Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2024-07-03 12:21:49
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 37491.57 | 809.40 | 809.40 |
Net Site Energy | 37491.57 | 809.40 | 809.40 |
Total Source Energy | 118735.79 | 2563.36 | 2563.36 |
Net Source Energy | 118735.79 | 2563.36 | 2563.36 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 3.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6973.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1008.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3135.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2035.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1144.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36062.55 |
Humidification | 0.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 280.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 37491.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38342.76 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 3.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 6973.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 1008.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 56.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 3135.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 2035.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1144.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36062.55 |
Humidification | General | 0.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 280.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 3.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 6973.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 1008.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 3135.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 2035.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1144.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36062.55 |
Humidification | Unassigned | 0.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 280.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 293.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 809.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 293.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 809.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 37491.565 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 37491.565 | 100.00 |
Total On-Site and Utility Electric Sources | 37491.565 | 100.00 |
Total Electricity End Uses | 37491.565 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 38342.76 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 38342.76 | 100.00 |
Total Water End Uses | 38342.76 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 210.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT HP COOLING COIL | AIRLOOP DATACENTER MID HP COOLING COIL | AIRLOOP DATACENTER TOP HP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT HP COOLING COIL | AIRLOOP DATACENTER MID HP COOLING COIL | AIRLOOP DATACENTER TOP HP COOLING COIL |PlantLoopDemandReportMonthly
| COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CORE_BOTTOM PIU FAN | PERIMETER_BOT_ZN_3 PIU FAN | PERIMETER_BOT_ZN_2 PIU FAN | PERIMETER_BOT_ZN_1 PIU FAN | PERIMETER_BOT_ZN_4 PIU FAN | CORE_MID PIU FAN | PERIMETER_MID_ZN_3 PIU FAN | PERIMETER_MID_ZN_2 PIU FAN | PERIMETER_MID_ZN_1 PIU FAN | PERIMETER_MID_ZN_4 PIU FAN | CORE_TOP PIU FAN | PERIMETER_TOP_ZN_3 PIU FAN | PERIMETER_TOP_ZN_2 PIU FAN | PERIMETER_TOP_ZN_1 PIU FAN | PERIMETER_TOP_ZN_4 PIU FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS SZVAV FAN | AIRLOOP DATACENTER BASEMENT SYS11 FAN | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 11.6510 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 11.6510 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 11.6510 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.6510 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 11.6510 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.6510 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 11.6510 | 18.58 | 484.4232 | |
Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.6100 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:00 | - | - | - | - | - | - | - | - | - | - | - | 21-JUL-11:00 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 654821.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235096.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 306380.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 111454.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 64095.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 19004.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2659123.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 654821.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 306380.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 111454.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 64095.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 19004.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 12.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22083.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17769.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3194.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8307.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9930.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6446.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3623.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 888.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 118735.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 476.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 214.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 139.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 78.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 19.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 476.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 214.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 139.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 78.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 19.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 7.70 | 0.275122 | 0.300000 | 2.31 |
DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | 31.74 | 0.018817 | 0.500000 | 15.87 |
Design Size Maximum Primary Air Flow Rate [m3/s] | Design Size Maximum Secondary Air Flow Rate [m3/s] | Design Size Minimum Primary Air Flow Fraction | User-Specified Minimum Primary Air Flow Fraction | |
CORE_BOTTOM VAV BOX COMPONENT | 7.66 | 7.66 | 0.140791 | 0.300000 |
CORE_MID VAV BOX COMPONENT | 72.49 | 72.49 | 0.148693 | 0.300000 |
CORE_TOP VAV BOX COMPONENT | 8.57 | 8.57 | 0.125790 | 0.300000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.87 | 1.87 | 0.072330 | 0.300000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.65 | 1.65 | 0.052925 | 0.300000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 2.17 | 2.17 | 0.062308 | 0.300000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 2.10 | 2.10 | 0.041539 | 0.300000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 18.74 | 18.74 | 0.072205 | 0.300000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 16.87 | 16.87 | 0.051710 | 0.300000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 21.48 | 21.48 | 0.063011 | 0.300000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 19.05 | 19.05 | 0.045774 | 0.300000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 2.22 | 2.22 | 0.061024 | 0.300000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.78 | 1.78 | 0.048953 | 0.300000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 2.48 | 2.48 | 0.054647 | 0.300000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 2.12 | 2.12 | 0.041056 | 0.300000 |
Design Size Maximum Flow Rate [m3/s] | |
CORE_BOTTOM PIU FAN | 7.66 |
CORE_MID PIU FAN | 72.49 |
CORE_TOP PIU FAN | 8.57 |
PERIMETER_BOT_ZN_3 PIU FAN | 1.87 |
PERIMETER_BOT_ZN_2 PIU FAN | 1.65 |
PERIMETER_BOT_ZN_1 PIU FAN | 2.17 |
PERIMETER_BOT_ZN_4 PIU FAN | 2.10 |
PERIMETER_MID_ZN_3 PIU FAN | 18.74 |
PERIMETER_MID_ZN_2 PIU FAN | 16.87 |
PERIMETER_MID_ZN_1 PIU FAN | 21.48 |
PERIMETER_MID_ZN_4 PIU FAN | 19.05 |
PERIMETER_TOP_ZN_3 PIU FAN | 2.22 |
PERIMETER_TOP_ZN_2 PIU FAN | 1.78 |
PERIMETER_TOP_ZN_1 PIU FAN | 2.48 |
PERIMETER_TOP_ZN_4 PIU FAN | 2.12 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 165437.44 |
CORE_MID VAV BOX REHEAT COIL | 1588901.29 |
CORE_TOP VAV BOX REHEAT COIL | 186454.97 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 40436.22 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 35665.96 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 47265.62 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 45371.85 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 406874.43 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 366148.35 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 466258.92 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 413568.79 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 48054.41 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 38604.57 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 53662.78 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 46028.99 |
VAV_BOT WITH REHEAT HEATING COIL | 16678.52 |
VAV_MID WITH REHEAT HEATING COIL | 0.000000 |
VAV_TOP WITH REHEAT HEATING COIL | 0.000000 |
CAV_BAS HEATING COIL | 71253.10 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 553461.53 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 16777.01 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 159653.40 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 16836.75 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.718053 |
DATACENTER_MID_ZN_6 DIRECT AIR | 6.84 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.720586 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 4.63 | 4.63 | 15.45 | 4.63 | 13.99 | 13.99 | 0.300000 | 0.331266 | 13.99 |
VAV_MID WITH REHEAT | 44.59 | 44.59 | 148.63 | 44.59 | 131.30 | 131.30 | 0.300000 | 0.339577 | 131.30 |
VAV_TOP WITH REHEAT | 5.15 | 5.15 | 17.17 | 6.12 | 16.72 | 16.72 | 0.300000 | 0.365887 | 16.72 |
CAV_BAS | 2.31 | 2.31 | 7.70 | 2.31 | 7.70 | 7.70 | 1.00 | 0.300000 | 7.70 |
AIRLOOP DATACENTER BASEMENT | 15.87 | 15.87 | 31.74 | 15.87 | 31.74 | 31.74 | 1.00 | 0.499996 | 31.74 |
AIRLOOP DATACENTER BOT | 0.718053 | 0.718053 | 0.718053 | 0.718053 | 0.718053 | 0.718053 | 1.00 | 1.00 | 0.718053 |
AIRLOOP DATACENTER MID | 6.84 | 6.84 | 6.84 | 6.84 | 6.84 | 6.84 | 1.00 | 1.00 | 6.84 |
AIRLOOP DATACENTER TOP | 0.720586 | 0.720586 | 0.720586 | 0.720586 | 0.720586 | 0.720586 | 1.00 | 1.00 | 0.720586 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 13.99 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 131.30 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 16.72 | |
CAV_BAS_OA_CONTROLLER | 7.70 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 31.74 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.718053 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 6.84 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.720586 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.73 | 6.67 | 11.11 | 0.007791 | 0.007000 | 301537.35 | 0.010770 | 13.99 |
VAV_MID WITH REHEAT COOLING COIL | 26.91 | 6.67 | 11.11 | 0.007871 | 0.007000 | 2892544.01 | 0.103315 | 131.30 |
VAV_TOP WITH REHEAT COOLING COIL | 26.28 | 6.67 | 11.12 | 0.007704 | 0.007000 | 346628.73 | 0.012381 | 16.72 |
CAV_BAS COOLING COIL | 25.86 | 6.67 | 11.10 | 0.007903 | 0.007000 | 156030.16 | 0.005573 | 7.70 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 27.17 | 6.67 | 15.04 | 0.007073 | 0.007000 | 462985.22 | 0.016537 | 31.74 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 13.99 |
VAV_MID WITH REHEAT FAN | 131.30 |
VAV_TOP WITH REHEAT FAN | 16.72 |
CAV_BAS SZVAV FAN | 7.70 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | 31.74 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.010770 | 0.000044 |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.103315 | 0.000005 |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.012381 | 0.000038 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | Design Size Minimum Supply Air Temperature [C] | User-Specified Minimum Supply Air Temperature [C] | User-Specified Maximum Supply Air Temperature [C] | User-Specified Nominal Cooling Capacity [W] | Design Size Maximum Supply Air Temperature [C] | User-Specified Supplemental Heating Coil Nominal Capacity [W] | |
CAV_BAS_UNITARY_PACKAGE_DX | 7.70 | 7.70 | 7.70 | 2.31 | 156030.16 | 71253.10 | 1.00 | 5.33 | 12.89 | 32.11 | |||
AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | 31.74 | 31.74 | 31.74 | 15.87 | 462985.22 | 553461.53 | 1.00 | 15.89 | 29.11 | ||||
AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | 0.718053 | 0.718053 | 0.718053 | 0.718053 | 11240.59 | 1.00 | 16777.01 | 29.11 | 16777.01 | ||||
AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | 6.84 | 6.84 | 6.84 | 6.84 | 106967.78 | 1.00 | 159653.40 | 29.11 | 159653.40 | ||||
AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | 0.720586 | 0.720586 | 0.720586 | 0.720586 | 11280.62 | 1.00 | 16836.75 | 29.11 | 16836.75 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000034 | 0.000037 | 96450.70 | 100000.00 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | 0.718053 | 1234.79 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | 6.84 | 11756.21 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | 0.720586 | 1239.15 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
AIRLOOP DATACENTER BOT HP COOLING COIL | 0.718050 | 0.359027 | 0.478700 | 16777.01 | 8388.50 | 0.720480 | 0.720480 |
AIRLOOP DATACENTER MID HP COOLING COIL | 6.84 | 3.42 | 4.56 | 159653.40 | 79826.70 | 0.720610 | 0.720610 |
AIRLOOP DATACENTER TOP HP COOLING COIL | 0.720590 | 0.360293 | 0.480393 | 16836.75 | 8418.38 | 0.720470 | 0.720470 |
Design Size Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | Design Size Speed 2 Gross Rated Heating Capacity [W] | Design Size Speed 1 Gross Rated Heating Capacity [W] | Design Size Resistive Defrost Heater Capacity | |
AIRLOOP DATACENTER BOT HEATING COIL | 0.718053 | 0.359027 | 16777.01 | 8388.50 | 0.000000 |
AIRLOOP DATACENTER MID HEATING COIL | 6.84 | 3.42 | 159653.40 | 79826.70 | 0.000000 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.720586 | 0.360293 | 16836.75 | 8418.38 | 0.000000 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.148576 | 30615.98 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.148576 | 17.83 |
COOLSYS1_SUPPLY | 0.148576 | 17.83 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.148576 | 0.148576 | 623647.00 | 6.67 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.074288 | 14130.68 |
COOLSYS1 CHILLER2 PUMP | 0.074288 | 14130.68 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.148576 | 0.074900 | 2097000.55 | 2096963.58 | 0.105092 |
COOLSYS1 CHILLER2 | 0.148576 | 0.074900 | 2097000.55 | 2096963.58 | 0.105092 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.210185 | 25.22 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.210185 | 73291.70 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 84.39 | 2509327.98 | 16.88 | 313666.00 |
TOWERWATERSYS COOLTOWER 2 | 84.39 | 2509327.98 | 16.88 | 313666.00 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 11.651 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 16.493 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 11.651 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 496.074 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 32383.100 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 32383.100 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 9130.649 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 9130.649 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
26 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
27 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
35 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
47 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
48 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
49 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
50 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
51 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
52 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
53 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
54 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
55 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
56 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
57 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
58 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
59 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
60 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
61 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
62 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
63 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
64 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
65 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
66 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
67 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
68 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
69 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
70 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
71 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
72 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
73 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
74 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
75 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
76 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
77 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
78 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
79 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
80 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
81 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
82 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
83 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
84 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
85 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
86 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
87 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
88 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
89 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
90 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
91 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
92 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
93 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
94 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
95 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
96 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
97 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
98 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
99 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
100 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
101 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
102 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
103 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
104 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
105 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
106 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
107 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
108 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
109 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
110 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
111 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
112 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
113 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
114 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
115 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
116 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
117 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
118 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
119 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
120 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
121 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_1.22_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 | ||
2 | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 | ||
3 | WINDOW_U_1.22_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 | ||
4 | WINDOW_U_1.22_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone BASEMENT | 1.2500 |
3 | Zone CORE_BOTTOM | 1.2500 |
4 | Zone CORE_MID | 1.2500 |
5 | Zone CORE_TOP | 1.2500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.2500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.2500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.2500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone BASEMENT | 1.1500 |
3 | Zone CORE_BOTTOM | 1.1500 |
4 | Zone CORE_MID | 1.1500 |
5 | Zone CORE_TOP | 1.1500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.1500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.1500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.1500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 91899.18308 | 105684.06055 | 6.69402 | 7.69812 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 12.70000 | 9.15345E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 91410.55285 | 105122.13578 | 6.65693 | 7.65547 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 865710.77184 | 995567.38762 | 63.03167 | 72.48642 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 105005.47321 | 131256.84151 | 7.45688 | 10.77825 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 101409.90695 | 116621.39299 | 7.45084 | 8.56847 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 42.80000 | 1.07818E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 33703.49121 | 42129.36401 | 2.41530 | 3.01912 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 22143.71414 | 25465.27126 | 1.62698 | 1.87103 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 42.80000 | 1.07818E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 25.96112 | 32.45140 | 1.90319E-003 | 0.13533 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 19502.46882 | 22427.83914 | 1.43292 | 1.64785 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 39.35650 | 1.07759E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 378.11546 | 472.64433 | 2.75420E-002 | 8.72129E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 25705.92268 | 29561.81108 | 1.88871 | 2.17201 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 42.55750 | 1.07814E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 2210.09630 | 2762.62038 | 0.15775 | 0.19719 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 24848.36132 | 28575.61552 | 1.82569 | 2.09954 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 42.08867 | 1.07806E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 0.00000 | 0.00000 | 0.00000 | 8.72129E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 | |
17 | PERIMETER_MID_ZN_3 | Cooling | 221810.38667 | 255081.94467 | 16.29793 | 18.74262 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 42.80000 | 1.07818E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 73589.58648 | 91986.98310 | 5.31752 | 6.64690 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 199600.10172 | 229540.11697 | 14.66595 | 16.86584 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 39.59900 | 1.07763E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 49961.43390 | 62451.79237 | 3.61216 | 4.51520 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 254182.01729 | 292309.31989 | 18.67646 | 21.47793 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 42.63833 | 1.07815E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 74638.89078 | 93298.61347 | 5.39420 | 6.74275 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 225483.83904 | 259306.41489 | 16.56777 | 19.05293 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 42.08867 | 1.07806E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 41718.29436 | 52147.86795 | 3.00979 | 3.76224 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 26244.94970 | 30181.69215 | 1.92842 | 2.21768 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 10457.96780 | 13072.45975 | 0.75782 | 0.94727 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 21083.85848 | 24246.43725 | 1.54920 | 1.78157 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 40.08400 | 1.07771E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 6983.67222 | 8729.59028 | 0.50619 | 0.63274 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 29307.99709 | 33704.19665 | 2.15348 | 2.47651 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 10553.41339 | 13191.76673 | 0.76479 | 0.95598 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 25139.11578 | 28909.98314 | 1.84716 | 2.12423 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 42.08867 | 1.07806E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 6208.53942 | 7760.67427 | 0.44963 | 0.56203 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8499.26308 | 9774.15254 | 0.62439 | 0.71805 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 33.16467 | 1.07653E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 80919.76233 | 93057.72668 | 5.94473 | 6.83644 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 33.16467 | 1.07653E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8528.32967 | 9807.57912 | 0.62660 | 0.72059 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 41.83000 | 1.07801E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 375609.66579 | 431951.11566 | 27.59635 | 31.73580 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 33.97300 | 1.07667E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 12.70000 | 9.15345E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 234124.55 | 13.98806 | 13.98806 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 362.06 | 1.58477 | 1.58477 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 2225988.92 | 131.30383 | 131.30383 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 4638.27 | 32.44534 | 32.44534 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 270711.66 | 16.71870 | 16.71870 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 392.50 | 6.11715 | 6.11715 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 22:40:00 |
7 | CAV_BAS | Cooling | Sensible | 120803.19 | 7.69812 | 7.69812 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
8 | CAV_BAS | Heating | Sensible | 28174.01 | 1.20016 | 1.20016 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 432394.49 | 31.73604 | 31.73604 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 6716.07 | 0.33839 | 0.33839 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 9896.76 | 0.71805 | 0.71805 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 310.25 | 1.56323E-002 | 1.56323E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 94214.23 | 6.83644 | 6.83644 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 3102.54 | 0.15632 | 0.15632 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 9964.84 | 0.72059 | 0.72059 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 310.25 | 1.56323E-002 | 1.56323E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 7.69812 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.27512 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 2.30944 |
5 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 7.65547 |
6 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 7.65547 |
7 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 0.14079 |
8 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
9 | Fan:ConstantVolume | CORE_BOTTOM PIU FAN | Design Size Maximum Flow Rate [m3/s] | 7.65547 |
10 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 165437.44063 |
11 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 72.48642 |
12 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 72.48642 |
13 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 0.14869 |
14 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
15 | Fan:ConstantVolume | CORE_MID PIU FAN | Design Size Maximum Flow Rate [m3/s] | 72.48642 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 1588901.28877 |
17 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 8.56847 |
18 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 8.56847 |
19 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 0.12579 |
20 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
21 | Fan:ConstantVolume | CORE_TOP PIU FAN | Design Size Maximum Flow Rate [m3/s] | 8.56847 |
22 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 186454.97050 |
23 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.87103 |
24 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.87103 |
25 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 7.23300E-002 |
26 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
27 | Fan:ConstantVolume | PERIMETER_BOT_ZN_3 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.87103 |
28 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 40436.22009 |
29 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.64785 |
30 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.64785 |
31 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 5.29251E-002 |
32 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
33 | Fan:ConstantVolume | PERIMETER_BOT_ZN_2 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.64785 |
34 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 35665.95913 |
35 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 2.17201 |
36 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 2.17201 |
37 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 6.23084E-002 |
38 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
39 | Fan:ConstantVolume | PERIMETER_BOT_ZN_1 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 2.17201 |
40 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 47265.62467 |
41 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 2.09954 |
42 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 2.09954 |
43 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 4.15390E-002 |
44 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
45 | Fan:ConstantVolume | PERIMETER_BOT_ZN_4 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 2.09954 |
46 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 45371.85409 |
47 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 18.74262 |
48 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 18.74262 |
49 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 7.22053E-002 |
50 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
51 | Fan:ConstantVolume | PERIMETER_MID_ZN_3 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 18.74262 |
52 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 406874.42841 |
53 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 16.86584 |
54 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 16.86584 |
55 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 5.17098E-002 |
56 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
57 | Fan:ConstantVolume | PERIMETER_MID_ZN_2 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 16.86584 |
58 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 366148.35300 |
59 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 21.47793 |
60 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 21.47793 |
61 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 6.30110E-002 |
62 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
63 | Fan:ConstantVolume | PERIMETER_MID_ZN_1 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 21.47793 |
64 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 466258.91756 |
65 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 19.05293 |
66 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 19.05293 |
67 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 4.57740E-002 |
68 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
69 | Fan:ConstantVolume | PERIMETER_MID_ZN_4 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 19.05293 |
70 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 413568.79074 |
71 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 2.21768 |
72 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 2.21768 |
73 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 6.10238E-002 |
74 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
75 | Fan:ConstantVolume | PERIMETER_TOP_ZN_3 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 2.21768 |
76 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 48054.40618 |
77 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.78157 |
78 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.78157 |
79 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 4.89527E-002 |
80 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
81 | Fan:ConstantVolume | PERIMETER_TOP_ZN_2 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.78157 |
82 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 38604.57340 |
83 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 2.47651 |
84 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 2.47651 |
85 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 5.46474E-002 |
86 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
87 | Fan:ConstantVolume | PERIMETER_TOP_ZN_1 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 2.47651 |
88 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 53662.78178 |
89 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 2.12423 |
90 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 2.12423 |
91 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 4.10562E-002 |
92 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
93 | Fan:ConstantVolume | PERIMETER_TOP_ZN_4 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 2.12423 |
94 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 46028.99021 |
95 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.71805 |
96 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.83644 |
97 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.72059 |
98 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 31.73580 |
99 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 1.88167E-002 |
100 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
101 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 15.86790 |
102 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.63377 |
103 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.63377 |
104 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 15.44591 |
105 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.63377 |
106 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 13.98806 |
107 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 13.98806 |
108 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
109 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.33127 |
110 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 44.58772 |
111 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 44.58772 |
112 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 148.62574 |
113 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 44.58772 |
114 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 131.30383 |
115 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 131.30383 |
116 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
117 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.33958 |
118 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.15054 |
119 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.15054 |
120 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 17.16847 |
121 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 6.11715 |
122 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 16.71870 |
123 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 16.71870 |
124 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.36589 |
126 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.30944 |
127 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.30944 |
128 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.69812 |
129 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.30944 |
130 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.69812 |
131 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 7.69812 |
132 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
133 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.30000 |
134 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 15.86790 |
135 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 15.86790 |
136 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 31.73580 |
137 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 15.86790 |
138 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 31.73604 |
139 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 31.73604 |
140 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
141 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.50000 |
142 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.71805 |
143 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.71805 |
144 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.71805 |
145 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.71805 |
146 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.71805 |
147 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.71805 |
148 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
149 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
150 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.83644 |
151 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.83644 |
152 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.83644 |
153 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 6.83644 |
154 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.83644 |
155 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 6.83644 |
156 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
157 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
158 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.72059 |
159 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.72059 |
160 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.72059 |
161 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.72059 |
162 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.72059 |
163 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.72059 |
164 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
165 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
166 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 13.98806 |
167 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 131.30383 |
168 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 16.71870 |
169 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 7.69812 |
170 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 31.73604 |
171 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.71805 |
172 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 6.83644 |
173 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.72059 |
174 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 13.98806 |
175 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.72788 |
176 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
177 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.11456 |
178 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.79128E-003 |
179 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
180 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 301537.35061 |
181 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.07702E-002 |
182 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 13.98806 |
183 | Coil:Heating:Electric | VAV_BOT WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 16678.51710 |
184 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 13.98806 |
185 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.07702E-002 |
186 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.42136E-005 |
187 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 131.30383 |
188 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.90607 |
189 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
190 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.10728 |
191 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.87111E-003 |
192 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
193 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2892544.00713 |
194 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 0.10331 |
195 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 131.30383 |
196 | Coil:Heating:Electric | VAV_MID WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
197 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 131.30383 |
198 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.10331 |
199 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.60911E-006 |
200 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 16.71870 |
201 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.28287 |
202 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
203 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.12362 |
204 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.70437E-003 |
205 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
206 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 346628.72606 |
207 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.23808E-002 |
208 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 16.71870 |
209 | Coil:Heating:Electric | VAV_TOP WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
210 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 16.71870 |
211 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.23808E-002 |
212 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.84621E-005 |
213 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.69812 |
214 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
215 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.69812 |
216 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.69812 |
217 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.69812 |
218 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.30944 |
219 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.86393 |
220 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
221 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.09787 |
222 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.90311E-003 |
223 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
224 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 156030.15749 |
225 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.57304E-003 |
226 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.69812 |
227 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 156030.15749 |
228 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 71253.09859 |
229 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
230 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Minimum Supply Air Temperature [C] | 5.33439 |
231 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 12.88890 |
232 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 32.11110 |
233 | Coil:Heating:Electric | CAV_BAS HEATING COIL | Design Size Nominal Capacity [W] | 71253.09859 |
234 | Fan:VariableVolume | CAV_BAS SZVAV FAN | Design Size Maximum Flow Rate [m3/s] | 7.69812 |
235 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 31.73604 |
236 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
237 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 31.73604 |
238 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 31.73604 |
239 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 31.73604 |
240 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 15.86802 |
241 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.16668 |
242 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
243 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 15.04159 |
244 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.07267E-003 |
245 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
246 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Coil Load [W] | 462985.21597 |
247 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.65368E-002 |
248 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 31.73604 |
249 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 462985.21597 |
250 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 553461.52813 |
251 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
252 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 15.88890 |
253 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 29.11110 |
254 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Nominal Capacity [W] | 553461.52813 |
255 | Fan:VariableVolume | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Design Size Maximum Flow Rate [m3/s] | 31.73604 |
256 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 3.41881E-005 |
257 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
258 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
259 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
260 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.71805 |
261 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
262 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.71805 |
263 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1234.79269 |
264 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.71805 |
265 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.71805 |
266 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.71805 |
267 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.71805 |
268 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.71805 |
269 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.35903 |
270 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.47870 |
271 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16777.01000 |
272 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8388.50500 |
273 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72048 |
274 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72048 |
275 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16777.01000 |
276 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 11240.59482 |
277 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
278 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 16777.00720 |
279 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:DX:MultiSpeed | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 0.71805 |
281 | Coil:Heating:DX:MultiSpeed | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.35903 |
282 | Coil:Heating:DX:MultiSpeed | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 16777.00720 |
283 | Coil:Heating:DX:MultiSpeed | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 8388.50360 |
284 | Coil:Heating:DX:MultiSpeed | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
285 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 16777.00720 |
286 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.83644 |
287 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
288 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 6.83644 |
289 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 11756.21111 |
290 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 6.83644 |
291 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 6.83644 |
292 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 6.83644 |
293 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 6.83644 |
294 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 6.83644 |
295 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.41822 |
296 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.55763 |
297 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 159653.40000 |
298 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 79826.70000 |
299 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72061 |
300 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72061 |
301 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 159653.40000 |
302 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 106967.77521 |
303 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
304 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 159653.39584 |
305 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
306 | Coil:Heating:DX:MultiSpeed | AIRLOOP DATACENTER MID HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 6.83644 |
307 | Coil:Heating:DX:MultiSpeed | AIRLOOP DATACENTER MID HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.41822 |
308 | Coil:Heating:DX:MultiSpeed | AIRLOOP DATACENTER MID HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 159653.39584 |
309 | Coil:Heating:DX:MultiSpeed | AIRLOOP DATACENTER MID HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 79826.69792 |
310 | Coil:Heating:DX:MultiSpeed | AIRLOOP DATACENTER MID HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
311 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 159653.39584 |
312 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.72059 |
313 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
314 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.72059 |
315 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1239.14806 |
316 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.72059 |
317 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.72059 |
318 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.72059 |
319 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.72059 |
320 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.72059 |
321 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.36029 |
322 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.48039 |
323 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16836.75000 |
324 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8418.37500 |
325 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72047 |
326 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72047 |
327 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16836.75000 |
328 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 11280.62294 |
329 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
330 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 16836.75066 |
331 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
332 | Coil:Heating:DX:MultiSpeed | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 0.72059 |
333 | Coil:Heating:DX:MultiSpeed | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.36029 |
334 | Coil:Heating:DX:MultiSpeed | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 16836.75066 |
335 | Coil:Heating:DX:MultiSpeed | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 8418.37533 |
336 | Coil:Heating:DX:MultiSpeed | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
337 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 16836.75066 |
338 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.14858 |
339 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 30615.98140 |
340 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.14858 |
341 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 17.82909 |
342 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.14858 |
343 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.14858 |
344 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 623646.99509 |
345 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 6.67000 |
346 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.14858 |
347 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 17.82909 |
348 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 7.42879E-002 |
349 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 14130.67939 |
350 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 7.42879E-002 |
351 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 14130.67939 |
352 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.14858 |
353 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 7.49000E-002 |
354 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 2097000.54731 |
355 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 2096963.58000 |
356 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 0.10509 |
357 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.14858 |
358 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 7.49000E-002 |
359 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 2097000.54731 |
360 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 2096963.58000 |
361 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 0.10509 |
362 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
363 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
364 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
365 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
366 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
367 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.21018 |
368 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 25.22218 |
369 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.21018 |
370 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 73291.70298 |
371 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 84.38567 |
372 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 2509327.97732 |
373 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 16.87713 |
374 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 313665.99717 |
375 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 84.38567 |
376 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 2509327.97732 |
377 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 16.87713 |
378 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 313665.99717 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 389082.18 | 265285.69 | 123796.48 | 0.68 | 61118.72 | 619.90 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 3682038.25 | 2502929.62 | 1179108.63 | 0.68 | 574789.57 | 5829.83 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 458586.50 | 314349.22 | 144237.28 | 0.69 | 73127.31 | 741.70 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 212223.91 | 145326.23 | 66897.68 | 0.68 | 35674.59 | 361.83 |
5 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | 641061.45 | 486012.36 | 155049.09 | 0.76 | 75931.10 | 770.14 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT HP COOLING COIL | 16211.2 | 9.66 | 9.66 | |||
2 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID HP COOLING COIL | 154266.4 | 9.94 | 9.94 | |||
3 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP HP COOLING COIL | 16268.9 | 9.66 | 9.66 |
Component Type | Component Name | High Temperature Heating (net) Rating Capacity {W} | Low Temperature Heating (net) Rating Capacity {W} | HSPF {Btu/W-h} | Region Number | |
1 | Coil:Heating:DX:MultiSpeed | AIRLOOP DATACENTER BOT HEATING COIL | 17352.6 | 9563.1 | 7.82 | 2 |
2 | Coil:Heating:DX:MultiSpeed | AIRLOOP DATACENTER MID HEATING COIL | 165133.6 | 91007.4 | 7.23 | 2 |
3 | Coil:Heating:DX:MultiSpeed | AIRLOOP DATACENTER TOP HEATING COIL | 17414.4 | 9597.2 | 7.91 | 2 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 6.37 | 21.74 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 6.37 | 21.74 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.25 | N/A | 6.926 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.25 | N/A | 6.926 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.25 | N/A | 6.926 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.25 | N/A | 6.926 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.25 | N/A | 6.926 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.25 | N/A | 6.926 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.25 | N/A | 6.926 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.25 | N/A | 6.926 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.25 | N/A | 6.926 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.25 | N/A | 6.926 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2117884445 | 0.1871498858 | Pass | Pass | 0.8911547361 | 2.0458160278 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1120931619 | 0.2176962333 | Pass | Pass | 9.0896632116E-002 | 0.2861604619 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.5396488194E-002 | 0.1180137757 | Pass | Pass | 2.1388659707E-002 | 0.1447058637 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.2128542338E-002 | 1.8733562133E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1763624569 | 0.3048522066 | Pass | Pass | 9.2112412586E-002 | 0.2849890801 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2186863517 | 0.3924311965 | Pass | Pass | 9.3182531730E-002 | 0.2846297512 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2324957322 | 0.3825474577 | Pass | Pass | 9.4373277006E-002 | 0.2917822465 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2753846513 | 0.5265444779 | Pass | Pass | 9.4074034605E-002 | 0.2833410530 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 9.5778310253E-002 | 0.1719703933 | Pass | Pass | 2.2453942930E-002 | 0.1462198380 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1162395956 | 0.2293259677 | Pass | Pass | 2.3574373462E-002 | 0.1503100335 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1529516554 | 0.2437874640 | Pass | Pass | 2.5548897153E-002 | 0.1627838814 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1391410821 | 0.2747836102 | Pass | Pass | 2.3795070374E-002 | 0.1489065661 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.5652208414E-002 | 4.6847018904E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.9486525188E-002 | 4.4868238587E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1036713215 | 8.3368184253E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.0985177996E-002 | 6.5529651329E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.2450451998E-002 | 5.0630478316E-002 | Pass | Pass | 0.1115811040 | 0.3289410539 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.4737332058E-002 | 2.3434197597E-002 | Pass | Pass | 2.5575189668E-002 | 0.1596043018 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.7089363230E-002 | 7.1995761080E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.7816307214E-005 | 2.9801276138E-005 | Pass | Pass | 2.8244711060E-003 | 2.1973013320E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.2171196739E-005 | 2.5173723506E-005 | Pass | Pass | 8.2300843746E-003 | 4.2701176584E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.2071909858E-002 | 5.3161894143E-002 | Pass | Pass | 0.5082894367 | 3.5923767396 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.7338460230E-004 | 3.2256412100E-004 | Pass | Pass | 5.9928323212E-005 | 1.0723097365E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6145.97 | -145.6 | 0.00 | -9611.5 | 50355.83 | 46744.72 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_1.22_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_1.22_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_1.22_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_1.22_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_1.22_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_1.22_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_1.22_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_1.22_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_1.22_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_1.22_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_1.22_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_1.22_SHGC_NORTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 6.926 | 0.251 | 0.277 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_1.22_SHGC_EAST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 6.926 | 0.251 | 0.277 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 6.926 | 0.251 | 0.277 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_1.22_SHGC_WEST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 6.926 | 0.251 | 0.277 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_1.22_SHGC_NORTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 6.926 | 0.251 | 0.277 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_1.22_SHGC_EAST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 6.926 | 0.251 | 0.277 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 6.926 | 0.251 | 0.277 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_1.22_SHGC_WEST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 6.926 | 0.251 | 0.277 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 6.926 | 0.251 | 0.277 | |||||||||||||||||
North Total or Average | 1390.74 | 6.926 | 0.251 | 0.277 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 6.926 | 0.251 | 0.277 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 11.6510 | 2779.43 | 32383.10 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 333.79 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.6510 | 24961.20 | 290822.99 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 2997.66 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.6510 | 3134.13 | 36515.73 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.6510 | 3134.20 | 36516.53 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 11.6510 | 783.68 | 9130.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 94.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 22.3674 | 362.03 | 8097.60 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 83.47 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
Interior Lighting Total | 11.7515 | 46320.38 | 544334.28 | 1723.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 64082.80 | AstronomicalClock | - | 83.85 | 83.85 | 1008.65 | |
Exterior Lighting Total | 64082.80 | 1008.65 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 4148887.00 | |||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 2096963.58 | 6.11 | 2086731.53 | 6.08 | 6.37 | 21.74 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 2096963.58 | 6.11 | 2086731.53 | 6.08 | 6.37 | 21.74 |
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 2509327.98 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 2509327.98 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 301537.35 | 389082.18 | 265285.69 | 123796.48 | 0.68 | - | 61118.72 | 619.90 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2892544.01 | 3682038.25 | 2502929.62 | 1179108.63 | 0.68 | - | 574789.57 | 5829.83 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 346628.73 | 458586.50 | 314349.22 | 144237.28 | 0.69 | - | 73127.31 | 741.70 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 156030.16 | 212223.91 | 145326.23 | 66897.68 | 0.68 | - | 35674.59 | 361.83 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | 462985.22 | 641061.45 | 486012.36 | 155049.09 | 0.76 | - | 75931.10 | 770.14 |
AIRLOOP DATACENTER BOT HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16777.01 | 12087.50 | 4689.51 | 0.72 | 3.00 | |||
AIRLOOP DATACENTER MID HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 159653.40 | 115047.84 | 44605.56 | 0.72 | 3.10 | |||
AIRLOOP DATACENTER TOP HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16836.75 | 12130.37 | 4706.38 | 0.72 | 3.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
AIRLOOP DATACENTER BOT HP COOLING COIL | 16211.2 | 9.66 | 9.66 | ||||
AIRLOOP DATACENTER MID HP COOLING COIL | 154266.4 | 9.94 | 9.94 | ||||
AIRLOOP DATACENTER TOP HP COOLING COIL | 16268.9 | 9.66 | 9.66 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
AIRLOOP DATACENTER BOT HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER MID HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER TOP HP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:DX:MultiSpeed | 17352.6 | 9563.1 | 7.82 | 2 |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:DX:MultiSpeed | 165133.6 | 91007.4 | 7.23 | 2 |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:DX:MultiSpeed | 17414.4 | 9597.2 | 7.91 | 2 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 165437.44 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 1588901.29 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 186454.97 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 40436.22 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 35665.96 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 47265.62 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 45371.85 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 406874.43 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 366148.35 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 466258.92 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 413568.79 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 48054.41 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 38604.57 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 53662.78 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 46028.99 | 1.00 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | 16678.52 | 1.00 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
CAV_BAS HEATING COIL | Coil:Heating:Electric | 71253.10 | 1.00 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Electric | 553461.53 | 1.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:DX:MultiSpeed | 16777.01 | 3.40 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 16777.01 | 1.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:DX:MultiSpeed | 159653.40 | 3.40 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 159653.40 | 1.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:DX:MultiSpeed | 16836.75 | 3.40 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 16836.75 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
CORE_BOTTOM PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 7.66 | 5674.65 | 741.25 | 1.00 | 1.16 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
CORE_MID PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 72.49 | 53730.84 | 741.25 | 1.00 | 1.09 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
CORE_TOP PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 8.57 | 6351.41 | 741.25 | 1.00 | 1.16 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PERIMETER_BOT_ZN_3 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.87 | 1386.91 | 741.25 | 1.00 | 1.31 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 |
PERIMETER_BOT_ZN_2 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.65 | 1221.48 | 741.25 | 1.00 | 1.33 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 |
PERIMETER_BOT_ZN_1 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 2.17 | 1610.01 | 741.25 | 1.00 | 1.28 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
PERIMETER_BOT_ZN_4 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 2.10 | 1556.29 | 741.25 | 1.00 | 1.29 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 |
PERIMETER_MID_ZN_3 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 18.74 | 13893.04 | 741.25 | 1.00 | 1.12 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 |
PERIMETER_MID_ZN_2 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 16.87 | 12501.87 | 741.25 | 1.00 | 1.13 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PERIMETER_MID_ZN_1 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 21.48 | 15920.60 | 741.25 | 1.00 | 1.12 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
PERIMETER_MID_ZN_4 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 19.05 | 14123.06 | 741.25 | 1.00 | 1.12 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 |
PERIMETER_TOP_ZN_3 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 2.22 | 1643.87 | 741.25 | 1.00 | 1.28 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
PERIMETER_TOP_ZN_2 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.78 | 1320.60 | 741.25 | 1.00 | 1.32 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 |
PERIMETER_TOP_ZN_1 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 2.48 | 1835.72 | 741.25 | 1.00 | 1.26 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 |
PERIMETER_TOP_ZN_4 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 2.12 | 1574.60 | 741.25 | 1.00 | 1.29 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 13.99 | 30449.91 | 2176.85 | 1.00 | 1.12 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 131.30 | 287043.71 | 2186.10 | 1.00 | 1.08 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1337.13 | 16.72 | 36202.54 | 2165.39 | 1.00 | 1.12 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
CAV_BAS SZVAV FAN | Fan:VariableVolume | 0.61 | 1337.13 | 7.70 | 16918.78 | 2197.78 | 1.00 | 1.13 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 0.61 | 637.69 | 31.74 | 32947.05 | 1038.16 | 1.00 | 1.19 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.72 | 1234.79 | 1719.64 | 1.00 | 1.37 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 6.84 | 11756.21 | 1719.64 | 1.00 | 1.09 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.72 | 1239.15 | 1719.64 | 1.00 | 1.37 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.83 | 0.148576 | 30615.98 | 206063.11 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.074288 | 14130.68 | 190215.15 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.074288 | 14130.68 | 190215.15 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 209234.68 | 0.210185 | 73291.70 | 348701.22 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 91899.18 | 105684.06 | 38.02 | 6.694 | 7.698 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00737 | 35.62 | 0.01077 | 1.200 | 0.00 |
CORE_BOTTOM | 91410.55 | 105122.14 | 42.11 | 6.657 | 7.655 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00734 | 35.62 | 0.01077 | 1.078 | 0.00 |
CORE_MID | 865710.77 | 995567.39 | 398.85 | 63.032 | 72.486 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00736 | 35.62 | 0.01077 | 10.778 | 0.00 |
CORE_TOP | 101409.91 | 116621.39 | 46.72 | 7.451 | 8.568 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00730 | 42.80 | 0.01078 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 22143.71 | 25465.27 | 81.25 | 1.627 | 1.871 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00723 | 42.80 | 0.01078 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 19502.47 | 22427.84 | 111.04 | 1.433 | 1.648 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 24.00 | 24.00 | 0.00717 | 39.36 | 0.01078 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 25705.92 | 29561.81 | 94.32 | 1.889 | 2.172 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00720 | 42.56 | 0.01078 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 24848.36 | 28575.62 | 141.48 | 1.826 | 2.100 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 24.00 | 24.00 | 0.00713 | 42.09 | 0.01078 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 221810.39 | 255081.94 | 813.88 | 16.298 | 18.743 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00731 | 42.80 | 0.01078 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 199600.10 | 229540.12 | 1136.48 | 14.666 | 16.866 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 24.00 | 24.00 | 0.00723 | 39.60 | 0.01078 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 254182.02 | 292309.32 | 932.65 | 18.676 | 21.478 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00727 | 42.64 | 0.01078 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 225483.84 | 259306.41 | 1283.85 | 16.568 | 19.053 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 24.00 | 24.00 | 0.00720 | 42.09 | 0.01078 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 26244.95 | 30181.69 | 96.30 | 1.928 | 2.218 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00729 | 42.80 | 0.01078 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 21083.86 | 24246.44 | 120.05 | 1.549 | 1.782 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 24.00 | 24.00 | 0.00724 | 40.08 | 0.01078 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 29308.00 | 33704.20 | 107.54 | 2.153 | 2.477 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00726 | 42.80 | 0.01078 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 25139.12 | 28909.98 | 143.14 | 1.847 | 2.124 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 24.00 | 24.00 | 0.00720 | 42.09 | 0.01078 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8499.26 | 9774.15 | 269.98 | 0.624 | 0.718 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 33.16 | 0.01077 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 80919.76 | 93057.73 | 2570.46 | 5.945 | 6.836 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 33.16 | 0.01077 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8528.33 | 9807.58 | 270.91 | 0.627 | 0.721 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 27.00 | 27.00 | 0.00707 | 41.83 | 0.01078 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 375609.67 | 431951.12 | 551.18 | 27.596 | 31.736 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00703 | 33.97 | 0.01077 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 26.70 | 0.00717 | 12.70 | 0.00915 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 24.49 | 0.00915 | 12.70 | 0.00915 | 1.078 | 0.00 | |
CORE_MID | 105005.47 | 131256.84 | 52.58 | 7.457 | 10.778 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 10.778 | 0.00 |
CORE_TOP | 33703.49 | 42129.36 | 16.88 | 2.415 | 3.019 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 25.96 | 32.45 | 0.10 | 0.002 | 0.135 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00908 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 378.12 | 472.64 | 2.34 | 0.028 | 0.087 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00856 | 12.70 | 0.00915 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 2210.10 | 2762.62 | 8.81 | 0.158 | 0.197 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00833 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 0.00 | 0.000 | 0.087 | 00:10:00 | 15.60 | 21.49 | 0.00915 | 12.70 | 0.00915 | 0.087 | 0.00 | |
PERIMETER_MID_ZN_3 | 73589.59 | 91986.98 | 293.50 | 5.318 | 6.647 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00813 | 12.70 | 0.00915 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 49961.43 | 62451.79 | 309.21 | 3.612 | 4.515 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00812 | 12.70 | 0.00915 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 74638.89 | 93298.61 | 297.68 | 5.394 | 6.743 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00812 | 12.70 | 0.00915 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 41718.29 | 52147.87 | 258.19 | 3.010 | 3.762 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00817 | 12.70 | 0.00915 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 10457.97 | 13072.46 | 41.71 | 0.758 | 0.947 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00807 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 6983.67 | 8729.59 | 43.22 | 0.506 | 0.633 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00807 | 12.70 | 0.00915 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 10553.41 | 13191.77 | 42.09 | 0.765 | 0.956 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00807 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 6208.54 | 7760.67 | 38.42 | 0.450 | 0.562 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00809 | 12.70 | 0.00915 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 12.70 | 0.00915 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 25.51 | 0.00700 | 12.70 | 0.00915 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 24.59 | 0.00850 | 12.70 | 0.00915 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 12.70 | 0.00915 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 13.99 | 13.99 | 1.58 | 1.58 | 13.9881 | 4.6338 | 13.9881 | 0.3313 | 0.3000 |
VAV_MID WITH REHEAT | 131.30 | 131.30 | 32.45 | 32.45 | 131.3038 | 44.5877 | 131.3038 | 0.3396 | 0.3000 |
VAV_TOP WITH REHEAT | 16.72 | 16.72 | 6.12 | 6.12 | 16.7187 | 6.1171 | 16.7187 | 0.3659 | 0.3000 |
CAV_BAS | 7.70 | 7.70 | 1.20 | 1.20 | 7.6981 | 2.3094 | 7.6981 | 0.3000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 31.74 | 31.74 | 0.34 | 0.34 | 31.7360 | 15.8679 | 31.7360 | 0.5000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.72 | 0.72 | 0.02 | 0.02 | 0.7181 | 0.7181 | 0.7181 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 6.84 | 6.84 | 0.16 | 0.16 | 6.8364 | 6.8364 | 6.8364 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.72 | 0.72 | 0.02 | 0.02 | 0.7206 | 0.7206 | 0.7206 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 165437.441 | 165437.441 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 165437.44 | 17917.06 | 1.077825 | 18.57 | 5.11 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 1588901.289 | 1588901.289 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 1588901.29 | 181737.73 | 10.778248 | 18.37 | 5.01 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 131256.84 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 186454.971 | 186454.971 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 186454.97 | 50536.82 | 3.019121 | 18.47 | 5.06 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 42129.36 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 40436.220 | 40436.220 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40436.22 | 2249.81 | 0.135332 | 18.57 | 5.11 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00907874 | 58.5629 | 32.45 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 35665.959 | 35665.959 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35665.96 | 1452.02 | 0.087213 | 18.55 | 5.10 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00856488 | 55.2929 | 472.64 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 47265.625 | 47265.625 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 47265.62 | 3300.85 | 0.197191 | 18.47 | 5.06 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00832630 | 53.7726 | 2762.62 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 45371.854 | 45371.854 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 45371.85 | 1449.77 | 0.087213 | 18.57 | 5.11 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 406874.428 | 406874.428 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 406874.43 | 110995.63 | 6.646900 | 18.51 | 5.08 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00812633 | 52.4975 | 91986.98 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 366148.353 | 366148.353 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 366148.35 | 75401.95 | 4.515199 | 18.50 | 5.08 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00811733 | 52.4402 | 62451.79 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 466258.918 | 466258.918 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 466258.92 | 112597.41 | 6.742750 | 18.51 | 5.08 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00812298 | 52.4762 | 93298.61 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 413568.791 | 413568.791 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 413568.79 | 62818.74 | 3.762241 | 18.51 | 5.08 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00816666 | 52.7545 | 52147.87 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 48054.406 | 48054.406 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 48054.41 | 15789.32 | 0.947269 | 18.53 | 5.09 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00807212 | 52.1521 | 13072.46 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 38604.573 | 38604.573 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38604.57 | 10546.65 | 0.632737 | 18.53 | 5.09 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00806973 | 52.1369 | 8729.59 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 53662.782 | 53662.782 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 53662.78 | 15934.59 | 0.955984 | 18.53 | 5.09 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00807105 | 52.1453 | 13191.77 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 46028.990 | 46028.990 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 46028.99 | 9368.05 | 0.562035 | 18.53 | 5.09 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00808866 | 52.2575 | 7760.67 | 0.00 | -999.00 | -999.00 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 301537.351 | -999.000 | 13.988063 | 0.01077022 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 301537.35 | 271620.11 | 13.988063 | 26.73 | 16.74 | 0.00779128 | 11.11 | 9.81 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 14.5159 | 24.00 | 0.00728346 | 39.2677 | 165550.65 | 0.00 | 301926.57 | 288973.61 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_BOT WITH REHEAT | 16678.517 | 16678.517 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16678.52 | 16678.52 | 4.196419 | 9.60 | 9.60 | 0.00908032 | 12.89 | 11.63 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 48.3865 | 22.79 | 0.00908149 | 52.5208 | 2614.17 | 0.00 | -999.00 | -999.00 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2892544.007 | -999.000 | 131.303828 | 0.10331497 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 2892544.01 | 2582437.79 | 131.303828 | 26.91 | 16.87 | 0.00787111 | 11.11 | 9.81 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 15.4649 | 24.00 | 0.00733862 | 39.5623 | 1553961.66 | 0.00 | 2896275.31 | 2742306.36 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_MID WITH REHEAT | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 39.391148 | 16.30 | 13.68 | 0.00868168 | 12.89 | 11.63 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 51.5497 | 19.84 | 0.00817653 | 56.7435 | 122498.56 | 0.00 | -999.00 | -999.00 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 346628.726 | -999.000 | 16.718696 | 0.01238077 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 346628.73 | 314974.11 | 16.718696 | 26.28 | 16.51 | 0.00770437 | 11.12 | 9.81 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 12.1451 | 24.00 | 0.00727873 | 39.2432 | 197776.32 | 0.00 | 347083.77 | 336156.91 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_TOP WITH REHEAT | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 22:40:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 5.015609 | 17.64 | 14.03 | 0.00849753 | 12.89 | 11.63 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 40.4836 | 19.04 | 0.00807823 | 58.9195 | 12305.70 | 0.00 | -999.00 | -999.00 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 156030.157 | -999.000 | 7.698119 | 0.00557304 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 156030.16 | 137840.24 | 7.698119 | 25.86 | 16.53 | 0.00790311 | 11.10 | 9.80 | 0.00700000 | 35.62 | 0.01076950 | 21.86 | 15.5903 | 24.00 | 0.00737369 | 39.7485 | 91899.18 | 0.00 | 160794.18 | 151215.93 |
CAV_BAS HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | CAV_BAS | 71253.099 | 71253.099 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 71253.10 | 71253.10 | 7.698119 | 1.98 | 1.98 | 0.00748051 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 15.5903 | 26.70 | 0.00717152 | 32.9331 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 462985.216 | -999.000 | 31.736043 | 0.01653676 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 462985.22 | 458456.73 | 31.736043 | 27.17 | 16.28 | 0.00707267 | 15.04 | 11.51 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 1.0663 | 27.00 | 0.00703265 | 31.7416 | 375160.89 | 0.00 | 479119.12 | 479119.12 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 553461.528 | 553461.528 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 553461.53 | 553461.53 | 31.736043 | 0.14 | 0.14 | 0.00702296 | 29.11 | 17.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 1.0663 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER BOT | 16777.010 | 12087.500 | 0.718050 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 8388.50 | 8224.55 | 0.478700 | 27.32 | 16.40 | 0.00714785 | 14.49 | 11.28 | 0.00700000 | 41.70 | 0.01077992 | 23.56 | 3.2656 | 27.00 | 0.00706677 | 31.8924 | 8472.33 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER BOT | 16777.007 | 16777.007 | 0.718053 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8388.50 | 8388.50 | 0.359027 | 0.28 | 0.28 | 0.00704688 | 29.11 | 17.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 4.3541 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | AIRLOOP DATACENTER BOT | 16777.007 | 16777.007 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 16777.01 | 16777.01 | 0.718053 | 0.28 | 0.28 | 0.00704688 | 29.11 | 17.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 2.1770 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER MID | 159653.400 | 115047.837 | 6.836440 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 79826.70 | 78189.50 | 4.557627 | 27.33 | 16.41 | 0.00715542 | 14.49 | 11.28 | 0.00700000 | 41.57 | 0.01077970 | 23.53 | 3.4299 | 27.00 | 0.00707023 | 31.9079 | 80558.05 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER MID | 159653.396 | 159653.396 | 6.836442 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 79826.70 | 79826.70 | 3.418221 | 0.29 | 0.29 | 0.00705068 | 29.11 | 17.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 4.5732 | 25.51 | 0.00700147 | 34.5121 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | AIRLOOP DATACENTER MID | 159653.396 | 159653.396 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 159653.40 | 159653.40 | 6.836442 | 0.29 | 0.29 | 0.00705068 | 29.11 | 17.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 2.2866 | 25.51 | 0.00700147 | 34.5121 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER TOP | 16836.750 | 12130.373 | 0.720590 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 8418.38 | 8254.92 | 0.480393 | 27.32 | 16.40 | 0.00714690 | 14.49 | 11.28 | 0.00700000 | 41.96 | 0.01078037 | 23.63 | 3.2541 | 27.00 | 0.00706632 | 31.8903 | 8527.99 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER TOP | 16836.751 | 16836.751 | 0.720586 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8418.38 | 8418.38 | 0.360293 | 0.28 | 0.28 | 0.00851686 | 29.11 | 17.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 4.3388 | 24.59 | 0.00850275 | 44.1521 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | AIRLOOP DATACENTER TOP | 16836.751 | 16836.751 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 16836.75 | 16836.75 | 0.720586 | 0.28 | 0.28 | 0.00851686 | 29.11 | 17.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 2.1694 | 24.59 | 0.00850275 | 44.1521 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 165437.441 | 165437.441 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 165437.44 | 17917.06 | 1.0000 | 1.29726454 | 1.077825 | 18.57 | 5.11 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 165437.44 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 1588901.289 | 1588901.289 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 1588901.29 | 181737.73 | 1.0000 | 12.97264538 | 10.778248 | 18.37 | 5.01 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1588901.29 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.72 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 131256.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 186454.971 | 186454.971 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 186454.97 | 50536.82 | 1.0000 | 3.63379915 | 3.019121 | 18.47 | 5.06 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 186454.97 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 42129.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 40436.220 | 40436.220 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 40436.22 | 2249.81 | 1.0000 | 0.16288451 | 0.135332 | 18.57 | 5.11 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40436.22 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00907874 | 21.00 | 0.00907874 | 58.5629 | 32.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 35665.959 | 35665.959 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 35665.96 | 1452.02 | 1.0000 | 0.10496897 | 0.087213 | 18.55 | 5.10 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35665.96 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.97 | 0.00856488 | 21.00 | 0.00856488 | 55.2929 | 472.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 47265.625 | 47265.625 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 47265.62 | 3300.85 | 1.0000 | 0.23733792 | 0.197191 | 18.47 | 5.06 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 47265.62 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00832630 | 21.00 | 0.00832630 | 53.7726 | 2762.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 45371.854 | 45371.854 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 45371.85 | 1449.77 | 1.0000 | 0.10496897 | 0.087213 | 18.57 | 5.11 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 45371.85 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 406874.428 | 406874.428 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 406874.43 | 110995.63 | 1.0000 | 8.00017549 | 6.646900 | 18.51 | 5.08 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 406874.43 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00812633 | 21.00 | 0.00812633 | 52.4975 | 91986.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 366148.353 | 366148.353 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 366148.35 | 75401.95 | 1.0000 | 5.43447029 | 4.515199 | 18.50 | 5.08 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 366148.35 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00811733 | 21.00 | 0.00811733 | 52.4402 | 62451.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 466258.918 | 466258.918 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 466258.92 | 112597.41 | 1.0000 | 8.11553973 | 6.742750 | 18.51 | 5.08 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 466258.92 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00812298 | 21.00 | 0.00812298 | 52.4762 | 93298.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 413568.791 | 413568.791 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 413568.79 | 62818.74 | 1.0000 | 4.52821418 | 3.762241 | 18.51 | 5.08 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 413568.79 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00816666 | 21.00 | 0.00816666 | 52.7545 | 52147.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 48054.406 | 48054.406 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 48054.41 | 15789.32 | 1.0000 | 1.14012860 | 0.947269 | 18.53 | 5.09 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48054.41 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.95 | 0.00807212 | 21.00 | 0.00807212 | 52.1521 | 13072.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 38604.573 | 38604.573 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 38604.57 | 10546.65 | 1.0000 | 0.76155908 | 0.632737 | 18.53 | 5.09 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38604.57 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.95 | 0.00806973 | 21.00 | 0.00806973 | 52.1369 | 8729.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 53662.782 | 53662.782 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 53662.78 | 15934.59 | 1.0000 | 1.15061764 | 0.955984 | 18.53 | 5.09 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 53662.78 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.95 | 0.00807105 | 21.00 | 0.00807105 | 52.1453 | 13191.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 46028.990 | 46028.990 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 46028.99 | 9368.05 | 1.0000 | 0.67646249 | 0.562035 | 18.53 | 5.09 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 46028.99 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.95 | 0.00808866 | 21.00 | 0.00808866 | 52.2575 | 7760.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 301537.351 | -999.000 | 13.988063 | 0.01077022 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3236 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 13.988063 | 16.83596246 | 4197.9300 | 999.8980 | 148.56059894 | 13.34 | 6.67 | 6.67 | 4159725.46 | 7.2490 | 7.248972 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 301537.35 | 271620.11 | 1.0000 | 16.83596246 | 13.988063 | 26.73 | 16.74 | 0.00779128 | 46729.9 | 11.11 | 9.81 | 0.00700000 | 28819.6 | 10.76911682 | 6.67 | 13.34 | 6.67 | 30449.912 | 271087.44 | 42.80 | 0.01078182 | 23.86 | 2.03050000 | 14.5159 | 24.00 | 0.00728346 | 24.00 | 0.00728346 | 39.2677 | 165550.65 | 0.00 | 301926.57 | 288973.61 | 16.83596246 | 26.73 | 16.74 | 0.00779128 | 46729.9 | 9.89 | 9.79 | 0.00748589 | 28796.4 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16678.517 | 16678.517 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 13.988063 | 16.83596246 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16678.52 | 16678.52 | 1.0000 | 5.05078874 | 4.196419 | 9.60 | 9.60 | 0.00908032 | 32520.6 | 12.89 | 11.63 | 0.00800000 | 33150.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16678.52 | 12.70 | 0.00915345 | 12.70 | 2.03050000 | 48.3865 | 6.70 | 0.00901176 | 22.79 | 0.00908149 | 52.5208 | 2614.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2892544.007 | -999.000 | 131.303828 | 0.10331497 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4720 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 131.303828 | 158.03662790 | 4197.9300 | 999.8980 | 148.56059894 | 13.34 | 6.67 | 6.67 | 4159725.46 | 69.5369 | 69.536897 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 2892544.01 | 2582437.79 | 1.0000 | 158.03662790 | 131.303828 | 26.91 | 16.87 | 0.00787111 | 47115.2 | 11.11 | 9.81 | 0.00700000 | 28812.2 | 103.30443068 | 6.67 | 13.34 | 6.67 | 287043.713 | 2605500.29 | 42.80 | 0.01078182 | 23.86 | 20.30600000 | 15.4649 | 24.00 | 0.00733862 | 24.00 | 0.00733862 | 39.5623 | 1553961.66 | 0.00 | 2896275.31 | 2742306.36 | 158.03662790 | 26.91 | 16.87 | 0.00787111 | 47115.2 | 9.89 | 9.79 | 0.00748439 | 28788.5 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 131.303828 | 158.03662790 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 47.41098837 | 39.391148 | 16.30 | 13.68 | 0.00868168 | 38356.1 | 12.89 | 11.63 | 0.00800000 | 33150.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 20.30600000 | 51.5497 | 20.13 | 0.00817974 | 19.84 | 0.00817653 | 56.7435 | 122498.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 346628.726 | -999.000 | 16.718696 | 0.01238077 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1620 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 16.718696 | 20.12253889 | 4197.9300 | 999.8980 | 148.56059894 | 13.34 | 6.67 | 6.67 | 4159725.46 | 8.3330 | 8.332971 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 346628.73 | 314974.11 | 1.0000 | 20.12253889 | 16.718696 | 26.28 | 16.51 | 0.00770437 | 46054.7 | 11.12 | 9.81 | 0.00700000 | 28828.8 | 12.37951198 | 6.67 | 13.34 | 6.67 | 36202.543 | 310426.18 | 42.80 | 0.01078182 | 23.86 | 2.03050000 | 12.1451 | 24.00 | 0.00727873 | 24.00 | 0.00727873 | 39.2432 | 197776.32 | 0.00 | 347083.77 | 336156.91 | 20.12253889 | 26.28 | 16.51 | 0.00770437 | 46054.7 | 9.89 | 9.80 | 0.00748883 | 28806.2 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 16.718696 | 20.12253889 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 22:40:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 6.03676167 | 5.015609 | 17.64 | 14.03 | 0.00849753 | 39255.7 | 12.89 | 11.63 | 0.00800000 | 33150.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 2.03050000 | 40.4836 | 21.00 | 0.00805136 | 19.04 | 0.00807823 | 58.9195 | 12305.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 156030.157 | -999.000 | 7.698119 | 0.00557304 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5315 | 1004.8586 | 1.2036 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 7.698119 | 9.26541693 | 4197.9300 | 999.8980 | 148.56059894 | 13.34 | 6.67 | 6.67 | 4159725.46 | 3.7510 | 3.750972 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 156030.16 | 137840.24 | 1.0000 | 9.26541693 | 7.698119 | 25.86 | 16.53 | 0.00790311 | 46134.3 | 11.10 | 9.80 | 0.00700000 | 28802.6 | 5.57246719 | 6.67 | 13.34 | 6.67 | 16918.779 | 139111.38 | 35.62 | 0.01076950 | 21.86 | 1.20015641 | 15.5903 | 24.06 | 0.00737369 | 24.00 | 0.00737369 | 39.7485 | 91899.18 | 0.00 | 160794.18 | 151215.93 | 9.26541693 | 25.86 | 16.54 | 0.00790311 | 46134.3 | 9.86 | 9.79 | 0.00749277 | 28780.1 | |
CAV_BAS HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 71253.099 | 71253.099 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 7.698119 | 9.26541693 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 71253.10 | 71253.10 | 1.0000 | 9.26541693 | 7.698119 | 1.98 | 1.98 | 0.00748051 | 20725.4 | 32.11 | 18.73 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 71253.10 | 12.70 | 0.00915345 | 12.70 | 1.20015641 | 15.5903 | 0.00 | 0.00717152 | 26.70 | 0.00717152 | 32.9331 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 462985.216 | -999.000 | 31.736043 | 0.01653676 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9877 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 31.736043 | 38.19734265 | 4197.9300 | 999.8980 | 148.56059894 | 13.34 | 6.67 | 6.67 | 4159725.46 | 11.1302 | 11.130187 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 462985.22 | 458456.73 | 1.0000 | 38.19734265 | 31.736043 | 27.17 | 16.28 | 0.00707267 | 45343.7 | 15.04 | 11.51 | 0.00700000 | 32816.7 | 16.53507225 | 6.67 | 13.34 | 6.67 | 32947.051 | 430038.17 | 42.80 | 0.01078182 | 23.86 | 0.33839277 | 1.0663 | 27.00 | 0.00703265 | 27.00 | 0.00703265 | 31.7416 | 375160.89 | 0.00 | 479119.12 | 479119.12 | 38.19734265 | 27.17 | 16.28 | 0.00707267 | 45343.7 | 14.85 | 11.51 | 0.00707267 | 32800.4 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 553461.528 | 553461.528 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 31.736043 | 38.19734265 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 553461.53 | 553461.53 | 1.0000 | 38.19734265 | 31.736043 | 0.14 | 0.14 | 0.00702296 | 17701.8 | 29.11 | 17.73 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 553461.53 | 12.70 | 0.00915345 | 12.70 | 0.33839277 | 1.0663 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16777.010 | 12087.500 | 0.718050 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.1275 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.718053 | 0.86424554 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | Sensible | 8388.50 | 8224.55 | 1.0000 | 0.57616092 | 0.478700 | 27.32 | 16.40 | 0.00714785 | 45691.4 | 14.49 | 11.28 | 0.00700000 | 32250.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8388.50 | 41.70 | 0.01077992 | 23.56 | 0.01563234 | 3.2656 | 27.00 | 0.00706677 | 27.00 | 0.00706677 | 31.8924 | 8472.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 16777.007 | 16777.007 | 0.718053 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.718053 | 0.86424554 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 8388.50 | 8388.50 | 1.0000 | 0.43212277 | 0.359027 | 0.28 | 0.28 | 0.00704688 | 17905.3 | 29.11 | 17.73 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8388.50 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 4.3541 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16777.007 | 16777.007 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.718053 | 0.86424554 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 16777.01 | 16777.01 | 1.0000 | 0.86424554 | 0.718053 | 0.28 | 0.28 | 0.00704688 | 17905.3 | 29.11 | 17.73 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16777.01 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 2.1770 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 159653.400 | 115047.837 | 6.836440 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.1416 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 6.836442 | 8.22830670 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | Sensible | 79826.70 | 78189.50 | 1.0000 | 5.48553658 | 4.557627 | 27.33 | 16.41 | 0.00715542 | 45724.6 | 14.49 | 11.28 | 0.00700000 | 32250.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 79826.70 | 41.57 | 0.01077970 | 23.53 | 0.15632344 | 3.4299 | 27.00 | 0.00707023 | 27.00 | 0.00707023 | 31.9079 | 80558.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 159653.396 | 159653.396 | 6.836442 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 6.836442 | 8.22830670 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 79826.70 | 79826.70 | 1.0000 | 4.11415335 | 3.418221 | 0.29 | 0.29 | 0.00705068 | 17928.9 | 29.11 | 17.73 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 79826.70 | 12.70 | 0.00915345 | 12.70 | 0.15632344 | 4.5732 | 0.00 | 0.00700147 | 25.51 | 0.00700147 | 34.5121 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 159653.396 | 159653.396 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 6.836442 | 8.22830670 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 159653.40 | 159653.40 | 1.0000 | 8.22830670 | 6.836442 | 0.29 | 0.29 | 0.00705068 | 17928.9 | 29.11 | 17.73 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 159653.40 | 12.70 | 0.00915345 | 12.70 | 0.15632344 | 2.2866 | 0.00 | 0.00700147 | 25.51 | 0.00700147 | 34.5121 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16836.750 | 12130.373 | 0.720590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.1257 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.720586 | 0.86729391 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | Sensible | 8418.38 | 8254.92 | 1.0000 | 0.57819901 | 0.480393 | 27.32 | 16.40 | 0.00714690 | 45692.6 | 14.49 | 11.28 | 0.00700000 | 32250.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8418.38 | 41.96 | 0.01078037 | 23.63 | 0.01563234 | 3.2541 | 27.00 | 0.00706632 | 27.00 | 0.00706632 | 31.8903 | 8527.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 16836.751 | 16836.751 | 0.720586 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.720586 | 0.86729391 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 8418.38 | 8418.38 | 1.0000 | 0.43364696 | 0.360293 | 0.28 | 0.28 | 0.00851686 | 21581.4 | 29.11 | 17.73 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8418.38 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 4.3388 | 0.00 | 0.00850275 | 24.59 | 0.00850275 | 44.1521 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16836.751 | 16836.751 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.720586 | 0.86729391 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 16836.75 | 16836.75 | 1.0000 | 0.86729391 | 0.720586 | 0.28 | 0.28 | 0.00851686 | 21581.4 | 29.11 | 17.73 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16836.75 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 2.1694 | 0.00 | 0.00850275 | 24.59 | 0.00850275 | 44.1521 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5725.33 | 199.50 | 199.50 |
CORE_BOTTOM | 5808.00 | 7.33 | 3.00 |
CORE_MID | 5236.67 | 170.00 | 0.00 |
CORE_TOP | 4675.17 | 782.00 | 13.50 |
PERIMETER_BOT_ZN_3 | 4833.17 | 891.17 | 214.67 |
PERIMETER_BOT_ZN_2 | 4557.67 | 1248.00 | 277.00 |
PERIMETER_BOT_ZN_1 | 4941.50 | 982.00 | 337.50 |
PERIMETER_BOT_ZN_4 | 5178.50 | 965.00 | 548.33 |
PERIMETER_MID_ZN_3 | 4158.67 | 1670.00 | 288.50 |
PERIMETER_MID_ZN_2 | 3405.67 | 1622.83 | 358.17 |
PERIMETER_MID_ZN_1 | 4652.00 | 1358.17 | 387.17 |
PERIMETER_MID_ZN_4 | 4019.33 | 1824.50 | 326.33 |
PERIMETER_TOP_ZN_3 | 3916.17 | 2023.00 | 355.83 |
PERIMETER_TOP_ZN_2 | 4091.17 | 1889.33 | 417.67 |
PERIMETER_TOP_ZN_1 | 4386.83 | 1670.00 | 423.83 |
PERIMETER_TOP_ZN_4 | 3823.50 | 2155.33 | 426.17 |
DATACENTER_BOT_ZN_6 | 5943.00 | 2704.50 | 2704.50 |
DATACENTER_MID_ZN_6 | 5943.00 | 971.00 | 971.00 |
DATACENTER_TOP_ZN_6 | 5943.00 | 1651.33 | 1651.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 86.33 | 0.00 | 0.33 |
CORE_BOTTOM | 0.00 | 1.33 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 55.00 | 0.00 | 45.17 |
PERIMETER_BOT_ZN_2 | 0.00 | 63.83 | 0.00 | 62.67 |
PERIMETER_BOT_ZN_1 | 0.00 | 81.00 | 0.00 | 76.50 |
PERIMETER_BOT_ZN_4 | 0.00 | 128.67 | 0.00 | 71.67 |
PERIMETER_MID_ZN_3 | 0.00 | 53.50 | 0.00 | 42.83 |
PERIMETER_MID_ZN_2 | 0.00 | 69.17 | 0.00 | 65.83 |
PERIMETER_MID_ZN_1 | 0.00 | 74.67 | 0.00 | 68.83 |
PERIMETER_MID_ZN_4 | 0.00 | 61.00 | 0.00 | 45.67 |
PERIMETER_TOP_ZN_3 | 0.00 | 63.33 | 0.00 | 48.67 |
PERIMETER_TOP_ZN_2 | 0.00 | 80.50 | 0.00 | 70.67 |
PERIMETER_TOP_ZN_1 | 0.00 | 80.83 | 0.00 | 70.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 71.50 | 0.00 | 51.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 13.50 | 0.00 | 1.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 379.50 | 0.00 | 210.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.29 | 149.60 | 6779.02 | 0.517 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.04 | 134.35 | 6849.35 | 0.419 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.04 | 134.35 | 6849.35 | 0.399 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.04 | 134.35 | 6849.35 | 0.396 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.91 | 16.87 | 860.00 | 0.743 | 0.037 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.45 | 10.87 | 554.22 | 0.928 | 0.038 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.91 | 16.87 | 860.02 | 0.893 | 0.037 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.45 | 10.87 | 554.22 | 1.200 | 0.038 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.91 | 16.87 | 860.00 | 0.808 | 0.087 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.88 | 10.87 | 554.22 | 1.040 | 0.094 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.91 | 16.87 | 860.02 | 0.978 | 0.087 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.45 | 10.87 | 554.22 | 1.160 | 0.090 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.91 | 16.87 | 860.00 | 0.792 | 0.108 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.45 | 10.87 | 554.22 | 0.992 | 0.111 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.91 | 16.87 | 860.02 | 0.934 | 0.108 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.45 | 10.87 | 554.22 | 1.103 | 0.111 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.589 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.589 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.589 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.28 | 42.18 | 1911.37 | 0.666 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.29 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.04 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.04 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.04 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.91 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.91 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.91 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.88 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.91 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.91 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.91 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.575 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.575 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.575 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.28 | 42.18 | 1911.37 | 0.647 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.29 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.04 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.04 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.04 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.91 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.91 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.91 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.88 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.91 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.91 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.91 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.80 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.28 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1015.76 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 20834923.00 | 0.00 | 20834923.00 | 0.00 | 20834923.00 | 37848132.68 | 4099.95 | 4660.05 | 0.00 | 599.93 |
CORE_BOTTOM | 19487223.81 | 0.00 | 19487223.81 | 0.00 | 19487223.81 | 33990283.35 | 8697.29 | 29.25 | 33.46 | 948.96 |
CORE_MID | 0.17E+09 | 0.00 | 0.17E+09 | 0.00 | 0.17E+09 | 0.34E+09 | 8747.11 | 0.49 | 12.40 | 569.44 |
CORE_TOP | 17259495.96 | 0.00 | 17259495.96 | 0.00 | 17259495.96 | 33990283.35 | 8754.04 | 0.33 | 5.63 | 533.38 |
PERIMETER_BOT_ZN_3 | 4391802.49 | 0.00 | 4391802.49 | 322129.40 | 4713931.89 | 4267819.30 | 3035.46 | 54.62 | 5669.92 | 948.96 |
PERIMETER_BOT_ZN_2 | 3591440.27 | 0.00 | 3591440.27 | 214752.79 | 3806193.06 | 2750345.05 | 2599.66 | 18.55 | 6141.79 | 948.96 |
PERIMETER_BOT_ZN_1 | 5254288.65 | 0.00 | 5254288.65 | 322129.40 | 5576418.05 | 4267912.63 | 2605.79 | 19.46 | 6134.75 | 948.96 |
PERIMETER_BOT_ZN_4 | 4635945.83 | 0.00 | 4635945.83 | 214752.79 | 4850698.62 | 2750345.05 | 2555.49 | 0.00 | 6204.51 | 948.96 |
PERIMETER_MID_ZN_3 | 44549533.07 | 0.00 | 44549533.07 | 755463.31 | 45304996.38 | 42678193.03 | 3311.30 | 70.73 | 5377.97 | 569.44 |
PERIMETER_MID_ZN_2 | 37441271.42 | 0.00 | 37441271.42 | 503641.86 | 37944913.29 | 27503450.52 | 3078.76 | 4.45 | 5676.80 | 1478.44 |
PERIMETER_MID_ZN_1 | 53647530.11 | 0.00 | 53647530.11 | 755463.31 | 54402993.42 | 42679126.28 | 3090.49 | 0.97 | 5668.53 | 569.44 |
PERIMETER_MID_ZN_4 | 41669801.21 | 0.00 | 41669801.21 | 503641.86 | 42173443.07 | 27503450.52 | 3074.62 | 0.10 | 5685.27 | 569.44 |
PERIMETER_TOP_ZN_3 | 4348041.88 | 0.00 | 4348041.88 | 937962.89 | 5286004.76 | 4267819.30 | 3161.51 | 26.53 | 5571.96 | 533.38 |
PERIMETER_TOP_ZN_2 | 3504614.49 | 0.00 | 3504614.49 | 625308.16 | 4129922.65 | 2750345.05 | 3132.79 | 0.73 | 5626.48 | 533.38 |
PERIMETER_TOP_ZN_1 | 5100795.58 | 0.00 | 5100795.58 | 937962.89 | 6038758.47 | 4267912.63 | 3134.29 | 4.49 | 5621.22 | 533.38 |
PERIMETER_TOP_ZN_4 | 3932389.35 | 0.00 | 3932389.35 | 625308.16 | 4557697.52 | 2750345.05 | 3125.78 | 0.46 | 5633.76 | 533.38 |
DATACENTER_BOT_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929815.99 | 0.00 | 4929815.99 | 0.00 | 4929815.99 | 4929815.99 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 10671692.10 | 0.00 | 10671692.10 | 0.00 | 10671692.10 | 10671554.30 | 0.00 | 8760.00 | 0.00 | 2817.00 |
Total Facility | 0.37E+10 | 0.00 | 0.37E+10 | 29382409.93 | 0.37E+10 | 0.50E+10 | 8760.00 | 8760.00 | 6524.08 | 3726.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9441 | 0.0000 | 0.9441 | 0.0000 | 0.9441 | 1.2002 | 1298.19 | 4644.81 | 0.00 |
CORE_BOTTOM | 0.7716 | 0.0000 | 0.7716 | 0.0000 | 0.7716 | 1.0778 | 5889.99 | 28.91 | 24.10 |
CORE_MID | 7.3445 | 0.0000 | 7.3445 | 0.0000 | 7.3445 | 10.7782 | 5935.37 | 0.32 | 7.31 |
CORE_TOP | 0.7299 | 0.0000 | 0.7299 | 0.0000 | 0.7299 | 1.0778 | 5939.27 | 0.25 | 3.48 |
PERIMETER_BOT_ZN_3 | 0.1716 | 0.0000 | 0.1716 | 0.0086 | 0.1802 | 0.1353 | 1148.07 | 54.13 | 4740.80 |
PERIMETER_BOT_ZN_2 | 0.1383 | 0.0000 | 0.1383 | 0.0057 | 0.1440 | 0.0872 | 721.87 | 18.30 | 5202.83 |
PERIMETER_BOT_ZN_1 | 0.2066 | 0.0000 | 0.2066 | 0.0086 | 0.2151 | 0.1353 | 721.74 | 19.08 | 5202.18 |
PERIMETER_BOT_ZN_4 | 0.1787 | 0.0000 | 0.1787 | 0.0057 | 0.1844 | 0.0872 | 687.46 | 0.00 | 5255.54 |
PERIMETER_MID_ZN_3 | 1.8672 | 0.0000 | 1.8672 | 0.0201 | 1.8873 | 1.3533 | 1051.29 | 70.44 | 4821.27 |
PERIMETER_MID_ZN_2 | 1.5511 | 0.0000 | 1.5511 | 0.0141 | 1.5652 | 0.8721 | 829.03 | 1.92 | 4203.05 |
PERIMETER_MID_ZN_1 | 2.2630 | 0.0000 | 2.2630 | 0.0201 | 2.2830 | 1.3533 | 835.52 | 0.70 | 5106.77 |
PERIMETER_MID_ZN_4 | 1.7301 | 0.0000 | 1.7301 | 0.0134 | 1.7435 | 0.8721 | 827.06 | 0.03 | 5115.91 |
PERIMETER_TOP_ZN_3 | 0.1832 | 0.0000 | 0.1832 | 0.0249 | 0.2081 | 0.1353 | 871.45 | 26.22 | 5045.32 |
PERIMETER_TOP_ZN_2 | 0.1479 | 0.0000 | 0.1479 | 0.0166 | 0.1645 | 0.0872 | 845.64 | 0.27 | 5097.09 |
PERIMETER_TOP_ZN_1 | 0.2162 | 0.0000 | 0.2162 | 0.0249 | 0.2411 | 0.1353 | 846.29 | 3.44 | 5093.27 |
PERIMETER_TOP_ZN_4 | 0.1647 | 0.0000 | 0.1647 | 0.0166 | 0.1813 | 0.0872 | 841.41 | 0.37 | 5101.22 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1563 | 0.00 | 5943.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.3384 | 0.0000 | 0.3384 | 0.0000 | 0.3384 | 0.3384 | 0.00 | 5943.00 | 0.00 |
Total Facility | 153.3439 | 0.0000 | 153.3439 | 0.7874 | 154.1313 | 158.4706 | 5943.00 | 5943.00 | 5397.96 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 54122243.23 | 0.00 | 54122243.23 | 48026705.38 | 2571.80 | 0.83 | 6187.37 | 948.96 |
VAV_MID WITH REHEAT | 0.51E+09 | 0.00 | 0.51E+09 | 0.48E+09 | 3088.76 | 0.81 | 5670.44 | 569.44 |
VAV_TOP WITH REHEAT | 49464331.01 | 0.00 | 49464331.01 | 48026705.38 | 3135.77 | 0.94 | 5623.29 | 533.38 |
CAV_BAS | 30180599.07 | 0.00 | 30180599.07 | 37848132.68 | 4078.72 | 1.25 | 4680.03 | 599.93 |
AIRLOOP DATACENTER BASEMENT | 15459249.82 | 0.00 | 15459249.82 | 10671554.30 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER BOT | 714153.30 | 0.00 | 714153.30 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 7141532.97 | 0.00 | 7141532.97 | 4929815.99 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 714153.30 | 0.00 | 714153.30 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.1248 | 0.0000 | 2.1248 | 1.5229 | 696.87 | 0.56 | 5245.57 |
VAV_MID WITH REHEAT | 21.3872 | 0.0000 | 21.3872 | 15.2292 | 835.10 | 0.43 | 5107.47 |
VAV_TOP WITH REHEAT | 2.0887 | 0.0000 | 2.0887 | 1.5229 | 848.06 | 0.64 | 5094.30 |
CAV_BAS | 1.3676 | 0.0000 | 1.3676 | 1.2002 | 1293.40 | 0.32 | 4649.28 |
AIRLOOP DATACENTER BASEMENT | 0.4902 | 0.0000 | 0.4902 | 0.3384 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER BOT | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2265 | 0.0000 | 0.2265 | 0.1563 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 87.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6117.35 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 145.45 | 0.00 | 0.00 | 0.00 | 0.00 | 5540.09 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 40.64 | 0.00 | 0.00 | 0.00 | 0.00 | 5594.98 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 5419.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.1254 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.4071 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 24.7829 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 24.8510 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 1.9910 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.4358 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6866 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4902 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2265 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1322 |
Defaulted Fields | 1274 |
Fields with Defaults | 3715 |
Autosized Fields | 288 |
Autosizable Fields | 452 |
Autocalculated Fields | 222 |
Autocalculatable Fields | 467 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 37491.57 | 315281.16 | 08-JAN-12:30 | 2659123.79 | 10-AUG-16:00 |
Electricity:Building | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 758.19 | 15076.70 | 01-JAN-00:10 | 42602.33 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 589.38 | 5907.35 | 01-JAN-00:10 | 43380.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5893.79 | 59073.32 | 01-JAN-00:10 | 433806.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 589.38 | 5907.33 | 01-JAN-00:10 | 43380.63 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 740.04 | 7417.49 | 01-JAN-00:10 | 54469.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 476.91 | 4780.12 | 01-JAN-00:10 | 35102.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 740.05 | 7417.62 | 01-JAN-00:10 | 54470.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 476.91 | 4780.09 | 01-JAN-00:10 | 35102.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7588.97 | 95364.66 | 01-JAN-00:10 | 387850.11 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1622.27 | 19890.94 | 01-JAN-00:10 | 85232.07 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:HVAC | 3862.43 | 31214.56 | 15-JAN-07:00 | 366883.73 | 16-AUG-14:10 |
ExteriorEquipment:Electricity | 2623.11 | 22123.82 | 01-JAN-00:10 | 235096.12 | 03-APR-07:20 |
Transformer:ExteriorEquipment:Electricity | 56.04 | 979.82 | 01-JAN-00:10 | 3543.78 | 03-APR-07:20 |
ElectricityPurchased:Facility | 37491.57 | 315281.16 | 08-JAN-12:30 | 2659123.79 | 10-AUG-16:00 |
ElectricityPurchased:Plant | 37491.57 | 315281.16 | 08-JAN-12:30 | 2659123.79 | 10-AUG-16:00 |
Cogeneration:ElectricityPurchased | 37491.57 | 315281.16 | 08-JAN-12:30 | 2659123.79 | 10-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 37491.57 | 315281.16 | 08-JAN-12:30 | 2659123.79 | 10-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 37491.57 | 315281.16 | 08-JAN-12:30 | 2659123.79 | 10-AUG-16:00 |
ElectricityNet:Plant | 37491.57 | 315281.16 | 08-JAN-12:30 | 2659123.79 | 10-AUG-16:00 |
Cogeneration:ElectricityNet | 37491.57 | 315281.16 | 08-JAN-12:30 | 2659123.79 | 10-AUG-16:00 |
General:Cogeneration:ElectricityNet | 37491.57 | 315281.16 | 08-JAN-12:30 | 2659123.79 | 10-AUG-16:00 |
Fans:Electricity | 3135.53 | 24113.44 | 01-JAN-06:50 | 318420.45 | 16-AUG-14:10 |
General:Fans:Electricity | 3135.53 | 24113.44 | 01-JAN-06:50 | 318420.45 | 16-AUG-14:10 |
Heating:Electricity | 3.90 | 0.00 | 01-JAN-00:10 | 30364.47 | 20-JAN-06:10 |
General:Heating:Electricity | 3.90 | 0.00 | 01-JAN-00:10 | 30364.47 | 20-JAN-06:10 |
Cooling:Electricity | 6973.06 | 6114.82 | 20-JAN-05:50 | 654821.53 | 10-AUG-16:00 |
General:Cooling:Electricity | 6973.06 | 6114.82 | 20-JAN-05:50 | 654821.53 | 10-AUG-16:00 |
ExteriorLights:Electricity | 1008.65 | 0.00 | 01-JAN-07:10 | 64082.80 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 1008.65 | 0.00 | 01-JAN-07:10 | 64082.80 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.31 | 1944.00 | 01-JAN-00:10 | 1944.00 | 01-JAN-00:10 |
Humidifier:Electricity | 0.11 | 0.00 | 01-JAN-00:10 | 2799.86 | 23-MAR-02:00 |
General:Humidifier:Electricity | 0.11 | 0.00 | 01-JAN-00:10 | 2799.86 | 23-MAR-02:00 |
Electricity:Plant | 9766.28 | 165.16 | 20-JAN-05:50 | 804552.05 | 10-AUG-16:00 |
WaterSystems:Electricity | 280.41 | 0.00 | 01-JAN-00:10 | 37718.15 | 12-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 280.41 | 0.00 | 01-JAN-00:10 | 37718.15 | 12-JAN-12:40 |
HeatRejection:Electricity | 1144.11 | 0.00 | 01-JAN-00:10 | 64095.10 | 30-APR-14:40 |
General:HeatRejection:Electricity | 1144.11 | 0.00 | 01-JAN-00:10 | 64095.10 | 30-APR-14:40 |
Pumps:Electricity | 2035.56 | 165.16 | 20-JAN-05:50 | 112104.97 | 18-JUL-05:10 |
General:Pumps:Electricity | 2035.56 | 165.16 | 20-JAN-05:50 | 112104.97 | 18-JUL-05:10 |
WIRED_LTG_ELECTRICITY | 157.66 | 0.00 | 01-JAN-00:10 | 13766.21 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 38118.85 | 93355.38 | 16-JAN-06:00 | 3772547.12 | 10-AUG-16:00 |
PlantLoopCoolingDemand:HVAC | 38118.85 | 93355.38 | 16-JAN-06:00 | 3772547.12 | 10-AUG-16:00 |
CoolingCoils:PlantLoopCoolingDemand | 38118.85 | 93355.38 | 16-JAN-06:00 | 3772547.12 | 10-AUG-16:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 38342.76 | 0.00 | 01-JAN-03:30 | 0.00 | 21-JUL-12:00 |
Water:HVAC | 0.04 | 0.00 | 01-JAN-00:10 | 0.00 | 23-MAR-02:00 |
Humidifier:Water | 0.04 | 0.00 | 01-JAN-00:10 | 0.00 | 23-MAR-02:00 |
General:Humidifier:Water | 0.04 | 0.00 | 01-JAN-00:10 | 0.00 | 23-MAR-02:00 |
MainsWater:Facility | 38342.76 | 0.00 | 01-JAN-03:30 | 0.00 | 21-JUL-12:00 |
MainsWater:HVAC | 0.04 | 0.00 | 01-JAN-00:10 | 0.00 | 23-MAR-02:00 |
Humidifier:MainsWater | 0.04 | 0.00 | 01-JAN-00:10 | 0.00 | 23-MAR-02:00 |
General:Humidifier:MainsWater | 0.04 | 0.00 | 01-JAN-00:10 | 0.00 | 23-MAR-02:00 |
Water:Plant | 38342.72 | 0.00 | 01-JAN-03:30 | 0.00 | 21-JUL-12:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 38342.72 | 0.00 | 01-JAN-03:30 | 0.00 | 21-JUL-12:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 36062.55 | 0.00 | 01-JAN-03:30 | 0.00 | 21-JUL-12:00 |
General:HeatRejection:Water | 36062.55 | 0.00 | 01-JAN-03:30 | 0.00 | 21-JUL-12:00 |
HeatRejection:MainsWater | 36062.55 | 0.00 | 01-JAN-03:30 | 0.00 | 21-JUL-12:00 |
General:HeatRejection:MainsWater | 36062.55 | 0.00 | 01-JAN-03:30 | 0.00 | 21-JUL-12:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 191657.57 | 277403.14 | 15-JAN-16:40 | 17958528.09 | 10-AUG-16:00 |
EnergyTransfer:Building | 28151.06 | 97692.84 | 15-JAN-07:20 | 3009516.78 | 18-DEC-06:40 |
EnergyTransfer:Zone:BASEMENT | 893.11 | 0.00 | 01-JAN-00:10 | 81026.76 | 26-DEC-06:10 |
Heating:EnergyTransfer | 667.60 | 0.00 | 01-JAN-00:10 | 2308446.28 | 28-JAN-06:40 |
Heating:EnergyTransfer:Zone:BASEMENT | 1.51 | 0.00 | 01-JAN-00:10 | 24111.10 | 29-JUL-16:10 |
General:Heating:EnergyTransfer | 667.60 | 0.00 | 01-JAN-00:10 | 2308446.28 | 28-JAN-06:40 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 1.51 | 0.00 | 01-JAN-00:10 | 24111.10 | 29-JUL-16:10 |
Cooling:EnergyTransfer | 27483.46 | 97504.35 | 15-JAN-07:30 | 2140885.75 | 16-AUG-14:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 891.61 | 0.00 | 01-JAN-00:10 | 81026.76 | 26-DEC-06:10 |
General:Cooling:EnergyTransfer | 27483.46 | 97504.35 | 15-JAN-07:30 | 2140885.75 | 16-AUG-14:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 891.61 | 0.00 | 01-JAN-00:10 | 81026.76 | 26-DEC-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 849.80 | 0.00 | 01-JAN-00:10 | 60136.40 | 13-NOV-14:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 849.80 | 0.00 | 01-JAN-00:10 | 60136.40 | 13-NOV-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 849.80 | 0.00 | 01-JAN-00:10 | 60136.40 | 13-NOV-14:10 |
EnergyTransfer:Zone:CORE_MID | 6607.72 | 0.00 | 01-JAN-00:10 | 505007.37 | 05-OCT-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 6607.72 | 0.00 | 01-JAN-00:10 | 505007.37 | 05-OCT-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 6607.72 | 0.00 | 01-JAN-00:10 | 505007.37 | 05-OCT-16:00 |
EnergyTransfer:Zone:CORE_TOP | 738.33 | 0.00 | 01-JAN-00:10 | 65258.66 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 738.33 | 0.00 | 01-JAN-00:10 | 65258.66 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 738.33 | 0.00 | 01-JAN-00:10 | 65258.66 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 187.67 | 0.00 | 01-JAN-00:10 | 19317.54 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 747.99 | 20-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 747.99 | 20-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 187.66 | 0.00 | 01-JAN-00:10 | 19317.54 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 187.66 | 0.00 | 01-JAN-00:10 | 19317.54 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 146.09 | 0.00 | 01-JAN-00:10 | 16721.52 | 21-JUL-10:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.08 | 0.00 | 01-JAN-00:10 | 1213.02 | 21-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.08 | 0.00 | 01-JAN-00:10 | 1213.02 | 21-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 146.00 | 0.00 | 01-JAN-00:10 | 16721.52 | 21-JUL-10:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 146.00 | 0.00 | 01-JAN-00:10 | 16721.52 | 21-JUL-10:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 225.77 | 0.00 | 01-JAN-00:10 | 23379.21 | 04-OCT-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.06 | 0.00 | 01-JAN-00:10 | 1607.67 | 02-JAN-06:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.06 | 0.00 | 01-JAN-00:10 | 1607.67 | 02-JAN-06:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 225.71 | 0.00 | 01-JAN-00:10 | 23379.21 | 04-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 225.71 | 0.00 | 01-JAN-00:10 | 23379.21 | 04-OCT-12:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 192.19 | 0.00 | 01-JAN-00:10 | 20321.45 | 10-AUG-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.03 | 0.00 | 01-JAN-00:10 | 1012.06 | 03-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.03 | 0.00 | 01-JAN-00:10 | 1012.06 | 03-JAN-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 192.17 | 0.00 | 01-JAN-00:10 | 20321.45 | 10-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 192.17 | 0.00 | 01-JAN-00:10 | 20321.45 | 10-AUG-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1640.61 | 0.00 | 01-JAN-00:10 | 190238.80 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.14 | 0.00 | 01-JAN-00:10 | 16988.18 | 20-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.14 | 0.00 | 01-JAN-00:10 | 16988.18 | 20-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1638.47 | 0.00 | 01-JAN-00:10 | 190238.80 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1638.47 | 0.00 | 01-JAN-00:10 | 190238.80 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1339.40 | 0.00 | 01-JAN-00:10 | 176778.64 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.99 | 0.00 | 01-JAN-00:10 | 16148.35 | 20-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.99 | 0.00 | 01-JAN-00:10 | 16148.35 | 20-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1336.41 | 0.00 | 01-JAN-00:10 | 176778.64 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1336.41 | 0.00 | 01-JAN-00:10 | 176778.64 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2017.81 | 0.00 | 01-JAN-00:10 | 231382.61 | 04-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.87 | 0.00 | 01-JAN-00:10 | 17459.49 | 20-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.87 | 0.00 | 01-JAN-00:10 | 17459.49 | 20-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2015.93 | 0.00 | 01-JAN-00:10 | 231382.61 | 04-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2015.93 | 0.00 | 01-JAN-00:10 | 231382.61 | 04-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1445.54 | 0.00 | 01-JAN-00:10 | 181418.73 | 09-JUN-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 3.47 | 0.00 | 01-JAN-00:10 | 16430.52 | 23-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 3.47 | 0.00 | 01-JAN-00:10 | 16430.52 | 23-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1442.07 | 0.00 | 01-JAN-00:10 | 181418.73 | 09-JUN-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1442.07 | 0.00 | 01-JAN-00:10 | 181418.73 | 09-JUN-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 177.79 | 0.00 | 01-JAN-00:10 | 21200.72 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.23 | 0.00 | 01-JAN-00:10 | 4439.96 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.23 | 0.00 | 01-JAN-00:10 | 4439.96 | 03-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 177.56 | 0.00 | 01-JAN-00:10 | 21200.72 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 177.56 | 0.00 | 01-JAN-00:10 | 21200.72 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 142.36 | 0.00 | 01-JAN-00:10 | 18058.97 | 21-JUL-10:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.14 | 0.00 | 01-JAN-00:10 | 2816.30 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.14 | 0.00 | 01-JAN-00:10 | 2816.30 | 03-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 142.22 | 0.00 | 01-JAN-00:10 | 18058.97 | 21-JUL-10:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 142.22 | 0.00 | 01-JAN-00:10 | 18058.97 | 21-JUL-10:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 213.78 | 0.00 | 01-JAN-00:10 | 24537.96 | 04-OCT-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.12 | 0.00 | 01-JAN-00:10 | 4172.79 | 20-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.12 | 0.00 | 01-JAN-00:10 | 4172.79 | 20-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 213.66 | 0.00 | 01-JAN-00:10 | 24537.96 | 04-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 213.66 | 0.00 | 01-JAN-00:10 | 24537.96 | 04-OCT-12:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 152.11 | 0.00 | 01-JAN-00:10 | 19410.15 | 09-JUN-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.08 | 0.00 | 01-JAN-00:10 | 2262.64 | 21-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.08 | 0.00 | 01-JAN-00:10 | 2262.64 | 21-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 152.04 | 0.00 | 01-JAN-00:10 | 19410.15 | 09-JUN-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 152.04 | 0.00 | 01-JAN-00:10 | 19410.15 | 09-JUN-15:30 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 159.28 | 0.00 | 01-JAN-00:10 | 78238.74 | 03-JAN-06:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 4.55 | 0.00 | 01-JAN-00:10 | 77798.73 | 21-JAN-06:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 4.55 | 0.00 | 01-JAN-00:10 | 77798.73 | 21-JAN-06:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 154.73 | 0.00 | 01-JAN-00:10 | 13742.21 | 05-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 154.73 | 0.00 | 01-JAN-00:10 | 13742.21 | 05-SEP-14:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1672.10 | 0.00 | 01-JAN-00:10 | 2019845.39 | 21-FEB-06:50 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 457.12 | 0.00 | 01-JAN-00:10 | 2019845.39 | 21-FEB-06:50 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 457.12 | 0.00 | 01-JAN-00:10 | 2019845.39 | 21-FEB-06:50 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1214.98 | 0.00 | 01-JAN-00:10 | 115329.73 | 16-AUG-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1214.98 | 0.00 | 01-JAN-00:10 | 115329.73 | 16-AUG-14:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 477.04 | 0.00 | 01-JAN-00:10 | 230312.68 | 13-DEC-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 193.21 | 0.00 | 01-JAN-00:10 | 230312.68 | 13-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 193.21 | 0.00 | 01-JAN-00:10 | 230312.68 | 13-DEC-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 283.83 | 0.00 | 01-JAN-00:10 | 45916.85 | 21-JUL-12:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 283.83 | 0.00 | 01-JAN-00:10 | 45916.85 | 21-JUL-12:10 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 145.51 | 1081.51 | 21-JAN-08:00 | 8065.92 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 145.51 | 1081.51 | 21-JAN-08:00 | 8065.92 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 145.51 | 1081.51 | 21-JAN-08:00 | 8065.92 | 10-AUG-16:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1348.05 | 6606.03 | 21-JAN-08:00 | 76766.94 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1348.05 | 6606.03 | 21-JAN-08:00 | 76766.94 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1348.05 | 6606.03 | 21-JAN-08:00 | 76766.94 | 10-AUG-16:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 133.61 | 5.12 | 08-JAN-07:00 | 8038.67 | 06-AUG-16:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 312.24 | 01-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 312.24 | 01-JAN-07:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 133.60 | 0.00 | 01-JAN-08:00 | 8038.67 | 06-AUG-16:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 133.60 | 0.00 | 01-JAN-08:00 | 8038.67 | 06-AUG-16:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7245.38 | 89281.29 | 22-JAN-06:00 | 371758.02 | 17-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7245.38 | 89281.29 | 22-JAN-06:00 | 371758.02 | 17-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7245.38 | 89281.29 | 22-JAN-06:00 | 371758.02 | 17-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
EnergyTransfer:HVAC | 40317.51 | 112827.77 | 15-JAN-07:00 | 3892534.24 | 10-AUG-16:00 |
HeatingCoils:EnergyTransfer | 3.90 | 0.00 | 01-JAN-00:10 | 30364.47 | 20-JAN-06:10 |
CoolingCoils:EnergyTransfer | 40313.61 | 112827.77 | 15-JAN-07:00 | 3892534.24 | 10-AUG-16:00 |
EnergyTransfer:Plant | 123189.00 | 48600.60 | 15-JAN-16:40 | 11969840.81 | 10-AUG-16:00 |
LoopToLoop:EnergyTransfer | 38962.33 | 35002.39 | 15-JAN-16:30 | 3768966.37 | 10-AUG-16:00 |
WaterSystems:EnergyTransfer | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
Chillers:EnergyTransfer | 38822.60 | 0.00 | 02-JAN-05:50 | 3785999.63 | 10-AUG-16:00 |
HeatRejection:EnergyTransfer | 45128.81 | 0.00 | 02-JAN-05:50 | 4395998.15 | 10-AUG-16:00 |
General:HeatRejection:EnergyTransfer | 45128.81 | 0.00 | 02-JAN-05:50 | 4395998.15 | 10-AUG-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 1.510 | -891.595 | 0.000 | 0.000 | 92.639 | 333.789 | 424.397 | 0.000 | 0.000 | 0.000 | 39.259 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -849.800 | 0.000 | 0.000 | 83.429 | 299.766 | 289.614 | 0.000 | 0.000 | 0.000 | 176.990 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 0.000 | -6607.718 | 0.000 | 0.000 | 836.079 | 2997.664 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.031 | 0.000 | 0.000 | 0.000 | 0.000 | -122.153 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -738.331 | 0.000 | 0.000 | 84.138 | 299.766 | 289.613 | 0.000 | 0.000 | 0.000 | 64.814 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.003 | -187.663 | 0.000 | 0.000 | 10.565 | 37.639 | 36.365 | 99.359 | 0.000 | 1.880 | 27.265 | 0.000 | -24.928 | 0.000 | -0.485 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.084 | -146.003 | 0.000 | 0.000 | 6.833 | 24.256 | 23.435 | 98.918 | 0.000 | 1.323 | 5.693 | 0.000 | -14.244 | 0.000 | -0.295 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.057 | -225.712 | 0.000 | 0.000 | 10.564 | 37.639 | 36.366 | 151.676 | 0.000 | 1.883 | 11.573 | 0.000 | -23.547 | 0.000 | -0.499 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.025 | -192.166 | 0.000 | 0.000 | 6.828 | 24.256 | 23.435 | 94.955 | 0.000 | 1.233 | 61.777 | 0.000 | -19.934 | 0.000 | -0.409 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 2.139 | -1638.452 | 0.000 | 0.000 | 106.945 | 376.387 | 363.654 | 1018.178 | 0.000 | 42.518 | 0.002 | 0.000 | -215.779 | 0.000 | -8.983 | -46.608 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 2.988 | -1336.399 | 0.000 | 0.000 | 50.714 | 242.558 | 234.352 | 978.698 | 0.000 | 28.818 | 0.005 | 0.000 | -132.485 | 0.000 | -6.044 | -63.200 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 1.871 | -2015.915 | 0.000 | 0.000 | 106.182 | 376.395 | 363.660 | 1513.058 | 0.000 | 41.917 | 0.006 | 0.000 | -222.535 | 0.000 | -10.761 | -153.872 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 3.469 | -1442.058 | 0.000 | 0.000 | 69.832 | 242.558 | 234.351 | 982.520 | 0.000 | 28.647 | 39.598 | 0.000 | -152.330 | 0.000 | -6.588 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.230 | -177.559 | 0.000 | 0.000 | 10.820 | 37.639 | 36.365 | 101.099 | 0.000 | 5.253 | 6.662 | 0.000 | -19.545 | 0.000 | -0.965 | 0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.140 | -142.219 | 0.000 | 0.000 | 6.928 | 24.256 | 23.435 | 97.149 | 0.000 | 3.522 | 0.000 | 0.000 | -12.297 | 0.000 | -0.676 | -0.238 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.120 | -213.657 | 0.000 | 0.000 | 10.710 | 37.639 | 36.366 | 150.038 | 0.000 | 5.165 | 0.001 | 0.000 | -20.397 | 0.000 | -1.195 | -4.789 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.075 | -152.036 | 0.000 | 0.000 | 7.050 | 24.256 | 23.435 | 97.234 | 0.000 | 3.544 | 11.338 | 0.000 | -14.144 | 0.000 | -0.752 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -145.512 | 0.000 | 0.000 | 0.950 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -17.665 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1348.053 | 0.000 | 0.000 | 9.501 | 83.466 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -283.720 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.005 | -133.601 | 0.000 | 0.000 | 0.950 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -29.581 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7245.383 | 0.000 | 0.000 | 20.597 | 94.114 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -364.186 |
GROUNDFLOOR_PLENUM | 1.267 | -155.526 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.520 | 151.951 | 0.000 | 0.000 | 0.000 | -1.212 | 0.000 |
MIDFLOOR_PLENUM | 9.558 | -1273.535 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 63.656 | 1219.601 | 0.000 | 0.000 | 0.000 | -19.280 | 0.000 |
TOPFLOOR_PLENUM | 2.542 | -286.147 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.677 | 278.613 | 0.000 | 0.000 | 0.000 | -1.685 | -0.000 |
Total Facility | 13.367 | -1715.208 | 12.717 | -25829.832 | 0.000 | 0.000 | 1532.255 | 5610.736 | 14676.396 | 5382.884 | 0.000 | 239.556 | 2095.180 | 0.000 | -872.165 | 0.000 | -59.829 | -1086.017 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 16-AUG-03:01 | 0.00 | 0.00 | 0.00 | -129962.45 | 0.00 | 0.00 | 0.00 | 1619.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 114885.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 21-FEB-05:11 | 0.00 | 0.00 | 0.00 | -127355.84 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.65 | 0.00 | 0.00 | 0.00 | 118509.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 26-APR-04:11 | 0.00 | 0.00 | 0.00 | -1113746.27 | 0.00 | 0.00 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 1025287.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 15-MAY-03:01 | 0.00 | 0.00 | 0.00 | -130670.93 | 0.00 | 0.00 | 0.00 | 1454.11 | 5937.62 | 0.00 | 0.00 | 0.00 | 123279.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 30-JUL-14:01 | 0.00 | 0.00 | 0.00 | -36295.43 | 0.00 | 0.00 | 32.47 | 182.58 | 720.18 | 12402.31 | 0.00 | 667.45 | 22290.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 30-JUL-10:01 | 0.00 | 0.00 | 0.00 | -33890.10 | 0.00 | 0.00 | 16.04 | 117.66 | 464.11 | 16752.37 | 0.00 | 213.24 | 16326.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-12:01 | 0.00 | 0.00 | 0.00 | -43555.85 | 0.00 | 0.00 | 27.79 | 182.58 | 720.19 | 21264.95 | 0.00 | 114.73 | 21245.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-JUL-14:41 | 0.00 | 0.00 | 0.00 | -43681.06 | 0.00 | 0.00 | 14.14 | 117.66 | 464.11 | 13629.06 | 0.00 | 402.44 | 29053.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 30-JUL-14:11 | 0.00 | 0.00 | 0.00 | -370365.59 | 0.00 | 0.00 | 311.76 | 1825.79 | 7201.84 | 122315.95 | 0.00 | 15295.67 | 223414.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 30-JUL-10:11 | 0.00 | 0.00 | 0.00 | -352217.70 | 0.00 | 0.00 | 149.41 | 1176.61 | 4641.14 | 159651.80 | 0.00 | 5241.43 | 181357.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 30-JUL-14:11 | 0.00 | 0.00 | 0.00 | -426467.85 | 0.00 | 0.00 | 299.67 | 1825.83 | 7201.95 | 132488.30 | 0.00 | 15209.50 | 269442.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 30-JUL-14:11 | 0.00 | 0.00 | 0.00 | -391863.43 | 0.00 | 0.00 | 157.61 | 1176.61 | 4641.11 | 142385.78 | 0.00 | 9712.23 | 233790.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 04-SEP-14:41 | 0.00 | 0.00 | 0.00 | -43640.23 | 0.00 | 0.00 | 30.41 | 182.58 | 720.18 | 10026.37 | 0.00 | 1182.27 | 31498.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-SEP-14:41 | 0.00 | 0.00 | 0.00 | -35036.86 | 0.00 | 0.00 | 18.55 | 117.66 | 464.11 | 6392.61 | 0.00 | 788.73 | 27255.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-14:41 | 0.00 | 0.00 | 0.00 | -51073.80 | 0.00 | 0.00 | 25.50 | 182.58 | 720.19 | 13610.39 | 0.00 | 1104.75 | 35430.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 04-SEP-16:01 | 0.00 | 0.00 | 0.00 | -44881.81 | 0.00 | 0.00 | 13.14 | 117.66 | 464.11 | 13143.31 | 0.00 | 690.19 | 30453.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 10-AUG-16:00 | 0.00 | 0.00 | 0.00 | -8065.97 | 0.00 | 0.00 | 100.84 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -558.07 |
DATACENTER_MID_ZN_6 | 10-AUG-16:00 | 0.00 | 0.00 | 0.00 | -76767.44 | 0.00 | 0.00 | 1008.37 | 7287.84 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9473.00 |
DATACENTER_TOP_ZN_6 | 06-AUG-16:40 | 0.00 | 0.00 | 0.00 | -8038.76 | 0.00 | 0.00 | 5.31 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 198.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 29-APR-05:07 | 0.00 | 0.00 | 0.00 | -384178.08 | 0.00 | 0.00 | 229.91 | 913.06 | 379632.52 | 0.00 | 0.00 | 0.00 | 3402.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 19-JAN-06:08 | 0.00 | -29441.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29613.00 | 0.00 | -0.00 | 0.00 | -171.38 | 0.00 |
MIDFLOOR_PLENUM | 30-DEC-06:05 | 0.00 | -306092.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306092.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-12:05 | 0.00 | -46030.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.30 | 45513.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-APR-03:01 | 0.00 | 86418.05 | 0.00 | -2501290.08 | 0.00 | 0.00 | 0.00 | 27216.71 | 562130.35 | 0.00 | 0.00 | 895.76 | 1863877.55 | 0.00 | -39248.35 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 29-JUL-16:01 | 0.00 | 0.00 | 25761.16 | 0.00 | 0.00 | 0.00 | 520.14 | 1619.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -41358.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 20-JAN-06:10 | 0.00 | 0.00 | 2992.14 | 0.00 | 0.00 | 0.00 | 130.61 | 365.16 | 960.25 | 0.00 | 0.00 | 0.00 | 967.57 | 0.00 | -5389.28 | 0.00 | -26.44 | 0.00 |
PERIMETER_BOT_ZN_2 | 03-JAN-06:06 | 0.00 | 0.00 | 4049.91 | 0.00 | 0.00 | 0.00 | 88.56 | 235.32 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3322.82 | 0.00 | 0.00 | -1669.79 |
PERIMETER_BOT_ZN_1 | 03-JAN-06:08 | 0.00 | 0.00 | 5040.74 | 0.00 | 0.00 | 0.00 | 136.90 | 365.17 | 960.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4967.74 | 0.00 | 0.00 | -1535.32 |
PERIMETER_BOT_ZN_4 | 19-JAN-06:08 | 0.00 | 0.00 | 3711.86 | 0.00 | 0.00 | 0.00 | 80.55 | 235.32 | 618.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3855.06 | 0.00 | -45.87 | -745.61 |
PERIMETER_MID_ZN_3 | 03-JAN-06:04 | 0.00 | 0.00 | 43395.35 | 0.00 | 0.00 | 0.00 | 1368.62 | 3651.57 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -47386.72 | 0.00 | 0.00 | -10631.27 |
PERIMETER_MID_ZN_2 | 02-JAN-05:20 | 0.00 | 0.00 | 54965.82 | 0.00 | 0.00 | 0.00 | 0.00 | 2353.21 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -32297.30 | 0.00 | -814.72 | -29011.69 |
PERIMETER_MID_ZN_1 | 01-FEB-06:06 | 0.00 | 0.00 | 47420.82 | 0.00 | 0.00 | 0.00 | 1338.41 | 3651.65 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -50759.13 | 0.00 | -333.98 | -10920.38 |
PERIMETER_MID_ZN_4 | 23-FEB-06:03 | 0.00 | 0.00 | 47436.59 | 0.00 | 0.00 | 0.00 | 923.94 | 2353.21 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -23108.70 | 0.00 | -224.84 | -33568.34 |
PERIMETER_TOP_ZN_3 | 03-JAN-06:02 | 0.00 | 0.00 | 14594.09 | 0.00 | 0.00 | 0.00 | 145.74 | 365.16 | 960.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4079.87 | 0.00 | 0.00 | -11985.37 |
PERIMETER_TOP_ZN_2 | 03-JAN-06:02 | 0.00 | 0.00 | 9138.58 | 0.00 | 0.00 | 0.00 | 93.89 | 235.32 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2716.73 | 0.00 | 0.00 | -7369.88 |
PERIMETER_TOP_ZN_1 | 03-JAN-06:02 | 0.00 | 0.00 | 13515.20 | 0.00 | 0.00 | 0.00 | 145.78 | 365.17 | 960.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4158.84 | 0.00 | 0.00 | -10827.56 |
PERIMETER_TOP_ZN_4 | 03-JAN-06:02 | 0.00 | 0.00 | 7296.44 | 0.00 | 0.00 | 0.00 | 93.49 | 235.32 | 618.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2801.32 | 0.00 | 0.00 | -5442.74 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 01-JAN-07:05 | 0.00 | 0.00 | 624.48 | 0.00 | 0.00 | 0.00 | 5.28 | 40.49 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2618.85 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 30-JUL-14:01 | 19868.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1526.89 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -21395.61 |
MIDFLOOR_PLENUM | 30-JUL-13:31 | 206770.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25026.67 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -231797.54 |
TOPFLOOR_PLENUM | 21-MAR-05:02 | 24147.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -18.96 | -24128.31 |
Total Facility | 30-JUL-13:31 | -1982327.86 | 2186086.36 | 0.00 | -2186086.36 | 0.00 | 0.00 | 7215.59 | 27216.71 | 465581.25 | 585397.76 | 0.00 | 87179.08 | 809737.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 15.4459 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 13.9881 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 148.6257 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 131.3038 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 17.1685 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 16.7187 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 7.6981 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 7.6981 | 0.1559 | 1.0000 | Not calculated | 1.2002 | 0.1559 | ||
AIRLOOP DATACENTER BASEMENT | 31.7358 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 31.7360 | 0.0107 | 1.0000 | Not calculated | 0.3384 | 0.0107 | ||
AIRLOOP DATACENTER BOT | 0.7181 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7181 | 0.0218 | 1.0000 | Not calculated | 0.0156 | 0.0218 | ||
AIRLOOP DATACENTER MID | 6.8364 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 6.8364 | 0.0229 | 1.0000 | Not calculated | 0.1563 | 0.0229 | ||
AIRLOOP DATACENTER TOP | 0.7206 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7206 | 0.0217 | 1.0000 | Not calculated | 0.0156 | 0.0217 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 4.6338 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6338 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 44.5877 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 44.5877 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.1505 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.1505 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 2.3094 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 2.3094 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.5197 | ||
AIRLOOP DATACENTER BASEMENT | 15.8679 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 15.8679 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0213 | ||
AIRLOOP DATACENTER BOT | 0.7181 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7181 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0218 | ||
AIRLOOP DATACENTER MID | 6.8364 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 6.8364 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0229 | ||
AIRLOOP DATACENTER TOP | 0.7206 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.7206 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0217 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 7.6981 | 7.6981 | 2.3094 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 7.6555 | 7.6555 | 2.2966 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 72.4864 | 72.4864 | 21.7459 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 8.5685 | 8.5685 | 2.5705 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.8710 | 1.8710 | 0.5613 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.6479 | 1.6479 | 0.4944 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 2.1720 | 2.1720 | 0.6516 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 2.0995 | 2.0995 | 0.6299 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 18.7426 | 18.7426 | 5.6228 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 16.8658 | 16.8658 | 5.0598 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 21.4779 | 21.4779 | 6.4434 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 19.0529 | 19.0529 | 5.7159 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 2.2177 | 2.2177 | 0.6653 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.7816 | 1.7816 | 0.5345 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 2.4765 | 2.4765 | 0.7430 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 2.1242 | 2.1242 | 0.6373 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7181 | 0.7181 | 0.7181 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.8364 | 6.8364 | 6.8364 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7206 | 0.7206 | 0.7206 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 31.7358 | 31.7358 | 15.8679 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 15.4459 | 13.9881 | 15.4459 | 4.6338 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 148.6257 | 131.3038 | 148.6257 | 44.5877 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 17.1685 | 16.7187 | 17.1685 | 5.1505 | 0.0000 | 1.0000 |
CAV_BAS | 7.6981 | 7.6981 | 7.6981 | 2.3094 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 31.7358 | 31.7360 | 31.7358 | 15.8679 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.7181 | 0.7181 | 0.7181 | 0.7181 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 6.8364 | 6.8364 | 6.8364 | 6.8364 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.7206 | 0.7206 | 0.7206 | 0.7206 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 2.3094 | 2.3094 | 2.3094 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 2.2966 | 9.9521 | 2.2966 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 21.7459 | 94.2323 | 21.7459 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 2.5705 | 11.1390 | 2.5705 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.5613 | 2.4323 | 0.5613 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.4944 | 2.1422 | 0.4944 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.6516 | 2.8236 | 0.6516 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.6299 | 2.7294 | 0.6299 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 5.6228 | 24.3654 | 5.6228 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 5.0598 | 21.9256 | 5.0598 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 6.4434 | 27.9213 | 6.4434 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 5.7159 | 24.7688 | 5.7159 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.6653 | 2.8830 | 0.6653 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.5345 | 2.3160 | 0.5345 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.7430 | 3.2195 | 0.7430 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.6373 | 2.7615 | 0.6373 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7181 | 0.7181 | 0.7181 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.8364 | 6.8364 | 6.8364 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7206 | 0.7206 | 0.7206 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 15.8679 | 15.8679 | 15.8679 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 4.6338 | 4.6338 | 20.0797 | 4.6338 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 44.5877 | 44.5877 | 193.2135 | 44.5877 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.1505 | 5.1505 | 22.3190 | 5.1505 | 0.0000 | 1.0000 |
CAV_BAS | 2.3094 | 2.3094 | 2.3094 | 2.3094 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 15.8679 | 15.8679 | 15.8679 | 15.8679 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.7181 | 0.7181 | 0.7181 | 0.7181 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 6.8364 | 6.8364 | 6.8364 | 6.8364 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.7206 | 0.7206 | 0.7206 | 0.7206 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 210.00 |
Number of hours not met | 210.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 3.90 | 30364.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 6973.06 | 654821.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 5610.74 | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 1008.65 | 64082.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 56.04 | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.31 | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 3135.53 | 318420.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 2035.56 | 112104.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1144.11 | 64095.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 0.11 | 2799.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 280.41 | 37718.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 37491.57 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 37491.57 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 121.13 |
Space Heating | 0.08 |
Space Cooling | 150.54 |
Fans (All) | 67.69 |
Service Water Heating | 6.05 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 809.40 |
Subtotal | 809.40 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.97 |
Space Heating | 0.01 |
Space Cooling | 18.60 |
Fans (All) | 8.36 |
Service Water Heating | 0.75 |
Receptacle Equipment | 39.15 |
Miscellaneous | 18.17 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
LTG_SCH_DATACENTER | 2939. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 7170.00 | 1590.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8490.00 | 270.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8635.33 | 124.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8627.67 | 132.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8572.33 | 187.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7784.50 | 975.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8203.50 | 556.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8277.00 | 483.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8153.83 | 606.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8009.33 | 750.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8191.00 | 569.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8195.83 | 564.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8142.17 | 617.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8062.50 | 697.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 4855.50 | 3904.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 4749.00 | 4011.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 4727.33 | 4032.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 466.33 | 8293.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8158.83 | 601.17 | 0.00 | 0.00 | 0.00 |
Min | 466.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 8293.67 | 0.00 | 0.00 | 0.00 |
Average | 7500.39 | 1259.61 | 0.00 | 0.00 | 0.00 |
Sum | 172509.00 | 28971.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 364222.33 | 4393.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330539.00 | 274.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1129.67 | 1138.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1097.00 | 1171.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1092.33 | 1175.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 4812.83 | 98582.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 364222.33 | 98582.17 | 0.00 | 0.00 | 0.00 |
Average | 75694.27 | 4640.64 | 0.00 | 0.00 | 0.00 |
Sum | 1740968.17 | 106734.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 6555.67 | 2204.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 6844.83 | 1915.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7031.67 | 1728.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7272.00 | 1488.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6886.83 | 1873.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7527.50 | 1232.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 6986.67 | 1773.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6557.83 | 2202.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6558.00 | 2202.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6770.67 | 1989.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6418.67 | 2341.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6647.00 | 2113.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6634.67 | 2125.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6729.67 | 2030.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6525.00 | 2235.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6733.67 | 2026.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 5941.50 | 2818.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 5797.83 | 2962.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 5769.00 | 2991.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 650.83 | 8109.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 5890.67 | 2869.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 6299.67 | 2460.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 4286.50 | 4473.50 | 0.00 | 0.00 | 0.00 |
Min | 650.83 | 1232.50 | 0.00 | 0.00 | 0.00 |
Max | 7527.50 | 8109.17 | 0.00 | 0.00 | 0.00 |
Average | 6231.14 | 2528.86 | 0.00 | 0.00 | 0.00 |
Sum | 143316.33 | 58163.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 363660.00 | 4956.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 327962.00 | 2851.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 328351.00 | 2462.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 328633.33 | 2179.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38924.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1371.67 | 896.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1334.17 | 933.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1330.50 | 937.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6503.67 | 96891.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 363660.00 | 96891.33 | 0.00 | 0.00 | 0.00 |
Average | 75460.66 | 4874.25 | 0.00 | 0.00 | 0.00 |
Sum | 1735595.17 | 112107.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.709815E+11 | 125301.35 | 17-JAN-05:11 | 16.67 | 11.90 | 0.567215E+10 | 7499.17 | 20-JAN-10:50 | 19.48 | 12.69 |
February | 0.637142E+11 | 121309.08 | 11-FEB-05:12 | 18.83 | 13.75 | 0.514450E+10 | 7499.43 | 08-FEB-14:09 | 18.83 | 13.75 |
March | 0.737217E+11 | 125929.23 | 28-MAR-03:01 | 26.02 | 14.38 | 0.613819E+10 | 7499.11 | 08-MAR-10:09 | 26.02 | 14.38 |
April | 0.674668E+11 | 128446.76 | 03-APR-03:12 | 24.80 | 17.70 | 0.545462E+10 | 7499.61 | 24-APR-09:50 | 33.00 | 17.72 |
May | 0.721088E+11 | 124305.99 | 29-MAY-15:58 | 35.10 | 24.43 | 0.590659E+10 | 7499.71 | 12-MAY-09:00 | 35.10 | 24.43 |
June | 0.729155E+11 | 119955.87 | 16-JUN-05:02 | 28.17 | 20.46 | 0.588694E+10 | 7499.39 | 21-JUN-09:39 | 38.00 | 19.85 |
July | 0.742354E+11 | 128334.00 | 11-JUL-03:01 | 32.98 | 24.23 | 0.547766E+10 | 7498.95 | 27-JUL-13:20 | 36.80 | 29.25 |
August | 0.840079E+11 | 129952.91 | 16-AUG-03:01 | 35.07 | 25.37 | 0.614081E+10 | 7498.92 | 16-AUG-09:20 | 37.30 | 27.57 |
September | 0.756754E+11 | 125953.88 | 04-SEP-09:16 | 36.53 | 22.23 | 0.545659E+10 | 7499.43 | 29-SEP-09:09 | 31.45 | 22.70 |
October | 0.806548E+11 | 124445.37 | 29-OCT-12:43 | 35.03 | 15.16 | 0.567528E+10 | 7499.42 | 27-OCT-09:50 | 35.03 | 15.16 |
November | 0.797179E+11 | 127185.08 | 13-NOV-05:22 | 21.00 | 17.47 | 0.561882E+10 | 7498.93 | 02-NOV-09:20 | 21.00 | 17.47 |
December | 0.764055E+11 | 122462.48 | 11-DEC-05:33 | 22.00 | 19.08 | 0.547563E+10 | 7499.20 | 18-DEC-10:09 | 20.42 | 13.70 |
Annual Sum or Average | 0.891605E+12 | 0.680478E+11 | ||||||||
Minimum of Months | 0.637142E+11 | 119955.87 | 16.67 | 11.90 | 0.514450E+10 | 7498.92 | 18.83 | 12.69 | ||
Maximum of Months | 0.840079E+11 | 129952.91 | 36.53 | 25.37 | 0.614081E+10 | 7499.71 | 38.00 | 29.25 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.564752E+11 | 125382.22 | 02-JAN-05:12 | 13.67 | 11.10 | 0.507575E+10 | 6734.93 | 25-JAN-10:09 | 20.25 | 15.27 |
February | 0.545465E+11 | 127386.51 | 21-FEB-05:11 | 14.67 | 13.69 | 0.460717E+10 | 6734.93 | 23-FEB-10:09 | 22.83 | 16.44 |
March | 0.690922E+11 | 124970.42 | 06-MAR-05:12 | 16.67 | 12.96 | 0.550116E+10 | 6734.93 | 31-MAR-09:50 | 22.17 | 21.45 |
April | 0.718353E+11 | 121328.99 | 07-APR-04:11 | 20.53 | 16.40 | 0.488052E+10 | 6734.93 | 19-APR-09:09 | 26.25 | 21.79 |
May | 0.718614E+11 | 114980.30 | 15-MAY-04:12 | 23.40 | 18.32 | 0.528336E+10 | 6734.93 | 18-MAY-13:00 | 37.00 | 24.23 |
June | 0.764231E+11 | 107306.61 | 20-JUN-05:02 | 28.00 | 25.80 | 0.526546E+10 | 6734.93 | 05-JUN-09:30 | 28.00 | 25.80 |
July | 0.812171E+11 | 106023.25 | 17-JUL-05:03 | 31.00 | 26.53 | 0.489000E+10 | 6734.93 | 06-JUL-13:39 | 31.00 | 26.53 |
August | 0.885150E+11 | 107781.11 | 07-AUG-05:02 | 32.82 | 23.16 | 0.549155E+10 | 6734.93 | 29-AUG-13:00 | 37.00 | 29.90 |
September | 0.709242E+11 | 113773.62 | 25-SEP-04:02 | 24.17 | 23.10 | 0.487765E+10 | 6734.93 | 20-SEP-13:30 | 24.17 | 23.10 |
October | 0.735393E+11 | 115383.44 | 28-OCT-03:01 | 24.00 | 21.21 | 0.507475E+10 | 6734.93 | 03-OCT-09:20 | 24.00 | 21.21 |
November | 0.694359E+11 | 121524.35 | 22-NOV-05:12 | 17.00 | 14.53 | 0.502929E+10 | 6734.93 | 01-NOV-13:20 | 17.00 | 14.53 |
December | 0.659337E+11 | 125671.28 | 18-DEC-05:12 | 13.00 | 10.66 | 0.490280E+10 | 6734.93 | 26-DEC-10:09 | 21.33 | 18.45 |
Annual Sum or Average | 0.849799E+12 | 0.608795E+11 | ||||||||
Minimum of Months | 0.545465E+11 | 106023.25 | 13.00 | 10.66 | 0.460717E+10 | 6734.93 | 17.00 | 14.53 | ||
Maximum of Months | 0.885150E+11 | 127386.51 | 32.82 | 26.53 | 0.550116E+10 | 6734.93 | 37.00 | 29.90 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.438716E+11 | 104434.14 | 02-JAN-05:12 | 13.67 | 11.10 | 0.504017E+10 | 6734.93 | 24-JAN-14:50 | 23.00 | 18.55 |
February | 0.417939E+11 | 105175.00 | 10-FEB-05:12 | 19.93 | 12.75 | 0.457927E+10 | 6734.93 | 01-FEB-14:20 | 19.93 | 12.75 |
March | 0.526518E+11 | 108098.65 | 23-MAR-04:11 | 21.67 | 13.58 | 0.548122E+10 | 6734.93 | 02-MAR-14:20 | 21.67 | 13.58 |
April | 0.523700E+11 | 111389.73 | 26-APR-04:11 | 23.07 | 11.89 | 0.487078E+10 | 6734.93 | 19-APR-09:09 | 23.07 | 11.89 |
May | 0.614768E+11 | 105305.46 | 05-MAY-04:02 | 25.75 | 15.83 | 0.527929E+10 | 6734.93 | 11-MAY-09:20 | 37.67 | 19.28 |
June | 0.625100E+11 | 97595.34 | 08-JUN-05:01 | 25.78 | 25.14 | 0.526078E+10 | 6734.93 | 28-JUN-13:09 | 37.58 | 26.82 |
July | 0.634660E+11 | 81662.32 | 13-JUL-05:02 | 30.00 | 20.11 | 0.487947E+10 | 6734.93 | 12-JUL-13:00 | 30.00 | 20.11 |
August | 0.676156E+11 | 81734.11 | 31-AUG-03:01 | 28.97 | 26.60 | 0.548308E+10 | 6734.93 | 01-AUG-13:39 | 28.97 | 26.60 |
September | 0.592634E+11 | 103862.09 | 22-SEP-04:01 | 27.82 | 26.18 | 0.487213E+10 | 6734.93 | 12-SEP-13:20 | 27.82 | 26.18 |
October | 0.580288E+11 | 107692.64 | 20-OCT-04:11 | 22.60 | 16.22 | 0.506933E+10 | 6734.93 | 10-OCT-13:09 | 22.60 | 16.22 |
November | 0.520156E+11 | 110648.36 | 13-NOV-05:12 | 21.00 | 17.39 | 0.501756E+10 | 6734.93 | 02-NOV-13:20 | 21.00 | 17.39 |
December | 0.457085E+11 | 106634.11 | 01-DEC-05:11 | 17.67 | 12.76 | 0.486746E+10 | 6734.93 | 01-DEC-10:39 | 26.47 | 16.31 |
Annual Sum or Average | 0.660772E+12 | 0.607005E+11 | ||||||||
Minimum of Months | 0.417939E+11 | 81662.32 | 13.67 | 11.10 | 0.457927E+10 | 6734.93 | 19.93 | 11.89 | ||
Maximum of Months | 0.676156E+11 | 111389.73 | 30.00 | 26.60 | 0.548308E+10 | 6734.93 | 37.67 | 26.82 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.408745E+11 | 65224.67 | 30-JAN-06:02 | 20.03 | 17.43 | 0.487645E+10 | 6734.93 | 03-JAN-14:00 | 20.03 | 17.43 |
February | 0.413765E+11 | 118702.64 | 06-FEB-06:02 | 21.88 | 19.06 | 0.447954E+10 | 6734.93 | 28-FEB-14:50 | 24.00 | 18.15 |
March | 0.545465E+11 | 124141.55 | 28-MAR-04:01 | 26.08 | 14.62 | 0.541662E+10 | 6734.93 | 31-MAR-09:50 | 22.17 | 21.45 |
April | 0.580211E+11 | 126447.66 | 24-APR-04:11 | 23.00 | 14.49 | 0.484345E+10 | 6734.93 | 19-APR-09:09 | 23.00 | 14.49 |
May | 0.732994E+11 | 130693.34 | 15-MAY-03:01 | 24.18 | 19.17 | 0.527533E+10 | 6734.93 | 02-MAY-13:30 | 24.18 | 19.17 |
June | 0.759229E+11 | 118814.32 | 08-JUN-05:01 | 25.78 | 25.14 | 0.525889E+10 | 6734.93 | 07-JUN-09:30 | 25.78 | 25.14 |
July | 0.795542E+11 | 111078.97 | 10-JUL-05:02 | 32.00 | 25.13 | 0.488221E+10 | 6734.93 | 07-JUL-13:09 | 32.00 | 25.13 |
August | 0.833656E+11 | 111818.83 | 25-AUG-05:02 | 30.42 | 28.22 | 0.548193E+10 | 6734.93 | 01-AUG-13:39 | 30.42 | 28.22 |
September | 0.702024E+11 | 122756.40 | 12-SEP-04:01 | 27.92 | 26.76 | 0.486847E+10 | 6734.93 | 01-SEP-13:50 | 27.92 | 26.76 |
October | 0.643821E+11 | 126504.75 | 19-OCT-04:01 | 24.58 | 19.83 | 0.505591E+10 | 6734.93 | 06-OCT-13:20 | 24.58 | 19.83 |
November | 0.530924E+11 | 121217.22 | 03-NOV-04:01 | 24.08 | 22.27 | 0.497630E+10 | 6734.93 | 09-NOV-10:30 | 30.45 | 21.13 |
December | 0.436957E+11 | 122487.86 | 12-DEC-06:02 | 23.03 | 17.89 | 0.475564E+10 | 6734.93 | 01-DEC-14:00 | 23.03 | 17.89 |
Annual Sum or Average | 0.738333E+12 | 0.601707E+11 | ||||||||
Minimum of Months | 0.408745E+11 | 65224.67 | 20.03 | 14.49 | 0.447954E+10 | 6734.93 | 20.03 | 14.49 | ||
Maximum of Months | 0.833656E+11 | 130693.34 | 32.00 | 28.22 | 0.548193E+10 | 6734.93 | 32.00 | 28.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.831841E+10 | 9610.34 | 23-JAN-14:00 | 28.00 | 16.55 | 0.605585E+09 | 845.64 | 03-JAN-14:00 | 28.00 | 16.55 |
February | 0.864986E+10 | 12464.79 | 06-FEB-14:30 | 32.25 | 17.25 | 0.559579E+09 | 845.64 | 07-FEB-14:30 | 29.50 | 21.41 |
March | 0.121034E+11 | 15393.78 | 27-MAR-04:11 | 22.43 | 13.90 | 0.677176E+09 | 845.64 | 01-MAR-14:50 | 22.43 | 13.90 |
April | 0.147933E+11 | 30094.40 | 02-APR-14:01 | 33.83 | 18.68 | 0.607310E+09 | 845.64 | 19-APR-09:09 | 26.25 | 21.79 |
May | 0.185856E+11 | 32503.25 | 07-MAY-14:11 | 37.00 | 20.10 | 0.663575E+09 | 845.64 | 31-MAY-09:09 | 34.53 | 24.63 |
June | 0.209715E+11 | 33367.36 | 11-JUN-13:21 | 36.90 | 28.45 | 0.662105E+09 | 845.64 | 05-JUN-09:09 | 36.90 | 28.45 |
July | 0.232098E+11 | 36315.77 | 30-JUL-14:01 | 43.50 | 24.98 | 0.616425E+09 | 845.64 | 25-JUL-09:09 | 43.50 | 24.98 |
August | 0.244051E+11 | 32464.35 | 06-AUG-15:01 | 40.85 | 24.99 | 0.691194E+09 | 845.64 | 04-AUG-09:09 | 40.85 | 24.99 |
September | 0.181601E+11 | 35324.66 | 04-SEP-14:41 | 41.00 | 24.39 | 0.612717E+09 | 845.64 | 20-SEP-13:30 | 36.85 | 23.99 |
October | 0.160481E+11 | 33241.62 | 09-OCT-14:41 | 37.00 | 20.65 | 0.634786E+09 | 845.64 | 03-OCT-13:00 | 37.00 | 20.65 |
November | 0.124839E+11 | 23742.64 | 05-NOV-14:21 | 32.50 | 21.12 | 0.625014E+09 | 845.64 | 03-NOV-13:09 | 32.50 | 21.12 |
December | 0.993459E+10 | 10384.58 | 11-DEC-14:10 | 26.77 | 18.23 | 0.598766E+09 | 845.64 | 04-DEC-14:50 | 26.77 | 18.23 |
Annual Sum or Average | 0.187664E+12 | 0.755423E+10 | ||||||||
Minimum of Months | 0.831841E+10 | 9610.34 | 22.43 | 13.90 | 0.559579E+09 | 845.64 | 22.43 | 13.90 | ||
Maximum of Months | 0.244051E+11 | 36315.77 | 43.50 | 28.45 | 0.691194E+09 | 845.64 | 43.50 | 28.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.687208E+10 | 7884.38 | 29-JAN-10:20 | 24.87 | 19.00 | 0.389062E+09 | 544.96 | 17-JAN-14:50 | 24.87 | 19.00 |
February | 0.691535E+10 | 12825.12 | 05-FEB-09:32 | 25.80 | 17.88 | 0.359830E+09 | 544.96 | 03-FEB-14:30 | 25.80 | 17.88 |
March | 0.944633E+10 | 19342.18 | 26-MAR-09:12 | 27.00 | 16.22 | 0.432405E+09 | 544.96 | 01-MAR-14:09 | 27.00 | 16.22 |
April | 0.116642E+11 | 30529.90 | 23-APR-10:01 | 32.75 | 16.81 | 0.388358E+09 | 544.96 | 19-APR-09:09 | 32.75 | 16.81 |
May | 0.148932E+11 | 31763.32 | 07-MAY-09:31 | 35.33 | 17.61 | 0.426721E+09 | 544.96 | 22-MAY-09:09 | 34.45 | 22.91 |
June | 0.159504E+11 | 30420.72 | 25-JUN-10:21 | 35.15 | 25.69 | 0.425324E+09 | 544.96 | 05-JUN-09:09 | 35.15 | 25.69 |
July | 0.173678E+11 | 33891.89 | 30-JUL-10:01 | 42.83 | 21.77 | 0.395956E+09 | 544.96 | 11-JUL-13:39 | 42.83 | 21.77 |
August | 0.183159E+11 | 28759.24 | 13-AUG-10:32 | 39.20 | 25.03 | 0.444060E+09 | 544.96 | 04-AUG-09:09 | 39.20 | 25.03 |
September | 0.144887E+11 | 30923.07 | 04-SEP-08:41 | 35.38 | 21.67 | 0.393748E+09 | 544.96 | 08-SEP-13:09 | 35.42 | 29.24 |
October | 0.127815E+11 | 29986.68 | 09-OCT-10:41 | 35.55 | 20.67 | 0.407539E+09 | 544.96 | 13-OCT-13:00 | 34.00 | 24.03 |
November | 0.973235E+10 | 23636.01 | 05-NOV-11:01 | 32.58 | 18.45 | 0.400764E+09 | 544.96 | 27-NOV-14:50 | 27.50 | 20.18 |
December | 0.757598E+10 | 7993.50 | 01-DEC-10:30 | 26.20 | 16.33 | 0.380229E+09 | 544.96 | 07-DEC-14:30 | 25.50 | 17.64 |
Annual Sum or Average | 0.146004E+12 | 0.484400E+10 | ||||||||
Minimum of Months | 0.687208E+10 | 7884.38 | 24.87 | 16.22 | 0.359830E+09 | 544.96 | 24.87 | 16.22 | ||
Maximum of Months | 0.183159E+11 | 33891.89 | 42.83 | 25.69 | 0.444060E+09 | 544.96 | 42.83 | 29.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127241E+11 | 18784.25 | 16-JAN-12:22 | 25.45 | 13.80 | 0.615003E+09 | 845.66 | 03-JAN-14:09 | 25.45 | 13.80 |
February | 0.126499E+11 | 34932.48 | 05-FEB-13:32 | 31.43 | 19.44 | 0.561841E+09 | 845.66 | 08-FEB-14:30 | 29.50 | 19.67 |
March | 0.157226E+11 | 37668.86 | 12-MAR-13:22 | 28.35 | 16.38 | 0.673421E+09 | 845.66 | 07-MAR-14:20 | 28.35 | 16.38 |
April | 0.168361E+11 | 38076.94 | 02-APR-13:21 | 33.20 | 17.97 | 0.603061E+09 | 845.66 | 04-APR-13:09 | 26.58 | 18.84 |
May | 0.191653E+11 | 37827.58 | 07-MAY-14:11 | 37.00 | 20.10 | 0.660788E+09 | 845.66 | 02-MAY-13:30 | 37.00 | 20.10 |
June | 0.207600E+11 | 37806.01 | 11-JUN-13:21 | 36.90 | 28.45 | 0.660052E+09 | 845.66 | 05-JUN-09:09 | 36.90 | 28.45 |
July | 0.235327E+11 | 42595.46 | 30-JUL-14:01 | 43.50 | 24.98 | 0.615300E+09 | 845.66 | 07-JUL-09:39 | 43.50 | 24.98 |
August | 0.261815E+11 | 37693.99 | 13-AUG-14:31 | 40.00 | 25.61 | 0.690489E+09 | 845.66 | 04-AUG-09:09 | 40.00 | 25.61 |
September | 0.222185E+11 | 43133.98 | 04-SEP-14:41 | 41.00 | 24.39 | 0.611992E+09 | 845.94 | 05-SEP-13:50 | 40.15 | 24.82 |
October | 0.222741E+11 | 43554.64 | 09-OCT-12:01 | 37.93 | 19.82 | 0.635012E+09 | 846.00 | 04-OCT-13:00 | 37.93 | 19.82 |
November | 0.186849E+11 | 43050.01 | 05-NOV-12:21 | 33.70 | 19.11 | 0.626898E+09 | 845.75 | 13-NOV-14:09 | 33.00 | 16.45 |
December | 0.149629E+11 | 41580.30 | 25-DEC-12:11 | 25.83 | 18.30 | 0.602061E+09 | 845.66 | 04-DEC-14:00 | 25.83 | 18.30 |
Annual Sum or Average | 0.225713E+12 | 0.755592E+10 | ||||||||
Minimum of Months | 0.126499E+11 | 18784.25 | 25.45 | 13.80 | 0.561841E+09 | 845.66 | 25.45 | 13.80 | ||
Maximum of Months | 0.261815E+11 | 43554.64 | 43.50 | 28.45 | 0.690489E+09 | 846.00 | 43.50 | 28.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.887619E+10 | 10679.19 | 29-JAN-16:53 | 25.00 | 20.23 | 0.378888E+09 | 544.96 | 23-JAN-14:00 | 25.00 | 20.23 |
February | 0.950657E+10 | 21782.62 | 06-FEB-05:11 | 21.93 | 19.24 | 0.356775E+09 | 544.96 | 27-FEB-14:20 | 23.33 | 16.82 |
March | 0.135313E+11 | 35748.52 | 12-MAR-15:21 | 26.30 | 18.18 | 0.436355E+09 | 544.96 | 15-MAR-13:50 | 24.95 | 17.84 |
April | 0.164741E+11 | 37247.29 | 02-APR-14:01 | 33.83 | 18.68 | 0.392765E+09 | 544.96 | 05-APR-13:20 | 24.07 | 19.69 |
May | 0.173752E+11 | 40228.25 | 14-MAY-15:21 | 34.50 | 20.63 | 0.424700E+09 | 544.96 | 01-MAY-13:20 | 34.50 | 20.63 |
June | 0.199345E+11 | 39489.63 | 25-JUN-15:01 | 34.93 | 28.61 | 0.425424E+09 | 544.96 | 05-JUN-13:00 | 34.93 | 28.61 |
July | 0.225881E+11 | 43721.19 | 30-JUL-14:41 | 41.50 | 26.59 | 0.397045E+09 | 544.96 | 20-JUL-09:09 | 41.50 | 26.59 |
August | 0.247870E+11 | 38578.69 | 06-AUG-15:41 | 40.25 | 25.55 | 0.445665E+09 | 544.96 | 04-AUG-09:09 | 40.25 | 25.55 |
September | 0.173158E+11 | 43027.20 | 04-SEP-15:21 | 40.85 | 24.13 | 0.392465E+09 | 544.96 | 18-SEP-13:30 | 36.65 | 25.44 |
October | 0.163532E+11 | 40772.15 | 09-OCT-15:21 | 36.90 | 19.74 | 0.407232E+09 | 544.96 | 02-OCT-13:30 | 36.90 | 19.74 |
November | 0.136578E+11 | 38116.96 | 05-NOV-14:21 | 32.50 | 21.12 | 0.402930E+09 | 544.96 | 09-NOV-14:00 | 30.00 | 22.93 |
December | 0.117667E+11 | 26365.06 | 15-DEC-05:11 | 20.00 | 18.24 | 0.388933E+09 | 544.96 | 21-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.192166E+12 | 0.484917E+10 | ||||||||
Minimum of Months | 0.887619E+10 | 10679.19 | 20.00 | 18.18 | 0.356775E+09 | 544.96 | 23.00 | 16.82 | ||
Maximum of Months | 0.247870E+11 | 43721.19 | 41.50 | 28.61 | 0.445665E+09 | 544.96 | 41.50 | 28.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.660388E+10 | 7580.12 | 22-JAN-14:32 | 26.00 | 16.51 | 0.570600E+09 | 845.64 | 30-JAN-14:00 | 22.00 | 20.56 |
February | 0.692742E+10 | 10984.44 | 06-FEB-14:50 | 32.42 | 17.27 | 0.536680E+09 | 845.64 | 06-FEB-14:09 | 32.42 | 17.27 |
March | 0.992868E+10 | 16207.11 | 28-MAR-05:02 | 25.67 | 14.74 | 0.658374E+09 | 845.64 | 02-MAR-14:00 | 25.67 | 14.74 |
April | 0.118284E+11 | 26551.96 | 30-APR-12:31 | 37.07 | 20.92 | 0.599296E+09 | 845.64 | 04-APR-13:00 | 37.07 | 20.92 |
May | 0.174818E+11 | 32982.62 | 07-MAY-14:11 | 37.00 | 20.10 | 0.663012E+09 | 845.64 | 31-MAY-09:09 | 34.53 | 24.63 |
June | 0.193431E+11 | 31281.26 | 11-JUN-16:11 | 36.60 | 26.54 | 0.662251E+09 | 845.64 | 05-JUN-09:09 | 36.60 | 26.54 |
July | 0.213367E+11 | 37065.83 | 30-JUL-14:11 | 43.00 | 25.45 | 0.616732E+09 | 845.64 | 25-JUL-09:09 | 43.00 | 25.45 |
August | 0.220715E+11 | 35080.70 | 13-AUG-15:01 | 39.80 | 25.70 | 0.691439E+09 | 845.64 | 04-AUG-09:09 | 39.80 | 25.70 |
September | 0.168856E+11 | 32569.65 | 17-SEP-14:11 | 36.00 | 25.62 | 0.612364E+09 | 845.64 | 01-SEP-13:50 | 36.00 | 25.62 |
October | 0.138491E+11 | 31233.75 | 15-OCT-14:31 | 34.33 | 20.80 | 0.631863E+09 | 845.64 | 05-OCT-13:50 | 34.33 | 20.80 |
November | 0.101599E+11 | 12575.04 | 20-NOV-06:02 | 25.85 | 18.49 | 0.614311E+09 | 845.64 | 14-NOV-14:00 | 25.85 | 18.49 |
December | 0.743079E+10 | 8419.72 | 11-DEC-14:20 | 26.83 | 18.23 | 0.567900E+09 | 845.64 | 06-DEC-14:20 | 26.83 | 18.23 |
Annual Sum or Average | 0.163847E+12 | 0.742482E+10 | ||||||||
Minimum of Months | 0.660388E+10 | 7580.12 | 25.67 | 14.74 | 0.536680E+09 | 845.64 | 22.00 | 14.74 | ||
Maximum of Months | 0.220715E+11 | 37065.83 | 43.00 | 26.54 | 0.691439E+09 | 845.64 | 43.00 | 26.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.578426E+10 | 6902.66 | 22-JAN-14:32 | 26.00 | 16.51 | 0.267942E+09 | 529.42 | 24-JAN-11:09 | 24.00 | 18.08 |
February | 0.591691E+10 | 12473.80 | 05-FEB-10:42 | 28.72 | 18.70 | 0.252978E+09 | 548.49 | 06-FEB-15:09 | 32.32 | 17.34 |
March | 0.826851E+10 | 24374.27 | 26-MAR-10:22 | 31.00 | 16.20 | 0.309236E+09 | 548.49 | 21-MAR-12:09 | 31.00 | 16.20 |
April | 0.100659E+11 | 30899.57 | 30-APR-10:31 | 32.33 | 22.41 | 0.283463E+09 | 548.49 | 12-APR-12:09 | 32.33 | 22.41 |
May | 0.143121E+11 | 32531.55 | 07-MAY-09:31 | 35.33 | 17.61 | 0.314870E+09 | 548.49 | 15-MAY-14:09 | 32.00 | 25.14 |
June | 0.151590E+11 | 29723.45 | 11-JUN-10:12 | 38.33 | 26.65 | 0.313788E+09 | 548.49 | 30-JUN-14:09 | 34.00 | 23.44 |
July | 0.166582E+11 | 35224.04 | 30-JUL-10:11 | 43.27 | 21.89 | 0.293222E+09 | 548.49 | 05-JUL-14:09 | 43.27 | 21.89 |
August | 0.175219E+11 | 32980.12 | 13-AUG-10:21 | 38.80 | 25.02 | 0.327753E+09 | 548.49 | 21-AUG-14:09 | 35.93 | 29.69 |
September | 0.137686E+11 | 31170.78 | 24-SEP-10:31 | 35.00 | 22.41 | 0.290695E+09 | 548.49 | 22-SEP-14:09 | 35.00 | 22.41 |
October | 0.114895E+11 | 29607.68 | 15-OCT-11:11 | 34.33 | 18.54 | 0.300038E+09 | 548.49 | 31-OCT-12:09 | 30.08 | 21.31 |
November | 0.841983E+10 | 11736.01 | 02-NOV-10:05 | 30.25 | 24.15 | 0.291618E+09 | 548.49 | 03-NOV-12:09 | 31.80 | 20.89 |
December | 0.627685E+10 | 8507.76 | 01-DEC-11:05 | 27.17 | 16.31 | 0.264702E+09 | 546.00 | 01-DEC-11:09 | 27.17 | 16.31 |
Annual Sum or Average | 0.133641E+12 | 0.351031E+10 | ||||||||
Minimum of Months | 0.578426E+10 | 6902.66 | 26.00 | 16.20 | 0.252978E+09 | 529.42 | 24.00 | 16.20 | ||
Maximum of Months | 0.175219E+11 | 35224.04 | 43.27 | 26.65 | 0.327753E+09 | 548.49 | 43.27 | 29.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111086E+11 | 37006.32 | 22-JAN-14:32 | 26.00 | 16.51 | 0.605264E+09 | 845.66 | 03-JAN-14:50 | 26.00 | 16.51 |
February | 0.110387E+11 | 40477.96 | 05-FEB-13:21 | 31.35 | 19.49 | 0.552966E+09 | 845.66 | 01-FEB-14:00 | 31.35 | 19.49 |
March | 0.136541E+11 | 37639.28 | 26-MAR-14:21 | 32.80 | 18.48 | 0.662540E+09 | 845.66 | 14-MAR-13:30 | 32.80 | 18.48 |
April | 0.138466E+11 | 38322.11 | 30-APR-12:31 | 37.07 | 20.92 | 0.596174E+09 | 845.66 | 10-APR-13:00 | 37.07 | 20.92 |
May | 0.178986E+11 | 37790.09 | 07-MAY-14:11 | 37.00 | 20.10 | 0.659826E+09 | 845.66 | 12-MAY-13:09 | 35.92 | 23.17 |
June | 0.188925E+11 | 28034.24 | 11-JUN-15:31 | 36.60 | 27.14 | 0.659876E+09 | 845.66 | 09-JUN-13:09 | 36.60 | 27.14 |
July | 0.214331E+11 | 42682.04 | 30-JUL-14:11 | 43.00 | 25.45 | 0.615307E+09 | 845.66 | 03-JUL-13:30 | 43.00 | 25.45 |
August | 0.237007E+11 | 40556.41 | 13-AUG-15:01 | 39.80 | 25.70 | 0.690495E+09 | 845.66 | 02-AUG-09:30 | 39.80 | 25.70 |
September | 0.208626E+11 | 40124.53 | 17-SEP-13:31 | 36.87 | 25.68 | 0.611778E+09 | 846.17 | 29-SEP-13:20 | 36.07 | 24.99 |
October | 0.201192E+11 | 41625.24 | 15-OCT-11:51 | 35.00 | 19.70 | 0.633671E+09 | 846.18 | 03-OCT-13:20 | 35.00 | 19.70 |
November | 0.165339E+11 | 38704.21 | 05-NOV-13:12 | 33.27 | 21.09 | 0.623030E+09 | 845.66 | 14-NOV-14:09 | 29.00 | 22.52 |
December | 0.125049E+11 | 41213.30 | 03-DEC-13:11 | 28.87 | 18.94 | 0.590675E+09 | 845.66 | 04-DEC-14:09 | 27.00 | 21.00 |
Annual Sum or Average | 0.201593E+12 | 0.750160E+10 | ||||||||
Minimum of Months | 0.110387E+11 | 28034.24 | 26.00 | 16.51 | 0.552966E+09 | 845.66 | 26.00 | 16.51 | ||
Maximum of Months | 0.237007E+11 | 42682.04 | 43.00 | 27.14 | 0.690495E+09 | 846.18 | 43.00 | 27.14 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.624217E+10 | 8783.20 | 22-JAN-14:32 | 26.00 | 16.51 | 0.356948E+09 | 544.96 | 23-JAN-14:50 | 25.50 | 16.89 |
February | 0.668254E+10 | 18952.96 | 05-FEB-16:42 | 31.17 | 18.53 | 0.334797E+09 | 544.96 | 07-FEB-14:00 | 28.00 | 22.41 |
March | 0.939803E+10 | 26817.21 | 26-MAR-15:41 | 31.93 | 18.55 | 0.412051E+09 | 544.96 | 23-MAR-13:09 | 31.93 | 18.55 |
April | 0.107920E+11 | 34126.58 | 30-APR-16:31 | 31.17 | 25.64 | 0.377545E+09 | 544.96 | 03-APR-13:09 | 31.17 | 25.64 |
May | 0.148799E+11 | 36463.09 | 14-MAY-15:21 | 34.50 | 20.63 | 0.421800E+09 | 544.96 | 15-MAY-13:09 | 32.00 | 24.26 |
June | 0.161420E+11 | 32787.34 | 11-JUN-16:11 | 36.60 | 26.54 | 0.422864E+09 | 544.96 | 01-JUN-13:39 | 36.60 | 26.54 |
July | 0.177557E+11 | 39223.25 | 30-JUL-14:11 | 43.00 | 25.45 | 0.394918E+09 | 544.96 | 03-JUL-13:20 | 43.00 | 25.45 |
August | 0.186767E+11 | 38362.83 | 13-AUG-15:41 | 39.00 | 26.01 | 0.443204E+09 | 544.96 | 04-AUG-13:50 | 39.00 | 26.01 |
September | 0.146324E+11 | 34514.35 | 04-SEP-16:11 | 40.47 | 23.66 | 0.390046E+09 | 544.96 | 12-SEP-13:30 | 37.50 | 26.69 |
October | 0.123686E+11 | 34725.21 | 15-OCT-15:11 | 33.83 | 21.34 | 0.399532E+09 | 544.96 | 13-OCT-13:50 | 33.83 | 21.34 |
November | 0.946040E+10 | 13423.04 | 05-NOV-15:12 | 31.80 | 21.10 | 0.385624E+09 | 544.96 | 06-NOV-14:50 | 32.17 | 21.60 |
December | 0.717664E+10 | 9197.67 | 01-DEC-15:20 | 27.63 | 18.18 | 0.354252E+09 | 544.96 | 04-DEC-14:00 | 27.00 | 21.53 |
Annual Sum or Average | 0.144207E+12 | 0.469358E+10 | ||||||||
Minimum of Months | 0.624217E+10 | 8783.20 | 26.00 | 16.51 | 0.334797E+09 | 544.96 | 25.50 | 16.89 | ||
Maximum of Months | 0.186767E+11 | 39223.25 | 43.00 | 26.54 | 0.443204E+09 | 544.96 | 43.00 | 26.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.642156E+10 | 8018.78 | 23-JAN-14:10 | 27.50 | 16.66 | 0.543724E+09 | 845.64 | 23-JAN-14:00 | 25.00 | 16.89 |
February | 0.703827E+10 | 12166.41 | 06-FEB-15:00 | 32.50 | 17.28 | 0.517979E+09 | 845.64 | 06-FEB-14:00 | 32.50 | 17.28 |
March | 0.103743E+11 | 15080.75 | 27-MAR-13:40 | 35.33 | 19.53 | 0.641412E+09 | 845.64 | 02-MAR-14:20 | 35.33 | 19.53 |
April | 0.128516E+11 | 37120.89 | 30-APR-12:31 | 37.07 | 20.92 | 0.588963E+09 | 845.64 | 25-APR-13:39 | 37.07 | 20.92 |
May | 0.193254E+11 | 39623.68 | 21-MAY-13:02 | 38.00 | 22.80 | 0.659832E+09 | 845.64 | 15-MAY-13:09 | 38.00 | 22.80 |
June | 0.214111E+11 | 40722.33 | 25-JUN-15:31 | 34.73 | 28.24 | 0.660755E+09 | 845.64 | 06-JUN-13:09 | 34.73 | 28.24 |
July | 0.239248E+11 | 40370.29 | 30-JUL-14:21 | 42.50 | 25.87 | 0.615821E+09 | 845.64 | 13-JUL-13:50 | 42.50 | 25.87 |
August | 0.245143E+11 | 42230.25 | 06-AUG-14:51 | 41.00 | 24.84 | 0.690340E+09 | 845.64 | 02-AUG-09:50 | 41.00 | 24.84 |
September | 0.187020E+11 | 43664.05 | 04-SEP-14:41 | 41.00 | 24.39 | 0.609414E+09 | 845.64 | 08-SEP-13:30 | 35.25 | 29.34 |
October | 0.149911E+11 | 32501.09 | 09-OCT-13:31 | 37.20 | 20.23 | 0.624661E+09 | 845.64 | 02-OCT-13:39 | 37.20 | 20.23 |
November | 0.106212E+11 | 20040.50 | 05-NOV-14:21 | 32.50 | 21.12 | 0.601423E+09 | 845.64 | 02-NOV-13:30 | 32.50 | 21.12 |
December | 0.738607E+10 | 9536.58 | 03-DEC-13:42 | 27.47 | 20.47 | 0.544543E+09 | 845.64 | 01-DEC-14:50 | 27.47 | 20.47 |
Annual Sum or Average | 0.177562E+12 | 0.729887E+10 | ||||||||
Minimum of Months | 0.642156E+10 | 8018.78 | 27.47 | 16.66 | 0.517979E+09 | 845.64 | 25.00 | 16.89 | ||
Maximum of Months | 0.245143E+11 | 43664.05 | 42.50 | 28.24 | 0.690340E+09 | 845.64 | 42.50 | 29.34 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.541000E+10 | 6824.38 | 29-JAN-10:42 | 25.72 | 18.92 | 0.359115E+09 | 544.50 | 24-JAN-10:00 | 25.72 | 18.92 |
February | 0.578599E+10 | 10392.12 | 05-FEB-10:35 | 28.43 | 18.68 | 0.342866E+09 | 544.96 | 16-FEB-14:30 | 25.00 | 18.22 |
March | 0.844220E+10 | 13734.77 | 27-MAR-10:50 | 37.50 | 18.71 | 0.420727E+09 | 544.96 | 22-MAR-13:30 | 37.50 | 18.71 |
April | 0.107389E+11 | 32726.27 | 23-APR-09:51 | 32.70 | 16.87 | 0.383879E+09 | 544.96 | 21-APR-13:09 | 32.70 | 16.87 |
May | 0.156224E+11 | 31932.76 | 21-MAY-10:22 | 38.15 | 20.67 | 0.426261E+09 | 544.96 | 01-MAY-13:39 | 38.15 | 20.67 |
June | 0.166315E+11 | 32654.15 | 25-JUN-09:31 | 32.87 | 26.66 | 0.425517E+09 | 544.96 | 19-JUN-13:09 | 32.87 | 26.66 |
July | 0.184181E+11 | 33368.51 | 30-JUL-10:21 | 43.70 | 22.01 | 0.396321E+09 | 544.96 | 25-JUL-13:20 | 43.70 | 22.01 |
August | 0.192283E+11 | 33772.67 | 06-AUG-14:51 | 41.00 | 24.84 | 0.444453E+09 | 544.96 | 25-AUG-13:00 | 36.00 | 28.42 |
September | 0.150386E+11 | 35058.94 | 04-SEP-14:41 | 41.00 | 24.39 | 0.393403E+09 | 544.96 | 14-SEP-13:50 | 38.15 | 25.47 |
October | 0.122611E+11 | 28200.82 | 29-OCT-13:21 | 34.55 | 17.47 | 0.405689E+09 | 544.96 | 10-OCT-13:50 | 34.55 | 17.47 |
November | 0.864062E+10 | 21102.85 | 05-NOV-11:01 | 32.58 | 18.45 | 0.394717E+09 | 544.96 | 17-NOV-14:09 | 29.00 | 19.38 |
December | 0.600286E+10 | 8062.00 | 03-DEC-13:01 | 29.33 | 18.32 | 0.356158E+09 | 544.96 | 01-DEC-14:09 | 29.33 | 18.32 |
Annual Sum or Average | 0.142221E+12 | 0.474910E+10 | ||||||||
Minimum of Months | 0.541000E+10 | 6824.38 | 25.72 | 16.87 | 0.342866E+09 | 544.50 | 25.00 | 16.87 | ||
Maximum of Months | 0.192283E+11 | 35058.94 | 43.70 | 26.66 | 0.444453E+09 | 544.96 | 43.70 | 28.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105431E+11 | 35211.93 | 22-JAN-14:22 | 26.00 | 16.36 | 0.588589E+09 | 845.66 | 05-JAN-14:09 | 26.00 | 16.36 |
February | 0.108961E+11 | 46191.05 | 05-FEB-13:51 | 31.60 | 19.33 | 0.540603E+09 | 845.66 | 14-FEB-14:39 | 23.00 | 16.25 |
March | 0.139061E+11 | 34498.69 | 26-MAR-15:12 | 32.33 | 18.58 | 0.649466E+09 | 845.66 | 07-MAR-14:00 | 32.33 | 18.58 |
April | 0.148125E+11 | 44687.13 | 30-APR-12:31 | 37.07 | 20.92 | 0.586445E+09 | 845.66 | 03-APR-13:00 | 37.07 | 20.92 |
May | 0.197552E+11 | 43992.93 | 21-MAY-13:02 | 38.00 | 22.80 | 0.655370E+09 | 845.66 | 19-MAY-13:39 | 38.00 | 22.80 |
June | 0.209717E+11 | 43957.56 | 25-JUN-15:31 | 34.73 | 28.24 | 0.657171E+09 | 845.66 | 01-JUN-13:39 | 34.73 | 28.24 |
July | 0.240043E+11 | 44998.81 | 30-JUL-14:21 | 42.50 | 25.87 | 0.613986E+09 | 845.66 | 18-JUL-13:50 | 42.50 | 25.87 |
August | 0.261322E+11 | 47460.24 | 06-AUG-14:11 | 40.33 | 25.76 | 0.688934E+09 | 845.66 | 14-AUG-13:39 | 37.90 | 26.71 |
September | 0.226510E+11 | 51105.80 | 04-SEP-14:41 | 41.00 | 24.39 | 0.608612E+09 | 845.66 | 05-SEP-13:39 | 40.30 | 24.57 |
October | 0.211410E+11 | 49605.48 | 29-OCT-13:21 | 34.55 | 17.47 | 0.628287E+09 | 845.66 | 06-OCT-13:20 | 34.55 | 17.47 |
November | 0.167466E+11 | 49064.29 | 05-NOV-12:21 | 33.70 | 19.11 | 0.615586E+09 | 845.66 | 02-NOV-13:30 | 33.70 | 19.11 |
December | 0.121000E+11 | 46812.06 | 03-DEC-13:01 | 29.33 | 18.32 | 0.576482E+09 | 845.66 | 04-DEC-14:09 | 27.00 | 21.00 |
Annual Sum or Average | 0.213660E+12 | 0.740953E+10 | ||||||||
Minimum of Months | 0.105431E+11 | 34498.69 | 26.00 | 16.36 | 0.540603E+09 | 845.66 | 23.00 | 16.25 | ||
Maximum of Months | 0.261322E+11 | 51105.80 | 42.50 | 28.24 | 0.688934E+09 | 845.66 | 42.50 | 28.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.588920E+10 | 7915.15 | 29-JAN-16:45 | 25.17 | 20.20 | 0.347456E+09 | 544.95 | 23-JAN-14:30 | 25.17 | 20.20 |
February | 0.656347E+10 | 23478.51 | 05-FEB-16:32 | 31.33 | 18.61 | 0.327893E+09 | 544.96 | 07-FEB-14:00 | 28.00 | 22.41 |
March | 0.956111E+10 | 24054.29 | 26-MAR-15:52 | 31.80 | 18.54 | 0.403610E+09 | 544.96 | 27-MAR-13:39 | 35.33 | 19.53 |
April | 0.113949E+11 | 38305.01 | 30-APR-16:31 | 31.17 | 25.64 | 0.371240E+09 | 544.96 | 03-APR-13:50 | 31.17 | 25.64 |
May | 0.160698E+11 | 38072.41 | 21-MAY-15:41 | 37.42 | 23.35 | 0.417962E+09 | 544.96 | 02-MAY-13:30 | 37.42 | 23.35 |
June | 0.174778E+11 | 41410.36 | 25-JUN-16:11 | 34.73 | 28.04 | 0.420234E+09 | 544.96 | 06-JUN-13:39 | 34.73 | 28.04 |
July | 0.193998E+11 | 39190.44 | 30-JUL-14:21 | 42.50 | 25.87 | 0.393214E+09 | 544.96 | 25-JUL-13:09 | 42.50 | 25.87 |
August | 0.202240E+11 | 43699.00 | 06-AUG-15:31 | 40.40 | 25.42 | 0.441253E+09 | 544.96 | 18-AUG-13:30 | 38.50 | 26.63 |
September | 0.158084E+11 | 44912.21 | 04-SEP-15:21 | 40.85 | 24.13 | 0.386601E+09 | 544.96 | 18-SEP-13:00 | 36.00 | 25.62 |
October | 0.130735E+11 | 36921.02 | 29-OCT-15:21 | 32.00 | 19.85 | 0.393836E+09 | 544.96 | 13-OCT-13:09 | 32.00 | 19.85 |
November | 0.964576E+10 | 36126.55 | 05-NOV-14:21 | 32.50 | 21.12 | 0.378416E+09 | 544.96 | 01-NOV-13:39 | 32.50 | 21.12 |
December | 0.693003E+10 | 10164.85 | 03-DEC-14:22 | 27.00 | 20.88 | 0.345444E+09 | 544.96 | 04-DEC-14:00 | 27.00 | 21.53 |
Annual Sum or Average | 0.152038E+12 | 0.462716E+10 | ||||||||
Minimum of Months | 0.588920E+10 | 7915.15 | 25.17 | 18.54 | 0.327893E+09 | 544.95 | 25.17 | 19.53 | ||
Maximum of Months | 0.202240E+11 | 44912.21 | 42.50 | 28.04 | 0.441253E+09 | 544.96 | 42.50 | 28.04 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.849065E+10 | 13783.60 | 02-JAN-06:13 | 13.00 | 10.85 | 0.00 | 0.00 | 01-JAN-00:10 | 13.00 | 10.85 |
February | 0.869988E+10 | 12795.07 | 21-FEB-06:13 | 13.90 | 13.23 | 0.00 | 0.00 | 01-FEB-00:10 | 13.90 | 13.23 |
March | 0.115292E+11 | 11649.95 | 27-MAR-05:13 | 21.93 | 13.41 | 0.00 | 0.00 | 01-MAR-00:10 | 21.93 | 13.41 |
April | 0.123704E+11 | 11824.24 | 17-APR-05:12 | 24.00 | 19.15 | 0.00 | 0.00 | 01-APR-00:10 | 24.00 | 19.15 |
May | 0.140871E+11 | 12939.77 | 09-MAY-05:02 | 26.00 | 19.74 | 0.00 | 0.00 | 01-MAY-00:10 | 26.00 | 19.74 |
June | 0.149416E+11 | 12024.68 | 12-JUN-13:30 | 38.95 | 27.59 | 0.00 | 0.00 | 01-JUN-00:10 | 38.95 | 27.59 |
July | 0.162086E+11 | 13008.17 | 31-JUL-15:20 | 39.90 | 26.27 | 0.00 | 0.00 | 01-JUL-00:10 | 39.90 | 26.27 |
August | 0.177894E+11 | 14639.07 | 07-AUG-05:15 | 32.63 | 23.12 | 0.00 | 0.00 | 01-AUG-00:10 | 32.63 | 23.12 |
September | 0.141446E+11 | 13742.21 | 05-SEP-14:00 | 40.00 | 25.05 | 0.00 | 0.00 | 01-SEP-00:10 | 40.00 | 25.05 |
October | 0.137787E+11 | 12928.25 | 16-OCT-05:13 | 25.67 | 23.52 | 0.00 | 0.00 | 01-OCT-00:10 | 25.67 | 23.52 |
November | 0.122024E+11 | 14139.55 | 06-NOV-06:13 | 20.03 | 17.51 | 0.00 | 0.00 | 01-NOV-00:10 | 20.03 | 17.51 |
December | 0.104885E+11 | 12956.22 | 26-DEC-06:13 | 14.60 | 14.60 | 0.00 | 0.00 | 01-DEC-00:10 | 14.60 | 14.60 |
Annual Sum or Average | 0.154731E+12 | 0.00 | ||||||||
Minimum of Months | 0.849065E+10 | 11649.95 | 13.00 | 10.85 | 0.00 | 0.00 | 13.00 | 10.85 | ||
Maximum of Months | 0.177894E+11 | 14639.07 | 40.00 | 27.59 | 0.00 | 0.00 | 40.00 | 27.59 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.496036E+10 | 9938.93 | 02-JAN-05:18 | 13.67 | 11.10 | 0.00 | 0.00 | 01-JAN-00:10 | 13.67 | 11.10 |
February | 0.561075E+10 | 8941.23 | 21-FEB-05:19 | 14.67 | 13.69 | 0.00 | 0.00 | 01-FEB-00:10 | 14.67 | 13.69 |
March | 0.816646E+10 | 9797.38 | 31-MAR-05:13 | 16.70 | 15.52 | 0.00 | 0.00 | 01-MAR-00:10 | 16.70 | 15.52 |
April | 0.932425E+10 | 11426.89 | 29-APR-05:13 | 25.00 | 16.37 | 0.00 | 0.00 | 01-APR-00:10 | 25.00 | 16.37 |
May | 0.124847E+11 | 12059.17 | 09-MAY-05:02 | 26.00 | 19.74 | 0.00 | 0.00 | 01-MAY-00:10 | 26.00 | 19.74 |
June | 0.130576E+11 | 11498.51 | 03-JUN-05:13 | 27.00 | 18.25 | 0.00 | 0.00 | 01-JUN-00:10 | 27.00 | 18.25 |
July | 0.135786E+11 | 11315.33 | 21-JUL-15:50 | 42.25 | 24.88 | 0.00 | 0.00 | 01-JUL-00:10 | 42.25 | 24.88 |
August | 0.146647E+11 | 11532.97 | 16-AUG-14:20 | 42.67 | 27.36 | 0.00 | 0.00 | 01-AUG-00:10 | 42.67 | 27.36 |
September | 0.124813E+11 | 11861.93 | 27-SEP-05:02 | 26.00 | 23.06 | 0.00 | 0.00 | 01-SEP-00:10 | 26.00 | 23.06 |
October | 0.115219E+11 | 11392.54 | 19-OCT-05:02 | 24.00 | 20.04 | 0.00 | 0.00 | 01-OCT-00:10 | 24.00 | 20.04 |
November | 0.925727E+10 | 10412.75 | 13-NOV-06:12 | 20.83 | 17.71 | 0.00 | 0.00 | 01-NOV-00:10 | 20.83 | 17.71 |
December | 0.638973E+10 | 9350.95 | 13-DEC-05:18 | 15.67 | 12.93 | 0.00 | 0.00 | 01-DEC-00:10 | 15.67 | 12.93 |
Annual Sum or Average | 0.121498E+12 | 0.00 | ||||||||
Minimum of Months | 0.496036E+10 | 8941.23 | 13.67 | 11.10 | 0.00 | 0.00 | 13.67 | 11.10 | ||
Maximum of Months | 0.146647E+11 | 12059.17 | 42.67 | 27.36 | 0.00 | 0.00 | 42.67 | 27.36 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.910967E+10 | 19025.27 | 31-JAN-13:50 | 23.15 | 16.15 | 0.00 | 0.00 | 01-JAN-00:10 | 23.15 | 16.15 |
February | 0.113444E+11 | 26926.24 | 07-FEB-14:05 | 30.50 | 20.52 | 0.00 | 0.00 | 01-FEB-00:10 | 30.50 | 20.52 |
March | 0.174377E+11 | 34774.07 | 27-MAR-13:05 | 35.83 | 19.71 | 0.00 | 0.00 | 01-MAR-00:10 | 35.83 | 19.71 |
April | 0.221404E+11 | 39848.89 | 30-APR-12:31 | 37.07 | 20.92 | 0.00 | 0.00 | 01-APR-00:10 | 37.07 | 20.92 |
May | 0.320519E+11 | 42208.29 | 10-MAY-14:20 | 40.00 | 20.19 | 0.00 | 0.00 | 01-MAY-00:10 | 40.00 | 20.19 |
June | 0.343165E+11 | 41820.51 | 27-JUN-12:40 | 39.60 | 26.40 | 0.00 | 0.00 | 01-JUN-00:10 | 39.60 | 26.40 |
July | 0.373784E+11 | 46031.44 | 21-JUL-12:05 | 45.38 | 23.17 | 0.00 | 0.00 | 01-JUL-00:10 | 45.38 | 23.17 |
August | 0.385738E+11 | 45811.75 | 16-AUG-13:05 | 44.17 | 25.68 | 0.00 | 0.00 | 01-AUG-00:10 | 44.17 | 25.68 |
September | 0.301186E+11 | 41278.07 | 05-SEP-13:05 | 40.75 | 23.81 | 0.00 | 0.00 | 01-SEP-00:10 | 40.75 | 23.81 |
October | 0.242257E+11 | 35895.99 | 04-OCT-13:05 | 36.50 | 20.99 | 0.00 | 0.00 | 01-OCT-00:10 | 36.50 | 20.99 |
November | 0.165220E+11 | 28664.85 | 01-NOV-13:30 | 32.70 | 26.16 | 0.00 | 0.00 | 01-NOV-00:10 | 32.70 | 26.16 |
December | 0.106107E+11 | 21442.85 | 04-DEC-13:10 | 27.83 | 21.18 | 0.00 | 0.00 | 01-DEC-00:10 | 27.83 | 21.18 |
Annual Sum or Average | 0.283830E+12 | 0.00 | ||||||||
Minimum of Months | 0.910967E+10 | 19025.27 | 23.15 | 16.15 | 0.00 | 0.00 | 23.15 | 16.15 | ||
Maximum of Months | 0.385738E+11 | 46031.44 | 45.38 | 26.40 | 0.00 | 0.00 | 45.38 | 26.40 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.420451E+10 | 2096.29 | 03-JAN-17:00 | 21.00 | 14.04 | 95237130.04 | 126.85 | 30-JAN-14:00 | 22.00 | 20.56 |
February | 0.859230E+10 | 4079.59 | 06-FEB-15:50 | 31.58 | 17.52 | 86402367.63 | 126.84 | 09-FEB-10:09 | 23.92 | 19.44 |
March | 0.147922E+11 | 7269.70 | 31-MAR-24:00 | 22.30 | 20.22 | 0.103239E+09 | 126.83 | 24-MAR-09:09 | 22.30 | 20.22 |
April | 0.192543E+11 | 7983.85 | 27-APR-16:00 | 35.70 | 22.76 | 91606076.70 | 126.83 | 28-APR-13:00 | 35.00 | 23.22 |
May | 0.490845E+10 | 3517.74 | 31-MAY-23:31 | 32.83 | 23.29 | 99242665.22 | 126.86 | 01-MAY-09:09 | 32.83 | 23.29 |
June | 0.965032E+10 | 5369.94 | 30-JUN-23:46 | 31.63 | 26.77 | 98967231.57 | 126.85 | 08-JUN-09:09 | 31.63 | 26.77 |
July | 0.150565E+11 | 7259.15 | 31-JUL-23:21 | 33.50 | 28.49 | 91884487.07 | 126.83 | 26-JUL-09:09 | 33.50 | 28.49 |
August | 0.201660E+11 | 8065.92 | 10-AUG-16:00 | 41.60 | 30.36 | 0.103243E+09 | 126.83 | 03-AUG-13:00 | 41.60 | 30.36 |
September | 0.476678E+10 | 3471.77 | 30-SEP-23:04 | 29.00 | 26.32 | 91615050.01 | 126.85 | 07-SEP-09:09 | 29.00 | 26.32 |
October | 0.992246E+10 | 5390.43 | 31-OCT-23:42 | 27.43 | 21.16 | 95240019.81 | 126.85 | 17-OCT-09:09 | 27.43 | 21.16 |
November | 0.144355E+11 | 6054.96 | 06-NOV-16:50 | 30.23 | 22.29 | 94304587.00 | 126.83 | 01-NOV-09:09 | 30.23 | 22.29 |
December | 0.197631E+11 | 7891.71 | 05-DEC-17:00 | 26.00 | 23.18 | 91881403.67 | 126.82 | 05-DEC-14:00 | 26.00 | 23.18 |
Annual Sum or Average | 0.145512E+12 | 0.114286E+10 | ||||||||
Minimum of Months | 0.420451E+10 | 2096.29 | 21.00 | 14.04 | 86402367.63 | 126.82 | 22.00 | 19.44 | ||
Maximum of Months | 0.201660E+11 | 8065.92 | 41.60 | 30.36 | 0.103243E+09 | 126.86 | 41.60 | 30.36 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.317711E+10 | 1912.34 | 31-JAN-17:00 | 23.00 | 17.31 | 95236720.65 | 126.85 | 30-JAN-14:00 | 23.00 | 17.31 |
February | 0.752471E+10 | 3810.56 | 07-FEB-17:00 | 28.00 | 21.23 | 86402541.06 | 126.84 | 09-FEB-10:39 | 24.57 | 19.20 |
March | 0.136141E+11 | 6821.07 | 31-MAR-24:00 | 22.30 | 20.22 | 0.103240E+09 | 126.83 | 29-MAR-09:09 | 22.30 | 20.22 |
April | 0.181747E+11 | 7604.84 | 27-APR-16:00 | 35.70 | 22.76 | 91606135.00 | 126.83 | 28-APR-13:00 | 35.00 | 23.22 |
May | 0.455314E+10 | 3404.41 | 31-MAY-23:44 | 32.77 | 23.34 | 99242353.44 | 126.85 | 30-MAY-13:09 | 32.77 | 23.34 |
June | 0.915244E+10 | 5193.36 | 30-JUN-23:16 | 31.43 | 26.51 | 98967729.51 | 126.85 | 20-JUN-09:09 | 31.43 | 26.51 |
July | 0.142750E+11 | 7027.36 | 31-JUL-23:43 | 33.37 | 28.37 | 91884721.06 | 126.83 | 26-JUL-09:09 | 33.37 | 28.37 |
August | 0.191635E+11 | 7676.69 | 10-AUG-16:00 | 41.60 | 30.36 | 0.103243E+09 | 126.83 | 08-AUG-13:00 | 41.60 | 30.36 |
September | 0.440061E+10 | 3407.67 | 30-SEP-24:00 | 29.00 | 26.44 | 91614070.21 | 126.85 | 06-SEP-09:00 | 29.00 | 26.44 |
October | 0.929973E+10 | 5164.10 | 31-OCT-24:00 | 27.40 | 21.22 | 95240532.25 | 126.85 | 06-OCT-09:00 | 27.40 | 21.22 |
November | 0.133806E+11 | 5724.13 | 06-NOV-17:00 | 30.00 | 22.38 | 94305106.33 | 126.83 | 01-NOV-09:09 | 30.00 | 22.38 |
December | 0.180898E+11 | 7444.84 | 06-DEC-17:00 | 26.00 | 20.50 | 91881615.66 | 126.82 | 15-DEC-10:09 | 19.67 | 18.50 |
Annual Sum or Average | 0.134805E+12 | 0.114286E+10 | ||||||||
Minimum of Months | 0.317711E+10 | 1912.34 | 22.30 | 17.31 | 86402541.06 | 126.82 | 19.67 | 17.31 | ||
Maximum of Months | 0.191635E+11 | 7676.69 | 41.60 | 30.36 | 0.103243E+09 | 126.85 | 41.60 | 30.36 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243200E+10 | 1973.80 | 31-JAN-17:00 | 23.00 | 17.31 | 95236753.52 | 126.85 | 30-JAN-14:00 | 23.00 | 17.31 |
February | 0.706688E+10 | 3952.21 | 06-FEB-16:00 | 31.40 | 17.56 | 86402758.86 | 126.84 | 09-FEB-14:00 | 23.00 | 20.24 |
March | 0.133339E+11 | 6661.44 | 31-MAR-24:00 | 22.30 | 20.22 | 0.103240E+09 | 126.83 | 29-MAR-09:09 | 22.30 | 20.22 |
April | 0.181495E+11 | 7809.23 | 27-APR-16:00 | 35.70 | 22.76 | 91606059.37 | 126.82 | 05-APR-09:09 | 35.70 | 22.76 |
May | 0.471511E+10 | 3444.34 | 31-MAY-23:44 | 32.77 | 23.34 | 99241814.87 | 126.85 | 16-MAY-13:00 | 32.77 | 23.34 |
June | 0.935839E+10 | 5201.08 | 30-JUN-23:14 | 31.43 | 26.51 | 98967679.10 | 126.85 | 20-JUN-09:09 | 31.43 | 26.51 |
July | 0.145655E+11 | 7059.21 | 31-JUL-23:35 | 33.43 | 28.43 | 91885503.92 | 126.84 | 26-JUL-09:09 | 33.43 | 28.43 |
August | 0.194248E+11 | 8038.75 | 06-AUG-16:40 | 40.03 | 26.01 | 0.103241E+09 | 126.83 | 03-AUG-13:00 | 40.03 | 26.01 |
September | 0.455861E+10 | 3433.44 | 30-SEP-24:00 | 29.00 | 26.44 | 91613580.04 | 126.85 | 06-SEP-09:00 | 29.00 | 26.44 |
October | 0.933060E+10 | 5105.05 | 31-OCT-24:00 | 27.40 | 21.22 | 95240612.78 | 126.85 | 06-OCT-09:00 | 27.40 | 21.22 |
November | 0.131490E+11 | 5826.39 | 01-NOV-16:00 | 32.00 | 25.92 | 94305678.94 | 126.83 | 01-NOV-09:09 | 32.00 | 25.92 |
December | 0.175170E+11 | 7523.27 | 06-DEC-16:50 | 26.12 | 20.49 | 91882302.98 | 126.83 | 26-DEC-10:09 | 21.33 | 18.45 |
Annual Sum or Average | 0.133601E+12 | 0.114286E+10 | ||||||||
Minimum of Months | 0.243200E+10 | 1973.80 | 22.30 | 17.31 | 86402758.86 | 126.82 | 21.33 | 17.31 | ||
Maximum of Months | 0.194248E+11 | 8038.75 | 40.03 | 28.43 | 0.103241E+09 | 126.85 | 40.03 | 28.43 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245184E+12 | 95236.85 | 31-JAN-17:00 | 23.00 | 17.31 | 0.206112E+10 | 2745.21 | 02-JAN-10:30 | 23.00 | 17.31 |
February | 0.441855E+12 | 186856.02 | 07-FEB-17:00 | 28.00 | 21.23 | 0.186869E+10 | 2744.48 | 08-FEB-14:50 | 28.50 | 20.28 |
March | 0.734673E+12 | 360658.01 | 31-MAR-24:00 | 22.30 | 20.22 | 0.223153E+10 | 2743.85 | 21-MAR-09:20 | 22.30 | 20.22 |
April | 0.946820E+12 | 384179.46 | 29-APR-05:07 | 25.00 | 16.37 | 0.197984E+10 | 2798.04 | 26-APR-09:09 | 25.00 | 16.37 |
May | 0.245639E+12 | 177716.57 | 31-MAY-24:00 | 32.70 | 23.39 | 0.214776E+10 | 2745.15 | 03-MAY-09:20 | 32.70 | 23.39 |
June | 0.474767E+12 | 269394.61 | 30-JUN-23:55 | 31.70 | 26.86 | 0.213998E+10 | 2744.55 | 16-JUN-13:20 | 31.70 | 26.86 |
July | 0.736886E+12 | 361687.22 | 31-JUL-23:52 | 33.30 | 28.31 | 0.198577E+10 | 2743.30 | 21-JUL-09:20 | 33.30 | 28.31 |
August | 0.984198E+12 | 371758.02 | 17-AUG-16:00 | 39.70 | 25.67 | 0.223009E+10 | 2741.63 | 15-AUG-09:20 | 39.70 | 25.67 |
September | 0.241519E+12 | 177867.65 | 30-SEP-24:00 | 29.00 | 26.44 | 0.198245E+10 | 2745.19 | 12-SEP-13:20 | 29.00 | 26.44 |
October | 0.494364E+12 | 270949.88 | 31-OCT-24:00 | 27.40 | 21.22 | 0.205958E+10 | 2744.58 | 11-OCT-13:20 | 27.40 | 21.22 |
November | 0.715970E+12 | 280213.46 | 07-NOV-17:00 | 29.00 | 24.59 | 0.203807E+10 | 2743.35 | 13-NOV-14:20 | 33.00 | 16.90 |
December | 0.983507E+12 | 374419.50 | 31-DEC-16:58 | 23.00 | 16.26 | 0.198515E+10 | 2742.71 | 29-DEC-10:09 | 23.00 | 16.26 |
Annual Sum or Average | 0.724538E+13 | 0.247100E+11 | ||||||||
Minimum of Months | 0.241519E+12 | 95236.85 | 22.30 | 16.26 | 0.186869E+10 | 2741.63 | 22.30 | 16.26 | ||
Maximum of Months | 0.984198E+12 | 384179.46 | 39.70 | 28.31 | 0.223153E+10 | 2798.04 | 39.70 | 28.31 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 238235.09 | 980.51 | 28-JAN-17:03 | 23.83 |
February | 15481015.03 | 6695.52 | 04-FEB-17:03 | 27.83 |
March | 27342260.47 | 9925.26 | 02-MAR-06:06 | 28.80 |
April | 0.140346E+09 | 18101.13 | 29-APR-16:02 | 35.33 |
May | 0.214646E+09 | 19193.99 | 20-MAY-16:02 | 36.17 |
June | 0.210790E+09 | 20685.54 | 03-JUN-16:02 | 37.08 |
July | 0.274221E+09 | 25760.97 | 29-JUL-16:01 | 40.58 |
August | 0.213890E+09 | 25162.15 | 05-AUG-16:01 | 40.08 |
September | 0.197481E+09 | 20251.10 | 02-SEP-16:02 | 36.92 |
October | 0.145053E+09 | 16324.78 | 07-OCT-16:03 | 34.33 |
November | 53765039.80 | 12203.87 | 04-NOV-16:03 | 31.58 |
December | 16262737.41 | 5166.57 | 09-DEC-17:03 | 26.83 |
Annual Sum or Average | 0.150952E+10 | |||
Minimum of Months | 238235.09 | 980.51 | 23.83 | |
Maximum of Months | 0.274221E+09 | 25760.97 | 40.58 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2717607.58 | 2991.96 | 20-JAN-06:10 | 12.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 2717607.58 | |||
Minimum of Months | 0.00 | 0.00 | 12.00 | |
Maximum of Months | 2717607.58 | 2991.96 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 42589676.40 | 4049.61 | 03-JAN-06:06 | 12.93 |
February | 22201712.03 | 3964.90 | 22-FEB-06:08 | 13.10 |
March | 4538848.29 | 3303.68 | 07-MAR-06:05 | 14.05 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 27.12 |
December | 14546345.74 | 3757.00 | 20-DEC-06:06 | 14.97 |
Annual Sum or Average | 83876582.46 | |||
Minimum of Months | 0.00 | 0.00 | 12.93 | |
Maximum of Months | 42589676.40 | 4049.61 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 47878671.77 | 5040.51 | 03-JAN-06:08 | 12.93 |
February | 8464559.60 | 4424.46 | 01-FEB-06:10 | 13.02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 27.12 |
December | 1139620.91 | 3527.79 | 30-DEC-06:47 | 13.17 |
Annual Sum or Average | 57482852.28 | |||
Minimum of Months | 0.00 | 0.00 | 12.93 | |
Maximum of Months | 47878671.77 | 5040.51 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 25322203.30 | 3711.52 | 19-JAN-06:08 | 12.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 25322203.30 | |||
Minimum of Months | 0.00 | 0.00 | 12.83 | |
Maximum of Months | 25322203.30 | 3711.52 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 92251565.58 | 4339.25 | 03-JAN-06:04 | 12.93 |
February | 49282874.44 | 4295.35 | 01-FEB-06:06 | 13.02 |
March | 21250198.85 | 3402.71 | 08-MAR-06:08 | 14.07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 27.12 |
December | 51109012.66 | 4001.60 | 26-DEC-06:08 | 14.80 |
Annual Sum or Average | 0.213894E+09 | |||
Minimum of Months | 0.00 | 0.00 | 12.93 | |
Maximum of Months | 92251565.58 | 4339.25 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108441E+09 | 5496.06 | 02-JAN-05:20 | 13.67 |
February | 59481376.39 | 5206.86 | 21-FEB-05:20 | 14.67 |
March | 44977081.09 | 3911.00 | 11-MAR-06:06 | 15.92 |
April | 8815123.34 | 3432.24 | 05-APR-05:10 | 17.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 3938841.34 | 3561.39 | 27-NOV-06:10 | 17.90 |
December | 73136157.54 | 3978.41 | 26-DEC-06:06 | 14.80 |
Annual Sum or Average | 0.298789E+09 | |||
Minimum of Months | 0.00 | 0.00 | 13.67 | |
Maximum of Months | 0.108441E+09 | 5496.06 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 71097387.19 | 4469.15 | 27-JAN-06:06 | 13.03 |
February | 46912642.71 | 4741.66 | 01-FEB-06:06 | 13.02 |
March | 27162877.32 | 4236.84 | 11-MAR-06:08 | 15.92 |
April | 1657144.50 | 2648.09 | 05-APR-05:47 | 17.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 1276080.40 | 3597.50 | 22-NOV-06:13 | 16.97 |
December | 39024869.04 | 4160.58 | 22-DEC-06:08 | 15.83 |
Annual Sum or Average | 0.187131E+09 | |||
Minimum of Months | 0.00 | 0.00 | 13.02 | |
Maximum of Months | 71097387.19 | 4741.66 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126328E+09 | 4384.45 | 02-JAN-05:40 | 13.33 |
February | 75757110.74 | 4744.15 | 23-FEB-06:03 | 16.02 |
March | 50685657.49 | 3920.51 | 11-MAR-06:06 | 15.92 |
April | 9512221.72 | 3494.30 | 05-APR-05:10 | 17.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 6405129.01 | 3636.61 | 27-NOV-06:10 | 17.90 |
December | 78229538.71 | 4103.40 | 20-DEC-06:06 | 14.97 |
Annual Sum or Average | 0.346918E+09 | |||
Minimum of Months | 0.00 | 0.00 | 13.33 | |
Maximum of Months | 0.126328E+09 | 4744.15 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151370E+09 | 14594.39 | 03-JAN-06:02 | 12.93 |
February | 42462532.29 | 12007.50 | 22-FEB-06:02 | 13.10 |
March | 1997748.08 | 1272.95 | 11-MAR-06:04 | 15.92 |
April | 268934.48 | 802.15 | 01-APR-05:10 | 17.83 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 125708.36 | 695.78 | 28-NOV-06:10 | 18.90 |
December | 33836174.28 | 11035.96 | 18-DEC-06:03 | 13.17 |
Annual Sum or Average | 0.230061E+09 | |||
Minimum of Months | 0.00 | 0.00 | 12.93 | |
Maximum of Months | 0.151370E+09 | 14594.39 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 84885286.47 | 9138.80 | 03-JAN-06:02 | 12.93 |
February | 26826798.75 | 8291.11 | 22-FEB-06:02 | 13.10 |
March | 3254298.34 | 1749.29 | 03-MAR-06:08 | 19.53 |
April | 1166320.15 | 1834.00 | 06-APR-05:10 | 21.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 1132971.34 | 1520.61 | 16-NOV-06:10 | 19.97 |
December | 23018239.75 | 6743.89 | 18-DEC-06:03 | 13.17 |
Annual Sum or Average | 0.140284E+09 | |||
Minimum of Months | 0.00 | 0.00 | 12.93 | |
Maximum of Months | 84885286.47 | 9138.80 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 80925245.95 | 13514.72 | 03-JAN-06:02 | 12.93 |
February | 23961833.96 | 9960.37 | 13-FEB-06:03 | 13.03 |
March | 1368036.73 | 1938.93 | 03-MAR-06:10 | 19.53 |
April | 483462.59 | 1403.08 | 13-APR-05:10 | 18.83 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 66711.84 | 555.93 | 28-NOV-06:10 | 18.90 |
December | 12788678.28 | 7580.85 | 18-DEC-06:03 | 13.17 |
Annual Sum or Average | 0.119594E+09 | |||
Minimum of Months | 0.00 | 0.00 | 12.93 | |
Maximum of Months | 80925245.95 | 13514.72 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 51765534.05 | 7296.11 | 03-JAN-06:02 | 12.93 |
February | 11527335.31 | 4929.49 | 13-FEB-06:03 | 13.03 |
March | 2622447.20 | 2153.52 | 30-MAR-05:10 | 19.00 |
April | 1123480.78 | 2083.70 | 06-APR-05:10 | 21.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 1413939.14 | 1857.88 | 15-NOV-06:10 | 19.98 |
December | 6986974.35 | 2817.16 | 18-DEC-06:03 | 13.17 |
Annual Sum or Average | 75439710.81 | |||
Minimum of Months | 0.00 | 0.00 | 12.93 | |
Maximum of Months | 51765534.05 | 7296.11 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.254882E+10 | 149584.17 | 28-JAN-06:40 | 13.60 |
February | 0.534562E+09 | 95099.54 | 22-FEB-06:45 | 13.50 |
March | 0.125350E+09 | 36099.21 | 08-MAR-07:00 | 14.40 |
April | 0.112049E+09 | 14429.89 | 02-APR-14:01 | 33.83 |
May | 0.117725E+09 | 13852.13 | 21-MAY-14:02 | 37.83 |
June | 0.135828E+09 | 15611.12 | 11-JUN-14:41 | 36.97 |
July | 0.161554E+09 | 19870.62 | 30-JUL-14:01 | 43.50 |
August | 0.111911E+09 | 18486.46 | 06-AUG-15:01 | 40.85 |
September | 0.153213E+09 | 18111.88 | 03-SEP-14:31 | 38.67 |
October | 0.146976E+09 | 15672.37 | 09-OCT-14:01 | 37.00 |
November | 0.102276E+09 | 11473.46 | 05-NOV-14:21 | 32.50 |
December | 0.303212E+09 | 92216.13 | 30-DEC-06:47 | 13.17 |
Annual Sum or Average | 0.455348E+10 | |||
Minimum of Months | 0.102276E+09 | 11473.46 | 13.17 | |
Maximum of Months | 0.254882E+10 | 149584.17 | 43.50 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193637E+11 | 204189.48 | 19-JAN-06:03 | 12.83 |
February | 0.104751E+11 | 201984.54 | 21-FEB-06:50 | 13.75 |
March | 0.456800E+10 | 197336.67 | 07-MAR-06:45 | 14.25 |
April | 0.516448E+09 | 144602.79 | 05-APR-06:00 | 17.00 |
May | 90505693.36 | 15322.20 | 07-MAY-14:51 | 37.00 |
June | 0.111201E+09 | 14315.04 | 18-JUN-15:51 | 36.10 |
July | 0.184738E+09 | 20676.73 | 30-JUL-13:31 | 44.17 |
August | 0.152991E+09 | 19047.06 | 13-AUG-14:21 | 40.00 |
September | 0.125187E+09 | 18859.33 | 03-SEP-14:31 | 38.67 |
October | 81276574.55 | 12818.29 | 15-OCT-14:31 | 34.33 |
November | 0.307904E+09 | 146318.14 | 22-NOV-06:40 | 16.93 |
December | 0.973521E+10 | 198379.18 | 18-DEC-06:40 | 13.67 |
Annual Sum or Average | 0.457123E+11 | |||
Minimum of Months | 81276574.55 | 12818.29 | 12.83 | |
Maximum of Months | 0.193637E+11 | 204189.48 | 44.17 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.681264E+11 | 232401.87 | 11-JAN-06:02 | 14.92 |
February | 0.412031E+11 | 232841.92 | 16-FEB-06:03 | 14.12 |
March | 0.276082E+11 | 232519.76 | 04-MAR-06:03 | 14.48 |
April | 0.629803E+10 | 227888.43 | 01-APR-06:10 | 17.07 |
May | 96177661.97 | 22930.33 | 08-MAY-03:01 | 29.47 |
June | 0.111255E+09 | 17667.00 | 15-JUN-03:01 | 28.98 |
July | 78346681.07 | 13290.47 | 06-JUL-03:01 | 29.87 |
August | 64127515.11 | 12917.60 | 22-AUG-03:01 | 31.00 |
September | 97096900.25 | 16748.93 | 25-SEP-03:01 | 25.73 |
October | 0.121761E+09 | 54104.15 | 21-OCT-07:00 | 22.00 |
November | 0.518234E+10 | 230640.36 | 22-NOV-06:07 | 16.98 |
December | 0.442225E+11 | 234181.14 | 13-DEC-06:03 | 15.02 |
Annual Sum or Average | 0.193209E+12 | |||
Minimum of Months | 64127515.11 | 12917.60 | 14.12 | |
Maximum of Months | 0.681264E+11 | 234181.14 | 31.00 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4532129.24 | 624.47 | 01-JAN-07:05 | 13.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 4532129.24 | |||
Minimum of Months | 0.00 | 0.00 | 13.17 | |
Maximum of Months | 4532129.24 | 624.47 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.278508E+11 | 29144.79 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.252627E+11 | 29144.79 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.300191E+11 | 29144.79 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.268132E+11 | 29144.79 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.289349E+11 | 29144.79 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.287951E+11 | 29144.79 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.269531E+11 | 29144.79 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.300191E+11 | 29144.79 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.268132E+11 | 29144.79 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.278508E+11 | 29144.79 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.275243E+11 | 29144.79 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.269531E+11 | 29144.79 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.333789E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.252627E+11 | 29144.79 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.300191E+11 | 29144.79 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.785272E+10 | 8217.58 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.712300E+10 | 8217.58 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.846411E+10 | 8217.58 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.756018E+10 | 8217.58 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.815842E+10 | 8217.58 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.811897E+10 | 8217.58 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.759962E+10 | 8217.58 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.846411E+10 | 8217.58 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.756018E+10 | 8217.58 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.785272E+10 | 8217.58 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.776069E+10 | 8217.58 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.759962E+10 | 8217.58 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.941143E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.712300E+10 | 8217.58 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.846411E+10 | 8217.58 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.289349E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.287951E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.275243E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.333789E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2989603.15 | 0.126830E+09 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15714598.95 | 0.127935E+09 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38555824.70 | 69177969.11 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92843797.12 | 26864074.12 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214209E+09 | 2234228.25 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273816E+09 | 46688.56 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381817E+09 | 0.00 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365421E+09 | 0.00 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261032E+09 | 288701.80 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154810E+09 | 3452024.26 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67563417.45 | 32127025.08 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11390872.95 | 96328448.72 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188016E+10 | 0.485284E+09 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2989603.15 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381817E+09 | 0.127935E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2151706.22 | 81812484.13 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10793566.10 | 79783784.88 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28925499.54 | 40890067.18 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67173966.10 | 14366702.32 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147724E+09 | 1158415.52 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192559E+09 | 26277.91 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267585E+09 | 0.00 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255650E+09 | 0.00 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180423E+09 | 150077.91 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110019E+09 | 1851540.54 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50152486.64 | 18792418.26 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9896847.22 | 56208556.94 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132305E+10 | 0.295040E+09 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2151706.22 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267585E+09 | 81812484.13 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 891275.69 | 0.135354E+09 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12454424.97 | 0.131305E+09 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37119063.02 | 68307172.52 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92768231.12 | 25008421.52 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219031E+09 | 2005407.79 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281591E+09 | 30026.80 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391317E+09 | 0.00 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371453E+09 | 0.00 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260662E+09 | 297150.75 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148993E+09 | 3715038.64 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58132027.17 | 32899570.89 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8489029.81 | 0.100178E+09 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188290E+10 | 0.499100E+09 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 891275.69 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391317E+09 | 0.135354E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2069573.88 | 92908822.24 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9984719.48 | 0.101714E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23842824.08 | 62162365.72 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56257121.33 | 27518667.08 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143356E+09 | 2436921.46 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181995E+09 | 90228.30 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254494E+09 | 0.00 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240749E+09 | 0.00 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174234E+09 | 320783.38 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99555980.77 | 4478027.60 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40486136.48 | 31207639.76 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6125094.94 | 85873911.41 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123315E+10 | 0.408712E+09 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2069573.88 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254494E+09 | 0.101714E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10732429.89 | 0.236367E+09 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40033092.15 | 0.234690E+09 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91982857.38 | 0.129146E+09 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209860E+09 | 58543645.77 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484277E+09 | 5238241.70 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607304E+09 | 260518.46 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.861878E+09 | 0.00 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824222E+09 | 0.00 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584667E+09 | 657484.14 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342342E+09 | 7299167.99 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160924E+09 | 59483397.85 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33609947.18 | 0.166642E+09 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425183E+10 | 0.898327E+09 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10732429.89 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.861878E+09 | 0.236367E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6437637.63 | 0.161487E+09 |
February | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25475166.76 | 0.157989E+09 |
March | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62078942.29 | 86536621.67 |
April | 0.688021E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138001E+09 | 38387360.24 |
May | 0.744847E+09 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327190E+09 | 3372235.69 |
June | 0.742030E+09 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415170E+09 | 170134.36 |
July | 0.690839E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589729E+09 | 0.00 |
August | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560314E+09 | 0.00 |
September | 0.688021E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395630E+09 | 437836.57 |
October | 0.715730E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230358E+09 | 5134672.11 |
November | 0.708685E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107404E+09 | 41000197.28 |
December | 0.690839E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24009569.90 | 0.109884E+09 |
Annual Sum or Average | 0.858171E+10 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288180E+10 | 0.604399E+09 |
Minimum of Months | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6437637.63 | 0.00 |
Maximum of Months | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589729E+09 | 0.161487E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1994059.32 | 0.297633E+09 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28406320.24 | 0.277175E+09 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81645895.19 | 0.144411E+09 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203458E+09 | 59106621.84 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495534E+09 | 4909403.88 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623589E+09 | 208309.79 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.881557E+09 | 0.00 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834291E+09 | 0.00 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581278E+09 | 747916.23 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319096E+09 | 9511722.70 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123063E+09 | 72509788.95 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17796255.86 | 0.209867E+09 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419171E+10 | 0.107608E+10 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1994059.32 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.881557E+09 | 0.297633E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7401547.50 | 0.170185E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27297511.79 | 0.168390E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60784491.93 | 97507854.27 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136340E+09 | 45112671.99 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326059E+09 | 4135304.04 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411487E+09 | 230219.74 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589088E+09 | 0.00 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560233E+09 | 0.00 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393477E+09 | 554649.11 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226263E+09 | 6267746.83 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104079E+09 | 44236657.92 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22188754.27 | 0.122160E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286470E+10 | 0.658779E+09 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7401547.50 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589088E+09 | 0.170185E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15407951.15 | 0.246845E+09 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51078362.38 | 0.255235E+09 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116473E+09 | 0.142917E+09 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256844E+09 | 66915425.84 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593792E+09 | 6448101.22 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747020E+09 | 324508.25 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106374E+10 | 0.00 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101868E+10 | 0.00 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719224E+09 | 829039.26 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422176E+09 | 8541012.97 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202410E+09 | 62651861.46 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46226397.66 | 0.174328E+09 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525308E+10 | 0.965036E+09 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15407951.15 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106374E+10 | 0.255235E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7940555.09 | 0.176345E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31006521.94 | 0.179061E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76036472.66 | 98934854.00 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166975E+09 | 45342362.46 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398877E+09 | 4356764.31 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507117E+09 | 224640.38 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721613E+09 | 0.00 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688496E+09 | 0.00 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482830E+09 | 583812.01 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280471E+09 | 6347928.50 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131128E+09 | 45406576.02 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29467155.02 | 0.119716E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352196E+10 | 0.676318E+09 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7940555.09 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721613E+09 | 0.179061E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2865643.52 | 0.326769E+09 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35683277.37 | 0.309611E+09 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102227E+09 | 0.162646E+09 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249856E+09 | 68271265.15 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606878E+09 | 6093872.48 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764725E+09 | 259084.85 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108514E+10 | 0.00 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103044E+10 | 0.00 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715740E+09 | 946701.69 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393806E+09 | 11464817.36 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154119E+09 | 78940731.00 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23042014.67 | 0.229532E+09 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516452E+10 | 0.119453E+10 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2865643.52 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108514E+10 | 0.326769E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9400474.48 | 0.191177E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34063023.86 | 0.193282E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76445240.25 | 0.112834E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168270E+09 | 53093078.03 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401926E+09 | 5037490.55 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507529E+09 | 291446.95 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728285E+09 | 0.00 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693700E+09 | 0.00 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485994E+09 | 679023.61 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279819E+09 | 7623425.87 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129596E+09 | 49612997.58 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29107864.26 | 0.138070E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354414E+10 | 0.751701E+09 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9400474.48 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728285E+09 | 0.193282E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.785272E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.712300E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.846411E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.756018E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.815842E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.811897E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.759962E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.846411E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.756018E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.785272E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.776069E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.759962E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.941143E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.712300E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.846411E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2441145.42 | 0.320067E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24715317.55 | 0.313465E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60747493.61 | 0.171136E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160403E+09 | 69519482.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413404E+09 | 5423667.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520981E+09 | 240049.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741069E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699896E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498311E+09 | 665792.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278910E+09 | 9116697.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105147E+09 | 80156619.52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13596931.04 | 0.241857E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351962E+10 | 0.121165E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2441145.42 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741069E+09 | 0.320067E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7536361.56 | 0.513045E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50382501.73 | 0.500736E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116323E+09 | 0.271681E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297721E+09 | 0.117739E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741561E+09 | 9444248.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.928437E+09 | 549118.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133542E+10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125621E+10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892021E+09 | 1135732.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502225E+09 | 15490041.21 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204560E+09 | 0.129021E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33203816.67 | 0.369192E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636560E+10 | 0.192803E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7536361.56 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133542E+10 | 0.513045E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2484943.74 | 0.469253E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40976103.31 | 0.466533E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109852E+09 | 0.258945E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251853E+09 | 88338153.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754848E+09 | 5909695.05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.993993E+09 | 217616.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143056E+10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137038E+10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952868E+09 | 593409.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538599E+09 | 6512859.32 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207450E+09 | 78336736.30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22699565.05 | 0.310357E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667656E+10 | 0.168500E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2484943.74 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143056E+10 | 0.469253E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 29144.79 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 29144.79 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 29144.79 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 29144.79 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 29144.79 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 29144.79 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 29144.79 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 29144.79 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 29144.79 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 29144.79 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 29144.79 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 29144.79 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.76 | 29-JAN-11:40 | 355.17 | 18-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 347.84 | 05-FEB-15:00 | 293.53 | 13-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 346.80 | 02-MAR-04:00 | 265.27 | 05-MAR-15:08 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 374.02 | 30-APR-13:00 | 195.64 | 05-APR-01:00 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2096.62 | 21-MAY-12:51 | 49.58 | 02-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 517.14 | 11-JUN-13:25 | 19.24 | 07-JUN-04:50 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 786.54 | 30-JUL-14:44 | 0.00 | 01-JUL-00:02 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 754.91 | 13-AUG-13:55 | 0.00 | 01-AUG-00:02 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 595.63 | 03-SEP-15:54 | 20.14 | 25-SEP-04:40 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 489.94 | 09-OCT-15:30 | 91.26 | 20-OCT-04:10 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.97 | 19-NOV-14:10 | 146.41 | 22-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 152.89 | 10-DEC-12:43 | 236.52 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 152.89 | 0.00 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2096.62 | 355.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 95.85 | 29-JAN-12:00 | 229.12 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 258.45 | 05-FEB-15:00 | 189.21 | 13-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 270.53 | 02-MAR-04:00 | 161.92 | 05-MAR-15:08 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.22 | 30-APR-13:00 | 118.37 | 05-APR-01:00 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1420.30 | 21-MAY-12:51 | 29.96 | 02-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.23 | 11-JUN-12:46 | 12.01 | 25-JUN-07:00 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 545.85 | 30-JUL-14:44 | 0.00 | 01-JUL-00:02 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 515.76 | 13-AUG-13:55 | 0.00 | 01-AUG-00:02 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 413.14 | 03-SEP-16:00 | 10.90 | 24-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.20 | 09-OCT-16:10 | 54.32 | 20-OCT-04:10 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.98 | 19-NOV-14:10 | 89.80 | 22-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 124.45 | 10-DEC-14:00 | 143.64 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 95.85 | 0.00 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1420.30 | 229.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 65.48 | 29-JAN-12:00 | 346.89 | 18-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 295.83 | 05-FEB-14:56 | 285.11 | 10-FEB-24:00 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 361.63 | 02-MAR-04:00 | 289.45 | 05-MAR-15:08 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 360.74 | 30-APR-12:57 | 188.89 | 05-APR-01:00 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2099.44 | 21-MAY-12:51 | 47.54 | 02-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 539.65 | 11-JUN-12:46 | 16.06 | 07-JUN-04:50 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 801.99 | 30-JUL-14:44 | 0.00 | 01-JUL-00:02 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 753.82 | 13-AUG-13:55 | 0.00 | 01-AUG-00:02 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 591.32 | 03-SEP-15:54 | 20.28 | 24-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 492.76 | 09-OCT-15:24 | 91.52 | 20-OCT-04:10 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.50 | 19-NOV-14:06 | 140.90 | 22-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 112.52 | 10-DEC-13:20 | 221.81 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 65.48 | 0.00 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2099.44 | 346.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 143.00 | 29-JAN-11:40 | 264.61 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 218.92 | 05-FEB-13:00 | 230.64 | 10-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 234.31 | 02-MAR-04:00 | 230.46 | 05-MAR-15:08 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 247.42 | 30-APR-12:57 | 172.48 | 05-APR-01:00 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1448.54 | 21-MAY-12:51 | 44.52 | 02-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 387.99 | 11-JUN-12:46 | 23.02 | 07-JUN-04:50 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 534.75 | 30-JUL-14:44 | 0.00 | 01-JUL-00:02 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 514.80 | 13-AUG-13:55 | 0.00 | 01-AUG-00:02 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 388.72 | 03-SEP-15:54 | 20.29 | 24-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.58 | 09-OCT-15:24 | 82.96 | 20-OCT-04:10 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.03 | 19-NOV-14:10 | 120.74 | 22-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.95 | 10-DEC-12:03 | 192.62 | 15-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 105.95 | 0.00 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1448.54 | 264.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 412.44 | 29-JAN-11:50 | 631.38 | 18-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 858.37 | 05-FEB-15:10 | 553.56 | 13-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 742.45 | 02-MAR-04:10 | 589.57 | 05-MAR-14:52 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 897.67 | 30-APR-13:00 | 381.06 | 05-APR-01:00 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4834.15 | 21-MAY-12:51 | 110.73 | 01-MAY-02:55 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1226.12 | 11-JUN-12:56 | 69.78 | 07-JUN-05:00 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1831.87 | 30-JUL-14:54 | 0.00 | 01-JUL-00:02 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.34 | 13-AUG-13:53 | 0.00 | 01-AUG-00:02 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1346.06 | 03-SEP-15:54 | 73.93 | 25-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1157.67 | 09-OCT-14:55 | 191.86 | 20-OCT-04:10 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 882.92 | 19-NOV-13:50 | 289.30 | 22-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 412.16 | 10-DEC-12:43 | 434.01 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 412.16 | 0.00 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 4834.15 | 631.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 223.76 | 29-JAN-11:50 | 418.90 | 18-JAN-04:00 |
February | 1239.33 | 01-FEB-08:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 594.89 | 05-FEB-14:50 | 369.62 | 13-FEB-04:00 |
March | 1239.33 | 01-MAR-08:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 550.97 | 02-MAR-04:10 | 413.10 | 05-MAR-14:52 |
April | 1239.33 | 03-APR-07:10 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 593.00 | 30-APR-12:53 | 248.22 | 05-APR-01:00 |
May | 1239.33 | 01-MAY-07:10 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3223.81 | 21-MAY-12:51 | 75.08 | 01-MAY-02:55 |
June | 1239.33 | 01-JUN-07:10 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 843.03 | 11-JUN-14:57 | 38.60 | 07-JUN-05:00 |
July | 1239.33 | 03-JUL-07:10 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1254.71 | 30-JUL-14:54 | 0.00 | 01-JUL-00:02 |
August | 1239.33 | 01-AUG-07:10 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1130.18 | 13-AUG-13:53 | 0.00 | 01-AUG-00:02 |
September | 1239.33 | 01-SEP-07:10 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 942.67 | 03-SEP-15:56 | 45.42 | 25-SEP-05:00 |
October | 1239.33 | 02-OCT-07:10 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 802.38 | 09-OCT-15:40 | 127.41 | 20-OCT-04:10 |
November | 1239.33 | 01-NOV-07:10 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 617.13 | 19-NOV-14:10 | 183.90 | 12-NOV-08:00 |
December | 1239.33 | 01-DEC-08:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 296.05 | 10-DEC-14:00 | 280.60 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 223.76 | 0.00 | |||||
Maximum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 3223.81 | 418.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 148.91 | 29-JAN-11:50 | 688.47 | 01-JAN-15:50 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 682.90 | 05-FEB-15:24 | 589.98 | 19-FEB-19:00 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 768.29 | 02-MAR-04:10 | 734.41 | 05-MAR-14:52 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 833.85 | 30-APR-12:53 | 382.34 | 05-APR-01:00 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4834.75 | 21-MAY-12:51 | 114.63 | 01-MAY-02:55 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1241.10 | 11-JUN-14:55 | 64.89 | 07-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1819.46 | 30-JUL-14:54 | 0.00 | 01-JUL-00:02 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1692.71 | 13-AUG-14:00 | 0.00 | 01-AUG-00:02 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1361.82 | 04-SEP-16:55 | 76.06 | 25-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1124.63 | 09-OCT-16:15 | 200.51 | 20-OCT-04:10 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 638.74 | 19-NOV-14:06 | 291.61 | 22-NOV-06:00 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 276.03 | 10-DEC-14:03 | 437.67 | 17-DEC-14:47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 148.91 | 0.00 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 4834.75 | 734.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 348.02 | 29-JAN-11:30 | 434.14 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 549.24 | 05-FEB-12:50 | 388.04 | 13-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 577.97 | 02-MAR-04:10 | 472.11 | 05-MAR-14:52 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 630.48 | 30-APR-13:00 | 272.53 | 05-APR-01:00 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3237.20 | 21-MAY-12:51 | 87.30 | 01-MAY-02:55 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 870.75 | 09-JUN-03:10 | 46.55 | 07-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.08 | 30-JUL-14:54 | 0.00 | 01-JUL-00:02 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1128.75 | 13-AUG-13:53 | 0.00 | 01-AUG-00:02 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 888.89 | 04-SEP-16:55 | 49.88 | 25-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 778.21 | 09-OCT-14:55 | 137.02 | 20-OCT-04:10 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 573.95 | 19-NOV-13:50 | 193.45 | 22-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 313.15 | 10-DEC-12:03 | 291.47 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 313.15 | 0.00 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 3237.20 | 472.11 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 587.11 | 29-JAN-12:00 | 670.00 | 19-JAN-06:00 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1069.38 | 05-FEB-15:00 | 590.85 | 13-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 948.89 | 02-MAR-04:10 | 735.23 | 05-MAR-15:02 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1088.65 | 30-APR-12:53 | 426.95 | 05-APR-01:00 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5680.30 | 21-MAY-12:51 | 141.69 | 01-MAY-02:55 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1532.03 | 11-JUN-12:56 | 76.80 | 07-JUN-05:00 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2252.76 | 30-JUL-14:24 | 0.00 | 01-JUL-00:02 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2159.59 | 13-AUG-13:55 | 0.00 | 01-AUG-00:02 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1671.13 | 03-SEP-15:54 | 82.73 | 25-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1458.05 | 09-OCT-14:55 | 219.70 | 20-OCT-04:10 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1117.16 | 19-NOV-14:00 | 326.83 | 22-NOV-05:53 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 530.57 | 10-DEC-12:30 | 466.93 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 530.57 | 0.00 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 5680.30 | 735.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 349.66 | 29-JAN-12:00 | 449.97 | 19-JAN-05:40 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 718.60 | 05-FEB-15:20 | 416.51 | 19-FEB-19:00 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 678.73 | 02-MAR-04:10 | 515.71 | 05-MAR-14:52 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 717.75 | 30-APR-13:15 | 279.95 | 05-APR-01:00 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3754.15 | 21-MAY-12:51 | 96.58 | 01-MAY-02:55 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1052.82 | 11-JUN-14:55 | 44.20 | 07-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1496.78 | 30-JUL-14:24 | 0.00 | 01-JUL-00:02 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1489.78 | 13-AUG-13:55 | 0.00 | 01-AUG-00:02 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1171.84 | 03-SEP-15:56 | 52.41 | 25-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 998.08 | 09-OCT-14:57 | 146.26 | 20-OCT-04:10 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 756.25 | 19-NOV-13:50 | 212.04 | 22-NOV-05:53 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 370.80 | 10-DEC-13:10 | 303.67 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 349.66 | 0.00 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 3754.15 | 515.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 286.82 | 29-JAN-12:00 | 923.94 | 01-JAN-14:52 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 846.20 | 05-FEB-15:15 | 729.19 | 19-FEB-19:00 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 976.02 | 02-MAR-04:10 | 913.95 | 05-MAR-14:52 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1024.17 | 30-APR-12:53 | 429.48 | 05-APR-01:00 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5667.41 | 21-MAY-12:51 | 145.70 | 01-MAY-02:55 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1560.90 | 11-JUN-14:55 | 70.98 | 07-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2248.16 | 30-JUL-14:24 | 0.00 | 01-JUL-00:02 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2147.45 | 13-AUG-13:55 | 0.00 | 01-AUG-00:02 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1650.49 | 03-SEP-15:54 | 85.18 | 25-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1399.06 | 09-OCT-16:15 | 229.78 | 20-OCT-04:10 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 823.00 | 19-NOV-13:46 | 334.77 | 22-NOV-05:53 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 397.27 | 10-DEC-14:30 | 534.36 | 17-DEC-14:34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 286.82 | 0.00 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5667.41 | 923.94 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 470.12 | 29-JAN-12:00 | 516.63 | 01-JAN-16:32 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 698.24 | 05-FEB-12:42 | 452.32 | 19-FEB-19:00 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 728.14 | 02-MAR-04:10 | 593.36 | 05-MAR-14:52 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 763.09 | 30-APR-12:53 | 309.79 | 05-APR-01:00 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3771.21 | 21-MAY-12:51 | 107.21 | 01-MAY-02:55 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1090.23 | 09-JUN-03:10 | 51.77 | 07-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1489.68 | 30-JUL-14:24 | 0.00 | 01-JUL-00:02 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1463.25 | 13-AUG-13:55 | 0.00 | 01-AUG-00:02 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1075.65 | 04-SEP-16:44 | 54.37 | 25-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 966.40 | 09-OCT-14:55 | 157.98 | 20-OCT-04:10 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 739.42 | 19-NOV-13:50 | 230.01 | 22-NOV-05:53 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 400.97 | 10-DEC-12:30 | 321.82 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 400.97 | 0.00 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 3771.21 | 593.36 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 8217.58 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 8217.58 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 8217.58 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 8217.58 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 8217.58 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 8217.58 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 8217.58 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 8217.58 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 8217.58 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 8217.58 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 8217.58 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 8217.58 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 8217.58 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 8217.58 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.06 | 29-JAN-12:00 | 850.66 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 626.08 | 05-FEB-15:00 | 700.27 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.22 | 26-MAR-14:00 | 607.60 | 06-MAR-05:53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 763.06 | 30-APR-13:00 | 441.69 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4303.61 | 21-MAY-13:00 | 111.95 | 01-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1057.60 | 11-JUN-13:00 | 64.63 | 07-JUN-04:52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.78 | 30-JUL-15:00 | 0.00 | 01-JUL-00:02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1486.41 | 13-AUG-14:00 | 0.00 | 01-AUG-00:02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1153.61 | 03-SEP-16:00 | 69.38 | 25-SEP-04:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 953.17 | 09-OCT-15:10 | 199.82 | 20-OCT-04:13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.00 | 19-NOV-13:51 | 362.39 | 22-NOV-05:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.16 | 10-DEC-13:00 | 547.59 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.06 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4303.61 | 850.66 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.53 | 29-JAN-11:52 | 1347.53 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1247.01 | 05-FEB-15:00 | 1150.94 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.56 | 26-MAR-14:00 | 1011.71 | 06-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1398.27 | 30-APR-13:00 | 751.81 | 05-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7614.78 | 21-MAY-13:00 | 204.49 | 01-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1921.03 | 11-JUN-13:20 | 138.01 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2867.29 | 30-JUL-14:41 | 0.00 | 01-JUL-00:02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2717.51 | 13-AUG-14:00 | 0.00 | 01-AUG-00:02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2080.03 | 03-SEP-16:00 | 138.59 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1753.76 | 09-OCT-15:20 | 346.50 | 20-OCT-04:13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1229.34 | 19-NOV-13:51 | 627.38 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.75 | 10-DEC-13:00 | 901.56 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.53 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7614.78 | 1347.53 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.98 | 29-JAN-12:00 | 1233.36 | 01-JAN-15:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1042.56 | 05-FEB-15:00 | 1055.90 | 19-FEB-19:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1066.20 | 02-MAR-03:55 | 1570.77 | 05-MAR-15:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1144.98 | 30-APR-13:00 | 621.15 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6396.32 | 21-MAY-12:51 | 207.52 | 01-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1943.66 | 09-JUN-02:52 | 65.85 | 07-JUN-04:52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2692.83 | 30-JUL-14:10 | 0.00 | 01-JUL-00:02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2459.25 | 16-AUG-21:01 | 0.00 | 01-AUG-00:02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2017.98 | 02-SEP-17:01 | 99.37 | 25-SEP-04:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.36 | 09-OCT-16:00 | 298.18 | 20-OCT-04:13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 993.28 | 19-NOV-14:00 | 486.00 | 22-NOV-05:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.24 | 10-DEC-12:10 | 792.90 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.98 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6396.32 | 1570.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 125301.35 | 17-JAN-05:11 | 0.00 | 22668.17 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 121309.08 | 11-FEB-05:12 | 0.00 | 9714.93 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 125929.23 | 28-MAR-03:01 | 0.00 | 11334.08 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 128446.76 | 03-APR-03:12 | 0.00 | 8095.77 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 124305.99 | 29-MAY-15:58 | 8078.51 | 14572.39 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 119955.87 | 16-JUN-05:02 | 8976.13 | 16191.55 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 128334.00 | 11-JUL-03:01 | 0.00 | 12953.24 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 129952.91 | 16-AUG-03:01 | 0.00 | 11334.08 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 125953.88 | 04-SEP-09:16 | 8078.51 | 14572.39 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 124445.37 | 29-OCT-12:43 | 8078.51 | 14572.39 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 127185.08 | 13-NOV-05:22 | 0.00 | 19429.86 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 122462.48 | 11-DEC-05:33 | 0.00 | 12953.24 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 119955.87 | 0.00 | 8095.77 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 129952.91 | 8976.13 | 22668.17 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 125382.22 | 02-JAN-05:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 127386.51 | 21-FEB-05:11 | 0.00 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 124970.42 | 06-MAR-05:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 121328.99 | 07-APR-04:11 | 0.00 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 114980.30 | 15-MAY-04:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 107306.61 | 20-JUN-05:02 | 8061.19 | 14541.15 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 106023.25 | 17-JUL-05:03 | 6448.95 | 11632.92 | 30589.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 107781.11 | 07-AUG-05:02 | 8061.19 | 14541.15 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 113773.62 | 25-SEP-04:02 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 115383.44 | 28-OCT-03:01 | 0.00 | 11632.92 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 121524.35 | 22-NOV-05:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 125671.28 | 18-DEC-05:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 106023.25 | 0.00 | 11632.92 | 30589.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 127386.51 | 8061.19 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 104434.14 | 02-JAN-05:12 | 0.00 | 17449.38 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 105175.00 | 10-FEB-05:12 | 0.00 | 17449.38 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 108098.65 | 23-MAR-04:11 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 111389.73 | 26-APR-04:11 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 105305.46 | 05-MAY-04:02 | 0.00 | 17449.38 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 97595.34 | 08-JUN-05:01 | 11285.67 | 20357.61 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 81662.32 | 13-JUL-05:02 | 8061.19 | 14541.15 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 81734.11 | 31-AUG-03:01 | 0.00 | 11632.92 | 47500.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 103862.09 | 22-SEP-04:01 | 0.00 | 23265.84 | 47500.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 107692.64 | 20-OCT-04:11 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 110648.36 | 13-NOV-05:12 | 0.00 | 17449.38 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 106634.11 | 01-DEC-05:11 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 81662.32 | 0.00 | 11632.92 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 111389.73 | 11285.67 | 23265.84 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 65224.67 | 30-JAN-06:02 | 8061.19 | 14541.15 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 118702.64 | 06-FEB-06:02 | 9673.43 | 17449.38 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 124141.55 | 28-MAR-04:01 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 126447.66 | 24-APR-04:11 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 130693.34 | 15-MAY-03:01 | 0.00 | 11632.92 | 47500.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 118814.32 | 08-JUN-05:01 | 11285.67 | 20357.61 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 111078.97 | 10-JUL-05:02 | 8061.19 | 14541.15 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 111818.83 | 25-AUG-05:02 | 8061.19 | 14541.15 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 122756.40 | 12-SEP-04:01 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 126504.75 | 19-OCT-04:01 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 121217.22 | 03-NOV-04:01 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 122487.86 | 12-DEC-06:02 | 9673.43 | 17449.38 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 65224.67 | 0.00 | 11632.92 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 130693.34 | 11285.67 | 20357.61 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9610.34 | 23-JAN-14:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 | 0.00 |
February | 12464.79 | 06-FEB-14:30 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 88.58 | 0.00 |
March | 15393.78 | 27-MAR-04:11 | 0.00 | 2556.10 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.62 |
April | 30094.40 | 02-APR-14:01 | 809.73 | 1460.63 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 238.72 | 0.00 |
May | 32503.25 | 07-MAY-14:11 | 809.73 | 1460.63 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 357.32 | 0.00 |
June | 33367.36 | 11-JUN-13:21 | 809.73 | 1460.63 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 444.94 | 0.00 |
July | 36315.77 | 30-JUL-14:01 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 667.45 | 0.00 |
August | 32464.35 | 06-AUG-15:01 | 708.51 | 1278.05 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 455.03 | 0.00 |
September | 35324.66 | 04-SEP-14:41 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 434.74 | 0.00 |
October | 33241.62 | 09-OCT-14:41 | 910.95 | 1643.21 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 414.15 | 0.00 |
November | 23742.64 | 05-NOV-14:21 | 809.73 | 1460.63 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 237.36 | 0.00 |
December | 10384.58 | 11-DEC-14:10 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 25.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9610.34 | 0.00 | 1278.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36315.77 | 2010.79 | 3286.42 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 667.45 | 18.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7884.38 | 29-JAN-10:20 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.77 |
February | 12825.12 | 05-FEB-09:32 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.37 |
March | 19342.18 | 26-MAR-09:12 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 | 0.00 |
April | 30529.90 | 23-APR-10:01 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 52.28 | 0.00 |
May | 31763.32 | 07-MAY-09:31 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 53.13 | 0.00 |
June | 30420.72 | 25-JUN-10:21 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 81.82 | 0.00 |
July | 33891.89 | 30-JUL-10:01 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 213.24 | 0.00 |
August | 28759.24 | 13-AUG-10:32 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 386.22 | 0.00 |
September | 30923.07 | 04-SEP-08:41 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 141.14 | 0.00 |
October | 29986.68 | 09-OCT-10:41 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 46.50 | 0.00 |
November | 23636.01 | 05-NOV-11:01 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 63.49 | 0.00 |
December | 7993.50 | 01-DEC-10:30 | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 9.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7884.38 | 326.14 | 588.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33891.89 | 1295.83 | 2117.89 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 386.22 | 78.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18784.25 | 16-JAN-12:22 | 506.09 | 912.91 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.89 |
February | 34932.48 | 05-FEB-13:32 | 506.09 | 912.91 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 213.58 | 0.00 |
March | 37668.86 | 12-MAR-13:22 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 31.40 | 0.00 |
April | 38076.94 | 02-APR-13:21 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 158.49 | 0.00 |
May | 37827.58 | 07-MAY-14:11 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 355.98 | 0.00 |
June | 37806.01 | 11-JUN-13:21 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 461.70 | 0.00 |
July | 42595.46 | 30-JUL-14:01 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 660.02 | 0.00 |
August | 37693.99 | 13-AUG-14:31 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 670.97 | 0.00 |
September | 43133.98 | 04-SEP-14:41 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 407.26 | 0.00 |
October | 43554.64 | 09-OCT-12:01 | 910.97 | 1643.24 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 114.73 | 0.00 |
November | 43050.01 | 05-NOV-12:21 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 103.71 | 0.00 |
December | 41580.30 | 25-DEC-12:11 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18784.25 | 506.09 | 912.91 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43554.64 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 670.97 | 13.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10679.19 | 29-JAN-16:53 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.56 |
February | 21782.62 | 06-FEB-05:11 | 0.00 | 1647.25 | 3363.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.31 |
March | 35748.52 | 12-MAR-15:21 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.84 |
April | 37247.29 | 02-APR-14:01 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 127.62 | 0.00 |
May | 40228.25 | 14-MAY-15:21 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.77 | 0.00 |
June | 39489.63 | 25-JUN-15:01 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 173.72 | 0.00 |
July | 43721.19 | 30-JUL-14:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 402.44 | 0.00 |
August | 38578.69 | 06-AUG-15:41 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 253.73 | 0.00 |
September | 43027.20 | 04-SEP-15:21 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 250.92 | 0.00 |
October | 40772.15 | 09-OCT-15:21 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.46 | 0.00 |
November | 38116.96 | 05-NOV-14:21 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 126.07 | 0.00 |
December | 26365.06 | 15-DEC-05:11 | 0.00 | 1647.25 | 3363.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10679.19 | 0.00 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43721.19 | 652.28 | 1647.25 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 402.44 | 70.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7580.12 | 22-JAN-14:32 | 607.30 | 1095.47 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.07 | 0.00 |
February | 10984.44 | 06-FEB-14:50 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 209.02 | 0.00 |
March | 16207.11 | 28-MAR-05:02 | 1214.60 | 2190.94 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 | 0.00 |
April | 26551.96 | 30-APR-12:31 | 708.51 | 1278.05 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 667.04 | 0.00 |
May | 32982.62 | 07-MAY-14:11 | 809.73 | 1460.63 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 813.28 | 0.00 |
June | 31281.26 | 11-JUN-16:11 | 708.51 | 1278.05 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 978.86 | 0.00 |
July | 37065.83 | 30-JUL-14:11 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1529.57 | 0.00 |
August | 35080.70 | 13-AUG-15:01 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1320.29 | 0.00 |
September | 32569.65 | 17-SEP-14:11 | 809.73 | 1460.63 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 879.04 | 0.00 |
October | 31233.75 | 15-OCT-14:31 | 809.73 | 1460.63 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 655.67 | 0.00 |
November | 12575.04 | 20-NOV-06:02 | 1012.16 | 1825.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 38.97 | 0.00 |
December | 8419.72 | 11-DEC-14:20 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 57.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7580.12 | 607.30 | 1095.47 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 | 0.00 | |
Maximum of Months | 37065.83 | 2010.79 | 3286.42 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1529.57 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6902.66 | 22-JAN-14:32 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 42.31 | 0.00 |
February | 12473.80 | 05-FEB-10:42 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 134.82 | 0.00 |
March | 24374.27 | 26-MAR-10:22 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 57.52 | 0.00 |
April | 30899.57 | 30-APR-10:31 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 124.95 | 0.00 |
May | 32531.55 | 07-MAY-09:31 | 521.82 | 941.28 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 122.69 | 0.00 |
June | 29723.45 | 11-JUN-10:12 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 492.01 | 0.00 |
July | 35224.04 | 30-JUL-10:11 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 524.14 | 0.00 |
August | 32980.12 | 13-AUG-10:21 | 587.05 | 1058.95 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 717.58 | 0.00 |
September | 31170.78 | 24-SEP-10:31 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 274.57 | 0.00 |
October | 29607.68 | 15-OCT-11:11 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 193.65 | 0.00 |
November | 11736.01 | 02-NOV-10:05 | 2478.65 | 4235.78 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 40.28 | 0.00 |
December | 8507.76 | 01-DEC-11:05 | 2478.65 | 4235.78 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 28.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6902.66 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 28.39 | 0.00 | |
Maximum of Months | 35224.04 | 2478.65 | 4235.78 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 717.58 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37006.32 | 22-JAN-14:32 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.92 |
February | 40477.96 | 05-FEB-13:21 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 336.66 | 0.00 |
March | 37639.28 | 26-MAR-14:21 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 485.83 | 0.00 |
April | 38322.11 | 30-APR-12:31 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 603.64 | 0.00 |
May | 37790.09 | 07-MAY-14:11 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 813.48 | 0.00 |
June | 28034.24 | 11-JUN-15:31 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1051.35 | 0.00 |
July | 42682.04 | 30-JUL-14:11 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1520.95 | 0.00 |
August | 40556.41 | 13-AUG-15:01 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1304.15 | 0.00 |
September | 40124.53 | 17-SEP-13:31 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 651.72 | 0.00 |
October | 41625.24 | 15-OCT-11:51 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 349.98 | 0.00 |
November | 38704.21 | 05-NOV-13:12 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 435.64 | 0.00 |
December | 41213.30 | 03-DEC-13:11 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 11.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 28034.24 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42682.04 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1520.95 | 38.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8783.20 | 22-JAN-14:32 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 0.00 |
February | 18952.96 | 05-FEB-16:42 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 275.70 | 0.00 |
March | 26817.21 | 26-MAR-15:41 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 266.49 | 0.00 |
April | 34126.58 | 30-APR-16:31 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 205.57 | 0.00 |
May | 36463.09 | 14-MAY-15:21 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.87 | 0.00 |
June | 32787.34 | 11-JUN-16:11 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 622.89 | 0.00 |
July | 39223.25 | 30-JUL-14:11 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 971.22 | 0.00 |
August | 38362.83 | 13-AUG-15:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 692.82 | 0.00 |
September | 34514.35 | 04-SEP-16:11 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 713.66 | 0.00 |
October | 34725.21 | 15-OCT-15:11 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 324.35 | 0.00 |
November | 13423.04 | 05-NOV-15:12 | 326.14 | 588.30 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 356.28 | 0.00 |
December | 9197.67 | 01-DEC-15:20 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 38.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8783.20 | 326.14 | 588.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 0.00 | |
Maximum of Months | 39223.25 | 1239.33 | 2117.89 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 971.22 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8018.78 | 23-JAN-14:10 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 78.81 | 0.00 |
February | 12166.41 | 06-FEB-15:00 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 258.59 | 0.00 |
March | 15080.75 | 27-MAR-13:40 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 389.07 | 0.00 |
April | 37120.89 | 30-APR-12:31 | 708.51 | 1278.05 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 812.56 | 0.00 |
May | 39623.68 | 21-MAY-13:02 | 607.30 | 1095.47 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 4791.80 | 0.00 |
June | 40722.33 | 25-JUN-15:31 | 910.95 | 1643.21 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 693.10 | 0.00 |
July | 40370.29 | 30-JUL-14:21 | 708.51 | 1278.05 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 2065.94 | 0.00 |
August | 42230.25 | 06-AUG-14:51 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.04 | 0.00 |
September | 43664.05 | 04-SEP-14:41 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1182.27 | 0.00 |
October | 32501.09 | 09-OCT-13:31 | 708.51 | 1278.05 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1070.53 | 0.00 |
November | 20040.50 | 05-NOV-14:21 | 809.73 | 1460.63 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 666.80 | 0.00 |
December | 9536.58 | 03-DEC-13:42 | 607.30 | 1095.47 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8018.78 | 607.30 | 1095.47 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 78.81 | 0.00 | |
Maximum of Months | 43664.05 | 2010.79 | 3286.42 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 4791.80 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6824.38 | 29-JAN-10:42 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.14 |
February | 10392.12 | 05-FEB-10:35 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 131.70 | 0.00 |
March | 13734.77 | 27-MAR-10:50 | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 325.86 | 0.00 |
April | 32726.27 | 23-APR-09:51 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 130.42 | 0.00 |
May | 31932.76 | 21-MAY-10:22 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 847.48 | 0.00 |
June | 32654.15 | 25-JUN-09:31 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 97.65 | 0.00 |
July | 33368.51 | 30-JUL-10:21 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 794.85 | 0.00 |
August | 33772.67 | 06-AUG-14:51 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 772.56 | 0.00 |
September | 35058.94 | 04-SEP-14:41 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 788.73 | 0.00 |
October | 28200.82 | 29-OCT-13:21 | 587.05 | 1058.95 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 390.77 | 0.00 |
November | 21102.85 | 05-NOV-11:01 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 178.76 | 0.00 |
December | 8062.00 | 03-DEC-13:01 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 96.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6824.38 | 391.37 | 705.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35058.94 | 1239.33 | 2117.89 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 847.48 | 51.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35211.93 | 22-JAN-14:22 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.56 |
February | 46191.05 | 05-FEB-13:51 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 467.68 | 0.00 |
March | 34498.69 | 26-MAR-15:12 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 534.56 | 0.00 |
April | 44687.13 | 30-APR-12:31 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 726.66 | 0.00 |
May | 43992.93 | 21-MAY-13:02 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 4831.00 | 0.00 |
June | 43957.56 | 25-JUN-15:31 | 910.97 | 1643.24 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 746.46 | 0.00 |
July | 44998.81 | 30-JUL-14:21 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 2069.85 | 0.00 |
August | 47460.24 | 06-AUG-14:11 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 944.15 | 0.00 |
September | 51105.80 | 04-SEP-14:41 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.75 | 0.00 |
October | 49605.48 | 29-OCT-13:21 | 910.97 | 1643.24 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 368.25 | 0.00 |
November | 49064.29 | 05-NOV-12:21 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 297.97 | 0.00 |
December | 46812.06 | 03-DEC-13:01 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 31.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 34498.69 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51105.80 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 4831.00 | 44.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7915.15 | 29-JAN-16:45 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.18 |
February | 23478.51 | 05-FEB-16:32 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 352.86 | 0.00 |
March | 24054.29 | 26-MAR-15:52 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 303.39 | 0.00 |
April | 38305.01 | 30-APR-16:31 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 230.93 | 0.00 |
May | 38072.41 | 21-MAY-15:41 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 907.62 | 0.00 |
June | 41410.36 | 25-JUN-16:11 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.05 | 0.00 |
July | 39190.44 | 30-JUL-14:21 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 1358.42 | 0.00 |
August | 43699.00 | 06-AUG-15:31 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 603.19 | 0.00 |
September | 44912.21 | 04-SEP-15:21 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 684.61 | 0.00 |
October | 36921.02 | 29-OCT-15:21 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 367.59 | 0.00 |
November | 36126.55 | 05-NOV-14:21 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 424.20 | 0.00 |
December | 10164.85 | 03-DEC-14:22 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 72.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7915.15 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44912.21 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 1358.42 | 24.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13783.60 | 02-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.24 |
February | 12795.07 | 21-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.61 |
March | 11649.95 | 27-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.12 |
April | 11824.24 | 17-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.49 |
May | 12939.77 | 09-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 | 0.00 |
June | 12024.68 | 12-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.16 | 0.00 |
July | 13008.17 | 31-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.62 | 0.00 |
August | 14639.07 | 07-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.93 | 0.00 |
September | 13742.21 | 05-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.95 | 0.00 |
October | 12928.25 | 16-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.45 | 0.00 |
November | 14139.55 | 06-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.94 |
December | 12956.22 | 26-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 11649.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14639.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.62 | 101.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9938.93 | 02-JAN-05:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.12 |
February | 8941.23 | 21-FEB-05:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 850.22 |
March | 9797.38 | 31-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.81 |
April | 11426.89 | 29-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
May | 12059.17 | 09-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 | 0.00 |
June | 11498.51 | 03-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.42 | 0.00 |
July | 11315.33 | 21-JUL-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 686.07 | 0.00 |
August | 11532.97 | 16-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.88 | 0.00 |
September | 11861.93 | 27-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 0.00 |
October | 11392.54 | 19-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.38 |
November | 10412.75 | 13-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.29 |
December | 9350.95 | 13-DEC-05:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 564.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8941.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12059.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 686.07 | 850.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19025.27 | 31-JAN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.69 |
February | 26926.24 | 07-FEB-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.93 | 0.00 |
March | 34774.07 | 27-MAR-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.04 | 0.00 |
April | 39848.89 | 30-APR-12:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 796.33 | 0.00 |
May | 42208.29 | 10-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.52 | 0.00 |
June | 41820.51 | 27-JUN-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.61 | 0.00 |
July | 46031.44 | 21-JUL-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.30 | 0.00 |
August | 45811.75 | 16-AUG-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.72 | 0.00 |
September | 41278.07 | 05-SEP-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 540.58 | 0.00 |
October | 35895.99 | 04-OCT-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.67 | 0.00 |
November | 28664.85 | 01-NOV-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.82 | 0.00 |
December | 21442.85 | 04-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 19025.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46031.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 796.33 | 66.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2096.29 | 03-JAN-17:00 | 222.14 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4079.59 | 06-FEB-15:50 | 222.14 | 728.78 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7269.70 | 31-MAR-24:00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7983.85 | 27-APR-16:00 | 222.14 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3517.74 | 31-MAY-23:31 | 0.00 | 323.90 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5369.94 | 30-JUN-23:46 | 0.00 | 202.44 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7259.15 | 31-JUL-23:21 | 0.00 | 283.42 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8065.92 | 10-AUG-16:00 | 222.14 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3471.77 | 30-SEP-23:04 | 0.00 | 202.44 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5390.43 | 31-OCT-23:42 | 0.00 | 202.44 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6054.96 | 06-NOV-16:50 | 222.14 | 728.78 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7891.71 | 05-DEC-17:00 | 222.14 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2096.29 | 0.00 | 40.49 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8065.92 | 222.14 | 728.78 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1912.34 | 31-JAN-17:00 | 222.14 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3810.56 | 07-FEB-17:00 | 222.14 | 728.78 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6821.07 | 31-MAR-24:00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7604.84 | 27-APR-16:00 | 222.14 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3404.41 | 31-MAY-23:44 | 0.00 | 202.44 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5193.36 | 30-JUN-23:16 | 0.00 | 202.44 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7027.36 | 31-JUL-23:43 | 0.00 | 242.93 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7676.69 | 10-AUG-16:00 | 222.14 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3407.67 | 30-SEP-24:00 | 0.00 | 40.49 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5164.10 | 31-OCT-24:00 | 0.00 | 80.98 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5724.13 | 06-NOV-17:00 | 222.14 | 728.78 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7444.84 | 06-DEC-17:00 | 222.14 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1912.34 | 0.00 | 40.49 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7676.69 | 222.14 | 728.78 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1973.80 | 31-JAN-17:00 | 222.14 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3952.21 | 06-FEB-16:00 | 222.14 | 728.78 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6661.44 | 31-MAR-24:00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7809.23 | 27-APR-16:00 | 222.14 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3444.34 | 31-MAY-23:44 | 0.00 | 202.44 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5201.08 | 30-JUN-23:14 | 0.00 | 202.44 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7059.21 | 31-JUL-23:35 | 0.00 | 242.93 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8038.75 | 06-AUG-16:40 | 23.38 | 80.98 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3433.44 | 30-SEP-24:00 | 0.00 | 40.49 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5105.05 | 31-OCT-24:00 | 0.00 | 80.98 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5826.39 | 01-NOV-16:00 | 222.14 | 728.78 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7523.27 | 06-DEC-16:50 | 222.14 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1973.80 | 0.00 | 40.49 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8038.75 | 222.14 | 728.78 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 95236.85 | 31-JAN-17:00 | 4808.68 | 8217.58 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 186856.02 | 07-FEB-17:00 | 4808.68 | 8217.58 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 360658.01 | 31-MAR-24:00 | 0.00 | 456.53 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 384179.46 | 29-APR-05:07 | 3037.06 | 5478.39 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 177716.57 | 31-MAY-24:00 | 0.00 | 2282.66 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 269394.61 | 30-JUN-23:55 | 0.00 | 913.06 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 361687.22 | 31-JUL-23:52 | 0.00 | 2739.19 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 371758.02 | 17-AUG-16:00 | 4808.68 | 8217.58 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 177867.65 | 30-SEP-24:00 | 0.00 | 456.53 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 270949.88 | 31-OCT-24:00 | 0.00 | 913.06 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 280213.46 | 07-NOV-17:00 | 4808.68 | 8217.58 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 374419.50 | 31-DEC-16:58 | 1518.53 | 2739.19 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 95236.85 | 0.00 | 456.53 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 384179.46 | 4808.68 | 8217.58 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.219415E+13 | 1670188.45 | 30-JAN-15:09 | 0.00 | 0.00 |
February | 0.237050E+13 | 2034143.19 | 06-FEB-15:09 | 0.00 | 0.00 |
March | 0.315915E+13 | 2217283.65 | 27-MAR-15:09 | 0.00 | 0.00 |
April | 0.350122E+13 | 2412734.00 | 28-APR-15:09 | 0.00 | 0.00 |
May | 0.267018E+13 | 2081979.31 | 31-MAY-15:00 | 0.00 | 0.00 |
June | 0.318610E+13 | 2239200.76 | 09-JUN-14:09 | 0.00 | 0.00 |
July | 0.373484E+13 | 2452420.21 | 19-JUL-15:09 | 0.00 | 0.00 |
August | 0.433861E+13 | 2659123.79 | 10-AUG-15:00 | 0.00 | 0.00 |
September | 0.275297E+13 | 2144620.35 | 07-SEP-14:09 | 0.00 | 0.00 |
October | 0.303110E+13 | 2193735.47 | 06-OCT-15:20 | 0.00 | 0.00 |
November | 0.313446E+13 | 2307554.92 | 01-NOV-14:09 | 0.00 | 0.00 |
December | 0.341829E+13 | 2294758.38 | 04-DEC-11:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.374916E+14 | 0.00 | 0.00 | ||
Minimum of Months | 0.219415E+13 | 1670188.45 | 0.00 | 0.00 | |
Maximum of Months | 0.433861E+13 | 2659123.79 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.468149E+12 | 0.955475E+11 | 0.766053E+12 | 0.218140E+12 | 0.191990E+12 | 0.136295E+12 | 0.197546E+10 | 0.267305E+12 | 0.202738E+11 | 54977008.04 | 0.00 | 0.283640E+11 | 0.00 |
February | 0.424646E+12 | 0.828975E+11 | 0.978954E+12 | 0.199667E+12 | 0.180367E+12 | 0.127079E+12 | 0.927531E+09 | 0.318496E+12 | 0.323833E+11 | 0.00 | 0.00 | 0.250830E+11 | 0.00 |
March | 0.504598E+12 | 0.868194E+11 | 0.141687E+13 | 0.230864E+12 | 0.234892E+12 | 0.149731E+12 | 0.202633E+09 | 0.456466E+12 | 0.511627E+11 | 54850511.03 | 0.00 | 0.274871E+11 | 0.00 |
April | 0.450709E+12 | 0.787449E+11 | 0.165903E+13 | 0.216144E+12 | 0.264850E+12 | 0.160713E+12 | 0.00 | 0.562845E+12 | 0.856499E+11 | 0.00 | 0.00 | 0.225411E+11 | 0.00 |
May | 0.486374E+12 | 0.771301E+11 | 0.774844E+12 | 0.224502E+12 | 0.278732E+12 | 0.164170E+12 | 0.00 | 0.534581E+12 | 0.108282E+12 | 0.00 | 0.00 | 0.215624E+11 | 0.00 |
June | 0.484022E+12 | 0.726699E+11 | 0.106252E+13 | 0.222585E+12 | 0.289144E+12 | 0.189133E+12 | 0.00 | 0.709171E+12 | 0.137307E+12 | 0.00 | 0.00 | 0.195464E+11 | 0.00 |
July | 0.453060E+12 | 0.758228E+11 | 0.139340E+13 | 0.218061E+12 | 0.313519E+12 | 0.215688E+12 | 0.00 | 0.891317E+12 | 0.155892E+12 | 0.00 | 0.00 | 0.180781E+11 | 0.00 |
August | 0.504598E+12 | 0.794755E+11 | 0.173200E+13 | 0.230864E+12 | 0.364932E+12 | 0.232746E+12 | 0.00 | 0.100805E+13 | 0.165346E+12 | 0.00 | 0.00 | 0.206010E+11 | 0.00 |
September | 0.450709E+12 | 0.817056E+11 | 0.740713E+12 | 0.216143E+12 | 0.276950E+12 | 0.179296E+12 | 0.00 | 0.652441E+12 | 0.134421E+12 | 0.00 | 0.00 | 0.205889E+11 | 0.00 |
October | 0.468149E+12 | 0.896647E+11 | 0.108340E+13 | 0.218140E+12 | 0.262897E+12 | 0.175521E+12 | 0.00 | 0.589635E+12 | 0.119958E+12 | 4333396.12 | 0.00 | 0.237258E+11 | 0.00 |
November | 0.462662E+12 | 0.912795E+11 | 0.135889E+13 | 0.209941E+12 | 0.238504E+12 | 0.157702E+12 | 2274344.41 | 0.507158E+12 | 0.826799E+11 | 0.00 | 0.00 | 0.256365E+11 | 0.00 |
December | 0.453060E+12 | 0.968932E+11 | 0.170972E+13 | 0.218060E+12 | 0.238748E+12 | 0.147480E+12 | 0.791876E+09 | 0.475592E+12 | 0.507571E+11 | 0.00 | 0.00 | 0.271916E+11 | 0.00 |
Annual Sum or Average | 0.561074E+13 | 0.100865E+13 | 0.146764E+14 | 0.262311E+13 | 0.313553E+13 | 0.203556E+13 | 0.389978E+10 | 0.697306E+13 | 0.114411E+13 | 0.114161E+09 | 0.00 | 0.280406E+12 | 0.00 |
Minimum of Months | 0.424646E+12 | 0.726699E+11 | 0.740713E+12 | 0.199667E+12 | 0.180367E+12 | 0.127079E+12 | 0.00 | 0.267305E+12 | 0.202738E+11 | 0.00 | 0.00 | 0.180781E+11 | 0.00 |
Maximum of Months | 0.504598E+12 | 0.968932E+11 | 0.173200E+13 | 0.230864E+12 | 0.364932E+12 | 0.232746E+12 | 0.197546E+10 | 0.100805E+13 | 0.165346E+12 | 54977008.04 | 0.00 | 0.283640E+11 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 489900.85 | 02-JAN-08:09 | 64082.80 | 01-JAN-00:10 | 423497.50 | 02-JAN-08:09 | 235096.12 | 02-JAN-08:20 | 167958.79 | 20-JAN-06:10 | 77829.04 | 30-JAN-06:10 | 30364.47 | 20-JAN-06:10 |
February | 489900.85 | 01-FEB-08:09 | 64082.80 | 01-FEB-00:10 | 541788.89 | 01-FEB-08:09 | 235096.12 | 01-FEB-08:20 | 211959.44 | 06-FEB-15:09 | 106917.69 | 06-FEB-14:30 | 27033.67 | 13-FEB-06:10 |
March | 489900.85 | 01-MAR-08:09 | 64082.80 | 01-MAR-00:10 | 660080.29 | 01-MAR-08:09 | 235096.12 | 01-MAR-08:20 | 258850.22 | 27-MAR-14:30 | 110737.18 | 22-MAR-13:50 | 9552.83 | 08-MAR-06:10 |
April | 489900.85 | 03-APR-07:10 | 64082.80 | 01-APR-00:10 | 778371.69 | 03-APR-07:10 | 235096.12 | 03-APR-07:19 | 274550.29 | 28-APR-12:30 | 111136.54 | 26-APR-12:30 | 0.00 | 01-APR-00:10 |
May | 489900.85 | 01-MAY-07:10 | 64082.80 | 01-MAY-00:10 | 423497.50 | 01-MAY-07:10 | 235096.12 | 01-MAY-07:19 | 273109.48 | 10-MAY-14:00 | 108476.13 | 10-MAY-07:00 | 0.00 | 01-MAY-00:10 |
June | 489900.85 | 01-JUN-07:10 | 64082.80 | 01-JUN-00:10 | 541788.89 | 01-JUN-07:10 | 235096.12 | 01-JUN-07:19 | 289933.23 | 09-JUN-15:30 | 108940.26 | 12-JUN-14:09 | 0.00 | 01-JUN-00:10 |
July | 489900.85 | 03-JUL-07:10 | 64082.80 | 01-JUL-00:10 | 660080.29 | 03-JUL-07:10 | 235096.12 | 03-JUL-07:19 | 303832.04 | 21-JUL-14:00 | 112104.97 | 18-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 489900.85 | 01-AUG-07:10 | 64082.80 | 01-AUG-00:10 | 778371.69 | 01-AUG-07:10 | 235096.12 | 01-AUG-07:19 | 318420.45 | 16-AUG-14:09 | 111454.19 | 10-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 489900.85 | 01-SEP-07:10 | 64082.80 | 01-SEP-00:10 | 423497.50 | 01-SEP-07:10 | 235096.12 | 01-SEP-07:19 | 288961.19 | 05-SEP-14:09 | 109502.07 | 07-SEP-14:09 | 0.00 | 01-SEP-00:10 |
October | 489900.85 | 02-OCT-07:10 | 64082.80 | 01-OCT-00:10 | 541788.89 | 02-OCT-07:10 | 235096.12 | 02-OCT-07:19 | 269294.70 | 05-OCT-14:09 | 108405.30 | 06-OCT-15:30 | 0.00 | 01-OCT-00:10 |
November | 489900.85 | 01-NOV-07:10 | 64082.80 | 01-NOV-00:10 | 660080.29 | 01-NOV-07:10 | 235096.12 | 01-NOV-07:19 | 245374.21 | 13-NOV-13:50 | 108527.87 | 01-NOV-14:09 | 842.72 | 22-NOV-06:00 |
December | 489900.85 | 01-DEC-08:09 | 64082.80 | 01-DEC-00:10 | 778371.69 | 01-DEC-08:09 | 235096.12 | 01-DEC-08:20 | 204860.63 | 01-DEC-13:00 | 107525.49 | 20-DEC-13:09 | 26400.38 | 18-DEC-06:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 489900.85 | 64082.80 | 423497.50 | 235096.12 | 167958.79 | 77829.04 | 0.00 | |||||||
Maximum of Months | 489900.85 | 64082.80 | 778371.69 | 235096.12 | 318420.45 | 112104.97 | 30364.47 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 259461.11 | 30-JAN-14:09 | 64095.10 | 30-JAN-13:00 | 2625.55 | 16-JAN-13:09 | 0.00 | 37718.15 | 12-JAN-12:39 | 0.00 |
February | 400820.60 | 07-FEB-13:09 | 64095.10 | 06-FEB-11:20 | 0.00 | 01-FEB-00:10 | 0.00 | 37435.21 | 01-FEB-12:50 | 0.00 |
March | 413823.23 | 28-MAR-14:09 | 64095.10 | 01-MAR-11:39 | 2799.86 | 23-MAR-01:00 | 0.00 | 35061.57 | 01-MAR-12:20 | 0.00 |
April | 449279.34 | 28-APR-14:00 | 64095.10 | 30-APR-14:39 | 0.00 | 01-APR-00:10 | 0.00 | 31707.12 | 03-APR-11:00 | 0.00 |
May | 484609.63 | 31-MAY-15:00 | 64095.10 | 21-MAY-14:00 | 0.00 | 01-MAY-00:10 | 0.00 | 28823.55 | 01-MAY-11:30 | 0.00 |
June | 515194.99 | 08-JUN-14:09 | 64095.10 | 10-JUN-17:10 | 0.00 | 01-JUN-00:10 | 0.00 | 26252.10 | 01-JUN-11:50 | 0.00 |
July | 609301.80 | 19-JUL-14:00 | 64095.10 | 01-JUL-03:09 | 0.00 | 01-JUL-00:10 | 0.00 | 24683.71 | 28-JUL-11:20 | 0.00 |
August | 654821.53 | 10-AUG-15:00 | 64095.10 | 01-AUG-01:00 | 0.00 | 01-AUG-00:10 | 0.00 | 26570.59 | 31-AUG-11:39 | 0.00 |
September | 543363.07 | 07-SEP-14:09 | 64095.10 | 03-SEP-23:30 | 0.00 | 01-SEP-00:10 | 0.00 | 29025.87 | 29-SEP-11:30 | 0.00 |
October | 480875.83 | 06-OCT-15:39 | 64095.10 | 01-OCT-07:10 | 2218.22 | 29-OCT-13:09 | 0.00 | 33061.66 | 31-OCT-11:00 | 0.00 |
November | 486453.80 | 01-NOV-14:09 | 64095.10 | 01-NOV-05:30 | 0.00 | 01-NOV-00:10 | 0.00 | 35633.31 | 30-NOV-12:00 | 0.00 |
December | 408932.24 | 05-DEC-13:09 | 64095.10 | 01-DEC-13:09 | 0.00 | 01-DEC-00:10 | 0.00 | 37553.52 | 28-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 259461.11 | 64095.10 | 0.00 | 0.00 | 24683.71 | 0.00 | ||||
Maximum of Months | 654821.53 | 64095.10 | 2799.86 | 0.00 | 37718.15 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1670188.45 | 30-JAN-15:09 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 133346.14 | 54395.49 | 0.00 | 248521.52 | 64095.10 |
February | 2034143.19 | 06-FEB-15:09 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 211959.44 | 106662.74 | 0.00 | 379093.97 | 48071.33 |
March | 2217283.65 | 27-MAR-15:09 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 256024.54 | 107910.31 | 0.00 | 379363.08 | 64095.10 |
April | 2412734.00 | 28-APR-15:09 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 266485.63 | 108135.78 | 0.00 | 448916.25 | 64095.10 |
May | 2081979.31 | 31-MAY-15:00 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 256656.55 | 108463.76 | 0.00 | 484609.63 | 64095.10 |
June | 2239200.76 | 09-JUN-14:09 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 275133.05 | 108838.21 | 0.00 | 510337.89 | 64095.10 |
July | 2452420.21 | 19-JUL-15:09 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 267900.36 | 110607.84 | 0.00 | 607097.61 | 64095.10 |
August | 2659123.79 | 10-AUG-15:00 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 306380.07 | 111454.19 | 0.00 | 654821.53 | 64095.10 |
September | 2144620.35 | 07-SEP-14:09 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 263362.10 | 109502.07 | 0.00 | 543363.07 | 64095.10 |
October | 2193735.47 | 06-OCT-15:20 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 252340.16 | 108395.28 | 0.00 | 478922.34 | 64095.10 |
November | 2307554.92 | 01-NOV-14:09 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 244520.16 | 108527.87 | 0.00 | 486453.80 | 64095.10 |
December | 2294758.38 | 04-DEC-11:00 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 189384.19 | 106597.66 | 0.00 | 401568.10 | 64095.10 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1670188.45 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 133346.14 | 54395.49 | 0.00 | 248521.52 | 48071.33 | |
Maximum of Months | 2659123.79 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 306380.07 | 111454.19 | 0.00 | 654821.53 | 64095.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 26.30 | 0.00 | 26.30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 26.28 | 0.00 | 26.28 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.12 | 0.00 | 26.12 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 25.79 | 0.00 | 25.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 26.02 | 0.00 | 26.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 25.73 | 0.00 | 25.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 25.83 | 0.00 | 25.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 25.82 | 0.00 | 25.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 25.85 | 0.17 | 25.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 25.84 | 0.00 | 25.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 25.97 | 0.17 | 26.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 25.78 | 0.00 | 25.78 |
Annual Sum or Average | 0.00 | 0.00 | 86.33 | 25.92 | 0.33 | 25.93 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 25.73 | 0.00 | 25.73 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 26.30 | 0.17 | 26.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.67 | 0.00 | 25.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.60 | 0.00 | 25.60 |
Annual Sum or Average | 0.00 | 0.00 | 1.33 | 25.63 | 0.00 | 25.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.67 | 0.00 | 25.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.40 | 1.00 | 27.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.61 | 7.33 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.81 | 7.17 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.85 | 12.17 | 27.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.65 | 8.00 | 27.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.76 | 7.17 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.56 | 2.33 | 27.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 55.00 | 27.73 | 45.17 | 27.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.85 | 12.17 | 27.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.58 | 0.83 | 27.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.96 | 3.67 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 28.09 | 10.33 | 28.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.08 | 8.33 | 28.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 28.31 | 13.67 | 28.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.26 | 8.83 | 28.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 28.16 | 10.00 | 28.17 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.78 | 6.67 | 27.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 63.83 | 28.12 | 62.67 | 28.13 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 28.31 | 13.67 | 28.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.59 | 1.17 | 27.59 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.05 | 2.50 | 28.05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.98 | 2.67 | 27.98 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.73 | 5.17 | 27.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.63 | 6.50 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.60 | 5.33 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.99 | 10.50 | 28.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.08 | 7.67 | 28.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.43 | 9.17 | 28.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 28.56 | 11.17 | 28.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.32 | 9.33 | 28.32 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.04 | 5.33 | 28.04 |
Annual Sum or Average | 0.00 | 0.00 | 81.00 | 28.10 | 76.50 | 28.12 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.59 | 1.17 | 27.59 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 28.56 | 11.17 | 28.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.70 | 1.00 | 27.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.89 | 2.83 | 27.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.97 | 7.83 | 28.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 28.20 | 7.33 | 28.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 28.06 | 7.17 | 28.21 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 28.13 | 12.17 | 28.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 27.69 | 9.17 | 28.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 28.13 | 7.83 | 28.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.94 | 7.83 | 28.08 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.80 | 6.67 | 27.84 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.52 | 1.83 | 27.56 |
Annual Sum or Average | 0.00 | 0.00 | 128.67 | 27.96 | 71.67 | 28.14 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 28.20 | 12.17 | 28.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.74 | 7.33 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.86 | 7.00 | 27.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.95 | 11.67 | 28.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.75 | 7.67 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.85 | 7.33 | 27.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.58 | 1.50 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 53.50 | 27.83 | 42.83 | 27.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.95 | 11.67 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.48 | 0.50 | 27.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.96 | 4.00 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.24 | 11.33 | 28.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.30 | 9.17 | 28.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 28.54 | 13.67 | 28.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.47 | 9.17 | 28.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 28.32 | 10.50 | 28.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.81 | 7.50 | 27.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 69.17 | 28.29 | 65.83 | 28.31 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 28.54 | 13.67 | 28.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.63 | 0.50 | 27.63 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.03 | 2.00 | 28.03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.11 | 1.67 | 28.11 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.70 | 3.17 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.70 | 6.33 | 27.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.65 | 5.67 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 28.05 | 10.00 | 28.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.09 | 7.50 | 28.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 28.47 | 9.00 | 28.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.55 | 11.00 | 28.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.24 | 8.50 | 28.25 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.98 | 3.50 | 27.98 |
Annual Sum or Average | 0.00 | 0.00 | 74.67 | 28.13 | 68.83 | 28.16 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.63 | 0.50 | 27.63 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.55 | 11.00 | 28.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.01 | 0.83 | 28.01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.94 | 3.50 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.60 | 6.00 | 28.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.45 | 5.67 | 28.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 28.53 | 9.83 | 28.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 28.62 | 7.00 | 28.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.56 | 6.33 | 28.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.20 | 5.50 | 28.23 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.61 | 0.83 | 27.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 61.00 | 28.45 | 45.67 | 28.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 28.62 | 9.83 | 28.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.61 | 1.00 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.09 | 8.33 | 28.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 28.21 | 7.67 | 28.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 28.28 | 12.00 | 28.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 28.22 | 7.67 | 28.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.16 | 8.00 | 28.19 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.68 | 4.00 | 27.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 63.33 | 28.16 | 48.67 | 28.21 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 28.28 | 12.00 | 28.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.38 | 0.67 | 27.38 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.95 | 5.83 | 27.95 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 28.56 | 11.50 | 28.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.63 | 9.17 | 28.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 28.77 | 14.33 | 28.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 28.71 | 9.17 | 28.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 28.61 | 11.00 | 28.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.97 | 9.00 | 27.97 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 80.50 | 28.52 | 70.67 | 28.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 28.77 | 14.33 | 28.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.34 | 0.33 | 27.34 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.26 | 1.33 | 28.26 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.45 | 1.33 | 28.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.87 | 4.17 | 27.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.11 | 7.83 | 28.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.09 | 6.50 | 28.13 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 28.37 | 10.83 | 28.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 28.42 | 7.50 | 28.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 28.71 | 9.17 | 28.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 28.73 | 10.83 | 28.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.23 | 8.00 | 28.23 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.15 | 2.17 | 28.15 |
Annual Sum or Average | 0.00 | 0.00 | 80.83 | 28.37 | 70.00 | 28.41 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.34 | 0.33 | 27.34 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 28.73 | 10.83 | 28.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.39 | 0.33 | 27.39 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.05 | 0.83 | 28.11 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.20 | 3.67 | 28.23 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 28.69 | 7.17 | 28.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 28.66 | 6.83 | 28.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 28.78 | 10.83 | 28.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 28.71 | 7.67 | 28.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.74 | 7.00 | 28.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.37 | 6.00 | 28.41 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.69 | 1.00 | 27.69 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 71.50 | 28.62 | 51.33 | 28.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 28.78 | 10.83 | 28.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.66 | 0.33 | 27.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.86 | 1.33 | 27.85 |
Annual Sum or Average | 0.00 | 0.00 | 13.50 | 27.85 | 1.67 | 27.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.86 | 1.33 | 27.85 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 471.67 | 24.65 | 0.00 | 24.65 |
February | 3.50 | 27.10 | 439.67 | 24.63 | 3.50 | 24.65 |
March | 0.00 | 0.00 | 490.50 | 24.51 | 0.00 | 24.51 |
April | 1.67 | 27.16 | 451.17 | 24.63 | 1.67 | 24.64 |
May | 4.50 | 27.03 | 477.33 | 24.62 | 4.50 | 24.64 |
June | 30.67 | 26.93 | 490.67 | 24.66 | 30.67 | 24.79 |
July | 36.50 | 26.95 | 473.00 | 24.85 | 36.50 | 24.99 |
August | 31.00 | 26.92 | 487.67 | 24.68 | 31.00 | 24.80 |
September | 45.00 | 26.93 | 481.17 | 24.80 | 45.00 | 24.97 |
October | 37.33 | 26.87 | 491.00 | 24.81 | 37.33 | 24.95 |
November | 3.17 | 27.11 | 484.33 | 24.67 | 3.17 | 24.69 |
December | 6.17 | 27.08 | 487.17 | 24.68 | 6.17 | 24.71 |
Annual Sum or Average | 199.50 | 26.93 | 5725.33 | 24.69 | 199.50 | 24.76 |
Minimum of Months | 0.00 | 0.00 | 439.67 | 24.51 | 0.00 | 24.51 |
Maximum of Months | 45.00 | 27.16 | 491.00 | 24.85 | 45.00 | 24.99 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.33 | 23.60 | 444.83 | 24.37 | 0.00 | 24.37 |
February | 1.50 | 27.13 | 433.67 | 24.38 | 1.50 | 24.39 |
March | 0.00 | 0.00 | 500.00 | 24.32 | 0.00 | 24.32 |
April | 0.00 | 0.00 | 477.67 | 24.28 | 0.00 | 24.28 |
May | 0.00 | 0.00 | 495.50 | 24.23 | 0.00 | 24.23 |
June | 0.00 | 0.00 | 496.00 | 24.17 | 0.00 | 24.17 |
July | 0.00 | 0.00 | 497.00 | 24.18 | 0.00 | 24.18 |
August | 0.00 | 0.00 | 514.00 | 24.14 | 0.00 | 24.14 |
September | 0.00 | 0.00 | 485.00 | 24.22 | 0.00 | 24.22 |
October | 0.00 | 0.00 | 494.50 | 24.30 | 0.00 | 24.30 |
November | 0.17 | 27.19 | 483.83 | 24.38 | 0.17 | 24.38 |
December | 1.33 | 27.15 | 486.00 | 24.42 | 1.33 | 24.42 |
Annual Sum or Average | 7.33 | 25.05 | 5808.00 | 24.28 | 3.00 | 24.28 |
Minimum of Months | 0.00 | 0.00 | 433.67 | 24.14 | 0.00 | 24.14 |
Maximum of Months | 4.33 | 27.19 | 514.00 | 24.42 | 1.50 | 24.42 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 68.67 | 23.28 | 309.50 | 24.06 | 0.00 | 24.06 |
February | 32.50 | 23.22 | 339.17 | 24.14 | 0.00 | 24.14 |
March | 16.50 | 23.27 | 391.83 | 24.20 | 0.00 | 24.20 |
April | 5.50 | 23.46 | 426.00 | 24.18 | 0.00 | 24.18 |
May | 0.00 | 0.00 | 484.17 | 24.18 | 0.00 | 24.18 |
June | 0.00 | 0.00 | 494.83 | 24.12 | 0.00 | 24.12 |
July | 0.00 | 0.00 | 489.83 | 24.06 | 0.00 | 24.06 |
August | 0.00 | 0.00 | 512.50 | 24.06 | 0.00 | 24.06 |
September | 0.00 | 0.00 | 482.67 | 24.15 | 0.00 | 24.15 |
October | 4.50 | 23.67 | 473.50 | 24.23 | 0.00 | 24.23 |
November | 4.00 | 23.53 | 466.00 | 24.21 | 0.00 | 24.21 |
December | 38.33 | 23.28 | 366.67 | 24.10 | 0.00 | 24.10 |
Annual Sum or Average | 170.00 | 23.29 | 5236.67 | 24.14 | 0.00 | 24.14 |
Minimum of Months | 0.00 | 0.00 | 309.50 | 24.06 | 0.00 | 24.06 |
Maximum of Months | 68.67 | 23.67 | 512.50 | 24.23 | 0.00 | 24.23 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 256.67 | 22.77 | 183.50 | 23.27 | 13.50 | 23.27 |
February | 158.67 | 22.82 | 234.83 | 23.58 | 0.00 | 23.58 |
March | 106.00 | 22.98 | 322.00 | 23.86 | 0.00 | 23.86 |
April | 30.50 | 23.05 | 396.00 | 24.11 | 0.00 | 24.11 |
May | 0.00 | 0.00 | 488.50 | 24.24 | 0.00 | 24.24 |
June | 0.00 | 0.00 | 492.50 | 24.18 | 0.00 | 24.18 |
July | 0.00 | 0.00 | 493.67 | 24.17 | 0.00 | 24.17 |
August | 0.00 | 0.00 | 511.83 | 24.12 | 0.00 | 24.12 |
September | 0.00 | 0.00 | 479.33 | 24.21 | 0.00 | 24.21 |
October | 4.33 | 23.22 | 467.17 | 24.22 | 0.00 | 24.22 |
November | 32.17 | 23.03 | 376.00 | 24.03 | 0.00 | 24.03 |
December | 193.67 | 22.76 | 229.83 | 23.46 | 0.00 | 23.46 |
Annual Sum or Average | 782.00 | 22.83 | 4675.17 | 23.97 | 13.50 | 23.97 |
Minimum of Months | 0.00 | 0.00 | 183.50 | 23.27 | 0.00 | 23.27 |
Maximum of Months | 256.67 | 23.22 | 511.83 | 24.24 | 13.50 | 24.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 244.50 | 22.49 | 175.17 | 23.14 | 0.00 | 23.14 |
February | 140.83 | 22.52 | 234.33 | 23.53 | 0.00 | 23.53 |
March | 93.50 | 22.63 | 356.67 | 23.84 | 0.00 | 23.84 |
April | 47.17 | 23.25 | 418.83 | 24.16 | 6.17 | 24.19 |
May | 31.00 | 26.60 | 489.17 | 24.54 | 30.67 | 24.66 |
June | 32.67 | 26.72 | 495.00 | 24.50 | 32.67 | 24.63 |
July | 53.67 | 26.88 | 497.00 | 24.72 | 53.67 | 24.91 |
August | 35.17 | 26.86 | 514.00 | 24.51 | 35.17 | 24.65 |
September | 37.50 | 26.57 | 475.50 | 24.56 | 37.50 | 24.69 |
October | 23.83 | 25.72 | 467.00 | 24.42 | 18.50 | 24.50 |
November | 30.83 | 22.79 | 415.67 | 24.12 | 0.33 | 24.12 |
December | 120.50 | 22.57 | 294.83 | 23.65 | 0.00 | 23.65 |
Annual Sum or Average | 891.17 | 23.56 | 4833.17 | 24.19 | 214.67 | 24.28 |
Minimum of Months | 23.83 | 22.49 | 175.17 | 23.14 | 0.00 | 23.14 |
Maximum of Months | 244.50 | 26.88 | 514.00 | 24.72 | 53.67 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 242.67 | 22.23 | 191.50 | 23.04 | 0.50 | 23.05 |
February | 177.17 | 22.25 | 232.83 | 23.33 | 0.67 | 23.34 |
March | 149.33 | 22.32 | 308.50 | 23.54 | 3.00 | 23.56 |
April | 92.00 | 23.13 | 373.83 | 24.02 | 19.17 | 24.13 |
May | 56.50 | 25.66 | 475.17 | 24.50 | 41.83 | 24.67 |
June | 42.17 | 26.09 | 475.33 | 24.40 | 36.33 | 24.55 |
July | 55.33 | 26.85 | 488.67 | 24.61 | 55.33 | 24.82 |
August | 36.83 | 26.80 | 507.17 | 24.39 | 36.83 | 24.54 |
September | 57.17 | 25.91 | 457.50 | 24.52 | 46.17 | 24.70 |
October | 66.00 | 24.47 | 442.33 | 24.32 | 32.83 | 24.45 |
November | 80.33 | 22.57 | 361.00 | 23.90 | 4.17 | 23.92 |
December | 192.50 | 22.25 | 243.83 | 23.24 | 0.17 | 23.24 |
Annual Sum or Average | 1248.00 | 23.25 | 4557.67 | 24.03 | 277.00 | 24.15 |
Minimum of Months | 36.83 | 22.23 | 191.50 | 23.04 | 0.17 | 23.05 |
Maximum of Months | 242.67 | 26.85 | 507.17 | 24.61 | 55.33 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 196.17 | 22.53 | 265.00 | 23.58 | 8.67 | 23.64 |
February | 136.50 | 22.69 | 278.67 | 23.78 | 11.50 | 23.86 |
March | 116.50 | 22.79 | 353.83 | 23.88 | 10.67 | 23.94 |
April | 78.33 | 23.64 | 398.00 | 24.17 | 22.33 | 24.28 |
May | 41.17 | 25.32 | 466.17 | 24.44 | 27.83 | 24.55 |
June | 26.00 | 26.45 | 483.17 | 24.37 | 25.83 | 24.47 |
July | 44.33 | 26.79 | 496.00 | 24.59 | 44.33 | 24.75 |
August | 32.67 | 26.92 | 514.00 | 24.45 | 32.67 | 24.59 |
September | 42.67 | 26.81 | 467.17 | 24.62 | 41.67 | 24.80 |
October | 63.83 | 26.00 | 459.00 | 24.68 | 48.83 | 24.87 |
November | 75.50 | 24.86 | 424.00 | 24.49 | 39.67 | 24.67 |
December | 128.33 | 23.15 | 336.50 | 24.02 | 23.50 | 24.15 |
Annual Sum or Average | 982.00 | 23.90 | 4941.50 | 24.28 | 337.50 | 24.41 |
Minimum of Months | 26.00 | 22.53 | 265.00 | 23.58 | 8.67 | 23.64 |
Maximum of Months | 196.17 | 26.92 | 514.00 | 24.68 | 48.83 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 215.50 | 22.08 | 223.33 | 23.11 | 0.83 | 23.12 |
February | 102.67 | 22.38 | 301.83 | 23.79 | 6.00 | 23.83 |
March | 61.83 | 23.40 | 419.83 | 24.21 | 14.67 | 24.28 |
April | 53.33 | 26.48 | 455.00 | 24.63 | 50.00 | 24.82 |
May | 52.33 | 26.16 | 467.67 | 24.57 | 45.50 | 24.74 |
June | 63.83 | 26.12 | 495.33 | 24.51 | 63.83 | 24.67 |
July | 105.17 | 25.81 | 497.00 | 24.71 | 105.17 | 24.87 |
August | 114.83 | 25.36 | 514.00 | 24.57 | 114.83 | 24.69 |
September | 52.83 | 26.55 | 464.67 | 24.58 | 51.17 | 24.77 |
October | 47.33 | 26.66 | 470.00 | 24.59 | 45.67 | 24.77 |
November | 37.00 | 26.19 | 455.00 | 24.48 | 32.83 | 24.62 |
December | 58.33 | 23.68 | 414.83 | 24.25 | 17.83 | 24.34 |
Annual Sum or Average | 965.00 | 24.45 | 5178.50 | 24.37 | 548.33 | 24.52 |
Minimum of Months | 37.00 | 22.08 | 223.33 | 23.11 | 0.83 | 23.12 |
Maximum of Months | 215.50 | 26.66 | 514.00 | 24.71 | 114.83 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 382.17 | 22.15 | 70.83 | 22.40 | 0.00 | 22.40 |
February | 270.50 | 22.26 | 135.33 | 22.84 | 0.83 | 22.84 |
March | 209.33 | 22.42 | 240.00 | 23.31 | 0.00 | 23.31 |
April | 90.83 | 22.76 | 360.83 | 23.95 | 13.67 | 23.97 |
May | 41.67 | 26.05 | 481.33 | 24.58 | 35.67 | 24.71 |
June | 45.33 | 26.63 | 494.17 | 24.59 | 45.33 | 24.75 |
July | 65.67 | 26.73 | 495.67 | 24.80 | 65.67 | 25.00 |
August | 46.33 | 26.66 | 514.00 | 24.60 | 46.33 | 24.76 |
September | 53.00 | 26.26 | 470.00 | 24.63 | 50.67 | 24.79 |
October | 54.67 | 24.29 | 442.83 | 24.37 | 27.50 | 24.45 |
November | 102.17 | 22.50 | 321.33 | 23.72 | 0.17 | 23.72 |
December | 308.33 | 22.26 | 132.33 | 22.76 | 2.67 | 22.76 |
Annual Sum or Average | 1670.00 | 23.00 | 4158.67 | 23.95 | 288.50 | 24.07 |
Minimum of Months | 41.67 | 22.15 | 70.83 | 22.40 | 0.00 | 22.40 |
Maximum of Months | 382.17 | 26.73 | 514.00 | 24.80 | 65.67 | 25.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 314.33 | 21.99 | 61.83 | 22.33 | 0.33 | 22.33 |
February | 226.00 | 22.02 | 121.83 | 22.75 | 0.83 | 22.76 |
March | 194.00 | 22.18 | 194.83 | 23.19 | 1.67 | 23.21 |
April | 115.50 | 23.16 | 291.50 | 24.06 | 30.33 | 24.21 |
May | 64.50 | 25.84 | 392.33 | 24.73 | 50.33 | 24.93 |
June | 51.50 | 26.51 | 400.00 | 24.67 | 49.00 | 24.87 |
July | 67.83 | 26.79 | 415.33 | 24.88 | 67.17 | 25.12 |
August | 48.50 | 26.76 | 430.00 | 24.65 | 48.50 | 24.84 |
September | 68.00 | 26.07 | 382.00 | 24.76 | 58.00 | 24.98 |
October | 84.67 | 24.59 | 358.17 | 24.53 | 47.17 | 24.70 |
November | 115.33 | 22.33 | 257.00 | 23.66 | 2.67 | 23.68 |
December | 272.67 | 22.07 | 100.83 | 22.59 | 2.17 | 22.60 |
Annual Sum or Average | 1622.83 | 23.08 | 3405.67 | 23.99 | 358.17 | 24.16 |
Minimum of Months | 48.50 | 21.99 | 61.83 | 22.33 | 0.33 | 22.33 |
Maximum of Months | 314.33 | 26.79 | 430.00 | 24.88 | 67.17 | 25.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 241.67 | 22.27 | 233.83 | 23.32 | 5.17 | 23.36 |
February | 195.33 | 22.48 | 234.50 | 23.48 | 9.83 | 23.55 |
March | 171.33 | 22.47 | 299.83 | 23.59 | 7.33 | 23.64 |
April | 110.17 | 22.99 | 359.83 | 23.99 | 23.83 | 24.07 |
May | 50.33 | 25.09 | 460.67 | 24.47 | 31.83 | 24.59 |
June | 39.00 | 26.33 | 480.17 | 24.48 | 38.17 | 24.61 |
July | 55.00 | 26.60 | 495.00 | 24.67 | 55.00 | 24.84 |
August | 42.33 | 26.69 | 514.00 | 24.55 | 42.33 | 24.70 |
September | 59.00 | 26.40 | 465.33 | 24.69 | 54.50 | 24.88 |
October | 86.33 | 25.51 | 452.83 | 24.71 | 61.00 | 24.91 |
November | 104.50 | 24.02 | 384.33 | 24.36 | 38.00 | 24.54 |
December | 203.17 | 22.67 | 271.67 | 23.66 | 20.17 | 23.78 |
Annual Sum or Average | 1358.17 | 23.50 | 4652.00 | 24.20 | 387.17 | 24.34 |
Minimum of Months | 39.00 | 22.27 | 233.83 | 23.32 | 5.17 | 23.36 |
Maximum of Months | 241.67 | 26.69 | 514.00 | 24.71 | 61.00 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 364.67 | 21.93 | 91.83 | 22.35 | 0.00 | 22.35 |
February | 270.67 | 22.04 | 143.17 | 22.73 | 1.50 | 22.74 |
March | 211.67 | 22.15 | 246.50 | 23.22 | 3.17 | 23.24 |
April | 127.00 | 22.86 | 346.83 | 23.89 | 27.33 | 24.00 |
May | 74.17 | 24.52 | 444.83 | 24.44 | 35.83 | 24.59 |
June | 54.67 | 26.15 | 454.67 | 24.57 | 47.33 | 24.75 |
July | 63.50 | 26.70 | 487.17 | 24.67 | 62.33 | 24.89 |
August | 52.17 | 26.69 | 507.50 | 24.53 | 52.17 | 24.72 |
September | 71.17 | 25.44 | 434.33 | 24.57 | 51.33 | 24.76 |
October | 97.17 | 23.86 | 411.33 | 24.26 | 38.17 | 24.41 |
November | 136.50 | 22.25 | 301.67 | 23.55 | 5.17 | 23.58 |
December | 301.17 | 22.01 | 149.50 | 22.67 | 2.00 | 22.67 |
Annual Sum or Average | 1824.50 | 22.85 | 4019.33 | 23.85 | 326.33 | 23.99 |
Minimum of Months | 52.17 | 21.93 | 91.83 | 22.35 | 0.00 | 22.35 |
Maximum of Months | 364.67 | 26.70 | 507.50 | 24.67 | 62.33 | 24.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 419.17 | 21.74 | 54.83 | 21.85 | 12.83 | 21.79 |
February | 303.33 | 21.88 | 116.33 | 22.41 | 4.33 | 22.40 |
March | 248.33 | 22.09 | 210.17 | 22.98 | 0.17 | 22.98 |
April | 125.50 | 22.51 | 338.33 | 23.75 | 17.67 | 23.79 |
May | 65.17 | 25.14 | 459.33 | 24.54 | 40.67 | 24.70 |
June | 51.67 | 26.50 | 481.83 | 24.60 | 50.00 | 24.77 |
July | 73.33 | 26.70 | 494.17 | 24.80 | 73.33 | 25.01 |
August | 51.83 | 26.57 | 513.00 | 24.58 | 51.83 | 24.74 |
September | 71.67 | 25.54 | 451.50 | 24.59 | 55.50 | 24.77 |
October | 93.17 | 23.79 | 416.50 | 24.26 | 37.83 | 24.37 |
November | 160.17 | 22.26 | 272.67 | 23.38 | 2.00 | 23.38 |
December | 359.67 | 21.88 | 107.50 | 22.27 | 9.67 | 22.25 |
Annual Sum or Average | 2023.00 | 22.68 | 3916.17 | 23.74 | 355.83 | 23.87 |
Minimum of Months | 51.67 | 21.74 | 54.83 | 21.85 | 0.17 | 21.79 |
Maximum of Months | 419.17 | 26.70 | 513.00 | 24.80 | 73.33 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 373.17 | 21.79 | 83.83 | 22.07 | 7.67 | 22.03 |
February | 251.67 | 21.80 | 165.83 | 22.64 | 2.83 | 22.63 |
March | 215.50 | 22.03 | 252.67 | 23.14 | 2.33 | 23.16 |
April | 131.33 | 23.10 | 358.17 | 24.00 | 36.33 | 24.14 |
May | 76.83 | 25.48 | 463.17 | 24.62 | 53.00 | 24.82 |
June | 56.83 | 26.38 | 469.67 | 24.61 | 51.33 | 24.80 |
July | 77.17 | 26.75 | 486.00 | 24.81 | 76.00 | 25.05 |
August | 58.67 | 26.54 | 505.50 | 24.59 | 58.67 | 24.77 |
September | 77.83 | 25.85 | 444.67 | 24.68 | 62.00 | 24.90 |
October | 106.17 | 24.41 | 424.33 | 24.43 | 56.67 | 24.62 |
November | 139.83 | 22.19 | 310.50 | 23.54 | 3.33 | 23.56 |
December | 324.33 | 21.87 | 126.83 | 22.39 | 7.50 | 22.39 |
Annual Sum or Average | 1889.33 | 22.91 | 4091.17 | 23.87 | 417.67 | 24.04 |
Minimum of Months | 56.83 | 21.79 | 83.83 | 22.07 | 2.33 | 22.03 |
Maximum of Months | 373.17 | 26.75 | 505.50 | 24.81 | 76.00 | 25.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 273.33 | 21.79 | 213.33 | 22.87 | 9.00 | 22.85 |
February | 226.33 | 22.06 | 211.00 | 23.11 | 10.33 | 23.16 |
March | 207.50 | 22.18 | 272.50 | 23.32 | 7.00 | 23.37 |
April | 141.83 | 22.78 | 337.00 | 23.83 | 30.83 | 23.94 |
May | 79.83 | 24.38 | 441.33 | 24.41 | 37.50 | 24.56 |
June | 54.17 | 25.66 | 455.00 | 24.50 | 42.50 | 24.65 |
July | 63.83 | 26.55 | 488.33 | 24.68 | 62.33 | 24.88 |
August | 48.33 | 26.58 | 506.67 | 24.53 | 48.33 | 24.70 |
September | 75.17 | 25.67 | 443.67 | 24.66 | 57.50 | 24.86 |
October | 109.83 | 24.72 | 431.17 | 24.57 | 61.00 | 24.78 |
November | 141.00 | 23.30 | 347.83 | 24.09 | 35.00 | 24.26 |
December | 248.83 | 22.21 | 239.00 | 23.24 | 22.50 | 23.32 |
Annual Sum or Average | 1670.00 | 23.09 | 4386.83 | 24.02 | 423.83 | 24.17 |
Minimum of Months | 48.33 | 21.79 | 211.00 | 22.87 | 7.00 | 22.85 |
Maximum of Months | 273.33 | 26.58 | 506.67 | 24.68 | 62.33 | 24.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 380.00 | 21.62 | 94.17 | 22.02 | 8.00 | 21.99 |
February | 289.33 | 21.80 | 134.00 | 22.48 | 3.50 | 22.49 |
March | 244.33 | 21.97 | 225.50 | 22.98 | 3.67 | 23.00 |
April | 149.50 | 22.62 | 329.00 | 23.73 | 30.67 | 23.85 |
May | 102.33 | 24.07 | 431.17 | 24.35 | 45.33 | 24.52 |
June | 91.83 | 25.00 | 441.00 | 24.48 | 62.50 | 24.67 |
July | 91.00 | 26.02 | 468.33 | 24.69 | 86.67 | 24.89 |
August | 72.00 | 25.96 | 485.17 | 24.53 | 69.67 | 24.70 |
September | 102.67 | 24.68 | 418.67 | 24.47 | 59.50 | 24.67 |
October | 121.67 | 23.45 | 389.67 | 24.13 | 41.33 | 24.29 |
November | 176.83 | 22.10 | 270.00 | 23.30 | 7.33 | 23.35 |
December | 333.83 | 21.76 | 136.83 | 22.36 | 8.00 | 22.35 |
Annual Sum or Average | 2155.33 | 22.65 | 3823.50 | 23.69 | 426.17 | 23.85 |
Minimum of Months | 72.00 | 21.62 | 94.17 | 22.02 | 3.50 | 21.99 |
Maximum of Months | 380.00 | 26.02 | 485.17 | 24.69 | 86.67 | 24.89 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 64.33 | 27.00 | 454.00 | 27.00 | 64.33 | 27.00 |
March | 186.17 | 27.00 | 514.00 | 27.00 | 186.17 | 27.00 |
April | 284.00 | 27.00 | 485.00 | 27.00 | 284.00 | 27.00 |
May | 162.17 | 27.00 | 508.00 | 27.00 | 162.17 | 27.00 |
June | 267.67 | 27.00 | 496.00 | 27.00 | 267.67 | 27.00 |
July | 389.83 | 27.00 | 497.00 | 27.00 | 389.83 | 27.00 |
August | 493.83 | 27.00 | 514.00 | 27.00 | 493.83 | 27.00 |
September | 207.00 | 27.00 | 485.00 | 27.00 | 207.00 | 27.00 |
October | 208.83 | 27.00 | 502.00 | 27.00 | 208.83 | 27.00 |
November | 216.67 | 27.00 | 489.00 | 27.00 | 216.67 | 27.00 |
December | 224.00 | 27.00 | 497.00 | 27.00 | 224.00 | 27.00 |
Annual Sum or Average | 2704.50 | 27.00 | 5943.00 | 27.00 | 2704.50 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 493.83 | 27.00 | 514.00 | 27.00 | 493.83 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 11.17 | 27.00 | 514.00 | 27.00 | 11.17 | 27.00 |
April | 64.50 | 27.00 | 485.00 | 27.00 | 64.50 | 27.00 |
May | 76.67 | 27.00 | 508.00 | 27.00 | 76.67 | 27.00 |
June | 148.67 | 27.00 | 496.00 | 27.00 | 148.67 | 27.00 |
July | 192.67 | 27.00 | 497.00 | 27.00 | 192.67 | 27.00 |
August | 238.83 | 27.00 | 514.00 | 27.00 | 238.83 | 27.00 |
September | 122.83 | 27.00 | 485.00 | 27.00 | 122.83 | 27.00 |
October | 68.50 | 27.00 | 502.00 | 27.00 | 68.50 | 27.00 |
November | 40.83 | 27.00 | 489.00 | 27.00 | 40.83 | 27.00 |
December | 6.33 | 27.00 | 497.00 | 27.00 | 6.33 | 27.00 |
Annual Sum or Average | 971.00 | 27.00 | 5943.00 | 27.00 | 971.00 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 238.83 | 27.00 | 514.00 | 27.00 | 238.83 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 10.00 | 27.00 | 454.00 | 27.00 | 10.00 | 27.00 |
March | 64.83 | 27.00 | 514.00 | 27.00 | 64.83 | 27.00 |
April | 139.83 | 27.00 | 485.00 | 27.00 | 139.83 | 27.00 |
May | 177.00 | 27.00 | 508.00 | 27.00 | 177.00 | 27.00 |
June | 237.50 | 27.00 | 496.00 | 27.00 | 237.50 | 27.00 |
July | 269.17 | 27.00 | 497.00 | 27.00 | 269.17 | 27.00 |
August | 298.83 | 27.00 | 514.00 | 27.00 | 298.83 | 27.00 |
September | 194.00 | 27.00 | 485.00 | 27.00 | 194.00 | 27.00 |
October | 146.00 | 27.00 | 502.00 | 27.00 | 146.00 | 27.00 |
November | 87.50 | 27.00 | 489.00 | 27.00 | 87.50 | 27.00 |
December | 26.67 | 27.00 | 497.00 | 27.00 | 26.67 | 27.00 |
Annual Sum or Average | 1651.33 | 27.00 | 5943.00 | 27.00 | 1651.33 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 298.83 | 27.00 | 514.00 | 27.00 | 298.83 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 26.99 | 454.00 | 26.99 | 454.00 | 26.99 |
March | 514.00 | 26.98 | 514.00 | 26.98 | 514.00 | 26.98 |
April | 485.00 | 26.98 | 485.00 | 26.98 | 485.00 | 26.98 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 26.99 | 496.00 | 26.99 | 496.00 | 26.99 |
July | 497.00 | 26.98 | 497.00 | 26.98 | 497.00 | 26.98 |
August | 514.00 | 26.98 | 514.00 | 26.98 | 514.00 | 26.98 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 26.99 | 502.00 | 26.99 | 502.00 | 26.99 |
November | 489.00 | 26.98 | 489.00 | 26.98 | 489.00 | 26.98 |
December | 497.00 | 26.98 | 497.00 | 26.98 | 497.00 | 26.98 |
Annual Sum or Average | 5943.00 | 26.99 | 5943.00 | 26.99 | 5943.00 | 26.99 |
Minimum of Months | 454.00 | 26.98 | 454.00 | 26.98 | 454.00 | 26.98 |
Maximum of Months | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00067 | 34.19660 | 0.91743 | 22.84516 |
February | 454.00000 | 27.00068 | 34.20119 | 0.96646 | 24.79237 |
March | 514.00000 | 27.00034 | 33.43549 | 1.00923 | 26.56475 |
April | 485.00000 | 27.00010 | 33.93173 | 1.05444 | 28.50936 |
May | 508.00000 | 27.00103 | 38.11072 | 0.36417 | 7.88401 |
June | 496.00000 | 27.00120 | 38.99234 | 0.42145 | 8.81365 |
July | 497.00000 | 27.00049 | 39.02596 | 0.47123 | 9.73462 |
August | 514.00000 | 27.00061 | 38.09338 | 0.50967 | 10.51355 |
September | 485.00000 | 27.00102 | 41.74018 | 0.39787 | 8.40952 |
October | 502.00000 | 27.00113 | 37.11594 | 1.03177 | 27.52734 |
November | 489.00000 | 27.00051 | 35.00459 | 1.03620 | 27.71514 |
December | 497.00000 | 27.00008 | 33.55488 | 1.03137 | 27.50436 |
Annual Sum or Average | 5943.00000 | 27.00065 | 36.46026 | 0.76559 | 19.17277 |
Minimum of Months | 454.00000 | 27.00008 | 33.43549 | 0.36417 | 7.88401 |
Maximum of Months | 514.00000 | 27.00120 | 41.74018 | 1.05444 | 28.50936 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00063 | 34.46383 | 0.84910 | 20.30721 |
February | 454.00000 | 27.00068 | 34.36420 | 0.88107 | 21.47766 |
March | 514.00000 | 27.00036 | 33.51533 | 0.91600 | 22.81270 |
April | 485.00000 | 27.00011 | 34.00521 | 0.96020 | 24.55154 |
May | 508.00000 | 27.00096 | 38.33469 | 0.31627 | 7.22229 |
June | 496.00000 | 27.00123 | 39.18773 | 0.35552 | 7.75743 |
July | 497.00000 | 27.00050 | 39.19568 | 0.37778 | 8.10170 |
August | 514.00000 | 27.00067 | 38.22284 | 0.39946 | 8.44841 |
September | 485.00000 | 27.00088 | 42.13624 | 0.34800 | 7.64766 |
October | 502.00000 | 27.00115 | 37.31130 | 0.97461 | 25.13192 |
November | 489.00000 | 27.00054 | 35.13398 | 0.94486 | 23.93729 |
December | 497.00000 | 27.00010 | 33.64163 | 0.90163 | 22.25121 |
Annual Sum or Average | 5943.00000 | 27.00065 | 36.63575 | 0.68333 | 16.58312 |
Minimum of Months | 454.00000 | 27.00010 | 33.51533 | 0.31627 | 7.22229 |
Maximum of Months | 514.00000 | 27.00123 | 42.13624 | 0.97461 | 25.13192 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00118 | 34.60852 | 0.81864 | 19.32917 |
February | 454.00000 | 27.00071 | 34.40712 | 0.86313 | 20.91612 |
March | 514.00000 | 27.00039 | 33.52218 | 0.90958 | 22.66262 |
April | 485.00000 | 27.00013 | 34.04475 | 0.96812 | 24.95505 |
May | 508.00000 | 27.00094 | 38.20945 | 0.34848 | 7.81092 |
June | 496.00000 | 27.00124 | 39.08364 | 0.39236 | 8.46589 |
July | 497.00000 | 27.00059 | 39.12416 | 0.42306 | 8.98639 |
August | 514.00000 | 27.00048 | 38.32749 | 0.43999 | 9.27523 |
September | 485.00000 | 27.00087 | 41.92136 | 0.37762 | 8.22746 |
October | 502.00000 | 27.00117 | 37.27943 | 0.98513 | 25.62349 |
November | 489.00000 | 27.00060 | 35.14575 | 0.93833 | 23.75096 |
December | 497.00000 | 27.00018 | 33.67248 | 0.87594 | 21.37691 |
Annual Sum or Average | 5943.00000 | 27.00071 | 36.62207 | 0.69322 | 16.73288 |
Minimum of Months | 454.00000 | 27.00013 | 33.52218 | 0.34848 | 7.81092 |
Maximum of Months | 514.00000 | 27.00124 | 41.92136 | 0.98513 | 25.62349 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99828 | 43.06083 | 1.23444 | 37.02638 |
February | 454.00000 | 26.99140 | 46.59157 | 1.40488 | 45.80261 |
March | 514.00000 | 26.98409 | 42.51459 | 1.50530 | 51.19455 |
April | 485.00000 | 26.98234 | 43.26692 | 1.63610 | 58.30185 |
May | 508.00000 | 26.99831 | 58.66400 | 0.79728 | 18.66871 |
June | 496.00000 | 26.98901 | 52.28832 | 0.95438 | 24.26354 |
July | 497.00000 | 26.98327 | 46.18260 | 1.10733 | 30.87708 |
August | 514.00000 | 26.97740 | 45.58475 | 1.30916 | 40.75179 |
September | 485.00000 | 26.99715 | 70.44389 | 0.94706 | 23.99941 |
October | 502.00000 | 26.99059 | 50.89030 | 1.48181 | 49.92366 |
November | 489.00000 | 26.98299 | 45.97863 | 1.57518 | 54.99373 |
December | 497.00000 | 26.98413 | 43.93020 | 1.67056 | 60.16299 |
Annual Sum or Average | 5943.00000 | 26.98821 | 49.09217 | 1.30071 | 41.27160 |
Minimum of Months | 454.00000 | 26.97740 | 42.51459 | 0.79728 | 18.66871 |
Maximum of Months | 514.00000 | 26.99831 | 70.44389 | 1.67056 | 60.16299 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.61370 | 44.71503 | 0.58461 | 12.82417 |
February | 454.00000 | 24.58897 | 46.22308 | 0.58945 | 12.94111 |
March | 514.00000 | 24.48868 | 45.60330 | 0.56436 | 12.20554 |
April | 485.00000 | 24.57785 | 45.13468 | 0.57692 | 12.65096 |
May | 508.00000 | 24.55800 | 45.33862 | -0.2580 | 7.69148 |
June | 496.00000 | 24.51549 | 46.47217 | -0.2567 | 7.70942 |
July | 497.00000 | 24.65074 | 45.83327 | -0.2152 | 7.57447 |
August | 514.00000 | 24.50823 | 45.99778 | -0.2384 | 7.45983 |
September | 485.00000 | 24.59296 | 47.26588 | -0.2121 | 7.58193 |
October | 502.00000 | 24.63863 | 46.82084 | 0.62450 | 14.07726 |
November | 489.00000 | 24.64849 | 45.99819 | 0.62280 | 13.83939 |
December | 497.00000 | 24.64020 | 46.14973 | 0.61411 | 13.65410 |
Annual Sum or Average | 5943.00000 | 24.58458 | 45.95733 | 0.24625 | 10.82785 |
Minimum of Months | 454.00000 | 24.48868 | 44.71503 | -0.2580 | 7.45983 |
Maximum of Months | 514.00000 | 24.65074 | 47.26588 | 0.62450 | 14.07726 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.32122 | 50.06510 | 0.55123 | 11.67982 |
February | 454.00000 | 24.35563 | 52.84299 | 0.58848 | 12.60040 |
March | 514.00000 | 24.31111 | 51.01287 | 0.57847 | 12.28441 |
April | 485.00000 | 24.27566 | 52.26510 | 0.58644 | 12.42000 |
May | 508.00000 | 24.22815 | 53.75310 | -0.2754 | 6.86565 |
June | 496.00000 | 24.17252 | 55.59356 | -0.2713 | 6.67815 |
July | 497.00000 | 24.17747 | 55.36621 | -0.2636 | 6.55560 |
August | 514.00000 | 24.14314 | 55.78724 | -0.2574 | 6.46856 |
September | 485.00000 | 24.22145 | 55.75560 | -0.2606 | 6.64299 |
October | 502.00000 | 24.29076 | 54.24226 | 0.60301 | 12.82105 |
November | 489.00000 | 24.37171 | 54.63691 | 0.62670 | 13.50700 |
December | 497.00000 | 24.39963 | 53.10544 | 0.61460 | 13.26888 |
Annual Sum or Average | 5943.00000 | 24.27146 | 53.70135 | 0.23155 | 10.12324 |
Minimum of Months | 454.00000 | 24.14314 | 50.06510 | -0.2754 | 6.46856 |
Maximum of Months | 514.00000 | 24.39963 | 55.78724 | 0.62670 | 13.50700 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.99880 | 51.19507 | 0.44758 | 9.50557 |
February | 454.00000 | 24.05475 | 54.02332 | 0.48713 | 10.22497 |
March | 514.00000 | 24.11342 | 51.73592 | 0.49762 | 10.40458 |
April | 485.00000 | 24.14508 | 52.91275 | 0.52306 | 10.94711 |
May | 508.00000 | 24.16532 | 54.01338 | -0.3224 | 7.44922 |
June | 496.00000 | 24.12034 | 55.97348 | -0.3205 | 7.33255 |
July | 497.00000 | 24.05306 | 56.22063 | -0.3469 | 7.66624 |
August | 514.00000 | 24.05597 | 56.60204 | -0.3362 | 7.48611 |
September | 485.00000 | 24.14613 | 56.20248 | -0.3143 | 7.29209 |
October | 502.00000 | 24.21032 | 54.65579 | 0.55867 | 11.73527 |
November | 489.00000 | 24.19125 | 55.64950 | 0.55255 | 11.58613 |
December | 497.00000 | 24.02450 | 54.69428 | 0.48535 | 10.20371 |
Annual Sum or Average | 5943.00000 | 24.10666 | 54.48583 | 0.15594 | 9.30759 |
Minimum of Months | 454.00000 | 23.99880 | 51.19507 | -0.3469 | 7.29209 |
Maximum of Months | 514.00000 | 24.21032 | 56.60204 | 0.55867 | 11.73527 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.33967 | 54.69333 | 0.29875 | 7.83586 |
February | 454.00000 | 23.59070 | 55.92158 | 0.38456 | 8.83556 |
March | 514.00000 | 23.83221 | 52.94458 | 0.44422 | 9.63334 |
April | 485.00000 | 24.05165 | 53.54474 | 0.52245 | 11.02502 |
May | 508.00000 | 24.21522 | 54.01433 | -0.2598 | 6.85286 |
June | 496.00000 | 24.17955 | 55.90780 | -0.2495 | 6.65176 |
July | 497.00000 | 24.16661 | 55.88380 | -0.2513 | 6.68337 |
August | 514.00000 | 24.12064 | 56.46022 | -0.2588 | 6.68893 |
September | 485.00000 | 24.20382 | 56.18122 | -0.2523 | 6.75419 |
October | 502.00000 | 24.18014 | 55.11391 | 0.57339 | 12.14058 |
November | 489.00000 | 23.95341 | 56.90496 | 0.50782 | 10.67968 |
December | 497.00000 | 23.48533 | 56.89595 | 0.36139 | 8.53408 |
Annual Sum or Average | 5943.00000 | 23.94538 | 55.36100 | 0.14909 | 8.51725 |
Minimum of Months | 454.00000 | 23.33967 | 52.94458 | -0.2598 | 6.65176 |
Maximum of Months | 514.00000 | 24.21522 | 56.90496 | 0.57339 | 12.14058 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.22282 | 52.27542 | 0.29670 | 7.85007 |
February | 454.00000 | 23.52729 | 54.60297 | 0.40539 | 9.34965 |
March | 514.00000 | 23.79335 | 51.68257 | 0.47871 | 10.50923 |
April | 485.00000 | 24.08231 | 52.29930 | 0.58875 | 12.89717 |
May | 508.00000 | 24.36830 | 52.54706 | -0.1021 | 6.42071 |
June | 496.00000 | 24.34730 | 54.49206 | -0.0588 | 6.14691 |
July | 497.00000 | 24.48789 | 53.89395 | 0.00872 | 6.43016 |
August | 514.00000 | 24.35085 | 54.65397 | -0.0212 | 6.03754 |
September | 485.00000 | 24.37504 | 54.96796 | -0.0839 | 6.42383 |
October | 502.00000 | 24.26892 | 53.91648 | 0.65510 | 14.57723 |
November | 489.00000 | 24.03260 | 55.11394 | 0.57310 | 12.33781 |
December | 497.00000 | 23.62415 | 54.88007 | 0.43604 | 9.71829 |
Annual Sum or Average | 5943.00000 | 24.04327 | 53.76292 | 0.26285 | 9.04401 |
Minimum of Months | 454.00000 | 23.22282 | 51.68257 | -0.1021 | 6.03754 |
Maximum of Months | 514.00000 | 24.48789 | 55.11394 | 0.65510 | 14.57723 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.09705 | 52.53852 | 0.29985 | 8.26723 |
February | 454.00000 | 23.33026 | 55.15741 | 0.39141 | 9.57147 |
March | 514.00000 | 23.50282 | 52.44691 | 0.44404 | 10.42770 |
April | 485.00000 | 23.83986 | 52.94253 | 0.57152 | 13.14781 |
May | 508.00000 | 24.26472 | 52.72358 | -0.0687 | 7.12233 |
June | 496.00000 | 24.19015 | 54.85484 | -0.0586 | 6.74551 |
July | 497.00000 | 24.33505 | 54.28478 | 0.00511 | 7.10986 |
August | 514.00000 | 24.19343 | 55.05361 | -0.0233 | 6.59327 |
September | 485.00000 | 24.26075 | 55.12664 | -0.0563 | 7.17967 |
October | 502.00000 | 24.09864 | 54.26387 | 0.65721 | 15.10132 |
November | 489.00000 | 23.77975 | 55.83298 | 0.54867 | 12.23199 |
December | 497.00000 | 23.24091 | 56.04962 | 0.37411 | 9.08137 |
Annual Sum or Average | 5943.00000 | 23.84775 | 54.25798 | 0.25528 | 9.36841 |
Minimum of Months | 454.00000 | 23.09705 | 52.44691 | -0.0687 | 6.59327 |
Maximum of Months | 514.00000 | 24.33505 | 56.04962 | 0.65721 | 15.10132 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.53176 | 51.14614 | 0.42320 | 10.83115 |
February | 454.00000 | 23.66352 | 53.99889 | 0.49194 | 11.87089 |
March | 514.00000 | 23.76478 | 51.62724 | 0.51543 | 11.94271 |
April | 485.00000 | 23.98803 | 52.53338 | 0.59076 | 13.38325 |
May | 508.00000 | 24.24865 | 52.90262 | -0.1338 | 6.78947 |
June | 496.00000 | 24.22880 | 54.88061 | -0.1056 | 6.27512 |
July | 497.00000 | 24.38956 | 54.19200 | -0.0240 | 6.36136 |
August | 514.00000 | 24.29753 | 54.77271 | -0.0160 | 6.21391 |
September | 485.00000 | 24.37169 | 54.81607 | -0.0183 | 7.09400 |
October | 502.00000 | 24.35679 | 53.43869 | 0.74675 | 17.98363 |
November | 489.00000 | 24.20619 | 54.36457 | 0.68898 | 16.34785 |
December | 497.00000 | 23.82055 | 54.06606 | 0.54386 | 13.00446 |
Annual Sum or Average | 5943.00000 | 24.07451 | 53.55123 | 0.30623 | 10.65098 |
Minimum of Months | 454.00000 | 23.53176 | 51.14614 | -0.1338 | 6.21391 |
Maximum of Months | 514.00000 | 24.38956 | 54.88061 | 0.74675 | 17.98363 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.13760 | 52.22263 | 0.34930 | 9.04284 |
February | 454.00000 | 23.64777 | 53.91223 | 0.51879 | 12.06250 |
March | 514.00000 | 24.02209 | 50.68513 | 0.63489 | 14.64181 |
April | 485.00000 | 24.32286 | 51.25726 | 0.76324 | 18.33890 |
May | 508.00000 | 24.25745 | 52.71133 | -0.0155 | 7.30789 |
June | 496.00000 | 24.29728 | 54.41290 | 0.06418 | 6.96661 |
July | 497.00000 | 24.47253 | 53.69234 | 0.16171 | 7.60596 |
August | 514.00000 | 24.39077 | 54.24231 | 0.17688 | 7.28789 |
September | 485.00000 | 24.28331 | 54.95839 | 0.01500 | 7.26175 |
October | 502.00000 | 24.27488 | 53.59575 | 0.75573 | 18.06219 |
November | 489.00000 | 24.22950 | 54.20741 | 0.72171 | 16.90279 |
December | 497.00000 | 24.05396 | 53.17890 | 0.63650 | 14.61786 |
Annual Sum or Average | 5943.00000 | 24.11837 | 53.24463 | 0.39686 | 11.65234 |
Minimum of Months | 454.00000 | 23.13760 | 50.68513 | -0.0155 | 6.96661 |
Maximum of Months | 514.00000 | 24.47253 | 54.95839 | 0.76324 | 18.33890 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.50722 | 54.32352 | 0.10572 | 6.44565 |
February | 454.00000 | 22.90333 | 56.76192 | 0.23523 | 7.43434 |
March | 514.00000 | 23.33664 | 53.01887 | 0.34507 | 8.68621 |
April | 485.00000 | 23.87419 | 53.56216 | 0.51588 | 11.47017 |
May | 508.00000 | 24.38171 | 52.84125 | -0.1137 | 6.71139 |
June | 496.00000 | 24.40350 | 55.18054 | -0.0564 | 6.39179 |
July | 497.00000 | 24.54561 | 54.71998 | 0.00404 | 6.64512 |
August | 514.00000 | 24.41549 | 55.52147 | -0.0303 | 6.24513 |
September | 485.00000 | 24.40511 | 56.01368 | -0.0862 | 6.73133 |
October | 502.00000 | 24.22108 | 55.02217 | 0.62916 | 14.05352 |
November | 489.00000 | 23.67150 | 56.85683 | 0.46642 | 10.27716 |
December | 497.00000 | 22.83399 | 57.85685 | 0.22353 | 7.26294 |
Annual Sum or Average | 5943.00000 | 23.79755 | 55.11729 | 0.18531 | 8.19212 |
Minimum of Months | 454.00000 | 22.50722 | 52.84125 | -0.1137 | 6.24513 |
Maximum of Months | 514.00000 | 24.54561 | 57.85685 | 0.62916 | 14.05352 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.45698 | 54.13603 | 0.11693 | 6.64924 |
February | 385.00000 | 22.80834 | 56.93669 | 0.23898 | 7.77275 |
March | 433.00000 | 23.19494 | 53.16984 | 0.33955 | 9.10685 |
April | 410.00000 | 23.83175 | 53.78353 | 0.54503 | 12.96478 |
May | 430.00000 | 24.39345 | 52.89755 | -0.0557 | 7.75099 |
June | 418.00000 | 24.36769 | 55.35694 | -0.0264 | 7.29560 |
July | 422.00000 | 24.54104 | 54.63048 | 0.04414 | 7.86028 |
August | 433.00000 | 24.40194 | 55.51894 | 0.01229 | 7.11672 |
September | 410.00000 | 24.40257 | 55.94848 | -0.0355 | 7.90083 |
October | 427.00000 | 24.20544 | 55.04209 | 0.66185 | 15.60944 |
November | 417.00000 | 23.58096 | 56.95639 | 0.47711 | 11.00659 |
December | 422.00000 | 22.66188 | 58.19173 | 0.20771 | 7.24155 |
Annual Sum or Average | 5034.00000 | 23.74242 | 55.19249 | 0.20978 | 9.02302 |
Minimum of Months | 385.00000 | 22.45698 | 52.89755 | -0.0557 | 6.64924 |
Maximum of Months | 433.00000 | 24.54104 | 58.19173 | 0.66185 | 15.60944 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.30046 | 51.68330 | 0.34849 | 10.12930 |
February | 454.00000 | 23.40382 | 54.92751 | 0.40991 | 10.75200 |
March | 514.00000 | 23.53293 | 52.23111 | 0.43683 | 10.79905 |
April | 485.00000 | 23.85483 | 53.50420 | 0.53768 | 12.36372 |
May | 508.00000 | 24.26493 | 53.16844 | -0.1464 | 7.07074 |
June | 496.00000 | 24.28621 | 55.54731 | -0.1054 | 6.50888 |
July | 497.00000 | 24.44694 | 54.98896 | -0.0307 | 6.56448 |
August | 514.00000 | 24.36822 | 55.56507 | -0.0232 | 6.41966 |
September | 485.00000 | 24.41331 | 55.70995 | -0.0161 | 7.34646 |
October | 502.00000 | 24.38204 | 54.18803 | 0.74110 | 17.98728 |
November | 489.00000 | 24.07464 | 55.25854 | 0.64066 | 15.31407 |
December | 497.00000 | 23.51636 | 55.35753 | 0.44693 | 11.61670 |
Annual Sum or Average | 5943.00000 | 23.99058 | 54.33035 | 0.26790 | 10.22224 |
Minimum of Months | 454.00000 | 23.30046 | 51.68330 | -0.1464 | 6.41966 |
Maximum of Months | 514.00000 | 24.44694 | 55.70995 | 0.74110 | 17.98728 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.43359 | 54.36885 | 0.13153 | 6.94545 |
February | 454.00000 | 22.76765 | 56.95032 | 0.25553 | 8.08364 |
March | 514.00000 | 23.20148 | 53.16505 | 0.37251 | 9.71022 |
April | 485.00000 | 23.71179 | 53.77913 | 0.54074 | 12.79692 |
May | 508.00000 | 24.19422 | 53.21979 | -0.0907 | 7.94384 |
June | 496.00000 | 24.23942 | 55.40867 | -0.0277 | 7.37722 |
July | 497.00000 | 24.38011 | 54.92891 | 0.03297 | 7.49700 |
August | 514.00000 | 24.29143 | 55.59624 | 0.02117 | 7.05158 |
September | 485.00000 | 24.23676 | 56.12381 | -0.0523 | 7.85274 |
October | 502.00000 | 24.01819 | 55.29729 | 0.64405 | 15.16675 |
November | 489.00000 | 23.45969 | 57.28780 | 0.47746 | 11.18273 |
December | 497.00000 | 22.71046 | 57.97024 | 0.24607 | 7.85827 |
Annual Sum or Average | 5943.00000 | 23.64310 | 55.31836 | 0.21150 | 9.11921 |
Minimum of Months | 454.00000 | 22.43359 | 53.16505 | -0.0907 | 6.94545 |
Maximum of Months | 514.00000 | 24.38011 | 57.97024 | 0.64405 | 15.16675 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.01750 | 56.20385 | -0.0123 | 6.69860 |
February | 454.00000 | 22.50155 | 58.43921 | 0.14739 | 7.34368 |
March | 514.00000 | 23.02864 | 54.34690 | 0.28693 | 8.54182 |
April | 485.00000 | 23.67780 | 54.64464 | 0.49214 | 11.55788 |
May | 508.00000 | 24.30297 | 53.45285 | -0.0989 | 7.36786 |
June | 496.00000 | 24.35133 | 55.74348 | -0.0298 | 6.85380 |
July | 497.00000 | 24.50560 | 55.18406 | 0.04108 | 7.19602 |
August | 514.00000 | 24.37172 | 56.05026 | 0.00203 | 6.62954 |
September | 485.00000 | 24.32846 | 56.69355 | -0.0717 | 7.35818 |
October | 502.00000 | 24.06599 | 56.07092 | 0.61653 | 14.12613 |
November | 489.00000 | 23.37041 | 58.41941 | 0.41098 | 9.77779 |
December | 497.00000 | 22.36905 | 59.88196 | 0.11880 | 7.02684 |
Annual Sum or Average | 5943.00000 | 23.58160 | 56.23325 | 0.15785 | 8.37168 |
Minimum of Months | 454.00000 | 22.01750 | 53.45285 | -0.0989 | 6.62954 |
Maximum of Months | 514.00000 | 24.50560 | 59.88196 | 0.61653 | 14.12613 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.24382 | 55.37392 | 0.06887 | 6.91242 |
February | 454.00000 | 22.70579 | 57.68824 | 0.22393 | 8.12048 |
March | 514.00000 | 23.14338 | 53.85739 | 0.34752 | 9.64440 |
April | 485.00000 | 23.78850 | 54.10488 | 0.56488 | 13.67539 |
May | 508.00000 | 24.31840 | 53.22644 | -0.0175 | 7.93521 |
June | 496.00000 | 24.30767 | 55.64258 | 0.02164 | 7.44967 |
July | 497.00000 | 24.46746 | 55.10364 | 0.09426 | 8.16089 |
August | 514.00000 | 24.33325 | 55.91829 | 0.06299 | 7.32004 |
September | 485.00000 | 24.32838 | 56.36454 | 0.00202 | 8.03984 |
October | 502.00000 | 24.12875 | 55.57203 | 0.67766 | 16.17810 |
November | 489.00000 | 23.49875 | 57.80994 | 0.47718 | 11.25046 |
December | 497.00000 | 22.48312 | 59.35791 | 0.17211 | 7.36710 |
Annual Sum or Average | 5943.00000 | 23.65183 | 55.81052 | 0.22378 | 9.33447 |
Minimum of Months | 454.00000 | 22.24382 | 53.22644 | -0.0175 | 6.91242 |
Maximum of Months | 514.00000 | 24.46746 | 59.35791 | 0.67766 | 16.17810 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.90456 | 53.29750 | 0.24856 | 9.87012 |
February | 454.00000 | 23.07225 | 56.42595 | 0.33488 | 10.46769 |
March | 514.00000 | 23.27622 | 53.43700 | 0.38790 | 10.66685 |
April | 485.00000 | 23.67316 | 54.56947 | 0.51652 | 12.52874 |
May | 508.00000 | 24.17938 | 53.81496 | -0.1334 | 7.85738 |
June | 496.00000 | 24.22850 | 56.13762 | -0.0799 | 7.06482 |
July | 497.00000 | 24.40922 | 55.46244 | 0.00714 | 7.19066 |
August | 514.00000 | 24.31818 | 56.12949 | 0.00692 | 6.91381 |
September | 485.00000 | 24.33370 | 56.43470 | -0.0040 | 8.14773 |
October | 502.00000 | 24.24886 | 55.21282 | 0.73150 | 18.15281 |
November | 489.00000 | 23.83596 | 56.62451 | 0.59599 | 14.76602 |
December | 497.00000 | 23.15535 | 57.05900 | 0.36155 | 11.01297 |
Annual Sum or Average | 5943.00000 | 23.80759 | 55.36573 | 0.24615 | 10.37319 |
Minimum of Months | 454.00000 | 22.90456 | 53.29750 | -0.1334 | 6.91381 |
Maximum of Months | 514.00000 | 24.40922 | 57.05900 | 0.73150 | 18.15281 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.13238 | 55.70704 | 0.05457 | 7.21159 |
February | 454.00000 | 22.51905 | 58.20925 | 0.20003 | 8.11929 |
March | 514.00000 | 22.96635 | 54.33900 | 0.32971 | 9.65387 |
April | 485.00000 | 23.54808 | 54.81626 | 0.52273 | 12.96795 |
May | 508.00000 | 24.09080 | 53.95028 | -0.0857 | 8.93571 |
June | 496.00000 | 24.16388 | 56.08891 | -0.0105 | 8.16581 |
July | 497.00000 | 24.32463 | 55.49347 | 0.06187 | 8.35906 |
August | 514.00000 | 24.22511 | 56.23259 | 0.04366 | 7.73321 |
September | 485.00000 | 24.13581 | 56.93403 | -0.0475 | 8.78416 |
October | 502.00000 | 23.86146 | 56.41394 | 0.63016 | 15.28786 |
November | 489.00000 | 23.22819 | 58.67037 | 0.43641 | 10.86826 |
December | 497.00000 | 22.41550 | 59.51032 | 0.17746 | 7.75592 |
Annual Sum or Average | 5943.00000 | 23.47425 | 56.33821 | 0.19191 | 9.48695 |
Minimum of Months | 454.00000 | 22.13238 | 53.95028 | -0.0857 | 7.21159 |
Maximum of Months | 514.00000 | 24.32463 | 59.51032 | 0.63016 | 15.28786 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.244414E+12 | 293493.51 | 11-JAN-06:04 | 726.48 | 0.140717E+13 | 0.00 | 0.165158E+13 | 5.18 | 7.17 | 19-JAN-06:03 | 0.00 | 0.00 |
February | 0.279056E+12 | 299921.67 | 02-FEB-06:04 | 664.82 | 0.168648E+13 | 0.00 | 0.196554E+13 | 5.48 | 7.10 | 10-FEB-06:03 | 0.00 | 0.00 |
March | 0.375887E+12 | 304662.34 | 28-MAR-11:00 | 737.35 | 0.232735E+13 | 0.00 | 0.270324E+13 | 5.71 | 7.11 | 25-MAR-05:03 | 0.00 | 0.00 |
April | 0.421915E+12 | 324550.36 | 30-APR-15:00 | 715.43 | 0.260486E+13 | 0.00 | 0.302677E+13 | 5.79 | 7.10 | 07-APR-11:05 | 0.00 | 0.00 |
May | 0.396703E+12 | 328695.35 | 31-MAY-03:04 | 691.75 | 0.250121E+13 | 0.00 | 0.289791E+13 | 5.48 | 7.13 | 15-MAY-03:01 | 0.00 | 0.00 |
June | 0.455662E+12 | 335233.22 | 20-JUN-03:04 | 690.61 | 0.280451E+13 | 0.00 | 0.326017E+13 | 5.62 | 7.12 | 03-JUN-04:01 | 0.00 | 0.00 |
July | 0.522973E+12 | 338536.24 | 30-JUL-14:53 | 724.82 | 0.320194E+13 | 0.00 | 0.372491E+13 | 5.76 | 7.09 | 20-JUL-21:20 | 0.00 | 0.00 |
August | 0.551200E+12 | 338498.42 | 08-AUG-01:01 | 738.35 | 0.336655E+13 | 0.00 | 0.391775E+13 | 5.89 | 6.79 | 06-AUG-04:40 | 0.00 | 0.00 |
September | 0.429654E+12 | 347453.61 | 17-SEP-19:40 | 663.61 | 0.265374E+13 | 0.00 | 0.308339E+13 | 5.37 | 7.02 | 26-SEP-03:01 | 0.00 | 0.00 |
October | 0.413057E+12 | 333586.38 | 02-OCT-03:04 | 724.24 | 0.255524E+13 | 0.00 | 0.296829E+13 | 5.60 | 7.06 | 14-OCT-03:01 | 0.00 | 0.00 |
November | 0.381775E+12 | 308714.52 | 30-NOV-11:10 | 710.50 | 0.235297E+13 | 0.00 | 0.273475E+13 | 5.67 | 7.12 | 22-NOV-06:03 | 0.00 | 0.00 |
December | 0.395459E+12 | 301751.59 | 05-DEC-05:13 | 741.99 | 0.240527E+13 | 0.00 | 0.280073E+13 | 5.69 | 7.08 | 16-DEC-06:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.486776E+13 | 8529.97 | 0.298673E+14 | 0.00 | 0.347350E+14 | 5.60 | 0.00 | 0.00 | ||||
Minimum of Months | 0.244414E+12 | 293493.51 | 663.61 | 0.140717E+13 | 0.00 | 0.165158E+13 | 5.18 | 6.79 | 0.00 | 0.00 | ||
Maximum of Months | 0.551200E+12 | 347453.61 | 741.99 | 0.336655E+13 | 0.00 | 0.391775E+13 | 5.89 | 7.17 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 44278932.30 | 188645.57 | 30-JAN-06:06 | 0.11 | 0.288576E+09 | 0.00 | 0.332855E+09 | 0.00 | 6.66 | 30-JAN-06:06 | 0.00 | 0.00 |
February | 0.287983E+10 | 234912.06 | 09-FEB-05:14 | 4.67 | 0.181503E+11 | 0.00 | 0.210301E+11 | 0.04 | 6.87 | 07-FEB-05:14 | 0.00 | 0.00 |
March | 0.234637E+11 | 266580.70 | 29-MAR-04:14 | 39.12 | 0.149313E+12 | 0.00 | 0.172776E+12 | 0.33 | 6.93 | 27-MAR-09:05 | 0.00 | 0.00 |
April | 0.685864E+11 | 265837.40 | 30-APR-16:34 | 109.92 | 0.435116E+12 | 0.00 | 0.503703E+12 | 0.96 | 6.92 | 29-APR-05:05 | 0.00 | 0.00 |
May | 0.101439E+12 | 328695.35 | 31-MAY-03:04 | 154.45 | 0.631707E+12 | 0.00 | 0.733146E+12 | 1.28 | 6.95 | 10-MAY-03:04 | 0.00 | 0.00 |
June | 0.198278E+12 | 335233.22 | 20-JUN-03:04 | 282.66 | 0.123120E+13 | 0.00 | 0.142947E+13 | 2.42 | 6.88 | 02-JUN-03:04 | 0.00 | 0.00 |
July | 0.291930E+12 | 338536.24 | 30-JUL-14:53 | 385.07 | 0.181275E+13 | 0.00 | 0.210468E+13 | 3.20 | 6.68 | 13-JUL-03:04 | 0.00 | 0.00 |
August | 0.362189E+12 | 338498.42 | 08-AUG-01:01 | 459.01 | 0.225441E+13 | 0.00 | 0.261659E+13 | 3.82 | 6.62 | 06-AUG-08:14 | 0.00 | 0.00 |
September | 0.184871E+12 | 336582.33 | 09-SEP-03:04 | 260.21 | 0.114349E+13 | 0.00 | 0.132836E+13 | 2.22 | 6.70 | 26-SEP-03:04 | 0.00 | 0.00 |
October | 0.124704E+12 | 333586.38 | 02-OCT-03:04 | 186.09 | 0.778044E+12 | 0.00 | 0.902748E+12 | 1.55 | 6.95 | 14-OCT-05:05 | 0.00 | 0.00 |
November | 0.669862E+11 | 250813.05 | 10-NOV-05:14 | 104.12 | 0.419251E+12 | 0.00 | 0.486237E+12 | 0.90 | 6.88 | 16-NOV-05:14 | 0.00 | 0.00 |
December | 0.130779E+11 | 224453.91 | 11-DEC-05:14 | 21.51 | 0.816133E+11 | 0.00 | 0.946913E+11 | 0.18 | 6.86 | 15-DEC-05:14 | 0.00 | 0.00 |
Annual Sum or Average | 0.143845E+13 | 2006.95 | 0.895532E+13 | 0.00 | 0.103938E+14 | 1.42 | 0.00 | 0.00 | ||||
Minimum of Months | 44278932.30 | 188645.57 | 0.11 | 0.288576E+09 | 0.00 | 0.332855E+09 | 0.00 | 6.62 | 0.00 | 0.00 | ||
Maximum of Months | 0.362189E+12 | 338536.24 | 459.01 | 0.225441E+13 | 0.00 | 0.261659E+13 | 3.82 | 6.95 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.201930E+11 | 628.94 | 32047.55 | 09-JAN-11:50 | 1878961.59 | 24-JAN-13:30 | 22.66 | 21.17 | 101.25 |
February | 0.314171E+11 | 663.47 | 32047.55 | 01-FEB-10:30 | 2124970.78 | 23-FEB-14:00 | 23.33 | 21.40 | 103.20 |
March | 0.448787E+11 | 737.29 | 32047.55 | 01-MAR-03:50 | 2289170.08 | 22-MAR-10:20 | 23.96 | 21.59 | 102.49 |
April | 0.655536E+11 | 715.40 | 32047.55 | 01-APR-00:10 | 2309866.73 | 28-APR-08:00 | 25.21 | 22.48 | 98.86 |
May | 0.724141E+11 | 691.65 | 32047.55 | 01-MAY-00:02 | 2298276.35 | 04-MAY-09:00 | 26.79 | 24.26 | 86.31 |
June | 0.791102E+11 | 690.61 | 32047.55 | 01-JUN-00:02 | 2194259.10 | 02-JUN-08:70 | 29.46 | 26.53 | 84.36 |
July | 0.828837E+11 | 724.82 | 32047.55 | 01-JUL-00:02 | 2125891.01 | 19-JUL-15:00 | 30.84 | 27.59 | 84.58 |
August | 0.851840E+11 | 738.35 | 32047.55 | 01-AUG-00:02 | 2230626.02 | 10-AUG-16:00 | 31.48 | 28.06 | 87.30 |
September | 0.765027E+11 | 663.61 | 32047.55 | 01-SEP-00:03 | 1946855.01 | 07-SEP-14:05 | 29.87 | 27.09 | 78.92 |
October | 0.786441E+11 | 724.24 | 32047.55 | 01-OCT-00:10 | 2301037.19 | 19-OCT-16:30 | 27.28 | 24.68 | 89.68 |
November | 0.625591E+11 | 710.50 | 32047.55 | 01-NOV-00:02 | 2193940.58 | 22-NOV-14:50 | 25.09 | 22.62 | 98.08 |
December | 0.470642E+11 | 741.86 | 32047.55 | 01-DEC-09:50 | 2318107.38 | 01-DEC-12:00 | 24.07 | 21.62 | 103.59 |
Annual Sum or Average | 0.746405E+12 | 8430.74 | 26.69 | 24.11 | 93.17 | ||||
Minimum of Months | 0.201930E+11 | 628.94 | 32047.55 | 1878961.59 | 22.66 | 21.17 | 78.92 | ||
Maximum of Months | 0.851840E+11 | 741.86 | 32047.55 | 2318107.38 | 31.48 | 28.06 | 103.59 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 80759830.51 | 0.70 | 32047.55 | 30-JAN-06:06 | 1631236.66 | 30-JAN-06:06 | 22.66 | 22.65 | 0.05 |
February | 0.966188E+09 | 8.37 | 32047.55 | 06-FEB-05:14 | 1569697.93 | 06-FEB-15:10 | 23.33 | 23.28 | 0.97 |
March | 0.628395E+10 | 54.61 | 32047.55 | 01-MAR-06:05 | 1943065.10 | 23-MAR-15:50 | 23.96 | 23.69 | 6.44 |
April | 0.200963E+11 | 174.45 | 32047.55 | 03-APR-06:30 | 1984226.70 | 14-APR-11:10 | 25.21 | 24.31 | 20.19 |
May | 0.358680E+11 | 310.94 | 32047.55 | 01-MAY-04:13 | 1814862.01 | 19-MAY-14:50 | 26.79 | 25.27 | 32.74 |
June | 0.581964E+11 | 504.43 | 32047.55 | 01-JUN-01:19 | 1863993.17 | 08-JUN-05:03 | 29.46 | 26.92 | 57.29 |
July | 0.730083E+11 | 632.81 | 32047.55 | 01-JUL-00:16 | 2125891.01 | 19-JUL-15:00 | 30.84 | 27.81 | 71.64 |
August | 0.801624E+11 | 694.82 | 32047.55 | 01-AUG-00:02 | 2230626.02 | 10-AUG-16:00 | 31.48 | 28.15 | 81.18 |
September | 0.579181E+11 | 502.02 | 32047.55 | 01-SEP-00:33 | 1946855.01 | 07-SEP-14:05 | 29.87 | 27.31 | 55.43 |
October | 0.413140E+11 | 358.10 | 32047.55 | 01-OCT-00:46 | 1963777.13 | 07-OCT-05:05 | 27.28 | 25.52 | 38.17 |
November | 0.201207E+11 | 174.42 | 32047.55 | 01-NOV-03:30 | 1885972.23 | 13-NOV-14:00 | 25.09 | 24.20 | 20.16 |
December | 0.369289E+10 | 32.01 | 32047.55 | 01-DEC-13:10 | 1594999.33 | 01-DEC-13:50 | 24.07 | 23.92 | 3.73 |
Annual Sum or Average | 0.397708E+12 | 3447.67 | 26.69 | 25.26 | 32.53 | ||||
Minimum of Months | 80759830.51 | 0.70 | 32047.55 | 1569697.93 | 22.66 | 22.65 | 0.05 | ||
Maximum of Months | 0.801624E+11 | 694.82 | 32047.55 | 2230626.02 | 31.48 | 28.15 | 81.18 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.104915E+12 | 0.00 | 427.85 | 0.101218E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 223674.71 | 30-JAN-05:12 | 155430.62 | 30-JAN-05:12 | 0.00 | 0.00 | 0.00 |
February | 0.112725E+12 | 0.00 | 392.39 | 0.105933E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 238924.66 | 09-FEB-05:11 | 176834.98 | 06-FEB-05:11 | 0.00 | 0.00 | 0.00 |
March | 0.154416E+12 | 0.00 | 475.64 | 0.146385E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 256807.01 | 01-MAR-04:01 | 189842.11 | 27-MAR-04:11 | 0.00 | 0.00 | 0.00 |
April | 0.190962E+12 | 0.00 | 516.37 | 0.172046E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 247407.81 | 12-APR-04:11 | 185520.15 | 24-APR-04:11 | 0.00 | 0.00 | 0.00 |
May | 0.239864E+12 | 0.00 | 539.50 | 0.205386E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 340072.35 | 29-MAY-14:41 | 216343.94 | 08-MAY-03:01 | 0.00 | 0.00 | 0.00 |
June | 0.304663E+12 | 0.00 | 579.92 | 0.227955E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 363786.28 | 27-JUN-05:02 | 224322.01 | 27-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.366479E+12 | 0.00 | 628.69 | 0.257162E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 398569.65 | 27-JUL-05:02 | 242939.26 | 27-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.400050E+12 | 0.00 | 650.75 | 0.278646E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 387665.46 | 18-AUG-05:02 | 256908.15 | 07-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.298511E+12 | 0.00 | 542.50 | 0.210900E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 377852.44 | 12-SEP-05:02 | 244481.42 | 18-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.248347E+12 | 0.00 | 534.31 | 0.195796E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 325373.40 | 05-OCT-05:02 | 211071.73 | 09-OCT-14:41 | 0.00 | 0.00 | 0.00 |
November | 0.184969E+12 | 0.00 | 468.37 | 0.159876E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 258956.36 | 03-NOV-05:02 | 185800.14 | 21-NOV-05:11 | 0.00 | 0.00 | 0.00 |
December | 0.139306E+12 | 0.00 | 448.23 | 0.127697E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 243918.31 | 11-DEC-05:11 | 178036.76 | 27-DEC-05:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274521E+13 | 0.00 | 6204.51 | 0.218900E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.104915E+12 | 0.00 | 392.39 | 0.101218E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 223674.71 | 155430.62 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.400050E+12 | 0.00 | 650.75 | 0.278646E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 398569.65 | 256908.15 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.829400E+12 | 0.00 | 406.56 | 0.797049E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1881438.98 | 30-JAN-06:02 | 1334511.91 | 18-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.892719E+12 | 0.00 | 375.40 | 0.830137E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2209819.60 | 09-FEB-06:02 | 1401178.67 | 10-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.122709E+13 | 0.00 | 449.48 | 0.115078E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2139412.25 | 29-MAR-05:03 | 1863610.46 | 28-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.148640E+13 | 0.00 | 442.14 | 0.132484E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2624962.25 | 30-APR-16:31 | 1943111.23 | 29-APR-03:01 | 0.00 | 0.00 | 0.00 |
May | 0.218709E+13 | 0.00 | 506.24 | 0.185884E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2765163.76 | 27-MAY-05:02 | 2080356.65 | 10-MAY-03:01 | 0.00 | 0.00 | 0.00 |
June | 0.271837E+13 | 0.00 | 523.95 | 0.200125E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3171803.11 | 20-JUN-04:01 | 2022664.06 | 02-JUN-03:01 | 0.00 | 0.00 | 0.00 |
July | 0.326427E+13 | 0.00 | 575.26 | 0.222141E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3585466.34 | 30-JUL-16:51 | 2260442.59 | 30-JUL-13:31 | 0.00 | 0.00 | 0.00 |
August | 0.350618E+13 | 0.00 | 588.54 | 0.235991E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3367526.89 | 27-AUG-15:51 | 2134106.38 | 13-AUG-13:41 | 0.00 | 0.00 | 0.00 |
September | 0.272878E+13 | 0.00 | 502.26 | 0.188744E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3249025.22 | 22-SEP-04:01 | 2154837.50 | 04-SEP-15:31 | 0.00 | 0.00 | 0.00 |
October | 0.211595E+13 | 0.00 | 473.80 | 0.164538E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3292296.83 | 07-OCT-05:02 | 1976885.30 | 04-OCT-03:01 | 0.00 | 0.00 | 0.00 |
November | 0.150119E+13 | 0.00 | 427.86 | 0.126355E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2529834.87 | 03-NOV-05:02 | 1720587.83 | 20-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.101770E+13 | 0.00 | 414.06 | 0.917510E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2265677.01 | 11-DEC-06:02 | 1465628.31 | 12-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234751E+14 | 0.00 | 5685.54 | 0.182581E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.829400E+12 | 0.00 | 375.40 | 0.797049E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1881438.98 | 1334511.91 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.350618E+13 | 0.00 | 588.54 | 0.235991E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3585466.34 | 2260442.59 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.833646E+11 | 0.00 | 400.67 | 0.802715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117359.52 | 24-JAN-13:20 | 111773.86 | 23-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.943700E+11 | 0.00 | 367.79 | 0.883633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 265346.96 | 09-FEB-06:02 | 160206.68 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.134215E+12 | 0.00 | 438.38 | 0.126719E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 244639.82 | 29-MAR-04:11 | 191670.02 | 27-MAR-13:40 | 0.00 | 0.00 | 0.00 |
April | 0.168432E+12 | 0.00 | 437.16 | 0.152389E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 366291.49 | 30-APR-16:31 | 249316.67 | 30-APR-12:31 | 0.00 | 0.00 | 0.00 |
May | 0.253441E+12 | 0.00 | 507.78 | 0.220471E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 379039.74 | 30-MAY-04:01 | 281778.16 | 11-MAY-03:01 | 0.00 | 0.00 | 0.00 |
June | 0.309946E+12 | 0.00 | 524.51 | 0.238558E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 440456.24 | 19-JUN-03:01 | 266285.69 | 25-JUN-14:11 | 0.00 | 0.00 | 0.00 |
July | 0.370574E+12 | 0.00 | 579.57 | 0.266793E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 464682.85 | 30-JUL-16:21 | 299402.20 | 30-JUL-13:41 | 0.00 | 0.00 | 0.00 |
August | 0.393673E+12 | 0.00 | 592.03 | 0.280068E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 422552.93 | 27-AUG-15:51 | 284000.80 | 13-AUG-14:31 | 0.00 | 0.00 | 0.00 |
September | 0.304294E+12 | 0.00 | 503.47 | 0.220449E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 442282.34 | 10-SEP-15:01 | 294344.53 | 04-SEP-14:42 | 0.00 | 0.00 | 0.00 |
October | 0.231345E+12 | 0.00 | 468.05 | 0.184777E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 369335.04 | 06-OCT-05:02 | 243549.43 | 09-OCT-14:52 | 0.00 | 0.00 | 0.00 |
November | 0.157674E+12 | 0.00 | 413.69 | 0.134545E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 307772.63 | 03-NOV-05:02 | 205495.10 | 05-NOV-14:21 | 0.00 | 0.00 | 0.00 |
December | 0.103306E+12 | 0.00 | 402.54 | 0.936591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 268504.88 | 11-DEC-06:02 | 167535.67 | 12-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.260463E+13 | 0.00 | 5635.62 | 0.208706E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.833646E+11 | 0.00 | 367.79 | 0.802715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117359.52 | 111773.86 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.393673E+12 | 0.00 | 592.03 | 0.280068E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 464682.85 | 299402.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.760111E+11 | 0.00 | 433.42 | 0.675704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152186.15 | 30-JAN-05:12 | 133049.53 | 17-JAN-05:11 | 0.00 | 0.00 | 0.00 |
February | 0.753168E+11 | 0.00 | 386.38 | 0.640120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 177085.44 | 06-FEB-05:42 | 133882.22 | 11-FEB-05:12 | 0.00 | 0.00 | 0.00 |
March | 0.915400E+11 | 0.00 | 443.36 | 0.796550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159080.09 | 02-MAR-06:02 | 150332.19 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.968317E+11 | 0.00 | 415.70 | 0.795387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 176176.57 | 17-APR-03:42 | 151236.31 | 03-APR-03:12 | 0.00 | 0.00 | 0.00 |
May | 0.122759E+12 | 0.00 | 453.06 | 0.948503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 223093.86 | 29-MAY-15:58 | 156251.17 | 29-MAY-15:58 | 0.00 | 0.00 | 0.00 |
June | 0.145321E+12 | 0.00 | 451.50 | 0.994878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 266090.29 | 25-JUN-14:41 | 152338.81 | 04-JUN-15:33 | 0.00 | 0.00 | 0.00 |
July | 0.163385E+12 | 0.00 | 453.47 | 0.102970E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 256071.15 | 16-JUL-16:59 | 167165.62 | 30-JUL-14:45 | 0.00 | 0.00 | 0.00 |
August | 0.186674E+12 | 0.00 | 489.75 | 0.116657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 246532.14 | 20-AUG-16:17 | 166208.14 | 16-AUG-03:01 | 0.00 | 0.00 | 0.00 |
September | 0.154582E+12 | 0.00 | 458.97 | 0.990277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 271273.73 | 10-SEP-14:08 | 163517.51 | 04-SEP-09:56 | 0.00 | 0.00 | 0.00 |
October | 0.136571E+12 | 0.00 | 482.55 | 0.976798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 250162.94 | 01-OCT-13:40 | 146381.89 | 01-OCT-13:40 | 0.00 | 0.00 | 0.00 |
November | 0.117088E+12 | 0.00 | 458.04 | 0.891692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 175423.42 | 13-NOV-05:22 | 139374.15 | 13-NOV-05:22 | 0.00 | 0.00 | 0.00 |
December | 0.931014E+11 | 0.00 | 450.73 | 0.767081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 192553.17 | 11-DEC-05:33 | 138211.67 | 11-DEC-05:33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145918E+13 | 0.00 | 5376.94 | 0.106733E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.753168E+11 | 0.00 | 386.38 | 0.640120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152186.15 | 133049.53 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.186674E+12 | 0.00 | 489.75 | 0.116657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 271273.73 | 167165.62 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.263010E+12 | 0.00 | 744.00 | 0.263010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 104738.75 | 23-JAN-14:00 | 104738.75 | 23-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.460117E+12 | 0.00 | 672.00 | 0.459473E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 204074.65 | 07-FEB-16:00 | 198521.91 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.772272E+12 | 0.00 | 744.00 | 0.770061E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 400477.95 | 31-MAR-23:10 | 382613.75 | 31-MAR-24:00 | 0.00 | 0.00 | 0.00 |
April | 0.101523E+13 | 0.00 | 720.00 | 0.100963E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 429487.79 | 26-APR-04:14 | 429487.79 | 26-APR-04:14 | 0.00 | 0.00 | 0.00 |
May | 0.278159E+12 | 0.00 | 744.00 | 0.277002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 261409.08 | 31-MAY-23:02 | 190027.68 | 31-MAY-24:00 | 0.00 | 0.00 | 0.00 |
June | 0.522509E+12 | 0.00 | 720.00 | 0.507042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 378988.42 | 30-JUN-23:01 | 285884.78 | 30-JUN-23:55 | 0.00 | 0.00 | 0.00 |
July | 0.811605E+12 | 0.00 | 744.00 | 0.786093E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 415712.37 | 31-JUL-23:02 | 388403.94 | 31-JUL-23:52 | 0.00 | 0.00 | 0.00 |
August | 0.108807E+13 | 0.00 | 744.00 | 0.105994E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 421353.87 | 25-AUG-08:20 | 404512.29 | 06-AUG-14:52 | 0.00 | 0.00 | 0.00 |
September | 0.281464E+12 | 0.00 | 720.00 | 0.273182E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 386094.51 | 30-SEP-23:02 | 188698.67 | 30-SEP-24:00 | 0.00 | 0.00 | 0.00 |
October | 0.535190E+12 | 0.00 | 744.00 | 0.523786E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 373522.34 | 31-OCT-23:10 | 285681.00 | 31-OCT-24:00 | 0.00 | 0.00 | 0.00 |
November | 0.760152E+12 | 0.00 | 720.00 | 0.753259E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 307758.48 | 01-NOV-14:00 | 297572.36 | 13-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.104690E+13 | 0.00 | 744.00 | 0.104310E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 413381.46 | 31-DEC-16:58 | 413381.46 | 31-DEC-16:58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.783468E+13 | 0.00 | 8760.00 | 0.772558E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.263010E+12 | 0.00 | 672.00 | 0.263010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 104738.75 | 104738.75 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.108807E+13 | 0.00 | 744.00 | 0.105994E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 429487.79 | 429487.79 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT HP COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.736250E+10 | 0.229358E+10 | 744.00 | 0.711230E+10 | 0.250206E+09 | 0.00 | 0.44 | 24-JAN-17:00 | 0.28 | 21-JAN-07:45 | 3518.01 | 30-JAN-15:00 | 3261.29 | 23-JAN-14:10 | 385.00 | 30-JAN-15:20 | 1128.23 | 23-JAN-14:00 | 0.00 |
February | 0.116389E+11 | 0.343960E+10 | 672.00 | 0.112882E+11 | 0.350718E+09 | 0.00 | 0.69 | 07-FEB-16:10 | 0.51 | 01-FEB-06:55 | 5747.43 | 07-FEB-16:10 | 5402.21 | 06-FEB-15:40 | 441.13 | 07-FEB-16:10 | 1867.83 | 06-FEB-15:00 | 0.00 |
March | 0.182687E+11 | 0.521438E+10 | 744.00 | 0.178990E+11 | 0.369660E+09 | 0.00 | 0.96 | 31-MAR-23:20 | 0.73 | 08-MAR-06:55 | 8786.92 | 31-MAR-23:10 | 8413.15 | 31-MAR-24:00 | 440.14 | 31-MAR-10:20 | 2674.02 | 27-MAR-11:00 | 0.00 |
April | 0.229621E+11 | 0.650121E+10 | 720.00 | 0.224283E+11 | 0.533839E+09 | 0.00 | 1.00 | 01-APR-14:00 | 0.44 | 30-APR-23:52 | 9694.52 | 27-APR-16:00 | 9386.00 | 27-APR-16:00 | 568.10 | 30-APR-15:00 | 3710.43 | 28-APR-12:00 | 0.00 |
May | 0.910803E+10 | 0.327806E+10 | 744.00 | 0.844134E+10 | 0.666687E+09 | 0.00 | 0.65 | 31-MAY-23:02 | 0.36 | 20-MAY-06:50 | 5228.07 | 31-MAY-23:02 | 4865.62 | 31-MAY-23:31 | 631.46 | 30-MAY-02:62 | 1813.55 | 31-MAY-23:02 | 0.00 |
June | 0.142552E+11 | 0.492813E+10 | 720.00 | 0.131516E+11 | 0.110361E+10 | 0.00 | 0.85 | 30-JUN-23:01 | 0.59 | 03-JUN-06:40 | 7403.16 | 30-JUN-23:01 | 6695.56 | 30-JUN-23:50 | 753.59 | 08-JUN-13:10 | 2455.14 | 09-JUN-15:00 | 0.00 |
July | 0.201885E+11 | 0.682333E+10 | 744.00 | 0.187863E+11 | 0.140220E+10 | 0.00 | 1.00 | 31-JUL-23:02 | 0.79 | 03-JUL-06:00 | 9473.23 | 31-JUL-23:02 | 8621.61 | 31-JUL-23:30 | 931.81 | 20-JUL-14:00 | 3189.87 | 21-JUL-12:00 | 0.00 |
August | 0.254420E+11 | 0.845293E+10 | 744.00 | 0.239081E+11 | 0.153385E+10 | 0.00 | 1.00 | 01-AUG-00:02 | 0.47 | 31-AUG-23:12 | 10395.00 | 22-AUG-16:00 | 9587.72 | 10-AUG-16:00 | 964.85 | 08-AUG-13:40 | 4117.52 | 16-AUG-12:00 | 0.00 |
September | 0.945381E+10 | 0.341100E+10 | 720.00 | 0.824486E+10 | 0.120895E+10 | 0.00 | 0.67 | 30-SEP-23:02 | 0.38 | 26-SEP-06:00 | 5639.45 | 30-SEP-23:02 | 4744.63 | 30-SEP-23:04 | 897.22 | 30-SEP-23:02 | 1777.35 | 30-SEP-23:02 | 0.00 |
October | 0.142957E+11 | 0.466538E+10 | 744.00 | 0.133606E+11 | 0.935085E+09 | 0.00 | 0.81 | 31-OCT-23:31 | 0.56 | 21-OCT-06:55 | 6924.83 | 31-OCT-23:31 | 6633.46 | 31-OCT-23:42 | 789.81 | 07-OCT-10:20 | 2131.92 | 06-OCT-16:00 | 0.00 |
November | 0.181945E+11 | 0.530220E+10 | 720.00 | 0.175622E+11 | 0.632312E+09 | 0.00 | 0.91 | 01-NOV-16:00 | 0.75 | 22-NOV-06:55 | 7950.66 | 01-NOV-16:00 | 7361.27 | 13-NOV-15:00 | 641.97 | 01-NOV-15:00 | 2522.41 | 01-NOV-14:00 | 0.00 |
December | 0.232398E+11 | 0.614839E+10 | 744.00 | 0.227670E+11 | 0.472837E+09 | 0.00 | 1.00 | 01-DEC-13:10 | 0.89 | 30-DEC-07:55 | 9653.98 | 05-DEC-17:00 | 9106.21 | 05-DEC-17:00 | 547.77 | 05-DEC-17:00 | 2654.58 | 05-DEC-16:40 | 0.00 |
Annual Sum or Average | 0.194410E+12 | 0.604582E+11 | 8760.00 | 0.184950E+12 | 0.945996E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.736250E+10 | 0.229358E+10 | 672.00 | 0.711230E+10 | 0.250206E+09 | 0.00 | 0.44 | 0.28 | 3518.01 | 3261.29 | 385.00 | 1128.23 | 0.00 | ||||||
Maximum of Months | 0.254420E+11 | 0.845293E+10 | 744.00 | 0.239081E+11 | 0.153385E+10 | 0.00 | 1.00 | 0.89 | 10395.00 | 9587.72 | 964.85 | 4117.52 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID HP COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.616866E+11 | 0.187810E+11 | 744.00 | 0.592643E+11 | 0.242225E+10 | 0.00 | 0.44 | 24-JAN-17:00 | 0.23 | 20-JAN-06:55 | 32791.61 | 24-JAN-17:00 | 30107.69 | 31-JAN-17:00 | 3805.50 | 30-JAN-15:20 | 10063.91 | 23-JAN-14:00 | 0.00 |
February | 0.104239E+12 | 0.300708E+11 | 672.00 | 0.100775E+12 | 0.346367E+10 | 0.00 | 0.68 | 07-FEB-16:20 | 0.47 | 13-FEB-07:00 | 54324.58 | 07-FEB-16:20 | 50680.33 | 06-FEB-15:50 | 4380.75 | 07-FEB-16:10 | 16985.44 | 06-FEB-15:00 | 0.00 |
March | 0.169300E+12 | 0.470180E+11 | 744.00 | 0.165624E+12 | 0.367547E+10 | 0.00 | 0.95 | 31-MAR-23:10 | 0.69 | 08-MAR-06:55 | 83011.44 | 31-MAR-23:10 | 79053.30 | 31-MAR-24:00 | 4381.38 | 31-MAR-10:20 | 24431.78 | 27-MAR-11:00 | 0.00 |
April | 0.217272E+12 | 0.595879E+11 | 720.00 | 0.211953E+12 | 0.531940E+10 | 0.00 | 1.00 | 01-APR-14:50 | 0.43 | 30-APR-23:12 | 92554.48 | 27-APR-16:00 | 89478.15 | 27-APR-16:00 | 5616.51 | 30-APR-15:00 | 34241.76 | 28-APR-12:00 | 0.00 |
May | 0.858760E+11 | 0.299359E+11 | 744.00 | 0.792757E+11 | 0.660032E+10 | 0.00 | 0.66 | 31-MAY-23:02 | 0.34 | 03-MAY-07:00 | 50469.81 | 31-MAY-23:02 | 46917.92 | 31-MAY-23:50 | 6222.99 | 30-MAY-01:02 | 16895.38 | 31-MAY-23:02 | 0.00 |
June | 0.135987E+12 | 0.454514E+11 | 720.00 | 0.125004E+12 | 0.109832E+11 | 0.00 | 0.86 | 30-JUN-23:01 | 0.59 | 03-JUN-07:00 | 71749.57 | 30-JUN-23:01 | 64555.26 | 30-JUN-23:20 | 7504.38 | 08-JUN-13:10 | 22665.48 | 09-JUN-15:00 | 0.00 |
July | 0.192438E+12 | 0.628884E+11 | 744.00 | 0.178462E+12 | 0.139753E+11 | 0.00 | 1.00 | 31-JUL-23:02 | 0.78 | 03-JUL-06:00 | 91791.80 | 31-JUL-23:02 | 83282.74 | 31-JUL-23:43 | 9279.69 | 20-JUL-14:00 | 29375.39 | 21-JUL-12:00 | 0.00 |
August | 0.242776E+12 | 0.780222E+11 | 744.00 | 0.227471E+12 | 0.153046E+11 | 0.00 | 1.00 | 01-AUG-00:02 | 0.44 | 31-AUG-23:02 | 99416.75 | 22-AUG-16:00 | 91393.16 | 10-AUG-16:00 | 9625.29 | 08-AUG-13:40 | 37984.76 | 16-AUG-12:00 | 0.00 |
September | 0.892322E+11 | 0.311546E+11 | 720.00 | 0.772533E+11 | 0.119789E+11 | 0.00 | 0.68 | 30-SEP-23:02 | 0.36 | 30-SEP-07:00 | 54885.12 | 30-SEP-23:02 | 46218.20 | 30-SEP-24:00 | 9096.16 | 30-SEP-23:02 | 16662.46 | 30-SEP-23:02 | 0.00 |
October | 0.135090E+12 | 0.426993E+11 | 744.00 | 0.125794E+12 | 0.929579E+10 | 0.00 | 0.81 | 31-OCT-23:31 | 0.54 | 21-OCT-06:55 | 66325.75 | 31-OCT-23:31 | 63473.22 | 31-OCT-24:00 | 7866.87 | 07-OCT-10:20 | 19666.94 | 06-OCT-16:00 | 0.00 |
November | 0.169827E+12 | 0.480872E+11 | 720.00 | 0.163539E+12 | 0.628820E+10 | 0.00 | 0.91 | 01-NOV-16:00 | 0.71 | 22-NOV-06:55 | 75859.19 | 01-NOV-16:00 | 69667.72 | 01-NOV-16:00 | 6391.83 | 01-NOV-15:00 | 23244.97 | 01-NOV-14:00 | 0.00 |
December | 0.214057E+12 | 0.552169E+11 | 744.00 | 0.209352E+12 | 0.470481E+10 | 0.00 | 1.00 | 01-DEC-13:50 | 0.86 | 18-DEC-07:00 | 91407.89 | 05-DEC-17:00 | 86002.68 | 06-DEC-17:00 | 5468.27 | 05-DEC-17:00 | 24291.32 | 05-DEC-16:50 | 0.00 |
Annual Sum or Average | 0.181778E+13 | 0.548914E+12 | 8760.00 | 0.172377E+13 | 0.940119E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.616866E+11 | 0.187810E+11 | 672.00 | 0.592643E+11 | 0.242225E+10 | 0.00 | 0.44 | 0.23 | 32791.61 | 30107.69 | 3805.50 | 10063.91 | 0.00 | ||||||
Maximum of Months | 0.242776E+12 | 0.780222E+11 | 744.00 | 0.227471E+12 | 0.153046E+11 | 0.00 | 1.00 | 0.86 | 99416.75 | 91393.16 | 9625.29 | 37984.76 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP HP COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.558448E+10 | 0.177248E+10 | 743.67 | 0.534709E+10 | 0.237396E+09 | 0.00 | 0.43 | 24-JAN-17:00 | 0.00 | 01-JAN-06:45 | 3389.34 | 24-JAN-17:00 | 3135.76 | 31-JAN-17:00 | 385.34 | 30-JAN-15:10 | 1086.63 | 23-JAN-14:00 | 0.00 |
February | 0.101183E+11 | 0.304930E+10 | 672.00 | 0.977338E+10 | 0.344918E+09 | 0.00 | 0.67 | 07-FEB-16:10 | 0.37 | 12-FEB-07:50 | 5624.16 | 07-FEB-16:10 | 5277.55 | 06-FEB-15:50 | 439.13 | 07-FEB-16:10 | 1829.96 | 06-FEB-15:00 | 0.00 |
March | 0.168194E+11 | 0.488343E+10 | 744.00 | 0.164524E+11 | 0.366996E+09 | 0.00 | 0.91 | 31-MAR-23:10 | 0.62 | 08-MAR-06:55 | 8216.64 | 31-MAR-23:10 | 7810.25 | 31-MAR-23:50 | 438.86 | 31-MAR-10:20 | 2590.40 | 27-MAR-11:00 | 0.00 |
April | 0.218658E+11 | 0.625489E+10 | 720.00 | 0.213348E+11 | 0.530956E+09 | 0.00 | 1.00 | 02-APR-14:13 | 0.42 | 30-APR-23:03 | 9522.65 | 27-APR-16:00 | 9215.99 | 27-APR-15:50 | 565.79 | 30-APR-15:00 | 3627.18 | 28-APR-12:00 | 0.00 |
May | 0.892365E+10 | 0.322477E+10 | 744.00 | 0.825968E+10 | 0.663968E+09 | 0.00 | 0.64 | 31-MAY-23:02 | 0.31 | 03-MAY-07:00 | 5153.23 | 31-MAY-23:02 | 4795.26 | 31-MAY-23:50 | 626.33 | 30-MAY-01:40 | 1792.60 | 31-MAY-23:02 | 0.00 |
June | 0.139721E+11 | 0.485136E+10 | 720.00 | 0.128710E+11 | 0.110113E+10 | 0.00 | 0.84 | 30-JUN-23:01 | 0.55 | 03-JUN-07:00 | 7242.91 | 30-JUN-23:01 | 6526.80 | 30-JUN-23:20 | 756.93 | 08-JUN-13:00 | 2466.14 | 09-JUN-15:00 | 0.00 |
July | 0.197063E+11 | 0.670207E+10 | 744.00 | 0.183070E+11 | 0.139932E+10 | 0.00 | 1.00 | 31-JUL-23:02 | 0.75 | 03-JUL-06:00 | 9237.58 | 31-JUL-23:02 | 8424.95 | 31-JUL-23:40 | 932.96 | 20-JUL-14:00 | 3170.73 | 21-JUL-12:00 | 0.00 |
August | 0.247054E+11 | 0.818689E+10 | 744.00 | 0.231787E+11 | 0.152670E+10 | 0.00 | 1.00 | 01-AUG-00:02 | 0.43 | 31-AUG-23:02 | 10239.87 | 10-AUG-16:00 | 9531.32 | 06-AUG-16:40 | 964.00 | 08-AUG-13:40 | 4041.18 | 16-AUG-12:10 | 0.00 |
September | 0.925236E+10 | 0.335027E+10 | 720.00 | 0.804799E+10 | 0.120437E+10 | 0.00 | 0.66 | 30-SEP-23:02 | 0.33 | 30-SEP-07:00 | 5574.81 | 30-SEP-23:02 | 4711.08 | 30-SEP-24:00 | 900.58 | 30-SEP-23:02 | 1770.29 | 04-SEP-15:45 | 0.00 |
October | 0.137109E+11 | 0.450941E+10 | 744.00 | 0.127804E+11 | 0.930495E+09 | 0.00 | 0.78 | 31-OCT-23:55 | 0.49 | 21-OCT-06:55 | 6636.94 | 31-OCT-23:31 | 6351.79 | 31-OCT-24:00 | 792.06 | 07-OCT-10:20 | 2117.27 | 06-OCT-16:00 | 0.00 |
November | 0.169151E+11 | 0.500723E+10 | 720.00 | 0.162869E+11 | 0.628175E+09 | 0.00 | 0.89 | 01-NOV-14:40 | 0.65 | 22-NOV-06:55 | 7785.75 | 01-NOV-15:10 | 7162.64 | 01-NOV-16:00 | 640.93 | 01-NOV-15:00 | 2483.84 | 01-NOV-14:00 | 0.00 |
December | 0.210020E+11 | 0.568884E+10 | 744.00 | 0.205326E+11 | 0.469413E+09 | 0.00 | 1.00 | 05-DEC-17:00 | 0.75 | 31-DEC-07:50 | 9274.24 | 05-DEC-17:00 | 8744.60 | 06-DEC-16:40 | 541.91 | 05-DEC-17:00 | 2543.00 | 01-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.182576E+12 | 0.574809E+11 | 8759.67 | 0.173172E+12 | 0.940384E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.558448E+10 | 0.177248E+10 | 672.00 | 0.534709E+10 | 0.237396E+09 | 0.00 | 0.43 | 0.00 | 3389.34 | 3135.76 | 385.34 | 1086.63 | 0.00 | ||||||
Maximum of Months | 0.247054E+11 | 0.818689E+10 | 744.00 | 0.231787E+11 | 0.152670E+10 | 0.00 | 1.00 | 0.75 | 10239.87 | 9531.32 | 964.00 | 4041.18 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.44 | 0.00 | 100.44 | 144.25 | 438.29 | 0.00 | 0.00 | 0.00 |
February | 115.13 | 0.00 | 115.13 | 216.39 | 368.80 | 0.00 | 0.00 | 0.00 |
March | 132.24 | 0.00 | 132.24 | 338.22 | 275.37 | 0.00 | 0.00 | 0.00 |
April | 149.21 | 0.52 | 148.68 | 536.87 | 156.74 | 0.00 | 0.00 | 0.00 |
May | 169.69 | 6.90 | 162.78 | 885.89 | 34.71 | 0.00 | 0.00 | 0.00 |
June | 183.11 | 13.53 | 169.59 | 1043.23 | 4.36 | 0.00 | 0.00 | 0.00 |
July | 166.80 | 6.78 | 160.01 | 1199.78 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 154.06 | 1.95 | 152.11 | 1184.54 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 139.73 | 0.03 | 139.70 | 870.11 | 10.67 | 0.00 | 0.00 | 0.00 |
October | 123.85 | 0.00 | 123.85 | 593.81 | 57.87 | 0.00 | 0.00 | 0.00 |
November | 106.33 | 0.00 | 106.33 | 345.86 | 192.53 | 0.00 | 0.00 | 0.00 |
December | 93.74 | 0.00 | 93.74 | 171.56 | 369.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 136.27 | 2.49 | 133.79 | 630.14 | 158.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.74 | 0.00 | 93.74 | 144.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.11 | 13.53 | 169.59 | 1199.78 | 438.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.44 | 0.00 | 100.44 | 144.25 | 438.29 | 0.00 | 0.00 | 0.00 |
February | 115.13 | 0.00 | 115.13 | 216.39 | 368.80 | 0.00 | 0.00 | 0.00 |
March | 132.24 | 0.00 | 132.24 | 338.22 | 275.37 | 0.00 | 0.00 | 0.00 |
April | 149.21 | 0.52 | 148.68 | 536.87 | 156.74 | 0.00 | 0.00 | 0.00 |
May | 169.69 | 6.90 | 162.78 | 885.89 | 34.71 | 0.00 | 0.00 | 0.00 |
June | 183.11 | 13.53 | 169.59 | 1043.23 | 4.36 | 0.00 | 0.00 | 0.00 |
July | 166.80 | 6.78 | 160.01 | 1199.78 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 154.06 | 1.95 | 152.11 | 1184.54 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 139.73 | 0.03 | 139.70 | 870.11 | 10.67 | 0.00 | 0.00 | 0.00 |
October | 123.85 | 0.00 | 123.85 | 593.81 | 57.87 | 0.00 | 0.00 | 0.00 |
November | 106.33 | 0.00 | 106.33 | 345.86 | 192.53 | 0.00 | 0.00 | 0.00 |
December | 93.74 | 0.00 | 93.74 | 171.56 | 369.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 136.27 | 2.49 | 133.79 | 630.14 | 158.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.74 | 0.00 | 93.74 | 144.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.11 | 13.53 | 169.59 | 1199.78 | 438.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.44 | 0.00 | 100.44 | 144.25 | 438.29 | 0.00 | 0.00 | 0.00 |
February | 115.13 | 0.00 | 115.13 | 216.39 | 368.80 | 0.00 | 0.00 | 0.00 |
March | 132.24 | 0.00 | 132.24 | 338.22 | 275.37 | 0.00 | 0.00 | 0.00 |
April | 149.21 | 0.52 | 148.68 | 536.87 | 156.74 | 0.00 | 0.00 | 0.00 |
May | 169.69 | 6.90 | 162.78 | 885.89 | 34.71 | 0.00 | 0.00 | 0.00 |
June | 183.11 | 13.53 | 169.59 | 1043.23 | 4.36 | 0.00 | 0.00 | 0.00 |
July | 166.80 | 6.78 | 160.01 | 1199.78 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 154.06 | 1.95 | 152.11 | 1184.54 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 139.73 | 0.03 | 139.70 | 870.11 | 10.67 | 0.00 | 0.00 | 0.00 |
October | 123.85 | 0.00 | 123.85 | 593.81 | 57.87 | 0.00 | 0.00 | 0.00 |
November | 106.33 | 0.00 | 106.33 | 345.86 | 192.53 | 0.00 | 0.00 | 0.00 |
December | 93.74 | 0.00 | 93.74 | 171.56 | 369.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 136.27 | 2.49 | 133.79 | 630.14 | 158.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.74 | 0.00 | 93.74 | 144.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.11 | 13.53 | 169.59 | 1199.78 | 438.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.44 | 0.00 | 100.44 | 144.25 | 438.29 | 0.00 | 0.00 | 0.00 |
February | 115.13 | 0.00 | 115.13 | 216.39 | 368.80 | 0.00 | 0.00 | 0.00 |
March | 132.24 | 0.00 | 132.24 | 338.22 | 275.37 | 0.00 | 0.00 | 0.00 |
April | 149.21 | 0.52 | 148.68 | 536.87 | 156.74 | 0.00 | 0.00 | 0.00 |
May | 169.69 | 6.90 | 162.78 | 885.89 | 34.71 | 0.00 | 0.00 | 0.00 |
June | 183.11 | 13.53 | 169.59 | 1043.23 | 4.36 | 0.00 | 0.00 | 0.00 |
July | 166.80 | 6.78 | 160.01 | 1199.78 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 154.06 | 1.95 | 152.11 | 1184.54 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 139.73 | 0.03 | 139.70 | 870.11 | 10.67 | 0.00 | 0.00 | 0.00 |
October | 123.85 | 0.00 | 123.85 | 593.81 | 57.87 | 0.00 | 0.00 | 0.00 |
November | 106.33 | 0.00 | 106.33 | 345.86 | 192.53 | 0.00 | 0.00 | 0.00 |
December | 93.74 | 0.00 | 93.74 | 171.56 | 369.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 136.27 | 2.49 | 133.79 | 630.14 | 158.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.74 | 0.00 | 93.74 | 144.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.11 | 13.53 | 169.59 | 1199.78 | 438.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.43 | 0.00 | 100.43 | 144.24 | 438.27 | 0.00 | 0.00 | 0.00 |
February | 115.12 | 0.00 | 115.12 | 216.38 | 368.78 | 0.00 | 0.00 | 0.00 |
March | 132.23 | 0.00 | 132.23 | 338.21 | 275.36 | 0.00 | 0.00 | 0.00 |
April | 149.20 | 0.52 | 148.68 | 536.85 | 156.73 | 0.00 | 0.00 | 0.00 |
May | 169.68 | 6.90 | 162.78 | 885.86 | 34.71 | 0.00 | 0.00 | 0.00 |
June | 183.11 | 13.52 | 169.58 | 1043.19 | 4.36 | 0.00 | 0.00 | 0.00 |
July | 166.79 | 6.78 | 160.01 | 1199.73 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 154.06 | 1.95 | 152.10 | 1184.49 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 139.72 | 0.03 | 139.69 | 870.08 | 10.67 | 0.00 | 0.00 | 0.00 |
October | 123.85 | 0.00 | 123.85 | 593.79 | 57.87 | 0.00 | 0.00 | 0.00 |
November | 106.32 | 0.00 | 106.32 | 345.85 | 192.52 | 0.00 | 0.00 | 0.00 |
December | 93.74 | 0.00 | 93.74 | 171.55 | 369.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 136.27 | 2.49 | 133.78 | 630.11 | 158.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.74 | 0.00 | 93.74 | 144.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.11 | 13.52 | 169.58 | 1199.73 | 438.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 202.20 | 61.40 | 140.80 | 376.70 | 432.51 | 0.00 | 0.00 | 0.00 |
February | 220.29 | 59.92 | 160.37 | 480.65 | 362.28 | 0.00 | 0.00 | 0.00 |
March | 243.05 | 59.94 | 183.11 | 653.85 | 264.70 | 0.00 | 0.00 | 0.00 |
April | 295.83 | 86.17 | 209.66 | 993.01 | 142.22 | 0.00 | 0.00 | 0.00 |
May | 330.11 | 104.81 | 225.30 | 1423.79 | 31.56 | 0.00 | 0.00 | 0.00 |
June | 323.98 | 99.19 | 224.79 | 1549.21 | 2.03 | 0.00 | 0.00 | 0.00 |
July | 302.89 | 87.80 | 215.10 | 1731.18 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 309.58 | 95.08 | 214.49 | 1785.90 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 290.71 | 89.69 | 201.02 | 1395.03 | 8.07 | 0.00 | 0.00 | 0.00 |
October | 263.89 | 86.14 | 177.75 | 1046.15 | 46.43 | 0.00 | 0.00 | 0.00 |
November | 221.67 | 70.51 | 151.16 | 681.39 | 178.73 | 0.00 | 0.00 | 0.00 |
December | 179.62 | 49.68 | 129.94 | 389.30 | 349.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 265.49 | 79.27 | 186.22 | 1045.56 | 150.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 179.62 | 49.68 | 129.94 | 376.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 330.11 | 104.81 | 225.30 | 1785.90 | 432.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 202.20 | 61.40 | 140.80 | 376.70 | 432.51 | 0.00 | 0.00 | 0.00 |
February | 220.29 | 59.92 | 160.37 | 480.65 | 362.28 | 0.00 | 0.00 | 0.00 |
March | 243.05 | 59.94 | 183.11 | 653.85 | 264.70 | 0.00 | 0.00 | 0.00 |
April | 295.83 | 86.17 | 209.66 | 993.01 | 142.22 | 0.00 | 0.00 | 0.00 |
May | 330.11 | 104.81 | 225.30 | 1423.79 | 31.56 | 0.00 | 0.00 | 0.00 |
June | 323.98 | 99.19 | 224.79 | 1549.21 | 2.03 | 0.00 | 0.00 | 0.00 |
July | 302.89 | 87.80 | 215.10 | 1731.18 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 309.58 | 95.08 | 214.49 | 1785.90 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 290.71 | 89.69 | 201.02 | 1395.03 | 8.07 | 0.00 | 0.00 | 0.00 |
October | 263.89 | 86.14 | 177.75 | 1046.15 | 46.43 | 0.00 | 0.00 | 0.00 |
November | 221.67 | 70.51 | 151.16 | 681.39 | 178.73 | 0.00 | 0.00 | 0.00 |
December | 179.62 | 49.68 | 129.94 | 389.30 | 349.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 265.49 | 79.27 | 186.22 | 1045.56 | 150.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 179.62 | 49.68 | 129.94 | 376.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 330.11 | 104.81 | 225.30 | 1785.90 | 432.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 202.20 | 61.40 | 140.79 | 376.69 | 432.50 | 0.00 | 0.00 | 0.00 |
February | 220.29 | 59.92 | 160.37 | 480.64 | 362.28 | 0.00 | 0.00 | 0.00 |
March | 243.05 | 59.93 | 183.11 | 653.83 | 264.69 | 0.00 | 0.00 | 0.00 |
April | 295.83 | 86.17 | 209.66 | 993.00 | 142.22 | 0.00 | 0.00 | 0.00 |
May | 330.10 | 104.81 | 225.29 | 1423.77 | 31.56 | 0.00 | 0.00 | 0.00 |
June | 323.97 | 99.19 | 224.78 | 1549.18 | 2.03 | 0.00 | 0.00 | 0.00 |
July | 302.89 | 87.79 | 215.09 | 1731.15 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 309.57 | 95.08 | 214.49 | 1785.87 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 290.70 | 89.69 | 201.01 | 1395.00 | 8.07 | 0.00 | 0.00 | 0.00 |
October | 263.89 | 86.13 | 177.75 | 1046.13 | 46.43 | 0.00 | 0.00 | 0.00 |
November | 221.67 | 70.51 | 151.16 | 681.38 | 178.73 | 0.00 | 0.00 | 0.00 |
December | 179.62 | 49.68 | 129.94 | 389.29 | 349.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 265.49 | 79.27 | 186.22 | 1045.54 | 150.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 179.62 | 49.68 | 129.94 | 376.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 330.10 | 104.81 | 225.29 | 1785.87 | 432.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 322.00 | 150.01 | 171.99 | 725.27 | 403.32 | 0.00 | 0.00 | 0.00 |
February | 306.44 | 126.31 | 180.13 | 747.79 | 349.09 | 0.00 | 0.00 | 0.00 |
March | 258.55 | 75.79 | 182.76 | 727.26 | 267.73 | 0.00 | 0.00 | 0.00 |
April | 204.62 | 28.32 | 176.30 | 724.32 | 153.23 | 0.00 | 0.00 | 0.00 |
May | 169.03 | 4.54 | 164.49 | 890.83 | 33.83 | 0.00 | 0.00 | 0.00 |
June | 157.54 | 0.41 | 157.13 | 970.70 | 3.14 | 0.00 | 0.00 | 0.00 |
July | 158.34 | 2.36 | 155.98 | 1177.21 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 188.06 | 18.51 | 169.55 | 1307.79 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 250.78 | 65.32 | 185.46 | 1233.25 | 10.16 | 0.00 | 0.00 | 0.00 |
October | 320.79 | 131.03 | 189.76 | 1195.18 | 55.24 | 0.00 | 0.00 | 0.00 |
November | 346.22 | 166.24 | 179.98 | 1037.16 | 185.22 | 0.00 | 0.00 | 0.00 |
December | 318.77 | 155.53 | 163.24 | 789.50 | 342.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 249.75 | 76.76 | 172.99 | 961.93 | 149.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 157.54 | 0.41 | 155.98 | 724.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 346.22 | 166.24 | 189.76 | 1307.79 | 403.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 322.00 | 150.01 | 171.99 | 725.27 | 403.32 | 0.00 | 0.00 | 0.00 |
February | 306.44 | 126.31 | 180.13 | 747.79 | 349.09 | 0.00 | 0.00 | 0.00 |
March | 258.55 | 75.79 | 182.76 | 727.26 | 267.73 | 0.00 | 0.00 | 0.00 |
April | 204.62 | 28.32 | 176.30 | 724.32 | 153.23 | 0.00 | 0.00 | 0.00 |
May | 169.03 | 4.54 | 164.49 | 890.83 | 33.83 | 0.00 | 0.00 | 0.00 |
June | 157.54 | 0.41 | 157.13 | 970.70 | 3.14 | 0.00 | 0.00 | 0.00 |
July | 158.34 | 2.36 | 155.98 | 1177.21 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 188.06 | 18.51 | 169.55 | 1307.79 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 250.78 | 65.32 | 185.46 | 1233.25 | 10.16 | 0.00 | 0.00 | 0.00 |
October | 320.79 | 131.03 | 189.76 | 1195.18 | 55.24 | 0.00 | 0.00 | 0.00 |
November | 346.22 | 166.24 | 179.98 | 1037.16 | 185.22 | 0.00 | 0.00 | 0.00 |
December | 318.77 | 155.53 | 163.24 | 789.50 | 342.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 249.75 | 76.76 | 172.99 | 961.93 | 149.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 157.54 | 0.41 | 155.98 | 724.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 346.22 | 166.24 | 189.76 | 1307.79 | 403.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 322.00 | 150.01 | 171.99 | 725.27 | 403.32 | 0.00 | 0.00 | 0.00 |
February | 306.44 | 126.31 | 180.13 | 747.79 | 349.09 | 0.00 | 0.00 | 0.00 |
March | 258.55 | 75.79 | 182.76 | 727.26 | 267.73 | 0.00 | 0.00 | 0.00 |
April | 204.62 | 28.32 | 176.30 | 724.32 | 153.23 | 0.00 | 0.00 | 0.00 |
May | 169.03 | 4.54 | 164.49 | 890.83 | 33.83 | 0.00 | 0.00 | 0.00 |
June | 157.54 | 0.41 | 157.13 | 970.70 | 3.14 | 0.00 | 0.00 | 0.00 |
July | 158.34 | 2.36 | 155.98 | 1177.21 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 188.06 | 18.51 | 169.55 | 1307.79 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 250.78 | 65.32 | 185.46 | 1233.25 | 10.16 | 0.00 | 0.00 | 0.00 |
October | 320.79 | 131.03 | 189.76 | 1195.18 | 55.24 | 0.00 | 0.00 | 0.00 |
November | 346.22 | 166.24 | 179.98 | 1037.16 | 185.22 | 0.00 | 0.00 | 0.00 |
December | 318.77 | 155.53 | 163.24 | 789.50 | 342.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 249.75 | 76.76 | 172.99 | 961.93 | 149.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 157.54 | 0.41 | 155.98 | 724.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 346.22 | 166.24 | 189.76 | 1307.79 | 403.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 322.00 | 150.01 | 171.99 | 725.27 | 403.32 | 0.00 | 0.00 | 0.00 |
February | 306.44 | 126.31 | 180.13 | 747.79 | 349.09 | 0.00 | 0.00 | 0.00 |
March | 258.55 | 75.79 | 182.76 | 727.26 | 267.73 | 0.00 | 0.00 | 0.00 |
April | 204.62 | 28.32 | 176.30 | 724.32 | 153.23 | 0.00 | 0.00 | 0.00 |
May | 169.03 | 4.54 | 164.49 | 890.83 | 33.83 | 0.00 | 0.00 | 0.00 |
June | 157.54 | 0.41 | 157.13 | 970.70 | 3.14 | 0.00 | 0.00 | 0.00 |
July | 158.34 | 2.36 | 155.98 | 1177.21 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 188.06 | 18.51 | 169.55 | 1307.79 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 250.78 | 65.32 | 185.46 | 1233.25 | 10.16 | 0.00 | 0.00 | 0.00 |
October | 320.79 | 131.03 | 189.76 | 1195.18 | 55.24 | 0.00 | 0.00 | 0.00 |
November | 346.22 | 166.24 | 179.98 | 1037.16 | 185.22 | 0.00 | 0.00 | 0.00 |
December | 318.77 | 155.53 | 163.24 | 789.50 | 342.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 249.75 | 76.76 | 172.99 | 961.93 | 149.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 157.54 | 0.41 | 155.98 | 724.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 346.22 | 166.24 | 189.76 | 1307.79 | 403.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 321.99 | 150.01 | 171.98 | 725.24 | 403.31 | 0.00 | 0.00 | 0.00 |
February | 306.43 | 126.31 | 180.12 | 747.76 | 349.07 | 0.00 | 0.00 | 0.00 |
March | 258.54 | 75.79 | 182.75 | 727.23 | 267.72 | 0.00 | 0.00 | 0.00 |
April | 204.61 | 28.32 | 176.29 | 724.29 | 153.23 | 0.00 | 0.00 | 0.00 |
May | 169.03 | 4.54 | 164.48 | 890.80 | 33.83 | 0.00 | 0.00 | 0.00 |
June | 157.53 | 0.41 | 157.12 | 970.66 | 3.14 | 0.00 | 0.00 | 0.00 |
July | 158.33 | 2.36 | 155.97 | 1177.16 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 188.05 | 18.51 | 169.54 | 1307.73 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 250.77 | 65.32 | 185.45 | 1233.20 | 10.16 | 0.00 | 0.00 | 0.00 |
October | 320.78 | 131.03 | 189.76 | 1195.13 | 55.24 | 0.00 | 0.00 | 0.00 |
November | 346.21 | 166.24 | 179.97 | 1037.12 | 185.21 | 0.00 | 0.00 | 0.00 |
December | 318.76 | 155.53 | 163.23 | 789.47 | 342.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 249.74 | 76.76 | 172.98 | 961.89 | 149.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 157.53 | 0.41 | 155.97 | 724.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 346.21 | 166.24 | 189.76 | 1307.73 | 403.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 198.44 | 57.32 | 141.11 | 380.73 | 516.19 | 0.00 | 0.00 | 0.00 |
February | 226.56 | 64.96 | 161.60 | 489.75 | 462.17 | 0.00 | 0.00 | 0.00 |
March | 267.58 | 79.08 | 188.50 | 684.39 | 375.14 | 0.00 | 0.00 | 0.00 |
April | 292.06 | 81.63 | 210.42 | 917.73 | 241.64 | 0.00 | 0.00 | 0.00 |
May | 318.50 | 95.32 | 223.18 | 1350.10 | 52.48 | 0.00 | 0.00 | 0.00 |
June | 329.20 | 103.79 | 225.41 | 1492.61 | 9.20 | 0.00 | 0.00 | 0.00 |
July | 302.57 | 86.98 | 215.59 | 1625.86 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 309.43 | 93.82 | 215.61 | 1652.04 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 294.40 | 92.29 | 202.12 | 1354.77 | 16.51 | 0.00 | 0.00 | 0.00 |
October | 261.91 | 84.61 | 177.30 | 997.48 | 90.29 | 0.00 | 0.00 | 0.00 |
November | 225.40 | 73.93 | 151.47 | 666.60 | 275.17 | 0.00 | 0.00 | 0.00 |
December | 189.11 | 57.64 | 131.47 | 395.72 | 504.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 268.08 | 81.00 | 187.08 | 1003.67 | 210.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 189.11 | 57.32 | 131.47 | 380.73 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 329.20 | 103.79 | 225.41 | 1652.04 | 516.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 198.44 | 57.32 | 141.11 | 380.73 | 516.19 | 0.00 | 0.00 | 0.00 |
February | 226.56 | 64.96 | 161.60 | 489.75 | 462.17 | 0.00 | 0.00 | 0.00 |
March | 267.58 | 79.08 | 188.50 | 684.39 | 375.14 | 0.00 | 0.00 | 0.00 |
April | 292.06 | 81.63 | 210.42 | 917.73 | 241.64 | 0.00 | 0.00 | 0.00 |
May | 318.50 | 95.32 | 223.18 | 1350.10 | 52.48 | 0.00 | 0.00 | 0.00 |
June | 329.20 | 103.79 | 225.41 | 1492.61 | 9.20 | 0.00 | 0.00 | 0.00 |
July | 302.57 | 86.98 | 215.59 | 1625.86 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 309.43 | 93.82 | 215.61 | 1652.04 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 294.40 | 92.29 | 202.12 | 1354.77 | 16.51 | 0.00 | 0.00 | 0.00 |
October | 261.91 | 84.61 | 177.30 | 997.48 | 90.29 | 0.00 | 0.00 | 0.00 |
November | 225.40 | 73.93 | 151.47 | 666.60 | 275.17 | 0.00 | 0.00 | 0.00 |
December | 189.11 | 57.64 | 131.47 | 395.72 | 504.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 268.08 | 81.00 | 187.08 | 1003.67 | 210.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 189.11 | 57.32 | 131.47 | 380.73 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 329.20 | 103.79 | 225.41 | 1652.04 | 516.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 198.43 | 57.32 | 141.11 | 380.72 | 516.18 | 0.00 | 0.00 | 0.00 |
February | 226.55 | 64.96 | 161.60 | 489.74 | 462.16 | 0.00 | 0.00 | 0.00 |
March | 267.57 | 79.07 | 188.50 | 684.37 | 375.13 | 0.00 | 0.00 | 0.00 |
April | 292.05 | 81.63 | 210.42 | 917.71 | 241.64 | 0.00 | 0.00 | 0.00 |
May | 318.49 | 95.31 | 223.18 | 1350.07 | 52.48 | 0.00 | 0.00 | 0.00 |
June | 329.19 | 103.78 | 225.41 | 1492.58 | 9.20 | 0.00 | 0.00 | 0.00 |
July | 302.56 | 86.97 | 215.59 | 1625.83 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 309.42 | 93.82 | 215.61 | 1652.01 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 294.40 | 92.28 | 202.11 | 1354.74 | 16.51 | 0.00 | 0.00 | 0.00 |
October | 261.90 | 84.61 | 177.30 | 997.46 | 90.29 | 0.00 | 0.00 | 0.00 |
November | 225.39 | 73.93 | 151.47 | 666.59 | 275.16 | 0.00 | 0.00 | 0.00 |
December | 189.10 | 57.64 | 131.46 | 395.71 | 504.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 268.07 | 81.00 | 187.07 | 1003.65 | 210.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 189.10 | 57.32 | 131.46 | 380.72 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 329.19 | 103.78 | 225.41 | 1652.01 | 516.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 502.17 | 0.00 | 502.17 | 805.20 | 1901.53 | 0.00 | 0.00 | 0.00 |
February | 575.63 | 0.00 | 575.63 | 1157.93 | 1576.84 | 0.00 | 0.00 | 0.00 |
March | 661.19 | 0.00 | 661.19 | 1753.07 | 1178.05 | 0.00 | 0.00 | 0.00 |
April | 746.02 | 2.61 | 743.41 | 2746.53 | 729.72 | 0.00 | 0.00 | 0.00 |
May | 848.43 | 34.52 | 813.91 | 4468.06 | 175.65 | 0.00 | 0.00 | 0.00 |
June | 915.56 | 67.63 | 847.93 | 5254.70 | 31.88 | 0.00 | 0.00 | 0.00 |
July | 833.97 | 33.90 | 800.06 | 6100.20 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 770.31 | 9.77 | 760.54 | 6043.47 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 698.64 | 0.16 | 698.48 | 4417.14 | 56.61 | 0.00 | 0.00 | 0.00 |
October | 619.26 | 0.00 | 619.26 | 3044.44 | 283.10 | 0.00 | 0.00 | 0.00 |
November | 531.62 | 0.00 | 531.62 | 1824.17 | 819.36 | 0.00 | 0.00 | 0.00 |
December | 468.71 | 0.00 | 468.71 | 971.03 | 1508.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 681.37 | 12.43 | 668.94 | 3228.62 | 684.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 468.71 | 0.00 | 468.71 | 805.20 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 915.56 | 67.63 | 847.93 | 6100.20 | 1901.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 606.59 | 184.21 | 422.38 | 1166.71 | 1164.74 | 0.00 | 0.00 | 0.00 |
February | 660.87 | 179.75 | 481.12 | 1451.50 | 973.65 | 0.00 | 0.00 | 0.00 |
March | 729.14 | 179.81 | 549.34 | 1946.09 | 731.35 | 0.00 | 0.00 | 0.00 |
April | 887.49 | 258.51 | 628.98 | 2925.68 | 457.93 | 0.00 | 0.00 | 0.00 |
May | 990.32 | 314.43 | 675.89 | 4209.00 | 104.92 | 0.00 | 0.00 | 0.00 |
June | 971.92 | 297.57 | 674.36 | 4562.49 | 15.57 | 0.00 | 0.00 | 0.00 |
July | 908.67 | 263.38 | 645.28 | 5131.20 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 928.72 | 285.24 | 643.48 | 5283.50 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 872.12 | 269.07 | 603.05 | 4124.21 | 29.82 | 0.00 | 0.00 | 0.00 |
October | 791.66 | 258.41 | 533.26 | 3084.38 | 161.88 | 0.00 | 0.00 | 0.00 |
November | 665.00 | 211.53 | 453.47 | 2030.65 | 504.40 | 0.00 | 0.00 | 0.00 |
December | 538.85 | 149.04 | 389.82 | 1205.56 | 928.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 796.47 | 237.82 | 558.66 | 3103.43 | 420.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 538.85 | 149.04 | 389.82 | 1166.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 990.32 | 314.43 | 675.89 | 5283.50 | 1164.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1609.98 | 750.05 | 859.94 | 3535.00 | 1926.15 | 0.00 | 0.00 | 0.00 |
February | 1532.19 | 631.55 | 900.64 | 3658.62 | 1630.41 | 0.00 | 0.00 | 0.00 |
March | 1292.74 | 378.94 | 913.80 | 3593.66 | 1231.91 | 0.00 | 0.00 | 0.00 |
April | 1023.08 | 141.61 | 881.48 | 3627.19 | 746.34 | 0.00 | 0.00 | 0.00 |
May | 845.16 | 22.71 | 822.45 | 4491.35 | 169.50 | 0.00 | 0.00 | 0.00 |
June | 787.69 | 2.07 | 785.63 | 4912.14 | 22.64 | 0.00 | 0.00 | 0.00 |
July | 791.69 | 11.79 | 779.90 | 5981.60 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 940.29 | 92.56 | 847.72 | 6621.40 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1253.86 | 326.59 | 927.27 | 6142.97 | 55.53 | 0.00 | 0.00 | 0.00 |
October | 1603.95 | 655.15 | 948.80 | 5910.10 | 293.96 | 0.00 | 0.00 | 0.00 |
November | 1731.08 | 831.20 | 899.88 | 5110.81 | 873.98 | 0.00 | 0.00 | 0.00 |
December | 1593.83 | 777.65 | 816.17 | 3898.83 | 1570.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1248.71 | 383.79 | 864.92 | 4797.88 | 705.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 787.69 | 2.07 | 779.90 | 3535.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1731.08 | 831.20 | 948.80 | 6621.40 | 1926.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 595.30 | 171.97 | 423.33 | 1195.19 | 1309.22 | 0.00 | 0.00 | 0.00 |
February | 679.66 | 194.87 | 484.79 | 1545.02 | 1086.41 | 0.00 | 0.00 | 0.00 |
March | 802.73 | 237.22 | 565.50 | 2136.79 | 838.36 | 0.00 | 0.00 | 0.00 |
April | 876.16 | 244.90 | 631.26 | 2859.89 | 544.22 | 0.00 | 0.00 | 0.00 |
May | 955.49 | 285.94 | 669.54 | 4078.64 | 135.08 | 0.00 | 0.00 | 0.00 |
June | 987.58 | 311.35 | 676.23 | 4567.49 | 23.38 | 0.00 | 0.00 | 0.00 |
July | 907.70 | 260.93 | 646.77 | 5064.43 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 928.28 | 281.46 | 646.82 | 5185.53 | 0.09 | 0.00 | 0.00 | 0.00 |
September | 883.20 | 276.85 | 606.34 | 4116.17 | 42.65 | 0.00 | 0.00 | 0.00 |
October | 785.72 | 253.82 | 531.90 | 3075.38 | 211.84 | 0.00 | 0.00 | 0.00 |
November | 676.18 | 221.78 | 454.40 | 2116.01 | 584.43 | 0.00 | 0.00 | 0.00 |
December | 567.31 | 172.92 | 394.39 | 1332.69 | 1055.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 804.23 | 243.00 | 561.23 | 3115.55 | 483.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 567.31 | 171.97 | 394.39 | 1195.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 987.58 | 311.35 | 676.23 | 5185.53 | 1309.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 502.17 | 0.00 | 502.17 | 854.44 | 1688.58 | 0.00 | 0.00 | 0.00 |
February | 575.63 | 0.00 | 575.63 | 1181.61 | 1424.53 | 0.00 | 0.00 | 0.00 |
March | 661.19 | 0.00 | 661.19 | 1749.22 | 1084.06 | 0.00 | 0.00 | 0.00 |
April | 746.02 | 2.61 | 743.41 | 2709.42 | 691.27 | 0.00 | 0.00 | 0.00 |
May | 848.43 | 34.52 | 813.91 | 4403.29 | 172.71 | 0.00 | 0.00 | 0.00 |
June | 915.56 | 67.63 | 847.93 | 5182.55 | 32.24 | 0.00 | 0.00 | 0.00 |
July | 833.97 | 33.90 | 800.06 | 6020.54 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 770.31 | 9.77 | 760.54 | 5977.34 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 698.64 | 0.16 | 698.48 | 4365.12 | 54.47 | 0.00 | 0.00 | 0.00 |
October | 619.26 | 0.00 | 619.26 | 3019.32 | 265.34 | 0.00 | 0.00 | 0.00 |
November | 531.62 | 0.00 | 531.62 | 1837.14 | 736.15 | 0.00 | 0.00 | 0.00 |
December | 468.71 | 0.00 | 468.71 | 1015.10 | 1334.54 | 3.00 | 0.00 | 0.00 |
Annual Sum or Average | 681.37 | 12.43 | 668.94 | 3205.83 | 619.76 | 3.00 | 0.00 | 0.00 |
Minimum of Months | 468.71 | 0.00 | 468.71 | 854.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 915.56 | 67.63 | 847.93 | 6020.54 | 1688.58 | 3.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 606.59 | 184.21 | 422.38 | 1199.24 | 1057.83 | 0.00 | 0.00 | 0.00 |
February | 660.87 | 179.75 | 481.12 | 1458.93 | 901.74 | 0.00 | 0.00 | 0.00 |
March | 729.14 | 179.81 | 549.34 | 1936.44 | 688.36 | 0.00 | 0.00 | 0.00 |
April | 887.49 | 258.51 | 628.98 | 2896.66 | 442.70 | 0.00 | 0.00 | 0.00 |
May | 990.32 | 314.43 | 675.89 | 4160.56 | 104.94 | 0.00 | 0.00 | 0.00 |
June | 971.92 | 297.57 | 674.36 | 4507.70 | 16.51 | 0.00 | 0.00 | 0.00 |
July | 908.67 | 263.38 | 645.28 | 5064.44 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 928.72 | 285.24 | 643.48 | 5228.86 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 872.12 | 269.07 | 603.05 | 4078.86 | 29.81 | 0.00 | 0.00 | 0.00 |
October | 791.66 | 258.41 | 533.26 | 3058.43 | 156.39 | 0.00 | 0.00 | 0.00 |
November | 665.00 | 211.53 | 453.47 | 2029.79 | 466.04 | 0.00 | 0.00 | 0.00 |
December | 538.85 | 149.04 | 389.82 | 1228.46 | 845.05 | 2.67 | 0.00 | 0.00 |
Annual Sum or Average | 796.47 | 237.82 | 558.66 | 3080.57 | 389.95 | 2.67 | 0.00 | 0.00 |
Minimum of Months | 538.85 | 149.04 | 389.82 | 1199.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 990.32 | 314.43 | 675.89 | 5228.86 | 1057.83 | 2.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1609.98 | 750.05 | 859.94 | 3557.24 | 1734.27 | 0.00 | 0.00 | 0.00 |
February | 1532.19 | 631.55 | 900.64 | 3650.03 | 1489.09 | 0.00 | 0.00 | 0.00 |
March | 1292.74 | 378.94 | 913.80 | 3566.06 | 1143.30 | 0.00 | 0.00 | 0.00 |
April | 1023.08 | 141.61 | 881.48 | 3580.60 | 707.81 | 0.00 | 0.00 | 0.00 |
May | 845.16 | 22.71 | 822.45 | 4428.02 | 165.10 | 0.00 | 0.00 | 0.00 |
June | 787.69 | 2.07 | 785.63 | 4844.48 | 22.63 | 0.00 | 0.00 | 0.00 |
July | 791.69 | 11.79 | 779.90 | 5900.63 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 940.29 | 92.56 | 847.72 | 6552.40 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1253.86 | 326.59 | 927.27 | 6072.69 | 53.46 | 0.00 | 0.00 | 0.00 |
October | 1603.95 | 655.15 | 948.80 | 5853.60 | 278.10 | 0.00 | 0.00 | 0.00 |
November | 1731.08 | 831.20 | 899.88 | 5085.10 | 799.74 | 0.00 | 0.00 | 0.00 |
December | 1593.83 | 777.65 | 816.17 | 3912.04 | 1417.23 | 1.83 | 0.00 | 0.00 |
Annual Sum or Average | 1248.71 | 383.79 | 864.92 | 4757.69 | 646.80 | 1.83 | 0.00 | 0.00 |
Minimum of Months | 787.69 | 2.07 | 779.90 | 3557.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1731.08 | 831.20 | 948.80 | 6552.40 | 1734.27 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 595.30 | 171.97 | 423.33 | 1193.37 | 1197.33 | 0.00 | 0.00 | 0.00 |
February | 679.66 | 194.87 | 484.79 | 1529.31 | 1007.61 | 0.00 | 0.00 | 0.00 |
March | 802.73 | 237.22 | 565.50 | 2109.30 | 786.86 | 0.00 | 0.00 | 0.00 |
April | 876.16 | 244.90 | 631.26 | 2816.31 | 519.48 | 0.00 | 0.00 | 0.00 |
May | 955.49 | 285.94 | 669.54 | 4027.21 | 130.39 | 0.00 | 0.00 | 0.00 |
June | 987.58 | 311.35 | 676.23 | 4513.74 | 23.40 | 0.00 | 0.00 | 0.00 |
July | 907.70 | 260.93 | 646.77 | 5007.44 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 928.28 | 281.46 | 646.82 | 5133.99 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 883.20 | 276.85 | 606.34 | 4074.15 | 41.36 | 0.00 | 0.00 | 0.00 |
October | 785.72 | 253.82 | 531.90 | 3047.26 | 201.75 | 0.00 | 0.00 | 0.00 |
November | 676.18 | 221.78 | 454.40 | 2102.95 | 540.44 | 0.00 | 0.00 | 0.00 |
December | 567.31 | 172.92 | 394.39 | 1331.75 | 966.03 | 1.50 | 0.00 | 0.00 |
Annual Sum or Average | 804.23 | 243.00 | 561.23 | 3083.27 | 448.51 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 567.31 | 171.97 | 394.39 | 1193.37 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 987.58 | 311.35 | 676.23 | 5133.99 | 1197.33 | 1.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.269006E+09 | 0.00 | 0.269006E+09 | 0.386346E+09 | 0.117392E+10 |
February | 0.278517E+09 | 0.00 | 0.278517E+09 | 0.523483E+09 | 0.892192E+09 |
March | 0.354191E+09 | 0.00 | 0.354191E+09 | 0.905900E+09 | 0.737560E+09 |
April | 0.386743E+09 | 1353735.36 | 0.385389E+09 | 0.139157E+10 | 0.406271E+09 |
May | 0.454495E+09 | 18493984.85 | 0.436001E+09 | 0.237277E+10 | 92980533.14 |
June | 0.474633E+09 | 35057811.72 | 0.439575E+09 | 0.270406E+10 | 11300602.25 |
July | 0.446744E+09 | 18161955.83 | 0.428582E+09 | 0.321350E+10 | 8802.59 |
August | 0.412644E+09 | 5231340.40 | 0.407412E+09 | 0.317266E+10 | 0.00 |
September | 0.362180E+09 | 82539.58 | 0.362097E+09 | 0.225533E+10 | 27653110.77 |
October | 0.331729E+09 | 0.00 | 0.331729E+09 | 0.159046E+10 | 0.155000E+09 |
November | 0.275596E+09 | 0.00 | 0.275596E+09 | 0.896469E+09 | 0.499037E+09 |
December | 0.251083E+09 | 0.00 | 0.251083E+09 | 0.459510E+09 | 0.989683E+09 |
Annual Sum or Average | 0.429756E+10 | 78381367.74 | 0.421918E+10 | 0.198721E+11 | 0.498560E+10 |
Minimum of Months | 0.251083E+09 | 0.00 | 0.251083E+09 | 0.386346E+09 | 0.00 |
Maximum of Months | 0.474633E+09 | 35057811.72 | 0.439575E+09 | 0.321350E+10 | 0.117392E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.269006E+09 | 0.00 | 0.269006E+09 | 0.386346E+09 | 0.117392E+10 |
February | 0.278517E+09 | 0.00 | 0.278517E+09 | 0.523483E+09 | 0.892192E+09 |
March | 0.354191E+09 | 0.00 | 0.354191E+09 | 0.905899E+09 | 0.737560E+09 |
April | 0.386743E+09 | 1353733.74 | 0.385389E+09 | 0.139157E+10 | 0.406271E+09 |
May | 0.454494E+09 | 18493962.65 | 0.436000E+09 | 0.237277E+10 | 92980401.98 |
June | 0.474632E+09 | 35057769.65 | 0.439574E+09 | 0.270405E+10 | 11300565.57 |
July | 0.446744E+09 | 18161934.04 | 0.428582E+09 | 0.321350E+10 | 8802.22 |
August | 0.412643E+09 | 5231334.12 | 0.407412E+09 | 0.317266E+10 | 0.00 |
September | 0.362180E+09 | 82539.48 | 0.362097E+09 | 0.225533E+10 | 27653054.07 |
October | 0.331729E+09 | 0.00 | 0.331729E+09 | 0.159046E+10 | 0.155000E+09 |
November | 0.275596E+09 | 0.00 | 0.275596E+09 | 0.896469E+09 | 0.499037E+09 |
December | 0.251082E+09 | 0.00 | 0.251082E+09 | 0.459509E+09 | 0.989683E+09 |
Annual Sum or Average | 0.429756E+10 | 78381273.69 | 0.421918E+10 | 0.198721E+11 | 0.498560E+10 |
Minimum of Months | 0.251082E+09 | 0.00 | 0.251082E+09 | 0.386346E+09 | 0.00 |
Maximum of Months | 0.474632E+09 | 35057769.65 | 0.439574E+09 | 0.321350E+10 | 0.117392E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.269006E+09 | 0.00 | 0.269006E+09 | 0.386346E+09 | 0.117392E+10 |
February | 0.278517E+09 | 0.00 | 0.278517E+09 | 0.523483E+09 | 0.892192E+09 |
March | 0.354191E+09 | 0.00 | 0.354191E+09 | 0.905900E+09 | 0.737560E+09 |
April | 0.386743E+09 | 1353735.36 | 0.385389E+09 | 0.139157E+10 | 0.406271E+09 |
May | 0.454495E+09 | 18493984.85 | 0.436001E+09 | 0.237277E+10 | 92980533.14 |
June | 0.474633E+09 | 35057811.72 | 0.439575E+09 | 0.270406E+10 | 11300602.25 |
July | 0.446744E+09 | 18161955.83 | 0.428582E+09 | 0.321350E+10 | 8802.59 |
August | 0.412644E+09 | 5231340.40 | 0.407412E+09 | 0.317266E+10 | 0.00 |
September | 0.362180E+09 | 82539.58 | 0.362097E+09 | 0.225533E+10 | 27653110.77 |
October | 0.331729E+09 | 0.00 | 0.331729E+09 | 0.159046E+10 | 0.155000E+09 |
November | 0.275596E+09 | 0.00 | 0.275596E+09 | 0.896469E+09 | 0.499037E+09 |
December | 0.251083E+09 | 0.00 | 0.251083E+09 | 0.459510E+09 | 0.989683E+09 |
Annual Sum or Average | 0.429756E+10 | 78381367.74 | 0.421918E+10 | 0.198721E+11 | 0.498560E+10 |
Minimum of Months | 0.251083E+09 | 0.00 | 0.251083E+09 | 0.386346E+09 | 0.00 |
Maximum of Months | 0.474633E+09 | 35057811.72 | 0.439575E+09 | 0.321350E+10 | 0.117392E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.269006E+09 | 0.00 | 0.269006E+09 | 0.386346E+09 | 0.117392E+10 |
February | 0.278517E+09 | 0.00 | 0.278517E+09 | 0.523483E+09 | 0.892192E+09 |
March | 0.354191E+09 | 0.00 | 0.354191E+09 | 0.905899E+09 | 0.737560E+09 |
April | 0.386743E+09 | 1353733.74 | 0.385389E+09 | 0.139157E+10 | 0.406271E+09 |
May | 0.454494E+09 | 18493962.65 | 0.436000E+09 | 0.237277E+10 | 92980401.98 |
June | 0.474632E+09 | 35057769.65 | 0.439574E+09 | 0.270405E+10 | 11300565.57 |
July | 0.446744E+09 | 18161934.04 | 0.428582E+09 | 0.321350E+10 | 8802.22 |
August | 0.412643E+09 | 5231334.12 | 0.407412E+09 | 0.317266E+10 | 0.00 |
September | 0.362180E+09 | 82539.48 | 0.362097E+09 | 0.225533E+10 | 27653054.07 |
October | 0.331729E+09 | 0.00 | 0.331729E+09 | 0.159046E+10 | 0.155000E+09 |
November | 0.275596E+09 | 0.00 | 0.275596E+09 | 0.896469E+09 | 0.499037E+09 |
December | 0.251082E+09 | 0.00 | 0.251082E+09 | 0.459509E+09 | 0.989683E+09 |
Annual Sum or Average | 0.429756E+10 | 78381273.69 | 0.421918E+10 | 0.198721E+11 | 0.498560E+10 |
Minimum of Months | 0.251082E+09 | 0.00 | 0.251082E+09 | 0.386346E+09 | 0.00 |
Maximum of Months | 0.474632E+09 | 35057769.65 | 0.439574E+09 | 0.321350E+10 | 0.117392E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268995E+09 | 0.00 | 0.268995E+09 | 0.386331E+09 | 0.117387E+10 |
February | 0.278506E+09 | 0.00 | 0.278506E+09 | 0.523462E+09 | 0.892156E+09 |
March | 0.354177E+09 | 0.00 | 0.354177E+09 | 0.905863E+09 | 0.737530E+09 |
April | 0.386727E+09 | 1353680.80 | 0.385374E+09 | 0.139152E+10 | 0.406255E+09 |
May | 0.454476E+09 | 18493239.46 | 0.435983E+09 | 0.237268E+10 | 92976785.62 |
June | 0.474613E+09 | 35056398.74 | 0.439557E+09 | 0.270395E+10 | 11300146.78 |
July | 0.446726E+09 | 18161223.82 | 0.428565E+09 | 0.321337E+10 | 8802.23 |
August | 0.412627E+09 | 5231129.55 | 0.407396E+09 | 0.317253E+10 | 0.00 |
September | 0.362165E+09 | 82536.26 | 0.362083E+09 | 0.225524E+10 | 27651996.22 |
October | 0.331716E+09 | 0.00 | 0.331716E+09 | 0.159040E+10 | 0.154994E+09 |
November | 0.275585E+09 | 0.00 | 0.275585E+09 | 0.896433E+09 | 0.499017E+09 |
December | 0.251072E+09 | 0.00 | 0.251072E+09 | 0.459491E+09 | 0.989643E+09 |
Annual Sum or Average | 0.429739E+10 | 78378208.62 | 0.421901E+10 | 0.198713E+11 | 0.498540E+10 |
Minimum of Months | 0.251072E+09 | 0.00 | 0.251072E+09 | 0.386331E+09 | 0.00 |
Maximum of Months | 0.474613E+09 | 35056398.74 | 0.439557E+09 | 0.321337E+10 | 0.117387E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.541572E+09 | 0.164465E+09 | 0.377107E+09 | 0.100894E+10 | 0.115844E+10 |
February | 0.532930E+09 | 0.144953E+09 | 0.387978E+09 | 0.116278E+10 | 0.876439E+09 |
March | 0.650984E+09 | 0.160532E+09 | 0.490452E+09 | 0.175126E+10 | 0.708960E+09 |
April | 0.766797E+09 | 0.223351E+09 | 0.543446E+09 | 0.257389E+10 | 0.368642E+09 |
May | 0.884163E+09 | 0.280726E+09 | 0.603437E+09 | 0.381349E+10 | 84522874.92 |
June | 0.839751E+09 | 0.257102E+09 | 0.582649E+09 | 0.401555E+10 | 5251947.83 |
July | 0.811268E+09 | 0.235151E+09 | 0.576116E+09 | 0.463680E+10 | 0.00 |
August | 0.829170E+09 | 0.254667E+09 | 0.574503E+09 | 0.478336E+10 | 0.00 |
September | 0.753518E+09 | 0.232481E+09 | 0.521037E+09 | 0.361592E+10 | 20920324.13 |
October | 0.706803E+09 | 0.230708E+09 | 0.476095E+09 | 0.280200E+10 | 0.124352E+09 |
November | 0.574568E+09 | 0.182762E+09 | 0.391806E+09 | 0.176617E+10 | 0.463276E+09 |
December | 0.481091E+09 | 0.133061E+09 | 0.348031E+09 | 0.104271E+10 | 0.937137E+09 |
Annual Sum or Average | 0.837261E+10 | 0.249996E+10 | 0.587266E+10 | 0.329729E+11 | 0.474794E+10 |
Minimum of Months | 0.481091E+09 | 0.133061E+09 | 0.348031E+09 | 0.100894E+10 | 0.00 |
Maximum of Months | 0.884163E+09 | 0.280726E+09 | 0.603437E+09 | 0.478336E+10 | 0.115844E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.541572E+09 | 0.164465E+09 | 0.377107E+09 | 0.100894E+10 | 0.115844E+10 |
February | 0.532930E+09 | 0.144953E+09 | 0.387978E+09 | 0.116278E+10 | 0.876439E+09 |
March | 0.650984E+09 | 0.160532E+09 | 0.490452E+09 | 0.175126E+10 | 0.708960E+09 |
April | 0.766797E+09 | 0.223351E+09 | 0.543446E+09 | 0.257389E+10 | 0.368642E+09 |
May | 0.884163E+09 | 0.280726E+09 | 0.603437E+09 | 0.381349E+10 | 84522874.92 |
June | 0.839751E+09 | 0.257102E+09 | 0.582649E+09 | 0.401555E+10 | 5251947.83 |
July | 0.811268E+09 | 0.235151E+09 | 0.576116E+09 | 0.463680E+10 | 0.00 |
August | 0.829170E+09 | 0.254667E+09 | 0.574503E+09 | 0.478336E+10 | 0.00 |
September | 0.753518E+09 | 0.232481E+09 | 0.521037E+09 | 0.361592E+10 | 20920324.13 |
October | 0.706803E+09 | 0.230708E+09 | 0.476095E+09 | 0.280200E+10 | 0.124352E+09 |
November | 0.574568E+09 | 0.182762E+09 | 0.391806E+09 | 0.176617E+10 | 0.463276E+09 |
December | 0.481091E+09 | 0.133061E+09 | 0.348031E+09 | 0.104271E+10 | 0.937137E+09 |
Annual Sum or Average | 0.837261E+10 | 0.249996E+10 | 0.587266E+10 | 0.329729E+11 | 0.474794E+10 |
Minimum of Months | 0.481091E+09 | 0.133061E+09 | 0.348031E+09 | 0.100894E+10 | 0.00 |
Maximum of Months | 0.884163E+09 | 0.280726E+09 | 0.603437E+09 | 0.478336E+10 | 0.115844E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.541562E+09 | 0.164462E+09 | 0.377100E+09 | 0.100892E+10 | 0.115842E+10 |
February | 0.532921E+09 | 0.144950E+09 | 0.387970E+09 | 0.116276E+10 | 0.876423E+09 |
March | 0.650972E+09 | 0.160529E+09 | 0.490443E+09 | 0.175123E+10 | 0.708947E+09 |
April | 0.766783E+09 | 0.223347E+09 | 0.543436E+09 | 0.257385E+10 | 0.368635E+09 |
May | 0.884147E+09 | 0.280721E+09 | 0.603426E+09 | 0.381342E+10 | 84521330.50 |
June | 0.839736E+09 | 0.257098E+09 | 0.582638E+09 | 0.401548E+10 | 5251851.87 |
July | 0.811253E+09 | 0.235147E+09 | 0.576106E+09 | 0.463671E+10 | 0.00 |
August | 0.829155E+09 | 0.254662E+09 | 0.574492E+09 | 0.478327E+10 | 0.00 |
September | 0.753504E+09 | 0.232476E+09 | 0.521028E+09 | 0.361585E+10 | 20919941.87 |
October | 0.706790E+09 | 0.230704E+09 | 0.476086E+09 | 0.280195E+10 | 0.124349E+09 |
November | 0.574558E+09 | 0.182759E+09 | 0.391799E+09 | 0.176614E+10 | 0.463267E+09 |
December | 0.481083E+09 | 0.133058E+09 | 0.348024E+09 | 0.104269E+10 | 0.937120E+09 |
Annual Sum or Average | 0.837246E+10 | 0.249991E+10 | 0.587255E+10 | 0.329723E+11 | 0.474785E+10 |
Minimum of Months | 0.481083E+09 | 0.133058E+09 | 0.348024E+09 | 0.100892E+10 | 0.00 |
Maximum of Months | 0.884147E+09 | 0.280721E+09 | 0.603426E+09 | 0.478327E+10 | 0.115842E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.862447E+09 | 0.401791E+09 | 0.460656E+09 | 0.194257E+10 | 0.108027E+10 |
February | 0.741344E+09 | 0.305575E+09 | 0.435769E+09 | 0.180906E+10 | 0.844508E+09 |
March | 0.692505E+09 | 0.202995E+09 | 0.489510E+09 | 0.194789E+10 | 0.717083E+09 |
April | 0.530373E+09 | 73410911.26 | 0.456962E+09 | 0.187743E+10 | 0.397176E+09 |
May | 0.452739E+09 | 12165572.84 | 0.440573E+09 | 0.238600E+10 | 90617628.01 |
June | 0.408345E+09 | 1070895.52 | 0.407274E+09 | 0.251606E+10 | 8138623.09 |
July | 0.424097E+09 | 6317580.66 | 0.417780E+09 | 0.315303E+10 | 0.00 |
August | 0.503700E+09 | 49585404.19 | 0.454115E+09 | 0.350277E+10 | 0.00 |
September | 0.650011E+09 | 0.169306E+09 | 0.480705E+09 | 0.319659E+10 | 26345426.77 |
October | 0.859213E+09 | 0.350952E+09 | 0.508261E+09 | 0.320117E+10 | 0.147953E+09 |
November | 0.897402E+09 | 0.430901E+09 | 0.466501E+09 | 0.268831E+10 | 0.480094E+09 |
December | 0.853791E+09 | 0.416579E+09 | 0.437212E+09 | 0.211460E+10 | 0.917358E+09 |
Annual Sum or Average | 0.787597E+10 | 0.242065E+10 | 0.545532E+10 | 0.303355E+11 | 0.470954E+10 |
Minimum of Months | 0.408345E+09 | 1070895.52 | 0.407274E+09 | 0.180906E+10 | 0.00 |
Maximum of Months | 0.897402E+09 | 0.430901E+09 | 0.508261E+09 | 0.350277E+10 | 0.108027E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.862446E+09 | 0.401790E+09 | 0.460655E+09 | 0.194257E+10 | 0.108026E+10 |
February | 0.741343E+09 | 0.305574E+09 | 0.435769E+09 | 0.180906E+10 | 0.844508E+09 |
March | 0.692504E+09 | 0.202995E+09 | 0.489509E+09 | 0.194789E+10 | 0.717082E+09 |
April | 0.530373E+09 | 73410823.17 | 0.456962E+09 | 0.187742E+10 | 0.397176E+09 |
May | 0.452738E+09 | 12165558.24 | 0.440573E+09 | 0.238600E+10 | 90617500.72 |
June | 0.408345E+09 | 1070894.24 | 0.407274E+09 | 0.251606E+10 | 8138596.16 |
July | 0.424097E+09 | 6317573.08 | 0.417780E+09 | 0.315303E+10 | 0.00 |
August | 0.503700E+09 | 49585344.69 | 0.454114E+09 | 0.350277E+10 | 0.00 |
September | 0.650010E+09 | 0.169306E+09 | 0.480705E+09 | 0.319659E+10 | 26345373.26 |
October | 0.859212E+09 | 0.350952E+09 | 0.508260E+09 | 0.320116E+10 | 0.147953E+09 |
November | 0.897401E+09 | 0.430900E+09 | 0.466501E+09 | 0.268831E+10 | 0.480093E+09 |
December | 0.853790E+09 | 0.416578E+09 | 0.437212E+09 | 0.211460E+10 | 0.917358E+09 |
Annual Sum or Average | 0.787596E+10 | 0.242065E+10 | 0.545531E+10 | 0.303355E+11 | 0.470954E+10 |
Minimum of Months | 0.408345E+09 | 1070894.24 | 0.407274E+09 | 0.180906E+10 | 0.00 |
Maximum of Months | 0.897401E+09 | 0.430900E+09 | 0.508260E+09 | 0.350277E+10 | 0.108026E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.862447E+09 | 0.401791E+09 | 0.460656E+09 | 0.194257E+10 | 0.108027E+10 |
February | 0.741344E+09 | 0.305575E+09 | 0.435769E+09 | 0.180906E+10 | 0.844508E+09 |
March | 0.692505E+09 | 0.202995E+09 | 0.489510E+09 | 0.194789E+10 | 0.717083E+09 |
April | 0.530373E+09 | 73410911.26 | 0.456962E+09 | 0.187743E+10 | 0.397176E+09 |
May | 0.452739E+09 | 12165572.84 | 0.440573E+09 | 0.238600E+10 | 90617628.01 |
June | 0.408345E+09 | 1070895.52 | 0.407274E+09 | 0.251606E+10 | 8138623.09 |
July | 0.424097E+09 | 6317580.66 | 0.417780E+09 | 0.315303E+10 | 0.00 |
August | 0.503700E+09 | 49585404.19 | 0.454115E+09 | 0.350277E+10 | 0.00 |
September | 0.650011E+09 | 0.169306E+09 | 0.480705E+09 | 0.319659E+10 | 26345426.77 |
October | 0.859213E+09 | 0.350952E+09 | 0.508261E+09 | 0.320117E+10 | 0.147953E+09 |
November | 0.897402E+09 | 0.430901E+09 | 0.466501E+09 | 0.268831E+10 | 0.480094E+09 |
December | 0.853791E+09 | 0.416579E+09 | 0.437212E+09 | 0.211460E+10 | 0.917358E+09 |
Annual Sum or Average | 0.787597E+10 | 0.242065E+10 | 0.545532E+10 | 0.303355E+11 | 0.470954E+10 |
Minimum of Months | 0.408345E+09 | 1070895.52 | 0.407274E+09 | 0.180906E+10 | 0.00 |
Maximum of Months | 0.897402E+09 | 0.430901E+09 | 0.508261E+09 | 0.350277E+10 | 0.108027E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.862446E+09 | 0.401790E+09 | 0.460655E+09 | 0.194257E+10 | 0.108026E+10 |
February | 0.741343E+09 | 0.305574E+09 | 0.435769E+09 | 0.180906E+10 | 0.844508E+09 |
March | 0.692504E+09 | 0.202995E+09 | 0.489509E+09 | 0.194789E+10 | 0.717082E+09 |
April | 0.530373E+09 | 73410823.17 | 0.456962E+09 | 0.187742E+10 | 0.397176E+09 |
May | 0.452738E+09 | 12165558.24 | 0.440573E+09 | 0.238600E+10 | 90617500.72 |
June | 0.408345E+09 | 1070894.24 | 0.407274E+09 | 0.251606E+10 | 8138596.16 |
July | 0.424097E+09 | 6317573.08 | 0.417780E+09 | 0.315303E+10 | 0.00 |
August | 0.503700E+09 | 49585344.69 | 0.454114E+09 | 0.350277E+10 | 0.00 |
September | 0.650010E+09 | 0.169306E+09 | 0.480705E+09 | 0.319659E+10 | 26345373.26 |
October | 0.859212E+09 | 0.350952E+09 | 0.508260E+09 | 0.320116E+10 | 0.147953E+09 |
November | 0.897401E+09 | 0.430900E+09 | 0.466501E+09 | 0.268831E+10 | 0.480093E+09 |
December | 0.853790E+09 | 0.416578E+09 | 0.437212E+09 | 0.211460E+10 | 0.917358E+09 |
Annual Sum or Average | 0.787596E+10 | 0.242065E+10 | 0.545531E+10 | 0.303355E+11 | 0.470954E+10 |
Minimum of Months | 0.408345E+09 | 1070894.24 | 0.407274E+09 | 0.180906E+10 | 0.00 |
Maximum of Months | 0.897401E+09 | 0.430900E+09 | 0.508260E+09 | 0.350277E+10 | 0.108026E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.862412E+09 | 0.401775E+09 | 0.460637E+09 | 0.194250E+10 | 0.108022E+10 |
February | 0.741314E+09 | 0.305562E+09 | 0.435752E+09 | 0.180899E+10 | 0.844474E+09 |
March | 0.692477E+09 | 0.202987E+09 | 0.489490E+09 | 0.194781E+10 | 0.717054E+09 |
April | 0.530352E+09 | 73407952.47 | 0.456944E+09 | 0.187735E+10 | 0.397160E+09 |
May | 0.452721E+09 | 12165082.51 | 0.440555E+09 | 0.238591E+10 | 90613975.72 |
June | 0.408329E+09 | 1070852.36 | 0.407258E+09 | 0.251596E+10 | 8138295.06 |
July | 0.424080E+09 | 6317326.03 | 0.417763E+09 | 0.315291E+10 | 0.00 |
August | 0.503680E+09 | 49583405.68 | 0.454096E+09 | 0.350263E+10 | 0.00 |
September | 0.649985E+09 | 0.169299E+09 | 0.480686E+09 | 0.319646E+10 | 26344364.93 |
October | 0.859179E+09 | 0.350938E+09 | 0.508240E+09 | 0.320104E+10 | 0.147947E+09 |
November | 0.897366E+09 | 0.430883E+09 | 0.466482E+09 | 0.268820E+10 | 0.480074E+09 |
December | 0.853756E+09 | 0.416562E+09 | 0.437194E+09 | 0.211452E+10 | 0.917321E+09 |
Annual Sum or Average | 0.787565E+10 | 0.242055E+10 | 0.545510E+10 | 0.303343E+11 | 0.470935E+10 |
Minimum of Months | 0.408329E+09 | 1070852.36 | 0.407258E+09 | 0.180899E+10 | 0.00 |
Maximum of Months | 0.897366E+09 | 0.430883E+09 | 0.508240E+09 | 0.350263E+10 | 0.108022E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.531493E+09 | 0.153537E+09 | 0.377956E+09 | 0.101974E+10 | 0.138257E+10 |
February | 0.548084E+09 | 0.157143E+09 | 0.390941E+09 | 0.118480E+10 | 0.111808E+10 |
March | 0.716681E+09 | 0.211796E+09 | 0.504885E+09 | 0.183306E+10 | 0.100477E+10 |
April | 0.757009E+09 | 0.211597E+09 | 0.545412E+09 | 0.237876E+10 | 0.626341E+09 |
May | 0.853069E+09 | 0.255294E+09 | 0.597775E+09 | 0.361611E+10 | 0.140561E+09 |
June | 0.853280E+09 | 0.269012E+09 | 0.584268E+09 | 0.386883E+10 | 23838253.43 |
July | 0.810403E+09 | 0.232958E+09 | 0.577445E+09 | 0.435469E+10 | 390368.16 |
August | 0.828775E+09 | 0.251286E+09 | 0.577490E+09 | 0.442481E+10 | 204568.71 |
September | 0.763089E+09 | 0.239205E+09 | 0.523884E+09 | 0.351155E+10 | 42787721.47 |
October | 0.701499E+09 | 0.226613E+09 | 0.474885E+09 | 0.267165E+10 | 0.241828E+09 |
November | 0.584227E+09 | 0.191623E+09 | 0.392604E+09 | 0.172784E+10 | 0.713239E+09 |
December | 0.506502E+09 | 0.154385E+09 | 0.352117E+09 | 0.105989E+10 | 0.134999E+10 |
Annual Sum or Average | 0.845411E+10 | 0.255445E+10 | 0.589966E+10 | 0.316517E+11 | 0.664461E+10 |
Minimum of Months | 0.506502E+09 | 0.153537E+09 | 0.352117E+09 | 0.101974E+10 | 204568.71 |
Maximum of Months | 0.853280E+09 | 0.269012E+09 | 0.597775E+09 | 0.442481E+10 | 0.138257E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.531493E+09 | 0.153537E+09 | 0.377956E+09 | 0.101974E+10 | 0.138257E+10 |
February | 0.548084E+09 | 0.157143E+09 | 0.390941E+09 | 0.118480E+10 | 0.111808E+10 |
March | 0.716681E+09 | 0.211796E+09 | 0.504885E+09 | 0.183306E+10 | 0.100477E+10 |
April | 0.757009E+09 | 0.211597E+09 | 0.545412E+09 | 0.237876E+10 | 0.626341E+09 |
May | 0.853069E+09 | 0.255294E+09 | 0.597775E+09 | 0.361611E+10 | 0.140561E+09 |
June | 0.853280E+09 | 0.269012E+09 | 0.584268E+09 | 0.386883E+10 | 23838253.43 |
July | 0.810403E+09 | 0.232958E+09 | 0.577445E+09 | 0.435469E+10 | 390368.16 |
August | 0.828775E+09 | 0.251286E+09 | 0.577490E+09 | 0.442481E+10 | 204568.71 |
September | 0.763089E+09 | 0.239205E+09 | 0.523884E+09 | 0.351155E+10 | 42787721.47 |
October | 0.701499E+09 | 0.226613E+09 | 0.474885E+09 | 0.267165E+10 | 0.241828E+09 |
November | 0.584227E+09 | 0.191623E+09 | 0.392604E+09 | 0.172784E+10 | 0.713239E+09 |
December | 0.506502E+09 | 0.154385E+09 | 0.352117E+09 | 0.105989E+10 | 0.134999E+10 |
Annual Sum or Average | 0.845411E+10 | 0.255445E+10 | 0.589966E+10 | 0.316517E+11 | 0.664461E+10 |
Minimum of Months | 0.506502E+09 | 0.153537E+09 | 0.352117E+09 | 0.101974E+10 | 204568.71 |
Maximum of Months | 0.853280E+09 | 0.269012E+09 | 0.597775E+09 | 0.442481E+10 | 0.138257E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.531484E+09 | 0.153534E+09 | 0.377949E+09 | 0.101972E+10 | 0.138254E+10 |
February | 0.548074E+09 | 0.157140E+09 | 0.390934E+09 | 0.118477E+10 | 0.111806E+10 |
March | 0.716668E+09 | 0.211792E+09 | 0.504876E+09 | 0.183303E+10 | 0.100475E+10 |
April | 0.756995E+09 | 0.211593E+09 | 0.545402E+09 | 0.237871E+10 | 0.626330E+09 |
May | 0.853054E+09 | 0.255290E+09 | 0.597764E+09 | 0.361604E+10 | 0.140559E+09 |
June | 0.853264E+09 | 0.269007E+09 | 0.584258E+09 | 0.386876E+10 | 23837817.85 |
July | 0.810388E+09 | 0.232954E+09 | 0.577434E+09 | 0.435461E+10 | 390361.03 |
August | 0.828760E+09 | 0.251281E+09 | 0.577479E+09 | 0.442473E+10 | 204564.98 |
September | 0.763075E+09 | 0.239200E+09 | 0.523874E+09 | 0.351149E+10 | 42786939.64 |
October | 0.701486E+09 | 0.226609E+09 | 0.474877E+09 | 0.267160E+10 | 0.241824E+09 |
November | 0.584216E+09 | 0.191619E+09 | 0.392597E+09 | 0.172780E+10 | 0.713226E+09 |
December | 0.506493E+09 | 0.154382E+09 | 0.352111E+09 | 0.105987E+10 | 0.134997E+10 |
Annual Sum or Average | 0.845396E+10 | 0.255440E+10 | 0.589956E+10 | 0.316511E+11 | 0.664448E+10 |
Minimum of Months | 0.506493E+09 | 0.153534E+09 | 0.352111E+09 | 0.101972E+10 | 204564.98 |
Maximum of Months | 0.853264E+09 | 0.269007E+09 | 0.597764E+09 | 0.442473E+10 | 0.138254E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134502E+10 | 0.00 | 0.134502E+10 | 0.215664E+10 | 0.509306E+10 |
February | 0.139257E+10 | 0.00 | 0.139257E+10 | 0.280125E+10 | 0.381470E+10 |
March | 0.177093E+10 | 0.00 | 0.177093E+10 | 0.469541E+10 | 0.315530E+10 |
April | 0.193369E+10 | 6768594.96 | 0.192692E+10 | 0.711902E+10 | 0.189142E+10 |
May | 0.227245E+10 | 92468806.09 | 0.217998E+10 | 0.119672E+11 | 0.470469E+09 |
June | 0.237313E+10 | 0.175287E+09 | 0.219785E+10 | 0.136202E+11 | 82639489.54 |
July | 0.223370E+10 | 90808681.10 | 0.214289E+10 | 0.163388E+11 | 26725.57 |
August | 0.206319E+10 | 26156385.70 | 0.203704E+10 | 0.161868E+11 | 62412.75 |
September | 0.181088E+10 | 412692.92 | 0.181047E+10 | 0.114492E+11 | 0.146727E+09 |
October | 0.165863E+10 | 0.00 | 0.165863E+10 | 0.815424E+10 | 0.758244E+09 |
November | 0.137796E+10 | 0.00 | 0.137796E+10 | 0.472826E+10 | 0.212377E+10 |
December | 0.125540E+10 | 0.00 | 0.125540E+10 | 0.260081E+10 | 0.404146E+10 |
Annual Sum or Average | 0.214875E+11 | 0.391902E+09 | 0.210956E+11 | 0.101818E+12 | 0.215779E+11 |
Minimum of Months | 0.125540E+10 | 0.00 | 0.125540E+10 | 0.215664E+10 | 26725.57 |
Maximum of Months | 0.237313E+10 | 0.175287E+09 | 0.219785E+10 | 0.163388E+11 | 0.509306E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.162470E+10 | 0.493389E+09 | 0.113131E+10 | 0.312490E+10 | 0.311965E+10 |
February | 0.159878E+10 | 0.434854E+09 | 0.116392E+10 | 0.351147E+10 | 0.235546E+10 |
March | 0.195293E+10 | 0.481592E+09 | 0.147134E+10 | 0.521241E+10 | 0.195885E+10 |
April | 0.230037E+10 | 0.670045E+09 | 0.163032E+10 | 0.758337E+10 | 0.118695E+10 |
May | 0.265246E+10 | 0.842168E+09 | 0.181029E+10 | 0.112734E+11 | 0.281008E+09 |
June | 0.251923E+10 | 0.771299E+09 | 0.174793E+10 | 0.118260E+11 | 40351693.35 |
July | 0.243378E+10 | 0.705447E+09 | 0.172833E+10 | 0.137434E+11 | 0.00 |
August | 0.248748E+10 | 0.763994E+09 | 0.172349E+10 | 0.141513E+11 | 0.00 |
September | 0.226053E+10 | 0.697435E+09 | 0.156310E+10 | 0.106900E+11 | 77306392.88 |
October | 0.212039E+10 | 0.692116E+09 | 0.142827E+10 | 0.826120E+10 | 0.433578E+09 |
November | 0.172369E+10 | 0.548281E+09 | 0.117541E+10 | 0.526345E+10 | 0.130740E+10 |
December | 0.144326E+10 | 0.399178E+09 | 0.104408E+10 | 0.322897E+10 | 0.248795E+10 |
Annual Sum or Average | 0.251176E+11 | 0.749980E+10 | 0.176178E+11 | 0.978698E+11 | 0.132485E+11 |
Minimum of Months | 0.144326E+10 | 0.399178E+09 | 0.104408E+10 | 0.312490E+10 | 0.00 |
Maximum of Months | 0.265246E+10 | 0.842168E+09 | 0.181029E+10 | 0.141513E+11 | 0.311965E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.431218E+10 | 0.200893E+10 | 0.230325E+10 | 0.946814E+10 | 0.515900E+10 |
February | 0.370667E+10 | 0.152785E+10 | 0.217882E+10 | 0.885094E+10 | 0.394428E+10 |
March | 0.346248E+10 | 0.101496E+10 | 0.244752E+10 | 0.962526E+10 | 0.329954E+10 |
April | 0.265183E+10 | 0.367050E+09 | 0.228478E+10 | 0.940167E+10 | 0.193452E+10 |
May | 0.226367E+10 | 60827128.67 | 0.220284E+10 | 0.120296E+11 | 0.454001E+09 |
June | 0.204170E+10 | 5354412.88 | 0.203635E+10 | 0.127323E+11 | 58682672.02 |
July | 0.212046E+10 | 31587521.34 | 0.208887E+10 | 0.160211E+11 | 0.00 |
August | 0.251847E+10 | 0.247924E+09 | 0.227055E+10 | 0.177348E+11 | 0.00 |
September | 0.325002E+10 | 0.846520E+09 | 0.240350E+10 | 0.159226E+11 | 0.143945E+09 |
October | 0.429601E+10 | 0.175474E+10 | 0.254127E+10 | 0.158296E+11 | 0.787333E+09 |
November | 0.448696E+10 | 0.215448E+10 | 0.233248E+10 | 0.132472E+11 | 0.226536E+10 |
December | 0.426890E+10 | 0.208287E+10 | 0.218603E+10 | 0.104426E+11 | 0.420681E+10 |
Annual Sum or Average | 0.393794E+11 | 0.121031E+11 | 0.272763E+11 | 0.151306E+12 | 0.222535E+11 |
Minimum of Months | 0.204170E+10 | 5354412.88 | 0.203635E+10 | 0.885094E+10 | 0.00 |
Maximum of Months | 0.448696E+10 | 0.215448E+10 | 0.254127E+10 | 0.177348E+11 | 0.515900E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.159446E+10 | 0.460607E+09 | 0.113386E+10 | 0.320121E+10 | 0.350660E+10 |
February | 0.164424E+10 | 0.471425E+09 | 0.117281E+10 | 0.373772E+10 | 0.262825E+10 |
March | 0.215002E+10 | 0.635382E+09 | 0.151464E+10 | 0.572319E+10 | 0.224546E+10 |
April | 0.227100E+10 | 0.634784E+09 | 0.163622E+10 | 0.741284E+10 | 0.141061E+10 |
May | 0.255918E+10 | 0.765875E+09 | 0.179331E+10 | 0.109242E+11 | 0.361806E+09 |
June | 0.255981E+10 | 0.807027E+09 | 0.175279E+10 | 0.118389E+11 | 60593800.47 |
July | 0.243118E+10 | 0.698867E+09 | 0.173232E+10 | 0.135646E+11 | 0.00 |
August | 0.248630E+10 | 0.753850E+09 | 0.173245E+10 | 0.138889E+11 | 233531.11 |
September | 0.228924E+10 | 0.717607E+09 | 0.157163E+10 | 0.106691E+11 | 0.110558E+09 |
October | 0.210447E+10 | 0.679833E+09 | 0.142464E+10 | 0.823710E+10 | 0.567381E+09 |
November | 0.175266E+10 | 0.574862E+09 | 0.117780E+10 | 0.548471E+10 | 0.151484E+10 |
December | 0.151949E+10 | 0.463150E+09 | 0.105634E+10 | 0.356947E+10 | 0.282662E+10 |
Annual Sum or Average | 0.253621E+11 | 0.766327E+10 | 0.176988E+11 | 0.982520E+11 | 0.152330E+11 |
Minimum of Months | 0.151949E+10 | 0.460607E+09 | 0.105634E+10 | 0.320121E+10 | 0.00 |
Maximum of Months | 0.255981E+10 | 0.807027E+09 | 0.179331E+10 | 0.138889E+11 | 0.350660E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134502E+10 | 0.00 | 0.134502E+10 | 0.228852E+10 | 0.452270E+10 |
February | 0.139257E+10 | 0.00 | 0.139257E+10 | 0.285856E+10 | 0.344623E+10 |
March | 0.177093E+10 | 0.00 | 0.177093E+10 | 0.468512E+10 | 0.290354E+10 |
April | 0.193369E+10 | 6768594.96 | 0.192692E+10 | 0.702282E+10 | 0.179176E+10 |
May | 0.227245E+10 | 92468806.09 | 0.217998E+10 | 0.117938E+11 | 0.462584E+09 |
June | 0.237313E+10 | 0.175287E+09 | 0.219785E+10 | 0.134332E+11 | 83577475.04 |
July | 0.223370E+10 | 90808681.10 | 0.214289E+10 | 0.161254E+11 | 65867.56 |
August | 0.206319E+10 | 26156385.70 | 0.203704E+10 | 0.160097E+11 | 876.78 |
September | 0.181088E+10 | 412692.92 | 0.181047E+10 | 0.113144E+11 | 0.141188E+09 |
October | 0.165863E+10 | 0.00 | 0.165863E+10 | 0.808696E+10 | 0.710679E+09 |
November | 0.137796E+10 | 0.00 | 0.137796E+10 | 0.476187E+10 | 0.190811E+10 |
December | 0.125540E+10 | 0.00 | 0.125540E+10 | 0.271884E+10 | 0.357443E+10 |
Annual Sum or Average | 0.214875E+11 | 0.391902E+09 | 0.210956E+11 | 0.101099E+12 | 0.195449E+11 |
Minimum of Months | 0.125540E+10 | 0.00 | 0.125540E+10 | 0.228852E+10 | 876.78 |
Maximum of Months | 0.237313E+10 | 0.175287E+09 | 0.219785E+10 | 0.161254E+11 | 0.452270E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.162470E+10 | 0.493389E+09 | 0.113131E+10 | 0.321204E+10 | 0.283331E+10 |
February | 0.159878E+10 | 0.434854E+09 | 0.116392E+10 | 0.352944E+10 | 0.218150E+10 |
March | 0.195293E+10 | 0.481592E+09 | 0.147134E+10 | 0.518657E+10 | 0.184369E+10 |
April | 0.230037E+10 | 0.670045E+09 | 0.163032E+10 | 0.750815E+10 | 0.114748E+10 |
May | 0.265246E+10 | 0.842168E+09 | 0.181029E+10 | 0.111436E+11 | 0.281063E+09 |
June | 0.251923E+10 | 0.771299E+09 | 0.174793E+10 | 0.116840E+11 | 42781352.23 |
July | 0.243378E+10 | 0.705447E+09 | 0.172833E+10 | 0.135646E+11 | 17299.40 |
August | 0.248748E+10 | 0.763994E+09 | 0.172349E+10 | 0.140050E+11 | 0.00 |
September | 0.226053E+10 | 0.697435E+09 | 0.156310E+10 | 0.105724E+11 | 77272609.65 |
October | 0.212039E+10 | 0.692116E+09 | 0.142827E+10 | 0.819170E+10 | 0.418870E+09 |
November | 0.172369E+10 | 0.548281E+09 | 0.117541E+10 | 0.526121E+10 | 0.120799E+10 |
December | 0.144326E+10 | 0.399178E+09 | 0.104408E+10 | 0.329030E+10 | 0.226337E+10 |
Annual Sum or Average | 0.251176E+11 | 0.749980E+10 | 0.176178E+11 | 0.971490E+11 | 0.122973E+11 |
Minimum of Months | 0.144326E+10 | 0.399178E+09 | 0.104408E+10 | 0.321204E+10 | 0.00 |
Maximum of Months | 0.265246E+10 | 0.842168E+09 | 0.181029E+10 | 0.140050E+11 | 0.283331E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.431218E+10 | 0.200893E+10 | 0.230325E+10 | 0.952771E+10 | 0.464507E+10 |
February | 0.370667E+10 | 0.152785E+10 | 0.217882E+10 | 0.883016E+10 | 0.360239E+10 |
March | 0.346248E+10 | 0.101496E+10 | 0.244752E+10 | 0.955134E+10 | 0.306222E+10 |
April | 0.265183E+10 | 0.367050E+09 | 0.228478E+10 | 0.928091E+10 | 0.183464E+10 |
May | 0.226367E+10 | 60827128.67 | 0.220284E+10 | 0.118600E+11 | 0.442211E+09 |
June | 0.204170E+10 | 5354412.88 | 0.203635E+10 | 0.125569E+11 | 58658036.10 |
July | 0.212046E+10 | 31587521.34 | 0.208887E+10 | 0.158042E+11 | 0.00 |
August | 0.251847E+10 | 0.247924E+09 | 0.227055E+10 | 0.175499E+11 | 0.00 |
September | 0.325002E+10 | 0.846520E+09 | 0.240350E+10 | 0.157404E+11 | 0.138556E+09 |
October | 0.429601E+10 | 0.175474E+10 | 0.254127E+10 | 0.156783E+11 | 0.744856E+09 |
November | 0.448696E+10 | 0.215448E+10 | 0.233248E+10 | 0.131806E+11 | 0.207292E+10 |
December | 0.426890E+10 | 0.208287E+10 | 0.218603E+10 | 0.104780E+11 | 0.379592E+10 |
Annual Sum or Average | 0.393794E+11 | 0.121031E+11 | 0.272763E+11 | 0.150038E+12 | 0.203974E+11 |
Minimum of Months | 0.204170E+10 | 5354412.88 | 0.203635E+10 | 0.883016E+10 | 0.00 |
Maximum of Months | 0.448696E+10 | 0.215448E+10 | 0.254127E+10 | 0.175499E+11 | 0.464507E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.159446E+10 | 0.460607E+09 | 0.113386E+10 | 0.319632E+10 | 0.320693E+10 |
February | 0.164424E+10 | 0.471425E+09 | 0.117281E+10 | 0.369970E+10 | 0.243760E+10 |
March | 0.215002E+10 | 0.635382E+09 | 0.151464E+10 | 0.564956E+10 | 0.210753E+10 |
April | 0.227100E+10 | 0.634784E+09 | 0.163622E+10 | 0.729988E+10 | 0.134649E+10 |
May | 0.255918E+10 | 0.765875E+09 | 0.179331E+10 | 0.107865E+11 | 0.349244E+09 |
June | 0.255981E+10 | 0.807027E+09 | 0.175279E+10 | 0.116996E+11 | 60652294.16 |
July | 0.243118E+10 | 0.698867E+09 | 0.173232E+10 | 0.134119E+11 | 22882.99 |
August | 0.248630E+10 | 0.753850E+09 | 0.173245E+10 | 0.137509E+11 | 90755.46 |
September | 0.228924E+10 | 0.717607E+09 | 0.157163E+10 | 0.105602E+11 | 0.107201E+09 |
October | 0.210447E+10 | 0.679833E+09 | 0.142464E+10 | 0.816179E+10 | 0.540366E+09 |
November | 0.175266E+10 | 0.574862E+09 | 0.117780E+10 | 0.545085E+10 | 0.140082E+10 |
December | 0.151949E+10 | 0.463150E+09 | 0.105634E+10 | 0.356696E+10 | 0.258741E+10 |
Annual Sum or Average | 0.253621E+11 | 0.766327E+10 | 0.176988E+11 | 0.972341E+11 | 0.141444E+11 |
Minimum of Months | 0.151949E+10 | 0.460607E+09 | 0.105634E+10 | 0.319632E+10 | 22882.99 |
Maximum of Months | 0.255981E+10 | 0.807027E+09 | 0.179331E+10 | 0.137509E+11 | 0.320693E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 721.22 | 2191.44 | 502.17 | 0.00 | 502.17 | 0.00 | 0.00 |
February | 1081.93 | 1843.97 | 575.63 | 0.00 | 575.63 | 0.00 | 0.00 |
March | 1691.11 | 1376.86 | 661.19 | 0.00 | 661.19 | 0.00 | 0.00 |
April | 2684.34 | 783.70 | 746.03 | 2.61 | 743.41 | 0.00 | 0.00 |
May | 4429.42 | 173.57 | 848.44 | 34.52 | 813.91 | 0.00 | 0.00 |
June | 5216.11 | 21.80 | 915.56 | 67.63 | 847.94 | 0.00 | 0.00 |
July | 5998.87 | 0.02 | 833.97 | 33.90 | 800.07 | 0.00 | 0.00 |
August | 5922.63 | 0.00 | 770.31 | 9.77 | 760.55 | 0.00 | 0.00 |
September | 4350.52 | 53.34 | 698.64 | 0.16 | 698.48 | 0.00 | 0.00 |
October | 2969.03 | 289.35 | 619.26 | 0.00 | 619.26 | 0.00 | 0.00 |
November | 1729.29 | 962.64 | 531.62 | 0.00 | 531.62 | 0.00 | 0.00 |
December | 857.80 | 1847.51 | 468.71 | 0.00 | 468.71 | 0.00 | 0.00 |
Annual Sum or Average | 3150.67 | 790.46 | 681.37 | 12.43 | 668.94 | 0.00 | 0.00 |
Minimum of Months | 721.22 | 0.00 | 468.71 | 0.00 | 468.71 | 0.00 | 0.00 |
Maximum of Months | 5998.87 | 2191.44 | 915.56 | 67.63 | 847.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1130.08 | 1297.53 | 606.60 | 184.21 | 422.38 | 0.00 | 0.00 |
February | 1441.94 | 1086.85 | 660.87 | 179.75 | 481.12 | 0.00 | 0.00 |
March | 1961.53 | 794.08 | 729.14 | 179.81 | 549.34 | 0.00 | 0.00 |
April | 2979.03 | 426.67 | 887.49 | 258.51 | 628.98 | 0.00 | 0.00 |
May | 4271.35 | 94.67 | 990.32 | 314.43 | 675.89 | 0.00 | 0.00 |
June | 4647.60 | 6.08 | 971.93 | 297.57 | 674.36 | 0.00 | 0.00 |
July | 5193.51 | 0.00 | 908.67 | 263.38 | 645.29 | 0.00 | 0.00 |
August | 5357.67 | 0.00 | 928.72 | 285.24 | 643.48 | 0.00 | 0.00 |
September | 4185.07 | 24.21 | 872.12 | 269.07 | 603.05 | 0.00 | 0.00 |
October | 3138.42 | 139.28 | 791.66 | 258.41 | 533.26 | 0.00 | 0.00 |
November | 2044.17 | 536.20 | 665.01 | 211.53 | 453.48 | 0.00 | 0.00 |
December | 1167.90 | 1049.65 | 538.85 | 149.04 | 389.82 | 0.00 | 0.00 |
Annual Sum or Average | 3136.67 | 451.67 | 796.48 | 237.82 | 558.66 | 0.00 | 0.00 |
Minimum of Months | 1130.08 | 0.00 | 538.85 | 149.04 | 389.82 | 0.00 | 0.00 |
Maximum of Months | 5357.67 | 1297.53 | 990.32 | 314.43 | 675.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3626.34 | 2016.61 | 1609.99 | 750.05 | 859.94 | 0.00 | 0.00 |
February | 3738.94 | 1745.41 | 1532.20 | 631.56 | 900.64 | 0.00 | 0.00 |
March | 3636.26 | 1338.63 | 1292.75 | 378.94 | 913.80 | 0.00 | 0.00 |
April | 3621.55 | 766.15 | 1023.09 | 141.61 | 881.48 | 0.00 | 0.00 |
May | 4454.12 | 169.16 | 845.16 | 22.71 | 822.45 | 0.00 | 0.00 |
June | 4853.47 | 15.70 | 787.70 | 2.07 | 785.63 | 0.00 | 0.00 |
July | 5885.99 | 0.00 | 791.69 | 11.79 | 779.90 | 0.00 | 0.00 |
August | 6538.87 | 0.00 | 940.29 | 92.56 | 847.73 | 0.00 | 0.00 |
September | 6166.21 | 50.82 | 1253.87 | 326.59 | 927.28 | 0.00 | 0.00 |
October | 5975.84 | 276.19 | 1603.95 | 655.15 | 948.81 | 0.00 | 0.00 |
November | 5185.74 | 926.10 | 1731.08 | 831.21 | 899.88 | 0.00 | 0.00 |
December | 3947.48 | 1712.50 | 1593.83 | 777.66 | 816.17 | 0.00 | 0.00 |
Annual Sum or Average | 4809.62 | 746.69 | 1248.72 | 383.79 | 864.93 | 0.00 | 0.00 |
Minimum of Months | 3621.55 | 0.00 | 787.70 | 2.07 | 779.90 | 0.00 | 0.00 |
Maximum of Months | 6538.87 | 2016.61 | 1731.08 | 831.21 | 948.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1142.17 | 1548.56 | 595.31 | 171.97 | 423.34 | 0.00 | 0.00 |
February | 1469.23 | 1386.50 | 679.66 | 194.87 | 484.80 | 0.00 | 0.00 |
March | 2053.15 | 1125.41 | 802.73 | 237.23 | 565.50 | 0.00 | 0.00 |
April | 2753.17 | 724.93 | 876.16 | 244.90 | 631.26 | 0.00 | 0.00 |
May | 4050.27 | 157.44 | 955.49 | 285.95 | 669.55 | 0.00 | 0.00 |
June | 4477.79 | 27.59 | 987.59 | 311.35 | 676.23 | 0.00 | 0.00 |
July | 4877.54 | 0.44 | 907.70 | 260.93 | 646.78 | 0.00 | 0.00 |
August | 4956.08 | 0.23 | 928.28 | 281.46 | 646.83 | 0.00 | 0.00 |
September | 4064.27 | 49.52 | 883.20 | 276.86 | 606.34 | 0.00 | 0.00 |
October | 2992.42 | 270.86 | 785.72 | 253.82 | 531.90 | 0.00 | 0.00 |
November | 1999.80 | 825.50 | 676.18 | 221.78 | 454.40 | 0.00 | 0.00 |
December | 1187.14 | 1512.08 | 567.32 | 172.92 | 394.39 | 0.00 | 0.00 |
Annual Sum or Average | 3010.99 | 632.09 | 804.23 | 243.00 | 561.23 | 0.00 | 0.00 |
Minimum of Months | 1142.17 | 0.23 | 567.32 | 171.97 | 394.39 | 0.00 | 0.00 |
Maximum of Months | 4956.08 | 1548.56 | 987.59 | 311.35 | 676.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 805.20 | 1901.53 | 502.17 | 0.00 | 502.17 | 0.00 | 0.00 |
February | 1157.93 | 1576.84 | 575.63 | 0.00 | 575.63 | 0.00 | 0.00 |
March | 1753.07 | 1178.05 | 661.19 | 0.00 | 661.19 | 0.00 | 0.00 |
April | 2746.53 | 729.72 | 746.02 | 2.61 | 743.41 | 0.00 | 0.00 |
May | 4468.06 | 175.65 | 848.43 | 34.52 | 813.91 | 0.00 | 0.00 |
June | 5254.70 | 31.88 | 915.56 | 67.63 | 847.93 | 0.00 | 0.00 |
July | 6100.20 | 0.01 | 833.97 | 33.90 | 800.06 | 0.00 | 0.00 |
August | 6043.47 | 0.02 | 770.31 | 9.77 | 760.54 | 0.00 | 0.00 |
September | 4417.14 | 56.61 | 698.64 | 0.16 | 698.48 | 0.00 | 0.00 |
October | 3044.44 | 283.10 | 619.26 | 0.00 | 619.26 | 0.00 | 0.00 |
November | 1824.17 | 819.36 | 531.62 | 0.00 | 531.62 | 0.00 | 0.00 |
December | 971.03 | 1508.91 | 468.71 | 0.00 | 468.71 | 0.00 | 0.00 |
Annual Sum or Average | 3228.62 | 684.23 | 681.37 | 12.43 | 668.94 | 0.00 | 0.00 |
Minimum of Months | 805.20 | 0.01 | 468.71 | 0.00 | 468.71 | 0.00 | 0.00 |
Maximum of Months | 6100.20 | 1901.53 | 915.56 | 67.63 | 847.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1166.71 | 1164.74 | 606.59 | 184.21 | 422.38 | 0.00 | 0.00 |
February | 1451.50 | 973.65 | 660.87 | 179.75 | 481.12 | 0.00 | 0.00 |
March | 1946.09 | 731.35 | 729.14 | 179.81 | 549.34 | 0.00 | 0.00 |
April | 2925.68 | 457.93 | 887.49 | 258.51 | 628.98 | 0.00 | 0.00 |
May | 4209.00 | 104.92 | 990.32 | 314.43 | 675.89 | 0.00 | 0.00 |
June | 4562.49 | 15.57 | 971.92 | 297.57 | 674.36 | 0.00 | 0.00 |
July | 5131.20 | 0.00 | 908.67 | 263.38 | 645.28 | 0.00 | 0.00 |
August | 5283.50 | 0.00 | 928.72 | 285.24 | 643.48 | 0.00 | 0.00 |
September | 4124.21 | 29.82 | 872.12 | 269.07 | 603.05 | 0.00 | 0.00 |
October | 3084.38 | 161.88 | 791.66 | 258.41 | 533.26 | 0.00 | 0.00 |
November | 2030.65 | 504.40 | 665.00 | 211.53 | 453.47 | 0.00 | 0.00 |
December | 1205.56 | 928.89 | 538.85 | 149.04 | 389.82 | 0.00 | 0.00 |
Annual Sum or Average | 3103.43 | 420.11 | 796.47 | 237.82 | 558.66 | 0.00 | 0.00 |
Minimum of Months | 1166.71 | 0.00 | 538.85 | 149.04 | 389.82 | 0.00 | 0.00 |
Maximum of Months | 5283.50 | 1164.74 | 990.32 | 314.43 | 675.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3535.00 | 1926.15 | 1609.98 | 750.05 | 859.94 | 0.00 | 0.00 |
February | 3658.62 | 1630.41 | 1532.19 | 631.55 | 900.64 | 0.00 | 0.00 |
March | 3593.66 | 1231.91 | 1292.74 | 378.94 | 913.80 | 0.00 | 0.00 |
April | 3627.19 | 746.34 | 1023.08 | 141.61 | 881.48 | 0.00 | 0.00 |
May | 4491.35 | 169.50 | 845.16 | 22.71 | 822.45 | 0.00 | 0.00 |
June | 4912.14 | 22.64 | 787.69 | 2.07 | 785.63 | 0.00 | 0.00 |
July | 5981.60 | 0.00 | 791.69 | 11.79 | 779.90 | 0.00 | 0.00 |
August | 6621.40 | 0.00 | 940.29 | 92.56 | 847.72 | 0.00 | 0.00 |
September | 6142.97 | 55.53 | 1253.86 | 326.59 | 927.27 | 0.00 | 0.00 |
October | 5910.10 | 293.96 | 1603.95 | 655.15 | 948.80 | 0.00 | 0.00 |
November | 5110.81 | 873.98 | 1731.08 | 831.20 | 899.88 | 0.00 | 0.00 |
December | 3898.83 | 1570.64 | 1593.83 | 777.65 | 816.17 | 0.00 | 0.00 |
Annual Sum or Average | 4797.88 | 705.65 | 1248.71 | 383.79 | 864.92 | 0.00 | 0.00 |
Minimum of Months | 3535.00 | 0.00 | 787.69 | 2.07 | 779.90 | 0.00 | 0.00 |
Maximum of Months | 6621.40 | 1926.15 | 1731.08 | 831.20 | 948.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1195.19 | 1309.22 | 595.30 | 171.97 | 423.33 | 0.00 | 0.00 |
February | 1545.02 | 1086.41 | 679.66 | 194.87 | 484.79 | 0.00 | 0.00 |
March | 2136.79 | 838.36 | 802.73 | 237.22 | 565.50 | 0.00 | 0.00 |
April | 2859.89 | 544.22 | 876.16 | 244.90 | 631.26 | 0.00 | 0.00 |
May | 4078.64 | 135.08 | 955.49 | 285.94 | 669.54 | 0.00 | 0.00 |
June | 4567.49 | 23.38 | 987.58 | 311.35 | 676.23 | 0.00 | 0.00 |
July | 5064.43 | 0.00 | 907.70 | 260.93 | 646.77 | 0.00 | 0.00 |
August | 5185.53 | 0.09 | 928.28 | 281.46 | 646.82 | 0.00 | 0.00 |
September | 4116.17 | 42.65 | 883.20 | 276.85 | 606.34 | 0.00 | 0.00 |
October | 3075.38 | 211.84 | 785.72 | 253.82 | 531.90 | 0.00 | 0.00 |
November | 2116.01 | 584.43 | 676.18 | 221.78 | 454.40 | 0.00 | 0.00 |
December | 1332.69 | 1055.34 | 567.31 | 172.92 | 394.39 | 0.00 | 0.00 |
Annual Sum or Average | 3115.55 | 483.03 | 804.23 | 243.00 | 561.23 | 0.00 | 0.00 |
Minimum of Months | 1195.19 | 0.00 | 567.31 | 171.97 | 394.39 | 0.00 | 0.00 |
Maximum of Months | 5185.53 | 1309.22 | 987.58 | 311.35 | 676.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 854.44 | 1688.58 | 502.17 | 0.00 | 502.17 | 0.00 | 0.00 |
February | 1181.61 | 1424.53 | 575.63 | 0.00 | 575.63 | 0.00 | 0.00 |
March | 1749.22 | 1084.06 | 661.19 | 0.00 | 661.19 | 0.00 | 0.00 |
April | 2709.42 | 691.27 | 746.02 | 2.61 | 743.41 | 0.00 | 0.00 |
May | 4403.29 | 172.71 | 848.43 | 34.52 | 813.91 | 0.00 | 0.00 |
June | 5182.55 | 32.24 | 915.56 | 67.63 | 847.93 | 0.00 | 0.00 |
July | 6020.54 | 0.02 | 833.97 | 33.90 | 800.06 | 0.00 | 0.00 |
August | 5977.34 | 0.00 | 770.31 | 9.77 | 760.54 | 0.00 | 0.00 |
September | 4365.12 | 54.47 | 698.64 | 0.16 | 698.48 | 0.00 | 0.00 |
October | 3019.32 | 265.34 | 619.26 | 0.00 | 619.26 | 0.00 | 0.00 |
November | 1837.14 | 736.15 | 531.62 | 0.00 | 531.62 | 0.00 | 0.00 |
December | 1015.10 | 1334.54 | 468.71 | 0.00 | 468.71 | 0.00 | 0.00 |
Annual Sum or Average | 3205.83 | 619.76 | 681.37 | 12.43 | 668.94 | 0.00 | 0.00 |
Minimum of Months | 854.44 | 0.00 | 468.71 | 0.00 | 468.71 | 0.00 | 0.00 |
Maximum of Months | 6020.54 | 1688.58 | 915.56 | 67.63 | 847.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1199.24 | 1057.83 | 606.59 | 184.21 | 422.38 | 0.00 | 0.00 |
February | 1458.93 | 901.74 | 660.87 | 179.75 | 481.12 | 0.00 | 0.00 |
March | 1936.44 | 688.36 | 729.14 | 179.81 | 549.34 | 0.00 | 0.00 |
April | 2896.66 | 442.70 | 887.49 | 258.51 | 628.98 | 0.00 | 0.00 |
May | 4160.56 | 104.94 | 990.32 | 314.43 | 675.89 | 0.00 | 0.00 |
June | 4507.70 | 16.51 | 971.92 | 297.57 | 674.36 | 0.00 | 0.00 |
July | 5064.44 | 0.01 | 908.67 | 263.38 | 645.28 | 0.00 | 0.00 |
August | 5228.86 | 0.00 | 928.72 | 285.24 | 643.48 | 0.00 | 0.00 |
September | 4078.86 | 29.81 | 872.12 | 269.07 | 603.05 | 0.00 | 0.00 |
October | 3058.43 | 156.39 | 791.66 | 258.41 | 533.26 | 0.00 | 0.00 |
November | 2029.79 | 466.04 | 665.00 | 211.53 | 453.47 | 0.00 | 0.00 |
December | 1228.46 | 845.05 | 538.85 | 149.04 | 389.82 | 0.00 | 0.00 |
Annual Sum or Average | 3080.57 | 389.95 | 796.47 | 237.82 | 558.66 | 0.00 | 0.00 |
Minimum of Months | 1199.24 | 0.00 | 538.85 | 149.04 | 389.82 | 0.00 | 0.00 |
Maximum of Months | 5228.86 | 1057.83 | 990.32 | 314.43 | 675.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3557.24 | 1734.27 | 1609.98 | 750.05 | 859.94 | 0.00 | 0.00 |
February | 3650.03 | 1489.09 | 1532.19 | 631.55 | 900.64 | 0.00 | 0.00 |
March | 3566.06 | 1143.30 | 1292.74 | 378.94 | 913.80 | 0.00 | 0.00 |
April | 3580.60 | 707.81 | 1023.08 | 141.61 | 881.48 | 0.00 | 0.00 |
May | 4428.02 | 165.10 | 845.16 | 22.71 | 822.45 | 0.00 | 0.00 |
June | 4844.48 | 22.63 | 787.69 | 2.07 | 785.63 | 0.00 | 0.00 |
July | 5900.63 | 0.00 | 791.69 | 11.79 | 779.90 | 0.00 | 0.00 |
August | 6552.40 | 0.00 | 940.29 | 92.56 | 847.72 | 0.00 | 0.00 |
September | 6072.69 | 53.46 | 1253.86 | 326.59 | 927.27 | 0.00 | 0.00 |
October | 5853.60 | 278.10 | 1603.95 | 655.15 | 948.80 | 0.00 | 0.00 |
November | 5085.10 | 799.74 | 1731.08 | 831.20 | 899.88 | 0.00 | 0.00 |
December | 3912.04 | 1417.23 | 1593.83 | 777.65 | 816.17 | 0.00 | 0.00 |
Annual Sum or Average | 4757.69 | 646.80 | 1248.71 | 383.79 | 864.92 | 0.00 | 0.00 |
Minimum of Months | 3557.24 | 0.00 | 787.69 | 2.07 | 779.90 | 0.00 | 0.00 |
Maximum of Months | 6552.40 | 1734.27 | 1731.08 | 831.20 | 948.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1193.37 | 1197.33 | 595.30 | 171.97 | 423.33 | 0.00 | 0.00 |
February | 1529.31 | 1007.61 | 679.66 | 194.87 | 484.79 | 0.00 | 0.00 |
March | 2109.30 | 786.86 | 802.73 | 237.22 | 565.50 | 0.00 | 0.00 |
April | 2816.31 | 519.48 | 876.16 | 244.90 | 631.26 | 0.00 | 0.00 |
May | 4027.21 | 130.39 | 955.49 | 285.94 | 669.54 | 0.00 | 0.00 |
June | 4513.74 | 23.40 | 987.58 | 311.35 | 676.23 | 0.00 | 0.00 |
July | 5007.44 | 0.01 | 907.70 | 260.93 | 646.77 | 0.00 | 0.00 |
August | 5133.99 | 0.03 | 928.28 | 281.46 | 646.82 | 0.00 | 0.00 |
September | 4074.15 | 41.36 | 883.20 | 276.85 | 606.34 | 0.00 | 0.00 |
October | 3047.26 | 201.75 | 785.72 | 253.82 | 531.90 | 0.00 | 0.00 |
November | 2102.95 | 540.44 | 676.18 | 221.78 | 454.40 | 0.00 | 0.00 |
December | 1331.75 | 966.03 | 567.31 | 172.92 | 394.39 | 0.00 | 0.00 |
Annual Sum or Average | 3083.27 | 448.51 | 804.23 | 243.00 | 561.23 | 0.00 | 0.00 |
Minimum of Months | 1193.37 | 0.01 | 567.31 | 171.97 | 394.39 | 0.00 | 0.00 |
Maximum of Months | 5133.99 | 1197.33 | 987.58 | 311.35 | 676.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.193172E+10 | 0.586954E+10 | 0.134502E+10 | 0.00 | 0.134502E+10 | 0.00 | 0.00 |
February | 0.261739E+10 | 0.446093E+10 | 0.139257E+10 | 0.00 | 0.139257E+10 | 0.00 | 0.00 |
March | 0.452946E+10 | 0.368777E+10 | 0.177094E+10 | 0.00 | 0.177094E+10 | 0.00 | 0.00 |
April | 0.695781E+10 | 0.203134E+10 | 0.193370E+10 | 6768618.99 | 0.192693E+10 | 0.00 | 0.00 |
May | 0.118638E+11 | 0.464899E+09 | 0.227246E+10 | 92469134.46 | 0.217999E+10 | 0.00 | 0.00 |
June | 0.135202E+11 | 56502482.42 | 0.237314E+10 | 0.175288E+09 | 0.219786E+10 | 0.00 | 0.00 |
July | 0.160674E+11 | 44011.84 | 0.223370E+10 | 90809003.57 | 0.214289E+10 | 0.00 | 0.00 |
August | 0.158632E+11 | 0.00 | 0.206320E+10 | 26156478.59 | 0.203704E+10 | 0.00 | 0.00 |
September | 0.112765E+11 | 0.138264E+09 | 0.181088E+10 | 412694.39 | 0.181047E+10 | 0.00 | 0.00 |
October | 0.795226E+10 | 0.774992E+09 | 0.165863E+10 | 0.00 | 0.165863E+10 | 0.00 | 0.00 |
November | 0.448231E+10 | 0.249517E+10 | 0.137797E+10 | 0.00 | 0.137797E+10 | 0.00 | 0.00 |
December | 0.229753E+10 | 0.494838E+10 | 0.125540E+10 | 0.00 | 0.125540E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.993595E+11 | 0.249278E+11 | 0.214876E+11 | 0.391903E+09 | 0.210957E+11 | 0.00 | 0.00 |
Minimum of Months | 0.193172E+10 | 0.00 | 0.125540E+10 | 0.00 | 0.125540E+10 | 0.00 | 0.00 |
Maximum of Months | 0.160674E+11 | 0.586954E+10 | 0.237314E+10 | 0.175288E+09 | 0.219786E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.302680E+10 | 0.347529E+10 | 0.162470E+10 | 0.493391E+09 | 0.113131E+10 | 0.00 | 0.00 |
February | 0.348833E+10 | 0.262930E+10 | 0.159878E+10 | 0.434856E+09 | 0.116393E+10 | 0.00 | 0.00 |
March | 0.525376E+10 | 0.212687E+10 | 0.195294E+10 | 0.481594E+09 | 0.147135E+10 | 0.00 | 0.00 |
April | 0.772163E+10 | 0.110592E+10 | 0.230038E+10 | 0.670048E+09 | 0.163033E+10 | 0.00 | 0.00 |
May | 0.114404E+11 | 0.253567E+09 | 0.265247E+10 | 0.842172E+09 | 0.181030E+10 | 0.00 | 0.00 |
June | 0.120466E+11 | 15755747.54 | 0.251924E+10 | 0.771302E+09 | 0.174794E+10 | 0.00 | 0.00 |
July | 0.139103E+11 | 0.00 | 0.243379E+10 | 0.705450E+09 | 0.172834E+10 | 0.00 | 0.00 |
August | 0.143500E+11 | 0.00 | 0.248749E+10 | 0.763997E+09 | 0.172350E+10 | 0.00 | 0.00 |
September | 0.108477E+11 | 62760590.14 | 0.226054E+10 | 0.697438E+09 | 0.156310E+10 | 0.00 | 0.00 |
October | 0.840595E+10 | 0.373053E+09 | 0.212040E+10 | 0.692119E+09 | 0.142828E+10 | 0.00 | 0.00 |
November | 0.529849E+10 | 0.138982E+10 | 0.172369E+10 | 0.548284E+09 | 0.117541E+10 | 0.00 | 0.00 |
December | 0.312810E+10 | 0.281139E+10 | 0.144327E+10 | 0.399180E+09 | 0.104409E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.989180E+11 | 0.142437E+11 | 0.251177E+11 | 0.749983E+10 | 0.176179E+11 | 0.00 | 0.00 |
Minimum of Months | 0.302680E+10 | 0.00 | 0.144327E+10 | 0.399180E+09 | 0.104409E+10 | 0.00 | 0.00 |
Maximum of Months | 0.143500E+11 | 0.347529E+10 | 0.265247E+10 | 0.842172E+09 | 0.181030E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.971279E+10 | 0.540128E+10 | 0.431220E+10 | 0.200894E+10 | 0.230326E+10 | 0.00 | 0.00 |
February | 0.904523E+10 | 0.422250E+10 | 0.370669E+10 | 0.152786E+10 | 0.217883E+10 | 0.00 | 0.00 |
March | 0.973936E+10 | 0.358538E+10 | 0.346249E+10 | 0.101497E+10 | 0.244753E+10 | 0.00 | 0.00 |
April | 0.938705E+10 | 0.198586E+10 | 0.265184E+10 | 0.367051E+09 | 0.228479E+10 | 0.00 | 0.00 |
May | 0.119299E+11 | 0.453084E+09 | 0.226368E+10 | 60827344.67 | 0.220285E+10 | 0.00 | 0.00 |
June | 0.125802E+11 | 40692733.56 | 0.204171E+10 | 5354431.89 | 0.203635E+10 | 0.00 | 0.00 |
July | 0.157650E+11 | 0.00 | 0.212047E+10 | 31587633.50 | 0.208888E+10 | 0.00 | 0.00 |
August | 0.175137E+11 | 0.00 | 0.251848E+10 | 0.247925E+09 | 0.227055E+10 | 0.00 | 0.00 |
September | 0.159828E+11 | 0.131726E+09 | 0.325003E+10 | 0.846523E+09 | 0.240351E+10 | 0.00 | 0.00 |
October | 0.160057E+11 | 0.739758E+09 | 0.429603E+10 | 0.175475E+10 | 0.254128E+10 | 0.00 | 0.00 |
November | 0.134414E+11 | 0.240045E+10 | 0.448697E+10 | 0.215449E+10 | 0.233249E+10 | 0.00 | 0.00 |
December | 0.105729E+11 | 0.458675E+10 | 0.426892E+10 | 0.208288E+10 | 0.218604E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.151676E+12 | 0.235475E+11 | 0.393795E+11 | 0.121031E+11 | 0.272764E+11 | 0.00 | 0.00 |
Minimum of Months | 0.904523E+10 | 0.00 | 0.204171E+10 | 5354431.89 | 0.203635E+10 | 0.00 | 0.00 |
Maximum of Months | 0.175137E+11 | 0.540128E+10 | 0.448697E+10 | 0.215449E+10 | 0.254128E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.305919E+10 | 0.414767E+10 | 0.159447E+10 | 0.460609E+09 | 0.113386E+10 | 0.00 | 0.00 |
February | 0.355436E+10 | 0.335422E+10 | 0.164424E+10 | 0.471427E+09 | 0.117282E+10 | 0.00 | 0.00 |
March | 0.549915E+10 | 0.301430E+10 | 0.215003E+10 | 0.635385E+09 | 0.151465E+10 | 0.00 | 0.00 |
April | 0.713623E+10 | 0.187901E+10 | 0.227101E+10 | 0.634787E+09 | 0.163623E+10 | 0.00 | 0.00 |
May | 0.108483E+11 | 0.421681E+09 | 0.255919E+10 | 0.765878E+09 | 0.179331E+10 | 0.00 | 0.00 |
June | 0.116064E+11 | 71514324.70 | 0.255982E+10 | 0.807030E+09 | 0.175279E+10 | 0.00 | 0.00 |
July | 0.130640E+11 | 1171097.36 | 0.243119E+10 | 0.698870E+09 | 0.173232E+10 | 0.00 | 0.00 |
August | 0.132744E+11 | 613702.40 | 0.248631E+10 | 0.753853E+09 | 0.173246E+10 | 0.00 | 0.00 |
September | 0.105346E+11 | 0.128362E+09 | 0.228925E+10 | 0.717610E+09 | 0.157164E+10 | 0.00 | 0.00 |
October | 0.801489E+10 | 0.725480E+09 | 0.210448E+10 | 0.679836E+09 | 0.142465E+10 | 0.00 | 0.00 |
November | 0.518348E+10 | 0.213970E+10 | 0.175267E+10 | 0.574864E+09 | 0.117781E+10 | 0.00 | 0.00 |
December | 0.317964E+10 | 0.404996E+10 | 0.151950E+10 | 0.463152E+09 | 0.105635E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.949546E+11 | 0.199337E+11 | 0.253622E+11 | 0.766330E+10 | 0.176989E+11 | 0.00 | 0.00 |
Minimum of Months | 0.305919E+10 | 613702.40 | 0.151950E+10 | 0.460609E+09 | 0.105635E+10 | 0.00 | 0.00 |
Maximum of Months | 0.132744E+11 | 0.414767E+10 | 0.255982E+10 | 0.807030E+09 | 0.179331E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.215664E+10 | 0.509306E+10 | 0.134502E+10 | 0.00 | 0.134502E+10 | 0.00 | 0.00 |
February | 0.280125E+10 | 0.381470E+10 | 0.139257E+10 | 0.00 | 0.139257E+10 | 0.00 | 0.00 |
March | 0.469541E+10 | 0.315530E+10 | 0.177093E+10 | 0.00 | 0.177093E+10 | 0.00 | 0.00 |
April | 0.711902E+10 | 0.189142E+10 | 0.193369E+10 | 6768594.96 | 0.192692E+10 | 0.00 | 0.00 |
May | 0.119672E+11 | 0.470469E+09 | 0.227245E+10 | 92468806.09 | 0.217998E+10 | 0.00 | 0.00 |
June | 0.136202E+11 | 82639489.54 | 0.237313E+10 | 0.175287E+09 | 0.219785E+10 | 0.00 | 0.00 |
July | 0.163388E+11 | 26725.57 | 0.223370E+10 | 90808681.10 | 0.214289E+10 | 0.00 | 0.00 |
August | 0.161868E+11 | 62412.75 | 0.206319E+10 | 26156385.70 | 0.203704E+10 | 0.00 | 0.00 |
September | 0.114492E+11 | 0.146727E+09 | 0.181088E+10 | 412692.92 | 0.181047E+10 | 0.00 | 0.00 |
October | 0.815424E+10 | 0.758244E+09 | 0.165863E+10 | 0.00 | 0.165863E+10 | 0.00 | 0.00 |
November | 0.472826E+10 | 0.212377E+10 | 0.137796E+10 | 0.00 | 0.137796E+10 | 0.00 | 0.00 |
December | 0.260081E+10 | 0.404146E+10 | 0.125540E+10 | 0.00 | 0.125540E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.101818E+12 | 0.215779E+11 | 0.214875E+11 | 0.391902E+09 | 0.210956E+11 | 0.00 | 0.00 |
Minimum of Months | 0.215664E+10 | 26725.57 | 0.125540E+10 | 0.00 | 0.125540E+10 | 0.00 | 0.00 |
Maximum of Months | 0.163388E+11 | 0.509306E+10 | 0.237313E+10 | 0.175287E+09 | 0.219785E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.312490E+10 | 0.311965E+10 | 0.162470E+10 | 0.493389E+09 | 0.113131E+10 | 0.00 | 0.00 |
February | 0.351147E+10 | 0.235546E+10 | 0.159878E+10 | 0.434854E+09 | 0.116392E+10 | 0.00 | 0.00 |
March | 0.521241E+10 | 0.195885E+10 | 0.195293E+10 | 0.481592E+09 | 0.147134E+10 | 0.00 | 0.00 |
April | 0.758337E+10 | 0.118695E+10 | 0.230037E+10 | 0.670045E+09 | 0.163032E+10 | 0.00 | 0.00 |
May | 0.112734E+11 | 0.281008E+09 | 0.265246E+10 | 0.842168E+09 | 0.181029E+10 | 0.00 | 0.00 |
June | 0.118260E+11 | 40351693.35 | 0.251923E+10 | 0.771299E+09 | 0.174793E+10 | 0.00 | 0.00 |
July | 0.137434E+11 | 0.00 | 0.243378E+10 | 0.705447E+09 | 0.172833E+10 | 0.00 | 0.00 |
August | 0.141513E+11 | 0.00 | 0.248748E+10 | 0.763994E+09 | 0.172349E+10 | 0.00 | 0.00 |
September | 0.106900E+11 | 77306392.88 | 0.226053E+10 | 0.697435E+09 | 0.156310E+10 | 0.00 | 0.00 |
October | 0.826120E+10 | 0.433578E+09 | 0.212039E+10 | 0.692116E+09 | 0.142827E+10 | 0.00 | 0.00 |
November | 0.526345E+10 | 0.130740E+10 | 0.172369E+10 | 0.548281E+09 | 0.117541E+10 | 0.00 | 0.00 |
December | 0.322897E+10 | 0.248795E+10 | 0.144326E+10 | 0.399178E+09 | 0.104408E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.978698E+11 | 0.132485E+11 | 0.251176E+11 | 0.749980E+10 | 0.176178E+11 | 0.00 | 0.00 |
Minimum of Months | 0.312490E+10 | 0.00 | 0.144326E+10 | 0.399178E+09 | 0.104408E+10 | 0.00 | 0.00 |
Maximum of Months | 0.141513E+11 | 0.311965E+10 | 0.265246E+10 | 0.842168E+09 | 0.181029E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.946814E+10 | 0.515900E+10 | 0.431218E+10 | 0.200893E+10 | 0.230325E+10 | 0.00 | 0.00 |
February | 0.885094E+10 | 0.394428E+10 | 0.370667E+10 | 0.152785E+10 | 0.217882E+10 | 0.00 | 0.00 |
March | 0.962526E+10 | 0.329954E+10 | 0.346248E+10 | 0.101496E+10 | 0.244752E+10 | 0.00 | 0.00 |
April | 0.940167E+10 | 0.193452E+10 | 0.265183E+10 | 0.367050E+09 | 0.228478E+10 | 0.00 | 0.00 |
May | 0.120296E+11 | 0.454001E+09 | 0.226367E+10 | 60827128.67 | 0.220284E+10 | 0.00 | 0.00 |
June | 0.127323E+11 | 58682672.02 | 0.204170E+10 | 5354412.88 | 0.203635E+10 | 0.00 | 0.00 |
July | 0.160211E+11 | 0.00 | 0.212046E+10 | 31587521.34 | 0.208887E+10 | 0.00 | 0.00 |
August | 0.177348E+11 | 0.00 | 0.251847E+10 | 0.247924E+09 | 0.227055E+10 | 0.00 | 0.00 |
September | 0.159226E+11 | 0.143945E+09 | 0.325002E+10 | 0.846520E+09 | 0.240350E+10 | 0.00 | 0.00 |
October | 0.158296E+11 | 0.787333E+09 | 0.429601E+10 | 0.175474E+10 | 0.254127E+10 | 0.00 | 0.00 |
November | 0.132472E+11 | 0.226536E+10 | 0.448696E+10 | 0.215448E+10 | 0.233248E+10 | 0.00 | 0.00 |
December | 0.104426E+11 | 0.420681E+10 | 0.426890E+10 | 0.208287E+10 | 0.218603E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.151306E+12 | 0.222535E+11 | 0.393794E+11 | 0.121031E+11 | 0.272763E+11 | 0.00 | 0.00 |
Minimum of Months | 0.885094E+10 | 0.00 | 0.204170E+10 | 5354412.88 | 0.203635E+10 | 0.00 | 0.00 |
Maximum of Months | 0.177348E+11 | 0.515900E+10 | 0.448696E+10 | 0.215448E+10 | 0.254127E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.320121E+10 | 0.350660E+10 | 0.159446E+10 | 0.460607E+09 | 0.113386E+10 | 0.00 | 0.00 |
February | 0.373772E+10 | 0.262825E+10 | 0.164424E+10 | 0.471425E+09 | 0.117281E+10 | 0.00 | 0.00 |
March | 0.572319E+10 | 0.224546E+10 | 0.215002E+10 | 0.635382E+09 | 0.151464E+10 | 0.00 | 0.00 |
April | 0.741284E+10 | 0.141061E+10 | 0.227100E+10 | 0.634784E+09 | 0.163622E+10 | 0.00 | 0.00 |
May | 0.109242E+11 | 0.361806E+09 | 0.255918E+10 | 0.765875E+09 | 0.179331E+10 | 0.00 | 0.00 |
June | 0.118389E+11 | 60593800.47 | 0.255981E+10 | 0.807027E+09 | 0.175279E+10 | 0.00 | 0.00 |
July | 0.135646E+11 | 0.00 | 0.243118E+10 | 0.698867E+09 | 0.173232E+10 | 0.00 | 0.00 |
August | 0.138889E+11 | 233531.11 | 0.248630E+10 | 0.753850E+09 | 0.173245E+10 | 0.00 | 0.00 |
September | 0.106691E+11 | 0.110558E+09 | 0.228924E+10 | 0.717607E+09 | 0.157163E+10 | 0.00 | 0.00 |
October | 0.823710E+10 | 0.567381E+09 | 0.210447E+10 | 0.679833E+09 | 0.142464E+10 | 0.00 | 0.00 |
November | 0.548471E+10 | 0.151484E+10 | 0.175266E+10 | 0.574862E+09 | 0.117780E+10 | 0.00 | 0.00 |
December | 0.356947E+10 | 0.282662E+10 | 0.151949E+10 | 0.463150E+09 | 0.105634E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.982520E+11 | 0.152330E+11 | 0.253621E+11 | 0.766327E+10 | 0.176988E+11 | 0.00 | 0.00 |
Minimum of Months | 0.320121E+10 | 0.00 | 0.151949E+10 | 0.460607E+09 | 0.105634E+10 | 0.00 | 0.00 |
Maximum of Months | 0.138889E+11 | 0.350660E+10 | 0.255981E+10 | 0.807027E+09 | 0.179331E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.228852E+10 | 0.452270E+10 | 0.134502E+10 | 0.00 | 0.134502E+10 | 0.00 | 0.00 |
February | 0.285856E+10 | 0.344623E+10 | 0.139257E+10 | 0.00 | 0.139257E+10 | 0.00 | 0.00 |
March | 0.468512E+10 | 0.290354E+10 | 0.177093E+10 | 0.00 | 0.177093E+10 | 0.00 | 0.00 |
April | 0.702282E+10 | 0.179176E+10 | 0.193369E+10 | 6768594.96 | 0.192692E+10 | 0.00 | 0.00 |
May | 0.117938E+11 | 0.462584E+09 | 0.227245E+10 | 92468806.09 | 0.217998E+10 | 0.00 | 0.00 |
June | 0.134332E+11 | 83577475.04 | 0.237313E+10 | 0.175287E+09 | 0.219785E+10 | 0.00 | 0.00 |
July | 0.161254E+11 | 65867.56 | 0.223370E+10 | 90808681.10 | 0.214289E+10 | 0.00 | 0.00 |
August | 0.160097E+11 | 876.78 | 0.206319E+10 | 26156385.70 | 0.203704E+10 | 0.00 | 0.00 |
September | 0.113144E+11 | 0.141188E+09 | 0.181088E+10 | 412692.92 | 0.181047E+10 | 0.00 | 0.00 |
October | 0.808696E+10 | 0.710679E+09 | 0.165863E+10 | 0.00 | 0.165863E+10 | 0.00 | 0.00 |
November | 0.476187E+10 | 0.190811E+10 | 0.137796E+10 | 0.00 | 0.137796E+10 | 0.00 | 0.00 |
December | 0.271884E+10 | 0.357443E+10 | 0.125540E+10 | 0.00 | 0.125540E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.101099E+12 | 0.195449E+11 | 0.214875E+11 | 0.391902E+09 | 0.210956E+11 | 0.00 | 0.00 |
Minimum of Months | 0.228852E+10 | 876.78 | 0.125540E+10 | 0.00 | 0.125540E+10 | 0.00 | 0.00 |
Maximum of Months | 0.161254E+11 | 0.452270E+10 | 0.237313E+10 | 0.175287E+09 | 0.219785E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.321204E+10 | 0.283331E+10 | 0.162470E+10 | 0.493389E+09 | 0.113131E+10 | 0.00 | 0.00 |
February | 0.352944E+10 | 0.218150E+10 | 0.159878E+10 | 0.434854E+09 | 0.116392E+10 | 0.00 | 0.00 |
March | 0.518657E+10 | 0.184369E+10 | 0.195293E+10 | 0.481592E+09 | 0.147134E+10 | 0.00 | 0.00 |
April | 0.750815E+10 | 0.114748E+10 | 0.230037E+10 | 0.670045E+09 | 0.163032E+10 | 0.00 | 0.00 |
May | 0.111436E+11 | 0.281063E+09 | 0.265246E+10 | 0.842168E+09 | 0.181029E+10 | 0.00 | 0.00 |
June | 0.116840E+11 | 42781352.23 | 0.251923E+10 | 0.771299E+09 | 0.174793E+10 | 0.00 | 0.00 |
July | 0.135646E+11 | 17299.40 | 0.243378E+10 | 0.705447E+09 | 0.172833E+10 | 0.00 | 0.00 |
August | 0.140050E+11 | 0.00 | 0.248748E+10 | 0.763994E+09 | 0.172349E+10 | 0.00 | 0.00 |
September | 0.105724E+11 | 77272609.65 | 0.226053E+10 | 0.697435E+09 | 0.156310E+10 | 0.00 | 0.00 |
October | 0.819170E+10 | 0.418870E+09 | 0.212039E+10 | 0.692116E+09 | 0.142827E+10 | 0.00 | 0.00 |
November | 0.526121E+10 | 0.120799E+10 | 0.172369E+10 | 0.548281E+09 | 0.117541E+10 | 0.00 | 0.00 |
December | 0.329030E+10 | 0.226337E+10 | 0.144326E+10 | 0.399178E+09 | 0.104408E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.971490E+11 | 0.122973E+11 | 0.251176E+11 | 0.749980E+10 | 0.176178E+11 | 0.00 | 0.00 |
Minimum of Months | 0.321204E+10 | 0.00 | 0.144326E+10 | 0.399178E+09 | 0.104408E+10 | 0.00 | 0.00 |
Maximum of Months | 0.140050E+11 | 0.283331E+10 | 0.265246E+10 | 0.842168E+09 | 0.181029E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.952771E+10 | 0.464507E+10 | 0.431218E+10 | 0.200893E+10 | 0.230325E+10 | 0.00 | 0.00 |
February | 0.883016E+10 | 0.360239E+10 | 0.370667E+10 | 0.152785E+10 | 0.217882E+10 | 0.00 | 0.00 |
March | 0.955134E+10 | 0.306222E+10 | 0.346248E+10 | 0.101496E+10 | 0.244752E+10 | 0.00 | 0.00 |
April | 0.928091E+10 | 0.183464E+10 | 0.265183E+10 | 0.367050E+09 | 0.228478E+10 | 0.00 | 0.00 |
May | 0.118600E+11 | 0.442211E+09 | 0.226367E+10 | 60827128.67 | 0.220284E+10 | 0.00 | 0.00 |
June | 0.125569E+11 | 58658036.10 | 0.204170E+10 | 5354412.88 | 0.203635E+10 | 0.00 | 0.00 |
July | 0.158042E+11 | 0.00 | 0.212046E+10 | 31587521.34 | 0.208887E+10 | 0.00 | 0.00 |
August | 0.175499E+11 | 0.00 | 0.251847E+10 | 0.247924E+09 | 0.227055E+10 | 0.00 | 0.00 |
September | 0.157404E+11 | 0.138556E+09 | 0.325002E+10 | 0.846520E+09 | 0.240350E+10 | 0.00 | 0.00 |
October | 0.156783E+11 | 0.744856E+09 | 0.429601E+10 | 0.175474E+10 | 0.254127E+10 | 0.00 | 0.00 |
November | 0.131806E+11 | 0.207292E+10 | 0.448696E+10 | 0.215448E+10 | 0.233248E+10 | 0.00 | 0.00 |
December | 0.104780E+11 | 0.379592E+10 | 0.426890E+10 | 0.208287E+10 | 0.218603E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.150038E+12 | 0.203974E+11 | 0.393794E+11 | 0.121031E+11 | 0.272763E+11 | 0.00 | 0.00 |
Minimum of Months | 0.883016E+10 | 0.00 | 0.204170E+10 | 5354412.88 | 0.203635E+10 | 0.00 | 0.00 |
Maximum of Months | 0.175499E+11 | 0.464507E+10 | 0.448696E+10 | 0.215448E+10 | 0.254127E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.319632E+10 | 0.320693E+10 | 0.159446E+10 | 0.460607E+09 | 0.113386E+10 | 0.00 | 0.00 |
February | 0.369970E+10 | 0.243760E+10 | 0.164424E+10 | 0.471425E+09 | 0.117281E+10 | 0.00 | 0.00 |
March | 0.564956E+10 | 0.210753E+10 | 0.215002E+10 | 0.635382E+09 | 0.151464E+10 | 0.00 | 0.00 |
April | 0.729988E+10 | 0.134649E+10 | 0.227100E+10 | 0.634784E+09 | 0.163622E+10 | 0.00 | 0.00 |
May | 0.107865E+11 | 0.349244E+09 | 0.255918E+10 | 0.765875E+09 | 0.179331E+10 | 0.00 | 0.00 |
June | 0.116996E+11 | 60652294.16 | 0.255981E+10 | 0.807027E+09 | 0.175279E+10 | 0.00 | 0.00 |
July | 0.134119E+11 | 22882.99 | 0.243118E+10 | 0.698867E+09 | 0.173232E+10 | 0.00 | 0.00 |
August | 0.137509E+11 | 90755.46 | 0.248630E+10 | 0.753850E+09 | 0.173245E+10 | 0.00 | 0.00 |
September | 0.105602E+11 | 0.107201E+09 | 0.228924E+10 | 0.717607E+09 | 0.157163E+10 | 0.00 | 0.00 |
October | 0.816179E+10 | 0.540366E+09 | 0.210447E+10 | 0.679833E+09 | 0.142464E+10 | 0.00 | 0.00 |
November | 0.545085E+10 | 0.140082E+10 | 0.175266E+10 | 0.574862E+09 | 0.117780E+10 | 0.00 | 0.00 |
December | 0.356696E+10 | 0.258741E+10 | 0.151949E+10 | 0.463150E+09 | 0.105634E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.972341E+11 | 0.141444E+11 | 0.253621E+11 | 0.766327E+10 | 0.176988E+11 | 0.00 | 0.00 |
Minimum of Months | 0.319632E+10 | 22882.99 | 0.151949E+10 | 0.460607E+09 | 0.105634E+10 | 0.00 | 0.00 |
Maximum of Months | 0.137509E+11 | 0.320693E+10 | 0.255981E+10 | 0.807027E+09 | 0.179331E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.283644E+11 | -0.279220E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442367908.8 | 60.05 | 0.00 | 0.00 |
February | 0.250828E+11 | -0.246830E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -399783411.9 | 60.05 | 0.00 | 0.00 |
March | 0.274870E+11 | -0.270429E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444078272.9 | 60.05 | 0.00 | 0.00 |
April | 0.225414E+11 | -0.221129E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -428529186.6 | 60.05 | 0.00 | 0.00 |
May | 0.215623E+11 | -0.211188E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443518076.1 | 60.05 | 0.00 | 0.00 |
June | 0.195464E+11 | -0.191167E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -429742693.3 | 60.05 | 0.00 | 0.00 |
July | 0.180781E+11 | -0.176362E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -441970804.6 | 60.05 | 0.00 | 0.00 |
August | 0.206006E+11 | -0.201569E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443689747.5 | 60.05 | 0.00 | 0.00 |
September | 0.205888E+11 | -0.201605E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -428314640.7 | 60.05 | 0.00 | 0.00 |
October | 0.237260E+11 | -0.232840E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -441925276.4 | 60.05 | 0.00 | 0.00 |
November | 0.256366E+11 | -0.252094E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -427156942.9 | 60.05 | 0.00 | 0.00 |
December | 0.271915E+11 | -0.267502E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -441384292.7 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.280406E+12 | -0.275193E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.521246E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.180781E+11 | -0.279220E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -444078272.9 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.283644E+11 | -0.176362E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -399783411.9 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 325.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 375.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 403.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 405.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 395.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 358.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 351.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 319.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4323.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2016691.05 | 5605.91 | 21-JAN-06:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2016691.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2016691.05 | 5605.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 102034.48 | 680.23 | 18-DEC-06:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 102034.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 102034.48 | 680.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1939174.59 | 9120.91 | 20-JAN-06:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1939174.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1939174.59 | 9120.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1609040.86 | 6634.64 | 20-JAN-06:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1609040.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1609040.86 | 6634.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.611872E+09 | 20173.65 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.280374E+09 | 16193.01 | 22-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 57848076.65 | 3955.92 | 08-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 557393.88 | 438.90 | 22-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.254989E+09 | 16059.87 | 18-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.611872E+09 | 20173.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.358240E+09 | 13523.88 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172595E+09 | 11525.80 | 22-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 41373741.74 | 3589.57 | 07-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 658131.50 | 1351.66 | 22-NOV-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157238E+09 | 10700.16 | 18-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.730105E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.358240E+09 | 13523.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.505299E+09 | 19708.57 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.252133E+09 | 15314.25 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 57577521.37 | 3268.77 | 08-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33780.27 | 112.60 | 22-NOV-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188200E+09 | 13333.59 | 18-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.505299E+09 | 19708.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.494487E+09 | 12545.54 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.222429E+09 | 9488.90 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 45833360.19 | 3057.85 | 08-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1025038.76 | 755.05 | 22-NOV-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191347E+09 | 7844.98 | 18-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.955121E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.494487E+09 | 12545.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.104915E+12 | 0.101218E+12 | 223674.71 | 30-JAN-05:12 | 155430.62 | 0.54 |
February | 0.00 | 0.00 | 0.112725E+12 | 0.105933E+12 | 238924.66 | 09-FEB-05:11 | 165414.63 | 0.58 |
March | 0.00 | 0.00 | 0.154416E+12 | 0.146385E+12 | 256807.01 | 01-MAR-04:01 | 178276.26 | 0.62 |
April | 0.00 | 0.00 | 0.190962E+12 | 0.172046E+12 | 247407.81 | 12-APR-04:11 | 174798.50 | 0.71 |
May | 0.00 | 0.00 | 0.239864E+12 | 0.205386E+12 | 340072.35 | 29-MAY-14:41 | 200880.35 | 0.72 |
June | 0.00 | 0.00 | 0.304663E+12 | 0.227955E+12 | 363786.28 | 27-JUN-05:02 | 224322.01 | 0.81 |
July | 0.00 | 0.00 | 0.366479E+12 | 0.257162E+12 | 398569.65 | 27-JUL-05:02 | 242939.26 | 0.85 |
August | 0.00 | 0.00 | 0.400050E+12 | 0.278646E+12 | 387665.46 | 18-AUG-05:02 | 243956.93 | 0.87 |
September | 0.00 | 0.00 | 0.298511E+12 | 0.210900E+12 | 377852.44 | 12-SEP-05:02 | 225416.53 | 0.75 |
October | 0.00 | 0.00 | 0.248347E+12 | 0.195796E+12 | 325373.40 | 05-OCT-05:02 | 210155.16 | 0.71 |
November | 0.00 | 0.00 | 0.184969E+12 | 0.159876E+12 | 258956.36 | 03-NOV-05:02 | 162621.80 | 0.65 |
December | 0.00 | 0.00 | 0.139306E+12 | 0.127697E+12 | 243918.31 | 11-DEC-05:11 | 175938.58 | 0.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.274521E+13 | 0.218900E+13 | 0.70 | |||
Minimum of Months | 0.00 | 0.00 | 0.104915E+12 | 0.101218E+12 | 223674.71 | 155430.62 | 0.54 | |
Maximum of Months | 0.00 | 0.00 | 0.400050E+12 | 0.278646E+12 | 398569.65 | 243956.93 | 0.87 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.829400E+12 | 0.797049E+12 | 1881438.98 | 30-JAN-06:02 | 1305767.33 | 0.51 |
February | 0.00 | 0.00 | 0.892719E+12 | 0.830137E+12 | 2209819.60 | 09-FEB-06:02 | 1397632.94 | 0.56 |
March | 0.00 | 0.00 | 0.122709E+13 | 0.115078E+13 | 2139412.25 | 29-MAR-05:03 | 1368832.43 | 0.59 |
April | 0.00 | 0.00 | 0.148640E+13 | 0.132484E+13 | 2624962.25 | 30-APR-16:31 | 1503414.29 | 0.60 |
May | 0.00 | 0.00 | 0.218709E+13 | 0.185884E+13 | 2765163.76 | 27-MAY-05:02 | 1876614.82 | 0.68 |
June | 0.00 | 0.00 | 0.271837E+13 | 0.200125E+13 | 3171803.11 | 20-JUN-04:01 | 1796489.20 | 0.73 |
July | 0.00 | 0.00 | 0.326427E+13 | 0.222141E+13 | 3585466.34 | 30-JUL-16:51 | 1904720.44 | 0.77 |
August | 0.00 | 0.00 | 0.350618E+13 | 0.235991E+13 | 3367526.89 | 27-AUG-15:51 | 1897043.79 | 0.79 |
September | 0.00 | 0.00 | 0.272878E+13 | 0.188744E+13 | 3249025.22 | 22-SEP-04:01 | 1764519.46 | 0.70 |
October | 0.00 | 0.00 | 0.211595E+13 | 0.164538E+13 | 3292296.83 | 07-OCT-05:02 | 1973630.11 | 0.63 |
November | 0.00 | 0.00 | 0.150119E+13 | 0.126355E+13 | 2529834.87 | 03-NOV-05:02 | 1517382.13 | 0.59 |
December | 0.00 | 0.00 | 0.101770E+13 | 0.917510E+12 | 2265677.01 | 11-DEC-06:02 | 1422674.32 | 0.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.234751E+14 | 0.182581E+14 | 0.64 | |||
Minimum of Months | 0.00 | 0.00 | 0.829400E+12 | 0.797049E+12 | 1881438.98 | 1305767.33 | 0.51 | |
Maximum of Months | 0.00 | 0.00 | 0.350618E+13 | 0.235991E+13 | 3585466.34 | 1973630.11 | 0.79 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.833646E+11 | 0.802715E+11 | 117359.52 | 24-JAN-13:20 | 96723.99 | 0.51 |
February | 0.00 | 0.00 | 0.943700E+11 | 0.883633E+11 | 265346.96 | 09-FEB-06:02 | 154025.03 | 0.55 |
March | 0.00 | 0.00 | 0.134215E+12 | 0.126719E+12 | 244639.82 | 29-MAR-04:11 | 149751.82 | 0.58 |
April | 0.00 | 0.00 | 0.168432E+12 | 0.152389E+12 | 366291.49 | 30-APR-16:31 | 230516.77 | 0.60 |
May | 0.00 | 0.00 | 0.253441E+12 | 0.220471E+12 | 379039.74 | 30-MAY-04:01 | 217658.06 | 0.68 |
June | 0.00 | 0.00 | 0.309946E+12 | 0.238558E+12 | 440456.24 | 19-JUN-03:01 | 245730.42 | 0.73 |
July | 0.00 | 0.00 | 0.370574E+12 | 0.266793E+12 | 464682.85 | 30-JUL-16:21 | 271422.18 | 0.78 |
August | 0.00 | 0.00 | 0.393673E+12 | 0.280068E+12 | 422552.93 | 27-AUG-15:51 | 262553.14 | 0.80 |
September | 0.00 | 0.00 | 0.304294E+12 | 0.220449E+12 | 442282.34 | 10-SEP-15:01 | 260468.24 | 0.70 |
October | 0.00 | 0.00 | 0.231345E+12 | 0.184777E+12 | 369335.04 | 06-OCT-05:02 | 224992.84 | 0.62 |
November | 0.00 | 0.00 | 0.157674E+12 | 0.134545E+12 | 307772.63 | 03-NOV-05:02 | 174280.60 | 0.57 |
December | 0.00 | 0.00 | 0.103306E+12 | 0.936591E+11 | 268504.88 | 11-DEC-06:02 | 157964.88 | 0.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.260463E+13 | 0.208706E+13 | 0.64 | |||
Minimum of Months | 0.00 | 0.00 | 0.833646E+11 | 0.802715E+11 | 117359.52 | 96723.99 | 0.51 | |
Maximum of Months | 0.00 | 0.00 | 0.393673E+12 | 0.280068E+12 | 464682.85 | 271422.18 | 0.80 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.760111E+11 | 0.675704E+11 | 152186.15 | 30-JAN-05:12 | 121523.87 | 0.54 |
February | 0.00 | 0.00 | 0.753168E+11 | 0.640120E+11 | 177085.44 | 06-FEB-05:42 | 133239.82 | 0.57 |
March | 0.00 | 0.00 | 0.915400E+11 | 0.796550E+11 | 159080.09 | 02-MAR-06:02 | 150332.19 | 0.57 |
April | 0.00 | 0.00 | 0.968317E+11 | 0.795387E+11 | 176176.57 | 17-APR-03:42 | 135628.07 | 0.55 |
May | 0.00 | 0.00 | 0.122759E+12 | 0.948503E+11 | 223093.86 | 29-MAY-15:58 | 156251.17 | 0.60 |
June | 0.00 | 0.00 | 0.145321E+12 | 0.994878E+11 | 266090.29 | 25-JUN-14:41 | 143359.78 | 0.63 |
July | 0.00 | 0.00 | 0.163385E+12 | 0.102970E+12 | 256071.15 | 16-JUL-16:59 | 149806.36 | 0.61 |
August | 0.00 | 0.00 | 0.186674E+12 | 0.116657E+12 | 246532.14 | 20-AUG-16:17 | 154441.98 | 0.66 |
September | 0.00 | 0.00 | 0.154582E+12 | 0.990277E+11 | 271273.73 | 10-SEP-14:08 | 137426.03 | 0.64 |
October | 0.00 | 0.00 | 0.136571E+12 | 0.976798E+11 | 250162.94 | 01-OCT-13:40 | 146381.89 | 0.64 |
November | 0.00 | 0.00 | 0.117088E+12 | 0.891692E+11 | 175423.42 | 13-NOV-05:22 | 139374.15 | 0.63 |
December | 0.00 | 0.00 | 0.931014E+11 | 0.767081E+11 | 192553.17 | 11-DEC-05:33 | 138211.67 | 0.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.145918E+13 | 0.106733E+13 | 0.60 | |||
Minimum of Months | 0.00 | 0.00 | 0.753168E+11 | 0.640120E+11 | 152186.15 | 121523.87 | 0.54 | |
Maximum of Months | 0.00 | 0.00 | 0.186674E+12 | 0.116657E+12 | 271273.73 | 156251.17 | 0.66 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.263010E+12 | 0.263010E+12 | 104738.75 | 23-JAN-14:00 | 104738.75 | 0.88 |
February | 0.00 | 0.00 | 0.460117E+12 | 0.459473E+12 | 204074.65 | 07-FEB-16:00 | 197018.64 | 1.00 |
March | 0.00 | 0.00 | 0.772272E+12 | 0.770061E+12 | 400477.95 | 31-MAR-23:10 | 381977.73 | 0.98 |
April | 0.00 | 0.00 | 0.101523E+13 | 0.100963E+13 | 429487.79 | 26-APR-04:14 | 429487.79 | 1.00 |
May | 0.00 | 0.00 | 0.278159E+12 | 0.277002E+12 | 261409.08 | 31-MAY-23:02 | 189685.38 | 1.00 |
June | 0.00 | 0.00 | 0.522509E+12 | 0.507042E+12 | 378988.42 | 30-JUN-23:01 | 284933.04 | 1.00 |
July | 0.00 | 0.00 | 0.811605E+12 | 0.786093E+12 | 415712.37 | 31-JUL-23:02 | 387837.77 | 1.00 |
August | 0.00 | 0.00 | 0.108807E+13 | 0.105994E+13 | 421353.87 | 25-AUG-08:20 | 397357.84 | 1.00 |
September | 0.00 | 0.00 | 0.281464E+12 | 0.273182E+12 | 386094.51 | 30-SEP-23:02 | 188092.41 | 1.00 |
October | 0.00 | 0.00 | 0.535190E+12 | 0.523786E+12 | 373522.34 | 31-OCT-23:10 | 285043.83 | 1.00 |
November | 0.00 | 0.00 | 0.760152E+12 | 0.753259E+12 | 307758.48 | 01-NOV-14:00 | 296314.45 | 1.00 |
December | 0.00 | 0.00 | 0.104690E+13 | 0.104310E+13 | 413381.46 | 31-DEC-16:58 | 413381.46 | 0.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.783468E+13 | 0.772558E+13 | 0.99 | |||
Minimum of Months | 0.00 | 0.00 | 0.263010E+12 | 0.263010E+12 | 104738.75 | 104738.75 | 0.88 | |
Maximum of Months | 0.00 | 0.00 | 0.108807E+13 | 0.105994E+13 | 429487.79 | 429487.79 | 1.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HP COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.736250E+10 | 0.711230E+10 | 3518.01 | 30-JAN-15:00 | 3134.53 | 0.00 |
February | 0.00 | 0.00 | 0.116389E+11 | 0.112882E+11 | 5747.43 | 07-FEB-16:10 | 5306.30 | 0.00 |
March | 0.00 | 0.00 | 0.182687E+11 | 0.178990E+11 | 8786.92 | 31-MAR-23:10 | 8360.67 | 0.00 |
April | 0.00 | 0.00 | 0.229621E+11 | 0.224283E+11 | 9694.52 | 27-APR-16:00 | 9386.00 | 0.00 |
May | 0.00 | 0.00 | 0.910803E+10 | 0.844134E+10 | 5228.07 | 31-MAY-23:02 | 4846.94 | 0.00 |
June | 0.00 | 0.00 | 0.142552E+11 | 0.131516E+11 | 7403.16 | 30-JUN-23:01 | 6676.74 | 0.00 |
July | 0.00 | 0.00 | 0.201885E+11 | 0.187863E+11 | 9473.23 | 31-JUL-23:02 | 8605.07 | 0.00 |
August | 0.00 | 0.00 | 0.254420E+11 | 0.239081E+11 | 10395.00 | 22-AUG-16:00 | 9459.60 | 0.00 |
September | 0.00 | 0.00 | 0.945381E+10 | 0.824486E+10 | 5639.45 | 30-SEP-23:02 | 4742.23 | 0.00 |
October | 0.00 | 0.00 | 0.142957E+11 | 0.133606E+11 | 6924.83 | 31-OCT-23:31 | 6628.41 | 0.00 |
November | 0.00 | 0.00 | 0.181945E+11 | 0.175622E+11 | 7950.66 | 01-NOV-16:00 | 7329.63 | 0.00 |
December | 0.00 | 0.00 | 0.232398E+11 | 0.227670E+11 | 9653.98 | 05-DEC-17:00 | 9106.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.194410E+12 | 0.184950E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.736250E+10 | 0.711230E+10 | 3518.01 | 3134.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.254420E+11 | 0.239081E+11 | 10395.00 | 9459.60 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HP COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.616866E+11 | 0.592643E+11 | 32791.61 | 24-JAN-17:00 | 29738.99 | 0.00 |
February | 0.00 | 0.00 | 0.104239E+12 | 0.100775E+12 | 54324.58 | 07-FEB-16:20 | 49944.43 | 0.00 |
March | 0.00 | 0.00 | 0.169300E+12 | 0.165624E+12 | 83011.44 | 31-MAR-23:10 | 78712.91 | 0.00 |
April | 0.00 | 0.00 | 0.217272E+12 | 0.211953E+12 | 92554.48 | 27-APR-16:00 | 89478.15 | 0.00 |
May | 0.00 | 0.00 | 0.858760E+11 | 0.792757E+11 | 50469.81 | 31-MAY-23:02 | 46642.30 | 0.00 |
June | 0.00 | 0.00 | 0.135987E+12 | 0.125004E+12 | 71749.57 | 30-JUN-23:01 | 64404.34 | 0.00 |
July | 0.00 | 0.00 | 0.192438E+12 | 0.178462E+12 | 91791.80 | 31-JUL-23:02 | 82963.08 | 0.00 |
August | 0.00 | 0.00 | 0.242776E+12 | 0.227471E+12 | 99416.75 | 22-AUG-16:00 | 90089.57 | 0.00 |
September | 0.00 | 0.00 | 0.892322E+11 | 0.772533E+11 | 54885.12 | 30-SEP-23:02 | 45788.95 | 0.00 |
October | 0.00 | 0.00 | 0.135090E+12 | 0.125794E+12 | 66325.75 | 31-OCT-23:31 | 63340.86 | 0.00 |
November | 0.00 | 0.00 | 0.169827E+12 | 0.163539E+12 | 75859.19 | 01-NOV-16:00 | 69667.72 | 0.00 |
December | 0.00 | 0.00 | 0.214057E+12 | 0.209352E+12 | 91407.89 | 05-DEC-17:00 | 85939.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.181778E+13 | 0.172377E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.616866E+11 | 0.592643E+11 | 32791.61 | 29738.99 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.242776E+12 | 0.227471E+12 | 99416.75 | 90089.57 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HP COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.558448E+10 | 0.534709E+10 | 3389.34 | 24-JAN-17:00 | 3082.86 | 0.00 |
February | 0.00 | 0.00 | 0.101183E+11 | 0.977338E+10 | 5624.16 | 07-FEB-16:10 | 5185.03 | 0.00 |
March | 0.00 | 0.00 | 0.168194E+11 | 0.164524E+11 | 8216.64 | 31-MAR-23:10 | 7787.66 | 0.00 |
April | 0.00 | 0.00 | 0.218658E+11 | 0.213348E+11 | 9522.65 | 27-APR-16:00 | 9215.76 | 0.00 |
May | 0.00 | 0.00 | 0.892365E+10 | 0.825968E+10 | 5153.23 | 31-MAY-23:02 | 4772.90 | 0.00 |
June | 0.00 | 0.00 | 0.139721E+11 | 0.128710E+11 | 7242.91 | 30-JUN-23:01 | 6510.98 | 0.00 |
July | 0.00 | 0.00 | 0.197063E+11 | 0.183070E+11 | 9237.58 | 31-JUL-23:02 | 8394.13 | 0.00 |
August | 0.00 | 0.00 | 0.247054E+11 | 0.231787E+11 | 10239.87 | 10-AUG-16:00 | 9444.40 | 0.00 |
September | 0.00 | 0.00 | 0.925236E+10 | 0.804799E+10 | 5574.81 | 30-SEP-23:02 | 4674.23 | 0.00 |
October | 0.00 | 0.00 | 0.137109E+11 | 0.127804E+11 | 6636.94 | 31-OCT-23:31 | 6337.20 | 0.00 |
November | 0.00 | 0.00 | 0.169151E+11 | 0.162869E+11 | 7785.75 | 01-NOV-15:10 | 7149.07 | 0.00 |
December | 0.00 | 0.00 | 0.210020E+11 | 0.205326E+11 | 9274.24 | 05-DEC-17:00 | 8732.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.182576E+12 | 0.173172E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.558448E+10 | 0.534709E+10 | 3389.34 | 3082.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.247054E+11 | 0.231787E+11 | 10239.87 | 9444.40 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 525562.19 | 2513755.55 | 30-JAN-06:06 | 2756.44 | 430459.18 | 16-JAN-11:53 |
February | 714086.48 | 3216738.25 | 09-FEB-05:14 | 1344.85 | 360869.23 | 07-FEB-22:06 |
March | 946595.88 | 3644700.69 | 29-MAR-04:14 | 879.99 | 267823.06 | 28-MAR-03:36 |
April | 1211668.75 | 3522969.57 | 12-APR-04:14 | 451.37 | 187429.51 | 29-APR-18:18 |
May | 1213050.56 | 4656307.88 | 24-MAY-03:04 | 15759.58 | 668710.65 | 23-MAY-21:10 |
June | 1600675.29 | 4549581.64 | 27-JUN-03:04 | 8255.92 | 583913.86 | 18-JUN-20:28 |
July | 1899788.48 | 4501609.93 | 19-JUL-05:04 | 3743.78 | 474753.23 | 02-JUL-09:57 |
August | 2115796.75 | 4238446.50 | 08-AUG-01:01 | 764.17 | 390875.75 | 31-AUG-23:47 |
September | 1510433.30 | 4962316.62 | 22-SEP-04:01 | 18059.48 | 711304.82 | 28-SEP-21:10 |
October | 1276039.20 | 5612679.30 | 07-OCT-05:03 | 4717.08 | 590908.11 | 06-OCT-21:08 |
November | 1111410.35 | 3419758.75 | 10-NOV-05:14 | 1426.53 | 359163.83 | 02-NOV-21:08 |
December | 953882.53 | 3073293.11 | 11-DEC-05:14 | 113.50 | 147312.69 | 10-DEC-11:06 |
Annual Sum or Average | 1259923.93 | 4860.89 | ||||
Minimum of Months | 525562.19 | 2513755.55 | 113.50 | 147312.69 | ||
Maximum of Months | 2115796.75 | 5612679.30 | 18059.48 | 711304.82 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 568585.94 | 5255253.78 | 30-JAN-06:02 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 757393.18 | 5949651.76 | 09-FEB-06:02 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 989026.06 | 5904705.79 | 29-MAR-04:11 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1245727.78 | 5961537.96 | 17-APR-05:02 | 0.00 | 0.00 | 01-APR-00:10 |
May | 1218281.82 | 8041310.37 | 24-MAY-03:01 | 0.00 | 0.00 | 01-MAY-00:02 |
June | 1604704.62 | 7026782.48 | 20-JUN-03:01 | 0.00 | 0.00 | 01-JUN-00:02 |
July | 1908847.13 | 6801899.24 | 18-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:02 |
August | 2122559.74 | 6587637.28 | 22-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:02 |
September | 1510692.06 | 8074956.76 | 23-SEP-03:01 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 1289642.59 | 6833987.95 | 07-OCT-03:01 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 1142351.33 | 6053196.85 | 02-NOV-04:11 | 0.00 | 0.00 | 01-NOV-00:02 |
December | 1001815.14 | 5612351.09 | 12-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 1283213.13 | 0.00 | ||||
Minimum of Months | 568585.94 | 5255253.78 | 0.00 | 0.00 | ||
Maximum of Months | 2122559.74 | 8074956.76 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 10346.39 | 36784.48 | 12-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 10124.80 | 36400.60 | 01-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 10018.70 | 34668.95 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 8455.30 | 31368.94 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 7809.90 | 28236.45 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 7301.11 | 25319.76 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 6511.33 | 23922.97 | 31-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 7451.38 | 25781.71 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 7703.11 | 28649.07 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 8617.10 | 32224.28 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 9648.27 | 35051.81 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9909.48 | 36590.09 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 8650.19 | ||||
Minimum of Months | 0.00 | 0.00 | 6511.33 | 23922.97 | ||
Maximum of Months | 0.00 | 0.00 | 10346.39 | 36784.48 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 671469.21 | 3594810.33 | 30-JAN-06:06 | 104.87 | 75222.09 | 03-JAN-03:30 |
February | 986355.12 | 6453681.76 | 07-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 1351161.40 | 6157505.86 | 29-MAR-10:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 2147187.08 | 8987685.79 | 30-APR-18:13 | 0.00 | 0.00 | 01-APR-00:10 |
May | 3031916.82 | 10557684.93 | 31-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:02 |
June | 5158938.94 | 10850241.06 | 08-JUN-14:05 | 0.00 | 0.00 | 01-JUN-00:02 |
July | 6645272.23 | 11808691.46 | 19-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:02 |
August | 7564616.75 | 12137564.73 | 10-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:02 |
September | 5184457.39 | 11240746.50 | 07-SEP-14:05 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 3530301.98 | 10443266.73 | 08-OCT-06:52 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2154284.91 | 10150315.75 | 01-NOV-14:05 | 0.00 | 0.00 | 01-NOV-00:02 |
December | 1370656.56 | 6750134.63 | 05-DEC-15:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 3331756.81 | 8.91 | ||||
Minimum of Months | 671469.21 | 3594810.33 | 0.00 | 0.00 | ||
Maximum of Months | 7564616.75 | 12137564.73 | 104.87 | 75222.09 |
Report: FanReportMonthly
For: CORE_BOTTOM PIU FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PERIMETER_BOT_ZN_3 PIU FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 2288397.99 | 0.00 | 1386.91 | 20-JAN-06:10 | 0.60 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 2288397.99 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2288397.99 | 0.00 | 1386.91 | 0.60 |
Report: FanReportMonthly
For: PERIMETER_BOT_ZN_2 PIU FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 25113588.36 | 0.00 | 1221.48 | 02-JAN-06:35 | 0.60 |
February | 11518537.85 | 0.00 | 1221.48 | 01-FEB-06:06 | 0.60 |
March | 2320808.26 | 0.00 | 1221.48 | 04-MAR-06:38 | 0.60 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 |
December | 7292223.86 | 0.00 | 1221.48 | 13-DEC-06:50 | 0.60 |
Annual Sum or Average | 46245158.33 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25113588.36 | 0.00 | 1221.48 | 0.60 |
Report: FanReportMonthly
For: PERIMETER_BOT_ZN_1 PIU FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 28014239.98 | 0.00 | 1610.01 | 02-JAN-06:38 | 0.60 |
February | 4459738.20 | 0.00 | 1610.01 | 01-FEB-06:10 | 0.60 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 |
December | 563504.83 | 0.00 | 1610.01 | 30-DEC-06:47 | 0.60 |
Annual Sum or Average | 33037483.01 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28014239.98 | 0.00 | 1610.01 | 0.60 |
Report: FanReportMonthly
For: PERIMETER_BOT_ZN_4 PIU FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 22348383.39 | 0.00 | 1556.29 | 02-JAN-07:00 | 0.60 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 22348383.39 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22348383.39 | 0.00 | 1556.29 | 0.60 |
Report: FanReportMonthly
For: CORE_MID PIU FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PERIMETER_MID_ZN_3 PIU FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.119953E+10 | 0.02 | 13893.04 | 02-JAN-06:03 | 0.60 |
February | 0.626576E+09 | 0.01 | 13893.04 | 01-FEB-06:06 | 0.60 |
March | 0.195475E+09 | 0.00 | 13893.04 | 04-MAR-06:10 | 0.60 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 |
December | 0.568364E+09 | 0.01 | 13893.04 | 08-DEC-06:43 | 0.60 |
Annual Sum or Average | 0.258994E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119953E+10 | 0.02 | 13893.04 | 0.60 |
Report: FanReportMonthly
For: PERIMETER_MID_ZN_2 PIU FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136233E+10 | 0.02 | 12501.87 | 02-JAN-05:20 | 0.60 |
February | 0.734181E+09 | 0.01 | 12501.87 | 01-FEB-06:04 | 0.60 |
March | 0.382182E+09 | 0.01 | 12501.87 | 03-MAR-06:35 | 0.60 |
April | 58633771.33 | 0.00 | 12501.87 | 01-APR-05:10 | 0.60 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 24628684.33 | 0.00 | 12501.87 | 22-NOV-06:07 | 0.60 |
December | 0.783742E+09 | 0.01 | 12501.87 | 01-DEC-06:10 | 0.60 |
Annual Sum or Average | 0.334570E+10 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136233E+10 | 0.02 | 12501.87 | 0.60 |
Report: FanReportMonthly
For: PERIMETER_MID_ZN_1 PIU FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.977525E+09 | 0.01 | 15920.60 | 02-JAN-06:05 | 0.60 |
February | 0.646376E+09 | 0.01 | 15920.60 | 01-FEB-06:06 | 0.60 |
March | 0.255048E+09 | 0.00 | 15920.60 | 04-MAR-06:10 | 0.60 |
April | 12736478.53 | 0.00 | 15920.60 | 05-APR-05:47 | 0.60 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 7960299.08 | 0.00 | 15920.60 | 22-NOV-06:13 | 0.60 |
December | 0.475071E+09 | 0.01 | 15920.60 | 08-DEC-06:13 | 0.60 |
Annual Sum or Average | 0.237472E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.977525E+09 | 0.01 | 15920.60 | 0.60 |
Report: FanReportMonthly
For: PERIMETER_MID_ZN_4 PIU FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.214543E+10 | 0.03 | 14123.06 | 02-JAN-05:40 | 0.60 |
February | 0.105923E+10 | 0.02 | 14123.06 | 01-FEB-06:04 | 0.60 |
March | 0.531733E+09 | 0.01 | 14123.06 | 03-MAR-06:40 | 0.60 |
April | 76264517.57 | 0.00 | 14123.06 | 01-APR-05:38 | 0.60 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 48300861.13 | 0.00 | 14123.06 | 22-NOV-06:07 | 0.60 |
December | 0.106064E+10 | 0.02 | 14123.06 | 01-DEC-06:10 | 0.60 |
Annual Sum or Average | 0.492160E+10 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.214543E+10 | 0.03 | 14123.06 | 0.60 |
Report: FanReportMonthly
For: CORE_TOP PIU FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PERIMETER_TOP_ZN_3 PIU FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.528158E+09 | 0.07 | 1643.87 | 02-JAN-05:20 | 0.60 |
February | 0.299759E+09 | 0.05 | 1643.87 | 01-FEB-06:02 | 0.60 |
March | 0.184393E+09 | 0.03 | 1643.87 | 03-MAR-06:35 | 0.60 |
April | 33107490.95 | 0.00 | 1643.87 | 01-APR-05:10 | 0.60 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 32992420.23 | 0.00 | 1643.87 | 22-NOV-06:07 | 0.60 |
December | 0.342911E+09 | 0.05 | 1643.87 | 01-DEC-06:07 | 0.60 |
Annual Sum or Average | 0.142132E+10 | 0.02 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.528158E+09 | 0.07 | 1643.87 | 0.60 |
Report: FanReportMonthly
For: PERIMETER_TOP_ZN_2 PIU FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.383027E+09 | 0.07 | 1320.60 | 02-JAN-05:12 | 0.60 |
February | 0.219827E+09 | 0.04 | 1320.60 | 01-FEB-06:02 | 0.60 |
March | 0.146837E+09 | 0.03 | 1320.60 | 03-MAR-06:08 | 0.60 |
April | 33477187.99 | 0.01 | 1320.60 | 01-APR-05:08 | 0.60 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 25210237.42 | 0.00 | 1320.60 | 16-NOV-06:10 | 0.60 |
December | 0.241155E+09 | 0.04 | 1320.60 | 01-DEC-06:07 | 0.60 |
Annual Sum or Average | 0.104953E+10 | 0.02 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.383027E+09 | 0.07 | 1320.60 | 0.60 |
Report: FanReportMonthly
For: PERIMETER_TOP_ZN_1 PIU FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.403216E+09 | 0.05 | 1835.72 | 02-JAN-06:03 | 0.60 |
February | 0.273100E+09 | 0.04 | 1835.72 | 01-FEB-06:02 | 0.60 |
March | 0.206004E+09 | 0.03 | 1835.72 | 03-MAR-06:10 | 0.60 |
April | 45452425.07 | 0.01 | 1835.72 | 01-APR-05:10 | 0.60 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 23350357.31 | 0.00 | 1835.72 | 22-NOV-06:07 | 0.60 |
December | 0.265739E+09 | 0.03 | 1835.72 | 01-DEC-06:07 | 0.60 |
Annual Sum or Average | 0.121686E+10 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.403216E+09 | 0.05 | 1835.72 | 0.60 |
Report: FanReportMonthly
For: PERIMETER_TOP_ZN_4 PIU FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.613116E+09 | 0.09 | 1574.60 | 02-JAN-06:03 | 0.60 |
February | 0.370691E+09 | 0.06 | 1574.60 | 01-FEB-06:02 | 0.60 |
March | 0.238504E+09 | 0.03 | 1574.60 | 02-MAR-21:57 | 0.60 |
April | 62747665.76 | 0.01 | 1574.60 | 01-APR-05:08 | 0.60 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 787298.19 | 0.00 | 1574.60 | 21-OCT-06:30 | 0.60 |
November | 62731919.80 | 0.01 | 1574.60 | 04-NOV-06:30 | 0.60 |
December | 0.398735E+09 | 0.06 | 1574.60 | 01-DEC-06:07 | 0.60 |
Annual Sum or Average | 0.174731E+10 | 0.02 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.613116E+09 | 0.09 | 1574.60 | 0.60 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116318E+11 | 0.56 | 16900.89 | 02-JAN-05:12 | 1.38 |
February | 0.118554E+11 | 0.59 | 22598.07 | 06-FEB-05:11 | 1.56 |
March | 0.159031E+11 | 0.67 | 26019.03 | 27-MAR-04:11 | 1.66 |
April | 0.172806E+11 | 0.74 | 25144.94 | 29-APR-05:02 | 1.63 |
May | 0.188903E+11 | 0.76 | 30422.51 | 23-MAY-05:02 | 1.77 |
June | 0.206677E+11 | 0.85 | 30422.51 | 27-JUN-03:01 | 1.76 |
July | 0.224419E+11 | 0.89 | 30363.61 | 27-JUL-05:02 | 1.77 |
August | 0.255183E+11 | 0.96 | 30422.51 | 17-AUG-05:02 | 1.77 |
September | 0.190981E+11 | 0.79 | 30422.51 | 08-SEP-05:02 | 1.77 |
October | 0.188270E+11 | 0.76 | 30422.51 | 02-OCT-03:01 | 1.76 |
November | 0.166973E+11 | 0.69 | 23346.11 | 04-NOV-04:11 | 1.58 |
December | 0.143266E+11 | 0.62 | 21388.01 | 11-DEC-05:11 | 1.52 |
Annual Sum or Average | 0.213138E+12 | 0.74 | |||
Minimum of Months | 0.116318E+11 | 0.56 | 16900.89 | 1.38 | |
Maximum of Months | 0.255183E+11 | 0.96 | 30422.51 | 1.77 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.930612E+11 | 0.51 | 163869.91 | 03-JAN-06:02 | 1.40 |
February | 0.914791E+11 | 0.53 | 163869.91 | 03-FEB-06:03 | 1.39 |
March | 0.120655E+12 | 0.60 | 222004.78 | 02-MAR-04:01 | 1.59 |
April | 0.127999E+12 | 0.62 | 286785.37 | 29-APR-05:02 | 1.78 |
May | 0.170769E+12 | 0.73 | 286785.37 | 05-MAY-03:01 | 1.78 |
June | 0.180141E+12 | 0.78 | 286785.37 | 02-JUN-03:01 | 1.77 |
July | 0.185985E+12 | 0.81 | 286785.37 | 06-JUL-03:01 | 1.77 |
August | 0.205296E+12 | 0.85 | 286785.37 | 22-AUG-03:01 | 1.77 |
September | 0.170440E+12 | 0.74 | 286785.37 | 01-SEP-05:02 | 1.77 |
October | 0.156142E+12 | 0.67 | 286785.37 | 02-OCT-03:01 | 1.77 |
November | 0.126241E+12 | 0.60 | 205335.44 | 20-NOV-06:02 | 1.54 |
December | 0.996187E+11 | 0.53 | 163869.91 | 02-DEC-05:11 | 1.40 |
Annual Sum or Average | 0.172783E+13 | 0.67 | |||
Minimum of Months | 0.914791E+11 | 0.51 | 163869.91 | 1.39 | |
Maximum of Months | 0.205296E+12 | 0.85 | 286785.37 | 1.78 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.829074E+10 | 0.44 | 12634.79 | 30-JAN-06:02 | 1.12 |
February | 0.847184E+10 | 0.46 | 17826.98 | 06-FEB-06:02 | 1.30 |
March | 0.115107E+11 | 0.52 | 19647.12 | 28-MAR-05:02 | 1.36 |
April | 0.128515E+11 | 0.56 | 24812.91 | 29-APR-05:02 | 1.50 |
May | 0.180175E+11 | 0.67 | 35286.26 | 08-MAY-03:01 | 1.74 |
June | 0.193231E+11 | 0.72 | 36169.96 | 09-JUN-05:02 | 1.76 |
July | 0.203856E+11 | 0.76 | 36169.96 | 06-JUL-03:01 | 1.75 |
August | 0.220990E+11 | 0.79 | 36169.96 | 05-AUG-05:02 | 1.76 |
September | 0.177544E+11 | 0.68 | 36169.96 | 09-SEP-03:01 | 1.75 |
October | 0.153980E+11 | 0.60 | 34137.98 | 05-OCT-03:01 | 1.71 |
November | 0.116454E+11 | 0.52 | 21215.07 | 25-NOV-06:02 | 1.40 |
December | 0.892951E+10 | 0.45 | 17826.98 | 06-DEC-06:02 | 1.30 |
Annual Sum or Average | 0.174677E+12 | 0.60 | |||
Minimum of Months | 0.829074E+10 | 0.44 | 12634.79 | 1.12 | |
Maximum of Months | 0.220990E+11 | 0.79 | 36169.96 | 1.76 |
Report: FanReportMonthly
For: CAV_BAS SZVAV FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.673060E+10 | 0.57 | 16903.55 | 02-JAN-05:12 | 1.79 |
February | 0.597972E+10 | 0.57 | 16903.55 | 01-FEB-05:12 | 1.79 |
March | 0.686384E+10 | 0.59 | 16903.55 | 01-MAR-04:01 | 1.79 |
April | 0.620172E+10 | 0.56 | 16903.55 | 01-APR-04:11 | 1.79 |
May | 0.646964E+10 | 0.58 | 16903.55 | 01-MAY-04:11 | 1.78 |
June | 0.649431E+10 | 0.59 | 16903.55 | 01-JUN-03:01 | 1.79 |
July | 0.677124E+10 | 0.58 | 16903.55 | 01-JUL-03:01 | 1.78 |
August | 0.786021E+10 | 0.65 | 16903.55 | 01-AUG-03:02 | 1.79 |
September | 0.715502E+10 | 0.62 | 16903.55 | 01-SEP-03:01 | 1.79 |
October | 0.792702E+10 | 0.64 | 16903.55 | 01-OCT-13:40 | 1.78 |
November | 0.798304E+10 | 0.65 | 16903.55 | 01-NOV-03:01 | 1.78 |
December | 0.747209E+10 | 0.61 | 16903.55 | 01-DEC-05:11 | 1.79 |
Annual Sum or Average | 0.839085E+11 | 0.60 | |||
Minimum of Months | 0.597972E+10 | 0.56 | 16903.55 | 1.78 | |
Maximum of Months | 0.798304E+10 | 0.65 | 16903.55 | 1.79 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SYS11 FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.264714E+11 | 0.51 | 9883.29 | 01-JAN-00:05 | 0.51 |
February | 0.239097E+11 | 0.51 | 9883.29 | 01-FEB-00:10 | 0.51 |
March | 0.397031E+11 | 0.60 | 23839.91 | 31-MAR-24:00 | 0.73 |
April | 0.633110E+11 | 0.74 | 32917.40 | 02-APR-14:01 | 0.85 |
May | 0.264714E+11 | 0.50 | 9883.29 | 01-MAY-00:02 | 0.50 |
June | 0.256334E+11 | 0.50 | 14308.94 | 30-JUN-23:55 | 0.59 |
July | 0.398211E+11 | 0.60 | 23920.76 | 31-JUL-23:52 | 0.73 |
August | 0.660446E+11 | 0.74 | 32917.40 | 06-AUG-14:12 | 0.84 |
September | 0.256175E+11 | 0.50 | 9883.29 | 01-SEP-00:03 | 0.50 |
October | 0.264878E+11 | 0.50 | 14450.70 | 31-OCT-23:55 | 0.59 |
November | 0.388273E+11 | 0.60 | 15383.56 | 07-NOV-17:00 | 0.61 |
December | 0.661433E+11 | 0.74 | 32917.40 | 30-DEC-18:14 | 0.85 |
Annual Sum or Average | 0.468441E+12 | 0.59 | |||
Minimum of Months | 0.239097E+11 | 0.50 | 9883.29 | 0.50 | |
Maximum of Months | 0.661433E+11 | 0.74 | 32917.40 | 0.85 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.330727E+10 | 1.40 | 1234.79 | 01-JAN-00:05 | 1.40 |
February | 0.298721E+10 | 1.40 | 1234.79 | 01-FEB-00:10 | 1.40 |
March | 0.330727E+10 | 1.40 | 1234.79 | 01-MAR-00:40 | 1.40 |
April | 0.320058E+10 | 1.40 | 1234.79 | 01-APR-00:30 | 1.40 |
May | 0.330727E+10 | 1.40 | 1234.79 | 01-MAY-00:04 | 1.40 |
June | 0.320058E+10 | 1.40 | 1234.79 | 01-JUN-00:06 | 1.40 |
July | 0.330727E+10 | 1.40 | 1234.79 | 01-JUL-00:20 | 1.40 |
August | 0.330727E+10 | 1.40 | 1234.79 | 05-AUG-16:14 | 1.40 |
September | 0.320058E+10 | 1.40 | 1234.79 | 01-SEP-00:08 | 1.40 |
October | 0.330727E+10 | 1.40 | 1234.79 | 01-OCT-00:30 | 1.40 |
November | 0.320058E+10 | 1.40 | 1234.79 | 01-NOV-00:06 | 1.40 |
December | 0.330727E+10 | 1.40 | 1234.79 | 01-DEC-00:40 | 1.40 |
Annual Sum or Average | 0.389404E+11 | 1.40 | |||
Minimum of Months | 0.298721E+10 | 1.40 | 1234.79 | 1.40 | |
Maximum of Months | 0.330727E+10 | 1.40 | 1234.79 | 1.40 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.314878E+11 | 1.40 | 11756.21 | 01-JAN-01:25 | 1.40 |
February | 0.284406E+11 | 1.40 | 11756.21 | 02-FEB-21:42 | 1.40 |
March | 0.314878E+11 | 1.40 | 11756.21 | 01-MAR-02:30 | 1.40 |
April | 0.304721E+11 | 1.40 | 11756.21 | 01-APR-09:30 | 1.40 |
May | 0.314878E+11 | 1.40 | 11756.21 | 01-MAY-22:30 | 1.40 |
June | 0.304721E+11 | 1.40 | 11756.21 | 01-JUN-17:20 | 1.40 |
July | 0.314878E+11 | 1.40 | 11756.21 | 01-JUL-00:45 | 1.40 |
August | 0.314878E+11 | 1.40 | 11756.21 | 01-AUG-00:25 | 1.40 |
September | 0.304721E+11 | 1.40 | 11756.21 | 01-SEP-04:58 | 1.40 |
October | 0.314878E+11 | 1.40 | 11756.21 | 03-OCT-12:50 | 1.40 |
November | 0.304721E+11 | 1.40 | 11756.21 | 01-NOV-03:20 | 1.40 |
December | 0.314878E+11 | 1.40 | 11756.21 | 01-DEC-07:20 | 1.40 |
Annual Sum or Average | 0.370744E+12 | 1.40 | |||
Minimum of Months | 0.284406E+11 | 1.40 | 11756.21 | 1.40 | |
Maximum of Months | 0.314878E+11 | 1.40 | 11756.21 | 1.40 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.331893E+10 | 1.40 | 1239.15 | 01-JAN-02:65 | 1.40 |
February | 0.299775E+10 | 1.40 | 1239.15 | 02-FEB-00:20 | 1.40 |
March | 0.331893E+10 | 1.40 | 1239.15 | 01-MAR-03:00 | 1.40 |
April | 0.321187E+10 | 1.40 | 1239.15 | 01-APR-03:00 | 1.40 |
May | 0.331893E+10 | 1.40 | 1239.15 | 01-MAY-01:25 | 1.40 |
June | 0.321187E+10 | 1.40 | 1239.15 | 01-JUN-14:00 | 1.40 |
July | 0.331893E+10 | 1.40 | 1239.15 | 01-JUL-17:45 | 1.40 |
August | 0.331893E+10 | 1.40 | 1239.15 | 01-AUG-01:25 | 1.40 |
September | 0.321187E+10 | 1.40 | 1239.15 | 01-SEP-00:24 | 1.40 |
October | 0.331893E+10 | 1.40 | 1239.15 | 01-OCT-13:16 | 1.40 |
November | 0.321187E+10 | 1.40 | 1239.15 | 02-NOV-05:30 | 1.40 |
December | 0.331893E+10 | 1.40 | 1239.15 | 01-DEC-11:20 | 1.40 |
Annual Sum or Average | 0.390778E+11 | 1.40 | |||
Minimum of Months | 0.299775E+10 | 1.40 | 1239.15 | 1.40 | |
Maximum of Months | 0.331893E+10 | 1.40 | 1239.15 | 1.40 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.401239E+10 | 0.361115E+10 | 21873.58 | 30-JAN-06:02 | 19686.22 | 19686.22 | 10.79 | 125.70 |
February | 0.468444E+10 | 0.421600E+10 | 26201.62 | 24-FEB-06:02 | 23581.46 | 23581.46 | 10.56 | 137.56 |
March | 0.717354E+10 | 0.645619E+10 | 29087.22 | 14-MAR-05:02 | 26178.50 | 26178.50 | 10.60 | 144.59 |
April | 0.851209E+10 | 0.766088E+10 | 30808.86 | 29-APR-05:02 | 27727.98 | 27727.98 | 10.42 | 148.56 |
May | 0.764785E+10 | 0.688307E+10 | 25355.80 | 05-MAY-03:01 | 22820.22 | 22820.22 | 11.07 | 135.36 |
June | 0.937589E+10 | 0.843830E+10 | 26407.48 | 27-JUN-03:01 | 23766.74 | 23766.74 | 11.09 | 138.07 |
July | 0.116906E+11 | 0.105215E+11 | 28404.94 | 18-JUL-05:02 | 25564.45 | 25564.45 | 11.14 | 142.97 |
August | 0.132921E+11 | 0.119629E+11 | 28601.95 | 22-AUG-05:02 | 25741.75 | 25741.75 | 10.16 | 143.46 |
September | 0.864862E+10 | 0.778376E+10 | 24988.96 | 28-SEP-03:01 | 22490.06 | 22490.06 | 11.56 | 134.39 |
October | 0.799505E+10 | 0.719554E+10 | 26871.50 | 20-OCT-04:11 | 24184.35 | 24184.35 | 10.80 | 139.24 |
November | 0.727301E+10 | 0.654571E+10 | 28580.21 | 02-NOV-04:11 | 25722.19 | 25722.19 | 10.57 | 143.40 |
December | 0.709239E+10 | 0.638315E+10 | 29439.77 | 11-DEC-06:02 | 26495.79 | 26495.79 | 9.92 | 145.42 |
Annual Sum or Average | 0.973980E+11 | 0.876582E+11 | ||||||
Minimum of Months | 0.401239E+10 | 0.361115E+10 | 21873.58 | 19686.22 | 19686.22 | 9.92 | 125.70 | |
Maximum of Months | 0.132921E+11 | 0.119629E+11 | 30808.86 | 27727.98 | 27727.98 | 11.56 | 148.56 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.369564E+11 | 0.332608E+11 | 14130.68 | 01-JAN-00:05 | 12717.61 | 12717.61 | 10.20 | 74.28 |
February | 0.338197E+11 | 0.304377E+11 | 14130.68 | 01-FEB-00:10 | 12717.61 | 12717.61 | 10.47 | 74.28 |
March | 0.375095E+11 | 0.337586E+11 | 14130.68 | 01-MAR-00:10 | 12717.61 | 12717.61 | 10.75 | 74.28 |
April | 0.363944E+11 | 0.327549E+11 | 14130.68 | 01-APR-00:10 | 12717.61 | 12717.61 | 10.22 | 74.28 |
May | 0.351898E+11 | 0.316708E+11 | 14130.68 | 01-MAY-00:02 | 12717.61 | 12717.61 | 10.23 | 74.28 |
June | 0.351317E+11 | 0.316186E+11 | 14130.68 | 01-JUN-00:02 | 12717.61 | 12717.61 | 9.53 | 74.28 |
July | 0.368721E+11 | 0.331849E+11 | 14130.68 | 01-JUL-00:02 | 12717.61 | 12717.61 | 9.94 | 74.28 |
August | 0.375600E+11 | 0.338040E+11 | 14130.68 | 01-AUG-00:02 | 12717.61 | 12717.61 | 10.12 | 74.28 |
September | 0.337582E+11 | 0.303823E+11 | 14130.68 | 01-SEP-00:03 | 12717.61 | 12717.61 | 10.52 | 74.28 |
October | 0.368425E+11 | 0.331583E+11 | 14130.68 | 01-OCT-00:10 | 12717.61 | 12717.61 | 10.20 | 74.28 |
November | 0.361434E+11 | 0.325291E+11 | 14130.68 | 01-NOV-00:02 | 12717.61 | 12717.61 | 10.28 | 74.28 |
December | 0.377453E+11 | 0.339708E+11 | 14130.68 | 01-DEC-00:10 | 12717.61 | 12717.61 | 10.50 | 74.28 |
Annual Sum or Average | 0.433923E+12 | 0.390531E+12 | ||||||
Minimum of Months | 0.337582E+11 | 0.303823E+11 | 14130.68 | 12717.61 | 12717.61 | 9.53 | 74.28 | |
Maximum of Months | 0.377453E+11 | 0.339708E+11 | 14130.68 | 12717.61 | 12717.61 | 10.75 | 74.28 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 7206646.49 | 6485981.84 | 14130.68 | 03-JAN-06:04 | 12717.61 | 12717.61 | 13.26 | 37.14 |
February | 0.660145E+09 | 0.594130E+09 | 14130.68 | 06-FEB-05:13 | 12717.61 | 12717.61 | 13.80 | 37.14 |
March | 0.297640E+10 | 0.267876E+10 | 14130.68 | 01-MAR-05:03 | 12717.61 | 12717.61 | 13.35 | 37.14 |
April | 0.726185E+10 | 0.653566E+10 | 14130.68 | 01-APR-04:13 | 12717.61 | 12717.61 | 13.44 | 37.14 |
May | 0.986495E+10 | 0.887846E+10 | 14130.68 | 01-MAY-04:13 | 12717.61 | 12717.61 | 15.34 | 37.14 |
June | 0.162059E+11 | 0.145853E+11 | 14130.68 | 01-JUN-07:40 | 12717.61 | 12717.61 | 13.06 | 37.14 |
July | 0.207303E+11 | 0.186573E+11 | 14130.68 | 01-JUL-01:21 | 12717.61 | 12717.61 | 12.34 | 74.28 |
August | 0.239953E+11 | 0.215957E+11 | 14130.68 | 01-AUG-00:34 | 12717.61 | 12717.61 | 13.45 | 37.14 |
September | 0.150727E+11 | 0.135654E+11 | 14130.68 | 01-SEP-03:03 | 12717.61 | 12717.61 | 14.56 | 37.14 |
October | 0.107979E+11 | 0.971810E+10 | 14130.68 | 01-OCT-07:01 | 12717.61 | 12717.61 | 12.89 | 74.28 |
November | 0.719032E+10 | 0.647128E+10 | 14130.68 | 01-NOV-04:13 | 12717.61 | 12717.61 | 13.80 | 37.14 |
December | 0.233084E+10 | 0.209775E+10 | 14130.68 | 01-DEC-13:10 | 12717.61 | 12717.61 | 13.47 | 37.14 |
Annual Sum or Average | 0.117094E+12 | 0.105384E+12 | ||||||
Minimum of Months | 7206646.49 | 6485981.84 | 14130.68 | 12717.61 | 12717.61 | 12.34 | 37.14 | |
Maximum of Months | 0.239953E+11 | 0.215957E+11 | 14130.68 | 12717.61 | 12717.61 | 15.34 | 74.28 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 57.81 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 57.92 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 58.06 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 58.20 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 58.47 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:02 | 16.86 | 16.86 | 58.58 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 58.66 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 58.66 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 58.53 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 58.18 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 58.12 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 57.90 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 57.81 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 58.66 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.952057E+11 | 0.856852E+11 | 72929.53 | 30-JAN-06:06 | 65636.57 | 65636.57 | 25.21 | 209.29 |
February | 0.878128E+11 | 0.790316E+11 | 73129.66 | 07-FEB-16:00 | 65816.69 | 65816.69 | 28.48 | 209.29 |
March | 0.101958E+12 | 0.917626E+11 | 73108.88 | 29-MAR-10:10 | 65797.99 | 65797.99 | 28.14 | 209.29 |
April | 0.108436E+12 | 0.975922E+11 | 73189.09 | 28-APR-14:50 | 65870.19 | 65870.19 | 29.49 | 209.29 |
May | 0.111354E+12 | 0.100219E+12 | 73189.09 | 03-MAY-13:05 | 65870.19 | 65870.19 | 29.47 | 209.29 |
June | 0.128311E+12 | 0.115480E+12 | 73189.09 | 01-JUN-19:30 | 65870.19 | 65870.19 | 29.67 | 209.29 |
July | 0.146282E+12 | 0.131654E+12 | 73189.09 | 01-JUL-01:21 | 65870.19 | 65870.19 | 31.75 | 209.29 |
August | 0.157786E+12 | 0.142007E+12 | 73189.09 | 01-AUG-00:34 | 65870.19 | 65870.19 | 30.96 | 209.29 |
September | 0.121708E+12 | 0.109537E+12 | 73189.09 | 01-SEP-05:06 | 65870.19 | 65870.19 | 29.98 | 209.29 |
October | 0.119773E+12 | 0.107796E+12 | 73189.09 | 01-OCT-07:01 | 65870.19 | 65870.19 | 30.81 | 209.29 |
November | 0.106986E+12 | 0.962876E+11 | 73189.09 | 01-NOV-09:20 | 65870.19 | 65870.19 | 29.56 | 209.29 |
December | 0.100198E+12 | 0.901783E+11 | 73150.47 | 05-DEC-15:10 | 65835.42 | 65835.42 | 28.82 | 209.29 |
Annual Sum or Average | 0.138581E+13 | 0.124723E+13 | ||||||
Minimum of Months | 0.878128E+11 | 0.790316E+11 | 72929.53 | 65636.57 | 65636.57 | 25.21 | 209.29 | |
Maximum of Months | 0.157786E+12 | 0.142007E+12 | 73189.09 | 65870.19 | 65870.19 | 31.75 | 209.29 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 525562.19 | 2513755.55 | 30-JAN-06:06 | 10.74 | 6.70 | 2756.44 | 430459.18 | 16-JAN-11:53 |
February | 714086.48 | 3216738.25 | 09-FEB-05:14 | 11.87 | 6.70 | 1344.85 | 360869.23 | 07-FEB-22:06 |
March | 946595.88 | 3644700.69 | 29-MAR-04:14 | 12.56 | 6.70 | 879.99 | 267823.06 | 28-MAR-03:36 |
April | 1211668.75 | 3522969.57 | 12-APR-04:14 | 12.36 | 6.70 | 451.37 | 187429.51 | 29-APR-18:18 |
May | 1213050.56 | 4656307.88 | 24-MAY-03:04 | 14.19 | 7.44 | 15759.58 | 668710.65 | 23-MAY-21:10 |
June | 1600675.29 | 4549581.64 | 27-JUN-03:04 | 14.02 | 7.27 | 8255.92 | 583913.86 | 18-JUN-20:28 |
July | 1899788.48 | 4501609.93 | 19-JUL-05:04 | 13.94 | 7.19 | 3743.78 | 474753.23 | 02-JUL-09:57 |
August | 2115796.75 | 4238446.50 | 08-AUG-01:01 | 13.51 | 6.77 | 764.17 | 390875.75 | 31-AUG-23:47 |
September | 1510433.30 | 4962316.62 | 22-SEP-04:01 | 14.72 | 7.98 | 18059.48 | 711304.82 | 28-SEP-21:10 |
October | 1276039.20 | 5612679.30 | 07-OCT-05:03 | 15.73 | 8.98 | 4717.08 | 590908.11 | 06-OCT-21:08 |
November | 1111410.35 | 3419758.75 | 10-NOV-05:14 | 12.20 | 6.70 | 1426.53 | 359163.83 | 02-NOV-21:08 |
December | 953882.53 | 3073293.11 | 11-DEC-05:14 | 11.64 | 6.70 | 113.50 | 147312.69 | 10-DEC-11:06 |
Annual Sum or Average | 1259923.93 | 4860.89 | ||||||
Minimum of Months | 525562.19 | 2513755.55 | 10.74 | 6.70 | 113.50 | 147312.69 | ||
Maximum of Months | 2115796.75 | 5612679.30 | 15.73 | 8.98 | 18059.48 | 711304.82 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 568585.94 | 5255253.78 | 30-JAN-06:02 | 16.69 | 11.90 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 757393.18 | 5949651.76 | 09-FEB-06:02 | 17.07 | 12.51 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 989026.06 | 5904705.79 | 29-MAR-04:11 | 16.53 | 12.42 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1245727.78 | 5961537.96 | 17-APR-05:02 | 16.31 | 12.11 | 0.00 | 0.00 | 01-APR-00:10 |
May | 1218281.82 | 8041310.37 | 24-MAY-03:01 | 21.05 | 14.38 | 0.00 | 0.00 | 01-MAY-00:02 |
June | 1604704.62 | 7026782.48 | 20-JUN-03:01 | 18.88 | 13.41 | 0.00 | 0.00 | 01-JUN-00:02 |
July | 1908847.13 | 6801899.24 | 18-JUL-05:02 | 18.07 | 13.68 | 0.00 | 0.00 | 01-JUL-00:02 |
August | 2122559.74 | 6587637.28 | 22-AUG-05:02 | 17.68 | 12.54 | 0.00 | 0.00 | 01-AUG-00:02 |
September | 1510692.06 | 8074956.76 | 23-SEP-03:01 | 21.07 | 14.39 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 1289642.59 | 6833987.95 | 07-OCT-03:01 | 18.53 | 13.27 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 1142351.33 | 6053196.85 | 02-NOV-04:11 | 16.79 | 12.50 | 0.00 | 0.00 | 01-NOV-00:02 |
December | 1001815.14 | 5612351.09 | 12-DEC-06:02 | 15.93 | 11.66 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 1283213.13 | 0.00 | ||||||
Minimum of Months | 568585.94 | 5255253.78 | 15.93 | 11.66 | 0.00 | 0.00 | ||
Maximum of Months | 2122559.74 | 8074956.76 | 21.07 | 14.39 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 58.66 | 58.66 | 10346.39 | 36784.48 | 12-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 58.31 | 58.31 | 10124.80 | 36400.60 | 01-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58.40 | 58.40 | 10018.70 | 34668.95 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 58.54 | 58.54 | 8455.30 | 31368.94 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 58.98 | 58.98 | 7809.90 | 28236.45 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 58.85 | 58.85 | 7301.11 | 25319.76 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 58.92 | 58.92 | 6511.33 | 23922.97 | 31-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 58.91 | 58.91 | 7451.38 | 25781.71 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 58.82 | 58.82 | 7703.11 | 28649.07 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 58.68 | 58.68 | 8617.10 | 32224.28 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 58.51 | 58.51 | 9648.27 | 35051.81 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 58.38 | 58.38 | 9909.48 | 36590.09 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 8650.19 | ||||||
Minimum of Months | 0.00 | 0.00 | 58.31 | 58.31 | 6511.33 | 23922.97 | ||
Maximum of Months | 0.00 | 0.00 | 58.98 | 58.98 | 10346.39 | 36784.48 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 671469.21 | 3594810.33 | 30-JAN-06:06 | 25.21 | 21.48 | 104.87 | 75222.09 | 03-JAN-03:30 |
February | 986355.12 | 6453681.76 | 07-FEB-16:00 | 28.48 | 25.54 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 1351161.40 | 6157505.86 | 29-MAR-10:10 | 28.14 | 24.86 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 2147187.08 | 8987685.79 | 30-APR-18:13 | 31.37 | 27.60 | 0.00 | 0.00 | 01-APR-00:10 |
May | 3031916.82 | 10557684.93 | 31-MAY-16:00 | 33.17 | 29.20 | 0.00 | 0.00 | 01-MAY-00:02 |
June | 5158938.94 | 10850241.06 | 08-JUN-14:05 | 33.50 | 29.33 | 0.00 | 0.00 | 01-JUN-00:02 |
July | 6645272.23 | 11808691.46 | 19-JUL-15:00 | 34.60 | 29.74 | 0.00 | 0.00 | 01-JUL-00:02 |
August | 7564616.75 | 12137564.73 | 10-AUG-16:00 | 34.97 | 29.87 | 0.00 | 0.00 | 01-AUG-00:02 |
September | 5184457.39 | 11240746.50 | 07-SEP-14:05 | 33.95 | 29.50 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 3530301.98 | 10443266.73 | 08-OCT-06:52 | 33.04 | 28.96 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2154284.91 | 10150315.75 | 01-NOV-14:05 | 32.70 | 28.79 | 0.00 | 0.00 | 01-NOV-00:02 |
December | 1370656.56 | 6750134.63 | 05-DEC-15:10 | 28.82 | 25.66 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 3331756.81 | 8.91 | ||||||
Minimum of Months | 671469.21 | 3594810.33 | 25.21 | 21.48 | 0.00 | 0.00 | ||
Maximum of Months | 7564616.75 | 12137564.73 | 34.97 | 29.87 | 104.87 | 75222.09 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.104915E+12 | 0.117095E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.112725E+12 | 0.118714E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.154416E+12 | 0.159054E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.190962E+12 | 0.172806E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.239864E+12 | 0.188903E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.304663E+12 | 0.206677E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.366479E+12 | 0.224419E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.400050E+12 | 0.255183E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.298511E+12 | 0.190981E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.248347E+12 | 0.188270E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.184969E+12 | 0.166973E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.139306E+12 | 0.143345E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.274521E+13 | 0.213242E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.104915E+12 | 0.117095E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.400050E+12 | 0.255183E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.829400E+12 | 0.987516E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.892719E+12 | 0.945455E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.122709E+13 | 0.122019E+12 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.148640E+13 | 0.128146E+12 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.218709E+13 | 0.170769E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.271837E+13 | 0.180141E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.326427E+13 | 0.185985E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.350618E+13 | 0.205296E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.272878E+13 | 0.170440E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.211595E+13 | 0.156142E+12 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.150119E+13 | 0.126322E+12 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.101770E+13 | 0.102507E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.234751E+14 | 0.174106E+13 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.829400E+12 | 0.945455E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.350618E+13 | 0.205296E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.833646E+11 | 0.121882E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.943700E+11 | 0.105627E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.134215E+12 | 0.124891E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.168432E+12 | 0.130263E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.253441E+12 | 0.180175E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.309946E+12 | 0.193231E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.370574E+12 | 0.203856E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.393673E+12 | 0.220990E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.304294E+12 | 0.177544E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.231345E+12 | 0.153988E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.157674E+12 | 0.117920E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.103306E+12 | 0.109698E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.260463E+13 | 0.184006E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.833646E+11 | 0.105627E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.393673E+12 | 0.220990E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.760111E+11 | 0.673060E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.753168E+11 | 0.597972E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.915400E+11 | 0.686384E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.968317E+11 | 0.620172E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.122759E+12 | 0.646964E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.145321E+12 | 0.649431E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.163385E+12 | 0.677124E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.186674E+12 | 0.786021E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.154582E+12 | 0.715502E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.136571E+12 | 0.792702E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.117088E+12 | 0.798304E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.931014E+11 | 0.747209E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.145918E+13 | 0.839085E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.753168E+11 | 0.597972E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.186674E+12 | 0.798304E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.263010E+12 | 0.265264E+11 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.460117E+12 | 0.239097E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.772272E+12 | 0.397580E+11 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.101523E+13 | 0.633110E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.278159E+12 | 0.264714E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.522509E+12 | 0.256334E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.811605E+12 | 0.398211E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.108807E+13 | 0.660446E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.281464E+12 | 0.256175E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.535190E+12 | 0.264921E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.760152E+12 | 0.388273E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.104690E+13 | 0.661433E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.783468E+13 | 0.468556E+12 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.263010E+12 | 0.239097E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.108807E+13 | 0.661433E+11 | 0.00 | 0.02 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.560085E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.642681E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.852165E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.970180E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.658533E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.812871E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.101306E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.117602E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.661158E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.797265E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.850279E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.945565E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.993986E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.560085E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.117602E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.502688E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.585114E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.785058E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.900600E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.614237E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.759235E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.943762E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.109510E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.616267E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.741871E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.785593E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.867048E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.919657E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.502688E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.109510E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.509141E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.604705E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.820236E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.946676E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.654370E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.806323E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.100210E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.115058E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.656215E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.782834E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.821910E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.900777E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.965587E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.509141E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.115058E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.117095E+11 | 0.104915E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118714E+11 | 0.112725E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159054E+11 | 0.154416E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172806E+11 | 0.190962E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.188903E+11 | 0.239864E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.206677E+11 | 0.304663E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.224419E+11 | 0.366479E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.255183E+11 | 0.400050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.190981E+11 | 0.298511E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.188270E+11 | 0.248347E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166973E+11 | 0.184969E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143345E+11 | 0.139306E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213242E+12 | 0.274521E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117095E+11 | 0.104915E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.255183E+11 | 0.400050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.987461E+11 | 0.829400E+12 | 5564906.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.945455E+11 | 0.892719E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122019E+12 | 0.122709E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128146E+12 | 0.148640E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170769E+12 | 0.218709E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.180141E+12 | 0.271837E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.185985E+12 | 0.326427E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.205296E+12 | 0.350618E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170440E+12 | 0.272878E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156142E+12 | 0.211595E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126322E+12 | 0.150119E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102507E+12 | 0.101770E+13 | 102034.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174106E+13 | 0.234751E+14 | 5666940.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.945455E+11 | 0.829400E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.205296E+12 | 0.350618E+13 | 5564906.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.102183E+11 | 0.833646E+11 | 0.196990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.963521E+10 | 0.943700E+11 | 0.927531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122865E+11 | 0.134215E+12 | 0.202633E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130263E+11 | 0.168432E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180175E+11 | 0.253441E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.193231E+11 | 0.309946E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.203856E+11 | 0.370574E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.220990E+11 | 0.393673E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.177544E+11 | 0.304294E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153988E+11 | 0.231345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117897E+11 | 0.157674E+12 | 2274344.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101780E+11 | 0.103306E+12 | 0.791774E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180112E+12 | 0.260463E+13 | 0.389411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.963521E+10 | 0.833646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.220990E+11 | 0.393673E+12 | 0.196990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.673060E+10 | 0.760111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.597972E+10 | 0.753168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.686384E+10 | 0.915400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.620172E+10 | 0.968317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.646964E+10 | 0.122759E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.649431E+10 | 0.145321E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.677124E+10 | 0.163385E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.786021E+10 | 0.186674E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.715502E+10 | 0.154582E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.792702E+10 | 0.136571E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.798304E+10 | 0.117088E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.747209E+10 | 0.931014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.839085E+11 | 0.145918E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.597972E+10 | 0.753168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.798304E+10 | 0.186674E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.264714E+11 | 0.263010E+12 | 0.00 | 0.00 | 0.00 | 54730643.23 | 0.00 | 0.00 |
February | 0.239097E+11 | 0.460117E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.397031E+11 | 0.772272E+12 | 0.00 | 0.00 | 0.00 | 54604713.08 | 0.00 | 0.00 |
April | 0.633110E+11 | 0.101523E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.264714E+11 | 0.278159E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.256334E+11 | 0.522509E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.398211E+11 | 0.811605E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.660446E+11 | 0.108807E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.256175E+11 | 0.281464E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.264878E+11 | 0.535190E+12 | 0.00 | 0.00 | 0.00 | 4313977.16 | 0.00 | 0.00 |
November | 0.388273E+11 | 0.760152E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.661433E+11 | 0.104690E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.468441E+12 | 0.783468E+13 | 0.00 | 0.00 | 0.00 | 0.113649E+09 | 0.00 | 0.00 |
Minimum of Months | 0.239097E+11 | 0.263010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.661433E+11 | 0.108807E+13 | 0.00 | 0.00 | 0.00 | 54730643.23 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.330727E+10 | 0.736250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.298721E+10 | 0.116389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.330727E+10 | 0.182687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.320058E+10 | 0.229621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.330727E+10 | 0.910803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.320058E+10 | 0.142552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.330727E+10 | 0.201885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.330727E+10 | 0.254420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.320058E+10 | 0.945381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.330727E+10 | 0.142957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.320058E+10 | 0.181945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.330727E+10 | 0.232398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389404E+11 | 0.194410E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.298721E+10 | 0.736250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.330727E+10 | 0.254420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.314878E+11 | 0.616866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.284406E+11 | 0.104239E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.314878E+11 | 0.169300E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.304721E+11 | 0.217272E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.314878E+11 | 0.858760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.304721E+11 | 0.135987E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.314878E+11 | 0.192438E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.314878E+11 | 0.242776E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.304721E+11 | 0.892322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.314878E+11 | 0.135090E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.304721E+11 | 0.169827E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.314878E+11 | 0.214057E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370744E+12 | 0.181778E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.284406E+11 | 0.616866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.314878E+11 | 0.242776E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.331893E+10 | 0.558448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.299775E+10 | 0.101183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.331893E+10 | 0.168194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.321187E+10 | 0.218658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.331893E+10 | 0.892365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.321187E+10 | 0.139721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.331893E+10 | 0.197063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.331893E+10 | 0.247054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.321187E+10 | 0.925236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.331893E+10 | 0.137109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.321187E+10 | 0.169151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331893E+10 | 0.210020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.390778E+11 | 0.182576E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.299775E+10 | 0.558448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.331893E+10 | 0.247054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.117095E+11 | 0.00 | 0.104915E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118714E+11 | 0.00 | 0.112725E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159054E+11 | 0.00 | 0.154416E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172806E+11 | 0.00 | 0.190962E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.188903E+11 | 0.00 | 0.239864E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.206677E+11 | 0.00 | 0.304663E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.224419E+11 | 0.00 | 0.366479E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.255183E+11 | 0.00 | 0.400050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.190981E+11 | 0.00 | 0.298511E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.188270E+11 | 0.00 | 0.248347E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166973E+11 | 0.00 | 0.184969E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143345E+11 | 0.00 | 0.139306E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213242E+12 | 0.00 | 0.274521E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117095E+11 | 0.00 | 0.104915E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.255183E+11 | 0.00 | 0.400050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.987461E+11 | 0.00 | 0.829400E+12 | 0.00 | 0.00 | 5564906.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.945455E+11 | 0.00 | 0.892719E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122019E+12 | 0.00 | 0.122709E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128146E+12 | 0.00 | 0.148640E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170769E+12 | 0.00 | 0.218709E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.180141E+12 | 0.00 | 0.271837E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.185985E+12 | 0.00 | 0.326427E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.205296E+12 | 0.00 | 0.350618E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170440E+12 | 0.00 | 0.272878E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156142E+12 | 0.00 | 0.211595E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126322E+12 | 0.00 | 0.150119E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102507E+12 | 0.00 | 0.101770E+13 | 0.00 | 0.00 | 102034.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174106E+13 | 0.00 | 0.234751E+14 | 0.00 | 0.00 | 5666940.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.945455E+11 | 0.00 | 0.829400E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.205296E+12 | 0.00 | 0.350618E+13 | 0.00 | 0.00 | 5564906.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.102183E+11 | 0.00 | 0.833646E+11 | 0.00 | 0.00 | 0.196990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.963521E+10 | 0.00 | 0.943700E+11 | 0.00 | 0.00 | 0.927531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122865E+11 | 0.00 | 0.134215E+12 | 0.00 | 0.00 | 0.202633E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130263E+11 | 0.00 | 0.168432E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180175E+11 | 0.00 | 0.253441E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.193231E+11 | 0.00 | 0.309946E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.203856E+11 | 0.00 | 0.370574E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.220990E+11 | 0.00 | 0.393673E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.177544E+11 | 0.00 | 0.304294E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153988E+11 | 0.00 | 0.231345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117897E+11 | 0.00 | 0.157674E+12 | 0.00 | 0.00 | 2274344.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101780E+11 | 0.00 | 0.103306E+12 | 0.00 | 0.00 | 0.791774E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180112E+12 | 0.00 | 0.260463E+13 | 0.00 | 0.00 | 0.389411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.963521E+10 | 0.00 | 0.833646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.220990E+11 | 0.00 | 0.393673E+12 | 0.00 | 0.00 | 0.196990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.673060E+10 | 0.00 | 0.760111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.597972E+10 | 0.00 | 0.753168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.686384E+10 | 0.00 | 0.915400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.620172E+10 | 0.00 | 0.968317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.646964E+10 | 0.00 | 0.122759E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.649431E+10 | 0.00 | 0.145321E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.677124E+10 | 0.00 | 0.163385E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.786021E+10 | 0.00 | 0.186674E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.715502E+10 | 0.00 | 0.154582E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.792702E+10 | 0.00 | 0.136571E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.798304E+10 | 0.00 | 0.117088E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.747209E+10 | 0.00 | 0.931014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.839085E+11 | 0.00 | 0.145918E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.597972E+10 | 0.00 | 0.753168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.798304E+10 | 0.00 | 0.186674E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.264714E+11 | 0.00 | 0.263010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54977008.04 | 0.00 | 0.00 | 0.00 |
February | 0.239097E+11 | 0.00 | 0.460117E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.397031E+11 | 0.00 | 0.772272E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54850511.03 | 0.00 | 0.00 | 0.00 |
April | 0.633110E+11 | 0.00 | 0.101523E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.264714E+11 | 0.00 | 0.278159E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.256334E+11 | 0.00 | 0.522509E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.398211E+11 | 0.00 | 0.811605E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.660446E+11 | 0.00 | 0.108807E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.256175E+11 | 0.00 | 0.281464E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.264878E+11 | 0.00 | 0.535190E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4333396.12 | 0.00 | 0.00 | 0.00 |
November | 0.388273E+11 | 0.00 | 0.760152E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.661433E+11 | 0.00 | 0.104690E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.468441E+12 | 0.00 | 0.783468E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114161E+09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.239097E+11 | 0.00 | 0.263010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.661433E+11 | 0.00 | 0.108807E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54977008.04 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.330727E+10 | 0.00 | 0.00 | 0.00 | 0.229358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.298721E+10 | 0.00 | 0.00 | 0.00 | 0.343960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.330727E+10 | 0.00 | 0.00 | 0.00 | 0.521438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.320058E+10 | 0.00 | 0.00 | 0.00 | 0.650121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.330727E+10 | 0.00 | 0.00 | 0.00 | 0.327806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.320058E+10 | 0.00 | 0.00 | 0.00 | 0.492813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.330727E+10 | 0.00 | 0.00 | 0.00 | 0.682333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.330727E+10 | 0.00 | 0.00 | 0.00 | 0.845293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.320058E+10 | 0.00 | 0.00 | 0.00 | 0.341100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.330727E+10 | 0.00 | 0.00 | 0.00 | 0.466538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.320058E+10 | 0.00 | 0.00 | 0.00 | 0.530220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.330727E+10 | 0.00 | 0.00 | 0.00 | 0.614839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389404E+11 | 0.00 | 0.00 | 0.00 | 0.604582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.298721E+10 | 0.00 | 0.00 | 0.00 | 0.229358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.330727E+10 | 0.00 | 0.00 | 0.00 | 0.845293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.314878E+11 | 0.00 | 0.00 | 0.00 | 0.187810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.284406E+11 | 0.00 | 0.00 | 0.00 | 0.300708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.314878E+11 | 0.00 | 0.00 | 0.00 | 0.470180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.304721E+11 | 0.00 | 0.00 | 0.00 | 0.595879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.314878E+11 | 0.00 | 0.00 | 0.00 | 0.299359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.304721E+11 | 0.00 | 0.00 | 0.00 | 0.454514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.314878E+11 | 0.00 | 0.00 | 0.00 | 0.628884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.314878E+11 | 0.00 | 0.00 | 0.00 | 0.780222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.304721E+11 | 0.00 | 0.00 | 0.00 | 0.311546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.314878E+11 | 0.00 | 0.00 | 0.00 | 0.426993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.304721E+11 | 0.00 | 0.00 | 0.00 | 0.480872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.314878E+11 | 0.00 | 0.00 | 0.00 | 0.552169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370744E+12 | 0.00 | 0.00 | 0.00 | 0.548914E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.284406E+11 | 0.00 | 0.00 | 0.00 | 0.187810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.314878E+11 | 0.00 | 0.00 | 0.00 | 0.780222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.331893E+10 | 0.00 | 0.00 | 0.00 | 0.177248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.299775E+10 | 0.00 | 0.00 | 0.00 | 0.304930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.331893E+10 | 0.00 | 0.00 | 0.00 | 0.488343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.321187E+10 | 0.00 | 0.00 | 0.00 | 0.625489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.331893E+10 | 0.00 | 0.00 | 0.00 | 0.322477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.321187E+10 | 0.00 | 0.00 | 0.00 | 0.485136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.331893E+10 | 0.00 | 0.00 | 0.00 | 0.670207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.331893E+10 | 0.00 | 0.00 | 0.00 | 0.818689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.321187E+10 | 0.00 | 0.00 | 0.00 | 0.335027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.331893E+10 | 0.00 | 0.00 | 0.00 | 0.450941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.321187E+10 | 0.00 | 0.00 | 0.00 | 0.500723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331893E+10 | 0.00 | 0.00 | 0.00 | 0.568884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.390778E+11 | 0.00 | 0.00 | 0.00 | 0.574809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.299775E+10 | 0.00 | 0.00 | 0.00 | 0.177248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.331893E+10 | 0.00 | 0.00 | 0.00 | 0.818689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 42462838.60 | 0.190723E+10 | 0.00 | 0.159161E+09 | 9546948.68 | 0.00 | 0.917530E+10 | 0.00 | 0.35 |
February | 48225944.69 | 0.499150E+10 | 0.00 | 94047560.48 | 21728901.92 | 0.00 | 0.445533E+10 | 0.00 | 0.35 |
March | 25975881.30 | 0.866118E+10 | 0.00 | 96489575.09 | 61733952.65 | 0.00 | 0.382104E+10 | 0.00 | 0.37 |
April | 4083089.97 | 0.185890E+11 | 0.00 | 34539464.87 | 0.257744E+09 | 0.00 | 0.846939E+09 | 0.00 | 0.36 |
May | 13199.25 | 0.382480E+11 | 0.00 | 6100651.16 | 0.414951E+09 | 0.00 | 44886522.43 | 0.00 | 0.37 |
June | 0.00 | 0.598779E+11 | 0.00 | 0.00 | 0.649850E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.766366E+11 | 0.00 | 3210686.92 | 0.922679E+09 | 0.00 | 12654249.97 | 0.00 | 0.36 |
August | 0.00 | 0.884578E+11 | 0.00 | 0.00 | 0.914202E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.660485E+11 | 0.00 | 0.00 | 0.928625E+09 | 0.00 | 0.00 | 0.00 | 0.37 |
October | 0.00 | 0.420679E+11 | 0.00 | 8820791.22 | 0.482402E+09 | 0.00 | 0.126876E+09 | 0.00 | 0.36 |
November | 0.00 | 0.239836E+11 | 0.00 | 25395865.89 | 0.102892E+09 | 0.00 | 0.269032E+09 | 0.00 | 0.36 |
December | 35245708.85 | 0.743658E+10 | 0.00 | 0.109526E+09 | 0.132892E+09 | 0.00 | 0.384017E+10 | 0.00 | 0.35 |
Annual Sum or Average | 0.156007E+09 | 0.436906E+12 | 0.00 | 0.537292E+09 | 0.489925E+10 | 0.00 | 0.225922E+11 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.190723E+10 | 0.00 | 0.00 | 9546948.68 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 48225944.69 | 0.884578E+11 | 0.00 | 0.159161E+09 | 0.928625E+09 | 0.00 | 0.917530E+10 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.934677E+09 | 0.371677E+09 | 0.00 | 0.118747E+09 | 0.153666E+09 | 0.00 | 0.958437E+10 | 0.00 | 0.29 |
February | 0.630395E+09 | 0.147159E+10 | 0.00 | 91681387.74 | 0.191914E+09 | 0.00 | 0.597484E+10 | 0.00 | 0.29 |
March | 0.599705E+09 | 0.358935E+10 | 0.00 | 88967609.54 | 0.324501E+09 | 0.00 | 0.525013E+10 | 0.00 | 0.32 |
April | 0.484243E+09 | 0.859251E+10 | 0.00 | 36342614.34 | 0.348243E+10 | 0.00 | 0.156514E+10 | 0.00 | 0.34 |
May | 0.121895E+09 | 0.196018E+11 | 0.00 | 9527474.86 | 0.746971E+10 | 0.00 | 0.240874E+09 | 0.00 | 0.33 |
June | 5764366.51 | 0.326299E+11 | 0.00 | 785512.03 | 0.173597E+11 | 0.00 | 10220242.18 | 0.00 | 0.37 |
July | 41873210.25 | 0.426737E+11 | 0.00 | 513182.25 | 0.287146E+11 | 0.00 | 7871487.65 | 0.00 | 0.39 |
August | 0.00 | 0.498511E+11 | 0.00 | 0.00 | 0.283544E+11 | 0.00 | 0.00 | 0.00 | 0.40 |
September | 0.00 | 0.370104E+11 | 0.00 | 651522.77 | 0.167333E+11 | 0.00 | 5109930.46 | 0.00 | 0.35 |
October | 0.109002E+09 | 0.228110E+11 | 0.00 | 7165753.97 | 0.988129E+10 | 0.00 | 0.240813E+09 | 0.00 | 0.34 |
November | 0.164107E+09 | 0.114162E+11 | 0.00 | 26768982.74 | 0.148699E+10 | 0.00 | 0.736918E+09 | 0.00 | 0.32 |
December | 0.457920E+09 | 0.251153E+10 | 0.00 | 0.104294E+09 | 0.646307E+09 | 0.00 | 0.588367E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.354958E+10 | 0.232531E+12 | 0.00 | 0.485446E+09 | 0.114799E+12 | 0.00 | 0.295000E+11 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.371677E+09 | 0.00 | 0.00 | 0.153666E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.934677E+09 | 0.498511E+11 | 0.00 | 0.118747E+09 | 0.287146E+11 | 0.00 | 0.958437E+10 | 0.00 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.301694E+11 | 0.303885E+10 | 0.00 | 0.590098E+09 | 0.224849E+10 | 0.00 | 0.575789E+11 | 0.00 | 0.27 |
February | 0.172835E+11 | 0.133338E+11 | 0.00 | 0.465143E+09 | 0.329906E+10 | 0.00 | 0.374188E+11 | 0.00 | 0.27 |
March | 0.119460E+11 | 0.349870E+11 | 0.00 | 0.477599E+09 | 0.328939E+10 | 0.00 | 0.358581E+11 | 0.00 | 0.29 |
April | 0.355795E+10 | 0.829385E+11 | 0.00 | 0.226634E+09 | 0.207764E+11 | 0.00 | 0.128551E+11 | 0.00 | 0.29 |
May | 0.111605E+10 | 0.191579E+12 | 0.00 | 81455263.39 | 0.563650E+11 | 0.00 | 0.241718E+10 | 0.00 | 0.31 |
June | 48324388.44 | 0.317013E+12 | 0.00 | 12207863.14 | 0.119706E+12 | 0.00 | 0.160775E+09 | 0.00 | 0.33 |
July | 0.275300E+09 | 0.408012E+12 | 0.00 | 1211545.15 | 0.219845E+12 | 0.00 | 81274264.84 | 0.00 | 0.34 |
August | 0.00 | 0.475916E+12 | 0.00 | 0.00 | 0.200666E+12 | 0.00 | 0.00 | 0.00 | 0.35 |
September | 760003.78 | 0.358877E+12 | 0.00 | 7157364.41 | 0.121690E+12 | 0.00 | 71857324.95 | 0.00 | 0.31 |
October | 0.111814E+10 | 0.220941E+12 | 0.00 | 52468018.08 | 0.575788E+11 | 0.00 | 0.200232E+10 | 0.00 | 0.29 |
November | 0.144953E+10 | 0.109798E+12 | 0.00 | 0.148185E+09 | 0.905848E+10 | 0.00 | 0.549945E+10 | 0.00 | 0.28 |
December | 0.169958E+11 | 0.214356E+11 | 0.00 | 0.452109E+09 | 0.757253E+10 | 0.00 | 0.332128E+11 | 0.00 | 0.27 |
Annual Sum or Average | 0.839608E+11 | 0.223787E+13 | 0.00 | 0.251427E+10 | 0.822096E+12 | 0.00 | 0.187157E+12 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.303885E+10 | 0.00 | 0.00 | 0.224849E+10 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.301694E+11 | 0.475916E+12 | 0.00 | 0.590098E+09 | 0.219845E+12 | 0.00 | 0.575789E+11 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.396372E+10 | 0.212238E+09 | 0.00 | 34945402.67 | 0.183744E+09 | 0.00 | 0.412572E+10 | 0.00 | 0.25 |
February | 0.224008E+10 | 0.103735E+10 | 0.00 | 33872421.05 | 0.407285E+09 | 0.00 | 0.298377E+10 | 0.00 | 0.26 |
March | 0.172290E+10 | 0.285075E+10 | 0.00 | 35784464.46 | 0.338453E+09 | 0.00 | 0.267710E+10 | 0.00 | 0.28 |
April | 0.730893E+09 | 0.723457E+10 | 0.00 | 16297823.90 | 0.185216E+10 | 0.00 | 0.626320E+09 | 0.00 | 0.29 |
May | 98846524.64 | 0.181484E+11 | 0.00 | 6386190.59 | 0.532514E+10 | 0.00 | 0.192968E+09 | 0.00 | 0.31 |
June | 2545385.48 | 0.308176E+11 | 0.00 | 1268127.44 | 0.116029E+11 | 0.00 | 12092619.74 | 0.00 | 0.33 |
July | 22003045.52 | 0.404989E+11 | 0.00 | 196180.86 | 0.214465E+11 | 0.00 | 4457682.37 | 0.00 | 0.35 |
August | 0.00 | 0.472239E+11 | 0.00 | 0.00 | 0.198952E+11 | 0.00 | 0.00 | 0.00 | 0.36 |
September | 0.00 | 0.351514E+11 | 0.00 | 227060.96 | 0.118986E+11 | 0.00 | 1713486.50 | 0.00 | 0.32 |
October | 0.187144E+09 | 0.208764E+11 | 0.00 | 3318741.24 | 0.554645E+10 | 0.00 | 98008557.30 | 0.00 | 0.29 |
November | 0.282141E+09 | 0.967253E+10 | 0.00 | 9195219.01 | 0.126025E+10 | 0.00 | 0.310818E+09 | 0.00 | 0.27 |
December | 0.201400E+10 | 0.161868E+10 | 0.00 | 30293005.07 | 0.101353E+10 | 0.00 | 0.245975E+10 | 0.00 | 0.26 |
Annual Sum or Average | 0.112643E+11 | 0.215343E+12 | 0.00 | 0.171785E+09 | 0.807703E+11 | 0.00 | 0.134927E+11 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.212238E+09 | 0.00 | 0.00 | 0.183744E+09 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.396372E+10 | 0.472239E+11 | 0.00 | 35784464.46 | 0.214465E+11 | 0.00 | 0.412572E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.141951E+10 | 57642114.34 | 0.00 | 4884891.55 | 41379778.54 | 0.00 | 0.489609E+09 | 0.00 | 0.41 |
February | 0.806357E+09 | 0.226890E+09 | 0.00 | 5305967.89 | 94277940.41 | 0.00 | 0.386873E+09 | 0.00 | 0.42 |
March | 0.648652E+09 | 0.686512E+09 | 0.00 | 5863900.63 | 0.102153E+09 | 0.00 | 0.398759E+09 | 0.00 | 0.47 |
April | 0.298699E+09 | 0.189252E+10 | 0.00 | 2114270.10 | 0.866805E+09 | 0.00 | 0.100774E+09 | 0.00 | 0.59 |
May | 37427869.64 | 0.549680E+10 | 0.00 | 1110860.60 | 0.159597E+10 | 0.00 | 40961769.35 | 0.00 | 0.68 |
June | 1596425.71 | 0.987040E+10 | 0.00 | 73178.52 | 0.365862E+10 | 0.00 | 2127998.83 | 0.00 | 0.79 |
July | 10304609.20 | 0.135937E+11 | 0.00 | 84372.58 | 0.592256E+10 | 0.00 | 1417357.43 | 0.00 | 0.84 |
August | 0.00 | 0.146917E+11 | 0.00 | 0.00 | 0.619148E+10 | 0.00 | 0.00 | 0.00 | 0.84 |
September | 0.00 | 0.995064E+10 | 0.00 | 61632.38 | 0.377227E+10 | 0.00 | 973636.73 | 0.00 | 0.69 |
October | 52244819.45 | 0.479618E+10 | 0.00 | 589821.41 | 0.253079E+10 | 0.00 | 20109139.95 | 0.00 | 0.60 |
November | 0.121319E+09 | 0.199672E+10 | 0.00 | 1275855.54 | 0.471135E+09 | 0.00 | 45218867.85 | 0.00 | 0.48 |
December | 0.706963E+09 | 0.395879E+09 | 0.00 | 5292553.57 | 0.185265E+09 | 0.00 | 0.360547E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.410307E+10 | 0.636556E+11 | 0.00 | 26657304.77 | 0.254327E+11 | 0.00 | 0.184737E+10 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 57642114.34 | 0.00 | 0.00 | 41379778.54 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.141951E+10 | 0.146917E+11 | 0.00 | 5863900.63 | 0.619148E+10 | 0.00 | 0.489609E+09 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118621E+10 | 41211829.00 | 0.00 | 4496286.36 | 39368012.45 | 0.00 | 0.478079E+09 | 0.00 | 0.55 |
February | 0.685382E+09 | 0.130413E+09 | 0.00 | 4641441.55 | 0.126906E+09 | 0.00 | 0.349271E+09 | 0.00 | 0.55 |
March | 0.609081E+09 | 0.450376E+09 | 0.00 | 4520442.88 | 0.176040E+09 | 0.00 | 0.294663E+09 | 0.00 | 0.61 |
April | 0.264008E+09 | 0.132655E+10 | 0.00 | 2424113.68 | 0.876932E+09 | 0.00 | 98332360.78 | 0.00 | 0.76 |
May | 38235461.33 | 0.412604E+10 | 0.00 | 1187934.48 | 0.147433E+10 | 0.00 | 32789009.44 | 0.00 | 0.87 |
June | 1867892.14 | 0.704487E+10 | 0.00 | 40525.54 | 0.353008E+10 | 0.00 | 1442024.52 | 0.00 | 0.97 |
July | 9363161.92 | 0.932265E+10 | 0.00 | 10123.86 | 0.578994E+10 | 0.00 | 961769.71 | 0.00 | 1.02 |
August | 0.00 | 0.102760E+11 | 0.00 | 0.00 | 0.587697E+10 | 0.00 | 0.00 | 0.00 | 1.03 |
September | 492797.02 | 0.755900E+10 | 0.00 | 57927.16 | 0.352391E+10 | 0.00 | 426601.23 | 0.00 | 0.89 |
October | 38975587.72 | 0.373867E+10 | 0.00 | 840398.53 | 0.235255E+10 | 0.00 | 28711280.15 | 0.00 | 0.77 |
November | 0.106767E+09 | 0.138234E+10 | 0.00 | 1065369.97 | 0.603090E+09 | 0.00 | 38402546.25 | 0.00 | 0.62 |
December | 0.637536E+09 | 0.211715E+09 | 0.00 | 3728218.29 | 0.258970E+09 | 0.00 | 0.270912E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.357792E+10 | 0.456098E+11 | 0.00 | 23012782.30 | 0.246291E+11 | 0.00 | 0.159399E+10 | 0.00 | 0.76 |
Minimum of Months | 0.00 | 41211829.00 | 0.00 | 0.00 | 39368012.45 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.118621E+10 | 0.102760E+11 | 0.00 | 4641441.55 | 0.587697E+10 | 0.00 | 0.478079E+09 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143528E+10 | 98063481.35 | 0.00 | 13248181.95 | 37652454.63 | 0.00 | 0.111406E+10 | 0.00 | 0.57 |
February | 0.860000E+09 | 0.345336E+09 | 0.00 | 10789242.40 | 88508479.42 | 0.00 | 0.711297E+09 | 0.00 | 0.57 |
March | 0.760686E+09 | 0.906814E+09 | 0.00 | 8440932.61 | 0.107344E+09 | 0.00 | 0.532432E+09 | 0.00 | 0.60 |
April | 0.373873E+09 | 0.221387E+10 | 0.00 | 2049308.81 | 0.980034E+09 | 0.00 | 88956367.08 | 0.00 | 0.68 |
May | 63851923.05 | 0.541975E+10 | 0.00 | 773036.88 | 0.204294E+10 | 0.00 | 25831544.38 | 0.00 | 0.72 |
June | 1895530.84 | 0.922803E+10 | 0.00 | 36572.09 | 0.464435E+10 | 0.00 | 2433841.52 | 0.00 | 0.81 |
July | 12047499.85 | 0.129273E+11 | 0.00 | 52664.58 | 0.747023E+10 | 0.00 | 1524171.76 | 0.00 | 0.88 |
August | 0.00 | 0.152798E+11 | 0.00 | 0.00 | 0.745247E+10 | 0.00 | 0.00 | 0.00 | 0.92 |
September | 515180.07 | 0.123938E+11 | 0.00 | 44385.03 | 0.412676E+10 | 0.00 | 599677.22 | 0.00 | 0.84 |
October | 52105049.05 | 0.700698E+10 | 0.00 | 2524075.43 | 0.264289E+10 | 0.00 | 38248264.73 | 0.00 | 0.80 |
November | 0.133015E+09 | 0.309324E+10 | 0.00 | 3141774.23 | 0.450070E+09 | 0.00 | 78931070.51 | 0.00 | 0.68 |
December | 0.722333E+09 | 0.668818E+09 | 0.00 | 12616437.52 | 0.186596E+09 | 0.00 | 0.695332E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.441560E+10 | 0.695818E+11 | 0.00 | 53716611.52 | 0.302298E+11 | 0.00 | 0.328964E+10 | 0.00 | 0.72 |
Minimum of Months | 0.00 | 98063481.35 | 0.00 | 0.00 | 37652454.63 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.143528E+10 | 0.152798E+11 | 0.00 | 13248181.95 | 0.747023E+10 | 0.00 | 0.111406E+10 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154629E+10 | 61162413.27 | 0.00 | 4906251.73 | 41871007.64 | 0.00 | 0.593433E+09 | 0.00 | 0.71 |
February | 0.814990E+09 | 0.275828E+09 | 0.00 | 6458894.20 | 76089543.17 | 0.00 | 0.522079E+09 | 0.00 | 0.72 |
March | 0.581687E+09 | 0.811155E+09 | 0.00 | 7925938.25 | 64420296.19 | 0.00 | 0.604617E+09 | 0.00 | 0.83 |
April | 0.255163E+09 | 0.243196E+10 | 0.00 | 3197759.37 | 0.692075E+09 | 0.00 | 0.185962E+09 | 0.00 | 1.02 |
May | 50107465.05 | 0.536174E+10 | 0.00 | 744004.19 | 0.169091E+10 | 0.00 | 35817429.21 | 0.00 | 1.04 |
June | 1641190.00 | 0.973304E+10 | 0.00 | 60793.88 | 0.379314E+10 | 0.00 | 2518697.03 | 0.00 | 1.22 |
July | 10836956.64 | 0.134846E+11 | 0.00 | 134223.46 | 0.626964E+10 | 0.00 | 2264623.92 | 0.00 | 1.32 |
August | 0.00 | 0.157256E+11 | 0.00 | 0.00 | 0.618054E+10 | 0.00 | 0.00 | 0.00 | 1.37 |
September | 164418.71 | 0.997005E+10 | 0.00 | 26268.56 | 0.390846E+10 | 0.00 | 882733.84 | 0.00 | 1.08 |
October | 45375354.41 | 0.527611E+10 | 0.00 | 574861.30 | 0.245753E+10 | 0.00 | 34547728.64 | 0.00 | 0.98 |
November | 0.111873E+09 | 0.230586E+10 | 0.00 | 1961034.87 | 0.378560E+09 | 0.00 | 75085098.35 | 0.00 | 0.82 |
December | 0.642257E+09 | 0.508248E+09 | 0.00 | 8116410.18 | 0.173784E+09 | 0.00 | 0.574101E+09 | 0.00 | 0.74 |
Annual Sum or Average | 0.406039E+10 | 0.659453E+11 | 0.00 | 34106439.98 | 0.257270E+11 | 0.00 | 0.263131E+10 | 0.00 | 0.99 |
Minimum of Months | 0.00 | 61162413.27 | 0.00 | 0.00 | 41871007.64 | 0.00 | 0.00 | 0.00 | 0.71 |
Maximum of Months | 0.154629E+10 | 0.157256E+11 | 0.00 | 8116410.18 | 0.626964E+10 | 0.00 | 0.604617E+09 | 0.00 | 1.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.150201E+11 | 0.410951E+09 | 0.00 | 18703884.68 | 0.638309E+09 | 0.139734E+09 | 0.306365E+10 | 0.00 | 0.43 |
February | 0.893634E+10 | 0.190912E+10 | 0.00 | 27801351.36 | 0.170622E+10 | 26747585.81 | 0.246621E+10 | 0.00 | 0.45 |
March | 0.779283E+10 | 0.663252E+10 | 0.00 | 31467833.03 | 0.192574E+10 | 0.00 | 0.239158E+10 | 0.00 | 0.50 |
April | 0.322425E+10 | 0.192598E+11 | 0.00 | 12495082.77 | 0.682147E+10 | 0.00 | 0.545008E+09 | 0.00 | 0.55 |
May | 0.444826E+09 | 0.592931E+11 | 0.00 | 9535584.35 | 0.122597E+11 | 0.00 | 0.420163E+09 | 0.00 | 0.69 |
June | 16687237.00 | 0.109058E+12 | 0.00 | 1473234.87 | 0.241478E+11 | 0.00 | 34982079.20 | 0.00 | 0.79 |
July | 62713231.11 | 0.155107E+12 | 0.00 | 956886.95 | 0.430935E+11 | 0.00 | 30444628.59 | 0.00 | 0.87 |
August | 0.00 | 0.169307E+12 | 0.00 | 0.00 | 0.419551E+11 | 0.00 | 0.00 | 0.00 | 0.87 |
September | 8797313.80 | 0.107735E+12 | 0.00 | 383424.81 | 0.281553E+11 | 0.00 | 7436090.17 | 0.00 | 0.70 |
October | 0.659377E+09 | 0.496608E+11 | 0.00 | 3616713.43 | 0.183545E+11 | 0.00 | 93374753.70 | 0.00 | 0.57 |
November | 0.131188E+10 | 0.191533E+11 | 0.00 | 7804988.91 | 0.612255E+10 | 0.00 | 0.260902E+09 | 0.00 | 0.48 |
December | 0.857360E+10 | 0.254983E+10 | 0.00 | 22282274.42 | 0.348891E+10 | 20103311.06 | 0.198599E+10 | 0.00 | 0.44 |
Annual Sum or Average | 0.460514E+11 | 0.700078E+12 | 0.00 | 0.136521E+09 | 0.188669E+12 | 0.186585E+09 | 0.112997E+11 | 0.00 | 0.61 |
Minimum of Months | 0.00 | 0.410951E+09 | 0.00 | 0.00 | 0.638309E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.150201E+11 | 0.169307E+12 | 0.00 | 31467833.03 | 0.430935E+11 | 0.139734E+09 | 0.306365E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.135141E+11 | 0.291004E+09 | 0.00 | 12364027.81 | 0.647150E+09 | 0.180599E+09 | 0.269750E+10 | 0.00 | 0.60 |
February | 0.743628E+10 | 0.130909E+10 | 0.00 | 22903264.36 | 0.173062E+10 | 69541304.86 | 0.275003E+10 | 0.00 | 0.61 |
March | 0.675755E+10 | 0.501649E+10 | 0.00 | 28062598.89 | 0.210616E+10 | 5954134.02 | 0.234082E+10 | 0.00 | 0.67 |
April | 0.260818E+10 | 0.151245E+11 | 0.00 | 19483722.40 | 0.671796E+10 | 0.00 | 0.866995E+09 | 0.00 | 0.74 |
May | 0.432388E+09 | 0.459401E+11 | 0.00 | 11152649.11 | 0.109986E+11 | 0.00 | 0.362481E+09 | 0.00 | 0.89 |
June | 18363568.98 | 0.813520E+11 | 0.00 | 924300.86 | 0.237137E+11 | 0.00 | 28380759.73 | 0.00 | 0.97 |
July | 63816390.33 | 0.113065E+12 | 0.00 | 396097.81 | 0.430266E+11 | 0.00 | 19204149.07 | 0.00 | 1.08 |
August | 0.00 | 0.127487E+12 | 0.00 | 0.00 | 0.403663E+11 | 0.00 | 0.00 | 0.00 | 1.08 |
September | 10363473.84 | 0.846591E+11 | 0.00 | 492018.17 | 0.262399E+11 | 0.00 | 5001690.46 | 0.00 | 0.90 |
October | 0.442399E+09 | 0.407681E+11 | 0.00 | 6490181.88 | 0.168615E+11 | 0.00 | 0.252489E+09 | 0.00 | 0.75 |
November | 0.107790E+10 | 0.142123E+11 | 0.00 | 7231715.03 | 0.695266E+10 | 0.00 | 0.319013E+09 | 0.00 | 0.64 |
December | 0.781114E+10 | 0.174938E+10 | 0.00 | 13360702.12 | 0.349371E+10 | 61564191.15 | 0.161997E+10 | 0.00 | 0.61 |
Annual Sum or Average | 0.401724E+11 | 0.530974E+12 | 0.00 | 0.122861E+09 | 0.182855E+12 | 0.317658E+09 | 0.112619E+11 | 0.00 | 0.80 |
Minimum of Months | 0.00 | 0.291004E+09 | 0.00 | 0.00 | 0.647150E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.135141E+11 | 0.127487E+12 | 0.00 | 28062598.89 | 0.430266E+11 | 0.180599E+09 | 0.275003E+10 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139010E+11 | 0.109958E+10 | 0.00 | 0.108790E+09 | 0.413309E+09 | 92663831.51 | 0.995525E+10 | 0.00 | 0.60 |
February | 0.869090E+10 | 0.360509E+10 | 0.00 | 87785209.05 | 0.140722E+10 | 15723955.24 | 0.645954E+10 | 0.00 | 0.62 |
March | 0.821470E+10 | 0.968906E+10 | 0.00 | 64590116.23 | 0.165619E+10 | 0.00 | 0.438659E+10 | 0.00 | 0.65 |
April | 0.372033E+10 | 0.232010E+11 | 0.00 | 14548242.56 | 0.755571E+10 | 0.00 | 0.616068E+09 | 0.00 | 0.64 |
May | 0.703573E+09 | 0.584637E+11 | 0.00 | 7094483.51 | 0.158710E+11 | 0.00 | 0.277924E+09 | 0.00 | 0.72 |
June | 21023219.28 | 0.101715E+12 | 0.00 | 1024529.79 | 0.318802E+11 | 0.00 | 38034424.49 | 0.00 | 0.79 |
July | 75845653.17 | 0.147996E+12 | 0.00 | 604298.75 | 0.553400E+11 | 0.00 | 29978595.25 | 0.00 | 0.89 |
August | 0.00 | 0.177769E+12 | 0.00 | 0.00 | 0.502891E+11 | 0.00 | 0.00 | 0.00 | 0.94 |
September | 14088189.86 | 0.134550E+12 | 0.00 | 322093.84 | 0.300028E+11 | 0.00 | 4378628.01 | 0.00 | 0.85 |
October | 0.634151E+09 | 0.767641E+11 | 0.00 | 17943782.01 | 0.163005E+11 | 0.00 | 0.266169E+09 | 0.00 | 0.79 |
November | 0.131207E+10 | 0.337290E+11 | 0.00 | 22200302.38 | 0.443503E+10 | 0.00 | 0.682787E+09 | 0.00 | 0.71 |
December | 0.805369E+10 | 0.703138E+10 | 0.00 | 96565891.93 | 0.231876E+10 | 0.00 | 0.594477E+10 | 0.00 | 0.63 |
Annual Sum or Average | 0.453413E+11 | 0.775613E+12 | 0.00 | 0.421469E+09 | 0.217470E+12 | 0.108388E+09 | 0.286615E+11 | 0.00 | 0.74 |
Minimum of Months | 0.00 | 0.109958E+10 | 0.00 | 0.00 | 0.413309E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.139010E+11 | 0.177769E+12 | 0.00 | 0.108790E+09 | 0.553400E+11 | 92663831.51 | 0.995525E+10 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.155653E+11 | 0.568609E+09 | 0.00 | 20846632.17 | 0.489756E+09 | 0.198773E+09 | 0.278931E+10 | 0.00 | 0.68 |
February | 0.911267E+10 | 0.174022E+10 | 0.00 | 27417840.91 | 0.183939E+10 | 74842972.71 | 0.253591E+10 | 0.00 | 0.70 |
March | 0.793734E+10 | 0.638001E+10 | 0.00 | 27381688.40 | 0.188230E+10 | 0.00 | 0.251175E+10 | 0.00 | 0.77 |
April | 0.344211E+10 | 0.190890E+11 | 0.00 | 7493400.91 | 0.619456E+10 | 0.00 | 0.317418E+09 | 0.00 | 0.82 |
May | 0.785587E+09 | 0.514893E+11 | 0.00 | 4475329.65 | 0.134104E+11 | 0.00 | 77230583.62 | 0.00 | 0.96 |
June | 43764571.54 | 0.906744E+11 | 0.00 | 688853.20 | 0.267410E+11 | 0.00 | 8376145.53 | 0.00 | 1.07 |
July | 71129838.07 | 0.126377E+12 | 0.00 | 558080.19 | 0.467447E+11 | 0.00 | 22636459.59 | 0.00 | 1.17 |
August | 0.00 | 0.143798E+12 | 0.00 | 0.00 | 0.439754E+11 | 0.00 | 0.00 | 0.00 | 1.19 |
September | 13542673.81 | 0.941651E+11 | 0.00 | 89725.20 | 0.307435E+11 | 0.00 | 2822887.67 | 0.00 | 0.98 |
October | 0.718863E+09 | 0.438741E+11 | 0.00 | 2060043.88 | 0.202188E+11 | 0.00 | 41212409.06 | 0.00 | 0.83 |
November | 0.135921E+10 | 0.169965E+11 | 0.00 | 6619692.14 | 0.740366E+10 | 0.00 | 0.244665E+09 | 0.00 | 0.74 |
December | 0.895713E+10 | 0.295209E+10 | 0.00 | 19526838.39 | 0.321132E+10 | 7004749.58 | 0.184002E+10 | 0.00 | 0.70 |
Annual Sum or Average | 0.480067E+11 | 0.598104E+12 | 0.00 | 0.117158E+09 | 0.202855E+12 | 0.280621E+09 | 0.103914E+11 | 0.00 | 0.89 |
Minimum of Months | 0.00 | 0.568609E+09 | 0.00 | 0.00 | 0.489756E+09 | 0.00 | 0.00 | 0.00 | 0.68 |
Maximum of Months | 0.155653E+11 | 0.143798E+12 | 0.00 | 27417840.91 | 0.467447E+11 | 0.198773E+09 | 0.278931E+10 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124794E+10 | 26079102.45 | 0.00 | 1191733.04 | 61542170.12 | 0.328732E+09 | 0.299529E+09 | 0.00 | 0.47 |
February | 0.719571E+09 | 0.129642E+09 | 0.00 | 2672268.42 | 0.198303E+09 | 0.140311E+09 | 0.300016E+09 | 0.00 | 0.46 |
March | 0.668208E+09 | 0.470455E+09 | 0.00 | 3402731.33 | 0.242869E+09 | 18332185.09 | 0.290367E+09 | 0.00 | 0.50 |
April | 0.262432E+09 | 0.149914E+10 | 0.00 | 2096483.78 | 0.703910E+09 | 0.00 | 66146613.55 | 0.00 | 0.54 |
May | 52771017.05 | 0.498668E+10 | 0.00 | 930722.98 | 0.124953E+10 | 0.00 | 22275863.20 | 0.00 | 0.66 |
June | 1625998.38 | 0.949392E+10 | 0.00 | 216291.83 | 0.237597E+10 | 0.00 | 2298031.28 | 0.00 | 0.74 |
July | 5134871.39 | 0.134945E+11 | 0.00 | 63397.00 | 0.430616E+10 | 0.00 | 1759896.65 | 0.00 | 0.81 |
August | 0.00 | 0.148811E+11 | 0.00 | 0.00 | 0.421740E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
September | 332236.90 | 0.955403E+10 | 0.00 | 10117.77 | 0.295091E+10 | 0.00 | 105563.54 | 0.00 | 0.67 |
October | 61749428.99 | 0.428715E+10 | 0.00 | 552459.36 | 0.207081E+10 | 0.00 | 11199145.85 | 0.00 | 0.55 |
November | 92217401.48 | 0.155285E+10 | 0.00 | 1103801.11 | 0.856031E+09 | 0.00 | 42262640.38 | 0.00 | 0.48 |
December | 0.694546E+09 | 0.169181E+09 | 0.00 | 1817236.61 | 0.418658E+09 | 93794522.35 | 0.222209E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.380653E+10 | 0.605447E+11 | 0.00 | 14057243.22 | 0.196521E+11 | 0.581170E+09 | 0.125817E+10 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 26079102.45 | 0.00 | 0.00 | 61542170.12 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.124794E+10 | 0.148811E+11 | 0.00 | 3402731.33 | 0.430616E+10 | 0.328732E+09 | 0.300016E+09 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.970709E+09 | 23546155.60 | 0.00 | 1486006.88 | 46853466.20 | 0.171427E+09 | 0.363980E+09 | 0.00 | 0.58 |
February | 0.505890E+09 | 95584986.07 | 0.00 | 3004997.56 | 0.162613E+09 | 83411628.04 | 0.344587E+09 | 0.00 | 0.58 |
March | 0.482471E+09 | 0.392193E+09 | 0.00 | 3590287.40 | 0.187666E+09 | 12037708.50 | 0.296155E+09 | 0.00 | 0.63 |
April | 0.180621E+09 | 0.124149E+10 | 0.00 | 2928332.24 | 0.552982E+09 | 0.00 | 98252628.80 | 0.00 | 0.70 |
May | 38404353.53 | 0.392983E+10 | 0.00 | 1206397.02 | 0.968581E+09 | 0.00 | 24430474.05 | 0.00 | 0.83 |
June | 1255642.38 | 0.723069E+10 | 0.00 | 192588.42 | 0.202357E+10 | 0.00 | 2165455.65 | 0.00 | 0.90 |
July | 4765488.09 | 0.100925E+11 | 0.00 | 38536.80 | 0.367201E+10 | 0.00 | 762656.89 | 0.00 | 0.99 |
August | 0.00 | 0.114608E+11 | 0.00 | 0.00 | 0.349692E+10 | 0.00 | 0.00 | 0.00 | 1.00 |
September | 274482.51 | 0.765929E+10 | 0.00 | 15339.24 | 0.234577E+10 | 0.00 | 105514.19 | 0.00 | 0.84 |
October | 37971337.59 | 0.370862E+10 | 0.00 | 910209.63 | 0.153850E+10 | 0.00 | 23309321.20 | 0.00 | 0.71 |
November | 65531122.15 | 0.126864E+10 | 0.00 | 1136368.62 | 0.686189E+09 | 269193.93 | 41325333.86 | 0.00 | 0.60 |
December | 0.513913E+09 | 0.152485E+09 | 0.00 | 1719388.07 | 0.316954E+09 | 54062470.29 | 0.242583E+09 | 0.00 | 0.57 |
Annual Sum or Average | 0.280181E+10 | 0.472557E+11 | 0.00 | 16228451.87 | 0.159986E+11 | 0.321208E+09 | 0.143766E+10 | 0.00 | 0.75 |
Minimum of Months | 0.00 | 23546155.60 | 0.00 | 0.00 | 46853466.20 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.970709E+09 | 0.114608E+11 | 0.00 | 3590287.40 | 0.367201E+10 | 0.171427E+09 | 0.363980E+09 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.102763E+10 | 71273069.41 | 0.00 | 10041713.19 | 39984562.14 | 0.244828E+09 | 0.110256E+10 | 0.00 | 0.60 |
February | 0.639757E+09 | 0.230340E+09 | 0.00 | 9133578.45 | 0.181181E+09 | 92901636.81 | 0.792904E+09 | 0.00 | 0.60 |
March | 0.662657E+09 | 0.668107E+09 | 0.00 | 7016807.75 | 0.220014E+09 | 2902656.96 | 0.534283E+09 | 0.00 | 0.62 |
April | 0.287760E+09 | 0.176786E+10 | 0.00 | 2642895.66 | 0.765512E+09 | 0.00 | 85492912.40 | 0.00 | 0.62 |
May | 69320587.34 | 0.483304E+10 | 0.00 | 831153.48 | 0.164628E+10 | 0.00 | 13312400.38 | 0.00 | 0.69 |
June | 2600113.99 | 0.870749E+10 | 0.00 | 198815.31 | 0.324540E+10 | 0.00 | 1561409.46 | 0.00 | 0.74 |
July | 6755308.80 | 0.129857E+11 | 0.00 | 40576.49 | 0.527162E+10 | 0.00 | 932358.52 | 0.00 | 0.83 |
August | 0.00 | 0.155756E+11 | 0.00 | 0.00 | 0.489392E+10 | 0.00 | 0.00 | 0.00 | 0.87 |
September | 381548.79 | 0.115997E+11 | 0.00 | 9595.54 | 0.318121E+10 | 0.00 | 109049.51 | 0.00 | 0.79 |
October | 51501518.80 | 0.641489E+10 | 0.00 | 2785756.96 | 0.189202E+10 | 0.00 | 39741243.72 | 0.00 | 0.74 |
November | 83463470.73 | 0.272846E+10 | 0.00 | 3830247.89 | 0.653133E+09 | 0.00 | 99059286.90 | 0.00 | 0.67 |
December | 0.601367E+09 | 0.521840E+09 | 0.00 | 9105662.73 | 0.294087E+09 | 52214682.59 | 0.666754E+09 | 0.00 | 0.61 |
Annual Sum or Average | 0.343319E+10 | 0.661043E+11 | 0.00 | 45636803.44 | 0.222844E+11 | 0.392847E+09 | 0.333671E+10 | 0.00 | 0.70 |
Minimum of Months | 0.00 | 71273069.41 | 0.00 | 0.00 | 39984562.14 | 0.00 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.102763E+10 | 0.155756E+11 | 0.00 | 10041713.19 | 0.527162E+10 | 0.244828E+09 | 0.110256E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120392E+10 | 35164435.69 | 0.00 | 2034652.47 | 48764555.38 | 0.254911E+09 | 0.337933E+09 | 0.00 | 0.70 |
February | 0.738486E+09 | 0.121177E+09 | 0.00 | 3017278.14 | 0.191161E+09 | 67540331.11 | 0.318594E+09 | 0.00 | 0.69 |
March | 0.650609E+09 | 0.447671E+09 | 0.00 | 3202636.89 | 0.217996E+09 | 1205440.32 | 0.299411E+09 | 0.00 | 0.74 |
April | 0.259142E+09 | 0.143530E+10 | 0.00 | 1463064.60 | 0.623231E+09 | 0.00 | 48514254.05 | 0.00 | 0.77 |
May | 60747652.24 | 0.414651E+10 | 0.00 | 557651.52 | 0.136033E+10 | 0.00 | 9206972.63 | 0.00 | 0.89 |
June | 2223822.18 | 0.737397E+10 | 0.00 | 137691.35 | 0.283096E+10 | 0.00 | 1092608.36 | 0.00 | 0.97 |
July | 6036953.84 | 0.105564E+11 | 0.00 | 35501.56 | 0.459590E+10 | 0.00 | 537306.41 | 0.00 | 1.07 |
August | 0.00 | 0.121567E+11 | 0.00 | 0.00 | 0.436472E+10 | 0.00 | 0.00 | 0.00 | 1.08 |
September | 327275.06 | 0.789752E+10 | 0.00 | 2208.94 | 0.328628E+10 | 0.00 | 99559.35 | 0.00 | 0.92 |
October | 60988885.65 | 0.374439E+10 | 0.00 | 353089.12 | 0.208819E+10 | 0.00 | 7245065.61 | 0.00 | 0.79 |
November | 88969494.88 | 0.134348E+10 | 0.00 | 981530.99 | 0.922636E+09 | 0.00 | 41280424.00 | 0.00 | 0.71 |
December | 0.729123E+09 | 0.205752E+09 | 0.00 | 2036744.67 | 0.365648E+09 | 29616958.19 | 0.213061E+09 | 0.00 | 0.69 |
Annual Sum or Average | 0.380058E+10 | 0.494640E+11 | 0.00 | 13822050.26 | 0.208958E+11 | 0.353274E+09 | 0.127698E+10 | 0.00 | 0.84 |
Minimum of Months | 0.00 | 35164435.69 | 0.00 | 0.00 | 48764555.38 | 0.00 | 0.00 | 0.00 | 0.69 |
Maximum of Months | 0.120392E+10 | 0.121567E+11 | 0.00 | 3202636.89 | 0.459590E+10 | 0.254911E+09 | 0.337933E+09 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 34000188.86 | 0.00 | 8622762.51 | 0.00 | 0.00 | 0.270929E+09 | 0.00 | 0.58 |
February | 0.00 | 99601955.59 | 0.00 | 12053093.48 | 0.00 | 0.00 | 0.115827E+09 | 0.00 | 0.58 |
March | 0.00 | 0.170937E+09 | 0.00 | 18465822.19 | 0.00 | 0.00 | 86405111.62 | 0.00 | 0.59 |
April | 0.00 | 0.441168E+09 | 0.00 | 8231009.01 | 0.00 | 0.00 | 14418248.56 | 0.00 | 0.59 |
May | 0.00 | 0.794372E+09 | 0.00 | 286223.77 | 0.00 | 0.00 | 1327183.34 | 0.00 | 0.59 |
June | 0.00 | 0.131078E+10 | 0.00 | 4375.64 | 0.00 | 0.00 | 16787.95 | 0.00 | 0.60 |
July | 0.00 | 0.173622E+10 | 0.00 | 67554.62 | 0.00 | 0.00 | 14295.75 | 0.00 | 0.60 |
August | 0.00 | 0.186950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.139978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.971834E+09 | 0.00 | 692644.50 | 0.00 | 0.00 | 1933217.55 | 0.00 | 0.59 |
November | 0.00 | 0.471769E+09 | 0.00 | 2693759.66 | 0.00 | 0.00 | 6445029.85 | 0.00 | 0.58 |
December | 0.00 | 0.186471E+09 | 0.00 | 22461131.08 | 0.00 | 0.00 | 87459225.69 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.948643E+10 | 0.00 | 73578376.47 | 0.00 | 0.00 | 0.584775E+09 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 34000188.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.186950E+10 | 0.00 | 22461131.08 | 0.00 | 0.00 | 0.270929E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.315233E+09 | 0.00 | 63980346.34 | 0.00 | 0.00 | 0.278643E+10 | 0.00 | 0.58 |
February | 0.00 | 0.972651E+09 | 0.00 | 0.105115E+09 | 0.00 | 0.00 | 0.119441E+10 | 0.00 | 0.58 |
March | 0.00 | 0.169334E+10 | 0.00 | 0.169894E+09 | 0.00 | 0.00 | 0.884873E+09 | 0.00 | 0.59 |
April | 0.00 | 0.439294E+10 | 0.00 | 78745504.51 | 0.00 | 0.00 | 0.148442E+09 | 0.00 | 0.59 |
May | 0.00 | 0.787537E+10 | 0.00 | 2691829.52 | 0.00 | 0.00 | 13703287.76 | 0.00 | 0.59 |
June | 0.00 | 0.130516E+11 | 0.00 | 46314.24 | 0.00 | 0.00 | 173384.23 | 0.00 | 0.60 |
July | 0.00 | 0.173117E+11 | 0.00 | 660672.47 | 0.00 | 0.00 | 157590.34 | 0.00 | 0.60 |
August | 0.00 | 0.186583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.138833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.966317E+10 | 0.00 | 6405455.47 | 0.00 | 0.00 | 20124915.39 | 0.00 | 0.59 |
November | 0.00 | 0.468490E+10 | 0.00 | 25387277.56 | 0.00 | 0.00 | 67680789.09 | 0.00 | 0.58 |
December | 0.00 | 0.184690E+10 | 0.00 | 0.207038E+09 | 0.00 | 0.00 | 0.898023E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.943494E+11 | 0.00 | 0.659964E+09 | 0.00 | 0.00 | 0.601402E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.315233E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.186583E+11 | 0.00 | 0.207038E+09 | 0.00 | 0.00 | 0.278643E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 10103725.79 | 31068521.74 | 0.00 | 4409313.85 | 0.00 | 0.00 | 0.274975E+09 | 0.00 | 0.58 |
February | 0.00 | 96952202.91 | 0.00 | 9496884.88 | 0.00 | 0.00 | 0.121734E+09 | 0.00 | 0.58 |
March | 0.00 | 0.169263E+09 | 0.00 | 16327662.84 | 0.00 | 0.00 | 89611614.62 | 0.00 | 0.59 |
April | 0.00 | 0.438462E+09 | 0.00 | 7766796.87 | 0.00 | 0.00 | 15065598.01 | 0.00 | 0.59 |
May | 0.00 | 0.791291E+09 | 0.00 | 259237.07 | 0.00 | 0.00 | 1394674.31 | 0.00 | 0.59 |
June | 0.00 | 0.130797E+10 | 0.00 | 4646.40 | 0.00 | 0.00 | 17339.64 | 0.00 | 0.60 |
July | 0.00 | 0.173308E+10 | 0.00 | 66280.16 | 0.00 | 0.00 | 16005.68 | 0.00 | 0.60 |
August | 0.00 | 0.186231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.139455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.967162E+09 | 0.00 | 624127.26 | 0.00 | 0.00 | 2058263.80 | 0.00 | 0.59 |
November | 0.00 | 0.467974E+09 | 0.00 | 2436881.83 | 0.00 | 0.00 | 7013321.24 | 0.00 | 0.58 |
December | 0.00 | 0.184047E+09 | 0.00 | 19804078.44 | 0.00 | 0.00 | 91181884.79 | 0.00 | 0.58 |
Annual Sum or Average | 10103725.79 | 0.944414E+10 | 0.00 | 61195909.61 | 0.00 | 0.00 | 0.603067E+09 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 31068521.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 10103725.79 | 0.186231E+10 | 0.00 | 19804078.44 | 0.00 | 0.00 | 0.274975E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 41943839.08 | 0.00 | 0.637362E+09 | 0.00 | 0.00 | 0.100608E+11 | 0.00 | 0.66 |
February | 0.00 | 0.217592E+09 | 0.00 | 0.102835E+10 | 0.00 | 0.00 | 0.665328E+10 | 0.00 | 0.66 |
March | 0.00 | 0.131189E+10 | 0.00 | 0.132099E+10 | 0.00 | 0.00 | 0.429883E+10 | 0.00 | 0.66 |
April | 0.00 | 0.501750E+10 | 0.00 | 0.778542E+09 | 0.00 | 0.00 | 0.100213E+10 | 0.00 | 0.66 |
May | 0.00 | 0.537450E+10 | 0.00 | 0.243311E+09 | 0.00 | 0.00 | 0.134549E+10 | 0.00 | 0.67 |
June | 0.00 | 0.200481E+11 | 0.00 | 51940123.62 | 0.00 | 0.00 | 71381842.95 | 0.00 | 0.67 |
July | 0.00 | 0.329435E+11 | 0.00 | 38777400.97 | 0.00 | 0.00 | 9021093.89 | 0.00 | 0.67 |
August | 0.00 | 0.356124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.126271E+11 | 0.00 | 60372825.92 | 0.00 | 0.00 | 0.216830E+09 | 0.00 | 0.67 |
October | 0.00 | 0.126799E+11 | 0.00 | 0.150666E+09 | 0.00 | 0.00 | 0.372924E+09 | 0.00 | 0.66 |
November | 0.00 | 0.483968E+10 | 0.00 | 0.573512E+09 | 0.00 | 0.00 | 0.970283E+09 | 0.00 | 0.66 |
December | 0.00 | 0.122137E+10 | 0.00 | 0.176255E+10 | 0.00 | 0.00 | 0.425622E+10 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.131935E+12 | 0.00 | 0.664637E+10 | 0.00 | 0.00 | 0.292571E+11 | 0.00 | 0.67 |
Minimum of Months | 0.00 | 41943839.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.00 | 0.356124E+11 | 0.00 | 0.176255E+10 | 0.00 | 0.00 | 0.100608E+11 | 0.00 | 0.67 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.396708E+12 | 0.409216E+10 | 0.00 | 0.411312E+12 | 0.185699E+13 |
February | 0.441469E+12 | 0.287827E+10 | 0.00 | 0.224789E+12 | 0.225449E+13 |
March | 0.557390E+12 | 0.947946E+09 | 0.00 | 0.106646E+12 | 0.327576E+13 |
April | 0.602426E+12 | -0.512800E+10 | 0.00 | -0.305197E+12 | 0.403626E+13 |
May | 0.644382E+12 | -0.128147E+11 | 0.00 | -0.900874E+12 | 0.397370E+13 |
June | 0.625597E+12 | -0.250298E+11 | 0.00 | -0.158613E+13 | 0.516497E+13 |
July | 0.615886E+12 | -0.342254E+11 | 0.00 | -0.219344E+13 | 0.643169E+13 |
August | 0.591345E+12 | -0.338531E+11 | 0.00 | -0.234021E+13 | 0.723837E+13 |
September | 0.520570E+12 | -0.263115E+11 | 0.00 | -0.178545E+13 | 0.480573E+13 |
October | 0.446543E+12 | -0.136614E+11 | 0.00 | -0.105888E+13 | 0.431206E+13 |
November | 0.358341E+12 | -0.390173E+10 | 0.00 | -0.337057E+12 | 0.365342E+13 |
December | 0.345312E+12 | 0.141444E+10 | 0.00 | 0.152871E+12 | 0.335233E+13 |
Annual Sum or Average | 0.614597E+13 | -0.145593E+12 | 0.00 | -0.961161E+13 | 0.503558E+14 |
Minimum of Months | 0.345312E+12 | -0.342254E+11 | 0.00 | -0.234021E+13 | 0.185699E+13 |
Maximum of Months | 0.644382E+12 | 0.409216E+10 | 0.00 | 0.411312E+12 | 0.723837E+13 |