Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2024-07-03 12:26:37
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 39680.02 | 856.64 | 856.64 |
Net Site Energy | 39680.02 | 856.64 | 856.64 |
Total Source Energy | 108689.17 | 2346.47 | 2346.47 |
Net Source Energy | 108689.17 | 2346.47 | 2346.47 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 8150.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1735.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1004.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3022.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 939.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 121.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5080.70 |
Humidification | 1280.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.27 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 514.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 31529.54 | 8150.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7837.15 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 8150.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1735.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 1004.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 56.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 3022.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 939.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 121.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5080.70 |
Humidification | General | 1280.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.27 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 514.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 8150.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1735.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 1004.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 3022.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 939.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 121.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5080.70 |
Humidification | Unassigned | 1280.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.27 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 514.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 164.39 | 175.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 680.68 | 175.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 164.39 | 175.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 680.68 | 175.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 31529.536 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 31529.536 | 100.00 |
Total On-Site and Utility Electric Sources | 31529.536 | 100.00 |
Total Electricity End Uses | 31529.536 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 7837.15 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 7837.15 | 100.00 |
Total Water End Uses | 7837.15 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 129.67 |
Time Setpoint Not Met During Occupied Cooling | 234.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5487.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS SZVAV FAN | AIRLOOP DATACENTER BASEMENT SYS11 FAN | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 11.6510 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 11.6510 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 11.6510 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.6510 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 11.6510 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.6510 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 11.6510 | 18.58 | 484.4232 | |
Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.6100 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 08-AUG-15:20 | 09-JAN-07:30 | - | - | - | - | - | - | - | - | - | - | 18-MAY-15:09 |
Heating | 0.00 | 3228629.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 457589.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235096.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 303257.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 96563.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 55784.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 38891.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2455455.28 | 3228629.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3228629.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 457589.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 303257.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 96563.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 55784.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 38891.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 8835.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5497.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17769.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3181.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8307.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9573.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2975.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 385.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 4054.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1628.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 99854.04 | 8835.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 190.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 118.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 206.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 64.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 8.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 87.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2155.73 | 190.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 190.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 118.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 206.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 64.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 8.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 87.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2155.73 | 190.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 7.50 | 0.282430 | 0.300000 | 2.25 |
DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | 32.88 | 0.018159 | 0.500000 | 16.44 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 7.77 | 0.244906 | 0.300000 | 2.33 | 0.653084 | 0.500000 | 0.001556 | 0.000267 | 2.33 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 73.35 | 0.259327 | 0.300000 | 22.00 | 0.691537 | 0.500000 | 0.001469 | 0.005765 | 28.73 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 9.65 | 0.197014 | 0.300000 | 2.90 | 0.525371 | 0.500000 | 0.001934 | 0.001922 | 9.65 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.73 | 0.138223 | 0.300000 | 0.518339 | 0.368594 | 0.500000 | 0.002756 | 0.000344 | 1.73 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.96 | 0.078465 | 0.300000 | 0.588438 | 0.300000 | 0.500000 | 0.004856 | 0.000233 | 1.17 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 2.43 | 0.098316 | 0.300000 | 0.728752 | 0.300000 | 0.500000 | 0.003875 | 0.000379 | 1.91 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 2.36 | 0.065186 | 0.300000 | 0.708304 | 0.300000 | 0.500000 | 0.005845 | 0.000204 | 1.03 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 22.94 | 0.104125 | 0.300000 | 6.88 | 0.300000 | 0.500000 | 0.003659 | 0.004558 | 22.94 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 20.92 | 0.300000 | 0.500000 | 0.005179 | 0.003029 | 15.24 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 24.82 | 0.096236 | 0.300000 | 7.44 | 0.300000 | 0.500000 | 0.003959 | 0.004659 | 23.44 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 22.52 | 0.068353 | 0.300000 | 6.75 | 0.300000 | 0.500000 | 0.005574 | 0.003026 | 15.23 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 3.06 | 0.078014 | 0.300000 | 0.918376 | 0.300000 | 0.500000 | 0.004884 | 0.000608 | 3.06 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 2.10 | 0.073416 | 0.300000 | 0.628900 | 0.300000 | 0.500000 | 0.005190 | 0.000401 | 2.02 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 3.11 | 0.076681 | 0.300000 | 0.934358 | 0.300000 | 0.500000 | 0.004969 | 0.000619 | 3.11 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 2.41 | 0.063803 | 0.300000 | 0.723660 | 0.300000 | 0.500000 | 0.005972 | 0.000406 | 2.04 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 30574.13 | 0.000267 | 640.21 | |
CORE_MID VAV BOX REHEAT COIL | 658977.35 | 0.005765 | 15430.05 | |
CORE_TOP VAV BOX REHEAT COIL | 219686.05 | 0.001922 | 5132.78 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 39271.36 | 0.000344 | 917.25 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 26601.41 | 0.000233 | 621.31 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 43292.91 | 0.000379 | 1011.13 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 23364.07 | 0.000204 | 545.74 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 521019.10 | 0.004558 | 12167.41 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 346211.43 | 0.003029 | 8085.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 532536.00 | 0.004659 | 12436.25 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 345869.13 | 0.003026 | 8076.99 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 69515.92 | 0.000608 | 1623.25 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 45832.54 | 0.000401 | 1070.22 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 70724.46 | 0.000619 | 1651.47 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 46435.92 | 0.000406 | 1084.30 | |
VAV_BOT WITH REHEAT HEATING COIL | 94972.66 | 0.000831 | 1525.16 | |
VAV_MID WITH REHEAT HEATING COIL | 960493.12 | 0.008403 | 15280.34 | |
VAV_TOP WITH REHEAT HEATING COIL | 84131.47 | 0.000736 | 1419.05 | |
CAV_BAS HEATING COIL | 129267.29 | 0.000875 | 2622.30 | 100000.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 567830.08 | 0.000875 | 2622.30 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.815034 |
DATACENTER_MID_ZN_6 DIRECT AIR | 7.87 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.807895 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 8.12 | 4.87 | 16.25 | 6.91 | 13.16 | 13.16 | 0.300000 | 0.524815 | 13.16 |
VAV_MID WITH REHEAT | 82.27 | 49.36 | 164.54 | 105.58 | 122.27 | 122.27 | 0.300000 | 0.863483 | 122.27 |
VAV_TOP WITH REHEAT | 10.17 | 6.10 | 20.34 | 19.89 | 15.02 | 19.89 | 0.300000 | 1.00 | 19.89 |
CAV_BAS | 2.25 | 2.25 | 7.50 | 2.25 | 7.50 | 7.50 | 1.00 | 0.300000 | 7.50 |
AIRLOOP DATACENTER BASEMENT | 16.44 | 16.44 | 32.88 | 16.44 | 32.88 | 32.88 | 1.00 | 0.500000 | 32.88 |
AIRLOOP DATACENTER BOT | 0.815034 | 0.815034 | 0.815034 | 0.815034 | 0.815034 | 0.815034 | 1.00 | 1.00 | 0.815034 |
AIRLOOP DATACENTER MID | 7.87 | 7.87 | 7.87 | 7.87 | 7.87 | 7.87 | 1.00 | 1.00 | 7.87 |
AIRLOOP DATACENTER TOP | 0.807895 | 0.807895 | 0.807895 | 0.807895 | 0.807895 | 0.807895 | 1.00 | 1.00 | 0.807895 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 13.16 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 122.27 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 19.89 | |
CAV_BAS_OA_CONTROLLER | 7.50 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 32.88 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.815034 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 7.87 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.807895 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 24.94 | 6.67 | 11.04 | 0.009418 | 0.008500 | 251110.40 | 0.008969 | 13.16 |
VAV_MID WITH REHEAT COOLING COIL | 25.01 | 6.67 | 11.04 | 0.009520 | 0.008500 | 2379307.07 | 0.084983 | 122.27 |
VAV_TOP WITH REHEAT COOLING COIL | 24.82 | 6.67 | 11.06 | 0.009354 | 0.008500 | 372423.84 | 0.013302 | 19.89 |
CAV_BAS COOLING COIL | 24.79 | 6.67 | 11.03 | 0.009601 | 0.008500 | 141841.05 | 0.005066 | 7.50 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 27.03 | 6.67 | 15.01 | 0.008576 | 0.008500 | 456895.97 | 0.016319 | 32.88 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 13.16 |
VAV_MID WITH REHEAT FAN | 122.27 |
VAV_TOP WITH REHEAT FAN | 19.89 |
CAV_BAS SZVAV FAN | 7.50 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | 32.88 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.008969 | 0.000053 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000831 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.084983 | 0.000006 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.008403 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.013302 | 0.000036 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000736 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | Design Size Minimum Supply Air Temperature [C] | User-Specified Minimum Supply Air Temperature [C] | User-Specified Maximum Supply Air Temperature [C] | User-Specified Nominal Cooling Capacity [W] | Design Size Maximum Supply Air Temperature [C] | |
CAV_BAS_UNITARY_PACKAGE_DX | 7.50 | 7.50 | 7.50 | 2.25 | 141841.05 | 100000.00 | 1.00 | 5.33 | 12.89 | 32.11 | ||
AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | 32.88 | 32.88 | 32.88 | 16.44 | 456895.97 | 100000.00 | 1.00 | 15.89 | 29.11 | |||
AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | 0.815034 | 0.815034 | 0.815034 | 0.815034 | 28103.35 | 1.00 | 13491.71 | 29.11 | ||||
AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | 7.87 | 7.87 | 7.87 | 7.87 | 271511.16 | 1.00 | 130247.14 | 29.11 | ||||
AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | 0.807895 | 0.807895 | 0.807895 | 0.807895 | 27862.37 | 1.00 | 13373.52 | 29.11 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000304 | 0.000037 | 96450.70 | 100000.00 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | 0.815034 | 1401.56 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | 7.87 | 13530.51 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | 0.807895 | 1389.29 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
AIRLOOP DATACENTER BOT COOLING COIL | 0.815030 | 0.407517 | 0.543353 | 13491.71 | 6745.85 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER MID COOLING COIL | 7.87 | 3.93 | 5.25 | 130247.14 | 65123.57 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.807890 | 0.403947 | 0.538593 | 13373.52 | 6686.76 | 0.800660 | 0.800660 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BOT HEATING COIL | 28103.35 |
AIRLOOP DATACENTER MID HEATING COIL | 271511.16 |
AIRLOOP DATACENTER TOP HEATING COIL | 27862.37 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.128640 | 26507.96 | |
HEATSYS1 PUMP | 0.038139 | 11485.76 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.128640 | 15.44 |
HEATSYS1 | 0.038139 | 4.58 |
COOLSYS1_SUPPLY | 0.128640 | 15.44 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.128640 | 0.128640 | 539966.77 | 6.67 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 4359509.04 | 4359509.04 | 0.038139 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.064320 | 12234.64 |
COOLSYS1 CHILLER2 PUMP | 0.064320 | 12234.64 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.128640 | 0.064910 | 1817307.15 | 1817360.45 | 0.091080 |
COOLSYS1 CHILLER2 | 0.128640 | 0.064910 | 1817307.15 | 1817360.45 | 0.091080 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.182159 | 21.86 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.182159 | 63519.20 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 76.61 | 2176855.80 | 15.32 | 272106.97 |
TOWERWATERSYS COOLTOWER 2 | 76.61 | 2176855.80 | 15.32 | 272106.97 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 11.651 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 16.493 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 11.651 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 496.074 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 32383.100 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 32383.100 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 9130.649 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 9130.649 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
26 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
27 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
35 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
47 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
48 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
49 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
50 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
51 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
52 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
53 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
54 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
55 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
56 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
57 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
58 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
59 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
60 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
61 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
62 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
63 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
64 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
65 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
66 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
67 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
68 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
69 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
70 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
71 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
72 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
73 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
74 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
75 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
76 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
77 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
78 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
79 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
80 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
81 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
82 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
83 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
84 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
85 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
86 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
87 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
88 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
89 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
90 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
91 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
92 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
93 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
94 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
95 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
96 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
97 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
98 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
99 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
100 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
101 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
102 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
103 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
104 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
105 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
106 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
107 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
108 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
109 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
110 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
111 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
112 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
113 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
114 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
115 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
116 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
117 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
118 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
119 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
120 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
121 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.49 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.491 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.49 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.491 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.49 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.491 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.49 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.491 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.40797 | 0.37250 | 0.37250 | 0.53900 | 0.12971 | 0.15583 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.40797 | 0.37250 | 0.37250 | 0.53900 | 0.12971 | 0.15583 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.40797 | 0.37250 | 0.37250 | 0.53900 | 0.12971 | 0.15583 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.40797 | 0.37250 | 0.37250 | 0.53900 | 0.12971 | 0.15583 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone BASEMENT | 1.2500 |
3 | Zone CORE_BOTTOM | 1.2500 |
4 | Zone CORE_MID | 1.2500 |
5 | Zone CORE_TOP | 1.2500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.2500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.2500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.2500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone BASEMENT | 1.1500 |
3 | Zone CORE_BOTTOM | 1.1500 |
4 | Zone CORE_MID | 1.1500 |
5 | Zone CORE_TOP | 1.1500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.1500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.1500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.1500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 86066.67921 | 98976.68109 | 6.52081 | 7.49894 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 89147.73353 | 102519.89356 | 6.75340 | 7.76641 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 6669.69577 | 8337.11972 | 0.50008 | 1.07782 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 842087.61326 | 968400.75525 | 63.77870 | 73.34551 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 307786.43100 | 384733.03875 | 22.98756 | 28.73446 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 91268.72696 | 104959.03600 | 6.97531 | 8.02161 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 29.97600 | 1.27256E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 102035.21924 | 127544.02406 | 7.72348 | 9.65435 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 15115.92654 | 17383.31552 | 1.15528 | 1.32857 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.10000 | 1.27259E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 18228.06644 | 22785.08306 | 1.38224 | 1.72780 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 22317.05974 | 25664.61870 | 1.70562 | 1.96146 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:40:00 | 22.49467 | 1.27126E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 12346.29514 | 15432.86892 | 0.93639 | 1.17048 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 27638.43039 | 31784.19495 | 2.11232 | 2.42917 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 29.68667 | 1.27251E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 20091.85416 | 25114.81770 | 1.52406 | 1.90507 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 26863.10956 | 30892.57599 | 2.05306 | 2.36101 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.15733 | 1.27224E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 10846.14187 | 13557.67734 | 0.82221 | 1.02776 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 143125.00631 | 164593.75726 | 10.93922 | 12.58010 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10000 | 1.27259E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 241771.81788 | 302214.77235 | 18.34877 | 22.93596 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 238019.69863 | 273722.65342 | 18.19188 | 20.92066 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 23.63133 | 1.27146E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 160649.66528 | 200812.08159 | 12.19314 | 15.24142 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 282344.24295 | 324695.87939 | 21.57968 | 24.81663 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27253E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 247109.06706 | 308886.33383 | 18.75497 | 23.44371 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 256173.29432 | 294599.28847 | 19.57934 | 22.51624 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 160490.28304 | 200612.85380 | 12.18115 | 15.22644 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 17223.45463 | 19806.97282 | 1.31643 | 1.51389 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.10000 | 1.27259E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 32249.86864 | 40312.33580 | 2.44900 | 3.06125 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 23850.09052 | 27427.60409 | 1.82290 | 2.09633 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.33400 | 1.27158E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 21262.36936 | 26577.96170 | 1.61469 | 2.01837 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 30998.87774 | 35648.70940 | 2.36929 | 2.72469 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 32810.00667 | 41012.50834 | 2.49162 | 3.11453 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 27443.83921 | 31560.41510 | 2.09757 | 2.41220 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 21541.92895 | 26927.41119 | 1.63598 | 2.04498 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 9273.43215 | 10664.44697 | 0.70873 | 0.81503 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.80933 | 1.27166E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -32.70000 | 1.83376E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 89524.20294 | 102952.83338 | 6.84194 | 7.86823 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.80933 | 1.27166E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -32.70000 | 1.83376E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 9192.19894 | 10571.02878 | 0.70252 | 0.80789 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.80933 | 1.27166E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -32.70000 | 1.83376E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 374133.82275 | 430253.89616 | 28.59565 | 32.88500 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 25.26400 | 1.27174E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:20:00 | -32.70000 | 1.83376E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 183951.81 | 13.16452 | 13.16452 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 107240.73 | 6.90893 | 6.90893 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1718467.76 | 122.27455 | 122.27455 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 1068709.57 | 105.58199 | 105.58199 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 207559.62 | 15.01877 | 15.01877 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 101782.47 | 19.89347 | 19.89347 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 |
7 | CAV_BAS | Cooling | Sensible | 93999.94 | 7.49894 | 7.49894 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 90190.82 | 1.20016 | 1.20016 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 424271.39 | 32.88500 | 32.88500 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 24252.82 | 0.33839 | 0.33839 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 10459.85 | 0.81503 | 0.81503 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1120.38 | 1.56323E-002 | 1.56323E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 100963.97 | 7.86823 | 7.86823 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 11203.80 | 0.15632 | 0.15632 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 10367.88 | 0.80789 | 0.80789 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1120.38 | 1.56323E-002 | 1.56323E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 7.49894 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.28243 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 2.24968 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.76641 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24491 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.32992 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65308 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.55570E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.67476E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.32992 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30574.13112 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.67476E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 640.20865 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 73.34551 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25933 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 22.00365 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69154 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.46919E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.76502E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 28.73446 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 658977.34574 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.76502E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 15430.05203 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.65435 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19701 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.89631 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52537 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.93387E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.92191E-003 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.65435 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 219686.05355 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.92191E-003 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5132.78404 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.72780 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13822 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.51834 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36859 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.75642E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.43563E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.72780 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 39271.36226 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.43563E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 917.25211 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.96146 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.84646E-002 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.58844 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.85570E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.32721E-004 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.17048 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26601.41045 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.32721E-004 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 621.30537 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.42917 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.83157E-002 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.72875 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.87527E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.78745E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.90507 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 43292.91227 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.78745E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1011.13267 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.36101 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.51860E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.70830 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.84481E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.04399E-004 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.02776 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23364.06798 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.04399E-004 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 545.73528 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 22.93596 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10412 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.88079 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.65907E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.55810E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 22.93596 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 521019.09837 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.55810E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 12167.40658 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 20.92066 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.17902E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.02881E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 15.24142 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 346211.42739 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.02881E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8084.99999 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 24.81663 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.62362E-002 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 7.44499 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.95901E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.65886E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 23.44371 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 532536.00096 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.65886E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 12436.25037 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 22.51624 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.83529E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.75487 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.57401E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.02581E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 15.22644 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 345869.13155 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.02581E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8076.99445 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.06125 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.80140E-002 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.91838 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.88374E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.08156E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.06125 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 69515.92094 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.08156E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1623.25469 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.09633 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.34163E-002 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.62890 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.18958E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.00963E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.01837 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 45832.53754 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.00963E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1070.22017 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.11453 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.66813E-002 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.93436 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.96862E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.18728E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.11453 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 70724.46291 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.18728E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1651.46732 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.41220 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.38027E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.72366 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.97153E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.06242E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.04498 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 46435.91800 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.06242E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1084.30383 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.81503 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.86823 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.80789 |
215 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 32.88500 |
216 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 1.81592E-002 |
217 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
218 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 16.44250 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 8.12293 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.87376 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 16.24586 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 6.90893 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 13.16452 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 13.16452 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.52481 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 82.26750 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 49.36050 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 164.53500 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 105.58199 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 122.27455 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 122.27455 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.86348 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 10.16933 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.10160 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 20.33866 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 19.89347 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 15.01877 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 19.89347 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 1.00000 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.24968 |
244 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.24968 |
245 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.49894 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.24968 |
247 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.49894 |
248 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 7.49894 |
249 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.30000 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 16.44250 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 16.44250 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 32.88500 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 16.44250 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 32.88500 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 32.88500 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.50000 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.81503 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.81503 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.81503 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.81503 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.81503 |
264 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.81503 |
265 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.86823 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.86823 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.86823 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 7.86823 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.86823 |
272 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 7.86823 |
273 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
274 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.80789 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.80789 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.80789 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.80789 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.80789 |
280 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.80789 |
281 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
282 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
283 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 13.16452 |
284 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 122.27455 |
285 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 19.89347 |
286 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 7.49894 |
287 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 32.88500 |
288 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.81503 |
289 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 7.86823 |
290 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.80789 |
291 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 13.16452 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.93972 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.03582 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.41841E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 251110.39998 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.96908E-003 |
299 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 13.16452 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 94972.66125 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.30862E-004 |
302 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1525.15858 |
303 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 13.16452 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.96908E-003 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.30924E-005 |
306 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.30862E-004 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 122.27455 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.01187 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.03616 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.52020E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2379307.07353 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.49833E-002 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 122.27455 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 960493.12055 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.40281E-003 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 15280.33789 |
319 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 122.27455 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.49833E-002 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.60334E-006 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.40281E-003 |
323 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 19.89347 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.82444 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.06086 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.35431E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 372423.84485 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.33021E-002 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 19.89347 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 84131.47296 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.36019E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1419.04768 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 19.89347 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.33021E-002 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.57981E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.36019E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.49894 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.49894 |
342 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.49894 |
343 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.49894 |
344 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.24968 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.78964 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.02654 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.60108E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 141841.04758 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.06623E-003 |
352 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.49894 |
353 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 141841.04758 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 129267.29103 |
355 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
356 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
357 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.29956 |
358 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
359 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
360 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Minimum Supply Air Temperature [C] | 5.33423 |
361 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 12.88890 |
362 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 32.11110 |
363 | Fan:VariableVolume | CAV_BAS SZVAV FAN | Design Size Maximum Flow Rate [m3/s] | 7.49894 |
364 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 32.88500 |
365 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
366 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 32.88500 |
367 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 32.88500 |
368 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 32.88500 |
369 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 16.44250 |
370 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.02990 |
371 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
372 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 15.00754 |
373 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57607E-003 |
374 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
375 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Coil Load [W] | 456895.96598 |
376 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.63193E-002 |
377 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 32.88500 |
378 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 456895.96598 |
379 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Capacity [W] | 567830.08062 |
380 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
381 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
382 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.29956 |
383 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
384 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
385 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 15.88890 |
386 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 29.11110 |
387 | Fan:VariableVolume | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Design Size Maximum Flow Rate [m3/s] | 32.88500 |
388 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 3.04012E-004 |
389 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
390 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
391 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.81503 |
393 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
394 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.81503 |
395 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1401.56406 |
396 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.81503 |
397 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.81503 |
398 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.81503 |
399 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.81503 |
400 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.81503 |
401 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.40752 |
402 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.54335 |
403 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 13491.71000 |
404 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6745.85500 |
405 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
406 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
407 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 13491.71000 |
408 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28103.34539 |
409 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
410 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
411 | Coil:Heating:Fuel | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Nominal Capacity [W] | 28103.34539 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.86823 |
413 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
414 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.86823 |
415 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 13530.51476 |
416 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.86823 |
417 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.86823 |
418 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.86823 |
419 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 7.86823 |
420 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.86823 |
421 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.93411 |
422 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.24549 |
423 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 130247.14000 |
424 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 65123.57000 |
425 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
426 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
427 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 130247.14000 |
428 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 271511.15554 |
429 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
430 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
431 | Coil:Heating:Fuel | AIRLOOP DATACENTER MID HEATING COIL | Design Size Nominal Capacity [W] | 271511.15554 |
432 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.80789 |
433 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
434 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.80789 |
435 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1389.28704 |
436 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.80789 |
437 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.80789 |
438 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.80789 |
439 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.80789 |
440 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.80789 |
441 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.40395 |
442 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.53859 |
443 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 13373.52000 |
444 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6686.76000 |
445 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
446 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
447 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 13373.52000 |
448 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27862.36587 |
449 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
450 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
451 | Coil:Heating:Fuel | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Nominal Capacity [W] | 27862.36587 |
452 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.12864 |
453 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 26507.96461 |
454 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.12864 |
455 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 15.43680 |
456 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.12864 |
457 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.12864 |
458 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 539966.76640 |
459 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 6.67000 |
460 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.81389E-002 |
461 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 4.57667 |
462 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.81389E-002 |
463 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 11485.75785 |
464 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
465 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 4359509.03576 |
466 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 4359509.04000 |
467 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.81389E-002 |
468 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.12864 |
469 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 15.43680 |
470 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 6.43200E-002 |
471 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 12234.64126 |
472 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 6.43200E-002 |
473 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 12234.64126 |
474 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12864 |
475 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.49100E-002 |
476 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1817307.14988 |
477 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1817360.44500 |
478 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 9.10797E-002 |
479 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12864 |
480 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.49100E-002 |
481 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1817307.14988 |
482 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1817360.44500 |
483 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 9.10797E-002 |
484 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
485 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
486 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
487 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
488 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
489 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.18216 |
490 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 21.85912 |
491 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.18216 |
492 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 63519.19662 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 76.60573 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 2176855.79541 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 15.32115 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 272106.97443 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 76.60573 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 2176855.79541 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 15.32115 |
500 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 272106.97443 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 29023.99 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 625183.04 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 208421.84 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 37257.81 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 25237.48 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 41073.17 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 22166.12 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 494305.30 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 328460.42 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 505231.72 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 328135.68 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 65951.71 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 43482.62 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 67098.29 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 44055.07 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 69376.55 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 687594.87 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 67939.16 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94839.37 |
20 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | 94839.37 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 315932.54 | 218988.53 | 96944.01 | 0.69 | 39924.89 | 404.94 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2958482.28 | 2044131.15 | 914351.13 | 0.69 | 372641.75 | 3779.54 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 473428.07 | 329202.78 | 144225.28 | 0.70 | 59889.63 | 607.43 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 181811.34 | 125742.77 | 56068.57 | 0.69 | 23726.85 | 240.65 |
5 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | 586444.53 | 441693.20 | 144751.33 | 0.75 | 58409.46 | 592.42 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | 12853.0 | 9.16 | 9.16 | |||
2 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | 124080.7 | 10.40 | 10.40 | |||
3 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | 12740.4 | 9.16 | 9.16 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 6.37 | 21.74 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 6.37 | 21.74 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.49 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.49 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.49 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.49 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.49 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.49 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.49 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.49 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.49 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.49 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.49 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.49 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.49 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.49 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.49 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.49 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.49 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.49 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.49 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.49 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.49 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.49 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.49 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.49 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 2.4532538422E-003 | 1.5818918593E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1336546512 | 9.2693420926E-002 | Pass | Pass | 0.4864254472 | 0.4979982157 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.1382955923E-002 | 2.2255870643E-002 | Pass | Pass | 0.4873288802 | 0.4957581681 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.2370609745 | 0.2572844817 | Pass | Pass | 0.5928400565 | 0.5921987347 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5010203415 | 0.5091185729 | Pass | Pass | 0.6277636427 | 0.5467037147 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4512683582 | 0.5182552036 | Pass | Pass | 2.4190211479 | 21.4914046937 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4580440523 | 0.4851291879 | Pass | Pass | 1.8543323998 | 11.6991999823 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2420030670 | 0.2783017540 | Pass | Pass | 0.6482394917 | 0.8493228651 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.1185153919 | 1.0763747820 | Pass | Pass | 0.6037649057 | 0.5336166440 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.9880211524 | 1.0340540171 | Pass | Pass | 0.6155129681 | 0.5520288512 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.7232433463 | 0.8395326649 | Pass | Pass | 0.6284920588 | 0.5888412974 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.9350710120 | 1.0013415924 | Pass | Pass | 0.6292565304 | 0.5635302373 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.4290431753 | 1.3874518574 | Pass | Pass | 0.5739932964 | 0.5330484245 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.3016858941 | 1.3188759512 | Pass | Pass | 0.5834486341 | 0.5386958121 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.9612456452 | 1.1435969219 | Pass | Pass | 0.6176117673 | 0.6621785903 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.2557267591 | 1.3024106925 | Pass | Pass | 0.5907764190 | 0.5359358906 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.6305891749E-002 | 3.0803624980E-002 | Pass | Pass | 0.6759716488 | 0.8610150771 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1049030813 | 7.2972685017E-002 | Pass | Pass | 0.4807659078 | 0.4846504100 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.4827283677 | 0.3916625225 | Pass | Pass | 0.4885526897 | 0.4942412084 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.6547290364E-003 | 6.5773364106E-003 | Pass | Pass | 0.1131345707 | 0.6654367782 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.9066834645E-002 | 5.0855796842E-002 | Pass | Pass | 7.8135281518E-003 | 1.2968803847E-002 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.7934904822E-002 | 5.2036633351E-002 | Pass | Pass | 1.0000040007E-002 | 1.3545871481E-002 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.8054466361E-002 | 2.6747275582E-002 | Pass | Pass | 2.0195297023E-003 | 1.4277152955E-003 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6414.33 | 293.55 | 0.00 | 32219.05 | 14269.05 | 53195.99 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.49 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.49 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.49 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.57_SHGC_NORTH_0.49 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.57_SHGC_NORTH_0.49 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.49 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.49 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.57_SHGC_EAST_0.49 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.49 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.49 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.49 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.57_SHGC_SOUTH_0.49 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.57_SHGC_SOUTH_0.49 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.49 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.49 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.57_SHGC_WEST_0.49 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.49 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.491 | 0.541 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.49 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.491 | 0.541 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.49 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.491 | 0.541 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.49 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.491 | 0.541 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.49 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.491 | 0.541 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.49 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.491 | 0.541 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.49 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.491 | 0.541 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.49 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.491 | 0.541 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 3.241 | 0.491 | 0.541 | |||||||||||||||||
North Total or Average | 1390.74 | 3.241 | 0.491 | 0.541 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 3.241 | 0.491 | 0.541 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 11.6510 | 2779.43 | 32383.10 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 333.79 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.6510 | 24961.20 | 290822.99 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 2997.66 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.6510 | 3134.13 | 36515.73 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.6510 | 3134.20 | 36516.53 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 11.6510 | 783.68 | 9130.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 94.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 22.3674 | 362.03 | 8097.60 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 83.47 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
Interior Lighting Total | 11.7515 | 46320.38 | 544334.28 | 1723.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 64082.80 | AstronomicalClock | - | 83.52 | 83.52 | 1004.65 | |
Exterior Lighting Total | 64082.80 | 1004.65 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3592194.17 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 4359509.04 | 0.79 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1817360.45 | 6.11 | 1808492.71 | 6.08 | 6.37 | 21.74 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1817360.45 | 6.11 | 1808492.71 | 6.08 | 6.37 | 21.74 |
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 2176855.80 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 2176855.80 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 251110.40 | 315932.54 | 218988.53 | 96944.01 | 0.69 | - | 39924.89 | 404.94 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2379307.07 | 2958482.28 | 2044131.15 | 914351.13 | 0.69 | - | 372641.75 | 3779.54 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 372423.84 | 473428.07 | 329202.78 | 144225.28 | 0.70 | - | 59889.63 | 607.43 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 141841.05 | 181811.34 | 125742.77 | 56068.57 | 0.69 | - | 23726.85 | 240.65 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | 456895.97 | 586444.53 | 441693.20 | 144751.33 | 0.75 | - | 58409.46 | 592.42 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | 13491.71 | 10802.27 | 2689.44 | 0.80 | 3.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | 130247.14 | 104283.68 | 25963.46 | 0.80 | 3.50 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 13373.52 | 10707.64 | 2665.88 | 0.80 | 3.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
AIRLOOP DATACENTER BOT COOLING COIL | 12853.0 | 9.16 | 9.16 | ||||
AIRLOOP DATACENTER MID COOLING COIL | 124080.7 | 10.40 | 10.40 | ||||
AIRLOOP DATACENTER TOP COOLING COIL | 12740.4 | 9.16 | 9.16 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 30574.13 | 29023.99 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 658977.35 | 625183.04 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 219686.05 | 208421.84 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 39271.36 | 37257.81 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 26601.41 | 25237.48 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 43292.91 | 41073.17 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 23364.07 | 22166.12 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 521019.10 | 494305.30 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 346211.43 | 328460.42 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 532536.00 | 505231.72 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 345869.13 | 328135.68 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 69515.92 | 65951.71 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 45832.54 | 43482.62 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 70724.46 | 67098.29 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 46435.92 | 44055.07 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 94972.66 | 69376.55 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 960493.12 | 687594.87 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 84131.47 | 67939.16 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94839.37 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | 100000.00 | 94839.37 | - |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | 28103.35 | 0.80 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | 271511.16 | 0.79 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | 27862.37 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 13.16 | 28778.99 | 2186.10 | 1.00 | 1.11 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 122.27 | 267304.78 | 2186.10 | 1.00 | 1.08 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1337.13 | 19.89 | 42896.57 | 2156.31 | 1.00 | 1.12 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
CAV_BAS SZVAV FAN | Fan:VariableVolume | 0.61 | 1337.13 | 7.50 | 16481.02 | 2197.78 | 1.00 | 1.13 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 0.61 | 637.69 | 32.88 | 34139.85 | 1038.16 | 1.00 | 1.19 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.82 | 1401.56 | 1719.64 | 1.00 | 1.34 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 7.87 | 13530.51 | 1719.64 | 1.00 | 1.08 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.81 | 1389.29 | 1719.64 | 1.00 | 1.34 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.83 | 0.128640 | 26507.96 | 206063.11 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.038139 | 11485.76 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.064320 | 12234.64 | 190215.15 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.064320 | 12234.64 | 190215.15 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 209234.68 | 0.182159 | 63519.20 | 348701.22 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 86066.68 | 98976.68 | 35.61 | 6.521 | 7.499 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 20.92 | 0.01271 | 1.200 | 0.00 |
CORE_BOTTOM | 89147.73 | 102519.89 | 41.07 | 6.753 | 7.766 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00885 | 20.92 | 0.01271 | 1.078 | 0.00 |
CORE_MID | 842087.61 | 968400.76 | 387.96 | 63.779 | 73.346 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00887 | 20.92 | 0.01271 | 10.778 | 0.00 |
CORE_TOP | 91268.73 | 104959.04 | 42.05 | 6.975 | 8.022 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00883 | 29.98 | 0.01273 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 15115.93 | 17383.32 | 55.46 | 1.155 | 1.329 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00884 | 30.10 | 0.01273 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 22317.06 | 25664.62 | 127.07 | 1.706 | 1.961 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:40:00 | 24.00 | 24.00 | 0.00865 | 22.49 | 0.01271 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 27638.43 | 31784.19 | 101.41 | 2.112 | 2.429 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00869 | 29.69 | 0.01273 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 26863.11 | 30892.58 | 152.95 | 2.053 | 2.361 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00863 | 28.16 | 0.01272 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 143125.01 | 164593.76 | 525.17 | 10.939 | 12.580 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00898 | 30.10 | 0.01273 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 238019.70 | 273722.65 | 1355.23 | 18.192 | 20.921 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00870 | 23.63 | 0.01271 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 282344.24 | 324695.88 | 1035.98 | 21.580 | 24.817 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00875 | 29.79 | 0.01273 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 256173.29 | 294599.29 | 1458.59 | 19.579 | 22.516 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00868 | 27.95 | 0.01272 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 17223.45 | 19806.97 | 63.20 | 1.316 | 1.514 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00894 | 30.10 | 0.01273 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 23850.09 | 27427.60 | 135.80 | 1.823 | 2.096 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00872 | 24.33 | 0.01272 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 30998.88 | 35648.71 | 113.74 | 2.369 | 2.725 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00875 | 29.89 | 0.01273 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 27443.84 | 31560.42 | 156.26 | 2.098 | 2.412 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00869 | 27.95 | 0.01272 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 9273.43 | 10664.45 | 294.58 | 0.709 | 0.815 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 27.00 | 27.00 | 0.00856 | 24.81 | 0.01272 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 89524.20 | 102952.83 | 2843.79 | 6.842 | 7.868 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 27.00 | 27.00 | 0.00856 | 24.81 | 0.01272 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 9192.20 | 10571.03 | 292.00 | 0.703 | 0.808 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 27.00 | 27.00 | 0.00856 | 24.81 | 0.01272 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 374133.82 | 430253.90 | 549.02 | 28.596 | 32.885 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.00 | 27.00 | 0.00853 | 25.26 | 0.01272 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 22.48 | 0.00018 | -32.70 | 0.00018 | 1.200 | 0.00 |
CORE_BOTTOM | 6669.70 | 8337.12 | 3.34 | 0.500 | 1.078 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 1.078 | 0.00 |
CORE_MID | 307786.43 | 384733.04 | 154.13 | 22.988 | 28.734 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 10.778 | 0.00 |
CORE_TOP | 102035.22 | 127544.02 | 51.10 | 7.723 | 9.654 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 18228.07 | 22785.08 | 72.70 | 1.382 | 1.728 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -32.70 | 0.00018 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 12346.30 | 15432.87 | 76.41 | 0.936 | 1.170 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -32.70 | 0.00018 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 20091.85 | 25114.82 | 80.13 | 1.524 | 1.905 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -32.70 | 0.00018 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 10846.14 | 13557.68 | 67.13 | 0.822 | 1.028 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -32.70 | 0.00018 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 241771.82 | 302214.77 | 964.27 | 18.349 | 22.936 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -32.70 | 0.00018 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 160649.67 | 200812.08 | 994.24 | 12.193 | 15.241 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -32.70 | 0.00018 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 247109.07 | 308886.33 | 985.54 | 18.755 | 23.444 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -32.70 | 0.00018 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 160490.28 | 200612.85 | 993.26 | 12.181 | 15.226 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -32.70 | 0.00018 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 32249.87 | 40312.34 | 128.62 | 2.449 | 3.061 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -32.70 | 0.00018 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 21262.37 | 26577.96 | 131.59 | 1.615 | 2.018 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -32.70 | 0.00018 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 32810.01 | 41012.51 | 130.85 | 2.492 | 3.115 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -32.70 | 0.00018 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 21541.93 | 26927.41 | 133.32 | 1.636 | 2.045 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -32.70 | 0.00018 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.11 | 0.00099 | -32.70 | 0.00018 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.17 | 0.00099 | -32.70 | 0.00018 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 18.49 | 0.00098 | -32.70 | 0.00018 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:20:00 | 18.00 | 27.00 | 0.00850 | -32.70 | 0.00018 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 13.16 | 13.16 | 6.91 | 6.91 | 13.1645 | 6.9089 | 13.1645 | 0.5248 | 0.3000 |
VAV_MID WITH REHEAT | 122.27 | 122.27 | 105.58 | 105.58 | 122.2745 | 105.5820 | 122.2745 | 0.8635 | 0.3000 |
VAV_TOP WITH REHEAT | 15.02 | 15.02 | 19.89 | 19.89 | 15.0188 | 19.8935 | 19.8935 | 1.0000 | 0.3000 |
CAV_BAS | 7.50 | 7.50 | 1.20 | 1.20 | 7.4989 | 2.2497 | 7.4989 | 0.3000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 32.88 | 32.88 | 0.34 | 0.34 | 32.8850 | 16.4425 | 32.8850 | 0.5000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.82 | 0.82 | 0.02 | 0.02 | 0.8150 | 0.8150 | 0.8150 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 7.87 | 7.87 | 0.16 | 0.16 | 7.8682 | 7.8682 | 7.8682 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.81 | 0.81 | 0.02 | 0.02 | 0.8079 | 0.8079 | 0.8079 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 30574.131 | 30574.131 | 2.329924 | 0.00026748 | 640.209 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30574.13 | 30574.13 | 2.329924 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00799998 | 49.5594 | 8337.12 | 0.00 | 30724.45 | 30724.45 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 658977.346 | 658977.346 | 28.734456 | 0.00576502 | 15430.052 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 658977.35 | 658977.35 | 28.734456 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 384733.04 | 0.00 | 661995.63 | 661995.63 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 219686.054 | 219686.054 | 9.654352 | 0.00192191 | 5132.784 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 219686.05 | 218364.03 | 9.654352 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 127544.02 | 0.00 | 220693.15 | 220693.15 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 39271.362 | 39271.362 | 1.727797 | 0.00034356 | 917.252 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39271.36 | 39079.66 | 1.727797 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00790137 | 48.9577 | 22785.08 | 0.00 | 39451.42 | 39451.42 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 26601.410 | 26601.410 | 1.170485 | 0.00023272 | 621.305 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26601.41 | 26601.41 | 1.170485 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00790286 | 48.9669 | 15432.87 | 0.00 | 26723.38 | 26723.38 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 43292.912 | 43292.912 | 1.905069 | 0.00037875 | 1011.133 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 43292.91 | 43292.91 | 1.905069 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00791024 | 49.0119 | 25114.82 | 0.00 | 43491.41 | 43491.41 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 23364.068 | 23364.068 | 1.027757 | 0.00020440 | 545.735 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23364.07 | 23364.07 | 1.027757 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00788963 | 48.8859 | 13557.68 | 0.00 | 23471.19 | 23471.19 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 521019.098 | 521019.098 | 22.935964 | 0.00455810 | 12167.407 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 521019.10 | 518770.15 | 22.935964 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00782651 | 48.5014 | 302214.77 | 0.00 | 523408.05 | 523408.05 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 346211.427 | 346211.427 | 15.241423 | 0.00302881 | 8085.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 346211.43 | 346211.43 | 15.241423 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00782587 | 48.4975 | 200812.08 | 0.00 | 347798.87 | 347798.87 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 532536.001 | 532536.001 | 23.443712 | 0.00465886 | 12436.250 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 532536.00 | 532536.00 | 23.443712 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00783016 | 48.5237 | 308886.33 | 0.00 | 534977.77 | 534977.77 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 345869.132 | 345869.132 | 15.226435 | 0.00302581 | 8076.994 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 345869.13 | 345869.13 | 15.226435 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00782586 | 48.4975 | 200612.85 | 0.00 | 347455.00 | 347455.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 69515.921 | 69515.921 | 3.061252 | 0.00060816 | 1623.255 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 69515.92 | 69240.01 | 3.061252 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00783749 | 48.5692 | 40312.34 | 0.00 | 69834.67 | 69834.67 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 45832.538 | 45832.538 | 2.018367 | 0.00040096 | 1070.220 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 45832.54 | 45832.54 | 2.018367 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00783568 | 48.5582 | 26577.96 | 0.00 | 46042.70 | 46042.70 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 70724.463 | 70724.463 | 3.114526 | 0.00061873 | 1651.467 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 70724.46 | 70444.96 | 3.114526 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00784023 | 48.5859 | 41012.51 | 0.00 | 71048.76 | 71048.76 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 46435.918 | 46435.918 | 2.044977 | 0.00040624 | 1084.304 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 46435.92 | 46435.92 | 2.044977 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00783796 | 48.5721 | 26927.41 | 0.00 | 46648.84 | 46648.84 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 251110.400 | -999.000 | 13.164517 | 0.00896908 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 251110.40 | 215746.53 | 13.164517 | 24.94 | 17.04 | 0.00941841 | 11.04 | 10.99 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 15.4240 | 24.00 | 0.00881523 | 45.4542 | 149782.76 | 0.00 | 259364.59 | 210528.39 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 94972.661 | 94972.661 | 3.949355 | 0.00083086 | 1525.159 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 94972.66 | 94972.66 | 3.949355 | -7.85 | -7.85 | 0.00387135 | 12.89 | 11.26 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 51.4135 | 18.79 | 0.00782839 | 55.6292 | 15036.87 | 0.00 | 83939.24 | 83939.24 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2379307.074 | -999.000 | 122.274549 | 0.08498333 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 2379307.07 | 2014387.45 | 122.274549 | 25.01 | 17.15 | 0.00952020 | 11.04 | 10.99 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 16.6069 | 24.00 | 0.00888168 | 45.7927 | 1390901.36 | 0.00 | 2455773.44 | 1966952.66 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 960493.121 | 960493.121 | 36.682365 | 0.00840281 | 15280.338 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 960493.12 | 960493.12 | 36.682365 | -9.69 | -9.69 | 0.00355120 | 12.89 | 11.26 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 55.3563 | 18.61 | 0.00784356 | 56.3547 | 158503.38 | 0.00 | 831803.35 | 831803.35 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 372423.845 | -999.000 | 19.893475 | 0.01330212 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 372423.84 | 322800.34 | 19.893475 | 24.82 | 16.95 | 0.00935431 | 11.06 | 11.00 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 10.2069 | 24.00 | 0.00882636 | 45.5116 | 170633.07 | 0.00 | 384788.96 | 314963.85 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 84131.473 | 84131.473 | 5.968042 | 0.00073602 | 1419.048 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 84131.47 | 84131.47 | 5.968042 | 0.73 | 0.73 | 0.00512091 | 12.89 | 11.26 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 34.0229 | 16.76 | 0.00785590 | 63.4570 | 29434.96 | 0.00 | 82238.03 | 82238.03 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 141841.048 | -999.000 | 7.498936 | 0.00506623 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 141841.05 | 118336.30 | 7.498936 | 24.79 | 17.14 | 0.00960108 | 11.03 | 10.99 | 0.00850000 | 28.49 | 0.01272303 | 20.66 | 16.0044 | 24.00 | 0.00893341 | 46.0548 | 77505.03 | 0.00 | 150554.62 | 119036.65 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.170652 | 0.00087484 | 2622.300 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.170652 | -5.23 | -9.59 | 0.00018338 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 37.8520 | 22.59 | 0.00018338 | 1.0438 | 0.00 | 0.00 | 100072.50 | 100072.50 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 456895.966 | -999.000 | 32.884996 | 0.01631927 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 456895.97 | 451554.48 | 32.884996 | 27.03 | 17.06 | 0.00857607 | 15.01 | 12.60 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 1.0290 | 27.00 | 0.00853287 | 36.8357 | 373651.11 | 0.00 | 488445.44 | 488445.44 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 100000.000 | 100000.000 | 3.170652 | 0.00087484 | 2622.300 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.170652 | -0.34 | -0.34 | 0.00841442 | 29.11 | 17.29 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 10.6727 | 27.00 | 0.00850000 | 36.6913 | 0.00 | 0.00 | 100072.50 | 100072.50 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER BOT | 13491.710 | 10802.273 | 0.815030 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 6745.85 | 6600.78 | 0.543353 | 26.96 | 17.09 | 0.00864070 | 14.43 | 12.38 | 0.00850000 | 24.81 | 0.01271660 | 19.55 | 2.8770 | 27.00 | 0.00856100 | 36.9535 | 9273.43 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER BOT | 28103.345 | 28103.345 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 28103.35 | 28103.35 | 0.815034 | -0.63 | -5.10 | 0.00096991 | 29.11 | 17.29 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 1.9180 | 24.77 | 0.00098529 | 4.9117 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER MID | 130247.140 | 104283.675 | 7.868230 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 65123.57 | 63674.57 | 5.245487 | 26.96 | 17.09 | 0.00864567 | 14.43 | 12.38 | 0.00850000 | 24.81 | 0.01271660 | 19.55 | 2.9802 | 27.00 | 0.00856315 | 36.9627 | 89524.20 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER MID | 271511.156 | 271511.156 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 271511.16 | 271511.16 | 7.868230 | -0.65 | -5.12 | 0.00096939 | 29.11 | 17.29 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 1.9868 | 23.39 | 0.00098533 | 5.3374 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER TOP | 13373.520 | 10707.643 | 0.807890 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 6686.76 | 6541.62 | 0.538593 | 26.96 | 17.09 | 0.00864203 | 14.43 | 12.38 | 0.00850000 | 24.81 | 0.01271660 | 19.55 | 2.9024 | 27.00 | 0.00856163 | 36.9562 | 9192.20 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER TOP | 27862.366 | 27862.366 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 27862.37 | 27862.37 | 0.807895 | -0.63 | -5.11 | 0.00096819 | 29.11 | 17.29 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 1.9349 | 20.78 | 0.00098367 | 6.2476 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 30574.131 | 30574.131 | 2.329924 | 0.00026748 | 640.209 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.13499627 | 54.44 | 82.22 | 27.78 | 4447245.89 | 0.6875 | 0.701321 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30574.13 | 30574.13 | 1.0000 | 2.68855725 | 2.329924 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.26744855 | 60.00 | 32.22 | 27.78 | 0.000 | 30574.13 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.83 | 0.00799998 | 21.00 | 0.00799998 | 49.5594 | 8337.12 | 0.00 | 30724.45 | 30724.45 | 2.68855725 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 24.01 | 15.96 | 0.00800000 | 44487.7 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 658977.346 | 658977.346 | 28.734456 | 0.00576502 | 15430.052 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.13499627 | 54.44 | 82.22 | 27.78 | 4447245.89 | 14.8177 | 15.115861 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 658977.35 | 658977.35 | 1.0000 | 33.15740281 | 28.734456 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 5.76443320 | 60.00 | 32.22 | 27.78 | 0.000 | 658977.35 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 384733.04 | 0.00 | 661995.63 | 661995.63 | 33.15740281 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.38 | 18.82 | 0.00800000 | 53025.1 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 219686.054 | 219686.054 | 9.654352 | 0.00192191 | 5132.784 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.13499627 | 54.44 | 82.22 | 27.78 | 4447245.89 | 4.9398 | 5.039238 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 219686.05 | 218364.03 | 1.0000 | 11.14039676 | 9.654352 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 1.92171338 | 60.00 | 32.22 | 27.78 | 0.000 | 219686.05 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 127544.02 | 0.00 | 220693.15 | 220693.15 | 11.14039676 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52870.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 39271.362 | 39271.362 | 1.727797 | 0.00034356 | 917.252 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.13499627 | 54.44 | 82.22 | 27.78 | 4447245.89 | 0.8830 | 0.900821 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39271.36 | 39079.66 | 1.0000 | 1.99374813 | 1.727797 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.34352796 | 60.00 | 32.22 | 27.78 | 0.000 | 39271.36 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00790137 | 21.00 | 0.00790137 | 48.9577 | 22785.08 | 0.00 | 39451.42 | 39451.42 | 1.99374813 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.76 | 0.00800000 | 52847.4 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26601.410 | 26601.410 | 1.170485 | 0.00023272 | 621.305 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.13499627 | 54.44 | 82.22 | 27.78 | 4447245.89 | 0.5982 | 0.610193 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26601.41 | 26601.41 | 1.0000 | 1.35065171 | 1.170485 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.23269700 | 60.00 | 32.22 | 27.78 | 0.000 | 26601.41 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00790286 | 21.00 | 0.00790286 | 48.9669 | 15432.87 | 0.00 | 26723.38 | 26723.38 | 1.35065171 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52845.4 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 43292.912 | 43292.912 | 1.905069 | 0.00037875 | 1011.133 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.13499627 | 54.44 | 82.22 | 27.78 | 4447245.89 | 0.9735 | 0.993069 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 43292.91 | 43292.91 | 1.0000 | 2.19830686 | 1.905069 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.37870665 | 60.00 | 32.22 | 27.78 | 0.000 | 43292.91 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00791024 | 21.00 | 0.00791024 | 49.0119 | 25114.82 | 0.00 | 43491.41 | 43491.41 | 2.19830686 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52843.9 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23364.068 | 23364.068 | 1.027757 | 0.00020440 | 545.735 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.13499627 | 54.44 | 82.22 | 27.78 | 4447245.89 | 0.5254 | 0.535933 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23364.07 | 23364.07 | 1.0000 | 1.18595379 | 1.027757 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.20437821 | 60.00 | 32.22 | 27.78 | 0.000 | 23364.07 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00788963 | 21.00 | 0.00788963 | 48.8859 | 13557.68 | 0.00 | 23471.19 | 23471.19 | 1.18595379 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52850.8 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 521019.098 | 521019.098 | 22.935964 | 0.00455810 | 12167.407 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.13499627 | 54.44 | 82.22 | 27.78 | 4447245.89 | 11.7155 | 11.951325 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 521019.10 | 518770.15 | 1.0000 | 26.46637894 | 22.935964 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 4.55763739 | 60.00 | 32.22 | 27.78 | 0.000 | 521019.10 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.94 | 0.00782651 | 21.00 | 0.00782651 | 48.5014 | 302214.77 | 0.00 | 523408.05 | 523408.05 | 26.46637894 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52836.2 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 346211.427 | 346211.427 | 15.241423 | 0.00302881 | 8085.000 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.13499627 | 54.44 | 82.22 | 27.78 | 4447245.89 | 7.7849 | 7.941523 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 346211.43 | 346211.43 | 1.0000 | 17.58745641 | 15.241423 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 3.02849963 | 60.00 | 32.22 | 27.78 | 0.000 | 346211.43 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.94 | 0.00782587 | 21.00 | 0.00782587 | 48.4975 | 200812.08 | 0.00 | 347798.87 | 347798.87 | 17.58745641 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52835.2 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 532536.001 | 532536.001 | 23.443712 | 0.00465886 | 12436.250 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.13499627 | 54.44 | 82.22 | 27.78 | 4447245.89 | 11.9745 | 12.215504 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 532536.00 | 532536.00 | 1.0000 | 27.05228172 | 23.443712 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 4.65838200 | 60.00 | 32.22 | 27.78 | 0.000 | 532536.00 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.94 | 0.00783016 | 21.00 | 0.00783016 | 48.5237 | 308886.33 | 0.00 | 534977.77 | 534977.77 | 27.05228172 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52835.5 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 345869.132 | 345869.132 | 15.226435 | 0.00302581 | 8076.994 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.13499627 | 54.44 | 82.22 | 27.78 | 4447245.89 | 7.7772 | 7.933672 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 345869.13 | 345869.13 | 1.0000 | 17.57016187 | 15.226435 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 3.02550538 | 60.00 | 32.22 | 27.78 | 0.000 | 345869.13 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.94 | 0.00782586 | 21.00 | 0.00782586 | 48.4975 | 200612.85 | 0.00 | 347455.00 | 347455.00 | 17.57016187 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52835.1 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 69515.921 | 69515.921 | 3.061252 | 0.00060816 | 1623.255 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.13499627 | 54.44 | 82.22 | 27.78 | 4447245.89 | 1.5631 | 1.594581 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 69515.92 | 69240.01 | 1.0000 | 3.53245531 | 3.061252 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.60809356 | 60.00 | 32.22 | 27.78 | 0.000 | 69515.92 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.94 | 0.00783749 | 21.00 | 0.00783749 | 48.5692 | 40312.34 | 0.00 | 69834.67 | 69834.67 | 3.53245531 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52829.3 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 45832.538 | 45832.538 | 2.018367 | 0.00040096 | 1070.220 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.13499627 | 54.44 | 82.22 | 27.78 | 4447245.89 | 1.0306 | 1.051323 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 45832.54 | 45832.54 | 1.0000 | 2.32904398 | 2.018367 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.40092213 | 60.00 | 32.22 | 27.78 | 0.000 | 45832.54 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.94 | 0.00783568 | 21.00 | 0.00783568 | 48.5582 | 26577.96 | 0.00 | 46042.70 | 46042.70 | 2.32904398 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52828.8 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 70724.463 | 70724.463 | 3.114526 | 0.00061873 | 1651.467 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.13499627 | 54.44 | 82.22 | 27.78 | 4447245.89 | 1.5903 | 1.622303 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 70724.46 | 70444.96 | 1.0000 | 3.59392895 | 3.114526 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.61866534 | 60.00 | 32.22 | 27.78 | 0.000 | 70724.46 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.94 | 0.00784023 | 21.00 | 0.00784023 | 48.5859 | 41012.51 | 0.00 | 71048.76 | 71048.76 | 3.59392895 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52828.9 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 46435.918 | 46435.918 | 2.044977 | 0.00040624 | 1084.304 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 38.13499627 | 54.44 | 82.22 | 27.78 | 4447245.89 | 1.0442 | 1.065164 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 46435.92 | 46435.92 | 1.0000 | 2.35975018 | 2.044977 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.40620023 | 60.00 | 32.22 | 27.78 | 0.000 | 46435.92 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.94 | 0.00783796 | 21.00 | 0.00783796 | 48.5721 | 26927.41 | 0.00 | 46648.84 | 46648.84 | 2.35975018 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52828.4 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 251110.400 | -999.000 | 13.164517 | 0.00896908 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.3484 | 1004.8586 | 1.1539 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 13.164517 | 15.19086392 | 4197.9300 | 999.8980 | 128.62691050 | 13.34 | 6.67 | 6.67 | 3601578.33 | 6.9722 | 6.972232 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 251110.40 | 215746.53 | 1.0000 | 15.19086392 | 13.164517 | 24.94 | 17.04 | 0.00941841 | 49052.0 | 11.04 | 10.99 | 0.00850000 | 32521.6 | 8.96816672 | 6.67 | 13.34 | 6.67 | 28778.993 | 222331.41 | 30.10 | 0.01272586 | 21.13 | 2.03050000 | 15.4240 | 24.00 | 0.00881523 | 24.00 | 0.00881523 | 45.4542 | 149782.76 | 0.00 | 259364.59 | 210528.39 | 15.19086392 | 24.94 | 17.49 | 0.00941841 | 49052.0 | 11.38 | 11.14 | 0.00814374 | 31978.2 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 94972.661 | 94972.661 | 3.949355 | 0.00083086 | 1525.159 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 13.164517 | 15.19086392 | 4197.9300 | 999.8980 | 38.13499627 | 54.44 | 82.22 | 27.78 | 4447245.89 | 2.1355 | 2.178517 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 94972.66 | 94972.66 | 1.0000 | 4.55725918 | 3.949355 | -7.85 | -7.85 | 0.00387135 | 1737.3 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 0.83077751 | 60.00 | 32.22 | 27.78 | 0.000 | 94972.66 | -32.70 | 0.00018338 | -32.70 | 2.03050000 | 51.4135 | 18.45 | 0.00777391 | 18.79 | 0.00782839 | 55.6292 | 15036.87 | 0.00 | 83939.24 | 83939.24 | 4.55725918 | 2.80 | 1.77 | 0.00387135 | 12515.7 | 21.00 | 10.79 | 0.00387135 | 30934.5 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2379307.074 | -999.000 | 122.274549 | 0.08498333 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.5376 | 1004.8586 | 1.1539 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 122.274549 | 141.09564197 | 4197.9300 | 999.8980 | 128.62691050 | 13.34 | 6.67 | 6.67 | 3601578.33 | 66.0629 | 66.062899 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 2379307.07 | 2014387.45 | 1.0000 | 141.09564197 | 122.274549 | 25.01 | 17.15 | 0.00952020 | 49385.0 | 11.04 | 10.99 | 0.00850000 | 32522.0 | 84.97466660 | 6.67 | 13.34 | 6.67 | 267304.779 | 2112002.29 | 30.10 | 0.01272586 | 21.13 | 20.30600000 | 16.6069 | 24.00 | 0.00888168 | 24.00 | 0.00888168 | 45.7927 | 1390901.36 | 0.00 | 2455773.44 | 1966952.66 | 141.09564197 | 25.01 | 17.60 | 0.00952020 | 49385.0 | 11.38 | 11.14 | 0.00814656 | 31980.0 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 960493.121 | 960493.121 | 36.682365 | 0.00840281 | 15280.338 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 122.274549 | 141.09564197 | 4197.9300 | 999.8980 | 38.13499627 | 54.44 | 82.22 | 27.78 | 4447245.89 | 21.5975 | 22.032140 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 960493.12 | 960493.12 | 1.0000 | 42.32869259 | 36.682365 | -9.69 | -9.69 | 0.00355120 | -922.3 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 8.40195565 | 60.00 | 32.22 | 27.78 | 0.000 | 960493.12 | -32.70 | 0.00018338 | -32.70 | 20.30600000 | 55.3563 | 18.84 | 0.00772715 | 18.61 | 0.00784356 | 56.3547 | 158503.38 | 0.00 | 831803.35 | 831803.35 | 42.32869259 | 2.80 | 1.31 | 0.00355120 | 11713.4 | 22.23 | 10.98 | 0.00355120 | 31364.4 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 372423.845 | -999.000 | 19.893475 | 0.01330212 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.2292 | 1004.8586 | 1.1539 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 19.893475 | 22.95557518 | 4197.9300 | 999.8980 | 128.62691050 | 13.34 | 6.67 | 6.67 | 3601578.33 | 10.3406 | 10.340573 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 372423.84 | 322800.34 | 1.0000 | 22.95557518 | 19.893475 | 24.82 | 16.95 | 0.00935431 | 48770.8 | 11.06 | 11.00 | 0.00850000 | 32547.2 | 13.30075987 | 6.67 | 13.34 | 6.67 | 42896.568 | 329527.28 | 30.10 | 0.01272586 | 21.13 | 2.03050000 | 10.2069 | 24.00 | 0.00882636 | 24.00 | 0.00882636 | 45.5116 | 170633.07 | 0.00 | 384788.96 | 314963.85 | 22.95557518 | 24.82 | 17.40 | 0.00935431 | 48770.8 | 11.40 | 11.16 | 0.00814829 | 32008.5 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 84131.473 | 84131.473 | 5.968042 | 0.00073602 | 1419.048 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 19.893475 | 22.95557518 | 4197.9300 | 999.8980 | 38.13499627 | 54.44 | 82.22 | 27.78 | 4447245.89 | 1.8918 | 1.929838 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 84131.47 | 84131.47 | 1.0000 | 6.88667256 | 5.968042 | 0.73 | 0.73 | 0.00512091 | 13549.0 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 0.73594375 | 60.00 | 32.22 | 27.78 | 0.000 | 84131.47 | -32.70 | 0.00018338 | -32.70 | 2.03050000 | 34.0229 | 17.97 | 0.00766708 | 16.76 | 0.00785590 | 63.4570 | 29434.96 | 0.00 | 82238.03 | 82238.03 | 6.88667256 | 2.80 | 2.80 | 0.00512091 | 15647.3 | 14.57 | 9.31 | 0.00512091 | 27588.9 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 141841.048 | -999.000 | 7.498936 | 0.00506623 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.6879 | 1004.8586 | 1.1539 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 7.498936 | 8.65320852 | 4197.9300 | 999.8980 | 128.62691050 | 13.34 | 6.67 | 6.67 | 3601578.33 | 3.9383 | 3.938302 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 141841.05 | 118336.30 | 1.0000 | 8.65320852 | 7.498936 | 24.79 | 17.14 | 0.00960108 | 49363.8 | 11.03 | 10.99 | 0.00850000 | 32512.1 | 5.06571676 | 6.67 | 13.34 | 6.67 | 16481.019 | 125360.03 | 28.49 | 0.01272303 | 20.66 | 1.20015641 | 16.0044 | 24.00 | 0.00893341 | 24.00 | 0.00893341 | 46.0548 | 77505.03 | 0.00 | 150554.62 | 119036.65 | 8.65320852 | 24.79 | 17.59 | 0.00960108 | 49363.8 | 11.34 | 11.14 | 0.00815686 | 31965.1 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.170652 | 0.00087484 | 2622.300 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 7.498936 | 8.65320852 | 4197.9300 | 999.8980 | 38.13499627 | 54.44 | 82.22 | 27.78 | 4447245.89 | 2.2486 | 2.293836 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.170652 | -5.23 | -9.59 | 0.00018338 | -4801.9 | 32.11 | 18.27 | 0.00800000 | 52750.5 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -32.70 | 0.00018338 | -32.70 | 1.20015641 | 37.8520 | 0.00 | 0.00018338 | 22.59 | 0.00018338 | 1.0438 | 0.00 | 0.00 | 100072.50 | 100072.50 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40239.2 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 456895.966 | -999.000 | 32.884996 | 0.01631927 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7825 | 1004.8586 | 1.1539 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 32.884996 | 37.94681391 | 4197.9300 | 999.8980 | 128.62691050 | 13.34 | 6.67 | 6.67 | 3601578.33 | 12.6860 | 12.685993 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 456895.97 | 451554.48 | 1.0000 | 37.94681391 | 32.884996 | 27.03 | 17.06 | 0.00857607 | 49039.9 | 15.01 | 12.60 | 0.00850000 | 36575.3 | 16.31760054 | 6.67 | 13.34 | 6.67 | 34139.845 | 422756.12 | 30.10 | 0.01272586 | 21.13 | 0.33839277 | 1.0290 | 27.00 | 0.00853287 | 27.00 | 0.00853287 | 36.8357 | 373651.11 | 0.00 | 488445.44 | 488445.44 | 37.94681391 | 27.03 | 17.51 | 0.00857607 | 49039.9 | 14.42 | 12.84 | 0.00857607 | 36168.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.170652 | 0.00087484 | 2622.300 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 32.884996 | 37.94681391 | 4197.9300 | 999.8980 | 38.13499627 | 54.44 | 82.22 | 27.78 | 4447245.89 | 2.2486 | 2.293836 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.170652 | -0.34 | -0.34 | 0.00841442 | 20700.6 | 29.11 | 17.29 | 0.00800000 | 49691.3 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -32.70 | 0.00018338 | -32.70 | 0.33839277 | 10.6727 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 36.6913 | 0.00 | 0.00 | 100072.50 | 100072.50 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40239.2 | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13491.710 | 10802.273 | 0.815030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9026 | 1004.8586 | 1.1539 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.815034 | 0.94048789 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 6745.85 | 6600.78 | 1.0000 | 0.62698892 | 0.543353 | 26.96 | 17.09 | 0.00864070 | 49130.2 | 14.43 | 12.38 | 0.00850000 | 35985.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6745.85 | 24.81 | 0.01271660 | 19.55 | 0.01563234 | 2.8770 | 27.00 | 0.00856100 | 27.00 | 0.00856100 | 36.9535 | 9273.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28103.345 | 28103.345 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.815034 | 0.94048789 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 28103.35 | 28103.35 | 1.0000 | 0.94048789 | 0.815034 | -0.63 | -5.10 | 0.00096991 | 1794.3 | 29.11 | 17.29 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28103.35 | -32.70 | 0.00018338 | -32.70 | 0.01563234 | 1.9180 | 0.00 | 0.00098529 | 24.77 | 0.00098529 | 4.9117 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 130247.140 | 104283.675 | 7.868230 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9119 | 1004.8586 | 1.1539 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.868230 | 9.07934616 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 65123.57 | 63674.57 | 1.0000 | 6.05289745 | 5.245487 | 26.96 | 17.09 | 0.00864567 | 49141.3 | 14.43 | 12.38 | 0.00850000 | 35985.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 65123.57 | 24.81 | 0.01271660 | 19.55 | 0.15632344 | 2.9802 | 27.00 | 0.00856315 | 27.00 | 0.00856315 | 36.9627 | 89524.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 271511.156 | 271511.156 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.868230 | 9.07934616 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 271511.16 | 271511.16 | 1.0000 | 9.07934616 | 7.868230 | -0.65 | -5.12 | 0.00096939 | 1770.4 | 29.11 | 17.29 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 271511.16 | -32.70 | 0.00018338 | -32.70 | 0.15632344 | 1.9868 | 0.00 | 0.00098533 | 23.39 | 0.00098533 | 5.3374 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13373.520 | 10707.643 | 0.807890 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9051 | 1004.8586 | 1.1539 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.807895 | 0.93224967 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 6686.76 | 6541.62 | 1.0000 | 0.62149623 | 0.538593 | 26.96 | 17.09 | 0.00864203 | 49133.2 | 14.43 | 12.38 | 0.00850000 | 35985.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6686.76 | 24.81 | 0.01271660 | 19.55 | 0.01563234 | 2.9024 | 27.00 | 0.00856163 | 27.00 | 0.00856163 | 36.9562 | 9192.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27862.366 | 27862.366 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.807895 | 0.93224967 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 27862.37 | 27862.37 | 1.0000 | 0.93224967 | 0.807895 | -0.63 | -5.11 | 0.00096819 | 1784.5 | 29.11 | 17.29 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27862.37 | -32.70 | 0.00018338 | -32.70 | 0.01563234 | 1.9349 | 0.00 | 0.00098367 | 20.78 | 0.00098367 | 6.2476 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 13.16 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 122.27 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 19.89 | - | |||
CAV_BAS_OA_CONTROLLER | FixedDryBulb | 1.20 | 7.50 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 32.88 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1888.33 | 2943.67 | 50.50 |
CORE_BOTTOM | 1914.00 | 2588.67 | 47.83 |
CORE_MID | 1953.83 | 3612.67 | 521.50 |
CORE_TOP | 2969.00 | 4597.50 | 2014.33 |
PERIMETER_BOT_ZN_3 | 3295.00 | 4110.50 | 1898.83 |
PERIMETER_BOT_ZN_2 | 3181.00 | 4267.00 | 1883.83 |
PERIMETER_BOT_ZN_1 | 3193.00 | 3880.33 | 1651.83 |
PERIMETER_BOT_ZN_4 | 2935.33 | 4074.00 | 1426.83 |
PERIMETER_MID_ZN_3 | 3491.50 | 4846.67 | 2656.67 |
PERIMETER_MID_ZN_2 | 3028.33 | 3905.33 | 2152.33 |
PERIMETER_MID_ZN_1 | 3342.83 | 4121.67 | 1973.00 |
PERIMETER_MID_ZN_4 | 3360.83 | 4750.00 | 2435.67 |
PERIMETER_TOP_ZN_3 | 3682.67 | 5204.50 | 3134.33 |
PERIMETER_TOP_ZN_2 | 3873.33 | 4682.67 | 2854.00 |
PERIMETER_TOP_ZN_1 | 3599.17 | 4507.50 | 2490.50 |
PERIMETER_TOP_ZN_4 | 3675.00 | 4910.17 | 2868.67 |
DATACENTER_BOT_ZN_6 | 5561.17 | 1131.83 | 1121.33 |
DATACENTER_MID_ZN_6 | 4722.17 | 676.33 | 499.17 |
DATACENTER_TOP_ZN_6 | 3981.17 | 1180.50 | 572.33 |
DATACENTER_BASEMENT_ZN_6 | 5938.50 | 3336.67 | 3336.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5941.50 | 5487.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 1.33 | 12.83 | 1.33 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 2.33 | 0.00 | 0.50 | 0.00 |
CORE_TOP | 40.00 | 0.00 | 3.50 | 0.00 |
PERIMETER_BOT_ZN_3 | 60.67 | 0.00 | 10.33 | 0.00 |
PERIMETER_BOT_ZN_2 | 59.50 | 13.17 | 6.00 | 13.17 |
PERIMETER_BOT_ZN_1 | 63.83 | 21.50 | 6.00 | 21.50 |
PERIMETER_BOT_ZN_4 | 22.50 | 30.83 | 1.00 | 16.50 |
PERIMETER_MID_ZN_3 | 225.67 | 0.00 | 45.83 | 0.00 |
PERIMETER_MID_ZN_2 | 352.00 | 12.00 | 39.00 | 12.00 |
PERIMETER_MID_ZN_1 | 172.00 | 24.67 | 23.00 | 24.67 |
PERIMETER_MID_ZN_4 | 173.50 | 20.67 | 30.00 | 10.50 |
PERIMETER_TOP_ZN_3 | 392.00 | 0.00 | 95.83 | 0.00 |
PERIMETER_TOP_ZN_2 | 377.17 | 10.00 | 83.83 | 10.00 |
PERIMETER_TOP_ZN_1 | 329.83 | 13.00 | 62.33 | 13.00 |
PERIMETER_TOP_ZN_4 | 307.67 | 19.50 | 66.17 | 10.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 279.00 | 0.00 | 143.67 |
DATACENTER_MID_ZN_6 | 0.00 | 225.00 | 0.00 | 115.17 |
DATACENTER_TOP_ZN_6 | 0.00 | 161.00 | 0.00 | 76.67 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 1.17 | 0.00 | 0.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 714.17 | 405.33 | 129.67 | 234.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.32 | 149.60 | 6779.02 | 0.927 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.97 | 134.35 | 6849.35 | 0.875 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.97 | 134.35 | 6849.35 | 0.712 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.97 | 134.35 | 6849.35 | 0.705 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.03 | 16.87 | 860.00 | 1.191 | 0.044 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.53 | 10.87 | 554.22 | 2.141 | 0.046 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.03 | 16.87 | 860.02 | 1.876 | 0.044 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.53 | 10.87 | 554.22 | 2.537 | 0.046 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.03 | 16.87 | 860.00 | 1.406 | 0.104 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.96 | 10.87 | 554.22 | 2.106 | 0.113 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.03 | 16.87 | 860.02 | 1.898 | 0.104 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.53 | 10.87 | 554.22 | 2.327 | 0.107 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.03 | 16.87 | 860.00 | 1.649 | 0.128 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.53 | 10.87 | 554.22 | 1.989 | 0.133 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.03 | 16.87 | 860.02 | 1.960 | 0.129 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.53 | 10.87 | 554.22 | 2.220 | 0.133 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.57 | 42.18 | 1911.37 | 19.589 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.32 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.96 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.57 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.32 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.97 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.97 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.97 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.03 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.03 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.03 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.96 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.03 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.03 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.03 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.57 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1032.96 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 37294843.79 | 0.00 | 37294843.79 | 0.00 | 37294843.79 | 37848132.68 | 4275.88 | 2849.75 | 1634.37 | 136.13 |
CORE_BOTTOM | 36562201.27 | 0.00 | 36562201.27 | 0.00 | 36562201.27 | 33990283.35 | 5861.65 | 33.09 | 2865.26 | 421.60 |
CORE_MID | 0.30E+09 | 0.00 | 0.30E+09 | 0.00 | 0.30E+09 | 0.34E+09 | 6408.57 | 26.74 | 2324.69 | 701.45 |
CORE_TOP | 28907341.25 | 0.00 | 28907341.25 | 0.00 | 28907341.25 | 33990283.35 | 6444.78 | 31.44 | 2283.78 | 353.86 |
PERIMETER_BOT_ZN_3 | 6333399.46 | 0.00 | 6333399.46 | 431999.69 | 6765399.14 | 4267819.30 | 3822.54 | 10.76 | 4926.69 | 421.60 |
PERIMETER_BOT_ZN_2 | 7338934.90 | 0.00 | 7338934.90 | 287999.59 | 7626934.49 | 2750345.05 | 3664.76 | 5.99 | 5089.26 | 421.60 |
PERIMETER_BOT_ZN_1 | 9921554.26 | 0.00 | 9921554.26 | 431999.69 | 10353553.95 | 4267912.63 | 3730.66 | 5.62 | 5023.72 | 421.60 |
PERIMETER_BOT_ZN_4 | 8712383.59 | 0.00 | 8712383.59 | 287999.59 | 9000383.19 | 2750345.05 | 3582.58 | 13.08 | 5164.34 | 421.60 |
PERIMETER_MID_ZN_3 | 75059159.71 | 0.00 | 75059159.71 | 1013169.02 | 76072328.74 | 42678193.03 | 3847.66 | 12.57 | 4899.77 | 701.45 |
PERIMETER_MID_ZN_2 | 68354250.07 | 0.00 | 68354250.07 | 675445.55 | 69029695.62 | 27503450.52 | 4139.17 | 17.76 | 4603.07 | 1114.29 |
PERIMETER_MID_ZN_1 | 99950453.18 | 0.00 | 99950453.18 | 1013169.02 | 0.10E+09 | 42679126.28 | 3800.73 | 14.27 | 4945.00 | 701.45 |
PERIMETER_MID_ZN_4 | 79711824.20 | 0.00 | 79711824.20 | 675445.55 | 80387269.75 | 27503450.52 | 3527.68 | 21.78 | 5210.54 | 701.45 |
PERIMETER_TOP_ZN_3 | 8539672.66 | 0.00 | 8539672.66 | 1257968.18 | 9797640.84 | 4267819.30 | 4020.10 | 4.42 | 4735.48 | 353.84 |
PERIMETER_TOP_ZN_2 | 6599611.26 | 0.00 | 6599611.26 | 838644.88 | 7438256.14 | 2750345.05 | 4007.16 | 3.76 | 4749.08 | 353.84 |
PERIMETER_TOP_ZN_1 | 10081475.12 | 0.00 | 10081475.12 | 1257968.18 | 11339443.30 | 4267912.63 | 4015.39 | 3.40 | 4741.20 | 353.84 |
PERIMETER_TOP_ZN_4 | 7384779.35 | 0.00 | 7384779.35 | 838644.88 | 8223424.23 | 2750345.05 | 3980.72 | 4.46 | 4774.82 | 353.84 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.31E+09 | 0.00 | 0.31E+09 | 0.00 | 0.31E+09 | 10671554.30 | 422.48 | 687.71 | 7649.81 | 2587.09 |
Total Facility | 0.67E+10 | 0.00 | 0.67E+10 | 39405516.14 | 0.68E+10 | 0.50E+10 | 6973.47 | 4460.46 | 8431.94 | 3080.74 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.7135 | 0.0000 | 1.7135 | 0.0000 | 1.7135 | 1.2002 | 1505.80 | 2848.58 | 1588.62 |
CORE_BOTTOM | 1.6311 | 0.0000 | 1.6311 | 0.0000 | 1.6311 | 1.0778 | 3203.85 | 31.85 | 2707.30 |
CORE_MID | 13.2930 | 0.0000 | 13.2930 | 0.0000 | 13.2930 | 10.7782 | 3672.68 | 26.47 | 2243.85 |
CORE_TOP | 1.3198 | 0.0000 | 1.3198 | 0.0000 | 1.3198 | 1.0778 | 3676.30 | 30.60 | 2236.10 |
PERIMETER_BOT_ZN_3 | 0.2797 | 0.0000 | 0.2797 | 0.0105 | 0.2902 | 0.1353 | 1208.29 | 8.69 | 4726.02 |
PERIMETER_BOT_ZN_2 | 0.3246 | 0.0000 | 0.3246 | 0.0070 | 0.3316 | 0.0872 | 1128.82 | 2.51 | 4811.67 |
PERIMETER_BOT_ZN_1 | 0.4408 | 0.0000 | 0.4408 | 0.0105 | 0.4513 | 0.1353 | 1155.25 | 3.01 | 4784.74 |
PERIMETER_BOT_ZN_4 | 0.3843 | 0.0000 | 0.3843 | 0.0070 | 0.3913 | 0.0872 | 1105.45 | 4.34 | 4833.20 |
PERIMETER_MID_ZN_3 | 3.3156 | 0.0000 | 3.3156 | 0.0246 | 3.3402 | 1.3533 | 1222.41 | 7.48 | 4713.12 |
PERIMETER_MID_ZN_2 | 3.1967 | 0.0000 | 3.1967 | 0.0173 | 3.2140 | 0.8721 | 1122.52 | 5.37 | 3906.12 |
PERIMETER_MID_ZN_1 | 4.4645 | 0.0000 | 4.4645 | 0.0246 | 4.4891 | 1.3533 | 1199.99 | 5.09 | 4737.92 |
PERIMETER_MID_ZN_4 | 3.5341 | 0.0000 | 3.5341 | 0.0164 | 3.5505 | 0.8721 | 1098.65 | 9.14 | 4835.21 |
PERIMETER_TOP_ZN_3 | 0.3892 | 0.0000 | 0.3892 | 0.0305 | 0.4197 | 0.1353 | 1292.72 | 3.11 | 4647.17 |
PERIMETER_TOP_ZN_2 | 0.3017 | 0.0000 | 0.3017 | 0.0204 | 0.3220 | 0.0872 | 1283.86 | 2.13 | 4657.01 |
PERIMETER_TOP_ZN_1 | 0.4611 | 0.0000 | 0.4611 | 0.0305 | 0.4916 | 0.1353 | 1288.81 | 2.21 | 4651.98 |
PERIMETER_TOP_ZN_4 | 0.3370 | 0.0000 | 0.3370 | 0.0204 | 0.3573 | 0.0872 | 1268.45 | 2.60 | 4671.95 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 10.1190 | 0.0000 | 10.1190 | 0.0000 | 10.1190 | 0.3384 | 178.50 | 687.34 | 5077.16 |
Total Facility | 296.9053 | 0.0000 | 296.9053 | 0.9658 | 297.8711 | 158.4706 | 4156.47 | 4395.57 | 5809.25 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 91701308.60 | 0.00 | 91701308.60 | 48026705.38 | 3789.59 | 3.87 | 4966.54 | 421.60 |
VAV_MID WITH REHEAT | 0.83E+09 | 0.00 | 0.83E+09 | 0.48E+09 | 3907.73 | 3.35 | 4848.92 | 701.45 |
VAV_TOP WITH REHEAT | 81907019.26 | 0.00 | 81907019.26 | 48026705.38 | 4056.19 | 2.66 | 4701.15 | 353.74 |
CAV_BAS | 49485471.75 | 0.00 | 49485471.75 | 37848132.68 | 4254.46 | 1.16 | 4504.38 | 136.13 |
AIRLOOP DATACENTER BASEMENT | 0.42E+09 | 0.00 | 0.42E+09 | 10671554.30 | 417.46 | 0.25 | 8342.29 | 2587.05 |
AIRLOOP DATACENTER BOT | 325290.55 | 0.00 | 325290.55 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3252905.49 | 0.00 | 3252905.49 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 325290.55 | 0.00 | 325290.55 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 4.0752 | 0.0000 | 4.0752 | 1.5229 | 1182.03 | 2.68 | 4758.29 |
VAV_MID WITH REHEAT | 36.7875 | 0.0000 | 36.7875 | 15.2292 | 1241.15 | 0.62 | 4701.23 |
VAV_TOP WITH REHEAT | 3.7400 | 0.0000 | 3.7400 | 1.5229 | 1317.11 | 1.85 | 4624.04 |
CAV_BAS | 2.2734 | 0.0000 | 2.2734 | 1.2002 | 1493.64 | 0.66 | 4448.69 |
AIRLOOP DATACENTER BASEMENT | 13.4739 | 0.0000 | 13.4739 | 0.3384 | 177.28 | 0.07 | 5765.65 |
AIRLOOP DATACENTER BOT | 0.0152 | 0.0000 | 0.0152 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1520 | 0.0000 | 0.1520 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0152 | 0.0000 | 0.0152 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 24.52 | 3653.58 | 0.00 | 0.00 | 0.00 | 1621.74 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 103.76 | 4076.42 | 0.00 | 0.00 | 0.00 | 1485.45 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 18.21 | 3279.79 | 0.00 | 0.00 | 0.00 | 1938.55 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 2868.58 | 1807.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 686.91 | 7671.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.5671 | 6.2939 | 0.0000 | 0.0000 | 0.0000 | 2.3556 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 26.4972 | 53.1924 | 0.0000 | 0.0000 | 0.0000 | 24.4945 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.7099 | 6.0574 | 0.0000 | 0.0000 | 0.0000 | 2.2996 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.5984 | 5.3421 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4512 | 15.6896 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0208 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2082 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0208 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1343 |
Defaulted Fields | 1287 |
Fields with Defaults | 3878 |
Autosized Fields | 320 |
Autosizable Fields | 465 |
Autocalculated Fields | 223 |
Autocalculatable Fields | 468 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 31529.54 | 291299.00 | 28-MAY-05:00 | 2455455.28 | 08-AUG-15:20 |
Electricity:Building | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 758.19 | 15076.70 | 01-JAN-00:10 | 42602.33 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 589.38 | 5907.35 | 01-JAN-00:10 | 43380.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5893.79 | 59073.32 | 01-JAN-00:10 | 433806.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 589.38 | 5907.33 | 01-JAN-00:10 | 43380.63 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 740.04 | 7417.49 | 01-JAN-00:10 | 54469.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 476.91 | 4780.12 | 01-JAN-00:10 | 35102.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 740.05 | 7417.62 | 01-JAN-00:10 | 54470.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 476.91 | 4780.09 | 01-JAN-00:10 | 35102.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7588.97 | 95364.66 | 01-JAN-00:10 | 387850.11 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1622.27 | 19890.94 | 01-JAN-00:10 | 85232.07 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:HVAC | 4774.62 | 33905.91 | 30-SEP-04:50 | 374681.83 | 21-APR-15:40 |
ExteriorEquipment:Electricity | 2623.11 | 22123.82 | 01-JAN-00:10 | 235096.12 | 03-APR-07:20 |
Transformer:ExteriorEquipment:Electricity | 56.04 | 979.82 | 01-JAN-00:10 | 3543.78 | 03-APR-07:20 |
ElectricityPurchased:Facility | 31529.54 | 291299.00 | 28-MAY-05:00 | 2455455.28 | 08-AUG-15:20 |
ElectricityPurchased:Plant | 31529.54 | 291299.00 | 28-MAY-05:00 | 2455455.28 | 08-AUG-15:20 |
Cogeneration:ElectricityPurchased | 31529.54 | 291299.00 | 28-MAY-05:00 | 2455455.28 | 08-AUG-15:20 |
General:Cogeneration:ElectricityPurchased | 31529.54 | 291299.00 | 28-MAY-05:00 | 2455455.28 | 08-AUG-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 31529.54 | 291299.00 | 28-MAY-05:00 | 2455455.28 | 08-AUG-15:20 |
ElectricityNet:Plant | 31529.54 | 291299.00 | 28-MAY-05:00 | 2455455.28 | 08-AUG-15:20 |
Cogeneration:ElectricityNet | 31529.54 | 291299.00 | 28-MAY-05:00 | 2455455.28 | 08-AUG-15:20 |
General:Cogeneration:ElectricityNet | 31529.54 | 291299.00 | 28-MAY-05:00 | 2455455.28 | 08-AUG-15:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1735.95 | 0.00 | 01-JAN-01:10 | 590463.98 | 05-JUL-10:20 |
General:Cooling:Electricity | 1735.95 | 0.00 | 01-JAN-01:10 | 590463.98 | 05-JUL-10:20 |
Fans:Electricity | 3022.89 | 26562.47 | 02-JAN-22:30 | 303816.83 | 30-JUN-15:00 |
General:Fans:Electricity | 3022.89 | 26562.47 | 02-JAN-22:30 | 303816.83 | 30-JUN-15:00 |
ExteriorLights:Electricity | 1004.65 | 0.00 | 01-JAN-08:20 | 64082.80 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 1004.65 | 0.00 | 01-JAN-08:20 | 64082.80 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.31 | 1944.00 | 01-JAN-00:10 | 1944.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1280.30 | 0.00 | 15-APR-01:20 | 100000.00 | 31-MAR-23:50 |
General:Humidifier:Electricity | 1280.30 | 0.00 | 15-APR-01:20 | 100000.00 | 31-MAR-23:50 |
Electricity:Plant | 2896.06 | 0.00 | 19-JAN-00:10 | 770868.62 | 05-JUL-13:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 514.24 | 0.00 | 01-JAN-00:10 | 62804.56 | 24-FEB-12:40 |
Water Heater:WaterSystems:Electricity | 514.24 | 0.00 | 01-JAN-00:10 | 62804.56 | 24-FEB-12:40 |
HeatRejection:Electricity | 121.82 | 0.00 | 01-JAN-00:10 | 55784.63 | 19-JUN-13:10 |
General:HeatRejection:Electricity | 121.82 | 0.00 | 01-JAN-00:10 | 55784.63 | 19-JUN-13:10 |
Pumps:Electricity | 939.44 | 0.00 | 19-JAN-00:10 | 111901.83 | 05-JUL-10:40 |
General:Pumps:Electricity | 939.44 | 0.00 | 19-JAN-00:10 | 111901.83 | 05-JUL-10:40 |
WIRED_LTG_ELECTRICITY | 157.66 | 0.00 | 01-JAN-00:10 | 13766.21 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 8150.49 | 0.00 | 01-JAN-00:40 | 3228629.56 | 09-JAN-07:30 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 8150.49 | 0.00 | 01-JAN-00:40 | 3228629.56 | 09-JAN-07:30 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 8150.49 | 0.00 | 01-JAN-00:40 | 3228629.56 | 09-JAN-07:30 |
Boiler:Heating:NaturalGas | 8150.49 | 0.00 | 01-JAN-00:40 | 3228629.56 | 09-JAN-07:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 7340.63 | 0.00 | 01-JAN-00:20 | 4052242.55 | 05-JUL-10:40 |
PlantLoopCoolingDemand:HVAC | 7340.63 | 0.00 | 01-JAN-00:20 | 4052242.55 | 05-JUL-10:40 |
CoolingCoils:PlantLoopCoolingDemand | 7340.63 | 0.00 | 01-JAN-00:20 | 4052242.55 | 05-JUL-10:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 7837.15 | 0.00 | 23-APR-23:50 | 0.00 | 18-MAY-15:10 |
Water:HVAC | 476.27 | 0.00 | 15-APR-01:20 | 0.00 | 02-APR-15:10 |
Humidifier:Water | 476.27 | 0.00 | 15-APR-01:20 | 0.00 | 02-APR-15:10 |
General:Humidifier:Water | 476.27 | 0.00 | 15-APR-01:20 | 0.00 | 02-APR-15:10 |
MainsWater:Facility | 7837.15 | 0.00 | 23-APR-23:50 | 0.00 | 18-MAY-15:10 |
MainsWater:HVAC | 476.27 | 0.00 | 15-APR-01:20 | 0.00 | 02-APR-15:10 |
Humidifier:MainsWater | 476.27 | 0.00 | 15-APR-01:20 | 0.00 | 02-APR-15:10 |
General:Humidifier:MainsWater | 476.27 | 0.00 | 15-APR-01:20 | 0.00 | 02-APR-15:10 |
Water:Plant | 7360.87 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-15:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:00 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:00 |
MainsWater:Plant | 7360.87 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-15:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:00 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:00 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 5080.70 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-15:10 |
General:HeatRejection:Water | 5080.70 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-15:10 |
HeatRejection:MainsWater | 5080.70 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-15:10 |
General:HeatRejection:MainsWater | 5080.70 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-15:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 66956.14 | 101495.27 | 01-JAN-00:40 | 17316377.27 | 05-JUL-10:40 |
EnergyTransfer:Building | 21717.16 | 88354.41 | 19-JAN-23:00 | 2140340.86 | 26-DEC-06:10 |
EnergyTransfer:Zone:BASEMENT | 723.01 | 0.00 | 01-JAN-00:10 | 84402.81 | 05-SEP-09:20 |
Heating:EnergyTransfer | 2401.93 | 0.00 | 04-FEB-17:30 | 1977141.40 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.89 | 0.00 | 01-JAN-00:10 | 15792.43 | 09-JAN-07:10 |
General:Heating:EnergyTransfer | 2401.93 | 0.00 | 04-FEB-17:30 | 1977141.40 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.89 | 0.00 | 01-JAN-00:10 | 15792.43 | 09-JAN-07:10 |
Cooling:EnergyTransfer | 19315.23 | 80368.52 | 02-JAN-06:50 | 1931077.18 | 08-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 722.12 | 0.00 | 01-JAN-00:10 | 84402.81 | 05-SEP-09:20 |
General:Cooling:EnergyTransfer | 19315.23 | 80368.52 | 02-JAN-06:50 | 1931077.18 | 08-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 722.12 | 0.00 | 01-JAN-00:10 | 84402.81 | 05-SEP-09:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 589.41 | 0.00 | 01-JAN-00:40 | 58982.74 | 05-JUL-10:50 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.03 | 0.00 | 01-JAN-00:10 | 11962.48 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.03 | 0.00 | 01-JAN-00:10 | 11962.48 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 589.37 | 0.00 | 01-JAN-00:40 | 58982.74 | 05-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 589.37 | 0.00 | 01-JAN-00:40 | 58982.74 | 05-JUL-10:50 |
EnergyTransfer:Zone:CORE_MID | 4690.52 | 0.00 | 01-JAN-00:40 | 570431.29 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 27.70 | 0.00 | 01-JAN-00:20 | 570431.29 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 27.70 | 0.00 | 01-JAN-00:20 | 570431.29 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4662.82 | 0.00 | 01-JAN-00:40 | 499523.08 | 30-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4662.82 | 0.00 | 01-JAN-00:40 | 499523.08 | 30-JUN-16:00 |
EnergyTransfer:Zone:CORE_TOP | 444.74 | 0.00 | 01-JAN-00:40 | 112146.92 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 62.74 | 0.00 | 01-JAN-00:40 | 112146.92 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 62.74 | 0.00 | 01-JAN-00:40 | 112146.92 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 382.00 | 0.00 | 01-JAN-00:10 | 62771.25 | 30-JUN-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 382.00 | 0.00 | 01-JAN-00:10 | 62771.25 | 30-JUN-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 90.72 | 0.00 | 01-JAN-00:40 | 20931.57 | 09-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.46 | 0.00 | 01-JAN-00:40 | 20931.57 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.46 | 0.00 | 01-JAN-00:40 | 20931.57 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 70.26 | 0.00 | 01-JAN-00:20 | 13656.79 | 29-JUN-14:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 70.26 | 0.00 | 01-JAN-00:20 | 13656.79 | 29-JUN-14:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 87.06 | 0.00 | 01-JAN-00:40 | 19269.54 | 31-JUL-08:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 13.00 | 0.00 | 01-JAN-00:40 | 15176.35 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 13.00 | 0.00 | 01-JAN-00:40 | 15176.35 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 74.07 | 0.00 | 01-JAN-00:20 | 19269.54 | 31-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 74.07 | 0.00 | 01-JAN-00:20 | 19269.54 | 31-JUL-08:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 138.10 | 0.00 | 01-JAN-00:40 | 30393.51 | 01-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 17.97 | 0.00 | 01-JAN-00:40 | 23848.80 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 17.97 | 0.00 | 01-JAN-00:40 | 23848.80 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 120.13 | 0.00 | 01-JAN-00:20 | 30393.51 | 01-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 120.13 | 0.00 | 01-JAN-00:20 | 30393.51 | 01-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 108.60 | 0.00 | 01-JAN-00:40 | 23119.13 | 24-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 5.11 | 0.00 | 01-JAN-00:40 | 13003.52 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 5.11 | 0.00 | 01-JAN-00:40 | 13003.52 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 103.49 | 0.00 | 01-JAN-00:20 | 23119.13 | 24-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 103.49 | 0.00 | 01-JAN-00:20 | 23119.13 | 24-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1134.00 | 0.00 | 01-JAN-00:40 | 291626.91 | 13-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 560.21 | 0.00 | 01-JAN-00:40 | 291626.91 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 560.21 | 0.00 | 01-JAN-00:40 | 291626.91 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 573.80 | 0.00 | 01-JAN-00:10 | 133821.49 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 573.80 | 0.00 | 01-JAN-00:10 | 133821.49 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 926.85 | 0.00 | 01-JAN-00:40 | 201623.81 | 13-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 315.91 | 0.00 | 01-JAN-00:40 | 201623.81 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 315.91 | 0.00 | 01-JAN-00:40 | 201623.81 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 610.94 | 0.00 | 01-JAN-00:20 | 201468.88 | 24-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 610.94 | 0.00 | 01-JAN-00:20 | 201468.88 | 24-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1495.04 | 0.00 | 01-JAN-00:40 | 328381.49 | 01-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 365.86 | 0.00 | 01-JAN-00:40 | 294165.89 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 365.86 | 0.00 | 01-JAN-00:40 | 294165.89 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1129.18 | 0.00 | 01-JAN-00:20 | 328381.49 | 01-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1129.18 | 0.00 | 01-JAN-00:20 | 328381.49 | 01-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 973.12 | 0.00 | 01-JAN-00:40 | 228816.90 | 30-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 277.40 | 0.00 | 01-JAN-00:40 | 199464.13 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 277.40 | 0.00 | 01-JAN-00:40 | 199464.13 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 695.72 | 0.00 | 01-JAN-00:20 | 228816.90 | 30-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 695.72 | 0.00 | 01-JAN-00:20 | 228816.90 | 30-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 157.00 | 0.00 | 01-JAN-00:40 | 37712.55 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 101.90 | 0.00 | 01-JAN-00:40 | 37712.55 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 101.90 | 0.00 | 01-JAN-00:40 | 37712.55 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 55.10 | 0.00 | 01-JAN-00:10 | 14644.29 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 55.10 | 0.00 | 01-JAN-00:10 | 14644.29 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 116.81 | 0.00 | 01-JAN-00:40 | 24812.56 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 59.43 | 0.00 | 01-JAN-00:40 | 24812.56 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 59.43 | 0.00 | 01-JAN-00:40 | 24812.56 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 57.38 | 0.00 | 01-JAN-00:10 | 20130.14 | 24-JUL-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 57.38 | 0.00 | 01-JAN-00:10 | 20130.14 | 24-JUL-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 178.79 | 0.00 | 01-JAN-00:40 | 37151.92 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 74.49 | 0.00 | 01-JAN-00:40 | 37151.92 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 74.49 | 0.00 | 01-JAN-00:40 | 37151.92 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 104.30 | 0.00 | 01-JAN-00:10 | 33947.82 | 01-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 104.30 | 0.00 | 01-JAN-00:10 | 33947.82 | 01-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 115.29 | 0.00 | 01-JAN-00:40 | 24675.90 | 04-JAN-05:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 50.82 | 0.00 | 01-JAN-00:40 | 24675.90 | 04-JAN-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 50.82 | 0.00 | 01-JAN-00:40 | 24675.90 | 04-JAN-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 64.47 | 0.00 | 01-JAN-00:10 | 23927.99 | 30-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 64.47 | 0.00 | 01-JAN-00:10 | 23927.99 | 30-JUN-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 84.93 | 0.00 | 01-JAN-00:40 | 12433.89 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 5.15 | 0.00 | 01-JAN-00:10 | 12433.89 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 5.15 | 0.00 | 01-JAN-00:10 | 12433.89 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 79.77 | 0.00 | 01-JAN-00:40 | 11024.48 | 30-MAY-05:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 79.77 | 0.00 | 01-JAN-00:40 | 11024.48 | 30-MAY-05:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 863.94 | 0.00 | 01-JAN-00:40 | 256959.26 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 210.50 | 0.00 | 01-JAN-00:40 | 256959.26 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 210.50 | 0.00 | 01-JAN-00:40 | 256959.26 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 653.43 | 0.00 | 01-JAN-00:10 | 123963.43 | 12-MAR-03:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 653.43 | 0.00 | 01-JAN-00:10 | 123963.43 | 12-MAR-03:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 287.17 | 0.00 | 01-JAN-00:40 | 71262.24 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 202.64 | 0.00 | 01-JAN-00:40 | 71262.24 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 202.64 | 0.00 | 01-JAN-00:40 | 71262.24 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 84.52 | 0.00 | 01-JAN-00:10 | 37249.27 | 30-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 84.52 | 0.00 | 01-JAN-00:10 | 37249.27 | 30-JUN-14:00 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 127.39 | 3.01 | 25-JAN-20:30 | 11683.06 | 20-DEC-11:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 1.34 | 0.00 | 01-JAN-16:00 | 1431.54 | 04-JAN-24:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 1.34 | 0.00 | 01-JAN-16:00 | 1431.54 | 04-JAN-24:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 126.05 | 0.00 | 01-JAN-00:10 | 11683.06 | 20-DEC-11:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 126.05 | 0.00 | 01-JAN-00:10 | 11683.06 | 20-DEC-11:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1109.72 | 7.37 | 25-JAN-09:20 | 108987.00 | 20-DEC-11:10 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 22.95 | 0.00 | 02-JAN-13:40 | 14464.29 | 01-JAN-17:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 22.95 | 0.00 | 02-JAN-13:40 | 14464.29 | 01-JAN-17:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1086.77 | 0.00 | 01-JAN-00:10 | 108987.00 | 20-DEC-11:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1086.77 | 0.00 | 01-JAN-00:10 | 108987.00 | 20-DEC-11:10 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 96.23 | 5.10 | 09-OCT-10:30 | 9966.83 | 20-DEC-11:10 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 3.57 | 0.00 | 02-JAN-13:40 | 1493.20 | 01-JAN-17:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 3.57 | 0.00 | 02-JAN-13:40 | 1493.20 | 01-JAN-17:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 92.66 | 0.00 | 01-JAN-00:10 | 9966.83 | 20-DEC-11:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 92.66 | 0.00 | 01-JAN-00:10 | 9966.83 | 20-DEC-11:10 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7178.72 | 79835.68 | 01-JAN-00:20 | 395724.40 | 24-APR-08:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 1.83 | 0.00 | 01-JAN-00:10 | 3065.44 | 20-FEB-15:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 1.83 | 0.00 | 01-JAN-00:10 | 3065.44 | 20-FEB-15:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7176.89 | 79835.68 | 01-JAN-00:20 | 395724.40 | 24-APR-08:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7176.89 | 79835.68 | 01-JAN-00:20 | 395724.40 | 24-APR-08:00 |
PlantLoopHeatingDemand:Facility | 6311.54 | 0.00 | 01-JAN-00:40 | 2597885.81 | 09-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 508.68 | 0.00 | 01-JAN-00:10 | 62462.67 | 24-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 508.68 | 0.00 | 01-JAN-00:10 | 62462.67 | 24-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 508.68 | 0.00 | 01-JAN-00:10 | 62462.67 | 24-FEB-12:10 |
EnergyTransfer:HVAC | 14869.47 | 0.47 | 27-JAN-23:00 | 4139136.26 | 05-JUL-10:40 |
HeatingCoils:EnergyTransfer | 5802.86 | 0.00 | 01-JAN-00:40 | 2577738.34 | 09-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 5802.86 | 0.00 | 01-JAN-00:40 | 2577738.34 | 09-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 5802.86 | 0.00 | 01-JAN-00:40 | 2577738.34 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 9066.61 | 0.00 | 01-JAN-01:10 | 4139136.26 | 05-JUL-10:40 |
EnergyTransfer:Plant | 30369.51 | 0.00 | 19-JAN-00:10 | 11717585.10 | 05-JUL-10:40 |
LoopToLoop:EnergyTransfer | 7487.14 | 0.00 | 01-JAN-00:20 | 3863639.36 | 05-JUL-10:40 |
WaterSystems:EnergyTransfer | 508.68 | 0.00 | 01-JAN-00:10 | 62462.67 | 24-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 508.68 | 0.00 | 01-JAN-00:10 | 62462.67 | 24-FEB-12:10 |
Boilers:EnergyTransfer | 5770.01 | 0.00 | 01-JAN-00:40 | 2529642.91 | 09-JAN-07:30 |
Chillers:EnergyTransfer | 7641.56 | 0.00 | 01-JAN-00:20 | 3634720.89 | 05-JUL-10:20 |
HeatRejection:EnergyTransfer | 8962.12 | 0.00 | 01-JAN-00:20 | 4205208.14 | 05-JUL-10:20 |
General:HeatRejection:EnergyTransfer | 8962.12 | 0.00 | 01-JAN-00:20 | 4205208.14 | 05-JUL-10:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.892 | -722.111 | 0.000 | 0.000 | 96.809 | 333.789 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -133.776 |
CORE_BOTTOM | 0.000 | 0.000 | 0.035 | -589.373 | 0.000 | 0.000 | 84.246 | 299.766 | 289.614 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -84.289 |
CORE_MID | 0.000 | 0.000 | 27.702 | -4662.807 | 0.000 | 0.000 | 864.288 | 2997.664 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -2122.974 |
CORE_TOP | 0.000 | 0.000 | 62.744 | -381.996 | 0.000 | 0.000 | 92.210 | 299.766 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -362.337 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 20.456 | -70.259 | 0.000 | 0.000 | 11.514 | 37.639 | 36.365 | 29.210 | 0.000 | 0.037 | 87.296 | 0.000 | -142.463 | 0.000 | -9.795 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 12.997 | -74.067 | 0.000 | 0.000 | 7.479 | 24.256 | 23.435 | 64.535 | 0.000 | 0.029 | 33.848 | 0.000 | -86.043 | 0.000 | -6.471 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 17.973 | -120.131 | 0.000 | 0.000 | 11.371 | 37.639 | 36.366 | 137.696 | 0.000 | 0.035 | 10.376 | 0.000 | -121.513 | 0.000 | -9.814 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 5.111 | -103.489 | 0.000 | 0.000 | 7.454 | 24.256 | 23.435 | 65.089 | 0.000 | 0.023 | 80.291 | 0.000 | -95.296 | 0.000 | -6.874 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 560.208 | -573.794 | 0.000 | 0.000 | 119.026 | 376.387 | 363.654 | 308.501 | 0.000 | 1.031 | 417.064 | 0.000 | -1358.130 | 0.000 | -213.948 | -0.004 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 315.909 | -610.938 | 0.000 | 0.000 | 55.603 | 242.558 | 234.352 | 640.888 | 0.000 | 0.623 | 97.745 | 0.000 | -831.968 | 0.000 | -144.772 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 365.863 | -1129.177 | 0.000 | 0.000 | 114.985 | 376.395 | 363.660 | 1364.907 | 0.000 | 0.764 | 0.000 | 0.000 | -1202.328 | 0.000 | -223.057 | -32.010 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 277.396 | -695.717 | 0.000 | 0.000 | 77.014 | 242.558 | 234.351 | 663.937 | 0.000 | 0.599 | 232.204 | 0.000 | -885.477 | 0.000 | -146.864 | -0.006 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 101.903 | -55.100 | 0.000 | 0.000 | 12.130 | 37.639 | 36.365 | 32.214 | 0.000 | 0.151 | 0.000 | 0.000 | -129.633 | 0.000 | -25.611 | -10.058 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 59.433 | -57.376 | 0.000 | 0.000 | 7.625 | 24.256 | 23.435 | 65.060 | 0.000 | 0.075 | 0.001 | 0.000 | -79.637 | 0.000 | -17.387 | -25.486 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 74.490 | -104.296 | 0.000 | 0.000 | 11.737 | 37.639 | 36.366 | 138.006 | 0.000 | 0.099 | 0.002 | 0.000 | -113.840 | 0.000 | -26.543 | -53.659 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 50.820 | -64.472 | 0.000 | 0.000 | 7.761 | 24.256 | 23.435 | 66.627 | 0.000 | 0.074 | 0.001 | 0.000 | -85.088 | 0.000 | -17.697 | -5.715 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 1.341 | -126.052 | 0.000 | 0.000 | 0.941 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -38.457 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 22.952 | -1086.764 | 0.000 | 0.000 | 9.432 | 83.466 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -567.892 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 3.571 | -92.658 | 0.000 | 0.000 | 0.948 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -74.088 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 1.834 | -7176.629 | 0.000 | 0.000 | 22.965 | 94.114 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -437.141 |
GROUNDFLOOR_PLENUM | 5.152 | -79.774 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.057 | 96.139 | 0.000 | 0.000 | 0.000 | -21.574 | -0.000 |
MIDFLOOR_PLENUM | 210.504 | -653.432 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.109 | 810.165 | 0.000 | 0.000 | 0.000 | -368.345 | -0.011 |
TOPFLOOR_PLENUM | 202.643 | -84.524 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.071 | 0.000 | 0.000 | 0.000 | 0.000 | -37.674 | -80.516 |
Total Facility | 418.299 | -817.730 | 1983.632 | -18497.207 | 0.000 | 0.000 | 1615.538 | 5610.736 | 14676.396 | 3576.671 | 0.000 | 4.779 | 1865.133 | 0.000 | -5131.417 | 0.000 | -1276.427 | -4028.420 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 23-OCT-04:11 | 0.00 | 0.00 | 0.00 | -147965.66 | 0.00 | 0.00 | 0.00 | 3238.31 | 13457.54 | 0.00 | 0.00 | 0.00 | 131269.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 31-JUL-04:11 | 0.00 | 0.00 | 0.00 | -122248.21 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.65 | 0.00 | 0.00 | 0.00 | 113402.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 30-MAY-04:12 | 0.00 | 0.00 | 0.00 | -1084515.33 | 0.00 | 0.00 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 996056.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 26-MAY-05:02 | 0.00 | 0.00 | 0.00 | -129176.12 | 0.00 | 0.00 | 844.33 | 2908.23 | 7647.36 | 0.00 | 0.00 | 0.00 | 117776.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 03-JUL-04:11 | 0.00 | 0.00 | 0.00 | -18243.34 | 0.00 | 0.00 | 0.00 | 365.16 | 745.56 | 0.00 | 0.00 | 0.00 | 19527.31 | 0.00 | -2297.48 | 0.00 | -97.21 | 0.00 |
PERIMETER_BOT_ZN_2 | 25-JUN-08:61 | 0.00 | 0.00 | 0.00 | -38607.69 | 0.00 | 0.00 | 16.35 | 117.66 | 464.11 | 25522.01 | 0.00 | 0.00 | 12614.53 | 0.00 | -0.00 | 0.00 | -126.98 | 0.00 |
PERIMETER_BOT_ZN_1 | 22-OCT-13:11 | 0.00 | 0.00 | 0.00 | -49053.16 | 0.00 | 0.00 | 24.60 | 182.58 | 720.19 | 38791.14 | 0.00 | 0.00 | 9645.87 | 0.00 | -0.00 | 0.00 | -311.23 | 0.00 |
PERIMETER_BOT_ZN_4 | 16-JUL-16:51 | 0.00 | 0.00 | 0.00 | -48077.00 | 0.00 | 0.00 | 12.53 | 117.66 | 464.11 | 22147.03 | 0.00 | 0.00 | 25680.02 | 0.00 | -0.00 | 0.00 | -344.35 | 0.00 |
PERIMETER_MID_ZN_3 | 28-JUN-05:01 | 0.00 | 0.00 | 0.00 | -183342.86 | 0.00 | 0.00 | 1117.09 | 3651.57 | 9602.45 | 64701.11 | 0.00 | 0.00 | 104270.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 25-JUN-08:11 | 0.00 | 0.00 | 0.00 | -415644.69 | 0.00 | 0.00 | 154.15 | 1176.61 | 4641.14 | 248993.86 | 0.00 | 0.00 | 163644.00 | 0.00 | -0.00 | 0.00 | -2965.07 | 0.00 |
PERIMETER_MID_ZN_1 | 22-OCT-13:11 | 0.00 | 0.00 | 0.00 | -526575.67 | 0.00 | 0.00 | 197.79 | 1825.83 | 7201.95 | 382871.56 | 0.00 | 0.00 | 142385.01 | 0.00 | -0.00 | 0.00 | -7906.46 | 0.00 |
PERIMETER_MID_ZN_4 | 23-APR-17:41 | 0.00 | 0.00 | 0.00 | -449325.01 | 0.00 | 0.00 | 0.00 | 1176.61 | 3603.49 | 211308.04 | 0.00 | 0.00 | 237920.34 | 0.00 | -0.00 | 0.00 | -4683.46 | 0.00 |
PERIMETER_TOP_ZN_3 | 28-JUN-05:01 | 0.00 | 0.00 | 0.00 | -17678.86 | 0.00 | 0.00 | 112.89 | 365.16 | 960.25 | 6592.23 | 0.00 | 0.00 | 9648.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 18-JUN-09:51 | 0.00 | 0.00 | 0.00 | -39482.19 | 0.00 | 0.00 | 17.83 | 117.66 | 464.11 | 17525.82 | 0.00 | 0.00 | 21832.71 | 0.00 | -0.00 | 0.00 | -475.95 | 0.00 |
PERIMETER_TOP_ZN_1 | 22-OCT-13:11 | 0.00 | 0.00 | 0.00 | -62326.89 | 0.00 | 0.00 | 23.33 | 182.58 | 720.19 | 38416.01 | 0.00 | 0.00 | 23897.61 | 0.00 | -0.00 | 0.00 | -912.83 | 0.00 |
PERIMETER_TOP_ZN_4 | 23-APR-16:51 | 0.00 | 0.00 | 0.00 | -48301.01 | 0.00 | 0.00 | 13.14 | 117.66 | 464.11 | 26952.76 | 0.00 | 0.00 | 21189.87 | 0.00 | -0.00 | 0.00 | -436.54 | 0.00 |
DATACENTER_BOT_ZN_6 | 12-MAR-07:01 | 0.00 | 0.00 | 0.00 | -12335.45 | 0.00 | 0.00 | 0.00 | 40.49 | 5845.82 | 0.00 | 0.00 | 0.00 | 6449.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 26-DEC-09:41 | 0.00 | 0.00 | 0.00 | -115818.56 | 0.00 | 0.00 | 1008.50 | 7287.84 | 77944.22 | 0.00 | 0.00 | 0.00 | 29577.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 26-DEC-09:41 | 0.00 | 0.00 | 0.00 | -11696.39 | 0.00 | 0.00 | 100.85 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 3072.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 31-MAR-15:52 | 0.00 | 0.00 | 0.00 | -525101.16 | 0.00 | 0.00 | 2723.28 | 8217.58 | 284724.39 | 0.00 | 0.00 | 0.00 | 229435.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 25-FEB-04:01 | 0.00 | -21404.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21404.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 02-DEC-02:61 | 0.00 | -259287.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301708.62 | 0.00 | -0.00 | 0.00 | -42421.12 | 0.00 |
TOPFLOOR_PLENUM | 30-JUN-14:00 | 0.00 | -37248.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.41 | 37032.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-JUL-05:01 | 0.00 | 27334.06 | 0.00 | -2284944.80 | 0.00 | 0.00 | 16307.27 | 54433.43 | 497997.76 | 164863.68 | 0.00 | 0.00 | 1575380.64 | 0.00 | -45146.07 | 0.00 | -6225.97 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-JAN-07:10 | 0.00 | 0.00 | 95204.70 | 0.00 | 0.00 | 0.00 | 2152.86 | 9714.93 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -120530.03 |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 19864.71 | 0.00 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -28710.59 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 682329.88 | 0.00 | 0.00 | 0.00 | 0.00 | 14541.15 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -756247.26 |
CORE_TOP | 09-JAN-04:01 | 0.00 | 0.00 | 140107.80 | 0.00 | 0.00 | 0.00 | 0.00 | 1454.11 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -147499.54 |
PERIMETER_BOT_ZN_3 | 24-DEC-08:11 | 0.00 | 0.00 | 25491.42 | 0.00 | 0.00 | 0.00 | 89.42 | 182.58 | 720.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13284.75 | 0.00 | -1852.59 | -11346.27 |
PERIMETER_BOT_ZN_2 | 25-DEC-04:51 | 0.00 | 0.00 | 24593.62 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8714.50 | 0.00 | -822.56 | -15534.58 |
PERIMETER_BOT_ZN_1 | 24-DEC-08:11 | 0.00 | 0.00 | 34454.75 | 0.00 | 0.00 | 0.00 | 90.20 | 182.58 | 720.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3960.38 | 0.00 | -1849.54 | -29637.81 |
PERIMETER_BOT_ZN_4 | 02-JAN-04:01 | 0.00 | 0.00 | 23329.38 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6816.07 | 0.00 | -750.29 | -16361.15 |
PERIMETER_MID_ZN_3 | 24-DEC-09:21 | 0.00 | 0.00 | 367402.72 | 0.00 | 0.00 | 0.00 | 940.68 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -116791.32 | 0.00 | -46006.99 | -214572.71 |
PERIMETER_MID_ZN_2 | 12-FEB-23:01 | 0.00 | 0.00 | 308601.71 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.61 | 3603.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -63121.16 | 0.00 | -44875.53 | -205385.13 |
PERIMETER_MID_ZN_1 | 12-FEB-23:01 | 0.00 | 0.00 | 394674.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1825.83 | 5591.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -95728.00 | 0.00 | -66947.50 | -239416.22 |
PERIMETER_MID_ZN_4 | 12-FEB-23:01 | 0.00 | 0.00 | 321568.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -67645.22 | 0.00 | -44959.34 | -213743.86 |
PERIMETER_TOP_ZN_3 | 24-DEC-08:41 | 0.00 | 0.00 | 50957.65 | 0.00 | 0.00 | 0.00 | 96.19 | 182.58 | 720.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -12161.16 | 0.00 | -5406.78 | -34388.67 |
PERIMETER_TOP_ZN_2 | 24-DEC-08:61 | 0.00 | 0.00 | 34695.06 | 0.00 | 0.00 | 0.00 | 61.91 | 117.66 | 464.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8299.11 | 0.00 | -3287.18 | -23752.45 |
PERIMETER_TOP_ZN_1 | 24-DEC-08:61 | 0.00 | 0.00 | 51286.42 | 0.00 | 0.00 | 0.00 | 95.82 | 182.58 | 720.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -12488.62 | 0.00 | -4942.68 | -34853.71 |
PERIMETER_TOP_ZN_4 | 13-FEB-03:51 | 0.00 | 0.00 | 38565.13 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7449.42 | 0.00 | -4274.64 | -27439.19 |
DATACENTER_BOT_ZN_6 | 02-DEC-01:52 | 0.00 | 0.00 | 2082.82 | 0.00 | 0.00 | 0.00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9917.73 |
DATACENTER_MID_ZN_6 | 21-DEC-00:02 | 0.00 | 0.00 | 17937.63 | 0.00 | 0.00 | 0.00 | 0.00 | 404.88 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -96286.73 |
DATACENTER_TOP_ZN_6 | 12-MAR-07:02 | 0.00 | 0.00 | 2141.16 | 0.00 | 0.00 | 0.00 | 3.56 | 40.49 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8031.03 |
DATACENTER_BASEMENT_ZN_6 | 22-OCT-09:51 | 0.00 | 0.00 | 26067.48 | 0.00 | 0.00 | 0.00 | 152.42 | 456.53 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -216492.70 |
GROUNDFLOOR_PLENUM | 26-MAR-15:31 | 21831.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -898.02 | -20933.21 |
MIDFLOOR_PLENUM | 02-JAN-06:12 | 280734.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -6028.08 | -274706.04 |
TOPFLOOR_PLENUM | 06-JAN-05:11 | 76147.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3792.84 | -72354.38 |
Total Facility | 02-JAN-05:21 | 102372.37 | 92045.57 | 2254913.88 | -92045.57 | 0.00 | 0.00 | 0.00 | 54433.43 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -387720.87 | 0.00 | -110414.39 | -2146009.65 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 16.2459 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 13.1645 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 164.5350 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 122.2745 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 20.3387 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 15.0188 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 7.4989 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 7.4989 | 0.1600 | 1.0000 | Not calculated | 1.2002 | 0.1600 | ||
AIRLOOP DATACENTER BASEMENT | 32.8850 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 32.8850 | 0.0103 | 1.0000 | Not calculated | 0.3384 | 0.0103 | ||
AIRLOOP DATACENTER BOT | 0.8150 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.8150 | 0.0192 | 1.0000 | Not calculated | 0.0156 | 0.0192 | ||
AIRLOOP DATACENTER MID | 7.8682 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 7.8682 | 0.0199 | 1.0000 | Not calculated | 0.1563 | 0.0199 | ||
AIRLOOP DATACENTER TOP | 0.8079 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.8079 | 0.0193 | 1.0000 | Not calculated | 0.0156 | 0.0193 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 8.1229 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.8738 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 82.2675 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 49.3605 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.1693 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.1016 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 2.2497 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 2.2497 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.5335 | ||
AIRLOOP DATACENTER BASEMENT | 16.4425 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 16.4425 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0206 | ||
AIRLOOP DATACENTER BOT | 0.8150 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.8150 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0192 | ||
AIRLOOP DATACENTER MID | 7.8682 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 7.8682 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0199 | ||
AIRLOOP DATACENTER TOP | 0.8079 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.8079 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0193 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 7.4989 | 7.4989 | 2.2497 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.7664 | 7.7664 | 2.3299 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 73.3455 | 73.3455 | 22.0037 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.6544 | 9.6544 | 2.8963 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7278 | 1.7278 | 0.5183 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9615 | 1.9615 | 0.5884 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4292 | 2.4292 | 0.7288 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3610 | 2.3610 | 0.7083 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 22.9360 | 22.9360 | 6.8808 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 20.9207 | 20.9207 | 6.2762 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 24.8166 | 24.8166 | 7.4450 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 22.5162 | 22.5162 | 6.7549 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0613 | 3.0613 | 0.9184 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0963 | 2.0963 | 0.6289 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1145 | 3.1145 | 0.9344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4122 | 2.4122 | 0.7237 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8150 | 0.8150 | 0.8150 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.8682 | 7.8682 | 7.8682 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8079 | 0.8079 | 0.8079 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 32.8850 | 32.8850 | 16.4425 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 16.2459 | 13.1645 | 16.2459 | 4.8738 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 164.5350 | 122.2745 | 164.5350 | 49.3605 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 20.3387 | 15.0188 | 20.3387 | 6.1016 | 0.0000 | 1.0000 |
CAV_BAS | 7.4989 | 7.4989 | 7.4989 | 2.2497 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 32.8850 | 32.8850 | 32.8850 | 16.4425 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.8150 | 0.8150 | 0.8150 | 0.8150 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 7.8682 | 7.8682 | 7.8682 | 7.8682 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.8079 | 0.8079 | 0.8079 | 0.8079 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 2.2497 | 2.2497 | 2.2497 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.8832 | 3.8832 | 2.3299 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 36.6728 | 36.6728 | 22.0037 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.8272 | 4.8272 | 2.8963 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8639 | 0.8639 | 0.5183 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9807 | 0.9807 | 0.5884 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2146 | 1.2146 | 0.7288 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1805 | 1.1805 | 0.7083 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.4680 | 11.4680 | 6.8808 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.4603 | 10.4603 | 6.2762 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.4083 | 12.4083 | 7.4450 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.2581 | 11.2581 | 6.7549 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5306 | 1.5306 | 0.9184 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0482 | 1.0482 | 0.6289 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5573 | 1.5573 | 0.9344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2061 | 1.2061 | 0.7237 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8150 | 0.8150 | 0.8150 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.8682 | 7.8682 | 7.8682 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8079 | 0.8079 | 0.8079 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 16.4425 | 16.4425 | 16.4425 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 8.1229 | 4.8738 | 4.8738 | 4.8738 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 82.2675 | 49.3605 | 49.3605 | 49.3605 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.1693 | 6.1016 | 6.1016 | 6.1016 | 0.0000 | 1.0000 |
CAV_BAS | 2.2497 | 2.2497 | 2.2497 | 2.2497 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 16.4425 | 16.4425 | 16.4425 | 16.4425 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.8150 | 0.8150 | 0.8150 | 0.8150 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 7.8682 | 7.8682 | 7.8682 | 7.8682 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.8079 | 0.8079 | 0.8079 | 0.8079 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 129.67 |
Number of hours cooling loads not met | 234.83 |
Number of hours not met | 348.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 8150.49 | 3228629.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1735.95 | 590463.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 5610.74 | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 1004.65 | 64082.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 56.04 | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.31 | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 3022.89 | 303816.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 939.44 | 111901.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 121.82 | 55784.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1280.30 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 514.24 | 62804.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 31529.54 |
Natural Gas | 0.00 | 8150.49 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 39680.02 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 121.13 |
Space Heating | 0.00 |
Space Cooling | 37.48 |
Fans (All) | 65.26 |
Service Water Heating | 11.10 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 680.68 |
Subtotal | 680.68 |
Natural Gas [MJ/m2] | |
Space Heating | 175.96 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 175.96 |
Subtotal | 175.96 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.14 |
Space Heating | 20.54 |
Space Cooling | 4.37 |
Fans (All) | 7.62 |
Service Water Heating | 1.30 |
Receptacle Equipment | 36.99 |
Miscellaneous | 15.04 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
LTG_SCH_DATACENTER | 2939. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8516.00 | 244.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8727.50 | 32.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8739.33 | 20.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8734.50 | 25.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8486.83 | 273.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8733.17 | 26.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8728.33 | 31.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8707.33 | 52.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8737.33 | 22.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8739.00 | 21.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8716.83 | 43.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6449.50 | 2212.83 | 97.67 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6502.33 | 2175.33 | 82.33 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6482.67 | 2244.17 | 33.17 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7473.00 | 1287.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8739.33 | 20.67 | 0.00 | 0.00 | 0.00 |
Min | 6449.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2244.17 | 97.67 | 0.00 | 0.00 |
Average | 8370.83 | 379.90 | 9.27 | 0.00 | 0.00 |
Sum | 192529.17 | 8737.67 | 213.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367869.33 | 746.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330799.00 | 14.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1536.67 | 722.33 | 9.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1548.50 | 710.50 | 9.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1552.50 | 706.67 | 8.83 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 84748.67 | 18646.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367869.33 | 18646.33 | 9.00 | 0.00 | 0.00 |
Average | 79396.94 | 936.80 | 1.17 | 0.00 | 0.00 |
Sum | 1826129.67 | 21546.50 | 26.83 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8339.83 | 420.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8265.17 | 494.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8373.67 | 386.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8600.00 | 160.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8562.67 | 197.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8671.17 | 88.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8602.50 | 157.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8276.67 | 483.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8632.33 | 127.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8616.33 | 143.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8574.50 | 185.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8477.83 | 282.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8675.17 | 84.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8626.50 | 133.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8621.67 | 138.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8517.67 | 242.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7993.17 | 766.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7980.50 | 779.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7949.00 | 811.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7483.83 | 1276.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8392.83 | 367.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8596.17 | 163.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8354.00 | 406.00 | 0.00 | 0.00 | 0.00 |
Min | 7483.83 | 84.83 | 0.00 | 0.00 | 0.00 |
Max | 8675.17 | 1276.17 | 0.00 | 0.00 | 0.00 |
Average | 8399.27 | 360.73 | 0.00 | 0.00 | 0.00 |
Sum | 193183.17 | 8296.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 367042.17 | 1573.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330050.00 | 763.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330232.00 | 581.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330542.00 | 271.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1867.50 | 400.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1842.00 | 426.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1812.17 | 455.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 85145.67 | 18249.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367042.17 | 18249.33 | 0.00 | 0.00 | 0.00 |
Average | 79347.07 | 987.85 | 0.00 | 0.00 | 0.00 |
Sum | 1824982.50 | 22720.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:37
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.566717E+11 | 127840.40 | 20-JAN-06:01 | -6.8 | -7.3 | 0.442904E+10 | 7044.30 | 20-JAN-14:00 | -5.0 | -6.8 |
February | 0.511706E+11 | 131286.20 | 09-FEB-06:01 | -3.2 | -4.5 | 0.439248E+10 | 7499.22 | 07-FEB-14:09 | -3.2 | -4.5 |
March | 0.561413E+11 | 130589.47 | 02-MAR-06:01 | -8.3 | -8.8 | 0.565174E+10 | 7498.39 | 27-MAR-13:30 | 6.15 | 2.33 |
April | 0.529242E+11 | 122318.50 | 24-APR-04:11 | 4.40 | 3.41 | 0.527339E+10 | 7499.30 | 12-APR-13:50 | 4.40 | 3.41 |
May | 0.602321E+11 | 141290.34 | 30-MAY-04:12 | 10.60 | 8.25 | 0.576729E+10 | 7499.46 | 26-MAY-13:09 | 10.60 | 8.25 |
June | 0.626353E+11 | 140154.55 | 08-JUN-04:11 | 8.87 | 8.40 | 0.585967E+10 | 7499.34 | 13-JUN-09:39 | 17.23 | 14.20 |
July | 0.660415E+11 | 126457.95 | 10-JUL-04:11 | 8.33 | 7.93 | 0.547048E+10 | 7618.07 | 05-JUL-13:39 | 8.33 | 7.93 |
August | 0.743529E+11 | 124610.95 | 25-AUG-04:11 | 8.53 | 8.43 | 0.610963E+10 | 7521.78 | 28-AUG-13:50 | 20.60 | 18.71 |
September | 0.643769E+11 | 139287.92 | 13-SEP-04:11 | 3.50 | 3.23 | 0.529854E+10 | 7499.34 | 19-SEP-09:20 | 15.93 | 15.73 |
October | 0.608499E+11 | 147975.18 | 23-OCT-04:11 | 5.60 | 4.25 | 0.554796E+10 | 7499.32 | 20-OCT-13:09 | 5.60 | 4.25 |
November | 0.561191E+11 | 124419.62 | 13-NOV-04:01 | -8.2 | -8.9 | 0.546666E+10 | 7499.28 | 21-NOV-14:09 | 13.77 | 12.33 |
December | 0.606006E+11 | 114538.36 | 01-DEC-05:01 | -18.3 | -18.5 | 0.461101E+10 | 7482.93 | 05-DEC-14:00 | -0.6 | -0.6 |
Annual Sum or Average | 0.722116E+12 | 0.638779E+11 | ||||||||
Minimum of Months | 0.511706E+11 | 114538.36 | -18.3 | -18.5 | 0.439248E+10 | 7044.30 | -5.0 | -6.8 | ||
Maximum of Months | 0.743529E+11 | 147975.18 | 10.60 | 8.43 | 0.610963E+10 | 7618.07 | 20.60 | 18.71 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.330114E+11 | 33761.18 | 20-JAN-16:30 | -6.4 | -7.8 | 0.470672E+10 | 6734.75 | 13-JAN-14:30 | -6.4 | -7.8 |
February | 0.316838E+11 | 38740.60 | 08-FEB-16:53 | 3.30 | -1.3 | 0.445256E+10 | 6734.89 | 28-FEB-10:20 | -5.0 | -6.8 |
March | 0.436018E+11 | 107545.89 | 28-MAR-05:01 | 1.70 | 0.50 | 0.542506E+10 | 6734.89 | 08-MAR-10:09 | 1.70 | 0.50 |
April | 0.489935E+11 | 114350.32 | 24-APR-04:11 | 4.40 | 3.41 | 0.486792E+10 | 6734.88 | 07-APR-09:00 | 4.40 | 3.41 |
May | 0.558684E+11 | 120351.10 | 30-MAY-04:12 | 10.60 | 8.25 | 0.528086E+10 | 6734.89 | 15-MAY-09:20 | 10.60 | 8.25 |
June | 0.609581E+11 | 118583.07 | 26-JUN-04:11 | 16.87 | 15.70 | 0.526712E+10 | 6734.90 | 13-JUN-09:00 | 16.87 | 15.70 |
July | 0.666176E+11 | 122183.51 | 31-JUL-04:11 | 15.20 | 13.38 | 0.489714E+10 | 6734.90 | 27-JUL-13:39 | 15.20 | 13.38 |
August | 0.713459E+11 | 120590.04 | 28-AUG-04:11 | 13.90 | 12.96 | 0.549779E+10 | 6734.88 | 03-AUG-09:00 | 13.90 | 12.96 |
September | 0.518920E+11 | 116605.74 | 05-SEP-04:12 | 6.33 | 5.88 | 0.487344E+10 | 6734.92 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.463864E+11 | 111747.50 | 23-OCT-04:11 | 5.60 | 4.25 | 0.505440E+10 | 6734.91 | 25-OCT-09:00 | 3.30 | 3.04 |
November | 0.415403E+11 | 107809.90 | 15-NOV-06:01 | -1.4 | -1.4 | 0.499202E+10 | 6734.90 | 20-NOV-10:09 | 6.28 | 5.15 |
December | 0.374746E+11 | 42670.36 | 06-DEC-06:01 | -0.8 | -0.8 | 0.474709E+10 | 6734.89 | 21-DEC-10:39 | -24.3 | -24.7 |
Annual Sum or Average | 0.589374E+12 | 0.600621E+11 | ||||||||
Minimum of Months | 0.316838E+11 | 33761.18 | -6.4 | -7.8 | 0.445256E+10 | 6734.75 | -24.3 | -24.7 | ||
Maximum of Months | 0.713459E+11 | 122183.51 | 16.87 | 15.70 | 0.549779E+10 | 6734.92 | 16.87 | 15.70 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285262E+11 | 24795.51 | 27-JAN-16:37 | -15.9 | -16.8 | 0.430255E+10 | 6734.42 | 27-JAN-14:00 | -15.9 | -16.8 |
February | 0.282551E+11 | 29081.23 | 08-FEB-16:53 | 3.30 | -1.3 | 0.409411E+10 | 6734.87 | 10-FEB-14:09 | -12.6 | -13.9 |
March | 0.348271E+11 | 37494.44 | 31-MAR-15:53 | 8.90 | 3.77 | 0.516402E+10 | 6734.89 | 24-MAR-09:09 | 8.90 | 3.77 |
April | 0.360352E+11 | 99255.41 | 14-APR-05:01 | 2.12 | 1.45 | 0.476079E+10 | 6734.88 | 18-APR-09:09 | 17.88 | 10.72 |
May | 0.468851E+11 | 108482.17 | 30-MAY-04:12 | 10.60 | 8.25 | 0.525615E+10 | 6734.91 | 15-MAY-09:20 | 10.60 | 8.25 |
June | 0.510107E+11 | 107551.91 | 28-JUN-04:11 | 15.20 | 14.63 | 0.525059E+10 | 6734.90 | 13-JUN-09:00 | 15.20 | 14.63 |
July | 0.512670E+11 | 107505.30 | 31-JUL-04:11 | 15.20 | 13.38 | 0.488750E+10 | 6734.91 | 27-JUL-13:50 | 15.20 | 13.38 |
August | 0.525043E+11 | 104865.63 | 25-AUG-04:11 | 8.53 | 8.43 | 0.547689E+10 | 6734.88 | 03-AUG-09:00 | 8.53 | 8.43 |
September | 0.418155E+11 | 102878.00 | 01-SEP-04:11 | 15.93 | 15.93 | 0.483973E+10 | 6734.91 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.351380E+11 | 98846.18 | 20-OCT-05:01 | 7.52 | 7.52 | 0.495124E+10 | 6734.90 | 25-OCT-09:00 | 3.30 | 3.04 |
November | 0.302828E+11 | 35374.40 | 17-NOV-16:13 | 8.90 | 2.59 | 0.466664E+10 | 6734.89 | 01-NOV-13:50 | 8.90 | 2.59 |
December | 0.297350E+11 | 25633.80 | 01-DEC-17:00 | -19.7 | -20.2 | 0.422948E+10 | 6734.83 | 01-DEC-14:30 | -19.7 | -20.2 |
Annual Sum or Average | 0.466282E+12 | 0.578797E+11 | ||||||||
Minimum of Months | 0.282551E+11 | 24795.51 | -19.7 | -20.2 | 0.409411E+10 | 6734.42 | -19.7 | -20.2 | ||
Maximum of Months | 0.525043E+11 | 108482.17 | 15.93 | 15.93 | 0.547689E+10 | 6734.91 | 17.88 | 14.63 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134656E+11 | 22148.41 | 19-JAN-17:00 | -2.8 | -3.6 | 0.375897E+10 | 5509.70 | 19-JAN-14:00 | -2.8 | -3.6 |
February | 0.161625E+11 | 25266.07 | 08-FEB-17:00 | 3.30 | -1.3 | 0.348981E+10 | 5980.85 | 08-FEB-14:00 | 3.30 | -1.3 |
March | 0.244917E+11 | 27423.10 | 31-MAR-16:00 | 8.90 | 3.77 | 0.432625E+10 | 6323.08 | 29-MAR-13:00 | 8.90 | 3.77 |
April | 0.300985E+11 | 41960.76 | 13-APR-16:00 | 20.00 | 8.11 | 0.416000E+10 | 6734.84 | 14-APR-13:30 | 16.10 | 7.07 |
May | 0.439824E+11 | 129203.89 | 26-MAY-05:02 | 19.40 | 15.69 | 0.496966E+10 | 6734.87 | 19-MAY-09:20 | 19.40 | 15.69 |
June | 0.515512E+11 | 125473.27 | 28-JUN-05:01 | 15.15 | 14.73 | 0.512904E+10 | 6734.90 | 13-JUN-09:00 | 15.15 | 14.73 |
July | 0.528944E+11 | 127457.15 | 13-JUL-05:01 | 15.00 | 14.67 | 0.479525E+10 | 6734.91 | 27-JUL-13:00 | 16.70 | 15.64 |
August | 0.510499E+11 | 127150.02 | 10-AUG-05:01 | 15.50 | 14.84 | 0.531928E+10 | 6734.91 | 10-AUG-13:39 | 19.03 | 16.37 |
September | 0.363261E+11 | 123799.95 | 01-SEP-05:02 | 15.68 | 15.63 | 0.442926E+10 | 6734.79 | 12-SEP-13:39 | 13.13 | 10.05 |
October | 0.268943E+11 | 37090.94 | 20-OCT-15:53 | 18.30 | 9.93 | 0.417115E+10 | 6734.86 | 20-OCT-13:00 | 18.30 | 9.93 |
November | 0.207981E+11 | 26047.45 | 01-NOV-16:00 | 17.80 | 13.26 | 0.391827E+10 | 6096.22 | 17-NOV-14:00 | 10.60 | 3.43 |
December | 0.142833E+11 | 22426.17 | 28-DEC-17:00 | -2.4 | -4.0 | 0.363195E+10 | 5604.32 | 28-DEC-14:00 | -2.4 | -4.0 |
Annual Sum or Average | 0.381998E+12 | 0.520989E+11 | ||||||||
Minimum of Months | 0.134656E+11 | 22148.41 | -2.8 | -4.0 | 0.348981E+10 | 5509.70 | -2.8 | -4.0 | ||
Maximum of Months | 0.528944E+11 | 129203.89 | 20.00 | 15.69 | 0.531928E+10 | 6734.91 | 19.40 | 16.37 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243096E+09 | 3356.58 | 30-JAN-06:05 | -4.0 | -4.6 | 0.464750E+09 | 632.65 | 19-JAN-14:09 | -4.0 | -4.6 |
February | 0.918997E+09 | 3978.68 | 08-FEB-14:41 | 5.00 | -0.5 | 0.427368E+09 | 708.70 | 08-FEB-14:50 | 5.00 | -0.5 |
March | 0.280196E+10 | 5414.67 | 26-MAR-16:51 | 10.00 | 4.91 | 0.532534E+09 | 807.01 | 28-MAR-13:00 | 6.10 | 2.91 |
April | 0.555781E+10 | 7835.41 | 18-APR-14:00 | 17.80 | 10.49 | 0.532867E+09 | 845.63 | 14-APR-13:30 | 17.80 | 10.49 |
May | 0.915366E+10 | 11197.07 | 23-MAY-14:40 | 26.40 | 17.14 | 0.640944E+09 | 845.64 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.113813E+11 | 15333.56 | 29-JUN-04:11 | 22.20 | 19.58 | 0.655155E+09 | 845.65 | 14-JUN-13:00 | 22.20 | 19.58 |
July | 0.125593E+11 | 18245.13 | 03-JUL-04:11 | 18.13 | 16.58 | 0.611931E+09 | 845.64 | 27-JUL-13:39 | 16.33 | 15.15 |
August | 0.115684E+11 | 12012.62 | 08-AUG-15:00 | 30.60 | 23.36 | 0.680805E+09 | 845.65 | 10-AUG-13:30 | 18.85 | 16.08 |
September | 0.730349E+10 | 9804.07 | 01-SEP-15:10 | 26.10 | 17.79 | 0.575246E+09 | 845.64 | 11-SEP-13:50 | 18.90 | 14.67 |
October | 0.525264E+10 | 6614.31 | 01-OCT-14:31 | 15.20 | 9.17 | 0.541156E+09 | 845.63 | 20-OCT-13:00 | 18.90 | 10.07 |
November | 0.299850E+10 | 5529.25 | 21-NOV-06:02 | 10.10 | 9.75 | 0.493376E+09 | 836.20 | 01-NOV-13:00 | 10.10 | 9.75 |
December | 0.520074E+09 | 3543.25 | 06-DEC-06:02 | -0.8 | -0.8 | 0.449076E+09 | 653.68 | 05-DEC-14:09 | -0.8 | -0.8 |
Annual Sum or Average | 0.702592E+11 | 0.660521E+10 | ||||||||
Minimum of Months | 0.243096E+09 | 3356.58 | -4.0 | -4.6 | 0.427368E+09 | 632.65 | -4.0 | -4.6 | ||
Maximum of Months | 0.125593E+11 | 18245.13 | 30.60 | 23.36 | 0.680805E+09 | 845.65 | 22.38 | 19.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.389107E+09 | 3920.79 | 25-JAN-10:10 | -23.2 | -23.5 | 0.299454E+09 | 417.98 | 25-JAN-10:20 | -23.1 | -23.4 |
February | 0.142638E+10 | 5583.43 | 28-FEB-09:55 | -6.1 | -7.7 | 0.278191E+09 | 531.95 | 28-FEB-10:09 | -5.5 | -7.3 |
March | 0.353296E+10 | 11457.46 | 26-MAR-10:11 | 3.33 | 0.54 | 0.353099E+09 | 544.96 | 23-MAR-09:09 | 3.33 | 0.54 |
April | 0.689432E+10 | 32711.07 | 30-APR-08:51 | 7.80 | 4.07 | 0.352037E+09 | 544.96 | 18-APR-09:09 | 7.80 | 4.07 |
May | 0.985265E+10 | 23477.94 | 21-MAY-09:02 | 12.52 | 7.56 | 0.406226E+09 | 544.98 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.119452E+11 | 38626.46 | 25-JUN-08:61 | 24.08 | 20.82 | 0.415269E+09 | 544.98 | 14-JUN-13:00 | 24.08 | 20.82 |
July | 0.129573E+11 | 33477.26 | 23-JUL-09:31 | 26.13 | 22.79 | 0.390150E+09 | 544.96 | 31-JUL-13:00 | 20.60 | 14.60 |
August | 0.112592E+11 | 35376.94 | 20-AUG-10:11 | 23.17 | 15.92 | 0.421917E+09 | 544.97 | 04-AUG-09:00 | 23.17 | 15.92 |
September | 0.785880E+10 | 17545.77 | 24-SEP-09:32 | 15.20 | 10.71 | 0.354035E+09 | 544.97 | 14-SEP-09:09 | 15.20 | 10.71 |
October | 0.495657E+10 | 32004.90 | 22-OCT-09:11 | 13.67 | 11.29 | 0.329715E+09 | 544.96 | 19-OCT-09:00 | 13.67 | 11.29 |
November | 0.255968E+10 | 5832.11 | 11-NOV-10:21 | -3.0 | -5.4 | 0.308278E+09 | 531.73 | 16-NOV-10:09 | 2.15 | -0.3 |
December | 0.434614E+09 | 4098.94 | 28-DEC-10:00 | -3.2 | -4.3 | 0.289225E+09 | 428.77 | 01-DEC-10:20 | -3.2 | -4.3 |
Annual Sum or Average | 0.740668E+11 | 0.419760E+10 | ||||||||
Minimum of Months | 0.389107E+09 | 3920.79 | -23.2 | -23.5 | 0.278191E+09 | 417.98 | -23.1 | -23.4 | ||
Maximum of Months | 0.129573E+11 | 38626.46 | 26.13 | 22.79 | 0.421917E+09 | 544.98 | 24.08 | 20.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342094E+10 | 19197.27 | 27-JAN-13:30 | -15.0 | -16.1 | 0.507505E+09 | 845.65 | 05-JAN-14:20 | -15.0 | -16.1 |
February | 0.554818E+10 | 39223.81 | 20-FEB-13:31 | 4.83 | 0.32 | 0.484539E+09 | 845.65 | 28-FEB-14:09 | 4.27 | 0.38 |
March | 0.756829E+10 | 45028.44 | 26-MAR-13:31 | 8.70 | 4.42 | 0.584002E+09 | 845.65 | 20-MAR-13:00 | 8.70 | 4.42 |
April | 0.106339E+11 | 41049.98 | 23-APR-13:12 | 23.33 | 15.57 | 0.547436E+09 | 845.91 | 13-APR-13:30 | 23.33 | 15.57 |
May | 0.133065E+11 | 39938.88 | 21-MAY-13:41 | 20.83 | 11.09 | 0.626244E+09 | 845.67 | 10-MAY-13:00 | 20.83 | 11.09 |
June | 0.148012E+11 | 42106.75 | 18-JUN-13:01 | 26.20 | 17.95 | 0.637272E+09 | 845.70 | 14-JUN-13:00 | 26.20 | 17.95 |
July | 0.171092E+11 | 42999.19 | 16-JUL-12:51 | 23.90 | 18.44 | 0.601044E+09 | 845.79 | 31-JUL-13:30 | 20.00 | 14.03 |
August | 0.173874E+11 | 45607.04 | 20-AUG-12:51 | 25.00 | 15.37 | 0.663619E+09 | 846.20 | 25-AUG-13:00 | 28.30 | 18.83 |
September | 0.129513E+11 | 43921.08 | 03-SEP-14:21 | 21.40 | 16.15 | 0.562057E+09 | 846.25 | 01-SEP-13:00 | 21.40 | 16.15 |
October | 0.914709E+10 | 49044.76 | 22-OCT-13:11 | 18.67 | 12.99 | 0.539042E+09 | 845.65 | 19-OCT-09:00 | 18.67 | 12.99 |
November | 0.564754E+10 | 22687.20 | 17-NOV-13:02 | 10.10 | 3.25 | 0.520218E+09 | 845.65 | 29-NOV-10:30 | -8.6 | -9.6 |
December | 0.260971E+10 | 15187.50 | 20-DEC-13:15 | -21.1 | -21.6 | 0.475293E+09 | 845.65 | 20-DEC-14:20 | -19.8 | -20.5 |
Annual Sum or Average | 0.120131E+12 | 0.674827E+10 | ||||||||
Minimum of Months | 0.260971E+10 | 15187.50 | -21.1 | -21.6 | 0.475293E+09 | 845.65 | -19.8 | -20.5 | ||
Maximum of Months | 0.173874E+11 | 49044.76 | 26.20 | 18.44 | 0.663619E+09 | 846.25 | 28.30 | 18.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127284E+10 | 6319.09 | 27-JAN-15:50 | -14.4 | -15.6 | 0.304105E+09 | 485.44 | 27-JAN-15:00 | -14.4 | -15.6 |
February | 0.277981E+10 | 10727.06 | 28-FEB-15:32 | 6.10 | 1.55 | 0.286613E+09 | 544.96 | 28-FEB-14:50 | 6.10 | 1.55 |
March | 0.627675E+10 | 43017.52 | 26-MAR-16:51 | 10.00 | 4.91 | 0.354711E+09 | 544.96 | 31-MAR-13:00 | 8.30 | 3.10 |
April | 0.998339E+10 | 43396.05 | 23-APR-16:31 | 26.30 | 16.77 | 0.346376E+09 | 544.96 | 14-APR-13:30 | 26.30 | 16.77 |
May | 0.125225E+11 | 44043.34 | 21-MAY-16:21 | 22.25 | 11.27 | 0.396749E+09 | 544.97 | 10-MAY-13:00 | 22.25 | 11.27 |
June | 0.139524E+11 | 41165.46 | 17-JUN-19:41 | 18.03 | 12.13 | 0.409122E+09 | 544.99 | 14-JUN-13:00 | 18.03 | 12.13 |
July | 0.163868E+11 | 48077.44 | 16-JUL-16:51 | 21.10 | 15.60 | 0.391065E+09 | 544.97 | 31-JUL-13:00 | 20.60 | 14.60 |
August | 0.158818E+11 | 40868.92 | 05-AUG-17:41 | 22.30 | 14.14 | 0.434463E+09 | 544.98 | 22-AUG-13:09 | 23.98 | 16.30 |
September | 0.986625E+10 | 45612.43 | 03-SEP-17:01 | 21.52 | 16.01 | 0.349555E+09 | 544.96 | 07-SEP-13:39 | 23.90 | 14.37 |
October | 0.718342E+10 | 38612.41 | 22-OCT-15:51 | 18.90 | 12.36 | 0.335968E+09 | 544.96 | 17-OCT-13:00 | 18.90 | 12.36 |
November | 0.481164E+10 | 8707.11 | 17-NOV-15:23 | 10.30 | 3.32 | 0.320628E+09 | 544.96 | 16-NOV-14:39 | 10.30 | 3.32 |
December | 0.257183E+10 | 5972.76 | 20-DEC-15:30 | -19.5 | -20.3 | 0.293609E+09 | 471.12 | 20-DEC-14:00 | -19.5 | -20.3 |
Annual Sum or Average | 0.103489E+12 | 0.422296E+10 | ||||||||
Minimum of Months | 0.127284E+10 | 5972.76 | -19.5 | -20.3 | 0.286613E+09 | 471.12 | -19.5 | -20.3 | ||
Maximum of Months | 0.163868E+11 | 48077.44 | 26.30 | 16.77 | 0.434463E+09 | 544.99 | 26.30 | 16.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34341681.26 | 4347.62 | 19-JAN-06:04 | -3.3 | -3.7 | 0.463032E+09 | 626.08 | 09-JAN-10:09 | -3.3 | -3.7 |
February | 0.224087E+09 | 4455.85 | 22-FEB-06:04 | -10.3 | -10.6 | 0.420843E+09 | 625.79 | 13-FEB-10:09 | -10.3 | -10.6 |
March | 0.126103E+10 | 5562.82 | 31-MAR-14:02 | 8.30 | 3.02 | 0.507328E+09 | 679.44 | 28-MAR-13:00 | 8.30 | 3.02 |
April | 0.377870E+10 | 8813.13 | 23-APR-16:22 | 26.40 | 16.81 | 0.471759E+09 | 796.16 | 18-APR-13:00 | 26.40 | 16.81 |
May | 0.865774E+10 | 10450.69 | 24-MAY-14:30 | 27.45 | 17.67 | 0.594948E+09 | 845.63 | 19-MAY-13:20 | 27.45 | 17.67 |
June | 0.108686E+11 | 18337.60 | 28-JUN-05:01 | 15.15 | 14.73 | 0.630211E+09 | 845.64 | 14-JUN-13:00 | 15.15 | 14.73 |
July | 0.111923E+11 | 14727.03 | 21-JUL-05:01 | 17.98 | 17.55 | 0.594707E+09 | 845.63 | 17-JUL-13:30 | 17.98 | 17.55 |
August | 0.101949E+11 | 10797.24 | 09-AUG-15:30 | 27.25 | 21.19 | 0.634898E+09 | 845.63 | 22-AUG-13:09 | 23.98 | 16.30 |
September | 0.666636E+10 | 8691.72 | 01-SEP-13:30 | 25.00 | 18.03 | 0.512293E+09 | 844.52 | 07-SEP-13:00 | 23.90 | 14.48 |
October | 0.345766E+10 | 7266.70 | 01-OCT-14:11 | 15.40 | 9.25 | 0.478750E+09 | 723.19 | 02-OCT-13:50 | 10.18 | 9.48 |
November | 0.100074E+10 | 5397.26 | 01-NOV-14:02 | 17.88 | 13.29 | 0.461433E+09 | 707.97 | 01-NOV-13:00 | 17.88 | 13.29 |
December | 43178692.75 | 4522.43 | 06-DEC-06:03 | -0.8 | -0.8 | 0.446551E+09 | 625.98 | 21-DEC-14:09 | -17.0 | -17.8 |
Annual Sum or Average | 0.573796E+11 | 0.621675E+10 | ||||||||
Minimum of Months | 34341681.26 | 4347.62 | -10.3 | -10.6 | 0.420843E+09 | 625.79 | -17.0 | -17.8 | ||
Maximum of Months | 0.111923E+11 | 18337.60 | 27.45 | 21.19 | 0.634898E+09 | 845.64 | 27.45 | 17.67 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 80358400.71 | 4226.12 | 25-JAN-11:03 | -22.4 | -22.8 | 0.215440E+09 | 425.04 | 25-JAN-11:09 | -22.4 | -22.8 |
February | 0.539761E+09 | 12822.02 | 28-FEB-11:01 | -2.4 | -4.8 | 0.199568E+09 | 548.49 | 28-FEB-11:09 | -2.4 | -4.8 |
March | 0.213897E+10 | 19049.51 | 31-MAR-10:01 | 2.07 | -0.7 | 0.252272E+09 | 548.49 | 23-MAR-10:09 | 2.07 | -0.7 |
April | 0.529565E+10 | 17857.42 | 22-APR-10:02 | 13.58 | 4.72 | 0.251974E+09 | 548.50 | 18-APR-10:09 | 13.58 | 4.72 |
May | 0.900738E+10 | 37742.55 | 21-MAY-08:51 | 12.20 | 7.39 | 0.293254E+09 | 548.51 | 23-MAY-10:09 | 18.85 | 13.45 |
June | 0.115740E+11 | 41588.27 | 25-JUN-08:11 | 24.27 | 20.87 | 0.302399E+09 | 548.52 | 07-JUN-12:09 | 24.27 | 20.87 |
July | 0.122942E+11 | 36350.01 | 23-JUL-09:31 | 26.13 | 22.79 | 0.286262E+09 | 548.51 | 31-JUL-14:09 | 20.50 | 14.52 |
August | 0.100032E+11 | 34918.23 | 20-AUG-09:12 | 21.33 | 15.66 | 0.303759E+09 | 548.52 | 04-AUG-10:09 | 21.33 | 15.66 |
September | 0.638722E+10 | 27263.00 | 10-SEP-09:42 | 15.22 | 10.50 | 0.253437E+09 | 548.50 | 07-SEP-14:09 | 15.22 | 10.50 |
October | 0.280878E+10 | 16850.12 | 19-OCT-10:01 | 14.27 | 10.24 | 0.235157E+09 | 548.49 | 25-OCT-10:09 | 4.05 | 3.56 |
November | 0.876224E+09 | 11966.11 | 16-NOV-11:01 | 4.68 | 0.79 | 0.220234E+09 | 548.49 | 01-NOV-14:09 | 4.68 | 0.79 |
December | 88325029.07 | 4654.27 | 28-DEC-11:02 | -2.3 | -3.6 | 0.207651E+09 | 441.88 | 28-DEC-11:09 | -2.3 | -3.6 |
Annual Sum or Average | 0.610940E+11 | 0.302141E+10 | ||||||||
Minimum of Months | 80358400.71 | 4226.12 | -22.4 | -22.8 | 0.199568E+09 | 425.04 | -22.4 | -22.8 | ||
Maximum of Months | 0.122942E+11 | 41588.27 | 26.13 | 22.79 | 0.303759E+09 | 548.52 | 24.27 | 20.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.329413E+10 | 22180.00 | 27-JAN-13:40 | -14.8 | -15.9 | 0.502861E+09 | 845.65 | 05-JAN-14:30 | -14.8 | -15.9 |
February | 0.577820E+10 | 39149.95 | 20-FEB-14:21 | 6.95 | 1.52 | 0.479270E+09 | 845.65 | 28-FEB-10:30 | -4.4 | -6.4 |
March | 0.748845E+10 | 47604.79 | 26-MAR-14:21 | 9.75 | 4.96 | 0.577202E+09 | 845.72 | 31-MAR-13:20 | 7.23 | 2.44 |
April | 0.972347E+10 | 46855.01 | 23-APR-13:01 | 23.07 | 15.44 | 0.536296E+09 | 846.24 | 13-APR-13:30 | 23.07 | 15.44 |
May | 0.128855E+11 | 41520.47 | 21-MAY-14:51 | 22.80 | 11.46 | 0.614772E+09 | 846.34 | 18-MAY-13:20 | 22.80 | 11.46 |
June | 0.141885E+11 | 41925.53 | 25-JUN-11:31 | 27.07 | 21.57 | 0.625934E+09 | 846.28 | 30-JUN-13:20 | 31.50 | 24.23 |
July | 0.157954E+11 | 42417.02 | 23-JUL-13:32 | 30.00 | 22.59 | 0.592061E+09 | 846.32 | 31-JUL-13:20 | 19.80 | 13.84 |
August | 0.159959E+11 | 42405.75 | 13-AUG-13:32 | 23.13 | 14.35 | 0.645388E+09 | 846.44 | 29-AUG-13:20 | 24.80 | 19.85 |
September | 0.126457E+11 | 48245.93 | 04-SEP-12:01 | 15.68 | 9.30 | 0.548739E+09 | 849.25 | 01-SEP-13:20 | 15.68 | 9.30 |
October | 0.854897E+10 | 52647.81 | 22-OCT-13:11 | 18.67 | 12.99 | 0.524199E+09 | 846.49 | 19-OCT-13:30 | 18.67 | 12.99 |
November | 0.459578E+10 | 24628.61 | 17-NOV-13:02 | 10.10 | 3.25 | 0.504651E+09 | 845.65 | 17-NOV-10:30 | 10.10 | 3.25 |
December | 0.197802E+10 | 15916.43 | 20-DEC-13:24 | -20.9 | -21.5 | 0.469902E+09 | 845.65 | 26-DEC-14:09 | -19.4 | -20.1 |
Annual Sum or Average | 0.112918E+12 | 0.662127E+10 | ||||||||
Minimum of Months | 0.197802E+10 | 15916.43 | -20.9 | -21.5 | 0.469902E+09 | 845.65 | -19.4 | -20.1 | ||
Maximum of Months | 0.159959E+11 | 52647.81 | 30.00 | 22.59 | 0.645388E+09 | 849.25 | 31.50 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.391306E+09 | 5417.19 | 27-JAN-15:50 | -14.4 | -15.6 | 0.299584E+09 | 449.91 | 27-JAN-15:00 | -14.4 | -15.6 |
February | 0.120112E+10 | 8143.48 | 08-FEB-16:23 | 3.85 | -1.1 | 0.277864E+09 | 521.20 | 08-FEB-16:00 | 3.30 | -1.3 |
March | 0.295961E+10 | 37181.96 | 26-MAR-17:01 | 9.82 | 4.83 | 0.337994E+09 | 521.20 | 31-MAR-15:00 | 8.90 | 3.77 |
April | 0.581861E+10 | 44931.38 | 23-APR-17:41 | 25.68 | 16.51 | 0.313345E+09 | 544.36 | 13-APR-13:00 | 25.68 | 16.51 |
May | 0.104542E+11 | 44668.79 | 14-MAY-17:11 | 20.00 | 8.46 | 0.372991E+09 | 544.95 | 17-MAY-13:50 | 26.02 | 16.16 |
June | 0.117723E+11 | 39865.63 | 17-JUN-19:41 | 18.03 | 12.13 | 0.386342E+09 | 544.97 | 14-JUN-13:00 | 18.03 | 12.13 |
July | 0.127408E+11 | 43471.51 | 04-JUL-16:11 | 24.27 | 19.86 | 0.367949E+09 | 544.96 | 17-JUL-13:30 | 18.60 | 14.13 |
August | 0.114098E+11 | 38583.77 | 05-AUG-17:41 | 22.30 | 14.14 | 0.393583E+09 | 544.95 | 02-AUG-13:00 | 22.30 | 14.14 |
September | 0.729462E+10 | 38259.10 | 03-SEP-17:11 | 21.33 | 15.90 | 0.322302E+09 | 544.68 | 07-SEP-13:00 | 23.90 | 14.48 |
October | 0.393682E+10 | 23440.36 | 22-OCT-15:51 | 18.90 | 12.36 | 0.314820E+09 | 521.20 | 06-OCT-15:00 | 18.90 | 12.36 |
November | 0.137164E+10 | 6107.61 | 17-NOV-15:40 | 10.20 | 3.28 | 0.300626E+09 | 490.62 | 17-NOV-15:50 | 10.10 | 3.24 |
December | 0.221156E+09 | 4365.49 | 20-DEC-15:30 | -19.5 | -20.3 | 0.288024E+09 | 403.43 | 11-DEC-14:00 | -19.5 | -20.3 |
Annual Sum or Average | 0.695719E+11 | 0.397543E+10 | ||||||||
Minimum of Months | 0.221156E+09 | 4365.49 | -19.5 | -20.3 | 0.277864E+09 | 403.43 | -19.5 | -20.3 | ||
Maximum of Months | 0.127408E+11 | 44931.38 | 25.68 | 19.86 | 0.393583E+09 | 544.97 | 26.02 | 16.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26420151.92 | 5219.38 | 21-JAN-17:01 | -5.0 | -7.1 | 0.462660E+09 | 626.08 | 09-JAN-14:00 | -5.0 | -7.1 |
February | 0.146975E+09 | 5979.91 | 07-FEB-06:04 | -7.7 | -8.0 | 0.420278E+09 | 625.80 | 10-FEB-10:09 | -18.5 | -19.0 |
March | 0.662267E+09 | 6000.96 | 23-MAR-05:04 | -17.1 | -17.4 | 0.504295E+09 | 625.80 | 15-MAR-09:09 | -17.1 | -17.4 |
April | 0.302061E+10 | 10965.48 | 23-APR-16:11 | 26.50 | 16.86 | 0.456386E+09 | 743.93 | 18-APR-13:00 | 26.50 | 16.86 |
May | 0.870990E+10 | 11462.68 | 18-MAY-15:00 | 28.90 | 16.60 | 0.553885E+09 | 845.62 | 24-MAY-13:20 | 26.57 | 17.52 |
June | 0.115148E+11 | 17679.81 | 28-JUN-05:01 | 15.15 | 14.73 | 0.592122E+09 | 845.64 | 21-JUN-13:50 | 15.15 | 14.73 |
July | 0.120685E+11 | 13587.73 | 23-JUL-16:11 | 29.43 | 22.47 | 0.562547E+09 | 845.62 | 12-JUL-13:20 | 29.43 | 22.47 |
August | 0.106731E+11 | 11907.57 | 08-AUG-15:50 | 30.60 | 23.05 | 0.589999E+09 | 845.61 | 23-AUG-13:20 | 25.77 | 20.28 |
September | 0.584397E+10 | 10973.44 | 03-SEP-14:21 | 21.40 | 16.15 | 0.475102E+09 | 811.68 | 01-SEP-13:00 | 21.40 | 16.15 |
October | 0.195976E+10 | 8043.88 | 22-OCT-14:31 | 19.40 | 12.77 | 0.467285E+09 | 686.27 | 20-OCT-13:00 | 19.40 | 12.77 |
November | 0.441425E+09 | 6021.39 | 01-NOV-15:00 | 18.30 | 13.44 | 0.458983E+09 | 635.22 | 01-NOV-13:00 | 18.30 | 13.44 |
December | 32372159.09 | 6148.57 | 06-DEC-06:03 | -0.8 | -0.8 | 0.446110E+09 | 626.08 | 11-DEC-14:00 | -17.8 | -18.7 |
Annual Sum or Average | 0.551001E+11 | 0.598965E+10 | ||||||||
Minimum of Months | 26420151.92 | 5219.38 | -17.1 | -17.4 | 0.420278E+09 | 625.80 | -18.5 | -19.0 | ||
Maximum of Months | 0.120685E+11 | 17679.81 | 30.60 | 23.05 | 0.592122E+09 | 845.64 | 29.43 | 22.47 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19941136.60 | 4081.92 | 17-JAN-06:04 | -5.9 | -6.4 | 0.298164E+09 | 403.48 | 19-JAN-14:09 | -2.8 | -3.6 |
February | 0.410138E+09 | 4713.29 | 28-FEB-10:30 | -4.4 | -6.4 | 0.271314E+09 | 449.89 | 28-FEB-10:39 | -3.9 | -5.9 |
March | 0.175081E+10 | 6670.72 | 31-MAR-09:51 | 1.70 | -0.9 | 0.336176E+09 | 544.96 | 20-MAR-09:39 | 1.70 | -0.9 |
April | 0.465312E+10 | 14767.91 | 18-APR-09:25 | 18.05 | 10.95 | 0.334006E+09 | 544.96 | 18-APR-09:09 | 18.05 | 10.95 |
May | 0.858625E+10 | 18002.41 | 18-MAY-09:30 | 24.55 | 16.00 | 0.389228E+09 | 544.98 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.114468E+11 | 39501.05 | 18-JUN-09:51 | 23.30 | 16.38 | 0.407058E+09 | 544.98 | 14-JUN-13:00 | 23.30 | 16.38 |
July | 0.122474E+11 | 36347.53 | 23-JUL-09:31 | 26.13 | 22.79 | 0.386419E+09 | 544.96 | 31-JUL-13:00 | 20.60 | 14.60 |
August | 0.982544E+10 | 37552.50 | 20-AUG-10:21 | 23.35 | 15.88 | 0.404224E+09 | 544.98 | 22-AUG-13:09 | 23.98 | 16.30 |
September | 0.573194E+10 | 16921.04 | 01-SEP-09:30 | 20.85 | 17.74 | 0.331079E+09 | 544.97 | 07-SEP-13:09 | 23.90 | 14.19 |
October | 0.207840E+10 | 8720.34 | 19-OCT-09:33 | 12.97 | 9.35 | 0.310319E+09 | 544.96 | 19-OCT-09:00 | 13.90 | 10.03 |
November | 0.590543E+09 | 4370.60 | 16-NOV-10:01 | 2.15 | -0.3 | 0.295987E+09 | 427.79 | 16-NOV-10:09 | 2.15 | -0.3 |
December | 35046217.53 | 4187.09 | 06-DEC-06:03 | -0.8 | -0.8 | 0.287499E+09 | 403.45 | 11-DEC-14:00 | -17.8 | -18.7 |
Annual Sum or Average | 0.573758E+11 | 0.405147E+10 | ||||||||
Minimum of Months | 19941136.60 | 4081.92 | -5.9 | -6.4 | 0.271314E+09 | 403.45 | -17.8 | -18.7 | ||
Maximum of Months | 0.122474E+11 | 39501.05 | 26.13 | 22.79 | 0.407058E+09 | 544.98 | 23.98 | 16.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.266056E+10 | 19186.38 | 27-JAN-13:50 | -14.6 | -15.8 | 0.489796E+09 | 845.65 | 09-JAN-14:20 | -14.6 | -15.8 |
February | 0.495298E+10 | 27422.00 | 28-FEB-13:31 | 3.33 | -0.5 | 0.463680E+09 | 845.65 | 28-FEB-10:50 | 3.33 | -0.5 |
March | 0.623273E+10 | 54300.19 | 26-MAR-14:31 | 10.03 | 5.07 | 0.559356E+09 | 845.65 | 20-MAR-13:00 | 10.03 | 5.07 |
April | 0.856161E+10 | 56176.46 | 23-APR-14:51 | 25.60 | 16.48 | 0.519074E+09 | 845.65 | 14-APR-13:30 | 25.60 | 16.48 |
May | 0.125382E+11 | 31380.53 | 14-MAY-14:41 | 19.82 | 8.15 | 0.586412E+09 | 845.68 | 10-MAY-13:00 | 19.82 | 8.15 |
June | 0.143157E+11 | 31374.36 | 18-JUN-14:32 | 26.30 | 18.90 | 0.602564E+09 | 845.71 | 14-JUN-13:00 | 26.30 | 18.90 |
July | 0.161410E+11 | 53644.41 | 16-JUL-14:21 | 24.15 | 18.35 | 0.573195E+09 | 845.68 | 31-JUL-13:00 | 20.60 | 14.60 |
August | 0.159332E+11 | 57078.13 | 20-AUG-13:41 | 25.00 | 16.26 | 0.615326E+09 | 845.70 | 22-AUG-13:09 | 23.98 | 16.30 |
September | 0.113215E+11 | 56756.93 | 04-SEP-12:01 | 15.68 | 9.30 | 0.519455E+09 | 846.13 | 01-SEP-13:00 | 15.68 | 9.30 |
October | 0.662910E+10 | 62316.52 | 22-OCT-13:11 | 18.67 | 12.99 | 0.504419E+09 | 845.65 | 19-OCT-09:39 | 18.67 | 12.99 |
November | 0.351647E+10 | 21889.39 | 17-NOV-13:12 | 10.20 | 3.29 | 0.490417E+09 | 845.65 | 07-NOV-14:30 | 10.20 | 3.29 |
December | 0.149309E+10 | 13339.31 | 26-DEC-13:23 | -19.8 | -20.4 | 0.458661E+09 | 845.65 | 20-DEC-14:20 | -19.8 | -20.4 |
Annual Sum or Average | 0.104296E+12 | 0.638236E+10 | ||||||||
Minimum of Months | 0.149309E+10 | 13339.31 | -19.8 | -20.4 | 0.458661E+09 | 845.65 | -19.8 | -20.4 | ||
Maximum of Months | 0.161410E+11 | 62316.52 | 26.30 | 18.90 | 0.615326E+09 | 846.13 | 26.30 | 18.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288070E+09 | 5280.78 | 27-JAN-15:50 | -14.4 | -15.6 | 0.298515E+09 | 422.49 | 27-JAN-15:00 | -14.4 | -15.6 |
February | 0.999657E+09 | 7970.31 | 28-FEB-15:51 | 6.10 | 1.55 | 0.275963E+09 | 521.20 | 08-FEB-16:49 | 6.10 | 1.55 |
March | 0.241695E+10 | 23680.14 | 26-MAR-17:11 | 9.63 | 4.75 | 0.335322E+09 | 521.20 | 31-MAR-15:00 | 8.90 | 3.77 |
April | 0.510533E+10 | 48298.82 | 23-APR-16:51 | 26.10 | 16.67 | 0.309176E+09 | 544.10 | 13-APR-13:00 | 26.10 | 16.67 |
May | 0.996260E+10 | 47174.20 | 14-MAY-17:21 | 20.00 | 8.49 | 0.363637E+09 | 544.95 | 17-MAY-13:39 | 25.93 | 16.13 |
June | 0.116065E+11 | 42396.48 | 17-JUN-19:41 | 18.03 | 12.13 | 0.378451E+09 | 544.98 | 14-JUN-13:00 | 18.03 | 12.13 |
July | 0.127085E+11 | 48165.04 | 16-JUL-16:21 | 21.95 | 16.03 | 0.360612E+09 | 544.96 | 17-JUL-13:50 | 19.13 | 14.51 |
August | 0.111048E+11 | 41100.15 | 05-AUG-17:41 | 22.30 | 14.14 | 0.382846E+09 | 544.95 | 22-AUG-13:00 | 24.40 | 16.49 |
September | 0.636367E+10 | 46040.32 | 03-SEP-17:01 | 21.52 | 16.01 | 0.314665E+09 | 544.95 | 01-SEP-13:00 | 21.52 | 16.01 |
October | 0.285542E+10 | 13321.75 | 19-OCT-16:00 | 21.70 | 13.55 | 0.311335E+09 | 524.96 | 19-OCT-13:00 | 21.70 | 13.55 |
November | 0.937825E+09 | 6040.97 | 17-NOV-15:40 | 10.20 | 3.28 | 0.297891E+09 | 462.96 | 17-NOV-15:50 | 10.10 | 3.24 |
December | 0.123221E+09 | 4669.35 | 06-DEC-06:03 | -0.8 | -0.8 | 0.287643E+09 | 403.46 | 04-DEC-10:50 | -0.8 | -0.8 |
Annual Sum or Average | 0.644725E+11 | 0.391606E+10 | ||||||||
Minimum of Months | 0.123221E+09 | 4669.35 | -14.4 | -15.6 | 0.275963E+09 | 403.46 | -14.4 | -15.6 | ||
Maximum of Months | 0.127085E+11 | 48298.82 | 26.10 | 16.67 | 0.382846E+09 | 544.98 | 26.10 | 16.67 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207712E+10 | 20582.03 | 28-JAN-04:01 | -26.7 | -26.9 | 0.00 | 0.00 | 01-JAN-00:10 | -26.7 | -26.9 |
February | 0.217552E+10 | 21405.67 | 25-FEB-04:01 | -27.5 | -27.7 | 0.00 | 0.00 | 01-FEB-00:10 | -27.5 | -27.7 |
March | 0.420558E+10 | 18045.35 | 16-MAR-03:01 | -25.8 | -25.9 | 0.00 | 0.00 | 01-MAR-00:10 | -25.8 | -25.9 |
April | 0.650924E+10 | 10685.43 | 05-APR-04:01 | -12.4 | -13.3 | 0.00 | 0.00 | 01-APR-00:10 | -12.4 | -13.3 |
May | 0.882190E+10 | 12490.47 | 30-MAY-04:18 | 10.60 | 8.25 | 0.00 | 0.00 | 01-MAY-00:10 | 10.60 | 8.25 |
June | 0.104095E+11 | 10456.81 | 17-JUN-04:18 | 4.60 | 4.37 | 0.00 | 0.00 | 01-JUN-00:10 | 4.60 | 4.37 |
July | 0.118024E+11 | 11549.53 | 21-JUL-05:02 | 17.98 | 17.55 | 0.00 | 0.00 | 01-JUL-00:10 | 17.98 | 17.55 |
August | 0.118374E+11 | 11527.12 | 28-AUG-05:12 | 13.90 | 13.22 | 0.00 | 0.00 | 01-AUG-00:10 | 13.90 | 13.22 |
September | 0.827186E+10 | 11455.01 | 05-SEP-04:18 | 6.33 | 5.88 | 0.00 | 0.00 | 01-SEP-00:10 | 6.33 | 5.88 |
October | 0.647824E+10 | 13716.85 | 30-OCT-04:01 | -10.0 | -10.7 | 0.00 | 0.00 | 01-OCT-00:10 | -10.0 | -10.7 |
November | 0.426891E+10 | 14671.40 | 24-NOV-05:01 | -10.6 | -11.2 | 0.00 | 0.00 | 01-NOV-00:10 | -10.6 | -11.2 |
December | 0.291628E+10 | 20186.10 | 02-DEC-04:01 | -26.8 | -27.0 | 0.00 | 0.00 | 01-DEC-00:10 | -26.8 | -27.0 |
Annual Sum or Average | 0.797739E+11 | 0.00 | ||||||||
Minimum of Months | 0.207712E+10 | 10456.81 | -27.5 | -27.7 | 0.00 | 0.00 | -27.5 | -27.7 | ||
Maximum of Months | 0.118374E+11 | 21405.67 | 17.98 | 17.55 | 0.00 | 0.00 | 17.98 | 17.55 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342120E+10 | 24436.17 | 28-JAN-04:01 | -26.7 | -26.9 | 0.00 | 0.00 | 01-JAN-00:10 | -26.7 | -26.9 |
February | 0.314566E+10 | 25684.29 | 11-FEB-04:01 | -17.1 | -17.6 | 0.00 | 0.00 | 01-FEB-00:10 | -17.1 | -17.6 |
March | 0.325487E+10 | 25859.63 | 05-MAR-01:51 | -24.4 | -24.7 | 0.00 | 0.00 | 01-MAR-00:10 | -24.4 | -24.7 |
April | 0.411811E+10 | 19404.89 | 03-APR-03:01 | -7.4 | -8.6 | 0.00 | 0.00 | 01-APR-00:10 | -7.4 | -8.6 |
May | 0.712217E+10 | 12345.90 | 30-MAY-05:06 | 10.60 | 8.25 | 0.00 | 0.00 | 01-MAY-00:10 | 10.60 | 8.25 |
June | 0.868818E+10 | 11351.84 | 17-JUN-04:18 | 4.60 | 4.37 | 0.00 | 0.00 | 01-JUN-00:10 | 4.60 | 4.37 |
July | 0.943745E+10 | 11372.41 | 08-JUL-05:05 | 11.70 | 10.47 | 0.00 | 0.00 | 01-JUL-00:10 | 11.70 | 10.47 |
August | 0.904890E+10 | 10702.46 | 25-AUG-05:06 | 7.88 | 7.62 | 0.00 | 0.00 | 01-AUG-00:10 | 7.88 | 7.62 |
September | 0.651007E+10 | 10982.66 | 02-SEP-05:10 | 13.80 | 10.55 | 0.00 | 0.00 | 01-SEP-00:10 | 13.80 | 10.55 |
October | 0.409396E+10 | 24636.66 | 30-OCT-03:01 | -9.5 | -10.3 | 0.00 | 0.00 | 01-OCT-00:10 | -9.5 | -10.3 |
November | 0.320356E+10 | 22171.43 | 23-NOV-18:41 | -9.4 | -10.3 | 0.00 | 0.00 | 01-NOV-00:10 | -9.4 | -10.3 |
December | 0.329928E+10 | 25928.33 | 02-DEC-02:61 | -25.4 | -25.6 | 0.00 | 0.00 | 01-DEC-00:10 | -25.4 | -25.6 |
Annual Sum or Average | 0.653434E+11 | 0.00 | ||||||||
Minimum of Months | 0.314566E+10 | 10702.46 | -26.7 | -26.9 | 0.00 | 0.00 | -26.7 | -26.9 | ||
Maximum of Months | 0.943745E+10 | 25928.33 | 13.80 | 10.55 | 0.00 | 0.00 | 13.80 | 10.55 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 92200463.97 | 3357.79 | 08-FEB-14:21 | 5.00 | -0.5 | 0.00 | 0.00 | 01-FEB-00:10 | 5.00 | -0.5 |
March | 0.112330E+10 | 9664.56 | 26-MAR-13:14 | 8.50 | 4.25 | 0.00 | 0.00 | 01-MAR-00:10 | 8.50 | 4.25 |
April | 0.536584E+10 | 19424.81 | 13-APR-14:30 | 19.45 | 7.77 | 0.00 | 0.00 | 01-APR-00:10 | 19.45 | 7.77 |
May | 0.137393E+11 | 32990.60 | 18-MAY-14:00 | 28.50 | 16.75 | 0.00 | 0.00 | 01-MAY-00:10 | 28.50 | 16.75 |
June | 0.181875E+11 | 37249.27 | 30-JUN-14:00 | 31.10 | 23.76 | 0.00 | 0.00 | 01-JUN-00:10 | 31.10 | 23.76 |
July | 0.203311E+11 | 33978.59 | 24-JUL-14:00 | 29.40 | 19.87 | 0.00 | 0.00 | 01-JUL-00:10 | 29.40 | 19.87 |
August | 0.158322E+11 | 31787.91 | 08-AUG-14:05 | 30.10 | 22.94 | 0.00 | 0.00 | 01-AUG-00:10 | 30.10 | 22.94 |
September | 0.761586E+10 | 27153.83 | 01-SEP-14:05 | 25.68 | 18.06 | 0.00 | 0.00 | 01-SEP-00:10 | 25.68 | 18.06 |
October | 0.205799E+10 | 14651.49 | 22-OCT-13:14 | 18.67 | 12.99 | 0.00 | 0.00 | 01-OCT-00:10 | 18.67 | 12.99 |
November | 0.179133E+09 | 6021.82 | 01-NOV-16:10 | 17.62 | 13.19 | 0.00 | 0.00 | 01-NOV-00:10 | 17.62 | 13.19 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.845244E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -21.9 | -22.1 | 0.00 | 0.00 | -21.9 | -22.1 | ||
Maximum of Months | 0.203311E+11 | 37249.27 | 31.10 | 23.76 | 0.00 | 0.00 | 31.10 | 23.76 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100772E+10 | 5507.27 | 14-JAN-04:21 | -24.7 | -24.9 | 98547020.93 | 176.71 | 05-JAN-16:40 | -24.7 | -24.9 |
February | 0.575370E+10 | 10916.86 | 14-FEB-10:01 | -24.6 | -25.0 | 87851462.58 | 206.24 | 14-FEB-10:09 | -24.6 | -25.0 |
March | 0.126618E+11 | 12335.52 | 12-MAR-07:01 | -24.5 | -24.8 | 0.103297E+09 | 126.82 | 21-MAR-13:09 | 0.00 | -1.0 |
April | 0.182496E+11 | 9045.14 | 23-APR-18:12 | 24.83 | 15.88 | 91605076.43 | 126.82 | 19-APR-09:09 | 24.83 | 15.88 |
May | 0.448249E+10 | 3161.67 | 31-MAY-23:51 | 11.20 | 9.10 | 99233940.42 | 126.83 | 26-MAY-13:09 | 11.20 | 9.10 |
June | 0.932025E+10 | 5370.32 | 30-JUN-23:02 | 17.35 | 13.59 | 98958841.39 | 126.83 | 30-JUN-09:09 | 17.35 | 13.59 |
July | 0.149938E+11 | 7253.20 | 31-JUL-24:00 | 17.00 | 15.17 | 91881266.11 | 126.82 | 21-JUL-13:00 | 17.00 | 15.17 |
August | 0.198972E+11 | 8786.90 | 02-AUG-18:40 | 18.53 | 13.51 | 0.103239E+09 | 126.83 | 08-AUG-13:00 | 30.00 | 22.85 |
September | 0.407019E+10 | 3359.49 | 05-SEP-17:42 | 15.78 | 9.39 | 91605832.64 | 126.83 | 01-SEP-09:00 | 15.78 | 9.39 |
October | 0.835501E+10 | 4692.96 | 18-OCT-16:43 | 15.28 | 10.42 | 95230031.06 | 126.82 | 02-OCT-13:00 | 15.28 | 10.42 |
November | 0.123790E+11 | 6317.80 | 09-NOV-16:02 | 0.82 | -3.8 | 94300291.49 | 126.82 | 21-NOV-10:00 | 12.80 | 12.80 |
December | 0.148818E+11 | 12262.37 | 20-DEC-11:12 | -24.3 | -24.6 | 96701623.21 | 232.27 | 19-DEC-10:09 | -24.3 | -24.6 |
Annual Sum or Average | 0.126053E+12 | 0.115245E+10 | ||||||||
Minimum of Months | 0.100772E+10 | 3161.67 | -24.7 | -25.0 | 87851462.58 | 126.82 | -24.7 | -25.0 | ||
Maximum of Months | 0.198972E+11 | 12335.52 | 24.83 | 15.88 | 0.103297E+09 | 232.27 | 30.00 | 22.85 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.403631E+09 | 2700.74 | 06-JAN-12:42 | -24.8 | -25.1 | 96236506.01 | 167.09 | 05-JAN-16:40 | -24.8 | -25.1 |
February | 0.397274E+10 | 10481.51 | 17-FEB-09:21 | -24.8 | -25.1 | 87467092.42 | 186.58 | 14-FEB-10:09 | -24.8 | -25.1 |
March | 0.107694E+11 | 10822.46 | 12-MAR-07:01 | -24.5 | -24.8 | 0.103289E+09 | 126.82 | 21-MAR-13:09 | 0.00 | -1.0 |
April | 0.164323E+11 | 8680.33 | 21-APR-18:15 | 10.53 | 2.25 | 91605079.83 | 126.82 | 19-APR-09:09 | 10.53 | 2.25 |
May | 0.371644E+10 | 3001.86 | 14-MAY-18:41 | 18.17 | 8.43 | 99233975.28 | 126.83 | 26-MAY-13:09 | 23.17 | 17.97 |
June | 0.857783E+10 | 5259.91 | 30-JUN-23:22 | 16.85 | 13.54 | 98958967.92 | 126.83 | 19-JUN-13:00 | 16.85 | 13.54 |
July | 0.140378E+11 | 6844.29 | 31-JUL-24:00 | 17.00 | 15.17 | 91881364.63 | 126.82 | 03-JUL-09:09 | 17.00 | 15.17 |
August | 0.185573E+11 | 8501.21 | 02-AUG-18:40 | 18.53 | 13.51 | 0.103240E+09 | 126.83 | 08-AUG-13:09 | 29.50 | 22.73 |
September | 0.308191E+10 | 3254.22 | 05-SEP-17:42 | 15.78 | 9.39 | 91605826.12 | 126.83 | 01-SEP-09:00 | 15.78 | 9.39 |
October | 0.683608E+10 | 4514.79 | 18-OCT-16:43 | 15.28 | 10.42 | 95230031.51 | 126.82 | 02-OCT-13:00 | 15.28 | 10.42 |
November | 0.987621E+10 | 5854.04 | 09-NOV-16:12 | 0.53 | -4.0 | 94300294.36 | 126.82 | 21-NOV-10:00 | 12.80 | 12.80 |
December | 0.124148E+11 | 11581.93 | 26-DEC-09:41 | -24.6 | -24.9 | 96700593.72 | 232.27 | 19-DEC-10:09 | -24.6 | -24.9 |
Annual Sum or Average | 0.108677E+12 | 0.114975E+10 | ||||||||
Minimum of Months | 0.403631E+09 | 2700.74 | -24.8 | -25.1 | 87467092.42 | 126.82 | -24.8 | -25.1 | ||
Maximum of Months | 0.185573E+11 | 11581.93 | 18.53 | 15.17 | 0.103289E+09 | 232.27 | 29.50 | 22.73 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150970E+09 | 1607.57 | 25-JAN-16:25 | -18.4 | -19.1 | 92207372.89 | 151.03 | 05-JAN-16:40 | -18.4 | -19.1 |
February | 0.243321E+10 | 10457.40 | 14-FEB-10:01 | -24.6 | -25.0 | 86973451.19 | 166.01 | 14-FEB-10:09 | -24.6 | -25.0 |
March | 0.852789E+10 | 10149.40 | 12-MAR-07:01 | -24.5 | -24.8 | 0.103263E+09 | 126.82 | 21-MAR-13:09 | 0.00 | -1.0 |
April | 0.145632E+11 | 8622.71 | 21-APR-18:02 | 10.82 | 2.42 | 91605082.33 | 126.82 | 19-APR-09:09 | 10.82 | 2.42 |
May | 0.286419E+10 | 3129.25 | 25-MAY-18:50 | 27.57 | 18.64 | 99236306.56 | 126.83 | 26-MAY-13:09 | 23.17 | 17.97 |
June | 0.802555E+10 | 5174.69 | 30-JUN-23:02 | 17.35 | 13.59 | 98958972.68 | 126.83 | 19-JUN-13:00 | 17.35 | 13.59 |
July | 0.136269E+11 | 6602.49 | 31-JUL-23:50 | 16.95 | 15.06 | 91881530.08 | 126.82 | 03-JUL-09:09 | 16.95 | 15.06 |
August | 0.179893E+11 | 8560.75 | 02-AUG-18:40 | 18.53 | 13.51 | 0.103239E+09 | 126.83 | 31-AUG-13:00 | 27.20 | 22.12 |
September | 0.193237E+10 | 3225.84 | 05-SEP-17:42 | 15.78 | 9.39 | 91606605.13 | 126.83 | 01-SEP-13:09 | 15.78 | 9.39 |
October | 0.459824E+10 | 4466.10 | 18-OCT-16:43 | 15.28 | 10.42 | 95230033.11 | 126.82 | 02-OCT-13:00 | 15.28 | 10.42 |
November | 0.746767E+10 | 5534.85 | 09-NOV-16:12 | 0.53 | -4.0 | 94300298.32 | 126.82 | 21-NOV-10:00 | 12.80 | 12.80 |
December | 0.104784E+11 | 11696.47 | 26-DEC-09:41 | -24.6 | -24.9 | 96654774.07 | 232.27 | 19-DEC-10:09 | -24.6 | -24.9 |
Annual Sum or Average | 0.926579E+11 | 0.114516E+10 | ||||||||
Minimum of Months | 0.150970E+09 | 1607.57 | -24.6 | -25.0 | 86973451.19 | 126.82 | -24.6 | -25.0 | ||
Maximum of Months | 0.179893E+11 | 11696.47 | 27.57 | 18.64 | 0.103263E+09 | 232.27 | 27.20 | 22.12 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229974E+12 | 96350.12 | 12-JAN-15:01 | -18.9 | -19.7 | 0.208445E+10 | 2793.30 | 27-JAN-14:00 | -14.4 | -15.6 |
February | 0.436233E+12 | 489288.91 | 01-FEB-00:12 | -23.0 | -23.4 | 0.155017E+10 | 2647.20 | 08-FEB-14:00 | 5.00 | -0.5 |
March | 0.721456E+12 | 525268.20 | 31-MAR-15:52 | 8.90 | 3.77 | 0.184759E+10 | 2326.28 | 23-MAR-13:30 | 8.90 | 3.77 |
April | 0.946541E+12 | 495373.02 | 26-APR-11:54 | 0.00 | -0.3 | 0.159487E+10 | 2851.55 | 18-APR-13:09 | 0.00 | -0.3 |
May | 0.240085E+12 | 478066.61 | 31-MAY-23:09 | 10.37 | 8.33 | 0.216235E+10 | 2864.06 | 03-MAY-13:09 | 10.37 | 8.33 |
June | 0.474137E+12 | 488108.90 | 17-JUN-00:22 | 6.40 | 6.02 | 0.198986E+10 | 2834.45 | 16-JUN-13:00 | 6.40 | 6.02 |
July | 0.735923E+12 | 495741.12 | 07-JUL-23:42 | 7.98 | 7.67 | 0.194071E+10 | 2875.05 | 05-JUL-10:00 | 7.98 | 7.67 |
August | 0.983492E+12 | 492282.96 | 25-AUG-05:37 | 8.13 | 8.03 | 0.210757E+10 | 2764.39 | 31-AUG-13:09 | 25.37 | 21.98 |
September | 0.236043E+12 | 468375.25 | 30-SEP-23:56 | 7.80 | 6.76 | 0.198939E+10 | 2810.55 | 08-SEP-13:09 | 7.80 | 6.76 |
October | 0.491410E+12 | 511611.61 | 31-OCT-23:53 | 3.30 | -0.4 | 0.174817E+10 | 2745.22 | 02-OCT-09:30 | 3.30 | -0.4 |
November | 0.703777E+12 | 517248.59 | 01-NOV-00:52 | 5.10 | 3.87 | 0.171732E+10 | 2744.00 | 02-NOV-09:00 | 2.80 | 2.54 |
December | 0.977817E+12 | 488110.99 | 21-DEC-10:23 | -24.8 | -25.1 | 0.160988E+10 | 2711.27 | 21-DEC-10:39 | -24.3 | -24.7 |
Annual Sum or Average | 0.717689E+13 | 0.223423E+11 | ||||||||
Minimum of Months | 0.229974E+12 | 96350.12 | -24.8 | -25.1 | 0.155017E+10 | 2326.28 | -24.3 | -24.7 | ||
Maximum of Months | 0.983492E+12 | 525268.20 | 10.37 | 8.33 | 0.216235E+10 | 2875.05 | 25.37 | 21.98 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163002E+09 | 95205.80 | 06-JAN-07:10 | -35.0 |
February | 77672184.75 | 2922.76 | 09-FEB-06:03 | -3.2 |
March | 41678466.66 | 2870.36 | 02-MAR-06:03 | -8.3 |
April | 74068220.60 | 3131.61 | 15-APR-05:12 | 5.60 |
May | 56046802.08 | 3176.96 | 10-MAY-05:45 | 4.25 |
June | 82379236.38 | 8700.55 | 24-JUN-16:01 | 28.98 |
July | 0.102500E+09 | 10812.43 | 29-JUL-16:01 | 30.50 |
August | 38752374.39 | 5202.14 | 26-AUG-16:02 | 26.60 |
September | 46369269.33 | 3029.12 | 29-SEP-05:05 | 7.20 |
October | 82483250.01 | 2649.47 | 14-OCT-05:03 | -0.2 |
November | 73838410.96 | 3046.31 | 13-NOV-06:11 | -8.5 |
December | 52887497.12 | 2883.35 | 08-DEC-06:04 | -21.0 |
Annual Sum or Average | 0.891677E+09 | |||
Minimum of Months | 38752374.39 | 2649.47 | -35.0 | |
Maximum of Months | 0.163002E+09 | 95205.80 | 30.50 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34772176.83 | 19864.72 | 02-JAN-05:01 | -18.2 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:03 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -8.8 |
Annual Sum or Average | 34772176.83 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 34772176.83 | 19864.72 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138935E+10 | 68233.01 | 02-JAN-04:01 | -18.8 |
February | 0.326617E+09 | 57052.14 | 27-FEB-05:01 | -17.4 |
March | 85613853.90 | 57344.12 | 06-MAR-05:01 | -18.4 |
April | 0.00 | 0.00 | 01-APR-00:03 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7.52 |
November | 0.216751E+09 | 60389.36 | 27-NOV-05:01 | -7.2 |
December | 0.751870E+09 | 61586.26 | 26-DEC-05:01 | -25.9 |
Annual Sum or Average | 0.277020E+10 | |||
Minimum of Months | 0.00 | 0.00 | -25.9 | |
Maximum of Months | 0.138935E+10 | 68233.01 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186107E+11 | 140106.84 | 09-JAN-04:01 | -32.4 |
February | 0.107774E+11 | 137293.29 | 13-FEB-03:51 | -22.8 |
March | 0.666236E+10 | 134016.49 | 06-MAR-04:01 | -17.4 |
April | 0.207291E+10 | 129930.82 | 03-APR-03:01 | -7.4 |
May | 0.176001E+09 | 110654.80 | 01-MAY-05:01 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 2521380.32 | 37820.70 | 19-AUG-05:01 | 4.60 |
September | 17522173.99 | 83968.23 | 23-SEP-05:01 | 4.90 |
October | 0.200555E+10 | 134897.42 | 30-OCT-03:11 | -9.6 |
November | 0.682918E+10 | 136288.02 | 13-NOV-04:01 | -8.2 |
December | 0.155902E+11 | 139589.65 | 25-DEC-04:41 | -29.9 |
Annual Sum or Average | 0.627444E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.4 | |
Maximum of Months | 0.186107E+11 | 140106.84 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.858107E+10 | 24999.64 | 09-JAN-03:11 | -32.2 |
February | 0.392864E+10 | 24618.50 | 13-FEB-04:01 | -22.9 |
March | 0.163326E+10 | 23502.09 | 06-MAR-04:01 | -17.4 |
April | 0.105737E+09 | 20379.79 | 05-APR-04:01 | -12.4 |
May | 14946.07 | 199.28 | 01-MAY-05:01 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 19.75 |
October | 43219250.65 | 20887.96 | 30-OCT-04:01 | -10.0 |
November | 0.708081E+09 | 21943.48 | 25-NOV-05:21 | -19.1 |
December | 0.545619E+10 | 25491.40 | 24-DEC-08:11 | -31.1 |
Annual Sum or Average | 0.204562E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.2 | |
Maximum of Months | 0.858107E+10 | 25491.40 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.517159E+10 | 23877.24 | 09-JAN-03:11 | -32.2 |
February | 0.228825E+10 | 23462.05 | 13-FEB-04:01 | -22.9 |
March | 0.106506E+10 | 22188.44 | 06-MAR-04:01 | -17.4 |
April | 90710705.25 | 18835.03 | 05-APR-04:01 | -12.4 |
May | 279612.31 | 3728.16 | 01-MAY-05:01 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 108058.39 | 1620.88 | 19-AUG-05:03 | 4.60 |
September | 532047.60 | 1990.19 | 06-SEP-05:02 | 1.28 |
October | 52368532.51 | 19714.41 | 30-OCT-04:01 | -10.0 |
November | 0.582608E+09 | 20456.54 | 25-NOV-05:21 | -19.1 |
December | 0.374604E+10 | 24593.59 | 25-DEC-04:51 | -29.8 |
Annual Sum or Average | 0.129976E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.2 | |
Maximum of Months | 0.517159E+10 | 24593.59 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.666056E+10 | 33759.69 | 09-JAN-03:11 | -32.2 |
February | 0.326536E+10 | 33749.97 | 13-FEB-04:01 | -22.9 |
March | 0.172848E+10 | 32879.49 | 05-MAR-06:31 | -28.3 |
April | 0.254288E+09 | 27488.91 | 05-APR-04:01 | -12.4 |
May | 7718219.53 | 20464.26 | 01-MAY-05:01 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 177900.53 | 2668.51 | 19-AUG-05:03 | 4.60 |
September | 948220.55 | 7052.79 | 13-SEP-05:01 | 3.98 |
October | 0.165693E+09 | 28681.07 | 30-OCT-04:01 | -10.0 |
November | 0.103339E+10 | 30668.45 | 25-NOV-04:01 | -18.0 |
December | 0.485675E+10 | 34454.75 | 24-DEC-08:11 | -31.1 |
Annual Sum or Average | 0.179734E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.2 | |
Maximum of Months | 0.666056E+10 | 34454.75 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.287407E+10 | 23329.37 | 02-JAN-04:01 | -18.8 |
February | 0.107869E+10 | 22765.07 | 13-FEB-04:01 | -22.9 |
March | 0.266539E+09 | 20406.50 | 06-MAR-05:01 | -18.4 |
April | 6563554.01 | 16324.70 | 04-APR-05:01 | -9.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 19.75 |
October | 12487598.87 | 18720.53 | 30-OCT-04:01 | -10.0 |
November | 0.118628E+09 | 20071.35 | 25-NOV-05:01 | -19.0 |
December | 0.754417E+09 | 22234.46 | 26-DEC-04:01 | -25.0 |
Annual Sum or Average | 0.511139E+10 | |||
Minimum of Months | 0.00 | 0.00 | -25.0 | |
Maximum of Months | 0.287407E+10 | 23329.37 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171819E+11 | 36344.35 | 04-JAN-04:11 | -28.0 |
February | 0.104920E+11 | 36696.74 | 12-FEB-23:01 | -17.4 |
March | 0.586123E+10 | 34862.71 | 06-MAR-04:11 | -17.6 |
April | 0.123837E+10 | 31480.37 | 03-APR-03:01 | -7.4 |
May | 53798185.58 | 25314.12 | 01-MAY-05:01 | -3.4 |
June | 123927.41 | 2065.46 | 10-JUN-05:03 | 14.60 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 404116.67 | 3136.16 | 19-AUG-05:01 | 4.60 |
September | 44078755.29 | 18514.35 | 23-SEP-05:01 | 4.90 |
October | 0.821766E+09 | 31072.39 | 30-OCT-03:01 | -9.5 |
November | 0.496333E+10 | 34018.73 | 25-NOV-04:11 | -18.2 |
December | 0.153639E+11 | 36740.57 | 24-DEC-09:21 | -30.5 |
Annual Sum or Average | 0.560209E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.5 | |
Maximum of Months | 0.171819E+11 | 36740.57 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.983614E+10 | 30421.20 | 04-JAN-04:11 | -28.0 |
February | 0.555157E+10 | 30860.93 | 12-FEB-23:01 | -17.4 |
March | 0.296273E+10 | 29145.72 | 06-MAR-04:11 | -17.6 |
April | 0.592050E+09 | 25655.55 | 03-APR-03:01 | -7.4 |
May | 20106641.76 | 16015.02 | 01-MAY-05:01 | -3.4 |
June | 44636.46 | 743.94 | 10-JUN-05:02 | 14.60 |
July | 37323.76 | 622.06 | 08-JUL-05:04 | 11.70 |
August | 560138.74 | 4008.04 | 19-AUG-05:01 | 4.60 |
September | 24734026.20 | 13505.35 | 23-SEP-05:01 | 4.90 |
October | 0.509130E+09 | 25687.22 | 30-OCT-03:01 | -9.5 |
November | 0.298986E+10 | 28503.33 | 25-NOV-04:11 | -18.2 |
December | 0.910402E+10 | 30851.69 | 24-DEC-08:61 | -31.1 |
Annual Sum or Average | 0.315910E+11 | |||
Minimum of Months | 37323.76 | 622.06 | -31.1 | |
Maximum of Months | 0.983614E+10 | 30860.93 | 14.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111860E+11 | 38902.42 | 04-JAN-04:11 | -28.0 |
February | 0.623709E+10 | 39468.21 | 12-FEB-23:01 | -17.4 |
March | 0.359566E+10 | 37062.73 | 06-MAR-04:11 | -17.6 |
April | 0.881836E+09 | 32314.76 | 03-APR-03:01 | -7.4 |
May | 43636146.89 | 26081.33 | 01-MAY-05:01 | -3.4 |
June | 96007.06 | 1600.12 | 10-JUN-05:03 | 14.60 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 148047.64 | 1507.96 | 18-AUG-05:04 | 11.60 |
September | 28863551.12 | 18966.47 | 20-SEP-05:01 | 5.60 |
October | 0.603129E+09 | 33219.65 | 30-OCT-03:01 | -9.5 |
November | 0.351297E+10 | 36394.78 | 27-NOV-00:01 | -6.7 |
December | 0.104969E+11 | 39225.22 | 24-DEC-08:61 | -31.1 |
Annual Sum or Average | 0.365864E+11 | |||
Minimum of Months | 0.00 | 0.00 | -31.1 | |
Maximum of Months | 0.111860E+11 | 39468.21 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.911194E+10 | 31492.00 | 04-JAN-04:11 | -28.0 |
February | 0.505136E+10 | 32157.68 | 12-FEB-23:01 | -17.4 |
March | 0.258814E+10 | 29788.90 | 06-MAR-04:11 | -17.6 |
April | 0.506494E+09 | 24112.98 | 04-APR-04:21 | -8.1 |
May | 20201115.87 | 16640.92 | 01-MAY-05:01 | -3.4 |
June | 97877.08 | 819.41 | 03-JUN-05:04 | 7.30 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 66186.51 | 882.49 | 18-AUG-05:04 | 11.60 |
September | 17450383.13 | 13526.30 | 20-SEP-05:01 | 5.60 |
October | 0.396106E+09 | 25832.07 | 30-OCT-03:01 | -9.5 |
November | 0.244957E+10 | 29160.09 | 23-NOV-22:01 | -10.7 |
December | 0.759817E+10 | 31051.94 | 24-DEC-08:41 | -31.1 |
Annual Sum or Average | 0.277396E+11 | |||
Minimum of Months | 0.00 | 0.00 | -31.1 | |
Maximum of Months | 0.911194E+10 | 32157.68 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259933E+11 | 49965.14 | 09-JAN-04:01 | -32.4 |
February | 0.182136E+11 | 50426.42 | 12-FEB-23:11 | -17.6 |
March | 0.122111E+11 | 48045.54 | 06-MAR-03:51 | -17.2 |
April | 0.426631E+10 | 42875.52 | 05-APR-03:11 | -12.2 |
May | 0.561562E+09 | 36234.59 | 01-MAY-05:01 | -3.4 |
June | 8190734.25 | 24854.05 | 10-JUN-05:01 | 14.60 |
July | 2791794.03 | 12100.66 | 10-JUL-05:01 | 9.68 |
August | 39467626.79 | 26022.98 | 19-AUG-05:01 | 4.60 |
September | 0.704589E+09 | 29762.67 | 28-SEP-04:11 | 6.30 |
October | 0.378055E+10 | 45130.84 | 30-OCT-03:11 | -9.6 |
November | 0.113736E+11 | 47107.84 | 23-NOV-22:01 | -10.7 |
December | 0.247485E+11 | 50958.33 | 24-DEC-08:41 | -31.1 |
Annual Sum or Average | 0.101904E+12 | |||
Minimum of Months | 2791794.03 | 12100.66 | -32.4 | |
Maximum of Months | 0.259933E+11 | 50958.33 | 14.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.156043E+11 | 34157.20 | 09-JAN-04:01 | -32.4 |
February | 0.102026E+11 | 34411.39 | 13-FEB-03:51 | -22.8 |
March | 0.647874E+10 | 32789.34 | 06-MAR-03:51 | -17.2 |
April | 0.214271E+10 | 29301.07 | 05-APR-03:11 | -12.2 |
May | 0.241757E+09 | 24089.77 | 01-MAY-05:01 | -3.4 |
June | 3685133.59 | 16724.60 | 10-JUN-05:01 | 14.60 |
July | 1892237.43 | 9293.27 | 10-JUL-04:11 | 8.33 |
August | 19162536.54 | 17395.10 | 19-AUG-05:01 | 4.60 |
September | 0.369479E+09 | 20141.73 | 28-SEP-04:11 | 6.30 |
October | 0.221939E+10 | 30913.11 | 30-OCT-03:11 | -9.6 |
November | 0.687389E+10 | 32109.41 | 23-NOV-22:01 | -10.7 |
December | 0.152760E+11 | 34695.47 | 24-DEC-08:61 | -31.1 |
Annual Sum or Average | 0.594335E+11 | |||
Minimum of Months | 1892237.43 | 9293.27 | -32.4 | |
Maximum of Months | 0.156043E+11 | 34695.47 | 14.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188415E+11 | 50787.26 | 09-JAN-04:01 | -32.4 |
February | 0.123710E+11 | 50882.43 | 12-FEB-23:11 | -17.6 |
March | 0.847637E+10 | 48525.60 | 05-MAR-03:51 | -28.3 |
April | 0.333063E+10 | 43087.36 | 05-APR-03:11 | -12.2 |
May | 0.529329E+09 | 36466.79 | 01-MAY-05:01 | -3.4 |
June | 23382949.66 | 26197.71 | 03-JUN-05:01 | 7.30 |
July | 6854100.60 | 25259.28 | 10-JUL-05:01 | 9.68 |
August | 40638226.54 | 26434.37 | 19-AUG-05:01 | 4.60 |
September | 0.526109E+09 | 30232.52 | 28-SEP-04:11 | 6.30 |
October | 0.286157E+10 | 45910.92 | 30-OCT-03:11 | -9.6 |
November | 0.867919E+10 | 47662.87 | 23-NOV-22:01 | -10.7 |
December | 0.188032E+11 | 51286.99 | 24-DEC-08:61 | -31.1 |
Annual Sum or Average | 0.744897E+11 | |||
Minimum of Months | 6854100.60 | 25259.28 | -32.4 | |
Maximum of Months | 0.188415E+11 | 51286.99 | 9.68 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143324E+11 | 38433.74 | 09-JAN-04:01 | -32.4 |
February | 0.899098E+10 | 38565.60 | 13-FEB-03:51 | -22.8 |
March | 0.548884E+10 | 36557.73 | 06-MAR-03:51 | -17.2 |
April | 0.172158E+10 | 32360.59 | 05-APR-03:11 | -12.2 |
May | 0.219885E+09 | 25401.65 | 01-MAY-05:01 | -3.4 |
June | 3102268.10 | 14186.51 | 10-JUN-05:01 | 14.60 |
July | 241175.45 | 2025.31 | 18-JUL-05:03 | 8.27 |
August | 18296054.28 | 18381.45 | 19-AUG-05:01 | 4.60 |
September | 0.265270E+09 | 20642.55 | 28-SEP-04:11 | 6.30 |
October | 0.155016E+10 | 33991.45 | 30-OCT-03:11 | -9.6 |
November | 0.545180E+10 | 35751.84 | 25-NOV-01:51 | -15.6 |
December | 0.127778E+11 | 38427.26 | 24-DEC-08:41 | -31.1 |
Annual Sum or Average | 0.508204E+11 | |||
Minimum of Months | 241175.45 | 2025.31 | -32.4 | |
Maximum of Months | 0.143324E+11 | 38565.60 | 14.60 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267294E+10 | 15657.72 | 02-JAN-06:06 | -17.8 |
February | 0.720987E+09 | 16484.13 | 20-FEB-14:11 | 6.50 |
March | 0.210557E+09 | 21831.22 | 26-MAR-15:31 | 10.93 |
April | 50863038.69 | 20111.66 | 23-APR-15:11 | 25.97 |
May | 60043640.44 | 13935.09 | 21-MAY-15:01 | 22.73 |
June | 58209696.57 | 12098.07 | 25-JUN-11:21 | 27.25 |
July | 0.104302E+09 | 16538.51 | 23-JUL-15:31 | 30.00 |
August | 99302243.00 | 18305.71 | 20-AUG-14:51 | 25.60 |
September | 59791826.09 | 16677.49 | 03-SEP-15:41 | 21.70 |
October | 41632908.87 | 14497.68 | 22-OCT-15:11 | 19.23 |
November | 53738559.74 | 10237.13 | 21-NOV-06:01 | 10.10 |
December | 0.101911E+10 | 8515.81 | 26-DEC-11:52 | -20.6 |
Annual Sum or Average | 0.515148E+10 | |||
Minimum of Months | 41632908.87 | 8515.81 | -20.6 | |
Maximum of Months | 0.267294E+10 | 21831.22 | 30.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.746960E+10 | 28073.40 | 02-JAN-06:12 | -17.8 |
February | 0.381378E+10 | 22296.49 | 20-FEB-15:01 | 8.40 |
March | 0.184916E+10 | 23203.69 | 26-MAR-16:21 | 10.55 |
April | 0.371073E+09 | 22414.23 | 23-APR-15:41 | 26.52 |
May | 52912107.39 | 15417.50 | 14-MAY-15:11 | 20.00 |
June | 49387965.78 | 14663.62 | 25-JUN-11:31 | 27.07 |
July | 67654324.48 | 17294.59 | 23-JUL-16:11 | 29.43 |
August | 62183481.01 | 14670.18 | 20-AUG-15:12 | 25.20 |
September | 48509918.13 | 17292.90 | 03-SEP-15:52 | 21.70 |
October | 0.107589E+09 | 15232.91 | 22-OCT-13:12 | 18.67 |
November | 0.200413E+10 | 16713.60 | 27-NOV-06:05 | -7.1 |
December | 0.515430E+10 | 22614.13 | 26-DEC-06:06 | -26.7 |
Annual Sum or Average | 0.210503E+11 | |||
Minimum of Months | 48509918.13 | 14663.62 | -26.7 | |
Maximum of Months | 0.746960E+10 | 28073.40 | 29.43 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.489648E+11 | 76147.20 | 06-JAN-05:11 | -34.8 |
February | 0.336592E+11 | 71407.55 | 13-FEB-05:16 | -23.5 |
March | 0.244630E+11 | 63269.74 | 06-MAR-05:15 | -18.5 |
April | 0.988718E+10 | 48996.85 | 03-APR-04:22 | -5.0 |
May | 0.214791E+10 | 30402.50 | 01-MAY-05:01 | -3.4 |
June | 0.442303E+09 | 40904.01 | 28-JUN-05:01 | 15.15 |
July | 0.323036E+09 | 38615.43 | 01-JUL-05:01 | 9.78 |
August | 0.484033E+09 | 30662.32 | 24-AUG-05:01 | 14.90 |
September | 0.263289E+10 | 20822.37 | 23-SEP-05:01 | 4.90 |
October | 0.100092E+11 | 48851.78 | 30-OCT-05:01 | -9.9 |
November | 0.236573E+11 | 54438.55 | 29-NOV-05:13 | -19.8 |
December | 0.459725E+11 | 71008.34 | 20-DEC-05:11 | -28.8 |
Annual Sum or Average | 0.202643E+12 | |||
Minimum of Months | 0.323036E+09 | 20822.37 | -34.8 | |
Maximum of Months | 0.489648E+11 | 76147.20 | 15.15 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.737674E+09 | 1910.66 | 14-JAN-04:22 | -24.7 |
February | 0.177483E+09 | 1663.50 | 13-FEB-22:32 | -25.5 |
March | 51992957.87 | 1910.06 | 16-MAR-02:32 | -25.2 |
April | 0.00 | 0.00 | 01-APR-00:03 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 3.60 |
December | 0.374277E+09 | 2082.82 | 02-DEC-01:52 | -25.2 |
Annual Sum or Average | 0.134143E+10 | |||
Minimum of Months | 0.00 | 0.00 | -25.5 | |
Maximum of Months | 0.737674E+09 | 2082.82 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171143E+10 | 1568.18 | 07-JAN-00:03 | -24.9 |
February | 0.171378E+09 | 1524.65 | 13-FEB-22:32 | -25.5 |
March | 50990823.30 | 1623.26 | 16-MAR-02:32 | -25.2 |
April | 0.00 | 0.00 | 01-APR-00:03 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 3.60 |
December | 0.361384E+09 | 1793.76 | 21-DEC-00:02 | -25.1 |
Annual Sum or Average | 0.229518E+10 | |||
Minimum of Months | 0.00 | 0.00 | -25.5 | |
Maximum of Months | 0.171143E+10 | 1793.76 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.228490E+10 | 1493.20 | 01-JAN-17:10 | -19.1 |
February | 0.563267E+09 | 1801.28 | 15-FEB-05:32 | -24.6 |
March | 53585821.34 | 2141.16 | 12-MAR-07:02 | -24.5 |
April | 1439621.47 | 538.40 | 30-APR-24:00 | 0.10 |
May | 0.118121E+09 | 1290.89 | 01-MAY-04:01 | -2.9 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.114768E+09 | 1029.71 | 11-SEP-04:12 | 12.40 |
October | 57915607.07 | 1182.86 | 15-OCT-06:41 | 1.10 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 3.60 |
December | 0.376947E+09 | 1676.78 | 21-DEC-00:02 | -25.1 |
Annual Sum or Average | 0.357095E+10 | |||
Minimum of Months | 0.00 | 0.00 | -25.1 | |
Maximum of Months | 0.228490E+10 | 2141.16 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 |
February | 0.120665E+10 | 19358.30 | 20-FEB-14:11 | 6.50 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:03 | 3.52 |
May | 202513.82 | 3296.84 | 31-MAY-23:10 | 10.37 |
June | 0.271751E+09 | 25809.75 | 11-JUN-06:01 | 11.10 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 44564.16 | 742.74 | 30-SEP-23:54 | 7.80 |
October | 0.355834E+09 | 26068.22 | 22-OCT-09:51 | 14.40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -8.8 |
Annual Sum or Average | 0.183448E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.9 | |
Maximum of Months | 0.120665E+10 | 26068.22 | 17.07 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.278508E+11 | 29144.79 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.252627E+11 | 29144.79 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.300191E+11 | 29144.79 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.268132E+11 | 29144.79 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.289349E+11 | 29144.79 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.287951E+11 | 29144.79 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.269531E+11 | 29144.79 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.300191E+11 | 29144.79 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.268132E+11 | 29144.79 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.278508E+11 | 29144.79 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.275243E+11 | 29144.79 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.269531E+11 | 29144.79 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.333789E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.252627E+11 | 29144.79 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.300191E+11 | 29144.79 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.785272E+10 | 8217.58 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.712300E+10 | 8217.58 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.846411E+10 | 8217.58 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.756018E+10 | 8217.58 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.815842E+10 | 8217.58 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.811897E+10 | 8217.58 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.759962E+10 | 8217.58 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.846411E+10 | 8217.58 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.756018E+10 | 8217.58 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.785272E+10 | 8217.58 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.776069E+10 | 8217.58 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.759962E+10 | 8217.58 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.941143E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.712300E+10 | 8217.58 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.846411E+10 | 8217.58 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.289349E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.287951E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.275243E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.333789E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159582E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138739E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959231E+09 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1777899.15 | 0.907969E+09 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2793980.87 | 0.428035E+09 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13041449.53 | 0.231004E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14344668.10 | 0.163323E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4656538.16 | 0.232527E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140595.19 | 0.405316E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636312E+09 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113723E+10 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171110E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36755131.00 | 0.979525E+10 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163323E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14344668.10 | 0.171110E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106022E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.926562E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640913E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2175164.99 | 0.602461E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2076352.63 | 0.282210E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10183609.20 | 0.148808E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11247919.94 | 98332790.00 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3606272.47 | 0.144963E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107244.17 | 0.263805E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419007E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750630E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113281E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29396563.40 | 0.647072E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98332790.00 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11247919.94 | 0.113281E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160059E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141577E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976538E+09 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 444960.72 | 0.911250E+09 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2844378.41 | 0.420142E+09 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13359070.76 | 0.218247E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14254883.09 | 0.154290E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4380276.10 | 0.230316E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140227.21 | 0.410494E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634998E+09 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112686E+10 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171465E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35423796.29 | 0.981415E+10 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154290E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14254883.09 | 0.171465E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108977E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.965440E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674327E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 449.47 | 0.658279E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1876897.88 | 0.304376E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9163636.36 | 0.165148E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9026701.96 | 0.125135E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2962000.04 | 0.179099E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97227.47 | 0.284165E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443447E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.793282E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119142E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23126913.17 | 0.687389E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125135E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9163636.36 | 0.119142E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364246E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310511E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212260E+10 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9023737.55 | 0.189268E+10 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6467303.51 | 0.907997E+09 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33920248.65 | 0.481769E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37715604.66 | 0.346638E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15576219.37 | 0.458478E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 415458.86 | 0.826956E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132111E+10 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242167E+10 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386728E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103119E+09 | 0.213948E+11 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346638E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37715604.66 | 0.386728E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242129E+10 |
February | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207880E+10 |
March | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144043E+10 |
April | 0.688021E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5954411.21 | 0.132043E+10 |
May | 0.744847E+09 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4474547.85 | 0.635763E+09 |
June | 0.742030E+09 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20349589.17 | 0.334738E+09 |
July | 0.690839E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23313860.96 | 0.233117E+09 |
August | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8033114.44 | 0.330909E+09 |
September | 0.688021E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 220929.06 | 0.581166E+09 |
October | 0.715730E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904485E+09 |
November | 0.708685E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162412E+10 |
December | 0.690839E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257200E+10 |
Annual Sum or Average | 0.858171E+10 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62346452.70 | 0.144772E+11 |
Minimum of Months | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233117E+09 |
Maximum of Months | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23313860.96 | 0.257200E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368346E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323214E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223765E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 356528.41 | 0.204335E+10 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6334379.38 | 0.956802E+09 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28079160.79 | 0.488600E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31435626.76 | 0.359155E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9887136.51 | 0.518352E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 298815.97 | 0.933617E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142745E+10 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250881E+10 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391634E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76391647.82 | 0.223057E+11 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359155E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31435626.76 | 0.391634E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243722E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210513E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146272E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 121718.52 | 0.134184E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4493400.72 | 0.655887E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22383186.04 | 0.339263E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23279807.03 | 0.260511E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9222806.15 | 0.344600E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 426394.22 | 0.589811E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918377E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163885E+10 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259223E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59927312.68 | 0.146864E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260511E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23279807.03 | 0.259223E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450857E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382717E+10 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256465E+10 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15760303.95 | 0.218381E+10 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9503940.91 | 0.102067E+10 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47140834.90 | 0.532644E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51828490.63 | 0.384695E+09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24681664.74 | 0.498246E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1992716.36 | 0.910392E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3779.28 | 0.148716E+10 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291508E+10 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477798E+10 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150912E+09 | 0.256111E+11 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384695E+09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51828490.63 | 0.477798E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300599E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255527E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172789E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8434458.38 | 0.152380E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5382548.89 | 0.733912E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23784206.53 | 0.388051E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27693586.85 | 0.274688E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9572829.08 | 0.380377E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 255502.21 | 0.651895E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101473E+10 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194451E+10 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318566E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75123131.95 | 0.173868E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274688E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27693586.85 | 0.318566E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453573E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392272E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267079E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1523755.38 | 0.235339E+10 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7698628.29 | 0.108813E+10 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37048177.48 | 0.551138E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40653459.97 | 0.407807E+09 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12117301.65 | 0.579979E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 339415.10 | 0.105260E+10 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160599E+10 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296758E+10 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480719E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99380737.89 | 0.265430E+11 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407807E+09 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40653459.97 | 0.480719E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301267E+10 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257963E+10 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176221E+10 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 558205.90 | 0.156508E+10 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5362755.31 | 0.769112E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27415684.53 | 0.399408E+09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28411014.61 | 0.309621E+09 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11446368.89 | 0.402521E+09 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 436832.65 | 0.682114E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105248E+10 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196484E+10 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319751E+10 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73630861.89 | 0.176972E+11 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309621E+09 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28411014.61 | 0.319751E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.785272E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.712300E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.846411E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.756018E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.815842E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.811897E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.759962E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.846411E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.756018E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.785272E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.776069E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.759962E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.941143E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.712300E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.846411E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344094E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306605E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211892E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1392895.89 | 0.202169E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3971023.80 | 0.933806E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21633571.56 | 0.501416E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23722001.34 | 0.358078E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6079133.57 | 0.518840E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143984.77 | 0.904669E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141866E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254095E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374982E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56942610.93 | 0.215738E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358078E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23722001.34 | 0.374982E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592094E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521863E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365620E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4877939.58 | 0.345087E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7263888.47 | 0.162740E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40595572.32 | 0.862605E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45340637.50 | 0.618774E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12558242.71 | 0.870791E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264600.98 | 0.155635E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242013E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424961E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638224E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110901E+09 | 0.368345E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618774E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45340637.50 | 0.638224E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634010E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546156E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376676E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2421258.21 | 0.339971E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3196752.36 | 0.164026E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32293237.36 | 0.867450E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27370023.35 | 0.633373E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6020337.13 | 0.868252E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9917.93 | 0.149976E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226869E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420778E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672075E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71311526.34 | 0.376745E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633373E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32293237.36 | 0.672075E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 29144.79 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 29144.79 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 29144.79 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 29144.79 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 29144.79 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 29144.79 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 29144.79 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 29144.79 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 29144.79 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 29144.79 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 29144.79 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 29144.79 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2932.15 | 04-JAN-05:57 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3331.93 | 12-FEB-22:51 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1775.50 | 15-MAR-04:51 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.48 | 23-APR-16:00 | 1453.91 | 09-APR-12:53 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.46 | 24-MAY-15:00 | 728.81 | 08-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.67 | 24-JUN-17:10 | 507.14 | 20-JUN-03:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.28 | 23-JUL-15:00 | 492.21 | 09-JUL-10:00 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.02 | 08-AUG-16:00 | 659.53 | 27-AUG-05:53 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.80 | 01-SEP-15:00 | 867.17 | 20-SEP-01:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 1144.91 | 31-OCT-21:01 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2056.00 | 22-NOV-01:51 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 2876.36 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.21 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 250.28 | 3331.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1954.82 | 04-JAN-05:59 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2221.31 | 12-FEB-22:51 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1183.37 | 15-MAR-04:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.18 | 23-APR-16:00 | 947.53 | 01-APR-18:55 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.61 | 24-MAY-18:00 | 554.37 | 14-MAY-08:10 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.18 | 24-JUN-17:10 | 341.28 | 18-JUN-07:00 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.30 | 23-JUL-15:00 | 324.53 | 09-JUL-09:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.29 | 20-AUG-14:20 | 423.12 | 27-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 | 01-SEP-15:00 | 562.42 | 20-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 762.74 | 31-OCT-21:01 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1338.33 | 22-NOV-01:51 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1915.45 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.53 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 225.18 | 2221.31 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2932.13 | 04-JAN-05:57 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3332.08 | 12-FEB-22:51 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1775.17 | 15-MAR-04:51 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.52 | 23-APR-18:00 | 1648.44 | 16-APR-12:10 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.46 | 24-MAY-15:00 | 725.68 | 29-MAY-17:55 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.33 | 24-JUN-17:10 | 485.50 | 20-JUN-03:51 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.99 | 23-JUL-14:57 | 452.22 | 09-JUL-10:00 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.02 | 08-AUG-16:00 | 643.90 | 27-AUG-05:53 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.74 | 01-SEP-15:00 | 837.12 | 20-SEP-01:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 1143.85 | 31-OCT-21:01 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1963.69 | 22-NOV-01:51 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 2873.10 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.22 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 235.99 | 3332.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1954.78 | 04-JAN-05:57 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2284.82 | 12-FEB-22:51 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1186.63 | 15-MAR-04:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.34 | 23-APR-15:54 | 1069.43 | 09-APR-12:53 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.31 | 24-MAY-15:00 | 510.18 | 29-MAY-17:55 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.11 | 18-JUN-12:30 | 367.92 | 20-JUN-03:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.05 | 15-JUL-17:30 | 404.39 | 16-JUL-16:50 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.35 | 08-AUG-16:00 | 520.77 | 27-AUG-05:53 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 | 01-SEP-15:00 | 598.70 | 20-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 770.84 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1431.25 | 22-NOV-01:51 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1924.06 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.92 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 158.05 | 2284.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6892.63 | 04-JAN-05:57 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 7752.37 | 12-FEB-22:51 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 4200.01 | 15-MAR-04:56 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 768.06 | 23-APR-15:50 | 3018.05 | 01-APR-18:32 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.06 | 24-MAY-15:00 | 1619.40 | 29-MAY-17:55 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 423.67 | 18-JUN-12:50 | 1046.72 | 20-JUN-03:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 767.16 | 23-JUL-15:00 | 1072.74 | 06-JUL-21:51 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.14 | 20-AUG-14:00 | 1335.96 | 27-AUG-05:53 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.64 | 24-SEP-15:00 | 1778.22 | 20-SEP-01:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2683.44 | 31-OCT-21:01 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 4193.66 | 21-NOV-22:01 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 6814.18 | 16-DEC-05:59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1046.72 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 768.06 | 7752.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4595.08 | 04-JAN-05:54 |
February | 1239.33 | 01-FEB-08:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 5167.60 | 12-FEB-22:51 |
March | 1239.33 | 01-MAR-08:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2800.02 | 15-MAR-04:56 |
April | 1239.33 | 03-APR-07:10 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 531.58 | 23-APR-15:50 | 2320.13 | 16-APR-11:52 |
May | 1239.33 | 01-MAY-07:10 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.35 | 24-MAY-18:00 | 1271.42 | 14-MAY-08:30 |
June | 1239.33 | 01-JUN-07:10 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.24 | 24-JUN-17:10 | 798.64 | 18-JUN-08:40 |
July | 1239.33 | 03-JUL-07:10 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 453.27 | 23-JUL-15:00 | 675.78 | 09-JUL-09:51 |
August | 1239.33 | 01-AUG-07:10 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.05 | 08-AUG-16:00 | 904.57 | 27-AUG-05:53 |
September | 1239.33 | 01-SEP-07:10 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.98 | 01-SEP-15:00 | 1182.88 | 20-SEP-01:00 |
October | 1239.33 | 02-OCT-07:10 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 1789.04 | 31-OCT-21:01 |
November | 1239.33 | 01-NOV-07:10 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2794.81 | 21-NOV-22:01 |
December | 1239.33 | 01-DEC-08:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 4542.84 | 16-DEC-05:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675.78 | |||||
Maximum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 531.58 | 5167.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6892.44 | 04-JAN-05:53 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 7760.46 | 12-FEB-22:51 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 4200.00 | 15-MAR-04:57 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.79 | 23-APR-17:50 | 3897.03 | 16-APR-11:58 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.06 | 24-MAY-15:00 | 1666.72 | 29-MAY-17:55 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 382.72 | 24-JUN-17:10 | 1036.83 | 20-JUN-03:51 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 529.75 | 23-JUL-14:55 | 1055.24 | 06-JUL-21:51 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.57 | 08-AUG-16:00 | 1394.28 | 27-AUG-05:53 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.32 | 01-SEP-15:00 | 1840.96 | 04-SEP-12:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2684.94 | 31-OCT-21:01 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 4192.98 | 21-NOV-22:01 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 6814.17 | 16-DEC-05:59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1036.83 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 529.75 | 7760.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4595.05 | 04-JAN-05:53 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 5172.96 | 12-FEB-22:51 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2800.00 | 15-MAR-04:55 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.55 | 23-APR-13:10 | 2101.16 | 16-APR-15:58 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.38 | 24-MAY-15:00 | 1130.44 | 29-MAY-17:55 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.83 | 18-JUN-12:10 | 703.22 | 20-JUN-03:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.02 | 15-JUL-17:02 | 943.26 | 16-JUL-17:10 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.96 | 20-AUG-10:42 | 973.86 | 27-AUG-05:53 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.74 | 07-SEP-12:05 | 1182.12 | 20-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 1789.51 | 31-OCT-21:01 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2795.67 | 21-NOV-22:01 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 4542.67 | 16-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 703.22 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 361.02 | 5172.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 8577.54 | 04-JAN-05:57 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 9767.66 | 12-FEB-22:53 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 5143.77 | 15-MAR-04:51 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1087.54 | 23-APR-15:41 | 3433.12 | 01-APR-18:12 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.75 | 21-MAY-15:20 | 1943.61 | 29-MAY-17:55 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 675.13 | 18-JUN-12:40 | 1162.22 | 20-JUN-03:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1031.22 | 23-JUL-15:00 | 1232.71 | 06-JUL-21:51 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 604.46 | 20-AUG-11:10 | 1456.67 | 27-AUG-05:53 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.33 | 24-SEP-14:33 | 2160.58 | 20-SEP-04:19 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 | 22-OCT-14:00 | 3334.39 | 31-OCT-21:01 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 5210.68 | 21-NOV-22:01 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 8486.33 | 16-DEC-05:58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1162.22 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1087.54 | 9767.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5718.36 | 04-JAN-05:57 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 6511.79 | 12-FEB-22:53 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 3429.88 | 15-MAR-04:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 693.17 | 23-APR-15:41 | 2497.80 | 16-APR-11:52 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.72 | 24-MAY-15:00 | 1446.59 | 14-MAY-08:10 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 365.83 | 24-JUN-17:10 | 940.63 | 18-JUN-08:30 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 533.91 | 23-JUL-15:00 | 789.30 | 06-JUL-21:51 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.21 | 08-AUG-16:00 | 1000.97 | 27-AUG-05:53 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.28 | 01-SEP-15:00 | 1440.36 | 20-SEP-04:17 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2222.70 | 31-OCT-21:01 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 3471.63 | 21-NOV-22:01 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 5657.70 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 789.30 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 693.17 | 6511.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 8577.29 | 04-JAN-06:00 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 9767.57 | 12-FEB-22:57 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 5150.46 | 15-MAR-04:51 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.80 | 23-APR-17:40 | 4275.92 | 16-APR-12:00 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.08 | 24-MAY-15:00 | 2002.35 | 29-MAY-17:55 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 494.90 | 24-JUN-17:10 | 1155.95 | 20-JUN-03:51 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 711.39 | 23-JUL-14:57 | 1227.40 | 06-JUL-21:51 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.31 | 08-AUG-16:00 | 1540.16 | 27-AUG-05:53 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.42 | 01-SEP-15:00 | 2198.91 | 04-SEP-12:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 3336.43 | 31-OCT-21:01 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 5209.09 | 21-NOV-22:01 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 8486.63 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1155.95 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 711.39 | 9767.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5718.36 | 04-JAN-05:57 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 6511.77 | 12-FEB-22:54 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 3433.56 | 15-MAR-04:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.59 | 23-APR-13:01 | 2505.82 | 16-APR-16:00 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.72 | 24-MAY-15:00 | 1366.51 | 29-MAY-17:55 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 449.16 | 18-JUN-12:00 | 827.94 | 08-JUN-23:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 447.21 | 23-JUL-14:57 | 1213.47 | 16-JUL-17:00 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 353.28 | 20-AUG-11:10 | 1096.89 | 27-AUG-05:53 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.66 | 07-SEP-12:05 | 1440.27 | 20-SEP-04:20 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2224.86 | 31-OCT-21:01 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 3474.86 | 21-NOV-22:01 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 5657.77 | 16-DEC-05:56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 827.94 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 449.16 | 6511.77 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 8217.58 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 8217.58 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 8217.58 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 8217.58 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 8217.58 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 8217.58 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 8217.58 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 8217.58 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 8217.58 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 8217.58 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 8217.58 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 8217.58 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 8217.58 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 8217.58 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5817.71 | 04-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 7548.84 | 12-FEB-22:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 3709.31 | 15-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.64 | 23-APR-16:00 | 3279.51 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.12 | 24-MAY-15:00 | 1624.85 | 08-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.43 | 24-JUN-17:01 | 1097.31 | 20-JUN-03:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.84 | 23-JUL-15:00 | 984.51 | 06-JUL-21:51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.74 | 08-AUG-16:00 | 1467.57 | 27-AUG-05:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.87 | 01-SEP-15:00 | 1938.49 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 2484.28 | 31-OCT-21:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 4683.53 | 22-NOV-01:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 5981.23 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 984.51 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.84 | 7548.84 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 10268.96 | 04-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 12858.42 | 12-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 6452.31 | 15-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 569.38 | 23-APR-16:00 | 5626.20 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.80 | 24-MAY-15:00 | 2835.09 | 20-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556.91 | 24-JUN-17:01 | 1871.12 | 20-JUN-03:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 877.31 | 23-JUL-15:00 | 1803.11 | 06-JUL-21:51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.24 | 08-AUG-16:00 | 2506.83 | 27-AUG-05:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.25 | 01-SEP-15:00 | 3344.60 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 4326.22 | 31-OCT-21:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 7881.44 | 22-NOV-01:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 10333.03 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1803.11 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 877.31 | 12858.42 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 11440.96 | 04-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 13014.26 | 12-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 6915.05 | 15-MAR-04:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.06 | 23-APR-16:00 | 5413.78 | 01-APR-18:12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.70 | 24-MAY-16:00 | 3114.22 | 29-MAY-17:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.03 | 29-JUN-21:02 | 1717.85 | 20-JUN-03:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 755.91 | 15-JUL-17:02 | 1651.06 | 16-JUL-17:01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.22 | 08-AUG-16:00 | 2296.44 | 27-AUG-05:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.51 | 01-SEP-16:00 | 3089.52 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 4676.64 | 31-OCT-21:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 7467.61 | 22-NOV-01:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 11067.21 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1651.06 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 755.91 | 13014.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 127840.40 | 20-JAN-06:01 | 14361.80 | 25906.48 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 131286.20 | 09-FEB-06:01 | 17952.25 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 130589.47 | 02-MAR-06:01 | 17952.25 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 122318.50 | 24-APR-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 141290.34 | 30-MAY-04:12 | 0.00 | 19429.86 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 140154.55 | 08-JUN-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 126457.95 | 10-JUL-04:11 | 0.00 | 22668.17 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 124610.95 | 25-AUG-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 139287.92 | 13-SEP-04:11 | 0.00 | 22668.17 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 147975.18 | 23-OCT-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 124419.62 | 13-NOV-04:01 | 0.00 | 16191.55 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 114538.36 | 01-DEC-05:01 | 0.00 | 22668.17 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 114538.36 | 0.00 | 16191.55 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 147975.18 | 17952.25 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 33761.18 | 20-JAN-16:30 | 30632.53 | 52348.14 | 34413.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 38740.60 | 08-FEB-16:53 | 153162.65 | 261740.70 | 172066.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 107545.89 | 28-MAR-05:01 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 114350.32 | 24-APR-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 120351.10 | 30-MAY-04:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 118583.07 | 26-JUN-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 122183.51 | 31-JUL-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 120590.04 | 28-AUG-04:11 | 0.00 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 116605.74 | 05-SEP-04:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 111747.50 | 23-OCT-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 107809.90 | 15-NOV-06:01 | 16122.38 | 29082.30 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 42670.36 | 06-DEC-06:01 | 14510.15 | 26174.07 | 68826.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 33761.18 | 0.00 | 17449.38 | 34413.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 122183.51 | 153162.65 | 261740.70 | 172066.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 24795.51 | 27-JAN-16:37 | 45948.79 | 78522.21 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 29081.23 | 08-FEB-16:53 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 37494.44 | 31-MAR-15:53 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 99255.41 | 14-APR-05:01 | 12897.91 | 23265.84 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 108482.17 | 30-MAY-04:12 | 0.00 | 17449.38 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 107551.91 | 28-JUN-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 107505.30 | 31-JUL-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 104865.63 | 25-AUG-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 102878.00 | 01-SEP-04:11 | 0.00 | 23265.84 | 47500.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 98846.18 | 20-OCT-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35374.40 | 17-NOV-16:13 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 25633.80 | 01-DEC-17:00 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 24795.51 | 0.00 | 17449.38 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 108482.17 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 22148.41 | 19-JAN-17:00 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25266.07 | 08-FEB-17:00 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27423.10 | 31-MAR-16:00 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41960.76 | 13-APR-16:00 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 129203.89 | 26-MAY-05:02 | 9673.43 | 17449.38 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 125473.27 | 28-JUN-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 127457.15 | 13-JUL-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 127150.02 | 10-AUG-05:01 | 11285.67 | 20357.61 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 123799.95 | 01-SEP-05:02 | 9673.43 | 17449.38 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 37090.94 | 20-OCT-15:53 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 26047.45 | 01-NOV-16:00 | 61265.06 | 104696.28 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22426.17 | 28-DEC-17:00 | 30632.53 | 52348.14 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 22148.41 | 9673.43 | 17449.38 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 129203.89 | 153162.65 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3356.58 | 30-JAN-06:05 | 1214.60 | 2190.94 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.41 |
February | 3978.68 | 08-FEB-14:41 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.65 |
March | 5414.67 | 26-MAR-16:51 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.61 |
April | 7835.41 | 18-APR-14:00 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.13 |
May | 11197.07 | 23-MAY-14:40 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 14.86 | 0.00 |
June | 15333.56 | 29-JUN-04:11 | 0.00 | 2921.26 | 5964.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.34 |
July | 18245.13 | 03-JUL-04:11 | 0.00 | 3651.57 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.21 |
August | 12012.62 | 08-AUG-15:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 74.47 | 0.00 |
September | 9804.07 | 01-SEP-15:10 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 12.51 | 0.00 |
October | 6614.31 | 01-OCT-14:31 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.73 |
November | 5529.25 | 21-NOV-06:02 | 1821.89 | 3286.42 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.56 |
December | 3543.25 | 06-DEC-06:02 | 1821.89 | 3286.42 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3356.58 | 0.00 | 1825.79 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18245.13 | 20107.90 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 74.47 | 387.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3920.79 | 25-JAN-10:10 | 2591.66 | 4235.78 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.82 |
February | 5583.43 | 28-FEB-09:55 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.80 |
March | 11457.46 | 26-MAR-10:11 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.19 |
April | 32711.07 | 30-APR-08:51 | 587.05 | 1058.95 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.07 |
May | 23477.94 | 21-MAY-09:02 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.35 |
June | 38626.46 | 25-JUN-08:61 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.98 |
July | 33477.26 | 23-JUL-09:31 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 |
August | 35376.94 | 20-AUG-10:11 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.02 |
September | 17545.77 | 24-SEP-09:32 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.00 |
October | 32004.90 | 22-OCT-09:11 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.35 |
November | 5832.11 | 11-NOV-10:21 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 704.49 |
December | 4098.94 | 28-DEC-10:00 | 3717.98 | 6353.67 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3920.79 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 | |
Maximum of Months | 38626.46 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 704.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19197.27 | 27-JAN-13:30 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 39223.81 | 20-FEB-13:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1378.64 |
March | 45028.44 | 26-MAR-13:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 732.76 |
April | 41049.98 | 23-APR-13:12 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.60 |
May | 39938.88 | 21-MAY-13:41 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.85 |
June | 42106.75 | 18-JUN-13:01 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.43 |
July | 42999.19 | 16-JUL-12:51 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.64 |
August | 45607.04 | 20-AUG-12:51 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.88 |
September | 43921.08 | 03-SEP-14:21 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.98 |
October | 49044.76 | 22-OCT-13:11 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.23 |
November | 22687.20 | 17-NOV-13:02 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.62 |
December | 15187.50 | 20-DEC-13:15 | 3846.30 | 6572.98 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15187.50 | 607.31 | 1095.50 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49044.76 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1378.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6319.09 | 27-JAN-15:50 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10727.06 | 28-FEB-15:32 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.17 |
March | 43017.52 | 26-MAR-16:51 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.83 |
April | 43396.05 | 23-APR-16:31 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.52 |
May | 44043.34 | 21-MAY-16:21 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.76 |
June | 41165.46 | 17-JUN-19:41 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.62 |
July | 48077.44 | 16-JUL-16:51 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.35 |
August | 40868.92 | 05-AUG-17:41 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.32 |
September | 45612.43 | 03-SEP-17:01 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.81 |
October | 38612.41 | 22-OCT-15:51 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.08 |
November | 8707.11 | 17-NOV-15:23 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.58 |
December | 5972.76 | 20-DEC-15:30 | 8675.28 | 14825.24 | 9746.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5972.76 | 0.00 | 823.62 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48077.44 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4347.62 | 19-JAN-06:04 | 1417.03 | 2556.10 | 6721.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.16 |
February | 4455.85 | 22-FEB-06:04 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5562.82 | 31-MAR-14:02 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.37 |
April | 8813.13 | 23-APR-16:22 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 424.21 | 0.00 |
May | 10450.69 | 24-MAY-14:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 71.98 | 0.00 |
June | 18337.60 | 28-JUN-05:01 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14727.03 | 21-JUL-05:01 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.17 |
August | 10797.24 | 09-AUG-15:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 38.76 | 0.00 |
September | 8691.72 | 01-SEP-13:30 | 4021.58 | 6572.83 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.76 | 0.00 |
October | 7266.70 | 01-OCT-14:11 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.59 |
November | 5397.26 | 01-NOV-14:02 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.54 |
December | 4522.43 | 06-DEC-06:03 | 1821.89 | 3286.42 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4347.62 | 1012.16 | 1825.79 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18337.60 | 19231.10 | 32864.16 | 21605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 424.21 | 352.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4226.12 | 25-JAN-11:03 | 3717.98 | 6353.67 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.22 |
February | 12822.02 | 28-FEB-11:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.58 |
March | 19049.51 | 31-MAR-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.35 |
April | 17857.42 | 22-APR-10:02 | 1956.83 | 3529.82 | 3867.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.57 |
May | 37742.55 | 21-MAY-08:51 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.73 |
June | 41588.27 | 25-JUN-08:11 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.51 |
July | 36350.01 | 23-JUL-09:31 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.82 |
August | 34918.23 | 20-AUG-09:12 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.39 |
September | 27263.00 | 10-SEP-09:42 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 513.52 |
October | 16850.12 | 19-OCT-10:01 | 8675.28 | 14825.24 | 9746.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.81 |
November | 11966.11 | 16-NOV-11:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.88 |
December | 4654.27 | 28-DEC-11:02 | 7435.95 | 12707.35 | 8354.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4226.12 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.82 | |
Maximum of Months | 41588.27 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 513.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22180.00 | 27-JAN-13:40 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 39149.95 | 20-FEB-14:21 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2860.64 |
March | 47604.79 | 26-MAR-14:21 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1502.73 |
April | 46855.01 | 23-APR-13:01 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 981.52 |
May | 41520.47 | 21-MAY-14:51 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.91 |
June | 41925.53 | 25-JUN-11:31 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.32 |
July | 42417.02 | 23-JUL-13:32 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 196.50 | 0.00 |
August | 42405.75 | 13-AUG-13:32 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.21 |
September | 48245.93 | 04-SEP-12:01 | 910.97 | 1643.24 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.94 |
October | 52647.81 | 22-OCT-13:11 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 790.65 |
November | 24628.61 | 17-NOV-13:02 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.29 |
December | 15916.43 | 20-DEC-13:24 | 9615.76 | 16432.44 | 10802.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 726.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15916.43 | 607.31 | 1095.50 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52647.81 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 196.50 | 2860.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5417.19 | 27-JAN-15:50 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8143.48 | 08-FEB-16:23 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.06 |
March | 37181.96 | 26-MAR-17:01 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 908.87 |
April | 44931.38 | 23-APR-17:41 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.35 |
May | 44668.79 | 14-MAY-17:11 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 658.32 |
June | 39865.63 | 17-JUN-19:41 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.76 |
July | 43471.51 | 04-JUL-16:11 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.70 |
August | 38583.77 | 05-AUG-17:41 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.69 |
September | 38259.10 | 03-SEP-17:11 | 0.00 | 823.62 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.98 |
October | 23440.36 | 22-OCT-15:51 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.44 |
November | 6107.61 | 17-NOV-15:40 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.81 |
December | 4365.49 | 20-DEC-15:30 | 8675.28 | 14825.24 | 9746.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4365.49 | 0.00 | 823.62 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44931.38 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 908.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5219.38 | 21-JAN-17:01 | 809.73 | 1460.63 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1157.00 |
February | 5979.91 | 07-FEB-06:04 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.34 |
March | 6000.96 | 23-MAR-05:04 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10965.48 | 23-APR-16:11 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 612.64 | 0.00 |
May | 11462.68 | 18-MAY-15:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 71.29 | 0.00 |
June | 17679.81 | 28-JUN-05:01 | 2024.33 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13587.73 | 23-JUL-16:11 | 809.73 | 1460.63 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 360.63 | 0.00 |
August | 11907.57 | 08-AUG-15:50 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 222.71 | 0.00 |
September | 10973.44 | 03-SEP-14:21 | 809.73 | 1460.63 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.49 |
October | 8043.88 | 22-OCT-14:31 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.99 |
November | 6021.39 | 01-NOV-15:00 | 5769.33 | 9859.25 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.79 |
December | 6148.57 | 06-DEC-06:03 | 1821.89 | 3286.42 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5219.38 | 809.73 | 1460.63 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17679.81 | 5769.33 | 9859.25 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 612.64 | 1157.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4081.92 | 17-JAN-06:04 | 1304.55 | 2353.21 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.70 |
February | 4713.29 | 28-FEB-10:30 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.17 |
March | 6670.72 | 31-MAR-09:51 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.27 |
April | 14767.91 | 18-APR-09:25 | 2591.66 | 4235.78 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.56 |
May | 18002.41 | 18-MAY-09:30 | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 2.71 | 0.00 |
June | 39501.05 | 18-JUN-09:51 | 587.05 | 1058.95 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.95 |
July | 36347.53 | 23-JUL-09:31 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.35 |
August | 37552.50 | 20-AUG-10:21 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 596.02 |
September | 16921.04 | 01-SEP-09:30 | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.39 |
October | 8720.34 | 19-OCT-09:33 | 9070.81 | 14825.24 | 9746.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.11 |
November | 4370.60 | 16-NOV-10:01 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.70 |
December | 4187.09 | 06-DEC-06:03 | 1174.10 | 2117.89 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4081.92 | 456.59 | 823.62 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39501.05 | 12958.30 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 2.71 | 596.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19186.38 | 27-JAN-13:50 | 1923.15 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27422.00 | 28-FEB-13:31 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 601.97 |
March | 54300.19 | 26-MAR-14:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1710.03 |
April | 56176.46 | 23-APR-14:51 | 910.97 | 1643.24 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 601.16 |
May | 31380.53 | 14-MAY-14:41 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 540.35 |
June | 31374.36 | 18-JUN-14:32 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.83 |
July | 53644.41 | 16-JUL-14:21 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.24 |
August | 57078.13 | 20-AUG-13:41 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.89 |
September | 56756.93 | 04-SEP-12:01 | 910.97 | 1643.24 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1885.32 |
October | 62316.52 | 22-OCT-13:11 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 912.83 |
November | 21889.39 | 17-NOV-13:12 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.17 |
December | 13339.31 | 26-DEC-13:23 | 5769.46 | 9859.46 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13339.31 | 607.31 | 1095.50 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 62316.52 | 19231.52 | 32864.88 | 21605.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1885.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5280.78 | 27-JAN-15:50 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7970.31 | 28-FEB-15:51 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.63 |
March | 23680.14 | 26-MAR-17:11 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1140.30 |
April | 48298.82 | 23-APR-16:51 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.54 |
May | 47174.20 | 14-MAY-17:21 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 826.24 |
June | 42396.48 | 17-JUN-19:41 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.62 |
July | 48165.04 | 16-JUL-16:21 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 842.14 |
August | 41100.15 | 05-AUG-17:41 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.78 |
September | 46040.32 | 03-SEP-17:01 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.95 |
October | 13321.75 | 19-OCT-16:00 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.02 |
November | 6040.97 | 17-NOV-15:40 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.59 |
December | 4669.35 | 06-DEC-06:03 | 1174.10 | 2117.89 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4669.35 | 0.00 | 823.62 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48298.82 | 12393.25 | 21178.91 | 13923.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1140.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20582.03 | 28-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2086.39 |
February | 21405.67 | 25-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18045.35 | 16-MAR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.98 |
April | 10685.43 | 05-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1200.91 |
May | 12490.47 | 30-MAY-04:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1033.17 |
June | 10456.81 | 17-JUN-04:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11549.53 | 21-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.65 |
August | 11527.12 | 28-AUG-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.13 |
September | 11455.01 | 05-SEP-04:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 749.09 |
October | 13716.85 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 757.05 |
November | 14671.40 | 24-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1108.42 |
December | 20186.10 | 02-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2232.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 10456.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21405.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2232.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24436.17 | 28-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3648.49 |
February | 25684.29 | 11-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.11 |
March | 25859.63 | 05-MAR-01:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3397.08 |
April | 19404.89 | 03-APR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2133.61 |
May | 12345.90 | 30-MAY-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.67 |
June | 11351.84 | 17-JUN-04:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11372.41 | 08-JUL-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.03 |
August | 10702.46 | 25-AUG-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10982.66 | 02-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.33 |
October | 24636.66 | 30-OCT-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.46 |
November | 22171.43 | 23-NOV-18:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5219.71 |
December | 25928.33 | 02-DEC-02:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4242.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 10702.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25928.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5219.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3771.16 |
February | 3357.79 | 08-FEB-14:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.79 |
March | 9664.56 | 26-MAR-13:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2234.14 |
April | 19424.81 | 13-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.95 |
May | 32990.60 | 18-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.81 | 0.00 |
June | 37249.27 | 30-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.41 | 0.00 |
July | 33978.59 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.49 | 0.00 |
August | 31787.91 | 08-AUG-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.60 | 0.00 |
September | 27153.83 | 01-SEP-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 |
October | 14651.49 | 22-OCT-13:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.91 |
November | 6021.82 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.28 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3800.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37249.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.41 | 3800.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5507.27 | 14-JAN-04:21 | 0.00 | 323.90 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10916.86 | 14-FEB-10:01 | 2322.69 | 7287.84 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12335.52 | 12-MAR-07:01 | 116.92 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9045.14 | 23-APR-18:12 | 0.00 | 404.88 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3161.67 | 31-MAY-23:51 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5370.32 | 30-JUN-23:02 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7253.20 | 31-JUL-24:00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8786.90 | 02-AUG-18:40 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3359.49 | 05-SEP-17:42 | 93.53 | 971.71 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4692.96 | 18-OCT-16:43 | 420.90 | 2429.28 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6317.80 | 09-NOV-16:02 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12262.37 | 20-DEC-11:12 | 2221.41 | 7287.84 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 3161.67 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12335.52 | 2322.69 | 7287.84 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2700.74 | 06-JAN-12:42 | 611.23 | 3643.92 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10481.51 | 17-FEB-09:21 | 2221.41 | 7287.84 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10822.46 | 12-MAR-07:01 | 116.92 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8680.33 | 21-APR-18:15 | 46.77 | 485.86 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3001.86 | 14-MAY-18:41 | 0.00 | 323.90 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5259.91 | 30-JUN-23:22 | 0.00 | 242.93 | 35074.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6844.29 | 31-JUL-24:00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8501.21 | 02-AUG-18:40 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3254.22 | 05-SEP-17:42 | 93.53 | 971.71 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4514.79 | 18-OCT-16:43 | 420.90 | 2429.28 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5854.04 | 09-NOV-16:12 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11581.93 | 26-DEC-09:41 | 1999.27 | 6559.06 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2700.74 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11581.93 | 2221.41 | 7287.84 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1607.57 | 25-JAN-16:25 | 444.28 | 1457.57 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10457.40 | 14-FEB-10:01 | 2322.69 | 7287.84 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10149.40 | 12-MAR-07:01 | 116.92 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8622.71 | 21-APR-18:02 | 116.92 | 1214.64 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3129.25 | 25-MAY-18:50 | 23.38 | 242.93 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5174.69 | 30-JUN-23:02 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6602.49 | 31-JUL-23:50 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8560.75 | 02-AUG-18:40 | 23.38 | 242.93 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3225.84 | 05-SEP-17:42 | 93.53 | 971.71 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4466.10 | 18-OCT-16:43 | 420.90 | 2429.28 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5534.85 | 09-NOV-16:12 | 2221.41 | 7287.84 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11696.47 | 26-DEC-09:41 | 1999.27 | 6559.06 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1607.57 | 0.00 | 40.49 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11696.47 | 2322.69 | 7287.84 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 96350.12 | 12-JAN-15:01 | 48086.79 | 82175.84 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 489288.91 | 01-FEB-00:12 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 525268.20 | 31-MAR-15:52 | 48086.79 | 82175.84 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 495373.02 | 26-APR-11:54 | 23816.47 | 73958.25 | 3416692.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 478066.61 | 31-MAY-23:09 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 488108.90 | 17-JUN-00:22 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 495741.12 | 07-JUL-23:42 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 492282.96 | 25-AUG-05:37 | 5061.77 | 9130.65 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 468375.25 | 30-SEP-23:56 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 511611.61 | 31-OCT-23:53 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 517248.59 | 01-NOV-00:52 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 488110.99 | 21-DEC-10:23 | 50279.21 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 96350.12 | 0.00 | 4565.32 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 525268.20 | 50279.21 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.195010E+13 | 1411037.64 | 20-JAN-16:49 | 0.227280E+13 | 3228629.56 | 09-JAN-07:30 |
February | 0.215148E+13 | 1613703.27 | 22-FEB-16:10 | 0.143653E+13 | 2541652.64 | 14-FEB-07:19 |
March | 0.291237E+13 | 1881391.90 | 31-MAR-14:09 | 0.981184E+12 | 2068651.25 | 06-MAR-07:19 |
April | 0.316097E+13 | 2109627.04 | 13-APR-15:20 | 0.291123E+12 | 1154886.55 | 05-APR-06:10 |
May | 0.210178E+13 | 1935541.39 | 25-MAY-15:20 | 0.477369E+11 | 896432.45 | 01-MAY-04:10 |
June | 0.257228E+13 | 2219626.51 | 30-JUN-15:09 | 0.980893E+10 | 287627.87 | 10-JUN-05:10 |
July | 0.301800E+13 | 2430776.02 | 05-JUL-10:39 | 0.367347E+10 | 112929.16 | 08-JUL-06:10 |
August | 0.339611E+13 | 2455455.28 | 08-AUG-15:20 | 0.137261E+11 | 449777.55 | 19-AUG-05:10 |
September | 0.189770E+13 | 1934622.79 | 01-SEP-10:00 | 0.820879E+11 | 744917.13 | 23-SEP-05:10 |
October | 0.233376E+13 | 1778982.47 | 19-OCT-15:09 | 0.293954E+12 | 1290716.56 | 30-OCT-06:49 |
November | 0.277412E+13 | 1829678.30 | 17-NOV-11:09 | 0.785211E+12 | 2027579.43 | 27-NOV-05:10 |
December | 0.326087E+13 | 1933435.77 | 29-DEC-16:40 | 0.193265E+13 | 2877322.87 | 26-DEC-07:19 |
Annual Sum or Average | 0.315295E+14 | 0.815049E+13 | ||||
Minimum of Months | 0.189770E+13 | 1411037.64 | 0.367347E+10 | 112929.16 | ||
Maximum of Months | 0.339611E+13 | 2455455.28 | 0.227280E+13 | 3228629.56 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.468149E+12 | 0.110235E+12 | 0.766053E+12 | 0.218140E+12 | 0.220223E+12 | 0.205284E+11 | 0.00 | 0.568356E+10 | 0.00 | 0.943659E+11 | 0.00 | 0.467233E+11 | 0.00 |
February | 0.424646E+12 | 0.905490E+11 | 0.978954E+12 | 0.199667E+12 | 0.211671E+12 | 0.338880E+11 | 0.00 | 0.568413E+11 | 781527.11 | 0.111872E+12 | 0.00 | 0.433902E+11 | 0.00 |
March | 0.504598E+12 | 0.880113E+11 | 0.141687E+13 | 0.230864E+12 | 0.239964E+12 | 0.993857E+11 | 0.00 | 0.926424E+11 | 814328.51 | 0.189219E+12 | 0.00 | 0.508127E+11 | 0.00 |
April | 0.450709E+12 | 0.728621E+11 | 0.165903E+13 | 0.216144E+12 | 0.266726E+12 | 0.944699E+11 | 0.00 | 0.118109E+12 | 0.467794E+09 | 0.237716E+12 | 0.00 | 0.447369E+11 | 0.00 |
May | 0.486374E+12 | 0.642110E+11 | 0.774844E+12 | 0.224502E+12 | 0.239435E+12 | 0.500166E+11 | 0.00 | 0.125839E+12 | 0.819991E+10 | 0.829277E+11 | 0.00 | 0.454307E+11 | 0.00 |
June | 0.484022E+12 | 0.561365E+11 | 0.106252E+13 | 0.222585E+12 | 0.272940E+12 | 0.900481E+11 | 0.00 | 0.287492E+12 | 0.298884E+11 | 0.242339E+11 | 0.00 | 0.424111E+11 | 0.00 |
July | 0.453060E+12 | 0.608274E+11 | 0.139340E+13 | 0.218061E+12 | 0.311051E+12 | 0.130016E+12 | 0.00 | 0.366206E+12 | 0.460621E+11 | 0.101895E+10 | 0.00 | 0.382940E+11 | 0.00 |
August | 0.504598E+12 | 0.703245E+11 | 0.173200E+13 | 0.230864E+12 | 0.326550E+12 | 0.124255E+12 | 0.00 | 0.332478E+12 | 0.333739E+11 | 0.945052E+09 | 0.00 | 0.407235E+11 | 0.00 |
September | 0.450709E+12 | 0.797831E+11 | 0.740713E+12 | 0.216143E+12 | 0.216615E+12 | 0.401540E+11 | 0.00 | 0.804860E+11 | 0.345950E+10 | 0.324847E+11 | 0.00 | 0.371526E+11 | 0.00 |
October | 0.468149E+12 | 0.952014E+11 | 0.108340E+13 | 0.218140E+12 | 0.216749E+12 | 0.417050E+11 | 0.00 | 0.820856E+11 | 0.308089E+09 | 0.882482E+11 | 0.00 | 0.397770E+11 | 0.00 |
November | 0.462662E+12 | 0.103314E+12 | 0.135889E+13 | 0.209941E+12 | 0.225381E+12 | 0.107729E+12 | 0.00 | 0.873678E+11 | 61828819.44 | 0.177513E+12 | 0.00 | 0.412547E+11 | 0.00 |
December | 0.453060E+12 | 0.113196E+12 | 0.170972E+13 | 0.218060E+12 | 0.275583E+12 | 0.107241E+12 | 0.00 | 0.100716E+12 | 7175.43 | 0.239762E+12 | 0.00 | 0.435331E+11 | 0.00 |
Annual Sum or Average | 0.561074E+13 | 0.100465E+13 | 0.146764E+14 | 0.262311E+13 | 0.302289E+13 | 0.939436E+12 | 0.00 | 0.173595E+13 | 0.121823E+12 | 0.128030E+13 | 0.00 | 0.514240E+12 | 0.00 |
Minimum of Months | 0.424646E+12 | 0.561365E+11 | 0.740713E+12 | 0.199667E+12 | 0.211671E+12 | 0.205284E+11 | 0.00 | 0.568356E+10 | 0.00 | 0.945052E+09 | 0.00 | 0.371526E+11 | 0.00 |
Maximum of Months | 0.504598E+12 | 0.113196E+12 | 0.173200E+13 | 0.230864E+12 | 0.326550E+12 | 0.130016E+12 | 0.00 | 0.366206E+12 | 0.460621E+11 | 0.239762E+12 | 0.00 | 0.508127E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.227280E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.143653E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.981184E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.291123E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.477369E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.980893E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.367347E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.137261E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.820879E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.293954E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.785211E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.193265E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.815049E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.367347E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.227280E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 489900.85 | 02-JAN-08:09 | 64082.80 | 01-JAN-00:10 | 423497.50 | 02-JAN-08:09 | 235096.12 | 02-JAN-08:20 | 157466.77 | 02-JAN-06:19 | 44840.22 | 31-JAN-06:30 | 0.00 | 01-JAN-00:10 |
February | 489900.85 | 01-FEB-08:09 | 64082.80 | 01-FEB-00:10 | 541788.89 | 01-FEB-08:09 | 235096.12 | 01-FEB-08:20 | 157362.17 | 08-FEB-13:00 | 44566.28 | 22-FEB-14:39 | 0.00 | 01-FEB-00:10 |
March | 489900.85 | 01-MAR-08:09 | 64082.80 | 01-MAR-00:10 | 660080.29 | 01-MAR-08:09 | 235096.12 | 01-MAR-08:20 | 209906.51 | 31-MAR-14:00 | 46683.63 | 31-MAR-13:20 | 0.00 | 01-MAR-00:10 |
April | 489900.85 | 03-APR-07:10 | 64082.80 | 01-APR-00:10 | 778371.69 | 03-APR-07:10 | 235096.12 | 03-APR-07:19 | 247552.58 | 21-APR-15:39 | 51132.61 | 23-APR-15:50 | 0.00 | 01-APR-00:10 |
May | 489900.85 | 01-MAY-07:10 | 64082.80 | 01-MAY-00:10 | 423497.50 | 01-MAY-07:10 | 235096.12 | 01-MAY-07:19 | 274796.82 | 18-MAY-14:00 | 95357.45 | 16-MAY-15:20 | 0.00 | 01-MAY-00:10 |
June | 489900.85 | 01-JUN-07:10 | 64082.80 | 01-JUN-00:10 | 541788.89 | 01-JUN-07:10 | 235096.12 | 01-JUN-07:19 | 303816.83 | 30-JUN-14:00 | 98854.08 | 08-JUN-14:00 | 0.00 | 01-JUN-00:10 |
July | 489900.85 | 03-JUL-07:10 | 64082.80 | 01-JUL-00:10 | 660080.29 | 03-JUL-07:10 | 235096.12 | 03-JUL-07:19 | 295966.20 | 21-JUL-15:20 | 111901.83 | 05-JUL-10:39 | 0.00 | 01-JUL-00:10 |
August | 489900.85 | 01-AUG-07:10 | 64082.80 | 01-AUG-00:10 | 778371.69 | 01-AUG-07:10 | 235096.12 | 01-AUG-07:19 | 303257.48 | 08-AUG-15:20 | 97182.87 | 31-AUG-12:39 | 0.00 | 01-AUG-00:10 |
September | 489900.85 | 01-SEP-07:10 | 64082.80 | 01-SEP-00:10 | 423497.50 | 01-SEP-07:10 | 235096.12 | 01-SEP-07:19 | 287714.19 | 01-SEP-15:39 | 95525.22 | 01-SEP-10:50 | 0.00 | 01-SEP-00:10 |
October | 489900.85 | 02-OCT-07:10 | 64082.80 | 01-OCT-00:10 | 541788.89 | 02-OCT-07:10 | 235096.12 | 02-OCT-07:19 | 225769.13 | 18-OCT-15:20 | 49740.24 | 19-OCT-12:20 | 0.00 | 01-OCT-00:10 |
November | 489900.85 | 01-NOV-07:10 | 64082.80 | 01-NOV-00:10 | 660080.29 | 01-NOV-07:10 | 235096.12 | 01-NOV-07:19 | 189490.07 | 17-NOV-13:30 | 46881.47 | 01-NOV-15:30 | 0.00 | 01-NOV-00:10 |
December | 489900.85 | 01-DEC-08:09 | 64082.80 | 01-DEC-00:10 | 778371.69 | 01-DEC-08:09 | 235096.12 | 01-DEC-08:20 | 165761.35 | 26-DEC-06:10 | 48376.69 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 489900.85 | 64082.80 | 423497.50 | 235096.12 | 157362.17 | 44566.28 | 0.00 | |||||||
Maximum of Months | 489900.85 | 64082.80 | 778371.69 | 235096.12 | 303816.83 | 111901.83 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 8414.85 | 20-JAN-16:30 | 0.00 | 01-JAN-00:10 | 46307.27 | 21-JAN-15:00 | 0.00 | 62564.32 | 31-JAN-12:00 | 0.00 |
February | 77523.42 | 06-FEB-06:00 | 18.61 | 21-FEB-14:09 | 78541.97 | 08-FEB-15:50 | 0.00 | 62804.56 | 24-FEB-12:39 | 0.00 |
March | 144623.79 | 31-MAR-13:20 | 82.10 | 31-MAR-14:09 | 100000.00 | 31-MAR-23:49 | 0.00 | 62796.63 | 01-MAR-12:00 | 0.00 |
April | 229972.72 | 23-APR-16:30 | 27892.31 | 23-APR-15:00 | 100000.00 | 01-APR-00:10 | 0.00 | 61856.52 | 04-APR-11:50 | 0.00 |
May | 342573.39 | 25-MAY-12:09 | 55784.63 | 17-MAY-13:30 | 100000.00 | 02-MAY-11:00 | 0.00 | 59258.61 | 01-MAY-11:20 | 0.00 |
June | 458631.14 | 29-JUN-15:00 | 55784.63 | 19-JUN-13:09 | 100000.00 | 01-JUN-16:30 | 0.00 | 55934.55 | 01-JUN-11:30 | 0.00 |
July | 590463.98 | 05-JUL-10:20 | 55784.63 | 03-JUL-13:09 | 68459.63 | 07-JUL-17:00 | 0.00 | 52595.67 | 03-JUL-11:00 | 0.00 |
August | 488761.13 | 31-AUG-12:39 | 55784.63 | 31-AUG-12:20 | 75856.83 | 31-AUG-12:50 | 0.00 | 50875.51 | 02-AUG-11:50 | 0.00 |
September | 367217.61 | 01-SEP-10:00 | 55784.63 | 01-SEP-10:30 | 99705.13 | 08-SEP-15:00 | 0.00 | 51317.80 | 29-SEP-11:20 | 0.00 |
October | 187429.93 | 19-OCT-14:00 | 9477.56 | 19-OCT-14:00 | 92214.84 | 21-OCT-15:00 | 0.00 | 53280.87 | 31-OCT-11:30 | 0.00 |
November | 141633.25 | 01-NOV-14:09 | 4651.88 | 01-NOV-14:09 | 98854.58 | 21-NOV-17:30 | 0.00 | 56905.21 | 30-NOV-12:39 | 0.00 |
December | 84438.69 | 05-DEC-16:30 | 4.91 | 26-DEC-06:40 | 100000.00 | 01-DEC-02:00 | 0.00 | 60393.88 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 8414.85 | 0.00 | 46307.27 | 0.00 | 50875.51 | 0.00 | ||||
Maximum of Months | 590463.98 | 55784.63 | 100000.00 | 0.00 | 62804.56 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1411037.64 | 20-JAN-16:49 | 489900.85 | 423497.50 | 64082.80 | 235096.12 | 101499.55 | 284.91 | 0.00 | 8084.50 | 0.00 |
February | 1613703.27 | 22-FEB-16:10 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 127080.52 | 31296.93 | 0.00 | 74623.35 | 9.65 |
March | 1881391.90 | 31-MAR-14:09 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 188469.49 | 46552.12 | 0.00 | 143216.44 | 82.10 |
April | 2109627.04 | 13-APR-15:20 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 244136.00 | 46076.50 | 0.00 | 167228.78 | 2107.99 |
May | 1935541.39 | 25-MAY-15:20 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 265145.19 | 93338.07 | 0.00 | 328826.89 | 55784.63 |
June | 2219626.51 | 30-JUN-15:09 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 302866.88 | 96396.49 | 0.00 | 458242.84 | 55784.63 |
July | 2430776.02 | 05-JUL-10:39 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 272737.06 | 111901.83 | 0.00 | 561907.26 | 55784.63 |
August | 2455455.28 | 08-AUG-15:20 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 303257.48 | 96563.23 | 0.00 | 457589.48 | 55784.63 |
September | 1934622.79 | 01-SEP-10:00 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 228091.54 | 93876.93 | 0.00 | 367217.61 | 55784.63 |
October | 1778982.47 | 19-OCT-15:09 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 214485.94 | 49434.61 | 0.00 | 185506.79 | 9327.26 |
November | 1829678.30 | 17-NOV-11:09 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 162944.38 | 45923.83 | 0.00 | 103923.10 | 31.75 |
December | 1933435.77 | 29-DEC-16:40 | 489900.85 | 778371.69 | 64082.80 | 235096.12 | 121552.18 | 45664.49 | 0.00 | 54484.61 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1411037.64 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 101499.55 | 284.91 | 0.00 | 8084.50 | 0.00 | |
Maximum of Months | 2455455.28 | 489900.85 | 778371.69 | 64082.80 | 235096.12 | 303257.48 | 111901.83 | 0.00 | 561907.26 | 55784.63 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 3228629.56 | 09-JAN-07:30 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 2541652.64 | 14-FEB-07:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 2068651.25 | 06-MAR-07:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 1154886.55 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 896432.45 | 01-MAY-04:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 287627.87 | 10-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 112929.16 | 08-JUL-06:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 449777.55 | 19-AUG-05:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 744917.13 | 23-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 1290716.56 | 30-OCT-06:49 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 2027579.43 | 27-NOV-05:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 2877322.87 | 26-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 112929.16 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 3228629.56 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 20.34 | 1.33 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.70 | 0.00 | 26.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.66 | 0.00 | 25.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 26.06 | 0.00 | 26.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 25.83 | 0.00 | 25.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 26.10 | 0.00 | 26.10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.77 | 0.00 | 25.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.67 | 0.00 | 25.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.33 | 20.34 | 1.33 | 20.34 | 12.83 | 24.98 | 0.00 | 24.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.34 | 1.33 | 20.34 | 4.50 | 26.70 | 0.00 | 26.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 19.21 | 0.33 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 19.45 | 0.17 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 |
Annual Sum or Average | 2.33 | 19.30 | 0.50 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.45 | 0.33 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.17 | 17.36 | 1.33 | 17.32 | 0.00 | 17.32 | 0.00 | 17.32 |
February | 6.50 | 18.55 | 0.17 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
March | 4.17 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
April | 1.00 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.33 | 18.09 | 0.00 | 18.09 | 0.00 | 18.09 | 0.00 | 18.09 |
November | 4.17 | 18.56 | 0.67 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
December | 9.67 | 17.88 | 1.33 | 17.84 | 0.00 | 17.84 | 0.00 | 17.84 |
Annual Sum or Average | 40.00 | 17.99 | 3.50 | 17.99 | 0.00 | 17.99 | 0.00 | 17.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.17 | 18.76 | 1.33 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.50 | 16.23 | 5.17 | 16.07 | 0.00 | 16.07 | 0.00 | 16.07 |
February | 9.50 | 18.29 | 1.00 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
March | 4.33 | 18.66 | 0.33 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.50 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
December | 18.83 | 16.45 | 3.83 | 16.25 | 0.00 | 16.25 | 0.00 | 16.25 |
Annual Sum or Average | 60.67 | 16.86 | 10.33 | 16.72 | 0.00 | 16.72 | 0.00 | 16.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.50 | 18.98 | 5.17 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.83 | 16.01 | 3.00 | 15.94 | 0.00 | 15.94 | 0.00 | 15.94 |
February | 9.33 | 17.69 | 0.67 | 17.69 | 0.00 | 17.69 | 0.00 | 17.69 |
March | 4.17 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 |
April | 0.17 | 19.42 | 0.00 | 19.42 | 0.33 | 24.93 | 0.33 | 26.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.25 | 2.00 | 28.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.86 | 3.67 | 28.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.44 | 2.33 | 28.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.70 | 3.50 | 28.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.81 | 1.17 | 27.81 |
October | 0.17 | 19.41 | 0.00 | 19.41 | 0.17 | 23.35 | 0.17 | 24.66 |
November | 1.50 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
December | 19.33 | 16.13 | 2.33 | 16.02 | 0.00 | 16.02 | 0.00 | 16.02 |
Annual Sum or Average | 59.50 | 16.57 | 6.00 | 16.47 | 13.17 | 18.48 | 13.17 | 19.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.94 | 0.00 | 15.94 |
Maximum of Months | 24.83 | 19.42 | 3.00 | 19.42 | 3.67 | 28.86 | 3.67 | 28.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.50 | 16.11 | 2.50 | 16.05 | 0.00 | 16.05 | 0.00 | 16.05 |
February | 11.50 | 17.48 | 1.17 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 |
March | 4.83 | 18.21 | 0.17 | 18.10 | 2.33 | 21.31 | 2.33 | 22.97 |
April | 0.50 | 19.36 | 0.00 | 19.36 | 1.50 | 26.21 | 1.50 | 27.18 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.68 | 1.17 | 27.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.02 | 1.33 | 28.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.34 | 3.17 | 28.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.38 | 4.83 | 28.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.39 | 4.00 | 28.39 |
October | 0.17 | 18.88 | 0.00 | 18.88 | 3.17 | 28.10 | 3.17 | 28.34 |
November | 2.50 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
December | 18.83 | 16.39 | 2.17 | 16.28 | 0.00 | 16.28 | 0.00 | 16.28 |
Annual Sum or Average | 63.83 | 16.73 | 6.00 | 16.66 | 21.50 | 19.40 | 21.50 | 21.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.05 | 0.00 | 16.05 |
Maximum of Months | 25.50 | 19.36 | 2.50 | 19.36 | 4.83 | 28.39 | 4.83 | 28.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.17 | 17.21 | 1.00 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
February | 5.00 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
March | 1.17 | 19.19 | 0.00 | 19.19 | 1.33 | 24.19 | 0.83 | 25.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 29.18 | 1.50 | 29.19 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.83 | 2.50 | 28.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.52 | 1.00 | 28.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.80 | 5.17 | 28.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.71 | 4.00 | 28.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 29.12 | 1.00 | 29.17 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.51 | 0.50 | 27.51 |
November | 0.67 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
December | 3.50 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
Annual Sum or Average | 22.50 | 17.95 | 1.00 | 17.86 | 30.83 | 24.05 | 16.50 | 25.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.10 | 0.00 | 17.10 |
Maximum of Months | 12.17 | 19.24 | 1.00 | 19.24 | 9.50 | 29.18 | 5.17 | 29.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 67.50 | 14.97 | 17.50 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
February | 45.67 | 15.47 | 7.17 | 15.43 | 0.00 | 15.43 | 0.00 | 15.43 |
March | 22.17 | 16.34 | 2.00 | 16.24 | 0.00 | 16.24 | 0.00 | 16.24 |
April | 4.00 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
May | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.83 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
November | 23.00 | 15.91 | 4.33 | 15.80 | 0.00 | 15.80 | 0.00 | 15.80 |
December | 61.33 | 14.90 | 14.83 | 14.78 | 0.00 | 14.78 | 0.00 | 14.78 |
Annual Sum or Average | 225.67 | 15.38 | 45.83 | 15.26 | 0.00 | 15.26 | 0.00 | 15.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.50 | 19.40 | 17.50 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 115.00 | 16.42 | 16.33 | 16.21 | 0.00 | 16.21 | 0.00 | 16.21 |
February | 56.83 | 16.46 | 3.50 | 16.42 | 0.00 | 16.42 | 0.00 | 16.42 |
March | 28.50 | 17.32 | 0.83 | 17.25 | 0.00 | 17.25 | 0.00 | 17.25 |
April | 4.00 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.57 | 1.50 | 28.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 29.02 | 3.83 | 29.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.46 | 2.83 | 28.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.70 | 3.33 | 28.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.62 | 0.50 | 27.62 |
October | 1.83 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 |
November | 35.17 | 17.01 | 4.33 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
December | 110.67 | 16.62 | 14.00 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 |
Annual Sum or Average | 352.00 | 16.66 | 39.00 | 16.47 | 12.00 | 16.83 | 12.00 | 17.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.21 | 0.00 | 16.21 |
Maximum of Months | 115.00 | 18.79 | 16.33 | 18.79 | 3.83 | 29.02 | 3.83 | 29.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 51.17 | 15.15 | 8.83 | 15.14 | 0.00 | 15.14 | 0.00 | 15.14 |
February | 32.83 | 15.87 | 3.00 | 15.88 | 0.00 | 15.88 | 0.00 | 15.88 |
March | 14.83 | 16.79 | 0.83 | 16.68 | 3.33 | 18.74 | 3.33 | 20.19 |
April | 3.50 | 18.54 | 0.00 | 18.54 | 1.50 | 21.58 | 1.50 | 23.22 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.91 | 1.67 | 27.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.85 | 1.83 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.40 | 3.17 | 28.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.44 | 4.67 | 28.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.45 | 4.67 | 28.45 |
October | 1.67 | 18.88 | 0.00 | 18.88 | 3.83 | 25.84 | 3.83 | 27.09 |
November | 17.00 | 16.23 | 2.00 | 16.18 | 0.00 | 16.18 | 0.00 | 16.18 |
December | 51.00 | 15.18 | 8.33 | 15.12 | 0.00 | 15.12 | 0.00 | 15.12 |
Annual Sum or Average | 172.00 | 15.65 | 23.00 | 15.59 | 24.67 | 17.03 | 24.67 | 18.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.12 | 0.00 | 15.12 |
Maximum of Months | 51.17 | 18.88 | 8.83 | 18.88 | 4.67 | 28.45 | 4.67 | 28.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 52.83 | 15.04 | 12.17 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
February | 33.83 | 15.62 | 4.33 | 15.60 | 0.00 | 15.60 | 0.00 | 15.60 |
March | 13.67 | 16.75 | 0.67 | 16.66 | 0.33 | 16.91 | 0.17 | 17.03 |
April | 3.00 | 18.70 | 0.00 | 18.70 | 1.50 | 22.27 | 0.83 | 23.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 29.18 | 1.50 | 29.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.72 | 0.83 | 28.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.77 | 3.67 | 28.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.49 | 2.83 | 28.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.95 | 0.67 | 29.01 |
October | 1.33 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
November | 16.00 | 16.22 | 1.67 | 16.10 | 0.00 | 16.10 | 0.00 | 16.10 |
December | 52.83 | 15.15 | 11.17 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 |
Annual Sum or Average | 173.50 | 15.52 | 30.00 | 15.41 | 20.67 | 16.65 | 10.50 | 17.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 | 0.00 | 14.97 |
Maximum of Months | 52.83 | 18.78 | 12.17 | 18.78 | 7.17 | 29.18 | 3.67 | 29.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 86.83 | 14.27 | 22.67 | 14.21 | 0.00 | 14.21 | 0.00 | 14.21 |
February | 72.50 | 14.71 | 17.50 | 14.70 | 0.00 | 14.70 | 0.00 | 14.70 |
March | 48.50 | 15.26 | 9.17 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
April | 19.33 | 15.93 | 2.67 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 |
May | 1.83 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1.67 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
October | 15.67 | 16.20 | 3.00 | 16.04 | 0.00 | 16.04 | 0.00 | 16.04 |
November | 57.67 | 15.02 | 16.83 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
December | 88.00 | 14.29 | 24.00 | 14.21 | 0.00 | 14.21 | 0.00 | 14.21 |
Annual Sum or Average | 392.00 | 14.79 | 95.83 | 14.70 | 0.00 | 14.70 | 0.00 | 14.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.00 | 19.27 | 24.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 87.33 | 14.27 | 23.00 | 14.24 | 0.00 | 14.24 | 0.00 | 14.24 |
February | 69.50 | 14.72 | 14.50 | 14.73 | 0.00 | 14.73 | 0.00 | 14.73 |
March | 43.67 | 15.36 | 5.00 | 15.34 | 0.00 | 15.34 | 0.00 | 15.34 |
April | 17.67 | 16.02 | 1.67 | 15.95 | 0.00 | 15.95 | 0.00 | 15.95 |
May | 1.50 | 18.69 | 0.00 | 18.69 | 0.50 | 20.94 | 0.50 | 22.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.80 | 3.33 | 28.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.30 | 3.17 | 28.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.24 | 2.83 | 28.24 |
September | 1.33 | 19.22 | 0.00 | 19.22 | 0.17 | 20.11 | 0.17 | 20.83 |
October | 13.83 | 16.31 | 2.17 | 16.17 | 0.00 | 16.17 | 0.00 | 16.17 |
November | 55.17 | 15.03 | 13.83 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
December | 87.17 | 14.29 | 23.67 | 14.23 | 0.00 | 14.23 | 0.00 | 14.23 |
Annual Sum or Average | 377.17 | 14.79 | 83.83 | 14.72 | 10.00 | 15.01 | 10.00 | 15.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.23 | 0.00 | 14.23 |
Maximum of Months | 87.33 | 19.22 | 23.67 | 19.22 | 3.33 | 28.80 | 3.33 | 28.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 80.83 | 14.45 | 18.17 | 14.44 | 0.00 | 14.44 | 0.00 | 14.44 |
February | 58.00 | 14.89 | 9.17 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
March | 36.83 | 15.64 | 4.00 | 15.61 | 1.00 | 15.90 | 1.00 | 16.18 |
April | 14.83 | 16.28 | 1.83 | 16.15 | 1.00 | 16.86 | 1.00 | 17.50 |
May | 1.33 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.81 | 1.00 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.63 | 2.50 | 28.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.48 | 3.17 | 28.48 |
September | 1.00 | 19.23 | 0.00 | 19.23 | 2.50 | 25.81 | 2.50 | 26.91 |
October | 11.00 | 16.53 | 1.50 | 16.33 | 1.83 | 17.92 | 1.83 | 19.15 |
November | 47.50 | 15.18 | 10.33 | 15.10 | 0.00 | 15.10 | 0.00 | 15.10 |
December | 78.50 | 14.48 | 17.33 | 14.46 | 0.00 | 14.46 | 0.00 | 14.46 |
Annual Sum or Average | 329.83 | 14.96 | 62.33 | 14.90 | 13.00 | 15.33 | 13.00 | 15.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.44 | 0.00 | 14.44 |
Maximum of Months | 80.83 | 19.23 | 18.17 | 19.23 | 3.17 | 28.63 | 3.17 | 28.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 82.00 | 14.40 | 20.67 | 14.36 | 0.00 | 14.36 | 0.00 | 14.36 |
February | 54.83 | 14.83 | 9.33 | 14.81 | 0.00 | 14.81 | 0.00 | 14.81 |
March | 32.67 | 15.57 | 4.67 | 15.49 | 0.00 | 15.49 | 0.00 | 15.49 |
April | 11.50 | 16.83 | 1.00 | 16.66 | 1.50 | 18.00 | 0.83 | 18.64 |
May | 1.00 | 19.02 | 0.00 | 19.02 | 3.67 | 26.83 | 1.50 | 27.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.80 | 0.83 | 28.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.85 | 3.83 | 28.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.48 | 2.50 | 28.47 |
September | 0.67 | 19.27 | 0.00 | 19.27 | 1.33 | 25.58 | 0.83 | 26.56 |
October | 7.00 | 17.03 | 0.17 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 |
November | 41.00 | 15.23 | 10.67 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 |
December | 77.00 | 14.52 | 19.67 | 14.47 | 0.00 | 14.47 | 0.00 | 14.47 |
Annual Sum or Average | 307.67 | 14.92 | 66.17 | 14.83 | 19.50 | 15.52 | 10.33 | 15.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.36 | 0.00 | 14.36 |
Maximum of Months | 82.00 | 19.27 | 20.67 | 19.27 | 6.83 | 28.85 | 3.83 | 28.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 127.50 | 29.36 | 76.83 | 29.37 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 | 33.64 | 19.00 | 33.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 35.71 | 3.33 | 35.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 95.17 | 40.24 | 44.50 | 40.29 |
Annual Sum or Average | 0.00 | 0.00 | 279.00 | 34.02 | 143.67 | 33.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 127.50 | 40.24 | 76.83 | 40.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 73.83 | 28.57 | 48.67 | 28.63 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 | 31.82 | 19.00 | 31.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 33.73 | 3.00 | 33.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 95.17 | 37.90 | 44.50 | 38.04 |
Annual Sum or Average | 0.00 | 0.00 | 225.00 | 33.42 | 115.17 | 33.31 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 95.17 | 37.90 | 48.67 | 38.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 28.40 | 10.33 | 28.40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 | 29.34 | 19.00 | 29.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 31.19 | 2.83 | 31.18 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 95.17 | 35.33 | 44.50 | 35.54 |
Annual Sum or Average | 0.00 | 0.00 | 161.00 | 32.95 | 76.67 | 33.05 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 95.17 | 35.33 | 44.50 | 35.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.67 | 0.17 | 27.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.93 | 0.50 | 27.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.17 | 27.90 | 0.67 | 27.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.93 | 0.50 | 27.94 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.92 | 8.00 | 21.90 | 8.00 | 21.88 |
February | 449.50 | 22.60 | 1.33 | 22.60 | 1.33 | 22.59 |
March | 478.83 | 23.23 | 0.00 | 23.23 | 0.00 | 23.23 |
April | 353.17 | 23.72 | 27.50 | 23.87 | 0.00 | 23.87 |
May | 147.83 | 23.59 | 187.50 | 24.34 | 0.00 | 24.34 |
June | 32.67 | 24.94 | 353.50 | 24.59 | 18.50 | 24.64 |
July | 14.17 | 26.77 | 483.17 | 24.67 | 14.17 | 24.73 |
August | 6.33 | 24.00 | 469.83 | 24.49 | 6.33 | 24.48 |
September | 60.67 | 23.31 | 193.67 | 24.72 | 1.33 | 24.71 |
October | 103.67 | 23.77 | 105.17 | 24.91 | 0.00 | 24.91 |
November | 304.33 | 23.67 | 57.83 | 23.99 | 0.00 | 23.99 |
December | 490.50 | 22.56 | 0.83 | 22.55 | 0.83 | 22.55 |
Annual Sum or Average | 2943.67 | 22.98 | 1888.33 | 23.68 | 50.50 | 23.69 |
Minimum of Months | 6.33 | 21.92 | 0.00 | 21.90 | 0.00 | 21.88 |
Maximum of Months | 502.00 | 26.77 | 483.17 | 24.91 | 18.50 | 24.91 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.71 | 36.50 | 22.56 | 36.50 | 22.43 |
February | 452.67 | 23.32 | 1.33 | 23.31 | 1.33 | 23.30 |
March | 412.33 | 23.62 | 0.67 | 23.62 | 0.00 | 23.62 |
April | 212.67 | 23.85 | 17.33 | 23.97 | 0.00 | 23.97 |
May | 89.83 | 23.78 | 199.17 | 24.34 | 0.00 | 24.34 |
June | 12.83 | 24.07 | 373.83 | 24.28 | 2.17 | 24.29 |
July | 0.00 | 0.00 | 491.00 | 24.31 | 0.00 | 24.31 |
August | 0.00 | 0.00 | 494.50 | 24.27 | 0.00 | 24.27 |
September | 33.00 | 23.63 | 220.67 | 24.41 | 0.00 | 24.41 |
October | 130.83 | 23.66 | 51.33 | 24.05 | 0.00 | 24.05 |
November | 264.83 | 23.73 | 19.83 | 23.77 | 0.00 | 23.77 |
December | 477.67 | 23.32 | 7.83 | 23.28 | 7.83 | 23.25 |
Annual Sum or Average | 2588.67 | 23.38 | 1914.00 | 23.76 | 47.83 | 23.73 |
Minimum of Months | 0.00 | 0.00 | 0.67 | 22.56 | 0.00 | 22.43 |
Maximum of Months | 502.00 | 24.07 | 494.50 | 24.41 | 36.50 | 24.41 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.56 | 188.83 | 21.19 | 188.83 | 20.97 |
February | 454.00 | 22.17 | 95.67 | 21.87 | 95.67 | 21.65 |
March | 498.83 | 22.88 | 37.67 | 22.73 | 37.67 | 22.60 |
April | 427.67 | 23.45 | 0.00 | 23.45 | 0.00 | 23.45 |
May | 163.67 | 23.55 | 152.67 | 24.00 | 0.00 | 24.00 |
June | 55.83 | 23.53 | 299.50 | 24.11 | 4.17 | 24.12 |
July | 5.50 | 23.20 | 449.83 | 24.22 | 0.00 | 24.22 |
August | 46.17 | 23.31 | 406.83 | 24.07 | 0.00 | 24.07 |
September | 142.17 | 23.39 | 118.50 | 23.83 | 0.00 | 23.83 |
October | 355.83 | 23.28 | 3.17 | 23.29 | 0.00 | 23.29 |
November | 464.00 | 22.71 | 57.83 | 22.51 | 51.83 | 22.33 |
December | 497.00 | 21.80 | 143.33 | 21.47 | 143.33 | 21.26 |
Annual Sum or Average | 3612.67 | 22.61 | 1953.83 | 22.82 | 521.50 | 22.61 |
Minimum of Months | 5.50 | 21.56 | 0.00 | 21.19 | 0.00 | 20.97 |
Maximum of Months | 502.00 | 23.55 | 449.83 | 24.22 | 188.83 | 24.22 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.18 | 446.33 | 20.10 | 446.33 | 20.07 |
February | 454.00 | 20.47 | 342.00 | 20.30 | 342.00 | 20.23 |
March | 514.00 | 21.01 | 273.33 | 20.76 | 273.33 | 20.64 |
April | 472.83 | 21.73 | 122.00 | 21.40 | 122.00 | 21.19 |
May | 308.00 | 22.48 | 131.17 | 22.85 | 21.00 | 22.74 |
June | 172.67 | 22.48 | 230.00 | 23.37 | 7.83 | 23.35 |
July | 110.00 | 22.55 | 335.67 | 23.75 | 0.00 | 23.75 |
August | 184.67 | 22.59 | 260.00 | 23.43 | 0.67 | 23.43 |
September | 401.33 | 22.35 | 37.50 | 22.45 | 10.17 | 22.44 |
October | 492.00 | 21.35 | 100.50 | 21.05 | 100.50 | 20.84 |
November | 489.00 | 20.67 | 267.50 | 20.37 | 267.50 | 20.22 |
December | 497.00 | 20.22 | 423.00 | 20.12 | 423.00 | 20.08 |
Annual Sum or Average | 4597.50 | 21.22 | 2969.00 | 21.28 | 2014.33 | 21.02 |
Minimum of Months | 110.00 | 20.18 | 37.50 | 20.10 | 0.00 | 20.07 |
Maximum of Months | 514.00 | 22.59 | 446.33 | 23.75 | 446.33 | 23.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.08 | 483.50 | 20.06 | 483.50 | 20.06 |
February | 454.00 | 20.44 | 383.00 | 20.37 | 383.00 | 20.35 |
March | 514.00 | 20.96 | 284.67 | 20.80 | 284.67 | 20.72 |
April | 449.83 | 22.01 | 48.33 | 21.92 | 44.33 | 21.82 |
May | 238.33 | 22.71 | 166.17 | 23.37 | 0.00 | 23.37 |
June | 82.83 | 22.99 | 326.83 | 23.92 | 0.00 | 23.92 |
July | 25.67 | 23.19 | 445.67 | 24.17 | 3.83 | 24.18 |
August | 73.33 | 22.79 | 372.83 | 23.88 | 0.00 | 23.88 |
September | 299.00 | 22.46 | 84.50 | 22.84 | 0.00 | 22.84 |
October | 490.00 | 21.89 | 24.67 | 21.83 | 24.67 | 21.78 |
November | 484.50 | 21.03 | 219.83 | 20.84 | 219.83 | 20.74 |
December | 497.00 | 20.17 | 455.00 | 20.13 | 455.00 | 20.12 |
Annual Sum or Average | 4110.50 | 21.23 | 3295.00 | 21.54 | 1898.83 | 21.27 |
Minimum of Months | 25.67 | 20.08 | 24.67 | 20.06 | 0.00 | 20.06 |
Maximum of Months | 514.00 | 23.19 | 483.50 | 24.17 | 483.50 | 24.18 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.06 | 476.83 | 20.04 | 476.83 | 20.03 |
February | 454.00 | 20.55 | 334.83 | 20.44 | 334.83 | 20.39 |
March | 483.17 | 21.01 | 239.33 | 20.89 | 228.83 | 20.79 |
April | 370.00 | 21.64 | 106.17 | 21.89 | 45.17 | 21.79 |
May | 244.67 | 22.33 | 193.50 | 23.26 | 6.17 | 23.31 |
June | 148.17 | 22.87 | 315.00 | 23.77 | 21.50 | 23.88 |
July | 107.67 | 23.06 | 382.17 | 23.88 | 33.50 | 23.96 |
August | 191.17 | 22.44 | 280.17 | 23.42 | 15.67 | 23.52 |
September | 316.33 | 21.95 | 113.33 | 22.57 | 5.83 | 22.61 |
October | 466.00 | 21.45 | 56.67 | 21.56 | 32.50 | 21.51 |
November | 486.83 | 20.86 | 226.83 | 20.71 | 226.83 | 20.63 |
December | 497.00 | 20.12 | 456.17 | 20.09 | 456.17 | 20.07 |
Annual Sum or Average | 4267.00 | 21.16 | 3181.00 | 21.49 | 1883.83 | 21.28 |
Minimum of Months | 107.67 | 20.06 | 56.67 | 20.04 | 5.83 | 20.03 |
Maximum of Months | 502.00 | 23.06 | 476.83 | 23.88 | 476.83 | 23.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 467.33 | 20.32 | 379.50 | 20.16 | 372.67 | 20.08 |
February | 376.17 | 20.77 | 288.67 | 20.74 | 256.00 | 20.59 |
March | 415.00 | 21.19 | 263.83 | 21.25 | 216.83 | 21.11 |
April | 347.83 | 21.69 | 153.17 | 21.98 | 79.00 | 21.84 |
May | 238.00 | 22.21 | 202.17 | 23.13 | 7.67 | 23.11 |
June | 164.33 | 22.42 | 277.33 | 23.50 | 6.33 | 23.55 |
July | 105.00 | 22.95 | 369.33 | 23.93 | 16.83 | 24.02 |
August | 162.50 | 22.87 | 326.67 | 23.77 | 20.50 | 23.89 |
September | 284.83 | 22.31 | 179.50 | 23.14 | 19.33 | 23.27 |
October | 417.83 | 21.64 | 129.50 | 21.94 | 66.33 | 21.89 |
November | 431.17 | 20.92 | 240.50 | 20.88 | 207.50 | 20.72 |
December | 470.33 | 20.38 | 382.83 | 20.24 | 382.83 | 20.19 |
Annual Sum or Average | 3880.33 | 21.33 | 3193.00 | 21.75 | 1651.83 | 21.52 |
Minimum of Months | 105.00 | 20.32 | 129.50 | 20.16 | 6.33 | 20.08 |
Maximum of Months | 470.33 | 22.95 | 382.83 | 23.93 | 382.83 | 24.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.42 | 417.50 | 20.34 | 417.50 | 20.31 |
February | 438.50 | 20.91 | 259.00 | 20.80 | 253.33 | 20.72 |
March | 463.00 | 21.34 | 151.50 | 21.38 | 121.83 | 21.29 |
April | 354.17 | 22.16 | 95.33 | 22.63 | 11.17 | 22.68 |
May | 241.17 | 22.55 | 219.83 | 23.48 | 28.17 | 23.58 |
June | 148.17 | 22.85 | 339.83 | 23.81 | 40.33 | 23.89 |
July | 113.17 | 24.53 | 448.17 | 24.40 | 84.33 | 24.52 |
August | 105.17 | 24.16 | 428.17 | 24.24 | 66.17 | 24.35 |
September | 295.33 | 22.15 | 141.17 | 22.87 | 10.33 | 22.94 |
October | 444.17 | 21.70 | 43.33 | 21.91 | 4.00 | 21.91 |
November | 472.17 | 21.34 | 88.83 | 21.25 | 87.00 | 21.17 |
December | 497.00 | 20.71 | 302.67 | 20.59 | 302.67 | 20.53 |
Annual Sum or Average | 4074.00 | 21.56 | 2935.33 | 22.06 | 1426.83 | 21.92 |
Minimum of Months | 105.17 | 20.42 | 43.33 | 20.34 | 4.00 | 20.31 |
Maximum of Months | 502.00 | 24.53 | 448.17 | 24.40 | 417.50 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.73 | 502.00 | 19.73 | 502.00 | 19.73 |
February | 454.00 | 19.90 | 437.83 | 19.88 | 437.83 | 19.87 |
March | 514.00 | 20.33 | 420.33 | 20.25 | 420.33 | 20.22 |
April | 485.00 | 20.92 | 202.83 | 20.70 | 202.83 | 20.57 |
May | 350.17 | 21.98 | 121.00 | 22.38 | 22.33 | 22.29 |
June | 199.33 | 22.36 | 232.50 | 23.24 | 2.17 | 23.25 |
July | 128.33 | 22.75 | 327.17 | 23.69 | 18.00 | 23.74 |
August | 279.17 | 22.12 | 177.83 | 22.79 | 0.00 | 22.79 |
September | 446.67 | 21.72 | 25.00 | 21.78 | 6.17 | 21.76 |
October | 502.00 | 20.76 | 158.33 | 20.57 | 158.33 | 20.45 |
November | 489.00 | 20.05 | 389.67 | 19.94 | 389.67 | 19.89 |
December | 497.00 | 19.74 | 497.00 | 19.74 | 497.00 | 19.74 |
Annual Sum or Average | 4846.67 | 20.74 | 3491.50 | 20.80 | 2656.67 | 20.59 |
Minimum of Months | 128.33 | 19.73 | 25.00 | 19.73 | 0.00 | 19.73 |
Maximum of Months | 514.00 | 22.75 | 502.00 | 23.69 | 502.00 | 23.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.50 | 427.00 | 19.50 | 427.00 | 19.50 |
February | 385.00 | 19.81 | 348.83 | 19.74 | 348.83 | 19.72 |
March | 421.33 | 20.54 | 297.00 | 20.38 | 294.83 | 20.31 |
April | 340.83 | 21.10 | 155.00 | 21.09 | 118.33 | 20.89 |
May | 243.33 | 22.02 | 147.50 | 22.94 | 9.17 | 22.98 |
June | 170.17 | 22.69 | 229.50 | 23.59 | 24.50 | 23.75 |
July | 142.00 | 23.20 | 288.50 | 23.89 | 47.83 | 24.03 |
August | 218.67 | 22.18 | 193.33 | 23.10 | 16.00 | 23.24 |
September | 311.50 | 21.65 | 69.00 | 22.09 | 6.67 | 22.10 |
October | 406.50 | 20.88 | 141.50 | 20.78 | 128.00 | 20.63 |
November | 417.00 | 19.99 | 311.67 | 19.83 | 311.67 | 19.76 |
December | 422.00 | 19.52 | 419.50 | 19.51 | 419.50 | 19.51 |
Annual Sum or Average | 3905.33 | 20.73 | 3028.33 | 20.93 | 2152.33 | 20.70 |
Minimum of Months | 142.00 | 19.50 | 69.00 | 19.50 | 6.67 | 19.50 |
Maximum of Months | 427.00 | 23.20 | 427.00 | 23.89 | 427.00 | 24.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 468.17 | 19.99 | 403.17 | 19.87 | 392.83 | 19.79 |
February | 378.67 | 20.42 | 310.17 | 20.37 | 276.17 | 20.22 |
March | 417.50 | 20.96 | 313.67 | 21.04 | 260.33 | 20.90 |
April | 356.17 | 21.30 | 203.00 | 21.51 | 128.50 | 21.32 |
May | 260.33 | 22.03 | 192.00 | 22.86 | 19.50 | 22.81 |
June | 202.67 | 22.20 | 247.33 | 23.28 | 8.67 | 23.33 |
July | 157.83 | 22.87 | 333.00 | 23.81 | 32.33 | 23.94 |
August | 225.17 | 22.48 | 273.50 | 23.43 | 24.33 | 23.57 |
September | 311.67 | 22.10 | 168.00 | 22.93 | 24.00 | 23.07 |
October | 426.83 | 21.33 | 177.00 | 21.56 | 115.50 | 21.46 |
November | 440.00 | 20.41 | 301.50 | 20.34 | 270.33 | 20.19 |
December | 476.67 | 20.03 | 420.50 | 19.91 | 420.50 | 19.86 |
Annual Sum or Average | 4121.67 | 21.07 | 3342.83 | 21.42 | 1973.00 | 21.18 |
Minimum of Months | 157.83 | 19.99 | 168.00 | 19.87 | 8.67 | 19.79 |
Maximum of Months | 476.67 | 22.87 | 420.50 | 23.81 | 420.50 | 23.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.81 | 479.50 | 19.78 | 479.50 | 19.77 |
February | 446.67 | 20.15 | 375.83 | 20.04 | 375.83 | 20.01 |
March | 483.50 | 20.60 | 337.33 | 20.53 | 320.00 | 20.44 |
April | 419.67 | 21.10 | 190.00 | 21.16 | 142.00 | 21.01 |
May | 324.83 | 22.01 | 170.50 | 22.75 | 35.33 | 22.81 |
June | 243.83 | 22.17 | 229.33 | 23.15 | 30.83 | 23.24 |
July | 200.83 | 22.96 | 314.83 | 23.77 | 67.50 | 23.93 |
August | 285.83 | 22.17 | 221.83 | 23.02 | 36.50 | 23.16 |
September | 389.33 | 21.63 | 76.33 | 22.06 | 7.00 | 22.11 |
October | 467.50 | 20.87 | 145.83 | 20.84 | 121.67 | 20.70 |
November | 489.00 | 20.25 | 335.67 | 20.08 | 335.67 | 20.00 |
December | 497.00 | 19.82 | 483.83 | 19.80 | 483.83 | 19.80 |
Annual Sum or Average | 4750.00 | 20.88 | 3360.83 | 21.06 | 2435.67 | 20.88 |
Minimum of Months | 200.83 | 19.81 | 76.33 | 19.78 | 7.00 | 19.77 |
Maximum of Months | 502.00 | 22.96 | 483.83 | 23.77 | 483.83 | 23.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.65 | 502.00 | 19.65 | 502.00 | 19.65 |
February | 454.00 | 19.77 | 445.83 | 19.76 | 445.83 | 19.76 |
March | 514.00 | 20.10 | 467.83 | 20.06 | 467.83 | 20.05 |
April | 485.00 | 20.43 | 301.17 | 20.25 | 301.17 | 20.17 |
May | 410.50 | 21.44 | 141.83 | 21.61 | 70.67 | 21.44 |
June | 285.83 | 21.79 | 158.00 | 22.47 | 9.67 | 22.44 |
July | 225.67 | 22.11 | 236.00 | 23.00 | 20.83 | 23.07 |
August | 366.50 | 21.60 | 110.67 | 22.05 | 3.50 | 22.04 |
September | 473.00 | 21.12 | 78.17 | 21.03 | 71.67 | 20.94 |
October | 502.00 | 20.24 | 302.17 | 20.04 | 302.17 | 19.95 |
November | 489.00 | 19.80 | 442.00 | 19.74 | 442.00 | 19.72 |
December | 497.00 | 19.64 | 497.00 | 19.64 | 497.00 | 19.64 |
Annual Sum or Average | 5204.50 | 20.49 | 3682.67 | 20.45 | 3134.33 | 20.29 |
Minimum of Months | 225.67 | 19.64 | 78.17 | 19.64 | 3.50 | 19.64 |
Maximum of Months | 514.00 | 22.11 | 502.00 | 23.00 | 502.00 | 23.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.65 | 502.00 | 19.65 | 502.00 | 19.65 |
February | 454.00 | 19.80 | 419.33 | 19.75 | 419.33 | 19.74 |
March | 508.17 | 20.35 | 389.83 | 20.19 | 389.83 | 20.13 |
April | 414.17 | 20.85 | 231.17 | 20.69 | 200.17 | 20.49 |
May | 294.50 | 21.69 | 197.83 | 22.51 | 31.67 | 22.40 |
June | 205.83 | 22.42 | 274.50 | 23.40 | 29.83 | 23.53 |
July | 177.67 | 22.97 | 348.67 | 23.75 | 56.33 | 23.88 |
August | 267.67 | 21.88 | 227.17 | 22.88 | 15.83 | 22.96 |
September | 386.83 | 21.33 | 113.83 | 21.62 | 46.83 | 21.52 |
October | 485.83 | 20.47 | 258.67 | 20.27 | 251.83 | 20.15 |
November | 489.00 | 19.82 | 413.33 | 19.72 | 413.33 | 19.68 |
December | 497.00 | 19.64 | 497.00 | 19.64 | 497.00 | 19.64 |
Annual Sum or Average | 4682.67 | 20.59 | 3873.33 | 20.79 | 2854.00 | 20.58 |
Minimum of Months | 177.67 | 19.64 | 113.83 | 19.64 | 15.83 | 19.64 |
Maximum of Months | 508.17 | 22.97 | 502.00 | 23.75 | 502.00 | 23.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 479.17 | 19.79 | 422.83 | 19.67 | 418.83 | 19.61 |
February | 405.00 | 20.13 | 337.67 | 20.03 | 313.83 | 19.90 |
March | 439.83 | 20.55 | 359.17 | 20.56 | 319.33 | 20.43 |
April | 380.83 | 20.82 | 275.83 | 20.91 | 213.83 | 20.72 |
May | 320.83 | 21.59 | 200.33 | 22.15 | 59.17 | 21.96 |
June | 258.67 | 21.77 | 215.00 | 22.74 | 17.67 | 22.75 |
July | 208.33 | 22.30 | 288.33 | 23.36 | 34.33 | 23.47 |
August | 287.50 | 21.94 | 222.67 | 22.89 | 30.17 | 23.02 |
September | 347.33 | 21.50 | 181.50 | 22.13 | 66.50 | 22.09 |
October | 434.00 | 20.61 | 283.83 | 20.73 | 225.67 | 20.56 |
November | 457.50 | 19.98 | 363.17 | 19.89 | 342.33 | 19.78 |
December | 488.50 | 19.81 | 448.83 | 19.71 | 448.83 | 19.68 |
Annual Sum or Average | 4507.50 | 20.71 | 3599.17 | 20.94 | 2490.50 | 20.71 |
Minimum of Months | 208.33 | 19.79 | 181.50 | 19.67 | 17.67 | 19.61 |
Maximum of Months | 488.50 | 22.30 | 448.83 | 23.36 | 448.83 | 23.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.69 | 485.50 | 19.66 | 485.50 | 19.66 |
February | 447.83 | 19.93 | 390.83 | 19.84 | 390.83 | 19.80 |
March | 488.50 | 20.37 | 387.67 | 20.30 | 372.67 | 20.23 |
April | 422.00 | 20.72 | 260.17 | 20.75 | 213.67 | 20.59 |
May | 350.67 | 21.76 | 198.67 | 22.33 | 76.17 | 22.28 |
June | 278.33 | 22.00 | 219.83 | 22.89 | 44.67 | 22.98 |
July | 240.33 | 22.72 | 292.67 | 23.55 | 78.83 | 23.72 |
August | 320.83 | 21.95 | 195.50 | 22.74 | 42.17 | 22.90 |
September | 402.33 | 21.33 | 106.67 | 21.64 | 47.17 | 21.61 |
October | 471.33 | 20.47 | 248.83 | 20.34 | 228.33 | 20.20 |
November | 489.00 | 19.92 | 395.67 | 19.79 | 395.67 | 19.75 |
December | 497.00 | 19.69 | 493.00 | 19.69 | 493.00 | 19.68 |
Annual Sum or Average | 4910.17 | 20.67 | 3675.00 | 20.81 | 2868.67 | 20.64 |
Minimum of Months | 240.33 | 19.69 | 106.67 | 19.66 | 42.17 | 19.66 |
Maximum of Months | 502.00 | 22.72 | 493.00 | 23.55 | 493.00 | 23.72 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 23.67 | 29.02 | 293.17 | 27.73 | 13.17 | 27.85 |
February | 21.50 | 32.58 | 334.17 | 27.68 | 21.50 | 27.96 |
March | 15.17 | 28.86 | 502.83 | 27.11 | 15.17 | 27.16 |
April | 35.17 | 27.00 | 485.00 | 27.00 | 35.17 | 27.00 |
May | 68.83 | 27.00 | 508.00 | 27.00 | 68.83 | 27.00 |
June | 182.67 | 27.00 | 496.00 | 27.00 | 182.67 | 27.00 |
July | 326.33 | 27.00 | 497.00 | 27.00 | 326.33 | 27.00 |
August | 346.00 | 27.00 | 514.00 | 27.00 | 346.00 | 27.00 |
September | 48.50 | 27.00 | 485.00 | 27.00 | 48.50 | 27.00 |
October | 16.67 | 27.00 | 502.00 | 27.00 | 16.67 | 27.00 |
November | 1.50 | 27.00 | 477.83 | 27.00 | 1.50 | 27.00 |
December | 45.83 | 40.01 | 466.17 | 29.33 | 45.83 | 30.21 |
Annual Sum or Average | 1131.83 | 27.70 | 5561.17 | 27.26 | 1121.33 | 27.32 |
Minimum of Months | 1.50 | 27.00 | 293.17 | 27.00 | 1.50 | 27.00 |
Maximum of Months | 346.00 | 40.01 | 514.00 | 29.33 | 346.00 | 30.21 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 102.00 | 26.49 | 134.00 | 27.12 | 4.50 | 27.18 |
February | 55.33 | 28.55 | 203.83 | 27.69 | 17.17 | 27.96 |
March | 9.00 | 29.32 | 356.17 | 27.12 | 8.67 | 27.17 |
April | 12.83 | 27.00 | 463.17 | 27.00 | 12.83 | 27.00 |
May | 38.50 | 27.00 | 508.00 | 27.00 | 38.50 | 27.00 |
June | 93.83 | 27.00 | 496.00 | 27.00 | 93.83 | 27.00 |
July | 143.83 | 27.00 | 497.00 | 27.00 | 143.83 | 27.00 |
August | 103.83 | 27.00 | 514.00 | 27.00 | 103.83 | 27.00 |
September | 22.67 | 27.00 | 485.00 | 27.00 | 22.67 | 27.00 |
October | 8.67 | 27.00 | 493.67 | 27.00 | 8.67 | 27.00 |
November | 13.17 | 27.00 | 325.50 | 27.00 | 0.00 | 27.00 |
December | 72.67 | 33.94 | 245.83 | 30.17 | 44.67 | 31.17 |
Annual Sum or Average | 676.33 | 27.83 | 4722.17 | 27.23 | 499.17 | 27.32 |
Minimum of Months | 8.67 | 26.49 | 134.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 143.83 | 33.94 | 514.00 | 30.17 | 143.83 | 31.17 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 243.83 | 25.29 | 78.17 | 25.33 | 33.33 | 25.12 |
February | 110.00 | 27.03 | 113.17 | 27.22 | 0.67 | 27.24 |
March | 65.67 | 27.00 | 227.33 | 27.04 | 2.67 | 27.04 |
April | 33.67 | 27.00 | 357.00 | 27.00 | 11.67 | 27.00 |
May | 54.83 | 27.00 | 480.83 | 27.00 | 54.83 | 27.00 |
June | 118.17 | 27.00 | 491.67 | 27.00 | 118.17 | 27.00 |
July | 162.67 | 27.00 | 497.00 | 27.00 | 162.67 | 27.00 |
August | 115.17 | 27.00 | 514.00 | 27.00 | 115.17 | 27.00 |
September | 23.33 | 27.00 | 477.00 | 27.00 | 23.33 | 27.00 |
October | 26.00 | 27.00 | 399.67 | 27.00 | 6.17 | 27.00 |
November | 90.00 | 27.00 | 208.83 | 27.00 | 0.00 | 27.00 |
December | 137.17 | 29.91 | 136.50 | 29.92 | 43.67 | 30.78 |
Annual Sum or Average | 1180.50 | 26.99 | 3981.17 | 27.06 | 572.33 | 27.10 |
Minimum of Months | 23.33 | 25.29 | 78.17 | 25.33 | 0.00 | 25.12 |
Maximum of Months | 243.83 | 29.91 | 514.00 | 29.92 | 162.67 | 30.78 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 87.33 | 27.18 | 502.00 | 27.14 | 87.33 | 27.14 |
February | 0.00 | 0.00 | 454.00 | 24.66 | 0.00 | 24.66 |
March | 240.83 | 25.83 | 514.00 | 25.70 | 240.83 | 25.73 |
April | 205.00 | 25.60 | 485.00 | 24.88 | 205.00 | 25.05 |
May | 486.17 | 27.10 | 508.00 | 27.10 | 486.17 | 27.10 |
June | 276.00 | 26.78 | 495.17 | 26.19 | 276.00 | 26.34 |
July | 494.00 | 26.68 | 497.00 | 26.67 | 494.00 | 26.68 |
August | 495.17 | 26.50 | 514.00 | 26.43 | 495.17 | 26.46 |
September | 485.00 | 27.04 | 485.00 | 27.04 | 485.00 | 27.04 |
October | 14.83 | 26.85 | 499.17 | 24.74 | 14.83 | 24.80 |
November | 418.33 | 25.84 | 488.17 | 25.78 | 418.33 | 25.80 |
December | 134.00 | 25.20 | 497.00 | 24.56 | 134.00 | 24.67 |
Annual Sum or Average | 3336.67 | 26.50 | 5938.50 | 26.07 | 3336.67 | 26.18 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 24.56 | 0.00 | 24.66 |
Maximum of Months | 495.17 | 27.18 | 514.00 | 27.14 | 495.17 | 27.14 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.36984 | 10.64051 | 0.60755 | 13.44050 |
February | 454.00000 | 27.26763 | 11.18830 | 0.66298 | 15.18553 |
March | 514.00000 | 27.05550 | 14.55886 | 0.72794 | 16.54835 |
April | 485.00000 | 27.00000 | 17.98058 | 0.83566 | 19.92609 |
May | 508.00000 | 27.00007 | 29.93166 | 0.24438 | 6.66691 |
June | 496.00000 | 27.00014 | 36.13196 | 0.35204 | 7.90488 |
July | 497.00000 | 27.00004 | 38.21768 | 0.44747 | 9.35941 |
August | 514.00000 | 27.00029 | 36.95803 | 0.45483 | 9.50845 |
September | 485.00000 | 27.00007 | 34.10995 | 0.24289 | 6.52824 |
October | 502.00000 | 27.00000 | 26.98581 | 0.82485 | 19.53092 |
November | 489.00000 | 27.00000 | 17.33985 | 0.73578 | 16.64400 |
December | 497.00000 | 28.19968 | 11.31934 | 0.86911 | 21.92483 |
Annual Sum or Average | 5943.00000 | 27.15686 | 23.88311 | 0.58287 | 13.57298 |
Minimum of Months | 454.00000 | 27.00000 | 10.64051 | 0.24289 | 6.52824 |
Maximum of Months | 514.00000 | 28.19968 | 38.21768 | 0.86911 | 21.92483 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.04114 | 10.58770 | 0.45371 | 10.22643 |
February | 454.00000 | 27.20500 | 11.18086 | 0.55193 | 12.18070 |
March | 514.00000 | 27.04252 | 14.55579 | 0.62054 | 13.56778 |
April | 485.00000 | 27.00000 | 17.97572 | 0.71836 | 16.16714 |
May | 508.00000 | 27.00007 | 29.93497 | 0.16444 | 6.13356 |
June | 496.00000 | 27.00015 | 36.17374 | 0.26751 | 6.92572 |
July | 497.00000 | 27.00005 | 38.27143 | 0.33378 | 7.60722 |
August | 514.00000 | 27.00029 | 37.08073 | 0.30300 | 7.22669 |
September | 485.00000 | 27.00007 | 34.13490 | 0.14324 | 5.79528 |
October | 502.00000 | 27.00000 | 26.98064 | 0.73782 | 16.70536 |
November | 489.00000 | 27.00000 | 17.33479 | 0.60017 | 12.95684 |
December | 497.00000 | 28.01537 | 11.35158 | 0.69572 | 18.03604 |
Annual Sum or Average | 5943.00000 | 27.10778 | 23.90017 | 0.46486 | 11.10912 |
Minimum of Months | 454.00000 | 27.00000 | 10.58770 | 0.14324 | 5.79528 |
Maximum of Months | 514.00000 | 28.01537 | 38.27143 | 0.73782 | 18.03604 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.19811 | 10.64929 | 0.21596 | 8.55566 |
February | 454.00000 | 27.11698 | 11.17837 | 0.44997 | 9.82509 |
March | 514.00000 | 27.02297 | 14.56026 | 0.52621 | 11.33537 |
April | 485.00000 | 27.00000 | 17.97936 | 0.63871 | 14.13607 |
May | 508.00000 | 27.00102 | 29.94051 | 0.10874 | 6.31688 |
June | 496.00000 | 27.00015 | 36.19008 | 0.24053 | 7.02928 |
July | 497.00000 | 27.00006 | 38.28034 | 0.31395 | 7.65208 |
August | 514.00000 | 27.00024 | 37.26115 | 0.26571 | 7.06660 |
September | 485.00000 | 27.00059 | 34.18665 | 0.05737 | 5.74909 |
October | 502.00000 | 27.00012 | 26.99153 | 0.64120 | 14.05439 |
November | 489.00000 | 27.00000 | 17.34151 | 0.50378 | 10.86138 |
December | 497.00000 | 27.80676 | 11.39698 | 0.56858 | 14.73616 |
Annual Sum or Average | 5943.00000 | 27.01084 | 23.93355 | 0.37670 | 9.76736 |
Minimum of Months | 454.00000 | 26.19811 | 10.64929 | 0.05737 | 5.74909 |
Maximum of Months | 514.00000 | 27.80676 | 38.28034 | 0.64120 | 14.73616 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.13133 | 29.98109 | 0.97134 | 25.00455 |
February | 454.00000 | 24.65727 | 28.10988 | 0.65020 | 13.93684 |
March | 514.00000 | 25.63849 | 26.85362 | 0.93508 | 23.63958 |
April | 485.00000 | 24.57921 | 24.97569 | 0.92901 | 23.99250 |
May | 508.00000 | 27.09535 | 32.46237 | 0.52282 | 10.84859 |
June | 496.00000 | 25.84793 | 41.65762 | 0.45332 | 11.68321 |
July | 497.00000 | 26.65984 | 44.86360 | 0.94907 | 24.83912 |
August | 514.00000 | 26.37274 | 44.52089 | 1.04013 | 29.79253 |
September | 485.00000 | 27.04160 | 33.88777 | 0.57608 | 12.12101 |
October | 502.00000 | 24.65984 | 31.38450 | 0.76390 | 17.51990 |
November | 489.00000 | 25.73002 | 27.52842 | 1.00815 | 26.63222 |
December | 497.00000 | 24.38863 | 28.20035 | 0.88203 | 21.66570 |
Annual Sum or Average | 5943.00000 | 25.82896 | 32.93453 | 0.80851 | 20.20794 |
Minimum of Months | 454.00000 | 24.38863 | 24.97569 | 0.45332 | 10.84859 |
Maximum of Months | 514.00000 | 27.13133 | 44.86360 | 1.04013 | 29.79253 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.92092 | 10.48812 | -0.3179 | 7.84501 |
February | 454.00000 | 22.62780 | 11.75788 | -0.1441 | 6.51084 |
March | 514.00000 | 23.35506 | 15.32044 | 0.04708 | 5.82471 |
April | 485.00000 | 24.11665 | 17.33627 | 0.23828 | 6.49631 |
May | 508.00000 | 24.24726 | 31.51348 | -0.4921 | 11.21344 |
June | 496.00000 | 24.36920 | 42.03017 | -0.3637 | 8.57495 |
July | 497.00000 | 24.58793 | 46.67681 | -0.2487 | 7.56997 |
August | 514.00000 | 24.42829 | 46.63371 | -0.2858 | 7.68588 |
September | 485.00000 | 24.26043 | 36.53136 | -0.4311 | 10.30604 |
October | 502.00000 | 24.30562 | 27.74394 | 0.36990 | 8.45144 |
November | 489.00000 | 24.14875 | 17.88276 | 0.25481 | 6.95440 |
December | 497.00000 | 22.59102 | 11.65812 | -0.1432 | 6.43151 |
Annual Sum or Average | 5943.00000 | 23.75293 | 26.43341 | -0.1272 | 7.83095 |
Minimum of Months | 454.00000 | 21.92092 | 10.48812 | -0.4921 | 5.82471 |
Maximum of Months | 514.00000 | 24.58793 | 46.67681 | 0.36990 | 11.21344 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.71395 | 11.23762 | -0.1819 | 6.99241 |
February | 454.00000 | 23.32027 | 12.84797 | -0.0164 | 5.73248 |
March | 514.00000 | 23.74501 | 15.80951 | 0.12852 | 5.82622 |
April | 485.00000 | 24.15946 | 17.76294 | 0.26650 | 6.68477 |
May | 508.00000 | 24.22383 | 32.20920 | -0.4708 | 10.43627 |
June | 496.00000 | 24.21027 | 45.17968 | -0.3608 | 8.21996 |
July | 497.00000 | 24.30701 | 51.45448 | -0.2684 | 6.92489 |
August | 514.00000 | 24.25480 | 50.95771 | -0.2831 | 7.06478 |
September | 485.00000 | 24.21156 | 38.16489 | -0.4375 | 9.60239 |
October | 502.00000 | 24.11657 | 28.39319 | 0.32183 | 7.39477 |
November | 489.00000 | 24.06091 | 18.99598 | 0.22626 | 6.46338 |
December | 497.00000 | 23.35251 | 12.50456 | -0.0079 | 5.84496 |
Annual Sum or Average | 5943.00000 | 23.89277 | 28.10349 | -0.0916 | 7.27513 |
Minimum of Months | 454.00000 | 22.71395 | 11.23762 | -0.4708 | 5.73248 |
Maximum of Months | 514.00000 | 24.30701 | 51.45448 | 0.32183 | 10.43627 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.56079 | 11.66124 | -0.4716 | 12.18295 |
February | 454.00000 | 22.16632 | 13.27850 | -0.3084 | 8.87031 |
March | 514.00000 | 22.91201 | 16.52511 | -0.0933 | 6.69067 |
April | 485.00000 | 23.53937 | 19.11617 | 0.09181 | 5.73927 |
May | 508.00000 | 24.03595 | 32.88213 | -0.5611 | 12.72577 |
June | 496.00000 | 24.04564 | 45.96494 | -0.4465 | 9.74847 |
July | 497.00000 | 24.18181 | 52.31758 | -0.3546 | 8.02716 |
August | 514.00000 | 24.03322 | 52.20022 | -0.4083 | 8.96847 |
September | 485.00000 | 23.90974 | 39.32975 | -0.5682 | 12.40557 |
October | 502.00000 | 23.52123 | 30.25252 | 0.15822 | 6.09366 |
November | 489.00000 | 22.77817 | 20.54583 | -0.1082 | 7.24591 |
December | 497.00000 | 21.79963 | 12.99970 | -0.3986 | 10.42018 |
Annual Sum or Average | 5943.00000 | 23.21480 | 29.06824 | -0.2894 | 9.09684 |
Minimum of Months | 454.00000 | 21.56079 | 11.66124 | -0.5682 | 5.73927 |
Maximum of Months | 514.00000 | 24.18181 | 52.31758 | 0.15822 | 12.72577 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.17798 | 12.27685 | -0.8641 | 23.52500 |
February | 454.00000 | 20.46543 | 13.91678 | -0.7618 | 20.02376 |
March | 514.00000 | 21.00959 | 17.93779 | -0.5815 | 14.65188 |
April | 485.00000 | 21.78341 | 20.76622 | -0.3411 | 10.13543 |
May | 508.00000 | 23.13850 | 34.31171 | -0.8623 | 24.46676 |
June | 496.00000 | 23.48485 | 47.92262 | -0.6170 | 15.49381 |
July | 497.00000 | 23.72197 | 54.44605 | -0.4856 | 11.58551 |
August | 514.00000 | 23.44755 | 54.72189 | -0.5951 | 14.24142 |
September | 485.00000 | 22.62159 | 42.52833 | -1.0100 | 28.84431 |
October | 502.00000 | 21.39822 | 32.88610 | -0.3717 | 10.48347 |
November | 489.00000 | 20.67026 | 22.18259 | -0.6428 | 17.34361 |
December | 497.00000 | 20.21559 | 13.85321 | -0.8387 | 22.67614 |
Annual Sum or Average | 5943.00000 | 21.85723 | 30.79706 | -0.6634 | 17.75913 |
Minimum of Months | 454.00000 | 20.17798 | 12.27685 | -1.0100 | 10.13543 |
Maximum of Months | 514.00000 | 23.72197 | 54.72189 | -0.3411 | 28.84431 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.07989 | 10.80657 | -0.9369 | 25.37923 |
February | 454.00000 | 20.44113 | 12.65560 | -0.7756 | 19.25578 |
March | 514.00000 | 20.96475 | 16.45400 | -0.5712 | 13.49564 |
April | 485.00000 | 22.15976 | 18.68000 | -0.2114 | 7.56058 |
May | 508.00000 | 23.49347 | 32.19384 | -0.6842 | 17.95991 |
June | 496.00000 | 23.91484 | 45.05684 | -0.4050 | 9.70678 |
July | 497.00000 | 24.11986 | 51.37250 | -0.2728 | 7.41123 |
August | 514.00000 | 23.82922 | 51.49773 | -0.4028 | 9.50592 |
September | 485.00000 | 23.05550 | 39.72398 | -0.8168 | 21.59831 |
October | 502.00000 | 21.93307 | 30.01711 | -0.2039 | 7.00970 |
November | 489.00000 | 21.05060 | 20.05480 | -0.5111 | 12.12551 |
December | 497.00000 | 20.17311 | 12.65178 | -0.8570 | 22.55354 |
Annual Sum or Average | 5943.00000 | 22.11477 | 28.57509 | -0.5526 | 14.42475 |
Minimum of Months | 454.00000 | 20.07989 | 10.80657 | -0.9369 | 7.00970 |
Maximum of Months | 514.00000 | 24.11986 | 51.49773 | -0.2039 | 25.37923 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.06053 | 10.39595 | -0.9232 | 25.01707 |
February | 454.00000 | 20.55413 | 12.19982 | -0.7184 | 17.64587 |
March | 514.00000 | 21.20815 | 15.87207 | -0.4773 | 12.47675 |
April | 485.00000 | 22.22786 | 18.24853 | -0.1214 | 8.61673 |
May | 508.00000 | 23.27708 | 32.47677 | -0.6364 | 18.66112 |
June | 496.00000 | 23.61207 | 45.76133 | -0.3690 | 12.16031 |
July | 497.00000 | 23.73496 | 52.32551 | -0.2615 | 9.73970 |
August | 514.00000 | 23.29131 | 53.04660 | -0.4675 | 13.99164 |
September | 485.00000 | 22.64739 | 40.44603 | -0.8481 | 24.89617 |
October | 502.00000 | 21.65400 | 30.05165 | -0.2335 | 7.93512 |
November | 489.00000 | 20.87736 | 19.94680 | -0.5396 | 12.63259 |
December | 497.00000 | 20.12486 | 12.28585 | -0.8684 | 23.01135 |
Annual Sum or Average | 5943.00000 | 21.95073 | 28.73904 | -0.5375 | 15.54395 |
Minimum of Months | 454.00000 | 20.06053 | 10.39595 | -0.9232 | 7.93512 |
Maximum of Months | 514.00000 | 23.73496 | 53.04660 | -0.1214 | 25.01707 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.57044 | 10.27968 | -0.7397 | 21.67504 |
February | 454.00000 | 21.36565 | 11.72223 | -0.4748 | 15.97074 |
March | 514.00000 | 21.77189 | 15.45894 | -0.3251 | 12.73176 |
April | 485.00000 | 22.39781 | 18.10648 | -0.0895 | 9.65159 |
May | 508.00000 | 23.25547 | 32.45172 | -0.6815 | 20.16134 |
June | 496.00000 | 23.46605 | 46.11883 | -0.4861 | 13.92718 |
July | 497.00000 | 23.79219 | 52.21517 | -0.2967 | 10.21213 |
August | 514.00000 | 23.59889 | 52.05501 | -0.3728 | 12.31121 |
September | 485.00000 | 23.04615 | 39.52687 | -0.7067 | 22.57231 |
October | 502.00000 | 22.07420 | 29.41995 | -0.1234 | 9.71416 |
November | 489.00000 | 21.31636 | 19.58584 | -0.4190 | 13.01695 |
December | 497.00000 | 20.58237 | 12.24296 | -0.7193 | 19.92662 |
Annual Sum or Average | 5943.00000 | 22.27820 | 28.41646 | -0.4528 | 15.14435 |
Minimum of Months | 454.00000 | 20.57044 | 10.27968 | -0.7397 | 9.65159 |
Maximum of Months | 514.00000 | 23.79219 | 52.21517 | -0.0895 | 22.57231 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.42371 | 10.06276 | -0.7747 | 19.58743 |
February | 454.00000 | 21.01901 | 11.73345 | -0.5533 | 13.67652 |
March | 514.00000 | 21.60464 | 15.39401 | -0.3176 | 9.99080 |
April | 485.00000 | 22.73076 | 17.57231 | 0.05033 | 8.23103 |
May | 508.00000 | 23.38238 | 32.08937 | -0.5393 | 17.27723 |
June | 496.00000 | 23.67586 | 45.45762 | -0.3036 | 11.12795 |
July | 497.00000 | 24.18444 | 50.91646 | -0.0412 | 8.54032 |
August | 514.00000 | 23.98772 | 50.71179 | -0.1387 | 9.03408 |
September | 485.00000 | 22.86979 | 39.72436 | -0.7220 | 21.09677 |
October | 502.00000 | 21.97656 | 29.41122 | -0.1134 | 7.16973 |
November | 489.00000 | 21.43992 | 19.29015 | -0.3524 | 9.04807 |
December | 497.00000 | 20.70619 | 11.82389 | -0.6309 | 14.74591 |
Annual Sum or Average | 5943.00000 | 22.34470 | 27.99485 | -0.3682 | 12.44120 |
Minimum of Months | 454.00000 | 20.42371 | 10.06276 | -0.7747 | 7.16973 |
Maximum of Months | 514.00000 | 24.18444 | 50.91646 | 0.05033 | 21.09677 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.73096 | 10.42118 | -1.1044 | 32.61795 |
February | 454.00000 | 19.90007 | 12.35232 | -0.9841 | 27.76831 |
March | 514.00000 | 20.32655 | 16.38354 | -0.7951 | 20.44553 |
April | 485.00000 | 20.92334 | 19.91733 | -0.5329 | 12.88377 |
May | 508.00000 | 22.61295 | 33.51352 | -0.9732 | 29.29401 |
June | 496.00000 | 23.27153 | 46.85909 | -0.6184 | 15.78365 |
July | 497.00000 | 23.59173 | 53.55295 | -0.4596 | 11.36175 |
August | 514.00000 | 22.84805 | 54.78122 | -0.7340 | 18.96659 |
September | 485.00000 | 21.86886 | 42.44678 | -1.2075 | 37.36086 |
October | 502.00000 | 20.76499 | 31.71885 | -0.5110 | 11.86056 |
November | 489.00000 | 20.05318 | 20.88291 | -0.8274 | 22.42605 |
December | 497.00000 | 19.73892 | 12.03975 | -1.0726 | 31.37565 |
Annual Sum or Average | 5943.00000 | 21.31599 | 29.72671 | -0.8169 | 22.62803 |
Minimum of Months | 454.00000 | 19.73096 | 10.42118 | -1.2075 | 11.36175 |
Maximum of Months | 514.00000 | 23.59173 | 54.78122 | -0.4596 | 37.36086 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.50444 | 10.16832 | -1.1357 | 34.29469 |
February | 385.00000 | 19.80813 | 11.91216 | -0.9618 | 27.25115 |
March | 433.00000 | 20.63326 | 15.47355 | -0.6752 | 17.85124 |
April | 410.00000 | 21.63128 | 18.85967 | -0.3018 | 11.52698 |
May | 430.00000 | 22.97987 | 32.67076 | -0.7586 | 23.68896 |
June | 418.00000 | 23.40725 | 46.40230 | -0.4512 | 15.06633 |
July | 422.00000 | 23.65512 | 53.10977 | -0.3114 | 11.66482 |
August | 433.00000 | 22.97374 | 54.17830 | -0.5980 | 18.37116 |
September | 410.00000 | 22.19970 | 41.56999 | -1.0318 | 32.08686 |
October | 427.00000 | 21.04828 | 30.59675 | -0.4279 | 11.49400 |
November | 417.00000 | 19.99409 | 20.16648 | -0.8289 | 22.74183 |
December | 422.00000 | 19.51801 | 11.81006 | -1.1118 | 33.28161 |
Annual Sum or Average | 5034.00000 | 21.45746 | 29.03823 | -0.7146 | 21.56221 |
Minimum of Months | 385.00000 | 19.50444 | 10.16832 | -1.1357 | 11.49400 |
Maximum of Months | 433.00000 | 23.65512 | 54.17830 | -0.3018 | 34.29469 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.26445 | 10.06190 | -0.8387 | 25.86792 |
February | 454.00000 | 21.03443 | 11.43615 | -0.5647 | 19.46670 |
March | 514.00000 | 21.56767 | 15.22988 | -0.3917 | 15.28830 |
April | 485.00000 | 22.07556 | 18.58017 | -0.1772 | 11.71020 |
May | 508.00000 | 23.05589 | 32.79364 | -0.7490 | 23.16540 |
June | 496.00000 | 23.24291 | 46.83749 | -0.5655 | 16.78878 |
July | 497.00000 | 23.63670 | 53.21997 | -0.3598 | 12.31391 |
August | 514.00000 | 23.27924 | 53.31785 | -0.4888 | 16.08348 |
September | 485.00000 | 22.81652 | 40.16817 | -0.7809 | 26.31516 |
October | 502.00000 | 21.75859 | 29.82114 | -0.2071 | 11.73854 |
November | 489.00000 | 20.79680 | 20.08400 | -0.5754 | 17.87797 |
December | 497.00000 | 20.19067 | 11.77300 | -0.8635 | 25.28934 |
Annual Sum or Average | 5943.00000 | 21.98585 | 28.76543 | -0.5467 | 18.47722 |
Minimum of Months | 454.00000 | 20.19067 | 10.06190 | -0.8635 | 11.71020 |
Maximum of Months | 514.00000 | 23.63670 | 53.31785 | -0.1772 | 26.31516 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.81068 | 10.12009 | -1.0307 | 29.89344 |
February | 454.00000 | 20.20991 | 11.84543 | -0.8431 | 23.28828 |
March | 514.00000 | 20.80451 | 15.70574 | -0.6122 | 16.87313 |
April | 485.00000 | 21.50673 | 19.09654 | -0.3182 | 11.85217 |
May | 508.00000 | 22.75810 | 33.25005 | -0.7929 | 26.11511 |
June | 496.00000 | 23.04948 | 47.29659 | -0.5604 | 17.95554 |
July | 497.00000 | 23.50418 | 53.57673 | -0.3404 | 13.37049 |
August | 514.00000 | 22.86337 | 54.55500 | -0.5982 | 18.83084 |
September | 485.00000 | 22.06363 | 41.82839 | -1.0506 | 33.29758 |
October | 502.00000 | 21.08629 | 30.87994 | -0.3934 | 10.77889 |
November | 489.00000 | 20.24695 | 20.46778 | -0.7462 | 19.68472 |
December | 497.00000 | 19.81967 | 11.73960 | -0.9997 | 28.50749 |
Annual Sum or Average | 5943.00000 | 21.48896 | 29.35277 | -0.6891 | 20.83989 |
Minimum of Months | 454.00000 | 19.81068 | 10.12009 | -1.0506 | 10.77889 |
Maximum of Months | 514.00000 | 23.50418 | 54.55500 | -0.3182 | 33.29758 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.64637 | 10.83234 | -1.1976 | 36.52826 |
February | 454.00000 | 19.77260 | 12.66883 | -1.0892 | 32.22395 |
March | 514.00000 | 20.10459 | 16.92975 | -0.9206 | 25.30047 |
April | 485.00000 | 20.43447 | 20.55165 | -0.6981 | 18.03134 |
May | 508.00000 | 21.89921 | 34.84268 | -1.2138 | 39.34970 |
June | 496.00000 | 22.58031 | 49.05577 | -0.8228 | 23.53829 |
July | 497.00000 | 22.94679 | 56.22696 | -0.6406 | 17.16654 |
August | 514.00000 | 22.12638 | 57.69096 | -0.9535 | 27.51924 |
September | 485.00000 | 21.17934 | 44.23278 | -1.4736 | 49.81397 |
October | 502.00000 | 20.23901 | 33.04661 | -0.7033 | 18.12319 |
November | 489.00000 | 19.80256 | 21.36804 | -0.9690 | 28.02687 |
December | 497.00000 | 19.63799 | 12.54598 | -1.1747 | 35.51548 |
Annual Sum or Average | 5943.00000 | 20.87521 | 30.99701 | -0.9871 | 29.22291 |
Minimum of Months | 454.00000 | 19.63799 | 10.83234 | -1.4736 | 17.16654 |
Maximum of Months | 514.00000 | 22.94679 | 57.69096 | -0.6406 | 49.81397 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.65126 | 10.79896 | -1.1625 | 35.24073 |
February | 454.00000 | 19.80471 | 12.61300 | -1.0230 | 29.89448 |
March | 514.00000 | 20.38532 | 16.60547 | -0.7848 | 21.46648 |
April | 485.00000 | 21.30822 | 19.56254 | -0.4135 | 14.47135 |
May | 508.00000 | 22.72914 | 33.50084 | -0.8519 | 27.31938 |
June | 496.00000 | 23.26145 | 47.19185 | -0.4882 | 16.62831 |
July | 497.00000 | 23.55000 | 54.06407 | -0.3214 | 12.70967 |
August | 514.00000 | 22.80781 | 55.49125 | -0.6487 | 20.50146 |
September | 485.00000 | 21.86525 | 42.64882 | -1.1820 | 38.72861 |
October | 502.00000 | 20.58468 | 32.24811 | -0.5956 | 16.06449 |
November | 489.00000 | 19.81870 | 21.31847 | -0.9380 | 27.01299 |
December | 497.00000 | 19.64398 | 12.51402 | -1.1507 | 34.66113 |
Annual Sum or Average | 5943.00000 | 21.29783 | 30.03631 | -0.7947 | 24.49594 |
Minimum of Months | 454.00000 | 19.64398 | 10.79896 | -1.1820 | 12.70967 |
Maximum of Months | 514.00000 | 23.55000 | 55.49125 | -0.3214 | 38.72861 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.97823 | 10.64146 | -0.9749 | 30.47199 |
February | 454.00000 | 20.54697 | 12.07030 | -0.7392 | 24.53644 |
March | 514.00000 | 21.07825 | 16.00028 | -0.5684 | 19.19659 |
April | 485.00000 | 21.51828 | 19.32532 | -0.3552 | 15.33855 |
May | 508.00000 | 22.49340 | 33.85970 | -0.9487 | 30.89660 |
June | 496.00000 | 22.78272 | 48.49167 | -0.7075 | 22.35419 |
July | 497.00000 | 23.20930 | 55.27595 | -0.4818 | 16.53802 |
August | 514.00000 | 22.76208 | 55.60253 | -0.6528 | 22.05533 |
September | 485.00000 | 22.23755 | 41.72628 | -1.0158 | 35.55925 |
October | 502.00000 | 21.11441 | 31.29782 | -0.4211 | 16.04361 |
November | 489.00000 | 20.23523 | 20.90077 | -0.7732 | 23.71862 |
December | 497.00000 | 19.87797 | 12.42768 | -1.0108 | 30.45203 |
Annual Sum or Average | 5943.00000 | 21.49564 | 29.96283 | -0.7205 | 23.91299 |
Minimum of Months | 454.00000 | 19.87797 | 10.64146 | -1.0158 | 15.33855 |
Maximum of Months | 514.00000 | 23.20930 | 55.60253 | -0.3552 | 35.55925 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.68806 | 10.70499 | -1.1268 | 33.91022 |
February | 454.00000 | 19.98391 | 12.38805 | -0.9535 | 27.81356 |
March | 514.00000 | 20.54889 | 16.38827 | -0.7291 | 20.75477 |
April | 485.00000 | 21.15240 | 19.67612 | -0.4440 | 15.39838 |
May | 508.00000 | 22.46643 | 33.87003 | -0.9085 | 31.28044 |
June | 496.00000 | 22.82672 | 48.32453 | -0.6314 | 21.31316 |
July | 497.00000 | 23.28433 | 54.98799 | -0.4015 | 15.98715 |
August | 514.00000 | 22.58990 | 56.09658 | -0.6895 | 22.71191 |
September | 485.00000 | 21.76016 | 42.75214 | -1.1954 | 40.18006 |
October | 502.00000 | 20.67522 | 32.06717 | -0.5446 | 15.28251 |
November | 489.00000 | 19.92025 | 21.13421 | -0.8833 | 25.04720 |
December | 497.00000 | 19.69163 | 12.41340 | -1.0978 | 32.59475 |
Annual Sum or Average | 5943.00000 | 21.22767 | 30.22695 | -0.7989 | 25.15137 |
Minimum of Months | 454.00000 | 19.68806 | 10.70499 | -1.1954 | 15.28251 |
Maximum of Months | 514.00000 | 23.28433 | 56.09658 | -0.4015 | 40.18006 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.106025E+10 | 3510.23 | 31-JAN-06:06 | 119.26 | 0.473220E+10 | 0.00 | 0.579245E+10 | 0.72 | 4.50 | 07-JAN-21:10 | 0.00 | 0.00 |
February | 0.372380E+11 | 146645.02 | 08-FEB-17:53 | 199.34 | 0.167796E+12 | 0.00 | 0.205034E+12 | 1.34 | 6.54 | 08-FEB-17:53 | 0.00 | 0.00 |
March | 0.538954E+11 | 153103.61 | 31-MAR-14:02 | 611.14 | 0.253933E+12 | 0.00 | 0.307828E+12 | 3.90 | 6.63 | 31-MAR-14:02 | 0.00 | 0.00 |
April | 0.651158E+11 | 227124.93 | 23-APR-16:23 | 580.99 | 0.321431E+12 | 0.00 | 0.386546E+12 | 3.88 | 7.02 | 23-APR-19:03 | 0.00 | 0.00 |
May | 0.946965E+11 | 266365.59 | 18-MAY-10:20 | 285.71 | 0.558675E+12 | 0.00 | 0.653371E+12 | 2.03 | 7.01 | 18-MAY-09:15 | 0.00 | 0.00 |
June | 0.214462E+12 | 270625.37 | 29-JUN-04:14 | 473.58 | 0.131417E+13 | 0.00 | 0.152863E+13 | 3.76 | 7.11 | 08-JUN-16:10 | 0.00 | 0.00 |
July | 0.248117E+12 | 285243.63 | 05-JUL-10:20 | 660.86 | 0.152649E+13 | 0.00 | 0.177461E+13 | 4.95 | 7.15 | 21-JUL-04:12 | 0.00 | 0.00 |
August | 0.218746E+12 | 264132.68 | 22-AUG-12:20 | 657.21 | 0.132665E+13 | 0.00 | 0.154539E+13 | 4.83 | 7.11 | 31-AUG-04:13 | 0.00 | 0.00 |
September | 0.573792E+11 | 257268.03 | 07-SEP-14:30 | 239.90 | 0.309173E+12 | 0.00 | 0.366552E+12 | 1.64 | 7.01 | 07-SEP-14:10 | 0.00 | 0.00 |
October | 0.517641E+11 | 193581.45 | 26-OCT-13:20 | 250.87 | 0.248145E+12 | 0.00 | 0.299909E+12 | 1.57 | 6.99 | 26-OCT-13:20 | 0.00 | 0.00 |
November | 0.504076E+11 | 147875.80 | 21-NOV-06:14 | 666.02 | 0.241403E+12 | 0.00 | 0.291811E+12 | 4.42 | 6.55 | 20-NOV-03:34 | 0.00 | 0.00 |
December | 0.601031E+11 | 105890.38 | 06-DEC-05:10 | 653.98 | 0.287262E+12 | 0.00 | 0.347365E+12 | 4.21 | 4.85 | 17-DEC-00:15 | 0.00 | 0.00 |
Annual Sum or Average | 0.115298E+13 | 5398.86 | 0.655986E+13 | 0.00 | 0.771284E+13 | 3.11 | 0.00 | 0.00 | ||||
Minimum of Months | 0.106025E+10 | 3510.23 | 119.26 | 0.473220E+10 | 0.00 | 0.579245E+10 | 0.72 | 4.50 | 0.00 | 0.00 | ||
Maximum of Months | 0.248117E+12 | 285243.63 | 666.02 | 0.152649E+13 | 0.00 | 0.177461E+13 | 4.95 | 7.15 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 |
May | 0.834421E+10 | 187352.59 | 26-MAY-12:05 | 15.75 | 0.537525E+11 | 0.00 | 0.620967E+11 | 0.14 | 6.80 | 18-MAY-13:05 | 0.00 | 0.00 |
June | 0.365671E+11 | 270625.37 | 29-JUN-04:14 | 61.11 | 0.234313E+12 | 0.00 | 0.270881E+12 | 0.54 | 6.92 | 21-JUN-14:05 | 0.00 | 0.00 |
July | 0.678668E+11 | 285243.63 | 05-JUL-10:20 | 116.40 | 0.437298E+12 | 0.00 | 0.505165E+12 | 1.00 | 6.89 | 05-JUL-05:04 | 0.00 | 0.00 |
August | 0.520024E+11 | 231885.23 | 31-AUG-12:40 | 88.83 | 0.338257E+12 | 0.00 | 0.390259E+12 | 0.77 | 6.94 | 01-AUG-04:14 | 0.00 | 0.00 |
September | 0.279704E+10 | 178376.67 | 01-SEP-11:00 | 5.42 | 0.180825E+11 | 0.00 | 0.208796E+11 | 0.05 | 6.78 | 01-SEP-11:00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.167577E+12 | 287.52 | 0.108170E+13 | 0.00 | 0.124928E+13 | 0.21 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.678668E+11 | 285243.63 | 116.40 | 0.437298E+12 | 0.00 | 0.505165E+12 | 1.00 | 6.94 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 313699.73 | 23-JAN-06:30 | 21.03 | 21.01 | 2.85 |
February | 781527.11 | 29.87 | 54.37 | 21-FEB-14:08 | 715774.95 | 06-FEB-02:28 | 21.56 | 21.31 | 25.92 |
March | 814328.51 | 10.82 | 97.60 | 31-MAR-14:05 | 1069132.13 | 31-MAR-14:05 | 21.18 | 20.80 | 40.72 |
April | 0.467794E+09 | 56.29 | 27892.31 | 23-APR-14:26 | 1621607.65 | 23-APR-14:27 | 21.27 | 20.81 | 48.44 |
May | 0.703081E+10 | 209.29 | 27892.31 | 16-MAY-12:30 | 2066143.42 | 16-MAY-13:40 | 21.89 | 21.21 | 30.76 |
June | 0.221710E+11 | 461.41 | 27892.31 | 06-JUN-10:00 | 2026043.23 | 08-JUN-14:50 | 23.63 | 22.03 | 58.42 |
July | 0.323266E+11 | 563.47 | 27892.31 | 03-JUL-08:20 | 2129253.66 | 05-JUL-14:00 | 23.74 | 21.93 | 78.01 |
August | 0.240438E+11 | 509.82 | 27892.31 | 01-AUG-04:14 | 2008427.04 | 22-AUG-12:20 | 23.12 | 21.53 | 77.10 |
September | 0.301601E+10 | 162.88 | 27892.31 | 01-SEP-08:35 | 2050645.47 | 07-SEP-14:30 | 21.58 | 21.18 | 26.35 |
October | 0.308089E+09 | 155.86 | 9477.56 | 19-OCT-15:00 | 1404031.76 | 18-OCT-13:34 | 21.90 | 21.58 | 28.66 |
November | 61828819.44 | 18.27 | 5287.43 | 01-NOV-14:06 | 937668.30 | 01-NOV-14:06 | 21.16 | 20.78 | 42.80 |
December | 7175.43 | 0.51 | 12.16 | 26-DEC-06:40 | 435530.39 | 26-DEC-06:40 | 21.12 | 20.69 | 47.52 |
Annual Sum or Average | 0.894276E+11 | 2178.48 | 21.94 | 21.24 | 42.41 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 313699.73 | 21.03 | 20.69 | 2.85 | ||
Maximum of Months | 0.323266E+11 | 563.47 | 27892.31 | 2129253.66 | 23.74 | 22.03 | 78.01 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 21.03 | 21.03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 21.56 | 21.56 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 21.18 | 21.18 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 21.27 | 21.27 | 0.00 |
May | 0.116911E+10 | 11.92 | 27892.31 | 17-MAY-13:30 | 1711861.41 | 16-MAY-15:30 | 21.89 | 21.83 | 1.45 |
June | 0.771736E+10 | 77.15 | 27892.31 | 19-JUN-10:01 | 1878444.90 | 08-JUN-15:50 | 23.63 | 23.23 | 8.57 |
July | 0.137355E+11 | 136.92 | 27892.31 | 03-JUL-12:15 | 2129253.66 | 05-JUL-14:00 | 23.74 | 23.07 | 15.20 |
August | 0.933010E+10 | 93.12 | 27892.31 | 01-AUG-04:14 | 1724042.47 | 31-AUG-12:40 | 23.12 | 22.67 | 10.98 |
September | 0.443488E+09 | 4.42 | 27892.31 | 01-SEP-10:30 | 1489935.58 | 01-SEP-15:40 | 21.58 | 21.56 | 0.56 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 21.90 | 21.90 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 21.16 | 21.16 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 21.12 | 21.12 | 0.00 |
Annual Sum or Average | 0.323956E+11 | 323.53 | 21.94 | 21.80 | 3.10 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.03 | 21.03 | 0.00 | ||
Maximum of Months | 0.137355E+11 | 136.92 | 27892.31 | 2129253.66 | 23.74 | 23.23 | 15.20 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.164629E+13 | 0.00 | 698.57 | 3841106.31 | 02-JAN-04:01 | 0.00 | 37.38 | 78.79 | 3.68 | 0.00 | 0.14 | 0.88 | 02-JAN-04:01 |
February | 0.101537E+13 | 0.00 | 603.80 | 3458925.58 | 28-FEB-06:01 | 0.00 | 36.03 | 75.70 | 2.40 | 0.00 | 0.10 | 0.79 | 28-FEB-06:01 |
March | 0.672435E+12 | 0.00 | 586.98 | 3530184.95 | 31-MAR-04:01 | 0.00 | 31.08 | 68.80 | 1.32 | 0.00 | 0.06 | 0.81 | 31-MAR-04:01 |
April | 0.188653E+12 | 0.00 | 404.65 | 3581806.44 | 07-APR-04:01 | 0.00 | 24.74 | 51.37 | 0.38 | 0.00 | 0.02 | 0.82 | 07-APR-04:01 |
May | 0.292723E+11 | 0.00 | 162.52 | 3152227.31 | 01-MAY-05:01 | 0.00 | 22.59 | 32.20 | 0.06 | 0.00 | 0.00 | 0.72 | 01-MAY-05:01 |
June | 0.584273E+10 | 0.00 | 87.40 | 378596.41 | 10-JUN-05:01 | 0.00 | 20.43 | 25.89 | 0.01 | 0.00 | 0.00 | 0.09 | 10-JUN-05:01 |
July | 0.218617E+10 | 0.00 | 49.07 | 160465.17 | 10-JUL-05:01 | 0.00 | 20.28 | 23.26 | 0.00 | 0.00 | 0.00 | 0.04 | 10-JUL-05:01 |
August | 0.819376E+10 | 0.00 | 116.11 | 901814.53 | 19-AUG-05:01 | 0.00 | 20.53 | 27.56 | 0.02 | 0.00 | 0.00 | 0.21 | 19-AUG-05:01 |
September | 0.493372E+11 | 0.00 | 246.76 | 3143504.72 | 23-SEP-05:01 | 0.00 | 21.92 | 36.96 | 0.11 | 0.00 | 0.00 | 0.72 | 23-SEP-05:01 |
October | 0.184287E+12 | 0.00 | 435.44 | 3684137.74 | 06-OCT-04:01 | 0.00 | 24.85 | 51.51 | 0.38 | 0.00 | 0.02 | 0.85 | 06-OCT-04:01 |
November | 0.543033E+12 | 0.00 | 567.50 | 3676641.31 | 24-NOV-05:01 | 0.00 | 31.29 | 67.04 | 1.13 | 0.00 | 0.05 | 0.84 | 24-NOV-05:01 |
December | 0.142511E+13 | 0.00 | 682.45 | 3790532.22 | 26-DEC-04:01 | 0.00 | 36.68 | 77.52 | 3.07 | 0.00 | 0.12 | 0.87 | 26-DEC-04:01 |
Annual Sum or Average | 0.577001E+13 | 0.00 | 4641.25 | 0.00 | 27.27 | 51.25 | 1.04 | 0.00 | 0.04 | ||||
Minimum of Months | 0.218617E+10 | 0.00 | 49.07 | 160465.17 | 0.00 | 20.28 | 23.26 | 0.00 | 0.00 | 0.00 | 0.04 | ||
Maximum of Months | 0.164629E+13 | 0.00 | 698.57 | 3841106.31 | 0.00 | 37.38 | 78.79 | 3.68 | 0.00 | 0.14 | 0.88 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 288.56 | 0.00 | 0.17 | 288.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 | 02-JAN-04:30 | 0.48 | 02-JAN-04:30 | 0.00 | 0.00 | 0.00 |
February | 3610.96 | 0.00 | 2.35 | 3610.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 | 06-FEB-04:01 | 0.94 | 06-FEB-04:01 | 0.00 | 0.00 | 0.00 |
March | 278.72 | 0.00 | 0.20 | 278.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 | 26-MAR-11:09 | 0.85 | 26-MAR-11:09 | 0.00 | 0.00 | 0.00 |
April | 0.572825E+10 | 0.00 | 61.09 | 0.572825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 130055.91 | 23-APR-15:11 | 130055.91 | 23-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.459015E+11 | 0.00 | 236.19 | 0.450256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 155114.15 | 25-MAY-15:00 | 144036.71 | 18-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.104210E+12 | 0.00 | 377.17 | 0.846726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 232922.76 | 30-JUN-05:02 | 167855.29 | 29-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.140679E+12 | 0.00 | 441.98 | 0.110014E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 345221.92 | 05-JUL-10:32 | 159883.58 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.112835E+12 | 0.00 | 433.14 | 0.860685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 244247.05 | 31-AUG-12:40 | 165324.29 | 08-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.242210E+11 | 0.00 | 176.90 | 0.216531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 162304.66 | 01-SEP-11:00 | 150277.66 | 01-SEP-15:30 | 0.00 | 0.00 | 0.00 |
October | 0.398972E+10 | 0.00 | 43.96 | 0.398972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90498.14 | 19-OCT-15:00 | 90498.14 | 19-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.559479E+09 | 0.00 | 11.42 | 0.559479E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31145.94 | 01-NOV-14:53 | 31145.94 | 01-NOV-14:53 | 0.00 | 0.00 | 0.00 |
December | 1062893.78 | 0.00 | 0.34 | 1062893.78 | 0.00 | 0.00 | 0.00 | 0.00 | 3541.92 | 05-DEC-17:05 | 3541.92 | 05-DEC-17:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438125E+12 | 0.00 | 1784.91 | 0.357712E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 278.72 | 0.00 | 0.17 | 278.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 | 0.48 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.140679E+12 | 0.00 | 441.98 | 0.110014E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 345221.92 | 167855.29 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 79687.54 | 0.00 | 26.16 | 79687.54 | 0.00 | 0.00 | 0.00 | 0.00 | 6.61 | 01-JAN-10:01 | 6.61 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 |
February | 61724729.79 | 0.00 | 42.88 | 61724729.79 | 0.00 | 0.00 | 0.00 | 0.00 | 42371.69 | 28-FEB-12:01 | 42371.69 | 28-FEB-12:01 | 0.00 | 0.00 | 0.00 |
March | 0.470785E+10 | 0.00 | 90.42 | 0.470785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 587690.75 | 31-MAR-14:01 | 587690.75 | 31-MAR-14:01 | 0.00 | 0.00 | 0.00 |
April | 0.550520E+11 | 0.00 | 136.55 | 0.550520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1247381.17 | 23-APR-15:42 | 1247381.17 | 23-APR-15:42 | 0.00 | 0.00 | 0.00 |
May | 0.438669E+12 | 0.00 | 259.64 | 0.430534E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1513706.04 | 25-MAY-15:20 | 1408259.49 | 18-MAY-14:05 | 0.00 | 0.00 | 0.00 |
June | 0.953687E+12 | 0.00 | 378.04 | 0.772718E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2261485.18 | 30-JUN-04:01 | 1629983.59 | 29-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.118708E+13 | 0.00 | 412.50 | 0.937635E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2942040.52 | 05-JUL-10:40 | 1480876.72 | 21-JUL-15:30 | 0.00 | 0.00 | 0.00 |
August | 0.937522E+12 | 0.00 | 410.10 | 0.721937E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1955308.36 | 31-AUG-12:40 | 1465930.27 | 08-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.237851E+12 | 0.00 | 202.07 | 0.215535E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1533265.15 | 01-SEP-12:05 | 1396832.20 | 01-SEP-15:40 | 0.00 | 0.00 | 0.00 |
October | 0.481928E+11 | 0.00 | 128.52 | 0.481928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 865478.87 | 19-OCT-15:00 | 865478.87 | 19-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.596113E+10 | 0.00 | 86.41 | 0.596113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 493339.80 | 01-NOV-14:01 | 493339.80 | 01-NOV-14:01 | 0.00 | 0.00 | 0.00 |
December | 178120.37 | 0.00 | 52.16 | 178120.37 | 0.00 | 0.00 | 0.00 | 0.00 | 5.72 | 12-DEC-04:11 | 5.72 | 12-DEC-04:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.386878E+13 | 0.00 | 2225.43 | 0.319233E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 79687.54 | 0.00 | 26.16 | 79687.54 | 0.00 | 0.00 | 0.00 | 0.00 | 5.72 | 5.72 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.118708E+13 | 0.00 | 412.50 | 0.937635E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2942040.52 | 1629983.59 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 4814712.23 | 0.00 | 2.87 | 4814712.23 | 0.00 | 0.00 | 0.00 | 0.00 | 2831.93 | 24-JAN-06:04 | 2831.93 | 24-JAN-06:04 | 0.00 | 0.00 | 0.00 |
February | 7252520.35 | 0.00 | 6.67 | 7252520.35 | 0.00 | 0.00 | 0.00 | 0.00 | 6353.30 | 27-FEB-06:12 | 6353.30 | 27-FEB-06:12 | 0.00 | 0.00 | 0.00 |
March | 7324451.20 | 0.00 | 4.88 | 7324451.20 | 0.00 | 0.00 | 0.00 | 0.00 | 5454.29 | 15-MAR-05:12 | 5454.29 | 15-MAR-05:12 | 0.00 | 0.00 | 0.00 |
April | 0.485663E+10 | 0.00 | 58.29 | 0.485663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 164348.04 | 23-APR-15:31 | 164348.04 | 23-APR-15:31 | 0.00 | 0.00 | 0.00 |
May | 0.467508E+11 | 0.00 | 225.28 | 0.461067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 181602.21 | 25-MAY-15:00 | 172803.29 | 18-MAY-14:50 | 0.00 | 0.00 | 0.00 |
June | 0.102742E+12 | 0.00 | 362.87 | 0.849439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 335691.33 | 29-JUN-05:02 | 198531.29 | 30-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.128762E+12 | 0.00 | 398.01 | 0.104887E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 278746.12 | 05-JUL-05:01 | 190246.12 | 23-JUL-15:31 | 0.00 | 0.00 | 0.00 |
August | 0.973381E+11 | 0.00 | 395.69 | 0.775754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 216477.12 | 08-AUG-15:00 | 179577.67 | 08-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.214093E+11 | 0.00 | 166.85 | 0.197024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 169740.45 | 01-SEP-15:30 | 163382.33 | 01-SEP-15:30 | 0.00 | 0.00 | 0.00 |
October | 0.349811E+10 | 0.00 | 39.30 | 0.349811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78710.99 | 19-OCT-15:00 | 78710.99 | 19-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.463047E+09 | 0.00 | 21.33 | 0.463047E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25093.39 | 01-NOV-14:53 | 25093.39 | 01-NOV-14:53 | 0.00 | 0.00 | 0.00 |
December | 12223538.73 | 0.00 | 8.15 | 12223538.73 | 0.00 | 0.00 | 0.00 | 0.00 | 4197.05 | 11-DEC-06:12 | 4197.05 | 11-DEC-06:12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.405851E+12 | 0.00 | 1690.19 | 0.342065E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4814712.23 | 0.00 | 2.87 | 4814712.23 | 0.00 | 0.00 | 0.00 | 0.00 | 2831.93 | 2831.93 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.128762E+12 | 0.00 | 398.01 | 0.104887E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 335691.33 | 198531.29 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 19249109.70 | 0.00 | 0.74 | 19249109.70 | 0.00 | 0.00 | 0.00 | 0.00 | 61179.83 | 31-JAN-06:01 | 61179.83 | 31-JAN-06:01 | 0.00 | 0.00 | 0.00 |
February | 0.156135E+09 | 0.00 | 3.02 | 0.156135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56924.67 | 24-FEB-06:02 | 56924.67 | 24-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.120275E+10 | 0.00 | 22.67 | 0.120275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114495.45 | 27-MAR-04:56 | 114495.45 | 27-MAR-04:56 | 0.00 | 0.00 | 0.00 |
April | 0.742352E+10 | 0.00 | 111.00 | 0.742352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115256.54 | 03-APR-04:49 | 115256.54 | 03-APR-04:49 | 0.00 | 0.00 | 0.00 |
May | 0.320570E+11 | 0.00 | 268.30 | 0.302008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105668.57 | 26-MAY-04:11 | 71948.41 | 09-MAY-10:32 | 0.00 | 0.00 | 0.00 |
June | 0.605015E+11 | 0.00 | 353.37 | 0.444672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 171815.73 | 29-JUN-04:52 | 129788.40 | 30-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.765549E+11 | 0.00 | 379.83 | 0.530869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 207444.01 | 05-JUL-10:25 | 120252.11 | 03-JUL-03:25 | 0.00 | 0.00 | 0.00 |
August | 0.704768E+11 | 0.00 | 403.75 | 0.465001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 147905.02 | 27-AUG-14:31 | 129966.69 | 13-AUG-17:50 | 0.00 | 0.00 | 0.00 |
September | 0.265505E+11 | 0.00 | 248.97 | 0.225827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 134277.39 | 04-SEP-11:58 | 134277.39 | 04-SEP-11:58 | 0.00 | 0.00 | 0.00 |
October | 0.117722E+11 | 0.00 | 127.27 | 0.116014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 139903.78 | 25-OCT-03:25 | 139903.78 | 25-OCT-03:25 | 0.00 | 0.00 | 0.00 |
November | 0.440852E+10 | 0.00 | 78.59 | 0.425696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114346.49 | 30-NOV-05:49 | 114346.49 | 30-NOV-05:49 | 0.00 | 0.00 | 0.00 |
December | 0.121492E+09 | 0.00 | 5.63 | 0.121492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 110640.78 | 01-DEC-05:50 | 110640.78 | 01-DEC-05:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.291245E+12 | 0.00 | 2003.16 | 0.221619E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 19249109.70 | 0.00 | 0.74 | 19249109.70 | 0.00 | 0.00 | 0.00 | 0.00 | 56924.67 | 56924.67 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.765549E+11 | 0.00 | 403.75 | 0.530869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 207444.01 | 139903.78 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3383165.69 | 0.00 | 183.58 | 3383165.69 | 0.00 | 0.00 | 0.00 | 0.00 | 63.72 | 28-JAN-13:02 | 63.72 | 28-JAN-13:02 | 0.00 | 0.00 | 0.00 |
February | 0.158739E+12 | 0.00 | 415.12 | 0.158739E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 277305.49 | 14-FEB-10:01 | 277305.49 | 14-FEB-10:01 | 0.00 | 0.00 | 0.00 |
March | 0.222015E+12 | 0.00 | 653.48 | 0.222015E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 267717.00 | 31-MAR-23:17 | 267717.00 | 31-MAR-23:17 | 0.00 | 0.00 | 0.00 |
April | 0.223204E+12 | 0.00 | 719.72 | 0.223204E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 434430.17 | 23-APR-15:46 | 434430.17 | 23-APR-15:46 | 0.00 | 0.00 | 0.00 |
May | 0.224752E+11 | 0.00 | 323.14 | 0.224752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 219021.98 | 31-MAY-23:47 | 219021.98 | 31-MAY-23:47 | 0.00 | 0.00 | 0.00 |
June | 0.292250E+12 | 0.00 | 501.38 | 0.236831E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 564778.66 | 19-JUN-10:52 | 344780.65 | 15-JUN-12:53 | 0.00 | 0.00 | 0.00 |
July | 0.381050E+12 | 0.00 | 742.81 | 0.330387E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 569313.14 | 03-JUL-23:48 | 300840.35 | 05-JUL-11:05 | 0.00 | 0.00 | 0.00 |
August | 0.402103E+12 | 0.00 | 743.50 | 0.348310E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 596664.11 | 31-AUG-19:10 | 410511.41 | 20-AUG-12:33 | 0.00 | 0.00 | 0.00 |
September | 0.394863E+10 | 0.00 | 242.34 | 0.394863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 242164.60 | 30-SEP-23:53 | 242164.60 | 30-SEP-23:53 | 0.00 | 0.00 | 0.00 |
October | 0.169996E+12 | 0.00 | 438.54 | 0.169706E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 319211.33 | 21-OCT-14:07 | 319211.33 | 21-OCT-14:07 | 0.00 | 0.00 | 0.00 |
November | 0.201866E+12 | 0.00 | 718.57 | 0.201426E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 326964.90 | 01-NOV-00:22 | 326964.90 | 01-NOV-00:22 | 0.00 | 0.00 | 0.00 |
December | 0.258978E+12 | 0.00 | 744.00 | 0.258978E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 262395.00 | 25-DEC-08:00 | 262395.00 | 25-DEC-08:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233663E+13 | 0.00 | 6426.19 | 0.217602E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3383165.69 | 0.00 | 183.58 | 3383165.69 | 0.00 | 0.00 | 0.00 | 0.00 | 63.72 | 63.72 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.402103E+12 | 0.00 | 744.00 | 0.348310E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 596664.11 | 434430.17 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.297686E+10 | 0.939306E+09 | 600.44 | 0.297686E+10 | -0.0 | 0.00 | 1.00 | 07-JAN-00:01 | 0.00 | 01-JAN-00:55 | 8839.70 | 14-JAN-04:21 | 8839.70 | 14-JAN-04:21 | 0.00 | 26-JAN-16:37 | 2291.12 | 14-JAN-04:21 | 0.00 | 01-JAN-00:01 |
February | 0.815117E+10 | 0.235474E+10 | 627.50 | 0.815117E+10 | -0.0 | 0.00 | 1.00 | 02-FEB-08:61 | 0.00 | 01-FEB-18:51 | 13831.56 | 15-FEB-05:31 | 13831.56 | 15-FEB-05:31 | 0.00 | 02-FEB-08:61 | 3713.92 | 14-FEB-10:01 | 0.00 | 01-FEB-00:01 |
March | 0.155617E+11 | 0.413150E+10 | 733.00 | 0.155617E+11 | -0.0 | 0.00 | 1.00 | 05-MAR-08:21 | 0.00 | 05-MAR-02:21 | 14361.92 | 05-MAR-08:21 | 14361.92 | 05-MAR-08:21 | 0.00 | 27-MAR-18:04 | 3872.87 | 05-MAR-08:21 | 0.00 | 01-MAR-00:01 |
April | 0.213917E+11 | 0.552513E+10 | 720.00 | 0.213917E+11 | -0.0 | 0.00 | 1.00 | 01-APR-00:03 | 0.48 | 30-APR-24:00 | 10446.70 | 23-APR-18:12 | 10446.70 | 23-APR-18:12 | 0.00 | 15-APR-08:51 | 2981.99 | 23-APR-18:05 | 0.00 | 01-APR-00:03 |
May | 0.799389E+10 | 0.240760E+10 | 744.00 | 0.796483E+10 | 29061935.37 | 0.00 | 0.69 | 14-MAY-18:41 | 0.33 | 13-MAY-06:30 | 4563.23 | 31-MAY-23:51 | 4563.23 | 31-MAY-23:51 | 235.84 | 26-MAY-13:05 | 1413.91 | 25-MAY-18:40 | 0.00 | 01-MAY-00:10 |
June | 0.129604E+11 | 0.366220E+10 | 720.00 | 0.127937E+11 | 0.166700E+09 | 0.00 | 0.92 | 30-JUN-23:01 | 0.63 | 10-JUN-06:11 | 6782.81 | 30-JUN-23:01 | 6771.86 | 30-JUN-23:02 | 472.63 | 30-JUN-16:00 | 2083.97 | 29-JUN-16:00 | 0.00 | 01-JUN-00:01 |
July | 0.188705E+11 | 0.499322E+10 | 744.00 | 0.186351E+11 | 0.235467E+09 | 0.00 | 1.00 | 01-JUL-18:10 | 0.86 | 08-JUL-16:51 | 8708.06 | 31-JUL-24:00 | 8654.48 | 31-JUL-24:00 | 495.81 | 05-JUL-11:00 | 2378.03 | 21-JUL-16:00 | 0.00 | 01-JUL-00:01 |
August | 0.237184E+11 | 0.621847E+10 | 744.00 | 0.234656E+11 | 0.252779E+09 | 0.00 | 1.00 | 01-AUG-00:10 | 0.51 | 31-AUG-24:00 | 10090.44 | 25-AUG-18:20 | 10086.36 | 05-AUG-18:37 | 418.10 | 08-AUG-15:30 | 3069.62 | 08-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.742465E+10 | 0.223487E+10 | 720.00 | 0.738802E+10 | 36632472.39 | 0.00 | 0.69 | 09-SEP-17:53 | 0.32 | 23-SEP-06:55 | 4640.80 | 03-SEP-17:52 | 4637.36 | 03-SEP-18:00 | 229.92 | 18-SEP-16:00 | 1306.21 | 03-SEP-17:52 | 0.00 | 01-SEP-00:02 |
October | 0.116344E+11 | 0.330118E+10 | 744.00 | 0.116323E+11 | 2019335.09 | 0.00 | 0.86 | 31-OCT-23:57 | 0.50 | 30-OCT-06:02 | 5948.54 | 31-OCT-23:52 | 5948.54 | 31-OCT-23:52 | 64.82 | 02-OCT-14:02 | 1585.13 | 19-OCT-16:44 | 0.00 | 01-OCT-00:01 |
November | 0.153998E+11 | 0.408795E+10 | 720.00 | 0.153953E+11 | 4433217.30 | 0.00 | 1.00 | 09-NOV-15:51 | 0.72 | 25-NOV-07:01 | 7243.11 | 09-NOV-16:02 | 7243.11 | 09-NOV-16:02 | 172.20 | 21-NOV-12:00 | 1841.11 | 17-NOV-16:00 | 0.00 | 01-NOV-00:01 |
December | 0.172946E+11 | 0.441767E+10 | 650.50 | 0.172946E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-00:01 | 0.00 | 02-DEC-01:41 | 14838.87 | 20-DEC-11:01 | 14838.87 | 20-DEC-11:01 | 0.00 | 29-DEC-13:32 | 3987.56 | 20-DEC-11:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.163378E+12 | 0.442738E+11 | 8467.44 | 0.162651E+12 | 0.727092E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.297686E+10 | 0.939306E+09 | 600.44 | 0.297686E+10 | -0.0 | 0.00 | 0.69 | 0.00 | 4563.23 | 4563.23 | 0.00 | 1306.21 | 0.00 | |||||||
Maximum of Months | 0.237184E+11 | 0.621847E+10 | 744.00 | 0.234656E+11 | 0.252779E+09 | 0.00 | 1.00 | 0.86 | 14838.87 | 14838.87 | 495.81 | 3987.56 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.127309E+11 | 0.350585E+10 | 467.67 | 0.127309E+11 | -0.0 | 0.00 | 0.68 | 06-JAN-12:42 | 0.00 | 01-JAN-00:01 | 42699.05 | 06-JAN-12:42 | 42699.05 | 06-JAN-12:42 | 0.00 | 27-JAN-16:10 | 10275.42 | 06-JAN-12:42 | 0.00 | 01-JAN-00:01 |
February | 0.626017E+11 | 0.159072E+11 | 627.50 | 0.626017E+11 | -0.0 | 0.00 | 1.00 | 02-FEB-08:61 | 0.00 | 01-FEB-18:51 | 131398.12 | 17-FEB-09:21 | 131398.12 | 17-FEB-09:21 | 0.00 | 14-FEB-10:02 | 30225.92 | 17-FEB-09:21 | 0.00 | 01-FEB-00:01 |
March | 0.135406E+12 | 0.314302E+11 | 733.00 | 0.135406E+12 | -0.0 | 0.00 | 1.00 | 05-MAR-08:21 | 0.00 | 05-MAR-02:21 | 136134.98 | 16-MAR-04:41 | 136134.98 | 16-MAR-04:41 | 0.00 | 28-MAR-18:16 | 31438.74 | 05-MAR-08:21 | 0.00 | 01-MAR-00:01 |
April | 0.194487E+12 | 0.428693E+11 | 720.00 | 0.194487E+12 | -0.0 | 0.00 | 1.00 | 01-APR-00:03 | 0.36 | 30-APR-24:00 | 99360.65 | 23-APR-18:01 | 99360.65 | 23-APR-18:01 | 0.00 | 17-APR-08:24 | 24366.82 | 23-APR-17:59 | 0.00 | 01-APR-00:03 |
May | 0.709772E+11 | 0.184799E+11 | 744.00 | 0.706885E+11 | 0.288664E+09 | 0.00 | 0.69 | 25-MAY-18:50 | 0.20 | 01-MAY-06:05 | 44815.98 | 25-MAY-18:50 | 43563.50 | 25-MAY-18:50 | 2343.49 | 26-MAY-13:05 | 11911.38 | 25-MAY-18:40 | 0.00 | 01-MAY-00:10 |
June | 0.120915E+12 | 0.294600E+11 | 720.00 | 0.119255E+12 | 0.166005E+10 | 0.00 | 0.93 | 30-JUN-23:11 | 0.59 | 10-JUN-06:01 | 66190.55 | 30-JUN-23:11 | 66129.49 | 30-JUN-23:30 | 4719.08 | 30-JUN-16:00 | 17163.22 | 29-JUN-16:00 | 0.00 | 01-JUN-00:01 |
July | 0.177837E+12 | 0.405377E+11 | 744.00 | 0.175492E+12 | 0.234575E+10 | 0.00 | 1.00 | 01-JUL-18:11 | 0.82 | 08-JUL-16:51 | 82437.91 | 31-JUL-24:00 | 81970.89 | 31-JUL-24:00 | 4890.54 | 05-JUL-11:05 | 19511.20 | 21-JUL-16:00 | 0.00 | 01-JUL-00:01 |
August | 0.222468E+12 | 0.498419E+11 | 744.00 | 0.219958E+12 | 0.250956E+10 | 0.00 | 1.00 | 01-AUG-00:10 | 0.45 | 31-AUG-24:00 | 97320.42 | 25-AUG-18:20 | 96982.73 | 02-AUG-18:40 | 4181.68 | 08-AUG-15:30 | 25050.75 | 08-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.631021E+11 | 0.164847E+11 | 720.00 | 0.627402E+11 | 0.361918E+09 | 0.00 | 0.68 | 05-SEP-17:50 | 0.26 | 23-SEP-06:55 | 44018.27 | 05-SEP-17:42 | 44018.27 | 05-SEP-17:42 | 2271.38 | 18-SEP-16:00 | 10654.29 | 05-SEP-17:42 | 0.00 | 01-SEP-00:02 |
October | 0.998551E+11 | 0.247067E+11 | 744.00 | 0.998349E+11 | 20134204.68 | 0.00 | 0.83 | 18-OCT-16:50 | 0.37 | 30-OCT-06:02 | 56574.07 | 19-OCT-16:42 | 56574.07 | 19-OCT-16:42 | 641.68 | 02-OCT-14:02 | 13063.04 | 19-OCT-16:46 | 0.00 | 01-OCT-00:01 |
November | 0.127713E+12 | 0.299143E+11 | 720.00 | 0.127668E+12 | 44353476.18 | 0.00 | 0.98 | 09-NOV-16:20 | 0.55 | 27-NOV-04:03 | 67408.35 | 17-NOV-16:03 | 67408.35 | 17-NOV-16:03 | 1706.95 | 21-NOV-12:00 | 14837.09 | 17-NOV-16:10 | 0.00 | 01-NOV-00:01 |
December | 0.147129E+12 | 0.327502E+11 | 650.50 | 0.147129E+12 | -0.0 | 0.00 | 1.00 | 01-DEC-12:53 | 0.00 | 02-DEC-01:41 | 141692.18 | 20-DEC-11:01 | 141692.18 | 20-DEC-11:01 | 0.00 | 06-DEC-12:33 | 32686.90 | 20-DEC-11:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.143522E+13 | 0.335888E+12 | 8334.67 | 0.142799E+13 | 0.723044E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.127309E+11 | 0.350585E+10 | 467.67 | 0.127309E+11 | -0.0 | 0.00 | 0.68 | 0.00 | 42699.05 | 42699.05 | 0.00 | 10275.42 | 0.00 | |||||||
Maximum of Months | 0.222468E+12 | 0.498419E+11 | 744.00 | 0.219958E+12 | 0.250956E+10 | 0.00 | 1.00 | 0.82 | 141692.18 | 141692.18 | 4890.54 | 32686.90 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.551483E+09 | 0.178148E+09 | 229.68 | 0.551483E+09 | -0.0 | 0.00 | 0.39 | 20-JAN-16:25 | 0.00 | 01-JAN-00:01 | 2287.93 | 20-JAN-16:25 | 2287.93 | 20-JAN-16:25 | 0.00 | 20-JAN-16:30 | 699.05 | 20-JAN-16:30 | 0.00 | 01-JAN-00:01 |
February | 0.441808E+10 | 0.134133E+10 | 625.23 | 0.441808E+10 | -0.0 | 0.00 | 1.00 | 02-FEB-08:61 | 0.00 | 01-FEB-00:01 | 13239.78 | 14-FEB-10:01 | 13239.78 | 14-FEB-10:01 | 0.00 | 06-FEB-16:44 | 3549.49 | 14-FEB-10:01 | 0.00 | 01-FEB-00:01 |
March | 0.113937E+11 | 0.318527E+10 | 732.98 | 0.113937E+11 | -0.0 | 0.00 | 1.00 | 05-MAR-08:21 | 0.00 | 05-MAR-02:21 | 13617.15 | 16-MAR-04:41 | 13617.15 | 16-MAR-04:41 | 0.00 | 28-MAR-17:49 | 3652.17 | 16-MAR-04:41 | 0.00 | 01-MAR-00:01 |
April | 0.176721E+11 | 0.459914E+10 | 720.00 | 0.176721E+11 | -0.0 | 0.00 | 1.00 | 04-APR-12:32 | 0.15 | 30-APR-24:00 | 9808.42 | 23-APR-18:01 | 9808.42 | 23-APR-18:01 | 0.00 | 25-APR-14:40 | 2806.06 | 23-APR-17:52 | 0.00 | 01-APR-00:03 |
May | 0.622485E+10 | 0.191081E+10 | 743.05 | 0.619597E+10 | 28886356.12 | 0.00 | 0.70 | 25-MAY-18:40 | 0.00 | 01-MAY-06:05 | 4653.45 | 25-MAY-18:50 | 4528.84 | 25-MAY-18:50 | 236.59 | 26-MAY-13:05 | 1442.30 | 25-MAY-18:40 | 0.00 | 01-MAY-00:10 |
June | 0.116331E+11 | 0.334067E+10 | 720.00 | 0.114672E+11 | 0.165948E+09 | 0.00 | 0.91 | 30-JUN-23:01 | 0.40 | 04-JUN-05:30 | 6575.11 | 30-JUN-23:01 | 6563.94 | 30-JUN-23:02 | 473.57 | 30-JUN-16:00 | 2075.23 | 29-JUN-16:00 | 0.00 | 01-JUN-00:01 |
July | 0.174697E+11 | 0.469156E+10 | 744.00 | 0.172352E+11 | 0.234481E+09 | 0.00 | 1.00 | 01-JUL-18:35 | 0.72 | 10-JUL-06:10 | 8186.79 | 28-JUL-18:50 | 7991.61 | 31-JUL-23:50 | 489.42 | 05-JUL-11:05 | 2345.23 | 21-JUL-16:00 | 0.00 | 01-JUL-00:01 |
August | 0.217737E+11 | 0.566940E+10 | 744.00 | 0.215249E+11 | 0.248804E+09 | 0.00 | 1.00 | 01-AUG-00:10 | 0.41 | 31-AUG-24:00 | 9881.25 | 25-AUG-18:20 | 9794.04 | 02-AUG-18:40 | 418.88 | 08-AUG-15:30 | 2995.90 | 08-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.513994E+10 | 0.159025E+10 | 719.08 | 0.510419E+10 | 35749667.69 | 0.00 | 0.66 | 05-SEP-17:50 | 0.00 | 11-SEP-03:33 | 4409.70 | 05-SEP-17:42 | 4409.70 | 05-SEP-17:42 | 229.68 | 18-SEP-16:00 | 1255.83 | 01-SEP-17:30 | 0.00 | 01-SEP-00:02 |
October | 0.778680E+10 | 0.231359E+10 | 743.72 | 0.778484E+10 | 1968869.08 | 0.00 | 0.81 | 19-OCT-16:44 | 0.00 | 15-OCT-06:31 | 5709.40 | 19-OCT-16:42 | 5709.40 | 19-OCT-16:42 | 63.32 | 02-OCT-14:02 | 1543.49 | 19-OCT-16:45 | 0.00 | 01-OCT-00:01 |
November | 0.104566E+11 | 0.295788E+10 | 720.00 | 0.104522E+11 | 4382657.40 | 0.00 | 0.93 | 17-NOV-16:01 | 0.37 | 24-NOV-03:33 | 6505.99 | 17-NOV-16:03 | 6505.99 | 17-NOV-16:03 | 169.43 | 21-NOV-12:00 | 1695.44 | 17-NOV-16:10 | 0.00 | 01-NOV-00:01 |
December | 0.128602E+11 | 0.344542E+10 | 650.50 | 0.128602E+11 | -0.0 | 0.00 | 1.00 | 02-DEC-09:31 | 0.00 | 02-DEC-01:41 | 14372.78 | 20-DEC-11:01 | 14372.78 | 20-DEC-11:01 | 0.00 | 26-DEC-09:54 | 3872.88 | 20-DEC-11:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.127380E+12 | 0.352235E+11 | 8092.24 | 0.126660E+12 | 0.720221E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.551483E+09 | 0.178148E+09 | 229.68 | 0.551483E+09 | -0.0 | 0.00 | 0.39 | 0.00 | 2287.93 | 2287.93 | 0.00 | 699.05 | 0.00 | |||||||
Maximum of Months | 0.217737E+11 | 0.566940E+10 | 744.00 | 0.215249E+11 | 0.248804E+09 | 0.00 | 1.00 | 0.72 | 14372.78 | 14372.78 | 489.42 | 3872.88 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.94 | 0.00 | 152.94 | 0.01 | 1895.06 | 0.00 | 0.00 | 0.00 |
February | 234.93 | 0.00 | 234.93 | 3.18 | 1556.58 | 0.00 | 0.00 | 0.00 |
March | 289.04 | 0.00 | 289.04 | 10.76 | 1250.41 | 0.00 | 0.00 | 0.00 |
April | 378.91 | 2.96 | 375.95 | 93.57 | 766.79 | 0.00 | 0.00 | 0.00 |
May | 532.92 | 28.70 | 504.23 | 373.18 | 371.65 | 0.00 | 0.00 | 0.00 |
June | 594.75 | 65.38 | 529.37 | 558.15 | 255.52 | 0.00 | 0.00 | 0.00 |
July | 568.08 | 48.75 | 519.33 | 572.59 | 233.33 | 0.00 | 0.00 | 0.00 |
August | 431.48 | 7.41 | 424.07 | 375.14 | 286.19 | 0.00 | 0.00 | 0.00 |
September | 336.24 | 0.08 | 336.15 | 183.99 | 466.30 | 0.00 | 0.00 | 0.00 |
October | 233.47 | 0.00 | 233.47 | 33.77 | 764.41 | 0.00 | 0.00 | 0.00 |
November | 154.58 | 0.00 | 154.58 | 4.27 | 1196.50 | 0.00 | 0.00 | 0.00 |
December | 129.58 | 0.00 | 129.58 | 0.00 | 1832.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 336.92 | 12.83 | 324.09 | 185.25 | 903.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 129.58 | 0.00 | 129.58 | 0.00 | 233.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 594.75 | 65.38 | 529.37 | 572.59 | 1895.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.94 | 0.00 | 152.94 | 0.01 | 1895.06 | 0.00 | 0.00 | 0.00 |
February | 234.93 | 0.00 | 234.93 | 3.18 | 1556.58 | 0.00 | 0.00 | 0.00 |
March | 289.04 | 0.00 | 289.04 | 10.76 | 1250.41 | 0.00 | 0.00 | 0.00 |
April | 378.91 | 2.96 | 375.95 | 93.57 | 766.79 | 0.00 | 0.00 | 0.00 |
May | 532.92 | 28.70 | 504.23 | 373.18 | 371.65 | 0.00 | 0.00 | 0.00 |
June | 594.75 | 65.38 | 529.37 | 558.14 | 255.52 | 0.00 | 0.00 | 0.00 |
July | 568.08 | 48.75 | 519.33 | 572.59 | 233.33 | 0.00 | 0.00 | 0.00 |
August | 431.47 | 7.41 | 424.07 | 375.14 | 286.19 | 0.00 | 0.00 | 0.00 |
September | 336.24 | 0.08 | 336.15 | 183.99 | 466.30 | 0.00 | 0.00 | 0.00 |
October | 233.46 | 0.00 | 233.46 | 33.77 | 764.41 | 0.00 | 0.00 | 0.00 |
November | 154.58 | 0.00 | 154.58 | 4.27 | 1196.50 | 0.00 | 0.00 | 0.00 |
December | 129.58 | 0.00 | 129.58 | 0.00 | 1832.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 336.92 | 12.83 | 324.09 | 185.25 | 903.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 129.58 | 0.00 | 129.58 | 0.00 | 233.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 594.75 | 65.38 | 529.37 | 572.59 | 1895.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.94 | 0.00 | 152.94 | 0.01 | 1895.06 | 0.00 | 0.00 | 0.00 |
February | 234.93 | 0.00 | 234.93 | 3.18 | 1556.58 | 0.00 | 0.00 | 0.00 |
March | 289.04 | 0.00 | 289.04 | 10.76 | 1250.41 | 0.00 | 0.00 | 0.00 |
April | 378.91 | 2.96 | 375.95 | 93.57 | 766.79 | 0.00 | 0.00 | 0.00 |
May | 532.92 | 28.70 | 504.23 | 373.18 | 371.65 | 0.00 | 0.00 | 0.00 |
June | 594.75 | 65.38 | 529.37 | 558.15 | 255.52 | 0.00 | 0.00 | 0.00 |
July | 568.08 | 48.75 | 519.33 | 572.59 | 233.33 | 0.00 | 0.00 | 0.00 |
August | 431.48 | 7.41 | 424.07 | 375.14 | 286.19 | 0.00 | 0.00 | 0.00 |
September | 336.24 | 0.08 | 336.15 | 183.99 | 466.30 | 0.00 | 0.00 | 0.00 |
October | 233.47 | 0.00 | 233.47 | 33.77 | 764.41 | 0.00 | 0.00 | 0.00 |
November | 154.58 | 0.00 | 154.58 | 4.27 | 1196.50 | 0.00 | 0.00 | 0.00 |
December | 129.58 | 0.00 | 129.58 | 0.00 | 1832.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 336.92 | 12.83 | 324.09 | 185.25 | 903.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 129.58 | 0.00 | 129.58 | 0.00 | 233.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 594.75 | 65.38 | 529.37 | 572.59 | 1895.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.94 | 0.00 | 152.94 | 0.01 | 1895.06 | 0.00 | 0.00 | 0.00 |
February | 234.93 | 0.00 | 234.93 | 3.18 | 1556.58 | 0.00 | 0.00 | 0.00 |
March | 289.04 | 0.00 | 289.04 | 10.76 | 1250.41 | 0.00 | 0.00 | 0.00 |
April | 378.91 | 2.96 | 375.95 | 93.57 | 766.79 | 0.00 | 0.00 | 0.00 |
May | 532.92 | 28.70 | 504.23 | 373.18 | 371.65 | 0.00 | 0.00 | 0.00 |
June | 594.75 | 65.38 | 529.37 | 558.14 | 255.52 | 0.00 | 0.00 | 0.00 |
July | 568.08 | 48.75 | 519.33 | 572.59 | 233.33 | 0.00 | 0.00 | 0.00 |
August | 431.47 | 7.41 | 424.07 | 375.14 | 286.19 | 0.00 | 0.00 | 0.00 |
September | 336.24 | 0.08 | 336.15 | 183.99 | 466.30 | 0.00 | 0.00 | 0.00 |
October | 233.46 | 0.00 | 233.46 | 33.77 | 764.41 | 0.00 | 0.00 | 0.00 |
November | 154.58 | 0.00 | 154.58 | 4.27 | 1196.50 | 0.00 | 0.00 | 0.00 |
December | 129.58 | 0.00 | 129.58 | 0.00 | 1832.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 336.92 | 12.83 | 324.09 | 185.25 | 903.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 129.58 | 0.00 | 129.58 | 0.00 | 233.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 594.75 | 65.38 | 529.37 | 572.59 | 1895.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.93 | 0.00 | 152.93 | 0.01 | 1894.98 | 0.00 | 0.00 | 0.00 |
February | 234.92 | 0.00 | 234.92 | 3.18 | 1556.52 | 0.00 | 0.00 | 0.00 |
March | 289.03 | 0.00 | 289.03 | 10.76 | 1250.36 | 0.00 | 0.00 | 0.00 |
April | 378.90 | 2.96 | 375.94 | 93.56 | 766.75 | 0.00 | 0.00 | 0.00 |
May | 532.90 | 28.70 | 504.21 | 373.17 | 371.63 | 0.00 | 0.00 | 0.00 |
June | 594.73 | 65.38 | 529.35 | 558.12 | 255.51 | 0.00 | 0.00 | 0.00 |
July | 568.06 | 48.75 | 519.31 | 572.57 | 233.32 | 0.00 | 0.00 | 0.00 |
August | 431.46 | 7.41 | 424.05 | 375.12 | 286.18 | 0.00 | 0.00 | 0.00 |
September | 336.22 | 0.08 | 336.14 | 183.98 | 466.28 | 0.00 | 0.00 | 0.00 |
October | 233.46 | 0.00 | 233.46 | 33.77 | 764.38 | 0.00 | 0.00 | 0.00 |
November | 154.58 | 0.00 | 154.58 | 4.27 | 1196.45 | 0.00 | 0.00 | 0.00 |
December | 129.58 | 0.00 | 129.58 | 0.00 | 1832.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 336.90 | 12.83 | 324.07 | 185.24 | 903.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 129.58 | 0.00 | 129.58 | 0.00 | 233.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 594.73 | 65.38 | 529.35 | 572.57 | 1894.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 372.56 | 155.52 | 217.04 | 81.12 | 1895.28 | 0.00 | 0.00 | 0.00 |
February | 585.45 | 249.73 | 335.72 | 239.86 | 1525.84 | 0.00 | 0.00 | 0.00 |
March | 797.71 | 400.14 | 397.57 | 471.70 | 1233.38 | 0.00 | 0.00 | 0.00 |
April | 1105.86 | 596.48 | 509.38 | 889.41 | 755.42 | 0.00 | 0.00 | 0.00 |
May | 1196.87 | 526.16 | 670.71 | 1162.04 | 398.35 | 0.00 | 0.00 | 0.00 |
June | 1354.94 | 648.14 | 706.79 | 1494.60 | 279.87 | 0.00 | 0.00 | 0.00 |
July | 1327.34 | 623.23 | 704.10 | 1523.39 | 246.97 | 0.00 | 0.00 | 0.00 |
August | 1023.38 | 447.29 | 576.09 | 1108.73 | 292.28 | 0.00 | 0.00 | 0.00 |
September | 819.56 | 366.83 | 452.73 | 746.95 | 473.12 | 0.00 | 0.00 | 0.00 |
October | 496.26 | 188.18 | 308.08 | 289.70 | 776.52 | 0.00 | 0.00 | 0.00 |
November | 315.92 | 105.62 | 210.30 | 102.11 | 1208.81 | 0.00 | 0.00 | 0.00 |
December | 288.27 | 106.55 | 181.72 | 49.52 | 1857.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 807.82 | 368.12 | 439.70 | 682.14 | 909.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 288.27 | 105.62 | 181.72 | 49.52 | 246.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1354.94 | 648.14 | 706.79 | 1523.39 | 1895.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 372.56 | 155.52 | 217.04 | 81.12 | 1895.28 | 0.00 | 0.00 | 0.00 |
February | 585.45 | 249.73 | 335.72 | 239.86 | 1525.84 | 0.00 | 0.00 | 0.00 |
March | 797.71 | 400.14 | 397.57 | 471.70 | 1233.38 | 0.00 | 0.00 | 0.00 |
April | 1105.86 | 596.48 | 509.38 | 889.41 | 755.42 | 0.00 | 0.00 | 0.00 |
May | 1196.87 | 526.16 | 670.71 | 1162.04 | 398.35 | 0.00 | 0.00 | 0.00 |
June | 1354.94 | 648.14 | 706.79 | 1494.60 | 279.87 | 0.00 | 0.00 | 0.00 |
July | 1327.34 | 623.23 | 704.10 | 1523.39 | 246.97 | 0.00 | 0.00 | 0.00 |
August | 1023.38 | 447.29 | 576.09 | 1108.73 | 292.28 | 0.00 | 0.00 | 0.00 |
September | 819.56 | 366.83 | 452.73 | 746.95 | 473.12 | 0.00 | 0.00 | 0.00 |
October | 496.26 | 188.18 | 308.08 | 289.70 | 776.52 | 0.00 | 0.00 | 0.00 |
November | 315.92 | 105.62 | 210.30 | 102.11 | 1208.81 | 0.00 | 0.00 | 0.00 |
December | 288.27 | 106.55 | 181.72 | 49.52 | 1857.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 807.82 | 368.12 | 439.70 | 682.14 | 909.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 288.27 | 105.62 | 181.72 | 49.52 | 246.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1354.94 | 648.14 | 706.79 | 1523.39 | 1895.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 372.56 | 155.52 | 217.04 | 81.12 | 1895.24 | 0.00 | 0.00 | 0.00 |
February | 585.44 | 249.72 | 335.72 | 239.86 | 1525.82 | 0.00 | 0.00 | 0.00 |
March | 797.70 | 400.14 | 397.56 | 471.69 | 1233.36 | 0.00 | 0.00 | 0.00 |
April | 1105.84 | 596.47 | 509.37 | 889.39 | 755.40 | 0.00 | 0.00 | 0.00 |
May | 1196.84 | 526.15 | 670.70 | 1162.02 | 398.34 | 0.00 | 0.00 | 0.00 |
June | 1354.91 | 648.13 | 706.78 | 1494.58 | 279.86 | 0.00 | 0.00 | 0.00 |
July | 1327.31 | 623.22 | 704.09 | 1523.36 | 246.96 | 0.00 | 0.00 | 0.00 |
August | 1023.36 | 447.28 | 576.08 | 1108.71 | 292.27 | 0.00 | 0.00 | 0.00 |
September | 819.54 | 366.82 | 452.72 | 746.94 | 473.11 | 0.00 | 0.00 | 0.00 |
October | 496.25 | 188.18 | 308.07 | 289.69 | 776.50 | 0.00 | 0.00 | 0.00 |
November | 315.91 | 105.62 | 210.30 | 102.11 | 1208.79 | 0.00 | 0.00 | 0.00 |
December | 288.27 | 106.55 | 181.72 | 49.52 | 1857.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 807.81 | 368.11 | 439.69 | 682.13 | 909.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 288.27 | 105.62 | 181.72 | 49.52 | 246.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1354.91 | 648.13 | 706.78 | 1523.36 | 1895.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1053.15 | 732.66 | 320.50 | 700.75 | 1476.49 | 0.00 | 0.00 | 0.00 |
February | 1333.55 | 900.72 | 432.82 | 1052.25 | 1247.01 | 0.00 | 0.00 | 0.00 |
March | 1175.02 | 743.62 | 431.39 | 961.54 | 1061.32 | 0.00 | 0.00 | 0.00 |
April | 1064.53 | 577.80 | 486.73 | 978.76 | 717.47 | 0.00 | 0.00 | 0.00 |
May | 894.99 | 305.97 | 589.01 | 922.49 | 394.98 | 0.00 | 0.00 | 0.00 |
June | 803.05 | 214.05 | 589.00 | 905.77 | 272.13 | 0.00 | 0.00 | 0.00 |
July | 878.00 | 278.15 | 599.85 | 1048.85 | 246.17 | 0.00 | 0.00 | 0.00 |
August | 937.65 | 392.21 | 545.44 | 1076.50 | 290.56 | 0.00 | 0.00 | 0.00 |
September | 1004.37 | 534.90 | 469.47 | 1044.86 | 448.60 | 0.00 | 0.00 | 0.00 |
October | 857.66 | 504.43 | 353.23 | 753.80 | 677.59 | 0.00 | 0.00 | 0.00 |
November | 763.98 | 479.48 | 284.51 | 563.61 | 981.99 | 0.00 | 0.00 | 0.00 |
December | 813.16 | 533.20 | 279.96 | 487.39 | 1458.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 962.51 | 513.98 | 448.52 | 873.27 | 770.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 763.98 | 214.05 | 279.96 | 487.39 | 246.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1333.55 | 900.72 | 599.85 | 1076.50 | 1476.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1053.15 | 732.65 | 320.50 | 700.75 | 1476.49 | 0.00 | 0.00 | 0.00 |
February | 1333.54 | 900.72 | 432.82 | 1052.25 | 1247.01 | 0.00 | 0.00 | 0.00 |
March | 1175.01 | 743.62 | 431.39 | 961.54 | 1061.32 | 0.00 | 0.00 | 0.00 |
April | 1064.53 | 577.79 | 486.73 | 978.75 | 717.47 | 0.00 | 0.00 | 0.00 |
May | 894.99 | 305.97 | 589.01 | 922.49 | 394.98 | 0.00 | 0.00 | 0.00 |
June | 803.05 | 214.05 | 589.00 | 905.76 | 272.13 | 0.00 | 0.00 | 0.00 |
July | 878.00 | 278.15 | 599.85 | 1048.85 | 246.17 | 0.00 | 0.00 | 0.00 |
August | 937.65 | 392.21 | 545.44 | 1076.50 | 290.56 | 0.00 | 0.00 | 0.00 |
September | 1004.36 | 534.90 | 469.47 | 1044.86 | 448.60 | 0.00 | 0.00 | 0.00 |
October | 857.66 | 504.43 | 353.23 | 753.80 | 677.59 | 0.00 | 0.00 | 0.00 |
November | 763.98 | 479.48 | 284.51 | 563.61 | 981.99 | 0.00 | 0.00 | 0.00 |
December | 813.16 | 533.20 | 279.96 | 487.39 | 1458.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 962.51 | 513.98 | 448.52 | 873.27 | 770.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 763.98 | 214.05 | 279.96 | 487.39 | 246.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1333.54 | 900.72 | 599.85 | 1076.50 | 1476.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1053.15 | 732.66 | 320.50 | 700.75 | 1476.49 | 0.00 | 0.00 | 0.00 |
February | 1333.55 | 900.72 | 432.82 | 1052.25 | 1247.01 | 0.00 | 0.00 | 0.00 |
March | 1175.02 | 743.62 | 431.39 | 961.54 | 1061.32 | 0.00 | 0.00 | 0.00 |
April | 1064.53 | 577.80 | 486.73 | 978.76 | 717.47 | 0.00 | 0.00 | 0.00 |
May | 894.99 | 305.97 | 589.01 | 922.49 | 394.98 | 0.00 | 0.00 | 0.00 |
June | 803.05 | 214.05 | 589.00 | 905.77 | 272.13 | 0.00 | 0.00 | 0.00 |
July | 878.00 | 278.15 | 599.85 | 1048.85 | 246.17 | 0.00 | 0.00 | 0.00 |
August | 937.65 | 392.21 | 545.44 | 1076.50 | 290.56 | 0.00 | 0.00 | 0.00 |
September | 1004.37 | 534.90 | 469.47 | 1044.86 | 448.60 | 0.00 | 0.00 | 0.00 |
October | 857.66 | 504.43 | 353.23 | 753.80 | 677.59 | 0.00 | 0.00 | 0.00 |
November | 763.98 | 479.48 | 284.51 | 563.61 | 981.99 | 0.00 | 0.00 | 0.00 |
December | 813.16 | 533.20 | 279.96 | 487.39 | 1458.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 962.51 | 513.98 | 448.52 | 873.27 | 770.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 763.98 | 214.05 | 279.96 | 487.39 | 246.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1333.55 | 900.72 | 599.85 | 1076.50 | 1476.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1053.15 | 732.65 | 320.50 | 700.75 | 1476.49 | 0.00 | 0.00 | 0.00 |
February | 1333.54 | 900.72 | 432.82 | 1052.25 | 1247.01 | 0.00 | 0.00 | 0.00 |
March | 1175.01 | 743.62 | 431.39 | 961.54 | 1061.32 | 0.00 | 0.00 | 0.00 |
April | 1064.53 | 577.79 | 486.73 | 978.75 | 717.47 | 0.00 | 0.00 | 0.00 |
May | 894.99 | 305.97 | 589.01 | 922.49 | 394.98 | 0.00 | 0.00 | 0.00 |
June | 803.05 | 214.05 | 589.00 | 905.76 | 272.13 | 0.00 | 0.00 | 0.00 |
July | 878.00 | 278.15 | 599.85 | 1048.85 | 246.17 | 0.00 | 0.00 | 0.00 |
August | 937.65 | 392.21 | 545.44 | 1076.50 | 290.56 | 0.00 | 0.00 | 0.00 |
September | 1004.36 | 534.90 | 469.47 | 1044.86 | 448.60 | 0.00 | 0.00 | 0.00 |
October | 857.66 | 504.43 | 353.23 | 753.80 | 677.59 | 0.00 | 0.00 | 0.00 |
November | 763.98 | 479.48 | 284.51 | 563.61 | 981.99 | 0.00 | 0.00 | 0.00 |
December | 813.16 | 533.20 | 279.96 | 487.39 | 1458.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 962.51 | 513.98 | 448.52 | 873.27 | 770.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 763.98 | 214.05 | 279.96 | 487.39 | 246.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1333.54 | 900.72 | 599.85 | 1076.50 | 1476.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1053.11 | 732.63 | 320.49 | 700.72 | 1476.43 | 0.00 | 0.00 | 0.00 |
February | 1333.49 | 900.69 | 432.81 | 1052.21 | 1246.96 | 0.00 | 0.00 | 0.00 |
March | 1174.97 | 743.59 | 431.38 | 961.50 | 1061.28 | 0.00 | 0.00 | 0.00 |
April | 1064.48 | 577.77 | 486.71 | 978.72 | 717.44 | 0.00 | 0.00 | 0.00 |
May | 894.95 | 305.96 | 588.99 | 922.45 | 394.96 | 0.00 | 0.00 | 0.00 |
June | 803.02 | 214.04 | 588.98 | 905.73 | 272.12 | 0.00 | 0.00 | 0.00 |
July | 877.96 | 278.13 | 599.83 | 1048.80 | 246.16 | 0.00 | 0.00 | 0.00 |
August | 937.61 | 392.20 | 545.42 | 1076.46 | 290.55 | 0.00 | 0.00 | 0.00 |
September | 1004.33 | 534.88 | 469.45 | 1044.82 | 448.58 | 0.00 | 0.00 | 0.00 |
October | 857.62 | 504.41 | 353.21 | 753.77 | 677.56 | 0.00 | 0.00 | 0.00 |
November | 763.95 | 479.46 | 284.50 | 563.59 | 981.95 | 0.00 | 0.00 | 0.00 |
December | 813.13 | 533.18 | 279.95 | 487.37 | 1458.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 962.47 | 513.96 | 448.51 | 873.24 | 770.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 763.95 | 214.04 | 279.95 | 487.37 | 246.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1333.49 | 900.69 | 599.83 | 1076.46 | 1476.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.55 | 157.68 | 218.87 | 96.27 | 2005.73 | 0.00 | 0.00 | 0.00 |
February | 613.51 | 280.21 | 333.30 | 295.64 | 1656.31 | 0.00 | 0.00 | 0.00 |
March | 807.33 | 413.11 | 394.23 | 506.61 | 1352.72 | 0.00 | 0.00 | 0.00 |
April | 1031.33 | 522.36 | 508.97 | 811.66 | 887.66 | 0.00 | 0.00 | 0.00 |
May | 1267.17 | 604.44 | 662.72 | 1279.51 | 467.89 | 0.00 | 0.00 | 0.00 |
June | 1222.79 | 528.72 | 694.06 | 1333.93 | 334.21 | 0.00 | 0.00 | 0.00 |
July | 1305.44 | 606.90 | 698.55 | 1478.68 | 321.39 | 0.00 | 0.00 | 0.00 |
August | 1074.29 | 488.15 | 586.14 | 1157.13 | 382.62 | 0.00 | 0.00 | 0.00 |
September | 839.60 | 377.22 | 462.38 | 776.08 | 538.67 | 0.00 | 0.00 | 0.00 |
October | 530.38 | 212.92 | 317.46 | 340.04 | 851.40 | 0.00 | 0.00 | 0.00 |
November | 322.13 | 108.61 | 213.52 | 104.34 | 1312.44 | 0.00 | 0.00 | 0.00 |
December | 287.16 | 100.51 | 186.65 | 46.83 | 2008.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 807.54 | 367.26 | 440.28 | 687.99 | 1007.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 287.16 | 100.51 | 186.65 | 46.83 | 321.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1305.44 | 606.90 | 698.55 | 1478.68 | 2008.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.55 | 157.68 | 218.87 | 96.27 | 2005.73 | 0.00 | 0.00 | 0.00 |
February | 613.51 | 280.21 | 333.30 | 295.64 | 1656.31 | 0.00 | 0.00 | 0.00 |
March | 807.33 | 413.11 | 394.23 | 506.61 | 1352.72 | 0.00 | 0.00 | 0.00 |
April | 1031.33 | 522.36 | 508.97 | 811.66 | 887.66 | 0.00 | 0.00 | 0.00 |
May | 1267.17 | 604.44 | 662.72 | 1279.51 | 467.89 | 0.00 | 0.00 | 0.00 |
June | 1222.79 | 528.72 | 694.06 | 1333.93 | 334.21 | 0.00 | 0.00 | 0.00 |
July | 1305.44 | 606.90 | 698.55 | 1478.68 | 321.39 | 0.00 | 0.00 | 0.00 |
August | 1074.29 | 488.15 | 586.14 | 1157.13 | 382.62 | 0.00 | 0.00 | 0.00 |
September | 839.60 | 377.22 | 462.38 | 776.08 | 538.67 | 0.00 | 0.00 | 0.00 |
October | 530.38 | 212.92 | 317.46 | 340.04 | 851.40 | 0.00 | 0.00 | 0.00 |
November | 322.13 | 108.61 | 213.52 | 104.34 | 1312.44 | 0.00 | 0.00 | 0.00 |
December | 287.16 | 100.51 | 186.65 | 46.83 | 2008.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 807.54 | 367.26 | 440.28 | 687.99 | 1007.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 287.16 | 100.51 | 186.65 | 46.83 | 321.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1305.44 | 606.90 | 698.55 | 1478.68 | 2008.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.54 | 157.67 | 218.87 | 96.27 | 2005.70 | 0.00 | 0.00 | 0.00 |
February | 613.50 | 280.21 | 333.29 | 295.63 | 1656.28 | 0.00 | 0.00 | 0.00 |
March | 807.32 | 413.10 | 394.22 | 506.61 | 1352.70 | 0.00 | 0.00 | 0.00 |
April | 1031.31 | 522.35 | 508.96 | 811.64 | 887.65 | 0.00 | 0.00 | 0.00 |
May | 1267.14 | 604.43 | 662.71 | 1279.49 | 467.89 | 0.00 | 0.00 | 0.00 |
June | 1222.77 | 528.71 | 694.05 | 1333.91 | 334.20 | 0.00 | 0.00 | 0.00 |
July | 1305.42 | 606.89 | 698.54 | 1478.66 | 321.38 | 0.00 | 0.00 | 0.00 |
August | 1074.27 | 488.14 | 586.13 | 1157.11 | 382.61 | 0.00 | 0.00 | 0.00 |
September | 839.59 | 377.21 | 462.37 | 776.07 | 538.66 | 0.00 | 0.00 | 0.00 |
October | 530.37 | 212.91 | 317.46 | 340.03 | 851.39 | 0.00 | 0.00 | 0.00 |
November | 322.12 | 108.61 | 213.51 | 104.34 | 1312.42 | 0.00 | 0.00 | 0.00 |
December | 287.15 | 100.51 | 186.65 | 46.83 | 2008.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 807.52 | 367.25 | 440.28 | 687.98 | 1007.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 287.15 | 100.51 | 186.65 | 46.83 | 321.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1305.42 | 606.89 | 698.54 | 1478.66 | 2008.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 764.69 | 0.00 | 764.69 | 1.09 | 9360.78 | 0.00 | 0.00 | 0.00 |
February | 1174.62 | 0.00 | 1174.62 | 29.50 | 7596.47 | 0.00 | 0.00 | 0.00 |
March | 1445.17 | 0.00 | 1445.17 | 75.36 | 6009.84 | 0.00 | 0.00 | 0.00 |
April | 1894.53 | 14.79 | 1879.74 | 551.59 | 3516.08 | 0.00 | 0.00 | 0.00 |
May | 2664.58 | 143.48 | 2521.10 | 1946.81 | 1739.29 | 0.00 | 0.00 | 0.00 |
June | 2973.72 | 326.89 | 2646.83 | 2866.50 | 1188.43 | 0.00 | 0.00 | 0.00 |
July | 2840.37 | 243.76 | 2596.61 | 2937.03 | 1089.47 | 0.00 | 0.00 | 0.00 |
August | 2157.35 | 37.05 | 2120.30 | 1985.30 | 1262.92 | 0.00 | 0.00 | 0.00 |
September | 1681.16 | 0.41 | 1680.75 | 1017.20 | 2124.74 | 0.00 | 0.00 | 0.00 |
October | 1167.31 | 0.00 | 1167.31 | 225.96 | 3482.95 | 0.00 | 0.00 | 0.00 |
November | 772.91 | 0.00 | 772.91 | 28.65 | 5528.31 | 0.00 | 0.00 | 0.00 |
December | 647.91 | 0.00 | 647.91 | 0.00 | 8941.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1684.57 | 64.15 | 1620.42 | 978.25 | 4306.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 647.91 | 0.00 | 647.91 | 0.00 | 1089.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2973.72 | 326.89 | 2646.83 | 2937.03 | 9360.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1117.68 | 466.55 | 651.12 | 242.37 | 5597.64 | 0.00 | 0.00 | 0.00 |
February | 1756.33 | 749.17 | 1007.16 | 727.46 | 4477.71 | 0.00 | 0.00 | 0.00 |
March | 2393.11 | 1200.42 | 1192.69 | 1410.79 | 3607.82 | 0.00 | 0.00 | 0.00 |
April | 3317.55 | 1789.42 | 1528.13 | 2648.94 | 2160.37 | 0.00 | 0.00 | 0.00 |
May | 3590.56 | 1578.45 | 2012.11 | 3443.13 | 1156.44 | 0.00 | 0.00 | 0.00 |
June | 4064.76 | 1944.40 | 2120.36 | 4441.23 | 807.27 | 0.00 | 0.00 | 0.00 |
July | 3981.97 | 1869.68 | 2112.29 | 4533.66 | 725.98 | 0.00 | 0.00 | 0.00 |
August | 3070.11 | 1341.85 | 1728.26 | 3302.21 | 837.42 | 0.00 | 0.00 | 0.00 |
September | 2458.64 | 1100.48 | 1358.17 | 2223.16 | 1353.45 | 0.00 | 0.00 | 0.00 |
October | 1488.75 | 564.53 | 924.22 | 872.33 | 2192.76 | 0.00 | 0.00 | 0.00 |
November | 947.75 | 316.85 | 630.90 | 313.75 | 3393.66 | 0.00 | 0.00 | 0.00 |
December | 864.81 | 319.65 | 545.16 | 149.93 | 5433.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2423.44 | 1104.35 | 1319.09 | 2032.24 | 2638.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 864.81 | 316.85 | 545.16 | 149.93 | 725.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4064.76 | 1944.40 | 2120.36 | 4533.66 | 5597.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5265.71 | 3663.24 | 1602.47 | 3459.82 | 7405.11 | 0.00 | 0.00 | 0.00 |
February | 6667.65 | 4503.56 | 2164.09 | 5184.39 | 6232.65 | 0.00 | 0.00 | 0.00 |
March | 5875.01 | 3718.06 | 2156.94 | 4743.60 | 5285.42 | 0.00 | 0.00 | 0.00 |
April | 5322.57 | 2888.94 | 2433.63 | 4845.74 | 3510.59 | 0.00 | 0.00 | 0.00 |
May | 4474.88 | 1529.86 | 2945.03 | 4568.13 | 1951.25 | 0.00 | 0.00 | 0.00 |
June | 4015.22 | 1070.23 | 2944.99 | 4510.70 | 1321.42 | 0.00 | 0.00 | 0.00 |
July | 4389.94 | 1390.71 | 2999.23 | 5222.57 | 1203.07 | 0.00 | 0.00 | 0.00 |
August | 4688.21 | 1961.04 | 2727.16 | 5359.99 | 1396.17 | 0.00 | 0.00 | 0.00 |
September | 5021.77 | 2674.47 | 2347.30 | 5168.70 | 2220.03 | 0.00 | 0.00 | 0.00 |
October | 4288.24 | 2522.13 | 1766.11 | 3734.32 | 3332.98 | 0.00 | 0.00 | 0.00 |
November | 3819.87 | 2397.36 | 1422.52 | 2802.51 | 4768.93 | 0.00 | 0.00 | 0.00 |
December | 4065.76 | 2665.97 | 1399.79 | 2419.98 | 7246.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4812.48 | 2569.89 | 2242.59 | 4328.09 | 3812.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3819.87 | 1070.23 | 1399.79 | 2419.98 | 1203.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6667.65 | 4503.56 | 2999.23 | 5359.99 | 7405.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1129.64 | 473.03 | 656.61 | 293.09 | 5834.59 | 0.00 | 0.00 | 0.00 |
February | 1840.52 | 840.63 | 999.89 | 901.36 | 4742.75 | 0.00 | 0.00 | 0.00 |
March | 2421.98 | 1239.31 | 1182.67 | 1545.88 | 3798.45 | 0.00 | 0.00 | 0.00 |
April | 3093.95 | 1567.05 | 1526.89 | 2499.94 | 2369.04 | 0.00 | 0.00 | 0.00 |
May | 3801.46 | 1813.32 | 1988.15 | 3875.98 | 1311.78 | 0.00 | 0.00 | 0.00 |
June | 3668.33 | 1586.16 | 2082.17 | 4058.83 | 905.53 | 0.00 | 0.00 | 0.00 |
July | 3916.29 | 1820.67 | 2095.62 | 4506.90 | 857.90 | 0.00 | 0.00 | 0.00 |
August | 3222.85 | 1464.44 | 1758.41 | 3570.77 | 956.33 | 0.00 | 0.00 | 0.00 |
September | 2518.78 | 1131.65 | 1387.13 | 2378.59 | 1476.86 | 0.00 | 0.00 | 0.00 |
October | 1591.13 | 638.75 | 952.38 | 1058.10 | 2315.19 | 0.00 | 0.00 | 0.00 |
November | 966.37 | 325.82 | 640.55 | 337.76 | 3541.19 | 0.00 | 0.00 | 0.00 |
December | 861.47 | 301.52 | 559.95 | 147.81 | 5676.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2422.59 | 1101.75 | 1320.84 | 2105.33 | 2807.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 861.47 | 301.52 | 559.95 | 147.81 | 857.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3916.29 | 1820.67 | 2095.62 | 4506.90 | 5834.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 764.69 | 0.00 | 764.69 | 1.92 | 9209.74 | 0.00 | 0.00 | 0.00 |
February | 1174.62 | 0.00 | 1174.62 | 34.21 | 7410.99 | 0.00 | 0.00 | 0.00 |
March | 1445.17 | 0.00 | 1445.17 | 89.96 | 5767.63 | 0.00 | 0.00 | 0.00 |
April | 1894.53 | 14.79 | 1879.74 | 602.71 | 3242.31 | 0.00 | 0.00 | 0.00 |
May | 2664.58 | 143.48 | 2521.10 | 2034.80 | 1579.92 | 0.00 | 0.00 | 0.00 |
June | 2973.72 | 326.89 | 2646.83 | 2951.82 | 1083.28 | 0.00 | 0.00 | 0.00 |
July | 2840.37 | 243.76 | 2596.61 | 3005.78 | 1003.72 | 0.00 | 0.00 | 0.00 |
August | 2157.35 | 37.05 | 2120.30 | 2057.91 | 1138.64 | 0.00 | 0.00 | 0.00 |
September | 1681.16 | 0.41 | 1680.75 | 1097.91 | 1906.80 | 0.00 | 0.00 | 0.00 |
October | 1167.31 | 0.00 | 1167.31 | 272.10 | 3137.78 | 0.00 | 0.00 | 0.00 |
November | 772.91 | 0.00 | 772.91 | 32.69 | 5239.68 | 0.00 | 0.00 | 0.00 |
December | 647.91 | 0.00 | 647.91 | 0.00 | 8766.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1684.57 | 64.15 | 1620.42 | 1021.50 | 4110.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 647.91 | 0.00 | 647.91 | 0.00 | 1003.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2973.72 | 326.89 | 2646.83 | 3005.78 | 9209.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1117.68 | 466.55 | 651.12 | 247.26 | 5527.20 | 0.00 | 0.00 | 0.00 |
February | 1756.33 | 749.17 | 1007.16 | 747.44 | 4364.14 | 0.00 | 0.00 | 0.00 |
March | 2393.11 | 1200.42 | 1192.69 | 1451.80 | 3446.15 | 0.00 | 0.00 | 0.00 |
April | 3317.55 | 1789.42 | 1528.13 | 2707.52 | 1994.12 | 0.00 | 0.00 | 0.00 |
May | 3590.56 | 1578.45 | 2012.11 | 3489.82 | 1075.58 | 0.00 | 0.00 | 0.00 |
June | 4064.76 | 1944.40 | 2120.36 | 4462.39 | 755.22 | 0.00 | 0.00 | 0.00 |
July | 3981.97 | 1869.68 | 2112.29 | 4542.25 | 687.80 | 0.00 | 0.00 | 0.00 |
August | 3070.11 | 1341.85 | 1728.26 | 3328.02 | 779.90 | 0.00 | 0.00 | 0.00 |
September | 2458.64 | 1100.48 | 1358.17 | 2283.90 | 1231.71 | 0.00 | 0.00 | 0.00 |
October | 1488.75 | 564.53 | 924.22 | 931.60 | 1971.43 | 0.00 | 0.00 | 0.00 |
November | 947.75 | 316.85 | 630.90 | 332.27 | 3205.22 | 0.00 | 0.00 | 0.00 |
December | 864.81 | 319.65 | 545.16 | 154.40 | 5348.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2423.44 | 1104.35 | 1319.09 | 2063.04 | 2525.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 864.81 | 316.85 | 545.16 | 154.40 | 687.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4064.76 | 1944.40 | 2120.36 | 4542.25 | 5527.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5265.71 | 3663.24 | 1602.47 | 3492.93 | 7240.31 | 0.00 | 0.00 | 0.00 |
February | 6667.65 | 4503.56 | 2164.09 | 5232.06 | 6013.67 | 0.00 | 0.00 | 0.00 |
March | 5875.01 | 3718.06 | 2156.94 | 4799.32 | 5015.31 | 0.00 | 0.00 | 0.00 |
April | 5322.57 | 2888.94 | 2433.63 | 4903.46 | 3229.96 | 0.00 | 0.00 | 0.00 |
May | 4474.88 | 1529.86 | 2945.03 | 4619.98 | 1785.34 | 0.00 | 0.00 | 0.00 |
June | 4015.22 | 1070.23 | 2944.99 | 4546.34 | 1211.27 | 0.00 | 0.00 | 0.00 |
July | 4389.94 | 1390.71 | 2999.23 | 5245.85 | 1114.58 | 0.00 | 0.00 | 0.00 |
August | 4688.21 | 1961.04 | 2727.16 | 5392.90 | 1276.37 | 0.00 | 0.00 | 0.00 |
September | 5021.77 | 2674.47 | 2347.30 | 5230.13 | 2013.86 | 0.00 | 0.00 | 0.00 |
October | 4288.24 | 2522.13 | 1766.11 | 3814.62 | 3002.11 | 0.00 | 0.00 | 0.00 |
November | 3819.87 | 2397.36 | 1422.52 | 2862.38 | 4474.61 | 0.00 | 0.00 | 0.00 |
December | 4065.76 | 2665.97 | 1399.79 | 2457.73 | 7060.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4812.48 | 2569.89 | 2242.59 | 4376.14 | 3609.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3819.87 | 1070.23 | 1399.79 | 2457.73 | 1114.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6667.65 | 4503.56 | 2999.23 | 5392.90 | 7240.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1129.64 | 473.03 | 656.61 | 295.85 | 5739.77 | 0.00 | 0.00 | 0.00 |
February | 1840.52 | 840.63 | 999.89 | 903.92 | 4626.44 | 0.00 | 0.00 | 0.00 |
March | 2421.98 | 1239.31 | 1182.67 | 1554.94 | 3649.02 | 0.00 | 0.00 | 0.00 |
April | 3093.95 | 1567.05 | 1526.89 | 2515.78 | 2211.05 | 0.00 | 0.00 | 0.00 |
May | 3801.46 | 1813.32 | 1988.15 | 3885.14 | 1227.07 | 0.00 | 0.00 | 0.00 |
June | 3668.33 | 1586.16 | 2082.17 | 4059.26 | 852.69 | 0.00 | 0.00 | 0.00 |
July | 3916.29 | 1820.67 | 2095.62 | 4502.08 | 815.20 | 0.00 | 0.00 | 0.00 |
August | 3222.85 | 1464.44 | 1758.41 | 3574.95 | 899.84 | 0.00 | 0.00 | 0.00 |
September | 2518.78 | 1131.65 | 1387.13 | 2394.83 | 1369.66 | 0.00 | 0.00 | 0.00 |
October | 1591.13 | 638.75 | 952.38 | 1079.79 | 2127.07 | 0.00 | 0.00 | 0.00 |
November | 966.37 | 325.82 | 640.55 | 347.86 | 3375.30 | 0.00 | 0.00 | 0.00 |
December | 861.47 | 301.52 | 559.95 | 149.28 | 5574.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2422.59 | 1101.75 | 1320.84 | 2112.72 | 2698.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 861.47 | 301.52 | 559.95 | 149.28 | 815.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3916.29 | 1820.67 | 2095.62 | 4502.08 | 5739.77 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.409635E+09 | 0.00 | 0.409635E+09 | 15494.19 | 0.507572E+10 |
February | 0.568337E+09 | 0.00 | 0.568337E+09 | 7688772.75 | 0.376569E+10 |
March | 0.774159E+09 | 0.00 | 0.774159E+09 | 28813541.59 | 0.334910E+10 |
April | 0.982136E+09 | 7665453.47 | 0.974470E+09 | 0.242524E+09 | 0.198751E+10 |
May | 0.142738E+10 | 76862393.79 | 0.135052E+10 | 0.999530E+09 | 0.995425E+09 |
June | 0.154159E+10 | 0.169462E+09 | 0.137213E+10 | 0.144671E+10 | 0.662318E+09 |
July | 0.152155E+10 | 0.130578E+09 | 0.139097E+10 | 0.153364E+10 | 0.624957E+09 |
August | 0.115566E+10 | 19846271.01 | 0.113582E+10 | 0.100476E+10 | 0.766523E+09 |
September | 0.871524E+09 | 213638.54 | 0.871310E+09 | 0.476897E+09 | 0.120865E+10 |
October | 0.625313E+09 | 0.00 | 0.625313E+09 | 90459769.23 | 0.204740E+10 |
November | 0.400681E+09 | 0.00 | 0.400681E+09 | 11062046.09 | 0.310133E+10 |
December | 0.347075E+09 | 0.00 | 0.347075E+09 | 0.00 | 0.490823E+10 |
Annual Sum or Average | 0.106250E+11 | 0.404628E+09 | 0.102204E+11 | 0.584211E+10 | 0.284928E+11 |
Minimum of Months | 0.347075E+09 | 0.00 | 0.347075E+09 | 0.00 | 0.624957E+09 |
Maximum of Months | 0.154159E+10 | 0.169462E+09 | 0.139097E+10 | 0.153364E+10 | 0.507572E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.409634E+09 | 0.00 | 0.409634E+09 | 15493.65 | 0.507572E+10 |
February | 0.568337E+09 | 0.00 | 0.568337E+09 | 7688726.96 | 0.376569E+10 |
March | 0.774158E+09 | 0.00 | 0.774158E+09 | 28813432.26 | 0.334910E+10 |
April | 0.982135E+09 | 7665444.27 | 0.974470E+09 | 0.242524E+09 | 0.198751E+10 |
May | 0.142738E+10 | 76862301.57 | 0.135052E+10 | 0.999528E+09 | 0.995425E+09 |
June | 0.154159E+10 | 0.169462E+09 | 0.137213E+10 | 0.144671E+10 | 0.662318E+09 |
July | 0.152155E+10 | 0.130577E+09 | 0.139097E+10 | 0.153364E+10 | 0.624957E+09 |
August | 0.115566E+10 | 19846247.20 | 0.113582E+10 | 0.100476E+10 | 0.766523E+09 |
September | 0.871523E+09 | 213638.29 | 0.871309E+09 | 0.476896E+09 | 0.120865E+10 |
October | 0.625313E+09 | 0.00 | 0.625313E+09 | 90459504.17 | 0.204740E+10 |
November | 0.400680E+09 | 0.00 | 0.400680E+09 | 11062019.05 | 0.310133E+10 |
December | 0.347075E+09 | 0.00 | 0.347075E+09 | 0.00 | 0.490823E+10 |
Annual Sum or Average | 0.106250E+11 | 0.404627E+09 | 0.102204E+11 | 0.584210E+10 | 0.284929E+11 |
Minimum of Months | 0.347075E+09 | 0.00 | 0.347075E+09 | 0.00 | 0.624957E+09 |
Maximum of Months | 0.154159E+10 | 0.169462E+09 | 0.139097E+10 | 0.153364E+10 | 0.507572E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.409635E+09 | 0.00 | 0.409635E+09 | 15494.19 | 0.507572E+10 |
February | 0.568337E+09 | 0.00 | 0.568337E+09 | 7688772.75 | 0.376569E+10 |
March | 0.774159E+09 | 0.00 | 0.774159E+09 | 28813541.59 | 0.334910E+10 |
April | 0.982136E+09 | 7665453.47 | 0.974470E+09 | 0.242524E+09 | 0.198751E+10 |
May | 0.142738E+10 | 76862393.79 | 0.135052E+10 | 0.999530E+09 | 0.995425E+09 |
June | 0.154159E+10 | 0.169462E+09 | 0.137213E+10 | 0.144671E+10 | 0.662318E+09 |
July | 0.152155E+10 | 0.130578E+09 | 0.139097E+10 | 0.153364E+10 | 0.624957E+09 |
August | 0.115566E+10 | 19846271.01 | 0.113582E+10 | 0.100476E+10 | 0.766523E+09 |
September | 0.871524E+09 | 213638.54 | 0.871310E+09 | 0.476897E+09 | 0.120865E+10 |
October | 0.625313E+09 | 0.00 | 0.625313E+09 | 90459769.23 | 0.204740E+10 |
November | 0.400681E+09 | 0.00 | 0.400681E+09 | 11062046.09 | 0.310133E+10 |
December | 0.347075E+09 | 0.00 | 0.347075E+09 | 0.00 | 0.490823E+10 |
Annual Sum or Average | 0.106250E+11 | 0.404628E+09 | 0.102204E+11 | 0.584211E+10 | 0.284928E+11 |
Minimum of Months | 0.347075E+09 | 0.00 | 0.347075E+09 | 0.00 | 0.624957E+09 |
Maximum of Months | 0.154159E+10 | 0.169462E+09 | 0.139097E+10 | 0.153364E+10 | 0.507572E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.409634E+09 | 0.00 | 0.409634E+09 | 15493.65 | 0.507572E+10 |
February | 0.568337E+09 | 0.00 | 0.568337E+09 | 7688726.96 | 0.376569E+10 |
March | 0.774158E+09 | 0.00 | 0.774158E+09 | 28813432.26 | 0.334910E+10 |
April | 0.982135E+09 | 7665444.27 | 0.974470E+09 | 0.242524E+09 | 0.198751E+10 |
May | 0.142738E+10 | 76862301.57 | 0.135052E+10 | 0.999528E+09 | 0.995425E+09 |
June | 0.154159E+10 | 0.169462E+09 | 0.137213E+10 | 0.144671E+10 | 0.662318E+09 |
July | 0.152155E+10 | 0.130577E+09 | 0.139097E+10 | 0.153364E+10 | 0.624957E+09 |
August | 0.115566E+10 | 19846247.20 | 0.113582E+10 | 0.100476E+10 | 0.766523E+09 |
September | 0.871523E+09 | 213638.29 | 0.871309E+09 | 0.476896E+09 | 0.120865E+10 |
October | 0.625313E+09 | 0.00 | 0.625313E+09 | 90459504.17 | 0.204740E+10 |
November | 0.400680E+09 | 0.00 | 0.400680E+09 | 11062019.05 | 0.310133E+10 |
December | 0.347075E+09 | 0.00 | 0.347075E+09 | 0.00 | 0.490823E+10 |
Annual Sum or Average | 0.106250E+11 | 0.404627E+09 | 0.102204E+11 | 0.584210E+10 | 0.284929E+11 |
Minimum of Months | 0.347075E+09 | 0.00 | 0.347075E+09 | 0.00 | 0.624957E+09 |
Maximum of Months | 0.154159E+10 | 0.169462E+09 | 0.139097E+10 | 0.153364E+10 | 0.507572E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.409618E+09 | 0.00 | 0.409618E+09 | 15493.56 | 0.507552E+10 |
February | 0.568314E+09 | 0.00 | 0.568314E+09 | 7688462.86 | 0.376554E+10 |
March | 0.774127E+09 | 0.00 | 0.774127E+09 | 28812380.28 | 0.334897E+10 |
April | 0.982096E+09 | 7665144.52 | 0.974431E+09 | 0.242515E+09 | 0.198743E+10 |
May | 0.142732E+10 | 76859295.90 | 0.135046E+10 | 0.999489E+09 | 0.995385E+09 |
June | 0.154153E+10 | 0.169456E+09 | 0.137208E+10 | 0.144665E+10 | 0.662292E+09 |
July | 0.152149E+10 | 0.130572E+09 | 0.139091E+10 | 0.153358E+10 | 0.624932E+09 |
August | 0.115562E+10 | 19845471.12 | 0.113577E+10 | 0.100472E+10 | 0.766492E+09 |
September | 0.871488E+09 | 213629.93 | 0.871275E+09 | 0.476878E+09 | 0.120860E+10 |
October | 0.625288E+09 | 0.00 | 0.625288E+09 | 90456123.30 | 0.204732E+10 |
November | 0.400665E+09 | 0.00 | 0.400665E+09 | 11061600.24 | 0.310120E+10 |
December | 0.347061E+09 | 0.00 | 0.347061E+09 | 0.00 | 0.490803E+10 |
Annual Sum or Average | 0.106246E+11 | 0.404611E+09 | 0.102200E+11 | 0.584187E+10 | 0.284917E+11 |
Minimum of Months | 0.347061E+09 | 0.00 | 0.347061E+09 | 0.00 | 0.624932E+09 |
Maximum of Months | 0.154153E+10 | 0.169456E+09 | 0.139091E+10 | 0.153358E+10 | 0.507552E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.997873E+09 | 0.416543E+09 | 0.581330E+09 | 0.217264E+09 | 0.507631E+10 |
February | 0.141632E+10 | 0.604139E+09 | 0.812181E+09 | 0.580271E+09 | 0.369132E+10 |
March | 0.213659E+10 | 0.107175E+10 | 0.106485E+10 | 0.126340E+10 | 0.330348E+10 |
April | 0.286639E+10 | 0.154607E+10 | 0.132032E+10 | 0.230534E+10 | 0.195804E+10 |
May | 0.320569E+10 | 0.140926E+10 | 0.179643E+10 | 0.311241E+10 | 0.106694E+10 |
June | 0.351199E+10 | 0.167998E+10 | 0.183201E+10 | 0.387402E+10 | 0.725414E+09 |
July | 0.355514E+10 | 0.166927E+10 | 0.188587E+10 | 0.408024E+10 | 0.661479E+09 |
August | 0.274102E+10 | 0.119802E+10 | 0.154300E+10 | 0.296961E+10 | 0.782831E+09 |
September | 0.212429E+10 | 0.950821E+09 | 0.117347E+10 | 0.193611E+10 | 0.122632E+10 |
October | 0.132917E+10 | 0.504019E+09 | 0.825152E+09 | 0.775922E+09 | 0.207983E+10 |
November | 0.818865E+09 | 0.273765E+09 | 0.545100E+09 | 0.264670E+09 | 0.313324E+10 |
December | 0.772114E+09 | 0.285386E+09 | 0.486728E+09 | 0.132628E+09 | 0.497583E+10 |
Annual Sum or Average | 0.254755E+11 | 0.116090E+11 | 0.138664E+11 | 0.215119E+11 | 0.286810E+11 |
Minimum of Months | 0.772114E+09 | 0.273765E+09 | 0.486728E+09 | 0.132628E+09 | 0.661479E+09 |
Maximum of Months | 0.355514E+10 | 0.167998E+10 | 0.188587E+10 | 0.408024E+10 | 0.507631E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.997873E+09 | 0.416543E+09 | 0.581330E+09 | 0.217264E+09 | 0.507631E+10 |
February | 0.141632E+10 | 0.604139E+09 | 0.812181E+09 | 0.580271E+09 | 0.369132E+10 |
March | 0.213659E+10 | 0.107175E+10 | 0.106485E+10 | 0.126340E+10 | 0.330348E+10 |
April | 0.286639E+10 | 0.154607E+10 | 0.132032E+10 | 0.230534E+10 | 0.195804E+10 |
May | 0.320569E+10 | 0.140926E+10 | 0.179643E+10 | 0.311241E+10 | 0.106694E+10 |
June | 0.351199E+10 | 0.167998E+10 | 0.183201E+10 | 0.387402E+10 | 0.725414E+09 |
July | 0.355514E+10 | 0.166927E+10 | 0.188587E+10 | 0.408024E+10 | 0.661479E+09 |
August | 0.274102E+10 | 0.119802E+10 | 0.154300E+10 | 0.296961E+10 | 0.782831E+09 |
September | 0.212429E+10 | 0.950821E+09 | 0.117347E+10 | 0.193611E+10 | 0.122632E+10 |
October | 0.132917E+10 | 0.504019E+09 | 0.825152E+09 | 0.775922E+09 | 0.207983E+10 |
November | 0.818865E+09 | 0.273765E+09 | 0.545100E+09 | 0.264670E+09 | 0.313324E+10 |
December | 0.772114E+09 | 0.285386E+09 | 0.486728E+09 | 0.132628E+09 | 0.497583E+10 |
Annual Sum or Average | 0.254755E+11 | 0.116090E+11 | 0.138664E+11 | 0.215119E+11 | 0.286810E+11 |
Minimum of Months | 0.772114E+09 | 0.273765E+09 | 0.486728E+09 | 0.132628E+09 | 0.661479E+09 |
Maximum of Months | 0.355514E+10 | 0.167998E+10 | 0.188587E+10 | 0.408024E+10 | 0.507631E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.997855E+09 | 0.416536E+09 | 0.581319E+09 | 0.217260E+09 | 0.507621E+10 |
February | 0.141629E+10 | 0.604128E+09 | 0.812166E+09 | 0.580260E+09 | 0.369126E+10 |
March | 0.213655E+10 | 0.107173E+10 | 0.106483E+10 | 0.126338E+10 | 0.330342E+10 |
April | 0.286634E+10 | 0.154605E+10 | 0.132029E+10 | 0.230530E+10 | 0.195801E+10 |
May | 0.320563E+10 | 0.140923E+10 | 0.179640E+10 | 0.311235E+10 | 0.106692E+10 |
June | 0.351193E+10 | 0.167995E+10 | 0.183198E+10 | 0.387395E+10 | 0.725400E+09 |
July | 0.355508E+10 | 0.166924E+10 | 0.188584E+10 | 0.408017E+10 | 0.661467E+09 |
August | 0.274097E+10 | 0.119800E+10 | 0.154297E+10 | 0.296956E+10 | 0.782817E+09 |
September | 0.212425E+10 | 0.950803E+09 | 0.117345E+10 | 0.193607E+10 | 0.122630E+10 |
October | 0.132915E+10 | 0.504010E+09 | 0.825137E+09 | 0.775908E+09 | 0.207979E+10 |
November | 0.818850E+09 | 0.273760E+09 | 0.545090E+09 | 0.264666E+09 | 0.313318E+10 |
December | 0.772100E+09 | 0.285380E+09 | 0.486719E+09 | 0.132625E+09 | 0.497574E+10 |
Annual Sum or Average | 0.254750E+11 | 0.116088E+11 | 0.138662E+11 | 0.215115E+11 | 0.286805E+11 |
Minimum of Months | 0.772100E+09 | 0.273760E+09 | 0.486719E+09 | 0.132625E+09 | 0.661467E+09 |
Maximum of Months | 0.355508E+10 | 0.167995E+10 | 0.188584E+10 | 0.408017E+10 | 0.507621E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282077E+10 | 0.196235E+10 | 0.858423E+09 | 0.187690E+10 | 0.395463E+10 |
February | 0.322611E+10 | 0.217903E+10 | 0.104708E+10 | 0.254561E+10 | 0.301677E+10 |
March | 0.314716E+10 | 0.199172E+10 | 0.115545E+10 | 0.257538E+10 | 0.284265E+10 |
April | 0.275925E+10 | 0.149765E+10 | 0.126161E+10 | 0.253693E+10 | 0.185967E+10 |
May | 0.239713E+10 | 0.819523E+09 | 0.157761E+10 | 0.247080E+10 | 0.105792E+10 |
June | 0.208152E+10 | 0.554815E+09 | 0.152670E+10 | 0.234774E+10 | 0.705363E+09 |
July | 0.235163E+10 | 0.744986E+09 | 0.160665E+10 | 0.280923E+10 | 0.659339E+09 |
August | 0.251141E+10 | 0.105050E+10 | 0.146090E+10 | 0.288331E+10 | 0.778227E+09 |
September | 0.260332E+10 | 0.138646E+10 | 0.121686E+10 | 0.270828E+10 | 0.116277E+10 |
October | 0.229715E+10 | 0.135107E+10 | 0.946081E+09 | 0.201898E+10 | 0.181486E+10 |
November | 0.198025E+10 | 0.124280E+10 | 0.737441E+09 | 0.146087E+10 | 0.254532E+10 |
December | 0.217797E+10 | 0.142812E+10 | 0.749849E+09 | 0.130542E+10 | 0.390525E+10 |
Annual Sum or Average | 0.303537E+11 | 0.162090E+11 | 0.141446E+11 | 0.275395E+11 | 0.243028E+11 |
Minimum of Months | 0.198025E+10 | 0.554815E+09 | 0.737441E+09 | 0.130542E+10 | 0.659339E+09 |
Maximum of Months | 0.322611E+10 | 0.217903E+10 | 0.160665E+10 | 0.288331E+10 | 0.395463E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282077E+10 | 0.196234E+10 | 0.858422E+09 | 0.187689E+10 | 0.395463E+10 |
February | 0.322611E+10 | 0.217903E+10 | 0.104708E+10 | 0.254561E+10 | 0.301677E+10 |
March | 0.314716E+10 | 0.199171E+10 | 0.115544E+10 | 0.257538E+10 | 0.284265E+10 |
April | 0.275925E+10 | 0.149764E+10 | 0.126161E+10 | 0.253693E+10 | 0.185967E+10 |
May | 0.239713E+10 | 0.819522E+09 | 0.157761E+10 | 0.247080E+10 | 0.105792E+10 |
June | 0.208151E+10 | 0.554815E+09 | 0.152670E+10 | 0.234774E+10 | 0.705363E+09 |
July | 0.235163E+10 | 0.744985E+09 | 0.160664E+10 | 0.280923E+10 | 0.659339E+09 |
August | 0.251141E+10 | 0.105050E+10 | 0.146090E+10 | 0.288331E+10 | 0.778227E+09 |
September | 0.260331E+10 | 0.138646E+10 | 0.121685E+10 | 0.270827E+10 | 0.116277E+10 |
October | 0.229715E+10 | 0.135107E+10 | 0.946080E+09 | 0.201898E+10 | 0.181486E+10 |
November | 0.198024E+10 | 0.124280E+10 | 0.737440E+09 | 0.146087E+10 | 0.254532E+10 |
December | 0.217797E+10 | 0.142812E+10 | 0.749848E+09 | 0.130541E+10 | 0.390526E+10 |
Annual Sum or Average | 0.303536E+11 | 0.162090E+11 | 0.141446E+11 | 0.275394E+11 | 0.243028E+11 |
Minimum of Months | 0.198024E+10 | 0.554815E+09 | 0.737440E+09 | 0.130541E+10 | 0.659339E+09 |
Maximum of Months | 0.322611E+10 | 0.217903E+10 | 0.160664E+10 | 0.288331E+10 | 0.395463E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282077E+10 | 0.196235E+10 | 0.858423E+09 | 0.187690E+10 | 0.395463E+10 |
February | 0.322611E+10 | 0.217903E+10 | 0.104708E+10 | 0.254561E+10 | 0.301677E+10 |
March | 0.314716E+10 | 0.199172E+10 | 0.115545E+10 | 0.257538E+10 | 0.284265E+10 |
April | 0.275925E+10 | 0.149765E+10 | 0.126161E+10 | 0.253693E+10 | 0.185967E+10 |
May | 0.239713E+10 | 0.819523E+09 | 0.157761E+10 | 0.247080E+10 | 0.105792E+10 |
June | 0.208152E+10 | 0.554815E+09 | 0.152670E+10 | 0.234774E+10 | 0.705363E+09 |
July | 0.235163E+10 | 0.744986E+09 | 0.160665E+10 | 0.280923E+10 | 0.659339E+09 |
August | 0.251141E+10 | 0.105050E+10 | 0.146090E+10 | 0.288331E+10 | 0.778227E+09 |
September | 0.260332E+10 | 0.138646E+10 | 0.121686E+10 | 0.270828E+10 | 0.116277E+10 |
October | 0.229715E+10 | 0.135107E+10 | 0.946081E+09 | 0.201898E+10 | 0.181486E+10 |
November | 0.198025E+10 | 0.124280E+10 | 0.737441E+09 | 0.146087E+10 | 0.254532E+10 |
December | 0.217797E+10 | 0.142812E+10 | 0.749849E+09 | 0.130542E+10 | 0.390525E+10 |
Annual Sum or Average | 0.303537E+11 | 0.162090E+11 | 0.141446E+11 | 0.275395E+11 | 0.243028E+11 |
Minimum of Months | 0.198025E+10 | 0.554815E+09 | 0.737441E+09 | 0.130542E+10 | 0.659339E+09 |
Maximum of Months | 0.322611E+10 | 0.217903E+10 | 0.160665E+10 | 0.288331E+10 | 0.395463E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282077E+10 | 0.196234E+10 | 0.858422E+09 | 0.187689E+10 | 0.395463E+10 |
February | 0.322611E+10 | 0.217903E+10 | 0.104708E+10 | 0.254561E+10 | 0.301677E+10 |
March | 0.314716E+10 | 0.199171E+10 | 0.115544E+10 | 0.257538E+10 | 0.284265E+10 |
April | 0.275925E+10 | 0.149764E+10 | 0.126161E+10 | 0.253693E+10 | 0.185967E+10 |
May | 0.239713E+10 | 0.819522E+09 | 0.157761E+10 | 0.247080E+10 | 0.105792E+10 |
June | 0.208151E+10 | 0.554815E+09 | 0.152670E+10 | 0.234774E+10 | 0.705363E+09 |
July | 0.235163E+10 | 0.744985E+09 | 0.160664E+10 | 0.280923E+10 | 0.659339E+09 |
August | 0.251141E+10 | 0.105050E+10 | 0.146090E+10 | 0.288331E+10 | 0.778227E+09 |
September | 0.260331E+10 | 0.138646E+10 | 0.121685E+10 | 0.270827E+10 | 0.116277E+10 |
October | 0.229715E+10 | 0.135107E+10 | 0.946080E+09 | 0.201898E+10 | 0.181486E+10 |
November | 0.198024E+10 | 0.124280E+10 | 0.737440E+09 | 0.146087E+10 | 0.254532E+10 |
December | 0.217797E+10 | 0.142812E+10 | 0.749848E+09 | 0.130541E+10 | 0.390526E+10 |
Annual Sum or Average | 0.303536E+11 | 0.162090E+11 | 0.141446E+11 | 0.275394E+11 | 0.243028E+11 |
Minimum of Months | 0.198024E+10 | 0.554815E+09 | 0.737440E+09 | 0.130541E+10 | 0.659339E+09 |
Maximum of Months | 0.322611E+10 | 0.217903E+10 | 0.160664E+10 | 0.288331E+10 | 0.395463E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282065E+10 | 0.196227E+10 | 0.858388E+09 | 0.187682E+10 | 0.395447E+10 |
February | 0.322598E+10 | 0.217894E+10 | 0.104704E+10 | 0.254551E+10 | 0.301665E+10 |
March | 0.314704E+10 | 0.199164E+10 | 0.115540E+10 | 0.257528E+10 | 0.284253E+10 |
April | 0.275914E+10 | 0.149759E+10 | 0.126156E+10 | 0.253683E+10 | 0.185960E+10 |
May | 0.239704E+10 | 0.819490E+09 | 0.157755E+10 | 0.247070E+10 | 0.105787E+10 |
June | 0.208143E+10 | 0.554793E+09 | 0.152664E+10 | 0.234765E+10 | 0.705334E+09 |
July | 0.235154E+10 | 0.744956E+09 | 0.160658E+10 | 0.280912E+10 | 0.659313E+09 |
August | 0.251131E+10 | 0.105046E+10 | 0.146085E+10 | 0.288319E+10 | 0.778196E+09 |
September | 0.260321E+10 | 0.138641E+10 | 0.121681E+10 | 0.270817E+10 | 0.116273E+10 |
October | 0.229706E+10 | 0.135101E+10 | 0.946043E+09 | 0.201890E+10 | 0.181479E+10 |
November | 0.198017E+10 | 0.124275E+10 | 0.737411E+09 | 0.146081E+10 | 0.254522E+10 |
December | 0.217788E+10 | 0.142806E+10 | 0.749819E+09 | 0.130536E+10 | 0.390510E+10 |
Annual Sum or Average | 0.303524E+11 | 0.162084E+11 | 0.141441E+11 | 0.275384E+11 | 0.243018E+11 |
Minimum of Months | 0.198017E+10 | 0.554793E+09 | 0.737411E+09 | 0.130536E+10 | 0.659313E+09 |
Maximum of Months | 0.322598E+10 | 0.217894E+10 | 0.160658E+10 | 0.288319E+10 | 0.395447E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100855E+10 | 0.422323E+09 | 0.586231E+09 | 0.257842E+09 | 0.537216E+10 |
February | 0.148421E+10 | 0.677888E+09 | 0.806321E+09 | 0.715211E+09 | 0.400694E+10 |
March | 0.216237E+10 | 0.110647E+10 | 0.105590E+10 | 0.135692E+10 | 0.362314E+10 |
April | 0.267320E+10 | 0.135395E+10 | 0.131925E+10 | 0.210382E+10 | 0.230082E+10 |
May | 0.339398E+10 | 0.161894E+10 | 0.177504E+10 | 0.342704E+10 | 0.125321E+10 |
June | 0.316947E+10 | 0.137045E+10 | 0.179901E+10 | 0.345756E+10 | 0.866273E+09 |
July | 0.349650E+10 | 0.162551E+10 | 0.187099E+10 | 0.396051E+10 | 0.860809E+09 |
August | 0.287739E+10 | 0.130747E+10 | 0.156992E+10 | 0.309925E+10 | 0.102481E+10 |
September | 0.217625E+10 | 0.977756E+09 | 0.119849E+10 | 0.201161E+10 | 0.139623E+10 |
October | 0.142058E+10 | 0.570281E+09 | 0.850294E+09 | 0.910756E+09 | 0.228039E+10 |
November | 0.834956E+09 | 0.281515E+09 | 0.553441E+09 | 0.270459E+09 | 0.340186E+10 |
December | 0.769127E+09 | 0.269200E+09 | 0.499927E+09 | 0.125435E+09 | 0.537882E+10 |
Annual Sum or Average | 0.254666E+11 | 0.115818E+11 | 0.138848E+11 | 0.216964E+11 | 0.317655E+11 |
Minimum of Months | 0.769127E+09 | 0.269200E+09 | 0.499927E+09 | 0.125435E+09 | 0.860809E+09 |
Maximum of Months | 0.349650E+10 | 0.162551E+10 | 0.187099E+10 | 0.396051E+10 | 0.537882E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100855E+10 | 0.422323E+09 | 0.586231E+09 | 0.257842E+09 | 0.537216E+10 |
February | 0.148421E+10 | 0.677888E+09 | 0.806321E+09 | 0.715211E+09 | 0.400694E+10 |
March | 0.216237E+10 | 0.110647E+10 | 0.105590E+10 | 0.135692E+10 | 0.362314E+10 |
April | 0.267320E+10 | 0.135395E+10 | 0.131925E+10 | 0.210382E+10 | 0.230082E+10 |
May | 0.339398E+10 | 0.161894E+10 | 0.177504E+10 | 0.342704E+10 | 0.125321E+10 |
June | 0.316947E+10 | 0.137045E+10 | 0.179901E+10 | 0.345756E+10 | 0.866273E+09 |
July | 0.349650E+10 | 0.162551E+10 | 0.187099E+10 | 0.396051E+10 | 0.860809E+09 |
August | 0.287739E+10 | 0.130747E+10 | 0.156992E+10 | 0.309925E+10 | 0.102481E+10 |
September | 0.217625E+10 | 0.977756E+09 | 0.119849E+10 | 0.201161E+10 | 0.139623E+10 |
October | 0.142058E+10 | 0.570281E+09 | 0.850294E+09 | 0.910756E+09 | 0.228039E+10 |
November | 0.834956E+09 | 0.281515E+09 | 0.553441E+09 | 0.270459E+09 | 0.340186E+10 |
December | 0.769127E+09 | 0.269200E+09 | 0.499927E+09 | 0.125435E+09 | 0.537882E+10 |
Annual Sum or Average | 0.254666E+11 | 0.115818E+11 | 0.138848E+11 | 0.216964E+11 | 0.317655E+11 |
Minimum of Months | 0.769127E+09 | 0.269200E+09 | 0.499927E+09 | 0.125435E+09 | 0.860809E+09 |
Maximum of Months | 0.349650E+10 | 0.162551E+10 | 0.187099E+10 | 0.396051E+10 | 0.537882E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100854E+10 | 0.422315E+09 | 0.586220E+09 | 0.257837E+09 | 0.537206E+10 |
February | 0.148418E+10 | 0.677875E+09 | 0.806306E+09 | 0.715198E+09 | 0.400687E+10 |
March | 0.216233E+10 | 0.110645E+10 | 0.105588E+10 | 0.135689E+10 | 0.362307E+10 |
April | 0.267315E+10 | 0.135392E+10 | 0.131922E+10 | 0.210378E+10 | 0.230078E+10 |
May | 0.339392E+10 | 0.161891E+10 | 0.177500E+10 | 0.342697E+10 | 0.125318E+10 |
June | 0.316941E+10 | 0.137043E+10 | 0.179898E+10 | 0.345749E+10 | 0.866257E+09 |
July | 0.349644E+10 | 0.162548E+10 | 0.187096E+10 | 0.396043E+10 | 0.860793E+09 |
August | 0.287734E+10 | 0.130744E+10 | 0.156989E+10 | 0.309919E+10 | 0.102480E+10 |
September | 0.217621E+10 | 0.977738E+09 | 0.119847E+10 | 0.201157E+10 | 0.139620E+10 |
October | 0.142055E+10 | 0.570271E+09 | 0.850279E+09 | 0.910739E+09 | 0.228035E+10 |
November | 0.834941E+09 | 0.281510E+09 | 0.553430E+09 | 0.270454E+09 | 0.340179E+10 |
December | 0.769113E+09 | 0.269195E+09 | 0.499918E+09 | 0.125433E+09 | 0.537872E+10 |
Annual Sum or Average | 0.254661E+11 | 0.115815E+11 | 0.138846E+11 | 0.216960E+11 | 0.317649E+11 |
Minimum of Months | 0.769113E+09 | 0.269195E+09 | 0.499918E+09 | 0.125433E+09 | 0.860793E+09 |
Maximum of Months | 0.349644E+10 | 0.162548E+10 | 0.187096E+10 | 0.396043E+10 | 0.537872E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204815E+10 | 0.00 | 0.204815E+10 | 2911096.12 | 0.250719E+11 |
February | 0.284165E+10 | 0.00 | 0.284165E+10 | 71357880.51 | 0.183774E+11 |
March | 0.387075E+10 | 0.00 | 0.387075E+10 | 0.201856E+09 | 0.160968E+11 |
April | 0.491062E+10 | 38326803.89 | 0.487229E+10 | 0.142972E+10 | 0.911368E+10 |
May | 0.713682E+10 | 0.384307E+09 | 0.675252E+10 | 0.521433E+10 | 0.465851E+10 |
June | 0.770788E+10 | 0.847302E+09 | 0.686058E+10 | 0.742997E+10 | 0.308041E+10 |
July | 0.760764E+10 | 0.652880E+09 | 0.695476E+10 | 0.786654E+10 | 0.291804E+10 |
August | 0.577825E+10 | 99230155.17 | 0.567901E+10 | 0.531744E+10 | 0.338260E+10 |
September | 0.435757E+10 | 1068179.80 | 0.435650E+10 | 0.263658E+10 | 0.550733E+10 |
October | 0.312653E+10 | 0.00 | 0.312653E+10 | 0.605201E+09 | 0.932874E+10 |
November | 0.200338E+10 | 0.00 | 0.200338E+10 | 74248998.35 | 0.143294E+11 |
December | 0.173536E+10 | 0.00 | 0.173536E+10 | 0.00 | 0.239483E+11 |
Annual Sum or Average | 0.531246E+11 | 0.202311E+10 | 0.511015E+11 | 0.308501E+11 | 0.135813E+12 |
Minimum of Months | 0.173536E+10 | 0.00 | 0.173536E+10 | 0.00 | 0.291804E+10 |
Maximum of Months | 0.770788E+10 | 0.847302E+09 | 0.695476E+10 | 0.786654E+10 | 0.250719E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.299359E+10 | 0.124962E+10 | 0.174397E+10 | 0.649162E+09 | 0.149927E+11 |
February | 0.424892E+10 | 0.181240E+10 | 0.243652E+10 | 0.175988E+10 | 0.108325E+11 |
March | 0.640971E+10 | 0.321521E+10 | 0.319451E+10 | 0.377865E+10 | 0.966319E+10 |
April | 0.859908E+10 | 0.463817E+10 | 0.396091E+10 | 0.686606E+10 | 0.559969E+10 |
May | 0.961696E+10 | 0.422772E+10 | 0.538923E+10 | 0.922208E+10 | 0.309741E+10 |
June | 0.105359E+11 | 0.503989E+10 | 0.549598E+10 | 0.115117E+11 | 0.209246E+10 |
July | 0.106653E+11 | 0.500776E+10 | 0.565755E+10 | 0.121430E+11 | 0.194445E+10 |
August | 0.822298E+10 | 0.359402E+10 | 0.462896E+10 | 0.884464E+10 | 0.224294E+10 |
September | 0.637280E+10 | 0.285243E+10 | 0.352037E+10 | 0.576244E+10 | 0.350813E+10 |
October | 0.398747E+10 | 0.151204E+10 | 0.247543E+10 | 0.233644E+10 | 0.587310E+10 |
November | 0.245657E+10 | 0.821288E+09 | 0.163528E+10 | 0.813244E+09 | 0.879638E+10 |
December | 0.231632E+10 | 0.856148E+09 | 0.146017E+10 | 0.401580E+09 | 0.145539E+11 |
Annual Sum or Average | 0.764256E+11 | 0.348267E+11 | 0.415989E+11 | 0.640888E+11 | 0.831968E+11 |
Minimum of Months | 0.231632E+10 | 0.821288E+09 | 0.146017E+10 | 0.401580E+09 | 0.194445E+10 |
Maximum of Months | 0.106653E+11 | 0.503989E+10 | 0.565755E+10 | 0.121430E+11 | 0.149927E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141037E+11 | 0.981161E+10 | 0.429206E+10 | 0.926678E+10 | 0.198338E+11 |
February | 0.161304E+11 | 0.108950E+11 | 0.523536E+10 | 0.125421E+11 | 0.150780E+11 |
March | 0.157356E+11 | 0.995846E+10 | 0.577716E+10 | 0.127053E+11 | 0.141565E+11 |
April | 0.137961E+11 | 0.748814E+10 | 0.630796E+10 | 0.125602E+11 | 0.909946E+10 |
May | 0.119855E+11 | 0.409757E+10 | 0.788796E+10 | 0.122353E+11 | 0.522622E+10 |
June | 0.104075E+11 | 0.277404E+10 | 0.763341E+10 | 0.116917E+11 | 0.342513E+10 |
July | 0.117580E+11 | 0.372488E+10 | 0.803313E+10 | 0.139881E+11 | 0.322231E+10 |
August | 0.125569E+11 | 0.525245E+10 | 0.730444E+10 | 0.143562E+11 | 0.373951E+10 |
September | 0.130164E+11 | 0.693222E+10 | 0.608420E+10 | 0.133973E+11 | 0.575432E+10 |
October | 0.114856E+11 | 0.675526E+10 | 0.473035E+10 | 0.100020E+11 | 0.892707E+10 |
November | 0.990111E+10 | 0.621395E+10 | 0.368716E+10 | 0.726411E+10 | 0.123611E+11 |
December | 0.108897E+11 | 0.714052E+10 | 0.374920E+10 | 0.648167E+10 | 0.194094E+11 |
Annual Sum or Average | 0.151767E+12 | 0.810441E+11 | 0.707224E+11 | 0.136491E+12 | 0.120233E+12 |
Minimum of Months | 0.990111E+10 | 0.277404E+10 | 0.368716E+10 | 0.648167E+10 | 0.322231E+10 |
Maximum of Months | 0.161304E+11 | 0.108950E+11 | 0.803313E+10 | 0.143562E+11 | 0.198338E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302563E+10 | 0.126696E+10 | 0.175867E+10 | 0.785001E+09 | 0.156274E+11 |
February | 0.445258E+10 | 0.203364E+10 | 0.241894E+10 | 0.218057E+10 | 0.114737E+11 |
March | 0.648703E+10 | 0.331937E+10 | 0.316766E+10 | 0.414048E+10 | 0.101738E+11 |
April | 0.801951E+10 | 0.406180E+10 | 0.395770E+10 | 0.647984E+10 | 0.614055E+10 |
May | 0.101818E+11 | 0.485678E+10 | 0.532505E+10 | 0.103814E+11 | 0.351347E+10 |
June | 0.950830E+10 | 0.411132E+10 | 0.539699E+10 | 0.105205E+11 | 0.234714E+10 |
July | 0.104894E+11 | 0.487649E+10 | 0.561292E+10 | 0.120713E+11 | 0.229781E+10 |
August | 0.863208E+10 | 0.392237E+10 | 0.470971E+10 | 0.956394E+10 | 0.256143E+10 |
September | 0.652868E+10 | 0.293324E+10 | 0.359544E+10 | 0.616530E+10 | 0.382803E+10 |
October | 0.426168E+10 | 0.171083E+10 | 0.255086E+10 | 0.283401E+10 | 0.620100E+10 |
November | 0.250484E+10 | 0.844538E+09 | 0.166030E+10 | 0.875476E+09 | 0.917875E+10 |
December | 0.230736E+10 | 0.807592E+09 | 0.149977E+10 | 0.395905E+09 | 0.152048E+11 |
Annual Sum or Average | 0.763989E+11 | 0.347449E+11 | 0.416540E+11 | 0.663937E+11 | 0.885477E+11 |
Minimum of Months | 0.230736E+10 | 0.807592E+09 | 0.149977E+10 | 0.395905E+09 | 0.229781E+10 |
Maximum of Months | 0.104894E+11 | 0.487649E+10 | 0.561292E+10 | 0.120713E+11 | 0.156274E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204815E+10 | 0.00 | 0.204815E+10 | 5147764.17 | 0.246674E+11 |
February | 0.284165E+10 | 0.00 | 0.284165E+10 | 82759066.79 | 0.179287E+11 |
March | 0.387075E+10 | 0.00 | 0.387075E+10 | 0.240959E+09 | 0.154480E+11 |
April | 0.491062E+10 | 38326803.89 | 0.487229E+10 | 0.156223E+10 | 0.840406E+10 |
May | 0.713682E+10 | 0.384307E+09 | 0.675252E+10 | 0.545001E+10 | 0.423164E+10 |
June | 0.770788E+10 | 0.847302E+09 | 0.686058E+10 | 0.765112E+10 | 0.280786E+10 |
July | 0.760764E+10 | 0.652880E+09 | 0.695476E+10 | 0.805069E+10 | 0.268835E+10 |
August | 0.577825E+10 | 99230155.17 | 0.567901E+10 | 0.551191E+10 | 0.304973E+10 |
September | 0.435757E+10 | 1068179.80 | 0.435650E+10 | 0.284578E+10 | 0.494243E+10 |
October | 0.312653E+10 | 0.00 | 0.312653E+10 | 0.728804E+09 | 0.840424E+10 |
November | 0.200338E+10 | 0.00 | 0.200338E+10 | 84721079.64 | 0.135812E+11 |
December | 0.173536E+10 | 0.00 | 0.173536E+10 | 0.00 | 0.234797E+11 |
Annual Sum or Average | 0.531246E+11 | 0.202311E+10 | 0.511015E+11 | 0.322141E+11 | 0.129633E+12 |
Minimum of Months | 0.173536E+10 | 0.00 | 0.173536E+10 | 0.00 | 0.268835E+10 |
Maximum of Months | 0.770788E+10 | 0.847302E+09 | 0.695476E+10 | 0.805069E+10 | 0.246674E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.299359E+10 | 0.124962E+10 | 0.174397E+10 | 0.662251E+09 | 0.148041E+11 |
February | 0.424892E+10 | 0.181240E+10 | 0.243652E+10 | 0.180819E+10 | 0.105577E+11 |
March | 0.640971E+10 | 0.321521E+10 | 0.319451E+10 | 0.388849E+10 | 0.923018E+10 |
April | 0.859908E+10 | 0.463817E+10 | 0.396091E+10 | 0.701788E+10 | 0.516876E+10 |
May | 0.961696E+10 | 0.422772E+10 | 0.538923E+10 | 0.934713E+10 | 0.288083E+10 |
June | 0.105359E+11 | 0.503989E+10 | 0.549598E+10 | 0.115665E+11 | 0.195754E+10 |
July | 0.106653E+11 | 0.500776E+10 | 0.565755E+10 | 0.121660E+11 | 0.184220E+10 |
August | 0.822298E+10 | 0.359402E+10 | 0.462896E+10 | 0.891376E+10 | 0.208887E+10 |
September | 0.637280E+10 | 0.285243E+10 | 0.352037E+10 | 0.591987E+10 | 0.319259E+10 |
October | 0.398747E+10 | 0.151204E+10 | 0.247543E+10 | 0.249520E+10 | 0.528028E+10 |
November | 0.245657E+10 | 0.821288E+09 | 0.163528E+10 | 0.861238E+09 | 0.830793E+10 |
December | 0.231632E+10 | 0.856148E+09 | 0.146017E+10 | 0.413544E+09 | 0.143256E+11 |
Annual Sum or Average | 0.764256E+11 | 0.348267E+11 | 0.415989E+11 | 0.650600E+11 | 0.796366E+11 |
Minimum of Months | 0.231632E+10 | 0.821288E+09 | 0.146017E+10 | 0.413544E+09 | 0.184220E+10 |
Maximum of Months | 0.106653E+11 | 0.503989E+10 | 0.565755E+10 | 0.121660E+11 | 0.148041E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141037E+11 | 0.981161E+10 | 0.429206E+10 | 0.935545E+10 | 0.193925E+11 |
February | 0.161304E+11 | 0.108950E+11 | 0.523536E+10 | 0.126574E+11 | 0.145483E+11 |
March | 0.157356E+11 | 0.995846E+10 | 0.577716E+10 | 0.128545E+11 | 0.134330E+11 |
April | 0.137961E+11 | 0.748814E+10 | 0.630796E+10 | 0.127098E+11 | 0.837204E+10 |
May | 0.119855E+11 | 0.409757E+10 | 0.788796E+10 | 0.123741E+11 | 0.478186E+10 |
June | 0.104075E+11 | 0.277404E+10 | 0.763341E+10 | 0.117841E+11 | 0.313961E+10 |
July | 0.117580E+11 | 0.372488E+10 | 0.803313E+10 | 0.140505E+11 | 0.298528E+10 |
August | 0.125569E+11 | 0.525245E+10 | 0.730444E+10 | 0.144444E+11 | 0.341862E+10 |
September | 0.130164E+11 | 0.693222E+10 | 0.608420E+10 | 0.135565E+11 | 0.521992E+10 |
October | 0.114856E+11 | 0.675526E+10 | 0.473035E+10 | 0.102171E+11 | 0.804085E+10 |
November | 0.990111E+10 | 0.621395E+10 | 0.368716E+10 | 0.741928E+10 | 0.115982E+11 |
December | 0.108897E+11 | 0.714052E+10 | 0.374920E+10 | 0.658279E+10 | 0.189101E+11 |
Annual Sum or Average | 0.151767E+12 | 0.810441E+11 | 0.707224E+11 | 0.138006E+12 | 0.113840E+12 |
Minimum of Months | 0.990111E+10 | 0.277404E+10 | 0.368716E+10 | 0.658279E+10 | 0.298528E+10 |
Maximum of Months | 0.161304E+11 | 0.108950E+11 | 0.803313E+10 | 0.144444E+11 | 0.193925E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302563E+10 | 0.126696E+10 | 0.175867E+10 | 0.792400E+09 | 0.153734E+11 |
February | 0.445258E+10 | 0.203364E+10 | 0.241894E+10 | 0.218676E+10 | 0.111923E+11 |
March | 0.648703E+10 | 0.331937E+10 | 0.316766E+10 | 0.416474E+10 | 0.977353E+10 |
April | 0.801951E+10 | 0.406180E+10 | 0.395770E+10 | 0.652090E+10 | 0.573103E+10 |
May | 0.101818E+11 | 0.485678E+10 | 0.532505E+10 | 0.104060E+11 | 0.328658E+10 |
June | 0.950830E+10 | 0.411132E+10 | 0.539699E+10 | 0.105216E+11 | 0.221016E+10 |
July | 0.104894E+11 | 0.487649E+10 | 0.561292E+10 | 0.120584E+11 | 0.218343E+10 |
August | 0.863208E+10 | 0.392237E+10 | 0.470971E+10 | 0.957515E+10 | 0.241012E+10 |
September | 0.652868E+10 | 0.293324E+10 | 0.359544E+10 | 0.620740E+10 | 0.355015E+10 |
October | 0.426168E+10 | 0.171083E+10 | 0.255086E+10 | 0.289210E+10 | 0.569714E+10 |
November | 0.250484E+10 | 0.844538E+09 | 0.166030E+10 | 0.901645E+09 | 0.874877E+10 |
December | 0.230736E+10 | 0.807592E+09 | 0.149977E+10 | 0.399833E+09 | 0.149317E+11 |
Annual Sum or Average | 0.763989E+11 | 0.347449E+11 | 0.416540E+11 | 0.666269E+11 | 0.850883E+11 |
Minimum of Months | 0.230736E+10 | 0.807592E+09 | 0.149977E+10 | 0.399833E+09 | 0.218343E+10 |
Maximum of Months | 0.104894E+11 | 0.487649E+10 | 0.561292E+10 | 0.120584E+11 | 0.153734E+11 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.03 | 9475.21 | 764.69 | 0.00 | 764.69 | 0.00 | 0.00 |
February | 15.89 | 7782.86 | 1174.63 | 0.00 | 1174.63 | 0.00 | 0.00 |
March | 53.79 | 6252.01 | 1445.18 | 0.00 | 1445.18 | 0.00 | 0.00 |
April | 467.83 | 3833.90 | 1894.54 | 14.79 | 1879.75 | 0.00 | 0.00 |
May | 1865.89 | 1858.23 | 2664.59 | 143.48 | 2521.11 | 0.00 | 0.00 |
June | 2790.70 | 1277.61 | 2973.73 | 326.89 | 2646.84 | 0.00 | 0.00 |
July | 2862.95 | 1166.65 | 2840.38 | 243.76 | 2596.62 | 0.00 | 0.00 |
August | 1875.66 | 1430.92 | 2157.36 | 37.05 | 2120.31 | 0.00 | 0.00 |
September | 919.93 | 2331.49 | 1681.17 | 0.41 | 1680.75 | 0.00 | 0.00 |
October | 168.87 | 3822.02 | 1167.32 | 0.00 | 1167.32 | 0.00 | 0.00 |
November | 21.34 | 5982.45 | 772.91 | 0.00 | 772.91 | 0.00 | 0.00 |
December | 0.00 | 9162.54 | 647.91 | 0.00 | 647.91 | 0.00 | 0.00 |
Annual Sum or Average | 926.25 | 4517.48 | 1684.58 | 64.15 | 1620.42 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 1166.65 | 647.91 | 0.00 | 647.91 | 0.00 | 0.00 |
Maximum of Months | 2862.95 | 9475.21 | 2973.73 | 326.89 | 2646.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 243.35 | 5685.79 | 1117.68 | 466.56 | 651.13 | 0.00 | 0.00 |
February | 719.58 | 4577.51 | 1756.34 | 749.18 | 1007.16 | 0.00 | 0.00 |
March | 1415.09 | 3700.12 | 2393.12 | 1200.43 | 1192.70 | 0.00 | 0.00 |
April | 2668.21 | 2266.24 | 3317.56 | 1789.43 | 1528.14 | 0.00 | 0.00 |
May | 3486.10 | 1195.04 | 3590.58 | 1578.46 | 2012.12 | 0.00 | 0.00 |
June | 4483.79 | 839.59 | 4064.78 | 1944.41 | 2120.37 | 0.00 | 0.00 |
July | 4570.14 | 740.90 | 3981.99 | 1869.69 | 2112.30 | 0.00 | 0.00 |
August | 3326.16 | 876.82 | 3070.12 | 1341.86 | 1728.26 | 0.00 | 0.00 |
September | 2240.85 | 1419.34 | 2458.65 | 1100.48 | 1358.17 | 0.00 | 0.00 |
October | 869.08 | 2329.54 | 1488.76 | 564.53 | 924.22 | 0.00 | 0.00 |
November | 306.33 | 3626.41 | 947.75 | 316.86 | 630.90 | 0.00 | 0.00 |
December | 148.55 | 5573.25 | 864.82 | 319.65 | 545.17 | 0.00 | 0.00 |
Annual Sum or Average | 2046.40 | 2728.39 | 2423.45 | 1104.35 | 1319.10 | 0.00 | 0.00 |
Minimum of Months | 148.55 | 740.90 | 864.82 | 316.86 | 545.17 | 0.00 | 0.00 |
Maximum of Months | 4570.14 | 5685.79 | 4064.78 | 1944.41 | 2120.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3503.73 | 7382.39 | 5265.73 | 3663.25 | 1602.48 | 0.00 | 0.00 |
February | 5261.23 | 6235.02 | 6667.67 | 4503.58 | 2164.09 | 0.00 | 0.00 |
March | 4807.65 | 5306.57 | 5875.03 | 3718.08 | 2156.95 | 0.00 | 0.00 |
April | 4893.73 | 3587.30 | 5322.59 | 2888.95 | 2433.64 | 0.00 | 0.00 |
May | 4612.42 | 1974.89 | 4474.90 | 1529.86 | 2945.04 | 0.00 | 0.00 |
June | 4528.79 | 1360.64 | 4015.24 | 1070.24 | 2945.00 | 0.00 | 0.00 |
July | 5244.19 | 1230.84 | 4389.96 | 1390.72 | 2999.24 | 0.00 | 0.00 |
August | 5382.48 | 1452.77 | 4688.22 | 1961.05 | 2727.17 | 0.00 | 0.00 |
September | 5224.26 | 2242.99 | 5021.79 | 2674.48 | 2347.31 | 0.00 | 0.00 |
October | 3768.98 | 3387.93 | 4288.25 | 2522.13 | 1766.12 | 0.00 | 0.00 |
November | 2818.02 | 4909.91 | 3819.89 | 2397.37 | 1422.52 | 0.00 | 0.00 |
December | 2436.91 | 7290.22 | 4065.77 | 2665.98 | 1399.80 | 0.00 | 0.00 |
Annual Sum or Average | 4366.32 | 3853.15 | 4812.50 | 2569.90 | 2242.60 | 0.00 | 0.00 |
Minimum of Months | 2436.91 | 1230.84 | 3819.89 | 1070.24 | 1399.80 | 0.00 | 0.00 |
Maximum of Months | 5382.48 | 7382.39 | 6667.67 | 4503.58 | 2999.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 288.80 | 6017.16 | 1129.65 | 473.03 | 656.62 | 0.00 | 0.00 |
February | 886.91 | 4968.90 | 1840.53 | 840.63 | 999.90 | 0.00 | 0.00 |
March | 1519.83 | 4058.15 | 2421.99 | 1239.32 | 1182.67 | 0.00 | 0.00 |
April | 2434.96 | 2662.97 | 3093.96 | 1567.06 | 1526.90 | 0.00 | 0.00 |
May | 3838.50 | 1403.67 | 3801.48 | 1813.32 | 1988.15 | 0.00 | 0.00 |
June | 4001.78 | 1002.62 | 3668.34 | 1586.16 | 2082.18 | 0.00 | 0.00 |
July | 4436.02 | 964.16 | 3916.31 | 1820.68 | 2095.63 | 0.00 | 0.00 |
August | 3471.36 | 1147.86 | 3222.86 | 1464.45 | 1758.41 | 0.00 | 0.00 |
September | 2328.23 | 1615.99 | 2518.79 | 1131.66 | 1387.13 | 0.00 | 0.00 |
October | 1020.11 | 2554.19 | 1591.14 | 638.75 | 952.38 | 0.00 | 0.00 |
November | 313.03 | 3937.31 | 966.38 | 325.83 | 640.55 | 0.00 | 0.00 |
December | 140.50 | 6024.63 | 861.47 | 301.52 | 559.95 | 0.00 | 0.00 |
Annual Sum or Average | 2063.95 | 3021.81 | 2422.60 | 1101.76 | 1320.85 | 0.00 | 0.00 |
Minimum of Months | 140.50 | 964.16 | 861.47 | 301.52 | 559.95 | 0.00 | 0.00 |
Maximum of Months | 4436.02 | 6024.63 | 3916.31 | 1820.68 | 2095.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.09 | 9360.78 | 764.69 | 0.00 | 764.69 | 0.00 | 0.00 |
February | 29.50 | 7596.47 | 1174.62 | 0.00 | 1174.62 | 0.00 | 0.00 |
March | 75.36 | 6009.84 | 1445.17 | 0.00 | 1445.17 | 0.00 | 0.00 |
April | 551.59 | 3516.08 | 1894.53 | 14.79 | 1879.74 | 0.00 | 0.00 |
May | 1946.81 | 1739.29 | 2664.58 | 143.48 | 2521.10 | 0.00 | 0.00 |
June | 2866.50 | 1188.43 | 2973.72 | 326.89 | 2646.83 | 0.00 | 0.00 |
July | 2937.03 | 1089.47 | 2840.37 | 243.76 | 2596.61 | 0.00 | 0.00 |
August | 1985.30 | 1262.92 | 2157.35 | 37.05 | 2120.30 | 0.00 | 0.00 |
September | 1017.20 | 2124.74 | 1681.16 | 0.41 | 1680.75 | 0.00 | 0.00 |
October | 225.96 | 3482.95 | 1167.31 | 0.00 | 1167.31 | 0.00 | 0.00 |
November | 28.65 | 5528.31 | 772.91 | 0.00 | 772.91 | 0.00 | 0.00 |
December | 0.00 | 8941.28 | 647.91 | 0.00 | 647.91 | 0.00 | 0.00 |
Annual Sum or Average | 978.25 | 4306.60 | 1684.57 | 64.15 | 1620.42 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 1089.47 | 647.91 | 0.00 | 647.91 | 0.00 | 0.00 |
Maximum of Months | 2937.03 | 9360.78 | 2973.72 | 326.89 | 2646.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 242.37 | 5597.64 | 1117.68 | 466.55 | 651.12 | 0.00 | 0.00 |
February | 727.46 | 4477.71 | 1756.33 | 749.17 | 1007.16 | 0.00 | 0.00 |
March | 1410.79 | 3607.82 | 2393.11 | 1200.42 | 1192.69 | 0.00 | 0.00 |
April | 2648.94 | 2160.37 | 3317.55 | 1789.42 | 1528.13 | 0.00 | 0.00 |
May | 3443.13 | 1156.44 | 3590.56 | 1578.45 | 2012.11 | 0.00 | 0.00 |
June | 4441.23 | 807.27 | 4064.76 | 1944.40 | 2120.36 | 0.00 | 0.00 |
July | 4533.66 | 725.98 | 3981.97 | 1869.68 | 2112.29 | 0.00 | 0.00 |
August | 3302.21 | 837.42 | 3070.11 | 1341.85 | 1728.26 | 0.00 | 0.00 |
September | 2223.16 | 1353.45 | 2458.64 | 1100.48 | 1358.17 | 0.00 | 0.00 |
October | 872.33 | 2192.76 | 1488.75 | 564.53 | 924.22 | 0.00 | 0.00 |
November | 313.75 | 3393.66 | 947.75 | 316.85 | 630.90 | 0.00 | 0.00 |
December | 149.93 | 5433.79 | 864.81 | 319.65 | 545.16 | 0.00 | 0.00 |
Annual Sum or Average | 2032.24 | 2638.15 | 2423.44 | 1104.35 | 1319.09 | 0.00 | 0.00 |
Minimum of Months | 149.93 | 725.98 | 864.81 | 316.85 | 545.16 | 0.00 | 0.00 |
Maximum of Months | 4533.66 | 5597.64 | 4064.76 | 1944.40 | 2120.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3459.82 | 7405.11 | 5265.71 | 3663.24 | 1602.47 | 0.00 | 0.00 |
February | 5184.39 | 6232.65 | 6667.65 | 4503.56 | 2164.09 | 0.00 | 0.00 |
March | 4743.60 | 5285.42 | 5875.01 | 3718.06 | 2156.94 | 0.00 | 0.00 |
April | 4845.74 | 3510.59 | 5322.57 | 2888.94 | 2433.63 | 0.00 | 0.00 |
May | 4568.13 | 1951.25 | 4474.88 | 1529.86 | 2945.03 | 0.00 | 0.00 |
June | 4510.70 | 1321.42 | 4015.22 | 1070.23 | 2944.99 | 0.00 | 0.00 |
July | 5222.57 | 1203.07 | 4389.94 | 1390.71 | 2999.23 | 0.00 | 0.00 |
August | 5359.99 | 1396.17 | 4688.21 | 1961.04 | 2727.16 | 0.00 | 0.00 |
September | 5168.70 | 2220.03 | 5021.77 | 2674.47 | 2347.30 | 0.00 | 0.00 |
October | 3734.32 | 3332.98 | 4288.24 | 2522.13 | 1766.11 | 0.00 | 0.00 |
November | 2802.51 | 4768.93 | 3819.87 | 2397.36 | 1422.52 | 0.00 | 0.00 |
December | 2419.98 | 7246.63 | 4065.76 | 2665.97 | 1399.79 | 0.00 | 0.00 |
Annual Sum or Average | 4328.09 | 3812.56 | 4812.48 | 2569.89 | 2242.59 | 0.00 | 0.00 |
Minimum of Months | 2419.98 | 1203.07 | 3819.87 | 1070.23 | 1399.79 | 0.00 | 0.00 |
Maximum of Months | 5359.99 | 7405.11 | 6667.65 | 4503.56 | 2999.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 293.09 | 5834.59 | 1129.64 | 473.03 | 656.61 | 0.00 | 0.00 |
February | 901.36 | 4742.75 | 1840.52 | 840.63 | 999.89 | 0.00 | 0.00 |
March | 1545.88 | 3798.45 | 2421.98 | 1239.31 | 1182.67 | 0.00 | 0.00 |
April | 2499.94 | 2369.04 | 3093.95 | 1567.05 | 1526.89 | 0.00 | 0.00 |
May | 3875.98 | 1311.78 | 3801.46 | 1813.32 | 1988.15 | 0.00 | 0.00 |
June | 4058.83 | 905.53 | 3668.33 | 1586.16 | 2082.17 | 0.00 | 0.00 |
July | 4506.90 | 857.90 | 3916.29 | 1820.67 | 2095.62 | 0.00 | 0.00 |
August | 3570.77 | 956.33 | 3222.85 | 1464.44 | 1758.41 | 0.00 | 0.00 |
September | 2378.59 | 1476.86 | 2518.78 | 1131.65 | 1387.13 | 0.00 | 0.00 |
October | 1058.10 | 2315.19 | 1591.13 | 638.75 | 952.38 | 0.00 | 0.00 |
November | 337.76 | 3541.19 | 966.37 | 325.82 | 640.55 | 0.00 | 0.00 |
December | 147.81 | 5676.81 | 861.47 | 301.52 | 559.95 | 0.00 | 0.00 |
Annual Sum or Average | 2105.33 | 2807.83 | 2422.59 | 1101.75 | 1320.84 | 0.00 | 0.00 |
Minimum of Months | 147.81 | 857.90 | 861.47 | 301.52 | 559.95 | 0.00 | 0.00 |
Maximum of Months | 4506.90 | 5834.59 | 3916.29 | 1820.67 | 2095.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.92 | 9209.74 | 764.69 | 0.00 | 764.69 | 0.00 | 0.00 |
February | 34.21 | 7410.99 | 1174.62 | 0.00 | 1174.62 | 0.00 | 0.00 |
March | 89.96 | 5767.63 | 1445.17 | 0.00 | 1445.17 | 0.00 | 0.00 |
April | 602.71 | 3242.31 | 1894.53 | 14.79 | 1879.74 | 0.00 | 0.00 |
May | 2034.80 | 1579.92 | 2664.58 | 143.48 | 2521.10 | 0.00 | 0.00 |
June | 2951.82 | 1083.28 | 2973.72 | 326.89 | 2646.83 | 0.00 | 0.00 |
July | 3005.78 | 1003.72 | 2840.37 | 243.76 | 2596.61 | 0.00 | 0.00 |
August | 2057.91 | 1138.64 | 2157.35 | 37.05 | 2120.30 | 0.00 | 0.00 |
September | 1097.91 | 1906.80 | 1681.16 | 0.41 | 1680.75 | 0.00 | 0.00 |
October | 272.10 | 3137.78 | 1167.31 | 0.00 | 1167.31 | 0.00 | 0.00 |
November | 32.69 | 5239.68 | 772.91 | 0.00 | 772.91 | 0.00 | 0.00 |
December | 0.00 | 8766.32 | 647.91 | 0.00 | 647.91 | 0.00 | 0.00 |
Annual Sum or Average | 1021.50 | 4110.65 | 1684.57 | 64.15 | 1620.42 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 1003.72 | 647.91 | 0.00 | 647.91 | 0.00 | 0.00 |
Maximum of Months | 3005.78 | 9209.74 | 2973.72 | 326.89 | 2646.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 247.26 | 5527.20 | 1117.68 | 466.55 | 651.12 | 0.00 | 0.00 |
February | 747.44 | 4364.14 | 1756.33 | 749.17 | 1007.16 | 0.00 | 0.00 |
March | 1451.80 | 3446.15 | 2393.11 | 1200.42 | 1192.69 | 0.00 | 0.00 |
April | 2707.52 | 1994.12 | 3317.55 | 1789.42 | 1528.13 | 0.00 | 0.00 |
May | 3489.82 | 1075.58 | 3590.56 | 1578.45 | 2012.11 | 0.00 | 0.00 |
June | 4462.39 | 755.22 | 4064.76 | 1944.40 | 2120.36 | 0.00 | 0.00 |
July | 4542.25 | 687.80 | 3981.97 | 1869.68 | 2112.29 | 0.00 | 0.00 |
August | 3328.02 | 779.90 | 3070.11 | 1341.85 | 1728.26 | 0.00 | 0.00 |
September | 2283.90 | 1231.71 | 2458.64 | 1100.48 | 1358.17 | 0.00 | 0.00 |
October | 931.60 | 1971.43 | 1488.75 | 564.53 | 924.22 | 0.00 | 0.00 |
November | 332.27 | 3205.22 | 947.75 | 316.85 | 630.90 | 0.00 | 0.00 |
December | 154.40 | 5348.56 | 864.81 | 319.65 | 545.16 | 0.00 | 0.00 |
Annual Sum or Average | 2063.04 | 2525.26 | 2423.44 | 1104.35 | 1319.09 | 0.00 | 0.00 |
Minimum of Months | 154.40 | 687.80 | 864.81 | 316.85 | 545.16 | 0.00 | 0.00 |
Maximum of Months | 4542.25 | 5527.20 | 4064.76 | 1944.40 | 2120.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3492.93 | 7240.31 | 5265.71 | 3663.24 | 1602.47 | 0.00 | 0.00 |
February | 5232.06 | 6013.67 | 6667.65 | 4503.56 | 2164.09 | 0.00 | 0.00 |
March | 4799.32 | 5015.31 | 5875.01 | 3718.06 | 2156.94 | 0.00 | 0.00 |
April | 4903.46 | 3229.96 | 5322.57 | 2888.94 | 2433.63 | 0.00 | 0.00 |
May | 4619.98 | 1785.34 | 4474.88 | 1529.86 | 2945.03 | 0.00 | 0.00 |
June | 4546.34 | 1211.27 | 4015.22 | 1070.23 | 2944.99 | 0.00 | 0.00 |
July | 5245.85 | 1114.58 | 4389.94 | 1390.71 | 2999.23 | 0.00 | 0.00 |
August | 5392.90 | 1276.37 | 4688.21 | 1961.04 | 2727.16 | 0.00 | 0.00 |
September | 5230.13 | 2013.86 | 5021.77 | 2674.47 | 2347.30 | 0.00 | 0.00 |
October | 3814.62 | 3002.11 | 4288.24 | 2522.13 | 1766.11 | 0.00 | 0.00 |
November | 2862.38 | 4474.61 | 3819.87 | 2397.36 | 1422.52 | 0.00 | 0.00 |
December | 2457.73 | 7060.22 | 4065.76 | 2665.97 | 1399.79 | 0.00 | 0.00 |
Annual Sum or Average | 4376.14 | 3609.85 | 4812.48 | 2569.89 | 2242.59 | 0.00 | 0.00 |
Minimum of Months | 2457.73 | 1114.58 | 3819.87 | 1070.23 | 1399.79 | 0.00 | 0.00 |
Maximum of Months | 5392.90 | 7240.31 | 6667.65 | 4503.56 | 2999.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 295.85 | 5739.77 | 1129.64 | 473.03 | 656.61 | 0.00 | 0.00 |
February | 903.92 | 4626.44 | 1840.52 | 840.63 | 999.89 | 0.00 | 0.00 |
March | 1554.94 | 3649.02 | 2421.98 | 1239.31 | 1182.67 | 0.00 | 0.00 |
April | 2515.78 | 2211.05 | 3093.95 | 1567.05 | 1526.89 | 0.00 | 0.00 |
May | 3885.14 | 1227.07 | 3801.46 | 1813.32 | 1988.15 | 0.00 | 0.00 |
June | 4059.26 | 852.69 | 3668.33 | 1586.16 | 2082.17 | 0.00 | 0.00 |
July | 4502.08 | 815.20 | 3916.29 | 1820.67 | 2095.62 | 0.00 | 0.00 |
August | 3574.95 | 899.84 | 3222.85 | 1464.44 | 1758.41 | 0.00 | 0.00 |
September | 2394.83 | 1369.66 | 2518.78 | 1131.65 | 1387.13 | 0.00 | 0.00 |
October | 1079.79 | 2127.07 | 1591.13 | 638.75 | 952.38 | 0.00 | 0.00 |
November | 347.86 | 3375.30 | 966.37 | 325.82 | 640.55 | 0.00 | 0.00 |
December | 149.28 | 5574.85 | 861.47 | 301.52 | 559.95 | 0.00 | 0.00 |
Annual Sum or Average | 2112.72 | 2698.13 | 2422.59 | 1101.75 | 1320.84 | 0.00 | 0.00 |
Minimum of Months | 149.28 | 815.20 | 861.47 | 301.52 | 559.95 | 0.00 | 0.00 |
Maximum of Months | 4502.08 | 5739.77 | 3916.29 | 1820.67 | 2095.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 77469.23 | 0.253784E+11 | 0.204816E+10 | 0.00 | 0.204816E+10 | 0.00 | 0.00 |
February | 38443462.28 | 0.188283E+11 | 0.284166E+10 | 0.00 | 0.284166E+10 | 0.00 | 0.00 |
March | 0.144066E+09 | 0.167454E+11 | 0.387076E+10 | 0.00 | 0.387076E+10 | 0.00 | 0.00 |
April | 0.121261E+10 | 0.993746E+10 | 0.491064E+10 | 38326939.99 | 0.487231E+10 | 0.00 | 0.00 |
May | 0.499761E+10 | 0.497709E+10 | 0.713685E+10 | 0.384309E+09 | 0.675254E+10 | 0.00 | 0.00 |
June | 0.723350E+10 | 0.331156E+10 | 0.770791E+10 | 0.847305E+09 | 0.686060E+10 | 0.00 | 0.00 |
July | 0.766813E+10 | 0.312476E+10 | 0.760767E+10 | 0.652883E+09 | 0.695479E+10 | 0.00 | 0.00 |
August | 0.502378E+10 | 0.383258E+10 | 0.577827E+10 | 99230507.55 | 0.567904E+10 | 0.00 | 0.00 |
September | 0.238447E+10 | 0.604321E+10 | 0.435758E+10 | 1068183.59 | 0.435651E+10 | 0.00 | 0.00 |
October | 0.452295E+09 | 0.102369E+11 | 0.312654E+10 | 0.00 | 0.312654E+10 | 0.00 | 0.00 |
November | 55309730.54 | 0.155065E+11 | 0.200339E+10 | 0.00 | 0.200339E+10 | 0.00 | 0.00 |
December | 0.00 | 0.245409E+11 | 0.173536E+10 | 0.00 | 0.173536E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.292103E+11 | 0.142463E+12 | 0.531248E+11 | 0.202312E+10 | 0.511017E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.312476E+10 | 0.173536E+10 | 0.00 | 0.173536E+10 | 0.00 | 0.00 |
Maximum of Months | 0.766813E+10 | 0.253784E+11 | 0.770791E+10 | 0.847305E+09 | 0.695479E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.651788E+09 | 0.152288E+11 | 0.299360E+10 | 0.124962E+10 | 0.174398E+10 | 0.00 | 0.00 |
February | 0.174080E+10 | 0.110739E+11 | 0.424893E+10 | 0.181240E+10 | 0.243653E+10 | 0.00 | 0.00 |
March | 0.379019E+10 | 0.991039E+10 | 0.640974E+10 | 0.321522E+10 | 0.319452E+10 | 0.00 | 0.00 |
April | 0.691599E+10 | 0.587409E+10 | 0.859912E+10 | 0.463819E+10 | 0.396093E+10 | 0.00 | 0.00 |
May | 0.933716E+10 | 0.320080E+10 | 0.961700E+10 | 0.422774E+10 | 0.538926E+10 | 0.00 | 0.00 |
June | 0.116220E+11 | 0.217623E+10 | 0.105359E+11 | 0.503991E+10 | 0.549600E+10 | 0.00 | 0.00 |
July | 0.122407E+11 | 0.198442E+10 | 0.106654E+11 | 0.500778E+10 | 0.565758E+10 | 0.00 | 0.00 |
August | 0.890879E+10 | 0.234848E+10 | 0.822301E+10 | 0.359403E+10 | 0.462898E+10 | 0.00 | 0.00 |
September | 0.580828E+10 | 0.367893E+10 | 0.637283E+10 | 0.285244E+10 | 0.352038E+10 | 0.00 | 0.00 |
October | 0.232775E+10 | 0.623944E+10 | 0.398749E+10 | 0.151205E+10 | 0.247544E+10 | 0.00 | 0.00 |
November | 0.794007E+09 | 0.939967E+10 | 0.245658E+10 | 0.821291E+09 | 0.163529E+10 | 0.00 | 0.00 |
December | 0.397881E+09 | 0.149274E+11 | 0.231633E+10 | 0.856151E+09 | 0.146018E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.645353E+11 | 0.860426E+11 | 0.764259E+11 | 0.348268E+11 | 0.415990E+11 | 0.00 | 0.00 |
Minimum of Months | 0.397881E+09 | 0.198442E+10 | 0.231633E+10 | 0.821291E+09 | 0.146018E+10 | 0.00 | 0.00 |
Maximum of Months | 0.122407E+11 | 0.152288E+11 | 0.106654E+11 | 0.503991E+10 | 0.565758E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.938439E+10 | 0.197730E+11 | 0.141037E+11 | 0.981164E+10 | 0.429208E+10 | 0.00 | 0.00 |
February | 0.127280E+11 | 0.150838E+11 | 0.161304E+11 | 0.108951E+11 | 0.523538E+10 | 0.00 | 0.00 |
March | 0.128768E+11 | 0.142131E+11 | 0.157357E+11 | 0.995850E+10 | 0.577718E+10 | 0.00 | 0.00 |
April | 0.126846E+11 | 0.929828E+10 | 0.137961E+11 | 0.748816E+10 | 0.630799E+10 | 0.00 | 0.00 |
May | 0.123539E+11 | 0.528954E+10 | 0.119856E+11 | 0.409758E+10 | 0.788799E+10 | 0.00 | 0.00 |
June | 0.117386E+11 | 0.352679E+10 | 0.104075E+11 | 0.277405E+10 | 0.763344E+10 | 0.00 | 0.00 |
July | 0.140460E+11 | 0.329667E+10 | 0.117581E+11 | 0.372490E+10 | 0.803316E+10 | 0.00 | 0.00 |
August | 0.144164E+11 | 0.389110E+10 | 0.125569E+11 | 0.525247E+10 | 0.730446E+10 | 0.00 | 0.00 |
September | 0.135413E+11 | 0.581382E+10 | 0.130165E+11 | 0.693225E+10 | 0.608423E+10 | 0.00 | 0.00 |
October | 0.100948E+11 | 0.907423E+10 | 0.114857E+11 | 0.675528E+10 | 0.473037E+10 | 0.00 | 0.00 |
November | 0.730430E+10 | 0.127265E+11 | 0.990115E+10 | 0.621397E+10 | 0.368717E+10 | 0.00 | 0.00 |
December | 0.652703E+10 | 0.195261E+11 | 0.108898E+11 | 0.714055E+10 | 0.374921E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.137696E+12 | 0.121513E+12 | 0.151767E+12 | 0.810444E+11 | 0.707227E+11 | 0.00 | 0.00 |
Minimum of Months | 0.652703E+10 | 0.329667E+10 | 0.990115E+10 | 0.277405E+10 | 0.368717E+10 | 0.00 | 0.00 |
Maximum of Months | 0.144164E+11 | 0.197730E+11 | 0.161304E+11 | 0.108951E+11 | 0.803316E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.773520E+09 | 0.161164E+11 | 0.302564E+10 | 0.126696E+10 | 0.175868E+10 | 0.00 | 0.00 |
February | 0.214562E+10 | 0.120208E+11 | 0.445260E+10 | 0.203365E+10 | 0.241895E+10 | 0.00 | 0.00 |
March | 0.407072E+10 | 0.108693E+11 | 0.648706E+10 | 0.331938E+10 | 0.316767E+10 | 0.00 | 0.00 |
April | 0.631141E+10 | 0.690243E+10 | 0.801954E+10 | 0.406182E+10 | 0.395772E+10 | 0.00 | 0.00 |
May | 0.102810E+11 | 0.375960E+10 | 0.101819E+11 | 0.485680E+10 | 0.532507E+10 | 0.00 | 0.00 |
June | 0.103726E+11 | 0.259880E+10 | 0.950834E+10 | 0.411133E+10 | 0.539701E+10 | 0.00 | 0.00 |
July | 0.118814E+11 | 0.258241E+10 | 0.104894E+11 | 0.487651E+10 | 0.561294E+10 | 0.00 | 0.00 |
August | 0.929769E+10 | 0.307442E+10 | 0.863211E+10 | 0.392238E+10 | 0.470973E+10 | 0.00 | 0.00 |
September | 0.603478E+10 | 0.418865E+10 | 0.652870E+10 | 0.293325E+10 | 0.359545E+10 | 0.00 | 0.00 |
October | 0.273225E+10 | 0.684114E+10 | 0.426170E+10 | 0.171083E+10 | 0.255087E+10 | 0.00 | 0.00 |
November | 0.811373E+09 | 0.102055E+11 | 0.250485E+10 | 0.844541E+09 | 0.166031E+10 | 0.00 | 0.00 |
December | 0.376303E+09 | 0.161364E+11 | 0.230737E+10 | 0.807595E+09 | 0.149977E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.650888E+11 | 0.952958E+11 | 0.763992E+11 | 0.347451E+11 | 0.416542E+11 | 0.00 | 0.00 |
Minimum of Months | 0.376303E+09 | 0.258241E+10 | 0.230737E+10 | 0.807595E+09 | 0.149977E+10 | 0.00 | 0.00 |
Maximum of Months | 0.118814E+11 | 0.161364E+11 | 0.104894E+11 | 0.487651E+10 | 0.561294E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 2911096.12 | 0.250719E+11 | 0.204815E+10 | 0.00 | 0.204815E+10 | 0.00 | 0.00 |
February | 71357880.51 | 0.183774E+11 | 0.284165E+10 | 0.00 | 0.284165E+10 | 0.00 | 0.00 |
March | 0.201856E+09 | 0.160968E+11 | 0.387075E+10 | 0.00 | 0.387075E+10 | 0.00 | 0.00 |
April | 0.142972E+10 | 0.911368E+10 | 0.491062E+10 | 38326803.89 | 0.487229E+10 | 0.00 | 0.00 |
May | 0.521433E+10 | 0.465851E+10 | 0.713682E+10 | 0.384307E+09 | 0.675252E+10 | 0.00 | 0.00 |
June | 0.742997E+10 | 0.308041E+10 | 0.770788E+10 | 0.847302E+09 | 0.686058E+10 | 0.00 | 0.00 |
July | 0.786654E+10 | 0.291804E+10 | 0.760764E+10 | 0.652880E+09 | 0.695476E+10 | 0.00 | 0.00 |
August | 0.531744E+10 | 0.338260E+10 | 0.577825E+10 | 99230155.17 | 0.567901E+10 | 0.00 | 0.00 |
September | 0.263658E+10 | 0.550733E+10 | 0.435757E+10 | 1068179.80 | 0.435650E+10 | 0.00 | 0.00 |
October | 0.605201E+09 | 0.932874E+10 | 0.312653E+10 | 0.00 | 0.312653E+10 | 0.00 | 0.00 |
November | 74248998.35 | 0.143294E+11 | 0.200338E+10 | 0.00 | 0.200338E+10 | 0.00 | 0.00 |
December | 0.00 | 0.239483E+11 | 0.173536E+10 | 0.00 | 0.173536E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.308501E+11 | 0.135813E+12 | 0.531246E+11 | 0.202311E+10 | 0.511015E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.291804E+10 | 0.173536E+10 | 0.00 | 0.173536E+10 | 0.00 | 0.00 |
Maximum of Months | 0.786654E+10 | 0.250719E+11 | 0.770788E+10 | 0.847302E+09 | 0.695476E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.649162E+09 | 0.149927E+11 | 0.299359E+10 | 0.124962E+10 | 0.174397E+10 | 0.00 | 0.00 |
February | 0.175988E+10 | 0.108325E+11 | 0.424892E+10 | 0.181240E+10 | 0.243652E+10 | 0.00 | 0.00 |
March | 0.377865E+10 | 0.966319E+10 | 0.640971E+10 | 0.321521E+10 | 0.319451E+10 | 0.00 | 0.00 |
April | 0.686606E+10 | 0.559969E+10 | 0.859908E+10 | 0.463817E+10 | 0.396091E+10 | 0.00 | 0.00 |
May | 0.922208E+10 | 0.309741E+10 | 0.961696E+10 | 0.422772E+10 | 0.538923E+10 | 0.00 | 0.00 |
June | 0.115117E+11 | 0.209246E+10 | 0.105359E+11 | 0.503989E+10 | 0.549598E+10 | 0.00 | 0.00 |
July | 0.121430E+11 | 0.194445E+10 | 0.106653E+11 | 0.500776E+10 | 0.565755E+10 | 0.00 | 0.00 |
August | 0.884464E+10 | 0.224294E+10 | 0.822298E+10 | 0.359402E+10 | 0.462896E+10 | 0.00 | 0.00 |
September | 0.576244E+10 | 0.350813E+10 | 0.637280E+10 | 0.285243E+10 | 0.352037E+10 | 0.00 | 0.00 |
October | 0.233644E+10 | 0.587310E+10 | 0.398747E+10 | 0.151204E+10 | 0.247543E+10 | 0.00 | 0.00 |
November | 0.813244E+09 | 0.879638E+10 | 0.245657E+10 | 0.821288E+09 | 0.163528E+10 | 0.00 | 0.00 |
December | 0.401580E+09 | 0.145539E+11 | 0.231632E+10 | 0.856148E+09 | 0.146017E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.640888E+11 | 0.831968E+11 | 0.764256E+11 | 0.348267E+11 | 0.415989E+11 | 0.00 | 0.00 |
Minimum of Months | 0.401580E+09 | 0.194445E+10 | 0.231632E+10 | 0.821288E+09 | 0.146017E+10 | 0.00 | 0.00 |
Maximum of Months | 0.121430E+11 | 0.149927E+11 | 0.106653E+11 | 0.503989E+10 | 0.565755E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.926678E+10 | 0.198338E+11 | 0.141037E+11 | 0.981161E+10 | 0.429206E+10 | 0.00 | 0.00 |
February | 0.125421E+11 | 0.150780E+11 | 0.161304E+11 | 0.108950E+11 | 0.523536E+10 | 0.00 | 0.00 |
March | 0.127053E+11 | 0.141565E+11 | 0.157356E+11 | 0.995846E+10 | 0.577716E+10 | 0.00 | 0.00 |
April | 0.125602E+11 | 0.909946E+10 | 0.137961E+11 | 0.748814E+10 | 0.630796E+10 | 0.00 | 0.00 |
May | 0.122353E+11 | 0.522622E+10 | 0.119855E+11 | 0.409757E+10 | 0.788796E+10 | 0.00 | 0.00 |
June | 0.116917E+11 | 0.342513E+10 | 0.104075E+11 | 0.277404E+10 | 0.763341E+10 | 0.00 | 0.00 |
July | 0.139881E+11 | 0.322231E+10 | 0.117580E+11 | 0.372488E+10 | 0.803313E+10 | 0.00 | 0.00 |
August | 0.143562E+11 | 0.373951E+10 | 0.125569E+11 | 0.525245E+10 | 0.730444E+10 | 0.00 | 0.00 |
September | 0.133973E+11 | 0.575432E+10 | 0.130164E+11 | 0.693222E+10 | 0.608420E+10 | 0.00 | 0.00 |
October | 0.100020E+11 | 0.892707E+10 | 0.114856E+11 | 0.675526E+10 | 0.473035E+10 | 0.00 | 0.00 |
November | 0.726411E+10 | 0.123611E+11 | 0.990111E+10 | 0.621395E+10 | 0.368716E+10 | 0.00 | 0.00 |
December | 0.648167E+10 | 0.194094E+11 | 0.108897E+11 | 0.714052E+10 | 0.374920E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.136491E+12 | 0.120233E+12 | 0.151767E+12 | 0.810441E+11 | 0.707224E+11 | 0.00 | 0.00 |
Minimum of Months | 0.648167E+10 | 0.322231E+10 | 0.990111E+10 | 0.277404E+10 | 0.368716E+10 | 0.00 | 0.00 |
Maximum of Months | 0.143562E+11 | 0.198338E+11 | 0.161304E+11 | 0.108950E+11 | 0.803313E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.785001E+09 | 0.156274E+11 | 0.302563E+10 | 0.126696E+10 | 0.175867E+10 | 0.00 | 0.00 |
February | 0.218057E+10 | 0.114737E+11 | 0.445258E+10 | 0.203364E+10 | 0.241894E+10 | 0.00 | 0.00 |
March | 0.414048E+10 | 0.101738E+11 | 0.648703E+10 | 0.331937E+10 | 0.316766E+10 | 0.00 | 0.00 |
April | 0.647984E+10 | 0.614055E+10 | 0.801951E+10 | 0.406180E+10 | 0.395770E+10 | 0.00 | 0.00 |
May | 0.103814E+11 | 0.351347E+10 | 0.101818E+11 | 0.485678E+10 | 0.532505E+10 | 0.00 | 0.00 |
June | 0.105205E+11 | 0.234714E+10 | 0.950830E+10 | 0.411132E+10 | 0.539699E+10 | 0.00 | 0.00 |
July | 0.120713E+11 | 0.229781E+10 | 0.104894E+11 | 0.487649E+10 | 0.561292E+10 | 0.00 | 0.00 |
August | 0.956394E+10 | 0.256143E+10 | 0.863208E+10 | 0.392237E+10 | 0.470971E+10 | 0.00 | 0.00 |
September | 0.616530E+10 | 0.382803E+10 | 0.652868E+10 | 0.293324E+10 | 0.359544E+10 | 0.00 | 0.00 |
October | 0.283401E+10 | 0.620100E+10 | 0.426168E+10 | 0.171083E+10 | 0.255086E+10 | 0.00 | 0.00 |
November | 0.875476E+09 | 0.917875E+10 | 0.250484E+10 | 0.844538E+09 | 0.166030E+10 | 0.00 | 0.00 |
December | 0.395905E+09 | 0.152048E+11 | 0.230736E+10 | 0.807592E+09 | 0.149977E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.663937E+11 | 0.885477E+11 | 0.763989E+11 | 0.347449E+11 | 0.416540E+11 | 0.00 | 0.00 |
Minimum of Months | 0.395905E+09 | 0.229781E+10 | 0.230736E+10 | 0.807592E+09 | 0.149977E+10 | 0.00 | 0.00 |
Maximum of Months | 0.120713E+11 | 0.156274E+11 | 0.104894E+11 | 0.487649E+10 | 0.561292E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5147764.17 | 0.246674E+11 | 0.204815E+10 | 0.00 | 0.204815E+10 | 0.00 | 0.00 |
February | 82759066.79 | 0.179287E+11 | 0.284165E+10 | 0.00 | 0.284165E+10 | 0.00 | 0.00 |
March | 0.240959E+09 | 0.154480E+11 | 0.387075E+10 | 0.00 | 0.387075E+10 | 0.00 | 0.00 |
April | 0.156223E+10 | 0.840406E+10 | 0.491062E+10 | 38326803.89 | 0.487229E+10 | 0.00 | 0.00 |
May | 0.545001E+10 | 0.423164E+10 | 0.713682E+10 | 0.384307E+09 | 0.675252E+10 | 0.00 | 0.00 |
June | 0.765112E+10 | 0.280786E+10 | 0.770788E+10 | 0.847302E+09 | 0.686058E+10 | 0.00 | 0.00 |
July | 0.805069E+10 | 0.268835E+10 | 0.760764E+10 | 0.652880E+09 | 0.695476E+10 | 0.00 | 0.00 |
August | 0.551191E+10 | 0.304973E+10 | 0.577825E+10 | 99230155.17 | 0.567901E+10 | 0.00 | 0.00 |
September | 0.284578E+10 | 0.494243E+10 | 0.435757E+10 | 1068179.80 | 0.435650E+10 | 0.00 | 0.00 |
October | 0.728804E+09 | 0.840424E+10 | 0.312653E+10 | 0.00 | 0.312653E+10 | 0.00 | 0.00 |
November | 84721079.64 | 0.135812E+11 | 0.200338E+10 | 0.00 | 0.200338E+10 | 0.00 | 0.00 |
December | 0.00 | 0.234797E+11 | 0.173536E+10 | 0.00 | 0.173536E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.322141E+11 | 0.129633E+12 | 0.531246E+11 | 0.202311E+10 | 0.511015E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.268835E+10 | 0.173536E+10 | 0.00 | 0.173536E+10 | 0.00 | 0.00 |
Maximum of Months | 0.805069E+10 | 0.246674E+11 | 0.770788E+10 | 0.847302E+09 | 0.695476E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.662251E+09 | 0.148041E+11 | 0.299359E+10 | 0.124962E+10 | 0.174397E+10 | 0.00 | 0.00 |
February | 0.180819E+10 | 0.105577E+11 | 0.424892E+10 | 0.181240E+10 | 0.243652E+10 | 0.00 | 0.00 |
March | 0.388849E+10 | 0.923018E+10 | 0.640971E+10 | 0.321521E+10 | 0.319451E+10 | 0.00 | 0.00 |
April | 0.701788E+10 | 0.516876E+10 | 0.859908E+10 | 0.463817E+10 | 0.396091E+10 | 0.00 | 0.00 |
May | 0.934713E+10 | 0.288083E+10 | 0.961696E+10 | 0.422772E+10 | 0.538923E+10 | 0.00 | 0.00 |
June | 0.115665E+11 | 0.195754E+10 | 0.105359E+11 | 0.503989E+10 | 0.549598E+10 | 0.00 | 0.00 |
July | 0.121660E+11 | 0.184220E+10 | 0.106653E+11 | 0.500776E+10 | 0.565755E+10 | 0.00 | 0.00 |
August | 0.891376E+10 | 0.208887E+10 | 0.822298E+10 | 0.359402E+10 | 0.462896E+10 | 0.00 | 0.00 |
September | 0.591987E+10 | 0.319259E+10 | 0.637280E+10 | 0.285243E+10 | 0.352037E+10 | 0.00 | 0.00 |
October | 0.249520E+10 | 0.528028E+10 | 0.398747E+10 | 0.151204E+10 | 0.247543E+10 | 0.00 | 0.00 |
November | 0.861238E+09 | 0.830793E+10 | 0.245657E+10 | 0.821288E+09 | 0.163528E+10 | 0.00 | 0.00 |
December | 0.413544E+09 | 0.143256E+11 | 0.231632E+10 | 0.856148E+09 | 0.146017E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.650600E+11 | 0.796366E+11 | 0.764256E+11 | 0.348267E+11 | 0.415989E+11 | 0.00 | 0.00 |
Minimum of Months | 0.413544E+09 | 0.184220E+10 | 0.231632E+10 | 0.821288E+09 | 0.146017E+10 | 0.00 | 0.00 |
Maximum of Months | 0.121660E+11 | 0.148041E+11 | 0.106653E+11 | 0.503989E+10 | 0.565755E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.935545E+10 | 0.193925E+11 | 0.141037E+11 | 0.981161E+10 | 0.429206E+10 | 0.00 | 0.00 |
February | 0.126574E+11 | 0.145483E+11 | 0.161304E+11 | 0.108950E+11 | 0.523536E+10 | 0.00 | 0.00 |
March | 0.128545E+11 | 0.134330E+11 | 0.157356E+11 | 0.995846E+10 | 0.577716E+10 | 0.00 | 0.00 |
April | 0.127098E+11 | 0.837204E+10 | 0.137961E+11 | 0.748814E+10 | 0.630796E+10 | 0.00 | 0.00 |
May | 0.123741E+11 | 0.478186E+10 | 0.119855E+11 | 0.409757E+10 | 0.788796E+10 | 0.00 | 0.00 |
June | 0.117841E+11 | 0.313961E+10 | 0.104075E+11 | 0.277404E+10 | 0.763341E+10 | 0.00 | 0.00 |
July | 0.140505E+11 | 0.298528E+10 | 0.117580E+11 | 0.372488E+10 | 0.803313E+10 | 0.00 | 0.00 |
August | 0.144444E+11 | 0.341862E+10 | 0.125569E+11 | 0.525245E+10 | 0.730444E+10 | 0.00 | 0.00 |
September | 0.135565E+11 | 0.521992E+10 | 0.130164E+11 | 0.693222E+10 | 0.608420E+10 | 0.00 | 0.00 |
October | 0.102171E+11 | 0.804085E+10 | 0.114856E+11 | 0.675526E+10 | 0.473035E+10 | 0.00 | 0.00 |
November | 0.741928E+10 | 0.115982E+11 | 0.990111E+10 | 0.621395E+10 | 0.368716E+10 | 0.00 | 0.00 |
December | 0.658279E+10 | 0.189101E+11 | 0.108897E+11 | 0.714052E+10 | 0.374920E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.138006E+12 | 0.113840E+12 | 0.151767E+12 | 0.810441E+11 | 0.707224E+11 | 0.00 | 0.00 |
Minimum of Months | 0.658279E+10 | 0.298528E+10 | 0.990111E+10 | 0.277404E+10 | 0.368716E+10 | 0.00 | 0.00 |
Maximum of Months | 0.144444E+11 | 0.193925E+11 | 0.161304E+11 | 0.108950E+11 | 0.803313E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.792400E+09 | 0.153734E+11 | 0.302563E+10 | 0.126696E+10 | 0.175867E+10 | 0.00 | 0.00 |
February | 0.218676E+10 | 0.111923E+11 | 0.445258E+10 | 0.203364E+10 | 0.241894E+10 | 0.00 | 0.00 |
March | 0.416474E+10 | 0.977353E+10 | 0.648703E+10 | 0.331937E+10 | 0.316766E+10 | 0.00 | 0.00 |
April | 0.652090E+10 | 0.573103E+10 | 0.801951E+10 | 0.406180E+10 | 0.395770E+10 | 0.00 | 0.00 |
May | 0.104060E+11 | 0.328658E+10 | 0.101818E+11 | 0.485678E+10 | 0.532505E+10 | 0.00 | 0.00 |
June | 0.105216E+11 | 0.221016E+10 | 0.950830E+10 | 0.411132E+10 | 0.539699E+10 | 0.00 | 0.00 |
July | 0.120584E+11 | 0.218343E+10 | 0.104894E+11 | 0.487649E+10 | 0.561292E+10 | 0.00 | 0.00 |
August | 0.957515E+10 | 0.241012E+10 | 0.863208E+10 | 0.392237E+10 | 0.470971E+10 | 0.00 | 0.00 |
September | 0.620740E+10 | 0.355015E+10 | 0.652868E+10 | 0.293324E+10 | 0.359544E+10 | 0.00 | 0.00 |
October | 0.289210E+10 | 0.569714E+10 | 0.426168E+10 | 0.171083E+10 | 0.255086E+10 | 0.00 | 0.00 |
November | 0.901645E+09 | 0.874877E+10 | 0.250484E+10 | 0.844538E+09 | 0.166030E+10 | 0.00 | 0.00 |
December | 0.399833E+09 | 0.149317E+11 | 0.230736E+10 | 0.807592E+09 | 0.149977E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.666269E+11 | 0.850883E+11 | 0.763989E+11 | 0.347449E+11 | 0.416540E+11 | 0.00 | 0.00 |
Minimum of Months | 0.399833E+09 | 0.218343E+10 | 0.230736E+10 | 0.807592E+09 | 0.149977E+10 | 0.00 | 0.00 |
Maximum of Months | 0.120584E+11 | 0.153734E+11 | 0.104894E+11 | 0.487649E+10 | 0.561292E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.467235E+11 | -0.462454E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -478079936.6 | 60.05 | 0.00 | 0.00 |
February | 0.433902E+11 | -0.429664E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -423755389.3 | 60.05 | 0.00 | 0.00 |
March | 0.508126E+11 | -0.503523E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -460335531.3 | 60.05 | 0.00 | 0.00 |
April | 0.447371E+11 | -0.443016E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -435590137.1 | 60.05 | 0.00 | 0.00 |
May | 0.454304E+11 | -0.449826E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -447751808.3 | 60.05 | 0.00 | 0.00 |
June | 0.424110E+11 | -0.419792E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -431874345.5 | 60.05 | 0.00 | 0.00 |
July | 0.382943E+11 | -0.378517E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442606403.7 | 60.05 | 0.00 | 0.00 |
August | 0.407234E+11 | -0.402787E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444650471.9 | 60.05 | 0.00 | 0.00 |
September | 0.371525E+11 | -0.367204E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -432147233.6 | 60.05 | 0.00 | 0.00 |
October | 0.397766E+11 | -0.393298E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -446894983.9 | 60.05 | 0.00 | 0.00 |
November | 0.412547E+11 | -0.408194E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -435277183.0 | 60.05 | 0.00 | 0.00 |
December | 0.435331E+11 | -0.430645E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -468627884.5 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.514240E+12 | -0.508892E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.534759E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.371525E+11 | -0.503523E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -478079936.6 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.508126E+11 | -0.367204E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -423755389.3 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 243.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 409.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 352.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 255.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.527659E+11 | 83187.48 | 06-JAN-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.286564E+11 | 77060.03 | 14-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131319E+11 | 54855.02 | 15-MAR-06:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.742184E+09 | 30332.99 | 05-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15331415.47 | 7318.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.276885E+09 | 22834.84 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.546742E+10 | 44230.47 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.367165E+11 | 69021.98 | 20-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137772E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.527659E+11 | 83187.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.241226E+09 | 36639.37 | 02-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2800876.28 | 3099.64 | 26-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.244027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.241226E+09 | 36639.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131223E+11 | 24768.53 | 02-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.741720E+10 | 24656.52 | 06-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.433357E+10 | 24655.38 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.651497E+09 | 26348.42 | 07-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10543763.32 | 4860.15 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19548813.38 | 1330.14 | 23-SEP-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.504308E+09 | 24422.05 | 30-OCT-04:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252664E+10 | 25737.35 | 17-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.962750E+10 | 24662.57 | 01-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.382131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131223E+11 | 26348.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.101692E+11 | 23419.91 | 23-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.590405E+10 | 23427.88 | 06-FEB-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.410978E+10 | 23421.82 | 08-MAR-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108895E+10 | 23770.54 | 07-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 83836724.57 | 9009.69 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9266586.23 | 2678.39 | 10-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1215024.45 | 278.48 | 08-JUL-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13814640.72 | 5790.93 | 19-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.295601E+09 | 6939.09 | 06-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131252E+10 | 23376.58 | 30-OCT-04:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.329956E+10 | 23427.77 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.863222E+10 | 23426.52 | 01-DEC-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1215024.45 | 278.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.101692E+11 | 23770.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.112618E+11 | 32812.47 | 25-JAN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.644193E+10 | 32820.73 | 18-FEB-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.487510E+10 | 32804.04 | 10-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151860E+10 | 33280.79 | 07-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.249865E+09 | 30705.86 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6232190.38 | 3187.51 | 03-JUN-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31883.04 | 531.38 | 10-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15840847.23 | 7830.97 | 19-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.315102E+09 | 13671.18 | 13-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150112E+10 | 32844.41 | 30-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.378000E+10 | 32823.92 | 24-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.968026E+10 | 32817.54 | 18-DEC-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.396459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 31883.04 | 531.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.112618E+11 | 33280.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.824069E+10 | 24203.97 | 23-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.468747E+10 | 24209.33 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.257389E+10 | 24204.30 | 06-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.294530E+09 | 22436.17 | 04-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 50845703.40 | 3777.87 | 10-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 101117.22 | 1225.17 | 10-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118967E+09 | 3906.37 | 28-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.727046E+09 | 24153.81 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191998E+10 | 24203.82 | 25-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.488572E+10 | 24203.28 | 13-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.824069E+10 | 24209.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.612956E+12 | 894716.54 | 06-JAN-08:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.368773E+12 | 840589.32 | 14-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218089E+12 | 1038447.05 | 23-MAR-13:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.244184E+11 | 764648.51 | 28-APR-13:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.163944E+10 | 557817.30 | 08-MAY-09:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2418008.80 | 40300.15 | 09-JUN-13:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7228207.27 | 43236.54 | 18-AUG-09:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.559928E+09 | 392372.38 | 27-SEP-13:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.943906E+10 | 491653.70 | 25-OCT-09:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120028E+12 | 722174.44 | 16-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.504185E+12 | 772896.83 | 20-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186010E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.612956E+12 | 1038447.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.378663E+11 | 719505.20 | 03-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111750E+11 | 719197.32 | 28-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.407958E+10 | 718862.69 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.942859E+10 | 719551.44 | 28-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207808E+11 | 719373.01 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.833303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.378663E+11 | 719551.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.235110E+12 | 330640.49 | 30-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160589E+12 | 328595.71 | 17-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115430E+12 | 328656.48 | 06-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.414532E+11 | 327325.61 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.489772E+10 | 322162.05 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252416E+09 | 69798.52 | 10-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 66150945.90 | 13389.08 | 08-JUL-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.746100E+09 | 93695.22 | 19-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.928154E+10 | 279212.07 | 13-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.393194E+11 | 328123.39 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100550E+12 | 329770.56 | 27-NOV-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.215673E+12 | 328651.33 | 11-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.923368E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 66150945.90 | 13389.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.235110E+12 | 330640.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144304E+12 | 273244.32 | 23-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.935260E+11 | 273048.90 | 27-FEB-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.658548E+11 | 272670.37 | 20-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.235170E+11 | 271655.87 | 04-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.356155E+10 | 227036.91 | 09-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.737009E+09 | 68075.33 | 10-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.298947E+09 | 46082.91 | 08-JUL-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160015E+10 | 96877.40 | 19-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.883384E+10 | 220266.28 | 13-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.300885E+11 | 272636.59 | 30-OCT-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.667450E+11 | 273241.64 | 13-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136181E+12 | 273060.85 | 18-DEC-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.575248E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.298947E+09 | 46082.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.144304E+12 | 273244.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.162076E+12 | 355558.97 | 23-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.983019E+11 | 354325.30 | 27-FEB-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.750400E+11 | 355787.38 | 06-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.305052E+11 | 354017.13 | 04-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.525922E+10 | 333501.37 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.894517E+09 | 69172.19 | 10-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181767E+09 | 25190.86 | 10-JUL-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.965687E+09 | 72767.12 | 19-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.744031E+10 | 294797.84 | 13-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.290712E+11 | 355026.80 | 30-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.735083E+11 | 356894.34 | 27-NOV-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160423E+12 | 355644.90 | 18-DEC-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.643668E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.181767E+09 | 25190.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.162076E+12 | 356894.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.149200E+12 | 284000.76 | 11-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.974117E+11 | 283985.91 | 27-FEB-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.722822E+11 | 283425.10 | 02-MAR-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.292126E+11 | 282584.90 | 04-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.558987E+10 | 236154.79 | 09-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164758E+10 | 53064.66 | 14-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.399312E+09 | 23389.73 | 18-JUL-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.186296E+10 | 60099.62 | 19-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105408E+11 | 228304.14 | 13-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.335243E+11 | 283535.11 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.712384E+11 | 283422.43 | 28-NOV-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134924E+12 | 284005.08 | 18-DEC-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.607833E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.399312E+09 | 23389.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.149200E+12 | 284005.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.697185E+11 | 87143.04 | 09-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.411099E+11 | 84109.48 | 14-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.223785E+11 | 67908.28 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.281234E+10 | 43942.28 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75839971.75 | 19496.42 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5491844.19 | 3318.64 | 06-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158879E+10 | 36247.61 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143096E+11 | 58426.80 | 25-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.592864E+11 | 82578.15 | 20-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.697185E+11 | 87143.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.357230E+11 | 138213.77 | 17-JAN-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.233741E+11 | 138430.06 | 22-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167272E+11 | 138229.06 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.633677E+10 | 137819.81 | 03-APR-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.830871E+09 | 135507.61 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2394236.11 | 3537.38 | 05-JUN-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29254312.45 | 15464.98 | 10-JUL-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 42750544.46 | 55572.07 | 19-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.682149E+09 | 112256.07 | 23-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.716279E+10 | 138257.62 | 30-OCT-03:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165032E+11 | 138236.75 | 06-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.317084E+11 | 138000.83 | 07-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139123E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2394236.11 | 3537.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.357230E+11 | 138430.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.344694E+11 | 43804.38 | 28-JAN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.257539E+11 | 43926.28 | 22-FEB-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206914E+11 | 44024.20 | 20-MAR-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.985767E+10 | 43887.83 | 04-APR-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.244392E+10 | 42879.80 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.629927E+09 | 33925.30 | 10-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.322981E+09 | 17862.76 | 10-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.994608E+09 | 35069.39 | 19-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.394330E+10 | 37534.01 | 07-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.103285E+11 | 43594.30 | 06-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190449E+11 | 43811.92 | 08-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.330170E+11 | 43831.35 | 25-DEC-08:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161498E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.322981E+09 | 17862.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.344694E+11 | 44024.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.213903E+11 | 29926.49 | 31-JAN-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150643E+11 | 30008.23 | 22-FEB-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112738E+11 | 30077.77 | 04-MAR-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.474740E+10 | 30066.65 | 04-APR-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.105017E+10 | 28897.77 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.256021E+09 | 22854.04 | 10-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150838E+09 | 12522.87 | 10-JUL-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.486615E+09 | 23626.53 | 19-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.207864E+10 | 25289.55 | 07-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.624246E+10 | 29889.20 | 06-OCT-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118506E+11 | 29985.76 | 07-NOV-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209173E+11 | 30021.92 | 29-DEC-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.955085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.150838E+09 | 12522.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.213903E+11 | 30077.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.256926E+11 | 44561.49 | 31-JAN-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175093E+11 | 44689.94 | 22-FEB-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144248E+11 | 44625.72 | 04-MAR-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.731693E+10 | 44650.82 | 04-APR-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.215540E+10 | 43625.28 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.885958E+09 | 35352.95 | 03-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.475740E+09 | 34605.81 | 10-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.867951E+09 | 35679.08 | 19-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.298359E+10 | 38186.54 | 07-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.789903E+10 | 44352.20 | 06-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147475E+11 | 44558.30 | 29-NOV-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261654E+11 | 44565.98 | 01-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121124E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.475740E+09 | 34605.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.261654E+11 | 44689.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.206934E+11 | 33765.76 | 12-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142070E+11 | 33764.03 | 13-FEB-03:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110253E+11 | 33775.98 | 02-MAR-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.516330E+10 | 33630.03 | 05-APR-03:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147446E+10 | 31443.95 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.571080E+09 | 18856.96 | 10-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.263241E+09 | 6622.90 | 18-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.617170E+09 | 25679.99 | 19-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.239168E+10 | 26268.98 | 13-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.591850E+10 | 33718.15 | 30-OCT-04:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109898E+11 | 33776.55 | 28-NOV-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191812E+11 | 33772.23 | 16-DEC-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.924962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.263241E+09 | 6622.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.206934E+11 | 33776.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110469E+11 | 186541.79 | 06-JAN-07:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150776E+10 | 184165.54 | 14-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9182823.29 | 7765.50 | 16-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142412E+10 | 27955.92 | 20-DEC-07:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110469E+11 | 186541.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 288.56 | 288.56 | 0.48 | 02-JAN-04:30 | 0.48 | 0.00 |
February | 0.00 | 0.00 | 3610.96 | 3610.96 | 0.94 | 06-FEB-04:01 | 0.94 | 0.00 |
March | 0.00 | 0.00 | 278.72 | 278.72 | 0.85 | 26-MAR-11:09 | 0.85 | 0.00 |
April | 0.00 | 0.00 | 0.572825E+10 | 0.572825E+10 | 130055.91 | 23-APR-15:11 | 130055.91 | 0.01 |
May | 0.00 | 0.00 | 0.459015E+11 | 0.450256E+11 | 155114.15 | 25-MAY-15:00 | 141105.96 | 0.18 |
June | 0.00 | 0.00 | 0.104210E+12 | 0.846726E+11 | 232922.76 | 30-JUN-05:02 | 162044.20 | 0.41 |
July | 0.00 | 0.00 | 0.140679E+12 | 0.110014E+12 | 345221.92 | 05-JUL-10:32 | 122594.09 | 0.59 |
August | 0.00 | 0.00 | 0.112835E+12 | 0.860685E+11 | 244247.05 | 31-AUG-12:40 | 112154.68 | 0.58 |
September | 0.00 | 0.00 | 0.242210E+11 | 0.216531E+11 | 162304.66 | 01-SEP-11:00 | 115217.53 | 0.13 |
October | 0.00 | 0.00 | 0.398972E+10 | 0.398972E+10 | 90498.14 | 19-OCT-15:00 | 90498.14 | 0.01 |
November | 0.00 | 0.00 | 0.559479E+09 | 0.559479E+09 | 31145.94 | 01-NOV-14:53 | 31145.94 | 0.01 |
December | 0.00 | 0.00 | 1062893.78 | 1062893.78 | 3541.92 | 05-DEC-17:05 | 3541.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.438125E+12 | 0.357712E+12 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 278.72 | 278.72 | 0.48 | 0.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.140679E+12 | 0.110014E+12 | 345221.92 | 162044.20 | 0.59 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 79687.54 | 79687.54 | 6.61 | 01-JAN-10:01 | 6.61 | 0.00 |
February | 0.00 | 0.00 | 61724729.79 | 61724729.79 | 42371.69 | 28-FEB-12:01 | 42371.69 | 0.00 |
March | 0.00 | 0.00 | 0.470785E+10 | 0.470785E+10 | 587690.75 | 31-MAR-14:01 | 587690.75 | 0.00 |
April | 0.00 | 0.00 | 0.550520E+11 | 0.550520E+11 | 1247381.17 | 23-APR-15:42 | 1247381.17 | 0.01 |
May | 0.00 | 0.00 | 0.438669E+12 | 0.430534E+12 | 1513706.04 | 25-MAY-15:20 | 1374168.27 | 0.18 |
June | 0.00 | 0.00 | 0.953687E+12 | 0.772718E+12 | 2261485.18 | 30-JUN-04:01 | 1415995.73 | 0.41 |
July | 0.00 | 0.00 | 0.118708E+13 | 0.937635E+12 | 2942040.52 | 05-JUL-10:40 | 1047839.17 | 0.55 |
August | 0.00 | 0.00 | 0.937522E+12 | 0.721937E+12 | 1955308.36 | 31-AUG-12:40 | 901345.66 | 0.55 |
September | 0.00 | 0.00 | 0.237851E+12 | 0.215535E+12 | 1533265.15 | 01-SEP-12:05 | 1213433.73 | 0.14 |
October | 0.00 | 0.00 | 0.481928E+11 | 0.481928E+11 | 865478.87 | 19-OCT-15:00 | 865478.87 | 0.01 |
November | 0.00 | 0.00 | 0.596113E+10 | 0.596113E+10 | 493339.80 | 01-NOV-14:01 | 493339.80 | 0.01 |
December | 0.00 | 0.00 | 178120.37 | 178120.37 | 5.72 | 12-DEC-04:11 | 5.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.386878E+13 | 0.319233E+13 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 79687.54 | 79687.54 | 5.72 | 5.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.118708E+13 | 0.937635E+12 | 2942040.52 | 1415995.73 | 0.55 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4814712.23 | 4814712.23 | 2831.93 | 24-JAN-06:04 | 2831.93 | 0.00 |
February | 0.00 | 0.00 | 7252520.35 | 7252520.35 | 6353.30 | 27-FEB-06:12 | 6353.30 | 0.00 |
March | 0.00 | 0.00 | 7324451.20 | 7324451.20 | 5454.29 | 15-MAR-05:12 | 5454.29 | 0.00 |
April | 0.00 | 0.00 | 0.485663E+10 | 0.485663E+10 | 164348.04 | 23-APR-15:31 | 164348.04 | 0.01 |
May | 0.00 | 0.00 | 0.467508E+11 | 0.461067E+11 | 181602.21 | 25-MAY-15:00 | 168285.01 | 0.18 |
June | 0.00 | 0.00 | 0.102742E+12 | 0.849439E+11 | 335691.33 | 29-JUN-05:02 | 157328.31 | 0.39 |
July | 0.00 | 0.00 | 0.128762E+12 | 0.104887E+12 | 278746.12 | 05-JUL-05:01 | 109315.00 | 0.53 |
August | 0.00 | 0.00 | 0.973381E+11 | 0.775754E+11 | 216477.12 | 08-AUG-15:00 | 179577.67 | 0.53 |
September | 0.00 | 0.00 | 0.214093E+11 | 0.197024E+11 | 169740.45 | 01-SEP-15:30 | 163382.33 | 0.12 |
October | 0.00 | 0.00 | 0.349811E+10 | 0.349811E+10 | 78710.99 | 19-OCT-15:00 | 78710.99 | 0.01 |
November | 0.00 | 0.00 | 0.463047E+09 | 0.463047E+09 | 25093.39 | 01-NOV-14:53 | 25093.39 | 0.01 |
December | 0.00 | 0.00 | 12223538.73 | 12223538.73 | 4197.05 | 11-DEC-06:12 | 4197.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.405851E+12 | 0.342065E+12 | 0.15 | |||
Minimum of Months | 0.00 | 0.00 | 4814712.23 | 4814712.23 | 2831.93 | 2831.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.128762E+12 | 0.104887E+12 | 335691.33 | 179577.67 | 0.53 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 19249109.70 | 19249109.70 | 61179.83 | 31-JAN-06:01 | 61179.83 | 0.00 |
February | 0.00 | 0.00 | 0.156135E+09 | 0.156135E+09 | 56924.67 | 24-FEB-06:02 | 56924.67 | 0.00 |
March | 0.00 | 0.00 | 0.120275E+10 | 0.120275E+10 | 114495.45 | 27-MAR-04:56 | 114495.45 | 0.00 |
April | 0.00 | 0.00 | 0.742352E+10 | 0.742352E+10 | 115256.54 | 03-APR-04:49 | 115256.54 | 0.00 |
May | 0.00 | 0.00 | 0.320570E+11 | 0.302008E+11 | 105668.57 | 26-MAY-04:11 | 71892.54 | 0.18 |
June | 0.00 | 0.00 | 0.605015E+11 | 0.444672E+11 | 171815.73 | 29-JUN-04:52 | 81473.07 | 0.39 |
July | 0.00 | 0.00 | 0.765549E+11 | 0.530869E+11 | 207444.01 | 05-JUL-10:25 | 74594.45 | 0.50 |
August | 0.00 | 0.00 | 0.704768E+11 | 0.465001E+11 | 147905.02 | 27-AUG-14:31 | 89221.03 | 0.53 |
September | 0.00 | 0.00 | 0.265505E+11 | 0.225827E+11 | 134277.39 | 04-SEP-11:58 | 134277.39 | 0.18 |
October | 0.00 | 0.00 | 0.117722E+11 | 0.116014E+11 | 139903.78 | 25-OCT-03:25 | 139903.78 | 0.02 |
November | 0.00 | 0.00 | 0.440852E+10 | 0.425696E+10 | 114346.49 | 30-NOV-05:49 | 114346.49 | 0.01 |
December | 0.00 | 0.00 | 0.121492E+09 | 0.121492E+09 | 110640.78 | 01-DEC-05:50 | 110640.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.291245E+12 | 0.221619E+12 | 0.15 | |||
Minimum of Months | 0.00 | 0.00 | 19249109.70 | 19249109.70 | 56924.67 | 56924.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.765549E+11 | 0.530869E+11 | 207444.01 | 139903.78 | 0.53 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3383165.69 | 3383165.69 | 63.72 | 28-JAN-13:02 | 63.72 | 0.02 |
February | 0.00 | 0.00 | 0.158739E+12 | 0.158739E+12 | 277305.49 | 14-FEB-10:01 | 277305.49 | 0.00 |
March | 0.00 | 0.00 | 0.222015E+12 | 0.222015E+12 | 267717.00 | 31-MAR-23:17 | 267717.00 | 0.00 |
April | 0.00 | 0.00 | 0.223204E+12 | 0.223204E+12 | 434430.17 | 23-APR-15:46 | 434430.17 | 0.01 |
May | 0.00 | 0.00 | 0.224752E+11 | 0.224752E+11 | 219021.98 | 31-MAY-23:47 | 219021.98 | 0.17 |
June | 0.00 | 0.00 | 0.292250E+12 | 0.236831E+12 | 564778.66 | 19-JUN-10:52 | 228932.14 | 0.53 |
July | 0.00 | 0.00 | 0.381050E+12 | 0.330387E+12 | 569313.14 | 03-JUL-23:48 | 195322.79 | 0.95 |
August | 0.00 | 0.00 | 0.402103E+12 | 0.348310E+12 | 596664.11 | 31-AUG-19:10 | 280587.13 | 0.90 |
September | 0.00 | 0.00 | 0.394863E+10 | 0.394863E+10 | 242164.60 | 30-SEP-23:53 | 242164.60 | 0.19 |
October | 0.00 | 0.00 | 0.169996E+12 | 0.169706E+12 | 319211.33 | 21-OCT-14:07 | 319211.33 | 0.04 |
November | 0.00 | 0.00 | 0.201866E+12 | 0.201426E+12 | 326964.90 | 01-NOV-00:22 | 326964.90 | 0.03 |
December | 0.00 | 0.00 | 0.258978E+12 | 0.258978E+12 | 262395.00 | 25-DEC-08:00 | 262395.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.233663E+13 | 0.217602E+13 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 3383165.69 | 3383165.69 | 63.72 | 63.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.402103E+12 | 0.348310E+12 | 596664.11 | 434430.17 | 0.95 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.297686E+10 | 0.297686E+10 | 8839.70 | 14-JAN-04:21 | 8839.70 | 0.00 |
February | 0.00 | 0.00 | 0.815117E+10 | 0.815117E+10 | 13831.56 | 15-FEB-05:31 | 13831.56 | 0.00 |
March | 0.00 | 0.00 | 0.155617E+11 | 0.155617E+11 | 14361.92 | 05-MAR-08:21 | 14361.92 | 0.00 |
April | 0.00 | 0.00 | 0.213917E+11 | 0.213917E+11 | 10446.70 | 23-APR-18:12 | 10446.70 | 0.00 |
May | 0.00 | 0.00 | 0.799389E+10 | 0.796483E+10 | 4563.23 | 31-MAY-23:51 | 4563.23 | 0.00 |
June | 0.00 | 0.00 | 0.129604E+11 | 0.127937E+11 | 6782.81 | 30-JUN-23:01 | 6771.81 | 0.00 |
July | 0.00 | 0.00 | 0.188705E+11 | 0.186351E+11 | 8708.06 | 31-JUL-24:00 | 8654.48 | 0.00 |
August | 0.00 | 0.00 | 0.237184E+11 | 0.234656E+11 | 10090.44 | 25-AUG-18:20 | 9843.60 | 0.00 |
September | 0.00 | 0.00 | 0.742465E+10 | 0.738802E+10 | 4640.80 | 03-SEP-17:52 | 4637.35 | 0.00 |
October | 0.00 | 0.00 | 0.116344E+11 | 0.116323E+11 | 5948.54 | 31-OCT-23:52 | 5948.54 | 0.00 |
November | 0.00 | 0.00 | 0.153998E+11 | 0.153953E+11 | 7243.11 | 09-NOV-16:02 | 7243.11 | 0.00 |
December | 0.00 | 0.00 | 0.172946E+11 | 0.172946E+11 | 14838.87 | 20-DEC-11:01 | 14838.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.163378E+12 | 0.162651E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.297686E+10 | 0.297686E+10 | 4563.23 | 4563.23 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.237184E+11 | 0.234656E+11 | 14838.87 | 14838.87 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.127309E+11 | 0.127309E+11 | 42699.05 | 06-JAN-12:42 | 42699.05 | 0.00 |
February | 0.00 | 0.00 | 0.626017E+11 | 0.626017E+11 | 131398.12 | 17-FEB-09:21 | 131398.12 | 0.00 |
March | 0.00 | 0.00 | 0.135406E+12 | 0.135406E+12 | 136134.98 | 16-MAR-04:41 | 136134.98 | 0.00 |
April | 0.00 | 0.00 | 0.194487E+12 | 0.194487E+12 | 99360.65 | 23-APR-18:01 | 99360.65 | 0.00 |
May | 0.00 | 0.00 | 0.709772E+11 | 0.706885E+11 | 44815.98 | 25-MAY-18:50 | 43563.50 | 0.00 |
June | 0.00 | 0.00 | 0.120915E+12 | 0.119255E+12 | 66190.55 | 30-JUN-23:11 | 66123.97 | 0.00 |
July | 0.00 | 0.00 | 0.177837E+12 | 0.175492E+12 | 82437.91 | 31-JUL-24:00 | 81970.89 | 0.00 |
August | 0.00 | 0.00 | 0.222468E+12 | 0.219958E+12 | 97320.42 | 25-AUG-18:20 | 94854.32 | 0.00 |
September | 0.00 | 0.00 | 0.631021E+11 | 0.627402E+11 | 44018.27 | 05-SEP-17:42 | 44018.27 | 0.00 |
October | 0.00 | 0.00 | 0.998551E+11 | 0.998349E+11 | 56574.07 | 19-OCT-16:42 | 56574.07 | 0.00 |
November | 0.00 | 0.00 | 0.127713E+12 | 0.127668E+12 | 67408.35 | 17-NOV-16:03 | 67408.35 | 0.00 |
December | 0.00 | 0.00 | 0.147129E+12 | 0.147129E+12 | 141692.18 | 20-DEC-11:01 | 141692.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143522E+13 | 0.142799E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.127309E+11 | 0.127309E+11 | 42699.05 | 42699.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.222468E+12 | 0.219958E+12 | 141692.18 | 141692.18 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.551483E+09 | 0.551483E+09 | 2287.93 | 20-JAN-16:25 | 2287.93 | 0.00 |
February | 0.00 | 0.00 | 0.441808E+10 | 0.441808E+10 | 13239.78 | 14-FEB-10:01 | 13239.78 | 0.00 |
March | 0.00 | 0.00 | 0.113937E+11 | 0.113937E+11 | 13617.15 | 16-MAR-04:41 | 13617.15 | 0.00 |
April | 0.00 | 0.00 | 0.176721E+11 | 0.176721E+11 | 9808.42 | 23-APR-18:01 | 9808.42 | 0.00 |
May | 0.00 | 0.00 | 0.622485E+10 | 0.619597E+10 | 4653.45 | 25-MAY-18:50 | 4528.84 | 0.00 |
June | 0.00 | 0.00 | 0.116331E+11 | 0.114672E+11 | 6575.11 | 30-JUN-23:01 | 6563.89 | 0.00 |
July | 0.00 | 0.00 | 0.174697E+11 | 0.172352E+11 | 8186.79 | 28-JUL-18:50 | 7919.52 | 0.00 |
August | 0.00 | 0.00 | 0.217737E+11 | 0.215249E+11 | 9881.25 | 25-AUG-18:20 | 9635.61 | 0.00 |
September | 0.00 | 0.00 | 0.513994E+10 | 0.510419E+10 | 4409.70 | 05-SEP-17:42 | 4409.70 | 0.00 |
October | 0.00 | 0.00 | 0.778680E+10 | 0.778484E+10 | 5709.40 | 19-OCT-16:42 | 5709.40 | 0.00 |
November | 0.00 | 0.00 | 0.104566E+11 | 0.104522E+11 | 6505.99 | 17-NOV-16:03 | 6505.99 | 0.00 |
December | 0.00 | 0.00 | 0.128602E+11 | 0.128602E+11 | 14372.78 | 20-DEC-11:01 | 14372.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.127380E+12 | 0.126660E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.551483E+09 | 0.551483E+09 | 2287.93 | 2287.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.217737E+11 | 0.215249E+11 | 14372.78 | 14372.78 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 614655.02 | 3841106.31 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 419712.02 | 3458925.58 | 28-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 251058.35 | 3530184.95 | 31-MAR-04:01 |
April | 0.00 | 0.00 | 01-APR-00:03 | 72782.66 | 3581806.44 | 07-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10929.04 | 3152227.31 | 01-MAY-05:01 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 2254.14 | 378596.41 | 10-JUN-05:01 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 816.22 | 160465.17 | 10-JUL-05:01 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 3059.20 | 901814.53 | 19-AUG-05:01 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 19034.41 | 3143504.72 | 23-SEP-05:01 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 68805.01 | 3684137.74 | 06-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 209503.51 | 3676641.31 | 24-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 532073.82 | 3790532.22 | 26-DEC-04:01 |
Annual Sum or Average | 0.00 | 182965.68 | ||||
Minimum of Months | 0.00 | 0.00 | 816.22 | 160465.17 | ||
Maximum of Months | 0.00 | 0.00 | 614655.02 | 3841106.31 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1766.80 | 15725.27 | 31-JAN-06:06 | 89560.22 | 939044.95 | 19-JAN-02:50 |
February | 69360.22 | 958761.07 | 08-FEB-17:53 | 178375.81 | 933242.29 | 01-FEB-00:01 |
March | 94807.73 | 1014555.08 | 31-MAR-14:02 | 8521.35 | 763910.47 | 05-MAR-15:58 |
April | 124010.18 | 1587601.76 | 23-APR-16:23 | 12502.54 | 882033.71 | 30-APR-24:00 |
May | 233024.43 | 2529863.12 | 26-MAY-12:05 | 248247.75 | 939036.65 | 09-MAY-19:20 |
June | 606536.21 | 3716886.64 | 29-JUN-04:14 | 60391.75 | 846514.80 | 01-JUN-00:22 |
July | 751397.14 | 6011431.27 | 05-JUL-10:40 | 13192.06 | 507186.24 | 24-JUL-21:07 |
August | 632764.31 | 3057420.12 | 31-AUG-12:40 | 11810.14 | 484910.60 | 23-AUG-04:04 |
September | 126613.31 | 2420471.29 | 01-SEP-11:00 | 260899.48 | 938999.33 | 05-SEP-22:40 |
October | 92646.68 | 1352940.02 | 26-OCT-13:20 | 171466.55 | 905143.36 | 07-OCT-16:42 |
November | 93135.54 | 966922.08 | 21-NOV-06:14 | 5947.09 | 831398.97 | 01-NOV-01:10 |
December | 107251.84 | 494040.88 | 06-DEC-05:10 | 5790.82 | 336603.32 | 06-DEC-06:47 |
Annual Sum or Average | 245957.18 | 88200.01 | ||||
Minimum of Months | 1766.80 | 15725.27 | 5790.82 | 336603.32 | ||
Maximum of Months | 751397.14 | 6011431.27 | 260899.48 | 939044.95 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1.81 | 16450.24 | 31-JAN-06:01 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 78725.39 | 487167.03 | 08-FEB-15:13 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 170191.76 | 1139507.38 | 31-MAR-14:04 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 231845.04 | 3051937.30 | 23-APR-17:01 | 0.00 | 0.00 | 01-APR-00:03 |
May | 248904.46 | 3414610.53 | 26-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 634301.02 | 5422966.27 | 30-JUN-03:01 | 0.00 | 0.00 | 01-JUN-00:01 |
July | 802098.87 | 6095476.17 | 05-JUL-10:40 | 0.00 | 0.00 | 01-JUL-00:01 |
August | 693730.03 | 4090903.93 | 01-AUG-04:11 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 145176.38 | 3785161.10 | 01-SEP-04:11 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 113326.38 | 1533874.95 | 18-OCT-13:32 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 196590.29 | 1080763.58 | 01-NOV-14:02 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 216675.89 | 567288.18 | 15-DEC-06:01 | 0.00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 295984.92 | 0.00 | ||||
Minimum of Months | 1.81 | 16450.24 | 0.00 | 0.00 | ||
Maximum of Months | 802098.87 | 6095476.17 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 17178.46 | 61748.42 | 31-JAN-12:15 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 17672.25 | 62342.89 | 24-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 18709.63 | 62329.18 | 01-MAR-12:35 |
April | 0.00 | 0.00 | 01-APR-00:03 | 17004.36 | 61076.40 | 03-APR-11:16 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16707.80 | 58693.69 | 01-MAY-11:38 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 16109.70 | 55326.83 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14048.94 | 52009.52 | 03-JUL-11:22 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 14953.83 | 49961.46 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 14083.47 | 50382.78 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14600.02 | 53040.62 | 31-OCT-11:37 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 15662.82 | 56303.10 | 30-NOV-12:27 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 15992.61 | 59350.51 | 29-DEC-12:13 |
Annual Sum or Average | 0.00 | 16050.86 | ||||
Minimum of Months | 0.00 | 0.00 | 14048.94 | 49961.46 | ||
Maximum of Months | 0.00 | 0.00 | 18709.63 | 62342.89 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 243.92 | 27124.95 | 23-JAN-06:30 | 4681.27 | 179565.13 | 03-JAN-04:01 |
February | 47443.80 | 715774.95 | 06-FEB-02:28 | 185.15 | 62103.74 | 08-FEB-14:21 |
March | 19042.43 | 1069132.13 | 31-MAR-14:05 | 6485.80 | 85607.20 | 24-MAR-10:30 |
April | 67557.59 | 1702964.53 | 23-APR-15:48 | 8223.59 | 172608.63 | 30-APR-05:20 |
May | 300323.94 | 4077019.11 | 26-MAY-12:05 | 1617.76 | 196194.44 | 10-MAY-04:15 |
June | 1025202.35 | 8383710.01 | 29-JUN-16:00 | 16.01 | 38770.35 | 02-JUN-17:29 |
July | 1298262.06 | 8926733.85 | 05-JUL-10:50 | 145.73 | 63814.48 | 08-JUL-02:35 |
August | 977995.84 | 7468137.21 | 08-AUG-15:10 | 392.26 | 58726.58 | 19-AUG-02:30 |
September | 159011.06 | 3593562.36 | 01-SEP-15:40 | 1338.37 | 134596.17 | 08-SEP-22:10 |
October | 102560.57 | 1404031.76 | 18-OCT-13:34 | 316.40 | 73577.78 | 05-OCT-09:57 |
November | 22838.48 | 937668.30 | 01-NOV-14:06 | 8173.16 | 159562.53 | 14-NOV-21:37 |
December | 19450.85 | 435530.39 | 26-DEC-06:40 | 11432.99 | 185382.56 | 19-DEC-20:20 |
Annual Sum or Average | 339235.56 | 3602.62 | ||||
Minimum of Months | 243.92 | 27124.95 | 16.01 | 38770.35 | ||
Maximum of Months | 1298262.06 | 8926733.85 | 11432.99 | 196194.44 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.952048E+10 | 0.62 | 12388.75 | 02-JAN-06:02 | 1.31 |
February | 0.829771E+10 | 0.57 | 11259.71 | 08-FEB-14:09 | 1.26 |
March | 0.107759E+11 | 0.62 | 21950.19 | 27-MAR-05:01 | 1.67 |
April | 0.124939E+11 | 0.63 | 22812.25 | 07-APR-05:01 | 1.70 |
May | 0.146500E+11 | 0.68 | 21589.03 | 26-MAY-04:11 | 1.64 |
June | 0.169305E+11 | 0.74 | 28753.09 | 29-JUN-04:11 | 1.85 |
July | 0.191776E+11 | 0.77 | 28753.09 | 05-JUL-10:34 | 1.84 |
August | 0.192378E+11 | 0.80 | 25242.08 | 01-AUG-04:11 | 1.75 |
September | 0.129357E+11 | 0.64 | 23069.43 | 01-SEP-15:20 | 1.68 |
October | 0.109840E+11 | 0.57 | 20321.75 | 04-OCT-05:01 | 1.61 |
November | 0.972406E+10 | 0.55 | 22812.25 | 17-NOV-06:01 | 1.70 |
December | 0.952947E+10 | 0.60 | 12951.38 | 06-DEC-06:01 | 1.33 |
Annual Sum or Average | 0.154257E+12 | 0.65 | |||
Minimum of Months | 0.829771E+10 | 0.55 | 11259.71 | 1.26 | |
Maximum of Months | 0.192378E+11 | 0.80 | 28753.09 | 1.85 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.122954E+12 | 0.80 | 133684.06 | 02-JAN-04:01 | 1.40 |
February | 0.104611E+12 | 0.74 | 133684.06 | 06-FEB-06:01 | 1.40 |
March | 0.109859E+12 | 0.68 | 141387.42 | 31-MAR-14:52 | 1.43 |
April | 0.107012E+12 | 0.61 | 193600.56 | 24-APR-05:01 | 1.62 |
May | 0.135027E+12 | 0.67 | 254446.99 | 09-MAY-05:01 | 1.83 |
June | 0.152636E+12 | 0.72 | 267064.21 | 30-JUN-03:01 | 1.85 |
July | 0.158470E+12 | 0.71 | 267064.21 | 05-JUL-10:40 | 1.84 |
August | 0.151353E+12 | 0.72 | 211819.90 | 08-AUG-15:20 | 1.67 |
September | 0.115970E+12 | 0.62 | 254446.99 | 20-SEP-05:01 | 1.82 |
October | 0.967308E+11 | 0.57 | 254446.99 | 03-OCT-05:01 | 1.83 |
November | 0.975235E+11 | 0.64 | 133684.06 | 13-NOV-05:01 | 1.40 |
December | 0.116119E+12 | 0.76 | 133684.06 | 04-DEC-05:01 | 1.40 |
Annual Sum or Average | 0.146826E+13 | 0.69 | |||
Minimum of Months | 0.967308E+11 | 0.57 | 133684.06 | 1.40 | |
Maximum of Months | 0.158470E+12 | 0.80 | 267064.21 | 1.85 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135361E+11 | 0.70 | 13363.10 | 01-JAN-04:01 | 1.13 |
February | 0.120099E+11 | 0.68 | 13363.10 | 01-FEB-05:01 | 1.13 |
March | 0.123205E+11 | 0.63 | 13363.10 | 01-MAR-05:01 | 1.13 |
April | 0.104675E+11 | 0.54 | 13363.10 | 03-APR-03:01 | 1.13 |
May | 0.110578E+11 | 0.50 | 20381.15 | 26-MAY-05:02 | 1.33 |
June | 0.124175E+11 | 0.54 | 26783.41 | 30-JUN-03:01 | 1.49 |
July | 0.128323E+11 | 0.52 | 23410.20 | 21-JUL-05:01 | 1.41 |
August | 0.121295E+11 | 0.53 | 20015.10 | 01-AUG-05:02 | 1.32 |
September | 0.954863E+10 | 0.48 | 20015.10 | 01-SEP-05:02 | 1.32 |
October | 0.100657E+11 | 0.51 | 13363.10 | 02-OCT-05:01 | 1.12 |
November | 0.117639E+11 | 0.63 | 13363.10 | 01-NOV-05:01 | 1.12 |
December | 0.132431E+11 | 0.69 | 13363.10 | 01-DEC-05:01 | 1.13 |
Annual Sum or Average | 0.141392E+12 | 0.58 | |||
Minimum of Months | 0.954863E+10 | 0.48 | 13363.10 | 1.12 | |
Maximum of Months | 0.135361E+11 | 0.70 | 26783.41 | 1.49 |
Report: FanReportMonthly
For: CAV_BAS SZVAV FAN
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.306736E+10 | 0.42 | 16466.19 | 04-JAN-07:47 | 1.89 |
February | 0.276148E+10 | 0.43 | 16466.19 | 06-FEB-06:01 | 1.88 |
March | 0.385722E+10 | 0.47 | 16466.19 | 01-MAR-06:01 | 1.88 |
April | 0.647065E+10 | 0.54 | 16466.19 | 01-APR-04:01 | 1.88 |
May | 0.752318E+10 | 0.58 | 16466.19 | 01-MAY-04:01 | 1.89 |
June | 0.807700E+10 | 0.63 | 16466.19 | 01-JUN-05:01 | 1.87 |
July | 0.874081E+10 | 0.62 | 16466.19 | 01-JUL-04:11 | 1.87 |
August | 0.112929E+11 | 0.73 | 16466.19 | 01-AUG-04:11 | 1.86 |
September | 0.929932E+10 | 0.64 | 16466.19 | 01-SEP-04:11 | 1.86 |
October | 0.746308E+10 | 0.55 | 16466.19 | 02-OCT-04:11 | 1.87 |
November | 0.551366E+10 | 0.51 | 16466.19 | 01-NOV-04:11 | 1.87 |
December | 0.294949E+10 | 0.41 | 16466.19 | 01-DEC-05:01 | 1.89 |
Annual Sum or Average | 0.770161E+11 | 0.54 | |||
Minimum of Months | 0.276148E+10 | 0.41 | 16466.19 | 1.86 | |
Maximum of Months | 0.112929E+11 | 0.73 | 16466.19 | 1.89 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SYS11 FAN
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.274298E+11 | 0.53 | 10241.10 | 01-JAN-00:01 | 0.53 |
February | 0.445061E+11 | 0.65 | 34109.12 | 01-FEB-00:03 | 0.89 |
March | 0.594368E+11 | 0.71 | 34109.12 | 01-MAR-00:02 | 0.89 |
April | 0.879777E+11 | 0.89 | 34109.12 | 01-APR-00:03 | 0.89 |
May | 0.274613E+11 | 0.53 | 34109.12 | 31-MAY-23:03 | 0.88 |
June | 0.405739E+11 | 0.61 | 34109.12 | 01-JUN-00:01 | 0.88 |
July | 0.681149E+11 | 0.76 | 34109.12 | 01-JUL-00:01 | 0.88 |
August | 0.888216E+11 | 0.87 | 34109.12 | 01-AUG-00:10 | 0.88 |
September | 0.265571E+11 | 0.53 | 34109.12 | 30-SEP-23:34 | 0.88 |
October | 0.477906E+11 | 0.64 | 34109.12 | 01-OCT-00:02 | 0.88 |
November | 0.585505E+11 | 0.72 | 34109.12 | 01-NOV-00:01 | 0.89 |
December | 0.900273E+11 | 0.88 | 34109.12 | 01-DEC-00:02 | 0.89 |
Annual Sum or Average | 0.667248E+12 | 0.69 | |||
Minimum of Months | 0.265571E+11 | 0.53 | 10241.10 | 0.53 | |
Maximum of Months | 0.900273E+11 | 0.89 | 34109.12 | 0.89 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.375395E+10 | 1.48 | 1401.56 | 16-JAN-04:36 | 1.48 |
February | 0.339066E+10 | 1.48 | 1401.56 | 01-FEB-00:19 | 1.48 |
March | 0.375395E+10 | 1.47 | 1401.56 | 01-MAR-00:06 | 1.47 |
April | 0.363285E+10 | 1.47 | 1401.56 | 10-APR-10:48 | 1.47 |
May | 0.375395E+10 | 1.46 | 1401.56 | 01-MAY-00:10 | 1.47 |
June | 0.363285E+10 | 1.46 | 1401.56 | 01-JUN-00:03 | 1.46 |
July | 0.375395E+10 | 1.46 | 1401.56 | 01-JUL-00:20 | 1.46 |
August | 0.375395E+10 | 1.46 | 1401.56 | 01-AUG-00:20 | 1.46 |
September | 0.363285E+10 | 1.46 | 1401.56 | 01-SEP-00:02 | 1.46 |
October | 0.375395E+10 | 1.47 | 1401.56 | 01-OCT-00:12 | 1.46 |
November | 0.363285E+10 | 1.47 | 1401.56 | 01-NOV-00:03 | 1.47 |
December | 0.375395E+10 | 1.48 | 1401.56 | 01-DEC-00:06 | 1.47 |
Annual Sum or Average | 0.441997E+11 | 1.47 | |||
Minimum of Months | 0.339066E+10 | 1.46 | 1401.56 | 1.46 | |
Maximum of Months | 0.375395E+10 | 1.48 | 1401.56 | 1.48 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.362401E+11 | 1.48 | 13530.51 | 03-JAN-01:23 | 1.48 |
February | 0.327330E+11 | 1.48 | 13530.51 | 20-FEB-22:12 | 1.48 |
March | 0.362401E+11 | 1.47 | 13530.51 | 10-MAR-17:01 | 1.47 |
April | 0.350711E+11 | 1.47 | 13530.51 | 01-APR-05:18 | 1.47 |
May | 0.362401E+11 | 1.46 | 13530.51 | 01-MAY-01:50 | 1.47 |
June | 0.350711E+11 | 1.46 | 13530.51 | 01-JUN-00:04 | 1.46 |
July | 0.362401E+11 | 1.46 | 13530.51 | 01-JUL-19:36 | 1.46 |
August | 0.362401E+11 | 1.46 | 13530.51 | 02-AUG-06:05 | 1.46 |
September | 0.350711E+11 | 1.46 | 13530.51 | 30-SEP-11:20 | 1.46 |
October | 0.362401E+11 | 1.47 | 13530.51 | 01-OCT-00:55 | 1.46 |
November | 0.350711E+11 | 1.47 | 13530.51 | 09-NOV-15:56 | 1.47 |
December | 0.362401E+11 | 1.48 | 13530.51 | 01-DEC-01:33 | 1.47 |
Annual Sum or Average | 0.426698E+12 | 1.47 | |||
Minimum of Months | 0.327330E+11 | 1.46 | 13530.51 | 1.46 | |
Maximum of Months | 0.362401E+11 | 1.48 | 13530.51 | 1.48 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.372107E+10 | 1.48 | 1389.29 | 02-JAN-22:02 | 1.48 |
February | 0.336096E+10 | 1.48 | 1389.29 | 01-FEB-00:19 | 1.48 |
March | 0.372107E+10 | 1.47 | 1389.29 | 02-MAR-16:45 | 1.47 |
April | 0.360103E+10 | 1.47 | 1389.29 | 01-APR-05:13 | 1.47 |
May | 0.372107E+10 | 1.46 | 1389.29 | 01-MAY-21:17 | 1.47 |
June | 0.360103E+10 | 1.46 | 1389.29 | 01-JUN-04:50 | 1.46 |
July | 0.372107E+10 | 1.46 | 1389.29 | 01-JUL-04:00 | 1.46 |
August | 0.372107E+10 | 1.46 | 1389.29 | 01-AUG-04:25 | 1.46 |
September | 0.360103E+10 | 1.46 | 1389.29 | 01-SEP-00:04 | 1.46 |
October | 0.372107E+10 | 1.47 | 1389.29 | 01-OCT-06:03 | 1.46 |
November | 0.360103E+10 | 1.47 | 1389.29 | 01-NOV-14:12 | 1.46 |
December | 0.372107E+10 | 1.48 | 1389.29 | 01-DEC-11:27 | 1.47 |
Annual Sum or Average | 0.438126E+11 | 1.47 | |||
Minimum of Months | 0.336096E+10 | 1.46 | 1389.29 | 1.46 | |
Maximum of Months | 0.372107E+10 | 1.48 | 1389.29 | 1.48 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.165363E+10 | 0.148827E+10 | 5499.48 | 30-JAN-06:02 | 4949.53 | 4949.53 | 50.68 | 25.54 |
February | 0.972326E+09 | 0.875093E+09 | 5708.68 | 21-FEB-06:01 | 5137.81 | 5137.81 | 47.54 | 26.15 |
March | 0.597257E+09 | 0.537531E+09 | 4996.41 | 06-MAR-06:01 | 4496.77 | 4496.77 | 55.46 | 24.03 |
April | 0.169087E+09 | 0.152179E+09 | 3870.40 | 10-APR-05:01 | 3483.36 | 3483.36 | 45.22 | 20.38 |
May | 27389337.85 | 24650404.07 | 3629.66 | 01-MAY-05:01 | 3266.69 | 3266.69 | 40.30 | 19.51 |
June | 5369745.41 | 4832770.87 | 342.86 | 10-JUN-05:01 | 308.58 | 308.58 | 21.07 | 2.03 |
July | 1990550.85 | 1791495.76 | 145.17 | 10-JUL-05:01 | 130.66 | 130.66 | 20.74 | 0.85 |
August | 7554299.33 | 6798869.39 | 800.72 | 19-AUG-05:01 | 720.65 | 720.65 | 26.50 | 4.85 |
September | 46652442.66 | 41987198.39 | 3542.57 | 23-SEP-05:01 | 3188.31 | 3188.31 | 31.57 | 19.23 |
October | 0.173234E+09 | 0.155911E+09 | 3724.55 | 13-OCT-05:01 | 3352.10 | 3352.10 | 40.89 | 19.87 |
November | 0.497049E+09 | 0.447344E+09 | 5033.47 | 27-NOV-06:02 | 4530.12 | 4530.12 | 54.65 | 24.15 |
December | 0.137677E+10 | 0.123909E+10 | 5689.52 | 05-DEC-06:01 | 5120.57 | 5120.57 | 46.64 | 26.11 |
Annual Sum or Average | 0.552830E+10 | 0.497547E+10 | ||||||
Minimum of Months | 1990550.85 | 1791495.76 | 145.17 | 130.66 | 130.66 | 20.74 | 0.85 | |
Maximum of Months | 0.165363E+10 | 0.148827E+10 | 5708.68 | 5137.81 | 5137.81 | 55.46 | 26.15 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 268624.41 | 241761.97 | 586.63 | 21-JAN-06:01 | 527.97 | 527.97 | 6.71 | 5.07 |
February | 0.141646E+10 | 0.127482E+10 | 2392.74 | 08-FEB-15:51 | 2153.47 | 2153.47 | 9.91 | 21.38 |
March | 0.253983E+10 | 0.228585E+10 | 4354.58 | 31-MAR-13:12 | 3919.12 | 3919.12 | 9.72 | 38.53 |
April | 0.278393E+10 | 0.250554E+10 | 17790.99 | 23-APR-17:42 | 16011.89 | 16011.89 | 9.63 | 105.37 |
May | 0.213840E+10 | 0.192456E+10 | 19241.57 | 26-MAY-05:02 | 17317.41 | 17317.41 | 9.69 | 109.73 |
June | 0.521475E+10 | 0.469327E+10 | 25102.57 | 24-JUN-05:01 | 22592.32 | 22592.32 | 9.41 | 125.01 |
July | 0.661313E+10 | 0.595181E+10 | 26674.96 | 14-JUL-05:01 | 24007.47 | 24007.47 | 10.11 | 128.63 |
August | 0.591677E+10 | 0.532510E+10 | 21897.90 | 08-AUG-05:02 | 19708.11 | 19708.11 | 10.31 | 117.07 |
September | 0.133493E+10 | 0.120143E+10 | 20087.65 | 01-SEP-05:02 | 18078.88 | 18078.88 | 10.40 | 112.15 |
October | 0.191438E+10 | 0.172294E+10 | 8017.68 | 19-OCT-12:18 | 7215.91 | 7215.91 | 7.81 | 64.24 |
November | 0.257864E+10 | 0.232077E+10 | 4194.53 | 01-NOV-14:02 | 3775.08 | 3775.08 | 8.10 | 37.20 |
December | 0.275225E+10 | 0.247703E+10 | 2392.74 | 08-DEC-06:37 | 2153.47 | 2153.47 | 9.88 | 21.38 |
Annual Sum or Average | 0.352037E+11 | 0.316834E+11 | ||||||
Minimum of Months | 268624.41 | 241761.97 | 586.63 | 527.97 | 527.97 | 6.71 | 5.07 | |
Maximum of Months | 0.661313E+10 | 0.595181E+10 | 26674.96 | 24007.47 | 24007.47 | 10.40 | 128.63 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.525297E+10 | 0.472767E+10 | 12234.64 | 01-JAN-00:01 | 11011.18 | 11011.18 | 6.75 | 64.31 |
February | 0.878126E+10 | 0.790313E+10 | 12234.64 | 01-FEB-00:03 | 11011.18 | 11011.18 | 6.80 | 64.31 |
March | 0.269176E+11 | 0.242258E+11 | 12234.64 | 01-MAR-00:02 | 11011.18 | 11011.18 | 7.73 | 64.31 |
April | 0.256014E+11 | 0.230413E+11 | 12234.64 | 01-APR-00:03 | 11011.18 | 11011.18 | 10.38 | 64.31 |
May | 0.125839E+11 | 0.113255E+11 | 12234.64 | 01-MAY-03:06 | 11011.18 | 11011.18 | 6.91 | 64.31 |
June | 0.208589E+11 | 0.187730E+11 | 12234.64 | 01-JUN-00:03 | 11011.18 | 11011.18 | 7.25 | 64.31 |
July | 0.291109E+11 | 0.261998E+11 | 12234.64 | 01-JUL-00:27 | 11011.18 | 11011.18 | 10.24 | 64.31 |
August | 0.289623E+11 | 0.260661E+11 | 12234.64 | 01-AUG-00:10 | 11011.18 | 11011.18 | 10.19 | 64.31 |
September | 0.105663E+11 | 0.950967E+10 | 12234.64 | 01-SEP-00:02 | 11011.18 | 11011.18 | 9.67 | 64.31 |
October | 0.110495E+11 | 0.994454E+10 | 12234.64 | 01-OCT-00:04 | 11011.18 | 11011.18 | 7.98 | 64.31 |
November | 0.293384E+11 | 0.264045E+11 | 12234.64 | 01-NOV-00:03 | 11011.18 | 11011.18 | 7.74 | 64.31 |
December | 0.288116E+11 | 0.259305E+11 | 12234.64 | 01-DEC-00:01 | 11011.18 | 11011.18 | 10.23 | 64.31 |
Annual Sum or Average | 0.237835E+12 | 0.214052E+12 | ||||||
Minimum of Months | 0.525297E+10 | 0.472767E+10 | 12234.64 | 11011.18 | 11011.18 | 6.75 | 64.31 | |
Maximum of Months | 0.293384E+11 | 0.264045E+11 | 12234.64 | 11011.18 | 11011.18 | 10.38 | 64.31 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 6.75 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 6.74 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 7.67 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 10.38 | 0.00 |
May | 0.891905E+09 | 0.802715E+09 | 12234.64 | 16-MAY-13:50 | 11011.18 | 11011.18 | 13.80 | 32.16 |
June | 0.303699E+10 | 0.273329E+10 | 12234.64 | 06-JUN-12:05 | 11011.18 | 11011.18 | 10.24 | 64.31 |
July | 0.574853E+10 | 0.517368E+10 | 12234.64 | 03-JUL-12:20 | 11011.18 | 11011.18 | 13.45 | 32.16 |
August | 0.435113E+10 | 0.391602E+10 | 12234.64 | 01-AUG-04:12 | 11011.18 | 11011.18 | 13.67 | 32.16 |
September | 0.245916E+09 | 0.221325E+09 | 12234.64 | 01-SEP-10:20 | 11011.18 | 11011.18 | 14.09 | 32.16 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 7.85 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 7.71 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 10.23 | 0.00 |
Annual Sum or Average | 0.142745E+11 | 0.128470E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.74 | 0.00 | |
Maximum of Months | 0.574853E+10 | 0.517368E+10 | 12234.64 | 11011.18 | 11011.18 | 14.09 | 64.31 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:01 | 16.86 | 16.86 | 57.10 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 56.67 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 56.64 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:01 | 16.86 | 16.86 | 56.67 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:01 | 16.86 | 16.86 | 57.09 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:01 | 16.86 | 16.86 | 57.02 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:01 | 16.86 | 16.86 | 57.19 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 57.18 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 57.22 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:01 | 16.86 | 16.86 | 57.29 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 57.08 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 56.97 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.64 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.29 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.135086E+11 | 0.121577E+11 | 31510.06 | 23-JAN-06:30 | 28359.06 | 28359.06 | 21.17 | 90.69 |
February | 0.226159E+11 | 0.203543E+11 | 31551.25 | 06-FEB-02:28 | 28396.13 | 28396.13 | 22.99 | 90.69 |
March | 0.692182E+11 | 0.622964E+11 | 31572.42 | 31-MAR-14:05 | 28415.18 | 28415.18 | 23.92 | 90.69 |
April | 0.658061E+11 | 0.592255E+11 | 31612.69 | 23-APR-15:48 | 28451.42 | 28451.42 | 25.59 | 90.69 |
May | 0.342620E+11 | 0.308358E+11 | 63272.51 | 26-MAY-12:05 | 56945.26 | 56945.26 | 26.48 | 181.39 |
June | 0.608228E+11 | 0.547405E+11 | 63430.27 | 29-JUN-11:30 | 57087.24 | 57087.24 | 29.62 | 181.39 |
July | 0.884281E+11 | 0.795853E+11 | 63430.27 | 03-JUL-13:10 | 57087.24 | 57087.24 | 29.57 | 181.39 |
August | 0.849045E+11 | 0.764140E+11 | 63430.27 | 08-AUG-12:20 | 57087.24 | 57087.24 | 29.61 | 181.39 |
September | 0.278509E+11 | 0.250658E+11 | 63238.71 | 01-SEP-15:40 | 56914.84 | 56914.84 | 25.84 | 181.39 |
October | 0.284550E+11 | 0.256095E+11 | 31592.50 | 18-OCT-13:34 | 28433.25 | 28433.25 | 24.80 | 90.69 |
November | 0.752052E+11 | 0.676847E+11 | 31564.54 | 01-NOV-14:06 | 28408.09 | 28408.09 | 23.57 | 90.69 |
December | 0.741871E+11 | 0.667684E+11 | 31534.48 | 26-DEC-06:40 | 28381.03 | 28381.03 | 22.25 | 90.69 |
Annual Sum or Average | 0.645265E+12 | 0.580738E+12 | ||||||
Minimum of Months | 0.135086E+11 | 0.121577E+11 | 31510.06 | 28359.06 | 28359.06 | 21.17 | 90.69 | |
Maximum of Months | 0.884281E+11 | 0.795853E+11 | 63430.27 | 57087.24 | 57087.24 | 29.62 | 181.39 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 39.64 | 39.64 | 614655.02 | 3841106.31 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 36.37 | 82.20 | 419712.02 | 3458925.58 | 28-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 26.63 | 26.63 | 251058.35 | 3530184.95 | 31-MAR-04:01 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.28 | 23.28 | 72782.66 | 3581806.44 | 07-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.24 | 20.24 | 10929.04 | 3152227.31 | 01-MAY-05:01 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 22.47 | 22.47 | 2254.14 | 378596.41 | 10-JUN-05:01 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.62 | 19.62 | 816.22 | 160465.17 | 10-JUL-05:01 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.22 | 20.22 | 3059.20 | 901814.53 | 19-AUG-05:01 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 19.73 | 19.73 | 19034.41 | 3143504.72 | 23-SEP-05:01 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 21.47 | 21.47 | 68805.01 | 3684137.74 | 06-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 27.74 | 27.74 | 209503.51 | 3676641.31 | 24-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 28.59 | 28.59 | 532073.82 | 3790532.22 | 26-DEC-04:01 |
Annual Sum or Average | 0.00 | 182965.68 | ||||||
Minimum of Months | 0.00 | 0.00 | 19.62 | 19.62 | 816.22 | 160465.17 | ||
Maximum of Months | 0.00 | 0.00 | 39.64 | 82.20 | 614655.02 | 3841106.31 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1766.80 | 15725.27 | 31-JAN-06:06 | 6.76 | 6.70 | 89560.22 | 939044.95 | 19-JAN-02:50 |
February | 69360.22 | 958761.07 | 08-FEB-17:53 | 10.26 | 6.70 | 178375.81 | 933242.29 | 01-FEB-00:01 |
March | 94807.73 | 1014555.08 | 31-MAR-14:02 | 10.48 | 6.72 | 8521.35 | 763910.47 | 05-MAR-15:58 |
April | 124010.18 | 1587601.76 | 23-APR-16:23 | 12.59 | 6.70 | 12502.54 | 882033.71 | 30-APR-24:00 |
May | 233024.43 | 2529863.12 | 26-MAY-12:05 | 11.39 | 6.70 | 248247.75 | 939036.65 | 09-MAY-19:20 |
June | 606536.21 | 3716886.64 | 29-JUN-04:14 | 13.60 | 6.85 | 60391.75 | 846514.80 | 01-JUN-00:22 |
July | 751397.14 | 6011431.27 | 05-JUL-10:40 | 17.87 | 11.12 | 13192.06 | 507186.24 | 24-JUL-21:07 |
August | 632764.31 | 3057420.12 | 31-AUG-12:40 | 12.38 | 6.70 | 11810.14 | 484910.60 | 23-AUG-04:04 |
September | 126613.31 | 2420471.29 | 01-SEP-11:00 | 11.19 | 6.70 | 260899.48 | 938999.33 | 05-SEP-22:40 |
October | 92646.68 | 1352940.02 | 26-OCT-13:20 | 11.72 | 6.70 | 171466.55 | 905143.36 | 07-OCT-16:42 |
November | 93135.54 | 966922.08 | 21-NOV-06:14 | 10.29 | 6.70 | 5947.09 | 831398.97 | 01-NOV-01:10 |
December | 107251.84 | 494040.88 | 06-DEC-05:10 | 10.48 | 8.65 | 5790.82 | 336603.32 | 06-DEC-06:47 |
Annual Sum or Average | 245957.18 | 88200.01 | ||||||
Minimum of Months | 1766.80 | 15725.27 | 6.76 | 6.70 | 5790.82 | 336603.32 | ||
Maximum of Months | 751397.14 | 6011431.27 | 17.87 | 11.12 | 260899.48 | 939044.95 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1.81 | 16450.24 | 31-JAN-06:01 | 7.47 | 6.72 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 78725.39 | 487167.03 | 08-FEB-15:13 | 12.14 | 9.67 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 170191.76 | 1139507.38 | 31-MAR-14:04 | 14.18 | 7.03 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 231845.04 | 3051937.30 | 23-APR-17:01 | 13.63 | 10.84 | 0.00 | 0.00 | 01-APR-00:03 |
May | 248904.46 | 3414610.53 | 26-MAY-05:02 | 14.13 | 10.58 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 634301.02 | 5422966.27 | 30-JUN-03:01 | 17.62 | 12.83 | 0.00 | 0.00 | 01-JUN-00:01 |
July | 802098.87 | 6095476.17 | 05-JUL-10:40 | 18.45 | 10.85 | 0.00 | 0.00 | 01-JUL-00:01 |
August | 693730.03 | 4090903.93 | 01-AUG-04:11 | 16.29 | 11.94 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 145176.38 | 3785161.10 | 01-SEP-04:11 | 15.84 | 10.31 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 113326.38 | 1533874.95 | 18-OCT-13:32 | 13.01 | 6.71 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 196590.29 | 1080763.58 | 01-NOV-14:02 | 13.64 | 7.94 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 216675.89 | 567288.18 | 15-DEC-06:01 | 13.04 | 9.71 | 0.00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 295984.92 | 0.00 | ||||||
Minimum of Months | 1.81 | 16450.24 | 7.47 | 6.71 | 0.00 | 0.00 | ||
Maximum of Months | 802098.87 | 6095476.17 | 18.45 | 12.83 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 57.78 | 57.78 | 17178.46 | 61748.42 | 31-JAN-12:15 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 57.11 | 57.11 | 17672.25 | 62342.89 | 24-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 57.08 | 57.08 | 18709.63 | 62329.18 | 01-MAR-12:35 |
April | 0.00 | 0.00 | 01-APR-00:03 | 57.13 | 57.13 | 17004.36 | 61076.40 | 03-APR-11:16 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.81 | 57.81 | 16707.80 | 58693.69 | 01-MAY-11:38 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 57.41 | 57.41 | 16109.70 | 55326.83 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 57.56 | 57.56 | 14048.94 | 52009.52 | 03-JUL-11:22 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.67 | 57.67 | 14953.83 | 49961.46 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 57.70 | 57.70 | 14083.47 | 50382.78 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 57.65 | 57.65 | 14600.02 | 53040.62 | 31-OCT-11:37 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 57.52 | 57.52 | 15662.82 | 56303.10 | 30-NOV-12:27 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 57.37 | 57.37 | 15992.61 | 59350.51 | 29-DEC-12:13 |
Annual Sum or Average | 0.00 | 16050.86 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.08 | 57.08 | 14048.94 | 49961.46 | ||
Maximum of Months | 0.00 | 0.00 | 57.81 | 57.81 | 18709.63 | 62342.89 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 243.92 | 27124.95 | 23-JAN-06:30 | 21.17 | 20.34 | 4681.27 | 179565.13 | 03-JAN-04:01 |
February | 47443.80 | 715774.95 | 06-FEB-02:28 | 22.99 | 21.10 | 185.15 | 62103.74 | 08-FEB-14:21 |
March | 19042.43 | 1069132.13 | 31-MAR-14:05 | 23.92 | 21.10 | 6485.80 | 85607.20 | 24-MAR-10:30 |
April | 67557.59 | 1702964.53 | 23-APR-15:48 | 25.59 | 21.46 | 8223.59 | 172608.63 | 30-APR-05:20 |
May | 300323.94 | 4077019.11 | 26-MAY-12:05 | 26.48 | 23.02 | 1617.76 | 196194.44 | 10-MAY-04:15 |
June | 1025202.35 | 8383710.01 | 29-JUN-16:00 | 32.16 | 27.83 | 16.01 | 38770.35 | 02-JUN-17:29 |
July | 1298262.06 | 8926733.85 | 05-JUL-10:50 | 32.87 | 27.30 | 145.73 | 63814.48 | 08-JUL-02:35 |
August | 977995.84 | 7468137.21 | 08-AUG-15:10 | 30.95 | 26.66 | 392.26 | 58726.58 | 19-AUG-02:30 |
September | 159011.06 | 3593562.36 | 01-SEP-15:40 | 25.84 | 21.91 | 1338.37 | 134596.17 | 08-SEP-22:10 |
October | 102560.57 | 1404031.76 | 18-OCT-13:34 | 24.80 | 21.10 | 316.40 | 73577.78 | 05-OCT-09:57 |
November | 22838.48 | 937668.30 | 01-NOV-14:06 | 23.57 | 21.10 | 8173.16 | 159562.53 | 14-NOV-21:37 |
December | 19450.85 | 435530.39 | 26-DEC-06:40 | 22.25 | 21.10 | 11432.99 | 185382.56 | 19-DEC-20:20 |
Annual Sum or Average | 339235.56 | 3602.62 | ||||||
Minimum of Months | 243.92 | 27124.95 | 21.17 | 20.34 | 16.01 | 38770.35 | ||
Maximum of Months | 1298262.06 | 8926733.85 | 32.87 | 27.83 | 11432.99 | 196194.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.958012E+11 | 0.00 | 288.56 | 0.952048E+10 | 0.00 | 0.00 |
February | 0.531070E+11 | 0.00 | 3610.96 | 0.829771E+10 | 0.00 | 0.00 |
March | 0.290243E+11 | 0.00 | 278.72 | 0.107759E+11 | 0.00 | 0.00 |
April | 0.429576E+10 | 0.00 | 0.572825E+10 | 0.124939E+11 | 0.00 | 0.00 |
May | 0.410422E+09 | 0.00 | 0.459015E+11 | 0.146500E+11 | 0.00 | 0.00 |
June | 15599893.83 | 0.00 | 0.104210E+12 | 0.169305E+11 | 0.00 | 0.00 |
July | 1246907.48 | 0.00 | 0.140679E+12 | 0.191776E+11 | 0.00 | 0.00 |
August | 29655487.95 | 0.00 | 0.112835E+12 | 0.192378E+11 | 0.00 | 0.00 |
September | 0.749219E+09 | 0.00 | 0.242210E+11 | 0.129357E+11 | 0.00 | 0.00 |
October | 0.432187E+10 | 0.00 | 0.398972E+10 | 0.109840E+11 | 0.00 | 0.00 |
November | 0.169936E+11 | 0.00 | 0.559479E+09 | 0.972406E+10 | 0.00 | 0.00 |
December | 0.695450E+11 | 0.00 | 1062893.78 | 0.952947E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.274295E+12 | 0.00 | 0.438125E+12 | 0.154257E+12 | 0.00 | 0.00 |
Minimum of Months | 1246907.48 | 0.00 | 278.72 | 0.829771E+10 | 0.00 | 0.00 |
Maximum of Months | 0.958012E+11 | 0.00 | 0.140679E+12 | 0.192378E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.134151E+13 | 0.00 | 79687.54 | 0.122954E+12 | 0.00 | 0.00 |
February | 0.829777E+12 | 0.00 | 61724729.79 | 0.104611E+12 | 0.00 | 0.00 |
March | 0.550775E+12 | 0.00 | 0.470785E+10 | 0.109859E+12 | 0.00 | 0.00 |
April | 0.149107E+12 | 0.00 | 0.550520E+11 | 0.107012E+12 | 0.00 | 0.00 |
May | 0.209478E+11 | 0.00 | 0.438669E+12 | 0.135027E+12 | 0.00 | 0.00 |
June | 0.353394E+10 | 0.00 | 0.953687E+12 | 0.152636E+12 | 0.00 | 0.00 |
July | 0.946177E+09 | 0.00 | 0.118708E+13 | 0.158470E+12 | 0.00 | 0.00 |
August | 0.518212E+10 | 0.00 | 0.937522E+12 | 0.151353E+12 | 0.00 | 0.00 |
September | 0.366564E+11 | 0.00 | 0.237851E+12 | 0.115970E+12 | 0.00 | 0.00 |
October | 0.141443E+12 | 0.00 | 0.481928E+11 | 0.967308E+11 | 0.00 | 0.00 |
November | 0.441498E+12 | 0.00 | 0.596113E+10 | 0.975235E+11 | 0.00 | 0.00 |
December | 0.117217E+13 | 0.00 | 178120.37 | 0.116119E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.469354E+13 | 0.00 | 0.386878E+13 | 0.146826E+13 | 0.00 | 0.00 |
Minimum of Months | 0.946177E+09 | 0.00 | 79687.54 | 0.967308E+11 | 0.00 | 0.00 |
Maximum of Months | 0.134151E+13 | 0.00 | 0.118708E+13 | 0.158470E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.207687E+12 | 0.00 | 4814712.23 | 0.135361E+11 | 0.00 | 0.00 |
February | 0.137018E+12 | 0.00 | 7252520.35 | 0.120099E+11 | 0.00 | 0.00 |
March | 0.965210E+11 | 0.00 | 7324451.20 | 0.123205E+11 | 0.00 | 0.00 |
April | 0.362344E+11 | 0.00 | 0.485663E+10 | 0.104675E+11 | 0.00 | 0.00 |
May | 0.803066E+10 | 0.00 | 0.467508E+11 | 0.110578E+11 | 0.00 | 0.00 |
June | 0.234538E+10 | 0.00 | 0.102742E+12 | 0.124175E+11 | 0.00 | 0.00 |
July | 0.124205E+10 | 0.00 | 0.128762E+12 | 0.128323E+11 | 0.00 | 0.00 |
August | 0.300910E+10 | 0.00 | 0.973381E+11 | 0.121295E+11 | 0.00 | 0.00 |
September | 0.120849E+11 | 0.00 | 0.214093E+11 | 0.954863E+10 | 0.00 | 0.00 |
October | 0.391401E+11 | 0.00 | 0.349811E+10 | 0.100657E+11 | 0.00 | 0.00 |
November | 0.874457E+11 | 0.00 | 0.463047E+09 | 0.117639E+11 | 0.00 | 0.00 |
December | 0.190276E+12 | 0.00 | 12223538.73 | 0.132431E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.821035E+12 | 0.00 | 0.405851E+12 | 0.141392E+12 | 0.00 | 0.00 |
Minimum of Months | 0.124205E+10 | 0.00 | 4814712.23 | 0.954863E+10 | 0.00 | 0.00 |
Maximum of Months | 0.207687E+12 | 0.00 | 0.128762E+12 | 0.135361E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.110469E+11 | 0.00 | 19249109.70 | 0.306736E+10 | 0.00 | 0.00 |
February | 0.150776E+10 | 0.00 | 0.156135E+09 | 0.276148E+10 | 0.00 | 0.00 |
March | 9182823.29 | 0.00 | 0.120275E+10 | 0.385722E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.742352E+10 | 0.647065E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.320570E+11 | 0.752318E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.605015E+11 | 0.807700E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.765549E+11 | 0.874081E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.704768E+11 | 0.112929E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.265505E+11 | 0.929932E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.117722E+11 | 0.746308E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.440852E+10 | 0.551366E+10 | 0.00 | 0.00 |
December | 0.142412E+10 | 0.00 | 0.121492E+09 | 0.294949E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.139880E+11 | 0.00 | 0.291245E+12 | 0.770161E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 19249109.70 | 0.276148E+10 | 0.00 | 0.00 |
Maximum of Months | 0.110469E+11 | 0.00 | 0.765549E+11 | 0.112929E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 3383165.69 | 0.121796E+12 | 0.00 | 35.10 |
February | 0.00 | 0.00 | 0.158739E+12 | 0.156378E+12 | 0.00 | 41.62 |
March | 0.00 | 0.00 | 0.222015E+12 | 0.248655E+12 | 0.00 | 70.39 |
April | 0.00 | 0.00 | 0.223204E+12 | 0.325694E+12 | 0.00 | 88.43 |
May | 0.00 | 0.00 | 0.224752E+11 | 0.110389E+12 | 0.00 | 30.85 |
June | 0.00 | 0.00 | 0.292250E+12 | 0.648078E+11 | 0.00 | 9.02 |
July | 0.00 | 0.00 | 0.381050E+12 | 0.691339E+11 | 0.00 | 0.38 |
August | 0.00 | 0.00 | 0.402103E+12 | 0.897666E+11 | 0.00 | 0.35 |
September | 0.00 | 0.00 | 0.394863E+10 | 0.590418E+11 | 0.00 | 12.08 |
October | 0.00 | 0.00 | 0.169996E+12 | 0.136039E+12 | 0.00 | 32.83 |
November | 0.00 | 0.00 | 0.201866E+12 | 0.236063E+12 | 0.00 | 66.03 |
December | 0.00 | 0.00 | 0.258978E+12 | 0.329789E+12 | 0.00 | 89.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.233663E+13 | 0.194755E+13 | 0.00 | 476.27 |
Minimum of Months | 0.00 | 0.00 | 3383165.69 | 0.590418E+11 | 0.00 | 0.35 |
Maximum of Months | 0.00 | 0.00 | 0.402103E+12 | 0.329789E+12 | 0.00 | 89.19 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.469326E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.574541E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.788545E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.915799E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.616155E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.729505E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.874717E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.997242E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.586772E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.705513E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.772080E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.817162E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.884736E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.469326E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.997242E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.397460E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.486402E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.676704E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.779403E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.547200E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.645311E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.767779E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.860820E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.515558E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.609468E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.649854E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.689904E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.762586E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.397460E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.860820E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.389921E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.470229E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.690634E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.820017E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.563187E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.694171E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.841263E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.939047E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.519129E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.603466E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.655891E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.716649E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.790360E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.389921E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.939047E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.952048E+10 | 288.56 | 0.958012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.829771E+10 | 3610.96 | 0.531070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107759E+11 | 278.72 | 0.290243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124939E+11 | 0.572825E+10 | 0.429576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146500E+11 | 0.459015E+11 | 0.410422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.169305E+11 | 0.104210E+12 | 15599893.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.191776E+11 | 0.140679E+12 | 1246907.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.192378E+11 | 0.112835E+12 | 29655487.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129357E+11 | 0.242210E+11 | 0.749219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109840E+11 | 0.398972E+10 | 0.432187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.972406E+10 | 0.559479E+09 | 0.169936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.952947E+10 | 1062893.78 | 0.695450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154257E+12 | 0.438125E+12 | 0.274295E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.829771E+10 | 278.72 | 1246907.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.192378E+11 | 0.140679E+12 | 0.958012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.122954E+12 | 79687.54 | 0.134151E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104611E+12 | 61724729.79 | 0.829777E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109859E+12 | 0.470785E+10 | 0.550775E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107012E+12 | 0.550520E+11 | 0.149107E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135027E+12 | 0.438669E+12 | 0.209478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152636E+12 | 0.953687E+12 | 0.353394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158470E+12 | 0.118708E+13 | 0.946177E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151353E+12 | 0.937522E+12 | 0.518212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115970E+12 | 0.237851E+12 | 0.366564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.967308E+11 | 0.481928E+11 | 0.141443E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.975235E+11 | 0.596113E+10 | 0.441498E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116119E+12 | 178120.37 | 0.117217E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146826E+13 | 0.386878E+13 | 0.469354E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.967308E+11 | 79687.54 | 0.946177E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158470E+12 | 0.118708E+13 | 0.134151E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135361E+11 | 4814712.23 | 0.207687E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120099E+11 | 7252520.35 | 0.137018E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123205E+11 | 7324451.20 | 0.965210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104675E+11 | 0.485663E+10 | 0.362344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110578E+11 | 0.467508E+11 | 0.803066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124175E+11 | 0.102742E+12 | 0.234538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.128323E+11 | 0.128762E+12 | 0.124205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.121295E+11 | 0.973381E+11 | 0.300910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.954863E+10 | 0.214093E+11 | 0.120849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100657E+11 | 0.349811E+10 | 0.391401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117639E+11 | 0.463047E+09 | 0.874457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132431E+11 | 12223538.73 | 0.190276E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141392E+12 | 0.405851E+12 | 0.821035E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.954863E+10 | 4814712.23 | 0.124205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135361E+11 | 0.128762E+12 | 0.207687E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.306736E+10 | 19249109.70 | 0.110469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.276148E+10 | 0.156135E+09 | 0.150776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.385722E+10 | 0.120275E+10 | 9182823.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.647065E+10 | 0.742352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.752318E+10 | 0.320570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.807700E+10 | 0.605015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.874081E+10 | 0.765549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.112929E+11 | 0.704768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.929932E+10 | 0.265505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.746308E+10 | 0.117722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.551366E+10 | 0.440852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.294949E+10 | 0.121492E+09 | 0.142412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.770161E+11 | 0.291245E+12 | 0.139880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.276148E+10 | 19249109.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.112929E+11 | 0.765549E+11 | 0.110469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.274298E+11 | 3383165.69 | 0.00 | 0.00 | 0.00 | 0.939431E+11 | 0.00 | 0.00 |
February | 0.445061E+11 | 0.158739E+12 | 0.00 | 0.00 | 0.00 | 0.111370E+12 | 0.00 | 0.00 |
March | 0.594368E+11 | 0.222015E+12 | 0.00 | 0.00 | 0.00 | 0.188371E+12 | 0.00 | 0.00 |
April | 0.879777E+11 | 0.223204E+12 | 0.00 | 0.00 | 0.00 | 0.236651E+12 | 0.00 | 0.00 |
May | 0.274613E+11 | 0.224752E+11 | 0.00 | 0.00 | 0.00 | 0.825561E+11 | 0.00 | 0.00 |
June | 0.405739E+11 | 0.292250E+12 | 0.00 | 0.00 | 0.00 | 0.241253E+11 | 0.00 | 0.00 |
July | 0.681149E+11 | 0.381050E+12 | 0.00 | 0.00 | 0.00 | 0.101437E+10 | 0.00 | 0.00 |
August | 0.888216E+11 | 0.402103E+12 | 0.00 | 0.00 | 0.00 | 0.940817E+09 | 0.00 | 0.00 |
September | 0.265571E+11 | 0.394863E+10 | 0.00 | 0.00 | 0.00 | 0.323391E+11 | 0.00 | 0.00 |
October | 0.477906E+11 | 0.169996E+12 | 0.00 | 0.00 | 0.00 | 0.878527E+11 | 0.00 | 0.00 |
November | 0.585505E+11 | 0.201866E+12 | 0.00 | 0.00 | 0.00 | 0.176717E+12 | 0.00 | 0.00 |
December | 0.900273E+11 | 0.258978E+12 | 0.00 | 0.00 | 0.00 | 0.238687E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.667248E+12 | 0.233663E+13 | 0.00 | 0.00 | 0.00 | 0.127457E+13 | 0.00 | 0.00 |
Minimum of Months | 0.265571E+11 | 3383165.69 | 0.00 | 0.00 | 0.00 | 0.940817E+09 | 0.00 | 0.00 |
Maximum of Months | 0.900273E+11 | 0.402103E+12 | 0.00 | 0.00 | 0.00 | 0.238687E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.375395E+10 | 0.297686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339066E+10 | 0.815117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.375395E+10 | 0.155617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363285E+10 | 0.213917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.375395E+10 | 0.799389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.363285E+10 | 0.129604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.375395E+10 | 0.188705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.375395E+10 | 0.237184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363285E+10 | 0.742465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.375395E+10 | 0.116344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.363285E+10 | 0.153998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.375395E+10 | 0.172946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.441997E+11 | 0.163378E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.339066E+10 | 0.297686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.375395E+10 | 0.237184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.362401E+11 | 0.127309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.327330E+11 | 0.626017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.362401E+11 | 0.135406E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.350711E+11 | 0.194487E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.362401E+11 | 0.709772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.350711E+11 | 0.120915E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.362401E+11 | 0.177837E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.362401E+11 | 0.222468E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.350711E+11 | 0.631021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.362401E+11 | 0.998551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.350711E+11 | 0.127713E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.362401E+11 | 0.147129E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.426698E+12 | 0.143522E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.327330E+11 | 0.127309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.362401E+11 | 0.222468E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.372107E+10 | 0.551483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.336096E+10 | 0.441808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.372107E+10 | 0.113937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.360103E+10 | 0.176721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.372107E+10 | 0.622485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.360103E+10 | 0.116331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.372107E+10 | 0.174697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.372107E+10 | 0.217737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.360103E+10 | 0.513994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.372107E+10 | 0.778680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.360103E+10 | 0.104566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.372107E+10 | 0.128602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438126E+11 | 0.127380E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.336096E+10 | 0.551483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.372107E+10 | 0.217737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.952048E+10 | 0.958012E+11 | 288.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.829771E+10 | 0.531070E+11 | 3610.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107759E+11 | 0.290243E+11 | 278.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124939E+11 | 0.429576E+10 | 0.572825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146500E+11 | 0.410422E+09 | 0.459015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.169305E+11 | 15599893.83 | 0.104210E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.191776E+11 | 1246907.48 | 0.140679E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.192378E+11 | 29655487.95 | 0.112835E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129357E+11 | 0.749219E+09 | 0.242210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109840E+11 | 0.432187E+10 | 0.398972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.972406E+10 | 0.169936E+11 | 0.559479E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.952947E+10 | 0.695450E+11 | 1062893.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154257E+12 | 0.274295E+12 | 0.438125E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.829771E+10 | 1246907.48 | 278.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.192378E+11 | 0.958012E+11 | 0.140679E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.122954E+12 | 0.134151E+13 | 79687.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104611E+12 | 0.829777E+12 | 61724729.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109859E+12 | 0.550775E+12 | 0.470785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107012E+12 | 0.149107E+12 | 0.550520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135027E+12 | 0.209478E+11 | 0.438669E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152636E+12 | 0.353394E+10 | 0.953687E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158470E+12 | 0.946177E+09 | 0.118708E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151353E+12 | 0.518212E+10 | 0.937522E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115970E+12 | 0.366564E+11 | 0.237851E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.967308E+11 | 0.141443E+12 | 0.481928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.975235E+11 | 0.441498E+12 | 0.596113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116119E+12 | 0.117217E+13 | 178120.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146826E+13 | 0.469354E+13 | 0.386878E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.967308E+11 | 0.946177E+09 | 79687.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158470E+12 | 0.134151E+13 | 0.118708E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135361E+11 | 0.207687E+12 | 4814712.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120099E+11 | 0.137018E+12 | 7252520.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123205E+11 | 0.965210E+11 | 7324451.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104675E+11 | 0.362344E+11 | 0.485663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110578E+11 | 0.803066E+10 | 0.467508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124175E+11 | 0.234538E+10 | 0.102742E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.128323E+11 | 0.124205E+10 | 0.128762E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.121295E+11 | 0.300910E+10 | 0.973381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.954863E+10 | 0.120849E+11 | 0.214093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100657E+11 | 0.391401E+11 | 0.349811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117639E+11 | 0.874457E+11 | 0.463047E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132431E+11 | 0.190276E+12 | 12223538.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141392E+12 | 0.821035E+12 | 0.405851E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.954863E+10 | 0.124205E+10 | 4814712.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135361E+11 | 0.207687E+12 | 0.128762E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.306736E+10 | 0.110469E+11 | 19249109.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.276148E+10 | 0.150776E+10 | 0.156135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.385722E+10 | 9182823.29 | 0.120275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.647065E+10 | 0.00 | 0.742352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.752318E+10 | 0.00 | 0.320570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.807700E+10 | 0.00 | 0.605015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.874081E+10 | 0.00 | 0.765549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.112929E+11 | 0.00 | 0.704768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.929932E+10 | 0.00 | 0.265505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.746308E+10 | 0.00 | 0.117722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.551366E+10 | 0.00 | 0.440852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.294949E+10 | 0.142412E+10 | 0.121492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.770161E+11 | 0.139880E+11 | 0.291245E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.276148E+10 | 0.00 | 19249109.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.112929E+11 | 0.110469E+11 | 0.765549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.274298E+11 | 0.00 | 3383165.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943659E+11 | 0.00 | 0.00 | 0.00 |
February | 0.445061E+11 | 0.00 | 0.158739E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111872E+12 | 0.00 | 0.00 | 0.00 |
March | 0.594368E+11 | 0.00 | 0.222015E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189219E+12 | 0.00 | 0.00 | 0.00 |
April | 0.879777E+11 | 0.00 | 0.223204E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237716E+12 | 0.00 | 0.00 | 0.00 |
May | 0.274613E+11 | 0.00 | 0.224752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829277E+11 | 0.00 | 0.00 | 0.00 |
June | 0.405739E+11 | 0.00 | 0.292250E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242339E+11 | 0.00 | 0.00 | 0.00 |
July | 0.681149E+11 | 0.00 | 0.381050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101895E+10 | 0.00 | 0.00 | 0.00 |
August | 0.888216E+11 | 0.00 | 0.402103E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.945052E+09 | 0.00 | 0.00 | 0.00 |
September | 0.265571E+11 | 0.00 | 0.394863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324847E+11 | 0.00 | 0.00 | 0.00 |
October | 0.477906E+11 | 0.00 | 0.169996E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882482E+11 | 0.00 | 0.00 | 0.00 |
November | 0.585505E+11 | 0.00 | 0.201866E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177513E+12 | 0.00 | 0.00 | 0.00 |
December | 0.900273E+11 | 0.00 | 0.258978E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239762E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.667248E+12 | 0.00 | 0.233663E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128030E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.265571E+11 | 0.00 | 3383165.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.945052E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.900273E+11 | 0.00 | 0.402103E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239762E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.375395E+10 | 0.00 | 0.00 | 0.00 | 0.939306E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339066E+10 | 0.00 | 0.00 | 0.00 | 0.235474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.375395E+10 | 0.00 | 0.00 | 0.00 | 0.413150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363285E+10 | 0.00 | 0.00 | 0.00 | 0.552513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.375395E+10 | 0.00 | 0.00 | 0.00 | 0.240760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.363285E+10 | 0.00 | 0.00 | 0.00 | 0.366220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.375395E+10 | 0.00 | 0.00 | 0.00 | 0.499322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.375395E+10 | 0.00 | 0.00 | 0.00 | 0.621847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363285E+10 | 0.00 | 0.00 | 0.00 | 0.223487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.375395E+10 | 0.00 | 0.00 | 0.00 | 0.330118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.363285E+10 | 0.00 | 0.00 | 0.00 | 0.408795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.375395E+10 | 0.00 | 0.00 | 0.00 | 0.441767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.441997E+11 | 0.00 | 0.00 | 0.00 | 0.442738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.339066E+10 | 0.00 | 0.00 | 0.00 | 0.939306E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.375395E+10 | 0.00 | 0.00 | 0.00 | 0.621847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.362401E+11 | 0.00 | 0.00 | 0.00 | 0.350585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.327330E+11 | 0.00 | 0.00 | 0.00 | 0.159072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.362401E+11 | 0.00 | 0.00 | 0.00 | 0.314302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.350711E+11 | 0.00 | 0.00 | 0.00 | 0.428693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.362401E+11 | 0.00 | 0.00 | 0.00 | 0.184799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.350711E+11 | 0.00 | 0.00 | 0.00 | 0.294600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.362401E+11 | 0.00 | 0.00 | 0.00 | 0.405377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.362401E+11 | 0.00 | 0.00 | 0.00 | 0.498419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.350711E+11 | 0.00 | 0.00 | 0.00 | 0.164847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.362401E+11 | 0.00 | 0.00 | 0.00 | 0.247067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.350711E+11 | 0.00 | 0.00 | 0.00 | 0.299143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.362401E+11 | 0.00 | 0.00 | 0.00 | 0.327502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.426698E+12 | 0.00 | 0.00 | 0.00 | 0.335888E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.327330E+11 | 0.00 | 0.00 | 0.00 | 0.350585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.362401E+11 | 0.00 | 0.00 | 0.00 | 0.498419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.372107E+10 | 0.00 | 0.00 | 0.00 | 0.178148E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.336096E+10 | 0.00 | 0.00 | 0.00 | 0.134133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.372107E+10 | 0.00 | 0.00 | 0.00 | 0.318527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.360103E+10 | 0.00 | 0.00 | 0.00 | 0.459914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.372107E+10 | 0.00 | 0.00 | 0.00 | 0.191081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.360103E+10 | 0.00 | 0.00 | 0.00 | 0.334067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.372107E+10 | 0.00 | 0.00 | 0.00 | 0.469156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.372107E+10 | 0.00 | 0.00 | 0.00 | 0.566940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.360103E+10 | 0.00 | 0.00 | 0.00 | 0.159025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.372107E+10 | 0.00 | 0.00 | 0.00 | 0.231359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.360103E+10 | 0.00 | 0.00 | 0.00 | 0.295788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.372107E+10 | 0.00 | 0.00 | 0.00 | 0.344542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438126E+11 | 0.00 | 0.00 | 0.00 | 0.352235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.336096E+10 | 0.00 | 0.00 | 0.00 | 0.178148E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.372107E+10 | 0.00 | 0.00 | 0.00 | 0.566940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.714185E+11 | 0.00 | 0.00 | 990659.99 | 0.00 | 0.238799E+10 | 0.125865E+10 | 0.00 | 0.31 |
February | 0.564996E+11 | 0.00 | 0.00 | 27794191.58 | 0.00 | 61016382.95 | 0.289650E+10 | 0.00 | 0.32 |
March | 0.522027E+11 | 0.00 | 0.00 | 96832849.07 | 0.00 | 0.00 | 0.117763E+11 | 0.00 | 0.38 |
April | 0.135704E+11 | 0.00 | 0.00 | 0.163938E+09 | 0.00 | 0.00 | 0.435832E+11 | 0.00 | 0.59 |
May | 0.471625E+10 | 0.760404E+09 | 0.00 | 0.128514E+09 | 0.00 | 0.00 | 0.380575E+11 | 0.00 | 0.76 |
June | 0.201942E+10 | 0.104643E+11 | 0.00 | 0.320036E+09 | 75598197.90 | 0.00 | 0.243127E+11 | 0.00 | 0.92 |
July | 0.642112E+09 | 0.154586E+11 | 0.00 | 0.234017E+09 | 0.243043E+09 | 0.00 | 0.185639E+11 | 0.00 | 0.88 |
August | 0.119020E+10 | 0.118467E+11 | 0.00 | 0.175621E+09 | 32462660.35 | 0.00 | 0.315968E+11 | 0.00 | 1.17 |
September | 0.578455E+10 | 0.398312E+09 | 0.00 | 0.157663E+09 | 0.00 | 0.00 | 0.477449E+11 | 0.00 | 0.92 |
October | 0.165854E+11 | 0.00 | 0.00 | 0.331847E+09 | 0.00 | 0.00 | 0.450147E+11 | 0.00 | 0.62 |
November | 0.297026E+11 | 0.00 | 0.00 | 0.252009E+09 | 0.00 | 0.00 | 0.320664E+11 | 0.00 | 0.48 |
December | 0.641966E+11 | 0.00 | 0.00 | 15663969.59 | 0.00 | 0.00 | 0.510759E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.318528E+12 | 0.389283E+11 | 0.00 | 0.190493E+10 | 0.351104E+09 | 0.244900E+10 | 0.301979E+12 | 0.00 | 0.64 |
Minimum of Months | 0.642112E+09 | 0.00 | 0.00 | 990659.99 | 0.00 | 0.00 | 0.125865E+10 | 0.00 | 0.31 |
Maximum of Months | 0.714185E+11 | 0.154586E+11 | 0.00 | 0.331847E+09 | 0.243043E+09 | 0.238799E+10 | 0.477449E+11 | 0.00 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.446516E+11 | 0.00 | 0.00 | 14413127.04 | 0.00 | 88984174.48 | 0.159334E+11 | 0.00 | 0.25 |
February | 0.333535E+11 | 0.00 | 0.00 | 0.186038E+09 | 0.00 | 0.00 | 0.156084E+11 | 0.00 | 0.26 |
March | 0.246175E+11 | 0.00 | 0.00 | 0.421814E+09 | 0.00 | 0.00 | 0.318360E+11 | 0.00 | 0.34 |
April | 0.854019E+10 | 0.00 | 0.00 | 0.274044E+09 | 22134261.43 | 0.00 | 0.486277E+11 | 0.00 | 0.61 |
May | 0.509725E+10 | 0.174657E+09 | 0.00 | 0.184771E+09 | 0.00 | 0.00 | 0.424772E+11 | 0.00 | 0.84 |
June | 0.328324E+10 | 0.526902E+10 | 0.00 | 0.370132E+09 | 0.343748E+09 | 0.00 | 0.270297E+11 | 0.00 | 0.97 |
July | 0.359105E+10 | 0.760556E+10 | 0.00 | 0.224252E+09 | 0.111055E+10 | 0.00 | 0.192859E+11 | 0.00 | 0.91 |
August | 0.418364E+10 | 0.498722E+10 | 0.00 | 0.187389E+09 | 0.104742E+09 | 0.00 | 0.326660E+11 | 0.00 | 1.18 |
September | 0.538256E+10 | 52536882.26 | 0.00 | 0.198913E+09 | 0.00 | 0.00 | 0.470959E+11 | 0.00 | 0.88 |
October | 0.129476E+11 | 0.00 | 0.00 | 0.466748E+09 | 0.00 | 0.00 | 0.404321E+11 | 0.00 | 0.55 |
November | 0.159205E+11 | 0.00 | 0.00 | 0.452322E+09 | 0.00 | 0.00 | 0.342324E+11 | 0.00 | 0.39 |
December | 0.345230E+11 | 0.00 | 0.00 | 0.100890E+09 | 0.00 | 0.00 | 0.233270E+11 | 0.00 | 0.25 |
Annual Sum or Average | 0.196092E+12 | 0.180890E+11 | 0.00 | 0.308173E+10 | 0.158118E+10 | 88984174.48 | 0.378552E+12 | 0.00 | 0.62 |
Minimum of Months | 0.328324E+10 | 0.00 | 0.00 | 14413127.04 | 0.00 | 0.00 | 0.156084E+11 | 0.00 | 0.25 |
Maximum of Months | 0.446516E+11 | 0.760556E+10 | 0.00 | 0.466748E+09 | 0.111055E+10 | 88984174.48 | 0.486277E+11 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.551938E+12 | 0.00 | 0.00 | 24060147.88 | 0.00 | 0.152169E+11 | 0.316660E+11 | 0.00 | 0.26 |
February | 0.450667E+12 | 0.00 | 0.00 | 0.250972E+09 | 0.00 | 0.624678E+10 | 0.230087E+11 | 0.00 | 0.27 |
March | 0.376222E+12 | 0.00 | 0.00 | 0.152593E+10 | 0.00 | 0.249486E+10 | 0.112778E+12 | 0.00 | 0.29 |
April | 0.180676E+12 | 0.00 | 0.00 | 0.129721E+10 | 0.528044E+09 | 0.00 | 0.231751E+12 | 0.00 | 0.45 |
May | 0.801011E+11 | 0.172354E+10 | 0.00 | 0.132662E+10 | 0.00 | 0.00 | 0.295948E+12 | 0.00 | 0.71 |
June | 0.616614E+11 | 0.469915E+11 | 0.00 | 0.232598E+10 | 0.429218E+10 | 0.00 | 0.178814E+12 | 0.00 | 0.82 |
July | 0.444757E+11 | 0.660410E+11 | 0.00 | 0.127725E+10 | 0.450054E+10 | 0.00 | 0.124300E+12 | 0.00 | 0.71 |
August | 0.578697E+11 | 0.411449E+11 | 0.00 | 0.973912E+09 | 0.798090E+09 | 0.00 | 0.191646E+12 | 0.00 | 0.87 |
September | 0.105162E+12 | 0.637065E+09 | 0.00 | 0.128151E+10 | 0.00 | 0.00 | 0.296114E+12 | 0.00 | 0.71 |
October | 0.189523E+12 | 0.00 | 0.00 | 0.244855E+10 | 0.00 | 0.00 | 0.201590E+12 | 0.00 | 0.42 |
November | 0.300056E+12 | 0.00 | 0.00 | 0.121235E+10 | 0.00 | 0.245581E+10 | 0.919519E+11 | 0.00 | 0.30 |
December | 0.524038E+12 | 0.00 | 0.00 | 48312468.83 | 0.00 | 0.950057E+10 | 0.219401E+11 | 0.00 | 0.26 |
Annual Sum or Average | 0.292239E+13 | 0.156538E+12 | 0.00 | 0.139926E+11 | 0.101189E+11 | 0.359150E+11 | 0.180151E+13 | 0.00 | 0.51 |
Minimum of Months | 0.444757E+11 | 0.00 | 0.00 | 24060147.88 | 0.00 | 0.00 | 0.219401E+11 | 0.00 | 0.26 |
Maximum of Months | 0.551938E+12 | 0.660410E+11 | 0.00 | 0.244855E+10 | 0.450054E+10 | 0.152169E+11 | 0.296114E+12 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.277733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197938E+11 | 0.00 | 0.00 | 0.21 |
February | 0.282334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105758E+11 | 0.00 | 0.00 | 0.23 |
March | 0.354225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597183E+10 | 0.00 | 0.00 | 0.27 |
April | 0.303440E+11 | 0.00 | 0.00 | 21945789.28 | 58266153.19 | 0.142465E+10 | 0.549278E+10 | 0.00 | 0.44 |
May | 0.211768E+11 | 84706493.86 | 0.00 | 51784901.11 | 0.00 | 0.162910E+09 | 0.136989E+11 | 0.00 | 0.70 |
June | 0.110653E+11 | 0.374506E+10 | 0.00 | 0.122870E+09 | 0.117234E+10 | 0.00 | 0.128372E+11 | 0.00 | 0.83 |
July | 0.721165E+10 | 0.440665E+10 | 0.00 | 58836392.71 | 0.195054E+10 | 0.00 | 0.937486E+10 | 0.00 | 0.71 |
August | 0.127794E+11 | 0.288806E+10 | 0.00 | 39085436.55 | 0.440964E+09 | 1260653.13 | 0.101758E+11 | 0.00 | 0.87 |
September | 0.274586E+11 | 0.00 | 0.00 | 21867855.25 | 0.00 | 16221404.61 | 0.803828E+10 | 0.00 | 0.69 |
October | 0.310770E+11 | 0.00 | 0.00 | 9660719.95 | 0.00 | 0.160636E+10 | 0.872886E+09 | 0.00 | 0.41 |
November | 0.266648E+11 | 0.00 | 273072.02 | 0.00 | 3752055.82 | 0.565644E+10 | 0.00 | 8016.77 | 0.28 |
December | 0.264820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168470E+11 | 0.00 | 0.00 | 0.21 |
Annual Sum or Average | 0.285689E+12 | 0.111245E+11 | 273072.02 | 0.326051E+09 | 0.362587E+10 | 0.620563E+11 | 0.604907E+11 | 8016.77 | 0.49 |
Minimum of Months | 0.721165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Maximum of Months | 0.354225E+11 | 0.440665E+10 | 273072.02 | 0.122870E+09 | 0.195054E+10 | 0.197938E+11 | 0.136989E+11 | 8016.77 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123694E+11 | 0.00 | 0.00 | 0.43 |
February | 0.280240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753485E+10 | 0.00 | 0.00 | 0.44 |
March | 0.643187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411873E+10 | 0.00 | 0.00 | 0.49 |
April | 0.743855E+10 | 0.00 | 0.00 | 4363779.89 | 4924218.26 | 0.409438E+09 | 0.102875E+10 | 0.00 | 0.74 |
May | 0.438236E+10 | 37780400.41 | 0.00 | 14651285.53 | 0.00 | 644732.36 | 0.355351E+10 | 0.00 | 1.15 |
June | 0.215063E+10 | 0.114251E+10 | 0.00 | 38198289.64 | 83450624.54 | 0.00 | 0.313349E+10 | 0.00 | 1.41 |
July | 0.172411E+10 | 0.153028E+10 | 0.00 | 18305443.68 | 0.265956E+09 | 0.00 | 0.227076E+10 | 0.00 | 1.32 |
August | 0.283472E+10 | 0.898372E+09 | 0.00 | 11757436.99 | 25249806.04 | 0.00 | 0.288382E+10 | 0.00 | 1.53 |
September | 0.567983E+10 | 8919206.06 | 0.00 | 7970095.54 | 0.00 | 0.00 | 0.259244E+10 | 0.00 | 1.12 |
October | 0.823640E+10 | 0.00 | 0.00 | 1334219.27 | 0.00 | 0.178171E+09 | 0.173980E+09 | 0.00 | 0.69 |
November | 0.631647E+10 | 0.00 | 0.00 | 119763.85 | 0.00 | 0.212245E+10 | 38304078.52 | 0.00 | 0.50 |
December | 0.208806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994181E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.511853E+11 | 0.361787E+10 | 0.00 | 96700314.39 | 0.379580E+09 | 0.366755E+11 | 0.156751E+11 | 0.00 | 0.85 |
Minimum of Months | 0.109989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.823640E+10 | 0.153028E+10 | 0.00 | 38198289.64 | 0.265956E+09 | 0.123694E+11 | 0.355351E+10 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.277167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124236E+11 | 0.00 | 0.00 | 0.76 |
February | 0.479381E+10 | 0.00 | 0.00 | 201.23 | 0.00 | 0.692081E+10 | 2306891.58 | 0.00 | 0.77 |
March | 0.727532E+10 | 0.00 | 0.00 | 10313765.13 | 0.00 | 0.404595E+10 | 0.849746E+09 | 0.00 | 0.87 |
April | 0.692971E+10 | 124363.01 | 0.00 | 18814862.39 | 5465792.58 | 0.523105E+09 | 0.379234E+10 | 0.00 | 1.45 |
May | 0.539133E+10 | 27534446.54 | 0.00 | 16346774.40 | 0.00 | 731924.13 | 0.410722E+10 | 0.00 | 2.08 |
June | 0.259731E+10 | 0.861484E+09 | 0.00 | 45999759.93 | 0.210140E+09 | 0.00 | 0.412968E+10 | 0.00 | 2.52 |
July | 0.194440E+10 | 0.126188E+10 | 0.00 | 29011921.19 | 0.461851E+09 | 0.00 | 0.307273E+10 | 0.00 | 2.41 |
August | 0.400578E+10 | 0.658252E+09 | 0.00 | 13020106.25 | 0.171658E+09 | 628250.07 | 0.261051E+10 | 0.00 | 2.61 |
September | 0.691914E+10 | 8499320.67 | 0.00 | 10703024.51 | 0.00 | 5733630.73 | 0.302308E+10 | 0.00 | 2.06 |
October | 0.895223E+10 | 0.00 | 0.00 | 5509839.88 | 0.00 | 0.390814E+09 | 0.547057E+09 | 0.00 | 1.24 |
November | 0.692329E+10 | 0.00 | 0.00 | 46458.24 | 0.00 | 0.268545E+10 | 15167129.72 | 0.00 | 0.88 |
December | 0.268612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109430E+11 | 0.00 | 0.00 | 0.73 |
Annual Sum or Average | 0.611901E+11 | 0.281777E+10 | 0.00 | 0.149767E+09 | 0.849115E+09 | 0.379398E+11 | 0.221498E+11 | 0.00 | 1.53 |
Minimum of Months | 0.194440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
Maximum of Months | 0.895223E+10 | 0.126188E+10 | 0.00 | 45999759.93 | 0.461851E+09 | 0.124236E+11 | 0.412968E+10 | 0.00 | 2.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.508304E+10 | 0.00 | 0.00 | 5145682.60 | 0.00 | 0.114870E+11 | 0.344108E+10 | 0.00 | 0.64 |
February | 0.564969E+10 | 0.00 | 0.00 | 54269154.49 | 0.00 | 0.640075E+10 | 0.444399E+10 | 0.00 | 0.72 |
March | 0.710808E+10 | 0.00 | 0.00 | 70870064.94 | 0.00 | 0.479503E+10 | 0.529303E+10 | 0.00 | 0.82 |
April | 0.736907E+10 | 4222335.30 | 0.00 | 39691668.69 | 3897283.24 | 0.977397E+09 | 0.762302E+10 | 0.00 | 1.44 |
May | 0.641283E+10 | 52543282.76 | 0.00 | 22304157.22 | 0.00 | 48137156.87 | 0.527123E+10 | 0.00 | 1.73 |
June | 0.432703E+10 | 0.135276E+10 | 0.00 | 27653532.39 | 0.218018E+09 | 0.00 | 0.286169E+10 | 0.00 | 1.91 |
July | 0.302710E+10 | 0.191846E+10 | 0.00 | 14949859.20 | 0.525091E+09 | 0.00 | 0.246885E+10 | 0.00 | 1.80 |
August | 0.502536E+10 | 0.132514E+10 | 0.00 | 14530190.39 | 67585716.74 | 778057.20 | 0.322422E+10 | 0.00 | 2.26 |
September | 0.774475E+10 | 27668574.78 | 0.00 | 24550656.02 | 0.00 | 6790199.69 | 0.625808E+10 | 0.00 | 2.02 |
October | 0.942719E+10 | 0.00 | 0.00 | 51359938.42 | 0.00 | 0.784901E+09 | 0.410271E+10 | 0.00 | 1.29 |
November | 0.739597E+10 | 0.00 | 0.00 | 40009287.55 | 0.00 | 0.306150E+10 | 0.301537E+10 | 0.00 | 0.80 |
December | 0.522795E+10 | 0.00 | 0.00 | 6988081.06 | 0.00 | 0.103207E+11 | 0.187434E+10 | 0.00 | 0.60 |
Annual Sum or Average | 0.737980E+11 | 0.468078E+10 | 0.00 | 0.372322E+09 | 0.814592E+09 | 0.378830E+11 | 0.498776E+11 | 0.00 | 1.34 |
Minimum of Months | 0.302710E+10 | 0.00 | 0.00 | 5145682.60 | 0.00 | 0.00 | 0.187434E+10 | 0.00 | 0.60 |
Maximum of Months | 0.942719E+10 | 0.191846E+10 | 0.00 | 70870064.94 | 0.525091E+09 | 0.114870E+11 | 0.762302E+10 | 0.00 | 2.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.638998E+10 | 0.00 | 0.00 | 46231.68 | 0.00 | 0.117184E+11 | 0.163376E+09 | 0.00 | 0.92 |
February | 0.792865E+10 | 0.00 | 0.00 | 5456457.06 | 0.00 | 0.580840E+10 | 0.437240E+09 | 0.00 | 0.93 |
March | 0.115810E+11 | 0.00 | 0.00 | 25299515.60 | 0.00 | 0.145830E+10 | 0.197847E+10 | 0.00 | 1.09 |
April | 0.888281E+10 | 149696.12 | 0.00 | 24779049.66 | 6579190.72 | 7229629.80 | 0.493962E+10 | 0.00 | 1.86 |
May | 0.630131E+10 | 54781743.13 | 0.00 | 18475072.11 | 0.00 | 0.00 | 0.473772E+10 | 0.00 | 2.49 |
June | 0.407834E+10 | 0.133784E+10 | 0.00 | 26855966.15 | 0.112252E+09 | 0.00 | 0.269866E+10 | 0.00 | 2.76 |
July | 0.249814E+10 | 0.196053E+10 | 0.00 | 20237211.44 | 0.325504E+09 | 0.00 | 0.264173E+10 | 0.00 | 2.64 |
August | 0.374979E+10 | 0.117302E+10 | 0.00 | 17100210.00 | 16580255.86 | 0.00 | 0.395242E+10 | 0.00 | 3.17 |
September | 0.858505E+10 | 10477059.81 | 0.00 | 9492887.92 | 0.00 | 0.00 | 0.310147E+10 | 0.00 | 2.47 |
October | 0.108372E+11 | 0.00 | 0.00 | 13605254.75 | 0.00 | 94869165.93 | 0.114023E+10 | 0.00 | 1.55 |
November | 0.105058E+11 | 0.00 | 0.00 | 3053106.17 | 0.00 | 0.801426E+09 | 0.285888E+09 | 0.00 | 1.07 |
December | 0.109565E+11 | 0.00 | 0.00 | 920.50 | 0.00 | 0.541739E+10 | 6615552.31 | 0.00 | 0.88 |
Annual Sum or Average | 0.922946E+11 | 0.453680E+10 | 0.00 | 0.164402E+09 | 0.460915E+09 | 0.253060E+11 | 0.260834E+11 | 0.00 | 1.82 |
Minimum of Months | 0.249814E+10 | 0.00 | 0.00 | 920.50 | 0.00 | 0.00 | 6615552.31 | 0.00 | 0.88 |
Maximum of Months | 0.115810E+11 | 0.196053E+10 | 0.00 | 26855966.15 | 0.325504E+09 | 0.117184E+11 | 0.493962E+10 | 0.00 | 3.17 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.353041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185280E+12 | 0.00 | 0.00 | 0.64 |
February | 0.135952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136903E+12 | 0.00 | 0.00 | 0.66 |
March | 0.452380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102626E+12 | 0.00 | 0.00 | 0.69 |
April | 0.791190E+11 | 0.00 | 0.00 | 555469.44 | 0.165125E+09 | 0.283927E+11 | 0.103287E+10 | 0.00 | 0.90 |
May | 0.717198E+11 | 0.383198E+09 | 0.00 | 49717171.38 | 0.00 | 0.219389E+10 | 0.147237E+11 | 0.00 | 1.29 |
June | 0.409922E+11 | 0.107209E+11 | 0.00 | 0.111725E+09 | 0.220151E+10 | 3815492.76 | 0.142753E+11 | 0.00 | 1.48 |
July | 0.263824E+11 | 0.139051E+11 | 0.00 | 60403849.07 | 0.328121E+10 | 0.00 | 0.131362E+11 | 0.00 | 1.29 |
August | 0.474087E+11 | 0.719801E+10 | 0.00 | 26924686.24 | 0.199482E+10 | 0.132380E+09 | 0.102547E+11 | 0.00 | 1.56 |
September | 0.867977E+11 | 0.117692E+09 | 0.00 | 6972624.79 | 0.00 | 0.391847E+10 | 0.532979E+10 | 0.00 | 1.33 |
October | 0.807667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252611E+11 | 0.00 | 0.00 | 0.88 |
November | 0.361534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822663E+11 | 0.00 | 0.00 | 0.71 |
December | 0.492808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169954E+12 | 0.00 | 0.00 | 0.64 |
Annual Sum or Average | 0.536632E+12 | 0.323249E+11 | 0.00 | 0.256299E+09 | 0.764267E+10 | 0.736932E+12 | 0.587526E+11 | 0.00 | 1.01 |
Minimum of Months | 0.353041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
Maximum of Months | 0.867977E+11 | 0.139051E+11 | 0.00 | 0.111725E+09 | 0.328121E+10 | 0.185280E+12 | 0.147237E+11 | 0.00 | 1.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.881596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131148E+12 | 0.00 | 0.00 | 0.74 |
February | 0.227166E+11 | 0.00 | 0.00 | 1684067.92 | 0.00 | 0.895750E+11 | 0.116751E+09 | 0.00 | 0.76 |
March | 0.458568E+11 | 0.00 | 0.00 | 80578471.03 | 0.00 | 0.617048E+11 | 0.612242E+10 | 0.00 | 0.83 |
April | 0.494724E+11 | 0.00 | 0.00 | 0.168097E+09 | 0.150616E+09 | 0.166426E+11 | 0.308572E+11 | 0.00 | 1.30 |
May | 0.472439E+11 | 0.298477E+09 | 0.00 | 0.161489E+09 | 1515385.11 | 0.996273E+09 | 0.351110E+11 | 0.00 | 1.96 |
June | 0.250790E+11 | 0.879900E+10 | 0.00 | 0.428414E+09 | 0.241564E+10 | 3458679.69 | 0.364941E+11 | 0.00 | 2.44 |
July | 0.179728E+11 | 0.131615E+11 | 0.00 | 0.254520E+09 | 0.335760E+10 | 4358415.93 | 0.269612E+11 | 0.00 | 2.26 |
August | 0.323083E+11 | 0.628689E+10 | 0.00 | 0.112674E+09 | 0.237279E+10 | 0.156898E+09 | 0.212784E+11 | 0.00 | 2.35 |
September | 0.564270E+11 | 0.116896E+09 | 0.00 | 99367432.06 | 0.00 | 0.244334E+10 | 0.247532E+11 | 0.00 | 1.85 |
October | 0.568841E+11 | 0.00 | 0.00 | 49054563.34 | 0.00 | 0.200497E+11 | 0.421293E+10 | 0.00 | 1.06 |
November | 0.288072E+11 | 0.00 | 0.00 | 1887939.38 | 0.00 | 0.595848E+11 | 97288038.72 | 0.00 | 0.82 |
December | 0.698817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122570E+12 | 0.00 | 0.00 | 0.73 |
Annual Sum or Average | 0.398572E+12 | 0.286627E+11 | 0.00 | 0.135777E+10 | 0.829817E+10 | 0.504879E+12 | 0.186004E+12 | 0.00 | 1.43 |
Minimum of Months | 0.698817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3458679.69 | 0.00 | 0.00 | 0.73 |
Maximum of Months | 0.568841E+11 | 0.131615E+11 | 0.00 | 0.428414E+09 | 0.335760E+10 | 0.131148E+12 | 0.364941E+11 | 0.00 | 2.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.472443E+11 | 0.00 | 0.00 | 56097560.78 | 0.00 | 0.133277E+12 | 0.382204E+11 | 0.00 | 0.74 |
February | 0.549375E+11 | 0.00 | 0.00 | 0.603397E+09 | 0.00 | 0.824653E+11 | 0.484498E+11 | 0.00 | 0.84 |
March | 0.629292E+11 | 0.00 | 0.00 | 0.800783E+09 | 0.00 | 0.665115E+11 | 0.570742E+11 | 0.00 | 0.90 |
April | 0.595182E+11 | 0.176098E+09 | 0.00 | 0.392877E+09 | 61378251.29 | 0.225303E+11 | 0.708166E+11 | 0.00 | 1.43 |
May | 0.607564E+11 | 0.584018E+09 | 0.00 | 0.207546E+09 | 0.00 | 0.222740E+10 | 0.461843E+11 | 0.00 | 1.70 |
June | 0.421341E+11 | 0.135375E+11 | 0.00 | 0.232120E+09 | 0.293823E+10 | 4128348.94 | 0.245449E+11 | 0.00 | 1.87 |
July | 0.282318E+11 | 0.197129E+11 | 0.00 | 0.113758E+09 | 0.414365E+10 | 0.00 | 0.211146E+11 | 0.00 | 1.68 |
August | 0.449967E+11 | 0.131385E+11 | 0.00 | 0.122325E+09 | 0.140424E+10 | 16113963.37 | 0.257866E+11 | 0.00 | 2.11 |
September | 0.705724E+11 | 0.410081E+09 | 0.00 | 0.249666E+09 | 0.00 | 0.265921E+10 | 0.582776E+11 | 0.00 | 2.01 |
October | 0.785924E+11 | 0.00 | 0.00 | 0.583499E+09 | 0.00 | 0.187711E+11 | 0.392557E+11 | 0.00 | 1.29 |
November | 0.535114E+11 | 0.00 | 0.00 | 0.378515E+09 | 0.00 | 0.616700E+11 | 0.269890E+11 | 0.00 | 0.86 |
December | 0.387836E+11 | 0.00 | 0.00 | 57694196.34 | 0.00 | 0.137040E+12 | 0.176546E+11 | 0.00 | 0.71 |
Annual Sum or Average | 0.642208E+12 | 0.475591E+11 | 0.00 | 0.379828E+10 | 0.854750E+10 | 0.527172E+12 | 0.474368E+12 | 0.00 | 1.35 |
Minimum of Months | 0.282318E+11 | 0.00 | 0.00 | 56097560.78 | 0.00 | 0.00 | 0.176546E+11 | 0.00 | 0.71 |
Maximum of Months | 0.785924E+11 | 0.197129E+11 | 0.00 | 0.800783E+09 | 0.414365E+10 | 0.137040E+12 | 0.708166E+11 | 0.00 | 2.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.211003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162795E+12 | 0.00 | 0.00 | 0.98 |
February | 0.359102E+11 | 0.00 | 0.00 | 24703339.32 | 0.00 | 0.109264E+12 | 0.194325E+10 | 0.00 | 1.00 |
March | 0.626167E+11 | 0.00 | 0.00 | 0.130789E+09 | 0.00 | 0.747707E+11 | 0.103949E+11 | 0.00 | 1.08 |
April | 0.696634E+11 | 0.00 | 0.00 | 0.152182E+09 | 0.162103E+09 | 0.202000E+11 | 0.281166E+11 | 0.00 | 1.60 |
May | 0.653426E+11 | 0.574891E+09 | 0.00 | 0.137801E+09 | 0.00 | 0.158819E+10 | 0.284223E+11 | 0.00 | 2.28 |
June | 0.409338E+11 | 0.110741E+11 | 0.00 | 0.183382E+09 | 0.286254E+10 | 15195373.96 | 0.176684E+11 | 0.00 | 2.52 |
July | 0.267072E+11 | 0.159004E+11 | 0.00 | 93283247.37 | 0.377188E+10 | 0.00 | 0.154454E+11 | 0.00 | 2.22 |
August | 0.456367E+11 | 0.890089E+10 | 0.00 | 58280024.31 | 0.167955E+10 | 5736179.98 | 0.143760E+11 | 0.00 | 2.61 |
September | 0.788603E+11 | 0.139399E+09 | 0.00 | 59763508.77 | 7433305.26 | 0.236107E+10 | 0.182921E+11 | 0.00 | 2.20 |
October | 0.808037E+11 | 0.00 | 0.00 | 86711385.53 | 0.00 | 0.178099E+11 | 0.710726E+10 | 0.00 | 1.38 |
November | 0.476835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683585E+11 | 0.00 | 0.00 | 1.08 |
December | 0.192636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151332E+12 | 0.00 | 0.00 | 0.97 |
Annual Sum or Average | 0.594522E+12 | 0.365896E+11 | 0.00 | 0.926895E+09 | 0.848351E+10 | 0.608500E+12 | 0.141766E+12 | 0.00 | 1.66 |
Minimum of Months | 0.192636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 |
Maximum of Months | 0.808037E+11 | 0.159004E+11 | 0.00 | 0.183382E+09 | 0.377188E+10 | 0.162795E+12 | 0.284223E+11 | 0.00 | 2.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150048E+11 | 0.00 | 0.00 | 0.54 |
February | 0.870065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114477E+11 | 0.00 | 0.00 | 0.59 |
March | 0.295619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101743E+11 | 0.00 | 0.00 | 0.68 |
April | 0.724397E+10 | 0.00 | 0.00 | 4088.16 | 18475336.83 | 0.430966E+10 | 40321666.35 | 0.00 | 1.07 |
May | 0.855057E+10 | 17851577.00 | 0.00 | 2869254.45 | 0.00 | 0.897488E+09 | 0.978348E+09 | 0.00 | 1.61 |
June | 0.525357E+10 | 0.787631E+09 | 0.00 | 4013568.78 | 0.522722E+09 | 21367334.41 | 0.129848E+10 | 0.00 | 1.80 |
July | 0.316851E+10 | 0.961678E+09 | 0.00 | 3468495.83 | 0.751548E+09 | 10940535.77 | 0.129151E+10 | 0.00 | 1.53 |
August | 0.564209E+10 | 0.426659E+09 | 0.00 | 1829687.52 | 0.445131E+09 | 0.136830E+09 | 0.913479E+09 | 0.00 | 1.97 |
September | 0.934260E+10 | 0.00 | 0.00 | 362026.95 | 0.00 | 0.142897E+10 | 0.210160E+09 | 0.00 | 1.68 |
October | 0.589422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472851E+10 | 0.00 | 0.00 | 1.02 |
November | 0.204026E+10 | 0.00 | 958203.79 | 0.00 | 85471.75 | 0.821055E+10 | 0.00 | 349630.49 | 0.72 |
December | 0.120257E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136350E+11 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.511947E+11 | 0.219382E+10 | 958203.79 | 12547121.70 | 0.173796E+10 | 0.700061E+11 | 0.473229E+10 | 349630.49 | 1.15 |
Minimum of Months | 0.112386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10940535.77 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.934260E+10 | 0.961678E+09 | 958203.79 | 4013568.78 | 0.751548E+09 | 0.150048E+11 | 0.129848E+10 | 349630.49 | 1.97 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128208E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102119E+11 | 0.00 | 0.00 | 0.57 |
February | 0.147010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695960E+10 | 0.00 | 0.00 | 0.62 |
March | 0.367408E+10 | 0.00 | 0.00 | 1382002.23 | 0.00 | 0.520981E+10 | 0.106554E+09 | 0.00 | 0.73 |
April | 0.428543E+10 | 0.00 | 0.00 | 11986540.39 | 12651831.97 | 0.199336E+10 | 0.219938E+10 | 0.00 | 1.24 |
May | 0.464545E+10 | 13688719.57 | 0.00 | 12869633.34 | 0.00 | 0.359084E+09 | 0.286331E+10 | 0.00 | 1.95 |
June | 0.231743E+10 | 0.755410E+09 | 0.00 | 35959362.01 | 0.269608E+09 | 16715817.20 | 0.355685E+10 | 0.00 | 2.45 |
July | 0.140282E+10 | 0.106725E+10 | 0.00 | 22157405.04 | 0.350001E+09 | 9534461.26 | 0.274061E+10 | 0.00 | 2.20 |
August | 0.309397E+10 | 0.424783E+09 | 0.00 | 9371911.85 | 0.255319E+09 | 61627912.98 | 0.194755E+10 | 0.00 | 2.41 |
September | 0.520544E+10 | 0.00 | 0.00 | 7492348.93 | 0.00 | 0.808161E+09 | 0.189366E+10 | 0.00 | 1.91 |
October | 0.438818E+10 | 0.00 | 0.00 | 1839814.89 | 0.00 | 0.271308E+10 | 0.186504E+09 | 0.00 | 1.09 |
November | 0.220064E+10 | 0.00 | 663558.50 | 0.00 | 58530.69 | 0.481809E+10 | 0.00 | 232040.84 | 0.76 |
December | 0.187101E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.922522E+10 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.329988E+11 | 0.226113E+10 | 663558.50 | 0.103059E+09 | 0.887638E+09 | 0.423862E+11 | 0.154944E+11 | 232040.84 | 1.38 |
Minimum of Months | 0.128208E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9534461.26 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.520544E+10 | 0.106725E+10 | 663558.50 | 35959362.01 | 0.350001E+09 | 0.102119E+11 | 0.355685E+10 | 232040.84 | 2.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.334905E+10 | 0.00 | 0.00 | 3217136.38 | 0.00 | 0.105549E+11 | 0.190949E+10 | 0.00 | 0.56 |
February | 0.389765E+10 | 0.00 | 0.00 | 43099995.90 | 0.00 | 0.695420E+10 | 0.286170E+10 | 0.00 | 0.67 |
March | 0.474048E+10 | 0.00 | 0.00 | 52309004.62 | 0.00 | 0.640830E+10 | 0.360097E+10 | 0.00 | 0.78 |
April | 0.492275E+10 | 7327381.54 | 0.00 | 32516549.77 | 13478680.91 | 0.312353E+10 | 0.639910E+10 | 0.00 | 1.41 |
May | 0.671065E+10 | 25750503.56 | 0.00 | 15572195.95 | 0.00 | 0.865292E+09 | 0.408968E+10 | 0.00 | 1.85 |
June | 0.471090E+10 | 0.102554E+10 | 0.00 | 15604502.74 | 0.507935E+09 | 0.112062E+09 | 0.266731E+10 | 0.00 | 2.07 |
July | 0.284225E+10 | 0.133869E+10 | 0.00 | 10071618.51 | 0.725980E+09 | 46879946.83 | 0.241864E+10 | 0.00 | 1.81 |
August | 0.486956E+10 | 0.827183E+09 | 0.00 | 11458318.27 | 0.303756E+09 | 0.131593E+09 | 0.267156E+10 | 0.00 | 2.33 |
September | 0.697697E+10 | 0.00 | 0.00 | 19177103.38 | 0.00 | 0.122087E+10 | 0.513887E+10 | 0.00 | 2.14 |
October | 0.589020E+10 | 0.00 | 0.00 | 45449706.69 | 0.00 | 0.328084E+10 | 0.335185E+10 | 0.00 | 1.32 |
November | 0.386683E+10 | 0.00 | 916414.31 | 26988699.10 | 161479.08 | 0.556127E+10 | 0.163349E+10 | 339659.68 | 0.78 |
December | 0.253002E+10 | 0.00 | 0.00 | 2402604.75 | 0.00 | 0.109405E+11 | 0.602325E+09 | 0.00 | 0.55 |
Annual Sum or Average | 0.553073E+11 | 0.322449E+10 | 916414.31 | 0.277867E+09 | 0.155131E+10 | 0.492003E+11 | 0.373450E+11 | 339659.68 | 1.36 |
Minimum of Months | 0.253002E+10 | 0.00 | 0.00 | 2402604.75 | 0.00 | 46879946.83 | 0.602325E+09 | 0.00 | 0.55 |
Maximum of Months | 0.697697E+10 | 0.133869E+10 | 916414.31 | 52309004.62 | 0.725980E+09 | 0.109405E+11 | 0.639910E+10 | 339659.68 | 2.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108432E+11 | 0.00 | 0.00 | 0.66 |
February | 0.211817E+10 | 0.00 | 0.00 | 1571295.70 | 0.00 | 0.743672E+10 | 0.141951E+09 | 0.00 | 0.72 |
March | 0.384817E+10 | 0.00 | 0.00 | 10594277.01 | 0.00 | 0.594411E+10 | 0.754672E+09 | 0.00 | 0.86 |
April | 0.509155E+10 | 0.00 | 0.00 | 14486545.37 | 14558169.06 | 0.230372E+10 | 0.283926E+10 | 0.00 | 1.51 |
May | 0.557983E+10 | 27111962.73 | 0.00 | 12855517.56 | 0.00 | 0.535904E+09 | 0.305345E+10 | 0.00 | 2.28 |
June | 0.363303E+10 | 0.853992E+09 | 0.00 | 18265304.24 | 0.362775E+09 | 18807795.85 | 0.220778E+10 | 0.00 | 2.55 |
July | 0.225460E+10 | 0.114775E+10 | 0.00 | 9397587.17 | 0.480077E+09 | 1673864.91 | 0.181643E+10 | 0.00 | 2.20 |
August | 0.402695E+10 | 0.588127E+09 | 0.00 | 6036933.34 | 0.235778E+09 | 65934774.05 | 0.162034E+10 | 0.00 | 2.66 |
September | 0.650170E+10 | 0.00 | 0.00 | 6008704.80 | 0.00 | 0.800222E+09 | 0.186949E+10 | 0.00 | 2.21 |
October | 0.539265E+10 | 0.00 | 0.00 | 7063736.43 | 0.00 | 0.247627E+10 | 0.627731E+09 | 0.00 | 1.29 |
November | 0.284988E+10 | 0.00 | 821057.61 | 0.00 | 67349.91 | 0.522475E+10 | 0.00 | 165432.03 | 0.88 |
December | 0.672517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101510E+11 | 0.00 | 0.00 | 0.66 |
Annual Sum or Average | 0.430078E+11 | 0.261698E+10 | 821057.61 | 86279901.63 | 0.109326E+10 | 0.458024E+11 | 0.149311E+11 | 165432.03 | 1.54 |
Minimum of Months | 0.672517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1673864.91 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.650170E+10 | 0.114775E+10 | 821057.61 | 18265304.24 | 0.480077E+09 | 0.108432E+11 | 0.305345E+10 | 165432.03 | 2.66 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 27343061.37 | 0.00 | 0.00 | 4733386.17 | 0.00 | 0.00 | 0.111572E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 71444452.89 | 0.00 | 0.00 | 0.830139E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.117549E+09 | 0.00 | 0.00 | 0.786529E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 65241705.50 | 0.00 | 0.00 | 0.517889E+09 | 0.00 | 0.29 |
May | 0.00 | 3605765.89 | 0.00 | 8254164.91 | 0.00 | 0.00 | 0.335530E+09 | 0.00 | 0.29 |
June | 0.00 | 75187217.90 | 0.00 | 29815615.77 | 0.00 | 0.00 | 0.138650E+09 | 0.00 | 0.30 |
July | 0.00 | 0.106396E+09 | 0.00 | 21932664.48 | 0.00 | 0.00 | 54836554.16 | 0.00 | 0.28 |
August | 0.00 | 70825099.14 | 0.00 | 24122080.56 | 0.00 | 0.00 | 83848241.01 | 0.00 | 0.31 |
September | 0.00 | 596581.55 | 0.00 | 8910794.26 | 0.00 | 0.00 | 0.364051E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 59060896.12 | 0.00 | 0.00 | 0.508624E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.101324E+09 | 0.00 | 0.00 | 0.603916E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 77180642.68 | 0.00 | 0.00 | 0.982187E+09 | 0.00 | 0.28 |
Annual Sum or Average | 27343061.37 | 0.256611E+09 | 0.00 | 0.589569E+09 | 0.00 | 0.00 | 0.632192E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 4733386.17 | 0.00 | 0.00 | 54836554.16 | 0.00 | 0.28 |
Maximum of Months | 27343061.37 | 0.106396E+09 | 0.00 | 0.117549E+09 | 0.00 | 0.00 | 0.111572E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.374342E+10 | 0.00 | 0.00 | 20886937.74 | 0.00 | 0.00 | 0.762860E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 0.578899E+09 | 0.00 | 0.00 | 0.842296E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.105369E+10 | 0.00 | 0.00 | 0.798704E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.605022E+09 | 0.00 | 0.00 | 0.522629E+10 | 0.00 | 0.29 |
May | 0.00 | 35322943.48 | 0.00 | 70119937.47 | 0.00 | 0.00 | 0.336975E+10 | 0.00 | 0.29 |
June | 0.00 | 0.745763E+09 | 0.00 | 0.278267E+09 | 0.00 | 0.00 | 0.140852E+10 | 0.00 | 0.30 |
July | 0.00 | 0.105612E+10 | 0.00 | 0.204841E+09 | 0.00 | 0.00 | 0.564802E+09 | 0.00 | 0.28 |
August | 0.00 | 0.699463E+09 | 0.00 | 0.226521E+09 | 0.00 | 0.00 | 0.864337E+09 | 0.00 | 0.31 |
September | 0.00 | 4909731.73 | 0.00 | 72277793.01 | 0.00 | 0.00 | 0.366167E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 0.517928E+09 | 0.00 | 0.00 | 0.515870E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.878904E+09 | 0.00 | 0.00 | 0.617365E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.679780E+09 | 0.00 | 0.00 | 0.989083E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.374342E+10 | 0.254157E+10 | 0.00 | 0.518714E+10 | 0.00 | 0.00 | 0.603571E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 20886937.74 | 0.00 | 0.00 | 0.564802E+09 | 0.00 | 0.28 |
Maximum of Months | 0.374342E+10 | 0.105612E+10 | 0.00 | 0.105369E+10 | 0.00 | 0.00 | 0.989083E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.791456E+09 | 0.00 | 0.00 | 653231.22 | 0.00 | 0.00 | 0.330864E+09 | 0.00 | 0.28 |
February | 2067644.60 | 0.00 | 0.00 | 42585740.92 | 0.00 | 0.00 | 0.853590E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 92914313.43 | 0.00 | 0.00 | 0.811130E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 56725583.38 | 0.00 | 0.00 | 0.526405E+09 | 0.00 | 0.29 |
May | 20104810.31 | 3565592.67 | 0.00 | 5772874.92 | 0.00 | 0.00 | 0.318103E+09 | 0.00 | 0.29 |
June | 0.00 | 74549297.94 | 0.00 | 26428360.73 | 0.00 | 0.00 | 0.142462E+09 | 0.00 | 0.30 |
July | 0.00 | 0.105618E+09 | 0.00 | 19501001.14 | 0.00 | 0.00 | 57607584.23 | 0.00 | 0.28 |
August | 0.00 | 69401572.64 | 0.00 | 21900893.85 | 0.00 | 0.00 | 89058509.68 | 0.00 | 0.31 |
September | 30769962.33 | 505062.22 | 0.00 | 5269877.63 | 0.00 | 0.00 | 0.338077E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 42152934.37 | 0.00 | 0.00 | 0.525577E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 77038626.55 | 0.00 | 0.00 | 0.628262E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 60724465.36 | 0.00 | 0.00 | 0.994091E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.844398E+09 | 0.253640E+09 | 0.00 | 0.451668E+09 | 0.00 | 0.00 | 0.561523E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 653231.22 | 0.00 | 0.00 | 57607584.23 | 0.00 | 0.28 |
Maximum of Months | 0.791456E+09 | 0.105618E+09 | 0.00 | 92914313.43 | 0.00 | 0.00 | 0.994091E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.119088E+10 | 0.00 | 0.00 | 0.351895E+12 | 0.00 | 3.88 |
February | 0.845472E+10 | 0.00 | 0.00 | 0.347074E+10 | 0.00 | 0.00 | 0.464167E+12 | 0.00 | 7.06 |
March | 0.292717E+10 | 0.00 | 0.00 | 0.797030E+10 | 0.00 | 0.00 | 0.791459E+12 | 0.00 | 12.36 |
April | 0.00 | 0.00 | 0.00 | 0.513818E+10 | 0.00 | 0.00 | 0.103990E+13 | 0.00 | 28.29 |
May | 996971.51 | 397846.05 | 0.00 | 0.880773E+09 | 0.00 | 0.00 | 0.328857E+12 | 0.00 | 12.84 |
June | 0.625841E+09 | 0.376739E+10 | 0.00 | 0.249642E+10 | 15624102.96 | 0.00 | 0.278248E+12 | 0.00 | 22.66 |
July | 23196456.39 | 0.104657E+11 | 0.00 | 0.425865E+10 | 0.00 | 0.00 | 0.444680E+12 | 0.00 | 37.29 |
August | 0.00 | 0.388260E+10 | 0.00 | 0.416372E+10 | 0.00 | 0.00 | 0.672742E+12 | 0.00 | 51.20 |
September | 0.00 | 0.00 | 0.00 | 0.915721E+09 | 0.00 | 0.00 | 0.292273E+12 | 0.00 | 12.67 |
October | 0.349257E+10 | 0.00 | 0.00 | 0.343409E+10 | 0.00 | 0.00 | 0.504041E+12 | 0.00 | 13.72 |
November | 11415530.70 | 0.00 | 0.00 | 0.791914E+10 | 0.00 | 0.00 | 0.779963E+12 | 0.00 | 14.85 |
December | 0.00 | 0.00 | 0.00 | 0.609137E+10 | 0.00 | 0.00 | 0.104214E+13 | 0.00 | 13.55 |
Annual Sum or Average | 0.155359E+11 | 0.181161E+11 | 0.00 | 0.479300E+11 | 15624102.96 | 0.00 | 0.699036E+13 | 0.00 | 19.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.880773E+09 | 0.00 | 0.00 | 0.278248E+12 | 0.00 | 3.88 |
Maximum of Months | 0.845472E+10 | 0.104657E+11 | 0.00 | 0.797030E+10 | 15624102.96 | 0.00 | 0.104214E+13 | 0.00 | 51.20 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:26:37
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.327427E+12 | 0.495178E+11 | 0.00 | 0.232527E+13 | 0.673732E+12 |
February | 0.430577E+12 | 0.431226E+11 | 0.00 | 0.230230E+13 | 0.742463E+12 |
March | 0.586513E+12 | 0.300599E+11 | 0.00 | 0.304101E+13 | 0.888998E+12 |
April | 0.703485E+12 | 0.272805E+11 | 0.00 | 0.348015E+13 | 0.848064E+12 |
May | 0.797482E+12 | 0.131076E+11 | 0.00 | 0.296161E+13 | 0.886608E+12 |
June | 0.807506E+12 | 0.443220E+10 | 0.00 | 0.197787E+13 | 0.207006E+13 |
July | 0.820660E+12 | 0.175116E+10 | 0.00 | 0.175003E+13 | 0.266946E+13 |
August | 0.687726E+12 | 0.581062E+10 | 0.00 | 0.254734E+13 | 0.238680E+13 |
September | 0.511586E+12 | 0.120312E+11 | 0.00 | 0.292833E+13 | 0.547221E+12 |
October | 0.309685E+12 | 0.193145E+11 | 0.00 | 0.310858E+13 | 0.587560E+12 |
November | 0.185102E+12 | 0.339389E+11 | 0.00 | 0.278289E+13 | 0.801933E+12 |
December | 0.246582E+12 | 0.531862E+11 | 0.00 | 0.301366E+13 | 0.116615E+13 |
Annual Sum or Average | 0.641433E+13 | 0.293553E+12 | 0.00 | 0.322190E+14 | 0.142690E+14 |
Minimum of Months | 0.185102E+12 | 0.175116E+10 | 0.00 | 0.175003E+13 | 0.547221E+12 |
Maximum of Months | 0.820660E+12 | 0.531862E+11 | 0.00 | 0.348015E+13 | 0.266946E+13 |