 0.926125E+09 7963.85 24-FEB-16:22 7.75 5.51 0.275963E+09 521.20 24-FEB-15:50 7.75 5.51
March 0.246962E+10 8097.71 23-MAR-15:53 17.20 10.15 0.337817E+09 521.20 22-MAR-15:20 17.20 10.15
April 0.531054E+10 33692.38 16-APR-16:21 28.60 20.44 0.317108E+09 544.94 18-APR-13:20 27.57 20.63
May 0.793291E+10 37022.61 14-MAY-17:01 21.42 15.87 0.366257E+09 544.95 31-MAY-13:20 29.80 19.61
June 0.105423E+11 35576.87 25-JUN-16:41 31.78 21.74 0.388636E+09 544.96 15-JUN-13:39 31.78 21.74
July 0.114058E+11 35100.77 02-JUL-16:51 28.90 21.17 0.371563E+09 544.95 21-JUL-13:20 22.40 16.99
August 0.110964E+11 34563.85 13-AUG-16:31 25.20 20.49 0.412361E+09 544.95 07-AUG-13:00 25.20 20.49
September 0.745651E+10 35604.67 04-SEP-17:21 21.40 14.23 0.334511E+09 544.95 07-SEP-13:20 31.87 18.17
October 0.396136E+10 12018.06 20-OCT-15:30 22.30 13.06 0.323573E+09 544.22 20-OCT-13:00 22.30 13.06
November 0.171169E+10 8206.86 03-NOV-15:22 15.55 9.47 0.301545E+09 521.19 03-NOV-15:00 15.00 9.33
December 0.480497E+09 4801.17 01-DEC-15:40 -1.5 -3.9 0.289533E+09 453.13 01-DEC-15:50 -1.6 -4.0
                     
Annual Sum or Average 0.636575E+11         0.401812E+10        
Minimum of Months 0.363678E+09 4800.69   -1.5 -3.9 0.275963E+09 451.99   -1.6 -4.0
Maximum of Months 0.114058E+11 37022.61   31.78 21.74 0.412361E+09 544.96   31.87 21.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 42967367.45 5577.65 14-JAN-17:01 -7.4 -8.6 0.462614E+09 626.12 05-JAN-10:00 -7.4 -8.6
February 0.132775E+09 6612.02 25-FEB-06:03 0.00 -0.6 0.420350E+09 625.82 03-FEB-14:20 0.00 -0.6
March 0.111933E+10 6865.74 28-MAR-15:30 16.40 10.50 0.505689E+09 648.61 28-MAR-13:00 16.40 10.50
April 0.357865E+10 13199.80 16-APR-16:21 28.60 20.44 0.460096E+09 841.58 18-APR-13:00 28.30 20.65
May 0.837554E+10 11774.72 31-MAY-15:00 30.00 19.70 0.529758E+09 845.61 31-MAY-13:20 30.00 19.70
June 0.116103E+11 15668.61 25-JUN-17:41 31.20 21.79 0.575638E+09 845.61 28-JUN-13:20 28.90 20.51
July 0.123217E+11 14591.60 02-JUL-17:51 28.30 21.02 0.546298E+09 845.61 05-JUL-13:20 26.87 20.29
August 0.117064E+11 13336.83 04-AUG-15:30 33.90 25.83 0.601361E+09 845.60 11-AUG-13:39 27.77 18.47
September 0.700796E+10 12929.57 17-SEP-14:11 27.20 18.12 0.488092E+09 845.61 11-SEP-13:20 27.20 18.12
October 0.237349E+10 7543.60 01-OCT-14:31 19.27 12.32 0.467044E+09 672.44 20-OCT-13:00 22.60 13.03
November 0.919529E+09 6715.94 07-NOV-06:02 10.50 9.67 0.459369E+09 638.24 03-NOV-13:00 10.50 9.67
December 43503618.61 5678.74 02-DEC-17:01 1.70 0.90 0.446310E+09 626.01 27-DEC-14:00 -6.7 -8.4
                     
Annual Sum or Average 0.592320E+11         0.596262E+10        
Minimum of Months 42967367.45 5577.65   -7.4 -8.6 0.420350E+09 625.82   -7.4 -8.6
Maximum of Months 0.123217E+11 15668.61   33.90 25.83 0.601361E+09 845.61   30.00 20.65



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 85794262.84 3614.55 14-JAN-17:01 -7.4 -8.6 0.298141E+09 403.47 03-JAN-14:50 -7.4 -8.6
February 0.377824E+09 4960.29 24-FEB-10:20 4.80 1.70 0.271562E+09 460.75 24-FEB-10:30 5.00 1.88
March 0.177252E+10 6049.79 28-MAR-10:00 10.00 6.30 0.333182E+09 529.46 28-MAR-09:00 10.00 6.30
April 0.376583E+10 14432.81 18-APR-09:40 24.67 19.90 0.315551E+09 544.96 13-APR-09:09 24.67 19.90
May 0.751325E+10 23119.46 29-MAY-09:01 22.48 18.29 0.375856E+09 544.98 04-MAY-09:50 22.48 18.29
June 0.103030E+11 38743.01 25-JUN-08:21 25.00 20.84 0.399604E+09 544.96 21-JUN-13:20 25.00 20.84
July 0.110306E+11 36759.21 02-JUL-07:51 23.90 20.48 0.380063E+09 545.00 18-JUL-09:30 21.40 14.62
August 0.101413E+11 28460.75 27-AUG-09:21 23.60 19.50 0.421376E+09 545.02 08-AUG-09:09 23.60 19.50
September 0.665157E+10 18182.84 03-SEP-09:52 18.30 13.33 0.342601E+09 544.97 06-SEP-09:00 25.60 18.61
October 0.256818E+10 6171.41 01-OCT-13:51 19.00 12.30 0.307088E+09 536.61 20-OCT-09:00 15.20 10.20
November 0.778143E+09 4562.45 03-NOV-10:36 13.87 11.30 0.296527E+09 429.50 03-NOV-13:00 16.10 10.47
December 57061171.72 3690.30 02-DEC-17:01 1.70 0.90 0.287654E+09 403.49 11-DEC-14:09 -19.4 -20.1
                     
Annual Sum or Average 0.550452E+11         0.402921E+10        
Minimum of Months 57061171.72 3614.55   -7.4 -8.6 0.271562E+09 403.47   -19.4 -20.1
Maximum of Months 0.110306E+11 38743.01   25.00 20.84 0.421376E+09 545.02   25.60 20.84



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.226856E+10 13051.41 12-JAN-12:40 2.03 0.42 0.485538E+09 845.65 02-JAN-14:20 2.03 0.42
February 0.330791E+10 20843.89 24-FEB-13:43 7.62 4.99 0.446136E+09 845.65 24-FEB-14:20 7.97 5.32
March 0.480300E+10 18596.32 24-MAR-13:32 12.93 6.50 0.546990E+09 845.65 28-MAR-13:09 15.78 9.88
April 0.686055E+10 29309.51 16-APR-13:42 27.62 20.47 0.502181E+09 845.67 14-APR-13:39 27.62 20.47
May 0.102174E+11 19599.75 30-MAY-13:30 26.70 19.86 0.561676E+09 845.66 22-MAY-13:00 26.70 19.86
June 0.130959E+11 52955.55 25-JUN-14:21 32.20 22.49 0.591637E+09 845.66 21-JUN-13:20 32.20 22.49
July 0.144419E+11 48975.01 02-JUL-14:31 29.23 21.69 0.562945E+09 845.65 18-JUL-13:20 24.07 16.16
August 0.153896E+11 42996.93 13-AUG-13:11 25.37 19.81 0.631567E+09 845.68 07-AUG-13:09 25.37 19.81
September 0.120548E+11 57722.24 17-SEP-13:31 26.67 18.01 0.530189E+09 845.66 12-SEP-13:20 26.67 18.01
October 0.730594E+10 52768.46 01-OCT-13:51 19.00 12.30 0.527496E+09 845.65 20-OCT-13:09 21.93 12.68
November 0.333665E+10 22461.04 03-NOV-13:22 15.85 10.76 0.475765E+09 845.65 03-NOV-13:09 15.85 10.76
December 0.239023E+10 15757.47 01-DEC-13:23 -0.9 -3.3 0.470127E+09 845.65 14-DEC-14:09 1.20 0.19
                     
Annual Sum or Average 0.954725E+11         0.633225E+10        
Minimum of Months 0.226856E+10 13051.41   -0.9 -3.3 0.446136E+09 845.65   1.20 0.19
Maximum of Months 0.153896E+11 57722.24   32.20 22.49 0.631567E+09 845.68   32.20 22.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.268087E+09 4882.98 12-JAN-15:50 2.80 1.13 0.298544E+09 431.90 12-JAN-15:00 2.80 1.13
February 0.768216E+09 7717.33 24-FEB-16:24 7.75 5.51 0.274371E+09 521.20 24-FEB-15:50 7.75 5.51
March 0.198633E+10 7863.95 23-MAR-15:51 17.20 10.15 0.334840E+09 521.20 22-MAR-15:30 17.20 10.15
April 0.474404E+10 36874.77 16-APR-16:21 28.60 20.44 0.313351E+09 544.94 18-APR-13:20 27.57 20.63
May 0.766947E+10 32141.97 14-MAY-16:32 21.70 15.60 0.356783E+09 544.94 31-MAY-13:20 29.80 19.61
June 0.106801E+11 44624.61 25-JUN-17:01 31.60 21.70 0.380753E+09 544.96 07-JUN-13:00 31.60 21.70
July 0.116303E+11 43671.98 02-JUL-17:11 28.70 21.12 0.363540E+09 544.95 18-JUL-13:39 24.23 16.07
August 0.111503E+11 37653.38 13-AUG-16:31 25.20 20.49 0.402635E+09 544.95 09-AUG-13:20 25.20 20.49
September 0.693258E+10 38167.72 04-SEP-17:21 21.40 14.23 0.326300E+09 544.95 05-SEP-13:00 27.20 16.61
October 0.311251E+10 12221.42 20-OCT-15:30 22.30 13.06 0.317338E+09 539.32 20-OCT-13:00 22.30 13.06
November 0.121938E+10 7874.93 03-NOV-15:22 15.55 9.47 0.298195E+09 521.19 03-NOV-15:00 15.00 9.33
December 0.355281E+09 4842.76 01-DEC-15:40 -1.5 -3.9 0.288232E+09 431.27 01-DEC-14:00 -1.5 -3.9
                     
Annual Sum or Average 0.605166E+11         0.395488E+10        
Minimum of Months 0.268087E+09 4842.76   -1.5 -3.9 0.274371E+09 431.27   -1.5 -3.9
Maximum of Months 0.116303E+11 44624.61   31.60 21.70 0.402635E+09 544.96   31.60 21.70



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.140397E+10 19776.40 06-JAN-04:11 -26.3 -26.5 0.00 0.00 01-JAN-00:10 -26.3 -26.5
February 0.192301E+10 17785.30 04-FEB-04:11 -30.9 -31.1 0.00 0.00 01-FEB-00:10 -30.9 -31.1
March 0.348671E+10 12217.35 06-MAR-04:01 -16.0 -16.5 0.00 0.00 01-MAR-00:10 -16.0 -16.5
April 0.560932E+10 11471.02 03-APR-04:01 -6.8 -7.6 0.00 0.00 01-APR-00:10 -6.8 -7.6
May 0.710202E+10 9225.22 06-MAY-05:06 9.40 6.46 0.00 0.00 01-MAY-00:10 9.40 6.46
June 0.964715E+10 9728.24 26-JUN-15:30 31.40 21.97 0.00 0.00 01-JUN-00:10 31.40 21.97
July 0.108507E+11 10129.68 31-JUL-05:04 16.88 15.09 0.00 0.00 01-JUL-00:10 16.88 15.09
August 0.116336E+11 10579.10 14-AUG-05:12 15.77 15.05 0.00 0.00 01-AUG-00:10 15.77 15.05
September 0.828964E+10 10721.95 09-SEP-05:12 13.70 13.03 0.00 0.00 01-SEP-00:10 13.70 13.03
October 0.563924E+10 11254.10 23-OCT-05:01 -2.7 -3.7 0.00 0.00 01-OCT-00:10 -2.7 -3.7
November 0.416137E+10 17211.05 26-NOV-02:41 -24.9 -25.2 0.00 0.00 01-NOV-00:10 -24.9 -25.2
December 0.215454E+10 19070.09 09-DEC-04:01 -22.8 -23.0 0.00 0.00 01-DEC-00:10 -22.8 -23.0
                     
Annual Sum or Average 0.719013E+11         0.00        
Minimum of Months 0.140397E+10 9225.22   -30.9 -31.1 0.00 0.00   -30.9 -31.1
Maximum of Months 0.116336E+11 19776.40   31.40 21.97 0.00 0.00   31.40 21.97



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.257073E+10 20726.82 06-JAN-04:01 -26.2 -26.5 0.00 0.00 01-JAN-00:10 -26.2 -26.5
February 0.247886E+10 23207.85 18-FEB-04:11 -15.6 -16.0 0.00 0.00 01-FEB-00:10 -15.6 -16.0
March 0.230159E+10 22385.37 21-MAR-03:01 -6.7 -7.9 0.00 0.00 01-MAR-00:10 -6.7 -7.9
April 0.395272E+10 18800.28 22-APR-04:01 -0.6 -1.1 0.00 0.00 01-APR-00:10 -0.6 -1.1
May 0.601346E+10 15396.50 02-MAY-04:11 2.60 0.50 0.00 0.00 01-MAY-00:10 2.60 0.50
June 0.838969E+10 10159.42 22-JUN-05:06 9.68 8.78 0.00 0.00 01-JUN-00:10 9.68 8.78
July 0.888101E+10 10473.61 06-JUL-05:08 18.90 18.18 0.00 0.00 01-JUL-00:10 18.90 18.18
August 0.899366E+10 10640.02 30-AUG-05:10 13.90 12.58 0.00 0.00 01-AUG-00:10 13.90 12.58
September 0.682522E+10 18396.41 30-SEP-04:01 -0.5 -1.9 0.00 0.00 01-SEP-00:10 -0.5 -1.9
October 0.340868E+10 17940.54 27-OCT-04:01 0.00 -1.2 0.00 0.00 01-OCT-00:10 0.00 -1.2
November 0.319270E+10 20907.71 10-NOV-04:01 -1.7 -2.3 0.00 0.00 01-NOV-00:10 -1.7 -2.3
December 0.233434E+10 26715.49 09-DEC-02:12 -22.6 -22.9 0.00 0.00 01-DEC-00:10 -22.6 -22.9
                     
Annual Sum or Average 0.593426E+11         0.00        
Minimum of Months 0.230159E+10 10159.42   -26.2 -26.5 0.00 0.00   -26.2 -26.5
Maximum of Months 0.899366E+10 26715.49   18.90 18.18 0.00 0.00   18.90 18.18



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 5055198.05 677.57 13-JAN-13:00 3.90 1.72 0.00 0.00 01-JAN-00:10 3.90 1.72
February 0.219825E+09 6389.05 24-FEB-13:50 7.62 4.99 0.00 0.00 01-FEB-00:10 7.62 4.99
March 0.187498E+10 14243.29 19-MAR-13:03 16.97 12.93 0.00 0.00 01-MAR-00:10 16.97 12.93
April 0.651486E+10 27152.02 18-APR-13:40 27.93 20.65 0.00 0.00 01-APR-00:10 27.93 20.65
May 0.130289E+11 31668.28 31-MAY-13:50 29.50 19.49 0.00 0.00 01-MAY-00:10 29.50 19.49
June 0.193032E+11 35257.58 30-JUN-13:50 29.40 21.96 0.00 0.00 01-JUN-00:10 29.40 21.96
July 0.209468E+11 34028.23 05-JUL-13:50 27.12 19.90 0.00 0.00 01-JUL-00:10 27.12 19.90
August 0.193111E+11 34891.45 04-AUG-14:30 33.60 25.57 0.00 0.00 01-AUG-00:10 33.60 25.57
September 0.108718E+11 33068.34 07-SEP-13:30 31.95 18.23 0.00 0.00 01-SEP-00:10 31.95 18.23
October 0.311880E+10 15603.56 20-OCT-14:30 22.95 13.19 0.00 0.00 01-OCT-00:10 22.95 13.19
November 0.622275E+09 9167.18 03-NOV-13:01 15.68 10.94 0.00 0.00 01-NOV-00:10 15.68 10.94
December 42943.42 134.55 03-DEC-14:15 5.40 2.13 0.00 0.00 01-DEC-00:10 5.40 2.13
                     
Annual Sum or Average 0.958176E+11         0.00        
Minimum of Months 42943.42 134.55   3.90 1.72 0.00 0.00   3.90 1.72
Maximum of Months 0.209468E+11 35257.58   33.60 25.57 0.00 0.00   33.60 25.57



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.112873E+10 6798.01 30-JAN-13:01 -24.9 -25.2 96253310.48 154.44 19-JAN-10:00 -24.9 -25.2
February 0.533245E+10 10396.54 04-FEB-10:31 -24.8 -25.2 94468169.12 222.14 02-FEB-16:49 -24.8 -25.2
March 0.128528E+11 6618.61 31-MAR-23:47 -0.8 -1.9 0.103236E+09 126.82 24-MAR-13:00 -0.8 -1.9
April 0.180738E+11 8329.20 16-APR-17:57 26.70 19.84 91605448.10 126.83 18-APR-13:09 27.38 20.62
May 0.408172E+10 3461.20 31-MAY-23:51 15.10 10.22 99235205.19 126.83 30-MAY-13:09 15.10 10.22
June 0.927105E+10 5369.73 30-JUN-23:51 19.10 15.95 98959367.83 126.83 26-JUN-09:09 19.10 15.95
July 0.149242E+11 7255.02 31-JUL-24:00 18.20 17.87 91881475.16 126.82 03-JUL-13:00 18.20 17.87
August 0.199462E+11 8484.50 29-AUG-17:40 21.67 14.89 0.103240E+09 126.83 04-AUG-09:09 21.67 14.89
September 0.416255E+10 2843.58 30-SEP-23:51 3.90 1.09 91606517.16 126.83 11-SEP-09:00 3.90 1.09
October 0.846482E+10 4730.37 31-OCT-23:52 1.50 -0.9 95230060.73 126.82 10-OCT-13:09 1.50 -0.9
November 0.123018E+11 9904.18 26-NOV-08:11 -24.8 -25.2 94344881.20 126.82 08-NOV-10:00 -24.8 -25.2
December 0.170412E+11 7867.82 01-DEC-16:03 -2.1 -4.3 91880866.73 126.82 05-DEC-14:20 -3.9 -7.4
                     
Annual Sum or Average 0.127581E+12         0.115194E+10        
Minimum of Months 0.112873E+10 2843.58   -24.9 -25.2 91605448.10 126.82   -24.9 -25.2
Maximum of Months 0.199462E+11 10396.54   26.70 19.84 0.103240E+09 222.14   27.38 20.62



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.399714E+09 1800.11 12-JAN-16:40 2.07 0.72 94914838.43 135.62 06-JAN-10:09 2.07 0.72
February 0.363062E+10 9982.48 04-FEB-10:31 -24.8 -25.2 93190390.17 217.27 03-FEB-16:00 -24.8 -25.2
March 0.109252E+11 5963.77 31-MAR-23:12 -0.3 -1.4 0.103236E+09 126.82 24-MAR-13:00 -0.3 -1.4
April 0.163957E+11 7852.62 15-APR-18:10 27.85 18.48 91605456.91 126.83 18-APR-13:09 27.38 20.62
May 0.327144E+10 3267.67 31-MAY-23:40 15.90 10.90 99235157.57 126.83 30-MAY-13:00 15.90 10.90
June 0.854844E+10 5200.13 30-JUN-23:51 19.10 15.95 98959515.88 126.83 30-JUN-09:00 19.10 15.95
July 0.139443E+11 6778.70 31-JUL-24:00 18.20 17.87 91881496.47 126.82 03-JUL-13:00 18.20 17.87
August 0.186612E+11 8127.41 29-AUG-17:40 21.67 14.89 0.103241E+09 126.83 04-AUG-09:09 21.67 14.89
September 0.322588E+10 2554.22 01-SEP-17:50 22.07 14.32 91606517.22 126.83 11-SEP-13:09 28.40 20.30
October 0.686008E+10 4228.77 11-OCT-16:52 16.70 11.06 95230063.77 126.82 10-OCT-13:00 16.70 11.06
November 0.993435E+10 9354.19 26-NOV-08:11 -24.8 -25.2 94335219.00 126.82 08-NOV-10:00 -24.8 -25.2
December 0.140112E+11 7292.86 01-DEC-16:03 -2.1 -4.3 91880868.78 126.82 05-DEC-14:20 -3.9 -7.4
                     
Annual Sum or Average 0.109808E+12         0.114932E+10        
Minimum of Months 0.399714E+09 1800.11   -24.8 -25.2 91605456.91 126.82   -24.8 -25.2
Maximum of Months 0.186612E+11 9982.48   27.85 18.48 0.103241E+09 217.27   28.40 20.62



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.157431E+09 1586.17 12-JAN-16:40 2.07 0.72 92405414.75 128.11 26-JAN-14:50 -12.3 -12.7
February 0.232062E+10 8266.63 04-FEB-10:31 -24.8 -25.2 91244992.21 200.63 02-FEB-16:00 -24.8 -25.2
March 0.905826E+10 5724.66 21-MAR-17:32 -1.8 -4.9 0.103236E+09 126.82 24-MAR-13:00 13.30 6.51
April 0.149642E+11 8020.34 16-APR-17:57 26.70 19.84 91605408.39 126.83 18-APR-13:09 27.38 20.62
May 0.252430E+10 3147.02 31-MAY-23:20 16.70 11.57 99236878.33 126.83 30-MAY-13:09 16.70 11.57
June 0.812456E+10 5093.88 30-JUN-23:30 19.60 15.96 98959516.64 126.83 13-JUN-13:09 19.60 15.96
July 0.136512E+11 6512.29 31-JUL-23:50 18.27 17.81 91881650.99 126.82 03-JUL-13:00 18.27 17.81
August 0.182648E+11 8229.25 29-AUG-17:40 21.67 14.89 0.103240E+09 126.83 04-AUG-09:09 21.67 14.89
September 0.237472E+10 2652.94 01-SEP-17:40 22.43 14.32 91610726.13 126.83 11-SEP-13:09 28.40 20.30
October 0.481198E+10 4220.85 11-OCT-16:41 16.88 11.21 95230115.54 126.82 10-OCT-13:00 16.88 11.21
November 0.785097E+10 9246.42 26-NOV-08:11 -24.8 -25.2 94318130.10 126.82 08-NOV-10:00 -24.8 -25.2
December 0.118451E+11 7031.56 01-DEC-16:03 -2.1 -4.3 91880869.74 126.82 05-DEC-14:20 -3.9 -7.4
                     
Annual Sum or Average 0.959481E+11         0.114485E+10        
Minimum of Months 0.157431E+09 1586.17   -24.8 -25.2 91244992.21 126.82   -24.8 -25.2
Maximum of Months 0.182648E+11 9246.42   26.70 19.84 0.103240E+09 200.63   28.40 20.62



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.227885E+12 95031.73 18-JAN-13:01 -16.2 -16.5 0.208450E+10 2793.44 11-JAN-14:09 -16.2 -16.5
February 0.430858E+12 484674.86 01-FEB-00:12 -24.4 -24.7 0.155635E+10 2634.97 08-FEB-14:00 2.20 0.97
March 0.720801E+12 521666.13 24-MAR-15:52 10.60 5.50 0.188083E+10 2742.35 24-MAR-09:09 10.60 5.50
April 0.939351E+12 490466.75 19-APR-09:42 5.60 4.05 0.161599E+10 2802.90 17-APR-13:00 5.60 4.05
May 0.233752E+12 466173.84 31-MAY-23:56 15.10 10.22 0.215333E+10 2813.48 22-MAY-13:09 15.10 10.22
June 0.469441E+12 487183.82 03-JUN-02:22 5.85 5.59 0.200615E+10 2745.24 19-JUN-09:09 15.18 12.11
July 0.730836E+12 488467.29 24-JUL-02:52 10.00 9.40 0.197130E+10 2746.06 14-JUL-09:09 10.00 9.40
August 0.979023E+12 496623.96 06-AUG-19:34 14.60 10.55 0.220072E+10 2991.14 07-AUG-15:20 22.80 14.05
September 0.234971E+12 481570.91 30-SEP-23:12 3.77 0.73 0.198824E+10 2794.55 15-SEP-13:30 3.77 0.73
October 0.490316E+12 510496.12 31-OCT-23:53 1.50 -0.9 0.176766E+10 2745.17 11-OCT-09:50 1.50 -0.9
November 0.703448E+12 517651.82 01-NOV-02:42 3.97 3.17 0.170453E+10 2729.36 15-NOV-14:09 7.07 4.91
December 0.977503E+12 486450.79 13-DEC-13:04 -5.5 -5.9 0.158179E+10 2632.37 08-DEC-14:00 -5.5 -5.9
                     
Annual Sum or Average 0.713818E+13         0.225114E+11        
Minimum of Months 0.227885E+12 95031.73   -24.4 -24.7 0.155635E+10 2632.37   -16.2 -16.5
Maximum of Months 0.979023E+12 521666.13   15.10 10.55 0.220072E+10 2991.14   22.80 14.05



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.136478E+09 91097.77 31-JAN-07:10 -30.5
February 0.529258E+09 92598.48 03-FEB-07:08 -33.9
March 40658174.29 2881.31 25-MAR-05:11 -1.3
April 73487402.21 10173.63 15-APR-16:01 30.00
May 62116073.69 3268.28 03-MAY-05:05 1.38
June 83564874.63 6163.81 10-JUN-16:01 27.20
July 51288683.50 6106.88 29-JUL-16:01 27.20
August 38833379.21 4467.71 05-AUG-16:01 26.02
September 86735601.22 7898.07 16-SEP-16:02 28.62
October 80884108.57 2695.15 23-OCT-05:04 -2.7
November 65911170.68 2946.03 13-NOV-06:11 -3.1
December 61706228.02 3474.65 27-DEC-06:12 -9.6
         
Annual Sum or Average 0.131092E+10      
Minimum of Months 38833379.21 2695.15   -33.9
Maximum of Months 0.529258E+09 92598.48   30.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 8294301.76 23479.40 30-JAN-06:01 -28.4
February 6320078.39 23948.61 06-FEB-06:01 -15.0
March 0.00 0.00 01-MAR-00:01 -11.0
April 0.00 0.00 01-APR-00:03 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:05 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:01 3.92
November 0.00 0.00 01-NOV-00:01 1.65
December 0.00 0.00 01-DEC-00:01 -0.7
         
Annual Sum or Average 14614380.15      
Minimum of Months 0.00 0.00   -28.4
Maximum of Months 8294301.76 23948.61   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.156821E+10 69532.47 02-JAN-04:01 -4.0
February 0.442404E+09 66369.50 06-FEB-05:01 -14.5
March 0.111465E+09 63762.90 06-MAR-05:01 -15.4
April 8313135.41 57350.92 03-APR-05:01 -7.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:05 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:01 3.92
November 0.278211E+09 66654.05 27-NOV-05:01 -9.4
December 0.586586E+09 65891.96 11-DEC-05:01 -22.2
         
Annual Sum or Average 0.299519E+10      
Minimum of Months 0.00 0.00   -22.2
Maximum of Months 0.156821E+10 69532.47   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.150433E+11 134327.99 30-JAN-03:21 -26.9
February 0.925446E+10 132635.39 06-FEB-02:61 -17.9
March 0.442678E+10 130902.62 06-MAR-04:01 -16.0
April 0.131304E+10 128947.37 03-APR-03:01 -6.2
May 34928832.20 81066.54 22-MAY-05:02 4.78
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:05 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.121038E+09 99905.81 30-SEP-05:01 0.10
October 0.144860E+10 112999.31 23-OCT-04:01 -1.9
November 0.627752E+10 132086.01 27-NOV-00:01 -12.6
December 0.110313E+11 133490.55 11-DEC-04:01 -21.8
         
Annual Sum or Average 0.489510E+11      
Minimum of Months 0.00 0.00   -26.9
Maximum of Months 0.150433E+11 134327.99   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.742857E+10 26385.04 30-JAN-03:51 -27.2
February 0.429137E+10 27298.32 02-FEB-04:11 -35.4
March 0.947796E+09 24988.01 06-MAR-04:01 -16.0
April 0.120388E+09 22732.68 03-APR-04:01 -6.8
May 276428.25 1842.85 02-MAY-05:03 2.20
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:05 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 4635388.32 17207.71 30-SEP-05:01 0.10
October 25274584.73 20213.76 23-OCT-05:01 -2.7
November 0.116734E+10 25978.42 26-NOV-04:41 -25.0
December 0.323976E+10 26337.26 11-DEC-02:61 -21.7
         
Annual Sum or Average 0.172254E+11      
Minimum of Months 0.00 0.00   -35.4
Maximum of Months 0.742857E+10 27298.32   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.448960E+10 22594.62 30-JAN-03:51 -27.2
February 0.251488E+10 23520.68 02-FEB-04:11 -35.4
March 0.699316E+09 21183.26 06-MAR-04:01 -16.0
April 0.121434E+09 19062.54 03-APR-04:01 -6.8
May 533331.81 2868.88 02-MAY-05:03 2.20
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:05 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 6286255.34 12864.12 30-SEP-05:01 0.10
October 34082634.83 15478.47 23-OCT-05:01 -2.7
November 0.866714E+09 22346.68 26-NOV-04:41 -25.0
December 0.247609E+10 22660.19 11-DEC-02:61 -21.7
         
Annual Sum or Average 0.112089E+11      
Minimum of Months 0.00 0.00   -35.4
Maximum of Months 0.448960E+10 23520.68   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.587065E+10 29393.63 30-JAN-03:51 -27.2
February 0.319683E+10 30318.91 02-FEB-04:11 -35.4
March 0.116593E+10 27899.06 06-MAR-04:21 -15.9
April 0.259931E+09 26669.74 03-APR-03:01 -6.2
May 5492577.10 10220.19 02-MAY-05:03 2.20
June 15219.15 101.46 03-JUN-05:03 5.78
July 0.00 0.00 01-JUL-00:05 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 25774198.20 19227.07 30-SEP-05:01 0.10
October 0.128808E+09 21774.01 23-OCT-05:01 -2.7
November 0.137305E+10 29337.58 26-NOV-07:21 -27.2
December 0.354305E+10 29543.33 11-DEC-02:61 -21.7
         
Annual Sum or Average 0.155695E+11      
Minimum of Months 0.00 0.00   -35.4
Maximum of Months 0.587065E+10 30318.91   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.255783E+10 22543.47 31-JAN-04:01 -31.0
February 0.113667E+10 22875.90 02-FEB-04:11 -35.4
March 0.116758E+09 19498.53 06-MAR-05:01 -15.4
April 10520145.38 18627.31 03-APR-04:01 -6.8
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:05 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 103486.05 1724.77 29-SEP-05:03 0.92
October 1807098.19 15348.63 23-OCT-05:01 -2.7
November 0.234893E+09 20819.72 27-NOV-04:01 -10.4
December 0.557570E+09 21835.41 11-DEC-04:01 -21.8
         
Annual Sum or Average 0.461615E+10      
Minimum of Months 0.00 0.00   -35.4
Maximum of Months 0.255783E+10 22875.90   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.174791E+11 41082.86 19-JAN-04:11 -26.5
February 0.103341E+11 40855.62 02-FEB-03:31 -35.0
March 0.458778E+10 38829.64 06-MAR-00:01 -16.3
April 0.128253E+10 36854.25 03-APR-01:41 -6.1
May 85774610.21 27137.74 02-MAY-04:11 2.60
June 4428058.19 18928.74 02-JUN-05:01 7.20
July 0.00 0.00 01-JUL-00:05 18.93
August 85947.37 859.47 07-AUG-05:03 8.80
September 0.182498E+09 28132.19 30-SEP-04:01 -0.5
October 0.914020E+09 30797.70 23-OCT-05:01 -2.7
November 0.594156E+10 39747.23 26-NOV-04:01 -25.0
December 0.121611E+11 42372.00 09-DEC-02:11 -22.6
         
Annual Sum or Average 0.529729E+11      
Minimum of Months 0.00 0.00   -35.0
Maximum of Months 0.174791E+11 42372.00   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.100512E+11 29670.23 19-JAN-04:11 -26.5
February 0.559123E+10 29453.74 02-FEB-03:31 -35.0
March 0.246809E+10 27976.22 06-MAR-04:01 -16.0
April 0.703816E+09 26568.02 03-APR-01:41 -6.1
May 31529502.93 18406.34 02-MAY-04:11 2.60
June 1583052.67 12503.09 02-JUN-05:01 7.20
July 0.00 0.00 01-JUL-00:05 18.93
August 32782.02 194.83 17-AUG-05:03 10.68
September 94058821.83 19073.47 30-SEP-04:01 -0.5
October 0.492395E+09 21104.31 23-OCT-05:01 -2.7
November 0.354366E+10 28667.49 26-NOV-04:01 -25.0
December 0.720494E+10 30429.25 09-DEC-02:11 -22.6
         
Annual Sum or Average 0.301825E+11      
Minimum of Months 0.00 0.00   -35.0
Maximum of Months 0.100512E+11 30429.25   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.116864E+11 40056.83 19-JAN-04:11 -26.5
February 0.627674E+10 39560.74 02-FEB-02:51 -35.0
March 0.320985E+10 37743.16 06-MAR-04:01 -16.0
April 0.101660E+10 35864.64 03-APR-01:41 -6.1
May 68248700.11 26094.02 02-MAY-04:11 2.60
June 3512760.71 18293.55 02-JUN-05:01 7.20
July 0.00 0.00 01-JUL-00:05 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.129802E+09 27231.25 30-SEP-04:01 -0.5
October 0.584881E+09 29976.40 23-OCT-05:01 -2.7
November 0.413799E+10 38671.29 26-NOV-03:21 -25.0
December 0.883056E+10 40779.52 09-DEC-02:11 -22.6
         
Annual Sum or Average 0.359446E+11      
Minimum of Months 0.00 0.00   -35.0
Maximum of Months 0.116864E+11 40779.52   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.932948E+10 31203.47 19-JAN-04:11 -26.5
February 0.495436E+10 30705.71 02-FEB-03:31 -35.0
March 0.215709E+10 29107.30 06-MAR-04:01 -16.0
April 0.537526E+09 26694.50 03-APR-03:01 -6.2
May 34237276.07 18876.50 02-MAY-04:11 2.60
June 1935516.16 12870.37 02-JUN-05:01 7.20
July 0.00 0.00 01-JUL-00:05 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 93646335.77 19863.84 30-SEP-04:01 -0.5
October 0.421161E+09 21603.96 23-OCT-05:01 -2.7
November 0.300983E+10 30094.04 26-NOV-03:21 -25.0
December 0.635144E+10 31971.44 09-DEC-02:11 -22.6
         
Annual Sum or Average 0.268907E+11      
Minimum of Months 0.00 0.00   -35.0
Maximum of Months 0.932948E+10 31971.44   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.255482E+11 55408.06 29-JAN-10:41 -22.3
February 0.172604E+11 54644.46 02-FEB-04:01 -35.2
March 0.930518E+10 52020.84 06-MAR-04:01 -16.0
April 0.372048E+10 48912.67 03-APR-02:41 -6.1
May 0.473738E+09 38838.53 02-MAY-04:11 2.60
June 0.114422E+09 30290.83 05-JUN-04:11 9.13
July 1896452.17 21190.22 24-JUL-05:01 10.28
August 22498465.84 20078.26 07-AUG-05:02 8.80
September 0.908305E+09 39187.47 30-SEP-03:01 -0.1
October 0.338106E+10 42798.04 23-OCT-04:31 -2.3
November 0.116100E+11 53329.77 26-NOV-04:01 -25.0
December 0.204165E+11 56194.12 09-DEC-02:61 -22.7
         
Annual Sum or Average 0.927627E+11      
Minimum of Months 1896452.17 20078.26   -35.2
Maximum of Months 0.255482E+11 56194.12   10.28



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.154355E+11 35794.67 29-JAN-06:41 -22.0
February 0.989386E+10 35356.55 02-FEB-04:01 -35.2
March 0.521464E+10 33746.11 06-MAR-04:01 -16.0
April 0.214373E+10 31700.14 03-APR-02:41 -6.1
May 0.198783E+09 25106.50 02-MAY-04:11 2.60
June 63165475.12 19412.65 05-JUN-04:11 9.13
July 409964.60 5691.41 24-JUL-05:01 10.28
August 9740309.09 12949.66 07-AUG-05:02 8.80
September 0.471744E+09 25306.28 30-SEP-03:01 -0.1
October 0.183492E+10 27771.12 23-OCT-04:31 -2.3
November 0.706343E+10 34521.68 26-NOV-04:01 -25.0
December 0.125515E+11 36447.43 09-DEC-02:61 -22.7
         
Annual Sum or Average 0.548814E+11      
Minimum of Months 409964.60 5691.41   -35.2
Maximum of Months 0.154355E+11 36447.43   10.28



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.188832E+11 53948.16 29-JAN-06:41 -22.0
February 0.121077E+11 53107.39 02-FEB-04:01 -35.2
March 0.715860E+10 50811.72 06-MAR-04:01 -16.0
April 0.320708E+10 47941.04 03-APR-02:41 -6.1
May 0.444614E+09 37674.87 02-MAY-04:11 2.60
June 0.113863E+09 29496.05 05-JUN-04:11 9.13
July 2724205.97 16324.18 24-JUL-05:01 10.28
August 12095670.24 19217.72 07-AUG-05:02 8.80
September 0.716188E+09 38191.37 30-SEP-03:01 -0.1
October 0.238226E+10 41881.33 23-OCT-04:31 -2.3
November 0.887212E+10 52041.66 26-NOV-04:01 -25.0
December 0.158550E+11 55007.19 09-DEC-02:61 -22.7
         
Annual Sum or Average 0.697555E+11      
Minimum of Months 2724205.97 16324.18   -35.2
Maximum of Months 0.188832E+11 55007.19   10.28



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.141462E+11 36282.99 29-JAN-10:41 -22.3
February 0.850993E+10 35411.13 02-FEB-04:01 -35.2
March 0.437566E+10 33491.92 06-MAR-04:01 -16.0
April 0.156778E+10 31473.43 03-APR-02:41 -6.1
May 0.195463E+09 24781.76 02-MAY-04:11 2.60
June 53444496.51 19073.84 05-JUN-04:11 9.13
July 5920.56 98.68 11-JUL-05:04 13.98
August 2293094.15 11035.18 07-AUG-05:02 8.80
September 0.416586E+09 25182.08 30-SEP-03:01 -0.1
October 0.143534E+10 27584.43 23-OCT-04:31 -2.3
November 0.575680E+10 34460.16 26-NOV-03:21 -25.0
December 0.105955E+11 36638.51 09-DEC-02:61 -22.7
         
Annual Sum or Average 0.470549E+11      
Minimum of Months 5920.56 98.68   -35.2
Maximum of Months 0.141462E+11 36638.51   13.98



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.238690E+10 12119.47 30-JAN-06:11 -28.5
February 0.133580E+10 11309.38 20-FEB-13:12 2.80
March 0.189233E+09 11671.49 19-MAR-11:27 14.70
April 86695860.38 14387.34 16-APR-15:31 28.70
May 58695608.24 9426.94 14-MAY-16:32 21.70
June 57434364.72 11064.67 25-JUN-15:11 32.20
July 0.101191E+09 11844.33 30-JUL-14:52 27.20
August 78013193.58 12528.01 31-AUG-04:11 19.07
September 55197957.76 9660.34 04-SEP-15:32 22.20
October 45340820.46 13956.66 01-OCT-14:51 19.40
November 0.360526E+09 10956.61 09-NOV-05:11 15.00
December 0.777130E+09 8409.43 03-DEC-13:12 5.60
         
Annual Sum or Average 0.553216E+10      
Minimum of Months 45340820.46 8409.43   -28.5
Maximum of Months 0.238690E+10 14387.34   32.20



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.819870E+10 26629.72 02-JAN-06:12 -5.2
February 0.431120E+10 21997.61 06-FEB-06:05 -15.0
March 0.175855E+10 14746.30 06-MAR-06:05 -14.1
April 0.494741E+09 13363.38 16-APR-15:42 28.80
May 45907047.63 9962.76 21-MAY-16:32 18.17
June 43237841.97 10004.68 11-JUN-15:22 33.05
July 61056905.94 12734.87 30-JUL-15:21 27.50
August 31459833.90 11958.92 13-AUG-15:11 25.93
September 39496416.96 14555.72 04-SEP-16:01 22.20
October 0.202712E+09 13984.23 01-OCT-14:21 19.20
November 0.254362E+10 19918.62 27-NOV-06:05 -9.4
December 0.497083E+10 21565.95 11-DEC-06:05 -22.1
         
Annual Sum or Average 0.227015E+11      
Minimum of Months 31459833.90 9962.76   -22.1
Maximum of Months 0.819870E+10 26629.72   33.05



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.431551E+11 75701.38 31-JAN-05:11 -30.6
February 0.292754E+11 77369.96 02-FEB-05:31 -36.5
March 0.168212E+11 63350.64 06-MAR-05:25 -15.0
April 0.788419E+10 54127.81 03-APR-04:11 -6.9
May 0.155078E+10 27651.54 31-MAY-05:02 16.38
June 0.543023E+09 35019.81 01-JUN-05:01 5.65
July 0.171445E+09 34030.16 13-JUL-05:01 13.27
August 0.392949E+09 29276.88 24-AUG-05:01 12.30
September 0.272370E+10 27940.33 08-SEP-05:02 14.32
October 0.790218E+10 41074.04 16-OCT-04:21 1.35
November 0.211943E+11 59500.11 24-NOV-05:04 -14.7
December 0.364245E+11 67721.97 11-DEC-05:31 -22.2
         
Annual Sum or Average 0.168039E+12      
Minimum of Months 0.171445E+09 27651.54   -36.5
Maximum of Months 0.431551E+11 77369.96   16.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.390224E+09 1587.41 20-JAN-04:03 -24.9
February 0.201442E+09 1524.94 01-FEB-00:52 -25.3
March 0.00 0.00 01-MAR-00:01 -11.0
April 0.00 0.00 01-APR-00:03 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:05 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:01 3.92
November 25401730.69 1673.39 26-NOV-03:02 -25.0
December 0.00 0.00 01-DEC-00:01 -0.7
         
Annual Sum or Average 0.617068E+09      
Minimum of Months 0.00 0.00   -25.3
Maximum of Months 0.390224E+09 1673.39   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.159470E+10 1361.20 30-JAN-23:55 -28.9
February 0.192199E+09 1400.56 01-FEB-00:52 -25.3
March 0.00 0.00 01-MAR-00:01 -11.0
April 0.00 0.00 01-APR-00:03 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:05 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:01 3.92
November 24623748.81 1457.64 26-NOV-03:02 -25.0
December 0.00 0.00 01-DEC-00:01 -0.7
         
Annual Sum or Average 0.181153E+10      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.159470E+10 1457.64   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.217409E+10 1446.72 29-JAN-17:21 -22.2
February 0.536700E+09 1409.75 01-FEB-23:01 -31.9
March 0.00 0.00 01-MAR-00:01 -11.0
April 0.00 0.00 01-APR-00:03 -1.2
May 86543682.00 996.56 14-MAY-09:50 16.93
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:05 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.138704E+09 1292.17 30-SEP-04:09 -0.5
October 8191797.38 1103.33 23-OCT-01:34 -0.1
November 25618663.84 1411.72 26-NOV-03:02 -25.0
December 0.00 0.00 01-DEC-00:01 -0.7
         
Annual Sum or Average 0.296985E+10      
Minimum of Months 0.00 0.00   -31.9
Maximum of Months 0.217409E+10 1446.72   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:02 -2.8
February 0.101447E+10 19252.08 01-FEB-00:31 -24.8
March 0.00 0.00 01-MAR-00:01 -11.0
April 0.00 0.00 01-APR-00:03 -1.2
May 162626.57 2050.35 31-MAY-23:54 15.10
June 0.292225E+09 39815.56 05-JUN-01:01 10.00
July 0.00 0.00 01-JUL-00:05 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 2831811.97 18013.64 30-SEP-23:31 3.83
October 0.331041E+09 27125.60 10-OCT-05:01 11.27
November 0.00 0.00 01-NOV-00:01 1.65
December 0.00 0.00 01-DEC-00:01 -0.7
         
Annual Sum or Average 0.164073E+10      
Minimum of Months 0.00 0.00   -24.8
Maximum of Months 0.101447E+10 39815.56   18.93



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.278508E+11 29144.79 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.252627E+11 29144.79 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.300191E+11 29144.79 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.268132E+11 29144.79 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.289349E+11 29144.79 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.287951E+11 29144.79 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.269531E+11 29144.79 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.300191E+11 29144.79 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.268132E+11 29144.79 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.278508E+11 29144.79 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.275243E+11 29144.79 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.269531E+11 29144.79 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.333789E+12     0.424397E+12    
Minimum of Months 0.252627E+11 29144.79   0.325565E+11 13457.54  
Maximum of Months 0.300191E+11 29144.79   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.250119E+11 26174.07 02-JAN-08:09 0.243681E+11 17206.63 02-JAN-08:09
February 0.226877E+11 26174.07 01-FEB-08:09 0.220609E+11 17206.63 01-FEB-08:09
March 0.269593E+11 26174.07 01-MAR-08:09 0.253549E+11 17206.63 01-MAR-08:09
April 0.240801E+11 26174.07 03-APR-07:10 0.235306E+11 17206.63 03-APR-07:10
May 0.259856E+11 26174.07 01-MAY-07:10 0.248615E+11 17206.63 01-MAY-07:10
June 0.258600E+11 26174.07 01-JUN-07:10 0.244160E+11 17206.63 01-JUN-07:10
July 0.242058E+11 26174.07 03-JUL-07:10 0.239708E+11 17206.63 03-JUL-07:10
August 0.269593E+11 26174.07 01-AUG-07:10 0.253549E+11 17206.63 01-AUG-07:10
September 0.240801E+11 26174.07 01-SEP-07:10 0.235199E+11 17206.63 01-SEP-07:10
October 0.250119E+11 26174.07 02-OCT-07:10 0.243735E+11 17206.63 02-OCT-07:10
November 0.247188E+11 26174.07 01-NOV-07:10 0.238373E+11 17206.63 01-NOV-07:10
December 0.242058E+11 26174.07 01-DEC-08:09 0.239654E+11 17206.63 01-DEC-08:09
             
Annual Sum or Average 0.299766E+12     0.289614E+12    
Minimum of Months 0.226877E+11 26174.07   0.220609E+11 17206.63  
Maximum of Months 0.269593E+11 26174.07   0.253549E+11 17206.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.250119E+11 26174.07 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.226877E+11 26174.07 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.269593E+11 26174.07 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.240801E+11 26174.07 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.259856E+11 26174.07 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.258600E+11 26174.07 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.242058E+11 26174.07 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.269593E+11 26174.07 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.240801E+11 26174.07 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.250119E+11 26174.07 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.247188E+11 26174.07 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.242058E+11 26174.07 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.299766E+12     0.289613E+12    
Minimum of Months 0.226877E+11 26174.07   0.220609E+11 17206.56  
Maximum of Months 0.269593E+11 26174.07   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.250119E+11 26174.07 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.226877E+11 26174.07 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.269593E+11 26174.07 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.240801E+11 26174.07 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.259856E+11 26174.07 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.258600E+11 26174.07 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.242058E+11 26174.07 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.269593E+11 26174.07 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.240801E+11 26174.07 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.250119E+11 26174.07 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.247188E+11 26174.07 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.242058E+11 26174.07 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.299766E+12     0.289613E+12    
Minimum of Months 0.226877E+11 26174.07   0.220609E+11 17206.56  
Maximum of Months 0.269593E+11 26174.07   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.314050E+10 3286.42 02-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.284867E+10 3286.42 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.338501E+10 3286.42 01-MAR-08:09 0.318369E+10 2160.55 01-MAR-08:09
April 0.302350E+10 3286.42 03-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.326275E+10 3286.42 01-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.324698E+10 3286.42 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.303928E+10 3286.42 03-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.338501E+10 3286.42 01-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.302350E+10 3286.42 01-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.314050E+10 3286.42 02-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.310369E+10 3286.42 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.303928E+10 3286.42 01-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.376387E+11     0.363654E+11    
Minimum of Months 0.284867E+10 3286.42   0.277008E+10 2160.55  
Maximum of Months 0.338501E+10 3286.42   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.202386E+10 2117.89 02-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.183579E+10 2117.89 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.218143E+10 2117.89 01-MAR-08:09 0.205169E+10 1392.34 01-MAR-08:09
April 0.194846E+10 2117.89 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.210264E+10 2117.89 01-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.209248E+10 2117.89 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.195863E+10 2117.89 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.218143E+10 2117.89 01-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.194846E+10 2117.89 01-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.202386E+10 2117.89 02-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.200014E+10 2117.89 01-NOV-07:10 0.192889E+10 1392.34 01-NOV-07:10
December 0.195863E+10 2117.89 01-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.242558E+11     0.234352E+11    
Minimum of Months 0.183579E+10 2117.89   0.178515E+10 1392.34  
Maximum of Months 0.218143E+10 2117.89   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.314057E+10 3286.49 02-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.284873E+10 3286.49 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.338508E+10 3286.49 01-MAR-08:09 0.318374E+10 2160.58 01-MAR-08:09
April 0.302357E+10 3286.49 03-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.326282E+10 3286.49 01-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.324705E+10 3286.49 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.303934E+10 3286.49 03-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.338508E+10 3286.49 01-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.302357E+10 3286.49 01-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.314057E+10 3286.49 02-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.310376E+10 3286.49 01-NOV-07:10 0.299318E+10 2160.58 01-NOV-07:10
December 0.303934E+10 3286.49 01-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.376395E+11     0.363660E+11    
Minimum of Months 0.284873E+10 3286.49   0.277013E+10 2160.58  
Maximum of Months 0.338508E+10 3286.49   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.202386E+10 2117.89 02-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.183579E+10 2117.89 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.218143E+10 2117.89 01-MAR-08:09 0.205168E+10 1392.33 01-MAR-08:09
April 0.194846E+10 2117.89 03-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.210264E+10 2117.89 01-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.209248E+10 2117.89 01-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.195863E+10 2117.89 03-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.218143E+10 2117.89 01-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.194846E+10 2117.89 01-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.202386E+10 2117.89 02-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.200014E+10 2117.89 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.195863E+10 2117.89 01-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.242558E+11     0.234351E+11    
Minimum of Months 0.183579E+10 2117.89   0.178514E+10 1392.33  
Maximum of Months 0.218143E+10 2117.89   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.314050E+10 3286.42 02-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.284867E+10 3286.42 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.338501E+10 3286.42 01-MAR-08:09 0.318369E+10 2160.55 01-MAR-08:09
April 0.302350E+10 3286.42 03-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.326275E+10 3286.42 01-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.324698E+10 3286.42 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.303928E+10 3286.42 03-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.338501E+10 3286.42 01-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.302350E+10 3286.42 01-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.314050E+10 3286.42 02-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.310369E+10 3286.42 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.303928E+10 3286.42 01-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.376387E+11     0.363654E+11    
Minimum of Months 0.284867E+10 3286.42   0.277008E+10 2160.55  
Maximum of Months 0.338501E+10 3286.42   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.202386E+10 2117.89 02-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.183579E+10 2117.89 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.218143E+10 2117.89 01-MAR-08:09 0.205169E+10 1392.34 01-MAR-08:09
April 0.194846E+10 2117.89 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.210264E+10 2117.89 01-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.209248E+10 2117.89 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.195863E+10 2117.89 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.218143E+10 2117.89 01-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.194846E+10 2117.89 01-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.202386E+10 2117.89 02-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.200014E+10 2117.89 01-NOV-07:10 0.192889E+10 1392.34 01-NOV-07:10
December 0.195863E+10 2117.89 01-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.242558E+11     0.234352E+11    
Minimum of Months 0.183579E+10 2117.89   0.178515E+10 1392.34  
Maximum of Months 0.218143E+10 2117.89   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.314057E+10 3286.49 02-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.284873E+10 3286.49 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.338508E+10 3286.49 01-MAR-08:09 0.318374E+10 2160.58 01-MAR-08:09
April 0.302357E+10 3286.49 03-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.326282E+10 3286.49 01-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.324705E+10 3286.49 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.303934E+10 3286.49 03-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.338508E+10 3286.49 01-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.302357E+10 3286.49 01-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.314057E+10 3286.49 02-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.310376E+10 3286.49 01-NOV-07:10 0.299318E+10 2160.58 01-NOV-07:10
December 0.303934E+10 3286.49 01-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.376395E+11     0.363660E+11    
Minimum of Months 0.284873E+10 3286.49   0.277013E+10 2160.58  
Maximum of Months 0.338508E+10 3286.49   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.202386E+10 2117.89 02-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.183579E+10 2117.89 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.218143E+10 2117.89 01-MAR-08:09 0.205168E+10 1392.33 01-MAR-08:09
April 0.194846E+10 2117.89 03-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.210264E+10 2117.89 01-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.209248E+10 2117.89 01-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.195863E+10 2117.89 03-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.218143E+10 2117.89 01-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.194846E+10 2117.89 01-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.202386E+10 2117.89 02-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.200014E+10 2117.89 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.195863E+10 2117.89 01-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.242558E+11     0.234351E+11    
Minimum of Months 0.183579E+10 2117.89   0.178514E+10 1392.33  
Maximum of Months 0.218143E+10 2117.89   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.314050E+10 3286.42 02-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.284867E+10 3286.42 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.338501E+10 3286.42 01-MAR-08:09 0.318369E+10 2160.55 01-MAR-08:09
April 0.302350E+10 3286.42 03-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.326275E+10 3286.42 01-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.324698E+10 3286.42 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.303928E+10 3286.42 03-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.338501E+10 3286.42 01-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.302350E+10 3286.42 01-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.314050E+10 3286.42 02-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.310369E+10 3286.42 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.303928E+10 3286.42 01-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.376387E+11     0.363654E+11    
Minimum of Months 0.284867E+10 3286.42   0.277008E+10 2160.55  
Maximum of Months 0.338501E+10 3286.42   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.202386E+10 2117.89 02-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.183579E+10 2117.89 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.218143E+10 2117.89 01-MAR-08:09 0.205169E+10 1392.34 01-MAR-08:09
April 0.194846E+10 2117.89 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.210264E+10 2117.89 01-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.209248E+10 2117.89 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.195863E+10 2117.89 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.218143E+10 2117.89 01-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.194846E+10 2117.89 01-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.202386E+10 2117.89 02-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.200014E+10 2117.89 01-NOV-07:10 0.192889E+10 1392.34 01-NOV-07:10
December 0.195863E+10 2117.89 01-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.242558E+11     0.234352E+11    
Minimum of Months 0.183579E+10 2117.89   0.178515E+10 1392.34  
Maximum of Months 0.218143E+10 2117.89   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.314057E+10 3286.49 02-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.284873E+10 3286.49 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.338508E+10 3286.49 01-MAR-08:09 0.318374E+10 2160.58 01-MAR-08:09
April 0.302357E+10 3286.49 03-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.326282E+10 3286.49 01-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.324705E+10 3286.49 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.303934E+10 3286.49 03-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.338508E+10 3286.49 01-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.302357E+10 3286.49 01-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.314057E+10 3286.49 02-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.310376E+10 3286.49 01-NOV-07:10 0.299318E+10 2160.58 01-NOV-07:10
December 0.303934E+10 3286.49 01-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.376395E+11     0.363660E+11    
Minimum of Months 0.284873E+10 3286.49   0.277013E+10 2160.58  
Maximum of Months 0.338508E+10 3286.49   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.202386E+10 2117.89 02-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.183579E+10 2117.89 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.218143E+10 2117.89 01-MAR-08:09 0.205168E+10 1392.33 01-MAR-08:09
April 0.194846E+10 2117.89 03-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.210264E+10 2117.89 01-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.209248E+10 2117.89 01-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.195863E+10 2117.89 03-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.218143E+10 2117.89 01-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.194846E+10 2117.89 01-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.202386E+10 2117.89 02-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.200014E+10 2117.89 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.195863E+10 2117.89 01-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.242558E+11     0.234351E+11    
Minimum of Months 0.183579E+10 2117.89   0.178514E+10 1392.33  
Maximum of Months 0.218143E+10 2117.89   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.696426E+09 728.78 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.631710E+09 728.78 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.750648E+09 728.78 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.670482E+09 728.78 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.723537E+09 728.78 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.720039E+09 728.78 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.673980E+09 728.78 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.750648E+09 728.78 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.670482E+09 728.78 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.696426E+09 728.78 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.688264E+09 728.78 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.673980E+09 728.78 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.834662E+10     0.153881E+12    
Minimum of Months 0.631710E+09 728.78   0.505780E+10 1948.61  
Maximum of Months 0.750648E+09 728.78   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.696426E+09 728.78 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.631710E+09 728.78 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.750648E+09 728.78 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.670482E+09 728.78 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.723537E+09 728.78 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.720039E+09 728.78 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.673980E+09 728.78 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.750648E+09 728.78 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.670482E+09 728.78 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.696426E+09 728.78 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.688264E+09 728.78 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.673980E+09 728.78 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.834662E+10     0.153881E+12    
Minimum of Months 0.631710E+09 728.78   0.505780E+10 1948.61  
Maximum of Months 0.750648E+09 728.78   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.696426E+09 728.78 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.631710E+09 728.78 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.750648E+09 728.78 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.670482E+09 728.78 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.723537E+09 728.78 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.720039E+09 728.78 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.673980E+09 728.78 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.750648E+09 728.78 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.670482E+09 728.78 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.696426E+09 728.78 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.688264E+09 728.78 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.673980E+09 728.78 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.834662E+10     0.153881E+12    
Minimum of Months 0.631710E+09 728.78   0.505780E+10 1948.61  
Maximum of Months 0.750648E+09 728.78   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.785272E+10 8217.58 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.712300E+10 8217.58 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.846411E+10 8217.58 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.756018E+10 8217.58 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.815842E+10 8217.58 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.811897E+10 8217.58 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.759962E+10 8217.58 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.846411E+10 8217.58 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.756018E+10 8217.58 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.785272E+10 8217.58 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.776069E+10 8217.58 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.759962E+10 8217.58 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.941143E+11     0.749486E+13    
Minimum of Months 0.712300E+10 8217.58   0.246344E+12 94908.13  
Maximum of Months 0.846411E+10 8217.58   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.278508E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.252627E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.300191E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.268132E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.289349E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.287951E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.269531E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.300191E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.268132E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.278508E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.275243E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.269531E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.333789E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.252627E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.300191E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.250119E+11 0.243681E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.226877E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.269593E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.240801E+11 0.235306E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.259856E+11 0.248615E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.258600E+11 0.244160E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.242058E+11 0.239708E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.269593E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.240801E+11 0.235199E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.250119E+11 0.243735E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.247188E+11 0.238373E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.242058E+11 0.239654E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.299766E+12 0.289614E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.226877E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.269593E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.250119E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.226877E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.269593E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.240801E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.259856E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.258600E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.242058E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.269593E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.240801E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.250119E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.247188E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.242058E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.299766E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.226877E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.269593E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.250119E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.226877E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.269593E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.240801E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.259856E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.258600E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.242058E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.269593E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.240801E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.250119E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.247188E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.242058E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.299766E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.226877E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.269593E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.314050E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.231970E+10
February 0.136985E+10 0.284867E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.173995E+10
March 0.163685E+10 0.338501E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.152994E+10
April 0.145243E+10 0.302350E+10 0.295462E+10 0.00 0.00 0.00 0.00 11241128.88 0.960015E+09
May 0.157338E+10 0.326275E+10 0.312174E+10 0.00 0.00 0.00 0.00 2872530.51 0.502848E+09
June 0.156900E+10 0.324698E+10 0.306580E+10 0.00 0.00 0.00 0.00 45970277.06 0.294823E+09
July 0.145680E+10 0.303928E+10 0.300989E+10 0.00 0.00 0.00 0.00 16905872.90 0.202769E+09
August 0.163685E+10 0.338501E+10 0.318369E+10 0.00 0.00 0.00 0.00 15740825.89 0.287592E+09
September 0.145243E+10 0.302350E+10 0.295328E+10 0.00 0.00 0.00 0.00 15636399.04 0.464863E+09
October 0.150991E+10 0.314050E+10 0.306046E+10 0.00 0.00 0.00 0.00 0.00 0.946912E+09
November 0.149516E+10 0.310369E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.153335E+10
December 0.145680E+10 0.303928E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.200480E+10
                   
Annual Sum or Average 0.181194E+11 0.376387E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.108367E+09 0.127876E+11
Minimum of Months 0.136985E+10 0.284867E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.202769E+09
Maximum of Months 0.163685E+10 0.338501E+10 0.318369E+10 0.00 0.00 0.00 0.00 45970277.06 0.231970E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.202386E+10 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.154259E+10
February 0.882782E+09 0.183579E+10 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.115952E+10
March 0.105485E+10 0.218143E+10 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.101861E+10
April 0.936002E+09 0.194846E+10 0.190407E+10 0.00 0.00 0.00 0.00 9209603.49 0.634299E+09
May 0.101394E+10 0.210264E+10 0.201177E+10 0.00 0.00 0.00 0.00 2023039.12 0.333536E+09
June 0.101113E+10 0.209248E+10 0.197572E+10 0.00 0.00 0.00 0.00 32708542.28 0.190745E+09
July 0.938820E+09 0.195863E+10 0.193969E+10 0.00 0.00 0.00 0.00 13130507.90 0.125467E+09
August 0.105485E+10 0.218143E+10 0.205169E+10 0.00 0.00 0.00 0.00 12908887.34 0.176342E+09
September 0.936002E+09 0.194846E+10 0.190321E+10 0.00 0.00 0.00 0.00 11037815.70 0.310498E+09
October 0.973041E+09 0.202386E+10 0.197228E+10 0.00 0.00 0.00 0.00 0.00 0.634392E+09
November 0.963541E+09 0.200014E+10 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.101349E+10
December 0.938820E+09 0.195863E+10 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.132974E+10
                   
Annual Sum or Average 0.116768E+11 0.242558E+11 0.234352E+11 0.00 0.00 0.00 0.00 81018395.83 0.846922E+10
Minimum of Months 0.882782E+09 0.183579E+10 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.125467E+09
Maximum of Months 0.105485E+10 0.218143E+10 0.205169E+10 0.00 0.00 0.00 0.00 32708542.28 0.154259E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.314057E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.232898E+10
February 0.136988E+10 0.284873E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.175701E+10
March 0.163688E+10 0.338508E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.154501E+10
April 0.145246E+10 0.302357E+10 0.295467E+10 0.00 0.00 0.00 0.00 8219654.55 0.960068E+09
May 0.157341E+10 0.326282E+10 0.312179E+10 0.00 0.00 0.00 0.00 2830845.59 0.498801E+09
June 0.156904E+10 0.324705E+10 0.306585E+10 0.00 0.00 0.00 0.00 43826646.09 0.283404E+09
July 0.145684E+10 0.303934E+10 0.300994E+10 0.00 0.00 0.00 0.00 15153436.49 0.195314E+09
August 0.163688E+10 0.338508E+10 0.318374E+10 0.00 0.00 0.00 0.00 14480359.10 0.285578E+09
September 0.145246E+10 0.302357E+10 0.295333E+10 0.00 0.00 0.00 0.00 10127875.87 0.477488E+09
October 0.150994E+10 0.314057E+10 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.966017E+09
November 0.149520E+10 0.310376E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.153118E+10
December 0.145684E+10 0.303934E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.201993E+10
                   
Annual Sum or Average 0.181198E+11 0.376395E+11 0.363660E+11 0.00 0.00 0.00 0.00 94638817.70 0.128488E+11
Minimum of Months 0.136988E+10 0.284873E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.195314E+09
Maximum of Months 0.163688E+10 0.338508E+10 0.318374E+10 0.00 0.00 0.00 0.00 43826646.09 0.232898E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.202386E+10 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.158702E+10
February 0.882782E+09 0.183579E+10 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.120676E+10
March 0.105485E+10 0.218143E+10 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.108837E+10
April 0.936002E+09 0.194846E+10 0.190406E+10 0.00 0.00 0.00 0.00 4378743.76 0.713979E+09
May 0.101394E+10 0.210264E+10 0.201175E+10 0.00 0.00 0.00 0.00 2050497.13 0.359862E+09
June 0.101113E+10 0.209248E+10 0.197570E+10 0.00 0.00 0.00 0.00 26824493.99 0.217141E+09
July 0.938820E+09 0.195863E+10 0.193968E+10 0.00 0.00 0.00 0.00 8807424.35 0.164603E+09
August 0.105485E+10 0.218143E+10 0.205168E+10 0.00 0.00 0.00 0.00 9356150.49 0.232988E+09
September 0.936002E+09 0.194846E+10 0.190319E+10 0.00 0.00 0.00 0.00 8529789.42 0.337746E+09
October 0.973041E+09 0.202386E+10 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.670770E+09
November 0.963541E+09 0.200014E+10 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.107181E+10
December 0.938820E+09 0.195863E+10 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.140054E+10
                   
Annual Sum or Average 0.116768E+11 0.242558E+11 0.234351E+11 0.00 0.00 0.00 0.00 59947099.14 0.905160E+10
Minimum of Months 0.882782E+09 0.183579E+10 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.164603E+09
Maximum of Months 0.105485E+10 0.218143E+10 0.205168E+10 0.00 0.00 0.00 0.00 26824493.99 0.158702E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.314050E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.527479E+10
February 0.136985E+10 0.284867E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.385243E+10
March 0.163685E+10 0.338501E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.328610E+10
April 0.145243E+10 0.302350E+10 0.295462E+10 0.00 0.00 0.00 0.00 38812179.92 0.198419E+10
May 0.157338E+10 0.326275E+10 0.312174E+10 0.00 0.00 0.00 0.00 8445489.70 0.103382E+10
June 0.156900E+10 0.324698E+10 0.306580E+10 0.00 0.00 0.00 0.00 0.129474E+09 0.607435E+09
July 0.145680E+10 0.303928E+10 0.300989E+10 0.00 0.00 0.00 0.00 54539530.01 0.409269E+09
August 0.163685E+10 0.338501E+10 0.318369E+10 0.00 0.00 0.00 0.00 50565280.46 0.568478E+09
September 0.145243E+10 0.302350E+10 0.295328E+10 0.00 0.00 0.00 0.00 53434636.61 0.937375E+09
October 0.150991E+10 0.314050E+10 0.306046E+10 0.00 0.00 0.00 0.00 72412.90 0.189782E+10
November 0.149516E+10 0.310369E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.326297E+10
December 0.145680E+10 0.303928E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.441925E+10
                   
Annual Sum or Average 0.181194E+11 0.376387E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.335343E+09 0.275339E+11
Minimum of Months 0.136985E+10 0.284867E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.409269E+09
Maximum of Months 0.163685E+10 0.338501E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.129474E+09 0.527479E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.202386E+10 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.350596E+10
February 0.649041E+09 0.183579E+10 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.257328E+10
March 0.773965E+09 0.218143E+10 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.222641E+10
April 0.688021E+09 0.194846E+10 0.190407E+10 0.00 0.00 0.00 0.00 20779257.71 0.138722E+10
May 0.744847E+09 0.210264E+10 0.201177E+10 0.00 0.00 0.00 0.00 4408373.18 0.745282E+09
June 0.742030E+09 0.209248E+10 0.197572E+10 0.00 0.00 0.00 0.00 72018217.01 0.426569E+09
July 0.690839E+09 0.195863E+10 0.193969E+10 0.00 0.00 0.00 0.00 27499967.92 0.296608E+09
August 0.773965E+09 0.218143E+10 0.205169E+10 0.00 0.00 0.00 0.00 27118942.77 0.399221E+09
September 0.688021E+09 0.194846E+10 0.190321E+10 0.00 0.00 0.00 0.00 25437258.15 0.674589E+09
October 0.715730E+09 0.202386E+10 0.197228E+10 0.00 0.00 0.00 0.00 0.00 0.133340E+10
November 0.708685E+09 0.200014E+10 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.218889E+10
December 0.690839E+09 0.195863E+10 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.294321E+10
                   
Annual Sum or Average 0.858171E+10 0.242558E+11 0.234352E+11 0.00 0.00 0.00 0.00 0.177262E+09 0.187006E+11
Minimum of Months 0.649041E+09 0.183579E+10 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.296608E+09
Maximum of Months 0.773965E+09 0.218143E+10 0.205169E+10 0.00 0.00 0.00 0.00 72018217.01 0.350596E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.314057E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.533424E+10
February 0.136988E+10 0.284873E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.397442E+10
March 0.163688E+10 0.338508E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.343622E+10
April 0.145246E+10 0.302357E+10 0.295467E+10 0.00 0.00 0.00 0.00 19721522.69 0.211974E+10
May 0.157341E+10 0.326282E+10 0.312179E+10 0.00 0.00 0.00 0.00 6742079.57 0.110083E+10
June 0.156904E+10 0.324705E+10 0.306585E+10 0.00 0.00 0.00 0.00 0.109319E+09 0.619076E+09
July 0.145684E+10 0.303934E+10 0.300994E+10 0.00 0.00 0.00 0.00 39130801.75 0.429779E+09
August 0.163688E+10 0.338508E+10 0.318374E+10 0.00 0.00 0.00 0.00 34715756.36 0.617923E+09
September 0.145246E+10 0.302357E+10 0.295333E+10 0.00 0.00 0.00 0.00 23627880.82 0.105903E+10
October 0.150994E+10 0.314057E+10 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.212904E+10
November 0.149520E+10 0.310376E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.339120E+10
December 0.145684E+10 0.303934E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.454103E+10
                   
Annual Sum or Average 0.181198E+11 0.376395E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.233257E+09 0.287525E+11
Minimum of Months 0.136988E+10 0.284873E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.429779E+09
Maximum of Months 0.163688E+10 0.338508E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.109319E+09 0.533424E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.202386E+10 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.352882E+10
February 0.882782E+09 0.183579E+10 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.261436E+10
March 0.105485E+10 0.218143E+10 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.225582E+10
April 0.936002E+09 0.194846E+10 0.190406E+10 0.00 0.00 0.00 0.00 12963437.85 0.143854E+10
May 0.101394E+10 0.210264E+10 0.201175E+10 0.00 0.00 0.00 0.00 5160980.21 0.758030E+09
June 0.101113E+10 0.209248E+10 0.197570E+10 0.00 0.00 0.00 0.00 65802700.93 0.441637E+09
July 0.938820E+09 0.195863E+10 0.193968E+10 0.00 0.00 0.00 0.00 23999237.87 0.329176E+09
August 0.105485E+10 0.218143E+10 0.205168E+10 0.00 0.00 0.00 0.00 26395761.58 0.441152E+09
September 0.936002E+09 0.194846E+10 0.190319E+10 0.00 0.00 0.00 0.00 22887352.16 0.693586E+09
October 0.973041E+09 0.202386E+10 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.134271E+10
November 0.963541E+09 0.200014E+10 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.221613E+10
December 0.938820E+09 0.195863E+10 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.297557E+10
                   
Annual Sum or Average 0.116768E+11 0.242558E+11 0.234351E+11 0.00 0.00 0.00 0.00 0.157209E+09 0.190355E+11
Minimum of Months 0.882782E+09 0.183579E+10 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.329176E+09
Maximum of Months 0.105485E+10 0.218143E+10 0.205168E+10 0.00 0.00 0.00 0.00 65802700.93 0.352882E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.314050E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.652123E+10
February 0.136985E+10 0.284867E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.473427E+10
March 0.163685E+10 0.338501E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.392205E+10
April 0.145243E+10 0.302350E+10 0.295462E+10 0.00 0.00 0.00 0.00 50629373.96 0.231715E+10
May 0.157338E+10 0.326275E+10 0.312174E+10 0.00 0.00 0.00 0.00 11916146.20 0.117101E+10
June 0.156900E+10 0.324698E+10 0.306580E+10 0.00 0.00 0.00 0.00 0.166982E+09 0.681113E+09
July 0.145680E+10 0.303928E+10 0.300989E+10 0.00 0.00 0.00 0.00 76262529.19 0.454479E+09
August 0.163685E+10 0.338501E+10 0.318369E+10 0.00 0.00 0.00 0.00 73170434.21 0.632339E+09
September 0.145243E+10 0.302350E+10 0.295328E+10 0.00 0.00 0.00 0.00 74549365.16 0.104723E+10
October 0.150991E+10 0.314050E+10 0.306046E+10 0.00 0.00 0.00 0.00 493735.75 0.208109E+10
November 0.149516E+10 0.310369E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.394558E+10
December 0.145680E+10 0.303928E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.544068E+10
                   
Annual Sum or Average 0.181194E+11 0.376387E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.454004E+09 0.329482E+11
Minimum of Months 0.136985E+10 0.284867E+10 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.454479E+09
Maximum of Months 0.163685E+10 0.338501E+10 0.318369E+10 0.00 0.00 0.00 0.00 0.166982E+09 0.652123E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.202386E+10 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.434807E+10
February 0.882782E+09 0.183579E+10 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.315786E+10
March 0.105485E+10 0.218143E+10 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.263820E+10
April 0.936002E+09 0.194846E+10 0.190407E+10 0.00 0.00 0.00 0.00 26209317.48 0.161347E+10
May 0.101394E+10 0.210264E+10 0.201177E+10 0.00 0.00 0.00 0.00 5496035.93 0.844410E+09
June 0.101113E+10 0.209248E+10 0.197572E+10 0.00 0.00 0.00 0.00 89273195.62 0.484965E+09
July 0.938820E+09 0.195863E+10 0.193969E+10 0.00 0.00 0.00 0.00 35007664.07 0.339659E+09
August 0.105485E+10 0.218143E+10 0.205169E+10 0.00 0.00 0.00 0.00 36109959.58 0.450310E+09
September 0.936002E+09 0.194846E+10 0.190321E+10 0.00 0.00 0.00 0.00 33615021.72 0.753499E+09
October 0.973041E+09 0.202386E+10 0.197228E+10 0.00 0.00 0.00 0.00 4613.51 0.144595E+10
November 0.963541E+09 0.200014E+10 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.263478E+10
December 0.938820E+09 0.195863E+10 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.362826E+10
                   
Annual Sum or Average 0.116768E+11 0.242558E+11 0.234352E+11 0.00 0.00 0.00 0.00 0.225716E+09 0.223394E+11
Minimum of Months 0.882782E+09 0.183579E+10 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.339659E+09
Maximum of Months 0.105485E+10 0.218143E+10 0.205169E+10 0.00 0.00 0.00 0.00 89273195.62 0.434807E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.314057E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.656029E+10
February 0.136988E+10 0.284873E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.480701E+10
March 0.163688E+10 0.338508E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.406171E+10
April 0.145246E+10 0.302357E+10 0.295467E+10 0.00 0.00 0.00 0.00 26652306.79 0.247345E+10
May 0.157341E+10 0.326282E+10 0.312179E+10 0.00 0.00 0.00 0.00 8661841.97 0.124875E+10
June 0.156904E+10 0.324705E+10 0.306585E+10 0.00 0.00 0.00 0.00 0.144456E+09 0.698331E+09
July 0.145684E+10 0.303934E+10 0.300994E+10 0.00 0.00 0.00 0.00 55253641.14 0.481153E+09
August 0.163688E+10 0.338508E+10 0.318374E+10 0.00 0.00 0.00 0.00 48066623.30 0.692878E+09
September 0.145246E+10 0.302357E+10 0.295333E+10 0.00 0.00 0.00 0.00 32978719.22 0.119123E+10
October 0.150994E+10 0.314057E+10 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.234978E+10
November 0.149520E+10 0.310376E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.403658E+10
December 0.145684E+10 0.303934E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.551216E+10
                   
Annual Sum or Average 0.181198E+11 0.376395E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.316069E+09 0.341133E+11
Minimum of Months 0.136988E+10 0.284873E+10 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.481153E+09
Maximum of Months 0.163688E+10 0.338508E+10 0.318374E+10 0.00 0.00 0.00 0.00 0.144456E+09 0.656029E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.202386E+10 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.435876E+10
February 0.882782E+09 0.183579E+10 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.318883E+10
March 0.105485E+10 0.218143E+10 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.269484E+10
April 0.936002E+09 0.194846E+10 0.190406E+10 0.00 0.00 0.00 0.00 15623837.28 0.169739E+10
May 0.101394E+10 0.210264E+10 0.201175E+10 0.00 0.00 0.00 0.00 6014545.87 0.886888E+09
June 0.101113E+10 0.209248E+10 0.197570E+10 0.00 0.00 0.00 0.00 79207318.04 0.516968E+09
July 0.938820E+09 0.195863E+10 0.193968E+10 0.00 0.00 0.00 0.00 29445103.59 0.389027E+09
August 0.105485E+10 0.218143E+10 0.205168E+10 0.00 0.00 0.00 0.00 33057821.23 0.516557E+09
September 0.936002E+09 0.194846E+10 0.190319E+10 0.00 0.00 0.00 0.00 28798266.39 0.804650E+09
October 0.973041E+09 0.202386E+10 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.151457E+10
November 0.963541E+09 0.200014E+10 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.267015E+10
December 0.938820E+09 0.195863E+10 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.364578E+10
                   
Annual Sum or Average 0.116768E+11 0.242558E+11 0.234351E+11 0.00 0.00 0.00 0.00 0.192147E+09 0.228844E+11
Minimum of Months 0.882782E+09 0.183579E+10 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.389027E+09
Maximum of Months 0.105485E+10 0.218143E+10 0.205168E+10 0.00 0.00 0.00 0.00 79207318.04 0.435876E+10



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.696426E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.631710E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.750648E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.670482E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.723537E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.720039E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.673980E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.750648E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.670482E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.696426E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.688264E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.673980E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.834662E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.631710E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.750648E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.696426E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.631710E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.750648E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.670482E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.723537E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.720039E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.673980E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.750648E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.670482E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.696426E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.688264E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.673980E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.834662E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.631710E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.750648E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.696426E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.631710E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.750648E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.670482E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.723537E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.720039E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.673980E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.750648E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.670482E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.696426E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.688264E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.673980E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.834662E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.631710E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.750648E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.785272E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.712300E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.846411E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.756018E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.815842E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.811897E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.759962E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.846411E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.756018E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.785272E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.776069E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.759962E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.941143E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.712300E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.846411E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.506322E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.382452E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.340740E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17659950.16 0.216465E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4244836.95 0.112597E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 82587798.18 0.644827E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24040233.15 0.458454E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21580779.24 0.650691E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21078930.64 0.105005E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.213748E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.342692E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.443615E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.171193E+09 0.283903E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.458454E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 82587798.18 0.506322E+10



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.858646E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.651708E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.577103E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 39967660.36 0.366052E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8145890.89 0.193701E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.162284E+09 0.110399E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50837882.66 0.773494E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 44706320.57 0.108928E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 45836461.62 0.178553E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.358603E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.571114E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.743134E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.351779E+09 0.479529E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.773494E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.162284E+09 0.858646E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.915092E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.678656E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.586111E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22279338.45 0.362208E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3913313.01 0.196488E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.116011E+09 0.108316E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21558024.58 0.765147E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25956461.61 0.106279E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26946184.86 0.166984E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.327496E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.570814E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.770251E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.216664E+09 0.486521E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.765147E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.116011E+09 0.915092E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 29144.79 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 29144.79 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 29144.79 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 29144.79 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 29144.79 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 29144.79 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 29144.79 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 29144.79 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 29144.79 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 29144.79 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 29144.79 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 29144.79 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   29144.79   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   29144.79   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 26174.07 02-JAN-08:09 17206.63 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 26174.07 01-FEB-08:09 17206.63 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 26174.07 01-MAR-08:09 17206.63 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 26174.07 03-APR-07:10 17206.63 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 26174.07 01-MAY-07:10 17206.63 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 26174.07 01-JUN-07:10 17206.63 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 26174.07 03-JUL-07:10 17206.63 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 26174.07 01-AUG-07:10 17206.63 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 26174.07 01-SEP-07:10 17206.63 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 26174.07 02-OCT-07:10 17206.63 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 26174.07 01-NOV-07:10 17206.63 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 26174.07 01-DEC-08:09 17206.63 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   26174.07   17206.63   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   26174.07   17206.63   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 26174.07 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 26174.07 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 26174.07 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 26174.07 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 26174.07 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 26174.07 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 26174.07 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 26174.07 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 26174.07 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 26174.07 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 26174.07 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 26174.07 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   26174.07   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   26174.07   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 26174.07 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 26174.07 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 26174.07 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 26174.07 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 26174.07 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 26174.07 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 26174.07 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 26174.07 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 26174.07 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 26174.07 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 26174.07 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 26174.07 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   26174.07   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   26174.07   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 3286.42 02-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 4371.73 29-JAN-10:53
February 2010.79 01-FEB-10:09 3286.42 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 3089.81 10-FEB-22:01
March 2010.79 01-MAR-10:09 3286.42 01-MAR-08:09 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 2605.33 12-MAR-15:51
April 2010.79 03-APR-09:09 3286.42 03-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 470.29 15-APR-17:10 1950.37 02-APR-23:51
May 2010.79 01-MAY-09:09 3286.42 01-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 61.81 31-MAY-13:00 1264.50 01-MAY-24:00
June 2010.79 01-JUN-09:09 3286.42 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 554.36 18-JUN-16:20 1020.88 02-JUN-05:00
July 2010.79 03-JUL-09:09 3286.42 03-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 215.03 02-JUL-15:30 443.37 09-JUL-20:51
August 2010.79 01-AUG-09:09 3286.42 01-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 110.47 13-AUG-14:10 626.16 06-AUG-09:00
September 2010.79 01-SEP-09:09 3286.42 01-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 303.82 17-SEP-14:40 908.60 18-SEP-23:00
October 2010.79 02-OCT-09:09 3286.42 02-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 1434.35 24-OCT-04:51
November 2010.79 01-NOV-09:09 3286.42 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 3381.00 20-NOV-22:01
December 2010.79 01-DEC-10:09 3286.42 01-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 5114.41 09-DEC-01:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   3286.42   2160.55   0.00 0.00 0.00 0.00 0.00   443.37  
Maximum of Months 2010.79   3286.42   2160.55   0.00 0.00 0.00 0.00 554.36   5114.41  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 2117.89 02-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 2954.84 29-JAN-10:51
February 1295.83 01-FEB-10:09 2117.89 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 2058.91 10-FEB-22:01
March 1295.83 01-MAR-10:09 2117.89 01-MAR-08:09 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 1843.69 05-MAR-09:51
April 1295.83 03-APR-09:09 2117.89 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 360.71 15-APR-17:10 1277.06 02-APR-23:51
May 1295.83 01-MAY-09:09 2117.89 01-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 41.20 31-MAY-13:00 836.02 01-MAY-24:00
June 1295.83 01-JUN-09:09 2117.89 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 428.63 18-JUN-16:20 666.15 02-JUN-05:00
July 1295.83 03-JUL-09:09 2117.89 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 162.76 02-JUL-15:30 305.27 09-JUL-10:30
August 1295.83 01-AUG-09:09 2117.89 01-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 117.58 13-AUG-14:10 408.41 06-AUG-09:00
September 1295.83 01-SEP-09:09 2117.89 01-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 221.23 17-SEP-14:40 595.80 18-SEP-23:00
October 1295.83 02-OCT-09:09 2117.89 02-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 949.86 29-OCT-09:00
November 1295.83 01-NOV-09:09 2117.89 01-NOV-07:10 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 2252.39 20-NOV-22:01
December 1295.83 01-DEC-10:09 2117.89 01-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 3407.50 09-DEC-01:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   2117.89   1392.34   0.00 0.00 0.00 0.00 0.00   305.27  
Maximum of Months 1295.83   2117.89   1392.34   0.00 0.00 0.00 0.00 428.63   3407.50  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 3286.49 02-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 4689.44 29-JAN-13:00
February 2010.83 01-FEB-10:09 3286.49 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 3088.11 10-FEB-22:01
March 2010.83 01-MAR-10:09 3286.49 01-MAR-08:09 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 2871.78 05-MAR-13:51
April 2010.83 03-APR-09:09 3286.49 03-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 416.63 15-APR-17:10 1830.85 02-APR-23:51
May 2010.83 01-MAY-09:09 3286.49 01-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 61.81 31-MAY-13:00 1245.49 01-MAY-24:00
June 2010.83 01-JUN-09:09 3286.49 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 540.48 18-JUN-16:20 985.36 02-JUN-05:00
July 2010.83 03-JUL-09:09 3286.49 03-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 190.19 02-JUL-16:10 433.21 09-JUL-20:51
August 2010.83 01-AUG-09:09 3286.49 01-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 95.45 04-AUG-16:40 649.88 06-AUG-14:00
September 2010.83 01-SEP-09:09 3286.49 01-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 142.95 10-SEP-15:20 967.75 24-SEP-12:45
October 2010.83 02-OCT-09:09 3286.49 02-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 1381.79 24-OCT-04:51
November 2010.83 01-NOV-09:09 3286.49 01-NOV-07:10 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 3378.35 20-NOV-22:01
December 2010.83 01-DEC-10:09 3286.49 01-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 5108.52 09-DEC-01:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   3286.49   2160.58   0.00 0.00 0.00 0.00 0.00   433.21  
Maximum of Months 2010.83   3286.49   2160.58   0.00 0.00 0.00 0.00 540.48   5108.52  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 2117.89 02-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 2914.48 29-JAN-10:55
February 1295.83 01-FEB-10:09 2117.89 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 2064.82 10-FEB-22:01
March 1295.83 01-MAR-10:09 2117.89 01-MAR-08:09 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 1901.23 05-MAR-15:00
April 1295.83 03-APR-09:09 2117.89 03-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 166.54 15-APR-17:10 1400.79 02-APR-23:51
May 1295.83 01-MAY-09:09 2117.89 01-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 41.20 31-MAY-13:00 889.14 01-MAY-24:00
June 1295.83 01-JUN-09:09 2117.89 01-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 341.42 11-JUN-16:30 710.53 02-JUN-05:00
July 1295.83 03-JUL-09:09 2117.89 03-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 123.35 02-JUL-11:30 357.08 09-JUL-20:51
August 1295.83 01-AUG-09:09 2117.89 01-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 63.63 04-AUG-16:40 493.32 06-AUG-06:00
September 1295.83 01-SEP-09:09 2117.89 01-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 172.72 17-SEP-12:00 683.29 24-SEP-16:00
October 1295.83 02-OCT-09:09 2117.89 02-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 1004.46 24-OCT-04:51
November 1295.83 01-NOV-09:09 2117.89 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 2260.21 20-NOV-22:01
December 1295.83 01-DEC-10:09 2117.89 01-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 3450.97 09-DEC-01:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   2117.89   1392.33   0.00 0.00 0.00 0.00 0.00   357.08  
Maximum of Months 1295.83   2117.89   1392.33   0.00 0.00 0.00 0.00 341.42   3450.97  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 3286.42 02-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 10282.74 29-JAN-10:58
February 2010.79 01-FEB-10:09 3286.42 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 7220.97 10-FEB-22:01
March 2010.79 01-MAR-10:09 3286.42 01-MAR-08:09 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 5784.13 06-MAR-05:51
April 2010.79 03-APR-09:09 3286.42 03-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 1347.43 15-APR-17:01 4101.21 02-APR-23:54
May 2010.79 01-MAY-09:09 3286.42 01-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 165.05 29-MAY-10:00 2595.88 01-MAY-24:00
June 2010.79 01-JUN-09:09 3286.42 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 1445.56 18-JUN-16:00 2140.48 02-JUN-04:51
July 2010.79 03-JUL-09:09 3286.42 03-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 687.37 02-JUL-15:40 958.52 09-JUL-20:51
August 2010.79 01-AUG-09:09 3286.42 01-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 464.98 13-AUG-14:00 1271.95 06-AUG-09:00
September 2010.79 01-SEP-09:09 3286.42 01-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 999.52 17-SEP-15:10 1867.95 18-SEP-23:00
October 2010.79 02-OCT-09:09 3286.42 02-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 21.75 20-OCT-15:00 3321.28 24-OCT-04:53
November 2010.79 01-NOV-09:09 3286.42 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 7887.25 20-NOV-22:01
December 2010.79 01-DEC-10:09 3286.42 01-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 12059.66 09-DEC-01:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   3286.42   2160.55   0.00 0.00 0.00 0.00 0.00   958.52  
Maximum of Months 2010.79   3286.42   2160.55   0.00 0.00 0.00 0.00 1445.56   12059.66  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 2117.89 02-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 6855.36 29-JAN-10:55
February 1239.33 01-FEB-08:09 2117.89 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 4813.39 10-FEB-22:01
March 1239.33 01-MAR-08:09 2117.89 01-MAR-08:09 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 3854.46 06-MAR-05:51
April 1239.33 03-APR-07:10 2117.89 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 836.98 15-APR-17:10 2734.11 02-APR-23:56
May 1239.33 01-MAY-07:10 2117.89 01-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 94.88 31-MAY-13:00 1761.50 01-MAY-24:00
June 1239.33 01-JUN-07:10 2117.89 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 985.52 18-JUN-16:20 1445.09 02-JUN-04:51
July 1239.33 03-JUL-07:10 2117.89 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 354.40 02-JUL-15:40 698.27 04-JUL-09:30
August 1239.33 01-AUG-07:10 2117.89 01-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 297.52 13-AUG-14:00 879.24 06-AUG-09:00
September 1239.33 01-SEP-07:10 2117.89 01-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 494.31 17-SEP-15:10 1256.02 18-SEP-23:00
October 1239.33 02-OCT-07:10 2117.89 02-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 2220.10 24-OCT-04:53
November 1239.33 01-NOV-07:10 2117.89 01-NOV-07:10 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 5257.18 20-NOV-22:01
December 1239.33 01-DEC-08:09 2117.89 01-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 8039.67 09-DEC-01:59
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   2117.89   1392.34   0.00 0.00 0.00 0.00 0.00   698.27  
Maximum of Months 1239.33   2117.89   1392.34   0.00 0.00 0.00 0.00 985.52   8039.67  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 3286.49 02-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 10375.73 29-JAN-12:51
February 2010.83 01-FEB-10:09 3286.49 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 7225.41 10-FEB-22:01
March 2010.83 01-MAR-10:09 3286.49 01-MAR-08:09 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 6181.46 05-MAR-14:00
April 2010.83 03-APR-09:09 3286.49 03-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 1001.86 15-APR-17:10 4101.14 02-APR-23:51
May 2010.83 01-MAY-09:09 3286.49 01-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 142.32 31-MAY-13:00 2659.15 01-MAY-24:00
June 2010.83 01-JUN-09:09 3286.49 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 1326.06 18-JUN-16:20 2166.58 02-JUN-04:51
July 2010.83 03-JUL-09:09 3286.49 03-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 464.78 02-JUL-16:20 984.17 09-JUL-20:51
August 2010.83 01-AUG-09:09 3286.49 01-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 220.32 04-AUG-16:40 1446.93 06-AUG-14:00
September 2010.83 01-SEP-09:09 3286.49 01-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 280.14 10-SEP-14:53 2199.50 24-SEP-13:40
October 2010.83 02-OCT-09:09 3286.49 02-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 3327.35 24-OCT-04:53
November 2010.83 01-NOV-09:09 3286.49 01-NOV-07:10 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 7892.51 20-NOV-22:01
December 2010.83 01-DEC-10:09 3286.49 01-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 12059.52 09-DEC-01:57
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   3286.49   2160.58   0.00 0.00 0.00 0.00 0.00   984.17  
Maximum of Months 2010.83   3286.49   2160.58   0.00 0.00 0.00 0.00 1326.06   12059.52  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 2117.89 02-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 6855.17 29-JAN-10:59
February 1295.83 01-FEB-10:09 2117.89 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 4814.51 10-FEB-22:01
March 1295.83 01-MAR-10:09 2117.89 01-MAR-08:09 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 3861.13 06-MAR-05:51
April 1295.83 03-APR-09:09 2117.89 03-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 527.10 16-APR-13:10 2734.15 02-APR-23:57
May 1295.83 01-MAY-09:09 2117.89 01-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 122.00 29-MAY-10:00 1768.46 01-MAY-24:00
June 1295.83 01-JUN-09:09 2117.89 01-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 754.24 25-JUN-12:10 1431.18 02-JUN-04:51
July 1295.83 03-JUL-09:09 2117.89 03-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 390.27 02-JUL-11:00 728.70 09-JUL-20:51
August 1295.83 01-AUG-09:09 2117.89 01-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 177.11 13-AUG-13:20 930.69 06-AUG-09:00
September 1295.83 01-SEP-09:09 2117.89 01-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 466.84 17-SEP-11:50 1480.05 24-SEP-17:18
October 1295.83 02-OCT-09:09 2117.89 02-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 2208.81 24-OCT-04:53
November 1295.83 01-NOV-09:09 2117.89 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 5260.36 20-NOV-22:01
December 1295.83 01-DEC-10:09 2117.89 01-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 8039.74 09-DEC-01:58
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   2117.89   1392.33   0.00 0.00 0.00 0.00 0.00   728.70  
Maximum of Months 1295.83   2117.89   1392.33   0.00 0.00 0.00 0.00 754.24   8039.74  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 3286.42 02-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 12804.69 29-JAN-10:59
February 2010.79 01-FEB-10:09 3286.42 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 8957.68 10-FEB-22:01
March 2010.79 01-MAR-10:09 3286.42 01-MAR-08:09 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 7162.91 06-MAR-05:51
April 2010.79 03-APR-09:09 3286.42 03-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 1715.12 15-APR-17:01 5068.05 03-APR-00:03
May 2010.79 01-MAY-09:09 3286.42 01-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 256.22 29-MAY-10:30 3005.07 02-MAY-05:00
June 2010.79 01-JUN-09:09 3286.42 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 1933.58 18-JUN-16:00 2646.62 02-JUN-04:54
July 2010.79 03-JUL-09:09 3286.42 03-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 859.36 02-JUL-15:20 1118.24 09-JUL-20:51
August 2010.79 01-AUG-09:09 3286.42 01-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 692.60 13-AUG-14:00 1405.21 06-AUG-09:00
September 2010.79 01-SEP-09:09 3286.42 01-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 1327.31 17-SEP-15:00 2108.21 18-SEP-23:00
October 2010.79 02-OCT-09:09 3286.42 02-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 91.64 01-OCT-14:41 4048.84 24-OCT-04:43
November 2010.79 01-NOV-09:09 3286.42 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 9787.58 20-NOV-22:01
December 2010.79 01-DEC-10:09 3286.42 01-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 14736.99 09-DEC-01:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   3286.42   2160.55   0.00 0.00 0.00 0.00 0.00   1118.24  
Maximum of Months 2010.79   3286.42   2160.55   0.00 0.00 0.00 0.00 1933.58   14736.99  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 2117.89 02-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 8536.56 29-JAN-10:54
February 1295.83 01-FEB-10:09 2117.89 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 5970.43 10-FEB-22:01
March 1295.83 01-MAR-10:09 2117.89 01-MAR-08:09 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 4773.05 06-MAR-05:51
April 1295.83 03-APR-09:09 2117.89 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 1047.87 15-APR-17:10 3378.46 03-APR-00:03
May 1295.83 01-MAY-09:09 2117.89 01-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 115.62 31-MAY-13:00 2003.42 02-MAY-04:58
June 1295.83 01-JUN-09:09 2117.89 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 1263.32 18-JUN-16:00 1764.45 02-JUN-04:54
July 1295.83 03-JUL-09:09 2117.89 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 463.37 02-JUL-16:00 869.35 04-JUL-09:30
August 1295.83 01-AUG-09:09 2117.89 01-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 388.96 13-AUG-14:00 975.59 06-AUG-09:00
September 1295.83 01-SEP-09:09 2117.89 01-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 700.23 17-SEP-15:00 1419.04 18-SEP-23:00
October 1295.83 02-OCT-09:09 2117.89 02-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 5.37 20-OCT-15:00 2699.20 24-OCT-04:44
November 1295.83 01-NOV-09:09 2117.89 01-NOV-07:10 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 6524.10 20-NOV-22:01
December 1295.83 01-DEC-10:09 2117.89 01-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 9822.26 09-DEC-01:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   2117.89   1392.34   0.00 0.00 0.00 0.00 0.00   869.35  
Maximum of Months 1295.83   2117.89   1392.34   0.00 0.00 0.00 0.00 1263.32   9822.26  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 3286.49 02-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 12804.74 29-JAN-10:55
February 2010.83 01-FEB-10:09 3286.49 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 8964.27 10-FEB-22:01
March 2010.83 01-MAR-10:09 3286.49 01-MAR-08:09 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 7173.77 05-MAR-14:00
April 2010.83 03-APR-09:09 3286.49 03-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 1307.65 15-APR-17:10 5068.23 03-APR-00:03
May 2010.83 01-MAY-09:09 3286.49 01-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 173.43 31-MAY-13:00 3005.20 02-MAY-05:00
June 2010.83 01-JUN-09:09 3286.49 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 1793.16 18-JUN-16:00 2646.67 02-JUN-04:56
July 2010.83 03-JUL-09:09 3286.49 03-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 737.52 02-JUL-16:00 1148.94 09-JUL-20:51
August 2010.83 01-AUG-09:09 3286.49 01-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 341.68 05-AUG-17:10 1713.70 06-AUG-13:50
September 2010.83 01-SEP-09:09 3286.49 01-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 565.79 10-SEP-15:20 2383.11 24-SEP-14:00
October 2010.83 02-OCT-09:09 3286.49 02-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 4048.83 24-OCT-04:47
November 2010.83 01-NOV-09:09 3286.49 01-NOV-07:10 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 9793.68 20-NOV-22:01
December 2010.83 01-DEC-10:09 3286.49 01-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 14744.61 09-DEC-01:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   3286.49   2160.58   0.00 0.00 0.00 0.00 0.00   1148.94  
Maximum of Months 2010.83   3286.49   2160.58   0.00 0.00 0.00 0.00 1793.16   14744.61  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 2117.89 02-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 8536.43 29-JAN-11:00
February 1295.83 01-FEB-10:09 2117.89 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 5975.34 10-FEB-22:01
March 1295.83 01-MAR-10:09 2117.89 01-MAR-08:09 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 4783.43 06-MAR-05:51
April 1295.83 03-APR-09:09 2117.89 03-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 726.48 16-APR-13:10 3378.41 03-APR-00:03
May 1295.83 01-MAY-09:09 2117.89 01-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 147.25 29-MAY-10:30 2017.72 01-MAY-24:00
June 1295.83 01-JUN-09:09 2117.89 01-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 954.13 11-JUN-15:05 1764.39 02-JUN-04:59
July 1295.83 03-JUL-09:09 2117.89 03-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 464.85 02-JUL-11:20 871.11 09-JUL-20:51
August 1295.83 01-AUG-09:09 2117.89 01-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 216.18 13-AUG-13:20 1054.20 06-AUG-09:00
September 1295.83 01-SEP-09:09 2117.89 01-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 585.53 17-SEP-11:40 1830.67 24-SEP-17:22
October 1295.83 02-OCT-09:09 2117.89 02-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 2699.05 24-OCT-04:50
November 1295.83 01-NOV-09:09 2117.89 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 6530.20 20-NOV-22:01
December 1295.83 01-DEC-10:09 2117.89 01-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 9828.66 09-DEC-01:51
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   2117.89   1392.33   0.00 0.00 0.00 0.00 0.00   871.11  
Maximum of Months 1295.83   2117.89   1392.33   0.00 0.00 0.00 0.00 954.13   9828.66  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 728.78 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 728.78 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 728.78 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 728.78 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 728.78 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 728.78 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 728.78 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 728.78 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 728.78 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 728.78 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 728.78 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 728.78 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   728.78   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   728.78   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 728.78 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 728.78 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 728.78 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 728.78 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 728.78 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 728.78 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 728.78 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 728.78 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 728.78 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 728.78 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 728.78 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 728.78 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   728.78   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   728.78   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 728.78 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 728.78 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 728.78 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 728.78 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 728.78 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 728.78 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 728.78 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 728.78 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 728.78 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 728.78 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 728.78 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 728.78 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   728.78   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   728.78   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 8217.58 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 8217.58 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 8217.58 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 8217.58 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 8217.58 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 8217.58 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 8217.58 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 8217.58 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 8217.58 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 8217.58 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 8217.58 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 8217.58 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   8217.58   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   8217.58   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 9443.57 29-JAN-10:51
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 6589.79 10-FEB-22:01
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 5730.68 12-MAR-15:51
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 800.38 15-APR-17:01 4508.40 02-APR-23:51
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 108.46 31-MAY-13:00 2873.07 01-MAY-24:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1035.68 11-JUN-14:51 2354.95 02-JUN-05:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 332.90 02-JUL-15:10 918.02 09-JUL-20:51
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 166.52 04-AUG-16:40 1306.25 06-AUG-06:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 354.78 17-SEP-15:00 2063.36 18-SEP-23:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 3330.40 24-OCT-04:51
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 7180.66 20-NOV-22:01
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 11599.50 09-DEC-02:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   918.02  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1035.68   11599.50  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 16238.12 29-JAN-11:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 11626.11 10-FEB-22:01
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 9509.13 12-MAR-15:51
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1618.45 15-APR-17:01 7273.66 02-APR-23:51
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 196.53 31-MAY-13:00 4895.58 01-MAY-24:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1965.75 11-JUN-15:00 4186.04 02-JUN-04:51
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 689.39 02-JUL-16:00 1566.83 09-JUL-20:51
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 296.99 04-AUG-16:40 2214.93 06-AUG-06:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 786.08 17-SEP-14:51 3559.83 18-SEP-23:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 5534.03 24-OCT-04:51
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 12222.71 20-NOV-22:01
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 19907.30 09-DEC-01:51
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   1566.83  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1965.75   19907.30  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 17437.46 29-JAN-11:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 12583.11 10-FEB-22:01
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 9748.92 20-MAR-21:01
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1479.91 15-APR-17:10 6864.17 02-APR-23:51
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 147.99 31-MAY-13:00 4576.31 01-MAY-24:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1630.84 18-JUN-16:00 3907.76 02-JUN-05:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 489.77 25-JUL-21:02 1748.91 09-JUL-12:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 279.77 04-AUG-16:30 2406.23 06-AUG-13:50
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 364.52 10-SEP-15:00 3339.53 18-SEP-23:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 5207.12 24-OCT-04:51
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 13654.78 20-NOV-22:01
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 20366.00 09-DEC-01:51
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   1748.91  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1630.84   20366.00  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 124702.25 14-JAN-06:01 12566.58 22668.17 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
February 123244.69 24-FEB-06:01 17952.25 32383.10 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
March 120310.84 25-MAR-05:01 17952.25 32383.10 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
April 113138.40 19-APR-13:24 89161.06 145723.95 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
May 125089.30 18-MAY-05:02 8976.13 16191.55 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
June 133453.03 19-JUN-04:11 0.00 32383.10 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
July 121305.34 24-JUL-04:11 0.00 32383.10 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
August 122927.14 07-AUG-04:12 0.00 19429.86 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
September 133566.64 27-SEP-04:11 0.00 29144.79 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
October 137659.95 23-OCT-03:01 0.00 16191.55 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
November 135351.93 01-NOV-04:11 0.00 32383.10 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
December 112070.72 04-DEC-05:01 0.00 22668.17 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 112070.72   0.00 16191.55 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 137659.95   89161.06 145723.95 134575.44 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 35261.86 13-JAN-16:55 30632.53 52348.14 34413.26 0.00 0.00 0.00 0.00 0.00 0.00
February 97582.52 25-FEB-06:01 16122.38 29082.30 76473.90 0.00 0.00 0.00 0.00 0.00 0.00
March 106365.89 30-MAR-05:01 16122.38 29082.30 76473.90 0.00 0.00 0.00 0.00 0.00 0.00
April 112600.27 17-APR-04:11 0.00 20357.61 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
May 111408.00 30-MAY-04:12 0.00 17449.38 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
June 115990.49 28-JUN-04:11 0.00 29082.30 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
July 116389.55 19-JUL-04:11 0.00 29082.30 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
August 117402.96 15-AUG-04:11 0.00 20357.61 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
September 115726.76 01-SEP-04:11 0.00 20357.61 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
October 109575.37 11-OCT-04:11 0.00 29082.30 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
November 109538.13 08-NOV-05:11 0.00 29082.30 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
December 42223.81 05-DEC-16:15 61265.06 104696.28 68826.51 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 35261.86   0.00 17449.38 34413.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 117402.96   61265.06 104696.28 76473.90 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 28456.77 13-JAN-16:55 30632.53 52348.14 34413.13 0.00 0.00 0.00 0.00 0.00 0.00
February 29143.87 24-FEB-16:52 122530.12 209392.56 137652.50 0.00 0.00 0.00 0.00 0.00 0.00
March 89702.57 24-MAR-05:01 16122.38 29082.30 76473.61 0.00 0.00 0.00 0.00 0.00 0.00
April 98619.05 17-APR-05:01 12897.91 23265.84 61178.89 0.00 0.00 0.00 0.00 0.00 0.00
May 102298.75 13-MAY-05:01 14510.15 26174.07 68826.25 0.00 0.00 0.00 0.00 0.00 0.00
June 107596.43 29-JUN-04:11 0.00 29082.30 59376.23 0.00 0.00 0.00 0.00 0.00 0.00
July 105790.21 01-JUL-04:11 0.00 14541.15 44532.17 0.00 0.00 0.00 0.00 0.00 0.00
August 102745.07 11-AUG-04:11 0.00 20357.61 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
September 103697.97 08-SEP-04:11 0.00 20357.61 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
October 94961.42 21-OCT-05:01 16122.38 29082.30 76473.61 0.00 0.00 0.00 0.00 0.00 0.00
November 94464.67 09-NOV-06:01 16122.38 29082.30 76473.61 0.00 0.00 0.00 0.00 0.00 0.00
December 25689.96 07-DEC-16:53 61265.06 104696.28 68826.25 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 25689.96   0.00 14541.15 34413.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 107596.43   122530.12 209392.56 137652.50 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 23505.48 13-JAN-17:00 30632.53 52348.14 34413.13 0.00 0.00 0.00 0.00 0.00 0.00
February 25549.76 24-FEB-17:00 122530.12 209392.56 137652.50 0.00 0.00 0.00 0.00 0.00 0.00
March 32688.99 24-MAR-15:53 153162.65 261740.70 172065.63 0.00 0.00 0.00 0.00 0.00 0.00
April 53703.53 18-APR-15:50 15316.26 26174.07 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
May 91174.43 31-MAY-05:02 8061.19 14541.15 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
June 129304.36 14-JUN-05:01 16122.38 29082.30 76473.61 0.00 0.00 0.00 0.00 0.00 0.00
July 122374.22 28-JUL-05:01 16122.38 29082.30 76473.61 0.00 0.00 0.00 0.00 0.00 0.00
August 129417.28 03-AUG-04:01 0.00 20357.61 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
September 121041.59 12-SEP-05:02 9673.43 17449.38 45884.17 0.00 0.00 0.00 0.00 0.00 0.00
October 36144.59 20-OCT-16:00 15316.26 26174.07 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
November 32269.58 03-NOV-15:53 61265.06 104696.28 68826.25 0.00 0.00 0.00 0.00 0.00 0.00
December 23143.19 01-DEC-16:30 61265.06 104696.28 68826.25 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 23143.19   0.00 14541.15 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 129417.28   153162.65 261740.70 172065.63 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3826.02 13-JAN-14:20 4021.58 6572.83 4321.10 0.00 0.00 0.00 0.00 0.00 213.98
February 4241.87 24-FEB-15:30 15384.88 26291.33 17284.41 0.00 0.00 0.00 0.00 0.00 135.89
March 6411.26 19-MAR-13:21 1012.16 1825.79 7201.84 0.00 0.00 0.00 0.00 0.00 355.58
April 10964.84 18-APR-15:00 1923.11 3286.42 2160.55 0.00 0.00 0.00 0.00 92.16 0.00
May 10904.01 31-MAY-14:50 1923.11 3286.42 2160.55 0.00 0.00 0.00 0.00 55.84 0.00
June 19433.48 25-JUN-18:31 0.00 1643.21 5032.54 0.00 0.00 0.00 0.00 180.65 0.00
July 12187.37 03-JUL-13:40 2010.79 3286.42 2160.55 0.00 0.00 0.00 0.00 18.34 0.00
August 12610.50 04-AUG-15:20 1923.11 3286.42 2160.55 0.00 0.00 0.00 0.00 74.41 0.00
September 14441.78 11-SEP-04:11 0.00 2556.10 5218.93 0.00 0.00 0.00 0.00 0.00 209.13
October 6453.39 01-OCT-14:51 1012.16 1825.79 7201.84 0.00 0.00 0.00 0.00 0.00 203.69
November 6335.99 09-NOV-06:02 2024.33 3651.57 9602.45 0.00 0.00 0.00 0.00 0.00 158.04
December 3577.10 01-DEC-06:03 1417.03 2556.10 6721.72 0.00 0.00 0.00 0.00 0.00 287.49
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3577.10   0.00 1643.21 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19433.48   15384.88 26291.33 17284.41 0.00 0.00 0.00 0.00 180.65 355.58



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3999.50 12-JAN-10:13 3887.49 6353.67 4177.03 0.00 0.00 0.00 0.00 0.00 157.43
February 6236.30 24-FEB-09:31 12393.25 21178.91 13923.42 0.00 0.00 0.00 0.00 0.00 116.98
March 9382.68 28-MAR-09:03 12958.30 21178.91 13923.42 0.00 0.00 0.00 0.00 0.00 229.05
April 26246.06 30-APR-08:32 391.37 705.96 2784.68 0.00 0.00 0.00 0.00 0.00 174.14
May 28737.87 29-MAY-09:01 456.59 823.62 3248.80 0.00 0.00 0.00 0.00 0.00 45.00
June 32153.56 25-JUN-07:51 521.82 941.28 3712.91 0.00 0.00 0.00 0.00 0.00 153.37
July 33138.61 02-JUL-08:41 587.05 1058.95 4177.03 0.00 0.00 0.00 0.00 0.00 99.80
August 30598.39 27-AUG-09:11 456.59 823.62 3248.80 0.00 0.00 0.00 0.00 0.00 60.31
September 21256.85 04-SEP-08:52 326.14 588.30 2320.57 0.00 0.00 0.00 0.00 0.00 107.68
October 10541.53 01-OCT-08:48 652.28 1176.61 4641.14 0.00 0.00 0.00 0.00 0.00 371.91
November 5650.48 09-NOV-05:11 0.00 2353.21 4804.68 0.00 0.00 0.00 0.00 0.00 375.70
December 4242.75 05-DEC-09:40 4957.30 8471.56 5569.37 0.00 0.00 0.00 0.00 0.00 541.63
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3999.50   0.00 588.30 2320.57 0.00 0.00 0.00 0.00 0.00 45.00
Maximum of Months 33138.61   12958.30 21178.91 13923.42 0.00 0.00 0.00 0.00 0.00 541.63



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 15112.47 12-JAN-12:30 1058.33 3286.49 1920.52 0.00 0.00 0.00 0.00 0.00 197.21
February 19931.08 24-FEB-13:23 15385.22 26291.90 17284.68 0.00 0.00 0.00 0.00 0.00 154.75
March 33268.89 19-MAR-12:41 1012.19 1825.83 7201.95 0.00 0.00 0.00 0.00 0.00 585.51
April 34708.58 16-APR-11:32 607.31 1095.50 4321.17 0.00 0.00 0.00 0.00 0.00 219.33
May 23478.78 29-MAY-12:22 607.31 1095.50 4321.17 0.00 0.00 0.00 0.00 0.00 52.07
June 34592.98 25-JUN-13:51 708.53 1278.08 5041.36 0.00 0.00 0.00 0.00 269.37 0.00
July 34307.85 02-JUL-12:42 607.31 1095.50 4321.17 0.00 0.00 0.00 0.00 37.45 0.00
August 25063.17 13-AUG-11:21 708.53 1278.08 5041.36 0.00 0.00 0.00 0.00 0.00 229.95
September 34678.20 10-SEP-14:31 708.53 1278.08 5041.36 0.00 0.00 0.00 0.00 0.00 11.74
October 35982.21 29-OCT-13:21 1012.19 1825.83 7201.95 0.00 0.00 0.00 0.00 0.00 1104.20
November 32885.93 12-NOV-12:31 1012.19 1825.83 7201.95 0.00 0.00 0.00 0.00 0.00 671.53
December 25795.94 03-DEC-13:12 506.09 912.91 3600.97 0.00 0.00 0.00 0.00 0.00 1581.91
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 15112.47   506.09 912.91 1920.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 35982.21   15385.22 26291.90 17284.68 0.00 0.00 0.00 0.00 269.37 1581.91



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5895.14 12-JAN-15:40 1239.33 2117.89 1392.33 0.00 0.00 0.00 0.00 0.00 176.57
February 10002.01 24-FEB-16:21 9914.60 16943.13 11138.66 0.00 0.00 0.00 0.00 0.00 99.92
March 11733.17 19-MAR-16:03 652.28 1176.61 4641.11 0.00 0.00 0.00 0.00 0.00 311.49
April 42036.42 16-APR-16:11 652.28 1176.61 4641.11 0.00 0.00 0.00 0.00 0.00 72.10
May 38508.26 21-MAY-16:21 521.82 941.28 3712.89 0.00 0.00 0.00 0.00 0.00 229.83
June 42746.18 25-JUN-17:11 0.00 1176.61 3603.49 0.00 0.00 0.00 0.00 65.02 0.00
July 43262.52 02-JUL-16:41 652.28 1176.61 4641.11 0.00 0.00 0.00 0.00 0.00 36.23
August 36780.93 13-AUG-16:01 456.59 823.62 3248.78 0.00 0.00 0.00 0.00 0.00 68.15
September 33277.80 10-SEP-14:31 456.59 823.62 3248.78 0.00 0.00 0.00 0.00 22.72 0.00
October 33610.45 01-OCT-16:11 652.28 1176.61 4641.11 0.00 0.00 0.00 0.00 0.00 277.86
November 10982.92 03-NOV-15:23 12393.25 21178.91 13923.33 0.00 0.00 0.00 0.00 0.00 61.43
December 6675.82 01-DEC-15:23 4957.30 8471.56 5569.33 0.00 0.00 0.00 0.00 0.00 113.13
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5895.14   0.00 823.62 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 43262.52   12393.25 21178.91 13923.33 0.00 0.00 0.00 0.00 65.02 311.49



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5030.61 11-JAN-06:04 1619.46 2921.26 7681.96 0.00 0.00 0.00 0.00 0.00 441.47
February 4846.95 14-FEB-06:04 2024.33 3651.57 9602.45 0.00 0.00 0.00 0.00 0.00 487.25
March 5865.50 28-MAR-15:30 1923.11 3286.42 2160.55 0.00 0.00 0.00 0.00 0.00 289.24
April 10094.88 16-APR-16:21 708.51 1278.05 5041.29 0.00 0.00 0.00 0.00 910.64 0.00
May 10423.22 31-MAY-15:00 1923.11 3286.42 2160.55 0.00 0.00 0.00 0.00 130.70 0.00
June 11850.11 26-JUN-14:30 1923.11 3286.42 2160.55 0.00 0.00 0.00 0.00 149.11 0.00
July 10956.37 26-JUL-15:20 1923.11 3286.42 2160.55 0.00 0.00 0.00 0.00 118.70 0.00
August 11834.59 04-AUG-15:30 1923.11 3286.42 2160.55 0.00 0.00 0.00 0.00 172.58 0.00
September 10265.69 11-SEP-14:30 1923.11 3286.42 2160.55 0.00 0.00 0.00 0.00 186.12 0.00
October 7136.14 01-OCT-15:01 1012.16 1825.79 7201.84 0.00 0.00 0.00 0.00 0.00 235.88
November 6805.14 08-NOV-06:01 2024.33 3651.57 9602.45 0.00 0.00 0.00 0.00 0.00 148.16
December 5075.71 30-DEC-06:03 1821.89 3286.42 8642.21 0.00 0.00 0.00 0.00 0.00 403.08
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4846.95   708.51 1278.05 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11850.11   2024.33 3651.57 9602.45 0.00 0.00 0.00 0.00 910.64 487.25



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4631.78 12-JAN-11:02 4957.30 8471.56 5569.37 0.00 0.00 0.00 0.00 0.00 430.31
February 13105.47 24-FEB-11:01 12393.25 21178.91 13923.42 0.00 0.00 0.00 0.00 0.00 301.31
March 17504.61 28-MAR-10:01 12393.25 21178.91 13923.42 0.00 0.00 0.00 0.00 0.00 436.20
April 21095.39 30-APR-09:02 391.37 705.96 2784.68 0.00 0.00 0.00 0.00 0.00 405.62
May 29725.76 14-MAY-08:52 391.37 705.96 2784.68 0.00 0.00 0.00 0.00 0.00 509.77
June 31266.32 25-JUN-09:22 391.37 705.96 2784.68 0.00 0.00 0.00 0.00 0.00 46.38
July 34218.91 30-JUL-09:21 521.82 941.28 3712.91 0.00 0.00 0.00 0.00 0.00 166.38
August 32132.56 20-AUG-09:01 456.59 823.62 3248.80 0.00 0.00 0.00 0.00 0.00 347.62
September 30732.21 04-SEP-08:41 456.59 823.62 3248.80 0.00 0.00 0.00 0.00 0.00 281.44
October 14534.15 20-OCT-10:01 8675.28 14825.24 9746.39 0.00 0.00 0.00 0.00 0.00 122.36
November 12878.08 04-NOV-10:01 3913.66 7059.64 7735.23 0.00 0.00 0.00 0.00 0.00 214.64
December 4175.53 01-DEC-11:02 4957.30 8471.56 5569.37 0.00 0.00 0.00 0.00 0.00 527.33
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4175.53   391.37 705.96 2784.68 0.00 0.00 0.00 0.00 0.00 46.38
Maximum of Months 34218.91   12393.25 21178.91 13923.42 0.00 0.00 0.00 0.00 0.00 527.33



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 15509.83 12-JAN-12:40 1058.33 3286.49 1920.52 0.00 0.00 0.00 0.00 0.00 421.98
February 22012.65 24-FEB-13:32 19231.52 32864.88 21605.85 0.00 0.00 0.00 0.00 0.00 373.89
March 31658.92 19-MAR-13:11 1012.19 1825.83 7201.95 0.00 0.00 0.00 0.00 0.00 1391.28
April 31983.54 16-APR-13:42 506.09 912.91 3600.97 0.00 0.00 0.00 0.00 102.75 0.00
May 18089.69 30-MAY-13:30 2010.83 3286.49 2160.58 0.00 0.00 0.00 0.00 42.56 0.00
June 18772.75 30-JUN-13:10 4021.67 6572.98 4321.17 0.00 0.00 0.00 0.00 74.95 0.00
July 41232.62 30-JUL-14:01 809.75 1460.66 5761.56 0.00 0.00 0.00 0.00 0.50 0.00
August 41695.74 13-AUG-13:11 708.53 1278.08 5041.36 0.00 0.00 0.00 0.00 0.00 255.69
September 45539.79 17-SEP-14:21 809.75 1460.66 5761.56 0.00 0.00 0.00 0.00 0.00 318.54
October 45667.80 01-OCT-13:41 1012.19 1825.83 7201.95 0.00 0.00 0.00 0.00 0.00 1266.06
November 23460.94 03-NOV-13:30 20108.34 32864.88 21605.85 0.00 0.00 0.00 0.00 0.00 236.24
December 17778.94 01-DEC-13:23 7692.61 13145.95 8642.34 0.00 0.00 0.00 0.00 0.00 590.56
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 15509.83   506.09 912.91 1920.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 45667.80   20108.34 32864.88 21605.85 0.00 0.00 0.00 0.00 102.75 1391.28



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4800.69 12-JAN-15:50 1239.33 2117.89 1392.33 0.00 0.00 0.00 0.00 0.00 414.82
February 7963.85 24-FEB-16:22 9914.60 16943.13 11138.66 0.00 0.00 0.00 0.00 0.00 235.92
March 8097.71 23-MAR-15:53 12393.25 21178.91 13923.33 0.00 0.00 0.00 0.00 0.00 231.01
April 33692.38 16-APR-16:21 456.59 823.62 3248.78 0.00 0.00 0.00 0.00 155.59 0.00
May 37022.61 14-MAY-17:01 0.00 1058.95 3243.14 0.00 0.00 0.00 0.00 0.00 243.78
June 35576.87 25-JUN-16:41 456.59 823.62 3248.78 0.00 0.00 0.00 0.00 396.86 0.00
July 35100.77 02-JUL-16:51 456.59 823.62 3248.78 0.00 0.00 0.00 0.00 55.80 0.00
August 34563.85 13-AUG-16:31 652.28 1176.61 4641.11 0.00 0.00 0.00 0.00 0.00 183.02
September 35604.67 04-SEP-17:21 0.00 941.28 2882.79 0.00 0.00 0.00 0.00 0.00 158.46
October 12018.06 20-OCT-15:30 1239.33 2117.89 1392.33 0.00 0.00 0.00 0.00 0.00 33.43
November 8206.86 03-NOV-15:22 12393.25 21178.91 13923.33 0.00 0.00 0.00 0.00 0.00 145.93
December 4801.17 01-DEC-15:40 4957.30 8471.56 5569.33 0.00 0.00 0.00 0.00 0.00 240.79
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4800.69   0.00 823.62 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 37022.61   12393.25 21178.91 13923.33 0.00 0.00 0.00 0.00 396.86 414.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5577.65 14-JAN-17:01 809.73 1460.63 5761.47 0.00 0.00 0.00 0.00 0.00 1006.47
February 6612.02 25-FEB-06:03 2024.33 3651.57 9602.45 0.00 0.00 0.00 0.00 0.00 490.32
March 6865.74 28-MAR-15:30 1923.11 3286.42 2160.55 0.00 0.00 0.00 0.00 0.00 327.59
April 13199.80 16-APR-16:21 708.51 1278.05 5041.29 0.00 0.00 0.00 0.00 1095.09 0.00
May 11774.72 31-MAY-15:00 1923.11 3286.42 2160.55 0.00 0.00 0.00 0.00 159.27 0.00
June 15668.61 25-JUN-17:41 0.00 1825.79 5591.71 0.00 0.00 0.00 0.00 854.67 0.00
July 14591.60 02-JUL-17:51 0.00 1825.79 5591.71 0.00 0.00 0.00 0.00 345.69 0.00
August 13336.83 04-AUG-15:30 1923.11 3286.42 2160.55 0.00 0.00 0.00 0.00 211.89 0.00
September 12929.57 17-SEP-14:11 809.73 1460.63 5761.47 0.00 0.00 0.00 0.00 693.67 0.00
October 7543.60 01-OCT-14:31 1012.16 1825.79 7201.84 0.00 0.00 0.00 0.00 0.00 74.09
November 6715.94 07-NOV-06:02 1619.46 2921.26 7681.96 0.00 0.00 0.00 0.00 0.00 158.78
December 5678.74 02-DEC-17:01 708.51 1278.05 5041.29 0.00 0.00 0.00 0.00 0.00 279.53
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5577.65   0.00 1278.05 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15668.61   2024.33 3651.57 9602.45 0.00 0.00 0.00 0.00 1095.09 1006.47



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3614.55 14-JAN-17:01 521.82 941.28 3712.91 0.00 0.00 0.00 0.00 0.00 670.99
February 4960.29 24-FEB-10:20 12958.30 21178.91 13923.42 0.00 0.00 0.00 0.00 0.00 308.74
March 6049.79 28-MAR-10:00 12958.30 21178.91 13923.42 0.00 0.00 0.00 0.00 0.00 543.46
April 14432.81 18-APR-09:40 1295.83 2117.89 1392.34 0.00 0.00 0.00 0.00 20.46 0.00
May 23119.46 29-MAY-09:01 456.59 823.62 3248.80 0.00 0.00 0.00 0.00 0.00 131.40
June 38743.01 25-JUN-08:21 521.82 941.28 3712.91 0.00 0.00 0.00 0.00 0.00 385.63
July 36759.21 02-JUL-07:51 521.82 941.28 3712.91 0.00 0.00 0.00 0.00 0.00 234.33
August 28460.75 27-AUG-09:21 456.59 823.62 3248.80 0.00 0.00 0.00 0.00 0.00 130.18
September 18182.84 03-SEP-09:52 391.37 705.96 2784.68 0.00 0.00 0.00 0.00 0.00 782.05
October 6171.41 01-OCT-13:51 652.28 1176.61 4641.14 0.00 0.00 0.00 0.00 0.00 261.16
November 4562.45 03-NOV-10:36 12393.25 21178.91 13923.42 0.00 0.00 0.00 0.00 0.00 94.57
December 3690.30 02-DEC-17:01 456.59 823.62 3248.80 0.00 0.00 0.00 0.00 0.00 186.50
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3614.55   391.37 705.96 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38743.01   12958.30 21178.91 13923.42 0.00 0.00 0.00 0.00 20.46 782.05



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 13051.41 12-JAN-12:40 1058.33 3286.49 1920.52 0.00 0.00 0.00 0.00 0.00 526.52
February 20843.89 24-FEB-13:43 13462.06 23005.41 15124.09 0.00 0.00 0.00 0.00 0.00 477.66
March 18596.32 24-MAR-13:32 20108.34 32864.88 21605.85 0.00 0.00 0.00 0.00 0.00 681.11
April 29309.51 16-APR-13:42 506.09 912.91 3600.97 0.00 0.00 0.00 0.00 109.64 0.00
May 19599.75 30-MAY-13:30 2010.83 3286.49 2160.58 0.00 0.00 0.00 0.00 50.62 0.00
June 52955.55 25-JUN-14:21 809.75 1460.66 5761.56 0.00 0.00 0.00 0.00 859.99 0.00
July 48975.01 02-JUL-14:31 809.75 1460.66 5761.56 0.00 0.00 0.00 0.00 267.17 0.00
August 42996.93 13-AUG-13:11 708.53 1278.08 5041.36 0.00 0.00 0.00 0.00 0.00 270.25
September 57722.24 17-SEP-13:31 809.75 1460.66 5761.56 0.00 0.00 0.00 0.00 0.00 375.67
October 52768.46 01-OCT-13:51 1012.19 1825.83 7201.95 0.00 0.00 0.00 0.00 0.00 1304.25
November 22461.04 03-NOV-13:22 20108.34 32864.88 21605.85 0.00 0.00 0.00 0.00 0.00 297.17
December 15757.47 01-DEC-13:23 7692.61 13145.95 8642.34 0.00 0.00 0.00 0.00 0.00 736.45
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 13051.41   506.09 912.91 1920.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 57722.24   20108.34 32864.88 21605.85 0.00 0.00 0.00 0.00 859.99 1304.25



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4882.98 12-JAN-15:50 1239.33 2117.89 1392.33 0.00 0.00 0.00 0.00 0.00 506.21
February 7717.33 24-FEB-16:24 9914.60 16943.13 11138.66 0.00 0.00 0.00 0.00 0.00 294.87
March 7863.95 23-MAR-15:51 12393.25 21178.91 13923.33 0.00 0.00 0.00 0.00 0.00 291.34
April 36874.77 16-APR-16:21 456.59 823.62 3248.78 0.00 0.00 0.00 0.00 177.45 0.00
May 32141.97 14-MAY-16:32 391.37 705.96 2784.67 0.00 0.00 0.00 0.00 0.00 182.67
June 44624.61 25-JUN-17:01 0.00 1176.61 3603.49 0.00 0.00 0.00 0.00 116.03 0.00
July 43671.98 02-JUL-17:11 0.00 1176.61 3603.49 0.00 0.00 0.00 0.00 0.00 128.66
August 37653.38 13-AUG-16:31 652.28 1176.61 4641.11 0.00 0.00 0.00 0.00 0.00 233.06
September 38167.72 04-SEP-17:21 0.00 941.28 2882.79 0.00 0.00 0.00 0.00 0.00 191.88
October 12221.42 20-OCT-15:30 1239.33 2117.89 1392.33 0.00 0.00 0.00 0.00 0.00 44.01
November 7874.93 03-NOV-15:22 12393.25 21178.91 13923.33 0.00 0.00 0.00 0.00 0.00 183.50
December 4842.76 01-DEC-15:40 4957.30 8471.56 5569.33 0.00 0.00 0.00 0.00 0.00 293.98
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4842.76   0.00 705.96 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 44624.61   12393.25 21178.91 13923.33 0.00 0.00 0.00 0.00 177.45 506.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19776.40 06-JAN-04:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2810.51
February 17785.30 04-FEB-04:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1804.69
March 12217.35 06-MAR-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3849.84
April 11471.02 03-APR-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3073.22
May 9225.22 06-MAY-05:06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 276.35
June 9728.24 26-JUN-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 114.86 0.00
July 10129.68 31-JUL-05:04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 123.12
August 10579.10 14-AUG-05:12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 82.17
September 10721.95 09-SEP-05:12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 139.86
October 11254.10 23-OCT-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 373.36
November 17211.05 26-NOV-02:41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4211.01
December 19070.09 09-DEC-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7549.40
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 9225.22   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19776.40   0.00 0.00 0.00 0.00 0.00 0.00 0.00 114.86 7549.40



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 20726.82 06-JAN-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4892.36
February 23207.85 18-FEB-04:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2815.47
March 22385.37 21-MAR-03:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8641.24
April 18800.28 22-APR-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2748.26
May 15396.50 02-MAY-04:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3887.66
June 10159.42 22-JUN-05:06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 305.16
July 10473.61 06-JUL-05:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 84.85
August 10640.02 30-AUG-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 169.86
September 18396.41 30-SEP-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2850.27
October 17940.54 27-OCT-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2809.23
November 20907.71 10-NOV-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7836.61
December 26715.49 09-DEC-02:12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17420.17
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 10159.42   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 84.85
Maximum of Months 26715.49   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17420.17



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 677.57 13-JAN-13:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1043.45
February 6389.05 24-FEB-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 694.48
March 14243.29 19-MAR-13:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1601.09
April 27152.02 18-APR-13:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 140.74 0.00
May 31668.28 31-MAY-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 119.21 0.00
June 35257.58 30-JUN-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 68.78 0.00
July 34028.23 05-JUL-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.59 0.00
August 34891.45 04-AUG-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 205.06 0.00
September 33068.34 07-SEP-13:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 59.70 0.00
October 15603.56 20-OCT-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 136.14
November 9167.18 03-NOV-13:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 478.04
December 134.55 03-DEC-14:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4140.43
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 134.55   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 35257.58   0.00 0.00 0.00 0.00 0.00 0.00 0.00 205.06 4140.43



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6798.01 30-JAN-13:01 2221.41 7287.84 19486.06 0.00 0.00 0.00 0.00 0.00 0.00
February 10396.54 04-FEB-10:31 733.48 2429.28 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
March 6618.61 31-MAR-23:47 0.00 121.46 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
April 8329.20 16-APR-17:57 0.00 121.46 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
May 3461.20 31-MAY-23:51 0.00 404.88 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
June 5369.73 30-JUN-23:51 0.00 404.88 58458.17 0.00 0.00 0.00 0.00 0.00 0.00
July 7255.02 31-JUL-24:00 0.00 40.49 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
August 8484.50 29-AUG-17:40 23.38 242.93 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 2843.58 30-SEP-23:51 0.00 404.88 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
October 4730.37 31-OCT-23:52 0.00 404.88 58458.17 0.00 0.00 0.00 0.00 0.00 0.00
November 9904.18 26-NOV-08:11 116.92 404.88 58458.17 0.00 0.00 0.00 0.00 0.00 0.00
December 7867.82 01-DEC-16:03 888.56 2915.14 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2843.58   0.00 40.49 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10396.54   2221.41 7287.84 58458.17 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1800.11 12-JAN-16:40 222.14 728.78 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 9982.48 04-FEB-10:31 733.48 2429.28 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
March 5963.77 31-MAR-23:12 0.00 364.39 70149.80 0.00 0.00 0.00 0.00 0.00 0.00
April 7852.62 15-APR-18:10 0.00 40.49 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3267.67 31-MAY-23:40 0.00 40.49 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5200.13 30-JUN-23:51 0.00 404.88 58458.17 0.00 0.00 0.00 0.00 0.00 0.00
July 6778.70 31-JUL-24:00 0.00 40.49 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
August 8127.41 29-AUG-17:40 23.38 242.93 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 2554.22 01-SEP-17:50 23.38 242.93 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
October 4228.77 11-OCT-16:52 701.50 4048.80 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
November 9354.19 26-NOV-08:11 116.92 404.88 58458.17 0.00 0.00 0.00 0.00 0.00 0.00
December 7292.86 01-DEC-16:03 888.56 2915.14 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1800.11   0.00 40.49 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9982.48   888.56 4048.80 70149.80 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1586.17 12-JAN-16:40 222.14 728.78 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 8266.63 04-FEB-10:31 733.48 2429.28 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
March 5724.66 21-MAR-17:32 233.83 2429.28 58458.17 0.00 0.00 0.00 0.00 0.00 0.00
April 8020.34 16-APR-17:57 0.00 121.46 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
May 3147.02 31-MAY-23:20 0.00 40.49 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5093.88 30-JUN-23:30 0.00 40.49 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 6512.29 31-JUL-23:50 0.00 40.49 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
August 8229.25 29-AUG-17:40 23.38 242.93 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 2652.94 01-SEP-17:40 23.38 242.93 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
October 4220.85 11-OCT-16:41 701.50 4048.80 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
November 9246.42 26-NOV-08:11 116.92 404.88 58458.17 0.00 0.00 0.00 0.00 0.00 0.00
December 7031.56 01-DEC-16:03 888.56 2915.14 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1586.17   0.00 40.49 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9246.42   888.56 4048.80 58458.17 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 95031.73 18-JAN-13:01 48086.79 82175.84 949081.30 0.00 0.00 0.00 0.00 0.00 0.00
February 484674.86 01-FEB-00:12 0.00 4565.32 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00
March 521666.13 24-MAR-15:52 48086.79 82175.84 2847243.91 0.00 0.00 0.00 0.00 0.00 0.00
April 490466.75 19-APR-09:42 50279.21 82175.84 3796325.22 0.00 0.00 0.00 0.00 0.00 0.00
May 466173.84 31-MAY-23:56 0.00 4565.32 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00
June 487183.82 03-JUN-02:22 0.00 4565.32 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00
July 488467.29 24-JUL-02:52 0.00 4565.32 2847243.91 0.00 0.00 0.00 0.00 0.00 0.00
August 496623.96 06-AUG-19:34 0.00 4565.32 3796325.22 0.00 0.00 0.00 0.00 0.00 0.00
September 481570.91 30-SEP-23:12 0.00 4565.32 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00
October 510496.12 31-OCT-23:53 0.00 4565.32 2847243.91 0.00 0.00 0.00 0.00 0.00 0.00
November 517651.82 01-NOV-02:42 0.00 4565.32 2847243.91 0.00 0.00 0.00 0.00 0.00 0.00
December 486450.79 13-DEC-13:04 48086.79 82175.84 3796325.22 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 95031.73   0.00 4565.32 949081.30 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 521666.13   50279.21 82175.84 3796325.22 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.194125E+13 1411334.87 13-JAN-16:49 0.211102E+13 3142160.44 30-JAN-07:30
February 0.213091E+13 1546355.86 10-FEB-16:10 0.132262E+13 2952795.65 02-FEB-07:30
March 0.286958E+13 1884423.17 24-MAR-14:09 0.729913E+12 2224171.88 06-MAR-05:10
April 0.310537E+13 2342252.82 18-APR-15:09 0.303491E+12 1530995.70 03-APR-05:10
May 0.201438E+13 1920782.27 31-MAY-15:09 0.522952E+11 946584.36 02-MAY-04:19
June 0.255638E+13 2103830.87 30-JUN-15:20 0.176633E+11 605771.10 02-JUN-05:10
July 0.304160E+13 2283152.47 26-JUL-15:09 0.223742E+10 114833.67 24-JUL-05:10
August 0.353133E+13 2520439.57 04-AUG-15:30 0.682291E+10 271304.58 07-AUG-05:10
September 0.199616E+13 1955108.29 06-SEP-15:09 0.847214E+11 990306.41 30-SEP-04:10
October 0.233109E+13 1791039.00 20-OCT-15:09 0.247987E+12 1292711.53 16-OCT-04:19
November 0.273841E+13 1870211.36 03-NOV-14:09 0.806248E+12 2301408.96 27-NOV-05:10
December 0.326027E+13 1944767.24 21-DEC-16:00 0.148851E+13 2628534.69 11-DEC-07:19
             
Annual Sum or Average 0.315167E+14     0.717353E+13    
Minimum of Months 0.194125E+13 1411334.87   0.223742E+10 114833.67  
Maximum of Months 0.353133E+13 2520439.57   0.211102E+13 3142160.44  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.468149E+12 0.106275E+12 0.766053E+12 0.218140E+12 0.217220E+12 0.188885E+11 0.00 0.605601E+10 0.00 0.956652E+11 0.00 0.448078E+11 0.00
February 0.424646E+12 0.885496E+11 0.978954E+12 0.199667E+12 0.204177E+12 0.368794E+11 0.00 0.553881E+11 536429.58 0.101147E+12 0.00 0.415063E+11 0.00
March 0.504598E+12 0.877422E+11 0.141687E+13 0.230864E+12 0.230426E+12 0.967965E+11 0.00 0.984368E+11 43747488.51 0.155483E+12 0.00 0.483130E+11 0.00
April 0.450709E+12 0.743617E+11 0.165903E+13 0.216144E+12 0.255042E+12 0.103474E+12 0.00 0.143128E+12 0.548371E+10 0.155814E+12 0.00 0.421876E+11 0.00
May 0.486374E+12 0.676330E+11 0.774844E+12 0.224502E+12 0.215789E+12 0.532724E+11 0.00 0.111152E+12 0.828423E+10 0.300785E+11 0.00 0.424529E+11 0.00
June 0.484022E+12 0.608274E+11 0.106252E+13 0.222585E+12 0.256422E+12 0.964670E+11 0.00 0.295994E+12 0.370735E+11 0.115680E+10 0.00 0.393094E+11 0.00
July 0.453060E+12 0.648262E+11 0.139340E+13 0.218061E+12 0.286446E+12 0.134590E+12 0.00 0.399126E+12 0.563215E+11 0.406189E+09 0.00 0.353631E+11 0.00
August 0.504598E+12 0.727852E+11 0.173200E+13 0.230864E+12 0.318629E+12 0.144022E+12 0.00 0.431333E+12 0.555318E+11 0.387331E+10 0.00 0.376926E+11 0.00
September 0.450709E+12 0.802060E+11 0.740713E+12 0.216143E+12 0.222737E+12 0.579105E+11 0.00 0.146147E+12 0.135503E+11 0.333688E+11 0.00 0.346697E+11 0.00
October 0.468149E+12 0.937788E+11 0.108340E+13 0.218140E+12 0.213680E+12 0.430041E+11 0.00 0.849705E+11 0.429446E+09 0.880261E+11 0.00 0.375117E+11 0.00
November 0.462662E+12 0.100161E+12 0.135889E+13 0.209941E+12 0.225367E+12 0.111315E+12 0.00 0.878474E+11 30181880.84 0.142918E+12 0.00 0.392732E+11 0.00
December 0.453060E+12 0.108851E+12 0.170972E+13 0.218060E+12 0.266226E+12 0.111692E+12 0.00 0.105851E+12 71270.49 0.245132E+12 0.00 0.416784E+11 0.00
                           
Annual Sum or Average 0.561074E+13 0.100600E+13 0.146764E+14 0.262311E+13 0.291216E+13 0.100831E+13 0.00 0.196543E+13 0.176749E+12 0.105307E+13 0.00 0.484766E+12 0.00
Minimum of Months 0.424646E+12 0.608274E+11 0.740713E+12 0.199667E+12 0.204177E+12 0.188885E+11 0.00 0.605601E+10 0.00 0.406189E+09 0.00 0.346697E+11 0.00
Maximum of Months 0.504598E+12 0.108851E+12 0.173200E+13 0.230864E+12 0.318629E+12 0.144022E+12 0.00 0.431333E+12 0.563215E+11 0.245132E+12 0.00 0.483130E+11 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.211102E+13 0.00 0.00 0.00 0.00
February 0.00 0.00 0.132262E+13 0.00 0.00 0.00 0.00
March 0.00 0.00 0.729913E+12 0.00 0.00 0.00 0.00
April 0.00 0.00 0.303491E+12 0.00 0.00 0.00 0.00
May 0.00 0.00 0.522952E+11 0.00 0.00 0.00 0.00
June 0.00 0.00 0.176633E+11 0.00 0.00 0.00 0.00
July 0.00 0.00 0.223742E+10 0.00 0.00 0.00 0.00
August 0.00 0.00 0.682291E+10 0.00 0.00 0.00 0.00
September 0.00 0.00 0.847214E+11 0.00 0.00 0.00 0.00
October 0.00 0.00 0.247987E+12 0.00 0.00 0.00 0.00
November 0.00 0.00 0.806248E+12 0.00 0.00 0.00 0.00
December 0.00 0.00 0.148851E+13 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.717353E+13 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.223742E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.211102E+13 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 489900.85 02-JAN-08:09 64082.80 01-JAN-00:10 423497.50 02-JAN-08:09 235096.12 02-JAN-08:20 149711.72 30-JAN-05:10 47998.42 09-JAN-05:49 0.00 01-JAN-00:10
February 489900.85 01-FEB-08:09 64082.80 01-FEB-00:10 541788.89 01-FEB-08:09 235096.12 01-FEB-08:20 151203.03 06-FEB-06:10 47113.70 08-FEB-13:30 0.00 01-FEB-00:10
March 489900.85 01-MAR-08:09 64082.80 01-MAR-00:10 660080.29 01-MAR-08:09 235096.12 01-MAR-08:20 184912.85 24-MAR-14:09 48978.55 28-MAR-14:39 0.00 01-MAR-00:10
April 489900.85 03-APR-07:10 64082.80 01-APR-00:10 778371.69 03-APR-07:10 235096.12 03-APR-07:19 259233.09 18-APR-14:00 99137.04 18-APR-14:00 0.00 01-APR-00:10
May 489900.85 01-MAY-07:10 64082.80 01-MAY-00:10 423497.50 01-MAY-07:10 235096.12 01-MAY-07:19 239428.74 31-MAY-14:00 97982.74 31-MAY-14:30 0.00 01-MAY-00:10
June 489900.85 01-JUN-07:10 64082.80 01-JUN-00:10 541788.89 01-JUN-07:10 235096.12 01-JUN-07:19 267693.67 30-JUN-15:20 99028.39 27-JUN-14:09 0.00 01-JUN-00:10
July 489900.85 03-JUL-07:10 64082.80 01-JUL-00:10 660080.29 03-JUL-07:10 235096.12 03-JUL-07:19 257378.41 05-JUL-15:39 100616.03 26-JUL-14:00 0.00 01-JUL-00:10
August 489900.85 01-AUG-07:10 64082.80 01-AUG-00:10 778371.69 01-AUG-07:10 235096.12 01-AUG-07:19 305773.99 04-AUG-15:30 102278.78 04-AUG-15:30 0.00 01-AUG-00:10
September 489900.85 01-SEP-07:10 64082.80 01-SEP-00:10 423497.50 01-SEP-07:10 235096.12 01-SEP-07:19 275387.60 07-SEP-15:20 99617.76 01-SEP-14:30 0.00 01-SEP-00:10
October 489900.85 02-OCT-07:10 64082.80 01-OCT-00:10 541788.89 02-OCT-07:10 235096.12 02-OCT-07:19 205058.12 20-OCT-14:00 52607.83 20-OCT-12:00 0.00 01-OCT-00:10
November 489900.85 01-NOV-07:10 64082.80 01-NOV-00:10 660080.29 01-NOV-07:10 235096.12 01-NOV-07:19 202982.74 03-NOV-14:30 50910.09 03-NOV-13:00 0.00 01-NOV-00:10
December 489900.85 01-DEC-08:09 64082.80 01-DEC-00:10 778371.69 01-DEC-08:09 235096.12 01-DEC-08:20 160760.10 11-DEC-05:10 51119.68 11-DEC-05:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 489900.85   64082.80   423497.50   235096.12   149711.72   47113.70   0.00  
Maximum of Months 489900.85   64082.80   778371.69   235096.12   305773.99   102278.78   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 10816.03 13-JAN-22:10 0.00 01-JAN-00:10 42402.75 14-JAN-14:09 0.00 60019.34 30-JAN-12:00 0.00
February 79137.94 08-FEB-17:10 17.44 15-FEB-05:00 56954.31 09-FEB-14:50 0.00 60480.04 21-FEB-12:30 0.00
March 151350.54 23-MAR-14:09 3061.30 19-MAR-15:30 100000.00 25-MAR-15:20 0.00 60429.63 02-MAR-12:00 0.00
April 383202.79 18-APR-14:00 58522.13 15-APR-11:00 100000.00 01-APR-09:09 0.00 58465.80 03-APR-11:20 0.00
May 356725.98 30-MAY-14:09 58522.13 12-MAY-14:20 100000.00 05-MAY-19:30 0.00 55773.48 01-MAY-11:00 0.00
June 382974.25 27-JUN-14:09 58522.13 11-JUN-15:09 32804.46 03-JUN-03:30 0.00 52183.01 01-JUN-11:30 0.00
July 455018.98 26-JUL-14:00 58522.13 03-JUL-07:49 82160.22 03-JUL-07:40 0.00 48427.27 03-JUL-11:20 0.00
August 515044.72 04-AUG-15:30 58522.13 03-AUG-04:30 100000.00 07-AUG-09:00 0.00 46612.12 01-AUG-11:30 0.00
September 371578.73 06-SEP-12:09 58522.13 05-SEP-14:39 100000.00 23-SEP-12:50 0.00 47561.67 29-SEP-11:30 0.00
October 233724.24 20-OCT-12:00 11838.55 20-OCT-14:00 68963.25 31-OCT-14:00 0.00 51313.56 31-OCT-11:50 0.00
November 192434.87 03-NOV-13:39 4606.37 03-NOV-13:50 99943.34 14-NOV-17:49 0.00 54641.99 30-NOV-12:39 0.00
December 91267.33 03-DEC-00:40 20.45 05-DEC-16:10 100000.00 01-DEC-11:39 0.00 57639.36 27-DEC-12:50 0.00
                     
Annual Sum or Average             0.00     0.00
Minimum of Months 10816.03   0.00   32804.46   0.00 46612.12   0.00
Maximum of Months 515044.72   58522.13   100000.00   0.00 60480.04   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1411334.87 13-JAN-16:49 489900.85 423497.50 64082.80 235096.12 110674.14 106.64 0.00 7948.42 0.00
February 1546355.86 10-FEB-16:10 489900.85 541788.89 0.00 235096.12 118808.33 46835.47 0.00 20949.18 0.00
March 1884423.17 24-MAR-14:09 489900.85 660080.29 0.00 235096.12 184912.85 48776.05 0.00 150096.84 516.91
April 2342252.82 18-APR-15:09 489900.85 778371.69 0.00 235096.12 258401.37 99068.02 0.00 380332.29 58522.13
May 1920782.27 31-MAY-15:09 489900.85 423497.50 0.00 235096.12 239133.43 97458.79 0.00 338335.13 58522.13
June 2103830.87 30-JUN-15:20 489900.85 541788.89 0.00 235096.12 267693.67 98888.61 0.00 373921.64 58522.13
July 2283152.47 26-JUL-15:09 489900.85 660080.29 0.00 235096.12 249844.10 100582.76 0.00 454076.26 58522.13
August 2520439.57 04-AUG-15:30 489900.85 778371.69 0.00 235096.12 305773.99 102278.78 0.00 515044.72 58522.13
September 1955108.29 06-SEP-15:09 489900.85 423497.50 0.00 235096.12 268448.13 98298.56 0.00 346507.89 58522.13
October 1791039.00 20-OCT-15:09 489900.85 541788.89 0.00 235096.12 203941.78 52364.37 0.00 219842.27 11519.85
November 1870211.36 03-NOV-14:09 489900.85 660080.29 0.00 235096.12 198127.03 50735.52 0.00 171634.49 3870.10
December 1944767.24 21-DEC-16:00 489900.85 778371.69 64082.80 235096.12 120765.18 48357.98 0.00 67806.15 0.00
                       
Annual Sum or Average                      
Minimum of Months 1411334.87   489900.85 423497.50 0.00 235096.12 110674.14 106.64 0.00 7948.42 0.00
Maximum of Months 2520439.57   489900.85 778371.69 64082.80 235096.12 305773.99 102278.78 0.00 515044.72 58522.13



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 3142160.44 30-JAN-07:30 0.00 0.00 0.00
February 0.00 0.00 2952795.65 02-FEB-07:30 0.00 0.00 0.00
March 0.00 0.00 2224171.88 06-MAR-05:10 0.00 0.00 0.00
April 0.00 0.00 1530995.70 03-APR-05:10 0.00 0.00 0.00
May 0.00 0.00 946584.36 02-MAY-04:19 0.00 0.00 0.00
June 0.00 0.00 605771.10 02-JUN-05:10 0.00 0.00 0.00
July 0.00 0.00 114833.67 24-JUL-05:10 0.00 0.00 0.00
August 0.00 0.00 271304.58 07-AUG-05:10 0.00 0.00 0.00
September 0.00 0.00 990306.41 30-SEP-04:10 0.00 0.00 0.00
October 0.00 0.00 1292711.53 16-OCT-04:19 0.00 0.00 0.00
November 0.00 0.00 2301408.96 27-NOV-05:10 0.00 0.00 0.00
December 0.00 0.00 2628534.69 11-DEC-07:19 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 114833.67   0.00 0.00 0.00
Maximum of Months 0.00 0.00 3142160.44   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 20.39 0.33 20.39 0.00 20.39 0.00 20.39
February 0.50 20.42 0.50 20.42 0.00 20.42 0.00 20.42
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.50 25.58 0.00 25.58
July 0.00 0.00 0.00 0.00 1.00 25.74 0.00 25.74
August 0.00 0.00 0.00 0.00 2.17 25.82 0.00 25.82
September 0.00 0.00 0.00 0.00 2.50 26.47 0.00 26.47
October 0.00 0.00 0.00 0.00 1.00 25.63 0.00 25.63
November 0.00 0.00 0.00 0.00 0.67 25.69 0.00 25.69
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.83 20.40 0.83 20.40 7.83 24.99 0.00 24.99
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.50 20.42 0.50 20.42 2.50 26.47 0.00 26.47



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.50 19.28 0.33 19.44 0.00 19.44 0.00 19.44
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.14 0.00 19.14 0.00 19.14 0.00 19.14
                 
Annual Sum or Average 1.67 19.26 0.33 19.42 0.00 19.42 0.00 19.42
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.50 19.28 0.33 19.44 0.00 19.44 0.00 19.44



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 8.33 18.10 0.50 18.21 0.00 18.21 0.00 18.21
February 5.67 18.36 0.33 18.47 0.00 18.47 0.00 18.47
March 2.17 18.38 0.17 18.50 0.00 18.50 0.00 18.50
April 0.67 18.00 0.00 18.00 0.00 18.00 0.00 18.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.83 19.26 0.00 19.26 0.00 19.26 0.00 19.26
November 3.00 18.29 0.17 18.38 0.00 18.38 0.00 18.38
December 5.67 18.36 0.33 18.46 0.00 18.46 0.00 18.46
                 
Annual Sum or Average 26.33 18.29 1.50 18.39 0.00 18.39 0.00 18.39
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8.33 19.26 0.50 19.26 0.00 19.26 0.00 19.26



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 19.67 16.60 3.67 16.45 0.00 16.45 0.00 16.45
February 13.83 16.46 1.17 16.50 0.00 16.50 0.00 16.50
March 2.33 18.71 0.00 18.71 0.00 18.71 0.00 18.71
April 0.33 18.93 0.00 18.93 0.00 18.93 0.00 18.93
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 2.83 17.63 0.00 17.63 0.00 17.63 0.00 17.63
December 10.00 16.75 1.00 16.73 0.00 16.73 0.00 16.73
                 
Annual Sum or Average 49.00 16.76 5.83 16.69 0.00 16.69 0.00 16.69
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19.67 18.93 3.67 18.93 0.00 18.93 0.00 18.93



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 17.83 16.51 1.50 16.46 0.00 16.46 0.00 16.46
February 14.50 16.24 1.00 16.32 0.00 16.32 0.00 16.32
March 2.83 18.71 0.00 18.71 0.00 18.71 0.00 18.71
April 0.33 18.80 0.00 18.80 0.50 24.14 0.50 25.47
May 0.00 0.00 0.00 0.00 2.50 27.86 2.50 27.86
June 0.00 0.00 0.00 0.00 2.67 28.60 2.67 28.60
July 0.00 0.00 0.00 0.00 4.33 28.49 4.33 28.49
August 0.00 0.00 0.00 0.00 1.83 28.21 1.83 28.21
September 0.00 0.00 0.00 0.00 2.17 28.18 2.17 28.18
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 4.00 16.91 0.33 16.76 0.00 16.76 0.00 16.76
December 11.33 16.75 0.83 16.76 0.00 16.76 0.00 16.76
                 
Annual Sum or Average 50.83 16.66 3.67 16.64 14.00 19.02 14.00 20.60
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17.83 18.80 1.50 18.80 4.33 28.60 4.33 28.60



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 19.50 16.67 1.33 16.67 0.00 16.67 0.00 16.67
February 13.50 16.49 1.00 16.55 0.00 16.55 0.00 16.55
March 3.33 18.60 0.00 18.60 0.00 18.60 0.00 18.60
April 0.50 18.07 0.00 18.07 1.50 25.67 1.50 26.75
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 2.50 27.80 2.50 27.80
July 0.00 0.00 0.00 0.00 3.00 27.97 3.00 27.97
August 0.00 0.00 0.00 0.00 3.00 27.72 3.00 27.72
September 0.00 0.00 0.00 0.00 3.83 28.30 3.83 28.30
October 0.00 0.00 0.00 0.00 2.00 28.07 2.00 28.07
November 6.33 16.57 0.50 16.44 0.17 16.71 0.17 16.96
December 12.17 16.82 1.00 16.86 0.17 16.99 0.17 17.12
                 
Annual Sum or Average 55.33 16.78 3.83 16.78 16.17 19.19 16.17 20.74
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19.50 18.60 1.33 18.60 3.83 28.30 3.83 28.30



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 9.50 17.65 0.17 17.69 0.00 17.69 0.00 17.69
February 4.17 17.96 0.00 17.96 0.00 17.96 0.00 17.96
March 0.50 19.22 0.00 19.22 0.00 19.22 0.00 19.22
April 0.00 0.00 0.00 0.00 4.17 28.67 2.50 28.77
May 0.00 0.00 0.00 0.00 3.17 28.35 1.83 28.40
June 0.00 0.00 0.00 0.00 5.83 28.72 3.67 28.71
July 0.00 0.00 0.00 0.00 12.00 28.63 5.67 28.70
August 0.00 0.00 0.00 0.00 8.50 28.10 4.33 28.19
September 0.00 0.00 0.00 0.00 3.83 28.02 3.17 28.01
October 0.00 0.00 0.00 0.00 0.33 27.47 0.33 27.47
November 1.50 18.77 0.00 18.77 0.00 18.77 0.00 18.77
December 1.67 18.30 0.00 18.30 0.00 18.30 0.00 18.30
                 
Annual Sum or Average 17.33 17.93 0.17 17.95 37.83 25.12 21.50 26.08
Minimum of Months 0.00 0.00 0.00 0.00 0.00 17.69 0.00 17.69
Maximum of Months 9.50 19.22 0.17 19.22 12.00 28.72 5.67 28.77



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 74.83 14.91 19.83 14.85 0.00 14.85 0.00 14.85
February 40.00 15.39 8.67 15.36 0.00 15.36 0.00 15.36
March 19.83 16.20 3.50 16.05 0.00 16.05 0.00 16.05
April 4.50 17.10 0.00 17.10 0.00 17.10 0.00 17.10
May 0.17 19.12 0.00 19.12 0.00 19.12 0.00 19.12
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.33 19.24 0.00 19.24 0.00 19.24 0.00 19.24
October 2.50 19.10 0.00 19.10 0.00 19.10 0.00 19.10
November 25.00 15.48 4.50 15.42 0.00 15.42 0.00 15.42
December 46.50 15.15 11.50 15.05 0.00 15.05 0.00 15.05
                 
Annual Sum or Average 213.67 15.35 48.00 15.25 0.00 15.25 0.00 15.25
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 74.83 19.24 19.83 19.24 0.00 19.24 0.00 19.24



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 125.67 16.43 18.17 16.23 0.00 16.23 0.00 16.23
February 59.67 16.63 6.17 16.52 0.00 16.52 0.00 16.52
March 24.33 17.13 1.33 17.07 0.00 17.07 0.00 17.07
April 7.67 18.05 0.00 18.05 0.17 18.24 0.17 18.43
May 0.17 19.15 0.00 19.15 2.33 27.30 2.33 27.58
June 0.00 0.00 0.00 0.00 3.17 28.64 3.17 28.64
July 0.00 0.00 0.00 0.00 4.17 28.67 4.17 28.67
August 0.00 0.00 0.00 0.00 1.50 28.18 1.50 28.18
September 0.33 19.26 0.00 19.26 2.00 26.62 2.00 27.19
October 2.33 19.08 0.00 19.08 0.00 19.08 0.00 19.08
November 37.00 16.79 4.50 16.63 0.00 16.63 0.00 16.63
December 86.33 16.82 11.00 16.62 0.00 16.62 0.00 16.62
                 
Annual Sum or Average 343.50 16.71 41.17 16.54 13.33 16.93 13.33 17.30
Minimum of Months 0.00 0.00 0.00 0.00 0.00 16.23 0.00 16.23
Maximum of Months 125.67 19.26 18.17 19.26 4.17 28.67 4.17 28.67



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 59.83 15.13 10.17 15.13 0.00 15.13 0.00 15.13
February 30.50 15.72 3.67 15.76 0.00 15.76 0.00 15.76
March 14.33 16.79 0.83 16.79 0.00 16.79 0.00 16.79
April 3.67 17.00 0.00 17.00 1.33 19.95 1.33 21.66
May 0.17 19.21 0.00 19.21 0.00 19.21 0.00 19.21
June 0.00 0.00 0.00 0.00 1.83 27.72 1.83 27.72
July 0.00 0.00 0.00 0.00 2.17 27.94 2.17 27.94
August 0.00 0.00 0.00 0.00 1.17 27.72 1.17 27.72
September 0.33 19.29 0.00 19.29 3.33 27.62 3.33 28.02
October 1.67 19.10 0.00 19.10 1.83 23.85 1.83 25.34
November 20.00 15.70 3.50 15.62 0.17 15.70 0.17 15.79
December 36.50 15.43 7.17 15.36 0.00 15.36 0.00 15.36
                 
Annual Sum or Average 167.00 15.61 25.33 15.57 11.83 16.29 11.83 16.94
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.13 0.00 15.13
Maximum of Months 59.83 19.29 10.17 19.29 3.33 27.94 3.33 28.02



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 62.33 15.02 14.33 15.00 0.00 15.00 0.00 15.00
February 30.67 15.61 5.17 15.57 0.00 15.57 0.00 15.57
March 15.00 16.70 1.83 16.59 0.00 16.59 0.00 16.59
April 3.33 17.10 0.00 17.10 2.17 21.58 1.33 22.95
May 0.17 19.18 0.00 19.18 2.83 27.82 1.50 28.00
June 0.00 0.00 0.00 0.00 4.50 28.96 2.50 28.96
July 0.00 0.00 0.00 0.00 7.83 28.70 3.50 28.75
August 0.00 0.00 0.00 0.00 2.17 28.35 1.17 28.39
September 0.33 19.24 0.00 19.24 2.33 26.87 1.83 27.28
October 1.83 19.12 0.00 19.12 0.00 19.12 0.00 19.12
November 18.83 15.52 3.67 15.46 0.00 15.46 0.00 15.46
December 35.50 15.42 7.17 15.31 0.00 15.31 0.00 15.31
                 
Annual Sum or Average 168.00 15.52 32.17 15.43 21.83 16.73 11.83 17.33
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.00 0.00 15.00
Maximum of Months 62.33 19.24 14.33 19.24 7.83 28.96 3.50 28.96



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 90.83 14.27 26.67 14.24 0.00 14.24 0.00 14.24
February 66.67 14.60 17.17 14.55 0.00 14.55 0.00 14.55
March 32.50 15.24 4.33 15.11 0.00 15.11 0.00 15.11
April 16.50 15.82 4.17 15.58 0.00 15.58 0.00 15.58
May 1.33 18.96 0.00 18.96 0.00 18.96 0.00 18.96
June 0.50 19.29 0.00 19.29 0.00 19.29 0.00 19.29
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 2.00 18.32 0.00 18.32 0.00 18.32 0.00 18.32
October 11.67 16.76 0.67 16.66 0.00 16.66 0.00 16.66
November 52.50 14.76 15.33 14.69 0.00 14.69 0.00 14.69
December 79.67 14.51 21.00 14.47 0.00 14.47 0.00 14.47
                 
Annual Sum or Average 354.17 14.75 89.33 14.66 0.00 14.66 0.00 14.66
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 90.83 19.29 26.67 19.29 0.00 19.29 0.00 19.29



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 90.33 14.28 26.17 14.27 0.00 14.27 0.00 14.27
February 63.17 14.61 13.67 14.57 0.00 14.57 0.00 14.57
March 31.00 15.28 3.33 15.21 0.00 15.21 0.00 15.21
April 16.33 15.79 3.33 15.59 0.00 15.59 0.00 15.59
May 1.33 19.01 0.00 19.01 0.50 21.32 0.50 22.64
June 0.33 19.26 0.00 19.26 4.00 27.56 4.00 27.89
July 0.00 0.00 0.00 0.00 3.67 28.44 3.67 28.44
August 0.00 0.00 0.00 0.00 0.83 27.41 0.83 27.41
September 2.00 18.32 0.00 18.32 0.00 18.32 0.00 18.32
October 11.17 16.84 0.50 16.76 0.00 16.76 0.00 16.76
November 49.17 14.75 11.33 14.69 0.00 14.69 0.00 14.69
December 78.50 14.54 18.83 14.51 0.00 14.51 0.00 14.51
                 
Annual Sum or Average 343.33 14.76 77.17 14.69 9.00 14.97 9.00 15.24
Minimum of Months 0.00 0.00 0.00 0.00 0.00 14.27 0.00 14.27
Maximum of Months 90.33 19.26 26.17 19.26 4.00 28.44 4.00 28.44



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 82.00 14.44 19.67 14.45 0.00 14.45 0.00 14.45
February 57.00 14.77 11.50 14.73 0.00 14.73 0.00 14.73
March 26.50 15.50 1.67 15.46 0.00 15.46 0.00 15.46
April 15.33 15.86 3.83 15.62 1.00 16.24 1.00 16.80
May 1.17 19.02 0.00 19.02 0.00 19.02 0.00 19.02
June 0.33 19.23 0.00 19.23 1.83 26.39 1.83 26.99
July 0.00 0.00 0.00 0.00 1.67 27.87 1.67 27.87
August 0.00 0.00 0.00 0.00 0.83 27.53 0.83 27.53
September 2.00 18.41 0.00 18.41 2.50 23.91 2.50 25.48
October 10.00 17.09 0.50 16.98 0.33 17.30 0.33 17.60
November 44.00 14.88 9.17 14.82 0.00 14.82 0.00 14.82
December 66.00 14.66 11.17 14.64 0.00 14.64 0.00 14.64
                 
Annual Sum or Average 304.33 14.91 57.50 14.85 8.17 15.14 8.17 15.42
Minimum of Months 0.00 0.00 0.00 0.00 0.00 14.45 0.00 14.45
Maximum of Months 82.00 19.23 19.67 19.23 2.50 27.87 2.50 27.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 86.33 14.43 24.17 14.41 0.00 14.41 0.00 14.41
February 53.17 14.82 10.50 14.76 0.00 14.76 0.00 14.76
March 24.67 15.60 2.50 15.51 0.00 15.51 0.00 15.51
April 11.00 16.12 3.00 15.86 1.67 17.24 1.00 17.95
May 0.83 19.06 0.00 19.06 2.67 26.10 1.50 26.71
June 0.33 19.34 0.00 19.34 4.67 28.52 2.67 28.76
July 0.00 0.00 0.00 0.00 8.17 28.73 3.50 28.80
August 0.00 0.00 0.00 0.00 2.33 28.27 1.17 28.33
September 1.83 18.43 0.00 18.43 2.17 23.57 1.67 24.83
October 6.33 18.03 0.00 18.03 0.00 18.03 0.00 18.03
November 40.17 14.98 8.33 14.89 0.00 14.89 0.00 14.89
December 64.50 14.71 14.00 14.66 0.00 14.66 0.00 14.66
                 
Annual Sum or Average 289.17 14.93 62.50 14.84 21.67 15.64 11.50 16.03
Minimum of Months 0.00 0.00 0.00 0.00 0.00 14.41 0.00 14.41
Maximum of Months 86.33 19.34 24.17 19.34 8.17 28.73 3.50 28.80



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 48.83 28.85 29.83 28.85
February 0.00 0.00 0.00 0.00 81.83 33.32 58.50 33.38
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 5.50 35.69 2.33 35.83
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   136.17 31.81 90.67 31.89
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 81.83 35.69 58.50 35.83



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 10.33 28.03 7.67 28.08
February 0.00 0.00 0.00 0.00 81.83 32.25 58.50 32.37
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 5.50 33.13 2.33 33.26
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   97.67 31.86 68.50 31.95
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 81.83 33.13 58.50 33.26



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.83 28.30 1.83 28.30
February 0.00 0.00 0.00 0.00 81.83 30.26 58.50 30.51
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 5.33 30.45 2.17 30.55
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   89.00 30.23 62.50 30.46
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 81.83 30.45 58.50 30.55



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.50 27.67 0.50 27.67
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 2.33 28.07 2.33 28.07
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.83 28.00 2.83 28.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.33 28.07 2.33 28.07



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 488.67 22.08 5.83 22.06 5.83 22.04
February 437.83 22.66 25.17 22.56 25.17 22.47
March 434.00 23.24 6.17 23.27 0.00 23.27
April 293.67 23.61 56.00 23.78 0.00 23.78
May 118.67 23.55 219.33 24.20 0.67 24.20
June 2.17 23.79 391.50 24.45 0.33 24.45
July 5.17 24.00 493.17 24.54 5.17 24.53
August 2.83 25.76 502.17 24.47 2.83 24.48
September 81.83 23.55 261.33 24.58 0.00 24.58
October 118.83 23.81 126.17 24.76 0.00 24.76
November 221.17 23.43 97.83 23.98 0.00 23.98
December 450.17 23.19 5.17 23.21 0.67 23.20
             
Annual Sum or Average 2655.00 23.03 2189.83 23.74 40.67 23.72
Minimum of Months 2.17 22.08 5.17 22.06 0.00 22.04
Maximum of Months 488.67 25.76 502.17 24.76 25.17 24.76



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 494.33 22.85 34.33 22.77 34.33 22.70
February 424.83 23.16 15.00 23.09 15.00 23.02
March 355.67 23.60 16.17 23.67 0.00 23.67
April 204.17 23.73 92.17 23.93 0.00 23.93
May 54.83 23.65 278.00 24.16 0.00 24.16
June 6.67 23.48 454.00 24.24 0.00 24.24
July 0.00 0.00 492.83 24.28 0.00 24.28
August 0.00 0.00 507.00 24.29 0.00 24.29
September 46.00 23.67 278.83 24.33 0.00 24.33
October 139.50 23.71 73.00 24.09 0.00 24.09
November 236.00 23.57 62.33 23.74 0.00 23.74
December 463.50 23.56 4.83 23.53 4.83 23.51
             
Annual Sum or Average 2425.50 23.38 2308.50 23.81 54.17 23.78
Minimum of Months 0.00 0.00 4.83 22.77 0.00 22.70
Maximum of Months 494.33 23.73 507.00 24.33 34.33 24.33



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.46 199.17 21.08 199.17 20.87
February 452.67 22.10 95.83 21.80 95.83 21.59
March 460.00 22.90 22.00 22.78 22.00 22.68
April 325.33 23.15 41.50 23.26 2.00 23.25
May 133.17 23.37 211.83 23.85 0.00 23.85
June 21.17 23.23 379.17 24.11 0.00 24.11
July 13.83 23.33 453.33 24.15 0.00 24.15
August 5.33 23.29 443.50 24.17 0.00 24.17
September 112.50 23.35 182.83 23.93 0.00 23.93
October 352.00 23.32 9.50 23.34 0.00 23.34
November 408.33 22.50 72.33 22.32 56.67 22.13
December 497.00 21.95 108.17 21.65 108.17 21.43
             
Annual Sum or Average 3283.33 22.48 2219.17 22.83 483.83 22.62
Minimum of Months 5.33 21.46 9.50 21.08 0.00 20.87
Maximum of Months 502.00 23.37 453.33 24.17 199.17 24.17



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.23 415.17 20.11 415.17 20.06
February 454.00 20.57 287.00 20.32 287.00 20.22
March 511.50 21.41 176.67 21.15 176.67 21.00
April 423.67 21.80 111.17 21.62 83.33 21.40
May 307.00 22.56 135.17 22.98 4.33 22.96
June 128.83 22.53 290.67 23.62 0.00 23.62
July 91.33 22.74 367.33 23.81 0.83 23.81
August 118.67 22.69 333.67 23.71 0.00 23.71
September 317.83 22.45 116.33 22.82 8.50 22.79
October 491.83 21.63 106.00 21.34 106.00 21.14
November 484.83 20.87 226.00 20.51 226.00 20.33
December 497.00 20.38 384.17 20.23 384.17 20.17
             
Annual Sum or Average 4328.50 21.32 2949.33 21.49 1692.00 21.21
Minimum of Months 91.33 20.23 106.00 20.11 0.00 20.06
Maximum of Months 511.50 22.74 415.17 23.81 415.17 23.81



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.13 472.67 20.10 472.67 20.09
February 454.00 20.44 325.83 20.33 325.83 20.29
March 510.17 21.25 182.17 21.05 182.17 20.94
April 412.67 21.73 97.83 21.82 53.83 21.69
May 281.50 22.53 159.33 23.08 0.00 23.08
June 92.33 22.68 354.50 23.87 2.33 23.88
July 24.17 22.91 440.33 24.07 0.83 24.08
August 51.00 22.78 412.83 23.94 1.67 23.95
September 265.17 22.35 152.33 22.99 2.00 22.98
October 474.33 21.90 25.83 21.90 17.83 21.86
November 481.17 21.14 201.67 20.88 201.67 20.74
December 497.00 20.42 428.33 20.38 428.33 20.37
             
Annual Sum or Average 4045.50 21.25 3253.67 21.64 1689.17 21.38
Minimum of Months 24.17 20.13 25.83 20.10 0.00 20.09
Maximum of Months 510.17 22.91 472.67 24.07 472.67 24.08



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.14 463.33 20.10 463.33 20.08
February 451.67 20.52 297.33 20.38 297.33 20.32
March 483.67 21.21 180.83 21.08 171.50 20.97
April 382.67 21.51 138.67 21.83 61.83 21.70
May 261.00 22.39 194.50 23.19 13.00 23.28
June 147.83 22.70 323.33 23.74 16.50 23.84
July 86.50 23.41 381.83 24.03 21.33 24.15
August 114.17 22.61 347.83 23.66 10.17 23.72
September 247.67 22.21 200.83 23.13 13.50 23.21
October 451.33 21.76 43.67 21.81 27.50 21.76
November 486.33 20.99 193.67 20.78 193.67 20.66
December 497.00 20.44 407.50 20.37 407.50 20.35
             
Annual Sum or Average 4111.83 21.25 3173.33 21.65 1697.17 21.44
Minimum of Months 86.50 20.14 43.67 20.10 10.17 20.08
Maximum of Months 502.00 23.41 463.33 24.03 463.33 24.15



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 469.67 20.41 372.83 20.23 366.17 20.14
February 410.17 20.86 257.33 20.69 239.17 20.53
March 422.50 21.34 213.67 21.33 173.00 21.17
April 346.50 21.60 168.33 21.99 73.33 21.85
May 256.50 22.24 187.67 23.05 4.00 23.06
June 152.00 22.72 309.00 23.73 15.67 23.81
July 77.17 23.34 396.83 24.06 16.67 24.15
August 93.50 23.14 396.17 23.97 17.17 24.05
September 231.17 22.50 227.50 23.43 21.67 23.54
October 364.67 21.92 132.00 22.35 39.67 22.30
November 426.50 21.14 200.00 21.04 170.33 20.84
December 443.33 20.67 356.67 20.60 339.00 20.50
             
Annual Sum or Average 3693.67 21.43 3218.00 21.93 1475.83 21.69
Minimum of Months 77.17 20.41 132.00 20.23 4.00 20.14
Maximum of Months 469.67 23.34 396.83 24.06 366.17 24.15



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 501.00 20.47 393.17 20.37 393.17 20.34
February 437.67 20.87 217.00 20.77 208.00 20.68
March 451.00 21.52 95.83 21.64 58.33 21.56
April 324.00 22.19 132.33 22.83 19.83 22.94
May 254.83 22.42 205.83 23.20 15.67 23.29
June 134.33 23.24 362.83 24.01 40.33 24.13
July 89.83 25.34 465.17 24.53 81.00 24.67
August 84.17 24.80 483.17 24.40 68.00 24.50
September 251.00 22.35 202.17 23.25 22.00 23.37
October 412.17 21.91 58.67 22.21 0.67 22.21
November 453.67 21.42 101.33 21.30 90.00 21.16
December 491.83 21.01 199.17 20.86 199.17 20.78
             
Annual Sum or Average 3885.50 21.66 2916.67 22.25 1196.17 22.13
Minimum of Months 84.17 20.47 58.67 20.37 0.67 20.34
Maximum of Months 501.00 25.34 483.17 24.53 393.17 24.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.72 492.17 19.71 492.17 19.71
February 454.00 19.90 415.17 19.85 415.17 19.83
March 514.00 20.53 335.00 20.42 335.00 20.37
April 464.17 20.86 184.33 20.71 169.50 20.57
May 418.00 21.70 73.50 21.91 15.83 21.87
June 220.50 22.10 207.17 22.98 7.67 23.01
July 182.33 22.34 260.83 23.25 9.83 23.28
August 253.83 22.20 198.33 22.90 6.67 22.92
September 398.00 21.62 83.67 21.85 23.50 21.80
October 502.00 20.75 186.33 20.57 186.33 20.46
November 489.00 20.12 323.83 19.92 323.83 19.83
December 497.00 19.80 497.00 19.80 497.00 19.80
             
Annual Sum or Average 4894.83 20.74 3257.33 20.78 2482.50 20.58
Minimum of Months 182.33 19.72 73.50 19.71 6.67 19.71
Maximum of Months 514.00 22.34 497.00 23.25 497.00 23.28



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 19.50 414.83 19.48 414.83 19.47
February 385.00 19.79 337.83 19.69 337.83 19.66
March 423.17 20.63 239.83 20.43 238.50 20.33
April 337.33 21.05 164.17 21.18 112.17 20.98
May 266.83 22.06 138.17 22.84 18.00 22.93
June 171.83 22.57 235.17 23.57 25.00 23.72
July 131.50 23.29 287.00 24.00 34.33 24.19
August 170.67 22.45 235.50 23.37 15.50 23.46
September 252.50 21.83 143.50 22.60 27.17 22.62
October 416.83 21.11 125.50 20.94 122.33 20.82
November 417.00 20.12 275.33 19.90 275.33 19.81
December 422.00 19.64 415.00 19.63 415.00 19.63
             
Annual Sum or Average 3821.67 20.78 3011.83 21.03 2036.00 20.80
Minimum of Months 131.50 19.50 125.50 19.48 15.50 19.47
Maximum of Months 427.00 23.29 415.00 24.00 415.00 24.19



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 473.33 19.96 399.17 19.81 392.33 19.73
February 419.00 20.43 302.00 20.26 284.00 20.11
March 440.83 20.90 266.67 20.89 226.00 20.74
April 369.67 21.14 211.67 21.44 126.17 21.24
May 323.17 21.84 146.83 22.48 12.50 22.44
June 224.17 22.26 247.83 23.24 18.33 23.33
July 160.50 22.64 311.17 23.64 22.00 23.74
August 183.67 22.39 296.33 23.43 14.17 23.49
September 267.67 22.06 209.50 22.99 33.17 23.06
October 385.17 21.36 184.33 21.73 96.17 21.60
November 445.00 20.57 258.00 20.45 231.50 20.26
December 459.50 20.20 397.67 20.12 385.33 20.04
             
Annual Sum or Average 4151.67 21.05 3231.17 21.40 1841.67 21.15
Minimum of Months 160.50 19.96 146.83 19.81 12.50 19.73
Maximum of Months 473.33 22.64 399.17 23.64 392.33 23.74



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.78 471.83 19.74 471.83 19.72
February 449.67 20.15 357.83 20.02 356.00 19.97
March 489.83 20.73 271.00 20.61 263.67 20.52
April 393.83 21.12 184.17 21.33 115.67 21.17
May 359.00 21.83 126.33 22.41 16.67 22.47
June 215.50 22.28 263.67 23.35 27.33 23.47
July 177.83 23.01 325.83 23.83 50.50 23.99
August 182.00 22.32 297.17 23.40 23.50 23.48
September 332.67 21.73 148.33 22.41 29.17 22.45
October 459.67 20.99 152.50 20.94 129.67 20.81
November 482.17 20.31 290.17 20.11 287.00 20.00
December 497.00 19.94 462.50 19.90 462.50 19.88
             
Annual Sum or Average 4541.17 20.88 3351.33 21.15 2233.50 20.94
Minimum of Months 177.83 19.78 126.33 19.74 16.67 19.72
Maximum of Months 502.00 23.01 471.83 23.83 471.83 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.65 499.50 19.64 499.50 19.64
February 454.00 19.78 437.50 19.76 437.50 19.75
March 514.00 20.26 404.17 20.17 404.17 20.14
April 468.50 20.57 251.50 20.41 239.50 20.29
May 449.50 21.23 87.50 21.31 46.67 21.21
June 300.33 21.72 172.00 22.37 21.17 22.35
July 268.83 21.92 201.67 22.65 20.00 22.70
August 331.17 21.76 150.83 22.30 10.33 22.33
September 423.83 21.20 120.67 21.26 80.83 21.15
October 502.00 20.22 293.50 20.02 293.50 19.92
November 489.00 19.86 371.50 19.70 371.50 19.64
December 497.00 19.68 497.00 19.68 497.00 19.68
             
Annual Sum or Average 5200.17 20.52 3487.33 20.48 2921.67 20.31
Minimum of Months 268.83 19.65 87.50 19.64 10.33 19.64
Maximum of Months 514.00 21.92 499.50 22.65 499.50 22.70



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.65 487.67 19.63 487.67 19.63
February 454.00 19.80 411.33 19.74 411.33 19.72
March 512.00 20.42 324.83 20.23 324.83 20.14
April 415.33 20.86 232.67 20.89 184.67 20.72
May 343.17 21.63 144.17 22.28 28.50 22.27
June 221.33 22.19 284.67 23.22 37.00 23.33
July 181.00 22.69 327.00 23.64 39.67 23.79
August 223.83 22.01 277.83 23.04 17.00 23.10
September 322.33 21.40 189.50 22.02 55.83 21.88
October 499.50 20.51 227.00 20.28 226.50 20.15
November 489.00 19.90 355.83 19.73 355.83 19.65
December 497.00 19.69 495.50 19.69 495.50 19.69
             
Annual Sum or Average 4660.50 20.60 3758.00 20.83 2664.33 20.62
Minimum of Months 181.00 19.65 144.17 19.63 17.00 19.63
Maximum of Months 512.00 22.69 495.50 23.64 495.50 23.79



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 487.33 19.80 419.17 19.65 416.33 19.59
February 433.83 20.07 342.17 19.93 328.83 19.83
March 462.67 20.52 323.00 20.45 295.67 20.33
April 389.83 20.83 259.67 21.03 186.67 20.83
May 373.33 21.38 139.50 21.83 39.33 21.72
June 276.67 21.84 222.33 22.72 29.33 22.76
July 229.50 22.13 263.67 23.12 30.17 23.22
August 251.00 21.93 247.33 22.93 16.67 22.98
September 317.67 21.61 212.50 22.31 73.33 22.25
October 409.50 20.64 253.67 20.79 184.33 20.57
November 469.33 20.18 308.17 20.01 294.33 19.87
December 476.67 19.91 415.00 19.80 411.50 19.75
             
Annual Sum or Average 4577.33 20.72 3406.17 20.94 2306.50 20.71
Minimum of Months 229.50 19.80 139.50 19.65 16.67 19.59
Maximum of Months 487.33 22.13 419.17 23.12 416.33 23.22



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.69 481.00 19.66 481.00 19.65
February 450.33 19.93 394.00 19.84 392.50 19.81
March 495.17 20.48 328.50 20.34 323.67 20.26
April 400.00 20.86 241.67 21.01 175.50 20.82
May 380.83 21.59 145.33 22.08 48.17 22.06
June 251.83 22.13 252.83 23.09 48.00 23.21
July 231.17 22.81 302.17 23.60 72.00 23.78
August 245.00 22.23 263.67 23.14 37.83 23.24
September 358.50 21.52 176.33 22.05 71.50 22.02
October 467.83 20.57 230.17 20.40 213.00 20.25
November 484.33 20.01 331.83 19.81 329.50 19.72
December 497.00 19.76 472.00 19.72 472.00 19.71
             
Annual Sum or Average 4764.00 20.72 3619.50 20.91 2664.67 20.72
Minimum of Months 231.17 19.69 145.33 19.66 37.83 19.65
Maximum of Months 502.00 22.81 481.00 23.60 481.00 23.78



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.33 30.00 314.83 27.18 1.33 27.20
February 64.33 32.89 381.33 28.70 60.33 29.24
March 2.33 27.00 512.00 27.00 2.33 27.00
April 72.83 27.00 485.00 27.00 72.83 27.00
May 33.67 27.00 508.00 27.00 33.67 27.00
June 178.83 27.00 496.00 27.00 178.83 27.00
July 295.33 27.00 497.00 27.00 295.33 27.00
August 390.17 27.00 514.00 27.00 390.17 27.00
September 72.50 27.00 485.00 27.00 72.50 27.00
October 16.50 27.00 502.00 27.00 16.50 27.00
November 5.83 30.66 470.00 27.09 5.83 27.13
December 0.17 27.00 470.33 27.00 0.17 27.00
             
Annual Sum or Average 1133.83 27.36 5635.50 27.13 1129.83 27.16
Minimum of Months 0.17 27.00 314.83 27.00 0.17 27.00
Maximum of Months 390.17 32.89 514.00 28.70 390.17 29.24



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 102.50 26.25 125.50 26.69 0.00 26.69
February 86.17 30.47 273.50 28.73 52.17 29.24
March 0.17 27.00 412.50 27.00 0.00 27.00
April 21.17 27.00 465.83 27.00 21.17 27.00
May 18.67 27.00 508.00 27.00 18.67 27.00
June 99.00 27.00 496.00 27.00 99.00 27.00
July 125.50 27.00 497.00 27.00 125.50 27.00
August 146.50 27.00 514.00 27.00 146.50 27.00
September 36.67 27.00 485.00 27.00 36.67 27.00
October 5.17 27.00 484.67 27.00 5.17 27.00
November 14.83 28.02 350.17 27.08 3.67 27.12
December 35.67 27.00 247.83 27.00 0.00 27.00
             
Annual Sum or Average 692.00 27.34 4860.00 27.11 508.50 27.15
Minimum of Months 0.17 26.25 125.50 26.69 0.00 26.69
Maximum of Months 146.50 30.47 514.00 28.73 146.50 29.24



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 217.00 25.23 84.17 25.41 25.67 25.24
February 109.17 28.29 199.83 28.14 27.33 28.47
March 32.67 27.00 311.83 27.00 0.00 27.00
April 42.50 27.00 403.50 27.00 26.00 27.00
May 30.67 27.00 499.67 27.00 30.67 27.00
June 132.50 27.00 496.00 27.00 132.50 27.00
July 153.67 27.00 497.00 27.00 153.67 27.00
August 163.17 27.00 514.00 27.00 163.17 27.00
September 45.00 27.00 475.83 27.00 45.00 27.00
October 23.83 27.00 377.17 27.00 4.33 27.00
November 77.67 27.00 260.17 27.02 1.33 27.02
December 98.00 27.00 126.50 27.00 0.00 27.00
             
Annual Sum or Average 1125.83 26.78 4245.67 26.98 609.67 26.99
Minimum of Months 23.83 25.23 84.17 25.41 0.00 25.24
Maximum of Months 217.00 28.29 514.00 28.14 163.17 28.47



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 23.33 27.17 502.00 27.13 23.33 27.14
February 0.00 0.00 452.33 24.57 0.00 24.57
March 41.50 25.77 499.17 25.52 40.50 25.55
April 173.33 26.25 485.00 25.15 173.33 25.38
May 339.50 27.03 508.00 27.03 339.50 27.03
June 300.67 26.86 493.00 26.35 300.00 26.49
July 496.83 26.80 497.00 26.80 496.83 26.80
August 507.67 26.72 514.00 26.70 507.67 26.71
September 485.00 27.04 485.00 27.04 485.00 27.04
October 36.83 26.89 499.50 24.99 36.83 25.11
November 373.83 25.83 485.83 25.75 373.83 25.77
December 78.00 25.18 497.00 24.37 78.00 24.47
             
Annual Sum or Average 2856.50 26.65 5917.83 26.13 2854.83 26.26
Minimum of Months 0.00 0.00 452.33 24.37 0.00 24.47
Maximum of Months 507.67 27.17 514.00 27.13 507.67 27.14



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.11341 13.06163 0.58493 12.44040
February 454.00000 27.83407 15.14419 0.78597 20.21948
March 514.00000 27.00000 19.51547 0.75898 17.37600
April 485.00000 27.00003 25.40073 0.88414 21.81640
May 508.00000 27.00019 34.84358 0.23618 6.40542
June 496.00000 27.00018 37.99437 0.35861 7.90530
July 497.00000 27.00006 38.35611 0.43657 9.11383
August 514.00000 27.00037 37.10689 0.46849 9.72351
September 485.00000 27.00012 34.27881 0.25578 6.73048
October 502.00000 27.00000 25.39416 0.82194 19.47559
November 489.00000 27.04369 21.08087 0.77543 18.12807
December 497.00000 27.00000 14.04939 0.68730 15.10999
           
Annual Sum or Average 5943.00000 27.07697 26.43927 0.58598 13.63869
Minimum of Months 454.00000 27.00000 13.06163 0.23618 6.40542
Maximum of Months 514.00000 27.83407 38.35611 0.88414 21.81640



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.86550 13.11082 0.43644 9.57809
February 454.00000 27.71444 15.13523 0.66974 16.64228
March 514.00000 27.00000 19.51579 0.65272 14.27813
April 485.00000 27.00003 25.41324 0.77341 18.02856
May 508.00000 27.00018 34.90123 0.15686 5.84285
June 496.00000 27.00019 38.04917 0.27556 6.90240
July 497.00000 27.00006 38.43167 0.31810 7.33850
August 514.00000 27.00038 37.21310 0.32335 7.45253
September 485.00000 27.00012 34.30960 0.15889 5.99759
October 502.00000 27.00000 25.38798 0.72841 16.46797
November 489.00000 27.03128 21.07388 0.64062 14.20487
December 497.00000 27.00000 14.04180 0.53338 11.22097
           
Annual Sum or Average 5943.00000 27.04587 26.46957 0.47038 11.10802
Minimum of Months 454.00000 26.86550 13.11082 0.15686 5.84285
Maximum of Months 514.00000 27.71444 38.43167 0.77341 18.02856



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.23240 13.31907 0.24887 8.63773
February 454.00000 27.49894 15.13369 0.55443 13.06486
March 514.00000 27.00000 19.51579 0.57905 12.48314
April 485.00000 27.00003 25.45431 0.71292 16.41752
May 508.00000 27.00053 34.94010 0.11139 5.92239
June 496.00000 27.00019 38.05358 0.25802 7.05872
July 497.00000 27.00008 38.43927 0.30746 7.45288
August 514.00000 27.00034 37.33821 0.30328 7.46778
September 485.00000 27.00111 34.34293 0.09593 6.07113
October 502.00000 27.00000 25.39743 0.64300 14.19321
November 489.00000 27.01686 21.08308 0.55264 12.07451
December 497.00000 27.00000 14.04752 0.45193 9.62033
           
Annual Sum or Average 5943.00000 26.97485 26.51030 0.40004 10.00402
Minimum of Months 454.00000 26.23240 13.31907 0.09593 5.92239
Maximum of Months 514.00000 27.49894 38.43927 0.71292 16.41752



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.13297 29.97745 0.94398 23.88149
February 454.00000 24.56583 29.26283 0.60083 12.64481
March 514.00000 25.38581 28.09979 0.87197 21.45807
April 485.00000 24.76216 31.08243 0.93577 24.72981
May 508.00000 27.03641 38.17910 0.44501 9.29455
June 496.00000 26.01522 45.08610 0.46924 12.00198
July 497.00000 26.79961 46.04688 0.96148 24.87256
August 514.00000 26.67779 44.44979 1.10595 31.76524
September 485.00000 27.04156 36.52776 0.58231 12.29143
October 502.00000 24.83231 30.88989 0.78958 18.49690
November 489.00000 25.64815 29.21764 0.99297 26.14698
December 497.00000 24.24772 27.88972 0.84394 20.23460
           
Annual Sum or Average 5943.00000 25.85823 34.78273 0.79717 19.88987
Minimum of Months 454.00000 24.24772 27.88972 0.44501 9.29455
Maximum of Months 514.00000 27.13297 46.04688 1.10595 31.76524



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.13721 13.50635 -0.2551 7.49409
February 454.00000 22.73874 16.51270 -0.1091 6.59037
March 514.00000 23.43957 21.40168 0.08820 5.90120
April 485.00000 23.90143 28.56891 0.24273 6.82286
May 508.00000 24.12821 40.78224 -0.5038 11.01648
June 496.00000 24.31948 46.20726 -0.3715 8.56733
July 497.00000 24.53770 47.65735 -0.2772 7.52887
August 514.00000 24.44593 47.51388 -0.2829 7.66055
September 485.00000 24.36151 37.43773 -0.3947 9.86602
October 502.00000 24.32851 25.96193 0.36076 8.17209
November 489.00000 24.06262 22.38174 0.26593 7.43229
December 497.00000 23.38254 14.84921 0.04795 5.97832
           
Annual Sum or Average 5943.00000 23.82171 30.35374 -0.1000 7.75947
Minimum of Months 454.00000 22.13721 13.50635 -0.5038 5.90120
Maximum of Months 514.00000 24.53770 47.65735 0.36076 11.01648



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.86458 15.42081 -0.1196 6.34822
February 454.00000 23.22315 17.76777 -0.0095 6.15748
March 514.00000 23.81563 21.85342 0.18375 6.22082
April 485.00000 24.01398 28.76711 0.30367 7.40256
May 508.00000 24.09725 42.93189 -0.4519 9.80815
June 496.00000 24.22239 50.35849 -0.3280 7.64187
July 497.00000 24.27735 54.04917 -0.2646 6.80743
August 514.00000 24.28314 52.91121 -0.2594 6.80067
September 485.00000 24.23162 39.67597 -0.4132 9.30230
October 502.00000 24.16247 27.24520 0.32514 7.50190
November 489.00000 23.97801 23.27943 0.23780 6.94799
December 497.00000 23.62226 15.72536 0.08376 5.79581
           
Annual Sum or Average 5943.00000 23.90372 32.63631 -0.0604 7.23161
Minimum of Months 454.00000 22.86458 15.42081 -0.4519 5.79581
Maximum of Months 514.00000 24.28314 54.04917 0.32514 9.80815



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.45689 14.35628 -0.4816 12.41968
February 454.00000 22.10709 18.30626 -0.2923 8.81641
March 514.00000 23.01850 22.75037 -0.0287 6.47477
April 485.00000 23.44250 30.24187 0.14410 6.49432
May 508.00000 23.88300 43.73959 -0.5474 12.06272
June 496.00000 24.05386 51.12643 -0.4121 9.00610
July 497.00000 24.11951 55.03804 -0.3603 8.09822
August 514.00000 24.10002 54.23658 -0.3710 8.23036
September 485.00000 23.95065 40.82466 -0.5394 12.00152
October 502.00000 23.54158 28.88891 0.15148 6.09238
November 489.00000 22.75941 24.77285 -0.0825 7.67258
December 497.00000 21.95231 16.56869 -0.3412 9.47583
           
Annual Sum or Average 5943.00000 23.20726 33.54191 -0.2637 8.90219
Minimum of Months 454.00000 21.45689 14.35628 -0.5474 6.09238
Maximum of Months 514.00000 24.11951 55.03804 0.15148 12.41968



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.23483 15.14141 -0.8256 22.44799
February 454.00000 20.56591 19.25871 -0.6999 18.54137
March 514.00000 21.42070 24.30079 -0.4336 11.23028
April 485.00000 22.06502 32.03571 -0.1943 9.45532
May 508.00000 23.11070 45.71432 -0.8018 21.32978
June 496.00000 23.60004 52.95489 -0.5419 13.31918
July 497.00000 23.77489 57.08095 -0.4471 10.33153
August 514.00000 23.69329 56.41532 -0.4873 11.23289
September 485.00000 22.98626 43.27080 -0.8673 24.08007
October 502.00000 21.67179 31.59310 -0.3106 9.41842
November 489.00000 20.89859 26.76659 -0.5522 15.67954
December 497.00000 20.37805 17.71231 -0.7658 20.18054
           
Annual Sum or Average 5943.00000 22.04641 35.32989 -0.5764 15.56437
Minimum of Months 454.00000 20.23483 15.14141 -0.8673 9.41842
Maximum of Months 514.00000 23.77489 57.08095 -0.1943 24.08007



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.13058 13.75315 -0.8919 23.67438
February 454.00000 20.43826 18.01246 -0.7415 18.40741
March 514.00000 21.26688 23.06736 -0.4384 10.85098
April 485.00000 22.07228 30.27991 -0.1542 8.28882
May 508.00000 23.15426 43.91515 -0.7367 19.16049
June 496.00000 23.83051 50.68347 -0.4093 10.45644
July 497.00000 24.01925 54.40024 -0.3004 7.60749
August 514.00000 23.88798 53.47969 -0.3555 8.57955
September 485.00000 23.10356 41.09985 -0.7719 21.25171
October 502.00000 22.00866 29.18612 -0.1857 7.11336
November 489.00000 21.17397 24.87628 -0.4506 12.24691
December 497.00000 20.42459 16.31912 -0.7438 18.01381
           
Annual Sum or Average 5943.00000 22.13995 33.39348 -0.5134 13.75893
Minimum of Months 454.00000 20.13058 13.75315 -0.8919 7.11336
Maximum of Months 514.00000 24.01925 54.40024 -0.1542 23.67438



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.13690 13.46739 -0.8738 23.11743
February 454.00000 20.53709 17.64178 -0.6950 17.25251
March 514.00000 21.38294 22.71739 -0.3855 10.53401
April 485.00000 22.08042 30.10856 -0.1125 9.31693
May 508.00000 23.14255 43.90533 -0.6488 18.55517
June 496.00000 23.60105 51.08985 -0.3816 12.53559
July 497.00000 23.81384 54.86487 -0.2621 9.46713
August 514.00000 23.55685 54.31835 -0.3751 10.68950
September 485.00000 23.09018 40.91133 -0.6864 21.10535
October 502.00000 22.00540 29.04372 -0.1553 7.33335
November 489.00000 21.00298 25.04612 -0.4800 12.29223
December 497.00000 20.44265 16.03519 -0.7422 18.12887
           
Annual Sum or Average 5943.00000 22.07884 33.40406 -0.4818 14.15992
Minimum of Months 454.00000 20.13690 13.46739 -0.8738 7.33335
Maximum of Months 514.00000 23.81384 54.86487 -0.1125 23.11743



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.63789 13.33045 -0.7074 20.41287
February 454.00000 21.18602 17.17795 -0.5098 15.47482
March 514.00000 21.83916 22.25910 -0.2750 10.63318
April 485.00000 22.34134 29.68429 -0.0575 10.31670
May 508.00000 23.12455 43.98096 -0.7093 19.96416
June 496.00000 23.61056 51.20076 -0.4460 12.90676
July 497.00000 23.91472 54.64307 -0.2883 8.97804
August 514.00000 23.84361 53.47272 -0.3005 9.48713
September 485.00000 23.36450 40.34137 -0.5937 19.61787
October 502.00000 22.54609 28.17588 -0.0117 8.77138
November 489.00000 21.56597 24.45904 -0.3381 12.54194
December 497.00000 21.06557 15.68687 -0.5668 16.61006
           
Annual Sum or Average 5943.00000 22.43045 33.00958 -0.3998 13.78597
Minimum of Months 454.00000 20.63789 13.33045 -0.7093 8.77138
Maximum of Months 514.00000 23.91472 54.64307 -0.0117 20.41287



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.47209 13.06503 -0.7377 18.21631
February 454.00000 21.00291 17.03674 -0.5285 13.37628
March 514.00000 21.85405 21.91044 -0.2174 8.46703
April 485.00000 22.81718 28.66984 0.13316 9.40224
May 508.00000 23.12015 43.81589 -0.6135 17.50538
June 496.00000 23.81087 50.38391 -0.2564 10.85096
July 497.00000 24.26937 53.30298 -0.0278 7.94581
August 514.00000 24.23257 52.05701 -0.0416 7.34946
September 485.00000 23.16946 40.61844 -0.6108 19.21970
October 502.00000 22.30169 28.31131 -0.0414 7.15858
November 489.00000 21.60172 24.05316 -0.2827 9.52546
December 497.00000 21.03923 15.37381 -0.5184 12.12284
           
Annual Sum or Average 5943.00000 22.48639 32.52111 -0.3103 11.73300
Minimum of Months 454.00000 20.47209 13.06503 -0.7377 7.15858
Maximum of Months 514.00000 24.26937 53.30298 0.13316 19.21970



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.72328 13.17594 -1.0836 31.91752
February 454.00000 19.89626 17.85870 -0.9513 26.74410
March 514.00000 20.52531 23.59612 -0.6773 16.53965
April 485.00000 20.97360 32.10178 -0.4444 12.21450
May 508.00000 22.02720 46.62856 -1.0960 33.02705
June 496.00000 22.99432 53.29371 -0.6762 17.90561
July 497.00000 23.20088 57.63358 -0.5696 13.77265
August 514.00000 22.91137 57.17118 -0.6818 17.11354
September 485.00000 21.99648 43.77962 -1.1417 35.57490
October 502.00000 20.74807 31.32464 -0.5128 11.78151
November 489.00000 20.11942 26.08204 -0.7722 21.23081
December 497.00000 19.80398 16.03575 -1.0074 28.68752
           
Annual Sum or Average 5943.00000 21.25581 35.04169 -0.8000 22.16016
Minimum of Months 454.00000 19.72328 13.17594 -1.1417 11.78151
Maximum of Months 514.00000 23.20088 57.63358 -0.4444 35.57490



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 19.49885 13.09783 -1.1139 33.54936
February 385.00000 19.78525 17.59189 -0.9409 26.84050
March 433.00000 20.70378 23.03048 -0.5996 15.67097
April 410.00000 21.62165 30.51290 -0.2619 12.08543
May 430.00000 22.80292 44.51113 -0.7836 24.13248
June 418.00000 23.38220 51.86195 -0.4734 15.89959
July 422.00000 23.71895 55.77557 -0.3159 11.60783
August 433.00000 23.26631 55.64949 -0.4988 14.19940
September 410.00000 22.65824 41.87532 -0.8652 27.92128
October 427.00000 21.18690 30.13226 -0.3887 10.03875
November 417.00000 20.11929 25.35774 -0.7655 21.13905
December 422.00000 19.64274 15.92831 -1.0309 29.81355
           
Annual Sum or Average 5034.00000 21.54377 33.89571 -0.6682 20.18278
Minimum of Months 385.00000 19.49885 13.09783 -1.1139 10.03875
Maximum of Months 433.00000 23.71895 55.77557 -0.2619 33.54936



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.19348 12.83718 -0.8441 25.73342
February 454.00000 20.72814 16.91773 -0.6344 19.69226
March 514.00000 21.35235 22.39993 -0.4058 13.39566
April 485.00000 21.86887 30.41093 -0.1822 12.20700
May 508.00000 22.61489 45.23963 -0.8687 25.91379
June 496.00000 23.15724 52.72248 -0.5906 17.31327
July 497.00000 23.49733 56.56174 -0.4288 12.41295
August 514.00000 23.35357 55.57806 -0.4658 13.67475
September 485.00000 22.96507 41.37279 -0.7197 24.58922
October 502.00000 22.02088 29.08620 -0.1349 10.25481
November 489.00000 20.93562 25.04154 -0.5156 16.76623
December 497.00000 20.50354 15.33856 -0.7491 22.34269
           
Annual Sum or Average 5943.00000 21.94275 33.77651 -0.5446 17.83452
Minimum of Months 454.00000 20.19348 12.83718 -0.8687 10.25481
Maximum of Months 514.00000 23.49733 56.56174 -0.1349 25.91379



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.78119 13.01186 -1.0158 29.45736
February 454.00000 20.18197 17.36312 -0.8210 22.60465
March 514.00000 20.88252 22.94395 -0.5437 14.12070
April 485.00000 21.66411 30.74544 -0.2186 11.74757
May 508.00000 22.42166 45.67167 -0.8941 27.62646
June 496.00000 23.19399 52.47469 -0.5118 17.03252
July 497.00000 23.57008 56.22653 -0.3382 12.46011
August 514.00000 23.28849 55.73445 -0.4489 13.68693
September 485.00000 22.43185 42.57878 -0.9183 30.09572
October 502.00000 21.23708 30.31683 -0.3555 10.23498
November 489.00000 20.36072 25.64437 -0.6806 18.49901
December 497.00000 19.94496 15.75083 -0.9271 25.65633
           
Annual Sum or Average 5943.00000 21.59213 34.18783 -0.6381 19.39213
Minimum of Months 454.00000 19.78119 13.01186 -1.0158 10.23498
Maximum of Months 514.00000 23.57008 56.22653 -0.2186 30.09572



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.64707 13.61647 -1.1645 35.24539
February 454.00000 19.78108 18.22089 -1.0452 30.61419
March 514.00000 20.26373 24.08343 -0.7951 20.71088
April 485.00000 20.66652 32.87810 -0.5600 15.49149
May 508.00000 21.49211 48.19637 -1.2800 41.29036
June 496.00000 22.43416 55.57111 -0.8358 24.09228
July 497.00000 22.61652 60.59313 -0.7233 19.07175
August 514.00000 22.32714 59.96612 -0.8463 23.24232
September 485.00000 21.48352 45.34559 -1.3367 44.51003
October 502.00000 20.22460 32.30680 -0.6928 17.79107
November 489.00000 19.85816 26.57749 -0.9040 26.02333
December 497.00000 19.68157 16.51372 -1.1071 32.85436
           
Annual Sum or Average 5943.00000 20.88319 36.31689 -0.9401 27.54060
Minimum of Months 454.00000 19.64707 13.61647 -1.3367 15.49149
Maximum of Months 514.00000 22.61652 60.59313 -0.5600 44.51003



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.65271 13.60403 -1.1301 34.01559
February 454.00000 19.80224 18.18642 -0.9915 28.85146
March 514.00000 20.43170 23.76375 -0.7036 18.61226
April 485.00000 21.30804 31.56291 -0.3676 13.78620
May 508.00000 22.38600 45.93299 -0.9196 29.08139
June 496.00000 23.10213 53.31862 -0.5369 18.70841
July 497.00000 23.44005 57.67066 -0.3684 13.20167
August 514.00000 22.98782 57.60403 -0.5578 16.50533
September 485.00000 22.25644 43.19398 -1.0082 33.62781
October 502.00000 20.52853 31.69584 -0.5820 14.57425
November 489.00000 19.89985 26.49767 -0.8726 24.86520
December 497.00000 19.69224 16.48989 -1.0809 31.90965
           
Annual Sum or Average 5943.00000 21.30340 35.11231 -0.7581 23.08077
Minimum of Months 454.00000 19.65271 13.60403 -1.1301 13.20167
Maximum of Months 514.00000 23.44005 57.67066 -0.3676 34.01559



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.91648 13.39802 -0.9673 29.87665
February 454.00000 20.23755 17.64104 -0.8016 24.34854
March 514.00000 20.87288 23.14275 -0.5652 17.30485
April 485.00000 21.49024 31.25090 -0.3118 14.88502
May 508.00000 22.05271 46.83841 -1.0604 33.98572
June 496.00000 22.68595 54.73198 -0.7259 22.73828
July 497.00000 23.01148 59.18840 -0.5559 16.79012
August 514.00000 22.86803 58.06615 -0.6035 18.55123
September 485.00000 22.44212 42.87352 -0.9168 32.42424
October 502.00000 21.30280 30.33739 -0.3508 14.02501
November 489.00000 20.34540 25.89530 -0.7097 21.33309
December 497.00000 20.07799 16.09986 -0.9073 27.38736
           
Annual Sum or Average 5943.00000 21.45201 35.11324 -0.7059 22.78292
Minimum of Months 454.00000 19.91648 13.39802 -1.0604 14.02501
Maximum of Months 514.00000 23.01148 59.18840 -0.3118 33.98572



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.68599 13.55701 -1.0961 32.76893
February 454.00000 19.95650 17.94648 -0.9247 26.61069
March 514.00000 20.60783 23.48883 -0.6511 17.54551
April 485.00000 21.42059 31.41324 -0.3104 14.33295
May 508.00000 22.15065 46.53833 -0.9970 32.64334
June 496.00000 22.96876 53.77462 -0.5753 20.28791
July 497.00000 23.33080 58.06456 -0.3953 14.91918
August 514.00000 23.02513 57.50895 -0.5221 16.69370
September 485.00000 22.14734 43.56583 -1.0391 35.81377
October 502.00000 20.79551 31.15137 -0.5034 14.41398
November 489.00000 20.04531 26.25705 -0.8063 23.01394
December 497.00000 19.75753 16.39707 -1.0269 29.84536
           
Annual Sum or Average 5943.00000 21.33634 35.12533 -0.7359 23.19276
Minimum of Months 454.00000 19.68599 13.55701 -1.0961 14.33295
Maximum of Months 514.00000 23.33080 58.06456 -0.3104 35.81377



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.980059E+09 20959.75 13-JAN-22:03 103.84 0.437438E+10 0.00 0.535444E+10 0.62 4.50 13-JAN-22:50 0.00 0.00
February 0.370377E+11 153978.25 24-FEB-19:02 207.65 0.167128E+12 0.00 0.204165E+12 1.39 6.54 24-FEB-19:02 0.00 0.00
March 0.590651E+11 166321.28 23-MAR-13:32 564.59 0.276727E+12 0.00 0.335792E+12 3.59 6.71 23-MAR-13:32 0.00 0.00
April 0.858220E+11 272923.35 18-APR-09:10 595.26 0.458823E+12 0.00 0.544645E+12 4.05 7.04 15-APR-17:41 0.00 0.00
May 0.872156E+11 272337.82 30-MAY-10:30 303.54 0.489633E+12 0.00 0.576849E+12 2.06 7.01 28-MAY-17:32 0.00 0.00
June 0.228807E+12 286893.39 18-JUN-15:33 490.33 0.139819E+13 0.00 0.162700E+13 3.87 7.12 13-JUN-04:13 0.00 0.00
July 0.289025E+12 283167.05 18-JUL-12:50 657.67 0.179603E+13 0.00 0.208506E+13 5.03 7.12 28-JUL-04:12 0.00 0.00
August 0.294136E+12 294685.66 03-AUG-05:03 692.44 0.182792E+13 0.00 0.212205E+13 5.25 7.20 29-AUG-13:40 0.00 0.00
September 0.114335E+12 280018.36 05-SEP-14:00 311.75 0.694738E+12 0.00 0.809073E+12 2.36 7.09 11-SEP-05:03 0.00 0.00
October 0.548636E+11 220090.00 20-OCT-13:00 245.71 0.262237E+12 0.00 0.317101E+12 1.53 7.01 20-OCT-13:00 0.00 0.00
November 0.511387E+11 178190.74 03-NOV-11:15 652.06 0.245786E+12 0.00 0.296925E+12 4.33 6.92 03-NOV-13:32 0.00 0.00
December 0.597620E+11 141791.28 05-DEC-13:38 649.39 0.285976E+12 0.00 0.345738E+12 4.18 6.23 05-DEC-13:38 0.00 0.00
                         
Annual Sum or Average 0.136219E+13     5474.21 0.790756E+13 0.00 0.926975E+13 3.20     0.00 0.00
Minimum of Months 0.980059E+09 20959.75   103.84 0.437438E+10 0.00 0.535444E+10 0.62 4.50   0.00 0.00
Maximum of Months 0.294136E+12 294685.66   692.44 0.182792E+13 0.00 0.212205E+13 5.25 7.20   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 0.00
February 0.00 0.00 01-FEB-00:01 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:01 0.00 0.00
March 0.00 0.00 01-MAR-00:01 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:01 0.00 0.00
April 0.412852E+10 185899.06 18-APR-09:20 6.83 0.264633E+11 0.00 0.305918E+11 0.06 6.75 18-APR-09:20 0.00 0.00
May 0.263919E+10 189729.15 30-MAY-14:05 4.67 0.168379E+11 0.00 0.194771E+11 0.04 6.68 30-MAY-14:05 0.00 0.00
June 0.308780E+11 264282.76 30-JUN-04:14 52.05 0.195339E+12 0.00 0.226217E+12 0.46 6.85 27-JUN-04:14 0.00 0.00
July 0.603377E+11 260677.26 27-JUL-04:14 101.89 0.381569E+12 0.00 0.441907E+12 0.86 6.90 15-JUL-04:14 0.00 0.00
August 0.739969E+11 294685.66 03-AUG-05:03 121.19 0.471177E+12 0.00 0.545174E+12 1.03 6.90 29-AUG-12:05 0.00 0.00
September 0.108068E+11 197579.54 11-SEP-12:05 19.50 0.686910E+11 0.00 0.794978E+11 0.17 6.80 07-SEP-12:05 0.00 0.00
October 0.00 0.00 01-OCT-00:01 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:01 0.00 0.00
November 0.00 0.00 01-NOV-00:01 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:01 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:01 0.00 0.00
                         
Annual Sum or Average 0.182787E+12     306.14 0.116008E+13 0.00 0.134286E+13 0.22     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.739969E+11 294685.66   121.19 0.471177E+12 0.00 0.545174E+12 1.03 6.90   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:02 330796.47 14-JAN-00:20 21.02 21.00 2.43
February 536429.58 14.76 45.69 09-FEB-18:39 735973.34 15-FEB-05:55 21.31 21.07 27.76
March 43747488.51 85.09 4612.22 19-MAR-14:15 1132062.74 23-MAR-13:34 21.36 20.98 46.07
April 0.434692E+10 130.36 29261.06 14-APR-13:30 2007487.23 14-APR-14:20 21.56 20.96 57.06
May 0.759074E+10 234.04 29261.06 04-MAY-13:40 2089443.74 05-MAY-16:00 21.85 21.28 35.56
June 0.299084E+11 483.26 29261.06 08-JUN-11:00 2188556.56 23-JUN-15:00 23.76 22.15 63.92
July 0.431134E+11 615.95 29261.06 01-JUL-07:40 2199175.30 18-JUL-12:50 24.17 22.17 82.31
August 0.406679E+11 585.15 29261.06 01-AUG-06:55 2155491.28 17-AUG-10:40 24.11 22.04 85.57
September 0.115700E+11 251.35 29261.06 01-SEP-15:00 2170200.40 05-SEP-14:00 22.12 21.31 38.08
October 0.429446E+09 174.28 11838.55 20-OCT-15:00 1768402.04 20-OCT-13:00 21.95 21.63 30.53
November 30181880.84 21.51 5484.46 03-NOV-13:40 1384260.22 03-NOV-13:40 21.19 20.83 48.50
December 71270.49 1.19 44.51 05-DEC-16:08 769891.28 05-DEC-16:08 21.12 20.71 47.70
                   
Annual Sum or Average 0.137701E+12 2596.94         22.13 21.35 47.23
Minimum of Months 0.00 0.00 0.00   330796.47   21.02 20.71 2.43
Maximum of Months 0.431134E+11 615.95 29261.06   2199175.30   24.17 22.17 85.57



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:02 0.00 01-JAN-00:02 21.02 21.02 0.00
February 0.00 0.00 0.00 01-FEB-00:01 0.00 01-FEB-00:01 21.31 21.31 0.00
March 0.00 0.00 0.00 01-MAR-00:01 0.00 01-MAR-00:01 21.36 21.36 0.00
April 0.113679E+10 10.79 29261.06 15-APR-12:00 1367936.93 18-APR-15:10 21.56 21.50 1.17
May 0.693487E+09 6.58 29261.06 12-MAY-14:20 1487533.89 31-MAY-14:05 21.85 21.82 0.72
June 0.716512E+10 68.14 29261.06 09-JUN-09:50 1729495.56 23-JUN-15:20 23.76 23.43 7.96
July 0.132081E+11 125.55 29261.06 02-JUL-12:21 1781958.68 18-JUL-15:40 24.17 23.58 14.49
August 0.148639E+11 141.52 29261.06 01-AUG-07:20 1816002.86 16-AUG-13:10 24.11 23.42 16.51
September 0.198035E+10 18.83 29261.06 05-SEP-14:05 1814698.49 01-SEP-14:05 22.12 22.03 2.42
October 0.00 0.00 0.00 01-OCT-00:01 0.00 01-OCT-00:01 21.95 21.95 0.00
November 0.00 0.00 0.00 01-NOV-00:01 0.00 01-NOV-00:01 21.19 21.19 0.00
December 0.00 0.00 0.00 01-DEC-00:01 0.00 01-DEC-00:01 21.12 21.12 0.00
                   
Annual Sum or Average 0.390477E+11 371.41         22.13 21.98 3.64
Minimum of Months 0.00 0.00 0.00   0.00   21.02 21.02 0.00
Maximum of Months 0.148639E+11 141.52 29261.06   1816002.86   24.17 23.58 16.51



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.151239E+13 0.00 676.42 4543504.69 02-JAN-04:01 0.00 37.04 76.58 3.46 0.00 0.13 1.02 02-JAN-04:01
February 0.940972E+12 0.00 587.61 3940492.96 21-FEB-05:01 0.00 35.01 72.84 2.39 0.00 0.09 0.89 21-FEB-05:01
March 0.489610E+12 0.00 535.54 3505456.42 25-MAR-04:01 0.00 27.93 61.85 0.98 0.00 0.04 0.79 25-MAR-04:01
April 0.196402E+12 0.00 379.48 3657453.71 01-APR-04:01 0.00 24.55 48.95 0.41 0.00 0.02 0.82 01-APR-04:01
May 0.319122E+11 0.00 197.91 3267873.93 02-MAY-04:11 0.00 21.67 33.26 0.07 0.00 0.00 0.74 02-MAY-04:11
June 0.106214E+11 0.00 97.14 2871209.72 02-JUN-05:01 0.00 20.63 26.61 0.02 0.00 0.00 0.65 02-JUN-05:01
July 0.133153E+10 0.00 49.95 208703.21 24-JUL-05:01 0.00 20.20 23.25 0.00 0.00 0.00 0.05 24-JUL-05:01
August 0.406522E+10 0.00 84.30 388786.70 07-AUG-05:02 0.00 20.40 25.51 0.01 0.00 0.00 0.09 07-AUG-05:02
September 0.518923E+11 0.00 222.73 3359021.90 30-SEP-04:01 0.00 22.23 35.66 0.11 0.00 0.00 0.76 30-SEP-04:01
October 0.155409E+12 0.00 411.39 3615852.69 16-OCT-04:11 0.00 24.41 49.00 0.33 0.00 0.01 0.81 16-OCT-04:11
November 0.562531E+12 0.00 555.89 3718956.36 28-NOV-05:01 0.00 30.71 64.57 1.24 0.00 0.05 0.84 28-NOV-05:01
December 0.107545E+13 0.00 665.41 3831784.04 18-DEC-05:01 0.00 34.07 75.21 2.28 0.00 0.09 0.86 18-DEC-05:01
                           
Annual Sum or Average 0.503259E+13 0.00 4463.77     0.00 26.52 49.31 0.94 0.00 0.04    
Minimum of Months 0.133153E+10 0.00 49.95 208703.21   0.00 20.20 23.25 0.00 0.00 0.00 0.05  
Maximum of Months 0.151239E+13 0.00 676.42 4543504.69   0.00 37.04 76.58 3.46 0.00 0.13 1.02  



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 3659.99 0.00 2.70 3659.99 0.00 0.00 0.00 0.00 0.52 08-JAN-02:03 0.52 08-JAN-02:03 0.00 0.00 0.00
February 183693.85 0.00 0.62 183693.85 0.00 0.00 0.00 0.00 2221.65 10-FEB-17:01 2221.65 10-FEB-17:01 0.00 0.00 0.00
March 0.883886E+09 0.00 19.04 0.883886E+09 0.00 0.00 0.00 0.00 39800.80 19-MAR-13:21 39800.80 19-MAR-13:21 0.00 0.00 0.00
April 0.164551E+11 0.00 96.36 0.151966E+11 0.00 0.00 0.00 0.00 167381.03 16-APR-14:51 142272.94 18-APR-15:00 0.00 0.00 0.00
May 0.369068E+11 0.00 261.16 0.335970E+11 0.00 0.00 0.00 0.00 145765.81 31-MAY-15:00 134178.08 31-MAY-15:00 0.00 0.00 0.00
June 0.103571E+12 0.00 372.07 0.882616E+11 0.00 0.00 0.00 0.00 227806.42 26-JUN-04:11 172318.52 26-JUN-04:11 0.00 0.00 0.00
July 0.150557E+12 0.00 478.94 0.119646E+12 0.00 0.00 0.00 0.00 208762.35 27-JUL-05:03 162009.71 26-JUL-04:11 0.00 0.00 0.00
August 0.151392E+12 0.00 470.49 0.121754E+12 0.00 0.00 0.00 0.00 231607.67 03-AUG-05:02 166247.73 04-AUG-15:20 0.00 0.00 0.00
September 0.575551E+11 0.00 250.14 0.550442E+11 0.00 0.00 0.00 0.00 175118.89 11-SEP-04:11 152609.98 06-SEP-15:20 0.00 0.00 0.00
October 0.518290E+10 0.00 61.11 0.518290E+10 0.00 0.00 0.00 0.00 107946.67 20-OCT-15:00 107946.67 20-OCT-15:00 0.00 0.00 0.00
November 0.335923E+09 0.00 11.64 0.335535E+09 0.00 0.00 0.00 0.00 48686.93 09-NOV-06:02 42227.79 09-NOV-06:02 0.00 0.00 0.00
December 166115.13 0.00 0.60 166115.13 0.00 0.00 0.00 0.00 750.52 01-DEC-17:03 750.52 01-DEC-17:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.522840E+12 0.00 2024.86 0.439902E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 3659.99 0.00 0.60 3659.99 0.00 0.00 0.00 0.00 0.52   0.52   0.00 0.00 0.00
Maximum of Months 0.151392E+12 0.00 478.94 0.121754E+12 0.00 0.00 0.00 0.00 231607.67   172318.52   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 127639.66 0.00 43.64 127639.66 0.00 0.00 0.00 0.00 5.36 01-JAN-16:43 5.36 01-JAN-16:43 0.00 0.00 0.00
February 554628.57 0.00 37.51 554628.57 0.00 0.00 0.00 0.00 7452.31 24-FEB-10:01 7452.31 24-FEB-10:01 0.00 0.00 0.00
March 0.136351E+11 0.00 82.80 0.136351E+11 0.00 0.00 0.00 0.00 642619.62 24-MAR-14:01 642619.62 24-MAR-14:01 0.00 0.00 0.00
April 0.147229E+12 0.00 179.35 0.134721E+12 0.00 0.00 0.00 0.00 1498924.52 18-APR-14:05 1257048.60 18-APR-14:05 0.00 0.00 0.00
May 0.357255E+12 0.00 272.38 0.325491E+12 0.00 0.00 0.00 0.00 1403143.10 31-MAY-14:05 1283721.90 31-MAY-15:00 0.00 0.00 0.00
June 0.953554E+12 0.00 372.84 0.802116E+12 0.00 0.00 0.00 0.00 2146880.78 13-JUN-05:01 1423933.09 30-JUN-04:11 0.00 0.00 0.00
July 0.128437E+13 0.00 441.84 0.100749E+13 0.00 0.00 0.00 0.00 2047954.22 27-JUL-05:03 1328430.81 26-JUL-04:11 0.00 0.00 0.00
August 0.124624E+13 0.00 435.02 0.985155E+12 0.00 0.00 0.00 0.00 2598503.78 03-AUG-05:02 1586144.32 03-AUG-05:02 0.00 0.00 0.00
September 0.525828E+12 0.00 259.98 0.504184E+12 0.00 0.00 0.00 0.00 1595941.38 06-SEP-14:05 1452921.56 07-SEP-14:05 0.00 0.00 0.00
October 0.600434E+11 0.00 103.38 0.600434E+11 0.00 0.00 0.00 0.00 981527.99 20-OCT-15:00 981527.99 20-OCT-15:00 0.00 0.00 0.00
November 0.627949E+10 0.00 60.95 0.627949E+10 0.00 0.00 0.00 0.00 734801.32 03-NOV-14:02 734801.32 03-NOV-14:02 0.00 0.00 0.00
December 114693.28 0.00 40.74 114693.28 0.00 0.00 0.00 0.00 5.59 02-DEC-16:07 5.59 02-DEC-16:07 0.00 0.00 0.00
                               
Annual Sum or Average 0.459444E+13 0.00 2330.44 0.383911E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 114693.28 0.00 37.51 114693.28 0.00 0.00 0.00 0.00 5.36   5.36   0.00 0.00 0.00
Maximum of Months 0.128437E+13 0.00 441.84 0.100749E+13 0.00 0.00 0.00 0.00 2598503.78   1586144.32   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 3783396.36 0.00 3.95 3783396.36 0.00 0.00 0.00 0.00 3347.61 02-JAN-06:01 3347.61 02-JAN-06:01 0.00 0.00 0.00
February 3968659.65 0.00 8.70 3968659.65 0.00 0.00 0.00 0.00 8640.76 06-FEB-06:12 8640.76 06-FEB-06:12 0.00 0.00 0.00
March 0.633974E+09 0.00 21.43 0.633974E+09 0.00 0.00 0.00 0.00 28778.33 25-MAR-14:57 28778.33 25-MAR-14:57 0.00 0.00 0.00
April 0.160024E+11 0.00 93.03 0.148713E+11 0.00 0.00 0.00 0.00 183505.27 16-APR-16:21 151047.48 18-APR-15:00 0.00 0.00 0.00
May 0.391425E+11 0.00 246.74 0.364163E+11 0.00 0.00 0.00 0.00 173833.49 31-MAY-15:00 163358.85 31-MAY-15:00 0.00 0.00 0.00
June 0.108946E+12 0.00 355.34 0.943255E+11 0.00 0.00 0.00 0.00 291819.28 25-JUN-15:01 219349.98 25-JUN-15:01 0.00 0.00 0.00
July 0.144089E+12 0.00 429.80 0.117918E+12 0.00 0.00 0.00 0.00 284430.01 20-JUL-05:02 199564.03 02-JUL-14:31 0.00 0.00 0.00
August 0.137558E+12 0.00 422.87 0.112298E+12 0.00 0.00 0.00 0.00 352989.54 03-AUG-04:01 190722.33 04-AUG-15:00 0.00 0.00 0.00
September 0.565082E+11 0.00 236.88 0.547364E+11 0.00 0.00 0.00 0.00 218712.19 11-SEP-05:02 176503.75 07-SEP-14:00 0.00 0.00 0.00
October 0.432015E+10 0.00 56.02 0.432015E+10 0.00 0.00 0.00 0.00 101476.74 20-OCT-15:00 101476.74 20-OCT-15:00 0.00 0.00 0.00
November 0.146621E+09 0.00 21.51 0.146621E+09 0.00 0.00 0.00 0.00 12066.10 03-NOV-14:45 12066.10 03-NOV-14:45 0.00 0.00 0.00
December 13278601.60 0.00 13.35 13278601.60 0.00 0.00 0.00 0.00 7464.80 09-DEC-06:12 7464.80 09-DEC-06:12 0.00 0.00 0.00
                               
Annual Sum or Average 0.507367E+12 0.00 1909.63 0.435687E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 3783396.36 0.00 3.95 3783396.36 0.00 0.00 0.00 0.00 3347.61   3347.61   0.00 0.00 0.00
Maximum of Months 0.144089E+12 0.00 429.80 0.117918E+12 0.00 0.00 0.00 0.00 352989.54   219349.98   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 91396726.16 0.00 1.44 91396726.16 0.00 0.00 0.00 0.00 57352.63 14-JAN-06:06 57352.63 14-JAN-06:06 0.00 0.00 0.00
February 0.141126E+09 0.00 3.32 0.141126E+09 0.00 0.00 0.00 0.00 71888.09 24-FEB-06:02 71888.09 24-FEB-06:02 0.00 0.00 0.00
March 0.159179E+10 0.00 26.26 0.159179E+10 0.00 0.00 0.00 0.00 111024.43 27-MAR-04:02 111024.43 27-MAR-04:02 0.00 0.00 0.00
April 0.839460E+10 0.00 92.05 0.729454E+10 0.00 0.00 0.00 0.00 101866.56 19-APR-05:00 101866.56 19-APR-05:00 0.00 0.00 0.00
May 0.265414E+11 0.00 237.58 0.205393E+11 0.00 0.00 0.00 0.00 109014.91 11-MAY-15:55 81197.26 10-MAY-04:17 0.00 0.00 0.00
June 0.584613E+11 0.00 343.21 0.427109E+11 0.00 0.00 0.00 0.00 156178.16 27-JUN-04:51 118280.74 07-JUN-04:54 0.00 0.00 0.00
July 0.797603E+11 0.00 377.18 0.537192E+11 0.00 0.00 0.00 0.00 141753.47 06-JUL-04:53 97522.12 26-JUL-04:11 0.00 0.00 0.00
August 0.866746E+11 0.00 416.63 0.604414E+11 0.00 0.00 0.00 0.00 147078.68 21-AUG-03:50 117329.13 03-AUG-03:01 0.00 0.00 0.00
September 0.406882E+11 0.00 291.13 0.358761E+11 0.00 0.00 0.00 0.00 132418.92 04-SEP-16:49 132418.92 04-SEP-16:49 0.00 0.00 0.00
October 0.130509E+11 0.00 146.96 0.127358E+11 0.00 0.00 0.00 0.00 133113.02 13-OCT-03:13 133113.02 13-OCT-03:13 0.00 0.00 0.00
November 0.524580E+10 0.00 87.42 0.511697E+10 0.00 0.00 0.00 0.00 110622.20 22-NOV-05:46 110622.20 22-NOV-05:46 0.00 0.00 0.00
December 0.626302E+09 0.00 12.54 0.626302E+09 0.00 0.00 0.00 0.00 111808.05 06-DEC-06:00 111808.05 06-DEC-06:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.321268E+12 0.00 2035.72 0.240885E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 91396726.16 0.00 1.44 91396726.16 0.00 0.00 0.00 0.00 57352.63   57352.63   0.00 0.00 0.00
Maximum of Months 0.866746E+11 0.00 416.63 0.604414E+11 0.00 0.00 0.00 0.00 156178.16   133113.02   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 3673730.69 0.00 172.45 3673730.69 0.00 0.00 0.00 0.00 59.12 07-JAN-21:52 59.12 07-JAN-21:52 0.00 0.00 0.00
February 0.157489E+12 0.00 397.52 0.157489E+12 0.00 0.00 0.00 0.00 319619.24 03-FEB-19:01 319619.24 03-FEB-19:01 0.00 0.00 0.00
March 0.234796E+12 0.00 626.90 0.234796E+12 0.00 0.00 0.00 0.00 323587.96 06-MAR-14:22 323587.96 06-MAR-14:22 0.00 0.00 0.00
April 0.266969E+12 0.00 720.00 0.266155E+12 0.00 0.00 0.00 0.00 524759.64 18-APR-08:35 395993.95 16-APR-16:24 0.00 0.00 0.00
May 0.257935E+11 0.00 300.37 0.257935E+11 0.00 0.00 0.00 0.00 232181.06 31-MAY-23:53 232181.06 31-MAY-23:53 0.00 0.00 0.00
June 0.332473E+12 0.00 510.09 0.284726E+12 0.00 0.00 0.00 0.00 546139.23 13-JUN-06:52 320976.17 22-JUN-15:03 0.00 0.00 0.00
July 0.466481E+12 0.00 743.95 0.427794E+12 0.00 0.00 0.00 0.00 517195.35 06-JUL-05:51 294799.82 04-JUL-23:07 0.00 0.00 0.00
August 0.610095E+12 0.00 743.33 0.548152E+12 0.00 0.00 0.00 0.00 560533.96 31-AUG-12:03 410106.39 04-AUG-05:05 0.00 0.00 0.00
September 0.564076E+11 0.00 363.22 0.564076E+11 0.00 0.00 0.00 0.00 266531.88 30-SEP-23:21 266531.88 30-SEP-23:21 0.00 0.00 0.00
October 0.168013E+12 0.00 448.46 0.167061E+12 0.00 0.00 0.00 0.00 344387.31 20-OCT-16:13 344387.31 20-OCT-16:13 0.00 0.00 0.00
November 0.204747E+12 0.00 716.18 0.204462E+12 0.00 0.00 0.00 0.00 326592.57 01-NOV-00:22 326592.57 01-NOV-00:22 0.00 0.00 0.00
December 0.255899E+12 0.00 744.00 0.255899E+12 0.00 0.00 0.00 0.00 260591.73 19-DEC-06:10 260591.73 19-DEC-06:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.277917E+13 0.00 6486.48 0.262874E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 3673730.69 0.00 172.45 3673730.69 0.00 0.00 0.00 0.00 59.12   59.12   0.00 0.00 0.00
Maximum of Months 0.610095E+12 0.00 744.00 0.548152E+12 0.00 0.00 0.00 0.00 560533.96   410106.39   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.344206E+10 0.108602E+10 683.60 0.344206E+10 -0.0 0.00 1.00 30-JAN-13:01 0.00 01-JAN-00:07 8799.44 30-JAN-13:01 8799.44 30-JAN-13:01 0.00 19-JAN-12:02 2289.18 30-JAN-13:01 0.00 01-JAN-00:02
February 0.766102E+10 0.220850E+10 590.17 0.766102E+10 -0.0 0.00 1.00 04-FEB-10:31 0.00 01-FEB-00:41 13114.04 04-FEB-10:31 13114.04 04-FEB-10:31 0.00 08-FEB-15:13 3515.78 04-FEB-10:31 0.00 01-FEB-00:01
March 0.158367E+11 0.418902E+10 744.00 0.158364E+11 260576.55 0.00 1.00 05-MAR-17:21 0.72 06-MAR-07:01 7978.41 31-MAR-23:47 7978.41 31-MAR-23:47 42.40 29-MAR-16:00 2058.16 31-MAR-23:47 0.00 01-MAR-00:01
April 0.211777E+11 0.550263E+10 720.00 0.211511E+11 26587787.50 0.00 1.00 01-APR-00:03 0.49 30-APR-24:00 9692.42 16-APR-17:53 9688.98 16-APR-18:00 347.62 18-APR-15:50 2845.91 15-APR-17:53 0.00 01-APR-00:03
May 0.754346E+10 0.227628E+10 744.00 0.744951E+10 93950998.22 0.00 0.72 31-MAY-23:30 0.32 02-MAY-06:10 4855.11 31-MAY-23:20 4821.01 31-MAY-23:51 258.35 12-MAY-16:00 1348.56 31-MAY-23:20 0.00 01-MAY-00:10
June 0.128432E+11 0.364407E+10 720.00 0.126384E+11 0.204784E+09 0.00 0.94 30-JUN-23:51 0.60 03-JUN-06:51 6732.73 30-JUN-23:51 6729.52 30-JUN-23:51 456.36 13-JUN-15:00 1869.56 26-JUN-16:00 0.00 01-JUN-00:10
July 0.187805E+11 0.495672E+10 744.00 0.184692E+11 0.311301E+09 0.00 1.00 01-JUL-17:42 0.89 24-JUL-06:10 8677.40 31-JUL-24:00 8614.48 31-JUL-24:00 595.60 26-JUL-15:40 2389.97 26-JUL-16:00 0.00 01-JUL-00:05
August 0.237950E+11 0.634373E+10 744.00 0.234714E+11 0.323615E+09 0.00 1.00 01-AUG-00:10 0.52 31-AUG-24:00 10140.29 04-AUG-16:00 9746.19 29-AUG-17:40 634.00 04-AUG-13:00 3319.43 04-AUG-16:00 0.00 01-AUG-00:10
September 0.751511E+10 0.228373E+10 720.00 0.745684E+10 58267402.49 0.00 0.67 30-SEP-23:51 0.29 30-SEP-07:00 4203.39 30-SEP-23:51 4203.39 30-SEP-23:51 260.01 11-SEP-10:40 1340.10 06-SEP-15:20 0.00 01-SEP-00:10
October 0.116843E+11 0.329108E+10 744.00 0.116785E+11 5872912.17 0.00 0.90 31-OCT-23:57 0.56 23-OCT-06:01 6090.18 31-OCT-23:52 6090.18 31-OCT-23:52 154.36 02-OCT-14:00 1597.13 31-OCT-23:52 0.00 01-OCT-00:01
November 0.152345E+11 0.402959E+10 714.67 0.152251E+11 9339870.11 0.00 1.00 03-NOV-15:53 0.00 26-NOV-02:51 13741.04 26-NOV-08:11 13741.04 26-NOV-08:11 133.87 08-NOV-11:00 3699.87 26-NOV-08:11 0.00 01-NOV-00:01
December 0.198902E+11 0.509560E+10 744.00 0.198902E+11 -0.0 0.00 1.00 01-DEC-00:01 0.89 11-DEC-07:02 8700.57 01-DEC-16:08 8700.57 01-DEC-16:08 0.00 03-DEC-18:35 2264.82 01-DEC-16:10 0.00 01-DEC-00:01
                                         
Annual Sum or Average 0.165404E+12 0.449070E+11 8612.43 0.164370E+12 0.103398E+10 0.00                            
Minimum of Months 0.344206E+10 0.108602E+10 590.17 0.344206E+10 -0.0 0.00 0.67   0.00   4203.39   4203.39   0.00   1340.10   0.00  
Maximum of Months 0.237950E+11 0.634373E+10 744.00 0.234714E+11 0.323615E+09 0.00 1.00   0.89   13741.04   13741.04   634.00   3699.87   0.00  



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.137109E+11 0.377815E+10 495.47 0.137109E+11 0.00 0.00 0.49 19-JAN-12:02 0.00 01-JAN-00:02 28259.09 19-JAN-12:02 28259.09 19-JAN-12:02 0.00 13-JAN-17:00 7181.45 19-JAN-12:02 0.00 01-JAN-00:02
February 0.584684E+11 0.148424E+11 590.17 0.584684E+11 -0.0 0.00 1.00 04-FEB-10:31 0.00 01-FEB-00:41 124749.76 04-FEB-10:31 124749.76 04-FEB-10:31 0.00 08-FEB-15:54 28666.72 04-FEB-10:31 0.00 01-FEB-00:01
March 0.137715E+12 0.318510E+11 744.00 0.137713E+12 2677893.09 0.00 1.00 21-MAR-17:27 0.56 06-MAR-04:16 72721.72 31-MAR-23:12 72721.72 31-MAR-23:12 423.43 29-MAR-16:00 15981.90 31-MAR-23:12 0.00 01-MAR-00:01
April 0.193661E+12 0.429739E+11 720.00 0.193398E+12 0.263352E+09 0.00 1.00 01-APR-00:03 0.37 30-APR-24:00 92202.27 18-APR-15:40 91606.97 15-APR-18:10 3461.10 18-APR-15:50 23197.02 15-APR-17:53 0.00 01-APR-00:03
May 0.659448E+11 0.172173E+11 744.00 0.650156E+11 0.929190E+09 0.00 0.72 31-MAY-23:20 0.21 02-MAY-06:10 46230.13 31-MAY-23:20 45759.87 31-MAY-23:40 2581.15 12-MAY-16:00 11027.26 31-MAY-23:20 0.00 01-MAY-00:10
June 0.119865E+12 0.293073E+11 720.00 0.117826E+12 0.203917E+10 0.00 0.94 30-JUN-23:30 0.56 03-JUN-06:05 65168.77 30-JUN-23:02 65085.20 30-JUN-23:51 4555.49 13-JUN-15:00 15359.66 26-JUN-16:00 0.00 01-JUN-00:10
July 0.176618E+12 0.401331E+11 744.00 0.173516E+12 0.310146E+10 0.00 1.00 01-JUL-17:55 0.85 22-JUL-06:42 81417.47 31-JUL-23:50 80868.06 31-JUL-24:00 5943.80 26-JUL-15:40 19572.26 26-JUL-16:00 0.00 01-JUL-00:05
August 0.223708E+12 0.510056E+11 744.00 0.220487E+12 0.322088E+10 0.00 1.00 01-AUG-00:10 0.44 31-AUG-24:00 97185.12 04-AUG-16:00 93376.79 29-AUG-17:40 6326.81 04-AUG-13:00 27244.06 04-AUG-16:00 0.00 01-AUG-00:10
September 0.644457E+11 0.169909E+11 720.00 0.638693E+11 0.576310E+09 0.00 0.64 06-SEP-17:30 0.19 30-SEP-06:10 39444.16 06-SEP-17:30 37874.30 04-SEP-17:50 2591.70 11-SEP-10:40 10924.40 06-SEP-17:00 0.00 01-SEP-00:10
October 0.994194E+11 0.244580E+11 744.00 0.993606E+11 58792012.26 0.00 0.85 31-OCT-23:13 0.44 23-OCT-06:02 54222.79 31-OCT-23:13 54222.79 31-OCT-23:13 1533.57 02-OCT-14:00 12410.14 11-OCT-16:50 0.00 01-OCT-00:01
November 0.127347E+12 0.296646E+11 714.67 0.127253E+12 93514500.64 0.00 1.00 26-NOV-08:11 0.00 26-NOV-02:51 129138.08 26-NOV-08:11 129138.08 26-NOV-08:11 1328.87 08-NOV-11:00 29698.32 26-NOV-08:11 0.00 01-NOV-00:01
December 0.167225E+12 0.370855E+11 744.00 0.167225E+12 -0.0 0.00 1.00 01-DEC-09:15 0.77 11-DEC-07:02 80742.34 01-DEC-16:08 80742.34 01-DEC-16:08 0.00 13-DEC-14:13 17949.74 01-DEC-16:10 0.00 01-DEC-00:01
                                         
Annual Sum or Average 0.144813E+13 0.339308E+12 8424.30 0.143784E+13 0.102854E+11 0.00                            
Minimum of Months 0.137109E+11 0.377815E+10 495.47 0.137109E+11 -0.0 0.00 0.49   0.00   28259.09   28259.09   0.00   7181.45   0.00  
Maximum of Months 0.223708E+12 0.510056E+11 744.00 0.220487E+12 0.322088E+10 0.00 1.00   0.85   129138.08   129138.08   6326.81   29698.32   0.00  



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.655072E+09 0.211784E+09 278.17 0.655072E+09 0.00 0.00 0.42 12-JAN-16:30 0.00 01-JAN-00:02 2483.49 12-JAN-16:30 2483.49 12-JAN-16:30 0.00 04-JAN-16:10 753.52 12-JAN-16:30 0.00 01-JAN-00:02
February 0.429078E+10 0.129949E+10 583.22 0.429078E+10 -0.0 0.00 1.00 04-FEB-10:31 0.00 01-FEB-00:01 10507.25 04-FEB-10:31 10507.25 04-FEB-10:31 0.00 08-FEB-17:35 2779.89 04-FEB-10:31 0.00 01-FEB-00:01
March 0.120082E+11 0.333168E+10 744.00 0.120079E+11 258244.50 0.00 0.96 21-MAR-17:38 0.34 06-MAR-04:12 6655.90 23-MAR-17:00 6655.90 23-MAR-17:00 42.05 29-MAR-16:00 1726.37 23-MAR-16:56 0.00 01-MAR-00:01
April 0.180343E+11 0.470094E+10 720.00 0.180086E+11 25737058.62 0.00 1.00 03-APR-13:52 0.28 30-APR-24:00 9429.27 18-APR-15:40 9367.38 16-APR-18:00 347.29 18-APR-15:50 2745.38 15-APR-17:53 0.00 01-APR-00:03
May 0.586428E+10 0.180327E+10 743.28 0.577173E+10 92551484.83 0.00 0.69 31-MAY-23:10 0.00 02-MAY-07:21 4549.17 31-MAY-23:10 4493.98 31-MAY-23:20 262.32 30-MAY-11:00 1276.08 31-MAY-23:10 0.00 01-MAY-00:10
June 0.116630E+11 0.335772E+10 720.00 0.114590E+11 0.204088E+09 0.00 0.92 30-JUN-23:02 0.42 04-JUN-05:40 6460.26 30-JUN-23:02 6440.91 30-JUN-23:30 459.67 13-JUN-15:00 1867.82 26-JUN-16:00 0.00 01-JUN-00:10
July 0.174722E+11 0.467349E+10 744.00 0.171622E+11 0.310063E+09 0.00 1.00 01-JUL-17:55 0.77 24-JUL-06:10 8001.66 03-JUL-16:00 7859.16 31-JUL-23:50 597.75 26-JUL-15:40 2349.24 26-JUL-16:00 0.00 01-JUL-00:05
August 0.220767E+11 0.585022E+10 744.00 0.217559E+11 0.320784E+09 0.00 1.00 01-AUG-00:10 0.39 31-AUG-24:00 9970.97 04-AUG-16:00 9478.20 29-AUG-17:40 635.31 04-AUG-13:00 3261.12 04-AUG-16:00 0.00 01-AUG-00:10
September 0.555530E+10 0.173066E+10 718.90 0.549774E+10 57564480.26 0.00 0.64 06-SEP-17:00 0.00 05-SEP-04:43 4119.97 06-SEP-17:30 3916.39 01-SEP-17:40 263.71 11-SEP-10:50 1333.42 06-SEP-17:00 0.00 01-SEP-00:10
October 0.798918E+10 0.235778E+10 743.86 0.798339E+10 5787793.89 0.00 0.80 11-OCT-16:49 0.00 15-OCT-21:11 5382.91 11-OCT-16:50 5382.91 11-OCT-16:50 153.01 02-OCT-14:02 1463.32 11-OCT-16:50 0.00 01-OCT-00:01
November 0.107505E+11 0.301448E+10 714.67 0.107413E+11 9223961.15 0.00 1.00 26-NOV-08:11 0.00 26-NOV-02:51 12894.34 26-NOV-08:11 12894.34 26-NOV-08:11 132.01 08-NOV-11:00 3456.88 26-NOV-08:11 0.00 01-NOV-00:01
December 0.146601E+11 0.390797E+10 744.00 0.146601E+11 -0.0 0.00 1.00 01-DEC-13:10 0.58 11-DEC-03:31 7851.66 01-DEC-16:08 7851.66 01-DEC-16:08 0.00 28-DEC-15:35 2024.15 01-DEC-16:10 0.00 01-DEC-00:01
                                         
Annual Sum or Average 0.131020E+12 0.362395E+11 8198.10 0.129993E+12 0.102606E+10 0.00                            
Minimum of Months 0.655072E+09 0.211784E+09 278.17 0.655072E+09 -0.0 0.00 0.42   0.00   2483.49   2483.49   0.00   753.52   0.00  
Maximum of Months 0.220767E+11 0.585022E+10 744.00 0.217559E+11 0.320784E+09 0.00 1.00   0.77   12894.34   12894.34   635.31   3456.88   0.00  



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 133.97 0.00 133.97 0.00 1726.79 0.00 0.00 0.00
February 169.85 0.00 169.85 0.22 1427.89 0.00 0.00 0.00
March 254.55 0.00 254.55 27.91 953.34 0.00 0.00 0.00
April 293.87 1.45 292.42 103.68 665.66 0.00 0.00 0.00
May 383.21 14.40 368.80 264.75 343.40 0.00 0.00 0.00
June 447.88 40.65 407.23 462.46 238.50 0.00 0.00 0.00
July 420.04 28.10 391.94 459.44 198.12 0.00 0.00 0.00
August 351.70 6.23 345.46 382.15 240.30 0.00 0.00 0.00
September 269.65 0.07 269.58 211.61 430.32 0.00 0.00 0.00
October 200.49 0.00 200.49 38.67 703.93 0.00 0.00 0.00
November 140.25 0.00 140.25 4.63 1097.30 0.00 0.00 0.00
December 90.97 0.00 90.97 0.00 1542.62 0.00 0.00 0.00
                 
Annual Sum or Average 263.53 7.60 255.92 163.94 794.24 0.00 0.00 0.00
Minimum of Months 90.97 0.00 90.97 0.00 198.12 0.00 0.00 0.00
Maximum of Months 447.88 40.65 407.23 462.46 1726.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 133.97 0.00 133.97 0.00 1726.79 0.00 0.00 0.00
February 169.85 0.00 169.85 0.22 1427.89 0.00 0.00 0.00
March 254.55 0.00 254.55 27.91 953.34 0.00 0.00 0.00
April 293.86 1.45 292.42 103.68 665.66 0.00 0.00 0.00
May 383.21 14.40 368.80 264.75 343.40 0.00 0.00 0.00
June 447.88 40.65 407.23 462.46 238.50 0.00 0.00 0.00
July 420.04 28.10 391.94 459.44 198.12 0.00 0.00 0.00
August 351.70 6.23 345.46 382.15 240.30 0.00 0.00 0.00
September 269.65 0.07 269.58 211.61 430.32 0.00 0.00 0.00
October 200.49 0.00 200.49 38.66 703.93 0.00 0.00 0.00
November 140.25 0.00 140.25 4.63 1097.30 0.00 0.00 0.00
December 90.97 0.00 90.97 0.00 1542.62 0.00 0.00 0.00
                 
Annual Sum or Average 263.53 7.60 255.92 163.94 794.24 0.00 0.00 0.00
Minimum of Months 90.97 0.00 90.97 0.00 198.12 0.00 0.00 0.00
Maximum of Months 447.88 40.65 407.23 462.46 1726.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 133.97 0.00 133.97 0.00 1726.79 0.00 0.00 0.00
February 169.85 0.00 169.85 0.22 1427.89 0.00 0.00 0.00
March 254.55 0.00 254.55 27.91 953.34 0.00 0.00 0.00
April 293.87 1.45 292.42 103.68 665.66 0.00 0.00 0.00
May 383.21 14.40 368.80 264.75 343.40 0.00 0.00 0.00
June 447.88 40.65 407.23 462.46 238.50 0.00 0.00 0.00
July 420.04 28.10 391.94 459.44 198.12 0.00 0.00 0.00
August 351.70 6.23 345.46 382.15 240.30 0.00 0.00 0.00
September 269.65 0.07 269.58 211.61 430.32 0.00 0.00 0.00
October 200.49 0.00 200.49 38.67 703.93 0.00 0.00 0.00
November 140.25 0.00 140.25 4.63 1097.30 0.00 0.00 0.00
December 90.97 0.00 90.97 0.00 1542.62 0.00 0.00 0.00
                 
Annual Sum or Average 263.53 7.60 255.92 163.94 794.24 0.00 0.00 0.00
Minimum of Months 90.97 0.00 90.97 0.00 198.12 0.00 0.00 0.00
Maximum of Months 447.88 40.65 407.23 462.46 1726.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 133.97 0.00 133.97 0.00 1726.79 0.00 0.00 0.00
February 169.85 0.00 169.85 0.22 1427.89 0.00 0.00 0.00
March 254.55 0.00 254.55 27.91 953.34 0.00 0.00 0.00
April 293.86 1.45 292.42 103.68 665.66 0.00 0.00 0.00
May 383.21 14.40 368.80 264.75 343.40 0.00 0.00 0.00
June 447.88 40.65 407.23 462.46 238.50 0.00 0.00 0.00
July 420.04 28.10 391.94 459.44 198.12 0.00 0.00 0.00
August 351.70 6.23 345.46 382.15 240.30 0.00 0.00 0.00
September 269.65 0.07 269.58 211.61 430.32 0.00 0.00 0.00
October 200.49 0.00 200.49 38.66 703.93 0.00 0.00 0.00
November 140.25 0.00 140.25 4.63 1097.30 0.00 0.00 0.00
December 90.97 0.00 90.97 0.00 1542.62 0.00 0.00 0.00
                 
Annual Sum or Average 263.53 7.60 255.92 163.94 794.24 0.00 0.00 0.00
Minimum of Months 90.97 0.00 90.97 0.00 198.12 0.00 0.00 0.00
Maximum of Months 447.88 40.65 407.23 462.46 1726.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 133.97 0.00 133.97 0.00 1726.72 0.00 0.00 0.00
February 169.84 0.00 169.84 0.22 1427.83 0.00 0.00 0.00
March 254.54 0.00 254.54 27.91 953.30 0.00 0.00 0.00
April 293.85 1.45 292.41 103.68 665.63 0.00 0.00 0.00
May 383.19 14.40 368.79 264.74 343.39 0.00 0.00 0.00
June 447.86 40.65 407.21 462.44 238.49 0.00 0.00 0.00
July 420.02 28.10 391.93 459.42 198.11 0.00 0.00 0.00
August 351.68 6.23 345.45 382.13 240.29 0.00 0.00 0.00
September 269.64 0.07 269.57 211.60 430.30 0.00 0.00 0.00
October 200.48 0.00 200.48 38.66 703.90 0.00 0.00 0.00
November 140.24 0.00 140.24 4.63 1097.25 0.00 0.00 0.00
December 90.97 0.00 90.97 0.00 1542.56 0.00 0.00 0.00
                 
Annual Sum or Average 263.52 7.60 255.91 163.93 794.21 0.00 0.00 0.00
Minimum of Months 90.97 0.00 90.97 0.00 198.11 0.00 0.00 0.00
Maximum of Months 447.86 40.65 407.21 462.44 1726.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 318.97 131.26 187.71 78.50 1721.87 0.00 0.00 0.00
February 422.80 185.91 236.88 164.67 1389.07 0.00 0.00 0.00
March 574.45 228.02 346.43 331.26 937.15 0.00 0.00 0.00
April 705.37 308.90 396.47 581.38 671.53 0.00 0.00 0.00
May 885.89 387.09 498.80 903.14 365.96 0.00 0.00 0.00
June 974.90 424.55 550.34 1166.32 254.76 0.00 0.00 0.00
July 985.37 454.67 530.70 1220.28 206.27 0.00 0.00 0.00
August 830.65 358.11 472.54 1029.23 244.96 0.00 0.00 0.00
September 740.86 350.10 390.77 816.40 438.63 0.00 0.00 0.00
October 472.13 197.20 274.92 323.59 700.13 0.00 0.00 0.00
November 278.56 90.48 188.08 92.50 1113.56 0.00 0.00 0.00
December 215.78 92.66 123.12 59.15 1570.23 0.00 0.00 0.00
                 
Annual Sum or Average 618.11 267.80 350.31 566.05 798.33 0.00 0.00 0.00
Minimum of Months 215.78 90.48 123.12 59.15 206.27 0.00 0.00 0.00
Maximum of Months 985.37 454.67 550.34 1220.28 1721.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 318.97 131.26 187.71 78.50 1721.87 0.00 0.00 0.00
February 422.80 185.91 236.88 164.67 1389.07 0.00 0.00 0.00
March 574.45 228.02 346.43 331.26 937.15 0.00 0.00 0.00
April 705.37 308.90 396.47 581.38 671.53 0.00 0.00 0.00
May 885.89 387.09 498.80 903.14 365.96 0.00 0.00 0.00
June 974.90 424.55 550.34 1166.32 254.76 0.00 0.00 0.00
July 985.37 454.67 530.70 1220.28 206.27 0.00 0.00 0.00
August 830.65 358.11 472.54 1029.23 244.96 0.00 0.00 0.00
September 740.86 350.10 390.77 816.40 438.63 0.00 0.00 0.00
October 472.13 197.20 274.92 323.59 700.13 0.00 0.00 0.00
November 278.56 90.48 188.08 92.50 1113.56 0.00 0.00 0.00
December 215.78 92.66 123.12 59.15 1570.23 0.00 0.00 0.00
                 
Annual Sum or Average 618.11 267.80 350.31 566.05 798.33 0.00 0.00 0.00
Minimum of Months 215.78 90.48 123.12 59.15 206.27 0.00 0.00 0.00
Maximum of Months 985.37 454.67 550.34 1220.28 1721.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 318.97 131.26 187.71 78.50 1721.84 0.00 0.00 0.00
February 422.79 185.91 236.88 164.67 1389.04 0.00 0.00 0.00
March 574.44 228.01 346.43 331.26 937.14 0.00 0.00 0.00
April 705.36 308.90 396.46 581.37 671.52 0.00 0.00 0.00
May 885.87 387.09 498.79 903.12 365.95 0.00 0.00 0.00
June 974.88 424.54 550.33 1166.30 254.75 0.00 0.00 0.00
July 985.35 454.66 530.69 1220.26 206.27 0.00 0.00 0.00
August 830.63 358.10 472.53 1029.21 244.96 0.00 0.00 0.00
September 740.85 350.09 390.76 816.38 438.62 0.00 0.00 0.00
October 472.12 197.20 274.92 323.58 700.12 0.00 0.00 0.00
November 278.56 90.48 188.08 92.50 1113.54 0.00 0.00 0.00
December 215.77 92.66 123.11 59.15 1570.20 0.00 0.00 0.00
                 
Annual Sum or Average 618.10 267.79 350.30 566.04 798.32 0.00 0.00 0.00
Minimum of Months 215.77 90.48 123.11 59.15 206.27 0.00 0.00 0.00
Maximum of Months 985.35 454.66 550.33 1220.26 1721.84 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 833.17 570.16 263.01 592.55 1357.65 0.00 0.00 0.00
February 892.73 603.13 289.59 675.38 1109.87 0.00 0.00 0.00
March 776.87 409.08 367.80 629.93 824.89 0.00 0.00 0.00
April 699.91 327.22 372.69 677.21 631.27 0.00 0.00 0.00
May 579.85 157.21 422.65 604.37 360.72 0.00 0.00 0.00
June 562.95 114.62 448.33 686.40 250.63 0.00 0.00 0.00
July 595.92 150.16 445.76 766.60 207.85 0.00 0.00 0.00
August 671.41 240.78 430.62 884.87 250.09 0.00 0.00 0.00
September 813.60 428.70 384.90 983.42 416.40 0.00 0.00 0.00
October 849.57 532.99 316.58 841.43 620.41 0.00 0.00 0.00
November 641.00 401.28 239.72 503.66 917.64 0.00 0.00 0.00
December 683.53 517.77 165.77 549.30 1276.33 0.00 0.00 0.00
                 
Annual Sum or Average 715.67 369.77 345.91 699.65 683.26 0.00 0.00 0.00
Minimum of Months 562.95 114.62 165.77 503.66 207.85 0.00 0.00 0.00
Maximum of Months 892.73 603.13 448.33 983.42 1357.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 833.17 570.16 263.01 592.55 1357.65 0.00 0.00 0.00
February 892.73 603.13 289.59 675.38 1109.87 0.00 0.00 0.00
March 776.87 409.08 367.80 629.93 824.89 0.00 0.00 0.00
April 699.91 327.22 372.69 677.21 631.27 0.00 0.00 0.00
May 579.85 157.21 422.65 604.37 360.72 0.00 0.00 0.00
June 562.95 114.62 448.33 686.40 250.63 0.00 0.00 0.00
July 595.92 150.16 445.76 766.60 207.85 0.00 0.00 0.00
August 671.40 240.78 430.62 884.87 250.09 0.00 0.00 0.00
September 813.60 428.70 384.90 983.42 416.40 0.00 0.00 0.00
October 849.57 532.99 316.58 841.43 620.41 0.00 0.00 0.00
November 641.00 401.28 239.72 503.66 917.64 0.00 0.00 0.00
December 683.53 517.77 165.76 549.30 1276.33 0.00 0.00 0.00
                 
Annual Sum or Average 715.67 369.77 345.91 699.65 683.26 0.00 0.00 0.00
Minimum of Months 562.95 114.62 165.76 503.66 207.85 0.00 0.00 0.00
Maximum of Months 892.73 603.13 448.33 983.42 1357.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 833.17 570.16 263.01 592.55 1357.65 0.00 0.00 0.00
February 892.73 603.13 289.59 675.38 1109.87 0.00 0.00 0.00
March 776.87 409.08 367.80 629.93 824.89 0.00 0.00 0.00
April 699.91 327.22 372.69 677.21 631.27 0.00 0.00 0.00
May 579.85 157.21 422.65 604.37 360.72 0.00 0.00 0.00
June 562.95 114.62 448.33 686.40 250.63 0.00 0.00 0.00
July 595.92 150.16 445.76 766.60 207.85 0.00 0.00 0.00
August 671.41 240.78 430.62 884.87 250.09 0.00 0.00 0.00
September 813.60 428.70 384.90 983.42 416.40 0.00 0.00 0.00
October 849.57 532.99 316.58 841.43 620.41 0.00 0.00 0.00
November 641.00 401.28 239.72 503.66 917.64 0.00 0.00 0.00
December 683.53 517.77 165.77 549.30 1276.33 0.00 0.00 0.00
                 
Annual Sum or Average 715.67 369.77 345.91 699.65 683.26 0.00 0.00 0.00
Minimum of Months 562.95 114.62 165.77 503.66 207.85 0.00 0.00 0.00
Maximum of Months 892.73 603.13 448.33 983.42 1357.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 833.17 570.16 263.01 592.55 1357.65 0.00 0.00 0.00
February 892.73 603.13 289.59 675.38 1109.87 0.00 0.00 0.00
March 776.87 409.08 367.80 629.93 824.89 0.00 0.00 0.00
April 699.91 327.22 372.69 677.21 631.27 0.00 0.00 0.00
May 579.85 157.21 422.65 604.37 360.72 0.00 0.00 0.00
June 562.95 114.62 448.33 686.40 250.63 0.00 0.00 0.00
July 595.92 150.16 445.76 766.60 207.85 0.00 0.00 0.00
August 671.40 240.78 430.62 884.87 250.09 0.00 0.00 0.00
September 813.60 428.70 384.90 983.42 416.40 0.00 0.00 0.00
October 849.57 532.99 316.58 841.43 620.41 0.00 0.00 0.00
November 641.00 401.28 239.72 503.66 917.64 0.00 0.00 0.00
December 683.53 517.77 165.76 549.30 1276.33 0.00 0.00 0.00
                 
Annual Sum or Average 715.67 369.77 345.91 699.65 683.26 0.00 0.00 0.00
Minimum of Months 562.95 114.62 165.76 503.66 207.85 0.00 0.00 0.00
Maximum of Months 892.73 603.13 448.33 983.42 1357.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 833.14 570.13 263.00 592.53 1357.59 0.00 0.00 0.00
February 892.69 603.11 289.58 675.36 1109.82 0.00 0.00 0.00
March 776.84 409.06 367.78 629.91 824.86 0.00 0.00 0.00
April 699.88 327.21 372.67 677.19 631.25 0.00 0.00 0.00
May 579.83 157.20 422.63 604.35 360.71 0.00 0.00 0.00
June 562.93 114.61 448.31 686.37 250.62 0.00 0.00 0.00
July 595.90 150.15 445.75 766.57 207.84 0.00 0.00 0.00
August 671.38 240.77 430.61 884.83 250.08 0.00 0.00 0.00
September 813.57 428.68 384.88 983.38 416.38 0.00 0.00 0.00
October 849.54 532.97 316.57 841.40 620.39 0.00 0.00 0.00
November 640.97 401.26 239.71 503.64 917.61 0.00 0.00 0.00
December 683.51 517.75 165.76 549.28 1276.28 0.00 0.00 0.00
                 
Annual Sum or Average 715.64 369.75 345.89 699.62 683.24 0.00 0.00 0.00
Minimum of Months 562.93 114.61 165.76 503.64 207.84 0.00 0.00 0.00
Maximum of Months 892.69 603.11 448.31 983.38 1357.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 316.34 128.00 188.35 86.04 1828.78 0.00 0.00 0.00
February 463.86 228.58 235.28 212.75 1505.22 0.00 0.00 0.00
March 553.75 206.03 347.73 299.51 1047.37 0.00 0.00 0.00
April 807.76 399.42 408.34 718.33 790.04 0.00 0.00 0.00
May 810.10 323.61 486.48 823.84 425.90 0.00 0.00 0.00
June 950.55 411.95 538.61 1135.05 315.64 0.00 0.00 0.00
July 1020.60 484.80 535.80 1255.37 282.43 0.00 0.00 0.00
August 892.27 409.49 482.77 1096.97 333.21 0.00 0.00 0.00
September 722.26 342.82 379.44 800.03 505.21 0.00 0.00 0.00
October 503.30 223.76 279.54 374.73 789.99 0.00 0.00 0.00
November 301.26 111.41 189.85 125.17 1212.49 0.00 0.00 0.00
December 231.68 109.22 122.47 78.02 1697.61 0.00 0.00 0.00
                 
Annual Sum or Average 631.82 281.64 350.17 585.65 891.54 0.00 0.00 0.00
Minimum of Months 231.68 109.22 122.47 78.02 282.43 0.00 0.00 0.00
Maximum of Months 1020.60 484.80 538.61 1255.37 1828.78 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 316.34 128.00 188.35 86.04 1828.78 0.00 0.00 0.00
February 463.86 228.58 235.28 212.75 1505.22 0.00 0.00 0.00
March 553.75 206.03 347.73 299.51 1047.37 0.00 0.00 0.00
April 807.76 399.42 408.34 718.33 790.04 0.00 0.00 0.00
May 810.10 323.61 486.48 823.84 425.90 0.00 0.00 0.00
June 950.55 411.95 538.61 1135.05 315.64 0.00 0.00 0.00
July 1020.60 484.80 535.80 1255.37 282.43 0.00 0.00 0.00
August 892.27 409.49 482.77 1096.97 333.21 0.00 0.00 0.00
September 722.26 342.82 379.44 800.03 505.21 0.00 0.00 0.00
October 503.30 223.76 279.54 374.73 789.99 0.00 0.00 0.00
November 301.26 111.41 189.85 125.17 1212.49 0.00 0.00 0.00
December 231.68 109.22 122.47 78.02 1697.61 0.00 0.00 0.00
                 
Annual Sum or Average 631.82 281.64 350.17 585.65 891.54 0.00 0.00 0.00
Minimum of Months 231.68 109.22 122.47 78.02 282.43 0.00 0.00 0.00
Maximum of Months 1020.60 484.80 538.61 1255.37 1828.78 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 316.34 127.99 188.34 86.04 1828.75 0.00 0.00 0.00
February 463.85 228.57 235.28 212.75 1505.19 0.00 0.00 0.00
March 553.74 206.02 347.72 299.50 1047.35 0.00 0.00 0.00
April 807.75 399.42 408.33 718.32 790.03 0.00 0.00 0.00
May 810.08 323.61 486.47 823.83 425.89 0.00 0.00 0.00
June 950.54 411.94 538.60 1135.03 315.63 0.00 0.00 0.00
July 1020.59 484.79 535.79 1255.35 282.42 0.00 0.00 0.00
August 892.25 409.48 482.76 1096.95 333.21 0.00 0.00 0.00
September 722.25 342.82 379.43 800.02 505.21 0.00 0.00 0.00
October 503.29 223.76 279.53 374.72 789.98 0.00 0.00 0.00
November 301.25 111.40 189.85 125.17 1212.47 0.00 0.00 0.00
December 231.68 109.22 122.46 78.02 1697.58 0.00 0.00 0.00
                 
Annual Sum or Average 631.80 281.64 350.16 585.64 891.52 0.00 0.00 0.00
Minimum of Months 231.68 109.22 122.46 78.02 282.42 0.00 0.00 0.00
Maximum of Months 1020.59 484.79 538.60 1255.35 1828.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 669.85 0.00 669.85 0.00 8489.76 0.00 0.00 0.00
February 849.24 0.00 849.24 4.74 6933.74 0.00 0.00 0.00
March 1272.75 0.00 1272.75 171.74 4517.03 0.00 0.00 0.00
April 1469.31 7.24 1462.07 593.98 3050.00 0.00 0.00 0.00
May 1916.01 72.02 1843.99 1428.98 1571.84 0.00 0.00 0.00
June 2239.37 203.25 2036.12 2402.14 1085.45 0.00 0.00 0.00
July 2100.18 140.48 1959.70 2408.77 890.17 0.00 0.00 0.00
August 1758.47 31.16 1727.30 2029.55 1052.81 0.00 0.00 0.00
September 1348.24 0.33 1347.90 1153.10 1938.14 0.00 0.00 0.00
October 1002.44 0.00 1002.44 263.62 3161.69 0.00 0.00 0.00
November 701.22 0.00 701.22 42.57 5070.10 0.00 0.00 0.00
December 454.85 0.00 454.85 0.00 7365.47 0.00 0.00 0.00
                 
Annual Sum or Average 1317.63 38.02 1279.60 880.19 3745.12 0.00 0.00 0.00
Minimum of Months 454.85 0.00 454.85 0.00 890.17 0.00 0.00 0.00
Maximum of Months 2239.37 203.25 2036.12 2408.77 8489.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 956.91 393.77 563.14 234.57 5049.03 0.00 0.00 0.00
February 1268.37 557.73 710.64 496.98 4033.38 0.00 0.00 0.00
March 1723.33 684.04 1039.29 992.22 2705.00 0.00 0.00 0.00
April 2116.09 926.70 1189.38 1726.78 1921.92 0.00 0.00 0.00
May 2657.64 1161.27 1496.37 2666.63 1056.01 0.00 0.00 0.00
June 2924.66 1273.64 1651.02 3463.62 734.95 0.00 0.00 0.00
July 2956.08 1364.00 1592.08 3624.01 600.66 0.00 0.00 0.00
August 2491.92 1074.32 1417.60 3065.52 705.84 0.00 0.00 0.00
September 2222.57 1050.28 1172.29 2437.27 1246.18 0.00 0.00 0.00
October 1416.37 591.61 824.77 988.03 1954.14 0.00 0.00 0.00
November 835.67 271.44 564.23 290.75 3137.61 0.00 0.00 0.00
December 647.32 277.98 369.35 185.89 4498.79 0.00 0.00 0.00
                 
Annual Sum or Average 1854.30 803.38 1050.92 1687.48 2295.36 0.00 0.00 0.00
Minimum of Months 647.32 271.44 369.35 185.89 600.66 0.00 0.00 0.00
Maximum of Months 2956.08 1364.00 1651.02 3624.01 5049.03 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 4165.81 2850.75 1315.05 2919.06 6762.48 0.00 0.00 0.00
February 4463.59 3015.63 1447.95 3323.03 5510.02 0.00 0.00 0.00
March 3884.32 2045.36 1838.97 3106.84 4054.84 0.00 0.00 0.00
April 3499.51 1636.09 1863.42 3354.26 3057.32 0.00 0.00 0.00
May 2899.23 786.02 2113.21 3011.62 1746.31 0.00 0.00 0.00
June 2814.71 573.09 2241.62 3441.96 1191.42 0.00 0.00 0.00
July 2979.57 750.77 2228.80 3849.53 979.80 0.00 0.00 0.00
August 3356.99 1203.90 2153.09 4431.09 1174.61 0.00 0.00 0.00
September 4067.96 2143.48 1924.48 4883.54 2018.34 0.00 0.00 0.00
October 4247.81 2664.90 1582.90 4170.79 3014.52 0.00 0.00 0.00
November 3204.96 2006.37 1198.59 2510.51 4458.04 0.00 0.00 0.00
December 3417.63 2588.81 828.82 2741.12 6246.33 0.00 0.00 0.00
                 
Annual Sum or Average 3578.32 1848.81 1729.51 3479.14 3340.77 0.00 0.00 0.00
Minimum of Months 2814.71 573.09 828.82 2510.51 979.80 0.00 0.00 0.00
Maximum of Months 4463.59 3015.63 2241.62 4883.54 6762.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 949.02 383.98 565.03 261.92 5279.20 0.00 0.00 0.00
February 1391.56 685.72 705.84 648.07 4295.95 0.00 0.00 0.00
March 1661.24 618.07 1043.17 934.06 2870.22 0.00 0.00 0.00
April 2423.26 1198.26 1225.00 2199.93 2084.19 0.00 0.00 0.00
May 2430.27 970.83 1459.43 2511.78 1173.36 0.00 0.00 0.00
June 2851.63 1235.83 1615.80 3449.75 843.36 0.00 0.00 0.00
July 3061.78 1454.40 1607.39 3837.27 733.07 0.00 0.00 0.00
August 2676.77 1228.46 1448.31 3386.40 826.92 0.00 0.00 0.00
September 2166.77 1028.46 1138.31 2442.37 1372.00 0.00 0.00 0.00
October 1509.89 671.28 838.61 1170.01 2114.79 0.00 0.00 0.00
November 903.77 334.21 569.56 406.20 3269.19 0.00 0.00 0.00
December 695.05 327.66 367.39 253.53 4687.15 0.00 0.00 0.00
                 
Annual Sum or Average 1895.43 844.93 1050.50 1797.53 2453.63 0.00 0.00 0.00
Minimum of Months 695.05 327.66 367.39 253.53 733.07 0.00 0.00 0.00
Maximum of Months 3061.78 1454.40 1615.80 3837.27 5279.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 669.85 0.00 669.85 0.00 8368.10 0.00 0.00 0.00
February 849.24 0.00 849.24 6.99 6765.90 0.00 0.00 0.00
March 1272.75 0.00 1272.75 190.65 4306.86 0.00 0.00 0.00
April 1469.31 7.24 1462.07 617.42 2841.01 0.00 0.00 0.00
May 1916.01 72.02 1843.99 1486.31 1435.57 0.00 0.00 0.00
June 2239.37 203.25 2036.12 2449.16 993.02 0.00 0.00 0.00
July 2100.18 140.48 1959.70 2457.34 818.34 0.00 0.00 0.00
August 1758.47 31.16 1727.30 2079.28 960.58 0.00 0.00 0.00
September 1348.24 0.33 1347.90 1201.09 1762.29 0.00 0.00 0.00
October 1002.44 0.00 1002.44 313.28 2847.28 0.00 0.00 0.00
November 701.22 0.00 701.22 55.52 4825.88 0.00 0.00 0.00
December 454.85 0.00 454.85 0.00 7191.46 0.00 0.00 0.00
                 
Annual Sum or Average 1317.63 38.02 1279.60 910.20 3577.77 0.00 0.00 0.00
Minimum of Months 454.85 0.00 454.85 0.00 818.34 0.00 0.00 0.00
Maximum of Months 2239.37 203.25 2036.12 2457.34 8368.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 956.91 393.77 563.14 237.65 4999.23 0.00 0.00 0.00
February 1268.37 557.73 710.64 508.27 3931.09 0.00 0.00 0.00
March 1723.33 684.04 1039.29 1032.83 2564.02 0.00 0.00 0.00
April 2116.09 926.70 1189.38 1765.16 1786.05 0.00 0.00 0.00
May 2657.64 1161.27 1496.37 2718.87 971.57 0.00 0.00 0.00
June 2924.66 1273.64 1651.02 3481.90 679.50 0.00 0.00 0.00
July 2956.08 1364.00 1592.08 3637.80 561.52 0.00 0.00 0.00
August 2491.92 1074.32 1417.60 3090.70 654.20 0.00 0.00 0.00
September 2222.57 1050.28 1172.29 2483.64 1135.24 0.00 0.00 0.00
October 1416.37 591.61 824.77 1068.52 1743.30 0.00 0.00 0.00
November 835.67 271.44 564.23 318.22 2980.86 0.00 0.00 0.00
December 647.32 277.98 369.35 192.59 4410.53 0.00 0.00 0.00
                 
Annual Sum or Average 1854.30 803.38 1050.92 1717.94 2193.30 0.00 0.00 0.00
Minimum of Months 647.32 271.44 369.35 192.59 561.52 0.00 0.00 0.00
Maximum of Months 2956.08 1364.00 1651.02 3637.80 4999.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 4165.81 2850.75 1315.05 2943.43 6620.89 0.00 0.00 0.00
February 4463.59 3015.63 1447.95 3367.17 5303.71 0.00 0.00 0.00
March 3884.32 2045.36 1838.97 3148.79 3828.40 0.00 0.00 0.00
April 3499.51 1636.09 1863.42 3375.87 2837.56 0.00 0.00 0.00
May 2899.23 786.02 2113.21 3056.11 1596.42 0.00 0.00 0.00
June 2814.71 573.09 2241.62 3464.42 1091.23 0.00 0.00 0.00
July 2979.57 750.77 2228.80 3872.66 902.25 0.00 0.00 0.00
August 3356.99 1203.90 2153.09 4454.36 1078.48 0.00 0.00 0.00
September 4067.96 2143.48 1924.48 4922.12 1841.62 0.00 0.00 0.00
October 4247.81 2664.90 1582.90 4254.86 2708.51 0.00 0.00 0.00
November 3204.96 2006.37 1198.59 2575.24 4203.43 0.00 0.00 0.00
December 3417.63 2588.81 828.82 2780.22 6044.79 0.00 0.00 0.00
                 
Annual Sum or Average 3578.32 1848.81 1729.51 3518.45 3161.34 0.00 0.00 0.00
Minimum of Months 2814.71 573.09 828.82 2575.24 902.25 0.00 0.00 0.00
Maximum of Months 4463.59 3015.63 2241.62 4922.12 6620.89 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 949.02 383.98 565.03 261.16 5201.62 0.00 0.00 0.00
February 1391.56 685.72 705.84 650.45 4190.12 0.00 0.00 0.00
March 1661.24 618.07 1043.17 940.03 2746.52 0.00 0.00 0.00
April 2423.26 1198.26 1225.00 2196.31 1960.55 0.00 0.00 0.00
May 2430.27 970.83 1459.43 2514.72 1096.85 0.00 0.00 0.00
June 2851.63 1235.83 1615.80 3441.24 795.86 0.00 0.00 0.00
July 3061.78 1454.40 1607.39 3828.23 696.81 0.00 0.00 0.00
August 2676.77 1228.46 1448.31 3383.02 781.48 0.00 0.00 0.00
September 2166.77 1028.46 1138.31 2448.99 1280.44 0.00 0.00 0.00
October 1509.89 671.28 838.61 1190.75 1940.74 0.00 0.00 0.00
November 903.77 334.21 569.56 416.09 3129.78 0.00 0.00 0.00
December 695.05 327.66 367.39 256.24 4582.44 0.00 0.00 0.00
                 
Annual Sum or Average 1895.43 844.93 1050.50 1799.70 2358.25 0.00 0.00 0.00
Minimum of Months 695.05 327.66 367.39 256.24 696.81 0.00 0.00 0.00
Maximum of Months 3061.78 1454.40 1615.80 3828.23 5201.62 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.358831E+09 0.00 0.358831E+09 0.00 0.462502E+10
February 0.410903E+09 0.00 0.410903E+09 528942.77 0.345435E+10
March 0.681797E+09 0.00 0.681797E+09 74755236.65 0.255342E+10
April 0.761698E+09 3752853.26 0.757946E+09 0.268750E+09 0.172539E+10
May 0.102638E+10 38579183.16 0.987799E+09 0.709098E+09 0.919773E+09
June 0.116090E+10 0.105367E+09 0.105554E+10 0.119871E+10 0.618198E+09
July 0.112504E+10 75252695.95 0.104979E+10 0.123056E+10 0.530642E+09
August 0.941986E+09 16694634.24 0.925292E+09 0.102355E+10 0.643628E+09
September 0.698936E+09 173304.80 0.698762E+09 0.548502E+09 0.111539E+10
October 0.536994E+09 0.00 0.536994E+09 0.103560E+09 0.188541E+10
November 0.363516E+09 0.00 0.363516E+09 11996884.78 0.284419E+10
December 0.243658E+09 0.00 0.243658E+09 0.00 0.413175E+10
           
Annual Sum or Average 0.831064E+10 0.239820E+09 0.807082E+10 0.517000E+10 0.250472E+11
Minimum of Months 0.243658E+09 0.00 0.243658E+09 0.00 0.530642E+09
Maximum of Months 0.116090E+10 0.105367E+09 0.105554E+10 0.123056E+10 0.462502E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.358831E+09 0.00 0.358831E+09 0.00 0.462502E+10
February 0.410902E+09 0.00 0.410902E+09 528935.05 0.345436E+10
March 0.681797E+09 0.00 0.681797E+09 74755031.55 0.255342E+10
April 0.761698E+09 3752848.76 0.757945E+09 0.268749E+09 0.172539E+10
May 0.102638E+10 38579136.87 0.987798E+09 0.709097E+09 0.919773E+09
June 0.116090E+10 0.105367E+09 0.105554E+10 0.119870E+10 0.618198E+09
July 0.112504E+10 75252605.65 0.104978E+10 0.123055E+10 0.530642E+09
August 0.941986E+09 16694614.21 0.925291E+09 0.102355E+10 0.643627E+09
September 0.698935E+09 173304.59 0.698762E+09 0.548501E+09 0.111539E+10
October 0.536994E+09 0.00 0.536994E+09 0.103560E+09 0.188541E+10
November 0.363515E+09 0.00 0.363515E+09 11996836.04 0.284419E+10
December 0.243658E+09 0.00 0.243658E+09 0.00 0.413175E+10
           
Annual Sum or Average 0.831063E+10 0.239820E+09 0.807081E+10 0.517000E+10 0.250472E+11
Minimum of Months 0.243658E+09 0.00 0.243658E+09 0.00 0.530642E+09
Maximum of Months 0.116090E+10 0.105367E+09 0.105554E+10 0.123055E+10 0.462502E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.358831E+09 0.00 0.358831E+09 0.00 0.462502E+10
February 0.410903E+09 0.00 0.410903E+09 528942.77 0.345435E+10
March 0.681797E+09 0.00 0.681797E+09 74755236.65 0.255342E+10
April 0.761698E+09 3752853.26 0.757946E+09 0.268750E+09 0.172539E+10
May 0.102638E+10 38579183.16 0.987799E+09 0.709098E+09 0.919773E+09
June 0.116090E+10 0.105367E+09 0.105554E+10 0.119871E+10 0.618198E+09
July 0.112504E+10 75252695.95 0.104979E+10 0.123056E+10 0.530642E+09
August 0.941986E+09 16694634.24 0.925292E+09 0.102355E+10 0.643628E+09
September 0.698936E+09 173304.80 0.698762E+09 0.548502E+09 0.111539E+10
October 0.536994E+09 0.00 0.536994E+09 0.103560E+09 0.188541E+10
November 0.363516E+09 0.00 0.363516E+09 11996884.78 0.284419E+10
December 0.243658E+09 0.00 0.243658E+09 0.00 0.413175E+10
           
Annual Sum or Average 0.831064E+10 0.239820E+09 0.807082E+10 0.517000E+10 0.250472E+11
Minimum of Months 0.243658E+09 0.00 0.243658E+09 0.00 0.530642E+09
Maximum of Months 0.116090E+10 0.105367E+09 0.105554E+10 0.123056E+10 0.462502E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.358831E+09 0.00 0.358831E+09 0.00 0.462502E+10
February 0.410902E+09 0.00 0.410902E+09 528935.05 0.345436E+10
March 0.681797E+09 0.00 0.681797E+09 74755031.55 0.255342E+10
April 0.761698E+09 3752848.76 0.757945E+09 0.268749E+09 0.172539E+10
May 0.102638E+10 38579136.87 0.987798E+09 0.709097E+09 0.919773E+09
June 0.116090E+10 0.105367E+09 0.105554E+10 0.119870E+10 0.618198E+09
July 0.112504E+10 75252605.65 0.104978E+10 0.123055E+10 0.530642E+09
August 0.941986E+09 16694614.21 0.925291E+09 0.102355E+10 0.643627E+09
September 0.698935E+09 173304.59 0.698762E+09 0.548501E+09 0.111539E+10
October 0.536994E+09 0.00 0.536994E+09 0.103560E+09 0.188541E+10
November 0.363515E+09 0.00 0.363515E+09 11996836.04 0.284419E+10
December 0.243658E+09 0.00 0.243658E+09 0.00 0.413175E+10
           
Annual Sum or Average 0.831063E+10 0.239820E+09 0.807081E+10 0.517000E+10 0.250472E+11
Minimum of Months 0.243658E+09 0.00 0.243658E+09 0.00 0.530642E+09
Maximum of Months 0.116090E+10 0.105367E+09 0.105554E+10 0.123055E+10 0.462502E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.358817E+09 0.00 0.358817E+09 0.00 0.462484E+10
February 0.410886E+09 0.00 0.410886E+09 528921.45 0.345422E+10
March 0.681770E+09 0.00 0.681770E+09 74752223.68 0.255331E+10
April 0.761668E+09 3752702.01 0.757915E+09 0.268739E+09 0.172532E+10
May 0.102634E+10 38577628.25 0.987759E+09 0.709069E+09 0.919735E+09
June 0.116086E+10 0.105363E+09 0.105549E+10 0.119866E+10 0.618173E+09
July 0.112499E+10 75249662.93 0.104974E+10 0.123051E+10 0.530621E+09
August 0.941948E+09 16693961.37 0.925255E+09 0.102351E+10 0.643602E+09
September 0.698907E+09 173297.81 0.698734E+09 0.548480E+09 0.111535E+10
October 0.536972E+09 0.00 0.536972E+09 0.103556E+09 0.188533E+10
November 0.363501E+09 0.00 0.363501E+09 11996401.26 0.284408E+10
December 0.243648E+09 0.00 0.243648E+09 0.00 0.413158E+10
           
Annual Sum or Average 0.831031E+10 0.239810E+09 0.807050E+10 0.516979E+10 0.250462E+11
Minimum of Months 0.243648E+09 0.00 0.243648E+09 0.00 0.530621E+09
Maximum of Months 0.116086E+10 0.105363E+09 0.105549E+10 0.123051E+10 0.462484E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.854335E+09 0.351561E+09 0.502773E+09 0.210251E+09 0.461186E+10
February 0.102283E+10 0.449758E+09 0.573070E+09 0.398372E+09 0.336043E+10
March 0.153861E+10 0.610719E+09 0.927888E+09 0.887259E+09 0.251008E+10
April 0.182832E+10 0.800680E+09 0.102764E+10 0.150693E+10 0.174061E+10
May 0.237276E+10 0.103679E+10 0.133597E+10 0.241896E+10 0.980177E+09
June 0.252693E+10 0.110044E+10 0.142649E+10 0.302309E+10 0.660333E+09
July 0.263922E+10 0.121779E+10 0.142142E+10 0.326840E+10 0.552482E+09
August 0.222481E+10 0.959165E+09 0.126564E+10 0.275669E+10 0.656111E+09
September 0.192032E+10 0.907451E+09 0.101287E+10 0.211611E+10 0.113692E+10
October 0.126455E+10 0.528194E+09 0.736358E+09 0.866699E+09 0.187524E+10
November 0.722029E+09 0.234529E+09 0.487501E+09 0.239767E+09 0.288634E+10
December 0.577933E+09 0.248179E+09 0.329755E+09 0.158418E+09 0.420571E+10
           
Annual Sum or Average 0.194926E+11 0.844526E+10 0.110474E+11 0.178510E+11 0.251763E+11
Minimum of Months 0.577933E+09 0.234529E+09 0.329755E+09 0.158418E+09 0.552482E+09
Maximum of Months 0.263922E+10 0.121779E+10 0.142649E+10 0.326840E+10 0.461186E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.854335E+09 0.351561E+09 0.502773E+09 0.210251E+09 0.461186E+10
February 0.102283E+10 0.449758E+09 0.573070E+09 0.398372E+09 0.336043E+10
March 0.153861E+10 0.610719E+09 0.927888E+09 0.887259E+09 0.251008E+10
April 0.182832E+10 0.800680E+09 0.102764E+10 0.150693E+10 0.174061E+10
May 0.237276E+10 0.103679E+10 0.133597E+10 0.241896E+10 0.980177E+09
June 0.252693E+10 0.110044E+10 0.142649E+10 0.302309E+10 0.660333E+09
July 0.263922E+10 0.121779E+10 0.142142E+10 0.326840E+10 0.552482E+09
August 0.222481E+10 0.959165E+09 0.126564E+10 0.275669E+10 0.656111E+09
September 0.192032E+10 0.907451E+09 0.101287E+10 0.211611E+10 0.113692E+10
October 0.126455E+10 0.528194E+09 0.736358E+09 0.866699E+09 0.187524E+10
November 0.722029E+09 0.234529E+09 0.487501E+09 0.239767E+09 0.288634E+10
December 0.577933E+09 0.248179E+09 0.329755E+09 0.158418E+09 0.420571E+10
           
Annual Sum or Average 0.194926E+11 0.844526E+10 0.110474E+11 0.178510E+11 0.251763E+11
Minimum of Months 0.577933E+09 0.234529E+09 0.329755E+09 0.158418E+09 0.552482E+09
Maximum of Months 0.263922E+10 0.121779E+10 0.142649E+10 0.326840E+10 0.461186E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.854319E+09 0.351555E+09 0.502764E+09 0.210247E+09 0.461178E+10
February 0.102281E+10 0.449750E+09 0.573059E+09 0.398364E+09 0.336037E+10
March 0.153858E+10 0.610708E+09 0.927871E+09 0.887243E+09 0.251003E+10
April 0.182829E+10 0.800665E+09 0.102762E+10 0.150690E+10 0.174058E+10
May 0.237272E+10 0.103677E+10 0.133595E+10 0.241892E+10 0.980159E+09
June 0.252688E+10 0.110042E+10 0.142647E+10 0.302304E+10 0.660321E+09
July 0.263917E+10 0.121777E+10 0.142140E+10 0.326834E+10 0.552472E+09
August 0.222477E+10 0.959147E+09 0.126562E+10 0.275664E+10 0.656099E+09
September 0.192028E+10 0.907434E+09 0.101285E+10 0.211607E+10 0.113690E+10
October 0.126453E+10 0.528184E+09 0.736345E+09 0.866683E+09 0.187521E+10
November 0.722016E+09 0.234524E+09 0.487492E+09 0.239762E+09 0.288629E+10
December 0.577923E+09 0.248174E+09 0.329749E+09 0.158415E+09 0.420564E+10
           
Annual Sum or Average 0.194923E+11 0.844510E+10 0.110472E+11 0.178506E+11 0.251758E+11
Minimum of Months 0.577923E+09 0.234524E+09 0.329749E+09 0.158415E+09 0.552472E+09
Maximum of Months 0.263917E+10 0.121777E+10 0.142647E+10 0.326834E+10 0.461178E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223157E+10 0.152711E+10 0.704457E+09 0.158709E+10 0.363632E+10
February 0.215969E+10 0.145910E+10 0.700585E+09 0.163389E+10 0.268500E+10
March 0.208078E+10 0.109567E+10 0.985109E+09 0.168721E+10 0.220940E+10
April 0.181417E+10 0.848161E+09 0.966010E+09 0.175533E+10 0.163626E+10
May 0.155308E+10 0.421061E+09 0.113202E+10 0.161875E+10 0.966164E+09
June 0.145916E+10 0.297094E+09 0.116207E+10 0.177915E+10 0.649622E+09
July 0.159612E+10 0.402179E+09 0.119394E+10 0.205326E+10 0.556694E+09
August 0.179829E+10 0.644911E+09 0.115338E+10 0.237003E+10 0.669843E+09
September 0.210886E+10 0.111119E+10 0.997662E+09 0.254903E+10 0.107931E+10
October 0.227549E+10 0.142755E+10 0.847940E+09 0.225370E+10 0.166171E+10
November 0.166147E+10 0.104011E+10 0.621359E+09 0.130549E+10 0.237853E+10
December 0.183078E+10 0.138679E+10 0.443985E+09 0.147125E+10 0.341852E+10
           
Annual Sum or Average 0.225694E+11 0.116609E+11 0.109085E+11 0.220642E+11 0.215474E+11
Minimum of Months 0.145916E+10 0.297094E+09 0.443985E+09 0.130549E+10 0.556694E+09
Maximum of Months 0.227549E+10 0.152711E+10 0.119394E+10 0.254903E+10 0.363632E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223156E+10 0.152711E+10 0.704456E+09 0.158708E+10 0.363632E+10
February 0.215969E+10 0.145910E+10 0.700585E+09 0.163388E+10 0.268500E+10
March 0.208078E+10 0.109567E+10 0.985108E+09 0.168721E+10 0.220940E+10
April 0.181417E+10 0.848159E+09 0.966009E+09 0.175533E+10 0.163626E+10
May 0.155308E+10 0.421060E+09 0.113202E+10 0.161875E+10 0.966164E+09
June 0.145916E+10 0.297094E+09 0.116207E+10 0.177915E+10 0.649622E+09
July 0.159611E+10 0.402179E+09 0.119394E+10 0.205326E+10 0.556694E+09
August 0.179829E+10 0.644910E+09 0.115338E+10 0.237003E+10 0.669843E+09
September 0.210885E+10 0.111119E+10 0.997661E+09 0.254903E+10 0.107931E+10
October 0.227549E+10 0.142755E+10 0.847940E+09 0.225369E+10 0.166171E+10
November 0.166147E+10 0.104011E+10 0.621359E+09 0.130549E+10 0.237853E+10
December 0.183077E+10 0.138679E+10 0.443985E+09 0.147124E+10 0.341852E+10
           
Annual Sum or Average 0.225694E+11 0.116609E+11 0.109085E+11 0.220641E+11 0.215474E+11
Minimum of Months 0.145916E+10 0.297094E+09 0.443985E+09 0.130549E+10 0.556694E+09
Maximum of Months 0.227549E+10 0.152711E+10 0.119394E+10 0.254903E+10 0.363632E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223157E+10 0.152711E+10 0.704457E+09 0.158709E+10 0.363632E+10
February 0.215969E+10 0.145910E+10 0.700585E+09 0.163389E+10 0.268500E+10
March 0.208078E+10 0.109567E+10 0.985109E+09 0.168721E+10 0.220940E+10
April 0.181417E+10 0.848161E+09 0.966010E+09 0.175533E+10 0.163626E+10
May 0.155308E+10 0.421061E+09 0.113202E+10 0.161875E+10 0.966164E+09
June 0.145916E+10 0.297094E+09 0.116207E+10 0.177915E+10 0.649622E+09
July 0.159612E+10 0.402179E+09 0.119394E+10 0.205326E+10 0.556694E+09
August 0.179829E+10 0.644911E+09 0.115338E+10 0.237003E+10 0.669843E+09
September 0.210886E+10 0.111119E+10 0.997662E+09 0.254903E+10 0.107931E+10
October 0.227549E+10 0.142755E+10 0.847940E+09 0.225370E+10 0.166171E+10
November 0.166147E+10 0.104011E+10 0.621359E+09 0.130549E+10 0.237853E+10
December 0.183078E+10 0.138679E+10 0.443985E+09 0.147125E+10 0.341852E+10
           
Annual Sum or Average 0.225694E+11 0.116609E+11 0.109085E+11 0.220642E+11 0.215474E+11
Minimum of Months 0.145916E+10 0.297094E+09 0.443985E+09 0.130549E+10 0.556694E+09
Maximum of Months 0.227549E+10 0.152711E+10 0.119394E+10 0.254903E+10 0.363632E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223156E+10 0.152711E+10 0.704456E+09 0.158708E+10 0.363632E+10
February 0.215969E+10 0.145910E+10 0.700585E+09 0.163388E+10 0.268500E+10
March 0.208078E+10 0.109567E+10 0.985108E+09 0.168721E+10 0.220940E+10
April 0.181417E+10 0.848159E+09 0.966009E+09 0.175533E+10 0.163626E+10
May 0.155308E+10 0.421060E+09 0.113202E+10 0.161875E+10 0.966164E+09
June 0.145916E+10 0.297094E+09 0.116207E+10 0.177915E+10 0.649622E+09
July 0.159611E+10 0.402179E+09 0.119394E+10 0.205326E+10 0.556694E+09
August 0.179829E+10 0.644910E+09 0.115338E+10 0.237003E+10 0.669843E+09
September 0.210885E+10 0.111119E+10 0.997661E+09 0.254903E+10 0.107931E+10
October 0.227549E+10 0.142755E+10 0.847940E+09 0.225369E+10 0.166171E+10
November 0.166147E+10 0.104011E+10 0.621359E+09 0.130549E+10 0.237853E+10
December 0.183077E+10 0.138679E+10 0.443985E+09 0.147124E+10 0.341852E+10
           
Annual Sum or Average 0.225694E+11 0.116609E+11 0.109085E+11 0.220641E+11 0.215474E+11
Minimum of Months 0.145916E+10 0.297094E+09 0.443985E+09 0.130549E+10 0.556694E+09
Maximum of Months 0.227549E+10 0.152711E+10 0.119394E+10 0.254903E+10 0.363632E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223148E+10 0.152705E+10 0.704429E+09 0.158702E+10 0.363617E+10
February 0.215960E+10 0.145904E+10 0.700557E+09 0.163382E+10 0.268489E+10
March 0.208069E+10 0.109563E+10 0.985069E+09 0.168714E+10 0.220931E+10
April 0.181410E+10 0.848126E+09 0.965971E+09 0.175526E+10 0.163619E+10
May 0.155302E+10 0.421044E+09 0.113197E+10 0.161869E+10 0.966125E+09
June 0.145910E+10 0.297082E+09 0.116202E+10 0.177908E+10 0.649596E+09
July 0.159605E+10 0.402163E+09 0.119389E+10 0.205318E+10 0.556672E+09
August 0.179822E+10 0.644885E+09 0.115333E+10 0.236993E+10 0.669816E+09
September 0.210877E+10 0.111115E+10 0.997622E+09 0.254893E+10 0.107927E+10
October 0.227540E+10 0.142749E+10 0.847906E+09 0.225361E+10 0.166165E+10
November 0.166140E+10 0.104007E+10 0.621334E+09 0.130544E+10 0.237844E+10
December 0.183070E+10 0.138674E+10 0.443967E+09 0.147119E+10 0.341838E+10
           
Annual Sum or Average 0.225685E+11 0.116605E+11 0.109081E+11 0.220633E+11 0.215465E+11
Minimum of Months 0.145910E+10 0.297082E+09 0.443967E+09 0.130544E+10 0.556672E+09
Maximum of Months 0.227540E+10 0.152705E+10 0.119389E+10 0.254893E+10 0.363617E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.847290E+09 0.342824E+09 0.504466E+09 0.230448E+09 0.489820E+10
February 0.112217E+10 0.552971E+09 0.569198E+09 0.514691E+09 0.364142E+10
March 0.148317E+10 0.551821E+09 0.931350E+09 0.802198E+09 0.280528E+10
April 0.209371E+10 0.103531E+10 0.105841E+10 0.186192E+10 0.204779E+10
May 0.216976E+10 0.866769E+09 0.130299E+10 0.220658E+10 0.114072E+10
June 0.246383E+10 0.106776E+10 0.139607E+10 0.294204E+10 0.818139E+09
July 0.273359E+10 0.129850E+10 0.143509E+10 0.336238E+10 0.756450E+09
August 0.238984E+10 0.109678E+10 0.129306E+10 0.293812E+10 0.892479E+09
September 0.187211E+10 0.888598E+09 0.983509E+09 0.207368E+10 0.130952E+10
October 0.134805E+10 0.599327E+09 0.748720E+09 0.100367E+10 0.211591E+10
November 0.780866E+09 0.288764E+09 0.492102E+09 0.324434E+09 0.314278E+10
December 0.620544E+09 0.292533E+09 0.328011E+09 0.208978E+09 0.454687E+10
           
Annual Sum or Average 0.199249E+11 0.888196E+10 0.110430E+11 0.184691E+11 0.281156E+11
Minimum of Months 0.620544E+09 0.288764E+09 0.328011E+09 0.208978E+09 0.756450E+09
Maximum of Months 0.273359E+10 0.129850E+10 0.143509E+10 0.336238E+10 0.489820E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.847290E+09 0.342824E+09 0.504466E+09 0.230448E+09 0.489820E+10
February 0.112217E+10 0.552971E+09 0.569198E+09 0.514691E+09 0.364142E+10
March 0.148317E+10 0.551821E+09 0.931350E+09 0.802198E+09 0.280528E+10
April 0.209371E+10 0.103531E+10 0.105841E+10 0.186192E+10 0.204779E+10
May 0.216976E+10 0.866769E+09 0.130299E+10 0.220658E+10 0.114072E+10
June 0.246383E+10 0.106776E+10 0.139607E+10 0.294204E+10 0.818139E+09
July 0.273359E+10 0.129850E+10 0.143509E+10 0.336238E+10 0.756450E+09
August 0.238984E+10 0.109678E+10 0.129306E+10 0.293812E+10 0.892479E+09
September 0.187211E+10 0.888598E+09 0.983509E+09 0.207368E+10 0.130952E+10
October 0.134805E+10 0.599327E+09 0.748720E+09 0.100367E+10 0.211591E+10
November 0.780866E+09 0.288764E+09 0.492102E+09 0.324434E+09 0.314278E+10
December 0.620544E+09 0.292533E+09 0.328011E+09 0.208978E+09 0.454687E+10
           
Annual Sum or Average 0.199249E+11 0.888196E+10 0.110430E+11 0.184691E+11 0.281156E+11
Minimum of Months 0.620544E+09 0.288764E+09 0.328011E+09 0.208978E+09 0.756450E+09
Maximum of Months 0.273359E+10 0.129850E+10 0.143509E+10 0.336238E+10 0.489820E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.847275E+09 0.342818E+09 0.504457E+09 0.230444E+09 0.489811E+10
February 0.112215E+10 0.552961E+09 0.569187E+09 0.514681E+09 0.364136E+10
March 0.148314E+10 0.551811E+09 0.931333E+09 0.802184E+09 0.280523E+10
April 0.209368E+10 0.103529E+10 0.105839E+10 0.186189E+10 0.204775E+10
May 0.216972E+10 0.866753E+09 0.130297E+10 0.220654E+10 0.114070E+10
June 0.246379E+10 0.106775E+10 0.139604E+10 0.294199E+10 0.818124E+09
July 0.273354E+10 0.129847E+10 0.143506E+10 0.336232E+10 0.756436E+09
August 0.238980E+10 0.109676E+10 0.129304E+10 0.293806E+10 0.892463E+09
September 0.187207E+10 0.888582E+09 0.983491E+09 0.207364E+10 0.130949E+10
October 0.134802E+10 0.599316E+09 0.748706E+09 0.100365E+10 0.211587E+10
November 0.780852E+09 0.288758E+09 0.492093E+09 0.324429E+09 0.314272E+10
December 0.620533E+09 0.292528E+09 0.328005E+09 0.208975E+09 0.454679E+10
           
Annual Sum or Average 0.199246E+11 0.888179E+10 0.110428E+11 0.184688E+11 0.281150E+11
Minimum of Months 0.620533E+09 0.288758E+09 0.328005E+09 0.208975E+09 0.756436E+09
Maximum of Months 0.273354E+10 0.129847E+10 0.143506E+10 0.336232E+10 0.489811E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.179414E+10 0.00 0.179414E+10 0.00 0.227390E+11
February 0.205449E+10 0.00 0.205449E+10 11461168.83 0.167741E+11
March 0.340895E+10 0.00 0.340895E+10 0.459985E+09 0.120984E+11
April 0.380845E+10 18764039.42 0.378968E+10 0.153959E+10 0.790559E+10
May 0.513183E+10 0.192894E+09 0.493893E+10 0.382737E+10 0.421002E+10
June 0.580445E+10 0.526829E+09 0.527762E+10 0.622634E+10 0.281348E+10
July 0.562512E+10 0.376259E+09 0.524886E+10 0.645164E+10 0.238422E+10
August 0.470988E+10 83472161.85 0.462640E+10 0.543594E+10 0.281985E+10
September 0.349464E+10 866513.52 0.349377E+10 0.298885E+10 0.502367E+10
October 0.268494E+10 0.00 0.268494E+10 0.706085E+09 0.846827E+10
November 0.181756E+10 0.00 0.181756E+10 0.110334E+09 0.131417E+11
December 0.121828E+10 0.00 0.121828E+10 0.00 0.197277E+11
           
Annual Sum or Average 0.415527E+11 0.119908E+10 0.403536E+11 0.277576E+11 0.118106E+12
Minimum of Months 0.121828E+10 0.00 0.121828E+10 0.00 0.238422E+10
Maximum of Months 0.580445E+10 0.526829E+09 0.527762E+10 0.645164E+10 0.227390E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.256298E+10 0.105467E+10 0.150830E+10 0.628261E+09 0.135233E+11
February 0.306845E+10 0.134926E+10 0.171919E+10 0.120229E+10 0.975755E+10
March 0.461578E+10 0.183214E+10 0.278364E+10 0.265757E+10 0.724508E+10
April 0.548490E+10 0.240201E+10 0.308289E+10 0.447582E+10 0.498161E+10
May 0.711822E+10 0.311034E+10 0.400788E+10 0.714231E+10 0.282841E+10
June 0.758072E+10 0.330128E+10 0.427943E+10 0.897771E+10 0.190500E+10
July 0.791757E+10 0.365335E+10 0.426422E+10 0.970654E+10 0.160880E+10
August 0.667436E+10 0.287746E+10 0.379689E+10 0.821069E+10 0.189053E+10
September 0.576090E+10 0.272233E+10 0.303857E+10 0.631742E+10 0.323011E+10
October 0.379362E+10 0.158456E+10 0.220905E+10 0.264633E+10 0.523398E+10
November 0.216607E+10 0.703579E+09 0.146249E+10 0.753612E+09 0.813268E+10
December 0.173378E+10 0.744528E+09 0.989254E+09 0.497886E+09 0.120495E+11
           
Annual Sum or Average 0.584773E+11 0.253355E+11 0.331418E+11 0.532164E+11 0.723866E+11
Minimum of Months 0.173378E+10 0.703579E+09 0.989254E+09 0.497886E+09 0.160880E+10
Maximum of Months 0.791757E+10 0.365335E+10 0.427943E+10 0.970654E+10 0.135233E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111577E+11 0.763545E+10 0.352224E+10 0.781842E+10 0.181126E+11
February 0.107983E+11 0.729542E+10 0.350288E+10 0.803907E+10 0.133298E+11
March 0.104038E+11 0.547828E+10 0.492548E+10 0.832137E+10 0.108605E+11
April 0.907074E+10 0.424075E+10 0.482999E+10 0.869424E+10 0.792456E+10
May 0.776529E+10 0.210528E+10 0.566002E+10 0.806631E+10 0.467731E+10
June 0.729573E+10 0.148545E+10 0.581028E+10 0.892155E+10 0.308816E+10
July 0.798048E+10 0.201087E+10 0.596961E+10 0.103106E+11 0.262429E+10
August 0.899135E+10 0.322452E+10 0.576684E+10 0.118682E+11 0.314608E+10
September 0.105441E+11 0.555590E+10 0.498825E+10 0.126581E+11 0.523154E+10
October 0.113773E+11 0.713767E+10 0.423965E+10 0.111710E+11 0.807408E+10
November 0.830726E+10 0.520050E+10 0.310676E+10 0.650725E+10 0.115552E+11
December 0.915377E+10 0.693387E+10 0.221990E+10 0.734182E+10 0.167302E+11
           
Annual Sum or Average 0.112846E+12 0.583040E+11 0.545419E+11 0.109718E+12 0.105354E+12
Minimum of Months 0.729573E+10 0.148545E+10 0.221990E+10 0.650725E+10 0.262429E+10
Maximum of Months 0.113773E+11 0.763545E+10 0.596961E+10 0.126581E+11 0.181126E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.254184E+10 0.102846E+10 0.151338E+10 0.701536E+09 0.141398E+11
February 0.336647E+10 0.165890E+10 0.170758E+10 0.156780E+10 0.103928E+11
March 0.444947E+10 0.165545E+10 0.279402E+10 0.250179E+10 0.768760E+10
April 0.628108E+10 0.310588E+10 0.317519E+10 0.570221E+10 0.540222E+10
May 0.650922E+10 0.260028E+10 0.390894E+10 0.672754E+10 0.314273E+10
June 0.739142E+10 0.320326E+10 0.418816E+10 0.894176E+10 0.218598E+10
July 0.820068E+10 0.389545E+10 0.430523E+10 0.102777E+11 0.196345E+10
August 0.716946E+10 0.329031E+10 0.387914E+10 0.907012E+10 0.221483E+10
September 0.561626E+10 0.266577E+10 0.295050E+10 0.633062E+10 0.355622E+10
October 0.404410E+10 0.179796E+10 0.224614E+10 0.313375E+10 0.566425E+10
November 0.234257E+10 0.866282E+09 0.147629E+10 0.105286E+10 0.847374E+10
December 0.186161E+10 0.877591E+09 0.984022E+09 0.679051E+09 0.125541E+11
           
Annual Sum or Average 0.597742E+11 0.266456E+11 0.331286E+11 0.566868E+11 0.773776E+11
Minimum of Months 0.186161E+10 0.866282E+09 0.984022E+09 0.679051E+09 0.196345E+10
Maximum of Months 0.820068E+10 0.389545E+10 0.430523E+10 0.102777E+11 0.141398E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.179414E+10 0.00 0.179414E+10 0.00 0.224131E+11
February 0.205449E+10 0.00 0.205449E+10 16909952.99 0.163681E+11
March 0.340895E+10 0.00 0.340895E+10 0.510626E+09 0.115355E+11
April 0.380845E+10 18764039.42 0.378968E+10 0.160035E+10 0.736391E+10
May 0.513183E+10 0.192894E+09 0.493893E+10 0.398094E+10 0.384503E+10
June 0.580445E+10 0.526829E+09 0.527762E+10 0.634823E+10 0.257391E+10
July 0.562512E+10 0.376259E+09 0.524886E+10 0.658174E+10 0.219184E+10
August 0.470988E+10 83472161.85 0.462640E+10 0.556914E+10 0.257282E+10
September 0.349464E+10 866513.52 0.349377E+10 0.311322E+10 0.456785E+10
October 0.268494E+10 0.00 0.268494E+10 0.839100E+09 0.762616E+10
November 0.181756E+10 0.00 0.181756E+10 0.143914E+09 0.125087E+11
December 0.121828E+10 0.00 0.121828E+10 0.00 0.192616E+11
           
Annual Sum or Average 0.415527E+11 0.119908E+10 0.403536E+11 0.287042E+11 0.112828E+12
Minimum of Months 0.121828E+10 0.00 0.121828E+10 0.00 0.219184E+10
Maximum of Months 0.580445E+10 0.526829E+09 0.527762E+10 0.658174E+10 0.224131E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.256298E+10 0.105467E+10 0.150830E+10 0.636515E+09 0.133899E+11
February 0.306845E+10 0.134926E+10 0.171919E+10 0.122962E+10 0.951009E+10
March 0.461578E+10 0.183214E+10 0.278364E+10 0.276634E+10 0.686747E+10
April 0.548490E+10 0.240201E+10 0.308289E+10 0.457529E+10 0.462944E+10
May 0.711822E+10 0.311034E+10 0.400788E+10 0.728222E+10 0.260225E+10
June 0.758072E+10 0.330128E+10 0.427943E+10 0.902509E+10 0.176125E+10
July 0.791757E+10 0.365335E+10 0.426422E+10 0.974348E+10 0.150398E+10
August 0.667436E+10 0.287746E+10 0.379689E+10 0.827814E+10 0.175222E+10
September 0.576090E+10 0.272233E+10 0.303857E+10 0.643760E+10 0.294255E+10
October 0.379362E+10 0.158456E+10 0.220905E+10 0.286193E+10 0.466927E+10
November 0.216607E+10 0.703579E+09 0.146249E+10 0.824832E+09 0.772640E+10
December 0.173378E+10 0.744528E+09 0.989254E+09 0.515829E+09 0.118132E+11
           
Annual Sum or Average 0.584773E+11 0.253355E+11 0.331418E+11 0.541769E+11 0.691680E+11
Minimum of Months 0.173378E+10 0.703579E+09 0.989254E+09 0.515829E+09 0.150398E+10
Maximum of Months 0.791757E+10 0.365335E+10 0.427943E+10 0.974348E+10 0.133899E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111577E+11 0.763545E+10 0.352224E+10 0.788368E+10 0.177334E+11
February 0.107983E+11 0.729542E+10 0.350288E+10 0.814585E+10 0.128307E+11
March 0.104038E+11 0.547828E+10 0.492548E+10 0.843371E+10 0.102540E+11
April 0.907074E+10 0.424075E+10 0.482999E+10 0.875025E+10 0.735495E+10
May 0.776529E+10 0.210528E+10 0.566002E+10 0.818548E+10 0.427585E+10
June 0.729573E+10 0.148545E+10 0.581028E+10 0.897978E+10 0.282848E+10
July 0.798048E+10 0.201087E+10 0.596961E+10 0.103725E+11 0.241658E+10
August 0.899135E+10 0.322452E+10 0.576684E+10 0.119306E+11 0.288860E+10
September 0.105441E+11 0.555590E+10 0.498825E+10 0.127581E+11 0.477347E+10
October 0.113773E+11 0.713767E+10 0.423965E+10 0.113962E+11 0.725448E+10
November 0.830726E+10 0.520050E+10 0.310676E+10 0.667501E+10 0.108953E+11
December 0.915377E+10 0.693387E+10 0.221990E+10 0.744655E+10 0.161904E+11
           
Annual Sum or Average 0.112846E+12 0.583040E+11 0.545419E+11 0.110958E+12 0.996962E+11
Minimum of Months 0.729573E+10 0.148545E+10 0.221990E+10 0.667501E+10 0.241658E+10
Maximum of Months 0.113773E+11 0.763545E+10 0.596961E+10 0.127581E+11 0.177334E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.254184E+10 0.102846E+10 0.151338E+10 0.699502E+09 0.139320E+11
February 0.336647E+10 0.165890E+10 0.170758E+10 0.157357E+10 0.101367E+11
March 0.444947E+10 0.165545E+10 0.279402E+10 0.251779E+10 0.735627E+10
April 0.628108E+10 0.310588E+10 0.317519E+10 0.569283E+10 0.508175E+10
May 0.650922E+10 0.260028E+10 0.390894E+10 0.673542E+10 0.293780E+10
June 0.739142E+10 0.320326E+10 0.418816E+10 0.891970E+10 0.206287E+10
July 0.820068E+10 0.389545E+10 0.430523E+10 0.102535E+11 0.186633E+10
August 0.716946E+10 0.329031E+10 0.387914E+10 0.906109E+10 0.209311E+10
September 0.561626E+10 0.266577E+10 0.295050E+10 0.634778E+10 0.331889E+10
October 0.404410E+10 0.179796E+10 0.224614E+10 0.318931E+10 0.519807E+10
November 0.234257E+10 0.866282E+09 0.147629E+10 0.107850E+10 0.811238E+10
December 0.186161E+10 0.877591E+09 0.984022E+09 0.686324E+09 0.122736E+11
           
Annual Sum or Average 0.597742E+11 0.266456E+11 0.331286E+11 0.567554E+11 0.743698E+11
Minimum of Months 0.186161E+10 0.866282E+09 0.984022E+09 0.686324E+09 0.186633E+10
Maximum of Months 0.820068E+10 0.389545E+10 0.430523E+10 0.102535E+11 0.139320E+11



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 8633.86 669.86 0.00 669.86 0.00 0.00
February 1.09 7139.40 849.25 0.00 849.25 0.00 0.00
March 139.55 4766.64 1272.76 0.00 1272.76 0.00 0.00
April 518.42 3328.27 1469.31 7.24 1462.07 0.00 0.00
May 1323.72 1717.00 1916.01 72.02 1843.99 0.00 0.00
June 2312.30 1192.50 2239.38 203.25 2036.13 0.00 0.00
July 2297.16 990.59 2100.19 140.48 1959.71 0.00 0.00
August 1910.73 1201.51 1758.47 31.17 1727.31 0.00 0.00
September 1058.06 2151.58 1348.24 0.33 1347.91 0.00 0.00
October 193.32 3519.62 1002.44 0.00 1002.44 0.00 0.00
November 23.14 5486.44 701.22 0.00 701.22 0.00 0.00
December 0.00 7713.03 454.85 0.00 454.85 0.00 0.00
               
Annual Sum or Average 819.69 3971.17 1317.63 38.02 1279.61 0.00 0.00
Minimum of Months 0.00 990.59 454.85 0.00 454.85 0.00 0.00
Maximum of Months 2312.30 8633.86 2239.38 203.25 2036.13 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 235.49 5165.58 956.91 393.77 563.14 0.00 0.00
February 494.01 4167.17 1268.38 557.73 710.65 0.00 0.00
March 993.79 2811.45 1723.34 684.05 1039.30 0.00 0.00
April 1744.12 2014.59 2116.10 926.71 1189.39 0.00 0.00
May 2709.39 1097.86 2657.65 1161.27 1496.38 0.00 0.00
June 3498.93 764.27 2924.67 1273.65 1651.02 0.00 0.00
July 3660.82 618.82 2956.09 1364.01 1592.08 0.00 0.00
August 3087.67 734.89 2491.93 1074.33 1417.60 0.00 0.00
September 2449.18 1315.87 2222.58 1050.28 1172.29 0.00 0.00
October 970.76 2100.39 1416.38 591.61 824.77 0.00 0.00
November 277.51 3340.65 835.68 271.44 564.23 0.00 0.00
December 177.44 4710.67 647.32 277.98 369.35 0.00 0.00
               
Annual Sum or Average 1698.14 2394.99 1854.31 803.39 1050.92 0.00 0.00
Minimum of Months 177.44 618.82 647.32 271.44 369.35 0.00 0.00
Maximum of Months 3660.82 5165.58 2956.09 1364.01 1651.02 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2962.72 6788.17 4165.82 2850.76 1315.06 0.00 0.00
February 3376.88 5549.30 4463.60 3015.64 1447.96 0.00 0.00
March 3149.64 4124.44 3884.33 2045.36 1838.97 0.00 0.00
April 3386.03 3156.33 3499.53 1636.10 1863.43 0.00 0.00
May 3021.84 1803.61 2899.24 786.02 2113.22 0.00 0.00
June 3431.98 1253.12 2814.72 573.09 2241.63 0.00 0.00
July 3832.96 1039.22 2979.58 750.78 2228.80 0.00 0.00
August 4424.30 1250.44 3357.00 1203.90 2153.10 0.00 0.00
September 4917.07 2081.99 4067.97 2143.49 1924.49 0.00 0.00
October 4207.13 3102.04 4247.82 2664.91 1582.91 0.00 0.00
November 2518.29 4588.18 3204.97 2006.37 1198.60 0.00 0.00
December 2746.48 6381.59 3417.64 2588.82 828.82 0.00 0.00
               
Annual Sum or Average 3498.22 3416.29 3578.33 1848.81 1729.52 0.00 0.00
Minimum of Months 2518.29 1039.22 2814.72 573.09 828.82 0.00 0.00
Maximum of Months 4917.07 6788.17 4463.60 3015.64 2241.63 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 258.12 5486.30 949.02 383.99 565.03 0.00 0.00
February 638.25 4515.63 1391.57 685.72 705.85 0.00 0.00
March 898.51 3142.09 1661.25 618.08 1043.17 0.00 0.00
April 2154.99 2370.11 2423.27 1198.26 1225.00 0.00 0.00
May 2471.51 1277.68 2430.28 970.84 1459.44 0.00 0.00
June 3405.12 946.91 2851.64 1235.83 1615.81 0.00 0.00
July 3766.09 847.27 3061.79 1454.40 1607.39 0.00 0.00
August 3290.88 999.63 2676.78 1228.47 1448.31 0.00 0.00
September 2400.08 1515.63 2166.78 1028.46 1138.31 0.00 0.00
October 1124.18 2369.96 1509.90 671.28 838.62 0.00 0.00
November 375.50 3637.45 903.77 334.22 569.56 0.00 0.00
December 234.07 5092.79 695.05 327.66 367.39 0.00 0.00
               
Annual Sum or Average 1756.95 2674.60 1895.43 844.93 1050.51 0.00 0.00
Minimum of Months 234.07 847.27 695.05 327.66 367.39 0.00 0.00
Maximum of Months 3766.09 5486.30 3061.79 1454.40 1615.81 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 8489.76 669.85 0.00 669.85 0.00 0.00
February 4.74 6933.74 849.24 0.00 849.24 0.00 0.00
March 171.74 4517.03 1272.75 0.00 1272.75 0.00 0.00
April 593.98 3050.00 1469.31 7.24 1462.07 0.00 0.00
May 1428.98 1571.84 1916.01 72.02 1843.99 0.00 0.00
June 2402.14 1085.45 2239.37 203.25 2036.12 0.00 0.00
July 2408.77 890.17 2100.18 140.48 1959.70 0.00 0.00
August 2029.55 1052.81 1758.47 31.16 1727.30 0.00 0.00
September 1153.10 1938.14 1348.24 0.33 1347.90 0.00 0.00
October 263.62 3161.69 1002.44 0.00 1002.44 0.00 0.00
November 42.57 5070.10 701.22 0.00 701.22 0.00 0.00
December 0.00 7365.47 454.85 0.00 454.85 0.00 0.00
               
Annual Sum or Average 880.19 3745.12 1317.63 38.02 1279.60 0.00 0.00
Minimum of Months 0.00 890.17 454.85 0.00 454.85 0.00 0.00
Maximum of Months 2408.77 8489.76 2239.37 203.25 2036.12 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 234.57 5049.03 956.91 393.77 563.14 0.00 0.00
February 496.98 4033.38 1268.37 557.73 710.64 0.00 0.00
March 992.22 2705.00 1723.33 684.04 1039.29 0.00 0.00
April 1726.78 1921.92 2116.09 926.70 1189.38 0.00 0.00
May 2666.63 1056.01 2657.64 1161.27 1496.37 0.00 0.00
June 3463.62 734.95 2924.66 1273.64 1651.02 0.00 0.00
July 3624.01 600.66 2956.08 1364.00 1592.08 0.00 0.00
August 3065.52 705.84 2491.92 1074.32 1417.60 0.00 0.00
September 2437.27 1246.18 2222.57 1050.28 1172.29 0.00 0.00
October 988.03 1954.14 1416.37 591.61 824.77 0.00 0.00
November 290.75 3137.61 835.67 271.44 564.23 0.00 0.00
December 185.89 4498.79 647.32 277.98 369.35 0.00 0.00
               
Annual Sum or Average 1687.48 2295.36 1854.30 803.38 1050.92 0.00 0.00
Minimum of Months 185.89 600.66 647.32 271.44 369.35 0.00 0.00
Maximum of Months 3624.01 5049.03 2956.08 1364.00 1651.02 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2919.06 6762.48 4165.81 2850.75 1315.05 0.00 0.00
February 3323.03 5510.02 4463.59 3015.63 1447.95 0.00 0.00
March 3106.84 4054.84 3884.32 2045.36 1838.97 0.00 0.00
April 3354.26 3057.32 3499.51 1636.09 1863.42 0.00 0.00
May 3011.62 1746.31 2899.23 786.02 2113.21 0.00 0.00
June 3441.96 1191.42 2814.71 573.09 2241.62 0.00 0.00
July 3849.53 979.80 2979.57 750.77 2228.80 0.00 0.00
August 4431.09 1174.61 3356.99 1203.90 2153.09 0.00 0.00
September 4883.54 2018.34 4067.96 2143.48 1924.48 0.00 0.00
October 4170.79 3014.52 4247.81 2664.90 1582.90 0.00 0.00
November 2510.51 4458.04 3204.96 2006.37 1198.59 0.00 0.00
December 2741.12 6246.33 3417.63 2588.81 828.82 0.00 0.00
               
Annual Sum or Average 3479.14 3340.77 3578.32 1848.81 1729.51 0.00 0.00
Minimum of Months 2510.51 979.80 2814.71 573.09 828.82 0.00 0.00
Maximum of Months 4883.54 6762.48 4463.59 3015.63 2241.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 261.92 5279.20 949.02 383.98 565.03 0.00 0.00
February 648.07 4295.95 1391.56 685.72 705.84 0.00 0.00
March 934.06 2870.22 1661.24 618.07 1043.17 0.00 0.00
April 2199.93 2084.19 2423.26 1198.26 1225.00 0.00 0.00
May 2511.78 1173.36 2430.27 970.83 1459.43 0.00 0.00
June 3449.75 843.36 2851.63 1235.83 1615.80 0.00 0.00
July 3837.27 733.07 3061.78 1454.40 1607.39 0.00 0.00
August 3386.40 826.92 2676.77 1228.46 1448.31 0.00 0.00
September 2442.37 1372.00 2166.77 1028.46 1138.31 0.00 0.00
October 1170.01 2114.79 1509.89 671.28 838.61 0.00 0.00
November 406.20 3269.19 903.77 334.21 569.56 0.00 0.00
December 253.53 4687.15 695.05 327.66 367.39 0.00 0.00
               
Annual Sum or Average 1797.53 2453.63 1895.43 844.93 1050.50 0.00 0.00
Minimum of Months 253.53 733.07 695.05 327.66 367.39 0.00 0.00
Maximum of Months 3837.27 5279.20 3061.78 1454.40 1615.80 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 8368.10 669.85 0.00 669.85 0.00 0.00
February 6.99 6765.90 849.24 0.00 849.24 0.00 0.00
March 190.65 4306.86 1272.75 0.00 1272.75 0.00 0.00
April 617.42 2841.01 1469.31 7.24 1462.07 0.00 0.00
May 1486.31 1435.57 1916.01 72.02 1843.99 0.00 0.00
June 2449.16 993.02 2239.37 203.25 2036.12 0.00 0.00
July 2457.34 818.34 2100.18 140.48 1959.70 0.00 0.00
August 2079.28 960.58 1758.47 31.16 1727.30 0.00 0.00
September 1201.09 1762.29 1348.24 0.33 1347.90 0.00 0.00
October 313.28 2847.28 1002.44 0.00 1002.44 0.00 0.00
November 55.52 4825.88 701.22 0.00 701.22 0.00 0.00
December 0.00 7191.46 454.85 0.00 454.85 0.00 0.00
               
Annual Sum or Average 910.20 3577.77 1317.63 38.02 1279.60 0.00 0.00
Minimum of Months 0.00 818.34 454.85 0.00 454.85 0.00 0.00
Maximum of Months 2457.34 8368.10 2239.37 203.25 2036.12 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 237.65 4999.23 956.91 393.77 563.14 0.00 0.00
February 508.27 3931.09 1268.37 557.73 710.64 0.00 0.00
March 1032.83 2564.02 1723.33 684.04 1039.29 0.00 0.00
April 1765.16 1786.05 2116.09 926.70 1189.38 0.00 0.00
May 2718.87 971.57 2657.64 1161.27 1496.37 0.00 0.00
June 3481.90 679.50 2924.66 1273.64 1651.02 0.00 0.00
July 3637.80 561.52 2956.08 1364.00 1592.08 0.00 0.00
August 3090.70 654.20 2491.92 1074.32 1417.60 0.00 0.00
September 2483.64 1135.24 2222.57 1050.28 1172.29 0.00 0.00
October 1068.52 1743.30 1416.37 591.61 824.77 0.00 0.00
November 318.22 2980.86 835.67 271.44 564.23 0.00 0.00
December 192.59 4410.53 647.32 277.98 369.35 0.00 0.00
               
Annual Sum or Average 1717.94 2193.30 1854.30 803.38 1050.92 0.00 0.00
Minimum of Months 192.59 561.52 647.32 271.44 369.35 0.00 0.00
Maximum of Months 3637.80 4999.23 2956.08 1364.00 1651.02 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2943.43 6620.89 4165.81 2850.75 1315.05 0.00 0.00
February 3367.17 5303.71 4463.59 3015.63 1447.95 0.00 0.00
March 3148.79 3828.40 3884.32 2045.36 1838.97 0.00 0.00
April 3375.87 2837.56 3499.51 1636.09 1863.42 0.00 0.00
May 3056.11 1596.42 2899.23 786.02 2113.21 0.00 0.00
June 3464.42 1091.23 2814.71 573.09 2241.62 0.00 0.00
July 3872.66 902.25 2979.57 750.77 2228.80 0.00 0.00
August 4454.36 1078.48 3356.99 1203.90 2153.09 0.00 0.00
September 4922.12 1841.62 4067.96 2143.48 1924.48 0.00 0.00
October 4254.86 2708.51 4247.81 2664.90 1582.90 0.00 0.00
November 2575.24 4203.43 3204.96 2006.37 1198.59 0.00 0.00
December 2780.22 6044.79 3417.63 2588.81 828.82 0.00 0.00
               
Annual Sum or Average 3518.45 3161.34 3578.32 1848.81 1729.51 0.00 0.00
Minimum of Months 2575.24 902.25 2814.71 573.09 828.82 0.00 0.00
Maximum of Months 4922.12 6620.89 4463.59 3015.63 2241.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 261.16 5201.62 949.02 383.98 565.03 0.00 0.00
February 650.45 4190.12 1391.56 685.72 705.84 0.00 0.00
March 940.03 2746.52 1661.24 618.07 1043.17 0.00 0.00
April 2196.31 1960.55 2423.26 1198.26 1225.00 0.00 0.00
May 2514.72 1096.85 2430.27 970.83 1459.43 0.00 0.00
June 3441.24 795.86 2851.63 1235.83 1615.80 0.00 0.00
July 3828.23 696.81 3061.78 1454.40 1607.39 0.00 0.00
August 3383.02 781.48 2676.77 1228.46 1448.31 0.00 0.00
September 2448.99 1280.44 2166.77 1028.46 1138.31 0.00 0.00
October 1190.75 1940.74 1509.89 671.28 838.61 0.00 0.00
November 416.09 3129.78 903.77 334.21 569.56 0.00 0.00
December 256.24 4582.44 695.05 327.66 367.39 0.00 0.00
               
Annual Sum or Average 1799.70 2358.25 1895.43 844.93 1050.50 0.00 0.00
Minimum of Months 256.24 696.81 695.05 327.66 367.39 0.00 0.00
Maximum of Months 3828.23 5201.62 3061.78 1454.40 1615.80 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.231249E+11 0.179414E+10 0.00 0.179414E+10 0.00 0.00
February 2644677.08 0.172716E+11 0.205450E+10 0.00 0.205450E+10 0.00 0.00
March 0.373773E+09 0.127670E+11 0.340896E+10 0.00 0.340896E+10 0.00 0.00
April 0.134374E+10 0.862687E+10 0.380846E+10 18764106.05 0.378970E+10 0.00 0.00
May 0.354546E+10 0.459883E+10 0.513185E+10 0.192894E+09 0.493895E+10 0.00 0.00
June 0.599348E+10 0.309097E+10 0.580447E+10 0.526831E+09 0.527764E+10 0.00 0.00
July 0.615273E+10 0.265319E+10 0.562514E+10 0.376260E+09 0.524888E+10 0.00 0.00
August 0.511770E+10 0.321811E+10 0.470989E+10 83472458.26 0.462642E+10 0.00 0.00
September 0.274249E+10 0.557691E+10 0.349465E+10 866516.60 0.349378E+10 0.00 0.00
October 0.517797E+09 0.942696E+10 0.268495E+10 0.00 0.268495E+10 0.00 0.00
November 59983842.91 0.142208E+11 0.181756E+10 0.00 0.181756E+10 0.00 0.00
December 0.00 0.206586E+11 0.121828E+10 0.00 0.121828E+10 0.00 0.00
               
Annual Sum or Average 0.258498E+11 0.125235E+12 0.415529E+11 0.119909E+10 0.403538E+11 0.00 0.00
Minimum of Months 0.00 0.265319E+10 0.121828E+10 0.00 0.121828E+10 0.00 0.00
Maximum of Months 0.615273E+10 0.231249E+11 0.580447E+10 0.526831E+09 0.527764E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.630749E+09 0.138355E+11 0.256299E+10 0.105468E+10 0.150831E+10 0.00 0.00
February 0.119511E+10 0.100812E+11 0.306846E+10 0.134926E+10 0.171920E+10 0.00 0.00
March 0.266176E+10 0.753018E+10 0.461579E+10 0.183215E+10 0.278365E+10 0.00 0.00
April 0.452077E+10 0.522181E+10 0.548492E+10 0.240202E+10 0.308290E+10 0.00 0.00
May 0.725684E+10 0.294051E+10 0.711825E+10 0.311035E+10 0.400790E+10 0.00 0.00
June 0.906923E+10 0.198099E+10 0.758075E+10 0.330130E+10 0.427945E+10 0.00 0.00
July 0.980515E+10 0.165744E+10 0.791760E+10 0.365336E+10 0.426424E+10 0.00 0.00
August 0.827003E+10 0.196832E+10 0.667439E+10 0.287748E+10 0.379691E+10 0.00 0.00
September 0.634828E+10 0.341073E+10 0.576092E+10 0.272234E+10 0.303859E+10 0.00 0.00
October 0.260008E+10 0.562569E+10 0.379363E+10 0.158457E+10 0.220906E+10 0.00 0.00
November 0.719296E+09 0.865896E+10 0.216607E+10 0.703581E+09 0.146249E+10 0.00 0.00
December 0.475251E+09 0.126171E+11 0.173379E+10 0.744531E+09 0.989258E+09 0.00 0.00
               
Annual Sum or Average 0.535525E+11 0.755284E+11 0.584776E+11 0.253356E+11 0.331419E+11 0.00 0.00
Minimum of Months 0.475251E+09 0.165744E+10 0.173379E+10 0.703581E+09 0.989258E+09 0.00 0.00
Maximum of Months 0.980515E+10 0.138355E+11 0.791760E+10 0.365336E+10 0.427945E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.793536E+10 0.181814E+11 0.111577E+11 0.763548E+10 0.352225E+10 0.00 0.00
February 0.816935E+10 0.134249E+11 0.107983E+11 0.729545E+10 0.350290E+10 0.00 0.00
March 0.843598E+10 0.110469E+11 0.104038E+11 0.547830E+10 0.492550E+10 0.00 0.00
April 0.877660E+10 0.818121E+10 0.907078E+10 0.424077E+10 0.483001E+10 0.00 0.00
May 0.809369E+10 0.483078E+10 0.776532E+10 0.210528E+10 0.566004E+10 0.00 0.00
June 0.889570E+10 0.324808E+10 0.729576E+10 0.148546E+10 0.581030E+10 0.00 0.00
July 0.102662E+11 0.278345E+10 0.798051E+10 0.201088E+10 0.596963E+10 0.00 0.00
August 0.118500E+11 0.334919E+10 0.899139E+10 0.322453E+10 0.576686E+10 0.00 0.00
September 0.127451E+11 0.539652E+10 0.105442E+11 0.555592E+10 0.498827E+10 0.00 0.00
October 0.112684E+11 0.830850E+10 0.113774E+11 0.713770E+10 0.423967E+10 0.00 0.00
November 0.652741E+10 0.118926E+11 0.830729E+10 0.520052E+10 0.310677E+10 0.00 0.00
December 0.735617E+10 0.170925E+11 0.915380E+10 0.693390E+10 0.221991E+10 0.00 0.00
               
Annual Sum or Average 0.110320E+12 0.107736E+12 0.112846E+12 0.583042E+11 0.545421E+11 0.00 0.00
Minimum of Months 0.652741E+10 0.278345E+10 0.729576E+10 0.148546E+10 0.221991E+10 0.00 0.00
Maximum of Months 0.127451E+11 0.181814E+11 0.113774E+11 0.763548E+10 0.596963E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.691340E+09 0.146945E+11 0.254186E+10 0.102847E+10 0.151339E+10 0.00 0.00
February 0.154406E+10 0.109242E+11 0.336649E+10 0.165890E+10 0.170758E+10 0.00 0.00
March 0.240658E+10 0.841578E+10 0.444948E+10 0.165545E+10 0.279403E+10 0.00 0.00
April 0.558573E+10 0.614333E+10 0.628110E+10 0.310590E+10 0.317521E+10 0.00 0.00
May 0.661969E+10 0.342215E+10 0.650925E+10 0.260029E+10 0.390896E+10 0.00 0.00
June 0.882607E+10 0.245440E+10 0.739145E+10 0.320327E+10 0.418818E+10 0.00 0.00
July 0.100871E+11 0.226934E+10 0.820071E+10 0.389547E+10 0.430524E+10 0.00 0.00
August 0.881430E+10 0.267742E+10 0.716949E+10 0.329033E+10 0.387916E+10 0.00 0.00
September 0.622100E+10 0.392852E+10 0.561629E+10 0.266578E+10 0.295051E+10 0.00 0.00
October 0.301099E+10 0.634770E+10 0.404412E+10 0.179797E+10 0.224615E+10 0.00 0.00
November 0.973297E+09 0.942828E+10 0.234258E+10 0.866286E+09 0.147630E+10 0.00 0.00
December 0.626932E+09 0.136405E+11 0.186162E+10 0.877595E+09 0.984026E+09 0.00 0.00
               
Annual Sum or Average 0.554071E+11 0.843462E+11 0.597744E+11 0.266457E+11 0.331287E+11 0.00 0.00
Minimum of Months 0.626932E+09 0.226934E+10 0.186162E+10 0.866286E+09 0.984026E+09 0.00 0.00
Maximum of Months 0.100871E+11 0.146945E+11 0.820071E+10 0.389547E+10 0.430524E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.227390E+11 0.179414E+10 0.00 0.179414E+10 0.00 0.00
February 11461168.83 0.167741E+11 0.205449E+10 0.00 0.205449E+10 0.00 0.00
March 0.459985E+09 0.120984E+11 0.340895E+10 0.00 0.340895E+10 0.00 0.00
April 0.153959E+10 0.790559E+10 0.380845E+10 18764039.42 0.378968E+10 0.00 0.00
May 0.382737E+10 0.421002E+10 0.513183E+10 0.192894E+09 0.493893E+10 0.00 0.00
June 0.622634E+10 0.281348E+10 0.580445E+10 0.526829E+09 0.527762E+10 0.00 0.00
July 0.645164E+10 0.238422E+10 0.562512E+10 0.376259E+09 0.524886E+10 0.00 0.00
August 0.543594E+10 0.281985E+10 0.470988E+10 83472161.85 0.462640E+10 0.00 0.00
September 0.298885E+10 0.502367E+10 0.349464E+10 866513.52 0.349377E+10 0.00 0.00
October 0.706085E+09 0.846827E+10 0.268494E+10 0.00 0.268494E+10 0.00 0.00
November 0.110334E+09 0.131417E+11 0.181756E+10 0.00 0.181756E+10 0.00 0.00
December 0.00 0.197277E+11 0.121828E+10 0.00 0.121828E+10 0.00 0.00
               
Annual Sum or Average 0.277576E+11 0.118106E+12 0.415527E+11 0.119908E+10 0.403536E+11 0.00 0.00
Minimum of Months 0.00 0.238422E+10 0.121828E+10 0.00 0.121828E+10 0.00 0.00
Maximum of Months 0.645164E+10 0.227390E+11 0.580445E+10 0.526829E+09 0.527762E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.628261E+09 0.135233E+11 0.256298E+10 0.105467E+10 0.150830E+10 0.00 0.00
February 0.120229E+10 0.975755E+10 0.306845E+10 0.134926E+10 0.171919E+10 0.00 0.00
March 0.265757E+10 0.724508E+10 0.461578E+10 0.183214E+10 0.278364E+10 0.00 0.00
April 0.447582E+10 0.498161E+10 0.548490E+10 0.240201E+10 0.308289E+10 0.00 0.00
May 0.714231E+10 0.282841E+10 0.711822E+10 0.311034E+10 0.400788E+10 0.00 0.00
June 0.897771E+10 0.190500E+10 0.758072E+10 0.330128E+10 0.427943E+10 0.00 0.00
July 0.970654E+10 0.160880E+10 0.791757E+10 0.365335E+10 0.426422E+10 0.00 0.00
August 0.821069E+10 0.189053E+10 0.667436E+10 0.287746E+10 0.379689E+10 0.00 0.00
September 0.631742E+10 0.323011E+10 0.576090E+10 0.272233E+10 0.303857E+10 0.00 0.00
October 0.264633E+10 0.523398E+10 0.379362E+10 0.158456E+10 0.220905E+10 0.00 0.00
November 0.753612E+09 0.813268E+10 0.216607E+10 0.703579E+09 0.146249E+10 0.00 0.00
December 0.497886E+09 0.120495E+11 0.173378E+10 0.744528E+09 0.989254E+09 0.00 0.00
               
Annual Sum or Average 0.532164E+11 0.723866E+11 0.584773E+11 0.253355E+11 0.331418E+11 0.00 0.00
Minimum of Months 0.497886E+09 0.160880E+10 0.173378E+10 0.703579E+09 0.989254E+09 0.00 0.00
Maximum of Months 0.970654E+10 0.135233E+11 0.791757E+10 0.365335E+10 0.427943E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.781842E+10 0.181126E+11 0.111577E+11 0.763545E+10 0.352224E+10 0.00 0.00
February 0.803907E+10 0.133298E+11 0.107983E+11 0.729542E+10 0.350288E+10 0.00 0.00
March 0.832137E+10 0.108605E+11 0.104038E+11 0.547828E+10 0.492548E+10 0.00 0.00
April 0.869424E+10 0.792456E+10 0.907074E+10 0.424075E+10 0.482999E+10 0.00 0.00
May 0.806631E+10 0.467731E+10 0.776529E+10 0.210528E+10 0.566002E+10 0.00 0.00
June 0.892155E+10 0.308816E+10 0.729573E+10 0.148545E+10 0.581028E+10 0.00 0.00
July 0.103106E+11 0.262429E+10 0.798048E+10 0.201087E+10 0.596961E+10 0.00 0.00
August 0.118682E+11 0.314608E+10 0.899135E+10 0.322452E+10 0.576684E+10 0.00 0.00
September 0.126581E+11 0.523154E+10 0.105441E+11 0.555590E+10 0.498825E+10 0.00 0.00
October 0.111710E+11 0.807408E+10 0.113773E+11 0.713767E+10 0.423965E+10 0.00 0.00
November 0.650725E+10 0.115552E+11 0.830726E+10 0.520050E+10 0.310676E+10 0.00 0.00
December 0.734182E+10 0.167302E+11 0.915377E+10 0.693387E+10 0.221990E+10 0.00 0.00
               
Annual Sum or Average 0.109718E+12 0.105354E+12 0.112846E+12 0.583040E+11 0.545419E+11 0.00 0.00
Minimum of Months 0.650725E+10 0.262429E+10 0.729573E+10 0.148545E+10 0.221990E+10 0.00 0.00
Maximum of Months 0.126581E+11 0.181126E+11 0.113773E+11 0.763545E+10 0.596961E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.701536E+09 0.141398E+11 0.254184E+10 0.102846E+10 0.151338E+10 0.00 0.00
February 0.156780E+10 0.103928E+11 0.336647E+10 0.165890E+10 0.170758E+10 0.00 0.00
March 0.250179E+10 0.768760E+10 0.444947E+10 0.165545E+10 0.279402E+10 0.00 0.00
April 0.570221E+10 0.540222E+10 0.628108E+10 0.310588E+10 0.317519E+10 0.00 0.00
May 0.672754E+10 0.314273E+10 0.650922E+10 0.260028E+10 0.390894E+10 0.00 0.00
June 0.894176E+10 0.218598E+10 0.739142E+10 0.320326E+10 0.418816E+10 0.00 0.00
July 0.102777E+11 0.196345E+10 0.820068E+10 0.389545E+10 0.430523E+10 0.00 0.00
August 0.907012E+10 0.221483E+10 0.716946E+10 0.329031E+10 0.387914E+10 0.00 0.00
September 0.633062E+10 0.355622E+10 0.561626E+10 0.266577E+10 0.295050E+10 0.00 0.00
October 0.313375E+10 0.566425E+10 0.404410E+10 0.179796E+10 0.224614E+10 0.00 0.00
November 0.105286E+10 0.847374E+10 0.234257E+10 0.866282E+09 0.147629E+10 0.00 0.00
December 0.679051E+09 0.125541E+11 0.186161E+10 0.877591E+09 0.984022E+09 0.00 0.00
               
Annual Sum or Average 0.566868E+11 0.773776E+11 0.597742E+11 0.266456E+11 0.331286E+11 0.00 0.00
Minimum of Months 0.679051E+09 0.196345E+10 0.186161E+10 0.866282E+09 0.984022E+09 0.00 0.00
Maximum of Months 0.102777E+11 0.141398E+11 0.820068E+10 0.389545E+10 0.430523E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.224131E+11 0.179414E+10 0.00 0.179414E+10 0.00 0.00
February 16909952.99 0.163681E+11 0.205449E+10 0.00 0.205449E+10 0.00 0.00
March 0.510626E+09 0.115355E+11 0.340895E+10 0.00 0.340895E+10 0.00 0.00
April 0.160035E+10 0.736391E+10 0.380845E+10 18764039.42 0.378968E+10 0.00 0.00
May 0.398094E+10 0.384503E+10 0.513183E+10 0.192894E+09 0.493893E+10 0.00 0.00
June 0.634823E+10 0.257391E+10 0.580445E+10 0.526829E+09 0.527762E+10 0.00 0.00
July 0.658174E+10 0.219184E+10 0.562512E+10 0.376259E+09 0.524886E+10 0.00 0.00
August 0.556914E+10 0.257282E+10 0.470988E+10 83472161.85 0.462640E+10 0.00 0.00
September 0.311322E+10 0.456785E+10 0.349464E+10 866513.52 0.349377E+10 0.00 0.00
October 0.839100E+09 0.762616E+10 0.268494E+10 0.00 0.268494E+10 0.00 0.00
November 0.143914E+09 0.125087E+11 0.181756E+10 0.00 0.181756E+10 0.00 0.00
December 0.00 0.192616E+11 0.121828E+10 0.00 0.121828E+10 0.00 0.00
               
Annual Sum or Average 0.287042E+11 0.112828E+12 0.415527E+11 0.119908E+10 0.403536E+11 0.00 0.00
Minimum of Months 0.00 0.219184E+10 0.121828E+10 0.00 0.121828E+10 0.00 0.00
Maximum of Months 0.658174E+10 0.224131E+11 0.580445E+10 0.526829E+09 0.527762E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.636515E+09 0.133899E+11 0.256298E+10 0.105467E+10 0.150830E+10 0.00 0.00
February 0.122962E+10 0.951009E+10 0.306845E+10 0.134926E+10 0.171919E+10 0.00 0.00
March 0.276634E+10 0.686747E+10 0.461578E+10 0.183214E+10 0.278364E+10 0.00 0.00
April 0.457529E+10 0.462944E+10 0.548490E+10 0.240201E+10 0.308289E+10 0.00 0.00
May 0.728222E+10 0.260225E+10 0.711822E+10 0.311034E+10 0.400788E+10 0.00 0.00
June 0.902509E+10 0.176125E+10 0.758072E+10 0.330128E+10 0.427943E+10 0.00 0.00
July 0.974348E+10 0.150398E+10 0.791757E+10 0.365335E+10 0.426422E+10 0.00 0.00
August 0.827814E+10 0.175222E+10 0.667436E+10 0.287746E+10 0.379689E+10 0.00 0.00
September 0.643760E+10 0.294255E+10 0.576090E+10 0.272233E+10 0.303857E+10 0.00 0.00
October 0.286193E+10 0.466927E+10 0.379362E+10 0.158456E+10 0.220905E+10 0.00 0.00
November 0.824832E+09 0.772640E+10 0.216607E+10 0.703579E+09 0.146249E+10 0.00 0.00
December 0.515829E+09 0.118132E+11 0.173378E+10 0.744528E+09 0.989254E+09 0.00 0.00
               
Annual Sum or Average 0.541769E+11 0.691680E+11 0.584773E+11 0.253355E+11 0.331418E+11 0.00 0.00
Minimum of Months 0.515829E+09 0.150398E+10 0.173378E+10 0.703579E+09 0.989254E+09 0.00 0.00
Maximum of Months 0.974348E+10 0.133899E+11 0.791757E+10 0.365335E+10 0.427943E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.788368E+10 0.177334E+11 0.111577E+11 0.763545E+10 0.352224E+10 0.00 0.00
February 0.814585E+10 0.128307E+11 0.107983E+11 0.729542E+10 0.350288E+10 0.00 0.00
March 0.843371E+10 0.102540E+11 0.104038E+11 0.547828E+10 0.492548E+10 0.00 0.00
April 0.875025E+10 0.735495E+10 0.907074E+10 0.424075E+10 0.482999E+10 0.00 0.00
May 0.818548E+10 0.427585E+10 0.776529E+10 0.210528E+10 0.566002E+10 0.00 0.00
June 0.897978E+10 0.282848E+10 0.729573E+10 0.148545E+10 0.581028E+10 0.00 0.00
July 0.103725E+11 0.241658E+10 0.798048E+10 0.201087E+10 0.596961E+10 0.00 0.00
August 0.119306E+11 0.288860E+10 0.899135E+10 0.322452E+10 0.576684E+10 0.00 0.00
September 0.127581E+11 0.477347E+10 0.105441E+11 0.555590E+10 0.498825E+10 0.00 0.00
October 0.113962E+11 0.725448E+10 0.113773E+11 0.713767E+10 0.423965E+10 0.00 0.00
November 0.667501E+10 0.108953E+11 0.830726E+10 0.520050E+10 0.310676E+10 0.00 0.00
December 0.744655E+10 0.161904E+11 0.915377E+10 0.693387E+10 0.221990E+10 0.00 0.00
               
Annual Sum or Average 0.110958E+12 0.996962E+11 0.112846E+12 0.583040E+11 0.545419E+11 0.00 0.00
Minimum of Months 0.667501E+10 0.241658E+10 0.729573E+10 0.148545E+10 0.221990E+10 0.00 0.00
Maximum of Months 0.127581E+11 0.177334E+11 0.113773E+11 0.763545E+10 0.596961E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.699502E+09 0.139320E+11 0.254184E+10 0.102846E+10 0.151338E+10 0.00 0.00
February 0.157357E+10 0.101367E+11 0.336647E+10 0.165890E+10 0.170758E+10 0.00 0.00
March 0.251779E+10 0.735627E+10 0.444947E+10 0.165545E+10 0.279402E+10 0.00 0.00
April 0.569283E+10 0.508175E+10 0.628108E+10 0.310588E+10 0.317519E+10 0.00 0.00
May 0.673542E+10 0.293780E+10 0.650922E+10 0.260028E+10 0.390894E+10 0.00 0.00
June 0.891970E+10 0.206287E+10 0.739142E+10 0.320326E+10 0.418816E+10 0.00 0.00
July 0.102535E+11 0.186633E+10 0.820068E+10 0.389545E+10 0.430523E+10 0.00 0.00
August 0.906109E+10 0.209311E+10 0.716946E+10 0.329031E+10 0.387914E+10 0.00 0.00
September 0.634778E+10 0.331889E+10 0.561626E+10 0.266577E+10 0.295050E+10 0.00 0.00
October 0.318931E+10 0.519807E+10 0.404410E+10 0.179796E+10 0.224614E+10 0.00 0.00
November 0.107850E+10 0.811238E+10 0.234257E+10 0.866282E+09 0.147629E+10 0.00 0.00
December 0.686324E+09 0.122736E+11 0.186161E+10 0.877591E+09 0.984022E+09 0.00 0.00
               
Annual Sum or Average 0.567554E+11 0.743698E+11 0.597742E+11 0.266456E+11 0.331286E+11 0.00 0.00
Minimum of Months 0.686324E+09 0.186633E+10 0.186161E+10 0.866282E+09 0.984022E+09 0.00 0.00
Maximum of Months 0.102535E+11 0.139320E+11 0.820068E+10 0.389545E+10 0.430523E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January -12.6 -13.1 -15.2 6.10 -26.1 37.55 107.22 0.02
February -7.7 -8.6 -10.9 6.39 -21.3 45.57 135.04 0.00
March 0.33 -1.4 -4.2 6.99 -10.6 74.69 127.11 0.00
April 7.02 4.40 1.63 6.38 -3.6 77.59 184.47 0.02
May 14.19 11.30 8.94 5.14 4.70 102.33 182.89 0.00
June 19.16 15.71 13.79 4.87 8.84 110.26 213.51 0.04
July 20.92 17.87 16.31 4.22 9.95 102.99 231.93 0.03
August 20.05 17.00 15.28 4.97 11.01 95.97 190.14 0.00
September 15.39 11.24 8.10 4.97 3.18 72.67 177.74 0.01
October 7.43 4.69 1.56 5.55 -3.9 55.50 131.91 0.00
November -0.0 -1.5 -3.9 6.30 -10.9 41.35 79.05 0.00
December -7.6 -8.4 -10.6 6.09 -20.0 22.97 92.59 0.00
                 
Annual Sum or Average 6.46 4.16 1.81 5.66 -4.8 70.09 154.52 0.01
Minimum of Months -12.6 -13.1 -15.2 4.22 -26.1 22.97 79.05 0.00
Maximum of Months 20.92 17.87 16.31 6.99 11.01 110.26 231.93 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 6.10 17-JAN-23:19 3.74 0.93 10.63 -0.4 0.00 0.00
February 8.30 24-FEB-14:00 5.62 2.80 5.20 -7.3 71.00 794.50
March 18.90 19-MAR-15:00 13.93 10.60 8.80 7.95 139.50 237.50
April 30.00 15-APR-15:20 19.12 13.53 12.70 15.70 115.83 790.83
May 30.00 31-MAY-12:00 19.70 14.40 6.20 19.52 251.00 580.50
June 33.30 11-JUN-14:00 24.81 21.70 10.30 24.50 281.00 458.50
July 30.00 26-JUL-15:20 25.67 24.23 5.13 20.98 260.33 436.00
August 33.90 04-AUG-14:00 25.31 22.20 4.60 23.82 194.50 612.00
September 32.20 06-SEP-13:00 21.19 16.10 6.20 18.28 135.00 769.00
October 23.30 20-OCT-14:00 13.36 5.60 7.20 7.35 55.00 745.50
November 16.10 03-NOV-13:00 10.47 5.60 6.70 0.51 82.00 691.00
December 7.20 02-DEC-13:00 3.94 0.00 7.70 -3.9 75.00 301.00
                 
Annual Sum or Average                
Minimum of Months 6.10   3.74 0.00 4.60 -7.3 0.00 0.00
Maximum of Months 33.90   25.67 24.23 12.70 24.50 281.00 794.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -31.1 31-JAN-03:00 -31.3 -34.4 4.60 -46.7 0.00 0.00
February -36.7 02-FEB-05:00 -36.8 -40.2 3.10 -59.6 0.00 0.00
March -17.2 06-MAR-00:00 -17.6 -20.0 5.20 -36.8 0.00 0.00
April -7.2 03-APR-05:19 -8.0 -9.8 7.37 -15.9 0.00 0.00
May 0.60 03-MAY-02:00 -0.1 -1.1 1.50 -15.5 0.00 0.00
June 5.00 01-JUN-04:00 5.00 5.00 3.10 -7.8 30.50 132.50
July 10.00 23-JUL-03:00 9.66 9.40 2.60 -4.3 0.00 0.00
August 8.30 07-AUG-03:00 7.41 6.70 3.10 -3.2 0.00 0.00
September -1.1 30-SEP-00:00 -2.4 -4.4 4.10 -17.8 0.00 0.00
October -3.3 23-OCT-05:00 -4.2 -6.1 3.60 -19.1 0.00 0.00
November -28.9 26-NOV-06:00 -29.0 -30.6 1.50 -50.2 0.00 0.00
December -22.8 09-DEC-00:20 -23.0 -25.0 13.40 -37.7 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -36.7   -36.8 -40.2 1.50 -59.6 0.00 0.00
Maximum of Months 10.00   9.66 9.40 13.40 -3.2 30.50 132.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 5.60 18-JAN-00:00 5.60 5.60 7.70 0.30 0.00 0.00
February 5.88 24-FEB-15:00 8.30 3.30 5.70 -7.3 54.50 665.50
March 13.93 19-MAR-15:00 18.90 10.60 8.80 7.95 139.50 237.50
April 20.94 18-APR-11:00 27.80 17.80 13.90 17.57 334.00 447.00
May 19.93 29-MAY-13:00 23.30 18.30 6.20 20.75 379.00 52.00
June 24.81 11-JUN-14:00 33.30 21.70 10.30 24.50 281.00 458.50
July 26.15 26-JUL-18:00 27.80 25.60 3.10 19.35 33.50 51.00
August 26.64 04-AUG-12:00 31.70 25.00 4.60 25.66 235.00 593.50
September 21.19 06-SEP-13:00 32.20 16.10 6.20 18.28 135.00 769.00
October 14.84 02-OCT-14:00 18.30 12.80 3.60 12.41 202.00 164.00
November 13.04 09-NOV-04:00 15.00 11.70 10.30 10.88 0.00 0.00
December 3.94 02-DEC-13:00 7.20 0.00 7.70 -3.9 75.00 301.00
                 
Annual Sum or Average                
Minimum of Months 3.94   5.60 0.00 3.10 -7.3 0.00 0.00
Maximum of Months 26.64   33.30 25.60 13.90 25.66 379.00 769.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 5.60 18-JAN-00:00 5.60 5.60 7.70 0.30 0.00 0.00
February 3.30 24-FEB-15:00 8.30 5.88 5.70 -7.3 54.50 665.50
March 11.10 26-MAR-05:00 13.30 12.04 8.20 9.13 0.00 0.00
April 18.30 18-APR-09:00 25.60 20.52 14.40 15.57 196.00 741.50
May 18.30 29-MAY-13:00 23.30 19.93 6.20 20.75 379.00 52.00
June 22.20 13-JUN-11:00 26.70 23.35 8.80 16.85 273.50 600.50
July 25.60 26-JUL-18:00 27.80 26.15 3.10 19.35 33.50 51.00
August 25.00 04-AUG-12:00 31.70 26.64 4.60 25.66 235.00 593.50
September 18.30 12-SEP-02:00 18.90 18.46 5.70 14.28 0.00 0.00
October 12.80 02-OCT-13:00 17.40 14.50 3.40 11.65 249.50 141.50
November 11.70 08-NOV-10:00 13.90 12.62 7.20 9.91 158.00 0.50
December 0.00 02-DEC-11:00 5.00 2.79 7.20 -8.3 115.50 562.00
                 
Annual Sum or Average                
Minimum of Months 0.00   5.00 2.79 3.10 -8.3 0.00 0.00
Maximum of Months 25.60   31.70 26.64 14.40 25.66 379.00 741.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 4.29 14.52 0.00
February 18.00 13.00 16.00 3.18 19.75 0.00
March 18.00 13.00 16.00 3.75 28.43 0.00
April 18.00 13.00 16.00 5.88 38.20 0.00
May 18.00 13.00 16.00 9.06 44.89 0.00
June 18.00 13.00 16.00 12.40 51.07 0.00
July 18.00 13.00 16.00 15.02 51.61 0.00
August 18.00 13.00 16.00 16.22 43.31 0.00
September 18.00 13.00 16.00 15.63 34.41 0.00
October 18.00 13.00 16.00 13.44 22.83 0.00
November 18.00 13.00 16.00 10.25 13.98 0.00
December 18.00 13.00 16.00 6.92 10.24 0.00
             
Annual Sum or Average 18.00 13.00 16.00 9.71 31.16 0.00
Minimum of Months 18.00 13.00 16.00 3.18 10.24 0.00
Maximum of Months 18.00 13.00 16.00 16.22 51.61 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.448078E+11 -0.443322E+11 0.00 0.00 744.00 0.00 -475521631.1 60.05 0.00 0.00
February 0.415062E+11 -0.410826E+11 0.00 0.00 672.00 0.00 -423664310.7 60.05 0.00 0.00
March 0.483134E+11 -0.478530E+11 0.00 0.00 744.00 0.00 -460412629.4 60.05 0.00 0.00
April 0.421874E+11 -0.417478E+11 0.00 0.00 720.00 0.00 -439679277.3 60.05 0.00 0.00
May 0.424530E+11 -0.420023E+11 0.00 0.00 744.00 0.00 -450631271.9 60.05 0.00 0.00
June 0.393092E+11 -0.388760E+11 0.00 0.00 720.00 0.00 -433183918.4 60.05 0.00 0.00
July 0.353633E+11 -0.349195E+11 0.00 0.00 744.00 0.00 -443767777.2 60.05 0.00 0.00
August 0.376925E+11 -0.372479E+11 0.00 0.00 744.00 0.00 -444598804.7 60.05 0.00 0.00
September 0.346700E+11 -0.342388E+11 0.00 0.00 720.00 0.00 -431170733.7 60.05 0.00 0.00
October 0.375115E+11 -0.370647E+11 0.00 0.00 744.00 0.00 -446871944.5 60.05 0.00 0.00
November 0.392728E+11 -0.388367E+11 0.00 0.00 720.00 0.00 -436189687.5 60.05 0.00 0.00
December 0.416785E+11 -0.412190E+11 0.00 0.00 744.00 0.00 -459453848.6 60.05 0.00 0.00
                     
Annual Sum or Average 0.484766E+12 -0.479420E+12 0.00 0.00 8760.00 0.00 -0.534515E+10 60.05 0.00 0.00
Minimum of Months 0.346700E+11 -0.478530E+11 0.00 0.00 672.00 0.00 -475521631.1 60.05 0.00 0.00
Maximum of Months 0.483134E+11 -0.342388E+11 0.00 0.00 744.00 0.00 -423664310.7 60.05 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: Environment

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME []
January 214.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 226.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 334.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 285.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 428.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 400.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 414.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 410.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 326.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 325.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 254.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 186.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average 3807.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 186.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 428.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.428249E+11 74755.51 31-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.236946E+11 85636.49 02-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.600778E+10 34681.28 06-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.125733E+10 21060.58 03-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 11409058.42 1962.85 29-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.131444E+09 8521.31 23-OCT-06:05 0.00 0.00 0.00 0.00 0.00
November 0.734678E+10 50894.37 25-NOV-18:00 0.00 0.00 0.00 0.00 0.00
December 0.187968E+11 57239.16 11-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.100071E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.428249E+11 85636.49   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 98915681.72 43244.81 30-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 73588601.21 43257.99 06-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:01 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:01 0.00 0.00 0.00 0.00 0.00
December 362137.08 1071.30 11-DEC-06:19 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.172866E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 98915681.72 43257.99   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.121303E+11 25983.43 02-JAN-05:22 0.00 0.00 0.00 0.00 0.00
February 0.771323E+10 25860.27 15-FEB-05:22 0.00 0.00 0.00 0.00 0.00
March 0.311521E+10 25869.41 06-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.818583E+09 26791.22 01-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 25903203.23 6802.47 02-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.126035E+09 25133.30 30-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.557563E+09 25854.16 28-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.309464E+10 25861.59 21-NOV-05:22 0.00 0.00 0.00 0.00 0.00
December 0.722607E+10 25868.85 22-DEC-05:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.348076E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.121303E+11 26791.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.879383E+10 22061.25 10-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.563054E+10 22060.04 15-FEB-05:02 0.00 0.00 0.00 0.00 0.00
March 0.287153E+10 22065.46 13-MAR-04:02 0.00 0.00 0.00 0.00 0.00
April 0.114434E+10 22160.97 01-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 53185181.31 7604.61 02-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 23719422.13 3017.46 02-JUN-05:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 89810.16 898.10 07-AUG-05:03 0.00 0.00 0.00 0.00 0.00
September 0.230683E+09 20313.19 30-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.835937E+09 20903.50 28-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.306134E+10 22063.59 24-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.635958E+10 22056.27 28-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.290048E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.879383E+10 22160.97   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.965714E+10 28958.18 18-JAN-05:02 0.00 0.00 0.00 0.00 0.00
February 0.592054E+10 28817.01 15-FEB-05:22 0.00 0.00 0.00 0.00 0.00
March 0.336147E+10 28828.88 16-MAR-04:02 0.00 0.00 0.00 0.00 0.00
April 0.128411E+10 29694.22 01-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.141568E+09 15732.61 02-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 32594620.43 3656.68 03-JUN-05:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.272979E+09 27244.31 30-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.820305E+09 28027.99 28-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.330504E+10 28821.34 27-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.720189E+10 28893.42 27-DEC-05:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.319976E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.965714E+10 29694.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.721799E+10 23191.66 27-JAN-05:22 0.00 0.00 0.00 0.00 0.00
February 0.410555E+10 23190.37 16-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.151991E+10 23161.71 06-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.260122E+09 23143.84 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 37960974.18 4266.54 02-MAY-05:05 0.00 0.00 0.00 0.00 0.00
June 2753760.60 1279.25 03-JUN-05:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.144621E+09 6224.30 29-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.416088E+09 21558.55 23-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.171195E+10 23190.11 27-NOV-05:12 0.00 0.00 0.00 0.00 0.00
December 0.354645E+10 23187.73 12-DEC-05:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.189634E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.721799E+10 23191.66   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.505457E+12 800793.71 30-JAN-08:65 0.00 0.00 0.00 0.00 0.00
February 0.299488E+12 908125.80 02-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.113125E+12 436206.98 23-MAR-09:23 0.00 0.00 0.00 0.00 0.00
April 0.275174E+11 680584.84 05-APR-13:27 0.00 0.00 0.00 0.00 0.00
May 0.422803E+09 358197.37 01-MAY-09:20 0.00 0.00 0.00 0.00 0.00
June 70829068.18 196086.74 01-JUN-13:13 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.686080E+09 417280.91 30-SEP-09:08 0.00 0.00 0.00 0.00 0.00
October 0.442731E+10 581631.63 13-OCT-09:59 0.00 0.00 0.00 0.00 0.00
November 0.130098E+12 601692.59 25-NOV-18:00 0.00 0.00 0.00 0.00 0.00
December 0.319095E+12 634852.68 11-DEC-08:32 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.140039E+13     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.505457E+12 908125.80   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.434782E+11 774723.36 17-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.153214E+11 772928.14 06-FEB-05:04 0.00 0.00 0.00 0.00 0.00
March 0.393458E+10 772519.81 06-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.769341E+09 768609.86 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:01 0.00 0.00 0.00 0.00 0.00
November 0.104704E+11 773708.64 24-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.180043E+11 772650.94 11-DEC-05:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.919781E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.434782E+11 774723.36   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.243737E+12 363301.42 18-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.164916E+12 361984.32 21-FEB-05:22 0.00 0.00 0.00 0.00 0.00
March 0.103859E+12 361963.23 13-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.464024E+11 360417.09 03-APR-04:23 0.00 0.00 0.00 0.00 0.00
May 0.794981E+10 317028.12 02-MAY-04:11 0.00 0.00 0.00 0.00 0.00
June 0.203547E+10 298646.29 02-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 61555791.28 35795.32 24-JUL-05:05 0.00 0.00 0.00 0.00 0.00
August 0.800599E+09 58219.85 07-AUG-05:03 0.00 0.00 0.00 0.00 0.00
September 0.137606E+11 338696.79 30-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.439926E+11 355189.03 23-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.110553E+12 361953.52 27-NOV-05:23 0.00 0.00 0.00 0.00 0.00
December 0.189925E+12 362207.08 26-DEC-05:42 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.927993E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 61555791.28 35795.32   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.243737E+12 363301.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.140270E+12 262742.50 18-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.894546E+11 262250.49 21-FEB-05:22 0.00 0.00 0.00 0.00 0.00
March 0.536732E+11 261706.69 13-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.244433E+11 260566.75 03-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.343102E+10 218936.49 02-MAY-04:11 0.00 0.00 0.00 0.00 0.00
June 0.136629E+10 206167.56 02-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 42484792.23 12888.31 24-JUL-05:07 0.00 0.00 0.00 0.00 0.00
August 0.358866E+09 41161.01 17-AUG-05:03 0.00 0.00 0.00 0.00 0.00
September 0.680789E+10 233964.93 30-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.226810E+11 245400.31 23-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.655045E+11 261699.61 27-NOV-05:23 0.00 0.00 0.00 0.00 0.00
December 0.111234E+12 262445.99 04-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.519267E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 42484792.23 12888.31   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.140270E+12 262742.50   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.167335E+12 355033.38 18-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.102538E+12 353938.37 06-FEB-06:06 0.00 0.00 0.00 0.00 0.00
March 0.696382E+11 353725.64 13-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.341735E+11 352214.70 03-APR-04:23 0.00 0.00 0.00 0.00 0.00
May 0.642367E+10 309813.06 02-MAY-04:11 0.00 0.00 0.00 0.00 0.00
June 0.204652E+10 291849.61 02-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 0.192818E+09 29986.92 24-JUL-05:06 0.00 0.00 0.00 0.00 0.00
August 0.573994E+09 38919.62 07-AUG-05:05 0.00 0.00 0.00 0.00 0.00
September 0.870763E+10 330988.57 30-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.237103E+11 347105.48 23-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.779680E+11 353716.15 27-NOV-05:23 0.00 0.00 0.00 0.00 0.00
December 0.139556E+12 353963.87 26-DEC-05:42 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.632863E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.192818E+09 29986.92   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.167335E+12 355033.38   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.144076E+12 274515.04 18-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.912476E+11 274284.72 06-FEB-05:23 0.00 0.00 0.00 0.00 0.00
March 0.592564E+11 274337.67 13-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.249597E+11 273839.53 03-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.527027E+10 228226.29 02-MAY-04:11 0.00 0.00 0.00 0.00 0.00
June 0.173264E+10 214864.14 02-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 0.114970E+09 26889.22 12-JUL-05:05 0.00 0.00 0.00 0.00 0.00
August 0.383647E+09 30263.28 07-AUG-05:07 0.00 0.00 0.00 0.00 0.00
September 0.917315E+10 243937.90 30-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.256181E+11 255891.29 23-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.665819E+11 274330.62 27-NOV-05:23 0.00 0.00 0.00 0.00 0.00
December 0.112757E+12 274413.67 04-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.541171E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.114970E+09 26889.22   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144076E+12 274515.04   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.567238E+11 72942.24 30-JAN-07:03 0.00 0.00 0.00 0.00 0.00
February 0.313747E+11 73746.22 02-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.103025E+11 49118.25 06-MAR-04:02 0.00 0.00 0.00 0.00 0.00
April 0.249679E+10 30704.65 03-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 12164715.73 4098.16 02-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.117739E+09 10995.96 29-SEP-06:05 0.00 0.00 0.00 0.00 0.00
October 0.867162E+09 20150.59 23-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.153226E+11 68120.51 25-NOV-18:00 0.00 0.00 0.00 0.00 0.00
December 0.365055E+11 68758.72 09-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.153723E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.567238E+11 73746.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.305554E+11 133043.02 17-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.206824E+11 132808.95 21-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.116090E+11 132785.03 02-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.488500E+10 132966.15 03-APR-04:04 0.00 0.00 0.00 0.00 0.00
May 0.396104E+09 109048.12 22-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 69217441.21 13736.94 03-JUN-05:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.105357E+10 124322.99 30-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.539055E+10 130809.50 23-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.140364E+11 132931.83 14-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.243162E+11 133040.72 04-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.112994E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.305554E+11 133043.02   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.346081E+11 46899.10 18-JAN-05:22 0.00 0.00 0.00 0.00 0.00
February 0.255992E+11 46846.79 05-FEB-20:42 0.00 0.00 0.00 0.00 0.00
March 0.179322E+11 46873.27 02-MAR-05:13 0.00 0.00 0.00 0.00 0.00
April 0.960648E+10 46603.55 03-APR-04:42 0.00 0.00 0.00 0.00 0.00
May 0.290381E+10 41424.42 02-MAY-04:12 0.00 0.00 0.00 0.00 0.00
June 0.107594E+10 37123.88 02-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 0.322817E+09 27939.03 24-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.789733E+09 26239.79 07-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.411785E+10 43801.08 30-SEP-04:22 0.00 0.00 0.00 0.00 0.00
October 0.100167E+11 45677.57 23-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.193277E+11 46829.17 14-NOV-05:42 0.00 0.00 0.00 0.00 0.00
December 0.292543E+11 46832.95 15-DEC-05:22 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.155555E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.322817E+09 26239.79   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.346081E+11 46899.10   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.212519E+11 30389.29 18-JAN-05:22 0.00 0.00 0.00 0.00 0.00
February 0.150176E+11 30355.39 05-FEB-20:42 0.00 0.00 0.00 0.00 0.00
March 0.989818E+10 30372.55 02-MAR-05:13 0.00 0.00 0.00 0.00 0.00
April 0.524149E+10 30197.78 03-APR-04:42 0.00 0.00 0.00 0.00 0.00
May 0.116980E+10 26841.86 02-MAY-04:12 0.00 0.00 0.00 0.00 0.00
June 0.521529E+09 24055.22 02-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 89328021.17 9719.43 24-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.256399E+09 16941.45 07-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.188470E+10 28381.86 30-SEP-04:22 0.00 0.00 0.00 0.00 0.00
October 0.524004E+10 29597.77 23-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.119019E+11 30343.98 14-NOV-05:42 0.00 0.00 0.00 0.00 0.00
December 0.182550E+11 30346.42 15-DEC-05:22 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.907277E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 89328021.17 9719.43   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.212519E+11 30389.29   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.260408E+11 46045.73 18-JAN-05:22 0.00 0.00 0.00 0.00 0.00
February 0.181131E+11 45990.25 11-FEB-05:32 0.00 0.00 0.00 0.00 0.00
March 0.132470E+11 46020.36 02-MAR-05:13 0.00 0.00 0.00 0.00 0.00
April 0.772400E+10 45755.56 03-APR-04:42 0.00 0.00 0.00 0.00 0.00
May 0.245115E+10 40670.67 02-MAY-04:12 0.00 0.00 0.00 0.00 0.00
June 0.112374E+10 36448.37 02-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 0.384021E+09 22422.68 24-JUL-05:01 0.00 0.00 0.00 0.00 0.00
August 0.653804E+09 25272.66 07-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.293681E+10 43004.08 30-SEP-04:22 0.00 0.00 0.00 0.00 0.00
October 0.645080E+10 44846.42 23-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.149263E+11 45977.07 14-NOV-05:42 0.00 0.00 0.00 0.00 0.00
December 0.229372E+11 45980.79 15-DEC-05:22 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.116989E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.384021E+09 22422.68   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.260408E+11 46045.73   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.198592E+11 30786.83 18-JAN-05:22 0.00 0.00 0.00 0.00 0.00
February 0.134409E+11 30749.75 11-FEB-05:32 0.00 0.00 0.00 0.00 0.00
March 0.907683E+10 30762.82 02-MAR-05:52 0.00 0.00 0.00 0.00 0.00
April 0.445756E+10 30592.81 03-APR-04:42 0.00 0.00 0.00 0.00 0.00
May 0.134436E+10 27193.00 02-MAY-04:12 0.00 0.00 0.00 0.00 0.00
June 0.552879E+09 24369.91 02-JUN-05:01 0.00 0.00 0.00 0.00 0.00
July 0.125298E+09 4210.16 11-JUL-05:04 0.00 0.00 0.00 0.00 0.00
August 0.264723E+09 15082.71 07-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.202630E+10 28753.15 30-SEP-04:22 0.00 0.00 0.00 0.00 0.00
October 0.476531E+10 29984.97 23-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.103145E+11 30740.93 14-NOV-05:42 0.00 0.00 0.00 0.00 0.00
December 0.160967E+11 30743.40 15-DEC-05:22 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.823246E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.125298E+09 4210.16   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.198592E+11 30786.83   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.703058E+10 181024.17 31-JAN-07:30 0.00 0.00 0.00 0.00 0.00
February 0.119773E+11 187251.84 02-FEB-07:27 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:01 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:01 0.00 0.00 0.00 0.00 0.00
December 0.550974E+09 19780.58 11-DEC-21:51 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.195589E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.119773E+11 187251.84   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:01 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:01 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:01 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:01 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:01 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:01 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:01 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:01 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 3659.99 3659.99 0.52 08-JAN-02:03 0.52 0.00
February 0.00 0.00 183693.85 183693.85 2221.65 10-FEB-17:01 2221.65 0.00
March 0.00 0.00 0.883886E+09 0.883886E+09 39800.80 19-MAR-13:21 39800.80 0.00
April 0.00 0.00 0.164551E+11 0.151966E+11 167381.03 16-APR-14:51 122251.95 0.08
May 0.00 0.00 0.369068E+11 0.335970E+11 145765.81 31-MAY-15:00 134178.08 0.27
June 0.00 0.00 0.103571E+12 0.882616E+11 227806.42 26-JUN-04:11 172318.52 0.51
July 0.00 0.00 0.150557E+12 0.119646E+12 208762.35 27-JUL-05:03 77323.24 0.64
August 0.00 0.00 0.151392E+12 0.121754E+12 231607.67 03-AUG-05:02 161003.15 0.62
September 0.00 0.00 0.575551E+11 0.550442E+11 175118.89 11-SEP-04:11 105109.56 0.27
October 0.00 0.00 0.518290E+10 0.518290E+10 107946.67 20-OCT-15:00 107946.67 0.03
November 0.00 0.00 0.335923E+09 0.335535E+09 48686.93 09-NOV-06:02 42227.79 0.00
December 0.00 0.00 166115.13 166115.13 750.52 01-DEC-17:03 750.52 0.00
                 
Annual Sum or Average 0.00 0.00 0.522840E+12 0.439902E+12       0.20
Minimum of Months 0.00 0.00 3659.99 3659.99 0.52   0.52 0.00
Maximum of Months 0.00 0.00 0.151392E+12 0.121754E+12 231607.67   172318.52 0.64



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 127639.66 127639.66 5.36 01-JAN-16:43 5.36 0.00
February 0.00 0.00 554628.57 554628.57 7452.31 24-FEB-10:01 7452.31 0.00
March 0.00 0.00 0.136351E+11 0.136351E+11 642619.62 24-MAR-14:01 642619.62 0.00
April 0.00 0.00 0.147229E+12 0.134721E+12 1498924.52 18-APR-14:05 1257048.60 0.07
May 0.00 0.00 0.357255E+12 0.325491E+12 1403143.10 31-MAY-14:05 1279931.93 0.27
June 0.00 0.00 0.953554E+12 0.802116E+12 2146880.78 13-JUN-05:01 866109.57 0.50
July 0.00 0.00 0.128437E+13 0.100749E+13 2047954.22 27-JUL-05:03 758011.47 0.59
August 0.00 0.00 0.124624E+13 0.985155E+12 2598503.78 03-AUG-05:02 1586144.32 0.57
September 0.00 0.00 0.525828E+12 0.504184E+12 1595941.38 06-SEP-14:05 1423082.45 0.27
October 0.00 0.00 0.600434E+11 0.600434E+11 981527.99 20-OCT-15:00 981527.99 0.03
November 0.00 0.00 0.627949E+10 0.627949E+10 734801.32 03-NOV-14:02 734801.32 0.00
December 0.00 0.00 114693.28 114693.28 5.59 02-DEC-16:07 5.59 0.00
                 
Annual Sum or Average 0.00 0.00 0.459444E+13 0.383911E+13       0.19
Minimum of Months 0.00 0.00 114693.28 114693.28 5.36   5.36 0.00
Maximum of Months 0.00 0.00 0.128437E+13 0.100749E+13 2598503.78   1586144.32 0.59



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 3783396.36 3783396.36 3347.61 02-JAN-06:01 3347.61 0.00
February 0.00 0.00 3968659.65 3968659.65 8640.76 06-FEB-06:12 8640.76 0.00
March 0.00 0.00 0.633974E+09 0.633974E+09 28778.33 25-MAR-14:57 28778.33 0.00
April 0.00 0.00 0.160024E+11 0.148713E+11 183505.27 16-APR-16:21 135094.35 0.07
May 0.00 0.00 0.391425E+11 0.364163E+11 173833.49 31-MAY-15:00 163358.85 0.26
June 0.00 0.00 0.108946E+12 0.943255E+11 291819.28 25-JUN-15:01 219349.98 0.48
July 0.00 0.00 0.144089E+12 0.117918E+12 284430.01 20-JUL-05:02 102823.58 0.58
August 0.00 0.00 0.137558E+12 0.112298E+12 352989.54 03-AUG-04:01 190698.39 0.55
September 0.00 0.00 0.565082E+11 0.547364E+11 218712.19 11-SEP-05:02 116165.49 0.26
October 0.00 0.00 0.432015E+10 0.432015E+10 101476.74 20-OCT-15:00 101476.74 0.03
November 0.00 0.00 0.146621E+09 0.146621E+09 12066.10 03-NOV-14:45 12066.10 0.00
December 0.00 0.00 13278601.60 13278601.60 7464.80 09-DEC-06:12 7464.80 0.00
                 
Annual Sum or Average 0.00 0.00 0.507367E+12 0.435687E+12       0.19
Minimum of Months 0.00 0.00 3783396.36 3783396.36 3347.61   3347.61 0.00
Maximum of Months 0.00 0.00 0.144089E+12 0.117918E+12 352989.54   219349.98 0.58



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 91396726.16 91396726.16 57352.63 14-JAN-06:06 57352.63 0.00
February 0.00 0.00 0.141126E+09 0.141126E+09 71888.09 24-FEB-06:02 71888.09 0.00
March 0.00 0.00 0.159179E+10 0.159179E+10 111024.43 27-MAR-04:02 111024.43 0.00
April 0.00 0.00 0.839460E+10 0.729454E+10 101866.56 19-APR-05:00 101866.56 0.06
May 0.00 0.00 0.265414E+11 0.205393E+11 109014.91 11-MAY-15:55 43000.35 0.24
June 0.00 0.00 0.584613E+11 0.427109E+11 156178.16 27-JUN-04:51 64644.94 0.46
July 0.00 0.00 0.797603E+11 0.537192E+11 141753.47 06-JUL-04:53 56893.46 0.51
August 0.00 0.00 0.866746E+11 0.604414E+11 147078.68 21-AUG-03:50 113358.76 0.54
September 0.00 0.00 0.406882E+11 0.358761E+11 132418.92 04-SEP-16:49 132418.92 0.27
October 0.00 0.00 0.130509E+11 0.127358E+11 133113.02 13-OCT-03:13 133113.02 0.05
November 0.00 0.00 0.524580E+10 0.511697E+10 110622.20 22-NOV-05:46 110622.20 0.02
December 0.00 0.00 0.626302E+09 0.626302E+09 111808.05 06-DEC-06:00 111808.05 0.00
                 
Annual Sum or Average 0.00 0.00 0.321268E+12 0.240885E+12       0.18
Minimum of Months 0.00 0.00 91396726.16 91396726.16 57352.63   43000.35 0.00
Maximum of Months 0.00 0.00 0.866746E+11 0.604414E+11 156178.16   133113.02 0.54



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 3673730.69 3673730.69 59.12 07-JAN-21:52 59.12 0.00
February 0.00 0.00 0.157489E+12 0.157489E+12 319619.24 03-FEB-19:01 319619.24 0.00
March 0.00 0.00 0.234796E+12 0.234796E+12 323587.96 06-MAR-14:22 323587.96 0.01
April 0.00 0.00 0.266969E+12 0.266155E+12 524759.64 18-APR-08:35 383175.16 0.12
May 0.00 0.00 0.257935E+11 0.257935E+11 232181.06 31-MAY-23:53 232181.06 0.25
June 0.00 0.00 0.332473E+12 0.284726E+12 546139.23 13-JUN-06:52 196184.47 0.69
July 0.00 0.00 0.466481E+12 0.427794E+12 517195.35 06-JUL-05:51 203815.29 0.99
August 0.00 0.00 0.610095E+12 0.548152E+12 560533.96 31-AUG-12:03 391240.52 0.94
September 0.00 0.00 0.564076E+11 0.564076E+11 266531.88 30-SEP-23:21 266531.88 0.37
October 0.00 0.00 0.168013E+12 0.167061E+12 344387.31 20-OCT-16:13 344387.31 0.05
November 0.00 0.00 0.204747E+12 0.204462E+12 326592.57 01-NOV-00:22 326592.57 0.07
December 0.00 0.00 0.255899E+12 0.255899E+12 260591.73 19-DEC-06:10 260591.73 0.00
                 
Annual Sum or Average 0.00 0.00 0.277917E+13 0.262874E+13       0.29
Minimum of Months 0.00 0.00 3673730.69 3673730.69 59.12   59.12 0.00
Maximum of Months 0.00 0.00 0.610095E+12 0.548152E+12 560533.96   391240.52 0.99



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.344206E+10 0.344206E+10 8799.44 30-JAN-13:01 8799.44 0.00
February 0.00 0.00 0.766102E+10 0.766102E+10 13114.04 04-FEB-10:31 13114.04 0.00
March 0.00 0.00 0.158367E+11 0.158364E+11 7978.41 31-MAR-23:47 7978.41 0.00
April 0.00 0.00 0.211777E+11 0.211511E+11 9692.42 16-APR-17:53 9688.97 0.00
May 0.00 0.00 0.754346E+10 0.744951E+10 4855.11 31-MAY-23:20 4804.62 0.00
June 0.00 0.00 0.128432E+11 0.126384E+11 6732.73 30-JUN-23:51 6729.52 0.00
July 0.00 0.00 0.187805E+11 0.184692E+11 8677.40 31-JUL-24:00 8614.48 0.00
August 0.00 0.00 0.237950E+11 0.234714E+11 10140.29 04-AUG-16:00 9576.08 0.00
September 0.00 0.00 0.751511E+10 0.745684E+10 4203.39 30-SEP-23:51 4203.39 0.00
October 0.00 0.00 0.116843E+11 0.116785E+11 6090.18 31-OCT-23:52 6090.18 0.00
November 0.00 0.00 0.152345E+11 0.152251E+11 13741.04 26-NOV-08:11 13741.04 0.00
December 0.00 0.00 0.198902E+11 0.198902E+11 8700.57 01-DEC-16:08 8700.57 0.00
                 
Annual Sum or Average 0.00 0.00 0.165404E+12 0.164370E+12       0.00
Minimum of Months 0.00 0.00 0.344206E+10 0.344206E+10 4203.39   4203.39 0.00
Maximum of Months 0.00 0.00 0.237950E+11 0.234714E+11 13741.04   13741.04 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.137109E+11 0.137109E+11 28259.09 19-JAN-12:02 28259.09 0.00
February 0.00 0.00 0.584684E+11 0.584684E+11 124749.76 04-FEB-10:31 124749.76 0.00
March 0.00 0.00 0.137715E+12 0.137713E+12 72721.72 31-MAR-23:12 72721.72 0.00
April 0.00 0.00 0.193661E+12 0.193398E+12 92202.27 18-APR-15:40 88746.63 0.00
May 0.00 0.00 0.659448E+11 0.650156E+11 46230.13 31-MAY-23:20 45714.33 0.00
June 0.00 0.00 0.119865E+12 0.117826E+12 65168.77 30-JUN-23:02 64917.61 0.00
July 0.00 0.00 0.176618E+12 0.173516E+12 81417.47 31-JUL-23:50 80833.42 0.00
August 0.00 0.00 0.223708E+12 0.220487E+12 97185.12 04-AUG-16:00 91546.37 0.00
September 0.00 0.00 0.644457E+11 0.638693E+11 39444.16 06-SEP-17:30 37407.11 0.00
October 0.00 0.00 0.994194E+11 0.993606E+11 54222.79 31-OCT-23:13 54222.79 0.00
November 0.00 0.00 0.127347E+12 0.127253E+12 129138.08 26-NOV-08:11 129138.08 0.00
December 0.00 0.00 0.167225E+12 0.167225E+12 80742.34 01-DEC-16:08 80742.34 0.00
                 
Annual Sum or Average 0.00 0.00 0.144813E+13 0.143784E+13       0.00
Minimum of Months 0.00 0.00 0.137109E+11 0.137109E+11 28259.09   28259.09 0.00
Maximum of Months 0.00 0.00 0.223708E+12 0.220487E+12 129138.08   129138.08 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.655072E+09 0.655072E+09 2483.49 12-JAN-16:30 2483.49 0.00
February 0.00 0.00 0.429078E+10 0.429078E+10 10507.25 04-FEB-10:31 10507.25 0.00
March 0.00 0.00 0.120082E+11 0.120079E+11 6655.90 23-MAR-17:00 6655.90 0.00
April 0.00 0.00 0.180343E+11 0.180086E+11 9429.27 18-APR-15:40 9082.38 0.00
May 0.00 0.00 0.586428E+10 0.577173E+10 4549.17 31-MAY-23:10 4490.55 0.00
June 0.00 0.00 0.116630E+11 0.114590E+11 6460.26 30-JUN-23:02 6434.64 0.00
July 0.00 0.00 0.174722E+11 0.171622E+11 8001.66 03-JUL-16:00 7453.32 0.00
August 0.00 0.00 0.220767E+11 0.217559E+11 9970.97 04-AUG-16:00 9406.98 0.00
September 0.00 0.00 0.555530E+10 0.549774E+10 4119.97 06-SEP-17:30 3915.41 0.00
October 0.00 0.00 0.798918E+10 0.798339E+10 5382.91 11-OCT-16:50 5382.91 0.00
November 0.00 0.00 0.107505E+11 0.107413E+11 12894.34 26-NOV-08:11 12894.34 0.00
December 0.00 0.00 0.146601E+11 0.146601E+11 7851.66 01-DEC-16:08 7851.66 0.00
                 
Annual Sum or Average 0.00 0.00 0.131020E+12 0.129993E+12       0.00
Minimum of Months 0.00 0.00 0.655072E+09 0.655072E+09 2483.49   2483.49 0.00
Maximum of Months 0.00 0.00 0.220767E+11 0.217559E+11 12894.34   12894.34 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 564661.18 4543504.69 02-JAN-04:01
February 0.00 0.00 01-FEB-00:01 388960.08 3940492.96 21-FEB-05:01
March 0.00 0.00 01-MAR-00:01 182799.26 3505456.42 25-MAR-04:01
April 0.00 0.00 01-APR-00:03 75772.34 3657453.71 01-APR-04:01
May 0.00 0.00 01-MAY-00:10 11914.64 3267873.93 02-MAY-04:11
June 0.00 0.00 01-JUN-00:10 4097.77 2871209.72 02-JUN-05:01
July 0.00 0.00 01-JUL-00:05 497.14 208703.21 24-JUL-05:01
August 0.00 0.00 01-AUG-00:10 1517.78 388786.70 07-AUG-05:02
September 0.00 0.00 01-SEP-00:10 20020.19 3359021.90 30-SEP-04:01
October 0.00 0.00 01-OCT-00:01 58022.95 3615852.69 16-OCT-04:11
November 0.00 0.00 01-NOV-00:01 217025.88 3718956.36 28-NOV-05:01
December 0.00 0.00 01-DEC-00:01 401527.92 3831784.04 18-DEC-05:01
             
Annual Sum or Average 0.00     159582.29    
Minimum of Months 0.00 0.00   497.14 208703.21  
Maximum of Months 0.00 0.00   564661.18 4543504.69  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 1633.21 93930.42 13-JAN-22:03 120702.01 990083.28 08-JAN-01:51
February 69083.89 1006999.74 24-FEB-19:02 179153.81 878222.57 11-FEB-10:02
March 103318.12 1115196.33 23-MAR-13:32 17456.60 814262.15 08-MAR-03:20
April 189422.26 2508654.79 18-APR-09:20 10974.05 760177.81 21-APR-16:11
May 192958.06 2533250.25 30-MAY-14:05 219451.16 990007.34 19-MAY-19:35
June 633333.46 3582745.10 30-JUN-04:14 54308.92 948925.92 05-JUN-07:55
July 842719.57 3525966.26 27-JUL-04:14 13396.54 521685.60 27-JUL-21:04
August 883728.97 4143317.39 03-AUG-05:03 7909.91 486574.19 01-AUG-04:47
September 300200.79 2668633.37 07-SEP-12:05 245613.49 989936.58 03-SEP-06:30
October 97908.14 1542457.23 20-OCT-13:00 200567.06 946547.60 11-OCT-10:13
November 94824.94 1224521.95 03-NOV-11:15 7993.43 795591.49 01-NOV-04:11
December 106771.77 883464.89 05-DEC-13:38 6266.82 686295.36 01-DEC-16:33
             
Annual Sum or Average 294706.76     89702.07    
Minimum of Months 1633.21 93930.42   6266.82 486574.19  
Maximum of Months 883728.97 4143317.39   245613.49 990083.28  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 16.43 33766.92 17-JAN-06:01 0.00 0.00 01-JAN-00:02
February 75611.05 381934.94 10-FEB-15:46 0.00 0.00 01-FEB-00:01
March 174412.00 1215698.81 23-MAR-14:02 0.00 0.00 01-MAR-00:01
April 289211.58 3516114.63 16-APR-16:21 0.00 0.00 01-APR-00:03
May 216149.69 2668505.21 12-MAY-05:02 0.00 0.00 01-MAY-00:10
June 660012.06 5526759.29 30-JUN-04:11 0.00 0.00 01-JUN-00:10
July 880525.14 5383535.62 15-JUL-04:11 0.00 0.00 01-JUL-00:05
August 925329.86 4897302.16 03-AUG-05:02 0.00 0.00 01-AUG-00:10
September 316793.62 4261817.37 11-SEP-04:11 0.00 0.00 01-SEP-00:10
October 120833.24 1559126.99 20-OCT-13:00 0.00 0.00 01-OCT-00:01
November 199365.22 1368941.36 03-NOV-13:38 0.00 0.00 01-NOV-00:01
December 220497.65 557086.98 09-DEC-06:01 0.00 0.00 01-DEC-00:01
             
Annual Sum or Average 341778.82     0.00    
Minimum of Months 16.43 33766.92   0.00 0.00  
Maximum of Months 925329.86 5526759.29   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 16465.26 59153.19 31-JAN-12:13
February 0.00 0.00 01-FEB-00:01 16894.76 59537.17 21-FEB-12:30
March 0.00 0.00 01-MAR-00:01 17777.98 59447.59 01-MAR-12:32
April 0.00 0.00 01-APR-00:03 16020.56 57772.50 03-APR-11:58
May 0.00 0.00 01-MAY-00:10 15596.57 55044.03 01-MAY-11:20
June 0.00 0.00 01-JUN-00:10 14913.99 51404.97 01-JUN-11:24
July 0.00 0.00 01-JUL-00:05 12955.52 48011.55 03-JUL-12:00
August 0.00 0.00 01-AUG-00:10 13823.67 46092.31 01-AUG-11:20
September 0.00 0.00 01-SEP-00:10 13127.28 47180.36 29-SEP-11:42
October 0.00 0.00 01-OCT-00:01 13755.39 50236.14 31-OCT-11:27
November 0.00 0.00 01-NOV-00:01 14898.82 53759.55 30-NOV-12:45
December 0.00 0.00 01-DEC-00:01 15304.54 56889.92 29-DEC-12:13
             
Annual Sum or Average 0.00     15117.59    
Minimum of Months 0.00 0.00   12955.52 46092.31  
Maximum of Months 0.00 0.00   17777.98 59537.17  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 210.60 35220.19 14-JAN-00:20 4327.11 196715.69 05-JAN-02:37
February 23609.35 735973.34 15-FEB-05:55 224.44 88544.08 08-FEB-12:59
March 57738.26 1132062.74 23-MAR-13:34 4967.55 158151.20 19-MAR-04:07
April 201500.29 4899639.69 18-APR-15:00 6962.58 183980.89 08-APR-00:50
May 264931.65 4607326.93 31-MAY-14:05 1151.21 153115.92 19-MAY-04:18
June 1090518.49 6700354.07 13-JUN-15:00 19.66 31907.91 15-JUN-05:50
July 1520822.83 9129450.82 26-JUL-15:00 70.49 42948.55 24-JUL-05:30
August 1595140.11 10278537.72 04-AUG-13:00 212.28 64343.31 07-AUG-02:13
September 410218.01 5387904.16 11-SEP-12:05 1203.76 175805.81 29-SEP-23:20
October 114693.73 1768402.04 20-OCT-13:00 167.43 76074.69 16-OCT-06:00
November 30228.53 1384260.22 03-NOV-13:40 7092.48 132003.10 14-NOV-23:10
December 18365.93 769891.28 05-DEC-16:08 13436.85 221022.84 13-DEC-16:20
             
Annual Sum or Average 447572.65     3339.61    
Minimum of Months 210.60 35220.19   19.66 31907.91  
Maximum of Months 1595140.11 10278537.72   13436.85 221022.84  



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.849530E+10 0.58 11715.34 30-JAN-06:01 1.31
February 0.787170E+10 0.58 22232.95 10-FEB-06:01 1.71
March 0.977607E+10 0.59 22232.95 23-MAR-05:01 1.71
April 0.113128E+11 0.63 22232.95 01-APR-05:01 1.72
May 0.123024E+11 0.65 18478.75 01-MAY-04:11 1.58
June 0.156374E+11 0.73 27529.67 30-JUN-04:11 1.86
July 0.176843E+11 0.77 24972.57 26-JUL-04:11 1.78
August 0.196492E+11 0.82 23749.51 04-AUG-14:40 1.74
September 0.133602E+11 0.67 25962.87 11-SEP-04:11 1.81
October 0.109151E+11 0.58 22232.95 24-OCT-05:01 1.72
November 0.965274E+10 0.58 21601.34 16-NOV-06:01 1.69
December 0.903797E+10 0.57 11295.92 05-DEC-13:23 1.29
           
Annual Sum or Average 0.145695E+12 0.65      
Minimum of Months 0.787170E+10 0.57 11295.92   1.29
Maximum of Months 0.196492E+11 0.82 27529.67   1.86



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.123066E+12 0.82 133008.57 09-JAN-05:22 1.42
February 0.991788E+11 0.73 133008.57 06-FEB-05:01 1.42
March 0.101410E+12 0.65 255468.51 24-MAR-05:01 1.87
April 0.102048E+12 0.62 192180.67 13-APR-05:03 1.65
May 0.117718E+12 0.64 192013.38 04-MAY-05:02 1.65
June 0.142969E+12 0.72 255468.51 02-JUN-05:01 1.86
July 0.145323E+12 0.70 208088.18 05-JUL-04:11 1.69
August 0.153102E+12 0.73 227024.03 03-AUG-05:02 1.76
September 0.123383E+12 0.66 255468.51 23-SEP-05:01 1.87
October 0.955314E+11 0.57 255468.51 05-OCT-05:01 1.86
November 0.984552E+11 0.65 235463.22 02-NOV-05:01 1.80
December 0.108510E+12 0.72 133008.57 19-DEC-06:01 1.42
           
Annual Sum or Average 0.141069E+13 0.68      
Minimum of Months 0.955314E+11 0.57 133008.57   1.42
Maximum of Months 0.153102E+12 0.82 255468.51   1.87



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.130552E+11 0.69 13022.49 02-JAN-04:01 1.11
February 0.113416E+11 0.66 13022.49 01-FEB-04:11 1.12
March 0.109998E+11 0.58 13022.49 01-MAR-05:01 1.12
April 0.983466E+10 0.52 14474.26 18-APR-15:00 1.15
May 0.100066E+11 0.49 19057.14 31-MAY-05:02 1.29
June 0.119640E+11 0.53 20521.45 12-JUN-05:01 1.33
July 0.120765E+11 0.52 20314.85 03-JUL-05:02 1.33
August 0.123579E+11 0.53 19823.38 03-AUG-05:02 1.31
September 0.998335E+10 0.48 19057.14 11-SEP-05:02 1.29
October 0.914583E+10 0.48 13022.49 02-OCT-05:01 1.11
November 0.110954E+11 0.60 13022.49 01-NOV-05:01 1.11
December 0.127432E+11 0.67 13022.49 01-DEC-05:01 1.11
           
Annual Sum or Average 0.134604E+12 0.56      
Minimum of Months 0.914583E+10 0.48 13022.49   1.11
Maximum of Months 0.130552E+11 0.69 20521.45   1.33



Table of Contents

Report: FanReportMonthly

For: CAV_BAS SZVAV FAN

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.290654E+10 0.42 15902.51 02-JAN-06:01 1.88
February 0.332259E+10 0.45 15902.51 01-FEB-07:07 1.90
March 0.391644E+10 0.48 15902.51 03-MAR-06:01 1.89
April 0.457866E+10 0.48 15902.51 01-APR-05:01 1.89
May 0.606045E+10 0.53 15902.51 01-MAY-05:02 1.89
June 0.619596E+10 0.58 15902.51 01-JUN-04:11 1.88
July 0.717946E+10 0.58 15902.51 01-JUL-04:11 1.87
August 0.907025E+10 0.68 15902.51 01-AUG-04:11 1.87
September 0.853330E+10 0.64 15902.51 01-SEP-04:11 1.88
October 0.808937E+10 0.58 15902.51 02-OCT-04:11 1.88
November 0.598694E+10 0.53 15902.51 01-NOV-04:11 1.89
December 0.308257E+10 0.42 15902.51 01-DEC-06:01 1.89
           
Annual Sum or Average 0.689225E+11 0.53      
Minimum of Months 0.290654E+10 0.42 15902.51   1.87
Maximum of Months 0.907025E+10 0.68 15902.51   1.90



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SYS11 FAN

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.274029E+11 0.53 10231.07 01-JAN-00:02 0.53
February 0.442613E+11 0.65 34075.71 01-FEB-00:03 0.89
March 0.620295E+11 0.73 34075.71 01-MAR-00:01 0.89
April 0.863382E+11 0.88 34075.71 01-APR-00:03 0.89
May 0.274072E+11 0.53 34075.71 31-MAY-23:53 0.89
June 0.387261E+11 0.60 34075.71 01-JUN-00:12 0.89
July 0.618888E+11 0.73 34075.71 01-JUL-00:05 0.88
August 0.821546E+11 0.84 34075.71 01-AUG-00:10 0.88
September 0.265475E+11 0.53 34075.71 30-SEP-23:03 0.89
October 0.477042E+11 0.65 34075.71 01-OCT-00:02 0.89
November 0.592467E+11 0.72 34075.71 01-NOV-00:01 0.89
December 0.905581E+11 0.89 34075.71 01-DEC-00:02 0.89
           
Annual Sum or Average 0.654265E+12 0.69      
Minimum of Months 0.265475E+11 0.53 10231.07   0.53
Maximum of Months 0.905581E+11 0.89 34075.71   0.89



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.364211E+10 1.48 1359.81 01-JAN-19:27 1.48
February 0.328965E+10 1.48 1359.81 04-FEB-12:51 1.49
March 0.364211E+10 1.48 1359.81 01-MAR-00:36 1.49
April 0.352462E+10 1.47 1359.81 02-APR-06:10 1.48
May 0.364211E+10 1.47 1359.81 02-MAY-14:03 1.47
June 0.352462E+10 1.47 1359.81 01-JUN-00:12 1.47
July 0.364211E+10 1.47 1359.81 02-JUL-17:58 1.47
August 0.364211E+10 1.47 1359.81 01-AUG-05:00 1.47
September 0.352462E+10 1.47 1359.81 02-SEP-12:50 1.47
October 0.364211E+10 1.47 1359.81 31-OCT-23:18 1.48
November 0.352462E+10 1.48 1359.81 02-NOV-09:43 1.47
December 0.364211E+10 1.48 1359.81 01-DEC-00:04 1.48
           
Annual Sum or Average 0.428829E+11 1.47      
Minimum of Months 0.328965E+10 1.47 1359.81   1.47
Maximum of Months 0.364211E+10 1.48 1359.81   1.49



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.350442E+11 1.48 13084.00 03-JAN-00:23 1.48
February 0.316528E+11 1.48 13084.00 07-FEB-06:14 1.48
March 0.350442E+11 1.48 13084.00 21-MAR-17:41 1.48
April 0.339137E+11 1.47 13084.00 01-APR-02:13 1.48
May 0.350442E+11 1.47 13084.00 06-MAY-05:04 1.47
June 0.339137E+11 1.47 13084.00 01-JUN-01:15 1.47
July 0.350442E+11 1.47 13084.00 01-JUL-01:08 1.47
August 0.350442E+11 1.47 13084.00 01-AUG-04:05 1.47
September 0.339137E+11 1.47 13084.00 21-SEP-01:20 1.47
October 0.350442E+11 1.47 13084.00 01-OCT-03:11 1.48
November 0.339137E+11 1.48 13084.00 01-NOV-00:43 1.48
December 0.350442E+11 1.48 13084.00 04-DEC-22:02 1.48
           
Annual Sum or Average 0.412617E+12 1.47      
Minimum of Months 0.316528E+11 1.47 13084.00   1.47
Maximum of Months 0.350442E+11 1.48 13084.00   1.48



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.360801E+10 1.48 1347.08 02-JAN-11:03 1.48
February 0.325885E+10 1.48 1347.08 01-FEB-00:11 1.48
March 0.360801E+10 1.48 1347.08 01-MAR-08:39 1.48
April 0.349162E+10 1.47 1347.08 01-APR-01:13 1.48
May 0.360801E+10 1.47 1347.08 01-MAY-02:50 1.47
June 0.349162E+10 1.47 1347.08 01-JUN-00:14 1.47
July 0.360801E+10 1.47 1347.08 01-JUL-01:15 1.47
August 0.360801E+10 1.47 1347.08 01-AUG-04:13 1.47
September 0.349162E+10 1.47 1347.08 01-SEP-02:50 1.47
October 0.360801E+10 1.47 1347.08 01-OCT-00:51 1.48
November 0.349162E+10 1.48 1347.08 01-NOV-01:51 1.48
December 0.360801E+10 1.48 1347.08 01-DEC-00:08 1.48
           
Annual Sum or Average 0.424814E+11 1.47      
Minimum of Months 0.325885E+10 1.47 1347.08   1.47
Maximum of Months 0.360801E+10 1.48 1347.08   1.48



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.155670E+10 0.140103E+10 6507.74 09-JAN-05:21 5856.97 5856.97 55.16 28.32
February 0.978374E+09 0.880536E+09 6463.18 07-FEB-06:01 5816.86 5816.86 47.95 28.30
March 0.447945E+09 0.403151E+09 5954.41 01-MAR-06:01 5358.97 5358.97 49.07 26.99
April 0.179880E+09 0.161892E+09 5422.51 03-APR-05:01 4880.26 4880.26 53.93 25.47
May 31035083.40 27931575.06 3365.69 02-MAY-04:11 3029.12 3029.12 30.95 18.60
June 10179177.79 9161260.01 3366.43 02-JUN-05:01 3029.79 3029.79 31.47 18.60
July 1211034.98 1089931.48 187.71 24-JUL-05:01 168.94 168.94 20.30 1.10
August 3740351.52 3366316.37 352.10 07-AUG-05:02 316.89 316.89 22.26 2.09
September 50359362.30 45323426.07 4130.60 30-SEP-05:01 3717.54 3717.54 44.90 21.45
October 0.152173E+09 0.136956E+09 4182.09 23-OCT-05:01 3763.88 3763.88 44.45 21.63
November 0.543483E+09 0.489135E+09 6453.39 20-NOV-06:01 5808.05 5808.05 46.02 28.30
December 0.102887E+10 0.925981E+09 6382.70 18-DEC-05:02 5744.43 5744.43 52.67 28.04
                 
Annual Sum or Average 0.498395E+10 0.448556E+10            
Minimum of Months 1211034.98 1089931.48 187.71   168.94 168.94 20.30 1.10
Maximum of Months 0.155670E+10 0.140103E+10 6507.74   5856.97 5856.97 55.16 28.32



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 1282061.06 1153854.95 580.86 02-JAN-06:01 522.78 522.78 6.70 5.01
February 0.139359E+10 0.125423E+10 2380.22 25-FEB-06:02 2142.20 2142.20 7.94 21.25
March 0.259852E+10 0.233867E+10 4183.24 24-MAR-13:12 3764.92 3764.92 9.76 37.22
April 0.308316E+10 0.277485E+10 14627.14 16-APR-16:21 13164.42 13164.42 9.10 96.87
May 0.174028E+10 0.156626E+10 13035.50 31-MAY-05:02 11731.95 11731.95 9.42 90.48
June 0.515959E+10 0.464363E+10 27182.16 29-JUN-05:01 24463.95 24463.95 9.90 133.45
July 0.674305E+10 0.606874E+10 27320.02 26-JUL-04:11 24588.01 24588.01 10.48 133.76
August 0.733352E+10 0.660017E+10 26324.52 03-AUG-05:02 23692.07 23692.07 8.22 131.47
September 0.246054E+10 0.221449E+10 21545.23 11-SEP-05:02 19390.71 19390.71 10.01 119.27
October 0.196402E+10 0.176761E+10 6446.90 20-OCT-13:08 5802.21 5802.21 6.73 54.79
November 0.261999E+10 0.235799E+10 6556.92 03-NOV-11:12 5901.23 5901.23 9.82 55.55
December 0.283995E+10 0.255595E+10 2380.44 01-DEC-15:48 2142.39 2142.39 10.06 21.25
                 
Annual Sum or Average 0.379375E+11 0.341437E+11            
Minimum of Months 1282061.06 1153854.95 580.86   522.78 522.78 6.70 5.01
Maximum of Months 0.733352E+10 0.660017E+10 27320.02   24588.01 24588.01 10.48 133.76



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER1 PUMP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.482147E+10 0.433933E+10 12898.32 01-JAN-00:03 11608.49 11608.49 6.73 67.80
February 0.964189E+10 0.867770E+10 12898.32 01-FEB-00:03 11608.49 11608.49 6.84 67.80
March 0.262159E+11 0.235943E+11 12898.32 01-MAR-00:03 11608.49 11608.49 7.72 67.80
April 0.276679E+11 0.249011E+11 12898.32 01-APR-00:03 11608.49 11608.49 10.33 67.80
May 0.140982E+11 0.126884E+11 12898.32 01-MAY-04:14 11608.49 11608.49 9.81 67.80
June 0.227881E+11 0.205093E+11 12898.32 01-JUN-00:15 11608.49 11608.49 9.02 67.80
July 0.305382E+11 0.274844E+11 12898.32 01-JUL-00:11 11608.49 11608.49 9.82 67.80
August 0.321565E+11 0.289408E+11 12898.32 01-AUG-00:10 11608.49 11608.49 10.21 67.80
September 0.144757E+11 0.130281E+11 12898.32 01-SEP-00:10 11608.49 11608.49 7.95 67.80
October 0.114092E+11 0.102683E+11 12898.32 01-OCT-00:04 11608.49 11608.49 7.66 67.80
November 0.302792E+11 0.272513E+11 12898.32 01-NOV-00:03 11608.49 11608.49 7.69 67.80
December 0.301693E+11 0.271523E+11 12898.32 01-DEC-00:01 11608.49 11608.49 10.21 67.80
                 
Annual Sum or Average 0.254262E+12 0.228835E+12            
Minimum of Months 0.482147E+10 0.433933E+10 12898.32   11608.49 11608.49 6.73 67.80
Maximum of Months 0.321565E+11 0.289408E+11 12898.32   11608.49 11608.49 10.33 67.80



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER2 PUMP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.00 0.00 0.00 01-JAN-00:02 0.00 0.00 6.72 0.00
February 0.00 0.00 0.00 01-FEB-00:01 0.00 0.00 6.73 0.00
March 0.00 0.00 0.00 01-MAR-00:01 0.00 0.00 7.59 0.00
April 0.421775E+09 0.379598E+09 12898.32 14-APR-14:30 11608.49 11608.49 13.31 33.90
May 0.406297E+09 0.365667E+09 12898.32 30-MAY-10:40 11608.49 11608.49 13.15 33.90
June 0.326680E+10 0.294012E+10 12898.32 09-JUN-10:00 11608.49 11608.49 13.24 33.90
July 0.611469E+10 0.550322E+10 12898.32 03-JUL-07:40 11608.49 11608.49 13.44 33.90
August 0.676517E+10 0.608865E+10 12898.32 01-AUG-07:15 11608.49 11608.49 13.30 33.90
September 0.114537E+10 0.103083E+10 12898.32 01-SEP-14:05 11608.49 11608.49 10.25 67.80
October 0.00 0.00 0.00 01-OCT-00:01 0.00 0.00 7.57 0.00
November 0.00 0.00 0.00 01-NOV-00:01 0.00 0.00 7.66 0.00
December 0.00 0.00 0.00 01-DEC-00:01 0.00 0.00 10.21 0.00
                 
Annual Sum or Average 0.181201E+11 0.163081E+11            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 6.72 0.00
Maximum of Months 0.676517E+10 0.608865E+10 12898.32   11608.49 11608.49 13.44 67.80



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.112905E+09 33871561.48 56.21 01-JAN-06:03 16.86 16.86 56.83 0.44
February 0.101979E+09 30593668.43 56.21 01-FEB-06:01 16.86 16.86 56.81 0.44
March 0.112905E+09 33871561.48 56.21 01-MAR-06:01 16.86 16.86 56.80 0.44
April 0.109263E+09 32778930.46 56.21 01-APR-05:01 16.86 16.86 56.81 0.44
May 0.112905E+09 33871561.48 56.21 01-MAY-05:02 16.86 16.86 57.06 0.44
June 0.109263E+09 32778930.46 56.21 01-JUN-05:01 16.86 16.86 57.21 0.44
July 0.112905E+09 33871561.48 56.21 01-JUL-05:01 16.86 16.86 57.41 0.44
August 0.112905E+09 33871561.48 56.21 01-AUG-05:02 16.86 16.86 57.40 0.44
September 0.109263E+09 32778930.46 56.21 01-SEP-05:01 16.86 16.86 57.49 0.44
October 0.112905E+09 33871561.48 56.21 01-OCT-05:05 16.86 16.86 57.07 0.44
November 0.109263E+09 32778930.46 56.21 01-NOV-05:01 16.86 16.86 57.30 0.44
December 0.112905E+09 33871561.48 56.21 01-DEC-06:01 16.86 16.86 57.01 0.44
                 
Annual Sum or Average 0.132937E+10 0.398810E+09            
Minimum of Months 0.101979E+09 30593668.43 56.21   16.86 16.86 56.80 0.44
Maximum of Months 0.112905E+09 33871561.48 56.21   16.86 16.86 57.49 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.123961E+11 0.111565E+11 33196.82 14-JAN-00:20 29877.14 29877.14 21.19 95.55
February 0.247636E+11 0.222872E+11 33238.73 15-FEB-05:55 29914.86 29914.86 22.94 95.55
March 0.674212E+11 0.606791E+11 33262.46 23-MAR-13:34 29936.21 29936.21 23.93 95.55
April 0.720117E+11 0.648106E+11 66701.05 18-APR-15:00 60030.95 60030.95 27.23 191.09
May 0.368837E+11 0.331953E+11 66680.58 31-MAY-14:05 60012.52 60012.52 26.87 191.09
June 0.651331E+11 0.586198E+11 66824.94 13-JUN-14:30 60142.44 60142.44 29.45 191.09
July 0.910804E+11 0.819723E+11 66824.94 03-JUL-12:10 60142.44 60142.44 29.49 191.09
August 0.976499E+11 0.878849E+11 66824.94 02-AUG-15:40 60142.44 60142.44 29.45 191.09
September 0.396692E+11 0.357023E+11 66735.27 11-SEP-12:05 60061.74 60061.74 27.85 191.09
October 0.293658E+11 0.264292E+11 33302.74 20-OCT-13:00 29972.46 29972.46 25.53 95.55
November 0.777628E+11 0.699865E+11 33277.58 03-NOV-13:40 29949.82 29949.82 24.57 95.55
December 0.775406E+11 0.697865E+11 33240.76 05-DEC-16:08 29916.69 29916.69 23.03 95.55
                 
Annual Sum or Average 0.691678E+12 0.622510E+12            
Minimum of Months 0.123961E+11 0.111565E+11 33196.82   29877.14 29877.14 21.19 95.55
Maximum of Months 0.976499E+11 0.878849E+11 66824.94   60142.44 60142.44 29.49 191.09



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 30.87 30.87 564661.18 4543504.69 02-JAN-04:01
February 0.00 0.00 01-FEB-00:01 36.87 82.20 388960.08 3940492.96 21-FEB-05:01
March 0.00 0.00 01-MAR-00:01 35.23 35.23 182799.26 3505456.42 25-MAR-04:01
April 0.00 0.00 01-APR-00:03 24.16 24.16 75772.34 3657453.71 01-APR-04:01
May 0.00 0.00 01-MAY-00:10 20.75 20.75 11914.64 3267873.93 02-MAY-04:11
June 0.00 0.00 01-JUN-00:10 20.20 20.20 4097.77 2871209.72 02-JUN-05:01
July 0.00 0.00 01-JUL-00:05 20.25 20.25 497.14 208703.21 24-JUL-05:01
August 0.00 0.00 01-AUG-00:10 20.44 20.44 1517.78 388786.70 07-AUG-05:02
September 0.00 0.00 01-SEP-00:10 19.88 19.88 20020.19 3359021.90 30-SEP-04:01
October 0.00 0.00 01-OCT-00:01 22.17 22.17 58022.95 3615852.69 16-OCT-04:11
November 0.00 0.00 01-NOV-00:01 25.08 25.08 217025.88 3718956.36 28-NOV-05:01
December 0.00 0.00 01-DEC-00:01 28.90 28.90 401527.92 3831784.04 18-DEC-05:01
                 
Annual Sum or Average 0.00         159582.29    
Minimum of Months 0.00 0.00   19.88 19.88 497.14 208703.21  
Maximum of Months 0.00 0.00   36.87 82.20 564661.18 4543504.69  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 1633.21 93930.42 13-JAN-22:03 7.03 6.70 120702.01 990083.28 08-JAN-01:51
February 69083.89 1006999.74 24-FEB-19:02 10.24 6.70 179153.81 878222.57 11-FEB-10:02
March 103318.12 1115196.33 23-MAR-13:32 10.63 6.70 17456.60 814262.15 08-MAR-03:20
April 189422.26 2508654.79 18-APR-09:20 11.23 6.82 10974.05 760177.81 21-APR-16:11
May 192958.06 2533250.25 30-MAY-14:05 11.16 6.70 219451.16 990007.34 19-MAY-19:35
June 633333.46 3582745.10 30-JUN-04:14 13.01 6.70 54308.92 948925.92 05-JUN-07:55
July 842719.57 3525966.26 27-JUL-04:14 12.91 6.70 13396.54 521685.60 27-JUL-21:04
August 883728.97 4143317.39 03-AUG-05:03 14.00 7.25 7909.91 486574.19 01-AUG-04:47
September 300200.79 2668633.37 07-SEP-12:05 11.40 6.70 245613.49 989936.58 03-SEP-06:30
October 97908.14 1542457.23 20-OCT-13:00 12.13 6.70 200567.06 946547.60 11-OCT-10:13
November 94824.94 1224521.95 03-NOV-11:15 11.12 6.81 7993.43 795591.49 01-NOV-04:11
December 106771.77 883464.89 05-DEC-13:38 9.81 6.70 6266.82 686295.36 01-DEC-16:33
                 
Annual Sum or Average 294706.76         89702.07    
Minimum of Months 1633.21 93930.42   7.03 6.70 6266.82 486574.19  
Maximum of Months 883728.97 4143317.39   14.00 7.25 245613.49 990083.28  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 16.43 33766.92 17-JAN-06:01 8.34 6.74 0.00 0.00 01-JAN-00:02
February 75611.05 381934.94 10-FEB-15:46 12.28 9.74 0.00 0.00 01-FEB-00:01
March 174412.00 1215698.81 23-MAR-14:02 14.91 7.80 0.00 0.00 01-MAR-00:01
April 289211.58 3516114.63 16-APR-16:21 15.37 10.90 0.00 0.00 01-APR-00:03
May 216149.69 2668505.21 12-MAY-05:02 14.00 9.70 0.00 0.00 01-MAY-00:10
June 660012.06 5526759.29 30-JUN-04:11 17.23 12.65 0.00 0.00 01-JUN-00:10
July 880525.14 5383535.62 15-JUL-04:11 17.33 13.05 0.00 0.00 01-JUL-00:05
August 925329.86 4897302.16 03-AUG-05:02 15.60 7.91 0.00 0.00 01-AUG-00:10
September 316793.62 4261817.37 11-SEP-04:11 16.43 10.82 0.00 0.00 01-SEP-00:10
October 120833.24 1559126.99 20-OCT-13:00 13.58 6.70 0.00 0.00 01-OCT-00:01
November 199365.22 1368941.36 03-NOV-13:38 15.24 6.90 0.00 0.00 01-NOV-00:01
December 220497.65 557086.98 09-DEC-06:01 12.96 9.75 0.00 0.00 01-DEC-00:01
                 
Annual Sum or Average 341778.82         0.00    
Minimum of Months 16.43 33766.92   8.34 6.70 0.00 0.00  
Maximum of Months 925329.86 5526759.29   17.33 13.05 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 57.87 57.87 16465.26 59153.19 31-JAN-12:13
February 0.00 0.00 01-FEB-00:01 57.23 57.23 16894.76 59537.17 21-FEB-12:30
March 0.00 0.00 01-MAR-00:01 57.22 57.22 17777.98 59447.59 01-MAR-12:32
April 0.00 0.00 01-APR-00:03 57.29 57.29 16020.56 57772.50 03-APR-11:58
May 0.00 0.00 01-MAY-00:10 57.95 57.95 15596.57 55044.03 01-MAY-11:20
June 0.00 0.00 01-JUN-00:10 57.60 57.60 14913.99 51404.97 01-JUN-11:24
July 0.00 0.00 01-JUL-00:05 57.75 57.75 12955.52 48011.55 03-JUL-12:00
August 0.00 0.00 01-AUG-00:10 57.85 57.85 13823.67 46092.31 01-AUG-11:20
September 0.00 0.00 01-SEP-00:10 57.87 57.87 13127.28 47180.36 29-SEP-11:42
October 0.00 0.00 01-OCT-00:01 57.80 57.80 13755.39 50236.14 31-OCT-11:27
November 0.00 0.00 01-NOV-00:01 57.66 57.66 14898.82 53759.55 30-NOV-12:45
December 0.00 0.00 01-DEC-00:01 57.49 57.49 15304.54 56889.92 29-DEC-12:13
                 
Annual Sum or Average 0.00         15117.59    
Minimum of Months 0.00 0.00   57.22 57.22 12955.52 46092.31  
Maximum of Months 0.00 0.00   57.95 57.95 17777.98 59537.17  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 210.60 35220.19 14-JAN-00:20 21.19 20.36 4327.11 196715.69 05-JAN-02:37
February 23609.35 735973.34 15-FEB-05:55 22.94 21.10 224.44 88544.08 08-FEB-12:59
March 57738.26 1132062.74 23-MAR-13:34 23.93 21.10 4967.55 158151.20 19-MAR-04:07
April 201500.29 4899639.69 18-APR-15:00 27.23 23.82 6962.58 183980.89 08-APR-00:50
May 264931.65 4607326.93 31-MAY-14:05 26.87 23.14 1151.21 153115.92 19-MAY-04:18
June 1090518.49 6700354.07 13-JUN-15:00 29.49 26.09 19.66 31907.91 15-JUN-05:50
July 1520822.83 9129450.82 26-JUL-15:00 32.53 28.51 70.49 42948.55 24-JUL-05:30
August 1595140.11 10278537.72 04-AUG-13:00 33.97 29.50 212.28 64343.31 07-AUG-02:13
September 410218.01 5387904.16 11-SEP-12:05 27.85 24.19 1203.76 175805.81 29-SEP-23:20
October 114693.73 1768402.04 20-OCT-13:00 25.53 21.10 167.43 76074.69 16-OCT-06:00
November 30228.53 1384260.22 03-NOV-13:40 24.57 21.10 7092.48 132003.10 14-NOV-23:10
December 18365.93 769891.28 05-DEC-16:08 23.03 21.10 13436.85 221022.84 13-DEC-16:20
                 
Annual Sum or Average 447572.65         3339.61    
Minimum of Months 210.60 35220.19   21.19 20.36 19.66 31907.91  
Maximum of Months 1595140.11 10278537.72   33.97 29.50 13436.85 221022.84  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.807231E+11 0.00 3659.99 0.849530E+10 0.00 0.00
February 0.471380E+11 0.00 183693.85 0.787170E+10 0.00 0.00
March 0.168759E+11 0.00 0.883886E+09 0.977607E+10 0.00 0.00
April 0.476448E+10 0.00 0.164551E+11 0.113128E+11 0.00 0.00
May 0.258618E+09 0.00 0.369068E+11 0.123024E+11 0.00 0.00
June 59067803.16 0.00 0.103571E+12 0.156374E+11 0.00 0.00
July 0.00 0.00 0.150557E+12 0.176843E+11 0.00 0.00
August 89810.16 0.00 0.151392E+12 0.196492E+11 0.00 0.00
September 0.785727E+09 0.00 0.575551E+11 0.133602E+11 0.00 0.00
October 0.276134E+10 0.00 0.518290E+10 0.109151E+11 0.00 0.00
November 0.185197E+11 0.00 0.335923E+09 0.965274E+10 0.00 0.00
December 0.431312E+11 0.00 166115.13 0.903797E+10 0.00 0.00
             
Annual Sum or Average 0.215017E+12 0.00 0.522840E+12 0.145695E+12 0.00 0.00
Minimum of Months 0.00 0.00 3659.99 0.787170E+10 0.00 0.00
Maximum of Months 0.807231E+11 0.00 0.151392E+12 0.196492E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.124435E+13 0.00 127639.66 0.123066E+12 0.00 0.00
February 0.762966E+12 0.00 554628.57 0.991788E+11 0.00 0.00
March 0.403487E+12 0.00 0.136351E+11 0.101410E+12 0.00 0.00
April 0.158266E+12 0.00 0.147229E+12 0.102048E+12 0.00 0.00
May 0.234976E+11 0.00 0.357255E+12 0.117718E+12 0.00 0.00
June 0.725175E+10 0.00 0.953554E+12 0.142969E+12 0.00 0.00
July 0.411828E+09 0.00 0.128437E+13 0.145323E+12 0.00 0.00
August 0.211711E+10 0.00 0.124624E+13 0.153102E+12 0.00 0.00
September 0.391353E+11 0.00 0.525828E+12 0.123383E+12 0.00 0.00
October 0.120429E+12 0.00 0.600434E+11 0.955314E+11 0.00 0.00
November 0.461176E+12 0.00 0.627949E+10 0.984552E+11 0.00 0.00
December 0.890571E+12 0.00 114693.28 0.108510E+12 0.00 0.00
             
Annual Sum or Average 0.411366E+13 0.00 0.459444E+13 0.141069E+13 0.00 0.00
Minimum of Months 0.411828E+09 0.00 114693.28 0.955314E+11 0.00 0.00
Maximum of Months 0.124435E+13 0.00 0.128437E+13 0.153102E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.189039E+12 0.00 3783396.36 0.130552E+11 0.00 0.00
February 0.124228E+12 0.00 3968659.65 0.113416E+11 0.00 0.00
March 0.720657E+11 0.00 0.633974E+09 0.109998E+11 0.00 0.00
April 0.344113E+11 0.00 0.160024E+11 0.983466E+10 0.00 0.00
May 0.827739E+10 0.00 0.391425E+11 0.100066E+11 0.00 0.00
June 0.334330E+10 0.00 0.108946E+12 0.119640E+11 0.00 0.00
July 0.921463E+09 0.00 0.144089E+12 0.120765E+11 0.00 0.00
August 0.196466E+10 0.00 0.137558E+12 0.123579E+11 0.00 0.00
September 0.121370E+11 0.00 0.565082E+11 0.998335E+10 0.00 0.00
October 0.327306E+11 0.00 0.432015E+10 0.914583E+10 0.00 0.00
November 0.858294E+11 0.00 0.146621E+09 0.110954E+11 0.00 0.00
December 0.147365E+12 0.00 13278601.60 0.127432E+11 0.00 0.00
             
Annual Sum or Average 0.712313E+12 0.00 0.507367E+12 0.134604E+12 0.00 0.00
Minimum of Months 0.921463E+09 0.00 3783396.36 0.914583E+10 0.00 0.00
Maximum of Months 0.189039E+12 0.00 0.144089E+12 0.130552E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.703058E+10 0.00 91396726.16 0.290654E+10 0.00 0.00
February 0.119773E+11 0.00 0.141126E+09 0.332259E+10 0.00 0.00
March 0.00 0.00 0.159179E+10 0.391644E+10 0.00 0.00
April 0.00 0.00 0.839460E+10 0.457866E+10 0.00 0.00
May 0.00 0.00 0.265414E+11 0.606045E+10 0.00 0.00
June 0.00 0.00 0.584613E+11 0.619596E+10 0.00 0.00
July 0.00 0.00 0.797603E+11 0.717946E+10 0.00 0.00
August 0.00 0.00 0.866746E+11 0.907025E+10 0.00 0.00
September 0.00 0.00 0.406882E+11 0.853330E+10 0.00 0.00
October 0.00 0.00 0.130509E+11 0.808937E+10 0.00 0.00
November 0.00 0.00 0.524580E+10 0.598694E+10 0.00 0.00
December 0.550974E+09 0.00 0.626302E+09 0.308257E+10 0.00 0.00
             
Annual Sum or Average 0.195589E+11 0.00 0.321268E+12 0.689225E+11 0.00 0.00
Minimum of Months 0.00 0.00 91396726.16 0.290654E+10 0.00 0.00
Maximum of Months 0.119773E+11 0.00 0.866746E+11 0.907025E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 3673730.69 0.123068E+12 0.00 35.59
February 0.00 0.00 0.157489E+12 0.145409E+12 0.00 37.63
March 0.00 0.00 0.234796E+12 0.217513E+12 0.00 57.84
April 0.00 0.00 0.266969E+12 0.242152E+12 0.00 57.96
May 0.00 0.00 0.257935E+11 0.574857E+11 0.00 11.19
June 0.00 0.00 0.332473E+12 0.398829E+11 0.00 0.43
July 0.00 0.00 0.466481E+12 0.622950E+11 0.00 0.15
August 0.00 0.00 0.610095E+12 0.860279E+11 0.00 1.44
September 0.00 0.00 0.564076E+11 0.599164E+11 0.00 12.41
October 0.00 0.00 0.168013E+12 0.135730E+12 0.00 32.75
November 0.00 0.00 0.204747E+12 0.202165E+12 0.00 53.17
December 0.00 0.00 0.255899E+12 0.335690E+12 0.00 91.19
             
Annual Sum or Average 0.00 0.00 0.277917E+13 0.170733E+13 0.00 391.74
Minimum of Months 0.00 0.00 3673730.69 0.398829E+11 0.00 0.15
Maximum of Months 0.00 0.00 0.610095E+12 0.335690E+12 0.00 91.19



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.472813E+10 0.00 0.00
February 0.00 0.00 0.00 0.549815E+10 0.00 0.00
March 0.00 0.00 0.00 0.783112E+10 0.00 0.00
April 0.00 0.00 0.00 0.902725E+10 0.00 0.00
May 0.00 0.00 0.00 0.591839E+10 0.00 0.00
June 0.00 0.00 0.00 0.716869E+10 0.00 0.00
July 0.00 0.00 0.00 0.859883E+10 0.00 0.00
August 0.00 0.00 0.00 0.998584E+10 0.00 0.00
September 0.00 0.00 0.00 0.580835E+10 0.00 0.00
October 0.00 0.00 0.00 0.693319E+10 0.00 0.00
November 0.00 0.00 0.00 0.755421E+10 0.00 0.00
December 0.00 0.00 0.00 0.873771E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.877899E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.472813E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.998584E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.388223E+11 0.00 0.00
February 0.00 0.00 0.00 0.464952E+11 0.00 0.00
March 0.00 0.00 0.00 0.668952E+11 0.00 0.00
April 0.00 0.00 0.00 0.768876E+11 0.00 0.00
May 0.00 0.00 0.00 0.522615E+11 0.00 0.00
June 0.00 0.00 0.00 0.632210E+11 0.00 0.00
July 0.00 0.00 0.00 0.751773E+11 0.00 0.00
August 0.00 0.00 0.00 0.860498E+11 0.00 0.00
September 0.00 0.00 0.00 0.509046E+11 0.00 0.00
October 0.00 0.00 0.00 0.595022E+11 0.00 0.00
November 0.00 0.00 0.00 0.635783E+11 0.00 0.00
December 0.00 0.00 0.00 0.721297E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.751925E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.388223E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.860498E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.381980E+10 0.00 0.00
February 0.00 0.00 0.00 0.455834E+10 0.00 0.00
March 0.00 0.00 0.00 0.693969E+10 0.00 0.00
April 0.00 0.00 0.00 0.819256E+10 0.00 0.00
May 0.00 0.00 0.00 0.541128E+10 0.00 0.00
June 0.00 0.00 0.00 0.684934E+10 0.00 0.00
July 0.00 0.00 0.00 0.828150E+10 0.00 0.00
August 0.00 0.00 0.00 0.945823E+10 0.00 0.00
September 0.00 0.00 0.00 0.522229E+10 0.00 0.00
October 0.00 0.00 0.00 0.596579E+10 0.00 0.00
November 0.00 0.00 0.00 0.650610E+10 0.00 0.00
December 0.00 0.00 0.00 0.751598E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.787209E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.381980E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.945823E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.849530E+10 3659.99 0.807231E+11 0.00 0.00 0.00 0.00 0.00
February 0.787170E+10 183693.85 0.471380E+11 0.00 0.00 0.00 0.00 0.00
March 0.977607E+10 0.883886E+09 0.168759E+11 0.00 0.00 0.00 0.00 0.00
April 0.113128E+11 0.164551E+11 0.476448E+10 0.00 0.00 0.00 0.00 0.00
May 0.123024E+11 0.369068E+11 0.258618E+09 0.00 0.00 0.00 0.00 0.00
June 0.156374E+11 0.103571E+12 59067803.16 0.00 0.00 0.00 0.00 0.00
July 0.176843E+11 0.150557E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196492E+11 0.151392E+12 89810.16 0.00 0.00 0.00 0.00 0.00
September 0.133602E+11 0.575551E+11 0.785727E+09 0.00 0.00 0.00 0.00 0.00
October 0.109151E+11 0.518290E+10 0.276134E+10 0.00 0.00 0.00 0.00 0.00
November 0.965274E+10 0.335923E+09 0.185197E+11 0.00 0.00 0.00 0.00 0.00
December 0.903797E+10 166115.13 0.431312E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.145695E+12 0.522840E+12 0.215017E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.787170E+10 3659.99 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196492E+11 0.151392E+12 0.807231E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.123066E+12 127639.66 0.124435E+13 0.00 0.00 0.00 0.00 0.00
February 0.991788E+11 554628.57 0.762966E+12 0.00 0.00 0.00 0.00 0.00
March 0.101410E+12 0.136351E+11 0.403487E+12 0.00 0.00 0.00 0.00 0.00
April 0.102048E+12 0.147229E+12 0.158266E+12 0.00 0.00 0.00 0.00 0.00
May 0.117718E+12 0.357255E+12 0.234976E+11 0.00 0.00 0.00 0.00 0.00
June 0.142969E+12 0.953554E+12 0.725175E+10 0.00 0.00 0.00 0.00 0.00
July 0.145323E+12 0.128437E+13 0.411828E+09 0.00 0.00 0.00 0.00 0.00
August 0.153102E+12 0.124624E+13 0.211711E+10 0.00 0.00 0.00 0.00 0.00
September 0.123383E+12 0.525828E+12 0.391353E+11 0.00 0.00 0.00 0.00 0.00
October 0.955314E+11 0.600434E+11 0.120429E+12 0.00 0.00 0.00 0.00 0.00
November 0.984552E+11 0.627949E+10 0.461176E+12 0.00 0.00 0.00 0.00 0.00
December 0.108510E+12 114693.28 0.890571E+12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.141069E+13 0.459444E+13 0.411366E+13 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.955314E+11 114693.28 0.411828E+09 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.153102E+12 0.128437E+13 0.124435E+13 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.130552E+11 3783396.36 0.189039E+12 0.00 0.00 0.00 0.00 0.00
February 0.113416E+11 3968659.65 0.124228E+12 0.00 0.00 0.00 0.00 0.00
March 0.109998E+11 0.633974E+09 0.720657E+11 0.00 0.00 0.00 0.00 0.00
April 0.983466E+10 0.160024E+11 0.344113E+11 0.00 0.00 0.00 0.00 0.00
May 0.100066E+11 0.391425E+11 0.827739E+10 0.00 0.00 0.00 0.00 0.00
June 0.119640E+11 0.108946E+12 0.334330E+10 0.00 0.00 0.00 0.00 0.00
July 0.120765E+11 0.144089E+12 0.921463E+09 0.00 0.00 0.00 0.00 0.00
August 0.123579E+11 0.137558E+12 0.196466E+10 0.00 0.00 0.00 0.00 0.00
September 0.998335E+10 0.565082E+11 0.121370E+11 0.00 0.00 0.00 0.00 0.00
October 0.914583E+10 0.432015E+10 0.327306E+11 0.00 0.00 0.00 0.00 0.00
November 0.110954E+11 0.146621E+09 0.858294E+11 0.00 0.00 0.00 0.00 0.00
December 0.127432E+11 13278601.60 0.147365E+12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.134604E+12 0.507367E+12 0.712313E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.914583E+10 3783396.36 0.921463E+09 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130552E+11 0.144089E+12 0.189039E+12 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.290654E+10 91396726.16 0.703058E+10 0.00 0.00 0.00 0.00 0.00
February 0.332259E+10 0.141126E+09 0.119773E+11 0.00 0.00 0.00 0.00 0.00
March 0.391644E+10 0.159179E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.457866E+10 0.839460E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.606045E+10 0.265414E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.619596E+10 0.584613E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.717946E+10 0.797603E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.907025E+10 0.866746E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.853330E+10 0.406882E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.808937E+10 0.130509E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.598694E+10 0.524580E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.308257E+10 0.626302E+09 0.550974E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.689225E+11 0.321268E+12 0.195589E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.290654E+10 91396726.16 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.907025E+10 0.866746E+11 0.119773E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.274029E+11 3673730.69 0.00 0.00 0.00 0.952365E+11 0.00 0.00
February 0.442613E+11 0.157489E+12 0.00 0.00 0.00 0.100694E+12 0.00 0.00
March 0.620295E+11 0.234796E+12 0.00 0.00 0.00 0.154787E+12 0.00 0.00
April 0.863382E+11 0.266969E+12 0.00 0.00 0.00 0.155116E+12 0.00 0.00
May 0.274072E+11 0.257935E+11 0.00 0.00 0.00 0.299437E+11 0.00 0.00
June 0.387261E+11 0.332473E+12 0.00 0.00 0.00 0.115161E+10 0.00 0.00
July 0.618888E+11 0.466481E+12 0.00 0.00 0.00 0.404367E+09 0.00 0.00
August 0.821546E+11 0.610095E+12 0.00 0.00 0.00 0.385596E+10 0.00 0.00
September 0.265475E+11 0.564076E+11 0.00 0.00 0.00 0.332193E+11 0.00 0.00
October 0.477042E+11 0.168013E+12 0.00 0.00 0.00 0.876316E+11 0.00 0.00
November 0.592467E+11 0.204747E+12 0.00 0.00 0.00 0.142277E+12 0.00 0.00
December 0.905581E+11 0.255899E+12 0.00 0.00 0.00 0.244033E+12 0.00 0.00
                 
Annual Sum or Average 0.654265E+12 0.277917E+13 0.00 0.00 0.00 0.104835E+13 0.00 0.00
Minimum of Months 0.265475E+11 3673730.69 0.00 0.00 0.00 0.404367E+09 0.00 0.00
Maximum of Months 0.905581E+11 0.610095E+12 0.00 0.00 0.00 0.244033E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.364211E+10 0.344206E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.328965E+10 0.766102E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.364211E+10 0.158367E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.352462E+10 0.211777E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.364211E+10 0.754346E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.352462E+10 0.128432E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364211E+10 0.187805E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.364211E+10 0.237950E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.352462E+10 0.751511E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.364211E+10 0.116843E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.352462E+10 0.152345E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364211E+10 0.198902E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.428829E+11 0.165404E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.328965E+10 0.344206E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.364211E+10 0.237950E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.350442E+11 0.137109E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.316528E+11 0.584684E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.350442E+11 0.137715E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.339137E+11 0.193661E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.350442E+11 0.659448E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.339137E+11 0.119865E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.350442E+11 0.176618E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.350442E+11 0.223708E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.339137E+11 0.644457E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.350442E+11 0.994194E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.339137E+11 0.127347E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.350442E+11 0.167225E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.412617E+12 0.144813E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.316528E+11 0.137109E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.350442E+11 0.223708E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.360801E+10 0.655072E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.325885E+10 0.429078E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.360801E+10 0.120082E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.349162E+10 0.180343E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.360801E+10 0.586428E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.349162E+10 0.116630E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.360801E+10 0.174722E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.360801E+10 0.220767E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.349162E+10 0.555530E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.360801E+10 0.798918E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.349162E+10 0.107505E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.360801E+10 0.146601E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.424814E+11 0.131020E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.325885E+10 0.655072E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.360801E+10 0.220767E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.849530E+10 0.807231E+11 3659.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.787170E+10 0.471380E+11 183693.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.977607E+10 0.168759E+11 0.883886E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.113128E+11 0.476448E+10 0.164551E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.123024E+11 0.258618E+09 0.369068E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.156374E+11 59067803.16 0.103571E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.176843E+11 0.00 0.150557E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196492E+11 89810.16 0.151392E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.133602E+11 0.785727E+09 0.575551E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.109151E+11 0.276134E+10 0.518290E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.965274E+10 0.185197E+11 0.335923E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.903797E+10 0.431312E+11 166115.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.145695E+12 0.215017E+12 0.522840E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.787170E+10 0.00 3659.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196492E+11 0.807231E+11 0.151392E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.123066E+12 0.124435E+13 127639.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.991788E+11 0.762966E+12 554628.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.101410E+12 0.403487E+12 0.136351E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.102048E+12 0.158266E+12 0.147229E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.117718E+12 0.234976E+11 0.357255E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.142969E+12 0.725175E+10 0.953554E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.145323E+12 0.411828E+09 0.128437E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.153102E+12 0.211711E+10 0.124624E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.123383E+12 0.391353E+11 0.525828E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.955314E+11 0.120429E+12 0.600434E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.984552E+11 0.461176E+12 0.627949E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.108510E+12 0.890571E+12 114693.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.141069E+13 0.411366E+13 0.459444E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.955314E+11 0.411828E+09 114693.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.153102E+12 0.124435E+13 0.128437E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.130552E+11 0.189039E+12 3783396.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.113416E+11 0.124228E+12 3968659.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.109998E+11 0.720657E+11 0.633974E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.983466E+10 0.344113E+11 0.160024E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.100066E+11 0.827739E+10 0.391425E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.119640E+11 0.334330E+10 0.108946E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.120765E+11 0.921463E+09 0.144089E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.123579E+11 0.196466E+10 0.137558E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.998335E+10 0.121370E+11 0.565082E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.914583E+10 0.327306E+11 0.432015E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.110954E+11 0.858294E+11 0.146621E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.127432E+11 0.147365E+12 13278601.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.134604E+12 0.712313E+12 0.507367E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.914583E+10 0.921463E+09 3783396.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130552E+11 0.189039E+12 0.144089E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.290654E+10 0.703058E+10 91396726.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.332259E+10 0.119773E+11 0.141126E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.391644E+10 0.00 0.159179E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.457866E+10 0.00 0.839460E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.606045E+10 0.00 0.265414E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.619596E+10 0.00 0.584613E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.717946E+10 0.00 0.797603E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.907025E+10 0.00 0.866746E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.853330E+10 0.00 0.406882E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.808937E+10 0.00 0.130509E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.598694E+10 0.00 0.524580E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.308257E+10 0.550974E+09 0.626302E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.689225E+11 0.195589E+11 0.321268E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.290654E+10 0.00 91396726.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.907025E+10 0.119773E+11 0.866746E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.274029E+11 0.00 3673730.69 0.00 0.00 0.00 0.00 0.00 0.956652E+11 0.00 0.00 0.00
February 0.442613E+11 0.00 0.157489E+12 0.00 0.00 0.00 0.00 0.00 0.101147E+12 0.00 0.00 0.00
March 0.620295E+11 0.00 0.234796E+12 0.00 0.00 0.00 0.00 0.00 0.155483E+12 0.00 0.00 0.00
April 0.863382E+11 0.00 0.266969E+12 0.00 0.00 0.00 0.00 0.00 0.155814E+12 0.00 0.00 0.00
May 0.274072E+11 0.00 0.257935E+11 0.00 0.00 0.00 0.00 0.00 0.300785E+11 0.00 0.00 0.00
June 0.387261E+11 0.00 0.332473E+12 0.00 0.00 0.00 0.00 0.00 0.115680E+10 0.00 0.00 0.00
July 0.618888E+11 0.00 0.466481E+12 0.00 0.00 0.00 0.00 0.00 0.406189E+09 0.00 0.00 0.00
August 0.821546E+11 0.00 0.610095E+12 0.00 0.00 0.00 0.00 0.00 0.387331E+10 0.00 0.00 0.00
September 0.265475E+11 0.00 0.564076E+11 0.00 0.00 0.00 0.00 0.00 0.333688E+11 0.00 0.00 0.00
October 0.477042E+11 0.00 0.168013E+12 0.00 0.00 0.00 0.00 0.00 0.880261E+11 0.00 0.00 0.00
November 0.592467E+11 0.00 0.204747E+12 0.00 0.00 0.00 0.00 0.00 0.142918E+12 0.00 0.00 0.00
December 0.905581E+11 0.00 0.255899E+12 0.00 0.00 0.00 0.00 0.00 0.245132E+12 0.00 0.00 0.00
                         
Annual Sum or Average 0.654265E+12 0.00 0.277917E+13 0.00 0.00 0.00 0.00 0.00 0.105307E+13 0.00 0.00 0.00
Minimum of Months 0.265475E+11 0.00 3673730.69 0.00 0.00 0.00 0.00 0.00 0.406189E+09 0.00 0.00 0.00
Maximum of Months 0.905581E+11 0.00 0.610095E+12 0.00 0.00 0.00 0.00 0.00 0.245132E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.364211E+10 0.00 0.00 0.00 0.108602E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.328965E+10 0.00 0.00 0.00 0.220850E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.364211E+10 0.00 0.00 0.00 0.418902E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.352462E+10 0.00 0.00 0.00 0.550263E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.364211E+10 0.00 0.00 0.00 0.227628E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.352462E+10 0.00 0.00 0.00 0.364407E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364211E+10 0.00 0.00 0.00 0.495672E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.364211E+10 0.00 0.00 0.00 0.634373E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.352462E+10 0.00 0.00 0.00 0.228373E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.364211E+10 0.00 0.00 0.00 0.329108E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.352462E+10 0.00 0.00 0.00 0.402959E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364211E+10 0.00 0.00 0.00 0.509560E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.428829E+11 0.00 0.00 0.00 0.449070E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.328965E+10 0.00 0.00 0.00 0.108602E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.364211E+10 0.00 0.00 0.00 0.634373E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.350442E+11 0.00 0.00 0.00 0.377815E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.316528E+11 0.00 0.00 0.00 0.148424E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.350442E+11 0.00 0.00 0.00 0.318510E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.339137E+11 0.00 0.00 0.00 0.429739E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.350442E+11 0.00 0.00 0.00 0.172173E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.339137E+11 0.00 0.00 0.00 0.293073E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.350442E+11 0.00 0.00 0.00 0.401331E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.350442E+11 0.00 0.00 0.00 0.510056E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.339137E+11 0.00 0.00 0.00 0.169909E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.350442E+11 0.00 0.00 0.00 0.244580E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.339137E+11 0.00 0.00 0.00 0.296646E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.350442E+11 0.00 0.00 0.00 0.370855E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.412617E+12 0.00 0.00 0.00 0.339308E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.316528E+11 0.00 0.00 0.00 0.377815E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.350442E+11 0.00 0.00 0.00 0.510056E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.360801E+10 0.00 0.00 0.00 0.211784E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.325885E+10 0.00 0.00 0.00 0.129949E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.360801E+10 0.00 0.00 0.00 0.333168E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.349162E+10 0.00 0.00 0.00 0.470094E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.360801E+10 0.00 0.00 0.00 0.180327E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.349162E+10 0.00 0.00 0.00 0.335772E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.360801E+10 0.00 0.00 0.00 0.467349E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.360801E+10 0.00 0.00 0.00 0.585022E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.349162E+10 0.00 0.00 0.00 0.173066E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.360801E+10 0.00 0.00 0.00 0.235778E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.349162E+10 0.00 0.00 0.00 0.301448E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.360801E+10 0.00 0.00 0.00 0.390797E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.424814E+11 0.00 0.00 0.00 0.362395E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.325885E+10 0.00 0.00 0.00 0.211784E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.360801E+10 0.00 0.00 0.00 0.585022E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.644703E+11 0.00 0.00 2976380.48 0.00 0.908775E+09 0.229873E+10 0.00 0.31
February 0.475207E+11 0.00 0.00 19146338.25 0.00 0.118375E+11 0.223214E+10 0.00 0.32
March 0.415399E+11 0.00 0.00 96341494.45 0.00 0.00 0.128116E+11 0.00 0.41
April 0.171331E+11 0.675418E+09 0.00 93745843.78 10343452.91 0.00 0.270464E+11 0.00 0.48
May 0.372455E+10 0.125194E+10 0.00 86210394.97 0.00 0.00 0.303377E+11 0.00 0.67
June 0.209355E+10 0.948343E+10 0.00 0.224676E+09 86130630.16 0.00 0.169233E+11 0.00 0.64
July 0.220228E+09 0.165903E+11 0.00 0.155564E+09 77163540.32 0.00 0.883517E+10 0.00 0.62
August 0.287887E+09 0.160136E+11 0.00 98209784.09 0.109223E+09 0.00 0.146822E+11 0.00 0.76
September 0.363436E+10 0.241947E+10 0.00 0.129019E+09 36399109.17 0.00 0.355248E+11 0.00 0.77
October 0.139309E+11 0.00 0.00 0.378831E+09 0.00 0.00 0.463469E+11 0.00 0.70
November 0.288255E+11 0.00 0.00 0.254323E+09 0.00 0.00 0.328807E+11 0.00 0.55
December 0.458572E+11 0.00 0.00 40152115.04 0.00 0.00 0.152699E+11 0.00 0.32
                   
Annual Sum or Average 0.269238E+12 0.464342E+11 0.00 0.157919E+10 0.319260E+09 0.127463E+11 0.245189E+12 0.00 0.55
Minimum of Months 0.220228E+09 0.00 0.00 2976380.48 0.00 0.00 0.223214E+10 0.00 0.31
Maximum of Months 0.644703E+11 0.165903E+11 0.00 0.378831E+09 0.109223E+09 0.118375E+11 0.463469E+11 0.00 0.77



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.402556E+11 0.00 0.00 17849475.72 0.00 9325576.88 0.161419E+11 0.00 0.26
February 0.331352E+11 0.00 0.00 0.160336E+09 0.00 6699712.70 0.130373E+11 0.00 0.28
March 0.198842E+11 0.00 0.00 0.406844E+09 0.00 0.00 0.315122E+11 0.00 0.41
April 0.113709E+11 0.359223E+09 0.00 0.206966E+09 11291516.75 0.00 0.387387E+11 0.00 0.57
May 0.557182E+10 0.396402E+09 0.00 0.139764E+09 0.00 0.00 0.401993E+11 0.00 0.83
June 0.291354E+10 0.419741E+10 0.00 0.302366E+09 92819907.90 0.00 0.234442E+11 0.00 0.69
July 0.196149E+10 0.787766E+10 0.00 0.164960E+09 0.270263E+09 0.00 0.103802E+11 0.00 0.60
August 0.242419E+10 0.769176E+10 0.00 0.111699E+09 0.208000E+09 0.00 0.163001E+11 0.00 0.71
September 0.375536E+10 0.844649E+09 0.00 0.156995E+09 27556864.86 0.00 0.354179E+11 0.00 0.69
October 0.114097E+11 0.00 0.00 0.500659E+09 0.00 0.00 0.425665E+11 0.00 0.63
November 0.178451E+11 0.00 0.00 0.436887E+09 0.00 0.00 0.350615E+11 0.00 0.48
December 0.264539E+11 0.00 0.00 0.126872E+09 0.00 0.00 0.249622E+11 0.00 0.27
                   
Annual Sum or Average 0.176981E+12 0.213671E+11 0.00 0.273220E+10 0.609930E+09 16025289.59 0.327762E+12 0.00 0.54
Minimum of Months 0.196149E+10 0.00 0.00 17849475.72 0.00 0.00 0.103802E+11 0.00 0.26
Maximum of Months 0.402556E+11 0.787766E+10 0.00 0.500659E+09 0.270263E+09 9325576.88 0.425665E+11 0.00 0.83



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.510636E+12 0.00 0.00 26227924.72 0.00 0.150362E+11 0.211606E+11 0.00 0.27
February 0.410558E+12 0.00 0.00 0.248834E+09 0.00 0.527839E+10 0.204652E+11 0.00 0.27
March 0.302785E+12 0.00 0.00 0.159015E+10 0.00 0.182208E+10 0.120404E+12 0.00 0.34
April 0.177702E+12 0.242852E+10 0.00 0.108812E+10 0.130313E+10 45677809.69 0.195903E+12 0.00 0.44
May 0.855608E+11 0.398406E+10 0.00 0.103694E+10 11556010.59 0.00 0.276628E+12 0.00 0.70
June 0.539240E+11 0.397849E+11 0.00 0.193127E+10 0.208309E+10 0.00 0.156001E+12 0.00 0.59
July 0.324922E+11 0.730174E+11 0.00 0.782268E+09 0.712173E+09 0.00 0.522293E+11 0.00 0.46
August 0.309613E+11 0.688964E+11 0.00 0.553167E+09 0.375188E+10 0.00 0.926679E+11 0.00 0.53
September 0.784280E+11 0.681149E+10 0.00 0.983907E+09 0.118171E+10 0.00 0.219873E+12 0.00 0.56
October 0.172694E+12 0.00 0.00 0.262860E+10 15191959.79 0.00 0.204201E+12 0.00 0.45
November 0.297621E+12 0.00 0.00 0.134711E+10 0.00 0.290889E+10 0.107131E+12 0.00 0.37
December 0.423957E+12 0.00 0.00 0.102919E+09 0.00 0.648878E+10 0.324736E+11 0.00 0.26
                   
Annual Sum or Average 0.257732E+13 0.194923E+12 0.00 0.123195E+11 0.905873E+10 0.315801E+11 0.149914E+13 0.00 0.44
Minimum of Months 0.309613E+11 0.00 0.00 26227924.72 0.00 0.00 0.204652E+11 0.00 0.26
Maximum of Months 0.510636E+12 0.730174E+11 0.00 0.262860E+10 0.375188E+10 0.150362E+11 0.276628E+12 0.00 0.70



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.273464E+11 0.00 0.00 0.00 0.00 0.152562E+11 0.00 0.00 0.22
February 0.254764E+11 0.00 0.00 0.00 0.00 0.969084E+10 0.00 0.00 0.24
March 0.327647E+11 0.00 0.00 4992786.35 0.00 0.355952E+10 0.512178E+09 0.00 0.33
April 0.266005E+11 0.167554E+09 0.00 23324146.91 0.111481E+09 0.120511E+10 0.588432E+10 0.00 0.43
May 0.205049E+11 0.209397E+09 0.00 45475014.26 4135424.87 24732220.35 0.144290E+11 0.00 0.71
June 0.101132E+11 0.308605E+10 0.00 0.103348E+09 0.489923E+09 0.00 0.962583E+10 0.00 0.58
July 0.427099E+10 0.576753E+10 0.00 40431204.80 0.771574E+09 0.00 0.354659E+10 0.00 0.46
August 0.527110E+10 0.551267E+10 0.00 37410096.37 0.113226E+10 0.00 0.554192E+10 0.00 0.51
September 0.174477E+11 0.423910E+09 0.00 28206034.28 0.101396E+09 0.209085E+09 0.686908E+10 0.00 0.52
October 0.308209E+11 0.00 0.00 5615556.79 4313201.18 0.147772E+10 0.591404E+09 0.00 0.44
November 0.280127E+11 0.00 0.00 3304512.09 0.00 0.465353E+10 0.371403E+09 0.00 0.34
December 0.262600E+11 0.00 0.00 0.00 0.00 0.979361E+10 0.00 0.00 0.22
                   
Annual Sum or Average 0.254889E+12 0.151671E+11 0.00 0.292108E+09 0.261508E+10 0.458703E+11 0.473718E+11 0.00 0.42
Minimum of Months 0.427099E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.22
Maximum of Months 0.327647E+11 0.576753E+10 0.00 0.103348E+09 0.113226E+10 0.152562E+11 0.144290E+11 0.00 0.71



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.121493E+10 0.00 0.00 0.00 0.00 0.120008E+11 0.00 0.00 0.48
February 0.335133E+10 0.00 0.00 0.00 0.00 0.710287E+10 0.00 0.00 0.49
March 0.721421E+10 0.00 0.00 135608.59 0.00 0.268118E+10 41862870.72 0.00 0.61
April 0.753333E+10 73748028.94 0.00 2537077.05 2666275.52 0.484073E+09 0.691436E+09 0.00 0.78
May 0.536023E+10 79570828.88 0.00 7882969.33 0.00 1256239.74 0.269734E+10 0.00 1.16
June 0.264097E+10 0.865160E+09 0.00 21728521.06 42218584.30 0.00 0.181306E+10 0.00 0.97
July 0.125151E+10 0.145516E+10 0.00 10154418.39 0.107877E+09 0.00 0.893434E+09 0.00 0.85
August 0.191532E+10 0.140312E+10 0.00 6630633.02 81314374.08 0.00 0.113801E+10 0.00 0.94
September 0.507689E+10 0.164873E+09 0.00 5090351.70 6624519.39 55050001.37 0.131502E+10 0.00 0.90
October 0.836772E+10 0.00 0.00 2761098.97 0.00 0.251739E+09 0.327695E+09 0.00 0.81
November 0.673055E+10 0.00 0.00 0.00 0.00 0.287426E+10 0.00 0.00 0.65
December 0.363260E+10 0.00 0.00 0.00 0.00 0.698968E+10 0.00 0.00 0.44
                   
Annual Sum or Average 0.542896E+11 0.404163E+10 0.00 56920678.11 0.240701E+09 0.324409E+11 0.891786E+10 0.00 0.76
Minimum of Months 0.121493E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.44
Maximum of Months 0.836772E+10 0.145516E+10 0.00 21728521.06 0.107877E+09 0.120008E+11 0.269734E+10 0.00 1.16



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.246687E+10 0.00 0.00 0.00 0.00 0.101293E+11 0.00 0.00 0.70
February 0.397965E+10 0.00 0.00 634579.40 0.00 0.592729E+10 48915843.50 0.00 0.72
March 0.648829E+10 0.00 0.00 6381324.50 0.00 0.250710E+10 0.604985E+09 0.00 0.92
April 0.650574E+10 70179672.83 0.00 7423111.84 2550845.78 0.733665E+09 0.149289E+10 0.00 1.22
May 0.484885E+10 72449960.47 0.00 9532163.03 415253.78 3333119.82 0.334213E+10 0.00 1.83
June 0.258578E+10 0.721433E+09 0.00 27729323.67 66128056.21 0.00 0.220185E+10 0.00 1.57
July 0.122402E+10 0.106870E+10 0.00 14741154.53 0.236325E+09 0.00 0.116103E+10 0.00 1.39
August 0.187768E+10 0.104004E+10 0.00 8420295.32 0.202721E+09 0.00 0.136926E+10 0.00 1.46
September 0.421342E+10 0.140306E+09 0.00 9340424.22 6951945.84 60958135.45 0.218081E+10 0.00 1.43
October 0.771203E+10 0.00 0.00 6070982.14 0.00 0.331467E+09 0.584911E+09 0.00 1.21
November 0.632098E+10 0.00 0.00 44616.78 0.00 0.285378E+10 12837832.58 0.00 0.97
December 0.336770E+10 0.00 0.00 0.00 0.00 0.678435E+10 0.00 0.00 0.66
                   
Annual Sum or Average 0.515910E+11 0.311311E+10 0.00 90317975.43 0.515093E+09 0.293312E+11 0.129996E+11 0.00 1.18
Minimum of Months 0.122402E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.66
Maximum of Months 0.771203E+10 0.106870E+10 0.00 27729323.67 0.236325E+09 0.101293E+11 0.334213E+10 0.00 1.83



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.403509E+10 0.00 0.00 4423197.11 0.00 0.890179E+10 0.243100E+10 0.00 0.56
February 0.530517E+10 0.00 0.00 23886927.28 0.00 0.512587E+10 0.196510E+10 0.00 0.60
March 0.617241E+10 0.00 0.00 46535993.75 0.00 0.283478E+10 0.366240E+10 0.00 0.82
April 0.641075E+10 0.159795E+09 0.00 20486390.45 2974357.59 0.963498E+09 0.402204E+10 0.00 1.08
May 0.567184E+10 0.110769E+09 0.00 11835608.81 6484.09 42856218.12 0.380937E+10 0.00 1.40
June 0.340192E+10 0.102819E+10 0.00 20522840.06 71290424.40 1183306.29 0.172927E+10 0.00 1.13
July 0.159916E+10 0.169511E+10 0.00 8145864.25 0.178966E+09 0.00 0.788896E+09 0.00 0.97
August 0.220911E+10 0.175403E+10 0.00 9379723.23 0.123566E+09 0.00 0.143307E+10 0.00 1.14
September 0.468483E+10 0.324138E+09 0.00 16155620.79 7258898.16 99420407.22 0.342360E+10 0.00 1.24
October 0.646472E+10 0.00 0.00 72842457.81 0.00 0.570978E+09 0.584112E+10 0.00 1.24
November 0.668410E+10 0.00 0.00 24144148.05 0.00 0.287886E+10 0.203269E+10 0.00 0.82
December 0.351748E+10 0.00 0.00 11746689.14 0.00 0.704105E+10 0.228742E+10 0.00 0.54
                   
Annual Sum or Average 0.561566E+11 0.507204E+10 0.00 0.270105E+09 0.384062E+09 0.284603E+11 0.334260E+11 0.00 0.96
Minimum of Months 0.159916E+10 0.00 0.00 4423197.11 0.00 0.00 0.788896E+09 0.00 0.54
Maximum of Months 0.668410E+10 0.175403E+10 0.00 72842457.81 0.178966E+09 0.890179E+10 0.584112E+10 0.00 1.40



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.553306E+10 0.00 0.00 38114.55 0.00 0.973373E+10 69358058.93 0.00 0.86
February 0.742053E+10 0.00 0.00 2951201.24 0.00 0.447921E+10 0.255728E+09 0.00 0.88
March 0.100036E+11 0.00 0.00 14868775.22 0.00 0.637792E+09 0.120833E+10 0.00 1.14
April 0.740232E+10 0.105881E+09 0.00 17983043.42 194154.30 69191536.61 0.380647E+10 0.00 1.61
May 0.621471E+10 0.101796E+09 0.00 8958222.41 0.00 0.00 0.341681E+10 0.00 2.16
June 0.343047E+10 0.997163E+09 0.00 22224553.07 44037122.05 0.00 0.193990E+10 0.00 1.83
July 0.142679E+10 0.187421E+10 0.00 11402111.74 76084255.53 0.00 0.113732E+10 0.00 1.59
August 0.174133E+10 0.175204E+10 0.00 11835826.65 48986635.13 0.00 0.197025E+10 0.00 1.79
September 0.581266E+10 0.219540E+09 0.00 6456264.24 2403775.74 454127.93 0.177993E+10 0.00 1.68
October 0.902445E+10 0.00 0.00 20786377.05 0.00 6149594.61 0.180497E+10 0.00 1.55
November 0.987989E+10 0.00 0.00 2490240.63 0.00 0.112982E+10 0.241476E+09 0.00 1.19
December 0.939452E+10 0.00 0.00 441080.86 0.00 0.276923E+10 0.195885E+09 0.00 0.80
                   
Annual Sum or Average 0.772843E+11 0.505063E+10 0.00 0.120436E+09 0.171706E+09 0.188256E+11 0.178264E+11 0.00 1.43
Minimum of Months 0.142679E+10 0.00 0.00 38114.55 0.00 0.00 69358058.93 0.00 0.80
Maximum of Months 0.100036E+11 0.187421E+10 0.00 22224553.07 76084255.53 0.973373E+10 0.380647E+10 0.00 2.16



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.612650E+10 0.00 0.00 0.00 0.00 0.184393E+12 0.00 0.00 0.73
February 0.143661E+11 0.00 0.00 0.00 0.00 0.137285E+12 0.00 0.00 0.75
March 0.554291E+11 0.00 0.00 0.00 0.00 0.837290E+11 0.00 0.00 0.87
April 0.781248E+11 0.452382E+09 0.00 689022.12 0.500269E+09 0.321985E+11 0.864517E+09 0.00 1.01
May 0.891342E+11 0.868051E+09 0.00 7287304.66 9778947.98 0.304709E+10 0.575520E+10 0.00 1.48
June 0.468383E+11 0.833126E+10 0.00 32340136.44 0.196283E+10 0.531588E+09 0.535596E+10 0.00 1.16
July 0.214303E+11 0.130459E+11 0.00 15295360.64 0.491272E+10 0.00 0.203450E+10 0.00 0.96
August 0.292606E+11 0.115979E+11 0.00 20923855.00 0.595654E+10 8971525.32 0.396616E+10 0.00 1.08
September 0.699480E+11 0.134211E+10 0.00 6261675.53 0.528699E+09 0.686694E+10 0.297556E+10 0.00 1.17
October 0.845955E+11 0.00 0.00 0.00 5266585.61 0.285801E+11 0.00 0.00 1.06
November 0.489557E+11 0.00 0.00 0.00 0.00 0.835958E+11 0.00 0.00 0.92
December 0.425829E+10 0.00 0.00 0.00 0.00 0.156637E+12 0.00 0.00 0.72
                   
Annual Sum or Average 0.548467E+12 0.356376E+11 0.00 82797354.40 0.138761E+11 0.716873E+12 0.209519E+11 0.00 0.99
Minimum of Months 0.425829E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.72
Maximum of Months 0.891342E+11 0.130459E+11 0.00 32340136.44 0.595654E+10 0.184393E+12 0.575520E+10 0.00 1.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.683290E+10 0.00 0.00 0.00 0.00 0.106003E+12 0.00 0.00 0.68
February 0.158172E+11 0.00 0.00 2103972.05 0.00 0.736923E+11 0.128479E+09 0.00 0.69
March 0.381802E+11 0.00 0.00 41085673.81 0.00 0.426088E+11 0.306858E+10 0.00 0.82
April 0.426486E+11 0.786145E+09 0.00 62722712.78 33634417.94 0.173844E+11 0.114549E+11 0.00 1.05
May 0.422836E+11 0.818146E+09 0.00 85101469.64 13506099.87 0.891908E+09 0.260465E+11 0.00 1.66
June 0.230860E+11 0.789550E+10 0.00 0.247137E+09 0.836777E+09 69749916.74 0.185944E+11 0.00 1.50
July 0.106818E+11 0.113513E+11 0.00 0.120928E+09 0.308902E+10 0.00 0.897568E+10 0.00 1.28
August 0.165974E+11 0.112127E+11 0.00 66116658.43 0.267002E+10 13487886.82 0.102288E+11 0.00 1.33
September 0.363476E+11 0.144306E+10 0.00 68480841.88 0.110829E+09 0.306877E+10 0.143703E+11 0.00 1.29
October 0.513813E+11 0.00 0.00 28295022.91 3813940.13 0.151138E+11 0.182118E+10 0.00 0.99
November 0.281540E+11 0.00 0.00 2579562.97 0.00 0.503280E+11 0.136231E+09 0.00 0.84
December 0.824080E+10 0.00 0.00 0.00 0.00 0.875461E+11 0.00 0.00 0.66
                   
Annual Sum or Average 0.320252E+12 0.335068E+11 0.00 0.724551E+09 0.675760E+10 0.396720E+12 0.948251E+11 0.00 1.07
Minimum of Months 0.683290E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.66
Maximum of Months 0.513813E+11 0.113513E+11 0.00 0.247137E+09 0.308902E+10 0.106003E+12 0.260465E+11 0.00 1.66



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.426734E+11 0.00 0.00 38233404.07 0.00 0.125363E+12 0.220627E+11 0.00 0.74
February 0.561447E+11 0.00 0.00 0.213392E+09 0.00 0.804544E+11 0.177104E+11 0.00 0.78
March 0.620520E+11 0.00 0.00 0.399886E+09 0.00 0.550372E+11 0.294833E+11 0.00 0.95
April 0.639090E+11 0.181750E+10 0.00 0.170448E+09 50536255.26 0.246308E+11 0.312397E+11 0.00 1.15
May 0.717341E+11 0.125357E+10 0.00 77916219.10 10628136.17 0.270531E+10 0.247644E+11 0.00 1.53
June 0.421641E+11 0.108504E+11 0.00 0.143929E+09 0.147071E+10 0.180861E+09 0.117885E+11 0.00 1.24
July 0.189542E+11 0.173965E+11 0.00 43857893.19 0.390185E+10 0.00 0.433333E+10 0.00 1.02
August 0.253308E+11 0.179161E+11 0.00 73735837.89 0.402734E+10 0.00 0.970608E+10 0.00 1.19
September 0.538140E+11 0.351130E+10 0.00 0.129790E+09 0.126304E+09 0.459372E+10 0.269167E+11 0.00 1.36
October 0.689795E+11 1996879.01 0.00 0.663783E+09 3668034.58 0.157576E+11 0.463677E+11 0.00 1.28
November 0.658908E+11 0.00 0.00 0.180990E+09 0.00 0.550172E+11 0.143496E+11 0.00 0.97
December 0.323556E+11 0.00 0.00 89349088.37 0.00 0.112195E+12 0.191537E+11 0.00 0.73
                   
Annual Sum or Average 0.604002E+12 0.527474E+11 0.00 0.222531E+10 0.959104E+10 0.475935E+12 0.257876E+12 0.00 1.08
Minimum of Months 0.189542E+11 0.00 0.00 38233404.07 0.00 0.00 0.433333E+10 0.00 0.73
Maximum of Months 0.717341E+11 0.179161E+11 0.00 0.663783E+09 0.402734E+10 0.125363E+12 0.463677E+11 0.00 1.53



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.171924E+11 0.00 0.00 0.00 0.00 0.130797E+12 0.00 0.00 0.89
February 0.330926E+11 0.00 0.00 8924485.79 0.00 0.839070E+11 0.857472E+09 0.00 0.91
March 0.546869E+11 0.00 0.00 51672070.36 0.00 0.498192E+11 0.438691E+10 0.00 1.06
April 0.569207E+11 0.757937E+09 0.00 86931401.41 0.186837E+09 0.171858E+11 0.178323E+11 0.00 1.34
May 0.612775E+11 0.106023E+10 0.00 50461793.65 21129551.57 0.170119E+10 0.166932E+11 0.00 1.91
June 0.337159E+11 0.898923E+10 0.00 0.149707E+09 0.123510E+10 0.203338E+09 0.115122E+11 0.00 1.65
July 0.147805E+11 0.158899E+11 0.00 43067301.37 0.247360E+10 0.00 0.457696E+10 0.00 1.31
August 0.198620E+11 0.134148E+11 0.00 51464893.90 0.317765E+10 0.00 0.798007E+10 0.00 1.46
September 0.518002E+11 0.199273E+10 0.00 32345421.25 0.113924E+09 0.432693E+10 0.753978E+10 0.00 1.50
October 0.680087E+11 0.00 0.00 86682878.76 4109266.41 0.143854E+11 0.706616E+10 0.00 1.31
November 0.471806E+11 0.00 0.00 9371220.13 0.00 0.552765E+11 0.965181E+09 0.00 1.11
December 0.181800E+11 0.00 0.00 0.00 0.00 0.107049E+12 0.00 0.00 0.87
                   
Annual Sum or Average 0.476698E+12 0.421049E+11 0.00 0.570629E+09 0.721234E+10 0.464651E+12 0.794101E+11 0.00 1.28
Minimum of Months 0.147805E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Maximum of Months 0.680087E+11 0.158899E+11 0.00 0.149707E+09 0.317765E+10 0.130797E+12 0.178323E+11 0.00 1.91



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.372213E+09 0.00 0.00 0.00 0.00 0.146800E+11 0.00 0.00 0.60
February 0.799069E+09 0.00 0.00 0.00 0.00 0.116360E+11 0.00 0.00 0.66
March 0.423294E+10 0.00 0.00 0.00 0.00 0.876362E+10 0.00 0.00 0.91
April 0.696490E+10 31205923.98 1053165.54 28125.89 45606028.36 0.447866E+10 0.100772E+09 6007.11 1.16
May 0.104171E+11 42976158.76 0.00 414610.60 6712312.93 0.915725E+09 0.326954E+09 0.00 1.84
June 0.520703E+10 0.618890E+09 0.00 1416033.08 0.307385E+09 0.267924E+09 0.567019E+09 0.00 1.38
July 0.233232E+10 0.973415E+09 0.00 1110454.40 0.784943E+09 12662828.17 0.180903E+09 0.00 1.12
August 0.299331E+10 0.882996E+09 0.00 1912514.09 0.922125E+09 0.116426E+09 0.339699E+09 0.00 1.26
September 0.669230E+10 79905615.31 0.00 556575.92 56183618.35 0.154232E+10 76228893.71 0.00 1.38
October 0.705849E+10 0.00 0.00 0.00 1522696.24 0.455215E+10 0.00 0.00 1.24
November 0.343829E+10 0.00 0.00 0.00 0.00 0.821858E+10 0.00 0.00 0.95
December 0.127736E+09 0.00 0.00 0.00 0.00 0.126058E+11 0.00 0.00 0.61
                   
Annual Sum or Average 0.506357E+11 0.262939E+10 1053165.54 5438313.96 0.212448E+10 0.677900E+11 0.159158E+10 6007.11 1.10
Minimum of Months 0.127736E+09 0.00 0.00 0.00 0.00 12662828.17 0.00 0.00 0.60
Maximum of Months 0.104171E+11 0.973415E+09 1053165.54 1912514.09 0.922125E+09 0.146800E+11 0.567019E+09 6007.11 1.84



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.426916E+09 0.00 0.00 0.00 0.00 0.932473E+10 0.00 0.00 0.61
February 0.110790E+10 0.00 0.00 0.00 0.00 0.694674E+10 0.00 0.00 0.67
March 0.419673E+10 0.00 0.00 628.70 0.00 0.422129E+10 3258198.01 0.00 0.92
April 0.437164E+10 59146903.95 383339.05 3284103.33 4653359.04 0.244294E+10 0.795231E+09 1710.13 1.20
May 0.549394E+10 44239656.44 0.00 4878290.65 1008672.77 0.366025E+09 0.191532E+10 0.00 1.94
June 0.242823E+10 0.626423E+09 0.00 20756720.84 0.119901E+09 0.164789E+09 0.180536E+10 0.00 1.60
July 0.106957E+10 0.903808E+09 0.00 9287584.71 0.398414E+09 1116817.11 0.797232E+09 0.00 1.31
August 0.143851E+10 0.904144E+09 0.00 6474246.73 0.459490E+09 37524325.36 0.966219E+09 0.00 1.40
September 0.415143E+10 92315599.88 0.00 4138202.15 13189518.96 0.662160E+09 0.628746E+09 0.00 1.44
October 0.536597E+10 0.00 0.00 148320.83 986676.26 0.212289E+10 34477182.23 0.00 1.25
November 0.249643E+10 0.00 0.00 0.00 0.00 0.505649E+10 0.00 0.00 0.95
December 0.390183E+09 0.00 0.00 0.00 0.00 0.786054E+10 0.00 0.00 0.62
                   
Annual Sum or Average 0.329375E+11 0.263008E+10 383339.05 48968097.94 0.997643E+09 0.392072E+11 0.694585E+10 1710.13 1.16
Minimum of Months 0.390183E+09 0.00 0.00 0.00 0.00 1116817.11 0.00 0.00 0.61
Maximum of Months 0.549394E+10 0.904144E+09 383339.05 20756720.84 0.459490E+09 0.932473E+10 0.191532E+10 1710.13 1.94



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.352524E+10 0.00 0.00 1603668.25 0.00 0.102321E+11 0.105948E+10 0.00 0.60
February 0.435718E+10 0.00 0.00 13517999.96 0.00 0.717048E+10 0.100274E+10 0.00 0.68
March 0.569205E+10 0.00 0.00 23908116.52 0.00 0.559388E+10 0.191851E+10 0.00 0.94
April 0.574668E+10 0.113517E+09 0.00 13090712.79 9203908.33 0.342061E+10 0.284891E+10 0.00 1.23
May 0.850020E+10 58385831.12 0.00 5482069.62 4859518.59 0.910255E+09 0.218398E+10 0.00 1.85
June 0.455023E+10 0.773781E+09 0.00 11593750.63 0.263577E+09 0.269148E+09 0.127463E+10 0.00 1.42
July 0.208496E+10 0.122801E+10 0.00 3783950.94 0.703654E+09 22295520.22 0.406595E+09 0.00 1.15
August 0.250057E+10 0.128820E+10 0.00 8841792.36 0.779146E+09 65956582.85 0.102199E+10 0.00 1.33
September 0.556718E+10 0.191478E+09 0.00 10409319.01 20904306.51 0.110851E+10 0.184327E+10 0.00 1.48
October 0.669978E+10 163155.78 0.00 43856213.90 1398291.75 0.245662E+10 0.331320E+10 0.00 1.36
November 0.521503E+10 0.00 0.00 11040048.13 0.00 0.570923E+10 0.845213E+09 0.00 0.98
December 0.240297E+10 0.00 0.00 4830751.24 0.00 0.932134E+10 0.900585E+09 0.00 0.61
                   
Annual Sum or Average 0.568421E+11 0.365353E+10 0.00 0.151958E+09 0.178274E+10 0.462804E+11 0.186191E+11 0.00 1.14
Minimum of Months 0.208496E+10 0.00 0.00 1603668.25 0.00 22295520.22 0.406595E+09 0.00 0.60
Maximum of Months 0.850020E+10 0.128820E+10 0.00 43856213.90 0.779146E+09 0.102321E+11 0.331320E+10 0.00 1.85



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.104955E+10 0.00 0.00 0.00 0.00 0.882721E+10 0.00 0.00 0.62
February 0.183763E+10 0.00 0.00 603564.64 0.00 0.626558E+10 54349887.05 0.00 0.68
March 0.395189E+10 0.00 0.00 3050884.84 0.00 0.429806E+10 0.292197E+09 0.00 0.93
April 0.434895E+10 46791458.69 0.00 7905394.53 16857968.13 0.195714E+10 0.175044E+10 0.00 1.28
May 0.580993E+10 49144932.98 0.00 5094842.71 3431731.47 0.406084E+09 0.178701E+10 0.00 1.98
June 0.299952E+10 0.650546E+09 0.00 15026110.36 0.144227E+09 0.143866E+09 0.131468E+10 0.00 1.64
July 0.127092E+10 0.114793E+10 0.00 4288543.21 0.349822E+09 281735.21 0.510311E+09 0.00 1.28
August 0.162584E+10 0.999648E+09 0.00 6268320.27 0.441857E+09 13664386.39 0.846818E+09 0.00 1.43
September 0.419814E+10 0.112002E+09 0.00 3790765.10 15489274.59 0.718535E+09 0.677340E+09 0.00 1.48
October 0.528867E+10 0.00 0.00 5779913.94 999599.35 0.187867E+10 0.529164E+09 0.00 1.28
November 0.310505E+10 0.00 0.00 657926.60 0.00 0.447771E+10 74122566.09 0.00 0.97
December 0.958403E+09 0.00 0.00 0.00 0.00 0.739630E+10 0.00 0.00 0.63
                   
Annual Sum or Average 0.364445E+11 0.300607E+10 0.00 52466266.19 0.972684E+09 0.363831E+11 0.783643E+10 0.00 1.19
Minimum of Months 0.958403E+09 0.00 0.00 0.00 0.00 281735.21 0.00 0.00 0.62
Maximum of Months 0.580993E+10 0.114793E+10 0.00 15026110.36 0.441857E+09 0.882721E+10 0.178701E+10 0.00 1.98



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 19690365.26 0.00 0.00 3343517.34 0.00 0.00 0.101994E+10 0.00 0.28
February 0.00 0.00 0.00 0.109631E+09 0.00 0.00 0.742417E+09 0.00 0.29
March 0.00 0.00 0.00 0.112029E+09 0.00 0.00 0.646145E+09 0.00 0.30
April 0.00 9862615.72 0.00 56910162.96 0.00 0.00 0.463962E+09 0.00 0.29
May 0.00 9499522.47 0.00 6871928.89 0.00 0.00 0.282601E+09 0.00 0.29
June 0.00 87120285.17 0.00 25987623.59 0.00 0.00 0.113916E+09 0.00 0.30
July 0.00 0.150096E+09 0.00 12838906.84 0.00 0.00 15038808.43 0.00 0.28
August 0.00 0.155698E+09 0.00 12473401.97 0.00 0.00 38973786.50 0.00 0.31
September 0.00 16055378.98 0.00 6663407.24 0.00 0.00 0.280475E+09 0.00 0.29
October 0.00 0.00 0.00 61987737.00 0.00 0.00 0.453505E+09 0.00 0.28
November 0.00 0.00 0.00 99211629.46 0.00 0.00 0.560186E+09 0.00 0.28
December 0.00 0.00 0.00 58769096.61 0.00 0.00 0.826099E+09 0.00 0.28
                   
Annual Sum or Average 19690365.26 0.428332E+09 0.00 0.566718E+09 0.00 0.00 0.544326E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 3343517.34 0.00 0.00 15038808.43 0.00 0.28
Maximum of Months 19690365.26 0.155698E+09 0.00 0.112029E+09 0.00 0.00 0.101994E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.378844E+10 0.00 0.00 12205870.01 0.00 0.00 0.657850E+10 0.00 0.28
February 0.00 0.00 0.00 0.926777E+09 0.00 0.00 0.755362E+10 0.00 0.29
March 0.00 0.00 0.00 0.100209E+10 0.00 0.00 0.658002E+10 0.00 0.30
April 0.00 97724250.41 0.00 0.528170E+09 0.00 0.00 0.468258E+10 0.00 0.29
May 0.00 92565768.46 0.00 57653249.51 0.00 0.00 0.284637E+10 0.00 0.29
June 0.00 0.864265E+09 0.00 0.241059E+09 0.00 0.00 0.116108E+10 0.00 0.30
July 0.00 0.149004E+10 0.00 0.121620E+09 0.00 0.00 0.159583E+09 0.00 0.28
August 0.00 0.154475E+10 0.00 0.117601E+09 0.00 0.00 0.403020E+09 0.00 0.31
September 0.00 0.157488E+09 0.00 53010204.63 0.00 0.00 0.282148E+10 0.00 0.29
October 0.00 0.00 0.00 0.541381E+09 0.00 0.00 0.461369E+10 0.00 0.28
November 0.00 0.00 0.00 0.861234E+09 0.00 0.00 0.573271E+10 0.00 0.28
December 0.00 0.00 0.00 0.516828E+09 0.00 0.00 0.833147E+10 0.00 0.28
                   
Annual Sum or Average 0.378844E+10 0.424683E+10 0.00 0.497963E+10 0.00 0.00 0.514641E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 12205870.01 0.00 0.00 0.159583E+09 0.00 0.28
Maximum of Months 0.378844E+10 0.154475E+10 0.00 0.100209E+10 0.00 0.00 0.833147E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.726954E+09 0.00 0.00 474501.14 0.00 0.00 0.300656E+09 0.00 0.28
February 534718.40 0.00 0.00 70485199.48 0.00 0.00 0.770225E+09 0.00 0.29
March 0.00 0.00 0.00 90612410.94 0.00 0.00 0.667575E+09 0.00 0.30
April 0.00 9717525.47 0.00 49934629.77 0.00 0.00 0.471676E+09 0.00 0.29
May 13072531.73 9367138.01 0.00 4856563.71 0.00 0.00 0.273118E+09 0.00 0.29
June 0.00 86548468.66 0.00 22707311.27 0.00 0.00 0.117693E+09 0.00 0.30
July 0.00 0.149002E+09 0.00 11774482.16 0.00 0.00 16480146.45 0.00 0.28
August 0.00 0.153653E+09 0.00 11465298.64 0.00 0.00 41465584.25 0.00 0.31
September 31755735.63 15807274.88 0.00 3912911.66 0.00 0.00 0.252303E+09 0.00 0.29
October 0.00 0.00 0.00 45518120.38 0.00 0.00 0.470069E+09 0.00 0.28
November 0.00 0.00 0.00 76908904.60 0.00 0.00 0.582580E+09 0.00 0.28
December 0.00 0.00 0.00 47258682.96 0.00 0.00 0.837600E+09 0.00 0.28
                   
Annual Sum or Average 0.772317E+09 0.424095E+09 0.00 0.435909E+09 0.00 0.00 0.480144E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 474501.14 0.00 0.00 16480146.45 0.00 0.28
Maximum of Months 0.726954E+09 0.153653E+09 0.00 90612410.94 0.00 0.00 0.837600E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.116205E+10 0.00 0.00 0.351026E+12 0.00 4.31
February 0.775949E+10 0.00 0.00 0.326354E+10 0.00 0.00 0.452257E+12 0.00 8.01
March 0.381769E+10 0.00 0.00 0.723896E+10 0.00 0.00 0.743052E+12 0.00 16.34
April 0.00 0.139378E+09 0.00 0.484940E+10 0.00 0.00 0.907443E+12 0.00 29.79
May 0.00 0.00 0.00 0.744680E+09 0.00 0.00 0.266908E+12 0.00 11.76
June 0.448152E+09 0.197686E+10 0.00 0.208712E+10 18110689.68 0.00 0.203362E+12 0.00 17.05
July 1248083.92 0.334384E+10 0.00 0.329357E+10 0.00 0.00 0.333876E+12 0.00 27.84
August 0.00 0.409970E+10 0.00 0.254854E+10 0.00 0.00 0.457223E+12 0.00 35.19
September 0.00 52560310.62 0.00 0.722947E+09 0.00 0.00 0.239945E+12 0.00 10.73
October 0.313682E+10 0.00 0.00 0.362664E+10 0.00 0.00 0.500312E+12 0.00 15.16
November 59050858.59 0.00 0.00 0.766764E+10 0.00 0.00 0.741473E+12 0.00 16.97
December 0.00 0.00 0.00 0.561405E+10 0.00 0.00 0.105071E+13 0.00 16.48
                   
Annual Sum or Average 0.152225E+11 0.961234E+10 0.00 0.428191E+11 18110689.68 0.00 0.624758E+13 0.00 17.53
Minimum of Months 0.00 0.00 0.00 0.722947E+09 0.00 0.00 0.203362E+12 0.00 4.31
Maximum of Months 0.775949E+10 0.409970E+10 0.00 0.766764E+10 18110689.68 0.00 0.105071E+13 0.00 35.19



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:26:25

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.406472E+12 0.721975E+11 0.00 0.212112E+13 0.643993E+12
February 0.435956E+12 0.537504E+11 0.00 0.215216E+13 0.703968E+12
March 0.627637E+12 0.471625E+11 0.00 0.286199E+13 0.850558E+12
April 0.728156E+12 0.284130E+11 0.00 0.310337E+13 0.105544E+13
May 0.824275E+12 0.152237E+11 0.00 0.266276E+13 0.756620E+12
June 0.849107E+12 0.348268E+10 0.00 0.160886E+13 0.213123E+13
July 0.851135E+12 0.779515E+09 0.00 0.111556E+13 0.292855E+13
August 0.739512E+12 0.418926E+10 0.00 0.164179E+13 0.316972E+13
September 0.520536E+12 0.134146E+11 0.00 0.221784E+13 0.106444E+13
October 0.409658E+12 0.272519E+11 0.00 0.289689E+13 0.587176E+12
November 0.273053E+12 0.456321E+11 0.00 0.269487E+13 0.809820E+12
December 0.236778E+12 0.618361E+11 0.00 0.287348E+13 0.110268E+13
           
Annual Sum or Average 0.690228E+13 0.373333E+12 0.00 0.279507E+14 0.158042E+14
Minimum of Months 0.236778E+12 0.779515E+09 0.00 0.111556E+13 0.587176E+12