Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2024-07-03 12:21:38
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 33721.20 | 728.00 | 728.00 |
Net Site Energy | 33721.20 | 728.00 | 728.00 |
Total Source Energy | 105693.86 | 2281.80 | 2281.80 |
Net Source Energy | 105693.86 | 2281.80 | 2281.80 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 528.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3082.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1007.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3141.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1109.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 253.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14259.38 |
Humidification | 1314.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.83 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 374.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 33192.55 | 528.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17028.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 528.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3082.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 1007.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 56.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 3141.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 1109.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 253.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14259.38 |
Humidification | General | 1314.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.83 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 374.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 528.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3082.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 5610.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 1007.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2623.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 3141.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 1109.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 253.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14259.38 |
Humidification | Unassigned | 1314.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.83 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 374.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 200.23 | 11.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 716.59 | 11.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 142.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 200.23 | 11.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Other | 373.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 716.59 | 11.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 33192.546 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 33192.546 | 100.00 |
Total On-Site and Utility Electric Sources | 33192.546 | 100.00 |
Total Electricity End Uses | 33192.546 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 17028.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 17028.38 | 100.00 |
Total Water End Uses | 17028.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 2.00 |
Time Setpoint Not Met During Occupied Cooling | 238.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5187.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS SZVAV FAN | AIRLOOP DATACENTER BASEMENT SYS11 FAN | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 11.6510 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.6510 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 11.6510 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 11.6510 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.3674 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 11.6510 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 11.7515 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 11.6510 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.6510 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 11.6510 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.6510 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.6510 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.6510 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.6510 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 22.3674 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 11.6510 | 18.58 | 484.4232 | |
Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 11.7515 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.6100 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-15:30 | 26-DEC-05:10 | - | - | - | - | - | - | - | - | - | - | 14-JUN-12:00 |
Heating | 0.00 | 795969.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 380112.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235096.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 307621.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 85305.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 50732.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26705.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2353846.47 | 795969.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 795969.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 380112.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 307621.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 85305.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 50732.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 26705.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 573.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9761.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17769.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3191.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8307.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9948.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3515.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 801.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 4161.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1184.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 105120.79 | 573.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 12.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 210.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 214.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 75.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 17.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 89.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2269.43 | 12.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 12.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 210.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 214.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 75.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 17.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 89.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2269.43 | 12.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 8.35 | 0.253738 | 0.300000 | 2.50 |
DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | 36.38 | 0.016413 | 0.500000 | 18.19 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 8.55 | 0.222453 | 0.300000 | 2.57 | 0.593208 | 0.500000 | 0.001713 | 0.000194 | 2.57 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 80.84 | 0.235272 | 0.300000 | 24.25 | 0.627392 | 0.500000 | 0.001619 | 0.004168 | 24.25 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 9.46 | 0.201165 | 0.300000 | 2.84 | 0.536441 | 0.500000 | 0.001894 | 0.001284 | 7.12 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.58 | 0.150781 | 0.300000 | 0.475168 | 0.402082 | 0.500000 | 0.002527 | 0.000147 | 0.816147 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.51 | 0.101921 | 0.300000 | 0.453011 | 0.300000 | 0.500000 | 0.003738 | 0.000103 | 0.572735 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.79 | 0.133236 | 0.300000 | 0.537753 | 0.355295 | 0.500000 | 0.002860 | 0.000180 | 0.996241 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.96 | 0.078455 | 0.300000 | 0.588513 | 0.300000 | 0.500000 | 0.004856 | 0.000087 | 0.588513 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 15.20 | 0.157161 | 0.300000 | 4.56 | 0.419095 | 0.500000 | 0.002424 | 0.002735 | 15.20 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 15.56 | 0.300000 | 0.500000 | 0.003852 | 0.001818 | 10.10 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 17.04 | 0.140160 | 0.300000 | 5.11 | 0.373760 | 0.500000 | 0.002718 | 0.002698 | 14.98 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 17.22 | 0.089387 | 0.300000 | 5.17 | 0.300000 | 0.500000 | 0.004262 | 0.001696 | 9.42 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 2.05 | 0.116639 | 0.300000 | 0.614255 | 0.311038 | 0.500000 | 0.003266 | 0.000368 | 2.05 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.63 | 0.094253 | 0.300000 | 0.489869 | 0.300000 | 0.500000 | 0.004042 | 0.000243 | 1.35 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 2.05 | 0.116261 | 0.300000 | 0.616264 | 0.310030 | 0.500000 | 0.003277 | 0.000364 | 2.03 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.95 | 0.078883 | 0.300000 | 0.585318 | 0.300000 | 0.500000 | 0.004830 | 0.000233 | 1.30 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 22156.39 | 0.000194 | 446.98 | |
CORE_MID VAV BOX REHEAT COIL | 476393.32 | 0.004168 | 10989.69 | |
CORE_TOP VAV BOX REHEAT COIL | 146721.91 | 0.001284 | 3429.15 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 16829.46 | 0.000147 | 393.35 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11806.49 | 0.000103 | 275.92 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 20527.98 | 0.000180 | 479.69 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9958.79 | 0.000087 | 221.78 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 312682.83 | 0.002735 | 7303.88 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 207774.41 | 0.001818 | 4853.24 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 308345.67 | 0.002698 | 7202.64 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 193815.17 | 0.001696 | 4527.39 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 42105.53 | 0.000368 | 983.37 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 27739.67 | 0.000243 | 647.85 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 41664.15 | 0.000364 | 973.06 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 26665.85 | 0.000233 | 622.78 | |
VAV_BOT WITH REHEAT HEATING COIL | 42691.59 | 0.000373 | 730.92 | |
VAV_MID WITH REHEAT HEATING COIL | 276725.65 | 0.002421 | 4833.47 | |
VAV_TOP WITH REHEAT HEATING COIL | 21639.62 | 0.000189 | 385.50 | |
CAV_BAS HEATING COIL | 0.000875 | 2621.21 | 100000.00 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 557573.71 | 0.000875 | 2621.21 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.818963 |
DATACENTER_MID_ZN_6 DIRECT AIR | 7.80 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.816938 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 7.70 | 4.62 | 15.40 | 4.62 | 13.75 | 13.75 | 0.300000 | 0.336087 | 13.75 |
VAV_MID WITH REHEAT | 72.93 | 43.76 | 145.86 | 71.61 | 127.29 | 127.29 | 0.300000 | 0.562574 | 127.29 |
VAV_TOP WITH REHEAT | 8.57 | 5.14 | 17.14 | 13.84 | 16.45 | 16.45 | 0.300000 | 0.841098 | 16.45 |
CAV_BAS | 2.50 | 2.50 | 8.35 | 2.50 | 8.35 | 8.35 | 1.00 | 0.300000 | 8.35 |
AIRLOOP DATACENTER BASEMENT | 18.19 | 18.19 | 36.38 | 18.19 | 36.38 | 36.38 | 1.00 | 0.499994 | 36.38 |
AIRLOOP DATACENTER BOT | 0.818963 | 0.818963 | 0.818963 | 0.818963 | 0.818963 | 0.818963 | 1.00 | 1.00 | 0.818963 |
AIRLOOP DATACENTER MID | 7.80 | 7.80 | 7.80 | 7.80 | 7.80 | 7.80 | 1.00 | 1.00 | 7.80 |
AIRLOOP DATACENTER TOP | 0.816938 | 0.816938 | 0.816938 | 0.816938 | 0.816938 | 0.816938 | 1.00 | 1.000000 | 0.816938 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 13.75 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 127.29 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 16.45 | |
CAV_BAS_OA_CONTROLLER | 8.35 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 36.38 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.818963 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 7.80 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.816938 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.08 | 6.67 | 10.84 | 0.007236 | 0.007000 | 231321.81 | 0.008262 | 13.75 |
VAV_MID WITH REHEAT COOLING COIL | 26.28 | 6.67 | 10.83 | 0.007252 | 0.007000 | 2175743.40 | 0.077713 | 127.29 |
VAV_TOP WITH REHEAT COOLING COIL | 25.74 | 6.67 | 10.84 | 0.007201 | 0.007000 | 269348.59 | 0.009621 | 16.45 |
CAV_BAS COOLING COIL | 25.73 | 6.67 | 10.82 | 0.007337 | 0.007000 | 136072.51 | 0.004860 | 8.35 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 27.10 | 6.67 | 14.92 | 0.007031 | 0.007000 | 459162.04 | 0.016400 | 36.38 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 13.75 |
VAV_MID WITH REHEAT FAN | 127.29 |
VAV_TOP WITH REHEAT FAN | 16.45 |
CAV_BAS SZVAV FAN | 8.35 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | 36.38 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.008262 | 0.000058 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000373 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.077713 | 0.000006 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.002421 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.009621 | 0.000049 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000189 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | Design Size Minimum Supply Air Temperature [C] | User-Specified Minimum Supply Air Temperature [C] | User-Specified Maximum Supply Air Temperature [C] | User-Specified Nominal Cooling Capacity [W] | Design Size Maximum Supply Air Temperature [C] | |
CAV_BAS_UNITARY_PACKAGE_DX | 8.35 | 8.35 | 8.35 | 2.50 | 136072.51 | 100000.00 | 1.00 | 5.34 | 12.89 | 32.11 | ||
AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | 36.38 | 36.38 | 36.38 | 18.19 | 459162.04 | 100000.00 | 1.00 | 15.89 | 29.11 | |||
AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | 0.818963 | 0.818963 | 0.818963 | 0.818963 | 25103.14 | 1.00 | 13556.74 | 29.11 | ||||
AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | 7.80 | 7.80 | 7.80 | 7.80 | 239277.27 | 1.00 | 129198.04 | 29.11 | ||||
AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | 0.816938 | 0.816938 | 0.816938 | 0.816938 | 25041.30 | 1.00 | 13523.23 | 29.11 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000190 | 0.000037 | 96450.70 | 100000.00 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | 0.818963 | 1408.32 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | 7.80 | 13421.53 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | 0.816938 | 1404.84 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
AIRLOOP DATACENTER BOT COOLING COIL | 0.818960 | 0.409481 | 0.545973 | 13556.74 | 6778.37 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER MID COOLING COIL | 7.80 | 3.90 | 5.20 | 129198.04 | 64599.02 | 0.800660 | 0.800660 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.816940 | 0.408469 | 0.544627 | 13523.23 | 6761.61 | 0.800660 | 0.800660 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BOT HEATING COIL | 25103.14 |
AIRLOOP DATACENTER MID HEATING COIL | 239277.27 |
AIRLOOP DATACENTER TOP HEATING COIL | 25041.30 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.116856 | 24079.65 | |
HEATSYS1 PUMP | 0.021051 | 6339.60 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.116856 | 14.02 |
HEATSYS1 | 0.021051 | 2.53 |
COOLSYS1_SUPPLY | 0.116856 | 14.02 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.116856 | 0.116856 | 490502.00 | 6.67 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2406244.49 | 2406244.49 | 0.021051 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.058428 | 11113.86 |
COOLSYS1 CHILLER2 PUMP | 0.058428 | 11113.86 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.116856 | 0.059035 | 1652822.79 | 1652772.51 | 0.082831 |
COOLSYS1 CHILLER2 | 0.116856 | 0.059035 | 1652822.79 | 1652772.51 | 0.082831 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.165662 | 19.88 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.165662 | 57766.63 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 76.98 | 1980436.58 | 15.40 | 247554.57 |
TOWERWATERSYS COOLTOWER 2 | 76.98 | 1980436.58 | 15.40 | 247554.57 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 11.651 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 16.493 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 11.651 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.721 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 22.367 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 237.667 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 11.651 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 496.074 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 32383.100 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 32383.100 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 29082.299 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 29082.299 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3651.573 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.573 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3651.653 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3651.653 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2353.212 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2353.212 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 9130.649 | 11.651 | 216.462 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 9130.649 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 809.760 | 22.367 | 415.559 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 809.760 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
26 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
27 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
35 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
47 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
48 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
49 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
50 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
51 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
52 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
53 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
54 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
55 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
56 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
57 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
58 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
59 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
60 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
61 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
62 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
63 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
64 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
65 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
66 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
67 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
68 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
69 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
70 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
71 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
72 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
73 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
74 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
75 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
76 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
77 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
78 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
79 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
80 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
81 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
82 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
83 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
84 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
85 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
86 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
87 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
88 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
89 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
90 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
91 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
92 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
93 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
94 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
95 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
96 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
97 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
98 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
99 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
100 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
101 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
102 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
103 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
104 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
105 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
106 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
107 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
108 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
109 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
110 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
111 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
112 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
113 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
114 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
115 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
116 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
117 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
118 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
119 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
120 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
121 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone BASEMENT | 1.2500 |
3 | Zone CORE_BOTTOM | 1.2500 |
4 | Zone CORE_MID | 1.2500 |
5 | Zone CORE_TOP | 1.2500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.2500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.2500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.2500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone BASEMENT | 1.1500 |
3 | Zone CORE_BOTTOM | 1.1500 |
4 | Zone CORE_MID | 1.1500 |
5 | Zone CORE_TOP | 1.1500 |
6 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
7 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
8 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
10 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
11 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
12 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
14 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
15 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
16 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
17 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
18 | Zone DATACENTER_BOT_ZN_6 | 1.1500 |
19 | Zone DATACENTER_MID_ZN_6 | 1.1500 |
20 | Zone DATACENTER_TOP_ZN_6 | 1.1500 |
21 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 86434.71096 | 99399.91760 | 7.25817 | 8.34690 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.48000 | 6.85626E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 88554.65609 | 101837.85451 | 7.43506 | 8.55032 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.48000 | 6.85626E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | -5.20000 | 2.80840E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 837457.96433 | 963076.65898 | 70.29950 | 80.84443 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.48000 | 6.85626E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 213521.10812 | 266901.38515 | 17.52964 | 21.91205 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 97095.38022 | 111659.68725 | 8.22185 | 9.45513 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10000 | 6.87148E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 68203.98916 | 85254.98645 | 5.69293 | 7.11616 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 16265.39739 | 18705.20700 | 1.37730 | 1.58389 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 7825.70150 | 9782.12687 | 0.65292 | 0.81615 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 15507.01932 | 17833.07221 | 1.31308 | 1.51004 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 32.42333 | 6.86244E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 5488.64357 | 6860.80447 | 0.45819 | 0.57274 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 18407.73466 | 21168.89486 | 1.55870 | 1.79251 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 9539.78798 | 11924.73498 | 0.79699 | 0.99624 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 20145.45970 | 23167.27866 | 1.70583 | 1.96171 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80000 | 6.86940E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 3902.69649 | 4878.37061 | 0.32479 | 0.40598 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 155828.73985 | 179203.05083 | 13.19502 | 15.17427 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10000 | 6.87148E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 145175.00146 | 181468.75183 | 12.15676 | 15.19596 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 159802.58034 | 183772.96740 | 13.53143 | 15.56115 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 32.79167 | 6.86302E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 96462.06010 | 120577.57512 | 8.07866 | 10.09832 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 174983.61848 | 201231.16125 | 14.81697 | 17.03952 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 143165.39659 | 178956.74573 | 11.98771 | 14.98464 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 176814.85233 | 203337.08018 | 14.97195 | 17.21774 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 89993.19892 | 112491.49866 | 7.53467 | 9.41833 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 19338.23391 | 22238.96900 | 1.63749 | 1.88311 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 19540.41706 | 24425.52132 | 1.63801 | 2.04752 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 16768.78486 | 19284.10259 | 1.41991 | 1.63290 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 33.48500 | 6.86412E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 12873.14604 | 16091.43254 | 1.07919 | 1.34899 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 21095.38585 | 24259.69373 | 1.78627 | 2.05421 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 19335.88854 | 24169.86068 | 1.62081 | 2.02601 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 20036.15059 | 23041.57318 | 1.69657 | 1.95106 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 12375.43552 | 15469.29440 | 1.03735 | 1.29669 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8410.01161 | 9671.51335 | 0.71214 | 0.81896 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 34.33000 | 6.86546E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | -5.20000 | 2.80840E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 80148.33388 | 92170.58396 | 6.78683 | 7.80485 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 34.00500 | 6.86494E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -5.20000 | 2.80840E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8389.22781 | 9647.61198 | 0.71038 | 0.81694 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -5.20000 | 2.80840E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 373636.20859 | 429681.63988 | 31.63793 | 36.38362 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 26.27000 | 6.85284E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20000 | 2.80840E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 190225.12 | 13.74508 | 13.74508 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 39531.38 | 3.86893 | 3.86893 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1761745.18 | 127.28871 | 127.28871 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 384471.56 | 71.60930 | 71.60930 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:20:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 221503.50 | 16.44917 | 16.44917 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 38418.14 | 13.83537 | 13.83537 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 01:10:00 |
7 | CAV_BAS | Cooling | Sensible | 103691.74 | 8.34690 | 8.34690 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 46990.12 | 1.20016 | 1.20016 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 427620.47 | 36.38408 | 36.38408 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 12183.87 | 0.33839 | 0.33839 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 9669.37 | 0.81896 | 0.81896 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 562.84 | 1.56323E-002 | 1.56323E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 92195.12 | 7.80485 | 7.80485 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 5628.44 | 0.15632 | 0.15632 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 9684.45 | 0.81694 | 0.81694 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 562.84 | 1.56323E-002 | 1.56323E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 8.34690 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.25374 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 2.50407 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.55032 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22245 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.56510 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59321 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.71272E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.93834E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.56510 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22156.39316 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.93834E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 446.98398 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 80.84443 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23527 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 24.25333 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62739 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61940E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.16770E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 24.25333 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 476393.31589 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.16770E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 10989.68528 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.45513 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20117 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.83654 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53644 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.89396E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.28359E-003 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.11616 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 146721.90606 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.28359E-003 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3429.15368 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.58389 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15078 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.47517 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40208 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.52685E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.47231E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.81615 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16829.45978 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.47231E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 393.34795 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.51004 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10192 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.45301 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.73818E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03288E-004 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.57274 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11806.49248 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03288E-004 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 275.92437 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.79251 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13324 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.53775 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35529 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.85960E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.79588E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.99624 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20527.98287 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.79588E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 479.69362 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.96171 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.84545E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.58851 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.85632E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.71239E-005 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.58851 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9958.79442 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.71239E-005 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 221.77800 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 15.19596 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15716 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.55879 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41910 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.42427E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.73549E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 15.19596 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 312682.83313 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.73549E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7303.87594 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 15.56115 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.85224E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.81770E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 10.09832 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 207774.40729 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.81770E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4853.24431 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 17.03952 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14016 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.11186 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37376 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.71832E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.69754E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 14.98464 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 308345.67315 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.69754E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7202.63696 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 17.21774 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.93875E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.16532 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.26234E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.69558E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.41833 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 193815.16939 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69558E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4527.38669 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.04752 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11664 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.61426 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31104 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.26649E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.68358E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.04752 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 42105.52765 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.68358E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 983.36577 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.63290 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.42528E-002 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.48987 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.04232E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.42679E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.34899 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27739.67370 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.42679E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 647.84685 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.05421 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11626 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.61626 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31003 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.27710E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.64496E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.02601 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 41664.15342 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.64496E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 973.06278 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.95106 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.88828E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.58532 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.82995E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.33284E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.29669 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26665.85156 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.33284E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 622.77849 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.81896 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.80485 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.81694 |
215 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 36.38362 |
216 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 1.64130E-002 |
217 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
218 | AirTerminal:SingleDuct:VAV:NoReheat | DATACENTER_BASEMENT_ZN_6 PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 18.19181 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.69923 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.61954 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 15.39847 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.61954 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 13.74508 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 13.74508 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.33609 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 72.92939 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 43.75764 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 145.85879 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 71.60930 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 127.28871 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 127.28871 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.56257 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 8.57041 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.14224 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 17.14081 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 13.83537 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 16.44917 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 16.44917 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.84110 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.50407 |
244 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.50407 |
245 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.34690 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.50407 |
247 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.34690 |
248 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 8.34690 |
249 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.30000 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 18.19181 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 18.19181 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 36.38362 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 18.19181 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 36.38408 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 36.38408 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.49999 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.81896 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.81896 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.81896 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.81896 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.81896 |
264 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.81896 |
265 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.80485 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.80485 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.80485 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 7.80485 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.80485 |
272 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 7.80485 |
273 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
274 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.81694 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.81694 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.81694 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.81694 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.81694 |
280 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.81694 |
281 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
282 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
283 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 13.74508 |
284 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 127.28871 |
285 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 16.44917 |
286 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 8.34690 |
287 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 36.38408 |
288 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.81896 |
289 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 7.80485 |
290 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.81694 |
291 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 13.74508 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.08282 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.84190 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.23613E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 231321.80968 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.26228E-003 |
299 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 13.74508 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 42691.58730 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.73485E-004 |
302 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 730.91822 |
303 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 13.74508 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.26228E-003 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.76343E-005 |
306 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.73485E-004 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 127.28871 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.28334 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.83326 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.25158E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2175743.39860 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.77125E-002 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 127.28871 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 276725.64845 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.42092E-003 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 4833.46545 |
319 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 127.28871 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.77125E-002 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.12759E-006 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.42092E-003 |
323 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 16.44917 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.74238 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.84177 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.20122E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 269348.59080 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.62051E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 16.44917 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 21639.61559 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.89313E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 385.49876 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 16.44917 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.62051E-003 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.94974E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.89313E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.34690 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 8.34690 |
342 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 8.34690 |
343 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.34690 |
344 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.50407 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.73192 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.82260 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.33727E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 136072.51059 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.86019E-003 |
352 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.34690 |
353 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 136072.51059 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
355 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
356 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2621.21250 |
357 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
358 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
359 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | Design Size Minimum Supply Air Temperature [C] | 5.34030 |
360 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 12.88890 |
361 | AirLoopHVAC:UnitarySystem | CAV_BAS_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 32.11110 |
362 | Fan:VariableVolume | CAV_BAS SZVAV FAN | Design Size Maximum Flow Rate [m3/s] | 8.34690 |
363 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 36.38408 |
364 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
365 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 36.38408 |
366 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 36.38408 |
367 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 36.38408 |
368 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 18.19204 |
369 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.10118 |
370 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
371 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 14.91744 |
372 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.03132E-003 |
373 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
374 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Coil Load [W] | 459162.04216 |
375 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.64002E-002 |
376 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 36.38408 |
377 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 459162.04216 |
378 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Capacity [W] | 557573.70766 |
379 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
380 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
381 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2621.21250 |
382 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 100000.00000 |
383 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
384 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 15.88890 |
385 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BASEMENT_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 29.11110 |
386 | Fan:VariableVolume | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Design Size Maximum Flow Rate [m3/s] | 36.38408 |
387 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.90450E-004 |
388 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
389 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
390 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
391 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.81896 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
393 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.81896 |
394 | Fan:SystemModel | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1408.31991 |
395 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.81896 |
396 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.81896 |
397 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.81896 |
398 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.81896 |
399 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.81896 |
400 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.40948 |
401 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.54597 |
402 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 13556.74000 |
403 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6778.37000 |
404 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
405 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
406 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 13556.74000 |
407 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25103.13641 |
408 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
409 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER BOT_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
410 | Coil:Heating:Fuel | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Nominal Capacity [W] | 25103.13641 |
411 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.80485 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
413 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.80485 |
414 | Fan:SystemModel | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 13421.53002 |
415 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.80485 |
416 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.80485 |
417 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.80485 |
418 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 7.80485 |
419 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.80485 |
420 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.90243 |
421 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.20323 |
422 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 129198.04000 |
423 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 64599.02000 |
424 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
425 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
426 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 129198.04000 |
427 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 239277.26937 |
428 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
429 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER MID_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
430 | Coil:Heating:Fuel | AIRLOOP DATACENTER MID HEATING COIL | Design Size Nominal Capacity [W] | 239277.26937 |
431 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.81694 |
432 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
433 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.81694 |
434 | Fan:SystemModel | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1404.83918 |
435 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.81694 |
436 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.81694 |
437 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.81694 |
438 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.81694 |
439 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.81694 |
440 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.40847 |
441 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.54463 |
442 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 13523.23000 |
443 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 6761.61500 |
444 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
445 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
446 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 13523.23000 |
447 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25041.30363 |
448 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 29.11000 |
449 | AirLoopHVAC:UnitarySystem | AIRLOOP DATACENTER TOP_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
450 | Coil:Heating:Fuel | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Nominal Capacity [W] | 25041.30363 |
451 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.11686 |
452 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 24079.64807 |
453 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.11686 |
454 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 14.02268 |
455 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.11686 |
456 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.11686 |
457 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 490502.00177 |
458 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 6.67000 |
459 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.10509E-002 |
460 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.52611 |
461 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.10509E-002 |
462 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 6339.59954 |
463 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
464 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2406244.48529 |
465 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2406244.49000 |
466 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.10509E-002 |
467 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.11686 |
468 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 14.02268 |
469 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 5.84278E-002 |
470 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 11113.86182 |
471 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 5.84278E-002 |
472 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 11113.86182 |
473 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.11686 |
474 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.90350E-002 |
475 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1652822.79454 |
476 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1652772.51000 |
477 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 8.28311E-002 |
478 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.11686 |
479 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.90350E-002 |
480 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1652822.79454 |
481 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1652772.51000 |
482 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 8.28311E-002 |
483 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
484 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
485 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
486 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
487 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
488 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.16566 |
489 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 19.87947 |
490 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.16566 |
491 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 57766.62649 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 76.97901 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1980436.58190 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 15.39580 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 247554.57274 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 76.97901 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1980436.58190 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 15.39580 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 247554.57274 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 21038.18 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 452081.67 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 139227.90 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 15969.87 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11203.46 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 19479.50 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9452.25 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 296712.73 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 197162.46 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 292597.07 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 183916.15 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 39955.03 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 26322.90 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 39536.20 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 25303.92 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 35485.27 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 238953.48 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 19381.46 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94845.68 |
20 | Coil:Heating:Water | AIRLOOP DATACENTER BASEMENT HEATING COIL | 94845.68 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 381370.54 | 234117.70 | 147252.84 | 0.61 | 119413.86 | 1211.16 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 3553437.49 | 2176648.39 | 1376789.09 | 0.61 | 1085729.14 | 11012.07 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 451471.66 | 278237.69 | 173233.97 | 0.62 | 148376.93 | 1504.92 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 230497.43 | 141740.71 | 88756.72 | 0.61 | 82084.77 | 832.55 |
5 | Coil:Cooling:Water | AIRLOOP DATACENTER BASEMENT COOLING COIL | 748460.71 | 517278.94 | 231181.77 | 0.69 | 122020.85 | 1237.60 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER BOT COOLING COIL | 12914.9 | 9.16 | 9.16 | |||
2 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER MID COOLING COIL | 123081.3 | 10.40 | 10.40 | |||
3 | Coil:Cooling:DX:MultiSpeed | AIRLOOP DATACENTER TOP COOLING COIL | 12883.0 | 9.16 | 9.16 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 6.37 | 21.74 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 6.37 | 21.74 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2014642420 | 0.1753502315 | Pass | Pass | 1.0481583669 | 2.6545809502 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1079924586 | 0.2011773781 | Pass | Pass | 0.1326335538 | 0.3378822657 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 6.6667488113E-002 | 0.1324775512 | Pass | Pass | 0.1054008641 | 0.3065523792 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 6.2119005866E-002 | 7.9376553283E-002 | Pass | Pass | 4.9029374972E-002 | 0.2134869433 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1265457326 | 0.2046944100 | Pass | Pass | 0.1331978563 | 0.3366807274 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2061785738 | 0.3265747375 | Pass | Pass | 0.1356719650 | 0.3405043663 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2611687597 | 0.4303539349 | Pass | Pass | 0.1365114395 | 0.3365695734 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2248248247 | 0.4290955586 | Pass | Pass | 0.1334320403 | 0.3305853876 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.8913867980E-002 | 0.1070375169 | Pass | Pass | 0.1048451147 | 0.3042957012 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1466180833 | 0.2193661133 | Pass | Pass | 0.1070773877 | 0.3087190205 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2467501338 | 0.3702685786 | Pass | Pass | 0.1064487901 | 0.3091553696 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1621134683 | 0.2687137480 | Pass | Pass | 0.1033360104 | 0.2946322205 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.6298805677E-002 | 7.4413812737E-002 | Pass | Pass | 4.8244183954E-002 | 0.2111763682 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1066762952 | 0.1440741310 | Pass | Pass | 4.8700941754E-002 | 0.2135998026 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2203019898 | 0.2470954888 | Pass | Pass | 4.9079239250E-002 | 0.2143658375 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1420511344 | 0.2111752675 | Pass | Pass | 4.6582990381E-002 | 0.2013242819 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.3825137844E-002 | 4.5377085567E-002 | Pass | Pass | 0.1546072990 | 0.3642532762 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.5031118228E-002 | 3.2651269816E-002 | Pass | Pass | 0.1309715563 | 0.3544910639 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1331678849 | 0.1224128462 | Pass | Pass | 5.0706270252E-002 | 0.2205461762 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.0419894735E-007 | 9.0856366155E-007 | Pass | Pass | 6.3936607090E-003 | 6.4561219267E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.3284749700E-007 | 3.4461299661E-007 | Pass | Pass | 5.2476727503E-002 | 3.0927196622E-002 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.7322223818E-003 | 5.4702963893E-003 | Pass | Pass | 0.1607230078 | 0.4959226332 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.1710581019E-002 | 2.1308635781E-002 | Pass | Pass | 1.5722854579E-003 | 1.7333654696E-003 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8466.18 | 78.10 | 0.00 | 21837.62 | 22711.92 | 53093.86 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.57_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.57_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 1390.74 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 3.241 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 11.6510 | 2779.43 | 32383.10 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 333.79 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.6510 | 24961.20 | 290822.99 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 2997.66 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.6510 | 2496.12 | 29082.30 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 299.77 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.6510 | 3134.13 | 36515.73 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.6510 | 3134.20 | 36516.53 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 376.39 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.6510 | 2019.75 | 23532.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 242.56 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.6510 | 313.41 | 3651.57 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.6510 | 313.42 | 3651.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 37.64 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.6510 | 201.98 | 2353.21 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 24.26 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 11.6510 | 783.68 | 9130.65 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 94.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 22.3674 | 362.03 | 8097.60 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 83.47 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 22.3674 | 36.20 | 809.76 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 8.35 |
Interior Lighting Total | 11.7515 | 46320.38 | 544334.28 | 1723.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 64082.80 | AstronomicalClock | - | 83.77 | 83.77 | 1007.65 | |
Exterior Lighting Total | 64082.80 | 1007.65 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3263123.84 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2406244.49 | 0.79 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1652772.51 | 6.11 | 1644707.88 | 6.08 | 6.37 | 21.74 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1652772.51 | 6.11 | 1644707.88 | 6.08 | 6.37 | 21.74 |
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1980436.58 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1980436.58 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 231321.81 | 381370.54 | 234117.70 | 147252.84 | 0.61 | - | 119413.86 | 1211.16 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2175743.40 | 3553437.49 | 2176648.39 | 1376789.09 | 0.61 | - | 1085729.14 | 11012.07 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 269348.59 | 451471.66 | 278237.69 | 173233.97 | 0.62 | - | 148376.93 | 1504.92 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 136072.51 | 230497.43 | 141740.71 | 88756.72 | 0.61 | - | 82084.77 | 832.55 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | 459162.04 | 748460.71 | 517278.94 | 231181.77 | 0.69 | - | 122020.85 | 1237.60 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | 13556.74 | 10854.34 | 2702.40 | 0.80 | 3.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | 129198.04 | 103443.70 | 25754.34 | 0.80 | 3.50 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 13523.23 | 10827.51 | 2695.72 | 0.80 | 3.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
AIRLOOP DATACENTER BOT COOLING COIL | 12914.9 | 9.16 | 9.16 | ||||
AIRLOOP DATACENTER MID COOLING COIL | 123081.3 | 10.40 | 10.40 | ||||
AIRLOOP DATACENTER TOP COOLING COIL | 12883.0 | 9.16 | 9.16 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 22156.39 | 21038.18 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 476393.32 | 452081.67 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 146721.91 | 139227.90 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 16829.46 | 15969.87 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11806.49 | 11203.46 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 20527.98 | 19479.50 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 9958.79 | 9452.25 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 312682.83 | 296712.73 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 207774.41 | 197162.46 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 308345.67 | 292597.07 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 193815.17 | 183916.15 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 42105.53 | 39955.03 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 27739.67 | 26322.90 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 41664.15 | 39536.20 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 26665.85 | 25303.92 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 42691.59 | 35485.27 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 276725.65 | 238953.48 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 21639.62 | 19381.46 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94845.68 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | 100000.00 | 94845.68 | - |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | 25103.14 | 0.80 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | 239277.27 | 0.79 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | 25041.30 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 13.75 | 29920.98 | 2176.85 | 1.00 | 1.12 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 127.29 | 278266.25 | 2186.10 | 1.00 | 1.08 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 16.45 | 35807.38 | 2176.85 | 1.00 | 1.11 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
CAV_BAS SZVAV FAN | Fan:VariableVolume | 0.61 | 1337.13 | 8.35 | 18344.66 | 2197.78 | 1.00 | 1.12 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 0.62 | 637.69 | 36.38 | 37573.65 | 1032.69 | 1.00 | 1.20 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.82 | 1408.32 | 1719.64 | 1.00 | 1.34 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 7.80 | 13421.53 | 1719.64 | 1.00 | 1.08 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 966.87 | 0.82 | 1404.84 | 1719.64 | 1.00 | 1.34 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.83 | 0.116856 | 24079.65 | 206063.11 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.021051 | 6339.60 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.058428 | 11113.86 | 190215.15 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 123258.43 | 0.058428 | 11113.86 | 190215.15 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 209234.68 | 0.165662 | 57766.63 | 348701.22 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 86434.71 | 99399.92 | 35.76 | 7.258 | 8.347 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00740 | 28.48 | 0.00686 | 1.200 | 0.00 |
CORE_BOTTOM | 88554.66 | 101837.85 | 40.80 | 7.435 | 8.550 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00735 | 28.48 | 0.00686 | 1.078 | 0.00 |
CORE_MID | 837457.96 | 963076.66 | 385.83 | 70.300 | 80.844 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00737 | 28.48 | 0.00686 | 10.778 | 0.00 |
CORE_TOP | 97095.38 | 111659.69 | 44.73 | 8.222 | 9.455 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00731 | 38.10 | 0.00687 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 16265.40 | 18705.21 | 59.68 | 1.377 | 1.584 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00723 | 38.10 | 0.00687 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 15507.02 | 17833.07 | 88.29 | 1.313 | 1.510 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00715 | 32.42 | 0.00686 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 18407.73 | 21168.89 | 67.54 | 1.559 | 1.793 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00720 | 37.88 | 0.00687 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 20145.46 | 23167.28 | 114.70 | 1.706 | 1.962 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 24.00 | 24.00 | 0.00712 | 36.80 | 0.00687 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 155828.74 | 179203.05 | 571.78 | 13.195 | 15.174 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00723 | 38.10 | 0.00687 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 159802.58 | 183772.97 | 909.88 | 13.531 | 15.561 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00714 | 32.79 | 0.00686 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 174983.62 | 201231.16 | 642.05 | 14.817 | 17.040 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00720 | 37.88 | 0.00687 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 176814.85 | 203337.08 | 1006.74 | 14.972 | 17.218 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00713 | 36.63 | 0.00687 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 19338.23 | 22238.97 | 70.96 | 1.637 | 1.883 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00718 | 37.97 | 0.00687 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16768.78 | 19284.10 | 95.48 | 1.420 | 1.633 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00714 | 33.48 | 0.00686 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 21095.39 | 24259.69 | 77.40 | 1.786 | 2.054 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00717 | 38.10 | 0.00687 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 20036.15 | 23041.57 | 114.08 | 1.697 | 1.951 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00712 | 36.63 | 0.00687 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8410.01 | 9671.51 | 267.15 | 0.712 | 0.819 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 27.00 | 27.00 | 0.00707 | 34.33 | 0.00687 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 80148.33 | 92170.58 | 2545.96 | 6.787 | 7.805 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 27.00 | 27.00 | 0.00707 | 34.01 | 0.00686 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8389.23 | 9647.61 | 266.49 | 0.710 | 0.817 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 27.00 | 27.00 | 0.00707 | 36.63 | 0.00687 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 373636.21 | 429681.64 | 548.29 | 31.638 | 36.384 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00703 | 26.27 | 0.00685 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 24.49 | 0.00281 | -5.20 | 0.00281 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | 19.60 | 22.09 | 0.00281 | -5.20 | 0.00281 | 1.078 | 0.00 |
CORE_MID | 213521.11 | 266901.39 | 106.93 | 17.530 | 21.912 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 10.778 | 0.00 |
CORE_TOP | 68203.99 | 85254.99 | 34.15 | 5.693 | 7.116 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 7825.70 | 9782.13 | 31.21 | 0.653 | 0.816 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -5.20 | 0.00281 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 5488.64 | 6860.80 | 33.97 | 0.458 | 0.573 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -5.20 | 0.00281 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 9539.79 | 11924.73 | 38.05 | 0.797 | 0.996 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -5.20 | 0.00281 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 3902.70 | 4878.37 | 24.15 | 0.325 | 0.406 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -5.20 | 0.00281 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 145175.00 | 181468.75 | 579.01 | 12.157 | 15.196 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00786 | -5.20 | 0.00281 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 96462.06 | 120577.58 | 596.99 | 8.079 | 10.098 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00786 | -5.20 | 0.00281 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 143165.40 | 178956.75 | 570.98 | 11.988 | 14.985 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00786 | -5.20 | 0.00281 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 89993.20 | 112491.50 | 556.96 | 7.535 | 9.418 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -5.20 | 0.00281 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 19540.42 | 24425.52 | 77.93 | 1.638 | 2.048 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -5.20 | 0.00281 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 12873.15 | 16091.43 | 79.67 | 1.079 | 1.349 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -5.20 | 0.00281 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 19335.89 | 24169.86 | 77.12 | 1.621 | 2.026 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -5.20 | 0.00281 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 12375.44 | 15469.29 | 76.59 | 1.037 | 1.297 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00786 | -5.20 | 0.00281 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | 18.00 | 26.27 | 0.00700 | -5.20 | 0.00281 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 23.21 | 0.00412 | -5.20 | 0.00281 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 20.65 | 0.00330 | -5.20 | 0.00281 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 18.00 | 27.00 | 0.00700 | -5.20 | 0.00281 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 13.75 | 13.75 | 3.87 | 3.87 | 13.7451 | 4.6195 | 13.7451 | 0.3361 | 0.3000 |
VAV_MID WITH REHEAT | 127.29 | 127.29 | 71.61 | 71.61 | 127.2887 | 71.6093 | 127.2887 | 0.5626 | 0.3000 |
VAV_TOP WITH REHEAT | 16.45 | 16.45 | 13.84 | 13.84 | 16.4492 | 13.8354 | 16.4492 | 0.8411 | 0.3000 |
CAV_BAS | 8.35 | 8.35 | 1.20 | 1.20 | 8.3469 | 2.5041 | 8.3469 | 0.3000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 36.38 | 36.38 | 0.34 | 0.34 | 36.3841 | 18.1918 | 36.3841 | 0.5000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.82 | 0.82 | 0.02 | 0.02 | 0.8190 | 0.8190 | 0.8190 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 7.80 | 7.80 | 0.16 | 0.16 | 7.8049 | 7.8049 | 7.8049 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.82 | 0.82 | 0.02 | 0.02 | 0.8169 | 0.8169 | 0.8169 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 22156.393 | 22156.393 | 2.565095 | 0.00019383 | 446.984 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | 22156.39 | 22156.39 | 2.565095 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 0.00 | 0.00 | 22266.79 | 22266.79 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 476393.316 | 476393.316 | 24.253329 | 0.00416770 | 10989.685 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 476393.32 | 476393.32 | 24.253329 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8526 | 266901.39 | 0.00 | 478588.93 | 478588.93 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 146721.906 | 146721.906 | 7.116163 | 0.00128359 | 3429.154 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 146721.91 | 146721.91 | 7.116163 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 85254.99 | 0.00 | 147394.43 | 147394.43 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 16829.460 | 16829.460 | 0.816147 | 0.00014723 | 393.348 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16829.46 | 16829.46 | 0.816147 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00785406 | 44.0458 | 9782.13 | 0.00 | 16906.60 | 16906.60 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 11806.492 | 11806.492 | 0.572735 | 0.00010329 | 275.924 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11806.49 | 11806.49 | 0.572735 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00787206 | 44.1454 | 6860.80 | 0.00 | 11860.61 | 11860.61 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 20527.983 | 20527.983 | 0.996241 | 0.00017959 | 479.694 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20527.98 | 20527.98 | 0.996241 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00789892 | 44.2939 | 11924.73 | 0.00 | 20622.08 | 20622.08 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 9958.794 | 9958.794 | 0.588513 | 0.00008712 | 221.778 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9958.79 | 9958.79 | 0.588513 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00772720 | 43.3437 | 4878.37 | 0.00 | 10005.90 | 10005.90 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 312682.833 | 312682.833 | 15.195955 | 0.00273549 | 7303.876 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 312682.83 | 311061.98 | 15.195955 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00785883 | 44.0726 | 181468.75 | 0.00 | 314116.39 | 314116.39 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 207774.407 | 207774.407 | 10.098325 | 0.00181770 | 4853.244 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 207774.41 | 207774.41 | 10.098325 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00785837 | 44.0702 | 120577.58 | 0.00 | 208727.00 | 208727.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 308345.673 | 308345.673 | 14.984638 | 0.00269754 | 7202.637 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 308345.67 | 308345.67 | 14.984638 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00785687 | 44.0618 | 178956.75 | 0.00 | 309759.34 | 309759.34 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 193815.169 | 193815.169 | 9.418332 | 0.00169558 | 4527.387 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 193815.17 | 193815.17 | 9.418332 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00784848 | 44.0154 | 112491.50 | 0.00 | 194703.74 | 194703.74 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 42105.528 | 42105.528 | 2.047517 | 0.00036836 | 983.366 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 42105.53 | 41912.78 | 2.047517 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00786875 | 44.1279 | 24425.52 | 0.00 | 42298.58 | 42298.58 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 27739.674 | 27739.674 | 1.348987 | 0.00024268 | 647.847 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 27739.67 | 27739.67 | 1.348987 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00786716 | 44.1191 | 16091.43 | 0.00 | 27866.86 | 27866.86 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 41664.153 | 41664.153 | 2.026015 | 0.00036450 | 973.063 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 41664.15 | 41664.15 | 2.026015 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00786741 | 44.1204 | 24169.86 | 0.00 | 41855.18 | 41855.18 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 26665.852 | 26665.852 | 1.296690 | 0.00023328 | 622.778 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 26665.85 | 26665.85 | 1.296690 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00786220 | 44.0916 | 15469.29 | 0.00 | 26788.11 | 26788.11 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 231321.810 | -999.000 | 13.745085 | 0.00826228 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 231321.81 | 224490.81 | 13.745085 | 26.08 | 14.59 | 0.00723613 | 10.84 | 8.50 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 14.7726 | 24.00 | 0.00729937 | 34.1451 | 141086.30 | 0.00 | 263148.76 | 253956.46 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 42691.587 | 42691.587 | 4.123525 | 0.00037348 | 730.918 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 42691.59 | 42691.59 | 4.123525 | 3.02 | 1.41 | 0.00417007 | 12.89 | 10.37 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 49.2418 | 20.71 | 0.00541173 | 31.0239 | 16005.01 | 0.00 | 42945.34 | 42945.34 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2175743.399 | -999.000 | 127.288708 | 0.07771251 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2175743.40 | 2108088.96 | 127.288708 | 26.28 | 14.67 | 0.00725158 | 10.83 | 8.50 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 15.9527 | 24.00 | 0.00732507 | 34.2639 | 1287090.87 | 0.00 | 2471173.67 | 2379864.88 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 276725.648 | 276725.648 | 38.186612 | 0.00242092 | 4833.465 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:20:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 276725.65 | 276725.65 | 38.186612 | 5.98 | 4.07 | 0.00506382 | 12.89 | 10.37 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 53.1757 | 18.62 | 0.00772195 | 50.2179 | 131400.56 | 0.00 | 289245.18 | 289245.18 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 269348.591 | -999.000 | 16.449172 | 0.00962051 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 269348.59 | 262424.38 | 16.449172 | 25.74 | 14.44 | 0.00720122 | 10.84 | 8.50 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 12.3441 | 24.00 | 0.00724775 | 33.9063 | 168636.68 | 0.00 | 307218.35 | 297845.70 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 21639.616 | 21639.616 | 4.934752 | 0.00018931 | 385.499 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 01:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21639.62 | 21639.62 | 4.934752 | 8.71 | 6.05 | 0.00562872 | 12.89 | 10.37 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 41.1470 | 16.83 | 0.00781509 | 56.8634 | 13706.42 | 0.00 | 23462.96 | 23462.96 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 136072.511 | -999.000 | 8.346900 | 0.00486019 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 136072.51 | 130306.48 | 8.346900 | 25.73 | 14.56 | 0.00733727 | 10.82 | 8.50 | 0.00700000 | 35.11 | 0.00686670 | 17.25 | 14.3785 | 24.00 | 0.00742425 | 34.7227 | 79006.45 | 0.00 | 159129.65 | 151223.49 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.503383 | 0.00087484 | 2621.212 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 100000.00 | 100000.00 | 3.503383 | -0.75 | -2.65 | 0.00280840 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 34.2571 | 24.56 | 0.00280840 | 12.7928 | 0.00 | 0.00 | 100048.86 | 100048.86 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 459162.042 | -999.000 | 36.384080 | 0.01640020 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 459162.04 | 457406.74 | 36.384080 | 27.10 | 14.77 | 0.00703132 | 14.92 | 10.20 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 0.9301 | 27.00 | 0.00703282 | 27.5424 | 373179.65 | 0.00 | 540998.06 | 540998.06 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 100000.000 | 100000.000 | 3.503383 | 0.00087484 | 2621.212 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 100000.00 | 100000.00 | 3.503383 | -0.05 | -0.05 | 0.00696102 | 29.11 | 16.23 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 9.6590 | 27.00 | 0.00700000 | 27.4118 | 0.00 | 0.00 | 100048.86 | 100048.86 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER BOT | 13556.740 | 10854.339 | 0.818960 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 6778.37 | 6726.25 | 0.545973 | 27.14 | 14.81 | 0.00706337 | 14.27 | 9.94 | 0.00700000 | 34.66 | 0.00686598 | 17.11 | 2.8632 | 27.00 | 0.00706721 | 27.6741 | 8406.25 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER BOT | 25103.136 | 25103.136 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 25103.14 | 25103.14 | 0.818963 | -0.10 | -0.10 | 0.00691996 | 29.11 | 16.23 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 1.9088 | 26.71 | 0.00699997 | 27.8828 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER MID | 129198.040 | 103443.703 | 7.804850 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 64599.02 | 64078.75 | 5.203233 | 27.15 | 14.81 | 0.00706640 | 14.27 | 9.94 | 0.00700000 | 34.33 | 0.00686546 | 17.01 | 3.0044 | 27.00 | 0.00707051 | 27.6870 | 80147.03 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER MID | 239277.269 | 239277.269 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 239277.27 | 239277.27 | 7.804853 | -0.10 | -0.43 | 0.00408937 | 29.11 | 16.23 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 2.0029 | 24.34 | 0.00411555 | 18.9587 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | AIRLOOP DATACENTER TOP | 13523.230 | 10827.509 | 0.816940 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 6761.61 | 6709.51 | 0.544627 | 27.19 | 14.83 | 0.00706364 | 14.27 | 9.94 | 0.00700000 | 36.80 | 0.00686940 | 17.78 | 2.8703 | 27.00 | 0.00706743 | 27.6749 | 8388.54 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | AIRLOOP DATACENTER TOP | 25041.304 | 25041.304 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 25041.30 | 25041.30 | 0.816938 | -0.10 | -1.58 | 0.00328647 | 29.11 | 16.23 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 1.9135 | 22.66 | 0.00329579 | 16.8174 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 22156.393 | 22156.393 | 2.565095 | 0.00019383 | 446.984 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.04872905 | 54.44 | 82.22 | 27.78 | 2454671.11 | 0.9026 | 0.920787 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | Sensible | 22156.39 | 22156.39 | 1.0000 | 2.67881022 | 2.565095 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.19381402 | 60.00 | 32.22 | 27.78 | 0.000 | 22156.39 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 0.00 | 0.00 | 22266.79 | 22266.79 | 2.67881022 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 20.95 | 14.83 | 0.00800000 | 41372.0 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 476393.316 | 476393.316 | 24.253329 | 0.00416770 | 10989.685 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.04872905 | 54.44 | 82.22 | 27.78 | 2454671.11 | 19.4076 | 19.798209 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 476393.32 | 476393.32 | 1.0000 | 25.32852056 | 24.253329 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 4.16727140 | 60.00 | 32.22 | 27.78 | 0.000 | 476393.32 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.84 | 0.00800000 | 21.00 | 0.00800000 | 44.8526 | 266901.39 | 0.00 | 478588.93 | 478588.93 | 25.32852056 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.33 | 18.48 | 0.00800000 | 51955.1 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 146721.906 | 146721.906 | 7.116163 | 0.00128359 | 3429.154 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.04872905 | 54.44 | 82.22 | 27.78 | 2454671.11 | 5.9773 | 6.097548 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 146721.91 | 146721.91 | 1.0000 | 7.43163435 | 7.116163 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 1.28345630 | 60.00 | 32.22 | 27.78 | 0.000 | 146721.91 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 85254.99 | 0.00 | 147394.43 | 147394.43 | 7.43163435 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.25 | 18.78 | 0.00800000 | 52893.2 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16829.460 | 16829.460 | 0.816147 | 0.00014723 | 393.348 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.04872905 | 54.44 | 82.22 | 27.78 | 2454671.11 | 0.6856 | 0.699408 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16829.46 | 16829.46 | 1.0000 | 0.85232779 | 0.816147 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.14721644 | 60.00 | 32.22 | 27.78 | 0.000 | 16829.46 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.91 | 0.00785406 | 21.00 | 0.00785406 | 44.0458 | 9782.13 | 0.00 | 16906.60 | 16906.60 | 0.85232779 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.25 | 18.78 | 0.00800000 | 52895.6 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11806.492 | 11806.492 | 0.572735 | 0.00010329 | 275.924 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.04872905 | 54.44 | 82.22 | 27.78 | 2454671.11 | 0.4810 | 0.490661 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11806.49 | 11806.49 | 1.0000 | 0.59812545 | 0.572735 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.10327781 | 60.00 | 32.22 | 27.78 | 0.000 | 11806.49 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00787206 | 21.00 | 0.00787206 | 44.1454 | 6860.80 | 0.00 | 11860.61 | 11860.61 | 0.59812545 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.25 | 18.78 | 0.00800000 | 52889.5 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20527.983 | 20527.983 | 0.996241 | 0.00017959 | 479.694 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.04872905 | 54.44 | 82.22 | 27.78 | 2454671.11 | 0.8363 | 0.853113 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 20527.98 | 20527.98 | 1.0000 | 1.04040593 | 0.996241 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.17956943 | 60.00 | 32.22 | 27.78 | 0.000 | 20527.98 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00789892 | 21.00 | 0.00789892 | 44.2939 | 11924.73 | 0.00 | 20622.08 | 20622.08 | 1.04040593 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.24 | 18.77 | 0.00800000 | 52881.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9958.794 | 9958.794 | 0.588513 | 0.00008712 | 221.778 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.04872905 | 54.44 | 82.22 | 27.78 | 2454671.11 | 0.4057 | 0.413873 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9958.79 | 9958.79 | 1.0000 | 0.61460280 | 0.588513 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.08711499 | 60.00 | 32.22 | 27.78 | 0.000 | 9958.79 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.91 | 0.00772720 | 21.00 | 0.00772720 | 43.3437 | 4878.37 | 0.00 | 10005.90 | 10005.90 | 0.61460280 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.77 | 17.62 | 0.00800000 | 49340.1 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 312682.833 | 312682.833 | 15.195955 | 0.00273549 | 7303.876 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.04872905 | 54.44 | 82.22 | 27.78 | 2454671.11 | 12.7383 | 12.994641 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 312682.83 | 311061.98 | 1.0000 | 15.86961806 | 15.195955 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 2.73520678 | 60.00 | 32.22 | 27.78 | 0.000 | 312682.83 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00785883 | 21.00 | 0.00785883 | 44.0726 | 181468.75 | 0.00 | 314116.39 | 314116.39 | 15.86961806 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52853.4 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 207774.407 | 207774.407 | 10.098325 | 0.00181770 | 4853.244 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.04872905 | 54.44 | 82.22 | 27.78 | 2454671.11 | 8.4644 | 8.634800 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 207774.41 | 207774.41 | 1.0000 | 10.54600101 | 10.098325 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 1.81751573 | 60.00 | 32.22 | 27.78 | 0.000 | 207774.41 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00785837 | 21.00 | 0.00785837 | 44.0702 | 120577.58 | 0.00 | 208727.00 | 208727.00 | 10.54600101 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52851.9 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 308345.673 | 308345.673 | 14.984638 | 0.00269754 | 7202.637 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.04872905 | 54.44 | 82.22 | 27.78 | 2454671.11 | 12.5616 | 12.814395 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 308345.67 | 308345.67 | 1.0000 | 15.64893330 | 14.984638 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 2.69726728 | 60.00 | 32.22 | 27.78 | 0.000 | 308345.67 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00785687 | 21.00 | 0.00785687 | 44.0618 | 178956.75 | 0.00 | 309759.34 | 309759.34 | 15.64893330 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52854.1 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 193815.169 | 193815.169 | 9.418332 | 0.00169558 | 4527.387 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.04872905 | 54.44 | 82.22 | 27.78 | 2454671.11 | 7.8958 | 8.054675 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 193815.17 | 193815.17 | 1.0000 | 9.83586272 | 9.418332 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 1.69540668 | 60.00 | 32.22 | 27.78 | 0.000 | 193815.17 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00784848 | 21.00 | 0.00784848 | 44.0154 | 112491.50 | 0.00 | 194703.74 | 194703.74 | 9.83586272 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52855.1 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 42105.528 | 42105.528 | 2.047517 | 0.00036836 | 983.366 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.04872905 | 54.44 | 82.22 | 27.78 | 2454671.11 | 1.7153 | 1.749844 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 42105.53 | 41912.78 | 1.0000 | 2.13828725 | 2.047517 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.36831995 | 60.00 | 32.22 | 27.78 | 0.000 | 42105.53 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.94 | 0.00786875 | 21.00 | 0.00786875 | 44.1279 | 24425.52 | 0.00 | 42298.58 | 42298.58 | 2.13828725 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52841.4 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 27739.674 | 27739.674 | 1.348987 | 0.00024268 | 647.847 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.04872905 | 54.44 | 82.22 | 27.78 | 2454671.11 | 1.1301 | 1.152820 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 27739.67 | 27739.67 | 1.0000 | 1.40878980 | 1.348987 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.24265401 | 60.00 | 32.22 | 27.78 | 0.000 | 27739.67 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.94 | 0.00786716 | 21.00 | 0.00786716 | 44.1191 | 16091.43 | 0.00 | 27866.86 | 27866.86 | 1.40878980 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52840.5 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 41664.153 | 41664.153 | 2.026015 | 0.00036450 | 973.063 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.04872905 | 54.44 | 82.22 | 27.78 | 2454671.11 | 1.6973 | 1.731501 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 41664.15 | 41664.15 | 1.0000 | 2.11583160 | 2.026015 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.36445901 | 60.00 | 32.22 | 27.78 | 0.000 | 41664.15 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.94 | 0.00786741 | 21.00 | 0.00786741 | 44.1204 | 24169.86 | 0.00 | 41855.18 | 41855.18 | 2.11583160 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52841.7 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26665.852 | 26665.852 | 1.296690 | 0.00023328 | 622.778 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.04872905 | 54.44 | 82.22 | 27.78 | 2454671.11 | 1.0863 | 1.108194 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 26665.85 | 26665.85 | 1.0000 | 1.35417422 | 1.296690 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.23326070 | 60.00 | 32.22 | 27.78 | 0.000 | 26665.85 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00786220 | 21.00 | 0.00786220 | 44.0916 | 15469.29 | 0.00 | 26788.11 | 26788.11 | 1.35417422 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52841.7 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 231321.810 | -999.000 | 13.745085 | 0.00826228 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.2916 | 1004.8586 | 1.0443 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 13.745085 | 14.35442791 | 4197.9300 | 999.8980 | 116.84377819 | 13.34 | 6.67 | 6.67 | 3271648.35 | 7.0705 | 7.070497 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 231321.81 | 224490.81 | 1.0000 | 14.35442791 | 13.745085 | 26.08 | 14.59 | 0.00723613 | 44657.1 | 10.84 | 8.50 | 0.00700000 | 28542.0 | 8.26143623 | 6.67 | 13.34 | 6.67 | 29920.985 | 201400.82 | 38.10 | 0.00687148 | 18.17 | 2.03050000 | 14.7726 | 24.00 | 0.00729937 | 24.00 | 0.00729937 | 34.1451 | 141086.30 | 0.00 | 263148.76 | 253956.46 | 14.35442791 | 26.08 | 16.04 | 0.00723613 | 44657.1 | 8.71 | 8.70 | 0.00698172 | 26324.8 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 42691.587 | 42691.587 | 4.123525 | 0.00037348 | 730.918 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 13.745085 | 14.35442791 | 4197.9300 | 999.8980 | 21.04872905 | 54.44 | 82.22 | 27.78 | 2454671.11 | 1.7392 | 1.774200 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 42691.59 | 42691.59 | 1.0000 | 4.30632837 | 4.123525 | 3.02 | 1.41 | 0.00417007 | 13490.3 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 0.37344653 | 60.00 | 32.22 | 27.78 | 0.000 | 42691.59 | -5.20 | 0.00280840 | -5.20 | 2.03050000 | 49.2418 | 11.00 | 0.00549106 | 20.71 | 0.00541173 | 31.0239 | 16005.01 | 0.00 | 42945.34 | 42945.34 | 4.30632837 | 2.80 | 2.18 | 0.00417007 | 13264.3 | 12.65 | 7.31 | 0.00417007 | 23237.0 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2175743.399 | -999.000 | 127.288708 | 0.07771251 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3203 | 1004.8586 | 1.0443 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 127.288708 | 132.93163670 | 4197.9300 | 999.8980 | 116.84377819 | 13.34 | 6.67 | 6.67 | 3271648.35 | 66.5030 | 66.502972 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2175743.40 | 2108088.96 | 1.0000 | 132.93163670 | 127.288708 | 26.28 | 14.67 | 0.00725158 | 44900.6 | 10.83 | 8.50 | 0.00700000 | 28533.2 | 77.70458549 | 6.67 | 13.34 | 6.67 | 278266.247 | 1897477.15 | 38.10 | 0.00687148 | 18.17 | 20.30600000 | 15.9527 | 24.00 | 0.00732507 | 24.00 | 0.00732507 | 34.2639 | 1287090.87 | 0.00 | 2471173.67 | 2379864.88 | 132.93163670 | 26.28 | 16.12 | 0.00725158 | 44900.6 | 8.70 | 8.70 | 0.00697869 | 26310.8 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 276725.648 | 276725.648 | 38.186612 | 0.00242092 | 4833.465 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 127.288708 | 132.93163670 | 4197.9300 | 999.8980 | 21.04872905 | 54.44 | 82.22 | 27.78 | 2454671.11 | 11.2734 | 11.500313 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:20:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 276725.65 | 276725.65 | 1.0000 | 39.87949101 | 38.186612 | 5.98 | 4.07 | 0.00506382 | 18733.0 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 2.42066973 | 60.00 | 32.22 | 27.78 | 0.000 | 276725.65 | -5.20 | 0.00280840 | -5.20 | 20.30600000 | 53.1757 | 18.68 | 0.00762518 | 18.62 | 0.00772195 | 50.2179 | 131400.56 | 0.00 | 289245.18 | 289245.18 | 39.87949101 | 2.80 | 2.80 | 0.00506382 | 15504.2 | 9.95 | 7.07 | 0.00506382 | 22757.2 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 269348.591 | -999.000 | 16.449172 | 0.00962051 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.2267 | 1004.8586 | 1.0443 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 16.449172 | 17.17839204 | 4197.9300 | 999.8980 | 116.84377819 | 13.34 | 6.67 | 6.67 | 3271648.35 | 8.2328 | 8.232810 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 269348.59 | 262424.38 | 1.0000 | 17.17839204 | 16.449172 | 25.74 | 14.44 | 0.00720122 | 44221.4 | 10.84 | 8.50 | 0.00700000 | 28541.9 | 9.61952619 | 6.67 | 13.34 | 6.67 | 35807.377 | 233541.21 | 38.10 | 0.00687148 | 18.17 | 2.03050000 | 12.3441 | 24.00 | 0.00724775 | 24.00 | 0.00724775 | 33.9063 | 168636.68 | 0.00 | 307218.35 | 297845.70 | 17.17839204 | 25.74 | 15.88 | 0.00720122 | 44221.4 | 8.71 | 8.71 | 0.00698446 | 26337.4 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 21639.616 | 21639.616 | 4.934752 | 0.00018931 | 385.499 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 16.449172 | 17.17839204 | 4197.9300 | 999.8980 | 21.04872905 | 54.44 | 82.22 | 27.78 | 2454671.11 | 0.8816 | 0.899311 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 01:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21639.62 | 21639.62 | 1.0000 | 5.15351761 | 4.934752 | 8.71 | 6.05 | 0.00562872 | 22920.6 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 0.18929349 | 60.00 | 32.22 | 27.78 | 0.000 | 21639.62 | -5.20 | 0.00280840 | -5.20 | 2.03050000 | 41.1470 | 18.44 | 0.00760055 | 16.83 | 0.00781509 | 56.8634 | 13706.42 | 0.00 | 23462.96 | 23462.96 | 5.15351761 | 2.80 | 2.80 | 0.00562872 | 16919.9 | 7.28 | 6.44 | 0.00562872 | 21472.8 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 136072.511 | -999.000 | 8.346900 | 0.00486019 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4796 | 1004.8586 | 1.0443 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 8.346900 | 8.71693239 | 4197.9300 | 999.8980 | 116.84377819 | 13.34 | 6.67 | 6.67 | 3271648.35 | 4.1591 | 4.159142 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 136072.51 | 130306.48 | 1.0000 | 8.71693239 | 8.346900 | 25.73 | 14.56 | 0.00733727 | 44557.5 | 10.82 | 8.50 | 0.00700000 | 28522.4 | 4.85969901 | 6.67 | 13.34 | 6.67 | 18344.658 | 117727.85 | 35.11 | 0.00686670 | 17.25 | 1.20015641 | 14.3785 | 24.00 | 0.00742425 | 24.00 | 0.00742425 | 34.7227 | 79006.45 | 0.00 | 159129.65 | 151223.49 | 8.71693239 | 25.73 | 16.00 | 0.00733727 | 44557.5 | 8.70 | 8.69 | 0.00697694 | 26302.3 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.503383 | 0.00087484 | 2621.212 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | CAV_BAS SZVAV FAN | Fan:VariableVolume | 8.346900 | 8.71693239 | 4197.9300 | 999.8980 | 21.04872905 | 54.44 | 82.22 | 27.78 | 2454671.11 | 4.0739 | 4.155854 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.503383 | -0.75 | -2.65 | 0.00280840 | 6268.4 | 32.11 | 17.18 | 0.00800000 | 52750.5 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -5.20 | 0.00280840 | -5.20 | 1.20015641 | 34.2571 | 0.00 | 0.00280840 | 24.56 | 0.00280840 | 12.7928 | 0.00 | 0.00 | 100048.86 | 100048.86 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.01 | 14.59 | 0.00000000 | 40232.7 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 459162.042 | -999.000 | 36.384080 | 0.01640020 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9109 | 1004.8586 | 1.0443 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 36.384080 | 37.99704877 | 4197.9300 | 999.8980 | 116.84377819 | 13.34 | 6.67 | 6.67 | 3271648.35 | 14.0346 | 14.034578 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 459162.04 | 457406.74 | 1.0000 | 37.99704877 | 36.384080 | 27.10 | 14.77 | 0.00703132 | 45171.5 | 14.92 | 10.20 | 0.00700000 | 32690.3 | 16.39853127 | 6.67 | 13.34 | 6.67 | 37573.647 | 421588.39 | 38.10 | 0.00687148 | 18.17 | 0.33839277 | 0.9301 | 27.00 | 0.00703282 | 27.00 | 0.00703282 | 27.5424 | 373179.65 | 0.00 | 540998.06 | 540998.06 | 37.99704877 | 27.10 | 16.22 | 0.00703132 | 45171.5 | 13.11 | 10.73 | 0.00703132 | 30933.6 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.503383 | 0.00087484 | 2621.212 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | AIRLOOP DATACENTER BASEMENT SYS11 FAN | Fan:VariableVolume | 36.384080 | 37.99704877 | 4197.9300 | 999.8980 | 21.04872905 | 54.44 | 82.22 | 27.78 | 2454671.11 | 4.0739 | 4.155854 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.503383 | -0.05 | -0.05 | 0.00696102 | 17359.9 | 29.11 | 16.23 | 0.00800000 | 49691.3 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -5.20 | 0.00280840 | -5.20 | 0.33839277 | 9.6590 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 27.4118 | 0.00 | 0.00 | 100048.86 | 100048.86 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.01 | 14.59 | 0.00000000 | 40232.7 | |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13556.740 | 10854.339 | 0.818960 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9705 | 1004.8586 | 1.0443 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.818963 | 0.85526858 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | Sensible | 6778.37 | 6726.25 | 1.0000 | 0.57017728 | 0.545973 | 27.14 | 14.81 | 0.00706337 | 45297.8 | 14.27 | 9.94 | 0.00700000 | 32032.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6778.37 | 34.66 | 0.00686598 | 17.11 | 0.01563234 | 2.8632 | 27.00 | 0.00706721 | 27.00 | 0.00706721 | 27.6741 | 8406.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25103.136 | 25103.136 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.818963 | 0.85526858 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 25103.14 | 25103.14 | 1.0000 | 0.85526858 | 0.818963 | -0.10 | -0.10 | 0.00691996 | 17205.4 | 29.11 | 16.23 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25103.14 | -5.20 | 0.00280840 | -5.20 | 0.01563234 | 1.9088 | 0.00 | 0.00699997 | 26.71 | 0.00699997 | 27.8828 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 129198.040 | 103443.703 | 7.804850 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9761 | 1004.8586 | 1.0443 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.804853 | 8.15085613 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | Sensible | 64599.02 | 64078.75 | 1.0000 | 5.43390168 | 5.203233 | 27.15 | 14.81 | 0.00706640 | 45306.1 | 14.27 | 9.94 | 0.00700000 | 32032.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 64599.02 | 34.33 | 0.00686546 | 17.01 | 0.15632344 | 3.0044 | 27.00 | 0.00707051 | 27.00 | 0.00707051 | 27.6870 | 80147.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 239277.269 | 239277.269 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.804853 | 8.15085613 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 239277.27 | 239277.27 | 1.0000 | 8.15085613 | 7.804853 | -0.10 | -0.43 | 0.00408937 | 10121.8 | 29.11 | 16.23 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 239277.27 | -5.20 | 0.00280840 | -5.20 | 0.15632344 | 2.0029 | 0.00 | 0.00411555 | 24.34 | 0.00411555 | 18.9587 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13523.230 | 10827.509 | 0.816940 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9710 | 1004.8586 | 1.0443 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.816938 | 0.85315475 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | Sensible | 6761.61 | 6709.51 | 1.0000 | 0.56877091 | 0.544627 | 27.19 | 14.83 | 0.00706364 | 45340.6 | 14.27 | 9.94 | 0.00700000 | 32032.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6761.61 | 36.80 | 0.00686940 | 17.78 | 0.01563234 | 2.8703 | 27.00 | 0.00706743 | 27.00 | 0.00706743 | 27.6749 | 8388.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25041.304 | 25041.304 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.816938 | 0.85315475 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 25041.30 | 25041.30 | 1.0000 | 0.85315475 | 0.816938 | -0.10 | -1.58 | 0.00328647 | 8118.7 | 29.11 | 16.23 | 0.00800000 | 49691.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25041.30 | -5.20 | 0.00280840 | -5.20 | 0.01563234 | 1.9135 | 0.00 | 0.00329579 | 22.66 | 0.00329579 | 16.8174 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 13.75 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 127.29 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | FixedDryBulb | 0.00 | 16.45 | - | |||
CAV_BAS_OA_CONTROLLER | FixedDryBulb | 1.20 | 8.35 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 36.38 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2866.17 | 1343.33 | 40.67 |
CORE_BOTTOM | 2663.17 | 1320.33 | 363.17 |
CORE_MID | 2160.33 | 2672.67 | 500.50 |
CORE_TOP | 2541.83 | 3519.33 | 955.83 |
PERIMETER_BOT_ZN_3 | 2412.83 | 3043.50 | 301.83 |
PERIMETER_BOT_ZN_2 | 2630.00 | 2817.50 | 335.67 |
PERIMETER_BOT_ZN_1 | 3088.33 | 2179.50 | 399.83 |
PERIMETER_BOT_ZN_4 | 3112.33 | 2428.00 | 377.17 |
PERIMETER_MID_ZN_3 | 2847.33 | 3651.83 | 1090.83 |
PERIMETER_MID_ZN_2 | 2395.17 | 2853.67 | 730.67 |
PERIMETER_MID_ZN_1 | 3112.17 | 2520.17 | 669.33 |
PERIMETER_MID_ZN_4 | 2779.83 | 3383.00 | 804.50 |
PERIMETER_TOP_ZN_3 | 3386.83 | 3984.00 | 1820.67 |
PERIMETER_TOP_ZN_2 | 3336.00 | 3463.17 | 1404.67 |
PERIMETER_TOP_ZN_1 | 3346.67 | 2986.83 | 1191.67 |
PERIMETER_TOP_ZN_4 | 3239.67 | 3754.17 | 1495.00 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1486.67 | 1486.67 |
DATACENTER_MID_ZN_6 | 5885.33 | 616.17 | 616.17 |
DATACENTER_TOP_ZN_6 | 5421.67 | 1033.67 | 988.00 |
DATACENTER_BASEMENT_ZN_6 | 5927.33 | 4310.67 | 4306.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5942.00 | 5187.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 34.50 | 0.00 | 0.50 |
CORE_BOTTOM | 0.00 | 0.50 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.67 | 0.00 | 0.33 |
PERIMETER_BOT_ZN_2 | 0.00 | 29.00 | 0.00 | 29.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 39.83 | 0.00 | 39.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 73.67 | 0.00 | 41.00 |
PERIMETER_MID_ZN_3 | 5.83 | 0.33 | 0.00 | 0.17 |
PERIMETER_MID_ZN_2 | 6.00 | 30.33 | 0.00 | 30.33 |
PERIMETER_MID_ZN_1 | 2.67 | 34.33 | 0.00 | 34.33 |
PERIMETER_MID_ZN_4 | 4.17 | 38.50 | 0.00 | 24.17 |
PERIMETER_TOP_ZN_3 | 35.00 | 4.33 | 2.00 | 3.33 |
PERIMETER_TOP_ZN_2 | 34.00 | 45.83 | 1.17 | 44.83 |
PERIMETER_TOP_ZN_1 | 26.83 | 33.17 | 0.83 | 31.33 |
PERIMETER_TOP_ZN_4 | 23.33 | 43.50 | 0.17 | 27.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 104.50 | 0.00 | 35.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 40.00 | 391.33 | 2.00 | 238.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 1.136 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 1.079 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.862 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.826 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 1.181 | 0.040 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.852 | 0.041 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 1.794 | 0.040 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 2.334 | 0.041 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 1.060 | 0.093 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.737 | 0.103 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 1.651 | 0.094 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.888 | 0.097 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 1.266 | 0.116 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.747 | 0.120 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 1.682 | 0.116 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.966 | 0.120 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 22.114 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.11 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.51 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1029.47 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 46236077.80 | 0.00 | 46236077.80 | 0.00 | 46236077.80 | 37848132.68 | 4152.89 | 2561.95 | 2045.16 | 221.90 |
CORE_BOTTOM | 45343879.05 | 0.00 | 45343879.05 | 0.00 | 45343879.05 | 33990283.35 | 5465.87 | 13.10 | 3281.03 | 245.96 |
CORE_MID | 0.35E+09 | 0.00 | 0.35E+09 | 0.00 | 0.35E+09 | 0.34E+09 | 5791.39 | 23.22 | 2945.40 | 123.39 |
CORE_TOP | 33787775.11 | 0.00 | 33787775.11 | 0.00 | 33787775.11 | 33990283.35 | 5988.75 | 15.50 | 2755.75 | 170.12 |
PERIMETER_BOT_ZN_3 | 6319196.81 | 0.00 | 6319196.81 | 398322.03 | 6717518.84 | 4267819.30 | 3754.24 | 20.33 | 4985.42 | 245.96 |
PERIMETER_BOT_ZN_2 | 6365105.43 | 0.00 | 6365105.43 | 265547.84 | 6630653.27 | 2750345.05 | 3697.33 | 4.67 | 5058.01 | 245.96 |
PERIMETER_BOT_ZN_1 | 9455004.89 | 0.00 | 9455004.89 | 398322.03 | 9853326.92 | 4267912.63 | 3714.99 | 8.42 | 5036.59 | 245.96 |
PERIMETER_BOT_ZN_4 | 8041887.65 | 0.00 | 8041887.65 | 265547.84 | 8307435.49 | 2750345.05 | 3683.99 | 0.00 | 5076.01 | 245.96 |
PERIMETER_MID_ZN_3 | 54996305.01 | 0.00 | 54996305.01 | 934163.77 | 55930468.78 | 42678193.03 | 3956.64 | 22.87 | 4780.49 | 123.39 |
PERIMETER_MID_ZN_2 | 55672071.19 | 0.00 | 55672071.19 | 622775.42 | 56294846.61 | 27503450.52 | 4142.95 | 6.28 | 4610.77 | 850.05 |
PERIMETER_MID_ZN_1 | 84892659.80 | 0.00 | 84892659.80 | 934163.77 | 85826823.57 | 42679126.28 | 3887.12 | 6.08 | 4866.80 | 123.39 |
PERIMETER_MID_ZN_4 | 63167174.42 | 0.00 | 63167174.42 | 622775.42 | 63789949.84 | 27503450.52 | 3855.87 | 0.00 | 4904.13 | 123.39 |
PERIMETER_TOP_ZN_3 | 6539341.67 | 0.00 | 6539341.67 | 1159847.75 | 7699189.42 | 4267819.30 | 4105.67 | 26.06 | 4628.27 | 170.12 |
PERIMETER_TOP_ZN_2 | 5789457.39 | 0.00 | 5789457.39 | 773231.30 | 6562688.69 | 2750345.05 | 3957.47 | 4.28 | 4798.25 | 170.12 |
PERIMETER_TOP_ZN_1 | 8613331.69 | 0.00 | 8613331.69 | 1159847.75 | 9773179.44 | 4267912.63 | 4028.29 | 12.07 | 4719.63 | 170.12 |
PERIMETER_TOP_ZN_4 | 6528280.16 | 0.00 | 6528280.16 | 773231.30 | 7301511.46 | 2750345.05 | 3936.91 | 2.30 | 4820.79 | 170.12 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.38E+09 | 0.00 | 0.38E+09 | 0.00 | 0.38E+09 | 10671554.30 | 1359.52 | 1944.33 | 5456.15 | 2044.37 |
Total Facility | 0.67E+10 | 0.00 | 0.67E+10 | 36332681.67 | 0.67E+10 | 0.50E+10 | 6593.23 | 4368.33 | 7470.45 | 2805.75 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.1060 | 0.0000 | 2.1060 | 0.0000 | 2.1060 | 1.2002 | 1421.45 | 2560.58 | 1960.97 |
CORE_BOTTOM | 2.0185 | 0.0000 | 2.0185 | 0.0000 | 2.0185 | 1.0778 | 2884.35 | 11.15 | 3047.50 |
CORE_MID | 16.1311 | 0.0000 | 16.1311 | 0.0000 | 16.1311 | 10.7782 | 3058.79 | 22.53 | 2861.68 |
CORE_TOP | 1.5486 | 0.0000 | 1.5486 | 0.0000 | 1.5486 | 1.0778 | 3220.76 | 14.66 | 2707.58 |
PERIMETER_BOT_ZN_3 | 0.2780 | 0.0000 | 0.2780 | 0.0094 | 0.2874 | 0.1353 | 1183.20 | 20.33 | 4739.46 |
PERIMETER_BOT_ZN_2 | 0.2811 | 0.0000 | 0.2811 | 0.0063 | 0.2873 | 0.0872 | 1126.29 | 4.67 | 4812.05 |
PERIMETER_BOT_ZN_1 | 0.4224 | 0.0000 | 0.4224 | 0.0094 | 0.4318 | 0.1353 | 1143.95 | 8.42 | 4790.63 |
PERIMETER_BOT_ZN_4 | 0.3541 | 0.0000 | 0.3541 | 0.0063 | 0.3604 | 0.0872 | 1112.95 | 0.00 | 4830.05 |
PERIMETER_MID_ZN_3 | 2.4983 | 0.0000 | 2.4983 | 0.0220 | 2.5203 | 1.3533 | 1262.04 | 21.45 | 4659.51 |
PERIMETER_MID_ZN_2 | 2.6370 | 0.0000 | 2.6370 | 0.0156 | 2.6526 | 0.8721 | 1162.26 | 0.67 | 3871.08 |
PERIMETER_MID_ZN_1 | 3.8873 | 0.0000 | 3.8873 | 0.0220 | 3.9093 | 1.3533 | 1193.51 | 6.08 | 4743.41 |
PERIMETER_MID_ZN_4 | 2.8706 | 0.0000 | 2.8706 | 0.0147 | 2.8852 | 0.8721 | 1162.26 | 0.00 | 4780.74 |
PERIMETER_TOP_ZN_3 | 0.2993 | 0.0000 | 0.2993 | 0.0273 | 0.3266 | 0.1353 | 1368.19 | 25.26 | 4549.54 |
PERIMETER_TOP_ZN_2 | 0.2655 | 0.0000 | 0.2655 | 0.0182 | 0.2837 | 0.0872 | 1230.46 | 2.72 | 4709.83 |
PERIMETER_TOP_ZN_1 | 0.3962 | 0.0000 | 0.3962 | 0.0273 | 0.4235 | 0.1353 | 1289.94 | 11.39 | 4641.68 |
PERIMETER_TOP_ZN_4 | 0.2991 | 0.0000 | 0.2991 | 0.0182 | 0.3173 | 0.0872 | 1221.93 | 0.84 | 4720.24 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 11.4794 | 0.0000 | 11.4794 | 0.0000 | 11.4794 | 0.3384 | 565.84 | 1943.92 | 3433.25 |
Total Facility | 301.1550 | 0.0000 | 301.1550 | 0.8655 | 302.0205 | 158.4706 | 3776.23 | 4357.89 | 5424.24 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 82369813.05 | 0.00 | 82369813.05 | 48026705.38 | 3684.25 | 0.39 | 5075.36 | 245.96 |
VAV_MID WITH REHEAT | 0.67E+09 | 0.00 | 0.67E+09 | 0.48E+09 | 3875.44 | 3.19 | 4881.37 | 123.39 |
VAV_TOP WITH REHEAT | 66809934.67 | 0.00 | 66809934.67 | 48026705.38 | 4024.88 | 4.35 | 4730.77 | 170.12 |
CAV_BAS | 50395756.95 | 0.00 | 50395756.95 | 37848132.68 | 4141.28 | 2.01 | 4616.71 | 221.90 |
AIRLOOP DATACENTER BASEMENT | 0.41E+09 | 0.00 | 0.41E+09 | 10671554.30 | 1357.14 | 0.47 | 7402.38 | 2044.29 |
AIRLOOP DATACENTER BOT | 266436.27 | 0.00 | 266436.27 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 2664362.65 | 0.00 | 2664362.65 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 266436.27 | 0.00 | 266436.27 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.6580 | 0.0000 | 3.6580 | 1.5229 | 1113.19 | 0.39 | 4829.42 |
VAV_MID WITH REHEAT | 30.4458 | 0.0000 | 30.4458 | 15.2292 | 1173.37 | 2.27 | 4767.36 |
VAV_TOP WITH REHEAT | 3.0632 | 0.0000 | 3.0632 | 1.5229 | 1273.06 | 2.90 | 4667.03 |
CAV_BAS | 2.2955 | 0.0000 | 2.2955 | 1.2002 | 1415.47 | 0.58 | 4526.95 |
AIRLOOP DATACENTER BASEMENT | 12.5199 | 0.0000 | 12.5199 | 0.3384 | 565.09 | 0.15 | 5377.76 |
AIRLOOP DATACENTER BOT | 0.0125 | 0.0000 | 0.0125 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1245 | 0.0000 | 0.1245 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0125 | 0.0000 | 0.0125 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 42.01 | 3346.91 | 0.00 | 0.00 | 0.00 | 1687.08 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 136.73 | 3049.89 | 0.00 | 0.00 | 0.00 | 1717.52 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 28.42 | 3052.16 | 0.00 | 0.00 | 0.00 | 1837.18 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 2566.61 | 2233.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 1943.69 | 5487.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 1.9932 | 6.0211 | 0.0000 | 0.0000 | 0.0000 | 1.7655 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 21.6993 | 50.2207 | 0.0000 | 0.0000 | 0.0000 | 18.0503 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.1300 | 5.1721 | 0.0000 | 0.0000 | 0.0000 | 1.7645 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.3092 | 5.1131 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3692 | 21.4024 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0170 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1705 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0170 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1343 |
Defaulted Fields | 1287 |
Fields with Defaults | 3878 |
Autosized Fields | 320 |
Autosizable Fields | 465 |
Autocalculated Fields | 223 |
Autocalculatable Fields | 468 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 33192.55 | 299053.52 | 02-SEP-18:20 | 2353846.47 | 04-AUG-15:30 |
Electricity:Building | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 758.19 | 15076.70 | 01-JAN-00:10 | 42602.33 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 20287.13 | 234472.87 | 01-JAN-00:10 | 1268272.53 | 03-APR-07:10 |
InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 333.79 | 1619.15 | 01-JAN-00:10 | 29144.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 5610.74 | 27216.71 | 01-JAN-00:10 | 489900.85 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 589.38 | 5907.35 | 01-JAN-00:10 | 43380.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5893.79 | 59073.32 | 01-JAN-00:10 | 433806.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2997.66 | 14541.15 | 01-JAN-00:10 | 261740.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 589.38 | 5907.33 | 01-JAN-00:10 | 43380.63 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 299.77 | 1454.11 | 01-JAN-00:10 | 26174.07 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 740.04 | 7417.49 | 01-JAN-00:10 | 54469.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 376.39 | 1825.79 | 01-JAN-00:10 | 32864.16 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 476.91 | 4780.12 | 01-JAN-00:10 | 35102.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 740.05 | 7417.62 | 01-JAN-00:10 | 54470.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 376.39 | 1825.83 | 01-JAN-00:10 | 32864.88 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 476.91 | 4780.09 | 01-JAN-00:10 | 35102.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 242.56 | 1176.61 | 01-JAN-00:10 | 21178.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 74.00 | 741.75 | 01-JAN-00:10 | 5446.97 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 74.01 | 741.76 | 01-JAN-00:10 | 5447.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 37.64 | 182.58 | 01-JAN-00:10 | 3286.49 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 47.69 | 478.01 | 01-JAN-00:10 | 3510.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.26 | 117.66 | 01-JAN-00:10 | 2117.89 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7588.97 | 95364.66 | 01-JAN-00:10 | 387850.11 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 94.11 | 456.53 | 01-JAN-00:10 | 8217.58 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1622.27 | 19890.94 | 01-JAN-00:10 | 85232.07 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 83.47 | 404.88 | 01-JAN-00:10 | 7287.84 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 162.23 | 1989.09 | 01-JAN-00:10 | 8523.21 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 8.35 | 40.49 | 01-JAN-00:10 | 728.78 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:HVAC | 5017.14 | 33184.51 | 16-JAN-04:50 | 371802.38 | 16-MAR-15:30 |
ExteriorEquipment:Electricity | 2623.11 | 22123.82 | 01-JAN-00:10 | 235096.12 | 03-APR-07:20 |
Transformer:ExteriorEquipment:Electricity | 56.04 | 979.82 | 01-JAN-00:10 | 3543.78 | 03-APR-07:20 |
ElectricityPurchased:Facility | 33192.55 | 299053.52 | 02-SEP-18:20 | 2353846.47 | 04-AUG-15:30 |
ElectricityPurchased:Plant | 33192.55 | 299053.52 | 02-SEP-18:20 | 2353846.47 | 04-AUG-15:30 |
Cogeneration:ElectricityPurchased | 33192.55 | 299053.52 | 02-SEP-18:20 | 2353846.47 | 04-AUG-15:30 |
General:Cogeneration:ElectricityPurchased | 33192.55 | 299053.52 | 02-SEP-18:20 | 2353846.47 | 04-AUG-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 33192.55 | 299053.52 | 02-SEP-18:20 | 2353846.47 | 04-AUG-15:30 |
ElectricityNet:Plant | 33192.55 | 299053.52 | 02-SEP-18:20 | 2353846.47 | 04-AUG-15:30 |
Cogeneration:ElectricityNet | 33192.55 | 299053.52 | 02-SEP-18:20 | 2353846.47 | 04-AUG-15:30 |
General:Cogeneration:ElectricityNet | 33192.55 | 299053.52 | 02-SEP-18:20 | 2353846.47 | 04-AUG-15:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 3082.16 | 3427.70 | 30-JAN-07:10 | 536296.01 | 21-JUL-09:30 |
General:Cooling:Electricity | 3082.16 | 3427.70 | 30-JAN-07:10 | 536296.01 | 21-JUL-09:30 |
Fans:Electricity | 3141.30 | 27505.84 | 04-JAN-05:50 | 307621.51 | 04-AUG-15:30 |
General:Fans:Electricity | 3141.30 | 27505.84 | 04-JAN-05:50 | 307621.51 | 04-AUG-15:30 |
ExteriorLights:Electricity | 1007.65 | 0.00 | 01-JAN-07:20 | 64082.80 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 1007.65 | 0.00 | 01-JAN-07:20 | 64082.80 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.31 | 1944.00 | 01-JAN-00:10 | 1944.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1314.06 | 0.00 | 15-JAN-13:20 | 100000.00 | 03-JAN-14:20 |
General:Humidifier:Electricity | 1314.06 | 0.00 | 15-JAN-13:20 | 100000.00 | 03-JAN-14:20 |
Electricity:Plant | 4313.56 | 0.00 | 01-JAN-01:30 | 678140.43 | 21-JUL-09:30 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 374.13 | 0.00 | 01-JAN-00:10 | 47541.54 | 30-JAN-13:00 |
Water Heater:WaterSystems:Electricity | 374.13 | 0.00 | 01-JAN-00:10 | 47541.54 | 30-JAN-13:00 |
HeatRejection:Electricity | 253.02 | 0.00 | 01-JAN-00:10 | 50732.53 | 21-APR-15:10 |
General:HeatRejection:Electricity | 253.02 | 0.00 | 01-JAN-00:10 | 50732.53 | 21-APR-15:10 |
Pumps:Electricity | 1109.98 | 0.00 | 01-JAN-01:30 | 89290.88 | 21-JUL-09:50 |
General:Pumps:Electricity | 1109.98 | 0.00 | 01-JAN-01:30 | 89290.88 | 21-JUL-09:50 |
WIRED_LTG_ELECTRICITY | 157.66 | 0.00 | 01-JAN-00:10 | 13766.21 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 528.66 | 0.00 | 01-JAN-00:10 | 795969.79 | 26-DEC-05:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 528.66 | 0.00 | 01-JAN-00:10 | 795969.79 | 26-DEC-05:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 528.66 | 0.00 | 01-JAN-00:10 | 795969.79 | 26-DEC-05:10 |
Boiler:Heating:NaturalGas | 528.66 | 0.00 | 01-JAN-00:10 | 795969.79 | 26-DEC-05:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 15493.53 | 0.00 | 01-JAN-01:30 | 3304590.04 | 21-JUL-09:50 |
PlantLoopCoolingDemand:HVAC | 15493.53 | 0.00 | 01-JAN-01:30 | 3304590.04 | 21-JUL-09:50 |
CoolingCoils:PlantLoopCoolingDemand | 15493.53 | 0.00 | 01-JAN-01:30 | 3304590.04 | 21-JUL-09:50 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 17028.38 | 0.00 | 16-JAN-00:10 | 0.00 | 14-JUN-13:00 |
Water:HVAC | 488.83 | 0.00 | 15-JAN-13:20 | 0.00 | 05-FEB-16:50 |
Humidifier:Water | 488.83 | 0.00 | 15-JAN-13:20 | 0.00 | 05-FEB-16:50 |
General:Humidifier:Water | 488.83 | 0.00 | 15-JAN-13:20 | 0.00 | 05-FEB-16:50 |
MainsWater:Facility | 17028.38 | 0.00 | 16-JAN-00:10 | 0.00 | 14-JUN-13:00 |
MainsWater:HVAC | 488.83 | 0.00 | 15-JAN-13:20 | 0.00 | 05-FEB-16:50 |
Humidifier:MainsWater | 488.83 | 0.00 | 15-JAN-13:20 | 0.00 | 05-FEB-16:50 |
General:Humidifier:MainsWater | 488.83 | 0.00 | 15-JAN-13:20 | 0.00 | 05-FEB-16:50 |
Water:Plant | 16539.55 | 0.00 | 01-JAN-00:10 | 0.00 | 14-JUN-13:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 24-OCT-11:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 24-OCT-11:10 |
MainsWater:Plant | 16539.55 | 0.00 | 01-JAN-00:10 | 0.00 | 14-JUN-13:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 24-OCT-11:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 24-OCT-11:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 14259.38 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JUN-13:30 |
General:HeatRejection:Water | 14259.38 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JUN-13:30 |
HeatRejection:MainsWater | 14259.38 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JUN-13:30 |
General:HeatRejection:MainsWater | 14259.38 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JUN-13:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 91062.04 | 107327.58 | 15-JAN-06:00 | 15235501.37 | 21-JUL-09:50 |
EnergyTransfer:Building | 22513.41 | 90279.47 | 15-JAN-06:00 | 1859619.49 | 04-AUG-15:40 |
EnergyTransfer:Zone:BASEMENT | 780.09 | 0.00 | 01-JAN-00:10 | 82583.33 | 10-OCT-07:30 |
Heating:EnergyTransfer | 141.91 | 0.00 | 01-JAN-15:00 | 389783.64 | 26-DEC-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 1.27 | 0.00 | 01-JAN-00:10 | 18030.86 | 01-JUL-16:10 |
General:Heating:EnergyTransfer | 141.91 | 0.00 | 01-JAN-15:00 | 389783.64 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 1.27 | 0.00 | 01-JAN-00:10 | 18030.86 | 01-JUL-16:10 |
Cooling:EnergyTransfer | 22371.49 | 88923.55 | 16-JAN-08:20 | 1859619.49 | 04-AUG-15:40 |
Cooling:EnergyTransfer:Zone:BASEMENT | 778.82 | 0.00 | 01-JAN-00:10 | 82583.33 | 10-OCT-07:30 |
General:Cooling:EnergyTransfer | 22371.49 | 88923.55 | 16-JAN-08:20 | 1859619.49 | 04-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 778.82 | 0.00 | 01-JAN-00:10 | 82583.33 | 10-OCT-07:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 725.85 | 0.00 | 01-JAN-00:10 | 58028.21 | 07-AUG-16:00 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 725.85 | 0.00 | 01-JAN-00:10 | 58028.21 | 07-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 725.85 | 0.00 | 01-JAN-00:10 | 58028.21 | 07-AUG-16:00 |
EnergyTransfer:Zone:CORE_MID | 5679.69 | 0.00 | 01-JAN-00:10 | 499784.38 | 12-JUL-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5679.69 | 0.00 | 01-JAN-00:10 | 499784.38 | 12-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5679.69 | 0.00 | 01-JAN-00:10 | 499784.38 | 12-JUL-16:00 |
EnergyTransfer:Zone:CORE_TOP | 573.16 | 0.00 | 01-JAN-00:10 | 66271.40 | 19-JUN-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 3.78 | 0.00 | 01-JAN-00:10 | 55087.38 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 3.78 | 0.00 | 01-JAN-00:10 | 55087.38 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 569.37 | 0.00 | 01-JAN-00:10 | 66271.40 | 19-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 569.37 | 0.00 | 01-JAN-00:10 | 66271.40 | 19-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 106.12 | 0.00 | 01-JAN-00:10 | 13470.19 | 03-JUL-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.09 | 0.00 | 01-JAN-00:10 | 3465.46 | 28-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.09 | 0.00 | 01-JAN-00:10 | 3465.46 | 28-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 106.03 | 0.00 | 01-JAN-00:10 | 13470.19 | 03-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 106.03 | 0.00 | 01-JAN-00:10 | 13470.19 | 03-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 98.00 | 0.00 | 01-JAN-00:10 | 14099.67 | 30-MAY-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.11 | 0.00 | 01-JAN-00:10 | 2760.68 | 28-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.11 | 0.00 | 01-JAN-00:10 | 2760.68 | 28-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 97.89 | 0.00 | 01-JAN-00:10 | 14099.67 | 30-MAY-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 97.89 | 0.00 | 01-JAN-00:10 | 14099.67 | 30-MAY-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 149.64 | 0.00 | 01-JAN-00:10 | 21519.95 | 03-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.25 | 0.00 | 01-JAN-00:10 | 4756.31 | 27-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.25 | 0.00 | 01-JAN-00:10 | 4756.31 | 27-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 149.39 | 0.00 | 01-JAN-00:10 | 21519.95 | 03-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 149.39 | 0.00 | 01-JAN-00:10 | 21519.95 | 03-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 134.56 | 0.00 | 01-JAN-00:10 | 18896.71 | 04-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 161.49 | 27-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 161.49 | 27-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 134.56 | 0.00 | 01-JAN-00:10 | 18896.71 | 04-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 134.56 | 0.00 | 01-JAN-00:10 | 18896.71 | 04-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 855.23 | 0.00 | 01-JAN-00:10 | 125767.67 | 03-JUL-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.27 | 0.00 | 01-JAN-00:10 | 92993.90 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.27 | 0.00 | 01-JAN-00:10 | 92993.90 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 828.96 | 0.00 | 01-JAN-00:10 | 125767.67 | 03-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 828.96 | 0.00 | 01-JAN-00:10 | 125767.67 | 03-JUL-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 849.82 | 0.00 | 01-JAN-00:10 | 145052.63 | 07-JUN-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 13.65 | 0.00 | 01-JAN-00:10 | 63549.88 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 13.65 | 0.00 | 01-JAN-00:10 | 63549.88 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 836.17 | 0.00 | 01-JAN-00:10 | 145052.63 | 07-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 836.17 | 0.00 | 01-JAN-00:10 | 145052.63 | 07-JUN-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1337.48 | 0.00 | 01-JAN-00:10 | 209119.26 | 03-NOV-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 13.06 | 0.00 | 01-JAN-00:10 | 69703.07 | 28-NOV-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 13.06 | 0.00 | 01-JAN-00:10 | 69703.07 | 28-NOV-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1324.43 | 0.00 | 01-JAN-00:10 | 209119.26 | 03-NOV-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1324.43 | 0.00 | 01-JAN-00:10 | 209119.26 | 03-NOV-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 943.65 | 0.00 | 01-JAN-00:10 | 170757.26 | 15-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 10.80 | 0.00 | 01-JAN-00:10 | 50636.56 | 28-JAN-05:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 10.80 | 0.00 | 01-JAN-00:10 | 50636.56 | 28-JAN-05:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 932.85 | 0.00 | 01-JAN-00:10 | 170757.26 | 15-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 932.85 | 0.00 | 01-JAN-00:10 | 170757.26 | 15-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 100.64 | 0.00 | 01-JAN-00:10 | 18099.24 | 18-DEC-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 11.52 | 0.00 | 01-JAN-00:10 | 18099.24 | 18-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 11.52 | 0.00 | 01-JAN-00:10 | 18099.24 | 18-DEC-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 89.13 | 0.00 | 01-JAN-00:10 | 14660.61 | 03-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 89.13 | 0.00 | 01-JAN-00:10 | 14660.61 | 03-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 92.75 | 0.00 | 01-JAN-00:10 | 15076.66 | 07-JUN-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 5.81 | 0.00 | 01-JAN-00:10 | 11873.68 | 18-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 5.81 | 0.00 | 01-JAN-00:10 | 11873.68 | 18-DEC-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 86.94 | 0.00 | 01-JAN-00:10 | 15076.66 | 07-JUN-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 86.94 | 0.00 | 01-JAN-00:10 | 15076.66 | 07-JUN-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 140.19 | 0.00 | 01-JAN-00:10 | 23093.77 | 03-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 7.16 | 0.00 | 01-JAN-00:10 | 16372.88 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 7.16 | 0.00 | 01-JAN-00:10 | 16372.88 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 133.03 | 0.00 | 01-JAN-00:10 | 23093.77 | 03-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 133.03 | 0.00 | 01-JAN-00:10 | 23093.77 | 03-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 99.80 | 0.00 | 01-JAN-00:10 | 18439.99 | 15-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.74 | 0.00 | 01-JAN-00:10 | 9866.39 | 18-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.74 | 0.00 | 01-JAN-00:10 | 9866.39 | 18-DEC-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 95.06 | 0.00 | 01-JAN-00:10 | 18439.99 | 15-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 95.06 | 0.00 | 01-JAN-00:10 | 18439.99 | 15-JUN-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 104.53 | 0.00 | 01-JAN-00:10 | 11090.36 | 07-AUG-15:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.77 | 0.00 | 01-JAN-00:10 | 2466.92 | 29-JAN-10:50 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.77 | 0.00 | 01-JAN-00:10 | 2466.92 | 29-JAN-10:50 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 103.76 | 0.00 | 01-JAN-00:10 | 11090.36 | 07-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 103.76 | 0.00 | 01-JAN-00:10 | 11090.36 | 07-AUG-15:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 762.71 | 0.00 | 01-JAN-00:10 | 96916.08 | 07-JUN-15:50 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 8.06 | 0.00 | 01-JAN-00:10 | 28138.60 | 02-JAN-15:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 8.06 | 0.00 | 01-JAN-00:10 | 28138.60 | 02-JAN-15:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 754.65 | 0.00 | 01-JAN-00:10 | 96916.08 | 07-JUN-15:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 754.65 | 0.00 | 01-JAN-00:10 | 96916.08 | 07-JUN-15:50 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 222.27 | 0.00 | 01-JAN-00:10 | 40813.71 | 26-JUL-14:00 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 30.37 | 0.00 | 01-JAN-00:10 | 27796.60 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 30.37 | 0.00 | 01-JAN-00:10 | 27796.60 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 191.90 | 0.00 | 01-JAN-00:10 | 40813.71 | 26-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 191.90 | 0.00 | 01-JAN-00:10 | 40813.71 | 26-JUL-14:00 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.21 | 726.29 | 14-JAN-18:20 | 8204.68 | 06-AUG-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.21 | 726.29 | 14-JAN-18:20 | 8204.68 | 06-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.21 | 726.29 | 14-JAN-18:20 | 8204.68 | 06-AUG-18:20 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1274.81 | 24.60 | 02-JAN-06:30 | 77262.75 | 06-AUG-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1274.81 | 24.60 | 02-JAN-06:30 | 77262.75 | 06-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1274.81 | 24.60 | 02-JAN-06:30 | 77262.75 | 06-AUG-18:10 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 120.06 | 5.40 | 08-JAN-15:40 | 8245.70 | 06-AUG-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.95 | 0.00 | 01-JAN-15:00 | 1436.43 | 09-JAN-04:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.95 | 0.00 | 01-JAN-15:00 | 1436.43 | 09-JAN-04:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 119.11 | 0.00 | 01-JAN-00:10 | 8245.70 | 06-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 119.11 | 0.00 | 01-JAN-00:10 | 8245.70 | 06-AUG-18:10 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7222.14 | 86449.93 | 29-JAN-18:00 | 403893.15 | 06-APR-11:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 3.24 | 0.00 | 01-JAN-00:10 | 4646.00 | 12-FEB-10:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 3.24 | 0.00 | 01-JAN-00:10 | 4646.00 | 12-FEB-10:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7218.90 | 86449.93 | 29-JAN-18:00 | 403893.15 | 06-APR-11:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7218.90 | 86449.93 | 29-JAN-18:00 | 403893.15 | 06-APR-11:20 |
PlantLoopHeatingDemand:Facility | 714.79 | 0.00 | 01-JAN-00:10 | 551007.68 | 27-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 368.85 | 0.00 | 01-JAN-00:10 | 47265.69 | 30-JAN-12:20 |
WaterSystems:PlantLoopHeatingDemand | 368.85 | 0.00 | 01-JAN-00:10 | 47265.69 | 30-JAN-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 368.85 | 0.00 | 01-JAN-00:10 | 47265.69 | 30-JAN-12:20 |
EnergyTransfer:HVAC | 17871.47 | 15990.74 | 14-JAN-18:00 | 3390996.25 | 21-JUL-09:50 |
HeatingCoils:EnergyTransfer | 345.94 | 0.00 | 01-JAN-00:10 | 535618.32 | 27-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 345.94 | 0.00 | 01-JAN-00:10 | 535618.32 | 27-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 345.94 | 0.00 | 01-JAN-00:10 | 535618.32 | 27-DEC-07:10 |
CoolingCoils:EnergyTransfer | 17525.54 | 12190.23 | 30-JAN-07:10 | 3390996.25 | 21-JUL-09:50 |
EnergyTransfer:Plant | 50677.17 | 0.00 | 01-JAN-01:30 | 10448317.73 | 21-JUL-09:50 |
LoopToLoop:EnergyTransfer | 15805.34 | 0.00 | 01-JAN-01:30 | 3312364.69 | 21-JUL-09:50 |
WaterSystems:EnergyTransfer | 368.85 | 0.00 | 01-JAN-00:10 | 47265.69 | 30-JAN-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 368.85 | 0.00 | 01-JAN-00:10 | 47265.69 | 30-JAN-12:20 |
Boilers:EnergyTransfer | 344.28 | 0.00 | 01-JAN-00:10 | 602727.59 | 26-DEC-05:10 |
Chillers:EnergyTransfer | 15791.14 | 0.00 | 01-JAN-00:10 | 3305545.02 | 21-JUL-09:40 |
HeatRejection:EnergyTransfer | 18367.56 | 0.00 | 01-JAN-00:10 | 3817045.72 | 21-JUL-09:40 |
General:HeatRejection:EnergyTransfer | 18367.56 | 0.00 | 01-JAN-00:10 | 3817045.72 | 21-JUL-09:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 1.272 | -778.813 | 0.000 | 0.000 | 93.358 | 333.789 | 424.397 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -74.003 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -725.848 | 0.000 | 0.000 | 83.486 | 299.766 | 289.614 | 0.000 | 0.000 | 0.000 | 52.982 | 0.000 | 0.000 | 0.000 | 0.000 | -0.004 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5679.667 | 0.000 | 0.000 | 838.619 | 2997.664 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1052.744 |
CORE_TOP | 0.000 | 0.000 | 3.785 | -569.367 | 0.000 | 0.000 | 86.412 | 299.766 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -110.209 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.093 | -106.029 | 0.000 | 0.000 | 10.816 | 37.639 | 36.365 | 32.548 | 0.000 | 0.446 | 52.711 | 0.000 | -61.668 | 0.000 | -2.922 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.113 | -97.887 | 0.000 | 0.000 | 6.947 | 24.256 | 23.435 | 66.709 | 0.000 | 0.324 | 14.294 | 0.000 | -36.274 | 0.000 | -1.917 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.249 | -149.394 | 0.000 | 0.000 | 10.659 | 37.639 | 36.366 | 113.646 | 0.000 | 0.442 | 8.299 | 0.000 | -54.913 | 0.000 | -2.995 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.001 | -134.557 | 0.000 | 0.000 | 6.966 | 24.256 | 23.435 | 66.452 | 0.000 | 0.270 | 58.975 | 0.000 | -43.629 | 0.000 | -2.168 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 26.268 | -828.950 | 0.000 | 0.000 | 111.413 | 376.387 | 363.654 | 339.349 | 0.000 | 10.038 | 224.137 | 0.000 | -561.514 | 0.000 | -60.781 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 13.649 | -836.168 | 0.000 | 0.000 | 51.765 | 242.558 | 234.352 | 662.858 | 0.000 | 6.674 | 11.878 | 0.000 | -345.469 | 0.000 | -42.098 | -0.001 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 13.055 | -1324.417 | 0.000 | 0.000 | 107.366 | 376.395 | 363.660 | 1131.105 | 0.000 | 9.646 | 0.009 | 0.000 | -536.254 | 0.000 | -67.772 | -72.783 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 10.803 | -932.835 | 0.000 | 0.000 | 72.179 | 242.558 | 234.351 | 680.561 | 0.000 | 6.175 | 112.965 | 0.000 | -383.142 | 0.000 | -43.614 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 11.517 | -89.125 | 0.000 | 0.000 | 11.387 | 37.639 | 36.365 | 34.212 | 0.000 | 1.236 | 14.424 | 0.000 | -50.921 | 0.000 | -6.733 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 5.811 | -86.941 | 0.000 | 0.000 | 7.161 | 24.256 | 23.435 | 66.753 | 0.000 | 0.789 | 0.000 | 0.000 | -31.624 | 0.000 | -4.720 | -4.921 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 7.161 | -133.029 | 0.000 | 0.000 | 10.923 | 37.639 | 36.366 | 113.496 | 0.000 | 1.159 | 0.005 | 0.000 | -49.153 | 0.000 | -7.636 | -16.926 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 4.740 | -95.056 | 0.000 | 0.000 | 7.307 | 24.256 | 23.435 | 67.821 | 0.000 | 0.754 | 7.304 | 0.000 | -35.559 | 0.000 | -5.002 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -140.207 | 0.000 | 0.000 | 0.950 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -22.970 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1274.809 | 0.000 | 0.000 | 9.502 | 83.466 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -356.965 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.954 | -119.106 | 0.000 | 0.000 | 0.950 | 8.347 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -45.025 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 3.238 | -7218.448 | 0.000 | 0.000 | 22.111 | 94.114 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -395.873 |
GROUNDFLOOR_PLENUM | 0.769 | -103.763 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.780 | 108.861 | 0.000 | 0.000 | 0.000 | -6.647 | 0.000 |
MIDFLOOR_PLENUM | 8.062 | -754.647 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.225 | 846.097 | 0.000 | 0.000 | 0.000 | -113.737 | 0.000 |
TOPFLOOR_PLENUM | 30.372 | -191.896 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.219 | 170.952 | 0.000 | 0.000 | 0.000 | -10.648 | -0.000 |
Total Facility | 39.203 | -1050.306 | 102.710 | -21320.653 | 0.000 | 0.000 | 1550.275 | 5610.736 | 14676.396 | 3375.510 | 0.000 | 54.177 | 1683.895 | 0.000 | -2190.119 | 0.000 | -379.390 | -2152.424 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-NOV-05:11 | 0.00 | 0.00 | 0.00 | -154699.55 | 0.00 | 0.00 | 0.00 | 3238.31 | 13457.54 | 0.00 | 0.00 | 0.00 | 138003.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 05-SEP-04:12 | 0.00 | 0.00 | 0.00 | -120007.46 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.65 | 0.00 | 0.00 | 0.00 | 111161.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 01-JUN-04:11 | 0.00 | 0.00 | 0.00 | -1068548.65 | 0.00 | 0.00 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 980090.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 05-JUN-04:11 | 0.00 | 0.00 | 0.00 | -121181.98 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.62 | 0.00 | 0.00 | 0.00 | 112336.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-JUN-16:51 | 0.00 | 0.00 | 0.00 | -23260.72 | 0.00 | 0.00 | 43.08 | 182.58 | 720.18 | 5841.83 | 0.00 | 0.00 | 16473.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUN-08:51 | 0.00 | 0.00 | 0.00 | -24578.33 | 0.00 | 0.00 | 21.34 | 117.66 | 464.11 | 13143.17 | 0.00 | 0.00 | 10853.48 | 0.00 | -0.00 | 0.00 | -21.43 | 0.00 |
PERIMETER_BOT_ZN_1 | 11-NOV-11:21 | 0.00 | 0.00 | 0.00 | -29210.12 | 0.00 | 0.00 | 35.74 | 182.58 | 720.19 | 21836.81 | 0.00 | 0.00 | 6645.92 | 0.00 | -0.00 | 0.00 | -211.13 | 0.00 |
PERIMETER_BOT_ZN_4 | 25-JUN-16:51 | 0.00 | 0.00 | 0.00 | -35013.34 | 0.00 | 0.00 | 15.96 | 117.66 | 464.11 | 15629.36 | 0.00 | 37.57 | 18748.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-JUN-16:51 | 0.00 | 0.00 | 0.00 | -196435.27 | 0.00 | 0.00 | 445.32 | 1825.79 | 7201.84 | 59097.52 | 0.00 | 0.00 | 127864.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUN-08:51 | 0.00 | 0.00 | 0.00 | -255731.56 | 0.00 | 0.00 | 207.33 | 1176.61 | 4641.14 | 129395.32 | 0.00 | 0.00 | 120878.74 | 0.00 | -0.00 | 0.00 | -567.57 | 0.00 |
PERIMETER_MID_ZN_1 | 29-OCT-13:21 | 0.00 | 0.00 | 0.00 | -296003.85 | 0.00 | 0.00 | 303.99 | 1825.83 | 7201.95 | 204299.61 | 0.00 | 0.00 | 87264.55 | 0.00 | -0.00 | 0.00 | -4892.07 | 0.00 |
PERIMETER_MID_ZN_4 | 25-JUN-17:01 | 0.00 | 0.00 | 0.00 | -307325.71 | 0.00 | 0.00 | 0.00 | 1176.61 | 3603.49 | 152551.58 | 0.00 | 750.23 | 149243.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 18-JUN-14:21 | 0.00 | 0.00 | 0.00 | -30358.03 | 0.00 | 0.00 | 39.52 | 182.58 | 720.18 | 5249.90 | 0.00 | 397.66 | 23768.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 18-JUN-08:21 | 0.00 | 0.00 | 0.00 | -26344.66 | 0.00 | 0.00 | 21.23 | 117.66 | 464.11 | 14039.84 | 0.00 | 0.00 | 11753.95 | 0.00 | -0.00 | 0.00 | -52.14 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-OCT-14:31 | 0.00 | 0.00 | 0.00 | -35187.79 | 0.00 | 0.00 | 29.58 | 182.58 | 720.19 | 15031.45 | 0.00 | 266.72 | 18957.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 29-MAY-16:41 | 0.00 | 0.00 | 0.00 | -34740.31 | 0.00 | 0.00 | 15.06 | 117.66 | 464.11 | 15698.67 | 0.00 | 224.46 | 18220.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 06-AUG-18:11 | 0.00 | 0.00 | 0.00 | -8204.68 | 0.00 | 0.00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 369.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 06-AUG-18:07 | 0.00 | 0.00 | 0.00 | -77262.75 | 0.00 | 0.00 | 0.00 | 404.88 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1086.35 |
DATACENTER_TOP_ZN_6 | 06-AUG-18:06 | 0.00 | 0.00 | 0.00 | -8245.70 | 0.00 | 0.00 | 0.00 | 40.49 | 7794.42 | 0.00 | 0.00 | 0.00 | 410.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 11-MAR-14:12 | 0.00 | 0.00 | 0.00 | -547020.41 | 0.00 | 0.00 | 316.61 | 1369.60 | 284724.39 | 0.00 | 0.00 | 0.00 | 260609.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 07-AUG-15:10 | 0.00 | -11090.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.40 | 11005.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 09-FEB-05:01 | 0.00 | -117374.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143528.76 | 0.00 | -0.00 | 0.00 | -26154.05 | 0.00 |
TOPFLOOR_PLENUM | 18-JUN-13:41 | 0.00 | -42571.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.15 | 42145.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-AUG-03:01 | 0.00 | 90048.91 | 0.00 | -2339059.12 | 0.00 | 0.00 | 0.00 | 27216.71 | 587299.42 | 0.00 | 0.00 | 1173.70 | 1648921.91 | 0.00 | -15601.54 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 01-JUL-16:02 | 0.00 | 0.00 | 19256.17 | 0.00 | 0.00 | 0.00 | 520.14 | 1619.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -34853.01 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 04-DEC-05:21 | 0.00 | 0.00 | 88322.53 | 0.00 | 0.00 | 0.00 | 0.00 | 2908.23 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -97168.38 |
PERIMETER_BOT_ZN_3 | 28-JAN-06:01 | 0.00 | 0.00 | 10020.69 | 0.00 | 0.00 | 0.00 | 146.13 | 365.16 | 960.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7521.36 | 0.00 | -180.31 | -3790.55 |
PERIMETER_BOT_ZN_2 | 26-DEC-06:01 | 0.00 | 0.00 | 7693.64 | 0.00 | 0.00 | 0.00 | 94.15 | 235.32 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4357.94 | 0.00 | -107.71 | -4176.27 |
PERIMETER_BOT_ZN_1 | 26-DEC-06:01 | 0.00 | 0.00 | 12207.38 | 0.00 | 0.00 | 0.00 | 146.10 | 365.17 | 960.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6132.14 | 0.00 | -161.03 | -7385.73 |
PERIMETER_BOT_ZN_4 | 27-JAN-06:03 | 0.00 | 0.00 | 1614.89 | 0.00 | 0.00 | 0.00 | 87.65 | 235.32 | 618.81 | 0.00 | 0.00 | 0.00 | 2649.67 | 0.00 | -5119.41 | 0.00 | -86.95 | 0.00 |
PERIMETER_MID_ZN_3 | 02-FEB-05:41 | 0.00 | 0.00 | 168692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 3651.57 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -70802.10 | 0.00 | -11016.26 | -97981.06 |
PERIMETER_MID_ZN_2 | 02-MAR-05:41 | 0.00 | 0.00 | 137966.06 | 0.00 | 0.00 | 0.00 | 0.00 | 2353.21 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -47856.28 | 0.00 | -5004.75 | -92262.92 |
PERIMETER_MID_ZN_1 | 02-MAR-05:41 | 0.00 | 0.00 | 175932.48 | 0.00 | 0.00 | 0.00 | 0.00 | 3651.65 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -71085.58 | 0.00 | -7588.28 | -108365.99 |
PERIMETER_MID_ZN_4 | 02-MAR-05:41 | 0.00 | 0.00 | 135869.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2353.21 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -47356.91 | 0.00 | -5084.24 | -90586.29 |
PERIMETER_TOP_ZN_3 | 02-MAR-05:21 | 0.00 | 0.00 | 24174.13 | 0.00 | 0.00 | 0.00 | 0.00 | 365.16 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6624.20 | 0.00 | -785.50 | -17875.15 |
PERIMETER_TOP_ZN_2 | 02-MAR-06:01 | 0.00 | 0.00 | 17732.72 | 0.00 | 0.00 | 0.00 | 105.49 | 235.32 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4375.46 | 0.00 | -157.91 | -14158.97 |
PERIMETER_TOP_ZN_1 | 02-MAR-05:21 | 0.00 | 0.00 | 23848.39 | 0.00 | 0.00 | 0.00 | 0.00 | 365.17 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6562.53 | 0.00 | -798.85 | -17597.75 |
PERIMETER_TOP_ZN_4 | 02-MAR-06:01 | 0.00 | 0.00 | 18452.10 | 0.00 | 0.00 | 0.00 | 103.95 | 235.32 | 618.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4349.70 | 0.00 | -161.57 | -14898.92 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 09-JAN-03:35 | 0.00 | 0.00 | 1436.62 | 0.00 | 0.00 | 0.00 | 0.00 | 40.49 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3425.71 |
DATACENTER_BASEMENT_ZN_6 | 29-OCT-04:41 | 0.00 | 0.00 | 29176.41 | 0.00 | 0.00 | 0.00 | 0.00 | 456.53 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -219449.20 |
GROUNDFLOOR_PLENUM | 18-DEC-05:11 | 11882.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2583.25 | -9299.33 |
MIDFLOOR_PLENUM | 01-OCT-15:11 | 84164.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7667.65 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -91831.89 |
TOPFLOOR_PLENUM | 04-DEC-06:04 | 34581.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -226.58 | -34354.45 |
Total Facility | 03-FEB-06:01 | -473871.36 | 436250.74 | 785521.77 | -436250.74 | 0.00 | 0.00 | 19291.47 | 54433.43 | 379706.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -284055.23 | 0.00 | -1401.49 | -479624.95 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 15.3985 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 13.7451 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 145.8588 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 127.2887 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 17.1408 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 16.4492 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 8.3469 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 8.3469 | 0.1438 | 1.0000 | Not calculated | 1.2002 | 0.1438 | ||
AIRLOOP DATACENTER BASEMENT | 36.3836 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 36.3841 | 0.0093 | 1.0000 | Not calculated | 0.3384 | 0.0093 | ||
AIRLOOP DATACENTER BOT | 0.8190 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.8190 | 0.0191 | 1.0000 | Not calculated | 0.0156 | 0.0191 | ||
AIRLOOP DATACENTER MID | 7.8049 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 7.8049 | 0.0200 | 1.0000 | Not calculated | 0.1563 | 0.0200 | ||
AIRLOOP DATACENTER TOP | 0.8169 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.8169 | 0.0191 | 1.0000 | Not calculated | 0.0156 | 0.0191 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 7.6992 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6195 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 72.9294 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 43.7576 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 8.5704 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.1422 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 2.5041 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 2.5041 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.4793 | ||
AIRLOOP DATACENTER BASEMENT | 18.1918 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 18.1918 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0186 | ||
AIRLOOP DATACENTER BOT | 0.8190 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.8190 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0191 | ||
AIRLOOP DATACENTER MID | 7.8049 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 7.8049 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0200 | ||
AIRLOOP DATACENTER TOP | 0.8169 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.8169 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0191 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 8.3469 | 8.3469 | 2.5041 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.5503 | 8.5503 | 2.5651 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 80.8444 | 80.8444 | 24.2533 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.4551 | 9.4551 | 2.8365 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5839 | 1.5839 | 0.4752 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5100 | 1.5100 | 0.4530 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7925 | 1.7925 | 0.5378 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9617 | 1.9617 | 0.5885 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 15.1960 | 15.1960 | 4.5588 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 15.5611 | 15.5611 | 4.6683 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 17.0395 | 17.0395 | 5.1119 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 17.2177 | 17.2177 | 5.1653 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0475 | 2.0475 | 0.6143 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6329 | 1.6329 | 0.4899 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0542 | 2.0542 | 0.6163 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9511 | 1.9511 | 0.5853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8190 | 0.8190 | 0.8190 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.8049 | 7.8049 | 7.8049 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8169 | 0.8169 | 0.8169 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 36.3836 | 36.3836 | 18.1918 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 15.3985 | 13.7451 | 15.3985 | 4.6195 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 145.8588 | 127.2887 | 145.8588 | 43.7576 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 17.1408 | 16.4492 | 17.1408 | 5.1422 | 0.0000 | 1.0000 |
CAV_BAS | 8.3469 | 8.3469 | 8.3469 | 2.5041 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 36.3836 | 36.3841 | 36.3836 | 18.1918 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.8190 | 0.8190 | 0.8190 | 0.8190 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 7.8049 | 7.8049 | 7.8049 | 7.8049 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.8169 | 0.8169 | 0.8169 | 0.8169 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 2.5041 | 2.5041 | 2.5041 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.2752 | 4.2752 | 2.5651 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 40.4222 | 40.4222 | 24.2533 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7276 | 4.7276 | 2.8365 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7919 | 0.7919 | 0.4752 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7550 | 0.7550 | 0.4530 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8963 | 0.8963 | 0.5378 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9809 | 0.9809 | 0.5885 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.5980 | 7.5980 | 4.5588 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.7806 | 7.7806 | 4.6683 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.5198 | 8.5198 | 5.1119 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.6089 | 8.6089 | 5.1653 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0238 | 1.0238 | 0.6143 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8164 | 0.8164 | 0.4899 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0271 | 1.0271 | 0.6163 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9755 | 0.9755 | 0.5853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8190 | 0.8190 | 0.8190 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.8049 | 7.8049 | 7.8049 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8169 | 0.8169 | 0.8169 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 18.1918 | 18.1918 | 18.1918 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 7.6992 | 4.6195 | 4.6195 | 4.6195 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 72.9294 | 43.7576 | 43.7576 | 43.7576 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 8.5704 | 5.1422 | 5.1422 | 5.1422 | 0.0000 | 1.0000 |
CAV_BAS | 2.5041 | 2.5041 | 2.5041 | 2.5041 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 18.1918 | 18.1918 | 18.1918 | 18.1918 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.8190 | 0.8190 | 0.8190 | 0.8190 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 7.8049 | 7.8049 | 7.8049 | 7.8049 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.8169 | 0.8169 | 0.8169 | 0.8169 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 2.00 |
Number of hours cooling loads not met | 238.50 |
Number of hours not met | 240.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 528.66 | 795969.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3082.16 | 536296.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 5610.74 | 489900.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 1007.65 | 64082.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 56.04 | 3543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.31 | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 3141.30 | 307621.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 1109.98 | 89290.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 253.02 | 50732.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1314.06 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 374.13 | 47541.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 33192.55 |
Natural Gas | 0.00 | 528.66 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 33721.20 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 121.13 |
Space Heating | 0.00 |
Space Cooling | 66.54 |
Fans (All) | 67.82 |
Service Water Heating | 8.08 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 716.59 |
Subtotal | 716.59 |
Natural Gas [MJ/m2] | |
Space Heating | 11.41 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 11.41 |
Subtotal | 11.41 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 16.64 |
Space Heating | 1.57 |
Space Cooling | 9.14 |
Fans (All) | 9.32 |
Service Water Heating | 1.11 |
Receptacle Equipment | 43.52 |
Miscellaneous | 18.71 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
LTG_SCH_DATACENTER | 2939. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8483.83 | 276.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8727.33 | 32.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8710.00 | 50.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8713.33 | 46.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8444.50 | 315.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8703.00 | 57.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8722.33 | 37.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8626.00 | 134.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8748.17 | 11.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8691.17 | 68.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8712.67 | 47.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8630.83 | 129.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8330.17 | 429.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8297.17 | 462.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8302.83 | 457.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6239.67 | 2520.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8290.67 | 469.33 | 0.00 | 0.00 | 0.00 |
Min | 6239.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2520.33 | 0.00 | 0.00 | 0.00 |
Average | 8518.51 | 241.49 | 0.00 | 0.00 | 0.00 |
Sum | 195925.83 | 5554.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367681.50 | 934.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330805.00 | 8.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1971.83 | 296.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1952.50 | 315.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1955.17 | 312.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 71873.67 | 31521.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367681.50 | 31521.33 | 0.00 | 0.00 | 0.00 |
Average | 78883.25 | 1451.67 | 0.00 | 0.00 | 0.00 |
Sum | 1814314.67 | 33388.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8376.17 | 383.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8348.50 | 411.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8381.00 | 379.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8413.50 | 346.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8508.50 | 251.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8561.67 | 198.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8472.17 | 287.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8187.50 | 572.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8475.83 | 284.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8420.00 | 340.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8398.17 | 361.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8311.33 | 448.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8495.50 | 264.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8403.00 | 357.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8428.17 | 331.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8338.50 | 421.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8724.83 | 35.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8710.00 | 50.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8714.50 | 45.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6436.50 | 2323.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8353.50 | 406.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8463.50 | 296.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7718.50 | 1041.50 | 0.00 | 0.00 | 0.00 |
Min | 6436.50 | 35.17 | 0.00 | 0.00 | 0.00 |
Max | 8724.83 | 2323.50 | 0.00 | 0.00 | 0.00 |
Average | 8332.21 | 427.79 | 0.00 | 0.00 | 0.00 |
Sum | 191640.83 | 9839.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 367648.83 | 967.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330288.00 | 525.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330370.00 | 443.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330380.00 | 433.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2233.50 | 34.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2225.33 | 42.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2229.33 | 38.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 73385.67 | 30009.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367648.83 | 30009.33 | 0.00 | 0.00 | 0.00 |
Average | 78922.16 | 1412.75 | 0.00 | 0.00 | 0.00 |
Sum | 1815209.67 | 32493.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:38
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.605714E+11 | 151912.04 | 17-JAN-05:11 | 5.20 | 3.69 | 0.541567E+10 | 7499.34 | 02-JAN-14:09 | 5.20 | 3.69 |
February | 0.505613E+11 | 150175.41 | 21-FEB-05:11 | 4.80 | 0.06 | 0.505945E+10 | 7499.34 | 14-FEB-14:00 | 4.80 | 0.06 |
March | 0.594976E+11 | 148197.63 | 27-MAR-04:11 | 9.63 | 3.84 | 0.606341E+10 | 7499.34 | 09-MAR-10:09 | 9.63 | 3.84 |
April | 0.591219E+11 | 126310.89 | 17-APR-04:12 | 14.63 | 10.22 | 0.541155E+10 | 7499.34 | 17-APR-13:30 | 16.65 | 10.04 |
May | 0.637305E+11 | 135273.12 | 01-MAY-04:11 | 15.20 | 5.46 | 0.589204E+10 | 7499.39 | 18-MAY-09:39 | 23.33 | 15.59 |
June | 0.655758E+11 | 144889.09 | 12-JUN-04:11 | 17.57 | 6.60 | 0.588284E+10 | 7499.19 | 27-JUN-13:20 | 31.30 | 16.77 |
July | 0.678382E+11 | 121215.84 | 25-JUL-05:02 | 24.32 | 17.42 | 0.547585E+10 | 7499.52 | 19-JUL-09:30 | 24.32 | 17.42 |
August | 0.773781E+11 | 131387.87 | 24-AUG-03:01 | 26.02 | 15.65 | 0.613954E+10 | 7499.53 | 25-AUG-09:39 | 25.93 | 16.57 |
September | 0.715353E+11 | 141720.95 | 25-SEP-04:22 | 9.75 | 8.81 | 0.545214E+10 | 7499.65 | 05-SEP-09:50 | 9.75 | 8.81 |
October | 0.718486E+11 | 149213.60 | 11-OCT-04:11 | 8.90 | 6.87 | 0.564757E+10 | 7499.61 | 04-OCT-09:00 | 8.90 | 6.87 |
November | 0.669767E+11 | 154735.47 | 06-NOV-05:11 | 3.50 | -0.5 | 0.556240E+10 | 7499.34 | 02-NOV-13:30 | 3.50 | -0.5 |
December | 0.641843E+11 | 130410.57 | 11-DEC-05:11 | 10.93 | 5.91 | 0.532731E+10 | 7499.34 | 20-DEC-14:50 | 17.43 | 4.96 |
Annual Sum or Average | 0.778820E+12 | 0.673298E+11 | ||||||||
Minimum of Months | 0.505613E+11 | 121215.84 | 3.50 | -0.5 | 0.505945E+10 | 7499.19 | 3.50 | -0.5 | ||
Maximum of Months | 0.773781E+11 | 154735.47 | 26.02 | 17.42 | 0.613954E+10 | 7499.65 | 31.30 | 17.42 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.462810E+11 | 112915.39 | 02-JAN-05:11 | 2.40 | 1.50 | 0.505707E+10 | 6734.86 | 02-JAN-10:09 | 10.97 | 7.20 |
February | 0.439994E+11 | 108879.69 | 21-FEB-05:11 | 4.80 | 0.06 | 0.458706E+10 | 6734.96 | 13-FEB-10:20 | 4.80 | 0.06 |
March | 0.566367E+11 | 111520.22 | 10-MAR-05:11 | 13.50 | 4.67 | 0.549003E+10 | 6734.87 | 17-MAR-09:00 | 8.30 | 1.95 |
April | 0.636998E+11 | 115445.49 | 06-APR-04:11 | 13.53 | 7.34 | 0.487899E+10 | 6734.90 | 27-APR-09:39 | 21.67 | 12.66 |
May | 0.637646E+11 | 114290.75 | 01-MAY-04:11 | 15.20 | 5.46 | 0.528389E+10 | 6734.82 | 08-MAY-09:20 | 25.33 | 12.01 |
June | 0.701369E+11 | 116021.42 | 01-JUN-04:12 | 20.53 | 9.26 | 0.526632E+10 | 6734.83 | 12-JUN-09:20 | 27.40 | 12.38 |
July | 0.744514E+11 | 114024.84 | 05-JUL-04:11 | 19.27 | 16.16 | 0.489160E+10 | 6734.80 | 11-JUL-09:20 | 29.47 | 18.61 |
August | 0.813309E+11 | 115438.23 | 30-AUG-04:12 | 18.50 | 14.17 | 0.549382E+10 | 6734.81 | 11-AUG-09:09 | 18.50 | 14.17 |
September | 0.619523E+11 | 120044.22 | 05-SEP-04:12 | 16.50 | 15.67 | 0.488162E+10 | 6734.82 | 06-SEP-09:09 | 25.28 | 18.43 |
October | 0.601089E+11 | 119229.67 | 10-OCT-04:11 | 13.17 | 8.78 | 0.507434E+10 | 6734.98 | 17-OCT-09:50 | 20.63 | 15.93 |
November | 0.534884E+11 | 115125.38 | 13-NOV-05:11 | 2.93 | 0.58 | 0.502379E+10 | 6734.88 | 09-NOV-10:09 | 2.93 | 0.58 |
December | 0.499997E+11 | 113632.42 | 11-DEC-05:11 | 10.93 | 5.91 | 0.489428E+10 | 6734.87 | 04-DEC-10:20 | 10.93 | 5.91 |
Annual Sum or Average | 0.725850E+12 | 0.608228E+11 | ||||||||
Minimum of Months | 0.439994E+11 | 108879.69 | 2.40 | 0.06 | 0.458706E+10 | 6734.80 | 2.93 | 0.06 | ||
Maximum of Months | 0.813309E+11 | 120044.22 | 20.53 | 16.16 | 0.549382E+10 | 6734.98 | 29.47 | 18.61 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.357947E+11 | 94404.51 | 13-JAN-06:01 | 3.22 | 0.84 | 0.497598E+10 | 6734.86 | 13-JAN-10:30 | 11.70 | 5.29 |
February | 0.354694E+11 | 98981.17 | 23-FEB-06:01 | 10.60 | 5.29 | 0.454227E+10 | 6734.96 | 13-FEB-10:20 | 10.60 | 5.29 |
March | 0.447934E+11 | 100964.69 | 09-MAR-06:01 | 7.70 | 1.78 | 0.545193E+10 | 6734.90 | 24-MAR-13:30 | 14.45 | 6.23 |
April | 0.473098E+11 | 102213.21 | 21-APR-04:11 | 17.60 | 6.24 | 0.485958E+10 | 6734.88 | 18-APR-09:00 | 17.60 | 6.24 |
May | 0.550541E+11 | 104407.41 | 23-MAY-04:11 | 20.40 | 14.91 | 0.527490E+10 | 6734.81 | 08-MAY-09:20 | 20.40 | 14.91 |
June | 0.582791E+11 | 106876.36 | 01-JUN-04:11 | 20.53 | 9.26 | 0.526381E+10 | 6734.82 | 13-JUN-09:20 | 28.53 | 13.08 |
July | 0.566119E+11 | 105005.63 | 05-JUL-04:11 | 19.27 | 16.16 | 0.488832E+10 | 6734.80 | 11-JUL-09:20 | 29.47 | 18.61 |
August | 0.596645E+11 | 105222.02 | 23-AUG-04:12 | 20.00 | 11.86 | 0.549177E+10 | 6734.81 | 11-AUG-09:09 | 20.00 | 11.86 |
September | 0.518577E+11 | 105638.25 | 21-SEP-04:11 | 20.93 | 16.42 | 0.487317E+10 | 6734.82 | 06-SEP-09:09 | 20.93 | 16.42 |
October | 0.481008E+11 | 106183.41 | 06-OCT-04:11 | 13.70 | 12.28 | 0.505070E+10 | 6734.95 | 17-OCT-09:50 | 20.63 | 15.93 |
November | 0.398097E+11 | 100853.99 | 03-NOV-05:01 | 8.80 | 8.26 | 0.497283E+10 | 6734.90 | 01-NOV-13:39 | 8.80 | 8.26 |
December | 0.352237E+11 | 91103.01 | 15-DEC-06:01 | 9.13 | 5.00 | 0.480131E+10 | 6734.89 | 14-DEC-14:30 | 9.13 | 5.00 |
Annual Sum or Average | 0.567969E+12 | 0.604466E+11 | ||||||||
Minimum of Months | 0.352237E+11 | 91103.01 | 3.22 | 0.84 | 0.454227E+10 | 6734.80 | 8.80 | 5.00 | ||
Maximum of Months | 0.596645E+11 | 106876.36 | 20.93 | 16.42 | 0.549177E+10 | 6734.96 | 29.47 | 18.61 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.269769E+11 | 38530.24 | 12-JAN-16:20 | 18.53 | 10.06 | 0.443794E+10 | 6734.82 | 11-JAN-14:00 | 18.53 | 10.06 |
February | 0.281616E+11 | 41808.09 | 07-FEB-14:52 | 20.00 | 9.25 | 0.415863E+10 | 6734.86 | 14-FEB-14:00 | 17.20 | 8.72 |
March | 0.393773E+11 | 52286.77 | 16-MAR-15:40 | 22.40 | 8.49 | 0.514195E+10 | 6734.86 | 23-MAR-13:00 | 15.60 | 6.41 |
April | 0.483504E+11 | 109140.69 | 21-APR-05:01 | 15.10 | 5.09 | 0.475612E+10 | 6734.86 | 17-APR-09:20 | 15.10 | 5.09 |
May | 0.612478E+11 | 113692.50 | 17-MAY-05:01 | 14.08 | 5.19 | 0.524165E+10 | 6734.80 | 19-MAY-09:20 | 26.83 | 16.66 |
June | 0.696327E+11 | 121216.98 | 05-JUN-04:11 | 22.57 | 13.89 | 0.525716E+10 | 6734.82 | 29-JUN-09:20 | 20.57 | 16.74 |
July | 0.679706E+11 | 119896.81 | 07-JUL-03:01 | 24.40 | 17.74 | 0.488660E+10 | 6734.79 | 11-JUL-09:20 | 29.47 | 18.61 |
August | 0.683998E+11 | 119106.62 | 21-AUG-04:12 | 21.50 | 15.65 | 0.547953E+10 | 6734.84 | 11-AUG-09:20 | 21.50 | 15.65 |
September | 0.558117E+11 | 115271.34 | 13-SEP-04:11 | 23.30 | 17.23 | 0.483475E+10 | 6734.84 | 06-SEP-09:20 | 23.30 | 17.23 |
October | 0.457779E+11 | 115611.40 | 04-OCT-05:01 | 17.80 | 15.98 | 0.491225E+10 | 6734.92 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.319517E+11 | 48135.88 | 10-NOV-14:53 | 15.60 | 10.20 | 0.457743E+10 | 6734.87 | 30-NOV-14:50 | 17.80 | 10.60 |
December | 0.257128E+11 | 31646.51 | 01-DEC-15:32 | 12.57 | 5.59 | 0.421277E+10 | 6734.86 | 01-DEC-14:20 | 12.57 | 5.59 |
Annual Sum or Average | 0.569371E+12 | 0.578968E+11 | ||||||||
Minimum of Months | 0.257128E+11 | 31646.51 | 12.57 | 5.09 | 0.415863E+10 | 6734.79 | 12.57 | 5.09 | ||
Maximum of Months | 0.696327E+11 | 121216.98 | 24.40 | 17.74 | 0.547953E+10 | 6734.92 | 29.47 | 18.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.447531E+10 | 5306.81 | 01-JAN-13:52 | 15.60 | 9.33 | 0.555971E+09 | 845.60 | 13-JAN-14:50 | 18.22 | 8.80 |
February | 0.462657E+10 | 6381.95 | 23-FEB-14:30 | 21.65 | 7.41 | 0.518765E+09 | 845.63 | 14-FEB-14:00 | 21.65 | 7.41 |
March | 0.655669E+10 | 8091.83 | 15-MAR-14:00 | 23.30 | 9.67 | 0.646438E+09 | 845.63 | 27-MAR-13:20 | 12.07 | 5.80 |
April | 0.902137E+10 | 11022.53 | 21-APR-15:00 | 32.20 | 15.49 | 0.601319E+09 | 845.64 | 27-APR-09:39 | 21.67 | 12.66 |
May | 0.109581E+11 | 17922.80 | 30-MAY-05:02 | 25.00 | 11.62 | 0.660530E+09 | 845.64 | 05-MAY-13:39 | 25.00 | 11.62 |
June | 0.139445E+11 | 23264.09 | 04-JUN-16:51 | 35.00 | 16.91 | 0.661238E+09 | 845.63 | 12-JUN-09:39 | 28.70 | 13.17 |
July | 0.143288E+11 | 16568.10 | 10-JUL-05:02 | 23.62 | 16.29 | 0.614612E+09 | 845.63 | 11-JUL-09:20 | 29.47 | 18.61 |
August | 0.141296E+11 | 14860.92 | 05-AUG-05:02 | 23.90 | 18.59 | 0.688900E+09 | 845.65 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.987378E+10 | 16282.11 | 13-SEP-04:11 | 23.30 | 17.23 | 0.608264E+09 | 845.63 | 06-SEP-09:09 | 23.30 | 17.23 |
October | 0.790941E+10 | 13695.27 | 05-OCT-04:11 | 21.30 | 16.26 | 0.621132E+09 | 845.65 | 17-OCT-09:50 | 20.63 | 15.93 |
November | 0.562382E+10 | 6943.68 | 08-NOV-14:30 | 23.60 | 11.30 | 0.587087E+09 | 845.63 | 09-NOV-10:09 | 18.58 | 8.97 |
December | 0.458131E+10 | 5001.70 | 11-DEC-05:12 | 10.93 | 5.91 | 0.538885E+09 | 845.62 | 08-DEC-14:20 | 10.93 | 5.91 |
Annual Sum or Average | 0.106029E+12 | 0.730314E+10 | ||||||||
Minimum of Months | 0.447531E+10 | 5001.70 | 10.93 | 5.91 | 0.518765E+09 | 845.60 | 10.93 | 5.80 | ||
Maximum of Months | 0.143288E+11 | 23264.09 | 35.00 | 18.59 | 0.688900E+09 | 845.65 | 31.70 | 19.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.421158E+10 | 6223.51 | 31-JAN-09:25 | 11.15 | 4.29 | 0.367115E+09 | 544.96 | 02-JAN-10:09 | 11.15 | 4.29 |
February | 0.466193E+10 | 16080.17 | 20-FEB-09:11 | 11.87 | 4.53 | 0.344242E+09 | 544.96 | 07-FEB-10:09 | 11.87 | 4.53 |
March | 0.662461E+10 | 22023.24 | 19-MAR-09:41 | 16.83 | 6.20 | 0.423790E+09 | 544.96 | 06-MAR-10:09 | 16.83 | 6.20 |
April | 0.880342E+10 | 24496.69 | 30-APR-08:31 | 19.43 | 12.60 | 0.389286E+09 | 544.98 | 27-APR-09:39 | 19.43 | 12.60 |
May | 0.105192E+11 | 23961.63 | 28-MAY-09:02 | 23.68 | 17.08 | 0.425659E+09 | 545.27 | 30-MAY-09:39 | 28.33 | 14.02 |
June | 0.122844E+11 | 24586.76 | 04-JUN-08:51 | 26.10 | 17.02 | 0.425310E+09 | 545.22 | 15-JUN-09:30 | 33.35 | 14.56 |
July | 0.121291E+11 | 24338.74 | 23-JUL-09:01 | 26.28 | 19.88 | 0.394875E+09 | 545.14 | 03-JUL-09:39 | 26.28 | 19.88 |
August | 0.120896E+11 | 19341.18 | 06-AUG-08:42 | 28.03 | 17.83 | 0.441470E+09 | 544.99 | 30-AUG-09:39 | 24.43 | 16.07 |
September | 0.955362E+10 | 24474.53 | 17-SEP-09:21 | 25.55 | 16.11 | 0.392098E+09 | 544.99 | 11-SEP-09:09 | 25.55 | 16.11 |
October | 0.747393E+10 | 22524.96 | 29-OCT-08:51 | 16.10 | 12.02 | 0.399113E+09 | 544.98 | 03-OCT-09:30 | 16.10 | 12.02 |
November | 0.544103E+10 | 10398.40 | 11-NOV-09:25 | 12.75 | 7.55 | 0.377533E+09 | 544.96 | 24-NOV-10:09 | 17.48 | 6.61 |
December | 0.409414E+10 | 5187.91 | 07-DEC-08:55 | 3.90 | -0.7 | 0.349772E+09 | 544.96 | 04-DEC-10:20 | 3.90 | -0.7 |
Annual Sum or Average | 0.978867E+11 | 0.473026E+10 | ||||||||
Minimum of Months | 0.409414E+10 | 5187.91 | 3.90 | -0.7 | 0.344242E+09 | 544.96 | 3.90 | -0.7 | ||
Maximum of Months | 0.122844E+11 | 24586.76 | 28.03 | 19.88 | 0.441470E+09 | 545.27 | 33.35 | 19.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.969197E+10 | 27660.59 | 01-JAN-13:52 | 15.60 | 9.33 | 0.605975E+09 | 846.29 | 03-JAN-14:50 | 20.50 | 8.55 |
February | 0.907960E+10 | 28304.25 | 19-FEB-12:21 | 20.00 | 7.71 | 0.550944E+09 | 846.69 | 22-FEB-14:09 | 21.78 | 7.94 |
March | 0.107202E+11 | 26560.90 | 05-MAR-14:01 | 18.98 | 8.70 | 0.659768E+09 | 845.97 | 16-MAR-13:09 | 22.30 | 9.05 |
April | 0.117294E+11 | 26465.41 | 16-APR-14:11 | 29.80 | 13.13 | 0.598504E+09 | 845.81 | 21-APR-13:09 | 31.78 | 14.74 |
May | 0.118915E+11 | 22983.12 | 21-MAY-14:01 | 34.90 | 17.83 | 0.656182E+09 | 845.67 | 05-MAY-13:39 | 34.90 | 17.83 |
June | 0.140639E+11 | 23049.98 | 04-JUN-16:11 | 35.40 | 17.17 | 0.659260E+09 | 845.65 | 12-JUN-13:20 | 32.97 | 15.61 |
July | 0.149386E+11 | 18661.10 | 23-JUL-13:41 | 30.40 | 21.37 | 0.613211E+09 | 845.65 | 11-JUL-09:20 | 30.40 | 21.37 |
August | 0.165798E+11 | 23304.94 | 06-AUG-15:21 | 36.10 | 18.39 | 0.687621E+09 | 846.77 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.146872E+11 | 28898.13 | 17-SEP-13:22 | 31.95 | 15.93 | 0.608605E+09 | 846.24 | 06-SEP-13:00 | 31.95 | 15.93 |
October | 0.142319E+11 | 28801.01 | 08-OCT-13:32 | 24.83 | 17.24 | 0.625828E+09 | 849.49 | 30-OCT-13:20 | 23.30 | 11.27 |
November | 0.119590E+11 | 29204.82 | 11-NOV-11:21 | 16.65 | 7.69 | 0.608256E+09 | 846.98 | 08-NOV-14:00 | 16.65 | 7.69 |
December | 0.982138E+10 | 27548.32 | 17-DEC-12:31 | 12.23 | 3.13 | 0.586316E+09 | 845.65 | 12-DEC-14:09 | 12.23 | 3.13 |
Annual Sum or Average | 0.149394E+12 | 0.746047E+10 | ||||||||
Minimum of Months | 0.907960E+10 | 18661.10 | 12.23 | 3.13 | 0.550944E+09 | 845.65 | 12.23 | 3.13 | ||
Maximum of Months | 0.165798E+11 | 29204.82 | 36.10 | 21.37 | 0.687621E+09 | 849.49 | 34.90 | 21.37 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.622244E+10 | 10122.81 | 12-JAN-15:30 | 18.90 | 10.10 | 0.359892E+09 | 544.96 | 11-JAN-14:20 | 18.90 | 10.10 |
February | 0.622763E+10 | 23138.31 | 19-FEB-15:42 | 22.80 | 8.58 | 0.331387E+09 | 544.96 | 14-FEB-14:30 | 22.80 | 8.58 |
March | 0.938269E+10 | 29081.97 | 05-MAR-16:42 | 20.50 | 8.93 | 0.416100E+09 | 544.96 | 10-MAR-14:09 | 17.80 | 6.82 |
April | 0.129132E+11 | 32050.74 | 30-APR-16:31 | 30.20 | 12.69 | 0.390629E+09 | 544.97 | 27-APR-09:39 | 30.20 | 12.69 |
May | 0.127105E+11 | 33466.41 | 14-MAY-16:21 | 31.95 | 13.61 | 0.422150E+09 | 544.97 | 05-MAY-13:39 | 31.95 | 13.61 |
June | 0.155167E+11 | 35013.75 | 25-JUN-16:51 | 31.70 | 16.84 | 0.425394E+09 | 544.96 | 22-JUN-09:09 | 31.70 | 16.84 |
July | 0.165907E+11 | 32825.74 | 23-JUL-15:01 | 31.20 | 21.52 | 0.396376E+09 | 544.96 | 11-JUL-09:20 | 31.20 | 21.52 |
August | 0.177686E+11 | 31837.94 | 06-AUG-16:41 | 36.10 | 18.73 | 0.445094E+09 | 544.99 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.118130E+11 | 32227.70 | 17-SEP-16:41 | 31.88 | 15.56 | 0.389125E+09 | 544.96 | 21-SEP-13:00 | 31.70 | 18.12 |
October | 0.101673E+11 | 28166.65 | 15-OCT-14:21 | 20.00 | 14.75 | 0.395096E+09 | 544.97 | 20-OCT-13:50 | 24.22 | 11.61 |
November | 0.811906E+10 | 28722.83 | 19-NOV-16:11 | 18.13 | 6.46 | 0.377727E+09 | 544.96 | 30-NOV-14:09 | 17.80 | 10.31 |
December | 0.712649E+10 | 11780.71 | 03-DEC-15:33 | 7.80 | 4.79 | 0.362094E+09 | 544.96 | 05-DEC-14:20 | 13.17 | 7.37 |
Annual Sum or Average | 0.134558E+12 | 0.471106E+10 | ||||||||
Minimum of Months | 0.622244E+10 | 10122.81 | 7.80 | 4.79 | 0.331387E+09 | 544.96 | 13.17 | 6.82 | ||
Maximum of Months | 0.177686E+11 | 35013.75 | 36.10 | 21.52 | 0.445094E+09 | 544.99 | 31.95 | 21.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.271443E+10 | 4691.69 | 12-JAN-14:30 | 18.60 | 9.87 | 0.500667E+09 | 793.91 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.314813E+10 | 4757.67 | 22-FEB-13:30 | 21.15 | 7.71 | 0.475649E+09 | 845.58 | 23-FEB-14:00 | 21.10 | 7.10 |
March | 0.469685E+10 | 6512.15 | 22-MAR-14:40 | 24.07 | 8.96 | 0.602971E+09 | 845.63 | 10-MAR-14:00 | 24.07 | 8.96 |
April | 0.668493E+10 | 10136.59 | 21-APR-15:00 | 32.20 | 15.49 | 0.579875E+09 | 845.64 | 27-APR-09:00 | 22.20 | 13.12 |
May | 0.972010E+10 | 12431.99 | 31-MAY-04:01 | 26.32 | 12.48 | 0.655222E+09 | 845.64 | 05-MAY-13:39 | 26.32 | 12.48 |
June | 0.122874E+11 | 19646.12 | 04-JUN-16:51 | 35.00 | 16.91 | 0.660822E+09 | 845.63 | 12-JUN-09:39 | 28.70 | 13.17 |
July | 0.116983E+11 | 18694.49 | 03-JUL-03:02 | 28.90 | 17.76 | 0.614271E+09 | 845.63 | 03-JUL-09:20 | 31.13 | 18.30 |
August | 0.109074E+11 | 16636.10 | 24-AUG-05:02 | 25.00 | 15.62 | 0.686457E+09 | 845.64 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.844511E+10 | 10269.63 | 20-SEP-14:30 | 33.30 | 17.76 | 0.601061E+09 | 845.63 | 06-SEP-09:09 | 33.30 | 17.76 |
October | 0.629238E+10 | 9856.69 | 03-OCT-14:30 | 32.25 | 19.38 | 0.595729E+09 | 845.63 | 02-OCT-09:09 | 32.25 | 19.38 |
November | 0.388624E+10 | 5279.36 | 09-NOV-14:40 | 23.30 | 12.57 | 0.528667E+09 | 844.99 | 08-NOV-14:00 | 23.30 | 12.57 |
December | 0.241455E+10 | 3861.80 | 07-DEC-14:20 | 15.77 | 6.80 | 0.476658E+09 | 771.65 | 08-DEC-14:00 | 17.20 | 7.54 |
Annual Sum or Average | 0.828958E+11 | 0.697805E+10 | ||||||||
Minimum of Months | 0.241455E+10 | 3861.80 | 15.77 | 6.80 | 0.475649E+09 | 771.65 | 17.20 | 7.10 | ||
Maximum of Months | 0.122874E+11 | 19646.12 | 35.00 | 19.38 | 0.686457E+09 | 845.64 | 33.30 | 19.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259992E+10 | 9086.13 | 12-JAN-11:02 | 14.18 | 7.39 | 0.253717E+09 | 548.49 | 12-JAN-15:09 | 18.90 | 10.04 |
February | 0.330538E+10 | 14880.07 | 21-FEB-11:01 | 20.00 | 7.35 | 0.242751E+09 | 548.49 | 17-FEB-15:09 | 20.00 | 7.35 |
March | 0.520210E+10 | 17717.99 | 21-MAR-10:01 | 17.15 | 6.75 | 0.302330E+09 | 548.50 | 21-MAR-14:09 | 23.98 | 9.19 |
April | 0.762050E+10 | 24589.16 | 30-APR-10:02 | 22.67 | 13.27 | 0.283521E+09 | 548.52 | 14-APR-10:09 | 22.67 | 13.27 |
May | 0.100887E+11 | 24782.29 | 28-MAY-09:12 | 24.07 | 17.19 | 0.312598E+09 | 548.52 | 26-MAY-10:09 | 24.07 | 17.19 |
June | 0.117523E+11 | 25582.51 | 04-JUN-08:51 | 26.10 | 17.02 | 0.313454E+09 | 548.51 | 12-JUN-10:09 | 30.10 | 14.01 |
July | 0.110048E+11 | 25566.83 | 09-JUL-09:01 | 26.38 | 19.19 | 0.292091E+09 | 548.50 | 11-JUL-10:09 | 30.60 | 18.98 |
August | 0.106800E+11 | 25370.51 | 27-AUG-09:51 | 31.70 | 14.69 | 0.324347E+09 | 548.54 | 31-AUG-10:09 | 24.18 | 15.58 |
September | 0.890253E+10 | 24722.46 | 04-SEP-09:22 | 24.70 | 18.41 | 0.287277E+09 | 548.51 | 29-SEP-10:09 | 24.18 | 15.46 |
October | 0.631313E+10 | 19386.36 | 01-OCT-09:52 | 24.40 | 13.63 | 0.287457E+09 | 548.53 | 05-OCT-12:09 | 28.58 | 18.41 |
November | 0.383435E+10 | 15806.25 | 03-NOV-10:01 | 15.97 | 12.12 | 0.265732E+09 | 548.50 | 08-NOV-15:09 | 23.80 | 11.44 |
December | 0.231325E+10 | 11093.38 | 14-DEC-11:01 | 9.68 | 5.96 | 0.239945E+09 | 548.49 | 01-DEC-13:09 | 9.68 | 5.96 |
Annual Sum or Average | 0.836169E+11 | 0.340522E+10 | ||||||||
Minimum of Months | 0.231325E+10 | 9086.13 | 9.68 | 5.96 | 0.239945E+09 | 548.49 | 9.68 | 5.96 | ||
Maximum of Months | 0.117523E+11 | 25582.51 | 31.70 | 19.19 | 0.324347E+09 | 548.54 | 30.60 | 18.98 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.911739E+10 | 25316.42 | 01-JAN-14:43 | 16.02 | 9.44 | 0.596858E+09 | 847.09 | 12-JAN-14:20 | 18.50 | 9.82 |
February | 0.851017E+10 | 27281.33 | 05-FEB-14:21 | 18.60 | 8.11 | 0.543123E+09 | 846.62 | 23-FEB-14:50 | 21.28 | 7.21 |
March | 0.943286E+10 | 25292.64 | 05-MAR-13:51 | 18.90 | 8.70 | 0.648367E+09 | 846.36 | 22-MAR-13:50 | 24.50 | 9.16 |
April | 0.962353E+10 | 25411.18 | 30-APR-14:41 | 29.90 | 12.59 | 0.587974E+09 | 846.25 | 21-APR-13:20 | 29.90 | 12.59 |
May | 0.107975E+11 | 13146.89 | 19-MAY-13:50 | 34.82 | 17.27 | 0.651415E+09 | 845.67 | 05-MAY-13:39 | 34.82 | 17.27 |
June | 0.123158E+11 | 22489.42 | 18-JUN-14:21 | 36.40 | 16.42 | 0.658217E+09 | 845.65 | 12-JUN-13:20 | 36.40 | 16.42 |
July | 0.121820E+11 | 25459.82 | 30-JUL-13:51 | 31.70 | 19.83 | 0.612370E+09 | 845.65 | 03-JUL-09:20 | 31.70 | 19.83 |
August | 0.134041E+11 | 25303.32 | 20-AUG-14:01 | 32.12 | 16.32 | 0.685420E+09 | 846.55 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.137454E+11 | 27013.93 | 04-SEP-13:22 | 30.60 | 18.77 | 0.605530E+09 | 846.25 | 26-SEP-13:20 | 25.97 | 15.08 |
October | 0.134127E+11 | 29607.35 | 29-OCT-13:21 | 23.90 | 11.32 | 0.619750E+09 | 873.94 | 30-OCT-13:20 | 23.30 | 11.27 |
November | 0.111172E+11 | 28326.35 | 05-NOV-13:31 | 16.50 | 8.48 | 0.599308E+09 | 870.68 | 03-NOV-13:39 | 16.50 | 8.48 |
December | 0.878421E+10 | 26152.53 | 31-DEC-13:52 | 13.30 | 5.24 | 0.574847E+09 | 845.67 | 07-DEC-14:39 | 13.30 | 5.24 |
Annual Sum or Average | 0.132443E+12 | 0.738318E+10 | ||||||||
Minimum of Months | 0.851017E+10 | 13146.89 | 13.30 | 5.24 | 0.543123E+09 | 845.65 | 13.30 | 5.24 | ||
Maximum of Months | 0.137454E+11 | 29607.35 | 36.40 | 19.83 | 0.685420E+09 | 873.94 | 36.40 | 19.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355694E+10 | 7578.43 | 12-JAN-15:30 | 18.90 | 10.10 | 0.332488E+09 | 541.87 | 12-JAN-14:00 | 18.90 | 10.10 |
February | 0.391192E+10 | 16506.74 | 19-FEB-16:32 | 22.40 | 8.34 | 0.308189E+09 | 544.96 | 03-FEB-14:00 | 22.40 | 8.34 |
March | 0.610189E+10 | 16383.82 | 05-MAR-16:32 | 20.40 | 8.89 | 0.382555E+09 | 544.95 | 22-MAR-13:00 | 24.40 | 9.14 |
April | 0.826570E+10 | 27643.77 | 30-APR-16:41 | 30.10 | 12.63 | 0.363624E+09 | 544.96 | 21-APR-13:20 | 30.10 | 12.63 |
May | 0.106584E+11 | 28255.67 | 29-MAY-16:31 | 32.97 | 16.56 | 0.411678E+09 | 544.97 | 05-MAY-13:39 | 32.97 | 16.56 |
June | 0.122180E+11 | 30733.39 | 25-JUN-17:01 | 31.60 | 16.78 | 0.420875E+09 | 544.96 | 12-JUN-09:39 | 31.60 | 16.78 |
July | 0.115376E+11 | 28510.45 | 30-JUL-15:11 | 31.87 | 19.80 | 0.391455E+09 | 544.96 | 03-JUL-09:20 | 31.87 | 19.80 |
August | 0.113974E+11 | 30174.24 | 27-AUG-16:31 | 35.00 | 16.38 | 0.435806E+09 | 544.97 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.963769E+10 | 26645.87 | 10-SEP-15:51 | 31.10 | 16.68 | 0.378143E+09 | 544.95 | 12-SEP-13:20 | 31.30 | 17.52 |
October | 0.764100E+10 | 27588.26 | 01-OCT-15:11 | 32.43 | 15.77 | 0.371416E+09 | 544.96 | 24-OCT-13:39 | 15.93 | 9.34 |
November | 0.506558E+10 | 11001.92 | 03-NOV-16:00 | 23.90 | 13.45 | 0.342663E+09 | 544.96 | 17-NOV-14:39 | 17.23 | 7.37 |
December | 0.329290E+10 | 6906.70 | 15-DEC-15:52 | 15.60 | 6.14 | 0.320061E+09 | 544.96 | 15-DEC-14:50 | 15.60 | 6.14 |
Annual Sum or Average | 0.932849E+11 | 0.445895E+10 | ||||||||
Minimum of Months | 0.329290E+10 | 6906.70 | 15.60 | 6.14 | 0.308189E+09 | 541.87 | 15.60 | 6.14 | ||
Maximum of Months | 0.122180E+11 | 30733.39 | 35.00 | 19.80 | 0.435806E+09 | 544.97 | 32.97 | 19.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204906E+10 | 4941.02 | 12-JAN-14:30 | 18.60 | 9.87 | 0.477314E+09 | 731.14 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.270945E+10 | 5532.48 | 20-FEB-14:22 | 22.75 | 8.67 | 0.448541E+09 | 806.62 | 22-FEB-14:00 | 22.20 | 8.00 |
March | 0.469879E+10 | 6990.01 | 22-MAR-14:40 | 24.07 | 8.96 | 0.568990E+09 | 845.62 | 22-MAR-13:50 | 24.07 | 8.96 |
April | 0.739637E+10 | 11564.38 | 21-APR-15:00 | 32.20 | 15.49 | 0.554313E+09 | 845.63 | 21-APR-13:20 | 32.20 | 15.49 |
May | 0.110368E+11 | 27154.51 | 29-MAY-16:41 | 32.88 | 16.50 | 0.640125E+09 | 845.64 | 05-MAY-13:39 | 32.88 | 16.50 |
June | 0.140998E+11 | 30359.07 | 18-JUN-14:21 | 36.40 | 16.42 | 0.656674E+09 | 845.63 | 30-JUN-09:30 | 24.70 | 17.49 |
July | 0.135947E+11 | 27742.55 | 02-JUL-16:21 | 38.05 | 18.71 | 0.610533E+09 | 845.63 | 03-JUL-09:20 | 31.13 | 18.30 |
August | 0.125486E+11 | 28451.95 | 13-AUG-16:01 | 31.60 | 18.60 | 0.676125E+09 | 845.63 | 11-AUG-09:20 | 31.60 | 18.60 |
September | 0.951287E+10 | 11833.37 | 20-SEP-14:30 | 33.30 | 17.76 | 0.583341E+09 | 845.63 | 12-SEP-13:20 | 33.30 | 17.76 |
October | 0.652914E+10 | 11258.72 | 03-OCT-14:30 | 32.25 | 19.38 | 0.564256E+09 | 845.62 | 02-OCT-13:20 | 32.25 | 19.38 |
November | 0.332581E+10 | 6107.04 | 09-NOV-14:10 | 23.30 | 12.48 | 0.497211E+09 | 826.14 | 08-NOV-14:00 | 23.30 | 12.48 |
December | 0.162489E+10 | 4232.09 | 08-DEC-15:30 | 17.20 | 7.54 | 0.455305E+09 | 702.07 | 08-DEC-14:00 | 17.20 | 7.54 |
Annual Sum or Average | 0.891263E+11 | 0.673273E+10 | ||||||||
Minimum of Months | 0.162489E+10 | 4232.09 | 17.20 | 7.54 | 0.448541E+09 | 702.07 | 17.20 | 7.54 | ||
Maximum of Months | 0.140998E+11 | 30359.07 | 38.05 | 19.38 | 0.676125E+09 | 845.64 | 33.30 | 19.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.246753E+10 | 4185.84 | 12-JAN-14:30 | 18.60 | 9.87 | 0.318964E+09 | 497.77 | 31-JAN-10:30 | 12.25 | 4.63 |
February | 0.308759E+10 | 5360.92 | 20-FEB-14:22 | 22.75 | 8.67 | 0.311413E+09 | 544.96 | 22-FEB-10:00 | 16.10 | 5.74 |
March | 0.499160E+10 | 7958.97 | 31-MAR-09:53 | 18.90 | 6.59 | 0.401645E+09 | 544.96 | 17-MAR-09:00 | 18.90 | 6.59 |
April | 0.773170E+10 | 18318.97 | 30-APR-09:32 | 21.47 | 13.12 | 0.383030E+09 | 544.98 | 27-APR-09:39 | 21.47 | 13.12 |
May | 0.107664E+11 | 25869.73 | 29-MAY-09:22 | 23.60 | 15.91 | 0.423183E+09 | 545.34 | 30-MAY-09:39 | 28.33 | 14.02 |
June | 0.129268E+11 | 26342.62 | 18-JUN-08:21 | 27.20 | 16.68 | 0.425184E+09 | 545.44 | 07-JUN-09:00 | 27.20 | 16.68 |
July | 0.121892E+11 | 25789.11 | 16-JUL-08:22 | 27.50 | 18.69 | 0.394652E+09 | 545.48 | 03-JUL-09:50 | 27.50 | 18.69 |
August | 0.116741E+11 | 25753.16 | 20-AUG-08:52 | 26.10 | 16.44 | 0.439284E+09 | 545.00 | 30-AUG-09:39 | 24.43 | 16.07 |
September | 0.939706E+10 | 25682.60 | 17-SEP-09:52 | 27.20 | 16.06 | 0.388465E+09 | 545.00 | 11-SEP-09:09 | 27.20 | 16.06 |
October | 0.616554E+10 | 12583.58 | 01-OCT-09:52 | 24.40 | 13.63 | 0.386118E+09 | 544.99 | 03-OCT-09:30 | 24.70 | 16.45 |
November | 0.345388E+10 | 7715.17 | 10-NOV-09:40 | 19.03 | 12.06 | 0.343284E+09 | 544.96 | 09-NOV-10:09 | 19.03 | 12.06 |
December | 0.209018E+10 | 3559.75 | 01-DEC-10:30 | 13.05 | 5.08 | 0.300410E+09 | 470.48 | 01-DEC-10:39 | 13.33 | 5.28 |
Annual Sum or Average | 0.869415E+11 | 0.451563E+10 | ||||||||
Minimum of Months | 0.209018E+10 | 3559.75 | 13.05 | 5.08 | 0.300410E+09 | 470.48 | 12.25 | 4.63 | ||
Maximum of Months | 0.129268E+11 | 26342.62 | 27.50 | 18.69 | 0.439284E+09 | 545.48 | 28.33 | 18.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.770328E+10 | 20301.03 | 12-JAN-14:13 | 18.50 | 9.82 | 0.573529E+09 | 846.08 | 12-JAN-14:00 | 18.90 | 10.02 |
February | 0.737478E+10 | 32031.09 | 20-FEB-14:22 | 22.75 | 8.67 | 0.523444E+09 | 845.75 | 22-FEB-14:09 | 21.78 | 7.94 |
March | 0.885904E+10 | 18992.86 | 05-MAR-14:01 | 18.98 | 8.70 | 0.624687E+09 | 845.65 | 27-MAR-13:09 | 11.88 | 5.69 |
April | 0.996526E+10 | 25870.80 | 16-APR-15:01 | 29.50 | 11.50 | 0.571317E+09 | 845.67 | 24-APR-13:09 | 24.50 | 9.80 |
May | 0.118994E+11 | 30051.39 | 21-MAY-14:11 | 34.80 | 17.82 | 0.639274E+09 | 845.66 | 05-MAY-13:39 | 34.80 | 17.82 |
June | 0.140395E+11 | 31162.81 | 18-JUN-14:21 | 36.40 | 16.42 | 0.653070E+09 | 845.65 | 12-JUN-13:20 | 36.40 | 16.42 |
July | 0.139414E+11 | 31726.29 | 30-JUL-15:11 | 31.87 | 19.80 | 0.608323E+09 | 845.65 | 03-JUL-09:20 | 31.87 | 19.80 |
August | 0.148563E+11 | 31481.48 | 13-AUG-16:01 | 31.60 | 18.60 | 0.677470E+09 | 845.83 | 29-AUG-13:39 | 31.50 | 19.75 |
September | 0.145118E+11 | 33813.58 | 17-SEP-13:51 | 32.20 | 16.09 | 0.595151E+09 | 846.24 | 06-SEP-13:00 | 32.20 | 16.09 |
October | 0.129971E+11 | 35187.98 | 01-OCT-14:31 | 32.60 | 15.77 | 0.603400E+09 | 846.25 | 03-OCT-13:00 | 32.80 | 19.64 |
November | 0.979362E+10 | 31701.11 | 11-NOV-11:51 | 17.20 | 7.85 | 0.576968E+09 | 846.16 | 08-NOV-14:39 | 17.20 | 7.85 |
December | 0.708913E+10 | 17027.50 | 06-DEC-13:42 | 12.12 | 4.00 | 0.550300E+09 | 845.65 | 13-DEC-10:20 | 9.80 | 5.25 |
Annual Sum or Average | 0.133031E+12 | 0.719693E+10 | ||||||||
Minimum of Months | 0.708913E+10 | 17027.50 | 12.12 | 4.00 | 0.523444E+09 | 845.65 | 9.80 | 5.25 | ||
Maximum of Months | 0.148563E+11 | 35187.98 | 36.40 | 19.80 | 0.677470E+09 | 846.25 | 36.40 | 19.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292016E+10 | 7959.70 | 12-JAN-15:30 | 18.90 | 10.10 | 0.326335E+09 | 544.49 | 12-JAN-14:00 | 18.90 | 10.10 |
February | 0.340289E+10 | 11844.47 | 20-FEB-16:22 | 22.75 | 8.45 | 0.301403E+09 | 544.96 | 07-FEB-14:39 | 22.75 | 8.45 |
March | 0.578293E+10 | 13173.90 | 21-MAR-16:00 | 25.00 | 9.53 | 0.372889E+09 | 544.94 | 22-MAR-13:00 | 24.40 | 9.14 |
April | 0.848539E+10 | 32077.04 | 16-APR-15:41 | 29.90 | 11.70 | 0.354159E+09 | 544.96 | 21-APR-13:20 | 31.87 | 14.84 |
May | 0.113791E+11 | 34744.07 | 29-MAY-16:41 | 32.88 | 16.50 | 0.403780E+09 | 544.96 | 05-MAY-13:39 | 32.88 | 16.50 |
June | 0.133573E+11 | 31493.90 | 18-JUN-14:21 | 36.40 | 16.42 | 0.416165E+09 | 544.96 | 12-JUN-13:20 | 36.40 | 16.42 |
July | 0.127129E+11 | 32881.59 | 30-JUL-15:11 | 31.87 | 19.80 | 0.387110E+09 | 544.96 | 03-JUL-09:20 | 31.87 | 19.80 |
August | 0.123756E+11 | 34511.26 | 13-AUG-16:01 | 31.60 | 18.60 | 0.428719E+09 | 544.96 | 30-AUG-13:20 | 29.80 | 18.64 |
September | 0.101823E+11 | 33690.41 | 17-SEP-15:51 | 32.80 | 15.88 | 0.369397E+09 | 544.95 | 12-SEP-13:20 | 32.80 | 15.88 |
October | 0.743900E+10 | 31234.42 | 01-OCT-15:11 | 32.43 | 15.77 | 0.361665E+09 | 544.96 | 20-OCT-13:50 | 24.22 | 11.61 |
November | 0.442774E+10 | 11442.00 | 03-NOV-16:00 | 23.90 | 13.45 | 0.335487E+09 | 544.96 | 15-NOV-14:39 | 14.80 | 5.14 |
December | 0.259197E+10 | 6542.20 | 15-DEC-15:52 | 15.60 | 6.14 | 0.312573E+09 | 541.34 | 07-DEC-14:00 | 15.60 | 6.14 |
Annual Sum or Average | 0.950572E+11 | 0.436968E+10 | ||||||||
Minimum of Months | 0.259197E+10 | 6542.20 | 15.60 | 6.14 | 0.301403E+09 | 541.34 | 14.80 | 5.14 | ||
Maximum of Months | 0.133573E+11 | 34744.07 | 36.40 | 19.80 | 0.428719E+09 | 544.96 | 36.40 | 19.80 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.484460E+10 | 8508.23 | 02-JAN-06:06 | -0.4 | -1.2 | 0.00 | 0.00 | 01-JAN-00:10 | -0.4 | -1.2 |
February | 0.479707E+10 | 7838.27 | 22-FEB-06:05 | 2.52 | -2.0 | 0.00 | 0.00 | 01-FEB-00:10 | 2.52 | -2.0 |
March | 0.660479E+10 | 7692.56 | 17-MAR-05:03 | 3.72 | -1.9 | 0.00 | 0.00 | 01-MAR-00:10 | 3.72 | -1.9 |
April | 0.895606E+10 | 9209.18 | 21-APR-15:20 | 31.83 | 15.27 | 0.00 | 0.00 | 01-APR-00:10 | 31.83 | 15.27 |
May | 0.102976E+11 | 10776.75 | 30-MAY-05:13 | 25.00 | 11.65 | 0.00 | 0.00 | 01-MAY-00:10 | 25.00 | 11.65 |
June | 0.121794E+11 | 10732.32 | 05-JUN-15:40 | 37.43 | 17.20 | 0.00 | 0.00 | 01-JUN-00:10 | 37.43 | 17.20 |
July | 0.123020E+11 | 10950.46 | 03-JUL-14:30 | 37.50 | 18.90 | 0.00 | 0.00 | 01-JUL-00:10 | 37.50 | 18.90 |
August | 0.129377E+11 | 11090.36 | 07-AUG-15:10 | 35.37 | 18.63 | 0.00 | 0.00 | 01-AUG-00:10 | 35.37 | 18.63 |
September | 0.104387E+11 | 10962.77 | 05-SEP-15:20 | 31.10 | 19.29 | 0.00 | 0.00 | 01-SEP-00:10 | 31.10 | 19.29 |
October | 0.882106E+10 | 9966.76 | 05-OCT-16:00 | 31.10 | 17.21 | 0.00 | 0.00 | 01-OCT-00:10 | 31.10 | 17.21 |
November | 0.642153E+10 | 7967.41 | 13-NOV-05:15 | 2.93 | 0.58 | 0.00 | 0.00 | 01-NOV-00:10 | 2.93 | 0.58 |
December | 0.516334E+10 | 7402.45 | 08-DEC-06:06 | 1.28 | -1.2 | 0.00 | 0.00 | 01-DEC-00:10 | 1.28 | -1.2 |
Annual Sum or Average | 0.103764E+12 | 0.00 | ||||||||
Minimum of Months | 0.479707E+10 | 7402.45 | -0.4 | -2.0 | 0.00 | 0.00 | -0.4 | -2.0 | ||
Maximum of Months | 0.129377E+11 | 11090.36 | 37.50 | 19.29 | 0.00 | 0.00 | 37.50 | 19.29 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233315E+10 | 10926.49 | 28-JAN-05:01 | -2.9 | -6.3 | 0.00 | 0.00 | 01-JAN-00:10 | -2.9 | -6.3 |
February | 0.290017E+10 | 11737.98 | 09-FEB-05:01 | -0.4 | -2.4 | 0.00 | 0.00 | 01-FEB-00:10 | -0.4 | -2.4 |
March | 0.423307E+10 | 11146.72 | 02-MAR-05:01 | -3.9 | -6.5 | 0.00 | 0.00 | 01-MAR-00:10 | -3.9 | -6.5 |
April | 0.613519E+10 | 8264.75 | 22-APR-05:06 | 8.80 | 3.38 | 0.00 | 0.00 | 01-APR-00:10 | 8.80 | 3.38 |
May | 0.842940E+10 | 8812.56 | 31-MAY-05:02 | 24.22 | 11.57 | 0.00 | 0.00 | 01-MAY-00:10 | 24.22 | 11.57 |
June | 0.103182E+11 | 9691.61 | 07-JUN-15:50 | 37.20 | 17.51 | 0.00 | 0.00 | 01-JUN-00:10 | 37.20 | 17.51 |
July | 0.987967E+10 | 9869.31 | 12-JUL-05:13 | 22.07 | 17.23 | 0.00 | 0.00 | 01-JUL-00:10 | 22.07 | 17.23 |
August | 0.100535E+11 | 9568.25 | 09-AUG-05:13 | 22.93 | 18.25 | 0.00 | 0.00 | 01-AUG-00:10 | 22.93 | 18.25 |
September | 0.842171E+10 | 8714.23 | 20-SEP-15:30 | 33.30 | 17.34 | 0.00 | 0.00 | 01-SEP-00:10 | 33.30 | 17.34 |
October | 0.646141E+10 | 8316.84 | 05-OCT-16:00 | 31.10 | 17.21 | 0.00 | 0.00 | 01-OCT-00:10 | 31.10 | 17.21 |
November | 0.384335E+10 | 9449.92 | 28-NOV-05:01 | -0.3 | -1.6 | 0.00 | 0.00 | 01-NOV-00:10 | -0.3 | -1.6 |
December | 0.245623E+10 | 10558.87 | 30-DEC-05:01 | -2.8 | -3.9 | 0.00 | 0.00 | 01-DEC-00:10 | -2.8 | -3.9 |
Annual Sum or Average | 0.754650E+11 | 0.00 | ||||||||
Minimum of Months | 0.233315E+10 | 8264.75 | -3.9 | -6.5 | 0.00 | 0.00 | -3.9 | -6.5 | ||
Maximum of Months | 0.103182E+11 | 11737.98 | 37.20 | 18.25 | 0.00 | 0.00 | 37.20 | 18.25 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.367300E+10 | 14413.50 | 12-JAN-15:02 | 18.90 | 10.04 | 0.00 | 0.00 | 01-JAN-00:10 | 18.90 | 10.04 |
February | 0.557640E+10 | 19057.64 | 22-FEB-14:00 | 21.70 | 7.92 | 0.00 | 0.00 | 01-FEB-00:10 | 21.70 | 7.92 |
March | 0.102265E+11 | 23859.25 | 16-MAR-14:05 | 22.80 | 9.24 | 0.00 | 0.00 | 01-MAR-00:10 | 22.80 | 9.24 |
April | 0.171822E+11 | 34497.90 | 28-APR-14:00 | 28.90 | 14.04 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 14.04 |
May | 0.244520E+11 | 38947.54 | 30-MAY-14:00 | 34.40 | 17.48 | 0.00 | 0.00 | 01-MAY-00:10 | 34.40 | 17.48 |
June | 0.308810E+11 | 42571.54 | 18-JUN-13:41 | 36.02 | 16.14 | 0.00 | 0.00 | 01-JUN-00:10 | 36.02 | 16.14 |
July | 0.286923E+11 | 40813.71 | 26-JUL-14:00 | 36.70 | 20.76 | 0.00 | 0.00 | 01-JUL-00:10 | 36.70 | 20.76 |
August | 0.268550E+11 | 39734.09 | 04-AUG-13:40 | 34.63 | 19.72 | 0.00 | 0.00 | 01-AUG-00:10 | 34.63 | 19.72 |
September | 0.217801E+11 | 36632.75 | 15-SEP-13:05 | 32.70 | 18.30 | 0.00 | 0.00 | 01-SEP-00:10 | 32.70 | 18.30 |
October | 0.133998E+11 | 32274.06 | 03-OCT-14:05 | 32.62 | 19.55 | 0.00 | 0.00 | 01-OCT-00:10 | 32.62 | 19.55 |
November | 0.634788E+10 | 19269.96 | 03-NOV-14:15 | 22.97 | 13.56 | 0.00 | 0.00 | 01-NOV-00:10 | 22.97 | 13.56 |
December | 0.283121E+10 | 10063.41 | 17-DEC-13:10 | 13.17 | 3.61 | 0.00 | 0.00 | 01-DEC-00:10 | 13.17 | 3.61 |
Annual Sum or Average | 0.191897E+12 | 0.00 | ||||||||
Minimum of Months | 0.283121E+10 | 10063.41 | 13.17 | 3.61 | 0.00 | 0.00 | 13.17 | 3.61 | ||
Maximum of Months | 0.308810E+11 | 42571.54 | 36.70 | 20.76 | 0.00 | 0.00 | 36.70 | 20.76 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.354799E+10 | 2340.02 | 30-JAN-16:53 | 15.60 | 6.12 | 95230013.08 | 126.82 | 25-JAN-14:09 | 15.60 | 6.12 |
February | 0.772096E+10 | 4177.86 | 21-FEB-17:00 | 22.20 | 7.81 | 86396498.14 | 126.82 | 13-FEB-14:00 | 22.20 | 7.81 |
March | 0.140421E+11 | 6998.90 | 31-MAR-23:52 | 11.20 | 2.36 | 0.103236E+09 | 126.82 | 14-MAR-13:09 | 11.20 | 2.36 |
April | 0.190777E+11 | 8156.59 | 30-APR-18:01 | 29.63 | 12.67 | 91605119.04 | 126.82 | 18-APR-13:00 | 29.63 | 12.67 |
May | 0.478571E+10 | 3520.72 | 31-MAY-24:00 | 25.20 | 11.70 | 99233798.52 | 126.83 | 25-MAY-09:00 | 25.20 | 11.70 |
June | 0.960824E+10 | 5359.45 | 30-JUN-23:20 | 27.97 | 17.38 | 98958029.42 | 126.83 | 28-JUN-09:00 | 27.97 | 17.38 |
July | 0.149449E+11 | 7231.50 | 31-JUL-23:33 | 27.83 | 17.96 | 91881692.91 | 126.82 | 26-JUL-13:00 | 27.83 | 17.96 |
August | 0.199944E+11 | 8204.68 | 06-AUG-18:11 | 35.40 | 18.00 | 0.103240E+09 | 126.83 | 02-AUG-09:09 | 35.40 | 18.00 |
September | 0.467949E+10 | 3430.27 | 30-SEP-23:51 | 16.10 | 8.62 | 91608292.90 | 126.84 | 22-SEP-09:00 | 16.10 | 8.62 |
October | 0.947072E+10 | 5132.17 | 31-OCT-23:52 | 10.60 | 4.98 | 95230808.96 | 126.83 | 04-OCT-09:09 | 10.60 | 4.98 |
November | 0.135426E+11 | 6292.31 | 09-NOV-16:50 | 22.88 | 12.85 | 94300292.11 | 126.82 | 03-NOV-13:09 | 22.88 | 12.85 |
December | 0.187925E+11 | 7970.44 | 15-DEC-16:35 | 15.20 | 5.96 | 91880876.41 | 126.82 | 15-DEC-14:00 | 15.20 | 5.96 |
Annual Sum or Average | 0.140207E+12 | 0.114280E+10 | ||||||||
Minimum of Months | 0.354799E+10 | 2340.02 | 10.60 | 2.36 | 86396498.14 | 126.82 | 10.60 | 2.36 | ||
Maximum of Months | 0.199944E+11 | 8204.68 | 35.40 | 18.00 | 0.103240E+09 | 126.84 | 35.40 | 18.00 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205675E+10 | 2089.29 | 30-JAN-16:53 | 15.60 | 6.12 | 95230015.75 | 126.82 | 25-JAN-14:09 | 15.60 | 6.12 |
February | 0.669127E+10 | 3946.28 | 21-FEB-17:00 | 22.20 | 7.81 | 86396498.69 | 126.82 | 13-FEB-14:00 | 22.20 | 7.81 |
March | 0.128580E+11 | 6524.83 | 31-MAR-23:33 | 11.27 | 2.40 | 0.103236E+09 | 126.82 | 14-MAR-13:09 | 11.27 | 2.40 |
April | 0.178427E+11 | 7676.87 | 30-APR-17:57 | 30.00 | 12.88 | 91605131.11 | 126.82 | 18-APR-13:00 | 30.00 | 12.88 |
May | 0.425279E+10 | 3407.21 | 31-MAY-24:00 | 25.20 | 11.70 | 99233808.25 | 126.83 | 24-MAY-13:09 | 25.20 | 11.70 |
June | 0.908679E+10 | 5236.77 | 30-JUN-24:00 | 27.70 | 17.05 | 98958098.02 | 126.83 | 28-JUN-09:00 | 27.70 | 17.05 |
July | 0.141965E+11 | 7031.64 | 31-JUL-23:54 | 27.50 | 18.10 | 91881747.04 | 126.82 | 26-JUL-13:00 | 27.50 | 18.10 |
August | 0.189978E+11 | 7726.28 | 06-AUG-18:07 | 35.50 | 18.11 | 0.103240E+09 | 126.83 | 02-AUG-09:09 | 35.50 | 18.11 |
September | 0.408621E+10 | 3126.64 | 30-SEP-23:26 | 16.40 | 9.13 | 91608339.15 | 126.84 | 22-SEP-09:00 | 16.40 | 9.13 |
October | 0.854639E+10 | 4694.90 | 31-OCT-23:42 | 10.60 | 4.91 | 95230864.85 | 126.83 | 04-OCT-09:00 | 10.60 | 4.91 |
November | 0.121216E+11 | 5970.57 | 09-NOV-16:50 | 22.88 | 12.85 | 94300295.30 | 126.82 | 03-NOV-13:09 | 22.88 | 12.85 |
December | 0.167442E+11 | 7562.84 | 15-DEC-16:45 | 15.10 | 5.92 | 91880876.74 | 126.82 | 15-DEC-14:00 | 15.10 | 5.92 |
Annual Sum or Average | 0.127481E+12 | 0.114280E+10 | ||||||||
Minimum of Months | 0.205675E+10 | 2089.29 | 10.60 | 2.40 | 86396498.69 | 126.82 | 10.60 | 2.40 | ||
Maximum of Months | 0.189978E+11 | 7726.28 | 35.50 | 18.11 | 0.103240E+09 | 126.84 | 35.50 | 18.11 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104763E+10 | 2076.92 | 19-JAN-16:55 | 12.80 | 6.10 | 95226379.67 | 126.82 | 30-JAN-10:09 | 7.57 | 1.63 |
February | 0.524518E+10 | 3991.84 | 21-FEB-17:00 | 22.20 | 7.81 | 86396500.16 | 126.82 | 13-FEB-14:00 | 22.20 | 7.81 |
March | 0.117266E+11 | 6032.49 | 31-MAR-23:10 | 11.37 | 2.47 | 0.103236E+09 | 126.82 | 14-MAR-13:09 | 11.37 | 2.47 |
April | 0.174270E+11 | 8027.45 | 30-APR-17:53 | 30.00 | 12.88 | 91605132.00 | 126.82 | 18-APR-13:00 | 30.00 | 12.88 |
May | 0.414993E+10 | 3422.57 | 31-MAY-24:00 | 25.20 | 11.70 | 99233788.98 | 126.83 | 25-MAY-09:00 | 25.20 | 11.70 |
June | 0.922493E+10 | 5212.34 | 30-JUN-24:00 | 27.70 | 17.05 | 98958093.04 | 126.83 | 28-JUN-09:00 | 27.70 | 17.05 |
July | 0.143750E+11 | 7027.84 | 31-JUL-23:54 | 27.50 | 18.10 | 91881781.28 | 126.82 | 19-JUL-09:09 | 27.50 | 18.10 |
August | 0.190729E+11 | 8245.70 | 06-AUG-18:06 | 35.50 | 18.11 | 0.103240E+09 | 126.83 | 02-AUG-09:09 | 35.50 | 18.11 |
September | 0.391719E+10 | 2770.39 | 30-SEP-23:02 | 16.60 | 9.47 | 91608251.37 | 126.84 | 22-SEP-09:00 | 16.60 | 9.47 |
October | 0.785253E+10 | 4287.96 | 05-OCT-17:00 | 28.30 | 17.90 | 95230896.11 | 126.83 | 04-OCT-09:00 | 28.30 | 17.90 |
November | 0.105105E+11 | 6054.10 | 09-NOV-16:50 | 22.88 | 12.85 | 94300305.22 | 126.82 | 03-NOV-13:09 | 22.88 | 12.85 |
December | 0.145569E+11 | 7501.88 | 15-DEC-16:45 | 15.10 | 5.92 | 91880876.81 | 126.82 | 15-DEC-14:00 | 15.10 | 5.92 |
Annual Sum or Average | 0.119106E+12 | 0.114280E+10 | ||||||||
Minimum of Months | 0.104763E+10 | 2076.92 | 11.37 | 2.47 | 86396500.16 | 126.82 | 7.57 | 1.63 | ||
Maximum of Months | 0.190729E+11 | 8245.70 | 35.50 | 18.11 | 0.103240E+09 | 126.84 | 35.50 | 18.11 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238618E+12 | 104153.48 | 11-JAN-05:11 | 3.50 | -1.8 | 0.209089E+10 | 2863.16 | 03-JAN-14:09 | 3.50 | -1.8 |
February | 0.443791E+12 | 508440.28 | 27-FEB-01:02 | 10.40 | 8.17 | 0.153634E+10 | 2875.84 | 21-FEB-14:09 | 10.40 | 8.17 |
March | 0.729142E+12 | 546933.07 | 11-MAR-14:12 | 14.07 | 9.82 | 0.192856E+10 | 2869.03 | 06-MAR-14:00 | 14.07 | 9.82 |
April | 0.944867E+12 | 525279.09 | 06-APR-10:57 | 16.10 | 9.69 | 0.191023E+10 | 2859.86 | 20-APR-09:09 | 21.78 | 9.29 |
May | 0.241292E+12 | 176278.24 | 31-MAY-24:00 | 25.20 | 11.70 | 0.216980E+10 | 2878.96 | 03-MAY-09:09 | 25.20 | 11.70 |
June | 0.471751E+12 | 489341.52 | 11-JUN-03:42 | 17.98 | 6.42 | 0.213166E+10 | 2779.75 | 12-JUN-09:09 | 26.75 | 11.99 |
July | 0.733810E+12 | 434747.97 | 05-JUL-05:27 | 18.90 | 16.35 | 0.198634E+10 | 2754.35 | 17-JUL-09:09 | 23.48 | 20.08 |
August | 0.980755E+12 | 370623.09 | 23-AUG-16:00 | 33.30 | 16.20 | 0.223255E+10 | 2750.94 | 23-AUG-09:09 | 33.30 | 16.20 |
September | 0.239492E+12 | 494914.92 | 30-SEP-23:12 | 16.50 | 9.30 | 0.198491E+10 | 2835.45 | 11-SEP-09:09 | 16.50 | 9.30 |
October | 0.495644E+12 | 538505.43 | 31-OCT-23:01 | 10.60 | 4.63 | 0.189541E+10 | 2872.58 | 26-OCT-13:09 | 10.60 | 4.63 |
November | 0.711675E+12 | 542938.94 | 15-NOV-14:22 | 14.70 | 5.05 | 0.172198E+10 | 2853.83 | 08-NOV-14:09 | 14.70 | 5.05 |
December | 0.988065E+12 | 528038.76 | 13-DEC-13:07 | 12.98 | 6.73 | 0.160743E+10 | 2832.27 | 08-DEC-14:00 | 12.98 | 6.73 |
Annual Sum or Average | 0.721890E+13 | 0.231961E+11 | ||||||||
Minimum of Months | 0.238618E+12 | 104153.48 | 3.50 | -1.8 | 0.153634E+10 | 2750.94 | 3.50 | -1.8 | ||
Maximum of Months | 0.988065E+12 | 546933.07 | 33.30 | 16.35 | 0.223255E+10 | 2878.96 | 33.30 | 20.08 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 74562402.93 | 3965.62 | 14-JAN-06:13 | 8.90 |
February | 91776490.12 | 2971.23 | 03-FEB-06:03 | -3.7 |
March | 0.112994E+09 | 2998.45 | 03-MAR-06:03 | 7.62 |
April | 0.131444E+09 | 10339.12 | 29-APR-16:03 | 31.02 |
May | 0.141408E+09 | 12188.35 | 20-MAY-16:01 | 32.20 |
June | 0.150370E+09 | 16539.97 | 17-JUN-16:01 | 35.68 |
July | 0.158978E+09 | 19256.23 | 01-JUL-16:02 | 37.88 |
August | 0.142597E+09 | 14496.80 | 05-AUG-16:01 | 33.98 |
September | 90478971.11 | 11966.64 | 02-SEP-16:02 | 32.23 |
October | 46095268.87 | 4047.58 | 21-OCT-16:03 | 26.02 |
November | 67800879.21 | 3547.93 | 24-NOV-06:11 | 12.57 |
December | 63422064.90 | 3104.44 | 28-DEC-06:04 | -3.8 |
Annual Sum or Average | 0.127193E+10 | |||
Minimum of Months | 46095268.87 | 2971.23 | -3.8 | |
Maximum of Months | 0.158978E+09 | 19256.23 | 37.88 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121620E+10 | 84501.72 | 28-JAN-06:01 | -3.3 |
February | 0.241693E+09 | 84144.13 | 03-FEB-06:01 | -3.7 |
March | 70368886.52 | 84364.97 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:05 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 |
November | 0.681687E+09 | 83935.57 | 27-NOV-05:21 | 3.30 |
December | 0.157465E+10 | 88322.41 | 04-DEC-05:21 | -0.9 |
Annual Sum or Average | 0.378460E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.157465E+10 | 88322.41 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35077555.10 | 10020.73 | 28-JAN-06:01 | -3.3 |
February | 29682646.15 | 9740.68 | 02-FEB-06:01 | -3.5 |
March | 5527047.75 | 9749.57 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:05 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 |
November | 892050.64 | 8178.95 | 28-NOV-06:01 | 1.02 |
December | 21617821.99 | 9947.84 | 26-DEC-06:01 | -0.6 |
Annual Sum or Average | 92797121.63 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 35077555.10 | 10020.73 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35140810.19 | 7509.12 | 28-JAN-06:01 | -3.3 |
February | 25702656.00 | 7250.53 | 02-FEB-06:01 | -3.5 |
March | 6187064.32 | 7285.62 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:05 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 |
November | 3019924.12 | 6422.02 | 13-NOV-06:01 | 2.30 |
December | 43049828.85 | 7693.57 | 26-DEC-06:01 | -0.6 |
Annual Sum or Average | 0.113100E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 43049828.85 | 7693.57 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 77014386.89 | 12138.92 | 28-JAN-06:01 | -3.3 |
February | 57145685.27 | 11964.49 | 02-FEB-06:01 | -3.5 |
March | 14774611.70 | 12027.63 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:05 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 |
November | 13711461.16 | 10503.68 | 28-NOV-06:01 | 1.02 |
December | 86676699.04 | 12207.25 | 26-DEC-06:01 | -0.6 |
Annual Sum or Average | 0.249323E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 86676699.04 | 12207.25 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 380642.82 | 1614.86 | 27-JAN-06:03 | -3.1 |
February | 314417.74 | 1521.87 | 10-FEB-06:02 | -2.8 |
March | 118505.98 | 1300.54 | 01-MAR-06:03 | 1.60 |
April | 0.00 | 0.00 | 01-APR-00:05 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 813566.54 | |||
Minimum of Months | 0.00 | 0.00 | -3.1 | |
Maximum of Months | 380642.82 | 1614.86 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.761402E+09 | 16626.13 | 28-JAN-05:42 | -3.2 |
February | 0.456172E+09 | 16869.45 | 02-FEB-05:41 | -3.1 |
March | 0.223201E+09 | 16768.01 | 02-MAR-05:41 | -3.9 |
April | 8052136.05 | 11566.17 | 11-APR-05:01 | 4.90 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 17959.78 | 269.40 | 25-OCT-05:02 | 7.12 |
November | 0.286759E+09 | 16125.30 | 28-NOV-05:01 | -0.3 |
December | 0.891186E+09 | 16473.62 | 28-DEC-05:01 | -3.0 |
Annual Sum or Average | 0.262679E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.9 | |
Maximum of Months | 0.891186E+09 | 16869.45 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.418408E+09 | 13318.29 | 28-JAN-05:42 | -3.2 |
February | 0.220636E+09 | 13666.30 | 02-FEB-05:41 | -3.1 |
March | 0.114048E+09 | 13796.92 | 02-MAR-05:41 | -3.9 |
April | 5349880.26 | 8758.16 | 11-APR-05:01 | 4.90 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 443811.41 | 2114.50 | 25-OCT-05:01 | 7.12 |
November | 0.129390E+09 | 13232.53 | 28-NOV-05:01 | -0.3 |
December | 0.476634E+09 | 13353.38 | 27-DEC-05:01 | -3.8 |
Annual Sum or Average | 0.136491E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.9 | |
Maximum of Months | 0.476634E+09 | 13796.92 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.384591E+09 | 17067.61 | 28-JAN-05:42 | -3.2 |
February | 0.241776E+09 | 17375.60 | 02-FEB-05:41 | -3.1 |
March | 0.107752E+09 | 17593.64 | 02-MAR-05:41 | -3.9 |
April | 6880540.05 | 11861.48 | 11-APR-05:01 | 4.90 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 |
November | 0.107791E+09 | 16576.84 | 28-NOV-05:01 | -0.3 |
December | 0.456737E+09 | 17265.57 | 27-DEC-05:42 | -3.4 |
Annual Sum or Average | 0.130553E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.9 | |
Maximum of Months | 0.456737E+09 | 17593.64 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.340044E+09 | 13088.91 | 28-JAN-05:42 | -3.2 |
February | 0.207646E+09 | 13490.42 | 02-FEB-05:41 | -3.1 |
March | 66983974.07 | 13587.26 | 02-MAR-05:41 | -3.9 |
April | 3092932.80 | 8278.07 | 11-APR-05:01 | 4.90 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 81888.31 | 1228.32 | 25-OCT-05:03 | 7.12 |
November | 98337617.54 | 12766.54 | 28-NOV-05:01 | -0.3 |
December | 0.364109E+09 | 13034.97 | 27-DEC-05:01 | -3.8 |
Annual Sum or Average | 0.108030E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.9 | |
Maximum of Months | 0.364109E+09 | 13587.26 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288501E+10 | 23111.01 | 28-JAN-06:01 | -3.3 |
February | 0.191445E+10 | 24070.01 | 02-FEB-06:01 | -3.5 |
March | 0.124152E+10 | 24174.70 | 02-MAR-05:21 | -3.9 |
April | 0.162526E+09 | 18760.63 | 11-APR-04:11 | 5.40 |
May | 940341.38 | 3241.43 | 02-MAY-05:03 | 9.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 |
September | 3168004.78 | 5535.12 | 25-SEP-05:02 | 9.08 |
October | 0.121997E+09 | 16405.58 | 25-OCT-04:51 | 7.20 |
November | 0.159311E+10 | 23679.55 | 27-NOV-05:21 | 3.30 |
December | 0.359421E+10 | 24128.88 | 04-DEC-05:21 | -0.9 |
Annual Sum or Average | 0.115169E+11 | |||
Minimum of Months | 0.00 | 0.00 | -3.9 | |
Maximum of Months | 0.359421E+10 | 24174.70 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152240E+10 | 16893.33 | 28-JAN-06:01 | -3.3 |
February | 0.902727E+09 | 17649.83 | 02-FEB-06:01 | -3.5 |
March | 0.612706E+09 | 17733.21 | 02-MAR-06:01 | -3.5 |
April | 69992928.69 | 13536.66 | 11-APR-04:11 | 5.40 |
May | 686006.91 | 2469.49 | 02-MAY-05:03 | 9.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 |
September | 1434753.88 | 2743.37 | 25-SEP-05:02 | 9.08 |
October | 67680922.60 | 11728.13 | 25-OCT-04:51 | 7.20 |
November | 0.766871E+09 | 17309.27 | 27-NOV-05:21 | 3.30 |
December | 0.186697E+10 | 17664.62 | 04-DEC-04:01 | -0.1 |
Annual Sum or Average | 0.581148E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.186697E+10 | 17733.21 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179455E+10 | 22845.06 | 28-JAN-06:01 | -3.3 |
February | 0.121117E+10 | 23797.04 | 02-FEB-06:01 | -3.5 |
March | 0.903420E+09 | 23848.92 | 02-MAR-05:21 | -3.9 |
April | 0.143463E+09 | 18595.31 | 11-APR-04:11 | 5.40 |
May | 1696781.09 | 2991.70 | 02-MAY-05:03 | 9.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 |
September | 15068.87 | 150.69 | 25-SEP-05:03 | 9.08 |
October | 50576365.19 | 15630.02 | 25-OCT-05:01 | 7.12 |
November | 0.941717E+09 | 23441.48 | 27-NOV-05:21 | 3.30 |
December | 0.211447E+10 | 23721.19 | 04-DEC-05:21 | -0.9 |
Annual Sum or Average | 0.716109E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.9 | |
Maximum of Months | 0.211447E+10 | 23848.92 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126799E+10 | 17584.56 | 28-JAN-06:01 | -3.3 |
February | 0.851895E+09 | 18405.12 | 02-FEB-06:01 | -3.5 |
March | 0.497502E+09 | 18452.62 | 02-MAR-06:01 | -3.5 |
April | 58410149.12 | 13846.18 | 11-APR-04:11 | 5.40 |
May | 66691.17 | 444.61 | 02-MAY-05:05 | 9.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 |
September | 87162.02 | 871.62 | 25-SEP-05:05 | 9.08 |
October | 20666067.06 | 11455.95 | 25-OCT-05:01 | 7.12 |
November | 0.614444E+09 | 17905.32 | 27-NOV-05:21 | 3.30 |
December | 0.142942E+10 | 17991.72 | 04-DEC-04:01 | -0.1 |
Annual Sum or Average | 0.474048E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.142942E+10 | 18452.62 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33371020.59 | 9469.35 | 17-JAN-05:11 | 5.20 |
February | 39232986.80 | 9466.27 | 27-FEB-05:11 | 8.90 |
March | 44389446.99 | 9975.07 | 23-MAR-04:11 | 8.13 |
April | 81574100.18 | 11420.81 | 05-APR-04:11 | 16.67 |
May | 50287912.96 | 8816.37 | 09-MAY-04:11 | 22.60 |
June | 72761871.69 | 9003.20 | 27-JUN-04:11 | 21.50 |
July | 0.113527E+09 | 10618.24 | 21-JUL-04:11 | 20.60 |
August | 0.121973E+09 | 11135.02 | 15-AUG-04:11 | 19.40 |
September | 51645369.80 | 10006.78 | 01-SEP-04:11 | 20.53 |
October | 63687304.39 | 10326.73 | 08-OCT-15:32 | 26.30 |
November | 50249699.49 | 11613.43 | 10-NOV-05:11 | 17.47 |
December | 46615889.99 | 11882.21 | 18-DEC-05:11 | 4.03 |
Annual Sum or Average | 0.769315E+09 | |||
Minimum of Months | 33371020.59 | 8816.37 | 4.03 | |
Maximum of Months | 0.121973E+09 | 11882.21 | 26.30 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241692E+09 | 7273.33 | 01-JAN-14:43 | 16.02 |
February | 39651062.89 | 8223.98 | 19-FEB-10:33 | 17.77 |
March | 19942992.89 | 7353.68 | 07-MAR-06:01 | 12.20 |
April | 29532664.34 | 6726.53 | 20-APR-04:12 | 20.00 |
May | 35778328.87 | 6997.07 | 04-MAY-04:12 | 16.83 |
June | 37336349.68 | 7151.00 | 07-JUN-03:01 | 25.40 |
July | 42155412.34 | 7850.28 | 26-JUL-03:01 | 27.52 |
August | 39516200.76 | 7668.04 | 24-AUG-03:01 | 26.02 |
September | 34505382.54 | 7827.44 | 10-SEP-15:51 | 31.10 |
October | 46117443.80 | 8416.51 | 01-OCT-15:11 | 32.43 |
November | 56157782.99 | 7721.32 | 10-NOV-05:11 | 17.47 |
December | 0.183777E+09 | 6299.30 | 31-DEC-14:32 | 14.03 |
Annual Sum or Average | 0.806162E+09 | |||
Minimum of Months | 19942992.89 | 6299.30 | 12.20 | |
Maximum of Months | 0.241692E+09 | 8416.51 | 32.43 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.641401E+10 | 31292.04 | 09-JAN-06:01 | 2.98 |
February | 0.459094E+10 | 31413.47 | 03-FEB-06:01 | -3.7 |
March | 0.363884E+10 | 30275.85 | 02-MAR-06:01 | -3.5 |
April | 0.115941E+10 | 32521.05 | 04-APR-05:01 | 13.35 |
May | 0.354611E+09 | 31496.89 | 12-MAY-05:01 | 14.03 |
June | 0.145878E+09 | 29196.54 | 12-JUN-05:01 | 16.28 |
July | 93252237.87 | 24392.22 | 05-JUL-04:11 | 19.27 |
August | 0.114046E+09 | 22498.15 | 26-AUG-05:02 | 19.78 |
September | 0.400934E+09 | 29934.66 | 12-SEP-05:01 | 15.13 |
October | 0.121986E+10 | 29122.31 | 18-OCT-05:01 | 14.32 |
November | 0.402283E+10 | 31500.94 | 27-NOV-05:25 | 3.30 |
December | 0.821758E+10 | 34581.10 | 04-DEC-06:04 | -1.0 |
Annual Sum or Average | 0.303722E+11 | |||
Minimum of Months | 93252237.87 | 22498.15 | -3.7 | |
Maximum of Months | 0.821758E+10 | 34581.10 | 19.78 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.953854E+09 | 1436.62 | 09-JAN-03:35 | 0.57 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 0.953854E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.57 | |
Maximum of Months | 0.953854E+09 | 1436.62 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.270095E+10 | 29171.09 | 27-FEB-04:11 | 8.90 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
June | 62570407.42 | 19907.48 | 13-JUN-05:01 | 15.18 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 27.32 |
September | 996746.02 | 5358.71 | 30-SEP-23:04 | 16.60 |
October | 0.473516E+09 | 29176.57 | 29-OCT-04:41 | 13.07 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 0.323803E+10 | |||
Minimum of Months | 0.00 | 0.00 | 6.70 | |
Maximum of Months | 0.270095E+10 | 29176.57 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.278508E+11 | 29144.79 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.252627E+11 | 29144.79 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.300191E+11 | 29144.79 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.268132E+11 | 29144.79 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.289349E+11 | 29144.79 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.287951E+11 | 29144.79 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.269531E+11 | 29144.79 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.300191E+11 | 29144.79 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.268132E+11 | 29144.79 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.278508E+11 | 29144.79 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.275243E+11 | 29144.79 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.269531E+11 | 29144.79 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.333789E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.252627E+11 | 29144.79 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.300191E+11 | 29144.79 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.250119E+11 | 26174.07 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.226877E+11 | 26174.07 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.269593E+11 | 26174.07 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.240801E+11 | 26174.07 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.259856E+11 | 26174.07 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.258600E+11 | 26174.07 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.242058E+11 | 26174.07 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.269593E+11 | 26174.07 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.240801E+11 | 26174.07 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.250119E+11 | 26174.07 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.247188E+11 | 26174.07 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.242058E+11 | 26174.07 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.299766E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.226877E+11 | 26174.07 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.269593E+11 | 26174.07 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314050E+10 | 3286.42 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.284867E+10 | 3286.42 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.338501E+10 | 3286.42 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.302350E+10 | 3286.42 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.326275E+10 | 3286.42 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.324698E+10 | 3286.42 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.303928E+10 | 3286.42 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.338501E+10 | 3286.42 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.302350E+10 | 3286.42 | 01-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.314050E+10 | 3286.42 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.310369E+10 | 3286.42 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.303928E+10 | 3286.42 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.376387E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.284867E+10 | 3286.42 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.338501E+10 | 3286.42 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.314057E+10 | 3286.49 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.284873E+10 | 3286.49 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.338508E+10 | 3286.49 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.302357E+10 | 3286.49 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.326282E+10 | 3286.49 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.324705E+10 | 3286.49 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.303934E+10 | 3286.49 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.338508E+10 | 3286.49 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.302357E+10 | 3286.49 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.314057E+10 | 3286.49 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.310376E+10 | 3286.49 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.303934E+10 | 3286.49 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.376395E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.284873E+10 | 3286.49 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.338508E+10 | 3286.49 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.202386E+10 | 2117.89 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.183579E+10 | 2117.89 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.218143E+10 | 2117.89 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.194846E+10 | 2117.89 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.210264E+10 | 2117.89 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.209248E+10 | 2117.89 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.195863E+10 | 2117.89 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.218143E+10 | 2117.89 | 01-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.194846E+10 | 2117.89 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.202386E+10 | 2117.89 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.200014E+10 | 2117.89 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.195863E+10 | 2117.89 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.242558E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.183579E+10 | 2117.89 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.218143E+10 | 2117.89 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.696426E+09 | 728.78 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.631710E+09 | 728.78 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.750648E+09 | 728.78 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.670482E+09 | 728.78 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.723537E+09 | 728.78 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.720039E+09 | 728.78 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.673980E+09 | 728.78 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.750648E+09 | 728.78 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.670482E+09 | 728.78 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.696426E+09 | 728.78 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.688264E+09 | 728.78 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.673980E+09 | 728.78 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.834662E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.631710E+09 | 728.78 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.750648E+09 | 728.78 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.785272E+10 | 8217.58 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.712300E+10 | 8217.58 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.846411E+10 | 8217.58 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.756018E+10 | 8217.58 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.815842E+10 | 8217.58 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.811897E+10 | 8217.58 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.759962E+10 | 8217.58 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.846411E+10 | 8217.58 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.756018E+10 | 8217.58 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.785272E+10 | 8217.58 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.776069E+10 | 8217.58 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.759962E+10 | 8217.58 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.941143E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.712300E+10 | 8217.58 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.846411E+10 | 8217.58 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.289349E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.287951E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.268132E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.278508E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.275243E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.269531E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.333789E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.252627E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.300191E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.250119E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.240801E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.259856E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.258600E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.242058E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.240801E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.250119E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.247188E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.242058E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.299766E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.226877E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.269593E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499783E+09 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42818.64 | 0.414938E+09 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 160101.62 | 0.431486E+09 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27463839.57 | 0.229219E+09 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76772396.69 | 0.127193E+09 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119513E+09 | 40603166.06 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102934E+09 | 25463709.09 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82632433.40 | 37860690.21 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26260905.96 | 62538984.12 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10176058.23 | 0.205596E+09 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405590E+09 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441237E+09 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445955E+09 | 0.292151E+10 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25463709.09 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119513E+09 | 0.499783E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332170E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28059.27 | 0.275388E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 122246.71 | 0.287032E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20605198.96 | 0.146473E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54202905.70 | 83282205.00 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86123865.18 | 24153111.40 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76824402.05 | 13246838.16 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61144098.62 | 20243817.29 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17992449.08 | 41408419.00 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7411639.29 | 0.134576E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269038E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289758E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324455E+09 | 0.191677E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13246838.16 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86123865.18 | 0.332170E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515380E+09 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428145E+09 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140600.84 | 0.447778E+09 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23950394.28 | 0.228406E+09 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77396689.39 | 0.122439E+09 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123086E+09 | 38743594.05 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106102E+09 | 23590241.35 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81773674.18 | 36605919.15 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22485822.51 | 65468433.47 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7516628.54 | 0.217157E+09 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420805E+09 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450686E+09 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442451E+09 | 0.299520E+10 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23590241.35 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123086E+09 | 0.515380E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353084E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294677E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93800.13 | 0.321092E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13547663.04 | 0.183852E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46527465.92 | 99228283.66 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75370694.89 | 34848431.09 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63257292.01 | 24259459.19 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49073349.46 | 34309113.16 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16200048.25 | 49159784.60 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5493777.96 | 0.154090E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295867E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323280E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269564E+09 | 0.216775E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24259459.19 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75370694.89 | 0.353084E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102723E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1634393.23 | 0.866648E+09 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1691113.53 | 0.894615E+09 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68665696.47 | 0.480543E+09 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178876E+09 | 0.270340E+09 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261205E+09 | 98342359.24 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221494E+09 | 74296670.94 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178112E+09 | 99742117.72 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64354854.96 | 0.132450E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27811434.10 | 0.419596E+09 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 770.86 | 0.816422E+09 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897915E+09 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100385E+10 | 0.607814E+10 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74296670.94 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261205E+09 | 0.102723E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706322E+09 |
February | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 340770.81 | 0.597852E+09 |
March | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 276410.23 | 0.632813E+09 |
April | 0.688021E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42623649.92 | 0.336041E+09 |
May | 0.744847E+09 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119577E+09 | 0.185054E+09 |
June | 0.742030E+09 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177544E+09 | 64662741.48 |
July | 0.690839E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150972E+09 | 49023594.23 |
August | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118730E+09 | 66574151.27 |
September | 0.688021E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40747456.30 | 93369220.69 |
October | 0.715730E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16595876.31 | 0.290350E+09 |
November | 0.708685E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 646.69 | 0.570213E+09 |
December | 0.690839E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617486E+09 |
Annual Sum or Average | 0.858171E+10 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667407E+09 | 0.420976E+10 |
Minimum of Months | 0.649041E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49023594.23 |
Maximum of Months | 0.773965E+09 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177544E+09 | 0.706322E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116158E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970511E+09 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 260673.88 | 0.101096E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52462067.25 | 0.509224E+09 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177538E+09 | 0.266948E+09 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268820E+09 | 94460677.96 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227163E+09 | 70963436.88 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172411E+09 | 0.101677E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50893664.11 | 0.148564E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15072820.94 | 0.489113E+09 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.942729E+09 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101051E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.964621E+09 | 0.677724E+10 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70963436.88 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268820E+09 | 0.116158E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719437E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6322.33 | 0.610105E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 465299.39 | 0.650656E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35349126.66 | 0.355988E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107150E+09 | 0.196756E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168393E+09 | 74882222.30 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142611E+09 | 59773283.01 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110632E+09 | 75733776.87 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39351200.14 | 99226154.36 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13514246.57 | 0.305153E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581792E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631921E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617472E+09 | 0.436142E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59773283.01 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168393E+09 | 0.719437E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.314050E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112343E+10 |
February | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4517557.74 | 0.961634E+09 |
March | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3314687.61 | 0.998890E+09 |
April | 0.145243E+10 | 0.302350E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85043878.81 | 0.543818E+09 |
May | 0.157338E+10 | 0.326275E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216867E+09 | 0.306804E+09 |
June | 0.156900E+10 | 0.324698E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319099E+09 | 0.119036E+09 |
July | 0.145680E+10 | 0.303928E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270608E+09 | 91292070.39 |
August | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219345E+09 | 0.116148E+09 |
September | 0.145243E+10 | 0.302350E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79644943.33 | 0.151673E+09 |
October | 0.150991E+10 | 0.314050E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37134703.33 | 0.461250E+09 |
November | 0.149516E+10 | 0.310369E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 162701.01 | 0.872288E+09 |
December | 0.145680E+10 | 0.303928E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987187E+09 |
Annual Sum or Average | 0.181194E+11 | 0.376387E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123574E+10 | 0.673345E+10 |
Minimum of Months | 0.136985E+10 | 0.284867E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91292070.39 |
Maximum of Months | 0.163685E+10 | 0.338501E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319099E+09 | 0.112343E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769238E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 654308.14 | 0.663409E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 346838.78 | 0.718630E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49655990.60 | 0.392785E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139802E+09 | 0.219074E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210906E+09 | 81011815.56 |
July | 0.938820E+09 | 0.195863E+10 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177981E+09 | 62928594.07 |
August | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141864E+09 | 80625341.07 |
September | 0.936002E+09 | 0.194846E+10 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47658686.38 | 0.111625E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19679342.62 | 0.330484E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.93 | 0.615777E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674196E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788549E+09 | 0.471978E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62928594.07 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210906E+09 | 0.769238E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.314057E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128930E+10 |
February | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109267E+10 |
March | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 247001.91 | 0.115013E+10 |
April | 0.145246E+10 | 0.302357E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63458599.60 | 0.586563E+09 |
May | 0.157341E+10 | 0.326282E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210878E+09 | 0.307835E+09 |
June | 0.156904E+10 | 0.324705E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323186E+09 | 0.116119E+09 |
July | 0.145684E+10 | 0.303934E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271865E+09 | 89176524.85 |
August | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209360E+09 | 0.120668E+09 |
September | 0.145246E+10 | 0.302357E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61817984.59 | 0.173733E+09 |
October | 0.150994E+10 | 0.314057E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18357567.74 | 0.556635E+09 |
November | 0.149520E+10 | 0.310376E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103428E+10 |
December | 0.145684E+10 | 0.303934E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111925E+10 |
Annual Sum or Average | 0.181198E+11 | 0.376395E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115917E+10 | 0.763636E+10 |
Minimum of Months | 0.136988E+10 | 0.284873E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89176524.85 |
Maximum of Months | 0.163688E+10 | 0.338508E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323186E+09 | 0.128930E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.202386E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817192E+09 |
February | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36813.78 | 0.699090E+09 |
March | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 518673.40 | 0.753133E+09 |
April | 0.936002E+09 | 0.194846E+10 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42858045.62 | 0.415398E+09 |
May | 0.101394E+10 | 0.210264E+10 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129386E+09 | 0.230057E+09 |
June | 0.101113E+10 | 0.209248E+10 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205398E+09 | 91424249.11 |
July | 0.938820E+09 | 0.195863E+10 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174724E+09 | 73839216.88 |
August | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136185E+09 | 89751763.43 |
September | 0.936002E+09 | 0.194846E+10 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47932322.51 | 0.117159E+09 |
October | 0.973041E+09 | 0.202386E+10 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16632348.93 | 0.352251E+09 |
November | 0.963541E+09 | 0.200014E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649078E+09 |
December | 0.938820E+09 | 0.195863E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713441E+09 |
Annual Sum or Average | 0.116768E+11 | 0.242558E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753671E+09 | 0.500181E+10 |
Minimum of Months | 0.882782E+09 | 0.183579E+10 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73839216.88 |
Maximum of Months | 0.105485E+10 | 0.218143E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205398E+09 | 0.817192E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.696426E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.631710E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.750648E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.670482E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.723537E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.720039E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.673980E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.750648E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.670482E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.696426E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.688264E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.673980E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.834662E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.631710E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.750648E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.785272E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.712300E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.846411E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.756018E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.815842E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.811897E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.759962E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.846411E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.756018E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.785272E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.776069E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.759962E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.941143E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.712300E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.846411E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113266E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.944753E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52944.54 | 0.985354E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40961724.11 | 0.521630E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135187E+09 | 0.280721E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217100E+09 | 91253100.32 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184785E+09 | 63275845.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143957E+09 | 94432018.96 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42614876.25 | 0.140261E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15469299.04 | 0.468004E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925893E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.999188E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.780128E+09 | 0.664742E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63275845.86 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217100E+09 | 0.113266E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192377E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162737E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141185.81 | 0.169175E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82904404.52 | 0.892787E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251383E+09 | 0.483826E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387174E+09 | 0.164022E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331463E+09 | 0.117512E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258291E+09 | 0.171825E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80713018.86 | 0.241345E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30409742.07 | 0.794958E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157572E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168879E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142248E+10 | 0.113737E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117512E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387174E+09 | 0.192377E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177638E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152404E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167102E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46408429.63 | 0.877089E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195896E+09 | 0.444190E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368072E+09 | 0.152617E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297145E+09 | 0.117803E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235941E+09 | 0.161891E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52104836.71 | 0.233720E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23513644.72 | 0.759461E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140708E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152223E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121908E+10 | 0.106475E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117803E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368072E+09 | 0.177638E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 29144.79 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 29144.79 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 29144.79 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 29144.79 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 29144.79 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 29144.79 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 29144.79 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 29144.79 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 29144.79 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 29144.79 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 29144.79 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 29144.79 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 29144.79 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 26174.07 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 26174.07 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 26174.07 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 26174.07 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 26174.07 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 26174.07 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 26174.07 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 26174.07 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 26174.07 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 26174.07 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 26174.07 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 26174.07 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1346.00 | 25-JAN-23:00 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.43 | 20-FEB-16:00 | 1639.06 | 09-FEB-00:51 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.27 | 19-MAR-14:50 | 1277.48 | 19-MAR-23:51 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.00 | 01-APR-17:01 | 1338.83 | 10-APR-23:52 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 498.26 | 14-MAY-15:50 | 632.65 | 04-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 477.14 | 04-JUN-19:00 | 448.27 | 28-JUN-01:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 552.73 | 02-JUL-21:10 | 231.73 | 18-JUL-21:10 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.54 | 26-AUG-17:50 | 361.60 | 14-AUG-01:00 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.05 | 10-SEP-15:00 | 231.10 | 24-SEP-07:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 277.40 | 01-OCT-15:00 | 606.81 | 24-OCT-01:51 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 838.41 | 26-NOV-13:51 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1128.96 | 18-DEC-05:02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.10 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 552.73 | 1639.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 878.80 | 25-JAN-23:00 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.03 | 20-FEB-16:00 | 1079.98 | 09-FEB-00:51 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.09 | 19-MAR-14:50 | 855.20 | 19-MAR-23:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.69 | 01-APR-17:50 | 867.68 | 10-APR-23:52 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.27 | 14-MAY-15:50 | 401.12 | 04-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.64 | 04-JUN-19:00 | 285.77 | 28-JUN-01:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 417.49 | 02-JUL-21:10 | 136.96 | 18-JUL-21:10 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 266.26 | 26-AUG-17:50 | 223.54 | 14-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.11 | 10-SEP-17:00 | 181.90 | 24-SEP-10:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.14 | 01-OCT-15:00 | 397.63 | 24-OCT-01:51 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 645.31 | 26-NOV-08:51 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 739.08 | 18-DEC-05:02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.96 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 417.49 | 1079.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1323.17 | 25-JAN-23:00 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1626.90 | 09-FEB-00:51 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 22-MAR-13:00 | 1295.38 | 19-MAR-23:51 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.01 | 01-APR-17:50 | 1316.03 | 10-APR-23:52 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 496.83 | 14-MAY-15:50 | 612.21 | 04-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 498.57 | 04-JUN-19:00 | 445.85 | 28-JUN-01:51 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 572.68 | 02-JUL-21:10 | 228.67 | 18-JUL-21:10 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 345.84 | 26-AUG-17:50 | 370.13 | 14-AUG-01:00 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.83 | 10-SEP-17:00 | 260.29 | 24-SEP-10:45 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.68 | 01-OCT-15:00 | 607.60 | 24-OCT-01:51 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 911.66 | 26-NOV-08:51 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1095.01 | 18-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.67 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 572.68 | 1626.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 934.59 | 25-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1139.24 | 09-FEB-00:51 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.34 | 22-MAR-13:00 | 950.93 | 19-MAR-23:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.06 | 21-APR-15:00 | 984.21 | 10-APR-23:52 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.83 | 14-MAY-15:44 | 481.89 | 04-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.30 | 04-JUN-19:00 | 349.85 | 28-JUN-01:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.50 | 02-JUL-21:30 | 186.15 | 18-JUL-21:10 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.88 | 27-AUG-13:00 | 297.90 | 14-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.21 | 10-SEP-12:20 | 183.87 | 24-SEP-16:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.59 | 01-OCT-14:55 | 438.64 | 24-OCT-01:51 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 622.25 | 26-NOV-16:51 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 832.56 | 18-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.87 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 378.50 | 1139.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2795.87 | 25-JAN-23:00 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.98 | 20-FEB-16:00 | 3420.79 | 09-FEB-00:51 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.55 | 19-MAR-15:00 | 2434.77 | 19-MAR-23:51 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 668.98 | 02-APR-13:55 | 2744.91 | 10-APR-23:52 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1131.87 | 14-MAY-16:00 | 1259.95 | 04-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1061.40 | 04-JUN-19:00 | 1007.81 | 28-JUN-01:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1268.18 | 02-JUL-21:10 | 506.18 | 18-JUL-21:10 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 797.41 | 26-AUG-17:50 | 795.94 | 14-AUG-00:02 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 494.89 | 10-SEP-14:53 | 480.01 | 24-SEP-10:00 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 687.08 | 01-OCT-15:00 | 1253.84 | 24-OCT-01:51 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.44 | 23-NOV-15:20 | 1601.68 | 26-NOV-09:00 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2454.45 | 18-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.01 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1268.18 | 3420.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1858.77 | 25-JAN-23:00 |
February | 1239.33 | 01-FEB-08:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.60 | 20-FEB-16:00 | 2284.21 | 09-FEB-00:51 |
March | 1239.33 | 01-MAR-08:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.05 | 19-MAR-15:00 | 1716.34 | 19-MAR-23:51 |
April | 1239.33 | 03-APR-07:10 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 449.06 | 01-APR-17:50 | 1820.44 | 10-APR-23:52 |
May | 1239.33 | 01-MAY-07:10 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 836.95 | 14-MAY-16:00 | 812.43 | 04-MAY-02:00 |
June | 1239.33 | 01-JUN-07:10 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 816.82 | 04-JUN-19:00 | 666.57 | 28-JUN-01:51 |
July | 1239.33 | 03-JUL-07:10 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 985.62 | 02-JUL-21:10 | 311.84 | 18-JUL-21:10 |
August | 1239.33 | 01-AUG-07:10 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 594.65 | 26-AUG-17:50 | 536.89 | 14-AUG-00:02 |
September | 1239.33 | 01-SEP-07:10 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 363.93 | 10-SEP-15:20 | 438.32 | 24-SEP-10:20 |
October | 1239.33 | 02-OCT-07:10 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 440.66 | 01-OCT-15:00 | 835.06 | 24-OCT-01:51 |
November | 1239.33 | 01-NOV-07:10 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 | 03-NOV-16:00 | 1279.19 | 26-NOV-08:51 |
December | 1239.33 | 01-DEC-08:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1636.32 | 18-DEC-05:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.84 | |||||
Maximum of Months | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 985.62 | 2284.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2845.98 | 25-JAN-23:00 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3513.10 | 09-FEB-00:51 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.13 | 22-MAR-13:00 | 2729.05 | 19-MAR-23:51 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 542.19 | 01-APR-17:01 | 2777.07 | 10-APR-23:52 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1111.52 | 14-MAY-16:00 | 1260.03 | 04-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1122.44 | 04-JUN-19:00 | 998.53 | 28-JUN-01:51 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.03 | 02-JUL-21:10 | 500.79 | 18-JUL-21:10 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 797.36 | 26-AUG-17:50 | 828.29 | 14-AUG-00:02 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 395.41 | 10-SEP-16:40 | 576.30 | 24-SEP-10:20 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 482.95 | 01-OCT-15:00 | 1341.55 | 23-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1937.76 | 26-NOV-08:51 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2460.45 | 18-DEC-05:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.79 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.03 | 3513.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1868.40 | 25-JAN-23:00 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.26 | 20-FEB-12:00 | 2314.08 | 09-FEB-00:51 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.16 | 19-MAR-12:20 | 1791.65 | 19-MAR-23:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.73 | 02-APR-13:21 | 1867.06 | 10-APR-23:52 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 624.11 | 14-MAY-15:53 | 871.42 | 04-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 751.61 | 04-JUN-19:00 | 720.91 | 28-JUN-01:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 942.15 | 02-JUL-21:10 | 405.02 | 04-JUL-19:05 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 544.89 | 27-AUG-12:55 | 603.66 | 14-AUG-00:02 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.71 | 10-SEP-12:00 | 361.23 | 24-SEP-15:50 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.04 | 01-OCT-14:55 | 874.05 | 24-OCT-01:51 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1178.68 | 26-NOV-16:51 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1636.37 | 18-DEC-05:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.23 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 942.15 | 2314.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 3286.42 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3293.10 | 25-JAN-22:03 |
February | 2010.79 | 01-FEB-10:09 | 3286.42 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 268.75 | 20-FEB-15:50 | 3803.31 | 08-FEB-22:01 |
March | 2010.79 | 01-MAR-10:09 | 3286.42 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 299.18 | 19-MAR-14:50 | 2880.57 | 01-MAR-22:01 |
April | 2010.79 | 03-APR-09:09 | 3286.42 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 832.88 | 01-APR-17:01 | 3072.91 | 10-APR-23:52 |
May | 2010.79 | 01-MAY-09:09 | 3286.42 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1353.67 | 14-MAY-15:40 | 1365.49 | 04-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 3286.42 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1216.86 | 04-JUN-18:52 | 1241.37 | 28-JUN-01:51 |
July | 2010.79 | 03-JUL-09:09 | 3286.42 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1576.94 | 02-JUL-21:10 | 617.78 | 18-JUL-21:10 |
August | 2010.79 | 01-AUG-09:09 | 3286.42 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1002.61 | 26-AUG-17:50 | 1018.94 | 14-AUG-00:12 |
September | 2010.79 | 01-SEP-09:09 | 3286.42 | 01-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 593.29 | 10-SEP-16:50 | 587.50 | 23-SEP-17:10 |
October | 2010.79 | 02-OCT-09:09 | 3286.42 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 861.21 | 01-OCT-15:00 | 1452.52 | 23-OCT-21:10 |
November | 2010.79 | 01-NOV-09:09 | 3286.42 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.07 | 23-NOV-15:10 | 1840.45 | 28-NOV-05:07 |
December | 2010.79 | 01-DEC-10:09 | 3286.42 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3060.30 | 18-DEC-05:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.50 | |||||
Maximum of Months | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1576.94 | 3803.31 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2193.51 | 25-JAN-22:03 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 119.92 | 20-FEB-15:50 | 2543.28 | 09-FEB-00:51 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 80.49 | 19-MAR-14:50 | 1920.33 | 01-MAR-22:01 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 541.20 | 01-APR-17:50 | 2052.00 | 10-APR-23:52 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 948.57 | 14-MAY-15:40 | 888.45 | 04-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 856.09 | 10-JUN-17:50 | 820.93 | 28-JUN-01:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1142.04 | 02-JUL-21:10 | 405.93 | 04-JUL-19:30 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 704.65 | 26-AUG-17:50 | 691.57 | 14-AUG-00:12 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 431.01 | 10-SEP-16:50 | 506.85 | 24-SEP-10:30 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 520.36 | 01-OCT-15:00 | 979.88 | 23-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.09 | 23-NOV-15:10 | 1252.67 | 26-NOV-08:51 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2040.34 | 18-DEC-05:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.93 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1142.04 | 2543.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 3286.49 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3297.96 | 25-JAN-22:03 |
February | 2010.83 | 01-FEB-10:09 | 3286.49 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3930.45 | 09-FEB-00:51 |
March | 2010.83 | 01-MAR-10:09 | 3286.49 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.50 | 22-MAR-13:00 | 3012.08 | 19-MAR-19:51 |
April | 2010.83 | 03-APR-09:09 | 3286.49 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 694.12 | 01-APR-17:50 | 3117.44 | 10-APR-23:52 |
May | 2010.83 | 01-MAY-09:09 | 3286.49 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1300.90 | 14-MAY-15:40 | 1374.80 | 04-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 3286.49 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1241.03 | 04-JUN-18:52 | 1229.47 | 28-JUN-01:51 |
July | 2010.83 | 03-JUL-09:09 | 3286.49 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1602.15 | 02-JUL-21:10 | 620.65 | 18-JUL-21:10 |
August | 2010.83 | 01-AUG-09:09 | 3286.49 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 978.00 | 26-AUG-17:50 | 1061.68 | 14-AUG-00:12 |
September | 2010.83 | 01-SEP-09:09 | 3286.49 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 513.02 | 10-SEP-16:50 | 715.27 | 24-SEP-11:00 |
October | 2010.83 | 02-OCT-09:09 | 3286.49 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 588.71 | 01-OCT-15:00 | 1560.74 | 23-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 3286.49 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1908.32 | 26-NOV-09:00 |
December | 2010.83 | 01-DEC-10:09 | 3286.49 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3060.44 | 18-DEC-05:45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.65 | |||||
Maximum of Months | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1602.15 | 3930.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 2117.89 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2199.19 | 25-JAN-22:03 |
February | 1295.83 | 01-FEB-10:09 | 2117.89 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.51 | 20-FEB-12:30 | 2613.30 | 09-FEB-00:51 |
March | 1295.83 | 01-MAR-10:09 | 2117.89 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 64.69 | 19-MAR-13:30 | 2017.71 | 19-MAR-19:51 |
April | 1295.83 | 03-APR-09:09 | 2117.89 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 380.27 | 29-APR-17:02 | 2114.85 | 10-APR-23:52 |
May | 1295.83 | 01-MAY-09:09 | 2117.89 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 786.40 | 14-MAY-15:33 | 964.44 | 04-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 2117.89 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 746.55 | 11-JUN-12:52 | 884.03 | 28-JUN-01:51 |
July | 1295.83 | 03-JUL-09:09 | 2117.89 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1153.27 | 02-JUL-21:10 | 554.36 | 04-JUL-19:10 |
August | 1295.83 | 01-AUG-09:09 | 2117.89 | 01-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 655.42 | 27-AUG-12:50 | 747.43 | 14-AUG-00:12 |
September | 1295.83 | 01-SEP-09:09 | 2117.89 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.48 | 10-SEP-12:10 | 500.64 | 24-SEP-16:00 |
October | 1295.83 | 02-OCT-09:09 | 2117.89 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 403.32 | 01-OCT-14:55 | 1029.31 | 23-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 2117.89 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1231.31 | 26-NOV-16:51 |
December | 1295.83 | 01-DEC-10:09 | 2117.89 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2040.22 | 18-DEC-05:45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.64 | |||||
Maximum of Months | 1295.83 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1153.27 | 2613.30 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 728.78 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 728.78 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 728.78 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 728.78 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 728.78 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 728.78 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 728.78 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 728.78 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 728.78 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 728.78 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 728.78 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 728.78 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 728.78 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 728.78 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 8217.58 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 8217.58 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 8217.58 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 8217.58 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 8217.58 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 8217.58 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 8217.58 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 8217.58 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 8217.58 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 8217.58 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 8217.58 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 8217.58 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 8217.58 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 8217.58 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3041.94 | 25-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3757.52 | 09-FEB-00:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.86 | 22-MAR-13:00 | 2932.20 | 19-MAR-23:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.78 | 01-APR-17:01 | 3013.84 | 10-APR-23:52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 927.38 | 14-MAY-16:00 | 1385.23 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 856.83 | 04-JUN-19:00 | 982.61 | 28-JUN-01:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1067.27 | 02-JUL-21:00 | 481.42 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 636.09 | 26-AUG-17:30 | 765.69 | 14-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.43 | 10-SEP-15:00 | 502.74 | 24-SEP-07:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.88 | 01-OCT-15:00 | 1365.77 | 24-OCT-01:51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1880.59 | 26-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2587.72 | 18-DEC-05:13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.42 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1067.27 | 3757.52 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5216.16 | 25-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 6555.62 | 09-FEB-00:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.61 | 22-MAR-13:00 | 4902.06 | 19-MAR-23:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 864.16 | 01-APR-17:01 | 5194.34 | 10-APR-23:52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1707.18 | 14-MAY-16:00 | 2359.63 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1580.20 | 04-JUN-19:00 | 1745.72 | 28-JUN-01:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1977.18 | 02-JUL-20:52 | 856.30 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1174.24 | 27-AUG-13:00 | 1325.61 | 14-AUG-00:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 716.02 | 10-SEP-15:00 | 873.59 | 24-SEP-07:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 922.64 | 01-OCT-15:00 | 2362.89 | 24-OCT-01:51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 3154.40 | 26-NOV-08:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 4218.84 | 18-DEC-05:02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 856.30 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1977.18 | 6555.62 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4947.71 | 25-JAN-23:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 5957.17 | 09-FEB-00:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 4129.10 | 19-MAR-19:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 742.08 | 19-APR-21:02 | 4650.13 | 10-APR-23:52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1273.19 | 19-MAY-21:52 | 1995.15 | 04-MAY-02:70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.69 | 04-JUN-18:52 | 1899.58 | 28-JUN-01:51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2088.66 | 02-JUL-21:20 | 963.31 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1124.65 | 26-AUG-18:00 | 1582.73 | 14-AUG-00:12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.65 | 10-SEP-16:50 | 1148.53 | 24-SEP-11:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 732.07 | 01-OCT-15:00 | 2295.03 | 23-OCT-21:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2769.15 | 26-NOV-13:51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3720.51 | 18-DEC-05:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 963.31 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2088.66 | 5957.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 151912.04 | 17-JAN-05:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 150175.41 | 21-FEB-05:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 148197.63 | 27-MAR-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 126310.89 | 17-APR-04:12 | 0.00 | 19429.86 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 135273.12 | 01-MAY-04:11 | 0.00 | 22668.17 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 144889.09 | 12-JUN-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 121215.84 | 25-JUL-05:02 | 8976.13 | 16191.55 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 131387.87 | 24-AUG-03:01 | 0.00 | 11334.08 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 141720.95 | 25-SEP-04:22 | 0.00 | 19429.86 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 149213.60 | 11-OCT-04:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 154735.47 | 06-NOV-05:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 130410.57 | 11-DEC-05:11 | 0.00 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 121215.84 | 0.00 | 11334.08 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 154735.47 | 8976.13 | 32383.10 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 112915.39 | 02-JAN-05:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 108879.69 | 21-FEB-05:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 111520.22 | 10-MAR-05:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 115445.49 | 06-APR-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 114290.75 | 01-MAY-04:11 | 0.00 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 116021.42 | 01-JUN-04:12 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 114024.84 | 05-JUL-04:11 | 0.00 | 20357.61 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 115438.23 | 30-AUG-04:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 120044.22 | 05-SEP-04:12 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 119229.67 | 10-OCT-04:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 115125.38 | 13-NOV-05:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 113632.42 | 11-DEC-05:11 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 108879.69 | 0.00 | 17449.38 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 120044.22 | 0.00 | 29082.30 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 94404.51 | 13-JAN-06:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 98981.17 | 23-FEB-06:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 100964.69 | 09-MAR-06:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 102213.21 | 21-APR-04:11 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 104407.41 | 23-MAY-04:11 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 106876.36 | 01-JUN-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 105005.63 | 05-JUL-04:11 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 105222.02 | 23-AUG-04:12 | 0.00 | 17449.38 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 105638.25 | 21-SEP-04:11 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 106183.41 | 06-OCT-04:11 | 0.00 | 29082.30 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 100853.99 | 03-NOV-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 91103.01 | 15-DEC-06:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91103.01 | 0.00 | 17449.38 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 106876.36 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 38530.24 | 12-JAN-16:20 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 41808.09 | 07-FEB-14:52 | 160145.81 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52286.77 | 16-MAR-15:40 | 15316.26 | 26174.07 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 109140.69 | 21-APR-05:01 | 12897.91 | 23265.84 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 113692.50 | 17-MAY-05:01 | 12897.91 | 23265.84 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 121216.98 | 05-JUN-04:11 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 119896.81 | 07-JUL-03:01 | 0.00 | 10178.80 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 119106.62 | 21-AUG-04:12 | 0.00 | 17449.38 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 115271.34 | 13-SEP-04:11 | 0.00 | 20357.61 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 115611.40 | 04-OCT-05:01 | 16122.38 | 29082.30 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 48135.88 | 10-NOV-14:53 | 64058.32 | 104696.28 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 31646.51 | 01-DEC-15:32 | 137846.38 | 235566.63 | 154859.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 31646.51 | 0.00 | 10178.80 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 121216.98 | 160145.81 | 261740.70 | 172065.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5306.81 | 01-JAN-13:52 | 506.08 | 912.89 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.74 |
February | 6381.95 | 23-FEB-14:30 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.74 |
March | 8091.83 | 15-MAR-14:00 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.87 |
April | 11022.53 | 21-APR-15:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 183.09 | 0.00 |
May | 17922.80 | 30-MAY-05:02 | 1012.16 | 1825.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 0.00 |
June | 23264.09 | 04-JUN-16:51 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16568.10 | 10-JUL-05:02 | 1012.16 | 1825.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 14860.92 | 05-AUG-05:02 | 1012.16 | 1825.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 |
September | 16282.11 | 13-SEP-04:11 | 0.00 | 2556.10 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 |
October | 13695.27 | 05-OCT-04:11 | 0.00 | 2556.10 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.38 |
November | 6943.68 | 08-NOV-14:30 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.49 |
December | 5001.70 | 11-DEC-05:12 | 0.00 | 3651.57 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5001.70 | 0.00 | 912.89 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23264.09 | 2010.79 | 3651.57 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 183.09 | 275.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6223.51 | 31-JAN-09:25 | 2478.65 | 4235.78 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.39 |
February | 16080.17 | 20-FEB-09:11 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22023.24 | 19-MAR-09:41 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.46 |
April | 24496.69 | 30-APR-08:31 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.98 |
May | 23961.63 | 28-MAY-09:02 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.05 |
June | 24586.76 | 04-JUN-08:51 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.43 |
July | 24338.74 | 23-JUL-09:01 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.70 |
August | 19341.18 | 06-AUG-08:42 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 | 0.00 |
September | 24474.53 | 17-SEP-09:21 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.59 |
October | 22524.96 | 29-OCT-08:51 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.53 |
November | 10398.40 | 11-NOV-09:25 | 652.28 | 1176.61 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.18 |
December | 5187.91 | 07-DEC-08:55 | 4957.30 | 8471.56 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5187.91 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24586.76 | 4957.30 | 8471.56 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 | 141.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27660.59 | 01-JAN-13:52 | 506.09 | 912.91 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.24 |
February | 28304.25 | 19-FEB-12:21 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.60 |
March | 26560.90 | 05-MAR-14:01 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.45 |
April | 26465.41 | 16-APR-14:11 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 48.95 | 0.00 |
May | 22983.12 | 21-MAY-14:01 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 249.67 | 0.00 |
June | 23049.98 | 04-JUN-16:11 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 107.62 | 0.00 |
July | 18661.10 | 23-JUL-13:41 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 64.14 | 0.00 |
August | 23304.94 | 06-AUG-15:21 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 142.15 | 0.00 |
September | 28898.13 | 17-SEP-13:22 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 68.01 | 0.00 |
October | 28801.01 | 08-OCT-13:32 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.44 |
November | 29204.82 | 11-NOV-11:21 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.13 |
December | 27548.32 | 17-DEC-12:31 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18661.10 | 506.09 | 912.91 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29204.82 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 249.67 | 349.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10122.81 | 12-JAN-15:30 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.72 |
February | 23138.31 | 19-FEB-15:42 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.23 |
March | 29081.97 | 05-MAR-16:42 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.78 |
April | 32050.74 | 30-APR-16:31 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.62 | 0.00 |
May | 33466.41 | 14-MAY-16:21 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.66 | 0.00 |
June | 35013.75 | 25-JUN-16:51 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 37.57 | 0.00 |
July | 32825.74 | 23-JUL-15:01 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 39.24 | 0.00 |
August | 31837.94 | 06-AUG-16:41 | 456.59 | 823.62 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 116.41 | 0.00 |
September | 32227.70 | 17-SEP-16:41 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 38.20 | 0.00 |
October | 28166.65 | 15-OCT-14:21 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.96 |
November | 28722.83 | 19-NOV-16:11 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.30 |
December | 11780.71 | 03-DEC-15:33 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10122.81 | 391.37 | 705.96 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35013.75 | 1239.33 | 2117.89 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 123.66 | 108.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4691.69 | 12-JAN-14:30 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.22 |
February | 4757.67 | 22-FEB-13:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.90 |
March | 6512.15 | 22-MAR-14:40 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 |
April | 10136.59 | 21-APR-15:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 423.68 | 0.00 |
May | 12431.99 | 31-MAY-04:01 | 0.00 | 2556.10 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 65.17 | 0.00 |
June | 19646.12 | 04-JUN-16:51 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18694.49 | 03-JUL-03:02 | 0.00 | 1095.47 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 160.21 | 0.00 |
August | 16636.10 | 24-AUG-05:02 | 1012.16 | 1825.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 18.06 | 0.00 |
September | 10269.63 | 20-SEP-14:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 76.11 | 0.00 |
October | 9856.69 | 03-OCT-14:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 67.69 | 0.00 |
November | 5279.36 | 09-NOV-14:40 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.13 |
December | 3861.80 | 07-DEC-14:20 | 10053.95 | 16432.08 | 10802.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3861.80 | 0.00 | 1095.47 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19646.12 | 10053.95 | 16432.08 | 10802.76 | 0.00 | 0.00 | 0.00 | 0.00 | 423.68 | 132.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9086.13 | 12-JAN-11:02 | 7435.95 | 12707.35 | 8354.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.92 |
February | 14880.07 | 21-FEB-11:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.08 |
March | 17717.99 | 21-MAR-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.01 |
April | 24589.16 | 30-APR-10:02 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.66 |
May | 24782.29 | 28-MAY-09:12 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.04 |
June | 25582.51 | 04-JUN-08:51 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.76 |
July | 25566.83 | 09-JUL-09:01 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.36 |
August | 25370.51 | 27-AUG-09:51 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 146.64 | 0.00 |
September | 24722.46 | 04-SEP-09:22 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.54 |
October | 19386.36 | 01-OCT-09:52 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15806.25 | 03-NOV-10:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.63 |
December | 11093.38 | 14-DEC-11:01 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9086.13 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25582.51 | 12393.25 | 21178.91 | 13923.42 | 0.00 | 0.00 | 0.00 | 0.00 | 146.64 | 146.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25316.42 | 01-JAN-14:43 | 404.87 | 730.33 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1048.71 |
February | 27281.33 | 05-FEB-14:21 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.81 |
March | 25292.64 | 05-MAR-13:51 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.57 |
April | 25411.18 | 30-APR-14:41 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 92.75 | 0.00 |
May | 13146.89 | 19-MAY-13:50 | 2010.83 | 3286.49 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 361.36 | 0.00 |
June | 22489.42 | 18-JUN-14:21 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 341.90 | 0.00 |
July | 25459.82 | 30-JUL-13:51 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 170.91 | 0.00 |
August | 25303.32 | 20-AUG-14:01 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 347.88 | 0.00 |
September | 27013.93 | 04-SEP-13:22 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 81.95 | 0.00 |
October | 29607.35 | 29-OCT-13:21 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.21 |
November | 28326.35 | 05-NOV-13:31 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.34 |
December | 26152.53 | 31-DEC-13:52 | 506.09 | 912.91 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13146.89 | 404.87 | 730.33 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29607.35 | 2010.83 | 3286.49 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 361.36 | 1048.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7578.43 | 12-JAN-15:30 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.28 |
February | 16506.74 | 19-FEB-16:32 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.88 |
March | 16383.82 | 05-MAR-16:32 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.46 |
April | 27643.77 | 30-APR-16:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 73.10 | 0.00 |
May | 28255.67 | 29-MAY-16:31 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 304.87 | 0.00 |
June | 30733.39 | 25-JUN-17:01 | 0.00 | 1176.61 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 75.02 | 0.00 |
July | 28510.45 | 30-JUL-15:11 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.40 | 0.00 |
August | 30174.24 | 27-AUG-16:31 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 184.45 | 0.00 |
September | 26645.87 | 10-SEP-15:51 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.66 | 0.00 |
October | 27588.26 | 01-OCT-15:11 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 208.34 | 0.00 |
November | 11001.92 | 03-NOV-16:00 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 |
December | 6906.70 | 15-DEC-15:52 | 6196.63 | 10589.46 | 6961.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6906.70 | 0.00 | 705.96 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30733.39 | 6196.63 | 10589.46 | 6961.66 | 0.00 | 0.00 | 0.00 | 0.00 | 304.87 | 248.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4941.02 | 12-JAN-14:30 | 2010.79 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.48 |
February | 5532.48 | 20-FEB-14:22 | 607.30 | 1095.47 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.68 | 0.00 |
March | 6990.01 | 22-MAR-14:40 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.29 |
April | 11564.38 | 21-APR-15:00 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 518.95 | 0.00 |
May | 27154.51 | 29-MAY-16:41 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 740.38 | 0.00 |
June | 30359.07 | 18-JUN-14:21 | 809.73 | 1460.63 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 397.66 | 0.00 |
July | 27742.55 | 02-JUL-16:21 | 708.51 | 1278.05 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 435.75 | 0.00 |
August | 28451.95 | 13-AUG-16:01 | 1012.16 | 1825.79 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 221.49 | 0.00 |
September | 11833.37 | 20-SEP-14:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 93.38 | 0.00 |
October | 11258.72 | 03-OCT-14:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 82.91 | 0.00 |
November | 6107.04 | 09-NOV-14:10 | 8043.16 | 13145.66 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 |
December | 4232.09 | 08-DEC-15:30 | 1923.11 | 3286.42 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4232.09 | 607.30 | 1095.47 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30359.07 | 8043.16 | 13145.66 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 740.38 | 91.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4185.84 | 12-JAN-14:30 | 1295.83 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.08 |
February | 5360.92 | 20-FEB-14:22 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.01 |
March | 7958.97 | 31-MAR-09:53 | 3887.49 | 6353.67 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.71 |
April | 18318.97 | 30-APR-09:32 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.56 |
May | 25869.73 | 29-MAY-09:22 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.37 |
June | 26342.62 | 18-JUN-08:21 | 456.59 | 823.62 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.14 |
July | 25789.11 | 16-JUL-08:22 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.23 |
August | 25753.16 | 20-AUG-08:52 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.79 |
September | 25682.60 | 17-SEP-09:52 | 391.37 | 705.96 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.65 |
October | 12583.58 | 01-OCT-09:52 | 326.14 | 588.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7715.17 | 10-NOV-09:40 | 1239.33 | 2117.89 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.85 |
December | 3559.75 | 01-DEC-10:30 | 10366.64 | 16943.13 | 11138.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3559.75 | 326.14 | 588.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26342.62 | 10366.64 | 16943.13 | 11138.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20301.03 | 12-JAN-14:13 | 6032.50 | 9859.46 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.47 |
February | 32031.09 | 20-FEB-14:22 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.74 |
March | 18992.86 | 05-MAR-14:01 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 683.05 |
April | 25870.80 | 16-APR-15:01 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 72.35 | 0.00 |
May | 30051.39 | 21-MAY-14:11 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 658.29 | 0.00 |
June | 31162.81 | 18-JUN-14:21 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 383.37 | 0.00 |
July | 31726.29 | 30-JUL-15:11 | 910.97 | 1643.24 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 35.19 | 0.00 |
August | 31481.48 | 13-AUG-16:01 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 179.73 | 0.00 |
September | 33813.58 | 17-SEP-13:51 | 708.53 | 1278.08 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 223.73 | 0.00 |
October | 35187.98 | 01-OCT-14:31 | 809.75 | 1460.66 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 266.72 | 0.00 |
November | 31701.11 | 11-NOV-11:51 | 1012.19 | 1825.83 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 604.09 |
December | 17027.50 | 06-DEC-13:42 | 9615.76 | 16432.44 | 10802.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17027.50 | 607.31 | 1095.50 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35187.98 | 9615.76 | 16432.44 | 10802.92 | 0.00 | 0.00 | 0.00 | 0.00 | 658.29 | 683.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7959.70 | 12-JAN-15:30 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.51 |
February | 11844.47 | 20-FEB-16:22 | 391.37 | 705.96 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.41 |
March | 13173.90 | 21-MAR-16:00 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 | 0.00 |
April | 32077.04 | 16-APR-15:41 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 26.86 | 0.00 |
May | 34744.07 | 29-MAY-16:41 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 224.46 | 0.00 |
June | 31493.90 | 18-JUN-14:21 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 0.00 |
July | 32881.59 | 30-JUL-15:11 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.72 | 0.00 |
August | 34511.26 | 13-AUG-16:01 | 652.28 | 1176.61 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 50.02 | 0.00 |
September | 33690.41 | 17-SEP-15:51 | 587.05 | 1058.95 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.92 | 0.00 |
October | 31234.42 | 01-OCT-15:11 | 521.82 | 941.28 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 251.53 | 0.00 |
November | 11442.00 | 03-NOV-16:00 | 1239.33 | 2117.89 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 |
December | 6542.20 | 15-DEC-15:52 | 6196.63 | 10589.46 | 6961.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6542.20 | 391.37 | 705.96 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34744.07 | 6196.63 | 10589.46 | 6961.66 | 0.00 | 0.00 | 0.00 | 0.00 | 251.53 | 338.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8508.23 | 02-JAN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.84 |
February | 7838.27 | 22-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.18 |
March | 7692.56 | 17-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.87 |
April | 9209.18 | 21-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.62 | 0.00 |
May | 10776.75 | 30-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
June | 10732.32 | 05-JUN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.14 | 0.00 |
July | 10950.46 | 03-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.95 | 0.00 |
August | 11090.36 | 07-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.40 | 0.00 |
September | 10962.77 | 05-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.02 | 0.00 |
October | 9966.76 | 05-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.35 | 0.00 |
November | 7967.41 | 13-NOV-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 644.35 |
December | 7402.45 | 08-DEC-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7402.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11090.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.62 | 644.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10926.49 | 28-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2105.30 |
February | 11737.98 | 09-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2615.41 |
March | 11146.72 | 02-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1069.53 |
April | 8264.75 | 22-APR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 666.83 |
May | 8812.56 | 31-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 |
June | 9691.61 | 07-JUN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.34 | 0.00 |
July | 9869.31 | 12-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.52 |
August | 9568.25 | 09-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.43 |
September | 8714.23 | 20-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.70 | 0.00 |
October | 8316.84 | 05-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.48 | 0.00 |
November | 9449.92 | 28-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2492.08 |
December | 10558.87 | 30-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1683.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8264.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11737.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.34 | 2615.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14413.50 | 12-JAN-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.73 |
February | 19057.64 | 22-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23859.25 | 16-MAR-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.06 |
April | 34497.90 | 28-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.96 | 0.00 |
May | 38947.54 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.53 | 0.00 |
June | 42571.54 | 18-JUN-13:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.15 | 0.00 |
July | 40813.71 | 26-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.86 | 0.00 |
August | 39734.09 | 04-AUG-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.96 | 0.00 |
September | 36632.75 | 15-SEP-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.94 | 0.00 |
October | 32274.06 | 03-OCT-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.44 | 0.00 |
November | 19269.96 | 03-NOV-14:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.38 |
December | 10063.41 | 17-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 10063.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42571.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.15 | 620.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2340.02 | 30-JAN-16:53 | 888.56 | 2915.14 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4177.86 | 21-FEB-17:00 | 222.14 | 728.78 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6998.90 | 31-MAR-23:52 | 0.00 | 404.88 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8156.59 | 30-APR-18:01 | 0.00 | 283.42 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3520.72 | 31-MAY-24:00 | 0.00 | 40.49 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5359.45 | 30-JUN-23:20 | 0.00 | 80.98 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7231.50 | 31-JUL-23:33 | 0.00 | 121.46 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8204.68 | 06-AUG-18:11 | 0.00 | 364.39 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3430.27 | 30-SEP-23:51 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5132.17 | 31-OCT-23:52 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6292.31 | 09-NOV-16:50 | 222.14 | 728.78 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7970.44 | 15-DEC-16:35 | 888.56 | 2915.14 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2340.02 | 0.00 | 40.49 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8204.68 | 888.56 | 2915.14 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2089.29 | 30-JAN-16:53 | 888.56 | 2915.14 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3946.28 | 21-FEB-17:00 | 222.14 | 728.78 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6524.83 | 31-MAR-23:33 | 0.00 | 283.42 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7676.87 | 30-APR-17:57 | 0.00 | 283.42 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3407.21 | 31-MAY-24:00 | 0.00 | 40.49 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5236.77 | 30-JUN-24:00 | 0.00 | 40.49 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7031.64 | 31-JUL-23:54 | 0.00 | 202.44 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7726.28 | 06-AUG-18:07 | 0.00 | 283.42 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3126.64 | 30-SEP-23:26 | 0.00 | 283.42 | 27280.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4694.90 | 31-OCT-23:42 | 0.00 | 404.88 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5970.57 | 09-NOV-16:50 | 222.14 | 728.78 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7562.84 | 15-DEC-16:45 | 888.56 | 2915.14 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2089.29 | 0.00 | 40.49 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7726.28 | 888.56 | 2915.14 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2076.92 | 19-JAN-16:55 | 888.56 | 2915.14 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3991.84 | 21-FEB-17:00 | 222.14 | 728.78 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6032.49 | 31-MAR-23:10 | 0.00 | 80.98 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8027.45 | 30-APR-17:53 | 0.00 | 283.42 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3422.57 | 31-MAY-24:00 | 0.00 | 40.49 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5212.34 | 30-JUN-24:00 | 0.00 | 40.49 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7027.84 | 31-JUL-23:54 | 0.00 | 202.44 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8245.70 | 06-AUG-18:06 | 0.00 | 283.42 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2770.39 | 30-SEP-23:02 | 0.00 | 404.88 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4287.96 | 05-OCT-17:00 | 70.15 | 404.88 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6054.10 | 09-NOV-16:50 | 222.14 | 728.78 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7501.88 | 15-DEC-16:45 | 888.56 | 2915.14 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2076.92 | 0.00 | 40.49 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8245.70 | 888.56 | 2915.14 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 104153.48 | 11-JAN-05:11 | 0.00 | 9130.65 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 508440.28 | 27-FEB-01:02 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 546933.07 | 11-MAR-14:12 | 5292.55 | 13695.97 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 525279.09 | 06-APR-10:57 | 48086.79 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176278.24 | 31-MAY-24:00 | 0.00 | 456.53 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 489341.52 | 11-JUN-03:42 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 434747.97 | 05-JUL-05:27 | 5061.77 | 9130.65 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 370623.09 | 23-AUG-16:00 | 4808.68 | 8217.58 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 494914.92 | 30-SEP-23:12 | 0.00 | 4565.32 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 538505.43 | 31-OCT-23:01 | 0.00 | 4565.32 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 542938.94 | 15-NOV-14:22 | 50279.21 | 82175.84 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 528038.76 | 13-DEC-13:07 | 48086.79 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 104153.48 | 0.00 | 456.53 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 546933.07 | 50279.21 | 82175.84 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.198805E+13 | 1614903.32 | 11-JAN-15:09 | 0.138483E+12 | 722143.46 | 09-JAN-05:19 |
February | 0.221964E+13 | 1795235.50 | 21-FEB-16:30 | 0.890486E+11 | 715326.01 | 10-FEB-05:10 |
March | 0.300522E+13 | 2054512.35 | 14-MAR-15:09 | 0.569493E+11 | 653875.15 | 02-MAR-05:10 |
April | 0.329796E+13 | 2292830.44 | 21-APR-15:09 | 0.849019E+10 | 497536.84 | 11-APR-05:10 |
May | 0.233532E+13 | 1889633.06 | 19-MAY-15:30 | 0.467358E+09 | 53373.58 | 02-MAY-05:10 |
June | 0.275554E+13 | 2062376.46 | 07-JUN-15:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.318965E+13 | 2228054.17 | 21-JUL-07:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.363632E+13 | 2353846.47 | 04-AUG-15:30 | 7071022.08 | 1856.17 | 17-AUG-05:40 |
September | 0.220591E+13 | 1900889.82 | 20-SEP-15:39 | 0.682068E+09 | 58612.74 | 25-SEP-05:49 |
October | 0.251621E+13 | 1998334.91 | 05-OCT-15:00 | 0.974340E+10 | 208687.58 | 25-OCT-05:10 |
November | 0.280355E+13 | 2008091.40 | 03-NOV-15:00 | 0.663972E+11 | 752817.71 | 28-NOV-05:10 |
December | 0.323919E+13 | 2025874.75 | 07-DEC-15:09 | 0.158389E+12 | 795969.79 | 26-DEC-05:10 |
Annual Sum or Average | 0.331925E+14 | 0.528657E+12 | ||||
Minimum of Months | 0.198805E+13 | 1614903.32 | 0.00 | 0.00 | ||
Maximum of Months | 0.363632E+13 | 2353846.47 | 0.158389E+12 | 795969.79 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.468149E+12 | 0.989695E+11 | 0.766053E+12 | 0.218140E+12 | 0.185990E+12 | 0.237294E+11 | 0.00 | 0.344648E+11 | 39561608.59 | 0.156392E+12 | 0.00 | 0.361231E+11 | 0.00 |
February | 0.424646E+12 | 0.846662E+11 | 0.978954E+12 | 0.199667E+12 | 0.196351E+12 | 0.436926E+11 | 0.00 | 0.104973E+12 | 0.261415E+09 | 0.153628E+12 | 0.00 | 0.327971E+11 | 0.00 |
March | 0.504598E+12 | 0.870116E+11 | 0.141687E+13 | 0.230864E+12 | 0.255355E+12 | 0.784687E+11 | 0.00 | 0.172325E+12 | 0.832812E+09 | 0.221715E+12 | 0.00 | 0.371790E+11 | 0.00 |
April | 0.450709E+12 | 0.774377E+11 | 0.165903E+13 | 0.216144E+12 | 0.290350E+12 | 0.108200E+12 | 0.00 | 0.286137E+12 | 0.851068E+10 | 0.169871E+12 | 0.00 | 0.315742E+11 | 0.00 |
May | 0.486374E+12 | 0.742079E+11 | 0.774844E+12 | 0.224502E+12 | 0.266114E+12 | 0.949672E+11 | 0.00 | 0.276017E+12 | 0.186082E+11 | 0.886290E+11 | 0.00 | 0.310528E+11 | 0.00 |
June | 0.484022E+12 | 0.689018E+11 | 0.106252E+13 | 0.222585E+12 | 0.296512E+12 | 0.129376E+12 | 0.00 | 0.405126E+12 | 0.408660E+11 | 0.172099E+11 | 0.00 | 0.284260E+11 | 0.00 |
July | 0.453060E+12 | 0.724776E+11 | 0.139340E+13 | 0.218061E+12 | 0.308551E+12 | 0.144381E+12 | 0.00 | 0.499900E+12 | 0.738015E+11 | 0.222100E+09 | 0.00 | 0.257913E+11 | 0.00 |
August | 0.504598E+12 | 0.774377E+11 | 0.173200E+13 | 0.230864E+12 | 0.348469E+12 | 0.142354E+12 | 0.00 | 0.507261E+12 | 0.609468E+11 | 0.415900E+10 | 0.00 | 0.282276E+11 | 0.00 |
September | 0.450709E+12 | 0.812057E+11 | 0.740713E+12 | 0.216143E+12 | 0.256720E+12 | 0.933835E+11 | 0.00 | 0.288349E+12 | 0.345994E+11 | 0.171614E+11 | 0.00 | 0.269274E+11 | 0.00 |
October | 0.468149E+12 | 0.909719E+11 | 0.108340E+13 | 0.218140E+12 | 0.246162E+12 | 0.792846E+11 | 0.00 | 0.229072E+12 | 0.135740E+11 | 0.574210E+11 | 0.00 | 0.300338E+11 | 0.00 |
November | 0.462662E+12 | 0.939326E+11 | 0.135889E+13 | 0.209941E+12 | 0.237697E+12 | 0.777224E+11 | 0.00 | 0.150497E+12 | 0.962254E+09 | 0.179254E+12 | 0.00 | 0.319865E+11 | 0.00 |
December | 0.453060E+12 | 0.100431E+12 | 0.170972E+13 | 0.218060E+12 | 0.253029E+12 | 0.944215E+11 | 0.00 | 0.128034E+12 | 20624620.51 | 0.248396E+12 | 0.00 | 0.340145E+11 | 0.00 |
Annual Sum or Average | 0.561074E+13 | 0.100765E+13 | 0.146764E+14 | 0.262311E+13 | 0.314130E+13 | 0.110998E+13 | 0.00 | 0.308216E+13 | 0.253023E+12 | 0.131406E+13 | 0.00 | 0.374133E+12 | 0.00 |
Minimum of Months | 0.424646E+12 | 0.689018E+11 | 0.740713E+12 | 0.199667E+12 | 0.185990E+12 | 0.237294E+11 | 0.00 | 0.344648E+11 | 20624620.51 | 0.222100E+09 | 0.00 | 0.257913E+11 | 0.00 |
Maximum of Months | 0.504598E+12 | 0.100431E+12 | 0.173200E+13 | 0.230864E+12 | 0.348469E+12 | 0.144381E+12 | 0.00 | 0.507261E+12 | 0.738015E+11 | 0.248396E+12 | 0.00 | 0.371790E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.138483E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.890486E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.569493E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.849019E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.467358E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 7071022.08 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.682068E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.974340E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.663972E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.158389E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.528657E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.158389E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 489900.85 | 02-JAN-08:09 | 64082.80 | 01-JAN-00:10 | 423497.50 | 02-JAN-08:09 | 235096.12 | 02-JAN-08:20 | 177298.17 | 12-JAN-15:00 | 41736.92 | 12-JAN-14:39 | 0.00 | 01-JAN-00:10 |
February | 489900.85 | 01-FEB-08:09 | 64082.80 | 01-FEB-00:10 | 541788.89 | 01-FEB-08:09 | 235096.12 | 01-FEB-08:20 | 185595.77 | 24-FEB-15:20 | 42393.34 | 07-FEB-13:39 | 0.00 | 01-FEB-00:10 |
March | 489900.85 | 01-MAR-08:09 | 64082.80 | 01-MAR-00:10 | 660080.29 | 01-MAR-08:09 | 235096.12 | 01-MAR-08:20 | 249244.80 | 16-MAR-15:30 | 82870.43 | 22-MAR-13:20 | 0.00 | 01-MAR-00:10 |
April | 489900.85 | 03-APR-07:10 | 64082.80 | 01-APR-00:10 | 778371.69 | 03-APR-07:10 | 235096.12 | 03-APR-07:19 | 285650.61 | 21-APR-14:00 | 87055.67 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 489900.85 | 01-MAY-07:10 | 64082.80 | 01-MAY-00:10 | 423497.50 | 01-MAY-07:10 | 235096.12 | 01-MAY-07:19 | 274818.03 | 19-MAY-15:30 | 85978.36 | 12-MAY-15:30 | 0.00 | 01-MAY-00:10 |
June | 489900.85 | 01-JUN-07:10 | 64082.80 | 01-JUN-00:10 | 541788.89 | 01-JUN-07:10 | 235096.12 | 01-JUN-07:19 | 297978.47 | 15-JUN-15:09 | 87013.08 | 07-JUN-15:20 | 0.00 | 01-JUN-00:10 |
July | 489900.85 | 03-JUL-07:10 | 64082.80 | 01-JUL-00:10 | 660080.29 | 03-JUL-07:10 | 235096.12 | 03-JUL-07:19 | 292286.05 | 06-JUL-15:30 | 89290.88 | 21-JUL-09:50 | 0.00 | 01-JUL-00:10 |
August | 489900.85 | 01-AUG-07:10 | 64082.80 | 01-AUG-00:10 | 778371.69 | 01-AUG-07:10 | 235096.12 | 01-AUG-07:19 | 307621.51 | 04-AUG-15:30 | 87106.01 | 23-AUG-15:20 | 0.00 | 01-AUG-00:10 |
September | 489900.85 | 01-SEP-07:10 | 64082.80 | 01-SEP-00:10 | 423497.50 | 01-SEP-07:10 | 235096.12 | 01-SEP-07:19 | 283893.92 | 20-SEP-15:30 | 86858.26 | 25-SEP-15:30 | 0.00 | 01-SEP-00:10 |
October | 489900.85 | 02-OCT-07:10 | 64082.80 | 01-OCT-00:10 | 541788.89 | 02-OCT-07:10 | 235096.12 | 02-OCT-07:19 | 259945.70 | 03-OCT-15:30 | 86474.85 | 19-OCT-14:20 | 0.00 | 01-OCT-00:10 |
November | 489900.85 | 01-NOV-07:10 | 64082.80 | 01-NOV-00:10 | 660080.29 | 01-NOV-07:10 | 235096.12 | 01-NOV-07:19 | 240374.56 | 10-NOV-15:50 | 83137.64 | 03-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 489900.85 | 01-DEC-08:09 | 64082.80 | 01-DEC-00:10 | 778371.69 | 01-DEC-08:09 | 235096.12 | 01-DEC-08:20 | 200334.89 | 15-DEC-15:30 | 42705.91 | 01-DEC-14:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 489900.85 | 64082.80 | 423497.50 | 235096.12 | 177298.17 | 41736.92 | 0.00 | |||||||
Maximum of Months | 489900.85 | 64082.80 | 778371.69 | 235096.12 | 307621.51 | 89290.88 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 147952.20 | 12-JAN-14:00 | 3484.71 | 12-JAN-14:00 | 100000.00 | 03-JAN-14:20 | 0.00 | 47541.54 | 30-JAN-12:00 | 0.00 |
February | 164995.89 | 21-FEB-15:00 | 3504.45 | 27-FEB-15:09 | 100000.00 | 06-FEB-12:09 | 0.00 | 47531.71 | 02-FEB-12:00 | 0.00 |
March | 307390.57 | 22-MAR-14:00 | 13321.57 | 14-MAR-15:09 | 100000.00 | 03-MAR-12:09 | 0.00 | 46772.18 | 01-MAR-12:00 | 0.00 |
April | 339825.81 | 21-APR-14:50 | 50732.53 | 21-APR-15:09 | 100000.00 | 01-APR-00:20 | 0.00 | 44241.38 | 03-APR-11:39 | 0.00 |
May | 323801.51 | 19-MAY-12:09 | 50732.53 | 18-MAY-12:30 | 100000.00 | 01-MAY-04:30 | 0.00 | 40796.73 | 02-MAY-11:00 | 0.00 |
June | 338277.77 | 02-JUN-15:00 | 50732.53 | 02-JUN-13:30 | 100000.00 | 11-JUN-00:00 | 0.00 | 37950.76 | 01-JUN-11:50 | 0.00 |
July | 536296.01 | 21-JUL-09:30 | 50732.53 | 01-JUL-08:00 | 45228.74 | 18-JUL-06:19 | 0.00 | 34866.32 | 03-JUL-11:00 | 0.00 |
August | 429658.86 | 02-AUG-07:49 | 50732.53 | 01-AUG-07:30 | 100000.00 | 23-AUG-01:30 | 0.00 | 34957.17 | 31-AUG-11:00 | 0.00 |
September | 316239.87 | 01-SEP-12:00 | 50732.53 | 01-SEP-07:49 | 100000.00 | 11-SEP-21:10 | 0.00 | 37808.43 | 29-SEP-11:30 | 0.00 |
October | 328767.06 | 03-OCT-13:50 | 50732.53 | 02-OCT-10:30 | 100000.00 | 09-OCT-16:30 | 0.00 | 40992.52 | 31-OCT-11:39 | 0.00 |
November | 294101.20 | 03-NOV-15:00 | 13927.15 | 03-NOV-15:20 | 100000.00 | 05-NOV-15:09 | 0.00 | 44489.54 | 30-NOV-12:39 | 0.00 |
December | 162086.64 | 07-DEC-15:09 | 1854.08 | 07-DEC-15:09 | 100000.00 | 01-DEC-07:30 | 0.00 | 46694.41 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 147952.20 | 1854.08 | 45228.74 | 0.00 | 34866.32 | 0.00 | ||||
Maximum of Months | 536296.01 | 50732.53 | 100000.00 | 0.00 | 47541.54 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1614903.32 | 11-JAN-15:09 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 164997.24 | 41301.93 | 0.00 | 132226.38 | 712.12 |
February | 1795235.50 | 21-FEB-16:30 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 182746.96 | 41707.58 | 0.00 | 164328.58 | 2889.66 |
March | 2054512.35 | 14-MAR-15:09 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 205075.36 | 82376.30 | 0.00 | 299876.63 | 13321.57 |
April | 2292830.44 | 21-APR-15:09 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 284869.81 | 83862.07 | 0.00 | 338386.01 | 50732.53 |
May | 1889633.06 | 19-MAY-15:30 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 274818.03 | 84926.04 | 0.00 | 301130.66 | 50732.53 |
June | 2062376.46 | 07-JUN-15:20 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 293775.68 | 87013.08 | 0.00 | 335278.98 | 50732.53 |
July | 2228054.17 | 21-JUL-07:00 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 203407.03 | 86317.25 | 0.00 | 481288.79 | 50732.53 |
August | 2353846.47 | 04-AUG-15:30 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 307621.51 | 85305.80 | 0.00 | 380112.48 | 50732.53 |
September | 1900889.82 | 20-SEP-15:39 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 280821.18 | 84511.03 | 0.00 | 307658.53 | 50732.53 |
October | 1998334.91 | 05-OCT-15:00 | 489900.85 | 541788.89 | 0.00 | 235096.12 | 258397.50 | 84703.57 | 0.00 | 308486.09 | 50732.53 |
November | 2008091.40 | 03-NOV-15:00 | 489900.85 | 660080.29 | 0.00 | 235096.12 | 207306.15 | 83137.64 | 0.00 | 294101.20 | 6465.91 |
December | 2025874.75 | 07-DEC-15:09 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 189891.28 | 42096.05 | 0.00 | 162086.64 | 1854.08 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1614903.32 | 489900.85 | 423497.50 | 0.00 | 235096.12 | 164997.24 | 41301.93 | 0.00 | 132226.38 | 712.12 | |
Maximum of Months | 2353846.47 | 489900.85 | 778371.69 | 0.00 | 235096.12 | 307621.51 | 87013.08 | 0.00 | 481288.79 | 50732.53 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 722143.46 | 09-JAN-05:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 715326.01 | 10-FEB-05:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 653875.15 | 02-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 497536.84 | 11-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 53373.58 | 02-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 1856.17 | 17-AUG-05:40 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 58612.74 | 25-SEP-05:49 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 208687.58 | 25-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 752817.71 | 28-NOV-05:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 795969.79 | 26-DEC-05:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 795969.79 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.75 | 0.50 | 26.83 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.77 | 0.00 | 25.77 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.71 | 0.00 | 25.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 26.17 | 0.00 | 26.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.66 | 0.00 | 25.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 25.83 | 0.00 | 25.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 25.78 | 0.00 | 25.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 25.91 | 0.00 | 25.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 25.82 | 0.00 | 25.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 25.76 | 0.00 | 25.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.85 | 0.00 | 25.85 |
Annual Sum or Average | 0.00 | 0.00 | 34.50 | 25.91 | 0.50 | 25.93 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 26.75 | 0.50 | 26.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.63 | 0.00 | 25.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.65 | 0.00 | 25.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 25.62 | 0.00 | 25.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.65 | 0.00 | 25.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
December | 0.67 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
Annual Sum or Average | 1.33 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.33 | 0.33 | 27.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 27.33 | 0.33 | 27.35 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.33 | 0.33 | 27.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.91 | 3.50 | 27.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.09 | 5.17 | 28.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.20 | 5.00 | 28.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.15 | 6.17 | 28.15 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.11 | 4.17 | 28.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.03 | 3.83 | 28.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.61 | 1.17 | 27.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 29.00 | 28.07 | 29.00 | 28.07 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.20 | 6.17 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.70 | 3.00 | 27.70 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.84 | 4.33 | 27.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.38 | 1.00 | 27.38 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.52 | 2.00 | 27.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.46 | 1.83 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.65 | 5.00 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.95 | 6.33 | 27.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.24 | 7.67 | 28.24 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.10 | 6.17 | 28.10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.70 | 2.33 | 27.70 |
Annual Sum or Average | 0.00 | 0.00 | 39.83 | 27.89 | 39.67 | 27.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.24 | 7.67 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.85 | 1.00 | 27.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.07 | 1.83 | 28.05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.40 | 6.00 | 28.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.54 | 5.33 | 28.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 28.25 | 5.83 | 28.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 28.20 | 6.33 | 28.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.88 | 6.00 | 28.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.29 | 3.83 | 28.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.24 | 3.67 | 28.29 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.45 | 1.17 | 27.45 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 73.67 | 28.19 | 41.00 | 28.32 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 28.54 | 6.33 | 28.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
February | 1.33 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
March | 0.33 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.17 | 27.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
December | 1.83 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
Annual Sum or Average | 5.83 | 19.18 | 0.00 | 19.18 | 0.33 | 19.62 | 0.17 | 19.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 19.25 | 0.00 | 19.25 | 0.33 | 27.28 | 0.17 | 27.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
February | 1.33 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
March | 0.33 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.98 | 2.50 | 27.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.17 | 4.83 | 28.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.25 | 5.67 | 28.25 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.16 | 8.17 | 28.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.19 | 5.50 | 28.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.07 | 3.17 | 28.07 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.63 | 0.50 | 27.63 |
November | 0.50 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
December | 1.83 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
Annual Sum or Average | 6.00 | 19.18 | 0.00 | 19.18 | 30.33 | 26.67 | 30.33 | 27.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.10 | 0.00 | 19.10 |
Maximum of Months | 2.00 | 19.23 | 0.00 | 19.23 | 8.17 | 28.25 | 8.17 | 28.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 19.33 | 0.00 | 19.33 | 2.67 | 26.08 | 2.67 | 26.83 |
February | 0.67 | 19.31 | 0.00 | 19.31 | 4.67 | 26.94 | 4.67 | 27.45 |
March | 0.17 | 19.33 | 0.00 | 19.33 | 0.67 | 25.80 | 0.67 | 26.52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.54 | 0.83 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.36 | 0.83 | 27.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.63 | 3.33 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.92 | 6.00 | 27.92 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.39 | 7.00 | 28.39 |
November | 0.33 | 19.26 | 0.00 | 19.26 | 6.33 | 27.76 | 6.33 | 27.97 |
December | 0.83 | 19.24 | 0.00 | 19.24 | 2.00 | 25.33 | 2.00 | 26.38 |
Annual Sum or Average | 2.67 | 19.29 | 0.00 | 19.29 | 34.33 | 27.38 | 34.33 | 27.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 19.33 | 0.00 | 19.33 | 7.00 | 28.39 | 7.00 | 28.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
February | 0.83 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
March | 0.33 | 19.36 | 0.00 | 19.36 | 0.50 | 24.41 | 0.33 | 25.38 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.32 | 2.83 | 28.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.54 | 4.00 | 28.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.64 | 3.67 | 28.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.46 | 4.83 | 28.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.65 | 3.50 | 28.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.28 | 2.50 | 28.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.94 | 2.50 | 27.94 |
November | 0.33 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
December | 1.50 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Annual Sum or Average | 4.17 | 19.30 | 0.00 | 19.30 | 38.50 | 27.56 | 24.17 | 27.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.27 | 0.00 | 19.27 |
Maximum of Months | 1.50 | 19.36 | 0.00 | 19.36 | 8.17 | 28.65 | 4.83 | 28.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.67 | 17.98 | 0.00 | 17.98 | 0.00 | 17.98 | 0.00 | 17.98 |
February | 5.83 | 18.40 | 0.50 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
March | 4.00 | 18.83 | 0.17 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
April | 0.33 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.71 | 1.33 | 27.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.77 | 1.17 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.47 | 0.83 | 27.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4.83 | 17.62 | 0.17 | 17.70 | 0.00 | 17.70 | 0.00 | 17.70 |
December | 12.33 | 17.25 | 1.17 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 |
Annual Sum or Average | 35.00 | 17.85 | 2.00 | 17.88 | 4.33 | 18.91 | 3.33 | 19.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.33 | 19.16 | 1.17 | 19.16 | 1.67 | 27.77 | 1.33 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.50 | 18.06 | 0.00 | 18.06 | 0.00 | 18.06 | 0.00 | 18.06 |
February | 5.67 | 18.35 | 0.33 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
March | 4.00 | 18.86 | 0.17 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
April | 0.33 | 19.15 | 0.00 | 19.15 | 1.67 | 26.43 | 1.67 | 27.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.79 | 9.17 | 27.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 28.15 | 9.33 | 28.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 28.13 | 12.33 | 28.14 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.10 | 9.00 | 28.10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.95 | 3.33 | 27.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4.83 | 17.65 | 0.17 | 17.73 | 0.00 | 17.73 | 0.00 | 17.73 |
December | 11.67 | 17.22 | 0.50 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
Annual Sum or Average | 34.00 | 17.87 | 1.17 | 17.89 | 45.83 | 23.63 | 44.83 | 25.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.67 | 19.15 | 0.50 | 19.15 | 12.83 | 28.15 | 12.33 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.67 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 |
February | 5.17 | 18.58 | 0.17 | 18.63 | 1.67 | 20.84 | 1.67 | 22.19 |
March | 2.83 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
April | 0.17 | 18.92 | 0.00 | 18.92 | 1.33 | 26.71 | 1.33 | 27.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.39 | 2.00 | 27.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.70 | 2.00 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.76 | 3.67 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.93 | 5.50 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.13 | 6.17 | 28.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.45 | 5.83 | 28.47 |
November | 3.33 | 18.42 | 0.17 | 18.50 | 3.17 | 22.91 | 3.17 | 24.48 |
December | 8.67 | 18.02 | 0.50 | 17.95 | 0.00 | 17.95 | 0.00 | 17.95 |
Annual Sum or Average | 26.83 | 18.33 | 0.83 | 18.33 | 33.17 | 23.58 | 31.33 | 25.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.95 | 0.00 | 17.95 |
Maximum of Months | 8.67 | 18.92 | 0.50 | 18.92 | 6.33 | 28.45 | 6.17 | 28.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.17 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 |
February | 4.67 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 |
March | 2.17 | 18.73 | 0.00 | 18.73 | 0.50 | 20.38 | 0.33 | 21.18 |
April | 0.17 | 19.07 | 0.00 | 19.07 | 4.83 | 28.17 | 3.50 | 28.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.79 | 4.67 | 28.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.84 | 4.00 | 28.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 28.69 | 5.17 | 28.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.90 | 4.00 | 29.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.42 | 3.33 | 28.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.04 | 2.00 | 28.06 |
November | 3.00 | 18.48 | 0.17 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
December | 7.17 | 18.25 | 0.00 | 18.25 | 0.00 | 18.25 | 0.00 | 18.25 |
Annual Sum or Average | 23.33 | 18.39 | 0.17 | 18.40 | 43.50 | 25.07 | 27.00 | 26.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.25 | 0.00 | 18.25 |
Maximum of Months | 7.17 | 19.07 | 0.17 | 19.07 | 9.67 | 28.90 | 5.17 | 29.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.57 | 2.67 | 27.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.59 | 5.00 | 27.59 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.57 | 1.33 | 27.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 82.17 | 27.59 | 17.50 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.59 | 0.00 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.56 | 0.83 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.57 | 8.00 | 27.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 104.50 | 27.59 | 35.33 | 27.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 82.17 | 27.59 | 17.50 | 27.59 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 314.50 | 23.56 | 82.50 | 24.09 | 0.00 | 24.09 |
February | 242.17 | 23.83 | 54.00 | 24.21 | 0.00 | 24.21 |
March | 270.17 | 23.85 | 59.00 | 24.22 | 0.00 | 24.22 |
April | 118.83 | 23.83 | 121.50 | 24.78 | 0.00 | 24.78 |
May | 24.33 | 23.72 | 230.67 | 24.94 | 0.00 | 24.94 |
June | 1.83 | 23.96 | 327.17 | 24.70 | 0.00 | 24.70 |
July | 12.33 | 26.83 | 494.00 | 24.69 | 12.33 | 24.74 |
August | 8.00 | 24.00 | 500.17 | 24.51 | 8.00 | 24.50 |
September | 20.17 | 26.49 | 451.83 | 24.70 | 19.67 | 24.78 |
October | 3.17 | 23.86 | 303.33 | 24.98 | 0.67 | 24.98 |
November | 68.50 | 23.79 | 154.67 | 25.16 | 0.00 | 25.16 |
December | 259.33 | 23.71 | 87.33 | 24.38 | 0.00 | 24.38 |
Annual Sum or Average | 1343.33 | 23.81 | 2866.17 | 24.58 | 40.67 | 24.60 |
Minimum of Months | 1.83 | 23.56 | 54.00 | 24.09 | 0.00 | 24.09 |
Maximum of Months | 314.50 | 26.83 | 500.17 | 25.16 | 19.67 | 25.16 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 211.50 | 23.78 | 48.00 | 24.09 | 0.00 | 24.09 |
February | 209.17 | 23.82 | 18.00 | 23.89 | 0.00 | 23.89 |
March | 190.50 | 23.90 | 30.50 | 24.18 | 0.00 | 24.18 |
April | 68.17 | 23.98 | 118.50 | 24.47 | 0.00 | 24.47 |
May | 31.67 | 23.95 | 226.50 | 24.41 | 14.50 | 24.39 |
June | 18.33 | 24.00 | 333.00 | 24.25 | 16.67 | 24.24 |
July | 129.33 | 24.36 | 495.33 | 24.24 | 129.33 | 24.26 |
August | 60.17 | 24.35 | 506.50 | 24.21 | 60.17 | 24.23 |
September | 114.33 | 24.49 | 443.33 | 24.36 | 113.83 | 24.38 |
October | 32.67 | 24.48 | 292.83 | 24.50 | 28.67 | 24.50 |
November | 89.33 | 23.90 | 111.50 | 24.54 | 0.00 | 24.54 |
December | 165.17 | 23.91 | 39.17 | 24.30 | 0.00 | 24.30 |
Annual Sum or Average | 1320.33 | 24.01 | 2663.17 | 24.28 | 363.17 | 24.29 |
Minimum of Months | 18.33 | 23.78 | 18.00 | 23.89 | 0.00 | 23.89 |
Maximum of Months | 211.50 | 24.49 | 506.50 | 24.54 | 129.33 | 24.54 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 411.00 | 23.50 | 0.00 | 23.50 | 0.00 | 23.50 |
February | 343.17 | 23.59 | 6.67 | 23.60 | 0.00 | 23.60 |
March | 340.17 | 23.69 | 1.67 | 23.69 | 0.00 | 23.69 |
April | 186.17 | 23.74 | 48.83 | 23.91 | 0.00 | 23.91 |
May | 88.17 | 23.79 | 174.33 | 24.20 | 12.83 | 24.19 |
June | 36.83 | 23.91 | 295.50 | 24.22 | 19.00 | 24.21 |
July | 185.17 | 24.18 | 486.67 | 24.17 | 185.17 | 24.17 |
August | 134.67 | 24.16 | 474.67 | 24.18 | 133.00 | 24.18 |
September | 128.17 | 24.21 | 415.00 | 24.21 | 119.33 | 24.22 |
October | 119.67 | 23.71 | 212.83 | 24.11 | 31.17 | 24.12 |
November | 279.67 | 23.60 | 44.17 | 23.71 | 0.00 | 23.71 |
December | 419.83 | 23.52 | 0.00 | 23.52 | 0.00 | 23.52 |
Annual Sum or Average | 2672.67 | 23.70 | 2160.33 | 23.94 | 500.50 | 23.97 |
Minimum of Months | 36.83 | 23.50 | 0.00 | 23.50 | 0.00 | 23.50 |
Maximum of Months | 419.83 | 24.21 | 486.67 | 24.22 | 185.17 | 24.22 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.17 | 21.93 | 101.33 | 21.63 | 101.33 | 21.42 |
February | 433.83 | 22.32 | 63.83 | 22.11 | 63.83 | 21.95 |
March | 428.50 | 22.77 | 24.33 | 22.67 | 24.33 | 22.59 |
April | 252.17 | 23.23 | 59.83 | 23.41 | 0.00 | 23.41 |
May | 118.00 | 23.44 | 227.17 | 23.99 | 17.83 | 23.99 |
June | 42.83 | 23.78 | 349.50 | 24.22 | 19.83 | 24.21 |
July | 198.83 | 24.20 | 493.50 | 24.22 | 197.50 | 24.22 |
August | 161.67 | 24.04 | 480.83 | 24.15 | 155.50 | 24.14 |
September | 190.17 | 23.87 | 388.33 | 24.06 | 146.17 | 24.07 |
October | 283.33 | 23.02 | 144.67 | 23.36 | 41.33 | 23.42 |
November | 424.00 | 22.29 | 78.00 | 22.16 | 57.67 | 22.00 |
December | 495.83 | 21.74 | 130.50 | 21.41 | 130.50 | 21.19 |
Annual Sum or Average | 3519.33 | 22.68 | 2541.83 | 23.08 | 955.83 | 23.02 |
Minimum of Months | 42.83 | 21.74 | 24.33 | 21.41 | 0.00 | 21.19 |
Maximum of Months | 495.83 | 24.20 | 493.50 | 24.22 | 197.50 | 24.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.00 | 22.17 | 34.33 | 22.10 | 34.33 | 22.03 |
February | 434.50 | 22.37 | 23.17 | 22.30 | 23.17 | 22.24 |
March | 437.33 | 22.76 | 9.00 | 22.73 | 9.00 | 22.69 |
April | 208.83 | 23.27 | 74.17 | 23.52 | 0.00 | 23.52 |
May | 75.33 | 23.39 | 265.33 | 24.15 | 0.50 | 24.15 |
June | 11.83 | 23.91 | 414.83 | 24.29 | 2.83 | 24.30 |
July | 80.33 | 24.89 | 495.33 | 24.39 | 80.33 | 24.45 |
August | 32.83 | 24.39 | 493.83 | 24.22 | 29.67 | 24.23 |
September | 113.83 | 23.96 | 389.67 | 24.16 | 74.33 | 24.20 |
October | 227.83 | 23.08 | 168.50 | 23.51 | 12.67 | 23.53 |
November | 424.50 | 22.61 | 11.00 | 22.64 | 1.33 | 22.63 |
December | 496.33 | 22.21 | 33.67 | 22.13 | 33.67 | 22.06 |
Annual Sum or Average | 3043.50 | 22.70 | 2412.83 | 23.32 | 301.83 | 23.33 |
Minimum of Months | 11.83 | 22.17 | 9.00 | 22.10 | 0.00 | 22.03 |
Maximum of Months | 500.00 | 24.89 | 495.33 | 24.39 | 80.33 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 463.67 | 22.10 | 38.33 | 22.06 | 32.50 | 22.00 |
February | 362.83 | 22.24 | 36.83 | 22.30 | 19.67 | 22.24 |
March | 345.50 | 22.43 | 53.17 | 22.64 | 10.00 | 22.60 |
April | 182.67 | 23.01 | 156.00 | 23.69 | 7.00 | 23.76 |
May | 93.17 | 23.68 | 330.17 | 24.26 | 16.50 | 24.37 |
June | 45.33 | 24.62 | 411.00 | 24.34 | 20.50 | 24.44 |
July | 83.67 | 25.12 | 479.67 | 24.38 | 75.83 | 24.50 |
August | 65.33 | 24.15 | 445.83 | 24.15 | 35.83 | 24.24 |
September | 113.17 | 24.16 | 387.67 | 24.26 | 62.83 | 24.39 |
October | 215.50 | 22.67 | 217.00 | 23.46 | 12.83 | 23.51 |
November | 380.67 | 22.35 | 33.67 | 22.52 | 3.33 | 22.51 |
December | 466.00 | 22.04 | 40.67 | 21.97 | 38.83 | 21.89 |
Annual Sum or Average | 2817.50 | 22.60 | 2630.00 | 23.36 | 335.67 | 23.41 |
Minimum of Months | 45.33 | 22.04 | 33.67 | 21.97 | 3.33 | 21.89 |
Maximum of Months | 466.00 | 25.12 | 479.67 | 24.38 | 75.83 | 24.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 302.50 | 22.16 | 123.83 | 22.68 | 30.50 | 22.63 |
February | 265.83 | 22.36 | 99.33 | 22.80 | 28.00 | 22.75 |
March | 288.83 | 22.57 | 83.33 | 22.94 | 10.83 | 22.88 |
April | 179.33 | 23.02 | 145.83 | 23.68 | 3.50 | 23.71 |
May | 106.67 | 23.12 | 267.17 | 24.01 | 2.00 | 24.02 |
June | 34.00 | 23.56 | 385.83 | 24.21 | 5.17 | 24.23 |
July | 84.33 | 24.80 | 491.50 | 24.32 | 83.33 | 24.38 |
August | 61.00 | 24.87 | 477.50 | 24.30 | 49.17 | 24.38 |
September | 122.33 | 24.44 | 407.50 | 24.39 | 82.50 | 24.51 |
October | 178.67 | 23.57 | 305.33 | 24.13 | 40.33 | 24.31 |
November | 263.17 | 22.75 | 170.33 | 23.44 | 23.17 | 23.52 |
December | 292.83 | 22.17 | 130.83 | 22.57 | 41.33 | 22.43 |
Annual Sum or Average | 2179.50 | 22.87 | 3088.33 | 23.69 | 399.83 | 23.73 |
Minimum of Months | 34.00 | 22.16 | 83.33 | 22.57 | 2.00 | 22.43 |
Maximum of Months | 302.50 | 24.87 | 491.50 | 24.39 | 83.33 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 407.67 | 22.12 | 42.33 | 22.29 | 8.67 | 22.26 |
February | 355.83 | 22.25 | 36.67 | 22.44 | 7.00 | 22.44 |
March | 297.83 | 22.68 | 99.00 | 23.11 | 4.83 | 23.15 |
April | 104.83 | 23.84 | 279.17 | 24.44 | 21.00 | 24.58 |
May | 100.00 | 23.78 | 340.00 | 24.35 | 23.00 | 24.48 |
June | 41.17 | 25.48 | 449.33 | 24.45 | 30.17 | 24.56 |
July | 105.33 | 25.53 | 495.83 | 24.61 | 105.33 | 24.74 |
August | 79.67 | 25.54 | 512.00 | 24.53 | 79.67 | 24.65 |
September | 103.33 | 24.41 | 416.00 | 24.34 | 70.50 | 24.46 |
October | 165.33 | 23.04 | 278.50 | 23.91 | 25.83 | 24.01 |
November | 306.50 | 22.60 | 108.67 | 23.07 | 1.17 | 23.09 |
December | 360.50 | 22.50 | 54.83 | 22.81 | 0.00 | 22.81 |
Annual Sum or Average | 2428.00 | 22.94 | 3112.33 | 23.77 | 377.17 | 23.89 |
Minimum of Months | 41.17 | 22.12 | 36.67 | 22.29 | 0.00 | 22.26 |
Maximum of Months | 407.67 | 25.54 | 512.00 | 24.61 | 105.33 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.09 | 215.00 | 20.91 | 215.00 | 20.81 |
February | 454.00 | 21.53 | 129.00 | 21.34 | 129.00 | 21.22 |
March | 496.50 | 22.08 | 75.67 | 21.91 | 75.67 | 21.78 |
April | 323.00 | 22.78 | 48.00 | 22.90 | 6.67 | 22.86 |
May | 129.67 | 23.17 | 220.17 | 23.87 | 2.33 | 23.87 |
June | 24.50 | 23.55 | 385.00 | 24.30 | 5.50 | 24.31 |
July | 120.17 | 24.32 | 494.33 | 24.31 | 120.17 | 24.31 |
August | 91.33 | 23.74 | 471.67 | 24.12 | 73.00 | 24.10 |
September | 179.33 | 23.38 | 352.00 | 23.83 | 91.17 | 23.84 |
October | 355.50 | 22.54 | 106.67 | 22.86 | 22.50 | 22.89 |
November | 478.83 | 21.58 | 101.33 | 21.38 | 101.33 | 21.24 |
December | 497.00 | 20.96 | 248.50 | 20.79 | 248.50 | 20.70 |
Annual Sum or Average | 3651.83 | 21.99 | 2847.33 | 22.53 | 1090.83 | 22.39 |
Minimum of Months | 24.50 | 20.96 | 48.00 | 20.79 | 2.33 | 20.70 |
Maximum of Months | 502.00 | 24.32 | 494.33 | 24.31 | 248.50 | 24.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 424.00 | 21.38 | 128.33 | 21.17 | 128.33 | 21.04 |
February | 352.00 | 21.76 | 66.67 | 21.65 | 60.50 | 21.52 |
March | 335.67 | 22.00 | 58.83 | 22.06 | 38.67 | 21.95 |
April | 196.17 | 22.70 | 115.00 | 23.41 | 9.17 | 23.46 |
May | 114.50 | 23.48 | 254.83 | 24.20 | 18.00 | 24.33 |
June | 52.17 | 24.63 | 335.83 | 24.52 | 23.83 | 24.66 |
July | 111.83 | 25.01 | 411.67 | 24.55 | 109.17 | 24.64 |
August | 93.17 | 24.12 | 373.67 | 24.28 | 64.00 | 24.35 |
September | 141.17 | 23.68 | 299.50 | 24.09 | 68.33 | 24.19 |
October | 240.67 | 22.24 | 140.33 | 22.97 | 13.50 | 23.00 |
November | 370.33 | 21.75 | 60.33 | 21.70 | 47.00 | 21.58 |
December | 422.00 | 21.30 | 150.17 | 21.08 | 150.17 | 20.94 |
Annual Sum or Average | 2853.67 | 22.19 | 2395.17 | 22.89 | 730.67 | 22.84 |
Minimum of Months | 52.17 | 21.30 | 58.83 | 21.08 | 9.17 | 20.94 |
Maximum of Months | 424.00 | 25.01 | 411.67 | 24.55 | 150.17 | 24.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 315.17 | 21.86 | 174.83 | 22.24 | 77.17 | 22.06 |
February | 276.33 | 22.11 | 129.67 | 22.55 | 53.00 | 22.45 |
March | 311.33 | 22.28 | 102.50 | 22.55 | 39.00 | 22.40 |
April | 226.83 | 22.71 | 122.00 | 23.29 | 7.33 | 23.27 |
May | 141.33 | 22.97 | 230.00 | 23.81 | 2.17 | 23.81 |
June | 51.00 | 23.27 | 364.83 | 24.20 | 5.83 | 24.19 |
July | 130.83 | 24.24 | 487.33 | 24.25 | 129.83 | 24.25 |
August | 105.33 | 24.04 | 467.83 | 24.20 | 83.00 | 24.22 |
September | 153.67 | 24.03 | 398.67 | 24.24 | 100.00 | 24.32 |
October | 210.00 | 23.24 | 282.17 | 23.94 | 42.83 | 24.11 |
November | 286.50 | 22.43 | 186.33 | 23.09 | 48.17 | 23.10 |
December | 311.83 | 21.81 | 166.00 | 22.10 | 81.00 | 21.89 |
Annual Sum or Average | 2520.17 | 22.63 | 3112.17 | 23.42 | 669.33 | 23.39 |
Minimum of Months | 51.00 | 21.81 | 102.50 | 22.10 | 2.17 | 21.89 |
Maximum of Months | 315.17 | 24.24 | 487.33 | 24.25 | 129.83 | 24.32 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 463.33 | 21.29 | 139.83 | 21.15 | 136.00 | 21.05 |
February | 400.33 | 21.53 | 86.83 | 21.48 | 77.50 | 21.38 |
March | 403.50 | 21.87 | 87.67 | 22.03 | 43.00 | 21.94 |
April | 277.50 | 22.54 | 131.50 | 23.14 | 12.33 | 23.20 |
May | 175.50 | 23.12 | 269.67 | 23.93 | 20.67 | 24.07 |
June | 82.17 | 23.74 | 372.83 | 24.30 | 19.17 | 24.40 |
July | 122.67 | 24.61 | 475.83 | 24.31 | 117.33 | 24.37 |
August | 106.00 | 23.91 | 441.00 | 24.18 | 69.00 | 24.24 |
September | 166.00 | 23.15 | 359.67 | 23.79 | 79.83 | 23.84 |
October | 305.00 | 22.36 | 174.50 | 23.01 | 22.17 | 23.08 |
November | 414.00 | 21.58 | 92.50 | 21.63 | 59.50 | 21.52 |
December | 467.00 | 21.27 | 148.00 | 21.09 | 148.00 | 20.97 |
Annual Sum or Average | 3383.00 | 22.07 | 2779.83 | 22.79 | 804.50 | 22.75 |
Minimum of Months | 82.17 | 21.27 | 86.83 | 21.09 | 12.33 | 20.97 |
Maximum of Months | 467.00 | 24.61 | 475.83 | 24.31 | 148.00 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.41 | 328.17 | 20.23 | 328.17 | 20.15 |
February | 454.00 | 20.88 | 237.33 | 20.67 | 237.33 | 20.56 |
March | 498.00 | 21.46 | 159.33 | 21.23 | 159.33 | 21.08 |
April | 348.00 | 22.23 | 92.50 | 22.31 | 40.83 | 22.18 |
May | 178.00 | 22.64 | 226.83 | 23.53 | 7.50 | 23.52 |
June | 63.83 | 23.37 | 387.00 | 24.19 | 13.50 | 24.22 |
July | 175.50 | 24.11 | 484.50 | 24.19 | 172.50 | 24.18 |
August | 153.00 | 23.35 | 441.67 | 23.89 | 112.33 | 23.85 |
September | 237.83 | 22.87 | 334.17 | 23.45 | 119.67 | 23.45 |
October | 392.00 | 21.90 | 110.50 | 22.19 | 44.67 | 22.17 |
November | 484.83 | 20.86 | 219.00 | 20.57 | 219.00 | 20.42 |
December | 497.00 | 20.30 | 365.83 | 20.16 | 365.83 | 20.10 |
Annual Sum or Average | 3984.00 | 21.51 | 3386.83 | 21.96 | 1820.67 | 21.78 |
Minimum of Months | 63.83 | 20.30 | 92.50 | 20.16 | 7.50 | 20.10 |
Maximum of Months | 502.00 | 24.11 | 484.50 | 24.19 | 365.83 | 24.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.72 | 244.50 | 20.45 | 244.50 | 20.32 |
February | 435.83 | 21.35 | 140.50 | 21.08 | 140.50 | 20.91 |
March | 391.17 | 21.70 | 96.00 | 21.54 | 90.17 | 21.39 |
April | 205.67 | 22.43 | 172.00 | 23.22 | 20.83 | 23.17 |
May | 129.17 | 23.43 | 325.83 | 24.14 | 28.00 | 24.27 |
June | 69.67 | 24.68 | 420.33 | 24.48 | 36.17 | 24.63 |
July | 170.17 | 24.72 | 487.50 | 24.46 | 166.50 | 24.52 |
August | 141.00 | 24.00 | 466.00 | 24.14 | 117.83 | 24.17 |
September | 186.50 | 23.57 | 376.50 | 23.97 | 110.67 | 24.04 |
October | 282.67 | 21.94 | 181.33 | 22.69 | 35.67 | 22.66 |
November | 452.33 | 21.29 | 149.00 | 21.07 | 137.33 | 20.88 |
December | 497.00 | 20.57 | 276.50 | 20.36 | 276.50 | 20.26 |
Annual Sum or Average | 3463.17 | 21.83 | 3336.00 | 22.48 | 1404.67 | 22.35 |
Minimum of Months | 69.67 | 20.57 | 96.00 | 20.36 | 20.83 | 20.26 |
Maximum of Months | 502.00 | 24.72 | 487.50 | 24.48 | 276.50 | 24.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 352.83 | 21.10 | 219.00 | 21.18 | 153.00 | 20.92 |
February | 300.00 | 21.37 | 173.00 | 21.54 | 118.67 | 21.32 |
March | 336.00 | 21.71 | 166.00 | 21.86 | 101.50 | 21.64 |
April | 254.17 | 22.26 | 160.83 | 22.82 | 37.17 | 22.71 |
May | 178.83 | 22.67 | 243.67 | 23.59 | 13.50 | 23.62 |
June | 87.17 | 23.24 | 364.67 | 24.13 | 16.50 | 24.17 |
July | 191.83 | 24.08 | 476.00 | 24.17 | 180.50 | 24.17 |
August | 159.17 | 23.67 | 449.17 | 24.03 | 118.83 | 24.04 |
September | 203.00 | 23.56 | 383.33 | 23.96 | 124.83 | 24.02 |
October | 257.83 | 22.62 | 260.00 | 23.47 | 53.50 | 23.60 |
November | 307.83 | 21.46 | 223.50 | 21.98 | 99.00 | 21.73 |
December | 358.17 | 21.10 | 227.50 | 21.10 | 174.67 | 20.86 |
Annual Sum or Average | 2986.83 | 22.12 | 3346.67 | 22.83 | 1191.67 | 22.70 |
Minimum of Months | 87.17 | 21.10 | 160.83 | 21.10 | 13.50 | 20.86 |
Maximum of Months | 358.17 | 24.08 | 476.00 | 24.17 | 180.50 | 24.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 471.83 | 20.86 | 234.50 | 20.64 | 230.00 | 20.51 |
February | 410.17 | 21.17 | 170.67 | 21.00 | 164.00 | 20.88 |
March | 408.33 | 21.49 | 163.67 | 21.58 | 113.83 | 21.42 |
April | 288.83 | 22.20 | 155.33 | 22.84 | 29.67 | 22.85 |
May | 200.17 | 22.81 | 268.50 | 23.74 | 27.00 | 23.88 |
June | 115.00 | 23.40 | 373.00 | 24.17 | 33.00 | 24.27 |
July | 212.67 | 24.00 | 472.67 | 24.10 | 198.50 | 24.10 |
August | 184.17 | 23.42 | 442.67 | 23.89 | 132.83 | 23.90 |
September | 234.17 | 22.93 | 357.17 | 23.52 | 133.83 | 23.53 |
October | 329.83 | 21.99 | 174.83 | 22.69 | 34.83 | 22.74 |
November | 420.67 | 21.11 | 168.17 | 21.02 | 139.00 | 20.84 |
December | 478.33 | 20.81 | 258.50 | 20.57 | 258.50 | 20.45 |
Annual Sum or Average | 3754.17 | 21.80 | 3239.67 | 22.39 | 1495.00 | 22.27 |
Minimum of Months | 115.00 | 20.81 | 155.33 | 20.57 | 27.00 | 20.45 |
Maximum of Months | 478.33 | 24.00 | 472.67 | 24.17 | 258.50 | 24.27 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 27.00 | 502.00 | 27.00 | 2.33 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 4.00 | 27.00 | 514.00 | 27.00 | 4.00 | 27.00 |
April | 114.00 | 27.00 | 485.00 | 27.00 | 114.00 | 27.00 |
May | 62.17 | 27.00 | 508.00 | 27.00 | 62.17 | 27.00 |
June | 185.17 | 27.00 | 496.00 | 27.00 | 185.17 | 27.00 |
July | 341.50 | 27.00 | 497.00 | 27.00 | 341.50 | 27.00 |
August | 439.33 | 27.00 | 514.00 | 27.00 | 439.33 | 27.00 |
September | 160.67 | 27.00 | 485.00 | 27.00 | 160.67 | 27.00 |
October | 109.50 | 27.00 | 502.00 | 27.00 | 109.50 | 27.00 |
November | 45.33 | 27.00 | 489.00 | 27.00 | 45.33 | 27.00 |
December | 22.67 | 27.00 | 497.00 | 27.00 | 22.67 | 27.00 |
Annual Sum or Average | 1486.67 | 27.00 | 5943.00 | 27.00 | 1486.67 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 439.33 | 27.00 | 514.00 | 27.00 | 439.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 478.50 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 440.33 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 513.00 | 27.00 | 0.00 | 27.00 |
April | 24.83 | 27.00 | 485.00 | 27.00 | 24.83 | 27.00 |
May | 27.33 | 27.00 | 508.00 | 27.00 | 27.33 | 27.00 |
June | 77.33 | 27.00 | 496.00 | 27.00 | 77.33 | 27.00 |
July | 177.83 | 27.00 | 497.00 | 27.00 | 177.83 | 27.00 |
August | 189.33 | 27.00 | 514.00 | 27.00 | 189.33 | 27.00 |
September | 79.00 | 27.00 | 485.00 | 27.00 | 79.00 | 27.00 |
October | 31.33 | 27.00 | 502.00 | 27.00 | 31.33 | 27.00 |
November | 9.17 | 27.00 | 486.00 | 27.00 | 9.17 | 27.00 |
December | 0.00 | 0.00 | 480.50 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 616.17 | 27.00 | 5885.33 | 27.00 | 616.17 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 440.33 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 189.33 | 27.00 | 514.00 | 27.00 | 189.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.17 | 26.76 | 366.00 | 26.99 | 0.00 | 26.99 |
February | 3.17 | 27.00 | 333.67 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 457.17 | 27.00 | 0.00 | 27.00 |
April | 49.17 | 27.00 | 477.33 | 27.00 | 49.17 | 27.00 |
May | 90.83 | 27.00 | 508.00 | 27.00 | 90.83 | 27.00 |
June | 173.17 | 27.00 | 496.00 | 27.00 | 173.17 | 27.00 |
July | 234.83 | 27.00 | 497.00 | 27.00 | 234.83 | 27.00 |
August | 234.67 | 27.00 | 514.00 | 27.00 | 234.67 | 27.00 |
September | 133.00 | 27.00 | 485.00 | 27.00 | 133.00 | 27.00 |
October | 60.33 | 27.00 | 502.00 | 27.00 | 60.33 | 27.00 |
November | 15.50 | 27.00 | 424.83 | 27.00 | 12.00 | 27.00 |
December | 23.83 | 27.00 | 360.67 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 1033.67 | 27.00 | 5421.67 | 27.00 | 988.00 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 333.67 | 26.99 | 0.00 | 26.99 |
Maximum of Months | 234.83 | 27.00 | 514.00 | 27.00 | 234.83 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.17 | 27.20 | 502.00 | 27.20 | 487.17 | 27.20 |
February | 22.17 | 27.27 | 450.00 | 24.66 | 21.67 | 24.78 |
March | 199.33 | 26.58 | 511.33 | 25.80 | 198.83 | 25.97 |
April | 420.67 | 26.84 | 485.00 | 26.61 | 420.67 | 26.68 |
May | 506.67 | 27.11 | 508.00 | 27.11 | 506.67 | 27.11 |
June | 481.00 | 26.97 | 495.67 | 26.93 | 481.00 | 26.95 |
July | 497.00 | 26.98 | 497.00 | 26.98 | 497.00 | 26.98 |
August | 514.00 | 26.99 | 514.00 | 26.99 | 514.00 | 26.99 |
September | 485.00 | 27.02 | 485.00 | 27.02 | 485.00 | 27.02 |
October | 254.50 | 26.86 | 498.17 | 26.06 | 253.33 | 26.27 |
November | 254.17 | 25.90 | 484.17 | 25.53 | 251.83 | 25.64 |
December | 189.00 | 25.48 | 497.00 | 24.63 | 189.00 | 24.81 |
Annual Sum or Average | 4310.67 | 26.86 | 5927.33 | 26.46 | 4306.17 | 26.58 |
Minimum of Months | 22.17 | 25.48 | 450.00 | 24.63 | 21.67 | 24.78 |
Maximum of Months | 514.00 | 27.27 | 514.00 | 27.20 | 514.00 | 27.20 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 20.94581 | 0.76894 | 17.61477 |
February | 454.00000 | 27.00000 | 18.01233 | 0.76368 | 17.47210 |
March | 514.00000 | 27.00000 | 18.73389 | 0.82898 | 19.63925 |
April | 485.00000 | 27.00000 | 21.31516 | 0.93073 | 23.43459 |
May | 508.00000 | 27.00006 | 28.01463 | 0.25921 | 6.58636 |
June | 496.00000 | 27.00006 | 30.66520 | 0.34142 | 7.57522 |
July | 497.00000 | 27.00007 | 36.04734 | 0.42630 | 8.88963 |
August | 514.00000 | 27.00032 | 34.23208 | 0.45270 | 9.37538 |
September | 485.00000 | 27.00030 | 35.16570 | 0.32441 | 7.34553 |
October | 502.00000 | 27.00007 | 31.17600 | 0.93874 | 23.73500 |
November | 489.00000 | 27.00000 | 22.84804 | 0.86036 | 20.81875 |
December | 497.00000 | 27.00000 | 18.17384 | 0.82776 | 19.60947 |
Annual Sum or Average | 5943.00000 | 27.00007 | 26.33728 | 0.64218 | 15.14040 |
Minimum of Months | 454.00000 | 27.00000 | 18.01233 | 0.25921 | 6.58636 |
Maximum of Months | 514.00000 | 27.00032 | 36.04734 | 0.93874 | 23.73500 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 20.94116 | 0.68229 | 14.97075 |
February | 454.00000 | 27.00000 | 18.00902 | 0.69273 | 15.31480 |
March | 514.00000 | 27.00000 | 18.72464 | 0.74675 | 16.91876 |
April | 485.00000 | 27.00000 | 21.30627 | 0.82812 | 19.67585 |
May | 508.00000 | 27.00006 | 28.00048 | 0.19463 | 6.04369 |
June | 496.00000 | 27.00006 | 30.65263 | 0.27078 | 6.70594 |
July | 497.00000 | 27.00008 | 36.09655 | 0.33046 | 7.41106 |
August | 514.00000 | 27.00035 | 34.27137 | 0.33367 | 7.47005 |
September | 485.00000 | 27.00030 | 35.22686 | 0.25162 | 6.52889 |
October | 502.00000 | 27.00007 | 31.18053 | 0.86944 | 21.11162 |
November | 489.00000 | 27.00000 | 22.84488 | 0.76299 | 17.52418 |
December | 497.00000 | 27.00000 | 18.15709 | 0.69728 | 15.44751 |
Annual Sum or Average | 5943.00000 | 27.00008 | 26.34408 | 0.55352 | 12.89547 |
Minimum of Months | 454.00000 | 27.00000 | 18.00902 | 0.19463 | 6.04369 |
Maximum of Months | 514.00000 | 27.00035 | 36.09655 | 0.86944 | 21.11162 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99366 | 20.95521 | 0.60322 | 13.01795 |
February | 454.00000 | 27.00000 | 18.01577 | 0.62717 | 13.68827 |
March | 514.00000 | 27.00000 | 18.73341 | 0.70200 | 15.76091 |
April | 485.00000 | 27.00000 | 21.32464 | 0.81625 | 19.44734 |
May | 508.00000 | 27.00006 | 28.02165 | 0.20840 | 6.41122 |
June | 496.00000 | 27.00006 | 30.67395 | 0.30397 | 7.27180 |
July | 497.00000 | 27.00008 | 36.09707 | 0.36463 | 8.05037 |
August | 514.00000 | 27.00031 | 34.36079 | 0.35454 | 7.94326 |
September | 485.00000 | 27.00030 | 35.22625 | 0.25645 | 6.82256 |
October | 502.00000 | 27.00008 | 31.20719 | 0.84249 | 20.30000 |
November | 489.00000 | 27.00000 | 22.85189 | 0.69469 | 15.65833 |
December | 497.00000 | 27.00000 | 18.17296 | 0.60562 | 13.14293 |
Annual Sum or Average | 5943.00000 | 26.99954 | 26.36351 | 0.53043 | 12.26967 |
Minimum of Months | 454.00000 | 26.99366 | 18.01577 | 0.20840 | 6.41122 |
Maximum of Months | 514.00000 | 27.00031 | 36.09707 | 0.84249 | 20.30000 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.19404 | 29.56932 | 1.09942 | 30.51573 |
February | 454.00000 | 24.51354 | 25.82372 | 0.64317 | 14.04534 |
March | 514.00000 | 25.46508 | 21.55846 | 0.89752 | 22.90047 |
April | 485.00000 | 26.40864 | 23.51380 | 1.30552 | 41.39944 |
May | 508.00000 | 27.10570 | 31.80086 | 0.54772 | 11.36972 |
June | 496.00000 | 26.89417 | 35.80605 | 0.73807 | 16.90552 |
July | 497.00000 | 26.98414 | 47.91985 | 1.08777 | 30.01345 |
August | 514.00000 | 26.98932 | 44.01823 | 1.26551 | 38.54835 |
September | 485.00000 | 27.02360 | 43.50951 | 0.70544 | 15.63383 |
October | 502.00000 | 25.60866 | 35.79313 | 1.01579 | 28.18240 |
November | 489.00000 | 25.29228 | 25.45285 | 0.94095 | 24.49194 |
December | 497.00000 | 24.31074 | 23.25834 | 0.90324 | 22.95843 |
Annual Sum or Average | 5943.00000 | 26.16237 | 32.38857 | 0.93134 | 24.82810 |
Minimum of Months | 454.00000 | 24.31074 | 21.55846 | 0.54772 | 11.36972 |
Maximum of Months | 514.00000 | 27.19404 | 47.91985 | 1.30552 | 41.39944 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.14785 | 19.05976 | 0.27089 | 7.24770 |
February | 454.00000 | 24.30344 | 16.85090 | 0.28172 | 7.05310 |
March | 514.00000 | 24.25272 | 16.48532 | 0.27306 | 6.85503 |
April | 485.00000 | 24.42164 | 20.67252 | 0.34830 | 8.00790 |
May | 508.00000 | 24.47598 | 29.80229 | -0.4185 | 9.69824 |
June | 496.00000 | 24.46724 | 35.37092 | -0.3706 | 8.78233 |
July | 497.00000 | 24.63421 | 45.43088 | -0.2407 | 7.46139 |
August | 514.00000 | 24.50494 | 43.93013 | -0.2735 | 7.45929 |
September | 485.00000 | 24.57702 | 42.26313 | -0.2631 | 7.80710 |
October | 502.00000 | 24.56883 | 34.55685 | 0.50252 | 11.08764 |
November | 489.00000 | 24.48613 | 21.44106 | 0.38288 | 8.74140 |
December | 497.00000 | 24.30684 | 16.12843 | 0.29413 | 7.36423 |
Annual Sum or Average | 5943.00000 | 24.42912 | 28.58933 | 0.06303 | 8.13729 |
Minimum of Months | 454.00000 | 24.14785 | 16.12843 | -0.4185 | 6.85503 |
Maximum of Months | 514.00000 | 24.63421 | 45.43088 | 0.50252 | 11.08764 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.16497 | 19.95033 | 0.27459 | 6.89920 |
February | 454.00000 | 24.11372 | 17.02950 | 0.24951 | 6.52968 |
March | 514.00000 | 24.16662 | 16.38010 | 0.27240 | 6.73133 |
April | 485.00000 | 24.24946 | 21.18964 | 0.34869 | 7.76866 |
May | 508.00000 | 24.23750 | 31.63728 | -0.4424 | 9.58988 |
June | 496.00000 | 24.19399 | 38.37130 | -0.3909 | 8.55423 |
July | 497.00000 | 24.21217 | 53.27469 | -0.2765 | 6.78783 |
August | 514.00000 | 24.19222 | 50.50998 | -0.2913 | 6.96598 |
September | 485.00000 | 24.29961 | 47.52197 | -0.3030 | 7.45333 |
October | 502.00000 | 24.29321 | 37.12313 | 0.46252 | 9.86620 |
November | 489.00000 | 24.29276 | 21.78414 | 0.33938 | 7.68369 |
December | 497.00000 | 24.28832 | 16.77473 | 0.29053 | 7.02358 |
Annual Sum or Average | 5943.00000 | 24.22567 | 31.07182 | 0.04207 | 7.66279 |
Minimum of Months | 454.00000 | 24.11372 | 16.38010 | -0.4424 | 6.52968 |
Maximum of Months | 514.00000 | 24.29961 | 53.27469 | 0.46252 | 9.86620 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.61067 | 21.42731 | 0.12128 | 5.73039 |
February | 454.00000 | 23.73740 | 17.93205 | 0.14035 | 5.82637 |
March | 514.00000 | 23.88590 | 17.22796 | 0.18317 | 5.95638 |
April | 485.00000 | 24.03660 | 21.77892 | 0.26742 | 6.77788 |
May | 508.00000 | 24.11867 | 31.86233 | -0.5093 | 10.92324 |
June | 496.00000 | 24.15568 | 38.32363 | -0.4371 | 9.39037 |
July | 497.00000 | 24.16253 | 53.47880 | -0.3349 | 7.63682 |
August | 514.00000 | 24.16217 | 50.56702 | -0.3523 | 7.89960 |
September | 485.00000 | 24.16614 | 47.88265 | -0.3804 | 8.44913 |
October | 502.00000 | 24.04718 | 37.96863 | 0.37879 | 8.33132 |
November | 489.00000 | 23.86872 | 23.04973 | 0.21126 | 6.35306 |
December | 497.00000 | 23.61625 | 18.29442 | 0.10181 | 5.65550 |
Annual Sum or Average | 5943.00000 | 23.96558 | 31.75628 | -0.0530 | 7.42567 |
Minimum of Months | 454.00000 | 23.61067 | 17.22796 | -0.5093 | 5.65550 |
Maximum of Months | 514.00000 | 24.16614 | 53.47880 | 0.37879 | 10.92324 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.97381 | 23.73008 | -0.2873 | 8.84828 |
February | 454.00000 | 22.39786 | 19.43590 | -0.1935 | 7.67415 |
March | 514.00000 | 22.97323 | 18.44469 | -0.0412 | 6.51149 |
April | 485.00000 | 23.65695 | 22.20788 | 0.18674 | 6.69612 |
May | 508.00000 | 24.01311 | 32.17408 | -0.5126 | 11.51958 |
June | 496.00000 | 24.17012 | 38.42119 | -0.3831 | 8.67026 |
July | 497.00000 | 24.22863 | 53.48077 | -0.2657 | 6.91600 |
August | 514.00000 | 24.15493 | 50.93565 | -0.3171 | 7.58064 |
September | 485.00000 | 24.02414 | 48.62273 | -0.4025 | 9.31060 |
October | 502.00000 | 23.45240 | 39.54089 | 0.23978 | 7.33480 |
November | 489.00000 | 22.51776 | 24.82201 | -0.1269 | 7.60940 |
December | 497.00000 | 21.74918 | 20.31829 | -0.3640 | 10.35635 |
Annual Sum or Average | 5943.00000 | 23.28302 | 32.78104 | -0.2063 | 8.25717 |
Minimum of Months | 454.00000 | 21.74918 | 18.44469 | -0.5126 | 6.51149 |
Maximum of Months | 514.00000 | 24.22863 | 53.48077 | 0.23978 | 11.51958 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.17841 | 21.11854 | -0.2195 | 7.06352 |
February | 454.00000 | 22.44231 | 18.04960 | -0.1653 | 6.80025 |
March | 514.00000 | 22.94811 | 16.88727 | -0.0345 | 6.14305 |
April | 485.00000 | 23.76430 | 21.06115 | 0.22818 | 6.90820 |
May | 508.00000 | 24.11676 | 30.81426 | -0.4533 | 10.36711 |
June | 496.00000 | 24.24456 | 37.40158 | -0.3059 | 7.56292 |
July | 497.00000 | 24.30096 | 52.45205 | -0.1856 | 6.25919 |
August | 514.00000 | 24.17562 | 49.90900 | -0.2633 | 6.99110 |
September | 485.00000 | 24.07613 | 47.42205 | -0.3621 | 8.80792 |
October | 502.00000 | 23.59952 | 37.97855 | 0.28649 | 7.64651 |
November | 489.00000 | 22.78855 | 22.91939 | -0.0425 | 6.21357 |
December | 497.00000 | 22.21609 | 18.13501 | -0.2281 | 7.13043 |
Annual Sum or Average | 5943.00000 | 23.41119 | 31.28101 | -0.1460 | 7.32892 |
Minimum of Months | 454.00000 | 22.17841 | 16.88727 | -0.4533 | 6.14305 |
Maximum of Months | 514.00000 | 24.30096 | 52.45205 | 0.28649 | 10.36711 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.26262 | 20.66799 | -0.1678 | 7.21399 |
February | 454.00000 | 22.63389 | 17.50842 | -0.0760 | 7.06783 |
March | 514.00000 | 23.00708 | 16.40928 | 0.03433 | 7.00203 |
April | 485.00000 | 23.73954 | 20.85418 | 0.29145 | 8.45945 |
May | 508.00000 | 24.11339 | 30.63467 | -0.3516 | 10.02023 |
June | 496.00000 | 24.16965 | 37.45921 | -0.2377 | 7.98557 |
July | 497.00000 | 24.20141 | 52.65064 | -0.1401 | 7.32177 |
August | 514.00000 | 23.99177 | 50.36529 | -0.2424 | 8.16650 |
September | 485.00000 | 24.04586 | 47.22976 | -0.2710 | 9.05838 |
October | 502.00000 | 23.46572 | 38.02432 | 0.31010 | 8.84182 |
November | 489.00000 | 22.75522 | 22.68189 | -0.0051 | 6.80037 |
December | 497.00000 | 22.18568 | 17.80071 | -0.2062 | 7.47153 |
Annual Sum or Average | 5943.00000 | 23.38620 | 31.12959 | -0.0894 | 7.95732 |
Minimum of Months | 454.00000 | 22.18568 | 16.40928 | -0.3516 | 6.80037 |
Maximum of Months | 514.00000 | 24.20141 | 52.65064 | 0.31010 | 10.02023 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.01464 | 19.77835 | 0.04687 | 8.58911 |
February | 454.00000 | 23.17171 | 16.96554 | 0.07249 | 8.26896 |
March | 514.00000 | 23.30086 | 16.14198 | 0.10509 | 7.59362 |
April | 485.00000 | 23.79221 | 20.86642 | 0.27376 | 8.18736 |
May | 508.00000 | 24.00771 | 30.94393 | -0.4715 | 11.46641 |
June | 496.00000 | 24.14746 | 37.62126 | -0.3381 | 8.28163 |
July | 497.00000 | 24.22803 | 52.66615 | -0.2014 | 6.73394 |
August | 514.00000 | 24.15518 | 49.91101 | -0.2271 | 7.30021 |
September | 485.00000 | 24.20552 | 46.86038 | -0.2234 | 8.53737 |
October | 502.00000 | 23.93323 | 36.87408 | 0.45001 | 11.60336 |
November | 489.00000 | 23.45183 | 21.68000 | 0.20053 | 9.12028 |
December | 497.00000 | 23.05226 | 16.86294 | 0.03923 | 8.45662 |
Annual Sum or Average | 5943.00000 | 23.70830 | 30.70465 | -0.0245 | 8.68245 |
Minimum of Months | 454.00000 | 23.01464 | 16.14198 | -0.4715 | 6.73394 |
Maximum of Months | 514.00000 | 24.22803 | 52.66615 | 0.45001 | 11.60336 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.51680 | 20.12565 | -0.0660 | 6.94932 |
February | 454.00000 | 22.69077 | 17.33495 | -0.0275 | 6.99325 |
March | 514.00000 | 23.33129 | 15.94445 | 0.15983 | 7.42877 |
April | 485.00000 | 24.21591 | 20.19401 | 0.47071 | 11.23683 |
May | 508.00000 | 24.13755 | 30.55591 | -0.2919 | 9.90306 |
June | 496.00000 | 24.28369 | 37.15999 | -0.1265 | 7.43914 |
July | 497.00000 | 24.40780 | 51.92256 | 0.02546 | 6.87893 |
August | 514.00000 | 24.36567 | 49.15020 | 0.00308 | 6.75944 |
September | 485.00000 | 24.12486 | 47.05686 | -0.1871 | 8.46260 |
October | 502.00000 | 23.77863 | 37.18711 | 0.43250 | 10.82411 |
November | 489.00000 | 23.19801 | 21.80757 | 0.14997 | 7.33071 |
December | 497.00000 | 23.01660 | 16.75710 | 0.04539 | 6.79355 |
Annual Sum or Average | 5943.00000 | 23.67891 | 30.53472 | 0.04884 | 8.08425 |
Minimum of Months | 454.00000 | 22.51680 | 15.94445 | -0.2919 | 6.75944 |
Maximum of Months | 514.00000 | 24.40780 | 51.92256 | 0.47071 | 11.23683 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.09241 | 22.70759 | -0.5071 | 11.38478 |
February | 454.00000 | 21.52930 | 19.32978 | -0.4045 | 9.76231 |
March | 514.00000 | 22.14424 | 17.86360 | -0.2460 | 7.83144 |
April | 485.00000 | 23.20587 | 21.67207 | 0.07144 | 6.64997 |
May | 508.00000 | 23.92902 | 30.78827 | -0.5415 | 12.68702 |
June | 496.00000 | 24.24047 | 37.10280 | -0.3381 | 8.07936 |
July | 497.00000 | 24.30270 | 52.67073 | -0.2204 | 6.59294 |
August | 514.00000 | 24.12427 | 49.94417 | -0.3255 | 7.95465 |
September | 485.00000 | 23.81706 | 48.08168 | -0.4756 | 11.25331 |
October | 502.00000 | 22.94899 | 39.53329 | 0.11565 | 6.80262 |
November | 489.00000 | 21.62890 | 24.60810 | -0.3365 | 9.09420 |
December | 497.00000 | 20.96177 | 19.75873 | -0.5624 | 12.81519 |
Annual Sum or Average | 5943.00000 | 22.83752 | 32.10140 | -0.3140 | 9.23853 |
Minimum of Months | 454.00000 | 20.96177 | 17.86360 | -0.5624 | 6.59294 |
Maximum of Months | 514.00000 | 24.30270 | 52.67073 | 0.11565 | 12.81519 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.39392 | 21.88110 | -0.4047 | 9.97154 |
February | 385.00000 | 21.99013 | 18.04608 | -0.2548 | 8.61366 |
March | 433.00000 | 22.52523 | 16.72401 | -0.1064 | 7.79278 |
April | 410.00000 | 23.53046 | 20.71416 | 0.21660 | 8.40835 |
May | 430.00000 | 24.04960 | 30.10962 | -0.4008 | 11.71698 |
June | 418.00000 | 24.28893 | 36.45791 | -0.2304 | 8.40699 |
July | 422.00000 | 24.39126 | 51.99224 | -0.1070 | 7.72223 |
August | 433.00000 | 24.11131 | 49.38257 | -0.2407 | 8.80297 |
September | 410.00000 | 23.91105 | 47.18890 | -0.3486 | 10.92522 |
October | 427.00000 | 23.04444 | 38.88579 | 0.18779 | 8.11751 |
November | 417.00000 | 22.01917 | 23.38891 | -0.2059 | 8.17131 |
December | 422.00000 | 21.29986 | 18.81617 | -0.4531 | 10.91208 |
Annual Sum or Average | 5034.00000 | 23.05200 | 31.22377 | -0.1959 | 9.13320 |
Minimum of Months | 385.00000 | 21.29986 | 16.72401 | -0.4531 | 7.72223 |
Maximum of Months | 433.00000 | 24.39126 | 51.99224 | 0.21660 | 11.71698 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.76662 | 20.26530 | -0.0177 | 9.45681 |
February | 454.00000 | 22.98437 | 17.47950 | 0.02405 | 9.05253 |
March | 514.00000 | 23.07212 | 16.49564 | 0.03938 | 8.01670 |
April | 485.00000 | 23.53285 | 21.09735 | 0.19166 | 7.89954 |
May | 508.00000 | 23.87206 | 30.82693 | -0.5388 | 13.23379 |
June | 496.00000 | 24.14210 | 37.33410 | -0.3713 | 8.86991 |
July | 497.00000 | 24.23186 | 52.86473 | -0.2355 | 7.08522 |
August | 514.00000 | 24.14318 | 49.79721 | -0.2715 | 7.94439 |
September | 485.00000 | 24.10298 | 47.01249 | -0.2743 | 9.44967 |
October | 502.00000 | 23.74840 | 37.27811 | 0.39871 | 11.29063 |
November | 489.00000 | 23.19284 | 22.20963 | 0.13380 | 9.75213 |
December | 497.00000 | 22.74453 | 17.52022 | -0.0455 | 9.59986 |
Annual Sum or Average | 5943.00000 | 23.54830 | 30.95236 | -0.0823 | 9.30960 |
Minimum of Months | 454.00000 | 22.74453 | 16.49564 | -0.5388 | 7.08522 |
Maximum of Months | 514.00000 | 24.23186 | 52.86473 | 0.39871 | 13.23379 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.49700 | 21.72756 | -0.3641 | 9.74616 |
February | 454.00000 | 21.85234 | 18.59747 | -0.2763 | 8.89046 |
March | 514.00000 | 22.36752 | 17.09559 | -0.1221 | 7.94157 |
April | 485.00000 | 23.25961 | 21.28241 | 0.17204 | 8.50190 |
May | 508.00000 | 23.79831 | 30.81998 | -0.4586 | 13.74020 |
June | 496.00000 | 24.12406 | 37.28151 | -0.2588 | 9.10394 |
July | 497.00000 | 24.17850 | 52.89736 | -0.1524 | 7.92398 |
August | 514.00000 | 24.02413 | 50.11887 | -0.2378 | 8.92556 |
September | 485.00000 | 23.71907 | 48.12969 | -0.3781 | 11.69444 |
October | 502.00000 | 22.99607 | 39.00095 | 0.20610 | 8.49311 |
November | 489.00000 | 21.95815 | 23.68409 | -0.1956 | 8.43189 |
December | 497.00000 | 21.43580 | 18.81206 | -0.4033 | 10.50237 |
Annual Sum or Average | 5943.00000 | 22.94285 | 31.71990 | -0.2058 | 9.49587 |
Minimum of Months | 454.00000 | 21.43580 | 17.09559 | -0.4586 | 7.92398 |
Maximum of Months | 514.00000 | 24.17850 | 52.89736 | 0.20610 | 13.74020 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.41415 | 23.61253 | -0.7111 | 17.85409 |
February | 454.00000 | 20.87728 | 19.71261 | -0.5921 | 14.43416 |
March | 514.00000 | 21.53943 | 18.18983 | -0.4038 | 10.76116 |
April | 485.00000 | 22.73420 | 22.12224 | -0.0262 | 7.65384 |
May | 508.00000 | 23.63743 | 31.37073 | -0.6015 | 15.80054 |
June | 496.00000 | 24.11960 | 37.70064 | -0.3325 | 8.78731 |
July | 497.00000 | 24.18934 | 53.38036 | -0.2121 | 7.20391 |
August | 514.00000 | 23.91306 | 51.00831 | -0.3539 | 9.45111 |
September | 485.00000 | 23.46247 | 49.48564 | -0.5583 | 14.66924 |
October | 502.00000 | 22.33543 | 40.97540 | -0.0240 | 7.51532 |
November | 489.00000 | 20.88355 | 25.34636 | -0.5434 | 14.17670 |
December | 497.00000 | 20.29816 | 20.46621 | -0.7733 | 19.96725 |
Annual Sum or Average | 5943.00000 | 22.37927 | 32.87940 | -0.4268 | 12.33821 |
Minimum of Months | 454.00000 | 20.29816 | 18.18983 | -0.7733 | 7.20391 |
Maximum of Months | 514.00000 | 24.18934 | 53.38036 | -0.0240 | 19.96725 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.71803 | 23.02602 | -0.5965 | 14.89327 |
February | 454.00000 | 21.46454 | 18.94050 | -0.4046 | 11.27320 |
March | 514.00000 | 22.28252 | 17.23347 | -0.1787 | 8.98123 |
April | 485.00000 | 23.46365 | 21.08102 | 0.21247 | 8.86929 |
May | 508.00000 | 23.98713 | 30.63728 | -0.3787 | 11.87408 |
June | 496.00000 | 24.25252 | 37.27222 | -0.1794 | 8.22764 |
July | 497.00000 | 24.34649 | 52.70625 | -0.0627 | 7.80600 |
August | 514.00000 | 24.05496 | 50.44325 | -0.2050 | 8.92820 |
September | 485.00000 | 23.84064 | 48.12744 | -0.3314 | 11.23637 |
October | 502.00000 | 22.86925 | 39.62646 | 0.14463 | 8.57248 |
November | 489.00000 | 21.48383 | 24.39738 | -0.3615 | 10.99287 |
December | 497.00000 | 20.57497 | 19.96962 | -0.6633 | 16.56606 |
Annual Sum or Average | 5943.00000 | 22.78850 | 32.05510 | -0.2498 | 10.67742 |
Minimum of Months | 454.00000 | 20.57497 | 17.23347 | -0.6633 | 7.80600 |
Maximum of Months | 514.00000 | 24.34649 | 52.70625 | 0.21247 | 16.56606 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.03712 | 21.40784 | -0.2295 | 12.64887 |
February | 454.00000 | 22.38127 | 18.09872 | -0.1522 | 11.32368 |
March | 514.00000 | 22.58719 | 16.94780 | -0.0950 | 9.72393 |
April | 485.00000 | 23.19703 | 21.49542 | 0.11976 | 8.79321 |
May | 508.00000 | 23.65725 | 31.31757 | -0.5783 | 15.90764 |
June | 496.00000 | 24.04728 | 37.86745 | -0.3584 | 9.67255 |
July | 497.00000 | 24.15667 | 53.48313 | -0.2166 | 7.82202 |
August | 514.00000 | 23.99411 | 50.70851 | -0.2836 | 9.29295 |
September | 485.00000 | 23.86369 | 48.20033 | -0.3267 | 11.97728 |
October | 502.00000 | 23.34459 | 38.45186 | 0.29988 | 11.30723 |
November | 489.00000 | 22.53173 | 23.00948 | -0.0552 | 11.53216 |
December | 497.00000 | 21.96793 | 18.53319 | -0.2752 | 13.10408 |
Annual Sum or Average | 5943.00000 | 23.15282 | 31.73136 | -0.1803 | 11.09430 |
Minimum of Months | 454.00000 | 21.96793 | 16.94780 | -0.5783 | 7.82202 |
Maximum of Months | 514.00000 | 24.15667 | 53.48313 | 0.29988 | 15.90764 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.04998 | 22.44574 | -0.5088 | 13.69542 |
February | 454.00000 | 21.46312 | 18.91215 | -0.4008 | 11.68078 |
March | 514.00000 | 22.03951 | 17.35826 | -0.2185 | 9.73312 |
April | 485.00000 | 22.99227 | 21.63300 | 0.11644 | 9.32531 |
May | 508.00000 | 23.60333 | 31.32981 | -0.4928 | 16.23862 |
June | 496.00000 | 24.00841 | 37.88909 | -0.2542 | 10.28991 |
July | 497.00000 | 24.07410 | 53.63856 | -0.1443 | 8.94931 |
August | 514.00000 | 23.85985 | 51.08798 | -0.2558 | 10.48383 |
September | 485.00000 | 23.48730 | 49.29575 | -0.4271 | 14.27823 |
October | 502.00000 | 22.67554 | 39.92120 | 0.12832 | 8.92837 |
November | 489.00000 | 21.51078 | 24.21419 | -0.3325 | 11.43868 |
December | 497.00000 | 20.92015 | 19.52108 | -0.5690 | 15.19248 |
Annual Sum or Average | 5943.00000 | 22.64999 | 32.37182 | -0.2795 | 11.68508 |
Minimum of Months | 454.00000 | 20.92015 | 17.35826 | -0.5690 | 8.92837 |
Maximum of Months | 514.00000 | 24.07410 | 53.63856 | 0.12832 | 16.23862 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.172964E+11 | 144435.42 | 03-JAN-13:05 | 161.72 | 0.842771E+11 | 0.00 | 0.101573E+12 | 1.01 | 6.72 | 03-JAN-13:05 | 0.00 | 0.00 |
February | 0.761074E+11 | 185165.07 | 20-FEB-18:13 | 290.55 | 0.382355E+12 | 0.00 | 0.458462E+12 | 2.09 | 7.01 | 20-FEB-18:13 | 0.00 | 0.00 |
March | 0.126396E+12 | 204647.18 | 22-MAR-12:10 | 522.17 | 0.663835E+12 | 0.00 | 0.790231E+12 | 3.48 | 7.14 | 22-MAR-14:20 | 0.00 | 0.00 |
April | 0.195583E+12 | 230705.86 | 18-APR-15:00 | 661.29 | 0.117987E+13 | 0.00 | 0.137545E+13 | 5.00 | 7.07 | 13-APR-16:30 | 0.00 | 0.00 |
May | 0.220386E+12 | 235967.00 | 26-MAY-10:30 | 563.49 | 0.138932E+13 | 0.00 | 0.160970E+13 | 4.44 | 7.19 | 09-MAY-04:11 | 0.00 | 0.00 |
June | 0.280380E+12 | 232416.81 | 05-JUN-07:30 | 684.86 | 0.179190E+13 | 0.00 | 0.207228E+13 | 5.67 | 7.18 | 16-JUN-04:11 | 0.00 | 0.00 |
July | 0.328175E+12 | 258167.58 | 21-JUL-09:30 | 731.49 | 0.206972E+13 | 0.00 | 0.239789E+13 | 5.83 | 7.14 | 12-JUL-05:03 | 0.00 | 0.00 |
August | 0.333707E+12 | 242936.85 | 03-AUG-04:14 | 738.63 | 0.210209E+13 | 0.00 | 0.243580E+13 | 5.90 | 7.15 | 14-AUG-04:13 | 0.00 | 0.00 |
September | 0.212318E+12 | 237589.00 | 12-SEP-10:00 | 512.39 | 0.135189E+13 | 0.00 | 0.156421E+13 | 4.24 | 7.28 | 22-SEP-04:13 | 0.00 | 0.00 |
October | 0.174285E+12 | 237477.94 | 19-OCT-14:05 | 486.52 | 0.103801E+13 | 0.00 | 0.121229E+13 | 3.62 | 7.14 | 05-OCT-05:03 | 0.00 | 0.00 |
November | 0.107576E+12 | 206457.55 | 09-NOV-15:30 | 519.82 | 0.565061E+12 | 0.00 | 0.672637E+12 | 3.57 | 7.07 | 03-NOV-16:05 | 0.00 | 0.00 |
December | 0.737504E+11 | 175751.77 | 01-DEC-12:34 | 639.72 | 0.355231E+12 | 0.00 | 0.428981E+12 | 4.11 | 6.99 | 01-DEC-12:34 | 0.00 | 0.00 |
Annual Sum or Average | 0.214596E+13 | 6512.66 | 0.129736E+14 | 0.00 | 0.151195E+14 | 4.09 | 0.00 | 0.00 | ||||
Minimum of Months | 0.172964E+11 | 144435.42 | 161.72 | 0.842771E+11 | 0.00 | 0.101573E+12 | 1.01 | 6.72 | 0.00 | 0.00 | ||
Maximum of Months | 0.333707E+12 | 258167.58 | 738.63 | 0.210209E+13 | 0.00 | 0.243580E+13 | 5.90 | 7.28 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.981867E+09 | 166596.97 | 22-MAR-14:05 | 2.42 | 0.636471E+10 | 0.00 | 0.734657E+10 | 0.02 | 6.93 | 22-MAR-14:05 | 0.00 | 0.00 |
April | 0.300496E+11 | 168506.22 | 03-APR-13:05 | 61.58 | 0.197422E+12 | 0.00 | 0.227471E+12 | 0.56 | 6.96 | 03-APR-13:05 | 0.00 | 0.00 |
May | 0.288117E+11 | 170415.75 | 19-MAY-12:05 | 60.21 | 0.186801E+12 | 0.00 | 0.215613E+12 | 0.52 | 6.91 | 08-MAY-14:05 | 0.00 | 0.00 |
June | 0.823265E+11 | 203840.86 | 01-JUN-04:13 | 165.55 | 0.541442E+12 | 0.00 | 0.623769E+12 | 1.50 | 6.95 | 03-JUN-05:04 | 0.00 | 0.00 |
July | 0.116086E+12 | 258167.58 | 21-JUL-09:30 | 219.68 | 0.756134E+12 | 0.00 | 0.872220E+12 | 1.91 | 6.87 | 26-JUL-03:04 | 0.00 | 0.00 |
August | 0.103771E+12 | 242936.85 | 03-AUG-04:14 | 196.29 | 0.685198E+12 | 0.00 | 0.788969E+12 | 1.73 | 7.00 | 26-AUG-16:03 | 0.00 | 0.00 |
September | 0.501286E+11 | 178972.67 | 13-SEP-04:14 | 101.60 | 0.324846E+12 | 0.00 | 0.374974E+12 | 0.91 | 6.94 | 19-SEP-12:05 | 0.00 | 0.00 |
October | 0.182217E+11 | 175147.79 | 04-OCT-10:05 | 36.50 | 0.118854E+12 | 0.00 | 0.137076E+12 | 0.32 | 6.88 | 02-OCT-12:05 | 0.00 | 0.00 |
November | 82230472.60 | 137050.79 | 03-NOV-16:00 | 0.17 | 0.525616E+09 | 0.00 | 0.607847E+09 | 0.00 | 6.39 | 03-NOV-16:00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.430459E+12 | 844.00 | 0.281759E+13 | 0.00 | 0.324805E+13 | 0.63 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.116086E+12 | 258167.58 | 219.68 | 0.756134E+12 | 0.00 | 0.872220E+12 | 1.91 | 7.00 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 39561608.59 | 42.88 | 3542.60 | 12-JAN-15:02 | 1072159.03 | 12-JAN-15:02 | 21.17 | 21.05 | 10.79 |
February | 0.261415E+09 | 256.40 | 4126.30 | 07-FEB-13:42 | 1241811.69 | 07-FEB-13:42 | 22.34 | 21.76 | 34.85 |
March | 0.799422E+09 | 364.35 | 7099.99 | 14-MAR-15:40 | 1649555.89 | 22-MAR-12:10 | 22.29 | 21.37 | 52.98 |
April | 0.640256E+10 | 447.29 | 25366.27 | 18-APR-16:30 | 1838921.26 | 18-APR-15:00 | 22.75 | 21.04 | 71.04 |
May | 0.154365E+11 | 479.42 | 25366.27 | 08-MAY-12:05 | 1876819.25 | 26-MAY-10:30 | 23.09 | 21.21 | 59.88 |
June | 0.297648E+11 | 672.25 | 25366.27 | 02-JUN-13:30 | 1801592.92 | 21-JUN-18:20 | 23.85 | 21.27 | 78.39 |
July | 0.525843E+11 | 730.27 | 25366.27 | 01-JUL-03:06 | 1924161.22 | 21-JUL-09:40 | 24.86 | 22.20 | 80.13 |
August | 0.444073E+11 | 729.37 | 25366.27 | 01-AUG-03:03 | 1817346.49 | 26-AUG-12:20 | 24.36 | 21.60 | 81.61 |
September | 0.268230E+11 | 477.71 | 25366.27 | 01-SEP-07:00 | 1836849.25 | 12-SEP-10:00 | 23.36 | 21.49 | 57.77 |
October | 0.109933E+11 | 468.45 | 25366.27 | 02-OCT-09:30 | 1829847.45 | 19-OCT-14:05 | 22.97 | 21.58 | 53.74 |
November | 0.962254E+09 | 280.23 | 13927.15 | 03-NOV-15:20 | 1673641.89 | 09-NOV-15:30 | 22.12 | 21.31 | 51.54 |
December | 20624620.51 | 78.82 | 2622.23 | 07-DEC-15:04 | 1255107.69 | 07-DEC-15:04 | 21.38 | 20.84 | 55.10 |
Annual Sum or Average | 0.188495E+12 | 5027.43 | 22.88 | 21.39 | 57.42 | ||||
Minimum of Months | 20624620.51 | 42.88 | 2622.23 | 1072159.03 | 21.17 | 20.84 | 10.79 | ||
Maximum of Months | 0.525843E+11 | 730.27 | 25366.27 | 1924161.22 | 24.86 | 22.20 | 81.61 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.17 | 21.17 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 22.34 | 22.34 | 0.00 |
March | 33390142.95 | 1.58 | 6660.78 | 14-MAR-15:10 | 1607829.21 | 22-MAR-14:05 | 22.29 | 22.28 | 0.18 |
April | 0.210812E+10 | 54.08 | 25366.27 | 21-APR-15:10 | 1709952.23 | 19-APR-16:00 | 22.75 | 22.42 | 6.20 |
May | 0.317169E+10 | 46.77 | 25366.27 | 18-MAY-12:05 | 1691333.69 | 12-MAY-15:30 | 23.09 | 22.83 | 5.19 |
June | 0.111012E+11 | 144.10 | 25366.27 | 02-JUN-13:30 | 1713833.20 | 01-JUN-14:30 | 23.85 | 23.03 | 16.42 |
July | 0.212172E+11 | 232.48 | 25366.27 | 01-JUL-09:00 | 1924161.22 | 21-JUL-09:40 | 24.86 | 23.76 | 24.78 |
August | 0.165394E+11 | 184.37 | 25366.27 | 01-AUG-03:04 | 1669895.98 | 23-AUG-11:00 | 24.36 | 23.45 | 20.23 |
September | 0.777642E+10 | 90.30 | 25366.27 | 01-SEP-07:50 | 1644448.29 | 27-SEP-13:30 | 23.36 | 22.91 | 10.33 |
October | 0.258069E+10 | 30.83 | 25366.27 | 02-OCT-10:30 | 1680171.13 | 19-OCT-13:00 | 22.97 | 22.81 | 3.42 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 22.12 | 22.12 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 21.38 | 21.38 | 0.00 |
Annual Sum or Average | 0.645282E+11 | 784.51 | 22.88 | 22.54 | 7.28 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 21.17 | 0.00 | ||
Maximum of Months | 0.212172E+11 | 232.48 | 25366.27 | 1924161.22 | 24.86 | 23.76 | 24.78 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.910663E+11 | 0.00 | 326.95 | 1873500.58 | 23-JAN-05:11 | 0.00 | 27.94 | 45.83 | 0.21 | 0.00 | 0.01 | 0.78 | 23-JAN-05:11 |
February | 0.579429E+11 | 0.00 | 258.58 | 2061744.01 | 03-FEB-05:01 | 0.00 | 24.97 | 41.02 | 0.14 | 0.00 | 0.01 | 0.86 | 03-FEB-05:01 |
March | 0.362033E+11 | 0.00 | 201.41 | 1941985.13 | 02-MAR-05:01 | 0.00 | 24.67 | 35.95 | 0.08 | 0.00 | 0.01 | 0.81 | 02-MAR-05:01 |
April | 0.518572E+10 | 0.00 | 72.42 | 1414546.54 | 11-APR-05:01 | 0.00 | 23.11 | 27.38 | 0.01 | 0.00 | 0.00 | 0.59 | 11-APR-05:01 |
May | 0.278574E+09 | 0.00 | 17.92 | 48536.20 | 02-MAY-05:08 | 0.00 | 21.30 | 22.36 | 0.00 | 0.00 | 0.00 | 0.02 | 02-MAY-05:08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 21.17 | 21.17 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 21.17 | 21.17 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 4208115.92 | 0.00 | 1.53 | 2984.37 | 17-AUG-05:10 | 0.00 | 21.14 | 21.23 | 0.00 | 0.00 | 0.00 | 0.00 | 17-AUG-05:10 |
September | 0.405913E+09 | 0.00 | 18.65 | 37205.63 | 25-SEP-05:05 | 0.00 | 21.14 | 22.29 | 0.00 | 0.00 | 0.00 | 0.02 | 25-SEP-05:05 |
October | 0.581236E+10 | 0.00 | 96.39 | 312738.48 | 25-OCT-05:01 | 0.00 | 22.14 | 27.73 | 0.01 | 0.00 | 0.00 | 0.13 | 25-OCT-05:01 |
November | 0.424018E+11 | 0.00 | 242.65 | 1858677.83 | 17-NOV-06:01 | 0.00 | 24.58 | 38.51 | 0.10 | 0.00 | 0.01 | 0.77 | 17-NOV-06:01 |
December | 0.104974E+12 | 0.00 | 381.14 | 1900851.03 | 05-DEC-05:01 | 0.00 | 26.51 | 48.10 | 0.24 | 0.00 | 0.02 | 0.79 | 05-DEC-05:01 |
Annual Sum or Average | 0.344275E+12 | 0.00 | 1617.63 | 0.00 | 23.32 | 31.02 | 0.07 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.14 | 21.17 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.104974E+12 | 0.00 | 381.14 | 2061744.01 | 0.00 | 27.94 | 48.10 | 0.24 | 0.00 | 0.02 | 0.86 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.403224E+10 | 0.00 | 62.18 | 0.403224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59766.50 | 03-JAN-15:00 | 59766.50 | 03-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.128698E+11 | 0.00 | 129.24 | 0.128698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87770.90 | 21-FEB-16:00 | 87770.90 | 21-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.313112E+11 | 0.00 | 238.37 | 0.313112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110578.98 | 21-MAR-16:00 | 110578.98 | 21-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.848202E+11 | 0.00 | 396.04 | 0.848202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 146957.86 | 21-APR-14:40 | 146957.86 | 21-APR-14:40 | 0.00 | 0.00 | 0.00 |
May | 0.123886E+12 | 0.00 | 468.69 | 0.123643E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 199704.97 | 30-MAY-05:02 | 199704.97 | 30-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.165922E+12 | 0.00 | 522.19 | 0.165271E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 193561.83 | 08-JUN-05:02 | 193561.83 | 08-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.196232E+12 | 0.00 | 568.51 | 0.170801E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 280273.44 | 21-JUL-04:11 | 194174.09 | 25-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.182827E+12 | 0.00 | 590.19 | 0.172169E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 256458.69 | 03-AUG-04:11 | 176425.17 | 05-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.131844E+12 | 0.00 | 438.46 | 0.123833E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 256603.97 | 14-SEP-04:11 | 151453.95 | 13-SEP-04:11 | 0.00 | 0.00 | 0.00 |
October | 0.754054E+11 | 0.00 | 361.94 | 0.731941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 185840.62 | 02-OCT-03:01 | 185840.62 | 02-OCT-03:01 | 0.00 | 0.00 | 0.00 |
November | 0.221262E+11 | 0.00 | 179.65 | 0.221262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113727.32 | 03-NOV-16:00 | 113727.32 | 03-NOV-16:00 | 0.00 | 0.00 | 0.00 |
December | 0.186669E+10 | 0.00 | 51.76 | 0.186669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34724.69 | 20-DEC-15:00 | 34724.69 | 20-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103314E+13 | 0.00 | 4007.21 | 0.985939E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.186669E+10 | 0.00 | 51.76 | 0.186669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34724.69 | 34724.69 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.196232E+12 | 0.00 | 590.19 | 0.172169E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 280273.44 | 199704.97 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.544641E+11 | 0.00 | 120.16 | 0.544641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 747832.77 | 12-JAN-15:02 | 747832.77 | 12-JAN-15:02 | 0.00 | 0.00 | 0.00 |
February | 0.130404E+12 | 0.00 | 163.45 | 0.130404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 749130.15 | 23-FEB-13:03 | 749130.15 | 23-FEB-13:03 | 0.00 | 0.00 | 0.00 |
March | 0.269586E+12 | 0.00 | 250.50 | 0.269586E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 941940.50 | 21-MAR-16:00 | 941940.50 | 21-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.654115E+12 | 0.00 | 361.87 | 0.654115E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1321986.21 | 21-APR-14:05 | 1321986.21 | 21-APR-14:05 | 0.00 | 0.00 | 0.00 |
May | 0.110295E+13 | 0.00 | 461.06 | 0.110085E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1668203.11 | 30-MAY-05:02 | 1668203.11 | 30-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.143538E+13 | 0.00 | 475.65 | 0.143009E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1879633.03 | 17-JUN-05:02 | 1879633.03 | 17-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.156943E+13 | 0.00 | 479.57 | 0.136993E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3078343.01 | 22-JUL-05:03 | 1724206.49 | 07-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.140775E+13 | 0.00 | 488.35 | 0.132942E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2990593.99 | 03-AUG-05:03 | 1895485.64 | 24-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.115109E+13 | 0.00 | 426.19 | 0.108012E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2375172.07 | 22-SEP-05:03 | 1400344.39 | 20-SEP-15:30 | 0.00 | 0.00 | 0.00 |
October | 0.644753E+12 | 0.00 | 356.56 | 0.624715E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1478655.95 | 04-OCT-05:02 | 1339448.32 | 05-OCT-16:00 | 0.00 | 0.00 | 0.00 |
November | 0.207418E+12 | 0.00 | 197.87 | 0.207418E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 969696.73 | 03-NOV-16:00 | 969696.73 | 03-NOV-16:00 | 0.00 | 0.00 | 0.00 |
December | 0.320775E+11 | 0.00 | 104.42 | 0.320775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 629399.36 | 15-DEC-15:02 | 629399.36 | 15-DEC-15:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.865941E+13 | 0.00 | 3885.66 | 0.828319E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.320775E+11 | 0.00 | 104.42 | 0.320775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 629399.36 | 629399.36 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.156943E+13 | 0.00 | 488.35 | 0.143009E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3078343.01 | 1895485.64 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.267709E+10 | 0.00 | 56.78 | 0.267709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41700.13 | 12-JAN-15:00 | 41700.13 | 12-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.104119E+11 | 0.00 | 120.02 | 0.104119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79489.25 | 20-FEB-15:01 | 79489.25 | 20-FEB-15:01 | 0.00 | 0.00 | 0.00 |
March | 0.264970E+11 | 0.00 | 222.91 | 0.264970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116581.68 | 14-MAR-15:30 | 116581.68 | 14-MAR-15:30 | 0.00 | 0.00 | 0.00 |
April | 0.785961E+11 | 0.00 | 351.65 | 0.785961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170457.50 | 21-APR-14:30 | 170457.50 | 21-APR-14:30 | 0.00 | 0.00 | 0.00 |
May | 0.136459E+12 | 0.00 | 451.42 | 0.136274E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 194298.73 | 29-MAY-16:41 | 194298.73 | 29-MAY-16:41 | 0.00 | 0.00 | 0.00 |
June | 0.180645E+12 | 0.00 | 473.34 | 0.180184E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 215764.04 | 18-JUN-14:21 | 215764.04 | 18-JUN-14:21 | 0.00 | 0.00 | 0.00 |
July | 0.193040E+12 | 0.00 | 480.64 | 0.172783E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 334515.99 | 21-JUL-05:03 | 205841.09 | 02-JUL-15:41 | 0.00 | 0.00 | 0.00 |
August | 0.170657E+12 | 0.00 | 486.23 | 0.163094E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 309740.16 | 03-AUG-05:03 | 204033.83 | 13-AUG-16:01 | 0.00 | 0.00 | 0.00 |
September | 0.136465E+12 | 0.00 | 418.45 | 0.129983E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 260773.88 | 22-SEP-04:11 | 183269.14 | 20-SEP-14:40 | 0.00 | 0.00 | 0.00 |
October | 0.703328E+11 | 0.00 | 339.07 | 0.688050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 186313.76 | 03-OCT-13:30 | 171588.62 | 03-OCT-14:20 | 0.00 | 0.00 | 0.00 |
November | 0.164537E+11 | 0.00 | 168.78 | 0.164537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110718.55 | 03-NOV-16:00 | 110718.55 | 03-NOV-16:00 | 0.00 | 0.00 | 0.00 |
December | 0.107523E+10 | 0.00 | 42.55 | 0.107523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21054.31 | 23-DEC-15:00 | 21054.31 | 23-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102331E+13 | 0.00 | 3611.83 | 0.986833E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.107523E+10 | 0.00 | 42.55 | 0.107523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21054.31 | 21054.31 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.193040E+12 | 0.00 | 486.23 | 0.180184E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 334515.99 | 215764.04 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.169720E+11 | 0.00 | 157.90 | 0.169668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90654.05 | 07-JAN-06:02 | 90654.05 | 07-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.158569E+11 | 0.00 | 154.97 | 0.155684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85840.12 | 13-FEB-18:11 | 83730.73 | 10-FEB-15:02 | 0.00 | 0.00 | 0.00 |
March | 0.254138E+11 | 0.00 | 246.48 | 0.253881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 141304.59 | 03-MAR-05:52 | 141304.59 | 03-MAR-05:52 | 0.00 | 0.00 | 0.00 |
April | 0.434536E+11 | 0.00 | 335.19 | 0.434522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95321.70 | 20-APR-05:03 | 95321.70 | 20-APR-05:03 | 0.00 | 0.00 | 0.00 |
May | 0.673026E+11 | 0.00 | 406.02 | 0.657574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149964.60 | 31-MAY-05:02 | 149964.60 | 31-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.829149E+11 | 0.00 | 415.97 | 0.799914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 156751.35 | 07-JUN-05:02 | 156751.35 | 07-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.105106E+12 | 0.00 | 420.41 | 0.803881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 232908.25 | 21-JUL-04:53 | 146225.74 | 01-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.102266E+12 | 0.00 | 460.42 | 0.853109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 201864.66 | 03-AUG-05:03 | 156865.47 | 24-AUG-03:01 | 0.00 | 0.00 | 0.00 |
September | 0.845023E+11 | 0.00 | 431.87 | 0.716629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 169786.88 | 14-SEP-04:11 | 109590.67 | 13-SEP-04:53 | 0.00 | 0.00 | 0.00 |
October | 0.545218E+11 | 0.00 | 378.57 | 0.494492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 172598.87 | 15-OCT-22:13 | 159723.18 | 02-OCT-04:23 | 0.00 | 0.00 | 0.00 |
November | 0.238444E+11 | 0.00 | 255.84 | 0.238174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 142089.26 | 12-NOV-18:22 | 142089.26 | 12-NOV-18:22 | 0.00 | 0.00 | 0.00 |
December | 0.128791E+11 | 0.00 | 183.37 | 0.128791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140542.13 | 05-DEC-04:43 | 140542.13 | 05-DEC-04:43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.635034E+12 | 0.00 | 3847.02 | 0.570632E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.128791E+11 | 0.00 | 154.97 | 0.128791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85840.12 | 83730.73 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.105106E+12 | 0.00 | 460.42 | 0.853109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 232908.25 | 159723.18 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 5273208.60 | 0.00 | 251.99 | 5273208.60 | 0.00 | 0.00 | 0.00 | 0.00 | 134.58 | 10-JAN-17:42 | 134.58 | 10-JAN-17:42 | 0.00 | 0.00 | 0.00 |
February | 0.201627E+12 | 0.00 | 386.40 | 0.201158E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 435610.10 | 23-FEB-15:03 | 435610.10 | 23-FEB-15:03 | 0.00 | 0.00 | 0.00 |
March | 0.299642E+12 | 0.00 | 543.93 | 0.299573E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 391604.65 | 18-MAR-19:32 | 391604.65 | 18-MAR-19:32 | 0.00 | 0.00 | 0.00 |
April | 0.485843E+12 | 0.00 | 719.44 | 0.485843E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 398384.60 | 21-APR-15:00 | 398384.60 | 21-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.147470E+12 | 0.00 | 594.60 | 0.147470E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 187560.29 | 31-MAY-24:00 | 187560.29 | 31-MAY-24:00 | 0.00 | 0.00 | 0.00 |
June | 0.443702E+12 | 0.00 | 701.58 | 0.438291E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 550350.56 | 29-JUN-09:15 | 381139.49 | 01-JUN-06:24 | 0.00 | 0.00 | 0.00 |
July | 0.713354E+12 | 0.00 | 744.00 | 0.674321E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 527390.82 | 21-JUL-09:50 | 387800.99 | 31-JUL-23:52 | 0.00 | 0.00 | 0.00 |
August | 0.866350E+12 | 0.00 | 744.00 | 0.853612E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 510079.79 | 02-AUG-08:00 | 402766.33 | 07-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.133421E+12 | 0.00 | 537.30 | 0.133421E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 314663.65 | 30-SEP-23:51 | 314663.65 | 30-SEP-23:51 | 0.00 | 0.00 | 0.00 |
October | 0.293563E+12 | 0.00 | 534.05 | 0.273882E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 605515.29 | 03-OCT-21:22 | 449036.86 | 10-OCT-14:51 | 0.00 | 0.00 | 0.00 |
November | 0.274918E+12 | 0.00 | 566.21 | 0.274911E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 411870.77 | 13-NOV-15:12 | 411870.77 | 13-NOV-15:12 | 0.00 | 0.00 | 0.00 |
December | 0.282735E+12 | 0.00 | 743.98 | 0.282735E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 367516.01 | 07-DEC-14:47 | 367516.01 | 07-DEC-14:47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.414263E+13 | 0.00 | 7067.48 | 0.406522E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5273208.60 | 0.00 | 251.99 | 5273208.60 | 0.00 | 0.00 | 0.00 | 0.00 | 134.58 | 134.58 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.866350E+12 | 0.00 | 744.00 | 0.853612E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 605515.29 | 449036.86 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.695588E+10 | 0.210299E+10 | 744.00 | 0.695588E+10 | -0.0 | 0.00 | 0.57 | 30-JAN-16:53 | 0.30 | 28-JAN-07:40 | 3560.09 | 30-JAN-16:57 | 3560.09 | 30-JAN-16:57 | 0.00 | 24-JAN-12:57 | 1039.75 | 02-JAN-17:00 | 0.00 | 01-JAN-00:05 |
February | 0.108346E+11 | 0.303461E+10 | 672.00 | 0.108322E+11 | 2341472.31 | 0.00 | 0.82 | 21-FEB-17:00 | 0.58 | 03-FEB-07:02 | 5506.73 | 21-FEB-17:00 | 5506.73 | 21-FEB-17:00 | 132.95 | 13-FEB-15:00 | 1512.05 | 21-FEB-17:00 | 0.00 | 01-FEB-00:01 |
March | 0.175310E+11 | 0.456045E+10 | 744.00 | 0.175310E+11 | -0.0 | 0.00 | 1.00 | 14-MAR-15:00 | 0.82 | 01-MAR-07:01 | 8407.22 | 31-MAR-23:52 | 8407.22 | 31-MAR-23:52 | 0.00 | 23-MAR-15:59 | 2175.37 | 31-MAR-23:52 | 0.00 | 01-MAR-00:01 |
April | 0.226041E+11 | 0.608159E+10 | 720.00 | 0.226024E+11 | 1748717.00 | 0.00 | 1.00 | 01-APR-00:05 | 0.52 | 30-APR-23:53 | 9564.91 | 30-APR-18:04 | 9564.91 | 30-APR-18:04 | 70.93 | 18-APR-16:00 | 3085.78 | 21-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.855433E+10 | 0.272563E+10 | 744.00 | 0.853294E+10 | 21387437.00 | 0.00 | 0.74 | 31-MAY-24:00 | 0.40 | 06-MAY-06:25 | 4929.04 | 31-MAY-24:00 | 4929.04 | 31-MAY-24:00 | 185.76 | 24-MAY-13:10 | 1467.89 | 31-MAY-23:20 | 0.00 | 01-MAY-00:03 |
June | 0.133781E+11 | 0.419399E+10 | 720.00 | 0.133309E+11 | 47214319.96 | 0.00 | 0.96 | 30-JUN-23:05 | 0.69 | 29-JUN-06:01 | 6767.77 | 30-JUN-23:20 | 6767.77 | 30-JUN-23:20 | 241.19 | 28-JUN-11:00 | 2197.95 | 02-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.190004E+11 | 0.549251E+10 | 744.00 | 0.187694E+11 | 0.230987E+09 | 0.00 | 1.00 | 01-JUL-12:00 | 0.93 | 05-JUL-06:02 | 8739.93 | 31-JUL-23:02 | 8639.47 | 31-JUL-23:40 | 525.89 | 20-JUL-15:00 | 2723.11 | 03-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 0.239745E+11 | 0.690364E+10 | 744.00 | 0.237814E+11 | 0.193130E+09 | 0.00 | 1.00 | 01-AUG-00:02 | 0.52 | 31-AUG-23:57 | 9745.39 | 08-AUG-16:00 | 9613.00 | 06-AUG-18:12 | 390.99 | 02-AUG-08:50 | 3450.95 | 07-AUG-16:00 | 0.00 | 01-AUG-00:02 |
September | 0.842988E+10 | 0.265297E+10 | 720.00 | 0.831096E+10 | 0.118925E+09 | 0.00 | 0.73 | 30-SEP-23:51 | 0.39 | 30-SEP-06:33 | 4838.59 | 30-SEP-23:51 | 4838.59 | 30-SEP-23:51 | 291.67 | 14-SEP-10:20 | 1391.83 | 01-SEP-16:00 | 0.00 | 01-SEP-00:05 |
October | 0.131607E+11 | 0.372943E+10 | 744.00 | 0.130911E+11 | 69528144.60 | 0.00 | 0.94 | 31-OCT-23:52 | 0.63 | 25-OCT-06:21 | 6540.49 | 31-OCT-23:52 | 6540.49 | 31-OCT-23:52 | 290.09 | 04-OCT-10:00 | 1861.10 | 03-OCT-14:10 | 0.00 | 01-OCT-00:01 |
November | 0.169243E+11 | 0.441454E+10 | 720.00 | 0.169162E+11 | 8157508.87 | 0.00 | 1.00 | 03-NOV-15:50 | 0.83 | 28-NOV-07:02 | 7632.11 | 09-NOV-16:50 | 7632.11 | 09-NOV-16:50 | 117.08 | 01-NOV-11:00 | 2014.08 | 09-NOV-16:40 | 0.00 | 01-NOV-00:01 |
December | 0.221794E+11 | 0.572840E+10 | 744.00 | 0.221794E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-00:05 | 1.00 | 01-DEC-00:05 | 9183.29 | 15-DEC-16:35 | 9183.29 | 15-DEC-16:35 | 0.00 | 14-DEC-16:59 | 2400.39 | 15-DEC-16:35 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.183527E+12 | 0.516207E+11 | 8760.00 | 0.182834E+12 | 0.693419E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.695588E+10 | 0.210299E+10 | 672.00 | 0.695588E+10 | -0.0 | 0.00 | 0.57 | 0.30 | 3560.09 | 3560.09 | 0.00 | 1039.75 | 0.00 | |||||||
Maximum of Months | 0.239745E+11 | 0.690364E+10 | 744.00 | 0.237814E+11 | 0.230987E+09 | 0.00 | 1.00 | 1.00 | 9745.39 | 9613.00 | 525.89 | 3450.95 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.528745E+11 | 0.139723E+11 | 744.00 | 0.528745E+11 | -0.0 | 0.00 | 0.55 | 30-JAN-16:55 | 0.18 | 02-JAN-07:03 | 32432.15 | 30-JAN-16:57 | 32432.15 | 30-JAN-16:57 | 0.00 | 20-JAN-16:34 | 8120.72 | 30-JAN-17:00 | 0.00 | 01-JAN-00:05 |
February | 0.964481E+11 | 0.234080E+11 | 672.00 | 0.964246E+11 | 23441551.80 | 0.00 | 0.81 | 21-FEB-17:00 | 0.51 | 02-FEB-07:02 | 52089.85 | 21-FEB-17:00 | 52089.85 | 21-FEB-17:00 | 1316.20 | 13-FEB-15:00 | 12278.00 | 21-FEB-17:00 | 0.00 | 01-FEB-00:01 |
March | 0.161697E+12 | 0.363158E+11 | 744.00 | 0.161697E+12 | 0.00 | 0.00 | 1.00 | 13-MAR-17:40 | 0.78 | 02-MAR-07:02 | 78669.80 | 31-MAR-23:33 | 78669.80 | 31-MAR-23:33 | 0.00 | 30-MAR-18:20 | 17414.75 | 31-MAR-23:33 | 0.00 | 01-MAR-00:01 |
April | 0.211976E+12 | 0.488198E+11 | 720.00 | 0.211959E+12 | 17461308.46 | 0.00 | 1.00 | 01-APR-00:05 | 0.49 | 30-APR-23:55 | 90190.26 | 30-APR-17:57 | 90190.26 | 30-APR-17:57 | 723.67 | 18-APR-16:00 | 25111.40 | 21-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.784416E+11 | 0.215432E+11 | 744.00 | 0.782281E+11 | 0.213471E+09 | 0.00 | 0.75 | 31-MAY-24:00 | 0.36 | 06-MAY-06:25 | 47493.63 | 31-MAY-24:00 | 47493.63 | 31-MAY-24:00 | 1854.51 | 24-MAY-13:10 | 12138.08 | 31-MAY-23:10 | 0.00 | 01-MAY-00:03 |
June | 0.126852E+12 | 0.341268E+11 | 720.00 | 0.126380E+12 | 0.472428E+09 | 0.00 | 0.97 | 30-JUN-24:00 | 0.68 | 29-JUN-06:01 | 65789.22 | 30-JUN-24:00 | 65789.22 | 30-JUN-24:00 | 2409.16 | 28-JUN-11:00 | 17982.04 | 02-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.180742E+12 | 0.447879E+11 | 744.00 | 0.178438E+12 | 0.230331E+10 | 0.00 | 1.00 | 01-JUL-11:50 | 0.91 | 05-JUL-06:02 | 84567.16 | 31-JUL-23:02 | 83736.12 | 31-JUL-23:54 | 5233.11 | 20-JUL-15:00 | 22219.19 | 03-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 0.228001E+12 | 0.562612E+11 | 744.00 | 0.226076E+12 | 0.192523E+10 | 0.00 | 1.00 | 01-AUG-00:02 | 0.49 | 31-AUG-23:57 | 92883.02 | 08-AUG-16:00 | 91381.99 | 07-AUG-16:00 | 3889.53 | 02-AUG-09:00 | 28129.90 | 07-AUG-16:00 | 0.00 | 01-AUG-00:02 |
September | 0.766399E+11 | 0.208070E+11 | 720.00 | 0.754618E+11 | 0.117810E+10 | 0.00 | 0.71 | 30-SEP-23:21 | 0.35 | 30-SEP-06:42 | 44687.98 | 30-SEP-23:23 | 44687.98 | 30-SEP-23:23 | 2910.01 | 14-SEP-10:20 | 11201.19 | 19-SEP-16:00 | 0.00 | 01-SEP-00:05 |
October | 0.120588E+12 | 0.294962E+11 | 744.00 | 0.119896E+12 | 0.692480E+09 | 0.00 | 0.91 | 31-OCT-23:42 | 0.59 | 07-OCT-06:51 | 60370.55 | 31-OCT-23:42 | 60370.55 | 31-OCT-23:42 | 2894.28 | 04-OCT-10:00 | 15123.91 | 03-OCT-14:10 | 0.00 | 01-OCT-00:01 |
November | 0.153318E+12 | 0.346596E+11 | 720.00 | 0.153237E+12 | 81825711.41 | 0.00 | 1.00 | 03-NOV-16:00 | 0.75 | 27-NOV-07:01 | 72441.94 | 09-NOV-16:50 | 72441.94 | 09-NOV-16:50 | 1166.86 | 01-NOV-11:00 | 16368.74 | 09-NOV-16:50 | 0.00 | 01-NOV-00:01 |
December | 0.199538E+12 | 0.439002E+11 | 744.00 | 0.199538E+12 | -0.0 | 0.00 | 1.00 | 01-DEC-00:05 | 0.96 | 27-DEC-07:03 | 87078.87 | 15-DEC-16:45 | 87078.87 | 15-DEC-16:45 | 0.00 | 15-DEC-08:50 | 19499.46 | 15-DEC-16:45 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.168712E+13 | 0.408098E+12 | 8760.00 | 0.168021E+13 | 0.690776E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.528745E+11 | 0.139723E+11 | 672.00 | 0.528745E+11 | -0.0 | 0.00 | 0.55 | 0.18 | 32432.15 | 32432.15 | 0.00 | 8120.72 | 0.00 | |||||||
Maximum of Months | 0.228001E+12 | 0.562612E+11 | 744.00 | 0.226076E+12 | 0.230331E+10 | 0.00 | 1.00 | 0.96 | 92883.02 | 91381.99 | 5233.11 | 28129.90 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.349352E+10 | 0.109310E+10 | 709.72 | 0.349352E+10 | -0.0 | 0.00 | 0.52 | 30-JAN-17:00 | 0.00 | 01-JAN-07:00 | 3269.59 | 12-JAN-16:40 | 3269.59 | 12-JAN-16:40 | 0.00 | 20-JAN-14:03 | 967.03 | 12-JAN-16:40 | 0.00 | 01-JAN-00:05 |
February | 0.835033E+10 | 0.242327E+10 | 672.00 | 0.834805E+10 | 2283426.00 | 0.00 | 0.80 | 21-FEB-17:00 | 0.31 | 05-FEB-07:50 | 5317.25 | 21-FEB-17:00 | 5317.25 | 21-FEB-17:00 | 129.36 | 13-FEB-15:02 | 1469.62 | 21-FEB-17:00 | 0.00 | 01-FEB-00:01 |
March | 0.152063E+11 | 0.407118E+10 | 744.00 | 0.152063E+11 | -0.0 | 0.00 | 1.00 | 14-MAR-17:00 | 0.62 | 02-MAR-07:02 | 7437.32 | 31-MAR-23:10 | 7437.32 | 31-MAR-23:10 | 0.00 | 27-MAR-15:19 | 1936.64 | 21-MAR-16:00 | 0.00 | 01-MAR-00:01 |
April | 0.209444E+11 | 0.560372E+10 | 720.00 | 0.209427E+11 | 1642016.05 | 0.00 | 1.00 | 01-APR-00:05 | 0.47 | 30-APR-24:00 | 9432.29 | 30-APR-17:53 | 9432.29 | 30-APR-17:53 | 72.76 | 18-APR-16:00 | 3013.35 | 21-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.790913E+10 | 0.255051E+10 | 744.00 | 0.788785E+10 | 21280491.48 | 0.00 | 0.73 | 31-MAY-24:00 | 0.26 | 02-MAY-06:02 | 4827.41 | 31-MAY-24:00 | 4827.41 | 31-MAY-24:00 | 189.18 | 24-MAY-13:10 | 1448.11 | 31-MAY-23:10 | 0.00 | 01-MAY-00:03 |
June | 0.129857E+11 | 0.409818E+10 | 720.00 | 0.129386E+11 | 47154867.07 | 0.00 | 0.94 | 30-JUN-23:50 | 0.63 | 29-JUN-06:01 | 6617.18 | 30-JUN-24:00 | 6617.18 | 30-JUN-24:00 | 242.47 | 28-JUN-11:00 | 2201.99 | 14-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.184202E+11 | 0.535876E+10 | 744.00 | 0.181902E+11 | 0.230024E+09 | 0.00 | 1.00 | 01-JUL-12:50 | 0.86 | 05-JUL-06:02 | 8500.91 | 31-JUL-23:02 | 8432.51 | 31-JUL-23:54 | 522.27 | 20-JUL-15:00 | 2701.67 | 02-JUL-16:01 | 0.00 | 01-JUL-00:10 |
August | 0.230416E+11 | 0.661790E+10 | 744.00 | 0.228506E+11 | 0.191034E+09 | 0.00 | 1.00 | 01-AUG-00:02 | 0.46 | 31-AUG-23:57 | 9650.54 | 06-AUG-18:06 | 9650.54 | 06-AUG-18:06 | 392.04 | 02-AUG-09:00 | 3394.77 | 07-AUG-16:00 | 0.00 | 01-AUG-00:02 |
September | 0.765781E+10 | 0.244261E+10 | 720.00 | 0.753964E+10 | 0.118163E+09 | 0.00 | 0.64 | 30-SEP-23:02 | 0.25 | 30-SEP-06:46 | 4175.23 | 30-SEP-23:03 | 4175.23 | 30-SEP-23:03 | 296.42 | 14-SEP-10:20 | 1396.69 | 19-SEP-16:00 | 0.00 | 01-SEP-00:05 |
October | 0.115328E+11 | 0.334018E+10 | 744.00 | 0.114637E+11 | 69181844.52 | 0.00 | 0.85 | 04-OCT-16:00 | 0.46 | 25-OCT-06:01 | 5834.83 | 05-OCT-17:00 | 5714.29 | 05-OCT-17:00 | 291.53 | 04-OCT-10:00 | 1846.95 | 03-OCT-14:10 | 0.00 | 01-OCT-00:01 |
November | 0.138832E+11 | 0.376423E+10 | 720.00 | 0.138751E+11 | 8109816.75 | 0.00 | 1.00 | 09-NOV-16:10 | 0.50 | 27-NOV-05:22 | 7390.43 | 09-NOV-16:50 | 7390.43 | 09-NOV-16:50 | 116.08 | 01-NOV-11:00 | 1944.24 | 09-NOV-16:40 | 0.00 | 01-NOV-00:01 |
December | 0.179345E+11 | 0.465513E+10 | 744.00 | 0.179345E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-09:32 | 0.74 | 04-DEC-04:14 | 8709.65 | 15-DEC-16:45 | 8709.65 | 15-DEC-16:45 | 0.00 | 05-DEC-11:26 | 2265.18 | 15-DEC-16:45 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.161360E+12 | 0.460188E+11 | 8725.72 | 0.160671E+12 | 0.688873E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.349352E+10 | 0.109310E+10 | 672.00 | 0.349352E+10 | -0.0 | 0.00 | 0.52 | 0.00 | 3269.59 | 3269.59 | 0.00 | 967.03 | 0.00 | |||||||
Maximum of Months | 0.230416E+11 | 0.661790E+10 | 744.00 | 0.228506E+11 | 0.230024E+09 | 0.00 | 1.00 | 0.86 | 9650.54 | 9650.54 | 522.27 | 3394.77 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.81 | 0.00 | 102.81 | 4.73 | 742.61 | 0.00 | 0.00 | 0.00 |
February | 125.54 | 0.00 | 125.54 | 32.90 | 649.50 | 0.00 | 0.00 | 0.00 |
March | 164.30 | 0.00 | 164.30 | 81.88 | 542.74 | 0.00 | 0.00 | 0.00 |
April | 189.70 | 1.49 | 188.21 | 195.32 | 314.42 | 0.00 | 0.00 | 0.00 |
May | 224.99 | 16.27 | 208.72 | 357.59 | 175.52 | 0.00 | 0.00 | 0.00 |
June | 239.24 | 29.45 | 209.79 | 523.33 | 89.56 | 0.00 | 0.00 | 0.00 |
July | 221.10 | 21.52 | 199.58 | 482.50 | 68.86 | 0.00 | 0.00 | 0.00 |
August | 186.44 | 3.81 | 182.63 | 368.54 | 98.72 | 0.00 | 0.00 | 0.00 |
September | 162.68 | 0.06 | 162.62 | 274.19 | 207.74 | 0.00 | 0.00 | 0.00 |
October | 135.07 | 0.00 | 135.07 | 124.37 | 349.77 | 0.00 | 0.00 | 0.00 |
November | 109.04 | 0.00 | 109.04 | 17.44 | 631.85 | 0.00 | 0.00 | 0.00 |
December | 102.02 | 0.00 | 102.02 | 3.42 | 836.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.76 | 6.08 | 157.68 | 206.42 | 391.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.02 | 0.00 | 102.02 | 3.42 | 68.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 239.24 | 29.45 | 209.79 | 523.33 | 836.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.81 | 0.00 | 102.81 | 4.73 | 742.61 | 0.00 | 0.00 | 0.00 |
February | 125.54 | 0.00 | 125.54 | 32.90 | 649.50 | 0.00 | 0.00 | 0.00 |
March | 164.30 | 0.00 | 164.30 | 81.88 | 542.74 | 0.00 | 0.00 | 0.00 |
April | 189.70 | 1.49 | 188.21 | 195.32 | 314.42 | 0.00 | 0.00 | 0.00 |
May | 224.99 | 16.27 | 208.72 | 357.59 | 175.52 | 0.00 | 0.00 | 0.00 |
June | 239.24 | 29.45 | 209.79 | 523.33 | 89.56 | 0.00 | 0.00 | 0.00 |
July | 221.10 | 21.52 | 199.58 | 482.50 | 68.86 | 0.00 | 0.00 | 0.00 |
August | 186.44 | 3.81 | 182.63 | 368.54 | 98.71 | 0.00 | 0.00 | 0.00 |
September | 162.68 | 0.06 | 162.62 | 274.19 | 207.74 | 0.00 | 0.00 | 0.00 |
October | 135.07 | 0.00 | 135.07 | 124.37 | 349.77 | 0.00 | 0.00 | 0.00 |
November | 109.04 | 0.00 | 109.04 | 17.44 | 631.85 | 0.00 | 0.00 | 0.00 |
December | 102.02 | 0.00 | 102.02 | 3.42 | 836.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.76 | 6.08 | 157.68 | 206.42 | 391.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.02 | 0.00 | 102.02 | 3.42 | 68.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 239.24 | 29.45 | 209.79 | 523.33 | 836.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.81 | 0.00 | 102.81 | 4.73 | 742.61 | 0.00 | 0.00 | 0.00 |
February | 125.54 | 0.00 | 125.54 | 32.90 | 649.50 | 0.00 | 0.00 | 0.00 |
March | 164.30 | 0.00 | 164.30 | 81.88 | 542.74 | 0.00 | 0.00 | 0.00 |
April | 189.70 | 1.49 | 188.21 | 195.32 | 314.42 | 0.00 | 0.00 | 0.00 |
May | 224.99 | 16.27 | 208.72 | 357.59 | 175.52 | 0.00 | 0.00 | 0.00 |
June | 239.24 | 29.45 | 209.79 | 523.33 | 89.56 | 0.00 | 0.00 | 0.00 |
July | 221.10 | 21.52 | 199.58 | 482.50 | 68.86 | 0.00 | 0.00 | 0.00 |
August | 186.44 | 3.81 | 182.63 | 368.54 | 98.72 | 0.00 | 0.00 | 0.00 |
September | 162.68 | 0.06 | 162.62 | 274.19 | 207.74 | 0.00 | 0.00 | 0.00 |
October | 135.07 | 0.00 | 135.07 | 124.37 | 349.77 | 0.00 | 0.00 | 0.00 |
November | 109.04 | 0.00 | 109.04 | 17.44 | 631.85 | 0.00 | 0.00 | 0.00 |
December | 102.02 | 0.00 | 102.02 | 3.42 | 836.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.76 | 6.08 | 157.68 | 206.42 | 391.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.02 | 0.00 | 102.02 | 3.42 | 68.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 239.24 | 29.45 | 209.79 | 523.33 | 836.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.81 | 0.00 | 102.81 | 4.73 | 742.61 | 0.00 | 0.00 | 0.00 |
February | 125.54 | 0.00 | 125.54 | 32.90 | 649.50 | 0.00 | 0.00 | 0.00 |
March | 164.30 | 0.00 | 164.30 | 81.88 | 542.74 | 0.00 | 0.00 | 0.00 |
April | 189.70 | 1.49 | 188.21 | 195.32 | 314.42 | 0.00 | 0.00 | 0.00 |
May | 224.99 | 16.27 | 208.72 | 357.59 | 175.52 | 0.00 | 0.00 | 0.00 |
June | 239.24 | 29.45 | 209.79 | 523.33 | 89.56 | 0.00 | 0.00 | 0.00 |
July | 221.10 | 21.52 | 199.58 | 482.50 | 68.86 | 0.00 | 0.00 | 0.00 |
August | 186.44 | 3.81 | 182.63 | 368.54 | 98.71 | 0.00 | 0.00 | 0.00 |
September | 162.68 | 0.06 | 162.62 | 274.19 | 207.74 | 0.00 | 0.00 | 0.00 |
October | 135.07 | 0.00 | 135.07 | 124.37 | 349.77 | 0.00 | 0.00 | 0.00 |
November | 109.04 | 0.00 | 109.04 | 17.44 | 631.85 | 0.00 | 0.00 | 0.00 |
December | 102.02 | 0.00 | 102.02 | 3.42 | 836.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.76 | 6.08 | 157.68 | 206.42 | 391.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.02 | 0.00 | 102.02 | 3.42 | 68.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 239.24 | 29.45 | 209.79 | 523.33 | 836.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.81 | 0.00 | 102.81 | 4.73 | 742.58 | 0.00 | 0.00 | 0.00 |
February | 125.54 | 0.00 | 125.54 | 32.90 | 649.48 | 0.00 | 0.00 | 0.00 |
March | 164.29 | 0.00 | 164.29 | 81.88 | 542.72 | 0.00 | 0.00 | 0.00 |
April | 189.69 | 1.49 | 188.20 | 195.31 | 314.41 | 0.00 | 0.00 | 0.00 |
May | 224.98 | 16.27 | 208.71 | 357.57 | 175.52 | 0.00 | 0.00 | 0.00 |
June | 239.23 | 29.45 | 209.78 | 523.31 | 89.55 | 0.00 | 0.00 | 0.00 |
July | 221.09 | 21.52 | 199.57 | 482.48 | 68.85 | 0.00 | 0.00 | 0.00 |
August | 186.43 | 3.81 | 182.62 | 368.53 | 98.71 | 0.00 | 0.00 | 0.00 |
September | 162.68 | 0.06 | 162.61 | 274.17 | 207.73 | 0.00 | 0.00 | 0.00 |
October | 135.07 | 0.00 | 135.07 | 124.37 | 349.76 | 0.00 | 0.00 | 0.00 |
November | 109.04 | 0.00 | 109.04 | 17.44 | 631.82 | 0.00 | 0.00 | 0.00 |
December | 102.01 | 0.00 | 102.01 | 3.42 | 836.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.76 | 6.08 | 157.68 | 206.41 | 391.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.01 | 0.00 | 102.01 | 3.42 | 68.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 239.23 | 29.45 | 209.78 | 523.31 | 836.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 305.54 | 165.74 | 139.79 | 250.32 | 732.23 | 0.00 | 0.00 | 0.00 |
February | 408.78 | 233.00 | 175.78 | 412.96 | 637.45 | 0.00 | 0.00 | 0.00 |
March | 504.71 | 278.08 | 226.63 | 573.03 | 528.50 | 0.00 | 0.00 | 0.00 |
April | 608.15 | 337.39 | 270.76 | 863.74 | 304.17 | 0.00 | 0.00 | 0.00 |
May | 627.58 | 341.07 | 286.51 | 1033.19 | 185.62 | 0.00 | 0.00 | 0.00 |
June | 627.93 | 349.33 | 278.60 | 1198.76 | 88.96 | 0.00 | 0.00 | 0.00 |
July | 563.12 | 294.39 | 268.73 | 1085.63 | 64.71 | 0.00 | 0.00 | 0.00 |
August | 535.84 | 274.24 | 261.60 | 987.19 | 92.53 | 0.00 | 0.00 | 0.00 |
September | 530.87 | 302.90 | 227.97 | 894.41 | 206.99 | 0.00 | 0.00 | 0.00 |
October | 408.27 | 220.34 | 187.93 | 555.72 | 351.85 | 0.00 | 0.00 | 0.00 |
November | 365.98 | 213.06 | 152.92 | 361.08 | 612.05 | 0.00 | 0.00 | 0.00 |
December | 305.28 | 161.74 | 143.53 | 233.13 | 810.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 482.72 | 264.13 | 218.59 | 705.12 | 383.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 305.28 | 161.74 | 139.79 | 233.13 | 64.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 627.93 | 349.33 | 286.51 | 1198.76 | 810.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 305.54 | 165.74 | 139.79 | 250.32 | 732.23 | 0.00 | 0.00 | 0.00 |
February | 408.78 | 233.00 | 175.78 | 412.96 | 637.45 | 0.00 | 0.00 | 0.00 |
March | 504.71 | 278.08 | 226.63 | 573.03 | 528.50 | 0.00 | 0.00 | 0.00 |
April | 608.15 | 337.39 | 270.76 | 863.74 | 304.17 | 0.00 | 0.00 | 0.00 |
May | 627.58 | 341.07 | 286.51 | 1033.19 | 185.62 | 0.00 | 0.00 | 0.00 |
June | 627.93 | 349.33 | 278.60 | 1198.76 | 88.96 | 0.00 | 0.00 | 0.00 |
July | 563.12 | 294.39 | 268.73 | 1085.63 | 64.71 | 0.00 | 0.00 | 0.00 |
August | 535.84 | 274.24 | 261.60 | 987.19 | 92.53 | 0.00 | 0.00 | 0.00 |
September | 530.87 | 302.90 | 227.97 | 894.41 | 206.99 | 0.00 | 0.00 | 0.00 |
October | 408.27 | 220.34 | 187.93 | 555.72 | 351.85 | 0.00 | 0.00 | 0.00 |
November | 365.98 | 213.06 | 152.92 | 361.08 | 612.05 | 0.00 | 0.00 | 0.00 |
December | 305.28 | 161.74 | 143.53 | 233.13 | 810.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 482.72 | 264.13 | 218.59 | 705.12 | 383.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 305.28 | 161.74 | 139.79 | 233.13 | 64.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 627.93 | 349.33 | 286.51 | 1198.76 | 810.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 305.53 | 165.74 | 139.79 | 250.32 | 732.22 | 0.00 | 0.00 | 0.00 |
February | 408.77 | 233.00 | 175.78 | 412.95 | 637.44 | 0.00 | 0.00 | 0.00 |
March | 504.70 | 278.07 | 226.63 | 573.02 | 528.49 | 0.00 | 0.00 | 0.00 |
April | 608.14 | 337.38 | 270.76 | 863.73 | 304.16 | 0.00 | 0.00 | 0.00 |
May | 627.57 | 341.06 | 286.51 | 1033.17 | 185.62 | 0.00 | 0.00 | 0.00 |
June | 627.92 | 349.32 | 278.60 | 1198.74 | 88.96 | 0.00 | 0.00 | 0.00 |
July | 563.11 | 294.38 | 268.72 | 1085.61 | 64.71 | 0.00 | 0.00 | 0.00 |
August | 535.83 | 274.23 | 261.60 | 987.17 | 92.53 | 0.00 | 0.00 | 0.00 |
September | 530.86 | 302.89 | 227.97 | 894.39 | 206.98 | 0.00 | 0.00 | 0.00 |
October | 408.26 | 220.34 | 187.93 | 555.71 | 351.85 | 0.00 | 0.00 | 0.00 |
November | 365.97 | 213.06 | 152.92 | 361.07 | 612.03 | 0.00 | 0.00 | 0.00 |
December | 305.27 | 161.74 | 143.53 | 233.12 | 810.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 482.71 | 264.13 | 218.59 | 705.10 | 383.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 305.27 | 161.74 | 139.79 | 233.12 | 64.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 627.92 | 349.32 | 286.51 | 1198.74 | 810.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 703.33 | 532.85 | 170.49 | 889.32 | 623.86 | 0.00 | 0.00 | 0.00 |
February | 652.42 | 459.95 | 192.47 | 842.71 | 561.23 | 0.00 | 0.00 | 0.00 |
March | 530.23 | 305.73 | 224.50 | 704.05 | 496.87 | 0.00 | 0.00 | 0.00 |
April | 359.49 | 134.14 | 225.36 | 552.17 | 312.90 | 0.00 | 0.00 | 0.00 |
May | 254.05 | 35.56 | 218.49 | 449.38 | 184.04 | 0.00 | 0.00 | 0.00 |
June | 219.18 | 13.91 | 205.27 | 498.82 | 90.69 | 0.00 | 0.00 | 0.00 |
July | 223.43 | 20.71 | 202.72 | 504.31 | 70.19 | 0.00 | 0.00 | 0.00 |
August | 284.81 | 75.39 | 209.42 | 591.96 | 101.45 | 0.00 | 0.00 | 0.00 |
September | 444.56 | 230.96 | 213.60 | 827.69 | 207.71 | 0.00 | 0.00 | 0.00 |
October | 604.02 | 408.36 | 195.66 | 937.67 | 329.86 | 0.00 | 0.00 | 0.00 |
November | 726.89 | 554.16 | 172.73 | 977.22 | 534.90 | 0.00 | 0.00 | 0.00 |
December | 720.37 | 540.75 | 179.63 | 884.52 | 678.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 475.89 | 275.00 | 200.89 | 720.74 | 348.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 219.18 | 13.91 | 170.49 | 449.38 | 70.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 726.89 | 554.16 | 225.36 | 977.22 | 678.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 703.33 | 532.85 | 170.48 | 889.32 | 623.86 | 0.00 | 0.00 | 0.00 |
February | 652.42 | 459.95 | 192.47 | 842.71 | 561.23 | 0.00 | 0.00 | 0.00 |
March | 530.23 | 305.73 | 224.50 | 704.05 | 496.87 | 0.00 | 0.00 | 0.00 |
April | 359.49 | 134.14 | 225.36 | 552.17 | 312.90 | 0.00 | 0.00 | 0.00 |
May | 254.05 | 35.56 | 218.49 | 449.38 | 184.04 | 0.00 | 0.00 | 0.00 |
June | 219.18 | 13.91 | 205.27 | 498.82 | 90.69 | 0.00 | 0.00 | 0.00 |
July | 223.43 | 20.71 | 202.72 | 504.31 | 70.19 | 0.00 | 0.00 | 0.00 |
August | 284.81 | 75.39 | 209.42 | 591.96 | 101.45 | 0.00 | 0.00 | 0.00 |
September | 444.56 | 230.96 | 213.60 | 827.69 | 207.71 | 0.00 | 0.00 | 0.00 |
October | 604.02 | 408.36 | 195.66 | 937.67 | 329.86 | 0.00 | 0.00 | 0.00 |
November | 726.89 | 554.16 | 172.73 | 977.22 | 534.90 | 0.00 | 0.00 | 0.00 |
December | 720.37 | 540.75 | 179.63 | 884.52 | 678.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 475.89 | 275.00 | 200.89 | 720.74 | 348.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 219.18 | 13.91 | 170.48 | 449.38 | 70.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 726.89 | 554.16 | 225.36 | 977.22 | 678.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 703.33 | 532.85 | 170.49 | 889.32 | 623.86 | 0.00 | 0.00 | 0.00 |
February | 652.42 | 459.95 | 192.47 | 842.71 | 561.23 | 0.00 | 0.00 | 0.00 |
March | 530.23 | 305.73 | 224.50 | 704.05 | 496.87 | 0.00 | 0.00 | 0.00 |
April | 359.49 | 134.14 | 225.36 | 552.17 | 312.90 | 0.00 | 0.00 | 0.00 |
May | 254.05 | 35.56 | 218.49 | 449.38 | 184.04 | 0.00 | 0.00 | 0.00 |
June | 219.18 | 13.91 | 205.27 | 498.82 | 90.69 | 0.00 | 0.00 | 0.00 |
July | 223.43 | 20.71 | 202.72 | 504.31 | 70.19 | 0.00 | 0.00 | 0.00 |
August | 284.81 | 75.39 | 209.42 | 591.96 | 101.45 | 0.00 | 0.00 | 0.00 |
September | 444.56 | 230.96 | 213.60 | 827.69 | 207.71 | 0.00 | 0.00 | 0.00 |
October | 604.02 | 408.36 | 195.66 | 937.67 | 329.86 | 0.00 | 0.00 | 0.00 |
November | 726.89 | 554.16 | 172.73 | 977.22 | 534.90 | 0.00 | 0.00 | 0.00 |
December | 720.37 | 540.75 | 179.63 | 884.52 | 678.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 475.89 | 275.00 | 200.89 | 720.74 | 348.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 219.18 | 13.91 | 170.49 | 449.38 | 70.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 726.89 | 554.16 | 225.36 | 977.22 | 678.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 703.33 | 532.85 | 170.48 | 889.32 | 623.86 | 0.00 | 0.00 | 0.00 |
February | 652.42 | 459.95 | 192.47 | 842.71 | 561.23 | 0.00 | 0.00 | 0.00 |
March | 530.23 | 305.73 | 224.50 | 704.05 | 496.87 | 0.00 | 0.00 | 0.00 |
April | 359.49 | 134.14 | 225.36 | 552.17 | 312.90 | 0.00 | 0.00 | 0.00 |
May | 254.05 | 35.56 | 218.49 | 449.38 | 184.04 | 0.00 | 0.00 | 0.00 |
June | 219.18 | 13.91 | 205.27 | 498.82 | 90.69 | 0.00 | 0.00 | 0.00 |
July | 223.43 | 20.71 | 202.72 | 504.31 | 70.19 | 0.00 | 0.00 | 0.00 |
August | 284.81 | 75.39 | 209.42 | 591.96 | 101.45 | 0.00 | 0.00 | 0.00 |
September | 444.56 | 230.96 | 213.60 | 827.69 | 207.71 | 0.00 | 0.00 | 0.00 |
October | 604.02 | 408.36 | 195.66 | 937.67 | 329.86 | 0.00 | 0.00 | 0.00 |
November | 726.89 | 554.16 | 172.73 | 977.22 | 534.90 | 0.00 | 0.00 | 0.00 |
December | 720.37 | 540.75 | 179.63 | 884.52 | 678.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 475.89 | 275.00 | 200.89 | 720.74 | 348.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 219.18 | 13.91 | 170.48 | 449.38 | 70.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 726.89 | 554.16 | 225.36 | 977.22 | 678.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 703.31 | 532.83 | 170.48 | 889.28 | 623.84 | 0.00 | 0.00 | 0.00 |
February | 652.39 | 459.93 | 192.47 | 842.67 | 561.21 | 0.00 | 0.00 | 0.00 |
March | 530.21 | 305.72 | 224.49 | 704.02 | 496.85 | 0.00 | 0.00 | 0.00 |
April | 359.48 | 134.13 | 225.35 | 552.15 | 312.88 | 0.00 | 0.00 | 0.00 |
May | 254.04 | 35.56 | 218.48 | 449.37 | 184.03 | 0.00 | 0.00 | 0.00 |
June | 219.17 | 13.91 | 205.26 | 498.80 | 90.69 | 0.00 | 0.00 | 0.00 |
July | 223.42 | 20.71 | 202.71 | 504.29 | 70.19 | 0.00 | 0.00 | 0.00 |
August | 284.80 | 75.39 | 209.41 | 591.93 | 101.45 | 0.00 | 0.00 | 0.00 |
September | 444.54 | 230.95 | 213.59 | 827.66 | 207.70 | 0.00 | 0.00 | 0.00 |
October | 604.00 | 408.34 | 195.66 | 937.63 | 329.84 | 0.00 | 0.00 | 0.00 |
November | 726.86 | 554.14 | 172.72 | 977.18 | 534.88 | 0.00 | 0.00 | 0.00 |
December | 720.35 | 540.72 | 179.62 | 884.49 | 678.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 475.87 | 274.98 | 200.88 | 720.71 | 348.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 219.17 | 13.91 | 170.48 | 449.37 | 70.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 726.86 | 554.14 | 225.35 | 977.18 | 678.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 321.85 | 181.26 | 140.59 | 309.30 | 816.34 | 0.00 | 0.00 | 0.00 |
February | 363.17 | 193.04 | 170.14 | 382.45 | 727.01 | 0.00 | 0.00 | 0.00 |
March | 494.90 | 265.25 | 229.65 | 584.98 | 632.40 | 0.00 | 0.00 | 0.00 |
April | 568.85 | 307.25 | 261.60 | 809.87 | 411.59 | 0.00 | 0.00 | 0.00 |
May | 612.71 | 327.83 | 284.88 | 1019.71 | 237.34 | 0.00 | 0.00 | 0.00 |
June | 596.42 | 320.34 | 276.08 | 1134.97 | 128.76 | 0.00 | 0.00 | 0.00 |
July | 529.28 | 263.01 | 266.27 | 1003.15 | 107.60 | 0.00 | 0.00 | 0.00 |
August | 512.58 | 261.23 | 251.35 | 921.03 | 151.59 | 0.00 | 0.00 | 0.00 |
September | 524.20 | 292.03 | 232.17 | 903.88 | 261.29 | 0.00 | 0.00 | 0.00 |
October | 451.25 | 263.36 | 187.88 | 650.72 | 418.97 | 0.00 | 0.00 | 0.00 |
November | 378.75 | 230.62 | 148.13 | 426.23 | 715.83 | 0.00 | 0.00 | 0.00 |
December | 305.22 | 165.81 | 139.42 | 266.56 | 940.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 471.99 | 256.09 | 215.90 | 702.40 | 461.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 305.22 | 165.81 | 139.42 | 266.56 | 107.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 612.71 | 327.83 | 284.88 | 1134.97 | 940.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 321.85 | 181.26 | 140.59 | 309.30 | 816.34 | 0.00 | 0.00 | 0.00 |
February | 363.17 | 193.04 | 170.14 | 382.45 | 727.01 | 0.00 | 0.00 | 0.00 |
March | 494.90 | 265.25 | 229.65 | 584.98 | 632.40 | 0.00 | 0.00 | 0.00 |
April | 568.85 | 307.25 | 261.60 | 809.87 | 411.59 | 0.00 | 0.00 | 0.00 |
May | 612.71 | 327.83 | 284.88 | 1019.71 | 237.34 | 0.00 | 0.00 | 0.00 |
June | 596.42 | 320.34 | 276.08 | 1134.97 | 128.76 | 0.00 | 0.00 | 0.00 |
July | 529.28 | 263.01 | 266.27 | 1003.15 | 107.60 | 0.00 | 0.00 | 0.00 |
August | 512.58 | 261.23 | 251.35 | 921.03 | 151.59 | 0.00 | 0.00 | 0.00 |
September | 524.20 | 292.03 | 232.17 | 903.88 | 261.29 | 0.00 | 0.00 | 0.00 |
October | 451.25 | 263.36 | 187.88 | 650.72 | 418.97 | 0.00 | 0.00 | 0.00 |
November | 378.75 | 230.62 | 148.13 | 426.23 | 715.83 | 0.00 | 0.00 | 0.00 |
December | 305.22 | 165.81 | 139.42 | 266.56 | 940.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 471.99 | 256.09 | 215.90 | 702.40 | 461.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 305.22 | 165.81 | 139.42 | 266.56 | 107.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 612.71 | 327.83 | 284.88 | 1134.97 | 940.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 321.84 | 181.25 | 140.59 | 309.29 | 816.33 | 0.00 | 0.00 | 0.00 |
February | 363.17 | 193.03 | 170.14 | 382.44 | 727.00 | 0.00 | 0.00 | 0.00 |
March | 494.89 | 265.25 | 229.65 | 584.97 | 632.39 | 0.00 | 0.00 | 0.00 |
April | 568.84 | 307.24 | 261.60 | 809.85 | 411.58 | 0.00 | 0.00 | 0.00 |
May | 612.69 | 327.82 | 284.88 | 1019.69 | 237.34 | 0.00 | 0.00 | 0.00 |
June | 596.41 | 320.34 | 276.07 | 1134.95 | 128.75 | 0.00 | 0.00 | 0.00 |
July | 529.27 | 263.01 | 266.27 | 1003.13 | 107.59 | 0.00 | 0.00 | 0.00 |
August | 512.57 | 261.23 | 251.35 | 921.01 | 151.59 | 0.00 | 0.00 | 0.00 |
September | 524.19 | 292.02 | 232.16 | 903.87 | 261.28 | 0.00 | 0.00 | 0.00 |
October | 451.24 | 263.36 | 187.88 | 650.71 | 418.96 | 0.00 | 0.00 | 0.00 |
November | 378.75 | 230.62 | 148.13 | 426.22 | 715.82 | 0.00 | 0.00 | 0.00 |
December | 305.22 | 165.80 | 139.41 | 266.56 | 940.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 471.98 | 256.08 | 215.90 | 702.39 | 461.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 305.22 | 165.80 | 139.41 | 266.56 | 107.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 612.69 | 327.82 | 284.88 | 1134.95 | 940.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 514.06 | 0.00 | 514.06 | 53.73 | 3351.92 | 0.00 | 0.00 | 0.00 |
February | 627.72 | 0.00 | 627.72 | 214.35 | 2981.15 | 0.00 | 0.00 | 0.00 |
March | 821.48 | 0.00 | 821.48 | 467.36 | 2492.39 | 0.00 | 0.00 | 0.00 |
April | 948.49 | 7.47 | 941.01 | 1047.70 | 1430.66 | 0.00 | 0.00 | 0.00 |
May | 1124.94 | 81.35 | 1043.59 | 1826.08 | 820.76 | 0.00 | 0.00 | 0.00 |
June | 1196.18 | 147.26 | 1048.92 | 2648.30 | 441.73 | 0.00 | 0.00 | 0.00 |
July | 1105.50 | 107.61 | 997.89 | 2445.75 | 349.94 | 0.00 | 0.00 | 0.00 |
August | 932.18 | 19.06 | 913.12 | 1888.21 | 483.23 | 0.00 | 0.00 | 0.00 |
September | 813.41 | 0.32 | 813.09 | 1412.50 | 962.59 | 0.00 | 0.00 | 0.00 |
October | 675.36 | 0.00 | 675.36 | 681.76 | 1578.23 | 0.00 | 0.00 | 0.00 |
November | 545.21 | 0.00 | 545.21 | 136.23 | 2812.40 | 0.00 | 0.00 | 0.00 |
December | 510.07 | 0.00 | 510.07 | 37.78 | 3730.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 818.81 | 30.41 | 788.40 | 1076.07 | 1780.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 510.07 | 0.00 | 510.07 | 37.78 | 349.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1196.18 | 147.26 | 1048.92 | 2648.30 | 3730.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 916.61 | 497.23 | 419.38 | 765.41 | 2052.79 | 0.00 | 0.00 | 0.00 |
February | 1226.33 | 699.00 | 527.33 | 1244.05 | 1817.01 | 0.00 | 0.00 | 0.00 |
March | 1514.12 | 834.23 | 679.89 | 1704.57 | 1513.65 | 0.00 | 0.00 | 0.00 |
April | 1824.43 | 1012.15 | 812.28 | 2564.33 | 883.72 | 0.00 | 0.00 | 0.00 |
May | 1882.72 | 1023.19 | 859.53 | 3069.85 | 533.57 | 0.00 | 0.00 | 0.00 |
June | 1883.78 | 1047.98 | 835.80 | 3560.16 | 280.73 | 0.00 | 0.00 | 0.00 |
July | 1689.34 | 883.16 | 806.18 | 3217.90 | 225.67 | 0.00 | 0.00 | 0.00 |
August | 1607.50 | 822.70 | 784.79 | 2924.82 | 308.75 | 0.00 | 0.00 | 0.00 |
September | 1592.59 | 908.69 | 683.90 | 2664.17 | 595.16 | 0.00 | 0.00 | 0.00 |
October | 1224.80 | 661.01 | 563.79 | 1659.26 | 988.24 | 0.00 | 0.00 | 0.00 |
November | 1097.93 | 639.18 | 458.75 | 1091.70 | 1711.90 | 0.00 | 0.00 | 0.00 |
December | 915.82 | 485.22 | 430.60 | 721.17 | 2274.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1448.16 | 792.39 | 655.77 | 2101.91 | 1095.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 915.82 | 485.22 | 419.38 | 721.17 | 225.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1883.78 | 1047.98 | 859.53 | 3560.16 | 2274.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3516.63 | 2664.21 | 852.41 | 4388.46 | 3066.05 | 0.00 | 0.00 | 0.00 |
February | 3262.06 | 2299.70 | 962.36 | 4151.33 | 2771.08 | 0.00 | 0.00 | 0.00 |
March | 2651.10 | 1528.62 | 1122.48 | 3469.18 | 2427.20 | 0.00 | 0.00 | 0.00 |
April | 1797.44 | 670.67 | 1126.77 | 2758.16 | 1494.39 | 0.00 | 0.00 | 0.00 |
May | 1270.23 | 177.79 | 1092.44 | 2264.13 | 873.97 | 0.00 | 0.00 | 0.00 |
June | 1095.89 | 69.53 | 1026.35 | 2534.65 | 445.18 | 0.00 | 0.00 | 0.00 |
July | 1117.14 | 103.56 | 1013.58 | 2556.27 | 358.13 | 0.00 | 0.00 | 0.00 |
August | 1424.04 | 376.95 | 1047.09 | 2979.99 | 510.09 | 0.00 | 0.00 | 0.00 |
September | 2222.77 | 1154.81 | 1067.96 | 4118.03 | 1006.23 | 0.00 | 0.00 | 0.00 |
October | 3020.09 | 2041.78 | 978.31 | 4645.48 | 1604.47 | 0.00 | 0.00 | 0.00 |
November | 3634.40 | 2770.78 | 863.62 | 4837.48 | 2609.87 | 0.00 | 0.00 | 0.00 |
December | 3601.83 | 2703.70 | 898.13 | 4388.82 | 3302.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2379.41 | 1374.96 | 1004.45 | 3586.71 | 1700.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1095.89 | 69.53 | 852.41 | 2264.13 | 358.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3634.40 | 2770.78 | 1126.77 | 4837.48 | 3302.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 965.54 | 543.77 | 421.78 | 963.17 | 2195.36 | 0.00 | 0.00 | 0.00 |
February | 1089.51 | 579.10 | 510.41 | 1181.32 | 1982.74 | 0.00 | 0.00 | 0.00 |
March | 1484.69 | 795.74 | 688.95 | 1801.49 | 1688.38 | 0.00 | 0.00 | 0.00 |
April | 1706.53 | 921.73 | 784.80 | 2510.78 | 1039.11 | 0.00 | 0.00 | 0.00 |
May | 1838.10 | 983.47 | 854.63 | 3080.06 | 638.35 | 0.00 | 0.00 | 0.00 |
June | 1789.25 | 961.02 | 828.22 | 3451.36 | 343.56 | 0.00 | 0.00 | 0.00 |
July | 1587.83 | 789.02 | 798.81 | 3079.15 | 279.22 | 0.00 | 0.00 | 0.00 |
August | 1537.73 | 783.69 | 754.04 | 2841.34 | 373.83 | 0.00 | 0.00 | 0.00 |
September | 1572.57 | 876.08 | 696.49 | 2745.50 | 700.08 | 0.00 | 0.00 | 0.00 |
October | 1353.73 | 790.08 | 563.65 | 2000.87 | 1102.87 | 0.00 | 0.00 | 0.00 |
November | 1136.25 | 691.86 | 444.40 | 1333.01 | 1866.41 | 0.00 | 0.00 | 0.00 |
December | 915.65 | 497.41 | 418.24 | 859.40 | 2414.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1415.96 | 768.26 | 647.70 | 2158.04 | 1214.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 915.65 | 497.41 | 418.24 | 859.40 | 279.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1838.10 | 983.47 | 854.63 | 3451.36 | 2414.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 514.06 | 0.00 | 514.06 | 88.80 | 2996.44 | 0.00 | 0.00 | 0.00 |
February | 627.72 | 0.00 | 627.72 | 255.28 | 2689.29 | 0.00 | 0.00 | 0.00 |
March | 821.48 | 0.00 | 821.48 | 504.79 | 2270.09 | 0.00 | 0.00 | 0.00 |
April | 948.49 | 7.47 | 941.01 | 1060.38 | 1319.47 | 0.00 | 0.00 | 0.00 |
May | 1124.94 | 81.35 | 1043.59 | 1818.82 | 777.72 | 0.00 | 0.00 | 0.00 |
June | 1196.18 | 147.26 | 1048.92 | 2609.45 | 435.04 | 0.00 | 0.00 | 0.00 |
July | 1105.50 | 107.61 | 997.89 | 2404.35 | 347.76 | 0.00 | 0.00 | 0.00 |
August | 932.18 | 19.06 | 913.12 | 1862.89 | 460.38 | 0.00 | 0.00 | 0.00 |
September | 813.41 | 0.32 | 813.09 | 1408.66 | 902.93 | 0.00 | 0.00 | 0.00 |
October | 675.36 | 0.00 | 675.36 | 714.71 | 1418.49 | 0.00 | 0.00 | 0.00 |
November | 545.21 | 0.00 | 545.21 | 172.90 | 2478.47 | 0.00 | 0.00 | 0.00 |
December | 510.07 | 0.00 | 510.07 | 66.52 | 3341.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 818.81 | 30.41 | 788.40 | 1084.87 | 1614.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 510.07 | 0.00 | 510.07 | 66.52 | 347.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1196.18 | 147.26 | 1048.92 | 2609.45 | 3341.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 916.61 | 497.23 | 419.38 | 825.42 | 1824.54 | 0.00 | 0.00 | 0.00 |
February | 1226.33 | 699.00 | 527.33 | 1304.36 | 1639.75 | 0.00 | 0.00 | 0.00 |
March | 1514.12 | 834.23 | 679.89 | 1747.40 | 1400.68 | 0.00 | 0.00 | 0.00 |
April | 1824.43 | 1012.15 | 812.28 | 2566.11 | 838.84 | 0.00 | 0.00 | 0.00 |
May | 1882.72 | 1023.19 | 859.53 | 3051.37 | 517.50 | 0.00 | 0.00 | 0.00 |
June | 1883.78 | 1047.98 | 835.80 | 3525.52 | 281.17 | 0.00 | 0.00 | 0.00 |
July | 1689.34 | 883.16 | 806.18 | 3179.60 | 228.44 | 0.00 | 0.00 | 0.00 |
August | 1607.50 | 822.70 | 784.79 | 2899.21 | 302.09 | 0.00 | 0.00 | 0.00 |
September | 1592.59 | 908.69 | 683.90 | 2654.57 | 574.37 | 0.00 | 0.00 | 0.00 |
October | 1224.80 | 661.01 | 563.79 | 1678.48 | 912.28 | 0.00 | 0.00 | 0.00 |
November | 1097.93 | 639.18 | 458.75 | 1152.32 | 1525.04 | 0.00 | 0.00 | 0.00 |
December | 915.82 | 485.22 | 430.60 | 784.02 | 2024.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1448.16 | 792.39 | 655.77 | 2116.73 | 1002.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 915.82 | 485.22 | 419.38 | 784.02 | 228.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1883.78 | 1047.98 | 859.53 | 3525.52 | 2024.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3516.63 | 2664.21 | 852.41 | 4458.34 | 2754.31 | 0.00 | 0.00 | 0.00 |
February | 3262.06 | 2299.70 | 962.36 | 4208.04 | 2515.19 | 0.00 | 0.00 | 0.00 |
March | 2651.10 | 1528.62 | 1122.48 | 3501.66 | 2233.80 | 0.00 | 0.00 | 0.00 |
April | 1797.44 | 670.67 | 1126.77 | 2752.41 | 1395.91 | 0.00 | 0.00 | 0.00 |
May | 1270.23 | 177.79 | 1092.44 | 2237.15 | 830.47 | 0.00 | 0.00 | 0.00 |
June | 1095.89 | 69.53 | 1026.35 | 2489.06 | 439.15 | 0.00 | 0.00 | 0.00 |
July | 1117.14 | 103.56 | 1013.58 | 2503.98 | 357.25 | 0.00 | 0.00 | 0.00 |
August | 1424.04 | 376.95 | 1047.09 | 2941.78 | 490.63 | 0.00 | 0.00 | 0.00 |
September | 2222.77 | 1154.81 | 1067.96 | 4097.13 | 956.23 | 0.00 | 0.00 | 0.00 |
October | 3020.09 | 2041.78 | 978.31 | 4659.39 | 1475.78 | 0.00 | 0.00 | 0.00 |
November | 3634.40 | 2770.78 | 863.62 | 4907.36 | 2339.83 | 0.00 | 0.00 | 0.00 |
December | 3601.83 | 2703.70 | 898.13 | 4485.06 | 2971.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2379.41 | 1374.96 | 1004.45 | 3598.94 | 1558.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1095.89 | 69.53 | 852.41 | 2237.15 | 357.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3634.40 | 2770.78 | 1126.77 | 4907.36 | 2971.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 965.54 | 543.77 | 421.78 | 975.15 | 2014.10 | 0.00 | 0.00 | 0.00 |
February | 1089.51 | 579.10 | 510.41 | 1190.67 | 1831.28 | 0.00 | 0.00 | 0.00 |
March | 1484.69 | 795.74 | 688.95 | 1799.51 | 1569.01 | 0.00 | 0.00 | 0.00 |
April | 1706.53 | 921.73 | 784.80 | 2497.53 | 978.40 | 0.00 | 0.00 | 0.00 |
May | 1838.10 | 983.47 | 854.63 | 3056.26 | 609.65 | 0.00 | 0.00 | 0.00 |
June | 1789.25 | 961.02 | 828.22 | 3420.47 | 337.46 | 0.00 | 0.00 | 0.00 |
July | 1587.83 | 789.02 | 798.81 | 3048.52 | 275.56 | 0.00 | 0.00 | 0.00 |
August | 1537.73 | 783.69 | 754.04 | 2817.99 | 359.49 | 0.00 | 0.00 | 0.00 |
September | 1572.57 | 876.08 | 696.49 | 2731.55 | 668.73 | 0.00 | 0.00 | 0.00 |
October | 1353.73 | 790.08 | 563.65 | 2000.08 | 1024.51 | 0.00 | 0.00 | 0.00 |
November | 1136.25 | 691.86 | 444.40 | 1343.50 | 1696.43 | 0.00 | 0.00 | 0.00 |
December | 915.65 | 497.41 | 418.24 | 877.65 | 2207.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1415.96 | 768.26 | 647.70 | 2150.58 | 1127.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 915.65 | 497.41 | 418.24 | 877.65 | 275.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1838.10 | 983.47 | 854.63 | 3420.47 | 2207.61 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275372E+09 | 0.00 | 0.275372E+09 | 12661403.77 | 0.198901E+10 |
February | 0.303718E+09 | 0.00 | 0.303718E+09 | 79586370.94 | 0.157127E+10 |
March | 0.440054E+09 | 0.00 | 0.440054E+09 | 0.219311E+09 | 0.145368E+10 |
April | 0.491702E+09 | 3873897.34 | 0.487828E+09 | 0.506262E+09 | 0.814981E+09 |
May | 0.602615E+09 | 43577493.91 | 0.559038E+09 | 0.957764E+09 | 0.470120E+09 |
June | 0.620108E+09 | 76342543.16 | 0.543765E+09 | 0.135648E+10 | 0.232129E+09 |
July | 0.592204E+09 | 57646476.54 | 0.534557E+09 | 0.129234E+10 | 0.184423E+09 |
August | 0.499356E+09 | 10210545.39 | 0.489146E+09 | 0.987106E+09 | 0.264398E+09 |
September | 0.421677E+09 | 168264.50 | 0.421509E+09 | 0.710688E+09 | 0.538451E+09 |
October | 0.361779E+09 | 0.00 | 0.361779E+09 | 0.333113E+09 | 0.936836E+09 |
November | 0.282641E+09 | 0.00 | 0.282641E+09 | 45198962.22 | 0.163774E+10 |
December | 0.273240E+09 | 0.00 | 0.273240E+09 | 9159723.19 | 0.224061E+10 |
Annual Sum or Average | 0.516447E+10 | 0.191819E+09 | 0.497265E+10 | 0.650967E+10 | 0.123337E+11 |
Minimum of Months | 0.273240E+09 | 0.00 | 0.273240E+09 | 9159723.19 | 0.184423E+09 |
Maximum of Months | 0.620108E+09 | 76342543.16 | 0.559038E+09 | 0.135648E+10 | 0.224061E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275372E+09 | 0.00 | 0.275372E+09 | 12661353.62 | 0.198901E+10 |
February | 0.303717E+09 | 0.00 | 0.303717E+09 | 79586274.24 | 0.157127E+10 |
March | 0.440054E+09 | 0.00 | 0.440054E+09 | 0.219311E+09 | 0.145368E+10 |
April | 0.491701E+09 | 3873892.69 | 0.487827E+09 | 0.506262E+09 | 0.814980E+09 |
May | 0.602615E+09 | 43577441.62 | 0.559037E+09 | 0.957764E+09 | 0.470120E+09 |
June | 0.620108E+09 | 76342451.56 | 0.543765E+09 | 0.135648E+10 | 0.232128E+09 |
July | 0.592203E+09 | 57646407.37 | 0.534557E+09 | 0.129234E+10 | 0.184423E+09 |
August | 0.499356E+09 | 10210533.14 | 0.489146E+09 | 0.987106E+09 | 0.264398E+09 |
September | 0.421677E+09 | 168264.30 | 0.421509E+09 | 0.710688E+09 | 0.538451E+09 |
October | 0.361779E+09 | 0.00 | 0.361779E+09 | 0.333113E+09 | 0.936836E+09 |
November | 0.282641E+09 | 0.00 | 0.282641E+09 | 45198909.33 | 0.163774E+10 |
December | 0.273240E+09 | 0.00 | 0.273240E+09 | 9159689.98 | 0.224061E+10 |
Annual Sum or Average | 0.516446E+10 | 0.191819E+09 | 0.497264E+10 | 0.650967E+10 | 0.123337E+11 |
Minimum of Months | 0.273240E+09 | 0.00 | 0.273240E+09 | 9159689.98 | 0.184423E+09 |
Maximum of Months | 0.620108E+09 | 76342451.56 | 0.559037E+09 | 0.135648E+10 | 0.224061E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275372E+09 | 0.00 | 0.275372E+09 | 12661403.77 | 0.198901E+10 |
February | 0.303718E+09 | 0.00 | 0.303718E+09 | 79586370.94 | 0.157127E+10 |
March | 0.440054E+09 | 0.00 | 0.440054E+09 | 0.219311E+09 | 0.145368E+10 |
April | 0.491702E+09 | 3873897.34 | 0.487828E+09 | 0.506262E+09 | 0.814981E+09 |
May | 0.602615E+09 | 43577493.91 | 0.559038E+09 | 0.957764E+09 | 0.470120E+09 |
June | 0.620108E+09 | 76342543.16 | 0.543765E+09 | 0.135648E+10 | 0.232129E+09 |
July | 0.592204E+09 | 57646476.54 | 0.534557E+09 | 0.129234E+10 | 0.184423E+09 |
August | 0.499356E+09 | 10210545.39 | 0.489146E+09 | 0.987106E+09 | 0.264398E+09 |
September | 0.421677E+09 | 168264.50 | 0.421509E+09 | 0.710688E+09 | 0.538451E+09 |
October | 0.361779E+09 | 0.00 | 0.361779E+09 | 0.333113E+09 | 0.936836E+09 |
November | 0.282641E+09 | 0.00 | 0.282641E+09 | 45198962.22 | 0.163774E+10 |
December | 0.273240E+09 | 0.00 | 0.273240E+09 | 9159723.19 | 0.224061E+10 |
Annual Sum or Average | 0.516447E+10 | 0.191819E+09 | 0.497265E+10 | 0.650967E+10 | 0.123337E+11 |
Minimum of Months | 0.273240E+09 | 0.00 | 0.273240E+09 | 9159723.19 | 0.184423E+09 |
Maximum of Months | 0.620108E+09 | 76342543.16 | 0.559038E+09 | 0.135648E+10 | 0.224061E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275372E+09 | 0.00 | 0.275372E+09 | 12661353.62 | 0.198901E+10 |
February | 0.303717E+09 | 0.00 | 0.303717E+09 | 79586274.24 | 0.157127E+10 |
March | 0.440054E+09 | 0.00 | 0.440054E+09 | 0.219311E+09 | 0.145368E+10 |
April | 0.491701E+09 | 3873892.69 | 0.487827E+09 | 0.506262E+09 | 0.814980E+09 |
May | 0.602615E+09 | 43577441.62 | 0.559037E+09 | 0.957764E+09 | 0.470120E+09 |
June | 0.620108E+09 | 76342451.56 | 0.543765E+09 | 0.135648E+10 | 0.232128E+09 |
July | 0.592203E+09 | 57646407.37 | 0.534557E+09 | 0.129234E+10 | 0.184423E+09 |
August | 0.499356E+09 | 10210533.14 | 0.489146E+09 | 0.987106E+09 | 0.264398E+09 |
September | 0.421677E+09 | 168264.30 | 0.421509E+09 | 0.710688E+09 | 0.538451E+09 |
October | 0.361779E+09 | 0.00 | 0.361779E+09 | 0.333113E+09 | 0.936836E+09 |
November | 0.282641E+09 | 0.00 | 0.282641E+09 | 45198909.33 | 0.163774E+10 |
December | 0.273240E+09 | 0.00 | 0.273240E+09 | 9159689.98 | 0.224061E+10 |
Annual Sum or Average | 0.516446E+10 | 0.191819E+09 | 0.497264E+10 | 0.650967E+10 | 0.123337E+11 |
Minimum of Months | 0.273240E+09 | 0.00 | 0.273240E+09 | 9159689.98 | 0.184423E+09 |
Maximum of Months | 0.620108E+09 | 76342451.56 | 0.559037E+09 | 0.135648E+10 | 0.224061E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275361E+09 | 0.00 | 0.275361E+09 | 12660893.46 | 0.198893E+10 |
February | 0.303705E+09 | 0.00 | 0.303705E+09 | 79583163.26 | 0.157121E+10 |
March | 0.440036E+09 | 0.00 | 0.440036E+09 | 0.219302E+09 | 0.145362E+10 |
April | 0.491682E+09 | 3873741.21 | 0.487808E+09 | 0.506242E+09 | 0.814948E+09 |
May | 0.602591E+09 | 43575737.54 | 0.559015E+09 | 0.957726E+09 | 0.470101E+09 |
June | 0.620083E+09 | 76339466.22 | 0.543744E+09 | 0.135643E+10 | 0.232119E+09 |
July | 0.592180E+09 | 57644153.13 | 0.534536E+09 | 0.129229E+10 | 0.184416E+09 |
August | 0.499336E+09 | 10210133.86 | 0.489126E+09 | 0.987066E+09 | 0.264388E+09 |
September | 0.421660E+09 | 168257.72 | 0.421492E+09 | 0.710660E+09 | 0.538430E+09 |
October | 0.361765E+09 | 0.00 | 0.361765E+09 | 0.333100E+09 | 0.936799E+09 |
November | 0.282630E+09 | 0.00 | 0.282630E+09 | 45197140.50 | 0.163768E+10 |
December | 0.273229E+09 | 0.00 | 0.273229E+09 | 9159354.01 | 0.224052E+10 |
Annual Sum or Average | 0.516426E+10 | 0.191811E+09 | 0.497245E+10 | 0.650941E+10 | 0.123332E+11 |
Minimum of Months | 0.273229E+09 | 0.00 | 0.273229E+09 | 9159354.01 | 0.184416E+09 |
Maximum of Months | 0.620083E+09 | 76339466.22 | 0.559015E+09 | 0.135643E+10 | 0.224052E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.818354E+09 | 0.443927E+09 | 0.374426E+09 | 0.670468E+09 | 0.196121E+10 |
February | 0.988923E+09 | 0.563680E+09 | 0.425243E+09 | 0.999029E+09 | 0.154213E+10 |
March | 0.135182E+10 | 0.744808E+09 | 0.607009E+09 | 0.153481E+10 | 0.141553E+10 |
April | 0.157633E+10 | 0.874509E+09 | 0.701818E+09 | 0.223882E+10 | 0.788398E+09 |
May | 0.168091E+10 | 0.913510E+09 | 0.767396E+09 | 0.276731E+10 | 0.497168E+09 |
June | 0.162760E+10 | 0.905465E+09 | 0.722134E+09 | 0.310719E+10 | 0.230593E+09 |
July | 0.150826E+10 | 0.788490E+09 | 0.719765E+09 | 0.290775E+10 | 0.173320E+09 |
August | 0.143519E+10 | 0.734516E+09 | 0.700671E+09 | 0.264409E+10 | 0.247843E+09 |
September | 0.137601E+10 | 0.785116E+09 | 0.590897E+09 | 0.231831E+10 | 0.536510E+09 |
October | 0.109352E+10 | 0.590160E+09 | 0.503356E+09 | 0.148843E+10 | 0.942400E+09 |
November | 0.948620E+09 | 0.552256E+09 | 0.396364E+09 | 0.935910E+09 | 0.158642E+10 |
December | 0.817651E+09 | 0.433210E+09 | 0.384441E+09 | 0.624403E+09 | 0.217001E+10 |
Annual Sum or Average | 0.152232E+11 | 0.832965E+10 | 0.689352E+10 | 0.222365E+11 | 0.120915E+11 |
Minimum of Months | 0.817651E+09 | 0.433210E+09 | 0.374426E+09 | 0.624403E+09 | 0.173320E+09 |
Maximum of Months | 0.168091E+10 | 0.913510E+09 | 0.767396E+09 | 0.310719E+10 | 0.217001E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.818354E+09 | 0.443927E+09 | 0.374426E+09 | 0.670468E+09 | 0.196121E+10 |
February | 0.988923E+09 | 0.563680E+09 | 0.425243E+09 | 0.999029E+09 | 0.154213E+10 |
March | 0.135182E+10 | 0.744808E+09 | 0.607009E+09 | 0.153481E+10 | 0.141553E+10 |
April | 0.157633E+10 | 0.874509E+09 | 0.701818E+09 | 0.223882E+10 | 0.788398E+09 |
May | 0.168091E+10 | 0.913510E+09 | 0.767396E+09 | 0.276731E+10 | 0.497168E+09 |
June | 0.162760E+10 | 0.905465E+09 | 0.722134E+09 | 0.310719E+10 | 0.230593E+09 |
July | 0.150826E+10 | 0.788490E+09 | 0.719765E+09 | 0.290775E+10 | 0.173320E+09 |
August | 0.143519E+10 | 0.734516E+09 | 0.700671E+09 | 0.264409E+10 | 0.247843E+09 |
September | 0.137601E+10 | 0.785116E+09 | 0.590897E+09 | 0.231831E+10 | 0.536510E+09 |
October | 0.109352E+10 | 0.590160E+09 | 0.503356E+09 | 0.148843E+10 | 0.942400E+09 |
November | 0.948620E+09 | 0.552256E+09 | 0.396364E+09 | 0.935910E+09 | 0.158642E+10 |
December | 0.817651E+09 | 0.433210E+09 | 0.384441E+09 | 0.624403E+09 | 0.217001E+10 |
Annual Sum or Average | 0.152232E+11 | 0.832965E+10 | 0.689352E+10 | 0.222365E+11 | 0.120915E+11 |
Minimum of Months | 0.817651E+09 | 0.433210E+09 | 0.374426E+09 | 0.624403E+09 | 0.173320E+09 |
Maximum of Months | 0.168091E+10 | 0.913510E+09 | 0.767396E+09 | 0.310719E+10 | 0.217001E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.818339E+09 | 0.443919E+09 | 0.374419E+09 | 0.670455E+09 | 0.196117E+10 |
February | 0.988905E+09 | 0.563669E+09 | 0.425235E+09 | 0.999011E+09 | 0.154210E+10 |
March | 0.135179E+10 | 0.744794E+09 | 0.606998E+09 | 0.153478E+10 | 0.141550E+10 |
April | 0.157630E+10 | 0.874493E+09 | 0.701805E+09 | 0.223878E+10 | 0.788384E+09 |
May | 0.168088E+10 | 0.913494E+09 | 0.767382E+09 | 0.276725E+10 | 0.497159E+09 |
June | 0.162757E+10 | 0.905449E+09 | 0.722121E+09 | 0.310713E+10 | 0.230589E+09 |
July | 0.150823E+10 | 0.788476E+09 | 0.719752E+09 | 0.290770E+10 | 0.173316E+09 |
August | 0.143516E+10 | 0.734502E+09 | 0.700659E+09 | 0.264405E+10 | 0.247838E+09 |
September | 0.137599E+10 | 0.785102E+09 | 0.590886E+09 | 0.231827E+10 | 0.536500E+09 |
October | 0.109350E+10 | 0.590149E+09 | 0.503347E+09 | 0.148840E+10 | 0.942382E+09 |
November | 0.948603E+09 | 0.552246E+09 | 0.396357E+09 | 0.935893E+09 | 0.158639E+10 |
December | 0.817636E+09 | 0.433202E+09 | 0.384434E+09 | 0.624391E+09 | 0.216997E+10 |
Annual Sum or Average | 0.152229E+11 | 0.832950E+10 | 0.689340E+10 | 0.222361E+11 | 0.120913E+11 |
Minimum of Months | 0.817636E+09 | 0.433202E+09 | 0.374419E+09 | 0.624391E+09 | 0.173316E+09 |
Maximum of Months | 0.168088E+10 | 0.913494E+09 | 0.767382E+09 | 0.310713E+10 | 0.216997E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188381E+10 | 0.142718E+10 | 0.456627E+09 | 0.238195E+10 | 0.167095E+10 |
February | 0.157834E+10 | 0.111270E+10 | 0.465634E+09 | 0.203868E+10 | 0.135773E+10 |
March | 0.142016E+10 | 0.818860E+09 | 0.601300E+09 | 0.188573E+10 | 0.133081E+10 |
April | 0.931803E+09 | 0.347679E+09 | 0.584124E+09 | 0.143124E+10 | 0.811025E+09 |
May | 0.680445E+09 | 95239968.29 | 0.585205E+09 | 0.120363E+10 | 0.492931E+09 |
June | 0.568115E+09 | 36047082.62 | 0.532068E+09 | 0.129294E+10 | 0.235065E+09 |
July | 0.598435E+09 | 55475984.25 | 0.542959E+09 | 0.135074E+10 | 0.188009E+09 |
August | 0.762840E+09 | 0.201928E+09 | 0.560912E+09 | 0.158550E+10 | 0.271734E+09 |
September | 0.115230E+10 | 0.598658E+09 | 0.553639E+09 | 0.214538E+10 | 0.538381E+09 |
October | 0.161782E+10 | 0.109375E+10 | 0.524066E+09 | 0.251145E+10 | 0.883484E+09 |
November | 0.188410E+10 | 0.143639E+10 | 0.447704E+09 | 0.253296E+10 | 0.138647E+10 |
December | 0.192945E+10 | 0.144833E+10 | 0.481117E+09 | 0.236910E+10 | 0.181604E+10 |
Annual Sum or Average | 0.150076E+11 | 0.867225E+10 | 0.633535E+10 | 0.227293E+11 | 0.109826E+11 |
Minimum of Months | 0.568115E+09 | 36047082.62 | 0.447704E+09 | 0.120363E+10 | 0.188009E+09 |
Maximum of Months | 0.192945E+10 | 0.144833E+10 | 0.601300E+09 | 0.253296E+10 | 0.181604E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188381E+10 | 0.142718E+10 | 0.456627E+09 | 0.238194E+10 | 0.167095E+10 |
February | 0.157833E+10 | 0.111270E+10 | 0.465633E+09 | 0.203867E+10 | 0.135772E+10 |
March | 0.142016E+10 | 0.818859E+09 | 0.601299E+09 | 0.188573E+10 | 0.133081E+10 |
April | 0.931802E+09 | 0.347679E+09 | 0.584123E+09 | 0.143123E+10 | 0.811024E+09 |
May | 0.680444E+09 | 95239854.01 | 0.585204E+09 | 0.120363E+10 | 0.492931E+09 |
June | 0.568115E+09 | 36047039.37 | 0.532068E+09 | 0.129294E+10 | 0.235065E+09 |
July | 0.598435E+09 | 55475917.69 | 0.542959E+09 | 0.135074E+10 | 0.188009E+09 |
August | 0.762839E+09 | 0.201928E+09 | 0.560911E+09 | 0.158550E+10 | 0.271734E+09 |
September | 0.115230E+10 | 0.598658E+09 | 0.553638E+09 | 0.214538E+10 | 0.538380E+09 |
October | 0.161782E+10 | 0.109375E+10 | 0.524065E+09 | 0.251145E+10 | 0.883484E+09 |
November | 0.188409E+10 | 0.143639E+10 | 0.447704E+09 | 0.253296E+10 | 0.138647E+10 |
December | 0.192945E+10 | 0.144833E+10 | 0.481117E+09 | 0.236910E+10 | 0.181604E+10 |
Annual Sum or Average | 0.150076E+11 | 0.867224E+10 | 0.633535E+10 | 0.227293E+11 | 0.109826E+11 |
Minimum of Months | 0.568115E+09 | 36047039.37 | 0.447704E+09 | 0.120363E+10 | 0.188009E+09 |
Maximum of Months | 0.192945E+10 | 0.144833E+10 | 0.601299E+09 | 0.253296E+10 | 0.181604E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188381E+10 | 0.142718E+10 | 0.456627E+09 | 0.238195E+10 | 0.167095E+10 |
February | 0.157834E+10 | 0.111270E+10 | 0.465634E+09 | 0.203868E+10 | 0.135773E+10 |
March | 0.142016E+10 | 0.818860E+09 | 0.601300E+09 | 0.188573E+10 | 0.133081E+10 |
April | 0.931803E+09 | 0.347679E+09 | 0.584124E+09 | 0.143124E+10 | 0.811025E+09 |
May | 0.680445E+09 | 95239968.29 | 0.585205E+09 | 0.120363E+10 | 0.492931E+09 |
June | 0.568115E+09 | 36047082.62 | 0.532068E+09 | 0.129294E+10 | 0.235065E+09 |
July | 0.598435E+09 | 55475984.25 | 0.542959E+09 | 0.135074E+10 | 0.188009E+09 |
August | 0.762840E+09 | 0.201928E+09 | 0.560912E+09 | 0.158550E+10 | 0.271734E+09 |
September | 0.115230E+10 | 0.598658E+09 | 0.553639E+09 | 0.214538E+10 | 0.538381E+09 |
October | 0.161782E+10 | 0.109375E+10 | 0.524066E+09 | 0.251145E+10 | 0.883484E+09 |
November | 0.188410E+10 | 0.143639E+10 | 0.447704E+09 | 0.253296E+10 | 0.138647E+10 |
December | 0.192945E+10 | 0.144833E+10 | 0.481117E+09 | 0.236910E+10 | 0.181604E+10 |
Annual Sum or Average | 0.150076E+11 | 0.867225E+10 | 0.633535E+10 | 0.227293E+11 | 0.109826E+11 |
Minimum of Months | 0.568115E+09 | 36047082.62 | 0.447704E+09 | 0.120363E+10 | 0.188009E+09 |
Maximum of Months | 0.192945E+10 | 0.144833E+10 | 0.601300E+09 | 0.253296E+10 | 0.181604E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188381E+10 | 0.142718E+10 | 0.456627E+09 | 0.238194E+10 | 0.167095E+10 |
February | 0.157833E+10 | 0.111270E+10 | 0.465633E+09 | 0.203867E+10 | 0.135772E+10 |
March | 0.142016E+10 | 0.818859E+09 | 0.601299E+09 | 0.188573E+10 | 0.133081E+10 |
April | 0.931802E+09 | 0.347679E+09 | 0.584123E+09 | 0.143123E+10 | 0.811024E+09 |
May | 0.680444E+09 | 95239854.01 | 0.585204E+09 | 0.120363E+10 | 0.492931E+09 |
June | 0.568115E+09 | 36047039.37 | 0.532068E+09 | 0.129294E+10 | 0.235065E+09 |
July | 0.598435E+09 | 55475917.69 | 0.542959E+09 | 0.135074E+10 | 0.188009E+09 |
August | 0.762839E+09 | 0.201928E+09 | 0.560911E+09 | 0.158550E+10 | 0.271734E+09 |
September | 0.115230E+10 | 0.598658E+09 | 0.553638E+09 | 0.214538E+10 | 0.538380E+09 |
October | 0.161782E+10 | 0.109375E+10 | 0.524065E+09 | 0.251145E+10 | 0.883484E+09 |
November | 0.188409E+10 | 0.143639E+10 | 0.447704E+09 | 0.253296E+10 | 0.138647E+10 |
December | 0.192945E+10 | 0.144833E+10 | 0.481117E+09 | 0.236910E+10 | 0.181604E+10 |
Annual Sum or Average | 0.150076E+11 | 0.867224E+10 | 0.633535E+10 | 0.227293E+11 | 0.109826E+11 |
Minimum of Months | 0.568115E+09 | 36047039.37 | 0.447704E+09 | 0.120363E+10 | 0.188009E+09 |
Maximum of Months | 0.192945E+10 | 0.144833E+10 | 0.601299E+09 | 0.253296E+10 | 0.181604E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188373E+10 | 0.142712E+10 | 0.456609E+09 | 0.238185E+10 | 0.167089E+10 |
February | 0.157827E+10 | 0.111266E+10 | 0.465615E+09 | 0.203860E+10 | 0.135767E+10 |
March | 0.142010E+10 | 0.818827E+09 | 0.601276E+09 | 0.188565E+10 | 0.133075E+10 |
April | 0.931765E+09 | 0.347665E+09 | 0.584100E+09 | 0.143118E+10 | 0.810992E+09 |
May | 0.680417E+09 | 95236129.70 | 0.585181E+09 | 0.120358E+10 | 0.492912E+09 |
June | 0.568092E+09 | 36045629.76 | 0.532047E+09 | 0.129289E+10 | 0.235056E+09 |
July | 0.598411E+09 | 55473748.32 | 0.542937E+09 | 0.135069E+10 | 0.188002E+09 |
August | 0.762809E+09 | 0.201920E+09 | 0.560889E+09 | 0.158543E+10 | 0.271723E+09 |
September | 0.115225E+10 | 0.598634E+09 | 0.553616E+09 | 0.214530E+10 | 0.538359E+09 |
October | 0.161776E+10 | 0.109371E+10 | 0.524045E+09 | 0.251135E+10 | 0.883448E+09 |
November | 0.188402E+10 | 0.143633E+10 | 0.447686E+09 | 0.253286E+10 | 0.138641E+10 |
December | 0.192937E+10 | 0.144828E+10 | 0.481098E+09 | 0.236901E+10 | 0.181597E+10 |
Annual Sum or Average | 0.150070E+11 | 0.867190E+10 | 0.633510E+10 | 0.227284E+11 | 0.109822E+11 |
Minimum of Months | 0.568092E+09 | 36045629.76 | 0.447686E+09 | 0.120358E+10 | 0.188002E+09 |
Maximum of Months | 0.192937E+10 | 0.144828E+10 | 0.601276E+09 | 0.253286E+10 | 0.181597E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.862044E+09 | 0.485479E+09 | 0.376565E+09 | 0.828422E+09 | 0.218649E+10 |
February | 0.878592E+09 | 0.466991E+09 | 0.411602E+09 | 0.925220E+09 | 0.175879E+10 |
March | 0.132555E+10 | 0.710448E+09 | 0.615100E+09 | 0.156680E+10 | 0.169382E+10 |
April | 0.147446E+10 | 0.796382E+09 | 0.678077E+09 | 0.209918E+10 | 0.106685E+10 |
May | 0.164107E+10 | 0.878047E+09 | 0.763024E+09 | 0.273118E+10 | 0.635690E+09 |
June | 0.154592E+10 | 0.830332E+09 | 0.715593E+09 | 0.294183E+10 | 0.333738E+09 |
July | 0.141763E+10 | 0.704448E+09 | 0.713181E+09 | 0.268683E+10 | 0.288186E+09 |
August | 0.137290E+10 | 0.699683E+09 | 0.673218E+09 | 0.246689E+10 | 0.406021E+09 |
September | 0.135871E+10 | 0.756941E+09 | 0.601773E+09 | 0.234287E+10 | 0.677255E+09 |
October | 0.120862E+10 | 0.705389E+09 | 0.503229E+09 | 0.174288E+10 | 0.112217E+10 |
November | 0.981733E+09 | 0.597771E+09 | 0.383962E+09 | 0.110478E+10 | 0.185544E+10 |
December | 0.817504E+09 | 0.444094E+09 | 0.373409E+09 | 0.713964E+09 | 0.251872E+10 |
Annual Sum or Average | 0.148847E+11 | 0.807600E+10 | 0.680873E+10 | 0.221509E+11 | 0.145432E+11 |
Minimum of Months | 0.817504E+09 | 0.444094E+09 | 0.373409E+09 | 0.713964E+09 | 0.288186E+09 |
Maximum of Months | 0.164107E+10 | 0.878047E+09 | 0.763024E+09 | 0.294183E+10 | 0.251872E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.862044E+09 | 0.485479E+09 | 0.376565E+09 | 0.828422E+09 | 0.218649E+10 |
February | 0.878592E+09 | 0.466991E+09 | 0.411602E+09 | 0.925220E+09 | 0.175879E+10 |
March | 0.132555E+10 | 0.710448E+09 | 0.615100E+09 | 0.156680E+10 | 0.169382E+10 |
April | 0.147446E+10 | 0.796382E+09 | 0.678077E+09 | 0.209918E+10 | 0.106685E+10 |
May | 0.164107E+10 | 0.878047E+09 | 0.763024E+09 | 0.273118E+10 | 0.635690E+09 |
June | 0.154592E+10 | 0.830332E+09 | 0.715593E+09 | 0.294183E+10 | 0.333738E+09 |
July | 0.141763E+10 | 0.704448E+09 | 0.713181E+09 | 0.268683E+10 | 0.288186E+09 |
August | 0.137290E+10 | 0.699683E+09 | 0.673218E+09 | 0.246689E+10 | 0.406021E+09 |
September | 0.135871E+10 | 0.756941E+09 | 0.601773E+09 | 0.234287E+10 | 0.677255E+09 |
October | 0.120862E+10 | 0.705389E+09 | 0.503229E+09 | 0.174288E+10 | 0.112217E+10 |
November | 0.981733E+09 | 0.597771E+09 | 0.383962E+09 | 0.110478E+10 | 0.185544E+10 |
December | 0.817504E+09 | 0.444094E+09 | 0.373409E+09 | 0.713964E+09 | 0.251872E+10 |
Annual Sum or Average | 0.148847E+11 | 0.807600E+10 | 0.680873E+10 | 0.221509E+11 | 0.145432E+11 |
Minimum of Months | 0.817504E+09 | 0.444094E+09 | 0.373409E+09 | 0.713964E+09 | 0.288186E+09 |
Maximum of Months | 0.164107E+10 | 0.878047E+09 | 0.763024E+09 | 0.294183E+10 | 0.251872E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.862028E+09 | 0.485470E+09 | 0.376558E+09 | 0.828407E+09 | 0.218645E+10 |
February | 0.878576E+09 | 0.466982E+09 | 0.411594E+09 | 0.925204E+09 | 0.175876E+10 |
March | 0.132552E+10 | 0.710435E+09 | 0.615088E+09 | 0.156677E+10 | 0.169379E+10 |
April | 0.147443E+10 | 0.796367E+09 | 0.678065E+09 | 0.209914E+10 | 0.106683E+10 |
May | 0.164104E+10 | 0.878031E+09 | 0.763010E+09 | 0.273113E+10 | 0.635679E+09 |
June | 0.154590E+10 | 0.830316E+09 | 0.715580E+09 | 0.294178E+10 | 0.333732E+09 |
July | 0.141760E+10 | 0.704435E+09 | 0.713168E+09 | 0.268678E+10 | 0.288180E+09 |
August | 0.137288E+10 | 0.699670E+09 | 0.673206E+09 | 0.246684E+10 | 0.406014E+09 |
September | 0.135869E+10 | 0.756927E+09 | 0.601762E+09 | 0.234283E+10 | 0.677243E+09 |
October | 0.120860E+10 | 0.705376E+09 | 0.503220E+09 | 0.174285E+10 | 0.112215E+10 |
November | 0.981715E+09 | 0.597760E+09 | 0.383955E+09 | 0.110476E+10 | 0.185541E+10 |
December | 0.817489E+09 | 0.444086E+09 | 0.373403E+09 | 0.713951E+09 | 0.251868E+10 |
Annual Sum or Average | 0.148845E+11 | 0.807586E+10 | 0.680861E+10 | 0.221504E+11 | 0.145429E+11 |
Minimum of Months | 0.817489E+09 | 0.444086E+09 | 0.373403E+09 | 0.713951E+09 | 0.288180E+09 |
Maximum of Months | 0.164104E+10 | 0.878031E+09 | 0.763010E+09 | 0.294178E+10 | 0.251868E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137685E+10 | 0.00 | 0.137685E+10 | 0.143903E+09 | 0.897779E+10 |
February | 0.151857E+10 | 0.00 | 0.151857E+10 | 0.518560E+09 | 0.721200E+10 |
March | 0.220024E+10 | 0.00 | 0.220024E+10 | 0.125179E+10 | 0.667560E+10 |
April | 0.245848E+10 | 19369252.49 | 0.243911E+10 | 0.271563E+10 | 0.370827E+10 |
May | 0.301304E+10 | 0.217885E+09 | 0.279516E+10 | 0.489098E+10 | 0.219831E+10 |
June | 0.310050E+10 | 0.381708E+09 | 0.271879E+10 | 0.686439E+10 | 0.114498E+10 |
July | 0.296098E+10 | 0.288229E+09 | 0.267275E+10 | 0.655071E+10 | 0.937271E+09 |
August | 0.249675E+10 | 51052109.64 | 0.244570E+10 | 0.505738E+10 | 0.129427E+10 |
September | 0.210836E+10 | 841312.35 | 0.210752E+10 | 0.366119E+10 | 0.249503E+10 |
October | 0.180887E+10 | 0.00 | 0.180887E+10 | 0.182603E+10 | 0.422714E+10 |
November | 0.141319E+10 | 0.00 | 0.141319E+10 | 0.353119E+09 | 0.728974E+10 |
December | 0.136618E+10 | 0.00 | 0.136618E+10 | 0.101194E+09 | 0.999100E+10 |
Annual Sum or Average | 0.258220E+11 | 0.959085E+09 | 0.248629E+11 | 0.339349E+11 | 0.561514E+11 |
Minimum of Months | 0.136618E+10 | 0.00 | 0.136618E+10 | 0.101194E+09 | 0.937271E+09 |
Maximum of Months | 0.310050E+10 | 0.381708E+09 | 0.279516E+10 | 0.686439E+10 | 0.999100E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245504E+10 | 0.133177E+10 | 0.112327E+10 | 0.205006E+10 | 0.549818E+10 |
February | 0.296674E+10 | 0.169102E+10 | 0.127572E+10 | 0.300960E+10 | 0.439571E+10 |
March | 0.405541E+10 | 0.223440E+10 | 0.182101E+10 | 0.456553E+10 | 0.405415E+10 |
April | 0.472893E+10 | 0.262350E+10 | 0.210543E+10 | 0.664675E+10 | 0.229061E+10 |
May | 0.504267E+10 | 0.274050E+10 | 0.230216E+10 | 0.822228E+10 | 0.142911E+10 |
June | 0.488275E+10 | 0.271637E+10 | 0.216638E+10 | 0.922794E+10 | 0.727650E+09 |
July | 0.452472E+10 | 0.236545E+10 | 0.215927E+10 | 0.861883E+10 | 0.604433E+09 |
August | 0.430552E+10 | 0.220352E+10 | 0.210199E+10 | 0.783383E+10 | 0.826953E+09 |
September | 0.412800E+10 | 0.235532E+10 | 0.177267E+10 | 0.690553E+10 | 0.154265E+10 |
October | 0.328051E+10 | 0.177046E+10 | 0.151005E+10 | 0.444417E+10 | 0.264691E+10 |
November | 0.284583E+10 | 0.165675E+10 | 0.118908E+10 | 0.282969E+10 | 0.443726E+10 |
December | 0.245293E+10 | 0.129962E+10 | 0.115331E+10 | 0.193159E+10 | 0.609324E+10 |
Annual Sum or Average | 0.456690E+11 | 0.249887E+11 | 0.206804E+11 | 0.662858E+11 | 0.345469E+11 |
Minimum of Months | 0.245293E+10 | 0.129962E+10 | 0.112327E+10 | 0.193159E+10 | 0.604433E+09 |
Maximum of Months | 0.504267E+10 | 0.274050E+10 | 0.230216E+10 | 0.922794E+10 | 0.609324E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.941893E+10 | 0.713583E+10 | 0.228311E+10 | 0.117541E+11 | 0.821210E+10 |
February | 0.789158E+10 | 0.556344E+10 | 0.232814E+10 | 0.100429E+11 | 0.670380E+10 |
March | 0.710072E+10 | 0.409425E+10 | 0.300646E+10 | 0.929185E+10 | 0.650101E+10 |
April | 0.465896E+10 | 0.173837E+10 | 0.292058E+10 | 0.714915E+10 | 0.387346E+10 |
May | 0.340218E+10 | 0.476194E+09 | 0.292599E+10 | 0.606425E+10 | 0.234084E+10 |
June | 0.284054E+10 | 0.180233E+09 | 0.266031E+10 | 0.656980E+10 | 0.115392E+10 |
July | 0.299214E+10 | 0.277377E+09 | 0.271476E+10 | 0.684672E+10 | 0.959203E+09 |
August | 0.381415E+10 | 0.100963E+10 | 0.280452E+10 | 0.798160E+10 | 0.136623E+10 |
September | 0.576142E+10 | 0.299326E+10 | 0.276816E+10 | 0.106739E+11 | 0.260816E+10 |
October | 0.808900E+10 | 0.546871E+10 | 0.262030E+10 | 0.124424E+11 | 0.429741E+10 |
November | 0.942036E+10 | 0.718187E+10 | 0.223849E+10 | 0.125387E+11 | 0.676478E+10 |
December | 0.964714E+10 | 0.724158E+10 | 0.240556E+10 | 0.117550E+11 | 0.884446E+10 |
Annual Sum or Average | 0.750371E+11 | 0.433607E+11 | 0.316764E+11 | 0.113110E+12 | 0.536254E+11 |
Minimum of Months | 0.284054E+10 | 0.180233E+09 | 0.223849E+10 | 0.606425E+10 | 0.959203E+09 |
Maximum of Months | 0.964714E+10 | 0.724158E+10 | 0.300646E+10 | 0.125387E+11 | 0.884446E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258610E+10 | 0.145642E+10 | 0.112968E+10 | 0.257975E+10 | 0.588006E+10 |
February | 0.263575E+10 | 0.140096E+10 | 0.123479E+10 | 0.285784E+10 | 0.479666E+10 |
March | 0.397660E+10 | 0.213132E+10 | 0.184528E+10 | 0.482512E+10 | 0.452215E+10 |
April | 0.442333E+10 | 0.238912E+10 | 0.203421E+10 | 0.650795E+10 | 0.269337E+10 |
May | 0.492316E+10 | 0.263412E+10 | 0.228905E+10 | 0.824963E+10 | 0.170975E+10 |
June | 0.463773E+10 | 0.249097E+10 | 0.214676E+10 | 0.894592E+10 | 0.890498E+09 |
July | 0.425284E+10 | 0.211332E+10 | 0.213952E+10 | 0.824720E+10 | 0.747868E+09 |
August | 0.411866E+10 | 0.209903E+10 | 0.201963E+10 | 0.761025E+10 | 0.100125E+10 |
September | 0.407610E+10 | 0.227080E+10 | 0.180530E+10 | 0.711632E+10 | 0.181460E+10 |
October | 0.362582E+10 | 0.211615E+10 | 0.150967E+10 | 0.535914E+10 | 0.295392E+10 |
November | 0.294517E+10 | 0.179329E+10 | 0.115187E+10 | 0.345516E+10 | 0.483774E+10 |
December | 0.245249E+10 | 0.133227E+10 | 0.112022E+10 | 0.230181E+10 | 0.646630E+10 |
Annual Sum or Average | 0.446538E+11 | 0.242278E+11 | 0.204260E+11 | 0.680561E+11 | 0.383142E+11 |
Minimum of Months | 0.245249E+10 | 0.133227E+10 | 0.112022E+10 | 0.230181E+10 | 0.747868E+09 |
Maximum of Months | 0.492316E+10 | 0.263412E+10 | 0.228905E+10 | 0.894592E+10 | 0.646630E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137685E+10 | 0.00 | 0.137685E+10 | 0.237832E+09 | 0.802566E+10 |
February | 0.151857E+10 | 0.00 | 0.151857E+10 | 0.617569E+09 | 0.650594E+10 |
March | 0.220024E+10 | 0.00 | 0.220024E+10 | 0.135203E+10 | 0.608021E+10 |
April | 0.245848E+10 | 19369252.49 | 0.243911E+10 | 0.274851E+10 | 0.342006E+10 |
May | 0.301304E+10 | 0.217885E+09 | 0.279516E+10 | 0.487153E+10 | 0.208305E+10 |
June | 0.310050E+10 | 0.381708E+09 | 0.271879E+10 | 0.676370E+10 | 0.112762E+10 |
July | 0.296098E+10 | 0.288229E+09 | 0.267275E+10 | 0.643981E+10 | 0.931428E+09 |
August | 0.249675E+10 | 51052109.64 | 0.244570E+10 | 0.498957E+10 | 0.123308E+10 |
September | 0.210836E+10 | 841312.35 | 0.210752E+10 | 0.365126E+10 | 0.234040E+10 |
October | 0.180887E+10 | 0.00 | 0.180887E+10 | 0.191428E+10 | 0.379929E+10 |
November | 0.141319E+10 | 0.00 | 0.141319E+10 | 0.448146E+09 | 0.642421E+10 |
December | 0.136618E+10 | 0.00 | 0.136618E+10 | 0.178156E+09 | 0.894993E+10 |
Annual Sum or Average | 0.258220E+11 | 0.959085E+09 | 0.248629E+11 | 0.342124E+11 | 0.509209E+11 |
Minimum of Months | 0.136618E+10 | 0.00 | 0.136618E+10 | 0.178156E+09 | 0.931428E+09 |
Maximum of Months | 0.310050E+10 | 0.381708E+09 | 0.279516E+10 | 0.676370E+10 | 0.894993E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245504E+10 | 0.133177E+10 | 0.112327E+10 | 0.221082E+10 | 0.488686E+10 |
February | 0.296674E+10 | 0.169102E+10 | 0.127572E+10 | 0.315550E+10 | 0.396689E+10 |
March | 0.405541E+10 | 0.223440E+10 | 0.182101E+10 | 0.468024E+10 | 0.375158E+10 |
April | 0.472893E+10 | 0.262350E+10 | 0.210543E+10 | 0.665135E+10 | 0.217428E+10 |
May | 0.504267E+10 | 0.274050E+10 | 0.230216E+10 | 0.817279E+10 | 0.138606E+10 |
June | 0.488275E+10 | 0.271637E+10 | 0.216638E+10 | 0.913816E+10 | 0.728801E+09 |
July | 0.452472E+10 | 0.236545E+10 | 0.215927E+10 | 0.851623E+10 | 0.611859E+09 |
August | 0.430552E+10 | 0.220352E+10 | 0.210199E+10 | 0.776523E+10 | 0.809114E+09 |
September | 0.412800E+10 | 0.235532E+10 | 0.177267E+10 | 0.688064E+10 | 0.148875E+10 |
October | 0.328051E+10 | 0.177046E+10 | 0.151005E+10 | 0.449563E+10 | 0.244345E+10 |
November | 0.284583E+10 | 0.165675E+10 | 0.118908E+10 | 0.298681E+10 | 0.395289E+10 |
December | 0.245293E+10 | 0.129962E+10 | 0.115331E+10 | 0.209992E+10 | 0.542335E+10 |
Annual Sum or Average | 0.456690E+11 | 0.249887E+11 | 0.206804E+11 | 0.667533E+11 | 0.316239E+11 |
Minimum of Months | 0.245293E+10 | 0.129962E+10 | 0.112327E+10 | 0.209992E+10 | 0.611859E+09 |
Maximum of Months | 0.504267E+10 | 0.274050E+10 | 0.230216E+10 | 0.913816E+10 | 0.542335E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.941893E+10 | 0.713583E+10 | 0.228311E+10 | 0.119412E+11 | 0.737715E+10 |
February | 0.789158E+10 | 0.556344E+10 | 0.232814E+10 | 0.101801E+11 | 0.608476E+10 |
March | 0.710072E+10 | 0.409425E+10 | 0.300646E+10 | 0.937885E+10 | 0.598301E+10 |
April | 0.465896E+10 | 0.173837E+10 | 0.292058E+10 | 0.713424E+10 | 0.361820E+10 |
May | 0.340218E+10 | 0.476194E+09 | 0.292599E+10 | 0.599197E+10 | 0.222434E+10 |
June | 0.284054E+10 | 0.180233E+09 | 0.266031E+10 | 0.645163E+10 | 0.113827E+10 |
July | 0.299214E+10 | 0.277377E+09 | 0.271476E+10 | 0.670665E+10 | 0.956869E+09 |
August | 0.381415E+10 | 0.100963E+10 | 0.280452E+10 | 0.787927E+10 | 0.131411E+10 |
September | 0.576142E+10 | 0.299326E+10 | 0.276816E+10 | 0.106197E+11 | 0.247854E+10 |
October | 0.808900E+10 | 0.546871E+10 | 0.262030E+10 | 0.124797E+11 | 0.395272E+10 |
November | 0.942036E+10 | 0.718187E+10 | 0.223849E+10 | 0.127199E+11 | 0.606484E+10 |
December | 0.964714E+10 | 0.724158E+10 | 0.240556E+10 | 0.120128E+11 | 0.795995E+10 |
Annual Sum or Average | 0.750371E+11 | 0.433607E+11 | 0.316764E+11 | 0.113496E+12 | 0.491528E+11 |
Minimum of Months | 0.284054E+10 | 0.180233E+09 | 0.223849E+10 | 0.599197E+10 | 0.956869E+09 |
Maximum of Months | 0.964714E+10 | 0.724158E+10 | 0.300646E+10 | 0.127199E+11 | 0.795995E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258610E+10 | 0.145642E+10 | 0.112968E+10 | 0.261185E+10 | 0.539456E+10 |
February | 0.263575E+10 | 0.140096E+10 | 0.123479E+10 | 0.288048E+10 | 0.443023E+10 |
March | 0.397660E+10 | 0.213132E+10 | 0.184528E+10 | 0.481980E+10 | 0.420244E+10 |
April | 0.442333E+10 | 0.238912E+10 | 0.203421E+10 | 0.647361E+10 | 0.253600E+10 |
May | 0.492316E+10 | 0.263412E+10 | 0.228905E+10 | 0.818588E+10 | 0.163288E+10 |
June | 0.463773E+10 | 0.249097E+10 | 0.214676E+10 | 0.886586E+10 | 0.874700E+09 |
July | 0.425284E+10 | 0.211332E+10 | 0.213952E+10 | 0.816516E+10 | 0.738061E+09 |
August | 0.411866E+10 | 0.209903E+10 | 0.201963E+10 | 0.754770E+10 | 0.962858E+09 |
September | 0.407610E+10 | 0.227080E+10 | 0.180530E+10 | 0.708018E+10 | 0.173336E+10 |
October | 0.362582E+10 | 0.211615E+10 | 0.150967E+10 | 0.535702E+10 | 0.274404E+10 |
November | 0.294517E+10 | 0.179329E+10 | 0.115187E+10 | 0.348236E+10 | 0.439715E+10 |
December | 0.245249E+10 | 0.133227E+10 | 0.112022E+10 | 0.235069E+10 | 0.591287E+10 |
Annual Sum or Average | 0.446538E+11 | 0.242278E+11 | 0.204260E+11 | 0.678206E+11 | 0.355591E+11 |
Minimum of Months | 0.245249E+10 | 0.133227E+10 | 0.112022E+10 | 0.235069E+10 | 0.738061E+09 |
Maximum of Months | 0.492316E+10 | 0.263412E+10 | 0.228905E+10 | 0.886586E+10 | 0.591287E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 23.64 | 3713.03 | 514.06 | 0.00 | 514.06 | 0.00 | 0.00 |
February | 164.49 | 3247.48 | 627.72 | 0.00 | 627.72 | 0.00 | 0.00 |
March | 409.40 | 2713.68 | 821.48 | 0.00 | 821.48 | 0.00 | 0.00 |
April | 976.58 | 1572.09 | 948.49 | 7.47 | 941.02 | 0.00 | 0.00 |
May | 1787.93 | 877.61 | 1124.94 | 81.35 | 1043.60 | 0.00 | 0.00 |
June | 2616.64 | 447.78 | 1196.19 | 147.26 | 1048.92 | 0.00 | 0.00 |
July | 2412.50 | 344.28 | 1105.51 | 107.61 | 997.90 | 0.00 | 0.00 |
August | 1842.70 | 493.57 | 932.18 | 19.06 | 913.12 | 0.00 | 0.00 |
September | 1370.92 | 1038.67 | 813.41 | 0.32 | 813.09 | 0.00 | 0.00 |
October | 621.85 | 1748.86 | 675.36 | 0.00 | 675.36 | 0.00 | 0.00 |
November | 87.19 | 3159.20 | 545.21 | 0.00 | 545.21 | 0.00 | 0.00 |
December | 17.10 | 4182.70 | 510.08 | 0.00 | 510.08 | 0.00 | 0.00 |
Annual Sum or Average | 1032.09 | 1955.47 | 818.81 | 30.41 | 788.40 | 0.00 | 0.00 |
Minimum of Months | 17.10 | 344.28 | 510.08 | 0.00 | 510.08 | 0.00 | 0.00 |
Maximum of Months | 2616.64 | 4182.70 | 1196.19 | 147.26 | 1048.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 750.97 | 2196.68 | 916.61 | 497.23 | 419.38 | 0.00 | 0.00 |
February | 1238.87 | 1912.35 | 1226.34 | 699.00 | 527.33 | 0.00 | 0.00 |
March | 1719.09 | 1585.49 | 1514.12 | 834.23 | 679.89 | 0.00 | 0.00 |
April | 2591.21 | 912.49 | 1824.44 | 1012.16 | 812.28 | 0.00 | 0.00 |
May | 3099.56 | 556.86 | 1882.72 | 1023.19 | 859.53 | 0.00 | 0.00 |
June | 3596.26 | 266.89 | 1883.78 | 1047.99 | 835.80 | 0.00 | 0.00 |
July | 3256.87 | 194.13 | 1689.34 | 883.16 | 806.18 | 0.00 | 0.00 |
August | 2961.56 | 277.60 | 1607.50 | 822.71 | 784.80 | 0.00 | 0.00 |
September | 2683.22 | 620.96 | 1592.60 | 908.69 | 683.90 | 0.00 | 0.00 |
October | 1667.14 | 1055.55 | 1224.81 | 661.02 | 563.79 | 0.00 | 0.00 |
November | 1083.22 | 1836.13 | 1097.93 | 639.18 | 458.75 | 0.00 | 0.00 |
December | 699.37 | 2430.55 | 915.82 | 485.22 | 430.60 | 0.00 | 0.00 |
Annual Sum or Average | 2115.33 | 1150.25 | 1448.16 | 792.39 | 655.77 | 0.00 | 0.00 |
Minimum of Months | 699.37 | 194.13 | 915.82 | 485.22 | 419.38 | 0.00 | 0.00 |
Maximum of Months | 3596.26 | 2430.55 | 1883.78 | 1047.99 | 859.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4446.55 | 3119.29 | 3516.64 | 2664.22 | 852.42 | 0.00 | 0.00 |
February | 4213.50 | 2806.12 | 3262.08 | 2299.71 | 962.36 | 0.00 | 0.00 |
March | 3520.22 | 2484.31 | 2651.11 | 1528.62 | 1122.49 | 0.00 | 0.00 |
April | 2760.85 | 1564.46 | 1797.44 | 670.67 | 1126.77 | 0.00 | 0.00 |
May | 2246.90 | 920.19 | 1270.23 | 177.79 | 1092.44 | 0.00 | 0.00 |
June | 2494.07 | 453.44 | 1095.89 | 69.53 | 1026.36 | 0.00 | 0.00 |
July | 2521.52 | 350.97 | 1117.14 | 103.56 | 1013.58 | 0.00 | 0.00 |
August | 2959.76 | 507.26 | 1424.05 | 376.95 | 1047.09 | 0.00 | 0.00 |
September | 4138.44 | 1038.53 | 2222.78 | 1154.81 | 1067.97 | 0.00 | 0.00 |
October | 4688.30 | 1649.26 | 3020.10 | 2041.79 | 978.31 | 0.00 | 0.00 |
November | 4886.08 | 2674.49 | 3634.41 | 2770.79 | 863.62 | 0.00 | 0.00 |
December | 4422.57 | 3390.14 | 3601.84 | 2703.71 | 898.14 | 0.00 | 0.00 |
Annual Sum or Average | 3603.68 | 1741.27 | 2379.42 | 1374.97 | 1004.46 | 0.00 | 0.00 |
Minimum of Months | 2246.90 | 350.97 | 1095.89 | 69.53 | 852.42 | 0.00 | 0.00 |
Maximum of Months | 4886.08 | 3390.14 | 3634.41 | 2770.79 | 1126.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 927.89 | 2449.01 | 965.54 | 543.77 | 421.78 | 0.00 | 0.00 |
February | 1147.34 | 2181.03 | 1089.52 | 579.10 | 510.42 | 0.00 | 0.00 |
March | 1754.92 | 1897.19 | 1484.70 | 795.75 | 688.95 | 0.00 | 0.00 |
April | 2429.59 | 1234.77 | 1706.54 | 921.73 | 784.81 | 0.00 | 0.00 |
May | 3059.10 | 712.01 | 1838.11 | 983.47 | 854.64 | 0.00 | 0.00 |
June | 3404.88 | 386.27 | 1789.25 | 961.03 | 828.23 | 0.00 | 0.00 |
July | 3009.42 | 322.79 | 1587.84 | 789.03 | 798.81 | 0.00 | 0.00 |
August | 2763.07 | 454.77 | 1537.74 | 783.69 | 754.05 | 0.00 | 0.00 |
September | 2711.64 | 783.86 | 1572.58 | 876.08 | 696.49 | 0.00 | 0.00 |
October | 1952.14 | 1256.90 | 1353.73 | 790.08 | 563.65 | 0.00 | 0.00 |
November | 1278.67 | 2147.49 | 1136.26 | 691.86 | 444.40 | 0.00 | 0.00 |
December | 799.69 | 2821.13 | 915.66 | 497.41 | 418.24 | 0.00 | 0.00 |
Annual Sum or Average | 2107.18 | 1383.47 | 1415.97 | 768.26 | 647.71 | 0.00 | 0.00 |
Minimum of Months | 799.69 | 322.79 | 915.66 | 497.41 | 418.24 | 0.00 | 0.00 |
Maximum of Months | 3404.88 | 2821.13 | 1838.11 | 983.47 | 854.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 53.73 | 3351.92 | 514.06 | 0.00 | 514.06 | 0.00 | 0.00 |
February | 214.35 | 2981.15 | 627.72 | 0.00 | 627.72 | 0.00 | 0.00 |
March | 467.36 | 2492.39 | 821.48 | 0.00 | 821.48 | 0.00 | 0.00 |
April | 1047.70 | 1430.66 | 948.49 | 7.47 | 941.01 | 0.00 | 0.00 |
May | 1826.08 | 820.76 | 1124.94 | 81.35 | 1043.59 | 0.00 | 0.00 |
June | 2648.30 | 441.73 | 1196.18 | 147.26 | 1048.92 | 0.00 | 0.00 |
July | 2445.75 | 349.94 | 1105.50 | 107.61 | 997.89 | 0.00 | 0.00 |
August | 1888.21 | 483.23 | 932.18 | 19.06 | 913.12 | 0.00 | 0.00 |
September | 1412.50 | 962.59 | 813.41 | 0.32 | 813.09 | 0.00 | 0.00 |
October | 681.76 | 1578.23 | 675.36 | 0.00 | 675.36 | 0.00 | 0.00 |
November | 136.23 | 2812.40 | 545.21 | 0.00 | 545.21 | 0.00 | 0.00 |
December | 37.78 | 3730.21 | 510.07 | 0.00 | 510.07 | 0.00 | 0.00 |
Annual Sum or Average | 1076.07 | 1780.55 | 818.81 | 30.41 | 788.40 | 0.00 | 0.00 |
Minimum of Months | 37.78 | 349.94 | 510.07 | 0.00 | 510.07 | 0.00 | 0.00 |
Maximum of Months | 2648.30 | 3730.21 | 1196.18 | 147.26 | 1048.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 765.41 | 2052.79 | 916.61 | 497.23 | 419.38 | 0.00 | 0.00 |
February | 1244.05 | 1817.01 | 1226.33 | 699.00 | 527.33 | 0.00 | 0.00 |
March | 1704.57 | 1513.65 | 1514.12 | 834.23 | 679.89 | 0.00 | 0.00 |
April | 2564.33 | 883.72 | 1824.43 | 1012.15 | 812.28 | 0.00 | 0.00 |
May | 3069.85 | 533.57 | 1882.72 | 1023.19 | 859.53 | 0.00 | 0.00 |
June | 3560.16 | 280.73 | 1883.78 | 1047.98 | 835.80 | 0.00 | 0.00 |
July | 3217.90 | 225.67 | 1689.34 | 883.16 | 806.18 | 0.00 | 0.00 |
August | 2924.82 | 308.75 | 1607.50 | 822.70 | 784.79 | 0.00 | 0.00 |
September | 2664.17 | 595.16 | 1592.59 | 908.69 | 683.90 | 0.00 | 0.00 |
October | 1659.26 | 988.24 | 1224.80 | 661.01 | 563.79 | 0.00 | 0.00 |
November | 1091.70 | 1711.90 | 1097.93 | 639.18 | 458.75 | 0.00 | 0.00 |
December | 721.17 | 2274.96 | 915.82 | 485.22 | 430.60 | 0.00 | 0.00 |
Annual Sum or Average | 2101.91 | 1095.47 | 1448.16 | 792.39 | 655.77 | 0.00 | 0.00 |
Minimum of Months | 721.17 | 225.67 | 915.82 | 485.22 | 419.38 | 0.00 | 0.00 |
Maximum of Months | 3560.16 | 2274.96 | 1883.78 | 1047.98 | 859.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4388.46 | 3066.05 | 3516.63 | 2664.21 | 852.41 | 0.00 | 0.00 |
February | 4151.33 | 2771.08 | 3262.06 | 2299.70 | 962.36 | 0.00 | 0.00 |
March | 3469.18 | 2427.20 | 2651.10 | 1528.62 | 1122.48 | 0.00 | 0.00 |
April | 2758.16 | 1494.39 | 1797.44 | 670.67 | 1126.77 | 0.00 | 0.00 |
May | 2264.13 | 873.97 | 1270.23 | 177.79 | 1092.44 | 0.00 | 0.00 |
June | 2534.65 | 445.18 | 1095.89 | 69.53 | 1026.35 | 0.00 | 0.00 |
July | 2556.27 | 358.13 | 1117.14 | 103.56 | 1013.58 | 0.00 | 0.00 |
August | 2979.99 | 510.09 | 1424.04 | 376.95 | 1047.09 | 0.00 | 0.00 |
September | 4118.03 | 1006.23 | 2222.77 | 1154.81 | 1067.96 | 0.00 | 0.00 |
October | 4645.48 | 1604.47 | 3020.09 | 2041.78 | 978.31 | 0.00 | 0.00 |
November | 4837.48 | 2609.87 | 3634.40 | 2770.78 | 863.62 | 0.00 | 0.00 |
December | 4388.82 | 3302.14 | 3601.83 | 2703.70 | 898.13 | 0.00 | 0.00 |
Annual Sum or Average | 3586.71 | 1700.45 | 2379.41 | 1374.96 | 1004.45 | 0.00 | 0.00 |
Minimum of Months | 2264.13 | 358.13 | 1095.89 | 69.53 | 852.41 | 0.00 | 0.00 |
Maximum of Months | 4837.48 | 3302.14 | 3634.40 | 2770.78 | 1126.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 963.17 | 2195.36 | 965.54 | 543.77 | 421.78 | 0.00 | 0.00 |
February | 1181.32 | 1982.74 | 1089.51 | 579.10 | 510.41 | 0.00 | 0.00 |
March | 1801.49 | 1688.38 | 1484.69 | 795.74 | 688.95 | 0.00 | 0.00 |
April | 2510.78 | 1039.11 | 1706.53 | 921.73 | 784.80 | 0.00 | 0.00 |
May | 3080.06 | 638.35 | 1838.10 | 983.47 | 854.63 | 0.00 | 0.00 |
June | 3451.36 | 343.56 | 1789.25 | 961.02 | 828.22 | 0.00 | 0.00 |
July | 3079.15 | 279.22 | 1587.83 | 789.02 | 798.81 | 0.00 | 0.00 |
August | 2841.34 | 373.83 | 1537.73 | 783.69 | 754.04 | 0.00 | 0.00 |
September | 2745.50 | 700.08 | 1572.57 | 876.08 | 696.49 | 0.00 | 0.00 |
October | 2000.87 | 1102.87 | 1353.73 | 790.08 | 563.65 | 0.00 | 0.00 |
November | 1333.01 | 1866.41 | 1136.25 | 691.86 | 444.40 | 0.00 | 0.00 |
December | 859.40 | 2414.24 | 915.65 | 497.41 | 418.24 | 0.00 | 0.00 |
Annual Sum or Average | 2158.04 | 1214.93 | 1415.96 | 768.26 | 647.70 | 0.00 | 0.00 |
Minimum of Months | 859.40 | 279.22 | 915.65 | 497.41 | 418.24 | 0.00 | 0.00 |
Maximum of Months | 3451.36 | 2414.24 | 1838.10 | 983.47 | 854.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 88.80 | 2996.44 | 514.06 | 0.00 | 514.06 | 0.00 | 0.00 |
February | 255.28 | 2689.29 | 627.72 | 0.00 | 627.72 | 0.00 | 0.00 |
March | 504.79 | 2270.09 | 821.48 | 0.00 | 821.48 | 0.00 | 0.00 |
April | 1060.38 | 1319.47 | 948.49 | 7.47 | 941.01 | 0.00 | 0.00 |
May | 1818.82 | 777.72 | 1124.94 | 81.35 | 1043.59 | 0.00 | 0.00 |
June | 2609.45 | 435.04 | 1196.18 | 147.26 | 1048.92 | 0.00 | 0.00 |
July | 2404.35 | 347.76 | 1105.50 | 107.61 | 997.89 | 0.00 | 0.00 |
August | 1862.89 | 460.38 | 932.18 | 19.06 | 913.12 | 0.00 | 0.00 |
September | 1408.66 | 902.93 | 813.41 | 0.32 | 813.09 | 0.00 | 0.00 |
October | 714.71 | 1418.49 | 675.36 | 0.00 | 675.36 | 0.00 | 0.00 |
November | 172.90 | 2478.47 | 545.21 | 0.00 | 545.21 | 0.00 | 0.00 |
December | 66.52 | 3341.52 | 510.07 | 0.00 | 510.07 | 0.00 | 0.00 |
Annual Sum or Average | 1084.87 | 1614.69 | 818.81 | 30.41 | 788.40 | 0.00 | 0.00 |
Minimum of Months | 66.52 | 347.76 | 510.07 | 0.00 | 510.07 | 0.00 | 0.00 |
Maximum of Months | 2609.45 | 3341.52 | 1196.18 | 147.26 | 1048.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 825.42 | 1824.54 | 916.61 | 497.23 | 419.38 | 0.00 | 0.00 |
February | 1304.36 | 1639.75 | 1226.33 | 699.00 | 527.33 | 0.00 | 0.00 |
March | 1747.40 | 1400.68 | 1514.12 | 834.23 | 679.89 | 0.00 | 0.00 |
April | 2566.11 | 838.84 | 1824.43 | 1012.15 | 812.28 | 0.00 | 0.00 |
May | 3051.37 | 517.50 | 1882.72 | 1023.19 | 859.53 | 0.00 | 0.00 |
June | 3525.52 | 281.17 | 1883.78 | 1047.98 | 835.80 | 0.00 | 0.00 |
July | 3179.60 | 228.44 | 1689.34 | 883.16 | 806.18 | 0.00 | 0.00 |
August | 2899.21 | 302.09 | 1607.50 | 822.70 | 784.79 | 0.00 | 0.00 |
September | 2654.57 | 574.37 | 1592.59 | 908.69 | 683.90 | 0.00 | 0.00 |
October | 1678.48 | 912.28 | 1224.80 | 661.01 | 563.79 | 0.00 | 0.00 |
November | 1152.32 | 1525.04 | 1097.93 | 639.18 | 458.75 | 0.00 | 0.00 |
December | 784.02 | 2024.85 | 915.82 | 485.22 | 430.60 | 0.00 | 0.00 |
Annual Sum or Average | 2116.73 | 1002.79 | 1448.16 | 792.39 | 655.77 | 0.00 | 0.00 |
Minimum of Months | 784.02 | 228.44 | 915.82 | 485.22 | 419.38 | 0.00 | 0.00 |
Maximum of Months | 3525.52 | 2024.85 | 1883.78 | 1047.98 | 859.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4458.34 | 2754.31 | 3516.63 | 2664.21 | 852.41 | 0.00 | 0.00 |
February | 4208.04 | 2515.19 | 3262.06 | 2299.70 | 962.36 | 0.00 | 0.00 |
March | 3501.66 | 2233.80 | 2651.10 | 1528.62 | 1122.48 | 0.00 | 0.00 |
April | 2752.41 | 1395.91 | 1797.44 | 670.67 | 1126.77 | 0.00 | 0.00 |
May | 2237.15 | 830.47 | 1270.23 | 177.79 | 1092.44 | 0.00 | 0.00 |
June | 2489.06 | 439.15 | 1095.89 | 69.53 | 1026.35 | 0.00 | 0.00 |
July | 2503.98 | 357.25 | 1117.14 | 103.56 | 1013.58 | 0.00 | 0.00 |
August | 2941.78 | 490.63 | 1424.04 | 376.95 | 1047.09 | 0.00 | 0.00 |
September | 4097.13 | 956.23 | 2222.77 | 1154.81 | 1067.96 | 0.00 | 0.00 |
October | 4659.39 | 1475.78 | 3020.09 | 2041.78 | 978.31 | 0.00 | 0.00 |
November | 4907.36 | 2339.83 | 3634.40 | 2770.78 | 863.62 | 0.00 | 0.00 |
December | 4485.06 | 2971.90 | 3601.83 | 2703.70 | 898.13 | 0.00 | 0.00 |
Annual Sum or Average | 3598.94 | 1558.62 | 2379.41 | 1374.96 | 1004.45 | 0.00 | 0.00 |
Minimum of Months | 2237.15 | 357.25 | 1095.89 | 69.53 | 852.41 | 0.00 | 0.00 |
Maximum of Months | 4907.36 | 2971.90 | 3634.40 | 2770.78 | 1126.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 975.15 | 2014.10 | 965.54 | 543.77 | 421.78 | 0.00 | 0.00 |
February | 1190.67 | 1831.28 | 1089.51 | 579.10 | 510.41 | 0.00 | 0.00 |
March | 1799.51 | 1569.01 | 1484.69 | 795.74 | 688.95 | 0.00 | 0.00 |
April | 2497.53 | 978.40 | 1706.53 | 921.73 | 784.80 | 0.00 | 0.00 |
May | 3056.26 | 609.65 | 1838.10 | 983.47 | 854.63 | 0.00 | 0.00 |
June | 3420.47 | 337.46 | 1789.25 | 961.02 | 828.22 | 0.00 | 0.00 |
July | 3048.52 | 275.56 | 1587.83 | 789.02 | 798.81 | 0.00 | 0.00 |
August | 2817.99 | 359.49 | 1537.73 | 783.69 | 754.04 | 0.00 | 0.00 |
September | 2731.55 | 668.73 | 1572.57 | 876.08 | 696.49 | 0.00 | 0.00 |
October | 2000.08 | 1024.51 | 1353.73 | 790.08 | 563.65 | 0.00 | 0.00 |
November | 1343.50 | 1696.43 | 1136.25 | 691.86 | 444.40 | 0.00 | 0.00 |
December | 877.65 | 2207.61 | 915.65 | 497.41 | 418.24 | 0.00 | 0.00 |
Annual Sum or Average | 2150.58 | 1127.57 | 1415.96 | 768.26 | 647.70 | 0.00 | 0.00 |
Minimum of Months | 877.65 | 275.56 | 915.65 | 497.41 | 418.24 | 0.00 | 0.00 |
Maximum of Months | 3420.47 | 2207.61 | 1838.10 | 983.47 | 854.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 63306408.24 | 0.994499E+10 | 0.137685E+10 | 0.00 | 0.137685E+10 | 0.00 | 0.00 |
February | 0.397928E+09 | 0.785631E+10 | 0.151858E+10 | 0.00 | 0.151858E+10 | 0.00 | 0.00 |
March | 0.109655E+10 | 0.726833E+10 | 0.220025E+10 | 0.00 | 0.220025E+10 | 0.00 | 0.00 |
April | 0.253129E+10 | 0.407487E+10 | 0.245849E+10 | 19369321.27 | 0.243912E+10 | 0.00 | 0.00 |
May | 0.478878E+10 | 0.235058E+10 | 0.301305E+10 | 0.217886E+09 | 0.279517E+10 | 0.00 | 0.00 |
June | 0.678234E+10 | 0.116063E+10 | 0.310051E+10 | 0.381709E+09 | 0.271880E+10 | 0.00 | 0.00 |
July | 0.646164E+10 | 0.922109E+09 | 0.296099E+10 | 0.288230E+09 | 0.267276E+10 | 0.00 | 0.00 |
August | 0.493549E+10 | 0.132198E+10 | 0.249676E+10 | 51052290.93 | 0.244571E+10 | 0.00 | 0.00 |
September | 0.355341E+10 | 0.269223E+10 | 0.210837E+10 | 841315.33 | 0.210753E+10 | 0.00 | 0.00 |
October | 0.166555E+10 | 0.468414E+10 | 0.180888E+10 | 0.00 | 0.180888E+10 | 0.00 | 0.00 |
November | 0.225993E+09 | 0.818866E+10 | 0.141319E+10 | 0.00 | 0.141319E+10 | 0.00 | 0.00 |
December | 45798180.33 | 0.112030E+11 | 0.136619E+10 | 0.00 | 0.136619E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.325481E+11 | 0.616678E+11 | 0.258221E+11 | 0.959088E+09 | 0.248630E+11 | 0.00 | 0.00 |
Minimum of Months | 45798180.33 | 0.922109E+09 | 0.136619E+10 | 0.00 | 0.136619E+10 | 0.00 | 0.00 |
Maximum of Months | 0.678234E+10 | 0.112030E+11 | 0.310051E+10 | 0.381709E+09 | 0.279517E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.201139E+10 | 0.588358E+10 | 0.245505E+10 | 0.133177E+10 | 0.112327E+10 | 0.00 | 0.00 |
February | 0.299707E+10 | 0.462635E+10 | 0.296675E+10 | 0.169103E+10 | 0.127572E+10 | 0.00 | 0.00 |
March | 0.460441E+10 | 0.424656E+10 | 0.405542E+10 | 0.223441E+10 | 0.182102E+10 | 0.00 | 0.00 |
April | 0.671641E+10 | 0.236518E+10 | 0.472895E+10 | 0.262351E+10 | 0.210544E+10 | 0.00 | 0.00 |
May | 0.830187E+10 | 0.149150E+10 | 0.504269E+10 | 0.274051E+10 | 0.230217E+10 | 0.00 | 0.00 |
June | 0.932151E+10 | 0.691774E+09 | 0.488277E+10 | 0.271638E+10 | 0.216639E+10 | 0.00 | 0.00 |
July | 0.872321E+10 | 0.519956E+09 | 0.452474E+10 | 0.236546E+10 | 0.215928E+10 | 0.00 | 0.00 |
August | 0.793224E+10 | 0.743523E+09 | 0.430553E+10 | 0.220353E+10 | 0.210200E+10 | 0.00 | 0.00 |
September | 0.695490E+10 | 0.160952E+10 | 0.412802E+10 | 0.235533E+10 | 0.177268E+10 | 0.00 | 0.00 |
October | 0.446526E+10 | 0.282718E+10 | 0.328053E+10 | 0.177047E+10 | 0.151006E+10 | 0.00 | 0.00 |
November | 0.280771E+10 | 0.475924E+10 | 0.284584E+10 | 0.165676E+10 | 0.118908E+10 | 0.00 | 0.00 |
December | 0.187320E+10 | 0.650998E+10 | 0.245294E+10 | 0.129962E+10 | 0.115332E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.667092E+11 | 0.362744E+11 | 0.456692E+11 | 0.249888E+11 | 0.206804E+11 | 0.00 | 0.00 |
Minimum of Months | 0.187320E+10 | 0.519956E+09 | 0.245294E+10 | 0.129962E+10 | 0.112327E+10 | 0.00 | 0.00 |
Maximum of Months | 0.932151E+10 | 0.650998E+10 | 0.504269E+10 | 0.274051E+10 | 0.230217E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119096E+11 | 0.835470E+10 | 0.941897E+10 | 0.713585E+10 | 0.228312E+10 | 0.00 | 0.00 |
February | 0.101933E+11 | 0.678857E+10 | 0.789161E+10 | 0.556346E+10 | 0.232815E+10 | 0.00 | 0.00 |
March | 0.942856E+10 | 0.665399E+10 | 0.710074E+10 | 0.409427E+10 | 0.300647E+10 | 0.00 | 0.00 |
April | 0.715612E+10 | 0.405509E+10 | 0.465898E+10 | 0.173838E+10 | 0.292059E+10 | 0.00 | 0.00 |
May | 0.601810E+10 | 0.246464E+10 | 0.340220E+10 | 0.476196E+09 | 0.292600E+10 | 0.00 | 0.00 |
June | 0.646464E+10 | 0.117532E+10 | 0.284055E+10 | 0.180234E+09 | 0.266032E+10 | 0.00 | 0.00 |
July | 0.675364E+10 | 0.940038E+09 | 0.299215E+10 | 0.277378E+09 | 0.271477E+10 | 0.00 | 0.00 |
August | 0.792742E+10 | 0.135866E+10 | 0.381417E+10 | 0.100963E+10 | 0.280454E+10 | 0.00 | 0.00 |
September | 0.107268E+11 | 0.269188E+10 | 0.576144E+10 | 0.299327E+10 | 0.276817E+10 | 0.00 | 0.00 |
October | 0.125572E+11 | 0.441738E+10 | 0.808903E+10 | 0.546873E+10 | 0.262031E+10 | 0.00 | 0.00 |
November | 0.126647E+11 | 0.693228E+10 | 0.942040E+10 | 0.718190E+10 | 0.223850E+10 | 0.00 | 0.00 |
December | 0.118454E+11 | 0.908015E+10 | 0.964718E+10 | 0.724161E+10 | 0.240557E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.113646E+12 | 0.549127E+11 | 0.750374E+11 | 0.433609E+11 | 0.316765E+11 | 0.00 | 0.00 |
Minimum of Months | 0.601810E+10 | 0.940038E+09 | 0.284055E+10 | 0.180234E+09 | 0.223850E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126647E+11 | 0.908015E+10 | 0.964718E+10 | 0.724161E+10 | 0.300647E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.248525E+10 | 0.655942E+10 | 0.258612E+10 | 0.145643E+10 | 0.112969E+10 | 0.00 | 0.00 |
February | 0.277564E+10 | 0.527634E+10 | 0.263576E+10 | 0.140096E+10 | 0.123480E+10 | 0.00 | 0.00 |
March | 0.470038E+10 | 0.508144E+10 | 0.397662E+10 | 0.213133E+10 | 0.184529E+10 | 0.00 | 0.00 |
April | 0.629751E+10 | 0.320052E+10 | 0.442335E+10 | 0.238913E+10 | 0.203422E+10 | 0.00 | 0.00 |
May | 0.819350E+10 | 0.190706E+10 | 0.492318E+10 | 0.263413E+10 | 0.228906E+10 | 0.00 | 0.00 |
June | 0.882545E+10 | 0.100121E+10 | 0.463774E+10 | 0.249098E+10 | 0.214677E+10 | 0.00 | 0.00 |
July | 0.806043E+10 | 0.864552E+09 | 0.425286E+10 | 0.211333E+10 | 0.213953E+10 | 0.00 | 0.00 |
August | 0.740062E+10 | 0.121806E+10 | 0.411868E+10 | 0.209904E+10 | 0.201964E+10 | 0.00 | 0.00 |
September | 0.702856E+10 | 0.203175E+10 | 0.407612E+10 | 0.227081E+10 | 0.180531E+10 | 0.00 | 0.00 |
October | 0.522862E+10 | 0.336649E+10 | 0.362583E+10 | 0.211615E+10 | 0.150968E+10 | 0.00 | 0.00 |
November | 0.331432E+10 | 0.556629E+10 | 0.294518E+10 | 0.179330E+10 | 0.115188E+10 | 0.00 | 0.00 |
December | 0.214188E+10 | 0.755612E+10 | 0.245250E+10 | 0.133228E+10 | 0.112022E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.664521E+11 | 0.436292E+11 | 0.446539E+11 | 0.242279E+11 | 0.204261E+11 | 0.00 | 0.00 |
Minimum of Months | 0.214188E+10 | 0.864552E+09 | 0.245250E+10 | 0.133228E+10 | 0.112022E+10 | 0.00 | 0.00 |
Maximum of Months | 0.882545E+10 | 0.755612E+10 | 0.492318E+10 | 0.263413E+10 | 0.228906E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.143903E+09 | 0.897779E+10 | 0.137685E+10 | 0.00 | 0.137685E+10 | 0.00 | 0.00 |
February | 0.518560E+09 | 0.721200E+10 | 0.151857E+10 | 0.00 | 0.151857E+10 | 0.00 | 0.00 |
March | 0.125179E+10 | 0.667560E+10 | 0.220024E+10 | 0.00 | 0.220024E+10 | 0.00 | 0.00 |
April | 0.271563E+10 | 0.370827E+10 | 0.245848E+10 | 19369252.49 | 0.243911E+10 | 0.00 | 0.00 |
May | 0.489098E+10 | 0.219831E+10 | 0.301304E+10 | 0.217885E+09 | 0.279516E+10 | 0.00 | 0.00 |
June | 0.686439E+10 | 0.114498E+10 | 0.310050E+10 | 0.381708E+09 | 0.271879E+10 | 0.00 | 0.00 |
July | 0.655071E+10 | 0.937271E+09 | 0.296098E+10 | 0.288229E+09 | 0.267275E+10 | 0.00 | 0.00 |
August | 0.505738E+10 | 0.129427E+10 | 0.249675E+10 | 51052109.64 | 0.244570E+10 | 0.00 | 0.00 |
September | 0.366119E+10 | 0.249503E+10 | 0.210836E+10 | 841312.35 | 0.210752E+10 | 0.00 | 0.00 |
October | 0.182603E+10 | 0.422714E+10 | 0.180887E+10 | 0.00 | 0.180887E+10 | 0.00 | 0.00 |
November | 0.353119E+09 | 0.728974E+10 | 0.141319E+10 | 0.00 | 0.141319E+10 | 0.00 | 0.00 |
December | 0.101194E+09 | 0.999100E+10 | 0.136618E+10 | 0.00 | 0.136618E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.339349E+11 | 0.561514E+11 | 0.258220E+11 | 0.959085E+09 | 0.248629E+11 | 0.00 | 0.00 |
Minimum of Months | 0.101194E+09 | 0.937271E+09 | 0.136618E+10 | 0.00 | 0.136618E+10 | 0.00 | 0.00 |
Maximum of Months | 0.686439E+10 | 0.999100E+10 | 0.310050E+10 | 0.381708E+09 | 0.279516E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.205006E+10 | 0.549818E+10 | 0.245504E+10 | 0.133177E+10 | 0.112327E+10 | 0.00 | 0.00 |
February | 0.300960E+10 | 0.439571E+10 | 0.296674E+10 | 0.169102E+10 | 0.127572E+10 | 0.00 | 0.00 |
March | 0.456553E+10 | 0.405415E+10 | 0.405541E+10 | 0.223440E+10 | 0.182101E+10 | 0.00 | 0.00 |
April | 0.664675E+10 | 0.229061E+10 | 0.472893E+10 | 0.262350E+10 | 0.210543E+10 | 0.00 | 0.00 |
May | 0.822228E+10 | 0.142911E+10 | 0.504267E+10 | 0.274050E+10 | 0.230216E+10 | 0.00 | 0.00 |
June | 0.922794E+10 | 0.727650E+09 | 0.488275E+10 | 0.271637E+10 | 0.216638E+10 | 0.00 | 0.00 |
July | 0.861883E+10 | 0.604433E+09 | 0.452472E+10 | 0.236545E+10 | 0.215927E+10 | 0.00 | 0.00 |
August | 0.783383E+10 | 0.826953E+09 | 0.430552E+10 | 0.220352E+10 | 0.210199E+10 | 0.00 | 0.00 |
September | 0.690553E+10 | 0.154265E+10 | 0.412800E+10 | 0.235532E+10 | 0.177267E+10 | 0.00 | 0.00 |
October | 0.444417E+10 | 0.264691E+10 | 0.328051E+10 | 0.177046E+10 | 0.151005E+10 | 0.00 | 0.00 |
November | 0.282969E+10 | 0.443726E+10 | 0.284583E+10 | 0.165675E+10 | 0.118908E+10 | 0.00 | 0.00 |
December | 0.193159E+10 | 0.609324E+10 | 0.245293E+10 | 0.129962E+10 | 0.115331E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.662858E+11 | 0.345469E+11 | 0.456690E+11 | 0.249887E+11 | 0.206804E+11 | 0.00 | 0.00 |
Minimum of Months | 0.193159E+10 | 0.604433E+09 | 0.245293E+10 | 0.129962E+10 | 0.112327E+10 | 0.00 | 0.00 |
Maximum of Months | 0.922794E+10 | 0.609324E+10 | 0.504267E+10 | 0.274050E+10 | 0.230216E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117541E+11 | 0.821210E+10 | 0.941893E+10 | 0.713583E+10 | 0.228311E+10 | 0.00 | 0.00 |
February | 0.100429E+11 | 0.670380E+10 | 0.789158E+10 | 0.556344E+10 | 0.232814E+10 | 0.00 | 0.00 |
March | 0.929185E+10 | 0.650101E+10 | 0.710072E+10 | 0.409425E+10 | 0.300646E+10 | 0.00 | 0.00 |
April | 0.714915E+10 | 0.387346E+10 | 0.465896E+10 | 0.173837E+10 | 0.292058E+10 | 0.00 | 0.00 |
May | 0.606425E+10 | 0.234084E+10 | 0.340218E+10 | 0.476194E+09 | 0.292599E+10 | 0.00 | 0.00 |
June | 0.656980E+10 | 0.115392E+10 | 0.284054E+10 | 0.180233E+09 | 0.266031E+10 | 0.00 | 0.00 |
July | 0.684672E+10 | 0.959203E+09 | 0.299214E+10 | 0.277377E+09 | 0.271476E+10 | 0.00 | 0.00 |
August | 0.798160E+10 | 0.136623E+10 | 0.381415E+10 | 0.100963E+10 | 0.280452E+10 | 0.00 | 0.00 |
September | 0.106739E+11 | 0.260816E+10 | 0.576142E+10 | 0.299326E+10 | 0.276816E+10 | 0.00 | 0.00 |
October | 0.124424E+11 | 0.429741E+10 | 0.808900E+10 | 0.546871E+10 | 0.262030E+10 | 0.00 | 0.00 |
November | 0.125387E+11 | 0.676478E+10 | 0.942036E+10 | 0.718187E+10 | 0.223849E+10 | 0.00 | 0.00 |
December | 0.117550E+11 | 0.884446E+10 | 0.964714E+10 | 0.724158E+10 | 0.240556E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.113110E+12 | 0.536254E+11 | 0.750371E+11 | 0.433607E+11 | 0.316764E+11 | 0.00 | 0.00 |
Minimum of Months | 0.606425E+10 | 0.959203E+09 | 0.284054E+10 | 0.180233E+09 | 0.223849E+10 | 0.00 | 0.00 |
Maximum of Months | 0.125387E+11 | 0.884446E+10 | 0.964714E+10 | 0.724158E+10 | 0.300646E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.257975E+10 | 0.588006E+10 | 0.258610E+10 | 0.145642E+10 | 0.112968E+10 | 0.00 | 0.00 |
February | 0.285784E+10 | 0.479666E+10 | 0.263575E+10 | 0.140096E+10 | 0.123479E+10 | 0.00 | 0.00 |
March | 0.482512E+10 | 0.452215E+10 | 0.397660E+10 | 0.213132E+10 | 0.184528E+10 | 0.00 | 0.00 |
April | 0.650795E+10 | 0.269337E+10 | 0.442333E+10 | 0.238912E+10 | 0.203421E+10 | 0.00 | 0.00 |
May | 0.824963E+10 | 0.170975E+10 | 0.492316E+10 | 0.263412E+10 | 0.228905E+10 | 0.00 | 0.00 |
June | 0.894592E+10 | 0.890498E+09 | 0.463773E+10 | 0.249097E+10 | 0.214676E+10 | 0.00 | 0.00 |
July | 0.824720E+10 | 0.747868E+09 | 0.425284E+10 | 0.211332E+10 | 0.213952E+10 | 0.00 | 0.00 |
August | 0.761025E+10 | 0.100125E+10 | 0.411866E+10 | 0.209903E+10 | 0.201963E+10 | 0.00 | 0.00 |
September | 0.711632E+10 | 0.181460E+10 | 0.407610E+10 | 0.227080E+10 | 0.180530E+10 | 0.00 | 0.00 |
October | 0.535914E+10 | 0.295392E+10 | 0.362582E+10 | 0.211615E+10 | 0.150967E+10 | 0.00 | 0.00 |
November | 0.345516E+10 | 0.483774E+10 | 0.294517E+10 | 0.179329E+10 | 0.115187E+10 | 0.00 | 0.00 |
December | 0.230181E+10 | 0.646630E+10 | 0.245249E+10 | 0.133227E+10 | 0.112022E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.680561E+11 | 0.383142E+11 | 0.446538E+11 | 0.242278E+11 | 0.204260E+11 | 0.00 | 0.00 |
Minimum of Months | 0.230181E+10 | 0.747868E+09 | 0.245249E+10 | 0.133227E+10 | 0.112022E+10 | 0.00 | 0.00 |
Maximum of Months | 0.894592E+10 | 0.646630E+10 | 0.492316E+10 | 0.263412E+10 | 0.228905E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.237832E+09 | 0.802566E+10 | 0.137685E+10 | 0.00 | 0.137685E+10 | 0.00 | 0.00 |
February | 0.617569E+09 | 0.650594E+10 | 0.151857E+10 | 0.00 | 0.151857E+10 | 0.00 | 0.00 |
March | 0.135203E+10 | 0.608021E+10 | 0.220024E+10 | 0.00 | 0.220024E+10 | 0.00 | 0.00 |
April | 0.274851E+10 | 0.342006E+10 | 0.245848E+10 | 19369252.49 | 0.243911E+10 | 0.00 | 0.00 |
May | 0.487153E+10 | 0.208305E+10 | 0.301304E+10 | 0.217885E+09 | 0.279516E+10 | 0.00 | 0.00 |
June | 0.676370E+10 | 0.112762E+10 | 0.310050E+10 | 0.381708E+09 | 0.271879E+10 | 0.00 | 0.00 |
July | 0.643981E+10 | 0.931428E+09 | 0.296098E+10 | 0.288229E+09 | 0.267275E+10 | 0.00 | 0.00 |
August | 0.498957E+10 | 0.123308E+10 | 0.249675E+10 | 51052109.64 | 0.244570E+10 | 0.00 | 0.00 |
September | 0.365126E+10 | 0.234040E+10 | 0.210836E+10 | 841312.35 | 0.210752E+10 | 0.00 | 0.00 |
October | 0.191428E+10 | 0.379929E+10 | 0.180887E+10 | 0.00 | 0.180887E+10 | 0.00 | 0.00 |
November | 0.448146E+09 | 0.642421E+10 | 0.141319E+10 | 0.00 | 0.141319E+10 | 0.00 | 0.00 |
December | 0.178156E+09 | 0.894993E+10 | 0.136618E+10 | 0.00 | 0.136618E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.342124E+11 | 0.509209E+11 | 0.258220E+11 | 0.959085E+09 | 0.248629E+11 | 0.00 | 0.00 |
Minimum of Months | 0.178156E+09 | 0.931428E+09 | 0.136618E+10 | 0.00 | 0.136618E+10 | 0.00 | 0.00 |
Maximum of Months | 0.676370E+10 | 0.894993E+10 | 0.310050E+10 | 0.381708E+09 | 0.279516E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.221082E+10 | 0.488686E+10 | 0.245504E+10 | 0.133177E+10 | 0.112327E+10 | 0.00 | 0.00 |
February | 0.315550E+10 | 0.396689E+10 | 0.296674E+10 | 0.169102E+10 | 0.127572E+10 | 0.00 | 0.00 |
March | 0.468024E+10 | 0.375158E+10 | 0.405541E+10 | 0.223440E+10 | 0.182101E+10 | 0.00 | 0.00 |
April | 0.665135E+10 | 0.217428E+10 | 0.472893E+10 | 0.262350E+10 | 0.210543E+10 | 0.00 | 0.00 |
May | 0.817279E+10 | 0.138606E+10 | 0.504267E+10 | 0.274050E+10 | 0.230216E+10 | 0.00 | 0.00 |
June | 0.913816E+10 | 0.728801E+09 | 0.488275E+10 | 0.271637E+10 | 0.216638E+10 | 0.00 | 0.00 |
July | 0.851623E+10 | 0.611859E+09 | 0.452472E+10 | 0.236545E+10 | 0.215927E+10 | 0.00 | 0.00 |
August | 0.776523E+10 | 0.809114E+09 | 0.430552E+10 | 0.220352E+10 | 0.210199E+10 | 0.00 | 0.00 |
September | 0.688064E+10 | 0.148875E+10 | 0.412800E+10 | 0.235532E+10 | 0.177267E+10 | 0.00 | 0.00 |
October | 0.449563E+10 | 0.244345E+10 | 0.328051E+10 | 0.177046E+10 | 0.151005E+10 | 0.00 | 0.00 |
November | 0.298681E+10 | 0.395289E+10 | 0.284583E+10 | 0.165675E+10 | 0.118908E+10 | 0.00 | 0.00 |
December | 0.209992E+10 | 0.542335E+10 | 0.245293E+10 | 0.129962E+10 | 0.115331E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.667533E+11 | 0.316239E+11 | 0.456690E+11 | 0.249887E+11 | 0.206804E+11 | 0.00 | 0.00 |
Minimum of Months | 0.209992E+10 | 0.611859E+09 | 0.245293E+10 | 0.129962E+10 | 0.112327E+10 | 0.00 | 0.00 |
Maximum of Months | 0.913816E+10 | 0.542335E+10 | 0.504267E+10 | 0.274050E+10 | 0.230216E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119412E+11 | 0.737715E+10 | 0.941893E+10 | 0.713583E+10 | 0.228311E+10 | 0.00 | 0.00 |
February | 0.101801E+11 | 0.608476E+10 | 0.789158E+10 | 0.556344E+10 | 0.232814E+10 | 0.00 | 0.00 |
March | 0.937885E+10 | 0.598301E+10 | 0.710072E+10 | 0.409425E+10 | 0.300646E+10 | 0.00 | 0.00 |
April | 0.713424E+10 | 0.361820E+10 | 0.465896E+10 | 0.173837E+10 | 0.292058E+10 | 0.00 | 0.00 |
May | 0.599197E+10 | 0.222434E+10 | 0.340218E+10 | 0.476194E+09 | 0.292599E+10 | 0.00 | 0.00 |
June | 0.645163E+10 | 0.113827E+10 | 0.284054E+10 | 0.180233E+09 | 0.266031E+10 | 0.00 | 0.00 |
July | 0.670665E+10 | 0.956869E+09 | 0.299214E+10 | 0.277377E+09 | 0.271476E+10 | 0.00 | 0.00 |
August | 0.787927E+10 | 0.131411E+10 | 0.381415E+10 | 0.100963E+10 | 0.280452E+10 | 0.00 | 0.00 |
September | 0.106197E+11 | 0.247854E+10 | 0.576142E+10 | 0.299326E+10 | 0.276816E+10 | 0.00 | 0.00 |
October | 0.124797E+11 | 0.395272E+10 | 0.808900E+10 | 0.546871E+10 | 0.262030E+10 | 0.00 | 0.00 |
November | 0.127199E+11 | 0.606484E+10 | 0.942036E+10 | 0.718187E+10 | 0.223849E+10 | 0.00 | 0.00 |
December | 0.120128E+11 | 0.795995E+10 | 0.964714E+10 | 0.724158E+10 | 0.240556E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.113496E+12 | 0.491528E+11 | 0.750371E+11 | 0.433607E+11 | 0.316764E+11 | 0.00 | 0.00 |
Minimum of Months | 0.599197E+10 | 0.956869E+09 | 0.284054E+10 | 0.180233E+09 | 0.223849E+10 | 0.00 | 0.00 |
Maximum of Months | 0.127199E+11 | 0.795995E+10 | 0.964714E+10 | 0.724158E+10 | 0.300646E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.261185E+10 | 0.539456E+10 | 0.258610E+10 | 0.145642E+10 | 0.112968E+10 | 0.00 | 0.00 |
February | 0.288048E+10 | 0.443023E+10 | 0.263575E+10 | 0.140096E+10 | 0.123479E+10 | 0.00 | 0.00 |
March | 0.481980E+10 | 0.420244E+10 | 0.397660E+10 | 0.213132E+10 | 0.184528E+10 | 0.00 | 0.00 |
April | 0.647361E+10 | 0.253600E+10 | 0.442333E+10 | 0.238912E+10 | 0.203421E+10 | 0.00 | 0.00 |
May | 0.818588E+10 | 0.163288E+10 | 0.492316E+10 | 0.263412E+10 | 0.228905E+10 | 0.00 | 0.00 |
June | 0.886586E+10 | 0.874700E+09 | 0.463773E+10 | 0.249097E+10 | 0.214676E+10 | 0.00 | 0.00 |
July | 0.816516E+10 | 0.738061E+09 | 0.425284E+10 | 0.211332E+10 | 0.213952E+10 | 0.00 | 0.00 |
August | 0.754770E+10 | 0.962858E+09 | 0.411866E+10 | 0.209903E+10 | 0.201963E+10 | 0.00 | 0.00 |
September | 0.708018E+10 | 0.173336E+10 | 0.407610E+10 | 0.227080E+10 | 0.180530E+10 | 0.00 | 0.00 |
October | 0.535702E+10 | 0.274404E+10 | 0.362582E+10 | 0.211615E+10 | 0.150967E+10 | 0.00 | 0.00 |
November | 0.348236E+10 | 0.439715E+10 | 0.294517E+10 | 0.179329E+10 | 0.115187E+10 | 0.00 | 0.00 |
December | 0.235069E+10 | 0.591287E+10 | 0.245249E+10 | 0.133227E+10 | 0.112022E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.678206E+11 | 0.355591E+11 | 0.446538E+11 | 0.242278E+11 | 0.204260E+11 | 0.00 | 0.00 |
Minimum of Months | 0.235069E+10 | 0.738061E+09 | 0.245249E+10 | 0.133227E+10 | 0.112022E+10 | 0.00 | 0.00 |
Maximum of Months | 0.886586E+10 | 0.591287E+10 | 0.492316E+10 | 0.263412E+10 | 0.228905E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.361234E+11 | -0.356750E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -448454471.2 | 60.05 | 0.00 | 0.00 |
February | 0.327970E+11 | -0.323926E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -404415441.6 | 60.05 | 0.00 | 0.00 |
March | 0.371788E+11 | -0.367302E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -448602270.8 | 60.05 | 0.00 | 0.00 |
April | 0.315745E+11 | -0.311436E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -430865097.4 | 60.05 | 0.00 | 0.00 |
May | 0.310527E+11 | -0.306080E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444659903.7 | 60.05 | 0.00 | 0.00 |
June | 0.284260E+11 | -0.279958E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -430270625.7 | 60.05 | 0.00 | 0.00 |
July | 0.257914E+11 | -0.253493E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442125548.5 | 60.05 | 0.00 | 0.00 |
August | 0.282273E+11 | -0.277836E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443637330.2 | 60.05 | 0.00 | 0.00 |
September | 0.269275E+11 | -0.264993E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -428149931.3 | 60.05 | 0.00 | 0.00 |
October | 0.300336E+11 | -0.295908E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442775298.1 | 60.05 | 0.00 | 0.00 |
November | 0.319864E+11 | -0.315565E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -429913138.9 | 60.05 | 0.00 | 0.00 |
December | 0.340147E+11 | -0.335685E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -446253632.6 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.374133E+12 | -0.368893E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.524012E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.257914E+11 | -0.367302E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -448602270.8 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.371788E+11 | -0.253493E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -404415441.6 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 373.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 400.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 377.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 365.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 295.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4125.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 55306231.03 | 7498.14 | 27-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 70194059.84 | 8960.91 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8171024.71 | 2663.38 | 02-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 80939489.74 | 6999.72 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80939489.74 | 8960.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.359874E+09 | 15562.39 | 28-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.237227E+09 | 15731.80 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 91491531.74 | 15742.61 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 56276763.75 | 14516.80 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.298964E+09 | 15717.40 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.359874E+09 | 15742.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.497762E+09 | 12660.97 | 28-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.262106E+09 | 12800.66 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171214E+09 | 12889.50 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10052449.46 | 2649.70 | 12-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4014767.79 | 1310.51 | 25-OCT-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125534E+09 | 11798.26 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.538604E+09 | 12787.86 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.538604E+09 | 12889.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.528792E+09 | 18237.87 | 28-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.312478E+09 | 18513.51 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209705E+09 | 18561.49 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13116339.78 | 2447.82 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1399618.29 | 666.76 | 25-OCT-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147230E+09 | 17169.99 | 28-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.499286E+09 | 18419.29 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.528792E+09 | 18561.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.267630E+09 | 5446.85 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178060E+09 | 6602.48 | 10-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 40206515.43 | 5123.12 | 01-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22149961.53 | 3013.81 | 28-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 54405267.89 | 2914.99 | 28-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.562452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.267630E+09 | 6602.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.316622E+10 | 255907.90 | 26-JAN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.208460E+10 | 277356.72 | 09-FEB-14:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.574980E+09 | 272457.55 | 01-MAR-14:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31871348.94 | 241351.84 | 11-APR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3909860.70 | 52131.48 | 24-OCT-11:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143846E+09 | 260112.58 | 16-NOV-10:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.606974E+10 | 260705.03 | 22-DEC-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.606974E+10 | 277356.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.215258E+11 | 193795.99 | 28-JAN-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131926E+11 | 194261.55 | 02-FEB-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.758117E+10 | 196172.18 | 02-MAR-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.817977E+09 | 170234.63 | 11-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6099992.35 | 3795.12 | 25-SEP-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.589895E+09 | 42343.37 | 25-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.952956E+10 | 184569.01 | 28-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245347E+11 | 195182.17 | 28-DEC-05:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.777777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.245347E+11 | 196172.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.149373E+11 | 164323.50 | 28-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.861175E+10 | 164807.01 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.569399E+10 | 165839.72 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.618832E+09 | 143180.19 | 11-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18984667.15 | 20690.97 | 02-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 71820803.63 | 18146.26 | 25-SEP-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139284E+10 | 59679.65 | 25-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.704167E+10 | 154465.76 | 28-NOV-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166898E+11 | 165706.37 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.550770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.166898E+11 | 165839.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.111397E+11 | 206847.84 | 28-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.706385E+10 | 207447.33 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.544045E+10 | 208731.84 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.853927E+09 | 180493.60 | 11-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7776790.16 | 4020.00 | 02-MAY-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.259242E+09 | 26719.04 | 25-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.464813E+10 | 194538.38 | 28-NOV-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121222E+11 | 208553.04 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.415352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121222E+11 | 208731.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.176353E+11 | 168469.49 | 28-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117934E+11 | 168967.53 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.685921E+10 | 170033.36 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.944845E+09 | 146645.60 | 11-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 46485201.38 | 12519.79 | 02-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 53620590.61 | 10116.50 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115447E+10 | 46050.62 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.831168E+10 | 158232.06 | 28-NOV-05:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189239E+11 | 169889.46 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.657229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.189239E+11 | 170033.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102931E+10 | 21072.89 | 27-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.663355E+09 | 21541.25 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.375316E+09 | 17135.84 | 02-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3702503.46 | 2554.48 | 12-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215499E+09 | 11992.83 | 17-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165661E+10 | 21151.52 | 27-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.394380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.165661E+10 | 21541.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.414213E+10 | 107342.38 | 28-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.213120E+10 | 107114.16 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.877115E+09 | 107821.36 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.228475E+10 | 100537.93 | 28-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.509107E+10 | 107722.79 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.509107E+10 | 107821.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.604787E+10 | 26414.48 | 28-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.424966E+10 | 26504.04 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.292590E+10 | 26526.34 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.636305E+09 | 22432.49 | 13-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 47875171.49 | 6735.78 | 02-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 92523106.73 | 9060.42 | 25-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.789094E+09 | 21571.44 | 26-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.372121E+10 | 24892.77 | 28-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.706078E+10 | 26616.73 | 28-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.255712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.706078E+10 | 26616.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.335255E+10 | 19378.15 | 28-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.215805E+10 | 19444.26 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152841E+10 | 19506.19 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.277354E+09 | 16437.32 | 13-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24096445.71 | 5252.04 | 02-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1843106.68 | 1663.82 | 17-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45428764.05 | 5553.09 | 25-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.532629E+09 | 15302.48 | 25-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.204309E+10 | 18251.63 | 28-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.392193E+10 | 19527.88 | 22-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.392193E+10 | 19527.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.331626E+10 | 26348.72 | 28-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246235E+10 | 26438.09 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.205253E+10 | 26521.86 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.556750E+09 | 22374.75 | 13-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 69886815.81 | 6497.80 | 02-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 57933966.64 | 3689.06 | 25-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.513603E+09 | 20843.55 | 25-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.205128E+10 | 24829.81 | 28-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.377363E+10 | 26552.29 | 22-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.377363E+10 | 26552.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.372105E+10 | 20861.22 | 28-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272445E+10 | 21005.31 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190257E+10 | 21072.99 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.466378E+09 | 17734.40 | 13-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 69752058.53 | 3783.13 | 02-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2689746.34 | 1343.60 | 17-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76755301.18 | 4232.40 | 25-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587673E+09 | 16508.10 | 25-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.222291E+10 | 19707.67 | 28-NOV-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.405177E+10 | 21098.53 | 22-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.405177E+10 | 21098.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.403224E+10 | 0.403224E+10 | 59766.50 | 03-JAN-15:00 | 59766.50 | 0.00 |
February | 0.00 | 0.00 | 0.128698E+11 | 0.128698E+11 | 87770.90 | 21-FEB-16:00 | 87770.90 | 0.00 |
March | 0.00 | 0.00 | 0.313112E+11 | 0.313112E+11 | 110578.98 | 21-MAR-16:00 | 110578.98 | 0.00 |
April | 0.00 | 0.00 | 0.848202E+11 | 0.848202E+11 | 146957.86 | 21-APR-14:40 | 146957.86 | 0.04 |
May | 0.00 | 0.00 | 0.123886E+12 | 0.123643E+12 | 199704.97 | 30-MAY-05:02 | 199704.97 | 0.21 |
June | 0.00 | 0.00 | 0.165922E+12 | 0.165271E+12 | 193561.83 | 08-JUN-05:02 | 193561.83 | 0.41 |
July | 0.00 | 0.00 | 0.196232E+12 | 0.170801E+12 | 280273.44 | 21-JUL-04:11 | 84798.00 | 0.76 |
August | 0.00 | 0.00 | 0.182827E+12 | 0.172169E+12 | 256458.69 | 03-AUG-04:11 | 122037.02 | 0.75 |
September | 0.00 | 0.00 | 0.131844E+12 | 0.123833E+12 | 256603.97 | 14-SEP-04:11 | 101936.75 | 0.52 |
October | 0.00 | 0.00 | 0.754054E+11 | 0.731941E+11 | 185840.62 | 02-OCT-03:01 | 185840.62 | 0.24 |
November | 0.00 | 0.00 | 0.221262E+11 | 0.221262E+11 | 113727.32 | 03-NOV-16:00 | 113727.32 | 0.02 |
December | 0.00 | 0.00 | 0.186669E+10 | 0.186669E+10 | 34724.69 | 20-DEC-15:00 | 34724.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.103314E+13 | 0.985939E+12 | 0.25 | |||
Minimum of Months | 0.00 | 0.00 | 0.186669E+10 | 0.186669E+10 | 34724.69 | 34724.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.196232E+12 | 0.172169E+12 | 280273.44 | 199704.97 | 0.76 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.544641E+11 | 0.544641E+11 | 747832.77 | 12-JAN-15:02 | 747832.77 | 0.00 |
February | 0.00 | 0.00 | 0.130404E+12 | 0.130404E+12 | 749130.15 | 23-FEB-13:03 | 749130.15 | 0.00 |
March | 0.00 | 0.00 | 0.269586E+12 | 0.269586E+12 | 941940.50 | 21-MAR-16:00 | 941940.50 | 0.00 |
April | 0.00 | 0.00 | 0.654115E+12 | 0.654115E+12 | 1321986.21 | 21-APR-14:05 | 1321986.21 | 0.04 |
May | 0.00 | 0.00 | 0.110295E+13 | 0.110085E+13 | 1668203.11 | 30-MAY-05:02 | 1668203.11 | 0.20 |
June | 0.00 | 0.00 | 0.143538E+13 | 0.143009E+13 | 1879633.03 | 17-JUN-05:02 | 1879633.03 | 0.38 |
July | 0.00 | 0.00 | 0.156943E+13 | 0.136993E+13 | 3078343.01 | 22-JUL-05:03 | 1032299.97 | 0.64 |
August | 0.00 | 0.00 | 0.140775E+13 | 0.132942E+13 | 2990593.99 | 03-AUG-05:03 | 1348342.48 | 0.62 |
September | 0.00 | 0.00 | 0.115109E+13 | 0.108012E+13 | 2375172.07 | 22-SEP-05:03 | 869339.57 | 0.50 |
October | 0.00 | 0.00 | 0.644753E+12 | 0.624715E+12 | 1478655.95 | 04-OCT-05:02 | 722796.60 | 0.23 |
November | 0.00 | 0.00 | 0.207418E+12 | 0.207418E+12 | 969696.73 | 03-NOV-16:00 | 969696.73 | 0.02 |
December | 0.00 | 0.00 | 0.320775E+11 | 0.320775E+11 | 629399.36 | 15-DEC-15:02 | 629399.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.865941E+13 | 0.828319E+13 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 0.320775E+11 | 0.320775E+11 | 629399.36 | 629399.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.156943E+13 | 0.143009E+13 | 3078343.01 | 1879633.03 | 0.64 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.267709E+10 | 0.267709E+10 | 41700.13 | 12-JAN-15:00 | 41700.13 | 0.00 |
February | 0.00 | 0.00 | 0.104119E+11 | 0.104119E+11 | 79489.25 | 20-FEB-15:01 | 79489.25 | 0.00 |
March | 0.00 | 0.00 | 0.264970E+11 | 0.264970E+11 | 116581.68 | 14-MAR-15:30 | 116581.68 | 0.00 |
April | 0.00 | 0.00 | 0.785961E+11 | 0.785961E+11 | 170457.50 | 21-APR-14:30 | 170457.50 | 0.04 |
May | 0.00 | 0.00 | 0.136459E+12 | 0.136274E+12 | 194298.73 | 29-MAY-16:41 | 194298.73 | 0.20 |
June | 0.00 | 0.00 | 0.180645E+12 | 0.180184E+12 | 215764.04 | 18-JUN-14:21 | 215764.04 | 0.39 |
July | 0.00 | 0.00 | 0.193040E+12 | 0.172783E+12 | 334515.99 | 21-JUL-05:03 | 106362.69 | 0.64 |
August | 0.00 | 0.00 | 0.170657E+12 | 0.163094E+12 | 309740.16 | 03-AUG-05:03 | 139504.31 | 0.62 |
September | 0.00 | 0.00 | 0.136465E+12 | 0.129983E+12 | 260773.88 | 22-SEP-04:11 | 95267.70 | 0.50 |
October | 0.00 | 0.00 | 0.703328E+11 | 0.688050E+11 | 186313.76 | 03-OCT-13:30 | 164151.76 | 0.22 |
November | 0.00 | 0.00 | 0.164537E+11 | 0.164537E+11 | 110718.55 | 03-NOV-16:00 | 110718.55 | 0.02 |
December | 0.00 | 0.00 | 0.107523E+10 | 0.107523E+10 | 21054.31 | 23-DEC-15:00 | 21054.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.102331E+13 | 0.986833E+12 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 0.107523E+10 | 0.107523E+10 | 21054.31 | 21054.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.193040E+12 | 0.180184E+12 | 334515.99 | 215764.04 | 0.64 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.169720E+11 | 0.169668E+11 | 90654.05 | 07-JAN-06:02 | 90654.05 | 0.00 |
February | 0.00 | 0.00 | 0.158569E+11 | 0.155684E+11 | 85840.12 | 13-FEB-18:11 | 69998.81 | 0.01 |
March | 0.00 | 0.00 | 0.254138E+11 | 0.253881E+11 | 141304.59 | 03-MAR-05:52 | 141304.59 | 0.00 |
April | 0.00 | 0.00 | 0.434536E+11 | 0.434522E+11 | 95321.70 | 20-APR-05:03 | 95321.70 | 0.03 |
May | 0.00 | 0.00 | 0.673026E+11 | 0.657574E+11 | 149964.60 | 31-MAY-05:02 | 149964.60 | 0.17 |
June | 0.00 | 0.00 | 0.829149E+11 | 0.799914E+11 | 156751.35 | 07-JUN-05:02 | 156751.35 | 0.32 |
July | 0.00 | 0.00 | 0.105106E+12 | 0.803881E+11 | 232908.25 | 21-JUL-04:53 | 73791.69 | 0.56 |
August | 0.00 | 0.00 | 0.102266E+12 | 0.853109E+11 | 201864.66 | 03-AUG-05:03 | 92179.81 | 0.58 |
September | 0.00 | 0.00 | 0.845023E+11 | 0.716629E+11 | 169786.88 | 14-SEP-04:11 | 67546.41 | 0.50 |
October | 0.00 | 0.00 | 0.545218E+11 | 0.494492E+11 | 172598.87 | 15-OCT-22:13 | 110265.80 | 0.24 |
November | 0.00 | 0.00 | 0.238444E+11 | 0.238174E+11 | 142089.26 | 12-NOV-18:22 | 142089.26 | 0.03 |
December | 0.00 | 0.00 | 0.128791E+11 | 0.128791E+11 | 140542.13 | 05-DEC-04:43 | 140542.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.635034E+12 | 0.570632E+12 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 0.128791E+11 | 0.128791E+11 | 85840.12 | 67546.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.105106E+12 | 0.853109E+11 | 232908.25 | 156751.35 | 0.58 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 5273208.60 | 5273208.60 | 134.58 | 10-JAN-17:42 | 134.58 | 0.06 |
February | 0.00 | 0.00 | 0.201627E+12 | 0.201158E+12 | 435610.10 | 23-FEB-15:03 | 435610.10 | 0.02 |
March | 0.00 | 0.00 | 0.299642E+12 | 0.299573E+12 | 391604.65 | 18-MAR-19:32 | 391604.65 | 0.01 |
April | 0.00 | 0.00 | 0.485843E+12 | 0.485843E+12 | 398384.60 | 21-APR-15:00 | 398384.60 | 0.21 |
May | 0.00 | 0.00 | 0.147470E+12 | 0.147470E+12 | 187560.29 | 31-MAY-24:00 | 187560.29 | 0.47 |
June | 0.00 | 0.00 | 0.443702E+12 | 0.438291E+12 | 550350.56 | 29-JUN-09:15 | 338483.54 | 0.79 |
July | 0.00 | 0.00 | 0.713354E+12 | 0.674321E+12 | 527390.82 | 21-JUL-09:50 | 214478.73 | 1.00 |
August | 0.00 | 0.00 | 0.866350E+12 | 0.853612E+12 | 510079.79 | 02-AUG-08:00 | 395652.91 | 0.96 |
September | 0.00 | 0.00 | 0.133421E+12 | 0.133421E+12 | 314663.65 | 30-SEP-23:51 | 314663.65 | 0.68 |
October | 0.00 | 0.00 | 0.293563E+12 | 0.273882E+12 | 605515.29 | 03-OCT-21:22 | 294694.93 | 0.38 |
November | 0.00 | 0.00 | 0.274918E+12 | 0.274911E+12 | 411870.77 | 13-NOV-15:12 | 411870.77 | 0.05 |
December | 0.00 | 0.00 | 0.282735E+12 | 0.282735E+12 | 367516.01 | 07-DEC-14:47 | 367516.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.414263E+13 | 0.406522E+13 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 5273208.60 | 5273208.60 | 134.58 | 134.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.866350E+12 | 0.853612E+12 | 605515.29 | 435610.10 | 1.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.695588E+10 | 0.695588E+10 | 3560.09 | 30-JAN-16:57 | 3560.09 | 0.00 |
February | 0.00 | 0.00 | 0.108346E+11 | 0.108322E+11 | 5506.73 | 21-FEB-17:00 | 5506.73 | 0.00 |
March | 0.00 | 0.00 | 0.175310E+11 | 0.175310E+11 | 8407.22 | 31-MAR-23:52 | 8407.22 | 0.00 |
April | 0.00 | 0.00 | 0.226041E+11 | 0.226024E+11 | 9564.91 | 30-APR-18:04 | 9564.91 | 0.00 |
May | 0.00 | 0.00 | 0.855433E+10 | 0.853294E+10 | 4929.04 | 31-MAY-24:00 | 4929.04 | 0.00 |
June | 0.00 | 0.00 | 0.133781E+11 | 0.133309E+11 | 6767.77 | 30-JUN-23:20 | 6767.77 | 0.00 |
July | 0.00 | 0.00 | 0.190004E+11 | 0.187694E+11 | 8739.93 | 31-JUL-23:02 | 8615.30 | 0.00 |
August | 0.00 | 0.00 | 0.239745E+11 | 0.237814E+11 | 9745.39 | 08-AUG-16:00 | 9470.03 | 0.00 |
September | 0.00 | 0.00 | 0.842988E+10 | 0.831096E+10 | 4838.59 | 30-SEP-23:51 | 4838.59 | 0.00 |
October | 0.00 | 0.00 | 0.131607E+11 | 0.130911E+11 | 6540.49 | 31-OCT-23:52 | 6540.49 | 0.00 |
November | 0.00 | 0.00 | 0.169243E+11 | 0.169162E+11 | 7632.11 | 09-NOV-16:50 | 7632.11 | 0.00 |
December | 0.00 | 0.00 | 0.221794E+11 | 0.221794E+11 | 9183.29 | 15-DEC-16:35 | 9183.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.183527E+12 | 0.182834E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.695588E+10 | 0.695588E+10 | 3560.09 | 3560.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.239745E+11 | 0.237814E+11 | 9745.39 | 9564.91 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.528745E+11 | 0.528745E+11 | 32432.15 | 30-JAN-16:57 | 32432.15 | 0.00 |
February | 0.00 | 0.00 | 0.964481E+11 | 0.964246E+11 | 52089.85 | 21-FEB-17:00 | 52089.85 | 0.00 |
March | 0.00 | 0.00 | 0.161697E+12 | 0.161697E+12 | 78669.80 | 31-MAR-23:33 | 78669.80 | 0.00 |
April | 0.00 | 0.00 | 0.211976E+12 | 0.211959E+12 | 90190.26 | 30-APR-17:57 | 90190.26 | 0.00 |
May | 0.00 | 0.00 | 0.784416E+11 | 0.782281E+11 | 47493.63 | 31-MAY-24:00 | 47493.63 | 0.00 |
June | 0.00 | 0.00 | 0.126852E+12 | 0.126380E+12 | 65789.22 | 30-JUN-24:00 | 65789.22 | 0.00 |
July | 0.00 | 0.00 | 0.180742E+12 | 0.178438E+12 | 84567.16 | 31-JUL-23:02 | 83285.86 | 0.00 |
August | 0.00 | 0.00 | 0.228001E+12 | 0.226076E+12 | 92883.02 | 08-AUG-16:00 | 90157.99 | 0.00 |
September | 0.00 | 0.00 | 0.766399E+11 | 0.754618E+11 | 44687.98 | 30-SEP-23:23 | 44687.98 | 0.00 |
October | 0.00 | 0.00 | 0.120588E+12 | 0.119896E+12 | 60370.55 | 31-OCT-23:42 | 60370.55 | 0.00 |
November | 0.00 | 0.00 | 0.153318E+12 | 0.153237E+12 | 72441.94 | 09-NOV-16:50 | 72441.94 | 0.00 |
December | 0.00 | 0.00 | 0.199538E+12 | 0.199538E+12 | 87078.87 | 15-DEC-16:45 | 87078.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.168712E+13 | 0.168021E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.528745E+11 | 0.528745E+11 | 32432.15 | 32432.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.228001E+12 | 0.226076E+12 | 92883.02 | 90190.26 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.349352E+10 | 0.349352E+10 | 3269.59 | 12-JAN-16:40 | 3269.59 | 0.00 |
February | 0.00 | 0.00 | 0.835033E+10 | 0.834805E+10 | 5317.25 | 21-FEB-17:00 | 5317.25 | 0.00 |
March | 0.00 | 0.00 | 0.152063E+11 | 0.152063E+11 | 7437.32 | 31-MAR-23:10 | 7437.32 | 0.00 |
April | 0.00 | 0.00 | 0.209444E+11 | 0.209427E+11 | 9432.29 | 30-APR-17:53 | 9432.29 | 0.00 |
May | 0.00 | 0.00 | 0.790913E+10 | 0.788785E+10 | 4827.41 | 31-MAY-24:00 | 4827.41 | 0.00 |
June | 0.00 | 0.00 | 0.129857E+11 | 0.129386E+11 | 6617.18 | 30-JUN-24:00 | 6617.18 | 0.00 |
July | 0.00 | 0.00 | 0.184202E+11 | 0.181902E+11 | 8500.91 | 31-JUL-23:02 | 8390.50 | 0.00 |
August | 0.00 | 0.00 | 0.230416E+11 | 0.228506E+11 | 9650.54 | 06-AUG-18:06 | 9650.54 | 0.00 |
September | 0.00 | 0.00 | 0.765781E+10 | 0.753964E+10 | 4175.23 | 30-SEP-23:03 | 4175.23 | 0.00 |
October | 0.00 | 0.00 | 0.115328E+11 | 0.114637E+11 | 5834.83 | 05-OCT-17:00 | 5714.29 | 0.00 |
November | 0.00 | 0.00 | 0.138832E+11 | 0.138751E+11 | 7390.43 | 09-NOV-16:50 | 7390.43 | 0.00 |
December | 0.00 | 0.00 | 0.179345E+11 | 0.179345E+11 | 8709.65 | 15-DEC-16:45 | 8709.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.161360E+12 | 0.160671E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.349352E+10 | 0.349352E+10 | 3269.59 | 3269.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.230416E+11 | 0.228506E+11 | 9650.54 | 9650.54 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 34000.25 | 1873500.58 | 23-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 23951.28 | 2061744.01 | 03-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 13516.75 | 1941985.13 | 02-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:05 | 2000.66 | 1414546.54 | 11-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 104.01 | 48536.20 | 02-MAY-05:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 1.57 | 2984.37 | 17-AUG-05:10 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 156.60 | 37205.63 | 25-SEP-05:05 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 2170.09 | 312738.48 | 25-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 16358.72 | 1858677.83 | 17-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 39192.89 | 1900851.03 | 05-DEC-05:01 |
Annual Sum or Average | 0.00 | 10916.90 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 39192.89 | 2061744.01 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 31465.45 | 970531.42 | 03-JAN-13:05 | 247781.55 | 852986.08 | 22-JAN-13:00 |
February | 158050.03 | 1297900.76 | 20-FEB-18:13 | 72759.05 | 715206.77 | 24-FEB-02:12 |
March | 253376.62 | 2308285.46 | 22-MAR-14:05 | 26498.24 | 735509.48 | 11-MAR-14:51 |
April | 544819.19 | 2345430.12 | 03-APR-13:05 | 6894.94 | 597531.41 | 30-APR-23:33 |
May | 623126.11 | 2332148.38 | 19-MAY-12:05 | 89391.57 | 852979.52 | 07-MAY-07:00 |
June | 932124.12 | 2831862.95 | 01-JUN-04:13 | 5896.18 | 807105.67 | 11-JUN-03:21 |
July | 1079532.79 | 4143744.83 | 21-JUL-09:50 | 1651.43 | 318852.55 | 18-JUL-21:08 |
August | 1061125.92 | 3969979.59 | 03-AUG-05:03 | 593.44 | 224575.79 | 17-AUG-04:47 |
September | 665767.23 | 2476013.22 | 13-SEP-04:14 | 77109.63 | 852973.50 | 23-SEP-23:40 |
October | 442593.83 | 2390506.39 | 04-OCT-10:05 | 53241.76 | 811075.54 | 21-OCT-22:51 |
November | 218992.45 | 1752054.21 | 03-NOV-16:00 | 32125.79 | 815733.00 | 10-NOV-02:31 |
December | 132627.93 | 1228174.56 | 01-DEC-12:34 | 9566.87 | 373023.80 | 14-DEC-13:30 |
Annual Sum or Average | 514015.89 | 52023.34 | ||||
Minimum of Months | 31465.45 | 970531.42 | 593.44 | 224575.79 | ||
Maximum of Months | 1079532.79 | 4143744.83 | 247781.55 | 852986.08 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 36411.04 | 880704.47 | 12-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 186583.79 | 1524970.15 | 07-FEB-13:05 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 299490.27 | 1733293.84 | 22-MAR-14:05 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 587361.86 | 2093971.69 | 21-APR-14:05 | 0.00 | 0.00 | 01-APR-00:05 |
May | 628442.89 | 3077943.95 | 09-MAY-04:11 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 941870.51 | 3972739.93 | 19-JUN-04:12 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1092923.23 | 5772366.79 | 21-JUL-04:11 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1081896.82 | 5669613.64 | 03-AUG-04:11 | 0.00 | 0.00 | 01-AUG-00:02 |
September | 672831.02 | 4778707.48 | 22-SEP-04:11 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 472460.46 | 3766472.56 | 05-OCT-04:11 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 283810.46 | 1777354.56 | 06-NOV-15:01 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 232209.44 | 1372548.68 | 07-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 545094.30 | 0.00 | ||||
Minimum of Months | 36411.04 | 880704.47 | 0.00 | 0.00 | ||
Maximum of Months | 1092923.23 | 5772366.79 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 13237.19 | 47157.61 | 30-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 13307.39 | 47153.23 | 01-FEB-12:58 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 13630.64 | 46272.54 | 01-MAR-12:19 |
April | 0.00 | 0.00 | 01-APR-00:05 | 11934.72 | 43577.36 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 11347.92 | 40486.57 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 10721.92 | 37095.98 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 9387.16 | 34593.00 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 10294.88 | 34731.23 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 10145.34 | 37044.59 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10968.61 | 40542.79 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 12093.69 | 43827.70 | 30-NOV-12:36 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 12451.77 | 46183.70 | 29-DEC-12:23 |
Annual Sum or Average | 0.00 | 11617.37 | ||||
Minimum of Months | 0.00 | 0.00 | 9387.16 | 34593.00 | ||
Maximum of Months | 0.00 | 0.00 | 13630.64 | 47157.61 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 31073.87 | 1072159.03 | 12-JAN-15:02 | 3040.77 | 177904.98 | 07-JAN-04:33 |
February | 195584.11 | 1241811.69 | 07-FEB-13:42 | 172.16 | 83547.62 | 01-FEB-11:40 |
March | 293578.56 | 3215658.43 | 22-MAR-14:05 | 1229.47 | 86294.10 | 15-MAR-22:10 |
April | 683631.53 | 3422872.18 | 21-APR-15:10 | 1355.00 | 108045.19 | 13-APR-22:20 |
May | 766827.39 | 3386191.26 | 18-MAY-13:50 | 901.46 | 101662.51 | 02-MAY-23:20 |
June | 1255512.85 | 3448454.05 | 06-JUN-14:50 | 14.99 | 20445.50 | 14-JUN-02:70 |
July | 1816008.82 | 7289722.02 | 21-JUL-09:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1540013.67 | 5443524.35 | 02-AUG-07:50 | 5.47 | 7126.67 | 17-AUG-01:10 |
September | 934598.52 | 3842249.83 | 22-SEP-09:05 | 213.12 | 78798.08 | 19-SEP-02:70 |
October | 567356.71 | 3726109.33 | 03-OCT-14:00 | 32.85 | 40146.29 | 07-OCT-11:30 |
November | 238665.19 | 2101281.56 | 03-NOV-16:00 | 2110.53 | 73956.97 | 27-NOV-06:50 |
December | 79453.24 | 1255107.69 | 07-DEC-15:04 | 4497.14 | 151306.11 | 19-DEC-01:11 |
Annual Sum or Average | 703485.69 | 1141.24 | ||||
Minimum of Months | 31073.87 | 1072159.03 | 0.00 | 0.00 | ||
Maximum of Months | 1816008.82 | 7289722.02 | 4497.14 | 177904.98 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.107322E+11 | 0.61 | 22153.82 | 05-JAN-06:01 | 1.82 |
February | 0.102458E+11 | 0.64 | 22153.82 | 01-FEB-06:01 | 1.81 |
March | 0.137608E+11 | 0.73 | 22153.82 | 02-MAR-06:01 | 1.82 |
April | 0.168032E+11 | 0.82 | 23495.23 | 05-APR-04:11 | 1.86 |
May | 0.173888E+11 | 0.81 | 28513.54 | 30-MAY-05:02 | 2.00 |
June | 0.205317E+11 | 0.93 | 29894.06 | 05-JUN-04:11 | 2.04 |
July | 0.208363E+11 | 0.95 | 29894.06 | 10-JUL-05:02 | 2.03 |
August | 0.229247E+11 | 1.01 | 29894.06 | 05-AUG-05:02 | 2.04 |
September | 0.172077E+11 | 0.80 | 29894.06 | 13-SEP-04:11 | 2.03 |
October | 0.150822E+11 | 0.73 | 28493.61 | 05-OCT-04:11 | 1.99 |
November | 0.126767E+11 | 0.68 | 22153.82 | 28-NOV-06:01 | 1.81 |
December | 0.116646E+11 | 0.63 | 22153.82 | 05-DEC-06:01 | 1.81 |
Annual Sum or Average | 0.189855E+12 | 0.78 | |||
Minimum of Months | 0.102458E+11 | 0.61 | 22153.82 | 1.81 | |
Maximum of Months | 0.229247E+11 | 1.01 | 29894.06 | 2.04 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.844537E+11 | 0.58 | 226942.33 | 13-JAN-06:01 | 1.89 |
February | 0.836965E+11 | 0.61 | 226942.33 | 11-FEB-06:01 | 1.90 |
March | 0.107813E+12 | 0.67 | 224685.16 | 25-MAR-05:01 | 1.89 |
April | 0.121839E+12 | 0.71 | 226942.33 | 11-APR-05:01 | 1.90 |
May | 0.152077E+12 | 0.78 | 243823.92 | 30-MAY-05:02 | 1.94 |
June | 0.176387E+12 | 0.86 | 278015.81 | 10-JUN-05:02 | 2.06 |
July | 0.163799E+12 | 0.81 | 278015.81 | 07-JUL-05:02 | 2.04 |
August | 0.170663E+12 | 0.83 | 278015.81 | 05-AUG-05:02 | 2.04 |
September | 0.144193E+12 | 0.75 | 241521.03 | 13-SEP-04:11 | 1.92 |
October | 0.118567E+12 | 0.68 | 185527.74 | 03-OCT-15:30 | 1.72 |
November | 0.936394E+11 | 0.62 | 226942.33 | 17-NOV-06:01 | 1.90 |
December | 0.831526E+11 | 0.57 | 226942.33 | 13-DEC-06:01 | 1.89 |
Annual Sum or Average | 0.150028E+13 | 0.71 | |||
Minimum of Months | 0.831526E+11 | 0.57 | 185527.74 | 1.72 | |
Maximum of Months | 0.176387E+12 | 0.86 | 278015.81 | 2.06 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.804786E+10 | 0.52 | 11523.89 | 02-JAN-05:11 | 1.27 |
February | 0.766868E+10 | 0.54 | 11523.89 | 02-FEB-06:01 | 1.28 |
March | 0.974614E+10 | 0.58 | 15918.95 | 16-MAR-15:30 | 1.46 |
April | 0.117707E+11 | 0.62 | 20897.13 | 21-APR-14:40 | 1.63 |
May | 0.156505E+11 | 0.70 | 24359.38 | 30-MAY-05:02 | 1.73 |
June | 0.193171E+11 | 0.80 | 28910.16 | 17-JUN-03:01 | 1.87 |
July | 0.178770E+11 | 0.75 | 32601.75 | 26-JUL-03:01 | 1.95 |
August | 0.178873E+11 | 0.76 | 29187.34 | 05-AUG-05:02 | 1.86 |
September | 0.146174E+11 | 0.67 | 22709.38 | 20-SEP-14:50 | 1.67 |
October | 0.112676E+11 | 0.58 | 21707.18 | 05-OCT-15:50 | 1.64 |
November | 0.877328E+10 | 0.55 | 14365.23 | 09-NOV-15:30 | 1.39 |
December | 0.835287E+10 | 0.55 | 11523.89 | 27-DEC-06:01 | 1.27 |
Annual Sum or Average | 0.150976E+12 | 0.64 | |||
Minimum of Months | 0.766868E+10 | 0.52 | 11523.89 | 1.27 | |
Maximum of Months | 0.193171E+11 | 0.80 | 32601.75 | 1.95 |
Report: FanReportMonthly
For: CAV_BAS SZVAV FAN
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.908462E+10 | 0.64 | 18328.15 | 02-JAN-05:11 | 2.07 |
February | 0.768927E+10 | 0.63 | 18328.15 | 01-FEB-05:01 | 2.08 |
March | 0.885959E+10 | 0.67 | 18328.15 | 01-MAR-05:01 | 2.08 |
April | 0.845404E+10 | 0.66 | 18328.15 | 01-APR-05:01 | 2.08 |
May | 0.732558E+10 | 0.64 | 18328.15 | 01-MAY-04:11 | 2.08 |
June | 0.690683E+10 | 0.65 | 18328.15 | 01-JUN-04:11 | 2.08 |
July | 0.754646E+10 | 0.65 | 18328.15 | 01-JUL-05:02 | 2.07 |
August | 0.923937E+10 | 0.75 | 18328.15 | 01-AUG-03:01 | 2.06 |
September | 0.937648E+10 | 0.74 | 18328.15 | 01-SEP-04:11 | 2.05 |
October | 0.111744E+11 | 0.75 | 18328.15 | 02-OCT-03:01 | 2.07 |
November | 0.120210E+11 | 0.75 | 18328.15 | 01-NOV-04:11 | 2.06 |
December | 0.104340E+11 | 0.68 | 18328.15 | 01-DEC-05:11 | 2.08 |
Annual Sum or Average | 0.108112E+12 | 0.68 | |||
Minimum of Months | 0.690683E+10 | 0.63 | 18328.15 | 2.05 | |
Maximum of Months | 0.120210E+11 | 0.75 | 18328.15 | 2.08 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SYS11 FAN
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.301887E+11 | 0.58 | 11271.15 | 01-JAN-00:05 | 0.58 |
February | 0.477753E+11 | 0.71 | 37539.83 | 01-FEB-00:03 | 0.97 |
March | 0.716927E+11 | 0.82 | 37539.83 | 01-MAR-00:02 | 0.98 |
April | 0.894029E+11 | 0.94 | 37539.83 | 01-APR-00:05 | 0.98 |
May | 0.301887E+11 | 0.58 | 11271.15 | 01-MAY-00:03 | 0.59 |
June | 0.312893E+11 | 0.59 | 37539.83 | 01-JUN-04:11 | 0.98 |
July | 0.550099E+11 | 0.73 | 37539.83 | 02-JUL-04:21 | 0.96 |
August | 0.842714E+11 | 0.89 | 37539.83 | 01-AUG-03:22 | 0.96 |
September | 0.292451E+11 | 0.58 | 37539.83 | 30-SEP-23:03 | 0.97 |
October | 0.465878E+11 | 0.67 | 37539.83 | 01-OCT-00:03 | 0.97 |
November | 0.685066E+11 | 0.81 | 37539.83 | 01-NOV-00:01 | 0.97 |
December | 0.959422E+11 | 0.95 | 37539.83 | 01-DEC-00:05 | 0.97 |
Annual Sum or Average | 0.680101E+12 | 0.74 | |||
Minimum of Months | 0.292451E+11 | 0.58 | 11271.15 | 0.58 | |
Maximum of Months | 0.959422E+11 | 0.95 | 37539.83 | 0.98 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.377204E+10 | 1.62 | 1408.32 | 01-JAN-01:10 | 1.61 |
February | 0.340701E+10 | 1.63 | 1408.32 | 01-FEB-00:03 | 1.63 |
March | 0.377204E+10 | 1.62 | 1408.32 | 01-MAR-00:05 | 1.62 |
April | 0.365037E+10 | 1.62 | 1408.32 | 01-APR-00:12 | 1.63 |
May | 0.377204E+10 | 1.62 | 1408.32 | 01-MAY-01:03 | 1.62 |
June | 0.365037E+10 | 1.62 | 1408.32 | 01-JUN-03:10 | 1.62 |
July | 0.377204E+10 | 1.61 | 1408.32 | 01-JUL-00:20 | 1.61 |
August | 0.377204E+10 | 1.61 | 1408.32 | 01-AUG-00:55 | 1.61 |
September | 0.365037E+10 | 1.61 | 1408.32 | 01-SEP-00:37 | 1.61 |
October | 0.377204E+10 | 1.62 | 1408.32 | 01-OCT-00:43 | 1.62 |
November | 0.365037E+10 | 1.62 | 1408.32 | 01-NOV-01:11 | 1.63 |
December | 0.377204E+10 | 1.63 | 1408.32 | 01-DEC-00:47 | 1.62 |
Annual Sum or Average | 0.444128E+11 | 1.62 | |||
Minimum of Months | 0.340701E+10 | 1.61 | 1408.32 | 1.61 | |
Maximum of Months | 0.377204E+10 | 1.63 | 1408.32 | 1.63 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.359482E+11 | 1.62 | 13421.53 | 01-JAN-00:10 | 1.61 |
February | 0.324694E+11 | 1.63 | 13421.53 | 01-FEB-00:03 | 1.63 |
March | 0.359482E+11 | 1.62 | 13421.53 | 01-MAR-00:27 | 1.62 |
April | 0.347886E+11 | 1.62 | 13421.53 | 01-APR-00:23 | 1.63 |
May | 0.359482E+11 | 1.62 | 13421.53 | 01-MAY-00:10 | 1.62 |
June | 0.347886E+11 | 1.62 | 13421.53 | 01-JUN-00:20 | 1.62 |
July | 0.359482E+11 | 1.61 | 13421.53 | 25-JUL-20:10 | 1.61 |
August | 0.359482E+11 | 1.61 | 13421.53 | 01-AUG-00:02 | 1.61 |
September | 0.347886E+11 | 1.61 | 13421.53 | 01-SEP-00:42 | 1.61 |
October | 0.359482E+11 | 1.62 | 13421.53 | 01-OCT-00:02 | 1.62 |
November | 0.347886E+11 | 1.62 | 13421.53 | 01-NOV-01:32 | 1.63 |
December | 0.359482E+11 | 1.63 | 13421.53 | 18-DEC-07:48 | 1.63 |
Annual Sum or Average | 0.423261E+12 | 1.62 | |||
Minimum of Months | 0.324694E+11 | 1.61 | 13421.53 | 1.61 | |
Maximum of Months | 0.359482E+11 | 1.63 | 13421.53 | 1.63 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.376272E+10 | 1.62 | 1404.84 | 01-JAN-03:30 | 1.61 |
February | 0.339859E+10 | 1.63 | 1404.84 | 01-FEB-05:16 | 1.63 |
March | 0.376272E+10 | 1.62 | 1404.84 | 01-MAR-04:02 | 1.62 |
April | 0.364134E+10 | 1.62 | 1404.84 | 01-APR-05:03 | 1.63 |
May | 0.376272E+10 | 1.62 | 1404.84 | 01-MAY-00:40 | 1.62 |
June | 0.364134E+10 | 1.62 | 1404.84 | 01-JUN-02:70 | 1.62 |
July | 0.376272E+10 | 1.61 | 1404.84 | 01-JUL-05:02 | 1.61 |
August | 0.376272E+10 | 1.61 | 1404.84 | 01-AUG-02:24 | 1.61 |
September | 0.364134E+10 | 1.61 | 1404.84 | 01-SEP-00:34 | 1.61 |
October | 0.376272E+10 | 1.62 | 1404.84 | 01-OCT-11:44 | 1.62 |
November | 0.364134E+10 | 1.62 | 1404.84 | 01-NOV-01:52 | 1.63 |
December | 0.376272E+10 | 1.63 | 1404.84 | 01-DEC-11:35 | 1.62 |
Annual Sum or Average | 0.443030E+11 | 1.62 | |||
Minimum of Months | 0.339859E+10 | 1.61 | 1404.84 | 1.61 | |
Maximum of Months | 0.376272E+10 | 1.63 | 1404.84 | 1.63 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 97428440.17 | 87685596.15 | 2309.96 | 05-JAN-06:01 | 2078.97 | 2078.97 | 46.41 | 11.87 |
February | 59731520.97 | 53758368.87 | 2307.65 | 10-FEB-06:01 | 2076.88 | 2076.88 | 44.58 | 11.87 |
March | 36667648.49 | 33000883.64 | 2259.72 | 02-MAR-06:01 | 2033.75 | 2033.75 | 44.33 | 11.70 |
April | 5165721.29 | 4649149.16 | 1848.20 | 11-APR-05:01 | 1663.38 | 1663.38 | 37.37 | 10.16 |
May | 262058.40 | 235852.56 | 45.73 | 02-MAY-05:08 | 41.16 | 41.16 | 22.10 | 0.27 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 21.17 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 21.17 | 0.00 |
August | 3912.04 | 3520.84 | 2.78 | 17-AUG-05:10 | 2.50 | 2.50 | 21.17 | 0.02 |
September | 376791.81 | 339112.63 | 33.78 | 25-SEP-05:05 | 30.40 | 30.40 | 21.21 | 0.20 |
October | 5581188.94 | 5023070.04 | 294.71 | 25-OCT-05:01 | 265.24 | 265.24 | 26.08 | 1.77 |
November | 45525534.97 | 40972981.47 | 2306.75 | 28-NOV-06:01 | 2076.08 | 2076.08 | 44.27 | 11.87 |
December | 0.109635E+09 | 98671181.33 | 2314.79 | 26-DEC-06:01 | 2083.31 | 2083.31 | 47.99 | 11.88 |
Annual Sum or Average | 0.360377E+09 | 0.324340E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 0.00 | |
Maximum of Months | 0.109635E+09 | 98671181.33 | 2314.79 | 2083.31 | 2083.31 | 47.99 | 11.88 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.369534E+09 | 0.332580E+09 | 1999.60 | 12-JAN-13:10 | 1799.64 | 1799.64 | 8.81 | 17.84 |
February | 0.191158E+10 | 0.172042E+10 | 3716.36 | 03-FEB-14:21 | 3344.72 | 3344.72 | 9.14 | 33.01 |
March | 0.297729E+10 | 0.267956E+10 | 3922.87 | 16-MAR-05:02 | 3530.58 | 3530.58 | 8.99 | 34.73 |
April | 0.380593E+10 | 0.342534E+10 | 7846.85 | 28-APR-12:05 | 7062.17 | 7062.17 | 7.65 | 61.59 |
May | 0.359062E+10 | 0.323156E+10 | 8830.01 | 30-MAY-05:02 | 7947.01 | 7947.01 | 9.47 | 66.84 |
June | 0.573470E+10 | 0.516123E+10 | 19612.04 | 19-JUN-04:12 | 17650.84 | 17650.84 | 10.77 | 105.60 |
July | 0.677509E+10 | 0.609758E+10 | 22134.32 | 18-JUL-04:11 | 19920.89 | 19920.89 | 10.69 | 111.96 |
August | 0.722435E+10 | 0.650191E+10 | 23418.82 | 05-AUG-05:02 | 21076.94 | 21076.94 | 10.71 | 114.97 |
September | 0.430130E+10 | 0.387117E+10 | 18142.27 | 13-SEP-04:11 | 16328.04 | 16328.04 | 11.11 | 101.57 |
October | 0.360907E+10 | 0.324817E+10 | 17442.57 | 04-OCT-05:02 | 15698.31 | 15698.31 | 9.68 | 99.58 |
November | 0.302343E+10 | 0.272108E+10 | 5815.39 | 03-NOV-15:20 | 5233.85 | 5233.85 | 6.73 | 49.02 |
December | 0.267044E+10 | 0.240339E+10 | 3781.49 | 15-DEC-14:33 | 3403.34 | 3403.34 | 8.97 | 33.55 |
Annual Sum or Average | 0.459933E+11 | 0.413940E+11 | ||||||
Minimum of Months | 0.369534E+09 | 0.332580E+09 | 1999.60 | 1799.64 | 1799.64 | 6.73 | 17.84 | |
Maximum of Months | 0.722435E+10 | 0.650191E+10 | 23418.82 | 21076.94 | 21076.94 | 11.11 | 114.97 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.647218E+10 | 0.582496E+10 | 11113.86 | 01-JAN-01:40 | 10002.48 | 10002.48 | 7.54 | 58.42 |
February | 0.116251E+11 | 0.104625E+11 | 11113.86 | 01-FEB-00:03 | 10002.48 | 10002.48 | 7.02 | 58.42 |
March | 0.208952E+11 | 0.188056E+11 | 11113.86 | 01-MAR-00:04 | 10002.48 | 10002.48 | 8.06 | 58.42 |
April | 0.264589E+11 | 0.238130E+11 | 11113.86 | 01-APR-00:05 | 10002.48 | 10002.48 | 10.79 | 58.42 |
May | 0.225451E+11 | 0.202906E+11 | 11113.86 | 01-MAY-00:03 | 10002.48 | 10002.48 | 7.48 | 58.42 |
June | 0.274013E+11 | 0.246612E+11 | 11113.86 | 01-JUN-00:10 | 10002.48 | 10002.48 | 10.22 | 58.42 |
July | 0.292669E+11 | 0.263403E+11 | 11113.86 | 01-JUL-00:10 | 10002.48 | 10002.48 | 10.20 | 58.42 |
August | 0.295526E+11 | 0.265973E+11 | 11113.86 | 01-AUG-00:02 | 10002.48 | 10002.48 | 10.34 | 58.42 |
September | 0.205007E+11 | 0.184507E+11 | 11113.86 | 01-SEP-00:05 | 10002.48 | 10002.48 | 10.23 | 58.42 |
October | 0.194655E+11 | 0.175190E+11 | 11113.86 | 01-OCT-00:02 | 10002.48 | 10002.48 | 8.10 | 58.42 |
November | 0.208037E+11 | 0.187233E+11 | 11113.86 | 01-NOV-00:04 | 10002.48 | 10002.48 | 8.02 | 58.42 |
December | 0.256001E+11 | 0.230401E+11 | 11113.86 | 01-DEC-00:30 | 10002.48 | 10002.48 | 10.32 | 58.42 |
Annual Sum or Average | 0.260587E+12 | 0.234529E+12 | ||||||
Minimum of Months | 0.647218E+10 | 0.582496E+10 | 11113.86 | 10002.48 | 10002.48 | 7.02 | 58.42 | |
Maximum of Months | 0.295526E+11 | 0.265973E+11 | 11113.86 | 10002.48 | 10002.48 | 10.79 | 58.42 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 8.67 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 6.77 | 0.00 |
March | 0.230057E+09 | 0.207051E+09 | 11113.86 | 14-MAR-15:00 | 10002.48 | 10002.48 | 13.87 | 29.21 |
April | 0.307743E+10 | 0.276969E+10 | 11113.86 | 03-APR-11:40 | 10002.48 | 10002.48 | 13.78 | 29.21 |
May | 0.412607E+10 | 0.371346E+10 | 11113.86 | 02-MAY-15:10 | 10002.48 | 10002.48 | 12.62 | 29.21 |
June | 0.805980E+10 | 0.725382E+10 | 11113.86 | 01-JUN-04:12 | 10002.48 | 10002.48 | 14.57 | 29.21 |
July | 0.970804E+10 | 0.873723E+10 | 11113.86 | 01-JUL-10:30 | 10002.48 | 10002.48 | 13.11 | 29.21 |
August | 0.872316E+10 | 0.785084E+10 | 11113.86 | 01-AUG-03:03 | 10002.48 | 10002.48 | 13.69 | 29.21 |
September | 0.493503E+10 | 0.444153E+10 | 11113.86 | 01-SEP-07:40 | 10002.48 | 10002.48 | 13.14 | 29.21 |
October | 0.196049E+10 | 0.176444E+10 | 11113.86 | 02-OCT-09:50 | 10002.48 | 10002.48 | 13.35 | 29.21 |
November | 46678219.64 | 42010397.68 | 11113.86 | 03-NOV-15:50 | 10002.48 | 10002.48 | 12.78 | 29.21 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 8.81 | 0.00 |
Annual Sum or Average | 0.408667E+11 | 0.367801E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.77 | 0.00 | |
Maximum of Months | 0.970804E+10 | 0.873723E+10 | 11113.86 | 10002.48 | 10002.48 | 14.57 | 29.21 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:10 | 16.86 | 16.86 | 57.09 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 57.47 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 57.52 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:01 | 16.86 | 16.86 | 57.63 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:01 | 16.86 | 16.86 | 58.01 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:02 | 16.86 | 16.86 | 57.88 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 58.02 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 58.03 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.97 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:01 | 16.86 | 16.86 | 57.97 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 57.83 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 57.65 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 57.09 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 58.03 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.166774E+11 | 0.150097E+11 | 28719.07 | 12-JAN-15:02 | 25847.17 | 25847.17 | 24.21 | 82.48 |
February | 0.299943E+11 | 0.269949E+11 | 28729.25 | 07-FEB-13:42 | 25856.32 | 25856.32 | 24.70 | 82.48 |
March | 0.542167E+11 | 0.487950E+11 | 57507.87 | 22-MAR-14:05 | 51757.09 | 51757.09 | 25.76 | 164.96 |
April | 0.747432E+11 | 0.672689E+11 | 57522.36 | 21-APR-15:10 | 51770.12 | 51770.12 | 26.07 | 164.96 |
May | 0.645922E+11 | 0.581330E+11 | 57519.79 | 18-MAY-13:50 | 51767.81 | 51767.81 | 26.01 | 164.96 |
June | 0.880709E+11 | 0.792638E+11 | 57524.15 | 06-JUN-14:50 | 51771.73 | 51771.73 | 26.10 | 164.96 |
July | 0.985183E+11 | 0.886665E+11 | 57685.75 | 19-JUL-10:30 | 51917.18 | 51917.18 | 29.52 | 164.96 |
August | 0.967406E+11 | 0.870665E+11 | 57663.97 | 02-AUG-07:50 | 51897.57 | 51897.57 | 28.99 | 164.96 |
September | 0.635368E+11 | 0.571831E+11 | 57551.69 | 22-SEP-09:05 | 51796.52 | 51796.52 | 26.67 | 164.96 |
October | 0.541310E+11 | 0.487179E+11 | 57543.57 | 03-OCT-14:00 | 51789.21 | 51789.21 | 26.50 | 164.96 |
November | 0.536938E+11 | 0.483244E+11 | 57435.93 | 03-NOV-16:00 | 51692.34 | 51692.34 | 24.15 | 164.96 |
December | 0.659284E+11 | 0.593355E+11 | 28730.04 | 07-DEC-15:04 | 25857.04 | 25857.04 | 24.74 | 82.48 |
Annual Sum or Average | 0.760844E+12 | 0.684759E+12 | ||||||
Minimum of Months | 0.166774E+11 | 0.150097E+11 | 28719.07 | 25847.17 | 25847.17 | 24.15 | 82.48 | |
Maximum of Months | 0.985183E+11 | 0.886665E+11 | 57685.75 | 51917.18 | 51917.18 | 29.52 | 164.96 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 68.89 | 68.89 | 34000.25 | 1873500.58 | 23-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 22.58 | 22.58 | 23951.28 | 2061744.01 | 03-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 22.37 | 22.37 | 13516.75 | 1941985.13 | 02-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:05 | 25.16 | 25.16 | 2000.66 | 1414546.54 | 11-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 21.90 | 21.90 | 104.01 | 48536.20 | 02-MAY-05:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 21.17 | 21.17 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.17 | 21.17 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 21.17 | 21.17 | 1.57 | 2984.37 | 17-AUG-05:10 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.11 | 21.11 | 156.60 | 37205.63 | 25-SEP-05:05 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 21.48 | 21.48 | 2170.09 | 312738.48 | 25-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 22.15 | 22.15 | 16358.72 | 1858677.83 | 17-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 22.23 | 22.23 | 39192.89 | 1900851.03 | 05-DEC-05:01 |
Annual Sum or Average | 0.00 | 10916.90 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.11 | 21.11 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 68.89 | 68.89 | 39192.89 | 2061744.01 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 31465.45 | 970531.42 | 03-JAN-13:05 | 10.66 | 6.70 | 247781.55 | 852986.08 | 22-JAN-13:00 |
February | 158050.03 | 1297900.76 | 20-FEB-18:13 | 12.00 | 6.70 | 72759.05 | 715206.77 | 24-FEB-02:12 |
March | 253376.62 | 2308285.46 | 22-MAR-14:05 | 11.42 | 6.70 | 26498.24 | 735509.48 | 11-MAR-14:51 |
April | 544819.19 | 2345430.12 | 03-APR-13:05 | 11.49 | 6.70 | 6894.94 | 597531.41 | 30-APR-23:33 |
May | 623126.11 | 2332148.38 | 19-MAY-12:05 | 11.46 | 6.70 | 89391.57 | 852979.52 | 07-MAY-07:00 |
June | 932124.12 | 2831862.95 | 01-JUN-04:13 | 12.49 | 6.70 | 5896.18 | 807105.67 | 11-JUN-03:21 |
July | 1079532.79 | 4143744.83 | 21-JUL-09:50 | 15.17 | 8.41 | 1651.43 | 318852.55 | 18-JUL-21:08 |
August | 1061125.92 | 3969979.59 | 03-AUG-05:03 | 14.82 | 8.06 | 593.44 | 224575.79 | 17-AUG-04:47 |
September | 665767.23 | 2476013.22 | 13-SEP-04:14 | 11.76 | 6.70 | 77109.63 | 852973.50 | 23-SEP-23:40 |
October | 442593.83 | 2390506.39 | 04-OCT-10:05 | 11.58 | 6.70 | 53241.76 | 811075.54 | 21-OCT-22:51 |
November | 218992.45 | 1752054.21 | 03-NOV-16:00 | 13.86 | 6.70 | 32125.79 | 815733.00 | 10-NOV-02:31 |
December | 132627.93 | 1228174.56 | 01-DEC-12:34 | 11.72 | 6.70 | 9566.87 | 373023.80 | 14-DEC-13:30 |
Annual Sum or Average | 514015.89 | 52023.34 | ||||||
Minimum of Months | 31465.45 | 970531.42 | 10.66 | 6.70 | 593.44 | 224575.79 | ||
Maximum of Months | 1079532.79 | 4143744.83 | 15.17 | 8.41 | 247781.55 | 852986.08 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 36411.04 | 880704.47 | 12-JAN-15:00 | 19.67 | 6.86 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 186583.79 | 1524970.15 | 07-FEB-13:05 | 18.75 | 8.03 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 299490.27 | 1733293.84 | 22-MAR-14:05 | 21.23 | 7.33 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 587361.86 | 2093971.69 | 21-APR-14:05 | 20.60 | 6.70 | 0.00 | 0.00 | 01-APR-00:05 |
May | 628442.89 | 3077943.95 | 09-MAY-04:11 | 23.85 | 9.51 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 941870.51 | 3972739.93 | 19-JUN-04:12 | 15.69 | 11.96 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1092923.23 | 5772366.79 | 21-JUL-04:11 | 19.74 | 13.55 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1081896.82 | 5669613.64 | 03-AUG-04:11 | 18.86 | 13.14 | 0.00 | 0.00 | 01-AUG-00:02 |
September | 672831.02 | 4778707.48 | 22-SEP-04:11 | 18.07 | 11.69 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 472460.46 | 3766472.56 | 05-OCT-04:11 | 15.92 | 12.00 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 283810.46 | 1777354.56 | 06-NOV-15:01 | 20.14 | 7.01 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 232209.44 | 1372548.68 | 07-DEC-15:00 | 16.80 | 7.32 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 545094.30 | 0.00 | ||||||
Minimum of Months | 36411.04 | 880704.47 | 15.69 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1092923.23 | 5772366.79 | 23.85 | 13.55 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 58.28 | 58.28 | 13237.19 | 47157.61 | 30-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 57.80 | 57.80 | 13307.39 | 47153.23 | 01-FEB-12:58 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 57.84 | 57.84 | 13630.64 | 46272.54 | 01-MAR-12:19 |
April | 0.00 | 0.00 | 01-APR-00:05 | 57.96 | 57.96 | 11934.72 | 43577.36 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 58.51 | 58.51 | 11347.92 | 40486.57 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.28 | 58.28 | 10721.92 | 37095.98 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.40 | 58.40 | 9387.16 | 34593.00 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 58.44 | 58.44 | 10294.88 | 34731.23 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 58.40 | 58.40 | 10145.34 | 37044.59 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 58.28 | 58.28 | 10968.61 | 40542.79 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 58.12 | 58.12 | 12093.69 | 43827.70 | 30-NOV-12:36 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 57.96 | 57.96 | 12451.77 | 46183.70 | 29-DEC-12:23 |
Annual Sum or Average | 0.00 | 11617.37 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.80 | 57.80 | 9387.16 | 34593.00 | ||
Maximum of Months | 0.00 | 0.00 | 58.51 | 58.51 | 13630.64 | 47157.61 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 31073.87 | 1072159.03 | 12-JAN-15:02 | 24.21 | 21.10 | 3040.77 | 177904.98 | 07-JAN-04:33 |
February | 195584.11 | 1241811.69 | 07-FEB-13:42 | 24.70 | 21.10 | 172.16 | 83547.62 | 01-FEB-11:40 |
March | 293578.56 | 3215658.43 | 22-MAR-14:05 | 25.76 | 21.10 | 1229.47 | 86294.10 | 15-MAR-22:10 |
April | 683631.53 | 3422872.18 | 21-APR-15:10 | 26.07 | 21.11 | 1355.00 | 108045.19 | 13-APR-22:20 |
May | 766827.39 | 3386191.26 | 18-MAY-13:50 | 26.01 | 21.92 | 901.46 | 101662.51 | 02-MAY-23:20 |
June | 1255512.85 | 3448454.05 | 06-JUN-14:50 | 26.10 | 21.84 | 14.99 | 20445.50 | 14-JUN-02:70 |
July | 1816008.82 | 7289722.02 | 21-JUL-09:50 | 31.67 | 26.09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1540013.67 | 5443524.35 | 02-AUG-07:50 | 28.99 | 24.46 | 5.47 | 7126.67 | 17-AUG-01:10 |
September | 934598.52 | 3842249.83 | 22-SEP-09:05 | 26.67 | 22.92 | 213.12 | 78798.08 | 19-SEP-02:70 |
October | 567356.71 | 3726109.33 | 03-OCT-14:00 | 26.50 | 23.03 | 32.85 | 40146.29 | 07-OCT-11:30 |
November | 238665.19 | 2101281.56 | 03-NOV-16:00 | 24.15 | 22.56 | 2110.53 | 73956.97 | 27-NOV-06:50 |
December | 79453.24 | 1255107.69 | 07-DEC-15:04 | 24.74 | 21.10 | 4497.14 | 151306.11 | 19-DEC-01:11 |
Annual Sum or Average | 703485.69 | 1141.24 | ||||||
Minimum of Months | 31073.87 | 1072159.03 | 24.15 | 21.10 | 0.00 | 0.00 | ||
Maximum of Months | 1816008.82 | 7289722.02 | 31.67 | 26.09 | 4497.14 | 177904.98 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.170936E+10 | 0.00 | 0.403224E+10 | 0.107322E+11 | 0.00 | 0.00 |
February | 0.106006E+10 | 0.00 | 0.128698E+11 | 0.102458E+11 | 0.00 | 0.00 |
March | 0.520788E+09 | 0.00 | 0.313112E+11 | 0.137608E+11 | 0.00 | 0.00 |
April | 23168789.24 | 0.00 | 0.848202E+11 | 0.168032E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.123886E+12 | 0.173888E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.165922E+12 | 0.205317E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.196232E+12 | 0.208363E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.182827E+12 | 0.229247E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.131844E+12 | 0.172077E+11 | 0.00 | 0.00 |
October | 5414386.08 | 0.00 | 0.754054E+11 | 0.150822E+11 | 0.00 | 0.00 |
November | 0.351191E+09 | 0.00 | 0.221262E+11 | 0.126767E+11 | 0.00 | 0.00 |
December | 0.147220E+10 | 0.00 | 0.186669E+10 | 0.116646E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.514219E+10 | 0.00 | 0.103314E+13 | 0.189855E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.186669E+10 | 0.102458E+11 | 0.00 | 0.00 |
Maximum of Months | 0.170936E+10 | 0.00 | 0.196232E+12 | 0.229247E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.684043E+11 | 0.00 | 0.544641E+11 | 0.844537E+11 | 0.00 | 0.00 |
February | 0.427462E+11 | 0.00 | 0.130404E+12 | 0.836965E+11 | 0.00 | 0.00 |
March | 0.261498E+11 | 0.00 | 0.269586E+12 | 0.107813E+12 | 0.00 | 0.00 |
April | 0.326745E+10 | 0.00 | 0.654115E+12 | 0.121839E+12 | 0.00 | 0.00 |
May | 73246658.70 | 0.00 | 0.110295E+13 | 0.152077E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.143538E+13 | 0.176387E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.156943E+13 | 0.163799E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.140775E+13 | 0.170663E+12 | 0.00 | 0.00 |
September | 0.131541E+09 | 0.00 | 0.115109E+13 | 0.144193E+12 | 0.00 | 0.00 |
October | 0.340036E+10 | 0.00 | 0.644753E+12 | 0.118567E+12 | 0.00 | 0.00 |
November | 0.296749E+11 | 0.00 | 0.207418E+12 | 0.936394E+11 | 0.00 | 0.00 |
December | 0.783403E+11 | 0.00 | 0.320775E+11 | 0.831526E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.252188E+12 | 0.00 | 0.865941E+13 | 0.150028E+13 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.320775E+11 | 0.831526E+11 | 0.00 | 0.00 |
Maximum of Months | 0.783403E+11 | 0.00 | 0.156943E+13 | 0.176387E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.216092E+11 | 0.00 | 0.267709E+10 | 0.804786E+10 | 0.00 | 0.00 |
February | 0.143891E+11 | 0.00 | 0.104119E+11 | 0.766868E+10 | 0.00 | 0.00 |
March | 0.966184E+10 | 0.00 | 0.264970E+11 | 0.974614E+10 | 0.00 | 0.00 |
April | 0.194049E+10 | 0.00 | 0.785961E+11 | 0.117707E+11 | 0.00 | 0.00 |
May | 0.211610E+09 | 0.00 | 0.136459E+12 | 0.156505E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.180645E+12 | 0.193171E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.193040E+12 | 0.178770E+11 | 0.00 | 0.00 |
August | 4532853.02 | 0.00 | 0.170657E+12 | 0.178873E+11 | 0.00 | 0.00 |
September | 0.272641E+09 | 0.00 | 0.136465E+12 | 0.146174E+11 | 0.00 | 0.00 |
October | 0.242300E+10 | 0.00 | 0.703328E+11 | 0.112676E+11 | 0.00 | 0.00 |
November | 0.125387E+11 | 0.00 | 0.164537E+11 | 0.877328E+10 | 0.00 | 0.00 |
December | 0.255558E+11 | 0.00 | 0.107523E+10 | 0.835287E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.886069E+11 | 0.00 | 0.102331E+13 | 0.150976E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.107523E+10 | 0.766868E+10 | 0.00 | 0.00 |
Maximum of Months | 0.255558E+11 | 0.00 | 0.193040E+12 | 0.193171E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.169720E+11 | 0.908462E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.158569E+11 | 0.768927E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.254138E+11 | 0.885959E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.434536E+11 | 0.845404E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.673026E+11 | 0.732558E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.829149E+11 | 0.690683E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.105106E+12 | 0.754646E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.102266E+12 | 0.923937E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.845023E+11 | 0.937648E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.545218E+11 | 0.111744E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.238444E+11 | 0.120210E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.128791E+11 | 0.104340E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.635034E+12 | 0.108112E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.128791E+11 | 0.690683E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.105106E+12 | 0.120210E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 5273208.60 | 0.186581E+12 | 0.00 | 58.18 |
February | 0.00 | 0.00 | 0.201627E+12 | 0.201403E+12 | 0.00 | 57.15 |
March | 0.00 | 0.00 | 0.299642E+12 | 0.293407E+12 | 0.00 | 82.48 |
April | 0.00 | 0.00 | 0.485843E+12 | 0.259274E+12 | 0.00 | 63.19 |
May | 0.00 | 0.00 | 0.147470E+12 | 0.118818E+12 | 0.00 | 32.97 |
June | 0.00 | 0.00 | 0.443702E+12 | 0.484992E+11 | 0.00 | 6.40 |
July | 0.00 | 0.00 | 0.713354E+12 | 0.552320E+11 | 0.00 | 0.08 |
August | 0.00 | 0.00 | 0.866350E+12 | 0.884304E+11 | 0.00 | 1.55 |
September | 0.00 | 0.00 | 0.133421E+12 | 0.464065E+11 | 0.00 | 6.38 |
October | 0.00 | 0.00 | 0.293563E+12 | 0.104009E+12 | 0.00 | 21.36 |
November | 0.00 | 0.00 | 0.274918E+12 | 0.247761E+12 | 0.00 | 66.68 |
December | 0.00 | 0.00 | 0.282735E+12 | 0.344338E+12 | 0.00 | 92.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.414263E+13 | 0.199416E+13 | 0.00 | 488.83 |
Minimum of Months | 0.00 | 0.00 | 5273208.60 | 0.464065E+11 | 0.00 | 0.08 |
Maximum of Months | 0.00 | 0.00 | 0.866350E+12 | 0.344338E+12 | 0.00 | 92.40 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.587503E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.644162E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.833250E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.973195E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.649767E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.784435E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.926455E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.106757E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.630334E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.750147E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.806490E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.950045E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.960335E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.587503E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.106757E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.499205E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.558773E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.722640E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.836084E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.574915E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.689154E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.807361E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.922094E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.555956E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.654444E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.694482E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.798484E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.831359E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.499205E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.922094E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.485582E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.582185E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.783390E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.924506E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.631323E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.773953E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.912148E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.103806E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.608395E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.710290E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.740557E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.841786E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.903218E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.485582E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.103806E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.107322E+11 | 0.403224E+10 | 0.170936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102458E+11 | 0.128698E+11 | 0.106006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137608E+11 | 0.313112E+11 | 0.520788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168032E+11 | 0.848202E+11 | 23168789.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173888E+11 | 0.123886E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.205317E+11 | 0.165922E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.208363E+11 | 0.196232E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.229247E+11 | 0.182827E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172077E+11 | 0.131844E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150822E+11 | 0.754054E+11 | 5414386.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126767E+11 | 0.221262E+11 | 0.351191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116646E+11 | 0.186669E+10 | 0.147220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189855E+12 | 0.103314E+13 | 0.514219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.102458E+11 | 0.186669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.229247E+11 | 0.196232E+12 | 0.170936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.844537E+11 | 0.544641E+11 | 0.684043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.836965E+11 | 0.130404E+12 | 0.427462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107813E+12 | 0.269586E+12 | 0.261498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121839E+12 | 0.654115E+12 | 0.326745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152077E+12 | 0.110295E+13 | 73246658.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.176387E+12 | 0.143538E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163799E+12 | 0.156943E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170663E+12 | 0.140775E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144193E+12 | 0.115109E+13 | 0.131541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118567E+12 | 0.644753E+12 | 0.340036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.936394E+11 | 0.207418E+12 | 0.296749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.831526E+11 | 0.320775E+11 | 0.783403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.150028E+13 | 0.865941E+13 | 0.252188E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.831526E+11 | 0.320775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176387E+12 | 0.156943E+13 | 0.783403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.804786E+10 | 0.267709E+10 | 0.216092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.766868E+10 | 0.104119E+11 | 0.143891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.974614E+10 | 0.264970E+11 | 0.966184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117707E+11 | 0.785961E+11 | 0.194049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156505E+11 | 0.136459E+12 | 0.211610E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.193171E+11 | 0.180645E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178770E+11 | 0.193040E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178873E+11 | 0.170657E+12 | 4532853.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146174E+11 | 0.136465E+12 | 0.272641E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112676E+11 | 0.703328E+11 | 0.242300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.877328E+10 | 0.164537E+11 | 0.125387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.835287E+10 | 0.107523E+10 | 0.255558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.150976E+12 | 0.102331E+13 | 0.886069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.766868E+10 | 0.107523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.193171E+11 | 0.193040E+12 | 0.255558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.908462E+10 | 0.169720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.768927E+10 | 0.158569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.885959E+10 | 0.254138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.845404E+10 | 0.434536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.732558E+10 | 0.673026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.690683E+10 | 0.829149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.754646E+10 | 0.105106E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.923937E+10 | 0.102266E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.937648E+10 | 0.845023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111744E+11 | 0.545218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120210E+11 | 0.238444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104340E+11 | 0.128791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108112E+12 | 0.635034E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.690683E+10 | 0.128791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.120210E+11 | 0.105106E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.301887E+11 | 5273208.60 | 0.00 | 0.00 | 0.00 | 0.155691E+12 | 0.00 | 0.00 |
February | 0.477753E+11 | 0.201627E+12 | 0.00 | 0.00 | 0.00 | 0.152939E+12 | 0.00 | 0.00 |
March | 0.716927E+11 | 0.299642E+12 | 0.00 | 0.00 | 0.00 | 0.220721E+12 | 0.00 | 0.00 |
April | 0.894029E+11 | 0.485843E+12 | 0.00 | 0.00 | 0.00 | 0.169110E+12 | 0.00 | 0.00 |
May | 0.301887E+11 | 0.147470E+12 | 0.00 | 0.00 | 0.00 | 0.882318E+11 | 0.00 | 0.00 |
June | 0.312893E+11 | 0.443702E+12 | 0.00 | 0.00 | 0.00 | 0.171328E+11 | 0.00 | 0.00 |
July | 0.550099E+11 | 0.713354E+12 | 0.00 | 0.00 | 0.00 | 0.221096E+09 | 0.00 | 0.00 |
August | 0.842714E+11 | 0.866350E+12 | 0.00 | 0.00 | 0.00 | 0.414036E+10 | 0.00 | 0.00 |
September | 0.292451E+11 | 0.133421E+12 | 0.00 | 0.00 | 0.00 | 0.170845E+11 | 0.00 | 0.00 |
October | 0.465878E+11 | 0.293563E+12 | 0.00 | 0.00 | 0.00 | 0.571637E+11 | 0.00 | 0.00 |
November | 0.685066E+11 | 0.274918E+12 | 0.00 | 0.00 | 0.00 | 0.178451E+12 | 0.00 | 0.00 |
December | 0.959422E+11 | 0.282735E+12 | 0.00 | 0.00 | 0.00 | 0.247283E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.680101E+12 | 0.414263E+13 | 0.00 | 0.00 | 0.00 | 0.130817E+13 | 0.00 | 0.00 |
Minimum of Months | 0.292451E+11 | 5273208.60 | 0.00 | 0.00 | 0.00 | 0.221096E+09 | 0.00 | 0.00 |
Maximum of Months | 0.959422E+11 | 0.866350E+12 | 0.00 | 0.00 | 0.00 | 0.247283E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.377204E+10 | 0.695588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.340701E+10 | 0.108346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.377204E+10 | 0.175310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.365037E+10 | 0.226041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.377204E+10 | 0.855433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.365037E+10 | 0.133781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.377204E+10 | 0.190004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.377204E+10 | 0.239745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.365037E+10 | 0.842988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377204E+10 | 0.131607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.365037E+10 | 0.169243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.377204E+10 | 0.221794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.444128E+11 | 0.183527E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.340701E+10 | 0.695588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.377204E+10 | 0.239745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.359482E+11 | 0.528745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.324694E+11 | 0.964481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.359482E+11 | 0.161697E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.347886E+11 | 0.211976E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.359482E+11 | 0.784416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.347886E+11 | 0.126852E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.359482E+11 | 0.180742E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.359482E+11 | 0.228001E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.347886E+11 | 0.766399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.359482E+11 | 0.120588E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.347886E+11 | 0.153318E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.359482E+11 | 0.199538E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.423261E+12 | 0.168712E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.324694E+11 | 0.528745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.359482E+11 | 0.228001E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.376272E+10 | 0.349352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339859E+10 | 0.835033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.376272E+10 | 0.152063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.364134E+10 | 0.209444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.376272E+10 | 0.790913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.364134E+10 | 0.129857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.376272E+10 | 0.184202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.376272E+10 | 0.230416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.364134E+10 | 0.765781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.376272E+10 | 0.115328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.364134E+10 | 0.138832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.376272E+10 | 0.179345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.443030E+11 | 0.161360E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.339859E+10 | 0.349352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.376272E+10 | 0.230416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.107322E+11 | 0.170936E+10 | 0.403224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102458E+11 | 0.106006E+10 | 0.128698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137608E+11 | 0.520788E+09 | 0.313112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168032E+11 | 23168789.24 | 0.848202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173888E+11 | 0.00 | 0.123886E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.205317E+11 | 0.00 | 0.165922E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.208363E+11 | 0.00 | 0.196232E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.229247E+11 | 0.00 | 0.182827E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172077E+11 | 0.00 | 0.131844E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150822E+11 | 5414386.08 | 0.754054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126767E+11 | 0.351191E+09 | 0.221262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116646E+11 | 0.147220E+10 | 0.186669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189855E+12 | 0.514219E+10 | 0.103314E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.102458E+11 | 0.00 | 0.186669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.229247E+11 | 0.170936E+10 | 0.196232E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.844537E+11 | 0.684043E+11 | 0.544641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.836965E+11 | 0.427462E+11 | 0.130404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107813E+12 | 0.261498E+11 | 0.269586E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121839E+12 | 0.326745E+10 | 0.654115E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152077E+12 | 73246658.70 | 0.110295E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.176387E+12 | 0.00 | 0.143538E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163799E+12 | 0.00 | 0.156943E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170663E+12 | 0.00 | 0.140775E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144193E+12 | 0.131541E+09 | 0.115109E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118567E+12 | 0.340036E+10 | 0.644753E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.936394E+11 | 0.296749E+11 | 0.207418E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.831526E+11 | 0.783403E+11 | 0.320775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.150028E+13 | 0.252188E+12 | 0.865941E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.831526E+11 | 0.00 | 0.320775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176387E+12 | 0.783403E+11 | 0.156943E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.804786E+10 | 0.216092E+11 | 0.267709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.766868E+10 | 0.143891E+11 | 0.104119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.974614E+10 | 0.966184E+10 | 0.264970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117707E+11 | 0.194049E+10 | 0.785961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156505E+11 | 0.211610E+09 | 0.136459E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.193171E+11 | 0.00 | 0.180645E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178770E+11 | 0.00 | 0.193040E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178873E+11 | 4532853.02 | 0.170657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146174E+11 | 0.272641E+09 | 0.136465E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112676E+11 | 0.242300E+10 | 0.703328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.877328E+10 | 0.125387E+11 | 0.164537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.835287E+10 | 0.255558E+11 | 0.107523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.150976E+12 | 0.886069E+11 | 0.102331E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.766868E+10 | 0.00 | 0.107523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.193171E+11 | 0.255558E+11 | 0.193040E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.908462E+10 | 0.00 | 0.169720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.768927E+10 | 0.00 | 0.158569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.885959E+10 | 0.00 | 0.254138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.845404E+10 | 0.00 | 0.434536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.732558E+10 | 0.00 | 0.673026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.690683E+10 | 0.00 | 0.829149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.754646E+10 | 0.00 | 0.105106E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.923937E+10 | 0.00 | 0.102266E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.937648E+10 | 0.00 | 0.845023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111744E+11 | 0.00 | 0.545218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120210E+11 | 0.00 | 0.238444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104340E+11 | 0.00 | 0.128791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108112E+12 | 0.00 | 0.635034E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.690683E+10 | 0.00 | 0.128791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.120210E+11 | 0.00 | 0.105106E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.301887E+11 | 0.00 | 5273208.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156392E+12 | 0.00 | 0.00 | 0.00 |
February | 0.477753E+11 | 0.00 | 0.201627E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153628E+12 | 0.00 | 0.00 | 0.00 |
March | 0.716927E+11 | 0.00 | 0.299642E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221715E+12 | 0.00 | 0.00 | 0.00 |
April | 0.894029E+11 | 0.00 | 0.485843E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169871E+12 | 0.00 | 0.00 | 0.00 |
May | 0.301887E+11 | 0.00 | 0.147470E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.886290E+11 | 0.00 | 0.00 | 0.00 |
June | 0.312893E+11 | 0.00 | 0.443702E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172099E+11 | 0.00 | 0.00 | 0.00 |
July | 0.550099E+11 | 0.00 | 0.713354E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222100E+09 | 0.00 | 0.00 | 0.00 |
August | 0.842714E+11 | 0.00 | 0.866350E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415900E+10 | 0.00 | 0.00 | 0.00 |
September | 0.292451E+11 | 0.00 | 0.133421E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171614E+11 | 0.00 | 0.00 | 0.00 |
October | 0.465878E+11 | 0.00 | 0.293563E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574210E+11 | 0.00 | 0.00 | 0.00 |
November | 0.685066E+11 | 0.00 | 0.274918E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179254E+12 | 0.00 | 0.00 | 0.00 |
December | 0.959422E+11 | 0.00 | 0.282735E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248396E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.680101E+12 | 0.00 | 0.414263E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131406E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.292451E+11 | 0.00 | 5273208.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222100E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.959422E+11 | 0.00 | 0.866350E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248396E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.377204E+10 | 0.00 | 0.00 | 0.00 | 0.210299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.340701E+10 | 0.00 | 0.00 | 0.00 | 0.303461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.377204E+10 | 0.00 | 0.00 | 0.00 | 0.456045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.365037E+10 | 0.00 | 0.00 | 0.00 | 0.608159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.377204E+10 | 0.00 | 0.00 | 0.00 | 0.272563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.365037E+10 | 0.00 | 0.00 | 0.00 | 0.419399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.377204E+10 | 0.00 | 0.00 | 0.00 | 0.549251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.377204E+10 | 0.00 | 0.00 | 0.00 | 0.690364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.365037E+10 | 0.00 | 0.00 | 0.00 | 0.265297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377204E+10 | 0.00 | 0.00 | 0.00 | 0.372943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.365037E+10 | 0.00 | 0.00 | 0.00 | 0.441454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.377204E+10 | 0.00 | 0.00 | 0.00 | 0.572840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.444128E+11 | 0.00 | 0.00 | 0.00 | 0.516207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.340701E+10 | 0.00 | 0.00 | 0.00 | 0.210299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.377204E+10 | 0.00 | 0.00 | 0.00 | 0.690364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.359482E+11 | 0.00 | 0.00 | 0.00 | 0.139723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.324694E+11 | 0.00 | 0.00 | 0.00 | 0.234080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.359482E+11 | 0.00 | 0.00 | 0.00 | 0.363158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.347886E+11 | 0.00 | 0.00 | 0.00 | 0.488198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.359482E+11 | 0.00 | 0.00 | 0.00 | 0.215432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.347886E+11 | 0.00 | 0.00 | 0.00 | 0.341268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.359482E+11 | 0.00 | 0.00 | 0.00 | 0.447879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.359482E+11 | 0.00 | 0.00 | 0.00 | 0.562612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.347886E+11 | 0.00 | 0.00 | 0.00 | 0.208070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.359482E+11 | 0.00 | 0.00 | 0.00 | 0.294962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.347886E+11 | 0.00 | 0.00 | 0.00 | 0.346596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.359482E+11 | 0.00 | 0.00 | 0.00 | 0.439002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.423261E+12 | 0.00 | 0.00 | 0.00 | 0.408098E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.324694E+11 | 0.00 | 0.00 | 0.00 | 0.139723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.359482E+11 | 0.00 | 0.00 | 0.00 | 0.562612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.376272E+10 | 0.00 | 0.00 | 0.00 | 0.109310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339859E+10 | 0.00 | 0.00 | 0.00 | 0.242327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.376272E+10 | 0.00 | 0.00 | 0.00 | 0.407118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.364134E+10 | 0.00 | 0.00 | 0.00 | 0.560372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.376272E+10 | 0.00 | 0.00 | 0.00 | 0.255051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.364134E+10 | 0.00 | 0.00 | 0.00 | 0.409818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.376272E+10 | 0.00 | 0.00 | 0.00 | 0.535876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.376272E+10 | 0.00 | 0.00 | 0.00 | 0.661790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.364134E+10 | 0.00 | 0.00 | 0.00 | 0.244261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.376272E+10 | 0.00 | 0.00 | 0.00 | 0.334018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.364134E+10 | 0.00 | 0.00 | 0.00 | 0.376423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.376272E+10 | 0.00 | 0.00 | 0.00 | 0.465513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.443030E+11 | 0.00 | 0.00 | 0.00 | 0.460188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.339859E+10 | 0.00 | 0.00 | 0.00 | 0.109310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.376272E+10 | 0.00 | 0.00 | 0.00 | 0.661790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.780781E+10 | 0.00 | 0.00 | 0.148699E+09 | 0.00 | 0.00 | 0.517575E+11 | 0.00 | 0.79 |
February | 0.925598E+10 | 0.00 | 0.00 | 0.384733E+09 | 0.00 | 0.00 | 0.380253E+11 | 0.00 | 0.82 |
March | 0.740769E+10 | 0.00 | 0.00 | 0.403653E+09 | 0.00 | 0.00 | 0.415175E+11 | 0.00 | 0.93 |
April | 0.170317E+10 | 0.517519E+09 | 0.00 | 0.173058E+09 | 34275872.36 | 0.00 | 0.281766E+11 | 0.00 | 0.85 |
May | 0.222047E+09 | 0.240083E+10 | 0.00 | 86259750.40 | 86629782.52 | 0.00 | 0.117061E+11 | 0.00 | 0.64 |
June | 4203537.88 | 0.738860E+10 | 0.00 | 73649258.22 | 0.127573E+09 | 0.00 | 0.258359E+10 | 0.00 | 0.51 |
July | 0.00 | 0.246993E+11 | 0.00 | 7240004.52 | 0.194953E+09 | 0.00 | 0.319430E+09 | 0.00 | 0.49 |
August | 15015.72 | 0.130351E+11 | 0.00 | 33168733.72 | 0.103456E+09 | 0.00 | 0.340168E+10 | 0.00 | 0.68 |
September | 0.100551E+09 | 0.875275E+10 | 0.00 | 71396047.55 | 98006850.82 | 0.00 | 0.103862E+11 | 0.00 | 0.74 |
October | 0.189480E+10 | 0.208664E+10 | 0.00 | 0.449937E+09 | 333134.23 | 0.00 | 0.340885E+11 | 0.00 | 1.08 |
November | 0.685540E+10 | 0.00 | 0.00 | 0.537637E+09 | 0.00 | 0.00 | 0.536657E+11 | 0.00 | 1.15 |
December | 0.909595E+10 | 0.00 | 0.00 | 0.295352E+09 | 0.00 | 0.00 | 0.586568E+11 | 0.00 | 0.83 |
Annual Sum or Average | 0.443476E+11 | 0.588807E+11 | 0.00 | 0.266478E+10 | 0.645227E+09 | 0.00 | 0.334285E+12 | 0.00 | 0.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 7240004.52 | 0.00 | 0.00 | 0.319430E+09 | 0.00 | 0.49 |
Maximum of Months | 0.925598E+10 | 0.246993E+11 | 0.00 | 0.537637E+09 | 0.194953E+09 | 0.00 | 0.586568E+11 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.635055E+10 | 0.00 | 0.00 | 0.202790E+09 | 0.00 | 0.00 | 0.496165E+11 | 0.00 | 0.75 |
February | 0.109021E+11 | 0.00 | 0.00 | 0.476777E+09 | 0.00 | 0.00 | 0.370653E+11 | 0.00 | 0.86 |
March | 0.734739E+10 | 0.00 | 0.00 | 0.564761E+09 | 0.00 | 0.00 | 0.467799E+11 | 0.00 | 1.07 |
April | 0.353609E+10 | 0.286005E+09 | 0.00 | 0.221258E+09 | 65597868.39 | 0.00 | 0.310716E+11 | 0.00 | 0.96 |
May | 0.139216E+10 | 0.925820E+09 | 0.00 | 95320170.30 | 80316775.14 | 0.00 | 0.133801E+11 | 0.00 | 0.64 |
June | 0.811022E+09 | 0.341998E+10 | 0.00 | 77386977.45 | 0.170908E+09 | 0.00 | 0.443327E+10 | 0.00 | 0.46 |
July | 0.164345E+09 | 0.116172E+11 | 0.00 | 12096050.93 | 0.129193E+10 | 0.00 | 0.536310E+09 | 0.00 | 0.47 |
August | 0.147533E+10 | 0.360816E+10 | 0.00 | 59426034.92 | 0.381711E+09 | 0.00 | 0.603956E+10 | 0.00 | 0.68 |
September | 0.972116E+09 | 0.218775E+10 | 0.00 | 77612797.82 | 0.104215E+09 | 0.00 | 0.940174E+10 | 0.00 | 0.61 |
October | 0.339541E+10 | 0.521526E+09 | 0.00 | 0.412183E+09 | 3074808.65 | 0.00 | 0.323184E+11 | 0.00 | 0.98 |
November | 0.639838E+10 | 0.00 | 0.00 | 0.605345E+09 | 0.00 | 0.00 | 0.484540E+11 | 0.00 | 1.02 |
December | 0.579462E+10 | 0.00 | 0.00 | 0.405020E+09 | 0.00 | 0.00 | 0.557517E+11 | 0.00 | 0.76 |
Annual Sum or Average | 0.485395E+11 | 0.225665E+11 | 0.00 | 0.320998E+10 | 0.209776E+10 | 0.00 | 0.334848E+12 | 0.00 | 0.77 |
Minimum of Months | 0.164345E+09 | 0.00 | 0.00 | 12096050.93 | 0.00 | 0.00 | 0.536310E+09 | 0.00 | 0.46 |
Maximum of Months | 0.109021E+11 | 0.116172E+11 | 0.00 | 0.605345E+09 | 0.129193E+10 | 0.00 | 0.557517E+11 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143673E+12 | 0.00 | 0.00 | 0.117936E+10 | 0.00 | 0.00 | 0.267447E+12 | 0.00 | 0.55 |
February | 0.137058E+12 | 0.00 | 0.00 | 0.314548E+10 | 0.00 | 0.00 | 0.231435E+12 | 0.00 | 0.68 |
March | 0.130624E+12 | 0.00 | 0.00 | 0.333727E+10 | 0.00 | 0.00 | 0.281796E+12 | 0.00 | 0.84 |
April | 0.470545E+11 | 0.227676E+10 | 0.00 | 0.126999E+10 | 0.128365E+10 | 0.00 | 0.198041E+12 | 0.00 | 0.72 |
May | 0.175807E+11 | 0.983707E+10 | 0.00 | 0.715419E+09 | 0.109046E+10 | 0.00 | 0.101425E+12 | 0.00 | 0.56 |
June | 0.685242E+10 | 0.353322E+11 | 0.00 | 0.613245E+09 | 0.118170E+10 | 0.00 | 0.351344E+11 | 0.00 | 0.41 |
July | 0.655641E+09 | 0.104172E+12 | 0.00 | 92526259.49 | 0.376158E+10 | 0.00 | 0.374244E+10 | 0.00 | 0.38 |
August | 0.347913E+10 | 0.342574E+11 | 0.00 | 0.471542E+09 | 0.118706E+10 | 0.00 | 0.482188E+11 | 0.00 | 0.51 |
September | 0.127559E+11 | 0.211244E+11 | 0.00 | 0.554300E+09 | 0.985941E+09 | 0.00 | 0.648598E+11 | 0.00 | 0.52 |
October | 0.812846E+11 | 0.520891E+10 | 0.00 | 0.231917E+10 | 44607772.66 | 0.00 | 0.188377E+12 | 0.00 | 0.78 |
November | 0.142665E+12 | 0.00 | 0.00 | 0.304853E+10 | 0.00 | 0.00 | 0.238718E+12 | 0.00 | 0.73 |
December | 0.173332E+12 | 0.00 | 0.00 | 0.182112E+10 | 0.00 | 0.00 | 0.242600E+12 | 0.00 | 0.53 |
Annual Sum or Average | 0.897015E+12 | 0.212209E+12 | 0.00 | 0.185679E+11 | 0.953500E+10 | 0.00 | 0.190179E+13 | 0.00 | 0.60 |
Minimum of Months | 0.655641E+09 | 0.00 | 0.00 | 92526259.49 | 0.00 | 0.00 | 0.374244E+10 | 0.00 | 0.38 |
Maximum of Months | 0.173332E+12 | 0.104172E+12 | 0.00 | 0.333727E+10 | 0.376158E+10 | 0.00 | 0.281796E+12 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.266162E+11 | 0.00 | 0.00 | 21583922.81 | 0.00 | 0.111725E+10 | 0.681542E+10 | 0.00 | 0.51 |
February | 0.228042E+11 | 0.00 | 0.00 | 94956561.67 | 0.00 | 0.457194E+09 | 0.887297E+10 | 0.00 | 0.63 |
March | 0.219878E+11 | 0.00 | 0.00 | 0.119994E+09 | 0.00 | 83061978.11 | 0.161080E+11 | 0.00 | 0.80 |
April | 0.870351E+10 | 0.112486E+09 | 0.00 | 82894070.57 | 37049185.98 | 0.00 | 0.143492E+11 | 0.00 | 0.69 |
May | 0.343506E+10 | 0.455779E+09 | 0.00 | 73803148.64 | 77309543.93 | 0.00 | 0.743436E+10 | 0.00 | 0.54 |
June | 0.122314E+10 | 0.257393E+10 | 0.00 | 58012718.30 | 96675017.02 | 0.00 | 0.297966E+10 | 0.00 | 0.42 |
July | 0.123779E+09 | 0.901219E+10 | 0.00 | 12969766.75 | 0.723929E+09 | 0.00 | 0.314684E+09 | 0.00 | 0.38 |
August | 0.819899E+09 | 0.257533E+10 | 0.00 | 56331896.75 | 0.230576E+09 | 0.00 | 0.440543E+10 | 0.00 | 0.51 |
September | 0.244296E+10 | 0.128739E+10 | 0.00 | 55050617.46 | 0.332620E+09 | 0.00 | 0.384120E+10 | 0.00 | 0.48 |
October | 0.116432E+11 | 0.280887E+09 | 0.00 | 0.113225E+09 | 26953726.56 | 0.00 | 0.124838E+11 | 0.00 | 0.74 |
November | 0.230635E+11 | 0.00 | 0.00 | 75084503.22 | 154232.28 | 0.587725E+09 | 0.997084E+10 | 0.00 | 0.70 |
December | 0.281048E+11 | 0.00 | 0.00 | 21870370.56 | 0.00 | 0.146424E+10 | 0.390154E+10 | 0.00 | 0.46 |
Annual Sum or Average | 0.150968E+12 | 0.162980E+11 | 0.00 | 0.785777E+09 | 0.152527E+10 | 0.370946E+10 | 0.914771E+11 | 0.00 | 0.57 |
Minimum of Months | 0.123779E+09 | 0.00 | 0.00 | 12969766.75 | 0.00 | 0.00 | 0.314684E+09 | 0.00 | 0.38 |
Maximum of Months | 0.281048E+11 | 0.901219E+10 | 0.00 | 0.119994E+09 | 0.723929E+09 | 0.146424E+10 | 0.161080E+11 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.676695E+10 | 0.00 | 0.00 | 583207.86 | 0.00 | 0.194032E+09 | 0.334039E+09 | 0.00 | 0.76 |
February | 0.557196E+10 | 0.00 | 0.00 | 5515490.57 | 0.00 | 0.158289E+09 | 0.590615E+09 | 0.00 | 0.90 |
March | 0.538051E+10 | 0.00 | 0.00 | 12897953.70 | 0.00 | 29208004.82 | 0.167132E+10 | 0.00 | 1.12 |
April | 0.237839E+10 | 55178982.06 | 0.00 | 13001890.96 | 12151608.79 | 0.00 | 0.211946E+10 | 0.00 | 1.04 |
May | 0.932496E+09 | 0.201970E+09 | 0.00 | 9491795.13 | 14918187.53 | 0.00 | 0.117969E+10 | 0.00 | 0.79 |
June | 0.322229E+09 | 0.796735E+09 | 0.00 | 8343229.74 | 32079678.33 | 0.00 | 0.500469E+09 | 0.00 | 0.67 |
July | 45246382.89 | 0.206095E+10 | 0.00 | 1436916.57 | 0.278659E+09 | 0.00 | 60495209.07 | 0.00 | 0.66 |
August | 0.398513E+09 | 0.635797E+09 | 0.00 | 7331096.17 | 79719838.77 | 0.00 | 0.690161E+09 | 0.00 | 0.85 |
September | 0.826943E+09 | 0.354813E+09 | 0.00 | 6658118.66 | 30910241.26 | 0.00 | 0.579726E+09 | 0.00 | 0.71 |
October | 0.294184E+10 | 85829121.91 | 0.00 | 17287567.47 | 947913.71 | 0.00 | 0.168988E+10 | 0.00 | 1.03 |
November | 0.567726E+10 | 0.00 | 0.00 | 8805683.06 | 0.00 | 12194178.13 | 0.116051E+10 | 0.00 | 0.98 |
December | 0.711445E+10 | 0.00 | 0.00 | 722115.47 | 0.00 | 0.149098E+09 | 0.289642E+09 | 0.00 | 0.73 |
Annual Sum or Average | 0.383568E+11 | 0.419127E+10 | 0.00 | 92075065.35 | 0.449386E+09 | 0.542822E+09 | 0.108660E+11 | 0.00 | 0.85 |
Minimum of Months | 45246382.89 | 0.00 | 0.00 | 583207.86 | 0.00 | 0.00 | 60495209.07 | 0.00 | 0.66 |
Maximum of Months | 0.711445E+10 | 0.206095E+10 | 0.00 | 17287567.47 | 0.278659E+09 | 0.194032E+09 | 0.211946E+10 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.559068E+10 | 0.00 | 0.00 | 3429892.02 | 0.00 | 0.209026E+09 | 0.124154E+10 | 0.00 | 1.13 |
February | 0.464887E+10 | 0.00 | 0.00 | 17430726.95 | 0.00 | 0.145144E+09 | 0.151076E+10 | 0.00 | 1.37 |
March | 0.425418E+10 | 0.00 | 0.00 | 34041179.04 | 0.00 | 58410547.82 | 0.318527E+10 | 0.00 | 1.76 |
April | 0.191902E+10 | 42181240.73 | 0.00 | 20327815.65 | 11584975.80 | 0.00 | 0.317553E+10 | 0.00 | 1.75 |
May | 0.773016E+09 | 0.161750E+09 | 0.00 | 12365945.40 | 14214959.21 | 0.00 | 0.181088E+10 | 0.00 | 1.38 |
June | 0.353911E+09 | 0.595831E+09 | 0.00 | 8367642.18 | 35440390.09 | 0.00 | 0.499118E+09 | 0.00 | 0.99 |
July | 58530801.37 | 0.161770E+10 | 0.00 | 1120409.02 | 0.379732E+09 | 0.00 | 45789230.14 | 0.00 | 0.92 |
August | 0.494427E+09 | 0.525165E+09 | 0.00 | 5927707.95 | 0.109145E+09 | 0.00 | 0.560207E+09 | 0.00 | 1.22 |
September | 0.708287E+09 | 0.347963E+09 | 0.00 | 8059135.95 | 43165159.00 | 0.00 | 0.932221E+09 | 0.00 | 1.23 |
October | 0.263881E+10 | 59559041.10 | 0.00 | 25405654.15 | 6769661.60 | 0.00 | 0.227057E+10 | 0.00 | 1.63 |
November | 0.504895E+10 | 0.00 | 0.00 | 18360197.66 | 0.00 | 16845189.66 | 0.180862E+10 | 0.00 | 1.51 |
December | 0.639407E+10 | 0.00 | 0.00 | 3222820.66 | 0.00 | 0.261500E+09 | 0.576967E+09 | 0.00 | 1.08 |
Annual Sum or Average | 0.328828E+11 | 0.335015E+10 | 0.00 | 0.158059E+09 | 0.600052E+09 | 0.690926E+09 | 0.176175E+11 | 0.00 | 1.33 |
Minimum of Months | 58530801.37 | 0.00 | 0.00 | 1120409.02 | 0.00 | 0.00 | 45789230.14 | 0.00 | 0.92 |
Maximum of Months | 0.639407E+10 | 0.161770E+10 | 0.00 | 34041179.04 | 0.379732E+09 | 0.261500E+09 | 0.318527E+10 | 0.00 | 1.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.366814E+10 | 0.00 | 0.00 | 40054859.16 | 0.00 | 0.365089E+09 | 0.906165E+10 | 0.00 | 1.44 |
February | 0.364676E+10 | 0.00 | 0.00 | 86975363.59 | 0.00 | 0.213053E+09 | 0.670667E+10 | 0.00 | 1.58 |
March | 0.441469E+10 | 0.00 | 0.00 | 62850045.04 | 0.00 | 85422236.22 | 0.607706E+10 | 0.00 | 1.77 |
April | 0.270292E+10 | 86761569.76 | 0.00 | 18892862.09 | 13752092.11 | 0.00 | 0.287976E+10 | 0.00 | 1.32 |
May | 0.129388E+10 | 0.233014E+09 | 0.00 | 8912572.29 | 16883055.78 | 0.00 | 0.101877E+10 | 0.00 | 0.85 |
June | 0.456695E+09 | 0.797544E+09 | 0.00 | 6608871.94 | 43672411.29 | 0.00 | 0.389893E+09 | 0.00 | 0.67 |
July | 68647793.17 | 0.203058E+10 | 0.00 | 1169902.00 | 0.368374E+09 | 0.00 | 43491832.93 | 0.00 | 0.68 |
August | 0.571801E+09 | 0.735394E+09 | 0.00 | 7799298.87 | 0.108100E+09 | 0.00 | 0.624789E+09 | 0.00 | 0.96 |
September | 0.898639E+09 | 0.538726E+09 | 0.00 | 10414121.90 | 41707170.04 | 0.00 | 0.823684E+09 | 0.00 | 0.95 |
October | 0.271479E+10 | 0.149632E+09 | 0.00 | 49561691.15 | 1072763.03 | 0.00 | 0.441399E+10 | 0.00 | 1.74 |
November | 0.401472E+10 | 0.00 | 0.00 | 96870633.77 | 0.00 | 65545676.13 | 0.814873E+10 | 0.00 | 1.96 |
December | 0.400758E+10 | 0.00 | 0.00 | 66648758.35 | 0.00 | 0.416888E+09 | 0.927229E+10 | 0.00 | 1.39 |
Annual Sum or Average | 0.284593E+11 | 0.457165E+10 | 0.00 | 0.456759E+09 | 0.593562E+09 | 0.114600E+10 | 0.494608E+11 | 0.00 | 1.27 |
Minimum of Months | 68647793.17 | 0.00 | 0.00 | 1169902.00 | 0.00 | 0.00 | 43491832.93 | 0.00 | 0.67 |
Maximum of Months | 0.441469E+10 | 0.203058E+10 | 0.00 | 96870633.77 | 0.368374E+09 | 0.416888E+09 | 0.927229E+10 | 0.00 | 1.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.714605E+10 | 0.00 | 0.00 | 9161905.52 | 0.00 | 2867153.14 | 0.238728E+10 | 0.00 | 1.56 |
February | 0.647723E+10 | 0.00 | 0.00 | 20703719.73 | 0.00 | 2786136.50 | 0.172394E+10 | 0.00 | 1.82 |
March | 0.596144E+10 | 0.00 | 0.00 | 31583155.34 | 0.00 | 780428.46 | 0.354160E+10 | 0.00 | 2.38 |
April | 0.225473E+10 | 92694892.83 | 0.00 | 23784450.32 | 8660996.35 | 0.00 | 0.373088E+10 | 0.00 | 2.18 |
May | 0.125045E+10 | 0.259851E+09 | 0.00 | 9218960.20 | 3882032.32 | 0.00 | 0.117662E+10 | 0.00 | 1.39 |
June | 0.415093E+09 | 0.937157E+09 | 0.00 | 7300324.30 | 22649890.72 | 0.00 | 0.489223E+09 | 0.00 | 1.12 |
July | 46810773.51 | 0.234536E+10 | 0.00 | 1593177.52 | 0.278249E+09 | 0.00 | 75031345.29 | 0.00 | 1.15 |
August | 0.328823E+09 | 0.796385E+09 | 0.00 | 10336644.33 | 68119140.99 | 0.00 | 0.954613E+09 | 0.00 | 1.59 |
September | 0.974212E+09 | 0.392532E+09 | 0.00 | 8025535.60 | 35370721.59 | 0.00 | 0.725981E+09 | 0.00 | 1.29 |
October | 0.380766E+10 | 0.103709E+09 | 0.00 | 18710237.78 | 1174025.00 | 0.00 | 0.201079E+10 | 0.00 | 2.01 |
November | 0.634943E+10 | 0.00 | 0.00 | 26427189.99 | 0.00 | 0.00 | 0.287818E+10 | 0.00 | 2.14 |
December | 0.685024E+10 | 0.00 | 0.00 | 20841798.73 | 0.00 | 0.00 | 0.335408E+10 | 0.00 | 1.57 |
Annual Sum or Average | 0.418622E+11 | 0.492768E+10 | 0.00 | 0.187687E+09 | 0.418106E+09 | 6433718.10 | 0.230482E+11 | 0.00 | 1.68 |
Minimum of Months | 46810773.51 | 0.00 | 0.00 | 1593177.52 | 0.00 | 0.00 | 75031345.29 | 0.00 | 1.12 |
Maximum of Months | 0.714605E+10 | 0.234536E+10 | 0.00 | 31583155.34 | 0.278249E+09 | 2867153.14 | 0.373088E+10 | 0.00 | 2.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.520525E+11 | 0.00 | 0.00 | 57732.65 | 0.00 | 0.128997E+11 | 0.306709E+09 | 0.00 | 0.68 |
February | 0.458254E+11 | 0.00 | 0.00 | 3845482.79 | 0.00 | 0.864296E+10 | 0.107743E+10 | 0.00 | 0.79 |
March | 0.478445E+11 | 0.00 | 0.00 | 24694467.62 | 0.00 | 0.606969E+10 | 0.575648E+10 | 0.00 | 0.95 |
April | 0.251741E+11 | 0.492825E+09 | 0.00 | 59821026.22 | 0.196891E+09 | 0.353367E+09 | 0.928565E+10 | 0.00 | 0.83 |
May | 0.100735E+11 | 0.222810E+10 | 0.00 | 69558539.70 | 0.169451E+09 | 0.00 | 0.752418E+10 | 0.00 | 0.72 |
June | 0.300827E+10 | 0.885176E+10 | 0.00 | 61636209.01 | 0.226298E+09 | 0.00 | 0.376930E+10 | 0.00 | 0.64 |
July | 0.329750E+09 | 0.196693E+11 | 0.00 | 10724169.94 | 0.138484E+10 | 0.00 | 0.390293E+09 | 0.00 | 0.57 |
August | 0.317935E+10 | 0.639578E+10 | 0.00 | 53967282.07 | 0.431223E+09 | 0.00 | 0.439962E+10 | 0.00 | 0.68 |
September | 0.853872E+10 | 0.315861E+10 | 0.00 | 45741908.42 | 0.634110E+09 | 0.00 | 0.327429E+10 | 0.00 | 0.64 |
October | 0.320749E+11 | 0.844752E+09 | 0.00 | 49589590.08 | 75844230.97 | 4530999.84 | 0.650742E+10 | 0.00 | 0.88 |
November | 0.502845E+11 | 0.00 | 0.00 | 3404188.90 | 0.00 | 0.579231E+10 | 0.197112E+10 | 0.00 | 0.85 |
December | 0.499185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162879E+11 | 0.00 | 0.00 | 0.65 |
Annual Sum or Average | 0.328304E+12 | 0.416411E+11 | 0.00 | 0.383041E+09 | 0.311865E+10 | 0.500505E+11 | 0.442625E+11 | 0.00 | 0.74 |
Minimum of Months | 0.329750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.520525E+11 | 0.196693E+11 | 0.00 | 69558539.70 | 0.138484E+10 | 0.162879E+11 | 0.928565E+10 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.419392E+11 | 0.00 | 0.00 | 11922856.94 | 0.00 | 0.989032E+10 | 0.379597E+10 | 0.00 | 0.90 |
February | 0.372371E+11 | 0.00 | 0.00 | 96133267.94 | 0.00 | 0.530291E+10 | 0.794327E+10 | 0.00 | 1.12 |
March | 0.337774E+11 | 0.00 | 0.00 | 0.245743E+09 | 0.00 | 0.422456E+10 | 0.226937E+11 | 0.00 | 1.49 |
April | 0.167489E+11 | 0.509918E+09 | 0.00 | 0.160470E+09 | 72114051.90 | 0.321593E+09 | 0.243286E+11 | 0.00 | 1.52 |
May | 0.803446E+10 | 0.190410E+10 | 0.00 | 0.106179E+09 | 0.161109E+09 | 0.00 | 0.149383E+11 | 0.00 | 1.34 |
June | 0.315727E+10 | 0.707569E+10 | 0.00 | 73917654.41 | 0.258958E+09 | 0.00 | 0.446396E+10 | 0.00 | 1.00 |
July | 0.365287E+09 | 0.171652E+11 | 0.00 | 9923288.73 | 0.221823E+10 | 0.00 | 0.419691E+09 | 0.00 | 0.86 |
August | 0.324864E+10 | 0.595005E+10 | 0.00 | 54783282.94 | 0.686881E+09 | 0.00 | 0.480650E+10 | 0.00 | 1.08 |
September | 0.734326E+10 | 0.355870E+10 | 0.00 | 64138997.10 | 0.528641E+09 | 0.00 | 0.693262E+10 | 0.00 | 1.17 |
October | 0.241970E+11 | 0.602506E+09 | 0.00 | 0.179110E+09 | 0.146507E+09 | 99281403.67 | 0.160033E+11 | 0.00 | 1.42 |
November | 0.407480E+11 | 0.00 | 0.00 | 0.100789E+09 | 0.00 | 0.371030E+10 | 0.932669E+10 | 0.00 | 1.23 |
December | 0.427241E+11 | 0.00 | 0.00 | 8440116.03 | 0.00 | 0.120162E+11 | 0.965322E+09 | 0.00 | 0.83 |
Annual Sum or Average | 0.259521E+12 | 0.367661E+11 | 0.00 | 0.111155E+10 | 0.407244E+10 | 0.355652E+11 | 0.116618E+12 | 0.00 | 1.16 |
Minimum of Months | 0.365287E+09 | 0.00 | 0.00 | 8440116.03 | 0.00 | 0.00 | 0.419691E+09 | 0.00 | 0.83 |
Maximum of Months | 0.427241E+11 | 0.171652E+11 | 0.00 | 0.245743E+09 | 0.221823E+10 | 0.120162E+11 | 0.243286E+11 | 0.00 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.299173E+11 | 0.00 | 0.00 | 0.385820E+09 | 0.00 | 0.876783E+10 | 0.777837E+11 | 0.00 | 1.30 |
February | 0.301267E+11 | 0.00 | 0.00 | 0.845490E+09 | 0.00 | 0.533400E+10 | 0.579707E+11 | 0.00 | 1.45 |
March | 0.366043E+11 | 0.00 | 0.00 | 0.527316E+09 | 0.00 | 0.387023E+10 | 0.506313E+11 | 0.00 | 1.59 |
April | 0.238844E+11 | 0.102431E+10 | 0.00 | 0.135576E+09 | 78965179.19 | 0.357019E+09 | 0.202888E+11 | 0.00 | 1.11 |
May | 0.120631E+11 | 0.261251E+10 | 0.00 | 71153159.13 | 0.176578E+09 | 0.00 | 0.780112E+10 | 0.00 | 0.80 |
June | 0.410234E+10 | 0.879688E+10 | 0.00 | 49731058.18 | 0.317485E+09 | 0.00 | 0.300078E+10 | 0.00 | 0.64 |
July | 0.501961E+09 | 0.189058E+11 | 0.00 | 9406150.58 | 0.284732E+10 | 0.00 | 0.283889E+09 | 0.00 | 0.59 |
August | 0.381731E+10 | 0.775032E+10 | 0.00 | 63281428.92 | 0.630504E+09 | 0.00 | 0.480053E+10 | 0.00 | 0.80 |
September | 0.812544E+10 | 0.564044E+10 | 0.00 | 89345418.86 | 0.582532E+09 | 0.00 | 0.665117E+10 | 0.00 | 0.91 |
October | 0.251987E+11 | 0.178398E+10 | 0.00 | 0.421157E+09 | 5032698.69 | 0.00 | 0.365066E+11 | 0.00 | 1.60 |
November | 0.339381E+11 | 0.00 | 0.00 | 0.907892E+09 | 0.00 | 0.287802E+10 | 0.664223E+11 | 0.00 | 1.72 |
December | 0.314969E+11 | 0.00 | 0.00 | 0.617751E+09 | 0.00 | 0.935925E+10 | 0.779187E+11 | 0.00 | 1.23 |
Annual Sum or Average | 0.239776E+12 | 0.465143E+11 | 0.00 | 0.412392E+10 | 0.463841E+10 | 0.305664E+11 | 0.410060E+12 | 0.00 | 1.14 |
Minimum of Months | 0.501961E+09 | 0.00 | 0.00 | 9406150.58 | 0.00 | 0.00 | 0.283889E+09 | 0.00 | 0.59 |
Maximum of Months | 0.366043E+11 | 0.189058E+11 | 0.00 | 0.907892E+09 | 0.284732E+10 | 0.935925E+10 | 0.779187E+11 | 0.00 | 1.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.540181E+11 | 0.00 | 0.00 | 37225431.60 | 0.00 | 0.111275E+11 | 0.100457E+11 | 0.00 | 1.23 |
February | 0.496146E+11 | 0.00 | 0.00 | 0.100446E+09 | 0.00 | 0.690808E+10 | 0.810436E+10 | 0.00 | 1.45 |
March | 0.517747E+11 | 0.00 | 0.00 | 0.149745E+09 | 0.00 | 0.325548E+10 | 0.173688E+11 | 0.00 | 1.84 |
April | 0.279699E+11 | 0.747584E+09 | 0.00 | 93289858.91 | 95116133.42 | 0.211522E+09 | 0.141086E+11 | 0.00 | 1.57 |
May | 0.130593E+11 | 0.267271E+10 | 0.00 | 59304343.42 | 61187966.64 | 0.00 | 0.640883E+10 | 0.00 | 1.23 |
June | 0.458292E+10 | 0.930034E+10 | 0.00 | 39217236.80 | 0.229064E+09 | 0.00 | 0.230005E+10 | 0.00 | 0.98 |
July | 0.523106E+09 | 0.174121E+11 | 0.00 | 7423270.86 | 0.333329E+10 | 0.00 | 0.248038E+09 | 0.00 | 0.88 |
August | 0.444390E+10 | 0.623273E+10 | 0.00 | 45733042.61 | 0.806014E+09 | 0.00 | 0.339741E+10 | 0.00 | 1.10 |
September | 0.987110E+10 | 0.310316E+10 | 0.00 | 51038670.19 | 0.962330E+09 | 0.00 | 0.373293E+10 | 0.00 | 1.13 |
October | 0.357614E+11 | 0.927717E+09 | 0.00 | 92953852.98 | 0.143506E+09 | 4056921.99 | 0.997104E+10 | 0.00 | 1.64 |
November | 0.533121E+11 | 0.00 | 0.00 | 0.105545E+09 | 0.00 | 0.487945E+10 | 0.108809E+11 | 0.00 | 1.62 |
December | 0.554604E+11 | 0.00 | 0.00 | 47812231.30 | 0.00 | 0.122572E+11 | 0.810748E+10 | 0.00 | 1.16 |
Annual Sum or Average | 0.360392E+12 | 0.403963E+11 | 0.00 | 0.829734E+09 | 0.563051E+10 | 0.386433E+11 | 0.946742E+11 | 0.00 | 1.32 |
Minimum of Months | 0.523106E+09 | 0.00 | 0.00 | 7423270.86 | 0.00 | 0.00 | 0.248038E+09 | 0.00 | 0.88 |
Maximum of Months | 0.554604E+11 | 0.174121E+11 | 0.00 | 0.149745E+09 | 0.333329E+10 | 0.122572E+11 | 0.173688E+11 | 0.00 | 1.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.499886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236981E+10 | 0.00 | 0.00 | 0.86 |
February | 0.495423E+10 | 0.00 | 0.00 | 78719.09 | 0.00 | 0.157705E+10 | 89936528.13 | 0.00 | 1.02 |
March | 0.571039E+10 | 0.00 | 0.00 | 1321717.73 | 0.00 | 0.108055E+10 | 0.623665E+09 | 0.00 | 1.20 |
April | 0.305835E+10 | 21286161.92 | 0.00 | 5410672.38 | 7877750.96 | 0.197193E+09 | 0.887754E+09 | 0.00 | 0.99 |
May | 0.112218E+10 | 92579690.09 | 0.00 | 10070957.69 | 20029634.93 | 6743719.65 | 0.795096E+09 | 0.00 | 0.79 |
June | 0.371571E+09 | 0.566679E+09 | 0.00 | 8109221.23 | 35237188.04 | 0.00 | 0.391573E+09 | 0.00 | 0.65 |
July | 44661357.62 | 0.139376E+10 | 0.00 | 2141027.74 | 0.492027E+09 | 0.00 | 40813855.10 | 0.00 | 0.59 |
August | 0.402924E+09 | 0.366673E+09 | 0.00 | 7776880.41 | 0.174970E+09 | 0.00 | 0.494899E+09 | 0.00 | 0.74 |
September | 0.866312E+09 | 0.151128E+09 | 0.00 | 6810786.82 | 0.150937E+09 | 20923161.98 | 0.323384E+09 | 0.00 | 0.72 |
October | 0.339180E+10 | 32139347.85 | 0.00 | 3765117.66 | 26448799.16 | 0.370812E+09 | 0.712773E+09 | 0.00 | 1.08 |
November | 0.534615E+10 | 0.00 | 2945.11 | 189630.95 | 6179.23 | 0.137699E+10 | 0.122128E+09 | 34084.43 | 1.10 |
December | 0.438235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282070E+10 | 0.00 | 0.00 | 0.79 |
Annual Sum or Average | 0.346498E+11 | 0.262424E+10 | 2945.11 | 45674731.70 | 0.907532E+09 | 0.982077E+10 | 0.448202E+10 | 34084.43 | 0.88 |
Minimum of Months | 44661357.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.571039E+10 | 0.139376E+10 | 2945.11 | 10070957.69 | 0.492027E+09 | 0.282070E+10 | 0.887754E+09 | 34084.43 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.464060E+10 | 0.00 | 0.00 | 3007.07 | 0.00 | 0.120478E+10 | 26609546.85 | 0.00 | 1.06 |
February | 0.421926E+10 | 0.00 | 0.00 | 1727617.33 | 0.00 | 0.740881E+09 | 0.321524E+09 | 0.00 | 1.27 |
March | 0.362988E+10 | 0.00 | 0.00 | 15857147.07 | 0.00 | 0.556666E+09 | 0.203497E+10 | 0.00 | 1.58 |
April | 0.139155E+10 | 20550098.39 | 0.00 | 14726348.15 | 3036050.30 | 86718877.71 | 0.245590E+10 | 0.00 | 1.49 |
May | 0.577852E+09 | 86918423.24 | 0.00 | 13287155.27 | 13361127.93 | 3502552.83 | 0.153860E+10 | 0.00 | 1.29 |
June | 0.255051E+09 | 0.465951E+09 | 0.00 | 9740492.92 | 23909062.82 | 0.00 | 0.495672E+09 | 0.00 | 0.97 |
July | 29960827.52 | 0.136976E+10 | 0.00 | 2063234.95 | 0.315265E+09 | 0.00 | 44878279.21 | 0.00 | 0.84 |
August | 0.280970E+09 | 0.404398E+09 | 0.00 | 8238880.02 | 99540001.99 | 0.00 | 0.543860E+09 | 0.00 | 1.07 |
September | 0.510408E+09 | 0.237473E+09 | 0.00 | 8736368.75 | 77771495.02 | 11492190.47 | 0.644073E+09 | 0.00 | 1.11 |
October | 0.205421E+10 | 24991689.01 | 0.00 | 14196046.92 | 21004540.25 | 0.224134E+09 | 0.158469E+10 | 0.00 | 1.47 |
November | 0.416705E+10 | 0.00 | 5040.46 | 3107737.16 | 4927.94 | 0.744931E+09 | 0.591452E+09 | 24490.62 | 1.39 |
December | 0.426412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147488E+10 | 0.00 | 0.00 | 0.98 |
Annual Sum or Average | 0.260209E+11 | 0.261004E+10 | 5040.46 | 91684035.62 | 0.553893E+09 | 0.504799E+10 | 0.102822E+11 | 24490.62 | 1.21 |
Minimum of Months | 29960827.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 |
Maximum of Months | 0.464060E+10 | 0.136976E+10 | 5040.46 | 15857147.07 | 0.315265E+09 | 0.147488E+10 | 0.245590E+10 | 24490.62 | 1.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.293529E+10 | 0.00 | 0.00 | 29512619.84 | 0.00 | 0.103516E+10 | 0.670450E+10 | 0.00 | 1.27 |
February | 0.293614E+10 | 0.00 | 0.00 | 65353879.10 | 0.00 | 0.759811E+09 | 0.547511E+10 | 0.00 | 1.46 |
March | 0.368096E+10 | 0.00 | 0.00 | 41209440.40 | 0.00 | 0.792478E+09 | 0.526260E+10 | 0.00 | 1.63 |
April | 0.231420E+10 | 36991292.91 | 0.00 | 13662942.82 | 3819408.06 | 0.185071E+09 | 0.228748E+10 | 0.00 | 1.16 |
May | 0.112658E+10 | 0.106225E+09 | 0.00 | 11274451.66 | 19999661.87 | 15320795.53 | 0.888695E+09 | 0.00 | 0.83 |
June | 0.406998E+09 | 0.550057E+09 | 0.00 | 7814742.60 | 47307474.44 | 0.00 | 0.359786E+09 | 0.00 | 0.65 |
July | 47860877.23 | 0.133007E+10 | 0.00 | 2208700.28 | 0.575663E+09 | 0.00 | 40456066.57 | 0.00 | 0.60 |
August | 0.381311E+09 | 0.424683E+09 | 0.00 | 10062451.81 | 0.177297E+09 | 0.00 | 0.599759E+09 | 0.00 | 0.82 |
September | 0.696868E+09 | 0.259992E+09 | 0.00 | 13678142.31 | 0.126317E+09 | 222577.12 | 0.728718E+09 | 0.00 | 0.89 |
October | 0.239608E+10 | 76211877.35 | 0.00 | 33765468.98 | 7995434.63 | 0.224753E+09 | 0.391503E+10 | 0.00 | 1.66 |
November | 0.317550E+10 | 0.00 | 6671.02 | 66154086.39 | 16860.78 | 0.778916E+09 | 0.664375E+10 | 15973.87 | 1.84 |
December | 0.289624E+10 | 0.00 | 0.00 | 45321386.97 | 0.00 | 0.115373E+10 | 0.614024E+10 | 0.00 | 1.14 |
Annual Sum or Average | 0.229940E+11 | 0.278423E+10 | 6671.02 | 0.340018E+09 | 0.958416E+09 | 0.494546E+10 | 0.390461E+11 | 15973.87 | 1.16 |
Minimum of Months | 47860877.23 | 0.00 | 0.00 | 2208700.28 | 0.00 | 0.00 | 40456066.57 | 0.00 | 0.60 |
Maximum of Months | 0.368096E+10 | 0.133007E+10 | 6671.02 | 66154086.39 | 0.575663E+09 | 0.115373E+10 | 0.670450E+10 | 15973.87 | 1.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.470503E+10 | 0.00 | 0.00 | 2903650.73 | 0.00 | 0.142948E+10 | 0.946962E+09 | 0.00 | 1.28 |
February | 0.466428E+10 | 0.00 | 0.00 | 8104181.16 | 0.00 | 0.944444E+09 | 0.815756E+09 | 0.00 | 1.55 |
March | 0.480477E+10 | 0.00 | 0.00 | 14195245.13 | 0.00 | 0.751426E+09 | 0.206527E+10 | 0.00 | 1.96 |
April | 0.261406E+10 | 27928165.40 | 0.00 | 10167170.33 | 2386984.12 | 0.139329E+09 | 0.162194E+10 | 0.00 | 1.62 |
May | 0.117290E+10 | 0.106216E+09 | 0.00 | 9982198.08 | 11812709.63 | 527503.02 | 0.718786E+09 | 0.00 | 1.22 |
June | 0.392032E+09 | 0.550130E+09 | 0.00 | 6679027.21 | 45290871.19 | 0.00 | 0.314524E+09 | 0.00 | 0.95 |
July | 46965666.69 | 0.118483E+10 | 0.00 | 1905019.22 | 0.587275E+09 | 0.00 | 33435022.00 | 0.00 | 0.86 |
August | 0.429890E+09 | 0.353934E+09 | 0.00 | 7393561.00 | 0.162403E+09 | 0.00 | 0.418556E+09 | 0.00 | 1.11 |
September | 0.786461E+09 | 0.132827E+09 | 0.00 | 7852508.24 | 0.158076E+09 | 219977.97 | 0.428173E+09 | 0.00 | 1.12 |
October | 0.323978E+10 | 35585432.13 | 0.00 | 9206273.73 | 25786880.26 | 0.132553E+09 | 0.119510E+10 | 0.00 | 1.74 |
November | 0.471770E+10 | 0.00 | 6968.91 | 10004632.23 | 16014.09 | 0.816271E+09 | 0.133898E+10 | 8842.73 | 1.76 |
December | 0.470791E+10 | 0.00 | 0.00 | 2593056.14 | 0.00 | 0.161291E+10 | 0.559293E+09 | 0.00 | 1.18 |
Annual Sum or Average | 0.322818E+11 | 0.239145E+10 | 6968.91 | 90986523.19 | 0.993048E+09 | 0.582716E+10 | 0.104568E+11 | 8842.73 | 1.36 |
Minimum of Months | 46965666.69 | 0.00 | 0.00 | 1905019.22 | 0.00 | 0.00 | 33435022.00 | 0.00 | 0.86 |
Maximum of Months | 0.480477E+10 | 0.118483E+10 | 6968.91 | 14195245.13 | 0.587275E+09 | 0.161291E+10 | 0.206527E+10 | 8842.73 | 1.96 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 9692188.47 | 0.00 | 0.00 | 0.460063E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 60269785.56 | 0.00 | 0.00 | 0.317269E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 90200860.23 | 0.00 | 0.00 | 0.302235E+09 | 0.00 | 0.30 |
April | 0.00 | 1058528.15 | 0.00 | 35877153.91 | 0.00 | 0.00 | 0.177911E+09 | 0.00 | 0.29 |
May | 0.00 | 12807580.74 | 0.00 | 3943655.18 | 0.00 | 0.00 | 0.114499E+09 | 0.00 | 0.29 |
June | 0.00 | 45022173.87 | 0.00 | 4404414.13 | 0.00 | 0.00 | 21897704.23 | 0.00 | 0.30 |
July | 0.00 | 0.197125E+09 | 0.00 | 111467.93 | 0.00 | 0.00 | 51516.47 | 0.00 | 0.28 |
August | 0.00 | 0.113558E+09 | 0.00 | 2209290.06 | 0.00 | 0.00 | 4046069.07 | 0.00 | 0.31 |
September | 0.00 | 59163632.99 | 0.00 | 2060538.62 | 0.00 | 0.00 | 54264462.16 | 0.00 | 0.29 |
October | 0.00 | 15559277.45 | 0.00 | 34084149.31 | 0.00 | 0.00 | 0.164212E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 88135980.08 | 0.00 | 0.00 | 0.272368E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 83867327.97 | 0.00 | 0.00 | 0.397086E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.444294E+09 | 0.00 | 0.414857E+09 | 0.00 | 0.00 | 0.228590E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 111467.93 | 0.00 | 0.00 | 51516.47 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.197125E+09 | 0.00 | 90200860.23 | 0.00 | 0.00 | 0.460063E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 71867861.50 | 0.00 | 0.00 | 0.462405E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 0.544282E+09 | 0.00 | 0.00 | 0.323158E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.838091E+09 | 0.00 | 0.00 | 0.308622E+10 | 0.00 | 0.30 |
April | 0.00 | 10529768.16 | 0.00 | 0.336010E+09 | 0.00 | 0.00 | 0.180278E+10 | 0.00 | 0.29 |
May | 0.00 | 0.125922E+09 | 0.00 | 35304214.14 | 0.00 | 0.00 | 0.114705E+10 | 0.00 | 0.29 |
June | 0.00 | 0.448152E+09 | 0.00 | 41938301.22 | 0.00 | 0.00 | 0.219096E+09 | 0.00 | 0.30 |
July | 0.00 | 0.196255E+10 | 0.00 | 1106642.26 | 0.00 | 0.00 | 559163.45 | 0.00 | 0.28 |
August | 0.00 | 0.112789E+10 | 0.00 | 21238188.48 | 0.00 | 0.00 | 41485715.08 | 0.00 | 0.31 |
September | 0.00 | 0.579690E+09 | 0.00 | 18082531.37 | 0.00 | 0.00 | 0.544513E+09 | 0.00 | 0.29 |
October | 0.00 | 0.153207E+09 | 0.00 | 0.310827E+09 | 0.00 | 0.00 | 0.167233E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.808735E+09 | 0.00 | 0.00 | 0.279720E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.770029E+09 | 0.00 | 0.00 | 0.403854E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.440795E+10 | 0.00 | 0.379751E+10 | 0.00 | 0.00 | 0.232054E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1106642.26 | 0.00 | 0.00 | 559163.45 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.196255E+10 | 0.00 | 0.838091E+09 | 0.00 | 0.00 | 0.462405E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 92100019.76 | 0.00 | 0.00 | 4999649.86 | 0.00 | 0.00 | 0.372673E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 47921860.88 | 0.00 | 0.00 | 0.329679E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 78445738.96 | 0.00 | 0.00 | 0.313990E+09 | 0.00 | 0.30 |
April | 0.00 | 1057036.50 | 0.00 | 32708686.44 | 0.00 | 0.00 | 0.181247E+09 | 0.00 | 0.29 |
May | 0.00 | 12729898.57 | 0.00 | 3397709.43 | 0.00 | 0.00 | 0.115103E+09 | 0.00 | 0.29 |
June | 0.00 | 44927811.96 | 0.00 | 4161269.95 | 0.00 | 0.00 | 22208532.07 | 0.00 | 0.30 |
July | 0.00 | 0.196232E+09 | 0.00 | 114154.56 | 0.00 | 0.00 | 58601.76 | 0.00 | 0.28 |
August | 0.00 | 0.111736E+09 | 0.00 | 2148877.84 | 0.00 | 0.00 | 4312291.94 | 0.00 | 0.31 |
September | 0.00 | 58269991.95 | 0.00 | 1673073.46 | 0.00 | 0.00 | 54769678.07 | 0.00 | 0.29 |
October | 0.00 | 15363067.03 | 0.00 | 28387806.45 | 0.00 | 0.00 | 0.170266E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 74287173.96 | 0.00 | 0.00 | 0.286288E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 71650659.23 | 0.00 | 0.00 | 0.409297E+09 | 0.00 | 0.28 |
Annual Sum or Average | 92100019.76 | 0.440316E+09 | 0.00 | 0.349897E+09 | 0.00 | 0.00 | 0.225989E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 114154.56 | 0.00 | 0.00 | 58601.76 | 0.00 | 0.28 |
Maximum of Months | 92100019.76 | 0.196232E+09 | 0.00 | 78445738.96 | 0.00 | 0.00 | 0.409297E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.960604E+09 | 0.00 | 0.00 | 0.425185E+12 | 0.00 | 10.63 |
February | 0.425214E+10 | 0.00 | 0.00 | 0.321335E+10 | 0.00 | 0.00 | 0.489412E+12 | 0.00 | 19.12 |
March | 0.241600E+10 | 0.00 | 0.00 | 0.598170E+10 | 0.00 | 0.00 | 0.771573E+12 | 0.00 | 34.21 |
April | 0.00 | 598662.35 | 0.00 | 0.400195E+10 | 0.00 | 0.00 | 0.716463E+12 | 0.00 | 44.61 |
May | 0.00 | 0.161591E+09 | 0.00 | 0.474087E+09 | 0.00 | 0.00 | 0.213891E+12 | 0.00 | 12.55 |
June | 51444323.99 | 0.355654E+09 | 0.00 | 0.804439E+09 | 2751701.44 | 0.00 | 0.822014E+11 | 0.00 | 9.69 |
July | 0.00 | 0.826409E+10 | 0.00 | 0.756075E+09 | 0.00 | 0.00 | 0.847995E+11 | 0.00 | 15.69 |
August | 0.00 | 0.129794E+10 | 0.00 | 0.173114E+10 | 0.00 | 0.00 | 0.204502E+12 | 0.00 | 25.13 |
September | 1224493.71 | 90128300.08 | 0.00 | 0.502757E+09 | 0.00 | 0.00 | 0.154089E+12 | 0.00 | 14.32 |
October | 0.817401E+09 | 92445963.54 | 0.00 | 0.272662E+10 | 20937917.51 | 0.00 | 0.341459E+12 | 0.00 | 24.68 |
November | 0.202822E+10 | 0.00 | 0.00 | 0.632504E+10 | 0.00 | 0.00 | 0.733670E+12 | 0.00 | 31.51 |
December | 0.00 | 0.00 | 0.00 | 0.687398E+10 | 0.00 | 0.00 | 0.105012E+13 | 0.00 | 34.40 |
Annual Sum or Average | 0.956643E+10 | 0.102624E+11 | 0.00 | 0.343518E+11 | 23689618.94 | 0.00 | 0.526737E+13 | 0.00 | 23.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.474087E+09 | 0.00 | 0.00 | 0.822014E+11 | 0.00 | 9.69 |
Maximum of Months | 0.425214E+10 | 0.826409E+10 | 0.00 | 0.687398E+10 | 20937917.51 | 0.00 | 0.105012E+13 | 0.00 | 44.61 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:38
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.498325E+12 | 0.148675E+11 | 0.00 | 0.280107E+13 | 0.245246E+12 |
February | 0.529242E+12 | 0.119914E+11 | 0.00 | 0.249726E+13 | 0.661304E+12 |
March | 0.790018E+12 | 0.131650E+11 | 0.00 | 0.307949E+13 | 0.111206E+13 |
April | 0.857262E+12 | 0.709115E+10 | 0.00 | 0.233653E+13 | 0.215838E+13 |
May | 0.919991E+12 | 0.376960E+10 | 0.00 | 0.128239E+13 | 0.211136E+13 |
June | 0.899745E+12 | -869417761.5 | 0.00 | 0.362429E+12 | 0.327413E+13 |
July | 0.864937E+12 | -0.349557E+10 | 0.00 | -0.334837E+12 | 0.371198E+13 |
August | 0.799159E+12 | -744972448.3 | 0.00 | 0.390364E+12 | 0.377932E+13 |
September | 0.729469E+12 | 0.135681E+10 | 0.00 | 0.731046E+12 | 0.221663E+13 |
October | 0.640681E+12 | 0.622650E+10 | 0.00 | 0.220029E+13 | 0.161990E+13 |
November | 0.509025E+12 | 0.119922E+11 | 0.00 | 0.309530E+13 | 0.974311E+12 |
December | 0.428323E+12 | 0.127501E+11 | 0.00 | 0.339590E+13 | 0.847288E+12 |
Annual Sum or Average | 0.846618E+13 | 0.781003E+11 | 0.00 | 0.218372E+14 | 0.227119E+14 |
Minimum of Months | 0.428323E+12 | -0.349557E+10 | 0.00 | -0.334837E+12 | 0.245246E+12 |
Maximum of Months | 0.919991E+12 | 0.148675E+11 | 0.00 | 0.339590E+13 | 0.377932E+13 |